Yaskawa V1000 Compact Current Vector Drive

We offer the Yaskawa V1000 for compact, flexible motor control across pumps, fans, conveyors, compressors and general machinery. It combines V/f control, open-loop current vector control and PM open-loop vector control, with application presets, PID, communications and parameter backup to make setup and maintenance more manageable.

Start with your supply, motor nameplate, load and enclosure requirements. The same drive can have different usable current and motor ratings under normal-duty and heavy-duty operation. We keep those ratings together with the exact model and source edition below.

Choose the model, supply and duty

The attached CIMR-VU technical manual, SIEP C71060618F, December 2016, covers these voltage and input-phase classes. Motor output is three-phase; a single-phase-input drive is not a controller for a single-phase motor.

Manual family Input class Published motor range
BA Single-phase 200 V class 0.1–3.7 kW
2A Three-phase 200 V class 0.1–18.5 kW
4A Three-phase 400 V class 0.2–18.5 kW

The November 2011 US catalogue CA.VJ.01 separately lists 200–240 V single-phase, 200–240 V three-phase and 380–480 V three-phase supplies, with horsepower schedules. Those historical US model and horsepower listings are not a current Australian stock list. We retain the catalogue's nominal HP, manual kW, rated currents and duty conditions separately; confirm the complete order code and local availability with us.

Heavy Duty (HD) generally suits constant-torque loads and lists 150% rated output current for 60 seconds. Normal Duty (ND) generally suits variable-torque loads and lists 120% for 60 seconds. Parameter C6-01 selects the duty and affects rated current, overload capacity, carrier frequency and associated motor defaults. The manual normally defaults to ND, but BA0018 is HD-only. The older catalogue places BA0018 in both columns with identical values; do not interpret that as a separate ND capability.

Size from the motor current and required overload, then account for ambient temperature, carrier frequency, altitude and mounting. Multiple induction motors require the manual's combined-current sizing and individual motor protection. Multiple synchronous motors must not share a single drive under this manual's instructions.

Enclosures and special variants

Standard and catalogue variants include NEMA Type 1, IP20/IP00 open chassis, finless, built-in C3-filter, conformal-coated, shakeproof and special 1167 Hz software versions. These are specific configurations, not features available together on every model. The catalogue's suffix substitutions and “Consult Factory” cells remain with their own schedules. Finless versions need the specified customer heat-removal arrangement; shakeproof is described for finless versions. Conformal coating does not establish a waterproof enclosure.

The V1000-4X is a separate enclosed family described for NEMA Type 4X/12 indoor use and IP66, including washdown and dust-sensitive applications. Its GAA ratings, dimensions and options remain separate. The catalogue's combined cover range and detailed 4X single-phase range disagree; use the individual model table and confirm the selected unit. The 4X specification page also retains generic NEMA1/Open Chassis ambient labels. The later manual explicitly lists −10°C to +40°C for NEMA Type 4X/IP66, but this does not replace the dedicated 4X installation manual or its model-specific requirements.

The shared catalogue also contains J1000 and VSmini. Their ratings and accessory schedules have not been assigned to V1000. Some V1000-4X and finless instructions are referenced by document number without being supplied as separate attachments; we have not invented their contents.

Control performance and applications

V/f supports general-purpose operation and multiple induction motors. Open-loop vector control provides more responsive speed and torque control after the appropriate motor setup and autotuning. PM open-loop vector supports specified SPM/IPM motors with its own restrictions and settings. The manual describes 200% starting torque at 0.5 Hz only for OLV, HD-rated induction motors of 3.7 kW or smaller; it separately lists 50% at 6 Hz for OLV/PM. These conditions must stay attached to the figures.

Manual speed-control ranges are 1:40 in V/f, 1:100 in OLV and 1:10 in OLV/PM. The stated OLV accuracy and response require the manual's tuning and test conditions. A general torque claim does not establish continuous full torque at very low speed; motor cooling, mechanical limits and the load still govern selection.

The standard manual frequency range is 0.01–400 Hz. The catalogue says 0–400 Hz and separately lists an order-specific 1167 Hz software variant. We do not extend the standard drive's limit to 1167 Hz. The default maximum output frequency is 60 Hz in the application precautions; always match speed limits to the motor and machine.

Functions include 16 preset speeds plus jog, four acceleration/deceleration settings, S-curves, three jump-frequency bands, dwell, slip and torque compensation, speed search, energy saving, over/undertorque detection, torque limiting and configurable power-loss recovery. The catalogue's “simple closed-loop speed control” relates to specific feedback arrangements; it does not make every control mode an encoder-based closed-loop vector system.

Application presets cover water supply pumps, conveyors, exhaust/HVAC fans, compressors and named special presets. Selecting a preset can alter parameters and control mode. PM operation has additional restrictions on braking, load inertia, coasting restart and holding-brake applications; these are retained in the original manual and reference notes. Confirm those restrictions before selecting PM control for transport or lifting equipment. The autotuning chapter explicitly says that autotuning cannot be performed on permanent-magnet motors; their motor code and data require the prescribed PM setup instead.

PID, inputs and communications

PID includes target and feedback selection, reverse action, feedback-loss detection, output limits, integral/derivative settings and sleep/wake control. Its behaviour depends on the selected reference and I/O functions. A loss-of-feedback setting can change whether the drive continues or stops; the feature name alone does not identify a safe process response.

The catalogue lists seven multifunction digital inputs, a programmable relay and two open-collector outputs, analogue monitoring and pulse I/O. Control logic supports NPN/PNP arrangements under the complete terminal instructions. A1 and A2 can accept voltage references; current input uses A2, with the required switch and parameter settings. The manual warns that assigning both A1 and A2 as frequency references adds their values. Do not infer independent selection from the presence of two inputs.

MEMOBUS/Modbus over RS-485/RS-422 is built in. The manual specifies up to 115.2 kbps and retains address, parity, timeout, command sequencing, register and error-code tables. Termination applies at the network ends. The configuration prose refers to 255 slaves, while the communication-specification table lists a maximum of 31 drives. We flag that difference rather than promising a 255-drive installation. Register read/write permissions, Enter-command behaviour and parameter persistence are distinct; do not write unused or reserved addresses. The catalogue's pulse-input limit of 33 kHz differs from the manual's 32 kHz specification and is flagged.

DeviceNet, EtherNet/IP, PROFINET, Profibus-DP, Modbus TCP/IP and MECHATROLINK-II are documented options with their own compatibility requirements. The RJ45-style operator connection is not assumed to be Ethernet. Catalogue software prerequisites include 1010 for SI-P3/V, 1012 for SI-N3/V, SI-EN3/V and SI-EP3/V, 1015 for SI-EM3/V, and 1016 for SI-T3/V. The 4X option list is narrower; confirm its interface and enclosure compatibility rather than transferring the standard-drive list wholesale.

Installation, dimensions and derating

Install vertically in a suitable indoor environment. The manual lists −10°C to +40°C for NEMA Type 1 and −10°C to +50°C for open-chassis/finless versions, with appropriate heat removal. Non-condensing humidity is limited to 95% RH. Storage is listed as −20°C to +60°C, with the specification section qualifying short-term transport. Protect against contamination, sunlight, corrosive materials and excessive vibration.

Standard ratings apply to 1,000 m altitude. Above that, the manual specifies 1% reduction in input voltage and rated output current per 100 m, up to 3,000 m. Carrier-frequency and temperature/mounting derating use the original curves and model tables. We have not interpolated missing curve values. Set the installation/ambient parameters for the actual arrangement; software settings do not provide missing panel cooling.

The standard spacing figure calls for 30 mm side clearance and 100 mm above/below. Compact side-by-side installation is separately illustrated at 2 mm between adjacent drives, with derating, top-cover and L8-35 conditions. This is not permission to remove all installation clearances.

Dimensions, weights, mounting holes and drawing suffixes remain with each source table. The catalogue uses inches in some tables and mm(in) in others, while thread labels such as M5 are not inch measurements. Summary tables and drawings sometimes differ; use the approved outline for the exact enclosure and model before machining or installation.

Braking, protection and Safe Disable

V1000 has a built-in braking transistor, but resistor selection and permissible duty remain application-specific. The catalogue's 3% and 10% duty resistor schedules use a 100-second interval. Higher duty requires supplier selection. Braking resistors need the specified thermal protection and interlock; a parameter setting does not protect every resistor type. PM braking and stall-prevention options have additional restrictions.

Protection functions include motor/drive overload, over/undervoltage, overcurrent, phase-loss and temperature functions, with configurable fault, restart and stopping responses. Some ground-fault conditions are expressly outside the drive's protection. For multiple motors, the manual requires individual thermal overload protection and disables the drive's single-motor electronic overload model.

The later manual describes Safe Disable / Safe Torque Off, with historical Cat.3/PL d and SIL2 claims under its stated standards and conditions. This switches off torque-producing output; it does not electrically isolate the drive, hold a vertical load or make an external brake a safety component. Baseblock is not the same function. PM motors can still move under the documented transistor-fault scenario, and gravity can move the load.

A qualified designer must assess and validate the complete machine safety system using the full manual, applicable requirements and the selected drive. The manual requires validation after wiring, startup, replacement and maintenance, with records retained, and states that drives with safety-related functions need replacement after ten years of use. We preserve these source conditions without claiming current certification or approval of a particular installation.

Setup, backup and maintenance

Commissioning includes the correct motor data, control mode, run/reference sources, duty, protection, applicable autotuning and no-load/loaded checks. Initialisation, application presets, LOCAL/REMOTE changes and fault recovery can alter behaviour or cause unexpected movement. The guide is a selection and reference resource; use the complete manual for qualified installation and commissioning.

The removable terminal board stores parameters and can help with drive replacement. It is not an unrestricted swap between different capacities or voltage classes: the manual calls for reinitialisation in those cases and describes the oPE04 handling sequence. JVOP-181 can read, copy and verify settings between compatible drives; DriveWizard Plus supports parameter storage, monitoring and graphing. Confirm software compatibility before applying a backup.

Maintenance monitors cover fans, capacitors, inrush circuits and IGBTs. Estimated component life depends on the stated environment, load and operating hours. The website's “28 years MTBF” and “1 in 10,000 failure rate” are historical promotional claims, not a service-life warranty or replacement interval. The manual's safety-related replacement condition is separate.

Service work requires isolation, discharge verification and the complete warnings. The manual specifies waiting at least five minutes after indicators are off and measuring the DC bus before service; the warning label and full procedure still apply. PM back-generated voltage and external supplies must also be considered. Cooling-fan replacement requires the heatsink to cool; software stop is not isolation.

Accessories and source editions

Model-specific options include 3%/5% reactors, C1/C3 EMC filters, braking resistors, DIN kits, V7 adapter plates, external-heatsink kits, 24 V control-power units with their required brackets, remote operators and operator mounting kits. JVOP-180 requires catalogue software 1012 or later; JVOP-182 requires 1016 or later. A 24 V control-power option maintains controls/communications; it does not power the motor.

The catalogue's C1-filter heading includes an explicit C2 exception for certain larger 200 V models. EMC outcomes also depend on the specified filter, wiring, shielding, grounding and installation; the drive alone does not establish a compliant system. The website/catalogue quote 30 kA SCCR, while the manual’s UL section states 31,000 RMS symmetrical amperes under its voltage and protection conditions. We retain both source statements and require confirmation of the selected model and protective devices. Historical listing claims do not establish current certification.

DriveWorksEZ provides function-block customisation, but its standard/pro descriptions differ between catalogue sections: the standard V1000 section lists 118 basic blocks, while the 4X section lists 119 and different training/access wording. We retain that difference and do not promise current licensing, training or download access.

The source references below retain rating, variant, dimension, accessory, parameter, default, diagnostic and register tables with their conditions. Repeated manual chunk overlap is removed; different source editions remain distinct. Full drawings, curves and procedures stay in the linked PDFs. Tell us the exact model, motor, supply, duty, enclosure, environment, communications and braking needs so we can confirm the configuration.

Catalogue — V1000 description and specifications — page 25

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Control:V/f,OpenLoopCurrentVector,PMOpenLoopCurrentVector andsimpleclosed-loopspeedcontrol. DCinjectionbraking/rampstop;electronicreversing;infinitelyadjustableV/Hzpattern;adjustablebrakingamplitude/duration/currentlimit;full-rangeautotorqueboost;speedsearch;autorestart;slipcompensation;energy-savingfunction;enhancedPIDwithfeedbackloss.

LEDstatusdisplay,remotemountkeypad,RJ-45styledigitaloperatorconnector;signal-followerbias/gain;coolingfancontrolledbyrun/stop;UL-recognizedelectronicoverload;built-indynamicbrakingtransistor;applicationpresets;maintenancemonitors.

Protection:currentlimit/stallpreventionduringaccel/decel/run;motoranddriveoverload;overvoltageprevention;instantaneousovercurrent;shortcircuit;undervoltage;heatsinkoverheat;groundfault;over/undertorque.

Side-by-sidemounting. Short-circuitcurrentrating30kArms symmetrical.

Context: Standards,MTBF,safety/category andlisting statements are historical supplierclaims, not independent compliance/certificatevalidation.

Table conditions: Sourcepage family-specific. Footnote1=V/fmode,2=OpenLoopCurrentVectorMode; preserve rating/duty distinctions. Analogresolution0.06/60Hz retained literally.

Table conditions: Printeddesignfeatures; do not infer availability from historicalcatalogue.

Table conditions: Exactprinted enclosure labels retained;4Xpage ambiguity flagged. No expanded environmentalrating inferred.

Table conditions: Historical source claims only; no current regulatoryapproval orcertificatevalidity assertion.

Table conditions: Option listing; compatibility requires source/factory confirmation. Detailed option tables are retained in their relevant sections.

Performance specifications — PDF page 25

Source label/context Source value
Ratings /200–240VAC1phase 1/8 to5HP
Ratings /200–240VAC3phase 1/8 to25HP(ND)
Ratings /380–480VAC3phase 1/2 to25HP(ND)
Heavy Duty overload 150% for60sec
Normal Duty overload 120% for60sec
Acceleration/deceleration 0.01 to6000seconds
Controlled speed range /V/fMode 40:1
Controlled speed range /OpenLoopCurrentVectorMode 100:1
Speed regulation /V/fMode withslipcompensation ±0.5 to1%
Speed regulation /OpenLoopCurrentVectorMode ±0.2%
Displacement power factor 0.98
Output frequency 0 to400Hz
Frequency resolution /digitalreference 0.01Hz
Frequency resolution /analogreference 0.06 /60Hz
Frequency accuracy /digitalcommand 0.01%
Frequency accuracy /analogcommand 0.5%
Power loss ride-through 0.5sec
Critical frequency rejection settings 3

Design specifications — PDF page 25

Source label/context Source value
Processors Dualmicroprocessorlogic
Keypad Digitaloperator,5digits
Digital inputs 7multifunction
Digital outputs 3multifunction
Hardwire baseblock EN954-1Cat.3
Programmable FormCcontact 1A at250VAC or30VDC
Control logic 24VDC;PNPorNPN sourcing/sinking compatible
Carrier frequency 15kHzmaximum;swingPWM
Speed settings 16multi-speed plusjog
Remote speed references 2;0–10VDC(20kohms) orisolated4–20mA(250ohms)
Open collector outputs 2programmable
Analog monitor 0–10VDC proportional tooutputfrequency oroutputcurrent
Parameters andmonitors Approximately400
Pulse traininput 33kHzmaximum
Communication RS-422/485Modbus115kbps
MTBF 28years
Enclosure NEMA1

Service conditions — PDF page 25

Source label/context Source value
Ambient service /NEMA1 −10 to40°C(+14 to104°F)
Ambient service /OpenChassis −10 to50°C(+14 to122°F)
Ambient storage −20 to60°C(−4 to140°F)
Humidity to95%,non-condensing
Altitude to3300ft;higherbyderating
Service factor 1.0
Inputvoltage tolerance −15% to+10%;200–240VAC,380–480VAC
Inputfrequency ±5%;50/60Hz
Inputphase sequence Insensitive

Printed standards and claims — PDF page 25

Source label/context Source value
UL 508C(PowerConversion)
CSA 22.2No.14-95(IndustrialControlEquipment)
Listings/marking UL,cULlisted;CEmarked
RoHS Compliant
LVD EN50178
EMC EN50081-2,EN50082-2
Safety EN954-1,Category3
OtherEN EN61800-3
IEC 529,146
FCC CFR47Part15SubpartB;withExternalFilter
TUV Printed claim

Listed options — PDF page 25

Source label/context Source value
1 Externaldynamicbrakingresistor
2 MultilingualfulltextremoteLCDwithcopy
3 Profibus-DP
4 DeviceNet
5 ModbusTCP/IP
6 EtherNet/IP
7 MECHATROLINK-II
8 DriveWizardPlus
9 CASEsoftware
10 DINrailmountingkit
11 USBCopyUnit(Y-Stick)
12 Reactors3%and5%
13 EMCfiltersC1andC3
14 Adapterplates
15 Externalheatsinkkits
16 24Vcontrolpowerunit
17 RemoteLEDoperator
18 RemoteLCDoperator
19 120Vinterface

Catalogue — V1000 standard drive ratings — page 27

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: Sourcepage ratings kept separate fromdimensionandvariantpages; discrepancies retained.

Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HPbasedon230/460V,NEMAB4poleinductionmotors;NECtable430.250. Typicallyinstock statement historical.

Standard drives — PDF page 27

Rated input voltage/phase Model suffix (CIMR-VU) ND output A ND nominal HP HD output A HD nominal HP
200-240V 1-Phase BA0001FAA 1.2 1/8 & 1/4 0.8 1/8
200-240V 1-Phase BA0002FAA 1.9 1/4 1.6 1/4
200-240V 1-Phase BA0003FAA 3.3 1/2 & 3/4 3.0 1/2
200-240V 1-Phase BA0006FAA 6.0 1 5.0 3/4 & 1
200-240V 1-Phase BA0010FAA 9.6 2 & 3 8.0 2
200-240V 1-Phase BA0012FAA 12.0 3 11.0 3
200-240V 1-Phase BA0018FAA 17.5 5 17.5 5
200-240V 3-Phase 2A0001FAA 1.2 1/8 & 1/4 0.8 1/8
200-240V 3-Phase 2A0002FAA 1.9 1/4 1.6 1/4
200-240V 3-Phase 2A0004FAA 3.5 1/2 & 3/4 3.0 1/2
200-240V 3-Phase 2A0006FAA 6.0 1 5.0 3/4 & 1
200-240V 3-Phase 2A0010FAA 9.6 2 & 3 8.0 2
200-240V 3-Phase 2A0012FAA 12.0 3 11 3
200-240V 3-Phase 2A0020FAA 19.6 5 17.5 5
200-240V 3-Phase 2A0030FAA 30.0 7.5 & 10 25.0 7.5
200-240V 3-Phase 2A0040FAA 40.0 10 33.0 10
200-240V 3-Phase 2A0056FAA 56.0 15 & 20 47.0 15
200-240V 3-Phase 2A0069FAA 69.0 25 60.0 20
380-480V 3-Phase 4A0001FAA 1.2 1/2 1.2 1/2
380-480V 3-Phase 4A0002FAA 2.1 3/4 & 1 1.8 3/4
380-480V 3-Phase 4A0004FAA 4.1 2 3.4 1 & 2
380-480V 3-Phase 4A0005FAA 5.4 3 4.8 3
380-480V 3-Phase 4A0007FAA 6.9 4 5.5 3
380-480V 3-Phase 4A0009FAA 8.8 5 7.2 4
380-480V 3-Phase 4A0011FAA 11.1 7.5 9.2 5
380-480V 3-Phase 4A0018FAA 17.5 10 14.8 7.5 & 10
380-480V 3-Phase 4A0023FAA 23.0 15 18.0 10
380-480V 3-Phase 4A0031FAA 31.0 20 24.0 15
380-480V 3-Phase 4A0038FAA 38.0 25 31.0 20

Catalogue — V1000 Finless, Open, C3filter variants — page 28

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Finless(flatheatsink) intendedforcustomer enclosurewithexternalheatsink;replaceFAAwithJAA(orLAA).

Openchassis intendedforcustomer enclosure;BAA=IP20,AAA=IP00;replaceFAAwithBAA(orAAA).

C3filter builtin;replaceFAAwithEAA. Text refers toEMCC3filters onprintedpage29; thatpage is adimensiondrawing inthiscatalogue, so cross-reference flagged.

Context: ConsultFactory is explicitsourcecontent with physicalmergedcellscope, not missing modelnumber or zero.

Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HP:NEMAB4pole,NEC430.150. Allvariantdrives16weekleadtimeunlessforecastprovided; historicalonly. Consultfactory foroptioncompatibility. Differentvoltageclasslabels200V/400V retained.

Variant availability and ratings — PDF page 28

Ratedinputvoltage/phase NDoutputA NDnominalHP HDoutputA HDnominalHP Finless model suffix (CIMR-VU) Open model suffix (CIMR-VU) C3filter model suffix (CIMR-VU)
200V, 1-Phase 1.2 1/8 & 1/4 0.8 1/8 BA0001JAA BA0001BAA BA0001EAA
200V, 1-Phase 1.9 1/4 1.6 1/4 BA0002JAA BA0002BAA BA0002EAA
200V, 1-Phase 3.3 1/2 & 3/4 3.0 1/2 BA0003JAA BA0003BAA BA0003EAA
200V, 1-Phase 6.0 1 5.0 3/4 & 1 BA0006JAA BA0006BAA BA0006EAA
200V, 1-Phase 9.6 2 & 3 8.0 2 BA0010JAA BA0010BAA BA0010EAA
200V, 1-Phase 12.0 3 11.0 3 BA0012JAA BA0012BAA BA0012EAA
200V, 1-Phase 17.5 5 17.5 5 Consult Factory BA0018BAA Consult Factory
200V, 3-Phase 1.2 1/8 & 1/4 0.8 1/8 2A0001JAA 2A0001BAA Consult Factory
200V, 3-Phase 1.9 1/4 1.6 1/4 2A0002JAA 2A0002BAA Consult Factory
200V, 3-Phase 3.5 1/2 & 3/4 3.0 1/2 2A0004JAA 2A0004BAA Consult Factory
200V, 3-Phase 6.0 1 5.0 3/4 & 1 2A0006JAA 2A0006BAA Consult Factory
200V, 3-Phase 9.6 2 & 3 8.0 2 2A0010JAA 2A0010BAA Consult Factory
200V, 3-Phase 12.0 3 11.0 3 2A0012JAA 2A0012BAA Consult Factory
200V, 3-Phase 19.6 5 17.5 5 2A0020JAA 2A0020BAA Consult Factory
200V, 3-Phase 30.0 7.5 & 10 25.0 7.5 2A0030JAA 2A0030AAA Consult Factory
200V, 3-Phase 40.0 10 33.0 10 2A0040JAA 2A0040AAA Consult Factory
200V, 3-Phase 56.0 20 47.0 15 2A0056JAA 2A0056AAA Consult Factory
200V, 3-Phase 69.0 25 60.0 20 2A0069LAA 2A0069AAA Consult Factory
400V, 3-Phase 1.2 1/2 1.2 1/2 4A0001JAA 4A0001BAA 4A0001EAA
400V, 3-Phase 2.1 3/4 & 1 1.8 3/4 4A0002JAA 4A0002BAA 4A0002EAA
400V, 3-Phase 4.1 2 3.4 1 & 2 4A0004JAA 4A0004BAA 4A0004EAA
400V, 3-Phase 5.4 3 4.8 3 4A0005JAA 4A0005BAA 4A0005EAA
400V, 3-Phase 6.9 4 5.5 3 4A0007JAA 4A0007BAA 4A0007EAA
400V, 3-Phase 8.8 5 7.2 4 4A0009JAA 4A0009BAA 4A0009EAA
400V, 3-Phase 11.1 7.5 9.2 5 4A0011JAA 4A0011BAA 4A0011EAA
400V, 3-Phase 18.0 10 15.0 7.5 & 10 4A0018JAA 4A0018AAA Consult Factory
400V, 3-Phase 23.0 15 18.0 10 4A0023JAA 4A0023AAA Consult Factory
400V, 3-Phase 31.0 20 25.8 15 4A0031JAA 4A0031AAA Consult Factory
400V, 3-Phase 38.0 25 31.7 20 4A0038JAA 4A0038AAA Consult Factory

Catalogue — V1000 Conformalcoat, Shakeproof, 1167Hz variants — page 29

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Conformalcoat:Humiseal circuitboards forhumidity/dustresistance;openchassisonly;FAA→BMA(orAMA).

Shakeproof:strengthenedcomponentsforvibrationresistance;finlessversiononly;FAA→JSA.

1167Hzsoftware permitsoutputupto1167Hz;deleteCIMR-prefixandadd-134. Printedcolumn prefixVU is distinctfromCIMR-VU.

Context: ConsultFactory is explicitsourcecontent with physicalmergedcellscope, not missing modelnumber or zero.

Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HP:NEMAB4pole,NEC430.150. Allvariantdrives16weekleadtimeunlessforecastprovided; historicalonly. Consultfactory foroptioncompatibility. Differentvoltageclasslabels200V/400V retained.

Variant availability and ratings — PDF page 29

Ratedinputvoltage/phase NDoutputA NDnominalHP HDoutputA HDnominalHP Conformalcoat model suffix (CIMR-VU) Shakeproof model suffix (CIMR-VU) 1167Hz model suffix (VU)
200V, 1-Phase 1.2 1/8 & 1/4 0.8 1/8 Consult Factory Consult Factory BA0001FAA-134
200V, 1-Phase 1.9 1/4 1.6 1/4 Consult Factory Consult Factory BA0002FAA-134
200V, 1-Phase 3.3 1/2 & 3/4 3.0 1/2 Consult Factory Consult Factory BA0003FAA-134
200V, 1-Phase 6.0 1 5.0 3/4 & 1 Consult Factory Consult Factory BA0006FAA-134
200V, 1-Phase 9.6 2 & 3 8.0 2 Consult Factory BA00100JSA BA0010FAA-134
200V, 1-Phase 12.0 3 11.0 3 Consult Factory Consult Factory BA0012FAA-134
200V, 1-Phase 17.5 5 17.5 5 Consult Factory Consult Factory BA0018FAA-134
200V, 3-Phase 1.2 1/8 & 1/4 0.8 1/8 Consult Factory Consult Factory 2A0001FAA-134
200V, 3-Phase 1.9 1/4 1.6 1/4 2A0002BMA Consult Factory 2A0002FAA-134
200V, 3-Phase 3.5 1/2 & 3/4 3.0 1/2 2A0004BMA Consult Factory 2A0004FAA-134
200V, 3-Phase 6.0 1 5.0 3/4 & 1 2A0006BMA 2A0006JSA 2A0006FAA-134
200V, 3-Phase 9.6 2 & 3 8.0 2 2A0010BMA 2A0010JSA 2A0010FAA-134
200V, 3-Phase 12.0 3 11.0 3 2A0012BMA 2A0012JSA 2A0012FAA-134
200V, 3-Phase 19.6 5 17.5 5 2A0020BMA 2A0020JSA 2A0020FAA-134
200V, 3-Phase 30.0 7.5 & 10 25.0 7.5 2A0030BMA 2A0030JSA 2A0030FAA-134
200V, 3-Phase 40.0 10 33.0 10 2A0040BMA Consult Factory 2A0040FAA-134
200V, 3-Phase 56.0 20 47.0 15 Consult Factory Consult Factory 2A0056FAA-134
200V, 3-Phase 69.0 25 60.0 20 Consult Factory Consult Factory 2A0069FAA-134
400V, 3-Phase 1.2 1/2 1.2 1/2 Consult Factory Consult Factory 4A0001FAA-134
400V, 3-Phase 2.1 3/4 & 1 1.8 3/4 4A0002BMA Consult Factory 4A0002FAA-134
400V, 3-Phase 4.1 2 3.4 1 & 2 4A0004BMA 4A0004JSA 4A0004FAA-134
400V, 3-Phase 5.4 3 4.8 3 4A0005BMA 4A0005JSA 4A0005FAA-134
400V, 3-Phase 6.9 4 5.5 3 4A0007BMA 4A0007JSA 4A0007FAA-134
400V, 3-Phase 8.8 5 7.2 4 4A0009BMA 4A0009JSA 4A0009FAA-134
400V, 3-Phase 11.1 7.5 9.2 5 4A0011BMA 4A0011JSA 4A0011FAA-134
400V, 3-Phase 18.0 10 15.0 7.5 & 10 4A0018AMA Consult Factory 4A0018FAA-134
400V, 3-Phase 23.0 15 18.0 10 4A0023AMA Consult Factory 4A0023FAA-134
400V, 3-Phase 31.0 20 25.8 15 Consult Factory Consult Factory 4A0031FAA-134
400V, 3-Phase 38.0 25 31.7 20 Consult Factory Consult Factory 4A0038FAA-134

Catalogue — V1000 summary dimensions and data — page 30

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: Sourcewildcard__A retained; do not turn it into aconcreteordercode. Summaryratings/dimensions differ fromotherpages andremainseparate.

Table conditions: Physicaldimensions heading(in.); mountingheadingdoesnotrepeatunit. Weightisdriveweight,notshipping. PreserveDD.V1K.FR_ source reference distinct fromDD.V1000 drawingtitles.

Summary dimensions and data — PDF page 30

Ratedinputvoltage/phase Printedmodel(CIMR-VU) NDoutputA NDnominalHP HDoutputA HDnominalHP H in W in D in H1 mounting (source unit not repeated) W1 mounting (source unit not repeated) Driveweight lb Drawingnumber suffix DD.V1K.FR_
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 0.8 1/8 5.89 2.68 2.99 5.10 2.20 1.8 1
200-240V 1-Phase BA0002__A 1.9 1/4 1.6 1/4 5.89 2.68 2.99 5.10 2.20 1.8 1
200-240V 1-Phase BA0003__A 3.3 1/2 & 3/4 3.0 1/2 5.89 2.68 4.65 5.10 2.20 2.6 3
200-240V 1-Phase BA0006__A 6.0 1 5.0 3/4 & 1 5.89 4.25 5.41 5.10 3.78 4.2 8
200-240V 1-Phase BA0010__A 9.6 2 & 3 8.0 2 5.89 4.25 6.06 5.10 3.78 4.4 10
200-240V 1-Phase BA0012__A 12.0 3 11.0 3 6.02 5.51 6.42 5.24 5.04 5.7 12
200-240V 1-Phase BA0018__A 17.5 5 17.5 5 6.02 6.69 7.09 5.24 6.22 6.6 13
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 0.8 1/8 5.89 2.68 2.99 5.10 2.20 1.8 1
200-240V 3-Phase 2A0002__A 1.9 1/4 1.6 1/4 5.89 2.68 2.99 5.10 2.20 1.8 1
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 3 1/2 5.89 2.68 4.25 5.10 2.20 2.4 2
200-240V 3-Phase 2A0006__A 6.0 1 5 3/4 & 1 5.89 2.68 5.04 5.10 2.20 2.9 4
200-240V 3-Phase 2A0010__A 9.6 2 & 3 8 2 5.89 4.25 5.08 5.10 3.78 4.2 7
200-240V 3-Phase 2A0012__A 12.0 3 11 3 5.89 4.25 5.41 5.10 3.78 4.2 8
200-240V 3-Phase 2A0020__A 19.6 5 17.5 5 6.02 5.51 5.63 5.24 5.04 5.7 11
200-240V 3-Phase 2A0030__A 30.0 7.5 & 10 25.0 7.5 10.00 5.51 5.51 9.76 4.80 8.4 14
200-240V 3-Phase 2A0040__A 40.0 10 33.0 10 10.00 5.51 5.51 9.76 4.80 8.4 14
200-240V 3-Phase 2A0056__A 56.0 20 47.0 15 11.42 7.09 6.42 11.18 6.30 12.1 16
200-240V 3-Phase 2A0069__A 69.0 25 57.5 20 14.09 8.66 7.36 13.23 7.56 20.2 17
380-480V 3-Phase 4A0001__A 1.2 1/2 1.2 1/2 5.89 4.25 3.19 5.10 3.78 2.6 5
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 1.8 3/4 5.89 4.25 3.90 5.10 3.78 3.1 6
380-480V 3-Phase 4A0004__A 4.1 2 3.4 1 & 2 5.89 4.25 5.41 5.10 3.78 3.5 8
380-480V 3-Phase 4A0005__A 5.4 3 4.8 3 5.89 4.25 6.06 5.10 3.78 4.2 9
380-480V 3-Phase 4A0007__A 6.9 4 5.5 3 5.89 4.25 6.06 5.10 3.78 4.2 9
380-480V 3-Phase 4A0009__A 8.8 5 7.2 4 5.89 4.25 6.06 5.10 3.78 4.2 9
380-480V 3-Phase 4A0011__A 11.1 7.5 9.2 5 6.02 5.51 5.63 5.24 5.04 5.7 11
380-480V 3-Phase 4A0018__A 18.0 10 15.0 7.5 & 10 10.00 5.51 5.51 9.21 4.80 8.4 14
380-480V 3-Phase 4A0023__A 24.0 15 19.2 10 10.00 5.51 5.51 9.21 4.80 8.4 14
380-480V 3-Phase 4A0031__A 31.0 20 25.8 15 11.42 7.09 5.63 10.63 6.30 11.4 15
380-480V 3-Phase 4A0038__A 38.0 25 31.7 20 11.42 7.09 6.42 10.63 6.30 12.1 16

Catalogue — DD.V1000.01 NEMA1 dimension drawing — page 31

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: Onlylabelledtabularvalues andexplicitcallouts normalized; geometry/orientation staysinoriginal. ShortmodelsuffixF preserved independentlyofFAA/__A elsewhere.

Table conditions: PrintedDD.V1000.01; sourceall dimensionheaders(in) butd=M5threadnotation not aninchvalue. Do not reconcile differences withsummary byassumption.

Table conditions: Literaldiagramcallout; no inferredholegeometry ormountingprocedure.

NEMA1 drawing dimension table — PDF page 31

Voltageclass Model(CIMR-VU) W1 in H2 in W in H1 in D in t1 in H5 in D1 in H in H4 in H3 in H6 in Weight lb
Single-Phase200V Class BA0001F 2.20 4.65 2.68 5.03 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 1.8
Single-Phase200V Class BA0002F 2.20 4.65 2.68 5.03 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 1.8
Single-Phase200V Class BA0003F 2.20 4.65 2.68 5.03 4.65 0.20 0.20 1.54 5.89 0.79 0.16 0.06 2.6
Three-Phase200V Class 2A0001F 2.20 4.65 2.68 5.03 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 1.8
Three-Phase200V Class 2A0002F 2.20 4.65 2.68 5.03 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 1.8
Three-Phase200V Class 2A0004F 2.20 4.65 2.68 5.03 4.25 0.20 0.20 1.54 5.89 0.79 0.16 0.06 2.4
Three-Phase200V Class 2A0006F 2.20 4.65 2.68 5.03 5.04 0.20 0.20 2.32 5.89 0.79 0.16 0.06 2.9

Explicit mounting callout — PDF page 31

Source label/context Source value
Mounting 2-M4

Catalogue — DD.V1000.02 NEMA1 dimension drawing — page 32

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: Onlylabelledtabularvalues andexplicitcallouts normalized; geometry/orientation staysinoriginal. ShortmodelsuffixF preserved independentlyofFAA/__A elsewhere.

Table conditions: PrintedDD.V1000.02; sourceall dimensionheaders(in) butd=M5threadnotation not aninchvalue. Do not reconcile differences withsummary byassumption.

Table conditions: Literaldiagramcallout; no inferredholegeometry ormountingprocedure.

NEMA1 drawing dimension table — PDF page 32

Voltageclass Model(CIMR-VU) W1 in H2 in W in H1 in D in t1 in H5 in D1 in H in H4 in H3 in H6 in Weight lb
Single-Phase200V Class BA0006F 3.78 4.65 4.25 5.03 5.41 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.2
Single-Phase200V Class BA0010F 3.78 4.65 4.25 5.03 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.4
Single-Phase200V Class BA0012F 5.04 4.65 5.51 5.03 6.42 0.20 0.20 2.56 6.02 0.79 0.19 0.20 5.7
Single-Phase200V Class BA0018F 6.22 4.64 6.69 5.23 7.08 0.20 0.20 2.56 6.73 1.50 0.19 0.20 7.3
Three-Phase200V Class 2A0010F 3.78 4.65 4.25 5.03 5.08 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.2
Three-Phase200V Class 2A0012F 3.78 4.65 4.25 5.03 5.41 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.2
Three-Phase200V Class 2A0020F 5.04 4.65 5.51 5.03 5.63 0.20 0.20 2.56 6.02 0.79 0.19 0.20 5.7
Three-Phase400V Class 4A0001F 3.78 4.65 4.25 5.03 3.19 0.20 0.20 0.39 5.89 0.79 0.16 0.06 2.6
Three-Phase400V Class 4A0002F 3.78 4.65 4.25 5.03 3.90 0.20 0.20 1.10 5.89 0.79 0.16 0.06 3.1
Three-Phase400V Class 4A0004F 3.78 4.65 4.25 5.03 5.41 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.2
Three-Phase400V Class 4A0005F 3.78 4.65 4.25 5.03 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.2
Three-Phase400V Class 4A0007F 3.78 4.65 4.25 5.03 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.2
Three-Phase400V Class 4A0009F 3.78 4.65 4.25 5.03 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 4.2
Three-Phase400V Class 4A0011F 5.04 4.65 5.51 5.03 5.63 0.20 0.20 2.56 6.02 0.79 0.19 0.20 5.7

Explicit mounting callout — PDF page 32

Source label/context Source value
Mounting 4-M4

Catalogue — DD.V1000.03 NEMA1 dimension drawing — page 33

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: Onlylabelledtabularvalues andexplicitcallouts normalized; geometry/orientation staysinoriginal. ShortmodelsuffixF preserved independentlyofFAA/__A elsewhere.

Table conditions: PrintedDD.V1000.03; sourceall dimensionheaders(in) butd=M5threadnotation not aninchvalue. Do not reconcile differences withsummary byassumption.

Table conditions: Literaldiagramcallout; no inferredholegeometry ormountingprocedure.

NEMA1 drawing dimension table — PDF page 33

Voltageclass Model(CIMR-VU) W1 in H2 in W in H1 in D in t1 in H5 in D1 in H in H4 in H3 in H6 in d threaddesignation Weight lb
Three-Phase200V Class 2A0030F 4.80 9.76 5.51 9.21 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 M5 8.4
Three-Phase200V Class 2A0040F 4.80 9.76 5.51 9.21 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 M5 8.4
Three-Phase200V Class 2A0056F 6.30 11.18 7.09 10.63 6.42 0.20 0.51 2.95 11.42 0.59 0.24 0.06 M5 12.1
Three-Phase200V Class 2A0069F 7.56 13.23 8.66 12.60 7.36 0.20 0.87 3.07 13.78 0.59 0.28 0.06 M5 20.3
Three-Phase400V Class 4A0018F 4.80 9.76 5.51 9.21 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 M5 8.4
Three-Phase400V Class 4A0023F 4.80 9.76 5.51 9.21 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 M5 8.4
Three-Phase400V Class 4A0031F 6.30 11.18 7.09 10.63 5.63 0.20 0.51 2.17 11.42 0.59 0.24 0.06 M5 11.5
Three-Phase400V Class 4A0038F 6.30 11.18 7.09 10.63 6.42 0.20 0.51 2.95 11.42 0.51 0.24 0.06 M5 12.1

Explicit mounting callout — PDF page 33

Source label/context Source value
Mounting 4-d; d=M5 in table

Catalogue — V1000 3% and 5% reactors — page 35

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options V1000 Drive OPT

Reactor, 3% and 5% Impedance - may be used on either the input or output of a drive to reduce the effect of load or line side transients on the drive. The three-phase reactors are available loose in a separate NEMA 1 enclosure.

CA.VJ.01, 11/01/11 Data subject to change without notice Page 33 Yaskawa America, Inc. Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 35, printed page 33. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 3% and 5% reactors — PDF page 35

Input voltage / phase Model suffix Rated output current (A) Nominal HP 3% reactor part suffix; prefix 05P00620- 3% H(in) 3% L(in) 3% W(in) 5% reactor part suffix; prefix 05P00620- 5% H(in) 5% L(in) 5% W(in)
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 0020 8.0 8.0 6.0 0015 8.0 8.0 6.0
200-240V 1-Phase BA0002__A 1.9 1/4 0020 8.0 8.0 6.0 0021 8.0 8.0 6.0
200-240V 1-Phase BA0003__A 3.3 1/2 & 3/4 0020 8.0 8.0 6.0 0021 8.0 8.0 6.0
200-240V 1-Phase BA0006__A 6.0 1 0027 8.0 8.0 6.0 0028 8.0 8.0 6.0
200-240V 1-Phase BA0010__A 9.6 2 & 3 0027 8.0 8.0 6.0 0028 8.0 8.0 6.0
200-240V 1-Phase BA0012__A 12.0 3 0032 8.0 8.0 6.0 0033 8.0 8.0 6.0
200-240V 1-Phase BA0018__A 17.5 5 0036 8.0 8.0 6.0 0037 8.0 8.0 6.0
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 0020 8.0 8.0 6.0 0015 8.0 8.0 6.0
200-240V 3-Phase 2A0002__A 1.9 1/4 0020 8.0 8.0 6.0 0021 8.0 8.0 6.0
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 0020 8.0 8.0 6.0 0021 8.0 8.0 6.0
200-240V 3-Phase 2A0006__A 6.0 1 0027 8.0 8.0 6.0 0028 8.0 8.0 6.0
200-240V 3-Phase 2A0010__A 9.6 2 & 3 0027 8.0 8.0 6.0 0028 8.0 8.0 6.0
200-240V 3-Phase 2A0012__A 12.0 3 0032 8.0 8.0 6.0 0033 8.0 8.0 6.0
200-240V 3-Phase 2A0020__A 19.6 5 0036 8.0 8.0 6.0 0037 8.0 8.0 6.0
200-240V 3-Phase 2A0030__A 30.0 7.5 & 10 0041 13.0 13.0 13.0 0042 13.0 13.0 13.0
200-240V 3-Phase 2A0040__A 40.0 10 0046 13.0 13.0 13.0 0047 13.0 13.0 13.0
200-240V 3-Phase 2A0056__A 56.0 20 0054 13.0 13.0 13.0 0055 13.0 13.0 13.0
200-240V 3-Phase 2A0069__A 69.0 25 0058 13.0 13.0 13.0 0059 13.0 13.0 13.0
380-480V 3-Phase 4A0001__A 1.2 1/2 0015 8.0 8.0 6.0 0016 8.0 8.0 6.0
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 0015 8.0 8.0 6.0 0016 8.0 8.0 6.0
380-480V 3-Phase 4A0004__A 4.1 2 0021 8.0 8.0 6.0 0023 8.0 8.0 6.0
380-480V 3-Phase 4A0005__A 5.4 3 0028 8.0 8.0 6.0 0029 8.0 8.0 6.0
380-480V 3-Phase 4A0007__A 6.9 4 0033 8.0 8.0 6.0 0034 8.0 8.0 6.0
380-480V 3-Phase 4A0009__A 8.8 5 0037 8.0 8.0 6.0 0038 13.0 13.0 13.0
380-480V 3-Phase 4A0011__A 11.1 7.5 0042 13.0 13.0 13.0 0043 13.0 13.0 13.0
380-480V 3-Phase 4A0018__A 17.5 10 0042 13.0 13.0 13.0 0043 13.0 13.0 13.0
380-480V 3-Phase 4A0023__A 23.0 15 0047 13.0 13.0 13.0 0048 13.0 13.0 13.0
380-480V 3-Phase 4A0031__A 31.0 20 0047 13.0 13.0 13.0 0048 13.0 13.0 13.0
380-480V 3-Phase 4A0038__A 38.0 25 0051 13.0 13.0 13.0 0052 13.0 13.0 13.0

Catalogue — V1000 C1 filters — page 36

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options

OPT V1000 Drive

EMC C1 Filters - may be used on the input of the drive to attenuate possible drive-generated noise. Filters should always be mounted as close to the drive as possible; these are designed such that the drive can be mounted to it, pancake-style. The drive should be installed with the EMC filters listed below in order to comply with the EN 61800-3, category C1 requirements. These C1 filters meet the requirements for CE. Note: EMC filters for models CIMR-VU2A0030 through 0069 are in compliance with EN 61800-3, Category 2. All other models comply with Category 1.

CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 34 Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 36, printed page 34. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 C1 filters — PDF page 36

Input voltage / phase Model suffix Rated output current (A) Nominal HP C1 filter part number Filter rated current(A) H(in) W(in) D(in) Weight(lb)
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 FS23638-10-07 10 6.65 2.80 1.77 0.97
200-240V 1-Phase BA0002__A 1.9 1/4 FS23638-10-07 10 6.65 2.80 1.77 0.97
200-240V 1-Phase BA0003__A 3.3 1/2 & 3/4 FS23638-10-07 10 6.65 2.80 1.77 0.97
200-240V 1-Phase BA0006__A 6.0 1 FS23638-20-07 20 6.65 4.37 1.97 1.76
200-240V 1-Phase BA0010__A 9.6 2 & 3 FS23638-20-07 20 6.65 4.37 1.97 1.76
200-240V 1-Phase BA0012__A 12.0 3 FS23638-30-07 30 6.85 5.67 1.97 2.64
200-240V 1-Phase BA0018__A 17.5 5 FS23638-40-07 40 6.85 6.85 1.97 3.52
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 FS23637-8-07 8 6.65 2.80 1.57 0.88
200-240V 3-Phase 2A0002__A 1.9 1/4 FS23637-8-07 8 6.65 2.80 1.57 0.88
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 FS23637-8-07 8 6.65 2.80 1.57 0.88
200-240V 3-Phase 2A0006__A 6.0 1 FS23637-8-07 8 6.65 2.80 1.57 0.88
200-240V 3-Phase 2A0010__A 9.6 2 & 3 FS23637-14-07 14 6.65 4.37 1.77 1.28
200-240V 3-Phase 2A0012__A 12.0 3 FS23637-14-07 14 6.65 4.37 1.77 1.28
200-240V 3-Phase 2A0020__A 19.6 5 FS23637-24-07 24 6.85 5.67 1.97 1.98
200-240V 3-Phase 2A0030__A 30.0 7.5 & 10 FS23637-52-07 52 11.97 5.39 2.20 4.41
200-240V 3-Phase 2A0040__A 40.0 10 FS23637-52-07 52 11.97 5.39 2.20 4.41
200-240V 3-Phase 2A0056__A 56.0 20 FS23637-68-07 68 13.39 6.89 2.56 5.73
200-240V 3-Phase 2A0069__A 69.0 25 FS23637-80-07 80 15.47 8.35 2.56 6.83
380-480V 3-Phase 4A0001__A 1.2 1/2 FS23639-5-07 5 6.65 4.37 1.77 1.10
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 FS23639-5-07 5 6.65 4.37 1.77 1.10
380-480V 3-Phase 4A0004__A 4.1 2 FS23639-5-07 5 6.65 4.37 1.77 1.10
380-480V 3-Phase 4A0005__A 5.4 3 FS23639-10-07 10 6.65 4.37 1.77 1.54
380-480V 3-Phase 4A0007__A 6.9 4 FS23639-10-07 10 6.65 4.37 1.77 1.54
380-480V 3-Phase 4A0009__A 8.8 5 FS23639-10-07 10 6.65 4.37 1.77 1.54
380-480V 3-Phase 4A0011__A 11.1 7.5 FS23639-15-07 15 6.85 5.67 1.97 1.98
380-480V 3-Phase 4A0018__A 17.5 10 FS23639-30-07 30 11.97 5.39 2.20 3.97
380-480V 3-Phase 4A0023__A 23.0 15 FS23639-30-07 30 11.97 5.39 2.20 3.97
380-480V 3-Phase 4A0031__A 31.0 20 FS23639-50-07 50 13.39 6.89 2.56 5.95
380-480V 3-Phase 4A0038__A 38.0 25 FS23639-50-07 50 13.39 6.89 2.56 5.95

Catalogue — V1000 C3 filters — page 37

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options V1000 Drive OPT

EMC C3 Filters (Conducted Interference Voltage Limits) - may be used on the input of a drive to attenuate possible drive- generated noise. An input filter with proper shielding, routing and grounding between itself and the drive is designed to reduce line-conducted noise levels within the limits of EN61800-3 Category C3, I ≤ 100A (second environment for industrial low- voltage supply network), when the drive’s output conductors are properly routed and shielded in grounded steel conduit all the way to the motor. The filters in combination with the drive meet UL and CE.

Note: Kit contains filter, cover, and mounting hardware.

CA.VJ.01, 11/01/11 Data subject to change without notice Page 35 Yaskawa America, Inc. Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 37, printed page 35. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 C3 filters — PDF page 37

Input voltage / phase Model suffix Rated output current (A) Nominal HP C3 filter kit part number Filter rated current(A)
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 FS22800-5-B 5
200-240V 1-Phase BA0002__A 1.9 1/4 FS22800-5-B 5
200-240V 1-Phase BA0003__A 3.3 1/2 & 3/4 FS22800-9-B 9
200-240V 1-Phase BA0006__A 6.0 1 FS22800-16-B 16
200-240V 1-Phase BA0010__A 9.6 2 & 3 FS22800-26-B 26
200-240V 1-Phase BA0012__A 12.0 3 FS22800-33-B 33
200-240V 1-Phase BA0018__A 17.5 5 Consult Factory Consult Factory
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 Consult Factory Consult Factory
200-240V 3-Phase 2A0002__A 1.9 1/4 Consult Factory Consult Factory
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 Consult Factory Consult Factory
200-240V 3-Phase 2A0006__A 6.0 1 Consult Factory Consult Factory
200-240V 3-Phase 2A0010__A 9.6 2 & 3 Consult Factory Consult Factory
200-240V 3-Phase 2A0012__A 12.0 3 Consult Factory Consult Factory
200-240V 3-Phase 2A0020__A 19.6 5 Consult Factory Consult Factory
200-240V 3-Phase 2A0030__A 30.0 7.5 & 10 Consult Factory Consult Factory
200-240V 3-Phase 2A0040__A 40.0 10 Consult Factory Consult Factory
200-240V 3-Phase 2A0056__A 56.0 20 Consult Factory Consult Factory
200-240V 3-Phase 2A0069__A 69.0 25 Consult Factory Consult Factory
380-480V 3-Phase 4A0001__A 1.2 1/2 FS22801-3-B 3
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 FS22801-3-B 3
380-480V 3-Phase 4A0004__A 4.1 2 FS22801-6-B 6
380-480V 3-Phase 4A0005__A 5.4 3 FS22801-12-B 12
380-480V 3-Phase 4A0007__A 6.9 4 FS22801-12-B 12
380-480V 3-Phase 4A0009__A 8.8 5 FS22801-12-B 12
380-480V 3-Phase 4A0011__A 11.1 7.5 FS22801-16-B 16
380-480V 3-Phase 4A0018__A 17.5 10 FS22801-24-B 24
380-480V 3-Phase 4A0023__A 23.0 15 FS22801-24-B 24
380-480V 3-Phase 4A0031__A 31.0 20 FS22801-44-B 44
380-480V 3-Phase 4A0038__A 38.0 25 FS22801-44-B 44

Catalogue — V1000 3% duty braking resistors — page 38

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options

OPT V1000 Drive

Dynamic Braking Resistor, 3% Duty Cycle - are rated for 3% duty cycle over a 100-second interval. Approximate braking torque for each rating is listed. These resistors are designed for separate panel mounting.

CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 36 Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 38, printed page 36. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 3% duty braking resistors — PDF page 38

Input voltage / phase Model suffix Normal duty current(A) Normal duty HP Heavy duty current(A) Heavy duty HP 3% resistor part number Quantity required Resistance each(ohms) Power each(W) Approximate braking torque(%) H(in) W(in) D(in)
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 0.8 1/8 R7507 1 400 150 125 7.16 1.73 0.51
200-240V 1-Phase BA0002__A 1.9 1/4 1.6 1/4 R7507 1 400 150 125 7.16 1.73 0.51
200-240V 1-Phase BA0003__A 3.5 1/2 & 3/4 3.0 1/2 R7505 1 200 150 230 7.16 1.73 0.51
200-240V 1-Phase BA0006__A 6.0 1 5.0 3/4 & 1 R7505 1 200 150 230 7.16 1.73 0.51
200-240V 1-Phase BA0010__A 9.6 2 & 3 8.0 2 R7504 1 100 150 125 7.16 1.73 0.51
200-240V 1-Phase BA0012__A 12.0 3 11.0 3 R7503 1 70 150 120 7.16 1.73 0.51
200-240V 1-Phase BA0018__A 17.5 5 17.5 5 R7510 1 62 150 100 7.16 1.73 0.51
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 0.8 1/8 R7507 1 400 150 125 7.16 1.73 0.51
200-240V 3-Phase 2A0002__A 1.9 1/4 1.6 1/4 R7507 1 400 150 125 7.16 1.73 0.51
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 3.0 1/2 R7505 1 200 150 230 7.16 1.73 0.51
200-240V 3-Phase 2A0006__A 6.0 1 5.0 3/4 & 1 R7505 1 200 150 230 7.16 1.73 0.51
200-240V 3-Phase 2A0010__A 9.6 2 & 3 8.0 2 R7504 1 100 150 125 7.16 1.73 0.51
200-240V 3-Phase 2A0012__A 12.0 3 11.0 3 R7503 1 70 150 120 7.16 1.73 0.51
200-240V 3-Phase 2A0020__A 19.6 5 17.5 5 R7510 1 62 150 100 7.16 1.73 0.51
200-240V 3-Phase 2A0030__A 30 7.5 & 10 25.0 7.5 N/A N/A N/A N/A N/A N/A N/A N/A
200-240V 3-Phase 2A0040__A 40 10 33.0 10 N/A N/A N/A N/A N/A N/A N/A N/A
200-240V 3-Phase 2A0056__A 56 20 47.0 15 N/A N/A N/A N/A N/A N/A N/A N/A
200-240V 3-Phase 2A0069__A 69 25 60.0 20 N/A N/A N/A N/A N/A N/A N/A N/A
380-480V 3-Phase 4A0001__A 1.2 1/2 1.2 1/2 R7508 1 750 150 230 7.16 1.73 0.51
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 1.8 3/4 R7508 1 750 150 230 7.16 1.73 0.51
380-480V 3-Phase 4A0004__A 4.1 2 3.4 1 & 2 R7508 1 750 150 130 7.16 1.73 0.51
380-480V 3-Phase 4A0005__A 5.4 3 4.8 3 R7507 1 400 150 125 7.16 1.73 0.51
380-480V 3-Phase 4A0007__A 6.9 4 5.5 3 R7507 2 400 150 125 7.16 1.73 0.51
380-480V 3-Phase 4A0009__A 8.8 5 7.2 4 R7507 2 400 150 125 7.16 1.73 0.51
380-480V 3-Phase 4A0011__A 11.1 7.5 9.2 5 N/A N/A N/A N/A N/A N/A N/A N/A
380-480V 3-Phase 4A0018__A 17.5 10 14.8 7.5 & 10 N/A N/A N/A N/A N/A N/A N/A N/A
380-480V 3-Phase 4A0023__A 23.0 15 18.0 10 N/A N/A N/A N/A N/A N/A N/A N/A
380-480V 3-Phase 4A0031__A 31.0 20 24.0 15 N/A N/A N/A N/A N/A N/A N/A N/A
380-480V 3-Phase 4A0038__A 38.0 25 31.0 20 N/A N/A N/A N/A N/A N/A N/A N/A

Catalogue — V1000 10% duty braking resistors — page 39

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options V1000 Drive OPT

Dynamic Braking Resistor, 10% Duty Cycle - are rated for 10% duty cycle over a 100-second interval. Approximate braking torque for each rating is listed. These resistors are designed in vented NEMA 1 enclosures for separate panel mounting. The built-in braking module supports the 3% and 10% duty cycle resistors listed here and on the previous page. Resistors for applications requiring 50% and 100% duty cycle can be supported; please consult Yaskawa for duty cycles above 10%.

CA.VJ.01, 11/01/11 Data subject to change without notice Page 37 Yaskawa America, Inc. Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 39, printed page 37. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 10% duty braking resistors — PDF page 39

Input voltage / phase Model suffix Normal duty current(A) Normal duty HP Heavy duty current(A) Heavy duty HP 10% resistor part number Quantity required Resistance each(ohms) Power each(W) Approximate ND braking torque(%) Approximate HD braking torque(%) L(in) W(in) H(in) Minimum resistance(ohms)
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 0.8 1/8 USR000032 1 750 600 120 150 12 7 5 300
200-240V 1-Phase BA0002__A 1.9 1/4 1.6 1/4 USR000033 1 400 500 120 150 12 7 5 300
200-240V 1-Phase BA0003__A 3.5 1/2 & 3/4 3.0 1/2 USR000022 1 200 250 120 150 12 5 5 200
200-240V 1-Phase BA0006__A 6.0 1 5.0 3/4 & 1 USR000035 1 150 500 102 150 12 7 5 120
200-240V 1-Phase BA0010__A 9.6 2 & 3 8.0 2 USR000024 1 70 250 107 150 12 5 5 60
200-240V 1-Phase BA0012__A 12.0 3 11.0 3 USR000024 1 70 250 107 107 12 5 5 60
200-240V 1-Phase BA0018__A 17.5 5 17.5 5 USR000025 1 40 846 111 111 12 7 5 32
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 0.8 1/8 USR000032 1 750 600 120 150 12 7 5 300
200-240V 3-Phase 2A0002__A 1.9 1/4 1.6 1/4 USR000033 1 400 500 120 150 12 7 5 300
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 3.0 1/2 USR000022 1 200 250 120 150 12 5 5 200
200-240V 3-Phase 2A0006__A 6.0 1 5.0 3/4 & 1 USR000035 1 150 500 102 150 12 7 5 120
200-240V 3-Phase 2A0010__A 9.6 2 & 3 8.0 2 USR000024 1 70 250 107 150 12 5 5 60
200-240V 3-Phase 2A0012__A 12.0 3 11.0 3 USR000024 1 70 250 107 107 12 5 5 60
200-240V 3-Phase 2A0020__A 19.6 5 17.5 5 USR000025 1 40 846 111 111 12 7 5 32
200-240V 3-Phase 2A0030__A 30 7.5 & 10 25.0 7.5 URS000148 1 18 1301 120 150 12 10 5 16
200-240V 3-Phase 2A0040__A 40 10 33.0 10 URS000140 1 13.6 1646 120 150 12 13 5 9.6
200-240V 3-Phase 2A0056__A 56 20 47.0 15 URS000136 1 10.5 3402 101 135 27 10 5 9.6
200-240V 3-Phase 2A0069__A 69 25 60.0 20 URS000136 1 10.5 3402 80 101 27 10 5 9.6
380-480V 3-Phase 4A0001__A 1.2 1/2 1.2 1/2 USR000032 1 750 600 120 150 12 7 5 750
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 1.8 3/4 USR000032 1 750 600 120 150 12 7 5 750
380-480V 3-Phase 4A0004__A 4.1 2 3.4 1 & 2 USR000032 1 750 600 61 61 12 7 5 510
380-480V 3-Phase 4A0005__A 5.4 3 4.8 3 USR000034 1 250 500 119 119 12 7 5 240
380-480V 3-Phase 4A0007__A 6.9 4 5.5 3 USR000034 1 250 500 119 119 12 7 5 200
380-480V 3-Phase 4A0009__A 8.8 5 7.2 4 USR000035 1 150 500 118 150 12 7 5 100
380-480V 3-Phase 4A0011__A 11.1 7.5 9.2 5 USR000036 1 100 975 117 150 12 10 5 100
380-480V 3-Phase 4A0018__A 17.5 10 14.8 7.5 & 10 USR000038 1 50 1600 120 150 12 13 5 32
380-480V 3-Phase 4A0023__A 23.0 15 18.0 10 USR000038 1 50 1600 113 150 12 13 5 32
380-480V 3-Phase 4A0031__A 31.0 20 24.0 15 USR000039 1 40 2050 106 142 12 16 5 20
380-480V 3-Phase 4A0038__A 38.0 25 31.0 20 URS000154 1 27.2 2720 120 150 19 13 5 20

Catalogue — V1000 DIN rail kits — page 40

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options

OPT V1000 Drive

DIN Rail Mounting Kits - The DIN rail attachment kit allows the drive to be mounted on a 35 mm DIN rail. The DIN rail itself is not included in the kit. Option kit for customer mounting.

CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 38 Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 40, printed page 38. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 DIN rail kits — PDF page 40

Input voltage / phase Model suffix Rated output current (A) Nominal HP Kit suffix; prefix 72606-EZZ08122
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 A
200-240V 1-Phase BA0002__A 1.9 1/4 A
200-240V 1-Phase BA0003__A 3.3 1/2 & 3/4 A
200-240V 1-Phase BA0006__A 6.0 1 B
200-240V 1-Phase BA0010__A 9.6 2 & 3 B
200-240V 1-Phase BA0012__A 12.0 3 C
200-240V 1-Phase BA0018__A 17.5 5 D
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 A
200-240V 3-Phase 2A0002__A 1.9 1/4 A
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 A
200-240V 3-Phase 2A0006__A 6.0 1 A
200-240V 3-Phase 2A0010__A 9.6 2 & 3 B
200-240V 3-Phase 2A0012__A 12.0 3 B
200-240V 3-Phase 2A0020__A 19.6 5 C
200-240V 3-Phase 2A0030__A 30.0 7.5 & 10 Not Available
200-240V 3-Phase 2A0040__A 40.0 10 Not Available
200-240V 3-Phase 2A0056__A 56.0 20 Not Available
200-240V 3-Phase 2A0069__A 69.0 25 Not Available
380-480V 3-Phase 4A0001__A 1.2 1/2 B
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 B
380-480V 3-Phase 4A0004__A 4.1 2 B
380-480V 3-Phase 4A0005__A 5.4 3 B
380-480V 3-Phase 4A0007__A 6.9 4 B
380-480V 3-Phase 4A0009__A 8.8 5 B
380-480V 3-Phase 4A0011__A 11.1 7.5 C
380-480V 3-Phase 4A0018__A 18.0 10 Not Available
380-480V 3-Phase 4A0023__A 23.0 15 Not Available
380-480V 3-Phase 4A0031__A 31.0 20 Not Available
380-480V 3-Phase 4A0038__A 38.0 25 Not Available

Catalogue — V1000 external heatsink and adapter kits — page 41

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options V1000 Drive OPT

Adapter Plate - Conversion kit used to mount a V1000 on the same footprint as a V7 drive. Not available for J1000 drives.

External Heatsink Kit - Allow for V1000 drives to be mounted with the drive’s heatsink external to the enclosure. Not available for J1000 drives. Option kit for customer mounting.

CA.VJ.01, 11/01/11 Data subject to change without notice Page 39 Yaskawa America, Inc. Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 41, printed page 39. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 external heatsink and adapter kits — PDF page 41

Input voltage / phase Model suffix Rated output current (A) Nominal HP External heatsink suffix; prefix EZZ020568_ Adapter suffix; prefix EZZ020572_
230V, 1-Phase BA0001__A 1.2 1/8 & 1/4 A Not Required
230V, 1-Phase BA0002__A 1.9 1/4 A Not Required
230V, 1-Phase BA0003__A 3.3 1/2 & 3/4 B Not Required
230V, 1-Phase BA0006__A 6.0 1 C Not Required
230V, 1-Phase BA0010__A 9.6 2 & 3 D Not Required
230V, 1-Phase BA0012__A 12.0 3 E Not Required
230V, 1-Phase BA0018__A 17.5 5 F Not Required
230V, 3-Phase 2A0001__A 1.2 1/8 & 1/4 A Not Required
230V, 3-Phase 2A0002__A 1.9 1/4 A Not Required
230V, 3-Phase 2A0004__A 3.5 1/2 & 3/4 B Not Required
230V, 3-Phase 2A0006__A 6.0 1 G Not Required
230V, 3-Phase 2A0010__A 9.6 2 & 3 D Not Required
230V, 3-Phase 2A0012__A 12.0 3 D Not Required
230V, 3-Phase 2A0020__A 19.6 5 E Not Required
230V, 3-Phase 2A0030__A 30.0 7.5 & 10 H B
230V, 3-Phase 2A0040__A 40.0 10 H B
230V, 3-Phase 2A0056__A 56.0 20 J Not Required
230V, 3-Phase 2A0069__A 69.0 25 K Not Required
460V 4A0001__A 1.2 1/2 L Not Required
460V 4A0002__A 2.1 3/4 & 1 C Not Required
460V 4A0004__A 4.1 2 C Not Required
460V 4A0005__A 5.4 3 D Not Required
460V 4A0007__A 6.9 4 D Not Required
460V 4A0009__A 8.8 5 D A
460V 4A0011__A 11.1 7.5 E Not Required
460V 4A0018__A 18.0 10 H B
460V 4A0023__A 23.0 15 H B
460V 4A0031__A 31.0 20 J Not Required
460V 4A0038__A 38.0 25 J Not Required

Catalogue — V1000 24VDC power and bracket kits — page 42

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options

OPT V1000 Drive

24VDC Control Power Unit - This option provides board-level component voltages for the V1000 drive when provided with 24VDC from an external, customer-supplied source. It is used to maintain both drive control power and network communications (when utilized). Both a Control Power Unit and a Bracket Kit are required for proper operation and certification. Option kit for customer mounting.

CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 40 Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 42, printed page 40. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.

V1000 24VDC power and bracket kits — PDF page 42

Input voltage / phase Model suffix Rated output current (A) Nominal HP Control power unit part number Bracket suffix; prefix EZZ020639_
200-240V 1-Phase BA0001__A 1.2 1/8 & 1/4 PS-V10S A
200-240V 1-Phase BA0002__A 1.9 1/4 PS-V10S A
200-240V 1-Phase BA0003__A 3.3 1/2 & 3/4 PS-V10S A
200-240V 1-Phase BA0006__A 6.0 1 PS-V10S B
200-240V 1-Phase BA0010__A 9.6 2 & 3 PS-V10S B
200-240V 1-Phase BA0012__A 12.0 3 PS-V10S B
200-240V 1-Phase BA0018__A 17.5 5 PS-V10S B
200-240V 3-Phase 2A0001__A 1.2 1/8 & 1/4 PS-V10S A
200-240V 3-Phase 2A0002__A 1.9 1/4 PS-V10S A
200-240V 3-Phase 2A0004__A 3.5 1/2 & 3/4 PS-V10S A
200-240V 3-Phase 2A0006__A 6.0 1 PS-V10S A
200-240V 3-Phase 2A0010__A 9.6 2 & 3 PS-V10S B
200-240V 3-Phase 2A0012__A 12.0 3 PS-V10S B
200-240V 3-Phase 2A0020__A 19.6 5 PS-V10S B
200-240V 3-Phase 2A0030__A 30.0 7.5 & 10 PV-V10M B
200-240V 3-Phase 2A0040__A 40.0 10 PV-V10M B
200-240V 3-Phase 2A0056__A 56.0 20 PS-V10M C
200-240V 3-Phase 2A0069__A 69.0 25 PS-V10M C
380-480V 3-Phase 4A0001__A 1.2 1/2 PS-V10S A
380-480V 3-Phase 4A0002__A 2.1 3/4 & 1 PS-V10S A
380-480V 3-Phase 4A0004__A 4.1 2 PS-V10S B
380-480V 3-Phase 4A0005__A 5.4 3 PS-V10S B
380-480V 3-Phase 4A0007__A 6.9 4 PS-V10S B
380-480V 3-Phase 4A0009__A 8.8 5 PS-V10S B
380-480V 3-Phase 4A0011__A 11.1 7.5 PS-V10S B
380-480V 3-Phase 4A0018__A 18.0 10 PS-V10M B
380-480V 3-Phase 4A0023__A 23.0 15 PS-V10M B
380-480V 3-Phase 4A0031__A 31.0 20 PS-V10M B
380-480V 3-Phase 4A0038__A 38.0 25 PS-V10M C

Catalogue — V1000: source text and annotations — page 43

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options V1000 Drive OPT

Operator, LCD Digital Remote, NEMA Type 1. This option allows the drive to be operated from a remote location, and provides a 16-character, 5-line alpha-numeric LCD. This option requires Installation Set A (EZZ020642A) for panel or door mounting and Remote Operator Cable (UWR0051 or UWR0052), each sold separately. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. JVOP-180

Operator, LED Digital Remote, NEMA Type 1. This option allows the drive to be operated from a remote location. This option requires Installation Set A (EZZ020642A) for panel or door mounting and Remote Operator Cable (UWR0051 or UWR0052), each sold separately. Note: This option requires the V1000 drive to contain 1016 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. JVOP-182

LCD/LED Keypad Installation Set A (Remote Operator Mounting Bracket Kit). This is a bracket to which the LCD Digital Remote Operator (JVOP-180) attaches, and has (4) threaded holes and screws to attach to the cover of an enclosure. The kit contains (2) screws to mount the Operator to the bracket and (4) screws to attach the bracket to the enclosure. Model No. EZZ020642A

LCD/LED Keypad Installation Set B (Remote Operator Mounting Bracket Kit). Contains a similar bracket that the keypad attaches to and has non-threaded holes for mounting to an enclosure that has the screws attached to the enclosure already. The kit contains (2) screws to mount the keypad to the bracket and (4) nuts to attach the bracket to the customer supplied screws attached to the enclosure. Model No. EZZ020642B

Operator Cable, Remote. These cables are used to connect the Remote LCD Digital Operator (JVOP-180) or Remote LED Operator (JVOP-182). They are available in one (1) or three (3) meter lengths. Model No. UWR0051 (1 meter) Model No. UWR0052 (3 meter)

Operator Kits, NEMA Type 3R/4X. This option is used to extend an LCD or LED Digital Remote Operator to the wall of a separately priced, oversized UL Type 3R, 4, 4X, or 12 enclosure (IPX6 environment). Price includes a faceplate bezel with digital operator brackets and membrane to cover the operator cutout in the enclosure door, a 3-foot cable, a 10-foot cable, and a 1:1 template for cutting the necessary cutouts in the enclosure. Keypad can be removed after kit installation. Designed for use with the LCD Operator JVOP-180 or the LED Operator JVOP-182 sold separately. Connects to RJ45 port and mounts to enclosure wall. Model No. UUX000526 (Blank Membrane) Model No. UUX000527 (Yaskawa Logo Membrane)

DriveWizard Plus Software. This optional software package allows upload and download of parameters via PC for data storage and for programming multiple drives. The software also includes graphing and monitoring tools. It is a Windows-based program designed to make startup, commissioning, and troubleshooting of the J1000 as simple as possible. Refer to our website at www.yaskawa.com to download the software, and for more information, including minimum system requirements and cable information to interface a PC to V1000 or J1000 drives. No Model No.

PC Interface Cable. This 6-foot cable interconnects the drive keypad port to the 9-pin communication port on a PC. This cable is used in conjunction with DriveWizard Plus software. Model No. UWR00468-2

USB Copy Unit (Y-Stick). This option allows the drive to connect to the USB port on a PC. It can read, copy and verify drive parameter settings from one drive to another like drive. The unit plugs into the RJ-45 port on the front of the digital operator. Refer to our website at www.yaskawa.com to download the software. Model No. JVOP-181

CopyUnitManager Software for USB Copy Unit (Y-Stick). This option allows the user to transfer and save parameter files from the Copy Unit (JVOP-181), sold separately, to a PC and vice versa. Refer to our website at www.yaskawa.com to download the software. No Model No.

120 VAC Interface. This option mounts directly to the control terminal block on the drive and allows the use of 120 VAC control logic circuits to produce multi-function control input signals for the drive. Model No. DI-100

DriveWorksEZ (DWEZ) Standard and Pro. A software system that provides the means to create custom drive functionality in the V1000 using function block programming to distribute control away from a PLC.

DWEZ Standard can be downloaded from www.yaskawa.com with a valid partner login. DWEZ Pro requires attending a factory training class - see below for details.

DriveWorksEZ (DWEZ) Standard. The V1000 provides for 118 basic function blocks and up to 20 block connections. Available via web download only. Valid www.yaskawa.com Partner Login required

DriveWorksEZ (DWEZ) Pro Certification. A two-day DWEZ- specific training class (TRM020-DriveWorksEZ) must be attended to become certified. This class is intended for those well-versed in V1000 programming. DWEZ Pro provides increased functionality, with 50 connections and 225 function blocks compared to the Standard version. Model No. CD.DWEZ.03

To enroll in class, call Technical Training Services at 847-887-7228.

Page

CA.VJ.01, 11/01/11 Data subject to change without notice 41 Yaskawa America, Inc. Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Catalogue — V1000: source text and annotations — page 44

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options

OPT V1000 Drive

DeviceNet™ With ADR. This option complies with all pertinent aspects of the ODVA (Open DeviceNet Vendor Association) specification and AC drive profile. All parameters, diagnostics and operational commands are accessible via DeviceNet. Automatic Device Replacement (ADR) is supported in this DeviceNet option, including the functions of Auto Baud Rate sensing and Faulted Node Recovery (using Group 4 messaging). Each DeviceNet network supports up to 63 drives. Controllers are available from many PLC and/or PC suppliers. The board mounts integrally in the drive and provides a DeviceNet standard open tap connector. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover and a monitor has been added to allow for improved diagnostics. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-N3/V

EtherNet/IP. This option complies with the EtherNet/IP protocol specification, and allows for communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user specified IP address, from a DHCP host, or from a BootP host. The IP address can be set from the drive keypad or from the network. All parameters, diagnostics and operational commands are accessible via EtherNet/IP. The web interface allows management of diagnostic information through a standard web browser. The embedded web pages include the main page, drive status page, network monitor page, and documentation page. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EN3/V

PROFINET. This option complies to PROFINET I/O device and PROFIDrive profile specifications. It allows connection of a PROFINET network and facilitates the exchange of data via a simple, networking solution that reduces the cost and time to wire and install factory automation devices, while providing interchangeability of like components from multiple vendors. This is a PROFINET Conformance Class A certified interface.

This interface makes it possible to perform the following from a PROFINET master device: • Operate the drive • Monitor the operation status of the drive • Change parameter settings Note: This option requires the V1000 to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EP3/V

Profibus DP. This option complies with the Profibus DP protocol specification. All parameters, diagnostics and operational commands are accessible via Profibus. The option board provides a 9-pin (F) type D-Sub connector for easily connecting to a standard Profibus style, shielded twisted-pair cable. Each Profibus network supports up to 99 drives. This option supports all of the Profibus data rates from 9.6 Kbps to 12 Mbps. Up to 32 bytes of input data and 32 bytes of output data are provided per message transaction. Sync and Freeze modes are supported for groups. Profibus DP-V1 support (cyclic and acyclic data exchange). Configurable PPO read and write parameters. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover, and a monitor has been added to allow for improved diagnostics. Option is backwards compatible with the previous generation option cards. Note: This option requires the V1000 drive to contain 1010 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-P3/V

Modbus TCP/IP. This option complies with the Modbus TCP/IP protocol specification. This allows for Modbus communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user-specified IP address, from a DHCP host, or from a BootP host. All parameters, diagnostics and operational commands are accessible via Modbus TCP/IP. This option supports up to 10 simultaneous PLC/PC connections. Note: This option requires the V1000 drive to contain 1015 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EM3/V

MECHATROLINK-II. This option is designed for connecting a drive to a field network using the MECHATROLINK protocol. The MECHATROLINK-II option allows the user to operate the drive, monitor the status, and change parameters from a MECHATROLINK master device at a communication speed up to 10 Mbps. Note: This option requires the V1000 drive to contain 1016 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-T3/V

CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Catalogue — V1000-4X description and specifications — page 45

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Control:V/f,OpenLoopCurrentVector,PMOpenLoopCurrentVector andsimpleclosed-loopspeedcontrol. DCinjectionbraking/rampstop;electronicreversing;infinitelyadjustableV/Hzpattern;adjustablebrakingamplitude/duration/currentlimit;full-rangeautotorqueboost;speedsearch;autorestart;slipcompensation;energy-savingfunction;enhancedPIDwithfeedbackloss.

LEDstatusdisplay,remotemountkeypad,RJ-45styledigitaloperatorconnector;signal-followerbias/gain;coolingfancontrolledbyrun/stop;UL-recognizedelectronicoverload;built-indynamicbrakingtransistor;applicationpresets;maintenancemonitors.

Protection:currentlimit/stallpreventionduringaccel/decel/run;motoranddriveoverload;overvoltageprevention;instantaneousovercurrent;shortcircuit;undervoltage;heatsinkoverheat;groundfault;over/undertorque.

Integral enclosure forNEMAtype4X/12 indooruse,ULtype4X/12,IP66ofIEC529. Coated againstsanitizingchemicaleffects in foodindustries; sourceapplications food/beverage,packaging,metalmachining,woodworking,pumping,refrigeration,printing.

LEDstatusdisplay isdoor-mounted. Printed short-circuitwithstandrating30K RMS; unit notexpandedbeyondsource.

Context: Standards,MTBF,safety/category andlisting statements are historical supplierclaims, not independent compliance/certificatevalidation.

Context: Serviceconditions still headedNEMA1/OpenChassis on4Xpage; retain asprinted andflag applicability ratherthan asserting4Xambientlimits.

Table conditions: Sourcepage family-specific. Footnote1=V/fmode,2=OpenLoopCurrentVectorMode; preserve rating/duty distinctions. Analogresolution0.06/60Hz retained literally.

Table conditions: Printeddesignfeatures; do not infer availability from historicalcatalogue.

Table conditions: Exactprinted enclosure labels retained;4Xpage ambiguity flagged. No expanded environmentalrating inferred.

Table conditions: Historical source claims only; no current regulatoryapproval orcertificatevalidity assertion.

Table conditions: Option listing; compatibility requires source/factory confirmation. Detailed option tables are retained in their relevant sections.

Performance specifications — PDF page 45

Source label/context Source value
Ratings /200–240VAC1phase 1/8 to3HP
Ratings /200–240VAC3phase 1/8 to25HP(ND)
Ratings /380–480VAC3phase 1/2 to25HP(ND)
Heavy Duty overload 150% for60sec
Normal Duty overload 120% for60sec
Acceleration/deceleration 0.01 to6000seconds
Controlled speed range /V/fMode 40:1
Controlled speed range /OpenLoopCurrentVectorMode 100:1
Speed regulation /V/fMode withslipcompensation ±0.5 to1%
Speed regulation /OpenLoopCurrentVectorMode ±0.2%
Displacement power factor 0.98
Output frequency 0 to400Hz
Frequency resolution /digitalreference 0.01Hz
Frequency resolution /analogreference 0.06 /60Hz
Frequency accuracy /digitalcommand 0.01%
Frequency accuracy /analogcommand 0.5%
Power loss ride-through 0.5sec
Critical frequency rejection settings 3

Design specifications — PDF page 45

Source label/context Source value
Processors Dualmicroprocessorlogic
Keypad Digitaloperator,5digits
Digital inputs 7multifunction
Digital outputs 3multifunction
Hardwire baseblock EN954-1Cat.3
Programmable FormCcontact 1A at250VAC or30VDC
Control logic 24VDC;PNPorNPN sourcing/sinking compatible
Carrier frequency 15kHzmaximum;swingPWM
Speed settings 16multi-speed plusjog
Remote speed references 2;0–10VDC(20kohms) orisolated4–20mA(250ohms)
Open collector outputs 2programmable
Analog monitor 0–10VDC proportional tooutputfrequency oroutputcurrent
Parameters andmonitors Approximately400parameters
Pulse traininput 33kHzmaximum
Communication RS-422/485Modbus115kbps
MTBF 28years
Enclosure NEMA4X/IP66

Service conditions — PDF page 45

Source label/context Source value
Ambient service /NEMA1 −10 to40°C(+14 to104°F)
Ambient service /OpenChassis −10 to50°C(+14 to122°F)
Ambient storage −20 to60°C(−4 to140°F)
Humidity to95%,non-condensing
Altitude to3300ft;higherbyderating
Service factor 1.0
Inputvoltage tolerance −15% to+10%;200–240VAC,380–480VAC
Inputfrequency ±5%;50/60Hz
Inputphase sequence Insensitive

Printed standards and claims — PDF page 45

Source label/context Source value
UL 508C(PowerConversion)
CSA 22.2No.14-95(IndustrialControlEquipment)
Listings/marking UL,cULlisted;CEmarked
RoHS Compliant
LVD EN50178
EMC EN50081-2,EN50082-2
Safety EN954-1,Category3
OtherEN EN61800-3
IEC 529,146
FCC CFR47Part15SubpartB;withExternalFilter
TUV Printed claim
NEMA type4X/12
Ingress IP66 ofIEC60529

Listed options — PDF page 45

Source label/context Source value
1 120VACinterface
2 Profibus-DP
3 DeviceNet
4 ModbusTCP/IP
5 EtherNet/IP
6 DriveWizardPlus
7 Y-StickCopyUnit
8 Reactors3%and5%
9 Externaldynamicbrakingresistor
10 MultilingualfulltextremoteLCDwithcopy
11 EMCfilterTypeC1

Catalogue — V1000-4X standard drive ratings — page 47

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: Sourcepage ratings kept separate fromdimensionandvariantpages; discrepancies retained.

Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HPbasedonNEMAB4polemotorandNECtable430.150.

Standard drives — PDF page 47

Rated input voltage/phase Model suffix (CIMR-VU) ND output A ND nominal HP HD output A HD nominal HP
200-240V 1-Phase BA0001GAA 1.2 1/8 & 1/4 0.8 1/8
200-240V 1-Phase BA0002GAA 1.9 1/4 1.6 1/4
200-240V 1-Phase BA0003GAA 3.3 1/2 & 3/4 3.0 1/2
200-240V 1-Phase BA0006GAA 6.0 1 5.0 3/4 & 1
200-240V 1-Phase BA0010GAA 9.6 2 & 3 8.0 2
200-240V 1-Phase BA0012GAA 12.0 3 11.0 3
200-240V 3-Phase 2A0001GAA 1.2 1/8 & 1/4 0.8 1/8
200-240V 3-Phase 2A0002GAA 1.9 1/4 1.6 1/4
200-240V 3-Phase 2A0004GAA 3.5 1/2 & 3/4 3.0 1/2
200-240V 3-Phase 2A0006GAA 6.0 1 5.0 3/4 & 1
200-240V 3-Phase 2A0010GAA 9.6 2 & 3 8.0 2
200-240V 3-Phase 2A0012GAA 12.0 3 11.0 3
200-240V 3-Phase 2A0020GAA 19.6 5 17.5 5
200-240V 3-Phase 2A0030GAA 30.0 7.5 & 10 25.0 7.5
200-240V 3-Phase 2A0040GAA 40.0 10 33.0 10
200-240V 3-Phase 2A0056GAA 56.0 20 47.0 15
200-240V 3-Phase 2A0069GAA 69.0 25 60.0 20
380-480V 3-Phase 4A0001GAA 1.2 1/2 1.2 1/2
380-480V 3-Phase 4A0002GAA 2.1 3/4 & 1 1.8 3/4
380-480V 3-Phase 4A0004GAA 4.1 2 3.4 1 & 2
380-480V 3-Phase 4A0005GAA 5.4 3 4.8 3
380-480V 3-Phase 4A0007GAA 6.9 4 5.5 3
380-480V 3-Phase 4A0009GAA 8.8 5 7.2 4
380-480V 3-Phase 4A0011GAA 11.1 7.5 9.2 5
380-480V 3-Phase 4A0018GAA 17.5 10 14.8 7.5 & 10
380-480V 3-Phase 4A0023GAA 24.0 15 18.0 10
380-480V 3-Phase 4A0031GAA 31.0 20 24.0 15
380-480V 3-Phase 4A0038GAA 38.0 25 31.0 20

Catalogue — V1000-4X summary dimensions and data — page 48

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: EachprintedGAAmodel retained. Ratings and roundedweights maydiffer fromstandard/drawingpages; preserveeachoccurrence.

Table conditions: Physicalandmountingdimensions expresslyinches. Weightisdriveweight,notshipping. Noordercodeorengineeringcorrection.

4X summary dimensions and data — PDF page 48

Ratedinputvoltage/phase Model(CIMR-VU) NDoutputA NDnominalHP HDoutputA HDnominalHP H in W in D in H1 in W1 in Driveweight lb
200-240V 1-Phase BA0001GAA 1.2 1/8 & 1/4 0.8 1/8 8.74 6.38 7.28 8.27 5.32 10.4
200-240V 1-Phase BA0002GAA 1.9 1/4 1.6 1/4 8.74 6.38 7.28 8.27 5.32 10.4
200-240V 1-Phase BA0003GAA 3.3 1/2 & 3/4 3.0 1/2 8.74 6.38 7.28 8.27 5.32 10.8
200-240V 1-Phase BA0006GAA 6.0 1 5.0 3/4 & 1 10.04 7.36 9.25 9.49 6.22 17.2
200-240V 1-Phase BA0010GAA 9.6 2 & 3 8.0 2 10.04 7.36 9.25 9.49 6.22 17.2
200-240V 1-Phase BA0012GAA 12.0 3 11.0 3 10.04 7.36 9.25 9.49 6.22 18.1
200-240V 3-Phase 2A0001GAA 1.2 1/8 & 1/4 0.8 1/8 8.74 6.38 7.28 8.27 5.32 10.4
200-240V 3-Phase 2A0002GAA 1.9 1/4 1.6 1/4 8.74 6.38 7.28 8.27 5.32 10.4
200-240V 3-Phase 2A0004GAA 3.5 1/2 & 3/4 3.0 1/2 8.74 6.38 7.28 8.27 5.32 10.6
200-240V 3-Phase 2A0006GAA 6.0 1 5.0 3/4 & 1 8.74 6.38 7.28 8.27 5.32 10.6
200-240V 3-Phase 2A0010GAA 9.6 2 & 3 8.0 2 10.04 7.36 9.25 9.49 6.22 17.0
200-240V 3-Phase 2A0012GAA 12.0 3 11.0 3 10.04 7.36 9.25 9.49 6.22 17.0
200-240V 3-Phase 2A0020GAA 19.6 5 17.5 5 10.04 7.36 9.25 9.49 6.22 17.9
200-240V 3-Phase 2A0030GAA 30.0 7.5 & 10 25.0 7.5 16.54 11.42 12.01 15.75 10.43 48.1
200-240V 3-Phase 2A0040GAA 40.0 10 33.0 10 16.54 11.42 12.01 15.75 10.43 48.1
200-240V 3-Phase 2A0056GAA 56.0 20 47.0 15 16.54 11.42 12.01 15.75 10.43 51.2
200-240V 3-Phase 2A0069GAA 69.0 25 60.0 20 18.31 11.42 12.01 17.52 10.43 61.1
380-480V 3-Phase 4A0001GAA 1.2 1/2 1.2 1/2 8.74 6.38 7.28 8.27 5.32 11.1
380-480V 3-Phase 4A0002GAA 2.1 3/4 & 1 1.8 3/4 8.74 6.38 7.28 8.27 5.32 11.1
380-480V 3-Phase 4A0004GAA 4.1 2 3.4 1 & 2 8.74 6.38 7.28 8.27 5.32 11.3
380-480V 3-Phase 4A0005GAA 5.4 3 4.8 3 10.04 7.36 9.25 9.49 6.22 17.0
380-480V 3-Phase 4A0007GAA 6.9 4 5.5 3 10.04 7.36 9.25 9.49 6.22 17.5
380-480V 3-Phase 4A0009GAA 8.8 5 7.2 4 10.04 7.36 9.25 9.49 6.22 17.5
380-480V 3-Phase 4A0011GAA 11.1 7.5 9.2 5 10.04 7.36 9.25 9.49 6.22 17.9
380-480V 3-Phase 4A0018GAA 17.5 10 14.8 7.5 & 10 16.54 11.42 12.01 15.75 10.43 47.9
380-480V 3-Phase 4A0023GAA 24.0 15 18.0 10 16.54 11.42 12.01 15.75 10.43 48.1
380-480V 3-Phase 4A0031GAA 31.0 20 24.0 15 16.54 11.42 12.01 15.75 10.43 50.5
380-480V 3-Phase 4A0038GAA 38.0 25 31.0 20 16.54 11.42 12.01 15.75 10.43 51.2

Catalogue — DD.V1000-4X.01 dimension drawing — page 49

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.

Table conditions: PrintedDD.V1000-4X.01. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan10models. Noauto-equivalence toGAAmodelsexceptsourcecontext.

Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.

4X drawing dimension table — PDF page 49

Voltageclass Model(CIMR-V□) W mm(in) H mm(in) D mm(in) W1 mm(in) H1 mm(in) H2 mm(in) t1 mm(in) A mm(in) B mm(in) E mm(in) Weight kg(lb)
Single-Phase200VClass BA0001G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 4.7 (10.36)
Single-Phase200VClass BA0002G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 4.7 (10.36)
Single-Phase200VClass BA0003G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 4.9 (10.80)
Three-Phase200VClass 2A0001G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 4.7 (10.36)
Three-Phase200VClass 2A0002G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 4.7 (10.36)
Three-Phase200VClass 2A0004G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 4.8 (10.58)
Three-Phase200VClass 2A0006G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 4.8 (10.58)
Three-Phase400VClass 4A0001G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 5.0 (11.02)
Three-Phase400VClass 4A0002G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 5.0 (11.02)
Three-Phase400VClass 4A0004G 162 (6.38) 222 (8.74) 185 (7.28) 135 (5.32) 210 (8.27) 6 (0.24) 2 (0.08) 81 (3.19) 126 (4.96) 90 (3.54) 5.1 (11.24)

Explicit drawing callouts — PDF page 49

Source label/context Source value
Mounting 4-M5
Entrycallout1 6-Φ22

Catalogue — DD.V1000-4X.02 dimension drawing — page 50

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.

Table conditions: PrintedDD.V1000-4X.02. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan10models. Noauto-equivalence toGAAmodelsexceptsourcecontext.

Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.

4X drawing dimension table — PDF page 50

Voltageclass Model(CIMR-V□) W mm(in) H mm(in) D mm(in) W1 mm(in) H1 mm(in) H2 mm(in) t1 mm(in) A mm(in) B mm(in) E mm(in) Weight kg(lb)
Single-Phase200VClass BA0006G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 7.8 (17.2)
Single-Phase200VClass BA0010G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 7.8 (17.2)
Single-Phase200VClass BA0012G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 8.2 (18.08)
Three-Phase200VClass 2A0010G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 7.7 (16.98)
Three-Phase200VClass 2A0012G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 7.7 (16.98)
Three-Phase200VClass 2A0020G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 8.1 (17.86)
Three-Phase400VClass 4A0005G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 7.7 (16.98)
Three-Phase400VClass 4A0007G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 7.9 (17.42)
Three-Phase400VClass 4A0009G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 7.9 (17.42)
Three-Phase400VClass 4A0011G 187 (7.36) 255 (10.04) 235 (9.25) 158 (6.22) 241 (9.49) 7 (0.28) 2.5 (0.10) 140 (5.51) 188 (7.40) 100 (3.94) 8.1 (17.86)

Explicit drawing callouts — PDF page 50

Source label/context Source value
Mounting 4-M6
Entrycallout1 6-Φ28

Catalogue — DD.V1000-4X.03 dimension drawing — page 51

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.

Table conditions: PrintedDD.V1000-4X.03. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan7models. Noauto-equivalence toGAAmodelsexceptsourcecontext.

Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.

4X drawing dimension table — PDF page 51

Voltageclass Model(CIMR-V□) W mm(in) H mm(in) D mm(in) W1 mm(in) H1 mm(in) H2 mm(in) t1 mm(in) A mm(in) B mm(in) C mm(in) E mm(in) F mm(in) Weight kg(lb)
Three-Phase200VClass 2A0030G 290 (11.42) 420 (16.54) 305 (12.01) 265 (10.43) 400 (15.75) 8.5 (0.33) 2.5 (0.10) 158 (6.22) 205.5 (8.09) 258 (10.16) 90 (3.54) 95 (3.74) 21.8 (48.06)
Three-Phase200VClass 2A0040G 290 (11.42) 420 (16.54) 305 (12.01) 265 (10.43) 400 (15.75) 8.5 (0.33) 2.5 (0.10) 158 (6.22) 205.5 (8.09) 258 (10.16) 90 (3.54) 95 (3.74) 21.8 (48.06)
Three-Phase200VClass 2A0056G 290 (11.42) 420 (16.54) 305 (12.01) 265 (10.43) 400 (15.75) 8.5 (0.33) 2.5 (0.10) 158 (6.22) 205.5 (8.09) 258 (10.16) 90 (3.54) 95 (3.74) 23.2 (51.15)
Three-Phase400VClass 4A0018G 290 (11.42) 420 (16.54) 305 (12.01) 265 (10.43) 400 (15.75) 8.5 (0.33) 2.5 (0.10) 158 (6.22) 205.5 (8.09) 258 (10.16) 90 (3.54) 95 (3.74) 21.7 (47.84)
Three-Phase400VClass 4A0023G 290 (11.42) 420 (16.54) 305 (12.01) 265 (10.43) 400 (15.75) 8.5 (0.33) 2.5 (0.10) 158 (6.22) 205.5 (8.09) 258 (10.16) 90 (3.54) 95 (3.74) 21.8 (48.06)
Three-Phase400VClass 4A0031G 290 (11.42) 420 (16.54) 305 (12.01) 265 (10.43) 400 (15.75) 8.5 (0.33) 2.5 (0.10) 158 (6.22) 205.5 (8.09) 258 (10.16) 90 (3.54) 95 (3.74) 22.9 (50.49)
Three-Phase400VClass 4A0038G 290 (11.42) 420 (16.54) 305 (12.01) 265 (10.43) 400 (15.75) 8.5 (0.33) 2.5 (0.10) 158 (6.22) 205.5 (8.09) 258 (10.16) 90 (3.54) 95 (3.74) 23.2 (51.15)

Explicit drawing callouts — PDF page 51

Source label/context Source value
Mounting 4-M6
Entrycallout1 3-Φ22
Entrycallout2 3-Φ44

Catalogue — DD.V1000-4X.04 dimension drawing — page 52

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.

Table conditions: PrintedDD.V1000-4X.04. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan1models. Noauto-equivalence toGAAmodelsexceptsourcecontext.

Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.

4X drawing dimension table — PDF page 52

Voltageclass Model(CIMR-V□) W mm(in) H mm(in) D mm(in) W1 mm(in) H1 mm(in) H2 mm(in) t1 mm(in) A mm(in) B mm(in) C mm(in) E mm(in) F mm(in) Weight kg(lb)
Three-Phase200VClass 2A0069G 290 (11.42) 465 (18.31) 305 (12.01) 265 (10.43) 445 (17.52) 8.5 (0.33) 2.5 (0.10) 173 (6.81) 188 (7.40) 248 (9.76) 130 (5.12) 160 (6.30) 27.7 (61.07)

Explicit drawing callouts — PDF page 52

Source label/context Source value
Mounting 4-M6
Entrycallout1 3-Φ22
Entrycallout2 3-Φ50

Catalogue — V1000-4X: source text and annotations — page 53

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options

V1000-4X Drive OPT

Operator, LCD Digital Remote, NEMA Type 1. This option allows the drive to be programmed before installation from a remote location, and provides a 16-character, 5-line alpha-numeric LCD. This option requires Remote Operator Cable (UWR0051 or UWR0052), sold separately. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. JVOP-180

Operator Cable, Remote. These cables are used to connect the Remote LCD Digital Operator (JVOP-180). They are available in one (1) or three (3) meter lengths. Model No. UWR0051 (1 meter) Model No. UWR0052 (3 meter)

Operator Kits, NEMA Type 3R/4X. This option is used to extend an LCD Digital Remote Operator to the wall of a separately priced, oversized UL Type 3R, 4, 4X, or 12 enclosure (IPX6 environment). Price includes a faceplate bezel with digital operator brackets and membrane to cover the operator cutout in the enclosure door, a 3- foot cable, a 10-foot cable, and a 1:1 template for cutting the necessary cutouts in the enclosure. Keypad can be removed after kit installation. Designed for use with the LCD Operator JVOP-180 sold separately. Connects to RJ45 port and mounts to enclosure wall. Model No. UUX000526 (Blank Membrane) Model No. UUX000527 (Yaskawa Logo Membrane)

DriveWizard Plus Software. This optional software package allows upload and download of parameters via PC for data storage and for programming multiple drives. The software also includes graphing and monitoring tools. It is a Windows-based program designed to make startup, commissioning, and troubleshooting of the J1000 as simple as possible. Refer to our website at www.yaskawa.com to download the software, and for more information, including minimum system requirements and cable information to interface a PC to V1000 or J1000 drives. No Model No.

PC Interface Cable. This 6-foot cable interconnects the drive keypad port to the 9-pin communication port on a PC. This cable is used in conjunction with DriveWizard Plus software. Model No. UWR00468-2

USB Copy Unit (Y-Stick). This option allows the drive to connect to the USB port on a PC. It can read, copy and verify drive parameter settings from one drive to another like drive. The unit plugs into the RJ-45 port on the front of the digital operator. Refer to our website at www.yaskawa.com to download the software. Model No. JVOP-181

CopyUnitManager Software for USB Copy Unit (Y-Stick). This option allows the user to transfer and save parameter files from the Copy Unit (JVOP-181), sold separately, to a PC and vice versa. Refer to our website at www.yaskawa.com to download the software. No Model No.

120 VAC Interface. This option mounts directly to the control terminal block on the drive and allows the use of 120 VAC control logic circuits to produce multi-function control input signals for the drive. Model No. DI-100

DriveWorksEZ (DWEZ) Standard and Pro. A software system that provides the means to create custom drive functionality in the V1000 using function block programming to distribute control away from a PLC. Must attend one of the two classes below to obtain software CD.

DriveWorksEZ (DWEZ) Standard Certification. A 3-day V1000 Application Programming training class (TRM010-V1000) must be attended to become certified. Provides 20 connections and 119 basic functions. Model No. CD.DWEZ.02

DriveWorksEZ (DWEZ) Pro Certification. A 2-day DWEZ-specific training class (TRM020-DriveWorksEZ) must be attended to become certified. This class is intended for those well-versed in V1000 programming. DWEZ Pro provides increased functionality, with 50 connections and 225 function blocks compared to the Standard version. Model No. CD.DWEZ.03

To enroll in class, call Technical Training Services at 847-887-7228.

Page

CA.VJ.01, 11/01/11 Data subject to change without notice 51 Yaskawa America, Inc. Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000-4X. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Catalogue — V1000-4X: source text and annotations — page 54

Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.

Options

OPT V1000-4X Drive

DeviceNet™ With ADR. This option complies with all pertinent aspects of the ODVA (Open DeviceNet Vendor Association) specification and AC drive profile. All parameters, diagnostics and operational commands are accessible via DeviceNet. Automatic Device Replacement (ADR) is supported in this DeviceNet option, including the functions of Auto Baud Rate sensing and Faulted Node Recovery (using Group 4 messaging). Each DeviceNet network supports up to 63 drives. Controllers are available from many PLC and/or PC suppliers. The board mounts integrally in the drive and provides a DeviceNet standard open tap connector. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover and a monitor has been added to allow for improved diagnostics. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. SI-N3/V

EtherNet/IP. This option complies with the EtherNet/IP protocol specification, and allows for communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user specified IP address, from a DHCP host, or from a BootP host. The IP address can be set from the drive keypad or from the network. All parameters, diagnostics and operational commands are accessible via EtherNet/IP. The web interface allows management of diagnostic information through a standard web browser. The embedded web pages include the main page, drive status page, network monitor page, and documentation page. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. SI-EN3/V

Profibus DP. This option complies with the Profibus DP protocol specification. All parameters, diagnostics and operational commands are accessible via Profibus. The option board provides a 9-pin (F) type D-Sub connector for easily connecting to a standard Profibus style, shielded twisted-pair cable. Each Profibus network supports up to 99 drives. This option supports all of the Profibus data rates from 9.6 Kbps to 12 Mbps. Up to 32 bytes of input data and 32 bytes of output data are provided per message transaction. Sync and Freeze modes are supported for groups. Profibus DP-V1 support (cyclic and acyclic data exchange). Configurable PPO read and write parameters. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover, and a monitor has been added to allow for improved diagnostics. Option is backwards compatible with the previous generation option cards. Note: This option requires the V1000 drive to contain 1010 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. SI-P3/V

Modbus TCP/IP. This option complies with the Modbus TCP/IP protocol specification. This allows for Modbus communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user-specified IP address, from a DHCP host, or from a BootP host. All parameters, diagnostics and operational commands are accessible via Modbus TCP/IP. This option supports up to 10 simultaneous PLC/PC connections. Note: This option requires the V1000 drive to contain 1015 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EM3/V

CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page Drives & Motion Division

Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000-4X. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.

Manual — Preface, documentation roles and terminology — page 12

Source reference: SIEP C71060618F, December 2016, physical PDF page 12. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.1 Preface i.1 Preface Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products. u Applicable Documentation The following manuals are available for V1000 series drives: u Symbols Note: [term-definition icon] Indicates a supplement or precaution that does not cause drive damage. Indicates a term or definition used in this manual. u Terms and Abbreviations [term-definition icon] • Drive: Yaskawa V1000 Series Drive • PM motor: Permanent Magnet Synchronous Motor (an abbreviation for IPM motor or SPM motor) • IPM motor: Interior Permanent Magnet Motor (e.g., Yaskawa SSR1 Series motor) • SPM motor: Surface Mounted Permanent Magnet Motor (e.g., Yaskawa SMRA Series SPM motor) • PG: Pulse Generator • r/min: Revolutions per Minute • V/f: V/f Control • OLV: Open Loop Vector Control • OLV/PM: Open Loop Vector Control for PM

Illustration of V1000 documentation/drive; no miniature display or pictogram values promoted as model specifications.

Source describes supplied Quick Start Guide and Technical Manual roles; does not prove a separate download is present.

Applicable documentation — PDF page 12

Source row Document Source description
1 V1000 Series AC Drive Quick Start Guide Read this manual first. This guide is packaged together with the product. It contains basic information required to install and wire the drive. This guide provides basic programming and simple setup and adjustment.
2 V1000 Series AC Drive Technical Manual This manual describes installation, wiring, operation procedures, functions, troubleshooting, maintenance, and inspections to perform before operation.

Manual — General precautions and hazard classification — page 13

Source reference: SIEP C71060618F, December 2016, physical PDF page 13. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.2 General Safety i.2 General Safety u Supplemental Safety Information General Precautions • The diagrams in this manual may be indicated without covers or safety shields to show details. Restore covers or shields before operating the drive and run the drive according to the instructions described in this manual. • Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable. • The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. • When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover. • If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office. WARNING Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according to this manual and local codes. The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or possibly even fatal injury or damage to the products or to related equipment and systems. DANGER Indicates a hazardous situation, which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation, which, if not avoided, could result in death or serious injury. WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety message. CAUTION Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury. CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety message. NOTICE Indicates a property damage message. NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety message. u Safety Messages DANGER Heed the safety messages in this manual. Failure to comply will result in death or serious injury. The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.

Manual — Electrical shock, unexpected start, lifting and handling safety — page 14

Source reference: SIEP C71060618F, December 2016, physical PDF page 14. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.2 General Safety DANGER Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level. WARNING Sudden Movement Hazard System may start unexpectedly upon application of power, resulting in death or serious injury. Clear all personnel from the drive, motor and machine area before applying power. Secure covers, couplings, shaft keys and machine loads before applying power to the drive. When using DriveWorksEZ to create custom programming, the drive I/O terminal functions change from factory settings and the drive will not perform as outlined in this manual. Unpredictable equipment operation may result in death or serious injury. Take special note of custom I/O programming in the drive before attempting to operate equipment. Electrical Shock Hazard Do not attempt to modify or alter the drive in any way not explained in this manual. Failure to comply could result in death or serious injury. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Do not allow unqualified personnel to use equipment. Failure to comply could result in death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Crush Hazard Do not use this drive in lifting applications without installing external safety circuitry to prevent accidental dropping of the load. The drive does not possess built-in load drop protection for lifting applications. Failure to comply could result in death or serious injury from falling loads. Install electrical and/or mechanical safety circuit mechanisms independent of drive circuitry. CAUTION Crush Hazard Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling.

Manual — Equipment protection and warning labels — page 15

Source reference: SIEP C71060618F, December 2016, physical PDF page 15. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.2 General Safety NOTICE Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not perform a withstand voltage test on any part of the drive. Failure to comply could result in damage to the sensitive devices within the drive. Do not operate damaged equipment. Failure to comply could result in further damage to the equipment. Do not connect or operate any equipment with visible damage or missing parts. Install adequate branch circuit short circuit protection per applicable codes. Failure to comply could result in damage to the drive. The drive is suitable for circuits capable of delivering not more than 31,000 RMS symmetrical Amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400 V Class). Do not expose the drive to halogen group disinfectants. Failure to comply may cause damage to the electrical components in the drive. Do not pack the drive in wooden materials that have been fumigated or sterilized. Do not sterilize the entire package after the product is packed. u Drive Label Warnings Always heed the warning information listed in Figure i.1 in the position shown in Figure i.2 . Figure i.1 Warning Information Figure i.2 Warning Information Position

WARNING — Risk of electric shock. Read manual before installing. Wait 5 minutes for capacitor discharge after disconnecting power supply. To conform to CE requirements, make sure to ground the supply neutral for 400V class.

Warning Label — location illustration on drive. Illustration geometry and miniature product artwork remain in original; no model-specific rating inferred.

Manual — Warranty restrictions and quick reference — page 16

Source reference: SIEP C71060618F, December 2016, physical PDF page 16. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.2 General Safety u Warranty Information n Restrictions The drive was not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or health. Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa representatives or the nearest Yaskawa sales office. This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident. u Quick Reference Easily Set Application-Specific Parameters Preset parameter defaults are available for many applications. Refer to Application Selection on page 96. Run a Motor of One-Frame Larger Capacity When using this drive for variable torque loads such as fans and pumps, a motor one frame size larger can be used. Refer to C6-01: Drive Duty Selection on page 155 Know the Details of Safety Measures The functions listed below affect the safe operation of the drive. Ensure that the settings fit the application requirements prior to operation. Operation of digital outputs during Auto-tuning. Rotational Auto-tuning allows for normal digital output operation. Non-rotational Auto-tuning does not allow for normal digital output operation. Safe operations. Run by power on. Parameter setting b1-17. LOCAL/REMOTE key effective during stop in drive mode. Parameter o2-01. LED operator stop key priority selection. Parameter o2-02. Enter press required after changing the keypad frequency reference. Parameter o2-05. Operation interlock when program mode is selected. Parameter b1-08. Replace the Drive The removable terminal block with parameter backup function allows the transfer of parameter settings after drive replacement. Refer to Dismantling the Removable Terminal Block on page 319. Drive a Synchronous PM Motor The V1000 drive can operate synchronous PM motors. Refer to Subchart A3: Operation with Permanent Magnet Motors on page 94. Perform Auto-Tuning Automatic tuning sets motor parameters. Refer to Auto-Tuning on page 102. Check the Maintenance Period Using Drive Monitors The maintenance period of fans and capacitors can be checked with drive monitors. Refer to Performance Life Monitors on page 314

Manual — Quick reference and historical compliance logos — page 17

Source reference: SIEP C71060618F, December 2016, physical PDF page 17. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.2 General Safety Drive or Motor Faults are Displayed on a Digital Operator Refer to Fault Displays, Causes, and Possible Solutions on page 267 and Refer to Detailed Alarm Codes, Causes, and Possible Solutions on page 282. Standards Compliance Refer to European Standards on page 466 and Refer to UL and CSA Standards on page 474.

CE; cULus LISTED; CSA. Source symbols only; current certification validity and applicability not verified.

Manual — Reactor selection, drive capacity, stopping and repetitive duty — page 18

Source reference: SIEP C71060618F, December 2016, physical PDF page 18. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.3 Application Precautions i.3 Application Precautions u General Application Precautions n Selecting a Reactor An AC reactor or DC link choke can be used for the following: • to suppress harmonic current. • to smooth peak current that results from capacitor switching. • when the power supply is above 600 kVA. • when the drive is running from a power supply system with thyristor converters. Note: A DC link choke is built in to 200 V and 400 V class models with a capacity of 22 kW and higher (HD rating). Figure i.3 Installing a Reactor n Drive Capacity Make sure that the motor rated current is less than the rated nameplate output current of the drive. When running more than one motor in parallel from a single drive, the drive rated current should 1.1 times larger than the total motor rated current for all connected motors or nuisance drive faults may occur. n Starting Torque The overload rating of the drive determines the starting and accelerating characteristics of the motor. Expect lower running torque than when running the motor from line power. To get more starting torque, use a larger drive or increase both the motor and drive capacity. n Emergency/Fast Stop During a drive fault condition, a protective circuit is activated and drive output is shut off. The motor may coast to a stop or attempt to decelerate depending on parameter settings. If the emergency/fast stop cannot stop the load as fast as desired, a customer-supplied mechanical brake may be required. Test emergency stop circuitry before putting drive into operation. n Options The B1, B2, +1, +2, and +3 terminals are used to connect optional power devices. Connect only devices compatible with the drive. n Repetitive Starting/Stopping Applications with frequent starts and stops often exceed 150% of their rated current values. Heat stress generated from repetitive high current can shorten the life span of the IGBTs. The expected lifetime for the IGBTs is about 8 million start and stop cycles with a 4 kHz carrier frequency and a 150% peak current. Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. The user can also choose to reduce the load, increase the acceleration and deceleration times, or switch to a larger drive. This will help keep peak current levels under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during the initial test run, and make adjustments accordingly.

Power Supply Capacity (kVA): 0, 600, 4000. Drive Capacity (kVA): 60, 400. Regions: Power supply harmonics reactor required; Reactor unnecessary. Original plot boundaries retained; no interpolation inferred.

Manual — Installation, settings, wiring and input contactor conditions — page 19

Source reference: SIEP C71060618F, December 2016, physical PDF page 19. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.3 Application Precautions u Installation Environment n Enclosure Panels Keep the drive in a clean environment by either selecting an area free of airborne dust, lint, and oil mist, or install the drive in an enclosure panel. Be sure to leave the required space between drives to provide for cooling, and that proper measures are taken so that the ambient temperature remains within allowable limits. Keep flammable materials away from the drive. If the drive must be used in an area where it is subjected to oil mist and excessive vibration, protective designs are available. Contact Yaskawa or your Yaskawa agent for details. n Installation Direction The drive should be installed upright as specified in the manual. u Settings n Motor Code If using OLV/PM designed for permanent magnet motors (A1-02 = 5), make sure that the proper motor code is set in parameter E5-01 before performing a trial run. n Upper Limits The drive is capable of running the motor up to 400 Hz. Due to the danger of accidentally operating the motor at high speed, be sure to set the upper frequency limit. The default setting for the maximum output frequency is 60 Hz. n DC Injection Braking Motor overheat can result if there is too much current used during DC Injection Braking, or if the DC Injection Braking time is too long. n Acceleration/Deceleration Times Acceleration and deceleration times are affected by how much torque the motor generates, the load torque, and the inertia moment ((GD2)/4). Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as long as the Stall Prevention function is operating. For faster acceleration and deceleration, install a braking option or increase the capacity of the drive. u General Handling NOTICE: Wiring Check. Never connect the power supply lines to output terminals U/T1, V/T2, or W/T3. Doing so will destroy the drive. Be sure to perform a final check of all control wiring and other connections before applying line power. Make sure there are no short circuits on the control terminals (+V, AC, etc.), as this could damage the drive. n Selecting a Molded Case Circuit Breaker (MCCB) or Ground Fault Circuit Interrupter (GFCI) Yaskawa recommends installing a GFCI on the line power supply to protect drive wiring and prevent damage in the event of component failure. An MCCB may also be used if permitted by the power system. The GFCI should be designed for use with an AC drive (i.e., protected against harmonics) MCCB selection depends on the power factor for the drive, determined by the power supply voltage, output frequency, and load. Refer to Installing Peripheral Devices on page 330 for more information on breaker installation. Note that a larger capacity breaker is needed when using a fully electromagnetic MCCB, as operation characteristics vary with harmonic current. n Magnetic Contactor (MC) Installation Use an MC to ensure that line power to the drive can be completely shut off when necessary. The MC should be wired so that it opens when the drive fault output is triggered. Avoid switching the MC on the power supply side more frequently than once every 30 minutes. Frequent switching can cause damage to the drive.

Manual — Inspection, maintenance and motor operation — page 20

Source reference: SIEP C71060618F, December 2016, physical PDF page 20. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.3 Application Precautions n Inspection and Maintenance DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Disconnect all power to the drive, wait at least five minutes after all indicators are OFF, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing to prevent electrical shock. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and make sure the heatsink has cooled to a safe level. WARNING! Electrical Shock Hazard. Wait for at least the time specified on the drive warning label after opening the load switch on the output side before any inspection or maintenance of permanent magnet (PM) motors. Failure to comply could result in death or serious injury. WARNING! Sudden Movement Hazard. Install a switch disconnect between the motor and the drive in applications where the machine can still rotate even though the drive has fully stopped. Unpredictable equipment operation may result in death or serious injury. WARNING! Sudden Movement Hazard. Do not attempt to move a load that could potentially rotate the motor faster than the maximum allowable r/min when the drive has been shut off. Unpredictable equipment operation may result in death or serious injury. NOTICE: Do not open and close the motor disconnect switch while the motor is running, as this may damage the drive. NOTICE: If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped before closing the load switch. n Wiring All wire ends should use ring terminals for UL/cUL compliance. Use only the tools recommended by the terminal manufacturer for crimping. n Transporting the Drive NOTICE: Prevent the drive from contact with salts, fluorine, bromine, phthalate ester, and other such harmful chemicals. Never steam clean the drive. Failure to comply may cause damage to the drive components. u Notes on Motor Operation n Using a Standard Motor Low Speed Range The cooling fan of a standard motor is usually designed to sufficiently cool the motor at the rated speed. As the self-cooling capability of such a motor reduces with the speed, applying full torque at low speed will possibly damage the motor. To prevent motor damage from overheat, reduce the load torque as the motor slows. Figure i.4 shows the allowable load characteristics for a Yaskawa standard motor. A motor designed specifically for operation with a drive should be used when 100% continuous torque is needed at low speeds. Figure i.4 Allowable Load Characteristics for a Yaskawa Motor Insulation Tolerance Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly long wiring distances. Contact Yaskawa or your Yaskawa agent for consultation.

Torque (%): 50, 60, 70, 80, 90, 100. Frequency (Hz): 3, 6, 20, 60. Duty labels: 25% ED (or 15 min); 40% ED (or 20 min); 60% ED (or 40 min); Continuous operation. Original curves remain authoritative; no interpolated torque or geometry inferred.

Manual — Motor operation and synchronous motor restrictions — page 21

Source reference: SIEP C71060618F, December 2016, physical PDF page 21. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.3 Application Precautions High Speed Operation Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed. Contact the motor or machine manufacturer. Torque Characteristics Torque characteristics differ compared to operating the motor directly from line power. The user should have a full understanding of the load torque characteristics for the application. Vibration and Shock The drive settings allow the user to choose between high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce motor oscillation. Take particular caution when using a variable speed drive for an application that is conventionally run from line power at a constant speed. If mechanical resonance occurs, install shock-absorbing rubber around the base of the motor and enable the Jump frequency selection parameter to prevent continuous operation in the resonant frequency range. Audible Noise Noise created during run varies by the carrier frequency setting. When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running from line power. Operating above the rated r/min, however, can create unpleasant motor noise. n Using a Synchronous Motor • Synchronous motors cannot be started directly from line power. Applications requiring line power to start should use an induction motor with the drive. • A single drive is not capable of running multiple synchronous motors at the same time. Use a standard induction motor for such setups. • At start, a synchronous motor may rotate slightly in the opposite direction of the Run command depending on parameter settings and motor type. • The amount of starting torque that can be generated differs by each control mode and by the type of motor being used. Set up the motor with the drive after verifying the starting torque, allowable load characteristics, impact load tolerance, and speed control range. Contact Yaskawa or your Yaskawa agent if you plan to use a motor that does not fall within these specifications. • Braking Torque: In Open Loop Vector Control for PM motors, braking torque is less than 125% when running between 20% to 100% speed, even with a braking resistor. Braking torque drops to less than half when running at less than 20% speed. • Load Inertia: In Open Loop Vector Control for PM motors, the allowable load inertia moment is approximately 50 times higher than the motor inertia moment or less. Contact Yaskawa or your Yaskawa agent concerning applications with a larger inertia moment. • Holding Brake: When using a holding brake in Open Loop Vector Control for PM motors, release the brake prior to starting the motor. Failure to set the proper timing can result in speed loss. Not for use with conveyor, transport, or hoist type applications. • Restarting a Coasting Motor: To restart a coasting motor rotating at over 200 Hz while in the V/f control mode, use the Short Circuit Braking function to first bring the motor to a stop. Short Circuit Braking requires a special braking resistor. Contact Yaskawa or your Yaskawa agent for details. Speed Search can be used to restart a coasting motor rotating slower than 200 Hz. If the motor cable is relatively long, however, the motor should instead be stopped using Short Circuit Braking, which forces the motor to stop by creating a short-circuit in the motor windings. n Applications with Specialized Motors Multi-Pole Motor Because the rated current will differ from a standard motor, be sure to check the maximum current when selecting a drive. Always stop the motor before switching between the number of motor poles. If a regen overvoltage (oV) fault occurs or if overcurrent protection (oC) is triggered, the motor will coast to stop. Submersible Motor Because motor rated current is greater than a standard motor, select the drive capacity accordingly. Be sure to use a large enough gauge motor cable to avoid decreasing the maximum torque level on account of voltage drop caused by a long motor cable.

Manual — Special motor and power machinery limitations — page 22

Source reference: SIEP C71060618F, December 2016, physical PDF page 22. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

i.3 Application Precautions Explosion-Proof Motor Both the motor and drive need to be tested together to be certified as explosion-proof. The drive is not designed for explosion proof areas. Furthermore, if an encoder is attached to an explosion-proof motor make sure the encoder is also explosion-proof. Use an insulating signal converter for connecting the encoder signal lines to the drives speed feedback option card. Geared Motor To avoid gear damage when operating at low speeds or very high speeds, make sure that both the gear and lubricant are rated for the desired speed range. Consult with the manufacturer for applications that require operation outside the rated speed range of the motor or gear box. Single-Phase Motor Variable speed AC drives are not designed for operation with single phase motors. Using capacitors to start the motor causes excessive current to flow and can damage drive components. A split-phase start or a repulsion start can end up burning out the starter coils because the internal centrifugal switch is not activated. The drive is for use with 3-phase motors only. Motor with Brake Caution should be taken when using a drive to operate a motor with a built-in holding brake. If the brake is connected to the output side of the drive, it may not release at start due to low voltage levels. A separate power supply should be installed for the motor brake. Motors with a built-in brake tend to generate a fair amount of noise when running at low speeds. n Power Driven Machinery (decelerators, belts, chains, etc.) Continuous operation at low speeds wears on the lubricating material used in gear box type systems to accelerate and decelerate power driven machinery. Caution should also be taken when operating at speeds above the rated machine speed due to noise and shortened performance life.

Manual — Receiving safety, ESD and PWM motor heating — page 24

Source reference: SIEP C71060618F, December 2016, physical PDF page 24. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.1 Section Safety 1.1 Section Safety CAUTION Do not carry the drive by the front cover. Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury. NOTICE Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. A motor connected to a PWM drive may operate at a higher temperature than a utility-fed motor and the operating speed range may reduce motor cooling capacity. Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the additional heating with the intended operating conditions.

Manual — Receiving checks, example nameplate and model-code ratings — page 25

Source reference: SIEP C71060618F, December 2016, physical PDF page 25. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.2 Model Number and Nameplate Check. Please perform the following tasks after receiving the drive: Inspect the drive for damage. If the drive appears damaged upon receipt, contact the shipper immediately. Verify receipt of the correct model by checking the information on the nameplate. If you have received the wrong model or the drive does not function properly, contact your supplier. Nameplate. Figure 1.1 Nameplate Information Example. <1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate. Model-code table headers: No. / Region Code; No. / Customized Specifications; No. / Enclosure Type; No. / Voltage Class; No. / Environmental Specification <3>. <1> Refer to manual TOBPC71060635 for more information on these models. <2> Refer to manual TOBPC71060621 for more information on these models. <3> Drives with these specifications do not guarantee complete protection for the specified environmental condition. Single-Phase 200 V Class. Chapter 1: Receiving.

Nameplate Information Example only. MODEL: CIMR-V followed by blank boxes. MAX APPLI. MOTOR: 0.75kW / 0.4kW; REV: A. INPUT: AC3PH 200-240V 50 / 60Hz 2.7A / 1.4A. OUTPUT: AC3PH 0-240V 0-400Hz 1.2A / 0.8A. MASS: 0.6kg. PRG: blank boxes. O/N and S/N: blank. FILE NO.: E131457. IP20; PASS; MADE IN JAPAN; IND.CONT.EQ. 7J48. YASKAWA ELECTRIC CORPORATION, 2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan. Source logos cULus LISTED, CE, TÜV SÜD Product Service, RoHS. Legend A: Normal Duty Amps / Heavy Duty Amps; B: Software version; C: CE and TÜV Certification; D: Enclosure type; E: Address <1>; F: Serial number; G: Lot number; H: Output specifications; I: Input specifications; J: AC drive model. Example and historical logo data only, not an actual installed unit or current certification verification.

CIMR - V U 2 A 0001 F A A. CIMR: Drive; V: V1000 Series; final A: Design Revision Order. Other positions refer to bounded model-code tables. Example only; not a guarantee that every combination is available.

Refer to the tables below. Pointer from model capacity digits to rating tables; initial single-phase table continues on PDF26.

Figure1.1 model-code key. Example identity not an actual purchased unit. Footnotes1/2 refer separate manuals;footnote3 says protection not guaranteed. No inferred order-code applicability.

Nameplate code Region code — PDF page 25

Source row Code Region code
1 U USA

Nameplate code Customized specifications — PDF page 25

Source row Code Customized specifications
1 A Standard model

Nameplate code Voltage class — PDF page 25

Source row Code Voltage class
1 B 1-phase, 200-240 Vac
2 2 3-phase, 200-240 Vac
3 4 3-phase, 380-480 Vac

Nameplate code Enclosure type — PDF page 25

Source row Code Enclosure type
1 A IP00/Open-Chassis
2 B IP20/Open-Chassis
3 F IP20/NEMA Type 1
4 G NEMA 4X/IP66 <1>
5 J IP20/Finless <2>
6 L IP00/Finless <2>

Nameplate code Environmental specification — PDF page 25

Source row Code Environmental specification
1 A Standard
2 M Humidity- and dust-resistant
3 S Vibration-resistant

Single-phase200V class initial ratings — PDF page 25

Source row Model Normal duty max motor kW Normal duty rated output A Heavy duty max motor kW Heavy duty rated output A
1 BA0001 0.2 1.2 0.1 0.8
2 BA0002 0.4 1.9 0.2 1.6
3 BA0003 0.75 3.3 0.4 3.0
4 BA0006 1.1 6.0 0.75 5.0
5 BA0010 2.2 9.6 1.5 8.0
6 BA0012 3.0 12.0 2.2 11.0

Manual — Rating tables: single-phase continuation and three-phase classes — page 26

Source reference: SIEP C71060618F, December 2016, physical PDF page 26. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.2 Model Number and Nameplate Check <1> Available with Heavy Duty rating only. n Three-Phase 200 V Class n Three-Phase 400 V Class Note: Refer to Component Names on page 28 for differences regarding enclosure protection types and component descriptions.

Single-phase200V continuation from PDF25; BA0018 HD only — PDF page 26

Source row Model Normal duty max motor kW Normal duty rated output A Heavy duty max motor kW Heavy duty rated output A
1 BA0018 <1> – – 3.7 17.5

Three-phase200V ratings — PDF page 26

Source row Model Normal duty max motor kW Normal duty rated output A Heavy duty max motor kW Heavy duty rated output A
1 2A0001 0.2 1.2 0.1 0.8
2 2A0002 0.4 1.9 0.2 1.6
3 2A0004 0.75 3.5 0.4 3.0
4 2A0006 1.1 6.0 0.75 5.0
5 2A0010 2.2 9.6 1.5 8.0
6 2A0012 3.0 12.0 2.2 11.0
7 2A0020 5.5 19.6 3.7 17.5
8 2A0030 7.5 30.0 5.5 25.0
9 2A0040 11 40.0 7.5 33.0
10 2A0056 15 56.0 11 47.0
11 2A0069 18.5 69.0 15 60.0

Three-phase400V ratings — PDF page 26

Source row Model Normal duty max motor kW Normal duty rated output A Heavy duty max motor kW Heavy duty rated output A
1 4A0001 0.4 1.2 0.2 1.2
2 4A0002 0.75 2.1 0.4 1.8
3 4A0004 1.5 4.1 0.75 3.4
4 4A0005 2.2 5.4 1.5 4.8
5 4A0007 3.0 6.9 2.2 5.5
6 4A0009 3.7 8.8 3.0 7.2
7 4A0011 5.5 11.1 3.7 9.2
8 4A0018 7.5 17.5 5.5 14.8
9 4A0023 11 23.0 7.5 18.0
10 4A0031 15 31.0 11 24.0
11 4A0038 18.5 38.0 15 31.0

Manual — Drive models and enclosure types — page 27

Source reference: SIEP C71060618F, December 2016, physical PDF page 27. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.3 Drive Models and Enclosure Types 1.3 Drive Models and Enclosure Types The following table describes drive enclosures and models. Table 1.1 Drive Models and Enclosure Types Receiving 1 Two types of enclosures are offered for V1000 drives. • IP20/Open-Chassis and IP00/Open-Chassis models are often placed inside a large enclosure panel where the front of the drive is covered to prevent someone from accidentally touching charged components. • IP20/NEMA Type 1 models mount to an indoor wall and not inside a large enclosure panel.

Single-Phase 200 V Class | BA0001B

Single-Phase 200 V Class | BA0002B

Single-Phase 200 V Class | BA0003B

Single-Phase 200 V Class | BA0006B

Single-Phase 200 V Class | BA0010B

Single-Phase 200 V Class | BA0012B

Single-Phase 200 V Class | BA0018B

Three-Phase 200 V Class | 2A0001B

Three-Phase 200 V Class | 2A0002B

Three-Phase 200 V Class | 2A0004B

Three-Phase 200 V Class | 2A0006B

Three-Phase 200 V Class | 2A0010B

Three-Phase 200 V Class | 2A0012B

Three-Phase 200 V Class | 2A0020B

Three-Phase 200 V Class | –

Three-Phase 400 V Class | 4A0001B

Three-Phase 400 V Class | 4A0002B

Three-Phase 400 V Class | 4A0004B

Three-Phase 400 V Class | 4A0005B

Three-Phase 400 V Class | 4A0007B

Three-Phase 400 V Class | 4A0009B

Three-Phase 400 V Class | 4A0011B

Three-Phase 400 V Class | –

Table1.1 enclosure model availability — PDF page 27

Source row Voltage class IP20/Open-Chassis drive model IP00/Open-Chassis drive model IP20/NEMA Type1 drive model
1 Single-Phase 200 V Class BA0001B – BA0001F
2 Single-Phase 200 V Class BA0002B – BA0002F
3 Single-Phase 200 V Class BA0003B – BA0003F
4 Single-Phase 200 V Class BA0006B – BA0006F
5 Single-Phase 200 V Class BA0010B – BA0010F
6 Single-Phase 200 V Class BA0012B – BA0012F
7 Single-Phase 200 V Class BA0018B – BA0018F
8 Three-Phase 200 V Class 2A0001B – 2A0001F
9 Three-Phase 200 V Class 2A0002B – 2A0002F
10 Three-Phase 200 V Class 2A0004B – 2A0004F
11 Three-Phase 200 V Class 2A0006B – 2A0006F
12 Three-Phase 200 V Class 2A0010B – 2A0010F
13 Three-Phase 200 V Class 2A0012B – 2A0012F
14 Three-Phase 200 V Class 2A0020B – 2A0020F
15 Three-Phase 200 V Class – 2A0030A 2A0030F
16 Three-Phase 200 V Class – 2A0040A 2A0040F
17 Three-Phase 200 V Class – 2A0056A 2A0056F
18 Three-Phase 200 V Class – 2A0069A 2A0069F
19 Three-Phase 400 V Class 4A0001B – 4A0001F
20 Three-Phase 400 V Class 4A0002B – 4A0002F
21 Three-Phase 400 V Class 4A0004B – 4A0004F
22 Three-Phase 400 V Class 4A0005B – 4A0005F
23 Three-Phase 400 V Class 4A0007B – 4A0007F
24 Three-Phase 400 V Class 4A0009B – 4A0009F
25 Three-Phase 400 V Class 4A0011B – 4A0011F
26 Three-Phase 400 V Class – 4A0018A 4A0018F
27 Three-Phase 400 V Class – 4A0023A 4A0023F
28 Three-Phase 400 V Class – 4A0031A 4A0031F
29 Three-Phase 400 V Class – 4A0038A 4A0038F

Manual — Component illustration and source-specific legend — page 28

Source reference: SIEP C71060618F, December 2016, physical PDF page 28. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.4 Component Names 1.4 Component Names This section illustrates the drive components as they are mentioned in this manual. u IP20/Open-Chassis n Single-Phase AC 200 V BA0001B to BA0003B Three-Phase AC 200 V 2A0001B to 2A0006B Figure 1.2 Exploded View of IP20/Open-Chassis Type Components (Model 2A0006B) <1> Models BA0001B to BA0003B and 2A0001B to 2A0004B do not have a cooling fan or a cooling fan cover.

Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.

A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 F – Terminal cover

G – Front cover screw H – Front cover I – Comm port J – LED operator Refer to Using the Digital LED Operator on page 80 K – Case L – Cooling fan <1>

Manual — Component illustration and source-specific legend — page 29

Source reference: SIEP C71060618F, December 2016, physical PDF page 29. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.4 Component Names n Single-Phase AC 200 V BA0006B to BA0018B Three-Phase AC 200 V 2A0010B to 2A0020B Three-Phase AC 400 V 4A0001B to 4A0011B Receiving 1 Figure 1.3 Exploded View of IP20/Open-Chassis Type Components (Model 2A0012B) <1> Models BA0006B and 4A0001B to 4A0004B do not have a cooling fan or a cooling fan cover. Model BA0018B has two cooling fans.

Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.

A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Comm port F – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 G – Front cover screw

H – Front cover I – Terminal cover J – Bottom cover K – LED operator Refer to Using the Digital LED Operator on page 80 L – Case M – Cooling fan <1>

Manual — Component illustration and source-specific legend — page 30

Source reference: SIEP C71060618F, December 2016, physical PDF page 30. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.4 Component Names u IP00/Open-Chassis n Three-Phase AC 200 V 2A0030A to 2A0069A Three-Phase AC 400 V 4A0018A to 4A0038A Figure 1.4 Exploded View of IP00/Open-Chassis Type Components (Model 4A0018A)

Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.

A – Fan cover B – Cooling Fan C – Mounting hole D – Heatsink E – Optional 24 VDC power supply connector cover F – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 G – Bottom cover

H – Front cover screw I – Front cover J – Terminal cover K – Comm port L – LED operator Refer to Using the Digital LED Operator on page 80 M – Case

Manual — Component illustration and source-specific legend — page 31

Source reference: SIEP C71060618F, December 2016, physical PDF page 31. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.4 Component Names u IP20/NEMA Type 1 Enclosure n Single-Phase AC 200 V BA0001F to BA0003F Three-Phase AC 200 V 2A0001F to 2A0006F Receiving 1 Figure 1.5 Exploded View of IP20/NEMA Type 1 Components (Model 2A0006F) <1> Models BA0001F to BA0003F and 2A0001F to 2A0004F do not have a cooling fan or a cooling fan cover.

Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.

A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 F – Bottom cover screws G – Rubber bushing H – Bottom front cover

I – Front cover screws J – Front cover K – Comm port L – LED operator Refer to Using the Digital LED Operator on page 80 M – Case N – Top cover O – Cooling fan <1>

Manual — Component illustration and source-specific legend — page 32

Source reference: SIEP C71060618F, December 2016, physical PDF page 32. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.4 Component Names n Single-Phase AC 200 V BA0006F to BA0018F Three-Phase AC 200 V 2A0010F to 2A0020F Three-Phase AC 400 V 4A0001F to 4A0011F Figure 1.6 Exploded view of IP20/NEMA Type 1 Components (Model 2A0012F) <1> Models BA0006B and 4A0001B to 4A0004B do not have a cooling fan or a cooling fan cover. Model BA0018B has two cooling fans.

Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.

A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 F – Cover screws G – Rubber bushing H – Bottom cover

I – Front cover screws J – Front cover K – Terminal cover L – Comm port M – LED operator Refer to Using the Digital LED Operator on page 80 N – Case O – Top cover P – Cooling fan <1>

Manual — Component illustration and source-specific legend — page 33

Source reference: SIEP C71060618F, December 2016, physical PDF page 33. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.4 Component Names n Three-Phase AC 200 V 2A0030F to 2A0069F Three-Phase AC 400 V 4A00018F to 4A0038F Receiving 1 Figure 1.7 Exploded View of IP20/NEMA Type 1 Components (Model 4A0018F)

Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.

A – Fan cover B – Cooling fan C – Mounting Hole D – Case and Heatsink E – Optional 24 VDC power supply connection cover F – Cover screws G – Rubber bushing H – Bottom cover

I – Front cover screws J – Terminal cover K – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 L – Front cover M – Comm port N – LED operator Refer to Using the Digital LED Operator on page 80 O – Case P – Top cover

Manual — Component illustration and source-specific legend — page 34

Source reference: SIEP C71060618F, December 2016, physical PDF page 34. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

1.4 Component Names u Front Views Figure 1.8 Front Views of Drives

Front-view example models 2A0006B and 2A0012B. Callouts A–I correspond to same-page legend; original terminal and switch geometry retained.

A – Terminal board connector B – DIP switch S1 Refer to DIP Switch S1 Analog Input Signal Selection on page 70 C – DIP switch S3 Refer to Sinking/ Sourcing Mode Switch on page 68 D – Control circuit terminal Refer to Control Circuit Wiring on page 63 E – Main circuit terminal Refer to Wiring the Main Circuit Terminal on page 62

F – Ground terminal G – Terminal cover H – Option card connector Refer to Connecting the Option Card on page 338 I – DIP switch S2 Refer to MEMOBUS/ Modbus Termination on page 71

Manual — Mechanical installation safety and cooling — page 36

Source reference: SIEP C71060618F, December 2016, physical PDF page 36. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.1 Section Safety 2.1 Section Safety WARNING Fire Hazard Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet. Failure to comply could result in overheating and fire. When multiple drives are placed inside the same enclosure panel, install proper cooling to ensure air entering the enclosure does not exceed 40 °C. CAUTION Crush Hazard Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling. NOTICE Observe proper electrostatic discharge (ESD) procedures when handling the drive. Failure to comply could result in ESD damage to the drive circuitry. It may be difficult to perform maintenance on the cooling fans of drives installed in a vertical row inside an enclosure. Ensure adequate spacing at the top of the drive to perform cooling fan replacement when required. Operating the motor in the low-speed range diminishes the cooling effects, increases motor temperature, and may lead to motor damage by overheating. Reduce the motor torque in the low-speed range whenever using a standard blower cooled motor. If 100% torque is required continuously at low speed, consider using a special drive or vector motor. Select a motor that is compatible with the required load torque and operating speed range. Do not operate motors above the maximum rated RPM. Failure to comply may lead to bearing or other mechanical motor failures. The speed range for continuous operation differs according to the lubrication method and motor manufacturer. If the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer. Continuously operating an oil-lubricated motor in the low-speed range may result in burning.

Manual — Motor wiring, explosion-proof system and motor restrictions — page 37

Source reference: SIEP C71060618F, December 2016, physical PDF page 37. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.1 Section Safety NOTICE When the wiring distance is greater than 100 meters, pay special attention to the motor insulation voltage or use a drive-rated motor. Failure to comply could lead to motor winding failure. Motor vibration may increase when operating a machine in variable-speed mode, if that machine previously operated at a constant speed. Install vibration-proof rubber on the motor base or use the frequency jump function to skip a frequency resonating the machine. The motor may require more acceleration torque with drive operation than with a commercial power supply. Set a proper V/f pattern by checking the load torque characteristics of the machine to be used with the motor. The rated input current of submersible motors is higher than the rated input current of standard motors. Select an appropriate drive according to its rated output current. When the distance between the motor and drive is long, use a cable thick enough to connect the motor to the drive to prevent motor torque reduction. When using an explosion-proof motor, it must be subject to an explosion-proof test in conjunction with the drive. This is also applicable when an existing explosion-proof motor is to be operated with the drive. Since the drive itself is not explosion-proof, always install it in a safe place. Be sure to set A1-02 to “0” when using an explosion-proof motor. Do not use a drive for a single-phase motor. Replace the motor with a three-phase motor. If an oil-lubricated gearbox or speed reducer is used in the power transmission mechanism, oil lubrication will be affected when the motor operates only in the low speed range. The power transmission mechanism will make noise and experience problems with service life and durability if the motor is operated at a speed higher than the rated speed. Installation Mechanical 2

Manual — Installation environment and orientation — page 38

Source reference: SIEP C71060618F, December 2016, physical PDF page 38. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation 2.2 Mechanical Installation This section outlines specifications, procedures, and environment for proper mechanical installation of the drive. u Installation Environment To help prolong the optimum performance life of the drive, install the drive in the proper environment. Table 2.1 describes the appropriate environment for the drive. Table 2.1 Installation Environment NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat. NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive. Failure to comply could result in erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise. u Installation Orientation and Spacing Install the drive upright as illustrated in Figure 2.1 to maintain proper cooling. A – Correct B – Incorrect Figure 2.1 Correct Installation Orientation

Figure2.1 A: Correct upright orientation; B: Incorrect orientations. Original orientation drawings remain authoritative.

Table2.1 Installation environment — PDF page 38

Source row Environment Conditions
1 Installation Area Indoors
2 Ambient Temperature IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F) IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F) Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F) NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F) Drive reliability improves in environments without wide temperature fluctuations. When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels. Do not allow ice to develop on the drive.
3 Humidity 95% RH or less and free of condensation
4 Storage Temperature -20 °C to +60 °C (-4 °F to +104 °F)
5 Surrounding Area Install the drive in an area free from: • oil mist and dust • metal shavings, oil, water or other foreign materials • radioactive materials • combustible materials (e.g., wood) • harmful gases and liquids • excessive vibration • chlorides • direct sunlight
6 Altitude Up to 1000 meters without derating; up to 3000 meters with output current, ambient temperature, and voltage derating. Refer to Altitude Derating on page 352 for details.
7 Vibration 10 to 20 Hz at 9.8 m/s2 20 to 55 Hz at 5.9 m/s2
8 Orientation Install the drive vertically to maintain maximum cooling effects.

Manual — Single and multiple drive spacing — page 39

Source reference: SIEP C71060618F, December 2016, physical PDF page 39. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation n Single Drive Installation Figure 2.2 shows the required installation spacing to maintain sufficient space for airflow and wiring. Install the heatsink against a closed surface to avoid diverting cooling air around the heatsink. Figure 2.2 Correct Installation Spacing Note: IP20/NEMA Type 1, IP00/Open-Chassis, and IP20/Open-Chassis models require the same amount of space above and below the drive for installation. n Multiple Drive Installation When installing multiple drives into the same enclosure panel, mount the drives according to Figure 2.2. When mounting drives with a minimum side-by-side clearance of 2 mm according to Figure 2.3, derating must be considered and parameter L8-35 must be set. Refer to Parameter List on page 353. Installation Mechanical 2 Figure 2.3 Space Between Drives (Side-by-Side Mounting) Note: When installing drives of different heights in the same enclosure panel, the tops of the drives should line up. Leave space between the top and bottom of stacked drives for cooling fan replacement if required. Using this method, it is possible to replace the cooling fans later. NOTICE: When mounting IP20/NEMA Type 1 enclosure drives side by side, the top covers of all drives must be removed as shown in Figure 2.4. Figure 2.4 IP20/NEMA Type 1 Side-by-Side Mounting in Enclosure

Figure2.2 Side Clearance A; Top/Bottom Clearance C; B airflow direction. The numeric legend is preserved separately; geometry remains original-only.

A – 30 mm minimum; B – Airflow direction; C – 100 mm minimum.

2 mm between adjacent drives; A top alignment, B side clearance, C top/bottom clearance, D airflow direction. Read with derating and L8-35 requirement and complete same-page instructions. Geometry original-only.

A – Line up the tops of the drives; B – 30 mm minimum; C – 100 mm minimum; D – Airflow direction.

IP20/NEMA Type1 side-by-side mounting in enclosure; source instruction requires removal of top covers. Illustration geometry remains original-only.

Manual — Dimension page index and protective design — page 40

Source reference: SIEP C71060618F, December 2016, physical PDF page 40. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation u Removing and Attaching the Protective Covers Refer to Electrical Installation on page 47, for information regarding the removal and reattachment of protective covers. u Exterior and Mounting Dimensions Table 2.2 Drive Models and Types Note: Refer to Specifications on page 341 for information on the amount of heat generated by the drive and appropriate cooling methods.

Source model groups and dimension-page references; cross-row borders explicitly followed. No implied compatibility across groups.

Table2.2 Drive models and dimension page references — PDF page 40

Source row Protective design Single-phase200V Three-phase200V Three-phase400V Page
1 IP20/Open-Chassis BA0001B BA0002B BA0003B 2A0001B 2A0002B 2A0004B 2A0006B – 41
2 IP20/Open-Chassis BA0006B BA0010B BA0012B BA0018B 2A0010B 2A0012B 2A0020B 4A0001B 4A0002B 4A0004B 4A0005B 4A0007B 4A0009B 4A0011B 41
3 IP00/Open-Chassis – 2A0030A 2A0040A 2A0056A 2A0069A 4A0018A 4A0023A 4A0031A 4A0038A 43
4 IP20/NEMA Type 1 BA0001F BA0002F BA0003F 2A0001F 2A0002F 2A0004F – 44
5 IP20/NEMA Type 1 BA0006F BA0010F BA0012F BA0018F 2A0006F 2A0010F 2A0012F 2A0020F 4A0001F 4A0002F 4A0004F 4A0005F 4A0007F 4A0009F 4A0011F 44
6 IP20/NEMA Type 1 – 2A0030F 2A0040F 2A0056F 2A0069F 4A0018F 4A0023F 4A0031F 4A0038F 46

Manual — Mounting dimensions and weights without EMC filter — page 41

Source reference: SIEP C71060618F, December 2016, physical PDF page 41. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation n IP20/Open-Chassis Drives Table 2.3 IP20/Open-Chassis (without an EMC filter) Installation Table 2.4 IP20/Open-Chassis (without an EMC filter) Mechanical 2

W, W1, H, H1, H2, D, D1, t1; 2-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

W, W1, H, H1, H2, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.

Single-Phase 200 V Class | BA0001B

Single-Phase 200 V Class | BA0002B

Single-Phase 200 V Class | BA0003B

Three-Phase 200 V Class | 2A0001B

Three-Phase 200 V Class | 2A0002B

Three-Phase 200 V Class | 2A0004B

Three-Phase 200 V Class | 2A0006B

Single-Phase 200 V Class | BA0006B

Single-Phase 200 V Class | BA0010B

Single-Phase 200 V Class | BA0012B

Single-Phase 200 V Class | BA0018B

Table2.3 IP20/Open-Chassis without EMC filter — PDF page 41

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) D1 mm (in) t1 mm (in) Wt kg (lb)
1 Single-Phase 200 V Class BA0001B 68 (2.68) 128 (5.04) 76 (2.99) 56 (2.20) 118 (4.65) 5 (0.20) 6.5 (0.26) 3 (0.12) 0.6 (1.3)
2 Single-Phase 200 V Class BA0002B 68 (2.68) 128 (5.04) 76 (2.99) 56 (2.20) 118 (4.65) 5 (0.20) 6.5 (0.26) 3 (0.12) 0.6 (1.3)
3 Single-Phase 200 V Class BA0003B 68 (2.68) 128 (5.04) 118 (4.65) 56 (2.20) 118 (4.65) 5 (0.20) 38.5 (1.52) 5 (0.20) 1.0 (2.2)
4 Three-Phase 200 V Class 2A0001B 68 (2.68) 128 (5.04) 76 (2.99) 56 (2.20) 118 (4.65) 5 (0.20) 6.5 (0.26) 3 (0.12) 0.6 (1.3)
5 Three-Phase 200 V Class 2A0002B 68 (2.68) 128 (5.04) 76 (2.99) 56 (2.20) 118 (4.65) 5 (0.20) 6.5 (0.26) 3 (0.12) 0.6 (1.3)
6 Three-Phase 200 V Class 2A0004B 68 (2.68) 128 (5.04) 108 (4.25) 56 (2.20) 118 (4.65) 5 (0.20) 38.5 (1.52) 5 (0.20) 0.9 (2.0)
7 Three-Phase 200 V Class 2A0006B 68 (2.68) 128 (5.04) 128 (5.04) 56 (2.20) 118 (4.65) 5 (0.20) 58.5 (2.30) 5 (0.20) 1.1 (2.4)

Table2.4 IP20/Open-Chassis without EMC filter — PDF page 41

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) D1 mm (in) t1 mm (in) Wt kg (lb)
1 Single-Phase 200 V Class BA0006B 108 (4.25) 128 (5.04) 137.5 (5.41) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.7 (3.7)
2 Single-Phase 200 V Class BA0010B 108 (4.25) 128 (5.04) 154 (6.06) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.8 (4.0)
3 Single-Phase 200 V Class BA0012B 140 (5.51) 128 (5.04) 163 (6.42) 128 (5.04) 118 (4.65) 5 (0.20) 65 (2.56) 5 (0.20) 2.4 (5.3)
4 Single-Phase 200 V Class BA0018B 170 (6.69) 128 (5.04) 180 (7.09) 158 (6.22) 118 (4.65) 5 (0.20) 65 (2.56) 5 (0.20) 3.0 (6.6)

Manual — Mounting dimensions and weights without EMC filter — page 42

Source reference: SIEP C71060618F, December 2016, physical PDF page 42. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation

W, W1, H, H1, H2, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.

Three-Phase 200 V Class | 2A0010B

Three-Phase 200 V Class | 2A0012B

Three-Phase 200 V Class | 2A0020B

Three-Phase 400 V Class | 4A0001B

Three-Phase 400 V Class | 4A0002B

Three-Phase 400 V Class | 4A0004B

Three-Phase 400 V Class | 4A0005B

Three-Phase 400 V Class | 4A0007B

Three-Phase 400 V Class | 4A0009B

Three-Phase 400 V Class | 4A0011B

Table2.4 continuation IP20/Open-Chassis without EMC filter — PDF page 42

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) D1 mm (in) t1 mm (in) Wt kg (lb)
1 Three-Phase 200 V Class 2A0010B 108 (4.25) 128 (5.04) 129 (5.08) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.7 (3.7)
2 Three-Phase 200 V Class 2A0012B 108 (4.25) 128 (5.04) 137.5 (5.41) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.7 (3.7)
3 Three-Phase 200 V Class 2A0020B 140 (5.51) 128 (5.04) 143 (5.63) 128 (5.04) 118 (4.65) 5 (0.20) 65 (2.56) 5 (0.20) 2.4 (5.3)
4 Three-Phase 400 V Class 4A0001B 108 (4.25) 128 (5.04) 81 (3.19) 96 (3.78) 118 (4.65) 5 (0.20) 10 (0.39) 5 (0.20) 1.0 (2.2)
5 Three-Phase 400 V Class 4A0002B 108 (4.25) 128 (5.04) 99 (3.90) 96 (3.78) 118 (4.65) 5 (0.20) 28 (1.10) 5 (0.20) 1.2 (2.6)
6 Three-Phase 400 V Class 4A0004B 108 (4.25) 128 (5.04) 137.5 (5.41) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.7 (3.7)
7 Three-Phase 400 V Class 4A0005B 108 (4.25) 128 (5.04) 154 (6.06) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.7 (3.7)
8 Three-Phase 400 V Class 4A0007B 108 (4.25) 128 (5.04) 154 (6.06) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.7 (3.7)
9 Three-Phase 400 V Class 4A0009B 108 (4.25) 128 (5.04) 154 (6.06) 96 (3.78) 118 (4.65) 5 (0.20) 58 (2.28) 5 (0.20) 1.7 (3.7)
10 Three-Phase 400 V Class 4A0011B 140 (5.51) 128 (5.04) 143 (5.63) 128 (5.04) 118 (4.65) 5 (0.20) 65 (2.56) 5 (0.20) 2.4 (5.3)

Manual — Mounting dimensions and weights without EMC filter — page 43

Source reference: SIEP C71060618F, December 2016, physical PDF page 43. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation n IP00/Open-Chassis Drives Table 2.5 IP00/Open-Chassis (without an EMC filter) Installation Mechanical 2

W, W1, H, H1, H2, H4, D, D1, t1; 4-d. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.

Three-Phase 200 V Class | 2A0030A

Three-Phase 200 V Class | 2A0040A

Three-Phase 200 V Class | 2A0056A

Three-Phase 200 V Class | 2A0069A

Three-Phase 400 V Class | 4A0018A

Three-Phase 400 V Class | 4A0023A

Three-Phase 400 V Class | 4A0031A

Three-Phase 400 V Class | 4A0038A

Table2.5 IP00/Open-Chassis without EMC filter — PDF page 43

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) H4 mm (in) D1 mm (in) d t1 mm (in) Wt kg (lb)
1 Three-Phase 200 V Class 2A0030A 140 (5.5) 254 (9.7) 140 (5.5) 122 (4.8) 234 (9.2) 248 (9.8) 13 (0.5) 55 (2.2) M5 5 (0.2) 3.8 (7.9)
2 Three-Phase 200 V Class 2A0040A 140 (5.5) 254 (9.7) 140 (5.5) 122 (4.8) 234 (9.2) 248 (9.8) 13 (0.5) 55 (2.2) M5 5 (0.2) 3.8 (7.9)
3 Three-Phase 200 V Class 2A0056A 180 (7.1) 290 (11.2) 163 (6.4) 160 (6.3) 270 (10.6) 284 (11.2) 15 (0.6) 75 (3.0) M5 5 (0.2) 5.5 (11.7)
4 Three-Phase 200 V Class 2A0069A 220 (8.7) 350 (13.2) 187 (7.4) 192 (7.6) 320 (12.6) 336 (13.2) 15 (0.6) 78 (3.1) M6 5 (0.2) 9.2 (19.2)
5 Three-Phase 400 V Class 4A0018A 140 (5.5) 254 (9.7) 140 (5.5) 122 (4.8) 234 (9.2) 248 (9.8) 13 (0.5) 55 (2.2) M5 5 (0.2) 3.8 (7.9)
6 Three-Phase 400 V Class 4A0023A 140 (5.5) 254 (9.7) 140 (5.5) 122 (4.8) 234 (9.2) 248 (9.8) 13 (0.5) 55 (2.2) M5 5 (0.2) 3.8 (7.9)
7 Three-Phase 400 V Class 4A0031A 180 (7.1) 290 (11.2) 143 (5.6) 160 (6.3) 270 (10.6) 284 (11.2) 15 (0.6) 55 (2.2) M5 5 (0.2) 5.2 (11.0)
8 Three-Phase 400 V Class 4A0038A 180 (7.1) 290 (11.2) 163 (6.4) 160 (6.3) 270 (10.6) 284 (11.2) 15 (0.6) 75 (3.0) M5 5 (0.2) 5.5 (11.7)

Manual — Mounting dimensions and weights without EMC filter — page 44

Source reference: SIEP C71060618F, December 2016, physical PDF page 44. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation n IP20/NEMA Type 1 Drives Table 2.6 IP20/NEMA Type 1 (without an EMC filter) Table 2.7 IP20/NEMA Type 1 (without an EMC filter)

W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 2-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.

Single-Phase 200 V Class | BA0001F

Single-Phase 200 V Class | BA0002F

Single-Phase 200 V Class | BA0003F

Three-Phase 200 V Class | 2A0001F

Three-Phase 200 V Class | 2A0002F

Three-Phase 200 V Class | 2A0004F

Three-Phase 200 V Class | 2A0006F

Single-Phase 200 V Class | BA0006F

Single-Phase 200 V Class | BA0010F

Single-Phase 200 V Class | BA0012F

Single-Phase 200 V Class | BA0018F

Table2.6 IP20/NEMA Type1 without EMC filter — PDF page 44

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) H3 mm (in) H4 mm (in) H5 mm (in) H6 mm (in) D1 mm (in) t1 mm (in) Wt kg (lb)
1 Single-Phase 200 V Class BA0001F 68 (2.68) 149.5 (5.89) 76 (2.99) 56 (2.20) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 6.5 (0.26) 3 (0.12) 0.8 (1.8)
2 Single-Phase 200 V Class BA0002F 68 (2.68) 149.5 (5.89) 76 (2.99) 56 (2.20) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 6.5 (0.26) 3 (0.12) 0.8 (1.8)
3 Single-Phase 200 V Class BA0003F 68 (2.68) 149.5 (5.89) 118 (4.65) 56 (2.20) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 38.5 (1.54) 5 (0.20) 1.2 (2.6)
4 Three-Phase 200 V Class 2A0001F 68 (2.68) 149.5 (5.89) 76 (2.99) 56 (2.20) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 6.5 (0.26) 3 (0.12) 0.8 (1.8)
5 Three-Phase 200 V Class 2A0002F 68 (2.68) 149.5 (5.89) 76 (2.99) 56 (2.20) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 6.5 (0.26) 3 (0.12) 0.8 (1.8)
6 Three-Phase 200 V Class 2A0004F 68 (2.68) 149.5 (5.89) 108 (4.25) 56 (2.20) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 38.5 (1.54) 5 (0.20) 1.1 (2.4)
7 Three-Phase 200 V Class 2A0006F 68 (2.68) 149.5 (5.89) 128 (5.04) 56 (2.20) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58.5 (2.32) 5 (0.20) 1.3 (2.9)

Table2.7 IP20/NEMA Type1 without EMC filter — PDF page 44

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) H3 mm (in) H4 mm (in) H5 mm (in) H6 mm (in) D1 mm (in) t1 mm (in) Wt kg (lb)
1 Single-Phase 200 V Class BA0006F 108 (4.25) 149.5 (5.89) 137.5 (5.41) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 1.9 (4.2)
2 Single-Phase 200 V Class BA0010F 108 (4.25) 149.5 (5.89) 154 (6.06) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 2.0 (4.4)
3 Single-Phase 200 V Class BA0012F 140 (5.51) 153 (6.02) 163 (6.42) 128 (5.04) 128 (5.03) 118 (4.65) 4.8 (0.19) 20 (0.79) 5 (0.20) 5 (0.20) 65 (2.56) 5 (0.20) 2.6 (5.7)
4 Single-Phase 200 V Class BA0018F 170 (6.69) 171 (6.73) 180 (7.08) 158 (6.22) 133 (5.23) 118 (4.64) 4.8 (0.19) 38 (1.50) 5 (0.20) 5 (0.20) 65 (2.56) 5 (0.20) 3.3 7.3

Manual — Mounting dimensions and weights without EMC filter — page 45

Source reference: SIEP C71060618F, December 2016, physical PDF page 45. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation Installation Mechanical 2

W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.

Three-Phase 200 V Class | 2A0010F

Three-Phase 200 V Class | 2A0012F

Three-Phase 200 V Class | 2A0020F

Three-Phase 400 V Class | 4A0001F

Three-Phase 400 V Class | 4A0002F

Three-Phase 400 V Class | 4A0004F

Three-Phase 400 V Class | 4A0005F

Three-Phase 400 V Class | 4A0007F

Three-Phase 400 V Class | 4A0009F

Three-Phase 400 V Class | 4A0011F

Table2.7 continuation IP20/NEMA Type1 without EMC filter — PDF page 45

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) H3 mm (in) H4 mm (in) H5 mm (in) H6 mm (in) D1 mm (in) t1 mm (in) Wt kg (lb)
1 Three-Phase 200 V Class 2A0010F 108 (4.25) 149.5 (5.89) 129 (5.08) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 1.9 (4.2)
2 Three-Phase 200 V Class 2A0012F 108 (4.25) 149.5 (5.89) 137.5 (5.41) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 1.9 (4.2)
3 Three-Phase 200 V Class 2A0020F 140 (5.51) 153 (6.02) 143 (5.63) 128 (5.04) 128 (5.03) 118 (4.65) 4.8 (0.19) 20 (0.79) 5 (0.20) 5 (0.20) 65 (2.56) 5 (0.20) 2.6 (5.7)
4 Three-Phase 400 V Class 4A0001F 108 (4.25) 149.5 (5.89) 81 (3.19) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 10 (0.39) 5 (0.20) 1.2 (2.6)
5 Three-Phase 400 V Class 4A0002F 108 (4.25) 149.5 (5.89) 99 (3.90) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 28 (1.10) 5 (0.20) 1.4 (3.1)
6 Three-Phase 400 V Class 4A0004F 108 (4.25) 149.5 (5.89) 137.5 (5.41) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 1.9 (4.2)
7 Three-Phase 400 V Class 4A0005F 108 (4.25) 149.5 (5.89) 154 (6.06) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 1.9 (4.2)
8 Three-Phase 400 V Class 4A0007F 108 (4.25) 149.5 (5.89) 154 (6.06) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 1.9 (4.2)
9 Three-Phase 400 V Class 4A0009F 108 (4.25) 149.5 (5.89) 154 (6.06) 96 (3.78) 128 (5.03) 118 (4.65) 4 (0.16) 20 (0.79) 5 (0.20) 1.5 (0.06) 58 (2.28) 5 (0.20) 1.9 (4.2)
10 Three-Phase 400 V Class 4A0011F 140 (5.51) 153 (6.02) 143 (5.63) 128 (5.04) 128 (5.03) 118 (4.65) 4.8 (0.19) 20 (0.79) 5 (0.20) 5 (0.20) 65 (2.56) 5 (0.20) 2.6 (5.7)

Manual — Mounting dimensions and weights without EMC filter — page 46

Source reference: SIEP C71060618F, December 2016, physical PDF page 46. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

2.2 Mechanical Installation Table 2.8 IP20/NEMA Type 1 (without an EMC filter)

W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 4-d. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.

Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.

Three- Phase 200 V Class | 2A0030F

Three- Phase 200 V Class | 2A0040F

Three- Phase 200 V Class | 2A0056F

Three- Phase 200 V Class | 2A0069F

Three- Phase 400 V Class | 4A0018F

Three- Phase 400 V Class | 4A0023F

Three- Phase 400 V Class | 4A0031F

Three- Phase 400 V Class | 4A0038F

Table2.8 IP20/NEMA Type1 without EMC filter — PDF page 46

Source row Voltage class Drive model W mm (in) H mm (in) D mm (in) W1 mm (in) H1 mm (in) H2 mm (in) H3 mm (in) H4 mm (in) H5 mm (in) H6 mm (in) D1 mm (in) t1 mm (in) d Wt kg (lb)
1 Three- Phase 200 V Class 2A0030F 140 (5.51) 254 (10.00) 140 (5.51) 122 (4.80) 234 (9.21) 248 (9.76) 6 (0.24) 13 (0.51) 13 (0.51) 1.5 (0.06) 55 (2.17) 5 (0.20) M5 3.8 (8.4)
2 Three- Phase 200 V Class 2A0040F 140 (5.51) 254 (10.00) 140 (5.51) 122 (4.80) 234 (9.21) 248 (9.76) 6 (0.24) 13 (0.51) 13 (0.51) 1.5 (0.06) 55 (2.17) 5 (0.20) M5 3.8 (8.4)
3 Three- Phase 200 V Class 2A0056F 180 (7.09) 290 (11.42) 163 (6.42) 160 (6.30) 270 (10.63) 284 (11.18) 6 (0.24) 15 (0.59) 13 (0.51) 1.5 (0.06) 75 (2.95) 5 (0.20) M5 5.5 (12.1)
4 Three- Phase 200 V Class 2A0069F 220 (8.66) 350 (13.78) 187 (7.36) 192 (7.56) 320 (12.60) 336 (13.23) 7 (0.28) 15 (0.59) 22 (0.87) 1.5 (0.06) 78 (3.07) 5 (0.20) M6 9.2 (20.3)
5 Three- Phase 400 V Class 4A0018F 140 (5.51) 254 (10.00) 140 (5.51) 122 (4.80) 234 (9.21) 248 (9.76) 6 (0.24) 13 (0.51) 13 (0.51) 1.5 (0.06) 55 (2.17) 5 (0.20) M5 3.8 (8.4)
6 Three- Phase 400 V Class 4A0023F 140 (5.51) 254 (10.00) 140 (5.51) 122 (4.80) 234 (9.21) 248 (9.76) 6 (0.24) 13 (0.51) 13 (0.51) 1.5 (0.06) 55 (2.17) 5 (0.20) M5 3.8 (8.4)
7 Three- Phase 400 V Class 4A0031F 180 (7.09) 290 (11.42) 143 (5.63) 160 (6.30) 270 (10.63) 284 (11.18) 6 (0.24) 15 (0.59) 13 (0.51) 1.5 (0.06) 55 (2.17) 5 (0.20) M5 5.2 (11.5)
8 Three- Phase 400 V Class 4A0038F 180 (7.09) 290 (11.42) 163 (6.42) 160 (6.30) 270 (10.63) 284 (11.18) 6 (0.24) 13 (0.51) 13 (0.51) 1.5 (0.06) 75 (2.95) 5 (0.20) M5 5.5 (12.1)

Manual — Electrical installation hazards and brake protection — page 48

Source reference: SIEP C71060618F, December 2016, physical PDF page 48. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.1 Section Safety 3.1 Section Safety DANGER Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. WARNING Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of AC drives. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Always use a thermal overload relay or an over-temperature contact when using a braking resistor. Failure to comply could result in death or serious injury by fire. Power to the drive should be interrupted when the relay is triggered.

Manual — Electrical wiring notices and lead routing — page 49

Source reference: SIEP C71060618F, December 2016, physical PDF page 49. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.1 Section Safety NOTICE Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Route motor leads U/T1, V/T2, and W/T3 separate from other leads to reduce possible interference-related issues. Failure to comply may result in abnormal operation of drive and nearby equipment. Installation Electrical 3

Manual — Standard connection prerequisites and relay minimum load — page 50

Source reference: SIEP C71060618F, December 2016, physical PDF page 50. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.2 Standard Connection Diagram 3.2 Standard Connection Diagram Connect the drive and peripheral devices as shown in Figure 3.. It is possible to run the drive via the digital operator without connecting digital I/O wiring. This section does not discuss drive operation; Refer to Start-Up Programming & Operation on page 77 for instructions on operating the drive. NOTICE: Inadequate branch short circuit protection could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable codes. The drive is suitable for circuits capable of delivering not more than 31,000 RMS symmetrical amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400 V Class). NOTICE: When the wiring distance is greater than 100 meters, pay special attention to the motor insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown. NOTICE: Correctly set Sink/Source jumper S3 for internal power supply. Failure to comply may result in damage to the drive. Refer to I/O Connections on page 68 for details. NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction. NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to comply may result in abnormal operation of drive and nearby equipment. NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA. If a circuit requires less than 10 mA (reference value), connect it to a photocoupler output (P1, P2, PC). Improper application of peripheral devices could result in damage to the photocoupler output of the drive.

Manual — Standard connection diagram — section title — page 51

Source reference: SIEP C71060618F, December 2016, physical PDF page 51. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.2 Standard Connection Diagram

Figure 3.1 Drive Standard Connection Diagram (original geometry retained). V1000 main circuit/control circuit. Terminals +1, +2, −, B1 and B2 are for connecting options; never connect power supply lines to these terminals. Single-phase 200 V power supply uses R/L1 and S/L2; three-phase power supply for 200 V / 400 V shows R/L1, S/L2, T/L3. Optional DC link choke, jumper +2/+1, optional thermal relay and braking resistor B1/B2. Motor outputs U/T1, V/T2, W/T3; separate cooling fan labels r1, s1, t1 and FU, FV, FW. Ground: 10 Ω or less (400 V class), 100 Ω or less (200 V class). Wiring sequence should shut off power to drive when fault output triggers; 1 MCCB, MC, 2 MCCB; braking resistor unit thermal relay trip contact; fault relay contact; labels TRX, THRX, OFF, ON, MC, SA, MB, contacts 1 and 2. Digital input defaults: S1 Forward run/stop; S2 Reverse run/stop; S3 External fault; S4 Fault reset; S5 Multi-step speed 1 main/aux switch; S6 Multi-step speed 2; S7 Jog reference; SC common. +24 V 8 mA; 24 V; 0 V; DIP switch S3 Sink/Source; shield ground terminal. Option card connector. DIP switch S1 V/I. Digital relay output Fault: MA, MB, MC, 250 Vac 10 mA to 1 A / 30 Vdc 10 mA to 1 A (default). Digital photocoupler output 5 to 48 Vdc, 2 to 50 mA (default): P1 During Run (photocoupler 1); P2 Frequency agree (photocoupler 2); PC photocoupler output common. Main speed frequency reference, multi-function programmable; 2 kΩ potentiometer; RP pulse train input max. 32 kHz; +V setting power supply +10.5 max. 20 mA; A1 0 to +10 V (20 kΩ); A2 0 to +10 V (20 kΩ), (0)4 to 20 mA (250 Ω); AC. MP pulse train output 0 to 32 kHz; AM analog monitor output 0 to +10 Vdc (2 mA); AC. Safe Disable Input: safety switch, HC, H1, jumper. DIP switch S2; termination resistor 120 Ω, 1/2 W; communications connector; R+, R-, S+, S-, IG; MEMOBUS/Modbus communications RS-485/422; cable shield ground. Legend: shielded line, twisted-pair shielded line, main circuit terminal, control terminal. Read footnotes 1–6 on PDF 51 and 7–8 on PDF 52; no wiring topology inferred from this label inventory.

<1> Remove the jumper when installing an optional DC link choke. <2> The MC on the input side of the main circuit should open when the thermal relay is triggered. <3> Self-cooled motors do not require separate cooling fan motor wiring. <4> Connected using sequence input signal (S1 to S7) from NPN transistor; Default: sink mode (0 V com). <5> Use only a +24 V internal power supply in sinking mode; the source mode requires an external power supply. Refer to I/O Connections on page 68 for details. <6> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters and wattmeters; they are not intended for use as a feedback-type of signal.

Installation Electrical 3

Manual — Standard connection footnotes 7–8 and three-wire setup warnings — page 52

Source reference: SIEP C71060618F, December 2016, physical PDF page 52. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.2 Standard Connection Diagram <7> Disconnect the wire jumper between HC and H1 when utilizing the safety input. Refer to Wiring Procedure on page 66 for details on removing the jumper. The wire length for the Safe Disable input should not exceed 30 m. Use only dry contacts on safety inputs HC-H1. External power supplies are not permitted. <8> Note that if the drive is set to trigger a fault output whenever the fault restart function is activated (L5-02 = 1), then a sequence to interrupt power when a fault occurs will result in shutting off the power to the drive as the drive attempts to restart itself. The default setting for L5-02 is 0 (fault output active during restart attempt). WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal parameter is properly set (S5 for 3-Wire; H1-05 = “0”). Improper sequencing of run/stop circuitry could result in death or serious injury from moving equipment. WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on terminal S1 may cause the drive to start. WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run command at power up (default). If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter b1-17 is set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at power up of the drive and may cause injury. WARNING! When the application preset function is executed (or A1-06 is set to any value other than 0) the drive I/O terminal functions change. This may cause unexpected operation and potential damage to equipment or injury. Figure 3.2 illustrates an example of a 3-Wire sequence.

Figure 3.2 3-Wire Sequence example: Stop relay (N.C.); Run relay (N.O.); Drive S1 Run command (run on momentary close); S2 Stop command (stop on momentary open); S5 Forward/reverse command (multi-function input: H1-05 = 0); SC Sequence input common. Original connection geometry remains authoritative.

Manual — Main circuit and negative DC bus warning; single-phase model scope — page 53

Source reference: SIEP C71060618F, December 2016, physical PDF page 53. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.3 Main Circuit Connection Diagram 3.3 Main Circuit Connection Diagram Refer to diagrams in this section for the Main Circuit wiring connections. Connections may vary based on drive capacity. The main circuit DC power supply powers the control circuit. NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high voltage DC potential. Improper wiring connections could result in damage to the drive. u Single-Phase 200 V Class Models BA0001 to BA0018

Figure 3.3 Connecting Single-Phase Main Circuit Terminals. BA0001 to BA0018, single-phase 200 Vac. Drive labels R/L1, S/L2, −, +2, +1, B1, B2; outputs U/T1, V/T2, W/T3 to Motor; ground symbol. Jumper; DC reactor (option); Braking Resistor Unit (option). Connection geometry original-only; single-phase refers to supply input.

NOTICE: Do not connect T/L3 terminal when using single-phase power supply input. Incorrect wiring may damage the drive. u Three-Phase 200 V Class Models 2A0001 to 2A0069 Three-Phase 400 V Class Models 4A0001 to 4A0038

Figure 3.4 Connecting Three-Phase Main Circuit Terminals. Three-phase 200 V Class 2A0001 to 2A0069; 400 V Class 4A0001 to 4A0038. Three phase 200 Vac (400 Vac); drive R/L1, S/L2, T/L3, −, +2, +1, B1, B2; outputs U/T1, V/T2, W/T3; Motor, ground symbol, jumper, DC reactor (option), Braking Resistor Unit (option). Original diagram retains connection geometry.

Installation Electrical 3

Manual — Terminal block configuration scope — page 54

Source reference: SIEP C71060618F, December 2016, physical PDF page 54. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Source limitation for this page: Source illustrations contain unlabelled screw heads and clipped/hidden side terminal names. All visible group labels checked at5x; unsupported group6 minus assertion superseded by F3172, visible ground/CHARGE context supplied. Do not infer hidden names.

3.4 Terminal Block Configuration 3.4 Terminal Block Configuration The figures in this section provide illustrations of the main circuit terminal block configurations of the different drive sizes.

CIMR-V□BA0001, 0002, 0003 and CIMR-V□2A0001, 0002, 0004, 0006. Visible terminal labels R/L1, S/L2, T/L3, +1, U/T1, V/T2, W/T3; −, +2, B1, B2; ground symbols.

CIMR-V□BA0006, 0010, 0012; CIMR-V□2A0010, 0012, 0020; CIMR-V□4A0001, 0002, 0004, 0005, 0007, 0009, 0011. Visible labels −, +1, +2; R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3; ground symbols.

CIMR-V□2A0030, 0040 and CIMR-V□4A0018, 0023. Visible labels R/L1, S/L2, T/L3, −, +1, +2, U/T1, V/T2, W/T3. Other screw/terminal geometry remains original-only; do not infer hidden brake-terminal labels.

CIMR-V□2A0069. Visible labels +1, +2, B1, B2; R/L1, S/L2, T/L3, −, U/T1, V/T2, W/T3. Other geometry remains original-only.

CIMR-V□BA0018. Visible labels R/L1, S/L2, −, +1, +2, B1, B2, U/T1, V/T2, W/T3; ground symbols.

Figure 3.5 Main Circuit Terminal Block Configurations

CIMR-V□2A0056 and CIMR-V□4A0031, 0038. Visible labels R/L1, S/L2, T/L3, +1, +2, U/T1, V/T2, W/T3; ground symbols are visible below. The side terminal edges and upper screw heads have no legible terminal names in this illustration. No visible minus label is supported here; no hidden brake-terminal labels or wiring topology inferred.

Figure3.5 also visibly draws ground symbols below the model groups CIMR-V□2A0030,0040 / CIMR-V□4A0018,0023; CIMR-V□2A0069; and CIMR-V□2A0056 / CIMR-V□4A0031,0038. These are glyph descriptions only, not a wiring route or terminal-rating assertion.

In Figure3.5 model CIMR-V□2A0069 illustration, the vertical left-side inscription visibly reads CHARGE. This is an illustration inscription, not an observed energized indicator state.

Manual — Protective covers — procedures, legends and enclosure conditions — page 55

Source reference: SIEP C71060618F, December 2016, physical PDF page 55. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.5 Protective Covers 3.5 Protective Covers Follow the procedure below to remove the protective covers before wiring the drive and to reattach the covers after wiring is complete. u IP20/Open-Chassis Front and Bottom Cover Removal and Installation n Removing the Protective Covers 1. Loosen the screw that locks the front cover in place to remove. Figure 3.6 Remove the Front Cover on an IP20/Open-Chassis Drive 2. Apply pressure to the tabs on each side of the terminal cover. Pull the terminal cover away from the drive while pushing in on the tabs to pull the cover free. Figure 3.7 Remove the Terminal Cover on an IP20/Open-Chassis Drive n Reattaching the Protective Covers Properly connect all wiring and route power wiring away from control signal wiring. Reattach all protective covers when wiring is complete. Apply only a small amount of pressure to lock the cover back into place. Figure 3.8 Reattach the Protective Covers on an IP20/Open-Chassis Drive

Installation Electrical 3

Manual — Protective covers — procedures, legends and enclosure conditions — page 56

Source reference: SIEP C71060618F, December 2016, physical PDF page 56. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.5 Protective Covers u IP20/NEMA Type 1 Front and Bottom Cover Removal and Installation n Removing the Protective Covers on an IP20/NEMA 1, UL Type 1 Design 1. Loosen the screw on the front cover to remove the front cover. Figure 3.9 Remove the Front Cover on an IP20/NEMA 1, UL Type 1 Drive 2. Loosen the screw on the terminal cover to remove the terminal cover and expose the conduit bracket. A B A – Conduit bracket B – Terminal cover Figure 3.10 Remove the Terminal Cover on an IP20/NEMA 1, UL Type 1 Drive 3. Loosen two screws attaching the conduit bracket to remove. A A –Conduit bracket Figure 3.11 Remove the Conduit Bracket on an IP20/NEMA 1, UL Type 1 Drive

Manual — Protective covers — procedures, legends and enclosure conditions — page 57

Source reference: SIEP C71060618F, December 2016, physical PDF page 57. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.5 Protective Covers n Reattaching the Protective Covers Pass power wiring and control signal wiring through the exit holes on the bottom of the conduit bracket of the drive. Place power wiring and control signal wiring in separate conduits. Properly connect all wiring after installing the drive and connecting other devices. Reattach all protective covers when wiring is complete. A A –Pass power wiring and control signal wiring through different exit holes at the bottom of the drive. Figure 3.12 Reattach the Protective Covers and Conduit Bracket on an IP20/NEMA 1, UL Type 1 Drive u IP20/NEMA Type 1 Top Cover Removal and Installation To improve the ambient temperature rating of a NEMA Type 1 drive from 40 °C to 50 °C or to mount NEMA Type 1 drives side-by-side, the top cover can be removed. Remove the top cover and set L8-35 to “2”. Refer to Temperature Derating on page 351 for details. Note: Removing the top cover of a NEMA Type 1 drive converts the drive to an IP20/Open-Chassis rating, and the drive will no longer have a NEMA Type 1 rating. n Removing the Top Cover Insert the blade of a straight-edge screwdriver into the opening of the top cover. Gently lift up on the front cover as indicated by the arrow in Figure 3.13 to remove it from the drive. Figure 3.13 Removing the Top Cover n Reattaching the Top Cover Align the connection tabs on the underside of the top cover with the connection tabs on the drive. Pinch in on the top cover to click the cover into place on the drive. Connection tabs Figure 3.14 Reattaching the Top Cover

Installation Electrical 3

Manual — Main circuit wiring introduction and prohibition on soldered ends — page 58

Source reference: SIEP C71060618F, December 2016, physical PDF page 58. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.6 Main Circuit Wiring 3.6 Main Circuit Wiring This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit of the drive. NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections. u Main Circuit Terminal Functions Table 3.1 Main Circuit Terminal Functions

u Wire Gauges and Tightening Torques Select the appropriate wires and crimp terminals from Table 3.2 through Table 3.4. Note: 1. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient temperature within 30 °C and wiring distance shorter than 100 m. 2. Terminals ⊕1, ⊕2, ⊖, B1 and B2 are for connecting optional devices such as a braking resistor. Do not connect other non-specified devices to these terminals. • Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate the amount of voltage drop: • Line drop voltage (V) = √3 x wire resistance (Ω/km) x wire length (m) x current (A) x 10-3 • Refer to instruction manual TOBP C720600 00 for braking unit or braking resistor unit wire gauges. • Refer to UL Standards Compliance on page 474 for information on UL compliance. n Single-Phase 200 V Class Table 3.2 Wire Gauge and Torque Specifications

R/L1 | Main circuit power supply input

S/L2 | Main circuit power supply input

T/L3 | Main circuit power supply input

U/T1 | Drive output

V/T2 | Drive output

W/T3 | Drive output

B1 | Braking resistor

B2 | Braking resistor

⊕1 | DC link choke connection

⊕2 | DC link choke connection

⊕1 | DC power supply input

⊖ | DC power supply input

[ground symbol] (2 terminals) | Ground

BA0001 BA0002 BA0003 | R/L1, S/L2, T/L3

BA0001 BA0002 BA0003 | U/T1, V/T2, W/T3

BA0001 BA0002 BA0003 | ⊖, ⊕1, ⊕2

BA0001 BA0002 BA0003 | B1, B2

BA0001 BA0002 BA0003 | [ground symbol]

BA0006 | R/L1, S/L2, T/L3

BA0006 | U/T1, V/T2, W/T3

BA0006 | ⊖, ⊕1, ⊕2

BA0006 | B1, B2

BA0006 | [ground symbol]

Table 3.1 Main Circuit Terminal Functions — PDF page 58

Source row Terminal Type Function Reference
1 R/L1 Main circuit power supply input Connects line power to the drive. Drives with single-phase 200 V input power use terminals R/L1 and S/L2 only. Do NOT use T/L3. 53
2 S/L2 Main circuit power supply input Connects line power to the drive. Drives with single-phase 200 V input power use terminals R/L1 and S/L2 only. Do NOT use T/L3. 53
3 T/L3 Main circuit power supply input Connects line power to the drive. Drives with single-phase 200 V input power use terminals R/L1 and S/L2 only. Do NOT use T/L3. 53
4 U/T1 Drive output Connects to the motor. 61
5 V/T2 Drive output Connects to the motor. 61
6 W/T3 Drive output Connects to the motor. 61
7 B1 Braking resistor Available for connecting a braking resistor or the braking resistor unit option. 72
8 B2 Braking resistor Available for connecting a braking resistor or the braking resistor unit option. 72
9 ⊕1 DC link choke connection These terminals are shorted at shipment. Remove the shorting bar between ⊕1 and ⊕2 when connecting a DC link choke to this terminal. 331
10 ⊕2 DC link choke connection These terminals are shorted at shipment. Remove the shorting bar between ⊕1 and ⊕2 when connecting a DC link choke to this terminal. 331
11 ⊕1 DC power supply input For connecting a DC power supply. –
12 ⊖ DC power supply input For connecting a DC power supply. –
13 [ground symbol] (2 terminals) Ground Grounding Terminal 62

Table 3.2 Single-Phase 200 V Class — PDF page 58

Source row Drive model Terminal Recommended gauge (AWG, kcmil) Wire range (AWG, kcmil) Screw size Tightening torque N·m (lb.in.)
1 BA0001 BA0002 BA0003 R/L1, S/L2, T/L3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
2 BA0001 BA0002 BA0003 U/T1, V/T2, W/T3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
3 BA0001 BA0002 BA0003 ⊖, ⊕1, ⊕2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
4 BA0001 BA0002 BA0003 B1, B2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
5 BA0001 BA0002 BA0003 [ground symbol] 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
6 BA0006 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
7 BA0006 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
8 BA0006 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
9 BA0006 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
10 BA0006 [ground symbol] 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)

Manual — Main circuit wiring continued — header — page 59

Source reference: SIEP C71060618F, December 2016, physical PDF page 59. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.6 Main Circuit Wiring

n Three-Phase 200 V Class Table 3.3 Wire Gauge and Torque Specifications

Installation Electrical 3

BA0010 | R/L1, S/L2, T/L3

BA0010 | U/T1, V/T2, W/T3

BA0010 | ⊖, ⊕1, ⊕2

BA0010 | B1, B2

BA0010 | [ground symbol]

BA0012 | R/L1, S/L2, T/L3

BA0012 | U/T1, V/T2, W/T3

BA0012 | ⊖, ⊕1, ⊕2

BA0012 | B1, B2

BA0012 | [ground symbol]

BA0018 | R/L1, S/L2, T/L3

BA0018 | U/T1, V/T2, W/T3

BA0018 | ⊖, ⊕1, ⊕2

BA0018 | B1, B2

BA0018 | [ground symbol]

2A0001 2A0002 2A0004 2A0006 | R/L1, S/L2, T/L3

2A0001 2A0002 2A0004 2A0006 | U/T1, V/T2, W/T3

2A0001 2A0002 2A0004 2A0006 | ⊖, ⊕1, ⊕2

2A0001 2A0002 2A0004 2A0006 | B1, B2

2A0001 2A0002 2A0004 2A0006 | [ground symbol]

2A0010 | R/L1, S/L2, T/L3

2A0010 | U/T1, V/T2, W/T3

2A0010 | ⊖, ⊕1, ⊕2

2A0010 | B1, B2

2A0010 | [ground symbol]

2A0012 | R/L1, S/L2, T/L3

2A0012 | U/T1, V/T2, W/T3

2A0012 | ⊖, ⊕1, ⊕2

2A0012 | B1, B2

2A0012 | [ground symbol]

2A0020 | R/L1, S/L2, T/L3

2A0020 | U/T1, V/T2, W/T3

2A0020 | ⊖, ⊕1, ⊕2

2A0020 | B1, B2

2A0020 | [ground symbol]

2A0030 | R/L1, S/L2, T/L3

2A0030 | U/T1, V/T2, W/T3

2A0030 | ⊖, ⊕1, ⊕2

2A0030 | B1, B2

2A0030 | [ground symbol]

Table 3.2 Single-Phase 200 V Class continued — PDF page 59

Source row Drive model Terminal Recommended gauge (AWG, kcmil) Wire range (AWG, kcmil) Screw size Tightening torque N·m (lb.in.)
1 BA0010 R/L1, S/L2, T/L3 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
2 BA0010 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
3 BA0010 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
4 BA0010 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
5 BA0010 [ground symbol] 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
6 BA0012 R/L1, S/L2, T/L3 10 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
7 BA0012 U/T1, V/T2, W/T3 14 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
8 BA0012 ⊖, ⊕1, ⊕2 – 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
9 BA0012 B1, B2 – 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
10 BA0012 [ground symbol] 10 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
11 BA0018 R/L1, S/L2, T/L3 8 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
12 BA0018 U/T1, V/T2, W/T3 10 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
13 BA0018 ⊖, ⊕1, ⊕2 – 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
14 BA0018 B1, B2 – 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
15 BA0018 [ground symbol] 8 12 to 8 M5 2 to 2.5 (17.7 to 22.1)

Table 3.3 Three-Phase 200 V Class — PDF page 59

Source row Drive model Terminal Recommended gauge (AWG, kcmil) Wire range (AWG, kcmil) Screw size Tightening torque N·m (lb.in.)
1 2A0001 2A0002 2A0004 2A0006 R/L1, S/L2, T/L3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
2 2A0001 2A0002 2A0004 2A0006 U/T1, V/T2, W/T3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
3 2A0001 2A0002 2A0004 2A0006 ⊖, ⊕1, ⊕2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
4 2A0001 2A0002 2A0004 2A0006 B1, B2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
5 2A0001 2A0002 2A0004 2A0006 [ground symbol] 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
6 2A0010 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
7 2A0010 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
8 2A0010 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
9 2A0010 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
10 2A0010 [ground symbol] 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
11 2A0012 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
12 2A0012 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
13 2A0012 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
14 2A0012 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
15 2A0012 [ground symbol] 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
16 2A0020 R/L1, S/L2, T/L3 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
17 2A0020 U/T1, V/T2, W/T3 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
18 2A0020 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
19 2A0020 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
20 2A0020 [ground symbol] 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
21 2A0030 R/L1, S/L2, T/L3 8 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
22 2A0030 U/T1, V/T2, W/T3 8 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
23 2A0030 ⊖, ⊕1, ⊕2 – 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
24 2A0030 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
25 2A0030 [ground symbol] 8 10 to 6 M5 2 to 2.5 (17.7 to 22.1)

Manual — Main circuit wiring continued — header — page 60

Source reference: SIEP C71060618F, December 2016, physical PDF page 60. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.6 Main Circuit Wiring

n Three-Phase 400 V Class Table 3.4 Wire Gauge and Torque Specifications

2A0040 | R/L1, S/L2, T/L3

2A0040 | U/T1, V/T2, W/T3

2A0040 | ⊖, ⊕1, ⊕2

2A0040 | B1, B2

2A0040 | [ground symbol]

2A0056 | R/L1, S/L2, T/L3

2A0056 | U/T1, V/T2, W/T3

2A0056 | ⊖, ⊕1, ⊕2

2A0056 | B1, B2

2A0056 | [ground symbol]

2A0069 | R/L1, S/L2, T/L3

2A0069 | U/T1, V/T2, W/T3

2A0069 | ⊖, ⊕1, ⊕2

2A0069 | B1, B2

2A0069 | [ground symbol]

4A0001 4A0002 4A0004 | R/L1, S/L2, T/L3

4A0001 4A0002 4A0004 | U/T1, V/T2, W/T3

4A0001 4A0002 4A0004 | ⊖, ⊕1, ⊕2

4A0001 4A0002 4A0004 | B1, B2

4A0001 4A0002 4A0004 | [ground symbol]

4A0005 4A0007 4A0009 | R/L1, S/L2, T/L3

4A0005 4A0007 4A0009 | U/T1, V/T2, W/T3

4A0005 4A0007 4A0009 | ⊖, ⊕1, ⊕2

4A0005 4A0007 4A0009 | B1, B2

4A0005 4A0007 4A0009 | [ground symbol]

4A0011 | R/L1, S/L2, T/L3

4A0011 | U/T1, V/T2, W/T3

4A0011 | ⊖, ⊕1, ⊕2

4A0011 | B1, B2

4A0011 | [ground symbol]

4A0018 | R/L1, S/L2, T/L3

4A0018 | U/T1, V/T2, W/T3

4A0018 | ⊖, ⊕1, ⊕2

4A0018 | B1, B2

4A0018 | [ground symbol]

Table 3.3 Three-Phase 200 V Class continued — PDF page 60

Source row Drive model Terminal Recommended gauge (AWG, kcmil) Wire range (AWG, kcmil) Screw size Tightening torque N·m (lb.in.)
1 2A0040 R/L1, S/L2, T/L3 6 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
2 2A0040 U/T1, V/T2, W/T3 8 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
3 2A0040 ⊖, ⊕1, ⊕2 – 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
4 2A0040 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
5 2A0040 [ground symbol] 6 10 to 6 M5 2 to 2.5 (17.7 to 22.1)
6 2A0056 R/L1, S/L2, T/L3 4 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
7 2A0056 U/T1, V/T2, W/T3 4 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
8 2A0056 ⊖, ⊕1, ⊕2 – 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
9 2A0056 B1, B2 – 10 to 6 M5 2.7 to 3.0 (23.9 to 26.6)
10 2A0056 [ground symbol] 6 8 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
11 2A0069 R/L1, S/L2, T/L3 3 8 to 2 M8 9.9 to 11 (87.6 to 97.4)
12 2A0069 U/T1, V/T2, W/T3 3 8 to 2 M8 9.9 to 11 (87.6 to 97.4)
13 2A0069 ⊖, ⊕1, ⊕2 – 8 to 2 M8 9.9 to 11 (87.6 to 97.4)
14 2A0069 B1, B2 – 8 to 6 M5 2.7 to 3.0 (23.9 to 26.6)
15 2A0069 [ground symbol] 6 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)

Table 3.4 Three-Phase 400 V Class — PDF page 60

Source row Drive model Terminal Recommended gauge (AWG, kcmil) Wire range (AWG, kcmil) Screw size Tightening torque N·m (lb.in.)
1 4A0001 4A0002 4A0004 R/L1, S/L2, T/L3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
2 4A0001 4A0002 4A0004 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
3 4A0001 4A0002 4A0004 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
4 4A0001 4A0002 4A0004 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
5 4A0001 4A0002 4A0004 [ground symbol] 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
6 4A0005 4A0007 4A0009 R/L1, S/L2, T/L3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
7 4A0005 4A0007 4A0009 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
8 4A0005 4A0007 4A0009 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
9 4A0005 4A0007 4A0009 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
10 4A0005 4A0007 4A0009 [ground symbol] 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
11 4A0011 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
12 4A0011 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
13 4A0011 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
14 4A0011 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
15 4A0011 [ground symbol] 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
16 4A0018 R/L1, S/L2, T/L3 10 14 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
17 4A0018 U/T1, V/T2, W/T3 10 14 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
18 4A0018 ⊖, ⊕1, ⊕2 – 14 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
19 4A0018 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
20 4A0018 [ground symbol] 8 14 to 6 M5 2 to 2.5 (17.7 to 22.1)

Manual — Main circuit wiring continued — header — page 61

Source reference: SIEP C71060618F, December 2016, physical PDF page 61. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.6 Main Circuit Wiring

u Main Circuit Terminal Power Supply and Motor Wiring This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals. NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward. NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to comply may result in abnormal operation of drive and nearby equipment. NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper application of noise filters could result in damage to the drive. NOTICE: Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious injury by fire as a result of drive damage from line voltage application to output terminals. n Cable Length Between Drive and Motor When the cable length between the drive and the motor is too long (especially at low frequency output), note that the cable voltage drop may cause reduced motor torque. Drive output current will increase as the leakage current from the cable increases. An increase in leakage current may trigger an overcurrent situation and weaken the accuracy of the current detection. Adjust the drive carrier frequency according to the following table. If the motor wiring distance exceeds 100 m because of the system configuration, reduce the ground currents. Refer to C6-02: Carrier Frequency Selection on page 156 Refer to Table 3.5 to set the carrier frequency to an appropriate level. Table 3.5 Cable Length Between Drive and Motor

Note: When setting carrier frequency, calculate the cable length as the total distance of wiring to all connected motors when running multiple motors from a single drive.

Installation Electrical 3

4A0023 | R/L1, S/L2, T/L3

4A0023 | U/T1, V/T2, W/T3

4A0023 | ⊖, ⊕1, ⊕2

4A0023 | B1, B2

4A0023 | [ground symbol]

4A0031 | R/L1, S/L2, T/L3

4A0031 | U/T1, V/T2, W/T3

4A0031 | ⊖, ⊕1, ⊕2

4A0031 | B1, B2

4A0031 | [ground symbol]

4A0038 | R/L1, S/L2, T/L3

4A0038 | U/T1, V/T2, W/T3

4A0038 | ⊖, ⊕1, ⊕2

4A0038 | B1, B2

4A0038 | [ground symbol]

Carrier Frequency | 15 kHz or less

Table 3.4 Three-Phase 400 V Class continued — PDF page 61

Source row Drive model Terminal Recommended gauge (AWG, kcmil) Wire range (AWG, kcmil) Screw size Tightening torque N·m (lb.in.)
1 4A0023 R/L1, S/L2, T/L3 10 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
2 4A0023 U/T1, V/T2, W/T3 10 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
3 4A0023 ⊖, ⊕1, ⊕2 – 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
4 4A0023 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
5 4A0023 [ground symbol] 8 10 to 6 M5 2 to 2.5 (17.7 to 22.1)
6 4A0031 R/L1, S/L2, T/L3 8 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
7 4A0031 U/T1, V/T2, W/T3 8 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
8 4A0031 ⊖, ⊕1, ⊕2 – 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
9 4A0031 B1, B2 – 14 to 10 M5 2.7 to 3.0 (23.9 to 26.6)
10 4A0031 [ground symbol] 6 10 to 6 M6 5.4 to 6.0 (47.8 to 53.1)
11 4A0038 R/L1, S/L2, T/L3 6 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
12 4A0038 U/T1, V/T2, W/T3 8 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
13 4A0038 ⊖, ⊕1, ⊕2 – 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
14 4A0038 B1, B2 – 10 to 8 M5 2.7 to 3.0 (23.9 to 26.6)
15 4A0038 [ground symbol] 6 10 to 6 M6 5.4 to 6.0 (47.8 to 53.1)

Table 3.5 Cable Length Between Drive and Motor — PDF page 61

Source row Cable length 50 m or less 100 m or less Greater than 100 m
1 Carrier Frequency 15 kHz or less 5 kHz or less 2 kHz or less

Manual — Ground wiring precautions and class-specific resistance — page 62

Source reference: SIEP C71060618F, December 2016, physical PDF page 62. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.6 Main Circuit Wiring n Ground Wiring Follow the precautions to wire the ground for one drive or a series of drives. WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could result in death or serious injury. WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal. (200 V Class: Ground to 100 Ω or less, 400 V Class: Ground to 10 Ω or less). Improper equipment grounding could result in death or serious injury by contacting ungrounded electrical equipment. NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper equipment grounding could result in drive or equipment malfunction due to electrical interference. NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in abnormal operation of drive or equipment. Refer to Figure 3.15 when using multiple drives. Do not loop the ground wire.

Figure 3.15 Multiple Drive Wiring. A – Correct; B – Incorrect. Two source arrangements marked A, one B. Do not loop ground wire. Original diagram retains routing topology; text label inventory does not specify a substitute wiring arrangement.

n Wiring the Main Circuit Terminal WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit terminals. Failure to comply may result in death or serious injury. Note: A cover placed over the DC Bus and braking circuit terminals prior to shipment helps prevent miswiring. Cut away covers as needed for terminals with a needle-nose pliers.

A – Protective Cover to Prevent Miswiring. Diagram shows cover placement only; terminal details remain original-only.

Note: The ground terminal screw on IP20/NEMA Type 1 holds the protective cover in place. Main Circuit Connection Diagram Refer to section 3.3 Main Circuit Connection Diagram on page 53 for drive main power circuit connections. WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect braking resistors to any other terminals. Improper wiring connections could cause the braking resistor to overheat and cause death or serious injury by fire. Failure to comply may result in damage to the braking circuit or drive.

Manual — Control circuit wiring and no-solder warning — page 63

Source reference: SIEP C71060618F, December 2016, physical PDF page 63. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.7 Control Circuit Wiring 3.7 Control Circuit Wiring NOTICE: Do not solder the ends of wire connections to the drive. Soldered wire connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.

Figure 3.16 Control Circuit Connection Diagram. V1000 Control circuit; default digital inputs S1 Forward run/stop; S2 Reverse run/stop; S3 External fault; S4 Fault reset; S5 Multi-step speed 1 main/aux switch; S6 Multi-step speed 2; S7 Jog reference; SC. +24 V 8 mA, 24 V, 0 V; DIP switch S3 Sink/Source; shield ground terminal. Option card connector; DIP switch S1 V/I. Fault relay MA, MB, MC; digital output 250 Vac 10 mA to 1 A / 30 Vdc 10 mA to 1 A default. Photocoupler digital output 5 to 48 Vdc, 2 to 50 mA default; P1 During Run (photocoupler 1); P2 Frequency agree (photocoupler 2); PC common. Main speed frequency reference multi-function programmable; 2 kΩ; RP pulse train input max. 32 kHz; +V setting power supply +10.5 max. 20 mA; A1 0 to +10 V (20 kΩ); A2 0 to +10 V (20 kΩ), (0)4 to 20 mA (250 Ω); AC. MP pulse train output 0 to 32 kHz; AM analog monitor output 0 to +10 Vdc (2 mA); AC. Safe Disable Input, Safety switch, Jumper, HC, H1. DIP switch S2, termination resistor 120 Ω, 1/2 W; communications connector; R+, R-, S+, S-, IG, cable shield ground; MEMOBUS/Modbus RS-485/422. Legend shielded line, twisted-pair shielded line, main circuit terminal, control terminal. Original wiring geometry and footnotes remain required.

<1> Connected using sequence input signal (S1 to S7) from NPN transistor; Default: sink mode (0 V com) <2> Use only the +24 V internal power supply in sinking mode; the source mode requires an external power supply. Refer to I/O Connections on page 68.

Installation Electrical 3

Manual — Control terminal function selection and test-run warnings — page 64

Source reference: SIEP C71060618F, December 2016, physical PDF page 64. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.7 Control Circuit Wiring u Control Circuit Terminal Block Functions Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S7), multi-function digital outputs (MA, MB), multi-function pulse inputs and outputs (RP, MP) and multi-function photocoupler outputs (P1, P2). The default is called out next to each terminal in Figure 3.. WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with untested control circuits could result in death or serious injury. WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter A1-06 may change the I/O terminal function automatically from the factory setting. Refer to Application Selection on page 96. Failure to comply may result in death or serious injury. n Input Terminals Table 3.6 Control Circuit Input Terminals

n Output Terminals Table 3.7 Control Circuit Output Terminals

<1> Do not assign functions to digital relay outputs that involve frequent switching. This may shorten relay performance life. Switching life is estimated at 200,000 times (assumes 1 A, resistive load).

Multi-Function Digital Inputs | S1

Multi-Function Digital Inputs | S2

Multi-Function Digital Inputs | S3

Multi-Function Digital Inputs | S4

Multi-Function Digital Inputs | S5

Multi-Function Digital Inputs | S6

Multi-Function Digital Inputs | S7

Multi-Function Digital Inputs | SC

Safe Disable Input | HC

Safe Disable Input | H1

Main Frequency Reference Input | RP

Main Frequency Reference Input | +V

Main Frequency Reference Input | A1

Main Frequency Reference Input | A2

Main Frequency Reference Input | AC

Multi-Function Digital Output <1> | MA

Multi-Function Digital Output <1> | MB

Multi-Function Digital Output <1> | MC

Multi-Function Photocoupler Output | P1

Multi-Function Photocoupler Output | P2

Multi-Function Photocoupler Output | PC

Monitor Output | MP

Monitor Output | AM

Monitor Output | AC

Table 3.6 Control Circuit Input Terminals — PDF page 64

Source row Type No. Terminal Name (Function) Function (Signal Level) Default Setting
1 Multi-Function Digital Inputs S1 Multi-function input 1 (Closed: Forward run, Open: Stop) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68.
2 Multi-Function Digital Inputs S2 Multi-function input 2 (Closed: Reverse run, Open: Stop) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68.
3 Multi-Function Digital Inputs S3 Multi-function input 3 (External fault (N.O.) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68.
4 Multi-Function Digital Inputs S4 Multi-function input 4 (Fault reset) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68.
5 Multi-Function Digital Inputs S5 Multi-function input 5 (Multi-step speed reference 1) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68.
6 Multi-Function Digital Inputs S6 Multi-function input 6 (Multi-step speed reference 2) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68.
7 Multi-Function Digital Inputs S7 Multi-function input 7 (Jog reference) Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68.
8 Multi-Function Digital Inputs SC Multi-function input common (Control common) Sequence common
9 Safe Disable Input HC Power supply for safe disable input +24 Vdc (max 10 mA allowed) Do not use external power supply.
10 Safe Disable Input H1 Safe disable input Open: Output disabled Closed: Normal operation Note: Disconnect wire jumper between HC and H1 when using the safe disable input. The wire length should not exceed 30 m. Use only dry contacts on safety inputs HC-H1.
11 Main Frequency Reference Input RP Multi-function pulse train input (frequency reference) Response frequency: 0.5 to 32 kHz (Duty Cycle: 30 to 70%) (High level voltage: 3.5 to 13.2 Vdc) (Low level voltage: 0.0 to 0.8 Vdc) (input impedance: 3 kΩ)
12 Main Frequency Reference Input +V Analog input power supply +10.5 Vdc (max allowable current 20 mA)
13 Main Frequency Reference Input A1 Multi-function analog input 1 (frequency reference) Input voltage 0 to +10 Vdc (20 kΩ) resolution 1/1000
14 Main Frequency Reference Input A2 Multi-function analog input 2 (frequency reference) Input voltage or input current (Selected by DIP switch S1 and H3-09) 0 to +10 Vdc (20 kΩ), Resolution: 1/1000 4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω), Resolution: 1/500
15 Main Frequency Reference Input AC Frequency reference common 0 Vdc

Table 3.7 Control Circuit Output Terminals — PDF page 64

Source row Type No. Terminal Name (Function) Function (Signal Level) Default Setting
1 Multi-Function Digital Output <1> MA N.O. (fault) Digital output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA (reference value)
2 Multi-Function Digital Output <1> MB N.C. output (fault) Digital output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA (reference value)
3 Multi-Function Digital Output <1> MC Digital output common Digital output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA (reference value)
4 Multi-Function Photocoupler Output P1 Photocoupler output 1 (During run) Photocoupler output 48 Vdc, 2 to 50 mA <2>
5 Multi-Function Photocoupler Output P2 Photocoupler output 2 (Frequency agree) Photocoupler output 48 Vdc, 2 to 50 mA <2>
6 Multi-Function Photocoupler Output PC Photocoupler output common Photocoupler output 48 Vdc, 2 to 50 mA <2>
7 Monitor Output MP Pulse train output (Output frequency) 32 kHz (max) <3> <4>
8 Monitor Output AM Analog monitor output 0 to 10 Vdc (2 mA or less) Resolution: 1/1000
9 Monitor Output AC Monitor common 0 V

Manual — Table 3.7 continued footnotes 2–4 — page 65

Source reference: SIEP C71060618F, December 2016, physical PDF page 65. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.7 Control Circuit Wiring <2> Connect a suppression diode as shown in Figure 3.17 when driving a reactive load such as a relay coil. Ensure the diode rating is greater than the circuit voltage. <3> When set for sourcing. +5 V/1.5 kΩ or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher. <4> When set for sinking, the external power supply should be +12 Vdc, ±5% with 16 mA or less.

Figure 3.17 Connecting a Suppression Diode: A – External power, 48 V max.; B – Suppression diode; C – Coil; D – 50 mA or less. Original diode orientation/connection geometry retained; footnote 2 requires diode rating greater than circuit voltage.

n Serial Communication Terminals Table 3.8 Control Circuit Terminals: Serial Communications

u Terminal Configuration

Figure 3.18 Removable Control Circuit Terminal Block. Enlarged terminal label rows: R+, R-, S+, S-, IG; P1, P2, PC, A1, A2, +V, AC, AM, AC, MP; S1, S2, S3, S4, S5, S6, S7, HC, SC, H1, RP; separate MA, MB, MC. Jumper pictured HC–H1. Geometry original-only; safety-input instructions remain required.

Installation Electrical 3

MEMOBUS/Modbus Communication | R+

MEMOBUS/Modbus Communication | R-

MEMOBUS/Modbus Communication | S+

MEMOBUS/Modbus Communication | S-

MEMOBUS/Modbus Communication | IG

Table 3.8 Control Circuit Terminals: Serial Communications — PDF page 65

Source row Type No. Signal Name Function (Signal Level) — connection Function (Signal Level) — protocol
1 MEMOBUS/Modbus Communication R+ Communications input (+) MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.)
2 MEMOBUS/Modbus Communication R- Communications input (-) MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.)
3 MEMOBUS/Modbus Communication S+ Communications output (+) MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.)
4 MEMOBUS/Modbus Communication S- Communications output (-) MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.)
5 MEMOBUS/Modbus Communication IG Shield ground 0 V 0 V

Manual — Wire size and torque context — page 66

Source reference: SIEP C71060618F, December 2016, physical PDF page 66. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.7 Control Circuit Wiring n Wire Size and Torque Specifications Select appropriate wire type and size from Table 3.9. For simpler and more reliable wiring, crimp ferrules to the wire ends. Refer to Table 3.10 for ferrule terminal types and sizes. Table 3.9 Wire Size and Torque Specifications (Same for All Models)

n Ferrule-Type Wire Terminations Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT.

Figure 3.19 Ferrule Dimensions. Labels d1, d2, L, and 6 mm. Dimension-arrow geometry remains original-only; numerical model dimensions are in Table 3.10.

Figure 3.19 Ferrule Dimensions Table 3.10 Ferrule Terminal Types and Sizes

u Wiring Procedure This section describes the proper procedures and preparations for wiring the control terminals. WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result in death or serious injury. NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference. NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit lines. Improper wiring practices could result in drive or equipment malfunction or nuisance trips. NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation due to improper power supply. NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could result in drive or equipment malfunction due to short circuit. NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or equipment malfunction or nuisance trips. Wire the control terminals using Figure 3.20 as a guide. Prepare the ends of the control circuit wiring as shown in Figure 3.21. Refer to Wire Size and Torque Specifications on page 66.

Table 3.9 Wire Size and Torque Specifications (Same for All Models) — PDF page 66

Source row Terminal Screw Size Tightening Torque N·m (in-lbs) Bare wire applicable size mm² (AWG) Bare wire recommended mm² (AWG) Ferrule applicable size mm² (AWG) Ferrule recommended mm² (AWG) Wire Type
1 MA, MB, MC M3 0.5 to 0.6 (4.4 to 5.3) Stranded: 0.25 to 1.5 (24 to 16) Single: 0.25 to 1.5 (24 to 16) 0.75 (18) 0.25 to 1.0 (24 to 17) 0.5 (20) Shielded line, etc.
2 S1-S7, SC, RP, +V, A1, A2, AC, HC, H1, P1, P2, PC, MP, AM, AC, S+, S-, R+, R-, IG M2 0.22 to 0.25 (1.9 to 2.2) Stranded: 0.25 to 1.0 (24 to 18) Single: 0.25 to 1.5 (24 to 16) 0.75 (18) 0.25 to 0.5 (24 to 20) 0.5 (20) Shielded line, etc.

Table 3.10 Ferrule Terminal Types and Sizes — PDF page 66

Source row Size mm² (AWG) Type L (mm) d1 (mm) d2 (mm) Manufacturer
1 0.25 (24) AI 0.25-6YE 10.5 0.8 2.0 PHOENIX CONTACT
2 0.34 (22) AI 0.34-6TQ 10.5 0.8 2.0 PHOENIX CONTACT
3 0.5 (20) AI 0.5-6WH 12 1.1 2.5 PHOENIX CONTACT
4 0.75 (18) AI 0.75-6GY 12 1.3 2.8 PHOENIX CONTACT
5 1.0 AI 1-6RD 12 1.5 3.0 PHOENIX CONTACT

Manual — Control terminal torque and twisted-pair notices — page 67

Source reference: SIEP C71060618F, December 2016, physical PDF page 67. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.7 Control Circuit Wiring NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the terminal block. NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or equipment malfunction due to electrical interference. Connect control wires as shown in the following figure:

Figure 3.20 diagram: A, B, C, D, E; Preparing wire terminal ends. Read source legend below; geometry original-only.

A – Control terminal block B – Avoid fraying wire strands when stripping insulation from wire. Strip length 5.5 mm. C – Single wire or stranded wire

D – Loosen screw to insert wire. E – Blade depth of 0.4 mm or less Blade width of 2.5 mm or less

Figure 3.20 Terminal Board Wiring Guide

Figure 3.21 diagram letter references A, B, C, D, E, F; original cable geometry remains authoritative.

A – Drive side B – Connect shield to ground terminal of drive. C – Insulation

D – Control device side E – Shield sheath (Insulate with tape) F – Shield

Figure 3.21 Preparing the Ends of Shielded Cables When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires and ground the shield of twisted-pair wires to the ground terminal of the drive. NOTICE: The analog signal lines between the drive and the operator station or peripheral equipment should not exceed 50 meters when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.

Figure 3.22 diagram: A, B, C, D, E, F, G; RP, +V, A1, A2, AC; 2 kΩ potentiometer; ground symbol. Read separate legends below; topology remains original-only.

A – Drive B – Ground terminal (shield connection) C – (RP) Pulse train (maximum 32 kHz) D – (+V) Frequency setting power source +10.5 Vdc maximum 20 mA

E – (A1) Main speed frequency reference 0 to +10 Vdc (20 kΩ) F – (A2) Multi-function analog input 0 to +10 Vdc (20 kΩ) or 4 to 20 mA (250 Ω)/ 0 to 20 mA (250 Ω) G – Frequency setting potentiometer

Figure 3.22 Wiring the Frequency Reference to the Control Circuit Terminals (External Reference)

Installation Electrical 3

Manual — Sinking/sourcing mode switch context — page 68

Source reference: SIEP C71060618F, December 2016, physical PDF page 68. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.8 I/O Connections 3.8 I/O Connections u Sinking/Sourcing Mode Switch Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between sinking mode and sourcing mode; the drive is preset to sinking mode. Table 3.11 Sinking/Sourcing Mode Setting

Figure 3.23 DIP switch S3, SINK and SOURCE. Original diagram identifies switch location; tiny repeated keypad face is not a live setting.

n Transistor Input Signal Using 0 V Common/Sink Mode When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the DIP switch S3 to SINK and use the internal 24 V power supply.

Figure 3.24 Sinking Mode: Sequence from NPN Transistor (0 V Common). Drive, shielded cable, multi-function input: S1 Forward run/stop; S2 Reverse run/stop; S3 External fault N.O.; S4 Fault reset; S5 Multi-speed step 1; S6 Multi-speed step 2; S7 Jog reference; SC. DIP switch S3 SINK/SOURCE, +24V. Original wiring diagram remains authoritative.

Table 3.11 Sinking/Sourcing Mode Setting — PDF page 68

Source row Set Value Details
1 SINK Sinking Mode (0 V common): default setting
2 SOURCE Sourcing Mode (+24 V common)

Manual — PNP transistor sourcing procedure — page 69

Source reference: SIEP C71060618F, December 2016, physical PDF page 69. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.8 I/O Connections n Transistor Input Signal Using +24 V Common/Source Mode When controlling digital inputs by PNP transistors (+24 V common/sourcing mode), set the DIP switch S3 to SOURCE and use an external 24 V power supply.

Figure 3.25 Source Mode: Sequence from PNP Transistor (+24 V Common). External power supply +24 V; shielded cable; drive; multi-function input labels S1 Forward run / stop; S2 Reverse run / stop; S3 External fault N.O.; S4 Fault rest [literal source spelling]; S5 Multi-step speed 1; S6 Multi-step speed 2; S7 Jog frequency; SC; DIP S3 SINK/SOURCE, +24V. Original wiring diagram remains authoritative.

Installation Electrical 3

Manual — Analog frequency-reference selection, H3-09 and H3-10 conditions — page 70

Source reference: SIEP C71060618F, December 2016, physical PDF page 70. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.9 Main Frequency Reference 3.9 Main Frequency Reference u DIP Switch S1 Analog Input Signal Selection The main frequency reference can either be a voltage or current signal input. For voltage signals both analog inputs, A1 and A2, can be used, for current signals A2 must be used. When using input A2 as a voltage input, set DIP switch S1 to “V” (left position) and program parameter H3-09 to “0” (0 to +10 Vdc with lower limit) or “1” (0 to +10 Vdc without lower limit). To use current input at terminal A2, set the DIP switch S1 to "I" (default setting) and set parameter H3-09 = “2” or “3” (4-20 mA or 0-20 mA). Set parameter H3-10 = “0” (frequency reference). Note: If Terminals A1 and A2 are both set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both input values builds the frequency reference. Table 3.12 Frequency Reference Configurations

Table 3.12 Frequency Reference Configurations consists of two diagrams. Voltage Input labels: Drive, 2 kΩ, 0 to 10 V, +V +10.5 V 20 mA current, A1 main speed frequency reference (voltage input), A2 main speed frequency reference (current input), AC frequency reference common. Current Input labels: Drive; +V +10.5 V 20 mA current; A1 main speed frequency reference (voltage input); A2 main speed frequency reference (current input); 4 to 20 mA input or 0 to 20 mA input; AC frequency reference common. Current signal uses A2 according to explicit source prose; do not map current text to A1 merely because labels are nearby. Original wiring geometry required.

Figure 3.26 DIP Switch S1 with V and I labels. Left/right electrical settings are specified by Table 3.13; original picture locates the switch.

Table 3.13 DIP Switch S1 Settings

Table 3.14 Parameter H3-09 Details

Literal visible table column boundaries; native detector split description prefix into name column. Actual rule corrected before freezing first reading. Source setting 1 says 0 to +10 V, bipolar input (no lower limit); preserve literal wording.

Table 3.13 DIP Switch S1 Settings — PDF page 70

Source row Setting Value Description
1 V (left position) Voltage input (0 to 10 V)
2 I (right position) Current input (4 to 20 mA or 0 to 20 mA): default setting

Table 3.14 Parameter H3-09 Details — PDF page 70

Source row No. Parameter Name Description Setting Range Default Setting
1 H3-09 Frequency ref. (current) terminal A2 signal level selection Selects the signal level for terminal A2. 0: 0 to +10 V, unipolar input (with lower limit) 1: 0 to +10 V, bipolar input (no lower limit) 2: 4 to 20 mA 3: 0 to 20 mA 0 to 3 2

Manual — Network termination requirements — page 71

Source reference: SIEP C71060618F, December 2016, physical PDF page 71. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.10 MEMOBUS/Modbus Termination 3.10 MEMOBUS/Modbus Termination The two ends of the MEMOBUS/Modbus network line must be terminated. The drive has a built-in termination resistor that can be enabled or disabled using DIP switch S2. If a drive is a single drive on the network or is located at the end of a network line, set DIP switch S2 to the ON position to enable the termination resistor. Disable the termination resistor on all slave drives that are not located at the network line end. Table 3.15 MEMOBUS/Modbus Switch Settings

Figure 3.27 DIP Switch S2; OFF, ON. Original picture identifies switch position; Table 3.15 gives settings.

Note: Refer to the MEMOBUS/Modbus communications manual for details on MEMOBUS/Modbus.

Installation Electrical 3

Table 3.15 MEMOBUS/Modbus Switch Settings — PDF page 71

Source row S2 Position Description
1 ON Internal termination resistor ON
2 OFF Internal termination resistor OFF (no termination resistor); default setting

Manual — Braking resistor sizing, thermal protection, installation steps 1–3 — page 72

Source reference: SIEP C71060618F, December 2016, physical PDF page 72. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.11 Braking Resistor 3.11 Braking Resistor Dynamic braking (DB) helps bring the motor to a smooth and rapid stop when working with high inertia loads. Regeneration occurs as the drive lowers the motor frequency with high inertia. When the regeneration flows back into the DC bus capacitors, an overvoltage situation occurs. A braking resistor prevents these overvoltage faults. NOTICE: Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review the braking resistor instruction manual when connecting a braking option to the drive. Note: The braking circuit must be sized properly in order to dissipate the power required to decelerate the load in the desired time. Ensure that the braking circuit can dissipate the energy for the set deceleration time prior to running the drive. NOTICE: Use a thermal overload relay or over-temperature contact to interrupt input power to the drive if the braking resistor overheats. In the event of a possible thermal overload, the relay triggers the input contactor and prevents the braking resistor from burning up. u Installation WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect a braking resistor directly to any other terminals. Improper wiring connections could result in death or serious injury by fire. Failure to comply may result in damage to the braking circuit or drive. NOTICE: Connect braking resistors to the drive as shown in the I/O wiring examples. Improperly wiring braking circuits could result in damage to the drive or equipment. n Installation Procedure 1. Disconnect all electrical power to the drive and wait at least five minutes before servicing the drive and any connected components. 2. Remove drive front cover. 3. Use a voltmeter to verify that voltage is disconnected from incoming power terminals and that the DC bus no longer holds a charge.

Figure 3.28 Connecting a Braking Resistor. Power supply, MCCB, MC, drive R/L1, S/L2, T/L3; B1 and B2, thermal relay, braking resistor; U/T1, V/T2, W/T3, Motor. Thermal relay switch for external braking resistor; fault contact; THRX, OFF, ON, MC, SA, TRX, MA, MC. Original interlock and connection geometry required.

  1. Follow manufacturer instructions to connect the resistor unit to the drive using proper wire gauge according to local electrical codes. Power leads for the remote mount resistors generate high levels of electrical noise; group these signal leads separately. 5. Mount the resistor unit on a noncombustible surface. Maintain minimum side and top clearances according to resistor manufacturer instructions. WARNING! Fire Hazard. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive or braking resistors to metal or other noncombustible material. 6. Reinstall drive covers and resistor covers, if provided. 7. Set parameter L3-04 = “0” or “3” to disable stall prevention during deceleration. Set parameter L8-01 to “1” to enable overheat protection when using a heatsink-mounted braking resistor option. Set L8-01 = “0” for other braking resistor types. Set parameter L3-04 = “3” to generate the shortest possible deceleration time.

Manual — Braking resistor table caption — page 73

Source reference: SIEP C71060618F, December 2016, physical PDF page 73. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.11 Braking Resistor Table 3.16 Braking Resistor Settings

  1. Operate the system and verify the required deceleration rate is obtained during dynamic braking or stopping.

Installation Electrical 3

Table 3.16 Braking Resistor Settings — PDF page 73

Source row Parameter Settings
1 L8-01: Internal Dynamic Braking Resistor Protection Selection 0: Disabled. The drive will not provide overheat protection. Supply separate means of overheat protection. 1: Enabled. Braking Resistor is protected from overheat.
2 L3-04: Stall Prevention During Deceleration Note: Select either 0 or 3 0: Stall prevention disabled.
3 L3-04: Stall Prevention During Deceleration Note: Select either 0 or 3 3: Stall prevention enabled with a braking resistor Note: This setting cannot be used in OLV control for PM motor.

Manual — Wiring checklist context — page 74

Source reference: SIEP C71060618F, December 2016, physical PDF page 74. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.12 Wiring Checklist 3.12 Wiring Checklist

Unmarked checklist items, not completed commissioning checks. Read with class-specific exclusions; diagrams original-only. Source cross references retained literally.

3.12 Wiring Checklist — PDF page 74

Source row No. Item Page
1 1 Check drive model number to ensure receipt of correct model. 25
2 2 Check for correct braking resistors, DC link chokes, noise filters, and other peripheral devices. 72
3 3 Check for correct option card model. 338
4 4 Ensure area surrounding the drive complies with specifications. 38
5 5 The voltage from the power supply should fall within the input voltage specification range of the drive. 169
6 6 The voltage rating for the motor should match the drive output specifications. 25
7 7 Confirm proper branch circuit protection exists per National and Local codes. 50
8 8 Properly wire the power supply to drive terminals R/L1, S/L2 and T/L3. 53
9 9 Properly wire the drive and motor together. The motor lines and drive output terminals R/T1, V/T2 and W/T3 should match in order to produce the desired phase order. If the phase order is incorrect, the drive will rotate in the opposite direction. 61
10 10 Use 600 Vac vinyl-sheathed wire for the power supply and motor lines. 58
11 11 Use the correct wire gauges for the main circuit. Refer to Table 3.2, Table 3.3, or Table 3.4. 58
12 ⟦blank source cell⟧ • When using comparatively long motor cable, calculate the amount of voltage drop. Motor rated voltage (V) x 0.02 ≥ 3 x voltage resistance (Ω/km) x cable length (m) x motor rated current (A) x 10-3 58
13 ⟦blank source cell⟧ • If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency (C6-02) accordingly. 61
14 12 Properly ground the drive. 62
15 13 Tightly fasten all terminal screws (control circuit terminals, grounding terminals). Refer to Table 3.2, Table 3.3, or Table 3.4. 58
16 14 Set up overload protection circuits when running multiple motors from a single drive. Diagram labels: Power supply; Drive; MC1, MC2, MCn; OL1, OL2, OLn; M1, M2, Mn. MC1–MCn: magnetic contactor. OL1–OLn: thermal relay. Note: Close MC1 through MCn before operating the drive. Original diagram geometry retained. –
17 15 If using a braking resistor or dynamic braking resistor unit, install a magnetic contactor. Properly install the resistor, and ensure that overload protection shuts off the power supply. 72
18 16 Verify phase advancing capacitors are NOT installed on the output side of the drive. –
19 17 Use twisted-pair cables for all drive control circuit wiring. 63
20 18 Ground the shields of shielded wiring to the GND [ground symbol] terminal. 66
21 19 If using a 3-Wire sequence, properly set parameters for multi-function contact input terminals S1 through S7, and properly wire control circuits. 52
22 20 Properly wire any option cards. 338
23 21 Check for any other wiring mistakes. Only use a multimeter to check wiring. –
24 22 Properly fasten the control circuit terminal screws in the drive. Refer to Table 3.2, Table 3.3, or Table 3.4. 58
25 23 Pick up all wire clippings. –

Manual — Wiring checklist continuation heading — page 75

Source reference: SIEP C71060618F, December 2016, physical PDF page 75. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

3.12 Wiring Checklist

Installation Electrical 3

Unmarked checklist items, not completed commissioning checks. Read with class-specific exclusions; diagrams original-only. Source cross references retained literally.

3.12 Wiring Checklist continued — PDF page 75

Source row No. Item Page
1 24 Ensure that no frayed wires on the terminal block are touching other terminals or connections. –
2 25 Properly separate control circuit wiring and main circuit wiring. –
3 26 Analog signal line wiring should not exceed 50 m. –
4 27 Safe Disable Input wiring should not exceed 30 m. –

Manual — Section safety: electrical shock and fire hazards — page 78

Source reference: SIEP C71060618F, December 2016, physical PDF page 78. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.1 Section Safety

DANGER

Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.

WARNING

Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may include drives without covers or safety shields to illustrate details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material.

Manual — Section safety: ESD and wiring notices — page 79

Source reference: SIEP C71060618F, December 2016, physical PDF page 79. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBP C720600 00 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive.

4.1 Section Safety

Start-Up Programming & Operation

Manual — LED operator components1–8 — page 80

Source reference: SIEP C71060618F, December 2016, physical PDF page 80. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Source limitation for this page: Human-readable miniature menu labels recovered in additive source context. Ambiguous segmented display glyph shapes remain unnormalized incidental illustration detail. Printed1-minute warning versus5-minute-plus-measurement source conflict retained.

Operator example F60.00. Numbered callouts:1 Data Display Area;2 ESC;3 RESET/right arrow;4 RUN;5 Up Arrow;6 Down Arrow;7 STOP;8 ENTER;9 LO/RE selection;10 RUN light;11 LO/RE light;12 ALM;13 REV;14 DRV;15 FOUT;16 communication port. Functions in Table4.1 on PDF80–81. Physical key/port geometry and miniature unit label remain original-only; example display is not a recommended setting.

4.2 Using the Digital LED Operator

Use the LED operator to enter run and stop commands, display data, edit parameters, as well as display fault and alarm information.

u Keys, Displays, and LEDs

Table 4.1 Keys and Displays on the LED Operator

No. Display Name Function

The miniature YASKAWA V1000 illustration lists these labels in top-to-bottom order: Fref (Hz); FWD/REV Sel; Fout (Hz); Iout (A); Mon1 (V); Monitor; Verify; SetUpGuide; Program; Auto-Tuning. Units shown in parentheses belong to their corresponding printed row. Small segmented display glyphs beside these labels remain original-image evidence, not normalized parameter values or operating settings.

Table4.1 LED operator component functions,1–8 — PDF page 80

Source row No. Display graphic Name Function
1 1 F60.00 Data Display Area Displays the frequency reference, parameter number, etc.
2 2 ESC key graphic ESC Key Returns to the previous menu.
3 3 RESET / right-arrow key graphic RESET Key Moves the cursor to the right. Resets the drive to clear a fault situation.
4 4 RUN key graphic RUN Key Starts the drive.
5 5 Up-arrow key graphic Up Arrow Key Scrolls up to select parameter numbers, setting values, etc.
6 6 Down-arrow key graphic Down Arrow Key Scrolls down to select parameter numbers, setting values, etc.
7 7 STOP key graphic STOP Key Stops the drive. Note: Stop priority circuit. Pressing the STOP key will always cause the drive to stop the motor, even when a Run command is active at an external Run command source. Set parameter o2-06 to 0 to disable the STOP key priority.
8 8 ENTER key graphic ENTER Key Selects all modes, parameters, settings, etc. Selects a menu item to move from one display screen to the next.

Manual — LED operator components9–16 and segment glyph table — page 81

Source reference: SIEP C71060618F, December 2016, physical PDF page 81. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Display Name Function

u Digital Text Display

Text appears on the LED Operator as shown below. This section explains the meaning of text as it appears on the display screen.

Lit Flashing

Table 4.2 Digital Text Display

Text LED Text LED Text LED Text LED

<1> Displayed in two digits.

4.2 Using the Digital LED Operator

Start-Up Programming & Operation

Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.

Table4.1 LED operator component functions,9–16 — PDF page 81

Source row No. Display graphic Name Function
1 9 LO/RE key graphic LO/RE Selection Key Switches drive control between the operator (LOCAL) and the control circuit terminals (REMOTE). Note: LOCAL/REMOTE key effective during stop in drive mode. If the digital operator could change from REMOTE to LOCAL by incorrect operation, set o2-01 (LOCAL/REMOTE Key Function Selection) to “0” (disabled) to disable LOCAL/ REMOTE key.
2 10 RUN light graphic RUN Light Lit while the drive is operating the motor.
3 11 LO/RE light graphic LO/RE Light Lit while the operator (LOCAL) is selected to run the drive.
4 12 ALM ALM LED Light Refer to LED Screen Displays on page 82.
5 13 REV REV LED Light Refer to LED Screen Displays on page 82.
6 14 DRV DRV LED Light Refer to LED Screen Displays on page 82.
7 15 FOUT FOUT LED Light Refer to LED Screen Displays on page 82.
8 16 – Communication Port Port used for USB Copy Unit, LCD Operator Keypad, and for connecting to a PC. NOTICE: Use only specified cable when making connections to the drive. Failure to comply may damage the drive. NOTICE: Do not open the port cover wider than 90 degrees. Failure to comply may break the port cover and leave the unprotected port susceptible to damage.

Lit/flashing LED examples — PDF page 81

Source row Lit Flashing
1 A1-03 (lit) A1-03 (flashing)

Table4.2 LED display character correspondence — PDF page 81

Source row Text LED graphic Text LED graphic Text LED graphic Text LED graphic
1 0 Segment glyph for 0; see original graphic 9 Segment glyph for 9; see original graphic I Segment glyph for I; see original graphic R Segment glyph for R; see original graphic
2 1 Segment glyph for 1; see original graphic A Segment glyph for A; see original graphic J Segment glyph for J; see original graphic S Segment glyph for S; see original graphic
3 2 Segment glyph for 2; see original graphic B Segment glyph for B; see original graphic K Segment glyph for K; see original graphic T Segment glyph for T; see original graphic
4 3 Segment glyph for 3; see original graphic C Segment glyph for C; see original graphic L Segment glyph for L; see original graphic U Segment glyph for U; see original graphic
5 4 Segment glyph for 4; see original graphic D Segment glyph for D; see original graphic M Segment glyph for M; see original graphic <1> Displayed in two digits V Segment glyph for V; see original graphic
6 5 Segment glyph for 5; see original graphic E Segment glyph for E; see original graphic N Segment glyph for N; see original graphic W Segment glyph for W; see original graphic <1> Displayed in two digits
7 6 Segment glyph for 6; see original graphic F Segment glyph for F; see original graphic O Segment glyph for O; see original graphic X None
8 7 Segment glyph for 7; see original graphic G Segment glyph for G; see original graphic P Segment glyph for P; see original graphic Y Segment glyph for Y; see original graphic
9 8 Segment glyph for 8; see original graphic H Segment glyph for H; see original graphic Q Segment glyph for Q; see original graphic Z None

Manual — LED states and timing illustrations — page 82

Source reference: SIEP C71060618F, December 2016, physical PDF page 82. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure4.1 RUN LED Status and Meaning: Flashing; Flashing quickly; ON;1 s reference arrow. Actual pulse geometry remains original-only; no additional timing inferred. Figure4.2 RUN LED and Drive Operation: Drive output frequency; RUN/STOP key commands; during stop; RUN; STOP; RUN; STOP; Frequency setting0 Hz and6 Hz; RUN LED OFF, ON, OFF, OFF; bracket labelled Flashing. Operating sequence is an illustration, not a device log.

u LED Screen Displays

Display Lit Flashing Off

<1> Refer to the DriveWorksEZ instruction manual for further information.

u LO/RE LED and RUN LED Indications

LED Lit Flashing Flashing Quickly <1> Off

<1> Refer to Figure 4.1 for the difference between “flashing” and “flashing quickly”. <2> Refer to the description for parameter U4-21 on page 403 for information on verifying operation interlock.

4.2 Using the Digital LED Operator

Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.

LED Screen Displays (unnumbered source table) — PDF page 82

Source row Indicator Lit Flashing OFF
1 ALM When the drive detects an alarm or error • When an alarm occurs • oPE detected • When a fault or error occurs during Auto-Tuning Normal state (no fault or alarm)
2 REV Motor is rotating in reverse — Motor is rotating forward
3 DRV Drive Mode Auto-Tuning When DriveWorksEZ is used <1> Programming Mode
4 FOUT Displays output frequency (Hz) — —
5 As illustrated in this manual F 0.00; enlarged DRV label in Lit-column illustration Er-03; alarm illustration flashing F 0.00; enlarged DRV label in Off-column illustration

LO/RE and RUN LED states — PDF page 82

Source row LED Lit Flashing Flashing quickly OFF
1 LO/RE light graphic When a Run command is selected from the LED operator (LOCAL) – – Run command is selected from device other than LED operator (REMOTE)
2 RUN light graphic During Run • During deceleration to stop • When a Run command is input and frequency reference is 0 • During deceleration at a fast- stop. • During stop by interlock <2> operation. During stop
3 As shown RUN light lit RUN light flashing RUN light flashing quickly RUN light off

Manual — Digital LED operator menu structure — page 83

Source reference: SIEP C71060618F, December 2016, physical PDF page 83. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Turn power on:F 0.00. DRIVE MODE, DRV light on, pressing RUN starts motor: Forward Selection For; ENTER selects Reverse Selection rEv; ESC returns. Reverse only when LOCAL is set. Cycle using UP/DOWN: output frequency0.00; output current0.00A; output voltage0.0V; Monitor Display Mon. Monitor entries U1-01 through U8-10; ENTER shows XX values, ESC returns. PROGRAMMING MODE, DRV light off, drive cannot operate motor: Verify Menu vrFY with XX-XX parameter placeholders and XX values; Set Up Mode StUP with APPL Application Preset and0X setting, other XX-XX/XX placeholders; Parameter Setting Mode PAr, A1-01 through r1-40, XX values; Auto-Tuning AtUn, T1-01 through T1-07, runXX, RUN, End. XX denotes actual setting values in the real display. Legend right arrow=ENTER,left arrow=ESC,downward navigation arrow=UP key,upward navigation arrow=DOWN key. Complete graphic and flash-state shapes remain in original.

u Menu Structure for Digital LED Operator

<1> Reverse can only be selected when LOCAL is set.

4.2 Using the Digital LED Operator

Start-Up Programming & Operation

Manual — Drive and Programming Mode summary — page 84

Source reference: SIEP C71060618F, December 2016, physical PDF page 84. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Mode Group | Description | Key Press | LED display. Drive Mode Functions (Motor operation and monitoring):Frequency Reference Display (Initial power-up state),UP,F0.00; Forward/Reverse,UP,For; Output Frequency Display,UP,0.00; Output Current Display,UP,0.00A; Output Voltage Reference,UP,0.0V; Monitor Display,UP,Mon. Programming Mode Functions (Changing parameters):Verify Function,UP,vrFY; Setup Group Parameters,UP,StUP; All Parameters,UP,PAr; Auto-Tuning,UP,AtUn. <1> Enlarged illustration of LED indicates LED on. Display/flash illustrations retained in original; values are source examples.

4.3 The Drive and Programming Modes

The drive functions are divided into two main groups accessible via the Digital LED Operator: Drive Mode: The Drive mode allows motor operation and parameter monitoring. Parameter settings cannot be changed when accessing functions in the Drive Mode (Table 4.3) Programming Mode: The Programming Mode allows access to setup/adjust, verify parameters and Auto-Tuning. The drive prohibits changes in motor operation such as start/stop when the Digital LED Operator is accessing a function in the Programming Mode. Table 4.3 illustrates the different functions visible as the “Up arrow” is scrolled immediately after powering up the drive.

Note: When b1-08 (Run Command Selection while in Programming Mode) is set to 1 (enabled), the drive can run even if the mode is switched to the programming mode. When setting b1-08 to 0 (disabled), the mode cannot be switched to the programming mode while the drive is running.

Table 4.3 Summary of Modes

<1> The enlarged illustration of the LED indicates that the LED is on.

Manual — Drive Mode navigation — page 85

Source reference: SIEP C71060618F, December 2016, physical PDF page 85. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Power Up:Frequency Reference/default setting/F0.00. This display monitors and sets frequency reference while running; see84. Initial display item selectable with o1-02. UP/DOWN navigate display rows. Drive Mode Forward/Reverse:For=motor rotates forward;rEv=motor rotates reverse. b1-04=1 prohibits reverse for applications such as fans/pumps. Illustrated reverse sequence also selects LOCAL:For→LO/RE→ENTER→For flashing→UP→rEv flashing→ENTER;LO/RE LED lit when LOCAL selected. Output Frequency Display0.00:monitors drive output frequency. Output Current Display0.00A:monitors output current. Output Voltage Reference0.0V(default setting):scroll o1-01(User Monitor Selection)until desired contents appear,Parameter List353. Monitor Display Mon:monitor parameters(U parameters). Physical display/LED/key shapes remain original-only.

u Navigating the Drive and Programming Modes

The drive is set to operate in Drive Mode when it is first powered up. Switch between display screens by using the [UP] and [DOWN] keys.

4.3 The Drive and Programming Modes

Start-Up Programming & Operation

Manual — Programming Mode navigation and frequency-reference example — page 86

Source reference: SIEP C71060618F, December 2016, physical PDF page 86. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Programming Mode, UP/DOWN navigation:Verify Function vrFY lists parameters edited/changed from defaults,see88. Setup StUP lists parameters needed for operation;see87;shown parameters depend on A1-06 Application Preset,see96. Parameter Setting PAr accesses/edits all settings,see353. Auto-Tuning AtUn calculates/sets motor parameters,see102. Drive Mode Frequency Reference F0.00 returns to frequency reference screen. Drawn LED/key illustrations retained in original.

Frequency reference display at power-up F0.00. LO/RE selects LOCAL; ENTER opens F00.00; RESET selects digit to right; UP until frequency reference6 Hz(F06.00); ENTER confirms,End; display F06.00; ESC returns F6.00. Figure4.4 Setting the Frequency Reference while in Drive Mode. Decimal glyph and flashing-digit shapes remain original; this is an example, not a current setting.

n Drive Mode Details

The following actions are possible in the Drive Mode: • Run and stop the drive. • Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.). • View information on an alarm. • View a history of alarms that have occurred.

Note: Select "Drive Mode" when running. The mode can be switched to any mode (program mode, etc.) other than drive mode while the drive is stopped. However, the drive cannot be operated in other modes. Return the mode to "Drive Mode" after completing periodic inspection. Figure 4.4 illustrates changing the default frequency reference of F 0.00 (0 Hz) to F 6.00 (6 Hz) while in Drive Mode. This example assumes the drive is set to LOCAL.

Note: The drive will not accept a frequency reference set value unless the ENTER key is pressed after the frequency reference is entered. This feature prevents accidental setting of the frequency reference. By setting o2-05 (Frequency Reference Setting Method Selection) to 1 (Enabled), the drive will accept the frequency reference while it is being adjusted on the digital operator.

4.3 The Drive and Programming Modes

Manual — Setup Group example — page 87

Source reference: SIEP C71060618F, December 2016, physical PDF page 87. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Frequency reference at power-up F0.00. Press DOWN until StUP appears; ENTER→APPL Application Preset; UP→A1-02 Parameter Display; UP→b1-01; ENTER→01 Control Circuit Terminal; RESET selects digit; DOWN→00 LED Operator; ENTER→End→b1-01; ESC→F6.00. Setup parameter sequence illustrated A1-02,b1-01,b1-02,b1-03,...L3-04. <1> ENTER from APPL navigates to Application Preset setting display; changing value changes parameter to optimum value for each application;0 General-purpose prior to shipment. <2> Move right to change parameter settings;scroll down to view/check Setup Mode settings. <3> ESC returns Top Menu; UP/DOWN view/edit other parameters. This source example changes b1-01 from1 to0; terminal/current drive settings are not inferred.

n Programming Mode Details

The following actions are possible in the programming mode: • Verify Function: Verify parameter setting changes from original default values. • Setup Group: Access a list of commonly used parameters to simplify setup. • Parameter Setting Mode: Access and edit all parameter settings. • Auto-Tuning: Automatically calculates and sets motor parameters for Open Loop or PM Vector control to optimize the drive for the motor characteristics.

The Setup Group within the Programming Mode In Setup Group, the user can access the minimum group of parameters required to operate the application.

Note: Setup Group parameters are listed in Table 4.4.

Note: Pressing ENTER from APPL navigates to the Application Preset setting display. When the set value is changed, the parameter is changed to the optimum value for each application. It is set to 0 (General-purpose) prior to shipment. Refer to Application Selection on page 96. Figure 4.5 illustrates the keys to press to enter the Setup Group. In this example, the source of the frequency reference is changed from the control circuit terminals to the LED Operator (i.e., b1-01 is changed from 1 to 0).

4.3 The Drive and Programming Modes

Start-Up Programming & Operation

Manual — Changing/verifying parameters and LOCAL/REMOTE warning — page 88

Source reference: SIEP C71060618F, December 2016, physical PDF page 88. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u Changing Parameter Settings or Values

This example explains changing C1-01 (Acceleration Time 1) from 10.0 seconds (default) to 20.0 seconds.

Step Display/Result

u Verifying Parameter Changes: Verify Menu

The Verify Menu lists edited parameters from the Programming Mode or as a result of Auto-Tuning. The Verify Menu helps determine which settings have been changed, and is particularly useful when replacing a drive. If no settings have been changed, the Verify Menu will read [nonE]. The Verify menu also allows users to access and re-edit previously edited parameters.

Note: The Verify Menu will not display A1-oo parameters (except for A1-02), nor will it display parameters A2-01 to A2-32 or E5-01 even if those parameters have been changed from default settings. The following example is a continuation of the steps beginning on page 88. Here, parameter C1-01 is accessed using the Verify Menu and is changed again to 20.0 s. To check the list of edited parameters:

u Switching Between LOCAL and REMOTE

Entering the run command using the LED operator is referred to as LOCAL, while entering the run command from an external device via the control circuit terminals or network option is referred to as REMOTE.

WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode. There are two ways to switch between LOCAL and REMOTE.

Note: 1. After selecting LOCAL, the LO/RE light will remain lit.

4.3 The Drive and Programming Modes

Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.

Changing C1-01 acceleration time example — PDF page 88

Source row Step Description Connector graphic LED display graphic
1 1. Turn on the power to the drive. The initial display appears. Right-arrow connector (not a key) F 0.00
2 2. Press the [UP] key until the Setup Mode Screen appears. Right-arrow connector (not a key) StUP
3 3. Press the [ENTER] key to view the parameter setting display. Right-arrow connector (not a key) APPL
4 4. Scroll through parameters by pressing the [UP] key until C1-01 appears. Right-arrow connector (not a key) C1-01
5 5. Press [ENTER] to view the current setting value (10.0). (Number farthest to the left flashes) Right-arrow connector (not a key) 0010.0 (leftmost digit flashes)
6 6. Press [RESET] until the desired number is selected. (“1” flashes) Right-arrow connector (not a key) 0010.0 (1 flashes)
7 7. Press the [UP] key and enter 0020.0. Right-arrow connector (not a key) 0020.0
8 8. Press [ENTER] and the drive will confirm the change. Right-arrow connector (not a key) End
9 9. The display automatically returns to the screen shown in Step 4. Right-arrow connector (not a key) C1-01
10 10. Press the [ESC] key until back at the initial display. Right-arrow connector (not a key) F 0.00

Verify menu example — PDF page 88

Source row Step Description Connector graphic LED display graphic
1 1. Turn on the power to the drive. The initial display appears. Right-arrow connector (not a key) F 0.00
2 2. Press [UP] until the display shows the “Verify” representation. Right-arrow connector (not a key) vrFY
3 3. Press [ENTER] to enter the list of parameters that have been edited from their original default settings. Scroll through the list by pressing the [UP] key. Right-arrow connector (not a key) A2-02
4 4. Press the [UP] key until C1-01 appears. Right-arrow connector (not a key) C1-01
5 5. Press the [ENTER] key to access the setting value. (number farthest to the left flashes) Right-arrow connector (not a key) 0020.0 (leftmost digit flashes)

Manual — LOCAL/REMOTE selection and Setup Group parameters — page 89

Source reference: SIEP C71060618F, December 2016, physical PDF page 89. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

  1. The drive will not allow the user to switch between LOCAL and REMOTE during run.

n Using the LO/RE Key on the LED Operator

Step Display/Result

n Using Input Terminals S1 through S7 to Switch between LO/RE

Switch between LOCAL and REMOTE using one of the digital input terminals S1 through S7 (set the corresponding parameter H1-01 through H1-07 to 1). Follow the example below to set the digital input terminals.

Note: 1. Refer to Parameter List on page 353 for a list of digital input selections. 2. Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator.

u Parameters Available in the Setup Group

n Setup Mode (STUP)

Parameters used for this drive are classified into A to U. To simplify the drive setup, frequently used parameters are selected and input into Setup Mode. 1. To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key until [StUP] is displayed. 2. Select the parameter and change the setting. Table 4.4 lists parameters available in the Setup group. If the desired parameter cannot be set in the Setup mode, use the Parameter Setting mode. Note: 1. When parameter A1-02 (Control Method Selection) is changed, some parameter set values are also changed automatically. 2. Use the “Par” menu in the Programming mode to access parameters not listed in the Setup Group. 3. Display parameters depend on A1-06. Refer to Application Selection on page 96.

Table 4.4 Setup Group Parameters

Parameter Name

4.3 The Drive and Programming Modes

Start-Up Programming & Operation

Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.

LOCAL/REMOTE selection example — PDF page 89

Source row Step Description Connector graphic LED display graphic
1 1. Turn on the power to the drive. The initial display appears. Right-arrow connector (not a key) F 0.00; DRV lit
2 2. Press [LO/RE]. The LO/RE light will light up. The drive is now in Local. To set the drive for REMOTE operation, press the [LO/RE] key again. Right-arrow connector (not a key) Operator example F60.00; LO/RE light changes from off to lit. Other key graphics remain original-only.

Table4.4 Setup Mode parameters left column — PDF page 89

Source row Parameter Name
1 A1-02 Control Method Selection
2 b1-01 Frequency Reference Selection 1
3 b1-02 Run Command Selection 1
4 b1-03 Stop Method Selection
5 C1-01 Acceleration Time 1
6 C1-02 Deceleration Time 1
7 C6-01 Duty Selection
8 C6-02 Carrier Frequency Selection
9 d1-01 Frequency Reference 1
10 d1-02 Frequency Reference 2
11 d1-03 Frequency Reference 3
12 d1-04 Frequency Reference 4
13 d1-17 Jog Frequency Reference

Table4.4 Setup Mode parameters right column — PDF page 89

Source row Parameter Name
1 E1-01 Input Voltage Reference
2 E1-03 V/f Pattern Selection
3 E1-04 Maximum Output Frequency
4 E1-05 Maximum Voltage
5 E1-06 Base Frequency
6 E1-09 Minimum Output Frequency
7 E1-13 Base Voltage
8 E2-01 Motor Rated Current
9 E2-04 Number of Motor Poles
10 E2-11 Motor Rate Capacity
11 H4-02 Terminal AM Gain Setting
12 L1-01 Motor Protection Function Selection
13 L3-04 Stall Prevention Selection during Deceleration

Manual — Startup flowchart index — page 90

Source reference: SIEP C71060618F, December 2016, physical PDF page 90. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.4 Start-up Flowcharts

The flowcharts in this section summarize basic steps required to start the drive. Use the flowcharts to determine the most appropriate start-up method for a given application. The charts are intended as a quick reference to help familiarize the user with start-up procedures.

Flowchart Subchart Objective Page

Startup flowchart index — PDF page 90

Source row Flowchart Sub-chart Purpose Page
1 A ⟦blank source cell⟧ Basic startup procedure and motor tuning. 91
2 ⟦blank source cell⟧ A-1 Simple motor setup with Energy Savings or Speed Search using V/f mode. 92
3 ⟦blank source cell⟧ A-2 High-performance operation using Open Loop Vector (OLV) motor control. 93
4 ⟦blank source cell⟧ A-3 Operation with Permanent Magnet (PM) motors. 94
5 ⟦blank source cell⟧ - Setup of drive using application specific selections. Refer to Application Selection on page 96. -

Manual — Flowchart A basic startup — page 91

Source reference: SIEP C71060618F, December 2016, physical PDF page 91. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

START→install/wire according to Chapters1,2,3→apply main power/adhering to safety. Application Presets A1-06 used? Yes→Application Selection section→rejoin control-mode branch. No→set A1-02 control mode→set basic parameters:b1-01/02 frequency/run-command sources;H1-□□,H2-□□,H3-□□,H4-□□,H6-□□ I/O terminals;d1-□□ multi-speed references if used;C1-□□ and C2-□□ accel/decel and S-curves;C6-01 heavy/normal duty;L3-04 if braking options used. A1-02=0 V/f→A-1;=2 Open Loop Vector→A-2;=5 Open Loop Vector for PM→A-3. Return from A-1/A-2/A-3→run without load/check rotation and external commands→couple load/check desired operation→fine-tune(PID if necessary)→check operation/verify settings→Drive is ready to run application. Last phrase is supplier flowchart endpoint, not completed commissioning.

u Flowchart A: Basic Start-up and Motor Tuning

Figure 4.6, Flowchart A, describes basic start-up sequence for the drive and motor system. This sequence varies slightly depending on application. Use drive default parameter settings in simple applications that do not require high precision.

4.4 Start-up Flowcharts

Start-Up Programming & Operation

Manual — Flowchart A1 V/f tuning — page 92

Source reference: SIEP C71060618F, December 2016, physical PDF page 92. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

From Flowchart A→set/verify V/f E1-□□. Energy Savings(b8-01=1)or Speed Estimation Speed Search(b3-24=1)enabled? YES→Rotational Auto-Tuning for V/f Control(T1-01=3)→Return to A. NO→motor cable longer than50 m? YES→Stationary Auto-Tuning terminal resistance(T1-01=2)→Return to A; NO→Return to A. Source conditions not general permission to perform work; original safety and complete instructions apply.

u Subchart A1: Simple Motor Setup with Energy Savings or Speed Search Using V/f Mode

Figure 4.7, Flowchart A1, describes simple motor setup for V/f control. V/f Motor Control is suited for the most basic applications such as fans or pumps. This procedure illustrates using Energy Savings and Speed Estimation Speed Search. V/ f control can be used where rotational auto-tuning cannot be performed.

4.4 Start-up Flowcharts

Manual — Flowchart A2 Open Loop Vector tuning — page 93

Source reference: SIEP C71060618F, December 2016, physical PDF page 93. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

From A→Possible for motor to rotate during tuning?<1>. YES→Rotating Auto-Tuning(T1-01=0)→Return to A. <1> Rotational tuning should be performed with load disconnected. NO→Motor test report/data sheet available? YES→enter motor data sheet into E2-□□→motor cable longer than50 m? YES→Stationary Auto-Tuning terminal resistance(T1-01=2)→Return to A;NO→Return to A. No motor report→calculate necessary E2-□□ using nameplate→Stationary Auto-Tuning terminal resistance(T1-01=2)→Return to A. No motor values are calculated in this transcription.

u Subchart A2: High Performance Operation Using Open Loop Vector Motor Control

Figure 4.8, Flowchart A2, describes Open Loop Vector Control for high-performance motor operation. This is appropriate for applications requiring high starting torque, torque limits, and improved speed regulation.

4.4 Start-up Flowcharts

Start-Up Programming & Operation

Manual — Flowchart A3 PM tuning — page 94

Source reference: SIEP C71060618F, December 2016, physical PDF page 94. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

From A→Motorcode is known? For E5-01(for Yaskawa PM Motors). YES→set motor code to E5-01→Return to A. NO→enter FFFF into E5-01→enter motor data E5-02 to E5-24→Return to A. Figure4.9 Operation with Permanent Magnet Motors; no motorcode or compatibility inferred.

u Subchart A3: Operation with Permanent Magnet Motors

Figure 4.9, Flowchart A3, describes tuning for PM motors in Open Loop Vector Control. PM motors can be used for energy savings in reduced or variable torque applications.

4.4 Start-up Flowcharts

Manual — Power-up checklist and status displays — page 95

Source reference: SIEP C71060618F, December 2016, physical PDF page 95. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.5 Powering Up the Drive

u Powering Up the Drive and Operation Status Display

n Powering Up the Drive

Review the following checklist before turning the power on.

Item to Check Description

n Status Display

When the power supply to the drive is turned on, the LED operator lights will appear as follows:

No. Name Description

Note: Display will vary depending on drive settings.

Start-Up Programming & Operation

Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.

Powering up checklist source conditions — PDF page 95

Source row Item Description
1 Power supply voltage Ensure the power supply voltage is correct: 200 V class: single-phase 200 to 240 Vac 50/60 Hz 200 V class: 3-phase 200 to 240 Vac 50/60 Hz 400 V class: 3-phase 380 to 480 Vac 50/60 Hz
2 Power supply voltage Properly wire the power supply input terminals (R/L1, S/L2, T/L3). (for single-phase 200 V class models, wire only R/L1 and S/L2)
3 Power supply voltage Check for proper grounding of drive and motor.
4 Drive output terminals and motor terminals Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.
5 Control circuit terminals Check control circuit terminal connections.
6 Drive control terminal status Open all control circuit terminals (off).
7 Status of the load and connected machinery Uncouple the motor from the load.

Power-up LED example displays — PDF page 95

Source row Status Display graphic Description
1 Normal Operation F 0.00; DRV lit The data display area displays the frequency reference. [DRV] is lit.
2 Fault Uv1; Main circuit low voltage (ex) Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible Solutions on page 267 for more information and possible solution. [ALM] and [DRV] are lit.

Manual — Application Selection and water-supply pump preset — page 96

Source reference: SIEP C71060618F, December 2016, physical PDF page 96. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.6 Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application Presets automatically sets the required parameters to the Application Preset default values and selects I/Os. In addition, the parameters most likely to be changed are assigned to the list of User Parameters, A2-01 through A2-16. These can be accessed in the Setup Mode and provide quicker application adjustment by eliminating the need to scroll through multiple menus. The following presets can be selected:

Note: 1. Do not set any value outside the allowable range for A1-06. Setting an out-of-range value will cause “APPL” to flash on the display in the Setup group and disable the up and down arrow keys on the digital operator. To fix this error, press the ESC key to return to the Setup group and then it will then be possible to switch to another mode using the up and down arrow keys. 2. A1-06 setting can only be changed by initializing the drive by first setting A1-03 to 2220. Setting A1-06 to a value that is out of range will not adversely affect drive operation. When the drive should not be initialized because initialization will cause other problems, then A1-06 does not need to be changed.

WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change the I/ O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.

No. Parameter Name Setting Range Default

<1> Application Preset settings 6 and 7 are only available in drive software versions PRG: 5010, PRG: 1010, and PRG: 1011. To determine the drive software version, refer to the PRG: field on the drive nameplate or drive parameter U1-25. <2> Available in drive software versions PRG: 1020 and later.

u Setting 1: Water Supply Pump Application

Table 4.5 Water Supply Pump Parameter Settings No. Name Default Setting

Table 4.6 Water Supply Pump: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name

b1-01 | Frequency Reference Selection 1

E1-08 | Middle Output Frequency Voltage

b1-02 | Run Command Selection 1

E2-01 | Motor Rated Current

b1-04 | Reverse Operation Selection

H1-05 | Multi-Function Digital Input Terminal S5 Function Selection

C1-01 | Acceleration Time 1

H1-06 | Multi-Function Digital Input Terminal S6 Function Selection

C1-02 | Deceleration Time 1

H1-07 | Multi-Function Digital Input Terminal S7 Function Selection

E1-03 | V/f Pattern Selection

L5-01 | Number of Auto Restart Attempts

A1-06 Application Selection — PDF page 96

Source row No. Parameter Name Setting Range Default
1 A1-06 Application Preset 0: Disabled 1: Water supply pump 2: Conveyor 3: Exhaust fan 4: HVAC 5: Compressor <1> 8: Conveyor 2 <2> 0

Table4.5 Pump preset A1-06=1 — PDF page 96

Source row Parameter Name Setting
1 A1-02 Control Method Selection 0: V/f Control
2 b1-04 Reverse Operation Selection 1: Reverse Prohibited
3 C1-01 Acceleration Time 1 1.0 s
4 C1-02 Deceleration Time 1 1.0 s
5 C6-01 Drive Duty Selection 1: Normal Duty
6 E1-03 V/f Pattern Selection 0FH
7 E1-07 Middle Output Frequency 30.0 Hz
8 E1-08 Middle Output Frequency Voltage 50.0 V
9 L2-01 Momentary Power Loss Operation Selection 1: Enabled
10 L3-04 Stall Prevention Selection during Deceleration 1: Enabled

Table4.6 Pump user parameters begin — PDF page 96

Source row Parameter Name Parameter Name
1 b1-01 Frequency Reference Selection 1 E1-08 Middle Output Frequency Voltage
2 b1-02 Run Command Selection 1 E2-01 Motor Rated Current
3 b1-04 Reverse Operation Selection H1-05 Multi-Function Digital Input Terminal S5 Function Selection
4 C1-01 Acceleration Time 1 H1-06 Multi-Function Digital Input Terminal S6 Function Selection
5 C1-02 Deceleration Time 1 H1-07 Multi-Function Digital Input Terminal S7 Function Selection
6 E1-03 V/f Pattern Selection L5-01 Number of Auto Restart Attempts

Manual — Pump continuation, conveyor, exhaust fan and HVAC presets — page 97

Source reference: SIEP C71060618F, December 2016, physical PDF page 97. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name No. Parameter Name

u Setting 2: Conveyor Application

Table 4.7 Conveyor: Parameter Settings No. Parameter Name Default Setting

Table 4.8 Conveyor: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name

u Setting 3: Exhaust Fan Application

Table 4.9 Exhaust Fan: Parameter Settings No. Parameter Name Default Setting

Table 4.10 Exhaust Fan: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name

u Setting 4: HVAC Fan Application

Table 4.11 HVAC Fan: Parameter Settings No. Parameter Name Default Setting

4.6 Application Selection

Start-Up Programming & Operation

E1-07 | Middle Output Frequency

− | −

A1-02 | Control Method Selection

C1-02 | Deceleration Time 1

b1-01 | Frequency Reference Selection 1

E2-01 | Motor Rated Current

b1-02 | Run Command Selection 1

L3-04 | Stall Prevention Selection during Deceleration

C1-01 | Acceleration Time 1

E1-08 | Middle Output Frequency Voltage

b1-04 | Reverse Operation Selection

b3-01 | Speed Search Selection at Start

H1-05 | Multi-Function Digital Input Terminal S5 Function Selection

H1-06 | Multi-Function Digital Input Terminal S6 Function Selection

H1-07 | Multi-Function Digital Input Terminal S7 Function Selection

E1-03 | V/f Pattern Selection

L5-01 | Number of Auto Restart Attempts

Table4.6 Pump user parameters continued — PDF page 97

Source row Parameter Name Parameter Name
1 E1-07 Middle Output Frequency − −

Table4.7 Conveyor preset A1-06=2 — PDF page 97

Source row Parameter Name Setting
1 A1-02 Control Method Selection 0: V/f Control
2 C1-01 Acceleration Time 1 3.0 s
3 C1-02 Deceleration Time 1 3.0 s
4 C6-01 Drive Duty Selection 0: Heavy Duty
5 L3-04 Stall Prevention Selection during Deceleration 1: Enabled

Table4.8 Conveyor user parameters — PDF page 97

Source row Parameter Name Parameter Name
1 A1-02 Control Method Selection C1-02 Deceleration Time 1
2 b1-01 Frequency Reference Selection 1 E2-01 Motor Rated Current
3 b1-02 Run Command Selection 1 L3-04 Stall Prevention Selection during Deceleration
4 C1-01 Acceleration Time 1 − −

Table4.9 Exhaust fan preset A1-06=3 — PDF page 97

Source row Parameter Name Setting
1 A1-02 Control Method Selection 0: V/f Control
2 b1-04 Reverse Operation Selection 1: Reverse Prohibited
3 C6-01 Drive Duty Selection 1: Normal Duty
4 E1-03 V/f Pattern Selection 0FH
5 E1-07 Middle Output Frequency 30.0 Hz
6 E1-08 Middle Output Frequency Voltage 50.0 V
7 L2-01 Momentary Power Loss Operation Selection 1: Enabled
8 L3-04 Stall Prevention Selection during Deceleration 1: Enabled

Table4.10 Exhaust fan user parameters — PDF page 97

Source row Parameter Name Parameter Name
1 b1-01 Frequency Reference Selection 1 E1-07 Middle Output Frequency
2 b1-02 Run Command Selection 1 E1-08 Middle Output Frequency Voltage
3 b1-04 Reverse Operation Selection E2-01 Motor Rated Current
4 b3-01 Speed Search Selection at Start H1-05 Multi-Function Digital Input Terminal S5 Function Selection
5 C1-01 Acceleration Time 1 H1-06 Multi-Function Digital Input Terminal S6 Function Selection
6 C1-02 Deceleration Time 1 H1-07 Multi-Function Digital Input Terminal S7 Function Selection
7 E1-03 V/f Pattern Selection L5-01 Number of Auto Restart Attempts

Table4.11 HVAC preset A1-06=4 begin — PDF page 97

Source row Parameter Name Setting
1 A1-02 Control Method Selection 0: V/f Control
2 b1-04 Reverse Operation Selection 1: Reverse Prohibited

Manual — HVAC continuation, compressor and Preset6 — page 98

Source reference: SIEP C71060618F, December 2016, physical PDF page 98. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name Default Setting

Table 4.12 HVAC Fan: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name

u Setting 5: Compressor Application

Table 4.13 Compressor: Parameter Settings No. Parameter Name Default Setting

Table 4.14 Compressor: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name

u Setting 6: Preset 6

Note: 1. Read the instructions listed in Notes on Controlling the Brake when Using Application Preset 6 on page 99 when using Application Preset 6 2. Perform Auto-Tuning after selecting Application Preset 6. 3. If UL3 appears on the operator display after Auto-Tuning is complete, set L6-01 to “0” to repeat the Auto-Tuning process.

Table 4.15 Preset 6: Parameters and Settings No. Parameter Name Default Setting

4.6 Application Selection

b1-01 | Frequency Reference Selection 1

E1-03 | V/f Pattern Selection

b1-02 | Run Command Selection 1

E1-04 | Maximum Output Frequency

b1-04 | Reverse Operation Selection

E2-01 | Motor Rated Current

C1-01 | Acceleration Time 1

H3-11 | Terminal A2 Gain Setting

C1-02 | Deceleration Time 1

H3-12 | Terminal A2 Bias Setting

C6-02 | Carrier Frequency Selection

L2-01 | Momentary Power Loss Operation Selection

d2-01 | Frequency Reference Upper Limit

L8-03 | Overheat Pre-Alarm Operation Selection

d2-02 | Frequency Reference Lower Limit

o4-12 | kWh Monitor Initialization

E1-07 | Middle Output Frequency

E1-08 | Middle Output Frequency Voltage

− | −

Table4.11 HVAC preset A1-06=4 continued — PDF page 98

Source row Parameter Name Setting
1 C6-01 Drive Duty Selection 1: Normal Duty
2 C6-02 Carrier Frequency Selection 3: 8.0 kHz
3 H2-03 Terminals P2 Function Selection 39: Watt Hour Pulse Output
4 L2-01 Momentary Power Loss Operation Selection 2: CPU Power Active - Drive will restart if power returns prior to control power supply shut down.
5 L8-03 Overheat Pre-Alarm Operation Selection 4: Operation at lower speed
6 L8-38 Carrier Frequency Reduction 2: Enabled across entire frequency range.

Table4.12 HVAC user parameters — PDF page 98

Source row Parameter Name Parameter Name
1 b1-01 Frequency Reference Selection 1 E1-03 V/f Pattern Selection
2 b1-02 Run Command Selection 1 E1-04 Maximum Output Frequency
3 b1-04 Reverse Operation Selection E2-01 Motor Rated Current
4 C1-01 Acceleration Time 1 H3-11 Terminal A2 Gain Setting
5 C1-02 Deceleration Time 1 H3-12 Terminal A2 Bias Setting
6 C6-02 Carrier Frequency Selection L2-01 Momentary Power Loss Operation Selection
7 d2-01 Frequency Reference Upper Limit L8-03 Overheat Pre-Alarm Operation Selection
8 d2-02 Frequency Reference Lower Limit o4-12 kWh Monitor Initialization

Table4.13 Compressor preset A1-06=5 — PDF page 98

Source row Parameter Name Setting
1 A1-02 Control Method Selection 0: V/f Control
2 b1-04 Reverse Operation Selection 1: Reverse Prohibited
3 C1-01 Acceleration Time 1 5.0 s
4 C1-02 Deceleration Time 1 5.0 s
5 C6-01 Drive Duty Selection 0: Heavy Duty
6 E1-03 V/f Pattern Selection 0FH
7 L2-01 Momentary Power Loss Operation Selection 1: Enabled
8 L3-04 Stall Prevention Selection during Deceleration 1: Enabled

Table4.14 Compressor user parameters — PDF page 98

Source row Parameter Name Parameter Name
1 b1-01 Frequency Reference Selection 1 E1-03 V/f Pattern Selection
2 b1-02 Run Command Selection 1 E1-07 Middle Output Frequency
3 b1-04 Reverse Operation Selection E1-08 Middle Output Frequency Voltage
4 C1-01 Acceleration Time 1 E2-01 Motor Rated Current
5 C1-02 Deceleration Time 1 − −

Table4.15 Preset6 settings begin — PDF page 98

Source row Parameter Name Setting
1 A1-02 Control Method Selection 2: Open Loop Vector Control
2 b1-01 Frequency Reference Selection 1 0: Operator

Manual — Preset6 continuation and brake controls — page 99

Source reference: SIEP C71060618F, December 2016, physical PDF page 99. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name Default Setting

<1> Disable L8-05 for single-phase models.

Table 4.16 Preset 6: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name

u Notes on Controlling the Brake when Using Application Preset 6

The frequency detection function is used for controlling the brake. When an external Baseblock command is present while a Run command is active, the frequency reference will be kept as long as the Run command is active. To avoid improper brake operation make sure that frequency detection is set so that the brake does not open during Baseblock (L4-07 = “0”, default). The table below shows how to set up the drive when using output terminals P2-PC as brake control output.

Brake Open/Close Brake Activation Level Control Mode

Function | Parameter | Signal | Parameter | V/f | OLV | OLV for PM

4.6 Application Selection

Start-Up Programming & Operation

A1-02 | Control Method Selection

d1-02 | Frequency Reference 2

b1-01 | Frequency Reference Selection 1

d1-03 | Frequency Reference 3

b6-01 | Dwell Reference at Start

E1-08 | Middle Output Frequency Voltage

b6-02 | Dwell Time at Start

H2-01 | Terminals MA, MB, and MC Function Selection

C1-01 | Acceleration Time 1

L1-01 | Motor Overload Protection Selection

C1-02 | Deceleration Time 1

L4-01 | Speed Agreement Detection Level

C6-02 | Carrier Frequency Selection

L6-02 | Torque Detection Level 1

d1-01 | Frequency Reference 1

L6-03 | Torque Detection Time 1

Table4.15 Preset6 settings continued — PDF page 99

Source row Parameter Name Setting
1 b6-01 Dwell Reference at Start 3.0 Hz
2 b6-02 Dwell Time at Start 0.3 s
3 C1-01 Acceleration Time 1 3.0 s
4 C1-02 Deceleration Time 1 3.0 s
5 C6-01 Drive Duty Selection 0: Heavy Duty
6 C6-02 Carrier Frequency Selection 2: 5 kHz
7 d1-01 Frequency Reference 1 6.0 Hz
8 d1-02 Frequency Reference 2 30.0 Hz
9 d1-03 Frequency Reference 3 60.0 Hz
10 E1-03 V/f Pattern Selection 0FH
11 H2-02 Terminals P1 Function Selection 37: During Frequency Output
12 H2-03 Terminals P2 Function Selection 5: Frequency Detection 2
13 L2-03 Momentary Power Loss Minimum Baseblock Time 0.3 s
14 L3-04 Momentary Power Loss Voltage Recovery Ramp Time 0: Disabled
15 L4-01 Speed Agreement Detection Level 2.0 Hz
16 L4-02 Speed Agreement Detection Width 0.0 Hz
17 L6-01 Torque Detection Selection 1 8: UL3 at RUN - Fault
18 L6-02 Torque Detection Level 1 5%
19 L6-03 Torque Detection Time 1 0.5 s
20 L8-05 Input Phase Loss Protection Selection 1: Enabled <1>
21 L8-07 Output Phase Loss Protection Selection 1: Enabled
22 L8-38 Carrier Frequency Reduction 1: Enabled below 6 Hz
23 L8-41 High Current Alarm Selection 1: Enabled (alarm is output)

Table4.16 Preset6 user parameters — PDF page 99

Source row Parameter Name Parameter Name
1 A1-02 Control Method Selection d1-02 Frequency Reference 2
2 b1-01 Frequency Reference Selection 1 d1-03 Frequency Reference 3
3 b6-01 Dwell Reference at Start E1-08 Middle Output Frequency Voltage
4 b6-02 Dwell Time at Start H2-01 Terminals MA, MB, and MC Function Selection
5 C1-01 Acceleration Time 1 L1-01 Motor Overload Protection Selection
6 C1-02 Deceleration Time 1 L4-01 Speed Agreement Detection Level
7 C6-02 Carrier Frequency Selection L6-02 Torque Detection Level 1
8 d1-01 Frequency Reference 1 L6-03 Torque Detection Time 1

Brake sequence source method — PDF page 99

Source row Method Parameter Required setting Related parameters V/f OLV OLV/PM
1 Frequency Detection 2 L4-07 = 0 Frequency Detection Level L4-01 = 1.0 to 3.0 Hz <1> O O −
2 Frequency Detection 2 H2-03 = 5 Frequency Detection Width L4-02 = 0.0 to 0.5 Hz <2> O O −

Manual — Brake controls continuation and Preset7 begin — page 100

Source reference: SIEP C71060618F, December 2016, physical PDF page 100. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure4.10 Frequency Detection2. Output frequency versus Time;L4-01 detection level;L4-02 difference indicator;Frequency detection2 ON/OFF. Source geometry retained in original; no unprinted timing or threshold inferred.

Input:S1-SC UP,OFF/ON;S6-SC Fast/Slow,OFF/ON. Output frequency versus Time,0,b6-02,b6-01,L4-01,d1-03,d1-01(Enabled when b1-01=0),b2-01,DC Injection braking. Output:P2-PC Frequency Detection2(H2-03=05),ON/OFF;Holding brake Closed→Open→Closed. Figure4.11 Holding Brake Time Chart. Exact timing geometry/overlap remains original-only; do not infer unnamed durations.

<1> This is the setting recommended when using Open Loop Vector Control. In V/f Control, set the level as the motor rated slip frequency plus 0.5 Hz. Not enough motor torque will be created if this value is set too low, and the load may tend to slip. Make sure this value is greater than the minimum output frequency and greater than the value of L4-02 as shown in the diagram below. If set too high, however, there may be a jolt at start. <2> Hysteresis for Frequency Detection 2 can be adjusted by changing the Frequency Detection Width (L4-02) between 0.0 and 0.5 Hz. If the load slips during stop, make changes in steps of 0.1 Hz until the load no longer slips.

The braking sequence should be designed as follows: • A normally open signal (N.O.) should be used to control the brake so that it is released when terminal P2-PC closes. • When an Up or Down command is entered, the brake should release. • When a fault signal is output, the brake should close.

• When changing the speed using an analog signal, make sure that the source of the frequency reference is assigned to the control circuit terminals (b1-01 = 1). • A sequence to open and close the holding brake appears in the diagram below.

u Setting 7: Preset 7

Table 4.17 Preset 7: Parameters and Settings No. Parameter Name Default Setting

4.6 Application Selection

Table4.17 Preset7 settings begin — PDF page 100

Source row Parameter Name Setting
1 A1-02 Control Method Selection 0: V/f Control
2 b1-01 Frequency Reference Selection 1 0: Operator
3 C1-01 Acceleration Time 1 3.0 s
4 C1-02 Deceleration Time 1 3.0 s
5 C6-01 Drive Duty Selection 0: Heavy Duty
6 C6-02 Carrier Frequency Selection 2: 5 kHz
7 d1-01 Frequency Reference 1 6.0 Hz
8 d1-02 Frequency Reference 2 30.0 Hz
9 d1-03 Frequency Reference 3 60.0 Hz
10 H1-05 Multi-Function Digital Input Terminal S5 Function 3: Multi-Step Speed 1
11 H1-06 Multi-Function Digital Input Terminal S6 Function 4: Multi-Step Speed 2
12 H2-02 Terminals P1 Function Selection 37: During frequency output
13 L3-04 Stall Prevention Selection during Deceleration 0: Disabled
14 L8-05 Input Phase Loss Protection Selection 1: Enabled <1>

Manual — Preset7 continuation and Conveyor2 preset — page 101

Source reference: SIEP C71060618F, December 2016, physical PDF page 101. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name Default Setting

<1> Disable L8-05 for single-phase models.

Table 4.18 Preset 7: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name

u Setting 8: Conveyor Application 2

This setting is available in drive software versions PRG: 1020 and later.

Table 4.19 Conveyor 2: Parameters and Settings No. Parameter Name Default Setting

Table 4.20 Conveyor 2: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name

4.6 Application Selection

Start-Up Programming & Operation

b1-01 | Frequency Reference Selection 1

d1-03 | Frequency Reference 3

C1-01 | Acceleration Time 1

E2-01 | Motor Rated Current

C1-02 | Deceleration Time 1

H1-05 | Multi-Function Digital Input Terminal S5 Function

C6-02 | Carrier Frequency Selection

H1-06 | Multi-Function Digital Input Terminal S6 Function

d1-01 | Frequency Reference 1

H2-01 | Terminals MA, MB, and MC Function Selection

d1-02 | Frequency Reference 2

L1-01 | Motor Overload Protection Selection

A1-02 | Control Method Selection

L3-04 | Stall Prevention Selection during Deceleration

b1-02 | Run Command Selection 1

n3-13 | Overexcitation Deceleration Gain

n3-21 | High-Slip Suppression Current Level

– | –

Table4.17 Preset7 continued — PDF page 101

Source row No. Parameter Name Default Setting
1 L8-07 Output Phase Loss Protection Selection 1: Triggered when a single phase is lost
2 L8-38 Carrier Frequency Reduction 1: Enabled below 6 Hz
3 L8-41 High Current Alarm Selection 1: Enabled (alarm output)

Table4.18 Preset7 user parameters — PDF page 101

Source row No. Parameter Name No. Parameter Name
1 b1-01 Frequency Reference Selection 1 d1-03 Frequency Reference 3
2 C1-01 Acceleration Time 1 E2-01 Motor Rated Current
3 C1-02 Deceleration Time 1 H1-05 Multi-Function Digital Input Terminal S5 Function
4 C6-02 Carrier Frequency Selection H1-06 Multi-Function Digital Input Terminal S6 Function
5 d1-01 Frequency Reference 1 H2-01 Terminals MA, MB, and MC Function Selection
6 d1-02 Frequency Reference 2 L1-01 Motor Overload Protection Selection

Table4.19 Conveyor2 settings — PDF page 101

Source row No. Parameter Name Default Setting
1 A1-02 Control Method Selection 0: V/f Control
2 C1-01 Acceleration Time 1 3.0 s
3 C1-02 Deceleration Time 1 3.0 s
4 C6-01 Drive Duty Selection 0: Heavy Duty
5 L3-04 Stall Prevention Selection during Deceleration 0: Disabled
6 n3-13 Overexcitation Deceleration Gain 1.4
7 n3-21 High-Slip Suppression Current Level 150%

Table4.20 Conveyor2 user parameters — PDF page 101

Source row No. Parameter Name No. Parameter Name
1 A1-02 Control Method Selection E2-01 Motor Rated Current
2 b1-01 Frequency Reference Selection 1 L3-04 Stall Prevention Selection during Deceleration
3 b1-02 Run Command Selection 1 n3-13 Overexcitation Deceleration Gain
4 C1-01 Acceleration Time 1 n3-21 High-Slip Suppression Current Level
5 C1-02 Deceleration Time 1 – –

Manual — Auto-Tuning types, prerequisites and load restrictions — page 102

Source reference: SIEP C71060618F, December 2016, physical PDF page 102. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.7 Auto-Tuning

u Types of Auto-Tuning

There are three types of Auto-Tuning. Select the best type of Auto-Tuning for the application. Refer to Auto-Tuning Procedure on page 103.

Type Setting Application Conditions and Benefits Control Mode

Note: Auto-Tuning cannot be performed on permanent magnet motors (IPM, SPM, etc.).

u Before Auto-Tuning the Drive

Check the items below before Auto-Tuning the drive.

n Basic Auto-Tuning Preparations

• Auto-Tuning automatically determines the electrical characteristics of the motor. This is fundamentally different from other types of Auto-Tuning features used in servo systems. • Auto-Tuning requires the user to input data from the motor nameplate. Make sure the information written on the nameplate is available before Auto-Tuning the drive. • For best performance, be sure the drive input supply voltage equals or exceeds the motor rated voltage.

Note: Performance can be enhanced by using a motor with a base voltage that is 20 V (40 V for 400 V class models) lower than the input supply voltage. This may be of special importance when operating the motor above 90% of base speed, where high torque precision is required. • Auto-Tuning is not possible with permanent magnet motors. • To cancel Auto-Tuning, press the STOP key on the LED operator. • Table 4.21 describes digital input and output terminal status during Auto-Tuning.

Table 4.21 Digital Input and Output Operation During Auto-Tuning

Auto-Tuning Type Digital Input Digital Output

WARNING! Sudden Movement Hazard. Do not release the mechanical brake during stationary Auto-Tuning. Inadvertent brake release may cause damage to equipment or injury to personnel. Ensure that the mechanical brake release circuit is not controlled by the drive multi- function digital outputs.

Note: It is recommended that Rotational Auto-Tuning is performed with the load disconnected. Failure to comply could result in improper drive operation. If Rotational Auto-Tuning is performed for a motor coupled to a load, the motor constants will be inaccurate and the motor may exhibit abnormal operation. Disconnect or decouple the motor from the load.

n Notes on Rotational Auto-Tuning

• For optimal performance, Auto-Tuning should only be done with the motor uncoupled from the load for applications requiring high performance over a wide speed range. • If motor and load cannot be uncoupled, the load should be lower than 30% of the rated load. Performing Rotational Auto- Tuning with a higher load will set motor parameters incorrectly, and can cause irregular motor rotation. • Ensure the motor-mounted brake is fully released if installed.

Types of Auto-Tuning — PDF page 102

Source row Type Setting Application Conditions and Benefits Control Mode
1 Rotational Auto-Tuning for V/f Control T1-01 = 3 • Assumes the motor can rotate during the Auto-Tuning process • Improves torque compensation, slip compensation, energy savings, and Speed Search performance • Should be performed when Speed Estimation Type Speed Search or Energy Saving is used in V/f Control V/f Control
2 Rotational Auto- Tuning for OLV Control T1-01 = 0 • Assumes the motor can rotate during the Auto-Tuning process • Achieves high-performance motor control and should be performed whenever Open Loop Vector Control is used Open Loop Vector Control
3 Stationary Auto- Tuning for Line-to-Line Resistance (V/f and OLV Control) T1-01 = 2 For use when: • The motor cable exceeds 50 m • The motor cable length has been modified after Auto-Tuning has been previously performed • When motor capacity and drive capacity differ V/f Control, Open Loop Vector Control

Table4.21 Digital I/O during Auto-Tuning — PDF page 102

Source row Auto-Tuning Type Digital Input Digital Output
1 Rotational Auto-Tuning for V/f Control Not available Functions the same as during normal operation
2 Rotational Auto-Tuning for OLV Control Not available Functions the same as during normal operation
3 Stationary Auto-Tuning for Line-to-Line Resistance Not available Maintains the status at the start of Auto-Tuning

Manual — Stationary tuning, interruption and procedure start — page 103

Source reference: SIEP C71060618F, December 2016, physical PDF page 103. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A – Normal Auto-Tuning Display: run10. B – Auto-Tuning Interrupted: Er-03. Figure4.12. These are source examples, not observed device status; exact LED segment shapes remain original-only.

• Connected machinery should be allowed to rotate the motor.

n Notes on Stationary Auto-Tuning for Terminal Resistance Only

• If the motor cable lead length has been significantly modified after Auto-Tuning has already been performed, perform Stationary Auto-Tuning with the new cables. • Perform when using motor cables longer than 50 m with V/f Control. WARNING! Electrical Shock Hazard. When executing stationary Auto-Tuning for line-to-line resistance only, the motor does not rotate, however, power is applied. Do not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury from electrical shock.

u Auto-Tuning Interruption and Fault Codes

If tuning results are abnormal or the STOP key is pressed before completion, Auto-Tuning will be interrupted and a fault code will be displayed on the digital operator.

u Performing Auto-Tuning

n Auto-Tuning Procedure

Auto-Tuning should generally be performed in the following steps. 1. Refer to Before Auto-Tuning the Drive on page 102. 2. Determine which type of Auto-Tuning best fits the application requirements following Figure 4.13.

4.7 Auto-Tuning

Start-Up Programming & Operation

Manual — Auto-Tuning selection flowchart and procedure — page 104

Source reference: SIEP C71060618F, December 2016, physical PDF page 104. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

START→Select Motor Control Mode A1-02. V/f Control A1-02=0→select V/f pattern E1-03→application allows motor rotation for Auto-Tuning? YES→V/f Rotational Auto-Tuning T1-01=3. NO→motor/drive cable longer than50m? YES→Stationary Auto-Tuning for Line-to-Line Resistance T1-01=2;NO→skip tuning. Open Loop Vector A1-02=2→can load disconnect from motor? YES→Rotational Auto-Tuning T1-01=0. NO→total connected load expected below30%motor rating? YES→notice:Auto-Tuning with connected load possible but may yield less than optimum performance→Rotational Auto-Tuning T1-01=0. NO→Use V/f control A1-02=0 or set motor parameters manually if OLV needed. PM Open Loop Vector A1-02=5→select motor code E5-01 or set motor data manually E5-□□→skip tuning. All branches join:run motor without load/fine tune if needed→connect load/run/fine tune if needed→verify system operates as required→Auto-Tuning finished. Endpoint is a source flowchart label, not actual testing or engineering approval. PDF106 notice gives stricter connected-load prohibition; preserve both, do not infer permission.

  1. Enter the type of Auto-Tuning to parameter T1-01. 4. Enter the motor nameplate data. 5. Start the Auto-Tuning process when prompted by the drive. 6. If Auto-Tuning was successfully performed, do a test run without the load and make any necessary parameter adjustments. 7. If the test run was successful, do a test run with the load connected and make parameter adjustments if necessary.

4.7 Auto-Tuning

Manual — Auto-Tuning selection and nameplate-entry examples — page 105

Source reference: SIEP C71060618F, December 2016, physical PDF page 105. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u Auto-Tuning Example

The following example illustrates how to perform Rotational Auto-Tuning for Open Loop Vector Control (A1-02 = 2).

n Set the Selected Type of Auto-Tuning

Step Display/Result

n Enter Data from the Motor Nameplate

After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.

Note: These instructions continue from Step 8 in “Set the Selected Type of Auto-Tuning”.

Note: 1. For the details on each setting, Refer to Input Data for Auto-Tuning on page 106. 2. For Stationary Auto-Tuning for Line-to-Line resistance only, set T1-02 and T1-04.

n Starting Auto-Tuning

WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.

WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.

NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in improper operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.

4.7 Auto-Tuning

Start-Up Programming & Operation

Literal historical source cells. Examples and blank checklists are not current device values or commissioning sign-off; retain complete safety text, preset/firmware conditions and footnotes.

Selected auto-tuning type example — PDF page 105

Source row Step Description Connector graphic Display/Result
1 1. Turn on the power to the drive. The initial display appears. Right-arrow connector (not a key) F 0.00; DRV lit
2 2. Press the key until the Auto-Tuning display appears. [Visible key(s), in source order: DOWN.] Right-arrow connector (not a key) AtUn
3 3. Press to begin setting parameters. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) T1-01
4 4. Press to display the value for T1-01. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) 02
5 5. Press to select the digit to edit. [Visible key(s), in source order: RESET.] Right-arrow connector (not a key) 02; selected digit flashes
6 6. Press and set the drive to perform Rotational Auto-Tuning (00). [Visible key(s), in source order: UP.] Right-arrow connector (not a key) 00
7 7. Save the setting by pressing . [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) End
8 8. The display automatically returns to the display shown in Step 3. Right-arrow connector (not a key) T1-01

Entering motor nameplate example — PDF page 105

Source row Step Description Connector graphic Display/Result
1 1. Press to access the motor output power parameter T1-02. [Visible key(s), in source order: UP.] Right-arrow connector (not a key) T1-02
2 2. Press to view the default setting. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) 000.40
3 3. Press to select the digit to edit. [Visible key(s), in source order: RESET.] Right-arrow connector (not a key) 000.40; selected digit flashes
4 4. Press and enter the motor power nameplate data in kW. [Visible key(s), in source order: UP.] Right-arrow connector (not a key) 000.20
5 5. Press to save the setting. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) End
6 6. The display automatically returns to the display in Step 1. Right-arrow connector (not a key) T1-02
7 7. Repeat Steps 1 through 5 to set the following parameters: • T1-03, Motor Rated Voltage • T1-04, Motor Rated Current • T1-05, Motor Base Frequency • T1-06, Number of Motor Poles • T1-07, Motor Base Speed Right-arrow connector (not a key) T1-03 → continuation arrow → T1-10

Manual — Starting tuning and T1-00 to T1-02 — page 106

Source reference: SIEP C71060618F, December 2016, physical PDF page 106. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

NOTICE: Never perform Rotational Auto-Tuning for a motor connected to a load. Failure to comply could result in improper drive operation. If Rotational Auto-Tuning is performed for a motor coupled to a load, the motor parameters will be inaccurate and the motor may exhibit abnormal operation. Disconnect or decouple the motor from the load.

Enter the required information from the motor nameplate. Press [UP] to proceed to the Auto-Tuning start display.

Note: These instructions continue from Step 7 in “Enter Data from the Motor Nameplate”.

Step Display/Result

u Input Data for Auto-Tuning

The T1-□□ parameters are used to set the Auto-Tuning input data.

Note: 1. Cycling power to the drive will reset any values set during the Auto-Tuning process to factory defaults. 2. For motors that are to be operated in the field weakening range, first perform the Auto-Tuning with the base data, i.e. the frequency at which the motor is operating with its rated voltage (base frequency). After Auto-Tuning is complete, change the maximum frequency E1-04 to the desired value.

n T1-00: Motor 1/Motor 2 Selection

Selects the motor to be tuned when motor 1/2 switching is enabled, i.e., a digital input is set for function H1-□□ = 16. This parameter is not displayed if motor 1/2 switching is disabled.

No. Name Setting Range Default

Setting 1: Motor 1 Auto-Tuning automatically sets parameters E1-□□ and E2-□□ for motor 1.

Setting 2: Motor 2 Auto-Tuning automatically sets parameters E3-□□ and E4-□□ for motor 2. Make sure that motor 2 is connected to the drive for Auto-Tuning.

n T1-01: Tuning Mode Selection

Sets the type of Auto-Tuning to be used. Refer to Types of Auto-Tuning on page 102 for details on different types of Auto- Tuning.

Setting 0: Rotating Auto-Tuning for Open Loop Vector Control

Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance

Setting 3: Rotating Auto-Tuning for V/f Control

n T1-02: Motor Rated Power

Used to set the motor rated power according to the motor nameplate value. For optimal performance, the motor rated power should be between 50 and 100% of the drive rating.

<1> The setting range differs based on drive software version. PRG: 1016 and later: 0.03 to 650.00 kW

4.7 Auto-Tuning

Starting Auto-Tuning example — PDF page 106

Source row Step Description Connector graphic Display/Result
1 1. After setting T1-07 as illustrated in the previous section, press and confirm the display is as described below: [Visible key(s), in source order: UP.] Right-arrow connector (not a key) run10
2 2. Press [RUN] to activate Auto-Tuning. [DRV] flashes. Note: The first digit indicates which motor is undergoing Auto-Tuning (motor 1 or motor 2). The second digit indicates the type of Auto-Tuning being performed. Right-arrow connector (not a key) run10; DRV flashes
3 3. Auto-Tuning finishes in approximately one to two minutes. Right-arrow connector (not a key) End

T1-00 Motor1/2 selection — PDF page 106

Source row No. Parameter Name Setting Range Default
1 T1-00 Motor 1/2 Selection 1 or 2 1

T1-01 Auto-Tuning mode — PDF page 106

Source row No. Parameter Name Setting Range Default
1 T1-01 Auto-Tuning Mode Selection 0, 2 (OLV) 2, 3 (V/f) 0 (OLV) 2 (V/f)

T1-02 Motor rated power — PDF page 106

Source row No. Parameter Name Setting Range Default
1 T1-02 Motor Rated Power <1> Determined by o2-04 and C6-01

Manual — Tuning inputs T1-03 to T1-11 and software restrictions — page 107

Source reference: SIEP C71060618F, December 2016, physical PDF page 107. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

PRG: 1015 and earlier: 0.00 to 650.00 kW

n T1-03: Motor Rated Voltage (T1-01 = 0 or 3)

Used to set the motor rated voltage according to the motor nameplate value. If the motor is used above its base speed, enter the voltage at base speed here. For higher tuning precision and better control performance, enter the motor no-load voltage here if known. The motor no-load voltage is referred as to the voltage needed to operate the motor under no-load condition at its rated speed. Refer to the motor data sheet.

No. Name Setting Range Default

<1> Values shown here are for 200 V class drives. Double values when using a 400 V class drive.

n T1-04: Motor Rated Current

Used to set the motor rated current according to the motor nameplate value. For optimal performance in OLV, the motor rated current should be between 50 and 100% of the drive rating. Enter the current at the motor base speed.

n T1-05: Motor Rated Frequency (T1-01 = 0 or 3)

Used to set the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or the motor is used in the field weakening area, enter the base frequency here. For higher tuning precision and better control performance, enter the motor no-load frequency here if known. The “no-load frequency” refers to the frequency needed to operate the motor under no-load condition at its rated speed. Refer to the motor data sheet.

n T1-06: Number of Motor Poles (T1-01 = 0 or 3)

Used to set the number of motor poles according to the motor nameplate value.

n T1-07: Motor Base Speed (T1-01 = 0 or 3)

Used to set the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is used or the motor is used in the field weakening area, enter the speed at base frequency here.

n T1-11: Motor Iron Loss (T1-01 = 3)

Provides iron loss information for determining the Energy Saving coefficient. If E2-10 has been changed and the power has been cycled, the value set to E2-10 will appear as the default in T1-11. If the value of T1-02 is not changed during Auto- Tuning data input, the drive will select a value that is typical for the motor power entered to T1-02.

4.7 Auto-Tuning

Start-Up Programming & Operation

T1-03 Motor rated voltage — PDF page 107

Source row No. Parameter Name Setting Range Default
1 T1-03 Motor Rated Voltage 0.0 to 255.5 V <1> 200.0 V <1>

T1-04 Motor rated current — PDF page 107

Source row No. Parameter Name Setting Range Default
1 T1-04 Motor Rated Current 10 to 200% of drive rated current Determined by o2-04 and C6-01

T1-05 Motor base frequency — PDF page 107

Source row No. Parameter Name Setting Range Default
1 T1-05 Motor Base Frequency 0.0 to 400.0 Hz 60.0 Hz

T1-06 Motor poles — PDF page 107

Source row No. Parameter Name Setting Range Default
1 T1-06 Number of Motor Poles 2 to 48 4

T1-07 Motor base speed — PDF page 107

Source row No. Parameter Name Setting Range Default
1 T1-07 Motor Base Speed 0 to 24000 r/min 1750 r/min

T1-11 Motor iron loss — PDF page 107

Source row No. Parameter Name Setting Range Default
1 T1-11 Motor Iron Loss 0 to 65535 W Determined by o2-04 and C6-01

Manual — No-load operation test procedure — page 108

Source reference: SIEP C71060618F, December 2016, physical PDF page 108. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.8 No-Load Operation Test Run

u No-Load Operation Test Run

This section explains how to operate the drive with the motor uncoupled from the load during a test run.

n Before Starting the Motor

Check the following items before operation: • Ensure the area around the motor is safe. • Ensure external emergency stop circuitry is working properly and other safety precautions have been taken.

n During Operation

Check the following items during operation: • The motor should rotate smoothly (i.e., no abnormal noise or oscillation). • The motor should accelerate and decelerate smoothly.

n No-Load Operation Instructions

The following example illustrates a test run procedure using the digital operator.

Note: Before starting the motor, set the frequency reference d1-01 to 6 Hz.

Step Display/Result

No-load operation example — PDF page 108

Source row Step Description Connector graphic Display/Result
1 1. Turn on the power to the drive. The initial display appears. Right-arrow connector (not a key) F 0.00; DRV lit
2 2. Press the key to select LOCAL. The LO/RE LED will turn on. [Visible key(s), in source order: LO/RE.] Right-arrow connector (not a key) F 0.00; operator graphic with LO/RE LOCAL light
3 3. Press to give the drive a Run command. RUN will light and the motor will rotate at 6 Hz. [Visible key(s), in source order: RUN.] Right-arrow connector (not a key) F6.00; RUN light Off → On
4 4. Ensure the motor is rotating in the correct direction and no faults or alarms occur. Right-arrow connector (not a key) Motor Forward illustration; actual rotation geometry remains original
5 5. If there is no error in step 4, press to increase the frequency reference. Increase the frequency in 10 Hz increments verifying smooth operation results at all speeds. For each frequency, monitor the drive output current (U1-03) through the LED operator to confirm the current is well below the motor rated current. Example: 6 Hz → 60 Hz. [Visible key(s), in source order: UP.] Right-arrow connector (not a key) F60.00
6 6. The drive should operate normally. Press STOP to stop the motor. RUN flashes until the motor comes to a complete stop. [Visible key(s), in source order: STOP.] Right-arrow connector (not a key) F60.00; RUN light Flashing → Off

Manual — Connected-load test procedure — page 109

Source reference: SIEP C71060618F, December 2016, physical PDF page 109. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.9 Test Run with Load Connected

u Test Run with the Load Connected

After performing a no-load test run connect the load and proceed to run the motor and load together.

n Notes on Connected Machinery

• Clear the area around the motor. • The motor should come to a complete stop without problems. • Connect the machinery. • Fasten all installation screws properly. Check that the motor and connected machinery are held in place. • Confirm that the Fast-stop circuit or mechanical safety measures operate correctly. • Be ready to press the STOP button in case of emergency.

n Checklist Before Operation

• The motor should rotate in the proper direction. • The motor should accelerate and decelerate smoothly.

n Operating the Motor under Loaded Conditions

Test run the application similarly to the no-load test procedure when connecting the machinery to the motor. • Check monitor parameter U1-03 to ensure there is no overcurrent. • If the application permits running the load in the reverse direction, try changing motor direction and the frequency reference while watching for abnormal motor oscillation or vibration. • Correct any problems that occurs with hunting, oscillation, or other control-related issues.

Start-Up Programming & Operation

Manual — Parameter verification, backup, access and passwords — page 110

Source reference: SIEP C71060618F, December 2016, physical PDF page 110. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.10 Verifying Parameter Settings and Backing Up Changes

Check changes to parameter settings as a result of Auto-Tuning using the Verify function. Refer to Verifying Parameter Changes: Verify Menu on page 88. Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental modification of parameter settings.

u Backing Up Parameter Values: o2-03

Performing the following procedure stores all parameters settings to drive memory where they can later be recalled if necessary. Set o2-03 to “1” to save parameter changes. This saves all parameter settings, and then returns o2-03 to 0. The drive can now “recall” the saved parameters by performing a “user-initialization” (A1-03 = 1110).

No. | Parameter Name | Description | Setting Range

Default Setting

u Parameter Access Level: A1-01

Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A1-□□ and U□-□□ only. Other parameters are not displayed. Setting the Access Level for “User Parameters” (A1-01 = 1) allows the user to access parameters that have been previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific application.

No. | Parameter Name | Description | Setting Range | Default

u Password Settings: A1-04, A1-05

The user can set a password to the drive to restrict access. The password is selected via parameter A1-05. The selected password must be entered in parameter A1-04 to unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following parameters cannot be viewed or edited until the value programmed into A1-04 correctly matches the value as programmed in parameter A1-05: A1-01, A1-02, A1-03, A1-06 and A2-01 through A2-33.

Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and simultaneously depress the [STOP] key and the [UP] key.

Parameter backup/initialization — PDF page 110

Source row No. Parameter Name Description Setting Range Default Setting
1 o2-03 User Parameter Default Value Allows storing of parameter settings as a User Initialization Selection. 0: Saved/Not set 1: Set Defaults - Saves current parameter settings as user default settings. 2: Clear All - Clears the currently saved user settings. After saving the user parameter set value, the items of 1110 (User Parameter Initialize) are displayed in A1-03 (User Parameter Default Value). 0 to 2 0
2 A1-03 Initialize Parameters Selects a method to initialize the parameters. 0: No Initialize 1110: User Initialize (The user must first program and store desired settings using parameter o2-03) 2220: 2-Wire Initialization (parameter initialized prior to shipment) 3330: 3-Wire Initialization 5550: oPE4 Fault reset 0 to 5550 0

Parameter access and user selection — PDF page 110

Source row No. Parameter Name Description Setting Range Default
1 A1-01 Access Level Selection Selects which parameters are accessible via the digital operator. 0: Operation only (A1-01, -04, and -06 can be set and monitored. U parameters can be monitored) 1: User Parameters (Only those recently changed among application parameters A2-01 to -16 and A2-17 to -32 can be set and monitored) 2: Advanced Access Level (All parameters can be set and monitored) 0 to 2 2
2 A2-01 to A2-32 User Parameters 1 to 32 Parameters selected by the user are stored to the User Parameter menu. This includes recently viewed parameters or parameters specifically selected for quick access. If parameter A2-33 is set to 1, recently viewed parameters will be listed between A2-17 and A2-32. Parameters A2-01 through A2-16 must be manually selected by the user. If A2-33 is set to 0, then recently viewed parameters will not be saved to the User Parameter group. The entire A2 parameter group is now available for manual programming. b1-01 to o2-08 –
3 A2-33 User Parameter Automatic Selection 0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. 1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access. The most recently changed parameter is registered in A2-17. The second most recently changed parameter is registered in A2-18. 0, 1 1

Manual — Parameter copy and software options — page 111

Source reference: SIEP C71060618F, December 2016, physical PDF page 111. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u Copy Function (Optional)

Parameter settings can be copied to another drive to simplify parameter restoration or multiple drive setup. The drive supports the following options:

n USB/Copy Unit (JVOP-181)

The copy unit is an external option connected to the drive to copy parameter settings to another drive. It includes a USB adapter to connect the drive to a PC.

n LCD Operator (JVOP-180)

The LCD operator operates the drive and supports copying, importing, and verifying parameter settings using the parameters o3-01 and o3-02.

Note: Use of the LCD operator requires that the drive is running drive software version PRG: 1012 or later. The LCD operator is not compatible with drive software version PRG: 5010.

n LED Operator (JVOP-182)

The LED operator operates the drive and supports copying, importing, and verifying parameter settings.

Note: Use of the LED operator requires that the drive is running drive software version PRG: 1014 or later. The LED operator is not compatible with version PRG: 5010.

n Drive Wizard Plus

Drive Wizard Plus is a PC software tool for parameter management, monitoring, and diagnosis. Drive Wizard Plus can load, store, and copy drive parameter settings. For details, refer to Help in the Drive Wizard Plus software. The installation files can be obtained at no charge from: U.S.: http://www.yaskawa.com

4.10 Verifying Parameter Settings and Backing Up Changes

Start-Up Programming & Operation

Manual — Test-run checklist1–20 and mode scopes — page 112

Source reference: SIEP C71060618F, December 2016, physical PDF page 112. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

4.11 Test Run Checklist

Review the checklist before performing a test run. Check each item that applies.

No. Checklist Page

Check the items that correspond to the control mode being used.

WARNING! Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on terminal S1 may cause the drive to start.

V/f Control (A1-02 = 0)

Open Loop Vector Control (A1-02 = 2)

PM Open Loop Vector Control (A1-02 = 5)

Proceed to the following checklist after checking items 4 through 9.

Test-run checklist1–3 — PDF page 112

Source row Checkbox No. Checklist Page
1 Unchecked source checkbox 1 Thoroughly read the manual before performing a test run. –
2 Unchecked source checkbox 2 Turn the power on. 95
3 Unchecked source checkbox 3 Set the voltage for the power supply to E1-01. 169

Test-run checklist10–20 — PDF page 112

Source row Checkbox No. Checklist Page
1 Unchecked source checkbox 10 The [DRV] should illuminate after giving a run command. –
2 Unchecked source checkbox 11 To give a run command and frequency reference from the LED Digital Operator, press [LO/RE] to set to LOCAL. The LO/RE key lights while LOCAL is displayed. 89
3 Unchecked source checkbox 12 If the motor rotates in the opposite direction during the test run, switch two of the drive output terminals (U/T1, V/T2, W/T3). 95
4 Unchecked source checkbox 13 Select the correct duty rating (C6-01) for the application. –
5 Unchecked source checkbox 14 Set the correct values for the motor rated current (E2-01) and the motor protection selection (L1-01) to ensure motor thermal protection. –
6 Unchecked source checkbox 15 If the run command and frequency reference are provided via the control circuit terminals, set the drive for REMOTE and be sure the LO/RE light is out. 89
7 Unchecked source checkbox 16 If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level (0 to 10 V) or the correct current input signal level (4 to 20 mA or 0 to 20 mA). 89
8 Unchecked source checkbox 17 Set the proper voltage to terminal A1. (0 to 10 V). 121
9 Unchecked source checkbox 18 Set the proper current to terminal A2. (4 to 20 mA or 0 to 20 mA). 121
10 Unchecked source checkbox 19 When current input is used, set H3-09 to “2” (4 to 20 mA) or “3” (0 to 20 mA) and set H3-10 to “0”. –
11 Unchecked source checkbox 20 When current input is used, switch the drive built-in DIP switch S1 from the V-side (OFF) to I-side (ON). –

Test-run checklist4–5:V/f A1-02=0 — PDF page 112

Source row Checkbox No. Checklist Page
1 Unchecked source checkbox 4 Select the best V/f pattern according to the application and motor characteristics. Example: If using a motor with a rated frequency of 60.0 Hz, set E1-03 to “1”. –
2 Unchecked source checkbox 5 Perform Auto-Tuning for Energy Savings if using Energy Saving functions. 102

Test-run checklist6–8:OLV A1-02=2 — PDF page 112

Source row Checkbox No. Checklist Page
1 Unchecked source checkbox 6 Uncouple the load from the motor when performing Rotational Auto-Tuning. 102
2 Unchecked source checkbox 7 Perform Rotational Auto-Tuning. 102
3 Unchecked source checkbox 8 The following data entered during Auto-Tuning should match the information written on the motor nameplate: • motor rated output power (kW) → T1-02 • rated voltage (V) → T1-03 • rated current (A) → T1-04 • base frequency (Hz) → T1-05 • number of motor poles → T1-06 • motor rotations per minutes (r/min) → T1-07 106

Test-run checklist9:PM OLV A1-02=5 — PDF page 112

Source row Checkbox No. Checklist Page
1 Unchecked source checkbox 9 Set permanent motor parameters E5-01 through E5-24 94

Manual — Test-run checklist21 continuation — page 113

Source reference: SIEP C71060618F, December 2016, physical PDF page 113. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Checklist Page

4.11 Test Run Checklist

Start-Up Programming & Operation

Test-run checklist21 continued — PDF page 113

Source row Checkbox No. Checklist Page
1 Unchecked source checkbox 21 Set the minimum and maximum frequency references to the desired values. Make the following adjustments if the drive does not operate as expected: Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for input A1, H3-11 for input A2) until the frequency reference value reaches the desired value. Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for input A1, H3-12 for input A2) until the frequency reference value reaches the desired minimum value. –

Manual — Language, parameter access and control modes — page 116

Source reference: SIEP C71060618F, December 2016, physical PDF page 116. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

5.1 A: Initialization

The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display language, access levels, initialization, and password are located in this group.

u A1: Initialization

n A1-00: Language Selection

Selects the display language for the digital operator.

Note: This parameter is not reset when the drive is initialized using parameter A1-03.

No. Parameter Name Setting Range Default

Setting 0: English Setting 1: Japanese Setting 2: German Setting 3: French Setting 4: Italian Setting 5: Spanish Setting 6: Portuguese Setting 7: Chinese n A1-01: Access Level Selection

Allows or restricts access to drive parameters.

Setting 0: Operation Only Access is restricted to parameters A1-01, A1-04, A1-06, and all U monitor parameters.

Setting 1: User Parameters Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the Setup mode of the digital operator.

Setting 2: Advanced Access Level (A) and Setup Access Level (S) All parameters can be viewed and edited.

Notes on Parameter Access • If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2 parameters cannot be modified. • If a digital input programmed for Program Lockout (H1-□□ = 1B) is enabled, parameter values cannot be modified, even though the A1-01 is set to 1 or 2. • If parameters are changed via serial communication the parameters cannot be changed from the digital operator until an Enter command is received from the serial communication.

n A1-02: Control Method Selection

Selects the Control Method of the drive.

Note: 1. Be sure to perform Auto-Tuning when using one of the vector control modes. 2. Reinitializing the drive does not reset A1-02 to the factory default value.

Setting 0: V/f Control • For general-purpose and multiple motor applications.

A1-00 language — PDF page 116

Source row No. Parameter Name Setting Range Default
1 A1-00 Language Selection 0 to 7 0

A1-01 access level — PDF page 116

Source row No. Parameter Name Setting Range Default
1 A1-01 Access Level Selection 0 to 2 2

A1-02 control method — PDF page 116

Source row No. Parameter Name Setting Range Default
1 A1-02 Control Method Selection 0, 2, 5 0

Manual — Control modes, initialization and nonreset parameters — page 117

Source reference: SIEP C71060618F, December 2016, physical PDF page 117. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

• For use when the motor parameters are unknown and Auto-tuning can not be performed.

Setting 2: Open Loop Vector • For general, variable-speed applications. • For applications requiring precise speed control, quick response, and higher torque at low speeds.

Setting 5: PM Open Loop Vector For operating SPM, IPM, and various permanent magnet motors. Takes advantage of Energy Saving features when operating with derated torque.

n A1-03: Initialize Parameters

Resets parameter settings back to their original default values. After the initialization the parameter automatically returns to 0.

No. Parameter Name Setting Range Default

Setting 0: No Initialization

Setting 1110: User Initialize The modified drive parameters are returned to the values selected as user settings. User settings are stored when parameter o2-03 = “1: Set Defaults”.

Note: A “user-initialization” resets all parameters to a user-defined set of default values that were previously saved to the drive. To clear the user- defined default values, set parameter o2-03 to “2”.

Setting 2220: 2-Wire Initialization Resets all parameters back to their original default settings with digital inputs S1 and S2 configured as forward run and reverse run, respectively. A 2-wire sequence assigns functions to input terminals S1 and S2. Refer to Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence on page 191 for more information.

Setting 3330: 3-Wire Initialization The drive parameters are returned to factory default values with digital inputs S1, S2, and S5 configured as run, stop, and forward/reverse respectively. A 3-wire sequence assigns functions to input terminals S1, S2, and S5. Refer to Setting 0: 3-Wire Sequence on page 185 for more information.

Setting 5550: oPE04 Reset If parameters on a certain drive have been edited and then a different terminal block is installed with different settings saved in its built-in memory, an oPE04 error will appear on the display. To use the parameter settings saved to the terminal block memory, set A1-03 to “5550”.

Notes on Parameter Initialization The parameters shown in Table 5.1 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. The fault history will not be reset when the drive is initialized by A1-03 = 2220 or 3330. Although the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.

Table 5.1 Parameters not Changed by Drive Initialization No. Parameter Name

5.1 A: Initialization

Parameter Details

A1-03 initialization — PDF page 117

Source row No. Parameter Name Setting Range Default
1 A1-03 Initialize Parameters 0, 1110, 2220, 3330, 5550 0

Table5.1 parameters not changed by initialization begin — PDF page 117

Source row No. Parameter Name
1 A1-00 Language Selection
2 A1-02 Control Method Selection
3 A1-07 DriveWorksEZ Function Selection
4 E1-03 V/f Pattern Selection
5 E5-01 Motor Code Selection (for PM motors)
6 E5-02 Motor Rated Capacity (for PM motors)
7 E5-03 Motor Rated Current (for PM motors)
8 E5-04 Motor Poles (for PM motors)
9 E5-05 Motor Stator Resistance (for PM motors)
10 E5-06 Motor d Axis Inductance (for PM motors)

Manual — Nonreset continuation and password lock examples — page 118

Source reference: SIEP C71060618F, December 2016, physical PDF page 118. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name

n A1-04, A1-05: Password and Password Setting

A1-04 is for entering the password when the drive is locked. A1-05 is a hidden parameter used to set the password.

No. Parameter Name Setting Range Default

How to use the Password The user can set a password for the drive to restrict access. The password is set to A1-05 and must be entered to A1-04 to unlock parameter access. Until the correct password is entered, the following parameters cannot be viewed or edited: A1-01, A1-02, A1-03, A1-06, and A2-01 through A2-33. The instructions below demonstrate how to set a new password. Here, the password set is “1234”. An explanation follows on how to enter the password to unlock the parameters.

Table 5.2 Setting the Password for Parameter Lock

Step Display/Result

Table 5.3 Check to see if A1-01 is locked (continuing from step 10 above)

5.1 A: Initialization

Table5.1 parameters not changed by initialization continued — PDF page 118

Source row No. Parameter Name
1 E5-07 Motor q Axis Inductance (for PM motors)
2 E5-09 Motor Induction Voltage Constant 1 (for PM motors)
3 E5-24 Motor Induction Voltage Constant 2 (for PM motors)
4 o2-04 Drive/kVA Selection
5 L8-35 Installation Selection

A1-04/05 password — PDF page 118

Source row No. Parameter Name Setting Range Default
1 A1-04 Password 0 to 9999 0
2 A1-05 Password Setting 0 to 9999 0

Table5.2 setting example password1234 — PDF page 118

Source row Step Description Connector graphic Display/Result
1 1. Turn on the power to the drive. The initial display appears. Right-arrow connector (not a key) F 0.00; DRV lit
2 2. Scroll to the Parameter Setup display and press . [Visible key(s), in source order: UP.] Right-arrow connector (not a key) PAr
3 3. Scroll to the right by pressing . [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) A1-01
4 4. Select the flashing digits by pressing . [Visible key(s), in source order: RESET.] Right-arrow connector (not a key) A1-01; selected digits flash
5 5. Select A1-04 by pressing . [Visible key(s), in source order: UP.] Right-arrow connector (not a key) A1-04
6 6. Press the key while holding down at the same time. A1-05 will appear. Note: A1-05 is normally hidden, but can be displayed by following the directions listed here. [Visible key(s), in source order: STOP + UP simultaneously.] Right-arrow connector (not a key) A1-05; “05” flashes
7 7. Press the key. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) 0000
8 8. Use , and to enter the password. [Visible key(s), in source order: RESET, DOWN, UP.] Right-arrow connector (not a key) 1234
9 9. Press to save what was entered. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) End
10 10. The display automatically returns to the display shown in step 5. Right-arrow connector (not a key) A1-05

Table5.3 checking parameter lock — PDF page 118

Source row Step Description Connector graphic Display/Result
1 1. Press to display A1-01. [Visible key(s), in source order: DOWN.] Right-arrow connector (not a key) A1-01; “01” flashes
2 2. Press to display the value set to A1-01. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) 0002
3 3. Press and , making sure that the setting values cannot be changed. [Visible key(s), in source order: DOWN, UP.] Blank source cell Blank source cell
4 4. Press to return to the first display. [Visible key(s), in source order: ESC.] Right-arrow connector (not a key) PAr

Manual — Password unlock example, presets and DriveWorksEZ — page 119

Source reference: SIEP C71060618F, December 2016, physical PDF page 119. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table 5.4 Enter the Password to Unlock Parameters (continuing from step 4 above)

Step Display/Result

Note: Parameter settings can be edited after entering the correct password. Performing a 2-Wire or 3-Wire initialization resets the password to “0000”. Reenter the password to parameter A1-05 after drive initialization.

n A1-06: Application Presets

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application Presets automatically sets the required parameters to default values and selects I/Os. In addition, Application Preset parameters are assigned to the list of User Parameters, A2-01 through A2-16. These can be accessed in the Setup Mode and provide quicker application adjustment by eliminating the need to scroll through multiple menus. Refer to Application Selection on page 96 for details on parameter A1-06.

n A1-07: DriveWorksEZ Function Selection

DriveWorksEZ is a software package that can be used to customize the drive functionality or add PLC functionality by the interconnection and configuration of basic software function blocks. The drive performs program created by the user in 2 ms cycles. Parameter A1-07 can be used to enable or disable the DriveWorksEZ program inside the drive.

Note: 1. If DriveWorksEZ assigned functions to any multi-function output terminals, those functions stay set after disabling DriveWorksEZ. 2. Reinitialization using A1-03 does not reset A1-07 to the factory default value. 3. For more information on DriveWorksEZ, contact a Yaskawa representative or the Yaskawa sales department directly.

No. Parameter Name Setting Range Default

Setting 0: DWEZ Disabled Setting 1: DWEZ Enabled Setting 2: Digital Input

5.1 A: Initialization

Parameter Details

Table5.4 unlocking with example password1234 — PDF page 119

Source row Step Description Connector graphic Display/Result
1 1. Press to enter the parameter setup display. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) A1-01
2 2. Press to select the flashing digits as shown. [Visible key(s), in source order: RESET.] Right-arrow connector (not a key) A1-01; “01” flashes
3 3. Press to scroll to A1-04. [Visible key(s), in source order: UP.] Right-arrow connector (not a key) A1-04
4 4. Enter the password “1234”. Right-arrow connector (not a key) 1234
5 5. Press to save the new password. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) End
6 6. Drive returns to the parameter display. Right-arrow connector (not a key) A1-04
7 7. Press and scroll to A1-01. [Visible key(s), in source order: DOWN.] Right-arrow connector (not a key) A1-01
8 8. Press to display the value set to A1-01. If the first "0" blinks, parameter settings are unlocked. [Visible key(s), in source order: ENTER.] Right-arrow connector (not a key) 0002
9 9. Use and to change the value if desired. This is not typical. [Visible key(s), in source order: RESET, UP.] Blank source cell Blank source cell
10 10. Press to save the setting, or to return to the previous display without saving changes. [Visible key(s), in source order: ENTER or ESC.] Right-arrow connector (not a key) End
11 11. The display automatically returns to the parameter display. Right-arrow connector (not a key) A1-01

A1-07 DriveWorksEZ — PDF page 119

Source row No. Parameter Name Setting Range Default
1 A1-07 DriveWorksEZ Function Selection 0 to 2 0

Manual — User parameters and automatic history — page 120

Source reference: SIEP C71060618F, December 2016, physical PDF page 120. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u A2: User Parameters

n A2-01 to A2-32: User Parameters

The user can select 32 parameters and assign them to A2-01 through A2-32. This saves time later scrolling through the parameter menu. The list of User Parameters can also track the most recently edited settings and save those parameters to this list.

No. Parameter Name Setting Range Default

Saving User Parameters To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2). Next assign the parameter number to the User Parameters list by entering it into one of the A2-□□ parameters. By then setting A1-01 to “1”, the access level can be restricted so that users can only set and reference the specific parameters saved as User Parameters.

n A2-33: User Parameter Automatic Selection

A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for quick, easy access.

Setting 0: Do not save list of recently viewed parameters. To manually select the parameters listed in the User Parameter group, set A2-33 to “0”.

Setting 1: Save history of recently viewed parameters. By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A total of 16 parameters are saved in order with the most recently edited parameter set to A2-17. User parameters can be accessed using the Setup mode of the digital operator.

5.1 A: Initialization

A2-01–32 user parameters — PDF page 120

Source row No. Parameter Name Setting Range Default
1 A2-01 to A2-32 User Parameters 1 to 32 A1-02; b1-01 to o2-08 Depending on A1-06

A2-33 automatic selection — PDF page 120

Source row No. Parameter Name Setting Range Default
1 A2-33 User Parameter Automatic Selection 0 or 1 Depending on A1-06

Manual — Frequency-reference source and analog voltage input — page 121

Source reference: SIEP C71060618F, December 2016, physical PDF page 121. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure5.1: Drive; +V (+10.5 V,20 mA); 2 kΩ;0 to10V;A1 Main Frequency Reference(voltage input);A2 Auxiliary Frequency Reference(voltage/current input);AC Frequency Reference Common. Drawing grounds and wiring geometry remain original-only; no connection inferred beyond labels.

5.2 b: Application

Application parameters configure the source of the frequency reference, the Run command, DC Injection Braking, Speed Search, various timer functions, PID control, the Dwell function, Energy Savings and a variety of other application-related settings.

u b1: Mode of Operation

n b1-01: Frequency Reference Selection 1

Use parameter b1-01 to select the frequency reference source 1 for the REMOTE mode.

Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED on the digital operator will light and the STOP indicator will flash. 2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.

No. Parameter Name Setting Range Default

Setting 0: Digital Operator Using this setting, the frequency reference can be input by: • Switching between the multi-speed references in the d1-□□ parameters. • Entering the frequency reference on the operator keypad.

Setting 1: Terminals (Analog Input Terminals) Using this setting, an analog frequency reference can be entered from: • Terminal A1 using a 0 to 10 Vdc signal. • Terminal A2 using either a 0 to 10 Vdc or a 0/4 to 20 mA signal. Note: Terminal A2 supports voltage and current input. The input signal type must be set up by setting DIP switch S1 and adjusting parameter H3-09. Refer to H3-09: Terminal A2 Signal Level Selection on page 207. Entering only the main frequency reference: Using Control Circuit Terminal A1 (0 to 10 Vdc voltage input): Use a circuit such as the one shown in Figure 5.1 or an external 0 to 10 Vdc voltage source like a PLC analog output and set the input level selection for A1 in parameter H3-02 as desired. Refer to H3-02: Terminal A1 Function Selection on page 205.

Figure 5.1 Setting the Frequency Reference by Voltage Input

• Using Control Circuit Terminal A2 (0 to 10 Vdc voltage input) Use the same connection like explained for terminal A1 for terminal A2. Make sure that switch S1 is set to “V” and set the appropriate signal level for terminal A2 by entering 0 or 1 into parameter H3-09. The terminal A2 function must be set to frequency bias by entering 0 into parameter H3-10 (Refer to H3-10: Terminal A2 Function Selection on page 207). • Using Control Circuit Terminal A2 (0/4 to 20 mA current input)

Parameter Details

b1-01 frequency reference1 — PDF page 121

Source row No. Parameter Name Setting Range Default
1 b1-01 Frequency Reference Selection 1 0 to 4 1

Manual — Current input and main/auxiliary switching — page 122

Source reference: SIEP C71060618F, December 2016, physical PDF page 122. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure5.2: DIP switch S1, V / I;Drive;+V (+10.5 V,20mA power supply);A1 Frequency reference;0 or4 to20mA input to A2 Frequency reference bias;AC Analog common. Switch drawing/terminal wiring geometry remains original-only.

Figure5.3:Drive;+V (+10.5 V,20mA);two2kΩ potentiometer labels;A1 Main Frequency Reference(voltage input);A2 Aux Frequency Reference1(voltage input);AC Frequency Reference Common;S5 Multi-Function Digital Input;SC Digital Input Common. Physical wiring/ground/switch geometry retained in original; no inferred electrical connection.

Connect input A2 to an external current source such as the one shown in Figure 5.2. Make sure that switch S1 is set to “I” and set the appropriate signal level for terminal A2 by entering 2 (4 to 20 mA) or 3 (0 to 20 mA) into parameter H3-09. The terminal A2 function must be set to frequency bias by entering 0 into parameter H3-10 (Refer to H3-10: Terminal A2 Function Selection on page 207).

Figure 5.2 Setting the Frequency Reference by Current Input

Switching between Main/Auxiliary Frequency References The frequency reference input can be switched between terminal A1 (main) and terminal A2 (auxiliary). When using this function: • Make sure that b1-01 is set to “1” (Frequency reference from analog input). • Set the terminal A2 function to auxiliary frequency (H3-10 = 2). • Set one digital input to multi-speed 1 (H1-□□ = 3, default for S5).

The frequency reference value is read from • Terminal A1 when the digital input set for multi-speed 1 is open. • Terminal A2 when the digital input set for multi-speed 1 is closed. Figure 5.2 shows a wiring example for main/auxiliary reference switching using digital input S5.

Figure 5.3 Switching between Analog Reference 1 and 2

5.2 b: Application

Manual — Serial/option/pulse reference and run-command source — page 123

Source reference: SIEP C71060618F, December 2016, physical PDF page 123. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 2: MEMOBUS/Modbus Communications This setting requires that the frequency reference is entered via the RS-485/422 serial communications port (control terminals R+, R-, S+, S-, Protocol: MEMOBUS/Modbus). For instructions, Refer to MEMOBUS/Modbus Communications on page 431.

Setting 3: Option Card This setting requires that the frequency reference is entered via an option board plugged into connector CN5 on the drive control board. Consult the manual supplied with the option board for instructions on integrating the drive with the communication system.

Note: If the frequency reference source is set for an option PCB (b1-01 = 3) but an option board is not installed in CN5, an oPE05 Programming Error will be displayed on the digital operator and the RUN command will not be accepted.

Setting 4: Pulse Train Input If b1-01 is set to 4 the frequency reference must be provided by a pulse train signal at terminal RP that complies with the following specification.

Pulse Train Input Specifications

Verifying Pulse Train is Working Properly • Make sure that b1-01 is set to 4 and H6-01 is set to 0. • Set the pulse input scaling H6-02 to the pulse train frequency value that equals 100% frequency reference. • Enter a pulse train signal to terminal RP and check if the correct frequency reference is displayed. Try also with different pulse train input frequencies.

n b1-02: Run Command Selection 1

Parameter b1-02 determines the Run and Stop command source 1 in the REMOTE mode.

WARNING! Sudden Movement Hazard. Clear personnel, secure equipment, and check sequence and safety circuitry before starting the drive. Failure to comply could result in death or serious injury from moving equipment.

No. Parameter Name Setting Range Default

Setting 0: Digital Operator Using this setting, the RUN and STOP keys on the operator keypad will start and stop the motor. The LED in the LO/RE key will be on to indicate that the Run command is assigned to the operator. The example below shows how the drive can be operated if b1-02 is set to 0.

Step Display/Result

Setting 1: Control Circuit Terminal This setting requires that the Run and Stop commands are entered from the digital input terminals. The following sequences can be used:

5.2 b: Application

Parameter Details

Pulse train input specifications — PDF page 123

Source row Specification Value
1 Response Frequency 0.5 to 32 kHz
2 Duty Cycle 30 to 70%
3 High Level Voltage 3.5 to 13.2 V
4 Low Level Voltage 0.0 to 0.8 V
5 Input Impedance 3 kΩ

b1-02 run-command source1 — PDF page 123

Source row No. Parameter Name Setting Range Default
1 b1-02 Run Command Selection 1 0 to 3 1

Digital operator run/stop example — PDF page 123

Source row Step Description Connector graphic Display/Result
1 1. Turn on the power to the drive. The initial display appears. Right-arrow connector (not a key) F 0.00; DRV lit
2 2. Set the frequency reference to F6.00 (6 Hz). Right-arrow connector (not a key) F6.00
3 3. Press the key to start the motor. The RUN indicator LED will light and the motor will begin rotating at 6 Hz. [Visible key(s), in source order: RUN.] Right-arrow connector (not a key) F6.00; RUN light off → on
4 4. Press the key to stop the motor. The RUN light will flash until the motor comes to a complete stop. [Visible key(s), in source order: STOP.] Right-arrow connector (not a key) RUN light flashing → off

Manual — Run-command sequences and stopping modes — page 124

Source reference: SIEP C71060618F, December 2016, physical PDF page 124. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure5.4:Run Command ON→OFF;Maximum Output Frequency;Decelerates according to specified deceleration time;Zero Speed Level(b2-01);Decel Time(C1-02,etc.);DC Injection Braking;DC Injection Current(b2-02);DC Braking Time at Stop(b2-04). Exact waveform geometry and unprinted times remain original-only.

• 2-Wire sequence 1: Two inputs (FWD/Stop-REV/Stop). Initializing the drive by setting A1-01 = 2220, presets the terminals S1 and S2 to these functions. This is the default setting of the drive. Refer to Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence on page 191. • 2-Wire sequence 2: Two inputs (Start/Stop-FWD/REV). Refer to Setting 42/43: Run and Direction Command for 2-Wire Sequence 2 on page 191. • 3-Wire sequence: Inputs S1, S2, S5 (Start-Stop-FWD/REV). Initialize the drive by setting A1-01 = 3330 presets the terminals S1, S2 and S5 to these functions. Refer to Setting 0: 3-Wire Sequence on page 185.

Setting 2: MEMOBUS/Modbus Communications To issue a Run command via serial communications, set b1-02 to “2” and connect the RS-485/422 serial communication cable to R+, R-, S+, and S- on the removable terminal block. Refer to MEMOBUS/Modbus Communications on page 431.

Setting 3: Option Card To issue the Run command via the communication option board, set b1-02 to “3” and plug a communication option board into the 2CN port on the control PCB. Refer to the manual supplied with the option board for instructions on integrating the drive into the communication system.

Note: If b1-01 is set to 3, but an option board is not installed in 2CN, an oPE05 operator programming error will be displayed on the digital operator and the drive will not run.

n b1-03: Stopping Method Selection

Select how the drive stops the motor when a Stop command is entered or when the Run command is removed.

No. Parameter Name Setting Range Default

Setting 0: Ramp to Stop When a Stop command is issued or the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the active deceleration time. The default deceleration time is set to parameter C1-02. DC Injection braking (for IM control) or Short Circuit Braking (PM Open Loop Vector) can be applied at the end of the ramp in order to completely stop high inertia loads. Refer to b2: DC Injection Braking on page 128 for details.

Figure 5.4 Ramp to Stop

Setting 1: Coast to Stop When a Stop command is issued or the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to stop where the stopping time is determined by the inertia and the friction in the driven system.

5.2 b: Application

b1-03 stopping method — PDF page 124

Source row No. Parameter Name Setting Range Default
1 b1-03 Stopping Method Selection 0 to 3 0

Manual — Coast and DC-injection stopping; source formula — page 125

Source reference: SIEP C71060618F, December 2016, physical PDF page 125. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure5.5:Run Command ON→OFF;Output Frequency;Drive output frequency is shut off;Motor rpm. Curve geometry remains original-only; no unprinted time or ramp inferred.

Figure5.6:Run Command ON→OFF;Output Frequency;Minimum Baseblock Time(L2-03);DC Injection Braking;Motor Speed;DC Injection Braking Time at Stop(b2-04)*;DC Braking Current(b2-02). Actual waveform geometry remains original-only. Source formula below qualifies time; this function unavailable with PM Open Loop Vector.

DC Injection brake time = (b2-04 · 10 · Output frequency) / Max. output frequency(E1-04). Source numerator and denominator preserved from actual fraction; no numerical result or extra unit inferred.

Figure 5.5 Coast to Stop

Note: After a stop is initiated, any subsequent Run command that is entered will be ignored until the Minimum Baseblock Time (L2-03) has expired. Do not attempt to start the motor again until it has come to a complete stop. To start the motor before it has stopped completely, use DC Injection at start (Refer to b2-03: DC Injection Braking Time at Start on page 129) or Speed Search (Refer to b3: Speed Search on page 130).

Setting 2: DC Injection Braking to Stop When the Run command is removed, the drive will baseblock (turn off its output) for the minimum baseblock time (L2-03). Once the minimum baseblock time has expired, the drive will brake the motor by injecting DC current into the motor windings. The stopping time will be reduced as compared to coast to stop. The level of DC Injection current is set by parameter b2-02 (default = 50%).

Note: This function is not available when using PM Open Loop Vector.

Figure 5.6 DC Injection Braking to Stop

The time for DC Injection Braking is determined by the value set to b2-04 and by the output frequency at the time the Run command is removed. It can be calculated by:

5.2 b: Application

Parameter Details

Manual — Stopping time graphs and reverse operation — page 126

Source reference: SIEP C71060618F, December 2016, physical PDF page 126. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Axes: DC Injection braking time; Output frequency when Stop command was entered. Source labels b2-04, b2-04 × 10, 10%, 100% (Maximum output frequency). The drawn line is flat at b2-04 up to 10%, then rises to b2-04 × 10 at 100%; retain this graph qualification alongside the PDF125 formula without deriving a new formula. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Run Command ON → OFF → ON → OFF → ON; Output Frequency; Drive output voltage interrupted; Operation Wait Time t. A run command inside the wait interval is not accepted; source prose requires cycling after it expires. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Operation wait time t; Selected decel time; Minimum Baseblock Time (L2-03); Min. output frequency; Output frequency when Stop command is entered; 100% (Max. output frequency). Source line rises from the minimum baseblock level to the selected decel time. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Note: If an overcurrent (oC) fault occurs during DC Injection Braking to stop, lengthen the minimum baseblock time (L2-03) until the fault no longer occurs.

Setting 3: Coast to Stop with Timer When the Run command is removed, the drive will turn off its output and the motor will coast to stop. If a Run command is input before the operation wait time t expires, the drive will not rotate the motor and the Run command will need to be cycled before operation can occur.

The operation wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.

Figure

n b1-04: Reverse Operation Selection

For some applications, reverse motor rotation is not appropriate and may even cause problems (e.g., air handling units, pumps, etc.). Setting parameter b1-04 to 1 instructs the drive to ignore any Reverse run commands.

No. Parameter Name Setting Range Default

Setting 0: Reverse Operation Enabled Possible to operate the motor in both forward and reverse directions.

5.2 b: Application

b1-04 / Reverse Operation Selection — PDF page 126

Source row No. Parameter Name Setting Range Default
1 b1-04 Reverse Operation Selection 0 or 1 0

Manual — Reverse, control-source switching and programming-mode run — page 127

Source reference: SIEP C71060618F, December 2016, physical PDF page 127. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 1: Reverse Operation Disabled Drive disregards a Reverse run command or a negative frequency reference.

n b1-07: LOCAL/REMOTE Run Selection

The drive has the following three separate control sources that can be switched using digital inputs or the LO/RE key on the digital operator (for details Refer to Setting 1: LOCAL/REMOTE Selection on page 185, Refer to Setting 2: External Reference 1/2 Selection on page 186 and Refer to o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection on page 248): • LOCAL - The digital operator is used to set the reference and the Run command. • REMOTE -Reference 1: The settings of b1-01 and b1-02 determine where the frequency reference and Run command are input from. • REMOTE - Reference 2: The settings of b1-15 and b1-16 determine where the frequency reference and Run command are input from. When switching from LOCAL to REMOTE, or between Reference 1 and Reference 2, the Run command may already be present at the location the source was switched to. Parameter b1-07 can be used to determine how the Run command is treated in this case.

No. Parameter Name Setting Range Default

Setting 0: Run Command Must Be Cycled If the Run command is issued differently in the old and new control source (e.g. old - terminals, new - serial communications) and it is active at the new source when switching takes place, the drive will either not start or it will stop if it was running before. The Run command has to be cycled to start from the new control source.

Setting 1: Continue Running If the Run command is active at the new control source, the drive starts or continues running. There is no need to cycle the Run command.

WARNING! The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel away from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.

n b1-08: Run Command Selection while in Programming Mode

As a safety precaution, the drive will not normally respond to a Run input when the digital operator is being used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning). If required by the application b1-08 can be used to changed this functionality.

Setting 0: Disabled A Run command is not accepted while the digital operator is in Programming Mode.

Setting 1: Enabled A Run command is accepted in any digital operator mode.

Setting 2: Prohibit Programming During Run It is not possible to enter the Programming Mode as long as the drive output is active.

n b1-14: Phase Order Selection

Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.

Setting 0: Standard Phase Order

Setting 1: Switched Phase Order

5.2 b: Application

Parameter Details

b1-07 / LOCAL/REMOTE Run Selection — PDF page 127

Source row No. Parameter Name Setting Range Default
1 b1-07 LOCAL/REMOTE Run Selection 0 or 1 0

b1-08 / Run Command Selection while in Programming Mode — PDF page 127

Source row No. Parameter Name Setting Range Default
1 b1-08 Run Command Selection while in Programming Mode 0 to 2 0

b1-14 / Phase Order Selection — PDF page 127

Source row No. Parameter Name Setting Range Default
1 b1-14 Phase Order Selection 0 or 1 0

Manual — Second references, power-up and braking threshold — page 128

Source reference: SIEP C71060618F, December 2016, physical PDF page 128. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n b1-15: Frequency Reference Selection 2

Refer to b1-01: Frequency Reference Selection 1 on page 121 for details. The value set to b1-15 is used as Frequency Reference 2 when one of the multi-function input terminals set for Frequency Reference Switching (H1-□□ = 2) closes. Refer to Setting 2: External Reference 1/2 Selection on page 186 for instructions on how this function works.

No. Parameter Name Setting Range Default

n b1-16: Run Command Selection 2

Refer to b1-02: Run Command Selection 1 on page 123 for details. The value set to b1-16 is used as Run Command Source 2 when one of the multi-function input terminals set for Frequency Reference Switching (H1-□□ = 2) closes. Refer to Setting 2: External Reference 1/2 Selection on page 186 for instructions on how this function works.

n b1-17: Run Command at Power Up

This parameter is used to determine whether an external Run command that is active during power up of the drive will start the drive or not.

Setting 0: Run Command at Power Up is not Issued The Run command has to be cycled to start the drive.

Note: For safety reasons, the drive is initially set up not to accept a Run command at power up (b1-17 = "0"). If a Run command is issued at power up, the RUN indicator LED will flash quickly. Change parameter b1-17 to 1 if a Run command active at power up shall be accepted by the drive.

Setting 1: Run Command and Power Up is Issued An external Run command active during power up is issued and the drive starts to operate the motor as soon as it gets ready for operation (i.e. once the internal start up process is complete).

WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to powering up the drive. Failure to comply may cause serious injury.

u b2: DC Injection Braking

These parameters determine how the DC Injection Braking/Short Circuit Braking feature operates. Parameters involving the starting frequency, current level, braking time are located here.

n b2-01: DC Injection Braking Start Frequency

Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0). Sets the starting frequency for: • DC Injection Braking at stop in V/f and OLV control. • Short Circuit Braking at stop in PM OLV control.

No. Name Setting Range Default

When the output frequency while ramping to stop drops below b2-01, the drive begins DC Injection/Short Circuit Braking in order to completely stop the motor at the end of deceleration. If b2-01 < E1-09 (Minimum Frequency), then DC Injection/ Short Circuit Braking begins at the frequency set to E1-09.

<1> The upper limit for the setting range is determined by E1-04.

5.2 b: Application

b1-15 / Frequency Reference Selection 2 — PDF page 128

Source row No. Parameter Name Setting Range Default
1 b1-15 Frequency Reference Selection 2 0 to 4 0

b1-16 / Run Command Selection 2 — PDF page 128

Source row No. Parameter Name Setting Range Default
1 b1-16 Run Command Selection 2 0 to 3 0

b1-17 / Run Command at Power Up — PDF page 128

Source row No. Parameter Name Setting Range Default
1 b1-17 Run Command at Power Up 0 or 1 0

b2-01 / DC Injection Braking Start Frequency — PDF page 128

Source row No. Name Setting Range Default
1 b2-01 DC Injection Braking Start Frequency 0.0 to 10.0 Hz 0.5 Hz

E1-09 / Minimum Output Frequency — PDF page 128

Source row No. Name Setting Range Default
1 E1-09 Minimum Output Frequency <1> 0.0 to 400.0 Hz Determined by A1-02 and E1-03 and on E5-01 in OLV/PM.

Manual — DC injection, flux and PM short-circuit braking — page 129

Source reference: SIEP C71060618F, December 2016, physical PDF page 129. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency; b2-01 DC Injection Braking start frequency; braking time; b2-04. No unstated braking time or braking region value inferred. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

n b2-02: DC Injection Braking Current

Sets the DC Injection Braking current as a percentage of the drive rated current. If set to larger than 50%, the carrier frequency is automatically reduced to 1 kHz.

No. Name Setting Range Default

The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft. Increasing the current level will increase the amount of heat generated by the motor windings. This parameter should only be increased to the level necessary to hold the motor shaft.

n b2-03: DC Injection Braking Time at Start

Sets the time of DC Injection Braking at start. It can be used to stop a coasting motor before restarting it or to apply a braking torque at start. Disabled when set to 0.00 s.

Note: Before starting an uncontrolled rotating motor (e.g. a fan motor driven by windmill effect), DC Injection or Speed Search should be used to either stop the motor or detect its speed before starting it. Otherwise motor stalling and other faults can occur.

n b2-04: DC Injection Braking Time at Stop

This parameter works in combination with b2-01, and sets the DC Injection Braking time at stop. Used to completely stop a motor with high inertia load after ramp down. Increase the setting if the motor tends to coast by inertia after a stop.

n b2-08: Magnetic Flux Compensation Value

Sets the magnetic flux compensation as a percentage of the no-load current value (E2-03) and can be used to increase the motor flux when the motor is started up.

This parameter allows the magnetizing motor flux to be boosted when starting the motor and thereby facilitate a quick ramp- up of the torque reference and magnetizing current reference in order to reduce motor slip during start. This flux level will be applied below the minimum output frequency set to E1-09 until the DC Injection time at start (b2-03) expires. It may be used to compensate for reduced starting torque due to motor circuit inefficiencies.

n b2-12: Short Circuit Brake Time at Start

Short-Circuit braking can be used in Open Loop Vector for PM motors. By shorting all three motor phases it produces a braking torque in the motor and can be used to stop a coasting motor before starting it. Parameter b2-12 sets the time for Short-Circuit Brake operation at start. Disabled when set to 0.00 s.

n b2-13: Short Circuit Brake Time at Stop

The Short-Circuit braking described for parameter b2-12 can also be applied at the end of deceleration in order to completely stop high inertia loads. Short circuit braking is initiated when the output frequency falls below the higher of the values b2-01 and E1-09.

5.2 b: Application

Parameter Details

b2-02 / DC Injection Braking Current — PDF page 129

Source row No. Name Setting Range Default
1 b2-02 DC Injection Braking Current 0 to 75% 50%

b2-03 / DC Injection Braking Time at Start — PDF page 129

Source row No. Name Setting Range Default
1 b2-03 DC Injection Braking Time at Start 0.00 to 10.00 s 0.50 s

b2-04 / DC Injection Braking Time at Stop — PDF page 129

Source row No. Name Setting Range Default
1 b2-04 DC Injection Braking Time at Stop 0.00 to 10.00 s 0.50 s

b2-08 / Magnetic Flux Compensation Value — PDF page 129

Source row No. Name Setting Range Default
1 b2-08 Magnetic Flux Compensation Value 0 to 1000% 0%

b2-12 / Short Circuit Brake Time at Start — PDF page 129

Source row No. Name Setting Range Default
1 b2-12 Short Circuit Brake Time at Start 0.00 to 25.50 s 0.00 s

Manual — Short-circuit stop and Speed Estimation methods — page 130

Source reference: SIEP C71060618F, December 2016, physical PDF page 130. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

AC power supply OFF → ON; Output frequency starts at the detected speed, then selected frequency reference; Output current; Several milliseconds; Min. Baseblock Time (L2-03); b3-05 <1>. Footnote below qualifies waiting after power restoration and longer interruptions. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Parameter b2-13 sets the time for Short-Circuit brake operation at stop. Disabled when set to 0.00 s.

No. Name Setting Range Default

u b3: Speed Search

The Speed Search function allows the drive to detect the speed of a rotating motor shaft that is driven by external forces (e.g. fan rotating by windmill effect or motor driven by load inertia). The motor operation can be directly started from the speed detected without needing to stop the machine before. Example: When a momentary loss of power occurs, the drive output shuts off. This results in a coasting motor. When power returns, the drive can find the speed of the coasting motor and restart it directly. The drive offers two types of Speed Search, Speed Estimation and Current Detection. Both methods are explained below followed by a description of all relevant parameters.

n Speed Estimation Type Speed Search (b3-24 = 1)

This method can be used for a single motor connected to a drive. It should not be utilized if the motor is one or more frame sizes smaller than the drive, at motor speeds above 130 Hz, or when using a single drive to operate more than one motor. The Speed Estimation type distinguishes two kinds of operation, Back EMF voltage estimation and DC current injection.

Back EMF Voltage Estimation This method is used by Speed Search after short Baseblock (e.g. a power loss where the drives CPU kept running and the Run command was kept active). Here the drive estimates the motor speed by analyzing the back EMF voltage. It outputs the estimated frequency and increases the voltage using the time constant set in parameter L2-04. After that the motor is accelerated or decelerated to the frequency reference starting from the detected speed.

<1> Once AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than the Minimum Baseblock Time L2-03, the drive will wait for b3-05 after the power has returned before starting Speed Search.

Current Injection This method is used when there is no detectable back EMF, e.g. after longer power losses, when Speed Search is applied with the Run command (b3-01 = 1) or if an External Search command is used. It injects the DC current set in b3-06 to the motor and detects the speed by measuring the current feedback. The drive outputs the detected frequency and increases the voltage using the time constant set in parameter L2-04. If the resulting current is higher than the level in b3-02 the output frequency is reduced. When the current becomes lower than b3-02 the motor speed is assumed to be found and the drive starts to accelerate or decelerate to the frequency reference.

5.2 b: Application

b2-13 / Short Circuit Brake Time at Stop — PDF page 130

Source row No. Name Setting Range Default
1 b2-13 Short Circuit Brake Time at Stop 0.00 to 25.50 s 0.50 s

Manual — Speed Search start and Current Detection scope — page 131

Source reference: SIEP C71060618F, December 2016, physical PDF page 131. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Run command OFF → ON; Output frequency starts at the detected speed; Decelerates at the Speed Search decel time set to b3-03; Waits for L2-04 × 2 time; Frequency reference set to the drive; Output current b3-02; 1.0 s; Min. Baseblock Time (L2-03) <1>. PDF131 footnote makes b3-05 the lower limit. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

<1> The wait time for Speed Search (b3-05) determines the lower limit.

Note: If the Run command is quickly switched off and then back on again when the drive is set to “Coast to stop” as the stopping method, Speed Search will operate as shown in Figure 5.11. Notes on Using Speed Estimation Type Speed Search • Auto-Tuning needs to be first performed if you plan to use Speed Estimation. Perform Auto-Tuning again if the there is a change in the cable length between the drive and motor. • Use Current Detection to search for speeds beyond 130 Hz or if the application is running multiple motors from the same drive, or if the motor is considerably smaller than the capacity of the drive. • Speed Estimation may have trouble finding the actual speed if the motor cable very long. Current Detection should be used in such situations. • Use Current Detection instead of Speed Estimation when operating motors smaller than 1.5 kW. Speed Estimation can end up stopping smaller motors as it might not be able to detect the speed or rotation direction of such small motors. • Use Short circuit Braking instead of Speed Estimation when using Open Loop Vector Control for PM motors along with a fairly long motor cable. • Use Short circuit Braking instead of Speed Estimation if attempting to find the speed of a motor coasting faster than 120 Hz in Open Loop Vector Control for PM motors.

n Current Detection Type Speed Search (b3-24 = 0)

Current Detection Speed Search can be applied to any motor. Be aware that sudden acceleration may occur when using Current Detection with relatively light loads. This method detects the motor speed by reducing the output frequency and measuring the current. The frequency reduction starts from the maximum output frequency or from the set frequency reference. As long as the output frequency is higher than the rotor speed, the slip will cause a high current. The closer the output frequency comes to the rotor speed, the lower the current draw will be. When the output current drops below the level as set in b3-02, the output frequency stops decreasing and normal operation resumes. The following time chart illustrates how Current Detection Speed Search operates after a momentary power loss:

5.2 b: Application

Parameter Details

Manual — Current Detection timing and activation methods — page 132

Source reference: SIEP C71060618F, December 2016, physical PDF page 132. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

AC power supply OFF → ON; Output frequency before momentary power loss; Decel time set to b3-03; Waits for L2-04 × 2 time; Selected frequency reference; Output current; Speed Search operation current set to b3-02; Min. Baseblock Time (L2-03); b3-05. Source waiting-time qualifications and PM exclusion below remain essential. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Run command OFF → ON; Output frequency: Max. output frequency or the specified frequency reference; Decel time set to b3-03; Waits for L2-04 × 2 time; Selected frequency reference; Output current b3-02; Minimum Baseblock Time (L2-03). Actual source notes qualify wait time and motor modes. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Note: After power is restored, the drive waits until the time set to b3-05 has passed before performing Speed Search. Thereby the Speed Search may start not at the end of L2-03 but even later. When Speed Search is applied using an external Search command or automatically with the Run command, the drive waits for the minimum baseblock time L2-03 before Speed Search is started. If L2-03 is smaller than the time set in parameter b3-05, b3-05 is used as the wait time.

Note: When the Run command is set the drive waits until the Speed Search Wait Time (b3-05) before Speed Search is performed, even if the Minimum Baseblock Time is set to smaller values than b3-05. Notes on Using Current Detection Type Speed Search • Increase the voltage recovery ramp time set to L2-04 if a Uv1 fault occurs when performing Current Detection Speed Search. • Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection Speed Search. • Current Detection Speed Search is not available when using Open Loop Vector Control for PM motors. • Increase the minimum baseblock time set to L2-03 if an overcurrent fault occurs when performing Speed Search after power is restored following a momentary power loss.

n Activation of Speed Search

Speed Search can be activated as described below. Independent of the activation method the Speed Search type must be selected in parameter b3-24. 1. Automatically at every Run command (Refer to b3-01: Speed Search Selection at Start on page 133). With this setting external Speed Search commands are disregarded.

  1. By digital inputs: The following input functions for H1-□□ can be used.

5.2 b: Application

Manual — Speed Search activation and b3-01 to b3-05 — page 133

Source reference: SIEP C71060618F, December 2016, physical PDF page 133. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table 5.5 Speed Search Activation by Digital Inputs

Setting Description b3-24 = 0 b3-24 = 1

To activate Speed Search by a digital input the input must always be set together with the Run command. 3. After automatic fault restart Set the number of maximum fault restarts in parameter L5-01 higher than 0.

  1. After momentary power loss The following parameter settings are necessary: • Enable Power Loss Ride-Thru selection by setting L2-01 to 1 (enabled) or 2 (enabled during CPU operation). Refer to L2-01: Momentary Power Loss Operation Selection on page 218. • Set the number of maximum fault restarts in parameter L5-01 higher than 0.

  2. After baseblock is released The drive will resume the operation starting with Speed Search if the Run command is present and the output frequency is above the minimum frequency when the Baseblock command (H1-□□ = 8 or 9, N.O. and N.C., respectively) is released.

n b3-01: Speed Search Selection at Start

Selects if Speed Search is automatically performed when a Run command is issued.

No. Parameter Name Setting Range Default

Setting 0: Disabled Speed Search is not automatically performed. It can be activated using a digital input.

Setting 1: Enabled Speed Search is performed with every Run command.

n b3-02: Speed Search Deactivation Current

Sets Speed Search operating current as a percentage of the drive rated current. If the current falls below this level while performing Current Detection Speed Search then Speed Search will be finished and normal operation will resume. Normally there is no need to change this setting. If the drive won’t run after a restart, lower this value.

No. Name Setting Range Default

Note: When parameter A1-02 = 0 (V/f Control) the factory default setting is 120. When parameter A1-02 = 2 (Open Loop Vector) the factory default setting is 100.

n b3-03: Speed Search Deceleration Time

Parameter b3-03 sets the output frequency reduction ramp used by Current Detection Speed Search (b3-24 = 0) and by the Current Injection Method of Speed Estimation (b3-24 = 1). The time entered into b3-03 will be the time to decelerate from maximum frequency (E1-04) to minimum frequency (E1-09).

n b3-05: Speed Search Delay Time

In cases where an output contactor is used between the drive and the motor, the contactor must be closed before Speed Search can be performed. For Speed Search after a momentary power loss, parameter b3-05 can be used to delay the Speed Search start providing enough time to operate the contactor. When Speed Search at start is used, b3-05 will serve as the lower limit of the minimum baseblock time (L2-03).

5.2 b: Application

Parameter Details

Table5.5 Speed Search Activation by Digital Inputs — PDF page 133

Source row Setting Description b3-24 = 0 b3-24 = 1
1 61 External Search Command 1 Closed: Activate Current Detection Speed Search from the maximum output frequency (E1-04). Activate Speed Estimation Speed Search
2 62 External Search Command 2 Closed: Activate Current Detection Speed Search from the frequency reference if b3-01 is set to 0. –

b3-01 / Speed Search Selection at Start — PDF page 133

Source row No. Parameter Name Setting Range Default
1 b3-01 Speed Search Selection at Start 0 or 1 0

b3-02 / Speed Search Deactivation Current — PDF page 133

Source row No. Name Setting Range Default
1 b3-02 Speed Search Deactivation Current 0 to 200% Determined by A1-02

b3-03 / Speed Search Deceleration Time — PDF page 133

Source row No. Name Setting Range Default
1 b3-03 Speed Search Deceleration Time 0.1 to 10.0 s 2.0 s

Manual — Speed Search gains, direction and restart thresholds — page 134

Source reference: SIEP C71060618F, December 2016, physical PDF page 134. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

n b3-06: Output Current 1 During Speed Search

Sets the current injected to the motor at the beginning of Estimation Type Speed Search as a factor related to motor rated current set in E2-01 and E4-01. If the motor speed is relatively slow when the drive starts to perform Speed Search after a long period of baseblock, it may be helpful to increase the setting value. The output current during Speed Search is automatically limited by the drive rated current. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).

Note: If Speed Estimation is not working correctly even after adjusting b3-06, try using Current Detection Speed Search instead.

n b3-08: Current Control Gain during Speed Search (Speed Estimation Type)

Note: Parameter available in drive software versions PRG: 1022 and later. Sets the proportional gain for the current controller during Speed Search. There is normally no need to change this parameter from the default value.

n b3-10: Speed Search Detection Compensation Gain

This parameter sets the gain for the detected motor speed of the Speed Estimation Speed Search. The drive will start the motor at the estimated speed multiplied by b3-10. The setting should be increased if an overvoltage fault occurs when the drive restarts the motor. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).

Note: Increase this value if overvoltage occurs when performing Speed Search at start after a relatively long period of baseblock.

n b3-14: Bi-Directional Speed Search Selection

Sets how the drive determines the motor rotation direction when performing Speed Estimation Speed Search. The setting has no influence on Current Detection Speed Search (b3-24 = 0).

No. Parameter Name Setting Range Default

Setting 0: Disabled The drive uses the frequency reference to determine the direction of motor rotation in order to restart the motor.

Setting 1: Enabled The drive detects the motor rotation direction in order to restart the motor.

n b3-17: Speed Search Restart Current Level

If there is a fairly large difference between the estimated frequency and the actual motor speed when performing Speed Estimation, a large current can flow. This parameter sets the current level at which Speed Estimation is restarted, thus avoiding overcurrent and overvoltage problems. The parameter is set as a percentage of the drive rated current. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).

n b3-18: Speed Search Restart Detection Time

Sets the time the current must be above the level set in b3-17 before Speed Search is restarted. This function has no influence when Current Detection Speed Search is used (b3-24 = 0)

5.2 b: Application

b3-05 / Speed Search Delay Time — PDF page 134

Source row No. Name Setting Range Default
1 b3-05 Speed Search Delay Time 0.0 to 100.0 s 0.2 s

b3-06 / Output Current 1 during Speed Search — PDF page 134

Source row No. Name Setting Range Default
1 b3-06 Output Current 1 during Speed Search 0.0 to 2.0 Determined by o2-04

b3-08 / Current Control Gain during Speed Search (Speed Estimation Type) — PDF page 134

Source row No. Name Setting Range Default
1 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) 0.00 to 6.00 A1-02 = 0 or 2: 0.50 A1-02 = 5: 0.30

b3-10 / Speed Search Detection Compensation Gain — PDF page 134

Source row No. Name Setting Range Default
1 b3-10 Speed Search Detection Compensation Gain 1.00 to 1.20 1.10

b3-14 / Bi-Directional Speed Search Selection — PDF page 134

Source row No. Parameter Name Setting Range Default
1 b3-14 Bi-Directional Speed Search Selection 0 or 1 0

b3-17 / Speed Search Restart Current Level — PDF page 134

Source row No. Name Setting Range Default
1 b3-17 Speed Search Restart Current Level 0 to 200% 150%

Manual — Search restart limits, method and timer function — page 135

Source reference: SIEP C71060618F, December 2016, physical PDF page 135. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

n b3-19: Number of Speed Search Restarts

Sets the number of times the drive should attempt to find the speed and restart the motor using Speed Estimation Speed Search. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).

n b3-24: Speed Search Method Selection

Sets the Speed Search method used.

Note: For explanations of the Speed Search methods, Refer to Current Detection Type Speed Search (b3-24 = 0) on page 131 and Refer to Speed Estimation Type Speed Search (b3-24 = 1) on page 130.

No. Parameter Name Setting Range Default

Setting 0: Current Detection Speed Search

Setting 1: Speed Estimation Speed Search

n b3-25: Speed Search Wait Time

Sets the wait time between Speed Search restarts.

n b3-29: Speed Search Induced Voltage Level

Performs Speed Search when the motor induced voltage exceeds the set level. There is normally no need to change this parameter from the default value. Lower this value in small increments if changes are necessary. However, setting this value too low will prevent the drive from performing Speed Search.

u b4: Delay Timers

The timer function is independent of the drive operation and can be used to delay the switching of a digital output triggered by a digital input signal. An On-delay and Off-delay can be separately set. The delay timer can help to get rid of chattering switch noise from sensors. To enable the timer function, a multi-function input must be set to “Timer input” (H1-□□ = 18) and a multi-function output must be set to “Timer output” (H2-□□ = 12). Only one timer can be used.

n b4-01/b4-02: Timer Function On/Off-Delay Time

b4-01 sets the On-delay time for switching the timer output. b4-02 sets the Off-delay time for switching the timer output.

n Timer Function Operation

When the timer function input closes for longer than the value set in b4-01, the timer output switches on. When the timer function input is open for longer than the value set in b4-02, the timer output function switches off. The following diagram demonstrates the timer function operation.

5.2 b: Application

Parameter Details

b3-18 / Speed Search Restart Detection Time — PDF page 135

Source row No. Name Setting Range Default
1 b3-18 Speed Search Restart Detection Time 0.00 to 1.00 s 0.10 s

b3-19 / Number of Speed Search Restarts — PDF page 135

Source row No. Name Setting Range Default
1 b3-19 Number of Speed Search Restarts 0 to 10 3

b3-24 / Speed Search Method Selection — PDF page 135

Source row No. Parameter Name Setting Range Default
1 b3-24 Speed Search Method Selection 0 or 1 0

b3-25 / Speed Search Wait Time — PDF page 135

Source row No. Name Setting Range Default
1 b3-25 Speed Search Wait Time 0.0 to 30.0 s 0.5 s

b3-29 / Speed Search Induced Voltage Level — PDF page 135

Source row No. Name Setting Range Default
1 b3-29 Speed Search Induced Voltage Level 0 to 10% 10%

b4-01 / b4-02 — Timer Function On-Delay Time — PDF page 135

Source row No. Name Setting Range Default
1 b4-01 Timer Function On-Delay Time 0.0 to 300.0 s 0.0 s
2 b4-02 Timer Function Off-Delay Time 0.0 to 300.0 s 0.0 s

Manual — Timer diagram and PID operation and applications — page 136

Source reference: SIEP C71060618F, December 2016, physical PDF page 136. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Multi-function Contact Input: Timer Function; Multi-function Contact Output: Timer Function. Each has On (Closed), Off (Open); waveform ON segments; b4-01 on-delay and b4-02 off-delay. Pulse widths and unprinted durations are not inferred. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

PID input step; Time. PID Output consists of illustrated P control, I control and D control contributions; PID output; Time. This is a conceptual diagram with no numerical values. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

u b5: PID Control

The drive has a built in PID (Proportional + Integral + Derivative) controller that can be used for closed loop control of system variables such as pressure, temperature etc. The difference between the target and the feedback value (deviation) is fed into the PID controller. The PID controller adjusts the drive output frequency in order to minimize the deviation, providing an accurate control of the system variables.

n P Control

The output of P control is the product of the deviation and the P gain so that it follows the deviation directly and linearly. With P control only an offset between the target and feedback remains.

n I Control

The output of I control is the integral of the deviation. It minimizes the offset between target and feedback value that typically remains when pure P control is used. The integral time (I-time) constant determines how fast the offset is eliminated.

n D Control

D control predicts the deviation signal by multiplying its derivative (slope of the deviation) with a time constant and adding this to the PID input. This way the D portion of a PID controller provides a braking action to the controller response and can reduce the tendency of oscillations and overshoot. Be aware that D control tends to amplify noise on the deviation signal, which can result in control instability. D control should therefore only be used when necessary.

n PID Operation

To better demonstrate how PID works, the diagram below shows how the PID output changes when the PID input (deviation) jumps from 0 to a constant level.

n Using PID Control

Applications for PID control are listed in the table below.

Application Description Sensors Used

5.2 b: Application

PID application examples — PDF page 136

Source row Application Description Sensors Used
1 Speed Control Machinery speed is fed back and adjusted to meet the target value. Synchronous control is performed using speed data from other machinery as the target value Tachometer
2 Pressure Maintains constant pressure using pressure feedback. Pressure sensor
3 Fluid Control Keeps flow at a constant level by feeding back flow data. Flow rate sensor
4 Temperature Control Maintains a constant temperature by controlling a fan with a thermostat. Thermocoupler, Thermistor

Manual — PID setpoint, feedback and differential source assignments — page 137

Source reference: SIEP C71060618F, December 2016, physical PDF page 137. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n PID Setpoint Input Methods

When the PID control parameter b5-01 is set to 1 or 2, the frequency reference in b1-01 (or b1-15) becomes the PID setpoint. If b5-01 is set to 3 or 4, then the PID setpoint can be input from one of the sources in the following table.

Table 5.6 PID Setpoint Sources PID Setpoint Source Settings

Note: A duplicate allocation of the PID setpoint input will result in an OPE alarm.

n PID Feedback Input Methods

Either one feedback signal can be input for normal PID control or two feedback signals can be input for controlling a differential process value.

Normal PID Feedback The PID feedback can be input from one of the sources listed below.

Table 5.7 PID Feedback Sources PID Feedback Source Settings

Note: A duplicate allocation of the PID feedback input will result in an OPE alarm.

Differential Feedback The second PID feedback signal for differential feedback can come from the sources listed below. The differential feedback function is automatically enabled when a differential feedback input is assigned.

Table 5.8 PID Differential Feedback Sources PID Differential Feedback Source Settings

Note: A duplicate allocation of the PID differential feedback input will result in an OPE alarm.

5.2 b: Application

Parameter Details

Table5.6 PID Setpoint Sources — PDF page 137

Source row PID Setpoint Source Settings
1 Analog Input A1 Set H3-02 = C
2 Analog Input A2 Set H3-10 = C
3 MEMOBUS/Modbus Register 0006H Set Bit 1 in register 000FH to 1 and input the setpoint to register 0006H
4 Pulse Input RP Set H6-01 = 2
5 Parameter b5-19 Set parameter b5-18 = 1 and input the PID setpoint to b5-19

Table5.7 PID Feedback Sources — PDF page 137

Source row PID Feedback Source Settings
1 Analog Input A1 Set H3-02 = B
2 Analog Input A2 Set H3-10 = B
3 Pulse Input RP Set H6-01 = 1

Table5.8 PID Differential Feedback Sources — PDF page 137

Source row PID Differential Feedback Source Settings
1 Analog Input A1 Set H3-02 = 16
2 Analog Input A2 Set H3-10 = 16

Manual — PID block diagram labels and original topology boundary — page 138

Source reference: SIEP C71060618F, December 2016, physical PDF page 138. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Frequency Reference 1 b1-01: 0 Frequency Reference 1 to 16 d1-01 to d1-16; 1 Analog Input A1/A2; 2 Serial Comm; 3 Option Card; 4 Pulse Input. b5-01 branches labeled 0, 1/2 and 3/4. PID Soft Starter b5-17; PID SFS Cancel DI H1-□□=34 On/Off. PID Target: MEMOBUS Reg. 0006h with Reg. 0Fh, bit 1 (0/1); b5-19 selected by b5-18=1/not 1; Pulse Input H6-01=2/not 2; Analog Input A1/A2 H3-02/10=C/not C; zero branch. PID Set Point U5-04. PID Feedback: Pulse Input H6-01=1/not 1; Analog Input A1/A2 H3-02/10=B/not B; zero branch; PID Feedback U5-01. Differential feedback Analog Input A1/A2 H3-02/10=16/not 16, zero branch; PID Differential Feedback U5-05; Adjusted PID Feedback U5-06. Derivative Time b5-05 and Z^-1 blocks; b5-01 2 or 4 / 1 or 3. PID Input U5-02; PID Input Limit b5-35; Proportional Gain b5-02 (P); PID Input Characteristic H1-□□=35 (0/1, -1); Integral Hold H1-□□=31 (0/1); I-time b5-03 (1/s); I-limit b5-04; feedback Z^-1; Integral Reset H1-□□=30 (0/1). Derivative Time b5-05 with Z^-1 and b5-01 1 or 3 / 2 or 4. PID Output Upper/Lower Limit b5-06/b5-34; PID Delay Time b5-08; PID Output Characteristic b5-09 (0/1, -1); PID Offset b5-07; PID Output Gain b5-10. Enable/Disable Reverse Operation when PID Output is Negative: b5-11 0/1, Always 1 when b5-01=3/4. Branch labels Upper Limit Fmax ×109%, Lower Limit 0; bidirectional branch Upper Limit Fmax ×109%, Lower Limit Fmax ×109% (literal lower label has no minus sign). PID Ouput [source spelling] U5-03. PID disable when b5-01=0, a JOG Command is Input, or PID Disable by Digital Input Enabled; Enabled/Disabled switch. Sleep Function: b5-15 Sleep Level, b5-16 Delay Timer, RUN 1 On/Off. SFS C1-□□; Output Frequency. Plus/minus summing nodes and arrow routing are visible but complete mathematical topology is not converted to executable logic; consult original diagram. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

n PID Block Diagram

5.2 b: Application

Manual — PID modes, proportional gain and integral control — page 139

Source reference: SIEP C71060618F, December 2016, physical PDF page 139. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Without Integral: PID feedback, Setpoint, Feedback, Offset, Time. With Integral: Setpoint, Feedback, Zero offset with integral action, Time. Diagram illustrates conceptual transient responses, not numerical gains or measured performance. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

n b5-01: PID Function Setting

Enables or disables the PID operation and selects the PID operation mode.

No. Parameter Name Setting Range Default

Setting 0: PID disabled

Setting 1: Output Frequency = PID Output 1 The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.

Setting 2: Output Frequency = PID Output 2 The PID controller is enabled and the PID output builds the frequency reference. The PID feedback is D controlled.

Setting 3: Output Frequency = Frequency Reference + PID Output 1 The PID controller is enabled and the PID output is added to the frequency reference. D control is applied to the difference of the feedback value (U5-02) and the setpoint.

Setting 4: Output Frequency = Frequency Reference + PID Output 2 The PID controller is enabled and the PID output is added to the frequency reference. Applies D control on the feedback value (U5-06).

n b5-02: Proportional Gain Setting (P)

Sets the P gain that is applied to the PID input. A large value will tend to reduce the error, but may cause instability (oscillations) if too high. A small value may allow too much offset between the setpoint and feedback.

No. Name Setting Range Default

n b5-03: Integral Time Setting (I)

Sets the time constant that is used to calculate the integral of the PID input. The smaller the integral time set to b5-03, the faster the offset will be eliminated. If set too short, it can cause overshoot or oscillations. To turn off the integral time, set b5-03 = 0.00.

n b5-04: Integral Limit Setting

Sets the maximum output possible from the integral block. Set as a percentage of the maximum frequency (E1-04).

Note: On some applications, especially those with rapidly varying loads, the output of the PID function may show a fair amount of oscillation. To suppress this oscillation, a limit can be applied to the integral output by programming b5-04.

5.2 b: Application

Parameter Details

b5-01 / PID Function Setting — PDF page 139

Source row No. Parameter Name Setting Range Default
1 b5-01 PID Function Setting 0 to 4 0

b5-02 / Proportional Gain Setting (P) — PDF page 139

Source row No. Name Setting Range Default
1 b5-02 Proportional Gain Setting (P) 0.00 to 25.00 1.00

b5-03 / Integral Time Setting (I) — PDF page 139

Source row No. Name Setting Range Default
1 b5-03 Integral Time Setting (I) 0.0 to 360.0 s 1.0 s

b5-04 / Integral Limit Setting — PDF page 139

Source row No. Name Setting Range Default
1 b5-04 Integral Limit Setting 0.0 to 100.0 100.0

Manual — PID derivative, output bounds, gain and reverse — page 140

Source reference: SIEP C71060618F, December 2016, physical PDF page 140. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n b5-05: Derivative Time (D)

Sets the time the drive predicts the PID input/PID feedback signal based on the derivative of the PID input/PID feedback. Longer time settings will improve the response but can cause vibrations. Shorter settings will reduce the overshoot but also reduce the controller responsiveness. D control is disabled by setting b5-05 to zero seconds.

No. Name Setting Range Default

n b5-06: PID Output Limit

Sets the maximum output possible from the entire PID controller. Set as a percentage of the maximum frequency (E1-04).

n b5-07: PID Offset Adjustment

Sets the offset added to the PID controller output. Set as a percentage of the maximum frequency.

n b5-08: PID Primary Delay Time Constant

Sets the time constant for the filter applied to the output of the PID controller. Normally, change is not required.

Note: Effective in preventing oscillation when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant frequency. Increasing this time constant reduces the responsiveness of the drive.

n b5-09: PID Output Level Selection

Normally, the output of the PID function increase whenever the PID input is negative (feedback below setpoint). Using b5-09 the PID controller can be set up for applications that require opposite operation.

No. Parameter Name Setting Range Default

Setting 0: Normal Output A negative PID input causes an increase in the PID output (direct acting).

Setting 1: Reverse Output A negative PID input causes a decrease in the PID output (reverse acting).

n b5-10: PID Output Gain Setting

Applies a gain to the PID output and can be helpful when the PID function is used to trim the frequency reference (b5-01 = 3 or 4). Increasing b5-10 causes the PID function to have a greater regulating effect on the frequency reference.

n b5-11: PID Output Reverse Selection

Determines whether a negative PID output reverses the drive operation direction or not. When the PID function is used to trim the frequency reference (b5-01 = 3 or 4), this parameter has no effect and the PID output will not be limited (same as b5-11 = 1).

Setting 0: Reverse Disabled Negative PID output will be limited to 0 and the drive output will be stopped.

5.2 b: Application

b5-05 / Derivative Time — PDF page 140

Source row No. Name Setting Range Default
1 b5-05 Derivative Time 0.00 to 10.00 s 0.00 s

b5-06 / PID Output Limit — PDF page 140

Source row No. Name Setting Range Default
1 b5-06 PID Output Limit 0.0 to 100.0% 100.0%

b5-07 / PID Offset Adjustment — PDF page 140

Source row No. Name Setting Range Default
1 b5-07 PID Offset Adjustment -100.0 to 100.0% 0.0%

b5-08 / PID Primary Delay Time Constant — PDF page 140

Source row No. Name Setting Range Default
1 b5-08 PID Primary Delay Time Constant 0.00 to 10.00 s 0.00 s

b5-09 / PID Output Level Selection — PDF page 140

Source row No. Parameter Name Setting Range Default
1 b5-09 PID Output Level Selection 0 or 1 0

b5-10 / PID Output Gain Setting — PDF page 140

Source row No. Name Setting Range Default
1 b5-10 PID Output Gain Setting 0.00 to 25.00 1.00

b5-11 / PID Output Reverse Selection — PDF page 140

Source row No. Parameter Name Setting Range Default
1 b5-11 PID Output Reverse Selection 0 or 1 0

Manual — PID reverse continuation and feedback loss detection — page 141

Source reference: SIEP C71060618F, December 2016, physical PDF page 141. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

PID feedback value; PID Feedback Detection Loss Level (b5-13); time; PID Feedback Loss Detection Time (b5-14) shown for both shorter and sufficient intervals; no FbL detection / FbL detection. Capitalization on graph retained separately from alarm prose FBL. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Setting 1: Reverse Enabled Negative PID output will cause the drive to run in the opposite direction.

n PID Feedback Loss Detection

The PID Feedback Loss Detection function can detect broken sensors or broken sensor wiring. It should be used whenever PID control is enabled to prevent critical machine conditions (e.g. acceleration to max. frequency) caused by a feedback loss. Feedback loss can be detected in two ways: • Feedback Low Detection: Detected when the feedback falls below a certain level for longer than the specified time. • Feedback High Detection: Detected when the feedback rises beyond a certain level for longer than the specified time. The following figure explains the working principle of feedback loss detection when the feedback signal is too low. Feedback high detection works in the same way.

The parameters necessary to set up the feedback loss detection are explained below.

n b5-12: PID Feedback Loss Detection Selection

Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.

No. Parameter Name Setting Range Default

Setting 0: Digital Output Only A digital output set for “PID feedback low” (H2-□□ = 3E) will be triggered if the PID feedback value is below the detection level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PID feedback high” (H2-□□ = 3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for the time set to b5-37 or longer. Neither a fault nor an alarm is displayed on the digital operator. The drive will continue operation. When the feedback value leaves the loss detection range, the output is reset.

Setting 1: Feedback Loss Alarm If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” alarm will be displayed and a digital output set for “PID feedback low” (H2-□□ = 3E) will be triggered. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed and a digital output set for “PID feedback high” (H2-□□ = 3F) will be triggered. Both events trigger an alarm output (H1-□□ = 10). The drive will continue operation. When the feedback value leaves the loss detection range, the alarm and outputs are reset.

Setting 2: Feedback Loss Fault If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” fault will be displayed. Both events trigger a fault output (H1-□□ = E) and cause the drive to stop the motor.

Setting 3: Digital Output Only, Even if PID is Disabled by Digital Input Same as b5-12 = 0. Detection is still active even if PID is disabled by a digital input (H1-□□ = 19).

5.2 b: Application

Parameter Details

b5-12 / PID Feedback Loss Detection Selection — PDF page 141

Source row No. Parameter Name Setting Range Default
1 b5-12 PID Feedback Loss Detection Selection 0 to 5 0

Manual — Feedback detection timing and sleep operation — page 142

Source reference: SIEP C71060618F, December 2016, physical PDF page 142. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

PID Output; PID Sleep Function Start Level (b5-15); Sleep Delay Time b5-16 on entering and leaving sleep; Internal Run command Run/Stop; External Run command remains enabled; During Run continues to output “During Run”. Source prose says sleep remains active even if PID control is disabled. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Setting 4: Feedback Loss Alarm, Even if PID is Disabled by Digital Input Same as b5-12 = 1. Detection is still active even if PID is disabled by a digital input (H1-□□ = 19).

Setting 5: Feedback Loss Fault, Even if PID is Disabled by Digital Input Same as b5-12 = 2. Detection is still active even if PID is disabled by a digital input (H1-□□ = 19).

n b5-13: PID Feedback Loss Detection Level

Sets the feedback level used for PID feedback loss detection. The PID feedback has to fall below this level for longer than the time b5-14 before feedback loss is detected.

No. Name Setting Range Default

n b5-14: PID Feedback Loss Detection Time

Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.

n b5-36: PID Feedback High Detection Level

Sets the feedback level used for PID feedback high detection. The PID feedback has to exceed this level for longer than the time b5-37 before feedback loss is detected.

n b5-37: PID Feedback High Detection Time

Sets the time for that the PID feedback has to exceed b5-36 before feedback loss is detected.

n PID Sleep

The PID Sleep function stops the drive when the PID output or the frequency reference falls below the PID Sleep operation level for a certain time. The drive will resume operating once the PID output or frequency reference rises above the PID Sleep operation level for the specified time. The operation is explained in the figure below.

Notes on using the PID Sleep function: • The PID Sleep function is always active, even if PID control is disabled. • The method the Sleep function uses to stop the motor is defined by parameter b1-03. • The parameters necessary to set up the PID Sleep function are explained below.

n b5-15: PID Sleep Function Start Level

Sets the level used for PID Sleep. The drive goes into Sleep mode if the PID output or frequency reference is smaller than b5-15 for longer than the time set in b5-16. It resumes the operation when the PID output or frequency reference is above b5-15 for longer than the time set in b5-16.

5.2 b: Application

b5-13 / PID Feedback Loss Detection Level — PDF page 142

Source row No. Name Setting Range Default
1 b5-13 PID Feedback Loss Detection Level 0 to 100% 0%

b5-14 / PID Feedback Loss Detection Time — PDF page 142

Source row No. Name Setting Range Default
1 b5-14 PID Feedback Loss Detection Time 0.0 to 25.5 s 1.0 s

b5-36 / PID Feedback High Detection Level — PDF page 142

Source row No. Name Setting Range Default
1 b5-36 PID Feedback High Detection Level 0 to 100% 100%

b5-37 / PID Feedback High Detection Time — PDF page 142

Source row No. Name Setting Range Default
1 b5-37 PID Feedback High Detection Time 0.0 to 25.5 s 1.0 s

Manual — PID sleep, acceleration, setpoint and scaling — page 143

Source reference: SIEP C71060618F, December 2016, physical PDF page 143. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

n b5-16: PID Sleep Delay Time

Sets the delay time to activate or deactivate the PID Sleep function.

n b5-17: PID Accel/Decel Time

The PID acceleration/deceleration time is applied on the PID setpoint value. As the normal acceleration times C1-□□ are applied after the PID output, they reduce the responsiveness of the system and can cause hunting or over- and undershooting when the setpoint changes quickly. Using the PID acceleration/deceleration time instead helps to avoid such problems. The PID acceleration/deceleration time can be canceled using a digital input programmed for “PID SFS cancel” (H1-□□ = 34).

n b5-18: PID Setpoint Selection

Enables or disables parameter b5-19 for PID setpoint.

No. Parameter Name Setting Range Default

Setting 0: Disabled Parameter b5-19 is not used as the PID setpoint. The setpoint must be entered via an analog input, pulse input, or MEMOBUS/ Modbus register 06H.

Setting 1: Enabled Parameter b5-19 is used as PID setpoint.

n b5-19: PID Setpoint Value

Used to adjust the PID setpoint if parameter b5-18 = 1.

n b5-20: PID Setpoint Scaling

Determines the units that the PID setpoint (b5-19) is set in and displayed. Also determines the units for monitors U5-01 and U5-04.

Setting 0: Hz The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.

Setting 1: % The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.

Setting 2: r/min The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined The setpoint b5-19 and PID monitors U1-01/04 are displayed with the unit and resolution defined by parameters b5-38 and b5-39.

5.2 b: Application

Parameter Details

b5-15 / PID Sleep Function Start Level — PDF page 143

Source row No. Name Setting Range Default
1 b5-15 PID Sleep Function Start Level 0.0 to 400.0 Hz 0.0 Hz

b5-16 / PID Sleep Delay Time — PDF page 143

Source row No. Name Setting Range Default
1 b5-16 PID Sleep Delay Time 0.0 to 25.5 s 0.0 s

b5-17 / PID Accel/Decel Time — PDF page 143

Source row No. Name Setting Range Default
1 b5-17 PID Accel/Decel Time 0 to 255 s 0 s

b5-18 / PID Setpoint Selection — PDF page 143

Source row No. Parameter Name Setting Range Default
1 b5-18 PID Setpoint Selection 0 or 1 0

b5-19 / PID Setpoint Value — PDF page 143

Source row No. Name Setting Range Default
1 b5-19 PID Setpoint Value 0.00 to 100.00% 0.00%

b5-20 / PID Setpoint Scaling — PDF page 143

Source row No. Parameter Name Setting Range Default
1 b5-20 PID Setpoint Scaling 0 to 3 1

Manual — PID limits, display, reverse selection and dwell — page 144

Source reference: SIEP C71060618F, December 2016, physical PDF page 144. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n b5-34: PID Output Lower Limit

Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower limit is disabled when set to 0.00%

No. Name Setting Range Default

n b5-35: PID Input Limit

Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1–04). Parameter b5-35 acts as a bipolar limit.

n b5-38/39 PID Setpoint/Monitor User Display Value/Display Digits

When parameter b5-20 is set to 3, the parameters b5-38 and b5-39 can be used to set a user defined display for the PID setpoint (b5-19) and feedback monitors (U5-01/04). Parameter b5-38 determines the display value when the maximum frequency is output. Parameter b5-39 determines the number of digits. The setting value is equal to the number of decimal places.

n b5-40: Frequency Reference Monitor Content During PID

Sets the content on the frequency reference monitor display (U1-01) when PID control is active.

Setting 0: Frequency Reference after PID Monitor U1-01 displays the frequency reference increased or reduced for the PID output.

Setting 1: Frequency Reference Monitor U1-01 displays the frequency reference value.

n b5-47: Reverse Operation Selection 2 by PID Output

Reverses operation selection when b5-01 is set to 3 or 4.

Setting 0: Zero Limit when PID Output is a Negative Value Setting 1: Reverse Operation when PID Output is a Negative Value (Zero Limit if the Reverse Operation Is Prohibited by b1-04) u b6: Dwell Function

The reference hold or Dwell function is used to temporarily hold the output frequency at a set reference value, for a set time, and then continue to ramp up or stop. The Dwell at start function can be used when driving a permanent magnet motor in V/f Control, or a motor with a heavy starting load. The pause in acceleration allows the PM motor rotor to align with the stator field of the motor, thus reducing the starting current. Dwell works as shown in the figure below.

Note: Using the Dwell function requires that the stopping method for the drive be set to “Ramp to Stop” (b1-03 = 0).

5.2 b: Application

b5-34 / PID Output Lower Limit — PDF page 144

Source row No. Name Setting Range Default
1 b5-34 PID Output Lower Limit -100.0 to 100.0% 0.00%

b5-35 / PID Input Limit — PDF page 144

Source row No. Name Setting Range Default
1 b5-35 PID Input Limit 0.0 to 1000.0% 1000.0%

b5-38 / b5-39 — PID Setpoint/Monitor User Display Value — PDF page 144

Source row No. Name Setting Range Default
1 b5-38 PID Setpoint/Monitor User Display Value 0 to 60000 Determined by b5-20
2 b5-39 PID Setpoint and Display Digits 0 to 3 Determined by b5-20

b5-40 / Frequency Reference Monitor Content During PID — PDF page 144

Source row No. Name Setting Range Default
1 b5-40 Frequency Reference Monitor Content During PID 0 or 1 0

b5-47 / Reverse Operation Selection 2 by PID Output — PDF page 144

Source row No. Name Setting Range Default
1 b5-47 Reverse Operation Selection 2 by PID Output 0 or 1 1

Manual — Dwell references and Energy Saving settings — page 145

Source reference: SIEP C71060618F, December 2016, physical PDF page 145. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Run Command OFF → ON → OFF; Output Frequency; start reference b6-01 held for b6-02; stop reference b6-03 held for b6-04. Dwell stopping conditions require b1-03=0 in adjacent source prose. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

n b6-01/b6-02: Dwell Reference/Time at Start

b6-01 sets the frequency that is kept for the time set in b6-02 during acceleration.

No. Name Setting Range Default

n b6-03/b6-04: Dwell Reference/Time at Stop

Parameter b6-03 sets the frequency that is kept for the time set in b6-04 during deceleration.

u b8: Energy Saving

The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient level. This is accomplished by continuously monitoring the motor load and controlling the motor so that it always operates near its rated slip frequency.

Note: Energy Saving is mainly designed for applications with variable torque (Normal Duty) but is not appropriate for applications where the load may suddenly increase.

n b8-01: Energy Saving Control Selection

Enables or disables the Energy Saving function.

No. Parameter Name Setting Range Default

Setting 0: Disabled

Setting 1: Enabled

n b8-02: Energy Saving Gain (OLV only)

Sets the gain that is used to for magnetizing current reduction during Energy Saving. A higher value results in lower magnetization of the motor and thereby less energy consumption. However, if b8-02 is too high the motor might stall.

n b8-03: Energy Saving Control Filter Time Constant (OLV only)

Parameter b8-03 sets the response time for Energy Saving. Although lowering this value allows for a quicker response, instability may result if it is too low.

5.2 b: Application

Parameter Details

b6-01 / b6-02 — Dwell Reference at Start — PDF page 145

Source row No. Name Setting Range Default
1 b6-01 Dwell Reference at Start 0.0 to 400.0 Hz 0.0 Hz
2 b6-02 Dwell Time at Start 0.0 to 10.0 s 0.0 s

b6-03 / b6-04 — Dwell Reference at Stop — PDF page 145

Source row No. Name Setting Range Default
1 b6-03 Dwell Reference at Stop 0.0 to 400.0 Hz 0.0 Hz
2 b6-04 Dwell Time at Stop 0.0 to 10.0 s 0.0 s

b8-01 / Energy Saving Control Selection — PDF page 145

Source row No. Parameter Name Setting Range Default
1 b8-01 Energy Saving Control Selection 0 or 1 0

b8-02 / Energy Saving Gain — PDF page 145

Source row No. Name Setting Range Default
1 b8-02 Energy Saving Gain 0.00 to 10.0 0.7

b8-03 / Energy Saving Control Filter Time Constant — PDF page 145

Source row No. Name Setting Range Default
1 b8-03 Energy Saving Control Filter Time Constant 0.00 to 10.00 Determined by o2-04

Manual — Energy Saving coefficients, filtering and motor parameters — page 146

Source reference: SIEP C71060618F, December 2016, physical PDF page 146. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n b8-04: Energy Saving Coefficient Value (V/f Control)

Fine tunes Energy Saving control. The default setting is for a standard Yaskawa motor. When using a different motor, adjust this parameter in 5% increments while running the drive with a light load until output power monitor U1-08 is at the minimum value. A low setting results in less output voltage and less energy consumption. If the value is set too low the motor may stall. The default setting depends on the capacity of the drive.

No. Name Setting Range Default

Note: This default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically when Auto-Tuning for Energy Saving is performed (Refer to Auto-Tuning on page 102).

n b8-05: Power Detection Filter Time (V/f Control only)

The Energy Saving function continuously searches out the lowest output voltage in order to achieve minimum output power. Parameter b8-05 determines how often the output power is measured and the output voltage is adjusted.

n b8-06: Search Operation Voltage Limit (V/f Control only)

Sets the voltage limit for the optimal output voltage detection of Speed Search as a percentage of the maximum output voltage. During the search operation the drive will keep the output voltage above this level to prevent motor stalling.

Note: If set too low, the motor may stall with a sudden increase to the load. Disabled when b8-06 = 0. Setting this value to 0 does not disable Energy Saving.

n Parameters Related to the Energy Saving Function

Open Loop Vector Control

No. Parameter Name Setting Range Default

<1> Automatically set when Rotational Auto-Tuning is performed. <2> Default setting is determined by drive capacity (o2-04).

V/f Control

<1> Automatically set when Auto-Tuning is performed. <2> Default setting is determined by drive capacity (o2-04).

5.2 b: Application

b8-04 / Energy Saving Coefficient Value — PDF page 146

Source row No. Name Setting Range Default
1 b8-04 Energy Saving Coefficient Value 0.00 to 655.00 Determined by C6-01, E2-11, and o2-04

b8-05 / Power Detection Filter Time — PDF page 146

Source row No. Name Setting Range Default
1 b8-05 Power Detection Filter Time 0 to 2000 ms 20 ms

b8-06 / Search Operation Voltage Limit — PDF page 146

Source row No. Name Setting Range Default
1 b8-06 Search Operation Voltage Limit 0 to 100% 0%

E2-02 <1> / Motor Rated Slip — PDF page 146

Source row No. Parameter Name Setting Range Default
1 E2-02 <1> Motor Rated Slip 0.00 to 20.00 <2>

E2-11 <1> / Motor Rated Capacity — PDF page 146

Source row No. Parameter Name Setting Range Default
1 E2-11 <1> Motor Rated Capacity 0.00 to 650.00 kW <2>

Manual — Acceleration/deceleration parameter groups and input selection — page 147

Source reference: SIEP C71060618F, December 2016, physical PDF page 147. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency / Time; Accel Time 1 C1-01, Decel Time 1 C1-02; Accel Time 2 C1-03, Decel Time 2 C1-04; Accel Time 3 C1-05, Decel Time 3 C1-06; Accel Time 4 C1-07, Decel Time 4 C1-08; further Decel Time 1 C1-02. FWD (REV) Run command ON/OFF transitions. Accel/Decel Time Selection 1 (Terminals S3 to S8, H1-0x=“7”); Selection 2 (Terminals S3 to S8, H1-0x=“1A”); ON/OFF source states. Numerical truth table is Table5.9 above; no timing durations inferred. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

5.3 C: Tuning

C parameters are used to set the acceleration and deceleration characteristics, as well as S-curves. Other parameters in this group cover settings for slip compensation, torque compensation, and carrier frequency.

u C1: Acceleration and Deceleration Times

n C1-01 to C1-08: Accel/Decel Times 1 to 4

Four different sets of acceleration and deceleration times can be set in the drive. They can be selected by digital inputs, by the motor selection, or can be switched automatically. Acceleration time parameters always set the time to accelerate from 0 to the maximum output frequency (E1-04). Deceleration time parameters always set the time to decelerate from maximum output frequency to 0. C1-01 and C1-02 are the default active accel/decel settings.

No. Parameter Name Setting Range Default

<1> The setting range for the acceleration and deceleration times is determined by C1-10 (Accel/Decel Time Setting Units). For example, if the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.

Switching Acceleration Times by Digital Input Accel/decel times 1 are active by default if no input is set. The accel/decel times 2, 3, and 4 can be activated by digital inputs (H1-□□= 7 and 1A) as explained in Table 5.9.

Table 5.9 Accel/Decel Time Selection by Digital Input

Accel/Decel Time Sel. 1 H1-□□ = 7 | Accel/Decel Time Sel. 2 H1-□□ = 1A

Active Times: Acceleration | Deceleration

Figure 5.22 shows an operation example for changing accel/decel. times. The example below requires that the stopping method be set for "Ramp to Stop" (b1-03 = 0).

Parameter Details

C1-01 / C1-02 / C1-03 / C1-04 / C1-05 / C1-06 / C1-07 / C1-08 — Acceleration Time 1 — PDF page 147

Source row No. Parameter Name Setting Range Default
1 C1-01 Acceleration Time 1 0.0 to 6000.0 s <1> 10.0 s
2 C1-02 Deceleration Time 1 0.0 to 6000.0 s <1> 10.0 s
3 C1-03 Acceleration Time 2 0.0 to 6000.0 s <1> 10.0 s
4 C1-04 Deceleration Time 2 0.0 to 6000.0 s <1> 10.0 s
5 C1-05 Acceleration Time 3 (Motor 2 Accel Time 1) 0.0 to 6000.0 s <1> 10.0 s
6 C1-06 Deceleration Time 3 (Motor 2 Decel Time 1) 0.0 to 6000.0 s <1> 10.0 s
7 C1-07 Acceleration Time 4 (Motor 2 Accel Time 2) 0.0 to 6000.0 s <1> 10.0 s
8 C1-08 Deceleration Time 4 (Motor 2 Accel Time 2) 0.0 to 6000.0 s <1> 10.0 s

Table5.9 Accel/Decel Time Selection by Digital Input — PDF page 147

Source row Accel/Decel Time Sel.1 H1-□□=7 Accel/Decel Time Sel.2 H1-□□=1A Active Times:Acceleration Active Times:Deceleration
1 0 0 C1-01 C1-02
2 1 0 C1-03 C1-04
3 0 1 C1-05 C1-06
4 1 1 C1-07 C1-08

Manual — Frequency/motor selection and fast-stop timing — page 148

Source reference: SIEP C71060618F, December 2016, physical PDF page 148. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C1-03 = [(accel time from 0 Hz to C1-11) × (E1-04)] / C1-11. C1-01 = [(accel time between C1-11 and E1-04) × (E1-04)] / (E1-04 - C1-11). C1-02 = [(decel time between E1-04 and C1-11) × (E1-04)] / (E1-04 - C1-11). C1-04 = [(decel time from C1-11 to 0 Hz) × (E1-04)] / C1-11. Graph Output Frequency; C1-11 Accel/Decel Time Switch Frequency; segments C1-03 setting, C1-01 setting, C1-02 setting, C1-04 setting. Printed caption statements: output frequency ≥ C1-11 uses Accel/Decel Time 1 (C1-01,-02); output frequency < C1-11 uses Accel/Decel Time 2 (C1-03,-04). These labels conflict with adjacent prose describing low-frequency C1-07/08; both preserved. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Switching Accel/decel Times by a Frequency Level The drive can automatically switch from accel/decel times 4 (C1-07 and C1-08) to the default accel/decel times (C1-01/02 for motor 1, C1-05/06 for motor 2) when the output frequency exceeds the frequency level set in parameter C1-11. When it falls below this level, the accel/decel times are switched back. Figure 5.23 shows an operation example.

Note: Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by a frequency level. For example, if accel/decel time 2 is selected, the drive will use this time only and not switch from accel/decel time 4 to the selected one.

Switching Acceleration and Deceleration Times by Motor Selection When switching between motor 1 and 2 using a digital input (H1-□□ = 16) parameters C1-01 to C1-04 become accel/decel time 1/2 for motor 1 and C1-05 to C1-08 become accel/decel time 1/2 for motor 2. In this case the digital input “Accel/Decel Time 2 Selection” cannot be used (this would trigger an oPE03 error, indicating a contradictory multi-function input settings). Table 5.10 explains the activation of accel/decel times depending on the motor selection and accel/decel time selection.

Table 5.10 Motor Switching and Accel/Decel Time Combinations

Accel/Decel Time 1 (H1-□□ = 7) | Motor 1 Selected: Accel, Decel | Motor 2 Selected: Accel, Decel

n C1-09: Fast-stop Time

Parameter C1-09 will set a special deceleration that is used when certain faults occur or that can be operated by closing a digital input configured as H1-□□ = 15 (N.O. input) or H1-□□ = 17 (N.C. input). The input does not have to be closed continuously, even a momentary closure will trigger the Fast-stop operation. Unlike standard deceleration, once the Fast-stop operation is initiated, the drive cannot be restarted until the deceleration is complete, the Fast-stop input is cleared, and the Run command is cycled. A digital output programmed for “During Fast-stop” (H2-01/02/03 = 4C) will be closed as long as Fast-stop is active.

No. Parameter Name Setting Range Default

<1> The setting range for the acceleration and deceleration times is determined by C1-10 (Accel/Decel Time Setting Units). For example, if the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s

NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast-stop time to C1-09.

n C1-10: Accel/Decel Time Setting Units

Determines the units for the acceleration and deceleration times set to C1-01 through C1-09 using parameter C1-10.

Setting 0: 0.01 s Units The accel/decel. times are set in 0.01 s units. The setting range will be 0.00 to 600.00 s. If any of the parameters C1-01 to C1-09 is set to 600.1 seconds or more, then C1-10 cannot be set to 0.

Setting 1: 0.1 s Units The accel/decel. times are set in 0.1 s units. The setting range will be 0.0 to 6000.0 s.

5.3 C: Tuning

C1-09 / Fast-stop Time — PDF page 148

Source row No. Parameter Name Setting Range Default
1 C1-09 Fast-stop Time 0.0 to 6000.0 s <1> 10.0 s

C1-10 / Accel/Decel Time Setting Units — PDF page 148

Source row No. Parameter Name Setting Range Default
1 C1-10 Accel/Decel Time Setting Units 0 or 1 1

Table5.10 Motor Switching and Accel/Decel Time Combinations — PDF page 148

Source row Accel/Decel Time1 H1-□□=7 Motor1:Accel Motor1:Decel Motor2:Accel Motor2:Decel
1 Open C1-01 C1-02 C1-05 C1-06
2 Closed C1-03 C1-04 C1-07 C1-08

Manual — Accel/decel switch and base-rate frequency — page 149

Source reference: SIEP C71060618F, December 2016, physical PDF page 149. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C1-14=0 Hz; E1-04=60 Hz; Frequency Reference=60 Hz. Output frequency / Time, 0; Accel Times 1 to 4; Decel Times 1 to 4. Values are illustrative source example, not installed drive settings. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

n C1-11: Accel/Decel Switch Frequency

Sets the switching frequency for automation accel/decel time change over. Refer to Switching Accel/decel Times by a Frequency Level on page 148 for details.

No. Parameter Name Setting Range Default

Note: Setting C1-11 to 0.0 Hz disables this function.

n C1-14: Accel/Decel Rate Frequency

Sets the base frequency used to calculate acceleration and deceleration times.

Note: The accel/decel rates set to parameters C1-01 to C1-09 change in response to the value set to C1-14. When C1-14 = 0.0 Hz Operation example is shown in Figure 5.24. • Accel Times 1 through 4 determine the time required to accelerate from 0 to the maximum output frequency (E1-04) • Decel Times 1 through 4 and the Fast-stop Time determine the time required to decelerate from the Maximum Output Frequency (E1-04) to 0 Hz.

When C1-14 ≠ 0.0 Hz Operation examples are shown in Figure 5.25 and Figure 5.26. • Accel Times 1 through 4 determine the time required to accelerate from 0 to the value set in C1-14 (Accel/Decel Rate Frequency) • Decel Times 1 through 4 and the Fast-stop Time determine the time required to decelerate from the value set in C1-14 (Accel/ Decel Rate Frequency ) to 0 Hz.

5.3 C: Tuning

Parameter Details

C1-11 / Accel/Decel Switch Frequency — PDF page 149

Source row No. Parameter Name Setting Range Default
1 C1-11 Accel/Decel Switch Frequency 0.0 to 400.0 Hz 0.0 Hz

C1-14 / Accel/Decel Rate Frequency — PDF page 149

Source row No. Parameter Name Setting Range Default
1 C1-14 Accel/Decel Rate Frequency 0.0 to 400.0 Hz 0.0 Hz

Manual — Rate examples, qualifications and S-curve parameters — page 150

Source reference: SIEP C71060618F, December 2016, physical PDF page 150. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C1-14=40 Hz; E1-04=60 Hz; Frequency reference=60 Hz. Output frequency / Time,0; Accel Times 1 to 4 shown to40 Hz; Decel Times 1 to 4 shown from40 Hz. Values are illustrative source example; no calculated elapsed times. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

C1-14=80 Hz; E1-04=60 Hz; Frequency reference=60 Hz. Output frequency / Time,0; Accel Times 1 to 4 and Decel Times 1 to 4 shown against extended dashed80 Hz ramp. Actual reference plateau is60 Hz. No calculated elapsed time or operating recommendation. Source figure geometry, electrical connections and unprinted numerical values remain original-only.

Note: 1. The accel/decel times shown in Figure 5.24 to Figure 5.26 assume S-curve characteristic time during accel/decel at start and accel/ decel at stop of 0.00 s (parameters C2-01 to C2-04). 2. When Stall Prevention during acceleration is enabled (L3-01 ≠ 0), the accel time may take longer than the set value. 3. When Stall Prevention during deceleration is enabled (L3-04 ≠ 0), the decel time may take longer than the set value. 4. When performing Rotational Auto-Tuning for OLV Control (T1-01 = 0) and Rotational Auto-Tuning for V/f Control (T1-04 = 3), the drive uses the maximum output frequency set in E1-04 to determine the base accel/decel rate, regardless of the C1-14 value.

u C2: S-Curve Characteristics

Use S-curve characteristics to smooth acceleration and deceleration and to minimize abrupt shock to the load. Set S-curve characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop. If a STo fault (Step Out Detection) occurs when starting a PM motor, try increasing the value set to C2-01.

n C2-01 to C2-04: S-Curve Characteristics

C2-01 through C2-04 set separate S-curves for each section of the acceleration or deceleration.

No. Parameter Name Setting Range Default

5.3 C: Tuning

C2-01 / C2-02 / C2-03 / C2-04 — S-Curve Characteristic at Accel Start — PDF page 150

Source row No. Parameter Name Setting Range Default
1 C2-01 S-Curve Characteristic at Accel Start 0.00 to 10.00 s Determined by A1-02
2 C2-02 S-Curve Characteristic at Accel End 0.00 to 10.00 s 0.20 s
3 C2-03 S-Curve Characteristic at Decel Start 0.00 to 10.00 s 0.20 s
4 C2-04 S-Curve Characteristic at Decel End 0.00 to 10.00 s 0.00 s

Manual — S-curve and Slip Compensation — page 151

Source reference: SIEP C71060618F, December 2016, physical PDF page 151. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Forward Run command; Reverse Run command; Output frequency positive and negative. C2-01 acceleration start, C2-02 acceleration end; C2-03 deceleration start, C2-04 deceleration end are labeled on the curves. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Setting the S-curve will increase the acceleration and deceleration times. Actual accel time = accel time setting + (C2-01 + C2-02)/2. Actual decel time = decel time setting + (C2-03 + C2-04)/2. Parentheses and fraction groupings restored from source; no calculated times. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Figure 5.27 explains how S-curves are applied.

u C3: Slip Compensation

The Slip Compensation function prevents motor speed loss due to an increase in load.

Note: Before making changes to the Slip Compensation parameters, make sure the motor parameters and V/f pattern are set properly or perform Auto-Tuning.

n C3-01: Slip Compensation Gain

This parameter sets the gain for the motor slip compensation function. Although this parameter rarely needs to be changed, adjustments might be needed under the following situations: • If the speed at constant frequency reference is lower than the frequency reference, increase C3-01. • If the speed at constant frequency reference is higher than the frequency reference, decrease C3-01.

No. Parameter Name Setting Range Default

Note: Default setting is 0.0 in V/f Control (A1-02 = 0). Default setting is 1.0 in Open Loop Vector Control (A1-02 = 2). This parameter is disabled when using V/f Control with Simple PG Feedback (H6-01 = 3).

n C3-02: Slip Compensation Primary Delay Time

Adjusts the filter on the output of the slip compensation function. Although this parameter rarely needs to be changed, adjustments might be needed under the following situations: • Decrease the setting when the slip compensation response is too slow. • Increase this setting when the speed is not stable.

Note: When using V/f Control (A1-02 = 0), the default setting becomes 2000 ms. When using Open Loop Vector Control (A1-02 = 2), the default setting becomes 200 ms. This function is not available when using V/f Control with Simple PG Feedback.

n C3-03: Slip Compensation Limit

Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E2-02).

5.3 C: Tuning

Parameter Details

C3-01 / Slip Compensation Gain — PDF page 151

Source row No. Parameter Name Setting Range Default
1 C3-01 Slip Compensation Gain 0.0 to 2.5 Determined by A1-02

C3-02 / Slip Compensation Primary Delay Time — PDF page 151

Source row No. Parameter Name Setting Range Default
1 C3-02 Slip Compensation Primary Delay Time 0 to 10000 ms Determined by A1-02

C3-03 / Slip Compensation Limit — PDF page 151

Source row No. Parameter Name Setting Range Default
1 C3-03 Slip Compensation Limit 0 to 250% 200%

Manual — Slip limits and Torque Compensation — page 152

Source reference: SIEP C71060618F, December 2016, physical PDF page 152. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Slip compensation limit; Output frequency; C3-03 level held to E1-06 Base frequency; rising to (E1-04/E1-06) × C3-03 at E1-04 Maximum output frequency. No additional formula inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

The slip compensation limit is constant throughout the constant torque range. In the constant power range it is increased based on C3-03 and the output frequency as shown in the following diagram.

Note: This parameter is disabled when using V/f Control with Simple PG Feedback Control (H6-01 = 3).

n C3-04: Slip Compensation Selection during Regeneration

When the slip compensation during regeneration function has been activated and regenerative load is applied, it might be necessary to use a braking option (braking resistor, braking resistor unit, or braking unit). Even if enabled, this function does not operate when the output frequency is too low.

No. Parameter Name Setting Range Default

Setting 0: Disabled Slip compensation is not provided. Depending on the load and operation mode (motoring or regenerative) the actual motor speed will be lower or higher than the frequency reference.

Setting 1: Enabled Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.

n C3-05: Output Voltage Limit Operation Selection

Determines if the motor flux reference is automatically reduced when output voltage reaches the saturation range.

Setting 0: Disabled

Setting 1: Enabled

n C3-18: Output Voltage Limit Level

Sets the maximum percentage of output voltage reduction when C3-05 is set to 1 (Enabled).

u C4: Torque Compensation

The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.

Note: Before making changes to the torque compensation parameters make sure the motor parameters and V/f pattern are set properly or perform Auto-Tuning.

n C4-01: Torque Compensation Gain

Sets the gain for the torque compensation function.

5.3 C: Tuning

C3-04 / Slip Compensation Selection during Regeneration — PDF page 152

Source row No. Parameter Name Setting Range Default
1 C3-04 Slip Compensation Selection during Regeneration 0 or 1 0

C3-05 / Output Voltage Limit Operation Selection — PDF page 152

Source row No. Parameter Name Setting Range Default
1 C3-05 Output Voltage Limit Operation Selection 0 or 1 0

C3-18 / Output Voltage Limit Level — PDF page 152

Source row No. Parameter Name Setting Range Default
1 C3-18 Output Voltage Limit Level 70.0 to 100.0% 90.0%

C4-01 / Torque Compensation Gain — PDF page 152

Source row No. Parameter Name Setting Range Default
1 C4-01 Torque Compensation Gain 0.00 to 2.50 Determined by A1-02

Manual — Torque compensation modes and offsets — page 153

Source reference: SIEP C71060618F, December 2016, physical PDF page 153. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Torque Compensation in V/f Control: The drive calculates the motor primary voltage loss using the output current and the terminal resistance value (E2-05) and then adjusts the output voltage to compensate insufficient torque at start or when load is applied. The effect of this voltage compensation can be increased or decreased using parameter C4-01.

Torque Compensation in Open Loop Vector Control: The drive controls the motor excitation current and torque producing current separately. Torque compensation affects the torque producing current only. C4-01 works as a factor of the torque reference value that builds the torque producing current reference.

Adjustment Although this parameter rarely needs to be adjusted, small changes in increments of 0.05 may help in the following situations: • Increase this setting when using a long motor cable. • Decrease this setting when motor oscillation occurs. Adjust C4-01 so that the output current does not exceed the drive rated current.

n C4-02: Torque Compensation Primary Delay Time 1

Sets the delay time used for applying torque compensation.

No. Parameter Name Setting Range Default

Adjustment Although C4-02 rarely needs to be changed, adjustments may help in the following situations: • If the motor vibrates, increase C4-02. • If the motor responds too slowly to changes in the load, decrease C4-02.

n C4-03: Torque Compensation at Forward Start (OLV only)

Sets the amount of torque at start in the forward direction in order to improve motor performance during start with heavy load. Compensation is applied using the time constant set in parameter C4-05. A setting of 0.0% disables this feature.

n C4-04: Torque Compensation at Reverse Start (OLV only)

Sets the amount of torque reference at start in the reverse direction in order to improve motor performance during start with heavy load. Compensation is applied using the time constant set in parameter C4-05. A setting of 0.0% disables this feature.

n C4-05: Torque Compensation at Start Time Constant (OLV only)

This parameter is the time constant for applying the torque compensation at start set in parameters C4-03 and C4-04.

n C4-06: Torque Compensation Primary Delay Time 2 (OLV only)

This time constant is used during Speed Search or during regenerative operation when the actual motor slip is higher than 50% of the rated slip. Adjust the value if an overvoltage fault occurs with sudden changes in the load or at the end of acceleration with high inertia load.

Note: 1. If C4-06 is set to a relatively large value, be sure to also increase the setting in n2-03 (AFR Time Constant 2) proportionally. 2. C4-06 will not be active if L3-04 is 0, 3 or 4, the output frequency is below 5 Hz, or Speed Search after momentary power loss is active.

5.3 C: Tuning

Parameter Details

C4-02 / Torque Compensation Primary Delay Time 1 — PDF page 153

Source row No. Parameter Name Setting Range Default
1 C4-02 Torque Compensation Primary Delay Time 1 0 to 60000 ms Determined by A1-02

C4-03 / Torque Compensation at Forward Start — PDF page 153

Source row No. Parameter Name Setting Range Default
1 C4-03 Torque Compensation at Forward Start 0.0 to 200.0% 0.0%

C4-04 / Torque Compensation at Reverse Start — PDF page 153

Source row No. Parameter Name Setting Range Default
1 C4-04 Torque Compensation at Reverse Start -200.0 to 0.0% 0.0%

C4-05 / Torque Compensation Time Constant — PDF page 153

Source row No. Parameter Name Setting Range Default
1 C4-05 Torque Compensation Time Constant 0 to 200 ms 10 ms

C4-06 / Torque Compensation Primary Delay Time 2 — PDF page 153

Source row No. Parameter Name Setting Range Default
1 C4-06 Torque Compensation Primary Delay Time 2 0 to 10000 ms 150 ms

Manual — ASR pulse-feedback control and activation — page 154

Source reference: SIEP C71060618F, December 2016, physical PDF page 154. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Frequency Reference U1-01; Soft Starter; Soft Starter Output U1-16; multiplication; Output Frequency U1-02. Direction input Digital Input H1-□□=7E: 1/0. External PG pulse converter takes A/B signals and outputs Direction FWD/REV and 1-track speed pulses. Pulse Input; unsigned motor speed feedback; multiplication by direction yields Motor Speed (signed) U1-05. ASR Input U6-03; P control C5-01/C5-03; I control C5-02/C5-04; ASR Limit C5-05; ASR Output U6-04. Summing signs and arrows are visible; complete executable control topology is not reconstructed. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

u C5: Automatic Speed Regulator (ASR)

The ASR is a PI controller that adjusts the output frequency in order to compensate the motor slip when load is applied. It is active only when V/f Control is used in combination with a speed feedback signal connected to the drive pulse input RP (V/ f Control with Simple Speed Feedback). The pulse input provides one track only and cannot detect the direction of motor rotation. A separate motor speed direction signal must therefore be input to the ASR by: 1. Using a Digital Input This method is automatically enabled when a digital input is programmed for “Forward/Reverse direction” (H1-□□= 7E). If the input is closed, the drive assumes reverse rotation. If open, then the drive assumes that the motor is rotating forwards. When a 2 track encoder is used, an external unit that converts the 2 tracks into 1 track and a digital direction signal can be used. 2. Using the Frequency Reference Direction When no digital input is set for “Forward/Reverse direction” (H1-□□≠ 7E), ASR uses the direction of the frequency reference. Figure 5.29 illustrates the ASR function when using V/f with Simple Speed Feedback.

To activate V/f Control with PG feedback: 1. Set the drive to V/f Control (A1-02 = 0). 2. Connect the motor speed pulse signal to the pulse input RP, set H6-01 = 3, and set the pulse signal frequency that is equal to the maximum speed to H6-02 (pulse input scaling). Make sure the pulse input bias (H6-04) is 0% and the gain (H6-03) is 100%. 3. Decide the signal used for detecting the direction. If a digital input is used set H1-□□ = 7E. 4. Use the ASR gain and integral time parameters described below for adjusting the ASR responsiveness. Note: 1. C5 parameters will appear only when using V/f Control (A1-02 = 0) and when the pulse input RP function is set for PG feedback in V/ f Control (H6-01 = 3). 2. V/f Control with PG feedback can be used for motor 1 only. ASR Tuning Parameters ASR provides two sets of gain and integral time. Set 1 is active at the maximum output frequency, set 2 is active at the minimum output frequency. The settings are changed linearly depending on the output frequency as shown in Figure 5.30.

5.3 C: Tuning

Manual — ASR gains, limits and Drive Duty — page 155

Source reference: SIEP C71060618F, December 2016, physical PDF page 155. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

P gain / I time; Motor Speed; 0; E1-09 Minimum output frequency; E1-04 Maximum output frequency. Low-speed gains C5-03 and C5-04; high-speed gains C5-01 and C5-02; transition drawn between speed thresholds. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

n C5-01/02: ASR Proportional Gain/Integral Time 1

These parameters determine the responsiveness of ASR at maximum output frequency. • Increase the gain and/or reduce the integral time if the response is slow at maximum output frequency. • Reduce the gain and/or increase the integral time when vibrations occur at the maximum output frequency. • When adjusting ASR always first adjust the P gain, then adjust the integral time.

No. Parameter Name Setting Range Default

n C5-03/04: ASR Proportional Gain/Integral Time 2

These parameters determine the responsiveness of ASR at the minimum output frequency. Use the same setting rules as described for C5-01/02

n C5-05: ASR Limit

Sets the ASR output limit as a percentage of the maximum output frequency (E1-04). If the motor slip is high, the setting might need to be increased to provide proper slip compensation. Use the ASR output monitor U6-04 to determine if ASR is working at the limit and make settings if necessary. If ASR is operating at the ASR limit, check the pulse signal and the pulse input settings prior to changes in C5-05.

u C6: Carrier Frequency

n C6-01: Drive Duty Selection

The drive has two different duty modes from which to select based on the load characteristics. The drive rated current, overload capacity, and carrier frequency will change depending upon the duty mode selection. Use parameter C6-01 to select Heavy Duty (HD) or Normal Duty (ND) for the application. The default setting is ND. Refer to Heavy Duty and Normal Duty Ratings on page 342 for details about the rated current.

<1> Model BA0018 does not have a Normal Duty mode. The default setting is 0.

5.3 C: Tuning

Parameter Details

C5-01 / C5-02 — ASR Proportional Gain 1 — PDF page 155

Source row No. Parameter Name Setting Range Default
1 C5-01 ASR Proportional Gain 1 0.00 to 300.00 0.20
2 C5-02 ASR Integral Time 1 0.000 to 10.000 s 0.200 s

C5-03 / C5-04 — ASR Proportional Gain 2 — PDF page 155

Source row No. Parameter Name Setting Range Default
1 C5-03 ASR Proportional Gain 2 0.00 to 300.00 0.02
2 C5-04 ASR Integral Time 2 0.000 to 10.000 s 0.050 s

C5-05 / ASR Limit — PDF page 155

Source row No. Parameter Name Setting Range Default
1 C5-05 ASR Limit 0.0 to 20.0% 5.0%

C6-01 / Drive Duty Selection — PDF page 155

Source row No. Parameter Name Setting Range Default
1 C6-01 Drive Duty Selection 0 or 1 1 <1>

Manual — Heavy/Normal Duty and Carrier Frequency — page 156

Source reference: SIEP C71060618F, December 2016, physical PDF page 156. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table 5.11 Differences between Heavy and Normal Duty

Mode Heavy Duty Rating (HD) Normal Duty Rating (ND)

Note: By changing the Drive Duty, the drive maximum applicable motor power changes and the E2-□□ and E4-□□ parameters are automatically set to appropriate values.

n C6-02: Carrier Frequency Selection

Parameter C6-02 sets the switching frequency of the drive’s output transistors. It can be changed in order to reduce audible noise and also reduce leakage current.

Note: The drive rated current is reduced when the carrier frequency is set higher than the default value. Refer to Rated Current Depending on Carrier Frequency on page 158.

No. Parameter Name Setting Range Default

<1> Setting range is determined by the drive software version. PRG: 1020 and later: 1 to B; F PRG: 1018 and earlier: 1 to A; F

Settings:

C6-02 Carrier Frequency

<1> Available in drive software versions PRG: 1020 and later. Setting B uses a PWM pattern that reduces the amount of leakage current detected over long wiring distances. This can help reduce alarm detection and problems with the current monitor that result from leakage current over long wiring distances. This is the same as setting the carrier frequency to 2 kHz.

Note: Swing PWM uses 2.0 kHz carrier frequency as a base. Applying special PWM patterns minimizes the audible noise of the motor. Guidelines for Carrier Frequency Parameter Setup

Symptom Remedy

5.3 C: Tuning

Table5.11 Differences between Heavy and Normal Duty — PDF page 156

Source row Mode Heavy Duty Rating (HD) Normal Duty Rating (ND)
1 C6-01 0 1
2 Characteristics Heavy Duty graph: Overload 150%; Rated Load 100%; Motor Speed 0 to 100%. Rated-load line is constant. Source characteristic diagram only; no intermediate values or measured geometry inferred. Normal Duty graph: Overload 120%; Rated Load 100%; Motor Speed 0 to 100%. Rated-load curve rises toward 100%. Source characteristic diagram only; no intermediate values or measured geometry inferred.
3 Application Use Heavy Duty Rating for applications requiring a high overload tolerance with constant load torque. Such applications include extruders and conveyors. Use Normal Duty Rating for applications in which the torque requirements drop along with the speed. Examples include fans or pumps where a high overload tolerance is not required.
4 Over load capability (oL2) 150% of drive rated Heavy Duty current for 60 s 120% of drive rated Normal Duty current for 60 s
5 L3-02 Stall Prevention during Acceleration 150% 120%
6 L3-06 Stall Prevention during Run 150% 120%
7 Default Carrier Frequency 8/10 kHz 2 kHz Swing PWM

C6-02 / Carrier Frequency Selection — PDF page 156

Source row No. Parameter Name Setting Range Default
1 C6-02 Carrier Frequency Selection <1> Determined by A1-02 and o2-04. Reset when C6-01 is changed.

C6-02 Carrier Frequency settings 1–7 — PDF page 156

Source row C6-02 Carrier Frequency
1 1 2.0 kHz
2 2 5.0 kHz
3 3 8.0 kHz
4 4 10.0 kHz
5 5 12.5 kHz
6 6 15.0 kHz
7 7 Swing PWM 1

C6-02 Carrier Frequency settings 8–B and F — PDF page 156

Source row C6-02 Carrier Frequency
1 8 Swing PWM 2
2 9 Swing PWM 3
3 A Swing PWM 4
4 B <1> Leakage Current Rejection PWM
5 F User-defined (C6-03 to C6-05)

Guidelines for Carrier Frequency Parameter Setup — PDF page 156

Source row Symptom Remedy
1 Speed and torque are unstable at low speeds. Lower the carrier frequency.
2 Noise from the drive is affecting peripheral devices. Lower the carrier frequency.
3 Excessive leakage current from the drive. Lower the carrier frequency.

Manual — Cable length and variable Carrier Frequency — page 157

Source reference: SIEP C71060618F, December 2016, physical PDF page 157. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Carrier Frequency; Output Frequency; lower C6-04; upper C6-03; maximum E1-04. Slope label Output Frequency × C6-05 × K*. K=2 when 10>C6-03≥5; K=1 when 5>C6-03; K=3 when C6-03≥10. Exact source inequalities retained. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Symptom Remedy

<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to the table below. <2> In Normal Duty default setting is 7 (Swing PWM), equivalent to setting 2 kHz. Increasing the carrier frequency is fine when using the drive is set for Normal Duty, but remember that the drive rated current falls when the carrier frequency is increased.

Wiring Distance Up to 50 m Up to 100 m Greater than 100 m

Note: If the motor cable is fairly long when using PM Open Loop Vector, set the carrier frequency to 2 kHz (C6-02 = 1). Switch to V/f Control if the cable is longer than 100 m.

n C6-03/C6-04/C6-05: Carrier Frequency Upper Limit/Lower Limit/Proportional Gain

Use these parameters to set a user defined or a variable carrier frequency. To set the upper and lower limits, first set C6-02 to “F”.

No. Parameter Name Setting Range Default

<1> The default value is determined by the control method (A1-02) as well as the drive capacity (o2-04), and is reinitialized when the value set to C6-01 is changed.

Setting a Fixed User Defined Carrier Frequency A carrier frequency between the fixed selectable values can be entered in parameter C6-03 when C6-02 is set to “F”. In V/f Control, parameter C6-04 must also be adjusted to the same value as C6-03.

Setting a Variable Carrier Frequency (V/f Control only) In V/f Control, the carrier frequency can be set up to change linearly with the output frequency. In this case the upper and lower limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) have to be set as shown in Figure 5.31.

K is a coefficient determined by the value of C6-03: • 10.0 kHz > C6-03 ≥ to 5.0 kHz: K = 2 • 5.0 kHz > C6-03: K = 1 • C6-03 ≥ 10.0 kHz: K = 3 Note: 1. A carrier frequency error (oPE11) will occur when the carrier frequency proportional gain is greater than 6 while C6-03 is less than C6-04. 2. When C6-05 is set lower than 7, C6-04 is disabled and the carrier frequency will be fixed to the value set in C6-03.

5.3 C: Tuning

Parameter Details

Guidelines for Carrier Frequency Parameter Setup continued — PDF page 157

Source row Symptom Remedy
1 Wiring between the drive and motor is too long. <1> • Lower the carrier frequency • Set C6-02 to B if an alarm is detected or if leakage current causes a problem with the current monitor.
2 Audible motor noise is too loud. Increase the carrier frequency or use Swing PWM. <2>

Wiring distance and carrier selection — PDF page 157

Source row Wiring Distance Up to 50 m Up to 100 m Greater than 100 m
1 C6-02 (Carrier Frequency Selection) 0 to 6 (15 kHz) 0 to 4 (10 kHz) 1, 7 to A (2 kHz)

C6-03 / C6-04 / C6-05 — Carrier Frequency Upper Limit — PDF page 157

Source row No. Parameter Name Setting Range Default
1 C6-03 Carrier Frequency Upper Limit 1.0 to 15.0 kHz <1>
2 C6-04 Carrier Frequency Lower Limit (V/f only) 1.0 to 15.0 kHz <1>
3 C6-05 Carrier Frequency Proportional Gain (V/f only) 0 to 99 <1>

Manual — Carrier Frequency rating tables — page 158

Source reference: SIEP C71060618F, December 2016, physical PDF page 158. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n Rated Current Depending on Carrier Frequency

The tables below show the drive output current depending on the carrier frequency settings. The 2 kHz value is equal to the Normal Duty rated current, the 8/10 kHz value is equal to the Heavy Duty rated current. The carrier frequency determines the output current linearly. Use the data below to calculate output current values for carrier frequencies not listed in the tables.

Note: In Heavy Duty mode the maximum rated output current is equal to the 8/10 kHz value, even if the carrier frequency is reduced.

Table 5.12 200 V Class Drives with 10 kHz Heavy Duty Default Carrier Frequency

Model | Rated Current (A): 2 kHz, 10 kHz, 15 kHz

Table 5.13 200 V Class Drives with 8 kHz Heavy Duty Default Carrier Frequency

Model | Rated Current (A): 2 kHz, 8 kHz, 15 kHz

Table 5.14 400 V Class Drives with 8 kHz Heavy Duty Default Carrier Frequency

5.3 C: Tuning

Table5.12 200Vclass drives with 10kHz Heavy Duty default carrier frequency — PDF page 158

Source row Model Rated Current(A) at2kHz Rated Current(A) at10kHz Rated Current(A) at15kHz
1 BA0001 2A0001 1.2 0.8 0.6
2 BA0002 2A0002 1.9 1.6 1.3
3 BA0003 2A0004 3.5 3.0 2.4
4 BA0006 2A0006 6.0 5.0 4.0

Table5.13 200Vclass drives with 8kHz Heavy Duty default carrier frequency — PDF page 158

Source row Model Rated Current(A) at2kHz Rated Current(A) at8kHz Rated Current(A) at15kHz
1 BA0010 2A0010 9.6 8.0 6.4
2 BA0012 2A0012 12.0 11.0 8.8
3 BA0018 17.5 17.5 14.0
4 2A0020 19.6 17.5 14.0
5 2A0030 30.0 25.0 20.0
6 2A0040 40.0 33.0 26.4
7 2A0056 56.0 47.0 37.6
8 2A0069 69.0 60.0 48.0

Table5.14 400Vclass drives with 8kHz Heavy Duty default carrier frequency — PDF page 158

Source row Model Rated Current(A) at2kHz Rated Current(A) at8kHz Rated Current(A) at15kHz
1 4A0001 1.2 1.2 0.7
2 4A0002 2.1 1.8 1.1
3 4A0004 4.1 3.4 2.0
4 4A0005 5.4 4.8 2.9
5 4A0007 6.9 5.5 3.3
6 4A0009 8.8 7.2 4.3
7 4A0011 11.1 9.2 5.5
8 4A0018 17.5 14.8 8.9
9 4A0023 23.0 18.0 10.8
10 4A0031 31.0 24.0 14.4
11 4A0038 38.0 31.0 18.6

Manual — Frequency Reference selection hierarchy — page 159

Source reference: SIEP C71060618F, December 2016, physical PDF page 159. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Frequency Reference Source1 b1-01 / Source2 b1-15: 0 Frequency Reference1 d1-01;1 Terminal A1/A2;2 MEMOBUS communications;3 Option Card;4 Pulse Train Input. Digital Input H1-□□=2 branches0/1; Remote/Local; d2-03 Frequency Reference Lower Limit. Terminal A2 auxiliary H3-10=2/not2 selects d1-02 Multi-Step Speed2. d1-03/04 through d1-15/16 Multi-Step Speed3 to16; d1-17 Jog. Jog Digital Input H1-□□=6; FJOG H1-□□=12; RJOG H1-□□=13. Multi-Step Speed. NetRef0/1 determined by communications option card; Option Card Signal is Off branch. ComRef0/1, MEMOBUS Register0001h bit4 when standard2-wire sequence used. Frequency Reference output. All source branch labels preserved; exact switch hierarchy requires original diagram. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

5.4 d: Reference Settings

The drive offers various ways of entering the frequency reference. The figure below gives an overview of the reference input, selections, and priorities.

Parameter Details

Manual — Multi-Step Speed and Jog selection — page 160

Source reference: SIEP C71060618F, December 2016, physical PDF page 160. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u d1: Frequency Reference

n d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference

Up to 17 preset references (including Jog reference) can be programmed in the drive. The references can be switched during Run by digital inputs. The acceleration/deceleration to the new reference is performed using the active acceleration/deceleration time. The Jog frequency must be selected by a separate digital input and has priority over the references 1 to 16. The multi-speed references 1 and 2 can be provided by analog inputs.

No. Parameter Name Setting Range Default

<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).

Multi-Step Speed Selection Depending on how many speeds are used, some digital inputs have to be programmed for Multi-Step Speed Reference 1, 2, 3 and 4 (H1-□□ = 3, 4, 5, 32). For the Jog reference a digital input must be set to H1-□□ = 6. Notes on using analog inputs as multi-speed 1 and 2: • If the frequency reference source is assigned to analog input A1 (b1-01 = 1), then this input will be used for Frequency Reference 1 instead of d1-01. If the reference source is assigned to the digital operator (b1-01 = 0), then d1-01 will be used as Frequency Reference 1. • When the analog input A2 function is set to “Auxiliary Frequency” (H3-10 = 2), then the value input to terminal A2 will be used as the Frequency Reference 2 instead of the value set to parameter d1-02. When H3-10 does not equal 2, then d1-02 becomes the reference for Frequency Reference 2. The different speed references can be selected as shown in Table 5.15. Figure 5.33 illustrates the multi-step speed selection.

Table 5.15 Multi-Step Speed Reference and Terminal Switch Combinations

Reference

Multi-Step Speed H1-□□=3

Multi-Step Speed 2 H1-□□=4

Multi-Step Speed 3 H1-□□=5

Multi-Step Speed 4 H1-□□=32

Jog Reference H1-□□=6

<1> The Jog frequency overrides the frequency reference being used.

5.4 d: Reference Settings

d1-01 to d1-16 / d1-17 — Frequency Reference 1 to 16 — PDF page 160

Source row No. Parameter Name Setting Range Default
1 d1-01 to d1-16 Frequency Reference 1 to 16 0.00 to 400.00 Hz <1> 0.00 Hz
2 d1-17 Jog Frequency Reference 0.00 to 400.00 Hz <1> 6.00 Hz

Table5.15 Multi-Step Speed Reference and Terminal Switch Combinations — PDF page 160

Source row Reference Multi-Step Speed H1-□□=3 Multi-Step Speed 2 H1-□□=4 Multi-Step Speed 3 H1-□□=5 Multi-Step Speed 4 H1-□□=32 Jog Reference H1-□□=6
1 Frequency Reference 1 (d1-01/A1) OFF OFF OFF OFF OFF
2 Frequency Reference 2 (d1-02/A2) ON OFF OFF OFF OFF
3 Frequency Reference 3 (d1-03) OFF ON OFF OFF OFF
4 Frequency Reference 4 (d1-04) ON ON OFF OFF OFF
5 Frequency Reference 5 (d1-05) OFF OFF ON OFF OFF
6 Frequency Reference 6 (d1-06) ON OFF ON OFF OFF
7 Frequency Reference 7 (d1-07) OFF ON ON OFF OFF
8 Frequency Reference 8 (d1-08) ON ON ON OFF OFF
9 Frequency Reference 9 (d1-09) OFF OFF OFF ON OFF
10 Frequency Reference 10 (d1-10) ON OFF OFF ON OFF
11 Frequency Reference 11 (d1-11) OFF ON OFF ON OFF
12 Frequency Reference 12 (d1-12) ON ON OFF ON OFF
13 Frequency Reference 13 (d1-13) OFF OFF ON ON OFF
14 Frequency Reference 14 (d1-14) ON OFF ON ON OFF
15 Frequency Reference 15 (d1-15) OFF ON ON ON OFF
16 Frequency Reference 16 (d1-16) ON ON ON ON OFF
17 Jog Frequency Reference (d1-17) <1> − − − − ON

Manual — Reference waveforms and frequency limits — page 161

Source reference: SIEP C71060618F, December 2016, physical PDF page 161. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency; d1-01 (A1),d1-02 (A2),d1-03,d1-04,d1-05,d1-06,d1-07; continuation break;d1-12,d1-13,d1-14,d1-15,d1-16,d1-17. FWD/REV Run command; Multi-Step Speed references1,2,3,4; Jog command; ON intervals. Exact selector truth table retained onPDF160; unprinted pulse durations not inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Internal frequency reference; Set frequency reference; Frequency Reference Upper Limit d2-01; Lower Limit d2-02; Operating range. Illustrated reference is clamped between printed limits; no numeric limits supplied by graph. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

u d2: Frequency Upper/Lower Limits

By entering upper or lower frequency limits, the drive programmer can prevent operation of the drive above or below levels that may cause resonance and or equipment damage.

n d2-01: Frequency Reference Upper Limit

Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency references. Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.

No. Parameter Name Setting Range Default

n d2-02: Frequency Reference Lower Limit

Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency references. If a lower reference than this value is input, the drive will run at the d2-02 level. If the drive is started with a lower reference than d2-02, it will accelerate up to d2-02.

5.4 d: Reference Settings

Parameter Details

d2-01 / Frequency Reference Upper Limit — PDF page 161

Source row No. Parameter Name Setting Range Default
1 d2-01 Frequency Reference Upper Limit 0.0 to 110.0% 100.0%

d2-02 / Frequency Reference Lower Limit — PDF page 161

Source row No. Parameter Name Setting Range Default
1 d2-02 Frequency Reference Lower Limit 0.0 to 110.0% 0.0%

Manual — Master limits, Jump Frequency and Hold — page 162

Source reference: SIEP C71060618F, December 2016, physical PDF page 162. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output Frequency; Frequency Reference; Increasing frequency reference / Decreasing frequency reference. Jump Frequency3 d3-03, Jump Frequency2 d3-02, Jump Frequency1 d3-01; each Jump Frequency Width d3-04. Source stepped/hysteresis path retained as diagram; no derived switching values. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

n d2-03: Master Speed Reference Lower Limit

Unlike frequency reference lower limit (d2-02) which will affect the frequency reference no matter where it is sourced from (i.e., analog input, preset speed, Jog speed, etc.), the master speed lower limit (d2-03) sets a lower limit that will only affect the analog input (terminals A1 and A2) that is the active master speed frequency. Set as a percentage of the maximum output frequency.

Note: The lower limits for the Jog frequency, multi-step speed settings, and 2-step speed settings do not change. When lower limits are set to both the frequency reference (d2-02) and the main frequency reference (d2-03), the drive uses the greater of those two values as the lower limit.

No. Parameter Name Setting Range Default

u d3: Jump Frequency

n d3-01 to d3-04: Jump Frequencies 1, 2, 3, and Jump Frequency Width

In order to avoid continuous operation at a speed that causes resonance in driven machinery, the drive can be programmed with three separate Jump frequencies that will not allow continued operation within specific frequency ranges. If the speed reference falls within a Jump frequency dead band, the drive will clamp the frequency reference just below the dead band and only accelerate past it when the frequency reference rises above the upper end of the dead band. Setting parameters d3-01 through d3-03 to 0.0 Hz disables the Jump frequency function.

Figure 5.35 shows the relationship between the Jump frequency and the output frequency.

Note: 1. The drive will use the active accel/decel time to pass through the specified dead band range but will not allow continuous operation in that range. 2. When using more than one Jump frequency, make sure that d3-01 ≥ d3-02 ≥ d3-03.

u d4: Frequency Hold and Up/Down 2 Function

n d4-01: Frequency Reference Hold Function Selection

This parameter is effective when either of the digital input functions listed below is used. • Accel/decel ramp hold function (H1-□□= A)

5.4 d: Reference Settings

d2-03 / Master Speed Reference Lower Limit — PDF page 162

Source row No. Parameter Name Setting Range Default
1 d2-03 Master Speed Reference Lower Limit 0.0 to 110.0% 0.0%

d3-01 / d3-02 / d3-03 / d3-04 — Jump Frequency 1 — PDF page 162

Source row No. Parameter Name Setting Range Default
1 d3-01 Jump Frequency 1 0.0 to 400.0 Hz 0.0 Hz
2 d3-02 Jump Frequency 2 0.0 to 400.0 Hz 0.0 Hz
3 d3-03 Jump Frequency 3 0.0 to 400.0 Hz 0.0 Hz
4 d3-04 Jump Frequency Width 0.0 to 20.0 Hz 1.0 Hz

Manual — Frequency-reference memory modes — page 163

Source reference: SIEP C71060618F, December 2016, physical PDF page 163. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Power supply ON/OFF/ON; Run command OFF/ON/OFF/ON; Accel/Decel Hold input OFF/ON/OFF/ON; Frequency reference / Output frequency; Hold intervals. After power returns, d4-01=1 restores held reference; d4-01=0 line at0. Adjacent source requires hold enabled for restoration. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

• Up/Down function (H1-□□ = 10 and 11, sets the frequency reference by digital inputs) • Up/Down 2 function (H1-□□ = 75/76, adds a bias to the frequency reference using digital inputs) Parameter d4-01 determines whether the frequency reference or the frequency bias (Up/Down 2) value is saved when the Run command is cleared or the power supply is shut down.

No. Parameter Name Setting Range Default

The operation depends on with what function parameter d4-01 is used.

Setting 0: Disabled • Acceleration Hold The hold value will be reset to 0 Hz when the Run command is canceled or the drive power is switched off. The active frequency reference will be the value the drive uses when it restarts. • Up/Down The frequency reference value will be reset to 0 Hz when the Run command is canceled or the drive power is switched off. The drive will start from 0 Hz when restarted. • Up/Down 2 The frequency bias is not saved when the Run command is switched off or 5 s after the Up/Down 2 command has been released. The Up/Down 2 function will start with a bias of 0% when the drive is restarted.

Setting 1: Enabled • Acceleration Hold The last hold value will be saved when the Run command or the drive power is switched off. The drive will use the value that was saved as the frequency reference when it restarts. The accel/decel hold input must be enabled the entire time or else the hold value will be cleared.

• Up/Down The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will use the frequency reference that was saved when it restarts. • Up/Down 2 with Frequency Reference from Digital Operator When the digital operator is selected as the frequency reference source, the bias will be added to the frequency reference that was selected 5 s after the Up/Down 2 command has been released, and then reset to 0 afterwards. The new frequency reference value is then saved. When the Run command or the power supply is switched off, the drive will use the value that was when it restarts.

5.4 d: Reference Settings

Parameter Details

d4-01 / Frequency Reference Hold Function Selection — PDF page 163

Source row No. Parameter Name Setting Range Default
1 d4-01 Frequency Reference Hold Function Selection 0 or 1 0

Manual — Up/Down2 bias memory diagrams — page 164

Source reference: SIEP C71060618F, December 2016, physical PDF page 164. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Frequency reference, Output frequency, Bias, Up2 input; 5s. With d4-01=1, bias is added to the frequency reference5s after release, bias reset to0, and new reference saved. Graph values are conceptual; no unprinted setting inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Frequency reference, Output frequency, Bias, Up2 input;5s; d4-01=1; d4-06 value. Other source bias saved to d4-06 five seconds after release; retained at restart. Actual source-limit settings remain separately qualified. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

• Up/Down 2 with Frequency Reference from Other Input Sources When the frequency reference is set by an another source than the digital operator, the bias value will be saved in parameter d4-06 exactly 5 s after the Up/Down 2 command has been released. When the Run command is turned off or the power is switched off, the drive will use the value saved in d4-06 when it restarts.

Note: Make sure to set the Up/Down 2 limits properly when using d4-01 = 1 in combination with the Up/Down 2 function. Refer to d4-08: Frequency Reference Bias Upper Limit (Up/Down 2) on page 166 and Refer to d4-09: Frequency Reference Bias Lower Limit (Up/ Down 2) on page 167 for details on the limit settings.

Clearing the Value that was Saved Depending on which function is used, the frequency reference value that was saved can be cleared by:

5.4 d: Reference Settings

Manual — Up/Down2 steps and selected ramp time — page 165

Source reference: SIEP C71060618F, December 2016, physical PDF page 165. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency; Bias; Up2 input. Bias ramps while input active; acceleration/deceleration time selected by d4-04. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Output frequency; Bias; Up2 input. Bias changes in d4-03 steps; output frequency ramps according to d4-04. No unprinted step count or rate inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

• Releasing the acceleration hold input. • Setting an Up or Down command while no Run command is active.

n d4-03: Frequency Reference Bias Step (Up/Down 2)

Sets the bias that is added to or subtracted from the frequency reference by the Up/Down 2 function.

No. Parameter Name Setting Range Default

The operation depends on the set value:

Setting d4-03 = 0.0 Hz While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel time determined by parameter d4-04.

Setting d4-03 > 0.0 Hz When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The frequency reference changes with the accel/decel times determined by parameter d4-04.

n d4-04: Frequency Reference Bias Accel/Decel (Up/Down 2)

Parameter d4-04 determines the accel/decel times that are used for increasing/decreasing the frequency reference or bias when the Up/Down 2 function is used.

5.4 d: Reference Settings

Parameter Details

d4-03 / Frequency Reference Bias Step — PDF page 165

Source row No. Parameter Name Setting Range Default
1 d4-03 Frequency Reference Bias Step 0.00 to 99.99 Hz 0.00 Hz

d4-04 / Frequency Reference Bias Accel/Decel — PDF page 165

Source row No. Parameter Name Setting Range Default
1 d4-04 Frequency Reference Bias Accel/Decel 0 or 1 0

Manual — Bias reset, memory and change thresholds — page 166

Source reference: SIEP C71060618F, December 2016, physical PDF page 166. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 0: Current Accel/Decel Time The drive uses the currently active accel/decel time.

Setting 1: Accel/Decel Time 4 The drive uses accel/decel time 4 set to parameters C1-07 and C1-08.

n d4-05: Frequency Reference Bias Operation Mode Selection (Up/Down 2)

Determines if the bias value is held or not when the Up/Down 2 inputs are both released or both enabled. The parameter is effective only when parameter d4-03 is set to 0.00.

No. Parameter Name Setting Range Default

Setting 0: Hold Bias Value The bias value will be held if no input Up 2 or Down 2 is active.

Setting 1: Reset Bias Value The bias is reset to 0% when both inputs Up 2 and Down 2 are either on or off. The drive will use the accel/decel time as selected in d4-04 to accelerate or decelerate to the frequency reference value.

n d4-06: Frequency Reference Bias (Up/Down 2)

This parameter is used to save the frequency reference bias value set by the Up/Down 2 function. It is set as a percentage of the maximum output frequency. The function of d4-06 depends on how the Up/Down 2 function is configured. • This parameter is not normally used when the frequency reference is set by the digital operator. The user can set d4-06 to a certain value that will be applied when the operation is started, but it will be reset when the frequency reference changes (including multi-step references) or will be disabled when d4-01 = 0 and the Run command is removed. • When d4-01 = 0 and the frequency reference is set by an analog or pulse input, the value set in d4-06 is generally added to or subtracted from the frequency reference. • When d4-01 = 1 and the frequency reference is set by a different source than the digital operator, the bias value adjusted with the Up/Down 2 inputs is stored in d4-06 when 5 s have passed after the Up 2 or Down 2 command release.

Conditions that Generally Reset or Disable Parameter d4-06 • When the Up/Down 2 function has not been assigned to the multi-function terminals • When the frequency reference source has been changed (including LOCAL/REMOTE or external reference 1/external reference 2 switch over by digital inputs) • If d4-03 = 0 Hz, d4-05 = 1 and the Up/Down 2 commands are both open or both closed • Any changes to the maximum frequency set to E1-04

n d4-07: Analog Frequency Reference Fluctuation Limit (Up/Down 2)

This parameter is for handling changes in the frequency reference while the terminal set for Up 2 or Down 2 is enabled. If the frequency reference changes for more than the level set to d4-07, then the bias value will be held, and the drive will accelerate or decelerate following the frequency reference. When the frequency reference is reached, the bias hold is released and the bias follows the Up/Down 2 input commands. Parameter d4-07 is applicable only if the frequency reference is set by an analog or pulse input.

n d4-08: Frequency Reference Bias Upper Limit (Up/Down 2)

Parameter d4-08 sets the upper limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter d4-06. Set this parameter to an appropriate value before using the Up/Down 2 function.

Note: When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the frequency reference if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. From that point the bias can be increased up to the limit set in d4-08 again.

5.4 d: Reference Settings

d4-05 / Frequency Reference Bias Operation Mode Selection — PDF page 166

Source row No. Parameter Name Setting Range Default
1 d4-05 Frequency Reference Bias Operation Mode Selection 0 or 1 0

d4-06 / Frequency Reference Bias — PDF page 166

Source row No. Parameter Name Setting Range Default
1 d4-06 Frequency Reference Bias -99.9 to 100.0% 0.0%

d4-07 / Analog Frequency Reference Fluctuation Limit — PDF page 166

Source row No. Parameter Name Setting Range Default
1 d4-07 Analog Frequency Reference Fluctuation Limit 0.1 to 100.0% 1.0%

Manual — Bias limits and Offset Frequencies — page 167

Source reference: SIEP C71060618F, December 2016, physical PDF page 167. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name Setting Range Default

<1> Default setting is determined by the software version. PRG: 1016 and later: 100.00% PRG: 1015 and earlier: 0.00%

n d4-09: Frequency Reference Bias Lower Limit (Up/Down 2)

Parameter d4-08 sets the lower limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter d4-06. Set this parameter to an appropriate value before using the Up/Down 2 function.

Note: When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the frequency reference if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. If the bias is increased using the Up 2 command, once it is added to the frequency reference the speed cannot be reduced with a Down 2 command if the limit set in d4-09 is 0. In this case make sure to set a negative lower limit in d4-09 to allow speed reduction.

n d4-10: Up/Down Frequency Reference Limit Selection

Selects how the lower frequency limit is set when the Up/Down function is used. Refer to Setting 10/11: Up/Down Command on page 187 for details on the Up/Down function in combination with frequency reference limits.

Setting 0: Lower Limit is Determined by d2-02 or Analog Input The lower frequency reference limit is determined by the higher value of both, parameter d2-02 or an analog input that is programmed for “Frequency Bias” (H3-02/10 = 0).

Note: If the external reference change over function (H1-□□ = 2) used to switch between Up/Down function and analog input as reference source, the analog value would become the lower reference limit when the Up/Down reference is active. Change d4-10 to 1 to make the Up/Down function independent of the analog input value.

Setting 1: Lower Limit is Determined by Parameter d2-02 Only parameter d2-02 sets the lower frequency reference limit.

u d7: Offset Frequencies

n d7-01 to d7-03: Offset Frequency 1 to 3

Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed for Offset frequency 1, 2 and 3 (H1-□□ = 44, 45, 46). The selected offset values are added if two or all three inputs are closed at the same time.

Note: This function can be used to replace the “Trim Control” function (H1-□□ = 1C/1D) of earlier Yaskawa drives.

Figure 5.41 illustrates the Offset Frequency Function.

5.4 d: Reference Settings

Parameter Details

d4-08 / Frequency Reference Bias Upper Limit — PDF page 167

Source row No. Parameter Name Setting Range Default
1 d4-08 Frequency Reference Bias Upper Limit 0.0 to 100.0% <1>

d4-09 / Frequency Reference Bias Lower Limit — PDF page 167

Source row No. Parameter Name Setting Range Default
1 d4-09 Frequency Reference Bias Lower Limit -99.9 to 0.0% 0.0%

d7-01 / d7-02 / d7-03 — Offset Frequency 1 — PDF page 167

Source row No. Parameter Name Setting Range Default
1 d7-01 Offset Frequency 1 -100.0 to 100.0% 0%
2 d7-02 Offset Frequency 2 -100.0 to 100.0% 0%
3 d7-03 Offset Frequency 3 -100.0 to 100.0% 0%

Manual — Additive Offset Frequency diagram — page 168

Source reference: SIEP C71060618F, December 2016, physical PDF page 168. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Frequency Reference; Frequency Reference Bias1 d7-01 controlled by Digital Input H1-□□=44; Bias2 d7-02 controlled by H1-□□=45; Bias3 d7-03 controlled by H1-□□=46. Additions to reference; SFS; Frequency reference after Soft Starter. Signed offsets combine when multiple inputs active; exact routing remains original. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

5.4 d: Reference Settings

Manual — Input Voltage and V/f Pattern selection — page 169

Source reference: SIEP C71060618F, December 2016, physical PDF page 169. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

5.5 E: Motor Parameters

E parameters cover V/f pattern and motor data settings.

u E1: V/f Characteristics

n E1-01: Input Voltage Setting

Set the input voltage parameter to the nominal voltage of the AC power supply. This parameter adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.).

NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. Failure to comply could result in improper drive operation.

No. Parameter Name Setting Range Default

<1> The setting range and default value shown here are for 200 V class drives. Double this for 400 V class units.

E1-01 Related Values The input voltage setting determines the over-/undervoltage detection level and the operation levels of the braking transistor as well as the KEB function and the overvoltage suppression function.

Voltage | Setting Value of E1-01

(Approximate Values)

ov Detection Level

BTR Operation Level

Uv Detection Level (L2-05)

Desired DC Bus Voltage during KEB (L2-11)

ov Suppression / Stall Prevention Level (L3-17)

Note: The braking transistor operation levels are valid for the drive internal braking transistor. If an external CDBR braking chopper is used, refer to the instruction manual of that unit.

n V/f Pattern Settings

The drive utilizes a set V/f pattern to determine the appropriate output voltage level for each relative to the frequency reference. There are 15 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern can be set up by programming parameters E1-04 through E1-10. V/f Pattern Setup for V/f Control 1. Set the input voltage for the drive. Refer to E1-01: Input Voltage Setting on page 169. 2. Set the V/f pattern by:

a) choosing one of the 15 preset V/f patterns (E1-03 = 0 to E).

b) select the custom V/f pattern (E1-03 = F, default setting). 3. When using one of the 15 presets, E1-04 through E1-13 are automatically set. Refer to the description below.

For a custom V/f pattern, E1-04 through E1-13 must be adjusted manually. Refer to V/f Pattern Settings E1-04 to E1-13 on page 172. Open Loop Vector Control Setup for IM and PM Motors In OLV only the user defined V/f pattern can be used. Refer to V/f Pattern Settings E1-04 to E1-13 on page 172.

n E1-03: V/f Pattern Selection

This parameter can only be changed when the drive is operating in V/f Control. It allows the user to select the V/f pattern from 15 predefined patterns or to create a custom V/f pattern.

Parameter Details

200 V Class | all settings

400 V Class | setting ≥ 400 V

400 V Class | setting < 400 V

E1-01 <1> / Input Voltage Setting — PDF page 169

Source row No. Parameter Name Setting Range Default
1 E1-01 <1> Input Voltage Setting 155 to 255 V 230 V

E1-01 Related Values (Approximate Values) — PDF page 169

Source row Voltage class Setting value E1-01 Approximate ov detection Approximate BTR operation Approximate Uv detection L2-05 Approximate DC bus KEB L2-11 Approximate ov suppression/Stall Prevention L3-17
1 200 V Class all settings 410 V 394 V 190 V (single-phase = 160 V) 240 V 370 V
2 400 V Class setting ≥ 400 V 820 V 788 V 380 V 480 V 740 V
3 400 V Class setting < 400 V 740 V 708 V 350 V 440 V 660 V

E1-03 / V/f Pattern Selection — PDF page 169

Source row No. Parameter Name Setting Range Default
1 E1-03 V/f Pattern Selection 0 to F F

Manual — Preset V/f patterns and small-power graphs — page 170

Source reference: SIEP C71060618F, December 2016, physical PDF page 170. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

200V class 0.1–3.7kW, setting0. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting1. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting2. Frequency-axis printed labels (Hz):0,1.5,3,50,60. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting3. Frequency-axis printed labels (Hz):0,1.5,3,60,72. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting4. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):8,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting5. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):9,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting6. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):8,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting7. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):9,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Setting the V/f Pattern Choose the V/f pattern that meets the application demands from the table below. Set the correct value to E1-03. The V/f parameters E1-04 to E1-13 can only be monitored, not changed.

Note: 1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation. 2. Parameter E1-03 is not reset when the drive is initialized.

Table 5.16 Predefined V/f Patterns

Setting Specification Characteristic Application

The following tables show details on predefined V/f patterns. The following graphs are for 200 V class drives; double the values for 400 V class drives.

Predefined V/f Patterns for 0.1 to 3.7 kW Drives Table 5.17 Constant Torque Characteristics, Settings 0 to 3

Table 5.18 Derated Torque Characteristics, Settings 4 to 7

5.5 E: Motor Parameters

Table5.16 Predefined V/f Patterns — PDF page 170

Source row Setting Specification Characteristic Application
1 0 50 Hz Constant torque For general purpose applications. Torque remains constant regardless of changes to speed.
2 1 60 Hz (default setting) Constant torque For general purpose applications. Torque remains constant regardless of changes to speed.
3 2 60 Hz (with 50 Hz base) Constant torque For general purpose applications. Torque remains constant regardless of changes to speed.
4 3 72 Hz (with 60 Hz base) Constant torque For general purpose applications. Torque remains constant regardless of changes to speed.
5 4 50 Hz, Heavy Duty 2 Derated torque For fans, pumps, and other applications that require torque derating relative to the load.
6 5 50 Hz, Heavy Duty 1 Derated torque For fans, pumps, and other applications that require torque derating relative to the load.
7 6 60 Hz, Heavy Duty 1 Derated torque For fans, pumps, and other applications that require torque derating relative to the load.
8 7 60 Hz, Heavy Duty 2 Derated torque For fans, pumps, and other applications that require torque derating relative to the load.
9 8 50 Hz, mid starting torque High starting torque Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed
10 9 50 Hz, high starting torque High starting torque Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed
11 A 60 Hz, mid starting torque High starting torque Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed
12 B 60 Hz, high starting torque High starting torque Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed
13 C 90 Hz (with 60 Hz base) Constant output When operating at greater than 60 Hz the output voltage will be constant.
14 D 120 Hz (with 60 Hz base) Constant output When operating at greater than 60 Hz the output voltage will be constant.
15 E 180 Hz (with 60 Hz base) Constant output When operating at greater than 60 Hz the output voltage will be constant.

Manual — Power-specific V/f pattern graphs — page 171

Source reference: SIEP C71060618F, December 2016, physical PDF page 171. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

200V class 0.1–3.7kW, setting8. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):12,19,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, setting9. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):13,24,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, settingA. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):12,19,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, settingB. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):15,24,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, settingC. Frequency-axis printed labels (Hz):0,1.5,3,60,90. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, settingD. Frequency-axis printed labels (Hz):0,1.5,3,60,120. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, settingE. Frequency-axis printed labels (Hz):0,1.5,3,60,180. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 0.1–3.7kW, settingF. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting0. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting1. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting2. Frequency-axis printed labels (Hz):0,1.5,3,50,60. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting3. Frequency-axis printed labels (Hz):0,1.5,3,60,72. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting4. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):6,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting5. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):7,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting6. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):6,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting7. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):7,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting8. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):9,18,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, setting9. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):11,23,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, settingA. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):9,18,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, settingB. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):13,23,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Table 5.19 High Starting Torque, Settings 8 to B

Table 5.20 Rated Output Operation, Settings C to F

Predefined V/f Patterns for 5.5 to 18.5 kW Drives The following graphs are for 200 V class drives. Double values when using a 400 V class drive.

Table 5.21 Rated Torque Characteristics, Settings 0 to 3

Table 5.22 Derated Torque Characteristics, Settings 4 to 7

Table 5.23 High Starting Torque, Settings 8 to B

5.5 E: Motor Parameters

Parameter Details

Manual — Custom V/f settings, graphs and qualifications — page 172

Source reference: SIEP C71060618F, December 2016, physical PDF page 172. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output Voltage: E1-05,E1-12,E1-13,E1-08,E1-10; Frequency:E1-09,E1-07,E1-06,E1-11,E1-04. Visible point pairs E1-09/E1-10, E1-07/E1-08, E1-06/E1-13, E1-11/E1-12, E1-04/E1-05. Full unit and mode footnotes apply; no interpolated values. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, settingC. Frequency-axis printed labels (Hz):0,1.5,3,60,90. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, settingD. Frequency-axis printed labels (Hz):0,1.5,3,60,120. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, settingE. Frequency-axis printed labels (Hz):0,1.5,3,60,180. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

200V class 5.5–18.5kW, settingF. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

Table 5.24 Constant Output, Settings C to F

Setting a Custom V/f Pattern Setting parameter E1-03 to “F” allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13. When E1-03 is changed to “F”, the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 1 of the predefined patterns.

n V/f Pattern Settings E1-04 to E1-13

Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if E1-03 =< 15 or set up a custom V/f pattern as shown in Figure 5.42 when E1-03 = F.

No. Parameter Name Setting Range Default

<1> Default setting is determined by the control mode. <2> Values shown are for 200 V class drives; double the value when using 400 V class drives. <3> In OLV for PM E1-09 specifies the start frequency for short circuit braking at stop. Refer to b2-13: Short Circuit Brake Time at Stop on page 129 for details. <4> When E1-13 is set to 0.0 V, the drive uses the value set in E1-05 to control the voltage. <5> Default setting is determined by E5-01 in OLV/PM. When E5-01 is set to FFFFH, the setting range for E1-04 and E1-06 is 10.0 to 40.0 Hz and the setting range for E1-09 is 0.0 to 400.0 Hz.

Note: 1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

5.5 E: Motor Parameters

E1-04 / E1-05 / E1-06 / E1-07 / E1-08 / E1-09 <3> / E1-10 / E1-11 / E1-12 / E1-13 <4> — Maximum Output Frequency — PDF page 172

Source row No. Parameter Name Setting Range Default
1 E1-04 Maximum Output Frequency 40.0 to 400.0 Hz <5> <1>
2 E1-05 Maximum Voltage 0.0 to 255.0 V <2> <1>
3 E1-06 Base Frequency 0.0 to 400.0 Hz <5> <1>
4 E1-07 Middle Output Frequency 0.0 to 400.0 Hz <1>
5 E1-08 Middle Output Frequency Voltage 0.0 to 255.0 V <2> <1>
6 E1-09 <3> Minimum Output Frequency 0.0 to 400.0 Hz <5> <1>
7 E1-10 Minimum Output Frequency Voltage 0.0 to 255.0 V <2> <1>
8 E1-11 Middle Output Frequency 2 0.0 to 400.0 Hz 0.0 Hz
9 E1-12 Middle Output Frequency Voltage 2 0.0 to 255.0 V <2> 0.0 V
10 E1-13 <4> Base Voltage 0.0 to 255.0 Hz 0.0 V

Manual — Motor1 data, slip and resistance — page 173

Source reference: SIEP C71060618F, December 2016, physical PDF page 173. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

  1. Setting E1-11 to 0 disables both E1-11 and E1-12 and the above conditions do not apply. 3. To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded. 4. E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned to their default values.

u E2: Motor 1 Parameters

These parameters contain the most important motor data needed for optimal motor control. The parameters are set automatically during Auto-Tuning. Set the parameters manually when Auto-Tuning cannot be performed.

n E2-01: Motor Rated Current

Set E2-01 to the full load amps (FLA) stamped on the motor nameplate. During Auto-Tuning the value must be entered to parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E2-01.

No. Parameter Name Setting Range Default

Note: 1. Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. 2. Change E2-01 only after changing the value set to E2-03. Setting E2-01 < E2-03 will trigger an oPE02 error.

n E2-02: Motor Rated Slip

Sets the motor rated slip in Hz. This value is automatically set during Rotational Auto-Tuning.

If Auto-Tuning cannot be performed calculate the motor rated slip using the information written on the motor nameplate and the formula below: E2-02 = f - (n x p)/120 (f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)

n E2-03: Motor No-Load Current

Set E2-03 to the motor no-load current at rated voltage and rated frequency. If Rotational Auto-Tuning completes successfully, this value is automatically calculated. If Auto-Tuning cannot be performed, contact the motor manufacturer for information about the no-load current.

Note: Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.

n E2-04: Number of Motor Poles

Set the number of motor poles to E2-04. This value must be entered during Auto-Tuning, and will automatically be saved to E2-04 if Auto-Tuning completes successfully.

n E2-05: Motor Line-to-Line Resistance

Sets the line-to-line resistance of the motor stator winding. If the Auto-Tuning completes successfully, this value is automatically calculated. Remember this value must be entered as line-line and not line-neutral.

Note: The setting range becomes 0.00 to 130.00 when using BA0002, 2A0002, 4A0001 and smaller.

5.5 E: Motor Parameters

Parameter Details

E2-01 / Motor Rated Current — PDF page 173

Source row No. Parameter Name Setting Range Default
1 E2-01 Motor Rated Current 10% to 200% of the drive rated current. (unit: 0.01 A) Depending on o2-04

E2-02 / Motor Rated Slip — PDF page 173

Source row No. Parameter Name Setting Range Default
1 E2-02 Motor Rated Slip 0.00 to 20.00 Hz Depending on o2-04

E2-03 / Motor No-Load Current — PDF page 173

Source row No. Parameter Name Setting Range Default
1 E2-03 Motor No-Load Current 0 to [E2-01] (unit: 0.01 A) Depending on o2-04

E2-04 / Number of Motor Poles — PDF page 173

Source row No. Parameter Name Setting Range Default
1 E2-04 Number of Motor Poles 2 to 48 poles 4 poles

E2-05 / Motor Line-to-Line Resistance — PDF page 173

Source row No. Parameter Name Setting Range Default
1 E2-05 Motor Line-to-Line Resistance 0.000 to 65.000 Ω Depending on o2-04

Manual — Motor1 loss and saturation parameters — page 174

Source reference: SIEP C71060618F, December 2016, physical PDF page 174. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

If Auto-Tuning is not possible, then contact the motor manufacturer to find out the line-to-line resistance or measure it manually. When using the manufacturer Motor Test Report, calculate E2-05 by the formulas below. • E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C • B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C. • F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the Test Report at 115 °C.

n E2-06: Motor Leakage Inductance

Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.

No. Parameter Name Setting Range Default

n E2-07: Motor Iron-Core Saturation Coefficient 1

This parameter sets the motor iron saturation coefficient at 50% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then this value is automatically calculated.

n E2-08: Motor Iron-Core Saturation Coefficient 2

This parameter sets the motor iron saturation coefficient at 75% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then this value is automatically calculated.

n E2-09: Motor Mechanical Loss

This parameter sets to the motor mechanical loss as a percentage of motor rated power (kW) capacity.

Adjust this setting in the following circumstances: • When there is a large amount of torque loss due to motor bearing friction. • When there is a large amount of torque loss in a fan or pump application. The setting for the mechanical loss is added to the torque.

n E2-10: Motor Iron Loss for Torque Compensation

This parameter sets the motor iron loss in watts.

n E2-11: Motor Rated Power

This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto- Tuning completes successfully, the value entered will automatically be saved to E2-11.

n E2-12: Motor Iron-Core Saturation Coefficient 3

This parameter sets the motor iron saturation coefficient at 130% of the magnetic flux.

5.5 E: Motor Parameters

E2-06 / Motor Leakage Inductance — PDF page 174

Source row No. Parameter Name Setting Range Default
1 E2-06 Motor Leakage Inductance 0.0 to 40.0% Depending on o2-04

E2-07 / Motor Iron-Core Saturation Coefficient 1 — PDF page 174

Source row No. Parameter Name Setting Range Default
1 E2-07 Motor Iron-Core Saturation Coefficient 1 0.00 to 0.50 0.50

E2-08 / Motor Iron-Core Saturation Coefficient 2 — PDF page 174

Source row No. Parameter Name Setting Range Default
1 E2-08 Motor Iron-Core Saturation Coefficient 2 E2-07 to 0.75 0.75

E2-09 / Motor Mechanical Loss — PDF page 174

Source row No. Parameter Name Setting Range Default
1 E2-09 Motor Mechanical Loss 0.0 to 10.0% 0.0%

E2-10 / Motor Iron Loss for Torque Compensation — PDF page 174

Source row No. Parameter Name Setting Range Default
1 E2-10 Motor Iron Loss for Torque Compensation 0 to 65535 W Depending on o2-04

E2-11 / Motor Rated Power — PDF page 174

Source row No. Parameter Name Setting Range Default
1 E2-11 Motor Rated Power 0.00 to 650.00 kW Depending on o2-04

E2-12 / Motor Iron-Core Saturation Coefficient 3 — PDF page 174

Source row No. Parameter Name Setting Range Default
1 E2-12 Motor Iron-Core Saturation Coefficient 3 1.30 to 5.00 1.30

Manual — Motor2 control and V/f pattern — page 175

Source reference: SIEP C71060618F, December 2016, physical PDF page 175. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output Voltage:E3-05,E3-12,E3-13,E3-08,E3-10; Frequency:E3-09,E3-07,E3-06,E3-11,E3-04. Point labels retained without deriving intermediate voltage; source voltage-class and mode footnotes apply. Source diagram geometry, exact routing and unprinted numerical values remain original-only.

u E3: V/f Characteristics for Motor 2

These parameters set the V/f pattern used for motor 2. Refer to Setting 16: Motor 2 Selection on page 189 for details on switching motors.

n E3-01: Motor 2 Control Mode Selection

Selects the control mode for motor 2. Motor 2 cannot be used in OLV/PM control mode.

No. Parameter Name Setting Range Default

Setting 0: V/f Control

Setting 2: Open Loop Vector Control

n E3-04 to E3-13

Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 like shown in Figure 5.43.

<1> Values shown here are for 200 V class drives. Multiply voltage values by 1.15 for U-spec drives. Double the value when using 400 V class drives. <2> Default setting is determined by the control mode for motor 2.

Note: 1. The following condition must be true when setting up the V/f pattern: E3-09 ≤ E3-07 ≤ E3-06 ≤ E3-11 ≤ E3-04 2. To make the V/f pattern a straight line set E3-09 = E3-07. In this case the E3-08 setting is disregarded.

5.5 E: Motor Parameters

Parameter Details

E3-01 / Motor 2 Control Mode Selection — PDF page 175

Source row No. Parameter Name Setting Range Default
1 E3-01 Motor 2 Control Mode Selection 0 or 2 0

E3-04 / E3-05 / E3-06 / E3-07 / E3-08 / E3-09 / E3-10 / E3-11 / E3-12 / E3-13 — Motor 2 Max Output Frequency — PDF page 175

Source row No. Parameter Name Setting Range Default
1 E3-04 Motor 2 Max Output Frequency 40.0 to 400.0 Hz 60.0 Hz
2 E3-05 Motor 2 Max Voltage 0.0 to 255.0 V <1> 230.0 V <1>
3 E3-06 Motor 2 Base Frequency 0.0 to 400.0 Hz 60.0 Hz
4 E3-07 Motor 2 Mid Output Frequency 0.0 to 400.0 Hz <2>
5 E3-08 Motor 2 Mid Output Frequency Voltage 0.0 to 255.0 V <1> <2>
6 E3-09 Motor 2 Minimum Output Frequency 0.0 to 400.0 Hz <2>
7 E3-10 Motor 2 Minimum Output Frequency Voltage 0.0 to 255.0 V <1> <2>
8 E3-11 Motor 2 Mid Output Frequency 2 0.0 to 400.0 Hz 0.0 Hz
9 E3-12 Motor 2 Mid Output Frequency Voltage 2 0.0 to 255.0 V <1> 0.0 Vac
10 E3-13 Motor 2 Base Voltage 0.0 to 255.0 V <1> 0.0 Vac

Manual — Motor2 current, slip and resistance — page 176

Source reference: SIEP C71060618F, December 2016, physical PDF page 176. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u E4: Motor 2 Parameters

E4 parameters contain the motor data for motor 2. These parameters are usually set automatically during the Auto-Tuning process. They may need to be set manually if there is a problem performing Auto-Tuning.

n E4-01: Motor 2 Rated Current

Set E4-01 to the full load amps (FLA) stamped on the nameplate of motor 2. During Auto-Tuning the value must be entered to parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E4-01.

No. Parameter Name Setting Range Default

Note: Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.

n E4-02: Motor 2 Rated Slip

This parameter sets the motor 2 rated slip frequency. The drive calculates this value automatically during Rotational Auto- Tuning. For information on calculating the motor rated slip, see the description for E2-02.

n E4-03: Motor 2 Rated No-Load Current

Set E4-03 to the motor no-load current at rated voltage and rated frequency. If Rotational Auto-Tuning completes successfully, this value is automatically calculated. If Auto-Tuning cannot be performed contact the motor manufacturer for information about the no-load current.

n E4-04: Motor 2 Motor Poles

Set the pole number of motor 2 to E4-04. During Auto-Tuning the value must entered to parameter T1-06. If Auto-Tuning completes successfully, the entered value will automatically be saved to E4-04.

n E4-05: Motor 2 Line-to-Line Resistance

Sets the line-to-line resistance of motor 2 stator winding. If the Auto-tuning completes successfully, this value is automatically calculated. Remember this value must be entered as line-line and not line-neutral.

Note: The setting range is 0.00 to 130.00 when using a drive capacity of 0.2 kW or less. Refer to E2-05: Motor Line-to-Line Resistance on page 173 to manually enter this parameter setting.

n E4-06: Motor 2 Leakage Inductance

Sets the voltage drop due to motor leakage inductance of motor 2. The value is set as a percentage of the rated voltage.

5.5 E: Motor Parameters

E4-01 / Motor 2 Rated Current — PDF page 176

Source row No. Parameter Name Setting Range Default
1 E4-01 Motor 2 Rated Current 10 to 200% of the drive rated current. Depending on o2-04

E4-02 / Motor 2 Rated Slip — PDF page 176

Source row No. Parameter Name Setting Range Default
1 E4-02 Motor 2 Rated Slip 0.00 to 20.00 Hz Depending on o2-04

E4-03 / Motor 2 Rated No-Load Current — PDF page 176

Source row No. Parameter Name Setting Range Default
1 E4-03 Motor 2 Rated No-Load Current 0 to [E4-01] Depending on o2-04

E4-04 / Motor 2 Motor Poles — PDF page 176

Source row No. Parameter Name Setting Range Default
1 E4-04 Motor 2 Motor Poles 2 to 48 4

E4-05 / Motor 2 Line-to-Line Resistance — PDF page 176

Source row No. Parameter Name Setting Range Default
1 E4-05 Motor 2 Line-to-Line Resistance 0.000 to 65.000 Ω Depending on o2-04

E4-06 / Motor 2 Leakage Inductance — PDF page 176

Source row No. Parameter Name Setting Range Default
1 E4-06 Motor 2 Leakage Inductance 0.0 to 40.0% Depending on o2-04

Manual — Motor2 losses, saturation and compensation — page 177

Source reference: SIEP C71060618F, December 2016, physical PDF page 177. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n E4-07: Motor 2 Motor Iron-Core Saturation Coefficient 1

Sets the motor 2 iron saturation coefficient at 50% of magnetic flux. This value is automatically set during Rotational Auto- Tuning.

No. Parameter Name Setting Range Default

n E4-08: Motor 2 Motor Iron-Core Saturation Coefficient 2

Sets the motor iron saturation coefficient at 75% of magnetic flux. This value is automatically set during Rotational Auto- Tuning.

n E4-09: Motor 2 Mechanical Loss

Sets the motor mechanical loss as a percentage of motor rated power (kW).

This parameter seldom needs to be changed, but may need to be adjusted in the following circumstances: • When there is a large amount of torque loss due to motor bearing friction. • When there is a large amount of torque loss in a fan or pump application.

n E4-10: Motor 2 Iron Loss

Sets the motor 2 iron loss in watts.

n E4-11: Motor 2 Rated Power

Sets the motor 2 rated power. During Auto-Tuning the value must entered to parameter T1-02. If Auto-Tuning completes successfully, the entered value will automatically be saved to E4-11.

n E4-12: Motor 2 Iron-Core Saturation Coefficient 3

Sets the motor 2 iron saturation coefficient at 130% of magnetic flux.

n E4-14: Motor 2 Slip Compensation Gain

Instead of C3-01 the value of E4-14 is used as gain for slip compensation when motor 2 is selected. Refer to C3-01: Slip Compensation Gain on page 151 for details and setting instructions.

n E4-15: Motor 2 Torque Compensation Gain

Instead of C4-01 the value of E4-15 is used as gain for torque compensation when motor 2 is selected. Refer to C4-01: Torque Compensation Gain on page 152 for details and setting instructions.

5.5 E: Motor Parameters

Parameter Details

E4-07 / Motor 2 Motor Iron-Core Saturation Coefficient 1 — PDF page 177

Source row No. Parameter Name Setting Range Default
1 E4-07 Motor 2 Motor Iron-Core Saturation Coefficient 1 0.00 to 0.50 0.50

E4-08 / Motor 2 Motor Iron-Core Saturation Coefficient 2 — PDF page 177

Source row No. Parameter Name Setting Range Default
1 E4-08 Motor 2 Motor Iron-Core Saturation Coefficient 2 [E4-07] to 0.75 0.75

E4-09 / Motor 2 Mechanical Loss — PDF page 177

Source row No. Parameter Name Setting Range Default
1 E4-09 Motor 2 Mechanical Loss 0.00 to 10.0% 0.0%

E4-10 / Motor 2 Iron Loss — PDF page 177

Source row No. Parameter Name Setting Range Default
1 E4-10 Motor 2 Iron Loss 0 to 65535 W Depending on o2-04

E4-11 / Motor 2 Rated Power — PDF page 177

Source row No. Parameter Name Setting Range Default
1 E4-11 Motor 2 Rated Power 0.00 to 650.00 kW Depending on o2-04

E4-12 / Motor 2 Iron-Core Saturation Coefficient 3 — PDF page 177

Source row No. Parameter Name Setting Range Default
1 E4-12 Motor 2 Iron-Core Saturation Coefficient 3 1.30 to 5.00 1.30

E4-14 / Motor 2 Slip Compensation Gain — PDF page 177

Source row No. Parameter Name Setting Range Default
1 E4-14 Motor 2 Slip Compensation Gain 0.0 to 2.50 Depending on E3-01

Manual — PM motor code and basic ratings — page 178

Source reference: SIEP C71060618F, December 2016, physical PDF page 178. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Illustration 0000. First character:0 Pico Motor (SMRA Series);1 Derated Torque for IPM Motors (SSR1 Series). Second character:0 1800r/min Series;1 3600r/min Series;2 1750r/min Series;3 1450r/min Series;4 1150r/min Series;F Special Motor. Remaining two characters: Motor Voltage Class and Capacity. No unprinted voltage/capacity code mappings inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

No. Parameter Name Setting Range Default

u E5: PM Motor Settings

These parameters set the motor data of a PM motor used in OLV for PM (A1-02 = 5). When Yaskawa motors are used, entering the motor code written on the motor nameplate will set up the E5-□□ parameters. For all other PM motors, the data must be entered manually.

n E5-01: PM Motor Code Selection

Set the motor code for the PM motor being used. Depending on the motor code entered, the drive automatically sets several parameters to appropriate values. Refer to Parameters that Change with the Motor Code Selection on page 417 for details on the supported motor codes and their parameter settings.

Note: 1. This parameter is not reset when the drive is initialized using parameter A1-03. 2. The default setting is for a Yaskawa SMRA Series SPM Motor with a speed rating of 1800 r/min. 3. Changing the motor code setting resets all E5-□□ settings to their default values. 4. Set to “FFFF” when using a non-Yaskawa PM motor or one that is not supported by the motor code settings. Figure 5.44 explains the motor code setting.

n E5-02: Motor Rated Power (PM OLV)

Sets the rated power of the motor.

Note: This parameter is not reset when the drive is initialized using A1-03.

n E5-03: Motor Rated Current (PM OLV)

Sets the motor rated current in amps.

Note: 1. Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. 2. This parameter is not reset when the drive is initialized using A1-03.

n E5-04: Number of Motor Poles (PM OLV)

Sets the number of motor poles.

5.5 E: Motor Parameters

E4-15 / Motor 2 Torque Compensation Gain — PDF page 178

Source row No. Parameter Name Setting Range Default
1 E4-15 Motor 2 Torque Compensation Gain 0.0 to 2.50 1.00

E5-01 / PM Motor Code Selection — PDF page 178

Source row No. Parameter Name Setting Range Default
1 E5-01 PM Motor Code Selection 0000 to FFFF Depending on o2-04

E5-02 / Motor Rated Power — PDF page 178

Source row No. Parameter Name Setting Range Default
1 E5-02 Motor Rated Power 0.10 to 18.50 kW Depending on E5-01

E5-03 / Motor Rated Current — PDF page 178

Source row No. Parameter Name Setting Range Default
1 E5-03 Motor Rated Current 10 to 200% of drive rated current Depending on E5-01

E5-04 / Number of Motor Poles — PDF page 178

Source row No. Parameter Name Setting Range Default
1 E5-04 Number of Motor Poles 2 to 48 Depending on E5-01

Manual — PM resistance, inductance and voltage constants — page 179

Source reference: SIEP C71060618F, December 2016, physical PDF page 179. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n E5-05: Motor Stator Resistance (PM OLV)

Set the resistance for each motor phase (not line-to-line resistance). When measuring the resistance manually make sure to enter the resistance of one phase into E5-05.

No. Parameter Name Setting Range Default

Note: This parameter is not reset when the drive is initialized using A1-03.

n E5-06: Motor d Axis Inductance (PM OLV)

Sets the d axis inductance in units of 0.01 mH. Contact the motor manufacturer for d-axis inductance. If an LCR meter is available, enter half the value of the measurement taken.

n E5-07: Motor q Axis Inductance (PM OLV)

Sets the q axis inductance in units of 0.01 mH. Contact the motor manufacturer for d-axis inductance. If an LCR meter is available, enter half the value of the measurement taken.

n E5-09: Motor Induction Voltage Constant 1 (PM OLV)

Set the induced phase peak voltage in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an SSR1 series IPM motor with derated torque or an SST4 series motor with constant torque. When E5-01 is set to “FFFF” use either E5-09 or E5-24 for setting the voltage constant.

Note: 1. Ensure that E5-24 = 0 when setting parameter E5-09. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or if neither parameter is set to 0. 2. This parameter is not reset when the drive is initialized using A1-03.

n E5-24: Motor Induction Voltage Constant 2 (PM OLV)

Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter to 0 when using an SMRA Series SPM Motor. When E5-01 is set to “FFFF” use either E5-09 or E5-24 for setting the voltage constant.

<1> Range depends on the drive software version. PRG: 1018 and later: 0.0 to 6500.0 mV/(r/min) PRG: 1017 and earlier: 0.0 to 2000.0 mV/(r/min)

Note: 1. If E5-03 is not set to 0, then setting both E5-09 and E5-24 to 0, or setting neither E5-09 nor E5-24 to 0, will trigger an oPE08 error. However, if E5-03 is set to 0, setting both E5-09 and E5-24 to 0 will not trigger the error. 2. This parameter is not reset when the drive is initialized using A1-03. 3. The values for the electrical and mechanical angle should be set using the same units specified by the manufacturer of the motor.

n E5-39: Current Detection Delay Time

Sets the current detection delay time of d-Axis and q-Axis current feedback calculation.

5.5 E: Motor Parameters

Parameter Details

E5-05 / Motor Stator Resistance — PDF page 179

Source row No. Parameter Name Setting Range Default
1 E5-05 Motor Stator Resistance 0.000 to 65.000 Ω Depending on E5-01

E5-06 / Motor d Axis Inductance — PDF page 179

Source row No. Parameter Name Setting Range Default
1 E5-06 Motor d Axis Inductance 0.00 to 300.00 mH Depending on E5-01

E5-07 / Motor q Axis Inductance — PDF page 179

Source row No. Parameter Name Setting Range Default
1 E5-07 Motor q Axis Inductance 0.00 to 600.00 mH Depending on E5-01

E5-09 / Motor Induction Voltage Constant 1 — PDF page 179

Source row No. Parameter Name Setting Range Default
1 E5-09 Motor Induction Voltage Constant 1 0.0 to 2000.0 mV/(rad/s) Depending on E5-01

E5-24 / Motor Induction Voltage Constant 2 (PM OLV) — PDF page 179

Source row No. Parameter Name Setting Range Default
1 E5-24 Motor Induction Voltage Constant 2 (PM OLV) <1> Depending on E5-01

Manual — PM current calculation delay — page 180

Source reference: SIEP C71060618F, December 2016, physical PDF page 180. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Changing this parameter from the default setting is not normally required.

Note: Parameter available in drive software versions PRG: 1022 and later.

No. Parameter Name Setting Range Default

5.5 E: Motor Parameters

E5-39 / Current Detection Delay Time — PDF page 180

Source row No. Parameter Name Setting Range Default
1 E5-39 Current Detection Delay Time -1000 to 1000 µs 0 µs

Manual — PG fault operations and detection thresholds — page 181

Source reference: SIEP C71060618F, December 2016, physical PDF page 181. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

5.6 F: Option Settings

u F1: Error Detection for V/f Control with PG

A one-track pulse signal can be connected to the drive pulse train input RP as speed feedback. Using this signal for slip compensation improves the speed control accuracy. This function is only available for motor 1. The F1 parameters determine how the error detection for the speed feedback signal works. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details on how to activate and tune the function.

n Operation at PG Fault Detection

The drive lets the user select from one of four possible operations when a fault occurs with the PG encoder. The operation can be set up separately for each fault using parameters F1-02/03/04. The table below list the stopping methods and the parameter setting values.

Table 5.25 Stopping Methods for PGo, oS, dEv Detection

Description Setting

NOTICE: Setting = 3: Alarm only will provide an alarm only while continuing to run the motor during abnormal PG fault conditions. This may cause damage to machinery. Use caution when selecting this setting.

n F1-02: Operation Selection at PG Open Circuit (PGo)

Sets the stopping method when a PG open circuit fault (PGo) occurs. Refer to Table 5.25 for setting explanations.

No. Parameter Name Setting Range Default

n F1-03: Operation Selection at Overspeed

Sets the stopping method when an overspeed (oS) fault occurs. Refer to Table 5.25 for setting explanations.

n F1-04: Operation Selection at Deviation

Sets the stopping method when a speed deviation (dEv) fault occurs. Refer to Table 5.25 for setting explanations.

n F1-08/F1-09: Overspeed Detection Level/Delay Time

F1-08 sets the detection level for an overspeed (oS) fault as a percentage of the maximum output frequency. The speed feedback has to exceed this level for longer than the time set in F1-09 before a fault is detected.

n F1-10/F1-11: Excessive Speed Deviation Detection Level/Delay Time

F1-10 sets the detection level for a speed deviation (dEv) fault as a percentage of the maximum output frequency. The speed feedback has to exceed this level for longer than the time set in F1-11 before a fault is detected. Speed deviation is the difference between actual motor speed and the frequency reference command.

Parameter Details

Table5.25 Stopping Methods for PGo, oS, dEv Detection — PDF page 181

Source row Description Setting
1 Ramp to Stop (uses the deceleration time set to C1-02) 0
2 Coast to Stop 1
3 Fast-stop (uses the Fast-stop time set to C1-09) 2
4 Alarm only 3

F1-02 / Operation Selection at PG Open Circuit (PGo) — PDF page 181

Source row No. Parameter Name Setting Range Default
1 F1-02 Operation Selection at PG Open Circuit (PGo) 0 to 3 1

F1-03 / Operation Selection at Overspeed (oS) — PDF page 181

Source row No. Parameter Name Setting Range Default
1 F1-03 Operation Selection at Overspeed (oS) 0 to 3 1

F1-04 / Operation Selection at Deviation (dEv) — PDF page 181

Source row No. Parameter Name Setting Range Default
1 F1-04 Operation Selection at Deviation (dEv) 0 to 3 3

F1-08 / F1-09 — Overspeed Detection Level — PDF page 181

Source row No. Parameter Name Setting Range Default
1 F1-08 Overspeed Detection Level 0 to 120% 115%
2 F1-09 Overspeed Detection Delay Time 0.0 to 2.0 s 1.0 s

Manual — Communications fault actions and detection — page 182

Source reference: SIEP C71060618F, December 2016, physical PDF page 182. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name Setting Range Default

n F1-14: PG Open-Circuit Detection Time

Sets the time required to detect PGo if no pulse signal is present at terminal RP.

u F6: Serial Communications Option Card Settings

These parameters configure communication option cards and communication fault detection methods.

n F6-01: Communications Error Operation Selection

Determines drive operation if a communication error occurs.

Setting 0: Ramp to Stop Using Current Accel/Decel Time

Setting 1: Coast to Stop

Setting 2: Fast-stop Using C1-09

Setting 3: Alarm Only, Continue Operation

Setting 4: Alarm and Run at d1-04 Note: Take proper safety measures, such as installing an emergency stop switch, as the drive will continue operation when detecting an bUS error.

Setting 5: Alarm and Ramp to stop

n F6-02: External Fault from Comm. Option Detection Selection

Determines the detection method of an external fault initiated by a communication option (EF0).

Setting 0: Always Detected

Setting 1: Detection During Run Only

n F6-03: External Fault from Comm. Option Operation Selection

Determines the operation when an external fault is initiated by a communication option (EF0).

n F6-07: NetRef/ComRef Function Selection

Selects how multi-step speed inputs are treated when the NetRef command is set.

5.6 F: Option Settings

F1-10 / F1-11 — Excessive Speed Deviation Detection Level — PDF page 182

Source row No. Parameter Name Setting Range Default
1 F1-10 Excessive Speed Deviation Detection Level 0 to 50% 10%
2 F1-11 Excessive Speed Deviation Detection Delay Time 0.0 to 10.0 s 0.5 s

F1-14 / PG Open-Circuit Detection Time — PDF page 182

Source row No. Parameter Name Setting Range Default
1 F1-14 PG Open-Circuit Detection Time 0.0 to 10.0 s 2.0 s

F6-01 / Communications Error Operation Selection — PDF page 182

Source row No. Parameter Name Setting Range Default
1 F6-01 Communications Error Operation Selection 0 to 5 1

F6-02 / External Fault from Comm. Option Selection — PDF page 182

Source row No. Parameter Name Setting Range Default
1 F6-02 External Fault from Comm. Option Selection 0 or 1 0

F6-03 / External Fault from Comm. Option Operation Selection — PDF page 182

Source row No. Parameter Name Setting Range Default
1 F6-03 External Fault from Comm. Option Operation Selection 0 to 3 1

Manual — Option resets and communications scopes — page 183

Source reference: SIEP C71060618F, December 2016, physical PDF page 183. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Parameter Name Setting Range Default

Setting 0: Multi-Step Speed Operation Disabled If the NetRef command is selected, multi-step speed input frequency references are disabled. This is the same as Yaskawa F7 drives.

Setting 1: Multi-Step Speed Operation Enabled Multi-step speed inputs are active and can override the frequency reference from the communications option even when the NetRef command is selected. This is the same as Yaskawa F7 drives.

n F6-08: Reset Communication Parameters

Determines whether communication-related parameters (F6-□□ and F7-□□) are reset when the drive is initialized using A1-03.

Setting 0: Do Not Reset Parameters F6-□□ and F7-□□ when the Drive Is Initialized with A1-03 Setting 1: Reset F6-□□ and F7-□□ when the Drive Is Initialized with A1-03 Note: F6-08 is not reset when the drive is initialized, but does determine whether initializing the drive with A1-03 resets communication parameters F6-□□ and F7-□□.

u MECHATROLINK-II Parameters

Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK-II network. Refer to the option manual for details on parameter settings.

u MECHATROLINK-III Parameters

Parameters F6-20, F6-21, and F6-23 through F6-26 set up the drive to operate on a MECHATROLINK-III network. Refer to the option manual for details on parameter settings.

u PROFIBUS-DP Parameters

Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network. Refer to the option manual for details on parameter settings.

u DeviceNet Parameters

Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network. Refer to the option manual for details on parameter settings.

u F7-01 to F7-42: EtherNet/IP and Modbus TCP/IP Option Parameters

F7-□□ parameters are reserved for use with SI-EN3/V and SI-EM3/V options. Refer to the Option Installation Manuals for details.

5.6 F: Option Settings

Parameter Details

F6-07 / NetRef/ComRef Function Selection — PDF page 183

Source row No. Parameter Name Setting Range Default
1 F6-07 NetRef/ComRef Function Selection 0 or 1 0

F6-08 / Reset Communication Parameters — PDF page 183

Source row No. Parameter Name Setting Range Default
1 F6-08 Reset Communication Parameters 0 or 1 0

Manual — Digital-input assignments and function index — page 184

Source reference: SIEP C71060618F, December 2016, physical PDF page 184. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

5.7 H: Terminal Functions

H parameters are used to assign functions to the external terminals.

u H1: Multi-Function Digital Inputs

n H1-01 to H1-07: Functions for Terminals S1 to S7

These parameters assign functions to the multi-function digital inputs. Settings 0 to 9F determine function for each terminal and are explained below.

Note: 1. Terminals that are not used and terminals using the through-mode should be set to “F”. 2. Drive software versions PRG: 1013 and later require that the Forward run and Reverse Run commands be set simultaneously.

No. | Parameter Name | Setting Range | Default

<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.

Table 5.26 Digital Multi-Function Input Settings

Setting Function Page

H1-01 to H1-07 Digital Input Terminal Assignments — PDF page 184

Source row No. Parameter Name Setting Range Default
1 H1-01 Digital Input S1 Function Selection 1 to 9F 40: Forward Run Command (2-wire sequence)
2 H1-02 Digital Input S2 Function Selection 1 to 9F 41: Reverse Run Command (2-wire sequence)
3 H1-03 Digital Input S3 Function Selection 0 to 9F 24: External Fault (N.O., always detected, coast to stop)
4 H1-04 Digital Input S4 Function Selection 0 to 9F 14: Fault Reset
5 H1-05 Digital Input S5 Function Selection 0 to 9F 3 (0) <1> : Multi-Step Speed Reference 1
6 H1-06 Digital Input S6 Function Selection 0 to 9F 4 (3) <1> : Multi-Step Speed Reference 2
7 H1-07 Digital Input S7 Function Selection 0 to 9F 6 (4) <1> : Jog Reference Selection

Table5.26 Digital Multi-Function Input Settings left — PDF page 184

Source row Setting Function Page
1 0 3-Wire Sequence 185
2 1 LOCAL/REMOTE Selection 185
3 2 External Reference 1/2 186
4 3 Multi-Step Speed Reference 1 186
5 4 Multi-Step Speed Reference 2 186
6 5 Multi-Step Speed Reference 3 186
7 6 Jog Reference Selection 186
8 7 Accel/Decel Time 1 186
9 8 Baseblock Command (N.O.) 186
10 9 Baseblock Command (N.C.) 186
11 A Accel/Decel Ramp Hold 186
12 B Drive Overheat Alarm (oH2) 187
13 C Terminal A1/A2 Enable/Disable 187
14 F Not used/Through Mode 187
15 10 Up Command 187
16 11 Down Command 187
17 12 Forward Jog 188
18 13 Reverse Jog 188
19 14 Fault Reset 188
20 15 Fast-Stop (N.O.) 188
21 16 Motor 2 Selection 189
22 17 Fast-stop (N.C.) 188
23 18 Timer Function Input 189
24 19 PID Disable 189
25 1A Accel/Decel Time Selection 2 189
26 1B Program Lockout 189
27 1E Reference Sample Hold 190
28 20 to 2F External Fault 190

Table5.26 Digital Multi-Function Input Settings right — PDF page 184

Source row Setting Function Page
1 30 PID Integral Reset 191
2 31 PID Integral Hold 191
3 32 Multi-Step Speed Reference 4 191
4 34 PID Soft Starter Cancel 191
5 35 PID Input Level Selection 191
6 40 Forward Run/Stop (2-wire sequence) 191
7 41 Reverse Run/Stop (2-wire sequence) 191
8 42 Run/Stop (2-Wire sequence 2) 191
9 43 FWD/REV (2-Wire sequence 2) 191
10 44 Offset Frequency 1 Addition 192
11 45 Offset Frequency 2 Addition 192
12 46 Offset Frequency 3 Addition 192
13 47 <1> Node Setup 192
14 60 DC Injection Braking Command 192
15 61 External Speed Search Command 1 192
16 62 External Speed Search Command 2 192
17 65 KEB Ride-Thru 1 (N.C.) 192
18 66 KEB Ride-Thru 1 (N.O.) 192
19 67 Communications Test Mode 192
20 68 High-Slip Braking 192
21 6A Drive Enable 192
22 75 Up 2 Command 193
23 76 Down 2 Command 193
24 7A KEB Ride-Thru 2 (N.C.) 194
25 7B KEB Ride-Thru 2 (N.O.) 194
26 7C Short-Circuit Braking (N.O.) 194
27 7D Short-Circuit Braking (N.C.) 194

Manual — Three-wire sequence and LOCAL/REMOTE — page 185

Source reference: SIEP C71060618F, December 2016, physical PDF page 185. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Stop Switch(N.C.); Run Switch(N.O.); DRIVE; S1 Run Command (Runs when Closed); S2 Stop Command (Stops when Open); S5 FWD/REV Multi-Function Input H1-05=0; SC Sequence Input Common. Wiring sketch is illustrative; complete installation and exact connectivity require original. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Run command with2ms min pulse; Can be either ON or OFF; Stop command2ms min; Can be ON or OFF; Forward/reverse command OFF(forward),ON(reverse); Motor speed; Stop,Forward,Reverse,Stop,Forward intervals. Source paragraph saysS1 closed longer than50ms, while this figure prints2ms min; both retained without selecting a preferred value. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Setting Function Page

<1> Available in drive software versions PRG: 1016 and later.

Setting 0: 3-Wire Sequence When one of the digital inputs is programmed for 3-Wire control, that input becomes a forward/reverse directional input, S1 becomes the Run command input, and S2 becomes the Stop command input. The drive will start the motor when the Run input S1 is closed for longer than 50 ms. The drive will stop the operation when the Stop input S2 is released. When the input programmed for 3-Wire sequence is open, the drive will be set for forward direction. If the input is closed, the drive is set for reverse direction.

Note: When 3-Wire sequence is selected the Run and Stop command must be input at S1 and S2.

Note: 1. The Run and Stop command must be open/closed for a short moment only to start and stop the drive. 2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the Run LED will flash to indicate that protective functions are operating. If required by the application, set b1-17 to “1” to have the Run command issued automatically as soon as the drive is powered up.

WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence but set up for 2-Wire sequence (default). When using 3-Wire sequence first set the drive properly (H1-□□ = 0) and then connect the control wires. Make sure b1-17 is set to “0” (drive does not accept Run command active at power up). When initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.

Setting 1: LOCAL/REMOTE Selection This setting allows the input terminal to determine if the drive will run in LOCAL mode or REMOTE mode.

Status Description

Note: 1. If one of the multi-function input terminals is set to for LOCAL/REMOTE, then the LO/RE key on the operator will be disabled. 2. When the drive is set to LOCAL, the LO/RE LED will light. 3. The default setting of the drive is not to allow switching between LOCAL and REMOTE during run. to Refer to b1-07: LOCAL/ REMOTE Run Selection on page 127 if this feature is required by the application.

5.7 H: Terminal Functions

Parameter Details

Table5.26 Digital Input Settings continued left — PDF page 185

Source row Setting Function Page
1 7E Forward/Reverse Detection (V/f Control with Simple PG Feedback) 194
2 90 to 96 DriveWorksEZ Digital Inputs 1 to 7 194

Table5.26 Digital Input Settings continued right — PDF page 185

Source row Setting Function Page
1 9F DriveWorksEZ Disable 194

Input Setting1 LOCAL/REMOTE Selection — PDF page 185

Source row Status Description
1 Closed LOCAL: Frequency reference and Run command are input from the digital operator.
2 Open REMOTE: Frequency reference and Run command are input from the selected external reference in accordance with the b1-01 and b1-02 or b1-15 and b1-16 settings.

Manual — Reference switching, Baseblock and Hold — page 186

Source reference: SIEP C71060618F, December 2016, physical PDF page 186. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Run command OFF/ON; Baseblock input ON and Baseblock release; Frequency reference; Output frequency. Begin Speed Search from the previous frequency reference; Output off,motor coasts. Exact waveforms are illustrative; adjacent elevator-brake notice retained. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Setting 2: External Reference 1/2 Selection The external reference 1/external reference 2 selection function allows the user to switch between the frequency reference and Run command source between external reference 1 and 2.

Status Description

Note: The default setting of the drive is not to allow switching between external reference 1 and 2 during run. Refer to b1-07: LOCAL/REMOTE Run Selection on page 127 if this feature is required by the application.

Setting 3 to 5: Multi-Step Speed Reference 1 to 3 Used to switch Multi-Step Speed frequency references d1-01 to d1-08 by digital inputs. Refer to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference on page 160 for details.

Setting 6: Jog Frequency Reference Selection Used to select the Jog frequency set in parameter d1-17 as active frequency reference. Refer to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference on page 160 for details.

Setting 7: Accel/Decel Time Selection 1 Used to switch between accel/decel times 1 and 2. Refer to C1-01 to C1-08: Accel/Decel Times 1 to 4 on page 147 for details.

Setting 8/9: External Baseblock (N.O.) and External Baseblock (N.C.) Setting 8 or 9 assign the Baseblock command to digital input terminals. When the drive receives a Baseblock command, the output transistor stop switching and the motor coasts to stop. During this time, the alarm “bb” will flash on the LED operator to indicate baseblock. For more information on alarms, Refer to Alarm Detection on page 282. When baseblock ends and a Run command is active, the drive performs Speed Search to get the motor running again (Refer to b3: Speed Search on page 130 for details).

Inputs Operation Setting 8 (N.O.) Setting 9 (N.C.)

NOTICE: If using baseblock in elevator applications, make sure the brake closes when the drive output is cut off by a Baseblock input. Failure to do so will result in the motor suddenly coasting when the Baseblock command is entered, causing the load to slip.

Setting A: Accel/Decel Ramp Hold When the digital input programmed for the Accel/Decel Ramp Hold function closes, the drive will lock ("hold") the output frequency. All acceleration or deceleration will cease, and the drive will hold the current speed. Acceleration or deceleration will resume once the input is opened again.

5.7 H: Terminal Functions

Input Setting2 External Reference1/2 Selection — PDF page 186

Source row Status Description
1 Open External reference 1 is used (defined by parameters b1-01 and b1-02)
2 Closed External reference 2 is used (defined by parameters b1-15 and b1-16)

Input Setting8/9 External Baseblock N.O./N.C. — PDF page 186

Source row Operation Setting 8 (N.O.) Setting 9 (N.C.)
1 Normal operation Open Closed
2 Baseblock (Interrupt output) Closed Open

Manual — Analog enable and Up/Down conditions — page 187

Source reference: SIEP C71060618F, December 2016, physical PDF page 187. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

If the Accel/Decel Ramp Hold function is enabled (d4-01 = 1), the drive will save the output frequency to memory whenever the Ramp Hold input is closed. When the drive is restarted after stop or after power supply interruption, the output frequency that was saved will become the frequency reference (provided that the Accel/Decel Ramp Hold input is still closed). Refer to d4-01: Frequency Reference Hold Function Selection on page 162 for details.

Setting B: Drive Overheat Alarm (oH2) Triggers an oH2 alarm when the contact closes. Because this is an alarm, drive operation is not affected.

Setting C: Analog Inputs A1/A2 Enable If a digital input programmed for this function is open, both analog inputs A1 and A2 are disabled. Close the input to enable the inputs. The drive disregards the input value selected by parameter H3-14 when this terminal closes.

Note: In drive software versions PRG: 1015 and earlier, input values to terminals A1 and A2 are both disregarded when this terminal closes.

Setting F: Not Used/Through Mode Any digital input that is not used should be set to F. When set to “F”, an input does not trigger any function in the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/Modbus communications (through mode). This way external sensors can be connected to unused drive digital inputs, thus reducing the need for separate PLC I/O units.

Setting 10/11: Up/Down Command Using the Up/Down function allows the frequency reference to be set by two push buttons. One digital input must be programmed as the Up input (H1-□□= 10) to increase the frequency reference, the other one must be programmed as the Down input (H1-□□= 11) to decrease the frequency reference. The Up/Down function has priority over the frequency references digital operator, analog inputs, and pulse input (b1-01 = 0, 1, 4). If the Up/Down function is used, then references provided by these sources will be disregarded. The inputs operate as shown in the table below.

Status: Up (10) | Down (11) | Description

Note: 1. An oPE03 alarm will occur when only one of the functions Up/Down is programmed for a digital input. 2. An oPE03 alarm will occur if the Up/Down function is assigned to the terminals while another input is programmed for the Accel/Decel Ramp Hold function. For more information on alarms, Refer to Drive Alarms, Faults, and Errors on page 263. 3. The Up/Down function can only be used for External Reference 1 for parameter b1-01. This should be taken into account when using Up/Down and the external reference parameter b1-15 switching command (H1-□□ = 2). Using the Up/Down Function with Frequency Reference Hold (d4-01) • When the frequency reference hold function is disabled (d4-01 = 0), the Up/Down frequency reference will be reset to 0 when the Run command is cleared or the power is cycled. • When d4-01 = 1, the drive will save the frequency reference set by the Up/Down function. When the Run command or the power is cycled, the drive will restart with the reference value that was saved. The value that was saved can be reset by closing either the Up or Down input without having a Run command active. Refer to d4-01: Frequency Reference Hold Function Selection on page 162. Using the Up/Down Function with Frequency Reference Limits The upper frequency reference limit is determined by parameter d2-01. The value for the lower frequency reference limit depends on the setting of parameter d4-10 and can be set by an analog input or parameter d2-02. Refer to d4-10: Up/Down Frequency Reference Limit Selection on page 167 for details. When a Run command is applied, the lower limits work as follows: • If the lower limit is set by parameter d2-02 only, the drive will accelerate to this limit as soon as a Run command is entered. • If the lower limit is determined by an analog input only, the drive will accelerate to the limit as long as the Run command and an Up or Down command are active. It will not start running if only the Run command is on. • If the lower limit is set by both an analog input and d2-02, and the analog limit is higher than the d2-02 value, the drive will accelerate to the d2-02 value when a Run command is input. Once the d2-02 value is reached, it will continue acceleration to the analog limit only if an Up or Down command is set.

5.7 H: Terminal Functions

Parameter Details

Up10=Open | Down11=Open

Up10=Closed | Down11=Open

Up10=Open | Down11=Closed

Up10=Closed | Down11=Closed

Input Setting10/11 Up/Down Command — PDF page 187

Source row Up(10) Down(11) Description
1 Open Open Hold current frequency reference
2 Closed Open Increase frequency reference
3 Open Closed Decrease frequency reference
4 Closed Closed Hold current frequency reference

Manual — Jog, Fault Reset and Fast Stop — page 188

Source reference: SIEP C71060618F, December 2016, physical PDF page 188. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency upper limit; Lower limit; Accelerates to lower limit; Same frequency; d4-01=1 andd4-01=0 trajectories. FWD run/stop ON; Up command ON; Down command ON; Hold frequency reset; Power supply ON/ON. No unprinted time or frequency inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Output Frequency; positive and negative d1-17 plateaus; FJOG ON then RJOG ON. Adjacent source500ms simultaneous-command fault and b1-04 reverse prohibition apply. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Figure 5.48 shows an Up/Down function example with a lower frequency reference limit set by d2-02 and the frequency reference hold function both enabled (d4-01 = 1) and disabled (d4-01 = 0).

Setting 12/13: FJOG/RJOG Reference Digital inputs programmed as Forward Jog (H1-□□ = 12) and Reverse Jog (H1-□□ = 13) will be Jog inputs that do not require a Run command. Closing the terminal set for Forward Jog input will cause the drive to ramp to the Jog Frequency Reference (d1-17) in the forward direction. The Reverse Jog will cause the same action in the reverse direction. The Forward Jog and Reverse Jog command can be set independently.

Note: The Forward Jog and Reverse Jog commands override all other frequency references. However, if the drive is set to prohibit reverse rotation (b1-04 = 1), then activating Reverse Jog will have no effect. If both the Forward Jog and Reverse Jog are input simultaneously for 500 ms or more, an external fault will occur and the drive will stop using the method set by b1-03.

Setting 14: Fault Reset Whenever the drive detects a fault condition, the fault output contact will close and the drive’s output will shut off. The motor then coasts to stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). Once the Run command is removed, the fault can be cleared by either the RESET key on the digital operator or by closing a digital input configured as a Fault Reset (H1-□□ = 14).

Note: Fault Reset commands are ignored as long as the Run command is present. To reset a fault, first remove the Run command.

Setting 15/17: Fast-stop (N.O./N.C.) The Fast-stop function operates much like an emergency stop input to the drive. If a Fast-stop command is input while the drive is running, the drive will decelerate to a stop by the deceleration time set to C1-09 (Refer to C1-09: Fast-stop Time on page 148). The drive can only be restarted after is has come to a complete stop, the Fast-stop input is off, and the Run command has been switched off. • To trigger the Fast-stop function with a N.O. switch, set H1-□□ = 15 • To trigger the Fast-stop function with a N.C. switch, set H1-□□ = 17 Figure 5.50 shows an operation example of Fast-stop.

5.7 H: Terminal Functions

Manual — Motor selection and related input functions — page 189

Source reference: SIEP C71060618F, December 2016, physical PDF page 189. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Run/Stop ON/ON; Fast-Stop H1-□□=17 ON/ON; Output Frequency; TIME; Decelerates atC1-09. Source shows Run cycling before restart after fast stop; no exact unprinted timing inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Drive; Motor switch input; Motor1 M and Motor2 M; selection contacts and three-phase line markings. Motor selection during run prohibited in adjacent source; wiring topology remains original-only. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast-stop time to C1-09.

Setting 16: Motor 2 Selection The drive has the capability to control two motors independently. A second motor may be selected using a multi-function digital input (H1-□□ = 16) as shown in Figure 5.51.

Motor 2 is selected when the input set for Motor 2 Selection closes. When operating motor 2, • E3-□□ and E4-□□ become valid for motor control. Refer to E3: V/f Characteristics for Motor 2 on page 175 and Refer to E4: Motor 2 Parameters on page 176 for details. • Accel/decel times set in parameters C1-05/06/07/08 are activated ( Refer to C1-01 to C1-08: Accel/Decel Times 1 to 4 on page 147 for details). • E4-14 is used as gain for slip compensation instead of C3-01. • E4-15 is used as gain for torque compensation instead of C4-01. • A digital output programmed for “Motor 2 Selection” (H2-01/02/03 = 1C) will be switched on. Note: 1. When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2. 2. It is not possible to switch between motor 1 and motor 2 during run. Doing so will trigger a "rUn" alarm.

Setting 18: Timer Function Input This setting configures a digital input terminal as the input for the timer function. Refer to b4: Delay Timers on page 135 for details.

Setting 19: PID Control Cancel When the PID Function has been enabled by b5-01 (PID Mode Selection), it can be indefinitely disabled by closing a digital input configured as a PID Disable (H1-□□ = 19). When the input is released, the drive resumes PID operation. Refer to PID Block Diagram on page 138 for more information on this function.

Setting 1A: Accel/Decel Time Selection 2 Used to select accel/decel times 3 and 4 in combination with the Accel/Decel Time Selection 1 command. Refer to C1-01 to C1-08: Accel/Decel Times 1 to 4 on page 147 for details.

Setting 1B: Program Lockout When an input is programmed for Program Lockout, parameters values can be monitored but not changed as long as this input is open.

5.7 H: Terminal Functions

Parameter Details

Manual — Sample/Hold and external fault matrix — page 190

Source reference: SIEP C71060618F, December 2016, physical PDF page 190. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Analog signal ramp; Frequency reference stair steps; Reference Sample Hold Input; ON(closed),OFF(open);100ms minimum sample intervals shown twice;Time. Power-off clears saved reference to0 per adjacent prose; no inferred sampled values. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Setting 1E: Analog Frequency Reference Sample/Hold This function allows the user to sample an analog frequency reference signal being input to terminal A1 or A2 and hold the frequency reference at the sampled level. Once the Analog Frequency Reference Sample/Hold function is held for at least 100 ms, the drive reads the analog input and changes the frequency reference to the newly sampled speed as illustrated in Figure 5.52. When the power is shut off and the sampled analog frequency reference is cleared, the frequency reference is reset to 0.

An oPE03 error will occur when one of the following functions is used simultaneously with the Analog Frequency Reference Sample/Hold function. • Hold Accel/Decel Stop (setting: A) • Up command, Down command (setting: 10, 11) • Offset Frequency (setting: 44 to 46) • Up or Down functions (setting: 75, 76)

Setting 20 to 2F: External Fault By using the External Fault function, the drive can be stopped when problems occur with external devices. To use the external fault function, set one of the multi-function digital inputs to any value between 20 to 2F. The operator will display EF□ where □ is the number of the terminal (terminal S□) to which the external fault signal is assigned. For example, if an external fault signal is input to terminal S3, “EF3” will be displayed. Select the value to be set in H1-□□ from a combination of any of the following three conditions: • Signal input level from peripheral devices (N.O./N.C.) • External fault detection method • Operation after external fault detection The following table shows the relationship between the conditions and the value set to H1-□□:

Setting

Terminal Status <1> Detection Method <2> Stopping Method

N.O. | N.C. | Always Detected

Detected during Run only

Ramp to Stop (fault)

Coast to Stop (fault)

Fast-stop (fault)

Setting | Terminal Status: N.O., N.C. | Detection Method: Always Detected, Detected during Run only | Stopping Method: Ramp to Stop (fault), Coast to Stop (fault), Fast-stop (fault), Alarm Only (continue running)

5.7 H: Terminal Functions

Input Setting20–2F External Fault matrix first — PDF page 190

Source row Setting Terminal N.O. <1> Terminal N.C. <1> Always Detected <2> Detected during Run only <2> Ramp to Stop (fault) Coast to Stop (fault) Fast-stop (fault) Alarm Only (continue running)
1 20 O ⟦blank source cell⟧ O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 21 ⟦blank source cell⟧ O O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 22 O ⟦blank source cell⟧ ⟦blank source cell⟧ O O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 23 ⟦blank source cell⟧ O ⟦blank source cell⟧ O O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
5 24 O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧
6 25 ⟦blank source cell⟧ O O ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧
7 26 O ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧
8 27 ⟦blank source cell⟧ O ⟦blank source cell⟧ O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧
9 28 O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧
10 29 ⟦blank source cell⟧ O O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧
11 2A O ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧
12 2B ⟦blank source cell⟧ O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧

Manual — External fault matrix and two-wire sequences — page 191

Source reference: SIEP C71060618F, December 2016, physical PDF page 191. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive; Forward Run atS1; Reverse Run atS2; SC Digital Input Common. Both inputs closed causes external fault per adjacent prose. No wiring installation inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Setting

Terminal Status <1> Detection Method <2> Stopping Method

N.O. | N.C. | Always Detected

Detected during Run only

Ramp to Stop (fault)

Coast to Stop (fault)

Fast-stop (fault)

Setting | Terminal Status: N.O., N.C. | Detection Method: Always Detected, Detected during Run only | Stopping Method: Ramp to Stop (fault), Coast to Stop (fault), Fast-stop (fault), Alarm Only (continue running)

<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed. <2> Determine whether detection for each fault should be enabled only during run or always detected.

Setting 30: PID Integral Reset By configuring one of the digital inputs as an Integral Reset Input, (H1-□□ = 30), the value of the integral component of PID control can be reset to 0 whenever the configured input is closed. The integral component of PID control will be held at 0 as long as the configured digital input is held closed. Refer to PID Block Diagram on page 138 for details.

Setting 31: PID Integral Hold By configuring a digital input for Integral Hold (H1-0□ = 31), the value of the integral component of the PID control is locked as long as the input is active. The PID controller resumes integral operation from the hold value as soon as the integral hold input is released. Refer to PID Block Diagram on page 138 for details.

Setting 32: Multi-Step Speed 4 Used to select the Multi-Step Speeds d1-09 to d1-16 in combination with the Multi-Step Speed inputs 1, 2 and 3. Refer to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference on page 160 for details.

Setting 34: PID SFS Cancel A digital input configured as a PID SFS Cancel input (H1-0□ = 34) can be used to enable or disable the PID soft starter and thereby canceling the Accel/Decel time b5-17. Refer to PID Block Diagram on page 138 for details.

Function 35: PID Input Level Selection An input programmed for this function can be used to switch the sign of the PID input. Refer to PID Block Diagram on page 138 for more information on this function.

Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence Sets the drive for 2-Wire sequence. When the input set to 40 is closed, the drive operates in the forward direction. When the input set for 41 is closed, the drive will operate in reverse. Closing both inputs at the same time will result in an external fault.

Note: 1. This function cannot be used simultaneously with settings 42 and 43. 2. These functions are assigned to the terminals S1 and S2 when the drive is initialized for 2-Wire sequence. 3. Software versions PRG: 1013 and later require that both Forward run and Reverse Run commands be set at the same time.

Figure

Setting 42/43: Run and Direction Command for 2-Wire Sequence 2 Sets the drive for 2-Wire sequence 2. When the input programmed for 42 is closed, the drive will operate in the selected direction. When the input opens, the drive will stop. The input programmed for 43 selects the direction. If it is open, forward direction is selected; if it is closed, reverse direction is selected.

Note: This function cannot be used simultaneously with settings 40 and 41.

5.7 H: Terminal Functions

Parameter Details

Input Setting20–2F External Fault matrix continued — PDF page 191

Source row Setting Terminal N.O. <1> Terminal N.C. <1> Always Detected <2> Detected during Run only <2> Ramp to Stop (fault) Coast to Stop (fault) Fast-stop (fault) Alarm Only (continue running)
1 2C O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ O
2 2D ⟦blank source cell⟧ O O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ O
3 2E O ⟦blank source cell⟧ ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ O
4 2F ⟦blank source cell⟧ O ⟦blank source cell⟧ O ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ O

Manual — Braking, Speed Search, KEB and Drive Enable — page 192

Source reference: SIEP C71060618F, December 2016, physical PDF page 192. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

DC Injection braking command OFF/ON/OFF; FWD Run command OFF/ON/OFF; Output frequency; DC Injection braking before and after run; DC Injection Braking Start Frequency b2-01. Run/Jog releases braking per adjacent prose; no unprinted duration inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Setting 44/45/46: Offset Frequency 1/2/3 Addition These inputs can be used to add offset frequencies d7-01, d7-02, and d7-03 to the frequency reference. Refer to d7-01 to d7-03: Offset Frequency 1 to 3 on page 167 for details.

Setting 47: Node Setup If the SI-S3/V option unit is connected, closing this terminal sets a node address for operation on a CANopen network.

Setting 60: DC Injection Braking When a DC Injection Braking command is input while the drive is stopped, DC Injection Braking operation is activated. When a Run command or a Jog command is input, DC Injection Braking is released. Refer to b2: DC Injection Braking on page 128 for details on setting up the DC braking function. The diagram below illustrates the DC Injection Braking function.

Setting 61/62: Speed Search 1/2 These input functions can be used to enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start. Refer to Activation of Speed Search on page 132 for details on how to use the input signals. If b3-24 is set to 0 and b3-01 is set to 0, when the input terminal set for Speed Search 1 (H1-□□ = 61) is enabled, Speed Search will begin looking for the motor speed from the maximum output frequency. If the Speed Search 2 input (H1-□□ = 62) is enabled, Speed Search starts looking for the motor speed starting at the frequency reference. Refer to b3: Speed Search on page 130 for more information about Speed Search.

Note: Operator error oPE03 will result if both Speed Search 1 and Speed Search 2 are set to the input terminals at the same time.

Setting 65/66: KEB Ride-Thru 1 (N.C.)/2 (N.O.) A digital input programmed for this function can be used to activate the KEB 1 function and detect power supply return.

Description | Digital Inputs: Setting 65 (N.C.), Setting 66 (N.O.)

Refer to Kinetic Energy Backup (KEB) Function on page 219 for details on how to use these input settings.

Setting 67: Communication Test Mode The drive has a built-in function for self-diagnosing the serial communications operation. The test involves wiring the send and receive terminals of the RS-485/RS-422 port together. The drive transmits data and then confirms the communications are received normally. Refer to Self-Diagnostics on page 461 for details on how to use this function.

Setting 68: High Slip Braking Closing an input programmed for this function triggers High Slip Braking. Once HSB is started, the drive has to completely stop and the HSB input has to be removed before a restart can be performed. Refer to n3: High Slip Braking (HSB)/ Overexcitation Deceleration on page 241 for details on High Slip Braking.

Setting 6A: Drive Enable A digital input configured as a Drive Enable input (H1-□□ = 6A) will prevent the drive from executing a Run command until the input is closed. When the Drive Enable input is open, the digital operator will display “dnE” to indicate that the drive is disabled.

5.7 H: Terminal Functions

Input Setting65/66 KEB Ride-Thru1 N.C./N.O. — PDF page 192

Source row Description Setting 65 (N.C.) Setting 66 (N.O.)
1 KEB 1 deceleration Open Closed
2 Normal operation Closed Open

Manual — Up/Down2 conditional operation matrix — page 193

Source reference: SIEP C71060618F, December 2016, physical PDF page 193. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

If a Run command is closed prior to the Drive Enable input being closed, then the drive will not run until the Run command is cycled. If the Drive Enable input is opened while the drive is running, the drive will stop using the method set by parameter b1-03 (Refer to b1-03: Stopping Method Selection on page 124 for details).

Setting 75/76: Up/Down 2 The Up/Down 2 function can be used to add a bias to the frequency reference. The input programmed for 75 will increase the bias and the input programmed for 76 will decrease it. Table 5.27 explains how the Up/Down 2 function works depending on the frequency reference source and parameters d4-01, d5-03 and d4-05. Refer to d4: Frequency Hold and Up/Down 2 Function on page 162 for detailed explanations of these and other Up/Down 2 related parameters.

Note: 1. The Up 2 and Down 2 functions must be set as a pair. 2. When using the Up/Down 2 function, set appropriate bias limit values in parameters d4-08 and d4-09.

Table 5.27 Up/Down 2 Operations

Condition | Freq. Ref. Source | d4-03 | d4-05 | d4-01 | Operation | Frequency Saved

5.7 H: Terminal Functions

Parameter Details

Condition 1 | source Multi-Step Speed Reference | d4-03=0 | d4-05=0 | d4-01=0

Condition 2 | source Multi-Step Speed Reference | d4-03=0 | d4-05=0 | d4-01=1

Condition 3 | source Multi-Step Speed Reference | d4-03=0 | d4-05=1 | d4-01=--

Condition 4 | source Multi-Step Speed Reference | d4-03=Value other than 0 | d4-05=-- | d4-01=0

Condition 5 | source Multi-Step Speed Reference | d4-03=Value other than 0 | d4-05=-- | d4-01=1

Condition 6 | source Other (analog communicati ons, etc.) | d4-03=0 | d4-05=0 | d4-01=0

Condition 7 | source Other (analog communicati ons, etc.) | d4-03=0 | d4-05=0 | d4-01=1

Table5.27 Up/Down2 Operations conditions1–7 — PDF page 193

Source row Condition Freq. Ref. Source d4-03 d4-05 d4-01 Operation Frequency Saved
1 1 Multi-Step Speed Reference 0 0 0 • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. Not saved
2 2 Multi-Step Speed Reference 0 0 1 • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. If the bias and frequency reference are constant for 5 s, the bias is added to the active frequency reference and reset afterwards.
3 3 Multi-Step Speed Reference 0 1 -- • Accelerates (increases the bias) while the Up 2 function is closed, • Decelerates (decreases the bias) while Down 2 is closed. • Otherwise operates at the frequency reference Not saved
4 4 Multi-Step Speed Reference Value other than 0 -- 0 • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (bias is increased for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (bias is decreased for d4-03). • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. Not saved
5 5 Multi-Step Speed Reference Value other than 0 -- 1 • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (bias is increased for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (bias is decreased for d4-03). • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. If the bias and frequency reference are constant for 5 s, the bias is added to the active frequency reference and reset afterwards.
6 6 Other (analog communicati ons, etc.) 0 0 0 • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • When during accel/decel. the frequency reference changes for more than d4-07, bias value is held until the output frequency meets the reference (speed agree). Not saved
7 7 Other (analog communicati ons, etc.) 0 0 1 • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • When during accel/decel. the frequency reference changes for more than d4-07, bias value is held until the output frequency meets the reference (speed agree). If the bias is constant for 5 s, it is saved to parameter d4-06. The frequency reference cannot be overwritten, so only the bias is saved.

Manual — Up/Down2 continuation and PM/DriveWorksEZ inputs — page 194

Source reference: SIEP C71060618F, December 2016, physical PDF page 194. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Condition | Freq. Ref. Source | d4-03 | d4-05 | d4-01 | Operation | Frequency Saved

Setting 7A/7B: KEB Ride-Thru 2 (N.C./N.O.) A digital input programmed for this function can be used to activate the KEB 2 function and detect power supply return.

Description | Digital Inputs: Setting 7A (N.C.), Setting 7B (N.O.)

Refer to Kinetic Energy Backup (KEB) Function on page 219 for details on how to use these input settings.

Setting 7C/7D: Short Circuit Braking (N.O./N.C.) (OLV/PM only) An input programmed for this function can be used to activate Short Circuit Braking in Open Loop Vector Control for PM motors. By linking all three phases of a PM motor it creates a braking torque in a rotating motor and can be used to stop a rotating motor or prevent a motor from coasting by external forces (like windmill effect in fan applications etc.).

Description | Digital Inputs: Setting 7C (N.O.), Setting 7D (N.C.)

Setting 7E: Forward Reverse Detection (V/f Control with Simple PG Feedback) When a digital input is programmed for this function, the input determines the direction of the speed feedback signal for V/f Control with PG feedback. If the input is open, the speed feedback signal is considered to be forward, if the input is closed, it is considered to be in reverse. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details.

Setting 90 to 96: DriveWorksEZ Digital Inputs 1 to 7 These settings are for digital inputs functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.

Setting 9F: DriveWorksEZ Function Disable This function is used to enable or disable a DriveWorksEZ program in the drive. An input programmed for this function is effective only if A1-07 = 2.

Status Description

5.7 H: Terminal Functions

Condition 8 | source Other (analog comms, etc.) | d4-03=0 | d4-05=1 | d4-01=--

Condition 9 | source Other (analog comms, etc.) | d4-03=Value than other 0 | d4-05=-- | d4-01=0

Condition 9 | source Other (analog comms, etc.) | d4-03=Value other than 0 | d4-05=-- | d4-01=0

Condition 10 | source Other (analog comms, etc.) | d4-03=Value than other 0 | d4-05=-- | d4-01=1

Condition 10 | source Other (analog comms, etc.) | d4-03=Value other than 0 | d4-05=-- | d4-01=1

Table5.27 Up/Down2 Operations conditions8–10 — PDF page 194

Source row Condition Freq. Ref. Source d4-03 d4-05 d4-01 Operation Frequency Saved
1 8 Other (analog comms, etc.) 0 1 -- • Accelerates (increases the bias) while the Up 2 function is closed, • Decelerates (decreases the bias) while Down 2 is closed. • Otherwise operates at the frequency reference Not saved
2 9 Other (analog comms, etc.) Value other than 0 -- 0 • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (increases the bias for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (decreases the bias for d4-03). • When during accel/decel the frequency reference changes for more then d4-07, bias value is held until the output frequency meets the reference (speed agree). Not saved
3 10 Other (analog comms, etc.) Value other than 0 -- 1 • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (increases the bias for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (decreases the bias for d4-03). • When during accel/decel the frequency reference changes for more then d4-07, bias value is held until the output frequency meets the reference (speed agree). If the bias is constant for 5 s, it is saved to parameter d4-06. The frequency reference cannot be overwritten, so only the bias is saved.

Input Setting7A/7B KEB Ride-Thru2 N.C./N.O. — PDF page 194

Source row Description Setting 7A (N.C.) Setting 7B (N.O.)
1 KEB 2 deceleration Open Closed
2 Normal operation Closed Open

Input Setting7C/7D Short-Circuit Braking N.O./N.C. OLV/PM only — PDF page 194

Source row Description Setting 7C (N.O.) Setting 7D (N.C.)
1 Normal operation Open Closed
2 Short-Circuit Braking Closed Open

Input Setting9F DriveWorksEZ Disable — PDF page 194

Source row Status Description
1 Open DriveWorksEZ enabled
2 Closed DriveWorksEZ disabled

Manual — Output assignments and function index — page 195

Source reference: SIEP C71060618F, December 2016, physical PDF page 195. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u H2: Multi-Function Output

n H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection

The drive has three multi-function output terminals. Set parameters H2-01 to H2-03 to values between 0 and 192 to assign functions to these terminals. Default values are listed in the following table.

No. Parameter Name Setting Range Default

Note: Terminals that are not used and terminals using the through-mode should be set to “F”.

Table 5.28 Multi-Function Output Terminal Settings

Setting Function Page

<1> Available in drive software versions PRG: 1016 and later.

Setting 0: During Run Output closes when the drive is outputting a voltage.

Status Description

5.7 H: Terminal Functions

Parameter Details

H2-01 to H2-03 Output Function Selection — PDF page 195

Source row No. Parameter Name Setting Range Default
1 H2-01 Terminal MA, MB and MC Function Selection (relay) 0 to 192 E: Fault
2 H2-02 Terminal P1 Function Selection (open-collector) 0 to 192 0: During Run
3 H2-03 Terminal P2 Function Selection (open-collector) 0 to 192 2: Speed Agree 1

Table5.28 Multi-Function Output Terminal Settings left — PDF page 195

Source row Setting Function Page
1 0 During Run 195
2 1 Zero Speed 196
3 2 Speed Agree 1 196
4 3 User Set Speed Agree 1 196
5 4 Frequency Detection 1 197
6 5 Frequency Detection 2 197
7 6 Drive Ready 198
8 7 DC Bus Undervoltage 198
9 8 During Baseblock (N.O.) 198
10 9 Frequency Reference Source 198
11 A Run Command Source 198
12 B Torque Detection 1 (N.O.) 198
13 C Frequency Reference Loss 199
14 D Braking Resistor Fault 199
15 E Fault 199
16 F Not used/Through Mode 199
17 10 Alarm 199
18 11 Reset Command Active 199
19 12 Timer Output 199
20 13 Speed Agree 2 199
21 14 User Set Speed Agree 2 200
22 15 Frequency Detection 3 200
23 16 Frequency Detection 4 201
24 17 Torque Detection 1 (N.C.) 198
25 18 Torque Detection 2 (N.O.) 198
26 19 Torque Detection 2 (N.C.) 198
27 1A During Reverse Operation 201

Table5.28 Multi-Function Output Terminal Settings right — PDF page 195

Source row Setting Function Page
1 1B During Baseblock (N.C.) 202
2 1C Motor 2 Selection 202
3 1E Restart Enabled 202
4 1F Motor Overload Alarm (oL1) 202
5 20 Drive Overheat Pre alarm (oH) 202
6 22 Mechanical Weakening 202
7 2F <1> Maintenance Period 202
8 30 During Torque Limit 202
9 37 During Frequency Output 202
10 38 Drive Enable 203
11 39 Watt Hour Pulse Output 203
12 3C LOCAL/REMOTE Status 203
13 3D During Speed Search 203
14 3E PID Feedback Low 203
15 3F PID Feedback High 203
16 4A During KEB Operation 203
17 4B During Short-Circuit Braking 203
18 4C During Fast-stop 203
19 4D oH Pre-Alarm Time Limit 203
20 4E <1> Braking Transistor Fault (rr) 203
21 4F <1> Braking Resistor Overheat (rH) 204
22 90 DriveWorksEZ Digital Output 1 204
23 91 DriveWorksEZ Digital Output 2 204
24 92 DriveWorksEZ Digital Output 3 204
25 100 to 192 H2 Parameter Functions Reversed Output Switching of 0 to 92 204

Output Setting0 During Run — PDF page 195

Source row Status Description
1 Open Drive is stopped.
2 Closed A Run command is input or the drive is during deceleration or during DC injection.

Manual — During Run, Zero Speed and Speed Agree1 — page 196

Source reference: SIEP C71060618F, December 2016, physical PDF page 196. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Run command OFF/ON; Baseblock command OFF/ON; Output frequency including interruption; During Run OFF/ON remains asserted through depicted baseblock interval, ramp stop and ending DC injection. Conceptual timing only. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Output frequency or motor speed; E1-09 (Max. Output Frequency) [literal source label]; Zero Speed OFF/ON as waveform falls below threshold. Adjacent text/table callE1-09 minimum output frequency; conflict retained. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Frequency reference; Output frequency positive/negative; L4-02 widths in both directions; Speed agree1 OFF/ON. Source detects reference±L4-02 independent of direction; no thresholds calculated. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Setting 1: Zero Speed Terminal closes whenever the output frequency falls below the minimum output frequency set to E1-09.

Status Description

Setting 2: Speed Agree 1 (fref/fout Agree 1) Closes whenever the actual output frequency is within the Speed Agree Width (L4-02) of the current frequency reference regardless of the direction.

Note: Detection works in both directions, forward and reverse.

Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.

Setting 3: User Set Speed Agree 1 (fref/fset Agree 1) Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-02) of the programmed Speed Agree Level (L4-01).

5.7 H: Terminal Functions

Output Setting1 Zero Speed — PDF page 196

Source row Status Description
1 Open Output frequency is above the minimum output frequency set to E1-09
2 Closed Output frequency is less than or equal to the minimum output frequency set to E1-09

Output Setting2 Speed Agree1 — PDF page 196

Source row Status Description
1 Open Output frequency does not match the frequency reference while the drive is running.
2 Closed Output frequency is within the range of frequency reference ± L4-02.

Manual — User speed and frequency detection — page 197

Source reference: SIEP C71060618F, December 2016, physical PDF page 197. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency; Frequency reference; L4-01 threshold with±L4-02 bands in both directions; User Set Speed Agree1 OFF/ON/OFF/ON. Both reference and output within band condition retained in table. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Output frequency positive/negative; L4-01 levels; L4-02 hysteresis; Frequency Detection1 <1> ON/OFF intervals. Footnote appliesL4-07=1 detection always enabled; default0 excludes baseblock. No invented edge timing. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Status Description

Note: The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.

Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.

Setting 4: Frequency Detection 1 Output is closed as long as the output frequency is below the detection level set in L4-01 plus the hysteresis set in L4-02. It closes when the output frequency falls below L4-01.

<1> This is the time chart when L4-07, Speed Agree Detection Selection, is set to 1 (Detection always enabled). The default setting for L4-07 is 0 (No detection during baseblock). When L4-07 is set to 0, the terminal opens during baseblock. Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.

Setting 5: Frequency Detection 2 Output closes whenever the output frequency is equal to or above the detection level set in L4-01. The output opens when the output frequency falls below L4-01 minus the hysteresis set in L4-02.

5.7 H: Terminal Functions

Parameter Details

Output Setting3 User Set Speed Agree1 — PDF page 197

Source row Status Description
1 Open Output frequency or frequency reference are outside the range of L4-01 ± L4-02.
2 Closed Output frequency and the frequency reference are both within the range of L4-01 ± L4-02.

Output Setting4 Frequency Detection1 — PDF page 197

Source row Status Description
1 Open Output frequency exceeded L4-01 + L4-02.
2 Closed Output frequency is below L4-01 or has not exceeded L4-01 + L4-02.

Output Setting5 Frequency Detection2 — PDF page 197

Source row Status Description
1 Open Output frequency is below L4-01 minus L4-02 or has not exceeded L4-01.
2 Closed Output frequency exceeded L4-01.

Manual — Drive Ready, voltage and source outputs — page 198

Source reference: SIEP C71060618F, December 2016, physical PDF page 198. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency positive/negative; L4-01 levels; L4-02 hysteresis; Frequency Detection2 OFF/ON intervals in both directions. Read withPDF197 source table and exact threshold wording. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.

Setting 6: Drive Ready Output closes whenever the drive is ready to operate the motor.

Status Description

Refer to b1-08: Run Command Selection while in Programming Mode on page 127 for details on the setting of b1-08.

Setting 7: DC Bus Undervoltage Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level. The undervoltage trip level is determined by L2-05. A fault in the DC bus charge circuit will also cause the DC Bus Undervoltage output to close.

Setting 8: During Baseblock (N.O.) Output closes to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors are not switched and no voltage will be output.

Setting 9: Frequency Reference Source A digital output programmed for this function shows the frequency reference source that is currently selected.

Setting A: Run Command Source A digital output programmed for this function shows the Run command source that is currently selected.

Setting B/17/18/19: Torque Detection 1 (N.O./N.C.) and Torque Detection 2 (N.O./N.C.) These digital output functions can be used to signal an overtorque or undertorque situation to an external device. Set up the torque detection and select the output function from the table below. Refer to L6: Torque Detection on page 231 for details.

5.7 H: Terminal Functions

Output Setting6 Drive Ready — PDF page 198

Source row Status Description
1 Open During power up, initialization, fault or in Programming Mode (while b1-08 = 0 or 2).
2 Closed Drive is ready for operation.

Output Setting7 DC Bus Undervoltage — PDF page 198

Source row Status Description
1 Open DC bus voltage is above the level set to L2-05
2 Closed DC bus voltage has fallen below the trip level set to L2-05.

Output Setting8 During Baseblock N.O. — PDF page 198

Source row Status Description
1 Open Drive is not in a baseblock state.
2 Closed Baseblock is being executed.

Output Setting9 Frequency Reference Source — PDF page 198

Source row Status Description
1 Open Frequency reference is provided from External Reference 1 (b1-01) or 2 (b1-15)
2 Closed Frequency reference is being sourced from the digital operator.

Output SettingA Run Command Source — PDF page 198

Source row Status Description
1 Open Run command is provided from External Reference 1 (b1-02) or 2 (b1-16)
2 Closed Run command is being sourced from the digital operator.

Manual — Torque detection and fault/status outputs — page 199

Source reference: SIEP C71060618F, December 2016, physical PDF page 199. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting Status Description

Setting C: Frequency Reference Loss An output set for this function will be closed if frequency reference loss is detected. Refer to L4-05: Frequency Reference Loss Detection Selection on page 227 for details.

Setting D: Dynamic Braking Resistor Overheat An output programmed for this function will close when the dynamic braking resistor (DB) overheats or the braking transistor is in a fault condition.

Setting E: Fault The Fault configured digital output will close whenever the drive experiences a fault (this excludes faults CPF00 and CPF01).

Setting F: Not Used Use this setting when the terminal is not used or when using the terminal as a throughput. When set to “F”, the output is not set by any drive function but it can be switched by a PLC via a communication option or MEMOBUS/Modbus communications (through mode).

Setting 10: Minor Fault Output closes when a minor fault condition is present.

Setting 11: Reset Command Active Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial communications, or using a communications option card.

Setting 12: Timer Output This setting configures a digital output terminal as output for the timer function. Refer to b4: Delay Timers on page 135 for details.

Setting 13: Speed Agree 2 (fref /fout Agree 2) Closes whenever the actual output frequency is within the Speed Agree Width (L4-04) of the current frequency reference regardless of the direction.

Status Description

Note: The detection works in both forward and reverse.

5.7 H: Terminal Functions

Parameter Details

Output SettingB/17/18/19 Torque Detection1/2 N.O./N.C. — PDF page 199

Source row Setting Status Description
1 B Closed Torque Detection 1 (N.O.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-02 for longer than the time specified in parameter L6-03.
2 17 Open Torque Detection 1 (N.C.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-02 for longer than the time specified in parameter L6-03.
3 18 Closed Torque Detection 2 (N.O.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-05 for longer than the time specified in parameter L6-06.
4 19 Open Torque Detection 2 (N.C.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-05 for longer than the time specified in parameter L6-06.

Output Setting13 Speed Agree2 — PDF page 199

Source row Status Description
1 Open Output frequency does not match the frequency reference while the drive is running
2 Closed Output frequency is within the range of frequency reference ± L4-04

Manual — Speed Agree2 and Frequency Detection3 — page 200

Source reference: SIEP C71060618F, December 2016, physical PDF page 200. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Frequency reference; Output frequency positive/negative; L4-04 widths; Speed Agree2 OFF/ON. Detects both directions; no unprinted numerical value. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Caption literally saysPositive L3-04 Value. Graph threshold labelL4-03 with±L4-04, Output frequency,Frequency reference, User Set Speed Agree2 OFF/ON; no output assertion in reverse example. Adjacent prose describes signedL4-03 and specified-direction-only detection; caption conflict retained. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.

Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227 for details on setting the detection width.

Setting 14: User Set Speed Agree 2 (fref /fset Agree 2) Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-04) of the programmed Speed Agree Level (L4-03). As the detection level L4-03 is a signed value, detection works in the specified direction only.

Status Description

Setting 15: Frequency Detection 3 Output is closed as long as the output frequency is below the detection level set in L4-03 plus the hysteresis set in L4-04. It closes when the output frequency falls below L4-03. As the detection level L4-03 is a signed value, the detection works in the specified direction only.

5.7 H: Terminal Functions

Output Setting14 User Set Speed Agree2 — PDF page 200

Source row Status Description
1 Open Output frequency or frequency reference are outside the range of L4-03 ± L4-04
2 Closed Output frequency and the frequency reference are both within the range of L4-03 ± L4-04

Output Setting15 Frequency Detection3 — PDF page 200

Source row Status Description
1 Open Output frequency exceeded L4-03 plus L4-04.
2 Closed Output frequency is below L4-03 or has not exceeded L4-03 plus L4-04 yet.

Manual — Frequency detection and reverse output — page 201

Source reference: SIEP C71060618F, December 2016, physical PDF page 201. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency, positive and negative; L4-03 threshold and L4-04 hysteresis; Frequency detection 3 <1> ON/OFF. Caption says Positive L3-04 Value, unlike L4-03 graph. Figure closes PDF200 continuation. Exact source geometry, routing and unprinted numerical values remain original-only.

Output frequency, positive and negative; L4-03 threshold, L4-04 hysteresis; Frequency Detection 4 OFF/ON in positive portion. Caption says Positive L3-04 Value, unlike L4-03 graph. Signed-direction detection per adjacent prose. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.63 Frequency Detection 3 Example with Positive L3-04 Value

<1> This is the time chart when L4-07, Speed Agree Detection Selection, is set to 1 (Detection always enabled). The default setting for L4-07 is 0 (No detection during baseblock). When L4-07 is set to 0, the terminal opens during baseblock. Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227 for details on setting the detection width.

Setting 16: Frequency Detection 4 Output closes whenever the output frequency is equal to or above the detection level set in L4-03. The output opens when the output frequency falls below L4-03 minus the hysteresis set in L4-04. As the detection level L4-03 is a signed value, the detection works in the specified direction only.

Status Description

Figure 5.64 Frequency Detection 4 Example with Positive L3-04 Value

Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227 for details on setting the detection width.

Setting 1A: During Reverse The During Reverse digital output will close whenever the drive is turning the motor in the reverse direction.

5.7 H: Terminal Functions

Parameter Details

Frequency Detection4 — PDF page 201

Source row Status Description
1 Open Output frequency is below L4-03 minus L4-04 or has not exceeded L4-03 yet.
2 Closed Output frequency exceeded L4-03.

During Reverse — PDF page 201

Source row Status Description
1 Open Motor is driven in the forward direction or stopped.
2 Closed Motor is driven in reverse.

Manual — Output status and motor selection — page 202

Source reference: SIEP C71060618F, December 2016, physical PDF page 202. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency positive then negative; FWD Run command, REV Run command; During Reverse OFF/ON; time. Output remains ON through reverse deceleration until zero-frequency crossing; no unprinted time inferred. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.65 Reverse Direction Output Example Time Chart

Setting 1B: During Baseblock (N.C.) Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors are not switched and no voltage is output.

Status Description

Setting 1C: Motor 2 Selected This output function shows the motor 1/2 selection status. Refer to Setting 16: Motor 2 Selection on page 189 for details on switching motors.

Setting 1E: Restart Enabled The Restart Enabled output will be closed once the fault restart function becomes active and will remain closed until a successful restart is accomplished or the number of Auto Restart attempts as specified by L5-01 is reached. Refer to L5: Fault Restart on page 230 for details on automatic fault restart.

Setting 1F: Motor Overload Alarm oL1 An output programmed for this function will be closed when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level. Refer to L1-01: Motor Overload Protection Selection on page 213 for details.

Setting 20: Drive Overheat Pre-alarm (oH) Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02. Refer to L8-02: Overheat Alarm Level on page 235 for details on drive overheat detection.

Setting 22: Mechanical Weakening Detection Output closes when mechanical weakening is detected. Refer to Mechanical Weakening Detection on page 233 for details.

Setting 2F: Maintenance Period The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined by the estimated performance life span of those components.

Setting 30: During Torque Limit Output closes when the motor is operating at the torque limit specified by the L7-□□ parameters or an analog input. This setting is only valid when using Open Loop Vector Control (A1-02 = 2). Refer to L7-01/02/03/04: Torque Limits on page 234 for details.

Setting 37: During Frequency Output Output closes when the drive is outputting a frequency.

5.7 H: Terminal Functions

Baseblock N.C. — PDF page 202

Source row Status Description
1 Open Baseblock is being executed.
2 Closed Drive is not in a baseblock state.

Motor2 Selected — PDF page 202

Source row Status Description
1 Open Motor 1 is selected.
2 Closed Motor 2 is selected.

During Frequency Output — PDF page 202

Source row Status Description
1 Open Drive is not outputting a frequency. One of the following functions is being performed: Stop, baseblock, DC injection braking (during initial excitation), short circuit braking.
2 Closed Drive is outputting frequency.

Manual — Output conditions and protection status — page 203

Source reference: SIEP C71060618F, December 2016, physical PDF page 203. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Run command OFF/ON; baseblock command OFF/ON; output frequency with shaded beginning/ending braking portions; During Run OFF/ON spanning braking and baseblock; During Frequency Output OFF/ON only during the depicted frequency-output segments. No duration inferred. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.66 During Frequency Output Time Chart

Setting 38: Drive Enabled A Drive Enable digital output will reflect the status of a digital input configured as a Drive Enable input (H1-□□ = 6A). If the Drive Enable digital input is closed then the Drive Enabled digital output will also close.

Setting 39: Watt Hour Pulse Output Outputs a pulse to indicate the watt hours. Refer to H2-06: Watt Hour Output Unit Selection on page 204 for details.

Setting 3C: LOCAL/REMOTE Status Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.

Status Description

Setting 3D: During Speed Search Output terminal closes while Speed Search is being performed. Refer to b3: Speed Search on page 130 for details on the Speed Search function.

Setting 3E: PID Feedback Low Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the level set to b5-13 for longer than the time set to b5-14. Refer to PID Feedback Loss Detection on page 141 for details.

Setting 3F: PID Feedback High Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the level set to b5-36 for longer than the time set to b5-37. Refer to PID Feedback Loss Detection on page 141 for details.

Setting 4A: During KEB Operation Output terminal closes while KEB is being performed. Refer to Kinetic Energy Backup (KEB) Function on page 219 for a KEB function description.

Setting 4B: During Short Circuit Braking Closes the output terminal while Short Circuit Braking is being executed.

Setting 4C: During Fast-stop Output terminal closes when a Fast-stop is being executed. C1-09: Fast-stop Time for details.

Setting 4D: oH Pre-Alarm Time Limit Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat alarm has not disappeared after ten frequency reduction operation cycles. Refer to L8-03: Overheat Pre-Alarm Operation Selection on page 235 for details.

Setting 4E: Braking Transistor Fault (rr) The output closes when the internal braking transistor reaches the overheat level.

5.7 H: Terminal Functions

Parameter Details

LOCAL/REMOTE — PDF page 203

Source row Status Description
1 Open REMOTE: The selected external reference (b1-01/b1-02 or b1-15/b1-16) is used as frequency reference and Run command source
2 Closed LOCAL: The digital operator is used as frequency reference and Run command source

Manual — Pulse energy unit and analog input selection — page 204

Source reference: SIEP C71060618F, December 2016, physical PDF page 204. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 4F: Braking Resistor Overheat (rH) The output closes when the braking resistor exceeds the overheat level. the braking resistor may overheat due to the motor regeneration or short deceleration time setting.

Setting 90 to 92: DriveWorksEZ Digital Output 1 to 3 These settings are for digital output functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.

Setting 100 to 192: Reverse Switching for Functions 0 to 92 These settings reverse the switching status of the specified function. Set as 1□□, where the last two digits specify the setting number of the function to be reversed. Examples: • To reverse the output for “8: During Baseblock”, set “108”. • To reverse the output for “4A: During KEB” set “14A” .

n H2-06: Watt Hour Output Unit Selection

When one of the multi-function terminals is set to output the number of watt hours (H2-01/02/03 = 39), parameter H2-06 determines the units for the output signal. The output is intended to drive a watt hour meter or a PLC input by a 200 ms pulse signal. A pulse is output according to the kWh unit selected in H2-06.

No. Parameter Name Setting Range Default

u H3: Multi-Function Analog Input Terminals

The drive is equipped with 2 multi-function analog input terminals, A1 and A2. The user can assign functions to these terminals by setting parameters H3-02 and H3-10 between 0 and 31.

n H3-01: Terminal A1 Signal Level Selection

Selects the input signal level for analog input A1.

No. Name Setting Range Default

Setting 0: 0 to 10 Vdc with Limit The input level is 0 to 10 Vdc. Negative input values will be limited to 0. Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency reference can be set from 0 to 100% with an analog input of 5 to 10 V. The frequency reference will be zero when the analog input is between 0 and 5 V.

5.7 H: Terminal Functions

H2-06 — Watt Hour Output Unit Selection — PDF page 204

Source row No. Parameter Name Setting Range Default
1 H2-06 Watt Hour Output Unit Selection 0: 0.1 kWh units 1: 1 kWh units 2: 10 kWh units 3: 100 kWh units 4: 1000 kWh units 0

H3-01 — Terminal A1 Signal Level Selection — PDF page 204

Source row No. Name Setting Range Default
1 H3-01 Terminal A1 Signal Level Selection 0 to 1 0

Manual — A1 gain, bias and reverse-reference behavior — page 205

Source reference: SIEP C71060618F, December 2016, physical PDF page 205. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Analog input value −100%, 0, 100%; input voltage 0, 10 V. Negative input is limited to 0; solid positive line and dashed below-zero extension. Read with PDF204 example, not a new device setting. Exact source geometry, routing and unprinted numerical values remain original-only.

Analog input value −100%, 0, 100%; input voltage 0 V, 10 V; line from−100% at 0 V to 100% at 10 V. Negative reference reverses rotation per adjacent source example. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.67 Analog Input with Limit (Bias Setting -100%)

Setting 1: 0 to 10 Vdc without Limit The input level is 0 to 10 Vdc. Negative input values will be accepted. Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency reference can be set from 0 to 100% with an analog input of 5 to 10 V. With an input of 0 to 5 V, the frequency reference can be set from -100% to 0%. The drive reverses the motor rotation with negative input.

Figure 5.68 Analog Input without Limit (Bias Setting -100%)

n H3-02: Terminal A1 Function Selection

Determines the function assigned to analog input terminal A1. Refer to Multi-Function Analog Input Terminal Settings on page 208 for a list of functions and descriptions.

No. Name Setting Range Default

Note: If not using an input terminal or if using it in the through-mode, be sure to set that terminal to “F”.

n H3-03/H3-04: Terminal A1 Gain/Bias Setting

Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (Gain). Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1. Both can be used to adjust the analog input A1 characteristics.

5.7 H: Terminal Functions

Parameter Details

H3-02 — Terminal A1 Function Selection — PDF page 205

Source row No. Name Setting Range Default
1 H3-02 Terminal A1 Function Selection 0 to 31 0

H3-03 / H3-04 — Terminal A1 Gain Setting — PDF page 205

Source row No. Name Setting Range Default
1 H3-03 Terminal A1 Gain Setting -999.9 to 999.9% 100.0%
2 H3-04 Terminal A1 Bias Setting -999.9 to 999.9% 0.0%

Manual — Analog gain and bias examples — page 206

Source reference: SIEP C71060618F, December 2016, physical PDF page 206. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Gain=100%, Bias=0%; Frequency reference versus 0 V to 10 V input. Linear example, not measured calibration. Exact source geometry, routing and unprinted numerical values remain original-only.

Gain=200%, Bias=0%; Frequency reference; 100% / E1-04 plateau from 5 V to 10 V; dashed extension reaches 200% at 10 V. Input 0 V, 5 V, 10 V. Exact source geometry, routing and unprinted numerical values remain original-only.

Gain=100%; Bias=−25%; Frequency reference; H3-01=0 clips at 0, H3-01=1 allows negative reference; input crossing is labeled 2.0 V, endpoint 10 V. Adjacent prose instead says 2.5 V; preserve both, do not resolve by calculation. Exact source geometry, routing and unprinted numerical values remain original-only.

Default Settings Using the factory default settings for the analog input’s function, gain, and bias, the 0 to 10 Vdc signal at the analog input will yield a 0 to 100% frequency reference span.

Figure 5.69 Analog Input A1 Default Characteristics

Setting Examples • Gain H3-03 = 200%, A1 as frequency reference input: An input 10 Vdc will be equivalent to a 200% frequency reference and 5 Vdc will be equivalent to a 100% frequency reference. Since the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04 above 5 Vdc.

Figure 5.70 Frequency Reference Setting by Analog Input with Increased Gain

• Bias H3-04 = -25%, A1 as frequency reference input An input of 0 Vdc will be equivalent to a -25% frequency reference. When parameter H3-01 = 0 the minimum frequency reference is 0% between 0 and 2.5 Vdc input. An analog input of 2.5 to 10 Vdc will now be the same as 0 to 100% of the frequency reference span. When parameter H3-01 = 1, the motor will rotate in reverse between 0 and 2.5 Vdc input.

Figure 5.71 Frequency Reference Setting by Analog Input with Negative Bias

• Gain = 0%, Bias = 100%, A1 as frequency reference input This setting leads to an inverse-acting frequency reference. The minimum analog input level (0 Vdc) will produce a 100% frequency reference and the maximum analog input level (10 Vdc) will produce a 0% frequency reference.

5.7 H: Terminal Functions

Manual — A2 signal selection and filter — page 207

Source reference: SIEP C71060618F, December 2016, physical PDF page 207. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Bias=100%, Gain=0%; Frequency reference from 100% at 0 V to 0% at 10 V. Inverse example. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.72 Frequency Reference Setting by Analog Input with Inverse Gain and Bias Settings

n H3-09: Terminal A2 Signal Level Selection

Selects the input signal level for analog input A2. Be sure to also set DIP switch S1 on the terminal board accordingly for a voltage input or current input.

No. Name Setting Range Default

Setting 0: 0 to 10 Vdc with Lower Limit The input level is 0 to 10 Vdc. Negative input values will be limited to 0. Refer to the explanation of H3-01, Setting 0. Refer to Setting 0: 0 to 10 Vdc with Limit on page 204

Setting 1: 0 to 10 Vdc without Lower Limit The input level is 0 to 10 Vdc. Negative input values will be accepted. Refer to the explanation of H3-01, Setting 1. Refer to Setting 1: 0 to 10 Vdc without Limit on page 205

Setting 2: 4 to 20 mA Current Input The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).

Setting 3: 0 to 20 mA Current Input The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).

n H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2. Refer to Multi-Function Analog Input Terminal Settings on page 208 for a list of functions and descriptions.

n H3-11/H3-12: Terminal A2 Gain/Bias Setting

Parameter H3-11 sets the level of the selected input value that is equal to 10 Vdc/20 mA input at terminal A2 (Gain). Parameter H3-12 sets the level of the selected input value that is equal to 0 Vdc/4 mA/0 mA input at terminal A2. Both can be used to adjust the analog input A2 characteristics. The setting works in the same way as parameters H3-03/04 for analog input A1.

n H3-13: Analog Input Filter Time Constant

Parameter H3-13 sets the time constant for a first order filter that will be applied to both analog inputs A1 and A2.

An analog input filter can be used to prevent erratic drive control when a “noisy” analog reference is used. The drive operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.

5.7 H: Terminal Functions

Parameter Details

H3-09 — Terminal A2 Signal Level Selection — PDF page 207

Source row No. Name Setting Range Default
1 H3-09 Terminal A2 Signal Level Selection 0 to 3 2

H3-10 — Terminal A2 Function Selection — PDF page 207

Source row No. Name Setting Range Default
1 H3-10 Terminal A2 Function Selection 0 to 31 0

H3-11 / H3-12 — Terminal A2 Gain Setting — PDF page 207

Source row No. Name Setting Range Default
1 H3-11 Terminal A2 Gain Setting -999.9 to 999.9% 100.0%
2 H3-12 Terminal A2 Bias Setting -999.9 to 999.9% 0.0%

H3-13 — Analog Input Filter Time Constant — PDF page 207

Source row No. Name Setting Range Default
1 H3-13 Analog Input Filter Time Constant 0.00 to 2.00 s 0.03 s

Manual — Analog function index and scaling — page 208

Source reference: SIEP C71060618F, December 2016, physical PDF page 208. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n Multi-Function Analog Input Terminal Settings

This section describes the various functions that can be assigned to terminals A1 and A2 by setting H3-02 and H3-10.

Note: The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting and adjusting analog input functions.

Table 5.29 Multi-Function Input Terminal Settings

Setting Function Page

<1> Available in drive software versions PRG: 1016 and later.

Setting 0: Frequency Bias The input value of an analog input set to this function will be added to the analog frequency reference value. Use this setting also when only one analog input is used to supply the frequency reference. By default both analog inputs A1 and A2 are set for this function. Using both A1 and A2 at the same time increases the frequency reference by the total of both inputs. Example: If the analog frequency reference by analog input A1 is 50% and a bias of 20% is applied by analog input A2, the resulting frequency reference will be 70% of the maximum output frequency.

Setting 1: Frequency Gain The input value of an analog input set to this function will be multiplied with the analog frequency reference value. Example: If the analog frequency reference from analog input A1 is 80% and a gain of 50% is applied from analog input A2, the resulting frequency reference will be 40% of the maximum output frequency.

Setting 2: Auxiliary Reference Sets the auxiliary frequency reference when Multi-Step Speed operation is selected. Refer to Multi-Step Speed Selection on page 160 for details.

Setting 4: Voltage Bias Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available only when using V/f Control.

Setting 7: Overtorque/Undertorque Level Overtorque level sets the overtorque/undertorque detection level using the analog input. This works with Torque Detection Selection 1 (L6-01) and will take the place of the torque detection level set to L6-02. For general Open Loop Vector Control, this function is based on 100% of the motor rated torque. For V/f Control and PM Open Loop Vector, this function is based on 100% of the drive rated current. Refer to L6: Torque Detection on page 231 for details on torque detection.

Setting B: PID Feedback An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01. Refer to PID Feedback Input Methods on page 137.

Setting C: PID Setpoint An input set for this function supplies the PID setpoint value. The frequency reference selected in parameter b1-01 no longer becomes the PID se point. This setting requires PID operation to be enabled in b5-01. Refer to PID Setpoint Input Methods on page 137.

Setting E: Motor Temperature In addition to or in place of the oL1 (motor overload) fault detection, it is possible to use a PTC (Positive Temperature Coefficient) thermistor for motor insulation protection. Refer to Motor Protection Using a Positive Temperature Coefficient (PTC) on page 215 for detailed explanations.

5.7 H: Terminal Functions

Table5.29 Analog input functions left — PDF page 208

Source row Setting Function Page
1 0 Frequency Bias 208
2 1 Frequency Gain 208
3 2 Auxiliary Frequency Reference 208
4 4 Output Voltage Bias 208
5 7 Overtorque/Undertorque Detection Level 208
6 B PID Feedback 208
7 C PID Set Point 208
8 E Motor Temperature (PTC input) 208
9 F Not used/Through Mode 209

Table5.29 Analog input functions right — PDF page 208

Source row Setting Function Page
1 10 Forward Torque Limit 209
2 11 Reverse Torque Limit 209
3 12 Regenerative Torque Limit 209
4 15 General Torque Limit 209
5 16 Differential PID Feedback 209
6 30 DriveWorksEZ Analog Input 1 209
7 31 DriveWorksEZ Analog Input 2 209
8 41 <1> Output Voltage Gain 209

Manual — Torque limits and analog enable — page 209

Source reference: SIEP C71060618F, December 2016, physical PDF page 209. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Axes positive/negative torque reference and REV/FWD motor rotation. Quadrant 1 FWD motoring:10 Positive Torque Limit, 15 Torque Limit, Parameter L7-01. Quadrant 2 REV regenerative:10 Positive, 12 Regenerative, 15 Torque Limit, Parameter L7-04. Quadrant 3 REV motoring:11 Negative, 15 Torque Limit, Parameter L7-03. Quadrant 4 FWD regenerative:11 Negative, 12 Regenerative, 15 Torque Limit, Parameter L7-02. Lowest applicable limit applies per prose; OLV only. Exact source geometry, routing and unprinted numerical values remain original-only.

Setting F: Not Used Any analog input that is not used should be set to F. When set to “F”, an input does not affect any drive function but the input level can be read out by a PLC via a communication option or MEMOBUS/Modbus communications (through mode). This way drive analog inputs can be used to read out external sensor values if there is a lack of PLC analog inputs.

Setting 10/11/12/15: Positive/Negative/Regenerative/General Torque Limit (OLV only) These functions make it possible to limit the torque reference with an analog input. The limit can either be set as a general value for all operation conditions (setting 15) or can be programmed separately for each operation condition (quadrants 1, 2, 3, and 4). Figure 5.73 shows which limit is applied in each quadrant. The lowest of the values will always be used as the limit. The value is set as a percentage of the motor rated torque. Refer to L7: Torque Limit on page 234 for information how torque limits work.

Figure 5.73 Analog Input Torque Limits

Setting 16: Differential PID Feedback If an analog value is set for this function, the PID controller is set for differential feedback. The subtraction of the PID feedback input value and the differential feedback input value builds the feedback value that is used to calculate the PID input. Refer to PID Feedback Input Methods on page 137.

Setting 30/31: DriveWorksEZ Analog Input 1/2 These settings are for analog output functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.

Setting 41: Output Voltage Gain Allows the user to change the output voltage by adjusting the voltage reference via one of the analog input terminals or with MEMOBUS/Modbus. An internal 0.3 second delay has been added to prevent sudden, drastic change to the V/f pattern.

Note: When an input terminal is assigned to adjust the Output Voltage Gain (H3-□□ = 41), a voltage reference from MEMOBUS/Modbus is ignored.

n H3-14: Analog Input Terminal Enable Selection

Note: Parameter available in drive software versions PRG: 1016 and later. Determines which of the analog input terminals will be enabled or disabled when a digital input programmed for “Analog input enable” (H1-□□ = C) is closed. When H1-□□ ≠ C, all of the input terminals are enabled all of the time. Terminals not set as the target are not influenced by input signals.

No. Name Setting Range Default

Setting 1: Terminal A1 only Setting 2: Terminal A2 only Setting 7: All Terminals Enabled n H3-16/H3-17: Terminal A1/A2 Offset

Note: Parameters available in drive software versions PRG: 1016 and later. Determines the amount of offset to be used to calibrate analog input signals from the terminals A1 and A2.

5.7 H: Terminal Functions

Parameter Details

H3-14 — Analog Input Terminal Enable Selection — PDF page 209

Source row No. Name Setting Range Default
1 H3-14 Analog Input Terminal Enable Selection 1, 2, 7 7

Manual — Analog output and terminal calibration — page 210

Source reference: SIEP C71060618F, December 2016, physical PDF page 210. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Left graph: terminal AM output voltage 0 V, 5 V, 10 V; monitor value 0–100%; Bias 0%; Gain 150%, 100%, 50% lines. Right graph: monitor 0–100%; terminal AM0 V, 3 V, 10 V; Gain 100% with Bias 30% versus Bias 0%. Output constrained 0–10 Vdc per source. Exact source geometry, routing and unprinted numerical values remain original-only.

Enter a 0 V signal to terminal A1. Next adjust the offset in H3-16 until the monitor U1-13 for the terminal A1 input voltage reads 0.0%. The process is the same for terminal A2. Enter a 0 V signal, and adjust the offset for terminal A2 in H3-17 until the monitor U1-14 for terminal A2 input voltage reads 0.0%.

No. Name Setting Range Default

u H4: Multi-Function Analog Output Terminals

These parameters assign a function to analog output terminal AM for monitoring a specific aspect of drive performance.

n H4-01: Multi-Function Analog Terminal AM Monitor Selection

Sets the desired drive monitor parameter U□-□□ to output as an analog value via terminal AM. Refer to U: Monitors on page 399 for a list of all monitors. The “Analog Output Level” columns indicates if a monitor can be applied for analog output. Example: Enter “103” for U1-03.

A setting of 031 or 000 applies no drive monitor to the analog output. With this setting the terminal AM output level can be set by a PLC via a communication option or MEMOBUS/Modbus communications (through mode).

n H4-02/H4-03: Multi-Function Analog Output Terminal AM Gain/Bias

Parameter H4-02 sets the output voltage that is equal to 100% of the monitor value. Parameter H4-03 sets the output voltage equal to 0% of the monitor value. Both values are set as a percentage of 10 V. The minimum output voltage for terminal AM is 0 V, the maximum is 10 Vdc. Figure 5.74 illustrates the function of the gain and bias settings.

Figure 5.74 Analog Output Gain/Bias Setting

When viewing the settings for H4-02, terminal AM will output a voltage that is equal to 100% of the monitor value (considering the present setting). When viewing the settings for H4-03, terminal AM will output a voltage that is equal to 0% of the monitor value.

u H5: MEMOBUS/Modbus Serial Communication

Through the drives built in RS-422/485 port (terminals R+, R-, S+, S-), serial communication can be performed with programmable logic controllers (PLCs) or similar devices using the MEMOBUS/Modbus protocol. The H5-□□ parameters are used to set up the drive for MEMOBUS/Modbus Communications. Refer to MEMOBUS/Modbus Serial Communication on page 439 for detailed descriptions of the H5-□□ parameters.

5.7 H: Terminal Functions

H3-16 / H3-17 — Terminal A1 Offset — PDF page 210

Source row No. Name Setting Range Default
1 H3-16 Terminal A1 Offset -500 to 500 0
2 H3-17 Terminal A2 Offset -500 to 500 0

H4-01 — Multi-Function Analog 1 (Terminal AM Monitor Selection) — PDF page 210

Source row No. Name Setting Range Default
1 H4-01 Multi-Function Analog 1 (Terminal AM Monitor Selection) 000 to 999 102

H4-02 / H4-03 — Multi-Function Analog Output Terminal AM Gain — PDF page 210

Source row No. Name Setting Range Default
1 H4-02 Multi-Function Analog Output Terminal AM Gain -999.9 to 999.9% 100.0%
2 H4-03 Multi-Function Analog Output Terminal AM Bias -999.9 to 999.9% 0.0%

Manual — Pulse input functions and scaling — page 211

Source reference: SIEP C71060618F, December 2016, physical PDF page 211. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u H6: Pulse Train Input/Output

A one track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse train signal can be used as the frequency reference, for PID functions, or as the speed feedback signal in V/f Control. The pulse output monitor terminal MP, which can be used in sinking or sourcing mode, can output drive monitors values as a pulse train signal with a maximum frequency of 32 kHz. Use parameters H6-□□ to scale and set up the function for the pulse input terminal RP and pulse output terminal MP.

n H6-01: Pulse Train Input Terminal RP Function Selection

Selects the function of pulse train input terminal RP.

No. Name Setting Range Default

Setting 0: Frequency Reference If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01/15 = 4), the drive reads the frequency value from terminal RP.

Setting 1: PID Feedback Value Using this setting, the feedback value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID Control on page 136 for details on PID control.

Setting 2: PID Setpoint Value Using this setting, the setpoint value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID Control on page 136 for details on PID control.

Setting 3: Speed Feedback for V/f Control (V/f Control only, Motor 1 only) This setting enables simple speed feedback for V/f Control. A pulse signal can be used to input the motor speed to the drive and thereby improve the speed control accuracy. Note that this speed feedback can only be a one track signal that cannot be used for direction detection. The drive needs a separate motor rotation direction signal. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details on using Simple V/f Control with Speed Feedback.

n H6-02: Pulse Train Input Terminal RP Scaling

The pulse train input scaling parameter sets the terminal RP input frequency that is equal to 100% of the signal selected as the input value in parameter H6-01.

<1> Setting range is determined by drive software version. PRG: 1016 and later: 100 to 32000 Hz PRG: 1015 and earlier: 1000 to 32000 Hz

n H6-03: Pulse Train Input Terminal RP Gain

Sets the level of the value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to terminal RP.

n H6-04: Pulse Train Input Terminal RP Bias

Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.

n H6-05: Pulse Train Input Terminal RP Filter Time

Sets the pulse train input filter time constant in seconds. The pulse train input filter helps prevent noise interference from causing erroneous operation when operating the drive within the pulse train signal.

5.7 H: Terminal Functions

Parameter Details

H6-01 — Pulse Train Input Terminal RP Function Selection — PDF page 211

Source row No. Name Setting Range Default
1 H6-01 Pulse Train Input Terminal RP Function Selection 0 to 4 0

H6-02 — Pulse Train Input Scaling — PDF page 211

Source row No. Name Setting Range Default
1 H6-02 Pulse Train Input Scaling <1> 1440 Hz

H6-03 — Pulse Train Input Gain — PDF page 211

Source row No. Name Setting Range Default
1 H6-03 Pulse Train Input Gain 0.0 to 1000.0% 100.0%

H6-04 — Pulse Train Input Bias — PDF page 211

Source row No. Name Setting Range Default
1 H6-04 Pulse Train Input Bias -100.0 to 100.0% 0.0%

Manual — Pulse output selection and scaling — page 212

Source reference: SIEP C71060618F, December 2016, physical PDF page 212. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Increasing the filter setting time increases the effectiveness of the noise prevention, however, this also increasingly slows drive response time.

No. Name Setting Range Default

n H6-06: Pulse Train Output Terminal MP Monitor Selection

Selects the pulse train monitor output terminal MP function. The set value □□□ is equal to the numerals in U□-□□ of the selected monitor. Refer to U: Monitors on page 399 for a complete list of monitors. Selectable monitor items are listed below.

n H6-07: Pulse Train Output Terminal MP Monitor Scaling

Pulse train monitor scaling sets the output frequency at terminal MP when the monitor item is 100%. Set H6-06 to 102 and H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.

5.7 H: Terminal Functions

H6-05 — Pulse Train Input Filter Time — PDF page 212

Source row No. Name Setting Range Default
1 H6-05 Pulse Train Input Filter Time 0.00 to 2.00 s 0.10 s

H6-06 — Pulse Train Output Terminal MP Monitor Selection — PDF page 212

Source row No. Name Setting Range Default
1 H6-06 Pulse Train Output Terminal MP Monitor Selection 000, 031, 101, 102, 105, 116, 501, 502, 801 to 809 102

H6-07 — Pulse Train Input Monitor Scaling — PDF page 212

Source row No. Name Setting Range Default
1 H6-07 Pulse Train Input Monitor Scaling 0 to 32000 Hz 1440 Hz

Manual — Motor overload selection and multiple motors — page 213

Source reference: SIEP C71060618F, December 2016, physical PDF page 213. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Power supply; Drive; M1/M2; MC1/MC2 magnetic contactors; L10/L20 thermal relays. Example circuit supports adjacent requirement for individual thermal overloads when multiple motors share a drive; not an inferred installation diagram. Exact source geometry, routing and unprinted numerical values remain original-only.

Torque (%) ticks 50, 60, 90, 100, 150; Speed (%) ticks 0, 5, 33, 100, 120, 167, 200; 100 speed corresponds 60 Hz. Rated Speed=100% Speed; 60 sec.; Continuous; curves A/B/C. No unprinted curve values or letter applicability inferred. Same row cooling/overload prose captured in V1000-P213-T2. Exact source geometry, routing and unprinted numerical values remain original-only.

5.8 L: Protection Functions

u L1: Motor Protection Functions

n L1-01: Motor Overload Protection Selection

The drive has an electronic overload protection function that estimates the motor overload level based on output current, output frequency, thermal motor characteristics, and time. An oL1 fault will be triggered when motor overload is detected. L1-01 sets the overload protection function characteristics according to the motor being used.

No. Name Setting Range Default

<1> Setting 6 is available in drive software versions PRG: 1016 and later.

Note: 1. When the motor protection function is enabled (L1-01 is not set to zero), an oL1 alarm can be output through one of the multi-function outputs by setting H2-01 to 1F. The output will close when the motor overload level reaches 90% of the oL1 detection level. 2. Select a method to protect the motor from overheat by setting L1-01 to a value between 1 and 4; use setting 6 when running a single motor from the drive. An external thermal relay is not required.

Setting 0: Disabled - Motor Overload Protection is not Provided This setting should be used if no motor overheat protection is desired or if multiple motors are connected to one drive. In this case it is recommended that you install a thermal relay for each motor as show in Figure 5.75

Figure 5.75 Example of Protection Circuit Design for Multiple Motors

NOTICE: Protect each motor with individual thermal overloads when multiple motors are connected to one drive. Failure to comply could result in motor damage. Disable the electronic overload protection of the drive (L1-01 = “0: Disabled”) and protect each motor with individual motor thermal overloads.

Setting 1: General Purpose Motor (standard self-cooled) Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the motor from overheat throughout the entire speed range.

Overload Tolerance Cooling Ability Overload Characteristics

Setting 2: Drive Dedicated Motor (constant torque, 1:10) Use this setting when operating a drive duty motor with a torque ratio of 1:10. This motor type is allowed to run with 100% load from 10% up to 100% speed. Running slower speeds with full load can trigger an overload fault.

Parameter Details

Read with same-row overload graph captured separately; no graph values inferred.

L1-01 — Motor Overload Protection Selection — PDF page 213

Source row No. Name Setting Range Default
1 L1-01 Motor Overload Protection Selection 0 to 4; 6 <1> A1-02 dependent

L1-01 Setting1 General Purpose Motor — PDF page 213

Source row Cooling Ability Overload Characteristics
1 Motor designed to operate from line power. Motor cooling is most effective when running at rated nameplate base frequency (check the motor specifications). Continuous operation at less than line power frequency with 100% load can trigger motor overload protection (oL1). A fault is output and the motor will coast to stop.

Manual — Motor-specific overload characteristics — page 214

Source reference: SIEP C71060618F, December 2016, physical PDF page 214. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Torque (%) ticks 50, 55, 100, 150; Speed (%) ticks 0, 1, 10, 100, 120, 167, 200; 100 speed corresponds 60 Hz. Rated Speed=100% Speed; 60 sec.; Continuous; curves A/D/B. Read with 1:10 and 100% load 10–100% speed prose and same-row 6 Hz cooling statement. No curve interpolation. Exact source geometry, routing and unprinted numerical values remain original-only.

Torque (%) ticks 0, 50, 90, 100, 150; Speed (%) ticks 1, 100, 120, 167, 200; 100 speed corresponds 60 Hz. Rated Speed=100% Speed; 60 sec.; Continuous; curves A/B/D. Read with 1:100 and 100% load 1–100% speed prose and approximately 0.6 Hz cooling statement. No curve interpolation. Exact source geometry, routing and unprinted numerical values remain original-only.

Torque (%) ticks 50, 80, 100, 120, 150; Motor Speed (%) ticks 0, 10, 33, 100.60 sec. upper curve; Continuous lower curve. Same-row PM cooling/overload prose retained separately. No intermediate curve value inferred. Exact source geometry, routing and unprinted numerical values remain original-only.

Overload Tolerance Cooling Ability Overload Characteristics

Setting 3: Vector Motor (constant torque, 1:100) Use this setting when operating a drive dedicated motor with a torque ratio of 1:100. This motor type is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload fault.

Setting 4: PM Derated Torque Motor This setting is for operating a PM motor. PM motors for derated torque have a self-cooling design, so the overload tolerance drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload characteristics, providing overheat protection across the entire speed range.

Setting 6: General-Purpose Motor Note: General-purpose motors are designed with a base speed that operates at line frequency (50/60 Hz depending on geographic region). Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately adjusts the electrothermal trigger point according to the motor overload characteristics and protects the motor from overheat throughout the entire speed range.

5.8 L: Protection Functions

Read with same-row overload graph captured separately; no graph values inferred.

L1-01 Setting2 Drive Dedicated Motor — PDF page 214

Source row Cooling Ability Overload Characteristics
1 Motor is designed to effectively cool itself at speeds as low as 6 Hz. Continuous operation with 100% load from 6 Hz to 50/60 Hz.

L1-01 Setting3 Vector Motor — PDF page 214

Source row Cooling Ability Overload Characteristics
1 Motor is designed to effectively cool itself at speeds as low as approximately 0.6 Hz. Continuous operation with 100% load from 0.6 Hz to 50/60 Hz.

L1-01 Setting4 PM Derated Torque — PDF page 214

Source row Cooling Ability Overload Characteristics
1 Motor is designed to produce 100% torque at base speed. Built with effective cooling capabilities. Reaching 100% when operating at below the base frequency causes a motor overload fault (oL1). The drive fault output closes and the motor coasts to stop.

Manual — Overload time and PTC introduction — page 215

Source reference: SIEP C71060618F, December 2016, physical PDF page 215. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Rated Speed=100% Speed; 60 s; Torque (%)50, 60, 90, 100, 150; Speed (%)0, 5, 33, 100, 120, 167, 200. A:Max.speed for 200LJ and above; B:Max.speed for 160MJ to 180 LJ; C:Max.speed for 132MJ and below; Continuous. Only literal printed letter legend retained; no applicability inferred for other plot letters. Exact source geometry, routing and unprinted numerical values remain original-only.

Operation time(minutes)0.1, 0.4, 1, 3, 7, 10; Motor current(%)0, 100, 150, 200; E2-01=100% motor current. Cold start curve: marked 150%/7 min and 200%/3 min; Hot start:marked 150%/1 min and 200%/0.4 min. Shaded region between curves. Example at E1-06 rated output frequency with L1-02=1 minute; not a universal overload guarantee. Exact source geometry, routing and unprinted numerical values remain original-only.

Overload Tolerance Cooling Ability Overload Characteristics

n L1-02: Motor Overload Protection Time

Sets the time for the drive to shut down on motor overload (oL1) when the motor is running with excessive current. Enter the time the motor can withstand operating at 150% current after previously running at 100% current (hot motor overload condition). This parameter rarely requires adjustment.

No. Name Setting Range Default

Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start after continuous operation at 100%. Figure 5.76 illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at the value of E1-06, Motor Base Speed, with L1-02 set to one minute. Motor overload protection operates in the area between a cold start and a hot start. • Cold start: Characteristics of motor protection operation time in response to an overload situation that was suddenly reached when starting a stationary motor. • Hot start: Characteristics of motor protection operation time in response to an overload situation that occurred while the motor was operating continuously at or below its rated current.

Figure 5.76 Protection Operation Time for General Purpose Motors at the Rated Output Frequency

n Motor Protection Using a Positive Temperature Coefficient (PTC)

A motor PTC can be connected to an analog input of the drive. This input is used by the drive for motor overheat protection. When the motor overheat alarm level is reached, an oH3 alarm will be triggered and the drive will continue operation as selected in L1-03. When the overheat fault level is reached an oH4 fault is triggered, a fault signal will be output and the drive will stop the motor using the stop method determined in L1-04. Figure 5.77 shows a PTC connection example for analog input A2. If using analog input A2, make sure to set DIP switch S1 on the terminal board for voltage input when using this function.

5.8 L: Protection Functions

Parameter Details

Read with same-row overload graph captured separately; no graph values inferred.

L1-02 — Motor Overload Protection Time — PDF page 215

Source row No. Name Setting Range Default
1 L1-02 Motor Overload Protection Time 0.1 to 5.0 minutes 1.0 minutes

L1-01 Setting6 General-Purpose Motor — PDF page 215

Source row Cooling Ability Overload Characteristics
1 Motor designed to operate from line power. Motor cooling is most effective when running at rated base frequency (check the motor nameplate or specifications) Continuous operation at less than line power frequency with 100% load can trigger motor overload protection (oL1). A fault is output and the motor will coast to stop.

Manual — PTC circuit, characteristics and alarm — page 216

Source reference: SIEP C71060618F, December 2016, physical PDF page 216. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive; Multi-function input; +V(+10.5 V, 20 mA); branch resistor 12 kΩ; PTC thermistor; A2(0–10 V); AC. MA/MB/MC multi-function output(contact); P1/P2/PC multi-function output(photocoupler). Source wiring example, exact connectivity original-only. Exact source geometry, routing and unprinted numerical values remain original-only.

Resistance(Ω)550, 1330; Temperature°C; Class F150°C, Class H180°C; Tr:threshold value; Tr−5, Tr, Tr+5, Tr′. Solid/dashed characteristics; one motor phase, normally three PTCs in series per prose. No interpolation of curves. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.77 Connection of a Motor PTC

The PTC must have the following characteristics for one motor phase. Normally a motor is protected by three PTCs connected in series.

Figure 5.78 Motor PTC Characteristics

Overheat detection using a PTC can be set up by parameters L1-03/04/05 as explained below.

n L1-03: Motor Overheat Alarm (oH3) Operation Selection

Sets the drive operation when the PTC input signal reaches the motor overheat alarm level. (PTC input level: Tr - 5 °C)

No. Name Setting Range Default

Setting 0: Ramp to Stop The drive stops the motor using the active deceleration time.

Setting 1: Coast to Stop The drive output is switched off and the motor coasts to stop.

Setting 2: Fast-stop The drive stops the motor using the Fast-stop time set in parameter C1-09.

Setting 3: Alarm Only The operation is continued and an oH3 alarm is displayed on the digital operator

5.8 L: Protection Functions

L1-03 — Motor Overheat Alarm Operation Selection — PDF page 216

Source row No. Name Setting Range Default
1 L1-03 Motor Overheat Alarm Operation Selection 0 to 3 3

Manual — PTC fault and leakage-current filters — page 217

Source reference: SIEP C71060618F, December 2016, physical PDF page 217. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n L1-04: Motor Overheat Fault (oH4) Operation Selection

Sets the drive operation when the PTC input signal reaches the motor overheat fault level. (PTC input level: Tr + 5 °C)

No. Name Setting Range Default

Setting 0: Ramp to Stop The drive stops the motor using the active deceleration time.

Setting 1: Coast to Stop The drive output is switched off and the motor coasts to stop.

Setting 2: Fast-stop The drive stops the motor using the Fast-stop time set in parameter C1-09.

n L1-05: Motor Temperature Input Filter Time

Used to set a filter on the PTC signal in order to prevent a motor overheat fault from being mistakenly detected.

n L1-13: Continuous Electrothermal Operation Selection

Determines whether to hold the current value of the electrothermal motor protection (L1-01) when the power supply is interrupted.

Setting 0: Disabled Setting 1: Enabled n L1-22: Leakage Current Filter Time Constant 1

Note: 1. Available in drive software versions PRG: 1021 and later. 2. Available only when C6-02 is set to B. To display this parameter, first set C6-02 to B. Sets the time constant for the filter applied to motor overload detection current or monitor current for constant speed operation. Leakage current can incorrectly trigger motor overload fault oL1 or result in incorrect monitor reading. Increase this setting if erroneous detection occurs or if the monitor display is incorrect.

NOTICE: Setting parameter L1-22 too high may cause the drive to detect motor overload too slowly and burn out the motor. Be sure to set L1-22 to an appropriate value for the application.

n L1-23: Leakage Current Filter Time Constant 2

Note: 1. Available in drive software versions PRG: 1021 and later. 2. Available only when C6-02 is set to B. To display this parameter, first set C6-02 to B. Sets the time constant for the filter applied to monitor current during acceleration and deceleration. Leakage current can result in incorrect monitor reading. Increase this setting if the monitor display is incorrect.

Note: Setting parameter L1-23 too high may cause the current monitor to take too long to read the initial current level. Check the operation sequence being used if this is a problem.

5.8 L: Protection Functions

Parameter Details

L1-04 — Motor Overheat Fault Operation Selection — PDF page 217

Source row No. Name Setting Range Default
1 L1-04 Motor Overheat Fault Operation Selection 0 to 2 1

L1-05 — Motor Temperature Input Filter Time — PDF page 217

Source row No. Name Setting Range Default
1 L1-05 Motor Temperature Input Filter Time 0.00 to 10.00 s 0.20 s

L1-13 — Continuous Electrothermal Operation Selection — PDF page 217

Source row No. Name Setting Range Default
1 L1-13 Continuous Electrothermal Operation Selection 0 or 1 1

L1-22 — Leakage Current Filter Time Constant 1 — PDF page 217

Source row No. Name Setting Range Default
1 L1-22 Leakage Current Filter Time Constant 1 0.0 to 60.0 s 20.0 s

L1-23 — Leakage Current Filter Time Constant 2 — PDF page 217

Source row No. Name Setting Range Default
1 L1-23 Leakage Current Filter Time Constant 2 0.0 to 60.0 s 1.0 s

Manual — Momentary power-loss recovery — page 218

Source reference: SIEP C71060618F, December 2016, physical PDF page 218. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u L2: Momentary Power Loss Ride-Thru

n L2-01: Momentary Power Loss Operation Selection

When a momentary power loss occurs (DC bus voltage falls below the level set in L2-05), the drive can be set to automatically return to the operation it was performing when the power went out based on certain conditions.

No. Name Setting Range Default

Setting 0: Disabled (default) If power is not restored within 15 ms, a Uv1 fault will result and the drive will stop the motor.

Setting 1: Enabled, Recover Within L2-02 When a momentary power loss occurs, the drive will attempt to restart and perform Speed Search if power is restored within the period of time set to parameter L2-02. If power is not restored within the time set to L2-02 (i.e. DC bus voltage level remains below Uv1 detection level L2-05), then a Uv1 fault is triggered and the drive output will be shut off.

Setting 2: Recover as Long as CPU has Power Drive will try to restart as long as the CPU still has power. This allows for a longer ride-through time than setting L2-01 to 1. A Uv1 fault is not triggered. This setting should also be used if the KEB function is utilized.

Note: 1. The amount of time the drive is capable of recovering after a power loss is determined by the capacity of the drive. Drive capacity determines the upper limit for L2-02. 2. When L2-01 is set to 1 or 2, and a magnetic contactor between motor and drive is used, be sure that the magnetic contactor is kept close as long as the drive attempts to restart. 3. When L2-01 is set to 1 or 2, “Uv” will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not output at this time.

n L2-02: Momentary Power Loss Ride-Thru Time

Set the time in which the power has to return before a Uv fault is tripped. This parameter is valid only if L2-01 = 1.

n L2-03: Momentary Power Loss Minimum Baseblock Time

Sets the minimum baseblock time when power is restored following a momentary power loss. This determines the time it takes for the leftover voltage in the motor to dissipate. Increase this setting if overcurrent or overvoltage occur at the beginning of Speed Search after a power loss or DC Injection Braking. If L2-03 > L2-02, then the drive will restart after the time set to L2-03 has passed from the beginning of the power loss.

n L2-04: Momentary Power Loss Voltage Recovery Ramp Time

Sets the time constant used to ramp up the voltage during Speed Search. The setting value determines the time for a change from zero to the maximum voltage.

n L2-05: Undervoltage Detection Level

Determines the voltage at which a Uv1 fault is triggered or at which the KEB function is activated.

<1> Values are for 200 V class drives and must be doubled for 400 V class drives. <2> This value is initialized when E1-01 is changed.

5.8 L: Protection Functions

L2-01 — Momentary Power Loss Operation Selection — PDF page 218

Source row No. Name Setting Range Default
1 L2-01 Momentary Power Loss Operation Selection 0 to 2 0

L2-02 — Momentary Power Loss Ride-Thru Time — PDF page 218

Source row No. Name Setting Range Default
1 L2-02 Momentary Power Loss Ride-Thru Time 0.0 to 25.5 s Determined by o2-04.

L2-03 — Momentary Power Loss Minimum Baseblock Time — PDF page 218

Source row No. Name Setting Range Default
1 L2-03 Momentary Power Loss Minimum Baseblock Time 0.1 to 5.0 s Determined by o2-04

L2-04 — Momentary Power Loss Voltage Recovery Ramp Time — PDF page 218

Source row No. Name Setting Range Default
1 L2-04 Momentary Power Loss Voltage Recovery Ramp Time 0.0 to 5.0 s Determined by o2-04

L2-05 <1> — Undervoltage Detection Level — PDF page 218

Source row No. Name Setting Range Default
1 L2-05 <1> Undervoltage Detection Level 150 to 210 V 190 V <2>

Manual — KEB modes and activation — page 219

Source reference: SIEP C71060618F, December 2016, physical PDF page 219. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

KEB Ride-Thru(H1-□□=65 or 66) OFF/ON/OFF; Output frequency; L2-06 deceleration interval followed by L2-07 acceleration. Run and activation conditions in adjacent prose apply; no numeric time inferred. Exact source geometry, routing and unprinted numerical values remain original-only.

This setting rarely needs to be changed. When setting L2-05 is lower than the default setting, be sure to install an AC reactor option to the input side of the power supply to prevent damage to drive circuitry.

n Kinetic Energy Backup (KEB) Function

In case of a power loss, the KEB function can decelerate the motor and use the rotational energy of the machine to backup/ maintain the drive DC bus for a certain period of time. This allows the drive to continue running without interrupting the output power during a momentary power loss. Once the power is restored, the drive smoothly returns to the same operational state before the power loss occurred. The KEB function supports two different operation modes.

KEB 1 In this mode the drive decelerates the motor based on the deceleration time set in parameter L2-06/C1-09 in order to keep the DC bus voltage level high. When the power supply returns, it uses the time set to L2-07 or the selected acceleration time to accelerate back to the frequency reference.

Figure 5.79 KEB Ride-Thru Timing Diagram for Multiple Drives

Note: If L2-06 is set to 0.0 s, C1-09 is used instead. If L2-07 is set to 0.0 s, the drive reaccelerates using the selected acceleration time. Use this method with setting parameters L2-06 and L2-07 if multiple drives must decelerate but still keep the speed ratio between the drives constant during power loss. In this case, a braking resistor is required in order to avoid overvoltage trips.

KEB 2 In this mode the drive decelerates the motor by calculating the energy of the rotating system. The deceleration rate is continuously adjusted so that the DC bus voltage meets the level set in parameter L2-11. The rotational energy is estimated using the parameters L3-24 and L3-25. When the power supply returns, the drive accelerates back to the frequency reference using the selected acceleration time.

Activation and Deactivation of the KEB Function The KEB function requires parameter L2-01 to be set to 1 or 2 and a digital input has to be configured for the KEB 1 (H1-□□ = 65/66) or KEB 2 (H1-□□ = 7A/7B) command. The input has to be enabled during KEB. Refer to Setting 65/66: KEB Ride-Thru 1 (N.C.)/2 (N.O.) on page 192 and Refer to Setting 7A/7B: KEB Ride-Thru 2 (N.C./N.O.) on page 194 for details on setting the KEB input commands. The KEB function is automatically activated when one of the conditions below becomes true. • The DC bus voltage falls below the level set in parameter L2-05. The KEB input has to be set within 50 ms after the KEB function was activated, or the drive will assume the power supply has returned and attempt to restart. • The input programmed for KEB 1 or 2 is activated. This input should be triggered by an external undervoltage detection relay. The KEB function ends when one of the conditions below become true. • The KEB input was released or • The function was activated by DC bus voltage detection and no KEB input was set within 50 ms after the KEB activation. Figure 5.80 shows a wiring example for triggering the KEB function at power loss using digital input S6.

5.8 L: Protection Functions

Parameter Details

Manual — KEB wiring example and adjustment scope — page 220

Source reference: SIEP C71060618F, December 2016, physical PDF page 220. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Braking Resistor atB1/B2; L1/L2/L3; driveR/L1, S/L2, T/L3 andU/T1, V/T2, W/T3; M; UV Detection Relay; S6 KEB command 1 or 2; S1 Start command; SC. Original topology retained; no new wiring recommendations. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.80 KEB Function Wiring Example

Note: Make sure the Run command is not switched off when momentary power loss occurs. If the Run command is shut off, the drive will not accelerate back to speed when the power is restored.

KEB Related Adjustment Parameters The KEB 1 functions can be adjusted using the following parameters: • L2-05, Undervoltage Detection Level • L2-06 or C1-09, KEB Deceleration Time or Fast-stop Time • L2-07, KEB Acceleration Time • L2-08, Frequency Gain at KEB Start Use the following parameters when adjusting the KEB 2 function: • L2-05, Undervoltage Detection Level • L2-08, Frequency Gain at KEB Start • L2-11, Desired DC Bus Voltage during KEB • L3-20, Main Circuit DC Voltage Adjustment Gain Sets the proportional gain for controlling the DC bus voltage and keeping it at the desired level during KEB 2 operation. • L3-21, Accel/Decel Rate Calculation Gain Sets the gain used to calculate the acceleration or deceleration rate when KEB 2 is active. • L3-24, Motor Acceleration Time This value is used to estimate the regenerative power fed back from the mechanics to the drive DC bus during KEB 2. • L3-25, Load Inertia Ratio This value is used to estimate the regenerative power fed back from the mechanics to the drive DC bus during KEB 2.

n L2-06: KEB Deceleration Time (KEB 1 only)

Sets the time to decelerate from the frequency reference when the KEB command was input down to zero speed. It can be used to decelerate different drives down to zero in the same time and thereby keep a constant speed ratio. When L2-06 is set to 0.0 s, the time set in parameter C1-09 (set for deceleration from maximum frequency to zero) is used for the deceleration.

No. Name Setting Range Default

n L2-07: KEB Acceleration Time (KEB 1 only)

Sets the time to reaccelerate from the speed when KEB was deactivated to the frequency reference. It can be used to accelerate different drives up to their frequency reference in the same time and thereby keep a constant speed ratio. When set to 0, the drive will accelerate back up to speed according to parameters C1-01 through C1-08 (set for acceleration from zero to maximum frequency).

5.8 L: Protection Functions

L2-06 — KEB Deceleration Time — PDF page 220

Source row No. Name Setting Range Default
1 L2-06 KEB Deceleration Time 0.0 to 200.0 s 0.0 s

Manual — KEB gains and acceleration stall prevention — page 221

Source reference: SIEP C71060618F, December 2016, physical PDF page 221. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

n L2-08: Frequency Gain at KEB Start (KEB 1 only)

When KEB 1 is activated, the output frequency is reduced in a single step in order to quickly get the motor into a regenerative state. The amount of this frequency reduction can be calculated using the following formula: Amount of reduction = Slip frequency prior to KEB x (L2-08/100) x 2

n L2-11: Desired DC Bus Voltage during KEB (KEB 2 only)

Sets the desired voltage in the DC bus during KEB 2 operation.

<1> Values are for 200 V class drives and must be doubled for 400 V class drives.

u L3: Stall Prevention

When the load is too high or acceleration and deceleration times are too short, the motor may be unable to keep up with the frequency reference, resulting in excessive slip. This “stalling” makes it impossible to decelerate or accelerate. The drive can prevent the motor from stalling and still reach the desired speed without the user needing to change the acceleration or deceleration time settings. The Stall Prevention function can be set separately for acceleration, operating at constant speeds, and deceleration.

n L3-01: Stall Prevention Selection during Acceleration

Stall Prevention during acceleration is used when the motor loses speed during acceleration due to a relatively large load. It prevents overcurrent and motor overload (oL1) from occurring. This parameter sets the Stall Prevention method for acceleration.

<1> Setting 2 is not available for PM OLV.

Setting 0: Disabled No Stall Prevention is provided. If the acceleration time setting is too short, the drive may not be able to accelerate within the set time and the motor may stall.

Setting 1: Enabled Enables Stall Prevention during acceleration. The operation depends on the selected control mode. • V/f or Open Loop Vector Control: When the output current exceeds 85% of the level set in parameter L3-02, the acceleration rate is reduced. The acceleration is stopped when the current exceeds L3-02. Acceleration continues when the current falls below L3-02. The Stall Prevention level is automatically reduced in the field weakening area. Refer to L3-03: Stall Prevention Limit During Acceleration on page 223.

5.8 L: Protection Functions

Parameter Details

L2-07 — KEB Acceleration Time — PDF page 221

Source row No. Name Setting Range Default
1 L2-07 KEB Acceleration Time 0.0 to 25.5 s 0.0 s

L2-08 — Minimum Frequency Gain at KEB Start — PDF page 221

Source row No. Name Setting Range Default
1 L2-08 Minimum Frequency Gain at KEB Start 0 to 300% 100%

L2-11 — Desired DC Bus Voltage during KEB — PDF page 221

Source row No. Name Setting Range Default
1 L2-11 Desired DC Bus Voltage during KEB 150 to 400 V <1> E1-01 x 1.22

L3-01 — Stall Prevention Selection during Acceleration — PDF page 221

Source row No. Name Setting Range Default
1 L3-01 Stall Prevention Selection during Acceleration 0 to 2 <1> 1

Manual — Induction and PM acceleration stall behavior — page 222

Source reference: SIEP C71060618F, December 2016, physical PDF page 222. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output current; Stall Prevention Level During Acceleration L3-02 andL3-02−15%; Time. Output frequency pauses while current above threshold; Controls the output frequency to prevent the motor from stalling. Qualitative waveform; no unprinted timing inferred. Exact source geometry, routing and unprinted numerical values remain original-only.

Output current; L3-02; 15% ofL3-02; Time. Output frequency; 100 ms before deceleration and 100 ms before reacceleration; Deceleration usingL3-22. Source PM operation conditions andL3-01=1 retained. Exact source geometry, routing and unprinted numerical values remain original-only.

Figure 5.81 Stall Prevention During Acceleration for Induction Motors

• Open Loop Vector Control for PM: Acceleration is stopped when the output current reaches the level set in parameter L3-02, and after 100 ms the drive decelerates using the deceleration time set in parameter L3-22 (Refer to L3-22: Deceleration Time at Stall Prevention During Acceleration on page 223). When the current falls below 85% of L3-02, deceleration is stopped. The drive will attempt to reaccelerate again after 100 ms.

Figure 5.82 Stall Prevention During Acceleration for Permanent Magnet Motors

Setting 2: Intelligent Stall Prevention When L3-01 = 2, the drive will disregard the selected acceleration time and try to accelerate in the minimum time. The acceleration rate is adjusted so that the current does not exceed the value set in parameter L3-02.

n L3-02: Stall Prevention Level During Acceleration

Sets the output current level at which the Stall Prevention during acceleration is activated.

No. Name Setting Range Default

<1> The upper limit and default value is determined by the duty rating and the carrier frequency derating selection (C6-01 and L8-38 respectively).

• If stalling occurs with L3-02 set to its default value when using a motor that is relatively small compared to the drive, try lowering L3-02. • When operating the motor in the constant power range, also set parameter L3-03.

5.8 L: Protection Functions

L3-02 — Stall Prevention Level during Acceleration — PDF page 222

Source row No. Name Setting Range Default
1 L3-02 Stall Prevention Level during Acceleration 0 to 150% <1> <1>

Manual — Deceleration stall limits and voltage levels — page 223

Source reference: SIEP C71060618F, December 2016, physical PDF page 223. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Stall Prevention level during Acceleration; L3-02 upper level, L3-03 lower limit; E1-06 Base frequency; Output frequency. Solid declining curve bounded by lower limit and dashed extension; no unprinted curve values. Exact source geometry, routing and unprinted numerical values remain original-only.

n L3-03: Stall Prevention Limit During Acceleration

The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets the lower limit for this reduction as a percentage of the drive rated current.

No. Name Setting Range Default

Figure 5.83 Stall Prevention Level and Limit During Acceleration

n L3-22: Deceleration Time at Stall Prevention During Acceleration

Sets the brief deceleration time used when stalling occurs while accelerating a PM motor. When set to 0, this function is disabled and the drive will decelerate at the selected deceleration time when stalling occurs. The function is effective only in Open Loop Vector Control for PM motors and if parameter L3-01 is set to 1.

n L3-04: Stall Prevention Selection during Deceleration

Stall Prevention during deceleration can control the deceleration based on the DC bus voltage and prevent an overvoltage fault caused by high inertia or rapid deceleration. Selects the Stall Prevention method during deceleration.

<1> Settings 3 and 4 are not available in OLV/PM control mode. <2> Setting 7 is available in drive software versions PRG: 1020 and later.

Setting 0: Disabled When this setting is used, the drive decelerates according to the set deceleration time. With high inertia loads or rapid deceleration, an overvoltage (ov) fault may occur. In this case use braking options or switch to another L3-04 selection.

Note: Use this setting or set L3-04 to 3 whenever a Dynamic Braking Resistor or another braking option is used.

Setting 1: General Purpose Stall Prevention With this setting the drive tries to decelerate in the set deceleration time. When the DC bus voltage exceeds the Stall Prevention level, the drive pauses deceleration. Deceleration continues as soon as the DC bus voltage drops below that level. Stall Prevention may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall Prevention depends on the input voltage setting E1-01.

Drive Input Voltage Stall Prevention Level during Deceleration

Note: 1. This setting should not be used in combination with a Dynamic Braking Resistor or other braking options. If Stall Prevention during deceleration is enabled, it will be triggered before the braking resistor option can operate.

5.8 L: Protection Functions

Parameter Details

200 V Class | 200 V Class

400 V Class | E1-01 ≥ 400 V

400 V Class | E1-01 < 400 V

L3-03 — Stall Prevention Limit during Acceleration — PDF page 223

Source row No. Name Setting Range Default
1 L3-03 Stall Prevention Limit during Acceleration 0 to 100% 50%

L3-22 — Deceleration Time at Stall Prevention During Acceleration — PDF page 223

Source row No. Name Setting Range Default
1 L3-22 Deceleration Time at Stall Prevention During Acceleration 0 to 6000.0 s 0.0 s

L3-04 — Stall Prevention Selection During Deceleration Selection — PDF page 223

Source row No. Name Setting Range Default
1 L3-04 Stall Prevention Selection During Deceleration Selection 0 to 4; 7 <1> <2> 1

Stall prevention during deceleration by input voltage — PDF page 223

Source row Drive Input Voltage class E1-01 condition (merged 200 V cell retained) Stall Prevention Level during Deceleration
1 200 V Class 200 V Class Vdc = 380 V
2 400 V Class E1-01 ≥ 400 V Vdc = 760 V
3 400 V Class E1-01 < 400 V Vdc = 660 V

Manual — Intelligent deceleration and run stall prevention — page 224

Source reference: SIEP C71060618F, December 2016, physical PDF page 224. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output Frequency; Time; specified deceleration time; stair-step Deceleration characteristics when Stall Prevention was triggered during deceleration, compared with dashed direct ramp. No numeric time inferred. Exact source geometry, routing and unprinted numerical values remain original-only.

  1. This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider using a braking option. Figure 5.84 illustrates the function of Stall Prevention during deceleration.

Figure 5.84 Stall Prevention During Deceleration

Setting 2: Intelligent Stall Prevention With this setting the drive adjusts the deceleration rate so that the DC bus voltage is kept at the level set in parameter L3-17. This way the shortest possible deceleration time is achieved while the motor is protected from stalling. The deceleration time that has been selected is disregarded, but the achievable deceleration time cannot be smaller than 1/10 of the set deceleration time. This function uses the following parameters for adjusting the deceleration rate: • DC bus voltage gain L3-20 • Deceleration rate calculations gain L3-21 • Inertia calculations for motor acceleration time L3-24 • Load inertia ratio L3-25 Refer to these parameter descriptions for details.

Note: As the deceleration time is not constant, Intelligent Stall Prevention should not be used in applications where stopping accuracy is a concern. Use braking options instead.

Setting 3: Stall Prevention with Braking Option Enables the Stall Prevention function while using a braking resistor. Use this setting if overvoltage occurs with L3-04 disabled when using a braking resistor. This makes it possible to reduce the deceleration time.

Setting 4: Overexcitation Deceleration Enables overexcitation deceleration. Overexcitation Deceleration (increasing the motor flux) shortens the deceleration time compared to deceleration with no Stall Prevention (L3-04 = 0). Repetitive or long overexcitation deceleration can result in motor overheat. In such situations, either shorten the deceleration time setting or use a braking resistor option. Use parameters n3-13 and n3-23 for fine-tuning this function.

Note: Because the allowable flux level for overexcitation varies based on the flux saturation characteristics of the motor, set the proper overexcitation level by adjusting the excitation gain in parameter n3-13. Motor characteristics and inertia of the machine influence the deceleration time during overexcitation deceleration.

Setting 7: Overexcitation Deceleration 3 Provides faster deceleration than normal Overexcitation Deceleration (L3-04 = 4) by increasing the amount of overexcitation current applied to the motor.

Note: When operation permits, use normal Overexcitation Deceleration (L3-04 = 4).

n L3-05: Stall Prevention Selection During Run

Stall Prevention During Run can prevent a motor from stalling by automatically reducing the speed when a transient overload occurs while the motor is running at constant speed. This parameter selects the Stall Prevention During Run method.

No. Name Setting Range Default

Note: 1. This function is not available in Open Loop Vector Control. Use the torque limit function instead. 2. When output frequency is 6 Hz or less, Stall Prevention During Run is disabled regardless of the setting in L3-05/06.

5.8 L: Protection Functions

L3-05 — Stall Prevention Selection During Run — PDF page 224

Source row No. Name Setting Range Default
1 L3-05 Stall Prevention Selection During Run 0 to 2 1

Manual — Run stall settings and overvoltage suppression — page 225

Source reference: SIEP C71060618F, December 2016, physical PDF page 225. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 0: Disabled Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an oC or oL fault.

Setting 1: Decelerate Using C1-02 If the current exceeds the Stall Prevention level set in parameter L3-06, the drive decelerates at Decel Time 1 (C1-02). Once the current level drops below the value of L3-06 minus 2% for 100 ms it accelerates back to the frequency reference at the active acceleration time.

Setting 2: Decelerate Using C1-04 Same as setting 1 except the drive decelerates at decel time 2 (C1-04).

n L3-06: Stall Prevention Level During Run

Sets the current level for Stall Prevention During Run. Depending on the setting of parameter L3-23 the level is automatically reduced in the constant power range (speed beyond base speed).

No. Name Setting Range Default

<1> The upper limit and default value for this setting are determined by C6-01, Drive Duty Selection, and L8-38, Carrier Frequency Reduction Selection.

n L3-23: Automatic Stall Prevention Level Reduction

This function reduces the Stall Prevention during run level in the constant power range.

Setting 0: Disabled The level set in L3-06 is used throughout the entire speed range.

Setting 1: Enabled The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.

n Overvoltage Suppression Function

This function suppresses overvoltage faults by slightly increasing the output frequency when the DC bus voltage rises. It can be used to drive loads with cyclic regenerative operation, such as punch presses or other applications that involve repetitive crank movements. The output frequency is adjusted during ov suppression so that the DC bus voltage does not exceed the level set in parameter L3-17. In addition to the parameters explained below, ov suppression also uses these settings for frequency adjustment: • DC bus voltage gain L3-20 • Deceleration rate calculations gain L3-21 • Inertia calculations for motor acceleration time L3-24 • Load inertia ratio L3-25 Note: 1. The motor speed will exceed the frequency reference when overvoltage suppression is triggered. Consequently, overvoltage suppression is not appropriate in applications that require a perfect match between the frequency reference and the actual motor speed. 2. Disable overvoltage suppression when using a braking resistor. 3. Overvoltage may still occur if there is a sudden increase to a regenerative load. 4. This function is enabled only when operating just below the maximum frequency. Overvoltage suppression does not increase the output frequency beyond the maximum frequency. If this is required by the application increase the maximum frequency and change the base frequency setting.

n L3-11: Overvoltage Suppression Function Selection

Enables or disables the overvoltage suppression function.

Setting 0: Disabled The output frequency is not adjusted. A regenerative load may trip the drive with an overvoltage fault. Use this setting if braking options are installed.

5.8 L: Protection Functions

Parameter Details

Run

L3-06 — Stall Prevention Level During Run — PDF page 225

Source row No. Name Setting Range Default
1 L3-06 Stall Prevention Level During Run 30 to 150 <1> <1>

L3-23 — Automatic Reduction Function Selection for Stall Prevention during — PDF page 225

Source row No. Name Setting Range Default
1 L3-23 Automatic Reduction Function Selection for Stall Prevention during Run 0 or 1 0

L3-11 — ov Suppression Function Selection — PDF page 225

Source row No. Name Setting Range Default
1 L3-11 ov Suppression Function Selection 0 or 1 0

Manual — Suppression voltage and inertia gains — page 226

Source reference: SIEP C71060618F, December 2016, physical PDF page 226. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 1: Enabled When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by increasing the output frequency.

n L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention

Sets the target DC bus voltage target level used by the overvoltage suppression function (L3-11 = 1) and Intelligent Stall Prevention during deceleration (L3-04 = 2).

No. Name Setting Range Default

<1> Values are for 200 V class drives and must be doubled for 400 V class drives. <2> This value is initialized when E1-01 is changed.

n L3-20: DC Bus Voltage Adjustment Gain

Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Kinetic Energy Backup 2, and Intelligent Stall Prevention during deceleration (L3-04 = 2) in order to control the DC bus voltage.

Adjustment for KEB 2 and Intelligent Stall Prevention During Deceleration • Increase this setting slowly in steps of 0.1 if overvoltage (ov) or undervoltage (Uv1) occurs at the beginning of deceleration while KEB Ride-Thru 2 is enabled or Intelligent Stall Prevention during deceleration is activated. • If this setting is too high, then a fair amount of speed or torque ripple can result.

Adjustment for Overvoltage Suppression • Increase this setting slowly in steps of 0.1 if overvoltage suppression is enabled (L3-11 = 1) and a sudden increase in a regenerative load results in an overvoltage (ov) fault. • If this setting is too high, excessive speed or torque ripple can result.

n L3-21: Accel/Decel Rate Calculation Gain

Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Kinetic Energy Backup 2, and Intelligent Stall Prevention during deceleration (L3-04 = 2) in order to calculate acceleration and deceleration rates.

<1> This value is reset to its default value when the control mode is changed (A1-02). The value shown here is for Open Loop Vector Control.

Adjustment for KEB 2 and Intelligent Stall Prevention During Deceleration • Reduce the setting in steps of 0.05 if there is a fairly large speed or current ripple during KEB Ride-Thru 2 or when using Intelligent Stall Prevention during deceleration. • Small reductions in the acceleration gain can also help solve problems with overvoltage and overcurrent. • Decreasing this setting too much can result in a slow DC bus voltage control response and may also lengthen deceleration times beyond optimal levels.

Adjustment for Overvoltage Suppression • Increase this setting in steps of 0.1 if overvoltage occurs as a result of a regenerative load when overvoltage suppression is enabled (L3-11 = 1). • If there is a fairly large speed ripple when overvoltage suppression is enabled, then decrease L3-21 in steps of 0.05.

n L3-24: Motor Acceleration Time for Inertia Calculations

Sets the time it takes to accelerate the motor from stop to the maximum speed at motor rated torque. This parameter should be set when using KEB Ride-Thru 2, Intelligent Stall Prevention during deceleration (L2-04 = 2), or the overvoltage suppression function (L3-11 = 1).

5.8 L: Protection Functions

Intelligent Stall Prevention During Deceleration

L3-17 — Target DC Bus Voltage for Overvoltage Suppression, and — PDF page 226

Source row No. Name Setting Range Default
1 L3-17 Target DC Bus Voltage for Overvoltage Suppression, and Intelligent Stall Prevention During Deceleration <1> 150 to 400 <1> <2> 370 V

L3-20 — DC Bus Voltage Adjustment Gain — PDF page 226

Source row No. Name Setting Range Default
1 L3-20 DC Bus Voltage Adjustment Gain 0.00 to 5.00 1.00

L3-21 — Accel/Decel Rate Calculation Gain — PDF page 226

Source row No. Name Setting Range Default
1 L3-21 Accel/Decel Rate Calculation Gain 0.00 to 200.00 1.00 <1>

L3-24 — Motor Acceleration Time for Inertia Calculations — PDF page 226

Source row No. Name Setting Range Default
1 L3-24 Motor Acceleration Time for Inertia Calculations 0.001 to 10.000 Determined by o2-04, E2-11, and <1> E5-01

Manual — Inertia calculations and speed detection — page 227

Source reference: SIEP C71060618F, December 2016, physical PDF page 227. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

L3-24 = (2 · π · J [kgm²] · n_rated [r/min]) / (60 · T_rated [Nm]). Source fraction transcribed as a parenthesized ratio; no computed value inferred. Exact geometry, routing and unprinted numerical values remain original-only.

T_rated [Nm] = (60 · P_Motor [kW] · 10³) / (2 · π · n_rated [r/min]). Source fraction transcribed as a parenthesized ratio. Exact geometry, routing and unprinted numerical values remain original-only.

L3-25 = Machine Inertia / Motor Inertia. No machine inertia inferred. Exact geometry, routing and unprinted numerical values remain original-only.

<1> Parameter L3-24 is defaulted for a Yaskawa standard 4-pole motor. During Auto-Tuning, L3-24 will be initialized to a Yaskawa standard 4-pole motor if parameter E2-11 is changed. This value also changes based on the motor code set to E5-01 when using the Open Loop Vector Control Mode for PM motors.

Calculations are made as follows:

The rated torque can be calculated as follows:

n L3-25: Load Inertia Ratio

Determines the ratio between the rotor inertia and the load. Set this parameter when using KEB Ride-Thru 2, Intelligent Stall Prevention during deceleration (L3-04 = 2), or the overvoltage suppression function (L3-11 = 1).

No. Name Setting Range Default

When set incorrectly, a fairly large current ripple can result during KEB Ride-Thru 2 and overvoltage suppression (L3-11 = 1) or other faults such as ov, Uv1, and oC may occur. Parameter L3-25 can be calculated by:

u L4: Speed Agree/Frequency Reference Loss Detection

These parameters set up the speed agree and speed detection functions which can be assigned to the multi-function output terminals.

n L4-01/02: Speed Agreement Detection Level and Detection Width

Parameter L4-01 sets the detection level for the digital output functions “Speed Agree 1”, “User Set Speed Agree 1”, “Frequency Detection 1”, and “Frequency Detection 2”. Parameter L4-02 sets the hysteresis level for these functions.

Refer to H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection on page 195, Settings 2, 3, 4, and 5.

n L4-03/04: Speed Agreement Detection Level and Detection Width (+/-)

Parameter L4-03 sets the detection level for the digital output functions “Speed Agree 2”, “User Set Speed Agree 2”, “Frequency Detection 3”, and “Frequency Detection 4”. Parameter L4-04 sets the hysteresis level for these functions.

Refer to H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection on page 195, Settings 13, 14, 15, and 16.

n L4-05: Frequency Reference Loss Detection Selection

The drive can detect a loss of an analog frequency reference from input A1 or A2. Reference loss is detected when the frequency reference value reduces for 90% within 400 ms.

5.8 L: Protection Functions

Parameter Details

L3-25 — Load Inertia Ratio — PDF page 227

Source row No. Name Setting Range Default
1 L3-25 Load Inertia Ratio 0.0 to 1000.0 1.0

L4-01 / L4-02 — Speed Agreement Detection Level — PDF page 227

Source row No. Name Setting Range Default
1 L4-01 Speed Agreement Detection Level 0.0 to 400.0 Hz 0.0 Hz
2 L4-02 Speed Agreement Detection Width 0.0 to 20.0 Hz 2.0 Hz

L4-03 / L4-04 — Speed Agreement Detection Level (+/-) — PDF page 227

Source row No. Name Setting Range Default
1 L4-03 Speed Agreement Detection Level (+/-) 0.0 to 400.0 Hz 0.0 Hz
2 L4-04 Speed Agreement Detection Width (+/-) 0.0 to 20.0 Hz 2.0 Hz

Manual — Reference-loss and speed agreement conditions — page 228

Source reference: SIEP C71060618F, December 2016, physical PDF page 228. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Analog frequency reference 100%,80%,10%; decline 400 ms; Loss of Reference output OFF/ON/OFF; time. Output shown ON after the reference reaches 10%, and OFF as the recovered reference rises above the 80% line. No unprinted timing inferred. Exact geometry, routing and unprinted numerical values remain original-only.

Figure 5.85 Loss of Reference Function

To have a fault output trigger when frequency reference loss occurs, set H2-01, H2-02, or H2-03 to “C”. Refer to Setting C: Frequency Reference Loss on page 199 for details on setting the output function. Parameter L4-05 selects the operation when a frequency reference loss is detected.

No. Name Setting Range Default

Setting 0: Stop The drive will stop the motor.

Setting 1: Continue Operation with Reduced Frequency Reference The drive will continue operation at the frequency reference value set in parameter L4-06. When the external frequency reference value is restored, the operation is continued with the frequency reference.

n L4-06: Frequency Reference at Reference Loss

Sets the frequency reference level the drive runs with when L4-05 = 1 and a reference loss was detected. The value is set as a percentage of the frequency reference before the loss was detected.

n L4-07: Speed Agreement Detection Selection

Determines when frequency detection is active using parameters L4-01 through L4-04.

Setting 0: No Detection During Baseblock

Setting 1: Detection Always Enabled

n L4-08: Speed Agreement Detection Conditions

Note: Parameter available in drive software versions PRG: 1016 and later. Determines whether soft-starter output or estimated motor speed constitutes a speed agreement situation.

Setting 0: Match Speed with the Soft-Starter Output

Setting 1: Match Frequency Reference and Motor Speed

Note: In V/f control the drive ignores the value set to L4-08 and refers to the soft-starter output to determine whether a speed agreement situation has been reached. The following functions are influenced by the speed agree condition: • Overtorque alarms oL3 and oL4 when parameters L6-01 or L6-04 are set to 1, 3, 5, or 7. • DriveWorksEZ functions that use speed agree output • The Up 2/Down 2 functions • Multi-Function Digital Output Settings

5.8 L: Protection Functions

L4-05 — Frequency Reference Loss Detection Selection — PDF page 228

Source row No. Name Setting Range Default
1 L4-05 Frequency Reference Loss Detection Selection 0 or 1 0

L4-06 — Frequency Reference at Reference Loss — PDF page 228

Source row No. Name Setting Range Default
1 L4-06 Frequency Reference at Reference Loss 0.0 to 100.0% 80.0%

L4-07 — Speed Agreement Detection Selection — PDF page 228

Source row No. Name Setting Range Default
1 L4-07 Speed Agreement Detection Selection 0, 1 0

L4-08 — Speed Agreement Detection Conditions — PDF page 228

Source row No. Name Setting Range Default
1 L4-08 Speed Agreement Detection Conditions 0, 1 0

Manual — Holding-brake conditions and status registers — page 229

Source reference: SIEP C71060618F, December 2016, physical PDF page 229. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output Frequency; L4-01;2.0 Hz(fixed) hysteresis; Time; Frequency Detection 2 ON/OFF. Rising waveform crosses L4-01; output releases at the lower hysteresis threshold. Source holding-brake conditions retained in table and prose. Exact geometry, routing and unprinted numerical values remain original-only.

Setting Value Function

• MEMOBUS/Modbus Monitor Data

Register No. Description

Drive Status 2

Drive Status (U1-12)

• U: Monitor

No. Name Description

n Notes on Drive Control for Holding Brake Applications

The frequency detection function is used for controlling the brake. When an external Baseblock command is present while a Run command is active, the frequency reference will be kept as long as the Run command is active. To avoid improper brake operation make sure that frequency detection is set so that the brake does not open during Baseblock (L4-07 = “0”, default).

Brake Open/Close Brake Activation Level Function Parameter Signal Parameter

<1> If the load slips during stop, make it greater than E1-09 or 2.0 Hz until the load no longer slips.

Figure 5.86 Frequency Detection 2

The braking sequence should be designed as follows: • A normally open signal (N.O.) should be used to control the brake so that it is released when terminal MA-MC closes. • An external circuit should be added to ensure the brake is fully applied in case of a fault or emergency condition. • An additional external circuit should also be added to ensure the brake releases properly when an Up/Down Command is entered. When changing the speed using an analog signal, make sure that the source of the frequency reference is assigned to the control circuit terminals (b1-01 = 1). A sequence to open and close the holding brake appears in the diagram below.

5.8 L: Protection Functions

Parameter Details

002CH | Bit 2

002CH | Bit 3

002CH | Bit 4

002CH | Bit 5

004BH | Bit 4

L4-08 affected digital output functions — PDF page 229

Source row Setting Value Function
1 2 Frequency (Speed) Agree 1
2 3 User-set Frequency (Speed) Agree 1
3 4 Frequency (FOUT) Detection 1
4 5 Frequency (FOUT) Detection 2
5 13 Frequency (Speed) Agree 2
6 14 User-set Frequency (Speed) Agree 2
7 15 Frequency (FOUT) Detection 3
8 16 Frequency (FOUT) Detection 4

U1-12 — Drive Status — PDF page 229

Source row No. Name Description
1 U1-12 Drive Status The fifth digit from the right side: During Speed Agree

L4-08 MEMOBUS monitor bits — PDF page 229

Source row Register No. Status bit Description
1 002CH Bit 2 Speed Agree, 1: During Agree
2 002CH Bit 3 User-set Speed Agree, 1: During Agree
3 002CH Bit 4 Frequency Detection 1, 1: Output Frequency ≤ L4-01
4 002CH Bit 5 Frequency Detection 2, 1: Output Frequency ≥ L4-01
5 004BH Bit 4 1: During Speed Agree

Holding brake frequency detection conditions — PDF page 229

Source row Brake function Brake parameter Activation signal Activation parameter
1 Frequency Detection Conditions L4-07 = 0 Frequency Detection Level <1> L4-01 = 2.0 to 3.0 Hz
2 Frequency Detection 2 H2-01 = 5 Frequency Detection Width 2.0 Hz (fixed)

Manual — Holding-brake timing and fault restart — page 230

Source reference: SIEP C71060618F, December 2016, physical PDF page 230. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

S1-SC UP OFF/ON; Output frequency 0; b6-02, b6-01, L4-01, d1-03, d1-01(Enabled when b1-01=0); b4-01 printed next to DC Injection braking. MA-MC Frequency Detection 2(H2-01=5) ON/OFF; Holding brake Closed/Open/Closed; Time. Parameter b4-01 retained literally, not substituted with a DC-braking parameter. Exact geometry, routing and unprinted numerical values remain original-only.

Figure 5.87 Holding Brake Time Chart

u L5: Fault Restart

The drive can be set up to perform a self-diagnostic check and resume the operation after a fault has occurred. If the self-check is successful and the cause of the fault has disappeared, the drive restarts by performing Speed Search (Refer to b3: Speed Search on page 130 for details). The drive can attempt to restart itself following the faults listed below.

Table 5.30 Restart Faults

Setting Function

<1> When L2-01 is set to 1 or 2 (continue operation during momentary power loss)

Use parameters L5-01 to L5-05 to set up automatic fault restart. To output a signal during fault restart, set H2-01, H2-02, or H2-03 to 1E. Do not use the fault restart function in elevator applications.

n L5-01: Number of Auto Restart Attempts

Sets the number of times that the drive may attempt to restart itself.

No. Name Setting Range Default

The method of incrementing the restart counter is determined by the setting of parameter L5-05. When the counter reaches the number set in L5-01 the operation stops and the fault has to be reset manually after correcting the cause. The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter reaches the number set in L5-01 the operation stops and the fault has to be reset manually after correcting the cause. The number of fault restarts is reset back to zero when: • The drive operates normally for ten minutes following a fault restart. • A fault is cleared manually after protective functions are triggered. • The power supply is cycled.

n L5-02: Auto Restart Fault Output Operation Selection

Selects if the fault output (H2-01/02/03 = E) is set when the drive attempts to restart.

5.8 L: Protection Functions

Table5.30 Restart Faults left — PDF page 230

Source row Setting Function
1 GF (Ground Fault)
2 LF (Output Open Phase)
3 oC (Overcurrent)
4 oH1 (Drive Overheat)
5 oL1 (Motor Overload)
6 oL2 (Drive Overload)
7 oL3 (Overtorque 1)
8 oL4 (Overtorque 2)

Table5.30 Restart Faults right — PDF page 230

Source row Setting Function
1 ov (DC Bus Overvoltage)
2 PF (Input Phase Loss)
3 rH (Braking Resistor Fault)
4 rr (Braking Transistor Fault)
5 STo (Step Out Detection)
6 Uv1 (DC Bus Undervoltage) <1>

L5-01 — Number of Auto Restarts — PDF page 230

Source row No. Name Setting Range Default
1 L5-01 Number of Auto Restarts 0 to 10 0

L5-02 — Auto Restart Fault Output Operation Selection — PDF page 230

Source row No. Name Setting Range Default
1 L5-02 Auto Restart Fault Output Operation Selection 0 or 1 0

Manual — Fault restart counter and torque detection — page 231

Source reference: SIEP C71060618F, December 2016, physical PDF page 231. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Motor current/torque; threshold L6-02/05;10% hysteresis; L6-03/06 delay at both rising crossings; Torque detection 1(NO) / Torque detection 2(NO) ON pulses. No current or torque values inferred beyond source labels. Exact geometry, routing and unprinted numerical values remain original-only.

Setting 0: No Fault Output

Setting 1: Fault Output is Set

n L5-04: Fault Reset Interval Time

Determines the amount of time to wait between attempts to restart the drive when parameter L5-05 is set to 1.

No. Name Setting Range Default

n L5-05: Fault Reset Operation Selection

Setting 0: Count Successful Restarts The drive will continuously attempt to restart. If a restart trial is successful, the restart counter is increased. This operation is repeated each time a fault occurs until the counter reaches the value set in L5-01.

Setting 1: Count Restart Attempts The drive will try to restart using the time interval set in parameter L5-04. Each attempt is counted, whether it was successful or not.

u L6: Torque Detection

The drive provides two independent torque detection functions that trigger an alarm or fault signal when the load is too heavy (oL), or suddenly drops (UL). They are set up using the L6-□□ parameters. To indicate the underload or overload condition to an external device, digital outputs should be programmed as shown below.

H2-01 /02/03 Setting Description

Figure 5.88 and Figure 5.89 show the function of overtorque and undertorque detection.

Figure 5.88 Overtorque Detection Operation

5.8 L: Protection Functions

Parameter Details

L5-04 — Fault Reset Interval Time — PDF page 231

Source row No. Name Setting Range Default
1 L5-04 Fault Reset Interval Time 0.5 to 600.0 s 10.0 s

L5-05 — Fault Reset Operation Selection — PDF page 231

Source row No. Name Setting Range Default
1 L5-05 Fault Reset Operation Selection 0 or 1 0

Torque detection output N.O./N.C. assignments — PDF page 231

Source row H2-01 /02/03 Setting Description
1 B Torque detection 1, N.O. (output close when over-/underload is detected)
2 17 Torque detection 1, N.C. (output opens when over-/underload is detected)
3 18 Torque detection 2, N.O. (output close when over-/underload is detected)
4 19 Torque detection 2, N.C. (output opens when over-/underload is detected)

Manual — Torque detection modes and fault codes — page 232

Source reference: SIEP C71060618F, December 2016, physical PDF page 232. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Motor current/torque; threshold L6-02/05;10% hysteresis; L6-03/06 delay at both downward crossings; Torque detection 1(NO) or Torque detection 2(NO) ON pulses. No unprinted threshold inferred. Exact geometry, routing and unprinted numerical values remain original-only.

Figure 5.89 Undertorque Detection Operation

Note: 1. The torque detection function uses a hysteresis of 10% of the drive rated output current/motor rated torque. 2. In V/f Control and Open Loop Vector Control for PM, the level is set as a percentage of the drive rated output current. In Open Loop Vector, it is set as a percentage of the motor rated torque.

Note: When overtorque occurs in the application, the drive may stop due to overcurrent (oC) or overload (oL1). To prevent this, an overload situation should be indicated to the controller before oC or oL1 occur in the drive. Use the torque detection for this purpose. Use undertorque detection to discover application problems like a torn belt, a pump shutting off, or other similar trouble.

n L6-01/L6-04: Torque Detection Selection 1/2

The torque detection function is triggered when the current/torque exceeds the levels set in parameter L6-02/L6-05 for longer than the time set in L6-03L6-/06. The parameters L6-01/L6-04 select the detection condition and the operation at detection.

No. Name Setting Range Default

Setting 0: Disabled

Setting 1: oL3/oL4 at Speed Agree - Alarm Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation continues after detection and an oL3/oL4 alarm is triggered.

Setting 2: oL3/oL4 at Run - Alarm Overtorque detection works whenever a Run command is active. The operation continues after detection and an oL3/oL4 alarm is triggered.

Setting 3: oL3/oL4 at Speed Agree - Fault Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation is stopped and an oL3/oL4 fault is triggered.

Setting 4: oL3/oL4 at Run - Fault Overtorque detection works whenever a Run command is active. The operation is stopped and an oL3/oL4 fault is triggered.

Setting 5: UL3/UL4 at Speed Agree - Alarm Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation continues after detection and a UL3/UL4 alarm is triggered.

Setting 6: oL5/UL5 at Run - Alarm Undertorque detection works whenever a Run command is active. The operation continues after detection and an oL5/UL5 alarm is triggered.

Setting 7: UL5 at Speed Agree - Fault Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation is stopped and a UL5 fault is triggered.

Setting 8: oL3/oL4 at Run - Fault Undertorque detection works whenever a Run command is active. The operation is stopped and an oL3/oL4 fault is triggered.

n L6-02/L6-05: Torque Detection Level 1/2

These parameters the detection levels for the torque detection functions 1 and 2.

5.8 L: Protection Functions

L6-01/ L6-04 — Torque Detection Selection 1/2 — PDF page 232

Source row No. Name Setting Range Default
1 L6-01/ L6-04 Torque Detection Selection 1/2 0 to 8 0

Manual — Torque levels and mechanical weakening — page 233

Source reference: SIEP C71060618F, December 2016, physical PDF page 233. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

Note: 1. The torque detection level 1 (L6-02) can also be supplied by an analog input set to H3-02/10 = 7. In this case the analog value has priority and the setting L6-02 is disregarded. Torque detection level 2 (L6-05) cannot be set by an analog input. 2. The detection levels for overtorque and undertorque are set as a percentage of the drive rated current when using V/f Control or Open Loop Vector Control. When using Closed Loop Vector Control, the drive sets torque detection as a percentage of the motor rated current.

n L6-03/L6-06: Torque Detection Time 1/2

These parameters set the time that the levels set in L6-02/05 have to be exceeded before an alarm/fault is triggered.

n Mechanical Weakening Detection

This function can be used to detect mechanical weakening of a machine that leads to overtorque or undertorque situations after a certain machine operation time has elapsed. The function is activated in the drive when the cumulative operation counter U4-01 exceeds the time set in parameter L6-11. Mechanical weakening detection uses the torque detection 1 settings (L6-01/02/03) and triggers an oL5 fault when overtorque or undertorque occurs in the speed range determined by parameter L6-08/09. The oL5 operation is set by parameter L6-08. To output a signal for mechanical weakening detection, set H2-01, H2-02, or H2-03 to 22.

n L6-08: Mechanical Weakening Detection Operation

Decides which speed range the function is active and sets the mechanical weakening detection operation.

Setting 0: Disabled

Setting 1: Continue Running if the Speed is Greater than L6-09 (signed) - Alarm Detection when the speed is above L6-09 (signed). Upon detection the operation is continued but an oL5 alarm is output.

Setting 2: Continue Running if the Speed is Greater than L6-09 - Alarm Detection when the speed is above L6-09 (unsigned). Upon detection the operation is continued but an oL5 alarm is output.

Setting 3: Stop when Motor Speed is Greater than L6-09 (signed) Detection when the speed is above L6-09 (signed). Upon detection the operation is stopped and an oL5 fault is output.

Setting 4: Stop when Motor Speed is Greater than L6-09 Detection when the speed is above L6-09 (unsigned). Upon detection the operation is stopped and an fault is output.

Setting 5: Continue Running if the Speed is less than L6-09 (signed) - Alarm Detection when the speed is below L6-09 (signed). Upon detection the operation is continued but an oL5 alarm is output.

Setting 6: Continue Running if the Speed is less than L6-09 - Alarm Detection when the speed is below L6-09 (unsigned). Upon detection the operation is continued but an oL5 alarm is output.

Setting 7: Stop when Motor Speed is less than L6-09 (signed) Detection when the speed is below L6-09 (signed). Upon detection the operation is stopped and an oL5 fault is output.

Setting 8: Stop when Motor Speed is less than L6-09 Detection when the speed is below L6-09 (unsigned). Upon detection the operation is stopped and an oL5 fault is output.

n L6-09: Mechanical Weakening Detection Speed Level

Sets the speed level that defines the speed range for mechanical weakening detection.

5.8 L: Protection Functions

Parameter Details

L6-02 / L6-05 — Torque Detection Level 1 — PDF page 233

Source row No. Name Setting Range Default
1 L6-02 Torque Detection Level 1 0 to 300% 150%
2 L6-05 Torque Detection Level 2 0 to 300% 150%

L6-03 / L6-06 — Torque Detection Time 1 — PDF page 233

Source row No. Name Setting Range Default
1 L6-03 Torque Detection Time 1 0.0 to 10.0 s 0.1 s
2 L6-06 Torque Detection Time 2 0.0 to 10.0 s 0.1 s

L6-08 — Mechanical Weakening Detection — PDF page 233

Source row No. Name Setting Range Default
1 L6-08 Mechanical Weakening Detection 0 to 8 0

L6-09 — Mechanical Weakening Detection Speed Level — PDF page 233

Source row No. Name Setting Range Default
1 L6-09 Mechanical Weakening Detection Speed Level -110.0 to 110.0% 110%

Manual — Torque limits and control methods — page 234

Source reference: SIEP C71060618F, December 2016, physical PDF page 234. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

The value is set as a percentage of the maximum frequency. If L6-08 is set for unsigned speed detection (L6-08 = 2, 4, 6, 8) then the absolute value of L6-09 is used, i.e., negative settings will be treated as positive.

n L6-10: Mechanical Weakening Detection Time

Sets the time permitted for the situation selected in parameter L6-08 to arise before mechanical weakening is detected.

No. Name Setting Range Default

n L6-11: Mechanical Weakening Detection Start Time

Sets the drives cumulative operation time at which mechanical weakening detection is activated. If U4-01 reaches the L6-11 value, the function is activated.

u L7: Torque Limit

The torque limit function can be used to limit the torque in each of the four quadrants individually and thereby protect the machinery. It can be used in the Open Loop Vector Control mode. A digital output programmed for “During Torque Limit” (H2-01/02/03 = 30) can be switched when the drive is operating at the torque limit.

n L7-01/02/03/04: Torque Limits

These parameters set the torque limits in each operation mode.

Note: If the multi-function analog input is programmed for “10: Positive Torque Limit”, “11: Negative Torque Limit”, “12: Regenerative Torque Limit”, or “15: General Torque Limit”, the drive uses the lower value of either L7-01 through L7-04, or analog input torque limit. Refer to Setting 10/11/12/15: Positive/Negative/Regenerative/General Torque Limit (OLV only) on page 209 for details on using analog torque limits.

n L7-06: Torque Limit Integral Time Constant

Sets the integral time constant for the torque limit function.

n L7-07: Torque Limit Control Method Selection during Accel/Decel

Selects the function of torque limit during acceleration and deceleration.

Setting 0: Proportional Control The torque limit function works with P-control during acceleration and deceleration and switches to I-control at constant speed. Use this setting when acceleration or deceleration to the desired speed has priority over torque limitation during speed changes.

Setting 1: Integral Control The torque limit function always uses I-control. Use this setting when high accuracy torque limitation is required even during speed changes. Using this function may increase the acceleration time, or may prevent the motor speed from reaching the frequency reference when the torque limit is reached before.

u L8: Hardware Protection

5.8 L: Protection Functions

Deceleration

L6-10 — Mechanical Weakening Detection Time — PDF page 234

Source row No. Name Setting Range Default
1 L6-10 Mechanical Weakening Detection Time 0.0 to 10.0 s 0.1 s

L6-11 — Mechanical Weakening Detection Start Time — PDF page 234

Source row No. Name Setting Range Default
1 L6-11 Mechanical Weakening Detection Start Time 0 to 65535 h 0 h

L7-01 / L7-02 / L7-03 / L7-04 — Forward Torque Limit — PDF page 234

Source row No. Name Setting Range Default
1 L7-01 Forward Torque Limit 0 to 300% 200%
2 L7-02 Reverse Torque Limit 0 to 300% 200%
3 L7-03 Forward Regenerative Torque Limit 0 to 300% 200%
4 L7-04 Reverse Regenerative Torque Limit 0 to 300% 200%

L7-06 — Torque Limit Integral Time Constant — PDF page 234

Source row No. Name Setting Range Default
1 L7-06 Torque Limit Integral Time Constant 5 to 10000 ms 200 ms

L7-07 — Torque Limit Control Method Selection during Acceleration/ — PDF page 234

Source row No. Name Setting Range Default
1 L7-07 Torque Limit Control Method Selection during Acceleration/ Deceleration 0 or 1 0

Manual — Braking resistor and overheat protection — page 235

Source reference: SIEP C71060618F, December 2016, physical PDF page 235. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n L8-01: Internal Dynamic Braking Resistor Protection Selection (ERF type)

This parameter selects the dynamic braking resistor protection when using an optional heatsink mounted braking resistor (ERF type, 3% ED).

No. Name Setting Range Default

Setting 0: Disabled Disables the braking resistor protection. Use this setting for any braking option other than the Yaskawa ERF Type resistor.

Setting 1: Enabled Enables the protection for ERF type resistors.

n L8-02: Overheat Alarm Level

Sets the overheat alarm (oH) detection level. The drive will output an alarm when the heatsink temperature exceeds the alarm level set in parameter L8-02. If the temperature reaches the overheat fault level, the drive will trigger an oH1 fault and stop operation. When an output terminal is set for the oH pre-alarm (H2-01/02/03 = 20), the switch will close when the heatsink temperature rises above L8-02.

n L8-03: Overheat Pre-Alarm Operation Selection

Sets the operation when an overheat pre-alarm is detected.

Setting 0: Ramp to Stop If an overheat alarm occurs, the drive decelerates to stop using the selected deceleration time. If a digital output is programmed for “fault” (H2-01/02/03 = E), this output will be triggered.

Setting 1: Coast to Stop If an overheat alarm occurs, the drive switches off the output and the motor coasts to stop. If a digital output is programmed for “fault” (H2-01/02/03 = E), this output will be triggered.

Setting 2: Fast-stop If an overheat alarm occurs, the drive decelerates to stop using the Fast-stop time (C1-09). If a digital output is programmed for “fault” (H2-01/02/03 = E), this output will be triggered.

Setting 3: Alarm Only If an overheat alarm occurs, an alarm is output and the drive continues operation.

Setting 4: Operation with Reduced Speed If an overheat alarm occurs, the operation is continued but the speed is reduced to the level set in parameter L8-19. If after 10 s the oH alarm is still present, the speed is reduced once more. The amount of reduction depends on how often the alarm repeats. If the oH alarm disappears while the drive is operating at a reduced speed, then the drive will switch back to the previous speed it was reduced to before. Figure 5.90 explains the operation with reduced speed during an oH alarm. A digital output programmed for 4D is switched when the oH alarm is still active after ten reduction cycles.

5.8 L: Protection Functions

Parameter Details

L8-01 — Internal Braking Resistor Protection — PDF page 235

Source row No. Name Setting Range Default
1 L8-01 Internal Braking Resistor Protection 0 or 1 0

L8-02 — Overheat Alarm Level — PDF page 235

Source row No. Name Setting Range Default
1 L8-02 Overheat Alarm Level 50 to 130 °C Depending on size

L8-03 — Overheat Pre-Alarm Operation — PDF page 235

Source row No. Name Setting Range Default
1 L8-03 Overheat Pre-Alarm Operation 0 to 4 3

Manual — Overheat reduction and phase-loss detection — page 236

Source reference: SIEP C71060618F, December 2016, physical PDF page 236. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Output frequency; f_ref; f_ref ×(L8-19), f_ref ×(L8-19)², f_ref ×(L8-19)³, f_ref ×(L8-19)⁴;10 s intervals; oH Alarm; Reset oH Alarm; oH Alarm number 1,2,3,4,5,6,...10; Time; Digital output(4D). Frequency is reduced with successive alarms;4D rises at the tenth depicted cycle. No unprinted values calculated. Exact geometry, routing and unprinted numerical values remain original-only.

Figure 5.90 Output Frequency Reduction During Overheat Alarm

n L8-19: Frequency Reduction Rate During Overheat Pre-Alarm

Specifies how much the output frequency is reduced when L8-03 is set to 4 and an oH alarm is present. Set as a factor of the maximum output frequency.

No. Name Setting Range Default

n L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

Setting 0: Disabled

Setting 1: Enabled Enables the input phase loss detection. As detection is performed by measuring the DC bus ripple, a phase loss fault (PF) can also be triggered by power supply voltage imbalance or main circuit capacitor deterioration. Detection is disabled when: • The drive is decelerating. • No Run command is active. • Output current is less than or equal to 30% of the drive rated current.

n L8-07: Output Phase Loss Protection Selection

Enables or disables the output phase loss detection, which is triggered when the output current falls below 5% of the drive rated current.

Note: Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable this parameter in such cases.

Setting 1: Fault when One Phase is Lost An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.

5.8 L: Protection Functions

L8-19 — Frequency Reduction Rate During oH Pre-Alarm — PDF page 236

Source row No. Name Setting Range Default
1 L8-19 Frequency Reduction Rate During oH Pre-Alarm 0.1 to 0.9 0.8

L8-05 — Input Phase Loss Detection Selection — PDF page 236

Source row No. Name Setting Range Default
1 L8-05 Input Phase Loss Detection Selection 0 or 1 1

L8-07 — Output Phase Loss Protection Selection — PDF page 236

Source row No. Name Setting Range Default
1 L8-07 Output Phase Loss Protection Selection 0 to 2 1

Manual — Fan, ambient and low-speed protection — page 237

Source reference: SIEP C71060618F, December 2016, physical PDF page 237. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 2: Fault when Two Phases are Lost An output phase loss fault (LF) is triggered when two output phases are lost. The output shuts off and the motor coasts to stop.

n L8-09: Output Ground Fault Detection Selection

Enables or disables the output ground fault detection.

No. Name Setting Range Default

Setting 0: Disabled Ground faults are not detected.

Setting 1: Enabled A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.

n L8-10: Heatsink Cooling Fan Operation Selection

Selects the heatsink cooling fan operation.

Setting 0: Run with Timer The fan is switched on when a Run command is active. It is switched off with the delay set in parameter L8-11 after the Run command has been released. Using this setting extends the fan lifetime.

Setting 1: Run always The fan runs whenever power is supplied to the drive.

n L8-11: Heatsink Cooling Fan Off Delay Time

Sets the cooling fan switch off delay time if parameter L8-10 is set to 0.

n L8-12: Ambient Temperature Setting

If the temperature where the drive is mounted is above the specified values, the drive rated current must be reduced for optimal performance life. By setting the ambient temperature to parameter L8-12 and adjusting the installation method setting in L8-35, the drive rating automatically adapts to safe values.

n L8-15: oL2 Characteristics Selection at Low Speeds

Selects whether the drive overload capability (oL fault detection level) is reduced at low speeds in order to prevent premature output transistor failures.

Setting 0: Disabled The overload protection level is not reduced. Frequently operating the drive with high output current at low speed can lead to premature drive faults.

Setting 1: Enabled The overload protection level (oL2 fault detection level) is automatically reduced at speeds below 6 Hz.

5.8 L: Protection Functions

Parameter Details

L8-09 — Output Ground Fault Detection — PDF page 237

Source row No. Name Setting Range Default
1 L8-09 Output Ground Fault Detection 0 or 1 1

L8-10 — Fan Operation Selection — PDF page 237

Source row No. Name Setting Range Default
1 L8-10 Fan Operation Selection 0 or 1 0

L8-11 — Cooling Fan Switch Off Delay — PDF page 237

Source row No. Name Setting Range Default
1 L8-11 Cooling Fan Switch Off Delay 0 to 300 s 60 s

L8-12 — Ambient Temperature Setting — PDF page 237

Source row No. Name Setting Range Default
1 L8-12 Ambient Temperature Setting -10 to +50 °C 40 °C

L8-15 — oL2 Characteristics at Low Speed — PDF page 237

Source row No. Name Setting Range Default
1 L8-15 oL2 Characteristics at Low Speed 0 or 1 1

Manual — CLA, PM imbalance and installation — page 238

Source reference: SIEP C71060618F, December 2016, physical PDF page 238. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n L8-18: Software Current Limit Selection

The Software Current Limit (CLA) is a drive protection function that prevents output transistor failures caused by high current. Parameter L8-18 enables or disables this function.

Note: This setting should not be changed unless absolutely necessary. For proper drive protection and operation leave the Software CLA function enabled.

No. Name Setting Range Default

<1> Default setting is determined by drive software version and C6-02 setting. Drive software versions PRG: 1021 and later have a default setting of 0 when the carrier frequency is set for Leakage Current Rejection PWM (C6-02 = B), and 1 when C6-02 is set to any other value.

Setting 0: Disabled The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.

Setting 1: Enabled When the soft CLA current level is reached, the drive reduces the output voltage in order to reduce the current. If the current level drops below the Software CLA level, then normal operation will continue.

n L8-29: Current Unbalance Detection (PM OLV only)

Current unbalance can heat up a PM motor and lead to demagnetization of the magnets from heat. The current imbalance detection function prevents such motor damage by monitoring output currents and triggering a LF2 fault in case of current unbalance.

Setting 0: Disabled The drive does not protect the motor.

Setting 1: Enabled When an output current imbalance is detected, a LF2 fault is triggered, the output is switched off, and the motor coasts to stop.

n L8-35: Installation Method Selection

Selects the type of installation and changes the drive overload (oL2) limits accordingly.

Note: 1. This parameter is not reset when the drive is initialized. 2. The value is preset to the appropriate value when the drive is shipped. Change the value only when using Side-by-Side installation or when mounting a standard drive with the heatsink outside the cabinet.

Setting 0: IP20/IP00 Drive Must be selected if an IP20/IP00 drive is installed with a minimum of 30 mm space to the next drive or a cabinet wall.

Setting 1: Side-by-Side Mounting Must be selected if drives are Side-by-Side mounted with a minimum space of 2 mm.

Setting 2: NEMA Type 1 Drive Must be selected if the drive has a NEMA Type 1 enclosure or an IP20/Open-Chassis drive fitted with the NEMA Type 1 Kit option.

Setting 3: Finless Drive or External Heatsink Installation Must be selected for finless drives or if a standard drive is mounted with the heatsink outside the cabinet.

n L8-38: Carrier Frequency Reduction Selection

The drive can reduce the carrier frequency when the output current exceeds a certain level. This temporarily increases the overload capability (oL2 detection) and the drive can run through transient load peaks without tripping. L8-38 selects the operation of the carrier frequency reduction function.

Note: This function cannot be used in Open Loop Vector for PM motors.

5.8 L: Protection Functions

L8-18 — Software Current Limit Selection — PDF page 238

Source row No. Name Setting Range Default
1 L8-18 Software Current Limit Selection 0 or 1 <1>

L8-29 — Current Unbalance Detection (LF2) — PDF page 238

Source row No. Name Setting Range Default
1 L8-29 Current Unbalance Detection (LF2) 0 or 1 1

L8-35 — Installation Method Selection — PDF page 238

Source row No. Name Setting Range Default
1 L8-35 Installation Method Selection 0 to 3 Determined by o2-04

Manual — Carrier reduction and step-out detection — page 239

Source reference: SIEP C71060618F, December 2016, physical PDF page 239. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

Setting 0: Disabled No carrier frequency reduction at high current.

Setting 1: Enabled for Output Frequencies below 6 Hz The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive returns to its normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.

Setting 2: Enabled for Entire Frequency Range The carrier frequency is reduced at the following speeds: • Below 6 Hz when the current exceeds 100% of the drive rated current. • Above 7 Hz when the current exceeds 112% of the drive rated current. The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to the set value.

n L8-40: Carrier Frequency Reduction Off Delay Time

Sets the delay time which is used to switch back to the normal carrier frequency. The carrier frequency reduction function is disabled if this value is 0 s.

n L8-41: High Current Alarm Selection

The drive can be set to trigger a high current alarm (HCA) when the output current rises too high.

Setting 0: Disabled No alarm is output.

Setting 1: Enabled An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output indicating an alarm (H2-01/02/03 = 10) can be programmed.

n L8-51: STo Fault Detection Level

Note: Parameter available in drive software versions PRG: 1018 and later. Sets the STo detection level as a percentage of the motor rated current. Increase this value for faster detection of pull-out during acceleration. The drive calculates this value automatically when L8-51 is set to 0.0%. There is normally no need to change this parameter from the default value.

n L8-54: STo Deviation Detection

Note: Parameter available in drive software versions PRG: 1018 and later. Enables or disables the STo Deviation fault detection. There is normally no need to change this parameter from the default value.

Setting 0: Disabled Setting 1: Enabled

5.8 L: Protection Functions

Parameter Details

L8-38 — Carrier Frequency Reduction Selection — PDF page 239

Source row No. Name Setting Range Default
1 L8-38 Carrier Frequency Reduction Selection 0 to 2 Determined by o2-04

L8-40 — Low Carrier Frequency Off Delay Time — PDF page 239

Source row No. Name Setting Range Default
1 L8-40 Low Carrier Frequency Off Delay Time 0.00 or 2.00 s 0.50 s

L8-41 — High Current Alarm Selection — PDF page 239

Source row No. Name Setting Range Default
1 L8-41 High Current Alarm Selection 0 or 1 0

L8-51 — STo Fault Detection Level — PDF page 239

Source row No. Name Setting Range Default
1 L8-51 STo Fault Detection Level 0.0 to 150. % 0.0%

L8-54 — STo Deviation Detection — PDF page 239

Source row No. Name Setting Range Default
1 L8-54 STo Deviation Detection 0 or 1 1

Manual — Hunting prevention and AFR introduction — page 240

Source reference: SIEP C71060618F, December 2016, physical PDF page 240. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

5.9 n: Special Adjustments

The n parameters handle a variety of specialized adjustments and functions, including Hunting Prevention, AFR Control, High Slip Braking, resistance between motor lines, and PM motor control functions.

u n1: Hunting Prevention

Hunting Prevention keeps the drive from hunting as a result of low inertia and operating with light load. It is available in V/f Control only.

n n1-01: Hunting Prevention Selection

Enables or disables the Hunting Prevention function.

Note: This function is available only when using V/f Control. Hunting Prevention should be disabled when drive response is need over suppressing motor oscillation. This function can also be disabled without any problems in applications with high inertia loads or relatively heavy loads.

No. Name Setting Range Default

Setting 0: Disabled

Setting 1: Enabled

n n1-02: Hunting Prevention Gain Setting

Sets the gain for the Hunting Prevention Function.

Normally, n1-02 does not need to be changed, but adjustment may help under the following conditions: • If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases. • If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.

n n1-03: Hunting Prevention Time Constant

Determines how responsive the Hunting Prevention function is (affects the primary delay time for Hunting Prevention).

n n1-05: Hunting Prevention Gain while in Reverse

This parameter is the same as n1-02, except that it is used when the motor rotates in reverse. See the setting instructions for n1-02.

Note: When set to 0 ms, n1-02 is enabled even when the drive is operating in reverse.

u n2: Automatic Frequency Regulator (AFR) Tuning

These parameters are used to achieve speed stability when a load is suddenly applied or removed by calculating changes in the torque current feedback and then compensating the output frequency.

Note: Before making changes to the AFR parameters, make sure the motor parameters are set properly or perform Auto-Tuning.

n n2-01: Speed Feedback Detection Control (AFR) Gain

Sets the internal speed feedback detection control gain in the AFR.

<1> Default setting is determined by drive model.

n1-01 — Hunting Prevention Selection — PDF page 240

Source row No. Name Setting Range Default
1 n1-01 Hunting Prevention Selection 0 or 1 1

n1-02 — Hunting Prevention Gain Setting — PDF page 240

Source row No. Name Setting Range Default
1 n1-02 Hunting Prevention Gain Setting 0.00 to 2.50 1.00

n1-03 — Hunting Prevention Time Constant — PDF page 240

Source row No. Name Setting Range Default
1 n1-03 Hunting Prevention Time Constant 0 to 500 ms Determined by o2-04

n1-05 — Hunting Prevention Gain while in Reverse — PDF page 240

Source row No. Name Setting Range Default
1 n1-05 Hunting Prevention Gain while in Reverse 0.00 to 2.50 0.00

n2-01 — Speed Feedback Detection Control (AFR) Gain — PDF page 240

Source row No. Name Setting Range Default
1 n2-01 Speed Feedback Detection Control (AFR) Gain 0.00 to 10.00 <1>

Manual — AFR constants and braking restrictions — page 241

Source reference: SIEP C71060618F, December 2016, physical PDF page 241. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00. Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50.

Normally there is no need to adjust n2-01 from the default setting. Make adjustments in the following cases: • If hunting occurs, increase the set value in steps of 0.05 while checking the response. • If response is low, decrease the set value in steps of 0.05 while checking the response.

n n2-02/n2-03: AFR Time Constant 1/2

Parameter n2-02 sets the time constant normally used by AFR. Parameter n2-03 sets the time constant during Speed Search or when during regenerative operation the actual motor slip exceeds 50% of the rated slip.

No. Name Setting Range Default

Note: Parameter n2-02 cannot be set higher than n2-03 or an oPE08 error will result. These parameters rarely need to be changed. Adjust settings only under the following conditions. • If hunting occurs, increase n2-02. If response is low, decrease it. • Increase the setting of n2-03 if overvoltage (ov) failures occur with high inertia loads at the end of acceleration or when the load changes radically. • When increasing n2-02, make sure to increase C4-02 (Torque Compensation Delay Time Constant 1) proportionally. • When increasing n2-03, make sure to increase C4-06 (Torque Compensation Delay Time Constant 2) proportionally.

u n3: High Slip Braking (HSB)/Overexcitation Deceleration

High Slip Braking (V/f Control) HSB works in V/f Control only and is used to decrease the stopping time compared to normal deceleration without using braking resistor options. HSB stops the motor by reducing the output frequency in large steps, thus producing a high slip. Regenerative energy created from decelerating the load is dissipated in the motor windings through increased motor slip. Because of the increased temperature of the motor windings, HSB should not be used for frequently stopping the motor. The duty cycle should be around 5% or less. Notes on using High Slip Braking: • The deceleration time that has been set is ignored during HSB. • Braking time varies based on the load inertia and motor characteristics. • HSB must be triggered by a digital input set to H1-□□ = 68. Once the HSB command is given, it is not possible to restart the drive until the motor is stopped and the Run command is cycled. Use parameters n3-01 through n3-04 for adjusting HSB. Overexcitation Deceleration (V/f Control and Open Loop Vector) Overexcitation deceleration increases the flux during deceleration and allows shorter deceleration time settings than with normal deceleration without the use of a braking resistor. Enabled by setting L3-04 = 4. Notes on Overexcitation Deceleration • As regenerative energy is mainly dissipated as heat in the motor, the motor temperature will rise if overexcitation deceleration is applied frequently. In such cases, make sure the motor temperature does not exceed the maximum allowable value or consider using a braking resistor option instead. • The drive decelerates at the active deceleration time. Make sure to set this time so that no overvoltage (ov) fault occurs. • When a Run command is entered during overexcitation deceleration, overexcitation operation is cancelled and the drive will reaccelerate to the specified speed. • Do not use overexcitation deceleration in combination with a braking resistor option. • Overexcitation deceleration cannot be used in OLV/PM control mode. Use parameters n3-13 through n3-23 for adjusting overexcitation deceleration.

n n3-01: High Slip Braking Deceleration Frequency Width

Sets the step width for frequency reduction during HSB. Increase this value if DC bus overvoltage (ov) occurs during HSB.

5.9 n: Special Adjustments

Parameter Details

n2-02 / n2-03 — AFR Time Constant 1 — PDF page 241

Source row No. Name Setting Range Default
1 n2-02 AFR Time Constant 1 0 to 2000 ms 50 ms
2 n2-03 AFR Time Constant 2 0 to 2000 ms 750 ms

Manual — High-slip and overexcitation settings — page 242

Source reference: SIEP C71060618F, December 2016, physical PDF page 242. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

n n3-02: High Slip Braking Current Limit

Sets the maximum current to be output during an HSB stop as a percentage of motor rated current (E2-01). Reducing the current limit increases the deceleration time. Make sure that this value does not exceed 150% of the drive’s current rating.

n n3-03: High Slip Braking Dwell Time at Stop

When the motor reaches a relatively low speed at the end of HSB, the output frequency is kept at the minimum output frequency E1-09 for the time set in n3-03. Increase this time if the inertia is very high and the motor is still coasting after HSB is complete.

n n3-04: High Slip Braking Overload Time

Sets the time required for an HSB overload fault (oL7) to occur when the drive output frequency does not change for some reason during an HSB stop.

n n3-13: Overexcitation Deceleration Gain

Applies a gain to the V/f pattern output value during overexcitation deceleration, thereby determining the level of overexcitation. The drive returns to the normal V/f value after the motor has stopped or when it is accelerating to the frequency reference.

The optimum setting for n3-13 depends on the motor flux saturation characteristics. • Increase the gain by 1.25 to 1.30 to improve the breaking power of overexcitation. • Reduce the value when the motor slip gets too high, which can trigger overcurrent (oC), motor overload (oL1), or drive overload (oL2) faults. Alternatively reduce n3-21.

n n3-21: High Slip Suppression Current Level

If overcurrent, oL1, or oL2 occur during overexcitation deceleration, reduce the overslip suppression current level. Set as a percentage of the drive rated current. Reduce this setting if the current during overexcitation deceleration exceeds the overslip suppression current set in n3-21 as a result of flux saturation and excessive slip. Alternatively reduce the overexcitation gain n3-13.

n n3-23: Overexcitation Operation Selection

Determines which direction overexcitation can be used in. However, parameter L3-04 must be set to 4 in order for n3-23 to be enabled.

Setting 0: Enabled in Both Directions

Setting 1: Enabled in Forward Direction Only

Setting 2: Enabled in Reverse Direction Only

5.9 n: Special Adjustments

n3-01 — High Slip Braking Deceleration Frequency Width — PDF page 242

Source row No. Name Setting Range Default
1 n3-01 High Slip Braking Deceleration Frequency Width 1 to 20% 5%

n3-02 — High Slip Braking Current Limit — PDF page 242

Source row No. Name Setting Range Default
1 n3-02 High Slip Braking Current Limit 100 to 200% 150%

n3-03 — High Slip Braking Dwell Time at Stop — PDF page 242

Source row No. Name Setting Range Default
1 n3-03 High Slip Braking Dwell Time at Stop 0.0 to 10.0 s 1.0 s

n3-04 — High Slip Braking Overload Time — PDF page 242

Source row No. Name Setting Range Default
1 n3-04 High Slip Braking Overload Time 30 to 1200 s 40 s

n3-13 — Overexcitation Deceleration Gain — PDF page 242

Source row No. Name Setting Range Default
1 n3-13 Overexcitation Deceleration Gain 1.00 to 1.40 1.10

n3-21 — Overslip Suppression Current Level — PDF page 242

Source row No. Name Setting Range Default
1 n3-21 Overslip Suppression Current Level 0 to 150% 100%

n3-23 — Overexcitation Operation Selection — PDF page 242

Source row No. Name Setting Range Default
1 n3-23 Overexcitation Operation Selection 0 to 2 0

Manual — Online resistance and PM current settings — page 243

Source reference: SIEP C71060618F, December 2016, physical PDF page 243. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u n6: Motor Line-to-Line Resistance Online Tuning

The drive can tune the motor line-to-line resistance during run in order to prevent torque loss due to a rise in motor temperature increase, especially at low speeds.

n n6-01: Motor Line-to-Line Resistance Online Tuning Selection

No. Name Setting Range Default

Setting 0: Disabled

Setting 1: Enabled

u n8: PM Motor Control

These parameters are available when using the special Open Loop Vector Control for permanent magnet motors and can be used to adjust the control performance.

n n8-45: Speed Feedback Detection Control Gain (for PM OLV)

Sets the gain for internal speed feedback detection control. Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions: • Increase this setting if motor oscillation or hunting occurs. • Decrease this setting in increments of 0.05 to decrease the drive responsiveness.

n n8-47: Pull-In Current Compensation Time Constant (for PM OLV)

Sets the time constant for making the actual current and the pull-in current agree. Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions: • Increase this setting when it takes too long for the reference value for the pull-in current to match the target value. • Decrease this setting if motor oscillation occurs.

n n8-48: Pull-In Current (for PM OLV)

Tells the drive the amount of d-axis current to be provided to the motor during no-load operation at a constant speed. Set as a percentage of the motor rated current. • Increase this setting when hunting occurs or the motor speed is unstable while running at a constant speed. • If there is too much current when driving a light load at a constant speed, then reduce this level slightly.

<1> Setting range varies depending on drive software version. Software versions PRG: 1018 and later disable pull-in current when n8-48 = 0, and allow the pull-in current to be changed during Run. PRG: 1018 and later: 0% or 20 to 200% PRG: 1017 and earlier: 20 to 200%

n n8-49: d Axis Current for High Efficiency Control (for PM OLV)

Sets the amount of d axis current when using Energy Saving control as a percentage of the motor rated current. Although this setting seldom needs to be changed, please note the following: • If motor operation is unstable when driving heavy loads, try increasing this setting (towards 0). • If motor parameters (E5) have been changed, this value will be reset to 0 and has to be readjusted.

5.9 n: Special Adjustments

Parameter Details

n6-01 — Motor Line-to-Line Resistance Online Tuning — PDF page 243

Source row No. Name Setting Range Default
1 n6-01 Motor Line-to-Line Resistance Online Tuning 0 or 1 1

n8-45 — Speed Feedback Detection Control Gain — PDF page 243

Source row No. Name Setting Range Default
1 n8-45 Speed Feedback Detection Control Gain 0.00 to 10.00 0.80

n8-47 — Pull-In Current Compensation Time Constant — PDF page 243

Source row No. Name Setting Range Default
1 n8-47 Pull-In Current Compensation Time Constant 0.0 to 100.0 s 5.0 s

n8-48 — Pull-In Current — PDF page 243

Source row No. Name Setting Range Default
1 n8-48 Pull-In Current <1> Determined by E5-01

Manual — PM current, inertia and voltage limit — page 244

Source reference: SIEP C71060618F, December 2016, physical PDF page 244. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

<1> Setting range varies depending on drive software version. Software versions PRG: 1018 and later allow this parameter to be changed during Run. PRG: 1018 and later: -200.0 to 200.0% PRG: 1017 and earlier: -200.0 to 0.0%

n n8-51: Acceleration/Deceleration Time Pull-In Current (for PM OLV)

Sets the d-axis current during acceleration and deceleration as a percentage of the motor rated current (E5-03). Adjustments to this setting may help in the following situations: • Increase this setting when a large amount of starting torque is required. • Lower this setting if there is excessive current during acceleration and deceleration.

n n8-54: Voltage Error Compensation Time Constant (for PM OLV)

Sets the time constant for voltage error compensation. Make changes to this parameter under the following conditions: • Adjust the value when hunting occurs at low speed. • Increase the value in steps of 0.1 when hunting occurs with sudden load changes. Try to disable the compensation by setting n8-51 = 0 if increasing does not help. • Increase the value when oscillations occur at start.

n n8-55: Load Inertia (for PM OLV)

Sets the ratio between motor inertia and the inertia of the connected machinery. If this value is set too low, the motor may not start very smoothly, and a STo fault (Motor Step-Out) might occur.

Setting 0: Below 1:10 The inertia ratio between the motor and the load is just less than 1:10.

Setting 1: Between 1:10 and 1:30 The inertia ratio between the motor and the load is between 1:10 and 1:30. Set n8-55 to 1 if a STo fault occurs as a result of impact load or sudden acceleration/deceleration when n8-55 = 0.

Setting 2: Between 1:30 and 1:50 The inertia ratio between the motor and the load is between 1:30 and 1:50. Set n8-55 to 2 if a STo fault occurs as a result of impact load or sudden acceleration/deceleration when n8-55 = 1.

Setting 3: Beyond 1:50 The inertia ratio between the motor and the load is higher than 1:50. Set n8-55 to 3 if a STo fault occurs as a result of impact load or sudden acceleration/deceleration when n8-55 = 2.

n n8-62: Output Voltage Limit (for PM OLV)

Sets the output voltage limit to prevent output voltage saturation. This value should not be set higher than the actual input voltage.

<1> Values shown here are for 200 V class drives. Double values when using a 400 V class drive.

5.9 n: Special Adjustments

n8-49 — d Axis Current for High Efficiency Control — PDF page 244

Source row No. Name Setting Range Default
1 n8-49 d Axis Current for High Efficiency Control <1> Determined by E5-01

n8-51 — Acceleration/Deceleration Time Pull-In Current — PDF page 244

Source row No. Name Setting Range Default
1 n8-51 Acceleration/Deceleration Time Pull-In Current 0 to 200% Determined by E5-01

n8-54 — Voltage Error Compensation Time Constant — PDF page 244

Source row No. Name Setting Range Default
1 n8-54 Voltage Error Compensation Time Constant 0.00 to 10.00 1.00

n8-55 — Motor/Load Inertia Ratio — PDF page 244

Source row No. Name Setting Range Default
1 n8-55 Motor/Load Inertia Ratio 0 to 3 0

n8-62 — Output Voltage Limit — PDF page 244

Source row No. Name Setting Range Default
1 n8-62 Output Voltage Limit 0.0 to 230.0 Vac <1> 230 Vac <1>

Manual — PM output voltage and suppression gains — page 245

Source reference: SIEP C71060618F, December 2016, physical PDF page 245. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n n8-63/n8-68: Output Voltage Limit Gain 1/2

n8-63 sets the gain for the output voltage limit in 0.01 units. n8-68 sets the voltage detection level adjustment gain. There is normally no need to change these parameters from their default values.

No. Name Setting Range Default

n n8-65: Speed Feedback Detection Control Gain during ov Suppression (for PM OLV)

Sets the gain for internal speed feedback detection control when overvoltage suppression is active. Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions: • Increase this setting if motor oscillation or hunting occurs when ov suppression is active. • Decrease this setting in increments of 0.05 to decrease the drive responsiveness during ov suppression.

n n8-87: Output Voltage Limit Selection

Note: Parameter available in drive software versions PRG: 1018 and later. Determines the method of the output voltage limit. Use the feed-forward method if oscillation occurs in the constant output range. There is normally no need to change this parameter from its default value.

Setting 0: Feedback Method Setting 1: Feed-Forward Method

n n8-88: Output Voltage Limit Switching Current Level

Note: Parameter available in drive software versions PRG: 1018 and later. Sets the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03). There is normally no need to change this parameter from its default value.

n n8-89: Output Voltage Limit Switching Current Hysteresis Width

Note: Parameter available in drive software versions PRG: 1018 and later. Determines the hysteresis of the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03).

n n8-90: Output Voltage Limit Switching Speed

Note: Parameter available in drive software versions PRG: 1018 and later. Sets the speed level to switch the output voltage limit sequence. Set as a percentage of the maximum output frequency (E1-04).

5.9 n: Special Adjustments

Parameter Details

during Overvoltage Suppression

n8-63 / n8-68 — Output Voltage Limit Gain 1 — PDF page 245

Source row No. Name Setting Range Default
1 n8-63 Output Voltage Limit Gain 1 0.00 to 100.00 1.00
2 n8-68 Output Voltage Limit Gain 2 0.50 to 1.50 0.95

n8-65 — Speed Feedback Detection Control Gain — PDF page 245

Source row No. Name Setting Range Default
1 n8-65 Speed Feedback Detection Control Gain during Overvoltage Suppression 0.00 to 10.00 1.50

n8-87 — Output Voltage Limit Selection — PDF page 245

Source row No. Name Setting Range Default
1 n8-87 Output Voltage Limit Selection 0 or 1 0

n8-88 — Output Voltage Limit Switching Current Level — PDF page 245

Source row No. Name Setting Range Default
1 n8-88 Output Voltage Limit Switching Current Level 0 to 400% 400%

n8-89 — Output Voltage Limit Switching Current Hysteresis Width — PDF page 245

Source row No. Name Setting Range Default
1 n8-89 Output Voltage Limit Switching Current Hysteresis Width 0 to [n8-88] 3%

n8-90 — Output Voltage Limit Switching Speed — PDF page 245

Source row No. Name Setting Range Default
1 n8-90 Output Voltage Limit Switching Speed 0 to 200% 200%

Manual — PM constant-speed current limit — page 246

Source reference: SIEP C71060618F, December 2016, physical PDF page 246. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n n8-91: Id Limit for Output Voltage Limit Control

Note: Parameter available in drive software versions PRG: 1018 and later. Sets the amount of pull-in current that flows through the motor while operating at constant speed. Set as a percentage of the motor rated current (E5-03). Increase this setting if hunting occurs at constant speed.

No. Name Setting Range Default

5.9 n: Special Adjustments

n8-91 — Id Limit for Output Voltage Limit Control — PDF page 246

Source row No. Name Setting Range Default
1 n8-91 Id Limit for Output Voltage Limit Control -200 to 0% -50%

Manual — Operator monitor and display selections — page 247

Source reference: SIEP C71060618F, December 2016, physical PDF page 247. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

5.10 o: Operator Related Settings

These parameters concern the various functions and features of the digital operator.

u o1: Display Settings and Selections

These parameters determine how data is shown on the operator display.

n o1-01: Drive Mode Unit Monitor Selection

When using an LED operator, pressing the up arrow key on the drive will display the following data: frequency reference → rotational direction → output frequency → output current → o1-01 selection. Parameter o1-01 selects the content of the last monitor in this sequence. There is no effect like this on an LCD operator.

No. Name Setting Range Default

<1> U2-□□ and U3-□□ parameters cannot be selected.

To select a monitor parameter, set the three numeric digits that make up that monitor. This is done by entering the □-□□ part of U□-□□. For a list of monitors, Refer to U: Monitor Parameters on page 254.

n o1-02: User Monitor Selection after Power Up

Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the drive is first turned on.

Setting 1: Frequency Reference (U1-01)

Setting 2: Forward/Reverse

Setting 3: Output Frequency (U1-02)

Setting 4: Output Current (U1-03)

Setting 5: User Selected Monitor (set by o1-01) Setting 5 displays the monitor selected from the U parameter by o1-01.

n o1-03: Digital Operator Display Selection

Sets the units used to display the frequency reference and output frequency. Set this parameter to 3 for user-set units before setting parameters o1-10 and o1-11.

Setting 0: 0.01 Hz Units Setting 1: 0.01% Units 100% = max output frequency.

Setting 2: r/min Units Calculated by the max output frequency and the number of motor poles.

Note: Setting 2 requires entering the number of motor poles to E2-04, E4-04, and E5-04.

Setting 3: User-Set Units (use o1-01 and 01-11) Set the value used for the maximum frequency reference to o1-10, then set the placement of the decimal point in this number to o1-11. For example, to display the maximum output frequency as “100.00”, set o1-10 to 10000 and o1-11 to 2 (i.e., 10000 with two numbers to the right of the decimal point).

Note: Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:

Parameter Details

o1-01 — Drive Mode Unit Monitor Selection — PDF page 247

Source row No. Name Setting Range Default
1 o1-01 Drive Mode Unit Monitor Selection 104 to 810 <1> (U1-04 to U8-10) 106 (U1-06)

o1-02 — User Monitor Selection after Power Up — PDF page 247

Source row No. Name Setting Range Default
1 o1-02 User Monitor Selection after Power Up 1 to 5 1

o1-03 — Digital Operator Display Selection — PDF page 247

Source row No. Name Setting Range Default
1 o1-03 Digital Operator Display Selection 0 to 3 0

Manual — Display units and operator key selections — page 248

Source reference: SIEP C71060618F, December 2016, physical PDF page 248. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

U1-01: Frequency Reference U1-02: Output Frequency U1-05: Motor Speed U1-16: Output Frequency after Soft-Starter (Accel/Decel Ramp Generator) d1-01 to d1-17: Frequency References

n o1-05: LCD Contrast Control

Note: Parameter available in drive software versions PRG: 1022 and later. Sets the brightness of the optional LCD operator. The lower the setting, the brighter the LCD contrast. The higher the setting, the darker the LCD contrast.

No. Name Setting Range Default

n o1-10: User-Set Display Units Maximum Value

Determines the display value that is equal to the maximum output frequency. The decimal number is defined by parameter o1-11.

Note: This setting changes automatically when o1-03 is changed. o1-10 can only be adjusted when o1-03 is set to 3.

n o1-11: User-Set Display Units Decimal Display

Determines the number of digits for user-set display if o1-03 is set to 3. The setting value is equal to the number of decimal places. The maximum display value is defined by o1-10.

Note: This setting changes automatically when o1-03 is changed. o1-11 can only be adjusted when o1-03 is set to 3.

u o2: Operator Key Selections

These parameters determine the functions assigned to the operator keys.

n o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection

Parameter o2-01 determines whether the LO/RE key on the digital operator will be enabled or not for switching between LOCAL and REMOTE.

Setting 0: Disabled The LO/RE key is disabled.

Setting 1: Enabled The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is selected, the LED indicator on the LO/RE key will light up.

WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode.

n o2-02: STOP Key Function Selection

Selects if the STOP key on the digital operator can be used to stop the operation when the drive is controlled from a remote source (i.e., not from digital operator).

5.10 o: Operator Related Settings

o1-05 — LCD Contrast Control — PDF page 248

Source row No. Name Setting Range Default
1 o1-05 LCD Contrast Control 0 to 5 3

o1-10 — User-Set Display Units Maximum Value — PDF page 248

Source row No. Name Setting Range Default
1 o1-10 User-Set Display Units Maximum Value 1 to 60000 Determined by o1-03

o1-11 — User-Set Display Units Decimal Display — PDF page 248

Source row No. Name Setting Range Default
1 o1-11 User-Set Display Units Decimal Display 0 to 3 Determined by o1-03

o2-01 — LO/RE Key Function Selection — PDF page 248

Source row No. Name Setting Range Default
1 o2-01 LO/RE Key Function Selection 0 or 1 1

o2-02 — STOP Key Function Selection — PDF page 248

Source row No. Name Setting Range Default
1 o2-02 STOP Key Function Selection 0 or 1 1

Manual — User defaults and reference input methods — page 249

Source reference: SIEP C71060618F, December 2016, physical PDF page 249. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 0: Disabled The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only be stopped from the Run command source that has been selected.

Setting 1: Enabled The STOP key can be used to terminate the operation, even if the Run command source is not assigned to the digital operator. If operation has been interrupted by pressing the STOP key, the Run command must be cycled to restart the drive.

n o2-03: User Parameter Default Value

Once drive parameters are set up completely, the values set can be saved as “User Initialization Values” by setting parameter o2-03. Once this has been done, the “Initialize Parameters” parameter (A1-03) will offer the choice of “1110: User Initialize”. Choosing A1-03 = “1110: User Initialize”, will reset all parameters to the values saved as “User Initialization Values”. Refer to A1-03: Initialize Parameters on page 117 for details on drive initialization.

No. Name Setting Range Default

Setting 0: No Change All “User Initialization Values” are saved as they are.

Setting 1: Set User Initialization Values The current parameter settings are saved as “User Initialization Values”. After setting o2-03 to 1 and pressing the ENTER key, the values are saved and the display returns to 0.

Setting 2: Clear User Initialization Values All “User Initialization Values” are cleared. After setting o2-03 to 2 and pressing the ENTER key, the values are erased and the display returns to 0. A1-03 = 1110 becomes invalid.

n o2-04: Drive Model Selection

Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal performance and proper protection for the drive hardware. This parameter is configured at the factory and does not normally require adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.

Note: 1. Refer to Defaults by Drive Model and Duty Rating (ND/HD) on page 409 for a list of o2-04 settings and parameters that change depending on the drive model selection. 2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly. 3. This parameter is not reset to the default value when the drive is initialized using A1-03.

n o2-05: Frequency Reference Setting Method Selection

Determines if the ENTER key must be used to input a frequency reference from the digital operator.

Setting 0: ENTER Key Required Every change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key before it becomes effective.

Setting 1: ENTER Key Not Required The output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator. The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key has been released. If an undervoltage error (Uv) occurs within 5 seconds of pressing the ENTER key, the frequency reference will not be saved to memory. The digital operator display flashes when settings can be made to the frequency reference.

5.10 o: Operator Related Settings

Parameter Details

o2-03 — User Parameter Default Value — PDF page 249

Source row No. Name Setting Range Default
1 o2-03 User Parameter Default Value 0 to 2 0

o2-04 — Drive Model Selection — PDF page 249

Source row No. Name Setting Range Default
1 o2-04 Drive Model Selection - Depending on drive size

o2-05 — Frequency Reference Setting Method Selection — PDF page 249

Source row No. Name Setting Range Default
1 o2-05 Frequency Reference Setting Method Selection 0 or 1 0

Manual — Operator loss and copy functions — page 250

Source reference: SIEP C71060618F, December 2016, physical PDF page 250. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

LED graphic shows F00.00 with three flash marks above. This is the illustrated display only, not an actual drive setting. Exact geometry, routing and unprinted numerical values remain original-only.

Figure 5.91 Ready to Set Frequency Reference

n o2-06: Operation Selection when Digital LCD Operator is Disconnected

Determines if the drive will stop when an external LCD operator is removed in LOCAL mode or with b1-02 set to 0.

Note: An LCD operator is available as an option. This setting is not applicable to the standard LED operator that comes with the drive.

No. Name Setting Range Default

Setting 0: Continue Operation The operation is continued.

Setting 1: Trigger a Fault The operation is stopped and an oPr fault is triggered. The motor coasts to stop.

n o2-07: Motor Direction at Power Up when Using Operator

Determines the direction the motor will rotate after the drive is powered up when the Run command is set to be given from the digital operator.

Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02/16 = 0).

Setting 0: Forward

Setting 1: Reverse

u o3: Copy Function

Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive.

n o3-01: Copy Function Selection

This parameter controls the copying of parameters to and from the LED operator (option). The copy function will change certain parameter default settings depending on the regional specification of the drive.

0: COPY SELECT (no function)

1: INV --> OP READ All parameters are copied from the drive to the digital operator.

Note: Set o3-02 to 1 to unlock copy protection.

2: OP --> INV WRITE All parameters are copied from the digital operator to the drive.

3: OP<-->INV VERIFY Parameter settings in the drive are compared to those in the digital operator.

Note: When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur.

n o3-02 Copy Allowed Selection

Enables and disables the digital operator copy functions.

5.10 o: Operator Related Settings

o2-06 — Digital Operator Disconnection Operation — PDF page 250

Source row No. Name Setting Range Default
1 o2-06 Digital Operator Disconnection Operation 0 or 1 0

o2-07 — Motor Direction at Power Up when Using Operator — PDF page 250

Source row No. Name Setting Range Default
1 o2-07 Motor Direction at Power Up when Using Operator 0 or 1 0

o3-01 — Copy Function Selection — PDF page 250

Source row No. Name Setting Range Default
1 o3-01 Copy Function Selection 0 to 3 0

Manual — Copy permission and maintenance counters — page 251

Source reference: SIEP C71060618F, December 2016, physical PDF page 251. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

0: Disabled No digital operator copy functions are allowed

1: Enabled Copying allowed

u o4: Maintenance Monitor Settings

n o4-01: Accumulated Operation Time Setting

Parameter o4-01 sets the cumulative operation time and allows the user to set the starting value of the accumulated operation time displayed in monitor U4-01.

Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also be displayed in monitor U4-01.

n o4-02: Accumulated Operation Time Selection

Selects the conditions for what is to be considered “accumulated operation time.” Accumulated operation time is displayed in U4-01.

Setting 0: Power On Time The drive logs the time it is connected to a power supply, no matter if the motor is running or not.

Setting 1: Run Time The drive logs the time that the output is active, i.e., whenever a Run command is active (even if the motor is not rotating) or a voltage is output.

n o4-03: Cooling Fan Operation Time/Maintenance Setting

Sets the value of the cooling fan operation time counter displayed in monitor U4-03. Parameter o4-03 also sets the base value used for the cooling fan maintenance value displayed in U4-04. Be sure to reset this parameter back to 0 if the cooling fan is replaced.

Note: 1. The value in o4-03 is set in 10 h units. For example, a setting of 30 will set the cooling fan operation time counter to 300 h. “300” will be displayed in monitor U4-03. 2. The actual maintenance time depends on the environment the drive is used in.

n o4-05: Capacitor Maintenance Setting

Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected performance life. This value should be reset to 0 when the DC bus capacitors have been replaced.

Note: The actual maintenance time will depend on the environment the drive is used in.

n o4-07: DC Bus Pre-charge Relay Maintenance Setting

Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected performance life. This value should be reset to 0 when the relay has been replaced.

Note: The maintenance actual time depends on the environment the drive is used in.

5.10 o: Operator Related Settings

Parameter Details

Operator and maintenance setting | o3-02

Operator and maintenance setting | o4-01

Operator and maintenance setting | o4-02

Operator and maintenance setting | o4-03

Operator and maintenance setting | o4-05

Operator and maintenance setting — PDF page 251

Source row No. Name Setting Range Default
1 o3-02 Copy Allowed Selection 0, 1 0

Operator and maintenance setting — PDF page 251

Source row No. Name Setting Range Default
1 o4-01 Accumulated Operation Time Setting 0 to 9999 0

Operator and maintenance setting — PDF page 251

Source row No. Name Setting Range Default
1 o4-02 Accumulated Operation Time Selection 0 or 1 0

Operator and maintenance setting — PDF page 251

Source row No. Name Setting Range Default
1 o4-03 Cooling Fan Operation Time 0 to 9999 0

Operator and maintenance setting — PDF page 251

Source row No. Name Setting Range Default
1 o4-05 Capacitor Maintenance Setting 0 to 150% 0%

Manual — Counter reset and user parameters — page 252

Source reference: SIEP C71060618F, December 2016, physical PDF page 252. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Setting Range Default

n o4-09: IGBT Maintenance Setting

Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. This value should be reset to 0 when the IGBTs have been replaced.

Note: The actual maintenance time depends on the environment the drive is used in.

n o4-11: U2, U3 Initialization

When the drive is initialized, the fault trace and fault history monitors (U2-□□ and U3-□□) are not reset. Parameter o4-11 can be used to initialize them.

Setting 0: No Action The drive keeps a record of the fault trace and fault history.

Setting 1: Reset Fault Data Resets the data for the U2-□□ and U3-□□ monitors. Once o4-11 is set to 1 and the ENTER key is pressed, the fault data are erased and the display returns to 0.

n o4-12: kWh Monitor Initialization

The kWh monitors U4-10 and U4-11 are not initialized when the power is cycled or the drive is initialized. o4-12 can be used to manually reset them.

Setting 0: No Action The kWh data are kept as they are.

Setting 1: Reset kWh Data Resets the kWh counter. The monitors U4-10 and U4-11 will show 0. Once o4-12 is set to 1 and the ENTER key is pressed, the kWh data are erased and the display returns to 0.

n o4-13: Number of Run Commands Counter Initialization

The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Using o4-13 it can be manually reset to 0.

Setting 0: No Action The Run command data are kept as they are.

Setting 1: Reset Run Commands Counter Resets the Run commands counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed, the counter value is erased and the display returns to 0.

u q: DriveWorksEZ Parameters

n q1-01 to q6-07: Reserved for Use by DriveWorksEZ

These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.

5.10 o: Operator Related Settings

Operator and maintenance setting | o4-07

Operator and maintenance setting | o4-09

Operator and maintenance setting | o4-11

Operator and maintenance setting | o4-12

Operator and maintenance setting | o4-13

Operator and maintenance setting — PDF page 252

Source row No. Name Setting Range Default
1 o4-07 DC Bus Pre-charge Relay Maintenance Setting 0 to 150% 0%

Operator and maintenance setting — PDF page 252

Source row No. Name Setting Range Default
1 o4-09 IGBT Maintenance Setting 0 to 150% 0%

Operator and maintenance setting — PDF page 252

Source row No. Name Setting Range Default
1 o4-11 U2, U3 Initialization 0 or 1 0

Operator and maintenance setting — PDF page 252

Source row No. Name Setting Range Default
1 o4-12 kWh Monitor Initialization 0 or 1 0

Operator and maintenance setting — PDF page 252

Source row No. Name Setting Range Default
1 o4-13 Number of Run Commands Counter Reset 0 or 1 0

Manual — DriveWorksEZ and auto-tuning references — page 253

Source reference: SIEP C71060618F, December 2016, physical PDF page 253. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u r: DriveWorksEZ Connection Parameters

n r1-01 to r1-40: DriveWorksEZ Connection Parameters

These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.

u T: Motor Tuning

Auto-Tuning automatically sets and tunes parameters required for optimal motor performance. Refer to Auto-Tuning on page 102 for details on Auto-Tuning parameters.

5.10 o: Operator Related Settings

Parameter Details

Manual — Status, fault and maintenance monitor groups — page 254

Source reference: SIEP C71060618F, December 2016, physical PDF page 254. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

5.11 U: Monitor Parameters

Monitor parameters let the user view various aspects of drive performance as it is shown on the operator display. Some monitors can be output from terminal AM by assigning the specific monitor parameter number to H4-01. Refer to H4-01: Multi-Function Analog Terminal AM Monitor Selection on page 210 for details on assigning functions to the analog output.

u U1: Operation Status Monitors

Status monitors display drive status like output frequency, current etc. Refer to U1: Operation Status Monitors on page 399 for a complete list of U1-□□ monitors and descriptions.

u U2: Fault Trace

These monitor parameters are used to view the status of various drive aspects when a fault occurs. This information is helpful for finding out why a fault occurred. Refer to U2: Fault Trace on page 400 for a complete list of U2-□□ monitors and descriptions. U2-□□ monitors are not reset when the drive is initialized. Refer to o4-11: U2, U3 Initialization on page 252 for instructions to initialize the fault trace.

u U3: Fault History

These parameters display faults that have occurred during operation as well as the drive operation time when those faults occurred. Refer to U3: Fault History on page 401 for a complete list of U3-□□ monitors and descriptions. U3-□□ monitors are not reset when the drive is initialized. Refer to o4-11: U2, U3 Initialization on page 252 for instructions to initialize the fault trace.

u U4: Maintenance Monitors

Maintenance monitors show: • Runtime data of the drive and cooling fans, and number of Run commands issued. • Maintenance data and replacement information for various drive components. • kWh data. • Highest peak current that has occurred and output frequency at the time the peak current occurred. • Motor overload status information. • Detailed information about the present Run command and frequency reference source selection. Refer to U4: Maintenance Monitors on page 402 for a complete list of U4-□□ monitors and descriptions.

u U5: PID Monitors

These monitors display various aspects of PID control. Refer to PID Block Diagram on page 138 for a description of where each monitor is located in the PID control block. Refer to U5: PID Monitors on page 403 for a complete list of U5-□□ monitors and descriptions.

u U6: Control Monitors

Control monitors show: • Reference data for the output voltage and vector control. • ASR monitors. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details and an illustration that shows where in the ASR block the monitors are located. • The offset value added to the frequency reference by the Frequency Offset function. Refer to Setting 44/45/46: Offset Frequency 1/2/3 Addition on page 192. • The bias value added to the frequency reference by the Up/Down 2 function. Refer to Setting 75/76: Up/Down 2 on page 193. Refer to U6: Control Monitors on page 404 for a complete list of U6-□□ monitors and descriptions.

Note: Fix monitors U6-80 to U6-99 for communication options. Monitor content will vary based on the communication option card connected to the drive. Refer to the option manual for more information.

Manual — DriveWorksEZ monitors — page 255

Source reference: SIEP C71060618F, December 2016, physical PDF page 255. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u U8: DriveWorksEZ Monitors

These monitors are reserved for use with DriveWorksEZ.

5.11 U: Monitor Parameters

Parameter Details

Manual — Troubleshooting safety warnings — page 258

Source reference: SIEP C71060618F, December 2016, physical PDF page 258. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

6.1 Section Safety

DANGER

Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.

WARNING

Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may illustrate drives without covers or safety shields to display details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not touch terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the drive input power is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry, or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming drive input power before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material.

Manual — ESD, wiring and braking notices — page 259

Source reference: SIEP C71060618F, December 2016, physical PDF page 259. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for modification of the product made by the user. Check all the wiring after installing the drive and connecting other devices to ensure that all connections are correct. Failure to comply could result in damage to the drive.

6.1 Section Safety

Troubleshooting

Manual — V/f tuning suggestions — page 260

Source reference: SIEP C71060618F, December 2016, physical PDF page 260. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

6.2 Motor Performance Fine Tuning

This section offers helpful information for counteracting oscillation, hunting, or other faults that occur while performing a trial run. Refer to the section below that corresponds to the motor control method used.

Note: This section describes parameters that are commonly edited. Consult Yaskawa for more information on detailed settings and fine-tuning the drive.

u V/f Motor Control Method Tuning

Table 6.1 Parameters for Tuning the Drive in V/f Motor Control Method

Problem | Parameter | Corrective Action | Default Value

Suggested Setting

<1> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default setting shown is for V/f Control.

Note: Use slip compensation to improve speed precision in V/f Control. First make sure that the proper values have been set for the motor rated current to E2-01, motor rated slip (E2-02), and motor no-load current (E2-03). Next, adjust the slip compensation gain set to C3-01 so that it is between 0.5 to 1.5.

V/f tuning | • Motor hunting and oscillation at speeds between 10 and 40 Hz

V/f tuning | • Motor noise • Motor hunting and oscillation at speeds up to 40 Hz

V/f tuning | • Poor torque or speed response • Motor hunting and oscillation

V/f tuning | • Poor motor torque at speeds below 10 Hz • Motor hunting and oscillation

V/f tuning | • Poor motor torque at low speeds • Motor instability at motor start

V/f tuning | • Poor speed precision

V/f tuning — PDF page 260

Source row Problem Parameter Corrective Action Default Value Suggested Setting
1 • Motor hunting and oscillation at speeds between 10 and 40 Hz Hunting Prevention Gain (n1-02) • If insufficient motor torque relative to the size of the load causes hunting, reduce the setting. • When motor hunting and oscillation occur with a light load, increase the setting. • Lower this setting if hunting occurs when using a motor with a relatively low inductance, such as a high-frequency motor or a motor with a larger frame size. 1.00 0.10 to 2.00
2 • Motor noise • Motor hunting and oscillation at speeds up to 40 Hz Carrier Frequency Selection (C6-02) • If the motor noise is too loud, increase the carrier frequency. • When motor hunting and oscillation occur at speeds up to 40 Hz, lower the carrier frequency. • The default setting for the carrier frequency depends on the drive capacity (o2-04) and the Drive Duty Selection (C6-01). 7 (Swing PWM 1) 1 to A
3 • Poor torque or speed response • Motor hunting and oscillation Torque Compensation Primary Delay Time (C4-02) • If motor torque and speed response are too slow, decrease the setting. • If motor hunting and oscillation occur, increase the setting. 200 ms <1> 100 to 1000 ms
4 • Poor motor torque at speeds below 10 Hz • Motor hunting and oscillation Torque Compensation Gain (C4-01) • If motor torque is insufficient at speeds below 10 Hz, increase the setting. • If motor hunting and oscillation with a relatively light load, decrease the setting. 1.00 0.50 to 1.50
5 • Poor motor torque at low speeds • Motor instability at motor start Mid Output Voltage A (E1-08) Minimum Output Voltage (E1-10) • If torque is insufficient at speeds below 10 Hz, increase the setting. • If motor instability occurs at motor start, decrease the setting. Note: The recommended setting value is for 200 V class drives. Double this value when using a 400 V class drive. E1-08: 18.4 V E1-10: 13.8 V <1> Initial value ±5 V
6 • Poor speed precision Slip Compensation Gain (C3-01) • After setting the motor-rated current (E2-01), motor-rated slip (E2-02) and motor no-load current (E2-03), adjust the slip compensation gain (C3-01). - 0.5 to 1.5

Manual — OLV tuning suggestions — page 261

Source reference: SIEP C71060618F, December 2016, physical PDF page 261. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u Open Loop Vector (OLV) Motor Control Method Tuning

Table 6.2 Parameters for Tuning the Drive in OLV Motor Control Method

Problem | Parameter No. | Corrective Action | Default Value | Suggested Setting

6.2 Motor Performance Fine Tuning

Troubleshooting

OLV tuning continuation | • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz.

OLV tuning continuation | • Overvoltage trips when accelerating, decelerating, or during sudden speed or load changes.

OLV tuning continuation | • Poor motor torque and speed response • Motor hunting and oscillation.

OLV tuning continuation | • Poor speed response and stability

OLV tuning continuation | • Poor speed precision

OLV tuning continuation | • Motor noise • Control motor hunting and oscillation occur at speeds below 10 Hz.

OLV tuning continuation — PDF page 261

Source row Problem Parameter No. Corrective Action Default Value Suggested Setting
1 • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz. AFR Gain (n2-01) • If motor torque and speed response are too slow, gradually decrease the setting by 0.05. • If motor hunting and oscillation occur, gradually increase the setting by 0.05. <1> 0.50 to 2.00
2 • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz. AFR Time Constant 1 (n2-02) • To improve motor torque speed response, gradually reduce this setting by 10 ms and check the performance. • If motor hunting and oscillation occur as a result of load inertia, gradually increase the setting by 50 ms and check the performance. Note: Ensure that n2-02 ≤ n2-03. When making adjustments to n2-02, set C4-02 (Torque Compensation Primary Delay Time Constant 1) accordingly. 50 ms 50 to 2000 ms
3 • Overvoltage trips when accelerating, decelerating, or during sudden speed or load changes. AFR Time Constant 2 (n2-03) • If overvoltage trips occur, gradually increase this setting by 50 ms. • If response is slow, gradually reduce this setting by 10 ms. Note: Ensure that n2-02 ≤ n2-03. When making adjustments to n2-03, increase the value of C4-06 (Torque Compensation Primary Delay Time 2) proportionally. 750 ms 750 to 2000 ms
4 • Overvoltage trips when accelerating, decelerating, or during sudden speed or load changes. Torque Compensation Primary Delay Time Constant 2 (C4-06) • If overvoltage trips occur, gradually increase this setting by 10 ms and check the performance. • If response is slow, gradually reduce this setting by 2 ms and check the performance. Note: Ensure that C4-02 ≤ C4-06. When changing C4-06 (Torque Compensation Primary Delay Time Constant 2), increase the value of n2-03 proportionally. 150 ms 150 to 750 ms
5 • Poor motor torque and speed response • Motor hunting and oscillation. Torque Compensation Primary Delay Time Constant 1 (C4-02) • To improve motor torque speed response, gradually reduce this setting by 2 ms and check the performance. • If motor hunting and oscillation occur, gradually increase this setting by 10 ms. Note: Ensure that C4-02 ≤ C4-06. When making adjustments to C4-02, increase n2-02 (AFR Time Constant) proportionally. 20 ms <2> 20 to 100 ms
6 • Poor speed response and stability Slip Compensation Primary Delay Time Constant (C3-02) • If response is slow, gradually decrease the setting by 10 ms. • If speed is unstable, gradually increase the setting by 10 ms. 200 ms <2> 100 to 500 ms
7 • Poor speed precision Slip Compensation Gain (C3-01) • If speed is too slow, gradually increase the setting by 0.1 ms. • If speed is too fast, gradually decrease the setting by 0.1 ms. 1.0 <2> 0.5 to 1.5
8 • Motor noise • Control motor hunting and oscillation occur at speeds below 10 Hz. Carrier Frequency Selection (C6-02) • If there is too much motor noise, the carrier frequency is too high. • If motor hunting and oscillation occur at low speeds, reduce the carrier frequency. • The default setting for the carrier frequency depends on the drive capacity (o2-04) and Drive Duty Selection (C6-01). 7 (Swing PWM 1) 0 to the default setting

Manual — OLV footnotes and application tuning — page 262

Source reference: SIEP C71060618F, December 2016, physical PDF page 262. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Problem | Parameter No. | Corrective Action | Default Value | Suggested Setting

<1> Default setting is determined by drive model. Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00. Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50. <2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default setting shown is for V/f Control.

When using OLV Motor Control, leave the torque compensation gain (C4-01) at its default setting of 1.00. To increase speed precision during regeneration in OLV Motor Control, enable slip compensation during regeneration (C3-04 = “1”).

u Motor Hunting and Oscillation Control Parameters

In addition to the parameters discussed on page 169, the following parameters indirectly affect motor hunting and oscillation.

Table 6.3 Parameters that Affect Control Performance in Applications

Name (Parameter No.) Application

6.2 Motor Performance Fine Tuning

OLV tuning continuation | • Poor motor torque at low speeds • Poor speed response • Motor instability at motor start.

Application tuning parameters | Dwell Function (b6-01 through b6-04)

Application tuning parameters | Accel/Decel Time (C1-01 through C1-09)

Application tuning parameters | S-Curve Characteristics (C2-01 through C2-04)

Application tuning parameters | Jump Frequency (d3-01 through d3-04)

Application tuning parameters | Analog Filter Time Constant (H3-13)

Application tuning parameters | Stall Prevention (L3-01 through L3-06, L3-11)

Application tuning parameters | Torque Limits (L7-01 through L7-04, L7-06, L7-07)

OLV tuning continuation — PDF page 262

Source row Problem Parameter No. Corrective Action Default Value Suggested Setting
1 • Poor motor torque at low speeds • Poor speed response • Motor instability at motor start. Mid Output Voltage A (E1-08) Minimum Output Voltage (E1-10) • If motor torque and speed response are too slow, increase the setting. • If the motor exhibits excessive instability at start- up, reduce the setting. Note: The default value is for 200 V class units. Double this value when using a 400 V class drive. When working with a relatively light load, increasing this value too much can create an excessively high of a torque reference. E1-08: <2> 12.0 V E1-10: 2.5 V <2> Initial ±2 V

Application tuning parameters — PDF page 262

Source row Name (Parameter No.) Application
1 Dwell Function (b6-01 through b6-04) Prevents motor speed loss by maintaining the output frequency when working with heavy loads or when there is powerful backlash on the machine side.
2 Accel/Decel Time (C1-01 through C1-09) Adjusting accel and decel times will affect the torque presented to the motor during acceleration or deceleration.
3 S-Curve Characteristics (C2-01 through C2-04) Prevents shock at the beginning and end of acceleration and deceleration.
4 Jump Frequency (d3-01 through d3-04) Skips over the resonant frequencies of connected machinery.
5 Analog Filter Time Constant (H3-13) Prevents fluctuation in the analog input signal due to noise.
6 Stall Prevention (L3-01 through L3-06, L3-11) • Prevents motor speed loss and overvoltage. Used when the load is too heavy and also during sudden acceleration/deceleration. • Adjustment is not normally required because Stall Prevention is enabled as a default. Disable Stall Prevention during deceleration (L3-04 = “0”) when using a braking resistor.
7 Torque Limits (L7-01 through L7-04, L7-06, L7-07) • Sets the maximum torque for Open Loop Vector Control. • Ensure that the drive capacity is greater than the motor capacity when increasing this setting. Be careful when reducing this value because motor speed loss may occur with heavy loads.

Manual — Alarm, fault and error responses — page 263

Source reference: SIEP C71060618F, December 2016, physical PDF page 263. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

6.3 Drive Alarms, Faults, and Errors

u Types of Alarms, Faults, and Errors

Check the LED operator for information about possible faults if the drive or motor fails to operate. Refer to Using the Digital LED Operator on page 80. If problems occur that are not covered in this manual, contact the nearest Yaskawa representative with the following information: • Drive model • Software version • Date of purchase • Description of the problem Table 6.4 contains descriptions of the various types of alarms, faults, and errors that may occur while operating the drive. Contact Yaskawa in the event of drive failure.

Table 6.4 Types of Alarms, Faults, and Errors

Type Drive Responses to Alarms, Faults, and Errors

Troubleshooting

Alarm, fault and error response | Faults

Alarm, fault and error response | Minor Faults and Alarms

Alarm, fault and error response | Operation Errors

Alarm, fault and error response | Tuning Errors

Alarm, fault and error response — PDF page 263

Source row Type Drive Responses to Alarms, Faults, and Errors
1 Faults When the drive detects a fault: • The digital operator displays text that indicates the specific fault and the ALM indicator LED remains lit until the fault is reset. • The fault interrupts drive output and the motor coasts to a stop. • Depending on the setting, the drive and motor may stop via different methods than listed. • If a digital output is programmed for fault output (H2-□□ = E), it will close if a fault occurs. When the drive detects a fault, it will remain inoperable until that fault has been reset. Refer to Fault Reset Methods on page 298.
2 Minor Faults and Alarms When the drive detects an alarm or a minor fault: • The digital operator displays text that indicates the specific alarm or minor fault and the ALM indicator LED flashes. • The motor does not stop. • One of the multi-function contact outputs closes if set to be tripped by a minor fault (H2-□□ = 10), but not by an alarm. • The digital operator displays text indicating a specific alarm and ALM indicator LED flashes. Remove the cause of an alarm or minor fault to automatically reset.
3 Operation Errors When parameter settings conflict with one another or do not match hardware settings (such as with an option card), it results in an operation error. When the drive detects an operation error: • The digital operator displays text that indicates the specific error. • Multi-function contact outputs do not operate. When the drive detects an operation error, it will not operate the motor until the error has been reset. Correct the settings that caused the operation error to reset.
4 Tuning Errors Tuning errors occur while performing Auto-Tuning. When the drive detects a tuning error: • The digital operator displays text indicating the specific error. • Multi-function contact outputs do not operate. • Motor coasts to stop. • Remove the cause of the error and repeat the Auto-Tuning process.

Manual — Complete fault display index — page 264

Source reference: SIEP C71060618F, December 2016, physical PDF page 264. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

bUS. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CE. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CoF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF02. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF03. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF06. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF07. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF08. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF11. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF12. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF13. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF14. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF16. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF17. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF18. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF19. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF20 or CPF21. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF22. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF23. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF24. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

CPF25. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

dEv. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

dWAL. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

dWFL. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

E5. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

EF0. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

EF1 to EF7. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

Err. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

FbH. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

FbL. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

GF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

LF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

LF2. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

nSE. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oC. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oFA00. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oFA01. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oFA03. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oFA04. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oFA30 to oFA43. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oH. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oH1. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oH3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oH4. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oL1. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oL2. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oL3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oL4. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oL5. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oL7. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oPr. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

oS. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

ov. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

PF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

PGo. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

rH. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

rr. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

SC. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

SEr. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

STo. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

UL3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

UL4. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

UL5. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

Uv1. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

Uv2. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

Uv3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.

u Alarm and Error Displays

n Faults

When the drive detects a fault, the ALM indicator LEDs remain lit without flashing. If the LEDs flash, the drive has detected a minor fault or alarm. Refer to Minor Faults and Alarms on page 265 for more information. Conditions such as overvoltage or external faults can trip both faults and minor faults, therefore it is important to note whether the LEDs remain lit or if the LEDs flash.

Table 6.5 Fault Displays

Digital Operator Display | Name | Pg.

6.3 Drive Alarms, Faults, and Errors

Literal index only; named faults, page references and minor-fault output availability are distinct. Read complete fault cause and solution sections. LED segment geometry remains original-only.

Fault index | bUS

Fault index | CE

Fault index | CF

Fault index | CoF

Fault index | CPF02

Fault index | CPF03

Fault index | CPF06

Fault index | CPF07

Fault index | CPF08

Fault index | CPF11

Fault index | CPF12

Fault index | CPF13

Fault index | CPF14

Fault index | CPF16

Fault index | CPF17

Fault index | CPF18

Fault index | CPF19

Fault index | CPF20 or CPF21

Fault index | CPF22

Fault index | CPF23

Fault index | CPF24

Fault index | CPF25

Fault index | dEv

Fault index | dWAL

Fault index | dWFL

Fault index | E5

Fault index | EF0

Fault index | EF1 to EF7

Fault index | Err

Fault index | FbH

Fault index | FbL

Fault index | GF

Fault index | LF

Fault index | LF2

Fault index | nSE

Fault index | oC

Fault index | oFA00

Fault index | oFA01

Fault index | oFA03

Fault index | oFA04

Fault index | oFA30 to oFA43

Fault index | oH

Fault index | oH1

Fault index | oH3

Fault index | oH4

Fault index | oL1

Fault index | oL2

Fault index | oL3

Fault index | oL4

Fault index | oL5

Fault index | oL7

Fault index | oPr

Fault index | oS

Fault index | ov

Fault index | PF

Fault index | PGo

Fault index | rH

Fault index | rr

Fault index | SC

Fault index | SEr

Fault index | STo

Fault index | UL3

Fault index | UL4

Fault index | UL5

Fault index | Uv1

Fault index | Uv2

Fault index | Uv3

Fault index — PDF page 264

Source row Literal display code Name Page
1 bUS Option Communication Error 267
2 CE MEMOBUS/Modbus Communication Error 267
3 CF Control Fault 267
4 CoF Current Offset Fault 267
5 CPF02 A/D Conversion Error 268
6 CPF03 PWM Data Fault 268
7 CPF06 Drive Specification Mismatch during Terminal Board or Control Board Replacement 268
8 CPF07 Terminal Board Communication Fault 268
9 CPF08 EEPROM Serial Communications Fault 268
10 CPF11 RAM Fault 268
11 CPF12 FLASH Memory Fault 268
12 CPF13 Watchdog Circuit Exception 269
13 CPF14 Control Circuit Fault 269
14 CPF16 Clock Fault 269
15 CPF17 Timing Fault 269
16 CPF18 Control Circuit Fault 269
17 CPF19 Control Circuit Fault 269
18 CPF20 or CPF21 RAM Fault 269
19 CPF20 or CPF21 FLASH Memory Fault 269
20 CPF20 or CPF21 Watchdog Circuit Exception 269
21 CPF20 or CPF21 Clock Fault 269
22 CPF22 A/D Conversion Error 269
23 CPF23 PWM Feedback Data Fault 269
24 CPF24 Drive Capacity Signal Fault 270
25 CPF25 Terminal Board Not Connected 270
26 dEv Excessive Speed Deviation (for Simple V/f with PG) 270
27 dWAL DriveWorksEZ Program Error Output 270
28 dWFL DriveWorksEZ Fault 270
29 E5 MECHATROLINK Watchdog Timer Error 270
30 EF0 Option External Fault 270
31 EF1 to EF7 External Fault (input terminal S1 to S7) 270
32 Err EEPROM Write Error 271
33 FbH Excessive PID Feedback 271
34 FbL PID Feedback Loss 271

Fault index — PDF page 264

Source row Literal display code Name Page
1 GF Ground Fault 271
2 LF Output Phase Loss 272
3 LF2 Current Imbalance 272
4 nSE Node Setup Error 272
5 oC Overcurrent 272
6 oFA00 Option Card Connection Error 273
7 oFA01 Option Unit Fault 273
8 oFA03 Option Card Fault 273
9 oFA04 Option Card Fault 273
10 oFA30 to oFA43 Option Card Fault 273
11 oH Heatsink Overheat 274
12 oH1 Heatsink Overheat 274
13 oH3 Motor Overheat 1 (PTC input) 274
14 oH4 Motor Overheat 2 (PTC input) 275
15 oL1 Motor Overload 275
16 oL2 Drive Overload 275
17 oL3 Overtorque Detection 1 276
18 oL4 Overtorque Detection 2 276
19 oL5 Mechanical Weakening Detection 1 276
20 oL7 High Slip Braking oL 276
21 oPr Operator Connection Fault 277
22 oS Overspeed (for Simple V/f with PG) 277
23 ov Overvoltage 277
24 PF Input Phase Loss 278
25 PGo PG Disconnect (for Simple V/f with PG) 278
26 rH Dynamic Braking Resistor 278
27 rr Dynamic Braking Transistor 279
28 SC IGBT Short Circuit 279
29 SEr Too Many Speed Search Restarts 279
30 STo Pull-Out Detection 279
31 UL3 Undertorque Detection 1 279
32 UL4 Undertorque Detection 2 280
33 UL5 Mechanical Weakening Detection 2 280
34 Uv1 Undervoltage 280
35 Uv2 Control Power Supply Undervoltage 280
36 Uv3 Soft Charge Circuit Fault 280

Manual — Minor-fault index and fault footnotes — page 265

Source reference: SIEP C71060618F, December 2016, physical PDF page 265. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

AEr. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

bb. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

bUS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CALL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CrST. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CyC. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

dEv. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

dnE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

dWAL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

E5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF0. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF1 to EF7. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

FbH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

FbL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Hbb. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

HbbF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

HCA. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

LT-1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

LT-2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

LT-3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

LT-4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oH2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oH3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oL3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oL4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oL5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

ov. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

PASS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

PGo. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

rUn. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

<1> Displayed as CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show CPF21. <2> Available in drive software versions PRG: 1020 and later. <3> Uv1 and Uv2 faults are not saved to the fault history

n Minor Faults and Alarms

When a minor fault or alarm occurs, the ALM LED flashes and the text display shows an alarm code. A fault has occurred if the text remains lit and does not flash. Refer to Alarm Detection on page 282. An overvoltage situation, for example, can trigger both faults and minor faults. It is therefore important to note whether the LEDs remain lit or if the LEDs flash.

Table 6.6 Minor Fault and Alarm Displays

Digital Operator Display | Name | Minor Fault Output (H2-□□ = 10) | Pg.

6.3 Drive Alarms, Faults, and Errors

Troubleshooting

Literal index only; named faults, page references and minor-fault output availability are distinct. Read complete fault cause and solution sections. LED segment geometry remains original-only.

Minor fault/alarm index | AEr

Minor fault/alarm index | bb

Minor fault/alarm index | bUS

Minor fault/alarm index | CALL

Minor fault/alarm index | CE

Minor fault/alarm index | CrST

Minor fault/alarm index | CyC

Minor fault/alarm index | dEv

Minor fault/alarm index | dnE

Minor fault/alarm index | dWAL

Minor fault/alarm index | E5

Minor fault/alarm index | EF

Minor fault/alarm index | EF0

Minor fault/alarm index | EF1 to EF7

Minor fault/alarm index | FbH

Minor fault/alarm index | FbL

Minor fault/alarm index | Hbb

Minor fault/alarm index | HbbF

Minor fault/alarm index | HCA

Minor fault/alarm index | LT-1

Minor fault/alarm index | LT-2

Minor fault/alarm index | LT-3

Minor fault/alarm index | LT-4

Minor fault/alarm index | oH

Minor fault/alarm index | oH2

Minor fault/alarm index | oH3

Minor fault/alarm index | oL3

Minor fault/alarm index | oL4

Minor fault/alarm index | oL5

Minor fault/alarm index | oS

Minor fault/alarm index | ov

Minor fault/alarm index | PASS

Minor fault/alarm index | PGo

Minor fault/alarm index | rUn

Minor fault/alarm index — PDF page 265

Source row Literal display code Name Minor Fault Output (H2-□□=10) Page
1 AEr Station Address Setting Error (CC-Link, CANopen, MECHATROLINK) YES 282
2 bb Drive Baseblock No output 282
3 bUS Option Card Communications Error YES 282
4 CALL Serial Communication Transmission Error YES 282
5 CE MEMOBUS/Modbus Communication Error YES 283
6 CrST Can Not Reset YES 283
7 CyC MECHATROLINK Comm. Cycle Setting Error YES 283
8 dEv Excessive Speed Deviation (for Simple V/f with PG) YES 283
9 dnE Drive Disabled YES 284
10 dWAL DriveWorksEZ Alarm YES 270
11 E5 MECHATROLINK Watchdog Timer Error YES 284
12 EF Run Command Input Error YES 284
13 EF0 Option Card External Fault YES 284
14 EF1 to EF7 External Fault (input terminal S1 to S7) YES 284
15 FbH Excessive PID Feedback YES 285
16 FbL PID Feedback Loss YES 285
17 Hbb Safe Disable Signal Input YES 285
18 HbbF Safe Disable Signal Input YES 285
19 HCA Current Alarm YES 285
20 LT-1 Cooling Fan Maintenance Alarm No output <1> 286
21 LT-2 Capacitor Maintenance Alarm No output <1> 286
22 LT-3 Soft Charge Bypass Relay Maintenance Time No output <1> 286
23 LT-4 IGBT Maintenance Time (50%) No output <1> 286
24 oH Heatsink Overheat YES 286
25 oH2 Drive Overheat YES 287
26 oH3 Motor Overheat YES 287
27 oL3 Overtorque 1 YES 287
28 oL4 Overtorque 2 YES 287
29 oL5 Mechanical Weakening Detection 1 YES 288
30 oS Overspeed (for Simple V/f with PG) YES 288
31 ov Overvoltage YES 288
32 PASS MEMOBUS/Modbus Test Mode Complete No output 288
33 PGo PG Disconnect (for Simple V/f with PG) YES 288
34 rUn During Run 2, Motor Switch Command Input YES 289

Manual — Minor, operation and tuning error indices — page 266

Source reference: SIEP C71060618F, December 2016, physical PDF page 266. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

SE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

TrPC. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

UL3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

UL4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

UL5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Uv. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE01. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE02. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE04. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE05. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE07. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE08. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE09. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE10. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE11. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oPE13. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

End1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

End2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

End3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-01. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-02. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-04. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-05. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-08. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-09. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-11. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Er-12. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display | Name | Minor Fault Output (H2-□□ = 10) | Pg.

<1> Output when H2-□□ = F

n Operation Errors

Table 6.7 Operation Error Displays

Digital Operator Display | Name | Pg.

n Auto-Tuning Errors

Table 6.8 Auto-Tuning Error Displays

6.3 Drive Alarms, Faults, and Errors

Literal index only; named faults, page references and minor-fault output availability are distinct. Read complete fault cause and solution sections. LED segment geometry remains original-only.

Minor fault/alarm index | SE

Minor fault/alarm index | TrPC

Minor fault/alarm index | UL3

Minor fault/alarm index | UL4

Minor fault/alarm index | UL5

Minor fault/alarm index | Uv

Operation error index | oPE01

Operation error index | oPE02

Operation error index | oPE03

Operation error index | oPE04

Operation error index | oPE05

Operation error index | oPE07

Operation error index | oPE08

Operation error index | oPE09

Operation error index | oPE10

Operation error index | oPE11

Operation error index | oPE13

Auto-Tuning error index | End1

Auto-Tuning error index | End2

Auto-Tuning error index | End3

Auto-Tuning error index | Er-01

Auto-Tuning error index | Er-02

Auto-Tuning error index | Er-03

Auto-Tuning error index | Er-04

Auto-Tuning error index | Er-05

Auto-Tuning error index | Er-08

Auto-Tuning error index | Er-09

Auto-Tuning error index | Er-11

Auto-Tuning error index | Er-12

Minor fault/alarm index — PDF page 266

Source row Literal display code Name Minor Fault Output (H2-□□=10) Page
1 SE MEMOBUS/Modbus Test Mode Fault YES 289
2 TrPC IGBT Maintenance Time (90%) YES 289
3 UL3 Undertorque 1 YES 289
4 UL4 Undertorque 2 YES 289
5 UL5 Mechanical Weakening Detection 2 YES 280
6 Uv Undervoltage YES 290

Operation error index — PDF page 266

Source row Literal display code Name Page
1 oPE01 Drive Unit Setting Error 291
2 oPE02 Parameter Setting Range Error 291
3 oPE03 Multi-Function Input Setting Error 291
4 oPE04 Terminal Board Mismatch Error 292
5 oPE05 Run Command Selection Error 292
6 oPE07 Multi-Function Analog Input Selection Error 292

Operation error index — PDF page 266

Source row Literal display code Name Page
1 oPE08 Parameter Selection Error 293
2 oPE09 PID Control Selection Error 293
3 oPE10 V/f Data Setting Error 294
4 oPE11 Carrier Frequency Setting Error 294
5 oPE13 Pulse Train Monitor Selection Error 294

Auto-Tuning error index — PDF page 266

Source row Literal display code Name Page
1 End1 Excessive V/f Setting 295
2 End2 Motor Iron Core Saturation Coefficient Error 295
3 End3 Rated Current Setting Alarm 295
4 Er-01 Motor Data Error 295
5 Er-02 Alarm 295
6 Er-03 STOP button Input 296

Auto-Tuning error index — PDF page 266

Source row Literal display code Name Page
1 Er-04 Line-to-Line Resistance Error 296
2 Er-05 No-Load Current Error 296
3 Er-08 Rated Slip Error 296
4 Er-09 Acceleration Error 296
5 Er-11 Motor Speed Error 296
6 Er-12 Current Detection Error 296

Manual — Communication and control faults — page 267

Source reference: SIEP C71060618F, December 2016, physical PDF page 267. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

bUS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CoF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

6.4 Fault Detection

u Fault Displays, Causes, and Possible Solutions

Table 6.9 Detailed Fault Displays, Causes, and Possible Solutions

Digital Operator Display Fault Name

Cause Possible Solution

Troubleshooting

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

bUS fault definition | bUS

Fault code scope bUS. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

bUS causes and possible solutions | No signal received from the PLC.

bUS causes and possible solutions | The communication cable is faulty or a short circuit exists.

bUS causes and possible solutions | A communications data error occurred due to noise.

bUS causes and possible solutions | The option card is damaged.

bUS causes and possible solutions | The option card is not properly connected to the drive.

CE fault definition | CE

Fault code scope CE. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CE causes and possible solutions | Faulty communications wiring, or a short circuit exists.

CE causes and possible solutions | A communications data error occurred due to noise.

CF fault definition | CF

Fault code scope CF. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CF causes and possible solutions | Motor parameters are not set properly.

CF causes and possible solutions | Torque limit is too low.

CF causes and possible solutions | Load inertia is too big.

CoF fault definition | CoF

bUS fault definition — PDF page 267

Source row Literal display code Source fault name or description
1 bUS Option Communication Error
2 bUS • After establishing initial communication, the connection was lost. • Only detected when the run command frequency reference is assigned to an option card.

bUS causes and possible solutions — PDF page 267

Source row Cause Possible solution
1 No signal received from the PLC. • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed.
2 The communication cable is faulty or a short circuit exists. • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed.
3 A communications data error occurred due to noise. • Check the various options available to minimize the effects of noise. • Counteract noise in control circuit, main circuit, and ground wiring. • Ensure that other equipment such as switches or relays do not cause noise and use surge suppressors if required. • Use cables recommended by Yaskawa or another type of shielded line. Ground the shield on the controller side or on the drive input power side. • Separate all wiring for communications devices from drive input power lines. Install an EMC noise filter to the input side of the drive input power.
4 The option card is damaged. • Replace the option card if there are no problems with the wiring and the error continues to occur.
5 The option card is not properly connected to the drive. • The connector pins on the option card are not properly lined up with the connector pins on the drive. • Reinstall the option card.

CE fault definition — PDF page 267

Source row Literal display code Source fault name or description
1 CE MEMOBUS/Modbus Communication Error
2 CE Control data was not received for the CE detection time set to H5-09.

CE causes and possible solutions — PDF page 267

Source row Cause Possible solution
1 Faulty communications wiring, or a short circuit exists. • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed.
2 A communications data error occurred due to noise. • Check the various options available to minimize the effects of noise. • Counteract noise in control circuit, main circuit, and ground wiring. • Use Yaskawa-recommended cables, or another type of shielded line. Ground the shield on the controller side or on the drive input power side. • Ensure that other equipment such as switches or relays do not cause noise and use surge suppressors if required. • Separate all wiring for communications devices from drive input power lines. Install an EMC noise filter to the input side of the drive input power.

CF fault definition — PDF page 267

Source row Literal display code Source fault name or description
1 CF Control Fault
2 CF A torque limit was reached continuously for three seconds or longer during a ramp to stop while in Open Loop Vector Control.

CF causes and possible solutions — PDF page 267

Source row Cause Possible solution
1 Motor parameters are not set properly. Check the motor parameter settings and repeat Auto-Tuning.
2 Torque limit is too low. Set the torque limit to the most appropriate setting (L7-01 through L7-04).
3 Load inertia is too big. • Adjust the deceleration time (C1-02, -04, -06, -08). • Set the frequency to the minimum value and interrupt the run command when the drive finishes decelerating.

CoF fault definition — PDF page 267

Source row Literal display code Source fault name or description
1 CoF Current Offset Fault
2 CoF The current sensor is damaged or there was residual induction current in the motor (e.g., during sudden deceleration or when coasting) when the drive attempted to start the motor.

Manual — Current offset and control-board faults — page 268

Source reference: SIEP C71060618F, December 2016, physical PDF page 268. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

CPF02. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF06. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF07. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF08. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF11. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF12. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.

CoF continued from PDF267 causes and possible solutions | Due to residual induction current in the motor when the drive attempted to start the motor, the drive attempted to adjust the current offset value beyond the allowable range.

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

CPF02 fault definition | CPF02

Fault code scope CPF02. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF02 causes and possible solutions | Control circuit is damaged.

CPF02 causes and possible solutions | Control circuit terminals have shorted out (+V, AC).

CPF02 causes and possible solutions | Control terminal input current has exceeded allowable levels.

CPF03 fault definition | CPF03

Fault code scope CPF03. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF03 causes and possible solutions | Drive hardware is damaged.

CPF06 fault definition | CPF06

Fault code scope CPF06. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF06 causes and possible solutions | Control circuit is damaged.

CPF06 causes and possible solutions | The power supply was switched off when parameters were written (e.g., using a communications option card).

CPF07 fault definition | CPF07

Fault code scope CPF07. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF07 causes and possible solutions | There is a fault connection between the terminal board and control board.

CPF08 fault definition | CPF08

Fault code scope CPF08. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF08 causes and possible solutions | Terminal board or control board is not connected properly.

CPF11 fault definition | CPF11

Fault code scope CPF11. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF11 causes and possible solutions | Hardware is damaged.

CPF12 fault definition | CPF12

Fault code scope CPF12. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF12 causes and possible solutions | Hardware is damaged.

CoF continued from PDF267 causes and possible solutions — PDF page 268

Source row Cause Possible solution
1 Due to residual induction current in the motor when the drive attempted to start the motor, the drive attempted to adjust the current offset value beyond the allowable range. • Create a motor restart sequence that allows enough time for the residual induction voltage to dissipate. • Enable Speed Search at start (b3-01 = 1). Use the multi-function terminals to execute External Speed Search 1 and 2 (H1-□□ = 61 or 62). Note: When using a PM motor, both External Speed Search 1 and 2 perform the same operation.

CPF02 fault definition — PDF page 268

Source row Literal display code Source fault name or description
1 CPF02 A/D Conversion Error
2 CPF02 An A/D conversion error occurred.

CPF02 causes and possible solutions — PDF page 268

Source row Cause Possible solution
1 Control circuit is damaged. Cycle power to the drive. If the problem continues, replace the drive.
2 Control circuit terminals have shorted out (+V, AC). • Check for wiring errors along the control circuit terminals. • Correct the wiring.
3 Control circuit terminals have shorted out (+V, AC). Check the resistance of the speed potentiometer and related wiring.
4 Control terminal input current has exceeded allowable levels. • Check the input current. • Reduce the current input to control circuit terminal (+V) to 20 mA.

CPF03 fault definition — PDF page 268

Source row Literal display code Source fault name or description
1 CPF03 PWM Data Error
2 CPF03 There is a problem with the PWM data.

CPF03 causes and possible solutions — PDF page 268

Source row Cause Possible solution
1 Drive hardware is damaged. Replace the drive.

CPF06 fault definition — PDF page 268

Source row Literal display code Source fault name or description
1 CPF06 EEPROM Data Error
2 CPF06 There is an error in the data saved to EEPROM.

CPF06 causes and possible solutions — PDF page 268

Source row Cause Possible solution
1 Control circuit is damaged. Cycle power to the drive. If the problem continues, replace the drive.
2 The power supply was switched off when parameters were written (e.g., using a communications option card). • Cycle power to the drive and check operation again. • Initialize the drive using A1-03. • If the problem persists after initializing the drive, replace the drive.

CPF07 fault definition — PDF page 268

Source row Literal display code Source fault name or description
1 CPF07 Terminal Board Communications Error
2 CPF07 A communication error occurred at the terminal board.

CPF07 causes and possible solutions — PDF page 268

Source row Cause Possible solution
1 There is a fault connection between the terminal board and control board. Turn the power off and reconnect the control circuit terminals.

CPF08 fault definition — PDF page 268

Source row Literal display code Source fault name or description
1 CPF08 EEPROM Serial Communication Fault
2 CPF08 EEPROM communications are not functioning properly.

CPF08 causes and possible solutions — PDF page 268

Source row Cause Possible solution
1 Terminal board or control board is not connected properly. Turn the power off and check the control terminal connections.

CPF11 fault definition — PDF page 268

Source row Literal display code Source fault name or description
1 CPF11 RAM Fault

CPF11 causes and possible solutions — PDF page 268

Source row Cause Possible solution
1 Hardware is damaged. Replace the drive.

CPF12 fault definition — PDF page 268

Source row Literal display code Source fault name or description
1 CPF12 FLASH Memory Fault
2 CPF12 Problem with the ROM (FLASH memory).

Manual — CPU and internal drive faults — page 269

Source reference: SIEP C71060618F, December 2016, physical PDF page 269. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

CPF13. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF14. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF16. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF17. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF18. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF19. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF20 or CPF21. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF22. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF23. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Troubleshooting

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

CPF13 fault definition | CPF13

Fault code scope CPF13. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF13 causes and possible solutions | Hardware is damaged.

CPF14 fault definition | CPF14

Fault code scope CPF14. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF14 causes and possible solutions | Hardware is damaged.

CPF16 fault definition | CPF16

Fault code scope CPF16. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF16 causes and possible solutions | Hardware is damaged.

CPF17 fault definition | CPF17

Fault code scope CPF17. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF17 causes and possible solutions | Hardware is damaged.

CPF18 fault definition | CPF18

Fault code scope CPF18. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF18 causes and possible solutions | Hardware is damaged.

CPF19 fault definition | CPF19

Fault code scope CPF19. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF19 causes and possible solutions | Hardware is damaged.

CPF20 or CPF21 fault definition | CPF20 or CPF21

Fault code scope CPF20 or CPF21. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF20 or CPF21 causes and possible solutions | Hardware is damaged.

CPF22 fault definition | CPF22

Fault code scope CPF22. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF22 causes and possible solutions | Control circuit is damaged.

CPF23 fault definition | CPF23

CPF13 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF13 Watchdog Circuit Exception
2 CPF13 Self-diagnostics problem.

CPF13 causes and possible solutions — PDF page 269

Source row Cause Possible solution
1 Hardware is damaged. Replace the drive.

CPF14 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF14 Control Circuit Fault
2 CPF14 CPU error (CPU operates incorrectly due to noise, etc.)

CPF16 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF16 Clock Fault
2 CPF16 Standard clock error.

CPF17 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF17 Timing Fault
2 CPF17 A timing error occurred during an internal process.

CPF18 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF18 Control Circuit Fault
2 CPF18 CPU error. Non-Maskable Interrupt (An unusual interrupt was triggered by noise, etc.)

CPF19 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF19 Control Circuit Fault
2 CPF19 CPU error (Manual reset due to noise, etc.)

CPF20 or CPF21 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF20 or CPF21 One of the following faults occurred: RAM fault, FLASH memory error, watchdog circuit exception, clock error
2 CPF20 or CPF21 • RAM fault. • FLASH memory error (ROM error). • Watchdog circuit exception (self-diagnostic error). • Clock error.

CPF22 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF22 A/D Conversion Fault
2 CPF22 A/D conversion error.

CPF22 causes and possible solutions — PDF page 269

Source row Cause Possible solution
1 Control circuit is damaged. • Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 298. • If the problem continues, replace the drive.

CPF23 fault definition — PDF page 269

Source row Literal display code Source fault name or description
1 CPF23 PWM Feedback Fault
2 CPF23 PWM feedback error.

Manual — Capacity, board, option and external faults — page 270

Source reference: SIEP C71060618F, December 2016, physical PDF page 270. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

CPF24. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

CPF25. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

dEv. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

dWFL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

dWAL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

E5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF0. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name Cause Possible Solution

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.

CPF23 continued from PDF269 causes and possible solutions | Hardware is damaged.

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

CPF24 fault definition | CPF24

Fault code scope CPF24. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF24 causes and possible solutions | Hardware is damaged.

CPF25 fault definition | CPF25

Fault code scope CPF25. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

CPF25 causes and possible solutions | Terminal board is not connected correctly.

dEv fault definition | dEv

Fault code scope dEv. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

dEv causes and possible solutions | Load is too heavy.

dEv causes and possible solutions | Acceleration and deceleration times are set too short.

dEv causes and possible solutions | The load is locked up.

dEv causes and possible solutions | Parameters are not set appropriately.

dEv causes and possible solutions | Motor brake engaged.

dWFL / dWAL fault definition | dWFL

dWFL / dWAL fault definition | dWAL

Fault code scope dWFL / dWAL. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

dWFL / dWAL causes and possible solutions | Fault output by DriveWorksEZ

E5 fault definition | E5

Fault code scope E5. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

E5 causes and possible solutions | Data has not been received from the PLC, triggering the watchdog timer.

EF0 fault definition | EF0

Fault code scope EF0. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

EF0 causes and possible solutions | An external fault was received from the PLC with other than F6-03 = 3 “alarm only” (the drive continued to run after external fault).

EF0 causes and possible solutions | Problem with the PLC program.

EF1 / EF2 / EF3 fault definition | EF1

EF1 / EF2 / EF3 fault definition | EF2

EF1 / EF2 / EF3 fault definition | EF3

CPF23 continued from PDF269 causes and possible solutions — PDF page 270

Source row Cause Possible solution
1 Hardware is damaged. Replace the drive.

CPF24 fault definition — PDF page 270

Source row Literal display code Source fault name or description
1 CPF24 Drive Capacity Signal Fault
2 CPF24 Entered a capacity that does not exist. (Checked when the drive is powered up.)

CPF25 fault definition — PDF page 270

Source row Literal display code Source fault name or description
1 CPF25 Terminal Board Not Connected

CPF25 causes and possible solutions — PDF page 270

Source row Cause Possible solution
1 Terminal board is not connected correctly. Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.

dEv fault definition — PDF page 270

Source row Literal display code Source fault name or description
1 dEv Speed Deviation (for Simple V/f with PG)
2 dEv According to the pulse input (RP), the speed deviation is greater than the setting in F1-10 for longer than the time set to F1-11.

dEv causes and possible solutions — PDF page 270

Source row Cause Possible solution
1 Load is too heavy. Reduce the load.
2 Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08).
3 The load is locked up. Check the machine.
4 Parameters are not set appropriately. Check the settings of parameters F1-10 and F1-11.
5 Motor brake engaged. Ensure the motor brake releases properly.

dWFL / dWAL fault definition — PDF page 270

Source row Literal display code Source fault name or description
1 dWFL DriveWorksEZ Fault
2 dWAL DriveWorksEZ Program Error Output

dWFL / dWAL causes and possible solutions — PDF page 270

Source row Cause Possible solution
1 Fault output by DriveWorksEZ Correct the cause of the fault.

E5 fault definition — PDF page 270

Source row Literal display code Source fault name or description
1 E5 MECHATROLINK Watchdog Timer Error
2 E5 The watchdog timed out.

E5 causes and possible solutions — PDF page 270

Source row Cause Possible solution
1 Data has not been received from the PLC, triggering the watchdog timer. Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and proceed to phase 3.

EF0 fault definition — PDF page 270

Source row Literal display code Source fault name or description
1 EF0 Option Card External Fault
2 EF0 An external fault condition is present.

EF0 causes and possible solutions — PDF page 270

Source row Cause Possible solution
1 An external fault was received from the PLC with other than F6-03 = 3 “alarm only” (the drive continued to run after external fault). • Remove the cause of the external fault. • Remove the external fault input from the PLC.
2 Problem with the PLC program. Check the PLC program and correct problems.

EF1 / EF2 / EF3 fault definition — PDF page 270

Source row Literal display code Source fault name or description
1 EF1 External Fault (input terminal S1)
2 EF1 External fault at multi-function input terminal S1.
3 EF2 External Fault (input terminal S2)
4 EF2 External fault at multi-function input terminal S2.
5 EF3 External Fault (input terminal S3)
6 EF3 External fault at multi-function input terminal S3.

Manual — External, EEPROM, PID and ground faults — page 271

Source reference: SIEP C71060618F, December 2016, physical PDF page 271. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

EF4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF6. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

EF7. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Err. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

FbH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

FbL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

GF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Troubleshooting

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

EF4 / EF5 / EF6 / EF7 fault definition | EF4

EF4 / EF5 / EF6 / EF7 fault definition | EF5

EF4 / EF5 / EF6 / EF7 fault definition | EF6

EF4 / EF5 / EF6 / EF7 fault definition | EF7

Fault code scope EF4 / EF5 / EF6 / EF7. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

EF4 / EF5 / EF6 / EF7 causes and possible solutions | An external device has tripped an alarm function.

EF4 / EF5 / EF6 / EF7 causes and possible solutions | Wiring is incorrect.

EF4 / EF5 / EF6 / EF7 causes and possible solutions | Incorrect setting of multi-function contact inputs.

Err fault definition | Err

Fault code scope Err. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

Err causes and possible solutions | -

FbH fault definition | FbH

Fault code scope FbH. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

FbH causes and possible solutions | Parameters are not set appropriately.

FbH causes and possible solutions | Wiring for PID feedback is incorrect.

FbH causes and possible solutions | There is a problem with the feedback sensor.

FbL fault definition | FbL

Fault code scope FbL. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

FbL causes and possible solutions | Parameters are not set appropriately.

FbL causes and possible solutions | Wiring for PID feedback is incorrect.

FbL causes and possible solutions | There is a problem with the feedback sensor.

GF fault definition | GF

Fault code scope GF. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

GF causes and possible solutions | Motor insulation is damaged.

EF4 / EF5 / EF6 / EF7 fault definition — PDF page 271

Source row Literal display code Source fault name or description
1 EF4 External Fault (input terminal S4)
2 EF4 External fault at multi-function input terminal S4.
3 EF5 External Fault (input terminal S5)
4 EF5 External fault at multi-function input terminal S5.
5 EF6 External Fault (input terminal S6)
6 EF6 External fault at multi-function input terminal S6.
7 EF7 External Fault (input terminal S7)
8 EF7 External fault at multi-function input terminal S7

EF4 / EF5 / EF6 / EF7 causes and possible solutions — PDF page 271

Source row Cause Possible solution
1 An external device has tripped an alarm function. Remove the cause of the external fault and reset the fault.
2 Wiring is incorrect. • Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1-□□ = 20 to 2F). • Reconnect the signal line.
3 Incorrect setting of multi-function contact inputs. • Check if the unused terminals set for H1-□□ = 20 to 2F (External Fault). • Change the terminal settings.

Err fault definition — PDF page 271

Source row Literal display code Source fault name or description
1 Err EEPROM Write Error
2 Err Data does not match the EEPROM being written to.

Err causes and possible solutions — PDF page 271

Source row Cause Possible solution
1 - • Press the ENTER button. • Correct the parameter settings. • Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 298.

FbH fault definition — PDF page 271

Source row Literal display code Source fault name or description
1 FbH Excessive PID Feedback
2 FbH PID feedback input is greater than the level set b5-36 for longer than the time set to b5-37. Set b5-12 to 2 or 5 to enable fault detection.

FbH causes and possible solutions — PDF page 271

Source row Cause Possible solution
1 Parameters are not set appropriately. Check the settings of parameters b5-36 and b5-37.
2 Wiring for PID feedback is incorrect. Correct the wiring.
3 There is a problem with the feedback sensor. • Check the sensor on the control side. • Replace the sensor if damaged.

FbL fault definition — PDF page 271

Source row Literal display code Source fault name or description
1 FbL PID Feedback Loss
2 FbL This fault occurs when PID Feedback Loss Detection is programmed to fault (b5-12 = 2) and the PID Feedback < PID Feedback Loss Detection Level (b5-13) for the PID Feedback Loss Detection Time (b5-14).

FbL causes and possible solutions — PDF page 271

Source row Cause Possible solution
1 Parameters are not set appropriately. Check the settings of parameters b5-13 and b5-14.
2 Wiring for PID feedback is incorrect. Correct the wiring.
3 There is a problem with the feedback sensor. Check the sensor on the controller side. If damaged, replace the sensor.

GF fault definition — PDF page 271

Source row Literal display code Source fault name or description
1 GF Ground Fault
2 GF • Current shorted to ground exceeded 50% of rated current on output side of the drive. • Setting L8-09 to 1 enables ground fault detection in models 2A0020 to 2A0069 and 4A0011 to 4A0038.

GF causes and possible solutions — PDF page 271

Source row Cause Possible solution
1 Motor insulation is damaged. • Check the insulation resistance of the motor. • Replace the motor.

Manual — Ground, phase, node and overcurrent faults — page 272

Source reference: SIEP C71060618F, December 2016, physical PDF page 272. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

LF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

LF2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

nSE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oC. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.

GF continued from PDF271 causes and possible solutions | A damaged motor cable is creating a short circuit.

GF continued from PDF271 causes and possible solutions | The leakage current at the drive output is too high.

GF continued from PDF271 causes and possible solutions | The drive started to run during Current Offset Fault or while coasting to a stop.

GF continued from PDF271 causes and possible solutions | Hardware problem.

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

LF fault definition | LF

Fault code scope LF. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

LF causes and possible solutions | The output cable is disconnected.

LF causes and possible solutions | The motor winding is damaged.

LF causes and possible solutions | The output terminal is loose.

LF causes and possible solutions | The motor being used is less than 5% of the drive rated current.

LF causes and possible solutions | An output transistor is damaged.

LF causes and possible solutions | A single-phase motor is being used.

LF2 fault definition | LF2

Fault code scope LF2. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

LF2 causes and possible solutions | Phase loss has occurred on the output side of the drive.

LF2 causes and possible solutions | Terminal wires on the output side of the drive are loose.

LF2 causes and possible solutions | No signal displays from the gate driver board.

LF2 causes and possible solutions | Motor impedance or motor phases are uneven.

nSE fault definition | nSE

Fault code scope nSE. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

nSE causes and possible solutions | The node setup terminal closed during Run.

nSE causes and possible solutions | A Run command was issued while the node setup function was active.

oC fault definition | oC

Fault code scope oC. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oC causes and possible solutions | The motor has been damaged due to overheating or the motor insulation is damaged.

GF continued from PDF271 causes and possible solutions — PDF page 272

Source row Cause Possible solution
1 A damaged motor cable is creating a short circuit. • Check the motor cable. • Remove the short circuit and turn the power back on.
2 A damaged motor cable is creating a short circuit. • Check the resistance between the cable and the ground terminal ⏚. • Replace the cable.
3 The leakage current at the drive output is too high. • Reduce the carrier frequency. • Reduce the amount of stray capacitance.
4 The drive started to run during Current Offset Fault or while coasting to a stop. • The value set exceeds the allowable setting range while the drive automatically adjusts the current offset (this happens only attempting to restart a PM motor that is coasting to stop). • Enable Speed Search at start (b3-01 = 1). • Perform Speed Search 1 or 2 (H1-□□ = 61 or 62) via one of the external terminals. Note: Speed Search 1 and 2 are the same when using OLV/PM control mode.
5 Hardware problem. • Replace the drive.

LF fault definition — PDF page 272

Source row Literal display code Source fault name or description
1 LF Output Phase Loss
2 LF • Phase loss on the output side of the drive. • Phase Loss Detection is enabled when L8-07 is set to 1 or 2.

LF causes and possible solutions — PDF page 272

Source row Cause Possible solution
1 The output cable is disconnected. • Check for wiring errors and ensure the output cable is connected properly. • Correct the wiring.
2 The motor winding is damaged. • Check the resistance between motor lines. • Replace the motor if the winding is damaged.
3 The output terminal is loose. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Size and Torque Specifications on page 66.
4 The motor being used is less than 5% of the drive rated current. Check the drive and motor capacities.
5 An output transistor is damaged. Replace the drive.
6 A single-phase motor is being used. The drive being used cannot operate a single phase motor.

LF2 fault definition — PDF page 272

Source row Literal display code Source fault name or description
1 LF2 Output current imbalance
2 LF2 One or more of the phases in the output current is lost.

LF2 causes and possible solutions — PDF page 272

Source row Cause Possible solution
1 Phase loss has occurred on the output side of the drive. • Check for faulty wiring or poor connections on the output side of the drive. • Correct the wiring.
2 Terminal wires on the output side of the drive are loose. Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Size and Torque Specifications on page 66.
3 No signal displays from the gate driver board. Replace the drive. Contact Yaskawa for assistance.
4 Motor impedance or motor phases are uneven. • Measure the line-to-line resistance for each motor phase. Ensure all values are the same. • Replace the motor. Contact Yaskawa for assistance.

nSE fault definition — PDF page 272

Source row Literal display code Source fault name or description
1 nSE Node Setup Error
2 nSE A terminal assigned to the node setup function closed during Run.

nSE causes and possible solutions — PDF page 272

Source row Cause Possible solution
1 The node setup terminal closed during Run. • Check whether a Run command was accidentally entered via the terminals or from a comm. option unit. • Turn off the Run command when using the node setup function.
2 A Run command was issued while the node setup function was active. • Check whether a Run command was accidentally entered via the terminals or from a comm. option unit. • Turn off the Run command when using the node setup function.

oC fault definition — PDF page 272

Source row Literal display code Source fault name or description
1 oC Overcurrent
2 oC Drive sensors have detected an output current greater than the specified overcurrent level.

oC causes and possible solutions — PDF page 272

Source row Cause Possible solution
1 The motor has been damaged due to overheating or the motor insulation is damaged. • Check the insulation resistance. • Replace the motor.

Manual — Overcurrent and option card faults — page 273

Source reference: SIEP C71060618F, December 2016, physical PDF page 273. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oFA00. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oFA01. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oFA03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Troubleshooting

Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.

oC continued from PDF272 causes and possible solutions | One of the motor cables has shorted out or there is a grounding problem.

oC continued from PDF272 causes and possible solutions | The load is too heavy.

oC continued from PDF272 causes and possible solutions | The acceleration or deceleration times are too short.

oC continued from PDF272 causes and possible solutions | The drive is attempting to operate a specialized motor or a motor larger than the maximum size allowed.

oC continued from PDF272 causes and possible solutions | Magnetic contactor (MC) on the output side of the drive has turned on or off.

oC continued from PDF272 causes and possible solutions | V/f setting is not operating as expected.

oC continued from PDF272 causes and possible solutions | Excessive torque compensation.

oC continued from PDF272 causes and possible solutions | Drive fails to operate properly due to noise interference.

oC continued from PDF272 causes and possible solutions | Overexcitation gain is set too high.

oC continued from PDF272 causes and possible solutions | Run command applied while motor was coasting.

oC continued from PDF272 causes and possible solutions | The wrong motor code has been entered for in OLV/PM (Yaskawa motors only).

oC continued from PDF272 causes and possible solutions | The motor control method and motor do not match.

oC continued from PDF272 causes and possible solutions | The motor cable is too long

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

oFA00 fault definition | oFA00

Fault code scope oFA00. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oFA00 causes and possible solutions | The option card is incompatible with the drive.

oFA01 fault definition | oFA01

Fault code scope oFA01. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oFA01 causes and possible solutions | The option card is not connected properly to the drive.

oFA03 fault definition | oFA03

oC continued from PDF272 causes and possible solutions — PDF page 273

Source row Cause Possible solution
1 One of the motor cables has shorted out or there is a grounding problem. • Check the motor cables. • Remove the short circuit and power the drive back up.
2 One of the motor cables has shorted out or there is a grounding problem. • Check the resistance between the motor cables and the ground terminal ⏚. • Replace damaged cables.
3 The load is too heavy. • Measure the current flowing into the motor. • Replace the drive with a larger capacity unit if the current value exceeds the rated current of the drive. • Determine if there is sudden fluctuation in the current level. • Reduce the load to avoid sudden changes in the current level or switch to a larger drive.
4 The acceleration or deceleration times are too short. Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration time. If the right amount of torque cannot be set, make the following changes: • Increase the acceleration time (C1-01, C1-03, C1-05, C1-07) • Increase the S-curve characteristics (C2-01 through C2-04) • Increase the capacity of the drive.
5 The drive is attempting to operate a specialized motor or a motor larger than the maximum size allowed. • Check the motor capacity. • Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the motor nameplate.
6 Magnetic contactor (MC) on the output side of the drive has turned on or off. Set up the operation sequence so that the MC is not tripped while the drive is outputting current.
7 V/f setting is not operating as expected. • Check the ratios between the voltage and frequency. • Set parameter E1-04 through E1-10 appropriately. Set E3-04 through E3-10 when using a second motor. • Lower the voltage if it is too high relative to the frequency.
8 Excessive torque compensation. • Check the amount of torque compensation. • Reduce the torque compensation gain (C4-01) until there is no speed loss and less current.
9 Drive fails to operate properly due to noise interference. • Review the possible solutions provided for handling noise interference. • Review the section on handling noise interference and check the control circuit lines, main circuit lines and ground wiring.
10 Overexcitation gain is set too high. • Check if fault occurs simultaneously to overexcitation function operation. • Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).
11 Run command applied while motor was coasting. • Set b3-01 to 1 to enable Speed Search at Start. • Program the Speed Search command input through one of the multi-function contact input terminals (H1-□□ = “61” or “62”).
12 The wrong motor code has been entered for in OLV/PM (Yaskawa motors only). Enter the correct motor code to E5-01 to indicate that a PM motor is connected.
13 The motor control method and motor do not match. Check which motor control method the drive is set to in A1-02. • For IM motors, set A1-02 to 0 or 2. • For PM motors, set A1-02 to 5.
14 The motor cable is too long Use a larger drive.

oFA00 fault definition — PDF page 273

Source row Literal display code Source fault name or description
1 oFA00 Option Card Connection Error at Option Port CN5
2 oFA00 The option card is incompatible with the drive.

oFA00 causes and possible solutions — PDF page 273

Source row Cause Possible solution
1 The option card is incompatible with the drive. Use a compatible option card.

oFA01 fault definition — PDF page 273

Source row Literal display code Source fault name or description
1 oFA01 Option Card Fault
2 oFA01 Replace the option card.

oFA01 causes and possible solutions — PDF page 273

Source row Cause Possible solution
1 The option card is not connected properly to the drive. Turn the power off and reconnect the option card.

oFA03 fault definition — PDF page 273

Source row Literal display code Source fault name or description
1 oFA03 Option Card Fault
2 oFA03 Option card self-diagnostic error

Manual — Option and heatsink/PTC faults — page 274

Source reference: SIEP C71060618F, December 2016, physical PDF page 274. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oFA04. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oFA30 to oFA43. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oH1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oH3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

oFA04 / oFA30 to oFA43 fault definition | oFA04

oFA04 / oFA30 to oFA43 fault definition | oFA30 to oFA43

Fault code scope oFA04 / oFA30 to oFA43. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oFA04 / oFA30 to oFA43 causes and possible solutions | Option card or hardware is damaged.

oH fault definition | oH

Fault code scope oH. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oH causes and possible solutions | Surrounding temperature is too high.

oH causes and possible solutions | Load is too heavy.

oH causes and possible solutions | Internal cooling fan is stopped.

oH1 fault definition | oH1

Fault code scope oH1. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oH1 causes and possible solutions | Surrounding temperature is too high.

oH1 causes and possible solutions | Load is too heavy.

oH1 causes and possible solutions | The internal cooling fan has reached its performance life or has malfunctioned.

oH1 causes and possible solutions | Current flowing to control circuit terminal +V exceeded the tolerance level.

oH3 fault definition | oH3

Fault code scope oH3. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oH3 causes and possible solutions | Motor has overheated

oFA04 / oFA30 to oFA43 fault definition — PDF page 274

Source row Literal display code Source fault name or description
1 oFA04 Option Card Fault
2 oFA04 An error occurred attempting to write to the option card memory.
3 oFA30 to oFA43 Option Card Fault
4 oFA30 to oFA43 Communication ID error

oFA04 / oFA30 to oFA43 causes and possible solutions — PDF page 274

Source row Cause Possible solution
1 Option card or hardware is damaged. Replace the option card. Contact Yaskawa for consultation.

oH fault definition — PDF page 274

Source row Literal display code Source fault name or description
1 oH Heatsink Overheat
2 oH The temperature of the heatsink exceeded the value set to L8-02. Default value for L8-02 is determined by drive capacity (o2-04).

oH causes and possible solutions — PDF page 274

Source row Cause Possible solution
1 Surrounding temperature is too high. • Check the temperature surrounding the drive. Verify temperature is within drive specifications. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool the surrounding area. • Remove anything near the drive that might be producing excessive heat.
2 Load is too heavy. • Measure the output current. • Decrease the load. • Lower the carrier frequency in C6-02.
3 Internal cooling fan is stopped. • After replacing the fan, set o4-03 to 0 to reset cooling fan maintenance.

oH1 fault definition — PDF page 274

Source row Literal display code Source fault name or description
1 oH1 Overheat 1 (Heatsink Overheat)
2 oH1 The temperature of the heatsink has exceeded 10 °C plus the default value of L8-02.

oH1 causes and possible solutions — PDF page 274

Source row Cause Possible solution
1 Surrounding temperature is too high. • Check the temperature surrounding the drive. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool the surrounding area. • Remove anything near the drive that might be producing excessive heat.
2 Load is too heavy. • Measure the output current. • Lower the carrier frequency (C6-02). • Reduce the load.
3 The internal cooling fan has reached its performance life or has malfunctioned. • Check the maintenance time for the cooling fan (U4-04). • After replacing the fan, set o4-03 to 0 to reset cooling fan maintenance.
4 Current flowing to control circuit terminal +V exceeded the tolerance level. • Check the current level of the terminal. • Set the current to the control circuit terminal to be 20 mA or less.

oH3 fault definition — PDF page 274

Source row Literal display code Source fault name or description
1 oH3 Motor Overheat Alarm (PTC Input)
2 oH3 • The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level. • Detection requires multi-function analog input H3-02 or H3-10 be set to E.

oH3 causes and possible solutions — PDF page 274

Source row Cause Possible solution
1 Motor has overheated • Check the size of the load, the accel/decel times and the cycle times. • Decrease the load. • Increase the acceleration and deceleration times (C1-01 through C1-08).
2 Motor has overheated • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. • Be careful not to lower E1-08 and E1-10 excessively, as this reduces load tolerance at low speeds.
3 Motor has overheated • Check the motor-rated current. • Enter the motor-rated current as indicated on the motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system.

Manual — PTC, motor overload and drive-overload definition — page 275

Source reference: SIEP C71060618F, December 2016, physical PDF page 275. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oH4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oL1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

oL2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Troubleshooting

Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.

oH4 fault definition | oH4

Fault code scope oH4. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oH4 causes and possible solutions | Motor has overheated.

oL1 fault definition | oL1

Fault code scope oL1. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.

oL1 causes and possible solutions | Cycle times are too short during acceleration and deceleration.

oL1 causes and possible solutions | • Drive overloaded at low speeds. • Overload may occur at low speeds when using a general-purpose motor, even if operating within the rated current limitation.

oL1 causes and possible solutions | Although a special type of motor is being used, the motor protection selection is set for a general-purpose motor (L1-01 = 1).

oL1 causes and possible solutions | Voltage is too high for the V/f characteristics.

oL1 causes and possible solutions | The wrong motor-rated current is set to E2-01.

oL1 causes and possible solutions | The motor base frequency for the drive input power is set too low.

oL1 causes and possible solutions | Multiple motors are running off the same drive.

oL1 causes and possible solutions | The electrical thermal protection characteristics and motor overload characteristics do not match.

oL1 causes and possible solutions | The electrical thermal relay is operating at the wrong level.

oL1 causes and possible solutions | Motor overheated by overexcitation operation.

oL1 causes and possible solutions | Speed Search related parameters are not set to the proper values.

oL1 causes and possible solutions | Output current fluctuation due to input phase loss

oL2 fault definition | oL2

oH4 fault definition — PDF page 275

Source row Literal display code Source fault name or description
1 oH4 Motor Overheat Fault (PTC Input)
2 oH4 • The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level. • Detection requires multi-function analog input H3-02 or H3-10 be set to E.

oH4 causes and possible solutions — PDF page 275

Source row Cause Possible solution
1 Motor has overheated. • Check the size of the load, the accel/decel times and the cycle times. • Decrease the load. • Increase the acceleration and deceleration times (C1-01 through C1-08).
2 Motor has overheated. • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds
3 Motor has overheated. • Check the motor-rated current. • Enter the motor-rated current as indicated on the motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system.

oL1 fault definition — PDF page 275

Source row Literal display code Source fault name or description
1 oL1 Motor Overload
2 oL1 The electrothermal sensor tripped overload protection. Note: The U4-16 value must be less than 100 before oL1 can be reset.

oL1 causes and possible solutions — PDF page 275

Source row Cause Possible solution
1 Cycle times are too short during acceleration and deceleration. Increase the acceleration and deceleration times (C1-01 through C1-08).
2 • Drive overloaded at low speeds. • Overload may occur at low speeds when using a general-purpose motor, even if operating within the rated current limitation. • Reduce the load. • Increase the speed. • If the drive is supposed to operate at low speeds, either increase the motor capacity or use a motor specifically designed to operate with the drive.
3 Although a special type of motor is being used, the motor protection selection is set for a general-purpose motor (L1-01 = 1). Set L1-01 to 2.
4 Voltage is too high for the V/f characteristics. • Adjust the user set V/f patterns (E1-04 through E1-10). Parameters E1-08 and E1-10 may need to be reduced. • If E1-08 and E1-10 are set too high, there may be very little load tolerance at low speed.
5 The wrong motor-rated current is set to E2-01. • Check the motor-rated current. • Enter the value written on the motor nameplate to parameter E2-01.
6 The motor base frequency for the drive input power is set too low. • Check the rated frequency indicated on the motor nameplate. • Enter the rated frequency to E1-06 (Base Frequency).
7 Multiple motors are running off the same drive. Set L1-01 to 0 to disable the Motor Protection function and install a thermal relay to each motor.
8 The electrical thermal protection characteristics and motor overload characteristics do not match. • Check the motor characteristics. • Correct the value set to L1-01 (Motor Protection Function). • Install an external thermal relay.
9 The electrical thermal relay is operating at the wrong level. • Check the current rating listed on the motor nameplate. • Check the value set for the motor-rated current (E2-01).
10 Motor overheated by overexcitation operation. • Overexcitation increases the motor losses and the motor temperature. If applied too long, motor damage can occur. Prevent excessive overexcitation operation or apply proper cooling to the motor • Reduce the excitation deceleration gain (n3-13). • Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
11 Speed Search related parameters are not set to the proper values. • Check values set to Speed Search related parameters. • Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively). • After Auto-Tuning, enable Speed Estimation Type Search (b3-24 = “1”).
12 Output current fluctuation due to input phase loss Check the power supply for phase loss.

oL2 fault definition — PDF page 275

Source row Literal display code Source fault name or description
1 oL2 Drive Overload
2 oL2 The thermal sensor of the drive triggered overload protection.

Manual — Drive overload, torque and high-slip faults — page 276

Source reference: SIEP C71060618F, December 2016, physical PDF page 276. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oL7. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name Cause Possible Solution

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

oL2 from PDF275 cause/solution continuation | Load is too heavy.

oL2 from PDF275 cause/solution continuation | Cycle times are too short during acceleration and deceleration.

oL2 from PDF275 cause/solution continuation | Voltage is too high for the V/f characteristics.

oL2 from PDF275 cause/solution continuation | Drive capacity is too small.

oL2 from PDF275 cause/solution continuation | Overload occurred when operating at low speeds.

oL2 from PDF275 cause/solution continuation | Excessive torque compensation.

oL2 from PDF275 cause/solution continuation | Speed Search related parameters are not set correctly.

oL2 from PDF275 cause/solution continuation | Output current fluctuation due to input phase loss

Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.

oL3 fault definition | oL3

Fault/error code scope: oL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oL3 fault causes and solutions | Parameter settings are not appropriate for the type of load.

oL3 fault causes and solutions | There is a fault on the machine side (e.g., the machine is locked up).

oL4 fault definition | oL4

Fault/error code scope: oL4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oL4 fault causes and solutions | Parameter settings are not appropriate for the type of load.

oL5 fault definition | oL5

Fault/error code scope: oL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oL5 fault causes and solutions | Overtorque occurred, triggering the mechanical weakening level set to L6-08.

oL7 fault definition | oL7

Fault/error code scope: oL7. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oL7 fault causes and solutions | Excessive load inertia.

oL7 fault causes and solutions | Motor is driven by the load.

oL7 fault causes and solutions | Something on the load side is restricting deceleration.

oL7 fault causes and solutions | The overload time during High-slip Braking is too short.

oL2 from PDF275 cause/solution continuation — PDF page 276

Source row Cause Possible solution
1 Load is too heavy. Reduce the load.
2 Cycle times are too short during acceleration and deceleration. Increase the settings for the acceleration and deceleration times (C1-01 through C1-08).
3 Voltage is too high for the V/f characteristics. • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. • Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds.
4 Drive capacity is too small. Replace the drive with a larger model.
5 Overload occurred when operating at low speeds. • Reduce the load when operating at low speeds. • Replace the drive with a model that is one frame size larger. • Lower the carrier frequency (C6-02).
6 Excessive torque compensation. Reduce the torque compensation gain (C4-01) until there is no speed loss but less current.
7 Speed Search related parameters are not set correctly. • Check the settings for all Speed Search related parameters. • Adjust the current used during Speed Search and the Speed Search deceleration time (b3-03 and b3-02 respectively). • After Auto-Tuning the drive, enable the Speed Search Estimation Type (b3-24 = “1”).
8 Output current fluctuation due to input phase loss Check the power supply for phase loss.

oL3 fault definition — PDF page 276

Source row Literal display code Name or definition
1 oL3 Overtorque Detection 1
2 oL3 The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).

oL3 fault causes and solutions — PDF page 276

Source row Cause Possible solution
1 Parameter settings are not appropriate for the type of load. Check the settings of parameters L6-02 and L6-03.
2 There is a fault on the machine side (e.g., the machine is locked up). Check the status of the load. Remove the cause of the fault.

oL4 fault definition — PDF page 276

Source row Literal display code Name or definition
1 oL4 Overtorque Detection 2
2 oL4 The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable time (L6-06).

oL4 fault causes and solutions — PDF page 276

Source row Cause Possible solution
1 Parameter settings are not appropriate for the type of load. Check the settings of parameters L6-05 and L6-06.

oL5 fault definition — PDF page 276

Source row Literal display code Name or definition
1 oL5 Mechanical Weakening Detection 1
2 oL5 Overtorque occurred, matching the conditions specified in L6-08.

oL5 fault causes and solutions — PDF page 276

Source row Cause Possible solution
1 Overtorque occurred, triggering the mechanical weakening level set to L6-08. Check for the cause of mechanical weakening.

oL7 fault definition — PDF page 276

Source row Literal display code Name or definition
1 oL7 High-Slip Braking oL
2 oL7 The output frequency stayed constant for longer than the time set in n3-04 during High-slip Braking.

oL7 fault causes and solutions — PDF page 276

Source row Cause Possible solution
1 Excessive load inertia. • Reduce deceleration times using parameters C1-02, C1-04, C1-06 and C1-08 in applications that do not use High-slip Braking. • Use a braking resistor to shorten deceleration time.
2 Motor is driven by the load. • Reduce deceleration times using parameters C1-02, C1-04, C1-06 and C1-08 in applications that do not use High-slip Braking. • Use a braking resistor to shorten deceleration time.
3 Something on the load side is restricting deceleration. • Reduce deceleration times using parameters C1-02, C1-04, C1-06 and C1-08 in applications that do not use High-slip Braking. • Use a braking resistor to shorten deceleration time.
4 The overload time during High-slip Braking is too short. • Increase parameter n3-04 (High-slip Braking Overload Time). • Install a thermal relay and increase the parameter setting of n3-04 to the maximum value.

Manual — Operator, overspeed and overvoltage faults — page 277

Source reference: SIEP C71060618F, December 2016, physical PDF page 277. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oPr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

ov. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Troubleshooting

Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.

oPr fault definition | oPr

Fault/error code scope: oPr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPr fault causes and solutions | External operator is not properly connected to the drive.

oS fault definition | oS

Fault/error code scope: oS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oS fault causes and solutions | Overshoot or undershoot is occurring.

oS fault causes and solutions | Incorrect PG pulse settings.

oS fault causes and solutions | Inappropriate parameter settings.

ov fault definition | ov

Fault/error code scope: ov. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

ov fault causes and solutions | Deceleration time is too short and regenerative energy flows from the motor into the drive.

ov fault causes and solutions | Fast acceleration time causes the motor to overshoot the speed reference.

ov fault causes and solutions | Excessive braking load.

ov fault causes and solutions | Surge voltage entering from the drive input power.

ov fault causes and solutions | Ground fault in the output circuit causing the DC bus capacitor to overcharge.

ov fault causes and solutions | Improper Setting of Speed Search related parameters. (Includes Speed Search after a momentary power loss and after a fault restart.)

ov fault causes and solutions | Excessive regeneration when overshoot occurs after acceleration.

ov fault causes and solutions | Drive input power voltage is too high.

ov fault causes and solutions | The dynamic braking transistor is damaged.

ov fault causes and solutions | The braking transistor is wired incorrectly.

oPr fault definition — PDF page 277

Source row Literal display code Name or definition
1 oPr External Digital Operator Connection Fault
2 oPr • The external operator has been disconnected from the drive. Note: An oPr fault will occur when all of the following conditions are true: • Output is interrupted when the operator is disconnected (o2-06 = 1). • The run command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).

oPr fault causes and solutions — PDF page 277

Source row Cause Possible solution
1 External operator is not properly connected to the drive. • Check the connection between the operator and the drive. • Replace the cable if damaged. • Turn off the drive input power and disconnect the operator. Next reconnect the operator and turn the drive input power back on.

oS fault definition — PDF page 277

Source row Literal display code Name or definition
1 oS Overspeed (Simple V/f with PG)
2 oS Pulse input (RP) indicates that motor speed feedback exceeded F1-08 setting.

oS fault causes and solutions — PDF page 277

Source row Cause Possible solution
1 Overshoot or undershoot is occurring. • Adjust the gain by using the pulse train input parameters (H6-02 through H6-05). • Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1).
2 Incorrect PG pulse settings. Set the H6-02 (Pulse Train Input Scaling) = 100%, the frequency of the PG pulses at maximum motor speed.
3 Inappropriate parameter settings. Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).

ov fault definition — PDF page 277

Source row Literal display code Name or definition
1 ov Overvoltage
2 ov Voltage in the DC bus has exceeded the overvoltage detection level. • For 200 V class: approximately 410 V • For 400 V class: approximately 820 V (740 V when E1-01 is less than 400)

ov fault causes and solutions — PDF page 277

Source row Cause Possible solution
1 Deceleration time is too short and regenerative energy flows from the motor into the drive. • Increase the deceleration time (C1-02, C1-04, C1-06, C1-08). • Install a braking resistor or a dynamic braking resistor unit. • Enable stall prevention during deceleration (L3-04 = “1”). Stall prevention is enabled as the default setting.
2 Fast acceleration time causes the motor to overshoot the speed reference. • Check if sudden drive acceleration triggers an overvoltage alarm. • Increase the acceleration time. • Use longer S-curve acceleration and deceleration times.
3 Excessive braking load. The braking torque was too high, causing regenerative energy to charge the DC bus. Reduce the braking torque, use a braking option, or lengthen decel time.
4 Surge voltage entering from the drive input power. Install a DC link choke. Note: Voltage surge can result from thyristor convertor and phase advancing capacitor using same drive main input power supply.
5 Ground fault in the output circuit causing the DC bus capacitor to overcharge. • Check the motor wiring for ground faults. • Correct grounding shorts and turn the power back on.
6 Improper Setting of Speed Search related parameters. (Includes Speed Search after a momentary power loss and after a fault restart.) • Check the settings for Speed Search related parameters. • Enable Speed Search Retry function (b3-19 greater than or equal to 1 to 10). • Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03 respectively). • Perform Line-to-Line Resistance Auto-Tuning and then enable Speed Estimation Type Speed Search (b3-24 = 1).
7 Excessive regeneration when overshoot occurs after acceleration. • Enable the Overvoltage Suppression function (L3-11 = 1). • Lengthen the S-curve at acceleration end.
8 Drive input power voltage is too high. • Check the voltage. • Lower drive input power voltage within the limits listed in the specifications.
9 The dynamic braking transistor is damaged. Replace the drive.
10 The braking transistor is wired incorrectly. • Check braking transistor wiring for errors. • Properly rewire the braking resistor device.

Manual — Overvoltage, phase-loss and braking faults — page 278

Source reference: SIEP C71060618F, December 2016, physical PDF page 278. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

PF. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

PGo. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

rH. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

ov from PDF277 cause/solution continuation | Drive fails to operate properly due to noise interference.

ov from PDF277 cause/solution continuation | Load inertia has been set incorrectly.

ov from PDF277 cause/solution continuation | Braking function is being used in PM Open Loop Vector Control.

ov from PDF277 cause/solution continuation | Motor hunting occurs.

Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.

PF fault definition | PF

Fault/error code scope: PF. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

PF fault causes and solutions | There is phase loss in the drive input power.

PF fault causes and solutions | There is loose wiring in the drive input power terminals.

PF fault causes and solutions | There is excessive fluctuation in the drive input power voltage.

PF fault causes and solutions | There is poor balance between voltage phases.

PF fault causes and solutions | The main circuit capacitors are worn.

PGo fault definition | PGo

Fault/error code scope: PGo. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

PGo fault causes and solutions | Pulse input (RP) is disconnected.

PGo fault causes and solutions | Pulse input (RP) wiring is wrong.

PGo fault causes and solutions | Motor brake engaged.

rH fault definition | rH

Fault/error code scope: rH. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

rH fault causes and solutions | Deceleration time is too short and excessive regenerative energy is flowing back into the drive.

ov from PDF277 cause/solution continuation — PDF page 278

Source row Cause Possible solution
1 Drive fails to operate properly due to noise interference. • Review the list of possible solutions provided for controlling noise. • Review the section on handling noise interference and check the control circuit lines, main circuit lines and ground wiring.
2 Load inertia has been set incorrectly. • Check the load inertia settings when using KEB, overvoltage suppression or Stall Prevention during deceleration. • Adjust L3-25 (Load Inertia Ratio) in accordance with the load.
3 Braking function is being used in PM Open Loop Vector Control. Connect a braking resistor.
4 Motor hunting occurs. • Adjust the parameters that control hunting. • Set the hunting prevention gain (n1-02). • Adjust the AFR time constant 1 (n2-02) and the AFR time constant 2 (n2-03) when in OLV Control. • Use parameters n8-45 (PM Speed Feedback Detection Suppression Gain) and n8-47 (Pull-In Current Compensation Time Constant).

PF fault definition — PDF page 278

Source row Literal display code Name or definition
1 PF Input Phase Loss
2 PF Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when L8-05 = 1 (enabled).

PF fault causes and solutions — PDF page 278

Source row Cause Possible solution
1 There is phase loss in the drive input power. • Check for wiring errors in the main circuit drive input power. • Correct the wiring.
2 There is loose wiring in the drive input power terminals. • Ensure the terminals are tightened properly. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torques on page 58 for details.
3 There is excessive fluctuation in the drive input power voltage. • Check the voltage from the drive input power. • Review the possible solutions for stabilizing the drive input power. • Disable Input Phase Loss Detection (L8-05 = “0”). PF is detected if DC bus ripple is too high. If it is disabled, there is no fault but the ripple is still too high, thereby the capacitors are stressed more and lose lifetime.
4 There is poor balance between voltage phases. • Stabilize drive input power or disable phase loss detection.
5 The main circuit capacitors are worn. • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 is greater than 90%.
6 The main circuit capacitors are worn. • Check for anything wrong with the drive input power. • If nothing is wrong with the drive input power, try the following solutions if the alarm continues: • Disable Input Phase Loss Protection selection (L8-05 = “0”). PF is detected if DC bus ripple is too high. If it is disabled, there is no fault but the ripple is still too high, thereby the capacitors are stressed more and lose lifetime. • Replace the drive.

PGo fault definition — PDF page 278

Source row Literal display code Name or definition
1 PGo PG Disconnect (for Simple V/f with PG)
2 PGo No PG pulses are received for longer than the time set to F1-14.

PGo fault causes and solutions — PDF page 278

Source row Cause Possible solution
1 Pulse input (RP) is disconnected. Reconnect the pulse input (RP).
2 Pulse input (RP) wiring is wrong. Correct the wiring.
3 Motor brake engaged. Ensure the motor brake releases properly.

rH fault definition — PDF page 278

Source row Literal display code Name or definition
1 rH Braking Resistor Overheat
2 rH Braking resistor protection was triggered. Fault detection is enabled when L8-01 = 1 (disabled as a default).

rH fault causes and solutions — PDF page 278

Source row Cause Possible solution
1 Deceleration time is too short and excessive regenerative energy is flowing back into the drive. • Check the load, deceleration time and speed. • Reduce the load. • Increase the acceleration and deceleration times (C1-01 through C1-08). • Replace the braking option with a larger device that can handle the power that is discharged.

Manual — Brake, short, speed-search and pull-out faults — page 279

Source reference: SIEP C71060618F, December 2016, physical PDF page 279. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

rr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

SC. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

SEr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

STo. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

UL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more frequently than its rating trips the alarm even when the braking resistor surface is not very hot.

Cause Possible Solution

6.4 Fault Detection

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

rH from PDF278 cause/solution continuation | Excessive braking inertia.

rH from PDF278 cause/solution continuation | The proper braking resistor has not been installed.

Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.

rr fault definition | rr

Fault/error code scope: rr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

rr fault causes and solutions | The braking transistor is damaged.

rr fault causes and solutions | The control circuit is damaged.

SC fault definition | SC

Fault/error code scope: SC. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

SC fault causes and solutions | IGBT fault

SC fault causes and solutions | IGBT short circuit detection and circuit fault

SEr fault definition | SEr

Fault/error code scope: SEr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

SEr fault causes and solutions | Speed Search parameters are set to the wrong values.

SEr fault causes and solutions | The motor is coasting in the opposite direction of the Run command.

STo fault definition | STo

Fault/error code scope: STo. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

STo fault causes and solutions | The wrong motor code has been set (Yaskawa motors only).

STo fault causes and solutions | Load is too heavy.

STo fault causes and solutions | Load inertia is too heavy.

STo fault causes and solutions | Acceleration and deceleration times are too short.

UL3 fault definition | UL3

Fault/error code scope: UL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

UL3 fault causes and solutions | Parameter settings are not appropriate for the type of load.

UL3 fault causes and solutions | There is a fault on the machine side.

rH from PDF278 cause/solution continuation — PDF page 279

Source row Cause Possible solution
1 Excessive braking inertia. Recalculate braking load and braking power. Then try reducing the braking load and checking the braking resistor settings and improve braking capacity.
2 The proper braking resistor has not been installed. • Check the specifications and conditions for the braking resistor device. • Select the optimal braking resistor.

rr fault definition — PDF page 279

Source row Literal display code Name or definition
1 rr Dynamic Braking Transistor
2 rr The built-in dynamic braking transistor failed.

rr fault causes and solutions — PDF page 279

Source row Cause Possible solution
1 The braking transistor is damaged. • Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing and Resetting Faults on page 298. • Replace the drive if the fault continues.
2 The control circuit is damaged. • Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing and Resetting Faults on page 298. • Replace the drive if the fault continues.

SC fault definition — PDF page 279

Source row Literal display code Name or definition
1 SC IGBT Short Circuit

SC fault causes and solutions — PDF page 279

Source row Cause Possible solution
1 IGBT fault • Check motor wiring • Cycle power to the drive. • If the problem continues, contact your Yaskawa representative or the nearest Yaskawa sales office.
2 IGBT short circuit detection and circuit fault • Check motor wiring • Cycle power to the drive. • If the problem continues, contact your Yaskawa representative or the nearest Yaskawa sales office.

SEr fault definition — PDF page 279

Source row Literal display code Name or definition
1 SEr Too Many Speed Search Restarts
2 SEr The number of speed search restarts exceeded the number set to b3-19.

SEr fault causes and solutions — PDF page 279

Source row Cause Possible solution
1 Speed Search parameters are set to the wrong values. • Reduce the detection compensation gain during Speed Search (b3-10). • Increase the current level when attempting Speed Search (b3-17). • Increase the detection time during Speed Search (b3-18). • Repeat Auto-Tuning.
2 The motor is coasting in the opposite direction of the Run command. Set b3-14 to 1 to enable Bi-directional Speed Search.

STo fault definition — PDF page 279

Source row Literal display code Name or definition
1 STo Motor Pull Out or Step Out Detection
2 STo Motor pull out or step out has occurred. Motor has exceeded its pull out torque.

STo fault causes and solutions — PDF page 279

Source row Cause Possible solution
1 The wrong motor code has been set (Yaskawa motors only). • Enter the correct motor code for the PM being used into E5-01. • For special-purpose motors, enter the correct data to all E5 parameters according to the Test Report provided for the motor.
2 Load is too heavy. • Increase the value set to n8-55 (Load Inertia for PM). • Increase the value set to n8-51 (Pull-In Current during Accel/Decel for PM). • Reduce the load. • Increase the motor or drive capacity.
3 Load inertia is too heavy. Increase n8-55 (Load Inertia for PM).
4 Acceleration and deceleration times are too short. • Increase the acceleration and deceleration times (C1-01 through C1-08). • Increase the S-curve acceleration and deceleration times (C2-01).

UL3 fault definition — PDF page 279

Source row Literal display code Name or definition
1 UL3 Undertorque Detection 1
2 UL3 The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable time (L6-03).

UL3 fault causes and solutions — PDF page 279

Source row Cause Possible solution
1 Parameter settings are not appropriate for the type of load. Check the settings of parameters L6-02 and L6-03.
2 There is a fault on the machine side. Check the load for any problems.

Manual — Undertorque and undervoltage faults — page 280

Source reference: SIEP C71060618F, December 2016, physical PDF page 280. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

UL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

UL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Uv1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Uv2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Uv3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.4 Fault Detection

Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.

UL4 fault definition | UL4

Fault/error code scope: UL4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

UL4 fault causes and solutions | Parameter settings are not appropriate for the type of load.

UL4 fault causes and solutions | There is a fault on the machine side.

UL5 fault definition | UL5

Fault/error code scope: UL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

UL5 fault causes and solutions | Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08).

Uv1 fault definition | Uv1

Fault/error code scope: Uv1. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Uv1 fault causes and solutions | Input power phase loss.

Uv1 fault causes and solutions | One of the drive input power wiring terminals is loose.

Uv1 fault causes and solutions | There is a problem with the voltage from the drive input power.

Uv1 fault causes and solutions | The power has been interrupted.

Uv1 fault causes and solutions | Drive internal circuitry has become worn.

Uv1 fault causes and solutions | The drive input power transformer is not large enough and voltage drops after switching on power.

Uv1 fault causes and solutions | Air inside the drive is too hot.

Uv1 fault causes and solutions | Problem with the CHARGE indicator.

Uv2 fault definition | Uv2

Fault/error code scope: Uv2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Uv2 fault causes and solutions | L2-02 changed from its default value in drive that is 7.5 kW or smaller without installing a Momentary Power Loss Ride-Thru.

Uv2 fault causes and solutions | The wiring for the control power supply is damaged.

Uv2 fault causes and solutions | Internal circuitry is damaged.

Uv3 fault definition | Uv3

UL4 fault definition — PDF page 280

Source row Literal display code Name or definition
1 UL4 Undertorque Detection 2
2 UL4 The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable time (L6-06).

UL4 fault causes and solutions — PDF page 280

Source row Cause Possible solution
1 Parameter settings are not appropriate for the type of load. Check the settings of parameters L6-05 and L6-06.
2 There is a fault on the machine side. Check the load for any problems.

UL5 fault definition — PDF page 280

Source row Literal display code Name or definition
1 UL5 Mechanical Weakening Detection 2
2 UL5 The operation conditions matched the conditions set to L6-08.

UL5 fault causes and solutions — PDF page 280

Source row Cause Possible solution
1 Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08). Check the load side for any problems.

Uv1 fault definition — PDF page 280

Source row Literal display code Name or definition
1 Uv1 DC Bus Undervoltage
2 Uv1 One of the following conditions occurred while the drive was in operation: • Voltage in the DC bus fell below the undervoltage detection level (L2-05). • For 200 V class: approximately 190 V (160 V for single phase drives) • For 400 V class: approximately 380 V (350 V when E1-01 is less than 400) The fault is output only if L2-01 = 0 or L2-01 = 1 and the DC bus voltage is under L2-05 for longer than L2-02.

Uv1 fault causes and solutions — PDF page 280

Source row Cause Possible solution
1 Input power phase loss. • The main circuit drive input power is wired incorrectly. • Correct the wiring.
2 One of the drive input power wiring terminals is loose. • Ensure there are no loose terminals. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torques on page 58 for details.
3 There is a problem with the voltage from the drive input power. • Check the voltage. • Correct the voltage to within range listed in drive input power specifications.
4 The power has been interrupted. Correct the drive input power.
5 Drive internal circuitry has become worn. • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 exceeds 90%.
6 The drive input power transformer is not large enough and voltage drops after switching on power. Check the capacity of the drive input power transformer.
7 Air inside the drive is too hot. Check the drive internal temperature.
8 Problem with the CHARGE indicator. Replace the drive.

Uv2 fault definition — PDF page 280

Source row Literal display code Name or definition
1 Uv2 Control Power Supply Voltage Fault
2 Uv2 Voltage is too low for the control drive input power.

Uv2 fault causes and solutions — PDF page 280

Source row Cause Possible solution
1 L2-02 changed from its default value in drive that is 7.5 kW or smaller without installing a Momentary Power Loss Ride-Thru. Correct parameter L2-02 setting or install optional Momentary Power Loss Ride-Thru unit.
2 The wiring for the control power supply is damaged. • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur.
3 Internal circuitry is damaged. • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur.

Uv3 fault definition — PDF page 280

Source row Literal display code Name or definition
1 Uv3 Undervoltage 3 (Inrush Prevention Circuit Fault)
2 Uv3 The inrush prevention circuit has failed.

Manual — Inrush circuit fault continuation — page 281

Source reference: SIEP C71060618F, December 2016, physical PDF page 281. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Digital Operator Display Fault Name

6.4 Fault Detection

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

Uv3 from PDF280 cause/solution continuation | The contactor on the inrush prevention circuit is damaged.

Uv3 from PDF280 cause/solution continuation — PDF page 281

Source row Cause Possible solution
1 The contactor on the inrush prevention circuit is damaged. • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur. • Check monitor U4-06 for the performance life of the inrush prevention circuit. • Replace the drive if U4-06 exceeds 90%.

Manual — Alarms and communication definitions — page 282

Source reference: SIEP C71060618F, December 2016, physical PDF page 282. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

AEr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

bb. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

bUS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

CALL. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

6.5 Alarm Detection

Alarms are drive protection functions that do not operate the fault contact. The drive will return to original status when the cause of the alarm has been removed. During an alarm condition, the Digital Operator display flashes and an alarm output is generated at the multi-function outputs (H2-01 to H2-03), if programmed. Investigate the cause of the alarm and Refer to Detailed Alarm Codes, Causes, and Possible Solutions on page 282 for the appropriate action.

u Alarm Codes, Causes, and Possible Solutions

Table 6.10 Detailed Alarm Codes, Causes, and Possible Solutions

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

AEr minor fault/alarm definition | AEr

Fault/error code scope: AEr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

AEr minor fault/alarm causes and solutions | Station number is set outside the possible setting range.

bb minor fault/alarm definition | bb

Fault/error code scope: bb. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

bb minor fault/alarm causes and solutions | External baseblock signal entered via multi- function input terminal (S1 to S7).

bUS minor fault/alarm definition | bUS

Fault/error code scope: bUS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

bUS minor fault/alarm causes and solutions | Connection is broken or master controller stopped communicating.

bUS minor fault/alarm causes and solutions | Option card is damaged.

bUS minor fault/alarm causes and solutions | The option card is not properly connected to the drive.

bUS minor fault/alarm causes and solutions | A data error occurred due to noise.

CALL minor fault/alarm definition | CALL

AEr minor fault/alarm definition — PDF page 282

Source row Literal display code Name or definition
1 AEr Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
2 AEr Option card node address is outside the acceptable setting range.

AEr minor fault/alarm causes and solutions — PDF page 282

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Station number is set outside the possible setting range. • Set parameter F6-10 to the proper value if a CC-Link option card is used • Set parameter F6-20 to the proper value if a MECHATROLINK option card is used. • Set parameter F6-35 to the proper value if a CANopen option card is used. YES

bb minor fault/alarm definition — PDF page 282

Source row Literal display code Name or definition
1 bb Baseblock
2 bb Drive output interrupted as indicated by an external baseblock signal.

bb minor fault/alarm causes and solutions — PDF page 282

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 External baseblock signal entered via multi- function input terminal (S1 to S7). Check external sequence and baseblock signal input timing. No output

bUS minor fault/alarm definition — PDF page 282

Source row Literal display code Name or definition
1 bUS Option Communication Error
2 bUS • After initial communication was established, the connection was lost. • Assign a run command frequency reference to the option card.

bUS minor fault/alarm causes and solutions — PDF page 282

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Connection is broken or master controller stopped communicating. • Check for faulty wiring. • Correct the wiring. • Repair ground wiring or disconnected cables. YES
2 Option card is damaged. If there are no problems with the wiring and the fault continues to occur, replace the option card. YES
3 The option card is not properly connected to the drive. • The connector pins on the option card are not properly lined up with the connector pins on the drive. • Reinstall the option card. YES
4 A data error occurred due to noise. • Check options available to minimize the effects of noise. • Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring. • Try to reduce noise on the controller side. • Use surge absorbers on magnetic contactors or other equipment causing the disturbance. • Use cables recommended by Yaskawa, or another type of shielded line. The shield should be grounded on the controller side or on the drive input power side. • All wiring for communications devices should be separated from drive input power lines. Install an EMC noise filter to the input side of the drive input power. YES

CALL minor fault/alarm definition — PDF page 282

Source row Literal display code Name or definition
1 CALL Serial Communication Transmission Error
2 CALL Communication has not yet been established.

Manual — Communication, reset and speed-deviation alarms — page 283

Source reference: SIEP C71060618F, December 2016, physical PDF page 283. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

CE. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

CrST. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

CyC. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

dEv. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

CALL from PDF282 cause/solution continuation | Communications wiring is faulty, there is a short circuit, or something is not connected properly.

CALL from PDF282 cause/solution continuation | Programming error on the master side.

CALL from PDF282 cause/solution continuation | Communications circuitry is damaged.

CALL from PDF282 cause/solution continuation | Terminal resistance setting is incorrect.

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

CE minor fault/alarm definition | CE

Fault/error code scope: CE. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

CE minor fault/alarm causes and solutions | A data error occurred due to noise.

CE minor fault/alarm causes and solutions | Communication protocol is incompatible.

CE minor fault/alarm causes and solutions | The CE detection time (H5-09) is set shorter than the time required for a communication cycle to take place.

CE minor fault/alarm causes and solutions | Incompatible PLC software settings or there is a hardware problem.

CE minor fault/alarm causes and solutions | Communications cable is disconnected or damaged.

CrST minor fault/alarm definition | CrST

Fault/error code scope: CrST. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

CrST minor fault/alarm causes and solutions | Fault reset was being executed when a run command was entered.

CyC minor fault/alarm definition | CyC

Fault/error code scope: CyC. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

CyC minor fault/alarm causes and solutions | The controller is using a comm. cycle beyond the allowable setting range for the MECHATROLINK option unit.

dEv minor fault/alarm definition | dEv

CALL from PDF282 cause/solution continuation — PDF page 283

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Communications wiring is faulty, there is a short circuit, or something is not connected properly. • Check for wiring errors. • Correct the wiring. • Remove and ground shorts and reconnect loose wires. YES
2 Programming error on the master side. Check communications at start-up and correct programming errors. YES
3 Communications circuitry is damaged. • Perform a self-diagnostics check. • Replace the drive if the fault continues to occurs. YES
4 Terminal resistance setting is incorrect. The terminal slave drive must have the internal terminal resistance switch set correctly. Place DIP switch S2 to the ON position. YES

CE minor fault/alarm definition — PDF page 283

Source row Literal display code Name or definition
1 CE MEMOBUS/Modbus Communication Error
2 CE Control data was not received correctly for two seconds.

CE minor fault/alarm causes and solutions — PDF page 283

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 A data error occurred due to noise. • Check options available to minimize the effects of noise. • Counteract noise in the control circuit wiring, main circuit lines and ground wiring. • Reduce noise on the controller side. • Use surge absorbers on magnetic contactors or other equipment causing the disturbance. • Use cables recommended by Yaskawa or another type of shielded line. The shield should be grounded on the controller side or on the drive input power side. • Separate all wiring for communications devices from drive input power lines. Install an EMC noise filter to the input side of the drive input power. YES
2 Communication protocol is incompatible. • Check the H5 parameter settings as well as the protocol setting in the controller. • Ensure settings are compatible. YES
3 The CE detection time (H5-09) is set shorter than the time required for a communication cycle to take place. • Check the PLC. • Change the software settings in the PLC. • Set a longer CE detection time (H5-09). YES
4 Incompatible PLC software settings or there is a hardware problem. • Check the PLC. • Remove the cause of the error on the controller side. YES
5 Communications cable is disconnected or damaged. • Check the connector for a signal through the cable. • Replace the communications cable. YES

CrST minor fault/alarm definition — PDF page 283

Source row Literal display code Name or definition
1 CrST Can Not Reset

CrST minor fault/alarm causes and solutions — PDF page 283

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Fault reset was being executed when a run command was entered. • Ensure that a run command cannot be entered from the external terminals or option card during fault reset. • Turn off the run command. YES

CyC minor fault/alarm definition — PDF page 283

Source row Literal display code Name or definition
1 CyC MECHATROLINK Comm. Cycle Setting Error
2 CyC Comm. Cycle Setting Error was detected.

CyC minor fault/alarm causes and solutions — PDF page 283

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 The controller is using a comm. cycle beyond the allowable setting range for the MECHATROLINK option unit. Set the comm. cycle for the upper controller within the allowable setting range for the MECHATROLINK option unit. YES

dEv minor fault/alarm definition — PDF page 283

Source row Literal display code Name or definition
1 dEv Speed Deviation (for Simple V/f with PG)
2 dEv According to the pulse input (RP), the speed deviation is greater than the setting in F1-10 for a time longer than the setting in F1-11.

Manual — External and enable alarms — page 284

Source reference: SIEP C71060618F, December 2016, physical PDF page 284. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

dnE. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

E5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF0. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF6. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

EF7. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

dEv from PDF283 cause/solution continuation | Load is too heavy

dEv from PDF283 cause/solution continuation | Acceleration and deceleration times are set too short.

dEv from PDF283 cause/solution continuation | The load is locked up.

dEv from PDF283 cause/solution continuation | Parameter settings are inappropriate.

dEv from PDF283 cause/solution continuation | The motor brake engaged.

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

dnE minor fault/alarm definition | dnE

Fault/error code scope: dnE. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

dnE minor fault/alarm causes and solutions | “Drive Enable” is set to a multi-function contact input (H1-oo = 6A) and that signal was switched off.

dnE minor fault/alarm causes and solutions | “Drive Enable” is set to a multi-function contact input (H1-□□ = 6A) and that signal was switched off.

E5 minor fault/alarm definition | E5

Fault/error code scope: E5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

E5 minor fault/alarm causes and solutions | The watchdog timer expired while waiting for data from the controller.

EF minor fault/alarm definition | EF

Fault/error code scope: EF. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

EF minor fault/alarm causes and solutions | Sequence error

EF0 minor fault/alarm definition | EF0

Fault/error code scope: EF0. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

EF0 minor fault/alarm causes and solutions | An external fault was received from the PLC with F6-03 = 3 (causing the drive to continue running when an external fault occurs).

EF0 minor fault/alarm causes and solutions | There is a problem with the PLC program.

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF1

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF2

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF3

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF4

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF5

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF6

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF7

dEv from PDF283 cause/solution continuation — PDF page 284

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Load is too heavy Reduce the load. YES
2 Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08). YES
3 The load is locked up. Check the machine. YES
4 Parameter settings are inappropriate. Check the settings of parameters F1-10 and F1-11. YES
5 The motor brake engaged. Ensure the brake releases properly. YES

dnE minor fault/alarm definition — PDF page 284

Source row Literal display code Name or definition
1 dnE Drive Disabled

dnE minor fault/alarm causes and solutions — PDF page 284

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 “Drive Enable” is set to a multi-function contact input (H1-□□ = 6A) and that signal was switched off. Check the operation sequence. YES

E5 minor fault/alarm definition — PDF page 284

Source row Literal display code Name or definition
1 E5 MECHATROLINK Watchdog Timer Error

E5 minor fault/alarm causes and solutions — PDF page 284

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 The watchdog timer expired while waiting for data from the controller. Issue a DISCONNECT or ALM_CLR command, followed by a CONNECT or SYNC_SET command and move to phase 3. YES

EF minor fault/alarm definition — PDF page 284

Source row Literal display code Name or definition
1 EF Forward/Reverse Run Command Input Error
2 EF Both forward run and reverse run closed simultaneously for over 0.5 s.

EF minor fault/alarm causes and solutions — PDF page 284

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Sequence error Check the forward and reverse command sequence and correct the problem. Note: Motor ramps to stop when minor fault EF is detected. YES

EF0 minor fault/alarm definition — PDF page 284

Source row Literal display code Name or definition
1 EF0 Option Card External Fault
2 EF0 An external fault condition is present.

EF0 minor fault/alarm causes and solutions — PDF page 284

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 An external fault was received from the PLC with F6-03 = 3 (causing the drive to continue running when an external fault occurs). • Remove the cause of the external fault. • Remove the external fault input from the PLC. YES
2 There is a problem with the PLC program. Check the PLC program and correct problems. YES

EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition — PDF page 284

Source row Literal display code Name or definition
1 EF1 External fault (input terminal S1)
2 EF1 External fault at multi-function input terminal S1.
3 EF2 External fault (input terminal S2)
4 EF2 External fault at multi-function input terminal S2.
5 EF3 External fault (input terminal S3)
6 EF3 External fault at multi-function input terminal S3.
7 EF4 External fault (input terminal S4)
8 EF4 External fault at multi-function input terminal S4.
9 EF5 External fault (input terminal S5)
10 EF5 External fault at multi-function input terminal S5.
11 EF6 External fault (input terminal S6)
12 EF6 External fault at multi-function input terminal S6.
13 EF7 External fault (input terminal S7)
14 EF7 External fault at multi-function input terminal S7.

Manual — PID, safety and current alarms — page 285

Source reference: SIEP C71060618F, December 2016, physical PDF page 285. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

FbH. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

FbL. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Hbb. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

HbbF. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

HCA. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

EF1 through EF7 from PDF284 cause/solution continuation | An external device has tripped an alarm function.

EF1 through EF7 from PDF284 cause/solution continuation | Wiring is incorrect.

EF1 through EF7 from PDF284 cause/solution continuation | Multi-function contact inputs are set incorrectly.

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

FbH minor fault/alarm definition | FbH

Fault/error code scope: FbH. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

FbH minor fault/alarm causes and solutions | Parameters settings for b5-36 and b5-37 are incorrect.

FbH minor fault/alarm causes and solutions | PID feedback wiring is faulty.

FbH minor fault/alarm causes and solutions | Feedback sensor has malfunctioned.

FbH minor fault/alarm causes and solutions | Feedback input circuit is damaged.

FbL minor fault/alarm definition | FbL

Fault/error code scope: FbL. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

FbL minor fault/alarm causes and solutions | Parameters settings for b5-13 and b5-14 are incorrect.

FbL minor fault/alarm causes and solutions | PID feedback wiring is faulty.

FbL minor fault/alarm causes and solutions | Feedback sensor has malfunctioned.

FbL minor fault/alarm causes and solutions | Feedback input circuit is damaged.

Hbb minor fault/alarm definition | Hbb

Fault/error code scope: Hbb. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Hbb minor fault/alarm causes and solutions | There is no signal at terminal H1.

Hbb minor fault/alarm causes and solutions | Internally, the Safe Disable channel is broken.

HbbF minor fault/alarm definition | HbbF

Fault/error code scope: HbbF. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

HbbF minor fault/alarm causes and solutions | One of the Safe Disable channels is faulty.

HCA minor fault/alarm definition | HCA

EF1 through EF7 from PDF284 cause/solution continuation — PDF page 285

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 An external device has tripped an alarm function. Remove the cause of the external fault and reset the multi-function input value. YES
2 Wiring is incorrect. • Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1-□□ = 20 to 2F). • Reconnect the signal line. YES
3 Multi-function contact inputs are set incorrectly. • Check if the unused terminals have been set for H1-□□ = 20 to 2F (External Fault). • Change the terminal settings. YES

FbH minor fault/alarm definition — PDF page 285

Source row Literal display code Name or definition
1 FbH Excessive PID Feedback
2 FbH The PID feedback input is higher than the level set in b5-36 for longer than the time set in b5-37, and b5-12 is set to 1 or 4.

FbH minor fault/alarm causes and solutions — PDF page 285

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Parameters settings for b5-36 and b5-37 are incorrect. Check parameters b5-36 and b5-37. YES
2 PID feedback wiring is faulty. Correct the wiring. YES
3 Feedback sensor has malfunctioned. Check the sensor and replace it if damaged. YES
4 Feedback input circuit is damaged. Replace the drive. YES

FbL minor fault/alarm definition — PDF page 285

Source row Literal display code Name or definition
1 FbL PID Feedback Loss
2 FbL The PID feedback input is lower than the level set in b5-13 for longer than the time set in b5-14, and b5-12 is set to 1 or 4.

FbL minor fault/alarm causes and solutions — PDF page 285

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Parameters settings for b5-13 and b5-14 are incorrect. Check parameters b5-13 and b5-14. YES
2 PID feedback wiring is faulty. Correct the wiring. YES
3 Feedback sensor has malfunctioned. Check the sensor and replace it if damaged. YES
4 Feedback input circuit is damaged. Replace the drive. YES

Hbb minor fault/alarm definition — PDF page 285

Source row Literal display code Name or definition
1 Hbb Safe Disable Signal Input
2 Hbb The Safe Disable Input channel is open.

Hbb minor fault/alarm causes and solutions — PDF page 285

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 There is no signal at terminal H1. Check if external safety circuit tripped and disabled the drive. If the Safe Disable function is not utilized, check if the terminals HC, H1, and H2 are linked. YES
2 Internally, the Safe Disable channel is broken. Replace the drive. YES

HbbF minor fault/alarm definition — PDF page 285

Source row Literal display code Name or definition
1 HbbF Safe Disable Signal Input
2 HbbF The safe disable input hardware is defective.

HbbF minor fault/alarm causes and solutions — PDF page 285

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 One of the Safe Disable channels is faulty. Replace the drive. YES

HCA minor fault/alarm definition — PDF page 285

Source row Literal display code Name or definition
1 HCA Current Alarm
2 HCA Drive current exceeded overcurrent warning level (150% of the rated current).

Manual — Maintenance and heatsink alarms — page 286

Source reference: SIEP C71060618F, December 2016, physical PDF page 286. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

LT-1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

LT-2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

LT-3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

LT-4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oH. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

HCA from PDF285 cause/solution continuation | Load is too heavy.

HCA from PDF285 cause/solution continuation | Acceleration and deceleration times are too short.

HCA from PDF285 cause/solution continuation | A special-purpose motor is being used, or the drive is attempting to run a motor greater than the maximum allowable capacity.

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

LT-1 minor fault/alarm definition | LT-1

Fault/error code scope: LT-1. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

LT-1 minor fault/alarm causes and solutions | The cooling fan has reached 90% of its expected performance life.

LT-2 minor fault/alarm definition | LT-2

Fault/error code scope: LT-2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

LT-2 minor fault/alarm causes and solutions | The main circuit and control circuit capacitors have reached 90% of their expected performance life.

LT-3 minor fault/alarm definition | LT-3

Fault/error code scope: LT-3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

LT-3 minor fault/alarm causes and solutions | The DC bus soft charge relay has reached 90% of their expected performance life.

LT-4 minor fault/alarm definition | LT-4

Fault/error code scope: LT-4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

LT-4 minor fault/alarm causes and solutions | IGBTs have reached 50% of their expected performance life.

oH minor fault/alarm definition | oH

HCA from PDF285 cause/solution continuation — PDF page 286

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Load is too heavy. • Measure the current flowing through the motor. • Reduce the load or increase the capacity of the drive. YES
2 Acceleration and deceleration times are too short. • Calculate the torque required during acceleration and for the inertia moment. • If the torque level is not right for the load, take the following steps: • Increase the acceleration and deceleration times (C1-01 through C1-08). • Increase the capacity of the drive. YES
3 A special-purpose motor is being used, or the drive is attempting to run a motor greater than the maximum allowable capacity. • Check the motor capacity. • Use a motor appropriate for the drive. Ensure the motor is within the allowable capacity range. YES

LT-1 minor fault/alarm definition — PDF page 286

Source row Literal display code Name or definition
1 LT-1 Cooling Fan Maintenance Time
2 LT-1 The cooling fan has reached its expected maintenance period and may need to be replaced. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F.

LT-1 minor fault/alarm causes and solutions — PDF page 286

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 The cooling fan has reached 90% of its expected performance life. Replace the cooling fan and reset the Maintenance Monitor by setting o4-03 to 0. –

LT-2 minor fault/alarm definition — PDF page 286

Source row Literal display code Name or definition
1 LT-2 Capacitor Maintenance Time
2 LT-2 The main circuit and control circuit capacitors are nearing the end of their expected performance life. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F.

LT-2 minor fault/alarm causes and solutions — PDF page 286

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 The main circuit and control circuit capacitors have reached 90% of their expected performance life. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. –

LT-3 minor fault/alarm definition — PDF page 286

Source row Literal display code Name or definition
1 LT-3 Soft Charge Bypass Relay Maintenance Time
2 LT-3 The DC bus soft charge relay is nearing the end of its expected performance life. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F.

LT-3 minor fault/alarm causes and solutions — PDF page 286

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 The DC bus soft charge relay has reached 90% of their expected performance life. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. –

LT-4 minor fault/alarm definition — PDF page 286

Source row Literal display code Name or definition
1 LT-4 IGBT Maintenance Time (50%)
2 LT-4 IGBTs have reached 50% of their expected performance life. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F.

LT-4 minor fault/alarm causes and solutions — PDF page 286

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 IGBTs have reached 50% of their expected performance life. Check the load, carrier frequency, and output frequency. –

oH minor fault/alarm definition — PDF page 286

Source row Literal display code Name or definition
1 oH Heatsink Overheat
2 oH The temperature exceeded the value set to L8-02.

Manual — Heat and overtorque alarms — page 287

Source reference: SIEP C71060618F, December 2016, physical PDF page 287. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oH2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oH3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

oH from PDF286 cause/solution continuation | Surrounding temperature is too high

oH from PDF286 cause/solution continuation | Internal cooling fan has stopped.

oH from PDF286 cause/solution continuation | Airflow around the drive is restricted.

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

oH2 minor fault/alarm definition | oH2

Fault/error code scope: oH2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oH2 minor fault/alarm causes and solutions | An external device triggered and overheat warning in the drive.

oH3 minor fault/alarm definition | oH3

Fault/error code scope: oH3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oH3 minor fault/alarm causes and solutions | Motor thermostat wiring is fault (PTC input).

oH3 minor fault/alarm causes and solutions | There is a fault on the machine side (e.g., the machine is locked up).

oH3 minor fault/alarm causes and solutions | Motor has overheated.

oL3 minor fault/alarm definition | oL3

Fault/error code scope: oL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oL3 minor fault/alarm causes and solutions | Inappropriate parameter settings.

oL3 minor fault/alarm causes and solutions | There is a fault on the machine side (e.g., the machine is locked up).

oL4 minor fault/alarm definition | oL4

oH from PDF286 cause/solution continuation — PDF page 287

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Surrounding temperature is too high • Check the surrounding temperature. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool surrounding area. • Remove anything near drive that may cause extra heat. YES
2 Internal cooling fan has stopped. • Replace the cooling fan. Refer to Cooling Fan Replacement on page 317. • After replacing the fan, reset the cooling fan maintenance parameter to (o4-03 = “0”). YES
3 Airflow around the drive is restricted. • Provide proper installation space around the drive as indicated in the manual. Refer to Correct Installation Orientation on page 38. • Allow for the specified space and ensure that there is sufficient circulation around the control panel. YES
4 Airflow around the drive is restricted. • Check for dust or foreign materials clogging cooling fan. • Clear debris caught in the fan that restricts air circulation. YES

oH2 minor fault/alarm definition — PDF page 287

Source row Literal display code Name or definition
1 oH2 Drive Overheat Warning
2 oH2 “Drive Overheat Warning” was input to a multi-function input terminal, S1 through S7 (H1-□□= B)

oH2 minor fault/alarm causes and solutions — PDF page 287

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 An external device triggered and overheat warning in the drive. • Search for the device that tripped the overheat warning. • Solving the problem will clear the warning. YES

oH3 minor fault/alarm definition — PDF page 287

Source row Literal display code Name or definition
1 oH3 Motor Overheat
2 oH3 The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02 or H3-10 = E).

oH3 minor fault/alarm causes and solutions — PDF page 287

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Motor thermostat wiring is fault (PTC input). Repair the PTC input wiring. YES
2 There is a fault on the machine side (e.g., the machine is locked up). • Check the status of the machine. • Remove the cause of the fault. YES
3 Motor has overheated. • Check the load size, accel/decel times, and cycle times. • Decrease the load. • Increase accel and decel times (C1-01 to C1-08). • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. Note: Do not lower E1-08 and E1-10 excessively, because this reduces load tolerance at low speeds. • Check the motor-rated current. • Enter motor-rated current on motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system. YES

oL3 minor fault/alarm definition — PDF page 287

Source row Literal display code Name or definition
1 oL3 Overtorque 1
2 oL3 Drive output current (or torque in OLV) was greater than L6-02 for longer than the time set in L6-03.

oL3 minor fault/alarm causes and solutions — PDF page 287

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Inappropriate parameter settings. Check parameters L6-02 and L6-03. YES
2 There is a fault on the machine side (e.g., the machine is locked up). • Check the status of the machine. • Remove the cause of the fault. YES

oL4 minor fault/alarm definition — PDF page 287

Source row Literal display code Name or definition
1 oL4 Overtorque 2
2 oL4 Drive output current (or torque in OLV) was greater than L6-05 for longer than the time set in L6-06.

Manual — Overtorque, overspeed and voltage alarms — page 288

Source reference: SIEP C71060618F, December 2016, physical PDF page 288. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

ov. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

PASS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

PGo. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

oL4 from PDF287 cause/solution continuation | Parameter settings are not appropriate.

oL4 from PDF287 cause/solution continuation | There is a fault on the machine side (e.g., the machine is locked up).

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

oL5 minor fault/alarm definition | oL5

Fault/error code scope: oL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oL5 minor fault/alarm causes and solutions | Overtorque occurred, triggering the mechanical weakening level set to L6-08.

oS minor fault/alarm definition | oS

Fault/error code scope: oS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oS minor fault/alarm causes and solutions | Overshoot or undershoot is occurring.

oS minor fault/alarm causes and solutions | PG pulse settings are incorrect.

oS minor fault/alarm causes and solutions | Parameter settings are inappropriate.

ov minor fault/alarm definition | ov

Fault/error code scope: ov. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

ov minor fault/alarm causes and solutions | Surge voltage present in the drive input power.

ov minor fault/alarm causes and solutions | • The motor is short-circuited. • Ground current has over-charged the main circuit capacitors via the drive input power.

ov minor fault/alarm causes and solutions | Noise interference causes the drive to operate incorrectly.

PASS minor fault/alarm definition | PASS

Fault/error code scope: PASS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

PASS minor fault/alarm causes and solutions | MEMOBUS/Modbus test has finished normally.

PGo minor fault/alarm definition | PGo

oL4 from PDF287 cause/solution continuation — PDF page 288

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Parameter settings are not appropriate. Check parameters L6-05 and L6-06. YES
2 There is a fault on the machine side (e.g., the machine is locked up). • Check the status of the machine being used. • Remove the cause of the fault. YES

oL5 minor fault/alarm definition — PDF page 288

Source row Literal display code Name or definition
1 oL5 Mechanical Weakening Detection 1
2 oL5 Overtorque occurred, matching the conditions specified in L6-08.

oL5 minor fault/alarm causes and solutions — PDF page 288

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Overtorque occurred, triggering the mechanical weakening level set to L6-08. Check for the cause of mechanical weakening. YES

oS minor fault/alarm definition — PDF page 288

Source row Literal display code Name or definition
1 oS Overspeed (for Simple V/f with PG)
2 oS Pulse input (RP) indicates that motor speed feedback exceeded F1-08 setting.

oS minor fault/alarm causes and solutions — PDF page 288

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Overshoot or undershoot is occurring. • Adjust the gain by using the pulse train input parameters (H6-02 through H6-05). • Adjust the speed feedback accuracy. • Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1). YES
2 PG pulse settings are incorrect. Set the H6-02 (Pulse Train Input Scaling) to the frequency of PG pulses at maximum motor speed. YES
3 Parameter settings are inappropriate. Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09). YES

ov minor fault/alarm definition — PDF page 288

Source row Literal display code Name or definition
1 ov DC Bus Overvoltage
2 ov The DC bus voltage exceeded the trip point. For 200 V class: approximately 410 V For 400 V class: approximately 820 V (740 V when E1-01 < 400)

ov minor fault/alarm causes and solutions — PDF page 288

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Surge voltage present in the drive input power. • Install an AC reactor or DC link choke. • Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on the same drive input power system. YES
2 • The motor is short-circuited. • Ground current has over-charged the main circuit capacitors via the drive input power. • Check the motor power cable, relay terminals and motor terminal box for short circuits. • Correct grounding shorts and turn the power back on. YES
3 Noise interference causes the drive to operate incorrectly. • Review possible solutions for handling noise interference. • Review section on handling noise interference and check control circuit lines, main circuit lines and ground wiring. • If the magnetic contactor is identified as a source of noise, install a surge protector to the MC coil. YES
4 Noise interference causes the drive to operate incorrectly. Set number of fault restarts (L5-01) to a value other than 0. YES

PASS minor fault/alarm definition — PDF page 288

Source row Literal display code Name or definition
1 PASS MEMOBUS/Modbus Comm. Test Mode Complete

PASS minor fault/alarm causes and solutions — PDF page 288

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 MEMOBUS/Modbus test has finished normally. This verifies that the test was successful. No output

PGo minor fault/alarm definition — PDF page 288

Source row Literal display code Name or definition
1 PGo PG Disconnect (for Simple V/f with PG)
2 PGo Detected when no PG pulses received for a time longer than setting in F1-14.

Manual — PG, switch, maintenance and undertorque alarms — page 289

Source reference: SIEP C71060618F, December 2016, physical PDF page 289. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

rUn. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

SE. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

TrPC. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

UL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

UL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

UL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

PGo from PDF288 cause/solution continuation | Pulse input (RP) is disconnected.

PGo from PDF288 cause/solution continuation | Pulse input (RP) wiring is wrong.

PGo from PDF288 cause/solution continuation | Motor brake is engaged.

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

rUn minor fault/alarm definition | rUn

Fault/error code scope: rUn. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

rUn minor fault/alarm causes and solutions | A motor switch command was entered during run.

SE minor fault/alarm definition | SE

Fault/error code scope: SE. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

SE minor fault/alarm causes and solutions | A digital input programmed to 67H (MEMOBUS/Modbus test) was closed while the drive was running.

TrPC minor fault/alarm definition | TrPC

Fault/error code scope: TrPC. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

TrPC minor fault/alarm causes and solutions | IGBTs have reached 90% of their expected performance life.

UL3 minor fault/alarm definition | UL3

Fault/error code scope: UL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

UL3 minor fault/alarm causes and solutions | Inappropriate parameter settings.

UL3 minor fault/alarm causes and solutions | Load has dropped or decreased significantly.

UL4 minor fault/alarm definition | UL4

Fault/error code scope: UL4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

UL4 minor fault/alarm causes and solutions | Inappropriate parameter settings.

UL4 minor fault/alarm causes and solutions | The load has dropped or decreased significantly.

UL5 minor fault/alarm definition | UL5

Fault/error code scope: UL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

UL5 minor fault/alarm causes and solutions | Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08).

PGo from PDF288 cause/solution continuation — PDF page 289

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Pulse input (RP) is disconnected. Reconnect the pulse input (RP). YES
2 Pulse input (RP) wiring is wrong. Correct the wiring. YES
3 Motor brake is engaged. Ensure the brake releases properly YES

rUn minor fault/alarm definition — PDF page 289

Source row Literal display code Name or definition
1 rUn Motor Switch during Run
2 rUn A command to switch motors was entered during run.

rUn minor fault/alarm causes and solutions — PDF page 289

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 A motor switch command was entered during run. Change the operation pattern so that the motor switch command is entered while the drive is stopped. YES

SE minor fault/alarm definition — PDF page 289

Source row Literal display code Name or definition
1 SE MEMOBUS/Modbus Communication Test Mode Error

SE minor fault/alarm causes and solutions — PDF page 289

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 A digital input programmed to 67H (MEMOBUS/Modbus test) was closed while the drive was running. Stop the drive and run the test again. No output

TrPC minor fault/alarm definition — PDF page 289

Source row Literal display code Name or definition
1 TrPC IGBT Maintenance Time (90%)
2 TrPC IGBTs have reached 90% of their expected performance life.

TrPC minor fault/alarm causes and solutions — PDF page 289

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 IGBTs have reached 90% of their expected performance life. Replace the drive. YES

UL3 minor fault/alarm definition — PDF page 289

Source row Literal display code Name or definition
1 UL3 Undertorque Detection 1
2 UL3 Drive output current (or torque in OLV) less than L6-02 for longer than L6-03 time.

UL3 minor fault/alarm causes and solutions — PDF page 289

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Inappropriate parameter settings. Check parameters L6-02 and L6-03. YES
2 Load has dropped or decreased significantly. Check for broken parts in the transmission system. YES

UL4 minor fault/alarm definition — PDF page 289

Source row Literal display code Name or definition
1 UL4 Undertorque Detection 2
2 UL4 Drive output current (or torque in OLV) less than L6-05 for longer than L6-06 time.

UL4 minor fault/alarm causes and solutions — PDF page 289

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Inappropriate parameter settings. Check parameters L6-05 and L6-06. YES
2 The load has dropped or decreased significantly. Check for broken parts in the transmission system. YES

UL5 minor fault/alarm definition — PDF page 289

Source row Literal display code Name or definition
1 UL5 Mechanical Weakening Detection 2
2 UL5 The operation conditions matched the conditions set to L6-08.

UL5 minor fault/alarm causes and solutions — PDF page 289

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08). Check the load side for any problems. YES

Manual — Undervoltage alarm — page 290

Source reference: SIEP C71060618F, December 2016, physical PDF page 290. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Uv. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Minor Fault Name

Minor Fault Cause Possible Solution (H2-□□ = 10)

6.5 Alarm Detection

Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.

Uv minor fault/alarm definition | Uv

Fault/error code scope: Uv. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Uv minor fault/alarm causes and solutions | Phase loss in the drive input power.

Uv minor fault/alarm causes and solutions | Loose wiring in the drive input power terminals.

Uv minor fault/alarm causes and solutions | There is a problem with the drive input power voltage.

Uv minor fault/alarm causes and solutions | Drive internal circuitry is worn.

Uv minor fault/alarm causes and solutions | The drive input power transformer is not large enough and voltage drops when the power is switched on.

Uv minor fault/alarm causes and solutions | Air inside the drive is too hot.

Uv minor fault/alarm causes and solutions | The CHARGE indicator light is broken or disconnected.

Uv minor fault/alarm definition — PDF page 290

Source row Literal display code Name or definition
1 Uv Undervoltage
2 Uv One of the following conditions was true when the drive was stopped and a run command was entered: • DC bus voltage dropped below the level specified in L2-05. • Contactor to suppress inrush current in the drive was open. • Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage is under L2-05.

Uv minor fault/alarm causes and solutions — PDF page 290

Source row Cause Possible solution Minor fault output (H2-□□=10)
1 Phase loss in the drive input power. Check for wiring errors in the main circuit drive input power. Correct the wiring. YES
2 Loose wiring in the drive input power terminals. • Ensure the terminals have been properly tightened. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torques on page 58. YES
3 There is a problem with the drive input power voltage. • Check the voltage. • Lower the voltage of the drive input power so that it is within the limits listed in the specifications. YES
4 Drive internal circuitry is worn. • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 exceeds 90%. YES
5 The drive input power transformer is not large enough and voltage drops when the power is switched on. • Check for a tripped alarm when the magnetic contactor, line breaker and leakage breaker are turned on. • Check the capacity of the drive input power transformer. YES
6 Air inside the drive is too hot. • Check the temperature inside the drive. YES
7 The CHARGE indicator light is broken or disconnected. • Replace the drive. YES

Manual — Operation errors and input conflicts — page 291

Source reference: SIEP C71060618F, December 2016, physical PDF page 291. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oPE01. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oPE02. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oPE03. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

6.6 Operator Programming Errors

An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter setting is inappropriate. The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPE occurs, investigate the cause and Refer to oPE Codes, Causes, and Possible Solutions on page 291 for the appropriate action. When an oPE error is displayed, press the ENTER button to display U1-18 (oPE fault constant). This monitor displays the parameter causing the oPE error.

u oPE Codes, Causes, and Possible Solutions

Table 6.11 Detailed oPE Codes, Causes, and Possible Solutions

Digital Operator Display Error Name

Cause Possible Solution

Digital Operator Display Fault Name

Note: Other errors are given precedence over oPE02 when multiple errors occur at the same time.

Troubleshooting

Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.

oPE01 operator error definition | oPE01

Fault/error code scope: oPE01. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE01 operator error causes and solutions | The drive capacity setting (o2-04) and the actual capacity of the drive are not the same.

oPE02 operator error definition | oPE02

Fault/error code scope: oPE02. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE02 operator error causes and solutions | Parameters were set outside the possible setting range.

oPE03 operator error definition | oPE03

Fault/error code scope: oPE03. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE03 operator error causes and solutions | • The same function is assigned to two multi-function inputs. • Excludes “Not used” and “External Fault.”

oPE03 operator error causes and solutions | The Up command was set but the Down command was not, or vice versa (settings 10 vs. 11).

oPE03 operator error causes and solutions | The Up 2 command was set but the Down 2 command was not, or vice versa (settings 75 vs. 76).

oPE03 operator error causes and solutions | • Run/Stop command for a 2-Wire sequence 2 was set (H1-oo = 42), but forward/ reverse command (H1-oo = 43) was not. • “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A).

oPE03 operator error causes and solutions | • Run/Stop command for a 2-Wire sequence 2 was set (H1-□□ = 42), but forward/ reverse command (H1-□□ = 43) was not. • “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A).

oPE03 operator error causes and solutions | Two of the following functions are set at the same time: • Up/Down Command (10 vs. 11) • Up 2/Down 2 Command (75 vs. 76) • Hold Accel/Decel Stop (A) • Analog Frequency Reference Sample/Hold (1E) • Offset Frequency 1, 2, 3 Calculations (44, 45, 46)

oPE03 operator error causes and solutions | The Up/Down command (10, 11) is enabled at the same time as PID control (b5-01).

oPE01 operator error definition — PDF page 291

Source row Literal display code Name or definition
1 oPE01 Drive Capacity Setting Fault
2 oPE01 Drive capacity and the value set to o2-04 do not match.

oPE01 operator error causes and solutions — PDF page 291

Source row Cause Possible solution
1 The drive capacity setting (o2-04) and the actual capacity of the drive are not the same. Correct the value set to o2-04.

oPE02 operator error definition — PDF page 291

Source row Literal display code Name or definition
1 oPE02 Parameter Range Setting Error
2 oPE02 Use U1-18 to find parameters set outside the range.

oPE02 operator error causes and solutions — PDF page 291

Source row Cause Possible solution
1 Parameters were set outside the possible setting range. Set parameters to the proper values.

oPE03 operator error definition — PDF page 291

Source row Literal display code Name or definition
1 oPE03 Multi-Function Input Selection Error
2 oPE03 A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-07.

oPE03 operator error causes and solutions — PDF page 291

Source row Cause Possible solution
1 • The same function is assigned to two multi-function inputs. • Excludes “Not used” and “External Fault.” • Ensure all multi-function inputs are assigned to different functions. • Re-enter the multi-function settings to ensure this does not occur.
2 The Up command was set but the Down command was not, or vice versa (settings 10 vs. 11). Correctly set functions that need to be enabled in combination with other functions.
3 The Up 2 command was set but the Down 2 command was not, or vice versa (settings 75 vs. 76). Correctly set functions that need to be enabled in combination with other functions.
4 • Run/Stop command for a 2-Wire sequence 2 was set (H1-□□ = 42), but forward/ reverse command (H1-□□ = 43) was not. • “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A). Correctly set functions that need to be enabled in combination with other functions.
5 Two of the following functions are set at the same time: • Up/Down Command (10 vs. 11) • Up 2/Down 2 Command (75 vs. 76) • Hold Accel/Decel Stop (A) • Analog Frequency Reference Sample/Hold (1E) • Offset Frequency 1, 2, 3 Calculations (44, 45, 46) • Check if contradictory settings have been assigned to the multi-function input terminals at the same time. • Correct setting errors.
6 The Up/Down command (10, 11) is enabled at the same time as PID control (b5-01). Set b5-01 to 0 to disable PID control or disable the Up/Down command.

Manual — Input conflicts and initialization errors — page 292

Source reference: SIEP C71060618F, December 2016, physical PDF page 292. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oPE04. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oPE05. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oPE07. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.6 Operator Programming Errors

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

oPE03 from PDF291 cause/solution continuation | Settings for NC and NO input for the following functions were selected at the same time: • External Search Command 1 and External Search Command 2 (61 vs. 62) • Fast-Stop N.O. and Fast-Stop N.C. (15 vs. 17) • KEB for Momentary Power Loss and High Slip Braking (65, 66, 7A, 7B vs. 68) • Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A) • KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B) • FWD Run Command (or REV) and FWD/ REV Run Command (2-wire) (40, 41 vs. 42, 43) • External DB Command and Drive Enable (60 vs. 6A) • Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76)

oPE03 from PDF291 cause/solution continuation | One of the following settings was entered while H1-oo = 2 (External Reference 1/2): • b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train Input Function Selection) not = 0 (Frequency Reference) • b1-15 or b1-16 set to 3 but no option card connected • Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias).

oPE03 from PDF291 cause/solution continuation | One of the following settings was entered while H1-□□ = 2 (External Reference 1/2): • b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train Input Function Selection) not = 0 (Frequency Reference) • b1-15 or b1-16 set to 3 but no option card connected • Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias).

oPE03 from PDF291 cause/solution continuation | H2-oo = 38 (Drive Enabled) but H1-oo is not set to 6A (Drive Enable).

oPE03 from PDF291 cause/solution continuation | H2-□□ = 38 (Drive Enabled) but H1-□□ is not set to 6A (Drive Enable).

oPE03 from PDF291 cause/solution continuation | H1-oo = 7E (Direction Detection) although H6-01 is not set to 3 (Simple V/f with PG).

oPE03 from PDF291 cause/solution continuation | H1-□□ = 7E (Direction Detection) although H6-01 is not set to 3 (Simple V/f with PG).

Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.

oPE04 operator error definition | oPE04

Fault/error code scope: oPE04. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE04 operator error causes and solutions | The drive, control board, or terminal board has been replaced and the parameter settings between the control board and the terminal board no longer match.

oPE05 operator error definition | oPE05

Fault/error code scope: oPE05. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE05 operator error causes and solutions | Frequency reference is assigned to an option card (b1-01 = 3) that is not connected to the drive.

oPE05 operator error causes and solutions | The Run command is assigned to an option card (b1-02 = 3) that is not connected to the drive.

oPE05 operator error causes and solutions | Frequency reference is assigned to the pulse train input (b1-01 = 4), but terminal RP is not set for pulse train input (H6-01 > 0)

oPE07 operator error definition | oPE07

oPE03 from PDF291 cause/solution continuation — PDF page 292

Source row Cause Possible solution
1 Settings for NC and NO input for the following functions were selected at the same time: • External Search Command 1 and External Search Command 2 (61 vs. 62) • Fast-Stop N.O. and Fast-Stop N.C. (15 vs. 17) • KEB for Momentary Power Loss and High Slip Braking (65, 66, 7A, 7B vs. 68) • Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A) • KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B) • FWD Run Command (or REV) and FWD/ REV Run Command (2-wire) (40, 41 vs. 42, 43) • External DB Command and Drive Enable (60 vs. 6A) • Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76) Check for contradictory settings assigned to the multi-function input terminals at the same time. Correct setting errors.
2 One of the following settings was entered while H1-□□ = 2 (External Reference 1/2): • b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train Input Function Selection) not = 0 (Frequency Reference) • b1-15 or b1-16 set to 3 but no option card connected • Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias). Correct the settings for the multi-function input terminal parameters.
3 H2-□□ = 38 (Drive Enabled) but H1-□□ is not set to 6A (Drive Enable). Correct the settings for the multi-function input terminal parameters.
4 H1-□□ = 7E (Direction Detection) although H6-01 is not set to 3 (Simple V/f with PG). Correct the settings for the multi-function input terminal parameters.

oPE04 operator error definition — PDF page 292

Source row Literal display code Name or definition
1 oPE04 Initialization required.

oPE04 operator error causes and solutions — PDF page 292

Source row Cause Possible solution
1 The drive, control board, or terminal board has been replaced and the parameter settings between the control board and the terminal board no longer match. To load the parameter settings to the drive that are stored in the terminal board, set A1-03 to 5550. Initialize parameters after drive replacement by setting A1-03 to 1110 or 2220.

oPE05 operator error definition — PDF page 292

Source row Literal display code Name or definition
1 oPE05 Run Command/Frequency Reference Source Selection Error

oPE05 operator error causes and solutions — PDF page 292

Source row Cause Possible solution
1 Frequency reference is assigned to an option card (b1-01 = 3) that is not connected to the drive. Reconnect the option card to the drive.
2 The Run command is assigned to an option card (b1-02 = 3) that is not connected to the drive. Reconnect the option card to the drive.
3 Frequency reference is assigned to the pulse train input (b1-01 = 4), but terminal RP is not set for pulse train input (H6-01 > 0) Set H6-01 to 0.

oPE07 operator error definition — PDF page 292

Source row Literal display code Name or definition
1 oPE07 Multi-Function Analog Input Selection Error
2 oPE07 A contradictory setting is assigned to multi-function analog inputs H3-02 through to H3-10 and PID functions conflict.

Manual — Analog, mode and PID errors — page 293

Source reference: SIEP C71060618F, December 2016, physical PDF page 293. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oPE08. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oPE09. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

Note: Use U1-18 to find parameters set outside of the specified setting range. Other errors are given precedence over oPE08 when multiple errors occur simultaneously.

6.6 Operator Programming Errors

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

oPE07 from PDF292 cause/solution continuation | H3-02 and H3-10 are set to the same value.

oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H3-02 or H3-10 = B (PID Feedback) H6-01 (Pulse Train Input) = 1 (PID Feedback)

oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) H6-01 = 2 (pulse train input sets the PID target value)

oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value)

oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H6-01 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value)

Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.

oPE08 operator error definition | oPE08

Fault/error code scope: oPE08. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE08 operator error causes and solutions | Attempted to use a function in the V/f motor control method that is only possible in Open Loop Vector Control.

oPE08 operator error causes and solutions | Simple V/f with PG was enabled while not in V/f Control (H6-01 = 3).

oPE08 operator error causes and solutions | In Open Loop Vector Control, n2-02 is greater than n2-03

oPE08 operator error causes and solutions | In Open Loop Vector Control, C4-02 is greater than C4-06

oPE08 operator error causes and solutions | In OLV/PMl, parameters E5-02 to E5-07 are set to 0.

oPE08 operator error causes and solutions | The following conditions are true in PM Open Loop Vector Control: • E5-03 does not equal 0 • E5-09 and E5-24 are both equal to 0, or neither equals 0

oPE09 operator error definition | oPE09

Fault/error code scope: oPE09. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE09 operator error causes and solutions | The following simultaneous contradictory settings: • b5-15 not 0.0 (PID Sleep Function Operation Level) • The stopping method is set to either DC injection braking or coast to stop with a timer (b1-03 = 2 or 3).

oPE09 operator error causes and solutions | • D control is being used on the setpoint deviation (b5-01 = 1) or on the feedback value (b5-01 = 2). • A negative PID output value is set to operate the drive in reverse (b5-11 = 1) and the frequency reference lower limit greater than 0 (d2-02 > 0).

oPE07 from PDF292 cause/solution continuation — PDF page 293

Source row Cause Possible solution
1 H3-02 and H3-10 are set to the same value. Change the settings to H3-02 and H3-10 so that functions no longer conflict. Note: Both 0 (primary analog frequency reference) and F (Not Used) can be set to H3-02 and H3-10 at the same time.
2 The following simultaneous contradictory settings: H3-02 or H3-10 = B (PID Feedback) H6-01 (Pulse Train Input) = 1 (PID Feedback) Disable one of the PID selections.
3 The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) H6-01 = 2 (pulse train input sets the PID target value) Disable one of the PID selections.
4 The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value) Disable one of the PID selections.
5 The following simultaneous contradictory settings: H6-01 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value) Disable one of the PID selections.

oPE08 operator error definition — PDF page 293

Source row Literal display code Name or definition
1 oPE08 Parameter Selection Error
2 oPE08 A function has been set that cannot be used in the motor control method selected.

oPE08 operator error causes and solutions — PDF page 293

Source row Cause Possible solution
1 Attempted to use a function in the V/f motor control method that is only possible in Open Loop Vector Control. Check the motor control method and the functions available.
2 Simple V/f with PG was enabled while not in V/f Control (H6-01 = 3). To use Simple V/f with PG, ensure the motor control method has been set to V/f Control (A1-02 = 0).
3 In Open Loop Vector Control, n2-02 is greater than n2-03 Correct parameter settings so that n2-02 is less than n2-03.
4 In Open Loop Vector Control, C4-02 is greater than C4-06 Correct parameter settings so that C4-02 is less than C4-06.
5 In OLV/PMl, parameters E5-02 to E5-07 are set to 0. • Set the correct motor code in accordance with the motor being used (E5-01). • When using a special-purpose motor, set E5-□□ in accordance with the Test Report provided.
6 The following conditions are true in PM Open Loop Vector Control: • E5-03 does not equal 0 • E5-09 and E5-24 are both equal to 0, or neither equals 0 • Set E5-09 or E5-24 to the correct value, and set the other to “0”. • Set the motor-rated current for PM to “0” (E5-03).

oPE09 operator error definition — PDF page 293

Source row Literal display code Name or definition
1 oPE09 PID Control Selection Fault
2 oPE09 PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 to 4).

oPE09 operator error causes and solutions — PDF page 293

Source row Cause Possible solution
1 The following simultaneous contradictory settings: • b5-15 not 0.0 (PID Sleep Function Operation Level) • The stopping method is set to either DC injection braking or coast to stop with a timer (b1-03 = 2 or 3). • Set b5-15 to a value other than 0. • Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
2 • D control is being used on the setpoint deviation (b5-01 = 1) or on the feedback value (b5-01 = 2). • A negative PID output value is set to operate the drive in reverse (b5-11 = 1) and the frequency reference lower limit greater than 0 (d2-02 > 0). Set parameters b5-01, b5-11, and d2-02 to the proper values.

Manual — PID, V/f, carrier and pulse errors — page 294

Source reference: SIEP C71060618F, December 2016, physical PDF page 294. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

oPE10. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oPE11. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

oPE13. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.6 Operator Programming Errors

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

oPE09 from PDF293 cause/solution continuation | • D control is being used on the setpoint deviation and the frequency reference plus the PID output (b5-01 = 4), D control is being used on the feedback value and the frequency reference plus the PID output (b5-01 = 4). • The frequency reference lower limit is set to a value greater than 0 (d2-02 > 0).

oPE09 from PDF293 cause/solution continuation | The absolute value of the lower limit for PID output is greater than the PID upper limit (b5-34 > b5-06).

Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.

oPE10 operator error definition | oPE10

Fault/error code scope: oPE10. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE10 operator error causes and solutions | V/f pattern setting error.

oPE11 operator error definition | oPE11

Fault/error code scope: oPE11. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE11 operator error causes and solutions | The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is less than or equal to 6, the drive operates at C6-03.

oPE11 operator error causes and solutions | Upper and lower limits between C6-02 and C6-05 contradict each other.

oPE13 operator error definition | oPE13

Fault/error code scope: oPE13. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

oPE13 operator error causes and solutions | Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 000, 031, 101, 102, 105, or 116.

oPE09 from PDF293 cause/solution continuation — PDF page 294

Source row Cause Possible solution
1 • D control is being used on the setpoint deviation and the frequency reference plus the PID output (b5-01 = 4), D control is being used on the feedback value and the frequency reference plus the PID output (b5-01 = 4). • The frequency reference lower limit is set to a value greater than 0 (d2-02 > 0). Set parameters b5-01 and d2-02 to the proper values.
2 The absolute value of the lower limit for PID output is greater than the PID upper limit (b5-34 > b5-06). Set parameters b5-34 and b5-06 to the proper values.

oPE10 operator error definition — PDF page 294

Source row Literal display code Name or definition
1 oPE10 V/f Data Setting Error
2 oPE10 One or more of the parameters listed below are not set according to the formula: • E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 • E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04

oPE10 operator error causes and solutions — PDF page 294

Source row Cause Possible solution
1 V/f pattern setting error. Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11. For motor 2, correct E3-04, E3-06, E3-07, E3-09, and E3-11.

oPE11 operator error definition — PDF page 294

Source row Literal display code Name or definition
1 oPE11 Carrier Frequency Setting Error
2 oPE11 Correct the setting for the carrier frequency.

oPE11 operator error causes and solutions — PDF page 294

Source row Cause Possible solution
1 The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is less than or equal to 6, the drive operates at C6-03. Correct the parameter settings.
2 Upper and lower limits between C6-02 and C6-05 contradict each other. Correct the parameter settings.

oPE13 operator error definition — PDF page 294

Source row Literal display code Name or definition
1 oPE13 Pulse Monitor Selection Error
2 oPE13 Incorrect setting of monitor selection for Pulse Train (H6-06).

oPE13 operator error causes and solutions — PDF page 294

Source row Cause Possible solution
1 Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 000, 031, 101, 102, 105, or 116. Change scaling for the Pulse Train monitor or set H6-06 to 000, 031, 101, 102, 105, or 116.

Manual — Auto-Tuning result and data errors — page 295

Source reference: SIEP C71060618F, December 2016, physical PDF page 295. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

End1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

End2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

End3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-01. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-02. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

6.7 Auto-Tuning Fault Detection

Auto-Tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor coasts to a stop. No fault or alarm outputs will occur

u Auto-Tuning Codes, Causes, and Possible Solutions

Table 6.12 Detailed Auto-Tuning Codes, Causes, and Possible Solutions

Digital Operator Display Error Name

Cause Possible Solution

Digital Operator Display Fault Name

Troubleshooting

Literal source name/definition; code shared only in physical merged source extent. Auto-Tuning error is distinct from other diagnostic categories.

End1 Auto-Tuning error definition | End1

Fault/error code scope: End1. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

End1 Auto-Tuning error causes and solutions | The torque reference exceeded 20% during Auto-Tuning.

End1 Auto-Tuning error causes and solutions | The no-load current exceeded 80% of the drive rated current during Auto-Tuning.

End2 Auto-Tuning error definition | End2

Fault/error code scope: End2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

End2 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.

End2 Auto-Tuning error causes and solutions | Auto-Tuning calculated values outside the parameter setting range, assigning the iron- core saturation coefficient (E2-07, E2-08) a temporary value.

End3 Auto-Tuning error definition | End3

Fault/error code scope: End3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

End3 Auto-Tuning error causes and solutions | • The motor line-to-line resistance and the motor-rated current are not consistent with one another. • The correct current rating printed on the nameplate was not entered into T1-04.

Er-01 Auto-Tuning error definition | Er-01

Fault/error code scope: Er-01. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-01 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.

Er-01 Auto-Tuning error causes and solutions | Motor output and motor-rated current settings (T1-02 and T1-04) do not match.

Er-01 Auto-Tuning error causes and solutions | Motor output and no-load current settings (T1-04 and E2-03) do not match. Data required when Auto-Tuning for OLV Control or Stationary Auto-Tuning.

Er-01 Auto-Tuning error causes and solutions | Base frequency and base motor rotations (T1-05 and T1-07) do not match.

Er-02 Auto-Tuning error definition | Er-02

Fault/error code scope: Er-02. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-02 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.

Er-02 Auto-Tuning error causes and solutions | The wiring is faulty.

Er-02 Auto-Tuning error causes and solutions | Load is too heavy.

End1 Auto-Tuning error definition — PDF page 295

Source row Literal display code Name or definition
1 End1 Excessive V/f Setting. Displayed after Auto-Tuning is complete.

End1 Auto-Tuning error causes and solutions — PDF page 295

Source row Cause Possible solution
1 The torque reference exceeded 20% during Auto-Tuning. • Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter that data to T1-03 through T1-05. • Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning. • If possible, disconnect the motor from the load and perform Auto-Tuning.
2 The no-load current exceeded 80% of the drive rated current during Auto-Tuning. • Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter that data to T1-03 through T1-05. • Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning. • If possible, disconnect the motor from the load and perform Auto-Tuning.

End2 Auto-Tuning error definition — PDF page 295

Source row Literal display code Name or definition
1 End2 Motor Iron-Core Saturation Coefficient. Detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is complete.

End2 Auto-Tuning error causes and solutions — PDF page 295

Source row Cause Possible solution
1 Motor data entered during Auto-Tuning was incorrect. • Enter the correct data. • Restart Auto-Tuning and enter the correct information.
2 Auto-Tuning calculated values outside the parameter setting range, assigning the iron- core saturation coefficient (E2-07, E2-08) a temporary value. • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Rotational Auto-Tuning.

End3 Auto-Tuning error definition — PDF page 295

Source row Literal display code Name or definition
1 End3 Rated Current Setting Alarm (displayed after Auto-Tuning is complete)

End3 Auto-Tuning error causes and solutions — PDF page 295

Source row Cause Possible solution
1 • The motor line-to-line resistance and the motor-rated current are not consistent with one another. • The correct current rating printed on the nameplate was not entered into T1-04. • Check T1-04 setting. • Check the motor data and repeat Auto-Tuning.

Er-01 Auto-Tuning error definition — PDF page 295

Source row Literal display code Name or definition
1 Er-01 Motor Data Error

Er-01 Auto-Tuning error causes and solutions — PDF page 295

Source row Cause Possible solution
1 Motor data entered during Auto-Tuning was incorrect. • Enter the correct data. • Restart Auto-Tuning and enter the correct information.
2 Motor output and motor-rated current settings (T1-02 and T1-04) do not match. • Check the drive and motor capacities. • Correct the settings of parameters T1-02 and T1-04.
3 Motor output and no-load current settings (T1-04 and E2-03) do not match. Data required when Auto-Tuning for OLV Control or Stationary Auto-Tuning. • Check the motor-rated current and no-load current. • Correct the settings of parameters T1-04 and E2-03.
4 Base frequency and base motor rotations (T1-05 and T1-07) do not match. Set T1-05 and T1-07 to the correct values.

Er-02 Auto-Tuning error definition — PDF page 295

Source row Literal display code Name or definition
1 Er-02 Minor Fault

Er-02 Auto-Tuning error causes and solutions — PDF page 295

Source row Cause Possible solution
1 Motor data entered during Auto-Tuning was incorrect. • Enter the correct data. • Restart Auto-Tuning and enter the correct information.
2 The wiring is faulty. • Check the wiring and correct defective connections. • Check around the machine. • Check the load.
3 Load is too heavy. • Check the wiring and correct defective connections. • Check around the machine. • Check the load.

Manual — Auto-Tuning resistance, slip and speed errors — page 296

Source reference: SIEP C71060618F, December 2016, physical PDF page 296. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Er-03. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-04. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-05. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-08. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-09. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-11. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Er-12. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.

Digital Operator Display Fault Name

Cause Possible Solution

6.7 Auto-Tuning Fault Detection

Literal source name/definition; code shared only in physical merged source extent. Auto-Tuning error is distinct from other diagnostic categories.

Er-03 Auto-Tuning error definition | Er-03

Fault/error code scope: Er-03. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-03 Auto-Tuning error causes and solutions | Auto-Tuning canceled by pressing STOP button.

Er-04 Auto-Tuning error definition | Er-04

Fault/error code scope: Er-04. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-04 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.

Er-04 Auto-Tuning error causes and solutions | Auto-Tuning did not complete within designated time frame.

Er-04 Auto-Tuning error causes and solutions | Drive-calculated values outside parameter setting range.

Er-05 Auto-Tuning error definition | Er-05

Fault/error code scope: Er-05. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-05 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.

Er-05 Auto-Tuning error causes and solutions | Auto-Tuning did not complete within designated time frame.

Er-05 Auto-Tuning error causes and solutions | Drive-calculated values outside parameter setting range.

Er-08 Auto-Tuning error definition | Er-08

Fault/error code scope: Er-08. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-08 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.

Er-08 Auto-Tuning error causes and solutions | Auto-Tuning did not complete within designated time frame.

Er-08 Auto-Tuning error causes and solutions | Values calculated by the drive are outside the allowable parameter setting ranges.

Er-09 Auto-Tuning error definition | Er-09

Fault/error code scope: Er-09. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-09 Auto-Tuning error causes and solutions | The motor did not accelerate for the specified acceleration time.

Er-09 Auto-Tuning error causes and solutions | Torque limit when motoring is too low (L7-01 and L7-02).

Er-11 Auto-Tuning error definition | Er-11

Fault/error code scope: Er-11. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-11 Auto-Tuning error causes and solutions | Torque reference is too high. (Enabled in OLV only.)

Er-12 Auto-Tuning error definition | Er-12

Fault/error code scope: Er-12. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.

Er-12 Auto-Tuning error causes and solutions | One of the motor phases is missing (U/T1, V/T2, W/T3).

Er-03 Auto-Tuning error definition — PDF page 296

Source row Literal display code Name or definition
1 Er-03 STOP Button Input

Er-03 Auto-Tuning error causes and solutions — PDF page 296

Source row Cause Possible solution
1 Auto-Tuning canceled by pressing STOP button. Auto-Tuning did not complete properly and will have to be performed again.

Er-04 Auto-Tuning error definition — PDF page 296

Source row Literal display code Name or definition
1 Er-04 Line-to-Line Resistance Error

Er-04 Auto-Tuning error causes and solutions — PDF page 296

Source row Cause Possible solution
1 Motor data entered during Auto-Tuning was incorrect. • Enter the correct data. • Restart Auto-Tuning and enter the correct information.
2 Auto-Tuning did not complete within designated time frame. • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Rotational Auto-Tuning.
3 Drive-calculated values outside parameter setting range. • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Rotational Auto-Tuning.

Er-05 Auto-Tuning error definition — PDF page 296

Source row Literal display code Name or definition
1 Er-05 No-Load Current Error

Er-08 Auto-Tuning error definition — PDF page 296

Source row Literal display code Name or definition
1 Er-08 Rated Slip Error

Er-08 Auto-Tuning error causes and solutions — PDF page 296

Source row Cause Possible solution
1 Motor data entered during Auto-Tuning was incorrect. • Enter the correct data. • Restart Auto-Tuning and enter the correct information.
2 Auto-Tuning did not complete within designated time frame. • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Auto-Tuning.
3 Values calculated by the drive are outside the allowable parameter setting ranges. • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Auto-Tuning.

Er-09 Auto-Tuning error definition — PDF page 296

Source row Literal display code Name or definition
1 Er-09 Acceleration Error (detected only during Rotational Auto-Tuning)

Er-09 Auto-Tuning error causes and solutions — PDF page 296

Source row Cause Possible solution
1 The motor did not accelerate for the specified acceleration time. • Increase the acceleration time (C1-01). • Check if it is possible to disconnect the machine from the motor.
2 Torque limit when motoring is too low (L7-01 and L7-02). • Check the settings of parameters L7-01 and L7-02. • Increase the setting.

Er-11 Auto-Tuning error definition — PDF page 296

Source row Literal display code Name or definition
1 Er-11 Motor Speed Fault (detected only when Auto-Tuning is enabled)

Er-11 Auto-Tuning error causes and solutions — PDF page 296

Source row Cause Possible solution
1 Torque reference is too high. (Enabled in OLV only.) • Increase the acceleration time in C1-01. • Disconnect the machine from the motor, if possible.

Er-12 Auto-Tuning error definition — PDF page 296

Source row Literal display code Name or definition
1 Er-12 Current Detection Error

Er-12 Auto-Tuning error causes and solutions — PDF page 296

Source row Cause Possible solution
1 One of the motor phases is missing (U/T1, V/T2, W/T3). Check motor wiring and correct problems.

Manual — Auto-Tuning current error continuation — page 297

Source reference: SIEP C71060618F, December 2016, physical PDF page 297. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Digital Operator Display Fault Name

6.7 Auto-Tuning Fault Detection

Troubleshooting

Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.

Er-12 from PDF296 cause/solution continuation | Current exceeded the current rating of the drive.

Er-12 from PDF296 cause/solution continuation | The current is too low.

Er-12 from PDF296 cause/solution continuation | Attempted Auto-Tuning without motor connected to the drive.

Er-12 from PDF296 cause/solution continuation | Current detection signal error.

Er-12 from PDF296 cause/solution continuation — PDF page 297

Source row Cause Possible solution
1 Current exceeded the current rating of the drive. • Check the motor wiring for a short between motor lines. • If a magnetic contactor is used between motors, ensure it is on. • Replace the drive.
2 The current is too low. • Check the motor wiring for a short between motor lines. • If a magnetic contactor is used between motors, ensure it is on. • Replace the drive.
3 Attempted Auto-Tuning without motor connected to the drive. Connect the motor and perform Auto-Tuning.
4 Current detection signal error. Replace the drive.

Manual — Fault diagnosis, trace and reset — page 298

Source reference: SIEP C71060618F, December 2016, physical PDF page 298. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

  1. Turn on the drive input power. The first screen displays. Illustration shows F00.00. Source example only; key and operator geometry original-only.

  2. Press [UP] until the monitor screen is displayed. Illustration shows Mon. Source example only; key and operator geometry original-only.

  3. Press [ENTER] to display the parameter setting screen. Illustration shows U1-01. Source example only; key and operator geometry original-only.

  4. Press [UP] and > until U2-02 (Fault History) is displayed. Illustration shows U2-02. Source example only; key and operator geometry original-only.

  5. Press [ENTER] to view most recent fault (here, EF3). Illustration shows F EF3. Source example only; key and operator geometry original-only.

  6. Press [UP] to view drive status information when fault occurred. Source example only; key and operator geometry original-only.

  7. Parameters U2-03 through U2-17 help determine cause of fault. Illustration shows U2-03 to U2-17. Source example only; key and operator geometry original-only.

6.8 Diagnosing and Resetting Faults

When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault, then restart the drive.

u Fault Occurs Simultaneously with Power Loss

WARNING! Electrical Shock Hazard. Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or between the ground and main circuit terminals before restarting the drive. Failure to comply may result in serious injury or death and will cause damage to equipment. 1. Turn on the drive input power. 2. Use monitor parameters U2-□□ to display data on the operating status of the drive just before the fault occurred. 3. Remove the cause of the fault and reset.

Note: To find out what faults were triggered, check U2-02 (Fault History). Information on drive status when the fault occurred such as the frequency, current and voltage, can be found in U2-03 through U2-17. Refer to Viewing Fault Trace Data After Fault on page 298 for information on how to view fault trace data.

Note: When the fault continues to be displayed after cycling power, remove the cause of the fault and reset.

u If the Drive Still has Power After a Fault Occurs 1. Look at the LED operator for information on the fault that occurred. 2. Refer to Fault Displays, Causes, and Possible Solutions on page 267 3. Reset the fault. Refer to Fault Reset Methods on page 298.

u Viewing Fault Trace Data After Fault

Step Display/Result

u Fault Reset Methods

After the Fault Occurs Procedure

Fault reset procedures | Fix the cause of the fault, restart the drive, and reset the fault

Fault reset procedures | Fix the cause of the fault and reset via Fault Reset Digital Input S4.

Fault reset procedures — PDF page 298

Source row Fault condition Procedure Graphic labels
1 Fix the cause of the fault, restart the drive, and reset the fault Press [RESET >] on the digital operator. [RESET >] button and illustrated operator displaying EF3. Example only; device and key geometry original-only.
2 Fix the cause of the fault and reset via Fault Reset Digital Input S4. Close then open the fault signal digital input via terminal S4. S4 is set fault reset as default (H1-04 = 12) Drive; Fault Reset Switch; S4 Fault Reset Digital Input; SC Digital Input Common. Illustration labels only; exact wiring geometry remains original-only.

Manual — Power-cycle reset continuation — page 299

Source reference: SIEP C71060618F, December 2016, physical PDF page 299. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

① OFF then ② ON. Source instruction alongside: reapply power after LED display is out. Switch geometry remains original-only; full electrical safety prerequisites retained.

After the Fault Occurs Procedure

If the above methods do not reset the fault, turn off the drive main power supply. Reapply power after LED operator display is out.

6.8 Diagnosing and Resetting Faults

Troubleshooting

Manual — Parameter access and motor-not-running troubleshooting — page 300

Source reference: SIEP C71060618F, December 2016, physical PDF page 300. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

6.9 Troubleshooting without Fault Display

This section describes troubleshooting problems that do not trip an alarm or fault.

u Cannot Change Parameter Settings

Cause Possible Solutions

u Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External Run Command

n Motor Does Not Rotate

Cannot change parameters | The drive is running the motor (i.e., the Run command is present).

Cannot change parameters | The Access Level is set to restrict access to parameter settings.

Cannot change parameters | The operator is not in the Parameter Setup Mode (the LED screen will display “PAr”).

Cannot change parameters | A multi-function contact input terminal is set to allow or restrict parameter editing (H1-01 through H1-07 = 1B).

Cannot change parameters | The wrong password was entered.

Cannot change parameters | Undervoltage was detected.

Motor does not rotate | The drive is not in the Drive Mode.

Motor does not rotate | The button was pushed.

Motor does not rotate | The [LO/RE] button was pushed.

Motor does not rotate | Auto-Tuning has just completed.

Motor does not rotate | A Fast-Stop was executed and has not yet been reset.

Motor does not rotate | Settings are incorrect for the source that provides the run command.

Motor does not rotate | One of the Safety Inputs is open.

Motor does not rotate | There is faulty wiring in the control circuit terminals.

Cannot change parameters — PDF page 300

Source row Cause Possible solutions
1 The drive is running the motor (i.e., the Run command is present). • Stop the drive and switch over to the Programming Mode. • Most parameters cannot be edited during run.
2 The Access Level is set to restrict access to parameter settings. • Set the Access Level to allow parameters to be edited (A1-01 = 2).
3 The operator is not in the Parameter Setup Mode (the LED screen will display “PAr”). • See what mode the LED parameter is current set for. • Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr” appears on the screen.
4 A multi-function contact input terminal is set to allow or restrict parameter editing (H1-01 through H1-07 = 1B). • When the terminal is open, parameters cannot be edited. • Turn on the multi-function contact input set to 1B.
5 The wrong password was entered. • If the password entered to A1-04 does not match the password saved to A1-05, then drive settings cannot be changed. • Reset the password. If you cannot remember the password: • Display parameter A1-04. Press the [STOP] button while pressing [UP] at the same time. Parameter A1-05 will appear. • Set a new password to parameter A1-05.
6 Undervoltage was detected. • Check the drive input power voltage by looking at the DC bus voltage (U1-07). • Check all main circuit wiring.

Motor does not rotate — PDF page 300

Source row Cause Possible solutions
1 The drive is not in the Drive Mode. • Check if the DRV light on the LED operator is lit. • Enter the Drive Mode to begin operating the motor. Refer to The Drive and Programming Modes on page 84.
2 The [LO/RE] button was pushed. Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the source, the LO/RE button LED must be on, if the source is REMOTE, it must be off. Take the following steps to solve the problem: • Push the [LO/RE] button. • If o2-01 is set to 0, then the LO/RE button will be disabled.
3 Auto-Tuning has just completed. • When Auto-Tuning has completed, the drive is switched back to the Programming Mode. The Run command will not be accepted unless the drive is in the Drive Mode. • Use the LED operator to enter the Drive Mode. Refer to The Drive and Programming Modes on page 84.
4 A Fast-Stop was executed and has not yet been reset. Reset the Fast-Stop command.
5 Settings are incorrect for the source that provides the run command. Check parameter b1-02 (Run Command Selection). Set b1-02 so that it corresponds with the correct run command source. 0: LED/LCD operator 1: Control circuit terminal (default setting) 2: MEMOBUS/Modbus communications 3: Option card
6 One of the Safety Inputs is open. • Check for a short-circuit between terminals H1 and HC. • See if one of the Safety Inputs is open. • Correct any faulty wiring.
7 There is faulty wiring in the control circuit terminals. • Check the wiring for the control terminal. • Correct wiring mistakes. • Check the input terminal status monitor (U1-10).

Manual — Motor not running and direction troubleshooting — page 301

Source reference: SIEP C71060618F, December 2016, physical PDF page 301. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Cause Possible Solutions

n Motor Rotates in the Opposite Direction from the Run Command

6.9 Troubleshooting without Fault Display

Troubleshooting

Motor does not rotate continued from PDF300 | The drive has been set to accept the frequency reference from the incorrect source.

Motor does not rotate continued from PDF300 | The terminal set to accept the main speed reference is set to the incorrect voltage and/or current.

Motor does not rotate continued from PDF300 | Selection for the sink/source mode is incorrect.

Motor does not rotate continued from PDF300 | Frequency reference is too low.

Motor does not rotate continued from PDF300 | Multi-function analog input is set up to accept gain for the frequency reference, but no voltage (current) has been provided.

Motor does not rotate continued from PDF300 | The STOP button was pressed when the drive was started from a REMOTE source.

Motor does not rotate continued from PDF300 | The [STOP] button was pressed when the drive was started from a REMOTE source.

Motor does not rotate continued from PDF300 | Motor is not producing enough torque in the V/f motor control method.

Motor does not rotate continued from PDF300 | Motor is not producing enough torque in Open Loop Vector Control.

Motor does not rotate continued from PDF300 | The drive is set for both 2-Wire and 3-Wire sequence at the same time.

Motor Rotates in the Opposite Direction from the Run Command | Phase wiring between the drive and motor is incorrect.

Motor Rotates in the Opposite Direction from the Run Command | The forward direction for the motor is setup incorrectly.

Motor does not rotate continued from PDF300 — PDF page 301

Source row Cause Possible solutions
1 The drive has been set to accept the frequency reference from the incorrect source. Check parameter b1-01 (Frequency Reference Selection 1). Set b1-01 to the correct source of the frequency reference. 0: LED operator 1: Control circuit terminal (default setting) 2: MEMOBUS/Modbus communications 3: Option card 4: Pulse train input (RP)
2 The terminal set to accept the main speed reference is set to the incorrect voltage and/or current. If the frequency reference is set at terminal A1, check parameter H3-01 for the correct signal level selection. If terminal A2 is used, check DIP switch S1. Then select the correct input level for terminal A2 in parameter H3-08. Refer to DIP Switch S1 Analog Input Signal Selection on page 70.
3 Selection for the sink/source mode is incorrect. Check DIP switch S3. Refer to Sinking/Sourcing Mode Switch on page 68.
4 Frequency reference is too low. • Check the frequency reference monitor (U1-01). • Increase the frequency by changing the maximum output frequency (E1-09).
5 Multi-function analog input is set up to accept gain for the frequency reference, but no voltage (current) has been provided. • Check the multi-function analog input settings. • Check if analog input A1 or A2 is set for frequency reference gain (H3-02/10 = 1). If so, check if the correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is applied to the gain input. • Check if H3-02 and H3-10 have been set to the proper values. • Check if the analog input value has been set properly.
6 The [STOP] button was pressed when the drive was started from a REMOTE source. • When the [STOP] button is pressed, the drive will decelerate to stop. • Switch off the run command and then re-enter a run command. • The [STOP] button is disabled when o2-02 is set to 0.
7 Motor is not producing enough torque in the V/f motor control method. • Ensure the selected V/f pattern corresponds with the characteristics of the motor being used. • Set the correct V/f pattern to E1-03. • When E1-03 = F, increase both the minimum and mid output frequency voltages (E1-08, E1-10).
8 Motor is not producing enough torque in the V/f motor control method. Increase the frequency reference so that it is higher than the minimum frequency reference (E1-09).
9 Motor is not producing enough torque in the V/f motor control method. Perform Line-to-Line Resistance Auto-Tuning when using particularly long motor cables.
10 Motor is not producing enough torque in the V/f motor control method. Increase the torque compensation gain (C4-01).
11 Motor is not producing enough torque in Open Loop Vector Control. • Execute Rotational Auto-Tuning. • If the motor cables are replaced with longer cables after Rotational Auto-Tuning was performed, Auto-Tuning may need to be repeated due to voltage drop across the line.
12 Motor is not producing enough torque in Open Loop Vector Control. • Check if the torque limit parameters have been set too low (L7-01 through L7-04). • Reset the torque limit back to its default setting (200%).
13 Motor is not producing enough torque in Open Loop Vector Control. Increase both the minimum and mid output frequency voltages (E1-08 and E1-10).
14 The drive is set for both 2-Wire and 3-Wire sequence at the same time. • The drive is set for a 3-Wire sequence when one of parameters H1-03 through H1-07 is set to 0. • If the drive is supposed to be set up for a 2-Wire sequence, then ensure parameters H1-03 through H1-07 are not set to 0. • If the drive is supposed to be set up for a 3-Wire sequence, then H1-□□ must be set to 0.

Motor Rotates in the Opposite Direction from the Run Command — PDF page 301

Source row Cause Possible solutions
1 Phase wiring between the drive and motor is incorrect. • Check the motor wiring. • Switch two motor cables (U, V, and W) to reverse motor direction. • Connect drive output terminals U/T1, V/T2 and W/T3 in the right order to the corresponding motor terminals U, V, and W. • Change the setting of parameter b1-14.
2 The forward direction for the motor is setup incorrectly. Typically, forward is designated as being counterclockwise when looking from the motor shaft (refer to the figure below). Figure labels: 1. Forward Rotating Motor (looking down the motor shaft); 2. Motor Shaft. Exact figure geometry original-only; manufacturer-specific note continues PDF302.

Manual — Direction, heat and tuning troubleshooting — page 302

Source reference: SIEP C71060618F, December 2016, physical PDF page 302. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Cause Possible Solutions

Note: Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the manufacturer of the motor.

n Motor Rotates in One Direction Only

n Motor is Too Hot

n Drive Does Not Allow Selection of Rotational Auto-Tuning

n Motor Hunting Occurs at Low Speeds

6.9 Troubleshooting without Fault Display

Motor rotates opposite to Run command continued from PDF301 | The motor is running at almost 0 Hz and the Speed Search estimated the speed to be in the opposite direction.

Motor Rotates in One Direction Only | The drive prohibits reverse rotation.

Motor Rotates in One Direction Only | A Reverse run signal has not been entered, although 3-Wire sequence is selected.

Motor is Too Hot | The load is too heavy.

Motor is Too Hot | The air around the motor is too hot.

Motor is Too Hot | The drive is operating in a vector control mode but Auto-Tuning has not yet been performed.

Motor is Too Hot | Insufficient voltage insulation between motor phases.

Motor is Too Hot | The motor fan has stopped or is clogged.

Drive Does Not Allow Selection of Rotational Auto-Tuning | The drive is in the incorrect motor control method for Rotational Auto-Tuning.

Motor Hunting Occurs at Low Speeds | Excessive load inertia in Open Loop Vector Control.

Motor rotates opposite to Run command continued from PDF301 — PDF page 302

Source row Cause Possible solutions
1 The motor is running at almost 0 Hz and the Speed Search estimated the speed to be in the opposite direction. • Disable bi-directional search (b3-14 = “0”) so that Speed Search is performed only in the specified direction.

Motor Rotates in One Direction Only — PDF page 302

Source row Cause Possible solutions
1 The drive prohibits reverse rotation. • Check parameter b1-04. • Set the drive to allow the motor to rotate in reverse (b1-04 = “0”).
2 A Reverse run signal has not been entered, although 3-Wire sequence is selected. • Make sure that one of the input terminals S3 to S7 used for the 3-Wire sequence has been set for reverse.

Motor is Too Hot — PDF page 302

Source row Cause Possible solutions
1 The load is too heavy. If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque value for an extended period of time. Keep in mind that the motor also has a short-term overload rating in addition to the possible solutions provided below: • Reduce the load. • Increase the acceleration and deceleration times. • Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current (E2-01). • Increase motor capacity.
2 The air around the motor is too hot. • Check the ambient temperature. • Cool the area until it is within the specified temperature range.
3 The drive is operating in a vector control mode but Auto-Tuning has not yet been performed. • Perform Auto-Tuning. • Calculate the motor value and reset the motor parameters. • Change the motor control method to V/f Control (A1-02 = “0”).
4 Insufficient voltage insulation between motor phases. When the motor is connected to terminals U/T1, V/T2, and W/T3, voltage surges occur between the motor coils and drive switching. Normally, surges can reach up to three times the drive input power supply voltage (600 V for 200 V class, and 1200 V for 400 V class). • Use a motor with voltage tolerance higher than the max voltage surge. • Use a motor designed to work specifically with a drive when using a 400 V class unit. • Install an AC reactor on the output side of the drive.
5 The motor fan has stopped or is clogged. Check the motor fan.

Drive Does Not Allow Selection of Rotational Auto-Tuning — PDF page 302

Source row Cause Possible solutions
1 The drive is in the incorrect motor control method for Rotational Auto-Tuning. • Check if the drive is set to V/f Control by accident (A1-02 = 0). • Change the motor control method to Open Loop Vector Control (A1-02 = “2”).

Motor Hunting Occurs at Low Speeds — PDF page 302

Source row Cause Possible solutions
1 Excessive load inertia in Open Loop Vector Control. • Excess load inertia can cause motor hunting in Open Loop Vector Control due to slow motor response. • Increase the speed feedback detection control time constant (n2-02) from its default value of 50 ms to an appropriate level between 200 and 1000 ms. Adjust this setting in combination with n2-03 (Feedback Detection Control Time Constant 2).

Manual — Current, overvoltage and acceleration troubleshooting — page 303

Source reference: SIEP C71060618F, December 2016, physical PDF page 303. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n oPE02 Error Occurs when Lowering the Motor Rated Current Setting

Cause Possible Solutions

n Overvoltage Occurs When Running at a Constant Speed

n Motor Stalls During Acceleration or With Large Loads

n Motor Will Not Accelerate or the Acceleration Time is Too Long

6.9 Troubleshooting without Fault Display

Troubleshooting

oPE02 Error Occurs when Lowering the Motor Rated Current Setting | The motor rated current and the motor no-load current settings in the drive are incorrect.

Overvoltage Occurs When Running at a Constant Speed | Excessive load inertia in Open Loop Vector Control.

Motor Stalls During Acceleration or With Large Loads | Load is too heavy.

Motor Will Not Accelerate or the Acceleration Time is Too Long | Frequency reference is too low.

Motor Will Not Accelerate or the Acceleration Time is Too Long | Load is too heavy.

Motor Will Not Accelerate or the Acceleration Time is Too Long | The torque limit function is operating in Open Loop Vector Control.

Motor Will Not Accelerate or the Acceleration Time is Too Long | Acceleration time has been set too long.

Motor Will Not Accelerate or the Acceleration Time is Too Long | Motor characteristics and drive parameter settings are incompatible with one another in V/f Control.

Motor Will Not Accelerate or the Acceleration Time is Too Long | The right combination of motor characteristics have not been set in Open Loop Vector Control.

Motor Will Not Accelerate or the Acceleration Time is Too Long | Incorrect frequency reference setting.

Motor Will Not Accelerate or the Acceleration Time is Too Long | The Stall Prevention level during acceleration and deceleration set too low.

Motor Will Not Accelerate or the Acceleration Time is Too Long | The Stall Prevention level during run has been set too low.

oPE02 Error Occurs when Lowering the Motor Rated Current Setting — PDF page 303

Source row Cause Possible solutions
1 The motor rated current and the motor no-load current settings in the drive are incorrect. The user is trying to set the motor rated current in E2-01 to a value lower than the no-load current set in E2-03. • Make sure that value set in E2-01 is higher than E2-03. Setting E2-01 < E2-03 will trigger an oPE02 error. • If it is necessary to set E2-01 lower than E2-03, first lower the value set to E2-03, then change the setting in E2-01 as needed.

Overvoltage Occurs When Running at a Constant Speed — PDF page 303

Source row Cause Possible solutions
1 Excessive load inertia in Open Loop Vector Control. • Loads with a lot of inertia (fans, etc.) can trigger an overvoltage fault when operating in Open Loop Vector Control. • Switch to the V/f motor control method. • Adjust the values set for the speed feedback detection control time constant (n2-02, n2-03).

Motor Stalls During Acceleration or With Large Loads — PDF page 303

Source row Cause Possible solutions
1 Load is too heavy. Take the following steps to resolve the problem: • Reduce the load. • Increase the acceleration time. • Increase motor capacity. • Although the drive has a Stall Prevention function and a Torque Compensation Limit function, accelerating too quickly or trying to drive an excessively large load can exceed the capabilities of the motor.

Motor Will Not Accelerate or the Acceleration Time is Too Long — PDF page 303

Source row Cause Possible solutions
1 Frequency reference is too low. • Check the maximum output frequency (E1-04). • Increase E1-04 if it is set too low.
2 Frequency reference is too low. Check U1-01 for proper frequency reference.
3 Frequency reference is too low. Check if a frequency reference signal switch has been set to one of the multi-function input terminals.
4 Frequency reference is too low. Check for low gain level set to terminals A1 or A2 (H3-03, H3-11).
5 Load is too heavy. • Reduce the load so that the output current remains within the motor-rated current. • In extruder and mixer applications, the load will sometimes increase as the temperature drops.
6 Load is too heavy. Check if the mechanical brake is fully releasing as it should.
7 The torque limit function is operating in Open Loop Vector Control. • Check the torque limit setting. It may be too low. (L7-01 through L7-04). • Reset the torque limit to its default value (200%).
8 Acceleration time has been set too long. Check if the acceleration time parameters have been set too long (C1-01, -03, -05, -07).
9 Motor characteristics and drive parameter settings are incompatible with one another in V/f Control. • Set the correct V/f pattern so that it matches the characteristics of the motor being used. • Check E1-03 (V/f Pattern Selection).
10 The right combination of motor characteristics have not been set in Open Loop Vector Control. Execute Rotational Auto-Tuning.
11 Incorrect frequency reference setting. • Check the multi-function analog input settings. • Check if multi-function analog input terminal A1 or A2 is set for frequency gain (H3-02 or H3-10 = “1”). If so, the frequency reference will be 0 if there is no voltage (current) input provided. • Ensure H3-02 and H3-10 are set to the proper values. • Ensure the analog input value is set to the right value (U1-13, U1-14).
12 The Stall Prevention level during acceleration and deceleration set too low. • Check the Stall Prevention level during acceleration (L3-02). • If L3-02 is set too low, acceleration will take a fair amount of time. • Increase L3-02.
13 The Stall Prevention level during run has been set too low. • Check the Stall Prevention level during run (L3-06). • If L3-06 is set too low, speed will drop as the drive outputs torque. • Increase the setting value.

Manual — Acceleration, reference and deceleration troubleshooting — page 304

Source reference: SIEP C71060618F, December 2016, physical PDF page 304. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Cause Possible Solutions

n Drive Frequency Reference Differs from the Controller Frequency Reference Command

n Poor Speed Control Accuracy

n Deceleration Takes Longer Than Expected with Dynamic Braking Enabled

6.9 Troubleshooting without Fault Display

Motor will not accelerate or acceleration time too long continued from PDF303 | Although the drive is operating in Open Loop Vector motor control method, Auto-Tuning has not been performed.

Motor will not accelerate or acceleration time too long continued from PDF303 | Drive reached the limitations of the V/f motor control method.

Drive Frequency Reference Differs from the Controller Frequency Reference Command | The analog input frequency gain and bias are set to incorrect values.

Drive Frequency Reference Differs from the Controller Frequency Reference Command | A frequency bias signal is being entered via analog input terminals A1 or A2.

Poor Speed Control Accuracy | Drive reached the slip compensation limit.

Poor Speed Control Accuracy | Motor-rated voltage is set too high in Open Loop Vector Control.

Poor Speed Control Accuracy | Auto-Tuning did not complete properly for Open Loop Vector Control.

Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | L3-04 is set incorrectly.

Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | The deceleration time is set too long.

Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | Insufficient motor torque.

Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | Reaching the torque limit.

Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | Load exceeded the internal torque limit determined by the drive rated current.

Motor will not accelerate or acceleration time too long continued from PDF303 — PDF page 304

Source row Cause Possible solutions
1 Although the drive is operating in Open Loop Vector motor control method, Auto-Tuning has not been performed. • Perform Auto-Tuning. • Calculate motor data and reset motor parameters. • Switch to the V/f motor control method (A1-02 = “0”).
2 Drive reached the limitations of the V/f motor control method. • The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line resistance. • Be aware that V/f Control is comparatively limited when it comes to producing torque at low speeds. • Consider switching to Open Loop Vector Control.

Drive Frequency Reference Differs from the Controller Frequency Reference Command — PDF page 304

Source row Cause Possible solutions
1 The analog input frequency gain and bias are set to incorrect values. • Check the main speed frequency reference terminal input gain level assigned to terminals A1 and A2, as well as the frequency reference input bias to terminals A1 and A2 (parameters H3-03, H3-04, and H3-12). • Set these parameters to the appropriate values.
2 A frequency bias signal is being entered via analog input terminals A1 or A2. • If multi-function analog input terminals A1 and A2 are set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both signals builds the frequency reference. • Ensure that H3-02 and H3-10 are set appropriately. • Check the input level set for terminals A1 and A2 (U1-13, U1-14).

Poor Speed Control Accuracy — PDF page 304

Source row Cause Possible solutions
1 Drive reached the slip compensation limit. • Check the slip compensation limit (C3-03). • Increase the value set to C3-03.
2 Motor-rated voltage is set too high in Open Loop Vector Control. • The input voltage for the drive determines the maximum output voltage. A drive with an input of 200 Vac can only output a maximum of 200 Vac. Open Loop Vector Control sometimes calculates an output voltage reference value that exceeds the maximum drive output voltage level, resulting in a loss of speed control accuracy. • Use a motor with a lower voltage rating (a vector control motor). • Increase the input power voltage.
3 Auto-Tuning did not complete properly for Open Loop Vector Control. • Perform Auto-Tuning again.

Deceleration Takes Longer Than Expected with Dynamic Braking Enabled — PDF page 304

Source row Cause Possible solutions
1 L3-04 is set incorrectly. • Check the Stall Prevention Level during deceleration (L3-04). • If a braking resistor option has been installed, disable Stall Prevention during deceleration (L3-04 = “0”).
2 The deceleration time is set too long. Set deceleration to more appropriate time (C1-02, C1-04, C1-06, C1-08).
3 Insufficient motor torque. • Assuming parameter settings are normal and that no overvoltage occurs when there is insufficient torque, it is likely that the demand on the motor has exceeded the motor capacity. • Use a larger motor.
4 Reaching the torque limit. • Check the settings for the torque limit (L7-01 through L7-04). • If the torque limit is enabled, deceleration might take longer than expected because the drive cannot output more torque than the limit setting. Ensure the torque limit is set to a large enough value. • Increase the torque limit setting.
5 Reaching the torque limit. • If multi-function analog input terminal A1 or A2 is set to torque limit (H3-02 or H3-10 equals 10, 11, 12, or 15), ensure that the analog input levels are set to the correct levels. • Ensure H3-02 and H3-10 are set to the right levels. • Ensure the analog input is set to the correct value.
6 Load exceeded the internal torque limit determined by the drive rated current. Switch to a larger capacity drive.

Manual — Hunting, elevator brake, noise and GFCI troubleshooting — page 305

Source reference: SIEP C71060618F, December 2016, physical PDF page 305. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n Motor Hunting Occurs When Operating With a Light Load

Cause Possible Solutions

n Load Falls When Brake is Applied (Elevator-Type Applications)

n Noise From Drive or Output Lines When the Drive is Powered On

n Ground Fault Circuit Interrupter (GFCI) Trips During Run

n Connected Machinery Vibrates When Motor Rotates

Excessive Motor Oscillation and Erratic Rotation

Cause Possible Solution

Unexpected Noise from Connected Machinery

Note: The drive may have trouble assessing the status of the load due to white noise generated when using Swing PWM (C6-02 = 7 to A).

6.9 Troubleshooting without Fault Display

Troubleshooting

Motor Hunting Occurs When Operating With a Light Load | Carrier frequency is too high.

Motor Hunting Occurs When Operating With a Light Load | Large V/f setting value at low speeds triggers overexcitation.

Motor Hunting Occurs When Operating With a Light Load | The maximum output frequency and the base frequency reference are not set properly in relationship to each other.

Motor Hunting Occurs When Operating With a Light Load | Hunting Prevention is disabled (V/f control only).

Load Falls When Brake is Applied (Elevator-Type Applications) | The timing for the brake to close and release is not set properly.

Load Falls When Brake is Applied (Elevator-Type Applications) | Insufficient DC Injection Braking.

Noise From Drive or Output Lines When the Drive is Powered On | Relay switching in the drive generates excessive noise.

Ground Fault Circuit Interrupter (GFCI) Trips During Run | Excessive leakage current trips MCCB.

Excessive Motor Oscillation and Erratic Rotation | Poor balance between motor phases.

Unexpected Noise from Connected Machinery | The carrier frequency is at the resonant frequency of the connected machinery.

Unexpected Noise from Connected Machinery | The drive output frequency is the same as the resonant frequency of the connected machinery.

Motor Hunting Occurs When Operating With a Light Load — PDF page 305

Source row Cause Possible solutions
1 Carrier frequency is too high. Lower the carrier frequency setting C6-02.
2 Large V/f setting value at low speeds triggers overexcitation. • Select the proper V/f pattern (E1-03). • Use parameters E1-04 through E1-10 to set the V/f pattern in relation to the load characteristics.
3 The maximum output frequency and the base frequency reference are not set properly in relationship to each other. Set the proper values for the maximum output frequency and base frequency (E1-04, E1-06).
4 Hunting Prevention is disabled (V/f control only). • Enable Hunting Prevention by setting n1-01 = “1”. • (OLV only) Increase the speed feedback detection control gain and time constant (n2-01, n2-02).

Load Falls When Brake is Applied (Elevator-Type Applications) — PDF page 305

Source row Cause Possible solutions
1 The timing for the brake to close and release is not set properly. Use frequency reference detection for closing and releasing the brake. • At start: Release the brake after creating enough torque. • At stop: Close the brake when the motor still produces torque. Make the following setting changes to hold the brake: • Set the frequency detection inactive during baseblock (L4-07 = 0). • Multi-function contact output terminal will switch on when the output frequency is greater than the frequency detection level set in L4-01. Set L4-01 between 1.0 and 3.0 Hz. • Slipping may occur when stopping because hysteresis is used in Frequency Reference 2 (where the frequency agree setting in L4-02 is 2.0 Hz). To prevent this, change the setting to 0.1 Hz. • Do not use the multi-function contact output setting “During Run” (H2-01 = 0) for the brake signal.
2 Insufficient DC Injection Braking. Increase the amount of DC Injection Braking (b2-02).

Noise From Drive or Output Lines When the Drive is Powered On — PDF page 305

Source row Cause Possible solutions
1 Relay switching in the drive generates excessive noise. • Lower the carrier frequency (C6-02). • Install a noise filter on the input side of drive input power. • Install a noise filter on the output side of the drive. • Place the wiring inside a metal conduit to shield it from switching noise. • Ground the drive and motor properly. • Separate the main circuit wiring and the control lines.

Ground Fault Circuit Interrupter (GFCI) Trips During Run — PDF page 305

Source row Cause Possible solutions
1 Excessive leakage current trips MCCB. • Increase the GFCI sensitivity or use GFCI with a higher threshold. • Lower the carrier frequency (C6-02). • Reduce the length of the cable used between the drive and the motor. • Install a noise filter or reactor on the output side of the drive.

Excessive Motor Oscillation and Erratic Rotation — PDF page 305

Source row Cause Possible solutions
1 Poor balance between motor phases. Check drive input power voltage to ensure that it provides stable power.

Unexpected Noise from Connected Machinery — PDF page 305

Source row Cause Possible solutions
1 The carrier frequency is at the resonant frequency of the connected machinery. Adjust the carrier frequency using parameters C6-02 through C6-05.
2 The drive output frequency is the same as the resonant frequency of the connected machinery. • Adjust the parameters used for the Jump Frequency function (d3-01 through d3-04) to skip the problem-causing bandwidth. • Place the motor on a rubber pad to reduce vibration.

Manual — Oscillation, PID, torque and stopping troubleshooting — page 306

Source reference: SIEP C71060618F, December 2016, physical PDF page 306. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n Oscillation or Hunting

Cause Possible Solutions

n PID Output Fault

n Insufficient Motor Torque

n Motor Rotates After the Drive Output is Shut Off

6.9 Troubleshooting without Fault Display

Oscillation or Hunting | Insufficient tuning in Open Loop Vector Control

Oscillation or Hunting | Auto-Tuning has not yet been performed (required for Open Loop Vector Control).

Oscillation or Hunting | Insufficient tuning in V/f Control.

Oscillation or Hunting | Gain is too low when using PID control.

Oscillation or Hunting | The frequency reference is assigned to an external source and the signal is noisy.

Oscillation or Hunting | The cable between the drive and motor is too long.

PID Output Fault | No PID feedback input.

PID Output Fault | The level of detection and the target value do not correspond with each other.

PID Output Fault | Reverse drive output frequency and speed detection. When output frequency rises, the sensor detects a speed decrease.

Insufficient Motor Torque | Auto-Tuning has not yet been performed (required for OLV Control).

Insufficient Motor Torque | The control mode was changed after performing Auto- Tuning.

Insufficient Motor Torque | Only Line-to-Line Resistance Auto-Tuning was performed.

Motor Rotates After the Drive Output is Shut Off | Low DC Injection Braking and the drive cannot decelerate properly.

Oscillation or Hunting — PDF page 306

Source row Cause Possible solutions
1 Insufficient tuning in Open Loop Vector Control Adjust the following parameters in the order listed. An increase in gain should be followed with an increase in the primary delay time constant. • C4-02 (Torque Compensation Primary Delay Time) • n2-01 (Speed Feedback Detection Control [AFR] Time Constant 1) • C3-02 (Slip Compensation Primary Delay Time) The response for torque compensation and slip compensation will drop as the time constant is increased.
2 Auto-Tuning has not yet been performed (required for Open Loop Vector Control). Perform Auto-Tuning. Set motor parameters after calculating the proper values. Change the motor control method to V/f Control (A1-02 = “0”).
3 Insufficient tuning in V/f Control. Reduce the gain. • n1-02 (Hunting Prevention Gain Setting) • n1-03 (Hunting Prevention Time Constant Setting)
4 Gain is too low when using PID control. Check the period of oscillation and adjust P, I, and D settings accordingly.
5 The frequency reference is assigned to an external source and the signal is noisy. • Ensure that noise is not affecting the signal lines. • Separate main circuit wiring and control circuit wiring. • Use twisted-pair cables or shielded wiring for the control circuit. • Increase the analog input time filter constant (H3-13).
6 The cable between the drive and motor is too long. • Perform Auto-Tuning. • Reduce the length of the cable.

PID Output Fault — PDF page 306

Source row Cause Possible solutions
1 No PID feedback input. • Check the multi-function analog input terminal settings. • Set multi-function analog input terminal A1 or A2 for PID feedback (H3-02 or H3-10 = “B”). • A signal input to the terminal selection for PID feedback is necessary. • Check the connection of the feedback signal. • Check the various PID-related parameter settings. • No PID feedback input to the terminal causes the value detected to be 0, causing a PID fault and the drive to operate at max frequency.
2 The level of detection and the target value do not correspond with each other. • PID control keeps the difference between target and detection values at 0. Set the input level for the values relative to one another. • Use analog input gains H3-03/11 to adjust PID target and feedback signal scaling.
3 Reverse drive output frequency and speed detection. When output frequency rises, the sensor detects a speed decrease. Set PID output for reverse characteristics (b5-09 = “1”).

Insufficient Motor Torque — PDF page 306

Source row Cause Possible solutions
1 Auto-Tuning has not yet been performed (required for OLV Control). Perform Auto-Tuning.
2 The control mode was changed after performing Auto- Tuning. Perform Auto-Tuning again.
3 Only Line-to-Line Resistance Auto-Tuning was performed. Perform Rotational Auto-Tuning.

Motor Rotates After the Drive Output is Shut Off — PDF page 306

Source row Cause Possible solutions
1 Low DC Injection Braking and the drive cannot decelerate properly. • Adjust the DC Injection braking settings. • Increase the value of b2-02 (DC Injection Braking Current). • Increase the b2-04 (DC Injection Braking Time at Stop).

Manual — Rotating load, frequency, PM and Run troubleshooting — page 307

Source reference: SIEP C71060618F, December 2016, physical PDF page 307. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n ov or Speed Loss Occurs When Starting into a Rotating Load

Cause Possible Solutions

n Output Frequency is not as High as Frequency Reference

n Buzzing Sound from Motor at 2 kHz

n Unstable Motor Speed when Using PM or IPM

n Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed

n Motor Does Not Operate When an External Run Command is Input

6.9 Troubleshooting without Fault Display

Troubleshooting

ov or Speed Loss Occurs When Starting into a Rotating Load | The load is already rotating when the drive is trying to start it.

Output Frequency is not as High as Frequency Reference | Frequency reference is set within the range of the Jump Frequency.

Output Frequency is not as High as Frequency Reference | Upper limit for the frequency reference has been exceeded.

Output Frequency is not as High as Frequency Reference | Large load triggered Stall Prevention function during acceleration.

Buzzing Sound from Motor at 2 kHz | Exceeded 110% of the rated output current of the drive while operating at low speeds.

Unstable Motor Speed when Using PM or IPM | The motor code for PM (E5-01) is set incorrectly. (Yaskawa motors only)

Unstable Motor Speed when Using PM or IPM | The drive is operating at less than 10% of the speed reference.

Unstable Motor Speed when Using PM or IPM | Motor hunting occurs.

Unstable Motor Speed when Using PM or IPM | Hunting occurs at start.

Unstable Motor Speed when Using PM or IPM | Too much current is flowing through the drive.

Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed | The LOCAL/REMOTE mode is not selected properly.

Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed | The drive is not in drive mode.

Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed | The frequency reference is too low.

Motor Does Not Operate When an External Run Command is Input | The LOCAL/REMOTE mode is not selected properly.

Motor Does Not Operate When an External Run Command is Input | The drive is not in Drive Mode.

ov or Speed Loss Occurs When Starting into a Rotating Load — PDF page 307

Source row Cause Possible solutions
1 The load is already rotating when the drive is trying to start it. • Stop the motor using DC Injection braking. Restart the motor. • Increase the value of b2-03 (DC Injection Braking Time at start). • Enable Speed Search at start (b3-01 = “1”). • Set a multi-function input terminal for external Speed Search command (H1-□□=“61” or “62” during restart).

Output Frequency is not as High as Frequency Reference — PDF page 307

Source row Cause Possible solutions
1 Frequency reference is set within the range of the Jump Frequency. • Adjust the parameters used for the Jump Frequency function (d3-01, d3-02, d3-03). • Enabling the Jump Frequency prevents the drive from outputting the frequencies specified in the Jump Frequency range.
2 Upper limit for the frequency reference has been exceeded. • Set the maximum output frequency and the upper limit for the frequency reference to more appropriate values (E1-04, d2-01). • The following calculation yields the upper value for the output frequency = E1-04 x d2-01 / 100
3 Large load triggered Stall Prevention function during acceleration. • Reduce the load. • Adjust the Stall Prevention level during acceleration (L3-02).

Buzzing Sound from Motor at 2 kHz — PDF page 307

Source row Cause Possible solutions
1 Exceeded 110% of the rated output current of the drive while operating at low speeds. • If the output current rises too high at low speeds, the carrier frequency automatically reduces and causes a whining or buzzing sound. • If the sound is coming from the motor, disable carrier frequency derating (L8-38 = “0”). • Disabling the automatic carrier frequency derating increases the chances of an overload fault (oL2). Switch to a larger capacity motor if oL2 faults occur too frequently.

Unstable Motor Speed when Using PM or IPM — PDF page 307

Source row Cause Possible solutions
1 The motor code for PM (E5-01) is set incorrectly. (Yaskawa motors only) Set parameter E5-01 in accordance with the motor being used.
2 The drive is operating at less than 10% of the speed reference. Consult with Yaskawa about using a different type of motor when attempting to operate at 10% of the speed reference.
3 Motor hunting occurs. Set and carefully adjust the following parameters in the order listed: • n8-45 (Speed Feedback Detection Suppression Gain) • n8-55 (Load Inertia for PM Motors) • C4-02 (Torque Compensation Primary Delay Time)
4 Hunting occurs at start. Increase the S-curve time at the start of acceleration (C2-01).
5 Too much current is flowing through the drive. • If using a PM motor, set the correct motor code to E5-01. • If using a specialized motor, set parameter E5-xx to the correct value according to the Motor Test Report.

Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed — PDF page 307

Source row Cause Possible solutions
1 The LOCAL/REMOTE mode is not selected properly. Press the LOCAL/REMOTE button to switch. The LO/RE LED should be on for LOCAL mode.
2 The drive is not in drive mode. A run command will not be issued. Exit to the drive mode and cycle the run command.
3 The frequency reference is too low. • If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the drive will not operate. • Raise the frequency reference to at least the minimum output frequency.

Motor Does Not Operate When an External Run Command is Input — PDF page 307

Source row Cause Possible solutions
1 The LOCAL/REMOTE mode is not selected properly. Press the LOCAL/REMOTE button to switch. The LO/RE LED should be off for REMOTE mode.
2 The drive is not in Drive Mode. A run command will not be issued. Exit to the Drive mode and cycle the run command.

Manual — External Run, direction, PID and interference troubleshooting — page 308

Source reference: SIEP C71060618F, December 2016, physical PDF page 308. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Cause Possible Solutions

n Motor Stops During Acceleration or When a Load is Connected

Cause Possible Solution

n Motor Rotates in One Direction Only

n Motor Operates at a Higher Speed than the Speed Command

n Poor Speed Control Accuracy Above Base Speed in Open Loop Vector Motor Control Method

n Peripheral Devices Affected by Drive Operation

n Ground Fault Interrupter Activates When Drive is Running

6.9 Troubleshooting without Fault Display

Motor does not operate on external Run continued from PDF307 | The frequency reference is too low.

Motor Stops During Acceleration or When a Load is Connected | • The load is too heavy. • The limit of motor response may be reached during rapid acceleration. This may be a result of improper stall prevention or automatic torque boost function adjustment.

Motor Rotates in One Direction Only | "Reverse run prohibited" is selected. If b1-04 (Reverse Prohibit Operation) is set to 1 (reverse run prohibited), the drive will not accept a reverse run command.

Motor Rotates in One Direction Only | The drive prohibits reverse rotation.

Motor Rotates in One Direction Only | A Reverse run signal has not been entered, although 3- Wire sequence is selected.

Motor Operates at a Higher Speed than the Speed Command | PID is enabled. If the PID mode is enabled (b5-01 = 1 to 4), the drive output frequency will change to regulate the process variable to the target setpoint. The PID can command a speed up to maximum output frequency (E1-04).

Poor Speed Control Accuracy Above Base Speed in Open Loop Vector Motor Control Method | The maximum output voltage of the drive is determined by its input voltage. Vector control uses voltage to control the currents within the motor. If the vector control voltage reference value exceeds the drive output voltage capability, the speed control accuracy will decrease because the motor currents cannot be properly controlled.

Peripheral Devices Affected by Drive Operation | Radio frequency interference may be generated by drive output PWM waveform.

Ground Fault Interrupter Activates When Drive is Running | The output of the drive is a series of high frequency pulses (PWM), so there is a certain amount of leakage current. This may cause the ground fault interrupter to operate and cut off the drive input power.

Motor does not operate on external Run continued from PDF307 — PDF page 308

Source row Cause Possible solutions
1 The frequency reference is too low. • If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the drive will not operate. • Raise the frequency reference to at least the minimum output frequency.

Motor Stops During Acceleration or When a Load is Connected — PDF page 308

Source row Cause Possible solutions
1 • The load is too heavy. • The limit of motor response may be reached during rapid acceleration. This may be a result of improper stall prevention or automatic torque boost function adjustment. Increase the acceleration time (C1-01) or reduce the motor load. Also, consider increasing the motor size and/or drive size.

Motor Rotates in One Direction Only — PDF page 308

Source row Cause Possible solutions
1 "Reverse run prohibited" is selected. If b1-04 (Reverse Prohibit Operation) is set to 1 (reverse run prohibited), the drive will not accept a reverse run command. Set b1-04 = “0” to allow reverse run operation.
2 The drive prohibits reverse rotation. • Check parameter b1-04. • Set the drive to allow the motor to rotate in reverse (b1-04 = “0”).
3 A Reverse run signal has not been entered, although 3- Wire sequence is selected. • Make sure that one of the input terminals S3 to S5 used for the 3-Wire sequence has been set for reverse.

Motor Operates at a Higher Speed than the Speed Command — PDF page 308

Source row Cause Possible solutions
1 PID is enabled. If the PID mode is enabled (b5-01 = 1 to 4), the drive output frequency will change to regulate the process variable to the target setpoint. The PID can command a speed up to maximum output frequency (E1-04). If PID operation is not target, disable PID by setting b5-01 = “0”.

Poor Speed Control Accuracy Above Base Speed in Open Loop Vector Motor Control Method — PDF page 308

Source row Cause Possible solutions
1 The maximum output voltage of the drive is determined by its input voltage. Vector control uses voltage to control the currents within the motor. If the vector control voltage reference value exceeds the drive output voltage capability, the speed control accuracy will decrease because the motor currents cannot be properly controlled. Use a motor with a lower rated voltage compared to the input voltage.

Peripheral Devices Affected by Drive Operation — PDF page 308

Source row Cause Possible solutions
1 Radio frequency interference may be generated by drive output PWM waveform. • Change the Carrier Frequency Selection (C6-02) to lower the carrier frequency. This will help to reduce the amount of transistor switching noise. • Install an Input Noise Filter at the input power terminals. • Install an Output Noise Filter at the motor terminals. • Use conduit. Metal can shield electrical noise. • Ground the drive and motor. • Separate main circuit wiring from control wiring.

Ground Fault Interrupter Activates When Drive is Running — PDF page 308

Source row Cause Possible solutions
1 The output of the drive is a series of high frequency pulses (PWM), so there is a certain amount of leakage current. This may cause the ground fault interrupter to operate and cut off the drive input power. • Change to a ground fault interrupter with a higher leakage current detection level (such as, a sensitivity current of 200 mA or greater per Unit, with an operating time of 0.1 s or more), or one that incorporates high-frequency corrective actions. • Change the Carrier Frequency Selection (C6-02) to lower the carrier frequency. Note: Leakage current increases in proportion to cable length.

Manual — Maintenance section safety — page 310

Source reference: SIEP C71060618F, December 2016, physical PDF page 310. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

7.1 Section Safety

DANGER

Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.

WARNING

Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material.

Manual — Maintenance equipment notices — page 311

Source reference: SIEP C71060618F, December 2016, physical PDF page 311. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive.

7.1 Section Safety

Periodic Inspection & Maintenance

Manual — Inspection conditions and daily checklist — page 312

Source reference: SIEP C71060618F, December 2016, physical PDF page 312. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

7.2 Inspection

Power electronics have limited life and may exhibit changed characteristics or performance deterioration after years of use under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and periodic inspection on the drive. Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and relays. The electronics in the drive serve a critical role in maintaining proper motor control. Follow the inspection lists provided in this chapter as a part of a regular maintenance program. Note: The drive will require more frequent inspection if it is placed in harsh environments, such as: • High ambient temperatures • Frequent starting and stopping • Fluctuations in the AC supply or load • Excessive vibrations or shock loading • Dust, metal dust, salt, sulfuric acid, chlorine atmospheres • Poor storage conditions. Perform the first equipment inspection 3 months after installation.

u Recommended Daily Inspection

Table 7.1 outlines the recommended daily inspection for Yaskawa drives. Check the following items on a daily basis to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection.

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

Table 7.1 General Recommended Daily Inspection Checklist

Inspection Category Inspection Points Corrective Action Checked

Daily Inspection checklist — blank Checked cells are template, not completed inspections | Motor

Daily Inspection checklist — blank Checked cells are template, not completed inspections | Cooling

Daily Inspection checklist — blank Checked cells are template, not completed inspections | Cooling Fan

Daily Inspection checklist — blank Checked cells are template, not completed inspections | Environment

Daily Inspection checklist — blank Checked cells are template, not completed inspections | Load

Daily Inspection checklist — blank Checked cells are template, not completed inspections | Power Supply Voltage

Daily Inspection checklist — blank Checked cells are template, not completed inspections — PDF page 312

Source row Inspection category Inspection points Corrective action Checked (blank template)
1 Motor • Inspect for abnormal oscillation or noise coming from the motor. • Check the load coupling. • Measure motor vibration. • Tighten all loose components. ⟦blank source cell⟧
2 Cooling • Inspect for abnormal heat generated from the drive or motor and visible discoloration. • Check for excessive load. • Loose connections • Check for dirty heatsink or motor. • Ambient temperature ⟦blank source cell⟧
3 Cooling Fan • Inspect drive cooling fan operation. • Check for clogged or dirty fan. • Check fan operation drive parameter. ⟦blank source cell⟧
4 Environment • Verify the drive environment complies with the specifications listed in the Installation section of this manual. • Eliminate the source of contaminants or correct poor environment. ⟦blank source cell⟧
5 Load • The drive output current should not be higher than the motor or drive rating for an extended period of time. • Check for excessive load. • Check the motor parameter settings of the drive. ⟦blank source cell⟧
6 Power Supply Voltage • Check main power supply and control voltages. • Correct the voltage or power supply to within nameplate specifications. • Verify all main circuit phases. ⟦blank source cell⟧

Manual — Periodic inspection checklist — page 313

Source reference: SIEP C71060618F, December 2016, physical PDF page 313. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u Recommended Periodic Inspection

Table 7.2 outlines the recommended periodic inspections for Yaskawa drive installations. Periodic inspections should generally be checked every 3-6 months; however, the drive may require more frequent inspection due to poor environments or rigorous use. Operating and environmental conditions, along with experience in each application, will determine the actual inspection frequency for each installation. Periodic inspection will help to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection.

n Periodic Inspection

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

Table 7.2 Periodic Inspection Checklist

Inspection Area Inspection Points Corrective Action Checked Main Circuit Periodic Inspection

Motor Periodic Inspection

Control Circuit Periodic Inspection

Cooling System Periodic Inspection

LED Periodic Inspection

Note: Periodic inspections should be performed every one or two years. The drive, however, may require more frequent inspection due to poor environments or rigorous use.

7.2 Inspection

Periodic Inspection & Maintenance

Periodic Inspection — Main Circuit — blank Checked cells are template | General

Periodic Inspection — Main Circuit — blank Checked cells are template | Conductors and Wiring

Periodic Inspection — Main Circuit — blank Checked cells are template | Terminals

Periodic Inspection — Main Circuit — blank Checked cells are template | Relays and Contactors

Periodic Inspection — Main Circuit — blank Checked cells are template | Braking Resistors

Periodic Inspection — Motor — blank Checked cells are template | Operation Check

Periodic Inspection — Control Circuit — blank Checked cells are template | General

Periodic Inspection — Cooling System — blank Checked cells are template | Cooling Fan

Periodic Inspection — Cooling System — blank Checked cells are template | Heatsink

Periodic Inspection — Cooling System — blank Checked cells are template | Air Duct

Periodic Inspection — LED — blank Checked cells are template | LEDs

Periodic Inspection — Main Circuit — blank Checked cells are template — PDF page 313

Source row Inspection area Inspection points Corrective action Checked (blank template)
1 General • Overall check of the main power circuit and ground terminals Take appropriate actions (e.g., tightening loose connections). ⟦blank source cell⟧
2 General • Inspect equipment for discoloration from overheating or deterioration. • Inspect for damaged or deformed parts. • Replace damaged components as required. • The drive has few serviceable parts and may require complete drive replacement. ⟦blank source cell⟧
3 General • Inspect for dirt, foreign particles, or dust collection on components. • Inspect enclosure door seal if present. Replace components if cleaning is not possible. • Remove foreign particles and dust with a vacuum cleaner to avoid touching parts. ⟦blank source cell⟧
4 Conductors and Wiring • Inspect wiring and connections for discoloration, damage, or heat stress. • Inspect wire insulation and shielding for wear. • Repair or replace damaged wiring. ⟦blank source cell⟧
5 Terminals • Inspect terminals for stripped, damaged, or loose connections. • Tighten loose screws and replace damaged screws or terminals. ⟦blank source cell⟧
6 Relays and Contactors • Inspect contactors and relays for excessive noise during operation. • Inspect coils for signs of overheating such as melted or cracked insulation. • Check coil voltage for over or under voltage conditions. • Replace damaged removable relays contactors or circuit board. ⟦blank source cell⟧
7 Braking Resistors • Inspect for discoloration of heat stress on or around resistors. • Minor discoloration may be acceptable. • If discoloration exists check for loose connections. ⟦blank source cell⟧

Periodic Inspection — Motor — blank Checked cells are template — PDF page 313

Source row Inspection area Inspection points Corrective action Checked (blank template)
1 Operation Check • Check for increased vibration or abnormal noise. • Stop the motor and contact qualified maintenance personnel as required. ⟦blank source cell⟧

Periodic Inspection — Control Circuit — blank Checked cells are template — PDF page 313

Source row Inspection area Inspection points Corrective action Checked (blank template)
1 General • Inspect terminals for stripped, damaged or loose connections. • Check for tightness. • Tighten loose screws and replace damaged screws or terminals. • If terminals are integral to a circuit board then board or drive replacement may be required. ⟦blank source cell⟧

Periodic Inspection — Cooling System — blank Checked cells are template — PDF page 313

Source row Inspection area Inspection points Corrective action Checked (blank template)
1 Cooling Fan • Check for abnormal oscillation or unusual noise. • Check for damaged or missing fan blades. • Replace as required. • Refer to Drive Cooling Fans on page 316 for information on cleaning or replacing the cooling fan. ⟦blank source cell⟧
2 Heatsink • Inspect for dust or other foreign material collected on the surface. • Remove foreign particles and dust with a vacuum cleaner to avoid touching parts. ⟦blank source cell⟧
3 Air Duct • Inspect air intake and exhaust openings. They must be free from obstruction and properly installed. • Visually inspect the area. • Clear obstructions and clean air duct as required. ⟦blank source cell⟧

Periodic Inspection — LED — blank Checked cells are template — PDF page 313

Source row Inspection area Inspection points Corrective action Checked (blank template)
1 LEDs • Make sure the LED lights correctly. • Inspect for dust or other foreign material that may have collected on surrounding components. • Contact your Yaskawa representative if there is any trouble with the LED or keypad. • Clean the LED. ⟦blank source cell⟧

Manual — Estimated component life and monitors — page 314

Source reference: SIEP C71060618F, December 2016, physical PDF page 314. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

7.3 Periodic Maintenance

The drive has various "maintenance monitors." This feature provides advance maintenance warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to check the following maintenance periods. • Cooling Fan • Electrolytic Capacitors (Main Circuit) • Inrush Prevention Circuit • IGBT

u Replacement Parts

Table 7.3 contains the estimated performance life of components that require replacement during the life of the drive. Only use Yaskawa replacement parts for the appropriate drive model and revision.

Table 7.3 Estimated Performance Life

Component Estimated Performance Life

<1> The drive has few serviceable parts and may require complete drive replacement.

NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage conditions for estimated performance life: • Ambient temperature: Yearly average of 40 °C • Load factor: 80% maximum • Operation time: 24 hours a day

n Performance Life Monitors

The drive calculates the maintenance period for components that may require replacement during the life of the drive. A percentage of the maintenance period is displayed on the LED digital operator by viewing the appropriate monitor parameter. When the maintenance period reaches 100%, there is increased risk that the drive may malfunction. Yaskawa recommends checking the maintenance period regularly to ensure maximum performance life. Refer to Recommended Periodic Inspection on page 313 for more details.

Table 7.4 Performance Life Monitors Used for Component Replacement

Parameter Component Contents

Estimated Performance Life under stated annual average40°C,80%loadmaximum,24h/day conditions | Cooling Fan

Estimated Performance Life under stated annual average40°C,80%loadmaximum,24h/day conditions | Electrolytic Capacitors (Main Circuit)

Maintenance Monitors | U4-03

Maintenance Monitors | U4-04

Maintenance Monitors | U4-05

Maintenance Monitors | U4-06

Maintenance Monitors | U4-07

Estimated Performance Life under stated annual average40°C,80%loadmaximum,24h/day conditions — PDF page 314

Source row Component Estimated performance life
1 Cooling Fan 10 years
2 Electrolytic Capacitors (Main Circuit) 10 years <1>

Maintenance Monitors — PDF page 314

Source row Parameter Component Contents
1 U4-03 Cooling Fan Displays the accumulated operation time of the cooling fan, from 0 to 99999 hours. This value is automatically reset to 0 once it reaches 99999.
2 U4-04 Cooling Fan Displays the accumulated cooling fan operation time as a percentage of the specified maintenance period (displayed in percent %).
3 U4-05 Main Circuit (DC bus) Electrolytic Capacitors Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period.
4 U4-06 Inrush (pre-charge) relay Displays the number of times the drive is powered up as a percentage of the performance life of the inrush circuit.
5 U4-07 IGBT Displays the percentage of the maintenance period reached by the IGBTs.

Manual — Maintenance alarms and counter reset — page 315

Source reference: SIEP C71060618F, December 2016, physical PDF page 315. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

n Alarm Outputs for Maintenance Monitors

An output can be set up to inform the user when a specific components has neared its expected performance life. When one of multi-function digital output terminals has been assigned the maintenance monitor function (H2-□□ = 2F), the terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected performance life, or when the IGBTs have reached 50% of their expected performance life. Additionally the digital operator will display an alarm like shown in Table 7.5 to indicate the specific components that may need maintenance.

Table 7.5 Maintenance Alarms Digital Operator Alarm Display Function Corrective Action

<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2-□□ = 2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2-□□ = 10). <2> This alarm message will always be output, even if the Maintenance Monitor function is not assigned to any of the digital outputs (H2-□□ = 2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2-□□ = 10).

n Related Drive Parameters

Use parameters o4-03, o4-05, o4-07, and o4-09 to reset a Maintenance Monitor to zero after replacing a specific component. Refer to Parameter List on page 353 for details on parameter settings.

NOTICE: If these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will continue to count down the performance life from the value that was reached with the old part. If the Maintenance Monitor is not reset, the drive will not have the correct value of the performance life for the new component.

7.3 Periodic Maintenance

Periodic Inspection & Maintenance

Maintenance Alarms | <1>

Maintenance Alarms | LT-1 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.

Maintenance Alarms | LT-2 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.

Maintenance Alarms | LT-3 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.

Maintenance Alarms | LT-4 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.

Maintenance Alarms | <2>

Maintenance Alarms | TrPC <2>; visible seven-segment graphic beside literal code, exact segment geometry original-only.

Maintenance Alarms — PDF page 315

Source row Seven-segment graphic / footnote Literal alarm display Function Corrective action
1 LT-1 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. LT-1 The cooling fans have reached 90% of their designated life time. Replace the cooling fan.
2 LT-2 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. LT-2 The DC bus capacitors have reached 90% of their designated life time. Contact a Yaskawa representative or the nearest Yaskawa sales office on possible drive replacement.
3 LT-3 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. LT-3 The DC bus charge circuit has reached 90% of its designated life time. Contact a Yaskawa representative or the nearest Yaskawa sales office on possible drive replacement.
4 LT-4 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. LT-4 The IGBTs have reached 50% of their designated life time. Check the load, carrier frequency, and output frequency.
5 TrPC <2>; visible seven-segment graphic beside literal code, exact segment geometry original-only. TrPC The IGBTs have reached 90% of their designated life time. Contact a Yaskawa representative or the nearest Yaskawa sales office on possible drive replacement.

Manual — Cooling fan counts by model and class — page 316

Source reference: SIEP C71060618F, December 2016, physical PDF page 316. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

7.4 Drive Cooling Fans

NOTICE: Follow cooling fan replacement instructions. The cooling fan cannot operate properly when installed incorrectly and could seriously damage the drive. To ensure maximum useful product life, replace all cooling fans when performing maintenance. Contact your Yaskawa representative or supplier to order replacement cooling fans as required. Some drive models have multiple cooling fans. For drives with multiple cooling fans, replace all the fans when performing maintenance to ensure maximum useful product life.

u Number of Cooling Fans

Drive Model Cooling Fans Single-Phase 200 V Class

Three-Phase 200 V Class

Three-Phase 400 V Class

Cooling fans — Single-Phase 200 V Class | BA0001

Cooling fans — Single-Phase 200 V Class | BA0002

Cooling fans — Single-Phase 200 V Class | BA0003

Cooling fans — Single-Phase 200 V Class | BA0006

Cooling fans — Single-Phase 200 V Class | BA0010

Cooling fans — Single-Phase 200 V Class | BA0012

Cooling fans — Single-Phase 200 V Class | BA0018

Cooling fans — Three-Phase 200 V Class | 2A0001

Cooling fans — Three-Phase 200 V Class | 2A0002

Cooling fans — Three-Phase 200 V Class | 2A0004

Cooling fans — Three-Phase 200 V Class | 2A0006

Cooling fans — Three-Phase 200 V Class | 2A0010

Cooling fans — Three-Phase 200 V Class | 2A0012

Cooling fans — Three-Phase 200 V Class | 2A0020

Cooling fans — Three-Phase 200 V Class | 2A0030

Cooling fans — Three-Phase 200 V Class | 2A0040

Cooling fans — Three-Phase 200 V Class | 2A0056

Cooling fans — Three-Phase 200 V Class | 2A0069

Cooling fans — Three-Phase 400 V Class | 4A0001

Cooling fans — Three-Phase 400 V Class | 4A0002

Cooling fans — Three-Phase 400 V Class | 4A0004

Cooling fans — Three-Phase 400 V Class | 4A0005

Cooling fans — Three-Phase 400 V Class | 4A0007

Cooling fans — Three-Phase 400 V Class | 4A0009

Cooling fans — Three-Phase 400 V Class | 4A0011

Cooling fans — Three-Phase 400 V Class | 4A0018

Cooling fans — Three-Phase 400 V Class | 4A0023

Cooling fans — Three-Phase 400 V Class | 4A0031

Cooling fans — Three-Phase 400 V Class | 4A0038

Cooling fans — Single-Phase 200 V Class — PDF page 316

Source row Drive model Cooling fans
1 BA0001 –
2 BA0002 –
3 BA0003 –
4 BA0006 –
5 BA0010 1
6 BA0012 1
7 BA0018 2

Cooling fans — Three-Phase 200 V Class — PDF page 316

Source row Drive model Cooling fans
1 2A0001 –
2 2A0002 –
3 2A0004 –
4 2A0006 1
5 2A0010 1
6 2A0012 1
7 2A0020 1
8 2A0030 2
9 2A0040 2
10 2A0056 2
11 2A0069 2

Cooling fans — Three-Phase 400 V Class — PDF page 316

Source row Drive model Cooling fans
1 4A0001 –
2 4A0002 –
3 4A0004 –
4 4A0005 1
5 4A0007 1
6 4A0009 1
7 4A0011 1
8 4A0018 2
9 4A0023 2
10 4A0031 2
11 4A0038 2

Manual — Cooling fan removal and warnings — page 317

Source reference: SIEP C71060618F, December 2016, physical PDF page 317. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure 7.1 Remove the Cooling Fan Cover. A – Fan cover; B – Cooling fan; C – Tab. Illustration shows a single fan; removal step1 and all warnings retained outside this region. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

Figure 7.2 Disconnect and Remove the Fan. Removal step2 and electrical/burn warnings retained outside this region. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

u Cooling Fan Replacement

The cooling fan is installed on the top of the drive. The cooling fan can easily be replaced without tools or removal of the drive or enclosure parts.

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled down.

n Removing the Cooling Fan 1. Depress the right and left sides of the fan cover tabs and pull upward. Remove the fan cover from the top of the drive. The following figure illustrates a drive with a single cooling fan.

  1. Remove the fan cable carefully, disconnect the pluggable connector and remove the fan.

7.4 Drive Cooling Fans

Periodic Inspection & Maintenance

Manual — Cooling fan installation — page 318

Source reference: SIEP C71060618F, December 2016, physical PDF page 318. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure 7.3 Cooling Fan Orientation. A – Label facing up; B – Back; C – Front. Installation step1 and notice retained outside this region. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

Figure 7.4 Connectors. A – Push the connectors together so no space remains between them. Step2 separately retains proper connection and cable recess instruction. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

n Installing the Cooling Fan

NOTICE: Prevent Equipment Damage. Follow cooling fan replacement instructions. Improper cooling fan replacement could result in damage to equipment. When installing the replacement cooling fan into the drive, make sure the fan is facing upwards. To ensure maximum useful product life, replace all cooling fans when performing maintenance. 1. Install the replacement cooling fan into the drive, ensuring the alignment pins line up, as shown in the figure below:

  1. Ensure the connectors are properly connected and place the cable back into the recess of the drive.

Note: Ensure that the left and right tabs are locked back into place. 3. Align the left and right cover tabs to install the fan cover back on the top of the drive.

7.4 Drive Cooling Fans

Manual — Drive replacement and terminal board — page 319

Source reference: SIEP C71060618F, December 2016, physical PDF page 319. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure 7.5 Terminal Board. A – Charge LED; B – Terminal Board Locking Pin; C – Removable Terminal Board. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

7.5 Drive Replacement

u Serviceable Parts

The drive contains few serviceable parts. The following parts are considered replacement parts on the drive: • Main control board and I/O Terminal board I/O PCBs. • Cooling fan(s) • Front cover Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa representative before replacing parts if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa warranty policy.

WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

u Terminal Board Overview

The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains on-board memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the replacement drive by disconnecting the terminal board from the damaged drive then reconnecting the terminal board to the replacement drive. There is no need to manually reprogram the replacement drive.

Note: When transferring the removable terminal block with backup memory to a drive with a different voltage class or different output capacity, set A1-03 to 2220 to initialize the drive after installing the terminal block.

u Dismantling the Removable Terminal Block

WARNING! Electrical Shock Hazard. Never connect or disconnect wiring, remove connectors or option cards, or replace the cooling fan while the power is on. Failure to comply may result in serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off.

WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives.

NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. 1. Loosen the screw on the front of the drive and remove the front cover.

Periodic Inspection & Maintenance

Manual — Terminal board dismantling continuation — page 320

Source reference: SIEP C71060618F, December 2016, physical PDF page 320. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure 7.6 Remove the Front Cover. Step1 is on PDF319; warnings and ESD requirements remain applicable. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

Figure 7.7 Pull Out the Ground Terminal. Source callout: Pull out the ground terminal pin in the direction indicated by the arrow. Labels: Cable; Terminal. Step2 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

Figure 7.8 Depress the Plastic Tab. Source callout: Push down the terminal board locking pin with a screwdriver. Step3 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

  1. Pull the pin on the ground terminal out of the removable terminal block.

  2. Push down the installation pin on the terminal board with a screwdriver

  3. While holding down the locking pin from step 3, slide the removable terminal block in the direction of the arrows in

Figure 7.9.

7.5 Drive Replacement

Manual — Terminal board removal and reinstallation — page 321

Source reference: SIEP C71060618F, December 2016, physical PDF page 321. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure 7.9 Remove the Terminal Board. Step4 on PDF320 refers to arrows in this figure. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

Figure 7.10 Removable Terminal Board Disconnected from the Drive. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

Figure 7.11 Terminal Board Reinstallation. Source callout: Place the terminal board below the guide tracks in the plastic case of the drive. Then push it gently down and slide it toward the keypad until the locking pin clicks into place. Reinstallation step1 and step2 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

n Reinstalling the Terminal Board 1. Reinstall the removable terminal block on the drive according to Figure 7.11.

  1. Ensure the terminal block is firmly fastened to the connector.

7.5 Drive Replacement

Periodic Inspection & Maintenance

Manual — Terminal board reinstallation and parameter transfer — page 322

Source reference: SIEP C71060618F, December 2016, physical PDF page 322. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure 7.12 Terminal Board Reinstalled. Label: Connector. Reinstallation steps3–5 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

  1. Put the lower cover and the terminal cover back in place. 4. After replacing the drive, check the drive unit selection setting in o2-04. Refer to Defaults by Drive Model and Duty Rating (ND/HD) on page 409 for more information. 5. An oPE04 error may occur when replacing the drive or the removable terminal block. If the data saved to the terminal block is compatible, set A1-03 to 5550 to write the parameter settings stored in the terminal block to the new drive. Reset the appropriate maintenance monitors using parameters o4-01 to o4-13.

u Details on Terminal Board (TB) or Control Board (CNT) Replacement

The drive Terminal Board retains drive parameter settings to significantly improve the ease of drive replacement. Refer to Troubleshooting Terminal Board or Control Board Replacement on page 323 for a flowchart to assist in board replacement. When replacing the drive, or changing the Control Board or Terminal Board, the following error codes may be encountered upon application of power: • oPE04 Drive parameter settings need to be initialized or uploaded from the TB. • CPF06 Drive specification does not match the replaced drive. • oPE01 Drive parameter o2-04 kVA requires setting. Procedural Notes: 1. When replacing the drive, control board or terminal board, make sure to confirm the kVA setting, parameter o2-04 is correct upon initial power-up. 2. Perform an initialization (via parameter A1-03) to obtain the desired parameter settings. 3. In cases where a previously programmed terminal board is retained, initializing the drive with a setting of A1-03 = 5550 may be desired to program the drive with previously programmed settings (settings used prior to replacing the drive or control board).

7.5 Drive Replacement

Manual — Terminal board replacement fault flowchart — page 323

Source reference: SIEP C71060618F, December 2016, physical PDF page 323. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Figure 7.13 Troubleshooting Terminal Board or Control Board Replacement. START: CPF06 fault displayed upon drive replacement? YES → initialize A1-03=2220 or3330, then Ready. NO → fault oPE01? YES → set o2-04 to match drive nameplate rating, then oPE04 decision; NO → oPE04 decision. Note: Drive kVA Setting o2-04="FF" inside a new Terminal Board. Fault oPE04? NO → Ready. YES → drive parameter settings need initialization or upload from TB; initialize using A1-03: set2220 or3330 → Ready; set5550 → parameter setting values copied TB to CNT → Ready. Ready → END. These are literal visible branch labels, not inferred wiring or authorization to initialize equipment. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.

7.5 Drive Replacement

Periodic Inspection & Maintenance

Manual — Peripheral safety — page 326

Source reference: SIEP C71060618F, December 2016, physical PDF page 326. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

8.1 Section Safety

DANGER

Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Disconnect all power to the drive, wait at least five minutes after all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc.

WARNING

Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work on the drive. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not change wiring or remove option unit while power is running through the drive. Failure to comply could result in death or serious injury. Disconnect all power to the drive and check for unsafe voltages before servicing. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive.

Manual — Options and models — page 327

Source reference: SIEP C71060618F, December 2016, physical PDF page 327. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

8.2 Drive Options and Peripheral Devices

The following table of peripheral devices lists the names of the various devices/options available for Yaskawa drives. Contact Yaskawa or your Yaskawa agent to order these peripheral devices. • Peripheral Device Selection: Refer to Yaskawa catalog for selection and part numbers. • Peripheral Device Installation: Refer to option manual for option installation instructions.

Table 8.1 Available Peripheral Devices

Option Model Number Description Power Options

Interface Options

Mechanical Options

Others

Communication Options

& Devices Peripheral Options

Power Options | Option

Power Options | Model number

Power Options | Description

Interface Options | Option

Interface Options | Model number

Interface Options | Description

Mechanical Options | Option

Mechanical Options | Model number

Mechanical Options | Description

Others | Option

Others | Model number

Others | Description

Communication Options | Option

Communication Options | Model number

Communication Options | Description

Power Options — PDF page 327

Source row Option Model number Description
1 DC Link Choke UZDA Series DC link choke to improve power factor
2 AC Reactor UZBA Series AC reactor to improve power factor
3 Braking Resistor ERF-150WJ Series 3% ED, 150 W braking resistor
4 Braking Chopper CDBR Series External braking transistor
5 Surge Absorber 200 V class: DCR2-□A 400 V class: RFN3AL-504KD Suppresses surge voltage caused by switching magnetic contactors
6 Molded Case Circuit Breaker NF Series Circuit breaker for short circuit or overload protection Note: Yaskawa recommends installing an MCCB to the power supply side to protect drive wiring and to prevent other damage in the event of component failure. Install an MCCB if permitted by the power system.
7 Ground Fault Circuit Interrupter (GFCI) NV, EG, or SG Series Provides protection against potentially harmful leakage currents Note: Yaskawa recommends installing a GFCI to the power supply side to protect drive wiring and to prevent other damage in the event of component failure. An MCCB can also be used if permitted by the power system.
8 Magnetic Contactor (Input) SC Series Prevents potential damage to the braking resistor and other internal circuitry by ensuring that power to drive is completely shut off when necessary. Install an MCCB when using a braking resistor to prevent the braking resistor from overheating. Wire the MC so that it opens when a fault output terminal is triggered to protect internal components from sudden high levels of input current.

Interface Options — PDF page 327

Source row Option Model number Description
1 Remote LCD Operator JVOP-180 Remote operator with 8 languages clear text LCD display and copy function; Cable length max. 3 m
2 USB/Copy Unit JVOP-181 Allows the user to copy and verify parameter settings between drives. Can also be used as adapter to connect the drive to a PC USB port

Mechanical Options — PDF page 327

Source row Option Model number Description
1 Heatsink External Mounting Attachment EZZ020568□ Installation kit for mounting the drive with the heatsink outside of the panel (side-by-side mounting possible)
2 DIN Rail Attachment EZZ08122□ Installation kit for mounting the drive on a DIN rail
3 NEMA Type 1 Kit <1> EZZ020564□ Parts to make the drive conform to NEMA Type 1 enclosure

Others — PDF page 327

Source row Option Model number Description
1 24 Vdc Control Power Supply Option PS-V10□ Provides power to the control circuit and option boards in the event of a power loss. Allows the user to monitor drive settings and fault information when the main circuit has no power.
2 Drive Wizard Plus — PC tool for drive setup and parameter management The installation files can be obtained at no charge from: http://www.yaskawa.com
3 DriveWorksEZ — PC tool for enhanced programming of the drive

Communication Options — PDF page 327

Source row Option Model number Description
1 CANopen Communications Option SI-S3/V Connects to a CANopen network
2 CC-Link Communications Option SI-C3/V Connects to a CC-Link network

Manual — Communication options and kit footnote — page 328

Source reference: SIEP C71060618F, December 2016, physical PDF page 328. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Option Model Number Description

<1> Available for models: BA0001 to BA0018, 2A0001 to 2A0020, and 4A0001 to 4A0011.

8.2 Drive Options and Peripheral Devices

Communication options continued from PDF327 | Option

Communication options continued from PDF327 | Model number

Communication options continued from PDF327 | Description

Communication options continued from PDF327 — PDF page 328

Source row Option Model number Description
1 CompoNet Communications Option SI-M3/V Connects to a CompoNet network
2 DeviceNet Communications Option SI-N3/V Connects to a DeviceNet network
3 EtherCAT Communications Option SI-ES3/V Connects to an EtherCAT network
4 EtherNet/IP Communications Option SI-EN3/V Connects to an EtherNet/IP network
5 MECHATROLINK-II Communications Option SI-T3/V Connects to a MECHATROLINK-II network
6 MECHATROLINK-III Communications Option SI-ET3/V Connects to a MECHATROLINK-III network
7 Modbus TCP/IP Communications Option SI-EM3/V Connects to a Modbus/TCP network
8 PROFIBUS-DP Communications Option SI-P3/V Connects to a PROFIBUS-DP network
9 PROFINET Communications Option SI-EP3/V Connects to a PROFINET network

Manual — Peripheral connection overview — page 329

Source reference: SIEP C71060618F, December 2016, physical PDF page 329. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Labels: Power supply; Line breaker(MCCB) or Leakage breaker; Surge absorber; AC reactor; Input side noise filter; DC link choke; Drive; Ground; Output side noise filter; Motor; Magnetic Contactor(MC); Braking resistor unit;24V power supply option;24V option connector;B1,B2;R/L1,S/L2,T/L3,U/T1,V/T2,W/T3,+1,+2. USB Copy Unit(RJ-45/USB adapter),RJ-45 cable,USB cable,Dedicated cable(RJ-45/D-sub adapter),PC;Engineering software tools DriveSelect,DriveWizard,DriveWorksEZ. Incidental JVOP-181 labels:Copy,Verify,Read,LOCK,USB Copy Unit,COM,ERR,YASKAWA. Figure8.1 Connecting Peripheral Devices. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

8.3 Connecting Peripheral Devices

Figure 8.1 illustrates how the drive and motor connect together with various peripheral devices. Refer to peripheral device option manual for detailed installation instructions.

<1> NOTICE: Do not connect the LAN port on a PC and the comm. port of the drive. Failure to comply may damage the drive and the PC.

Note: If the drive is set to trigger an output terminal when performing a fault restart (L5-02 = 1), the power supply will be shut off during fault restart as the drive outputs a fault signal. Keep this in mind when designing a wiring sequence to interrupt the power to the drive. The default setting for the drive is to not trigger an output terminal that indicates a fault restart is being performed (L5-02 = 0).

& Devices Peripheral Options

Manual — Protection and breakers — page 330

Source reference: SIEP C71060618F, December 2016, physical PDF page 330. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

8.4 Installing Peripheral Devices

This section describes the proper steps and precautions to take when installing or connecting various peripheral devices to the drive. Refer to peripheral device manual for detailed installation instructions.

NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation due to improper power supply.

u Installing a Molded Case Circuit Breaker (MCCB) and Earth Leakage Circuit Breaker (ELCB)

Install an MCCB or ELCB for line protection between the power supply and the main circuit power supply input terminals R/ L1, S/L2 and T/L3. This protects the main circuit and devices wired to the main circuit while also providing overload protection. Consider the following when selecting and installing an MCCB or ELCB: • The rated current of the MCCB or ELCB should be 1.5 to 2 times the rated output current of the drive. Use an MCCB or ELCB with operation characteristics that do not trip the MCCB or ELCB faster than the drive overload protection (shuts off the drive after 1 minute of operation at 150% of the drive rated current). • If several drives are connected to one MCCB or an ELCB that is shared with other equipment, use a sequence that shuts the power OFF when errors are output by using magnetic contactor (MC) as shown in the following figure.

Drive

Power Supply

R/L1

MB

MCCB MC

MC

S/L2 T/L3

SA

Figure 8.2 Connecting an MCCB

WARNING! Electrical Shock Hazard. Disconnect the MCCB (or ELCB) and MC before wiring terminals. Failure to comply may result in serious injury or death.

u Installing a Leakage Breaker

Drive outputs generate high-frequency leakage current as a result of high-speed switching. Install a GFCI on the input side of the drive to switch off potentially harmful leakage current. Factors in determining leakage current: • Size of the AC drive • AC drive carrier frequency • Motor cable type and length • EMI/RFI filter If the GFCI trips spuriously, consider changing these items or use a GFCI with a higher trip level.

Note: Choose a GFCI designed specifically for an AC drive. The operation time should be at least 0.1 s with sensitivity amperage of at least 200 mA per drive. The output waveform of the drive may cause an increase in leakage current. This may in turn cause the leakage breaker to malfunction. Increase the sensitivity amperage or lower the carrier frequency to correct the problem.

Manual — Magnetic contactors and reactors — page 331

Source reference: SIEP C71060618F, December 2016, physical PDF page 331. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A Power supply;B MCCB;C AC reactor;D Drive. Source terminals U,V,W,X,Y,Z,R/L1,S/L2,T/L3. Figure8.3 Connecting an AC Reactor. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

u Installing a Magnetic Contactor

n Disconnecting the Power Supply

The drive should be shut off in the case of a fault in external equipment such as braking resistors through use of a Magnetic Contactor (MC).

NOTICE: Do not connect electromagnetic switches or MCs to the output motor circuits without proper sequencing. Improper sequencing of output motor circuits may cause damage to the drive.

NOTICE: Install an MC on the input side of the drive when the drive should not automatically restart after power loss. To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the MC more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.

Note: 1. Install an MC to the drive output to prevent the drive from restarting automatically when the power is restored after momentary power loss. 2. Set up a delay for the MC so that it does not open prematurely for the drive to continue operating through momentary power loss.

n Protecting the Braking Resistor or Braking Resistor Unit

Use an MC on the input side of the drive to protect a braking resistor or braking resistor unit from overheat or fire.

WARNING! Fire Hazard. When using a braking unit, use a thermal relay on the braking resistors and configure a fault contact output for the braking resistor unit to disconnect drive main power via an input contactor. Inadequate braking circuit protection could result in death or serious injury by fire from overheating resistors.

u Connecting an AC Reactor or DC Link Choke

AC reactors and DC link chokes suppress surges in current and improve the power factor on the input side of the drive. Use an AC reactor, DC link choke, or both: • To suppress harmonic current or improve the power factor of the power supply. • When using a phase advancing capacitor switch. • With a large capacity power supply transformer (over 600 kVA).

Note: Use an AC reactor or DC link choke when also connecting a thyristor converter (such as a DC drive) to the same power supply system, regardless of the conditions of the power supply.

n Connecting an AC Reactor

8.4 Installing Peripheral Devices

& Devices Peripheral Options

Manual — DC choke and input filter — page 332

Source reference: SIEP C71060618F, December 2016, physical PDF page 332. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A Power supply;B MCCB;C Drive;D DC link choke. Terminals R/L1,S/L2,T/L3,+1,+2. Figure8.4 Connecting a DC Link Choke. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

A Power supply;B Input-side noise filter(Model LNFB-□□);C Drive;D Other control device. MCCB;R/L1,S/L2;filter labels1,2,3,4,E. Figure8.5 Input-Side Noise Filter(Single-Phase200V). Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

n Connecting a DC Link Choke

Ensure the jumper between terminals +1 and +2 (terminals are jumpered for shipment) is removed when connecting a DC link choke. The jumper must be installed if no DC link choke is used. Refer to Connecting a DC Link Choke on page 332 for an example of DC link choke wiring.

u Connecting a Surge Suppressor

A surge suppressor suppresses transient voltages generated from switching an inductive load near the drive. Inductive loads include magnetic contactors, relays, valves, solenoids and brakes. Always use a surge suppressor or diode when operating with an inductive load.

Note: Never connect a surge suppressor to the drive output.

u Connecting a Noise Filter

n Input-Side Noise Filter

Drive outputs generate noise as a result of high-speed switching. This noise flows from inside the drive back toward the power supply, possibly affecting other equipment. Installing a noise filter to the input side of the drive can reduce the amount of noise flowing back into the power supply. This also prevents noise from entering the drive from the power supply. • Use a noise filter specifically designed for AC drives. • Install the noise filter as close as possible to the drive.

8.4 Installing Peripheral Devices

Manual — Input and output filtering — page 333

Source reference: SIEP C71060618F, December 2016, physical PDF page 333. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A Power supply;B Input-side noise filter(Model LNFD-□□);C Drive;D Other control device. MCCB;R,L1 terminal shown R/L1;S/L2,T/L3;filter R,S,T,U,V,W,E. Figure8.6 Input-Side Noise Filter(Three-Phase200/400V). Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

A Power supply;B Drive;C Output-side noise filter;D Motor. MCCB;R/L1,S/L2,T/L3,U/T1,V/T2,W/T3;filter labels1,2,3,4,5,6. Figure8.7 Output-Side Noise Filter. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

Refer to EMC Filter Installation on page 469 for details about EMC filter selection and installation in order to make the drive compliant with European standards EN 61800-3:2004/A1:2012 and the EMC guidelines.

n Output-Side Noise Filter

A noise filter on the output side of the drive reduces inductive noise and radiated noise. Figure 8.7 illustrates an example of output-side noise filter wiring.

NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper application of noise filters could result in damage to the drive.

• Radiated Noise: Electromagnetic waves radiated from the drive and cables create noise throughout the radio bandwidth that can affect devices. • Induced Noise: Noise generated by electromagnetic induction can affect the signal line and may cause the controller to malfunction.

Preventing Induced Noise Use a noise filter on the output side or use shielded cables. Lay the cables at least 30 cm away from the signal line to prevent induced noise.

8.4 Installing Peripheral Devices

& Devices Peripheral Options

Manual — Noise suppression and reactor passes — page 334

Source reference: SIEP C71060618F, December 2016, physical PDF page 334. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A Power supply;B Drive;C Shielded motor cable;D Motor;E Separate at least30cm;F Controller;G Signal line. MCCB,R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Figure8.8 Preventing Induced Noise. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

A Metal enclosure;B Power supply;C Noise filter;D Drive;E Noise filter;F Shielded motor cable;G Motor. MCCB,R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Figure8.9 Reducing Radio Frequency Noise. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

A Power supply;B MCCB;C Zero-phase reactor on input side;D Drive;E Zero-phase reactor on output side;F Motor. R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Close-up of V/T2-phase wiring:1st pass,2nd pass,3rd pass,4th pass. Pass each wire(U/T1,V/T2,W/T3)through the core4times. Figure8.10 Zero-Phase Reactor. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

Reducing Radiated/Radio Frequency Noise The drive, input lines, and output lines generate radio frequency noise. Use noise filters on input and output sides and install the drive in a metal enclosure panel to reduce radio frequency noise.

Note: The cable running between the drive and motor should be as short as possible.

u EMC Filter Installation

This drive is tested according to European standards IEC/EN 61800-5-1 and it complies with the EMC guidelines. Refer to EMC Filter Installation on page 469 for details about EMC filter selection and installation.

u Zero-Phase Reactor

A zero-phase reactor can be used to reduce the noise on the input and output sides of the drive.

8.4 Installing Peripheral Devices

Manual — Fuses heatsinks and thermal relays — page 335

Source reference: SIEP C71060618F, December 2016, physical PDF page 335. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u Installing Fuses on the Input Side

Always install input fuses to the input side of the as a protective measure against damage caused by a short circuit. Refer to Standards Compliance on page 463 for details on input fuse selection.

u Attachment for External Heatsink

An external attachment can be used to project the heatsink outside of an enclosure to ensure that there is sufficient air circulation around the heatsink. This installation method still requires a certain amount of airflow over the drive case. Refer to Output Current Derating Due to Ambient Temperature on page 351 if derating is required. Contact a Yaskawa sales representative for more information.

u Noise Filter Installation

This drive has undergone testing in conformance with IEC/EN 61800-5-1 and is in compliance with low voltage directives. Refer to EMC Guidelines Compliance on page 469 for information on selecting a noise filter.

u Installing a Motor Thermal Overload (oL) Relay on the Drive Output

Motor thermal overload relays protect the motor by disconnecting power lines to the motor due to a motor overload condition. Install a motor thermal overload relay between the drive and motor: • When operating multiple motors on a single AC drive. • When using a power line bypass to operate the motor directly from the power line. It is not necessary to install a motor thermal overload relay when operating a single motor from a single AC drive. The AC drive has UL recognized electronic motor overload protection built into the drive software.

Note: Disable the motor protection function (L1-0 1 = “0”) when using an external motor thermal overload relay. The relay should shut off main power on the input side of the main circuit when triggered.

n General Precautions when Using Thermal Overload Relays

The following application precautions should be considered when using motor thermal overload relays on the output of AC drives in order to prevent nuisance trips or overheat of the motor at low speeds: • Low speed motor operation • Use of multiple motors on a single AC drive • Motor cable length • Nuisance tripping resulting from high AC drive carrier frequency

Low Speed Operation and Motor Thermal oL Relays Generally, thermal relays are applied on general-purpose motors. When general-purpose motors are driven by AC drives, the motor current is approximately 5 to 10% greater than if driven by the commercial power supply. In addition, the cooling capacity of a motor with a shaft-driven fan decreases when operating at low speeds. Even if the load current is within the motor rated value, motor overheating may occur. A thermal relay cannot effectively protect the motor due to the reduction of cooling at low speeds. For this reason, apply the UL recognized electronic thermal overload protection function built into the drive whenever possible. UL recognized electronic thermal overload function of the drive: Speed-dependent heat characteristics are simulated using data from standard motors and force-ventilated motors. The motor is protected from overload using this function.

Using One Drive with Multiple Motors Turn off the electronic thermal overload function. Please refer to the appropriate product instruction manual to determine which parameter disables this function. The UL recognized electronic thermal overload function of the drive cannot be applied when using multiple motors on one drive.

Long Motor Cables When long motor cables and high carrier frequency are used, nuisance tripping of the thermal relay may occur due to increased leakage current. Therefore, reduce the carrier frequency or increase the tripping level of the thermal overload relay.

Nuisance Tripping Resulting from High AC Drive Carrier Frequency Current waveforms generated by high carrier frequency PWM drives tend to create additional temperature rise in overload relays. Therefore, it may be necessary to increase the trip level setting when encountering nuisance triggering of the relay.

8.4 Installing Peripheral Devices

& Devices Peripheral Options

Manual — Thermal relay fire warning — page 336

Source reference: SIEP C71060618F, December 2016, physical PDF page 336. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

WARNING! Fire Hazard. Confirm an actual motor overload condition is not present prior to increasing the thermal oL trip setting. Check local electrical codes before making adjustments to motor thermal overload settings.

8.4 Installing Peripheral Devices

Manual — Communication card options — page 337

Source reference: SIEP C71060618F, December 2016, physical PDF page 337. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

8.5 Communication Options

Table 8.2 gives detailed information about the available options that allow Yaskawa drives to connect to communication networks. A host controller can control and monitor the drive, read and change parameters by using a communication option. Contact Yaskawa or your Yaskawa agent to order options. • Option Selection: Refer to Yaskawa catalog for more details on option selection and part numbers. • Option Installation: Refer to option manual for option installation instructions.

Table 8.2 Available Communication Options

Option Model Function

& Devices Peripheral Options

Available communication options | Option

Available communication options | Model

Available communication options | Function

Available communication options — PDF page 337

Source row Option Model Function
1 PROFIBUS-DP Communications Option SI-P3/V Connects to a PROFIBUS-DP network
2 CC-Link Communications Option SI-C3/V Connects to a CC-Link network
3 DeviceNet Communications Option SI-N3/V Connects to a DeviceNet network
4 CompoNet Communications Option SI-M3/V Connects to a CompoNet network
5 CANopen Communications Option SI-S3/V Connects to a CANopen network
6 EtherNet/IP Communications Option SI-EN3/V Connects to an EtherNet/IP network
7 MECHATROLINK-II Communications Option SI-T3/V Connects to a MECHATROLINK-II network
8 MECHATROLINK-III Communications Option SI-ET3/V Connects to a MECHATROLINK-III network
9 EtherCAT Communications Option SI-ES3/V Connects to an EtherCAT network
10 PROFINET Communications Option SI-EP3/V Connects to a PROFINET network
11 Modbus TCP/IP Communications Option SI-EM3/V Connects to a Modbus TCP network

Manual — Option card installation — page 338

Source reference: SIEP C71060618F, December 2016, physical PDF page 338. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A Option card;B Option card cover installation screw holes;C Tabs for mounting front cover;D Comm.connector(CN1);E Ground lead connection screw holes;F Wire through-hole;G Option card cover;H Cover screw;I Ground lead. Figure8.11 Option Card. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

Figure8.12 Remove Cover; full numberedstep1 separately retained. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

A Ground terminal;B Ground lead;C Terminal cover. Figure8.13 Connect Lead; full numberedstep2 separately retained. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

8.6 Connecting an Option Card

The drive can communicate with other devices through a specially designed option card. The following section describes how to install an option card. Refer to option card manual for detailed installation instructions.

Note: Refer to Available Communication Options on page 337 for a list of option cards for use with this product.

u Verifying the Option Card and Product Type

u Connecting the Option Card 1. Loosen the screw on the front cover of the drive to remove the cover.

  1. Remove the terminal cover. Connect the lead from the option card to the drive ground terminal.

  2. Reattach the terminal cover.

Manual — Option card installation continuation — page 339

Source reference: SIEP C71060618F, December 2016, physical PDF page 339. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A Line up the tab with the mounting hole;B Line up the tab with the mounting hole. Figure8.14 Attach Option Card. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

A Drive ground terminal;B Route the lead wire on the inside of the lower cover;C Ground lead;D Ground lead through-hole;E Ground lead. Figure8.15 Lead Wire Connection. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

A Align the tab with the mounting hole. Figure8.16 Reattach Cover. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.

  1. Attach the option card to the drive.

Note: Gently pack wires to fit behind the left and right side of the cover into the provided recess. 5. Connect the lead from the drive ground terminal to the same terminal as the option card lead.

The option card lead should exit through the holes provided on the underside of the drive as it gets routed passed the ground terminal.

  1. Reattach the option card cover.

8.6 Connecting an Option Card

& Devices Peripheral Options

Manual — Heavy and normal duty — page 342

Source reference: SIEP C71060618F, December 2016, physical PDF page 342. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A.1 Heavy Duty and Normal Duty Ratings

The capacity of the drive is based on two types of load characteristics: Heavy Duty (HD) and Normal Duty (ND). Refer to Selecting the Appropriate Load Rating on page 342 for the differences between HD and ND. Specifications for capacity ratings are listed on the following pages.

Table A.1 Selecting the Appropriate Load Rating

Setting Parameter Rated Output Current Overload Tolerance Default Carrier Frequency C6-01

<1> The following pages list information on rating changes based on drive model.

TERMS • HD and ND: HD refers to applications requiring constant torque output, while ND refers to applications with variable torque needs. The drive allows the user to select HD or ND torque depending on the application. Fans, pumps, and blowers should use ND (C6-01 = 1), and other applications generally use HD (C6-01 = 0). • Swing PWM: Swing PWM equivalent to a 2 kHz audible noise. This function turns the motor noise into a less obtrusive white noise.

Note: Differences between HD ratings and ND ratings for the drive include rated input and output current, overload capacity, carrier frequency, and current limit. The default setting is for ND (C6-01 = 1).

Selecting the appropriate load rating | Setting parameter C6-01

Selecting the appropriate load rating | Rated output current

Selecting the appropriate load rating | Overload tolerance

Selecting the appropriate load rating | Default carrier frequency

Selecting the appropriate load rating — PDF page 342

Source row Setting parameter C6-01 Rated output current Overload tolerance Default carrier frequency
1 0: Heavy Duty HD Rating varies by model <1> 150% rated output current for 60 s 8/10 kHz varies by model
2 1: Normal Duty (default) ND Rating varies by model <1> 120% rated output current for 60 s varies by model 2 kHz, Swing PWM

Manual — 200 V small frame ratings — page 343

Source reference: SIEP C71060618F, December 2016, physical PDF page 343. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A.2 Single/Three-Phase 200 V Class Drives

Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to 0 for HD or 1 for ND (default).

Table A.2 Power Ratings

Item Specification Three-Phase Drive Model 2A0001 2A0002 2A0004 2A0006 2A0010 2A0012 2A0020

Single-Phase Drive Model <1> BA0001 BA0002 BA0003 BA0006 BA0010 BA0012 BA0018

Maximum Motor Size Allowed (HP)

<3>

ND Rating

HD Rating

Input Current Input <4> (A)

Three- phase

Single- phase

ND Rating HD Rating

Output

Rated Output Capacity (kVA) <5>

ND Rating <6> Output Current (A)

Overload Tolerance Carrier Frequency

Max Output Voltage (V) Max Output Frequency (Hz)

Power Supply

Rated Voltage Rated Frequency

Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective DC Link Choke Actions

<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor. <2> 2A0020 only. BA0018 is available with a Heavy Duty rating only. <3> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <4> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance. <5> Rated motor capacity is calculated with a rated output voltage of 230 V. <6> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier frequency. <7> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency. <8> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency. <9> DC is not available for UL standards.

A

Specifications

Actual physical source row; model columns 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0001 / BA0001

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0002 / BA0002

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0004 / BA0003

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0006 / BA0006

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0010 / BA0010

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0012 / BA0012

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0020 / BA0018

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0001 / BA0001

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0002 / BA0002

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0004 / BA0003

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0006 / BA0006

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0010 / BA0010

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0012 / BA0012

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0020 / BA0018

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0001 / BA0001

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0002 / BA0002

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0004 / BA0003

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0006 / BA0006

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0010 / BA0010

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0012 / BA0012

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0020 / BA0018

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0001 / BA0001

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0002 / BA0002

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0004 / BA0003

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0006 / BA0006

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0010 / BA0010

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0012 / BA0012

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0020 / BA0018

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0001 / BA0001

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0002 / BA0002

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0004 / BA0003

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0006 / BA0006

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0010 / BA0010

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0012 / BA0012

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0020 / BA0018

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0001 / BA0001

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0002 / BA0002

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0004 / BA0003

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0006 / BA0006

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0010 / BA0010

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0012 / BA0012

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0020 / BA0018

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0001 / BA0001

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0002 / BA0002

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0004 / BA0003

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0006 / BA0006

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0010 / BA0010

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0012 / BA0012

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0020 / BA0018

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0001 / BA0001

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0002 / BA0002

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0004 / BA0003

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0006 / BA0006

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0010 / BA0010

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0012 / BA0012

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0020 / BA0018

Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0001 / BA0001

Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0002 / BA0002

Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0004 / BA0003

Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0006 / BA0006

Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0010 / BA0010

Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0012 / BA0012

Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0020 / BA0018

Power ratings 200 V — Output Current (A) | HD Rating | 2A0001 / BA0001

Power ratings 200 V — Output Current (A) | HD Rating | 2A0002 / BA0002

Power ratings 200 V — Output Current (A) | HD Rating | 2A0004 / BA0003

Power ratings 200 V — Output Current (A) | HD Rating | 2A0006 / BA0006

Power ratings 200 V — Output Current (A) | HD Rating | 2A0010 / BA0010

Power ratings 200 V — Output Current (A) | HD Rating | 2A0012 / BA0012

Power ratings 200 V — Output Current (A) | HD Rating | 2A0020 / BA0018

Power ratings 200 V — Overload Tolerance | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Carrier Frequency | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Max Output Voltage (V) | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Max Output Frequency (Hz) | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Allowable Voltage Fluctuation | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Allowable Frequency Fluctuation | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 0.13 0.25 0.5/ 0.75 1.0/ 1.5 2.0/ 3.0 3.0 5.0 <2>

Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 0.13 0.25 0.5 0.75/ 1.0 1.5/ 2.0 3.0 5.0

Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 1.1 1.9 3.9 7.3 10.8 13.9 24.0 <2>

Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 0.7 1.5 2.9 5.8 7.5 11.0 18.9

Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 2.0 3.6 7.3 13.8 20.2 24.0 –

Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 1.4 2.8 5.5 11.0 14.1 20.6 35.0

Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 0.5 0.7 1.3 2.3 3.7 4.6 7.5 <2>

Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 0.3 0.6 1.1 1.9 3.0 4.2 6.7

Power ratings 200 V — Output Current (A) | ND Rating <6> — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 1.2 1.9 3.5 (3.3) 6.0 9.6 12.0 19.6 <2>

Power ratings 200 V — Output Current (A) | HD Rating — PDF page 343

Source row 2A0001 / BA0001 2A0002 / BA0002 2A0004 / BA0003 2A0006 / BA0006 2A0010 / BA0010 2A0012 / BA0012 2A0020 / BA0018
1 0.8 <7> 1.6 <7> 3.0 <7> 5.0 <7> 8.0 <8> 11.0 <8> 17.5 <8>

Power ratings 200 V — Overload Tolerance — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 ND Rating: 120% of rated output current for 1 minute HD Rating: 150% of rated output current for 1 minute (Derating may be required for applications that start and stop frequently)

Power ratings 200 V — Carrier Frequency — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 User-adjustable 2 to 15 kHz

Power ratings 200 V — Max Output Voltage (V) — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 Three-phase power: 200 to 240 V Single-phase power: 200 to 240 V (both proportional to input voltage)

Power ratings 200 V — Max Output Frequency (Hz) — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 400 Hz (user-adjustable)

Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 Three-phase power: 200 to 240 V 50/60 Hz Single-phase power: 200 to 240 V 50/60 Hz DC power supply: 270 to 340 V <9>

Power ratings 200 V — Allowable Voltage Fluctuation — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 -15 to 10%

Power ratings 200 V — Allowable Frequency Fluctuation — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 ±5%

Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke — PDF page 343

Source row All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
1 Optional

Manual — 200 V larger frame ratings — page 344

Source reference: SIEP C71060618F, December 2016, physical PDF page 344. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table A.3 Power Ratings Continued

Item Specification Three-Phase Model 2A0030 2A0040 2A0056 2A0069

Single-Phase Model <1> - - - -

ND Rating Maximum Motor Size Allowed (HP) <2> HD Rating

Input Input Current (A) <3>

Three- Phase

ND Rating HD Rating

Single- Phase

Output

ND Rating Rated Output Capacity (kVA) <4> HD Rating

ND Rating <5> Output Current (A)

HD Rating

Overload Tolerance Carrier Frequency

Max Output Voltage (V) Max Output Frequency (Hz)

Power Supply

Rated Voltage Rated Frequency

Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective Actions DC Link Choke

<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor. <2> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance. <4> Rated motor capacity is calculated with a rated output voltage of 220 V. <5> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier frequency. <6> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency. <7> DC is not available for UL standards.

A.2 Single/Three-Phase 200 V Class Drives

Actual physical source row; model columns 2A0030, 2A0040, 2A0056, 2A0069. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0030

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0040

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0056

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0069

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0030

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0040

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0056

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0069

Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0030

Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0040

Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0056

Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0069

Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0030

Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0040

Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0056

Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0069

Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0030

Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0040

Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0056

Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0069

Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0030

Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0040

Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0056

Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0069

Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0030

Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0040

Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0056

Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0069

Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0030

Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0040

Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0056

Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0069

Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0030

Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0040

Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0056

Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0069

Power ratings 200 V — Output Current (A) | HD Rating | 2A0030

Power ratings 200 V — Output Current (A) | HD Rating | 2A0040

Power ratings 200 V — Output Current (A) | HD Rating | 2A0056

Power ratings 200 V — Output Current (A) | HD Rating | 2A0069

Power ratings 200 V — Overload Tolerance | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Carrier Frequency | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Max Output Voltage (V) | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Max Output Frequency (Hz) | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Allowable Voltage Fluctuation | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Allowable Frequency Fluctuation | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 7.5/10.0 10.0 20.0 25.0

Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 7.5 10.0 15.0 20.0

Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 37.0 52.0 68.0 80.0

Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 24.0 37.0 52.0 68.0

Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 - - - -

Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 11.4 15.2 21.3 26.3

Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 9.5 12.6 17.9 22.9

Power ratings 200 V — Output Current (A) | ND Rating <5> — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 30.0 40.0 56.0 69.0

Power ratings 200 V — Output Current (A) | HD Rating — PDF page 344

Source row 2A0030 2A0040 2A0056 2A0069
1 25.0 <6> 33.0 <6> 47. 0 <6> 60.0 <6>

Power ratings 200 V — Overload Tolerance — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 ND Rating: 120% of rated output current for 1 minute HD Rating: 150% of rated output current for 1 minute (Derating may be required for applications that start and stop frequently)

Power ratings 200 V — Carrier Frequency — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 User-adjustable 2 to 15 kHz

Power ratings 200 V — Max Output Voltage (V) — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 Three-phase power: 200 to 240 V Single-phase power: 200 to 240 V (both proportional to input voltage)

Power ratings 200 V — Max Output Frequency (Hz) — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 400 Hz (user-adjustable)

Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 Three-phase power: 200 to 240 V 50/60 Hz Single-phase power: 200 to 240 V 50/60 Hz DC power supply: 270 to 340 V <7>

Power ratings 200 V — Allowable Voltage Fluctuation — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 -15 to 10%

Power ratings 200 V — Allowable Frequency Fluctuation — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 ±5%

Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke — PDF page 344

Source row All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
1 Optional

Manual — 400 V small frame ratings — page 345

Source reference: SIEP C71060618F, December 2016, physical PDF page 345. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A.3 Three-Phase 400 V Class Drives

Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to 0 for HD or 1 for ND (default).

Table A.4 Power Ratings

Item Specification Three-Phase Model 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009

Maximum Applicable Motor Capacity (HP) <1>

ND Rating HD Rating

Input Current Input <2> (A)

Output

Output Current (kVA) <3>

ND Rating <4>

HD Rating <5>

Output Current (A)

Overload Tolerance Carrier Frequency Max Output Voltage (V) Max Output Frequency (Hz)

Power Supply

Rated Voltage Rated Frequency

Supply Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective Actions DC Link Choke

<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance. <3> Rated motor capacity is calculated with a rated output voltage of 460 V. <4> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency. <5> Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency. <6> DC is not available for UL standards.

A

Specifications

Actual physical source row; model columns 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0001

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0002

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0004

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0005

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0007

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0009

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0001

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0002

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0004

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0005

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0007

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0009

Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0001

Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0002

Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0004

Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0005

Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0007

Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0009

Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0001

Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0002

Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0004

Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0005

Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0007

Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0009

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0001

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0002

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0004

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0005

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0007

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0009

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0001

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0002

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0004

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0005

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0007

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0009

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0001

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0002

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0004

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0005

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0007

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0009

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0001

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0002

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0004

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0005

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0007

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0009

Power ratings 400 V — Overload Tolerance | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Carrier Frequency | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Max Output Voltage (V) | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Max Output Frequency (Hz) | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Allowable Voltage Fluctuation | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Allowable Frequency Fluctuation | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 0.5 0.75/1.0 1.5/2.0 3.0 3.0 5.0

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 0.5 0.75 1.0/1.5/2.0 3.0 3.0 3.0

Power ratings 400 V — Input | Input Current <2> (A) | ND Rating — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 1.2 2.1 4.3 5.9 8.1 9.4

Power ratings 400 V — Input Current <2> (A) | HD Rating — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 1.2 1.8 3.2 4.4 6.0 8.2

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 0.9 1.6 3.1 4.1 5.3 6.7

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 0.9 1.4 2.6 3.7 4.2 5.5

Power ratings 400 V — Output Current (A) | ND Rating <4> — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 1.2 2.1 4.1 5.4 6.9 8.8

Power ratings 400 V — Output Current (A) | HD Rating <5> — PDF page 345

Source row 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
1 1.2 1.8 3.4 4.8 5.5 7.2

Power ratings 400 V — Overload Tolerance — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 ND Rating: 120% of rated output current for 60 s HD Rating: 150% of rated output current for 60 s (Derating may be required for applications that start and stop frequently)

Power ratings 400 V — Carrier Frequency — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 User-adjustable 2 to 15 kHz

Power ratings 400 V — Max Output Voltage (V) — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 Three-phase power: 380 to 480 V (proportional to input voltage)

Power ratings 400 V — Max Output Frequency (Hz) — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 400 Hz (user-adjustable)

Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 Three-phase power: 380 to 480 V 50/60 Hz DC power supply: 510 to 680 V <6>

Power ratings 400 V — Allowable Voltage Fluctuation — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 -15 to 10%

Power ratings 400 V — Allowable Frequency Fluctuation — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 ±5%

Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke — PDF page 345

Source row All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
1 Optional

Manual — 400 V larger frame ratings — page 346

Source reference: SIEP C71060618F, December 2016, physical PDF page 346. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table A.5 Power Ratings Continued

Item Specification Three-Phase Model 4A0011 4A0018 4A0023 4A0031 4A0038

Maximum Applicable Motor Capacity (HP) <1>

ND Rating HD Rating

ND Rating Input Input Current (A) <2> HD Rating

Output

ND Rating <4> Output Current (kVA) <3>

HD Rating <5>

ND Rating <4> Output Current (A)

Overload Tolerance Carrier Frequency Max Output Voltage (V) Max Output Frequency (Hz)

Power Supply

Rated Voltage Rated Frequency

Supply Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective Actions DC Link Choke

<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance. <3> Rated motor capacity is calculated with a rated output voltage of 440 V. <4> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency. <5> Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency. <6> DC is not available for UL standards.

A.3 Three-Phase 400 V Class Drives

Actual physical source row; model columns 4A0011, 4A0018, 4A0023, 4A0031, 4A0038. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0011

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0018

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0023

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0031

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0038

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0011

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0018

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0023

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0031

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0038

Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0011

Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0018

Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0023

Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0031

Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0038

Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0011

Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0018

Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0023

Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0031

Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0038

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0011

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0018

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0023

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0031

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0038

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0011

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0018

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0023

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0031

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0038

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0011

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0018

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0023

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0031

Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0038

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0011

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0018

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0023

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0031

Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0038

Power ratings 400 V — Overload Tolerance | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Carrier Frequency | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Max Output Voltage (V) | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Max Output Frequency (Hz) | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Allowable Voltage Fluctuation | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Allowable Frequency Fluctuation | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 7.5 10.0 15.0 20.0 25.0

Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 5.0 10.0 10.0 15.0 20.0

Power ratings 400 V — Input | Input Current (A) <2> | ND Rating — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 14.0 20.0 24.0 38.0 44.0

Power ratings 400 V — Input Current (A) <2> | HD Rating — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 10.4 15.0 20.0 29.0 39.0

Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 8.5 13.3 17.5 23.6 29.0

Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 7.0 11.3 13.7 18.3 23.6

Power ratings 400 V — Output Current (A) | ND Rating <4> — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 11.1 17.5 23.0 31.0 38.0

Power ratings 400 V — Output Current (A) | HD Rating <5> — PDF page 346

Source row 4A0011 4A0018 4A0023 4A0031 4A0038
1 9.2 14.8 18.0 24.0 31.0

Power ratings 400 V — Overload Tolerance — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 ND Rating: 120% of rated output current for 60 s HD Rating: 150% of rated output current for 60 s (Derating may be required for applications that start and stop frequently)

Power ratings 400 V — Carrier Frequency — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 User-adjustable 2 to 15 kHz

Power ratings 400 V — Max Output Voltage (V) — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 Three-phase power: 380 to 480 V (proportional to input voltage)

Power ratings 400 V — Max Output Frequency (Hz) — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 400 Hz (user-adjustable)

Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 Three-phase power: 380 to 480 V 50/60 Hz DC power supply: 510 to 680 V <6>

Power ratings 400 V — Allowable Voltage Fluctuation — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 -15 to 10%

Power ratings 400 V — Allowable Frequency Fluctuation — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 ±5%

Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke — PDF page 346

Source row All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
1 Optional

Manual — Control specifications — page 347

Source reference: SIEP C71060618F, December 2016, physical PDF page 347. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A.4 Drive Specifications

Note: 1. Perform rotational Auto-Tuning to obtain OLV performance specifications. 2. For optimum performance life of the drive, install the drive in an environment that meets the environmental conditions.

Item Specification

Control Character- istics

Control Method

Frequency Control Range

Frequency Accuracy

Frequency Setting Resolution

Output Frequency Calculation Resolution

Frequency Setting Signal

Starting Torque

Speed Control Range

Speed Control Accuracy

Speed Response

Torque Limit

Accel/Decel Time

Braking Torque

V/f Characteristics

Functions

A

Specifications

Literal source row. Full PDF347–349 footnotes apply; historical compliance claims not validated certification. No installation approval inferred.

Drive specifications — Control Character- istics | Control Method | Specification

Drive specifications — Control Character- istics | Frequency Control Range | Specification

Drive specifications — Control Character- istics | Frequency Accuracy | Specification

Drive specifications — Control Character- istics | Frequency Setting Resolution | Specification

Drive specifications — Control Character- istics | Output Frequency Calculation Resolution | Specification

Drive specifications — Control Character- istics | Frequency Setting Signal | Specification

Drive specifications — Control Character- istics | Starting Torque | Specification

Drive specifications — Control Character- istics | Speed Control Range | Specification

Drive specifications — Control Character- istics | Speed Control Accuracy | Specification

Drive specifications — Control Character- istics | Speed Response | Specification

Drive specifications — Control Character- istics | Torque Limit | Specification

Drive specifications — Control Character- istics | Accel/Decel Time | Specification

Drive specifications — Control Character- istics | Braking Torque | Specification

Drive specifications — Control Character- istics | V/f Characteristics | Specification

Drive specifications — Control Character- istics | Functions | Specification

Drive specifications — Control Character- istics | Control Method — PDF page 347

Source row Specification
1 The following control methods are available: Open Loop Vector Control (current vector), V/f Control, and PM Open Loop Vector (for use with SPM and IPM)

Drive specifications — Control Character- istics | Frequency Control Range — PDF page 347

Source row Specification
1 0.01 to 400 Hz

Drive specifications — Control Character- istics | Frequency Accuracy — PDF page 347

Source row Specification
1 Digital input: within ±0.01% of the max output frequency (-10 to +50 °C) Analog input: within ±0.5% of the max output frequency (25 °C ±10 °C)

Drive specifications — Control Character- istics | Frequency Setting Resolution — PDF page 347

Source row Specification
1 Digital inputs: 0.01 Hz Analog inputs: 1/1000 of maximum output frequency

Drive specifications — Control Character- istics | Output Frequency Calculation Resolution — PDF page 347

Source row Specification
1 1/(2^20) x Maximum output frequency (E1-04)

Drive specifications — Control Character- istics | Frequency Setting Signal — PDF page 347

Source row Specification
1 Main frequency reference: 0 to +10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω) Main speed reference: Pulse Train Input (max 32 kHz)

Drive specifications — Control Character- istics | Starting Torque — PDF page 347

Source row Specification
1 200%/0.5 Hz (OLV Control, HD rating, IM of 3.7 kW or smaller), 50%/6 Hz (OLV/PM Control)

Drive specifications — Control Character- istics | Speed Control Range — PDF page 347

Source row Specification
1 1:100 (OLV Control), 1:40 (V/f Control), 1:10 (OLV/PM Control)

Drive specifications — Control Character- istics | Speed Control Accuracy — PDF page 347

Source row Specification
1 ±0.2% in Open Loop Vector Control <1>

Drive specifications — Control Character- istics | Speed Response — PDF page 347

Source row Specification
1 5 Hz (25 °C ±10 °C) in Open Loop Vector Control (excludes temperature fluctuation when performing Rotational Auto-Tuning)

Drive specifications — Control Character- istics | Torque Limit — PDF page 347

Source row Specification
1 Open Loop Vector Control only. Adjustable in 4 quadrants.

Drive specifications — Control Character- istics | Accel/Decel Time — PDF page 347

Source row Specification
1 0.00 to 6000.0 s (allows four separate settings for accel and decel)

Drive specifications — Control Character- istics | Braking Torque — PDF page 347

Source row Specification
1 Instantaneous Average Decel Torque <2> : 0.1/0.2 kW: over 150%, 0.4/0.75 kW: over 100%, 1.5 kW: over 50%, 2.2 kW and above: over 20% Continuous Regen Torque: 20%, 125% with a Braking Resistor Unit <3> : (10% ED) 10 s with an internal braking transistor.

Drive specifications — Control Character- istics | V/f Characteristics — PDF page 347

Source row Specification
1 Preset V/f patterns and user-set program available.

Drive specifications — Control Character- istics | Functions — PDF page 347

Source row Specification
1 Momentary Power Loss Ride-Thru Speed Search Over/Undertorque Detection Torque Limit, Multi-Step Speed (17 steps max) Accel/Decel Time Switch S-Curve Accel/Decel, 2-Wire/3-Wire Sequence Rotational Auto-Tuning Stationary Auto-Tuning of Line-to-Line Resistance Dwell Cooling Fan ON/OFF Slip Compensation Torque Compensation Jump Frequencies (reference dead band) Frequency Reference Upper/Lower Limit DC Injection Braking (start and stop), High Slip Braking PID Control (with Sleep Function) Energy Saving MEMOBUS/Modbus (RS-485/RS-422 Max 115.2 kbps) Fault Reset Parameter Copy DriveWorksEZ Fault Restart Removable Terminals with Parameter Backup Function

Manual — Protection and environment specifications — page 348

Source reference: SIEP C71060618F, December 2016, physical PDF page 348. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Item Specification

Protection Functions

Motor Protection

Overcurrent Protection

Overload Protection

Overvoltage Specification

Low Voltage Protection

Momentary Power Loss Ride-Thru

Heatsink Overheat Protection

Braking Resistor Overheat Protection

Stall Prevention

Cooling Fan Failure Protection

Ground Fault Protection

DC Bus Charge LED

Environment

Storage/Installation Area

Ambient Temperature

Humidity

Storage Temperature

Altitude

Shock, Impact

Surrounding Area

Orientation

Standards

Protective Enclosure

Cooling Method

<1> Speed control accuracy varies somewhat according to the type of motor and drive settings. <2> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed down to zero in the shortest time. <3> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a braking resistor or the Braking Resistor Unit. The default setting for the stall prevention function will interfere with the braking transistor. <4> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.

A.4 Drive Specifications

Literal source row. Full PDF347–349 footnotes apply; historical compliance claims not validated certification. No installation approval inferred.

Drive specifications — Protection Functions | Motor Protection | Specification

Drive specifications — Protection Functions | Overcurrent Protection | Specification

Drive specifications — Protection Functions | Overload Protection | Specification

Drive specifications — Protection Functions | Overvoltage Specification | Specification

Drive specifications — Protection Functions | Low Voltage Protection | Specification

Drive specifications — Protection Functions | Momentary Power Loss Ride-Thru | Specification

Drive specifications — Protection Functions | Heatsink Overheat Protection | Specification

Drive specifications — Protection Functions | Braking Resistor Overheat Protection | Specification

Drive specifications — Protection Functions | Stall Prevention | Specification

Drive specifications — Protection Functions | Cooling Fan Failure Protection | Specification

Drive specifications — Protection Functions | Ground Fault Protection | Specification

Drive specifications — Protection Functions | DC Bus Charge LED | Specification

Drive specifications — Environment | Storage/Installation Area | Specification

Drive specifications — Environment | Ambient Temperature | Specification

Drive specifications — Environment | Humidity | Specification

Drive specifications — Environment | Storage Temperature | Specification

Drive specifications — Environment | Altitude | Specification

Drive specifications — Environment | Shock, Impact | Specification

Drive specifications — Environment | Surrounding Area | Specification

Drive specifications — Environment | Orientation | Specification

Drive specifications — Standards | Specification

Drive specifications — Protective Enclosure | Specification

Drive specifications — Cooling Method | Specification

Drive specifications — Protection Functions | Motor Protection — PDF page 348

Source row Specification
1 Motor overheat protection via output current sensor

Drive specifications — Protection Functions | Overcurrent Protection — PDF page 348

Source row Specification
1 Drives stops when output exceeds 200% of the rated current (Heavy Duty)

Drive specifications — Protection Functions | Overload Protection — PDF page 348

Source row Specification
1 A stop command will be entered after operating at 150% for 60 s (Heavy Duty) <4>

Drive specifications — Protection Functions | Overvoltage Specification — PDF page 348

Source row Specification
1 200 V Class: Stops when DC bus voltage exceeds approx. 410 V 400 V Class: Stops when DC bus voltage exceeds approx. 820 V

Drive specifications — Protection Functions | Low Voltage Protection — PDF page 348

Source row Specification
1 Drive stops when DC bus voltage falls below the levels indicated: <5> 190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V), 350 V (3-phase 380 V)

Drive specifications — Protection Functions | Momentary Power Loss Ride-Thru — PDF page 348

Source row Specification
1 3 selections available: Ride-Thru disabled (stops after 15 ms), time <6> base of 0.5 s, and continue running as long as the drive control board is powered up.

Drive specifications — Protection Functions | Heatsink Overheat Protection — PDF page 348

Source row Specification
1 Protected by thermistor

Drive specifications — Protection Functions | Braking Resistor Overheat Protection — PDF page 348

Source row Specification
1 Overheat input signal for braking resistor (Optional ERF-type, 3% ED)

Drive specifications — Protection Functions | Stall Prevention — PDF page 348

Source row Specification
1 Stall prevention is available during acceleration, deceleration, and during run. Separate settings for each type of stall prevention determine the current level at which stall prevention is triggered.

Drive specifications — Protection Functions | Cooling Fan Failure Protection — PDF page 348

Source row Specification
1 Circuit protection (“fan-lock” sensor)

Drive specifications — Protection Functions | Ground Fault Protection — PDF page 348

Source row Specification
1 Electronic circuit protection <7>

Drive specifications — Protection Functions | DC Bus Charge LED — PDF page 348

Source row Specification
1 Remains lit until DC bus voltage falls below 50 V

Drive specifications — Environment | Storage/Installation Area — PDF page 348

Source row Specification
1 Indoors

Drive specifications — Environment | Ambient Temperature — PDF page 348

Source row Specification
1 IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F) IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F) Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F) NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

Drive specifications — Environment | Humidity — PDF page 348

Source row Specification
1 95% RH or less with no condensation

Drive specifications — Environment | Storage Temperature — PDF page 348

Source row Specification
1 -20 to +60 °C (-4 to +140 °F) allowed for short-term transport of the product

Drive specifications — Environment | Altitude — PDF page 348

Source row Specification
1 Up to 1000 meters without derating; up to 3000 meters with output current and voltage derating. Refer to Altitude Derating on page 352 for details.

Drive specifications — Environment | Shock, Impact — PDF page 348

Source row Specification
1 10 to 20 Hz: 9.8 m/s2 20 to 55 Hz: 5.9 m/s2

Drive specifications — Environment | Surrounding Area — PDF page 348

Source row Specification
1 Install the drive in an area free from: • oil mist and dust • metal shavings, oil, water or other foreign materials • radioactive materials • combustible materials • harmful gases and liquids • excessive vibration • chlorides • direct sunlight

Drive specifications — Environment | Orientation — PDF page 348

Source row Specification
1 Install the drive vertically to maintain maximum cooling effects

Drive specifications — Standards — PDF page 348

Source row Specification
1 • UL508C • EN 61800-3:2004/A1:2012, IEC/EN 61800-5-1 • ISO/EN 13849-1 Cat.3 PLd, IEC/EN 61508 SIL2 Time from input open to drive output stop is less than 1 ms.

Drive specifications — Protective Enclosure — PDF page 348

Source row Specification
1 IP20/Open-Chassis or IP00/Open-Chassis <8> IP20/NEMA Type 1 <9>

Drive specifications — Cooling Method — PDF page 348

Source row Specification
1 BA0001 to BA0006: self-cooled BA0010 to BA0018: cooling fan 2A0001 to 2A0004: self-cooled 2A0006 to 2A0069: cooling fan 4A0001 to 4A0004: self-cooled 4A0005 to 4A0038: cooling fan

Manual — Specification footnotes — page 349

Source reference: SIEP C71060618F, December 2016, physical PDF page 349. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

<5> Parameter settings allow up to 150 V. <6> A Momentary Power Loss Ride-Thru Unit is required for 200/400 V class drives 7.5 kW and less if the application needs to continue running during a momentary power loss up to 2 seconds. <7> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the motor windings during run: Low ground resistance for the motor cable and terminal block; low ground resistance for the motor cable and terminal block; or the drive is powered up from a ground short. <8> The following models have an IP20/Open-Chassis enclosure as standard. Customers may convert these models to IP20/NEMA Type 1 enclosures using the IP20/NEMA Type 1 Kit Option: 2A0030 to 2A0069 4A0018 to 4A0038 <9> The following models have an IP20/NEMA Type 1 enclosure as standard. For an IP20/Open-Chassis or IP00/Open-Chassis design, remove the top and bottom covers: BA0001 to BA0018 2A0001 to 2A0020 4A0001 to 4A0011

Note: Time from input open to drive output stop is less than 1 ms.

A.4 Drive Specifications

A

Specifications

Manual — Watt loss by model and duty — page 350

Source reference: SIEP C71060618F, December 2016, physical PDF page 350. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

A.5 Drive Watt Loss Data

Table A.6 Watt Loss 200 V Class Single-Phase Models

Drive Model

Heavy Duty (Carrier Frequency 8 kHz) <1> Normal Duty (Swing PWM equal 2 kHz)

Rated Amps (A)

Heatsink Loss (W)

Interior Unit Loss (W)

Total Loss (W)

Drive Model Rated Amps Heatsink Interior Unit Total Loss Rated Amps Heatsink Interior Unit Total Loss (A) Loss (W) Loss (W) (W) (A) Loss (W) Loss (W) (W)

<1> 10 kHz for BA0001 to BA0006

Table A.7 Watt Loss 200 V Class Three-Phase Models

<1> 10 kHz for 2A0001 to 2A0006

Table A.8 Watt Loss 400 V Class Three-Phase Models

Heavy Duty (Carrier Frequency 8 kHz) Normal Duty (Swing PWM equal 2 kHz) Rated Amps Heatsink Interior Unit Total Loss Rated Amps Heatsink Interior Unit Total (A) Loss (W) Loss (W) (W) (A) Loss (W) Loss (W)

Watt loss — 200 V single-phase | Drive model

Watt loss — 200 V single-phase | HD rated amps (A)

Watt loss — 200 V single-phase | HD heatsink loss (W)

Watt loss — 200 V single-phase | HD interior unit loss (W)

Watt loss — 200 V single-phase | HD total loss (W)

Watt loss — 200 V single-phase | ND rated amps (A)

Watt loss — 200 V single-phase | ND heatsink loss (W)

Watt loss — 200 V single-phase | ND interior unit loss (W)

Watt loss — 200 V single-phase | ND total loss (W)

Watt loss — 200 V three-phase | Drive model

Watt loss — 200 V three-phase | HD rated amps (A)

Watt loss — 200 V three-phase | HD heatsink loss (W)

Watt loss — 200 V three-phase | HD interior unit loss (W)

Watt loss — 200 V three-phase | HD total loss (W)

Watt loss — 200 V three-phase | ND rated amps (A)

Watt loss — 200 V three-phase | ND heatsink loss (W)

Watt loss — 200 V three-phase | ND interior unit loss (W)

Watt loss — 200 V three-phase | ND total loss (W)

Watt loss — 400 V three-phase | Drive model

Watt loss — 400 V three-phase | HD rated amps (A)

Watt loss — 400 V three-phase | HD heatsink loss (W)

Watt loss — 400 V three-phase | HD interior unit loss (W)

Watt loss — 400 V three-phase | HD total loss (W)

Watt loss — 400 V three-phase | ND rated amps (A)

Watt loss — 400 V three-phase | ND heatsink loss (W)

Watt loss — 400 V three-phase | ND interior unit loss (W)

Watt loss — 400 V three-phase | ND total loss (W)

Watt loss — 200 V single-phase — PDF page 350

Source row Drive model HD rated amps (A) HD heatsink loss (W) HD interior unit loss (W) HD total loss (W) ND rated amps (A) ND heatsink loss (W) ND interior unit loss (W) ND total loss (W)
1 BA0001 0.8 4.3 7.4 11.7 1.2 5.0 8.5 13.5
2 BA0002 1.6 7.9 8.9 16.7 1.9 7.6 9.7 17.3
3 BA0003 3.0 16.1 11.5 27.7 3.2 14.6 14.4 29.1
4 BA0006 5.0 33.7 16.8 50.5 6.0 30.1 19.4 49.5
5 BA0010 8.0 54.8 25.9 80.7 9.6 51.7 29.8 81.4
6 BA0012 11.0 70.7 34.1 104.8 12.0 61.3 37.1 98.4
7 BA0018 17.5 110.5 51.4 161.9 — — — —

Watt loss — 200 V three-phase — PDF page 350

Source row Drive model HD rated amps (A) HD heatsink loss (W) HD interior unit loss (W) HD total loss (W) ND rated amps (A) ND heatsink loss (W) ND interior unit loss (W) ND total loss (W)
1 2A0001 0.8 4.3 7.3 11.6 1.2 5.0 8.0 13.0
2 2A0002 1.6 7.9 8.8 16.7 1.9 7.6 9.5 17.1
3 2A0004 3.0 16.2 11.5 27.7 3.5 15.8 13.6 29.4
4 2A0006 5.0 27.4 15.9 43.3 6.0 27.5 17.2 44.7
5 2A0010 8.0 54.8 23.8 78.6 9.6 51.7 25.8 77.5
6 2A0012 11.0 70.7 29.9 100.6 12.0 61.3 30.4 91.7
7 2A0020 17.5 110.5 43.3 153.8 19.6 98.7 46.3 145.0
8 2A0030 25.0 231.5 72.2 303.7 30.0 246.4 88.9 335.3
9 2A0040 33.0 339.5 82.8 321.3 40.0 266.7 112.8 379.6
10 2A0056 47.0 347.6 117.6 465.2 56.0 357.9 151.8 509.7
11 2A0069 60.0 437.7 151.4 589.1 69.0 461.7 184.5 646.2

Watt loss — 400 V three-phase — PDF page 350

Source row Drive model HD rated amps (A) HD heatsink loss (W) HD interior unit loss (W) HD total loss (W) ND rated amps (A) ND heatsink loss (W) ND interior unit loss (W) ND total loss (W)
1 4A0001 1.2 19.2 11.5 30.7 1.2 10.0 9.6 19.6
2 4A0002 1.8 28.9 14.8 43.7 2.1 18.5 13.9 32.4
3 4A0004 3.4 42.3 17.9 60.2 4.1 30.5 16.8 47.3
4 4A0005 4.8 70.7 26.2 96.9 5.4 44.5 21.8 66.3
5 4A0007 5.5 81.0 30.7 111.7 6.9 58.5 28.4 86.9
6 4A0009 7.2 84.6 32.9 117.5 8.8 63.7 31.4 95.1
7 4A0011 9.2 107.2 41.5 148.7 11.1 81.7 46.0 127.7
8 4A0018 14.8 166.0 62.7 228.7 17.5 181.2 80.1 261.3
9 4A0023 18.0 207.1 78.1 285.2 23.0 213.4 107.7 321.1
10 4A0031 24.0 266.9 105.9 372.8 31.0 287.5 146.1 433.6
11 4A0038 31.0 319.1 126.6 445.7 38.0 319.2 155.8 475.0

Manual — Carrier and ambient derating — page 351

Source reference: SIEP C71060618F, December 2016, physical PDF page 351. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive Rating vertical0,HD,ND;horizontalCarrier Frequency(C6-02)ticks2,10(8),15. At15,source marks200VClass80%ofHD and400VClass60%ofHD;HDflatto10(8),NDflatto2thenlinefalls toHD at10(8). FigureA.1 Carrier Frequency Derating. Carrierfrequencyaxis itself prints no unit; kHz context comes from surrounding specification tables, not inferred into axis. Exact curves remain original-only; no intermediate value interpolation or operating approval.

Drive Rating axis0%,50%,70%,80%,85%,100%;Ambienttemp°C,ParameterL8-12 ticks-10°,30°,35°,40°,50°. CurvelabelsL8-35=0(IP20/IP00Drive),=2(NEMAType1Drive),=3(Finless Drive orExternalHeatsinkInstallation),=1(Side-by-SideMounting). FigureA.2 Ambient Temperature and Installation Method Derating; exact curve intersections remain original-only. Exact curves remain original-only; no intermediate value interpolation or operating approval.

A.6 Drive Derating Data

The drive can be operated at above rated temperature, altitude and default carrier frequency by derating the drive capacity.

u Carrier Frequency Derating

Derate drive capacity using Figure A.1 as the carrier frequency of the drive increases above the factory setting.

u Temperature Derating

As the ambient temperature for the drive is increased above the drive specification the drive should be derated. Additionally parameter L8-35 Installation Method Selection on page 351 should be set according to enclosure type and mounting method as illustrated in Figure A.2.

n Output Current Derating Due to Ambient Temperature

Set L8-12 and L8-35 according to the installation conditions when the ambient temperature is above the drive specification or when drives are mounted side-by-side in a cabinet. The output current is derated as shown in Figure A.2.

No. Name Description Range Def.

A

Specifications

L8-12 | Ambient Temperature Setting

L8-35 | Installation Method Selection

Temperature and installation derating parameters — PDF page 351

Source row Parameter Name Description Range Default
1 L8-12 Ambient Temperature Setting Adjust the drive overload (oL2) protection level when the drive is installed in an environment that exceeds its ambient temperature rating. -10 to 50 40 °C
2 L8-35 Installation Method Selection 0: IP20/IP00 Drive 1: Side-by-Side Mounting 2: NEMA Type 1 Drive 3: Finless Drive or External Heatsink Installation 0 to 3 0

Manual — Altitude derating — page 352

Source reference: SIEP C71060618F, December 2016, physical PDF page 352. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u Altitude Derating

The drive standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000 m, both the drive input voltage and the rated output current must be derated for 1% per 100 m. The maximum altitude is 3000 m.

A.6 Drive Derating Data

Manual — Parameter group index — page 354

Source reference: SIEP C71060618F, December 2016, physical PDF page 354. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

B.1 Parameter Groups

Parameter Name Page Group

A1 | Initialization

A2 | User Parameters

b1 | Operation Mode Selection

b2 | DC Injection Braking

b3 | Speed Search

b4 | Delay Timer

b5 | PID Control

b6 | Dwell Function

b8 | Energy Saving

C1 | Acceleration/Deceleration Time

C2 | S-Curve Accel/Decel

C3 | Motor Slip Compensation

C4 | Motor Torque Compensation

C5 | Speed Control (ASR)

C6 | Carrier Frequency

d1 | Frequency Reference

d2 | Reference Limits

d3 | Jump Frequencies

d4 | Frequency Reference Hold

d7 | Off-Set Frequency

E1 | V/f Pattern

E2 | Motor Setup

E3 | Motor 2 V/f Pattern

E4 | Motor Setup 2

E5 | PM Motor Setup

F1 | Fault Detection during PG Speed Control

F6 | Network Communications

F7 | EtherNet/IP and Modbus TCP/IP Communications

H1 | Digital Inputs

H2 | Digital Outputs

H3 | Analog Inputs

H4 | Analog Outputs

H5 | Serial Communications Setup

H6 | Pulse Train I/O Setup

L1 | Motor Overload

L2 | Power Loss Ride-Thru

L3 | Stall Prevention

L4 | Reference Detection

L5 | Fault Restart

L6 | Overtorque Detection

L7 | Torque Limit

L8 | Hardware Protection

n1 | Hunting Prevention

n2 | Speed Feedback Detection

n3 | High-Slip Braking

n6 | Motor Line-to-Line Resistance Online Tuning

n8 | PM Motor Control

o1 | Monitor Display Selection

o2 | Operator Keypad Functions

o4 | Maintenance Functions

q | DWEZ Parameters

r | DriveWorksEZ Connection

T1 | Auto-Tuning

U1 | Status Monitor

U2 | Fault Trace

U3 | Fault History

U4 | Maintenance Monitor

U5 | PID Monitor

U6 | Control Monitor

U8 | Custom Monitors for DriveWorksEZ

Parameter group index 1 — PDF page 354

Source row Parameter group Name Reference page
1 A1 Initialization 355
2 A2 User Parameters 356
3 b1 Operation Mode Selection 356
4 b2 DC Injection Braking 357
5 b3 Speed Search 358
6 b4 Delay Timer 358
7 b5 PID Control 358
8 b6 Dwell Function 360
9 b8 Energy Saving 360
10 C1 Acceleration/Deceleration Time 361
11 C2 S-Curve Accel/Decel 362
12 C3 Motor Slip Compensation 362
13 C4 Motor Torque Compensation 362
14 C5 Speed Control (ASR) 363
15 C6 Carrier Frequency 363
16 d1 Frequency Reference 364
17 d2 Reference Limits 365
18 d3 Jump Frequencies 365
19 d4 Frequency Reference Hold 365
20 d7 Off-Set Frequency 366
21 E1 V/f Pattern 367
22 E2 Motor Setup 367
23 E3 Motor 2 V/f Pattern 368
24 E4 Motor Setup 2 369
25 E5 PM Motor Setup 370
26 F1 Fault Detection during PG Speed Control 371
27 F6 Network Communications 372
28 F7 EtherNet/IP and Modbus TCP/IP Communications 374
29 H1 Digital Inputs 376
30 H2 Digital Outputs 378

Parameter group index 2 — PDF page 354

Source row Parameter group Name Reference page
1 H3 Analog Inputs 381
2 H4 Analog Outputs 382
3 H5 Serial Communications Setup 382
4 H6 Pulse Train I/O Setup 383
5 L1 Motor Overload 384
6 L2 Power Loss Ride-Thru 384
7 L3 Stall Prevention 385
8 L4 Reference Detection 387
9 L5 Fault Restart 387
10 L6 Overtorque Detection 387
11 L7 Torque Limit 389
12 L8 Hardware Protection 389
13 n1 Hunting Prevention 391
14 n2 Speed Feedback Detection 392
15 n3 High-Slip Braking 392
16 n6 Motor Line-to-Line Resistance Online Tuning 392
17 n8 PM Motor Control 392
18 o1 Monitor Display Selection 394
19 o2 Operator Keypad Functions 394
20 o4 Maintenance Functions 395
21 q DWEZ Parameters 396
22 r DriveWorksEZ Connection 396
23 T1 Auto-Tuning 398
24 U1 Status Monitor 399
25 U2 Fault Trace 400
26 U3 Fault History 401
27 U4 Maintenance Monitor 402
28 U5 PID Monitor 403
29 U6 Control Monitor 404
30 U8 Custom Monitors for DriveWorksEZ 404

Manual — Control mode legend and initialization — page 355

Source reference: SIEP C71060618F, December 2016, physical PDF page 355. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

B.2 Parameter Table

An “A” in the “Control Mode” column indicates that the parameter is available in the Advanced menu of the respective control mode. An “S” in the “Control Mode” column indicates that the parameter is available in the Startup menu of the respective control mode. A “–” in the “Control Mode” column indicates that the parameter is NOT available in the respective control mode. An “O” in the “Control Mode” column indicates that the multi-function selection is available in the respective control mode.

u A: Initialization Parameters

The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor Control Method, Password, User Parameters and more.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

A1: Initialization Parameters Use A1 parameters to configure the basic environment for drive operation.

The following parameters are not reset when the performing initialization: A1-00, A1-02, A1-07, E1-03, E5-□□, F6-08, L8-35, o2-04, o2-09, and all U2 and U3 monitors.

This parameter is hidden from view. To access A1-05, first display A1-04. Then press the STOP key while holding down — the up arrow key. Parameter A1-05 will appear.

—

B

List Parameter

A1-00 <1> <2> | Language Selection

A1-01 <1> <3> | Access Level Selection

A1-02 <2> | Control Method Selection

A1-03 | Initialize Parameters

A1-04 | Password

A1-05 | Password Setting

Parameter catalogue PDF355 section1 — PDF page 355

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 A1-00 <1> <2> Language Selection 0: English 1: Japanese 2: German 3: French 4: Italian 5: Spanish 6: Portuguese 7: Chinese 0 to 7 0 A A A 100 116
2 A1-01 <1> <3> Access Level Selection Selects which parameters are accessible via the digital operator. 0: Operation only 1: User Parameters (access to a set of parameters selected by the user) 2: Advanced Access Level 0 to 2 2 A A A 101 116
3 A1-02 <2> Control Method Selection Selects the Control Method of the drive. Auto-Tuning must be performed when selecting one of the vector control modes. 0: V/f Control without PG 2: Open Loop Vector (OLV) 5: PM Open Loop Vector (PM) Note: 1. Does not return to the default setting after initialization. 2. If using Open Loop Vector Control (A1-02 = 2), then Auto-Tuning must be performed again after the drive is initialized. Refer to Auto- Tuning on page 102 for details. 0, 2, 5 0 S S S 102 116
4 A1-03 Initialize Parameters Resets all parameters to factory default settings. (Initializes the drive then returns A1-03 to 0) 0: No Initialization 1110: User Initialize (First set user parameter values must be stored using parameter o2-03) 2220: 2-Wire Initialization 3330: 3-Wire Initialization 5550: oPE04 Error Reset 0 to 5550 0 A A A 103 117
5 A1-04 Password When the value set into A1-04 does not match the value set into A1-05, parameters A1-01 through A1-03, A1-06, and A2-01 through A2-32 cannot be changed. 0 to 9999 0 A A A 104 118
6 A1-05 Password Setting When the value set into A1-04 does not match the value set into A1-05, parameters A1-01 through A1-03, A1-06, and A2-01 through A2-32 cannot be changed. 0 to 9999 0 A A A 105 118

Manual — Application presets and run sources — page 356

Source reference: SIEP C71060618F, December 2016, physical PDF page 356. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

A2: User Parameters Use A2 parameters to program the drive.

<1> Parameter can be changed during run. <2> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <3> Default setting value is dependent on parameter A1-06, Application Selection. <4> Available in drive software versions PRG: 1020 and later. <5> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0.

u b: Application

Application parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID control, the Dwell function, Energy Savings and a variety of other application-related settings.

b1: Operation Mode Selection Use b1 parameters to configure the operation mode.

B.2 Parameter Table

A1-06 | Application Preset

A1-07 <2> | DriveWorksEZ Function Selection

A2-01 to A2-32 | User Parameters, 1 to 32

A2-33 | User Parameter Automatic Selection

b1-01 | Frequency Reference Selection 1

b1-02 | Run Command Selection 1

Parameter catalogue PDF356 section1 — PDF page 356

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 A1-06 Application Preset Sets parameters that are commonly used in certain applications to A2-01 through A2-16 for easier access. 0: General-purpose (A2 parameters are not affected) 1: Water supply pump 2: Conveyor 3: Exhaust fan 4: HVAC fan 5: Air compressor 8: Conveyor 2 <4> Note: Application Preset settings 6 and 7 are only present in drive software versions PRG: 1011 and earlier. 0 to 5; 8 0 A A A 127 96
2 A1-07 <2> DriveWorksEZ Function Selection 0: Disabled 1: Enabled 2: Multi-function input (enabled when H1-□□ = 9F) 0 to 2 0 A A A 128 119
3 A2-01 to A2-32 User Parameters, 1 to 32 Parameters that were recently edited are listed here. The user can also select parameters to appear here for quick access. Parameters will be stored here for quick access when A1-01 = 1. A1-00 to o2-08 <3> A A A 106 to 125 120
4 A2-33 User Parameter Automatic Selection 0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. 1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access. 0, 1 <5> A A A 126 120

Parameter catalogue PDF356 section2 — PDF page 356

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 b1-01 Frequency Reference Selection 1 Selects the frequency reference input source. 0: Digital operator - Digital preset speed d1-01 to d1-17. 1: Terminals - Analog input terminal A1 or A2. 2: MEMOBUS communications 3: Option PCB 4: Pulse Input (Terminal RP) 0 to 4 1 S S S 180 121
2 b1-02 Run Command Selection 1 Selects the run command input source. 0: Digital operator - RUN and STOP keys on the digital operator. 1: Digital input terminals 2: MEMOBUS communications 3: Option PCB. 0 to 3 1 S S S 181 123

Manual — Run and braking parameters — page 357

Source reference: SIEP C71060618F, December 2016, physical PDF page 357. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

DC Injection Braking at Stop cannot be selected when using Open Loop Vector for PM motors.

b2: DC Injection Braking Use b2 parameters to configure DC Injection Braking operation

B.2 Parameter Table

B

List Parameter

b1-03 | Stopping Method Selection

b1-04 | Reverse Operation Selection

b1-07 | LOCAL/REMOTE Run Selection

b1-08 | Run Command Selection while in Programming Mode

b1-14 | Phase Order Selection

b1-15 | Frequency Reference Selection 2

b1-16 | Run Command Selection 2

b1-17 | Run Command at Power Up

b2-01 | DC Injection Braking Start Frequency

b2-02 | DC Injection Braking Current

b2-03 | DC Injection Braking Time/ DC Excitation Time at Start

b2-04 | DC Injection Braking Time at Stop

b2-08 | Magnetic Flux Compensation Value

b2-12 | Short Circuit Brake Time at Start

Parameter catalogue PDF357 section1 — PDF page 357

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 b1-03 Stopping Method Selection Selects the stopping method when the run command is removed. 0: Ramp to Stop 1: Coast to Stop 2: DC Injection Braking to Stop 3: Coast with Timer (A new run command is ignored if received before the timer expires) 0 to 3 0 S S S 182 124
2 b1-04 Reverse Operation Selection Permits or prohibits reverse operation. 0: Reverse enabled. 1: Reverse disabled. 0, 1 0 A A A 183 126
3 b1-07 LOCAL/REMOTE Run Selection Determines the operation when the Run command source is switched from LOCAL to REMOTE or between Run source 1 and 2 while an external Run command is active at the new source. 0: External Run command has to be cycled at the new source to be activated. 1: External Run command at new source is accepted immediately. 0, 1 0 A A A 186 127
4 b1-08 Run Command Selection while in Programming Mode 0: Run command accepted only in the operation menu. 1: Run command accepted in all menus. 2: Prohibit entering Programming Mode during Run 0 to 2 0 A A A 187 127
5 b1-14 Phase Order Selection Sets the phase order for drive output terminals U/T1, V/T2 and W/T3. 0 : Standard 1 : Switch phase order 0, 1 0 A A A 1C3 127
6 b1-15 Frequency Reference Selection 2 Selects the frequency reference input source 2. 0: Operator - Digital preset speed d1-01 to d1-17. 1: Terminals - Analog input terminal A1 or A2 2: MEMOBUS communications 3: Option PCB 4: Pulse Input (Terminal RP) 0 to 4 0 A A A 1C4 128
7 b1-16 Run Command Selection 2 Selects the run command input source 2. 0: Operator - RUN and STOP keys on the digital operator. 1: Digital input terminals 2: MEMOBUS communications 3: Option PCB 0 to 3 0 A A A 1C5 128
8 b1-17 Run Command at Power Up Determines the operation when a Run command is active at power up of the drive. 0: Run command not issued, needs to be cycled 1: Run command issued, motor operation start 0, 1 0 A A A 1C6 128
9 b2-01 DC Injection Braking Start Frequency Sets the frequency at which DC Injection Braking starts when Ramp to Stop (b1-03 = 0) is selected. If b2-01< E1-09, DC Injection Braking starts at E1-09. 0.0 to 10.0 0.5 Hz A A A 189 128
10 b2-02 DC Injection Braking Current Sets the DC Injection Braking current as a percentage of the drive rated current. 0 to 75 50% A A A 18A 129
11 b2-03 DC Injection Braking Time/ DC Excitation Time at Start Sets DC Injection Braking time at start. Disabled when set to 0.00 seconds. 0.00 to 10.00 0.00 s <1> A A A 18B 129
12 b2-04 DC Injection Braking Time at Stop Sets DC Injection Braking time at stop. When b1-03 = 2, actual DC Injection time is calculated as follows: (b2-04) x 10 x (Output Freq)/(E1-04). When b1-03 = 0, this parameter sets the amount of DC Injection time applied to the motor at the end of the decel ramp or High Slip Braking. Disabled when set to 0.00. 0.00 to 10.00 0.50 s A A − 18C 129
13 b2-08 Magnetic Flux Compensation Value Sets the magnetic flux compensation as a percentage of the no- load current value (E2-03). 0 to 1000 0% − A − 190 129
14 b2-12 Short Circuit Brake Time at Start Sets the time for Short-Circuit brake operation at start. Disabled when set to 0.00. <2> 0.00 to 25.50 0.00 s − − A 1BA 129

Manual — Speed search and timer parameters — page 358

Source reference: SIEP C71060618F, December 2016, physical PDF page 358. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

b3: Speed Search Use b3 parameters to configure Speed Search function operation.

b4: Timer Function Use b4 parameters to configure timer function operation.

b5: PID Control Use b5 parameters to configure the PID control drive function.

B.2 Parameter Table

b2-13 | Short Circuit Brake Time at Stop

b3-01 | Speed Search Selection at Start

b3-02 | Speed Search Deactivation Current

b3-03 | Speed Search Deceleration Time

b3-05 | Speed Search Delay Time

b3-06 | Output Current 1 during Speed Search

b3-08 <11> | Current Control Gain during Speed Search (Speed Estimation Type)

b3-10 | Speed Search Detection Compensation Gain

b3-14 | Bi-Directional Speed Search Selection

b3-17 | Speed Search Restart Current Level

b3-18 | Speed Search Restart Detection Time

b3-19 | Number of Speed Search Restarts

b3-24 | Speed Search Method Selection

b3-25 | Speed Search Retry Interval Time

b3-29 <5> | Speed Search Induced Voltage Level

b4-01 | Timer Function On-Delay Time

b4-02 | Timer Function Off-Delay Time

Parameter catalogue PDF358 section1 — PDF page 358

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 b2-13 Short Circuit Brake Time at Stop Sets the Short-Circuit brake operation time at stop. Used to stop a motor rotating due to inertia. Disabled when set to 0.00 seconds. <2> 0.00 to 25.50 0.50 s − − A 1BB 129
2 b3-01 Speed Search Selection at Start Enables/disables the Speed Search function at start. 0: Disabled - Speed Search is not automatically performed at start. 1: Enabled - Speed Search is automatically performed at start. 0, 1 0 A A A 191 133
3 b3-02 Speed Search Deactivation Current Sets the current level at which the speed is assumed to be detected and Speed Search is ended. Set as a percentage of the drive rated current. 0 to 200 120 <3> A A − 192 133
4 b3-03 Speed Search Deceleration Time Sets the time constant used to reduce the output frequency during Speed Search. Related to a change from max. output frequency to 0. 0.1 to 10.0 2.0 s A A − 193 133
5 b3-05 Speed Search Delay Time Delays the Speed Search operation after a momentary power loss to allow time for an external output contactor to close. 0.0 to 100 0.2 s A A A 195 133
6 b3-06 Output Current 1 during Speed Search Sets the current injected to the motor at the beginning of Estimation type Speed Search. Set as a factor of the motor rated current. 0.0 to 2.0 <4> A A − 196 134
7 b3-08 <11> Current Control Gain during Speed Search (Speed Estimation Type) Sets the proportional gain for the current controller during Speed Search. There is normally no need to change this parameter from the default value. 0.00 to 6.00 <12> A A A 198 134
8 b3-10 Speed Search Detection Compensation Gain Sets the gain which is applied to the speed detected by Speed Estimation Speed Search before the motor is reaccelerated. Increase this setting if ov occurs when performing Speed Search. 1.00 to 1.20 1.05 A A − 19A 134
9 b3-14 Bi-Directional Speed Search Selection Selects if Speed Search detects the motor rotation direction during Speed Search. 0: Disabled–Frequency reference direction used 1: Enabled–Detected direction used 0, 1 0 A A − 19E 134
10 b3-17 Speed Search Restart Current Level Sets the Speed Search restart current level as a percentage of the drive rated current. 0 to 200 150% A A − 1F0 134
11 b3-18 Speed Search Restart Detection Time Sets the time in seconds for Speed Search restart to be detected. 0.00 to 1.00 0.10 s A A − 1F1 134
12 b3-19 Number of Speed Search Restarts Sets the number of restarts possible for Speed Search restart operations. 0 to 10 3 A A − 1F2 135
13 b3-24 Speed Search Method Selection Sets the Speed Search detection mode. 0: Current Detection Type 1: Speed Estimation Type 0, 1 0 A A − 1C0 135
14 b3-25 Speed Search Retry Interval Time Sets the wait time before Speed Search restarts. 0 to 30.0 0.5 s A A A 1C8 135
15 b3-29 <5> Speed Search Induced Voltage Level Performs Speed Search when the motor induced voltage exceeds the set level. This setting rarely needs to be changed. If changes are necessary, try lowering this value in small increments. If set too low, then the drive will not perform Speed Search. 0 to 10 10% – – A 77C 135
16 b4-01 Timer Function On-Delay Time Used in conjunction with a multi-function digital input (H1- oo = 18) and a multi-function digital output (H2-□□ = 12) programmed for the timer function. This sets the amount of time between digital input closure and digital output activation. 0.0 to 300.0 0.0 s A A A 1A3 135
17 b4-02 Timer Function Off-Delay Time Used in conjunction with a multi-function digital input (H1- oo = 18) and a multi-function digital output programmed for the timer function. This sets the amount of time the output remains activated after the digital input is opened. 0.0 to 300.0 0.0 s A A A 1A4 135

Manual — PID parameters — page 359

Source reference: SIEP C71060618F, December 2016, physical PDF page 359. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

B.2 Parameter Table

B

List Parameter

b5-01 | PID Function Setting

b5-02 <6> | Proportional Gain Setting (P)

b5-03 <6> | Integral Time Setting (I)

b5-04 <6> | Integral Limit Setting

b5-05 <6> | Derivative Time (D)

b5-06 <6> | PID Output Limit

b5-07 <6> | PID Offset Adjustment

b5-08 <6> | PID Primary Delay Time Constant

b5-09 | PID Output Level Selection

b5-10 | PID Output Gain Setting

b5-11 | PID Output Reverse Selection

b5-12 | PID Feedback Reference Missing Detection Selection

b5-13 | PID Feedback Loss Detection Level

b5-14 | PID Feedback Loss Detection Time

b5-15 | PID Sleep Function Start Level

b5-16 | PID Sleep Delay Time

b5-17 | PID Accel/Decel Time

b5-18 | PID Setpoint Selection

Parameter catalogue PDF359 section1 — PDF page 359

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 b5-01 PID Function Setting Sets the PID control mode. 0: Disabled 1: Enable (PID output = freq. ref., PID input is D-controlled) 2: (PID output = freq. ref., PID feedback is D-controlled) 3: Enable (PID output added to freq. ref., PID input is D- controlled) 4: Enable (PID output added to freq. ref., PID feedback is D- controlled) 0 to 4 0 A A A 1A5 139
2 b5-02 <6> Proportional Gain Setting (P) Sets the proportional gain of the PID controller. A setting of 0.00 disables P control. 0.00 to 25.00 1.00 A A A 1A6 139
3 b5-03 <6> Integral Time Setting (I) Sets the integral time for the PID controller. A setting of 0.0 s disables integral control. 0.0 to 360.0 1.0 s A A A 1A7 139
4 b5-04 <6> Integral Limit Setting Sets the maximum output possible from the integrator. 0.0 to 100.0 100.0 % A A A 1A8 139
5 b5-05 <6> Derivative Time (D) Sets D control derivative time. A setting of 0.00 s disables derivative control. 0.00 to 10.00 0.00 s A A A 1A9 140
6 b5-06 <6> PID Output Limit Sets the maximum output possible from the entire PID controller. 0.0 to 100.0 100.0 % A A A 1AA 140
7 b5-07 <6> PID Offset Adjustment Applies an offset to the PID controller output. -100.0 to +100.0 0.0% A A A 1AB 140
8 b5-08 <6> PID Primary Delay Time Constant Sets the amount of time for the filter on the output of the PID controller. 0.00 to 10.00 0.00 s A A A 1AC 140
9 b5-09 PID Output Level Selection Sets the PID controller output direction. 0: Normal Output (direct acting) 1: Reverse Output (reverse acting) 0, 1 0 A A A 1AD 140
10 b5-10 PID Output Gain Setting Sets the gain applied to the PID output. 0.00 to 25.00 1.00 A A A 1AE 140
11 b5-11 PID Output Reverse Selection Sets the drive operation with negative PID output. 0: Negative PID output triggers zero limit and drive stops. 1: Rotation direction reverses with negative PID output. When using setting 1 make sure, reverse operation is permitted by parameter b1-04. 0, 1 0 A A A 1AF 140
12 b5-12 PID Feedback Reference Missing Detection Selection Configures the PID feedback loss detection. With all setting a digital output programmed for H2-01/02/03 = 3E/3F (PID feedback low/PID feedback high) is operated when the detection condition becomes true. 0: Digital output only. 1: Feedback loss detected when PID enabled. Alarm output, operation is continued without triggering a fault contact. 2: Feedback loss detected when PID enabled. Fault output, operation is stopped and a fault contact is triggered. 3: Feedback loss detection even when PID is disabled by digital input. No alarm/fault output. 4: PID Feedback error detection even when PID is disabled by digital input. An alarm is triggered and the drive continues to run. 5: PID Feedback error detection even when PID is disabled by digital input. Fault is triggered and output is shut off. 0 to 5 0 A A A 1B0 141
13 b5-13 PID Feedback Loss Detection Level Sets the PID feedback loss detection level. 0 to 100 0% A A A 1B1 142
14 b5-14 PID Feedback Loss Detection Time Sets the PID feedback loss detection delay time in terms of seconds. 0.0 to 25.5 1.0 s A A A 1B2 142
15 b5-15 PID Sleep Function Start Level Sets the sleep function start frequency. Note: Also enabled when PID is not active. 0.0 to 400.0 0.0 Hz A A A 1B3 142
16 b5-16 PID Sleep Delay Time Sets the sleep function delay time. 0.0 to 25.5 0.0 s A A A 1B4 143
17 b5-17 PID Accel/Decel Time Applies an accel/decel time to the PID setpoint. 0 to 255 0 s A A A 1B5 143
18 b5-18 PID Setpoint Selection Selects b5-19 as PID setpoint value. 0: Disabled 1: Enabled, b5-19 becomes PID target 0, 1 0 A A A 1DC 143

Manual — PID dwell and energy savings — page 360

Source reference: SIEP C71060618F, December 2016, physical PDF page 360. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

b6: Dwell Function Use b6 parameters to configure dwell function operation.

b8: Energy Saving Use b8 parameters to configure the energy saving/conservation drive function.

B.2 Parameter Table

b5-19 | PID Setpoint Value

b5-20 | PID Setpoint Scaling

b5-34 <6> | PID Output Lower Limit

b5-35 <6> | PID Input Limit

b5-36 | PID Feedback High Detection Level

b5-37 | PID Feedback High Level Detection Time

b5-38 | PID Setpoint / User Display

b5-39 | PID Setpoint Display Digits

b5-40 <8> | Frequency Reference Monitor Content during PID

b5-47 <5> | Reverse Operation Selection 2 by PID Output

b6-01 | Dwell Reference at Start

b6-02 | Dwell Time at Start

b6-03 | Dwell Frequency at Stop

b6-04 | Dwell Time at Stop

b8-01 | Energy Saving Control Selection

b8-02 <6> | Energy Saving Gain

b8-03 <6> | Energy Saving Control Filter Time Constant

b8-04 | Energy Saving Coefficient Value

Parameter catalogue PDF360 section1 — PDF page 360

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 b5-19 PID Setpoint Value Sets the PID target value when b5-18 = 1. 0.00 to 100.00 0.00 % A A A 1DD 143
2 b5-20 PID Setpoint Scaling Sets the units for setting/display b5-19, and for parameter monitors U5-01 (PID Feedback) and U5-04 (PID Setpoint). 0: 0.01Hz units 1: 0.01% units (100% = max output frequency) 2: r/min (number of motor poles must be set up) 3: User-set (set to b5-38 and b5-39) 0 to 3 1 A A A 1E2 143
3 b5-34 <6> PID Output Lower Limit Sets the minimum output possible from the PID controller. -100.0 to +100.0 0.00 % A A A 19F 144
4 b5-35 <6> PID Input Limit Limits the PID control input (deviation signal). Acts as a bipolar limit. 0.0 to 1000.0 1000. 0% A A A 1A0 144
5 b5-36 PID Feedback High Detection Level Sets the PID feedback high detection level. 0 to 100 100% A A A 1A1 142
6 b5-37 PID Feedback High Level Detection Time Sets the PID feedback high level detection delay time. 0.0 to 25.5 1.0 s A A A 1A2 142
7 b5-38 PID Setpoint / User Display Sets the display value of U5-01 and U5-04 when the maximum frequency is output. Changeable only if b5-20 = 3. 0 to 60000: User-Set Display if b5-20 = 3 1 to 60000 <7> A A A 1FE 144
8 b5-39 PID Setpoint Display Digits Sets the number of digits of U5-01 and U5-04. Changeable only if b5-20 = 3. 0: No decimal places 1: One decimal places 2: Two decimal places 3: Three decimal places 0 to 3 <7> A A A 1FF 144
9 b5-40 <8> Frequency Reference Monitor Content during PID 0: Display the frequency reference (U1-01) after PID compensation has been added. 1: Display the frequency reference (U1-01) before PID compensation has been added. 0, 1 0 A A A 17F 144
10 b5-47 <5> Reverse Operation Selection 2 by PID Output Reverses operation selection when b5-01 = 3 or 4 0: Zero limit when PID output is a negative value 1: Reverse operation when PID output is a negative value (Zero limit if the reverse operation is prohibited by b1-04) 0, 1 1 A A A 17D 144
11 b6-01 Dwell Reference at Start The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. 0.0 to 400.0 0.0 Hz A A A 1B6 145
12 b6-02 Dwell Time at Start The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. 0.0 to 10.0 0.0 s A A A 1B7 145
13 b6-03 Dwell Frequency at Stop The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. 0.0 to 400.0 0.0 Hz A A A 1B8 145
14 b6-04 Dwell Time at Stop The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. 0.0 to 10.0 0.0 s A A A 1B9 145
15 b8-01 Energy Saving Control Selection Selects the Energy Savings function. 0: Disabled 1: Enabled 0, 1 0 A A − 1CC 145
16 b8-02 <6> Energy Saving Gain Sets energy savings control gain when in Open Loop Vector Control. 0.0 to 10.0 0.7 − A − 1CD 145
17 b8-03 <6> Energy Saving Control Filter Time Constant Sets energy saving control filter time constant when in Open Loop Vector Control. 0.00 to 10.00 0.50 <4> − A − 1CE 145
18 b8-04 Energy Saving Coefficient Value Sets the Energy Saving coefficient and is used to fine adjustments in V/f Control. 0.0 to 655.00 <9> <10> A − − 1CF 146

Manual — Energy notes and acceleration parameters — page 361

Source reference: SIEP C71060618F, December 2016, physical PDF page 361. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control. <2> A coasting motor may require a braking resistor circuit to bring the motor to a stop in the required time. <3> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <4> Default setting value is dependent on parameter o2-04, Drive Model Selection. <5> Available in drive software versions PRG: 1020 and later. <6> Parameter can be changed during Run. <7> Default setting is dependent on parameter b5-20, PID Setpoint Scaling. <8> Available in drive software versions PRG: 1014 and later. <9> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. <10> Parameter value is changed if E2-11 is manually changed or changed by Auto-Tuning. <11> Available in drive software versions PRG: 1022 and later. <12> Default setting is determined by A1-02, Control Method Selection

u C: Tuning

C parameters are used to adjust the acceleration and deceleration times, S-curves, slip and torque compensation functions and carrier frequency selections.

C1: Acceleration and Deceleration Times Use C1 parameters to configure motor acceleration and deceleration.

B.2 Parameter Table

B

List Parameter

b8-05 | Power Detection Filter Time

b8-06 | Search Operation Voltage Limit

C1-01 <1> | Acceleration Time 1

C1-02 <1> | Deceleration Time 1

C1-03 <1> | Acceleration Time 2

C1-04 <1> | Deceleration Time 2

C1-05 <1> | Acceleration Time 3 (Motor 2 Accel Time 1)

C1-06 <1> | Deceleration Time 3 (Motor 2 Decel Time 1)

C1-07 <1> | Acceleration Time 4 (Motor 2 Accel Time 2)

C1-08 <1> | Deceleration Time 4 (Motor 2 Decel Time 2)

C1-09 | Fast-Stop Time

C1-10 | Accel/Decel Time Setting Units

Parameter catalogue PDF361 section1 — PDF page 361

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 b8-05 Power Detection Filter Time Sets a filter time for the Power Detection used by Energy Savings in V/f Control. 0 to 2000 20 ms A − − 1D0 146
2 b8-06 Search Operation Voltage Limit Sets the limit for the voltage search operation performed by Energy Savings in V/f Control. Set as a percentage of the motor base voltage. Disabled when set to 0%. 0 to 100 0% A − − 1D1 146

Parameter catalogue PDF361 section2 — PDF page 361

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 C1-01 <1> Acceleration Time 1 Sets the time to accelerate from 0 to maximum frequency. 0.0 to 6000.0 <2> 10.0 s S S S 200 147
2 C1-02 <1> Deceleration Time 1 Sets the time to decelerate from maximum frequency to 0. 0.0 to 6000.0 <2> 10.0 s S S S 201 147
3 C1-03 <1> Acceleration Time 2 Sets the time to accelerate from 0 to maximum frequency when Accel/Decel times 2 are selected by a digital input. 0.0 to 6000.0 <2> 10.0 s A A A 202 147
4 C1-04 <1> Deceleration Time 2 Sets the time to decelerate from maximum frequency to 0 when Accel/Decel times 2 are selected by a digital input. 0.0 to 6000.0 <2> 10.0 s A A A 203 147
5 C1-05 <1> Acceleration Time 3 (Motor 2 Accel Time 1) Sets the time to accelerate from 0 to maximum frequency when Accel/Decel times 3 are selected by a digital input. 0.0 to 6000.0 <2> 10.0 s A A A 204 147
6 C1-06 <1> Deceleration Time 3 (Motor 2 Decel Time 1) Sets the time to decelerate from maximum frequency to 0 when Accel/Decel times 3 are selected by a digital input. 0.0 to 6000.0 <2> 10.0 s A A A 205 147
7 C1-07 <1> Acceleration Time 4 (Motor 2 Accel Time 2) Sets the time to accelerate from 0 to maximum frequency when Accel/Decel times 4 are selected by a digital input. 0.0 to 6000.0 <2> 10.0 s A A A 206 147
8 C1-08 <1> Deceleration Time 4 (Motor 2 Decel Time 2) Sets the time to decelerate from maximum frequency to 0 when Accel/Decel times 4 are selected by a digital input. 0.0 to 6000.0 <2> 10.0 s A A A 207 147
9 C1-09 Fast-Stop Time Sets the time to decelerate from maximum frequency to 0 for the multi-function input fast-stop function. Note: This parameter is also used by selecting “Fast-Stop” as a Stop Method when a fault is detected. 0.0 to 6000.0 <2> 10.0 s A A A 208 148
10 C1-10 Accel/Decel Time Setting Units Sets the resolution of C1-01 to C1-09. 0: 0.01 s (0.00 to 600.00 s) 1: 0.1 s (0.0 to 6000.0 s) 0, 1 1 A A A 209 148

Manual — S-curve and slip compensation — page 362

Source reference: SIEP C71060618F, December 2016, physical PDF page 362. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

C2: S-Curve Characteristics Use C2 parameters to configure S-curve operation.

C3: Slip Compensation Use C3 parameters to configure the slip compensation function.

C4: Torque Compensation Use C4 parameters to configure Torque Compensation function.

B.2 Parameter Table

C1-11 | Accel/Decel Time Switching Frequency

C1-14 <3> | Accel/Decel Rate Frequency

C2-01 | S-Curve Characteristic at Accel Start

C2-02 | S-Curve Accel End Characteristic at

C2-03 | S-Curve Characteristic at Decel Start

C2-04 | S-Curve Characteristic at Decel End

C3-01 <1> | Slip Compensation Gain

C3-02 | Slip Compensation Primary Delay Time

C3-03 | Slip Compensation Limit

C3-04 | Slip Compensation Selection during Regeneration

C3-05 | Output Voltage Limit Operation Selection

C3-18 <10> | Output Voltage Limit Level

Parameter catalogue PDF362 section1 — PDF page 362

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 C1-11 Accel/Decel Time Switching Frequency Sets the frequency for automatic acceleration/deceleration switching. Below set frequency: Accel/Decel Time 4 Above set frequency: Accel/Decel Time 1 The multi-function input “Accel/Decel Time 1” or “Accel/ Decel Time 2” take priority. 0.0 to 400.0 Hz 0.0 Hz A A A 20A 149
2 C1-14 <3> Accel/Decel Rate Frequency Sets the base frequency used to calculate acceleration and deceleration times. When set to 0.0 Hz, the drive calculates the time required to accelerate from 0 Hz to E1-04, and decelerate from E1-04 down to 0 Hz (conventional setting). When set to any other value above 0.0 Hz, the drive calculates the time required to accelerate from 0 Hz to C1-14, and to decelerate from C1-14 down to 0 Hz. 0.0 to 400.0 Hz 0.0 Hz A A A 264 149
3 C2-01 S-Curve Characteristic at Accel Start The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. 0.00 to 10.00 0.20 s <4> A A A 20B 150
4 C2-02 S-Curve Characteristic at Accel End The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. 0.00 to 10.0 0.20 s A A A 20C 150
5 C2-03 S-Curve Characteristic at Decel Start The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. 0.00 to 10.0 0.20 s A A A 20D 150
6 C2-04 S-Curve Characteristic at Decel End The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. 0.00 to 10.0 0.00 s A A A 20E 150
7 C3-01 <1> Slip Compensation Gain Sets the slip compensation gain. Decides for what amount the output frequency is boosted in order to compensate the slip. Note: Adjustment is not normally required. 0.0 to 2.5 0.0 <4> A A − 20F 151
8 C3-02 Slip Compensation Primary Delay Time Adjusts the slip compensation function delay time. Decrease the setting when the slip compensation response is too slow, increase it when the speed is not stable. Disabled when Simple V/f Control with PG (H6-01 = 3) is used. 0 to 10000 2000 ms <4> A A − 210 151
9 C3-03 Slip Compensation Limit Sets the slip compensation upper limit. Set as a percentage of motor rated slip (E2-02). Disabled when Simple V/f Control with PG (H6-01 = 3) is used. 0 to 250 200% A A − 211 151
10 C3-04 Slip Compensation Selection during Regeneration Selects slip compensation during regenerative operation. 0: Disabled 1: Enabled Using the Slip Compensation function during regeneration may require a braking option to handle momentary increasing regenerative energy. 0, 1 0 A A − 212 152
11 C3-05 Output Voltage Limit Operation Selection Selects if the motor magnetic flux is reduced during output voltage saturation. 0: Disabled 1: Enabled 0, 1 0 <4> − A − 213 152
12 C3-18 <10> Output Voltage Limit Level Sets the maximum percentage of output voltage reduction when C3-05 is enabled. 70.0 to 100.0 90.0% − A − 263 152

Manual — Torque speed and carrier controls — page 363

Source reference: SIEP C71060618F, December 2016, physical PDF page 363. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

C5: Speed Control (ASR) Use C5 parameters to configure the Automatic Speed Regulator (ASR). C5 parameters are available only when using V/f Control with Simple PG Feedback (H6-01 = 3).

C6: Carrier Frequency Use C6 parameters to configure the carrier frequency drive settings.

B.2 Parameter Table

B

List Parameter

C4-01 <5> | Torque Compensation Gain

C4-02 | Torque Compensation Primary Delay Time

C4-03 | Torque Compensation at Forward Start

C4-04 | Torque Compensation at Reverse Start

C4-05 | Torque Compensation Time Constant

C4-06 | Torque Compensation Primary Delay Time 2

C5-01 <1> | ASR Proportional Gain 1

C5-02 <1> | ASR Integral Time 1

C5-03 <1> | ASR Proportional Gain 2

C5-04 <1> | ASR Integral Time 2

C5-05 <1> | ASR Limit

C6-01 | Drive Duty Selection

C6-02 | Carrier Frequency Selection

Parameter catalogue PDF363 section1 — PDF page 363

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 C4-01 <5> Torque Compensation Gain V/f Control: Sets the gain for the automatic torque (voltage) boost function and helps to produce better starting torque. Increase this setting when using a long motor cable or when the motor is significantly smaller than the drive capacity. Decrease this setting when motor oscillation occurs. Set the value so that the current at low speed does not exceeds the drives rated current. Open Loop Vector: Sets the torque compensation function gain. Normally no change is required. 0.00 to 2.50 1.00 <4> A A A 215 152
2 C4-02 Torque Compensation Primary Delay Time Sets the torque compensation filter time. Increase this setting when motor oscillation occurs. Reduce the setting if there is not enough response from the motor. 0 to 60000 200 ms <6> A A A 216 153
3 C4-03 Torque Compensation at Forward Start Sets torque compensation at forward start as a percentage of motor torque. 0.0 to 200.0 0.0% − A − 217 153
4 C4-04 Torque Compensation at Reverse Start Sets torque compensation at reverse start as a percentage of motor torque. -200.0 to 0.0 0.0% − A − 218 153
5 C4-05 Torque Compensation Time Constant Sets the time constant for torque compensation at forward start and reverse start (C4-03 and C4-04). The filter is disabled if the time is set to 4 ms or less. 0 to 200 10 ms – A – 219 153
6 C4-06 Torque Compensation Primary Delay Time 2 Sets the torque compensation time 2. When an ov fault occurs with sudden load changes or at the and of an acceleration, increase the setting. Note: Adjustment is not normally required. If adjusted then AFR time 2 (n2-03) should be adjusted too. 0 to 10000 150 ms – A – 21AH 153
7 C5-01 <1> ASR Proportional Gain 1 Sets the proportional gain of the speed control loop (ASR). 0.00 to 300.00 0.20 A – – 21B 155
8 C5-02 <1> ASR Integral Time 1 Sets the integral time of the speed control loop (ASR). 0.000 to 10.000 0.200 A – – 21C 155
9 C5-03 <1> ASR Proportional Gain 2 Sets the speed control gain 2 of the speed control loop (ASR). 0.00 to 300.00 0.02 A − − 21D 155
10 C5-04 <1> ASR Integral Time 2 Sets the integral time 2 of the speed control loop (ASR). 0.000 to 10.000 0.050 s A – – 21E 155
11 C5-05 <1> ASR Limit Sets the upper limit for the speed control loop (ASR) as a percentage of the maximum output frequency (E1-04). 0.0 to 20.0 5.0% A – – 21F 155
12 C6-01 Drive Duty Selection Selects the load rating for the drive. 0: Heavy Duty (HD) for constant torque applications. 1: Normal Duty (ND) for variable torque applications. This setting affects the Rated output current and overload tolerance of the drive. 0, 1 1 S S S 223 155
13 C6-02 Carrier Frequency Selection Selects the carrier frequency 1 : 2.0 kHz 2 : 5.0 kHz 3 : 8.0 kHz 4 : 10.0 kHz 5 : 12.5 kHz 6 : 15.0 kHz 7 : Swing PWM1 (Audible sound 1) 8 : Swing PWM2 (Audible sound 2) 9 : Swing PWM3 (Audible sound 3) A : Swing PWM4 (Audible sound 4) <3> B: Leakage Current Rejection PWM C to E: No setting possible F : User defined (determined by C6-03 through C6-05) <7> <8> S S S 224 156

Manual — Carrier conditions and frequency references — page 364

Source reference: SIEP C71060618F, December 2016, physical PDF page 364. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

<1> Parameter can be changed during run. <2> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range becomes 0.00 to 600.00 seconds. <3> Available in drive software versions PRG: 1020 and later. <4> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <5> Parameter cannot be changed during run when parameter A1-02 = 5-PM OLV Control. <6> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control. <7> Setting range is determined by the drive software version. PRG: 1020 and later: 1 to B; F PRG: 1018 and earlier: 1 to A; F <8> Default setting value is dependent on parameters o2-04, Drive Model Selection, A1-02, Control Method Selection and C6-01, Drive Duty Selection. <9> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection. <10> Available in drive software versions PRG: 1024 and later.

u d: References

Reference parameters are used to set the various frequency reference values during operation.

d1: Frequency Reference Use d1 parameters to configure the drive frequency reference.

B.2 Parameter Table

C6-03 | Carrier Frequency Upper Limit

C6-04 | Carrier Frequency Lower Limit

C6-05 | Carrier Frequency Proportional Gain

d1-01 <1> | Frequency Reference 1

d1-02 <1> | Frequency Reference 2

d1-03 <1> | Frequency Reference 3

d1-04 <1> | Frequency Reference 4

d1-05 <1> | Frequency Reference 5

d1-06 <1> | Frequency Reference 6

Parameter catalogue PDF364 section1 — PDF page 364

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 C6-03 Carrier Frequency Upper Limit Note: Set C6-02 to F before setting C6-03. Open Loop Vector: C6-03 defines the fixed carrier frequency if C6-02 = F. V/f Control: C6-03 and C6-04 set upper and lower limits for the carrier frequency. Diagram labels: carrier frequency,C6-03,C6-04; output frequency,E1-04 max output frequency; slope label output frequency ×(C6-05)×K. The coefficient K depends on C6-03: C6-03 ≥ 10.0 kHz: K = 3 10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2 5.0 kHz > C6-03: K = 1 When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value). Exact graph geometry original-only. 1.0 to 15.0 <9> A A A 225 157
2 C6-04 Carrier Frequency Lower Limit Note: Set C6-02 to F before setting C6-03. Open Loop Vector: C6-03 defines the fixed carrier frequency if C6-02 = F. V/f Control: C6-03 and C6-04 set upper and lower limits for the carrier frequency. Diagram labels: carrier frequency,C6-03,C6-04; output frequency,E1-04 max output frequency; slope label output frequency ×(C6-05)×K. The coefficient K depends on C6-03: C6-03 ≥ 10.0 kHz: K = 3 10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2 5.0 kHz > C6-03: K = 1 When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value). Exact graph geometry original-only. 1.0 to 15.0 <9> A - - 226 157
3 C6-05 Carrier Frequency Proportional Gain Sets the relationship of output frequency to carrier frequency when C6-02 = F. 00 to 99 <9> A - - 227 157

Parameter catalogue PDF364 section2 — PDF page 364

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 d1-01 <1> Frequency Reference 1 Frequency reference. Refer to b1-01: Frequency Reference Selection 1 on page 121 for instructions to use d1-01 as the main frequency reference. 0.00 to 400.00 Hz <2> <3> 0.00 Hz S S S 280 160
2 d1-02 <1> Frequency Reference 2 Frequency reference when digital input "Multi-Step Speed Reference 1" (H1-□□ = 3) is on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz S S S 281 160
3 d1-03 <1> Frequency Reference 3 Frequency reference when digital input "Multi-Step Speed Reference 2” (H1-□□ = 4) is on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz S S S 282 160
4 d1-04 <1> Frequency Reference 4 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2" (H1-□□ = 3 and 4) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz S S S 283 160
5 d1-05 <1> Frequency Reference 5 Frequency reference when digital input "Multi-Step Speed Reference 3" (H1-□□ = 5) is on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 284 160
6 d1-06 <1> Frequency Reference 6 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3 " (H1-□□ = 3 and 5) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 285 160

Manual — Frequency limits and jump controls — page 365

Source reference: SIEP C71060618F, December 2016, physical PDF page 365. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

d2: Frequency Upper and Lower Limits Use d2 parameters to configure the frequency reference limits.

d3: Jump Frequency Use d3 parameters to configure the drive Jump Frequency settings.

d4: Frequency Reference Hold Use d4 parameters to configure the drive frequency reference hold function.

B.2 Parameter Table

B

List Parameter

d1-07 <1> | Frequency Reference 7

d1-08 <1> | Frequency Reference 8

d1-09 <1> | Frequency Reference 9

d1-10 <1> | Frequency Reference 10

d1-11 <1> | Frequency Reference 11

d1-12 <1> | Frequency Reference 12

d1-13 <1> | Frequency Reference 13

d1-14 <1> | Frequency Reference 14

d1-15 <1> | Frequency Reference 15

d1-16 <1> | Frequency Reference 16

d1-17 <1> | Jog Frequency Reference

d2-01 | Frequency Reference Upper Limit

d2-02 | Frequency Reference Lower Limit

d2-03 | Master Speed Reference Lower Limit

d3-01 | Jump Frequency 1

d3-02 | Jump Frequency 2

d3-03 | Jump Frequency 3

d3-04 | Jump Frequency Width

Parameter catalogue PDF365 section1 — PDF page 365

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 d1-07 <1> Frequency Reference 7 Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3" (H1-□□ = 4 and 5) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 286 160
2 d1-08 <1> Frequency Reference 8 Frequency reference when multi-function input "Multi-Step speed reference 1, 2, 3" (H1-□□ = 3, 4, 5) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 287 160
3 d1-09 <1> Frequency Reference 9 Frequency reference when multi-function input "Multi-Step Speed Reference 4" (H1-□□= 32) is on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 288 160
4 d1-10 <1> Frequency Reference 10 Frequency reference when digital input "Multi-Step Speed Reference 1, 4" (H1-□□ = 3 and 32) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 28B 160
5 d1-11 <1> Frequency Reference 11 Frequency reference when digital inputs "Multi-Step Speed Reference 2, 4" (H1-□□ = 4 and 32) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 28C 160
6 d1-12 <1> Frequency Reference 12 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2, 4" (H1-□□ = 3, 4, 32) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 28D 160
7 d1-13 <1> Frequency Reference 13 Frequency reference when digital inputs "Multi-Step Speed Reference 3, 4" (H1-□□ = 5 and 32) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 28E 160
8 d1-14 <1> Frequency Reference 14 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3, 4" (H1-□□ = 3, 5, 32) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 28F 160
9 d1-15 <1> Frequency Reference 15 Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3, 4" (H1-□□ = 4, 5, 32) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 290 160
10 d1-16 <1> Frequency Reference 16 Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2, 3, 4" (H1-□□ = 3, 4, 5, 32) are on. 0.00 to 400.00 Hz <2> <3> 0.00 Hz A A A 291 160
11 d1-17 <1> Jog Frequency Reference Frequency reference when digital inputs "Jog Frequency Reference", "Forward Jog", or "Reverse Jog." are on. "Jog Frequency Reference" has priority over "Multi-Step Speed Reference 1 to 16”. 0.00 to 400.00 <2> <3> Hz 6.00 Hz S S S 292 160
12 d2-01 Frequency Reference Upper Limit Sets the frequency reference upper limit as a percentage of maximum output frequency (E1-04). Output speed is limited to this value even if the frequency reference is higher. This limit applies to all frequency reference sources. 0.0 to 110.0 100.0 % A A A 289 161
13 d2-02 Frequency Reference Lower Limit Sets the frequency reference lower limit as a percentage of maximum output frequency (E1-04). Output speed is limited to this value even if the frequency reference is lower. This limit applies to all frequency reference sources. 0.0 to 110.0 0.0% A A A 28A 161
14 d2-03 Master Speed Reference Lower Limit Sets the minimum frequency reference lower limit if the frequency reference is input using an analog input. Set as a percentage of maximum output frequency (E1-04). The higher of both values d2-02 and d2-03 will be the lower limit. 0.0 to 110.0 0.0% A A A 293 162
15 d3-01 Jump Frequency 1 d3-01 to d3-04 allow programming of three prohibited frequency reference points for eliminating problems with resonant vibration of the motor / machine. This feature does not eliminate the selected frequency values, but accelerates and decelerates the motor through the prohibited bandwidth. The parameters must be according to the rule d3-01 ≥ d3-02 ≥ d3-03. 0.0 to 400.0 0.0 Hz A A A 294 162
16 d3-02 Jump Frequency 2 d3-01 to d3-04 allow programming of three prohibited frequency reference points for eliminating problems with resonant vibration of the motor / machine. This feature does not eliminate the selected frequency values, but accelerates and decelerates the motor through the prohibited bandwidth. The parameters must be according to the rule d3-01 ≥ d3-02 ≥ d3-03. 0.0 to 400.0 0.0 Hz A A A 295 162
17 d3-03 Jump Frequency 3 d3-01 to d3-04 allow programming of three prohibited frequency reference points for eliminating problems with resonant vibration of the motor / machine. This feature does not eliminate the selected frequency values, but accelerates and decelerates the motor through the prohibited bandwidth. The parameters must be according to the rule d3-01 ≥ d3-02 ≥ d3-03. 0.0 to 400.0 0.0 Hz A A A 296 162
18 d3-04 Jump Frequency Width This parameter sets the dead-band width around each selected prohibited frequency reference point. The bandwidth becomes the designated Jump frequency, plus or minus d3-04. 0.0 to 20.0 1.0 Hz A A A 297 162

Manual — Frequency hold and offset — page 366

Source reference: SIEP C71060618F, December 2016, physical PDF page 366. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

d7: Offset Frequency Use d7 parameters to set the offset frequency.

<1> Parameter can be changed during Run. <2> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection. <3> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit. <4> Default setting is determined by the drive software version. PRG: 1016 and later: 100.00% PRG: 1015 and earlier: 0.00 %

B.2 Parameter Table

d4-01 | Frequency Reference Hold Function Selection

d4-03 <1> | Frequency Reference Bias Step (Up/Down 2)

d4-04 <1> | Frequency Reference Bias Accel/Decel (Up/Down 2)

d4-05 <1> | Frequency Reference Bias Operation Mode Selection (Up/Down 2)

d4-06 | Frequency Reference Bias (Up/Down 2)

d4-07 <1> | Analog Frequency Reference Fluctuation Limit (Up/Down 2)

d4-08 <1> | Frequency Upper Limit Reference (Up/Down Bias 2)

d4-09 <1> | Frequency Reference Bias Lower Limit (Up/Down 2)

d4-10 | Up/Down Frequency Reference Limit Selection

d7-01 <1> | Offset Frequency 1

d7-02 <1> | Offset Frequency 2

d7-03 <1> | Offset Frequency 3

Parameter catalogue PDF366 section1 — PDF page 366

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 d4-01 Frequency Reference Hold Function Selection Determines if the frequency reference or frequency reference bias is saved when the Run command is removed or the power goes off. 0: Disabled 1: Enabled This parameter is effective when the multi-function inputs “Accel/Decel Ramp Hold”, “Up/Down” or “Up/Down 2” commands are selected (H1-□□ = A or 10/11 or 75/76). 0, 1 0 A A A 298 162
2 d4-03 <1> Frequency Reference Bias Step (Up/Down 2) Sets the bias added to the frequency reference when the Up/ Down 2 digital inputs are set. When set to 0.00 Hz, the bias value is increased or decreased according to d4-04. When greater than 0.0 Hz, the bias value d4-03 is added or subtracted to/from the frequency reference. The acceleration or deceleration rate is ultimately determined by d4-04. 0.00 to 99.99 Hz 0.00 Hz A A A 2AA 165
3 d4-04 <1> Frequency Reference Bias Accel/Decel (Up/Down 2) Selects how the bias or frequency reference is increased when using the Up/Down 2 function. 0: Use selected accel/decel time. 1: Use Accel/Decel Time 4 (C1-07 and C1-08). 0, 1 0 A A A 2AB 165
4 d4-05 <1> Frequency Reference Bias Operation Mode Selection (Up/Down 2) 0: Bias value is held if no input Up 2 or Down 2 is active. 1: When the Up 2 reference and Down 2 reference are both on or both off, the applied bias becomes 0. Currently selected accel / decel. times are used. Enabled only when d4-03 = 0. 0, 1 0 A A A 2AC 166
5 d4-06 Frequency Reference Bias (Up/Down 2) The Up/Down 2 bias value is saved in d4-06 when the frequency reference is not input by the digital operator. The function depends on the setting of d4-01. It is limited by d4-08 and d4-09. -99.9 to +100.0 0.0% A A A 2AD 166
6 d4-07 <1> Analog Frequency Reference Fluctuation Limit (Up/Down 2) When an Up 2 or Down 2 input is active and the frequency reference value from analog or pulse input changes for more than the level set in d4-07, the bias value is hold and the frequency reference is changed to the new value. After the speed reaches the frequency reference the bias hold is released. 0.1 to +100.0 1.0% A A A 2AE 166
7 d4-08 <1> Frequency Reference Bias Upper Limit (Up/Down 2) Sets the upper limit for the bias and the value that can be saved in d4-06. Set as a percentage of the maximum output frequency E1-04. 0.1 100.0 to <4> A A A 2AF 166
8 d4-09 <1> Frequency Reference Bias Lower Limit (Up/Down 2) Sets the lower limit for the bias and the value that can be saved in d4-06. Set as a percentage of the maximum output frequency E1-04. -99.9 to 0.0 0.0% A A A 2B0 167
9 d4-10 Up/Down Frequency Reference Limit Selection Selects which value is used as frequency reference lower limit if the Up/Down function is used. 0: The lower limit is determined by d2-02 or analog input (H3-02/10 = 0). The higher of both values becomes the reference limit. 1: The lower limit is determined by d2-02. 0 or 1 0 A A A 2B6 167
10 d7-01 <1> Offset Frequency 1 Added to the frequency reference when the digital input “Frequency Offset 1” (H1-□□ = 44) is switched on. -100.0 to +100.0 0.0% A A A 2B2 167
11 d7-02 <1> Offset Frequency 2 Added to the frequency reference when the digital input “Frequency Offset 2” (H1-□□ = 45) is switched on. -100.0 to +100.0 0.0% A A A 2B3 167
12 d7-03 <1> Offset Frequency 3 Added to the frequency reference when the digital input “Frequency Offset 3” (H1-□□ = 46) is switched on. -100.0 to +100.0 0.0% A A A 2B4 167

Manual — Motor voltage pattern and current — page 367

Source reference: SIEP C71060618F, December 2016, physical PDF page 367. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

u E: Motor Parameters

No. Name Description Range Def.

Control Mode Addr. Hex Pg. O V/f PM LV

E1: V/f Pattern Characteristics Use E1 parameters to set V/f characteristics for the motor.

E2: Motor Parameters Use E2 parameters to set motor-related data.

B.2 Parameter Table

B

List Parameter

E1-01 <1> | Input Voltage Setting

E1-03 <2> | V/f Pattern Selection

E1-04 | Maximum Output Frequency

E1-05 <1> | Maximum Output Voltage

E1-06 | Base Frequency

E1-07 | Middle Output Frequency

E1-08 <1> | Middle Output Frequency Voltage

E1-09 | Minimum Output Frequency

E1-10 <1> | Minimum Output Frequency Voltage

E1-11 | Middle Output Frequency 2

E1-12 <1> <7> | Middle Output Frequency Voltage 2

E1-13 <1> <9> | Base Voltage

E2-01 <8> | Motor Current Rated

E2-02 | Motor Rated Slip

Parameter catalogue PDF367 section1 — PDF page 367

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 E1-01 <1> Input Voltage Setting This parameter must be set to the power supply voltage. It sets the maximum and base voltage used by preset V/f patterns (E1-03 = 0 to E) and adjusts levels used by certain functions. WARNING! Electrical Shock Hazard. Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. failure to do so may result in equipment damage and/or death or personal injury. 155 to 255 230 V S S S 300 169
2 E1-03 <2> V/f Pattern Selection Selects a preset V/f pattern. 0: 50 Hz Constant torque 1 1: 60 Hz Constant torque 2 2: 60 Hz Constant torque 3 (50 Hz base) 3: 72 Hz Constant torque 4 (60 Hz base) 4: 50 Hz Variable torque 1 5: 50 Hz Variable torque 2 6: 60 Hz Variable torque 3 7: 60 Hz Variable torque 4 8: 50 Hz High starting torque 1 9: 50 Hz High starting torque 2 A: 60 Hz High starting torque 3 B: 60 Hz High starting torque 4 C: 90 Hz (60 Hz base) D: 120 Hz (60 Hz base) E: 180 Hz (60 Hz base) F: Custom V/f. E1-04 through E1-13 settings define the V/f pattern 0 to F F A A − 302 169
3 E1-04 Maximum Output Frequency E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 40.0 to 400.0 <3> 60 Hz <4> S S S 303 172
4 E1-05 <1> Maximum Output Voltage E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to 255.0 230 V <4> S S S 304 172
5 E1-06 Base Frequency E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. E1-04 0.0 to 60 <4> Hz S S S 305 172
6 E1-07 Middle Output Frequency E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to E1-04 3.0 Hz <3> A A - 306 172
7 E1-08 <1> Middle Output Frequency Voltage E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to 255.0 18.4 V <5> <6> A A - 307 172
8 E1-09 Minimum Output Frequency E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to E1-04 1.5 Hz <5> <4> S S S 308 172
9 E1-10 <1> Minimum Output Frequency Voltage E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to 255.0 13.8 V <5> <6> A A - 309 172
10 E1-11 Middle Output Frequency 2 E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to E1-04 0.0 Hz A A - 30A 172
11 E1-12 <1> <7> Middle Output Frequency Voltage 2 E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to 255.0 0.0 V A A - 30B 172
12 E1-13 <1> <9> Base Voltage E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. 0.0 to 255.0 0.0 V A S - 30C 172
13 E2-01 <8> Motor Rated Current Sets the motor nameplate full load current in amperes (A). Automatically set during Auto-Tuning. Note: Set E2-03 (Motor No-Load Current) before making changes to E2-01. An oPE01 error will be triggered if E2-01 < E2-03. 10 to 200% of drive rated current <9> <10> S S − 30E 173
14 E2-02 Motor Rated Slip Sets the motor rated slip in Hertz. Automatically set during rotational Auto-Tuning. 0.00 to 20.00 <10> A A − 30F 173

Manual — Motor1 values and Motor2 selection — page 368

Source reference: SIEP C71060618F, December 2016, physical PDF page 368. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. Hex Pg. O V/f PM LV

E3: Motor 2 V/f Characteristics Use E3 parameters to set the V/f pattern for a second motor.

B.2 Parameter Table

E2-03 | Motor No-Load Current

E2-04 | Number of Motor Poles

E2-05 | Motor Line-to-Line Resistance

E2-06 | Motor Leakage Inductance

E2-07 | Motor Iron-Core Saturation Coefficient 1

E2-08 | Motor Iron-Core Saturation Coefficient 2

E2-09 | Motor Mechanical Loss

E2-10 | Motor Iron Loss for Torque Compensation

E2-11 | Motor Rated Output

E2-12 | Motor Iron-Core Saturation Coefficient 3

E3-01 | Motor 2 Control Method

Parameter catalogue PDF368 section1 — PDF page 368

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 E2-03 Motor No-Load Current Sets the magnetizing current of the motor in Ampere. Automatically set during rotational Auto-Tuning. Note: Set E2-03 (Motor No-Load Current) before making changes to E2-01. An oPE01 error will be triggered if E2-01 < E2-03. 0 to less than E2-01 <10> A A − 310 173
2 E2-04 Number of Motor Poles Sets the number of motor poles. Automatically set during Auto-Tuning. 2 to 48 4 poles A A − 311 173
3 E2-05 Motor Line-to-Line Resistance Sets the phase-to-phase motor resistance in ohms. Automatically set during Auto-Tuning. 0.000 to 65.000 <11> <10> A A − 312 173
4 E2-06 Motor Leakage Inductance Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. Automatically set during Auto-Tuning. 0.0 to 40.0 <10> A A − 313 174
5 E2-07 Motor Iron-Core Saturation Coefficient 1 Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during Auto-Tuning. 0.00 to 0.50 0.50 − A − 314 174
6 E2-08 Motor Iron-Core Saturation Coefficient 2 Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during Auto-Tuning. E2-07 to 0.75 0.75 − A − 315 174
7 E2-09 Motor Mechanical Loss Sets the motor mechanical loss as a percentage of motor rated power (kW). Adjust in the following circumstances: When there is a large amount of torque loss due to motor bearing friction. When there is a large amount of torque loss. 0.0 to 10.0 0.0% − A − 316 174
8 E2-10 Motor Iron Loss for Torque Compensation Sets the motor iron loss in watts (W). 0 to 65535 <10> A − − 317 174
9 E2-11 Motor Rated Output Sets the motor rated power in kilowatts (kW). Automatically set during Auto-Tuning. (1 HP = 0.746 kW). 0.00 to 650.00 0.40 kW <6> S S − 318 174
10 E2-12 Motor Iron-Core Saturation Coefficient 3 Set to the motor iron saturation coefficient at 130% of magnetic flux. Automatically set during rotational Auto-Tuning. 1.30 to 5.00 1.30 − A − 328 174
11 E3-01 Motor 2 Control Method 0: V/f Control 2: Open Loop Vector (OLV) 0 or 2 0 A A − 319 175

Manual — Motor2 parameters — page 369

Source reference: SIEP C71060618F, December 2016, physical PDF page 369. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. Hex Pg. O V/f PM LV

E4: Motor 2 Parameters Use E4 parameters to control a second motor operating on the same drive.

B.2 Parameter Table

B

List Parameter

E3-04 | Motor 2 Max Output Frequency

E3-05 <1> | Motor 2 Max Voltage

E3-06 | Motor 2 Base Frequency

E3-07 | Motor 2 Mid Output Freq.

E3-08 <1> | Motor 2 Mid Output Freq. Voltage

E3-09 | Motor 2 Min. Output Freq.

E3-10 <1> | Motor 2 Min. Output Freq. Voltage

E3-11 <7> | Motor 2 Mid Output Frequency 2

E3-12 <1> <13> | Motor 2 Mid Output Frequency Voltage 2

E3-13 <1> <9> | Motor 2 Base Voltage

E4-01 | Motor 2 Rated Current

E4-02 | Motor 2 Rated Slip

E4-03 | Motor 2 Rated No- Load Current

E4-04 | Motor 2 Motor Poles

E4-05 | Motor 2 Line-to- Line Resistance

E4-06 | Motor 2 Leakage Inductance

E4-07 | Motor 2 Motor Iron- Core Saturation Coefficient 1

E4-08 | Motor 2 Motor Iron- Core Saturation Coefficient 2

E4-09 | Motor 2 Mechanical Loss

E4-10 | Motor 2 Iron Loss

E4-11 | Motor 2 Rated Capacity

Parameter catalogue PDF369 section1 — PDF page 369

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 E3-04 Motor 2 Max Output Frequency To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 40.0 to 400.0 60 Hz A A − 31A 175
2 E3-05 <1> Motor 2 Max Voltage To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to 255.0 230.0 V A A − 31B 175
3 E3-06 Motor 2 Base Frequency To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to E3-04 60 Hz A A − 31C 175
4 E3-07 Motor 2 Mid Output Freq. To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to E3-04 3.0 Hz <12> A A − 31D 175
5 E3-08 <1> Motor 2 Mid Output Freq. Voltage To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to 255.0 18.4 V <6> <12> A A − 31E 175
6 E3-09 Motor 2 Min. Output Freq. To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to E3-04 1.5 Hz <12> A A − 31F 175
7 E3-10 <1> Motor 2 Min. Output Freq. Voltage To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to 255.0 13.8 V <6> <12> A A − 320 175
8 E3-11 <7> Motor 2 Mid Output Frequency 2 To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to E3-04 0.0 Hz A A − 345 175
9 E3-12 <1> <13> Motor 2 Mid Output Frequency Voltage 2 To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to <1> 255.0 0.0 Vac A A − 346 175
10 E3-13 <1> <9> Motor 2 Base Voltage To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. 0.0 to 255.0 <1> 0.0 Vac A S − 347 175
11 E4-01 Motor 2 Rated Current Sets the motor 2 nameplate full load current in amperes (A). This value is automatically set during Auto-Tuning. 10 to 200% of drive rated current <10> A A − 321 176
12 E4-02 Motor 2 Rated Slip Sets the motor 2 rated slip in Hz. Automatically set during Auto-Tuning. 0.00 to 20.00 <10> A A − 322 176
13 E4-03 Motor 2 Rated No- Load Current Sets the magnetizing current of motor 2 in Ampere. Automatically set during Rotational Auto-Tuning. 0 to less than E4-01 <9> <10> A A − 323 176
14 E4-04 Motor 2 Motor Poles Sets the number of poles of motor 2. This value is automatically set during Auto-Tuning. 2 to 48 4 poles A A − 324 176
15 E4-05 Motor 2 Line-to- Line Resistance Sets the phase-to-phase resistance of motor 2 in ohms. Automatically during Auto-Tuning. 0.000 to 65.000 <11> <10> A A − 325 176
16 E4-06 Motor 2 Leakage Inductance Sets the voltage drop due to motor leakage inductance as a percentage of rated voltage of motor 2. Automatically set during Auto-Tuning. 0.0 to 40.0 <10> A A − 326 176
17 E4-07 Motor 2 Motor Iron- Core Saturation Coefficient 1 Set to the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during Rotational Auto-Tuning. 0.00 to 0.50 0.50 − A − 343 177
18 E4-08 Motor 2 Motor Iron- Core Saturation Coefficient 2 Set to the motor iron saturation coefficient at 75% of magnetic flux. This value is automatically set during Rotational Auto-Tuning. Setting for E4-07 to 0.75 0.75 − A − 344 177
19 E4-09 Motor 2 Mechanical Loss Sets the motor mechanical loss as a percentage of motor rated power (kW) capacity. Adjust in the following circumstances: • When there is a large amount of torque loss due to motor bearing friction. • When there is a large amount of torque loss. 0.00 to 10.0 0.0 − A − 33F 177
20 E4-10 Motor 2 Iron Loss Sets the motor iron loss in watts. 0 to 65535 <10> Α − − 340 177
21 E4-11 Motor 2 Rated Capacity Sets the motor rated capacity in kW. Automatically set during Auto-Tuning. 0.00 to 650.00 <6> A A − 327 177

Manual — PM motor parameters — page 370

Source reference: SIEP C71060618F, December 2016, physical PDF page 370. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. Hex Pg. O V/f PM LV

E5: PM Motor Parameters

<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.

B.2 Parameter Table

E4-12 | Motor 2 Iron-Core Saturation Coefficient 3

E4-14 <14> | Motor 2 Slip Compensation Gain

E4-15 | Torque Compensation Gain - Motor 2

E5-01 <2> | Motor Code Selection (for PM motor)

E5-02 <2> | Motor Rated Capacity (for PM motor)

E5-03 <2> | Motor Current Rated

E5-04 <2> | Motor Poles

E5-05 <2> | Motor Resistance Stator

E5-06 <2> | Motor Inductance d Axis

E5-07 <2> | Motor Inductance q Axis

E5-09 <2> | Motor Voltage Induction Constant 1

E5-24 <2> | Motor Voltage Induction Constant 2

E5-39 <18> | Current Detection Delay Time

Parameter catalogue PDF370 section1 — PDF page 370

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 E4-12 Motor 2 Iron-Core Saturation Coefficient 3 Set to the motor iron saturation coefficient at 130% of magnetic flux. Automatically set during Rotational Auto-Tuning. 1.30 to 5.00 1.30 − A − 342 177
2 E4-14 <14> Motor 2 Slip Compensation Gain Sets the slip compensation gain for motor 2. The function is the same as C3-01 for motor 1. Refer to C3-01: Slip Compensation Gain on page 151. 0.0 to 2.5 0.0 <12> A A − 341 177
3 E4-15 Torque Compensation Gain - Motor 2 Sets the torque compensation gain for motor 2. The function is the same as C4-01 for motor 1. Refer to C4-01: Torque Compensation Gain on page 152. 1.00 to 2.50 1.00 A A − 341 177
4 E5-01 <2> Motor Code Selection (for PM motor) Enter the Yaskawa motor code for the PM motor being used. Various motor parameters are automatically set based on the value of this parameter. Note: Set to FFFF when using a specialized, custom, or non- Yaskawa motor. For all other motors: diagram0000 with Motor Voltage Class and Capacity callout;motor series0:Pico Motor(SMRA Series),1:Derated Torque for IPM Motors(SSR1 Series);speed series0:1800r/min,1:3600r/min,2:1750r/min,3:1450r/min,4:1150r/min,F:Special Motor. Exact digit/bracket layout original-only; no motor code inferred. All motor parameters are reinitialized to factory settings when this parameter is set. 0000 to FFFF <6> <15> − − S 329 178
5 E5-02 <2> Motor Rated Capacity (for PM motor) Sets the rated capacity of the motor. 0.10 18.50 to <4> − − S 32A 178
6 E5-03 <2> Motor Current Rated Sets the motor rated current in amps. 10 to 200% of drive rated current <9> <16> − − S 32B 178
7 E5-04 <2> Motor Poles Sets the number of motor poles. 2 to 48 <4> − − S 32C 178
8 E5-05 <2> Motor Stator Resistance Set the resistance for each motor phase in units of 0.001 Ω. 0.000 65.000 to <4> − − S 32D 179
9 E5-06 <2> Motor d Axis Inductance Sets the d axis inductance in units of 0.01 mH. 0.00 300.00 to <4> − − S 32E 179
10 E5-07 <2> Motor q Axis Inductance Sets the q axis inductance in units of 0.01 mH. 0.00 600.00 to <4> − − S 32F 179
11 E5-09 <2> Motor Induction Voltage Constant 1 Set the induced phase peak voltage in units of 0.1 mV (rad/ s) [electrical angle]. Set this parameter when using a Yaskawa SSR1 series PM motor with derate torque, or a Yaskawa SST4 series motor with constant torque. When setting this parameter, E5-24 should be set to 0. An alarm will be triggered if both E5-09 and E5-24 are set to 0, or if neither parameter is set to 0. 2000.0 0.0 to <4> − − S 331 179
12 E5-24 <2> Motor Induction Voltage Constant 2 Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using a Yaskawa SMRA Series SPM Motor. When setting this parameter, E5-09 should be set to 0. An alarm will be triggered if both E5-09 and E5-24 are set to 0, or if neither parameter is set to 0. If E5-03 (Motor Rated Current) is set to 0, however, then an alarm will not be triggered when both E5-09 and E5-24 are set to 0. <17> <4> − − S 353 179
13 E5-39 <18> Current Detection Delay Time Sets the current detection delay time at the time of d-Axis and q-Axis current feedback calculation. Changing this parameter from the default setting is not normally required. -1000 to 1000 0 µs A A A 5E2 179

Manual — Motor notes and PG options — page 371

Source reference: SIEP C71060618F, December 2016, physical PDF page 371. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

<2> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <3> Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current. <4> Default setting value is dependent on parameter E5-01, Motor Code Selection. <5> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <6> Default setting value is dependent on parameter o2-04, Drive Model Selection. <7> Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency Voltage 2, are set to 0.0. <8> When setting motor parameters, the motor rated current must be set to a value greater than the motor no-load current (E2-01 > E2-03). <9> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. <10> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. <11> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller. <12> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f Control. <13> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0. <14> Parameter can be changed during Run. <15> If using a Yaskawa SMRA Series SPM Motor, the default setting is 1800 r/min. <16> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0. <17> Default setting is determined by drive software version. PRG: 1018 and later: 0.0 to 6500.0 mV/(r/min) PRG: 1017 and earlier: 0.0 to 2000.0 mV/(r/min) <18> Available in drive software versions PRG: 1022 and later.

u F: Options

F parameters are used to program the drive for PG feedback and to function with option cards.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

F1: V/f Control with Simple PG Feedback - PG Setup Parameters Use F1 parameters to set up the drive for V/f Control with Simple PG Feedback. These parameters are enabled only when H6-01 = 03

B.2 Parameter Table

B

List Parameter

F1-02 | Operation Selection at PG Open Circuit (PGo)

F1-03 | Operation Selection at Overspeed (oS)

F1-04 | Operation Selection at Deviation

F1-08 | Overspeed Detection Level

F1-09 | Overspeed Detection Delay Time

Parameter catalogue PDF371 section1 — PDF page 371

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 F1-02 Operation Selection at PG Open Circuit (PGo) Sets stopping method when a PG open circuit fault (PGo) occurs. Refer to parameter F1-14. 0: Ramp to Stop - Decelerate to stop using the active deceleration time. 1: Coast to Stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm only - Drive continues operation. 0 to 3 1 A − − 381 181
2 F1-03 Operation Selection at Overspeed (oS) Sets the stopping method when an overspeed (oS) fault occurs. Refer to F1-08 and F1-09. 0: Ramp to stop - Decelerate to stop using the active deceleration time. 1: Coast to stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm Only - Drive continues operation. 0 to 3 1 A − − 382 181
3 F1-04 Operation Selection at Deviation Sets the stopping method when a speed deviation (dEv) fault occurs. Refer to F1-10 and F1-11. 0: Ramp to stop - Decelerate to stop using the active deceleration time. 1: Coast to stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm only - Drive continues operation. 0 to 3 3 A − − 383 181
4 F1-08 Overspeed Detection Level Sets the speed feedback level which has to be exceeded for the time set in F1-09 before an oS fault will occur. Set as a percentage of the maximum output frequency (E1-04). 0 to 120 115% A − − 387 181
5 F1-09 Overspeed Detection Delay Time Sets the time in seconds for which the speed feedback has to exceed the overspeed detection level F1-08 before an oS fault will occur. 0.0 to 2.0 1.0 A − − 388 181

Manual — PG and communication options — page 372

Source reference: SIEP C71060618F, December 2016, physical PDF page 372. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

F6: Serial Communications Option Card Settings Use F6 parameters to program the drive for serial communication.

B.2 Parameter Table

F1-10 | Excessive Speed Deviation Detection Level

F1-11 | Excessive Speed Deviation Detection Delay Time

F1-14 | PG Open-Circuit Detection Time

F6-01 | Communications Error operation Selection

F6-02 | External fault from comm. option selection

F6-03 | External fault from comm. option operation selection

F6-04 | Bus Error Detection Time

F6-07 <6> | NetRef/ComRef Function Selection

F6-08 <6> | Reset Communication Parameters

F6-10 | CC-Link Node Address

F6-11 | CC-Link communications speed

F6-14 | BUS Error Auto Reset

F6-20 <7> | MECHATROLINK Address Station

F6-21 <7> | MECHATROLINK Frame Size

F6-22 <7> | MECHATROLINK Speed Link

F6-23 <7> | MECHATROLINK Monitor Selection (E)

F6-24 <7> | MECHATROLINK Monitor Selection (F)

Parameter catalogue PDF372 section1 — PDF page 372

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 F1-10 Excessive Speed Deviation Detection Level Sets the allowable deviation between motor speed and frequency reference before a speed deviation fault (dEv) is triggered. Set as a percentage of the maximum output frequency (E1-04). 0 to 50 10% A − − 389 181
2 F1-11 Excessive Speed Deviation Detection Delay Time Sets the time in seconds for which a deviation between motor speed and frequency reference has to exceed the speed deviation detection level F1-10 before a dEv fault will occur. 0.0 to 10.0 0.5 s A − − 38A 181
3 F1-14 PG Open-Circuit Detection Time Sets the time for which no PG pulses must be detected before a PG Open (PGo) fault is triggered. 0.0 to 10.0 2.0 s A − − 38D 182
4 F6-01 Communications Error operation Selection Selects the operation after a communications error occurred. 0: Ramp to stop using current accel/decel time 1: Coast to stop 2: Fast-stop using C1-09 3: Alarm only 4: Alarm and Run at d1-04 <9> <10> 5: Alarm and Ramp to stop <9> 0 to 5 1 A A A 3A2 182
5 F6-02 External fault from comm. option selection Sets when an external fault from a comm option is detected. 0: Always detected 1: Detection during Run only 0, 1 0 A A A 3A3 182
6 F6-03 External fault from comm. option operation selection Selects the operation after an external fault set by a communications option (EF0). 0: Ramp to stop using current accel/decel time 1: Coast to stop 2: Fast-stop using C1-09 3: Alarm only 0 to 3 1 A A A 3A4 182
7 F6-04 Bus Error Detection Time Set the delay time for error detection if a bus error occurs. 0.0 to 5.0 2.0 s A A A 3A5 –
8 F6-07 <6> NetRef/ComRef Function Selection 0: Multi-step reference disabled (same as F7) 1: Multi-step reference enabled (same as V7) 0, 1 0 A A A 3A8 182
9 F6-08 <6> Reset Communication Parameters 0: Communication-related parameters (F6-□□ and F7-□□) are not reset when the drive is initialized using A1-03. 1: Reset all communication-related parameters (F6-□□ and F7-□□) when the drive is initialized using A1-03. 0, 1 0 <1> A A A 36A 183
10 F6-10 CC-Link Node Address Sets the node address if a CC-Link option card is installed. 0 to 63 0 A A A 3E6 –
11 F6-11 CC-Link communications speed 0: 156 Kbps 1: 625 Kbps 2: 2.5 Mbps 3: 5 Mbps 4: 10 Mbps 0 to 4 0 A A A 3E7 –
12 F6-14 BUS Error Auto Reset Selects if a BUS fault can be automatically reset. 0: Disabled 1: Enabled 0, 1 0 A A A 3BB –
13 F6-20 <7> MECHATROLINK Station Address Sets the station address when the MECHATROLINK option has been installed. <8> 21 A A A 36B –
14 F6-21 <7> MECHATROLINK Frame Size MECHATROLINK-II 0: 32 byte 1: 17 byte MECHATROLINK-III 0: 64 byte 1: 32 byte 0, 1 0 A A A 36C –
15 F6-22 <7> MECHATROLINK Link Speed 0: 10 Mbps 1: 4 Mbps Note: Available only for MECHATROLINK-II. 0, 1 0 A A A 36D –
16 F6-23 <7> MECHATROLINK Monitor Selection (E) Sets the MECHATROLINK monitor (E). 0 to FFFFH 0 A A A 36E –
17 F6-24 <7> MECHATROLINK Monitor Selection (F) Sets the MECHATROLINK monitor (F). 0 to FFFFH 0 A A A 36F –

Manual — Communication option parameters — page 373

Source reference: SIEP C71060618F, December 2016, physical PDF page 373. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

B.2 Parameter Table

B

List Parameter

F6-25 <7> | Operation Selection at MECHATROLINK Watchdog Timer Error (E5)

F6-26 <7> | MECHATROLINK bUS Errors Detected

F6-30 | PROFIBUS node address

F6-31 | PROFIBUS Clear Mode Selection

F6-32 | PROFIBUS Data Format Selections

F6-35 | CANopen Node ID selection

F6-36 | CANopen Communications speed

F6-40 | CompoNet Node ID

F6-41 | CompoNet Speed

F6-50 <3> | DeviceNet MAC Address

F6-51 <3> | Device Net Communications Speed

F6-52 <3> | DeviceNet PCA setting

F6-53 <3> | DeviceNet PPA setting

F6-54 <3> | DeviceNet Idle Mode Fault Detection

F6-55 | DeviceNet Baud Rate Monitor

F6-56 <3> | DeviceNet Speed Scaling Factor

F6-57 <3> | DeviceNet Current Scaling Factor

F6-58 <3> | DeviceNet Torque Scaling Factor

F6-59 <3> | DeviceNet Power Scaling Factor

Parameter catalogue PDF373 section1 — PDF page 373

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 F6-25 <7> Operation Selection at MECHATROLINK Watchdog Timer Error (E5) 0: Ramp to stop. Decelerate using the deceleration time in C1-02. 1: Coast to stop 2: Fast stop. Decelerate using the deceleration time in C1-09. 3: Alarm only 0 to 3 1 A A A 3C9 –
2 F6-26 <7> MECHATROLINK bUS Errors Detected Sets the number of option communication errors (bUS). 2 to 10 2 A A A 3CA –
3 F6-30 PROFIBUS node address Sets the node address for a PROFIBUS option. 0 to 125 0 A A A 3CB –
4 F6-31 PROFIBUS Clear Mode Selection Selects the operation when a "Clear Mode" command is received. 0: Resets drive operation. 1: Maintains the previous operation state. 0, 1 0 A A A 3CC –
5 F6-32 PROFIBUS Data Format Selections 0: PPO Type 1: Conventional 0, 1 0 A A A 3CD –
6 F6-35 CANopen Node ID selection Sets the Node ID for a CANopen option <2> 99 A A A 3D0 –
7 F6-36 CANopen Communications speed 0: Auto-adjust 1: 10 kbps 2: 20 kbps 3: 50 kbps 4: 125 kbps 5: 250 kbps 6: 500 kbps 7: 800 kbps 8: 1 Mbps 0 to 8 6 A A A 3D1 –
8 F6-40 CompoNet Node ID Sets the Node ID for a CompoNet option. 0 to 63 0 A A A 3D5 –
9 F6-41 CompoNet Speed 0: 93.75 kbps 1: Reserved 2: 1.5 Mbps 3: 3 Mbps 4: 4 Mbps 5-255: Reserved 0 to 255 0 A A A 3D6 –
10 F6-50 <3> DeviceNet MAC Address Selects the drives MAC address for DeviceNet. 0 to 64 64 A A A 3C1 –
11 F6-51 <3> Device Net Communications Speed 0: 125 kbps 1: 250 kbps 2: 500 kbps 3: Adjustable from Network 4: Detect automatically 0 to 4 4 A A A 3C2 –
12 F6-52 <3> DeviceNet PCA setting I/O Polled Consuming Assembly Data Instance 0 to 255 21 A A A 3C3 –
13 F6-53 <3> DeviceNet PPA setting I/O Polled Producing Assembly Data Instance 0 to 255 71 A A A 3C4 –
14 F6-54 <3> DeviceNet Idle Mode Fault Detection Selects if an EF0 fault is detected when no data are received from the master. <4> 0: Detection enabled 1: No detection 0, 1 0 A A A 3C5 –
15 F6-55 DeviceNet Baud Rate Monitor Verifies the baud rate running on the network. 0: 125 kbps 1: 250 kbps 2: 500 kbps 0 to 2 0 A A A 3C6 –
16 F6-56 <3> DeviceNet Speed Scaling Factor Sets the scaling factor for the speed monitor in DeviceNet Class ID 2AH Object. -15 to 15 0 A A A 3D7 –
17 F6-57 <3> DeviceNet Current Scaling Factor Sets the scaling factor for the output current monitor in DeviceNet Class ID 2AH Object. -15 to 15 0 A A A 3D8 –
18 F6-58 <3> DeviceNet Torque Scaling Factor Sets the scaling factor for the torque monitor in DeviceNet Class ID 2AH Object. -15 to 15 0 A A A 3D9 –
19 F6-59 <3> DeviceNet Power Scaling Factor Sets the scaling factor for the power monitor in DeviceNet Class ID 2AH Object. -15 to 15 0 A A A 3DA –

Manual — Software-dependent assembly mappings — page 374

Source reference: SIEP C71060618F, December 2016, physical PDF page 374. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

F7: EtherNet/IP and Modbus TCP/IP Option Parameters Use F7 parameters to program the drive for EtherNet communication.

B.2 Parameter Table

F6-60 <3> | DeviceNet Voltage Scaling Factor

F6-61 <3> | DeviceNet Time Scaling Factor

F6-62 <3> | DeviceNet Heartbeat Interval

F6-63 | Dynamic Output Assembly 109 Parameter 1 <5>

F6-63 | MAC ID Memory <6>

F6-64 | Dynamic Output Assembly 109 Parameter 2 <5>

F6-64 | Dynamic Output Assembly 109 Parameter 1 <6>

F6-65 | Dynamic Output Assembly 109 Parameter 3 <5>

F6-65 | Dynamic Output Assembly 109 Parameter 2 <6>

F6-66 | Dynamic Output Assembly 109 Parameter 4 <5>

F6-66 | Dynamic Output Assembly 109 Parameter 3 <6>

F6-67 | Dynamic Output Assembly 159 Parameter 1 <5>

F6-67 | Dynamic Output Assembly 109 Parameter 4 <6>

F6-68 | Dynamic Output Assembly 159 Parameter 2 <5>

F6-68 | Dynamic Output Assembly 159 Parameter 1 <6>

F6-69 | Dynamic Output Assembly 159 Parameter 3 <5>

F6-69 | Dynamic Output Assembly 159 Parameter 2 <6>

F6-70 | Dynamic Output Assembly 159 Parameter 4 <5>

F6-70 | Dynamic Output Assembly 159 Parameter 3 <6>

F6-71 | Dynamic Output Assembly 159 Parameter 4 <6>

Parameter catalogue PDF374 section1 — PDF page 374

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 F6-60 <3> DeviceNet Voltage Scaling Factor Sets the scaling factor for the voltage monitor in DeviceNet Class ID 2AH Object. -15 to 15 0 A A A 3DB –
2 F6-61 <3> DeviceNet Time Scaling Factor Sets the scaling factor for the time monitor in DeviceNet Class ID 2AH Object. -15 to 15 0 A A A 3DC –
3 F6-62 <3> DeviceNet Heartbeat Interval Sets the heartbeat interval for DeviceNet communications. 0 to 10 0 A A A 3DD –
4 F6-63 Dynamic Output Assembly 109 Parameter 1 <5> Dynamic Output Assembly 109 Parameter 1 0x0 to 0xFFFF 0 A A A 3DE –
5 F6-63 MAC ID Memory <6> Sets the MAC ID memory (Read only) 0 to 63 – A A A 3DE –
6 F6-64 Dynamic Output Assembly 109 Parameter 2 <5> Dynamic Output Assembly 109 Parameter 2 0x0 to 0xFFFF 0 A A A 3DF –
7 F6-64 Dynamic Output Assembly 109 Parameter 1 <6> Dynamic Output Assembly 109 Parameter 1 0x0 to 0xFFFF 0 A A A 3DF –
8 F6-65 Dynamic Output Assembly 109 Parameter 3 <5> Dynamic Output Assembly 109 Parameter 3 0x0 to 0xFFFF 0 A A A 3E0 –
9 F6-65 Dynamic Output Assembly 109 Parameter 2 <6> Dynamic Output Assembly 109 Parameter 2 0x0 to 0xFFFF 0 A A A 3E0 –
10 F6-66 Dynamic Output Assembly 109 Parameter 4 <5> Dynamic Output Assembly 109 Parameter 4 0x0 to 0xFFFF 0 A A A 3E1 –
11 F6-66 Dynamic Output Assembly 109 Parameter 3 <6> Dynamic Output Assembly 109 Parameter 3 0x0 to 0xFFFF 0 A A A 3E1 –
12 F6-67 Dynamic Output Assembly 159 Parameter 1 <5> Dynamic Output Assembly 159 Parameter 1 0x0 to 0xFFFF 0 A A A 3E2 –
13 F6-67 Dynamic Output Assembly 109 Parameter 4 <6> Dynamic Output Assembly 109 Parameter 4 0x0 to 0xFFFF 0 A A A 3E2 –
14 F6-68 Dynamic Output Assembly 159 Parameter 2 <5> Dynamic Output Assembly 159 Parameter 2 0x0 to 0xFFFF 0 A A A 3E3 –
15 F6-68 Dynamic Output Assembly 159 Parameter 1 <6> Dynamic Output Assembly 159 Parameter 1 0x0 to 0xFFFF 0 A A A 3E3 –
16 F6-69 Dynamic Output Assembly 159 Parameter 3 <5> Dynamic Output Assembly 159 Parameter 3 0x0 to 0xFFFF 0 A A A 3E4 –
17 F6-69 Dynamic Output Assembly 159 Parameter 2 <6> Dynamic Output Assembly 159 Parameter 2 0x0 to 0xFFFF 0 A A A 3E4 –
18 F6-70 Dynamic Output Assembly 159 Parameter 4 <5> Dynamic Output Assembly 159 Parameter 4 0x0 to 0xFFFF 0 A A A 3C7 –
19 F6-70 Dynamic Output Assembly 159 Parameter 3 <6> Dynamic Output Assembly 159 Parameter 3 0x0 to 0xFFFF 0 A A A 3C7 –
20 F6-71 Dynamic Output Assembly 159 Parameter 4 <6> Dynamic Output Assembly 159 Parameter 4 0x0 to 0xFFFF 0 A A A 3C8 –

Manual — Ethernet options and communication footnotes — page 375

Source reference: SIEP C71060618F, December 2016, physical PDF page 375. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode Addr. V/ O P Hex Pg. L f M V

O L V

P M

<1> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <2> Setting range is determined by the drive software version. PRG: 1016 and later: 0 to 126 PRG: 1015 and earlier: 0 to 127 <3> Parameter available in drive software versions PRG: 1011 and later. <4> The following parameter settings apply to drive software versions 1015 and earlier: 0: Disabled 1: Enabled <5> Parameter available in drive software versions PRG: 1012 and later. <6> Parameter available in drive software versions PRG: 1014 and later. <7> Parameter available in drive software versions PRG: 1023 and later. <8> Setting range is determined by the option. MECHATROLINK-II: 20H to 3FH MECHATROLINK-III: 03H to EFH <9> Available in drive software version PRG: 1024 and later. <10> Take proper safety measures, such as installing an emergency stop switch, as the drive will continue operation when detecting an bUS error.

B.2 Parameter Table

B

List Parameter

F7-01 to F7-42 | EtherNet/IP and Modbus TCP/IP Option Parameters

Parameter catalogue PDF375 section1 — PDF page 375

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 F7-01 to F7-42 EtherNet/IP and Modbus TCP/IP Option Parameters F7 parameters are reserved for use with SI-EN3/V and SI- EM3/V options. Refer to the respective Option Installation Manuals for details. – – – – – – –

Manual — Digital input parameters and selections — page 376

Source reference: SIEP C71060618F, December 2016, physical PDF page 376. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ H Parameters: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

H1: Multi-Function Digital Input H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".

<1> The availability of certain functions depends on the control method used. <2> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.

H1 Multi-Function Digital Input Selections

H1-□□ Setting Function Description

Control Mode

Control modes: V/f, OLV, PM; Pg.

B.2 Parameter Table

H1-01 | Multi-Function Digital Input Terminal S1 Function Selection

H1-02 | Multi-Function Digital Input Terminal S2 Function Selection

H1-03 | Multi-Function Digital Input Terminal S3 Function Selection

H1-04 | Multi-Function Digital Input Terminal S4 Function Selection

H1-05 | Multi-Function Digital Input Terminal S5 Function Selection

H1-06 | Multi-Function Digital Input Terminal S6 Function Selection

H1-07 | Multi-Function Digital Input Terminal S7 Function Selection

0 | 3-Wire Sequence

1 | LOCAL/REMOTE Selection

2 | External Reference 1/2

3 | Multi-Step Speed Reference 1

4 | Multi-Step Speed Reference 2

5 | Multi-Step Speed Reference 3

6 | Jog Reference Selection

7 | Accel/Decel Time 1

8 | Baseblock Command (N.O.)

9 | Baseblock Command (N.C.)

A | Accel/Decel Ramp Hold

B | Drive Overheat Alarm (oH2)

C | Terminal A1/A2 Enable

Parameter catalogue PDF376 section1 — PDF page 376

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 H1-01 Multi-Function Digital Input Terminal S1 Function Selection Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. 1 to 9F <1> 40 A A A 438 184
2 H1-02 Multi-Function Digital Input Terminal S2 Function Selection Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. 1 to 9F <1> 41 A A A 439 184
3 H1-03 Multi-Function Digital Input Terminal S3 Function Selection Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. 1 to 9F <1> 24 A A A 400 184
4 H1-04 Multi-Function Digital Input Terminal S4 Function Selection Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. 1 to 9F <1> 14 A A A 401 184
5 H1-05 Multi-Function Digital Input Terminal S5 Function Selection Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. 1 to 9F <1> 3 (0) <2> A A A 402 184
6 H1-06 Multi-Function Digital Input Terminal S6 Function Selection Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. 1 to 9F <1> 4 (3) <2> A A A 403 184
7 H1-07 Multi-Function Digital Input Terminal S7 Function Selection Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. 1 to 9F <1> 6 (4) <2> A A A 404 184

Multi-function selections PDF376 — PDF page 376

Source row Function setting Function Description Control mode V/f Control mode OLV Control mode PM Reference page
1 0 3-Wire Sequence Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence) O O O 185
2 1 LOCAL/REMOTE Selection Open: REMOTE, Reference 1 or 2 (b1-01/02 or b1-15/16) Closed: LOCAL, LED operator is run and reference source O O O 185
3 2 External Reference 1/2 Open: Run and frequency reference source 1 (b1-01/02) Closed: Run and frequency reference source 2 (b1-15/16) O O O 186
4 3 Multi-Step Speed Reference 1 Used to select Multi-Step Speeds set in d1-01 to d1-16 O O O 186
5 4 Multi-Step Speed Reference 2 Used to select Multi-Step Speeds set in d1-01 to d1-16 O O O 186
6 5 Multi-Step Speed Reference 3 Used to select Multi-Step Speeds set in d1-01 to d1-16 O O O 186
7 6 Jog Reference Selection Open: Selected speed reference Closed: Jog Frequency reference (d1-17). Jog has priority over all other reference sources. O O O 186
8 7 Accel/Decel Time 1 Used to switch between Accel/Decel. Time 1/2 O O O 186
9 8 Baseblock Command (N.O.) Open: Normal operation Closed: No drive output O O O 186
10 9 Baseblock Command (N.C.) Open: No drive output Closed: Normal operation O O O 186
11 A Accel/Decel Ramp Hold Closed: The drive pauses during acceleration or deceleration and maintains the output frequency. O O O 186
12 B Drive Overheat Alarm (oH2) Closed: Closes when an oH2 alarm occurs. O O O 187
13 C Terminal A1/A2 Enable Terminal status differs depending on drive software version. PRG: 1016 and later: Open: Analog input selected by H3-14 is disabled. Closed: Analog input selected by H3-14 is enabled. PRG: 1015 and earlier: Open: Analog inputs selected for terminals A1 and A2 are disabled. Closed: Analog inputs selected for terminals A1 and A2 are enabled. O O O 187

Manual — Digital input function restrictions — page 377

Source reference: SIEP C71060618F, December 2016, physical PDF page 377. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

H1 Multi-Function Digital Input Selections

H1-□□ Setting Function Description

Control Mode

Control modes: V/f, OLV, PM; Pg.

OLV

PM

B.2 Parameter Table

B

Parameter List

F | Not used

10 | Up Command

11 | Down Command

12 | Forward Jog

13 | Reverse Jog

14 | Fault Reset

15 | Fast-Stop (N.O.)

16 | Motor 2 Selection

17 | Fast-stop (N.C.)

18 | Timer Function Input

19 | PID Disable

1A | Accel/Decel Time Selection 2

1B | Program Lockout

1E | Reference Sample Hold

20 to 2F | External Fault

30 | PID Integral Reset

31 | PID Integral Hold

32 | Multi-Step Speed Reference 4

34 | PID Soft Starter

35 | PID Input Switch

40 | Forward Run Command (2-Wire sequence)

41 | Reverse Run Command (2-Wire sequence)

42 | Run Command (2-Wire sequence 2)

43 | FWD/REV Command (2-Wire sequence 2)

Multi-function selections PDF377 — PDF page 377

Source row Function setting Function Description Control mode V/f Control mode OLV Control mode PM Reference page
1 F Not used Select this setting when not using the terminal or when using the terminal in a pass-through mode. O O O 187
2 10 Up Command Open: Maintains the current frequency reference Closed: Increases or decreases the current frequency reference. Ensure that the increase and decrease commands are set in conjunction with one another. O O O 187
3 11 Down Command Open: Maintains the current frequency reference Closed: Increases or decreases the current frequency reference. Ensure that the increase and decrease commands are set in conjunction with one another. O O O 187
4 12 Forward Jog Closed: Runs forward at the Jog Frequency d1-17. O O O 188
5 13 Reverse Jog Closed: Runs reverse at the Jog Frequency d1-17. O O O 188
6 14 Fault Reset Closed: Resets faults if the cause is cleared and the Run command is removed. O O O 188
7 15 Fast-Stop (N.O.) Closed: Decelerates at the Fast-Stop time C1-09. To restart the Fast-Stop input must be released and Run must be cycled. O O O 188
8 16 Motor 2 Selection Open: Motor 1 (E1-□□, E2-□□) Closed: Motor 2 (E3-□□, E4-□□) O O O 189
9 17 Fast-stop (N.C.) Open: Decelerates according to C1-09 (Fast-stop Time) O O O 188
10 18 Timer Function Input Set the timer delay using parameters b4-01 and b4-02. Ensure this function is set in conjunction with the multi-function output timer (H2-□□ = 12). O O O 189
11 19 PID Disable Closed: PID control disabled O O O 189
12 1A Accel/Decel Time Selection 2 Switches Accel/Decel times. O O O 189
13 1B Program Lockout Open: Parameters can not be edited. (except U1-01 if reference source is set for operator) Closed: Parameters may be edited and saved. O O O 189
14 1E Reference Sample Hold Closed: Samples the analog frequency reference and operates the drive at that speed. O O O 190
15 20 to 2F External Fault 20: N.O., Always Detected, Ramp To Stop 21: N.C., Always Detected, Ramp To Stop 22: N.O., During Run, Ramp To Stop 23: N.C., During Run, Ramp To Stop 24: N.O., Always Detected, Coast To Stop 25: N.C., Always Detected, Coast To Stop 26: N.O., During Run, Coast To Stop 27: N.C., During Run, Coast To Stop 28: N.O., Always Detected, Fast-stop 29: N.C., Always Detected, Fast-stop 2A: N.O., During Run, Fast-stop 2B: N.C., During Run, Fast-stop 2C: N.O., Always Detected, Alarm Only (continue running) 2D: N.C., Always Detected, Alarm Only (continue running) 2E: N.O., During Run, Alarm Only (continue running) 2F: N.C., During Run, Alarm Only (continue running) O O O 190
16 30 PID Integral Reset Closed: Resets the PID control integral value. O O O 191
17 31 PID Integral Hold Closed: Maintains the current PID control integral value. O O O 191
18 32 Multi-Step Speed Reference 4 Used to select Multi-Step Speeds set in d1-01 to d1-16 O O O 191
19 34 PID Soft Starter Closed: Disables the PID soft starter b5-17. O O O 191
20 35 PID Input Switch Closed: Inverses the PID input signal O O O 191
21 40 Forward Run Command (2-Wire sequence) Open: Stop Closed: Forward run Note: Can not be set together with Settings 42 or 43. O O O 191
22 41 Reverse Run Command (2-Wire sequence) Open: Stop Closed: Reverse run Note: Can not be set together with Settings 42 or 43. O O O 191
23 42 Run Command (2-Wire sequence 2) Open: Stop Closed: Run Note: Can not be set together with Settings 40 or 41. O O O 191
24 43 FWD/REV Command (2-Wire sequence 2) Open: Forward Closed: Reverse Note: Can not be set together with Settings 40 or 41. O O O 191

Manual — Digital input continuations and outputs — page 378

Source reference: SIEP C71060618F, December 2016, physical PDF page 378. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

H1 Multi-Function Digital Input Selections

H1-□□ Setting Function Description

Control Mode

Control modes: V/f, OLV, PM; Pg.

OLV

PM

<1> Available in drive software versions PRG: 1016 and later.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

H2: Multi-Function Digital Outputs Use H2 parameters to assign functions to the multi-function digital outputs.

B.2 Parameter Table

44 | Offset Frequency 1 Addition

45 | Offset Frequency 2 Addition

46 | Offset Frequency 3 Addition

47 <1> | Node Setup

60 | DC Injection Braking Command

61 | External Search Command 1

62 | External Search Command 2

65 | KEB Ride-Thru 1 (N.C.)

66 | KEB Ride-Thru 1 (N.O.)

67 | Communications Test Mode

68 | High-Slip Braking

6A | Drive Enable

75 | Up 2 Command

76 | Down 2 Command

7A | KEB Ride-Thru 2 (N.C.)

7B | KEB Ride-Thru 2 (N.O.)

7C | Short-Circuit Braking (N.O.)

7D | Short-Circuit Braking (N.C.)

7E | Forward/Reverse Detection

90 to 96 | DWEZ Digital Inputs 1 to 7

9F | DriveWorksEZ enable

H2-01 | Terminal MA, MB and MC Function Selection (relay)

H2-02 | Terminal P1 Function Selection (open- collector)

H2-03 | Terminal P2 Function Selection (open- collector)

Multi-function selections PDF378 — PDF page 378

Source row Function setting Function Description Control mode V/f Control mode OLV Control mode PM Reference page
1 44 Offset Frequency 1 Addition Closed: Adds d7-01 to the frequency reference. O O O 192
2 45 Offset Frequency 2 Addition Closed: Adds d7-02 to the frequency reference. O O O 192
3 46 Offset Frequency 3 Addition Closed: Adds d7-03 to the frequency reference. O O O 192
4 47 <1> Node Setup Closed: Node setup for SI-S3/V enabled. O O O 192
5 60 DC Injection Braking Command Closed: Triggers DC Injection Braking (b2-02) O O - 192
6 61 External Search Command 1 Closed: Activates Current Detection Speed Search from the max. output frequency (E1-04) if b3-01 = 0. Activates Speed Estimation Type Speed search if b3-01 = 0. O O O 192
7 62 External Search Command 2 Closed: Activates Current Detection Speed Search from the frequency reference b3-01 = 0. Activates Speed Estimation Type Speed search if b3-01 = 0. O O O 192
8 65 KEB Ride-Thru 1 (N.C.) Open: KEB Ride-Thru 1 enabled Closed: Normal operation O O O 192
9 66 KEB Ride-Thru 1 (N.O.) Open: Normal operation Closed: KEB Ride-Thru 1 enabled O O O 192
10 67 Communications Test Mode Tests the MEMOBUS/Modbus RS-485/422 interface. O O O 192
11 68 High-Slip Braking Closed: High-Slip braking is executed. Drive stops. O - - 192
12 6A Drive Enable Open: Drive disabled. If this input is opened during run, then the drive will stop as specified by parameter b1-03. Closed: Ready for operation. O O O 192
13 75 Up 2 Command Open: Maintains the current frequency reference. Closed: Increases or decreases the frequency reference. UP 2 and Down 2 commands must be set in combination with each other. The frequency reference source must be assigned to the operator (b1-01 = “0”). O O O 193
14 76 Down 2 Command Open: Maintains the current frequency reference. Closed: Increases or decreases the frequency reference. UP 2 and Down 2 commands must be set in combination with each other. The frequency reference source must be assigned to the operator (b1-01 = “0”). O O O 193
15 7A KEB Ride-Thru 2 (N.C.) Open: KEB Ride-Thru 2 enabled Closed: Normal operation O O O 194
16 7B KEB Ride-Thru 2 (N.O.) Open: Normal operation Closed: KEB Ride-Thru 2 enabled O O O 194
17 7C Short-Circuit Braking (N.O.) Open: Normal operation Closed: Short-Circuit Braking - - O 194
18 7D Short-Circuit Braking (N.C.) Open: Short-Circuit Braking Closed: Normal operation - - O 194
19 7E Forward/Reverse Detection Direction of rotation detection (for V/f with Simple PG Feedback) O - - 194
20 90 to 96 DWEZ Digital Inputs 1 to 7 Reserved for DWEZ input functions O O O 194
21 9F DriveWorksEZ enable Open: DWEZ enabled Closed: DWEZ disabled O O O 194

Parameter catalogue PDF378 section2 — PDF page 378

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 H2-01 Terminal MA, MB and MC Function Selection (relay) Refer to H2 Multi-Function Digital Output Settings on page 379 for a description of setting values. 0 to 192 <1> E A A A 40B 195
2 H2-02 Terminal P1 Function Selection (open- collector) Refer to H2 Multi-Function Digital Output Settings on page 379 for a description of setting values. 0 to 192 <1> 0 A A A 40C 195
3 H2-03 Terminal P2 Function Selection (open- collector) Refer to H2 Multi-Function Digital Output Settings on page 379 for a description of setting values. 0 to 192 <1> 2 A A A 40D 195

Manual — Digital output settings and functions — page 379

Source reference: SIEP C71060618F, December 2016, physical PDF page 379. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

<1> The availability of certain functions depends on the control method used.

H2 Multi-Function Digital Output Settings

H2-□□ Setting Function Description

Control Mode

Control modes: V/f, OLV, PM; Pg.

B.2 Parameter Table

B

Parameter List

H2-06 | Watt Hour Output Unit Selection

0 | During Run

1 | Zero Speed

2 | Speed Agree 1

3 | User Set Speed Agree 1

4 | Frequency Detection 1

5 | Frequency Detection 2

6 | Drive Ready

7 | DC Bus Undervoltage

8 | During Baseblock (N.O.)

9 | Frequency reference selection

A | Run command selection

B | Torque Detection 1 (N.O.)

C | Frequency Reference Loss

D | Braking Resistor Fault

E | Fault

F | Not used/Through Mode

10 | Minor Fault

11 | Reset Command Active

12 | Timer Output

13 | Speed Agree 2

14 | User Set Speed Agree 2

15 | Frequency Detection 3

16 | Frequency Detection 4

Parameter catalogue PDF379 section1 — PDF page 379

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 H2-06 Watt Hour Output Unit Selection Sets the output units for the watt hours when Watt Hour Pulse Output is selected as the digital output (H2-01, H2-02, or H2-03 = 39). Outputs a 200 ms pulse signal when the watt- hour counter increases by the units selected. 0: 0.1 kWh units 1: 1 kWh units 2: 10 kWh units 3: 100 kWh units 4: 1000 kWh units 0 to 4 0 A A A 437 204

Multi-function selections PDF379 — PDF page 379

Source row Function setting Function Description Control mode V/f Control mode OLV Control mode PM Reference page
1 0 During Run Closed: A Run command is active or voltage is output. O O O 195
2 1 Zero Speed Closed: Output frequency is 0. O O O 196
3 2 Speed Agree 1 Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02). O O O 196
4 3 User Set Speed Agree 1 Closed: Output frequency and speed reference equal the value in L4-01 (plus or minus the hysteresis of L4-02). O O O 196
5 4 Frequency Detection 1 Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined by L4-02. O O O 197
6 5 Frequency Detection 2 Closed: Output frequency is greater than or equal to the value in L4-01, with hysteresis determined by L4-02. O O O 197
7 6 Drive Ready Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive mode. O O O 198
8 7 DC Bus Undervoltage Closed: DC bus voltage is below the Uv trip level set in L2-05. O O O 198
9 8 During Baseblock (N.O.) Closed: There is no output voltage O O O 198
10 9 Frequency reference selection Open: External Reference 1 or 2 supplies the frequency reference Closed: Digital operator supplies the frequency reference. O O O 198
11 A Run command selection Open: External Reference 1 or 2 supplies the Run command Closed: Digital operator supplies the Run command. O O O 198
12 B Torque Detection 1 (N.O.) Closed: Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time set in parameter L6-03. O O O 198
13 C Frequency Reference Loss Closed: Loss of the analog frequency reference detected. Enabled when L4-05 = 1. O O O 199
14 D Braking Resistor Fault Closed: Braking resistor or transistor is overheated or faulted out. This selection requires that braking resistor protection parameter be set for ERF (L8-01 = “1”). O O O 199
15 E Fault Closed: Fault occurred (other than CPF00 and CPF01). O O O 199
16 F Not used/Through Mode Set this value when the terminal is not used, or when using the terminal in the pass- through mode. O O O 199
17 10 Minor Fault Closed: An alarm is triggered. O O O 199
18 11 Reset Command Active Closed: The drive has received a reset command from the multi-function input terminals or from serial network, or the digital operator RESET key has been pressed. O O O 199
19 12 Timer Output Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital input (H1-□□ = 18 “timer function”). O O O 199
20 13 Speed Agree 2 Closed: When drive output frequency equals the frequency reference +/- L4-04. O O O 199
21 14 User Set Speed Agree 2 Closed: When the drive output frequency is equal to the value in L4-03 (plus or minus L4-04). O O O 200
22 15 Frequency Detection 3 Closed: When the drive output frequency is less than or equal to the value in L4-03 with the hysteresis determined by L4-04. O O O 200
23 16 Frequency Detection 4 Closed: When the output frequency is greater than or equal to the value in L4-03 with the hysteresis determined by L4-04. O O O 201

Manual — Output function continuations — page 380

Source reference: SIEP C71060618F, December 2016, physical PDF page 380. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

H2 Multi-Function Digital Output Settings

H2-□□ Setting Function Description

Control Mode

Control modes: V/f, OLV, PM; Pg.

OLV

PM

<1> Available in drive software versions PRG: 1016 and later.

B.2 Parameter Table

17 | Torque Detection 1 (N.C.)

18 | Torque Detection 2 (N.O.)

19 | Torque Detection 2 (N.C.)

1A | Reverse Direction

1B | During Baseblock (N.C.)

1C | Motor 2 Selection

1E | Restart Enabled

1F | Overload Alarm oL1

20 | oH Pre alarm

22 | Mechanical Weakening (N.O.)

2F <1> | Maintenance Period

30 | During Torque Limit

37 | During Frequency Output

38 | Drive Enable

39 | Watt Hour Pulse Output

3C | LOCAL/REMOTE Status

3D | Speed Search

3E | PID Feedback Loss Low

3F | PID Feedback Loss High

4A | KEB Operation

4B | Short-Circuit Brake

4C | During Fast-stop

4D | oH Pre-alarm Time Limit

4E <1> | Braking Transistor Fault (rr)

4F <1> | Braking Resistor Overheat (oH)

90 to 92 | DWEZ Digital Outputs 1 to 3

100 to 192 | H2 Parameter Functions Reversed Output Switching of 0 to 92

Multi-function selections PDF380 — PDF page 380

Source row Function setting Function Description Control mode V/f Control mode OLV Control mode PM Reference page
1 17 Torque Detection 1 (N.C.) Open: When the output current/torque exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03. O O O 198
2 18 Torque Detection 2 (N.O.) Closed: When the output current/torque exceeds the value set in parameter L6-05 for more time than is set in parameter L6-06. O O O 198
3 19 Torque Detection 2 (N.C.) Open: Output current/torque exceeds the value set in parameter L6-05 for more time than is set in parameter L6-06. O O O 198
4 1A Reverse Direction Closed: Drive is running in the reverse direction. O O O 201
5 1B During Baseblock (N.C.) Open: Drive is in Baseblock condition. Output is disabled. O O O 202
6 1C Motor 2 Selection Closed: Motor 2 is selected by a digital input (H1-□□ = 16) O O − 202
7 1E Restart Enabled Closed: An automatic restart is performed O O O 202
8 1F Overload Alarm oL1 Closed: oL1 is at 90% of its trip point or greater. O O O 202
9 20 oH Pre alarm Closed: Heatsink temperature exceeds the parameter L8-02 value. O O O 202
10 22 Mechanical Weakening (N.O.) Closed: Mechanical Weakening detected. O O O 202
11 2F <1> Maintenance Period Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require maintenance. O O O 202
12 30 During Torque Limit Closed: When the torque limit has been reached. − O − 202
13 37 During Frequency Output Open: No frequency output from drive if stopped, with baseblock, with DC injection braking during initial excitation, or with short-circuit braking. Closed: Drive is outputting a frequency O O O 202
14 38 Drive Enable Closed: Multi-function input closes (H1-□□ = 6A) O O O 203
15 39 Watt Hour Pulse Output Output units are determined by H2-06, outputs 200 ms pulse for each incremented kWh count. O O O 203
16 3C LOCAL/REMOTE Status Closed: LOCAL Open: REMOTE O O O 203
17 3D Speed Search Closed: Speed search is being executed. O O O 203
18 3E PID Feedback Loss Low Closed: PID Feedback Loss Low. PID feedback value is below the level set to b5-13 for longer than the time set in b5-14. O O O 203
19 3F PID Feedback Loss High Closed: PID Feedback Loss High. PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37. O O O 203
20 4A KEB Operation Closed: KEB is being performed. O O O 203
21 4B Short-Circuit Brake Closed: Short-Circuit Braking is active. − − O 203
22 4C During Fast-stop Closed: Fast-stop command is entered O O O 203
23 4D oH Pre-alarm Time Limit Closed: oH Pre-alarm time limit is passed. O O O 203
24 4E <1> Braking Transistor Fault (rr) Closed: The built-in dynamic braking transistor failed. O O O 203
25 4F <1> Braking Resistor Overheat (oH) Closed: The dynamic braking resistor has overheated. O O O 203
26 90 to 92 DWEZ Digital Outputs 1 to 3 Reserved for DWEZ digital output functions. O O O 204
27 100 to 192 H2 Parameter Functions Reversed Output Switching of 0 to 92 Reverse the output switching of the multi-function output functions. Set the last two digits of 1□□ to reverse the output signal of that specific function. Examples: Setting “108” reverses the output of “During baseblock,” which is setting value 08. Setting “14A” reverses the output of “During KEB operation”, which is setting “4A”. O O O 204

Manual — Analog input parameters and selections — page 381

Source reference: SIEP C71060618F, December 2016, physical PDF page 381. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

H3: Analog Inputs Use H3 parameters to set the multi-function analog input terminals.

Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.

<1> The availability of certain parameters depends on the control method used. <2> Parameter can be changed during Run. <3> Parameter available in drive software versions PRG: 1016 and later.

H3 Multi-Function Analog Input Settings

H3-□□ Setting Function Maximum Input Level Possible

Control Mode

Control modes: V/f, OLV, PM; Pg.

B.2 Parameter Table

B

Parameter List

H3-01 | Terminal A1 Signal Level Selection

H3-02 | Terminal A1 Function Selection

H3-03 <2> | Terminal A1 Gain Setting

H3-04 <2> | Terminal A1 Bias Setting

H3-09 | Terminal A2 Signal Level Selection

H3-10 | Terminal A2 Function Selection

H3-11 <2> | Terminal A2 Gain Setting

H3-12 <2> | Terminal A2 Bias Setting

H3-13 | Analog Input Filter Time Constant

H3-14 <3> | Analog Input Terminal Enable Selection

H3-16 <3> | Terminal A1 Offset

H3-17 <3> | Terminal A2 offset

0 | Frequency Bias

1 | Frequency Gain

2 | Auxiliary Frequency Reference (used as a Multi-Step Speed 2)

4 | Output Voltage Bias

7 | Overtorque/Undertorque Detection Level

B | PID Feedback

Parameter catalogue PDF381 section1 — PDF page 381

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 H3-01 Terminal A1 Signal Level Selection Sets the input level for terminal A1. 0: 0 to +10 V (lower limit) 1: 0 to +10 V (no lower limit) 0, 1 0 A A A 410 204
2 H3-02 Terminal A1 Function Selection Sets the function of terminal A1. When terminal A1 is not used or is used as a through terminal, this parameter must be set to “F”. 0 to 31 <1> 0 A A A 434 205
3 H3-03 <2> Terminal A1 Gain Setting Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1. -999.9 to 999.9 100.0 % A A A 411 205
4 H3-04 <2> Terminal A1 Bias Setting Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1. -999.9 to 999.9 0.0% A A A 412 205
5 H3-09 Terminal A2 Signal Level Selection Sets the input signal level for terminal A2. 0: 0 to +10 V (with lower limit) 1: 0 to +10 V (no lower limit) 2: 4 to 20 mA 3: 0 to 20 mA 0 to 3 2 A A A 417 207
6 H3-10 Terminal A2 Function Selection Sets the function of terminal A2. When terminal A2 is not used or is used as a through terminal, this parameter must be set to “F”. 0 to 31 <1> 0 A A A 418 207
7 H3-11 <2> Terminal A2 Gain Setting Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input at terminal A2. -999.9 to 999.9 100.0 % A A A 419 207
8 H3-12 <2> Terminal A2 Bias Setting Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is input at terminal A2. -999.9 to 999.9 0.0% A A A 41A 207
9 H3-13 Analog Input Filter Time Constant Sets the primary delay filter time constant for terminals A1 and A2. Used for noise filtering. 0.00 to 2.00 0.03 s A A A 41B 207
10 H3-14 <3> Analog Input Terminal Enable Selection Determines which analog input terminal will be enabled when a digital input programmed for “Analog input enable” (H1- oo = C) is activated. 1: Terminal A1 only 2: Terminal A2 only 7: All terminals enabled 1, 2, 7 7 A A A 41C 209
11 H3-16 <3> Terminal A1 Offset Enter a 0 V signal to terminal A1. Next adjust the offset in H3-16 until the monitor U1-13 for the terminal A1 input voltage reads 0.0%. The process is the same for terminal A2. -500 to 500 0 A A A 440 209
12 H3-17 <3> Terminal A2 offset Enter a 0 V signal, and adjust the offset for terminal A2 in H3-17 until the monitor U1-14 for terminal A2 input voltage reads 0.0%. -500 to 500 0 A A A 441 209

Multi-function selections PDF381 — PDF page 381

Source row Function setting Function Maximum input level possible Control mode V/f Control mode OLV Control mode PM Reference page
1 0 Frequency Bias Max output frequency (E1-04). Same value can be set using H3-02 and H3-10. O O O 208
2 1 Frequency Gain 10 V = 100% O O O 208
3 2 Auxiliary Frequency Reference (used as a Multi-Step Speed 2) Maximum output frequency (E1-04) O O O 208
4 4 Output Voltage Bias Motor rated voltage (E1-05). O – − 208
5 7 Overtorque/Undertorque Detection Level Open Loop Vector: Motor rated torque V/f Control: Drive rated current O O O 208
6 B PID Feedback 10 V = 100% O O O 208

Manual — Analog output and communication parameters — page 382

Source reference: SIEP C71060618F, December 2016, physical PDF page 382. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

H3 Multi-Function Analog Input Settings

H3-□□ Setting Function Maximum Input Level Possible

Control Mode

Control modes: V/f, OLV, PM; Pg.

OLV

PM

<1> Parameter available in drive software versions PRG: 1016 and later.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

H4: Multi-Function Analog Outputs Use H4 parameters to configure the multi-function analog output terminals.

H5: MEMOBUS/Modbus Communications Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network. The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.

B.2 Parameter Table

C | PID Set Point

E | Motor Temperature (PTC input)

F | Not used/Through Mode

10 | FWD Torque Limit

11 | REV Torque Limit

12 | Regenerative Torque Limit

15 | FWD/REV Torque Limit

16 | Differential PID Feedback

30/31 | DWEZ Analog Input 1/2

41 <1> | Output Voltage Gain

H4-01 | Multi-Function Analog Output Terminal AM

H4-02 <2> | Multi-Function Analog Output Terminal AM Gain

H4-03 <2> | Multi-Function Analog Output Terminal AM Bias

H5-01 <3> | Drive Node Address

H5-02 | Communication Speed Selection

H5-03 | Communication Parity Selection

Multi-function selections PDF382 — PDF page 382

Source row Function setting Function Maximum input level possible Control mode V/f Control mode OLV Control mode PM Reference page
1 C PID Set Point 10 V = 100% O O O 208
2 E Motor Temperature (PTC input) 10 V = 100.00% O O O 208
3 F Not used/Through Mode – O O O 209
4 10 FWD Torque Limit Motor rated torque − O − 209
5 11 REV Torque Limit Motor rated torque − O − 209
6 12 Regenerative Torque Limit Motor rated torque − O − 209
7 15 FWD/REV Torque Limit Motor rated torque − O − 209
8 16 Differential PID Feedback 10 V = 100% O O O 209
9 30/31 DWEZ Analog Input 1/2 Depending on function. O O O 209
10 41 <1> Output Voltage Gain 10 V = 100% O − − 209

Parameter catalogue PDF382 section2 — PDF page 382

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 H4-01 Multi-Function Analog Output Terminal AM Selects the data to be output through multi-function analog output terminal AM. Set the desired monitor parameter to the digits available in U□-□□. For example, enter “103” for U1-03. When using this terminal in through mode or when not using it at all, set “000” or “031”. 000 to 999 <1> 102 A A A 41D 210
2 H4-02 <2> Multi-Function Analog Output Terminal AM Gain Sets terminal AM output gain. Maximum output voltage is 10 V. -999.9 to 999.9 100.0 % S S S 41E 210
3 H4-03 <2> Multi-Function Analog Output Terminal AM Bias Sets terminal AM output bias. -999.9 to 999.9 0.0% A A A 41F 210
4 H5-01 <3> Drive Node Address Selects drive station node number (address) for MEMOBUS/ Modbus terminals R+, R-, S+, S-. Cycle power for the setting to take effect. 0 to 20 H 1F A A A 425 439
5 H5-02 Communication Speed Selection Selects the baud rate for MEMOBUS/Modbus terminals R+, R-, S+ and S-. Cycle power for the setting to take effect. 0 : 1200 bps 1 : 2400 bps 2 : 4800 bps 3 : 9600 bps 4 : 19200 bps 5 : 38400 bps 6 : 57600 bps 7 : 76800 bps 8 : 115200 bps 0 to 8 3 A A A 426 439
6 H5-03 Communication Parity Selection Selects the communication parity for MEMOBUS/Modbus terminals R+, R-, S+ and S-. Cycle power for the setting to take effect. 0: No parity 1: Even parity 2: Odd parity 0 to 2 0 A A A 427 439

Manual — Communications and pulse I/O — page 383

Source reference: SIEP C71060618F, December 2016, physical PDF page 383. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

H6: Pulse Train Input/Output Use H6 parameters to configure Pulse Train I/O operation.

<1> The availability of certain functions depends on the control method used. <2> Parameter can be changed during Run. <3> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands. <4> Default setting is determined by drive software version. PRG: 1016 and later: 100 to 32000 Hz

B.2 Parameter Table

B

Parameter List

H5-04 | Stopping Method After Communication Error

H5-05 | Communication Fault Detection Selection

H5-06 | Drive Transmit Wait Time

H5-07 | RTS Control Selection

H5-09 | CE Detection Time

H5-10 | Unit Selection for MEMOBUS/Modbus Register 0025H

H5-11 | Communications ENTER Function Selection

H5-12 | Run Command Method Selection

H6-01 | Pulse Train Input Terminal RP Function Selection

H6-02 <2> | Pulse Train Input Scaling

H6-03 <2> | Pulse Train Input Gain

H6-04 <2> | Pulse Train Input Bias

H6-05 <2> | Pulse Train Input Filter Time

H6-06 <2> | Pulse Train Monitor Terminal MP Selection

H6-07 <2> | Pulse Train Monitor Scaling

Parameter catalogue PDF383 section1 — PDF page 383

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 H5-04 Stopping Method After Communication Error Selects the stopping method when a communication time-out fault (CE) is detected. 0: Ramp to stop 1: Coast to stop 2: Fast-stop 3: Alarm only 0 to 3 3 A A A 428 439
2 H5-05 Communication Fault Detection Selection Enables or disables the communications time-out fault (CE) detection. 0: Disabled 1: Enabled - If communication is lost for more than two seconds, a CE fault will occur. 0, 1 1 A A A 429 440
3 H5-06 Drive Transmit Wait Time Set the wait time between receiving and sending data. 5 to 65 5 ms A A A 42A 440
4 H5-07 RTS Control Selection Selects "request to send" (RTS) control: 0: Disabled - RTS is always on. 1: Enabled - RTS turns on only when sending. 0, 1 1 A A A 42B 440
5 H5-09 CE Detection Time Sets the time required to detect a communications error. Adjustment may be need when networking several drives. 0.0 to 10.0 s 2.0 s A A A 435 440
6 H5-10 Unit Selection for MEMOBUS/Modbus Register 0025H Selects the units used for MEMOBUS/Modbus register 0025H (Output Voltage Reference Monitor). 0: 0.1 V units 1: 1 V units 0, 1 0 A A A 436 440
7 H5-11 Communications ENTER Function Selection Select the function for the enter command that saves parameter data to the drive. 0: Parameter changes are activated when ENTER command is entered. 1: Parameter changes are activated immediately without ENTER command (compatible with Varispeed VS606-V7). 0, 1 1 A A A 43C 441
8 H5-12 Run Command Method Selection 0: FWD/STOP, REV/STOP Method 1: RUN/STOP, FWD/REV Method 0, 1 0 A A A 43D 441
9 H6-01 Pulse Train Input Terminal RP Function Selection Selects pulse train input function. 0: Frequency reference 1: PID feedback value 2: PID setpoint value 3: V/f Control with Simple PG Feedback (can be set only when using motor 1 in V/f Control) 0 to 3 0 A A A 42C 211
10 H6-02 <2> Pulse Train Input Scaling Sets 100% the of terminal the value RP selected input signal in H6-01. frequency that is equal to <4> 1440 Hz A A A 42D 211
11 H6-03 <2> Pulse Train Input Gain Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is input. 0.0 to 1000.0 100.0 % A A A 42E 211
12 H6-04 <2> Pulse Train Input Bias Sets the level of the value selected in H6-01 when 0 Hz is input. -100.0 to +100.0 0.0% A A A 42F 211
13 H6-05 <2> Pulse Train Input Filter Time Sets the pulse train input filter time constant. 0.00 to 2.00 0.10 s A A A 430 211
14 H6-06 <2> Pulse Train Monitor Terminal MP Selection Select the pulse train monitor output function (value of the o-□□ part of U□-□□). Refer to U: Monitors on page 399 for the list of U monitors. Example: To select U5-01, set “501. ”When not using this parameter or when using in the through mode, set “000”. <5> 000, 031, 101, 102, 501, 105, 502; 116, 801 to 809 102 A A A 431 212
15 H6-07 <2> Pulse Train Monitor Scaling Sets the terminal MP output signal frequency when the monitor value is 100%. Set H6-06 to 102 and H6-07 to 0 to make the pulse train monitor output equal to the output frequency. 0 to 32000 1440 Hz A A A 432 212

Manual — Pulse electrical notes and motor protection — page 384

Source reference: SIEP C71060618F, December 2016, physical PDF page 384. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

PRG: 1015 and earlier: 1000 to 32000 Hz <5> When set for sourcing, +5 V/1.5 kΩ or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher. When set for sinking, the external power supply should be +12 Vdc, ±5% with 16 mA or less.

Note: Cycle power to the drive to enable MEMOBUS/Modbus settings.

◆ L: Protection Function

L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention, frequency detection, fault restarts, overtorque detection, torque limits and other types of hardware protection.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

L1: Motor Protection Functions Use L1 parameters to configure motor protective functions.

L2: Momentary Power Loss Use L2 parameters to configure drive functions for momentary power loss conditions.

B.2 Parameter Table

L1-01 | Motor Overload Protection Selection

L1-02 | Motor Overload Protection Time

L1-03 | Motor Overheat Alarm Operation Selection (PTC input)

L1-04 | Motor Overheat Fault Operation Selection (PTC input)

L1-05 | Motor Temperature Input Filter Time (PTC input)

L1-13 | Continuous Electrothermal Operation Selection

L1-22 <16> <17> | Leakage Current Filter Time Constant 1

L1-23 <16> <17> | Leakage Current Filter Time Constant 2

Parameter catalogue PDF384 section1 — PDF page 384

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L1-01 Motor Overload Protection Selection Sets the motor thermal overload protection (oL1) based on the cooling capacity of the motor. 0: Disabled 1: General Purpose Motor (Standard Fan Cooled) 2: Drive Dedicated Motor with a Speed Range of 1:10 3: Vector Motor with a Speed Range of 1:100 4: PM Motor with Variable Torque 6: General Purpose Motor (50 Hz) <1> Note: When using multiple motors the drive may not be able to provide protection, even if overload is enabled in L1-01. Set L1-01 to 0 and ensure each motor has separate thermal relays installed. 0 to 4; 6 1 <2> S S S 480 213
2 L1-02 Motor Overload Protection Time Sets the motor thermal overload protection (oL1) time. A larger L1-02 time will increase the time for an oL1 fault to occur. This parameter does not typically require adjustment. Should be set in accordance with the overload tolerance of the motor. 0.1 to 20.0 8.0 min A A A 481 215
3 L1-03 Motor Overheat Alarm Operation Selection (PTC input) Sets operation when the motor temperature analog input (H3-02/10 = E) exceeds the oH3 alarm level. 0: Ramp to Stop 1: Coast to Stop 2: Fast-stop using C1-09 3: Alarm Only (“oH3” will flash) 0 to 3 3 A A A 482 216
4 L1-04 Motor Overheat Fault Operation Selection (PTC input) Sets stopping method when the motor temperature analog input (H3-02/10 = E) exceeds the oH4 fault level. 0: Ramp to Stop 1: Coast to Stop 2: Fast-stop 0 to 2 1 A A A 483 217
5 L1-05 Motor Temperature Input Filter Time (PTC input) This parameter adjusts the filter on the motor temperature analog input (H3-02 or H3-10 = E). Increase to add stability, decrease to improve response. 0.00 to 10.00 0.20 s A A A 484 217
6 L1-13 Continuous Electrothermal Operation Selection Determines whether or not to hold the electrothermal value when the power supply is interrupted. 0: Disabled 1: Enabled 0, 1 1 A A A 46D 217
7 L1-22 <16> <17> Leakage Current Filter Time Constant 1 Sets the time constant for reducing the sensitivity level when detecting leakage current. Set in seconds and used when operating at constant speed. Note: This parameter is available only when C6-02 is set to B. To display this parameter, first set C6-02 = B. 0.0 to 60.0 20.0 s A A A 768 217
8 L1-23 <16> <17> Leakage Current Filter Time Constant 2 Sets the time constant for reducing the sensitivity level when detecting leakage current. Set in seconds and used during acceleration and deceleration operation. Note: This parameter is available only when C6-02 is set to B. To display this parameter, first set C6-02 = B. 0.0 to 60.0 1.0 s A A A 769 217

Manual — Power loss and acceleration stall prevention — page 385

Source reference: SIEP C71060618F, December 2016, physical PDF page 385. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

For a restart to occur, the run command must be maintained throughout the Ride- Thru period.

L3: Stall Prevention Function Use L3 parameters to configure the Stall Prevention function.

B.2 Parameter Table

B

Parameter List

L2-01 | Momentary Power Loss Operation Selection

L2-02 | Momentary Power Loss Ride- Thru Time

L2-03 | Momentary Power Loss Minimum Baseblock Time

L2-04 | Momentary Power Loss Voltage Recovery Ramp Time

L2-05 <5> | Undervoltage Detection Level (Uv)

L2-06 | KEB Deceleration Time

L2-07 | KEB Acceleration Time

L2-08 | KEB Start Output Frequency Reduction

L2-11 <5> | Desired DC Bus Voltage during KEB

L3-01 | Stall Prevention Selection during Acceleration

L3-02 | Stall Prevention Level during Acceleration

L3-03 | Stall Prevention Limit during Acceleration

Parameter catalogue PDF385 section1 — PDF page 385

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L2-01 Momentary Power Loss Operation Selection Enables and disables the momentary power loss function. 0: Disabled - Drive trips on (Uv1) fault when power is lost. 1: Power Loss Ride-Thru Time - Drive will restart if power returns within the time set in L2-02. 2: CPU Power Active - Drive will restart if power returns as long as the CPU is working. 0 to 2 0 A A A 485 218
2 L2-02 Momentary Power Loss Ride- Thru Time Sets the Power Loss Ride-Thru time. Only effective when L2-01 = 1. 0.0 to 25.5 <3> A A A 486 218
3 L2-03 Momentary Power Loss Minimum Baseblock Time Sets the minimum wait time for residual motor voltage decay before the drive output reenergizes after power loss Ride-Thru. If L2-03 is greater than L2-02, operation resumes after the time set in L2-03. 0.1 to 5.0 <4> A A A 487 218
4 L2-04 Momentary Power Loss Voltage Recovery Ramp Time Sets the time for the output voltage to return to the preset V/f pattern during Speed Search. 0.0 to 5.0 <3> A A A 488 218
5 L2-05 <5> Undervoltage Detection Level (Uv) Sets the DC Bus undervoltage trip level. If this is set lower than the default setting, additional AC input impedance or DC bus reactance may be necessary. This value is used for KEB activation if L2-01 > 0. 150 to 210 <3> <6> A A A 489 218
6 L2-06 KEB Deceleration Time Sets the time required to decelerate from the speed when KEB was activated to zero speed. 0.0 to 200.0 0.0 s A A A 48A 220
7 L2-07 KEB Acceleration Time Sets the time to accelerate to the frequency reference when momentary power loss is over. If set to 0.0, the active acceleration time (C1-01, C1-03, C1-05, or C1-07) is used. 0.0 to 25.5 0.0 s A A A 48B 220
8 L2-08 KEB Start Output Frequency Reduction Sets the percentage of output frequency reduction at the beginning of deceleration when the KEB function is started. Reduction = (slip frequency before KEB) x (L2-08/100) x 2 0 to 300 100% A A A 48C 221
9 L2-11 <5> Desired DC Bus Voltage during KEB Sets the desired value of the DC bus voltage during KEB. 150 to 400 V E1-01 x 1.22 A A A 461 221
10 L3-01 Stall Prevention Selection during Acceleration Selects the Stall Prevention method used to prevent excessive current during acceleration. 0: Disabled - Motor accelerates at active acceleration rate. The motor may stall if load is too heavy or accel time is too short. 1: General Purpose - When output current exceeds L3-02 level, acceleration stops. Acceleration will continue when the output current level falls below the L3-02 level. 2: Intelligent - The active acceleration rate is ignored. Acceleration is completed in the shortest amount of time without exceeding the current value set in L3-02. 0 to 2 <7> 1 A A A 48F 221
11 L3-02 Stall Prevention Level during Acceleration Used when L3-01 = 1 or 2. 100% is equal to the drive rated current. Decrease the set value if stalling or excessive current occurs with default setting. 0 to 150 <18> <8> <18> A A A 490 222
12 L3-03 Stall Prevention Limit during Acceleration Sets Stall Prevention lower limit during acceleration when operating in the constant power range. Set as a percentage of the drive's rated current. 0 to 100 50% A A A 491 223

Manual — Stall prevention and overvoltage suppression — page 386

Source reference: SIEP C71060618F, December 2016, physical PDF page 386. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

B.2 Parameter Table

L3-04 | Stall Prevention Selection during Deceleration

L3-05 | Stall Prevention Selection during Run

L3-06 | Stall Prevention Level during Run

L3-11 | ov Suppression Function Selection

L3-17 <5> | Overvoltage Suppression and Stall Prevention Desired DC Bus Voltage

L3-20 | Main Power Circuit Voltage Adjustment Gain

L3-21 | Accel/Decel Rate Calculation Gain

L3-22 | Deceleration Time at Stall Prevention during Acceleration

Parameter catalogue PDF386 section1 — PDF page 386

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L3-04 Stall Prevention Selection during Deceleration When using a braking resistor, use setting "0". Setting "3" is used in specific applications. 0: Disabled - The drive decelerates at the active deceleration rate. If the load is too large or the deceleration time is too short, an ov fault may occur. 1: General Purpose - The drive decelerates at the active deceleration rate, but if the main circuit DC bus voltage reaches the Stall Prevention level, deceleration will stop. Deceleration will continue once the DC bus level drops below the Stall Prevention level. 2: Intelligent - The active deceleration rate is ignored and the drive decelerates as fast as possible without hitting ov fault level. Range: C1-02 / 10. 3: Stall Prevention with Braking Resistor - Stall Prevention during deceleration is enabled in coordination with dynamic braking. 4: Overexcitation Deceleration - Decelerates with the flux level determined by n3-13 (Overexcitation Gain). 7: Overexcitation Deceleration 3 - Applies more braking power than normal overexcitation deceleration. Yaskawa recommends extra caution due to the heavy load on the motor. 0 to 4; 7 <9> 1 S S S 492 223
2 L3-05 Stall Prevention Selection during Run Selects the Stall Prevention method to use to prevent drive faults during run. 0: Disabled - Drive runs a set frequency. A heavy load may cause the drive to trip on an oC or oL fault. 1: Decel Time 1 - The drive will decelerate at Decel Time 1 (C1-02) if the output current exceeds the level set by L3-06. Once the current level drops below the L3-06 level, the drive will accelerate back to its frequency reference at the active acceleration rate. 2: Decel Time 2 - Same as setting 1 except the drive decelerates at Decel Time 2 (C1-04). When output frequency is 6 Hz or less, Stall Prevention during run is disabled regardless of the setting in L3-05. 0 to 2 1 A − A 493 224
3 L3-06 Stall Prevention Level during Run Enabled when L3-05 is set to "1" or "2". 100% is equal to the drive rated current. Decrease the set value if stalling or excessive current occurs with the default settings. 30 to 150 <18> <8> <18> A − A 494 225
4 L3-11 ov Suppression Function Selection Enables or disables ov suppression function, which allows the drive to change the output frequency as the load changes, thus preventing an ov fault. 0: Disabled 1: Enabled Note: The frequency reference and motor speed diverge as the regenerative energy begins to flow back into the DC bus and triggers the ov suppression function. Disable this function when using a braking resistor. 0, 1 0 A A A 4C7 225
5 L3-17 <5> Overvoltage Suppression and Stall Prevention Desired DC Bus Voltage Sets the desired value for the DC bus voltage during overvoltage suppression and Stall Prevention during deceleration. Enabled only when L3-04 = 2 or L3-11 = 1. 150 to 400 V 370 V <6> A A A 462 226
6 L3-20 Main Power Circuit Voltage Adjustment Gain Sets the proportional gain used by KEB, Stall Prevention and overvoltage suppression. If ov or Uv1 occurs at the beginning of KEB deceleration, slowly increase this setting by 0.1. 0.00 to 5.00 1.00 A A A 465 226
7 L3-21 Accel/Decel Rate Calculation Gain Sets the proportional gain used to calculate the deceleration rate during KEB, ov suppression function and Stall Prevention during deceleration (L3-04 = 2). This parameter does not typically require adjustment. Increase the value in steps of 1.0 if overcurrent and overvoltage occur. 0.00 to 200.00 1.00 A A A 466 226
8 L3-22 Deceleration Time at Stall Prevention during Acceleration Sets the deceleration time used for Stall Prevention during acceleration in Open Loop Vector Control for PM motors. When set to 0, the drive decelerates at the normal deceleration time. 0.0 to 6000.0 0.0 s − − A 4F9 223

Manual — Frequency detection and fault restart — page 387

Source reference: SIEP C71060618F, December 2016, physical PDF page 387. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

L4: Frequency Detection Use L4 parameters to configure frequency detection operation.

L5: Fault Reset Use L5 parameters to configure Automatic Restart after fault.

L6: Overtorque Detection Use L6 parameters to configure overtorque detection.

B.2 Parameter Table

B

Parameter List

L3-23 | Automatic Reduction Selection for Stall Prevention during Run

L3-24 | Motor Acceleration Time for Inertia Calculations

L3-25 | Load Inertia Ratio

L4-01 | Speed Agreement Detection Level

L4-02 | Speed Agreement Detection Width

L4-03 | Speed Agreement Detection Level (+/-)

L4-04 | Speed Agreement Detection Width (+/-)

L4-05 | Frequency Reference Loss Detection Selection

L4-06 | Frequency Reference at Reference Loss

L4-07 | Frequency Detection Conditions

L4-08 <12> | Speed Agreement Detection Conditions

L5-01 | Number of Auto Restart Attempts

L5-02 | Auto Restart Operation Selection

L5-04 | Fault Reset Interval Time

L5-05 | Fault Reset Operation Selection

Parameter catalogue PDF387 section1 — PDF page 387

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L3-23 Automatic Reduction Selection for Stall Prevention during Run 0: Sets the Stall Prevention level throughout the entire frequency range to the value in parameter L3-06. 1: Automatically lowers the Stall Prevention level in the constant output range. The lower limit value is 40% of L3-06. 0, 1 0 A A Α 4FD 225
2 L3-24 Motor Acceleration Time for Inertia Calculations Sets the time needed to accelerate the uncoupled motor at rated torque from stop to the maximum frequency. Setting the drive capacity to parameter o2-04 or changing E2-11 will automatically set this parameter for a 4-pole motor. 0.001 to 10.000 <4> <10> <11> A A A 46E 226
3 L3-25 Load Inertia Ratio Sets the ratio between the motor and machine inertia. 0.0 to 1000.0 1.0 A A A 46F 227
4 L4-01 Speed Agreement Detection Level These parameters configure the multi-function output (H2- oo = 2, 3, 4, 5) settings "Speed Agree 1", "User Set Speed Agree 1", "Frequency Detection 1," and "Frequency detection 2". Parameter L4-01 sets the level while parameter L4-02 sets the hysteresis for the Speed Detection Output Function. 0.0 to 400.0 0.0 Hz A A A 499 227
5 L4-02 Speed Agreement Detection Width These parameters configure the multi-function output (H2- oo = 2, 3, 4, 5) settings "Speed Agree 1", "User Set Speed Agree 1", "Frequency Detection 1," and "Frequency detection 2". Parameter L4-01 sets the level while parameter L4-02 sets the hysteresis for the Speed Detection Output Function. 0.0 to 20.0 2.0 Hz A A A 49A 227
6 L4-03 Speed Agreement Detection Level (+/-) These parameters configure the Multi-Function Output (H2- oo = 13, 14, 15, 16) settings "Speed Agree 2", "User Set Speed Agree 2", "Frequency Detection 3," or "Frequency Detection 4". Parameter L4-03 sets the level while parameter L4-04 sets the hysteresis for the Speed Detection Output Function. -400.0 to +400.0 0.0 Hz A A A 49B 227
7 L4-04 Speed Agreement Detection Width (+/-) These parameters configure the Multi-Function Output (H2- oo = 13, 14, 15, 16) settings "Speed Agree 2", "User Set Speed Agree 2", "Frequency Detection 3," or "Frequency Detection 4". Parameter L4-03 sets the level while parameter L4-04 sets the hysteresis for the Speed Detection Output Function. 0.0 to 20.0 2.0 Hz A A A 49C 227
8 L4-05 Frequency Reference Loss Detection Selection Sets operation when the frequency reference is lost (reference drops 90% or more within 400 ms). 0: Stop - Drive will stop. 1: Run at L4-06 Level - Drive will run at the percentage set in L4-06 of the frequency reference before loss. 0, 1 0 A A A 49D 227
9 L4-06 Frequency Reference at Reference Loss Sets the frequency reference when a reference loss was detected and L4-05 = 1. Reference will be: Fref = Fref at time of loss x L4-06. 0.0 to 100.0 80.0% A A A 4C2 228
10 L4-07 Frequency Detection Conditions 0: No detection during baseblock. 1: Detection always enabled. 0, 1 0 A A A 470 228
11 L4-08 <12> Speed Agreement Detection Conditions 0: Match speed with the soft-starter output 1: Match frequency reference and motor speed Note: In V/f Control, the drive ignores the value set to L4-08 and refers to the soft-starter output to determine whether a speed agree situation has been reached. 0, 1 0 A A A 47F 228
12 L5-01 Number of Auto Restart Attempts Sets the counter for the number of times the drive attempts to restart when one of the following faults occurs: GF, LF, oC, oH1, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1. Parameter L5-05 determines the how the restart counter is incremented. When the drive operates without fault for 10 minutes, the counter will be reset. 0 to 10 0 A A A 49E 230
13 L5-02 Auto Restart Operation Selection Sets fault contact (H2-□□ = E) activation during automatic restart attempts. 0: Fault output not active. 1: Fault output active during restart attempt. 0, 1 0 A A A 49F 230
14 L5-04 Fault Reset Interval Time Sets the amount of time to wait between performing fault restarts. Enabled when L5-05 is set to 1. 0.5 to 600.0 s 10.0 s A A A 46C 231
15 L5-05 Fault Reset Operation Selection Selects the method of incrementing the restart counter. 0: Continuously attempt to restart and increment counter after successful restart (same as Varispeed VS616-F7/G7) 1: Attempt to restart with the interval time set in L5-04. Every trial increments the counter. (same as Varispeed VS606-V7) 0, 1 0 A A A 467 231

Manual — Torque detection selection and levels — page 388

Source reference: SIEP C71060618F, December 2016, physical PDF page 388. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

B.2 Parameter Table

L6-01 | Torque Detection Selection 1

L6-02 | Torque Detection Level 1

L6-03 | Torque Detection Time 1

L6-04 | Torque Detection Selection 2

L6-05 | Torque Detection Level 2

L6-06 | Torque Detection Time 2

Parameter catalogue PDF388 section1 — PDF page 388

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L6-01 Torque Detection Selection 1 Selects the overtorque/undertorque operation. overtorque and undertorque are determined by the settings in parameters L6-02 and L6-03. The multi-function output settings (H2- oo= B and 17) are also active if programmed. 0: Disabled 1: oL3 at Speed Agree - Alarm (overtorque detection only active during Speed Agree and operation continues after detection). 2: oL3 at RUN - Alarm (overtorque detection is always active and operation continues after detection). 3: oL3 at Speed Agree - Fault (overtorque detection only active during Speed Agree and drive output will shut down on an oL3 fault). 4: oL3 at RUN - Fault (overtorque detection is always active and drive output will shut down on an oL3 fault). 5: UL3 at Speed Agree - Alarm (undertorque detection is only active during Speed Agree and operation continues after detection). 6: UL3 at RUN - Alarm (undertorque detection is always active and operation continues after detection). 7: UL3 at Speed Agree - Fault (undertorque detection only active during Speed Agree and drive output will shut down on an oL3 fault). 8: UL3 at RUN - Fault (undertorque detection is always active and drive output will shut down on an oL3 fault). 0 to 8 0 A A A 4A1 231
2 L6-02 Torque Detection Level 1 Sets the overtorque/undertorque detection level. 100% is equal to the motor rated current in V/f Control and the motor rated torque in Open Loop Vector Control. 0 to 300 150% A A A 4A2 232
3 L6-03 Torque Detection Time 1 Sets the length of time an overtorque/undertorque condition must exist before Torque Detection 1 is triggered. 0.0 to 10.0 0.1 s A A A 4A3 233
4 L6-04 Torque Detection Selection 2 Sets the response to an overtorque/undertorque condition. overtorque and undertorque are determined by the settings in parameters L6-05 and L6-06. The multi-function output settings (H2-□□ = 18 and 19). 0: Disabled 1: oL4 at Speed Agree - Alarm (overtorque Detection only active during Speed Agree and Operation continues after detection). 2: oL4 at RUN - Alarm (overtorque Detection is always active and operation continues after detection). 3: oL4 at Speed Agree - Fault (overtorque Detection only active during Speed Agree and drive output will shut down on an oL4 fault). 4: oL4 at RUN - Fault (overtorque Detection is always active and drive output will shut down on an oL4 fault). 5: UL4 at Speed Agree - Alarm (undertorque Detection is only active during Speed Agree and operation continues after detection). 6: UL4 at RUN - Alarm (undertorque Detection is always active and operation continues after detection). 7: UL4 at Speed Agree - Fault (undertorque Detection only active during Speed Agree and drive output will shut down on an oL4 fault). 8: UL4 at RUN - Fault (undertorque Detection is always active and drive output will shut down on an oL4 fault). 0 to 8 0 A A A 4A4 232
5 L6-05 Torque Detection Level 2 Sets the overtorque/undertorque detection level. 100% is equal to the motor rated current in V/f Control or PM OLV and equal to the motor rated torque in Open Loop Vector Control. 0 to 300 150% A A A 4A5 232
6 L6-06 Torque Detection Time 2 Sets the length of time an overtorque/undertorque condition must exist before torque detection 2 is recognized by the drive. 0.0 to 10.0 0.1 s A A A 4A6 233

Manual — Mechanical weakening and torque limits — page 389

Source reference: SIEP C71060618F, December 2016, physical PDF page 389. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

L7: Torque Limit Use L7 parameters to configure the torque limit function.

L8: Hardware Protection Use L8 parameters to configure hardware protection functions.

B.2 Parameter Table

B

Parameter List

L6-08 | Mechanical Weakening (oL5) Detection Operation

L6-09 | Mechanical Weakening Detection Speed Level

L6-10 | Mechanical Weakening Detection Time

L6-11 | Mechanical Weakening Detection Start Time

L7-01 | Forward Torque Limit

L7-02 | Reverse Torque Limit

L7-03 | Forward Regenerative Torque Limit

L7-04 | Reverse Regenerative Torque Limit

L7-06 | Torque Limit Integral Time Constant

L7-07 | Torque Limit Control Method Selection during Accel/ Decel

L8-01 | Internal Dynamic Braking Resistor Protection Selection (ERF type)

L8-02 | Overheat Alarm Level

Parameter catalogue PDF389 section1 — PDF page 389

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L6-08 Mechanical Weakening (oL5) Detection Operation This function can detect an over/undertorque in a certain speed range as a result of machine fatigue. It is triggered by a certain operation time and uses the oL1 detection settings (L6-01 to L6-02) 0: Mechanical Weakening Detection disabled. 1: Continue running (alarm only). Detected when the speed (signed) is greater than L6-09. 2: Continue running (alarm only). Detected when the speed (not signed) is greater than L6-09. 3: Interrupt drive output (fault). Detected when the speed (signed) is greater than L6-09. 4: Interrupt drive output (fault). Detected when the speed (not signed) is greater than L6-09. 5: Continue running (alarm only). Detected when the speed (signed) is less than L6-09. 6: Continue running (alarm only). Detected when the speed (not signed) is less than L6-09. 7: Interrupt drive output (fault). Detected when the speed (signed) is less than L6-09. 8: Interrupt drive output (fault). Detected when the speed (not signed) is less than L6-09. 0 to 8 0 A A A 468 233
2 L6-09 Mechanical Weakening Detection Speed Level Sets the speed that triggers mechanical weakening detection. When L6-08 is set for an unsigned value, the absolute value is used even if the setting is negative. -110.0 to +110.0% 110% A A A 469 233
3 L6-10 Mechanical Weakening Detection Time Sets the time a mechanical weakening has to be detected before an Alarm/Fault is triggered. 0.0 to 10.0 s 0.1 s A A A 46A 234
4 L6-11 Mechanical Weakening Detection Start Time Sets the operation time (U1-04) that has to be passed before Mechanical weakening detection is active. 0 to 65535 0 A A A 46B 234
5 L7-01 Forward Torque Limit Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. 0 to 300 200% − A − 4A7 234
6 L7-02 Reverse Torque Limit Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. 0 to 300 200% − A − 4A8 234
7 L7-03 Forward Regenerative Torque Limit Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. 0 to 300 200% − A − 4A9 234
8 L7-04 Reverse Regenerative Torque Limit Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. 0 to 300 200% − A − 4AA 234
9 L7-06 Torque Limit Integral Time Constant Sets the integral time constant for the torque limit. 5 to 10000 200 ms − A − 4AC 234
10 L7-07 Torque Limit Control Method Selection during Accel/ Decel Selects the method of torque limit control during accel/decel. 0: Proportional Control (change to integral controls at fixed speeds). Use this setting when acceleration to the desired speed has priority over torque limitation. 1: Integral Control. Use this setting if the torque limitation has priority. When torque limit is applied to the motor, accel/decel time may increase and motor speed may not meet the speed reference. 0, 1 0 − A − 4C9 234
11 L8-01 Internal Dynamic Braking Resistor Protection Selection (ERF type) Selects the Braking resistor when using a 3% duty cycle heatsink mounted braking resistor. This parameter does not enable or disable the braking transistor of the drive. 0: Resistor overheat protection disabled 1: Resistor overheat protection enabled 0, 1 0 A A A 4AD 235
12 L8-02 Overheat Alarm Level When the heatsink temperature exceeds the value set in this parameter, an Overheat Alarm (oH) will occur. 50 to 130 <3> A A A 4AE 235

Manual — Hardware protection parameters — page 390

Source reference: SIEP C71060618F, December 2016, physical PDF page 390. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

B.2 Parameter Table

L8-03 | Overheat Pre-Alarm Operation Selection

L8-05 | Input Phase Loss Protection Selection

L8-07 | Output Phase Loss Protection Selection

L8-09 | Output Ground Fault Detection Selection

L8-10 | Heatsink Cooling Fan Operation Selection

L8-11 | Heatsink Cooling Fan Operation Delay Time

L8-12 | Ambient Temperature Setting

L8-15 | oL2 Characteristics Selection at Low Speeds

L8-18 | Soft Current Limit Selection

L8-19 | Frequency Reduction Rate during oH Pre-Alarm

L8-29 | Current Unbalance Detection (LF2)

L8-35 | Installation Method Selection

L8-38 | Carrier Frequency Reduction

Parameter catalogue PDF390 section1 — PDF page 390

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L8-03 Overheat Pre-Alarm Operation Selection Sets the drive operation when an overheat alarm oH is detected. 0: Ramp to Stop using the active decel time. 1: Coast to Stop. 2: Fast-stop using the time set in C1-09. 3: Alarm Only. Drive continues running, but displays an alarm. 4: Reduced Speed Operation. Drive continues to run with reduced frequency reference as specified in L8-19. Settings 0 through 2 trigger a fault relay if the heatsink becomes too hot. 0 to 4 3 A A A 4AF 235
2 L8-05 Input Phase Loss Protection Selection Selects the detection of input current phase loss, power supply voltage imbalance, or main circuit electrolytic capacitor deterioration. 0: Disabled 1: Enabled Note: This parameter is disabled in 200 V single-phase drives. 0, 1 1 A A A 4B1 236
3 L8-07 Output Phase Loss Protection Selection Selects the output phase loss detection. 0: Disabled 1: Enabled (triggered by a single phase loss) 2: Enabled (triggered when two phases are lost) Output phase loss is detected when operating with less than 5% of the drive rated current. Detection can mistakenly occur if the motor is small relative to the drive capacity rating (this parameter should be disabled in such cases). 0 to 2 1 A A A 4B3 236
4 L8-09 Output Ground Fault Detection Selection Selects the output ground fault detection. 0: Disabled 1: Enabled 0, 1 <3> A A A 4B5 237
5 L8-10 Heatsink Cooling Fan Operation Selection Controls the heatsink cooling fan operation. 0: Run with timer (Fan operates only during run and for L8-11 seconds after stop.) 1: Run always (Cooling fan operates whenever the drive is powered up.) 0, 1 0 A A A 4B6 237
6 L8-11 Heatsink Cooling Fan Operation Delay Time This parameter sets the delay time for the cooling fan to shut off after the run command is removed when L8-10 = 0. 0 to 300 60 s A A A 4B7 237
7 L8-12 Ambient Temperature Setting Used to input the ambient temperature. This value adjusts the drives oL2 detection level. -10 to 50 40 °C A A A 4B8 237
8 L8-15 oL2 Characteristics Selection at Low Speeds Sets the oL2 characteristics at output frequencies below 6 Hz. 0: No oL2 level reduction below 6 Hz. 1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz. 0, 1 1 A A A 4BB 237
9 L8-18 Soft Current Limit Selection Selects the software current limit function. Typically no adjustment is required. 0: Disabled 1: Enabled 0, 1 <15> A A − 4BE 238
10 L8-19 Frequency Reduction Rate during oH Pre-Alarm Specifies the frequency reference reduction gain at overheat pre-alarm when L8-03 = 4. 0.1 to 1.0 0.8 A A A 4BF 236
11 L8-29 Current Unbalance Detection (LF2) Selects the detection of unbalanced output currents caused by faulty devices in the output circuit. 0: Disabled 1: Enabled 0, 1 1 − − A 4DF 238
12 L8-35 Installation Method Selection Selects the installation type: 0: IP20/Open-Chassis Drive, IP00/Open-Chassis Drive 1: Side-by-Side Mounting 2: NEMA Type 1 Drive 3: Finless Drive or External Heatsink Installation 0 to 3 2 <13> Α Α A 4EC 238
13 L8-38 Carrier Frequency Reduction Provides protection to the IGBTs by reducing the carrier frequency at low speeds. 0: Disabled 1: Enabled below 6 Hz 2: Enabled for the whole speed range 0 to 2 <3> A A A 4EF 238

Manual — Protection footnotes and hunting control — page 391

Source reference: SIEP C71060618F, December 2016, physical PDF page 391. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

<1> Setting 6 available in drive software versions PRG: 1016 and later. <2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <3> Default setting value is dependent on parameter o2-04, Drive Model Selection. <4> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. <5> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. <6> Default setting value is dependent on parameter E1-01, Input Voltage Setting. <7> Setting value 2 is not available A1-02 = 5-PM OLV Control. When enabled, the drive stops accelerating when it exceeds the value of L3-02, Stall Prevention Level. The drive decelerates after 100 ms and begins accelerating again after restoring the current level. <8> Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD). <9> The setting range depends on the control mode set in A1-02. For PM OLV Control the setting range is 0 to 2 and 7. <10> Default setting value is dependent on parameter E5-01, Motor Code Selection. <11> Parameter value is changed if E2-11 is manually changed or changed by Auto-Tuning. <12> Available in drive software versions PRG: 1016 and later. <13> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <14> Available in drive software versions PRG: 1018 and later. There is normally no need to change this parameter from the default value. <15> Default setting is determined by drive software version and C6-02 setting. Drive software versions PRG: 1021 and later have a default setting of 0 when the carrier frequency is set for Leakage Current Rejection PWM (C6-02 = B), and 1 when C6-02 is set to any other value. <16> Parameter can be changed during Run. <17> Available in drive software versions PRG: 1021 and later. <18> The default setting and the upper limit of the setting range are determined by C6-01, Drive Duty Mode, and L8-38, Carrier Frequency Reduction Selection.

◆ n: Advanced Performance Set-Up

The n parameters are used to adjust more advanced performance characteristics such as hunting prevention, speed feedback detection, high-slip braking and R1 online tuning.

n1: Hunting Prevention Use n1 parameters to configure hunting prevention operation.

B.2 Parameter Table

B

Parameter List

L8-40 | Carrier Frequency Reduction Time

L8-41 | High Current Alarm Selection

L8-51 <14> | STo Fault Detection Level

L8-54 <14> | STo Deviation Detection

n1-01 | Hunting Prevention Selection

Parameter catalogue PDF391 section1 — PDF page 391

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 L8-40 Carrier Frequency Reduction Time Sets the time for that the drive continues running with reduced carrier frequency after the carrier reduction condition has gone (see also L8-38). A setting of 0.00 s disables the carrier frequency reduction time. 0.00 to 2.00 0.50 A A A 4F1 239
2 L8-41 High Current Alarm Selection Configures an alarm when the output current exceeds 150% of the drive rated current. 0: Alarm disabled. 1: Alarm enabled. 0, 1 0 A A A 4F2 239
3 L8-51 <14> STo Fault Detection Level Sets the STo detection level as a percentage of the motor rated current. Increase this value to detect pull-out more quickly during acceleration. The drive calculates this value automatically when L8-51 is set to 0.0%. 0.0 to 150.0% 0.0% – – A 471 239
4 L8-54 <14> STo Deviation Detection 0: Disabled. 1: Enabled. 0, 1 1 – – A 474 239

Parameter catalogue PDF391 section2 — PDF page 391

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 n1-01 Hunting Prevention Selection If the motor vibrates while lightly loaded, Hunting Prevention may reduce the vibration. 0: Disabled 1: Enabled When quick response is needed disable Hunting Prevention. 0, 1 1 A − − 580 240

Manual — Speed feedback braking and online tuning — page 392

Source reference: SIEP C71060618F, December 2016, physical PDF page 392. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

n2: Speed Feedback Detection Control Function Use n2 parameters to configure the Speed Feedback Detection Control function operation.

Adjust the setting by 0.05 units at a time, while checking the response.

n3: High-Slip Braking Use n3 parameters to configure the high-slip braking function.

n6: Online Tuning of Motor Line-to-Line Resistance Use n6 parameters to adjust the motor line-to-line resistance while the drive is online.

n8: Permanent Magnet (PM) Motor Control Use n8 parameters to control the PM motor control.

B.2 Parameter Table

n1-02 | Hunting Prevention Gain Setting

n1-03 | Hunting Prevention Time Constant

n1-05 | Hunting Prevention Gain while in Reverse

n2-01 | Speed Feedback Detection Control (AFR) Gain

n2-02 | Speed Feedback Detection Control (AFR) Time Constant

n2-03 | Speed Feedback Detection Control (AFR) Time Constant 2

n3-01 | High-Slip Braking Deceleration Frequency Width

n3-02 | High-Slip Braking Current Limit

n3-03 | High-Slip Braking Dwell Time at Stop

n3-04 | High-Slip Braking Overload Time

n3-13 | Overexcitation Deceleration Gain

n3-21 | High-Slip Suppression Current Level

n3-23 | Overexcitation Operation Selection

n6-01 | Line-to-Line Motor Resistance Online Tuning

Parameter catalogue PDF392 section1 — PDF page 392

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 n1-02 Hunting Prevention Gain Setting Sets the gain for the Hunting Prevention Function. If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases. If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases. 0.00 to 2.50 1.00 A − − 581 240
2 n1-03 Hunting Prevention Time Constant Sets the time constant used for hunting prevention. 0 to 500 <1> A − − 582 240
3 n1-05 Hunting Prevention Gain while in Reverse Sets the gain used for Hunting Prevention. When set to 0, the gain n1-02 is used for operation in reverse direction. 0.00 to 2.50 0.00 A − − 530 240
4 n2-01 Speed Feedback Detection Control (AFR) Gain Sets the internal speed feedback detection control gain in the automatic frequency regulator (AFR). This parameter does not typically require adjustment. Adjust this parameter as follows: If hunting occurs, increase the set value. If response is low, decrease the set value. 0.00 to 10.00 <8> − A − 584 240
5 n2-02 Speed Feedback Detection Control (AFR) Time Constant Sets the AFR time constant 1. 0 to 2000 50 ms − A − 585 241
6 n2-03 Speed Feedback Detection Control (AFR) Time Constant 2 Sets the AFR time constant 2. Increase the setting if overvoltage occurs during sudden load changes or the speed overshoots during fast acceleration. 0 to 2000 750 ms − A − 586 241
7 n3-01 High-Slip Braking Deceleration Frequency Width Sets the output frequency reduction step width when the drive stops the motor using high-slip braking (HSB). If Overvoltage (ov) faults occur during HSB, this parameter may need to be increased. 1 to 20 5% A − − 588 241
8 n3-02 High-Slip Braking Current Limit Sets the current limit during HSB. Higher n3-02 settings will shorten motor stopping times but increase the motor current, and therefore motor heating. 100 to 200 150% A − − 589 242
9 n3-03 High-Slip Braking Dwell Time at Stop Sets the time the drive will run with minimum frequency (E1-09) at the end of deceleration. If this time is set too low, the machine inertia can cause the motor to rotate slightly after HSB completion. 0.0 to 10.0 1.0 s A − − 58A 242
10 n3-04 High-Slip Braking Overload Time Sets the time required for an HSB overload fault (oL7) to occur when the drive output frequency does not change during an HSB stop. This parameter does not typically require adjustment. 30 to 1200 40 s A − − 58B 242
11 n3-13 Overexcitation Deceleration Gain Applies a gain to the V/f pattern during deceleration (L3-04 = 4). Returns to normal values after ramp to stop or at re- acceleration. To increase the braking power of overexcitation, increase the gain by 1.25 to 1.30. 1.00 to 1.40 1.10 A A − 531 242
12 n3-21 High-Slip Suppression Current Level If overcurrent or overload occur during high-slip deceleration, reduce the high-slip suppression current level. Set as a percentage of the drive rated current. 0 to 150 100% A A − 579 242
13 n3-23 Overexcitation Operation Selection 0: Enabled in both directions 1: Enabled only when rotating forward 2: Enabled only when in reverse 0 to 2 0 A A − 57B 242
14 n6-01 Line-to-Line Motor Resistance Online Tuning Tunes the line-to-line motor resistance continuously during operation. 0: Disabled 1: Enabled 0, 1 1 − A − 570 243

Manual — PM performance controls — page 393

Source reference: SIEP C71060618F, December 2016, physical PDF page 393. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection. <2> Parameter can be changed during Run. <3> Setting range varies depending on drive software version. Software versions PRG: 1018 and later disable pull-in current when n8-48 = 0 and allow this parameter to be changed during run. PRG: 1018 and later: 0% or 20 to 200% PRG: 1017 and earlier: 20 to 200%

B.2 Parameter Table

B

Parameter List

n8-45 | Speed Feedback Detection Control Gain

n8-47 | Pull-In Current Compensation Time Constant

n8-48 <2> | Pull-In Current

n8-49 <2> | d-Axis Efficiency Current Control for High-

n8-51 | Acceleration Pull-In Current

n8-54 | Voltage Error Compensation Time Constant

n8-55 | Load Inertia

n8-62 <5> | Output Voltage Limit

n8-63 <6> | Output Voltage Limit Gain 1

n8-65 <7> | Speed Feedback Detection Control Gain during ov Suppression

n8-68 <6> | Output Voltage Limit Gain 2

n8-87 <6> | Output Voltage Limit Selection

n8-88 <6> | Output Voltage Limit Switching Current Level

n8-89 <6> | Output Voltage Limit Switching Current Hysteresis Width

n8-90 <6> | Output Voltage Limit Switching Speed

n8-91 <6> | Id Limit for Output Voltage Limit Control

Parameter catalogue PDF393 section1 — PDF page 393

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 n8-45 Speed Feedback Detection Control Gain Sets the gain for internal speed feedback detection control. This parameter does not typically require adjustment. Increase this setting if hunting occurs. Decrease to lower the response. 0.00 to 10.00 0.80 − − A 538 243
2 n8-47 Pull-In Current Compensation Time Constant Sets the time constant to make the pull-in current and actual current value agree. Decrease the value if the motor begins to oscillate. Increase the value if it takes too long for the current reference to equal the output current. 0.0 to 100.0 s 5.0 s − − A 53A 243
3 n8-48 <2> Pull-In Current Defines the amount of current provided to the motor during no-load operation at a constant speed. Set as a percentage of the motor rated current. Increase this setting when hunting occurs while running at a constant speed. <3> 30% − − A 53B 243
4 n8-49 <2> d-Axis Current for High- Efficiency Control Sets control. the amount of d-Axis current when using Energy Saving <4> 0% − − A 53C 243
5 n8-51 Acceleration Pull-In Current Sets the pull-in current during acceleration as a percentage of the motor rated current (E5-03). Set to a high value when more starting torque is needed. 0 to 200% 50% − − A 53E 244
6 n8-54 Voltage Error Compensation Time Constant Sets the time constant for voltage error compensation. Adjust the value when hunting occurs at low speed. Increase in steps of 0.1 or disable the compensation by setting n8-45 to 0 when hunting occurs with sudden load changes or when oscillations occur at start. 0.00 to 10.00 s 1.00 s − − A 56D 244
7 n8-55 Load Inertia Sets the ratio between motor and machine inertia. 0: less than 1:10. 1: between 1:10 to 1:30. 2: between 1:30 to 1:50. 3: higher than 1:50. 0 to 3 0 − − A 56E 244
8 n8-62 <5> Output Voltage Limit Sets the limit for the output voltage. Adjustment is normally needed only if the input voltage is below the n8-62 set value. In this case set n8-62 to the input voltage. 0.0 to 230.0 200 Vac − − A 57D 244
9 n8-63 <6> Output Voltage Limit Gain 1 Sets the gain used for output voltage limit. 0.00 to 100.00 1.00 – – A 57E 245
10 n8-65 <7> Speed Feedback Detection Control Gain during ov Suppression Sets the gain used for internal speed feedback detection during ov Suppression 0.00 to 10.00 1.50 − − A 65C 245
11 n8-68 <6> Output Voltage Limit Gain 2 Sets the voltage detection level adjustment gain. 0.50 to 1.50 0.95 – – A 237 245
12 n8-87 <6> Output Voltage Limit Selection Determines the method of the output voltage limit. 0: Feedback method 1: Feed forward method Use the feed forward method if oscillation occurs in the constant output range. 0, 1 0 – – A 2BC 245
13 n8-88 <6> Output Voltage Limit Switching Current Level Sets the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03). 0 to 400% 400% – – A 2BD 245
14 n8-89 <6> Output Voltage Limit Switching Current Hysteresis Width Determines the hysteresis of the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03). 0 to [n8-88] 3% – – A 2BE 245
15 n8-90 <6> Output Voltage Limit Switching Speed Sets the speed level to switch the output voltage limit sequence. Set as a percentage of the maximum output frequency (E1-04). 0 to 200% 200% – – A 2BF 245
16 n8-91 <6> Id Limit for Output Voltage Limit Control Sets the amount of pull-in current that flows through the motor while operating at constant speed. Set as a percentage of the motor rated current (E5-03). Increase this setting if hunting occurs at constant speed. -200 to 0% -50% – – A 2F7 246

Manual — Advanced footnotes and operator displays — page 394

Source reference: SIEP C71060618F, December 2016, physical PDF page 394. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

<4> Setting range varies depending on drive software version. Software versions PRG: 1018 and later allow this parameter to be changed during run. PRG: 1018 and later: -200.0 to 200.0% PRG: 1017 and earlier: -200.0 to 0.0% <5> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. <6> Available in drive software versions PRG: 1018 and later. There is normally no need to change this parameter from the default value. <7> Parameter available in drive software versions PRG: 1011 and later. <8> Default setting is determined by drive model. Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00. Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50.

◆ o: Operator Related Parameters

o parameters are used to set up the LED digital operator displays.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

o1: Display Settings Use o1 parameters to configure the digital operator display.

Set to U1-06 as a default (Output Voltage Reference).

o2: Operator Keypad Functions Use o2 parameters to configure LED digital operator key functions.

B.2 Parameter Table

o1-01 <1> | Drive Mode Unit Monitor Selection

o1-02 <1> | User Monitor Selection After Power Up

o1-03 | Digital Operator Display Selection

o1-05 <1> <7> | LCD Contrast Control

o1-10 | Frequency Reference Setting and User-Set Display

o1-11 | Frequency Reference Setting / Decimal Display

o2-01 | LO/RE Key Function Selection

o2-02 | STOP Key Function Selection

Parameter catalogue PDF394 section1 — PDF page 394

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 o1-01 <1> Drive Mode Unit Monitor Selection Switches the display after the power has been turned on. When using an LED operator, pressing the up arrow key will display the following data: frequency reference → rotational direction → output frequency → output current → output voltage → U1-□□. (This is done by entering the 1□□ part of U1-□□. Certain monitors are not available in some control modes.) <2> 106 A A A 500 247
2 o1-02 <1> User Monitor Selection After Power Up Selects the information that is displayed when the power is turned on. 1: Frequency Reference (U1-01) 2: Forward/Reverse 3: Output Frequency (U1-02) 4: Output Current (U1-03) 5: User Monitor (set by o1-01) 1 to 5 1 A A A 501 247
3 o1-03 Digital Operator Display Selection Sets the units to display the frequency reference and output frequency. 0: Hz 1: % (100% = E1-04) 2: r/min (enter the number of motor poles into E2-04/E4-04/ E5-04) 3: User defined by parameters o1-10 and o1-11 0 to 3 0 A A A 502 247
4 o1-05 <1> <7> LCD Contrast Control Sets the brightness of the optional LCD operator. 0 to 5 3 A A A 504 248
5 o1-10 Frequency Reference Setting and User-Set Display These settings define the display values when o1-03 is set to 3. o1-10 sets display values when operating at the maximum output frequency. o1-11 sets the position of the decimal positions. 1 to 60000 <3> A A A 520 248
6 o1-11 Frequency Reference Setting / Decimal Display These settings define the display values when o1-03 is set to 3. o1-10 sets display values when operating at the maximum output frequency. o1-11 sets the position of the decimal positions. 0 to 3 <3> A A A 521 248
7 o2-01 LO/RE Key Function Selection Enables/Disables the digital operator LO/RE key. 0: Disabled 1: Enabled 0, 1 1 A A A 505 248
8 o2-02 STOP Key Function Selection Enables/Disables the operator panel STOP key when the drive is operated form external sources (not operator). 0: Disabled 1: Enabled 0, 1 1 A A A 506 248

Manual — Operator copy and maintenance parameters — page 395

Source reference: SIEP C71060618F, December 2016, physical PDF page 395. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

o3: Copy Function Use o3 parameters to Read, Copy and Verify the parameter settings to and from the drive.

o4: Maintenance Period Use o4 parameters to perform maintenance.

B.2 Parameter Table

B

Parameter List

o2-03 | User Parameter Default Value

o2-04 <4> | Drive Model Selection

o2-05 | Frequency Reference Setting Method Selection

o2-06 | Operation Selection when Digital Operator is Disconnected

o2-07 | Motor Direction at Power Up when Using Operator

o2-09 | –

o3-01 | Copy Function Selection

o3-02 | Copy Allowed Selection

o4-01 | Accumulated Operation Time Setting

o4-02 | Accumulated Operation Time Selection

o4-03 | Cooling Fan Operation Time Setting

o4-05 | Capacitor Maintenance Setting

o4-07 | DC Bus Pre-Charge Relay Maintenance Setting

o4-09 | IGBT Maintenance Setting

Parameter catalogue PDF395 section1 — PDF page 395

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 o2-03 User Parameter Default Value Allows storing of parameter settings as a User Initialization Selection (value 1110 for A1-03). The value returns to 0 after entering 1 or 2. 0: No Change 1: Set Defaults - Saves current parameter settings as user initialization. 2: Clear All - Clears the currently saved user initialization. 0 to 2 0 A A A 507 249
2 o2-04 <4> Drive Model Selection Sets the drive model. This parameter only needs to be set when installing a new control board. Do not change for other reason. 0 to FF <5> A A A 508 249
3 o2-05 Frequency Reference Setting Method Selection Selects if the ENTER key must be pressed when inputting the frequency reference by the operator keypad. 0: Data/Enter key must be pressed to enter a frequency reference. 1: Data/Enter key is not required. The output frequency changes immediately when the reference is changed by the UP or DOWN keys on the digital operator. The ENTER key does not need to be pressed. 0, 1 0 A A A 509 249
4 o2-06 Operation Selection when Digital Operator is Disconnected Sets drive action when the digital operator is removed in LOCAL mode or with b1-02 = 0. 0: The drive will continue operation 1: The drive will trigger a fault (oPr) and the motor will coast to stop 0, 1 0 A A A 50A 250
5 o2-07 Motor Direction at Power Up when Using Operator 0: Forward 1: Reverse This parameter requires that drive operation be assigned to the digital operator. 0, 1 0 A A A 527 250
6 o2-09 – Factory use. – – – – – – –
7 o3-01 Copy Function Selection 0: Copy select 1: INV → OP READ (Read parameters from the drive, saving them onto the digital operator.) 2: OP → INV WRITE (Copy parameters from the digital operator, writing them to the drive.) 3: OP → INV VERIFY (Verify parameter settings on the drive to check if they match the data saved on the operator.) To read the drive parameter settings into the digital operator, set o3-02 to 1 (to allow reading). 0 to 3 0 A A A 515 —
8 o3-02 Copy Allowed Selection Locks the READ operation to prevent accidental overwriting of the data stored in the LED operator. 0: READ operation prohibited 1: READ operation allowed 0, 1 0 A A A 516 —
9 o4-01 Accumulated Operation Time Setting Sets the value for the cumulative operation time of the drive in units of 10 h. 0 to 9999 0 A A A 50B 251
10 o4-02 Accumulated Operation Time Selection Determines, how the cumulative operation time (U4-01) is counted. 0: Logs power-on time 1: Logs operation time when the drive output is active (output operation time). 0, 1 0 A A A 50C 251
11 o4-03 Cooling Fan Operation Time Setting Sets the value of the fan operation time monitor U4-03 in units of 10 h. <6> 0 to 9999 0 A A A 50E 251
12 o4-05 Capacitor Maintenance Setting Sets the value of the capacitor maintenance time monitor U4-05. 0 to 150 0% A A A 51D 251
13 o4-07 DC Bus Pre-Charge Relay Maintenance Setting Sets the value of the Soft Charge Bypass Relay Maintenance monitor U4-06. 0 to 150 0% A A A 523 251
14 o4-09 IGBT Maintenance Setting Sets the value of the IGBT Maintenance monitor U4-07. 0 to 150 0% A A A 525 252

Manual — Operator notes and DriveWorksEZ connections — page 396

Source reference: SIEP C71060618F, December 2016, physical PDF page 396. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

<1> Parameter can be changed during run. <2> Setting range is determined by drive software version. PRG: 1016 and later: 104 to 810 PRG: 1015 and earlier: 104 to 621 <3> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection. <4> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330 <5> Default setting value is dependent on parameter o2-04, Drive Model Selection. <6> Available in drive software versions PRG: 1011 and later. Parameter o4-03 is set in 10 h units. When o4-03 = 30, the operation time for the cooling fan will start counting from 300 hours, and monitor U4-03 will display “300 H”. Earlier software versions set o4-03 in 1 h units. <7> Available in drive software versions PRG: 1022 and later.

◆ q: DriveWorksEZ Parameters

◆ r: DriveWorksEZ Connection Parameters

B.2 Parameter Table

o4-11 | U2, U3 Initialization

o4-12 | kWh Monitor Initialization

o4-13 | Number of Run Commands Initialize Selection

q1-01 to q6-07 | DriveWorksEZ Parameters

r1-01 | DriveWorksEZ Connection Parameter 1 (upper)

r1-02 | DriveWorksEZ Connection Parameter 1 (lower)

r1-03 | DriveWorksEZ Connection Parameter 2 (upper)

r1-04 | DriveWorksEZ Connection Parameter 2 (lower)

r1-05 | DriveWorksEZ Connection Parameter 3 (upper)

r1-06 | DriveWorksEZ Connection Parameter 3 (lower)

r1-07 | DriveWorksEZ Connection Parameter 4 (upper)

Parameter catalogue PDF396 section1 — PDF page 396

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 o4-11 U2, U3 Initialization 0: U2-□□ and U3-□□ monitor data are not reset when the drive is initialized using A1-03. 1: U2-□□ and U3-□□ monitor data are reset when the drive is initialized using A1-03. (The value of o4-11 is automatically returned to 0.) 0, 1 0 A A A 510 252
2 o4-12 kWh Monitor Initialization 0: U4-10 and U4-11 monitor data are not reset when the drive is initialized using A1-03. 1: U4-10 and U4-11 monitor data are reset when the drive is initialized using A1-03. (The value of o4-12 is automatically returned to 0.) 0, 1 0 A A A 512 252
3 o4-13 Number of Run Commands Initialize Selection 0: U4-02 monitor data is not reset when the drive is initialized using A1-03. 1: U4-02 monitor data is reset when the drive is initialized using A1-03. (The value of o4-13 is automatically returned to 0.) 0, 1 0 A A A 528 252

Parameter catalogue PDF396 section2 — PDF page 396

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 q1-01 to q6-07 DriveWorksEZ Parameters Reserved for DriveWorksEZ. - - A A Α - —

Parameter catalogue PDF396 section3 — PDF page 396

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 r1-01 DriveWorksEZ Connection Parameter 1 (upper) Parameter 1 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1840 —
2 r1-02 DriveWorksEZ Connection Parameter 1 (lower) Parameter 1 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1841 —
3 r1-03 DriveWorksEZ Connection Parameter 2 (upper) Parameter 2 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1842 —
4 r1-04 DriveWorksEZ Connection Parameter 2 (lower) Parameter 1 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1843 —
5 r1-05 DriveWorksEZ Connection Parameter 3 (upper) Parameter 1 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1844 —
6 r1-06 DriveWorksEZ Connection Parameter 3 (lower) Parameter 3 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1845 —
7 r1-07 DriveWorksEZ Connection Parameter 4 (upper) Parameter 4 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1846 —

Manual — DriveWorksEZ connection register pairs — page 397

Source reference: SIEP C71060618F, December 2016, physical PDF page 397. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

B.2 Parameter Table

B

Parameter List

r1-08 | DriveWorksEZ Connection Parameter 4 (lower)

r1-09 | DriveWorksEZ Connection Parameter 5 (upper)

r1-10 | DriveWorksEZ Connection Parameter 5 (lower)

r1-11 | DriveWorksEZ Connection Parameter 6 (upper)

r1-12 | DriveWorksEZ Connection Parameter 6 (lower)

r1-13 | DriveWorksEZ Connection Parameter 7 (upper)

r1-14 | DriveWorksEZ Connection Parameter 7 (lower)

r1-15 | DriveWorksEZ Connection Parameter 8 (upper)

r1-16 | DriveWorksEZ Connection Parameter 8 (lower)

r1-17 | DriveWorksEZ Connection Parameter 9 (upper)

r1-18 | DriveWorksEZ Connection Parameter 9 (lower)

r1-19 | DriveWorksEZ Connection Parameter 10 (upper)

r1-20 | DriveWorksEZ Connection Parameter 10 (lower)

r1-21 | DriveWorksEZ Connection Parameter 11 (upper)

r1-22 | DriveWorksEZ Connection Parameter 11 (lower)

r1-23 | DriveWorksEZ Connection Parameter 12 (upper)

r1-24 | DriveWorksEZ Connection Parameter 12 (lower)

r1-25 | DriveWorksEZ Connection Parameter 13 (upper)

r1-26 | DriveWorksEZ Connection Parameter 13 (lower)

r1-27 | DriveWorksEZ Connection Parameter 14 (upper)

r1-28 | DriveWorksEZ Connection Parameter 14 (lower)

r1-29 | DriveWorksEZ Connection Parameter 15 (upper)

r1-30 | DriveWorksEZ Connection Parameter 15 (lower)

r1-31 | DriveWorksEZ Connection Parameter 16 (upper)

r1-32 | DriveWorksEZ Connection Parameter 16 (lower)

r1-33 | DriveWorksEZ Connection Parameter 17 (upper)

r1-34 | DriveWorksEZ Connection Parameter 17 (lower)

r1-35 | DriveWorksEZ Connection Parameter 18 (upper)

Parameter catalogue PDF397 section1 — PDF page 397

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 r1-08 DriveWorksEZ Connection Parameter 4 (lower) Parameter 4 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1847 —
2 r1-09 DriveWorksEZ Connection Parameter 5 (upper) Parameter 5 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1848 —
3 r1-10 DriveWorksEZ Connection Parameter 5 (lower) Parameter 5 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1849 —
4 r1-11 DriveWorksEZ Connection Parameter 6 (upper) Parameter 6 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 184A —
5 r1-12 DriveWorksEZ Connection Parameter 6 (lower) Parameter 6 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 184BH —
6 r1-13 DriveWorksEZ Connection Parameter 7 (upper) Parameter 7 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 184C —
7 r1-14 DriveWorksEZ Connection Parameter 7 (lower) Parameter 7 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 184D —
8 r1-15 DriveWorksEZ Connection Parameter 8 (upper) Parameter 8 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 184E —
9 r1-16 DriveWorksEZ Connection Parameter 8 (lower) Parameter 8 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 184F —
10 r1-17 DriveWorksEZ Connection Parameter 9 (upper) Parameter 9 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1850 —
11 r1-18 DriveWorksEZ Connection Parameter 9 (lower) Parameter 9 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1851 —
12 r1-19 DriveWorksEZ Connection Parameter 10 (upper) Parameter 10 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1852 —
13 r1-20 DriveWorksEZ Connection Parameter 10 (lower) Parameter 10 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1853 —
14 r1-21 DriveWorksEZ Connection Parameter 11 (upper) Parameter 11 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1854 —
15 r1-22 DriveWorksEZ Connection Parameter 11 (lower) Parameter 11 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1855 —
16 r1-23 DriveWorksEZ Connection Parameter 12 (upper) Parameter 12 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1856 —
17 r1-24 DriveWorksEZ Connection Parameter 12 (lower) Parameter 12 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1857 —
18 r1-25 DriveWorksEZ Connection Parameter 13 (upper) Parameter 13 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1858 —
19 r1-26 DriveWorksEZ Connection Parameter 13 (lower) Parameter 13 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1859 —
20 r1-27 DriveWorksEZ Connection Parameter 14 (upper) Parameter 14 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 185A —
21 r1-28 DriveWorksEZ Connection Parameter 14 (lower) Parameter 14 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 185B —
22 r1-29 DriveWorksEZ Connection Parameter 15 (upper) Parameter 15 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 185C —
23 r1-30 DriveWorksEZ Connection Parameter 15 (lower) Parameter 15 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 185D —
24 r1-31 DriveWorksEZ Connection Parameter 16 (upper) Parameter 16 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 185E —
25 r1-32 DriveWorksEZ Connection Parameter 16 (lower) Parameter 16 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 185F —
26 r1-33 DriveWorksEZ Connection Parameter 17 (upper) Parameter 17 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1860 —
27 r1-34 DriveWorksEZ Connection Parameter 17 (lower) Parameter 17 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1861 —
28 r1-35 DriveWorksEZ Connection Parameter 18 (upper) Parameter 18 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1862 —

Manual — Connection continuations and motor tuning — page 398

Source reference: SIEP C71060618F, December 2016, physical PDF page 398. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Name Description Range Def.

Control Mode: V/f, OLV, PM; Addr. Hex; Pg.

OLV

PM

◆ T: Motor Tuning

Enter data into the following parameters to tune the motor and drive for optimal performance

These values differ depending on the motor code value and motor parameter settings.

<1> The available tuning methods depend on control mode. Select values 2 or 3 in V/f Control, 0 or 2 in OLV control, and 2 for Motor 2 control. <2> Setting range varies depending on drive software version. PRG: 1016 and later: 0.03 to 650.00 kW PRG: 1015 and earlier: 0.00 to 650.00 kW <3> Default setting value is dependent on parameter o2-04, Drive Model Selection. <4> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.

B.2 Parameter Table

r1-36 | DriveWorksEZ Connection Parameter 18 (lower)

r1-37 | DriveWorksEZ Connection Parameter 19 (upper)

r1-38 | DriveWorksEZ Connection Parameter 19 (lower)

r1-39 | DriveWorksEZ Connection Parameter 20 (upper)

r1-40 | DriveWorksEZ Connection Parameter 20 (lower)

T1-00 | Motor Selection 1/2

T1-01 | Auto-Tuning Mode Selection

T1-02 | Motor Rated Power

T1-03 <4> | Motor Rated Voltage

T1-04 | Motor Rated Current

T1-05 | Motor Base Frequency

T1-06 | Number of Motor Poles

T1-07 | Motor Base Speed

T1-11 | Motor Iron Loss

Parameter catalogue PDF398 section1 — PDF page 398

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 r1-36 DriveWorksEZ Connection Parameter 18 (lower) Parameter 18 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1863 —
2 r1-37 DriveWorksEZ Connection Parameter 19 (upper) Parameter 19 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1864 —
3 r1-38 DriveWorksEZ Connection Parameter 19 (lower) Parameter 19 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1865 —
4 r1-39 DriveWorksEZ Connection Parameter 20 (upper) Parameter 20 for connecting DriveWorksEZ (upper). 0 to FFFFH 0 – A A 1866 —
5 r1-40 DriveWorksEZ Connection Parameter 20 (lower) Parameter 20 for connecting DriveWorksEZ (lower). 0 to FFFFH 0 – A A 1867 —

Parameter catalogue PDF398 section2 — PDF page 398

Source row Parameter Name Description Range Default Control mode V/f Control mode OLV Control mode PM Address (hex) Reference page
1 T1-00 Motor Selection 1/2 Selects which set of motor parameters are used and set during Auto-Tuning. If Motor 2 selection (H1-□□ = 16) is not selected, this parameter will not be displayed. 1: Motor 1 (sets E1-□□, E2-□□) 2: Motor 2 (sets E3-□□, E4-□□. This selection is not displayed if motor 2 has not been selected.) 1, 2 1 A A − 700 106
2 T1-01 Auto-Tuning Mode Selection Selects the Auto-Tuning mode. 0: Rotational Auto-Tuning 2: Stationary Auto-Tuning for Line-to-Line Resistance 3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Speed Estimation type Speed Search) 0, 2, 3 <1> 2 or 3 in V/f 0 or 2 in OLV 2 in Motor 2 A A − 701 106
3 T1-02 Motor Rated Power Sets the motor rated power in kilowatts (kW). Note: If motor power is given in horsepower, power in kW can be calculated using the following formula: kW = HP x 0.746. <2> <3> A A − 702 106
4 T1-03 <4> Motor Rated Voltage Sets the motor rated voltage in volts (V). 0.0 to 255.5 200.0 V A A − 703 107
5 T1-04 Motor Rated Current Sets the motor rated current in amperes (A). 10 to 200% of drive rated current <3> A A − 704 107
6 T1-05 Motor Base Frequency Sets the base frequency of the motor in Hertz (Hz). 0.0 to 400.0 60.0 Hz A A − 705 107
7 T1-06 Number of Motor Poles Sets the number of motor poles. 2 to 48 4 A A − 706 107
8 T1-07 Motor Base Speed Sets the base speed of the motor in revolutions per minute r/min (RPM). 0 to 24000 1750 r/ min A A − 707 107
9 T1-11 Motor Iron Loss Provides the iron loss for determining the Energy Saving coefficient. The value set to E2-10 (motor iron loss) when the power is cycled. If T1-02 is changed, an initial value valid for the selected capacity will be shown. 0 to 65535 14 W A − − 70B 107

Manual — Operation status monitors — page 399

Source reference: SIEP C71060618F, December 2016, physical PDF page 399. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ U: Monitors

Monitor parameters allow the user to view drive status, fault information, and other information about drive operation.

No.; Name; Description; Analog Output Level; Unit

Control Mode: V/f, OLV, PM; Addr. Hex.

OLV

PM

U1: Operation Status Monitors Use U1 monitors to display the operation status of the drive.

B.2 Parameter Table

B

Parameter List

U1-01 | Frequency Reference

U1-02 | Output Frequency

U1-03 | Output Current

U1-04 | Control Mode

U1-05 | Motor Speed

U1-06 | Output Voltage Reference

U1-07 | DC Bus Voltage

U1-08 | Output Power

U1-09 | Torque Reference

U1-10 | Input Terminal Status

Monitor catalogue PDF399 — PDF page 399

Source row Monitor Name Description Analog output level Unit Control mode V/f Control mode OLV Control mode PM Address (hex)
1 U1-01 Frequency Reference Monitors the frequency 10 V: Max frequency 0.01 Hz A A A 40
2 U1-02 Output Frequency Displays the output frequency. Display units are determined by o1-03. 10 V: Max frequency 0.01 Hz A A A 41
3 U1-03 Output Current Displays the output current. 10 V: Drive rated current 0.01 A <1> <2> A A A 42
4 U1-04 Control Mode Control method set in A1-02. 0: V/f without PG 2: Open Loop Vector (OLV) 5: PM Open Loop Vector (PM) No output signal available – A A A 43
5 U1-05 Motor Speed Displays the motor speed feedback. Display units are determined by o1-03. 10 V: Maximum speed 0.01 Hz – A – 44
6 U1-06 Output Voltage Reference Displays the output voltage. 10 V: 200 Vrms (400 Vrms) 0.1 V A A A 45
7 U1-07 DC Bus Voltage Displays the DC bus voltage. 10 V: 400 V (800 V) 1 V A A A 46
8 U1-08 Output Power Displays the output power (this value is determined internally). 10 V: Drive capacity (kW) (rated motor capacity) <1> A A A 47
9 U1-09 Torque Reference Monitor of internal torque reference value for Open Loop Vector (OLV) control 10 V: Motor rated torque – – A – 48
10 U1-10 Input Terminal Status Displays the input terminal status. LED callout labels, top to bottom: Digital input terminal S1 enabled; S2 enabled; S3 enabled; S4 enabled; S5 enabled; S6 enabled; S7 enabled. Exact LED segment geometry and callout-to-segment position remain in source image; no numeric bit assignment inferred. No output signal available – A A A 49

Manual — Status and error monitors and fault trace — page 400

Source reference: SIEP C71060618F, December 2016, physical PDF page 400. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No.; Name; Description; Analog Output Level; Unit

Control Mode: V/f, OLV, PM; Addr. Hex.

OLV

PM

U2: Fault Trace Use U2 monitors to view fault trace data. <3>

B.2 Parameter Table

U1-11 | Output Terminal Status

U1-12 | Drive Status

U1-13 | Terminal A1 Input Level

U1-14 | Terminal A2 Input Level

U1-16 | Output Frequency after Soft Starter

U1-18 | oPE Fault Parameter

U1-19 | MEMOBUS/Modbus Error Code

U1-24 | Input Pulse Monitor

U1-25 | Software No. (Flash)

U1-26 | Software No. (ROM)

U1-27 | Operator Message ID

U1-28 | Drive Message ID

U2-01 | Current Fault

Monitor catalogue PDF400 — PDF page 400

Source row Monitor Name Description Analog output level Unit Control mode V/f Control mode OLV Control mode PM Address (hex)
1 U1-11 Output Terminal Status Displays the output terminal status. Multi-Function Digital Output (fault) (terminal MA/MB-MC) Multi-Function Digital Output 1 (terminal P1) enabled Multi-Function Digital Output 2 (terminal P2) enabled LED diagram labels retained in printed top-to-bottom order. Exact segment geometry and callout-to-segment position remain original-only; no numeric bit assignment inferred. No output signal available – A A A 4A
2 U1-12 Drive Status Verifies the drive operation status. During run During zero-speed During REV During fault reset signal input During speed agree Drive ready During alarm detection During fault detection LED diagram labels retained in printed top-to-bottom order. Exact segment geometry and callout-to-segment position remain original-only; no numeric bit assignment inferred. No output signal available – A A A 4B
3 U1-13 Terminal A1 Input Level Displays analog input A1 level: 100% when input is 10 V. 10 V: 100% 0.1% A A A 4E
4 U1-14 Terminal A2 Input Level Displays analog input A2 level: 100% when input is 10 V. 10 V: 100% 0.1% A A A 4F
5 U1-16 Output Frequency after Soft Starter Displays output frequency with ramp time and S-curves. Units determined by o1-03. 10 V: Max frequency 0.01 Hz A A A 53
6 U1-18 oPE Fault Parameter Displays parameter no. for oPEoo or Err where error occurred. No output signal available – A A A 61
7 U1-19 MEMOBUS/Modbus Error Code Displays the contents of a MEMOBUS/Modbus error. CRC Error Data Length Error Not Used Parity Error Overrun Error Framing Error Timed Out Not Used LED diagram labels retained in printed top-to-bottom order. Exact segment geometry and callout-to-segment position remain original-only; no numeric bit assignment inferred. No output signal available – A A A 66
8 U1-24 Input Pulse Monitor Displays the Pulse Train input RP frequency. 32000 1 Hz A A A 7D
9 U1-25 Software No. (Flash) Flash ID No signal output avail. – A A A 4D
10 U1-26 Software No. (ROM) ROM ID No signal output avail. – A A A 5B
11 U1-27 Operator Message ID Displays the numeric code of the remote operator (for use by the manufacturer). No signal output avail. – A A A 7A8
12 U1-28 Drive Message ID Displays the numeric code of the drive (for use by the manufacturer) No signal output avail. – A A A 7A9
13 U2-01 Current Fault Displays the current fault. No signal output avail. – A A A 80

Manual — Previous fault snapshots and fault history — page 401

Source reference: SIEP C71060618F, December 2016, physical PDF page 401. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No.; Name; Description; Analog Output Level; Unit

Control Mode: V/f, OLV, PM; Addr. Hex.

OLV

PM

U3: Fault History Use U3 monitors to display fault data. <3>

B.2 Parameter Table

B

Parameter List

U2-02 | Previous Fault

U2-03 | Frequency Reference at Previous Fault

U2-04 | Output Frequency at Previous Fault

U2-05 | Output Current at Previous Fault

U2-06 | Motor Speed at Previous Fault

U2-07 | Output Voltage at Previous Fault

U2-08 | DC Bus Voltage at Previous Fault

U2-09 | Output Power at Previous Fault

U2-10 | Torque Reference at Previous Fault

U2-11 | Input Terminal Status at Previous Fault

U2-12 | Output Terminal Status at Previous Fault

U2-13 | Drive Operation Status at Previous Fault

U2-14 | Cumulative Operation Time at Previous Fault

U2-15 | Soft Starter Speed Reference at Previous Fault

U2-16 | Motor q-Axis Current at Previous Fault

U2-17 | Motor d-Axis Current at Previous Fault

U3-01 | Most Recent Fault

U3-02 | 2nd Most Recent Fault

U3-03 | 3rd Most Recent Fault

U3-04 | 4th Most Recent Fault

U3-05 | 5th Most Recent Fault

U3-06 | 6th Most Recent Fault

U3-07 | 7th Most Recent Fault

U3-08 | 8th Most Recent Fault

U3-09 | 9th Most Recent Fault

U3-10 | 10th Most Recent Fault

U3-11 | Cumulative Operation Time at Most Recent Fault

Monitor catalogue PDF401 — PDF page 401

Source row Monitor Name Description Analog output level Unit Control mode V/f Control mode OLV Control mode PM Address (hex)
1 U2-02 Previous Fault Displays the previous fault. No signal output avail. – A A A 81
2 U2-03 Frequency Reference at Previous Fault Displays the frequency reference at the previous fault. No signal output avail. 0.01 Hz A A A 82
3 U2-04 Output Frequency at Previous Fault Displays the output frequency at the previous fault. No signal output avail. 0.01 Hz A A A 83
4 U2-05 Output Current at Previous Fault Displays the output current at the previous fault. No signal output avail. <1> <2> A A A 84
5 U2-06 Motor Speed at Previous Fault Displays the motor speed at the previous fault. No signal output avail. 0.01 Hz − A − 85
6 U2-07 Output Voltage at Previous Fault Displays the output voltage at the previous fault. No signal output avail. 0.1 V A A A 86
7 U2-08 DC Bus Voltage at Previous Fault Displays the DC bus voltage at the previous fault. No signal output avail. 1 V A A A 87
8 U2-09 Output Power at Previous Fault Displays the output power at the previous fault. No signal output avail. 0.1 kW A A A 88
9 U2-10 Torque Reference at Previous Fault Displays the torque reference at the previous fault. No signal output avail. 0.1% − Α − 89
10 U2-11 Input Terminal Status at Previous Fault Displays the input terminal status at the previous fault. Displayed as in U1-10. No signal output avail. – A A A 8A
11 U2-12 Output Terminal Status at Previous Fault Displays the output status at the previous fault. Displays the same status displayed in U1-11. No signal output avail. – A A A 8B
12 U2-13 Drive Operation Status at Previous Fault Displays the operation status of the drive at the previous fault. Displays the same status displayed in U1-12. No signal output avail. – A A A 8C
13 U2-14 Cumulative Operation Time at Previous Fault Displays the cumulative operation time at the previous fault. No signal output avail. 1 H A A A 8D
14 U2-15 Soft Starter Speed Reference at Previous Fault Displays the run speed after a soft start when a previous fault occurred. Displayed as in U1-16. No signal output avail. 0.01 % A A A 7E0
15 U2-16 Motor q-Axis Current at Previous Fault Displays the q-axis current for the motor at the previous fault. No signal output avail. 0.10 % A A A 7E1
16 U2-17 Motor d-Axis Current at Previous Fault Displays the d-axis current for the motor at the previous fault. No signal output avail. 0.10 % − A A 7E2
17 U3-01 Most Recent Fault Displays the most recent fault. No signal output avail. – A A A 90 (800)
18 U3-02 2nd Most Recent Fault Displays the second most recent fault. No signal output avail. – A A A 91 (801)
19 U3-03 3rd Most Recent Fault Displays the third most recent fault. No signal output avail. – A A A 92 (802)
20 U3-04 4th Most Recent Fault Displays the fourth most recent fault. No signal output avail. – A A A 93 (803)
21 U3-05 5th Most Recent Fault Displays the fifth most recent fault. No signal output avail. – A A A 804
22 U3-06 6th Most Recent Fault Displays the sixth most recent fault. No signal output avail. – A A A 805
23 U3-07 7th Most Recent Fault Displays the seventh most recent fault. No signal output avail. – A A A 806
24 U3-08 8th Most Recent Fault Displays the eighth most recent fault. No signal output avail. – A A A 807
25 U3-09 9th Most Recent Fault Displays the ninth most recent fault. No signal output avail. – A A A 808
26 U3-10 10th Most Recent Fault Displays the tenth most recent fault. No signal output avail. – A A A 809
27 U3-11 Cumulative Operation Time at Most Recent Fault Displays the cumulative operation time at the most recent fault. No signal output avail. 1 h A A A 94 (80A)

Manual — Fault times and maintenance monitors — page 402

Source reference: SIEP C71060618F, December 2016, physical PDF page 402. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No.; Name; Description; Analog Output Level; Unit

Control Mode: V/f, OLV, PM; Addr. Hex.

OLV

PM

U4: Maintenance Monitors Use U4 monitors to display drive maintenance information.

B.2 Parameter Table

U3-12 | Cumulative Operation Time at 2nd Most Recent Fault

U3-13 | Cumulative Operation Time at 3rd Most Recent Fault

U3-14 | Cumulative Operation Time at 4th Most Recent Fault

U3-15 | Cumulative Operation Time at 5th Most Recent Fault

U3-16 | Cumulative Operation Time at 6th Most Recent Fault

U3-17 | Cumulative Operation Time at 7th Most Recent Fault

U3-18 | Cumulative Operation Time at 8th Most Recent Fault

U3-19 | Cumulative Operation Time at 9th Most Recent Fault

U3-20 | Cumulative Operation Time at 10th Most Recent Fault

U4-01 <7> | Accumulated Operation Time

U4-02 | Number of Run Commands

U4-03 <5> <8> | Cooling Fan Operation Time

U4-04 | Cooling Fan Maintenance

U4-05 | Capacitor Maintenance

U4-06 <5> | Soft Charge Bypass Relay Maintenance

U4-07 <5> | IGBT Maintenance

U4-08 <6> | Heatsink Temperature

U4-09 | LED Check

U4-10 | kWh, Lower 4 Digits

U4-11 | kWh, Upper 5 Digits

Monitor catalogue PDF402 — PDF page 402

Source row Monitor Name Description Analog output level Unit Control mode V/f Control mode OLV Control mode PM Address (hex)
1 U3-12 Cumulative Operation Time at 2nd Most Recent Fault Displays the cumulative operation time at the second most recent fault. No signal output avail. 1 h A A A 95 (80B)
2 U3-13 Cumulative Operation Time at 3rd Most Recent Fault Displays the cumulative operation time at the third most recent fault. No signal output avail. 1 h A A A 96 (80C)
3 U3-14 Cumulative Operation Time at 4th Most Recent Fault Displays the cumulative operation time at the fourth most recent fault. No signal output avail. 1 h A A A 97 (80D)
4 U3-15 Cumulative Operation Time at 5th Most Recent Fault Displays the cumulative operation time at the fifth most recent fault. No signal output avail. 1 h A A A 80E
5 U3-16 Cumulative Operation Time at 6th Most Recent Fault Displays the cumulative operation time at the sixth most recent fault. No signal output avail. 1 h A A A 80F
6 U3-17 Cumulative Operation Time at 7th Most Recent Fault Displays the cumulative operation time at the seventh most recent fault. No signal output avail. 1 h A A A 810
7 U3-18 Cumulative Operation Time at 8th Most Recent Fault Displays the cumulative operation time at the eighth most recent fault. No signal output avail. 1 h A A A 811
8 U3-19 Cumulative Operation Time at 9th Most Recent Fault Displays the cumulative operation time at the ninth most recent fault. No signal output avail. 1 h A A A 812
9 U3-20 Cumulative Operation Time at 10th Most Recent Fault Displays the cumulative operation time at the tenth most recent fault. No signal output avail. 1 h A A A 813
10 U4-01 <7> Accumulated Operation Time Displays the cumulative operation time of the drive. The value for the cumulative operation time counter can be reset in parameter o4-01. Use parameter o4-02 to determine if the operation time should start as soon as the power is switched on or only while the run command is present. The maximum number displayed is 99999, after which the value is reset to 0. No signal output avail. 1 h A A A 4C
11 U4-02 Number of Run Commands Displays the number of times the run command is entered. Reset the number of run commands using parameter o4-13. This value will reset to 0 and start counting again after reaching 65535. No signal output avail. – A A A 75
12 U4-03 <5> <8> Cooling Fan Operation Time Displays the cumulative operation time of the cooling fan. The default value for the fan operation time is reset in parameter o4-03. This value will reset to 0 and start counting again after reaching 99999. <4> No signal output avail. 1 h A A A 67
13 U4-04 Cooling Fan Maintenance Displays main cooling fan usage time in as a percentage of their expected performance life. Parameter o4-03 can be used to reset this monitor. No signal output avail. 1% A A A 7E
14 U4-05 Capacitor Maintenance Displays main circuit capacitor usage time in as a percentage of their expected performance life. Parameter o4-05 can be used to reset this monitor. No signal output avail. 1% A A A 7C
15 U4-06 <5> Soft Charge Bypass Relay Maintenance Displays the soft charge bypass relay maintenance time as a percentage of the estimated product life. Parameter o4-07 can be used to reset this monitor. No signal output avail. 1% A A A 7D6
16 U4-07 <5> IGBT Maintenance Displays IGBT usage time as a percent of expected performance life. Parameter o4-09 can be used to reset this monitor. No signal output avail. 1% A A A 7D7
17 U4-08 <6> Heatsink Temperature Displays the heatsink temperature. 10 V: 100 °C 1 °C A A A 68
18 U4-09 LED Check Lights all segments of the LED to verify that the display is working properly. No signal output avail. – A A A 3C
19 U4-10 kWh, Lower 4 Digits Monitors the drive output power. The value is shown as a 9 digit number displayed across two monitor parameters, U4-10 and U4-11. Example: 12345678.9 kWh is displayed as: U4-10: 678.9 kWh U4-11: 12345 MWh No signal output avail. kWh A A A 5C
20 U4-11 kWh, Upper 5 Digits Monitors the drive output power. The value is shown as a 9 digit number displayed across two monitor parameters, U4-10 and U4-11. Example: 12345678.9 kWh is displayed as: U4-10: 678.9 kWh U4-11: 12345 MWh No signal output avail. MWh A A A 5D

Manual — Reference source and run state monitors — page 403

Source reference: SIEP C71060618F, December 2016, physical PDF page 403. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No.; Name; Description; Analog Output Level; Unit

Control Mode: V/f, OLV, PM; Addr. Hex.

OLV

PM

U5: PID Monitor Use U5 monitors to view application-specific settings.

B.2 Parameter Table

B

Parameter List

U4-13 | Peak Hold Current

U4-14 | Peak Hold Output Frequency

U4-16 | Motor Overload Estimate (oL1)

U4-18 | Frequency Reference Source Selection

U4-19 | Frequency Reference from MEMOBUS/Modbus Comm.

U4-20 | Option Frequency Reference

U4-21 | Run Command Source Selection

U4-22 | MEMOBUS/Modbus Communications Reference

U4-23 | Option Card Reference

Monitor catalogue PDF403 — PDF page 403

Source row Monitor Name Description Analog output level Unit Control mode V/f Control mode OLV Control mode PM Address (hex)
1 U4-13 Peak Hold Current Displays the peak hold current during run. No signal output avail. 0.01 A <2> A A A 7CF
2 U4-14 Peak Hold Output Frequency Displays the output frequency when operating at the peak hold current. No signal output avail. 0.01 Hz A A A 7D0
3 U4-16 Motor Overload Estimate (oL1) 100% = oL1 detection level 100% = oL1 detection level 0.1% A A A 7D8
4 U4-18 Frequency Reference Source Selection Displays the source for the frequency reference as XY-nn. X: indicates which reference is used: 1 = Reference 1 (b1-01) 2 = Reference 2 (b1-15) Y-nn: indicates the reference source 0-01 = Operator (d1-01) 1-01 = Analog (terminal A1) 1-02 = Analog (terminal A2) 2-02 to 17 = Multi-step speed (d1-02 to 17) 3-01 = MEMOBUS/Modbus comm. 4-01 = Option 5-01 = Pulse Input 6-01 = CASE 7-01 = DWEZ – – A A A 7DA
5 U4-19 Frequency Reference from MEMOBUS/Modbus Comm. Displays the frequency reference provided by MEMOBUS/ Modbus (decimal). – – A A A 7DB
6 U4-20 Option Frequency Reference Displays the frequency reference input by an option card (decimal). – – A A A 7DD
7 U4-21 Run Command Source Selection Displays the source for the Run command as XY-nn. X: Indicates which Run source is used: 1 = Reference 1 (b1-02) 2 = Reference 2 (b1-16) Y: Input power supply data 0 = Operator 1 = External terminals 2 = Not used 3 = MEMOBUS/Modbus communications 4 = Option 5 = Not used 6 = CASE 7 = DWEZ nn: Run command limit status data 00: No limit status. 01: Run command was left on when stopped in the PRG mode. 02: Run command was left on when switching from LOCAL to REMOTE operation. 03: Waiting for the soft charge bypass contactor after the power is switched on (Uv or Uv1 flashes after 10 seconds). 04: Waiting for “Run Command Prohibited” time period to end. 05: Fast-stop (digital input (H1-□□ = 15), operator) 06: b1-17 (run command given at power-up). 07: During Baseblock while coast to stop with timer 08: Frequency reference is below minimal reference during Baseblock 09: Waiting for Enter command 10: Run command was switched on while copying parameters – – A A A 7DD
8 U4-22 MEMOBUS/Modbus Communications Reference Displays the drive control data set by MEMOBUS/Modbus communications register No. 0001H as a 4 digit hexadecimal number. – – A A A 7DE
9 U4-23 Option Card Reference Displays drive control data set by an option card as a 4 digit hexadecimal number. – – A A A 7DF

Manual — PID, control and custom monitors — page 404

Source reference: SIEP C71060618F, December 2016, physical PDF page 404. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No.; Name; Description; Analog Output Level; Unit

Control Mode: V/f, OLV, PM; Addr. Hex.

OLV

PM

U6: Control Monitor Use U6 monitors to display drive control information.

U8: Custom Monitors for DriveWorksEZ U8 monitors are reserved for DriveWorksEZ

B.2 Parameter Table

U5-01 | PID Feedback

U5-02 | PID Input

U5-03 | PID Output

U5-04 | PID Setpoint

U5-05 | PID Differential Feedback

U5-06 | PID Adjusted Feedback

U6-01 | Motor Secondary Current (Iq)

U6-02 | Motor Excitation Current (ld)

U6-03 | ASR Input

U6-04 | ASR Output

U6-05 | Output voltage reference (Vq)

U6-06 | Output Voltage Reference (Vd)

U6-07 | q-axis ACR Output

U6-08 | d-Axis ACR Output

U6-20 | Frequency Reference Bias (Up/Down 2)

U6-21 | Offset Frequency

U6-80 to U6-99 | Option Monitors 1 to 20

U8-01 | –

U8-02 | –

U8-03 | –

U8-04 | –

U8-05 | –

U8-06 | –

U8-07 | –

Monitor catalogue PDF404 — PDF page 404

Source row Monitor Name Description Analog output level Unit Control mode V/f Control mode OLV Control mode PM Address (hex)
1 U5-01 PID Feedback Displays the PID feedback value in. 10 V: 100% (max. freq.) 0.01 % A A A 57
2 U5-02 PID Input Displays the amount of PID input (deviation between PID target and feedback). 10 V: 100% (max. freq.) 0.01 % A A A 63
3 U5-03 PID Output Displays PID control output. 10 V: 100% (max. freq.) 0.01 % A A A 64
4 U5-04 PID Setpoint Displays the PID setpoint. 10 V: 100% (max. freq.) 0.01 % A A A 65
5 U5-05 PID Differential Feedback Displays the 2nd PID feedback value if differential feedback is used. 10 V: 100% (max. freq.) 0.01 % A A A 7D2
6 U5-06 PID Adjusted Feedback Displays the difference of both feedback values if differential feedback is used (U5-01) - (U5-05). If differential feedback is not used, then U5-01 and U5-06 will be the same. 10 V: 100% (max. freq.) 0.01 % A A A 7D3
7 U6-01 Motor Secondary Current (Iq) Displays the value of the motor secondary current (Iq). 10 V: 100% 0.1% A A A 51
8 U6-02 Motor Excitation Current (ld) Displays the value calculated for the motor excitation current (Id). 10 V: 100% 0.1% − A A 52
9 U6-03 ASR Input Displays the ASR input value if V/f Control with Simple PG Feedback is enabled. 10 V: 100% (max. freq.) 0.1% A − − 54
10 U6-04 ASR Output Displays the ASR output value if V/f Control with Simple PG Feedback is enabled. 10 V: 100% (max. freq.) 0.1% A − − 55
11 U6-05 Output voltage reference (Vq) Output voltage reference (Vq). (q-axis) 10 V: 200 V (400 V) 0.1 Vac − A A 59
12 U6-06 Output Voltage Reference (Vd) Output voltage reference (Vd). (d-axis) 10 V: 200 V (400 V) 0.1 Vac − A A 5A
13 U6-07 q-axis ACR Output Displays the current control (ACR) output of for the motor secondary current (Iq). 10 V: 100% 0.1% − A − 5F
14 U6-08 d-Axis ACR Output Displays the current control (ACR) output of for the motor excitation current (Id). 10 V: 100% 0.1% − A − 60
15 U6-20 Frequency Reference Bias (Up/Down 2) Displays the bias value used to adjust the frequency reference. 10 V: max. frequency 0.1% A A A 7D4
16 U6-21 Offset Frequency The total value of the offset frequencies d7-01, d7-02 and d7-03 selected with digital inputs 44 to 46 is displayed. 10 V: max. frequency 0.1% A A A 7D5
17 U6-80 to U6-99 Option Monitors 1 to 20 Monitors reserved for use by the communication option card. Monitor content varies based on the communication option connected to the drive. Refer to the instruction manual for the option card for more information.. No signal output avail. – A A A 7B0 to 7F9
18 U8-01 – Reserved for DriveWorksEZ, Monitor 1. – 0.01 % Α A Α 1950
19 U8-02 – Reserved for DriveWorksEZ, Monitor 2. – 0.01 % A A A 1951
20 U8-03 – Reserved for DriveWorksEZ, Monitor 3. – 0.01 % A A A 1952
21 U8-04 – Reserved for DriveWorksEZ, Monitor 4. – 0.01 % A A A 1953
22 U8-05 – Reserved for DriveWorksEZ, Monitor 5. – 0.01 % A A A 1954
23 U8-06 – Reserved for DriveWorksEZ, Monitor 6. – 0.01 % A A A 1955
24 U8-07 – Reserved for DriveWorksEZ, Monitor 7. – 0.01 % A A A 1956

Manual — Custom monitor continuation and monitor footnotes — page 405

Source reference: SIEP C71060618F, December 2016, physical PDF page 405. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No.; Name; Description; Analog Output Level; Unit

Control Mode: V/f, OLV, PM; Addr. Hex.

OLV

PM

<1> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. <2> U1-03, U2-05, and U4-13 display monitor contents in amp units. When reading the value of these monitors via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current. <3> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330 <4> Available in drive software versions PRG: 1011 and later. Maximum value is 65536 in drive software versions PRG: 1010 and earlier. <5> When this value reaches 100%, the maintenance period has been reached for the component in question and the drive is at risk of faulting out due to component failure. Periodically check the maintenance monitors to avoid this situation. <6> Available in drive software versions PRG: 1011 and later. <7> MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register 0099H. <8> MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register 009BH.

B.2 Parameter Table

B

Parameter List

U8-08 | –

U8-09 | –

U8-10 | –

Monitor catalogue PDF405 — PDF page 405

Source row Monitor Name Description Analog output level Unit Control mode V/f Control mode OLV Control mode PM Address (hex)
1 U8-08 – Reserved for DriveWorksEZ, Monitor 8. – 0.01 % A A A 1957
2 U8-09 – Reserved for DriveWorksEZ, Monitor 9. – 0.01 % A A A 1958
3 U8-10 – Reserved for DriveWorksEZ, Monitor 10. – 0.01 % A A A 1959

Manual — Motor 1 control-dependent defaults — page 406

Source reference: SIEP C71060618F, December 2016, physical PDF page 406. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

B.3 Control Mode Dependent Parameter Default Values

The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2). These parameters are initialized to the shown values if the control mode is changed.

◆ A1-02 (Motor 1 Control Mode) Dependent Parameters

Table B.1 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values

Parameter Description Setting Range Resolution

Control Modes (A1-02)

V/f (0) OLV (2) PM (5)

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection. <2> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. <3> Default setting value is dependent on parameter E5-01, Motor Code Selection.

b3-02 | Speed Search deactivation current

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type)

b8-02 | Energy Saving gain

C2-01 | S-curve time at acceleration start

C3-01 | Slip compensation gain

C3-02 | Slip compensation time constant

C4-01 | Torque compensation gain

C4-02 | Torque comp. primary delay time

C6-02 | Carrier frequency

E1-04 | Maximum output frequency

E1-05 | Maximum output voltage <2>

E1-06 | Base Frequency

E1-07 | Middle output frequency

E1-08 | Middle output freq. voltage <2>

E1-09 | Minimum output frequency

E1-10 | Minimum output voltage <2>

E1-11 | Middle output frequency 2

E1-12 | Middle output freq. voltage 2 <2>

E1-13 | Base voltage <2>

L1-01 | Motor protection selection

L3-20 | Main power circuit voltage adjustment gain

L3-21 | Accel/decel rate calculation gain

Table B.1 A1-02 Motor1 control-mode-dependent defaults — PDF page 406

Source row Parameter Description Setting range Resolution V/f (0) default OLV (2) default PM (5) default
1 b3-02 Speed Search deactivation current 0 to 200 1% 120 100 –
2 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) 0.00 to 6.00 – 0.50 <1> 0.50 <1> 0.30
3 b8-02 Energy Saving gain 0.0 to 10.0 0.1 – 0.7 –
4 C2-01 S-curve time at acceleration start 0.00 to 10.00 0.01 s 0.20 0.20 1.00
5 C3-01 Slip compensation gain 0.0 to 2.5 0.1 0.0 1.0 –
6 C3-02 Slip compensation time constant 0 to 10000 1 ms 2000 200 –
7 C4-01 Torque compensation gain 0.00 to 2.50 0.01 1.00 1.00 0.00
8 C4-02 Torque comp. primary delay time 0 to 10000 1 ms 200 20 100
9 C6-02 Carrier frequency 1 to F 1 7 <1> 7 <1> 2
10 E1-04 Maximum output frequency 40.0 to 400.0 0.1 Hz 60.0 60.0 <3>
11 E1-05 Maximum output voltage <2> 0.0 to 255.0 0.1 V 230.0 230.0 <3>
12 E1-06 Base Frequency 0.0 to 400.0 0.1 Hz 60.0 60.0 <3>
13 E1-07 Middle output frequency 0.0 to 400.0 0.1 Hz 3.0 3.0 –
14 E1-08 Middle output freq. voltage <2> 0.0 to 255.0 0.1 V 18.4 13.8 –
15 E1-09 Minimum output frequency 0.0 to 400.0 0.1 Hz 1.5 0.5 <3>
16 E1-10 Minimum output voltage <2> 0.0 to 255.0 0.1 V 13.8 2.9 –
17 E1-11 Middle output frequency 2 0.0 to 400.0 0.1 Hz 0.0 0.0 –
18 E1-12 Middle output freq. voltage 2 <2> 0.0 to 255.0 0.1 V 0.0 0.0 –
19 E1-13 Base voltage <2> 0.0 to 255.0 0.1 V 0.0 0.0 –
20 L1-01 Motor protection selection 0 to 4 – 1 1 4
21 L3-20 Main power circuit voltage adjustment gain 0.00 to 5.00 0.01 1.00 0.30 0.65
22 L3-21 Accel/decel rate calculation gain 0.00 to 200.00 0.01 1.00 1.00 2.50

Manual — Motor 2 control-dependent defaults — page 407

Source reference: SIEP C71060618F, December 2016, physical PDF page 407. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ E3-01 (Motor 2 Control Mode) Dependent Parameters

Table B.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values

Parameter Description Setting Range Resolution

Control Modes (E3-01)

V/f (0) OLV (2)

<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.

B.3 Control Mode Dependent Parameter Default Values

B

Parameter List

E3-04 | Maximum output frequency

E3-05 | Maximum output voltage <1>

E3-06 | Base Frequency

E3-07 | Middle output frequency

E3-08 | Middle output freq. voltage <1>

E3-09 | Minimum output frequency

E3-10 | Minimum output voltage <1>

E3-11 | Middle output frequency 2

E3-12 | Middle output freq. voltage 2 <1>

E3-13 | Base voltage <1>

E3-14 | Motor 2 Slip compensation gain

Table B.2 E3-01 Motor2 control-mode-dependent defaults — PDF page 407

Source row Parameter Description Setting range Resolution V/f (0) default OLV (2) default
1 E3-04 Maximum output frequency 40.0 to 400.0 0.1 Hz 60.0 60.0
2 E3-05 Maximum output voltage <1> 0.0 to 255.0 0.1 V 200.0 230.0
3 E3-06 Base Frequency 0.0 to 400.0 0.1 Hz 60.0 60.0
4 E3-07 Middle output frequency 0.0 to 400.0 0.1 Hz 3.0 3.0
5 E3-08 Middle output freq. voltage <1> 0.0 to 255.0 0.1 V 18.4 13.8
6 E3-09 Minimum output frequency 0.0 to 400.0 0.1 Hz 1.5 0.5
7 E3-10 Minimum output voltage <1> 0.0 to 255.0 0.1 V 13.8 2.9
8 E3-11 Middle output frequency 2 0.0 to 400.0 0.1 Hz 0.0 0.0
9 E3-12 Middle output freq. voltage 2 <1> 0.0 to 255.0 0.1 V 0.0 0.0
10 E3-13 Base voltage <1> 0.0 to 255.0 0.1 V 0.0 0.0
11 E3-14 Motor 2 Slip compensation gain 0.0 to 2.5 0.1 0.0 1.0

Manual — V/f patterns by drive model range — page 408

Source reference: SIEP C71060618F, December 2016, physical PDF page 408. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

B.4 V/f Pattern Default Values

The tables below show the V/f pattern settings default values depending on the control mode (A1-02) and the V/f pattern selection (E1-03 in V/f Control).

Table B.3 E1-03 V/f Pattern Settings for Drive Capacity: Models BA0001 to BA0010, 2A0001 to 2A0010, and 4A0001 to 4A0005

No.; Unit; V/f Control E1-03 settings0,1,2,3,4,5,6,7,8,9,A,B,C,D,E,F; OLV

<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.

Table B.4 E1-03 V/f Pattern Settings for Drive Capacity: Models BA0012 to BA0018, 2A0012 to 2A0069, and 4A0007 to 4A0038

E1-04 | Hz | 50.0

E1-05 <1> | V | 200

E1-06 | Hz | 50.0

E1-07 | Hz | 2.5

E1-08 <1> | V | 16.0

E1-09 | Hz | 1.3

E1-10 <1> | V | 12.0

E1-08 <1> | V | 14.0

E1-10 <1> | V | 7.0

Table B.3 V/f default patterns models BA0001–BA0010;2A0001–2A0010;4A0001–4A0005 — PDF page 408

Source row Parameter Unit V/f E1-03=0 V/f E1-03=1 V/f E1-03=2 V/f E1-03=3 V/f E1-03=4 V/f E1-03=5 V/f E1-03=6 V/f E1-03=7 V/f E1-03=8 V/f E1-03=9 V/f E1-03=A V/f E1-03=B V/f E1-03=C V/f E1-03=D V/f E1-03=E V/f E1-03=F OLV
1 E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120 180 60.0 60.0
2 E1-05 <1> V 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 230 230
3 E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0
4 E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0
5 E1-08 <1> V 16.0 16.0 16.0 16.0 35.0 50.0 35.0 50.0 19.0 24.0 19.0 24.0 16.0 16.0 16.0 18.4 13.8
6 E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5 0.5
7 E1-10 <1> V 12.0 12.0 12.0 12.0 8.0 9.0 8.0 9.0 12.0 13.0 12.0 15.0 12.0 12.0 12.0 13.8 2.9

Table B.4 V/f default patterns models BA0012–BA0018;2A0012–2A0069;4A0007–4A0038 — PDF page 408

Source row Parameter Unit V/f E1-03=0 V/f E1-03=1 V/f E1-03=2 V/f E1-03=3 V/f E1-03=4 V/f E1-03=5 V/f E1-03=6 V/f E1-03=7 V/f E1-03=8 V/f E1-03=9 V/f E1-03=A V/f E1-03=B V/f E1-03=C V/f E1-03=D V/f E1-03=E V/f E1-03=F OLV
1 E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120 180 60.0 60.0
2 E1-05 <1> V 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 230 230
3 E1-06 Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0
4 E1-07 Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0
5 E1-08 <1> V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0 16.1 12.7
6 E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5 0.5
7 E1-10 <1> V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 7.0 2.3

Manual — Single-phase 200V small-model defaults — page 409

Source reference: SIEP C71060618F, December 2016, physical PDF page 409. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

Table B.5 Single-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Settings

No. Description Unit Default Settings

B

Parameter List

− | Model | −

o2-04 | Drive Model Selection | Hex

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor code | hex

L2-02 | Momentary power loss ride-through time | s

L2-03 | Mom. power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier freq. reduction sel. | −

n1-03 | Hunting Prev. Time Const. | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults single-phase 200V PDF409 — PDF page 409

Source row Parameter Description Unit BA0001 / HD (C6-01=0) BA0001 / ND (C6-01=1) BA0002 / HD (C6-01=0) BA0002 / ND (C6-01=1) BA0003 / HD (C6-01=0) BA0003 / ND (C6-01=1)
1 − Model − BA0001 BA0001 BA0002 BA0002 BA0003 BA0003
2 o2-04 Drive Model Selection Hex 30 30 31 31 32 32
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1
5 E2-11 (E4-11, T1-02) Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75
6 b3-06 Speed Search current 1 − 1 1 1 1 1 1
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 481.7 356.9 356.9 288.2 288.2 223.7
9 C6-02 Carrier frequency − 4 7 4 7 4 7
10 E2-01 (E4-01, T1-04) Motor rated current A 0.6 1.1 1.1 1.9 1.9 3.3
11 E2-02 (E4-02) Motor rated slip Hz 2.5 2.6 2.6 2.9 2.9 2.5
12 E2-03 (E4-03) Motor no-load current A 0.4 0.8 0.8 1.2 1.2 1.8
13 E2-05 (E4-05) Motor line-to-line resistance Ω 35.98 20.56 20.56 9.84 9.842 5.156
14 E2-06 (E4-06) Motor leakage inductance % 21.6 20.1 20.1 18.2 18.2 13.8
15 E2-10 (E4-10) Motor Iron Loss W 6 11 11 14 14 26
16 E5-01 Motor code hex FFFF FFFF FFFF FFFF 0002 0002
17 L2-02 Momentary power loss ride-through time s 0.1 0.1 0.1 0.1 0.1 0.1
18 L2-03 Mom. power loss Baseblock time s 0.2 0.2 0.2 0.2 0.2 0.3
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3
20 L2-05 Uv detection voltage V dc 160 160 160 160 160 160
21 L3-24 Motor acceleration time s 0.178 0.178 0.178 0.178 0.178 0.142
22 L8-02 Overheat alarm level °C 115 115 115 115 110 110
23 L8-09 Ground fault selection − 0 0 0 0 0 0
24 L8-38 Carrier freq. reduction sel. − 1 1 1 1 1 1
25 n1-03 Hunting Prev. Time Const. ms 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.00 1.00 1.00 1.00 1.00 1.00

Manual — Single-phase 200V large-model defaults and HD-only model — page 410

Source reference: SIEP C71060618F, December 2016, physical PDF page 410. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Description Unit Default Settings

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

− | Model | −

o2-04 | Drive Model Selection | Hex

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor Code | hex

L2-02 | Momentary power loss ride-through time | s

L2-03 | Momentary power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier frequency reduction selection | −

n1-03 | Hunting Prevention Time Constant | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults single-phase 200V PDF410 — PDF page 410

Source row Parameter Description Unit BA0006 / HD (C6-01=0) BA0006 / ND (C6-01=1) BA0010 / HD (C6-01=0) BA0010 / ND (C6-01=1) BA0012 / HD (C6-01=0) BA0012 / ND (C6-01=1) BA0018 / HD (C6-01=0)
1 − Model − BA0006 BA0006 BA0010 BA0010 BA0012 BA0012 BA0018
2 o2-04 Drive Model Selection Hex 33 33 34 34 35 35 37
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND HD
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1 0
5 E2-11 (E4-11, T1-02) Motor rated power kW 0.75 1.1 1.5 2.2 2.2 3.0 3.7
6 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5 0.5
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 223.7 169.4 169.4 156.8 156.8 136.4 122.9
9 C6-02 Carrier frequency − 4 7 3 7 3 7 3
10 E2-01 (E4-01, T1-04) Motor rated current A 3.3 6.2 6.2 8.5 8.5 11.4 14.0
11 E2-02 (E4-02) Motor rated slip Hz 2.5 2.6 2.6 2.9 2.9 2.7 2.73
12 E2-03 (E4-03) Motor no-load current A 1.8 2.8 2.8 3 3 3.7 4.5
13 E2-05 (E4-05) Motor line-to-line resistance Ω 5.156 1.997 1.997 1.601 1.601 1.034 0.771
14 E2-06 (E4-06) Motor leakage inductance % 13.8 18.5 18.5 18.4 18.4 19 19.6
15 E2-10 (E4-10) Motor Iron Loss W 26 53 53 77 77 91 112
16 E5-01 Motor Code hex 0003 0003 0005 0005 0006 0006 0008
17 L2-02 Momentary power loss ride-through time s 0.2 0.2 0.3 0.3 0.5 0.5 1.0
18 L2-03 Momentary power loss Baseblock time s 0.3 0.4 0.4 0.5 0.5 0.5 0.6
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3
20 L2-05 Uv detection voltage V dc 160 160 160 160 160 160 160
21 L3-24 Motor acceleration time s 0.142 0.142 0.166 0.145 0.145 0.145 0.154
22 L8-02 Overheat alarm level °C 105 105 100 100 95 95 100
23 L8-09 Ground fault selection − 0 0 0 0 0 0 0
24 L8-38 Carrier frequency reduction selection − 1 1 1 1 1 1 1
25 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.00 1.00 1.00 1.00 1.00 1.00 1.50

Manual — Three-phase 200V small-model defaults — page 411

Source reference: SIEP C71060618F, December 2016, physical PDF page 411. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table B.6 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Setting

No. Description Unit Default Settings

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

B

Parameter List

− | Model | −

o2-04 | Drive Model Selection | Hex

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor Code | hex

L2-02 | Momentary power loss ride-through time | s

L2-03 | Momentary power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier frequency reduction selection | −

n1-03 | Hunting Prevention Time Constant | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults three-phase 200V PDF411 — PDF page 411

Source row Parameter Description Unit 2A0001 / HD (C6-01=0) 2A0001 / ND (C6-01=1) 2A0002 / HD (C6-01=0) 2A0002 / ND (C6-01=1) 2A0004 / HD (C6-01=0) 2A0004 / ND (C6-01=1) 2A0006 / HD (C6-01=0) 2A0006 / ND (C6-01=1) 2A0010 / HD (C6-01=0) 2A0010 / ND (C6-01=1)
1 − Model − 2A0001 2A0001 2A0002 2A0002 2A0004 2A0004 2A0006 2A0006 2A0010 2A0010
2 o2-04 Drive Model Selection Hex 60 60 61 61 62 62 63 63 65 65
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND HD ND HD ND
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1 0 1 0 1
5 E2-11 (E4-11, T1-02) Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75 0.75 1.1 1.5 2.2
6 b3-06 Speed Search current 1 − 1.0 1.0 1.0 1.0 1.0 1.0 0.5 0.5 0.5 0.5
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 481.7 356.9 356.9 288.2 288.2 223.7 223.7 196.6 169.4 156.8
9 C6-02 Carrier frequency − 4 7 4 7 4 7 4 7 3 7
10 E2-01 (E4-01, T1-04) Motor rated current A 0.6 1.1 1.1 1.9 1.9 3.3 3.3 4.9 6.2 8.5
11 E2-02 (E4-02) Motor rated slip Hz 2.5 2.6 2.6 2.9 2.9 2.5 2.5 2.6 2.6 2.9
12 E2-03 (E4-03) Motor no-load current A 0.4 0.8 0.8 1.2 1.2 1.8 1.8 2.3 2.8 3.0
13 E2-05 (E4-05) Motor line-to-line resistance Ω 35.98 20.56 20.56 9.84 9.842 5.156 5.156 3.577 1.997 1.601
14 E2-06 (E4-06) Motor leakage inductance % 21.6 20.1 20.1 18.2 18.2 13.8 13.8 18.5 18.5 18.4
15 E2-10 (E4-10) Motor Iron Loss W 6 11 11 14 14 26 26 38 53 77
16 E5-01 Motor Code hex FFFF FFFF FFFF FFFF 0002 0002 0003 0003 0005 0005
17 L2-02 Momentary power loss ride-through time s 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3
18 L2-03 Momentary power loss Baseblock time s 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.5
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
20 L2-05 Uv detection voltage V dc 190 190 190 190 190 190 190 190 190 190
21 L3-24 Motor acceleration time s 0.178 0.178 0.178 0.178 0.178 0.142 0.142 0.142 0.166 0.145
22 L8-02 Overheat alarm level °C 110 110 110 110 115 115 100 100 100 100
23 L8-09 Ground fault selection − 0 0 0 0 0 0 0 0 0 0
24 L8-38 Carrier frequency reduction selection − 1 1 1 1 1 1 1 1 1 1
25 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00

Manual — Three-phase 200V middle-model defaults — page 412

Source reference: SIEP C71060618F, December 2016, physical PDF page 412. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Description Unit Default Settings

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

− | Model | −

o2-04 | Drive Model Selection | Hex

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor Code | hex

L2-02 | Momentary power loss ride- through time | s

L2-03 | Momentary power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier frequency reduction selection | −

n1-03 | Hunting Prevention Time Constant | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults three-phase 200V PDF412 — PDF page 412

Source row Parameter Description Unit 2A0012 / HD (C6-01=0) 2A0012 / ND (C6-01=1) 2A0020 / HD (C6-01=0) 2A0020 / ND (C6-01=1) 2A0030 / HD (C6-01=0) 2A0030 / ND (C6-01=1)
1 − Model − 2A0012 2A0012 2A0020 2A0020 2A0030 2A0030
2 o2-04 Drive Model Selection Hex 66 66 68 68 6A 6A
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1
5 E2-11 (E4-11, T1-02) Motor rated power kW 2.2 3.0 3.7 5.5 5.5 7.5
6 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 156.8 136.4 122.9 94.8 94.75 72.69
9 C6-02 Carrier frequency − 3 7 3 7 3 7
10 E2-01 (E4-01, T1-04) Motor rated current A 8.5 11.4 14 19.6 19.6 26.6
11 E2-02 (E4-02) Motor rated slip Hz 2.9 2.7 2.73 1.5 1.5 1.3
12 E2-03 (E4-03) Motor no-load current A 3.0 3.7 4.5 5.1 5.1 8.0
13 E2-05 (E4-05) Motor line-to-line resistance Ω 1.601 1.034 0.771 0.399 0.399 0.288
14 E2-06 (E4-06) Motor leakage inductance % 18.4 19 19.6 18.2 18.2 15.5
15 E2-10 (E4-10) Motor Iron Loss W 77 91 112 172 172 262
16 E5-01 Motor Code hex 0006 0006 0008 0008 FFFF FFFF
17 L2-02 Momentary power loss ride- through time s 0.5 0.5 1 1 1.0 1.0
18 L2-03 Momentary power loss Baseblock time s 0.5 0.5 0.6 0.7 0.7 0.8
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.6 0.3 0.6
20 L2-05 Uv detection voltage V dc 190 190 190 190 190 190
21 L3-24 Motor acceleration time s 0.145 0.145 0.154 0.168 0.168 0.175
22 L8-02 Overheat alarm level °C 100 100 110 110 115 115
23 L8-09 Ground fault selection − 0 0 0 0 1 1
24 L8-38 Carrier frequency reduction selection − 1 1 1 1 2 2
25 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.00 1.00 1.00 1.00 1.50 1.50

Manual — Three-phase 200V large-model defaults — page 413

Source reference: SIEP C71060618F, December 2016, physical PDF page 413. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Description Unit Default Settings

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

B

Parameter List

− | Model | −

o2-04 | Drive Model Selection | Hex

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor Code | hex

L2-02 | Momentary power loss ride-through time | s

L2-03 | Momentary power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier frequency reduction selection | −

n1-03 | Hunting Prevention Time Constant | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults three-phase 200V PDF413 — PDF page 413

Source row Parameter Description Unit 2A0040 / HD (C6-01=0) 2A0040 / ND (C6-01=1) 2A0056 / HD (C6-01=0) 2A0056 / ND (C6-01=1) 2A0069 / HD (C6-01=0) 2A0069 / ND (C6-01=1)
1 − Model − 2A0040 2A0040 2A0056 2A0056 2A0069 2A0069
2 o2-04 Drive Model Selection Hex 6B 6B 6D 6D 6E 6E
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1
5 E2-11 (E4-11, T1-02) Motor rated power kW 7.5 11.0 11.0 15.0 15.0 18.5
6 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 72.69 70.44 70.44 63.13 63.13 57.87
9 C6-02 Carrier frequency − 3 7 3 7 3 7
10 E2-01 (E4-01, T1-04) Motor rated current A 26.6 39.7 39.7 53 53 65.8
11 E2-02 (E4-02) Motor rated slip Hz 1.3 1.7 1.7 1.6 1.6 1.67
12 E2-03 (E4-03) Motor no-load current A 8.0 11.2 11.2 15.2 15.2 15.7
13 E2-05 (E4-05) Motor line-to-line resistance Ω 0.288 0.230 0.230 0.138 0.138 0.101
14 E2-06 (E4-06) Motor leakage inductance % 15.5 19.5 19.5 17.2 17.2 15.7
15 E2-10 (E4-10) Motor Iron Loss W 262 245 245 272 272 505
16 E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF
17 L2-02 Momentary power loss ride-through time s 1.0 1.0 2.0 2.0 2.0 2.0
18 L2-03 Momentary power loss Baseblock time s 0.8 0.9 0.9 1.0 1.0 1.0
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.6 0.6
20 L2-05 Uv detection voltage V dc 190 190 190 190 190 190
21 L3-24 Motor acceleration time s 0.175 0.265 0.265 0.244 0.244 0.317
22 L8-02 Overheat alarm level °C 121 121 120 120 120 120
23 L8-09 Ground fault selection − 1 1 1 1 1 1
24 L8-38 Carrier frequency reduction selection − 2 2 2 2 2 2
25 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.50 1.50 1.50 1.50 1.50 1.50

Manual — Three-phase 400V small-model defaults — page 414

Source reference: SIEP C71060618F, December 2016, physical PDF page 414. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table B.7 Three-Phase 400 V Class Drives Default Settings by Drive Capacity and ND/HD Setting

No. Description Unit Default Settings

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

− | Model | −

o2-04 | Drive Model Selection | Hex

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor Code | hex

L2-02 | Momentary power loss ride-through time | s

L2-03 | Momentary power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier frequency reduction selection | −

n1-03 | Hunting Prevention Time Constant | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults three-phase 400V PDF414 — PDF page 414

Source row Parameter Description Unit 4A0001 / HD (C6-01=0) 4A0001 / ND (C6-01=1) 4A0002 / HD (C6-01=0) 4A0002 / ND (C6-01=1) 4A0004 / HD (C6-01=0) 4A0004 / ND (C6-01=1) 4A0005 / HD (C6-01=0) 4A0005 / ND (C6-01=1)
1 − Model − 4A0001 4A0001 4A0002 4A0002 4A0004 4A0004 4A0005 4A0005
2 o2-04 Drive Model Selection Hex 91 91 92 92 93 93 94 94
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND HD ND
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1 0 1
5 E2-11 (E4-11, T1-02) Motor rated power kW 0.2 0.4 0.4 0.75 0.75 1.5 1.5 2.2
6 b3-06 Speed Search current 1 − 1.0 1.0 0.5 0.5 0.5 0.5 0.5 0.5
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 713.8 576.4 576.4 447.4 447.4 338.8 338.8 313.6
9 C6-02 Carrier frequency − 3 7 3 7 3 7 3 7
10 E2-01 (E4-01, T1-04) Motor rated current A 0.6 1 1 1.6 1.6 3.1 3.1 4.2
11 E2-02 (E4-02) Motor rated slip Hz 2.5 2.9 2.9 2.6 2.6 2.5 2.5 3
12 E2-03 (E4-03) Motor no-load current A 0.4 0.6 0.6 0.8 0.8 1.4 1.4 1.5
13 E2-05 (E4-05) Motor line-to-line resistance Ω 83.94 38.20 38.198 22.459 22.459 10.1 10.1 6.495
14 E2-06 (E4-06) Motor leakage inductance % 21.9 18.2 18.2 14.3 14.3 18.3 18.3 18.7
15 E2-10 (E4-10) Motor Iron Loss W 12 14 14 26 26 53 53 77
16 E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
17 L2-02 Momentary power loss ride-through time s 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3
18 L2-03 Momentary power loss Baseblock time s 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.5
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
20 L2-05 Uv detection voltage V dc 380 380 380 380 380 380 380 380
21 L3-24 Motor acceleration time s 0.178 0.178 0.178 0.142 0.142 0.166 0.166 0.145
22 L8-02 Overheat alarm level °C 110 110 110 110 110 110 90 90
23 L8-09 Ground fault selection − 0 0 0 0 0 0 0 0
24 L8-38 Carrier frequency reduction selection − 1 1 1 1 1 1 1 1
25 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00

Manual — Three-phase 400V middle-model defaults — page 415

Source reference: SIEP C71060618F, December 2016, physical PDF page 415. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Description Unit Setting Range

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

B

Parameter List

− | Model | −

o2-04 | Drive Model Selection | −

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor Code | hex

L2-02 | Momentary power loss ride-through time | s

L2-03 | Momentary power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier frequency reduction selection | −

n1-03 | Hunting Prevention Time Constant | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults three-phase 400V PDF415 — PDF page 415

Source row Parameter Description Unit 4A0007 / HD (C6-01=0) 4A0007 / ND (C6-01=1) 4A0009 / HD (C6-01=0) 4A0009 / ND (C6-01=1) 4A0011 / HD (C6-01=0) 4A0011 / ND (C6-01=1) 4A0018 / HD (C6-01=0) 4A0018 / ND (C6-01=1)
1 − Model − 4A0007 4A0007 4A0009 4A0009 4A0011 4A0011 4A0018 4A0018
2 o2-04 Drive Model Selection − 95 95 96 96 97 97 99 99
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND HD ND
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1 0 1
5 E2-11 (E4-11, T1-02) Motor rated power kW 2.2 3.0 3.0 3.7 4.0 5.5 5.5 7.5
6 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 313.6 265.7 265.7 245.8 245.8 189.5 189.5 145.38
9 C6-02 Carrier frequency − 3 7 3 7 3 7 3 7
10 E2-01 (E4-01, T1-04) Motor rated current A 4.2 5.7 5.7 7 7 9.8 9.8 13.30
11 E2-02 (E4-02) Motor rated slip Hz 3 2.7 2.7 2.7 2.7 1.5 1.5 1.3
12 E2-03 (E4-03) Motor no-load current A 1.5 1.9 1.9 2.3 2.3 2.6 2.6 4.0
13 E2-05 (E4-05) Motor line-to-line resistance Ω 6.495 4.360 4.360 3.333 3.333 1.595 1.595 1.152
14 E2-06 (E4-06) Motor leakage inductance % 18.7 19 19 19.3 19.3 18.2 18.2 15.5
15 E2-10 (E4-10) Motor Iron Loss W 77 105 105 130 130 193 193 263
16 E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
17 L2-02 Momentary power loss ride-through time s 0.5 0.5 0.5 0.5 0.5 0.5 0.8 0.8
18 L2-03 Momentary power loss Baseblock time s 0.5 0.5 0.5 0.6 0.6 0.7 0.7 0.8
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
20 L2-05 Uv detection voltage V dc 380 380 380 380 380 380 380 380
21 L3-24 Motor acceleration time s 0.145 0.145 0.145 0.154 0.154 0.154 0.168 0.175
22 L8-02 Overheat alarm level °C 100 100 100 100 100 100 110 110
23 L8-09 Ground fault selection − 0 0 0 0 0 0 1 1
24 L8-38 Carrier frequency reduction selection − 1 1 1 1 1 1 2 2
25 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.00 1.00 1.00 1.00 1.00 1.00 1.50 1.50

Manual — Three-phase 400V large-model defaults — page 416

Source reference: SIEP C71060618F, December 2016, physical PDF page 416. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

No. Description Unit Setting Range

B.5 Defaults by Drive Model and Duty Rating (ND/HD)

− | Model | −

o2-04 | Drive Model Selection | −

C6-01 | Normal/Heavy Duty | −

E2-11 (E4-11, T1-02) | Motor rated power | kW

b3-06 | Speed Search current 1 | −

b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –

b8-04 | Energy saving coefficient | −

C6-02 | Carrier frequency | −

E2-01 (E4-01, T1-04) | Motor rated current | A

E2-02 (E4-02) | Motor rated slip | Hz

E2-03 (E4-03) | Motor no-load current | A

E2-05 (E4-05) | Motor line-to-line resistance | Ω

E2-06 (E4-06) | Motor leakage inductance | %

E2-10 (E4-10) | Motor Iron Loss | W

E5-01 | Motor Code | hex

L2-02 | Momentary power loss ride-through time | s

L2-03 | Momentary power loss Baseblock time | s

L2-04 | Momentary power loss voltage recovery time | s

L2-05 | Uv detection voltage | V dc

L3-24 | Motor acceleration time | s

L8-02 | Overheat alarm level | °C

L8-09 | Ground fault selection | −

L8-38 | Carrier frequency reduction selection | −

n1-03 | Hunting Prevention Time Constant | ms

n2-01 | Speed Feedback Detection Control (AFR) Gain | –

Drive-model/duty-dependent defaults three-phase 400V PDF416 — PDF page 416

Source row Parameter Description Unit 4A0023 / HD (C6-01=0) 4A0023 / ND (C6-01=1) 4A0031 / HD (C6-01=0) 4A0031 / ND (C6-01=1) 4A0038 / HD (C6-01=0) 4A0038 / ND (C6-01=1)
1 − Model − 4A0023 4A0023 4A0031 4A0031 4A0038 4A0038
2 o2-04 Drive Model Selection − 9A 9A 9C 9C 9D 9D
3 C6-01 Normal/Heavy Duty − HD ND HD ND HD ND
4 C6-01 Normal/Heavy Duty − 0 1 0 1 0 1
5 E2-11 (E4-11, T1-02) Motor rated power kW 7.5 11.0 11.0 15.0 15.0 18.5
6 b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5
7 b3-08 Current Control Gain during Speed Search (Speed Estimation Type) – 0.5 0.5 0.5 0.5 0.5 0.5
8 b8-04 Energy saving coefficient − 145.38 140.88 140.88 126.26 126.26 115.74
9 C6-02 Carrier frequency − 3 7 3 7 3 7
10 E2-01 (E4-01, T1-04) Motor rated current A 13.3 19.9 19.9 26.5 26.5 32.9
11 E2-02 (E4-02) Motor rated slip Hz 1.30 1.70 1.70 1.60 1.60 1.67
12 E2-03 (E4-03) Motor no-load current A 4.0 5.6 5.6 7.6 7.6 7.8
13 E2-05 (E4-05) Motor line-to-line resistance Ω 1.152 0.922 0.922 0.550 0.550 0.403
14 E2-06 (E4-06) Motor leakage inductance % 15.5 19.6 19.6 17.2 17.2 20.1
15 E2-10 (E4-10) Motor Iron Loss W 263 385 385 440 440 508
16 E5-01 Motor Code hex FFFF FFFF FFFF FFFF FFFF FFFF
17 L2-02 Momentary power loss ride-through time s 1 1 2 2 2 2
18 L2-03 Momentary power loss Baseblock time s 0.8 0.9 0.9 1.0 1.0 1.0
19 L2-04 Momentary power loss voltage recovery time s 0.3 0.3 0.3 0.6 0.6 0.6
20 L2-05 Uv detection voltage V dc 380 380 380 380 380 380
21 L3-24 Motor acceleration time s 0.175 0.265 0.265 0.244 0.244 0.317
22 L8-02 Overheat alarm level °C 110 110 110 110 110 110
23 L8-09 Ground fault selection − 1 1 1 1 1 1
24 L8-38 Carrier frequency reduction selection − 2 2 2 2 2 2
25 n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
26 n2-01 Speed Feedback Detection Control (AFR) Gain – 1.50 1.50 1.50 1.50 1.50 1.50

Manual — SMRA SPM motor-code defaults at 1800 and 3600 r/min — page 417

Source reference: SIEP C71060618F, December 2016, physical PDF page 417. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

B.6 Parameters that Change with the Motor Code Selection

The following tables show parameters and default settings that change with the motor code selection E5-01 when Open Loop Vector for PM motors is used.

◆ Yaskawa SMRA Series SPM Motor

Table B.8 1800 rpm Type Yaskawa SMRA Series SPM Motor Settings

Par. Description Unit Default Settings

Table B.9 3600 rpm Type Yaskawa SMRA Series SPM Motor Settings

B

Parameter List

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Motor-code defaults SMRA SPM;200 Vac;1800r/min;not specified in table — PDF page 417

Source row Parameter Description Unit E5-01 motor code 0002 E5-01 motor code 0003 E5-01 motor code 0005 E5-01 motor code 0006 E5-01 motor code 0008
1 E5-01 Motor Code − 0002 0003 0005 0006 0008
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW
4 E5-01 Rated Speed r/min 1800 1800 1800 1800 1800
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7
6 E5-03 Motor Rated Current A 2.1 4.0 6.9 10.8 17.4
7 E5-04 Motor Pole Number – 8 8 8 8 8
8 E5-05 Motor Winding Resistance Ω 2.47 1.02 0.679 0.291 0.169
9 E5-06 d-Axis Inductance mH 12.7 4.8 3.9 3.6 2.5
10 E5-07 q-Axis Inductance mH 12.7 4.8 3.9 3.6 2.5
11 E5-09 Induction Voltage Constant 1 mVs/rad 0 0 0 0 0
12 E5-24 Induction Voltage Constant 2 mV/(r/min) 62.0 64.1 73.4 69.6 72.2
13 E1-04 Maximum Output Frequency Hz 120 120 120 120 120
14 E1-05 Maximum Output Voltage V 200.0 200.0 200.0 200.0 200.0
15 E1-06 Base Frequency Hz 120 120 120 120 120
16 E1-09 Minimum Output Frequency Hz 6 6 6 6 6
17 L3-24 Motor Acceleration Time for Inertia Calculations s 0.064 0.066 0.049 0.051 0.044
18 n8-49 d-Axis Current for High-Efficiency Control % 0 0 0 0 0

Motor-code defaults SMRA SPM;200 Vac;3600r/min;not specified in table — PDF page 417

Source row Parameter Description Unit E5-01 motor code 0103 E5-01 motor code 0105 E5-01 motor code 0106 E5-01 motor code 0108
1 E5-01 Motor Code − 0103 0105 0106 0108
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.75 kW 1.5 kW 2.2 kW 3.7 kW
4 E5-01 Rated Speed r/min 3600 3600 3600 3600
5 E5-02 Motor Rated Power kW 0.75 1.5 2.2 3.7
6 E5-03 Motor Rated Current A 4.1 8.0 10.5 16.5
7 E5-04 Motor Pole Number – 8 8 8 8
8 E5-05 Motor Winding Resistance Ω 0.538 0.20 0.15 0.097
9 E5-06 d-Axis Inductance mH 3.2 1.3 1.1 1.1
10 E5-07 q-Axis Inductance mH 3.2 1.3 1.1 1.1
11 E5-09 Induction Voltage Constant 1 mVs/rad 0 0 0 0
12 E5-24 Induction Voltage Constant 2 mV/(r/min) 32.4 32.7 36.7 39.7
13 E1-04 Maximum Output Frequency Hz 240 240 240 240
14 E1-05 Maximum Output Voltage V 200.0 200.0 200.0 200.0
15 E1-06 Base Frequency Hz 240 240 240 240
16 E1-09 Minimum Output Frequency Hz 12 12 12 12
17 L3-24 Motor Acceleration Time for Inertia Calculations s 0.137 0.132 0.132 0.122
18 n8-49 d-Axis Current for High-Efficiency Control % 0 0 0 0

Manual — SSR1 200V 1750 r/min PRG1017 and earlier — page 418

Source reference: SIEP C71060618F, December 2016, physical PDF page 418. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ SS5 Motor: Yaskawa SSR1 Series IPM Motor

Default values vary based on drive software version.

■ Drive Software Version PRG: 1017 and Earlier

Table B.10 200 V, 1750 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High- Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;200 Vac;1750r/min;PRG1017 and earlier — PDF page 418

Source row Parameter Description Unit E5-01 motor code 1202 E5-01 motor code 1203 E5-01 motor code 1205 E5-01 motor code 1206 E5-01 motor code 1208 E5-01 motor code 120A E5-01 motor code 120B E5-01 motor code 120D E5-01 motor code 120E E5-01 motor code 120F
1 E5-01 Motor Code − 1202 1203 1205 1206 1208 120A 120B 120D 120E 120F
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.0
6 E5-03 Motor Rated Current A 1.65 2.97 5.50 8.10 13.40 19.80 27.00 39.7 53.2 65.5
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 8.233 2.284 1.501 0.827 0.455 0.246 0.198 0.094 0.066 0.052
9 E5-06 d-Axis Inductance mH 54.84 23.02 17.08 8.61 7.20 4.86 4.15 3.40 2.65 2.17
10 E5-07 q-Axis Inductance mH 64.10 29.89 21.39 13.50 10.02 7.43 5.91 3.91 3.11 2.55
11 E5-09 Induction Voltage Constant 1 mVs/rad 233.0 229.5 250.9 247.9 248.6 249.6 269.0 249.3 266.6 265.1
12 E5-24 Induction Voltage Constant 2 mV/(r/min) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
13 E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
14 E1-05 Maximum Output Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
15 E1-06 Base Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
16 E1-09 Minimum Output Frequency Hz 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.092 0.076 0.051 0.066 0.075 0.083 0.077 0.084 0.102 0.103
18 n8-49 d-Axis Current for High- Efficiency Control % –7.2 –10.8 –11.1 –17.8 –17.5 –22.0 –17.3 –10.1 –10.3 –10.1

Manual — SSR1 200V 1750 r/min PRG1018 and later — page 419

Source reference: SIEP C71060618F, December 2016, physical PDF page 419. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1018 and Later

Table B.11 200 V, 1750 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

B

Parameter List

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High- Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;200 Vac;1750r/min;PRG1018 and later — PDF page 419

Source row Parameter Description Unit E5-01 motor code 1202 E5-01 motor code 1203 E5-01 motor code 1205 E5-01 motor code 1206 E5-01 motor code 1208 E5-01 motor code 120A E5-01 motor code 120B E5-01 motor code 120D E5-01 motor code 120E E5-01 motor code 120F
1 E5-01 Motor Code − 1202 1203 1205 1206 1208 120A 120B 120D 120E 120F
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
6 E5-03 Motor Rated Current A 1.77 3.13 5.73 8.44 13.96 20.63 28.13 41.4 55.4 68.2
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 8.233 2.284 1.470 0.827 0.455 0.246 0.198 0.094 0.066 0.051
9 E5-06 d-Axis Inductance mH 54.84 23.02 17.22 8.61 7.2 4.86 4.15 3.4 2.45 2.18
10 E5-07 q-Axis Inductance mH 64.1 29.89 20.41 13.5 10.02 7.43 5.91 3.91 3.11 2.55
11 E5-09 Induction Voltage Constant 1 mVs/rad 223.7 220.3 240.8 238 238.7 239.6 258.2 239.3 248.1 253.6
12 E5-24 Induction Voltage Constant 2 mV/(r/min) 0 0 0 0 0 0 0 0 0 0
13 E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
14 E1-05 Maximum Output Voltage V 190 190 190 190 190 190 190 190 190 190
15 E1-06 Base Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
16 E1-09 Minimum Output Frequency Hz 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.092 0.076 0.051 0.066 0.075 0.083 0.077 0.084 0.102 0.101
18 n8-49 d-Axis Current for High- Efficiency Control % –7.6 –11.5 –9.1 –19 –18.7 –23.4 –18.5 –10.9 –16.5 –11.3

Manual — SSR1 400V 1750 r/min PRG1017 and earlier — page 420

Source reference: SIEP C71060618F, December 2016, physical PDF page 420. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1017 and Earlier

Table B.12 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;400 Vac;1750r/min;PRG1017 and earlier — PDF page 420

Source row Parameter Description Unit E5-01 motor code 1232 E5-01 motor code 1233 E5-01 motor code 1235 E5-01 motor code 1236 E5-01 motor code 1238 E5-01 motor code 123A E5-01 motor code 123B E5-01 motor code 123D E5-01 motor code 123E E5-01 motor code 123F
1 E5-01 Motor Code − 1232 1233 1235 1236 1238 123A 123B 123D 123E 123F
2 E5-01 Voltage Class − 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.0
6 E5-03 Motor Rated Current A 0.83 1.49 2.75 4.05 6.80 9.90 13.10 19.9 26.4 32.1
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 32.932 9.136 6.004 3.297 1.798 0.982 0.786 0.368 0.263 0.202
9 E5-06 d-Axis Inductance mH 219.36 92.08 68.32 40.39 32.93 22.7 16.49 13.38 10.51 8.56
10 E5-07 q-Axis Inductance mH 256.40 119.56 85.56 48.82 37.70 26.80 23.46 16.99 12.77 11.22
11 E5-09 Induction Voltage Constant 1 mVs/rad 466.0 459.0 501.8 485.7 498.7 498.0 541.7 508.7 531.9 536.4
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
13 E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
14 E1-05 Maximum Output Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
15 E1-06 Base Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
16 E1-09 Minimum Output Frequency Hz 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.092 0.076 0.051 0.066 0.075 0.083 0.077 0.084 0.102 0.103
18 n8-49 d-Axis Current for High-Efficiency Control % –7.2 –10.7 –11.1 –8.9 –7.9 –10.2 –17.4 –15.8 –12.6 –16.3

Manual — SSR1 400V 1750 r/min PRG1018 and later — page 421

Source reference: SIEP C71060618F, December 2016, physical PDF page 421. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1018 and Later

Table B.13 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

B

Parameter List

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;400 Vac;1750r/min;PRG1018 and later — PDF page 421

Source row Parameter Description Unit E5-01 motor code 1232 E5-01 motor code 1233 E5-01 motor code 1235 E5-01 motor code 1236 E5-01 motor code 1238 E5-01 motor code 123A E5-01 motor code 123B E5-01 motor code 123D E5-01 motor code 123E E5-01 motor code 123F
1 E5-01 Motor Code − 1232 1233 1235 1236 1238 123A 123B 123D 123E 123F
2 E5-01 Voltage Class − 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
6 E5-03 Motor Rated Current A 0.89 1.56 2.81 4.27 7.08 10.31 13.65 20.7 27.5 33.4
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 25.370 9.136 6.010 3.297 1.798 0.982 0.786 0.349 0.272 0.207
9 E5-06 d-Axis Inductance mH 169.00 92.08 67.71 34.40 32.93 22.7 16.49 13.17 10.30 8.72
10 E5-07 q-Axis Inductance mH 197.5 119.56 81.71 54.00 37.7 26.8 23.46 15.60 12.77 11.22
11 E5-09 Induction Voltage Constant 1 mVs/rad 392.6 440.6 478.3 466.3 478.8 478.1 520.0 481.5 498.8 509.5
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0 0 0 0 0 0 0 0 0 0
13 E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
14 E1-05 Maximum Output Voltage V 380 380 380 380 380 380 380 380 380 380
15 E1-06 Base Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
16 E1-09 Minimum Output Frequency Hz 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.092 0.076 0.051 0.066 0.075 0.083 0.077 0.084 0.102 0.101
18 n8-49 d-Axis Current for High-Efficiency Control % –8.6 –11.5 –10.3 –19.8 –8.5 –11 –18.6 –12.5 –15.5 –17.9

Manual — SSR1 200V 1450 r/min PRG1017 and earlier — page 422

Source reference: SIEP C71060618F, December 2016, physical PDF page 422. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1017 and Earlier

Table B.14 200 V, 1450 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;200 Vac;1450r/min;PRG1017 and earlier — PDF page 422

Source row Parameter Description Unit E5-01 motor code 1302 E5-01 motor code 1303 E5-01 motor code 1305 E5-01 motor code 1306 E5-01 motor code 1308 E5-01 motor code 130A E5-01 motor code 130B E5-01 motor code 130D E5-01 motor code 130E E5-01 motor code 130F
1 E5-01 Motor Code − 1302 1303 1305 1306 1308 130A 130B 130D 130E 130F
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.0
6 E5-03 Motor Rated Current A 1.78 3.12 5.88 8.00 14.10 20.00 26.60 38.0 53.3 63.0
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 4.405 2.425 1.647 0.665 0.452 0.341 0.184 0.099 0.075 0.057
9 E5-06 d-Axis Inductance mH 26.62 19.14 14.53 12.27 7.10 5.90 6.91 4.07 3.29 2.53
10 E5-07 q-Axis Inductance mH 41.70 29.98 19.98 14.77 10.14 8.42 8.37 5.25 4.57 3.01
11 E5-09 Induction Voltage Constant 1 mVs/rad 262.6 276.3 291.0 299.1 294.3 306.6 325.1 316.6 332.2 313.4
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
13 E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
14 E1-05 Maximum Output Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
15 E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
16 E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096 0.085 0.082
18 n8-49 d-Axis Current for High-Efficiency Control % –10.8 –13.1 –12.1 –8.4 –16.0 –17.8 –12.8 –16.3 –19.1 –11.6

Manual — SSR1 200V 1450 r/min PRG1018 and later — page 423

Source reference: SIEP C71060618F, December 2016, physical PDF page 423. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1018 and Later

Table B.15 200 V, 1450 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

B

Parameter List

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;200 Vac;1450r/min;PRG1018 and later — PDF page 423

Source row Parameter Description Unit E5-01 motor code 1302 E5-01 motor code 1303 E5-01 motor code 1305 E5-01 motor code 1306 E5-01 motor code 1308 E5-01 motor code 130A E5-01 motor code 130B E5-01 motor code 130D E5-01 motor code 130E E5-01 motor code 130F
1 E5-01 Motor Code − 1302 1303 1305 1306 1308 130A 130B 130D 130E 130F
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
6 E5-03 Motor Rated Current A 1.88 3.13 5.63 8.33 14.17 20.63 27.71 39.6 55.5 65.6
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 3.190 1.940 1.206 0.665 0.341 0.252 0.184 0.099 0.075 0.057
9 E5-06 d-Axis Inductance mH 32.15 26.12 14.72 12.27 8.27 6.49 6.91 4.07 3.29 2.53
10 E5-07 q-Axis Inductance mH 41.74 34.3 20.15 14.77 9.81 7.74 7.66 4.65 3.84 3.01
11 E5-09 Induction Voltage Constant 1 mVs/rad 264.3 269.6 284.3 287.1 284.5 298.0 335.0 303.9 311.2 300.9
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0 0 0 0 0 0 0 0 0 0
13 E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
14 E1-05 Maximum Output Voltage V 190 190 190 190 190 190 190 190 190 190
15 E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
16 E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096 0.085 0.08
18 n8-49 d-Axis Current for High-Efficiency Control % –6.6 –10.9 –13.5 –9 –9.5 –10.1 –6 –9.3 –10.7 –13.2

Manual — SSR1 400V 1450 r/min PRG1017 and earlier — page 424

Source reference: SIEP C71060618F, December 2016, physical PDF page 424. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1017 and Earlier

Table B.16 400 V, 1450 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;400 Vac;1450r/min;PRG1017 and earlier — PDF page 424

Source row Parameter Description Unit E5-01 motor code 1332 E5-01 motor code 1333 E5-01 motor code 1335 E5-01 motor code 1336 E5-01 motor code 1338 E5-01 motor code 133A E5-01 motor code 133B E5-01 motor code 133D E5-01 motor code 133E E5-01 motor code 133F
1 E5-01 Motor Code − 1332 1333 1335 1336 1338 133A 133B 133D 133E 133F
2 E5-01 Voltage Class − 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.0
6 E5-03 Motor Rated Current A 0.89 1.50 2.70 4.10 6.70 9.80 13.30 18.7 26.3 31.5
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 17.620 7.421 4.825 2.656 1.353 0.999 0.713 0.396 0.295 0.223
9 E5-06 d-Axis Inductance mH 106.50 85.11 58.87 46.42 31.73 26.20 27.06 15.22 12.65 9.87
10 E5-07 q-Axis Inductance mH 166.80 113.19 80.59 60.32 40.45 30.94 33.45 19.63 15.87 12.40
11 E5-09 Induction Voltage Constant 1 mVs/rad 525.2 566.9 592.2 579.4 586.4 612.1 640.4 643.5 650.6 635.8
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
13 E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
14 E1-05 Maximum Output Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
15 E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
16 E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096 0.085 0.082
18 n8-49 d-Axis Current for High-Efficiency Control % –10.8 –8.5 –12.5 –12.2 –12.7 –9.4 –14.4 –15.0 –14.1 –14.3

Manual — SSR1 400V 1450 r/min PRG1018 and later — page 425

Source reference: SIEP C71060618F, December 2016, physical PDF page 425. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1018 and Later

Table B.17 400 V, 1450 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

B

Parameter List

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Motor-code defaults SS5 SSR1 IPM;400 Vac;1450r/min;PRG1018 and later — PDF page 425

Source row Parameter Description Unit E5-01 motor code 1332 E5-01 motor code 1333 E5-01 motor code 1335 E5-01 motor code 1336 E5-01 motor code 1338 E5-01 motor code 133A E5-01 motor code 133B E5-01 motor code 133D E5-01 motor code 133E E5-01 motor code 133F
1 E5-01 Motor Code − 1332 1333 1335 1336 1338 133A 133B 133D 133E 133F
2 E5-01 Voltage Class − 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
6 E5-03 Motor Rated Current A 0.94 1.56 2.81 4.27 6.98 10.21 13.85 19.5 27.4 32.9
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 12.76 7.421 4.825 2.656 1.353 0.999 0.713 0.393 0.295 0.223
9 E5-06 d-Axis Inductance mH 128.6 85.11 58.87 46.42 31.73 26.2 27.06 15.51 12.65 9.87
10 E5-07 q-Axis Inductance mH 166.96 113.19 80.59 60.32 40.45 30.94 33.45 19.63 15.87 12.4
11 E5-09 Induction Voltage Constant 1 mVs/rad 528.6 544.2 568.5 572.8 562.9 587.6 670.1 612.7 624.6 610.4
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0 0 0 0 0 0 0 0 0 0
13 E1-04 Maximum Output Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
14 E1-05 Maximum Output Voltage V 380 380 380 380 380 380 380 380 380 380
15 E1-06 Base Frequency Hz 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5 72.5
16 E1-09 Minimum Output Frequency Hz 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.098 0.071 0.066 0.087 0.085 0.072 0.084 0.096 0.085 0.08
18 n8-49 d-Axis Current for High-Efficiency Control % –6.6 –9.2 –13.5 –12.1 –13.7 –10.1 –12.2 –15.5 –15.1 –16

Manual — SSR1 200V 1150 r/min PRG1017 and earlier — page 426

Source reference: SIEP C71060618F, December 2016, physical PDF page 426. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1017 and Earlier

Table B.18 200 V, 1150 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Table B.18 SS5 SSR1 IPM;200Vac;1150r/min;PRG1017 and earlier — PDF page 426

Source row Parameter Description Unit E5-01 motor code 1402 E5-01 motor code 1403 E5-01 motor code 1405 E5-01 motor code 1406 E5-01 motor code 1408 E5-01 motor code 140A E5-01 motor code 140B E5-01 motor code 140D E5-01 motor code 140E E5-01 motor code 140F
1 E5-01 Motor Code − 1402 1403 1405 1406 1408 140A 140B 140D 140E 140F
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.0
6 E5-03 Motor Rated Current A 1.74 3.17 5.9 8.84 13.7 18.6 25.8 38.6 53.4 63.8
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 6.763 3.660 1.480 0.696 0.412 0.414 0.262 0.149 0.084 0.083
9 E5-06 d-Axis Inductance mH 42.88 28.59 17.64 10.40 7.94 10.60 7.53 4.49 3.83 2.78
10 E5-07 q-Axis Inductance mH 67.17 44.78 24.23 14.85 11.86 14.92 10.97 6.82 4.65 4.39
11 E5-09 Induction Voltage Constant 1 mVs/rad 333.3 337.7 365.5 356.2 359.2 428.2 410.0 389.8 387.6 392.6
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
13 E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
14 E1-05 Maximum Output Voltage V 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0 190.0
15 E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
16 E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.062 0.044 0.080 0.090 0.067 0.072 0.088 0.073 0.063 0.093
18 n8-49 d-Axis Current for High-Efficiency Control % –13.5 –16.3 –11.8 –12.3 –18.2 –18.7 –21.8 –24.0 –13.4 –25.4

Manual — SSR1 200V 1150 r/min PRG1018 and later — page 427

Source reference: SIEP C71060618F, December 2016, physical PDF page 427. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1018 and Later

Table B.19 200 V, 1150 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

B

Parameter List

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Table B.19 SS5 SSR1 IPM;200Vac;1150r/min;PRG1018 and later — PDF page 427

Source row Parameter Description Unit E5-01 motor code 1402 E5-01 motor code 1403 E5-01 motor code 1405 E5-01 motor code 1406 E5-01 motor code 1408 E5-01 motor code 140A E5-01 motor code 140B E5-01 motor code 140D E5-01 motor code 140E E5-01 motor code 140F
1 E5-01 Motor Code − 1402 1403 1405 1406 1408 140A 140B 140D 140E 140F
2 E5-01 Voltage Class − 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac 200 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
6 E5-03 Motor Rated Current A 1.88 3.02 6.00 8.85 14.27 20.21 26.67 39.9 55.6 63.5
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 4.832 2.704 1.114 0.511 0.412 0.303 0.165 0.113 0.084 0.066
9 E5-06 d-Axis Inductance mH 48.68 32.31 19.22 12.15 7.94 11.13 6.59 4.96 3.83 3.33
10 E5-07 q-Axis Inductance mH 63.21 40.24 24.38 15.35 11.86 14.06 8.55 6.12 4.65 4.5
11 E5-09 Induction Voltage Constant 1 mVs/rad 320.4 327.1 364.4 344.4 357.5 430.8 391.5 384.4 372.1 421.3
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0 0 0 0 0 0 0 0 0 0
13 E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
14 E1-05 Maximum Output Voltage V 190 190 190 190 190 190 190 190 190 190
15 E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
16 E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.062 0.044 0.08 0.09 0.067 0.072 0.088 0.073 0.062 0.091
18 n8-49 d-Axis Current for High-Efficiency Control % –8.8 –9.9 –9.3 –10 –17.7 –12.3 –15.3 –13.9 –14.4 –17.9

Manual — SSR1 400V 1150 r/min PRG1017 and earlier — page 428

Source reference: SIEP C71060618F, December 2016, physical PDF page 428. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1017 and Earlier

Table B.20 400 V, 1150 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Table B.20 SS5 SSR1 IPM;400Vac;1150r/min;PRG1017 and earlier — PDF page 428

Source row Parameter Description Unit E5-01 motor code 1432 E5-01 motor code 1433 E5-01 motor code 1435 E5-01 motor code 1436 E5-01 motor code 1438 E5-01 motor code 143A E5-01 motor code 143B E5-01 motor code 143D E5-01 motor code 143E E5-01 motor code 143F
1 E5-01 Motor Code − 1432 1433 1435 1436 1438 143A 143B 143D 143E 143F
2 E5-01 Voltage Class − 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15 18.0
6 E5-03 Motor Rated Current A 0.87 1.59 2.95 4.42 6.80 9.70 12.60 19.1 26.7 31.9
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 27.050 14.640 5.291 2.783 1.480 1.220 0.655 0.443 0.334 0.332
9 E5-06 d-Axis Inductance mH 171.50 114.40 70.56 41.61 38.39 45.97 25.46 18.84 15.27 11.10
10 E5-07 q-Axis Inductance mH 268.70 179.10 96.90 59.41 47.65 56.26 33.63 24.68 18.56 17.56
11 E5-09 Induction Voltage Constant 1 mVs/rad 666.9 675.5 731.0 712.4 792.7 859.9 820.2 805.4 796.4 785.1
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
13 E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
14 E1-05 Maximum Output Voltage V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
15 E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
16 E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.062 0.044 0.080 0.090 0.067 0.072 0.088 0.073 0.062 0.093
18 n8-49 d-Axis Current for High-Efficiency Control % –13.5 –16.2 –11.8 –12.3 –8.8 –11.5 –14.8 –15.6 –12.5 –25.4

Manual — SSR1 400V 1150 r/min PRG1018 and later — page 429

Source reference: SIEP C71060618F, December 2016, physical PDF page 429. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Drive Software Version PRG: 1018 and Later

Table B.21 400 V, 1150 rpm Type Yaskawa SSR1 Series Motor

Par. Description Unit Default Settings

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.

B.6 Parameters that Change with the Motor Code Selection

B

Parameter List

E5-01 | Motor Code | −

E5-01 | Voltage Class | −

E5-01 | Rated Power | −

E5-01 | Rated Speed | r/min

E5-02 | Motor Rated Power | kW

E5-03 | Motor Rated Current | A

E5-04 | Motor Pole Number | –

E5-05 | Motor Winding Resistance | Ω

E5-06 | d-Axis Inductance | mH

E5-07 | q-Axis Inductance | mH

E5-09 | Induction Voltage Constant 1 | mVs/rad

E5-24 | Induction Voltage Constant 2 | mV/(r/ min)

E1-04 | Maximum Output Frequency | Hz

E1-05 | Maximum Output Voltage | V

E1-06 | Base Frequency | Hz

E1-09 | Minimum Output Frequency | Hz

L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s

n8-49 | d-Axis Current for High-Efficiency Control | %

Table B.21 SS5 SSR1 IPM;400Vac;1150r/min;PRG1018 and later — PDF page 429

Source row Parameter Description Unit E5-01 motor code 1432 E5-01 motor code 1433 E5-01 motor code 1435 E5-01 motor code 1436 E5-01 motor code 1438 E5-01 motor code 143A E5-01 motor code 143B E5-01 motor code 143D E5-01 motor code 143E E5-01 motor code 143F
1 E5-01 Motor Code − 1432 1433 1435 1436 1438 143A 143B 143D 143E 143F
2 E5-01 Voltage Class − 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
3 E5-01 Rated Power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 5.5 kW 7.5 kW 11 kW 15 kW 18 kW
4 E5-01 Rated Speed r/min 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150
5 E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
6 E5-03 Motor Rated Current A 0.94 1.51 3.00 4.43 7.08 10.1 13.33 19.9 27.8 31.8
7 E5-04 Motor Pole Number – 6 6 6 6 6 6 6 6 6 6
8 E5-05 Motor Winding Resistance Ω 19.32 10.8 4.456 2.044 1.483 1.215 0.66 0.443 0.331 0.264
9 E5-06 d-Axis Inductance mH 194.7 129.2 76.88 48.6 37.58 44.54 26.36 19.1 15.09 13.32
10 E5-07 q-Axis Inductance mH 252.84 160.9 97.52 61.4 47.65 56.26 34.2 24.67 18.56 18
11 E5-09 Induction Voltage Constant 1 mVs/rad 640.9 654.1 728.8 688.9 702.0 861.5 783.0 762.2 749.6 842.7
12 E5-24 Induction Voltage Constant 2 mV/(r/ min) 0 0 0 0 0 0 0 0 0 0
13 E1-04 Maximum Output Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
14 E1-05 Maximum Output Voltage V 380 380 380 380 380 380 380 380 380 380
15 E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5 57.5
16 E1-09 Minimum Output Frequency Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
17 L3-24 <1> Motor Acceleration Time for Inertia Calculations s 0.062 0.044 0.08 0.09 0.067 0.072 0.088 0.073 0.062 0.091
18 n8-49 d-Axis Current for High-Efficiency Control % –8.8 –9.9 –9.3 –10 –12.8 –12.3 –15.3 –16.7 –14.9 –17.9

Manual — Communications section safety — page 432

Source reference: SIEP C71060618F, December 2016, physical PDF page 432. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.1 Section Safety

DANGER

Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

WARNING

Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not allow unqualified personnel to use equipment. Failure to comply could result in death or serious injury. Maintenance, inspection and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.

CAUTION

Crush Hazard Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive.

Manual — MEMOBUS/Modbus configuration — page 433

Source reference: SIEP C71060618F, December 2016, physical PDF page 433. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.2 MEMOBUS/Modbus Configuration

Drives can be controlled from a PLC or other master device via serial communications using the MEMOBUS/Modbus protocol. MEMOBUS/Modbus communication can be configured using one master (PLC) and a maximum of 255 slaves. The drive has slave functionality only, meaning that serial communication is normally initiated from the master and responded to by the slaves. The master performs serial communications with only one slave at a time. The address or node for each slave must be set beforehand so that the master can communicate with the slave at that address. A slave that receives a command from the master will perform the specified function and then send a response back to the master.

Figure C.1 Connecting Multiple Drives to a PLC

C

MEMOBUS/Modbus Communications

Figure C.1 labels: Master (PLC or other); DRIVE; DRIVE; DRIVE. Network illustration topology remains original-only; no physical wiring inferred.

Manual — Communication specifications — page 434

Source reference: SIEP C71060618F, December 2016, physical PDF page 434. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.3 Communication Specifications

MEMOBUS/Modbus specifications appear in the following table:

Item Specifications

Interface | RS-422, RS-485

Communications Cycle | Asynchronous (Start-stop synchronization)

Communication Parameters | Communication Speeds Available

Communication Parameters | Data length

Communication Parameters | Parity

Communication Parameters | Stop bit

Protocol | MEMOBUS/Modbus (using RTU mode only)

Max Number of Slaves | 31 drives

MEMOBUS/Modbus communication specifications — PDF page 434

Source row Item Subitem / merged specification Specification
1 Interface RS-422, RS-485 RS-422, RS-485
2 Communications Cycle Asynchronous (Start-stop synchronization) Asynchronous (Start-stop synchronization)
3 Communication Parameters Communication Speeds Available 1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 76.8; 115.2 kbps
4 Communication Parameters Data length 8 bit (fixed)
5 Communication Parameters Parity Select even, odd, or none
6 Communication Parameters Stop bit 1 bit (fixed)
7 Protocol MEMOBUS/Modbus (using RTU mode only) MEMOBUS/Modbus (using RTU mode only)
8 Max Number of Slaves 31 drives 31 drives

Manual — Network cable connection procedure — page 435

Source reference: SIEP C71060618F, December 2016, physical PDF page 435. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.4 Connecting to a Network

This section explains the connection of a drive to a MEMOBUS/Modbus network and the network termination.

◆ Network Cable Connection

Follow the instructions below to connect the drive to a MEMOBUS/Modbus network. 1. With the power shut off, connect the communications cable to the drive and the master. Use the terminals shown in the figure below for network cable connections.

Figure C.2 Serial Communications Cable Connection Terminals

Note: Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for the communications cables, and properly shielded clamps to prevent problems with noise. When using RS-485 communications, connect S+ to R+, and S- to R- as shown in the diagram below. 2. Check or set the terminating resistance at all slaves. Use the description in Network Termination for slaves that are 1000 series drives. 3. Switch the power on. 4. Set the parameters needed for serial communications (H5-01 through H5-12) using the LED operator. 5. Shut the power off and wait until the display on the LED operator goes out completely. 6. Turn the power back on. 7. The drive is now ready to begin communicating with the master.

C

MEMOBUS/Modbus Communications

Figure C.2 labels: R+ Receive (+); R− Receive (−); S+ Send (+); S− Send (−); IG Shield Ground. Enlarged terminal labels R+, R−, S+, S−, IG. Background miniature terminal legends remain in raw evidence and original image; exact board placement and wiring geometry are original-only.

Manual — RS-485 network figure and conditions — page 436

Source reference: SIEP C71060618F, December 2016, physical PDF page 436. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ Wiring Diagram for Multiple Connections

Figure C.3 and Figure C.4 explain the wiring diagrams for multiple connections using MEMOBUS/Modbus communication.

■ RS-485 Interface

Note: The isolated ground (IG) connection is optional but strongly recommended to improve network immunity to electrical interference.

<1> The Ground symbol represents a direct electrical connection to the Earth. Connect the shield to ground at the controller side only if common mode noise issues are suspected.

<2> The IG terminal is the signal common point for the RS-485 transceiver chip power supply. Connect the isolated ground IG between all nodes to help prevent the coupling of external noise to the bus and to limit bus emissions if desired.

Figure C.3 RS-485 Interface

Note: 1. Set DIP switch S2 to the ON position on the drive located at the end of the network. Set DIP switch S2 to the OFF positions on all other slave devices. 2. Set H5-07 to 1 when using the RS-485 interface.

C.4 Connecting to a Network

Figure C.3 RS-485 labels: Controller R−,R+,S−,S+,IG; three Drive terminal groups S−,S+,R−,R+,IG; S2 OFF on first and middle illustrated drives, S2 ON on end drive. Ground symbols and footnote markers1/2 retained in original. Exact network wiring, shields, junctions and topology remain original-only; source prose and footnotes separately retained.

Manual — RS-422 network figure and conditions — page 437

Source reference: SIEP C71060618F, December 2016, physical PDF page 437. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ RS-422 Interface

Figure C.4 RS-422 Interface

Note: 1. Set DIP switch S2 to the ON position on the drive located at the end of the network. Set DIP switch S2 to the OFF positions on all other slave devices. 2. Set H5-07 to 1 when using the RS-422 interface in a multi-drop circuit. Set H5-07 to 0 when using the RS-422 interface in a point-to-point circuit.

C.4 Connecting to a Network

C

MEMOBUS/Modbus Communications

Figure C.4 RS-422 labels: PLC R−,R+,S−,S+,IG; three Drive terminal groups S−,S+,R−,R+,IG; S2 OFF on first and middle illustrated drives, S2 ON on end drive. Exact network wiring, shield, junction and ground topology remain original-only; same-page notes preserved separately.

Manual — Network termination and resistance — page 438

Source reference: SIEP C71060618F, December 2016, physical PDF page 438. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ Network Termination

The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in terminating resistance that can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the terminating resistance by setting DIP switch S2 to the ON position. Disable the terminating resistance on all slaves that are not located at the network line end. Figure C.5 illustrates the setting of DIP switch S2.

Figure C.5 Serial Communications Terminal and DIP Switch S2

C.4 Connecting to a Network

Figure C.5 labels: DIP switch S2 (in the ON position); OFF; ON; enlarged terminals R+,R−,S+,S−,IG. RS-422A or RS-485; S+,S−,R+,R−; +,−; DIP switch S2; terminal resistance (1/2 W, 120 Ω). Source Ω symbol restored from image. Miniature background-board legends remain in raw evidence; exact switch orientation, connections and circuit topology are original-only.

Manual — Communication address speed parity and fault action — page 439

Source reference: SIEP C71060618F, December 2016, physical PDF page 439. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.5 MEMOBUS/Modbus Setup Parameters

◆ MEMOBUS/Modbus Serial Communication

This section describes parameters necessary to set up MEMOBUS/Modbus communications.

■ H5-01: Drive Slave Address

Sets the drive slave address used for MEMOBUS/Modbus communications.

Note: After changing this parameter, the power must be cycled to enable the new setting.

No. Name Setting Range Default

<1> If the address is set to 0, no response will be provided during communications.

For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01 to any value besides 0 assigns the drive its address in the network. Slave address don't need to be assigned in sequential order, but each address needs to be unique so that no two drives have the same address.

■ H5-02: Communication Speed Selection

Sets the MEMOBUS/Modbus communications speed.

H5-02 Communication Speed H5-02 Communication Speed

■ H5-03: Communication Parity Selection

Sets the parity used for MEMOBUS/Modbus communications.

Setting 0: No Parity

Setting 1: Even Parity

Setting 2: Odd Parity

■ H5-04: Stopping Method after Communication Error

Selects the stopping method after a communications error (CE) has occurred.

Setting 0: Ramp to Stop Using Current Accel/Decel Time

Setting 1: Coast to Stop

Setting 2: Fast-stop Using C1-09

C

MEMOBUS/Modbus Communications

H5-01 | Drive Slave Address

H5-02 | Communication Speed Selection

0 | 1200 bps

1 | 2400 bps

2 | 4800 bps

3 | 9600 bps

4 | 19200 bps

H5-03 | Communication Parity Selection

H5-04 | Stopping Method after Communication Error

H5-01 communications setup — PDF page 439

Source row Parameter Name Setting range Default
1 H5-01 Drive Slave Address 0 to 20 H <1> 1F

H5-02 communications setup — PDF page 439

Source row Parameter Name Setting range Default
1 H5-02 Communication Speed Selection 0 to 5 3

H5-02 communication speed choices — PDF page 439

Source row H5-02 first column Communication speed first column H5-02 second column Communication speed second column
1 0 1200 bps 5 38400 bps
2 1 2400 bps 6 57600 bps
3 2 4800 bps 7 76800 bps
4 3 9600 bps 8 115200 bps
5 4 19200 bps – –

H5-03 communications setup — PDF page 439

Source row Parameter Name Setting range Default
1 H5-03 Communication Parity Selection 0 to 2 0

H5-04 communications setup — PDF page 439

Source row Parameter Name Setting range Default
1 H5-04 Stopping Method after Communication Error 0 to 3 3

Manual — Communication fault wait RTS and voltage units — page 440

Source reference: SIEP C71060618F, December 2016, physical PDF page 440. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Setting 3: Alarm Only, Continue Operation

■ H5-05: Communication Fault Detection Selection

Enables or disabled the communication error (CE) detection for MEMOBUS/Modbus communications.

No. Name Setting Range Default

Setting 0: Disabled No error detection. The drive continues operation.

Setting 1: Enabled If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and the drive will operate as determined by parameter H5-04.

■ H5-06: Drive Transmit Wait Time

Sets the time the drive waits after receiving data from a master until responding data.

Figure C.6 Drive Transmit Wait Time Setting

■ H5-07: RTS Control Selection

Enables or disables RTS control.

Setting 0: Disabled - RTS is Always ON Use this setting when using RS-422 signals for communications (1:1).

Setting 1: Enabled - RTS Switches while Sending Use this setting when using RS-485 signals for communications or when using the RS-422 signals for multi-drop communications.

■ H5-09: CE Detection Time

Sets the time the communications must be lost before the drive triggers a CE fault.

■ H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H

Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.

Setting 0: 0.1 V Units

Setting 1: 1 V Units

C.5 MEMOBUS/Modbus Setup Parameters

Figure C.6 labels in time order: PLC→Drive Command message; Drive→PLC Response message; PLC→Drive Command message; Time. Gap labels 24 bit length and H5-06 setting. Exact arrow/gap geometry original-only; no additional numerical time inferred.

H5-05 | Communication Fault Detection Selection

H5-06 | Drive Transmit Wait Time

H5-07 | RTS Control Selection

H5-09 | CE Detection Time

H5-10 | Unit Selection for MEMOBUS/Modbus Register 0025H

H5-05 communications setup — PDF page 440

Source row Parameter Name Setting range Default
1 H5-05 Communication Fault Detection Selection 0 or 1 1

H5-06 communications setup — PDF page 440

Source row Parameter Name Setting range Default
1 H5-06 Drive Transmit Wait Time 5 to 65 ms 5 ms

H5-07 communications setup — PDF page 440

Source row Parameter Name Setting range Default
1 H5-07 RTS Control Selection 0 or 1 1

H5-09 communications setup — PDF page 440

Source row Parameter Name Setting range Default
1 H5-09 CE Detection Time 0.0 to 10.0 s 2.0 s

H5-10 communications setup — PDF page 440

Source row Parameter Name Setting range Default
1 H5-10 Unit Selection for MEMOBUS/Modbus Register 0025H 0 or 1 0

Manual — Enter command and run sequence settings — page 441

Source reference: SIEP C71060618F, December 2016, physical PDF page 441. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ H5-11: Communications Enter Function Selection

Selects if an Enter command is needed to change parameter values via MEMOBUS/Modbus communications. Refer to Enter Command on page 459.

No. Name Setting Range Default

Setting 0: Enter Command Necessary Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter change, not for each single parameter (such as in Varispeed F7).

Setting 1: Enter Command not Necessary Parameter value changes become effective immediately without the need to send an Enter command (such as in Varispeed VS606-V7)

■ H5-12: Run Command Method Selection

Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications (b1-02/16 = 2).

Setting 0: FWD/Stop, REV/Stop Bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Bit 1 will start and stop the drive in reverse.

Setting 1: Run/Stop, FWD/REV Bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Bit 1 changes the direction.

C.5 MEMOBUS/Modbus Setup Parameters

C

MEMOBUS/Modbus Communications

H5-11 | Communications Enter Function Selection

H5-12 | Run Command Method Selection

H5-11 communications setup — PDF page 441

Source row Parameter Name Setting range Default
1 H5-11 Communications Enter Function Selection 0 or 1 1

H5-12 communications setup — PDF page 441

Source row Parameter Name Setting range Default
1 H5-12 Run Command Method Selection 0 or 1 0

Manual — Observing and controlling the drive — page 442

Source reference: SIEP C71060618F, December 2016, physical PDF page 442. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.6 Drive Operations by MEMOBUS/Modbus

The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings. This section explains the functions that can be used and related parameter settings.

◆ Observing the Drive Operation

A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter settings (except H5-□□). • Observe drive status and drive control terminal status from a PLC. • Read and write parameters. • Set and reset faults. • Set multi-function inputs. Inputs settings from the input terminals S□ and from MEMOBUS/Modbus communications are both linked by an OR operation.

◆ Controlling the Drive

To start and stop the drive or set the frequency reference using MEMOBUS/Modbus communications, an external reference must be selected and the parameters listed below must be adjusted accordingly.

Table C.1 Setting Parameters for Drive Control from MEMOBUS/Modbus

Reference Source Parameter Name Required Setting

Refer to b1-01: Frequency Reference Selection 1 on page 121 and Refer to b1-02: Run Command Selection 1 on page 123 for details on external reference parameter selections. Refer to Setting 2: External Reference 1/2 Selection on page 186 for instructions on how to select external reference 1 and 2.

External Reference 1 | b1-01

External Reference 1 | b1-02

External Reference 2 | b1-15

External Reference 2 | b1-16

Table C.1 external reference settings for communication drive control — PDF page 442

Source row Reference source Parameter Name Required setting
1 External Reference 1 b1-01 Frequency Reference Selection 1 2
2 External Reference 1 b1-02 Run Command Selection 1 2
3 External Reference 2 b1-15 Frequency Reference Selection 2 2
4 External Reference 2 b1-16 Run Command Selection 2 2

Manual — Command and response timing — page 443

Source reference: SIEP C71060618F, December 2016, physical PDF page 443. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.7 Communications Timing

To prevent overrun in the slave drive, the master should wait a certain time between sending messages to the same drive. In the same way, the slave drive must wait before sending response messages to prevent an overrun in the master. This section explains the message timing.

◆ Command Messages from Master to Drive

In order to prevent overrun and data loss, the master must wait between receiving a response and sending the same type of command as before to the same slave drive. The minimum wait time depends on the command as shown in the table below.

Table C.2 Minimum Wait Time for Sending Messages Command Type Example Minimum Wait Time

<1> If the drive receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it receives a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.

Figure C.7 Minimum Wait Time for Sending Messages

A timer should be set in the master to check how long it takes for the slave drive(s) to respond to the master. If no response is received within a certain amount of time, the master should try resending the message.

◆ Response Messages from Drive to Master

If the drive receives a command from the master, it will process the data received and wait for the time set in H5-06 until it responds. Increase H5-06 if the drive response causes overrun in the master.

Figure C.8 Minimum Response Wait Time

C

MEMOBUS/Modbus Communications

Figure C.7 labels in time order: PLC→Drive Command message; Drive→PLC Response message; PLC→Drive Command message; Time. Gap labels24 bit length; Master Send Wait Time. Original arrow/gap geometry retained; table C.2 supplies numerical conditions separately.

Figure C.8 labels in time order: PLC→Drive Command message; Drive→PLC Response message; PLC→Drive Command message; Time. Gap labels24 bit length; H5-06 setting. Exact arrow/gap geometry original-only.

1 | • Control command (Run, Stop) • Set inputs/outputs • Read monitors and parameter values

2 | • Write parameters

3 | • Save changes using an Enter command

Table C.2 minimum wait for sending messages — PDF page 443

Source row Command type Example Minimum wait time
1 1 • Control command (Run, Stop) • Set inputs/outputs • Read monitors and parameter values 5 ms
2 2 • Write parameters H5-11 = 0: 50 ms; H5-11 = 1: 200 ms <1>
3 3 • Save changes using an Enter command 200 ms to 2 s, depending on the number of changed parameters <1>

Manual — Message format and CRC calculation procedure — page 444

Source reference: SIEP C71060618F, December 2016, physical PDF page 444. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.8 Message Format

◆ Message Content

In MEMOBUS/Modbus communications, the master sends commands to the slave, and the slave responds. The message format is configured for both sending and receiving as shown below, and the length of data packets depends on the command (function) content.

SLAVE ADDRESS FUNCTION CODE DATA ERROR CHECK

◆ Slave Address

The slave address in the message defines the note the message is sent to. Use addresses between 0 and 20H. If a message with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves do not provide a response to a broadcast type message.

◆ Function Code

The three types of function codes are shown in the table below.

Function Code; Function Name

Function Code; Function Name; Data Length (bytes): Command Message Minimum/Maximum; Response Message Minimum/Maximum

◆ Data

Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test) and the data the register contains. The data length changes depending on the command details.

A drive MEMOBUS/Modbus register always has a data length of two bytes. Therefore data written into drive registers must also always have a length of two bytes. Register data read out from the drive will always consist of two bytes.

◆ Error Check

The drive uses a CRC-16 (cyclic redundancy check, checksum method) for checking data validity. Use the procedure described below when calculating the CRC-16 checksum for command data or when verifying response data.

■ Command Data

When the drive receives data, it calculates the CRC-16 checksum from the data and compares it to the CRC-16 value received within the message. Both must match before a command is processed. An initial value of FFFFH (i.e., all 16 bits equal 1) must be used for CRC-16 calculations for the MEMOBUS/Modbus protocol. Calculate the CRC-16 checksum using the following steps: • The starting value is FFFFH. • Perform an XOR operation of this value and the slave address. • Right shift the result. • When the overflow bit of the shift operation becomes 1, perform an XOR operation of the result from step 3 above and the fix value A001H. • Repeat steps 3 and 4 until eight shift operations have been performed. • After eight shift operations, perform an XOR operation with the result and the next data in the message (function code, register address, data). Continue with steps 3 to 5 until the last data has been processed. • The result of the last shift or XOR operation is the checksum.

03H | Read MEMOBUS/Modbus registers

08H | Loopback test

10H | Write to multiple MEMOBUS/Modbus registers

Function codes and message length limits in bytes — PDF page 444

Source row Function code Function name Command minimum bytes Command maximum bytes Response minimum bytes Response maximum bytes
1 03H Read MEMOBUS/Modbus registers 8 8 7 37
2 08H Loopback test 8 8 8 8
3 10H Write to multiple MEMOBUS/Modbus registers 11 41 8 8

Manual — CRC example and response validation — page 445

Source reference: SIEP C71060618F, December 2016, physical PDF page 445. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

The example in Table C.3 shows the CRC-16 calculation of the slave address 02H and the function code 03H, yielding the result D140H.

Note: This example does not show the calculation for a complete MEMOBUS/Modbus command. Normally data would follow in the calculation.

Table C.3 CRC-16 Checksum Calculation Example Description Calculation Overflow Description Calculation Overflow

Perform operations with next data (function code)

Continue from here with next data.

■ Response Data

To be sure that the data is valid, perform a CRC-16 calculation on the response message data as described above. Compare the result to the CRC-16 checksum that was received within the response message. Both should match.

C.8 Message Format

C

MEMOBUS/Modbus Communications

CRC-16 example result: 1101 0001 0100 0000; D 1 labelled (Lower); 4 0 labelled (Upper). The source labels are preserved literally without a byte-order correction. This incomplete command example continues with next data.

Illustrative incomplete message CRC calculation only. The right-hand source block continues the left-hand block; no running-device value. Final D140H and lower/upper labels retained separately as source context, no reimplementation or inferred byte correction.

Initial Value (FFFFH) | 1111 1111 1111 1111

Address 02H | 0000 0000 0000 0010

XOR w initial value | 1111 1111 1111 1101

Shift 1 | 0111 1111 1111 1110

XOR w A001H | 1010 0000 0000 0001

XOR result | 1101 1111 1111 1111

Shift 2 | 0110 1111 1111 1111

XOR result | 1100 1111 1111 1110

Shift 3 | 0110 0111 1111 1111

Shift 4 | 0011 0011 1111 1111

XOR result | 1001 0011 1111 1110

Shift 5 | 0100 1001 1111 1111

Shift 6 | 0010 0100 1111 1111

XOR result | 1000 0100 1111 1110

Shift 7 | 0100 0010 0111 1111

Shift 8 | 0010 0001 0011 1111

XOR result | 1000 0001 0011 1110

Function Code 03H | 0000 0000 0000 0011

XOR w result | 1000 0001 0011 1101

Shift 1 | 0100 0000 1001 1110

XOR result | 1110 0000 1001 1111

Shift 2 | 0111 0000 0100 1111

XOR result | 1101 0000 0100 1110

Shift 3 | 0110 1000 0010 0111

Shift 4 | 0011 0100 0001 0011

XOR result | 1001 0100 0001 0010

Shift 5 | 0100 1010 0000 1001

Shift 6 | 0010 0101 0000 0100

XOR result | 1000 0101 0000 0101

Shift 7 | 0100 0010 1000 0010

XOR result | 1110 0010 1000 0011

Shift 8 | 0111 0001 0100 0001

XOR result | 1101 0001 0100 0000

Table C.3 CRC16 example first stage slave address02H — PDF page 445

Source row Description Calculation Overflow
1 Initial Value (FFFFH) 1111 1111 1111 1111 ⟦blank source cell⟧
2 Address 02H 0000 0000 0000 0010 ⟦blank source cell⟧
3 XOR w initial value 1111 1111 1111 1101 ⟦blank source cell⟧
4 Shift 1 0111 1111 1111 1110 1
5 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
6 XOR result 1101 1111 1111 1111 ⟦blank source cell⟧
7 Shift 2 0110 1111 1111 1111 1
8 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
9 XOR result 1100 1111 1111 1110 ⟦blank source cell⟧
10 Shift 3 0110 0111 1111 1111 0
11 Shift 4 0011 0011 1111 1111 1
12 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
13 XOR result 1001 0011 1111 1110 ⟦blank source cell⟧
14 Shift 5 0100 1001 1111 1111 0
15 Shift 6 0010 0100 1111 1111 1
16 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
17 XOR result 1000 0100 1111 1110 ⟦blank source cell⟧
18 Shift 7 0100 0010 0111 1111 0
19 Shift 8 0010 0001 0011 1111 1
20 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
21 XOR result 1000 0001 0011 1110 ⟦blank source cell⟧

Table C.3 CRC16 example continuation function code03H — PDF page 445

Source row Description Calculation Overflow
1 Function Code 03H 0000 0000 0000 0011 ⟦blank source cell⟧
2 XOR w result 1000 0001 0011 1101 ⟦blank source cell⟧
3 Shift 1 0100 0000 1001 1110 1
4 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
5 XOR result 1110 0000 1001 1111 ⟦blank source cell⟧
6 Shift 2 0111 0000 0100 1111 1
7 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
8 XOR result 1101 0000 0100 1110 ⟦blank source cell⟧
9 Shift 3 0110 1000 0010 0111 0
10 Shift 4 0011 0100 0001 0011 0
11 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
12 XOR result 1001 0100 0001 0010 ⟦blank source cell⟧
13 Shift 5 0100 1010 0000 1001 0
14 Shift 6 0010 0101 0000 0100 1
15 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
16 XOR result 1000 0101 0000 0101 ⟦blank source cell⟧
17 Shift 7 0100 0010 1000 0010 1
18 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
19 XOR result 1110 0010 1000 0011 ⟦blank source cell⟧
20 Shift 8 0111 0001 0100 0001 1
21 XOR w A001H 1010 0000 0000 0001 ⟦blank source cell⟧
22 XOR result 1101 0001 0100 0000 ⟦blank source cell⟧

Manual — Read and loopback message examples — page 446

Source reference: SIEP C71060618F, December 2016, physical PDF page 446. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.9 Message Examples

Below are some examples of command and response messages.

◆ Reading Drive MEMOBUS/Modbus Register Contents

Using the function code 03H (Read), a maximum of 16 MEMOBUS/Modbus registers can be read out at a time. The following table shows message examples when reading status signals, error details, data link status, and frequency references from the slave 2 drive.

Command Message Response Message (normal) Response Message (fault)

◆ Loopback Test

Function code 08H performs a loopback test. This test returns a response message with exactly the same content as the command message and can be used to check the communications between the master and slave. User-defined test code and data values can be set. The following table shows a message example when performing a loopback test with the slave 1 drive.

Separate physical message panel; content is an example, not current settings. Exact source upper/lower labels retained. Shared item labels span only their actual physical extent; empty end panels omitted. Read with same-page protocol and Enter-command conditions.

Slave Address | Slave Address

Function Code | Function Code

Starting No. | Upper

Starting No. | Lower

Data Quantity | Upper

Data Quantity | Lower

CRC-16 | Upper

CRC-16 | Lower

Data Quantity | Data Quantity

1st storage register | Upper

1st storage register | Lower

Next storage register | Upper

Next storage register | Lower

Error Code | Error Code

Test Code | Upper

Test Code | Lower

Data | Upper

Data | Lower

Read registers example — Command — PDF page 446

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 02H
2 Function Code Function Code 03H
3 Starting No. Upper 00H
4 Starting No. Lower 20H
5 Data Quantity Upper 00H
6 Data Quantity Lower 04H
7 CRC-16 Upper 45H
8 CRC-16 Lower F0H

Read registers example — Normal response — PDF page 446

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 02H
2 Function Code Function Code 03H
3 Data Quantity Data Quantity 08H
4 1st storage register Upper 00H
5 1st storage register Lower 65H
6 Next storage register Upper 00H
7 Next storage register Lower 00H
8 Next storage register Upper 00H
9 Next storage register Lower 00H
10 Next storage register Upper 01H
11 Next storage register Lower F4H
12 CRC-16 Upper AFH
13 CRC-16 Lower 82H

Read registers example — Fault response — PDF page 446

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 02H
2 Function Code Function Code 83H
3 Error Code Error Code 03H
4 CRC-16 Upper F1H
5 CRC-16 Lower 31H

Loopback example — Command — PDF page 446

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 01H
2 Function Code Function Code 08H
3 Test Code Upper 00H
4 Test Code Lower 00H
5 Data Upper A5H
6 Data Lower 37H
7 CRC-16 Upper DAH
8 CRC-16 Lower 8DH

Loopback example — Fault response — PDF page 446

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 01H
2 Function Code Function Code 89H
3 Error Code Error Code 01H
4 CRC-16 Upper 86H
5 CRC-16 Lower 50H

Manual — Multiple-register write example — page 447

Source reference: SIEP C71060618F, December 2016, physical PDF page 447. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ Writing to Multiple Registers

Function code 10h allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process works similar to reading registers, i.e., the address of the first register that is to be written and the data quantity must be set in the command message. The data to be written must be consecutive so that the register addresses are in order, starting from the specified address in the command message. The data order must be high byte, then lower byte. The following table shows an example of a message where a forward operation has been set with a frequency reference of 60.00 Hz for the slave 1 drive. If parameter values are changed using the Write command, depending on the setting of H5-11, an Enter command will be necessary to activate the data or save them. Refer to H5-11: Communications Enter Function Selection on page 441 and Refer to Enter Command on page 459 for detailed descriptions.

Command Message Response Message (normal) Response Message (fault)

Note: For the number of bytes in the command message, take double the number of the data quantity.

C.9 Message Examples

C

MEMOBUS/Modbus Communications

Separate physical message panel; content is an example, not current settings. Exact source upper/lower labels retained. Shared item labels span only their actual physical extent; empty end panels omitted. Read with same-page protocol and Enter-command conditions.

Slave Address | Slave Address

Function Code | Function Code

Starting No. | Upper

Starting No. | Lower

Data Quantity | Upper

Data Quantity | Lower

Number of Bytes | Number of Bytes

Starting Data | Upper

Starting Data | Lower

Next Data | Upper

Next Data | Lower

CRC-16 | Upper

CRC-16 | Lower

Error Code | Error Code

Write registers example — Command — PDF page 447

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 01H
2 Function Code Function Code 10H
3 Starting No. Upper 00H
4 Starting No. Lower 01H
5 Data Quantity Upper 00H
6 Data Quantity Lower 02H
7 Number of Bytes Number of Bytes 04H
8 Starting Data Upper 00H
9 Starting Data Lower 01H
10 Next Data Upper 17H
11 Next Data Lower 70H
12 CRC-16 Upper 6DH
13 CRC-16 Lower 67H

Write registers example — Normal response — PDF page 447

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 01H
2 Function Code Function Code 10H
3 Starting No. Upper 00H
4 Starting No. Lower 01H
5 Data Quantity Upper 00H
6 Data Quantity Lower 02H
7 CRC-16 Upper 10H
8 CRC-16 Lower 08H

Write registers example — Fault response — PDF page 447

Source row Item Upper/lower byte or shared item Hexadecimal value
1 Slave Address Slave Address 01H
2 Function Code Function Code 90H
3 Error Code Error Code 02H
4 CRC-16 Upper CDH
5 CRC-16 Lower C1H

Manual — Command register and bit map — page 448

Source reference: SIEP C71060618F, December 2016, physical PDF page 448. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.10 MEMOBUS/Modbus Data Table

Table below lists all MEMOBUS/Modbus data. There are three types of data: command data, monitor data, and broadcast data.

◆ Command Data

It is possible to both read and write command data.

Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.

Register No. Contents

0000H | Reserved

0001H | Operation Signals and Multi-function Inputs

0001H | bit 0

0001H | bit 1

0001H | bit 2

0001H | bit 3

0001H | bit 4

0001H | bit 5

0001H | bit 6

0001H | bit 7

0001H | bit 8

0001H | bit 9

0001H | bit A

0001H | bit B to F

0002H | Frequency Reference

0003H | Output Voltage Gain

0004H-0005H | Reserved

0006H | PID Target, 0.01% units, signed

0007H | Analog Output Terminal AM Setting (10 V / 4000 H)

0008H | Reserved

0009H | Settings for Multi-Function Digital Outputs

0009H | bit 0

0009H | bit 1

0009H | bit 2

0009H | bit 3 to F

000AH | Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000

000BH-000EH | Reserved

000FH | Control Selection Setting

000FH | bit 0

000FH | bit 1

000FH | bit 2 to B

000FH | bit C

000FH | bit D

000FH | bit E

000FH | bit F

Command register map — PDF page 448

Source row Register number hex Bit / subitem / merged contents Contents
1 0000H Reserved Reserved
2 0001H Operation Signals and Multi-function Inputs Operation Signals and Multi-function Inputs
3 0001H bit 0 H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run) H5-12 = 1: Run Command (0 = Stop, 1 = Run)
4 0001H bit 1 H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Reverse Run) H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse)
5 0001H bit 2 External Fault (EF0)
6 0001H bit 3 Fault Reset
7 0001H bit 4 Multi-Function Input 1 Function is ComRef when H1-01 = 40 (Forward/Stop). Note: When the bit at ComRef is turned on, commands from MEMOBUS/Modbus communications take control of the frequency. When a communications option card is connected, that option card is given priority.
8 0001H bit 5 Multi-Function Input 2 Function is ComCtrl when H1-02 = 41 (Reverse/Stop).
9 0001H bit 6 Multi-Function Input 3
10 0001H bit 7 Multi-Function Input 4
11 0001H bit 8 Multi-Function Input 5
12 0001H bit 9 Multi-Function Input 6
13 0001H bit A Multi-Function Input 7
14 0001H bit B to F Reserved
15 0002H Frequency Reference Units are determined by parameter o1-03
16 0003H Output Voltage Gain Set in units of 1 (0.1%) with a setting range of 20 to 2000 (2.0% to 200.0%) Note: Initial value at power up: 1000 (100.0%)
17 0004H-0005H Reserved Reserved
18 0006H PID Target, 0.01% units, signed PID Target, 0.01% units, signed
19 0007H Analog Output Terminal AM Setting (10 V / 4000 H) Analog Output Terminal AM Setting (10 V / 4000 H)
20 0008H Reserved Reserved
21 0009H Settings for Multi-Function Digital Outputs Settings for Multi-Function Digital Outputs
22 0009H bit 0 Contact Output (terminal MA/MB-MC)
23 0009H bit 1 Photocoupler Output 1 (terminal P1-PC)
24 0009H bit 2 Photocoupler Output 2 (terminal P2-PC)
25 0009H bit 3 to F Reserved
26 000AH Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000 Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000
27 000BH-000EH Reserved Reserved
28 000FH Control Selection Setting Control Selection Setting
29 000FH bit 0 Reserved
30 000FH bit 1 PID Target Input
31 000FH bit 2 to B Reserved
32 000FH bit C Enable Terminal S5 Input for Broadcast Data
33 000FH bit D Enable Terminal S6 Input for Broadcast Data
34 000FH bit E Enable Terminal S7 Input for Broadcast Data
35 000FH bit F Reserved

Manual — Read-only status fault and monitor register map — page 449

Source reference: SIEP C71060618F, December 2016, physical PDF page 449. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ Monitor Data

Monitor data can be read only.

Register No. Contents

C.10 MEMOBUS/Modbus Data Table

C

MEMOBUS/Modbus Communications

0020H | Drive Status 1

0020H | bit 0

0020H | bit 1

0020H | bit 2

0020H | bit 3

0020H | bit 4

0020H | bit 5

0020H | bit 6

0020H | bit 7

0020H | bit 8 to bit D

0020H | bit E

0020H | bit F

0021H | Fault Contents 1

0021H | bit 0

0021H | bit 1

0021H | bit 2

0021H | bit 3

0021H | bit 4

0021H | bit 5

0021H | bit 6

0021H | bit 7

0021H | bit 8

0021H | bit 9

0021H | bit A

0021H | bit B

0021H | bit C

0021H | bit D

0021H | bit E

0021H | bit F

0022H | Data Link Status

0022H | bit 0

0022H | bit 1

0022H | bit 2

0022H | bit 3

0022H | bit 4

0022H | bit 5

0022H | bit 6 to bit F

0023H | Frequency Reference, <1>

0024H | Output Frequency, <1>

0025H | Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)

0026H | Output Current, <2>

0027H | Output Power

0028H | Torque Reference (OLV only)

Monitor register map (read only) — PDF page 449

Source row Register number hex Bit / subitem / merged contents Contents
1 0020H Drive Status 1 Drive Status 1
2 0020H bit 0 During Run
3 0020H bit 1 During Reverse
4 0020H bit 2 Drive Ready
5 0020H bit 3 Fault
6 0020H bit 4 Data Setting Error
7 0020H bit 5 Multi-Function Contact Output (terminal MA/MB-MC)
8 0020H bit 6 Multi-Function Photocoupler Output 1 (terminal P1 - PC)
9 0020H bit 7 Multi-Function Photocoupler Output 2 (terminal P2 - PC)
10 0020H bit 8 to bit D Reserved
11 0020H bit E When ComRef has been enabled
12 0020H bit F When ComCtrl has been enabled
13 0021H Fault Contents 1 Fault Contents 1
14 0021H bit 0 Overcurrent (oC), Ground fault (GF), IGBT Short Circuit or Ground Fault (SC)
15 0021H bit 1 Overvoltage (ov)
16 0021H bit 2 Drive Overload (oL2)
17 0021H bit 3 Overheat 1 (oH1), Drive Overheat Warning (oH2)
18 0021H bit 4 Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)
19 0021H bit 5 Reserved
20 0021H bit 6 PID Feedback Loss (FbL/FbH)
21 0021H bit 7 EF0 to 7: External Fault
22 0021H bit 8 CPF□□: Hardware Fault (includes oFA□□)
23 0021H bit 9 Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/ UL4)
24 0021H bit A PG Disconnected (PGo), Overspeed (oS), Excessive Speed Deviation (dEv),
25 0021H bit B Main Circuit Undervoltage (Uv)
26 0021H bit C Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
27 0021H bit D Output Phase Loss (LF), Input Phase Loss (PF)
28 0021H bit E MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
29 0021H bit F Operator Connection Fault (oPr)
30 0022H Data Link Status Data Link Status
31 0022H bit 0 Writing data or switching motors
32 0022H bit 1 Reserved
33 0022H bit 2 Reserved
34 0022H bit 3 Upper or lower limit error
35 0022H bit 4 Data conformity error
36 0022H bit 5 Writing to EEPROM
37 0022H bit 6 to bit F Reserved
38 0023H Frequency Reference, <1> Frequency Reference, <1>
39 0024H Output Frequency, <1> Output Frequency, <1>
40 0025H Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10) Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)
41 0026H Output Current, <2> Output Current, <2>
42 0027H Output Power Output Power
43 0028H Torque Reference (OLV only) Torque Reference (OLV only)

Manual — Read-only fault alarm and input register map — page 450

Source reference: SIEP C71060618F, December 2016, physical PDF page 450. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Register No. Contents

C.10 MEMOBUS/Modbus Data Table

0029H | Fault Contents 2

0029H | bit 0

0029H | bit 1

0029H | bit 2

0029H | bit 3

0029H | bit 4

0029H | bit 5

0029H | bit 6

0029H | bit 7 to bit F

002AH | Alarm Contents1

002AH | bit 0 to bit 1

002AH | bit 2

002AH | bit 3

002AH | bit 4

002AH | bit 5

002AH | bit 6

002AH | bit 7

002AH | bit 8

002AH | bit 9

002AH | bit A

002AH | bit B

002AH | bit C

002AH | bit D

002AH | bit E

002AH | bit F

002BH | Input Terminal Status

002BH | bit 0

002BH | bit 1

002BH | bit 2

002BH | bit 3

002BH | bit 4

002BH | bit 5

002BH | bit 6

002BH | bit 7 to bit F

Monitor register map (read only) — PDF page 450

Source row Register number hex Bit / subitem / merged contents Contents
1 0029H Fault Contents 2 Fault Contents 2
2 0029H bit 0 IGBT Short Circuit or Ground Fault (SC)
3 0029H bit 1 Ground Fault (GF)
4 0029H bit 2 Input Phase Loss (PF)
5 0029H bit 3 Output Phase Loss (LF)
6 0029H bit 4 Braking Resistor Overheat (rH)
7 0029H bit 5 Reserved
8 0029H bit 6 Motor Overheat 2 (PTC input) (oH4)
9 0029H bit 7 to bit F Reserved
10 002AH Alarm Contents1 Alarm Contents1
11 002AH bit 0 to bit 1 Reserved
12 002AH bit 2 Run Command Input Error (EF)
13 002AH bit 3 Drive Baseblock (bb)
14 002AH bit 4 Overtorque Detection 1 (oL3)
15 002AH bit 5 Heatsink Overheat (oH)
16 002AH bit 6 Overvoltage (ov)
17 002AH bit 7 Undervoltage (Uv)
18 002AH bit 8 Reserved
19 002AH bit 9 MEMOBUS/Modbus Communication Error (CE)
20 002AH bit A Option Communication Error (bUS)
21 002AH bit B Undertorque Detection 1/2 (UL3/UL4)
22 002AH bit C Motor Overheat (oH3)
23 002AH bit D PID Feedback Loss (FbL, FbH)
24 002AH bit E Reserved
25 002AH bit F Serial Communication Transmission Error (CALL)
26 002BH Input Terminal Status Input Terminal Status
27 002BH bit 0 Terminal S1 Closed
28 002BH bit 1 Terminal S2 Closed
29 002BH bit 2 Terminal S3 Closed
30 002BH bit 3 Terminal S4 Closed
31 002BH bit 4 Terminal S5 Closed
32 002BH bit 5 Terminal S6 Closed
33 002BH bit 6 Terminal S7 Closed
34 002BH bit 7 to bit F Reserved

Manual — Monitor status and output registers — page 451

Source reference: SIEP C71060618F, December 2016, physical PDF page 451. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Register No. Contents

C.10 MEMOBUS/Modbus Data Table

C

MEMOBUS/Modbus Communications

002CH | Drive Status 2

002CH | bit 0

002CH | bit 1

002CH | bit 2

002CH | bit 3

002CH | bit 4

002CH | bit 5

002CH | bit 6

002CH | bit 7

002CH | bit 8

002CH | bit 9

002CH | bit A

002CH | bit B

002CH | bit C

002CH | bit D

002CH | bit E

002CH | bit F

002DH | Output Terminal Status

002DH | bit 0

002DH | bit 1

002DH | bit 2

002DH | bit 3 to bit F

002EH | Reserved

002FH | Frequency Reference Bias (from Up/Down 2 Function), 0.1% units

0030H | Reserved

0031H | DC Bus Voltage, 1 Vdc units

0032H | Torque Monitor, 1% units

0033H | Reserved

0034H | Product Code 1 [ASCII], Product Type (V0 for V1000)

0035H | Product Code 2 [ASCII], Region Code

0036H to 0037H | Reserved

0038H | PID Feedback, 0.1% units, unsigned, 100% / max. output frequency

0039H | PID Input, 0.1% units, signed, 100% / max. output frequency

003AH | PID Output, 0.1% units, signed, 100% / max. output frequency

003BH to 003CH | Reserved

003DH | Communications Error Log <3>

003DH | bit 0

003DH | bit 1

003DH | bit 2

003DH | bit 3

003DH | bit 4

003DH | bit 5

003DH | bit 6

003DH | bit 7 to bit F

003EH | Output Frequency

003FH | Output Frequency

0040H to 004AH | Used for various monitors U1-□□. Refer to U: Monitors on page 399 for parameter details.

C10 read-only monitor register and bit map — PDF page 451

Source row Register number hex Bit / subitem / merged contents Contents
1 002CH Drive Status 2 Drive Status 2
2 002CH bit 0 During Run
3 002CH bit 1 Zero Speed
4 002CH bit 2 Speed Agree
5 002CH bit 3 User Speed Agree
6 002CH bit 4 Frequency Detection 1
7 002CH bit 5 Frequency Detection 2
8 002CH bit 6 Drive Ready
9 002CH bit 7 During Undervoltage
10 002CH bit 8 During Baseblock
11 002CH bit 9 Frequency Reference from Operator Keypad
12 002CH bit A Run Command from Operator Keypad
13 002CH bit B Over/Undertorque 1, 2
14 002CH bit C Frequency Reference Loss
15 002CH bit D During Fault Restart
16 002CH bit E Fault
17 002CH bit F Communication Timeout
18 002DH Output Terminal Status Output Terminal Status
19 002DH bit 0 Multi-Function Contact Output (terminal MA/MB-MC)
20 002DH bit 1 Multi-Function Photocoupler Output 1 (terminal P1 - PC)
21 002DH bit 2 Multi-Function Photocoupler Output 2 (terminal P2 - PC)
22 002DH bit 3 to bit F Reserved
23 002EH Reserved Reserved
24 002FH Frequency Reference Bias (from Up/Down 2 Function), 0.1% units Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
25 0030H Reserved Reserved
26 0031H DC Bus Voltage, 1 Vdc units DC Bus Voltage, 1 Vdc units
27 0032H Torque Monitor, 1% units Torque Monitor, 1% units
28 0033H Reserved Reserved
29 0034H Product Code 1 [ASCII], Product Type (V0 for V1000) Product Code 1 [ASCII], Product Type (V0 for V1000)
30 0035H Product Code 2 [ASCII], Region Code Product Code 2 [ASCII], Region Code
31 0036H to 0037H Reserved Reserved
32 0038H PID Feedback, 0.1% units, unsigned, 100% / max. output frequency PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
33 0039H PID Input, 0.1% units, signed, 100% / max. output frequency PID Input, 0.1% units, signed, 100% / max. output frequency
34 003AH PID Output, 0.1% units, signed, 100% / max. output frequency PID Output, 0.1% units, signed, 100% / max. output frequency
35 003BH to 003CH Reserved Reserved
36 003DH Communications Error Log <3> Communications Error Log <3>
37 003DH bit 0 CRC Error
38 003DH bit 1 Data Length Error
39 003DH bit 2 Reserved
40 003DH bit 3 Parity Error
41 003DH bit 4 Overrun Error
42 003DH bit 5 Framing Error
43 003DH bit 6 Timeout
44 003DH bit 7 to bit F Reserved
45 003EH Output Frequency r/min <4>
46 003FH Output Frequency 0.01% units
47 0040H to 004AH Used for various monitors U1-□□. Refer to U: Monitors on page 399 for parameter details. Used for various monitors U1-□□. Refer to U: Monitors on page 399 for parameter details.

Manual — Monitor codes hours and option identifiers — page 452

Source reference: SIEP C71060618F, December 2016, physical PDF page 452. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Register No. Contents

C.10 MEMOBUS/Modbus Data Table

004BH | Drive status (U1-12)

004BH | bit 0

004BH | bit 1

004BH | bit 2

004BH | bit 3

004BH | bit 4

004BH | bit 5

004BH | bit 6

004BH | bit 7

004BH | bit 8

004BH | bit 9

004BH | bit A

004BH | bit B to D

004BH | bit E

004BH | bit F

004CH to 007EH | Used for various monitors U1-□□, U4-□□, U5-□□ and U6-□□. Refer to U: Monitors on page 399 for parameter details.

007FH | Alarm Code, Refer to Alarm Register Contents on page 458 for alarm codes.

0080H to 0097H | Used for monitors U2-□□, U3-□□. Refer to U: Monitors on page 399 for parameter details and Refer to Fault Trace Contents on page 457 for register value descriptions.

0098H, 0099H | U4-01 (Cumulative Operation Time) Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.

009AH, 009BH | U4-03 (Cooling Fan Operation Time) Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.

00ABH | Drive Rated Current <2>

00ACH | Motor Speed (Open Loop Vector only)

00ADH | Motor Speed (Open Loop Vector only)

00AEH, 00AFH | Reserved

00B0H | Option Code

00B1H to 00B4H | Reserved

00B5H | Frequency Reference After Soft-starter

00B6H | Frequency Reference After Soft-starter

00B7H | Frequency Reference

00B8H | Frequency Reference

00BFH | oPE Error Number

C10 read-only monitor register and bit map — PDF page 452

Source row Register number hex Bit / subitem / merged contents Contents
1 004BH Drive status (U1-12) Drive status (U1-12)
2 004BH bit 0 During Run
3 004BH bit 1 During Zero Speed
4 004BH bit 2 During Reverse Run
5 004BH bit 3 During Fault Reset Signal Input
6 004BH bit 4 During Speed Agree
7 004BH bit 5 Drive Ready
8 004BH bit 6 Alarm
9 004BH bit 7 Fault
10 004BH bit 8 During Operation Error (oPE□□)
11 004BH bit 9 During Momentary Power Loss
12 004BH bit A Motor 2 selected
13 004BH bit B to D Reserved
14 004BH bit E ComRef status, NetRef status
15 004BH bit F ComCtrl status, NetCtrl status
16 004CH to 007EH Used for various monitors U1-□□, U4-□□, U5-□□ and U6-□□. Refer to U: Monitors on page 399 for parameter details. Used for various monitors U1-□□, U4-□□, U5-□□ and U6-□□. Refer to U: Monitors on page 399 for parameter details.
17 007FH Alarm Code, Refer to Alarm Register Contents on page 458 for alarm codes. Alarm Code, Refer to Alarm Register Contents on page 458 for alarm codes.
18 0080H to 0097H Used for monitors U2-□□, U3-□□. Refer to U: Monitors on page 399 for parameter details and Refer to Fault Trace Contents on page 457 for register value descriptions. Used for monitors U2-□□, U3-□□. Refer to U: Monitors on page 399 for parameter details and Refer to Fault Trace Contents on page 457 for register value descriptions.
19 0098H, 0099H U4-01 (Cumulative Operation Time) Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5. U4-01 (Cumulative Operation Time) Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.
20 009AH, 009BH U4-03 (Cooling Fan Operation Time) Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5. U4-03 (Cooling Fan Operation Time) Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.
21 00ABH Drive Rated Current <2> Drive Rated Current <2>
22 00ACH Motor Speed (Open Loop Vector only) r/min units <4>
23 00ADH Motor Speed (Open Loop Vector only) 0.01% units
24 00AEH, 00AFH Reserved Reserved
25 00B0H Option Code The following lists the 3 and 4 letter ASCII codes stored for each serial communication option: CANopen (Model: SI-S3/V): 5353H CC-Link (Model: SI-C3/V): 5343H DeviceNet (Model: SI-N3/V): 534EH PROFIBUS-DP (Model: SI-P3/V): 5350H MECHATROLINK-II (Model: SI-T3/V): 5354H MECHATROLINK-III (Model: SI-ET3/V): 1004H CompoNet (Model: SI-M3/V): 434EH Other options use their own unique codes. Refer to the communication option instruction manual for the option code.
26 00B1H to 00B4H Reserved Reserved
27 00B5H Frequency Reference After Soft-starter r/min units <4>
28 00B6H Frequency Reference After Soft-starter 0.01% units
29 00B7H Frequency Reference r/min <4>
30 00B8H Frequency Reference 0.01% units
31 00BFH oPE Error Number oPE Error Number

Manual — Fault contents registers3–5 — page 453

Source reference: SIEP C71060618F, December 2016, physical PDF page 453. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Register No. Contents

C.10 MEMOBUS/Modbus Data Table

C

MEMOBUS/Modbus Communications

00C0H | Fault contents 3

00C0H | bit 0

00C0H | bit 1

00C0H | bit 2

00C0H | bit 3

00C0H | bit 4

00C0H | bit 5

00C0H | bit 6

00C0H | bit 7

00C0H | bit 8

00C0H | bit 9

00C0H | bit A

00C0H | bit B

00C0H | bit C

00C0H | bit D

00C0H | bit E

00C0H | bit F

00C1H | Fault contents 4

00C1H | bit 0

00C1H | bit 1

00C1H | bit 2

00C1H | bit 3

00C1H | bit 4

00C1H | bit 5 to 6

00C1H | bit 7

00C1H | bit 8

00C1H | bit 9

00C1H | bit A

00C1H | bit B

00C1H | bit C

00C1H | bit D

00C1H | bit E

00C1H | bit F

00C2H | Fault contents 5

00C2H | bit 0

00C2H | bit 1

00C2H | bit 2 to 3

00C2H | bit 4

00C2H | bit 5

00C2H | bit 6

00C2H | bit 7

00C2H | bit 8

00C2H | bit 9

00C2H | bit A

00C2H | bit B to E

00C2H | bit F

C10 read-only monitor register and bit map — PDF page 453

Source row Register number hex Bit / subitem / merged contents Contents
1 00C0H Fault contents 3 Fault contents 3
2 00C0H bit 0 Reserved
3 00C0H bit 1 Undervoltage (Uv1)
4 00C0H bit 2 Control Power Supply Undervoltage (Uv2)
5 00C0H bit 3 Soft Charge Circuit Fault (Uv3)
6 00C0H bit 4 IGBT Short Circuit or Ground Fault (SC)
7 00C0H bit 5 Ground Fault (GF)
8 00C0H bit 6 Overcurrent (oC)
9 00C0H bit 7 Overvoltage (ov)
10 00C0H bit 8 Heatsink Overheat (oH)
11 00C0H bit 9 Heatsink Overheat (oH1)
12 00C0H bit A Motor Overload (oL1)
13 00C0H bit B Drive Overload (oL2)
14 00C0H bit C Overtorque Detection 1 (oL3)
15 00C0H bit D Overtorque Detection 2 (oL4)
16 00C0H bit E Dynamic Braking Transistor Fault (rr)
17 00C0H bit F Braking Resistor Overheat (rH)
18 00C1H Fault contents 4 Fault contents 4
19 00C1H bit 0 External Fault at input terminal S3 (EF3)
20 00C1H bit 1 External Fault at input terminal S4 (EF4)
21 00C1H bit 2 External Fault at input terminal S5 (EF5)
22 00C1H bit 3 External Fault at input terminal S6 (EF6)
23 00C1H bit 4 External Fault at input terminal S7 (EF7)
24 00C1H bit 5 to 6 Reserved
25 00C1H bit 7 Overspeed (oS)
26 00C1H bit 8 Excessive Speed Deviation (dEv)
27 00C1H bit 9 PG Disconnected (PGo)
28 00C1H bit A Input Phase Loss (PF)
29 00C1H bit B Output Phase Loss (LF)
30 00C1H bit C Motor Overheat Alarm (PTC input) (oH3)
31 00C1H bit D Digital Operator Connection Fault (oPr)
32 00C1H bit E EEPROM Write Error (Err)
33 00C1H bit F Motor Overheat Fault (PTC input) (oH4)
34 00C2H Fault contents 5 Fault contents 5
35 00C2H bit 0 MEMOBUS/Modbus Communication Error (CE)
36 00C2H bit 1 Option Communication Error (bUS)
37 00C2H bit 2 to 3 Reserved
38 00C2H bit 4 Control Fault (CF)
39 00C2H bit 5 Reserved
40 00C2H bit 6 Option External Fault (EF0)
41 00C2H bit 7 PID Feedback Loss (FbL)
42 00C2H bit 8 Undertorque Detection 1 (UL3)
43 00C2H bit 9 Undertorque Detection 2 (UL4)
44 00C2H bit A High Slip Braking Overload (oL7)
45 00C2H bit B to E Reserved
46 00C2H bit F Hardware fault (includes oFA□□)

Manual — Fault contents6–7 and alarm2 — page 454

Source reference: SIEP C71060618F, December 2016, physical PDF page 454. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Register No. Contents

C.10 MEMOBUS/Modbus Data Table

00C3H | Fault contents 6

00C3H | bit 0 to 4

00C3H | bit 5

00C3H | bit 6

00C3H | bit 7

00C3H | bit 8

00C3H | bit 9

00C3H | bit A

00C3H | bit B to F

00C4H | Fault contents 7

00C4H | bit 0

00C4H | bit 1

00C4H | bit 2

00C4H | bit 3

00C4H | bit 4

00C4H | bit 5

00C4H | bit 6

00C4H | bit 7

00C4H | bit 8

00C4H | bit 9 to F

00C8H | Alarm contents 2

00C8H | bit 0

00C8H | bit 1

00C8H | bit 2

00C8H | bit 3

00C8H | bit 4

00C8H | bit 5

00C8H | bit 6

00C8H | bit 7

00C8H | bit 8

00C8H | bit 9

00C8H | bit A

00C8H | bit B

00C8H | bit C

00C8H | bit D, E

00C8H | bit F

C10 read-only monitor register and bit map — PDF page 454

Source row Register number hex Bit / subitem / merged contents Contents
1 00C3H Fault contents 6 Fault contents 6
2 00C3H bit 0 to 4 Reserved
3 00C3H bit 5 Output Current Imbalance (LF2)
4 00C3H bit 6 Pullout Detection (STo)
5 00C3H bit 7 PG Disconnected (PGo)
6 00C3H bit 8 MECHATROLINK Watchdog Timer Error (E5)
7 00C3H bit 9 Reserved
8 00C3H bit A Too many speed search restarts (SEr)
9 00C3H bit B to F Reserved
10 00C4H Fault contents 7 Fault contents 7
11 00C4H bit 0 PID Feedback Loss (FbH)
12 00C4H bit 1 External Fault 1, input terminal S1 (EF1)
13 00C4H bit 2 External Fault 2, input terminal S2 (EF2)
14 00C4H bit 3 Mechanical Weakening Detection 1 (oL5)
15 00C4H bit 4 Mechanical Weakening Detection 2 (UL5)
16 00C4H bit 5 Current Offset Fault (CoF)
17 00C4H bit 6 Reserved
18 00C4H bit 7 Reserved
19 00C4H bit 8 DriveWorksEZ fault (dWFL)
20 00C4H bit 9 to F Reserved
21 00C8H Alarm contents 2 Alarm contents 2
22 00C8H bit 0 Undervoltage (Uv)
23 00C8H bit 1 Overvoltage (ov)
24 00C8H bit 2 Heatsink Overheat (oH)
25 00C8H bit 3 Drive Overheat (oH2)
26 00C8H bit 4 Overtorque 1 (oL3)
27 00C8H bit 5 Overtorque 2 (oL4)
28 00C8H bit 6 Run Commands Input Error (EF)
29 00C8H bit 7 Drive Baseblock (bb)
30 00C8H bit 8 External Fault 3, input terminal S3 (EF3)
31 00C8H bit 9 External Fault 4, input terminal S4 (EF4)
32 00C8H bit A External Fault 5, input terminal S5 (EF5)
33 00C8H bit B External Fault 6, input terminal S6 (EF6)
34 00C8H bit C External Fault 7, input terminal S7 (EF7)
35 00C8H bit D, E Reserved
36 00C8H bit F Overspeed (oS)

Manual — Alarm contents3–5 — page 455

Source reference: SIEP C71060618F, December 2016, physical PDF page 455. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Register No. Contents

C.10 MEMOBUS/Modbus Data Table

C

MEMOBUS/Modbus Communications

00C9H | Alarm contents 3

00C9H | bit 0

00C9H | bit 1

00C9H | bit 2

00C9H | bit 3

00C9H | bit 4

00C9H | bit 5

00C9H | bit 6

00C9H | bit 7

00C9H | bit 8

00C9H | bit 9

00C9H | bit A

00C9H | bit B

00C9H | bit C

00C9H | bit D

00C9H | bit E

00C9H | bit F

00CAH | Alarm contents 4

00CAH | bit 0

00CAH | bit 1

00CAH | bit 2 to 5

00CAH | bit 6

00CAH | bit 7

00CAH | bit 9

00CAH | bit A to F

00CBH | Alarm contents 5

00CBH | bit 0

00CBH | bit 1

00CBH | bit 2

00CBH | bit 3

00CBH | bit 4

00CBH | bit 5

00CBH | bit 6

00CBH | bit 7

00CBH | bit 8

00CBH | bit 9

00CBH | bit A

00CBH | bit B

00CBH | bit C

00CBH | bit D

00CBH | bit E to F

C10 read-only monitor register and bit map — PDF page 455

Source row Register number hex Bit / subitem / merged contents Contents
1 00C9H Alarm contents 3 Alarm contents 3
2 00C9H bit 0 Excessive Speed Deviation (dEv)
3 00C9H bit 1 PG Disconnected (PGo)
4 00C9H bit 2 Digital Operator Connection Fault (oPr)
5 00C9H bit 3 MEMOBUS/Modbus Communication Error (CE)
6 00C9H bit 4 Option Communication Error (bUS)
7 00C9H bit 5 Serial Communication Transmission Error (CALL)
8 00C9H bit 6 Motor Overload (oL1)
9 00C9H bit 7 Drive Overload (oL2)
10 00C9H bit 8 Reserved
11 00C9H bit 9 Option Card External fault (EF0)
12 00C9H bit A Motor 2 Switch command input during run (rUn)
13 00C9H bit B Reserved
14 00C9H bit C Serial Communication Transmission Error (CALL)
15 00C9H bit D Undertorque Detection 1 (UL3)
16 00C9H bit E Undertorque Detection 2 (UL4)
17 00C9H bit F MEMOBUS/Modbus Test Mode Fault (SE)
18 00CAH Alarm contents 4 Alarm contents 4
19 00CAH bit 0 Reserved
20 00CAH bit 1 Motor Overheat 1 (PTC Input) (oH3)
21 00CAH bit 2 to 5 Reserved
22 00CAH bit 6 PID Feedback Loss (FbL)
23 00CAH bit 7 PID Feedback Loss (FbH)
24 00CAH bit 9 Drive Disabled (dnE)
25 00CAH bit A to F Reserved
26 00CBH Alarm contents 5 Alarm contents 5
27 00CBH bit 0 MECHATROLINK Watchdog Timer Error (E5)
28 00CBH bit 1 Reserved
29 00CBH bit 2 MECHATROLINK Comm. Cycle Setting Error (CyC)
30 00CBH bit 3 High Current Alarm (HCA)
31 00CBH bit 4 Cooling Fan Maintenance Time (LT-1)
32 00CBH bit 5 Soft Charge Bypass Relay Maintenance Time (LT-2)
33 00CBH bit 6 Reserved
34 00CBH bit 7 SI-S/V EEPROM Error (EEP)
35 00CBH bit 8 External Fault 1 (input terminal S1) (EF1)
36 00CBH bit 9 External Fault 2 (input terminal S2) (EF2)
37 00CBH bit A Safe Disable Input (HbbF)
38 00CBH bit B Safe Disable Input (Hbb)
39 00CBH bit C Mechanical Weakening Detection 1 (oL5)
40 00CBH bit D Mechanical Weakening Detection 2 (UL5)
41 00CBH bit E to F Reserved

Manual — Control and option fault bits; register footnotes — page 456

Source reference: SIEP C71060618F, December 2016, physical PDF page 456. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Register No. Contents

<1> Units are determined by parameter o1-03. <2> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. <3> The communication error log is stored until the fault is reset. <4> Depending on the motor used the correct motor pole number must be set to parameter E2-04, E4-04 or E5-05. <5> Available in drive software versions PRG: 1011 and later.

C.10 MEMOBUS/Modbus Data Table

00D0H | CPF Contents 1

00D0H | bit 0 to 1

00D0H | bit 2

00D0H | bit 3

00D0H | bit 4 to 5

00D0H | bit 6

00D0H | bit 7

00D0H | bit 8

00D0H | bit 9 to A

00D0H | bit B

00D0H | bit C

00D0H | bit D

00D0H | bit E

00D0H | bit F

00D1H | CPF Contents 2

00D1H | bit 0

00D1H | bit 1

00D1H | bit 2

00D1H | bit 3

00D1H | bit 4

00D1H | bit 5

00D1H | bit 6

00D1H | bit 7

00D1H | bit 8

00D1H | bit 9

00D1H | bit A to F

00D8H | Option Card Fault Contents

00D8H | bit 0

00D8H | bit 1

00D8H | bit 3

00D8H | bit 4

00D8H | bit 5 to F

00FBH | Output Current <2>

C10 read-only monitor register and bit map — PDF page 456

Source row Register number hex Bit / subitem / merged contents Contents
1 00D0H CPF Contents 1 CPF Contents 1
2 00D0H bit 0 to 1 Reserved
3 00D0H bit 2 A/D Conversion Error (CPF02)
4 00D0H bit 3 PWM Data Fault (CPF03)
5 00D0H bit 4 to 5 Reserved
6 00D0H bit 6 Drive specification mismatch during Terminal Board or Control Board replacement (CPF06)
7 00D0H bit 7 Terminal Board Communications Fault (CPF07)
8 00D0H bit 8 EEPROM Serial Communications Fault (CPF08)
9 00D0H bit 9 to A Reserved
10 00D0H bit B RAM Fault (CPF11)
11 00D0H bit C FLASH Memory Fault (CPF12)
12 00D0H bit D Watchdog Circuit Exception (CPF13)
13 00D0H bit E Control Circuit Fault (CPF14)
14 00D0H bit F Reserved
15 00D1H CPF Contents 2 CPF Contents 2
16 00D1H bit 0 Clock Fault (CPF16)
17 00D1H bit 1 Timing Fault (CPF17)
18 00D1H bit 2 Control Circuit Fault (CPF18)
19 00D1H bit 3 Control Circuit Fault (CPF19)
20 00D1H bit 4 Hardware fault at power up (CPF20)
21 00D1H bit 5 Hardware fault at communication start up (CPF21)
22 00D1H bit 6 A/D Conversion Fault (CPF22)
23 00D1H bit 7 PWM Feedback Fault (CPF23)
24 00D1H bit 8 Drive capacity signal fault (CPF24)
25 00D1H bit 9 Terminal board is not properly connected (CPF25)
26 00D1H bit A to F Reserved
27 00D8H Option Card Fault Contents Option Card Fault Contents
28 00D8H bit 0 Option Compatibility Error (oFA00)
29 00D8H bit 1 Option not properly connected (oFA01)
30 00D8H bit 3 Option Self-diagnostics Error (oFA03)
31 00D8H bit 4 Option Flash Write Mode Error (oFA04)
32 00D8H bit 5 to F Reserved
33 00FBH Output Current <2> Output Current <2>

Manual — Broadcast and fault trace codes — page 457

Source reference: SIEP C71060618F, December 2016, physical PDF page 457. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ Broadcast Messages

Data can be written from the master to all slave devices at the same time. The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not respond.

Register No. Contents

◆ Fault Trace Contents

The table below shows the fault codes that can be read out by MEMOBUS/Modbus commands from the U2-□□ monitor parameters.

Note: Uv1 and Uv2 faults are not saved to the fault history.

Table C.4 Fault Trace / History Register Contents

Fault Code Fault Name

C.10 MEMOBUS/Modbus Data Table

C

MEMOBUS/Modbus Communications

0001H | Digital Input Command

0001H | bit 0

0001H | bit 1

0001H | bit 2, 3

0001H | bit 4

0001H | bit 5

0001H | bit 6 to B

0001H | bit C

0001H | bit D

0001H | bit E

0001H | bit F

0002H | Frequency Reference

0002H | Undervoltage (Uv1)

0003H | Control Power Supply Undervoltage (Uv2)

0004H | Soft Charge Circuit Fault (Uv3)

0005H <1> | IGBT Short Circuit (SC)

0006H | Ground Fault (GF)

0007H | Overcurrent (oC)

0008H | Overvoltage (ov)

0009H | Heatsink Overheat (oH)

000AH | Heatsink Overheat (oH1)

000BH | Motor Overload (oL1)

000CH | Drive Overload (oL2)

000DH | Overtorque Detection 1 (oL3)

000EH | Overtorque Detection 2 (oL4)

000FH | Dynamic Braking Transistor (rr)

0010H | Braking Resistor Overheat (rH)

0011H | External Fault at input terminal S3 (EF3)

0012H | External Fault at input terminal S4 (EF4)

0013H | External Fault at input terminal S5 (EF5)

0014H | External Fault at input terminal S6 (EF6)

0015H | External Fault at input terminal S7 (EF7)

0018H | Overspeed (oS)

0019H | Excessive Speed Deviation (dEv)

001AH | PG Disconnect (PGo)

001BH | Input Phase Loss (PF)

001CH | Output Phase Loss (LF)

001DH | Motor Overheat (PTC input) (oH3)

001EH | Digital Operator Connection (oPr)

001FH | EEPROM Write Error (Err)

0020H | Motor Overheat (PTC input) (oH4)

0021H | MEMOBUS/Modbus Communication Error (CE)

0022H | Option Communication Error (bUS)

0025H | Control fault (CF)

0027H | PROFIBUS-DP Option External Fault (EF0)

0028H | PID Feedback Loss (FbL)

0029H | Undertorque Detection 1 (UL3)

002AH | Undertorque Detection 2 (UL4)

002BH | High Slip Braking Overload (oL7)

0030H | Hardware Fault (including oFx)

0036H | Output Current Imbalance (LF2)

0037H | Pullout Detection (Sto)

0038H | PG Disconnected (PGo)

0039H | MECHATROLINK Watchdog Timer Error (E5)

003BH | Too many speed search restarts (SEr)

0041H | PID Feedback Loss (FbH)

0042H | External Fault 1, input terminal S1 (EF1)

0043H | External Fault 2, input terminal S2 (EF2)

0044H | Mechanical Weakening Detection 1 (oL5)

0045H | Mechanical Weakening Detection 2 (UL5)

0046H | Current Offset Fault (CoF)

0049H | DriveWorksEZ Fault (dWFL)

0083H | A/D Conversion Error (CPF02)

Broadcast command registers — PDF page 457

Source row Register number hex Bit / subitem / merged contents Contents
1 0001H Digital Input Command Digital Input Command
2 0001H bit 0 Forward Run (0: Stop 1: Run)
3 0001H bit 1 Direction Command (0: Forward, 1: Reverse)
4 0001H bit 2, 3 Reserved
5 0001H bit 4 External Fault
6 0001H bit 5 Fault Reset
7 0001H bit 6 to B Reserved
8 0001H bit C Multi-Function Digital Input S5 (enabled when bit C of register 000FH is on)
9 0001H bit D Multi-Function Digital Input S6 (enabled when bit D of register 000FH is on)
10 0001H bit E Multi-Function Digital Input S7 (enabled when bit E of register 000FH is on)
11 0001H bit F Reserved
12 0002H Frequency Reference 30000/100%

C4 fault trace/history column 1 — PDF page 457

Source row Code hex Name
1 0002H Undervoltage (Uv1)
2 0003H Control Power Supply Undervoltage (Uv2)
3 0004H Soft Charge Circuit Fault (Uv3)
4 0005H <1> IGBT Short Circuit (SC)
5 0006H Ground Fault (GF)
6 0007H Overcurrent (oC)
7 0008H Overvoltage (ov)
8 0009H Heatsink Overheat (oH)
9 000AH Heatsink Overheat (oH1)
10 000BH Motor Overload (oL1)
11 000CH Drive Overload (oL2)
12 000DH Overtorque Detection 1 (oL3)
13 000EH Overtorque Detection 2 (oL4)
14 000FH Dynamic Braking Transistor (rr)
15 0010H Braking Resistor Overheat (rH)
16 0011H External Fault at input terminal S3 (EF3)
17 0012H External Fault at input terminal S4 (EF4)
18 0013H External Fault at input terminal S5 (EF5)
19 0014H External Fault at input terminal S6 (EF6)
20 0015H External Fault at input terminal S7 (EF7)
21 0018H Overspeed (oS)
22 0019H Excessive Speed Deviation (dEv)
23 001AH PG Disconnect (PGo)
24 001BH Input Phase Loss (PF)
25 001CH Output Phase Loss (LF)

C4 fault trace/history column 2 — PDF page 457

Source row Code hex Name
1 001DH Motor Overheat (PTC input) (oH3)
2 001EH Digital Operator Connection (oPr)
3 001FH EEPROM Write Error (Err)
4 0020H Motor Overheat (PTC input) (oH4)
5 0021H MEMOBUS/Modbus Communication Error (CE)
6 0022H Option Communication Error (bUS)
7 0025H Control fault (CF)
8 0027H PROFIBUS-DP Option External Fault (EF0)
9 0028H PID Feedback Loss (FbL)
10 0029H Undertorque Detection 1 (UL3)
11 002AH Undertorque Detection 2 (UL4)
12 002BH High Slip Braking Overload (oL7)
13 0030H Hardware Fault (including oFx)
14 0036H Output Current Imbalance (LF2)
15 0037H Pullout Detection (Sto)
16 0038H PG Disconnected (PGo)
17 0039H MECHATROLINK Watchdog Timer Error (E5)
18 003BH Too many speed search restarts (SEr)
19 0041H PID Feedback Loss (FbH)
20 0042H External Fault 1, input terminal S1 (EF1)
21 0043H External Fault 2, input terminal S2 (EF2)
22 0044H Mechanical Weakening Detection 1 (oL5)
23 0045H Mechanical Weakening Detection 2 (UL5)
24 0046H Current Offset Fault (CoF)
25 0049H DriveWorksEZ Fault (dWFL)
26 0083H A/D Conversion Error (CPF02)

Manual — Fault trace continuation and alarm codes — page 458

Source reference: SIEP C71060618F, December 2016, physical PDF page 458. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Fault Code Fault Name

<1> Available in drive software versions PRG: 1020 and later.

◆ Alarm Register Contents

The table below shows the alarm codes that can be read out from MEMOBUS/Modbus register 007FH.

Table C.5 Alarm Register 007FH Contents

Alarm Code Fault Name

C.10 MEMOBUS/Modbus Data Table

0084H | PWM Data Fault (CPF03)

0087H | Drive specification mismatch during Terminal Board or Control Board replacement (CPF06)

0088H | Terminal Board Communication Fault (CPF07)

0089H | EEPROM Serial Communication Fault (CPF08)

008CH | RAM fault (CPF11)

008DH | Flash memory circuit exception (CPF12)

008EH | Watchdog circuit exception (CPF13)

008FH | Control Circuit Fault (CPF14)

0091H | Clock Fault (CPF16)

0092H | Timing Fault (CPF17)

0093H | Control Circuit Fault (CPF18)

0094H | Control Circuit Fault (CPF19)

0095H | Hardware fault at power up (CPF20)

0096H | Hardware fault at communication start up (CPF21)

0097H | A/D Conversion Fault (CPF22)

0098H | PWM Feedback Fault (CPF23)

0099H | Drive capacity signal fault (CPF24)

0101H | Option compatibility error (oFA00)

0102H | Option not properly connected (oFA01)

0104H | Option Self-diagnostics Error (oFA03)

0105H | Option Flash Write Mode Error (oFA04)

0001H | Undervoltage (Uv)

0002H | Overvoltage (ov)

0003H | Heatsink Overheat (oH)

0004H | Drive Overheat (oH2)

0005H | Overtorque 1 (oL3)

0006H | Overtorque 2 (oL4)

0007H | Run commands input error (EF)

0008H | Drive Baseblock (bb)

0009H | External Fault 3, input terminal S3 (EF3)

000AH | External Fault 4, input terminal S4 (EF4)

000BH | External Fault 5, input terminal S5 (EF5)

000CH | External Fault 6, input terminal S6 (EF6)

000DH | External Fault 7, input terminal S7 (EF7)

000FH | Reserved

0010H | Overspeed (oS)

0011H | Excessive Speed Deviation (dEv)

0012H | PG Disconnected (PGo)

0013H | Digital operator connection fault (oPr)

0014H | MEMOBUS/Modbus Communication Error (CE)

0015H | Option Communication Error (bUS)

0016H | Serial Communication Transmission Error (CALL)

0017H | Motor Overload (oL1)

0018H | Drive Overload (oL2)

001AH | Option Card External Fault (EF0)

001BH | Motor Switch command input during run (rUn)

001DH | Serial Communication Transmission Error (CALL)

001EH | Undertorque Detection 1 (UL3)

001FH | Undertorque Detection 2 (UL4)

0020H | MEMOBUS/Modbus Test Mode Fault (SE)

0022H | Motor Overheat (oH3)

0027H | PID Feedback Loss (FbL)

0028H | PID Feedback Loss (FbH)

002AH | Drive Disabled (dnE)

002BH | PG Disconnected (PGo)

0031H | MECHATROLINK Watchdog Timer Error (E5)

0032H | Station Address Setting Error (AEr)

0033H | MECHATROLINK Comm. Cycle Setting Error (CyC)

0034H | High Current Alarm (HCA)

0039H | External Fault (input terminal S1) (EF1)

003AH | External Fault (input terminal S2) (EF2)

003BH | Safe Disable Input (HbbF)

003CH | Safe Disable Input (Hbb)

003DH | Mechanical Weakening Detection 1 (oL5)

003EH | Mechanical Weakening Detection 2 (UL5)

0049H | DriveWorksEZ Alarm (dWAL)

C4 fault trace/history column 0 — PDF page 458

Source row Code hex Name
1 0084H PWM Data Fault (CPF03)
2 0087H Drive specification mismatch during Terminal Board or Control Board replacement (CPF06)
3 0088H Terminal Board Communication Fault (CPF07)
4 0089H EEPROM Serial Communication Fault (CPF08)
5 008CH RAM fault (CPF11)
6 008DH Flash memory circuit exception (CPF12)
7 008EH Watchdog circuit exception (CPF13)
8 008FH Control Circuit Fault (CPF14)
9 0091H Clock Fault (CPF16)
10 0092H Timing Fault (CPF17)
11 0093H Control Circuit Fault (CPF18)

C4 fault trace/history column 1 — PDF page 458

Source row Code hex Name
1 0094H Control Circuit Fault (CPF19)
2 0095H Hardware fault at power up (CPF20)
3 0096H Hardware fault at communication start up (CPF21)
4 0097H A/D Conversion Fault (CPF22)
5 0098H PWM Feedback Fault (CPF23)
6 0099H Drive capacity signal fault (CPF24)
7 0101H Option compatibility error (oFA00)
8 0102H Option not properly connected (oFA01)
9 0104H Option Self-diagnostics Error (oFA03)
10 0105H Option Flash Write Mode Error (oFA04)

C5 alarm register007FH column 2 — PDF page 458

Source row Code hex Name
1 0001H Undervoltage (Uv)
2 0002H Overvoltage (ov)
3 0003H Heatsink Overheat (oH)
4 0004H Drive Overheat (oH2)
5 0005H Overtorque 1 (oL3)
6 0006H Overtorque 2 (oL4)
7 0007H Run commands input error (EF)
8 0008H Drive Baseblock (bb)
9 0009H External Fault 3, input terminal S3 (EF3)
10 000AH External Fault 4, input terminal S4 (EF4)
11 000BH External Fault 5, input terminal S5 (EF5)
12 000CH External Fault 6, input terminal S6 (EF6)
13 000DH External Fault 7, input terminal S7 (EF7)
14 000FH Reserved
15 0010H Overspeed (oS)
16 0011H Excessive Speed Deviation (dEv)
17 0012H PG Disconnected (PGo)
18 0013H Digital operator connection fault (oPr)
19 0014H MEMOBUS/Modbus Communication Error (CE)
20 0015H Option Communication Error (bUS)
21 0016H Serial Communication Transmission Error (CALL)
22 0017H Motor Overload (oL1)
23 0018H Drive Overload (oL2)

C5 alarm register007FH column 3 — PDF page 458

Source row Code hex Name
1 001AH Option Card External Fault (EF0)
2 001BH Motor Switch command input during run (rUn)
3 001DH Serial Communication Transmission Error (CALL)
4 001EH Undertorque Detection 1 (UL3)
5 001FH Undertorque Detection 2 (UL4)
6 0020H MEMOBUS/Modbus Test Mode Fault (SE)
7 0022H Motor Overheat (oH3)
8 0027H PID Feedback Loss (FbL)
9 0028H PID Feedback Loss (FbH)
10 002AH Drive Disabled (dnE)
11 002BH PG Disconnected (PGo)
12 0031H MECHATROLINK Watchdog Timer Error (E5)
13 0032H Station Address Setting Error (AEr)
14 0033H MECHATROLINK Comm. Cycle Setting Error (CyC)
15 0034H High Current Alarm (HCA)
16 0039H External Fault (input terminal S1) (EF1)
17 003AH External Fault (input terminal S2) (EF2)
18 003BH Safe Disable Input (HbbF)
19 003CH Safe Disable Input (Hbb)
20 003DH Mechanical Weakening Detection 1 (oL5)
21 003EH Mechanical Weakening Detection 2 (UL5)
22 0049H DriveWorksEZ Alarm (dWAL)

Manual — Enter commands and H5-11 behavior — page 459

Source reference: SIEP C71060618F, December 2016, physical PDF page 459. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.11 Enter Command

When writing parameters to the drive from the PLC using MEMOBUS/Modbus communication it depends on the setting of parameter H5-11 if an Enter command must be used to enable these parameters or not. This sections explains Enter commands.

◆ Enter Command Types

The drive supports two types of Enter commands as shown in Table C.6. An Enter command is enabled by writing 0 to register number 0900H or 0910H. These registers can be written to only. An error will occur if the user attempts to read from these registers.

Table C.6 Enter Command Types

Register No. Description

Note: 1. Because the EEPROM can be written to a maximum of 100,000 times, refrain from writing to the EEPROM too often. The Enter command registers are write-only. Consequently, if these registers are read, then the register address will be invalid (Error code: 02H). An Enter command is not required if reference or broadcast data are sent to the drive. 2. Parameter data cannot be written to EEPROM during undervoltage, even using 0900H. 3. If undervoltage occurs when a making several parameter changes issued with a single ENTER command, the writing process may be aborted before all of the new changes have been written. Because all of the data has not yet been written, the EEPROM data error “CPF06” will be displayed the next time power to the drive is cycled. To prevent this problem, wait approximately 5 seconds after issuing the ENTER command before shutting off drive power.

◆ Enter Command Settings when Upgrading the Drive

When replacing earlier Yaskawa drive models with a V1000 and keeping the MEMOBUS/Modbus communications settings, parameter H5-11 needs to be set in accordance with how the Enter command functions in the older drive. H5-11 determines if an Enter command is needed to activate parameter changes in the drive. • Set H5-11 to 0 when upgrading from a G7 or F7 series drive to V1000 series drive. • Set H5-11 to 1 when upgrading from a V7 series drive to V1000 series drive.

■ H5-11 and the Enter Command

H5-11 Settings H5-11 = 0 H5-11 = 1

C

MEMOBUS/Modbus Communications

0900H | Writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM at the same time. Parameter changes remain even if the power supply is cycled.

0910H | Writes data in the RAM only. Parameter changes are lost when the drive is shut off.

Drive being replaced | G7, F7

How parameter settings are enabled | When the Enter command is received from the master.

Upper/lower limit check | Upper/lower limit check takes the settings of related parameters into account.

Default value of related parameters | Not affected. The settings of related parameters remain unchanged. They must be changed manually if needed.

Error handling when setting multiple parameters | Data is accepted even if one setting is invalid. The invalid setting will be discarded. No error message occurs.

C6 Enter command types — PDF page 459

Source row Register hex Description
1 0900H Writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM at the same time. Parameter changes remain even if the power supply is cycled.
2 0910H Writes data in the RAM only. Parameter changes are lost when the drive is shut off.

H5-11 Enter command behavior comparison — PDF page 459

Source row H5-11 behavior H5-11=0 H5-11=1
1 Drive being replaced G7, F7 V7
2 How parameter settings are enabled When the Enter command is received from the master. As soon as the value is changed.
3 Upper/lower limit check Upper/lower limit check takes the settings of related parameters into account. The upper/lower limit of the changed parameter is checked only.
4 Default value of related parameters Not affected. The settings of related parameters remain unchanged. They must be changed manually if needed. The default settings of related parameters are changed automatically.
5 Error handling when setting multiple parameters Data is accepted even if one setting is invalid. The invalid setting will be discarded. No error message occurs. Error occurs if only one setting is invalid. All data sent are discarded.

Manual — Communication errors and no-response conditions — page 460

Source reference: SIEP C71060618F, December 2016, physical PDF page 460. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.12 Communication Errors

◆ MEMOBUS/Modbus Error Codes

A list of MEMOBUS/Modbus errors appears below. When an error occurs, remove whatever caused the error and restart communications.

Error Name Error Code

Cause

◆ Slave Not Responding

In the following situations, the slave drive will ignore the command message sent from the master, and not send a response message: • When a communications error (overrun, framing, parity or CRC-16) is detected in the command message. • When the slave address in the command message and the slave address in the drive do not match (remember to set the slave address for the drive using H5-01). • When the gap between two blocks (8 bit) of a message exceeds 24 bits. • When the command message data length is invalid.

Note: If the slave address specified in the command message is 00H, all slaves execute the write function, but do not return response messages to the master.

01H | Function Code Error

01H | • Attempted to set a function code from a PLC other than 03H, 08H, and 10H.

02H | Register Number Error

02H | • A register number specified in the command message does not exist. • Attempted to send a broadcast message using other register numbers than 0001H or 0002H.

03H | Bit Count Error

03H | • Read data or write data is greater than 16 bits. Invalid command message quantity. • In a write message, the “Number of Data Items” contained within the message does not equal twice the amount of data words (i.e., the total of Data 1+ Data 2, etc.).

21H | Data Setting Error

21H | • Control data or parameter write data is outside the allowable setting range. • Attempted to write a contradictory parameter setting.

22H | Write Mode Error

22H | • Attempted to write while the drive was operating to a parameter that cannot be written to during run. • During an EEPROM data error (CPF06), the master attempted to write to a parameter other than A1-00 to -05, E1-03, or o2-04. • Attempted to write to read-only data.

23H | DC Bus Undervoltage Write Error

23H | • Attempted to write from the master during an undervoltage fault (Uv1). • Attempted to execute and Enter command during Uv1.

24H | Write Error During Parameter Process

24H | • Master attempted writing to the drive while the drive was processing parameter data.

MEMOBUS/Modbus error codes and causes — PDF page 460

Source row Error code hex Error name / cause
1 01H Function Code Error
2 01H • Attempted to set a function code from a PLC other than 03H, 08H, and 10H.
3 02H Register Number Error
4 02H • A register number specified in the command message does not exist. • Attempted to send a broadcast message using other register numbers than 0001H or 0002H.
5 03H Bit Count Error
6 03H • Read data or write data is greater than 16 bits. Invalid command message quantity. • In a write message, the “Number of Data Items” contained within the message does not equal twice the amount of data words (i.e., the total of Data 1+ Data 2, etc.).
7 21H Data Setting Error
8 21H • Control data or parameter write data is outside the allowable setting range. • Attempted to write a contradictory parameter setting.
9 22H Write Mode Error
10 22H • Attempted to write while the drive was operating to a parameter that cannot be written to during run. • During an EEPROM data error (CPF06), the master attempted to write to a parameter other than A1-00 to -05, E1-03, or o2-04. • Attempted to write to read-only data.
11 23H DC Bus Undervoltage Write Error
12 23H • Attempted to write from the master during an undervoltage fault (Uv1). • Attempted to execute and Enter command during Uv1.
13 24H Write Error During Parameter Process
14 24H • Master attempted writing to the drive while the drive was processing parameter data.

Manual — Communication self-diagnostics and safety — page 461

Source reference: SIEP C71060618F, December 2016, physical PDF page 461. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

C.13 Self-Diagnostics

The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosis function, use the following procedure.

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level. 1. Turn on the power to the drive. 2. Note the present terminal S6 function selection setting (H1-06) and set it for the communications test mode (H1-06 = 67). 3. Turn off the power to the drive. 4. With the power off, wire the drive as shown in the following figure:

Figure C.9 Terminal Connections for Communication Self-Diagnostics

  1. Check and note the setting of DIP switch S3. Set it to NPN if it is in the PNP position. 6. Turn the power to the drive back on. 7. During normal operation, the drive will display PASS. This indicates that the communications test mode is operating normally.

When a fault occurs, the drive will display “CE” on the keypad display. 8. Turn off the power supply. 9. Remove the wire jumpers from terminal R+, R-, S+, S- and, S6-SC and set back DIP switch S3 to its original position. Set terminal S6 to its original function. 10.Return to normal operation.

C

MEMOBUS/Modbus Communications

Figure C.9 enlarged terminal labels: R+, R−, S+, S−, IG; P1, P2, PC, A1, A2, +V, AC, AM, AC, MP; S1, S2, S3, S4, S5, S6, S7, HC, SC, H1, RP. Exact jumper paths and board geometry remain original-only. Follow complete numbered self-diagnostics procedure and safety; this text is not a wiring substitute.

Manual — Standards section safety — page 464

Source reference: SIEP C71060618F, December 2016, physical PDF page 464. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

D.1 Section Safety

DANGER

Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.

WARNING

Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes, 240 Vac maximum (200 V class) and 480 Vac maximum (400 V class) when protected by branch circuit protection devices specified in this manual.

Manual — Standards section notices — page 465

Source reference: SIEP C71060618F, December 2016, physical PDF page 465. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

NOTICE

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting other devices. Failure to comply could result in damage to the drive.

D.1 Section Safety

D

Standards Compliance

Manual — European standards and AC branch fuses — page 466

Source reference: SIEP C71060618F, December 2016, physical PDF page 466. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

D.2 European Standards

Figure D.1 CE Mark

The CE mark indicates compliance with European safety and environmental regulations and is required for engaging in business and commerce in Europe. European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics manufacturers and the EMC guidelines for controlling noise. This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive. • Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE standards. After setting up the device, verify that conditions meet European standards. • Low Voltage Directive: 73/23/EEC, 93/68/EEC

◆ CE Low Voltage Directive Compliance

This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage Directive. To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other devices:

■ Area of Use

Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.

■ Factory Recommended Branch Circuit Protection

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in Table D.1.

NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.

Table D.1 Factory Recommended Drive Branch Circuit Protection

Drive Model

Fuse Type

Manufacturer: Bussmann

Model Fuse Ampere Rating (A)

Figure D.1 CE mark. Graphic logo only; no inference of current certification validity.

Single-Phase 200 V Class | Single-Phase 200 V Class

BA0001 | FWH-25A14F

BA0002 | FWH-25A14F

BA0003 | FWH-60B

BA0006 | FWH-80B

BA0010 | FWH-100B

BA0012 | FWH-125B

BA0018 | FWH-175B

Three-Phase 200 V Class | Three-Phase 200 V Class

2A0001 | FWH-25A14F

2A0002 | FWH-25A14F

2A0004 | FWH-25A14F

2A0006 | FWH-25A14F

2A0010 | FWH-70B

2A0012 | FWH-70B

2A0020 | FWH-90B

2A0030 | FWH-100B

D1 Bussmann AC branch protection — 466 — PDF page 466

Source row Drive model or phase class Bussmann fuse model Fuse ampere rating (A)
1 Single-Phase 200 V Class Single-Phase 200 V Class Single-Phase 200 V Class
2 BA0001 FWH-25A14F 25
3 BA0002 FWH-25A14F 25
4 BA0003 FWH-60B 60
5 BA0006 FWH-80B 80
6 BA0010 FWH-100B 100
7 BA0012 FWH-125B 125
8 BA0018 FWH-175B 175
9 Three-Phase 200 V Class Three-Phase 200 V Class Three-Phase 200 V Class
10 2A0001 FWH-25A14F 25
11 2A0002 FWH-25A14F 25
12 2A0004 FWH-25A14F 25
13 2A0006 FWH-25A14F 25
14 2A0010 FWH-70B 70
15 2A0012 FWH-70B 70
16 2A0020 FWH-90B 90
17 2A0030 FWH-100B 100

Manual — AC fuses continuation and DC input conditions — page 467

Source reference: SIEP C71060618F, December 2016, physical PDF page 467. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive Model

Fuse Type

Manufacturer: Bussmann

Model Fuse Ampere Rating (A)

■ Grounding

The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded systems, contact your dealer or Yaskawa for instructions.

■ CE Standards Compliance for DC Power Supply Input

Install the fuses in the following tables to meet CE standards.

Figure D.2 Example of DC Power Supply Input (Two Drives Connected in Series)

Note: 1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows. 2. Refer to on page 50 for an AC power supply. 3. The recommended fuses and fuse holders are made by Fuji Electric.

D.2 European Standards

D

Standards Compliance

Figure D.2 labels: DC power supply (converter); plus/minus; two Fuse labels; two Drive blocks with +1 and minus, outputs U/T1, V/T2, W/T3; two motors M. Source caption says Two Drives Connected in Series; exact circuit topology remains original-only and is not corrected or inferred.

2A0040 | FWH-200B

2A0056 | FWH-200B

2A0069 | FWH-200B

Three-Phase 400 V Class | Three-Phase 400 V Class

4A0001 | FWH-40B

4A0002 | FWH-40B

4A0004 | FWH-50B

4A0005 | FWH-70B

4A0007 | FWH-70B

4A0009 | FWH-90B

4A0011 | FWH-90B

4A0018 | FWH-80B

4A0023 | FWH-100B

4A0031 | FWH-125B

4A0038 | FWH-200B

D1 Bussmann AC branch protection — 467 — PDF page 467

Source row Drive model or phase class Bussmann fuse model Fuse ampere rating (A)
1 2A0040 FWH-200B 200
2 2A0056 FWH-200B 200
3 2A0069 FWH-200B 200
4 Three-Phase 400 V Class Three-Phase 400 V Class Three-Phase 400 V Class
5 4A0001 FWH-40B 40
6 4A0002 FWH-40B 40
7 4A0004 FWH-50B 50
8 4A0005 FWH-70B 70
9 4A0007 FWH-70B 70
10 4A0009 FWH-90B 90
11 4A0011 FWH-90B 90
12 4A0018 FWH-80B 80
13 4A0023 FWH-100B 100
14 4A0031 FWH-125B 125
15 4A0038 FWH-200B 200

Manual — DC input fuses and holders — page 468

Source reference: SIEP C71060618F, December 2016, physical PDF page 468. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Table D.2 Single-Phase 200 V Class Fuses and Fuse Holders

Drive Model

DC Power Supply Input Fuse Fuse Holder Manufacturer: Fuji Electric

Type

Rated Short Circuit Braking Current (kA)

Qty. Type Qty.

Table D.3 Three-Phase 200 V Class Fuses and Fuse Holders

<1> Manufacturer does not recommend a specific fuse holder for this fuse. Contact Yaskawa or your nearest sales representative for fuse dimensions.

Table D.4 Three-Phase 400 V Class Fuses and Fuse Holders

D.2 European Standards

BA0001 | CR6L-20/UL

BA0002 | CR6L-30/UL

BA0003 | CR6L-50/UL

BA0006 | CR6L-75/UL

BA0010 | CR6L-100/UL

BA0012 | CR6L-100/UL

BA0018 | CR6L-150/UL

2A0001 | CR6L-20/UL

2A0002 | CR6L-20/UL

2A0004 | CR6L-20/UL

2A0006 | CR6L-30/UL

2A0010 | CR6L-50/UL

2A0012 | CR6L-50/UL

2A0020 | CR6L-75/UL

2A0030 | CR6L-100/UL

2A0040 | CR6L-150/UL

2A0056 | CR6L-150/UL

2A0069 | CR6L-200/UL

4A0001 | CR6L-20/UL

4A0002 | CR6L-20/UL

4A0004 | CR6L-50/UL

4A0005 | CR6L-50/UL

4A0007 | CR6L-50/UL

4A0009 | CR6L-50/UL

4A0011 | CR6L-50/UL

4A0018 | CR6L-50/UL

4A0023 | CR6L-75/UL

4A0031 | CR6L-100/UL

4A0038 | CR6L-150/UL

D2 Single-phase200V Fuji Electric DC-input fuses and holders — PDF page 468

Source row Drive model Fuse type Rated short circuit braking current (kA) Fuse quantity Fuse holder type Fuse holder quantity
1 BA0001 CR6L-20/UL 100 2 CMS-4 2
2 BA0002 CR6L-30/UL 100 2 CMS-4 2
3 BA0003 CR6L-50/UL 100 2 CMS-4 2
4 BA0006 CR6L-75/UL 100 2 CMS-5 2
5 BA0010 CR6L-100/UL 100 2 CMS-5 2
6 BA0012 CR6L-100/UL 100 2 CMS-5 2
7 BA0018 CR6L-150/UL 100 2 CMS-5 2

D3 Three-phase200V Fuji Electric DC-input fuses and holders — PDF page 468

Source row Drive model Fuse type Rated short circuit braking current (kA) Fuse quantity Fuse holder type Fuse holder quantity
1 2A0001 CR6L-20/UL 100 2 CMS-4 2
2 2A0002 CR6L-20/UL 100 2 CMS-4 2
3 2A0004 CR6L-20/UL 100 2 CMS-4 2
4 2A0006 CR6L-30/UL 100 2 CMS-4 2
5 2A0010 CR6L-50/UL 100 2 CMS-4 2
6 2A0012 CR6L-50/UL 100 2 CMS-4 2
7 2A0020 CR6L-75/UL 100 2 CMS–5 2
8 2A0030 CR6L-100/UL 100 2 CMS–5 2
9 2A0040 CR6L-150/UL 100 2 CMS–5 2
10 2A0056 CR6L-150/UL 100 2 CMS–5 2
11 2A0069 CR6L-200/UL 100 2 <1> –

D4 Three-phase400V Fuji Electric DC-input fuses and holders — PDF page 468

Source row Drive model Fuse type Rated short circuit braking current (kA) Fuse quantity Fuse holder type Fuse holder quantity
1 4A0001 CR6L-20/UL 100 2 CMS-4 2
2 4A0002 CR6L-20/UL 100 2 CMS-4 2
3 4A0004 CR6L-50/UL 100 2 CMS-4 2
4 4A0005 CR6L-50/UL 100 2 CMS-4 2
5 4A0007 CR6L-50/UL 100 2 CMS-4 2
6 4A0009 CR6L-50/UL 100 2 CMS-4 2
7 4A0011 CR6L-50/UL 100 2 CMS-4 2
8 4A0018 CR6L-50/UL 100 2 CMS-4 2
9 4A0023 CR6L-75/UL 100 2 CMS–5 2
10 4A0031 CR6L-100/UL 100 2 CMS–5 2
11 4A0038 CR6L-150/UL 100 2 CMS–5 2

Manual — EMC installation and grounding — page 469

Source reference: SIEP C71060618F, December 2016, physical PDF page 469. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Guarding Against Harmful Materials

When installing IP20/Open-Chassis enclosure drives, use an enclosure that prevents foreign material from entering the drive from above or below.

◆ EMC Guidelines Compliance

This drive is tested according to European standards EN 61800-3:2004/A1:2012 and it complies with the EMC guidelines.

■ EMC Filter Installation

The following conditions must be met to ensure continued compliance with guidelines. Refer to EMC Filters on page 471 for EMC filter selection.

Installation Method Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive also comply with EMC guidelines. 1. Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards. 2. Place the drive and EMC noise filter in the same enclosure. 3. Use braided shield cable for the drive and motor wiring or run the wiring through a metal conduit. 4. Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.

A – Drive B – 20 m max cable length between drive and motor C – Motor

D – Metal conduit E – Ground wire should be as short as possible.

Figure D.3 Installation Method

  1. Ground the largest possible surface area of the shield to the metal conduit when using braided shield cable. Yaskawa recommends using a cable clamp.

A – Braided shield cable; B – Metal panel; C – Cable clamp (conductive)

Figure D.4 Ground Area

D.2 European Standards

D

Standards Compliance

Figure D.3 diagram labels A,B,C,D,E; U/T1,V/T2,W/T3 andU,V,W;M;groundsymbols. Geometry and wiring original-only. Explicit A–E legend captured separately.

Figure D.4 diagram labels A,B,C. Braided shield/cable clamp drawing original-only; explicit A–C legend captured separately.

Manual — Three-phase EMC illustration and legend — page 470

Source reference: SIEP C71060618F, December 2016, physical PDF page 470. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Three-Phase 200 V / 400 V Class

A – Ground the cable shield B – Enclosure panel C – Metal plate D – Grounding surface (remove any paint or sealant) E – Drive

F – Motor cable (braided shield cable, max. 20 m) G – Motor H – Cable clamp I – Wiring distance as short as possible J – EMC noise filter

Figure D.5 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)

D.2 European Standards

Figure D.5 diagram labels L1,L2,L3,PE; A–J; E; L3,L2,L1; R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Three-phase200/400V source figure; miniature drive-face detail retained in raw source, no additional terminal association inferred. Exact wiring/ground/shieldgeometry original-only; A–J legend separate.

Manual — Single-phase EMC illustration and filter table — page 471

Source reference: SIEP C71060618F, December 2016, physical PDF page 471. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Single-Phase 200 V Class

A – Ground the cable shield B – Enclosure panel C – Metal plate D – Grounding surface (remove any paint or sealant) E – Drive

F – Motor cable (braided shield cable, max. 20 m) G – Motor H – Cable clamp I – Wiring distance as short as possible J – EMC noise filter

Figure D.6 EMC Filter and Drive Installation for CE Compliance (Single-Phase 200 V Class)

■ EMC Filters

The drive should be installed with the EMC filters listed below in order to comply with the EN 61800-3:2004/A1:2012, category C1 requirements.

Table D.5 EN 61800-3:2004/A1:2012 Category C1 Filters

Drive Model

Filter Data (Manufacturer: Schaffner)

Type

Rated Current (A)

Weight (lb)

Dimensions [W x L x H] (in)

Mounting Dimensions [Y x X] (in)

Drive Mounting Screw A

Drive Model; Type; Rated Current (A); Weight (lb); Dimensions [W x L x H] (in); Mounting Dimensions [Y x X] (in); Drive Mounting Screw A; Filter Mounting Screw

D.2 European Standards

D

Standards Compliance

Figure D.6 diagram labels N,L1,PE; A–J; E; N,L1; R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Single-phase200V source figure; miniature drive-face details retained in raw source. Exact wiring,ground andshieldgeometry original-only; A–J legend separately captured.

200 V Class Single-Phase | 200 V Class Single-Phase

BA0001 | FS23638-10-07

BA0002 | FS23638-10-07

BA0003 | FS23638-10-07

BA0006 | FS23638-20-07

BA0010 | FS23638-20-07

BA0012 | FS23638-30-07

BA0018 | FS23638-40-07

200 V Three-Phase | 200 V Three-Phase

2A0001 | FS23637-8-07

2A0002 | FS23637-8-07

2A0004 | FS23637-8-07

2A0006 | FS23637-8-07

D5 Schaffner EMC filters 471 — PDF page 471

Source row Drive model or phase class Filter type Rated current A Weight lb Dimensions W x L x H in Mounting Y x X in Drive mounting screw A Filter mounting screw
1 200 V Class Single-Phase 200 V Class Single-Phase 200 V Class Single-Phase 200 V Class Single-Phase 200 V Class Single-Phase 200 V Class Single-Phase 200 V Class Single-Phase 200 V Class Single-Phase
2 BA0001 FS23638-10-07 10 0.97 2.8 x 6.7 x 1.8 2.0 x 6.1 M4 M5
3 BA0002 FS23638-10-07 10 0.97 2.8 x 6.7 x 1.8 2.0 x 6.1 M4 M5
4 BA0003 FS23638-10-07 10 0.97 2.8 x 6.7 x 1.8 2.0 x 6.1 M4 M5
5 BA0006 FS23638-20-07 20 1.65 4.4 x 6.7 x 2.0 3.6 x 6.1 M4 M5
6 BA0010 FS23638-20-07 20 1.65 4.4 x 6.7 x 2.0 3.6 x 6.1 M4 M5
7 BA0012 FS23638-30-07 30 2.42 5.7 x 6.9 x 2.0 4.7 x 6.3 M4 M5
8 BA0018 FS23638-40-07 40 2.87 6.9 x 6.9 x 2.0 5.9 x 6.3 M4 M5
9 200 V Three-Phase 200 V Three-Phase 200 V Three-Phase 200 V Three-Phase 200 V Three-Phase 200 V Three-Phase 200 V Three-Phase 200 V Three-Phase
10 2A0001 FS23637-8-07 7.3 0.88 2.8 x 6.7 x 1.6 2.0 x 6.1 M4 M5
11 2A0002 FS23637-8-07 7.3 0.88 2.8 x 6.7 x 1.6 2.0 x 6.1 M4 M5
12 2A0004 FS23637-8-07 7.3 0.88 2.8 x 6.7 x 1.6 2.0 x 6.1 M4 M5
13 2A0006 FS23637-8-07 7.3 0.88 2.8 x 6.7 x 1.6 2.0 x 6.1 M4 M5

Manual — EMC filter continuation and category exceptions — page 472

Source reference: SIEP C71060618F, December 2016, physical PDF page 472. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive Model

Filter Data (Manufacturer: Schaffner)

Type

Rated Current (A)

Weight (lb)

Dimensions [W x L x H] (in)

Mounting Dimensions [Y x X] (in)

Drive Mounting Screw A

Drive Model; Type; Rated Current (A); Weight (lb); Dimensions [W x L x H] (in); Mounting Dimensions [Y x X] (in); Drive Mounting Screw A; Filter Mounting Screw

Note: EMC filters for models BA0018 and 2A0030 through 2A0069 are in compliance with EN 61800-3:2004/A1:2012, Category 2. All other models comply with Category 1.

Figure D.7 EMC Filter Dimensions

D.2 European Standards

Figure D.7 labels W,Y,L,X,H,A,PE,LINE,LOAD. W×L×H andY×X dimensions supplied in D5 tables; exact drawinggeometry,mounting positions andcable lengths not inferred.

2A0010 | FS23637-14-07

2A0012 | FS23637-14-07

2A0020 | FS23637-24-07

2A0030 | FS23637-52-07

2A0040 | FS23637-52-07

2A0056 | FS23637-68-07

2A0069 | FS23637-80-07

400 V Class Three-Phase | 400 V Class Three-Phase

4A0001 | FS23639-5-07

4A0002 | FS23639-5-07

4A0004 | FS23639-5-07

4A0005 | FS23639-10-07

4A0007 | FS23639-10-07

4A0009 | FS23639-10-07

4A0011 | FS23639-15-07

4A0018 | FS23639-30-07

4A0023 | FS23639-30-07

4A0031 | FS23639-50-07

4A0038 | FS23639-50-07

D5 Schaffner EMC filters 472 — PDF page 472

Source row Drive model or phase class Filter type Rated current A Weight lb Dimensions W x L x H in Mounting Y x X in Drive mounting screw A Filter mounting screw
1 2A0010 FS23637-14-07 14 1.28 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
2 2A0012 FS23637-14-07 14 1.28 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
3 2A0020 FS23637-24-07 24 1.98 5.7 x 6.9 x 2.0 4.7 x 6.3 M4 M5
4 2A0030 FS23637-52-07 52 4.41 5.4 x 12.0 x 2.2 3.9 x 11.4 M5 M5
5 2A0040 FS23637-52-07 52 4.41 5.4 x 12.0 x 2.2 3.9 x 11.4 M5 M5
6 2A0056 FS23637-68-07 68 5.73 6.9 x 13.4 x 2.6 5.1 x 12.8 M5 M6
7 2A0069 FS23637-80-07 80 6.83 8.3 x 15.5 x 2.6 6.6 x 14.9 M6 M8
8 400 V Class Three-Phase 400 V Class Three-Phase 400 V Class Three-Phase 400 V Class Three-Phase 400 V Class Three-Phase 400 V Class Three-Phase 400 V Class Three-Phase 400 V Class Three-Phase
9 4A0001 FS23639-5-07 5 1.10 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
10 4A0002 FS23639-5-07 5 1.10 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
11 4A0004 FS23639-5-07 5 1.10 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
12 4A0005 FS23639-10-07 10 1.54 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
13 4A0007 FS23639-10-07 10 1.54 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
14 4A0009 FS23639-10-07 10 1.54 4.4 x 6.7 x 1.8 3.6 x 6.1 M4 M5
15 4A0011 FS23639-15-07 15 1.98 5.7 x 6.9 x 2.0 4.7 x 6.3 M4 M5
16 4A0018 FS23639-30-07 30 4.0 5.4 x 12.0 x 2.2 3.9 x 11.4 M5 M5
17 4A0023 FS23639-30-07 30 4.0 5.4 x 12.0 x 2.2 3.9 x 11.4 M5 M5
18 4A0031 FS23639-50-07 50 6.0 6.9 x 13.4 x 2.6 5.1 x 12.8 M5 M6
19 4A0038 FS23639-50-07 50 6.0 6.9 x 13.4 x 2.6 5.1 x 12.8 M5 M6

Manual — DC link choke table — page 473

Source reference: SIEP C71060618F, December 2016, physical PDF page 473. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ DC Link Chokes for IEC/EN 61000-3-2 Compliance

DC Link Choke Drive Model Model Rating

Note: Models not listed in the above table do not require a DC link choke for EMC compliance.

D.2 European Standards

D

Standards Compliance

200V Three-Phase Units | 200V Three-Phase Units

2A0004 | UZDA-B

2A0006 | UZDA-B

400 V Three-Phase Units | 400 V Three-Phase Units

4A0002 | UZDA-B

4A0004 | UZDA-B

DC link chokes for IEC/EN61000-3-2 compliance — PDF page 473

Source row Drive model or phase class Choke model Rating
1 200V Three-Phase Units 200V Three-Phase Units 200V Three-Phase Units
2 2A0004 UZDA-B 5.4 A 8 mH
3 2A0006 UZDA-B 5.4 A 8 mH
4 400 V Three-Phase Units 400 V Three-Phase Units 400 V Three-Phase Units
5 4A0002 UZDA-B 3.2 A 28 mH
6 4A0004 UZDA-B 3.2 A 28 mH

Manual — UL conditions and wire gauge table — page 474

Source reference: SIEP C71060618F, December 2016, physical PDF page 474. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

D.3 UL and CSA Standards

◆ UL Standards Compliance

The UL/cUL mark applies to products in the United States and Canada and indicates that UL has performed product testing and evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL certification, all components inside that product must also receive UL certification.

Figure D.8 UL/cUL Mark

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The following conditions must be met to maintain compliance when using this drive in combination with other equipment:

■ Installation Area

Do not install the drive to an area greater than pollution severity 2 (UL standard).

■ Ambient Temperature

IP20/NEMA 1, UL Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F) IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F) Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F) NEMA 4X, UL Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

■ Main Circuit Terminal Wiring

Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL Listed closed-loop crimp terminals when wiring the drive main circuit terminals. Use only the tools recommended by the terminal manufacturer for crimping. The wire gauges listed in Table D.6, Table D.7, and Table D.8 are Yaskawa recommendations. Refer to local codes for proper wire gauge selections.

Table D.6 Wire Gauge and Torque Specifications

Drive Model; Terminal

Recomm. Gauge AWG, kcmil

Wire Range AWG, kcmil

Screw Size

Tightening Torque N•m (lb.in.)

Figure D.8 UL/cUL mark; c UL US LISTED. Historical graphic logo,not currentcertificate validation.

BA0001 BA0002 BA0003 | R/L1, S/L2, T/L3

BA0001 BA0002 BA0003 | U/T1, V/T2, W/T3

BA0001 BA0002 BA0003 | ⊖, ⊕1, ⊕2

BA0001 BA0002 BA0003 | B1, B2

BA0001 BA0002 BA0003 | ⏚ (ground symbol)

BA0006 | R/L1, S/L2, T/L3

BA0006 | U/T1, V/T2, W/T3

BA0006 | ⊖, ⊕1, ⊕2

BA0006 | B1, B2

BA0006 | ⏚ (ground symbol)

BA0010 | R/L1, S/L2, T/L3

BA0010 | U/T1, V/T2, W/T3

BA0010 | ⊖, ⊕1, ⊕2

BA0010 | B1, B2

BA0010 | ⏚ (ground symbol)

D6 single-phase wire gauge and torque — PDF page 474

Source row Drive model Terminal Recommended gauge AWG/kcmil Wire range AWG/kcmil Screw size Tightening torque N·m (lb.in.)
1 BA0001 BA0002 BA0003 R/L1, S/L2, T/L3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
2 BA0001 BA0002 BA0003 U/T1, V/T2, W/T3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
3 BA0001 BA0002 BA0003 ⊖, ⊕1, ⊕2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
4 BA0001 BA0002 BA0003 B1, B2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
5 BA0001 BA0002 BA0003 ⏚ (ground symbol) 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
6 BA0006 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
7 BA0006 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
8 BA0006 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
9 BA0006 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
10 BA0006 ⏚ (ground symbol) 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
11 BA0010 R/L1, S/L2, T/L3 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
12 BA0010 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
13 BA0010 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
14 BA0010 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
15 BA0010 ⏚ (ground symbol) 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)

Manual — Wire gauge and torque continuation — page 475

Source reference: SIEP C71060618F, December 2016, physical PDF page 475. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive Model; Terminal

Recomm. Gauge AWG, kcmil

Wire Range AWG, kcmil

Screw Size

Tightening Torque N•m (lb.in.)

Table D.7 Wire Gauge and Torque Specifications

D.3 UL and CSA Standards

D

Standards Compliance

BA0012 | R/L1, S/L2, T/L3

BA0012 | U/T1, V/T2, W/T3

BA0012 | ⊖, ⊕1, ⊕2

BA0012 | B1, B2

BA0012 | ⏚ (ground symbol)

BA0018 | R/L1, S/L2, T/L3

BA0018 | U/T1, V/T2, W/T3

BA0018 | ⊖, ⊕1, ⊕2

BA0018 | B1, B2

BA0018 | ⏚ (ground symbol)

2A0001 2A0002 2A0004 2A0006 | R/L1, S/L2, T/L3

2A0001 2A0002 2A0004 2A0006 | U/T1, V/T2, W/T3

2A0001 2A0002 2A0004 2A0006 | ⊖, ⊕1, ⊕2

2A0001 2A0002 2A0004 2A0006 | B1, B2

2A0001 2A0002 2A0004 2A0006 | ⏚ (ground symbol)

2A0010 | R/L1, S/L2, T/L3

2A0010 | U/T1, V/T2, W/T3

2A0010 | ⊖, ⊕1, ⊕2

2A0010 | B1, B2

2A0010 | ⏚ (ground symbol)

2A0012 | R/L1, S/L2, T/L3

2A0012 | U/T1, V/T2, W/T3

2A0012 | ⊖, ⊕1, ⊕2

2A0012 | B1, B2

2A0012 | ⏚ (ground symbol)

2A0020 | R/L1, S/L2, T/L3

2A0020 | U/T1, V/T2, W/T3

2A0020 | ⊖, ⊕1, ⊕2

2A0020 | B1, B2

2A0020 | ⏚ (ground symbol)

2A0030 | R/L1, S/L2, T/L3

2A0030 | U/T1, V/T2, W/T3

2A0030 | ⊖, ⊕1, ⊕2

2A0030 | B1, B2

2A0030 | ⏚ (ground symbol)

2A0040 | R/L1, S/L2, T/L3

2A0040 | U/T1, V/T2, W/T3

2A0040 | –, +1, +2

2A0040 | B1, B2

2A0040 | ⏚ (ground symbol)

D6 single-phase wire gauge and torque — PDF page 475

Source row Drive model Terminal Recommended gauge AWG/kcmil Wire range AWG/kcmil Screw size Tightening torque N·m (lb.in.)
1 BA0012 R/L1, S/L2, T/L3 10 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
2 BA0012 U/T1, V/T2, W/T3 14 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
3 BA0012 ⊖, ⊕1, ⊕2 – 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
4 BA0012 B1, B2 – 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
5 BA0012 ⏚ (ground symbol) 10 14 to 10 M4 2.3 to 2.5 (20.4 to 22.1)
6 BA0018 R/L1, S/L2, T/L3 8 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
7 BA0018 U/T1, V/T2, W/T3 10 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
8 BA0018 ⊖, ⊕1, ⊕2 – 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
9 BA0018 B1, B2 – 12 to 8 M5 2.3 to 2.5 (20.4 to 22.1)
10 BA0018 ⏚ (ground symbol) 8 12 to 8 M5 2 to 2.5 (17.7 to 22.1)

D7 three-phase200V wire gauge and torque — PDF page 475

Source row Drive model Terminal Recommended gauge AWG/kcmil Wire range AWG/kcmil Screw size Tightening torque N·m (lb.in.)
1 2A0001 2A0002 2A0004 2A0006 R/L1, S/L2, T/L3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
2 2A0001 2A0002 2A0004 2A0006 U/T1, V/T2, W/T3 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
3 2A0001 2A0002 2A0004 2A0006 ⊖, ⊕1, ⊕2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
4 2A0001 2A0002 2A0004 2A0006 B1, B2 – 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
5 2A0001 2A0002 2A0004 2A0006 ⏚ (ground symbol) 14 18 to 14 M3.5 0.8 to 1.0 (7.1 to 8.9)
6 2A0010 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
7 2A0010 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
8 2A0010 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
9 2A0010 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
10 2A0010 ⏚ (ground symbol) 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
11 2A0012 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
12 2A0012 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
13 2A0012 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
14 2A0012 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
15 2A0012 ⏚ (ground symbol) 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
16 2A0020 R/L1, S/L2, T/L3 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
17 2A0020 U/T1, V/T2, W/T3 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
18 2A0020 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
19 2A0020 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
20 2A0020 ⏚ (ground symbol) 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
21 2A0030 R/L1, S/L2, T/L3 8 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
22 2A0030 U/T1, V/T2, W/T3 8 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
23 2A0030 ⊖, ⊕1, ⊕2 – 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
24 2A0030 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
25 2A0030 ⏚ (ground symbol) 8 <1> 10 to 6 M5 2 to 2.5 (17.7 to 22.1)
26 2A0040 R/L1, S/L2, T/L3 6 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
27 2A0040 U/T1, V/T2, W/T3 8 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
28 2A0040 –, +1, +2 – 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
29 2A0040 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
30 2A0040 ⏚ (ground symbol) 6 10 to 6 M5 2 to 2.5 (17.7 to 22.1)

Manual — Wire gauges and torque D7–D8 — page 476

Source reference: SIEP C71060618F, December 2016, physical PDF page 476. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive Model; Terminal

Recomm. Gauge AWG, kcmil

Wire Range AWG, kcmil

Screw Size

Tightening Torque N•m (lb.in.)

<1> When an EMC filter is installed, additional measures must be taken to comply with IEC/EN 61800-5-1. Refer to EMC Filter Installation on page 469 for details.

Table D.8 Wire Gauge and Torque Specifications

D.3 UL and CSA Standards

2A0056 | R/L1, S/L2, T/L3

2A0056 | U/T1, V/T2, W/T3

2A0056 | ⊖, ⊕1, ⊕2

2A0056 | B1, B2

2A0056 | ⏚ (ground symbol)

2A0069 | R/L1, S/L2, T/L3

2A0069 | U/T1, V/T2, W/T3

2A0069 | ⊖, ⊕1, ⊕2

2A0069 | B1, B2

2A0069 | ⏚ (ground symbol)

4A0001 4A0002 4A0004 | R/L1, S/L2, T/L3

4A0001 4A0002 4A0004 | U/T1, V/T2, W/T3

4A0001 4A0002 4A0004 | ⊖, ⊕1, ⊕2

4A0001 4A0002 4A0004 | B1, B2

4A0001 4A0002 4A0004 | ⏚ (ground symbol)

4A0005 4A0007 4A0009 | R/L1, S/L2, T/L3

4A0005 4A0007 4A0009 | U/T1, V/T2, W/T3

4A0005 4A0007 4A0009 | ⊖, ⊕1, ⊕2

4A0005 4A0007 4A0009 | B1, B2

4A0005 4A0007 4A0009 | ⏚ (ground symbol)

4A0011 | R/L1, S/L2, T/L3

4A0011 | U/T1, V/T2, W/T3

4A0011 | ⊖, ⊕1, ⊕2

4A0011 | B1, B2

4A0011 | ⏚ (ground symbol)

4A0018 | R/L1, S/L2, T/L3

4A0018 | U/T1, V/T2, W/T3

4A0018 | ⊖, ⊕1, ⊕2

4A0018 | B1, B2

4A0018 | ⏚ (ground symbol)

4A0023 | R/L1, S/L2, T/L3

4A0023 | U/T1, V/T2, W/T3

4A0023 | ⊖, ⊕1, ⊕2

4A0023 | B1, B2

4A0023 | ⏚ (ground symbol)

D7 three-phase200V wire gauge and torque — PDF page 476

Source row Drive model Terminal Recommended gauge AWG/kcmil Wire range AWG/kcmil Screw size Tightening torque N·m (lb.in.)
1 2A0056 R/L1, S/L2, T/L3 4 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
2 2A0056 U/T1, V/T2, W/T3 4 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
3 2A0056 ⊖, ⊕1, ⊕2 – 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
4 2A0056 B1, B2 – 10 to 6 M5 2.7 to 3.0 (23.9 to 26.6)
5 2A0056 ⏚ (ground symbol) 6 8 to 4 M6 5.4 to 6.0 (47.8 to 53.1)
6 2A0069 R/L1, S/L2, T/L3 3 8 to 2 M8 9.9 to 11 (87.6 to 97.4)
7 2A0069 U/T1, V/T2, W/T3 3 8 to 2 M8 9.9 to 11 (87.6 to 97.4)
8 2A0069 ⊖, ⊕1, ⊕2 – 8 to 2 M8 9.9 to 11 (87.6 to 97.4)
9 2A0069 B1, B2 – 8 to 6 M5 2.7 to 3.0 (23.9 to 26.6)
10 2A0069 ⏚ (ground symbol) 6 6 to 4 M6 5.4 to 6.0 (47.8 to 53.1)

D8 three-phase400V wire gauge and torque — PDF page 476

Source row Drive model Terminal Recommended gauge AWG/kcmil Wire range AWG/kcmil Screw size Tightening torque N·m (lb.in.)
1 4A0001 4A0002 4A0004 R/L1, S/L2, T/L3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
2 4A0001 4A0002 4A0004 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
3 4A0001 4A0002 4A0004 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
4 4A0001 4A0002 4A0004 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
5 4A0001 4A0002 4A0004 ⏚ (ground symbol) 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
6 4A0005 4A0007 4A0009 R/L1, S/L2, T/L3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
7 4A0005 4A0007 4A0009 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
8 4A0005 4A0007 4A0009 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
9 4A0005 4A0007 4A0009 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
10 4A0005 4A0007 4A0009 ⏚ (ground symbol) 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
11 4A0011 R/L1, S/L2, T/L3 12 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
12 4A0011 U/T1, V/T2, W/T3 14 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
13 4A0011 ⊖, ⊕1, ⊕2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
14 4A0011 B1, B2 – 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
15 4A0011 ⏚ (ground symbol) 10 14 to 10 M4 1.2 to 1.5 (10.6 to 13.3)
16 4A0018 R/L1, S/L2, T/L3 10 14 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
17 4A0018 U/T1, V/T2, W/T3 10 14 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
18 4A0018 ⊖, ⊕1, ⊕2 – 14 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
19 4A0018 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
20 4A0018 ⏚ (ground symbol) 8 14 to 6 M5 2 to 2.5 (17.7 to 22.1)
21 4A0023 R/L1, S/L2, T/L3 10 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
22 4A0023 U/T1, V/T2, W/T3 10 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
23 4A0023 ⊖, ⊕1, ⊕2 – 10 to 6 M4 2.1 to 2.3 (18.6 to 20.4)
24 4A0023 B1, B2 – 14 to 10 M4 2.1 to 2.3 (18.6 to 20.4)
25 4A0023 ⏚ (ground symbol) 8 10 to 6 M5 2 to 2.5 (17.7 to 22.1)

Manual — D8 continuation, crimp terminals and voltage drop — page 477

Source reference: SIEP C71060618F, December 2016, physical PDF page 477. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

Drive Model; Terminal

Recomm. Gauge AWG, kcmil

Wire Range AWG, kcmil

Screw Size

Tightening Torque N•m (lb.in.)

<1> When an EMC filter is installed, additional measures must be taken to comply with IEC/EN 61800-5-1. Refer to EMC Filter Installation on page 469 for details.

Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable temperature of 75 °C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 30 °C. Closed-Loop Crimp Terminal Recommendations Yaskawa recommends crimp terminals made by JST and Tokyo DIP for the insulation cap. Table D.9 matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department. The closed-loop crimp terminal sizes and values listed in Table D.9 are Yaskawa recommendations. Refer to local codes for proper selections.

Table D.9 Closed-Loop Crimp Terminal Sizes

Wire Gauge Terminal Screws

Crimp Terminal Model Number

Tool Insulation Cap Die Jaw Model No.

Cap Code <1> Machine No. Die Jaw Model No.

<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection. Example: Models with 14 AWG for both input and output require one set for input terminals and one set for output terminals, so the user should order two sets of [100-066-218].

Note: Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor

D.3 UL and CSA Standards

D

Standards Compliance

Source formula: Line drop voltage (V) = √3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10⁻³. Increase wire gauge when voltage drop exceeds2% of motor rated voltage; no calculation performed. Formula reconstructed from visible root, multiplication and exponent, raw retained.

4A0031 | R/L1, S/L2, T/L3

4A0031 | U/T1, V/T2, W/T3

4A0031 | ⊖, ⊕1, ⊕2

4A0031 | B1, B2

4A0031 | ⏚ (ground symbol)

4A0038 | R/L1, S/L2, T/L3

4A0038 | U/T1, V/T2, W/T3

4A0038 | ⊖, ⊕1, ⊕2

4A0038 | B1, B2

4A0038 | ⏚ (ground symbol)

18 AWG | M3.5

16 AWG | M3.5

14 AWG | M3.5

14 AWG | M4

12 / 10 AWG | M4

12 / 10 AWG | M5

8 AWG | M4

8 AWG | M5

8 AWG | M8

6 AWG | M4

6 AWG | M5

6 AWG | M6

6 AWG | M8

4 AWG | M6

4 AWG | M8

3 AWG | M8

2 AWG | M8

D8 three-phase400V wire gauge and torque — PDF page 477

Source row Drive model Terminal Recommended gauge AWG/kcmil Wire range AWG/kcmil Screw size Tightening torque N·m (lb.in.)
1 4A0031 R/L1, S/L2, T/L3 8 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
2 4A0031 U/T1, V/T2, W/T3 8 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
3 4A0031 ⊖, ⊕1, ⊕2 – 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
4 4A0031 B1, B2 – 14 to 10 M5 2.7 to 3.0 (23.9 to 26.6)
5 4A0031 ⏚ (ground symbol) 6 <1> 10 to 6 M6 5.4 to 6.0 (47.8 to 53.1)
6 4A0038 R/L1, S/L2, T/L3 6 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
7 4A0038 U/T1, V/T2, W/T3 8 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
8 4A0038 ⊖, ⊕1, ⊕2 – 10 to 6 M5 3.6 to 4.0 (31.8 to 35.4)
9 4A0038 B1, B2 – 10 to 8 M5 2.7 to 3.0 (23.9 to 26.6)
10 4A0038 ⏚ (ground symbol) 6 10 to 6 M6 5.4 to 6.0 (47.8 to 53.1)

D9 closed-loop crimp terminal sizes — PDF page 477

Source row Wire gauge Terminal screw Crimp terminal model Tool machine number Tool die jaw Insulation cap model Order code footnote1
1 18 AWG M3.5 R1.25-3.5 YA-4 AD-900 TP-003 100-066-217
2 16 AWG M3.5 R1.25-3.5 YA-4 AD-900 TP-003 100-066-217
3 14 AWG M3.5 R2-3.5 YA-4 AD-900 TP-003 100-066-218
4 14 AWG M4 R2-4 YA-4 AD-900 TP-003 100-054-028
5 12 / 10 AWG M4 R5.5-4 YA-4 AD-900 TP-005 100-054-029
6 12 / 10 AWG M5 R5.5-5 YA-4 AD-900 TP-005 100-054-030
7 8 AWG M4 8-4 YA-4 AD-901 TP-008 100-054-031
8 8 AWG M5 R8-5 YA-4 AD-901 TP-008 100-054-032
9 8 AWG M8 R8-8 YA-4 AD-901 TP-008 100-061-111
10 6 AWG M4 14-4 YA-4 AD-902 TP-014 100-66-220
11 6 AWG M5 R14-5 YA-4 AD-902 TP-014 100-054-034
12 6 AWG M6 R14-6 YA-5 AD-952 TP-014 100-051-261
13 6 AWG M8 R14-8 YA-5 AD-952 TP-014 100-054-035
14 4 AWG M6 R22-6 YA-5 AD-953 TP-022 100-051-262
15 4 AWG M8 R22-8 YA-5 AD-953 TP-022 100-051-263
16 3 AWG M8 R38-8 YA-5 AD-954 TP-038 100-051-264
17 2 AWG M8 R38-8 YA-5 AD-954 TP-038 100-051-264

Manual — Recommended circuit protection D10 — page 478

Source reference: SIEP C71060618F, December 2016, physical PDF page 478. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

■ Factory Recommended Branch Circuit Protection

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C. Semiconductor protective type fuses are preferred. Branch circuit protection shall be provided by any of the following according to Table D.10. • Non-time Delay Class J, T, or CC fuses. • Time Delay Class J, T, CC, or RK5 fuses. • Semiconductor fuses. • Molded Case Circuit Breakers (MCCB).

Table D.10 Factory Recommended Drive Branch Circuit Protection

Drive Model

Non-time Delay Fuse Rating (A)

<1>

Time Delay Fuses Bussmann T, or CC Class RK5 Semiconductor Fuse Part Number Rating (A) Fuse Rating (A) <2> <3> (Fuse Ampere) <4>

MCCB <5>

Class J, T, or CC Fuse Rating (A)

<2>

Class RK5 Fuse Rating (A)

<3>

Rating (A)

Minimum Enclosure Volume (in3)

<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 2A0002, 2A0004, 4A0004, 4A0005, and 4A0007. <2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse. <3> Maximum 225% of drive input current rating for any Class RK5 fuse. <4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.

D.3 UL and CSA Standards

200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives

BA0001 | 6

BA0002 | 10

BA0003 | 20

BA0006 | 40

BA0010 | 40

BA0012 | 50

BA0018 | 80

200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives

2A0001 | 3

2A0002 | 6 <6>

2A0004 | 15 <7>

2A0006 | 20

2A0010 | 25

2A0012 | 25

2A0020 | 40

2A0030 | –

2A0040 | –

2A0056 | –

2A0069 | –

400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives

4A0001 | 3

4A0002 | 6

4A0004 | 15 <7>

4A0005 | 20 <8>

4A0007 | 25 <9>

4A0009 | 25

4A0011 | 30

4A0018 | –

4A0023 | –

4A0031 | –

4A0038 | –

D10 factory-recommended branch protection — PDF page 478

Source row Drive model or phase class Non-time-delay fuse A foot1 Time-delay ClassJ/T/CC A foot2 Time-delay ClassRK5 A foot3 Bussmann semiconductor fuse model andA foot4 MCCB A foot5 Minimum enclosure volume in³ foot5
1 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives
2 BA0001 6 3.5 4 FWH-25A14F (25) 15 600
3 BA0002 10 6 8 FWH-25A14F (25) 15 600
4 BA0003 20 10 15 FWH-60B (60) 15 600
5 BA0006 40 20 30 FWH-80B (80) 30 1152
6 BA0010 40 35 45 FWH-100B (100) 50 1152
7 BA0012 50 40 50 FWH-125B (125) 60 1152
8 BA0018 80 60 70 FWH-175B (175) 80 1152
9 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives
10 2A0001 3 1.5 2 FWH-25A14F (25) 15 600
11 2A0002 6 <6> 3 3 FWH-25A14F (25) 15 600
12 2A0004 15 <7> 6 8 FWH-25A14F (25) 15 600
13 2A0006 20 10 15 FWH-25A14F (25) 15 1152
14 2A0010 25 15 20 FWH-70B (70) 25 1152
15 2A0012 25 20 30 FWH-70B (70) 30 1152
16 2A0020 40 40 50 FWH-90B (90) 60 1152
17 2A0030 – 60 80 FWH-100B (100) 90 1152
18 2A0040 – 90 110 FWH-200B (200) 125 1152
19 2A0056 – 110 150 FWH-200B (200) 150 2560
20 2A0069 – 125 175 FWH-200B (200) 200 2560
21 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives
22 4A0001 3 2 2 FWH-40B (40) 15 1152
23 4A0002 6 3.5 3 FWH-40B (40) 15 1152
24 4A0004 15 <7> 7 8 FWH-50B (50) 15 1152
25 4A0005 20 <8> 10 10 FWH-70B (70) 15 1152
26 4A0007 25 <9> 12 15 FWH-70B (70) 20 1152
27 4A0009 25 15 20 FWH-90B (90) 20 1152
28 4A0011 30 20 30 FWH-90B (90) 35 1152
29 4A0018 – 35 45 FWH-80B (80) 50 1152
30 4A0023 – 40 50 FWH-100B (100) 60 1152
31 4A0031 – 60 80 FWH-125B (125) 90 1152
32 4A0038 – 70 90 FWH-200B (200) 110 1152

Manual — Fuse footnotes, control wiring, CSA and overload — page 479

Source reference: SIEP C71060618F, December 2016, physical PDF page 479. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater. Additionally, when using MCCBs for protection, the drive must be installed in a ventilated enclosure with minimum volume according the “Minimum Enclosure Volume” column. <6> Model 2A0002 requires Mersen (Ferraz) part number A6T6 for compliance. <7> Models 2A0004 and 4A0004 require Mersen (Ferraz) part number A6T15 for compliance. <8> Model 4A0005 requires Mersen (Ferraz) part number A6T20 for compliance. <9> Model 4A0007 requires Mersen (Ferraz) part number A6T25 for compliance.

■ Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external power supply shall be a UL-Listed Class 2 power source or equivalent.

Table D.11 Control Circuit Terminal Power Supply

Input / Output Terminal Signal Power Supply Specifications

■ Drive Short-Circuit Rating

This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise above 31,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives. • The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the power supply being used. • Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes for 240 V in 200 V class drives (up to 480 V for 400 V class drives) motor overload protection.

◆ CSA Standards Compliance

Figure D.9 CSA Mark

■ CSA for Industrial Control Equipment

The drive is CSA-certified as Industrial Control Equipment Class 3211. Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.

◆ Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload protection is UL listed and in accordance with the NEC and CEC.

■ E2-01: Motor Rated Current

Setting Range: Model Dependent Default Setting: Model Dependent Parameter E2-01 (motor rated current) protects the motor if parameter L1-01 is not set to 0 (default is 1, standard induction motor protection enabled).

D.3 UL and CSA Standards

D

Standards Compliance

Figure D.9 CSA mark and registration symbol. Historical logo only; no current certification validity inferred.

Multi-function photocoupler output | P1, P2, PC

Multi-function digital inputs | S1, S2, S3, S4, S5, S6, S7, SC

Multi-function analog inputs | A1, A2, AC

Pulse train input | RP

Pulse train output | MP

D11 control circuit terminal power supply — PDF page 479

Source row Input/output Terminal signal Power supply specification
1 Multi-function photocoupler output P1, P2, PC Requires class 2 power supply
2 Multi-function digital inputs S1, S2, S3, S4, S5, S6, S7, SC Use the internal power supply of the drive. Use class 2 for external power supply.
3 Multi-function analog inputs A1, A2, AC Use the internal power supply of the drive. Use class 2 for external power supply.
4 Pulse train input RP Use the internal LVLC power supply of the drive. Use class 2 for external power supply.
5 Pulse train output MP Use the internal LVLC power supply of the drive. Use class 2 for external power supply.

Manual — Motor overload selection and timing — page 480

Source reference: SIEP C71060618F, December 2016, physical PDF page 480. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

If Auto-Tuning has been performed successfully, the motor data that was entered in T1-04 is automatically written into parameter E2-01. If Auto-Tuning has not been performed, manually enter the correct motor rated current in parameter E2-01.

■ L1-01: Motor Overload Protection Selection

The drive has an electronic overload protection function (oL1) based on time, output current and output frequency, which protects the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external thermal overload relay for single motor operation. This parameter selects the motor overload curve used according to the type of motor applied.

Table D.12 Overload Protection Settings

Setting Description

Disable the electronic overload protection (L1-01 = 0: Disabled) and wire each motor with its own motor thermal overload when connecting the drive to more than one motor for simultaneous operation. Enable the motor overload protection (L1-01 = “1”, “2”, or “3”) when connecting the drive to a single motor unless there is another means of preventing motor thermal overload. The electronic thermal overload function causes an oL1 fault, which shuts off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated as long as the drive is powered up. Setting L1-01 = 1 selects a motor with limited cooling capability below rated (base) speed when running at 100% load. The oL1 function derates the motor when it is running below base speed. Setting L1-01 = 2 selects a motor capable of cooling itself over a 10:1 speed range when running at 100% load. The oL1 function derates the motor when it is running at 1/10 or less of its rated speed. Setting L1-01 = 3 selects a motor capable of cooling itself at any speed — including zero speed — when running at 100% load. The oL1 function does not derate the motor at any speed. Setting L1-01 = 4 selects protection for a PM motor with variable torque.

■ L1-02: Motor Overload Protection Time

Setting Range: 0.1 to 5.0 Minutes Factory Default: 1.0 Minutes The L1-02 parameter sets the allowed operation time before the oL1 fault occurs when the drive is running at 60 Hz and 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the set of oL1 curves up the Y-axis of the diagram below but will not change the shape of the curves.

Figure D.10 Motor Overload Protection Time

D.3 UL and CSA Standards

Figure D.10: Operation time (minutes), ticks0.1,0.4,1,3,7,10; Motor current (%), ticks0,100,150,200; E2-01=100% motor current. Cold start: characteristics when an overload occurs at a complete stop. Hot start: characteristics when an overload occurs during continuous operation at100%. Curves, shaded region and points retained only in original figure, no interpolated trip times.

0 | Disabled

1 | Standard Fan-Cooled Motor (Default)

2 | Drive Duty Motor with a Speed Range of 1:10

3 | Vector Motor with a Speed Range of 1:100

4 | Permanent Magnet Motor with Variable Torque

6 | Standard Fan-Cooled Motor (50 Hz)

D12 L1-01 motor overload protection choices — PDF page 480

Source row Setting Description
1 0 Disabled
2 1 Standard Fan-Cooled Motor (Default)
3 2 Drive Duty Motor with a Speed Range of 1:10
4 3 Vector Motor with a Speed Range of 1:100
5 4 Permanent Magnet Motor with Variable Torque
6 6 Standard Fan-Cooled Motor (50 Hz)

Manual — Safe Disable standards and specifications — page 481

Source reference: SIEP C71060618F, December 2016, physical PDF page 481. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

D.4 Safe Disable Input

Figure D.11 TUV Mark

The TUV Mark indicates compliance with safety standards. This section explains precautions regarding the Safe Disable input. Contact Yaskawa or your nearest sales representative for more information. The Safety Disable function complies with the standards listed in Table D.13.

Table D.13 Safety Standards and Applicable EU Standards

Safety Standards Applicable EU Standards

Note: SIL stands for Safety Integrity Level.

◆ Specifications

The Safe Disable input provides a stop function in compliance with the “Safe Torque Off” function defined in IEC/EN 61800-5-2:2007. The Safe Disable input satisfies the requirements in EN ISO 13849-1 and IEC/EN 61508, SIL2. Table D. 14 lists the specifications for the Safety Disable function.

Table D.14 Specifications for Safe Disable Function

Note: PFD = Probability of Failure on Demand PFH = Probability of Dangerous Failure per Hour

D

Standards Compliance

Figure D.11 TÜV SÜD mark, Functional Safety. Historical logo, not current certification validity.

Functional Safety | IEC 61508:2000/EN 61508:2001(SIL2)

Functional Safety | IEC/EN 61800-5-2: 2007 (SIL2)

Mechanical Safety | ISO 13849-1:2006 (Cat.III, PL d) / EN ISO 13849-1/AC:2009 (Cat.III, PL d)

EMC | EN 61800-3:2004/A1:2012

EMC | EN 61800-5-1:2007

Inputs/Outputs | Inputs/Outputs

Response Time from Input Open to Drive Output Stop | Response Time from Input Open to Drive Output Stop

Failure Probability | Demand Rate Low

Failure Probability | Demand Rate High/ Continuous

Performance Level | Performance Level

HFT (Hardware Fault Tolerance) | HFT (Hardware Fault Tolerance)

Classification of Subsystem | Classification of Subsystem

D13 historical safety and applicable EU standards — PDF page 481

Source row Safety category Applicable standard
1 Functional Safety IEC 61508:2000/EN 61508:2001(SIL2)
2 Functional Safety IEC/EN 61800-5-2: 2007 (SIL2)
3 Mechanical Safety ISO 13849-1:2006 (Cat.III, PL d) / EN ISO 13849-1/AC:2009 (Cat.III, PL d)
4 EMC EN 61800-3:2004/A1:2012
5 EMC EN 61800-5-1:2007

D14 safe-disable function specification — PDF page 481

Source row Specification Subitem or shared specification Value
1 Inputs/Outputs Inputs/Outputs • Inputs: 1 Safe Disable input H1 • Outputs: 0
2 Response Time from Input Open to Drive Output Stop Response Time from Input Open to Drive Output Stop Shorter than 1 ms
3 Failure Probability Demand Rate Low PFD = 1.24E−7
4 Failure Probability Demand Rate High/ Continuous PFH = 5.17E−10
5 Performance Level Performance Level The Safe Disable inputs satisfy the following requirements in consideration of the self-diagnostic function. Performance Level (PL) d according to EN ISO 13849-1
6 HFT (Hardware Fault Tolerance) HFT (Hardware Fault Tolerance) N = 1
7 Classification of Subsystem Classification of Subsystem Type B

Manual — Safe Disable full precautions — page 482

Source reference: SIEP C71060618F, December 2016, physical PDF page 482. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ Precautions

DANGER! Sudden Movement Hazard. Make sure the whole system or machinery in which the Safe Disable function is used complies with safety requirements. When implementing the Safe Disable function into the safety system of a machine, perform a thorough risk assessment for the entire system to assure compliance with relevant safety norms. Improper use of the Safe Disable function will cause serious injury or even death.

DANGER! Sudden Movement Hazard. An external holding brake and dynamic break are not considered to be safety components for drives. Even when using an external holding brake or dynamic brake with a drive output signal, it is still not considered a safe system because the drive output signal is not a safety component. A system is required that satisfies safety requirements. Failure to comply will cause death or serious injury.

DANGER! Sudden Movement Hazard. Connect the Safe Disable inputs to the devices in compliance with safety requirements. Failure to comply will cause death or serious injury.

WARNING! Sudden Movement Hazard. When using a PM motor, even if the drive output is shut off by the Safe Disable function, a breakdown of two output transistors can cause current to flow through the motor winding, resulting in a motor output axis movement for a maximum angle of 180 degrees (electrically). Make sure such a situation would have no effect on the safety of the application when using the Safe Disable function. Failure to comply could cause serious injury or death.

WARNING! Electrical Shock Hazard. The Safe Disable function can switch off the drive output, but does not cut the drive power supply and cannot electrically isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or installations on the drive input side as well as the drive output side. Failure to comply could cause serious injury or death.

WARNING! Sudden Movement Hazard. The motor will move when an external gravitational force in the vertical axis is applied even if the Safe Disable function is in operation. Failure to comply could cause serious injury or death.

WARNING! Sudden Movement Hazard. When using the Safe Disable inputs, make sure to remove the wire links between terminals H1 and HC that were installed prior to shipment. Failure to do so will keep the Safe Disable circuit from operating properly and could cause death or serious injury.

WARNING! Sudden Movement Hazard. All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating normally, this could cause death or serious injury.

WARNING! Sudden Movement Hazard. Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should be permitted to wire, inspect, and maintain the Safe Disable input. Failure to comply could cause death or serious injury.

NOTICE: From the moment terminal inputs H1 and HC have opened, it takes up to 1 ms for drive output to shut off completely. The sequence set up to trigger terminals H1-HC should make sure that terminals H1-HC remain open for at least 1 ms in order to properly interrupt drive output.

NOTICE: Drives with safety-related functions need to be replaced after 10 years of use.

D.4 Safe Disable Input

Manual — Safe Disable wiring and operation — page 483

Source reference: SIEP C71060618F, December 2016, physical PDF page 483. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

◆ Using the Safe Disable Function

■ Safe Disable Wiring

If the Safe Disable function is utilized, the wire link between the terminals HC and H1 that is installed at shipment must be removed entirely. Connect the drive to an ISO/EN 13849-1, Safety Category 3 interrupting device so that in case of a Safe Disable request the connection between the terminals HC and H1 is opened.

Figure D.12 Safe Disable Wiring Example

■ Disabling and Enabling the Drive Output (“Safe Torque Off”)

Refer to Figure D.13 for an example of drive operation when switching from the “Safe Torque Off” status until reaching normal operation.

Figure D.13 Safe Disable Operation

Switching from Normal Operation to “Safe Torque Off” Turning OFF (opening) safety input terminal H1-HC will enable the Safe Disable function. Triggering the Safe Disable function while the motor is running will shut off the drive output and motor torque and the motor will coast to stop regardless of the b1-03 setting value. The “Safe Torque Off” status is only possible when using the Safe Disable function. Clear the Run command to stop the drive. Shutting off the drive output, as in a baseblock condition, is not the same as "Safe Torque Off".

Note: Switch OFF terminals H1-HC after the motor has come to a complete stop to prevent the motor from coasting to stop during normal operation.

Returning to Normal Operation from “Safe Torque Off” The safety input releases only when the Run command is not present. • During Stop: Place short circuit between terminals H1 and HC to disable “Safe Torque Off” when the Safe Disable function is triggered during stop. Enter the Run command after the drive stops normally.

D.4 Safe Disable Input

D

Standards Compliance

Figure D.12 Safe Disable wiring example: ISO/EN13849-1 Safety Cat,3 Device; Drive; Power Supply; Controller; HC; H1; M. Exact wiring, semiconductor topology and interlocks remain original-only; full precautions and qualified-personnel conditions mandatory.

Figure D.13: Output Frequency; Motor coasts to stop. Run Command: Run thenStop; Run Command must be released to deactivate Safe Disable. H1 Input: ON (Safe Disable off), OFF (Safe Disable activated); Drive is ready for operation. Drive Output: Normal operation; Safe Torque-Off; Baseblock (Not Safe!). Actual timing/arrow geometry remains original-only; no interval inferred.

Manual — Safe Disable recovery and validation — page 484

Source reference: SIEP C71060618F, December 2016, physical PDF page 484. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.

• During run: Place short circuit between terminals H1 and HC to disable "Safe Torque Off" after clearing the Run command when the Safe Disable function is triggered during stop. Enter the Run command after entering the STOP command regardless of whether terminals H1-HC are ON.

■ Validating Safe Disable Function

Always perform the validation test on the Safe Disable inputs after completing the wiring after start-up, when replacing parts, or when conducting maintenance. Maintain check results as a record of tests performed.

D.4 Safe Disable Input

Selection checks and source differences

Manual communication configuration says255slaves but specificationtable says31drives. Website/catalogue SCCR30kA differs from manual ULsection31kA under statedvoltage/protectionconditions. Do not merge these into a single unqualified rating.

Catalogue CA.VJ.01 (2011) and manual SIEP C71060618F (2016) remain separate. US HP/code schedules do not establish current Australian availability. Shared J1000/VSmini data are excluded from V1000 specifications.

BA0018 appears in both duty columns of the older catalogue; the manual explicitly calls it HD-only. The combined cover and detailed V1000-4X single-phase range differ. No automatic stock or range expansion.

Catalogue pulse input33kHz differs from manual32kHz. Catalogue ramp minimum0.01s differs from manual0.00s; standard frequency0–400 differs from0.01–400Hz. Special1167Hz software is a separate configuration.

Catalogue dimensional summaries, rating pages and drawing tables contain different suffixes, weights or dimensions. Inches,mm(in),kg(lb),thread sizes and wildcard model positions remain literal; no invented conversion or outline equivalence.

Catalogue4X service table repeats NEMA1/OpenChassis headings. Dedicated4X installation manual is referenced but not separately supplied. Manual general enclosure footnotes also differ from its larger-frame IP00 model schedule; confirm exact hardware.

Catalogue calls a hardwire baseblock EN954-1Cat.3, while the later manual distinguishes baseblock from Safe Disable/STO. Use the full later safety section, selected hardware and machine assessment; no current certification claim is made.

Website vibration claim20–50Hz/0.65G differs from manual20–55Hz/5.9m/s². Website28yearMTBF/failure-rate and catalogue historical lead times are not warranties, current availability or maintenance intervals.

DriveWorksEZ standard section118blocks differs from4X119blocks and different access/training language. Catalogue guide calls120VAC interface D1-100 in one reference versusDI-100 in option prose. Confirm exact accessory.

C1 filter section explicitly gives C2 exceptions for some200Vmodels. Manual reactor note referring22kWandhigher lies beyond its stated18.5kWcover range; no larger V1000 model inferred. Historical safety/EMC standards and source logos are not independent current-validity proof.

The collected set contains a60-page shared catalogue and512-page manual, not dedicated dimension PDFs for every catalogue row. All supplied models/parameter tables remain represented; separately referenced option manuals are not treated as downloaded documents.

Product documents

Our company certificates and conditions of sale remain separate from the selected product’s ratings and approvals.

Talk to our team about your application, supply, motor rating and configuration.