Yaskawa V1000 Compact Current Vector Drive
We offer the Yaskawa V1000 for compact, flexible motor control across pumps, fans, conveyors, compressors and general machinery. It combines V/f control, open-loop current vector control and PM open-loop vector control, with application presets, PID, communications and parameter backup to make setup and maintenance more manageable.
Start with your supply, motor nameplate, load and enclosure requirements. The same drive can have different usable current and motor ratings under normal-duty and heavy-duty operation. We keep those ratings together with the exact model and source edition below.
Choose the model, supply and duty
The attached CIMR-VU technical manual, SIEP C71060618F, December 2016, covers these voltage and input-phase classes. Motor output is three-phase; a single-phase-input drive is not a controller for a single-phase motor.
| Manual family | Input class | Published motor range |
|---|---|---|
| BA | Single-phase 200 V class | 0.1–3.7 kW |
| 2A | Three-phase 200 V class | 0.1–18.5 kW |
| 4A | Three-phase 400 V class | 0.2–18.5 kW |
The November 2011 US catalogue CA.VJ.01 separately lists 200–240 V single-phase, 200–240 V three-phase and 380–480 V three-phase supplies, with horsepower schedules. Those historical US model and horsepower listings are not a current Australian stock list. We retain the catalogue's nominal HP, manual kW, rated currents and duty conditions separately; confirm the complete order code and local availability with us.
Heavy Duty (HD) generally suits constant-torque loads and lists 150% rated output current for 60 seconds. Normal Duty (ND) generally suits variable-torque loads and lists 120% for 60 seconds. Parameter C6-01 selects the duty and affects rated current, overload capacity, carrier frequency and associated motor defaults. The manual normally defaults to ND, but BA0018 is HD-only. The older catalogue places BA0018 in both columns with identical values; do not interpret that as a separate ND capability.
Size from the motor current and required overload, then account for ambient temperature, carrier frequency, altitude and mounting. Multiple induction motors require the manual's combined-current sizing and individual motor protection. Multiple synchronous motors must not share a single drive under this manual's instructions.
Enclosures and special variants
Standard and catalogue variants include NEMA Type 1, IP20/IP00 open chassis, finless, built-in C3-filter, conformal-coated, shakeproof and special 1167 Hz software versions. These are specific configurations, not features available together on every model. The catalogue's suffix substitutions and “Consult Factory” cells remain with their own schedules. Finless versions need the specified customer heat-removal arrangement; shakeproof is described for finless versions. Conformal coating does not establish a waterproof enclosure.
The V1000-4X is a separate enclosed family described for NEMA Type 4X/12 indoor use and IP66, including washdown and dust-sensitive applications. Its GAA ratings, dimensions and options remain separate. The catalogue's combined cover range and detailed 4X single-phase range disagree; use the individual model table and confirm the selected unit. The 4X specification page also retains generic NEMA1/Open Chassis ambient labels. The later manual explicitly lists −10°C to +40°C for NEMA Type 4X/IP66, but this does not replace the dedicated 4X installation manual or its model-specific requirements.
The shared catalogue also contains J1000 and VSmini. Their ratings and accessory schedules have not been assigned to V1000. Some V1000-4X and finless instructions are referenced by document number without being supplied as separate attachments; we have not invented their contents.
Control performance and applications
V/f supports general-purpose operation and multiple induction motors. Open-loop vector control provides more responsive speed and torque control after the appropriate motor setup and autotuning. PM open-loop vector supports specified SPM/IPM motors with its own restrictions and settings. The manual describes 200% starting torque at 0.5 Hz only for OLV, HD-rated induction motors of 3.7 kW or smaller; it separately lists 50% at 6 Hz for OLV/PM. These conditions must stay attached to the figures.
Manual speed-control ranges are 1:40 in V/f, 1:100 in OLV and 1:10 in OLV/PM. The stated OLV accuracy and response require the manual's tuning and test conditions. A general torque claim does not establish continuous full torque at very low speed; motor cooling, mechanical limits and the load still govern selection.
The standard manual frequency range is 0.01–400 Hz. The catalogue says 0–400 Hz and separately lists an order-specific 1167 Hz software variant. We do not extend the standard drive's limit to 1167 Hz. The default maximum output frequency is 60 Hz in the application precautions; always match speed limits to the motor and machine.
Functions include 16 preset speeds plus jog, four acceleration/deceleration settings, S-curves, three jump-frequency bands, dwell, slip and torque compensation, speed search, energy saving, over/undertorque detection, torque limiting and configurable power-loss recovery. The catalogue's “simple closed-loop speed control” relates to specific feedback arrangements; it does not make every control mode an encoder-based closed-loop vector system.
Application presets cover water supply pumps, conveyors, exhaust/HVAC fans, compressors and named special presets. Selecting a preset can alter parameters and control mode. PM operation has additional restrictions on braking, load inertia, coasting restart and holding-brake applications; these are retained in the original manual and reference notes. Confirm those restrictions before selecting PM control for transport or lifting equipment. The autotuning chapter explicitly says that autotuning cannot be performed on permanent-magnet motors; their motor code and data require the prescribed PM setup instead.
PID, inputs and communications
PID includes target and feedback selection, reverse action, feedback-loss detection, output limits, integral/derivative settings and sleep/wake control. Its behaviour depends on the selected reference and I/O functions. A loss-of-feedback setting can change whether the drive continues or stops; the feature name alone does not identify a safe process response.
The catalogue lists seven multifunction digital inputs, a programmable relay and two open-collector outputs, analogue monitoring and pulse I/O. Control logic supports NPN/PNP arrangements under the complete terminal instructions. A1 and A2 can accept voltage references; current input uses A2, with the required switch and parameter settings. The manual warns that assigning both A1 and A2 as frequency references adds their values. Do not infer independent selection from the presence of two inputs.
MEMOBUS/Modbus over RS-485/RS-422 is built in. The manual specifies up to 115.2 kbps and retains address, parity, timeout, command sequencing, register and error-code tables. Termination applies at the network ends. The configuration prose refers to 255 slaves, while the communication-specification table lists a maximum of 31 drives. We flag that difference rather than promising a 255-drive installation. Register read/write permissions, Enter-command behaviour and parameter persistence are distinct; do not write unused or reserved addresses. The catalogue's pulse-input limit of 33 kHz differs from the manual's 32 kHz specification and is flagged.
DeviceNet, EtherNet/IP, PROFINET, Profibus-DP, Modbus TCP/IP and MECHATROLINK-II are documented options with their own compatibility requirements. The RJ45-style operator connection is not assumed to be Ethernet. Catalogue software prerequisites include 1010 for SI-P3/V, 1012 for SI-N3/V, SI-EN3/V and SI-EP3/V, 1015 for SI-EM3/V, and 1016 for SI-T3/V. The 4X option list is narrower; confirm its interface and enclosure compatibility rather than transferring the standard-drive list wholesale.
Installation, dimensions and derating
Install vertically in a suitable indoor environment. The manual lists −10°C to +40°C for NEMA Type 1 and −10°C to +50°C for open-chassis/finless versions, with appropriate heat removal. Non-condensing humidity is limited to 95% RH. Storage is listed as −20°C to +60°C, with the specification section qualifying short-term transport. Protect against contamination, sunlight, corrosive materials and excessive vibration.
Standard ratings apply to 1,000 m altitude. Above that, the manual specifies 1% reduction in input voltage and rated output current per 100 m, up to 3,000 m. Carrier-frequency and temperature/mounting derating use the original curves and model tables. We have not interpolated missing curve values. Set the installation/ambient parameters for the actual arrangement; software settings do not provide missing panel cooling.
The standard spacing figure calls for 30 mm side clearance and 100 mm above/below. Compact side-by-side installation is separately illustrated at 2 mm between adjacent drives, with derating, top-cover and L8-35 conditions. This is not permission to remove all installation clearances.
Dimensions, weights, mounting holes and drawing suffixes remain with each source table. The catalogue uses inches in some tables and mm(in) in others, while thread labels such as M5 are not inch measurements. Summary tables and drawings sometimes differ; use the approved outline for the exact enclosure and model before machining or installation.
Braking, protection and Safe Disable
V1000 has a built-in braking transistor, but resistor selection and permissible duty remain application-specific. The catalogue's 3% and 10% duty resistor schedules use a 100-second interval. Higher duty requires supplier selection. Braking resistors need the specified thermal protection and interlock; a parameter setting does not protect every resistor type. PM braking and stall-prevention options have additional restrictions.
Protection functions include motor/drive overload, over/undervoltage, overcurrent, phase-loss and temperature functions, with configurable fault, restart and stopping responses. Some ground-fault conditions are expressly outside the drive's protection. For multiple motors, the manual requires individual thermal overload protection and disables the drive's single-motor electronic overload model.
The later manual describes Safe Disable / Safe Torque Off, with historical Cat.3/PL d and SIL2 claims under its stated standards and conditions. This switches off torque-producing output; it does not electrically isolate the drive, hold a vertical load or make an external brake a safety component. Baseblock is not the same function. PM motors can still move under the documented transistor-fault scenario, and gravity can move the load.
A qualified designer must assess and validate the complete machine safety system using the full manual, applicable requirements and the selected drive. The manual requires validation after wiring, startup, replacement and maintenance, with records retained, and states that drives with safety-related functions need replacement after ten years of use. We preserve these source conditions without claiming current certification or approval of a particular installation.
Setup, backup and maintenance
Commissioning includes the correct motor data, control mode, run/reference sources, duty, protection, applicable autotuning and no-load/loaded checks. Initialisation, application presets, LOCAL/REMOTE changes and fault recovery can alter behaviour or cause unexpected movement. The guide is a selection and reference resource; use the complete manual for qualified installation and commissioning.
The removable terminal board stores parameters and can help with drive replacement. It is not an unrestricted swap between different capacities or voltage classes: the manual calls for reinitialisation in those cases and describes the oPE04 handling sequence. JVOP-181 can read, copy and verify settings between compatible drives; DriveWizard Plus supports parameter storage, monitoring and graphing. Confirm software compatibility before applying a backup.
Maintenance monitors cover fans, capacitors, inrush circuits and IGBTs. Estimated component life depends on the stated environment, load and operating hours. The website's “28 years MTBF” and “1 in 10,000 failure rate” are historical promotional claims, not a service-life warranty or replacement interval. The manual's safety-related replacement condition is separate.
Service work requires isolation, discharge verification and the complete warnings. The manual specifies waiting at least five minutes after indicators are off and measuring the DC bus before service; the warning label and full procedure still apply. PM back-generated voltage and external supplies must also be considered. Cooling-fan replacement requires the heatsink to cool; software stop is not isolation.
Accessories and source editions
Model-specific options include 3%/5% reactors, C1/C3 EMC filters, braking resistors, DIN kits, V7 adapter plates, external-heatsink kits, 24 V control-power units with their required brackets, remote operators and operator mounting kits. JVOP-180 requires catalogue software 1012 or later; JVOP-182 requires 1016 or later. A 24 V control-power option maintains controls/communications; it does not power the motor.
The catalogue's C1-filter heading includes an explicit C2 exception for certain larger 200 V models. EMC outcomes also depend on the specified filter, wiring, shielding, grounding and installation; the drive alone does not establish a compliant system. The website/catalogue quote 30 kA SCCR, while the manual’s UL section states 31,000 RMS symmetrical amperes under its voltage and protection conditions. We retain both source statements and require confirmation of the selected model and protective devices. Historical listing claims do not establish current certification.
DriveWorksEZ provides function-block customisation, but its standard/pro descriptions differ between catalogue sections: the standard V1000 section lists 118 basic blocks, while the 4X section lists 119 and different training/access wording. We retain that difference and do not promise current licensing, training or download access.
The source references below retain rating, variant, dimension, accessory, parameter, default, diagnostic and register tables with their conditions. Repeated manual chunk overlap is removed; different source editions remain distinct. Full drawings, curves and procedures stay in the linked PDFs. Tell us the exact model, motor, supply, duty, enclosure, environment, communications and braking needs so we can confirm the configuration.
Catalogue — V1000 description and specifications — page 25
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Control:V/f,OpenLoopCurrentVector,PMOpenLoopCurrentVector andsimpleclosed-loopspeedcontrol. DCinjectionbraking/rampstop;electronicreversing;infinitelyadjustableV/Hzpattern;adjustablebrakingamplitude/duration/currentlimit;full-rangeautotorqueboost;speedsearch;autorestart;slipcompensation;energy-savingfunction;enhancedPIDwithfeedbackloss.
LEDstatusdisplay,remotemountkeypad,RJ-45styledigitaloperatorconnector;signal-followerbias/gain;coolingfancontrolledbyrun/stop;UL-recognizedelectronicoverload;built-indynamicbrakingtransistor;applicationpresets;maintenancemonitors.
Protection:currentlimit/stallpreventionduringaccel/decel/run;motoranddriveoverload;overvoltageprevention;instantaneousovercurrent;shortcircuit;undervoltage;heatsinkoverheat;groundfault;over/undertorque.
Side-by-sidemounting. Short-circuitcurrentrating30kArms symmetrical.
Context: Standards,MTBF,safety/category andlisting statements are historical supplierclaims, not independent compliance/certificatevalidation.
Table conditions: Sourcepage family-specific. Footnote1=V/fmode,2=OpenLoopCurrentVectorMode; preserve rating/duty distinctions. Analogresolution0.06/60Hz retained literally.
Table conditions: Printeddesignfeatures; do not infer availability from historicalcatalogue.
Table conditions: Exactprinted enclosure labels retained;4Xpage ambiguity flagged. No expanded environmentalrating inferred.
Table conditions: Historical source claims only; no current regulatoryapproval orcertificatevalidity assertion.
Table conditions: Option listing; compatibility requires source/factory confirmation. Detailed option tables are retained in their relevant sections.
Performance specifications — PDF page 25
| Source label/context | Source value |
|---|---|
| Ratings /200–240VAC1phase | 1/8 to5HP |
| Ratings /200–240VAC3phase | 1/8 to25HP(ND) |
| Ratings /380–480VAC3phase | 1/2 to25HP(ND) |
| Heavy Duty overload | 150% for60sec |
| Normal Duty overload | 120% for60sec |
| Acceleration/deceleration | 0.01 to6000seconds |
| Controlled speed range /V/fMode | 40:1 |
| Controlled speed range /OpenLoopCurrentVectorMode | 100:1 |
| Speed regulation /V/fMode withslipcompensation | ±0.5 to1% |
| Speed regulation /OpenLoopCurrentVectorMode | ±0.2% |
| Displacement power factor | 0.98 |
| Output frequency | 0 to400Hz |
| Frequency resolution /digitalreference | 0.01Hz |
| Frequency resolution /analogreference | 0.06 /60Hz |
| Frequency accuracy /digitalcommand | 0.01% |
| Frequency accuracy /analogcommand | 0.5% |
| Power loss ride-through | 0.5sec |
| Critical frequency rejection settings | 3 |
Design specifications — PDF page 25
| Source label/context | Source value |
|---|---|
| Processors | Dualmicroprocessorlogic |
| Keypad | Digitaloperator,5digits |
| Digital inputs | 7multifunction |
| Digital outputs | 3multifunction |
| Hardwire baseblock | EN954-1Cat.3 |
| Programmable FormCcontact | 1A at250VAC or30VDC |
| Control logic | 24VDC;PNPorNPN sourcing/sinking compatible |
| Carrier frequency | 15kHzmaximum;swingPWM |
| Speed settings | 16multi-speed plusjog |
| Remote speed references | 2;0–10VDC(20kohms) orisolated4–20mA(250ohms) |
| Open collector outputs | 2programmable |
| Analog monitor | 0–10VDC proportional tooutputfrequency oroutputcurrent |
| Parameters andmonitors | Approximately400 |
| Pulse traininput | 33kHzmaximum |
| Communication | RS-422/485Modbus115kbps |
| MTBF | 28years |
| Enclosure | NEMA1 |
Service conditions — PDF page 25
| Source label/context | Source value |
|---|---|
| Ambient service /NEMA1 | −10 to40°C(+14 to104°F) |
| Ambient service /OpenChassis | −10 to50°C(+14 to122°F) |
| Ambient storage | −20 to60°C(−4 to140°F) |
| Humidity | to95%,non-condensing |
| Altitude | to3300ft;higherbyderating |
| Service factor | 1.0 |
| Inputvoltage tolerance | −15% to+10%;200–240VAC,380–480VAC |
| Inputfrequency | ±5%;50/60Hz |
| Inputphase sequence | Insensitive |
Printed standards and claims — PDF page 25
| Source label/context | Source value |
|---|---|
| UL | 508C(PowerConversion) |
| CSA | 22.2No.14-95(IndustrialControlEquipment) |
| Listings/marking | UL,cULlisted;CEmarked |
| RoHS | Compliant |
| LVD | EN50178 |
| EMC | EN50081-2,EN50082-2 |
| Safety | EN954-1,Category3 |
| OtherEN | EN61800-3 |
| IEC | 529,146 |
| FCC | CFR47Part15SubpartB;withExternalFilter |
| TUV | Printed claim |
Listed options — PDF page 25
| Source label/context | Source value |
|---|---|
| 1 | Externaldynamicbrakingresistor |
| 2 | MultilingualfulltextremoteLCDwithcopy |
| 3 | Profibus-DP |
| 4 | DeviceNet |
| 5 | ModbusTCP/IP |
| 6 | EtherNet/IP |
| 7 | MECHATROLINK-II |
| 8 | DriveWizardPlus |
| 9 | CASEsoftware |
| 10 | DINrailmountingkit |
| 11 | USBCopyUnit(Y-Stick) |
| 12 | Reactors3%and5% |
| 13 | EMCfiltersC1andC3 |
| 14 | Adapterplates |
| 15 | Externalheatsinkkits |
| 16 | 24Vcontrolpowerunit |
| 17 | RemoteLEDoperator |
| 18 | RemoteLCDoperator |
| 19 | 120Vinterface |
Catalogue — V1000 standard drive ratings — page 27
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: Sourcepage ratings kept separate fromdimensionandvariantpages; discrepancies retained.
Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HPbasedon230/460V,NEMAB4poleinductionmotors;NECtable430.250. Typicallyinstock statement historical.
Standard drives — PDF page 27
| Rated input voltage/phase | Model suffix (CIMR-VU) | ND output A | ND nominal HP | HD output A | HD nominal HP |
|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001FAA | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 |
| 200-240V 1-Phase | BA0002FAA | 1.9 | 1/4 | 1.6 | 1/4 |
| 200-240V 1-Phase | BA0003FAA | 3.3 | 1/2 & 3/4 | 3.0 | 1/2 |
| 200-240V 1-Phase | BA0006FAA | 6.0 | 1 | 5.0 | 3/4 & 1 |
| 200-240V 1-Phase | BA0010FAA | 9.6 | 2 & 3 | 8.0 | 2 |
| 200-240V 1-Phase | BA0012FAA | 12.0 | 3 | 11.0 | 3 |
| 200-240V 1-Phase | BA0018FAA | 17.5 | 5 | 17.5 | 5 |
| 200-240V 3-Phase | 2A0001FAA | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 |
| 200-240V 3-Phase | 2A0002FAA | 1.9 | 1/4 | 1.6 | 1/4 |
| 200-240V 3-Phase | 2A0004FAA | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 |
| 200-240V 3-Phase | 2A0006FAA | 6.0 | 1 | 5.0 | 3/4 & 1 |
| 200-240V 3-Phase | 2A0010FAA | 9.6 | 2 & 3 | 8.0 | 2 |
| 200-240V 3-Phase | 2A0012FAA | 12.0 | 3 | 11 | 3 |
| 200-240V 3-Phase | 2A0020FAA | 19.6 | 5 | 17.5 | 5 |
| 200-240V 3-Phase | 2A0030FAA | 30.0 | 7.5 & 10 | 25.0 | 7.5 |
| 200-240V 3-Phase | 2A0040FAA | 40.0 | 10 | 33.0 | 10 |
| 200-240V 3-Phase | 2A0056FAA | 56.0 | 15 & 20 | 47.0 | 15 |
| 200-240V 3-Phase | 2A0069FAA | 69.0 | 25 | 60.0 | 20 |
| 380-480V 3-Phase | 4A0001FAA | 1.2 | 1/2 | 1.2 | 1/2 |
| 380-480V 3-Phase | 4A0002FAA | 2.1 | 3/4 & 1 | 1.8 | 3/4 |
| 380-480V 3-Phase | 4A0004FAA | 4.1 | 2 | 3.4 | 1 & 2 |
| 380-480V 3-Phase | 4A0005FAA | 5.4 | 3 | 4.8 | 3 |
| 380-480V 3-Phase | 4A0007FAA | 6.9 | 4 | 5.5 | 3 |
| 380-480V 3-Phase | 4A0009FAA | 8.8 | 5 | 7.2 | 4 |
| 380-480V 3-Phase | 4A0011FAA | 11.1 | 7.5 | 9.2 | 5 |
| 380-480V 3-Phase | 4A0018FAA | 17.5 | 10 | 14.8 | 7.5 & 10 |
| 380-480V 3-Phase | 4A0023FAA | 23.0 | 15 | 18.0 | 10 |
| 380-480V 3-Phase | 4A0031FAA | 31.0 | 20 | 24.0 | 15 |
| 380-480V 3-Phase | 4A0038FAA | 38.0 | 25 | 31.0 | 20 |
Catalogue — V1000 Finless, Open, C3filter variants — page 28
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Finless(flatheatsink) intendedforcustomer enclosurewithexternalheatsink;replaceFAAwithJAA(orLAA).
Openchassis intendedforcustomer enclosure;BAA=IP20,AAA=IP00;replaceFAAwithBAA(orAAA).
C3filter builtin;replaceFAAwithEAA. Text refers toEMCC3filters onprintedpage29; thatpage is adimensiondrawing inthiscatalogue, so cross-reference flagged.
Context: ConsultFactory is explicitsourcecontent with physicalmergedcellscope, not missing modelnumber or zero.
Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HP:NEMAB4pole,NEC430.150. Allvariantdrives16weekleadtimeunlessforecastprovided; historicalonly. Consultfactory foroptioncompatibility. Differentvoltageclasslabels200V/400V retained.
Variant availability and ratings — PDF page 28
| Ratedinputvoltage/phase | NDoutputA | NDnominalHP | HDoutputA | HDnominalHP | Finless model suffix (CIMR-VU) | Open model suffix (CIMR-VU) | C3filter model suffix (CIMR-VU) |
|---|---|---|---|---|---|---|---|
| 200V, 1-Phase | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | BA0001JAA | BA0001BAA | BA0001EAA |
| 200V, 1-Phase | 1.9 | 1/4 | 1.6 | 1/4 | BA0002JAA | BA0002BAA | BA0002EAA |
| 200V, 1-Phase | 3.3 | 1/2 & 3/4 | 3.0 | 1/2 | BA0003JAA | BA0003BAA | BA0003EAA |
| 200V, 1-Phase | 6.0 | 1 | 5.0 | 3/4 & 1 | BA0006JAA | BA0006BAA | BA0006EAA |
| 200V, 1-Phase | 9.6 | 2 & 3 | 8.0 | 2 | BA0010JAA | BA0010BAA | BA0010EAA |
| 200V, 1-Phase | 12.0 | 3 | 11.0 | 3 | BA0012JAA | BA0012BAA | BA0012EAA |
| 200V, 1-Phase | 17.5 | 5 | 17.5 | 5 | Consult Factory | BA0018BAA | Consult Factory |
| 200V, 3-Phase | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | 2A0001JAA | 2A0001BAA | Consult Factory |
| 200V, 3-Phase | 1.9 | 1/4 | 1.6 | 1/4 | 2A0002JAA | 2A0002BAA | Consult Factory |
| 200V, 3-Phase | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 | 2A0004JAA | 2A0004BAA | Consult Factory |
| 200V, 3-Phase | 6.0 | 1 | 5.0 | 3/4 & 1 | 2A0006JAA | 2A0006BAA | Consult Factory |
| 200V, 3-Phase | 9.6 | 2 & 3 | 8.0 | 2 | 2A0010JAA | 2A0010BAA | Consult Factory |
| 200V, 3-Phase | 12.0 | 3 | 11.0 | 3 | 2A0012JAA | 2A0012BAA | Consult Factory |
| 200V, 3-Phase | 19.6 | 5 | 17.5 | 5 | 2A0020JAA | 2A0020BAA | Consult Factory |
| 200V, 3-Phase | 30.0 | 7.5 & 10 | 25.0 | 7.5 | 2A0030JAA | 2A0030AAA | Consult Factory |
| 200V, 3-Phase | 40.0 | 10 | 33.0 | 10 | 2A0040JAA | 2A0040AAA | Consult Factory |
| 200V, 3-Phase | 56.0 | 20 | 47.0 | 15 | 2A0056JAA | 2A0056AAA | Consult Factory |
| 200V, 3-Phase | 69.0 | 25 | 60.0 | 20 | 2A0069LAA | 2A0069AAA | Consult Factory |
| 400V, 3-Phase | 1.2 | 1/2 | 1.2 | 1/2 | 4A0001JAA | 4A0001BAA | 4A0001EAA |
| 400V, 3-Phase | 2.1 | 3/4 & 1 | 1.8 | 3/4 | 4A0002JAA | 4A0002BAA | 4A0002EAA |
| 400V, 3-Phase | 4.1 | 2 | 3.4 | 1 & 2 | 4A0004JAA | 4A0004BAA | 4A0004EAA |
| 400V, 3-Phase | 5.4 | 3 | 4.8 | 3 | 4A0005JAA | 4A0005BAA | 4A0005EAA |
| 400V, 3-Phase | 6.9 | 4 | 5.5 | 3 | 4A0007JAA | 4A0007BAA | 4A0007EAA |
| 400V, 3-Phase | 8.8 | 5 | 7.2 | 4 | 4A0009JAA | 4A0009BAA | 4A0009EAA |
| 400V, 3-Phase | 11.1 | 7.5 | 9.2 | 5 | 4A0011JAA | 4A0011BAA | 4A0011EAA |
| 400V, 3-Phase | 18.0 | 10 | 15.0 | 7.5 & 10 | 4A0018JAA | 4A0018AAA | Consult Factory |
| 400V, 3-Phase | 23.0 | 15 | 18.0 | 10 | 4A0023JAA | 4A0023AAA | Consult Factory |
| 400V, 3-Phase | 31.0 | 20 | 25.8 | 15 | 4A0031JAA | 4A0031AAA | Consult Factory |
| 400V, 3-Phase | 38.0 | 25 | 31.7 | 20 | 4A0038JAA | 4A0038AAA | Consult Factory |
Catalogue — V1000 Conformalcoat, Shakeproof, 1167Hz variants — page 29
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Conformalcoat:Humiseal circuitboards forhumidity/dustresistance;openchassisonly;FAA→BMA(orAMA).
Shakeproof:strengthenedcomponentsforvibrationresistance;finlessversiononly;FAA→JSA.
1167Hzsoftware permitsoutputupto1167Hz;deleteCIMR-prefixandadd-134. Printedcolumn prefixVU is distinctfromCIMR-VU.
Context: ConsultFactory is explicitsourcecontent with physicalmergedcellscope, not missing modelnumber or zero.
Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HP:NEMAB4pole,NEC430.150. Allvariantdrives16weekleadtimeunlessforecastprovided; historicalonly. Consultfactory foroptioncompatibility. Differentvoltageclasslabels200V/400V retained.
Variant availability and ratings — PDF page 29
| Ratedinputvoltage/phase | NDoutputA | NDnominalHP | HDoutputA | HDnominalHP | Conformalcoat model suffix (CIMR-VU) | Shakeproof model suffix (CIMR-VU) | 1167Hz model suffix (VU) |
|---|---|---|---|---|---|---|---|
| 200V, 1-Phase | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | Consult Factory | Consult Factory | BA0001FAA-134 |
| 200V, 1-Phase | 1.9 | 1/4 | 1.6 | 1/4 | Consult Factory | Consult Factory | BA0002FAA-134 |
| 200V, 1-Phase | 3.3 | 1/2 & 3/4 | 3.0 | 1/2 | Consult Factory | Consult Factory | BA0003FAA-134 |
| 200V, 1-Phase | 6.0 | 1 | 5.0 | 3/4 & 1 | Consult Factory | Consult Factory | BA0006FAA-134 |
| 200V, 1-Phase | 9.6 | 2 & 3 | 8.0 | 2 | Consult Factory | BA00100JSA | BA0010FAA-134 |
| 200V, 1-Phase | 12.0 | 3 | 11.0 | 3 | Consult Factory | Consult Factory | BA0012FAA-134 |
| 200V, 1-Phase | 17.5 | 5 | 17.5 | 5 | Consult Factory | Consult Factory | BA0018FAA-134 |
| 200V, 3-Phase | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | Consult Factory | Consult Factory | 2A0001FAA-134 |
| 200V, 3-Phase | 1.9 | 1/4 | 1.6 | 1/4 | 2A0002BMA | Consult Factory | 2A0002FAA-134 |
| 200V, 3-Phase | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 | 2A0004BMA | Consult Factory | 2A0004FAA-134 |
| 200V, 3-Phase | 6.0 | 1 | 5.0 | 3/4 & 1 | 2A0006BMA | 2A0006JSA | 2A0006FAA-134 |
| 200V, 3-Phase | 9.6 | 2 & 3 | 8.0 | 2 | 2A0010BMA | 2A0010JSA | 2A0010FAA-134 |
| 200V, 3-Phase | 12.0 | 3 | 11.0 | 3 | 2A0012BMA | 2A0012JSA | 2A0012FAA-134 |
| 200V, 3-Phase | 19.6 | 5 | 17.5 | 5 | 2A0020BMA | 2A0020JSA | 2A0020FAA-134 |
| 200V, 3-Phase | 30.0 | 7.5 & 10 | 25.0 | 7.5 | 2A0030BMA | 2A0030JSA | 2A0030FAA-134 |
| 200V, 3-Phase | 40.0 | 10 | 33.0 | 10 | 2A0040BMA | Consult Factory | 2A0040FAA-134 |
| 200V, 3-Phase | 56.0 | 20 | 47.0 | 15 | Consult Factory | Consult Factory | 2A0056FAA-134 |
| 200V, 3-Phase | 69.0 | 25 | 60.0 | 20 | Consult Factory | Consult Factory | 2A0069FAA-134 |
| 400V, 3-Phase | 1.2 | 1/2 | 1.2 | 1/2 | Consult Factory | Consult Factory | 4A0001FAA-134 |
| 400V, 3-Phase | 2.1 | 3/4 & 1 | 1.8 | 3/4 | 4A0002BMA | Consult Factory | 4A0002FAA-134 |
| 400V, 3-Phase | 4.1 | 2 | 3.4 | 1 & 2 | 4A0004BMA | 4A0004JSA | 4A0004FAA-134 |
| 400V, 3-Phase | 5.4 | 3 | 4.8 | 3 | 4A0005BMA | 4A0005JSA | 4A0005FAA-134 |
| 400V, 3-Phase | 6.9 | 4 | 5.5 | 3 | 4A0007BMA | 4A0007JSA | 4A0007FAA-134 |
| 400V, 3-Phase | 8.8 | 5 | 7.2 | 4 | 4A0009BMA | 4A0009JSA | 4A0009FAA-134 |
| 400V, 3-Phase | 11.1 | 7.5 | 9.2 | 5 | 4A0011BMA | 4A0011JSA | 4A0011FAA-134 |
| 400V, 3-Phase | 18.0 | 10 | 15.0 | 7.5 & 10 | 4A0018AMA | Consult Factory | 4A0018FAA-134 |
| 400V, 3-Phase | 23.0 | 15 | 18.0 | 10 | 4A0023AMA | Consult Factory | 4A0023FAA-134 |
| 400V, 3-Phase | 31.0 | 20 | 25.8 | 15 | Consult Factory | Consult Factory | 4A0031FAA-134 |
| 400V, 3-Phase | 38.0 | 25 | 31.7 | 20 | Consult Factory | Consult Factory | 4A0038FAA-134 |
Catalogue — V1000 summary dimensions and data — page 30
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: Sourcewildcard__A retained; do not turn it into aconcreteordercode. Summaryratings/dimensions differ fromotherpages andremainseparate.
Table conditions: Physicaldimensions heading(in.); mountingheadingdoesnotrepeatunit. Weightisdriveweight,notshipping. PreserveDD.V1K.FR_ source reference distinct fromDD.V1000 drawingtitles.
Summary dimensions and data — PDF page 30
| Ratedinputvoltage/phase | Printedmodel(CIMR-VU) | NDoutputA | NDnominalHP | HDoutputA | HDnominalHP | H in | W in | D in | H1 mounting (source unit not repeated) | W1 mounting (source unit not repeated) | Driveweight lb | Drawingnumber suffix DD.V1K.FR_ |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | 5.89 | 2.68 | 2.99 | 5.10 | 2.20 | 1.8 | 1 |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | 1.6 | 1/4 | 5.89 | 2.68 | 2.99 | 5.10 | 2.20 | 1.8 | 1 |
| 200-240V 1-Phase | BA0003__A | 3.3 | 1/2 & 3/4 | 3.0 | 1/2 | 5.89 | 2.68 | 4.65 | 5.10 | 2.20 | 2.6 | 3 |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | 5.0 | 3/4 & 1 | 5.89 | 4.25 | 5.41 | 5.10 | 3.78 | 4.2 | 8 |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | 8.0 | 2 | 5.89 | 4.25 | 6.06 | 5.10 | 3.78 | 4.4 | 10 |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | 11.0 | 3 | 6.02 | 5.51 | 6.42 | 5.24 | 5.04 | 5.7 | 12 |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | 17.5 | 5 | 6.02 | 6.69 | 7.09 | 5.24 | 6.22 | 6.6 | 13 |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | 5.89 | 2.68 | 2.99 | 5.10 | 2.20 | 1.8 | 1 |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | 1.6 | 1/4 | 5.89 | 2.68 | 2.99 | 5.10 | 2.20 | 1.8 | 1 |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | 3 | 1/2 | 5.89 | 2.68 | 4.25 | 5.10 | 2.20 | 2.4 | 2 |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | 5 | 3/4 & 1 | 5.89 | 2.68 | 5.04 | 5.10 | 2.20 | 2.9 | 4 |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | 8 | 2 | 5.89 | 4.25 | 5.08 | 5.10 | 3.78 | 4.2 | 7 |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | 11 | 3 | 5.89 | 4.25 | 5.41 | 5.10 | 3.78 | 4.2 | 8 |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | 17.5 | 5 | 6.02 | 5.51 | 5.63 | 5.24 | 5.04 | 5.7 | 11 |
| 200-240V 3-Phase | 2A0030__A | 30.0 | 7.5 & 10 | 25.0 | 7.5 | 10.00 | 5.51 | 5.51 | 9.76 | 4.80 | 8.4 | 14 |
| 200-240V 3-Phase | 2A0040__A | 40.0 | 10 | 33.0 | 10 | 10.00 | 5.51 | 5.51 | 9.76 | 4.80 | 8.4 | 14 |
| 200-240V 3-Phase | 2A0056__A | 56.0 | 20 | 47.0 | 15 | 11.42 | 7.09 | 6.42 | 11.18 | 6.30 | 12.1 | 16 |
| 200-240V 3-Phase | 2A0069__A | 69.0 | 25 | 57.5 | 20 | 14.09 | 8.66 | 7.36 | 13.23 | 7.56 | 20.2 | 17 |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | 1.2 | 1/2 | 5.89 | 4.25 | 3.19 | 5.10 | 3.78 | 2.6 | 5 |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | 1.8 | 3/4 | 5.89 | 4.25 | 3.90 | 5.10 | 3.78 | 3.1 | 6 |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | 3.4 | 1 & 2 | 5.89 | 4.25 | 5.41 | 5.10 | 3.78 | 3.5 | 8 |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | 4.8 | 3 | 5.89 | 4.25 | 6.06 | 5.10 | 3.78 | 4.2 | 9 |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | 5.5 | 3 | 5.89 | 4.25 | 6.06 | 5.10 | 3.78 | 4.2 | 9 |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | 7.2 | 4 | 5.89 | 4.25 | 6.06 | 5.10 | 3.78 | 4.2 | 9 |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | 9.2 | 5 | 6.02 | 5.51 | 5.63 | 5.24 | 5.04 | 5.7 | 11 |
| 380-480V 3-Phase | 4A0018__A | 18.0 | 10 | 15.0 | 7.5 & 10 | 10.00 | 5.51 | 5.51 | 9.21 | 4.80 | 8.4 | 14 |
| 380-480V 3-Phase | 4A0023__A | 24.0 | 15 | 19.2 | 10 | 10.00 | 5.51 | 5.51 | 9.21 | 4.80 | 8.4 | 14 |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | 25.8 | 15 | 11.42 | 7.09 | 5.63 | 10.63 | 6.30 | 11.4 | 15 |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | 31.7 | 20 | 11.42 | 7.09 | 6.42 | 10.63 | 6.30 | 12.1 | 16 |
Catalogue — DD.V1000.01 NEMA1 dimension drawing — page 31
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: Onlylabelledtabularvalues andexplicitcallouts normalized; geometry/orientation staysinoriginal. ShortmodelsuffixF preserved independentlyofFAA/__A elsewhere.
Table conditions: PrintedDD.V1000.01; sourceall dimensionheaders(in) butd=M5threadnotation not aninchvalue. Do not reconcile differences withsummary byassumption.
Table conditions: Literaldiagramcallout; no inferredholegeometry ormountingprocedure.
NEMA1 drawing dimension table — PDF page 31
| Voltageclass | Model(CIMR-VU) | W1 in | H2 in | W in | H1 in | D in | t1 in | H5 in | D1 in | H in | H4 in | H3 in | H6 in | Weight lb |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Single-Phase200V Class | BA0001F | 2.20 | 4.65 | 2.68 | 5.03 | 2.99 | 0.12 | 0.20 | 0.26 | 5.89 | 0.79 | 0.16 | 0.06 | 1.8 |
| Single-Phase200V Class | BA0002F | 2.20 | 4.65 | 2.68 | 5.03 | 2.99 | 0.12 | 0.20 | 0.26 | 5.89 | 0.79 | 0.16 | 0.06 | 1.8 |
| Single-Phase200V Class | BA0003F | 2.20 | 4.65 | 2.68 | 5.03 | 4.65 | 0.20 | 0.20 | 1.54 | 5.89 | 0.79 | 0.16 | 0.06 | 2.6 |
| Three-Phase200V Class | 2A0001F | 2.20 | 4.65 | 2.68 | 5.03 | 2.99 | 0.12 | 0.20 | 0.26 | 5.89 | 0.79 | 0.16 | 0.06 | 1.8 |
| Three-Phase200V Class | 2A0002F | 2.20 | 4.65 | 2.68 | 5.03 | 2.99 | 0.12 | 0.20 | 0.26 | 5.89 | 0.79 | 0.16 | 0.06 | 1.8 |
| Three-Phase200V Class | 2A0004F | 2.20 | 4.65 | 2.68 | 5.03 | 4.25 | 0.20 | 0.20 | 1.54 | 5.89 | 0.79 | 0.16 | 0.06 | 2.4 |
| Three-Phase200V Class | 2A0006F | 2.20 | 4.65 | 2.68 | 5.03 | 5.04 | 0.20 | 0.20 | 2.32 | 5.89 | 0.79 | 0.16 | 0.06 | 2.9 |
Explicit mounting callout — PDF page 31
| Source label/context | Source value |
|---|---|
| Mounting | 2-M4 |
Catalogue — DD.V1000.02 NEMA1 dimension drawing — page 32
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: Onlylabelledtabularvalues andexplicitcallouts normalized; geometry/orientation staysinoriginal. ShortmodelsuffixF preserved independentlyofFAA/__A elsewhere.
Table conditions: PrintedDD.V1000.02; sourceall dimensionheaders(in) butd=M5threadnotation not aninchvalue. Do not reconcile differences withsummary byassumption.
Table conditions: Literaldiagramcallout; no inferredholegeometry ormountingprocedure.
NEMA1 drawing dimension table — PDF page 32
| Voltageclass | Model(CIMR-VU) | W1 in | H2 in | W in | H1 in | D in | t1 in | H5 in | D1 in | H in | H4 in | H3 in | H6 in | Weight lb |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Single-Phase200V Class | BA0006F | 3.78 | 4.65 | 4.25 | 5.03 | 5.41 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.2 |
| Single-Phase200V Class | BA0010F | 3.78 | 4.65 | 4.25 | 5.03 | 6.06 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.4 |
| Single-Phase200V Class | BA0012F | 5.04 | 4.65 | 5.51 | 5.03 | 6.42 | 0.20 | 0.20 | 2.56 | 6.02 | 0.79 | 0.19 | 0.20 | 5.7 |
| Single-Phase200V Class | BA0018F | 6.22 | 4.64 | 6.69 | 5.23 | 7.08 | 0.20 | 0.20 | 2.56 | 6.73 | 1.50 | 0.19 | 0.20 | 7.3 |
| Three-Phase200V Class | 2A0010F | 3.78 | 4.65 | 4.25 | 5.03 | 5.08 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.2 |
| Three-Phase200V Class | 2A0012F | 3.78 | 4.65 | 4.25 | 5.03 | 5.41 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.2 |
| Three-Phase200V Class | 2A0020F | 5.04 | 4.65 | 5.51 | 5.03 | 5.63 | 0.20 | 0.20 | 2.56 | 6.02 | 0.79 | 0.19 | 0.20 | 5.7 |
| Three-Phase400V Class | 4A0001F | 3.78 | 4.65 | 4.25 | 5.03 | 3.19 | 0.20 | 0.20 | 0.39 | 5.89 | 0.79 | 0.16 | 0.06 | 2.6 |
| Three-Phase400V Class | 4A0002F | 3.78 | 4.65 | 4.25 | 5.03 | 3.90 | 0.20 | 0.20 | 1.10 | 5.89 | 0.79 | 0.16 | 0.06 | 3.1 |
| Three-Phase400V Class | 4A0004F | 3.78 | 4.65 | 4.25 | 5.03 | 5.41 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.2 |
| Three-Phase400V Class | 4A0005F | 3.78 | 4.65 | 4.25 | 5.03 | 6.06 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.2 |
| Three-Phase400V Class | 4A0007F | 3.78 | 4.65 | 4.25 | 5.03 | 6.06 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.2 |
| Three-Phase400V Class | 4A0009F | 3.78 | 4.65 | 4.25 | 5.03 | 6.06 | 0.20 | 0.20 | 2.28 | 5.89 | 0.79 | 0.16 | 0.06 | 4.2 |
| Three-Phase400V Class | 4A0011F | 5.04 | 4.65 | 5.51 | 5.03 | 5.63 | 0.20 | 0.20 | 2.56 | 6.02 | 0.79 | 0.19 | 0.20 | 5.7 |
Explicit mounting callout — PDF page 32
| Source label/context | Source value |
|---|---|
| Mounting | 4-M4 |
Catalogue — DD.V1000.03 NEMA1 dimension drawing — page 33
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: Onlylabelledtabularvalues andexplicitcallouts normalized; geometry/orientation staysinoriginal. ShortmodelsuffixF preserved independentlyofFAA/__A elsewhere.
Table conditions: PrintedDD.V1000.03; sourceall dimensionheaders(in) butd=M5threadnotation not aninchvalue. Do not reconcile differences withsummary byassumption.
Table conditions: Literaldiagramcallout; no inferredholegeometry ormountingprocedure.
NEMA1 drawing dimension table — PDF page 33
| Voltageclass | Model(CIMR-VU) | W1 in | H2 in | W in | H1 in | D in | t1 in | H5 in | D1 in | H in | H4 in | H3 in | H6 in | d threaddesignation | Weight lb |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Three-Phase200V Class | 2A0030F | 4.80 | 9.76 | 5.51 | 9.21 | 5.51 | 0.20 | 0.51 | 2.17 | 10.00 | 0.51 | 0.24 | 0.06 | M5 | 8.4 |
| Three-Phase200V Class | 2A0040F | 4.80 | 9.76 | 5.51 | 9.21 | 5.51 | 0.20 | 0.51 | 2.17 | 10.00 | 0.51 | 0.24 | 0.06 | M5 | 8.4 |
| Three-Phase200V Class | 2A0056F | 6.30 | 11.18 | 7.09 | 10.63 | 6.42 | 0.20 | 0.51 | 2.95 | 11.42 | 0.59 | 0.24 | 0.06 | M5 | 12.1 |
| Three-Phase200V Class | 2A0069F | 7.56 | 13.23 | 8.66 | 12.60 | 7.36 | 0.20 | 0.87 | 3.07 | 13.78 | 0.59 | 0.28 | 0.06 | M5 | 20.3 |
| Three-Phase400V Class | 4A0018F | 4.80 | 9.76 | 5.51 | 9.21 | 5.51 | 0.20 | 0.51 | 2.17 | 10.00 | 0.51 | 0.24 | 0.06 | M5 | 8.4 |
| Three-Phase400V Class | 4A0023F | 4.80 | 9.76 | 5.51 | 9.21 | 5.51 | 0.20 | 0.51 | 2.17 | 10.00 | 0.51 | 0.24 | 0.06 | M5 | 8.4 |
| Three-Phase400V Class | 4A0031F | 6.30 | 11.18 | 7.09 | 10.63 | 5.63 | 0.20 | 0.51 | 2.17 | 11.42 | 0.59 | 0.24 | 0.06 | M5 | 11.5 |
| Three-Phase400V Class | 4A0038F | 6.30 | 11.18 | 7.09 | 10.63 | 6.42 | 0.20 | 0.51 | 2.95 | 11.42 | 0.51 | 0.24 | 0.06 | M5 | 12.1 |
Explicit mounting callout — PDF page 33
| Source label/context | Source value |
|---|---|
| Mounting | 4-d; d=M5 in table |
Catalogue — V1000 3% and 5% reactors — page 35
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options V1000 Drive OPT
Reactor, 3% and 5% Impedance - may be used on either the input or output of a drive to reduce the effect of load or line side transients on the drive. The three-phase reactors are available loose in a separate NEMA 1 enclosure.
CA.VJ.01, 11/01/11 Data subject to change without notice Page 33 Yaskawa America, Inc. Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 35, printed page 33. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 3% and 5% reactors — PDF page 35
| Input voltage / phase | Model suffix | Rated output current (A) | Nominal HP | 3% reactor part suffix; prefix 05P00620- | 3% H(in) | 3% L(in) | 3% W(in) | 5% reactor part suffix; prefix 05P00620- | 5% H(in) | 5% L(in) | 5% W(in) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | 0020 | 8.0 | 8.0 | 6.0 | 0015 | 8.0 | 8.0 | 6.0 |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | 0020 | 8.0 | 8.0 | 6.0 | 0021 | 8.0 | 8.0 | 6.0 |
| 200-240V 1-Phase | BA0003__A | 3.3 | 1/2 & 3/4 | 0020 | 8.0 | 8.0 | 6.0 | 0021 | 8.0 | 8.0 | 6.0 |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | 0027 | 8.0 | 8.0 | 6.0 | 0028 | 8.0 | 8.0 | 6.0 |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | 0027 | 8.0 | 8.0 | 6.0 | 0028 | 8.0 | 8.0 | 6.0 |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | 0032 | 8.0 | 8.0 | 6.0 | 0033 | 8.0 | 8.0 | 6.0 |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | 0036 | 8.0 | 8.0 | 6.0 | 0037 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | 0020 | 8.0 | 8.0 | 6.0 | 0015 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | 0020 | 8.0 | 8.0 | 6.0 | 0021 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | 0020 | 8.0 | 8.0 | 6.0 | 0021 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | 0027 | 8.0 | 8.0 | 6.0 | 0028 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | 0027 | 8.0 | 8.0 | 6.0 | 0028 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | 0032 | 8.0 | 8.0 | 6.0 | 0033 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | 0036 | 8.0 | 8.0 | 6.0 | 0037 | 8.0 | 8.0 | 6.0 |
| 200-240V 3-Phase | 2A0030__A | 30.0 | 7.5 & 10 | 0041 | 13.0 | 13.0 | 13.0 | 0042 | 13.0 | 13.0 | 13.0 |
| 200-240V 3-Phase | 2A0040__A | 40.0 | 10 | 0046 | 13.0 | 13.0 | 13.0 | 0047 | 13.0 | 13.0 | 13.0 |
| 200-240V 3-Phase | 2A0056__A | 56.0 | 20 | 0054 | 13.0 | 13.0 | 13.0 | 0055 | 13.0 | 13.0 | 13.0 |
| 200-240V 3-Phase | 2A0069__A | 69.0 | 25 | 0058 | 13.0 | 13.0 | 13.0 | 0059 | 13.0 | 13.0 | 13.0 |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | 0015 | 8.0 | 8.0 | 6.0 | 0016 | 8.0 | 8.0 | 6.0 |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | 0015 | 8.0 | 8.0 | 6.0 | 0016 | 8.0 | 8.0 | 6.0 |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | 0021 | 8.0 | 8.0 | 6.0 | 0023 | 8.0 | 8.0 | 6.0 |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | 0028 | 8.0 | 8.0 | 6.0 | 0029 | 8.0 | 8.0 | 6.0 |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | 0033 | 8.0 | 8.0 | 6.0 | 0034 | 8.0 | 8.0 | 6.0 |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | 0037 | 8.0 | 8.0 | 6.0 | 0038 | 13.0 | 13.0 | 13.0 |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | 0042 | 13.0 | 13.0 | 13.0 | 0043 | 13.0 | 13.0 | 13.0 |
| 380-480V 3-Phase | 4A0018__A | 17.5 | 10 | 0042 | 13.0 | 13.0 | 13.0 | 0043 | 13.0 | 13.0 | 13.0 |
| 380-480V 3-Phase | 4A0023__A | 23.0 | 15 | 0047 | 13.0 | 13.0 | 13.0 | 0048 | 13.0 | 13.0 | 13.0 |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | 0047 | 13.0 | 13.0 | 13.0 | 0048 | 13.0 | 13.0 | 13.0 |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | 0051 | 13.0 | 13.0 | 13.0 | 0052 | 13.0 | 13.0 | 13.0 |
Catalogue — V1000 C1 filters — page 36
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options
OPT V1000 Drive
EMC C1 Filters - may be used on the input of the drive to attenuate possible drive-generated noise. Filters should always be mounted as close to the drive as possible; these are designed such that the drive can be mounted to it, pancake-style. The drive should be installed with the EMC filters listed below in order to comply with the EN 61800-3, category C1 requirements. These C1 filters meet the requirements for CE. Note: EMC filters for models CIMR-VU2A0030 through 0069 are in compliance with EN 61800-3, Category 2. All other models comply with Category 1.
CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 34 Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 36, printed page 34. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 C1 filters — PDF page 36
| Input voltage / phase | Model suffix | Rated output current (A) | Nominal HP | C1 filter part number | Filter rated current(A) | H(in) | W(in) | D(in) | Weight(lb) |
|---|---|---|---|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | FS23638-10-07 | 10 | 6.65 | 2.80 | 1.77 | 0.97 |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | FS23638-10-07 | 10 | 6.65 | 2.80 | 1.77 | 0.97 |
| 200-240V 1-Phase | BA0003__A | 3.3 | 1/2 & 3/4 | FS23638-10-07 | 10 | 6.65 | 2.80 | 1.77 | 0.97 |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | FS23638-20-07 | 20 | 6.65 | 4.37 | 1.97 | 1.76 |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | FS23638-20-07 | 20 | 6.65 | 4.37 | 1.97 | 1.76 |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | FS23638-30-07 | 30 | 6.85 | 5.67 | 1.97 | 2.64 |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | FS23638-40-07 | 40 | 6.85 | 6.85 | 1.97 | 3.52 |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | FS23637-8-07 | 8 | 6.65 | 2.80 | 1.57 | 0.88 |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | FS23637-8-07 | 8 | 6.65 | 2.80 | 1.57 | 0.88 |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | FS23637-8-07 | 8 | 6.65 | 2.80 | 1.57 | 0.88 |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | FS23637-8-07 | 8 | 6.65 | 2.80 | 1.57 | 0.88 |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | FS23637-14-07 | 14 | 6.65 | 4.37 | 1.77 | 1.28 |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | FS23637-14-07 | 14 | 6.65 | 4.37 | 1.77 | 1.28 |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | FS23637-24-07 | 24 | 6.85 | 5.67 | 1.97 | 1.98 |
| 200-240V 3-Phase | 2A0030__A | 30.0 | 7.5 & 10 | FS23637-52-07 | 52 | 11.97 | 5.39 | 2.20 | 4.41 |
| 200-240V 3-Phase | 2A0040__A | 40.0 | 10 | FS23637-52-07 | 52 | 11.97 | 5.39 | 2.20 | 4.41 |
| 200-240V 3-Phase | 2A0056__A | 56.0 | 20 | FS23637-68-07 | 68 | 13.39 | 6.89 | 2.56 | 5.73 |
| 200-240V 3-Phase | 2A0069__A | 69.0 | 25 | FS23637-80-07 | 80 | 15.47 | 8.35 | 2.56 | 6.83 |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | FS23639-5-07 | 5 | 6.65 | 4.37 | 1.77 | 1.10 |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | FS23639-5-07 | 5 | 6.65 | 4.37 | 1.77 | 1.10 |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | FS23639-5-07 | 5 | 6.65 | 4.37 | 1.77 | 1.10 |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | FS23639-10-07 | 10 | 6.65 | 4.37 | 1.77 | 1.54 |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | FS23639-10-07 | 10 | 6.65 | 4.37 | 1.77 | 1.54 |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | FS23639-10-07 | 10 | 6.65 | 4.37 | 1.77 | 1.54 |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | FS23639-15-07 | 15 | 6.85 | 5.67 | 1.97 | 1.98 |
| 380-480V 3-Phase | 4A0018__A | 17.5 | 10 | FS23639-30-07 | 30 | 11.97 | 5.39 | 2.20 | 3.97 |
| 380-480V 3-Phase | 4A0023__A | 23.0 | 15 | FS23639-30-07 | 30 | 11.97 | 5.39 | 2.20 | 3.97 |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | FS23639-50-07 | 50 | 13.39 | 6.89 | 2.56 | 5.95 |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | FS23639-50-07 | 50 | 13.39 | 6.89 | 2.56 | 5.95 |
Catalogue — V1000 C3 filters — page 37
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options V1000 Drive OPT
EMC C3 Filters (Conducted Interference Voltage Limits) - may be used on the input of a drive to attenuate possible drive- generated noise. An input filter with proper shielding, routing and grounding between itself and the drive is designed to reduce line-conducted noise levels within the limits of EN61800-3 Category C3, I ≤ 100A (second environment for industrial low- voltage supply network), when the drive’s output conductors are properly routed and shielded in grounded steel conduit all the way to the motor. The filters in combination with the drive meet UL and CE.
Note: Kit contains filter, cover, and mounting hardware.
CA.VJ.01, 11/01/11 Data subject to change without notice Page 35 Yaskawa America, Inc. Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 37, printed page 35. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 C3 filters — PDF page 37
| Input voltage / phase | Model suffix | Rated output current (A) | Nominal HP | C3 filter kit part number | Filter rated current(A) |
|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | FS22800-5-B | 5 |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | FS22800-5-B | 5 |
| 200-240V 1-Phase | BA0003__A | 3.3 | 1/2 & 3/4 | FS22800-9-B | 9 |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | FS22800-16-B | 16 |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | FS22800-26-B | 26 |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | FS22800-33-B | 33 |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0030__A | 30.0 | 7.5 & 10 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0040__A | 40.0 | 10 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0056__A | 56.0 | 20 | Consult Factory | Consult Factory |
| 200-240V 3-Phase | 2A0069__A | 69.0 | 25 | Consult Factory | Consult Factory |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | FS22801-3-B | 3 |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | FS22801-3-B | 3 |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | FS22801-6-B | 6 |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | FS22801-12-B | 12 |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | FS22801-12-B | 12 |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | FS22801-12-B | 12 |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | FS22801-16-B | 16 |
| 380-480V 3-Phase | 4A0018__A | 17.5 | 10 | FS22801-24-B | 24 |
| 380-480V 3-Phase | 4A0023__A | 23.0 | 15 | FS22801-24-B | 24 |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | FS22801-44-B | 44 |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | FS22801-44-B | 44 |
Catalogue — V1000 3% duty braking resistors — page 38
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options
OPT V1000 Drive
Dynamic Braking Resistor, 3% Duty Cycle - are rated for 3% duty cycle over a 100-second interval. Approximate braking torque for each rating is listed. These resistors are designed for separate panel mounting.
CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 36 Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 38, printed page 36. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 3% duty braking resistors — PDF page 38
| Input voltage / phase | Model suffix | Normal duty current(A) | Normal duty HP | Heavy duty current(A) | Heavy duty HP | 3% resistor part number | Quantity required | Resistance each(ohms) | Power each(W) | Approximate braking torque(%) | H(in) | W(in) | D(in) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | R7507 | 1 | 400 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | 1.6 | 1/4 | R7507 | 1 | 400 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 200-240V 1-Phase | BA0003__A | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 | R7505 | 1 | 200 | 150 | 230 | 7.16 | 1.73 | 0.51 |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | 5.0 | 3/4 & 1 | R7505 | 1 | 200 | 150 | 230 | 7.16 | 1.73 | 0.51 |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | 8.0 | 2 | R7504 | 1 | 100 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | 11.0 | 3 | R7503 | 1 | 70 | 150 | 120 | 7.16 | 1.73 | 0.51 |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | 17.5 | 5 | R7510 | 1 | 62 | 150 | 100 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | R7507 | 1 | 400 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | 1.6 | 1/4 | R7507 | 1 | 400 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 | R7505 | 1 | 200 | 150 | 230 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | 5.0 | 3/4 & 1 | R7505 | 1 | 200 | 150 | 230 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | 8.0 | 2 | R7504 | 1 | 100 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | 11.0 | 3 | R7503 | 1 | 70 | 150 | 120 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | 17.5 | 5 | R7510 | 1 | 62 | 150 | 100 | 7.16 | 1.73 | 0.51 |
| 200-240V 3-Phase | 2A0030__A | 30 | 7.5 & 10 | 25.0 | 7.5 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 200-240V 3-Phase | 2A0040__A | 40 | 10 | 33.0 | 10 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 200-240V 3-Phase | 2A0056__A | 56 | 20 | 47.0 | 15 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 200-240V 3-Phase | 2A0069__A | 69 | 25 | 60.0 | 20 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | 1.2 | 1/2 | R7508 | 1 | 750 | 150 | 230 | 7.16 | 1.73 | 0.51 |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | 1.8 | 3/4 | R7508 | 1 | 750 | 150 | 230 | 7.16 | 1.73 | 0.51 |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | 3.4 | 1 & 2 | R7508 | 1 | 750 | 150 | 130 | 7.16 | 1.73 | 0.51 |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | 4.8 | 3 | R7507 | 1 | 400 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | 5.5 | 3 | R7507 | 2 | 400 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | 7.2 | 4 | R7507 | 2 | 400 | 150 | 125 | 7.16 | 1.73 | 0.51 |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | 9.2 | 5 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 380-480V 3-Phase | 4A0018__A | 17.5 | 10 | 14.8 | 7.5 & 10 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 380-480V 3-Phase | 4A0023__A | 23.0 | 15 | 18.0 | 10 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | 24.0 | 15 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | 31.0 | 20 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
Catalogue — V1000 10% duty braking resistors — page 39
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options V1000 Drive OPT
Dynamic Braking Resistor, 10% Duty Cycle - are rated for 10% duty cycle over a 100-second interval. Approximate braking torque for each rating is listed. These resistors are designed in vented NEMA 1 enclosures for separate panel mounting. The built-in braking module supports the 3% and 10% duty cycle resistors listed here and on the previous page. Resistors for applications requiring 50% and 100% duty cycle can be supported; please consult Yaskawa for duty cycles above 10%.
CA.VJ.01, 11/01/11 Data subject to change without notice Page 37 Yaskawa America, Inc. Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 39, printed page 37. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 10% duty braking resistors — PDF page 39
| Input voltage / phase | Model suffix | Normal duty current(A) | Normal duty HP | Heavy duty current(A) | Heavy duty HP | 10% resistor part number | Quantity required | Resistance each(ohms) | Power each(W) | Approximate ND braking torque(%) | Approximate HD braking torque(%) | L(in) | W(in) | H(in) | Minimum resistance(ohms) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | USR000032 | 1 | 750 | 600 | 120 | 150 | 12 | 7 | 5 | 300 |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | 1.6 | 1/4 | USR000033 | 1 | 400 | 500 | 120 | 150 | 12 | 7 | 5 | 300 |
| 200-240V 1-Phase | BA0003__A | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 | USR000022 | 1 | 200 | 250 | 120 | 150 | 12 | 5 | 5 | 200 |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | 5.0 | 3/4 & 1 | USR000035 | 1 | 150 | 500 | 102 | 150 | 12 | 7 | 5 | 120 |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | 8.0 | 2 | USR000024 | 1 | 70 | 250 | 107 | 150 | 12 | 5 | 5 | 60 |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | 11.0 | 3 | USR000024 | 1 | 70 | 250 | 107 | 107 | 12 | 5 | 5 | 60 |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | 17.5 | 5 | USR000025 | 1 | 40 | 846 | 111 | 111 | 12 | 7 | 5 | 32 |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | USR000032 | 1 | 750 | 600 | 120 | 150 | 12 | 7 | 5 | 300 |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | 1.6 | 1/4 | USR000033 | 1 | 400 | 500 | 120 | 150 | 12 | 7 | 5 | 300 |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 | USR000022 | 1 | 200 | 250 | 120 | 150 | 12 | 5 | 5 | 200 |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | 5.0 | 3/4 & 1 | USR000035 | 1 | 150 | 500 | 102 | 150 | 12 | 7 | 5 | 120 |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | 8.0 | 2 | USR000024 | 1 | 70 | 250 | 107 | 150 | 12 | 5 | 5 | 60 |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | 11.0 | 3 | USR000024 | 1 | 70 | 250 | 107 | 107 | 12 | 5 | 5 | 60 |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | 17.5 | 5 | USR000025 | 1 | 40 | 846 | 111 | 111 | 12 | 7 | 5 | 32 |
| 200-240V 3-Phase | 2A0030__A | 30 | 7.5 & 10 | 25.0 | 7.5 | URS000148 | 1 | 18 | 1301 | 120 | 150 | 12 | 10 | 5 | 16 |
| 200-240V 3-Phase | 2A0040__A | 40 | 10 | 33.0 | 10 | URS000140 | 1 | 13.6 | 1646 | 120 | 150 | 12 | 13 | 5 | 9.6 |
| 200-240V 3-Phase | 2A0056__A | 56 | 20 | 47.0 | 15 | URS000136 | 1 | 10.5 | 3402 | 101 | 135 | 27 | 10 | 5 | 9.6 |
| 200-240V 3-Phase | 2A0069__A | 69 | 25 | 60.0 | 20 | URS000136 | 1 | 10.5 | 3402 | 80 | 101 | 27 | 10 | 5 | 9.6 |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | 1.2 | 1/2 | USR000032 | 1 | 750 | 600 | 120 | 150 | 12 | 7 | 5 | 750 |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | 1.8 | 3/4 | USR000032 | 1 | 750 | 600 | 120 | 150 | 12 | 7 | 5 | 750 |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | 3.4 | 1 & 2 | USR000032 | 1 | 750 | 600 | 61 | 61 | 12 | 7 | 5 | 510 |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | 4.8 | 3 | USR000034 | 1 | 250 | 500 | 119 | 119 | 12 | 7 | 5 | 240 |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | 5.5 | 3 | USR000034 | 1 | 250 | 500 | 119 | 119 | 12 | 7 | 5 | 200 |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | 7.2 | 4 | USR000035 | 1 | 150 | 500 | 118 | 150 | 12 | 7 | 5 | 100 |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | 9.2 | 5 | USR000036 | 1 | 100 | 975 | 117 | 150 | 12 | 10 | 5 | 100 |
| 380-480V 3-Phase | 4A0018__A | 17.5 | 10 | 14.8 | 7.5 & 10 | USR000038 | 1 | 50 | 1600 | 120 | 150 | 12 | 13 | 5 | 32 |
| 380-480V 3-Phase | 4A0023__A | 23.0 | 15 | 18.0 | 10 | USR000038 | 1 | 50 | 1600 | 113 | 150 | 12 | 13 | 5 | 32 |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | 24.0 | 15 | USR000039 | 1 | 40 | 2050 | 106 | 142 | 12 | 16 | 5 | 20 |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | 31.0 | 20 | URS000154 | 1 | 27.2 | 2720 | 120 | 150 | 19 | 13 | 5 | 20 |
Catalogue — V1000 DIN rail kits — page 40
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options
OPT V1000 Drive
DIN Rail Mounting Kits - The DIN rail attachment kit allows the drive to be mounted on a 35 mm DIN rail. The DIN rail itself is not included in the kit. Option kit for customer mounting.
CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 38 Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 40, printed page 38. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 DIN rail kits — PDF page 40
| Input voltage / phase | Model suffix | Rated output current (A) | Nominal HP | Kit suffix; prefix 72606-EZZ08122 |
|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | A |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | A |
| 200-240V 1-Phase | BA0003__A | 3.3 | 1/2 & 3/4 | A |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | B |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | B |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | C |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | D |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | A |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | A |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | A |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | A |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | B |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | B |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | C |
| 200-240V 3-Phase | 2A0030__A | 30.0 | 7.5 & 10 | Not Available |
| 200-240V 3-Phase | 2A0040__A | 40.0 | 10 | Not Available |
| 200-240V 3-Phase | 2A0056__A | 56.0 | 20 | Not Available |
| 200-240V 3-Phase | 2A0069__A | 69.0 | 25 | Not Available |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | B |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | B |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | B |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | B |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | B |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | B |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | C |
| 380-480V 3-Phase | 4A0018__A | 18.0 | 10 | Not Available |
| 380-480V 3-Phase | 4A0023__A | 23.0 | 15 | Not Available |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | Not Available |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | Not Available |
Catalogue — V1000 external heatsink and adapter kits — page 41
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options V1000 Drive OPT
Adapter Plate - Conversion kit used to mount a V1000 on the same footprint as a V7 drive. Not available for J1000 drives.
External Heatsink Kit - Allow for V1000 drives to be mounted with the drive’s heatsink external to the enclosure. Not available for J1000 drives. Option kit for customer mounting.
CA.VJ.01, 11/01/11 Data subject to change without notice Page 39 Yaskawa America, Inc. Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 41, printed page 39. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 external heatsink and adapter kits — PDF page 41
| Input voltage / phase | Model suffix | Rated output current (A) | Nominal HP | External heatsink suffix; prefix EZZ020568_ | Adapter suffix; prefix EZZ020572_ |
|---|---|---|---|---|---|
| 230V, 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | A | Not Required |
| 230V, 1-Phase | BA0002__A | 1.9 | 1/4 | A | Not Required |
| 230V, 1-Phase | BA0003__A | 3.3 | 1/2 & 3/4 | B | Not Required |
| 230V, 1-Phase | BA0006__A | 6.0 | 1 | C | Not Required |
| 230V, 1-Phase | BA0010__A | 9.6 | 2 & 3 | D | Not Required |
| 230V, 1-Phase | BA0012__A | 12.0 | 3 | E | Not Required |
| 230V, 1-Phase | BA0018__A | 17.5 | 5 | F | Not Required |
| 230V, 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | A | Not Required |
| 230V, 3-Phase | 2A0002__A | 1.9 | 1/4 | A | Not Required |
| 230V, 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | B | Not Required |
| 230V, 3-Phase | 2A0006__A | 6.0 | 1 | G | Not Required |
| 230V, 3-Phase | 2A0010__A | 9.6 | 2 & 3 | D | Not Required |
| 230V, 3-Phase | 2A0012__A | 12.0 | 3 | D | Not Required |
| 230V, 3-Phase | 2A0020__A | 19.6 | 5 | E | Not Required |
| 230V, 3-Phase | 2A0030__A | 30.0 | 7.5 & 10 | H | B |
| 230V, 3-Phase | 2A0040__A | 40.0 | 10 | H | B |
| 230V, 3-Phase | 2A0056__A | 56.0 | 20 | J | Not Required |
| 230V, 3-Phase | 2A0069__A | 69.0 | 25 | K | Not Required |
| 460V | 4A0001__A | 1.2 | 1/2 | L | Not Required |
| 460V | 4A0002__A | 2.1 | 3/4 & 1 | C | Not Required |
| 460V | 4A0004__A | 4.1 | 2 | C | Not Required |
| 460V | 4A0005__A | 5.4 | 3 | D | Not Required |
| 460V | 4A0007__A | 6.9 | 4 | D | Not Required |
| 460V | 4A0009__A | 8.8 | 5 | D | A |
| 460V | 4A0011__A | 11.1 | 7.5 | E | Not Required |
| 460V | 4A0018__A | 18.0 | 10 | H | B |
| 460V | 4A0023__A | 23.0 | 15 | H | B |
| 460V | 4A0031__A | 31.0 | 20 | J | Not Required |
| 460V | 4A0038__A | 38.0 | 25 | J | Not Required |
Catalogue — V1000 24VDC power and bracket kits — page 42
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options
OPT V1000 Drive
24VDC Control Power Unit - This option provides board-level component voltages for the V1000 drive when provided with 24VDC from an external, customer-supplied source. It is used to maintain both drive control power and network communications (when utilized). Both a Control Power Unit and a Bracket Kit are required for proper operation and certification. Option kit for customer mounting.
CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page 40 Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Table conditions: V1000; all models retain printed suffixes. Prefix CIMR-JU for J1000 schedules (except dimension drawing prefix CIMR-J□); CIMR-VU for V1000 schedules. Source page 42, printed page 40. Units/normal-heavy duty/braking-duty conditions remain as printed. Header units flattened only; no engineering inference.
V1000 24VDC power and bracket kits — PDF page 42
| Input voltage / phase | Model suffix | Rated output current (A) | Nominal HP | Control power unit part number | Bracket suffix; prefix EZZ020639_ |
|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001__A | 1.2 | 1/8 & 1/4 | PS-V10S | A |
| 200-240V 1-Phase | BA0002__A | 1.9 | 1/4 | PS-V10S | A |
| 200-240V 1-Phase | BA0003__A | 3.3 | 1/2 & 3/4 | PS-V10S | A |
| 200-240V 1-Phase | BA0006__A | 6.0 | 1 | PS-V10S | B |
| 200-240V 1-Phase | BA0010__A | 9.6 | 2 & 3 | PS-V10S | B |
| 200-240V 1-Phase | BA0012__A | 12.0 | 3 | PS-V10S | B |
| 200-240V 1-Phase | BA0018__A | 17.5 | 5 | PS-V10S | B |
| 200-240V 3-Phase | 2A0001__A | 1.2 | 1/8 & 1/4 | PS-V10S | A |
| 200-240V 3-Phase | 2A0002__A | 1.9 | 1/4 | PS-V10S | A |
| 200-240V 3-Phase | 2A0004__A | 3.5 | 1/2 & 3/4 | PS-V10S | A |
| 200-240V 3-Phase | 2A0006__A | 6.0 | 1 | PS-V10S | A |
| 200-240V 3-Phase | 2A0010__A | 9.6 | 2 & 3 | PS-V10S | B |
| 200-240V 3-Phase | 2A0012__A | 12.0 | 3 | PS-V10S | B |
| 200-240V 3-Phase | 2A0020__A | 19.6 | 5 | PS-V10S | B |
| 200-240V 3-Phase | 2A0030__A | 30.0 | 7.5 & 10 | PV-V10M | B |
| 200-240V 3-Phase | 2A0040__A | 40.0 | 10 | PV-V10M | B |
| 200-240V 3-Phase | 2A0056__A | 56.0 | 20 | PS-V10M | C |
| 200-240V 3-Phase | 2A0069__A | 69.0 | 25 | PS-V10M | C |
| 380-480V 3-Phase | 4A0001__A | 1.2 | 1/2 | PS-V10S | A |
| 380-480V 3-Phase | 4A0002__A | 2.1 | 3/4 & 1 | PS-V10S | A |
| 380-480V 3-Phase | 4A0004__A | 4.1 | 2 | PS-V10S | B |
| 380-480V 3-Phase | 4A0005__A | 5.4 | 3 | PS-V10S | B |
| 380-480V 3-Phase | 4A0007__A | 6.9 | 4 | PS-V10S | B |
| 380-480V 3-Phase | 4A0009__A | 8.8 | 5 | PS-V10S | B |
| 380-480V 3-Phase | 4A0011__A | 11.1 | 7.5 | PS-V10S | B |
| 380-480V 3-Phase | 4A0018__A | 18.0 | 10 | PS-V10M | B |
| 380-480V 3-Phase | 4A0023__A | 23.0 | 15 | PS-V10M | B |
| 380-480V 3-Phase | 4A0031__A | 31.0 | 20 | PS-V10M | B |
| 380-480V 3-Phase | 4A0038__A | 38.0 | 25 | PS-V10M | C |
Catalogue — V1000: source text and annotations — page 43
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options V1000 Drive OPT
Operator, LCD Digital Remote, NEMA Type 1. This option allows the drive to be operated from a remote location, and provides a 16-character, 5-line alpha-numeric LCD. This option requires Installation Set A (EZZ020642A) for panel or door mounting and Remote Operator Cable (UWR0051 or UWR0052), each sold separately. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. JVOP-180
Operator, LED Digital Remote, NEMA Type 1. This option allows the drive to be operated from a remote location. This option requires Installation Set A (EZZ020642A) for panel or door mounting and Remote Operator Cable (UWR0051 or UWR0052), each sold separately. Note: This option requires the V1000 drive to contain 1016 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. JVOP-182
LCD/LED Keypad Installation Set A (Remote Operator Mounting Bracket Kit). This is a bracket to which the LCD Digital Remote Operator (JVOP-180) attaches, and has (4) threaded holes and screws to attach to the cover of an enclosure. The kit contains (2) screws to mount the Operator to the bracket and (4) screws to attach the bracket to the enclosure. Model No. EZZ020642A
LCD/LED Keypad Installation Set B (Remote Operator Mounting Bracket Kit). Contains a similar bracket that the keypad attaches to and has non-threaded holes for mounting to an enclosure that has the screws attached to the enclosure already. The kit contains (2) screws to mount the keypad to the bracket and (4) nuts to attach the bracket to the customer supplied screws attached to the enclosure. Model No. EZZ020642B
Operator Cable, Remote. These cables are used to connect the Remote LCD Digital Operator (JVOP-180) or Remote LED Operator (JVOP-182). They are available in one (1) or three (3) meter lengths. Model No. UWR0051 (1 meter) Model No. UWR0052 (3 meter)
Operator Kits, NEMA Type 3R/4X. This option is used to extend an LCD or LED Digital Remote Operator to the wall of a separately priced, oversized UL Type 3R, 4, 4X, or 12 enclosure (IPX6 environment). Price includes a faceplate bezel with digital operator brackets and membrane to cover the operator cutout in the enclosure door, a 3-foot cable, a 10-foot cable, and a 1:1 template for cutting the necessary cutouts in the enclosure. Keypad can be removed after kit installation. Designed for use with the LCD Operator JVOP-180 or the LED Operator JVOP-182 sold separately. Connects to RJ45 port and mounts to enclosure wall. Model No. UUX000526 (Blank Membrane) Model No. UUX000527 (Yaskawa Logo Membrane)
DriveWizard Plus Software. This optional software package allows upload and download of parameters via PC for data storage and for programming multiple drives. The software also includes graphing and monitoring tools. It is a Windows-based program designed to make startup, commissioning, and troubleshooting of the J1000 as simple as possible. Refer to our website at www.yaskawa.com to download the software, and for more information, including minimum system requirements and cable information to interface a PC to V1000 or J1000 drives. No Model No.
PC Interface Cable. This 6-foot cable interconnects the drive keypad port to the 9-pin communication port on a PC. This cable is used in conjunction with DriveWizard Plus software. Model No. UWR00468-2
USB Copy Unit (Y-Stick). This option allows the drive to connect to the USB port on a PC. It can read, copy and verify drive parameter settings from one drive to another like drive. The unit plugs into the RJ-45 port on the front of the digital operator. Refer to our website at www.yaskawa.com to download the software. Model No. JVOP-181
CopyUnitManager Software for USB Copy Unit (Y-Stick). This option allows the user to transfer and save parameter files from the Copy Unit (JVOP-181), sold separately, to a PC and vice versa. Refer to our website at www.yaskawa.com to download the software. No Model No.
120 VAC Interface. This option mounts directly to the control terminal block on the drive and allows the use of 120 VAC control logic circuits to produce multi-function control input signals for the drive. Model No. DI-100
DriveWorksEZ (DWEZ) Standard and Pro. A software system that provides the means to create custom drive functionality in the V1000 using function block programming to distribute control away from a PLC.
DWEZ Standard can be downloaded from www.yaskawa.com with a valid partner login. DWEZ Pro requires attending a factory training class - see below for details.
DriveWorksEZ (DWEZ) Standard. The V1000 provides for 118 basic function blocks and up to 20 block connections. Available via web download only. Valid www.yaskawa.com Partner Login required
DriveWorksEZ (DWEZ) Pro Certification. A two-day DWEZ- specific training class (TRM020-DriveWorksEZ) must be attended to become certified. This class is intended for those well-versed in V1000 programming. DWEZ Pro provides increased functionality, with 50 connections and 225 function blocks compared to the Standard version. Model No. CD.DWEZ.03
To enroll in class, call Technical Training Services at 847-887-7228.
Page
CA.VJ.01, 11/01/11 Data subject to change without notice 41 Yaskawa America, Inc. Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Catalogue — V1000: source text and annotations — page 44
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options
OPT V1000 Drive
DeviceNet™ With ADR. This option complies with all pertinent aspects of the ODVA (Open DeviceNet Vendor Association) specification and AC drive profile. All parameters, diagnostics and operational commands are accessible via DeviceNet. Automatic Device Replacement (ADR) is supported in this DeviceNet option, including the functions of Auto Baud Rate sensing and Faulted Node Recovery (using Group 4 messaging). Each DeviceNet network supports up to 63 drives. Controllers are available from many PLC and/or PC suppliers. The board mounts integrally in the drive and provides a DeviceNet standard open tap connector. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover and a monitor has been added to allow for improved diagnostics. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-N3/V
EtherNet/IP. This option complies with the EtherNet/IP protocol specification, and allows for communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user specified IP address, from a DHCP host, or from a BootP host. The IP address can be set from the drive keypad or from the network. All parameters, diagnostics and operational commands are accessible via EtherNet/IP. The web interface allows management of diagnostic information through a standard web browser. The embedded web pages include the main page, drive status page, network monitor page, and documentation page. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EN3/V
PROFINET. This option complies to PROFINET I/O device and PROFIDrive profile specifications. It allows connection of a PROFINET network and facilitates the exchange of data via a simple, networking solution that reduces the cost and time to wire and install factory automation devices, while providing interchangeability of like components from multiple vendors. This is a PROFINET Conformance Class A certified interface.
This interface makes it possible to perform the following from a PROFINET master device: • Operate the drive • Monitor the operation status of the drive • Change parameter settings Note: This option requires the V1000 to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EP3/V
Profibus DP. This option complies with the Profibus DP protocol specification. All parameters, diagnostics and operational commands are accessible via Profibus. The option board provides a 9-pin (F) type D-Sub connector for easily connecting to a standard Profibus style, shielded twisted-pair cable. Each Profibus network supports up to 99 drives. This option supports all of the Profibus data rates from 9.6 Kbps to 12 Mbps. Up to 32 bytes of input data and 32 bytes of output data are provided per message transaction. Sync and Freeze modes are supported for groups. Profibus DP-V1 support (cyclic and acyclic data exchange). Configurable PPO read and write parameters. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover, and a monitor has been added to allow for improved diagnostics. Option is backwards compatible with the previous generation option cards. Note: This option requires the V1000 drive to contain 1010 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-P3/V
Modbus TCP/IP. This option complies with the Modbus TCP/IP protocol specification. This allows for Modbus communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user-specified IP address, from a DHCP host, or from a BootP host. All parameters, diagnostics and operational commands are accessible via Modbus TCP/IP. This option supports up to 10 simultaneous PLC/PC connections. Note: This option requires the V1000 drive to contain 1015 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EM3/V
MECHATROLINK-II. This option is designed for connecting a drive to a field network using the MECHATROLINK protocol. The MECHATROLINK-II option allows the user to operate the drive, monitor the status, and change parameters from a MECHATROLINK master device at a communication speed up to 10 Mbps. Note: This option requires the V1000 drive to contain 1016 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-T3/V
CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Catalogue — V1000-4X description and specifications — page 45
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Control:V/f,OpenLoopCurrentVector,PMOpenLoopCurrentVector andsimpleclosed-loopspeedcontrol. DCinjectionbraking/rampstop;electronicreversing;infinitelyadjustableV/Hzpattern;adjustablebrakingamplitude/duration/currentlimit;full-rangeautotorqueboost;speedsearch;autorestart;slipcompensation;energy-savingfunction;enhancedPIDwithfeedbackloss.
LEDstatusdisplay,remotemountkeypad,RJ-45styledigitaloperatorconnector;signal-followerbias/gain;coolingfancontrolledbyrun/stop;UL-recognizedelectronicoverload;built-indynamicbrakingtransistor;applicationpresets;maintenancemonitors.
Protection:currentlimit/stallpreventionduringaccel/decel/run;motoranddriveoverload;overvoltageprevention;instantaneousovercurrent;shortcircuit;undervoltage;heatsinkoverheat;groundfault;over/undertorque.
Integral enclosure forNEMAtype4X/12 indooruse,ULtype4X/12,IP66ofIEC529. Coated againstsanitizingchemicaleffects in foodindustries; sourceapplications food/beverage,packaging,metalmachining,woodworking,pumping,refrigeration,printing.
LEDstatusdisplay isdoor-mounted. Printed short-circuitwithstandrating30K RMS; unit notexpandedbeyondsource.
Context: Standards,MTBF,safety/category andlisting statements are historical supplierclaims, not independent compliance/certificatevalidation.
Context: Serviceconditions still headedNEMA1/OpenChassis on4Xpage; retain asprinted andflag applicability ratherthan asserting4Xambientlimits.
Table conditions: Sourcepage family-specific. Footnote1=V/fmode,2=OpenLoopCurrentVectorMode; preserve rating/duty distinctions. Analogresolution0.06/60Hz retained literally.
Table conditions: Printeddesignfeatures; do not infer availability from historicalcatalogue.
Table conditions: Exactprinted enclosure labels retained;4Xpage ambiguity flagged. No expanded environmentalrating inferred.
Table conditions: Historical source claims only; no current regulatoryapproval orcertificatevalidity assertion.
Table conditions: Option listing; compatibility requires source/factory confirmation. Detailed option tables are retained in their relevant sections.
Performance specifications — PDF page 45
| Source label/context | Source value |
|---|---|
| Ratings /200–240VAC1phase | 1/8 to3HP |
| Ratings /200–240VAC3phase | 1/8 to25HP(ND) |
| Ratings /380–480VAC3phase | 1/2 to25HP(ND) |
| Heavy Duty overload | 150% for60sec |
| Normal Duty overload | 120% for60sec |
| Acceleration/deceleration | 0.01 to6000seconds |
| Controlled speed range /V/fMode | 40:1 |
| Controlled speed range /OpenLoopCurrentVectorMode | 100:1 |
| Speed regulation /V/fMode withslipcompensation | ±0.5 to1% |
| Speed regulation /OpenLoopCurrentVectorMode | ±0.2% |
| Displacement power factor | 0.98 |
| Output frequency | 0 to400Hz |
| Frequency resolution /digitalreference | 0.01Hz |
| Frequency resolution /analogreference | 0.06 /60Hz |
| Frequency accuracy /digitalcommand | 0.01% |
| Frequency accuracy /analogcommand | 0.5% |
| Power loss ride-through | 0.5sec |
| Critical frequency rejection settings | 3 |
Design specifications — PDF page 45
| Source label/context | Source value |
|---|---|
| Processors | Dualmicroprocessorlogic |
| Keypad | Digitaloperator,5digits |
| Digital inputs | 7multifunction |
| Digital outputs | 3multifunction |
| Hardwire baseblock | EN954-1Cat.3 |
| Programmable FormCcontact | 1A at250VAC or30VDC |
| Control logic | 24VDC;PNPorNPN sourcing/sinking compatible |
| Carrier frequency | 15kHzmaximum;swingPWM |
| Speed settings | 16multi-speed plusjog |
| Remote speed references | 2;0–10VDC(20kohms) orisolated4–20mA(250ohms) |
| Open collector outputs | 2programmable |
| Analog monitor | 0–10VDC proportional tooutputfrequency oroutputcurrent |
| Parameters andmonitors | Approximately400parameters |
| Pulse traininput | 33kHzmaximum |
| Communication | RS-422/485Modbus115kbps |
| MTBF | 28years |
| Enclosure | NEMA4X/IP66 |
Service conditions — PDF page 45
| Source label/context | Source value |
|---|---|
| Ambient service /NEMA1 | −10 to40°C(+14 to104°F) |
| Ambient service /OpenChassis | −10 to50°C(+14 to122°F) |
| Ambient storage | −20 to60°C(−4 to140°F) |
| Humidity | to95%,non-condensing |
| Altitude | to3300ft;higherbyderating |
| Service factor | 1.0 |
| Inputvoltage tolerance | −15% to+10%;200–240VAC,380–480VAC |
| Inputfrequency | ±5%;50/60Hz |
| Inputphase sequence | Insensitive |
Printed standards and claims — PDF page 45
| Source label/context | Source value |
|---|---|
| UL | 508C(PowerConversion) |
| CSA | 22.2No.14-95(IndustrialControlEquipment) |
| Listings/marking | UL,cULlisted;CEmarked |
| RoHS | Compliant |
| LVD | EN50178 |
| EMC | EN50081-2,EN50082-2 |
| Safety | EN954-1,Category3 |
| OtherEN | EN61800-3 |
| IEC | 529,146 |
| FCC | CFR47Part15SubpartB;withExternalFilter |
| TUV | Printed claim |
| NEMA | type4X/12 |
| Ingress | IP66 ofIEC60529 |
Listed options — PDF page 45
| Source label/context | Source value |
|---|---|
| 1 | 120VACinterface |
| 2 | Profibus-DP |
| 3 | DeviceNet |
| 4 | ModbusTCP/IP |
| 5 | EtherNet/IP |
| 6 | DriveWizardPlus |
| 7 | Y-StickCopyUnit |
| 8 | Reactors3%and5% |
| 9 | Externaldynamicbrakingresistor |
| 10 | MultilingualfulltextremoteLCDwithcopy |
| 11 | EMCfilterTypeC1 |
Catalogue — V1000-4X standard drive ratings — page 47
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: Sourcepage ratings kept separate fromdimensionandvariantpages; discrepancies retained.
Table conditions: NormalDuty120%ratedoutputcurrent60seconds;HeavyDuty150%60seconds. Model prefix CIMR-VU unless explicitlydifferent. Historicalsourceavailability not currentstock. HPbasedonNEMAB4polemotorandNECtable430.150.
Standard drives — PDF page 47
| Rated input voltage/phase | Model suffix (CIMR-VU) | ND output A | ND nominal HP | HD output A | HD nominal HP |
|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001GAA | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 |
| 200-240V 1-Phase | BA0002GAA | 1.9 | 1/4 | 1.6 | 1/4 |
| 200-240V 1-Phase | BA0003GAA | 3.3 | 1/2 & 3/4 | 3.0 | 1/2 |
| 200-240V 1-Phase | BA0006GAA | 6.0 | 1 | 5.0 | 3/4 & 1 |
| 200-240V 1-Phase | BA0010GAA | 9.6 | 2 & 3 | 8.0 | 2 |
| 200-240V 1-Phase | BA0012GAA | 12.0 | 3 | 11.0 | 3 |
| 200-240V 3-Phase | 2A0001GAA | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 |
| 200-240V 3-Phase | 2A0002GAA | 1.9 | 1/4 | 1.6 | 1/4 |
| 200-240V 3-Phase | 2A0004GAA | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 |
| 200-240V 3-Phase | 2A0006GAA | 6.0 | 1 | 5.0 | 3/4 & 1 |
| 200-240V 3-Phase | 2A0010GAA | 9.6 | 2 & 3 | 8.0 | 2 |
| 200-240V 3-Phase | 2A0012GAA | 12.0 | 3 | 11.0 | 3 |
| 200-240V 3-Phase | 2A0020GAA | 19.6 | 5 | 17.5 | 5 |
| 200-240V 3-Phase | 2A0030GAA | 30.0 | 7.5 & 10 | 25.0 | 7.5 |
| 200-240V 3-Phase | 2A0040GAA | 40.0 | 10 | 33.0 | 10 |
| 200-240V 3-Phase | 2A0056GAA | 56.0 | 20 | 47.0 | 15 |
| 200-240V 3-Phase | 2A0069GAA | 69.0 | 25 | 60.0 | 20 |
| 380-480V 3-Phase | 4A0001GAA | 1.2 | 1/2 | 1.2 | 1/2 |
| 380-480V 3-Phase | 4A0002GAA | 2.1 | 3/4 & 1 | 1.8 | 3/4 |
| 380-480V 3-Phase | 4A0004GAA | 4.1 | 2 | 3.4 | 1 & 2 |
| 380-480V 3-Phase | 4A0005GAA | 5.4 | 3 | 4.8 | 3 |
| 380-480V 3-Phase | 4A0007GAA | 6.9 | 4 | 5.5 | 3 |
| 380-480V 3-Phase | 4A0009GAA | 8.8 | 5 | 7.2 | 4 |
| 380-480V 3-Phase | 4A0011GAA | 11.1 | 7.5 | 9.2 | 5 |
| 380-480V 3-Phase | 4A0018GAA | 17.5 | 10 | 14.8 | 7.5 & 10 |
| 380-480V 3-Phase | 4A0023GAA | 24.0 | 15 | 18.0 | 10 |
| 380-480V 3-Phase | 4A0031GAA | 31.0 | 20 | 24.0 | 15 |
| 380-480V 3-Phase | 4A0038GAA | 38.0 | 25 | 31.0 | 20 |
Catalogue — V1000-4X summary dimensions and data — page 48
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: EachprintedGAAmodel retained. Ratings and roundedweights maydiffer fromstandard/drawingpages; preserveeachoccurrence.
Table conditions: Physicalandmountingdimensions expresslyinches. Weightisdriveweight,notshipping. Noordercodeorengineeringcorrection.
4X summary dimensions and data — PDF page 48
| Ratedinputvoltage/phase | Model(CIMR-VU) | NDoutputA | NDnominalHP | HDoutputA | HDnominalHP | H in | W in | D in | H1 in | W1 in | Driveweight lb |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 200-240V 1-Phase | BA0001GAA | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 10.4 |
| 200-240V 1-Phase | BA0002GAA | 1.9 | 1/4 | 1.6 | 1/4 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 10.4 |
| 200-240V 1-Phase | BA0003GAA | 3.3 | 1/2 & 3/4 | 3.0 | 1/2 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 10.8 |
| 200-240V 1-Phase | BA0006GAA | 6.0 | 1 | 5.0 | 3/4 & 1 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.2 |
| 200-240V 1-Phase | BA0010GAA | 9.6 | 2 & 3 | 8.0 | 2 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.2 |
| 200-240V 1-Phase | BA0012GAA | 12.0 | 3 | 11.0 | 3 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 18.1 |
| 200-240V 3-Phase | 2A0001GAA | 1.2 | 1/8 & 1/4 | 0.8 | 1/8 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 10.4 |
| 200-240V 3-Phase | 2A0002GAA | 1.9 | 1/4 | 1.6 | 1/4 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 10.4 |
| 200-240V 3-Phase | 2A0004GAA | 3.5 | 1/2 & 3/4 | 3.0 | 1/2 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 10.6 |
| 200-240V 3-Phase | 2A0006GAA | 6.0 | 1 | 5.0 | 3/4 & 1 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 10.6 |
| 200-240V 3-Phase | 2A0010GAA | 9.6 | 2 & 3 | 8.0 | 2 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.0 |
| 200-240V 3-Phase | 2A0012GAA | 12.0 | 3 | 11.0 | 3 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.0 |
| 200-240V 3-Phase | 2A0020GAA | 19.6 | 5 | 17.5 | 5 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.9 |
| 200-240V 3-Phase | 2A0030GAA | 30.0 | 7.5 & 10 | 25.0 | 7.5 | 16.54 | 11.42 | 12.01 | 15.75 | 10.43 | 48.1 |
| 200-240V 3-Phase | 2A0040GAA | 40.0 | 10 | 33.0 | 10 | 16.54 | 11.42 | 12.01 | 15.75 | 10.43 | 48.1 |
| 200-240V 3-Phase | 2A0056GAA | 56.0 | 20 | 47.0 | 15 | 16.54 | 11.42 | 12.01 | 15.75 | 10.43 | 51.2 |
| 200-240V 3-Phase | 2A0069GAA | 69.0 | 25 | 60.0 | 20 | 18.31 | 11.42 | 12.01 | 17.52 | 10.43 | 61.1 |
| 380-480V 3-Phase | 4A0001GAA | 1.2 | 1/2 | 1.2 | 1/2 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 11.1 |
| 380-480V 3-Phase | 4A0002GAA | 2.1 | 3/4 & 1 | 1.8 | 3/4 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 11.1 |
| 380-480V 3-Phase | 4A0004GAA | 4.1 | 2 | 3.4 | 1 & 2 | 8.74 | 6.38 | 7.28 | 8.27 | 5.32 | 11.3 |
| 380-480V 3-Phase | 4A0005GAA | 5.4 | 3 | 4.8 | 3 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.0 |
| 380-480V 3-Phase | 4A0007GAA | 6.9 | 4 | 5.5 | 3 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.5 |
| 380-480V 3-Phase | 4A0009GAA | 8.8 | 5 | 7.2 | 4 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.5 |
| 380-480V 3-Phase | 4A0011GAA | 11.1 | 7.5 | 9.2 | 5 | 10.04 | 7.36 | 9.25 | 9.49 | 6.22 | 17.9 |
| 380-480V 3-Phase | 4A0018GAA | 17.5 | 10 | 14.8 | 7.5 & 10 | 16.54 | 11.42 | 12.01 | 15.75 | 10.43 | 47.9 |
| 380-480V 3-Phase | 4A0023GAA | 24.0 | 15 | 18.0 | 10 | 16.54 | 11.42 | 12.01 | 15.75 | 10.43 | 48.1 |
| 380-480V 3-Phase | 4A0031GAA | 31.0 | 20 | 24.0 | 15 | 16.54 | 11.42 | 12.01 | 15.75 | 10.43 | 50.5 |
| 380-480V 3-Phase | 4A0038GAA | 38.0 | 25 | 31.0 | 20 | 16.54 | 11.42 | 12.01 | 15.75 | 10.43 | 51.2 |
Catalogue — DD.V1000-4X.01 dimension drawing — page 49
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.
Table conditions: PrintedDD.V1000-4X.01. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan10models. Noauto-equivalence toGAAmodelsexceptsourcecontext.
Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.
4X drawing dimension table — PDF page 49
| Voltageclass | Model(CIMR-V□) | W mm(in) | H mm(in) | D mm(in) | W1 mm(in) | H1 mm(in) | H2 mm(in) | t1 mm(in) | A mm(in) | B mm(in) | E mm(in) | Weight kg(lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Single-Phase200VClass | BA0001G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 4.7 (10.36) |
| Single-Phase200VClass | BA0002G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 4.7 (10.36) |
| Single-Phase200VClass | BA0003G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 4.9 (10.80) |
| Three-Phase200VClass | 2A0001G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 4.7 (10.36) |
| Three-Phase200VClass | 2A0002G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 4.7 (10.36) |
| Three-Phase200VClass | 2A0004G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 4.8 (10.58) |
| Three-Phase200VClass | 2A0006G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 4.8 (10.58) |
| Three-Phase400VClass | 4A0001G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 5.0 (11.02) |
| Three-Phase400VClass | 4A0002G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 5.0 (11.02) |
| Three-Phase400VClass | 4A0004G | 162 (6.38) | 222 (8.74) | 185 (7.28) | 135 (5.32) | 210 (8.27) | 6 (0.24) | 2 (0.08) | 81 (3.19) | 126 (4.96) | 90 (3.54) | 5.1 (11.24) |
Explicit drawing callouts — PDF page 49
| Source label/context | Source value |
|---|---|
| Mounting | 4-M5 |
| Entrycallout1 | 6-Φ22 |
Catalogue — DD.V1000-4X.02 dimension drawing — page 50
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.
Table conditions: PrintedDD.V1000-4X.02. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan10models. Noauto-equivalence toGAAmodelsexceptsourcecontext.
Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.
4X drawing dimension table — PDF page 50
| Voltageclass | Model(CIMR-V□) | W mm(in) | H mm(in) | D mm(in) | W1 mm(in) | H1 mm(in) | H2 mm(in) | t1 mm(in) | A mm(in) | B mm(in) | E mm(in) | Weight kg(lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Single-Phase200VClass | BA0006G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 7.8 (17.2) |
| Single-Phase200VClass | BA0010G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 7.8 (17.2) |
| Single-Phase200VClass | BA0012G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 8.2 (18.08) |
| Three-Phase200VClass | 2A0010G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 7.7 (16.98) |
| Three-Phase200VClass | 2A0012G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 7.7 (16.98) |
| Three-Phase200VClass | 2A0020G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 8.1 (17.86) |
| Three-Phase400VClass | 4A0005G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 7.7 (16.98) |
| Three-Phase400VClass | 4A0007G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 7.9 (17.42) |
| Three-Phase400VClass | 4A0009G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 7.9 (17.42) |
| Three-Phase400VClass | 4A0011G | 187 (7.36) | 255 (10.04) | 235 (9.25) | 158 (6.22) | 241 (9.49) | 7 (0.28) | 2.5 (0.10) | 140 (5.51) | 188 (7.40) | 100 (3.94) | 8.1 (17.86) |
Explicit drawing callouts — PDF page 50
| Source label/context | Source value |
|---|---|
| Mounting | 4-M6 |
| Entrycallout1 | 6-Φ28 |
Catalogue — DD.V1000-4X.03 dimension drawing — page 51
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.
Table conditions: PrintedDD.V1000-4X.03. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan7models. Noauto-equivalence toGAAmodelsexceptsourcecontext.
Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.
4X drawing dimension table — PDF page 51
| Voltageclass | Model(CIMR-V□) | W mm(in) | H mm(in) | D mm(in) | W1 mm(in) | H1 mm(in) | H2 mm(in) | t1 mm(in) | A mm(in) | B mm(in) | C mm(in) | E mm(in) | F mm(in) | Weight kg(lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Three-Phase200VClass | 2A0030G | 290 (11.42) | 420 (16.54) | 305 (12.01) | 265 (10.43) | 400 (15.75) | 8.5 (0.33) | 2.5 (0.10) | 158 (6.22) | 205.5 (8.09) | 258 (10.16) | 90 (3.54) | 95 (3.74) | 21.8 (48.06) |
| Three-Phase200VClass | 2A0040G | 290 (11.42) | 420 (16.54) | 305 (12.01) | 265 (10.43) | 400 (15.75) | 8.5 (0.33) | 2.5 (0.10) | 158 (6.22) | 205.5 (8.09) | 258 (10.16) | 90 (3.54) | 95 (3.74) | 21.8 (48.06) |
| Three-Phase200VClass | 2A0056G | 290 (11.42) | 420 (16.54) | 305 (12.01) | 265 (10.43) | 400 (15.75) | 8.5 (0.33) | 2.5 (0.10) | 158 (6.22) | 205.5 (8.09) | 258 (10.16) | 90 (3.54) | 95 (3.74) | 23.2 (51.15) |
| Three-Phase400VClass | 4A0018G | 290 (11.42) | 420 (16.54) | 305 (12.01) | 265 (10.43) | 400 (15.75) | 8.5 (0.33) | 2.5 (0.10) | 158 (6.22) | 205.5 (8.09) | 258 (10.16) | 90 (3.54) | 95 (3.74) | 21.7 (47.84) |
| Three-Phase400VClass | 4A0023G | 290 (11.42) | 420 (16.54) | 305 (12.01) | 265 (10.43) | 400 (15.75) | 8.5 (0.33) | 2.5 (0.10) | 158 (6.22) | 205.5 (8.09) | 258 (10.16) | 90 (3.54) | 95 (3.74) | 21.8 (48.06) |
| Three-Phase400VClass | 4A0031G | 290 (11.42) | 420 (16.54) | 305 (12.01) | 265 (10.43) | 400 (15.75) | 8.5 (0.33) | 2.5 (0.10) | 158 (6.22) | 205.5 (8.09) | 258 (10.16) | 90 (3.54) | 95 (3.74) | 22.9 (50.49) |
| Three-Phase400VClass | 4A0038G | 290 (11.42) | 420 (16.54) | 305 (12.01) | 265 (10.43) | 400 (15.75) | 8.5 (0.33) | 2.5 (0.10) | 158 (6.22) | 205.5 (8.09) | 258 (10.16) | 90 (3.54) | 95 (3.74) | 23.2 (51.15) |
Explicit drawing callouts — PDF page 51
| Source label/context | Source value |
|---|---|
| Mounting | 4-M6 |
| Entrycallout1 | 3-Φ22 |
| Entrycallout2 | 3-Φ44 |
Catalogue — DD.V1000-4X.04 dimension drawing — page 52
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Context: SourceprefixprintsCIMR-V followedbyboxglyph; retainedasCIMR-V□, not replacedwithCIMR-VU. Physicalmergeddimensions appliedonlyto namedrows onthispage. Geometryoriginal-only.
Table conditions: PrintedDD.V1000-4X.04. Unitsmm(in)andkg(lb)retained asprinted; no conversionorrounding. Sharedcells physicallyspan1models. Noauto-equivalence toGAAmodelsexceptsourcecontext.
Table conditions: Exactvisiblelabels; drawingdefinesgeometry andplacement. No wiringorholeinterpretationgenerated.
4X drawing dimension table — PDF page 52
| Voltageclass | Model(CIMR-V□) | W mm(in) | H mm(in) | D mm(in) | W1 mm(in) | H1 mm(in) | H2 mm(in) | t1 mm(in) | A mm(in) | B mm(in) | C mm(in) | E mm(in) | F mm(in) | Weight kg(lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Three-Phase200VClass | 2A0069G | 290 (11.42) | 465 (18.31) | 305 (12.01) | 265 (10.43) | 445 (17.52) | 8.5 (0.33) | 2.5 (0.10) | 173 (6.81) | 188 (7.40) | 248 (9.76) | 130 (5.12) | 160 (6.30) | 27.7 (61.07) |
Explicit drawing callouts — PDF page 52
| Source label/context | Source value |
|---|---|
| Mounting | 4-M6 |
| Entrycallout1 | 3-Φ22 |
| Entrycallout2 | 3-Φ50 |
Catalogue — V1000-4X: source text and annotations — page 53
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options
V1000-4X Drive OPT
Operator, LCD Digital Remote, NEMA Type 1. This option allows the drive to be programmed before installation from a remote location, and provides a 16-character, 5-line alpha-numeric LCD. This option requires Remote Operator Cable (UWR0051 or UWR0052), sold separately. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. JVOP-180
Operator Cable, Remote. These cables are used to connect the Remote LCD Digital Operator (JVOP-180). They are available in one (1) or three (3) meter lengths. Model No. UWR0051 (1 meter) Model No. UWR0052 (3 meter)
Operator Kits, NEMA Type 3R/4X. This option is used to extend an LCD Digital Remote Operator to the wall of a separately priced, oversized UL Type 3R, 4, 4X, or 12 enclosure (IPX6 environment). Price includes a faceplate bezel with digital operator brackets and membrane to cover the operator cutout in the enclosure door, a 3- foot cable, a 10-foot cable, and a 1:1 template for cutting the necessary cutouts in the enclosure. Keypad can be removed after kit installation. Designed for use with the LCD Operator JVOP-180 sold separately. Connects to RJ45 port and mounts to enclosure wall. Model No. UUX000526 (Blank Membrane) Model No. UUX000527 (Yaskawa Logo Membrane)
DriveWizard Plus Software. This optional software package allows upload and download of parameters via PC for data storage and for programming multiple drives. The software also includes graphing and monitoring tools. It is a Windows-based program designed to make startup, commissioning, and troubleshooting of the J1000 as simple as possible. Refer to our website at www.yaskawa.com to download the software, and for more information, including minimum system requirements and cable information to interface a PC to V1000 or J1000 drives. No Model No.
PC Interface Cable. This 6-foot cable interconnects the drive keypad port to the 9-pin communication port on a PC. This cable is used in conjunction with DriveWizard Plus software. Model No. UWR00468-2
USB Copy Unit (Y-Stick). This option allows the drive to connect to the USB port on a PC. It can read, copy and verify drive parameter settings from one drive to another like drive. The unit plugs into the RJ-45 port on the front of the digital operator. Refer to our website at www.yaskawa.com to download the software. Model No. JVOP-181
CopyUnitManager Software for USB Copy Unit (Y-Stick). This option allows the user to transfer and save parameter files from the Copy Unit (JVOP-181), sold separately, to a PC and vice versa. Refer to our website at www.yaskawa.com to download the software. No Model No.
120 VAC Interface. This option mounts directly to the control terminal block on the drive and allows the use of 120 VAC control logic circuits to produce multi-function control input signals for the drive. Model No. DI-100
DriveWorksEZ (DWEZ) Standard and Pro. A software system that provides the means to create custom drive functionality in the V1000 using function block programming to distribute control away from a PLC. Must attend one of the two classes below to obtain software CD.
DriveWorksEZ (DWEZ) Standard Certification. A 3-day V1000 Application Programming training class (TRM010-V1000) must be attended to become certified. Provides 20 connections and 119 basic functions. Model No. CD.DWEZ.02
DriveWorksEZ (DWEZ) Pro Certification. A 2-day DWEZ-specific training class (TRM020-DriveWorksEZ) must be attended to become certified. This class is intended for those well-versed in V1000 programming. DWEZ Pro provides increased functionality, with 50 connections and 225 function blocks compared to the Standard version. Model No. CD.DWEZ.03
To enroll in class, call Technical Training Services at 847-887-7228.
Page
CA.VJ.01, 11/01/11 Data subject to change without notice 51 Yaskawa America, Inc. Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000-4X. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Catalogue — V1000-4X: source text and annotations — page 54
Source reference: CA.VJ.01, November 2011. Historical US catalogue; family, model, duty, units and conditions apply.
Options
OPT V1000-4X Drive
DeviceNet™ With ADR. This option complies with all pertinent aspects of the ODVA (Open DeviceNet Vendor Association) specification and AC drive profile. All parameters, diagnostics and operational commands are accessible via DeviceNet. Automatic Device Replacement (ADR) is supported in this DeviceNet option, including the functions of Auto Baud Rate sensing and Faulted Node Recovery (using Group 4 messaging). Each DeviceNet network supports up to 63 drives. Controllers are available from many PLC and/or PC suppliers. The board mounts integrally in the drive and provides a DeviceNet standard open tap connector. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover and a monitor has been added to allow for improved diagnostics. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. SI-N3/V
EtherNet/IP. This option complies with the EtherNet/IP protocol specification, and allows for communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user specified IP address, from a DHCP host, or from a BootP host. The IP address can be set from the drive keypad or from the network. All parameters, diagnostics and operational commands are accessible via EtherNet/IP. The web interface allows management of diagnostic information through a standard web browser. The embedded web pages include the main page, drive status page, network monitor page, and documentation page. Note: This option requires the V1000 drive to contain 1012 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. SI-EN3/V
Profibus DP. This option complies with the Profibus DP protocol specification. All parameters, diagnostics and operational commands are accessible via Profibus. The option board provides a 9-pin (F) type D-Sub connector for easily connecting to a standard Profibus style, shielded twisted-pair cable. Each Profibus network supports up to 99 drives. This option supports all of the Profibus data rates from 9.6 Kbps to 12 Mbps. Up to 32 bytes of input data and 32 bytes of output data are provided per message transaction. Sync and Freeze modes are supported for groups. Profibus DP-V1 support (cyclic and acyclic data exchange). Configurable PPO read and write parameters. The option is configured using parameters within the drive, which allows for easy configuration eliminating the use of hardware switches. Status LEDs are viewable through the front cover, and a monitor has been added to allow for improved diagnostics. Option is backwards compatible with the previous generation option cards. Note: This option requires the V1000 drive to contain 1010 software or later; please consult your Yaskawa representative to ensure proper operation. Model No. SI-P3/V
Modbus TCP/IP. This option complies with the Modbus TCP/IP protocol specification. This allows for Modbus communication over 10/100 Mbps Ethernet networks. This option has the ability to configure the IP Address from a user-specified IP address, from a DHCP host, or from a BootP host. All parameters, diagnostics and operational commands are accessible via Modbus TCP/IP. This option supports up to 10 simultaneous PLC/PC connections. Note: This option requires the V1000 drive to contain 1015 software or later; please consult your Yaskawa representative to ensure proper operation. Mounts at option connector CN5. Model No. SI-EM3/V
CA.VJ.01, 11/01/11 Data subject to change without notice Yaskawa America, Inc. Page Drives & Motion Division
Context: Historical source CA.VJ.01, 11/01/11. Section applicability: V1000-4X. Source product association P059 does not make every family in this catalogue a V1000 specification. Supplier claims, options, commercial terms and contact information are edition-specific, not independently verified current.
Manual — Preface, documentation roles and terminology — page 12
Source reference: SIEP C71060618F, December 2016, physical PDF page 12. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.1 Preface i.1 Preface Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products. u Applicable Documentation The following manuals are available for V1000 series drives: u Symbols Note: [term-definition icon] Indicates a supplement or precaution that does not cause drive damage. Indicates a term or definition used in this manual. u Terms and Abbreviations [term-definition icon] • Drive: Yaskawa V1000 Series Drive • PM motor: Permanent Magnet Synchronous Motor (an abbreviation for IPM motor or SPM motor) • IPM motor: Interior Permanent Magnet Motor (e.g., Yaskawa SSR1 Series motor) • SPM motor: Surface Mounted Permanent Magnet Motor (e.g., Yaskawa SMRA Series SPM motor) • PG: Pulse Generator • r/min: Revolutions per Minute • V/f: V/f Control • OLV: Open Loop Vector Control • OLV/PM: Open Loop Vector Control for PM
Illustration of V1000 documentation/drive; no miniature display or pictogram values promoted as model specifications.
Source describes supplied Quick Start Guide and Technical Manual roles; does not prove a separate download is present.
Applicable documentation — PDF page 12
| Source row | Document | Source description |
|---|---|---|
| 1 | V1000 Series AC Drive Quick Start Guide | Read this manual first. This guide is packaged together with the product. It contains basic information required to install and wire the drive. This guide provides basic programming and simple setup and adjustment. |
| 2 | V1000 Series AC Drive Technical Manual | This manual describes installation, wiring, operation procedures, functions, troubleshooting, maintenance, and inspections to perform before operation. |
Manual — General precautions and hazard classification — page 13
Source reference: SIEP C71060618F, December 2016, physical PDF page 13. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.2 General Safety i.2 General Safety u Supplemental Safety Information General Precautions • The diagrams in this manual may be indicated without covers or safety shields to show details. Restore covers or shields before operating the drive and run the drive according to the instructions described in this manual. • Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable. • The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. • When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover. • If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office. WARNING Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according to this manual and local codes. The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or possibly even fatal injury or damage to the products or to related equipment and systems. DANGER Indicates a hazardous situation, which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation, which, if not avoided, could result in death or serious injury. WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety message. CAUTION Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury. CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety message. NOTICE Indicates a property damage message. NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety message. u Safety Messages DANGER Heed the safety messages in this manual. Failure to comply will result in death or serious injury. The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
Manual — Electrical shock, unexpected start, lifting and handling safety — page 14
Source reference: SIEP C71060618F, December 2016, physical PDF page 14. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.2 General Safety DANGER Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level. WARNING Sudden Movement Hazard System may start unexpectedly upon application of power, resulting in death or serious injury. Clear all personnel from the drive, motor and machine area before applying power. Secure covers, couplings, shaft keys and machine loads before applying power to the drive. When using DriveWorksEZ to create custom programming, the drive I/O terminal functions change from factory settings and the drive will not perform as outlined in this manual. Unpredictable equipment operation may result in death or serious injury. Take special note of custom I/O programming in the drive before attempting to operate equipment. Electrical Shock Hazard Do not attempt to modify or alter the drive in any way not explained in this manual. Failure to comply could result in death or serious injury. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Do not allow unqualified personnel to use equipment. Failure to comply could result in death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Crush Hazard Do not use this drive in lifting applications without installing external safety circuitry to prevent accidental dropping of the load. The drive does not possess built-in load drop protection for lifting applications. Failure to comply could result in death or serious injury from falling loads. Install electrical and/or mechanical safety circuit mechanisms independent of drive circuitry. CAUTION Crush Hazard Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling.
Manual — Equipment protection and warning labels — page 15
Source reference: SIEP C71060618F, December 2016, physical PDF page 15. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.2 General Safety NOTICE Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not perform a withstand voltage test on any part of the drive. Failure to comply could result in damage to the sensitive devices within the drive. Do not operate damaged equipment. Failure to comply could result in further damage to the equipment. Do not connect or operate any equipment with visible damage or missing parts. Install adequate branch circuit short circuit protection per applicable codes. Failure to comply could result in damage to the drive. The drive is suitable for circuits capable of delivering not more than 31,000 RMS symmetrical Amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400 V Class). Do not expose the drive to halogen group disinfectants. Failure to comply may cause damage to the electrical components in the drive. Do not pack the drive in wooden materials that have been fumigated or sterilized. Do not sterilize the entire package after the product is packed. u Drive Label Warnings Always heed the warning information listed in Figure i.1 in the position shown in Figure i.2 . Figure i.1 Warning Information Figure i.2 Warning Information Position
WARNING — Risk of electric shock. Read manual before installing. Wait 5 minutes for capacitor discharge after disconnecting power supply. To conform to CE requirements, make sure to ground the supply neutral for 400V class.
Warning Label — location illustration on drive. Illustration geometry and miniature product artwork remain in original; no model-specific rating inferred.
Manual — Warranty restrictions and quick reference — page 16
Source reference: SIEP C71060618F, December 2016, physical PDF page 16. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.2 General Safety u Warranty Information n Restrictions The drive was not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or health. Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa representatives or the nearest Yaskawa sales office. This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident. u Quick Reference Easily Set Application-Specific Parameters Preset parameter defaults are available for many applications. Refer to Application Selection on page 96. Run a Motor of One-Frame Larger Capacity When using this drive for variable torque loads such as fans and pumps, a motor one frame size larger can be used. Refer to C6-01: Drive Duty Selection on page 155 Know the Details of Safety Measures The functions listed below affect the safe operation of the drive. Ensure that the settings fit the application requirements prior to operation. Operation of digital outputs during Auto-tuning. Rotational Auto-tuning allows for normal digital output operation. Non-rotational Auto-tuning does not allow for normal digital output operation. Safe operations. Run by power on. Parameter setting b1-17. LOCAL/REMOTE key effective during stop in drive mode. Parameter o2-01. LED operator stop key priority selection. Parameter o2-02. Enter press required after changing the keypad frequency reference. Parameter o2-05. Operation interlock when program mode is selected. Parameter b1-08. Replace the Drive The removable terminal block with parameter backup function allows the transfer of parameter settings after drive replacement. Refer to Dismantling the Removable Terminal Block on page 319. Drive a Synchronous PM Motor The V1000 drive can operate synchronous PM motors. Refer to Subchart A3: Operation with Permanent Magnet Motors on page 94. Perform Auto-Tuning Automatic tuning sets motor parameters. Refer to Auto-Tuning on page 102. Check the Maintenance Period Using Drive Monitors The maintenance period of fans and capacitors can be checked with drive monitors. Refer to Performance Life Monitors on page 314
Manual — Quick reference and historical compliance logos — page 17
Source reference: SIEP C71060618F, December 2016, physical PDF page 17. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.2 General Safety Drive or Motor Faults are Displayed on a Digital Operator Refer to Fault Displays, Causes, and Possible Solutions on page 267 and Refer to Detailed Alarm Codes, Causes, and Possible Solutions on page 282. Standards Compliance Refer to European Standards on page 466 and Refer to UL and CSA Standards on page 474.
CE; cULus LISTED; CSA. Source symbols only; current certification validity and applicability not verified.
Manual — Reactor selection, drive capacity, stopping and repetitive duty — page 18
Source reference: SIEP C71060618F, December 2016, physical PDF page 18. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.3 Application Precautions i.3 Application Precautions u General Application Precautions n Selecting a Reactor An AC reactor or DC link choke can be used for the following: • to suppress harmonic current. • to smooth peak current that results from capacitor switching. • when the power supply is above 600 kVA. • when the drive is running from a power supply system with thyristor converters. Note: A DC link choke is built in to 200 V and 400 V class models with a capacity of 22 kW and higher (HD rating). Figure i.3 Installing a Reactor n Drive Capacity Make sure that the motor rated current is less than the rated nameplate output current of the drive. When running more than one motor in parallel from a single drive, the drive rated current should 1.1 times larger than the total motor rated current for all connected motors or nuisance drive faults may occur. n Starting Torque The overload rating of the drive determines the starting and accelerating characteristics of the motor. Expect lower running torque than when running the motor from line power. To get more starting torque, use a larger drive or increase both the motor and drive capacity. n Emergency/Fast Stop During a drive fault condition, a protective circuit is activated and drive output is shut off. The motor may coast to a stop or attempt to decelerate depending on parameter settings. If the emergency/fast stop cannot stop the load as fast as desired, a customer-supplied mechanical brake may be required. Test emergency stop circuitry before putting drive into operation. n Options The B1, B2, +1, +2, and +3 terminals are used to connect optional power devices. Connect only devices compatible with the drive. n Repetitive Starting/Stopping Applications with frequent starts and stops often exceed 150% of their rated current values. Heat stress generated from repetitive high current can shorten the life span of the IGBTs. The expected lifetime for the IGBTs is about 8 million start and stop cycles with a 4 kHz carrier frequency and a 150% peak current. Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. The user can also choose to reduce the load, increase the acceleration and deceleration times, or switch to a larger drive. This will help keep peak current levels under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during the initial test run, and make adjustments accordingly.
Power Supply Capacity (kVA): 0, 600, 4000. Drive Capacity (kVA): 60, 400. Regions: Power supply harmonics reactor required; Reactor unnecessary. Original plot boundaries retained; no interpolation inferred.
Manual — Installation, settings, wiring and input contactor conditions — page 19
Source reference: SIEP C71060618F, December 2016, physical PDF page 19. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.3 Application Precautions u Installation Environment n Enclosure Panels Keep the drive in a clean environment by either selecting an area free of airborne dust, lint, and oil mist, or install the drive in an enclosure panel. Be sure to leave the required space between drives to provide for cooling, and that proper measures are taken so that the ambient temperature remains within allowable limits. Keep flammable materials away from the drive. If the drive must be used in an area where it is subjected to oil mist and excessive vibration, protective designs are available. Contact Yaskawa or your Yaskawa agent for details. n Installation Direction The drive should be installed upright as specified in the manual. u Settings n Motor Code If using OLV/PM designed for permanent magnet motors (A1-02 = 5), make sure that the proper motor code is set in parameter E5-01 before performing a trial run. n Upper Limits The drive is capable of running the motor up to 400 Hz. Due to the danger of accidentally operating the motor at high speed, be sure to set the upper frequency limit. The default setting for the maximum output frequency is 60 Hz. n DC Injection Braking Motor overheat can result if there is too much current used during DC Injection Braking, or if the DC Injection Braking time is too long. n Acceleration/Deceleration Times Acceleration and deceleration times are affected by how much torque the motor generates, the load torque, and the inertia moment ((GD2)/4). Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as long as the Stall Prevention function is operating. For faster acceleration and deceleration, install a braking option or increase the capacity of the drive. u General Handling NOTICE: Wiring Check. Never connect the power supply lines to output terminals U/T1, V/T2, or W/T3. Doing so will destroy the drive. Be sure to perform a final check of all control wiring and other connections before applying line power. Make sure there are no short circuits on the control terminals (+V, AC, etc.), as this could damage the drive. n Selecting a Molded Case Circuit Breaker (MCCB) or Ground Fault Circuit Interrupter (GFCI) Yaskawa recommends installing a GFCI on the line power supply to protect drive wiring and prevent damage in the event of component failure. An MCCB may also be used if permitted by the power system. The GFCI should be designed for use with an AC drive (i.e., protected against harmonics) MCCB selection depends on the power factor for the drive, determined by the power supply voltage, output frequency, and load. Refer to Installing Peripheral Devices on page 330 for more information on breaker installation. Note that a larger capacity breaker is needed when using a fully electromagnetic MCCB, as operation characteristics vary with harmonic current. n Magnetic Contactor (MC) Installation Use an MC to ensure that line power to the drive can be completely shut off when necessary. The MC should be wired so that it opens when the drive fault output is triggered. Avoid switching the MC on the power supply side more frequently than once every 30 minutes. Frequent switching can cause damage to the drive.
Manual — Inspection, maintenance and motor operation — page 20
Source reference: SIEP C71060618F, December 2016, physical PDF page 20. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.3 Application Precautions n Inspection and Maintenance DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Disconnect all power to the drive, wait at least five minutes after all indicators are OFF, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing to prevent electrical shock. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and make sure the heatsink has cooled to a safe level. WARNING! Electrical Shock Hazard. Wait for at least the time specified on the drive warning label after opening the load switch on the output side before any inspection or maintenance of permanent magnet (PM) motors. Failure to comply could result in death or serious injury. WARNING! Sudden Movement Hazard. Install a switch disconnect between the motor and the drive in applications where the machine can still rotate even though the drive has fully stopped. Unpredictable equipment operation may result in death or serious injury. WARNING! Sudden Movement Hazard. Do not attempt to move a load that could potentially rotate the motor faster than the maximum allowable r/min when the drive has been shut off. Unpredictable equipment operation may result in death or serious injury. NOTICE: Do not open and close the motor disconnect switch while the motor is running, as this may damage the drive. NOTICE: If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped before closing the load switch. n Wiring All wire ends should use ring terminals for UL/cUL compliance. Use only the tools recommended by the terminal manufacturer for crimping. n Transporting the Drive NOTICE: Prevent the drive from contact with salts, fluorine, bromine, phthalate ester, and other such harmful chemicals. Never steam clean the drive. Failure to comply may cause damage to the drive components. u Notes on Motor Operation n Using a Standard Motor Low Speed Range The cooling fan of a standard motor is usually designed to sufficiently cool the motor at the rated speed. As the self-cooling capability of such a motor reduces with the speed, applying full torque at low speed will possibly damage the motor. To prevent motor damage from overheat, reduce the load torque as the motor slows. Figure i.4 shows the allowable load characteristics for a Yaskawa standard motor. A motor designed specifically for operation with a drive should be used when 100% continuous torque is needed at low speeds. Figure i.4 Allowable Load Characteristics for a Yaskawa Motor Insulation Tolerance Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly long wiring distances. Contact Yaskawa or your Yaskawa agent for consultation.
Torque (%): 50, 60, 70, 80, 90, 100. Frequency (Hz): 3, 6, 20, 60. Duty labels: 25% ED (or 15 min); 40% ED (or 20 min); 60% ED (or 40 min); Continuous operation. Original curves remain authoritative; no interpolated torque or geometry inferred.
Manual — Motor operation and synchronous motor restrictions — page 21
Source reference: SIEP C71060618F, December 2016, physical PDF page 21. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.3 Application Precautions High Speed Operation Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed. Contact the motor or machine manufacturer. Torque Characteristics Torque characteristics differ compared to operating the motor directly from line power. The user should have a full understanding of the load torque characteristics for the application. Vibration and Shock The drive settings allow the user to choose between high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce motor oscillation. Take particular caution when using a variable speed drive for an application that is conventionally run from line power at a constant speed. If mechanical resonance occurs, install shock-absorbing rubber around the base of the motor and enable the Jump frequency selection parameter to prevent continuous operation in the resonant frequency range. Audible Noise Noise created during run varies by the carrier frequency setting. When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running from line power. Operating above the rated r/min, however, can create unpleasant motor noise. n Using a Synchronous Motor • Synchronous motors cannot be started directly from line power. Applications requiring line power to start should use an induction motor with the drive. • A single drive is not capable of running multiple synchronous motors at the same time. Use a standard induction motor for such setups. • At start, a synchronous motor may rotate slightly in the opposite direction of the Run command depending on parameter settings and motor type. • The amount of starting torque that can be generated differs by each control mode and by the type of motor being used. Set up the motor with the drive after verifying the starting torque, allowable load characteristics, impact load tolerance, and speed control range. Contact Yaskawa or your Yaskawa agent if you plan to use a motor that does not fall within these specifications. • Braking Torque: In Open Loop Vector Control for PM motors, braking torque is less than 125% when running between 20% to 100% speed, even with a braking resistor. Braking torque drops to less than half when running at less than 20% speed. • Load Inertia: In Open Loop Vector Control for PM motors, the allowable load inertia moment is approximately 50 times higher than the motor inertia moment or less. Contact Yaskawa or your Yaskawa agent concerning applications with a larger inertia moment. • Holding Brake: When using a holding brake in Open Loop Vector Control for PM motors, release the brake prior to starting the motor. Failure to set the proper timing can result in speed loss. Not for use with conveyor, transport, or hoist type applications. • Restarting a Coasting Motor: To restart a coasting motor rotating at over 200 Hz while in the V/f control mode, use the Short Circuit Braking function to first bring the motor to a stop. Short Circuit Braking requires a special braking resistor. Contact Yaskawa or your Yaskawa agent for details. Speed Search can be used to restart a coasting motor rotating slower than 200 Hz. If the motor cable is relatively long, however, the motor should instead be stopped using Short Circuit Braking, which forces the motor to stop by creating a short-circuit in the motor windings. n Applications with Specialized Motors Multi-Pole Motor Because the rated current will differ from a standard motor, be sure to check the maximum current when selecting a drive. Always stop the motor before switching between the number of motor poles. If a regen overvoltage (oV) fault occurs or if overcurrent protection (oC) is triggered, the motor will coast to stop. Submersible Motor Because motor rated current is greater than a standard motor, select the drive capacity accordingly. Be sure to use a large enough gauge motor cable to avoid decreasing the maximum torque level on account of voltage drop caused by a long motor cable.
Manual — Special motor and power machinery limitations — page 22
Source reference: SIEP C71060618F, December 2016, physical PDF page 22. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
i.3 Application Precautions Explosion-Proof Motor Both the motor and drive need to be tested together to be certified as explosion-proof. The drive is not designed for explosion proof areas. Furthermore, if an encoder is attached to an explosion-proof motor make sure the encoder is also explosion-proof. Use an insulating signal converter for connecting the encoder signal lines to the drives speed feedback option card. Geared Motor To avoid gear damage when operating at low speeds or very high speeds, make sure that both the gear and lubricant are rated for the desired speed range. Consult with the manufacturer for applications that require operation outside the rated speed range of the motor or gear box. Single-Phase Motor Variable speed AC drives are not designed for operation with single phase motors. Using capacitors to start the motor causes excessive current to flow and can damage drive components. A split-phase start or a repulsion start can end up burning out the starter coils because the internal centrifugal switch is not activated. The drive is for use with 3-phase motors only. Motor with Brake Caution should be taken when using a drive to operate a motor with a built-in holding brake. If the brake is connected to the output side of the drive, it may not release at start due to low voltage levels. A separate power supply should be installed for the motor brake. Motors with a built-in brake tend to generate a fair amount of noise when running at low speeds. n Power Driven Machinery (decelerators, belts, chains, etc.) Continuous operation at low speeds wears on the lubricating material used in gear box type systems to accelerate and decelerate power driven machinery. Caution should also be taken when operating at speeds above the rated machine speed due to noise and shortened performance life.
Manual — Receiving safety, ESD and PWM motor heating — page 24
Source reference: SIEP C71060618F, December 2016, physical PDF page 24. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.1 Section Safety 1.1 Section Safety CAUTION Do not carry the drive by the front cover. Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury. NOTICE Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. A motor connected to a PWM drive may operate at a higher temperature than a utility-fed motor and the operating speed range may reduce motor cooling capacity. Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the additional heating with the intended operating conditions.
Manual — Receiving checks, example nameplate and model-code ratings — page 25
Source reference: SIEP C71060618F, December 2016, physical PDF page 25. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.2 Model Number and Nameplate Check. Please perform the following tasks after receiving the drive: Inspect the drive for damage. If the drive appears damaged upon receipt, contact the shipper immediately. Verify receipt of the correct model by checking the information on the nameplate. If you have received the wrong model or the drive does not function properly, contact your supplier. Nameplate. Figure 1.1 Nameplate Information Example. <1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate. Model-code table headers: No. / Region Code; No. / Customized Specifications; No. / Enclosure Type; No. / Voltage Class; No. / Environmental Specification <3>. <1> Refer to manual TOBPC71060635 for more information on these models. <2> Refer to manual TOBPC71060621 for more information on these models. <3> Drives with these specifications do not guarantee complete protection for the specified environmental condition. Single-Phase 200 V Class. Chapter 1: Receiving.
Nameplate Information Example only. MODEL: CIMR-V followed by blank boxes. MAX APPLI. MOTOR: 0.75kW / 0.4kW; REV: A. INPUT: AC3PH 200-240V 50 / 60Hz 2.7A / 1.4A. OUTPUT: AC3PH 0-240V 0-400Hz 1.2A / 0.8A. MASS: 0.6kg. PRG: blank boxes. O/N and S/N: blank. FILE NO.: E131457. IP20; PASS; MADE IN JAPAN; IND.CONT.EQ. 7J48. YASKAWA ELECTRIC CORPORATION, 2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan. Source logos cULus LISTED, CE, TÜV SÜD Product Service, RoHS. Legend A: Normal Duty Amps / Heavy Duty Amps; B: Software version; C: CE and TÜV Certification; D: Enclosure type; E: Address <1>; F: Serial number; G: Lot number; H: Output specifications; I: Input specifications; J: AC drive model. Example and historical logo data only, not an actual installed unit or current certification verification.
CIMR - V U 2 A 0001 F A A. CIMR: Drive; V: V1000 Series; final A: Design Revision Order. Other positions refer to bounded model-code tables. Example only; not a guarantee that every combination is available.
Refer to the tables below. Pointer from model capacity digits to rating tables; initial single-phase table continues on PDF26.
Figure1.1 model-code key. Example identity not an actual purchased unit. Footnotes1/2 refer separate manuals;footnote3 says protection not guaranteed. No inferred order-code applicability.
Nameplate code Region code — PDF page 25
| Source row | Code | Region code |
|---|---|---|
| 1 | U | USA |
Nameplate code Customized specifications — PDF page 25
| Source row | Code | Customized specifications |
|---|---|---|
| 1 | A | Standard model |
Nameplate code Voltage class — PDF page 25
| Source row | Code | Voltage class |
|---|---|---|
| 1 | B | 1-phase, 200-240 Vac |
| 2 | 2 | 3-phase, 200-240 Vac |
| 3 | 4 | 3-phase, 380-480 Vac |
Nameplate code Enclosure type — PDF page 25
| Source row | Code | Enclosure type |
|---|---|---|
| 1 | A | IP00/Open-Chassis |
| 2 | B | IP20/Open-Chassis |
| 3 | F | IP20/NEMA Type 1 |
| 4 | G | NEMA 4X/IP66 <1> |
| 5 | J | IP20/Finless <2> |
| 6 | L | IP00/Finless <2> |
Nameplate code Environmental specification — PDF page 25
| Source row | Code | Environmental specification |
|---|---|---|
| 1 | A | Standard |
| 2 | M | Humidity- and dust-resistant |
| 3 | S | Vibration-resistant |
Single-phase200V class initial ratings — PDF page 25
| Source row | Model | Normal duty max motor kW | Normal duty rated output A | Heavy duty max motor kW | Heavy duty rated output A |
|---|---|---|---|---|---|
| 1 | BA0001 | 0.2 | 1.2 | 0.1 | 0.8 |
| 2 | BA0002 | 0.4 | 1.9 | 0.2 | 1.6 |
| 3 | BA0003 | 0.75 | 3.3 | 0.4 | 3.0 |
| 4 | BA0006 | 1.1 | 6.0 | 0.75 | 5.0 |
| 5 | BA0010 | 2.2 | 9.6 | 1.5 | 8.0 |
| 6 | BA0012 | 3.0 | 12.0 | 2.2 | 11.0 |
Manual — Rating tables: single-phase continuation and three-phase classes — page 26
Source reference: SIEP C71060618F, December 2016, physical PDF page 26. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.2 Model Number and Nameplate Check <1> Available with Heavy Duty rating only. n Three-Phase 200 V Class n Three-Phase 400 V Class Note: Refer to Component Names on page 28 for differences regarding enclosure protection types and component descriptions.
Single-phase200V continuation from PDF25; BA0018 HD only — PDF page 26
| Source row | Model | Normal duty max motor kW | Normal duty rated output A | Heavy duty max motor kW | Heavy duty rated output A |
|---|---|---|---|---|---|
| 1 | BA0018 <1> | – | – | 3.7 | 17.5 |
Three-phase200V ratings — PDF page 26
| Source row | Model | Normal duty max motor kW | Normal duty rated output A | Heavy duty max motor kW | Heavy duty rated output A |
|---|---|---|---|---|---|
| 1 | 2A0001 | 0.2 | 1.2 | 0.1 | 0.8 |
| 2 | 2A0002 | 0.4 | 1.9 | 0.2 | 1.6 |
| 3 | 2A0004 | 0.75 | 3.5 | 0.4 | 3.0 |
| 4 | 2A0006 | 1.1 | 6.0 | 0.75 | 5.0 |
| 5 | 2A0010 | 2.2 | 9.6 | 1.5 | 8.0 |
| 6 | 2A0012 | 3.0 | 12.0 | 2.2 | 11.0 |
| 7 | 2A0020 | 5.5 | 19.6 | 3.7 | 17.5 |
| 8 | 2A0030 | 7.5 | 30.0 | 5.5 | 25.0 |
| 9 | 2A0040 | 11 | 40.0 | 7.5 | 33.0 |
| 10 | 2A0056 | 15 | 56.0 | 11 | 47.0 |
| 11 | 2A0069 | 18.5 | 69.0 | 15 | 60.0 |
Three-phase400V ratings — PDF page 26
| Source row | Model | Normal duty max motor kW | Normal duty rated output A | Heavy duty max motor kW | Heavy duty rated output A |
|---|---|---|---|---|---|
| 1 | 4A0001 | 0.4 | 1.2 | 0.2 | 1.2 |
| 2 | 4A0002 | 0.75 | 2.1 | 0.4 | 1.8 |
| 3 | 4A0004 | 1.5 | 4.1 | 0.75 | 3.4 |
| 4 | 4A0005 | 2.2 | 5.4 | 1.5 | 4.8 |
| 5 | 4A0007 | 3.0 | 6.9 | 2.2 | 5.5 |
| 6 | 4A0009 | 3.7 | 8.8 | 3.0 | 7.2 |
| 7 | 4A0011 | 5.5 | 11.1 | 3.7 | 9.2 |
| 8 | 4A0018 | 7.5 | 17.5 | 5.5 | 14.8 |
| 9 | 4A0023 | 11 | 23.0 | 7.5 | 18.0 |
| 10 | 4A0031 | 15 | 31.0 | 11 | 24.0 |
| 11 | 4A0038 | 18.5 | 38.0 | 15 | 31.0 |
Manual — Drive models and enclosure types — page 27
Source reference: SIEP C71060618F, December 2016, physical PDF page 27. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.3 Drive Models and Enclosure Types 1.3 Drive Models and Enclosure Types The following table describes drive enclosures and models. Table 1.1 Drive Models and Enclosure Types Receiving 1 Two types of enclosures are offered for V1000 drives. • IP20/Open-Chassis and IP00/Open-Chassis models are often placed inside a large enclosure panel where the front of the drive is covered to prevent someone from accidentally touching charged components. • IP20/NEMA Type 1 models mount to an indoor wall and not inside a large enclosure panel.
Single-Phase 200 V Class | BA0001B
Single-Phase 200 V Class | BA0002B
Single-Phase 200 V Class | BA0003B
Single-Phase 200 V Class | BA0006B
Single-Phase 200 V Class | BA0010B
Single-Phase 200 V Class | BA0012B
Single-Phase 200 V Class | BA0018B
Three-Phase 200 V Class | 2A0001B
Three-Phase 200 V Class | 2A0002B
Three-Phase 200 V Class | 2A0004B
Three-Phase 200 V Class | 2A0006B
Three-Phase 200 V Class | 2A0010B
Three-Phase 200 V Class | 2A0012B
Three-Phase 200 V Class | 2A0020B
Three-Phase 200 V Class | –
Three-Phase 400 V Class | 4A0001B
Three-Phase 400 V Class | 4A0002B
Three-Phase 400 V Class | 4A0004B
Three-Phase 400 V Class | 4A0005B
Three-Phase 400 V Class | 4A0007B
Three-Phase 400 V Class | 4A0009B
Three-Phase 400 V Class | 4A0011B
Three-Phase 400 V Class | –
Table1.1 enclosure model availability — PDF page 27
| Source row | Voltage class | IP20/Open-Chassis drive model | IP00/Open-Chassis drive model | IP20/NEMA Type1 drive model |
|---|---|---|---|---|
| 1 | Single-Phase 200 V Class | BA0001B | – | BA0001F |
| 2 | Single-Phase 200 V Class | BA0002B | – | BA0002F |
| 3 | Single-Phase 200 V Class | BA0003B | – | BA0003F |
| 4 | Single-Phase 200 V Class | BA0006B | – | BA0006F |
| 5 | Single-Phase 200 V Class | BA0010B | – | BA0010F |
| 6 | Single-Phase 200 V Class | BA0012B | – | BA0012F |
| 7 | Single-Phase 200 V Class | BA0018B | – | BA0018F |
| 8 | Three-Phase 200 V Class | 2A0001B | – | 2A0001F |
| 9 | Three-Phase 200 V Class | 2A0002B | – | 2A0002F |
| 10 | Three-Phase 200 V Class | 2A0004B | – | 2A0004F |
| 11 | Three-Phase 200 V Class | 2A0006B | – | 2A0006F |
| 12 | Three-Phase 200 V Class | 2A0010B | – | 2A0010F |
| 13 | Three-Phase 200 V Class | 2A0012B | – | 2A0012F |
| 14 | Three-Phase 200 V Class | 2A0020B | – | 2A0020F |
| 15 | Three-Phase 200 V Class | – | 2A0030A | 2A0030F |
| 16 | Three-Phase 200 V Class | – | 2A0040A | 2A0040F |
| 17 | Three-Phase 200 V Class | – | 2A0056A | 2A0056F |
| 18 | Three-Phase 200 V Class | – | 2A0069A | 2A0069F |
| 19 | Three-Phase 400 V Class | 4A0001B | – | 4A0001F |
| 20 | Three-Phase 400 V Class | 4A0002B | – | 4A0002F |
| 21 | Three-Phase 400 V Class | 4A0004B | – | 4A0004F |
| 22 | Three-Phase 400 V Class | 4A0005B | – | 4A0005F |
| 23 | Three-Phase 400 V Class | 4A0007B | – | 4A0007F |
| 24 | Three-Phase 400 V Class | 4A0009B | – | 4A0009F |
| 25 | Three-Phase 400 V Class | 4A0011B | – | 4A0011F |
| 26 | Three-Phase 400 V Class | – | 4A0018A | 4A0018F |
| 27 | Three-Phase 400 V Class | – | 4A0023A | 4A0023F |
| 28 | Three-Phase 400 V Class | – | 4A0031A | 4A0031F |
| 29 | Three-Phase 400 V Class | – | 4A0038A | 4A0038F |
Manual — Component illustration and source-specific legend — page 28
Source reference: SIEP C71060618F, December 2016, physical PDF page 28. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.4 Component Names 1.4 Component Names This section illustrates the drive components as they are mentioned in this manual. u IP20/Open-Chassis n Single-Phase AC 200 V BA0001B to BA0003B Three-Phase AC 200 V 2A0001B to 2A0006B Figure 1.2 Exploded View of IP20/Open-Chassis Type Components (Model 2A0006B) <1> Models BA0001B to BA0003B and 2A0001B to 2A0004B do not have a cooling fan or a cooling fan cover.
Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.
A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 F – Terminal cover
G – Front cover screw H – Front cover I – Comm port J – LED operator Refer to Using the Digital LED Operator on page 80 K – Case L – Cooling fan <1>
Manual — Component illustration and source-specific legend — page 29
Source reference: SIEP C71060618F, December 2016, physical PDF page 29. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.4 Component Names n Single-Phase AC 200 V BA0006B to BA0018B Three-Phase AC 200 V 2A0010B to 2A0020B Three-Phase AC 400 V 4A0001B to 4A0011B Receiving 1 Figure 1.3 Exploded View of IP20/Open-Chassis Type Components (Model 2A0012B) <1> Models BA0006B and 4A0001B to 4A0004B do not have a cooling fan or a cooling fan cover. Model BA0018B has two cooling fans.
Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.
A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Comm port F – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 G – Front cover screw
H – Front cover I – Terminal cover J – Bottom cover K – LED operator Refer to Using the Digital LED Operator on page 80 L – Case M – Cooling fan <1>
Manual — Component illustration and source-specific legend — page 30
Source reference: SIEP C71060618F, December 2016, physical PDF page 30. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.4 Component Names u IP00/Open-Chassis n Three-Phase AC 200 V 2A0030A to 2A0069A Three-Phase AC 400 V 4A0018A to 4A0038A Figure 1.4 Exploded View of IP00/Open-Chassis Type Components (Model 4A0018A)
Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.
A – Fan cover B – Cooling Fan C – Mounting hole D – Heatsink E – Optional 24 VDC power supply connector cover F – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 G – Bottom cover
H – Front cover screw I – Front cover J – Terminal cover K – Comm port L – LED operator Refer to Using the Digital LED Operator on page 80 M – Case
Manual — Component illustration and source-specific legend — page 31
Source reference: SIEP C71060618F, December 2016, physical PDF page 31. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.4 Component Names u IP20/NEMA Type 1 Enclosure n Single-Phase AC 200 V BA0001F to BA0003F Three-Phase AC 200 V 2A0001F to 2A0006F Receiving 1 Figure 1.5 Exploded View of IP20/NEMA Type 1 Components (Model 2A0006F) <1> Models BA0001F to BA0003F and 2A0001F to 2A0004F do not have a cooling fan or a cooling fan cover.
Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.
A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 F – Bottom cover screws G – Rubber bushing H – Bottom front cover
I – Front cover screws J – Front cover K – Comm port L – LED operator Refer to Using the Digital LED Operator on page 80 M – Case N – Top cover O – Cooling fan <1>
Manual — Component illustration and source-specific legend — page 32
Source reference: SIEP C71060618F, December 2016, physical PDF page 32. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.4 Component Names n Single-Phase AC 200 V BA0006F to BA0018F Three-Phase AC 200 V 2A0010F to 2A0020F Three-Phase AC 400 V 4A0001F to 4A0011F Figure 1.6 Exploded view of IP20/NEMA Type 1 Components (Model 2A0012F) <1> Models BA0006B and 4A0001B to 4A0004B do not have a cooling fan or a cooling fan cover. Model BA0018B has two cooling fans.
Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.
A – Fan cover <1> B – Mounting hole C – Heatsink D – Optional 24 VDC power supply connector cover E – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 F – Cover screws G – Rubber bushing H – Bottom cover
I – Front cover screws J – Front cover K – Terminal cover L – Comm port M – LED operator Refer to Using the Digital LED Operator on page 80 N – Case O – Top cover P – Cooling fan <1>
Manual — Component illustration and source-specific legend — page 33
Source reference: SIEP C71060618F, December 2016, physical PDF page 33. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.4 Component Names n Three-Phase AC 200 V 2A0030F to 2A0069F Three-Phase AC 400 V 4A00018F to 4A0038F Receiving 1 Figure 1.7 Exploded View of IP20/NEMA Type 1 Components (Model 4A0018F)
Exploded-view callout letters correspond to the same-page source legend. Geometry, miniature operator/terminal artwork and assembly routing remain in original.
A – Fan cover B – Cooling fan C – Mounting Hole D – Case and Heatsink E – Optional 24 VDC power supply connection cover F – Cover screws G – Rubber bushing H – Bottom cover
I – Front cover screws J – Terminal cover K – Terminal board Refer to Control Circuit Terminal Block Functions on page 64 L – Front cover M – Comm port N – LED operator Refer to Using the Digital LED Operator on page 80 O – Case P – Top cover
Manual — Component illustration and source-specific legend — page 34
Source reference: SIEP C71060618F, December 2016, physical PDF page 34. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
1.4 Component Names u Front Views Figure 1.8 Front Views of Drives
Front-view example models 2A0006B and 2A0012B. Callouts A–I correspond to same-page legend; original terminal and switch geometry retained.
A – Terminal board connector B – DIP switch S1 Refer to DIP Switch S1 Analog Input Signal Selection on page 70 C – DIP switch S3 Refer to Sinking/ Sourcing Mode Switch on page 68 D – Control circuit terminal Refer to Control Circuit Wiring on page 63 E – Main circuit terminal Refer to Wiring the Main Circuit Terminal on page 62
F – Ground terminal G – Terminal cover H – Option card connector Refer to Connecting the Option Card on page 338 I – DIP switch S2 Refer to MEMOBUS/ Modbus Termination on page 71
Manual — Mechanical installation safety and cooling — page 36
Source reference: SIEP C71060618F, December 2016, physical PDF page 36. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.1 Section Safety 2.1 Section Safety WARNING Fire Hazard Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet. Failure to comply could result in overheating and fire. When multiple drives are placed inside the same enclosure panel, install proper cooling to ensure air entering the enclosure does not exceed 40 °C. CAUTION Crush Hazard Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling. NOTICE Observe proper electrostatic discharge (ESD) procedures when handling the drive. Failure to comply could result in ESD damage to the drive circuitry. It may be difficult to perform maintenance on the cooling fans of drives installed in a vertical row inside an enclosure. Ensure adequate spacing at the top of the drive to perform cooling fan replacement when required. Operating the motor in the low-speed range diminishes the cooling effects, increases motor temperature, and may lead to motor damage by overheating. Reduce the motor torque in the low-speed range whenever using a standard blower cooled motor. If 100% torque is required continuously at low speed, consider using a special drive or vector motor. Select a motor that is compatible with the required load torque and operating speed range. Do not operate motors above the maximum rated RPM. Failure to comply may lead to bearing or other mechanical motor failures. The speed range for continuous operation differs according to the lubrication method and motor manufacturer. If the motor is to be operated at a speed higher than the rated speed, consult with the manufacturer. Continuously operating an oil-lubricated motor in the low-speed range may result in burning.
Manual — Motor wiring, explosion-proof system and motor restrictions — page 37
Source reference: SIEP C71060618F, December 2016, physical PDF page 37. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.1 Section Safety NOTICE When the wiring distance is greater than 100 meters, pay special attention to the motor insulation voltage or use a drive-rated motor. Failure to comply could lead to motor winding failure. Motor vibration may increase when operating a machine in variable-speed mode, if that machine previously operated at a constant speed. Install vibration-proof rubber on the motor base or use the frequency jump function to skip a frequency resonating the machine. The motor may require more acceleration torque with drive operation than with a commercial power supply. Set a proper V/f pattern by checking the load torque characteristics of the machine to be used with the motor. The rated input current of submersible motors is higher than the rated input current of standard motors. Select an appropriate drive according to its rated output current. When the distance between the motor and drive is long, use a cable thick enough to connect the motor to the drive to prevent motor torque reduction. When using an explosion-proof motor, it must be subject to an explosion-proof test in conjunction with the drive. This is also applicable when an existing explosion-proof motor is to be operated with the drive. Since the drive itself is not explosion-proof, always install it in a safe place. Be sure to set A1-02 to “0” when using an explosion-proof motor. Do not use a drive for a single-phase motor. Replace the motor with a three-phase motor. If an oil-lubricated gearbox or speed reducer is used in the power transmission mechanism, oil lubrication will be affected when the motor operates only in the low speed range. The power transmission mechanism will make noise and experience problems with service life and durability if the motor is operated at a speed higher than the rated speed. Installation Mechanical 2
Manual — Installation environment and orientation — page 38
Source reference: SIEP C71060618F, December 2016, physical PDF page 38. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation 2.2 Mechanical Installation This section outlines specifications, procedures, and environment for proper mechanical installation of the drive. u Installation Environment To help prolong the optimum performance life of the drive, install the drive in the proper environment. Table 2.1 describes the appropriate environment for the drive. Table 2.1 Installation Environment NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat. NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive. Failure to comply could result in erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise. u Installation Orientation and Spacing Install the drive upright as illustrated in Figure 2.1 to maintain proper cooling. A – Correct B – Incorrect Figure 2.1 Correct Installation Orientation
Figure2.1 A: Correct upright orientation; B: Incorrect orientations. Original orientation drawings remain authoritative.
Table2.1 Installation environment — PDF page 38
| Source row | Environment | Conditions |
|---|---|---|
| 1 | Installation Area | Indoors |
| 2 | Ambient Temperature | IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F) IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F) Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F) NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F) Drive reliability improves in environments without wide temperature fluctuations. When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels. Do not allow ice to develop on the drive. |
| 3 | Humidity | 95% RH or less and free of condensation |
| 4 | Storage Temperature | -20 °C to +60 °C (-4 °F to +104 °F) |
| 5 | Surrounding Area | Install the drive in an area free from: • oil mist and dust • metal shavings, oil, water or other foreign materials • radioactive materials • combustible materials (e.g., wood) • harmful gases and liquids • excessive vibration • chlorides • direct sunlight |
| 6 | Altitude | Up to 1000 meters without derating; up to 3000 meters with output current, ambient temperature, and voltage derating. Refer to Altitude Derating on page 352 for details. |
| 7 | Vibration | 10 to 20 Hz at 9.8 m/s2 20 to 55 Hz at 5.9 m/s2 |
| 8 | Orientation | Install the drive vertically to maintain maximum cooling effects. |
Manual — Single and multiple drive spacing — page 39
Source reference: SIEP C71060618F, December 2016, physical PDF page 39. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation n Single Drive Installation Figure 2.2 shows the required installation spacing to maintain sufficient space for airflow and wiring. Install the heatsink against a closed surface to avoid diverting cooling air around the heatsink. Figure 2.2 Correct Installation Spacing Note: IP20/NEMA Type 1, IP00/Open-Chassis, and IP20/Open-Chassis models require the same amount of space above and below the drive for installation. n Multiple Drive Installation When installing multiple drives into the same enclosure panel, mount the drives according to Figure 2.2. When mounting drives with a minimum side-by-side clearance of 2 mm according to Figure 2.3, derating must be considered and parameter L8-35 must be set. Refer to Parameter List on page 353. Installation Mechanical 2 Figure 2.3 Space Between Drives (Side-by-Side Mounting) Note: When installing drives of different heights in the same enclosure panel, the tops of the drives should line up. Leave space between the top and bottom of stacked drives for cooling fan replacement if required. Using this method, it is possible to replace the cooling fans later. NOTICE: When mounting IP20/NEMA Type 1 enclosure drives side by side, the top covers of all drives must be removed as shown in Figure 2.4. Figure 2.4 IP20/NEMA Type 1 Side-by-Side Mounting in Enclosure
Figure2.2 Side Clearance A; Top/Bottom Clearance C; B airflow direction. The numeric legend is preserved separately; geometry remains original-only.
A – 30 mm minimum; B – Airflow direction; C – 100 mm minimum.
2 mm between adjacent drives; A top alignment, B side clearance, C top/bottom clearance, D airflow direction. Read with derating and L8-35 requirement and complete same-page instructions. Geometry original-only.
A – Line up the tops of the drives; B – 30 mm minimum; C – 100 mm minimum; D – Airflow direction.
IP20/NEMA Type1 side-by-side mounting in enclosure; source instruction requires removal of top covers. Illustration geometry remains original-only.
Manual — Dimension page index and protective design — page 40
Source reference: SIEP C71060618F, December 2016, physical PDF page 40. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation u Removing and Attaching the Protective Covers Refer to Electrical Installation on page 47, for information regarding the removal and reattachment of protective covers. u Exterior and Mounting Dimensions Table 2.2 Drive Models and Types Note: Refer to Specifications on page 341 for information on the amount of heat generated by the drive and appropriate cooling methods.
Source model groups and dimension-page references; cross-row borders explicitly followed. No implied compatibility across groups.
Table2.2 Drive models and dimension page references — PDF page 40
| Source row | Protective design | Single-phase200V | Three-phase200V | Three-phase400V | Page |
|---|---|---|---|---|---|
| 1 | IP20/Open-Chassis | BA0001B BA0002B BA0003B | 2A0001B 2A0002B 2A0004B 2A0006B | – | 41 |
| 2 | IP20/Open-Chassis | BA0006B BA0010B BA0012B BA0018B | 2A0010B 2A0012B 2A0020B | 4A0001B 4A0002B 4A0004B 4A0005B 4A0007B 4A0009B 4A0011B | 41 |
| 3 | IP00/Open-Chassis | – | 2A0030A 2A0040A 2A0056A 2A0069A | 4A0018A 4A0023A 4A0031A 4A0038A | 43 |
| 4 | IP20/NEMA Type 1 | BA0001F BA0002F BA0003F | 2A0001F 2A0002F 2A0004F | – | 44 |
| 5 | IP20/NEMA Type 1 | BA0006F BA0010F BA0012F BA0018F | 2A0006F 2A0010F 2A0012F 2A0020F | 4A0001F 4A0002F 4A0004F 4A0005F 4A0007F 4A0009F 4A0011F | 44 |
| 6 | IP20/NEMA Type 1 | – | 2A0030F 2A0040F 2A0056F 2A0069F | 4A0018F 4A0023F 4A0031F 4A0038F | 46 |
Manual — Mounting dimensions and weights without EMC filter — page 41
Source reference: SIEP C71060618F, December 2016, physical PDF page 41. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation n IP20/Open-Chassis Drives Table 2.3 IP20/Open-Chassis (without an EMC filter) Installation Table 2.4 IP20/Open-Chassis (without an EMC filter) Mechanical 2
W, W1, H, H1, H2, D, D1, t1; 2-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
W, W1, H, H1, H2, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.
Single-Phase 200 V Class | BA0001B
Single-Phase 200 V Class | BA0002B
Single-Phase 200 V Class | BA0003B
Three-Phase 200 V Class | 2A0001B
Three-Phase 200 V Class | 2A0002B
Three-Phase 200 V Class | 2A0004B
Three-Phase 200 V Class | 2A0006B
Single-Phase 200 V Class | BA0006B
Single-Phase 200 V Class | BA0010B
Single-Phase 200 V Class | BA0012B
Single-Phase 200 V Class | BA0018B
Table2.3 IP20/Open-Chassis without EMC filter — PDF page 41
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | D1 mm (in) | t1 mm (in) | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Single-Phase 200 V Class | BA0001B | 68 (2.68) | 128 (5.04) | 76 (2.99) | 56 (2.20) | 118 (4.65) | 5 (0.20) | 6.5 (0.26) | 3 (0.12) | 0.6 (1.3) |
| 2 | Single-Phase 200 V Class | BA0002B | 68 (2.68) | 128 (5.04) | 76 (2.99) | 56 (2.20) | 118 (4.65) | 5 (0.20) | 6.5 (0.26) | 3 (0.12) | 0.6 (1.3) |
| 3 | Single-Phase 200 V Class | BA0003B | 68 (2.68) | 128 (5.04) | 118 (4.65) | 56 (2.20) | 118 (4.65) | 5 (0.20) | 38.5 (1.52) | 5 (0.20) | 1.0 (2.2) |
| 4 | Three-Phase 200 V Class | 2A0001B | 68 (2.68) | 128 (5.04) | 76 (2.99) | 56 (2.20) | 118 (4.65) | 5 (0.20) | 6.5 (0.26) | 3 (0.12) | 0.6 (1.3) |
| 5 | Three-Phase 200 V Class | 2A0002B | 68 (2.68) | 128 (5.04) | 76 (2.99) | 56 (2.20) | 118 (4.65) | 5 (0.20) | 6.5 (0.26) | 3 (0.12) | 0.6 (1.3) |
| 6 | Three-Phase 200 V Class | 2A0004B | 68 (2.68) | 128 (5.04) | 108 (4.25) | 56 (2.20) | 118 (4.65) | 5 (0.20) | 38.5 (1.52) | 5 (0.20) | 0.9 (2.0) |
| 7 | Three-Phase 200 V Class | 2A0006B | 68 (2.68) | 128 (5.04) | 128 (5.04) | 56 (2.20) | 118 (4.65) | 5 (0.20) | 58.5 (2.30) | 5 (0.20) | 1.1 (2.4) |
Table2.4 IP20/Open-Chassis without EMC filter — PDF page 41
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | D1 mm (in) | t1 mm (in) | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Single-Phase 200 V Class | BA0006B | 108 (4.25) | 128 (5.04) | 137.5 (5.41) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.7 (3.7) |
| 2 | Single-Phase 200 V Class | BA0010B | 108 (4.25) | 128 (5.04) | 154 (6.06) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.8 (4.0) |
| 3 | Single-Phase 200 V Class | BA0012B | 140 (5.51) | 128 (5.04) | 163 (6.42) | 128 (5.04) | 118 (4.65) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 2.4 (5.3) |
| 4 | Single-Phase 200 V Class | BA0018B | 170 (6.69) | 128 (5.04) | 180 (7.09) | 158 (6.22) | 118 (4.65) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 3.0 (6.6) |
Manual — Mounting dimensions and weights without EMC filter — page 42
Source reference: SIEP C71060618F, December 2016, physical PDF page 42. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation
W, W1, H, H1, H2, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.
Three-Phase 200 V Class | 2A0010B
Three-Phase 200 V Class | 2A0012B
Three-Phase 200 V Class | 2A0020B
Three-Phase 400 V Class | 4A0001B
Three-Phase 400 V Class | 4A0002B
Three-Phase 400 V Class | 4A0004B
Three-Phase 400 V Class | 4A0005B
Three-Phase 400 V Class | 4A0007B
Three-Phase 400 V Class | 4A0009B
Three-Phase 400 V Class | 4A0011B
Table2.4 continuation IP20/Open-Chassis without EMC filter — PDF page 42
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | D1 mm (in) | t1 mm (in) | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Three-Phase 200 V Class | 2A0010B | 108 (4.25) | 128 (5.04) | 129 (5.08) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.7 (3.7) |
| 2 | Three-Phase 200 V Class | 2A0012B | 108 (4.25) | 128 (5.04) | 137.5 (5.41) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.7 (3.7) |
| 3 | Three-Phase 200 V Class | 2A0020B | 140 (5.51) | 128 (5.04) | 143 (5.63) | 128 (5.04) | 118 (4.65) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 2.4 (5.3) |
| 4 | Three-Phase 400 V Class | 4A0001B | 108 (4.25) | 128 (5.04) | 81 (3.19) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 10 (0.39) | 5 (0.20) | 1.0 (2.2) |
| 5 | Three-Phase 400 V Class | 4A0002B | 108 (4.25) | 128 (5.04) | 99 (3.90) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 28 (1.10) | 5 (0.20) | 1.2 (2.6) |
| 6 | Three-Phase 400 V Class | 4A0004B | 108 (4.25) | 128 (5.04) | 137.5 (5.41) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.7 (3.7) |
| 7 | Three-Phase 400 V Class | 4A0005B | 108 (4.25) | 128 (5.04) | 154 (6.06) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.7 (3.7) |
| 8 | Three-Phase 400 V Class | 4A0007B | 108 (4.25) | 128 (5.04) | 154 (6.06) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.7 (3.7) |
| 9 | Three-Phase 400 V Class | 4A0009B | 108 (4.25) | 128 (5.04) | 154 (6.06) | 96 (3.78) | 118 (4.65) | 5 (0.20) | 58 (2.28) | 5 (0.20) | 1.7 (3.7) |
| 10 | Three-Phase 400 V Class | 4A0011B | 140 (5.51) | 128 (5.04) | 143 (5.63) | 128 (5.04) | 118 (4.65) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 2.4 (5.3) |
Manual — Mounting dimensions and weights without EMC filter — page 43
Source reference: SIEP C71060618F, December 2016, physical PDF page 43. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation n IP00/Open-Chassis Drives Table 2.5 IP00/Open-Chassis (without an EMC filter) Installation Mechanical 2
W, W1, H, H1, H2, H4, D, D1, t1; 4-d. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.
Three-Phase 200 V Class | 2A0030A
Three-Phase 200 V Class | 2A0040A
Three-Phase 200 V Class | 2A0056A
Three-Phase 200 V Class | 2A0069A
Three-Phase 400 V Class | 4A0018A
Three-Phase 400 V Class | 4A0023A
Three-Phase 400 V Class | 4A0031A
Three-Phase 400 V Class | 4A0038A
Table2.5 IP00/Open-Chassis without EMC filter — PDF page 43
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | H4 mm (in) | D1 mm (in) | d | t1 mm (in) | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Three-Phase 200 V Class | 2A0030A | 140 (5.5) | 254 (9.7) | 140 (5.5) | 122 (4.8) | 234 (9.2) | 248 (9.8) | 13 (0.5) | 55 (2.2) | M5 | 5 (0.2) | 3.8 (7.9) |
| 2 | Three-Phase 200 V Class | 2A0040A | 140 (5.5) | 254 (9.7) | 140 (5.5) | 122 (4.8) | 234 (9.2) | 248 (9.8) | 13 (0.5) | 55 (2.2) | M5 | 5 (0.2) | 3.8 (7.9) |
| 3 | Three-Phase 200 V Class | 2A0056A | 180 (7.1) | 290 (11.2) | 163 (6.4) | 160 (6.3) | 270 (10.6) | 284 (11.2) | 15 (0.6) | 75 (3.0) | M5 | 5 (0.2) | 5.5 (11.7) |
| 4 | Three-Phase 200 V Class | 2A0069A | 220 (8.7) | 350 (13.2) | 187 (7.4) | 192 (7.6) | 320 (12.6) | 336 (13.2) | 15 (0.6) | 78 (3.1) | M6 | 5 (0.2) | 9.2 (19.2) |
| 5 | Three-Phase 400 V Class | 4A0018A | 140 (5.5) | 254 (9.7) | 140 (5.5) | 122 (4.8) | 234 (9.2) | 248 (9.8) | 13 (0.5) | 55 (2.2) | M5 | 5 (0.2) | 3.8 (7.9) |
| 6 | Three-Phase 400 V Class | 4A0023A | 140 (5.5) | 254 (9.7) | 140 (5.5) | 122 (4.8) | 234 (9.2) | 248 (9.8) | 13 (0.5) | 55 (2.2) | M5 | 5 (0.2) | 3.8 (7.9) |
| 7 | Three-Phase 400 V Class | 4A0031A | 180 (7.1) | 290 (11.2) | 143 (5.6) | 160 (6.3) | 270 (10.6) | 284 (11.2) | 15 (0.6) | 55 (2.2) | M5 | 5 (0.2) | 5.2 (11.0) |
| 8 | Three-Phase 400 V Class | 4A0038A | 180 (7.1) | 290 (11.2) | 163 (6.4) | 160 (6.3) | 270 (10.6) | 284 (11.2) | 15 (0.6) | 75 (3.0) | M5 | 5 (0.2) | 5.5 (11.7) |
Manual — Mounting dimensions and weights without EMC filter — page 44
Source reference: SIEP C71060618F, December 2016, physical PDF page 44. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation n IP20/NEMA Type 1 Drives Table 2.6 IP20/NEMA Type 1 (without an EMC filter) Table 2.7 IP20/NEMA Type 1 (without an EMC filter)
W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 2-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.
Single-Phase 200 V Class | BA0001F
Single-Phase 200 V Class | BA0002F
Single-Phase 200 V Class | BA0003F
Three-Phase 200 V Class | 2A0001F
Three-Phase 200 V Class | 2A0002F
Three-Phase 200 V Class | 2A0004F
Three-Phase 200 V Class | 2A0006F
Single-Phase 200 V Class | BA0006F
Single-Phase 200 V Class | BA0010F
Single-Phase 200 V Class | BA0012F
Single-Phase 200 V Class | BA0018F
Table2.6 IP20/NEMA Type1 without EMC filter — PDF page 44
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | H3 mm (in) | H4 mm (in) | H5 mm (in) | H6 mm (in) | D1 mm (in) | t1 mm (in) | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Single-Phase 200 V Class | BA0001F | 68 (2.68) | 149.5 (5.89) | 76 (2.99) | 56 (2.20) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 6.5 (0.26) | 3 (0.12) | 0.8 (1.8) |
| 2 | Single-Phase 200 V Class | BA0002F | 68 (2.68) | 149.5 (5.89) | 76 (2.99) | 56 (2.20) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 6.5 (0.26) | 3 (0.12) | 0.8 (1.8) |
| 3 | Single-Phase 200 V Class | BA0003F | 68 (2.68) | 149.5 (5.89) | 118 (4.65) | 56 (2.20) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 38.5 (1.54) | 5 (0.20) | 1.2 (2.6) |
| 4 | Three-Phase 200 V Class | 2A0001F | 68 (2.68) | 149.5 (5.89) | 76 (2.99) | 56 (2.20) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 6.5 (0.26) | 3 (0.12) | 0.8 (1.8) |
| 5 | Three-Phase 200 V Class | 2A0002F | 68 (2.68) | 149.5 (5.89) | 76 (2.99) | 56 (2.20) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 6.5 (0.26) | 3 (0.12) | 0.8 (1.8) |
| 6 | Three-Phase 200 V Class | 2A0004F | 68 (2.68) | 149.5 (5.89) | 108 (4.25) | 56 (2.20) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 38.5 (1.54) | 5 (0.20) | 1.1 (2.4) |
| 7 | Three-Phase 200 V Class | 2A0006F | 68 (2.68) | 149.5 (5.89) | 128 (5.04) | 56 (2.20) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58.5 (2.32) | 5 (0.20) | 1.3 (2.9) |
Table2.7 IP20/NEMA Type1 without EMC filter — PDF page 44
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | H3 mm (in) | H4 mm (in) | H5 mm (in) | H6 mm (in) | D1 mm (in) | t1 mm (in) | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Single-Phase 200 V Class | BA0006F | 108 (4.25) | 149.5 (5.89) | 137.5 (5.41) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 1.9 (4.2) |
| 2 | Single-Phase 200 V Class | BA0010F | 108 (4.25) | 149.5 (5.89) | 154 (6.06) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 2.0 (4.4) |
| 3 | Single-Phase 200 V Class | BA0012F | 140 (5.51) | 153 (6.02) | 163 (6.42) | 128 (5.04) | 128 (5.03) | 118 (4.65) | 4.8 (0.19) | 20 (0.79) | 5 (0.20) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 2.6 (5.7) |
| 4 | Single-Phase 200 V Class | BA0018F | 170 (6.69) | 171 (6.73) | 180 (7.08) | 158 (6.22) | 133 (5.23) | 118 (4.64) | 4.8 (0.19) | 38 (1.50) | 5 (0.20) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 3.3 7.3 |
Manual — Mounting dimensions and weights without EMC filter — page 45
Source reference: SIEP C71060618F, December 2016, physical PDF page 45. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation Installation Mechanical 2
W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 4-M4. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.
Three-Phase 200 V Class | 2A0010F
Three-Phase 200 V Class | 2A0012F
Three-Phase 200 V Class | 2A0020F
Three-Phase 400 V Class | 4A0001F
Three-Phase 400 V Class | 4A0002F
Three-Phase 400 V Class | 4A0004F
Three-Phase 400 V Class | 4A0005F
Three-Phase 400 V Class | 4A0007F
Three-Phase 400 V Class | 4A0009F
Three-Phase 400 V Class | 4A0011F
Table2.7 continuation IP20/NEMA Type1 without EMC filter — PDF page 45
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | H3 mm (in) | H4 mm (in) | H5 mm (in) | H6 mm (in) | D1 mm (in) | t1 mm (in) | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Three-Phase 200 V Class | 2A0010F | 108 (4.25) | 149.5 (5.89) | 129 (5.08) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 1.9 (4.2) |
| 2 | Three-Phase 200 V Class | 2A0012F | 108 (4.25) | 149.5 (5.89) | 137.5 (5.41) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 1.9 (4.2) |
| 3 | Three-Phase 200 V Class | 2A0020F | 140 (5.51) | 153 (6.02) | 143 (5.63) | 128 (5.04) | 128 (5.03) | 118 (4.65) | 4.8 (0.19) | 20 (0.79) | 5 (0.20) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 2.6 (5.7) |
| 4 | Three-Phase 400 V Class | 4A0001F | 108 (4.25) | 149.5 (5.89) | 81 (3.19) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 10 (0.39) | 5 (0.20) | 1.2 (2.6) |
| 5 | Three-Phase 400 V Class | 4A0002F | 108 (4.25) | 149.5 (5.89) | 99 (3.90) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 28 (1.10) | 5 (0.20) | 1.4 (3.1) |
| 6 | Three-Phase 400 V Class | 4A0004F | 108 (4.25) | 149.5 (5.89) | 137.5 (5.41) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 1.9 (4.2) |
| 7 | Three-Phase 400 V Class | 4A0005F | 108 (4.25) | 149.5 (5.89) | 154 (6.06) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 1.9 (4.2) |
| 8 | Three-Phase 400 V Class | 4A0007F | 108 (4.25) | 149.5 (5.89) | 154 (6.06) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 1.9 (4.2) |
| 9 | Three-Phase 400 V Class | 4A0009F | 108 (4.25) | 149.5 (5.89) | 154 (6.06) | 96 (3.78) | 128 (5.03) | 118 (4.65) | 4 (0.16) | 20 (0.79) | 5 (0.20) | 1.5 (0.06) | 58 (2.28) | 5 (0.20) | 1.9 (4.2) |
| 10 | Three-Phase 400 V Class | 4A0011F | 140 (5.51) | 153 (6.02) | 143 (5.63) | 128 (5.04) | 128 (5.03) | 118 (4.65) | 4.8 (0.19) | 20 (0.79) | 5 (0.20) | 5 (0.20) | 65 (2.56) | 5 (0.20) | 2.6 (5.7) |
Manual — Mounting dimensions and weights without EMC filter — page 46
Source reference: SIEP C71060618F, December 2016, physical PDF page 46. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
2.2 Mechanical Installation Table 2.8 IP20/NEMA Type 1 (without an EMC filter)
W, W1, H, H1, H2, H3, H4, H5, H6, D, D1, t1; 4-d. Numeric values belong to the adjacent model table. Original dimension arrows and geometry remain authoritative; no measured or inferred dimension.
Dimensions mm (in); Wt. kg (lb.). Without an EMC filter. Literal metric/imperial pairs retained, including source discrepancies. Shared voltage class repeated only in its physical merged extent; diagram geometry remains original-only.
Three- Phase 200 V Class | 2A0030F
Three- Phase 200 V Class | 2A0040F
Three- Phase 200 V Class | 2A0056F
Three- Phase 200 V Class | 2A0069F
Three- Phase 400 V Class | 4A0018F
Three- Phase 400 V Class | 4A0023F
Three- Phase 400 V Class | 4A0031F
Three- Phase 400 V Class | 4A0038F
Table2.8 IP20/NEMA Type1 without EMC filter — PDF page 46
| Source row | Voltage class | Drive model | W mm (in) | H mm (in) | D mm (in) | W1 mm (in) | H1 mm (in) | H2 mm (in) | H3 mm (in) | H4 mm (in) | H5 mm (in) | H6 mm (in) | D1 mm (in) | t1 mm (in) | d | Wt kg (lb) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Three- Phase 200 V Class | 2A0030F | 140 (5.51) | 254 (10.00) | 140 (5.51) | 122 (4.80) | 234 (9.21) | 248 (9.76) | 6 (0.24) | 13 (0.51) | 13 (0.51) | 1.5 (0.06) | 55 (2.17) | 5 (0.20) | M5 | 3.8 (8.4) |
| 2 | Three- Phase 200 V Class | 2A0040F | 140 (5.51) | 254 (10.00) | 140 (5.51) | 122 (4.80) | 234 (9.21) | 248 (9.76) | 6 (0.24) | 13 (0.51) | 13 (0.51) | 1.5 (0.06) | 55 (2.17) | 5 (0.20) | M5 | 3.8 (8.4) |
| 3 | Three- Phase 200 V Class | 2A0056F | 180 (7.09) | 290 (11.42) | 163 (6.42) | 160 (6.30) | 270 (10.63) | 284 (11.18) | 6 (0.24) | 15 (0.59) | 13 (0.51) | 1.5 (0.06) | 75 (2.95) | 5 (0.20) | M5 | 5.5 (12.1) |
| 4 | Three- Phase 200 V Class | 2A0069F | 220 (8.66) | 350 (13.78) | 187 (7.36) | 192 (7.56) | 320 (12.60) | 336 (13.23) | 7 (0.28) | 15 (0.59) | 22 (0.87) | 1.5 (0.06) | 78 (3.07) | 5 (0.20) | M6 | 9.2 (20.3) |
| 5 | Three- Phase 400 V Class | 4A0018F | 140 (5.51) | 254 (10.00) | 140 (5.51) | 122 (4.80) | 234 (9.21) | 248 (9.76) | 6 (0.24) | 13 (0.51) | 13 (0.51) | 1.5 (0.06) | 55 (2.17) | 5 (0.20) | M5 | 3.8 (8.4) |
| 6 | Three- Phase 400 V Class | 4A0023F | 140 (5.51) | 254 (10.00) | 140 (5.51) | 122 (4.80) | 234 (9.21) | 248 (9.76) | 6 (0.24) | 13 (0.51) | 13 (0.51) | 1.5 (0.06) | 55 (2.17) | 5 (0.20) | M5 | 3.8 (8.4) |
| 7 | Three- Phase 400 V Class | 4A0031F | 180 (7.09) | 290 (11.42) | 143 (5.63) | 160 (6.30) | 270 (10.63) | 284 (11.18) | 6 (0.24) | 15 (0.59) | 13 (0.51) | 1.5 (0.06) | 55 (2.17) | 5 (0.20) | M5 | 5.2 (11.5) |
| 8 | Three- Phase 400 V Class | 4A0038F | 180 (7.09) | 290 (11.42) | 163 (6.42) | 160 (6.30) | 270 (10.63) | 284 (11.18) | 6 (0.24) | 13 (0.51) | 13 (0.51) | 1.5 (0.06) | 75 (2.95) | 5 (0.20) | M5 | 5.5 (12.1) |
Manual — Electrical installation hazards and brake protection — page 48
Source reference: SIEP C71060618F, December 2016, physical PDF page 48. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.1 Section Safety 3.1 Section Safety DANGER Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. WARNING Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of AC drives. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Always use a thermal overload relay or an over-temperature contact when using a braking resistor. Failure to comply could result in death or serious injury by fire. Power to the drive should be interrupted when the relay is triggered.
Manual — Electrical wiring notices and lead routing — page 49
Source reference: SIEP C71060618F, December 2016, physical PDF page 49. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.1 Section Safety NOTICE Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Route motor leads U/T1, V/T2, and W/T3 separate from other leads to reduce possible interference-related issues. Failure to comply may result in abnormal operation of drive and nearby equipment. Installation Electrical 3
Manual — Standard connection prerequisites and relay minimum load — page 50
Source reference: SIEP C71060618F, December 2016, physical PDF page 50. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.2 Standard Connection Diagram 3.2 Standard Connection Diagram Connect the drive and peripheral devices as shown in Figure 3.. It is possible to run the drive via the digital operator without connecting digital I/O wiring. This section does not discuss drive operation; Refer to Start-Up Programming & Operation on page 77 for instructions on operating the drive. NOTICE: Inadequate branch short circuit protection could result in damage to the drive. Install adequate branch circuit short circuit protection per applicable codes. The drive is suitable for circuits capable of delivering not more than 31,000 RMS symmetrical amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400 V Class). NOTICE: When the wiring distance is greater than 100 meters, pay special attention to the motor insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown. NOTICE: Correctly set Sink/Source jumper S3 for internal power supply. Failure to comply may result in damage to the drive. Refer to I/O Connections on page 68 for details. NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction. NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to comply may result in abnormal operation of drive and nearby equipment. NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA. If a circuit requires less than 10 mA (reference value), connect it to a photocoupler output (P1, P2, PC). Improper application of peripheral devices could result in damage to the photocoupler output of the drive.
Manual — Standard connection diagram — section title — page 51
Source reference: SIEP C71060618F, December 2016, physical PDF page 51. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.2 Standard Connection Diagram
Figure 3.1 Drive Standard Connection Diagram (original geometry retained). V1000 main circuit/control circuit. Terminals +1, +2, −, B1 and B2 are for connecting options; never connect power supply lines to these terminals. Single-phase 200 V power supply uses R/L1 and S/L2; three-phase power supply for 200 V / 400 V shows R/L1, S/L2, T/L3. Optional DC link choke, jumper +2/+1, optional thermal relay and braking resistor B1/B2. Motor outputs U/T1, V/T2, W/T3; separate cooling fan labels r1, s1, t1 and FU, FV, FW. Ground: 10 Ω or less (400 V class), 100 Ω or less (200 V class). Wiring sequence should shut off power to drive when fault output triggers; 1 MCCB, MC, 2 MCCB; braking resistor unit thermal relay trip contact; fault relay contact; labels TRX, THRX, OFF, ON, MC, SA, MB, contacts 1 and 2. Digital input defaults: S1 Forward run/stop; S2 Reverse run/stop; S3 External fault; S4 Fault reset; S5 Multi-step speed 1 main/aux switch; S6 Multi-step speed 2; S7 Jog reference; SC common. +24 V 8 mA; 24 V; 0 V; DIP switch S3 Sink/Source; shield ground terminal. Option card connector. DIP switch S1 V/I. Digital relay output Fault: MA, MB, MC, 250 Vac 10 mA to 1 A / 30 Vdc 10 mA to 1 A (default). Digital photocoupler output 5 to 48 Vdc, 2 to 50 mA (default): P1 During Run (photocoupler 1); P2 Frequency agree (photocoupler 2); PC photocoupler output common. Main speed frequency reference, multi-function programmable; 2 kΩ potentiometer; RP pulse train input max. 32 kHz; +V setting power supply +10.5 max. 20 mA; A1 0 to +10 V (20 kΩ); A2 0 to +10 V (20 kΩ), (0)4 to 20 mA (250 Ω); AC. MP pulse train output 0 to 32 kHz; AM analog monitor output 0 to +10 Vdc (2 mA); AC. Safe Disable Input: safety switch, HC, H1, jumper. DIP switch S2; termination resistor 120 Ω, 1/2 W; communications connector; R+, R-, S+, S-, IG; MEMOBUS/Modbus communications RS-485/422; cable shield ground. Legend: shielded line, twisted-pair shielded line, main circuit terminal, control terminal. Read footnotes 1–6 on PDF 51 and 7–8 on PDF 52; no wiring topology inferred from this label inventory.
<1> Remove the jumper when installing an optional DC link choke. <2> The MC on the input side of the main circuit should open when the thermal relay is triggered. <3> Self-cooled motors do not require separate cooling fan motor wiring. <4> Connected using sequence input signal (S1 to S7) from NPN transistor; Default: sink mode (0 V com). <5> Use only a +24 V internal power supply in sinking mode; the source mode requires an external power supply. Refer to I/O Connections on page 68 for details. <6> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters and wattmeters; they are not intended for use as a feedback-type of signal.
Installation Electrical 3
Manual — Standard connection footnotes 7–8 and three-wire setup warnings — page 52
Source reference: SIEP C71060618F, December 2016, physical PDF page 52. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.2 Standard Connection Diagram <7> Disconnect the wire jumper between HC and H1 when utilizing the safety input. Refer to Wiring Procedure on page 66 for details on removing the jumper. The wire length for the Safe Disable input should not exceed 30 m. Use only dry contacts on safety inputs HC-H1. External power supplies are not permitted. <8> Note that if the drive is set to trigger a fault output whenever the fault restart function is activated (L5-02 = 1), then a sequence to interrupt power when a fault occurs will result in shutting off the power to the drive as the drive attempts to restart itself. The default setting for L5-02 is 0 (fault output active during restart attempt). WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal parameter is properly set (S5 for 3-Wire; H1-05 = “0”). Improper sequencing of run/stop circuitry could result in death or serious injury from moving equipment. WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on terminal S1 may cause the drive to start. WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run command at power up (default). If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter b1-17 is set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at power up of the drive and may cause injury. WARNING! When the application preset function is executed (or A1-06 is set to any value other than 0) the drive I/O terminal functions change. This may cause unexpected operation and potential damage to equipment or injury. Figure 3.2 illustrates an example of a 3-Wire sequence.
Figure 3.2 3-Wire Sequence example: Stop relay (N.C.); Run relay (N.O.); Drive S1 Run command (run on momentary close); S2 Stop command (stop on momentary open); S5 Forward/reverse command (multi-function input: H1-05 = 0); SC Sequence input common. Original connection geometry remains authoritative.
Manual — Main circuit and negative DC bus warning; single-phase model scope — page 53
Source reference: SIEP C71060618F, December 2016, physical PDF page 53. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.3 Main Circuit Connection Diagram 3.3 Main Circuit Connection Diagram Refer to diagrams in this section for the Main Circuit wiring connections. Connections may vary based on drive capacity. The main circuit DC power supply powers the control circuit. NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high voltage DC potential. Improper wiring connections could result in damage to the drive. u Single-Phase 200 V Class Models BA0001 to BA0018
Figure 3.3 Connecting Single-Phase Main Circuit Terminals. BA0001 to BA0018, single-phase 200 Vac. Drive labels R/L1, S/L2, −, +2, +1, B1, B2; outputs U/T1, V/T2, W/T3 to Motor; ground symbol. Jumper; DC reactor (option); Braking Resistor Unit (option). Connection geometry original-only; single-phase refers to supply input.
NOTICE: Do not connect T/L3 terminal when using single-phase power supply input. Incorrect wiring may damage the drive. u Three-Phase 200 V Class Models 2A0001 to 2A0069 Three-Phase 400 V Class Models 4A0001 to 4A0038
Figure 3.4 Connecting Three-Phase Main Circuit Terminals. Three-phase 200 V Class 2A0001 to 2A0069; 400 V Class 4A0001 to 4A0038. Three phase 200 Vac (400 Vac); drive R/L1, S/L2, T/L3, −, +2, +1, B1, B2; outputs U/T1, V/T2, W/T3; Motor, ground symbol, jumper, DC reactor (option), Braking Resistor Unit (option). Original diagram retains connection geometry.
Installation Electrical 3
Manual — Terminal block configuration scope — page 54
Source reference: SIEP C71060618F, December 2016, physical PDF page 54. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Source limitation for this page: Source illustrations contain unlabelled screw heads and clipped/hidden side terminal names. All visible group labels checked at5x; unsupported group6 minus assertion superseded by F3172, visible ground/CHARGE context supplied. Do not infer hidden names.
3.4 Terminal Block Configuration 3.4 Terminal Block Configuration The figures in this section provide illustrations of the main circuit terminal block configurations of the different drive sizes.
CIMR-V□BA0001, 0002, 0003 and CIMR-V□2A0001, 0002, 0004, 0006. Visible terminal labels R/L1, S/L2, T/L3, +1, U/T1, V/T2, W/T3; −, +2, B1, B2; ground symbols.
CIMR-V□BA0006, 0010, 0012; CIMR-V□2A0010, 0012, 0020; CIMR-V□4A0001, 0002, 0004, 0005, 0007, 0009, 0011. Visible labels −, +1, +2; R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3; ground symbols.
CIMR-V□2A0030, 0040 and CIMR-V□4A0018, 0023. Visible labels R/L1, S/L2, T/L3, −, +1, +2, U/T1, V/T2, W/T3. Other screw/terminal geometry remains original-only; do not infer hidden brake-terminal labels.
CIMR-V□2A0069. Visible labels +1, +2, B1, B2; R/L1, S/L2, T/L3, −, U/T1, V/T2, W/T3. Other geometry remains original-only.
CIMR-V□BA0018. Visible labels R/L1, S/L2, −, +1, +2, B1, B2, U/T1, V/T2, W/T3; ground symbols.
Figure 3.5 Main Circuit Terminal Block Configurations
CIMR-V□2A0056 and CIMR-V□4A0031, 0038. Visible labels R/L1, S/L2, T/L3, +1, +2, U/T1, V/T2, W/T3; ground symbols are visible below. The side terminal edges and upper screw heads have no legible terminal names in this illustration. No visible minus label is supported here; no hidden brake-terminal labels or wiring topology inferred.
Figure3.5 also visibly draws ground symbols below the model groups CIMR-V□2A0030,0040 / CIMR-V□4A0018,0023; CIMR-V□2A0069; and CIMR-V□2A0056 / CIMR-V□4A0031,0038. These are glyph descriptions only, not a wiring route or terminal-rating assertion.
In Figure3.5 model CIMR-V□2A0069 illustration, the vertical left-side inscription visibly reads CHARGE. This is an illustration inscription, not an observed energized indicator state.
Manual — Protective covers — procedures, legends and enclosure conditions — page 55
Source reference: SIEP C71060618F, December 2016, physical PDF page 55. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.5 Protective Covers 3.5 Protective Covers Follow the procedure below to remove the protective covers before wiring the drive and to reattach the covers after wiring is complete. u IP20/Open-Chassis Front and Bottom Cover Removal and Installation n Removing the Protective Covers 1. Loosen the screw that locks the front cover in place to remove. Figure 3.6 Remove the Front Cover on an IP20/Open-Chassis Drive 2. Apply pressure to the tabs on each side of the terminal cover. Pull the terminal cover away from the drive while pushing in on the tabs to pull the cover free. Figure 3.7 Remove the Terminal Cover on an IP20/Open-Chassis Drive n Reattaching the Protective Covers Properly connect all wiring and route power wiring away from control signal wiring. Reattach all protective covers when wiring is complete. Apply only a small amount of pressure to lock the cover back into place. Figure 3.8 Reattach the Protective Covers on an IP20/Open-Chassis Drive
Installation Electrical 3
Manual — Protective covers — procedures, legends and enclosure conditions — page 56
Source reference: SIEP C71060618F, December 2016, physical PDF page 56. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.5 Protective Covers u IP20/NEMA Type 1 Front and Bottom Cover Removal and Installation n Removing the Protective Covers on an IP20/NEMA 1, UL Type 1 Design 1. Loosen the screw on the front cover to remove the front cover. Figure 3.9 Remove the Front Cover on an IP20/NEMA 1, UL Type 1 Drive 2. Loosen the screw on the terminal cover to remove the terminal cover and expose the conduit bracket. A B A – Conduit bracket B – Terminal cover Figure 3.10 Remove the Terminal Cover on an IP20/NEMA 1, UL Type 1 Drive 3. Loosen two screws attaching the conduit bracket to remove. A A –Conduit bracket Figure 3.11 Remove the Conduit Bracket on an IP20/NEMA 1, UL Type 1 Drive
Manual — Protective covers — procedures, legends and enclosure conditions — page 57
Source reference: SIEP C71060618F, December 2016, physical PDF page 57. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.5 Protective Covers n Reattaching the Protective Covers Pass power wiring and control signal wiring through the exit holes on the bottom of the conduit bracket of the drive. Place power wiring and control signal wiring in separate conduits. Properly connect all wiring after installing the drive and connecting other devices. Reattach all protective covers when wiring is complete. A A –Pass power wiring and control signal wiring through different exit holes at the bottom of the drive. Figure 3.12 Reattach the Protective Covers and Conduit Bracket on an IP20/NEMA 1, UL Type 1 Drive u IP20/NEMA Type 1 Top Cover Removal and Installation To improve the ambient temperature rating of a NEMA Type 1 drive from 40 °C to 50 °C or to mount NEMA Type 1 drives side-by-side, the top cover can be removed. Remove the top cover and set L8-35 to “2”. Refer to Temperature Derating on page 351 for details. Note: Removing the top cover of a NEMA Type 1 drive converts the drive to an IP20/Open-Chassis rating, and the drive will no longer have a NEMA Type 1 rating. n Removing the Top Cover Insert the blade of a straight-edge screwdriver into the opening of the top cover. Gently lift up on the front cover as indicated by the arrow in Figure 3.13 to remove it from the drive. Figure 3.13 Removing the Top Cover n Reattaching the Top Cover Align the connection tabs on the underside of the top cover with the connection tabs on the drive. Pinch in on the top cover to click the cover into place on the drive. Connection tabs Figure 3.14 Reattaching the Top Cover
Installation Electrical 3
Manual — Main circuit wiring introduction and prohibition on soldered ends — page 58
Source reference: SIEP C71060618F, December 2016, physical PDF page 58. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.6 Main Circuit Wiring 3.6 Main Circuit Wiring This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit of the drive. NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections. u Main Circuit Terminal Functions Table 3.1 Main Circuit Terminal Functions
u Wire Gauges and Tightening Torques Select the appropriate wires and crimp terminals from Table 3.2 through Table 3.4. Note: 1. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient temperature within 30 °C and wiring distance shorter than 100 m. 2. Terminals ⊕1, ⊕2, ⊖, B1 and B2 are for connecting optional devices such as a braking resistor. Do not connect other non-specified devices to these terminals. • Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to calculate the amount of voltage drop: • Line drop voltage (V) = √3 x wire resistance (Ω/km) x wire length (m) x current (A) x 10-3 • Refer to instruction manual TOBP C720600 00 for braking unit or braking resistor unit wire gauges. • Refer to UL Standards Compliance on page 474 for information on UL compliance. n Single-Phase 200 V Class Table 3.2 Wire Gauge and Torque Specifications
R/L1 | Main circuit power supply input
S/L2 | Main circuit power supply input
T/L3 | Main circuit power supply input
U/T1 | Drive output
V/T2 | Drive output
W/T3 | Drive output
B1 | Braking resistor
B2 | Braking resistor
⊕1 | DC link choke connection
⊕2 | DC link choke connection
⊕1 | DC power supply input
⊖ | DC power supply input
[ground symbol] (2 terminals) | Ground
BA0001 BA0002 BA0003 | R/L1, S/L2, T/L3
BA0001 BA0002 BA0003 | U/T1, V/T2, W/T3
BA0001 BA0002 BA0003 | ⊖, ⊕1, ⊕2
BA0001 BA0002 BA0003 | B1, B2
BA0001 BA0002 BA0003 | [ground symbol]
BA0006 | R/L1, S/L2, T/L3
BA0006 | U/T1, V/T2, W/T3
BA0006 | ⊖, ⊕1, ⊕2
BA0006 | B1, B2
BA0006 | [ground symbol]
Table 3.1 Main Circuit Terminal Functions — PDF page 58
| Source row | Terminal | Type | Function | Reference |
|---|---|---|---|---|
| 1 | R/L1 | Main circuit power supply input | Connects line power to the drive. Drives with single-phase 200 V input power use terminals R/L1 and S/L2 only. Do NOT use T/L3. | 53 |
| 2 | S/L2 | Main circuit power supply input | Connects line power to the drive. Drives with single-phase 200 V input power use terminals R/L1 and S/L2 only. Do NOT use T/L3. | 53 |
| 3 | T/L3 | Main circuit power supply input | Connects line power to the drive. Drives with single-phase 200 V input power use terminals R/L1 and S/L2 only. Do NOT use T/L3. | 53 |
| 4 | U/T1 | Drive output | Connects to the motor. | 61 |
| 5 | V/T2 | Drive output | Connects to the motor. | 61 |
| 6 | W/T3 | Drive output | Connects to the motor. | 61 |
| 7 | B1 | Braking resistor | Available for connecting a braking resistor or the braking resistor unit option. | 72 |
| 8 | B2 | Braking resistor | Available for connecting a braking resistor or the braking resistor unit option. | 72 |
| 9 | ⊕1 | DC link choke connection | These terminals are shorted at shipment. Remove the shorting bar between ⊕1 and ⊕2 when connecting a DC link choke to this terminal. | 331 |
| 10 | ⊕2 | DC link choke connection | These terminals are shorted at shipment. Remove the shorting bar between ⊕1 and ⊕2 when connecting a DC link choke to this terminal. | 331 |
| 11 | ⊕1 | DC power supply input | For connecting a DC power supply. | – |
| 12 | ⊖ | DC power supply input | For connecting a DC power supply. | – |
| 13 | [ground symbol] (2 terminals) | Ground | Grounding Terminal | 62 |
Table 3.2 Single-Phase 200 V Class — PDF page 58
| Source row | Drive model | Terminal | Recommended gauge (AWG, kcmil) | Wire range (AWG, kcmil) | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | BA0001 BA0002 BA0003 | R/L1, S/L2, T/L3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 2 | BA0001 BA0002 BA0003 | U/T1, V/T2, W/T3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 3 | BA0001 BA0002 BA0003 | ⊖, ⊕1, ⊕2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 4 | BA0001 BA0002 BA0003 | B1, B2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 5 | BA0001 BA0002 BA0003 | [ground symbol] | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 6 | BA0006 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 7 | BA0006 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 8 | BA0006 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 9 | BA0006 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 10 | BA0006 | [ground symbol] | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
Manual — Main circuit wiring continued — header — page 59
Source reference: SIEP C71060618F, December 2016, physical PDF page 59. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.6 Main Circuit Wiring
n Three-Phase 200 V Class Table 3.3 Wire Gauge and Torque Specifications
Installation Electrical 3
BA0010 | R/L1, S/L2, T/L3
BA0010 | U/T1, V/T2, W/T3
BA0010 | ⊖, ⊕1, ⊕2
BA0010 | B1, B2
BA0010 | [ground symbol]
BA0012 | R/L1, S/L2, T/L3
BA0012 | U/T1, V/T2, W/T3
BA0012 | ⊖, ⊕1, ⊕2
BA0012 | B1, B2
BA0012 | [ground symbol]
BA0018 | R/L1, S/L2, T/L3
BA0018 | U/T1, V/T2, W/T3
BA0018 | ⊖, ⊕1, ⊕2
BA0018 | B1, B2
BA0018 | [ground symbol]
2A0001 2A0002 2A0004 2A0006 | R/L1, S/L2, T/L3
2A0001 2A0002 2A0004 2A0006 | U/T1, V/T2, W/T3
2A0001 2A0002 2A0004 2A0006 | ⊖, ⊕1, ⊕2
2A0001 2A0002 2A0004 2A0006 | B1, B2
2A0001 2A0002 2A0004 2A0006 | [ground symbol]
2A0010 | R/L1, S/L2, T/L3
2A0010 | U/T1, V/T2, W/T3
2A0010 | ⊖, ⊕1, ⊕2
2A0010 | B1, B2
2A0010 | [ground symbol]
2A0012 | R/L1, S/L2, T/L3
2A0012 | U/T1, V/T2, W/T3
2A0012 | ⊖, ⊕1, ⊕2
2A0012 | B1, B2
2A0012 | [ground symbol]
2A0020 | R/L1, S/L2, T/L3
2A0020 | U/T1, V/T2, W/T3
2A0020 | ⊖, ⊕1, ⊕2
2A0020 | B1, B2
2A0020 | [ground symbol]
2A0030 | R/L1, S/L2, T/L3
2A0030 | U/T1, V/T2, W/T3
2A0030 | ⊖, ⊕1, ⊕2
2A0030 | B1, B2
2A0030 | [ground symbol]
Table 3.2 Single-Phase 200 V Class continued — PDF page 59
| Source row | Drive model | Terminal | Recommended gauge (AWG, kcmil) | Wire range (AWG, kcmil) | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | BA0010 | R/L1, S/L2, T/L3 | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 2 | BA0010 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 3 | BA0010 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 4 | BA0010 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 5 | BA0010 | [ground symbol] | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 6 | BA0012 | R/L1, S/L2, T/L3 | 10 | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 7 | BA0012 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 8 | BA0012 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 9 | BA0012 | B1, B2 | – | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 10 | BA0012 | [ground symbol] | 10 | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 11 | BA0018 | R/L1, S/L2, T/L3 | 8 | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 12 | BA0018 | U/T1, V/T2, W/T3 | 10 | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 13 | BA0018 | ⊖, ⊕1, ⊕2 | – | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 14 | BA0018 | B1, B2 | – | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 15 | BA0018 | [ground symbol] | 8 | 12 to 8 | M5 | 2 to 2.5 (17.7 to 22.1) |
Table 3.3 Three-Phase 200 V Class — PDF page 59
| Source row | Drive model | Terminal | Recommended gauge (AWG, kcmil) | Wire range (AWG, kcmil) | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 2A0001 2A0002 2A0004 2A0006 | R/L1, S/L2, T/L3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 2 | 2A0001 2A0002 2A0004 2A0006 | U/T1, V/T2, W/T3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 3 | 2A0001 2A0002 2A0004 2A0006 | ⊖, ⊕1, ⊕2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 4 | 2A0001 2A0002 2A0004 2A0006 | B1, B2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 5 | 2A0001 2A0002 2A0004 2A0006 | [ground symbol] | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 6 | 2A0010 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 7 | 2A0010 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 8 | 2A0010 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 9 | 2A0010 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 10 | 2A0010 | [ground symbol] | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 11 | 2A0012 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 12 | 2A0012 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 13 | 2A0012 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 14 | 2A0012 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 15 | 2A0012 | [ground symbol] | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 16 | 2A0020 | R/L1, S/L2, T/L3 | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 17 | 2A0020 | U/T1, V/T2, W/T3 | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 18 | 2A0020 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 19 | 2A0020 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 20 | 2A0020 | [ground symbol] | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 21 | 2A0030 | R/L1, S/L2, T/L3 | 8 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 22 | 2A0030 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 23 | 2A0030 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 24 | 2A0030 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 25 | 2A0030 | [ground symbol] | 8 | 10 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
Manual — Main circuit wiring continued — header — page 60
Source reference: SIEP C71060618F, December 2016, physical PDF page 60. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.6 Main Circuit Wiring
n Three-Phase 400 V Class Table 3.4 Wire Gauge and Torque Specifications
2A0040 | R/L1, S/L2, T/L3
2A0040 | U/T1, V/T2, W/T3
2A0040 | ⊖, ⊕1, ⊕2
2A0040 | B1, B2
2A0040 | [ground symbol]
2A0056 | R/L1, S/L2, T/L3
2A0056 | U/T1, V/T2, W/T3
2A0056 | ⊖, ⊕1, ⊕2
2A0056 | B1, B2
2A0056 | [ground symbol]
2A0069 | R/L1, S/L2, T/L3
2A0069 | U/T1, V/T2, W/T3
2A0069 | ⊖, ⊕1, ⊕2
2A0069 | B1, B2
2A0069 | [ground symbol]
4A0001 4A0002 4A0004 | R/L1, S/L2, T/L3
4A0001 4A0002 4A0004 | U/T1, V/T2, W/T3
4A0001 4A0002 4A0004 | ⊖, ⊕1, ⊕2
4A0001 4A0002 4A0004 | B1, B2
4A0001 4A0002 4A0004 | [ground symbol]
4A0005 4A0007 4A0009 | R/L1, S/L2, T/L3
4A0005 4A0007 4A0009 | U/T1, V/T2, W/T3
4A0005 4A0007 4A0009 | ⊖, ⊕1, ⊕2
4A0005 4A0007 4A0009 | B1, B2
4A0005 4A0007 4A0009 | [ground symbol]
4A0011 | R/L1, S/L2, T/L3
4A0011 | U/T1, V/T2, W/T3
4A0011 | ⊖, ⊕1, ⊕2
4A0011 | B1, B2
4A0011 | [ground symbol]
4A0018 | R/L1, S/L2, T/L3
4A0018 | U/T1, V/T2, W/T3
4A0018 | ⊖, ⊕1, ⊕2
4A0018 | B1, B2
4A0018 | [ground symbol]
Table 3.3 Three-Phase 200 V Class continued — PDF page 60
| Source row | Drive model | Terminal | Recommended gauge (AWG, kcmil) | Wire range (AWG, kcmil) | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 2A0040 | R/L1, S/L2, T/L3 | 6 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 2 | 2A0040 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 3 | 2A0040 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 4 | 2A0040 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 5 | 2A0040 | [ground symbol] | 6 | 10 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
| 6 | 2A0056 | R/L1, S/L2, T/L3 | 4 | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 7 | 2A0056 | U/T1, V/T2, W/T3 | 4 | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 8 | 2A0056 | ⊖, ⊕1, ⊕2 | – | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 9 | 2A0056 | B1, B2 | – | 10 to 6 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 10 | 2A0056 | [ground symbol] | 6 | 8 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 11 | 2A0069 | R/L1, S/L2, T/L3 | 3 | 8 to 2 | M8 | 9.9 to 11 (87.6 to 97.4) |
| 12 | 2A0069 | U/T1, V/T2, W/T3 | 3 | 8 to 2 | M8 | 9.9 to 11 (87.6 to 97.4) |
| 13 | 2A0069 | ⊖, ⊕1, ⊕2 | – | 8 to 2 | M8 | 9.9 to 11 (87.6 to 97.4) |
| 14 | 2A0069 | B1, B2 | – | 8 to 6 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 15 | 2A0069 | [ground symbol] | 6 | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
Table 3.4 Three-Phase 400 V Class — PDF page 60
| Source row | Drive model | Terminal | Recommended gauge (AWG, kcmil) | Wire range (AWG, kcmil) | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 4A0001 4A0002 4A0004 | R/L1, S/L2, T/L3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 2 | 4A0001 4A0002 4A0004 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 3 | 4A0001 4A0002 4A0004 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 4 | 4A0001 4A0002 4A0004 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 5 | 4A0001 4A0002 4A0004 | [ground symbol] | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 6 | 4A0005 4A0007 4A0009 | R/L1, S/L2, T/L3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 7 | 4A0005 4A0007 4A0009 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 8 | 4A0005 4A0007 4A0009 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 9 | 4A0005 4A0007 4A0009 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 10 | 4A0005 4A0007 4A0009 | [ground symbol] | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 11 | 4A0011 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 12 | 4A0011 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 13 | 4A0011 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 14 | 4A0011 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 15 | 4A0011 | [ground symbol] | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 16 | 4A0018 | R/L1, S/L2, T/L3 | 10 | 14 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 17 | 4A0018 | U/T1, V/T2, W/T3 | 10 | 14 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 18 | 4A0018 | ⊖, ⊕1, ⊕2 | – | 14 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 19 | 4A0018 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 20 | 4A0018 | [ground symbol] | 8 | 14 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
Manual — Main circuit wiring continued — header — page 61
Source reference: SIEP C71060618F, December 2016, physical PDF page 61. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.6 Main Circuit Wiring
u Main Circuit Terminal Power Supply and Motor Wiring This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals. NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward. NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to comply may result in abnormal operation of drive and nearby equipment. NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper application of noise filters could result in damage to the drive. NOTICE: Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could result in death or serious injury by fire as a result of drive damage from line voltage application to output terminals. n Cable Length Between Drive and Motor When the cable length between the drive and the motor is too long (especially at low frequency output), note that the cable voltage drop may cause reduced motor torque. Drive output current will increase as the leakage current from the cable increases. An increase in leakage current may trigger an overcurrent situation and weaken the accuracy of the current detection. Adjust the drive carrier frequency according to the following table. If the motor wiring distance exceeds 100 m because of the system configuration, reduce the ground currents. Refer to C6-02: Carrier Frequency Selection on page 156 Refer to Table 3.5 to set the carrier frequency to an appropriate level. Table 3.5 Cable Length Between Drive and Motor
Note: When setting carrier frequency, calculate the cable length as the total distance of wiring to all connected motors when running multiple motors from a single drive.
Installation Electrical 3
4A0023 | R/L1, S/L2, T/L3
4A0023 | U/T1, V/T2, W/T3
4A0023 | ⊖, ⊕1, ⊕2
4A0023 | B1, B2
4A0023 | [ground symbol]
4A0031 | R/L1, S/L2, T/L3
4A0031 | U/T1, V/T2, W/T3
4A0031 | ⊖, ⊕1, ⊕2
4A0031 | B1, B2
4A0031 | [ground symbol]
4A0038 | R/L1, S/L2, T/L3
4A0038 | U/T1, V/T2, W/T3
4A0038 | ⊖, ⊕1, ⊕2
4A0038 | B1, B2
4A0038 | [ground symbol]
Carrier Frequency | 15 kHz or less
Table 3.4 Three-Phase 400 V Class continued — PDF page 61
| Source row | Drive model | Terminal | Recommended gauge (AWG, kcmil) | Wire range (AWG, kcmil) | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 4A0023 | R/L1, S/L2, T/L3 | 10 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 2 | 4A0023 | U/T1, V/T2, W/T3 | 10 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 3 | 4A0023 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 4 | 4A0023 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 5 | 4A0023 | [ground symbol] | 8 | 10 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
| 6 | 4A0031 | R/L1, S/L2, T/L3 | 8 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 7 | 4A0031 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 8 | 4A0031 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 9 | 4A0031 | B1, B2 | – | 14 to 10 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 10 | 4A0031 | [ground symbol] | 6 | 10 to 6 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 11 | 4A0038 | R/L1, S/L2, T/L3 | 6 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 12 | 4A0038 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 13 | 4A0038 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 14 | 4A0038 | B1, B2 | – | 10 to 8 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 15 | 4A0038 | [ground symbol] | 6 | 10 to 6 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
Table 3.5 Cable Length Between Drive and Motor — PDF page 61
| Source row | Cable length | 50 m or less | 100 m or less | Greater than 100 m |
|---|---|---|---|---|
| 1 | Carrier Frequency | 15 kHz or less | 5 kHz or less | 2 kHz or less |
Manual — Ground wiring precautions and class-specific resistance — page 62
Source reference: SIEP C71060618F, December 2016, physical PDF page 62. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.6 Main Circuit Wiring n Ground Wiring Follow the precautions to wire the ground for one drive or a series of drives. WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could result in death or serious injury. WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal. (200 V Class: Ground to 100 Ω or less, 400 V Class: Ground to 10 Ω or less). Improper equipment grounding could result in death or serious injury by contacting ungrounded electrical equipment. NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper equipment grounding could result in drive or equipment malfunction due to electrical interference. NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in abnormal operation of drive or equipment. Refer to Figure 3.15 when using multiple drives. Do not loop the ground wire.
Figure 3.15 Multiple Drive Wiring. A – Correct; B – Incorrect. Two source arrangements marked A, one B. Do not loop ground wire. Original diagram retains routing topology; text label inventory does not specify a substitute wiring arrangement.
n Wiring the Main Circuit Terminal WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit terminals. Failure to comply may result in death or serious injury. Note: A cover placed over the DC Bus and braking circuit terminals prior to shipment helps prevent miswiring. Cut away covers as needed for terminals with a needle-nose pliers.
A – Protective Cover to Prevent Miswiring. Diagram shows cover placement only; terminal details remain original-only.
Note: The ground terminal screw on IP20/NEMA Type 1 holds the protective cover in place. Main Circuit Connection Diagram Refer to section 3.3 Main Circuit Connection Diagram on page 53 for drive main power circuit connections. WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect braking resistors to any other terminals. Improper wiring connections could cause the braking resistor to overheat and cause death or serious injury by fire. Failure to comply may result in damage to the braking circuit or drive.
Manual — Control circuit wiring and no-solder warning — page 63
Source reference: SIEP C71060618F, December 2016, physical PDF page 63. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.7 Control Circuit Wiring 3.7 Control Circuit Wiring NOTICE: Do not solder the ends of wire connections to the drive. Soldered wire connections can loosen over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
Figure 3.16 Control Circuit Connection Diagram. V1000 Control circuit; default digital inputs S1 Forward run/stop; S2 Reverse run/stop; S3 External fault; S4 Fault reset; S5 Multi-step speed 1 main/aux switch; S6 Multi-step speed 2; S7 Jog reference; SC. +24 V 8 mA, 24 V, 0 V; DIP switch S3 Sink/Source; shield ground terminal. Option card connector; DIP switch S1 V/I. Fault relay MA, MB, MC; digital output 250 Vac 10 mA to 1 A / 30 Vdc 10 mA to 1 A default. Photocoupler digital output 5 to 48 Vdc, 2 to 50 mA default; P1 During Run (photocoupler 1); P2 Frequency agree (photocoupler 2); PC common. Main speed frequency reference multi-function programmable; 2 kΩ; RP pulse train input max. 32 kHz; +V setting power supply +10.5 max. 20 mA; A1 0 to +10 V (20 kΩ); A2 0 to +10 V (20 kΩ), (0)4 to 20 mA (250 Ω); AC. MP pulse train output 0 to 32 kHz; AM analog monitor output 0 to +10 Vdc (2 mA); AC. Safe Disable Input, Safety switch, Jumper, HC, H1. DIP switch S2, termination resistor 120 Ω, 1/2 W; communications connector; R+, R-, S+, S-, IG, cable shield ground; MEMOBUS/Modbus RS-485/422. Legend shielded line, twisted-pair shielded line, main circuit terminal, control terminal. Original wiring geometry and footnotes remain required.
<1> Connected using sequence input signal (S1 to S7) from NPN transistor; Default: sink mode (0 V com) <2> Use only the +24 V internal power supply in sinking mode; the source mode requires an external power supply. Refer to I/O Connections on page 68.
Installation Electrical 3
Manual — Control terminal function selection and test-run warnings — page 64
Source reference: SIEP C71060618F, December 2016, physical PDF page 64. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.7 Control Circuit Wiring u Control Circuit Terminal Block Functions Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S7), multi-function digital outputs (MA, MB), multi-function pulse inputs and outputs (RP, MP) and multi-function photocoupler outputs (P1, P2). The default is called out next to each terminal in Figure 3.. WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive with untested control circuits could result in death or serious injury. WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter A1-06 may change the I/O terminal function automatically from the factory setting. Refer to Application Selection on page 96. Failure to comply may result in death or serious injury. n Input Terminals Table 3.6 Control Circuit Input Terminals
n Output Terminals Table 3.7 Control Circuit Output Terminals
<1> Do not assign functions to digital relay outputs that involve frequent switching. This may shorten relay performance life. Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
Multi-Function Digital Inputs | S1
Multi-Function Digital Inputs | S2
Multi-Function Digital Inputs | S3
Multi-Function Digital Inputs | S4
Multi-Function Digital Inputs | S5
Multi-Function Digital Inputs | S6
Multi-Function Digital Inputs | S7
Multi-Function Digital Inputs | SC
Safe Disable Input | HC
Safe Disable Input | H1
Main Frequency Reference Input | RP
Main Frequency Reference Input | +V
Main Frequency Reference Input | A1
Main Frequency Reference Input | A2
Main Frequency Reference Input | AC
Multi-Function Digital Output <1> | MA
Multi-Function Digital Output <1> | MB
Multi-Function Digital Output <1> | MC
Multi-Function Photocoupler Output | P1
Multi-Function Photocoupler Output | P2
Multi-Function Photocoupler Output | PC
Monitor Output | MP
Monitor Output | AM
Monitor Output | AC
Table 3.6 Control Circuit Input Terminals — PDF page 64
| Source row | Type | No. | Terminal Name (Function) | Function (Signal Level) Default Setting |
|---|---|---|---|---|
| 1 | Multi-Function Digital Inputs | S1 | Multi-function input 1 (Closed: Forward run, Open: Stop) | Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 2 | Multi-Function Digital Inputs | S2 | Multi-function input 2 (Closed: Reverse run, Open: Stop) | Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 3 | Multi-Function Digital Inputs | S3 | Multi-function input 3 (External fault (N.O.) | Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 4 | Multi-Function Digital Inputs | S4 | Multi-function input 4 (Fault reset) | Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 5 | Multi-Function Digital Inputs | S5 | Multi-function input 5 (Multi-step speed reference 1) | Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 6 | Multi-Function Digital Inputs | S6 | Multi-function input 6 (Multi-step speed reference 2) | Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 7 | Multi-Function Digital Inputs | S7 | Multi-function input 7 (Jog reference) | Photocoupler 24 Vdc, 8 mA Note: Drive preset to sinking mode. When using source mode, set DIP switch S3 to allow for a 24 Vdc (±10%) external power supply. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 8 | Multi-Function Digital Inputs | SC | Multi-function input common (Control common) | Sequence common |
| 9 | Safe Disable Input | HC | Power supply for safe disable input | +24 Vdc (max 10 mA allowed) Do not use external power supply. |
| 10 | Safe Disable Input | H1 | Safe disable input | Open: Output disabled Closed: Normal operation Note: Disconnect wire jumper between HC and H1 when using the safe disable input. The wire length should not exceed 30 m. Use only dry contacts on safety inputs HC-H1. |
| 11 | Main Frequency Reference Input | RP | Multi-function pulse train input (frequency reference) | Response frequency: 0.5 to 32 kHz (Duty Cycle: 30 to 70%) (High level voltage: 3.5 to 13.2 Vdc) (Low level voltage: 0.0 to 0.8 Vdc) (input impedance: 3 kΩ) |
| 12 | Main Frequency Reference Input | +V | Analog input power supply | +10.5 Vdc (max allowable current 20 mA) |
| 13 | Main Frequency Reference Input | A1 | Multi-function analog input 1 (frequency reference) | Input voltage 0 to +10 Vdc (20 kΩ) resolution 1/1000 |
| 14 | Main Frequency Reference Input | A2 | Multi-function analog input 2 (frequency reference) | Input voltage or input current (Selected by DIP switch S1 and H3-09) 0 to +10 Vdc (20 kΩ), Resolution: 1/1000 4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω), Resolution: 1/500 |
| 15 | Main Frequency Reference Input | AC | Frequency reference common | 0 Vdc |
Table 3.7 Control Circuit Output Terminals — PDF page 64
| Source row | Type | No. | Terminal Name (Function) | Function (Signal Level) Default Setting |
|---|---|---|---|---|
| 1 | Multi-Function Digital Output <1> | MA | N.O. (fault) | Digital output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA (reference value) |
| 2 | Multi-Function Digital Output <1> | MB | N.C. output (fault) | Digital output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA (reference value) |
| 3 | Multi-Function Digital Output <1> | MC | Digital output common | Digital output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA (reference value) |
| 4 | Multi-Function Photocoupler Output | P1 | Photocoupler output 1 (During run) | Photocoupler output 48 Vdc, 2 to 50 mA <2> |
| 5 | Multi-Function Photocoupler Output | P2 | Photocoupler output 2 (Frequency agree) | Photocoupler output 48 Vdc, 2 to 50 mA <2> |
| 6 | Multi-Function Photocoupler Output | PC | Photocoupler output common | Photocoupler output 48 Vdc, 2 to 50 mA <2> |
| 7 | Monitor Output | MP | Pulse train output (Output frequency) | 32 kHz (max) <3> <4> |
| 8 | Monitor Output | AM | Analog monitor output | 0 to 10 Vdc (2 mA or less) Resolution: 1/1000 |
| 9 | Monitor Output | AC | Monitor common | 0 V |
Manual — Table 3.7 continued footnotes 2–4 — page 65
Source reference: SIEP C71060618F, December 2016, physical PDF page 65. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.7 Control Circuit Wiring <2> Connect a suppression diode as shown in Figure 3.17 when driving a reactive load such as a relay coil. Ensure the diode rating is greater than the circuit voltage. <3> When set for sourcing. +5 V/1.5 kΩ or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher. <4> When set for sinking, the external power supply should be +12 Vdc, ±5% with 16 mA or less.
Figure 3.17 Connecting a Suppression Diode: A – External power, 48 V max.; B – Suppression diode; C – Coil; D – 50 mA or less. Original diode orientation/connection geometry retained; footnote 2 requires diode rating greater than circuit voltage.
n Serial Communication Terminals Table 3.8 Control Circuit Terminals: Serial Communications
u Terminal Configuration
Figure 3.18 Removable Control Circuit Terminal Block. Enlarged terminal label rows: R+, R-, S+, S-, IG; P1, P2, PC, A1, A2, +V, AC, AM, AC, MP; S1, S2, S3, S4, S5, S6, S7, HC, SC, H1, RP; separate MA, MB, MC. Jumper pictured HC–H1. Geometry original-only; safety-input instructions remain required.
Installation Electrical 3
MEMOBUS/Modbus Communication | R+
MEMOBUS/Modbus Communication | R-
MEMOBUS/Modbus Communication | S+
MEMOBUS/Modbus Communication | S-
MEMOBUS/Modbus Communication | IG
Table 3.8 Control Circuit Terminals: Serial Communications — PDF page 65
| Source row | Type | No. | Signal Name | Function (Signal Level) — connection | Function (Signal Level) — protocol |
|---|---|---|---|---|---|
| 1 | MEMOBUS/Modbus Communication | R+ | Communications input (+) | MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. | RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.) |
| 2 | MEMOBUS/Modbus Communication | R- | Communications input (-) | MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. | RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.) |
| 3 | MEMOBUS/Modbus Communication | S+ | Communications output (+) | MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. | RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.) |
| 4 | MEMOBUS/Modbus Communication | S- | Communications output (-) | MEMOBUS/Modbus communication: Use a RS-485 or RS-422 cable to connect the drive. | RS-485/422 MEMOBUS/ Modbus communication protocol 115.2 kbps (max.) |
| 5 | MEMOBUS/Modbus Communication | IG | Shield ground | 0 V | 0 V |
Manual — Wire size and torque context — page 66
Source reference: SIEP C71060618F, December 2016, physical PDF page 66. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.7 Control Circuit Wiring n Wire Size and Torque Specifications Select appropriate wire type and size from Table 3.9. For simpler and more reliable wiring, crimp ferrules to the wire ends. Refer to Table 3.10 for ferrule terminal types and sizes. Table 3.9 Wire Size and Torque Specifications (Same for All Models)
n Ferrule-Type Wire Terminations Crimp a ferrule to signal wiring to improve wiring simplicity and reliability. Use CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT.
Figure 3.19 Ferrule Dimensions. Labels d1, d2, L, and 6 mm. Dimension-arrow geometry remains original-only; numerical model dimensions are in Table 3.10.
Figure 3.19 Ferrule Dimensions Table 3.10 Ferrule Terminal Types and Sizes
u Wiring Procedure This section describes the proper procedures and preparations for wiring the control terminals. WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result in death or serious injury. NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference. NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit lines. Improper wiring practices could result in drive or equipment malfunction or nuisance trips. NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation due to improper power supply. NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could result in drive or equipment malfunction due to short circuit. NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or equipment malfunction or nuisance trips. Wire the control terminals using Figure 3.20 as a guide. Prepare the ends of the control circuit wiring as shown in Figure 3.21. Refer to Wire Size and Torque Specifications on page 66.
Table 3.9 Wire Size and Torque Specifications (Same for All Models) — PDF page 66
| Source row | Terminal | Screw Size | Tightening Torque N·m (in-lbs) | Bare wire applicable size mm² (AWG) | Bare wire recommended mm² (AWG) | Ferrule applicable size mm² (AWG) | Ferrule recommended mm² (AWG) | Wire Type |
|---|---|---|---|---|---|---|---|---|
| 1 | MA, MB, MC | M3 | 0.5 to 0.6 (4.4 to 5.3) | Stranded: 0.25 to 1.5 (24 to 16) Single: 0.25 to 1.5 (24 to 16) | 0.75 (18) | 0.25 to 1.0 (24 to 17) | 0.5 (20) | Shielded line, etc. |
| 2 | S1-S7, SC, RP, +V, A1, A2, AC, HC, H1, P1, P2, PC, MP, AM, AC, S+, S-, R+, R-, IG | M2 | 0.22 to 0.25 (1.9 to 2.2) | Stranded: 0.25 to 1.0 (24 to 18) Single: 0.25 to 1.5 (24 to 16) | 0.75 (18) | 0.25 to 0.5 (24 to 20) | 0.5 (20) | Shielded line, etc. |
Table 3.10 Ferrule Terminal Types and Sizes — PDF page 66
| Source row | Size mm² (AWG) | Type | L (mm) | d1 (mm) | d2 (mm) | Manufacturer |
|---|---|---|---|---|---|---|
| 1 | 0.25 (24) | AI 0.25-6YE | 10.5 | 0.8 | 2.0 | PHOENIX CONTACT |
| 2 | 0.34 (22) | AI 0.34-6TQ | 10.5 | 0.8 | 2.0 | PHOENIX CONTACT |
| 3 | 0.5 (20) | AI 0.5-6WH | 12 | 1.1 | 2.5 | PHOENIX CONTACT |
| 4 | 0.75 (18) | AI 0.75-6GY | 12 | 1.3 | 2.8 | PHOENIX CONTACT |
| 5 | 1.0 | AI 1-6RD | 12 | 1.5 | 3.0 | PHOENIX CONTACT |
Manual — Control terminal torque and twisted-pair notices — page 67
Source reference: SIEP C71060618F, December 2016, physical PDF page 67. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.7 Control Circuit Wiring NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the terminal block. NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or equipment malfunction due to electrical interference. Connect control wires as shown in the following figure:
Figure 3.20 diagram: A, B, C, D, E; Preparing wire terminal ends. Read source legend below; geometry original-only.
A – Control terminal block B – Avoid fraying wire strands when stripping insulation from wire. Strip length 5.5 mm. C – Single wire or stranded wire
D – Loosen screw to insert wire. E – Blade depth of 0.4 mm or less Blade width of 2.5 mm or less
Figure 3.20 Terminal Board Wiring Guide
Figure 3.21 diagram letter references A, B, C, D, E, F; original cable geometry remains authoritative.
A – Drive side B – Connect shield to ground terminal of drive. C – Insulation
D – Control device side E – Shield sheath (Insulate with tape) F – Shield
Figure 3.21 Preparing the Ends of Shielded Cables When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires and ground the shield of twisted-pair wires to the ground terminal of the drive. NOTICE: The analog signal lines between the drive and the operator station or peripheral equipment should not exceed 50 meters when using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.
Figure 3.22 diagram: A, B, C, D, E, F, G; RP, +V, A1, A2, AC; 2 kΩ potentiometer; ground symbol. Read separate legends below; topology remains original-only.
A – Drive B – Ground terminal (shield connection) C – (RP) Pulse train (maximum 32 kHz) D – (+V) Frequency setting power source +10.5 Vdc maximum 20 mA
E – (A1) Main speed frequency reference 0 to +10 Vdc (20 kΩ) F – (A2) Multi-function analog input 0 to +10 Vdc (20 kΩ) or 4 to 20 mA (250 Ω)/ 0 to 20 mA (250 Ω) G – Frequency setting potentiometer
Figure 3.22 Wiring the Frequency Reference to the Control Circuit Terminals (External Reference)
Installation Electrical 3
Manual — Sinking/sourcing mode switch context — page 68
Source reference: SIEP C71060618F, December 2016, physical PDF page 68. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.8 I/O Connections 3.8 I/O Connections u Sinking/Sourcing Mode Switch Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between sinking mode and sourcing mode; the drive is preset to sinking mode. Table 3.11 Sinking/Sourcing Mode Setting
Figure 3.23 DIP switch S3, SINK and SOURCE. Original diagram identifies switch location; tiny repeated keypad face is not a live setting.
n Transistor Input Signal Using 0 V Common/Sink Mode When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the DIP switch S3 to SINK and use the internal 24 V power supply.
Figure 3.24 Sinking Mode: Sequence from NPN Transistor (0 V Common). Drive, shielded cable, multi-function input: S1 Forward run/stop; S2 Reverse run/stop; S3 External fault N.O.; S4 Fault reset; S5 Multi-speed step 1; S6 Multi-speed step 2; S7 Jog reference; SC. DIP switch S3 SINK/SOURCE, +24V. Original wiring diagram remains authoritative.
Table 3.11 Sinking/Sourcing Mode Setting — PDF page 68
| Source row | Set Value | Details |
|---|---|---|
| 1 | SINK | Sinking Mode (0 V common): default setting |
| 2 | SOURCE | Sourcing Mode (+24 V common) |
Manual — PNP transistor sourcing procedure — page 69
Source reference: SIEP C71060618F, December 2016, physical PDF page 69. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.8 I/O Connections n Transistor Input Signal Using +24 V Common/Source Mode When controlling digital inputs by PNP transistors (+24 V common/sourcing mode), set the DIP switch S3 to SOURCE and use an external 24 V power supply.
Figure 3.25 Source Mode: Sequence from PNP Transistor (+24 V Common). External power supply +24 V; shielded cable; drive; multi-function input labels S1 Forward run / stop; S2 Reverse run / stop; S3 External fault N.O.; S4 Fault rest [literal source spelling]; S5 Multi-step speed 1; S6 Multi-step speed 2; S7 Jog frequency; SC; DIP S3 SINK/SOURCE, +24V. Original wiring diagram remains authoritative.
Installation Electrical 3
Manual — Analog frequency-reference selection, H3-09 and H3-10 conditions — page 70
Source reference: SIEP C71060618F, December 2016, physical PDF page 70. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.9 Main Frequency Reference 3.9 Main Frequency Reference u DIP Switch S1 Analog Input Signal Selection The main frequency reference can either be a voltage or current signal input. For voltage signals both analog inputs, A1 and A2, can be used, for current signals A2 must be used. When using input A2 as a voltage input, set DIP switch S1 to “V” (left position) and program parameter H3-09 to “0” (0 to +10 Vdc with lower limit) or “1” (0 to +10 Vdc without lower limit). To use current input at terminal A2, set the DIP switch S1 to "I" (default setting) and set parameter H3-09 = “2” or “3” (4-20 mA or 0-20 mA). Set parameter H3-10 = “0” (frequency reference). Note: If Terminals A1 and A2 are both set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both input values builds the frequency reference. Table 3.12 Frequency Reference Configurations
Table 3.12 Frequency Reference Configurations consists of two diagrams. Voltage Input labels: Drive, 2 kΩ, 0 to 10 V, +V +10.5 V 20 mA current, A1 main speed frequency reference (voltage input), A2 main speed frequency reference (current input), AC frequency reference common. Current Input labels: Drive; +V +10.5 V 20 mA current; A1 main speed frequency reference (voltage input); A2 main speed frequency reference (current input); 4 to 20 mA input or 0 to 20 mA input; AC frequency reference common. Current signal uses A2 according to explicit source prose; do not map current text to A1 merely because labels are nearby. Original wiring geometry required.
Figure 3.26 DIP Switch S1 with V and I labels. Left/right electrical settings are specified by Table 3.13; original picture locates the switch.
Table 3.13 DIP Switch S1 Settings
Table 3.14 Parameter H3-09 Details
Literal visible table column boundaries; native detector split description prefix into name column. Actual rule corrected before freezing first reading. Source setting 1 says 0 to +10 V, bipolar input (no lower limit); preserve literal wording.
Table 3.13 DIP Switch S1 Settings — PDF page 70
| Source row | Setting Value | Description |
|---|---|---|
| 1 | V (left position) | Voltage input (0 to 10 V) |
| 2 | I (right position) | Current input (4 to 20 mA or 0 to 20 mA): default setting |
Table 3.14 Parameter H3-09 Details — PDF page 70
| Source row | No. | Parameter Name | Description | Setting Range | Default Setting |
|---|---|---|---|---|---|
| 1 | H3-09 | Frequency ref. (current) terminal A2 signal level selection | Selects the signal level for terminal A2. 0: 0 to +10 V, unipolar input (with lower limit) 1: 0 to +10 V, bipolar input (no lower limit) 2: 4 to 20 mA 3: 0 to 20 mA | 0 to 3 | 2 |
Manual — Network termination requirements — page 71
Source reference: SIEP C71060618F, December 2016, physical PDF page 71. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.10 MEMOBUS/Modbus Termination 3.10 MEMOBUS/Modbus Termination The two ends of the MEMOBUS/Modbus network line must be terminated. The drive has a built-in termination resistor that can be enabled or disabled using DIP switch S2. If a drive is a single drive on the network or is located at the end of a network line, set DIP switch S2 to the ON position to enable the termination resistor. Disable the termination resistor on all slave drives that are not located at the network line end. Table 3.15 MEMOBUS/Modbus Switch Settings
Figure 3.27 DIP Switch S2; OFF, ON. Original picture identifies switch position; Table 3.15 gives settings.
Note: Refer to the MEMOBUS/Modbus communications manual for details on MEMOBUS/Modbus.
Installation Electrical 3
Table 3.15 MEMOBUS/Modbus Switch Settings — PDF page 71
| Source row | S2 Position | Description |
|---|---|---|
| 1 | ON | Internal termination resistor ON |
| 2 | OFF | Internal termination resistor OFF (no termination resistor); default setting |
Manual — Braking resistor sizing, thermal protection, installation steps 1–3 — page 72
Source reference: SIEP C71060618F, December 2016, physical PDF page 72. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.11 Braking Resistor 3.11 Braking Resistor Dynamic braking (DB) helps bring the motor to a smooth and rapid stop when working with high inertia loads. Regeneration occurs as the drive lowers the motor frequency with high inertia. When the regeneration flows back into the DC bus capacitors, an overvoltage situation occurs. A braking resistor prevents these overvoltage faults. NOTICE: Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review the braking resistor instruction manual when connecting a braking option to the drive. Note: The braking circuit must be sized properly in order to dissipate the power required to decelerate the load in the desired time. Ensure that the braking circuit can dissipate the energy for the set deceleration time prior to running the drive. NOTICE: Use a thermal overload relay or over-temperature contact to interrupt input power to the drive if the braking resistor overheats. In the event of a possible thermal overload, the relay triggers the input contactor and prevents the braking resistor from burning up. u Installation WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect a braking resistor directly to any other terminals. Improper wiring connections could result in death or serious injury by fire. Failure to comply may result in damage to the braking circuit or drive. NOTICE: Connect braking resistors to the drive as shown in the I/O wiring examples. Improperly wiring braking circuits could result in damage to the drive or equipment. n Installation Procedure 1. Disconnect all electrical power to the drive and wait at least five minutes before servicing the drive and any connected components. 2. Remove drive front cover. 3. Use a voltmeter to verify that voltage is disconnected from incoming power terminals and that the DC bus no longer holds a charge.
Figure 3.28 Connecting a Braking Resistor. Power supply, MCCB, MC, drive R/L1, S/L2, T/L3; B1 and B2, thermal relay, braking resistor; U/T1, V/T2, W/T3, Motor. Thermal relay switch for external braking resistor; fault contact; THRX, OFF, ON, MC, SA, TRX, MA, MC. Original interlock and connection geometry required.
- Follow manufacturer instructions to connect the resistor unit to the drive using proper wire gauge according to local electrical codes. Power leads for the remote mount resistors generate high levels of electrical noise; group these signal leads separately. 5. Mount the resistor unit on a noncombustible surface. Maintain minimum side and top clearances according to resistor manufacturer instructions. WARNING! Fire Hazard. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive or braking resistors to metal or other noncombustible material. 6. Reinstall drive covers and resistor covers, if provided. 7. Set parameter L3-04 = “0” or “3” to disable stall prevention during deceleration. Set parameter L8-01 to “1” to enable overheat protection when using a heatsink-mounted braking resistor option. Set L8-01 = “0” for other braking resistor types. Set parameter L3-04 = “3” to generate the shortest possible deceleration time.
Manual — Braking resistor table caption — page 73
Source reference: SIEP C71060618F, December 2016, physical PDF page 73. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.11 Braking Resistor Table 3.16 Braking Resistor Settings
- Operate the system and verify the required deceleration rate is obtained during dynamic braking or stopping.
Installation Electrical 3
Table 3.16 Braking Resistor Settings — PDF page 73
| Source row | Parameter | Settings |
|---|---|---|
| 1 | L8-01: Internal Dynamic Braking Resistor Protection Selection | 0: Disabled. The drive will not provide overheat protection. Supply separate means of overheat protection. 1: Enabled. Braking Resistor is protected from overheat. |
| 2 | L3-04: Stall Prevention During Deceleration Note: Select either 0 or 3 | 0: Stall prevention disabled. |
| 3 | L3-04: Stall Prevention During Deceleration Note: Select either 0 or 3 | 3: Stall prevention enabled with a braking resistor Note: This setting cannot be used in OLV control for PM motor. |
Manual — Wiring checklist context — page 74
Source reference: SIEP C71060618F, December 2016, physical PDF page 74. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.12 Wiring Checklist 3.12 Wiring Checklist
Unmarked checklist items, not completed commissioning checks. Read with class-specific exclusions; diagrams original-only. Source cross references retained literally.
3.12 Wiring Checklist — PDF page 74
| Source row | No. | Item | Page |
|---|---|---|---|
| 1 | 1 | Check drive model number to ensure receipt of correct model. | 25 |
| 2 | 2 | Check for correct braking resistors, DC link chokes, noise filters, and other peripheral devices. | 72 |
| 3 | 3 | Check for correct option card model. | 338 |
| 4 | 4 | Ensure area surrounding the drive complies with specifications. | 38 |
| 5 | 5 | The voltage from the power supply should fall within the input voltage specification range of the drive. | 169 |
| 6 | 6 | The voltage rating for the motor should match the drive output specifications. | 25 |
| 7 | 7 | Confirm proper branch circuit protection exists per National and Local codes. | 50 |
| 8 | 8 | Properly wire the power supply to drive terminals R/L1, S/L2 and T/L3. | 53 |
| 9 | 9 | Properly wire the drive and motor together. The motor lines and drive output terminals R/T1, V/T2 and W/T3 should match in order to produce the desired phase order. If the phase order is incorrect, the drive will rotate in the opposite direction. | 61 |
| 10 | 10 | Use 600 Vac vinyl-sheathed wire for the power supply and motor lines. | 58 |
| 11 | 11 | Use the correct wire gauges for the main circuit. Refer to Table 3.2, Table 3.3, or Table 3.4. | 58 |
| 12 | ⟦blank source cell⟧ | • When using comparatively long motor cable, calculate the amount of voltage drop. Motor rated voltage (V) x 0.02 ≥ 3 x voltage resistance (Ω/km) x cable length (m) x motor rated current (A) x 10-3 | 58 |
| 13 | ⟦blank source cell⟧ | • If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency (C6-02) accordingly. | 61 |
| 14 | 12 | Properly ground the drive. | 62 |
| 15 | 13 | Tightly fasten all terminal screws (control circuit terminals, grounding terminals). Refer to Table 3.2, Table 3.3, or Table 3.4. | 58 |
| 16 | 14 | Set up overload protection circuits when running multiple motors from a single drive. Diagram labels: Power supply; Drive; MC1, MC2, MCn; OL1, OL2, OLn; M1, M2, Mn. MC1–MCn: magnetic contactor. OL1–OLn: thermal relay. Note: Close MC1 through MCn before operating the drive. Original diagram geometry retained. | – |
| 17 | 15 | If using a braking resistor or dynamic braking resistor unit, install a magnetic contactor. Properly install the resistor, and ensure that overload protection shuts off the power supply. | 72 |
| 18 | 16 | Verify phase advancing capacitors are NOT installed on the output side of the drive. | – |
| 19 | 17 | Use twisted-pair cables for all drive control circuit wiring. | 63 |
| 20 | 18 | Ground the shields of shielded wiring to the GND [ground symbol] terminal. | 66 |
| 21 | 19 | If using a 3-Wire sequence, properly set parameters for multi-function contact input terminals S1 through S7, and properly wire control circuits. | 52 |
| 22 | 20 | Properly wire any option cards. | 338 |
| 23 | 21 | Check for any other wiring mistakes. Only use a multimeter to check wiring. | – |
| 24 | 22 | Properly fasten the control circuit terminal screws in the drive. Refer to Table 3.2, Table 3.3, or Table 3.4. | 58 |
| 25 | 23 | Pick up all wire clippings. | – |
Manual — Wiring checklist continuation heading — page 75
Source reference: SIEP C71060618F, December 2016, physical PDF page 75. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
3.12 Wiring Checklist
Installation Electrical 3
Unmarked checklist items, not completed commissioning checks. Read with class-specific exclusions; diagrams original-only. Source cross references retained literally.
3.12 Wiring Checklist continued — PDF page 75
| Source row | No. | Item | Page |
|---|---|---|---|
| 1 | 24 | Ensure that no frayed wires on the terminal block are touching other terminals or connections. | – |
| 2 | 25 | Properly separate control circuit wiring and main circuit wiring. | – |
| 3 | 26 | Analog signal line wiring should not exceed 50 m. | – |
| 4 | 27 | Safe Disable Input wiring should not exceed 30 m. | – |
Manual — Section safety: electrical shock and fire hazards — page 78
Source reference: SIEP C71060618F, December 2016, physical PDF page 78. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.1 Section Safety
DANGER
Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may include drives without covers or safety shields to illustrate details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material.
Manual — Section safety: ESD and wiring notices — page 79
Source reference: SIEP C71060618F, December 2016, physical PDF page 79. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBP C720600 00 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive.
4.1 Section Safety
Start-Up Programming & Operation
Manual — LED operator components1–8 — page 80
Source reference: SIEP C71060618F, December 2016, physical PDF page 80. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Source limitation for this page: Human-readable miniature menu labels recovered in additive source context. Ambiguous segmented display glyph shapes remain unnormalized incidental illustration detail. Printed1-minute warning versus5-minute-plus-measurement source conflict retained.
Operator example F60.00. Numbered callouts:1 Data Display Area;2 ESC;3 RESET/right arrow;4 RUN;5 Up Arrow;6 Down Arrow;7 STOP;8 ENTER;9 LO/RE selection;10 RUN light;11 LO/RE light;12 ALM;13 REV;14 DRV;15 FOUT;16 communication port. Functions in Table4.1 on PDF80–81. Physical key/port geometry and miniature unit label remain original-only; example display is not a recommended setting.
4.2 Using the Digital LED Operator
Use the LED operator to enter run and stop commands, display data, edit parameters, as well as display fault and alarm information.
u Keys, Displays, and LEDs
Table 4.1 Keys and Displays on the LED Operator
No. Display Name Function
The miniature YASKAWA V1000 illustration lists these labels in top-to-bottom order: Fref (Hz); FWD/REV Sel; Fout (Hz); Iout (A); Mon1 (V); Monitor; Verify; SetUpGuide; Program; Auto-Tuning. Units shown in parentheses belong to their corresponding printed row. Small segmented display glyphs beside these labels remain original-image evidence, not normalized parameter values or operating settings.
Table4.1 LED operator component functions,1–8 — PDF page 80
| Source row | No. | Display graphic | Name | Function |
|---|---|---|---|---|
| 1 | 1 | F60.00 | Data Display Area | Displays the frequency reference, parameter number, etc. |
| 2 | 2 | ESC key graphic | ESC Key | Returns to the previous menu. |
| 3 | 3 | RESET / right-arrow key graphic | RESET Key | Moves the cursor to the right. Resets the drive to clear a fault situation. |
| 4 | 4 | RUN key graphic | RUN Key | Starts the drive. |
| 5 | 5 | Up-arrow key graphic | Up Arrow Key | Scrolls up to select parameter numbers, setting values, etc. |
| 6 | 6 | Down-arrow key graphic | Down Arrow Key | Scrolls down to select parameter numbers, setting values, etc. |
| 7 | 7 | STOP key graphic | STOP Key | Stops the drive. Note: Stop priority circuit. Pressing the STOP key will always cause the drive to stop the motor, even when a Run command is active at an external Run command source. Set parameter o2-06 to 0 to disable the STOP key priority. |
| 8 | 8 | ENTER key graphic | ENTER Key | Selects all modes, parameters, settings, etc. Selects a menu item to move from one display screen to the next. |
Manual — LED operator components9–16 and segment glyph table — page 81
Source reference: SIEP C71060618F, December 2016, physical PDF page 81. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Display Name Function
u Digital Text Display
Text appears on the LED Operator as shown below. This section explains the meaning of text as it appears on the display screen.
Lit Flashing
Table 4.2 Digital Text Display
Text LED Text LED Text LED Text LED
<1> Displayed in two digits.
4.2 Using the Digital LED Operator
Start-Up Programming & Operation
Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.
Table4.1 LED operator component functions,9–16 — PDF page 81
| Source row | No. | Display graphic | Name | Function |
|---|---|---|---|---|
| 1 | 9 | LO/RE key graphic | LO/RE Selection Key | Switches drive control between the operator (LOCAL) and the control circuit terminals (REMOTE). Note: LOCAL/REMOTE key effective during stop in drive mode. If the digital operator could change from REMOTE to LOCAL by incorrect operation, set o2-01 (LOCAL/REMOTE Key Function Selection) to “0” (disabled) to disable LOCAL/ REMOTE key. |
| 2 | 10 | RUN light graphic | RUN Light | Lit while the drive is operating the motor. |
| 3 | 11 | LO/RE light graphic | LO/RE Light | Lit while the operator (LOCAL) is selected to run the drive. |
| 4 | 12 | ALM | ALM LED Light | Refer to LED Screen Displays on page 82. |
| 5 | 13 | REV | REV LED Light | Refer to LED Screen Displays on page 82. |
| 6 | 14 | DRV | DRV LED Light | Refer to LED Screen Displays on page 82. |
| 7 | 15 | FOUT | FOUT LED Light | Refer to LED Screen Displays on page 82. |
| 8 | 16 | – | Communication Port | Port used for USB Copy Unit, LCD Operator Keypad, and for connecting to a PC. NOTICE: Use only specified cable when making connections to the drive. Failure to comply may damage the drive. NOTICE: Do not open the port cover wider than 90 degrees. Failure to comply may break the port cover and leave the unprotected port susceptible to damage. |
Lit/flashing LED examples — PDF page 81
| Source row | Lit | Flashing |
|---|---|---|
| 1 | A1-03 (lit) | A1-03 (flashing) |
Table4.2 LED display character correspondence — PDF page 81
| Source row | Text | LED graphic | Text | LED graphic | Text | LED graphic | Text | LED graphic |
|---|---|---|---|---|---|---|---|---|
| 1 | 0 | Segment glyph for 0; see original graphic | 9 | Segment glyph for 9; see original graphic | I | Segment glyph for I; see original graphic | R | Segment glyph for R; see original graphic |
| 2 | 1 | Segment glyph for 1; see original graphic | A | Segment glyph for A; see original graphic | J | Segment glyph for J; see original graphic | S | Segment glyph for S; see original graphic |
| 3 | 2 | Segment glyph for 2; see original graphic | B | Segment glyph for B; see original graphic | K | Segment glyph for K; see original graphic | T | Segment glyph for T; see original graphic |
| 4 | 3 | Segment glyph for 3; see original graphic | C | Segment glyph for C; see original graphic | L | Segment glyph for L; see original graphic | U | Segment glyph for U; see original graphic |
| 5 | 4 | Segment glyph for 4; see original graphic | D | Segment glyph for D; see original graphic | M | Segment glyph for M; see original graphic <1> Displayed in two digits | V | Segment glyph for V; see original graphic |
| 6 | 5 | Segment glyph for 5; see original graphic | E | Segment glyph for E; see original graphic | N | Segment glyph for N; see original graphic | W | Segment glyph for W; see original graphic <1> Displayed in two digits |
| 7 | 6 | Segment glyph for 6; see original graphic | F | Segment glyph for F; see original graphic | O | Segment glyph for O; see original graphic | X | None |
| 8 | 7 | Segment glyph for 7; see original graphic | G | Segment glyph for G; see original graphic | P | Segment glyph for P; see original graphic | Y | Segment glyph for Y; see original graphic |
| 9 | 8 | Segment glyph for 8; see original graphic | H | Segment glyph for H; see original graphic | Q | Segment glyph for Q; see original graphic | Z | None |
Manual — LED states and timing illustrations — page 82
Source reference: SIEP C71060618F, December 2016, physical PDF page 82. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure4.1 RUN LED Status and Meaning: Flashing; Flashing quickly; ON;1 s reference arrow. Actual pulse geometry remains original-only; no additional timing inferred. Figure4.2 RUN LED and Drive Operation: Drive output frequency; RUN/STOP key commands; during stop; RUN; STOP; RUN; STOP; Frequency setting0 Hz and6 Hz; RUN LED OFF, ON, OFF, OFF; bracket labelled Flashing. Operating sequence is an illustration, not a device log.
u LED Screen Displays
Display Lit Flashing Off
<1> Refer to the DriveWorksEZ instruction manual for further information.
u LO/RE LED and RUN LED Indications
LED Lit Flashing Flashing Quickly <1> Off
<1> Refer to Figure 4.1 for the difference between “flashing” and “flashing quickly”. <2> Refer to the description for parameter U4-21 on page 403 for information on verifying operation interlock.
4.2 Using the Digital LED Operator
Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.
LED Screen Displays (unnumbered source table) — PDF page 82
| Source row | Indicator | Lit | Flashing | OFF |
|---|---|---|---|---|
| 1 | ALM | When the drive detects an alarm or error | • When an alarm occurs • oPE detected • When a fault or error occurs during Auto-Tuning | Normal state (no fault or alarm) |
| 2 | REV | Motor is rotating in reverse | — | Motor is rotating forward |
| 3 | DRV | Drive Mode Auto-Tuning | When DriveWorksEZ is used <1> | Programming Mode |
| 4 | FOUT | Displays output frequency (Hz) | — | — |
| 5 | As illustrated in this manual | F 0.00; enlarged DRV label in Lit-column illustration | Er-03; alarm illustration flashing | F 0.00; enlarged DRV label in Off-column illustration |
LO/RE and RUN LED states — PDF page 82
| Source row | LED | Lit | Flashing | Flashing quickly | OFF |
|---|---|---|---|---|---|
| 1 | LO/RE light graphic | When a Run command is selected from the LED operator (LOCAL) | – | – | Run command is selected from device other than LED operator (REMOTE) |
| 2 | RUN light graphic | During Run | • During deceleration to stop • When a Run command is input and frequency reference is 0 | • During deceleration at a fast- stop. • During stop by interlock <2> operation. | During stop |
| 3 | As shown | RUN light lit | RUN light flashing | RUN light flashing quickly | RUN light off |
Manual — Digital LED operator menu structure — page 83
Source reference: SIEP C71060618F, December 2016, physical PDF page 83. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Turn power on:F 0.00. DRIVE MODE, DRV light on, pressing RUN starts motor: Forward Selection For; ENTER selects Reverse Selection rEv; ESC returns. Reverse only when LOCAL is set. Cycle using UP/DOWN: output frequency0.00; output current0.00A; output voltage0.0V; Monitor Display Mon. Monitor entries U1-01 through U8-10; ENTER shows XX values, ESC returns. PROGRAMMING MODE, DRV light off, drive cannot operate motor: Verify Menu vrFY with XX-XX parameter placeholders and XX values; Set Up Mode StUP with APPL Application Preset and0X setting, other XX-XX/XX placeholders; Parameter Setting Mode PAr, A1-01 through r1-40, XX values; Auto-Tuning AtUn, T1-01 through T1-07, runXX, RUN, End. XX denotes actual setting values in the real display. Legend right arrow=ENTER,left arrow=ESC,downward navigation arrow=UP key,upward navigation arrow=DOWN key. Complete graphic and flash-state shapes remain in original.
u Menu Structure for Digital LED Operator
<1> Reverse can only be selected when LOCAL is set.
4.2 Using the Digital LED Operator
Start-Up Programming & Operation
Manual — Drive and Programming Mode summary — page 84
Source reference: SIEP C71060618F, December 2016, physical PDF page 84. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Mode Group | Description | Key Press | LED display. Drive Mode Functions (Motor operation and monitoring):Frequency Reference Display (Initial power-up state),UP,F0.00; Forward/Reverse,UP,For; Output Frequency Display,UP,0.00; Output Current Display,UP,0.00A; Output Voltage Reference,UP,0.0V; Monitor Display,UP,Mon. Programming Mode Functions (Changing parameters):Verify Function,UP,vrFY; Setup Group Parameters,UP,StUP; All Parameters,UP,PAr; Auto-Tuning,UP,AtUn. <1> Enlarged illustration of LED indicates LED on. Display/flash illustrations retained in original; values are source examples.
4.3 The Drive and Programming Modes
The drive functions are divided into two main groups accessible via the Digital LED Operator: Drive Mode: The Drive mode allows motor operation and parameter monitoring. Parameter settings cannot be changed when accessing functions in the Drive Mode (Table 4.3) Programming Mode: The Programming Mode allows access to setup/adjust, verify parameters and Auto-Tuning. The drive prohibits changes in motor operation such as start/stop when the Digital LED Operator is accessing a function in the Programming Mode. Table 4.3 illustrates the different functions visible as the “Up arrow” is scrolled immediately after powering up the drive.
Note: When b1-08 (Run Command Selection while in Programming Mode) is set to 1 (enabled), the drive can run even if the mode is switched to the programming mode. When setting b1-08 to 0 (disabled), the mode cannot be switched to the programming mode while the drive is running.
Table 4.3 Summary of Modes
<1> The enlarged illustration of the LED indicates that the LED is on.
Manual — Drive Mode navigation — page 85
Source reference: SIEP C71060618F, December 2016, physical PDF page 85. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Power Up:Frequency Reference/default setting/F0.00. This display monitors and sets frequency reference while running; see84. Initial display item selectable with o1-02. UP/DOWN navigate display rows. Drive Mode Forward/Reverse:For=motor rotates forward;rEv=motor rotates reverse. b1-04=1 prohibits reverse for applications such as fans/pumps. Illustrated reverse sequence also selects LOCAL:For→LO/RE→ENTER→For flashing→UP→rEv flashing→ENTER;LO/RE LED lit when LOCAL selected. Output Frequency Display0.00:monitors drive output frequency. Output Current Display0.00A:monitors output current. Output Voltage Reference0.0V(default setting):scroll o1-01(User Monitor Selection)until desired contents appear,Parameter List353. Monitor Display Mon:monitor parameters(U parameters). Physical display/LED/key shapes remain original-only.
u Navigating the Drive and Programming Modes
The drive is set to operate in Drive Mode when it is first powered up. Switch between display screens by using the [UP] and [DOWN] keys.
4.3 The Drive and Programming Modes
Start-Up Programming & Operation
Manual — Programming Mode navigation and frequency-reference example — page 86
Source reference: SIEP C71060618F, December 2016, physical PDF page 86. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Programming Mode, UP/DOWN navigation:Verify Function vrFY lists parameters edited/changed from defaults,see88. Setup StUP lists parameters needed for operation;see87;shown parameters depend on A1-06 Application Preset,see96. Parameter Setting PAr accesses/edits all settings,see353. Auto-Tuning AtUn calculates/sets motor parameters,see102. Drive Mode Frequency Reference F0.00 returns to frequency reference screen. Drawn LED/key illustrations retained in original.
Frequency reference display at power-up F0.00. LO/RE selects LOCAL; ENTER opens F00.00; RESET selects digit to right; UP until frequency reference6 Hz(F06.00); ENTER confirms,End; display F06.00; ESC returns F6.00. Figure4.4 Setting the Frequency Reference while in Drive Mode. Decimal glyph and flashing-digit shapes remain original; this is an example, not a current setting.
n Drive Mode Details
The following actions are possible in the Drive Mode: • Run and stop the drive. • Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.). • View information on an alarm. • View a history of alarms that have occurred.
Note: Select "Drive Mode" when running. The mode can be switched to any mode (program mode, etc.) other than drive mode while the drive is stopped. However, the drive cannot be operated in other modes. Return the mode to "Drive Mode" after completing periodic inspection. Figure 4.4 illustrates changing the default frequency reference of F 0.00 (0 Hz) to F 6.00 (6 Hz) while in Drive Mode. This example assumes the drive is set to LOCAL.
Note: The drive will not accept a frequency reference set value unless the ENTER key is pressed after the frequency reference is entered. This feature prevents accidental setting of the frequency reference. By setting o2-05 (Frequency Reference Setting Method Selection) to 1 (Enabled), the drive will accept the frequency reference while it is being adjusted on the digital operator.
4.3 The Drive and Programming Modes
Manual — Setup Group example — page 87
Source reference: SIEP C71060618F, December 2016, physical PDF page 87. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Frequency reference at power-up F0.00. Press DOWN until StUP appears; ENTER→APPL Application Preset; UP→A1-02 Parameter Display; UP→b1-01; ENTER→01 Control Circuit Terminal; RESET selects digit; DOWN→00 LED Operator; ENTER→End→b1-01; ESC→F6.00. Setup parameter sequence illustrated A1-02,b1-01,b1-02,b1-03,...L3-04. <1> ENTER from APPL navigates to Application Preset setting display; changing value changes parameter to optimum value for each application;0 General-purpose prior to shipment. <2> Move right to change parameter settings;scroll down to view/check Setup Mode settings. <3> ESC returns Top Menu; UP/DOWN view/edit other parameters. This source example changes b1-01 from1 to0; terminal/current drive settings are not inferred.
n Programming Mode Details
The following actions are possible in the programming mode: • Verify Function: Verify parameter setting changes from original default values. • Setup Group: Access a list of commonly used parameters to simplify setup. • Parameter Setting Mode: Access and edit all parameter settings. • Auto-Tuning: Automatically calculates and sets motor parameters for Open Loop or PM Vector control to optimize the drive for the motor characteristics.
The Setup Group within the Programming Mode In Setup Group, the user can access the minimum group of parameters required to operate the application.
Note: Setup Group parameters are listed in Table 4.4.
Note: Pressing ENTER from APPL navigates to the Application Preset setting display. When the set value is changed, the parameter is changed to the optimum value for each application. It is set to 0 (General-purpose) prior to shipment. Refer to Application Selection on page 96. Figure 4.5 illustrates the keys to press to enter the Setup Group. In this example, the source of the frequency reference is changed from the control circuit terminals to the LED Operator (i.e., b1-01 is changed from 1 to 0).
4.3 The Drive and Programming Modes
Start-Up Programming & Operation
Manual — Changing/verifying parameters and LOCAL/REMOTE warning — page 88
Source reference: SIEP C71060618F, December 2016, physical PDF page 88. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u Changing Parameter Settings or Values
This example explains changing C1-01 (Acceleration Time 1) from 10.0 seconds (default) to 20.0 seconds.
Step Display/Result
u Verifying Parameter Changes: Verify Menu
The Verify Menu lists edited parameters from the Programming Mode or as a result of Auto-Tuning. The Verify Menu helps determine which settings have been changed, and is particularly useful when replacing a drive. If no settings have been changed, the Verify Menu will read [nonE]. The Verify menu also allows users to access and re-edit previously edited parameters.
Note: The Verify Menu will not display A1-oo parameters (except for A1-02), nor will it display parameters A2-01 to A2-32 or E5-01 even if those parameters have been changed from default settings. The following example is a continuation of the steps beginning on page 88. Here, parameter C1-01 is accessed using the Verify Menu and is changed again to 20.0 s. To check the list of edited parameters:
u Switching Between LOCAL and REMOTE
Entering the run command using the LED operator is referred to as LOCAL, while entering the run command from an external device via the control circuit terminals or network option is referred to as REMOTE.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode. There are two ways to switch between LOCAL and REMOTE.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
4.3 The Drive and Programming Modes
Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.
Changing C1-01 acceleration time example — PDF page 88
| Source row | Step | Description | Connector graphic | LED display graphic |
|---|---|---|---|---|
| 1 | 1. | Turn on the power to the drive. The initial display appears. | Right-arrow connector (not a key) | F 0.00 |
| 2 | 2. | Press the [UP] key until the Setup Mode Screen appears. | Right-arrow connector (not a key) | StUP |
| 3 | 3. | Press the [ENTER] key to view the parameter setting display. | Right-arrow connector (not a key) | APPL |
| 4 | 4. | Scroll through parameters by pressing the [UP] key until C1-01 appears. | Right-arrow connector (not a key) | C1-01 |
| 5 | 5. | Press [ENTER] to view the current setting value (10.0). (Number farthest to the left flashes) | Right-arrow connector (not a key) | 0010.0 (leftmost digit flashes) |
| 6 | 6. | Press [RESET] until the desired number is selected. (“1” flashes) | Right-arrow connector (not a key) | 0010.0 (1 flashes) |
| 7 | 7. | Press the [UP] key and enter 0020.0. | Right-arrow connector (not a key) | 0020.0 |
| 8 | 8. | Press [ENTER] and the drive will confirm the change. | Right-arrow connector (not a key) | End |
| 9 | 9. | The display automatically returns to the screen shown in Step 4. | Right-arrow connector (not a key) | C1-01 |
| 10 | 10. | Press the [ESC] key until back at the initial display. | Right-arrow connector (not a key) | F 0.00 |
Verify menu example — PDF page 88
| Source row | Step | Description | Connector graphic | LED display graphic |
|---|---|---|---|---|
| 1 | 1. | Turn on the power to the drive. The initial display appears. | Right-arrow connector (not a key) | F 0.00 |
| 2 | 2. | Press [UP] until the display shows the “Verify” representation. | Right-arrow connector (not a key) | vrFY |
| 3 | 3. | Press [ENTER] to enter the list of parameters that have been edited from their original default settings. Scroll through the list by pressing the [UP] key. | Right-arrow connector (not a key) | A2-02 |
| 4 | 4. | Press the [UP] key until C1-01 appears. | Right-arrow connector (not a key) | C1-01 |
| 5 | 5. | Press the [ENTER] key to access the setting value. (number farthest to the left flashes) | Right-arrow connector (not a key) | 0020.0 (leftmost digit flashes) |
Manual — LOCAL/REMOTE selection and Setup Group parameters — page 89
Source reference: SIEP C71060618F, December 2016, physical PDF page 89. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
- The drive will not allow the user to switch between LOCAL and REMOTE during run.
n Using the LO/RE Key on the LED Operator
Step Display/Result
n Using Input Terminals S1 through S7 to Switch between LO/RE
Switch between LOCAL and REMOTE using one of the digital input terminals S1 through S7 (set the corresponding parameter H1-01 through H1-07 to 1). Follow the example below to set the digital input terminals.
Note: 1. Refer to Parameter List on page 353 for a list of digital input selections. 2. Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator.
u Parameters Available in the Setup Group
n Setup Mode (STUP)
Parameters used for this drive are classified into A to U. To simplify the drive setup, frequently used parameters are selected and input into Setup Mode. 1. To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key until [StUP] is displayed. 2. Select the parameter and change the setting. Table 4.4 lists parameters available in the Setup group. If the desired parameter cannot be set in the Setup mode, use the Parameter Setting mode. Note: 1. When parameter A1-02 (Control Method Selection) is changed, some parameter set values are also changed automatically. 2. Use the “Par” menu in the Programming mode to access parameters not listed in the Setup Group. 3. Display parameters depend on A1-06. Refer to Application Selection on page 96.
Table 4.4 Setup Group Parameters
Parameter Name
4.3 The Drive and Programming Modes
Start-Up Programming & Operation
Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.
LOCAL/REMOTE selection example — PDF page 89
| Source row | Step | Description | Connector graphic | LED display graphic |
|---|---|---|---|---|
| 1 | 1. | Turn on the power to the drive. The initial display appears. | Right-arrow connector (not a key) | F 0.00; DRV lit |
| 2 | 2. | Press [LO/RE]. The LO/RE light will light up. The drive is now in Local. To set the drive for REMOTE operation, press the [LO/RE] key again. | Right-arrow connector (not a key) | Operator example F60.00; LO/RE light changes from off to lit. Other key graphics remain original-only. |
Table4.4 Setup Mode parameters left column — PDF page 89
| Source row | Parameter | Name |
|---|---|---|
| 1 | A1-02 | Control Method Selection |
| 2 | b1-01 | Frequency Reference Selection 1 |
| 3 | b1-02 | Run Command Selection 1 |
| 4 | b1-03 | Stop Method Selection |
| 5 | C1-01 | Acceleration Time 1 |
| 6 | C1-02 | Deceleration Time 1 |
| 7 | C6-01 | Duty Selection |
| 8 | C6-02 | Carrier Frequency Selection |
| 9 | d1-01 | Frequency Reference 1 |
| 10 | d1-02 | Frequency Reference 2 |
| 11 | d1-03 | Frequency Reference 3 |
| 12 | d1-04 | Frequency Reference 4 |
| 13 | d1-17 | Jog Frequency Reference |
Table4.4 Setup Mode parameters right column — PDF page 89
| Source row | Parameter | Name |
|---|---|---|
| 1 | E1-01 | Input Voltage Reference |
| 2 | E1-03 | V/f Pattern Selection |
| 3 | E1-04 | Maximum Output Frequency |
| 4 | E1-05 | Maximum Voltage |
| 5 | E1-06 | Base Frequency |
| 6 | E1-09 | Minimum Output Frequency |
| 7 | E1-13 | Base Voltage |
| 8 | E2-01 | Motor Rated Current |
| 9 | E2-04 | Number of Motor Poles |
| 10 | E2-11 | Motor Rate Capacity |
| 11 | H4-02 | Terminal AM Gain Setting |
| 12 | L1-01 | Motor Protection Function Selection |
| 13 | L3-04 | Stall Prevention Selection during Deceleration |
Manual — Startup flowchart index — page 90
Source reference: SIEP C71060618F, December 2016, physical PDF page 90. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.4 Start-up Flowcharts
The flowcharts in this section summarize basic steps required to start the drive. Use the flowcharts to determine the most appropriate start-up method for a given application. The charts are intended as a quick reference to help familiarize the user with start-up procedures.
Flowchart Subchart Objective Page
Startup flowchart index — PDF page 90
| Source row | Flowchart | Sub-chart | Purpose | Page |
|---|---|---|---|---|
| 1 | A | ⟦blank source cell⟧ | Basic startup procedure and motor tuning. | 91 |
| 2 | ⟦blank source cell⟧ | A-1 | Simple motor setup with Energy Savings or Speed Search using V/f mode. | 92 |
| 3 | ⟦blank source cell⟧ | A-2 | High-performance operation using Open Loop Vector (OLV) motor control. | 93 |
| 4 | ⟦blank source cell⟧ | A-3 | Operation with Permanent Magnet (PM) motors. | 94 |
| 5 | ⟦blank source cell⟧ | - | Setup of drive using application specific selections. Refer to Application Selection on page 96. | - |
Manual — Flowchart A basic startup — page 91
Source reference: SIEP C71060618F, December 2016, physical PDF page 91. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
START→install/wire according to Chapters1,2,3→apply main power/adhering to safety. Application Presets A1-06 used? Yes→Application Selection section→rejoin control-mode branch. No→set A1-02 control mode→set basic parameters:b1-01/02 frequency/run-command sources;H1-□□,H2-□□,H3-□□,H4-□□,H6-□□ I/O terminals;d1-□□ multi-speed references if used;C1-□□ and C2-□□ accel/decel and S-curves;C6-01 heavy/normal duty;L3-04 if braking options used. A1-02=0 V/f→A-1;=2 Open Loop Vector→A-2;=5 Open Loop Vector for PM→A-3. Return from A-1/A-2/A-3→run without load/check rotation and external commands→couple load/check desired operation→fine-tune(PID if necessary)→check operation/verify settings→Drive is ready to run application. Last phrase is supplier flowchart endpoint, not completed commissioning.
u Flowchart A: Basic Start-up and Motor Tuning
Figure 4.6, Flowchart A, describes basic start-up sequence for the drive and motor system. This sequence varies slightly depending on application. Use drive default parameter settings in simple applications that do not require high precision.
4.4 Start-up Flowcharts
Start-Up Programming & Operation
Manual — Flowchart A1 V/f tuning — page 92
Source reference: SIEP C71060618F, December 2016, physical PDF page 92. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
From Flowchart A→set/verify V/f E1-□□. Energy Savings(b8-01=1)or Speed Estimation Speed Search(b3-24=1)enabled? YES→Rotational Auto-Tuning for V/f Control(T1-01=3)→Return to A. NO→motor cable longer than50 m? YES→Stationary Auto-Tuning terminal resistance(T1-01=2)→Return to A; NO→Return to A. Source conditions not general permission to perform work; original safety and complete instructions apply.
u Subchart A1: Simple Motor Setup with Energy Savings or Speed Search Using V/f Mode
Figure 4.7, Flowchart A1, describes simple motor setup for V/f control. V/f Motor Control is suited for the most basic applications such as fans or pumps. This procedure illustrates using Energy Savings and Speed Estimation Speed Search. V/ f control can be used where rotational auto-tuning cannot be performed.
4.4 Start-up Flowcharts
Manual — Flowchart A2 Open Loop Vector tuning — page 93
Source reference: SIEP C71060618F, December 2016, physical PDF page 93. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
From A→Possible for motor to rotate during tuning?<1>. YES→Rotating Auto-Tuning(T1-01=0)→Return to A. <1> Rotational tuning should be performed with load disconnected. NO→Motor test report/data sheet available? YES→enter motor data sheet into E2-□□→motor cable longer than50 m? YES→Stationary Auto-Tuning terminal resistance(T1-01=2)→Return to A;NO→Return to A. No motor report→calculate necessary E2-□□ using nameplate→Stationary Auto-Tuning terminal resistance(T1-01=2)→Return to A. No motor values are calculated in this transcription.
u Subchart A2: High Performance Operation Using Open Loop Vector Motor Control
Figure 4.8, Flowchart A2, describes Open Loop Vector Control for high-performance motor operation. This is appropriate for applications requiring high starting torque, torque limits, and improved speed regulation.
4.4 Start-up Flowcharts
Start-Up Programming & Operation
Manual — Flowchart A3 PM tuning — page 94
Source reference: SIEP C71060618F, December 2016, physical PDF page 94. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
From A→Motorcode is known? For E5-01(for Yaskawa PM Motors). YES→set motor code to E5-01→Return to A. NO→enter FFFF into E5-01→enter motor data E5-02 to E5-24→Return to A. Figure4.9 Operation with Permanent Magnet Motors; no motorcode or compatibility inferred.
u Subchart A3: Operation with Permanent Magnet Motors
Figure 4.9, Flowchart A3, describes tuning for PM motors in Open Loop Vector Control. PM motors can be used for energy savings in reduced or variable torque applications.
4.4 Start-up Flowcharts
Manual — Power-up checklist and status displays — page 95
Source reference: SIEP C71060618F, December 2016, physical PDF page 95. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.5 Powering Up the Drive
u Powering Up the Drive and Operation Status Display
n Powering Up the Drive
Review the following checklist before turning the power on.
Item to Check Description
n Status Display
When the power supply to the drive is turned on, the LED operator lights will appear as follows:
No. Name Description
Note: Display will vary depending on drive settings.
Start-Up Programming & Operation
Literal manual source; examples are not device settings. Read with surrounding safety notes, preset-specific applicability and footnotes. Drawn key/LED glyphs require original figure.
Powering up checklist source conditions — PDF page 95
| Source row | Item | Description |
|---|---|---|
| 1 | Power supply voltage | Ensure the power supply voltage is correct: 200 V class: single-phase 200 to 240 Vac 50/60 Hz 200 V class: 3-phase 200 to 240 Vac 50/60 Hz 400 V class: 3-phase 380 to 480 Vac 50/60 Hz |
| 2 | Power supply voltage | Properly wire the power supply input terminals (R/L1, S/L2, T/L3). (for single-phase 200 V class models, wire only R/L1 and S/L2) |
| 3 | Power supply voltage | Check for proper grounding of drive and motor. |
| 4 | Drive output terminals and motor terminals | Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W. |
| 5 | Control circuit terminals | Check control circuit terminal connections. |
| 6 | Drive control terminal status | Open all control circuit terminals (off). |
| 7 | Status of the load and connected machinery | Uncouple the motor from the load. |
Power-up LED example displays — PDF page 95
| Source row | Status | Display graphic | Description |
|---|---|---|---|
| 1 | Normal Operation | F 0.00; DRV lit | The data display area displays the frequency reference. [DRV] is lit. |
| 2 | Fault | Uv1; Main circuit low voltage (ex) | Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible Solutions on page 267 for more information and possible solution. [ALM] and [DRV] are lit. |
Manual — Application Selection and water-supply pump preset — page 96
Source reference: SIEP C71060618F, December 2016, physical PDF page 96. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.6 Application Selection
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application Presets automatically sets the required parameters to the Application Preset default values and selects I/Os. In addition, the parameters most likely to be changed are assigned to the list of User Parameters, A2-01 through A2-16. These can be accessed in the Setup Mode and provide quicker application adjustment by eliminating the need to scroll through multiple menus. The following presets can be selected:
Note: 1. Do not set any value outside the allowable range for A1-06. Setting an out-of-range value will cause “APPL” to flash on the display in the Setup group and disable the up and down arrow keys on the digital operator. To fix this error, press the ESC key to return to the Setup group and then it will then be possible to switch to another mode using the up and down arrow keys. 2. A1-06 setting can only be changed by initializing the drive by first setting A1-03 to 2220. Setting A1-06 to a value that is out of range will not adversely affect drive operation. When the drive should not be initialized because initialization will cause other problems, then A1-06 does not need to be changed.
WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change the I/ O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.
No. Parameter Name Setting Range Default
<1> Application Preset settings 6 and 7 are only available in drive software versions PRG: 5010, PRG: 1010, and PRG: 1011. To determine the drive software version, refer to the PRG: field on the drive nameplate or drive parameter U1-25. <2> Available in drive software versions PRG: 1020 and later.
u Setting 1: Water Supply Pump Application
Table 4.5 Water Supply Pump Parameter Settings No. Name Default Setting
Table 4.6 Water Supply Pump: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name
b1-01 | Frequency Reference Selection 1
E1-08 | Middle Output Frequency Voltage
b1-02 | Run Command Selection 1
E2-01 | Motor Rated Current
b1-04 | Reverse Operation Selection
H1-05 | Multi-Function Digital Input Terminal S5 Function Selection
C1-01 | Acceleration Time 1
H1-06 | Multi-Function Digital Input Terminal S6 Function Selection
C1-02 | Deceleration Time 1
H1-07 | Multi-Function Digital Input Terminal S7 Function Selection
E1-03 | V/f Pattern Selection
L5-01 | Number of Auto Restart Attempts
A1-06 Application Selection — PDF page 96
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A1-06 | Application Preset | 0: Disabled 1: Water supply pump 2: Conveyor 3: Exhaust fan 4: HVAC 5: Compressor <1> 8: Conveyor 2 <2> | 0 |
Table4.5 Pump preset A1-06=1 — PDF page 96
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0: V/f Control |
| 2 | b1-04 | Reverse Operation Selection | 1: Reverse Prohibited |
| 3 | C1-01 | Acceleration Time 1 | 1.0 s |
| 4 | C1-02 | Deceleration Time 1 | 1.0 s |
| 5 | C6-01 | Drive Duty Selection | 1: Normal Duty |
| 6 | E1-03 | V/f Pattern Selection | 0FH |
| 7 | E1-07 | Middle Output Frequency | 30.0 Hz |
| 8 | E1-08 | Middle Output Frequency Voltage | 50.0 V |
| 9 | L2-01 | Momentary Power Loss Operation Selection | 1: Enabled |
| 10 | L3-04 | Stall Prevention Selection during Deceleration | 1: Enabled |
Table4.6 Pump user parameters begin — PDF page 96
| Source row | Parameter | Name | Parameter | Name |
|---|---|---|---|---|
| 1 | b1-01 | Frequency Reference Selection 1 | E1-08 | Middle Output Frequency Voltage |
| 2 | b1-02 | Run Command Selection 1 | E2-01 | Motor Rated Current |
| 3 | b1-04 | Reverse Operation Selection | H1-05 | Multi-Function Digital Input Terminal S5 Function Selection |
| 4 | C1-01 | Acceleration Time 1 | H1-06 | Multi-Function Digital Input Terminal S6 Function Selection |
| 5 | C1-02 | Deceleration Time 1 | H1-07 | Multi-Function Digital Input Terminal S7 Function Selection |
| 6 | E1-03 | V/f Pattern Selection | L5-01 | Number of Auto Restart Attempts |
Manual — Pump continuation, conveyor, exhaust fan and HVAC presets — page 97
Source reference: SIEP C71060618F, December 2016, physical PDF page 97. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name No. Parameter Name
u Setting 2: Conveyor Application
Table 4.7 Conveyor: Parameter Settings No. Parameter Name Default Setting
Table 4.8 Conveyor: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name
u Setting 3: Exhaust Fan Application
Table 4.9 Exhaust Fan: Parameter Settings No. Parameter Name Default Setting
Table 4.10 Exhaust Fan: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name
u Setting 4: HVAC Fan Application
Table 4.11 HVAC Fan: Parameter Settings No. Parameter Name Default Setting
4.6 Application Selection
Start-Up Programming & Operation
E1-07 | Middle Output Frequency
− | −
A1-02 | Control Method Selection
C1-02 | Deceleration Time 1
b1-01 | Frequency Reference Selection 1
E2-01 | Motor Rated Current
b1-02 | Run Command Selection 1
L3-04 | Stall Prevention Selection during Deceleration
C1-01 | Acceleration Time 1
E1-08 | Middle Output Frequency Voltage
b1-04 | Reverse Operation Selection
b3-01 | Speed Search Selection at Start
H1-05 | Multi-Function Digital Input Terminal S5 Function Selection
H1-06 | Multi-Function Digital Input Terminal S6 Function Selection
H1-07 | Multi-Function Digital Input Terminal S7 Function Selection
E1-03 | V/f Pattern Selection
L5-01 | Number of Auto Restart Attempts
Table4.6 Pump user parameters continued — PDF page 97
| Source row | Parameter | Name | Parameter | Name |
|---|---|---|---|---|
| 1 | E1-07 | Middle Output Frequency | − | − |
Table4.7 Conveyor preset A1-06=2 — PDF page 97
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0: V/f Control |
| 2 | C1-01 | Acceleration Time 1 | 3.0 s |
| 3 | C1-02 | Deceleration Time 1 | 3.0 s |
| 4 | C6-01 | Drive Duty Selection | 0: Heavy Duty |
| 5 | L3-04 | Stall Prevention Selection during Deceleration | 1: Enabled |
Table4.8 Conveyor user parameters — PDF page 97
| Source row | Parameter | Name | Parameter | Name |
|---|---|---|---|---|
| 1 | A1-02 | Control Method Selection | C1-02 | Deceleration Time 1 |
| 2 | b1-01 | Frequency Reference Selection 1 | E2-01 | Motor Rated Current |
| 3 | b1-02 | Run Command Selection 1 | L3-04 | Stall Prevention Selection during Deceleration |
| 4 | C1-01 | Acceleration Time 1 | − | − |
Table4.9 Exhaust fan preset A1-06=3 — PDF page 97
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0: V/f Control |
| 2 | b1-04 | Reverse Operation Selection | 1: Reverse Prohibited |
| 3 | C6-01 | Drive Duty Selection | 1: Normal Duty |
| 4 | E1-03 | V/f Pattern Selection | 0FH |
| 5 | E1-07 | Middle Output Frequency | 30.0 Hz |
| 6 | E1-08 | Middle Output Frequency Voltage | 50.0 V |
| 7 | L2-01 | Momentary Power Loss Operation Selection | 1: Enabled |
| 8 | L3-04 | Stall Prevention Selection during Deceleration | 1: Enabled |
Table4.10 Exhaust fan user parameters — PDF page 97
| Source row | Parameter | Name | Parameter | Name |
|---|---|---|---|---|
| 1 | b1-01 | Frequency Reference Selection 1 | E1-07 | Middle Output Frequency |
| 2 | b1-02 | Run Command Selection 1 | E1-08 | Middle Output Frequency Voltage |
| 3 | b1-04 | Reverse Operation Selection | E2-01 | Motor Rated Current |
| 4 | b3-01 | Speed Search Selection at Start | H1-05 | Multi-Function Digital Input Terminal S5 Function Selection |
| 5 | C1-01 | Acceleration Time 1 | H1-06 | Multi-Function Digital Input Terminal S6 Function Selection |
| 6 | C1-02 | Deceleration Time 1 | H1-07 | Multi-Function Digital Input Terminal S7 Function Selection |
| 7 | E1-03 | V/f Pattern Selection | L5-01 | Number of Auto Restart Attempts |
Table4.11 HVAC preset A1-06=4 begin — PDF page 97
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0: V/f Control |
| 2 | b1-04 | Reverse Operation Selection | 1: Reverse Prohibited |
Manual — HVAC continuation, compressor and Preset6 — page 98
Source reference: SIEP C71060618F, December 2016, physical PDF page 98. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name Default Setting
Table 4.12 HVAC Fan: User Parameters (A2-01 to A2-16) No. Parameter Name No. Parameter Name
u Setting 5: Compressor Application
Table 4.13 Compressor: Parameter Settings No. Parameter Name Default Setting
Table 4.14 Compressor: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name
u Setting 6: Preset 6
Note: 1. Read the instructions listed in Notes on Controlling the Brake when Using Application Preset 6 on page 99 when using Application Preset 6 2. Perform Auto-Tuning after selecting Application Preset 6. 3. If UL3 appears on the operator display after Auto-Tuning is complete, set L6-01 to “0” to repeat the Auto-Tuning process.
Table 4.15 Preset 6: Parameters and Settings No. Parameter Name Default Setting
4.6 Application Selection
b1-01 | Frequency Reference Selection 1
E1-03 | V/f Pattern Selection
b1-02 | Run Command Selection 1
E1-04 | Maximum Output Frequency
b1-04 | Reverse Operation Selection
E2-01 | Motor Rated Current
C1-01 | Acceleration Time 1
H3-11 | Terminal A2 Gain Setting
C1-02 | Deceleration Time 1
H3-12 | Terminal A2 Bias Setting
C6-02 | Carrier Frequency Selection
L2-01 | Momentary Power Loss Operation Selection
d2-01 | Frequency Reference Upper Limit
L8-03 | Overheat Pre-Alarm Operation Selection
d2-02 | Frequency Reference Lower Limit
o4-12 | kWh Monitor Initialization
E1-07 | Middle Output Frequency
E1-08 | Middle Output Frequency Voltage
− | −
Table4.11 HVAC preset A1-06=4 continued — PDF page 98
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | C6-01 | Drive Duty Selection | 1: Normal Duty |
| 2 | C6-02 | Carrier Frequency Selection | 3: 8.0 kHz |
| 3 | H2-03 | Terminals P2 Function Selection | 39: Watt Hour Pulse Output |
| 4 | L2-01 | Momentary Power Loss Operation Selection | 2: CPU Power Active - Drive will restart if power returns prior to control power supply shut down. |
| 5 | L8-03 | Overheat Pre-Alarm Operation Selection | 4: Operation at lower speed |
| 6 | L8-38 | Carrier Frequency Reduction | 2: Enabled across entire frequency range. |
Table4.12 HVAC user parameters — PDF page 98
| Source row | Parameter | Name | Parameter | Name |
|---|---|---|---|---|
| 1 | b1-01 | Frequency Reference Selection 1 | E1-03 | V/f Pattern Selection |
| 2 | b1-02 | Run Command Selection 1 | E1-04 | Maximum Output Frequency |
| 3 | b1-04 | Reverse Operation Selection | E2-01 | Motor Rated Current |
| 4 | C1-01 | Acceleration Time 1 | H3-11 | Terminal A2 Gain Setting |
| 5 | C1-02 | Deceleration Time 1 | H3-12 | Terminal A2 Bias Setting |
| 6 | C6-02 | Carrier Frequency Selection | L2-01 | Momentary Power Loss Operation Selection |
| 7 | d2-01 | Frequency Reference Upper Limit | L8-03 | Overheat Pre-Alarm Operation Selection |
| 8 | d2-02 | Frequency Reference Lower Limit | o4-12 | kWh Monitor Initialization |
Table4.13 Compressor preset A1-06=5 — PDF page 98
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0: V/f Control |
| 2 | b1-04 | Reverse Operation Selection | 1: Reverse Prohibited |
| 3 | C1-01 | Acceleration Time 1 | 5.0 s |
| 4 | C1-02 | Deceleration Time 1 | 5.0 s |
| 5 | C6-01 | Drive Duty Selection | 0: Heavy Duty |
| 6 | E1-03 | V/f Pattern Selection | 0FH |
| 7 | L2-01 | Momentary Power Loss Operation Selection | 1: Enabled |
| 8 | L3-04 | Stall Prevention Selection during Deceleration | 1: Enabled |
Table4.14 Compressor user parameters — PDF page 98
| Source row | Parameter | Name | Parameter | Name |
|---|---|---|---|---|
| 1 | b1-01 | Frequency Reference Selection 1 | E1-03 | V/f Pattern Selection |
| 2 | b1-02 | Run Command Selection 1 | E1-07 | Middle Output Frequency |
| 3 | b1-04 | Reverse Operation Selection | E1-08 | Middle Output Frequency Voltage |
| 4 | C1-01 | Acceleration Time 1 | E2-01 | Motor Rated Current |
| 5 | C1-02 | Deceleration Time 1 | − | − |
Table4.15 Preset6 settings begin — PDF page 98
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 2: Open Loop Vector Control |
| 2 | b1-01 | Frequency Reference Selection 1 | 0: Operator |
Manual — Preset6 continuation and brake controls — page 99
Source reference: SIEP C71060618F, December 2016, physical PDF page 99. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name Default Setting
<1> Disable L8-05 for single-phase models.
Table 4.16 Preset 6: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name
u Notes on Controlling the Brake when Using Application Preset 6
The frequency detection function is used for controlling the brake. When an external Baseblock command is present while a Run command is active, the frequency reference will be kept as long as the Run command is active. To avoid improper brake operation make sure that frequency detection is set so that the brake does not open during Baseblock (L4-07 = “0”, default). The table below shows how to set up the drive when using output terminals P2-PC as brake control output.
Brake Open/Close Brake Activation Level Control Mode
Function | Parameter | Signal | Parameter | V/f | OLV | OLV for PM
4.6 Application Selection
Start-Up Programming & Operation
A1-02 | Control Method Selection
d1-02 | Frequency Reference 2
b1-01 | Frequency Reference Selection 1
d1-03 | Frequency Reference 3
b6-01 | Dwell Reference at Start
E1-08 | Middle Output Frequency Voltage
b6-02 | Dwell Time at Start
H2-01 | Terminals MA, MB, and MC Function Selection
C1-01 | Acceleration Time 1
L1-01 | Motor Overload Protection Selection
C1-02 | Deceleration Time 1
L4-01 | Speed Agreement Detection Level
C6-02 | Carrier Frequency Selection
L6-02 | Torque Detection Level 1
d1-01 | Frequency Reference 1
L6-03 | Torque Detection Time 1
Table4.15 Preset6 settings continued — PDF page 99
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | b6-01 | Dwell Reference at Start | 3.0 Hz |
| 2 | b6-02 | Dwell Time at Start | 0.3 s |
| 3 | C1-01 | Acceleration Time 1 | 3.0 s |
| 4 | C1-02 | Deceleration Time 1 | 3.0 s |
| 5 | C6-01 | Drive Duty Selection | 0: Heavy Duty |
| 6 | C6-02 | Carrier Frequency Selection | 2: 5 kHz |
| 7 | d1-01 | Frequency Reference 1 | 6.0 Hz |
| 8 | d1-02 | Frequency Reference 2 | 30.0 Hz |
| 9 | d1-03 | Frequency Reference 3 | 60.0 Hz |
| 10 | E1-03 | V/f Pattern Selection | 0FH |
| 11 | H2-02 | Terminals P1 Function Selection | 37: During Frequency Output |
| 12 | H2-03 | Terminals P2 Function Selection | 5: Frequency Detection 2 |
| 13 | L2-03 | Momentary Power Loss Minimum Baseblock Time | 0.3 s |
| 14 | L3-04 | Momentary Power Loss Voltage Recovery Ramp Time | 0: Disabled |
| 15 | L4-01 | Speed Agreement Detection Level | 2.0 Hz |
| 16 | L4-02 | Speed Agreement Detection Width | 0.0 Hz |
| 17 | L6-01 | Torque Detection Selection 1 | 8: UL3 at RUN - Fault |
| 18 | L6-02 | Torque Detection Level 1 | 5% |
| 19 | L6-03 | Torque Detection Time 1 | 0.5 s |
| 20 | L8-05 | Input Phase Loss Protection Selection | 1: Enabled <1> |
| 21 | L8-07 | Output Phase Loss Protection Selection | 1: Enabled |
| 22 | L8-38 | Carrier Frequency Reduction | 1: Enabled below 6 Hz |
| 23 | L8-41 | High Current Alarm Selection | 1: Enabled (alarm is output) |
Table4.16 Preset6 user parameters — PDF page 99
| Source row | Parameter | Name | Parameter | Name |
|---|---|---|---|---|
| 1 | A1-02 | Control Method Selection | d1-02 | Frequency Reference 2 |
| 2 | b1-01 | Frequency Reference Selection 1 | d1-03 | Frequency Reference 3 |
| 3 | b6-01 | Dwell Reference at Start | E1-08 | Middle Output Frequency Voltage |
| 4 | b6-02 | Dwell Time at Start | H2-01 | Terminals MA, MB, and MC Function Selection |
| 5 | C1-01 | Acceleration Time 1 | L1-01 | Motor Overload Protection Selection |
| 6 | C1-02 | Deceleration Time 1 | L4-01 | Speed Agreement Detection Level |
| 7 | C6-02 | Carrier Frequency Selection | L6-02 | Torque Detection Level 1 |
| 8 | d1-01 | Frequency Reference 1 | L6-03 | Torque Detection Time 1 |
Brake sequence source method — PDF page 99
| Source row | Method | Parameter | Required setting | Related parameters | V/f | OLV | OLV/PM |
|---|---|---|---|---|---|---|---|
| 1 | Frequency Detection 2 | L4-07 = 0 | Frequency Detection Level | L4-01 = 1.0 to 3.0 Hz <1> | O | O | − |
| 2 | Frequency Detection 2 | H2-03 = 5 | Frequency Detection Width | L4-02 = 0.0 to 0.5 Hz <2> | O | O | − |
Manual — Brake controls continuation and Preset7 begin — page 100
Source reference: SIEP C71060618F, December 2016, physical PDF page 100. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure4.10 Frequency Detection2. Output frequency versus Time;L4-01 detection level;L4-02 difference indicator;Frequency detection2 ON/OFF. Source geometry retained in original; no unprinted timing or threshold inferred.
Input:S1-SC UP,OFF/ON;S6-SC Fast/Slow,OFF/ON. Output frequency versus Time,0,b6-02,b6-01,L4-01,d1-03,d1-01(Enabled when b1-01=0),b2-01,DC Injection braking. Output:P2-PC Frequency Detection2(H2-03=05),ON/OFF;Holding brake Closed→Open→Closed. Figure4.11 Holding Brake Time Chart. Exact timing geometry/overlap remains original-only; do not infer unnamed durations.
<1> This is the setting recommended when using Open Loop Vector Control. In V/f Control, set the level as the motor rated slip frequency plus 0.5 Hz. Not enough motor torque will be created if this value is set too low, and the load may tend to slip. Make sure this value is greater than the minimum output frequency and greater than the value of L4-02 as shown in the diagram below. If set too high, however, there may be a jolt at start. <2> Hysteresis for Frequency Detection 2 can be adjusted by changing the Frequency Detection Width (L4-02) between 0.0 and 0.5 Hz. If the load slips during stop, make changes in steps of 0.1 Hz until the load no longer slips.
The braking sequence should be designed as follows: • A normally open signal (N.O.) should be used to control the brake so that it is released when terminal P2-PC closes. • When an Up or Down command is entered, the brake should release. • When a fault signal is output, the brake should close.
• When changing the speed using an analog signal, make sure that the source of the frequency reference is assigned to the control circuit terminals (b1-01 = 1). • A sequence to open and close the holding brake appears in the diagram below.
u Setting 7: Preset 7
Table 4.17 Preset 7: Parameters and Settings No. Parameter Name Default Setting
4.6 Application Selection
Table4.17 Preset7 settings begin — PDF page 100
| Source row | Parameter | Name | Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0: V/f Control |
| 2 | b1-01 | Frequency Reference Selection 1 | 0: Operator |
| 3 | C1-01 | Acceleration Time 1 | 3.0 s |
| 4 | C1-02 | Deceleration Time 1 | 3.0 s |
| 5 | C6-01 | Drive Duty Selection | 0: Heavy Duty |
| 6 | C6-02 | Carrier Frequency Selection | 2: 5 kHz |
| 7 | d1-01 | Frequency Reference 1 | 6.0 Hz |
| 8 | d1-02 | Frequency Reference 2 | 30.0 Hz |
| 9 | d1-03 | Frequency Reference 3 | 60.0 Hz |
| 10 | H1-05 | Multi-Function Digital Input Terminal S5 Function | 3: Multi-Step Speed 1 |
| 11 | H1-06 | Multi-Function Digital Input Terminal S6 Function | 4: Multi-Step Speed 2 |
| 12 | H2-02 | Terminals P1 Function Selection | 37: During frequency output |
| 13 | L3-04 | Stall Prevention Selection during Deceleration | 0: Disabled |
| 14 | L8-05 | Input Phase Loss Protection Selection | 1: Enabled <1> |
Manual — Preset7 continuation and Conveyor2 preset — page 101
Source reference: SIEP C71060618F, December 2016, physical PDF page 101. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name Default Setting
<1> Disable L8-05 for single-phase models.
Table 4.18 Preset 7: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name
u Setting 8: Conveyor Application 2
This setting is available in drive software versions PRG: 1020 and later.
Table 4.19 Conveyor 2: Parameters and Settings No. Parameter Name Default Setting
Table 4.20 Conveyor 2: User Parameters (A2-01 to A2-16): No. Parameter Name No. Parameter Name
4.6 Application Selection
Start-Up Programming & Operation
b1-01 | Frequency Reference Selection 1
d1-03 | Frequency Reference 3
C1-01 | Acceleration Time 1
E2-01 | Motor Rated Current
C1-02 | Deceleration Time 1
H1-05 | Multi-Function Digital Input Terminal S5 Function
C6-02 | Carrier Frequency Selection
H1-06 | Multi-Function Digital Input Terminal S6 Function
d1-01 | Frequency Reference 1
H2-01 | Terminals MA, MB, and MC Function Selection
d1-02 | Frequency Reference 2
L1-01 | Motor Overload Protection Selection
A1-02 | Control Method Selection
L3-04 | Stall Prevention Selection during Deceleration
b1-02 | Run Command Selection 1
n3-13 | Overexcitation Deceleration Gain
n3-21 | High-Slip Suppression Current Level
– | –
Table4.17 Preset7 continued — PDF page 101
| Source row | No. | Parameter Name | Default Setting |
|---|---|---|---|
| 1 | L8-07 | Output Phase Loss Protection Selection | 1: Triggered when a single phase is lost |
| 2 | L8-38 | Carrier Frequency Reduction | 1: Enabled below 6 Hz |
| 3 | L8-41 | High Current Alarm Selection | 1: Enabled (alarm output) |
Table4.18 Preset7 user parameters — PDF page 101
| Source row | No. | Parameter Name | No. | Parameter Name |
|---|---|---|---|---|
| 1 | b1-01 | Frequency Reference Selection 1 | d1-03 | Frequency Reference 3 |
| 2 | C1-01 | Acceleration Time 1 | E2-01 | Motor Rated Current |
| 3 | C1-02 | Deceleration Time 1 | H1-05 | Multi-Function Digital Input Terminal S5 Function |
| 4 | C6-02 | Carrier Frequency Selection | H1-06 | Multi-Function Digital Input Terminal S6 Function |
| 5 | d1-01 | Frequency Reference 1 | H2-01 | Terminals MA, MB, and MC Function Selection |
| 6 | d1-02 | Frequency Reference 2 | L1-01 | Motor Overload Protection Selection |
Table4.19 Conveyor2 settings — PDF page 101
| Source row | No. | Parameter Name | Default Setting |
|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0: V/f Control |
| 2 | C1-01 | Acceleration Time 1 | 3.0 s |
| 3 | C1-02 | Deceleration Time 1 | 3.0 s |
| 4 | C6-01 | Drive Duty Selection | 0: Heavy Duty |
| 5 | L3-04 | Stall Prevention Selection during Deceleration | 0: Disabled |
| 6 | n3-13 | Overexcitation Deceleration Gain | 1.4 |
| 7 | n3-21 | High-Slip Suppression Current Level | 150% |
Table4.20 Conveyor2 user parameters — PDF page 101
| Source row | No. | Parameter Name | No. | Parameter Name |
|---|---|---|---|---|
| 1 | A1-02 | Control Method Selection | E2-01 | Motor Rated Current |
| 2 | b1-01 | Frequency Reference Selection 1 | L3-04 | Stall Prevention Selection during Deceleration |
| 3 | b1-02 | Run Command Selection 1 | n3-13 | Overexcitation Deceleration Gain |
| 4 | C1-01 | Acceleration Time 1 | n3-21 | High-Slip Suppression Current Level |
| 5 | C1-02 | Deceleration Time 1 | – | – |
Manual — Auto-Tuning types, prerequisites and load restrictions — page 102
Source reference: SIEP C71060618F, December 2016, physical PDF page 102. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.7 Auto-Tuning
u Types of Auto-Tuning
There are three types of Auto-Tuning. Select the best type of Auto-Tuning for the application. Refer to Auto-Tuning Procedure on page 103.
Type Setting Application Conditions and Benefits Control Mode
Note: Auto-Tuning cannot be performed on permanent magnet motors (IPM, SPM, etc.).
u Before Auto-Tuning the Drive
Check the items below before Auto-Tuning the drive.
n Basic Auto-Tuning Preparations
• Auto-Tuning automatically determines the electrical characteristics of the motor. This is fundamentally different from other types of Auto-Tuning features used in servo systems. • Auto-Tuning requires the user to input data from the motor nameplate. Make sure the information written on the nameplate is available before Auto-Tuning the drive. • For best performance, be sure the drive input supply voltage equals or exceeds the motor rated voltage.
Note: Performance can be enhanced by using a motor with a base voltage that is 20 V (40 V for 400 V class models) lower than the input supply voltage. This may be of special importance when operating the motor above 90% of base speed, where high torque precision is required. • Auto-Tuning is not possible with permanent magnet motors. • To cancel Auto-Tuning, press the STOP key on the LED operator. • Table 4.21 describes digital input and output terminal status during Auto-Tuning.
Table 4.21 Digital Input and Output Operation During Auto-Tuning
Auto-Tuning Type Digital Input Digital Output
WARNING! Sudden Movement Hazard. Do not release the mechanical brake during stationary Auto-Tuning. Inadvertent brake release may cause damage to equipment or injury to personnel. Ensure that the mechanical brake release circuit is not controlled by the drive multi- function digital outputs.
Note: It is recommended that Rotational Auto-Tuning is performed with the load disconnected. Failure to comply could result in improper drive operation. If Rotational Auto-Tuning is performed for a motor coupled to a load, the motor constants will be inaccurate and the motor may exhibit abnormal operation. Disconnect or decouple the motor from the load.
n Notes on Rotational Auto-Tuning
• For optimal performance, Auto-Tuning should only be done with the motor uncoupled from the load for applications requiring high performance over a wide speed range. • If motor and load cannot be uncoupled, the load should be lower than 30% of the rated load. Performing Rotational Auto- Tuning with a higher load will set motor parameters incorrectly, and can cause irregular motor rotation. • Ensure the motor-mounted brake is fully released if installed.
Types of Auto-Tuning — PDF page 102
| Source row | Type | Setting | Application Conditions and Benefits | Control Mode |
|---|---|---|---|---|
| 1 | Rotational Auto-Tuning for V/f Control | T1-01 = 3 | • Assumes the motor can rotate during the Auto-Tuning process • Improves torque compensation, slip compensation, energy savings, and Speed Search performance • Should be performed when Speed Estimation Type Speed Search or Energy Saving is used in V/f Control | V/f Control |
| 2 | Rotational Auto- Tuning for OLV Control | T1-01 = 0 | • Assumes the motor can rotate during the Auto-Tuning process • Achieves high-performance motor control and should be performed whenever Open Loop Vector Control is used | Open Loop Vector Control |
| 3 | Stationary Auto- Tuning for Line-to-Line Resistance (V/f and OLV Control) | T1-01 = 2 | For use when: • The motor cable exceeds 50 m • The motor cable length has been modified after Auto-Tuning has been previously performed • When motor capacity and drive capacity differ | V/f Control, Open Loop Vector Control |
Table4.21 Digital I/O during Auto-Tuning — PDF page 102
| Source row | Auto-Tuning Type | Digital Input | Digital Output |
|---|---|---|---|
| 1 | Rotational Auto-Tuning for V/f Control | Not available | Functions the same as during normal operation |
| 2 | Rotational Auto-Tuning for OLV Control | Not available | Functions the same as during normal operation |
| 3 | Stationary Auto-Tuning for Line-to-Line Resistance | Not available | Maintains the status at the start of Auto-Tuning |
Manual — Stationary tuning, interruption and procedure start — page 103
Source reference: SIEP C71060618F, December 2016, physical PDF page 103. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A – Normal Auto-Tuning Display: run10. B – Auto-Tuning Interrupted: Er-03. Figure4.12. These are source examples, not observed device status; exact LED segment shapes remain original-only.
• Connected machinery should be allowed to rotate the motor.
n Notes on Stationary Auto-Tuning for Terminal Resistance Only
• If the motor cable lead length has been significantly modified after Auto-Tuning has already been performed, perform Stationary Auto-Tuning with the new cables. • Perform when using motor cables longer than 50 m with V/f Control. WARNING! Electrical Shock Hazard. When executing stationary Auto-Tuning for line-to-line resistance only, the motor does not rotate, however, power is applied. Do not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury from electrical shock.
u Auto-Tuning Interruption and Fault Codes
If tuning results are abnormal or the STOP key is pressed before completion, Auto-Tuning will be interrupted and a fault code will be displayed on the digital operator.
u Performing Auto-Tuning
n Auto-Tuning Procedure
Auto-Tuning should generally be performed in the following steps. 1. Refer to Before Auto-Tuning the Drive on page 102. 2. Determine which type of Auto-Tuning best fits the application requirements following Figure 4.13.
4.7 Auto-Tuning
Start-Up Programming & Operation
Manual — Auto-Tuning selection flowchart and procedure — page 104
Source reference: SIEP C71060618F, December 2016, physical PDF page 104. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
START→Select Motor Control Mode A1-02. V/f Control A1-02=0→select V/f pattern E1-03→application allows motor rotation for Auto-Tuning? YES→V/f Rotational Auto-Tuning T1-01=3. NO→motor/drive cable longer than50m? YES→Stationary Auto-Tuning for Line-to-Line Resistance T1-01=2;NO→skip tuning. Open Loop Vector A1-02=2→can load disconnect from motor? YES→Rotational Auto-Tuning T1-01=0. NO→total connected load expected below30%motor rating? YES→notice:Auto-Tuning with connected load possible but may yield less than optimum performance→Rotational Auto-Tuning T1-01=0. NO→Use V/f control A1-02=0 or set motor parameters manually if OLV needed. PM Open Loop Vector A1-02=5→select motor code E5-01 or set motor data manually E5-□□→skip tuning. All branches join:run motor without load/fine tune if needed→connect load/run/fine tune if needed→verify system operates as required→Auto-Tuning finished. Endpoint is a source flowchart label, not actual testing or engineering approval. PDF106 notice gives stricter connected-load prohibition; preserve both, do not infer permission.
- Enter the type of Auto-Tuning to parameter T1-01. 4. Enter the motor nameplate data. 5. Start the Auto-Tuning process when prompted by the drive. 6. If Auto-Tuning was successfully performed, do a test run without the load and make any necessary parameter adjustments. 7. If the test run was successful, do a test run with the load connected and make parameter adjustments if necessary.
4.7 Auto-Tuning
Manual — Auto-Tuning selection and nameplate-entry examples — page 105
Source reference: SIEP C71060618F, December 2016, physical PDF page 105. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u Auto-Tuning Example
The following example illustrates how to perform Rotational Auto-Tuning for Open Loop Vector Control (A1-02 = 2).
n Set the Selected Type of Auto-Tuning
Step Display/Result
n Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 8 in “Set the Selected Type of Auto-Tuning”.
Note: 1. For the details on each setting, Refer to Input Data for Auto-Tuning on page 106. 2. For Stationary Auto-Tuning for Line-to-Line resistance only, set T1-02 and T1-04.
n Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in improper operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.
4.7 Auto-Tuning
Start-Up Programming & Operation
Literal historical source cells. Examples and blank checklists are not current device values or commissioning sign-off; retain complete safety text, preset/firmware conditions and footnotes.
Selected auto-tuning type example — PDF page 105
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | Turn on the power to the drive. The initial display appears. | Right-arrow connector (not a key) | F 0.00; DRV lit |
| 2 | 2. | Press the key until the Auto-Tuning display appears. [Visible key(s), in source order: DOWN.] | Right-arrow connector (not a key) | AtUn |
| 3 | 3. | Press to begin setting parameters. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | T1-01 |
| 4 | 4. | Press to display the value for T1-01. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | 02 |
| 5 | 5. | Press to select the digit to edit. [Visible key(s), in source order: RESET.] | Right-arrow connector (not a key) | 02; selected digit flashes |
| 6 | 6. | Press and set the drive to perform Rotational Auto-Tuning (00). [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | 00 |
| 7 | 7. | Save the setting by pressing . [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | End |
| 8 | 8. | The display automatically returns to the display shown in Step 3. | Right-arrow connector (not a key) | T1-01 |
Entering motor nameplate example — PDF page 105
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | Press to access the motor output power parameter T1-02. [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | T1-02 |
| 2 | 2. | Press to view the default setting. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | 000.40 |
| 3 | 3. | Press to select the digit to edit. [Visible key(s), in source order: RESET.] | Right-arrow connector (not a key) | 000.40; selected digit flashes |
| 4 | 4. | Press and enter the motor power nameplate data in kW. [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | 000.20 |
| 5 | 5. | Press to save the setting. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | End |
| 6 | 6. | The display automatically returns to the display in Step 1. | Right-arrow connector (not a key) | T1-02 |
| 7 | 7. | Repeat Steps 1 through 5 to set the following parameters: • T1-03, Motor Rated Voltage • T1-04, Motor Rated Current • T1-05, Motor Base Frequency • T1-06, Number of Motor Poles • T1-07, Motor Base Speed | Right-arrow connector (not a key) | T1-03 → continuation arrow → T1-10 |
Manual — Starting tuning and T1-00 to T1-02 — page 106
Source reference: SIEP C71060618F, December 2016, physical PDF page 106. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
NOTICE: Never perform Rotational Auto-Tuning for a motor connected to a load. Failure to comply could result in improper drive operation. If Rotational Auto-Tuning is performed for a motor coupled to a load, the motor parameters will be inaccurate and the motor may exhibit abnormal operation. Disconnect or decouple the motor from the load.
Enter the required information from the motor nameplate. Press [UP] to proceed to the Auto-Tuning start display.
Note: These instructions continue from Step 7 in “Enter Data from the Motor Nameplate”.
Step Display/Result
u Input Data for Auto-Tuning
The T1-□□ parameters are used to set the Auto-Tuning input data.
Note: 1. Cycling power to the drive will reset any values set during the Auto-Tuning process to factory defaults. 2. For motors that are to be operated in the field weakening range, first perform the Auto-Tuning with the base data, i.e. the frequency at which the motor is operating with its rated voltage (base frequency). After Auto-Tuning is complete, change the maximum frequency E1-04 to the desired value.
n T1-00: Motor 1/Motor 2 Selection
Selects the motor to be tuned when motor 1/2 switching is enabled, i.e., a digital input is set for function H1-□□ = 16. This parameter is not displayed if motor 1/2 switching is disabled.
No. Name Setting Range Default
Setting 1: Motor 1 Auto-Tuning automatically sets parameters E1-□□ and E2-□□ for motor 1.
Setting 2: Motor 2 Auto-Tuning automatically sets parameters E3-□□ and E4-□□ for motor 2. Make sure that motor 2 is connected to the drive for Auto-Tuning.
n T1-01: Tuning Mode Selection
Sets the type of Auto-Tuning to be used. Refer to Types of Auto-Tuning on page 102 for details on different types of Auto- Tuning.
Setting 0: Rotating Auto-Tuning for Open Loop Vector Control
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotating Auto-Tuning for V/f Control
n T1-02: Motor Rated Power
Used to set the motor rated power according to the motor nameplate value. For optimal performance, the motor rated power should be between 50 and 100% of the drive rating.
<1> The setting range differs based on drive software version. PRG: 1016 and later: 0.03 to 650.00 kW
4.7 Auto-Tuning
Starting Auto-Tuning example — PDF page 106
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | After setting T1-07 as illustrated in the previous section, press and confirm the display is as described below: [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | run10 |
| 2 | 2. | Press [RUN] to activate Auto-Tuning. [DRV] flashes. Note: The first digit indicates which motor is undergoing Auto-Tuning (motor 1 or motor 2). The second digit indicates the type of Auto-Tuning being performed. | Right-arrow connector (not a key) | run10; DRV flashes |
| 3 | 3. | Auto-Tuning finishes in approximately one to two minutes. | Right-arrow connector (not a key) | End |
T1-00 Motor1/2 selection — PDF page 106
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-00 | Motor 1/2 Selection | 1 or 2 | 1 |
T1-01 Auto-Tuning mode — PDF page 106
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-01 | Auto-Tuning Mode Selection | 0, 2 (OLV) 2, 3 (V/f) | 0 (OLV) 2 (V/f) |
T1-02 Motor rated power — PDF page 106
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-02 | Motor Rated Power | <1> | Determined by o2-04 and C6-01 |
Manual — Tuning inputs T1-03 to T1-11 and software restrictions — page 107
Source reference: SIEP C71060618F, December 2016, physical PDF page 107. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
PRG: 1015 and earlier: 0.00 to 650.00 kW
n T1-03: Motor Rated Voltage (T1-01 = 0 or 3)
Used to set the motor rated voltage according to the motor nameplate value. If the motor is used above its base speed, enter the voltage at base speed here. For higher tuning precision and better control performance, enter the motor no-load voltage here if known. The motor no-load voltage is referred as to the voltage needed to operate the motor under no-load condition at its rated speed. Refer to the motor data sheet.
No. Name Setting Range Default
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class drive.
n T1-04: Motor Rated Current
Used to set the motor rated current according to the motor nameplate value. For optimal performance in OLV, the motor rated current should be between 50 and 100% of the drive rating. Enter the current at the motor base speed.
n T1-05: Motor Rated Frequency (T1-01 = 0 or 3)
Used to set the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or the motor is used in the field weakening area, enter the base frequency here. For higher tuning precision and better control performance, enter the motor no-load frequency here if known. The “no-load frequency” refers to the frequency needed to operate the motor under no-load condition at its rated speed. Refer to the motor data sheet.
n T1-06: Number of Motor Poles (T1-01 = 0 or 3)
Used to set the number of motor poles according to the motor nameplate value.
n T1-07: Motor Base Speed (T1-01 = 0 or 3)
Used to set the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is used or the motor is used in the field weakening area, enter the speed at base frequency here.
n T1-11: Motor Iron Loss (T1-01 = 3)
Provides iron loss information for determining the Energy Saving coefficient. If E2-10 has been changed and the power has been cycled, the value set to E2-10 will appear as the default in T1-11. If the value of T1-02 is not changed during Auto- Tuning data input, the drive will select a value that is typical for the motor power entered to T1-02.
4.7 Auto-Tuning
Start-Up Programming & Operation
T1-03 Motor rated voltage — PDF page 107
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-03 | Motor Rated Voltage | 0.0 to 255.5 V <1> | 200.0 V <1> |
T1-04 Motor rated current — PDF page 107
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-04 | Motor Rated Current | 10 to 200% of drive rated current | Determined by o2-04 and C6-01 |
T1-05 Motor base frequency — PDF page 107
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-05 | Motor Base Frequency | 0.0 to 400.0 Hz | 60.0 Hz |
T1-06 Motor poles — PDF page 107
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-06 | Number of Motor Poles | 2 to 48 | 4 |
T1-07 Motor base speed — PDF page 107
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-07 | Motor Base Speed | 0 to 24000 r/min | 1750 r/min |
T1-11 Motor iron loss — PDF page 107
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | T1-11 | Motor Iron Loss | 0 to 65535 W | Determined by o2-04 and C6-01 |
Manual — No-load operation test procedure — page 108
Source reference: SIEP C71060618F, December 2016, physical PDF page 108. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.8 No-Load Operation Test Run
u No-Load Operation Test Run
This section explains how to operate the drive with the motor uncoupled from the load during a test run.
n Before Starting the Motor
Check the following items before operation: • Ensure the area around the motor is safe. • Ensure external emergency stop circuitry is working properly and other safety precautions have been taken.
n During Operation
Check the following items during operation: • The motor should rotate smoothly (i.e., no abnormal noise or oscillation). • The motor should accelerate and decelerate smoothly.
n No-Load Operation Instructions
The following example illustrates a test run procedure using the digital operator.
Note: Before starting the motor, set the frequency reference d1-01 to 6 Hz.
Step Display/Result
No-load operation example — PDF page 108
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | Turn on the power to the drive. The initial display appears. | Right-arrow connector (not a key) | F 0.00; DRV lit |
| 2 | 2. | Press the key to select LOCAL. The LO/RE LED will turn on. [Visible key(s), in source order: LO/RE.] | Right-arrow connector (not a key) | F 0.00; operator graphic with LO/RE LOCAL light |
| 3 | 3. | Press to give the drive a Run command. RUN will light and the motor will rotate at 6 Hz. [Visible key(s), in source order: RUN.] | Right-arrow connector (not a key) | F6.00; RUN light Off → On |
| 4 | 4. | Ensure the motor is rotating in the correct direction and no faults or alarms occur. | Right-arrow connector (not a key) | Motor Forward illustration; actual rotation geometry remains original |
| 5 | 5. | If there is no error in step 4, press to increase the frequency reference. Increase the frequency in 10 Hz increments verifying smooth operation results at all speeds. For each frequency, monitor the drive output current (U1-03) through the LED operator to confirm the current is well below the motor rated current. Example: 6 Hz → 60 Hz. [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | F60.00 |
| 6 | 6. | The drive should operate normally. Press STOP to stop the motor. RUN flashes until the motor comes to a complete stop. [Visible key(s), in source order: STOP.] | Right-arrow connector (not a key) | F60.00; RUN light Flashing → Off |
Manual — Connected-load test procedure — page 109
Source reference: SIEP C71060618F, December 2016, physical PDF page 109. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.9 Test Run with Load Connected
u Test Run with the Load Connected
After performing a no-load test run connect the load and proceed to run the motor and load together.
n Notes on Connected Machinery
• Clear the area around the motor. • The motor should come to a complete stop without problems. • Connect the machinery. • Fasten all installation screws properly. Check that the motor and connected machinery are held in place. • Confirm that the Fast-stop circuit or mechanical safety measures operate correctly. • Be ready to press the STOP button in case of emergency.
n Checklist Before Operation
• The motor should rotate in the proper direction. • The motor should accelerate and decelerate smoothly.
n Operating the Motor under Loaded Conditions
Test run the application similarly to the no-load test procedure when connecting the machinery to the motor. • Check monitor parameter U1-03 to ensure there is no overcurrent. • If the application permits running the load in the reverse direction, try changing motor direction and the frequency reference while watching for abnormal motor oscillation or vibration. • Correct any problems that occurs with hunting, oscillation, or other control-related issues.
Start-Up Programming & Operation
Manual — Parameter verification, backup, access and passwords — page 110
Source reference: SIEP C71060618F, December 2016, physical PDF page 110. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.10 Verifying Parameter Settings and Backing Up Changes
Check changes to parameter settings as a result of Auto-Tuning using the Verify function. Refer to Verifying Parameter Changes: Verify Menu on page 88. Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental modification of parameter settings.
u Backing Up Parameter Values: o2-03
Performing the following procedure stores all parameters settings to drive memory where they can later be recalled if necessary. Set o2-03 to “1” to save parameter changes. This saves all parameter settings, and then returns o2-03 to 0. The drive can now “recall” the saved parameters by performing a “user-initialization” (A1-03 = 1110).
No. | Parameter Name | Description | Setting Range
Default Setting
u Parameter Access Level: A1-01
Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A1-□□ and U□-□□ only. Other parameters are not displayed. Setting the Access Level for “User Parameters” (A1-01 = 1) allows the user to access parameters that have been previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific application.
No. | Parameter Name | Description | Setting Range | Default
u Password Settings: A1-04, A1-05
The user can set a password to the drive to restrict access. The password is selected via parameter A1-05. The selected password must be entered in parameter A1-04 to unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following parameters cannot be viewed or edited until the value programmed into A1-04 correctly matches the value as programmed in parameter A1-05: A1-01, A1-02, A1-03, A1-06 and A2-01 through A2-33.
Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and simultaneously depress the [STOP] key and the [UP] key.
Parameter backup/initialization — PDF page 110
| Source row | No. | Parameter Name | Description | Setting Range | Default Setting |
|---|---|---|---|---|---|
| 1 | o2-03 | User Parameter Default Value | Allows storing of parameter settings as a User Initialization Selection. 0: Saved/Not set 1: Set Defaults - Saves current parameter settings as user default settings. 2: Clear All - Clears the currently saved user settings. After saving the user parameter set value, the items of 1110 (User Parameter Initialize) are displayed in A1-03 (User Parameter Default Value). | 0 to 2 | 0 |
| 2 | A1-03 | Initialize Parameters | Selects a method to initialize the parameters. 0: No Initialize 1110: User Initialize (The user must first program and store desired settings using parameter o2-03) 2220: 2-Wire Initialization (parameter initialized prior to shipment) 3330: 3-Wire Initialization 5550: oPE4 Fault reset | 0 to 5550 | 0 |
Parameter access and user selection — PDF page 110
| Source row | No. | Parameter Name | Description | Setting Range | Default |
|---|---|---|---|---|---|
| 1 | A1-01 | Access Level Selection | Selects which parameters are accessible via the digital operator. 0: Operation only (A1-01, -04, and -06 can be set and monitored. U parameters can be monitored) 1: User Parameters (Only those recently changed among application parameters A2-01 to -16 and A2-17 to -32 can be set and monitored) 2: Advanced Access Level (All parameters can be set and monitored) | 0 to 2 | 2 |
| 2 | A2-01 to A2-32 | User Parameters 1 to 32 | Parameters selected by the user are stored to the User Parameter menu. This includes recently viewed parameters or parameters specifically selected for quick access. If parameter A2-33 is set to 1, recently viewed parameters will be listed between A2-17 and A2-32. Parameters A2-01 through A2-16 must be manually selected by the user. If A2-33 is set to 0, then recently viewed parameters will not be saved to the User Parameter group. The entire A2 parameter group is now available for manual programming. | b1-01 to o2-08 | – |
| 3 | A2-33 | User Parameter Automatic Selection | 0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. 1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access. The most recently changed parameter is registered in A2-17. The second most recently changed parameter is registered in A2-18. | 0, 1 | 1 |
Manual — Parameter copy and software options — page 111
Source reference: SIEP C71060618F, December 2016, physical PDF page 111. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u Copy Function (Optional)
Parameter settings can be copied to another drive to simplify parameter restoration or multiple drive setup. The drive supports the following options:
n USB/Copy Unit (JVOP-181)
The copy unit is an external option connected to the drive to copy parameter settings to another drive. It includes a USB adapter to connect the drive to a PC.
n LCD Operator (JVOP-180)
The LCD operator operates the drive and supports copying, importing, and verifying parameter settings using the parameters o3-01 and o3-02.
Note: Use of the LCD operator requires that the drive is running drive software version PRG: 1012 or later. The LCD operator is not compatible with drive software version PRG: 5010.
n LED Operator (JVOP-182)
The LED operator operates the drive and supports copying, importing, and verifying parameter settings.
Note: Use of the LED operator requires that the drive is running drive software version PRG: 1014 or later. The LED operator is not compatible with version PRG: 5010.
n Drive Wizard Plus
Drive Wizard Plus is a PC software tool for parameter management, monitoring, and diagnosis. Drive Wizard Plus can load, store, and copy drive parameter settings. For details, refer to Help in the Drive Wizard Plus software. The installation files can be obtained at no charge from: U.S.: http://www.yaskawa.com
4.10 Verifying Parameter Settings and Backing Up Changes
Start-Up Programming & Operation
Manual — Test-run checklist1–20 and mode scopes — page 112
Source reference: SIEP C71060618F, December 2016, physical PDF page 112. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
4.11 Test Run Checklist
Review the checklist before performing a test run. Check each item that applies.
No. Checklist Page
Check the items that correspond to the control mode being used.
WARNING! Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on terminal S1 may cause the drive to start.
V/f Control (A1-02 = 0)
Open Loop Vector Control (A1-02 = 2)
PM Open Loop Vector Control (A1-02 = 5)
Proceed to the following checklist after checking items 4 through 9.
Test-run checklist1–3 — PDF page 112
| Source row | Checkbox | No. | Checklist | Page |
|---|---|---|---|---|
| 1 | Unchecked source checkbox | 1 | Thoroughly read the manual before performing a test run. | – |
| 2 | Unchecked source checkbox | 2 | Turn the power on. | 95 |
| 3 | Unchecked source checkbox | 3 | Set the voltage for the power supply to E1-01. | 169 |
Test-run checklist10–20 — PDF page 112
| Source row | Checkbox | No. | Checklist | Page |
|---|---|---|---|---|
| 1 | Unchecked source checkbox | 10 | The [DRV] should illuminate after giving a run command. | – |
| 2 | Unchecked source checkbox | 11 | To give a run command and frequency reference from the LED Digital Operator, press [LO/RE] to set to LOCAL. The LO/RE key lights while LOCAL is displayed. | 89 |
| 3 | Unchecked source checkbox | 12 | If the motor rotates in the opposite direction during the test run, switch two of the drive output terminals (U/T1, V/T2, W/T3). | 95 |
| 4 | Unchecked source checkbox | 13 | Select the correct duty rating (C6-01) for the application. | – |
| 5 | Unchecked source checkbox | 14 | Set the correct values for the motor rated current (E2-01) and the motor protection selection (L1-01) to ensure motor thermal protection. | – |
| 6 | Unchecked source checkbox | 15 | If the run command and frequency reference are provided via the control circuit terminals, set the drive for REMOTE and be sure the LO/RE light is out. | 89 |
| 7 | Unchecked source checkbox | 16 | If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level (0 to 10 V) or the correct current input signal level (4 to 20 mA or 0 to 20 mA). | 89 |
| 8 | Unchecked source checkbox | 17 | Set the proper voltage to terminal A1. (0 to 10 V). | 121 |
| 9 | Unchecked source checkbox | 18 | Set the proper current to terminal A2. (4 to 20 mA or 0 to 20 mA). | 121 |
| 10 | Unchecked source checkbox | 19 | When current input is used, set H3-09 to “2” (4 to 20 mA) or “3” (0 to 20 mA) and set H3-10 to “0”. | – |
| 11 | Unchecked source checkbox | 20 | When current input is used, switch the drive built-in DIP switch S1 from the V-side (OFF) to I-side (ON). | – |
Test-run checklist4–5:V/f A1-02=0 — PDF page 112
| Source row | Checkbox | No. | Checklist | Page |
|---|---|---|---|---|
| 1 | Unchecked source checkbox | 4 | Select the best V/f pattern according to the application and motor characteristics. Example: If using a motor with a rated frequency of 60.0 Hz, set E1-03 to “1”. | – |
| 2 | Unchecked source checkbox | 5 | Perform Auto-Tuning for Energy Savings if using Energy Saving functions. | 102 |
Test-run checklist6–8:OLV A1-02=2 — PDF page 112
| Source row | Checkbox | No. | Checklist | Page |
|---|---|---|---|---|
| 1 | Unchecked source checkbox | 6 | Uncouple the load from the motor when performing Rotational Auto-Tuning. | 102 |
| 2 | Unchecked source checkbox | 7 | Perform Rotational Auto-Tuning. | 102 |
| 3 | Unchecked source checkbox | 8 | The following data entered during Auto-Tuning should match the information written on the motor nameplate: • motor rated output power (kW) → T1-02 • rated voltage (V) → T1-03 • rated current (A) → T1-04 • base frequency (Hz) → T1-05 • number of motor poles → T1-06 • motor rotations per minutes (r/min) → T1-07 | 106 |
Test-run checklist9:PM OLV A1-02=5 — PDF page 112
| Source row | Checkbox | No. | Checklist | Page |
|---|---|---|---|---|
| 1 | Unchecked source checkbox | 9 | Set permanent motor parameters E5-01 through E5-24 | 94 |
Manual — Test-run checklist21 continuation — page 113
Source reference: SIEP C71060618F, December 2016, physical PDF page 113. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Checklist Page
4.11 Test Run Checklist
Start-Up Programming & Operation
Test-run checklist21 continued — PDF page 113
| Source row | Checkbox | No. | Checklist | Page |
|---|---|---|---|---|
| 1 | Unchecked source checkbox | 21 | Set the minimum and maximum frequency references to the desired values. Make the following adjustments if the drive does not operate as expected: Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for input A1, H3-11 for input A2) until the frequency reference value reaches the desired value. Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for input A1, H3-12 for input A2) until the frequency reference value reaches the desired minimum value. | – |
Manual — Language, parameter access and control modes — page 116
Source reference: SIEP C71060618F, December 2016, physical PDF page 116. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
5.1 A: Initialization
The initialization group contains parameters associated with initial setup of the drive. Parameters involving the display language, access levels, initialization, and password are located in this group.
u A1: Initialization
n A1-00: Language Selection
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No. Parameter Name Setting Range Default
Setting 0: English Setting 1: Japanese Setting 2: German Setting 3: French Setting 4: Italian Setting 5: Spanish Setting 6: Portuguese Setting 7: Chinese n A1-01: Access Level Selection
Allows or restricts access to drive parameters.
Setting 0: Operation Only Access is restricted to parameters A1-01, A1-04, A1-06, and all U monitor parameters.
Setting 1: User Parameters Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the Setup mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S) All parameters can be viewed and edited.
Notes on Parameter Access • If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2 parameters cannot be modified. • If a digital input programmed for Program Lockout (H1-□□ = 1B) is enabled, parameter values cannot be modified, even though the A1-01 is set to 1 or 2. • If parameters are changed via serial communication the parameters cannot be changed from the digital operator until an Enter command is received from the serial communication.
n A1-02: Control Method Selection
Selects the Control Method of the drive.
Note: 1. Be sure to perform Auto-Tuning when using one of the vector control modes. 2. Reinitializing the drive does not reset A1-02 to the factory default value.
Setting 0: V/f Control • For general-purpose and multiple motor applications.
A1-00 language — PDF page 116
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A1-00 | Language Selection | 0 to 7 | 0 |
A1-01 access level — PDF page 116
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A1-01 | Access Level Selection | 0 to 2 | 2 |
A1-02 control method — PDF page 116
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A1-02 | Control Method Selection | 0, 2, 5 | 0 |
Manual — Control modes, initialization and nonreset parameters — page 117
Source reference: SIEP C71060618F, December 2016, physical PDF page 117. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
• For use when the motor parameters are unknown and Auto-tuning can not be performed.
Setting 2: Open Loop Vector • For general, variable-speed applications. • For applications requiring precise speed control, quick response, and higher torque at low speeds.
Setting 5: PM Open Loop Vector For operating SPM, IPM, and various permanent magnet motors. Takes advantage of Energy Saving features when operating with derated torque.
n A1-03: Initialize Parameters
Resets parameter settings back to their original default values. After the initialization the parameter automatically returns to 0.
No. Parameter Name Setting Range Default
Setting 0: No Initialization
Setting 1110: User Initialize The modified drive parameters are returned to the values selected as user settings. User settings are stored when parameter o2-03 = “1: Set Defaults”.
Note: A “user-initialization” resets all parameters to a user-defined set of default values that were previously saved to the drive. To clear the user- defined default values, set parameter o2-03 to “2”.
Setting 2220: 2-Wire Initialization Resets all parameters back to their original default settings with digital inputs S1 and S2 configured as forward run and reverse run, respectively. A 2-wire sequence assigns functions to input terminals S1 and S2. Refer to Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence on page 191 for more information.
Setting 3330: 3-Wire Initialization The drive parameters are returned to factory default values with digital inputs S1, S2, and S5 configured as run, stop, and forward/reverse respectively. A 3-wire sequence assigns functions to input terminals S1, S2, and S5. Refer to Setting 0: 3-Wire Sequence on page 185 for more information.
Setting 5550: oPE04 Reset If parameters on a certain drive have been edited and then a different terminal block is installed with different settings saved in its built-in memory, an oPE04 error will appear on the display. To use the parameter settings saved to the terminal block memory, set A1-03 to “5550”.
Notes on Parameter Initialization The parameters shown in Table 5.1 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. The fault history will not be reset when the drive is initialized by A1-03 = 2220 or 3330. Although the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.
Table 5.1 Parameters not Changed by Drive Initialization No. Parameter Name
5.1 A: Initialization
Parameter Details
A1-03 initialization — PDF page 117
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A1-03 | Initialize Parameters | 0, 1110, 2220, 3330, 5550 | 0 |
Table5.1 parameters not changed by initialization begin — PDF page 117
| Source row | No. | Parameter Name |
|---|---|---|
| 1 | A1-00 | Language Selection |
| 2 | A1-02 | Control Method Selection |
| 3 | A1-07 | DriveWorksEZ Function Selection |
| 4 | E1-03 | V/f Pattern Selection |
| 5 | E5-01 | Motor Code Selection (for PM motors) |
| 6 | E5-02 | Motor Rated Capacity (for PM motors) |
| 7 | E5-03 | Motor Rated Current (for PM motors) |
| 8 | E5-04 | Motor Poles (for PM motors) |
| 9 | E5-05 | Motor Stator Resistance (for PM motors) |
| 10 | E5-06 | Motor d Axis Inductance (for PM motors) |
Manual — Nonreset continuation and password lock examples — page 118
Source reference: SIEP C71060618F, December 2016, physical PDF page 118. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name
n A1-04, A1-05: Password and Password Setting
A1-04 is for entering the password when the drive is locked. A1-05 is a hidden parameter used to set the password.
No. Parameter Name Setting Range Default
How to use the Password The user can set a password for the drive to restrict access. The password is set to A1-05 and must be entered to A1-04 to unlock parameter access. Until the correct password is entered, the following parameters cannot be viewed or edited: A1-01, A1-02, A1-03, A1-06, and A2-01 through A2-33. The instructions below demonstrate how to set a new password. Here, the password set is “1234”. An explanation follows on how to enter the password to unlock the parameters.
Table 5.2 Setting the Password for Parameter Lock
Step Display/Result
Table 5.3 Check to see if A1-01 is locked (continuing from step 10 above)
5.1 A: Initialization
Table5.1 parameters not changed by initialization continued — PDF page 118
| Source row | No. | Parameter Name |
|---|---|---|
| 1 | E5-07 | Motor q Axis Inductance (for PM motors) |
| 2 | E5-09 | Motor Induction Voltage Constant 1 (for PM motors) |
| 3 | E5-24 | Motor Induction Voltage Constant 2 (for PM motors) |
| 4 | o2-04 | Drive/kVA Selection |
| 5 | L8-35 | Installation Selection |
A1-04/05 password — PDF page 118
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A1-04 | Password | 0 to 9999 | 0 |
| 2 | A1-05 | Password Setting | 0 to 9999 | 0 |
Table5.2 setting example password1234 — PDF page 118
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | Turn on the power to the drive. The initial display appears. | Right-arrow connector (not a key) | F 0.00; DRV lit |
| 2 | 2. | Scroll to the Parameter Setup display and press . [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | PAr |
| 3 | 3. | Scroll to the right by pressing . [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | A1-01 |
| 4 | 4. | Select the flashing digits by pressing . [Visible key(s), in source order: RESET.] | Right-arrow connector (not a key) | A1-01; selected digits flash |
| 5 | 5. | Select A1-04 by pressing . [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | A1-04 |
| 6 | 6. | Press the key while holding down at the same time. A1-05 will appear. Note: A1-05 is normally hidden, but can be displayed by following the directions listed here. [Visible key(s), in source order: STOP + UP simultaneously.] | Right-arrow connector (not a key) | A1-05; “05” flashes |
| 7 | 7. | Press the key. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | 0000 |
| 8 | 8. | Use , and to enter the password. [Visible key(s), in source order: RESET, DOWN, UP.] | Right-arrow connector (not a key) | 1234 |
| 9 | 9. | Press to save what was entered. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | End |
| 10 | 10. | The display automatically returns to the display shown in step 5. | Right-arrow connector (not a key) | A1-05 |
Table5.3 checking parameter lock — PDF page 118
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | Press to display A1-01. [Visible key(s), in source order: DOWN.] | Right-arrow connector (not a key) | A1-01; “01” flashes |
| 2 | 2. | Press to display the value set to A1-01. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | 0002 |
| 3 | 3. | Press and , making sure that the setting values cannot be changed. [Visible key(s), in source order: DOWN, UP.] | Blank source cell | Blank source cell |
| 4 | 4. | Press to return to the first display. [Visible key(s), in source order: ESC.] | Right-arrow connector (not a key) | PAr |
Manual — Password unlock example, presets and DriveWorksEZ — page 119
Source reference: SIEP C71060618F, December 2016, physical PDF page 119. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table 5.4 Enter the Password to Unlock Parameters (continuing from step 4 above)
Step Display/Result
Note: Parameter settings can be edited after entering the correct password. Performing a 2-Wire or 3-Wire initialization resets the password to “0000”. Reenter the password to parameter A1-05 after drive initialization.
n A1-06: Application Presets
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application Presets automatically sets the required parameters to default values and selects I/Os. In addition, Application Preset parameters are assigned to the list of User Parameters, A2-01 through A2-16. These can be accessed in the Setup Mode and provide quicker application adjustment by eliminating the need to scroll through multiple menus. Refer to Application Selection on page 96 for details on parameter A1-06.
n A1-07: DriveWorksEZ Function Selection
DriveWorksEZ is a software package that can be used to customize the drive functionality or add PLC functionality by the interconnection and configuration of basic software function blocks. The drive performs program created by the user in 2 ms cycles. Parameter A1-07 can be used to enable or disable the DriveWorksEZ program inside the drive.
Note: 1. If DriveWorksEZ assigned functions to any multi-function output terminals, those functions stay set after disabling DriveWorksEZ. 2. Reinitialization using A1-03 does not reset A1-07 to the factory default value. 3. For more information on DriveWorksEZ, contact a Yaskawa representative or the Yaskawa sales department directly.
No. Parameter Name Setting Range Default
Setting 0: DWEZ Disabled Setting 1: DWEZ Enabled Setting 2: Digital Input
5.1 A: Initialization
Parameter Details
Table5.4 unlocking with example password1234 — PDF page 119
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | Press to enter the parameter setup display. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | A1-01 |
| 2 | 2. | Press to select the flashing digits as shown. [Visible key(s), in source order: RESET.] | Right-arrow connector (not a key) | A1-01; “01” flashes |
| 3 | 3. | Press to scroll to A1-04. [Visible key(s), in source order: UP.] | Right-arrow connector (not a key) | A1-04 |
| 4 | 4. | Enter the password “1234”. | Right-arrow connector (not a key) | 1234 |
| 5 | 5. | Press to save the new password. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | End |
| 6 | 6. | Drive returns to the parameter display. | Right-arrow connector (not a key) | A1-04 |
| 7 | 7. | Press and scroll to A1-01. [Visible key(s), in source order: DOWN.] | Right-arrow connector (not a key) | A1-01 |
| 8 | 8. | Press to display the value set to A1-01. If the first "0" blinks, parameter settings are unlocked. [Visible key(s), in source order: ENTER.] | Right-arrow connector (not a key) | 0002 |
| 9 | 9. | Use and to change the value if desired. This is not typical. [Visible key(s), in source order: RESET, UP.] | Blank source cell | Blank source cell |
| 10 | 10. | Press to save the setting, or to return to the previous display without saving changes. [Visible key(s), in source order: ENTER or ESC.] | Right-arrow connector (not a key) | End |
| 11 | 11. | The display automatically returns to the parameter display. | Right-arrow connector (not a key) | A1-01 |
A1-07 DriveWorksEZ — PDF page 119
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A1-07 | DriveWorksEZ Function Selection | 0 to 2 | 0 |
Manual — User parameters and automatic history — page 120
Source reference: SIEP C71060618F, December 2016, physical PDF page 120. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u A2: User Parameters
n A2-01 to A2-32: User Parameters
The user can select 32 parameters and assign them to A2-01 through A2-32. This saves time later scrolling through the parameter menu. The list of User Parameters can also track the most recently edited settings and save those parameters to this list.
No. Parameter Name Setting Range Default
Saving User Parameters To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all parameters (A1-02 = 2). Next assign the parameter number to the User Parameters list by entering it into one of the A2-□□ parameters. By then setting A1-01 to “1”, the access level can be restricted so that users can only set and reference the specific parameters saved as User Parameters.
n A2-33: User Parameter Automatic Selection
A2-33 determines whether or not parameters that have been edited are saved to the User Parameters (A2-17 to A2-32) for quick, easy access.
Setting 0: Do not save list of recently viewed parameters. To manually select the parameters listed in the User Parameter group, set A2-33 to “0”.
Setting 1: Save history of recently viewed parameters. By setting A2-33 to 1, all parameters that were recently edited will be automatically saved to A2-17 through A2-32. A total of 16 parameters are saved in order with the most recently edited parameter set to A2-17. User parameters can be accessed using the Setup mode of the digital operator.
5.1 A: Initialization
A2-01–32 user parameters — PDF page 120
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A2-01 to A2-32 | User Parameters 1 to 32 | A1-02; b1-01 to o2-08 | Depending on A1-06 |
A2-33 automatic selection — PDF page 120
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | A2-33 | User Parameter Automatic Selection | 0 or 1 | Depending on A1-06 |
Manual — Frequency-reference source and analog voltage input — page 121
Source reference: SIEP C71060618F, December 2016, physical PDF page 121. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure5.1: Drive; +V (+10.5 V,20 mA); 2 kΩ;0 to10V;A1 Main Frequency Reference(voltage input);A2 Auxiliary Frequency Reference(voltage/current input);AC Frequency Reference Common. Drawing grounds and wiring geometry remain original-only; no connection inferred beyond labels.
5.2 b: Application
Application parameters configure the source of the frequency reference, the Run command, DC Injection Braking, Speed Search, various timer functions, PID control, the Dwell function, Energy Savings and a variety of other application-related settings.
u b1: Mode of Operation
n b1-01: Frequency Reference Selection 1
Use parameter b1-01 to select the frequency reference source 1 for the REMOTE mode.
Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED on the digital operator will light and the STOP indicator will flash. 2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
No. Parameter Name Setting Range Default
Setting 0: Digital Operator Using this setting, the frequency reference can be input by: • Switching between the multi-speed references in the d1-□□ parameters. • Entering the frequency reference on the operator keypad.
Setting 1: Terminals (Analog Input Terminals) Using this setting, an analog frequency reference can be entered from: • Terminal A1 using a 0 to 10 Vdc signal. • Terminal A2 using either a 0 to 10 Vdc or a 0/4 to 20 mA signal. Note: Terminal A2 supports voltage and current input. The input signal type must be set up by setting DIP switch S1 and adjusting parameter H3-09. Refer to H3-09: Terminal A2 Signal Level Selection on page 207. Entering only the main frequency reference: Using Control Circuit Terminal A1 (0 to 10 Vdc voltage input): Use a circuit such as the one shown in Figure 5.1 or an external 0 to 10 Vdc voltage source like a PLC analog output and set the input level selection for A1 in parameter H3-02 as desired. Refer to H3-02: Terminal A1 Function Selection on page 205.
Figure 5.1 Setting the Frequency Reference by Voltage Input
• Using Control Circuit Terminal A2 (0 to 10 Vdc voltage input) Use the same connection like explained for terminal A1 for terminal A2. Make sure that switch S1 is set to “V” and set the appropriate signal level for terminal A2 by entering 0 or 1 into parameter H3-09. The terminal A2 function must be set to frequency bias by entering 0 into parameter H3-10 (Refer to H3-10: Terminal A2 Function Selection on page 207). • Using Control Circuit Terminal A2 (0/4 to 20 mA current input)
Parameter Details
b1-01 frequency reference1 — PDF page 121
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-01 | Frequency Reference Selection 1 | 0 to 4 | 1 |
Manual — Current input and main/auxiliary switching — page 122
Source reference: SIEP C71060618F, December 2016, physical PDF page 122. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure5.2: DIP switch S1, V / I;Drive;+V (+10.5 V,20mA power supply);A1 Frequency reference;0 or4 to20mA input to A2 Frequency reference bias;AC Analog common. Switch drawing/terminal wiring geometry remains original-only.
Figure5.3:Drive;+V (+10.5 V,20mA);two2kΩ potentiometer labels;A1 Main Frequency Reference(voltage input);A2 Aux Frequency Reference1(voltage input);AC Frequency Reference Common;S5 Multi-Function Digital Input;SC Digital Input Common. Physical wiring/ground/switch geometry retained in original; no inferred electrical connection.
Connect input A2 to an external current source such as the one shown in Figure 5.2. Make sure that switch S1 is set to “I” and set the appropriate signal level for terminal A2 by entering 2 (4 to 20 mA) or 3 (0 to 20 mA) into parameter H3-09. The terminal A2 function must be set to frequency bias by entering 0 into parameter H3-10 (Refer to H3-10: Terminal A2 Function Selection on page 207).
Figure 5.2 Setting the Frequency Reference by Current Input
Switching between Main/Auxiliary Frequency References The frequency reference input can be switched between terminal A1 (main) and terminal A2 (auxiliary). When using this function: • Make sure that b1-01 is set to “1” (Frequency reference from analog input). • Set the terminal A2 function to auxiliary frequency (H3-10 = 2). • Set one digital input to multi-speed 1 (H1-□□ = 3, default for S5).
The frequency reference value is read from • Terminal A1 when the digital input set for multi-speed 1 is open. • Terminal A2 when the digital input set for multi-speed 1 is closed. Figure 5.2 shows a wiring example for main/auxiliary reference switching using digital input S5.
Figure 5.3 Switching between Analog Reference 1 and 2
5.2 b: Application
Manual — Serial/option/pulse reference and run-command source — page 123
Source reference: SIEP C71060618F, December 2016, physical PDF page 123. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 2: MEMOBUS/Modbus Communications This setting requires that the frequency reference is entered via the RS-485/422 serial communications port (control terminals R+, R-, S+, S-, Protocol: MEMOBUS/Modbus). For instructions, Refer to MEMOBUS/Modbus Communications on page 431.
Setting 3: Option Card This setting requires that the frequency reference is entered via an option board plugged into connector CN5 on the drive control board. Consult the manual supplied with the option board for instructions on integrating the drive with the communication system.
Note: If the frequency reference source is set for an option PCB (b1-01 = 3) but an option board is not installed in CN5, an oPE05 Programming Error will be displayed on the digital operator and the RUN command will not be accepted.
Setting 4: Pulse Train Input If b1-01 is set to 4 the frequency reference must be provided by a pulse train signal at terminal RP that complies with the following specification.
Pulse Train Input Specifications
Verifying Pulse Train is Working Properly • Make sure that b1-01 is set to 4 and H6-01 is set to 0. • Set the pulse input scaling H6-02 to the pulse train frequency value that equals 100% frequency reference. • Enter a pulse train signal to terminal RP and check if the correct frequency reference is displayed. Try also with different pulse train input frequencies.
n b1-02: Run Command Selection 1
Parameter b1-02 determines the Run and Stop command source 1 in the REMOTE mode.
WARNING! Sudden Movement Hazard. Clear personnel, secure equipment, and check sequence and safety circuitry before starting the drive. Failure to comply could result in death or serious injury from moving equipment.
No. Parameter Name Setting Range Default
Setting 0: Digital Operator Using this setting, the RUN and STOP keys on the operator keypad will start and stop the motor. The LED in the LO/RE key will be on to indicate that the Run command is assigned to the operator. The example below shows how the drive can be operated if b1-02 is set to 0.
Step Display/Result
Setting 1: Control Circuit Terminal This setting requires that the Run and Stop commands are entered from the digital input terminals. The following sequences can be used:
5.2 b: Application
Parameter Details
Pulse train input specifications — PDF page 123
| Source row | Specification | Value |
|---|---|---|
| 1 | Response Frequency | 0.5 to 32 kHz |
| 2 | Duty Cycle | 30 to 70% |
| 3 | High Level Voltage | 3.5 to 13.2 V |
| 4 | Low Level Voltage | 0.0 to 0.8 V |
| 5 | Input Impedance | 3 kΩ |
b1-02 run-command source1 — PDF page 123
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-02 | Run Command Selection 1 | 0 to 3 | 1 |
Digital operator run/stop example — PDF page 123
| Source row | Step | Description | Connector graphic | Display/Result |
|---|---|---|---|---|
| 1 | 1. | Turn on the power to the drive. The initial display appears. | Right-arrow connector (not a key) | F 0.00; DRV lit |
| 2 | 2. | Set the frequency reference to F6.00 (6 Hz). | Right-arrow connector (not a key) | F6.00 |
| 3 | 3. | Press the key to start the motor. The RUN indicator LED will light and the motor will begin rotating at 6 Hz. [Visible key(s), in source order: RUN.] | Right-arrow connector (not a key) | F6.00; RUN light off → on |
| 4 | 4. | Press the key to stop the motor. The RUN light will flash until the motor comes to a complete stop. [Visible key(s), in source order: STOP.] | Right-arrow connector (not a key) | RUN light flashing → off |
Manual — Run-command sequences and stopping modes — page 124
Source reference: SIEP C71060618F, December 2016, physical PDF page 124. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure5.4:Run Command ON→OFF;Maximum Output Frequency;Decelerates according to specified deceleration time;Zero Speed Level(b2-01);Decel Time(C1-02,etc.);DC Injection Braking;DC Injection Current(b2-02);DC Braking Time at Stop(b2-04). Exact waveform geometry and unprinted times remain original-only.
• 2-Wire sequence 1: Two inputs (FWD/Stop-REV/Stop). Initializing the drive by setting A1-01 = 2220, presets the terminals S1 and S2 to these functions. This is the default setting of the drive. Refer to Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence on page 191. • 2-Wire sequence 2: Two inputs (Start/Stop-FWD/REV). Refer to Setting 42/43: Run and Direction Command for 2-Wire Sequence 2 on page 191. • 3-Wire sequence: Inputs S1, S2, S5 (Start-Stop-FWD/REV). Initialize the drive by setting A1-01 = 3330 presets the terminals S1, S2 and S5 to these functions. Refer to Setting 0: 3-Wire Sequence on page 185.
Setting 2: MEMOBUS/Modbus Communications To issue a Run command via serial communications, set b1-02 to “2” and connect the RS-485/422 serial communication cable to R+, R-, S+, and S- on the removable terminal block. Refer to MEMOBUS/Modbus Communications on page 431.
Setting 3: Option Card To issue the Run command via the communication option board, set b1-02 to “3” and plug a communication option board into the 2CN port on the control PCB. Refer to the manual supplied with the option board for instructions on integrating the drive into the communication system.
Note: If b1-01 is set to 3, but an option board is not installed in 2CN, an oPE05 operator programming error will be displayed on the digital operator and the drive will not run.
n b1-03: Stopping Method Selection
Select how the drive stops the motor when a Stop command is entered or when the Run command is removed.
No. Parameter Name Setting Range Default
Setting 0: Ramp to Stop When a Stop command is issued or the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the active deceleration time. The default deceleration time is set to parameter C1-02. DC Injection braking (for IM control) or Short Circuit Braking (PM Open Loop Vector) can be applied at the end of the ramp in order to completely stop high inertia loads. Refer to b2: DC Injection Braking on page 128 for details.
Figure 5.4 Ramp to Stop
Setting 1: Coast to Stop When a Stop command is issued or the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to stop where the stopping time is determined by the inertia and the friction in the driven system.
5.2 b: Application
b1-03 stopping method — PDF page 124
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-03 | Stopping Method Selection | 0 to 3 | 0 |
Manual — Coast and DC-injection stopping; source formula — page 125
Source reference: SIEP C71060618F, December 2016, physical PDF page 125. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure5.5:Run Command ON→OFF;Output Frequency;Drive output frequency is shut off;Motor rpm. Curve geometry remains original-only; no unprinted time or ramp inferred.
Figure5.6:Run Command ON→OFF;Output Frequency;Minimum Baseblock Time(L2-03);DC Injection Braking;Motor Speed;DC Injection Braking Time at Stop(b2-04)*;DC Braking Current(b2-02). Actual waveform geometry remains original-only. Source formula below qualifies time; this function unavailable with PM Open Loop Vector.
DC Injection brake time = (b2-04 · 10 · Output frequency) / Max. output frequency(E1-04). Source numerator and denominator preserved from actual fraction; no numerical result or extra unit inferred.
Figure 5.5 Coast to Stop
Note: After a stop is initiated, any subsequent Run command that is entered will be ignored until the Minimum Baseblock Time (L2-03) has expired. Do not attempt to start the motor again until it has come to a complete stop. To start the motor before it has stopped completely, use DC Injection at start (Refer to b2-03: DC Injection Braking Time at Start on page 129) or Speed Search (Refer to b3: Speed Search on page 130).
Setting 2: DC Injection Braking to Stop When the Run command is removed, the drive will baseblock (turn off its output) for the minimum baseblock time (L2-03). Once the minimum baseblock time has expired, the drive will brake the motor by injecting DC current into the motor windings. The stopping time will be reduced as compared to coast to stop. The level of DC Injection current is set by parameter b2-02 (default = 50%).
Note: This function is not available when using PM Open Loop Vector.
Figure 5.6 DC Injection Braking to Stop
The time for DC Injection Braking is determined by the value set to b2-04 and by the output frequency at the time the Run command is removed. It can be calculated by:
5.2 b: Application
Parameter Details
Manual — Stopping time graphs and reverse operation — page 126
Source reference: SIEP C71060618F, December 2016, physical PDF page 126. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Axes: DC Injection braking time; Output frequency when Stop command was entered. Source labels b2-04, b2-04 × 10, 10%, 100% (Maximum output frequency). The drawn line is flat at b2-04 up to 10%, then rises to b2-04 × 10 at 100%; retain this graph qualification alongside the PDF125 formula without deriving a new formula. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Run Command ON → OFF → ON → OFF → ON; Output Frequency; Drive output voltage interrupted; Operation Wait Time t. A run command inside the wait interval is not accepted; source prose requires cycling after it expires. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Operation wait time t; Selected decel time; Minimum Baseblock Time (L2-03); Min. output frequency; Output frequency when Stop command is entered; 100% (Max. output frequency). Source line rises from the minimum baseblock level to the selected decel time. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Note: If an overcurrent (oC) fault occurs during DC Injection Braking to stop, lengthen the minimum baseblock time (L2-03) until the fault no longer occurs.
Setting 3: Coast to Stop with Timer When the Run command is removed, the drive will turn off its output and the motor will coast to stop. If a Run command is input before the operation wait time t expires, the drive will not rotate the motor and the Run command will need to be cycled before operation can occur.
The operation wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
Figure
n b1-04: Reverse Operation Selection
For some applications, reverse motor rotation is not appropriate and may even cause problems (e.g., air handling units, pumps, etc.). Setting parameter b1-04 to 1 instructs the drive to ignore any Reverse run commands.
No. Parameter Name Setting Range Default
Setting 0: Reverse Operation Enabled Possible to operate the motor in both forward and reverse directions.
5.2 b: Application
b1-04 / Reverse Operation Selection — PDF page 126
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-04 | Reverse Operation Selection | 0 or 1 | 0 |
Manual — Reverse, control-source switching and programming-mode run — page 127
Source reference: SIEP C71060618F, December 2016, physical PDF page 127. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 1: Reverse Operation Disabled Drive disregards a Reverse run command or a negative frequency reference.
n b1-07: LOCAL/REMOTE Run Selection
The drive has the following three separate control sources that can be switched using digital inputs or the LO/RE key on the digital operator (for details Refer to Setting 1: LOCAL/REMOTE Selection on page 185, Refer to Setting 2: External Reference 1/2 Selection on page 186 and Refer to o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection on page 248): • LOCAL - The digital operator is used to set the reference and the Run command. • REMOTE -Reference 1: The settings of b1-01 and b1-02 determine where the frequency reference and Run command are input from. • REMOTE - Reference 2: The settings of b1-15 and b1-16 determine where the frequency reference and Run command are input from. When switching from LOCAL to REMOTE, or between Reference 1 and Reference 2, the Run command may already be present at the location the source was switched to. Parameter b1-07 can be used to determine how the Run command is treated in this case.
No. Parameter Name Setting Range Default
Setting 0: Run Command Must Be Cycled If the Run command is issued differently in the old and new control source (e.g. old - terminals, new - serial communications) and it is active at the new source when switching takes place, the drive will either not start or it will stop if it was running before. The Run command has to be cycled to start from the new control source.
Setting 1: Continue Running If the Run command is active at the new control source, the drive starts or continues running. There is no need to cycle the Run command.
WARNING! The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel away from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
n b1-08: Run Command Selection while in Programming Mode
As a safety precaution, the drive will not normally respond to a Run input when the digital operator is being used to adjust parameters in the Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning). If required by the application b1-08 can be used to changed this functionality.
Setting 0: Disabled A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled A Run command is accepted in any digital operator mode.
Setting 2: Prohibit Programming During Run It is not possible to enter the Programming Mode as long as the drive output is active.
n b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Setting 0: Standard Phase Order
Setting 1: Switched Phase Order
5.2 b: Application
Parameter Details
b1-07 / LOCAL/REMOTE Run Selection — PDF page 127
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-07 | LOCAL/REMOTE Run Selection | 0 or 1 | 0 |
b1-08 / Run Command Selection while in Programming Mode — PDF page 127
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-08 | Run Command Selection while in Programming Mode | 0 to 2 | 0 |
b1-14 / Phase Order Selection — PDF page 127
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-14 | Phase Order Selection | 0 or 1 | 0 |
Manual — Second references, power-up and braking threshold — page 128
Source reference: SIEP C71060618F, December 2016, physical PDF page 128. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n b1-15: Frequency Reference Selection 2
Refer to b1-01: Frequency Reference Selection 1 on page 121 for details. The value set to b1-15 is used as Frequency Reference 2 when one of the multi-function input terminals set for Frequency Reference Switching (H1-□□ = 2) closes. Refer to Setting 2: External Reference 1/2 Selection on page 186 for instructions on how this function works.
No. Parameter Name Setting Range Default
n b1-16: Run Command Selection 2
Refer to b1-02: Run Command Selection 1 on page 123 for details. The value set to b1-16 is used as Run Command Source 2 when one of the multi-function input terminals set for Frequency Reference Switching (H1-□□ = 2) closes. Refer to Setting 2: External Reference 1/2 Selection on page 186 for instructions on how this function works.
n b1-17: Run Command at Power Up
This parameter is used to determine whether an external Run command that is active during power up of the drive will start the drive or not.
Setting 0: Run Command at Power Up is not Issued The Run command has to be cycled to start the drive.
Note: For safety reasons, the drive is initially set up not to accept a Run command at power up (b1-17 = "0"). If a Run command is issued at power up, the RUN indicator LED will flash quickly. Change parameter b1-17 to 1 if a Run command active at power up shall be accepted by the drive.
Setting 1: Run Command and Power Up is Issued An external Run command active during power up is issued and the drive starts to operate the motor as soon as it gets ready for operation (i.e. once the internal start up process is complete).
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to powering up the drive. Failure to comply may cause serious injury.
u b2: DC Injection Braking
These parameters determine how the DC Injection Braking/Short Circuit Braking feature operates. Parameters involving the starting frequency, current level, braking time are located here.
n b2-01: DC Injection Braking Start Frequency
Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0). Sets the starting frequency for: • DC Injection Braking at stop in V/f and OLV control. • Short Circuit Braking at stop in PM OLV control.
No. Name Setting Range Default
When the output frequency while ramping to stop drops below b2-01, the drive begins DC Injection/Short Circuit Braking in order to completely stop the motor at the end of deceleration. If b2-01 < E1-09 (Minimum Frequency), then DC Injection/ Short Circuit Braking begins at the frequency set to E1-09.
<1> The upper limit for the setting range is determined by E1-04.
5.2 b: Application
b1-15 / Frequency Reference Selection 2 — PDF page 128
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-15 | Frequency Reference Selection 2 | 0 to 4 | 0 |
b1-16 / Run Command Selection 2 — PDF page 128
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-16 | Run Command Selection 2 | 0 to 3 | 0 |
b1-17 / Run Command at Power Up — PDF page 128
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b1-17 | Run Command at Power Up | 0 or 1 | 0 |
b2-01 / DC Injection Braking Start Frequency — PDF page 128
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b2-01 | DC Injection Braking Start Frequency | 0.0 to 10.0 Hz | 0.5 Hz |
E1-09 / Minimum Output Frequency — PDF page 128
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E1-09 | Minimum Output Frequency | <1> 0.0 to 400.0 Hz | Determined by A1-02 and E1-03 and on E5-01 in OLV/PM. |
Manual — DC injection, flux and PM short-circuit braking — page 129
Source reference: SIEP C71060618F, December 2016, physical PDF page 129. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency; b2-01 DC Injection Braking start frequency; braking time; b2-04. No unstated braking time or braking region value inferred. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
n b2-02: DC Injection Braking Current
Sets the DC Injection Braking current as a percentage of the drive rated current. If set to larger than 50%, the carrier frequency is automatically reduced to 1 kHz.
No. Name Setting Range Default
The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft. Increasing the current level will increase the amount of heat generated by the motor windings. This parameter should only be increased to the level necessary to hold the motor shaft.
n b2-03: DC Injection Braking Time at Start
Sets the time of DC Injection Braking at start. It can be used to stop a coasting motor before restarting it or to apply a braking torque at start. Disabled when set to 0.00 s.
Note: Before starting an uncontrolled rotating motor (e.g. a fan motor driven by windmill effect), DC Injection or Speed Search should be used to either stop the motor or detect its speed before starting it. Otherwise motor stalling and other faults can occur.
n b2-04: DC Injection Braking Time at Stop
This parameter works in combination with b2-01, and sets the DC Injection Braking time at stop. Used to completely stop a motor with high inertia load after ramp down. Increase the setting if the motor tends to coast by inertia after a stop.
n b2-08: Magnetic Flux Compensation Value
Sets the magnetic flux compensation as a percentage of the no-load current value (E2-03) and can be used to increase the motor flux when the motor is started up.
This parameter allows the magnetizing motor flux to be boosted when starting the motor and thereby facilitate a quick ramp- up of the torque reference and magnetizing current reference in order to reduce motor slip during start. This flux level will be applied below the minimum output frequency set to E1-09 until the DC Injection time at start (b2-03) expires. It may be used to compensate for reduced starting torque due to motor circuit inefficiencies.
n b2-12: Short Circuit Brake Time at Start
Short-Circuit braking can be used in Open Loop Vector for PM motors. By shorting all three motor phases it produces a braking torque in the motor and can be used to stop a coasting motor before starting it. Parameter b2-12 sets the time for Short-Circuit Brake operation at start. Disabled when set to 0.00 s.
n b2-13: Short Circuit Brake Time at Stop
The Short-Circuit braking described for parameter b2-12 can also be applied at the end of deceleration in order to completely stop high inertia loads. Short circuit braking is initiated when the output frequency falls below the higher of the values b2-01 and E1-09.
5.2 b: Application
Parameter Details
b2-02 / DC Injection Braking Current — PDF page 129
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b2-02 | DC Injection Braking Current | 0 to 75% | 50% |
b2-03 / DC Injection Braking Time at Start — PDF page 129
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b2-03 | DC Injection Braking Time at Start | 0.00 to 10.00 s | 0.50 s |
b2-04 / DC Injection Braking Time at Stop — PDF page 129
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b2-04 | DC Injection Braking Time at Stop | 0.00 to 10.00 s | 0.50 s |
b2-08 / Magnetic Flux Compensation Value — PDF page 129
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b2-08 | Magnetic Flux Compensation Value | 0 to 1000% | 0% |
b2-12 / Short Circuit Brake Time at Start — PDF page 129
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b2-12 | Short Circuit Brake Time at Start | 0.00 to 25.50 s | 0.00 s |
Manual — Short-circuit stop and Speed Estimation methods — page 130
Source reference: SIEP C71060618F, December 2016, physical PDF page 130. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
AC power supply OFF → ON; Output frequency starts at the detected speed, then selected frequency reference; Output current; Several milliseconds; Min. Baseblock Time (L2-03); b3-05 <1>. Footnote below qualifies waiting after power restoration and longer interruptions. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Parameter b2-13 sets the time for Short-Circuit brake operation at stop. Disabled when set to 0.00 s.
No. Name Setting Range Default
u b3: Speed Search
The Speed Search function allows the drive to detect the speed of a rotating motor shaft that is driven by external forces (e.g. fan rotating by windmill effect or motor driven by load inertia). The motor operation can be directly started from the speed detected without needing to stop the machine before. Example: When a momentary loss of power occurs, the drive output shuts off. This results in a coasting motor. When power returns, the drive can find the speed of the coasting motor and restart it directly. The drive offers two types of Speed Search, Speed Estimation and Current Detection. Both methods are explained below followed by a description of all relevant parameters.
n Speed Estimation Type Speed Search (b3-24 = 1)
This method can be used for a single motor connected to a drive. It should not be utilized if the motor is one or more frame sizes smaller than the drive, at motor speeds above 130 Hz, or when using a single drive to operate more than one motor. The Speed Estimation type distinguishes two kinds of operation, Back EMF voltage estimation and DC current injection.
Back EMF Voltage Estimation This method is used by Speed Search after short Baseblock (e.g. a power loss where the drives CPU kept running and the Run command was kept active). Here the drive estimates the motor speed by analyzing the back EMF voltage. It outputs the estimated frequency and increases the voltage using the time constant set in parameter L2-04. After that the motor is accelerated or decelerated to the frequency reference starting from the detected speed.
<1> Once AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than the Minimum Baseblock Time L2-03, the drive will wait for b3-05 after the power has returned before starting Speed Search.
Current Injection This method is used when there is no detectable back EMF, e.g. after longer power losses, when Speed Search is applied with the Run command (b3-01 = 1) or if an External Search command is used. It injects the DC current set in b3-06 to the motor and detects the speed by measuring the current feedback. The drive outputs the detected frequency and increases the voltage using the time constant set in parameter L2-04. If the resulting current is higher than the level in b3-02 the output frequency is reduced. When the current becomes lower than b3-02 the motor speed is assumed to be found and the drive starts to accelerate or decelerate to the frequency reference.
5.2 b: Application
b2-13 / Short Circuit Brake Time at Stop — PDF page 130
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b2-13 | Short Circuit Brake Time at Stop | 0.00 to 25.50 s | 0.50 s |
Manual — Speed Search start and Current Detection scope — page 131
Source reference: SIEP C71060618F, December 2016, physical PDF page 131. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Run command OFF → ON; Output frequency starts at the detected speed; Decelerates at the Speed Search decel time set to b3-03; Waits for L2-04 × 2 time; Frequency reference set to the drive; Output current b3-02; 1.0 s; Min. Baseblock Time (L2-03) <1>. PDF131 footnote makes b3-05 the lower limit. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
<1> The wait time for Speed Search (b3-05) determines the lower limit.
Note: If the Run command is quickly switched off and then back on again when the drive is set to “Coast to stop” as the stopping method, Speed Search will operate as shown in Figure 5.11. Notes on Using Speed Estimation Type Speed Search • Auto-Tuning needs to be first performed if you plan to use Speed Estimation. Perform Auto-Tuning again if the there is a change in the cable length between the drive and motor. • Use Current Detection to search for speeds beyond 130 Hz or if the application is running multiple motors from the same drive, or if the motor is considerably smaller than the capacity of the drive. • Speed Estimation may have trouble finding the actual speed if the motor cable very long. Current Detection should be used in such situations. • Use Current Detection instead of Speed Estimation when operating motors smaller than 1.5 kW. Speed Estimation can end up stopping smaller motors as it might not be able to detect the speed or rotation direction of such small motors. • Use Short circuit Braking instead of Speed Estimation when using Open Loop Vector Control for PM motors along with a fairly long motor cable. • Use Short circuit Braking instead of Speed Estimation if attempting to find the speed of a motor coasting faster than 120 Hz in Open Loop Vector Control for PM motors.
n Current Detection Type Speed Search (b3-24 = 0)
Current Detection Speed Search can be applied to any motor. Be aware that sudden acceleration may occur when using Current Detection with relatively light loads. This method detects the motor speed by reducing the output frequency and measuring the current. The frequency reduction starts from the maximum output frequency or from the set frequency reference. As long as the output frequency is higher than the rotor speed, the slip will cause a high current. The closer the output frequency comes to the rotor speed, the lower the current draw will be. When the output current drops below the level as set in b3-02, the output frequency stops decreasing and normal operation resumes. The following time chart illustrates how Current Detection Speed Search operates after a momentary power loss:
5.2 b: Application
Parameter Details
Manual — Current Detection timing and activation methods — page 132
Source reference: SIEP C71060618F, December 2016, physical PDF page 132. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
AC power supply OFF → ON; Output frequency before momentary power loss; Decel time set to b3-03; Waits for L2-04 × 2 time; Selected frequency reference; Output current; Speed Search operation current set to b3-02; Min. Baseblock Time (L2-03); b3-05. Source waiting-time qualifications and PM exclusion below remain essential. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Run command OFF → ON; Output frequency: Max. output frequency or the specified frequency reference; Decel time set to b3-03; Waits for L2-04 × 2 time; Selected frequency reference; Output current b3-02; Minimum Baseblock Time (L2-03). Actual source notes qualify wait time and motor modes. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Note: After power is restored, the drive waits until the time set to b3-05 has passed before performing Speed Search. Thereby the Speed Search may start not at the end of L2-03 but even later. When Speed Search is applied using an external Search command or automatically with the Run command, the drive waits for the minimum baseblock time L2-03 before Speed Search is started. If L2-03 is smaller than the time set in parameter b3-05, b3-05 is used as the wait time.
Note: When the Run command is set the drive waits until the Speed Search Wait Time (b3-05) before Speed Search is performed, even if the Minimum Baseblock Time is set to smaller values than b3-05. Notes on Using Current Detection Type Speed Search • Increase the voltage recovery ramp time set to L2-04 if a Uv1 fault occurs when performing Current Detection Speed Search. • Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection Speed Search. • Current Detection Speed Search is not available when using Open Loop Vector Control for PM motors. • Increase the minimum baseblock time set to L2-03 if an overcurrent fault occurs when performing Speed Search after power is restored following a momentary power loss.
n Activation of Speed Search
Speed Search can be activated as described below. Independent of the activation method the Speed Search type must be selected in parameter b3-24. 1. Automatically at every Run command (Refer to b3-01: Speed Search Selection at Start on page 133). With this setting external Speed Search commands are disregarded.
- By digital inputs: The following input functions for H1-□□ can be used.
5.2 b: Application
Manual — Speed Search activation and b3-01 to b3-05 — page 133
Source reference: SIEP C71060618F, December 2016, physical PDF page 133. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table 5.5 Speed Search Activation by Digital Inputs
Setting Description b3-24 = 0 b3-24 = 1
To activate Speed Search by a digital input the input must always be set together with the Run command. 3. After automatic fault restart Set the number of maximum fault restarts in parameter L5-01 higher than 0.
After momentary power loss The following parameter settings are necessary: • Enable Power Loss Ride-Thru selection by setting L2-01 to 1 (enabled) or 2 (enabled during CPU operation). Refer to L2-01: Momentary Power Loss Operation Selection on page 218. • Set the number of maximum fault restarts in parameter L5-01 higher than 0.
After baseblock is released The drive will resume the operation starting with Speed Search if the Run command is present and the output frequency is above the minimum frequency when the Baseblock command (H1-□□ = 8 or 9, N.O. and N.C., respectively) is released.
n b3-01: Speed Search Selection at Start
Selects if Speed Search is automatically performed when a Run command is issued.
No. Parameter Name Setting Range Default
Setting 0: Disabled Speed Search is not automatically performed. It can be activated using a digital input.
Setting 1: Enabled Speed Search is performed with every Run command.
n b3-02: Speed Search Deactivation Current
Sets Speed Search operating current as a percentage of the drive rated current. If the current falls below this level while performing Current Detection Speed Search then Speed Search will be finished and normal operation will resume. Normally there is no need to change this setting. If the drive won’t run after a restart, lower this value.
No. Name Setting Range Default
Note: When parameter A1-02 = 0 (V/f Control) the factory default setting is 120. When parameter A1-02 = 2 (Open Loop Vector) the factory default setting is 100.
n b3-03: Speed Search Deceleration Time
Parameter b3-03 sets the output frequency reduction ramp used by Current Detection Speed Search (b3-24 = 0) and by the Current Injection Method of Speed Estimation (b3-24 = 1). The time entered into b3-03 will be the time to decelerate from maximum frequency (E1-04) to minimum frequency (E1-09).
n b3-05: Speed Search Delay Time
In cases where an output contactor is used between the drive and the motor, the contactor must be closed before Speed Search can be performed. For Speed Search after a momentary power loss, parameter b3-05 can be used to delay the Speed Search start providing enough time to operate the contactor. When Speed Search at start is used, b3-05 will serve as the lower limit of the minimum baseblock time (L2-03).
5.2 b: Application
Parameter Details
Table5.5 Speed Search Activation by Digital Inputs — PDF page 133
| Source row | Setting | Description | b3-24 = 0 | b3-24 = 1 |
|---|---|---|---|---|
| 1 | 61 | External Search Command 1 | Closed: Activate Current Detection Speed Search from the maximum output frequency (E1-04). | Activate Speed Estimation Speed Search |
| 2 | 62 | External Search Command 2 | Closed: Activate Current Detection Speed Search from the frequency reference if b3-01 is set to 0. | – |
b3-01 / Speed Search Selection at Start — PDF page 133
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-01 | Speed Search Selection at Start | 0 or 1 | 0 |
b3-02 / Speed Search Deactivation Current — PDF page 133
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-02 | Speed Search Deactivation Current | 0 to 200% | Determined by A1-02 |
b3-03 / Speed Search Deceleration Time — PDF page 133
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-03 | Speed Search Deceleration Time | 0.1 to 10.0 s | 2.0 s |
Manual — Speed Search gains, direction and restart thresholds — page 134
Source reference: SIEP C71060618F, December 2016, physical PDF page 134. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
n b3-06: Output Current 1 During Speed Search
Sets the current injected to the motor at the beginning of Estimation Type Speed Search as a factor related to motor rated current set in E2-01 and E4-01. If the motor speed is relatively slow when the drive starts to perform Speed Search after a long period of baseblock, it may be helpful to increase the setting value. The output current during Speed Search is automatically limited by the drive rated current. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).
Note: If Speed Estimation is not working correctly even after adjusting b3-06, try using Current Detection Speed Search instead.
n b3-08: Current Control Gain during Speed Search (Speed Estimation Type)
Note: Parameter available in drive software versions PRG: 1022 and later. Sets the proportional gain for the current controller during Speed Search. There is normally no need to change this parameter from the default value.
n b3-10: Speed Search Detection Compensation Gain
This parameter sets the gain for the detected motor speed of the Speed Estimation Speed Search. The drive will start the motor at the estimated speed multiplied by b3-10. The setting should be increased if an overvoltage fault occurs when the drive restarts the motor. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).
Note: Increase this value if overvoltage occurs when performing Speed Search at start after a relatively long period of baseblock.
n b3-14: Bi-Directional Speed Search Selection
Sets how the drive determines the motor rotation direction when performing Speed Estimation Speed Search. The setting has no influence on Current Detection Speed Search (b3-24 = 0).
No. Parameter Name Setting Range Default
Setting 0: Disabled The drive uses the frequency reference to determine the direction of motor rotation in order to restart the motor.
Setting 1: Enabled The drive detects the motor rotation direction in order to restart the motor.
n b3-17: Speed Search Restart Current Level
If there is a fairly large difference between the estimated frequency and the actual motor speed when performing Speed Estimation, a large current can flow. This parameter sets the current level at which Speed Estimation is restarted, thus avoiding overcurrent and overvoltage problems. The parameter is set as a percentage of the drive rated current. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).
n b3-18: Speed Search Restart Detection Time
Sets the time the current must be above the level set in b3-17 before Speed Search is restarted. This function has no influence when Current Detection Speed Search is used (b3-24 = 0)
5.2 b: Application
b3-05 / Speed Search Delay Time — PDF page 134
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-05 | Speed Search Delay Time | 0.0 to 100.0 s | 0.2 s |
b3-06 / Output Current 1 during Speed Search — PDF page 134
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-06 | Output Current 1 during Speed Search | 0.0 to 2.0 | Determined by o2-04 |
b3-08 / Current Control Gain during Speed Search (Speed Estimation Type) — PDF page 134
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | 0.00 to 6.00 | A1-02 = 0 or 2: 0.50 A1-02 = 5: 0.30 |
b3-10 / Speed Search Detection Compensation Gain — PDF page 134
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-10 | Speed Search Detection Compensation Gain | 1.00 to 1.20 | 1.10 |
b3-14 / Bi-Directional Speed Search Selection — PDF page 134
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-14 | Bi-Directional Speed Search Selection | 0 or 1 | 0 |
b3-17 / Speed Search Restart Current Level — PDF page 134
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-17 | Speed Search Restart Current Level | 0 to 200% | 150% |
Manual — Search restart limits, method and timer function — page 135
Source reference: SIEP C71060618F, December 2016, physical PDF page 135. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
n b3-19: Number of Speed Search Restarts
Sets the number of times the drive should attempt to find the speed and restart the motor using Speed Estimation Speed Search. This function has no influence when Current Detection Speed Search is used (b3-24 = 0).
n b3-24: Speed Search Method Selection
Sets the Speed Search method used.
Note: For explanations of the Speed Search methods, Refer to Current Detection Type Speed Search (b3-24 = 0) on page 131 and Refer to Speed Estimation Type Speed Search (b3-24 = 1) on page 130.
No. Parameter Name Setting Range Default
Setting 0: Current Detection Speed Search
Setting 1: Speed Estimation Speed Search
n b3-25: Speed Search Wait Time
Sets the wait time between Speed Search restarts.
n b3-29: Speed Search Induced Voltage Level
Performs Speed Search when the motor induced voltage exceeds the set level. There is normally no need to change this parameter from the default value. Lower this value in small increments if changes are necessary. However, setting this value too low will prevent the drive from performing Speed Search.
u b4: Delay Timers
The timer function is independent of the drive operation and can be used to delay the switching of a digital output triggered by a digital input signal. An On-delay and Off-delay can be separately set. The delay timer can help to get rid of chattering switch noise from sensors. To enable the timer function, a multi-function input must be set to “Timer input” (H1-□□ = 18) and a multi-function output must be set to “Timer output” (H2-□□ = 12). Only one timer can be used.
n b4-01/b4-02: Timer Function On/Off-Delay Time
b4-01 sets the On-delay time for switching the timer output. b4-02 sets the Off-delay time for switching the timer output.
n Timer Function Operation
When the timer function input closes for longer than the value set in b4-01, the timer output switches on. When the timer function input is open for longer than the value set in b4-02, the timer output function switches off. The following diagram demonstrates the timer function operation.
5.2 b: Application
Parameter Details
b3-18 / Speed Search Restart Detection Time — PDF page 135
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-18 | Speed Search Restart Detection Time | 0.00 to 1.00 s | 0.10 s |
b3-19 / Number of Speed Search Restarts — PDF page 135
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-19 | Number of Speed Search Restarts | 0 to 10 | 3 |
b3-24 / Speed Search Method Selection — PDF page 135
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-24 | Speed Search Method Selection | 0 or 1 | 0 |
b3-25 / Speed Search Wait Time — PDF page 135
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-25 | Speed Search Wait Time | 0.0 to 30.0 s | 0.5 s |
b3-29 / Speed Search Induced Voltage Level — PDF page 135
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b3-29 | Speed Search Induced Voltage Level | 0 to 10% | 10% |
b4-01 / b4-02 — Timer Function On-Delay Time — PDF page 135
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b4-01 | Timer Function On-Delay Time | 0.0 to 300.0 s | 0.0 s |
| 2 | b4-02 | Timer Function Off-Delay Time | 0.0 to 300.0 s | 0.0 s |
Manual — Timer diagram and PID operation and applications — page 136
Source reference: SIEP C71060618F, December 2016, physical PDF page 136. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Multi-function Contact Input: Timer Function; Multi-function Contact Output: Timer Function. Each has On (Closed), Off (Open); waveform ON segments; b4-01 on-delay and b4-02 off-delay. Pulse widths and unprinted durations are not inferred. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
PID input step; Time. PID Output consists of illustrated P control, I control and D control contributions; PID output; Time. This is a conceptual diagram with no numerical values. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
u b5: PID Control
The drive has a built in PID (Proportional + Integral + Derivative) controller that can be used for closed loop control of system variables such as pressure, temperature etc. The difference between the target and the feedback value (deviation) is fed into the PID controller. The PID controller adjusts the drive output frequency in order to minimize the deviation, providing an accurate control of the system variables.
n P Control
The output of P control is the product of the deviation and the P gain so that it follows the deviation directly and linearly. With P control only an offset between the target and feedback remains.
n I Control
The output of I control is the integral of the deviation. It minimizes the offset between target and feedback value that typically remains when pure P control is used. The integral time (I-time) constant determines how fast the offset is eliminated.
n D Control
D control predicts the deviation signal by multiplying its derivative (slope of the deviation) with a time constant and adding this to the PID input. This way the D portion of a PID controller provides a braking action to the controller response and can reduce the tendency of oscillations and overshoot. Be aware that D control tends to amplify noise on the deviation signal, which can result in control instability. D control should therefore only be used when necessary.
n PID Operation
To better demonstrate how PID works, the diagram below shows how the PID output changes when the PID input (deviation) jumps from 0 to a constant level.
n Using PID Control
Applications for PID control are listed in the table below.
Application Description Sensors Used
5.2 b: Application
PID application examples — PDF page 136
| Source row | Application | Description | Sensors Used |
|---|---|---|---|
| 1 | Speed Control | Machinery speed is fed back and adjusted to meet the target value. Synchronous control is performed using speed data from other machinery as the target value | Tachometer |
| 2 | Pressure | Maintains constant pressure using pressure feedback. | Pressure sensor |
| 3 | Fluid Control | Keeps flow at a constant level by feeding back flow data. | Flow rate sensor |
| 4 | Temperature Control | Maintains a constant temperature by controlling a fan with a thermostat. | Thermocoupler, Thermistor |
Manual — PID setpoint, feedback and differential source assignments — page 137
Source reference: SIEP C71060618F, December 2016, physical PDF page 137. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n PID Setpoint Input Methods
When the PID control parameter b5-01 is set to 1 or 2, the frequency reference in b1-01 (or b1-15) becomes the PID setpoint. If b5-01 is set to 3 or 4, then the PID setpoint can be input from one of the sources in the following table.
Table 5.6 PID Setpoint Sources PID Setpoint Source Settings
Note: A duplicate allocation of the PID setpoint input will result in an OPE alarm.
n PID Feedback Input Methods
Either one feedback signal can be input for normal PID control or two feedback signals can be input for controlling a differential process value.
Normal PID Feedback The PID feedback can be input from one of the sources listed below.
Table 5.7 PID Feedback Sources PID Feedback Source Settings
Note: A duplicate allocation of the PID feedback input will result in an OPE alarm.
Differential Feedback The second PID feedback signal for differential feedback can come from the sources listed below. The differential feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.8 PID Differential Feedback Sources PID Differential Feedback Source Settings
Note: A duplicate allocation of the PID differential feedback input will result in an OPE alarm.
5.2 b: Application
Parameter Details
Table5.6 PID Setpoint Sources — PDF page 137
| Source row | PID Setpoint Source | Settings |
|---|---|---|
| 1 | Analog Input A1 | Set H3-02 = C |
| 2 | Analog Input A2 | Set H3-10 = C |
| 3 | MEMOBUS/Modbus Register 0006H | Set Bit 1 in register 000FH to 1 and input the setpoint to register 0006H |
| 4 | Pulse Input RP | Set H6-01 = 2 |
| 5 | Parameter b5-19 | Set parameter b5-18 = 1 and input the PID setpoint to b5-19 |
Table5.7 PID Feedback Sources — PDF page 137
| Source row | PID Feedback Source | Settings |
|---|---|---|
| 1 | Analog Input A1 | Set H3-02 = B |
| 2 | Analog Input A2 | Set H3-10 = B |
| 3 | Pulse Input RP | Set H6-01 = 1 |
Table5.8 PID Differential Feedback Sources — PDF page 137
| Source row | PID Differential Feedback Source | Settings |
|---|---|---|
| 1 | Analog Input A1 | Set H3-02 = 16 |
| 2 | Analog Input A2 | Set H3-10 = 16 |
Manual — PID block diagram labels and original topology boundary — page 138
Source reference: SIEP C71060618F, December 2016, physical PDF page 138. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Frequency Reference 1 b1-01: 0 Frequency Reference 1 to 16 d1-01 to d1-16; 1 Analog Input A1/A2; 2 Serial Comm; 3 Option Card; 4 Pulse Input. b5-01 branches labeled 0, 1/2 and 3/4. PID Soft Starter b5-17; PID SFS Cancel DI H1-□□=34 On/Off. PID Target: MEMOBUS Reg. 0006h with Reg. 0Fh, bit 1 (0/1); b5-19 selected by b5-18=1/not 1; Pulse Input H6-01=2/not 2; Analog Input A1/A2 H3-02/10=C/not C; zero branch. PID Set Point U5-04. PID Feedback: Pulse Input H6-01=1/not 1; Analog Input A1/A2 H3-02/10=B/not B; zero branch; PID Feedback U5-01. Differential feedback Analog Input A1/A2 H3-02/10=16/not 16, zero branch; PID Differential Feedback U5-05; Adjusted PID Feedback U5-06. Derivative Time b5-05 and Z^-1 blocks; b5-01 2 or 4 / 1 or 3. PID Input U5-02; PID Input Limit b5-35; Proportional Gain b5-02 (P); PID Input Characteristic H1-□□=35 (0/1, -1); Integral Hold H1-□□=31 (0/1); I-time b5-03 (1/s); I-limit b5-04; feedback Z^-1; Integral Reset H1-□□=30 (0/1). Derivative Time b5-05 with Z^-1 and b5-01 1 or 3 / 2 or 4. PID Output Upper/Lower Limit b5-06/b5-34; PID Delay Time b5-08; PID Output Characteristic b5-09 (0/1, -1); PID Offset b5-07; PID Output Gain b5-10. Enable/Disable Reverse Operation when PID Output is Negative: b5-11 0/1, Always 1 when b5-01=3/4. Branch labels Upper Limit Fmax ×109%, Lower Limit 0; bidirectional branch Upper Limit Fmax ×109%, Lower Limit Fmax ×109% (literal lower label has no minus sign). PID Ouput [source spelling] U5-03. PID disable when b5-01=0, a JOG Command is Input, or PID Disable by Digital Input Enabled; Enabled/Disabled switch. Sleep Function: b5-15 Sleep Level, b5-16 Delay Timer, RUN 1 On/Off. SFS C1-□□; Output Frequency. Plus/minus summing nodes and arrow routing are visible but complete mathematical topology is not converted to executable logic; consult original diagram. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
n PID Block Diagram
5.2 b: Application
Manual — PID modes, proportional gain and integral control — page 139
Source reference: SIEP C71060618F, December 2016, physical PDF page 139. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Without Integral: PID feedback, Setpoint, Feedback, Offset, Time. With Integral: Setpoint, Feedback, Zero offset with integral action, Time. Diagram illustrates conceptual transient responses, not numerical gains or measured performance. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
n b5-01: PID Function Setting
Enables or disables the PID operation and selects the PID operation mode.
No. Parameter Name Setting Range Default
Setting 0: PID disabled
Setting 1: Output Frequency = PID Output 1 The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.
Setting 2: Output Frequency = PID Output 2 The PID controller is enabled and the PID output builds the frequency reference. The PID feedback is D controlled.
Setting 3: Output Frequency = Frequency Reference + PID Output 1 The PID controller is enabled and the PID output is added to the frequency reference. D control is applied to the difference of the feedback value (U5-02) and the setpoint.
Setting 4: Output Frequency = Frequency Reference + PID Output 2 The PID controller is enabled and the PID output is added to the frequency reference. Applies D control on the feedback value (U5-06).
n b5-02: Proportional Gain Setting (P)
Sets the P gain that is applied to the PID input. A large value will tend to reduce the error, but may cause instability (oscillations) if too high. A small value may allow too much offset between the setpoint and feedback.
No. Name Setting Range Default
n b5-03: Integral Time Setting (I)
Sets the time constant that is used to calculate the integral of the PID input. The smaller the integral time set to b5-03, the faster the offset will be eliminated. If set too short, it can cause overshoot or oscillations. To turn off the integral time, set b5-03 = 0.00.
n b5-04: Integral Limit Setting
Sets the maximum output possible from the integral block. Set as a percentage of the maximum frequency (E1-04).
Note: On some applications, especially those with rapidly varying loads, the output of the PID function may show a fair amount of oscillation. To suppress this oscillation, a limit can be applied to the integral output by programming b5-04.
5.2 b: Application
Parameter Details
b5-01 / PID Function Setting — PDF page 139
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-01 | PID Function Setting | 0 to 4 | 0 |
b5-02 / Proportional Gain Setting (P) — PDF page 139
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-02 | Proportional Gain Setting (P) | 0.00 to 25.00 | 1.00 |
b5-03 / Integral Time Setting (I) — PDF page 139
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-03 | Integral Time Setting (I) | 0.0 to 360.0 s | 1.0 s |
b5-04 / Integral Limit Setting — PDF page 139
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-04 | Integral Limit Setting | 0.0 to 100.0 | 100.0 |
Manual — PID derivative, output bounds, gain and reverse — page 140
Source reference: SIEP C71060618F, December 2016, physical PDF page 140. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n b5-05: Derivative Time (D)
Sets the time the drive predicts the PID input/PID feedback signal based on the derivative of the PID input/PID feedback. Longer time settings will improve the response but can cause vibrations. Shorter settings will reduce the overshoot but also reduce the controller responsiveness. D control is disabled by setting b5-05 to zero seconds.
No. Name Setting Range Default
n b5-06: PID Output Limit
Sets the maximum output possible from the entire PID controller. Set as a percentage of the maximum frequency (E1-04).
n b5-07: PID Offset Adjustment
Sets the offset added to the PID controller output. Set as a percentage of the maximum frequency.
n b5-08: PID Primary Delay Time Constant
Sets the time constant for the filter applied to the output of the PID controller. Normally, change is not required.
Note: Effective in preventing oscillation when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant frequency. Increasing this time constant reduces the responsiveness of the drive.
n b5-09: PID Output Level Selection
Normally, the output of the PID function increase whenever the PID input is negative (feedback below setpoint). Using b5-09 the PID controller can be set up for applications that require opposite operation.
No. Parameter Name Setting Range Default
Setting 0: Normal Output A negative PID input causes an increase in the PID output (direct acting).
Setting 1: Reverse Output A negative PID input causes a decrease in the PID output (reverse acting).
n b5-10: PID Output Gain Setting
Applies a gain to the PID output and can be helpful when the PID function is used to trim the frequency reference (b5-01 = 3 or 4). Increasing b5-10 causes the PID function to have a greater regulating effect on the frequency reference.
n b5-11: PID Output Reverse Selection
Determines whether a negative PID output reverses the drive operation direction or not. When the PID function is used to trim the frequency reference (b5-01 = 3 or 4), this parameter has no effect and the PID output will not be limited (same as b5-11 = 1).
Setting 0: Reverse Disabled Negative PID output will be limited to 0 and the drive output will be stopped.
5.2 b: Application
b5-05 / Derivative Time — PDF page 140
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-05 | Derivative Time | 0.00 to 10.00 s | 0.00 s |
b5-06 / PID Output Limit — PDF page 140
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-06 | PID Output Limit | 0.0 to 100.0% | 100.0% |
b5-07 / PID Offset Adjustment — PDF page 140
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-07 | PID Offset Adjustment | -100.0 to 100.0% | 0.0% |
b5-08 / PID Primary Delay Time Constant — PDF page 140
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-08 | PID Primary Delay Time Constant | 0.00 to 10.00 s | 0.00 s |
b5-09 / PID Output Level Selection — PDF page 140
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-09 | PID Output Level Selection | 0 or 1 | 0 |
b5-10 / PID Output Gain Setting — PDF page 140
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-10 | PID Output Gain Setting | 0.00 to 25.00 | 1.00 |
b5-11 / PID Output Reverse Selection — PDF page 140
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-11 | PID Output Reverse Selection | 0 or 1 | 0 |
Manual — PID reverse continuation and feedback loss detection — page 141
Source reference: SIEP C71060618F, December 2016, physical PDF page 141. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
PID feedback value; PID Feedback Detection Loss Level (b5-13); time; PID Feedback Loss Detection Time (b5-14) shown for both shorter and sufficient intervals; no FbL detection / FbL detection. Capitalization on graph retained separately from alarm prose FBL. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Setting 1: Reverse Enabled Negative PID output will cause the drive to run in the opposite direction.
n PID Feedback Loss Detection
The PID Feedback Loss Detection function can detect broken sensors or broken sensor wiring. It should be used whenever PID control is enabled to prevent critical machine conditions (e.g. acceleration to max. frequency) caused by a feedback loss. Feedback loss can be detected in two ways: • Feedback Low Detection: Detected when the feedback falls below a certain level for longer than the specified time. • Feedback High Detection: Detected when the feedback rises beyond a certain level for longer than the specified time. The following figure explains the working principle of feedback loss detection when the feedback signal is too low. Feedback high detection works in the same way.
The parameters necessary to set up the feedback loss detection are explained below.
n b5-12: PID Feedback Loss Detection Selection
Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.
No. Parameter Name Setting Range Default
Setting 0: Digital Output Only A digital output set for “PID feedback low” (H2-□□ = 3E) will be triggered if the PID feedback value is below the detection level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PID feedback high” (H2-□□ = 3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for the time set to b5-37 or longer. Neither a fault nor an alarm is displayed on the digital operator. The drive will continue operation. When the feedback value leaves the loss detection range, the output is reset.
Setting 1: Feedback Loss Alarm If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” alarm will be displayed and a digital output set for “PID feedback low” (H2-□□ = 3E) will be triggered. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed and a digital output set for “PID feedback high” (H2-□□ = 3F) will be triggered. Both events trigger an alarm output (H1-□□ = 10). The drive will continue operation. When the feedback value leaves the loss detection range, the alarm and outputs are reset.
Setting 2: Feedback Loss Fault If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” fault will be displayed. Both events trigger a fault output (H1-□□ = E) and cause the drive to stop the motor.
Setting 3: Digital Output Only, Even if PID is Disabled by Digital Input Same as b5-12 = 0. Detection is still active even if PID is disabled by a digital input (H1-□□ = 19).
5.2 b: Application
Parameter Details
b5-12 / PID Feedback Loss Detection Selection — PDF page 141
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-12 | PID Feedback Loss Detection Selection | 0 to 5 | 0 |
Manual — Feedback detection timing and sleep operation — page 142
Source reference: SIEP C71060618F, December 2016, physical PDF page 142. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
PID Output; PID Sleep Function Start Level (b5-15); Sleep Delay Time b5-16 on entering and leaving sleep; Internal Run command Run/Stop; External Run command remains enabled; During Run continues to output “During Run”. Source prose says sleep remains active even if PID control is disabled. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Setting 4: Feedback Loss Alarm, Even if PID is Disabled by Digital Input Same as b5-12 = 1. Detection is still active even if PID is disabled by a digital input (H1-□□ = 19).
Setting 5: Feedback Loss Fault, Even if PID is Disabled by Digital Input Same as b5-12 = 2. Detection is still active even if PID is disabled by a digital input (H1-□□ = 19).
n b5-13: PID Feedback Loss Detection Level
Sets the feedback level used for PID feedback loss detection. The PID feedback has to fall below this level for longer than the time b5-14 before feedback loss is detected.
No. Name Setting Range Default
n b5-14: PID Feedback Loss Detection Time
Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.
n b5-36: PID Feedback High Detection Level
Sets the feedback level used for PID feedback high detection. The PID feedback has to exceed this level for longer than the time b5-37 before feedback loss is detected.
n b5-37: PID Feedback High Detection Time
Sets the time for that the PID feedback has to exceed b5-36 before feedback loss is detected.
n PID Sleep
The PID Sleep function stops the drive when the PID output or the frequency reference falls below the PID Sleep operation level for a certain time. The drive will resume operating once the PID output or frequency reference rises above the PID Sleep operation level for the specified time. The operation is explained in the figure below.
Notes on using the PID Sleep function: • The PID Sleep function is always active, even if PID control is disabled. • The method the Sleep function uses to stop the motor is defined by parameter b1-03. • The parameters necessary to set up the PID Sleep function are explained below.
n b5-15: PID Sleep Function Start Level
Sets the level used for PID Sleep. The drive goes into Sleep mode if the PID output or frequency reference is smaller than b5-15 for longer than the time set in b5-16. It resumes the operation when the PID output or frequency reference is above b5-15 for longer than the time set in b5-16.
5.2 b: Application
b5-13 / PID Feedback Loss Detection Level — PDF page 142
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-13 | PID Feedback Loss Detection Level | 0 to 100% | 0% |
b5-14 / PID Feedback Loss Detection Time — PDF page 142
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-14 | PID Feedback Loss Detection Time | 0.0 to 25.5 s | 1.0 s |
b5-36 / PID Feedback High Detection Level — PDF page 142
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-36 | PID Feedback High Detection Level | 0 to 100% | 100% |
b5-37 / PID Feedback High Detection Time — PDF page 142
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-37 | PID Feedback High Detection Time | 0.0 to 25.5 s | 1.0 s |
Manual — PID sleep, acceleration, setpoint and scaling — page 143
Source reference: SIEP C71060618F, December 2016, physical PDF page 143. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
n b5-16: PID Sleep Delay Time
Sets the delay time to activate or deactivate the PID Sleep function.
n b5-17: PID Accel/Decel Time
The PID acceleration/deceleration time is applied on the PID setpoint value. As the normal acceleration times C1-□□ are applied after the PID output, they reduce the responsiveness of the system and can cause hunting or over- and undershooting when the setpoint changes quickly. Using the PID acceleration/deceleration time instead helps to avoid such problems. The PID acceleration/deceleration time can be canceled using a digital input programmed for “PID SFS cancel” (H1-□□ = 34).
n b5-18: PID Setpoint Selection
Enables or disables parameter b5-19 for PID setpoint.
No. Parameter Name Setting Range Default
Setting 0: Disabled Parameter b5-19 is not used as the PID setpoint. The setpoint must be entered via an analog input, pulse input, or MEMOBUS/ Modbus register 06H.
Setting 1: Enabled Parameter b5-19 is used as PID setpoint.
n b5-19: PID Setpoint Value
Used to adjust the PID setpoint if parameter b5-18 = 1.
n b5-20: PID Setpoint Scaling
Determines the units that the PID setpoint (b5-19) is set in and displayed. Also determines the units for monitors U5-01 and U5-04.
Setting 0: Hz The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: % The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined The setpoint b5-19 and PID monitors U1-01/04 are displayed with the unit and resolution defined by parameters b5-38 and b5-39.
5.2 b: Application
Parameter Details
b5-15 / PID Sleep Function Start Level — PDF page 143
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-15 | PID Sleep Function Start Level | 0.0 to 400.0 Hz | 0.0 Hz |
b5-16 / PID Sleep Delay Time — PDF page 143
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-16 | PID Sleep Delay Time | 0.0 to 25.5 s | 0.0 s |
b5-17 / PID Accel/Decel Time — PDF page 143
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-17 | PID Accel/Decel Time | 0 to 255 s | 0 s |
b5-18 / PID Setpoint Selection — PDF page 143
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-18 | PID Setpoint Selection | 0 or 1 | 0 |
b5-19 / PID Setpoint Value — PDF page 143
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-19 | PID Setpoint Value | 0.00 to 100.00% | 0.00% |
b5-20 / PID Setpoint Scaling — PDF page 143
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-20 | PID Setpoint Scaling | 0 to 3 | 1 |
Manual — PID limits, display, reverse selection and dwell — page 144
Source reference: SIEP C71060618F, December 2016, physical PDF page 144. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n b5-34: PID Output Lower Limit
Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower limit is disabled when set to 0.00%
No. Name Setting Range Default
n b5-35: PID Input Limit
Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1–04). Parameter b5-35 acts as a bipolar limit.
n b5-38/39 PID Setpoint/Monitor User Display Value/Display Digits
When parameter b5-20 is set to 3, the parameters b5-38 and b5-39 can be used to set a user defined display for the PID setpoint (b5-19) and feedback monitors (U5-01/04). Parameter b5-38 determines the display value when the maximum frequency is output. Parameter b5-39 determines the number of digits. The setting value is equal to the number of decimal places.
n b5-40: Frequency Reference Monitor Content During PID
Sets the content on the frequency reference monitor display (U1-01) when PID control is active.
Setting 0: Frequency Reference after PID Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
Setting 1: Frequency Reference Monitor U1-01 displays the frequency reference value.
n b5-47: Reverse Operation Selection 2 by PID Output
Reverses operation selection when b5-01 is set to 3 or 4.
Setting 0: Zero Limit when PID Output is a Negative Value Setting 1: Reverse Operation when PID Output is a Negative Value (Zero Limit if the Reverse Operation Is Prohibited by b1-04) u b6: Dwell Function
The reference hold or Dwell function is used to temporarily hold the output frequency at a set reference value, for a set time, and then continue to ramp up or stop. The Dwell at start function can be used when driving a permanent magnet motor in V/f Control, or a motor with a heavy starting load. The pause in acceleration allows the PM motor rotor to align with the stator field of the motor, thus reducing the starting current. Dwell works as shown in the figure below.
Note: Using the Dwell function requires that the stopping method for the drive be set to “Ramp to Stop” (b1-03 = 0).
5.2 b: Application
b5-34 / PID Output Lower Limit — PDF page 144
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-34 | PID Output Lower Limit | -100.0 to 100.0% | 0.00% |
b5-35 / PID Input Limit — PDF page 144
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-35 | PID Input Limit | 0.0 to 1000.0% | 1000.0% |
b5-38 / b5-39 — PID Setpoint/Monitor User Display Value — PDF page 144
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-38 | PID Setpoint/Monitor User Display Value | 0 to 60000 | Determined by b5-20 |
| 2 | b5-39 | PID Setpoint and Display Digits | 0 to 3 | Determined by b5-20 |
b5-40 / Frequency Reference Monitor Content During PID — PDF page 144
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-40 | Frequency Reference Monitor Content During PID | 0 or 1 | 0 |
b5-47 / Reverse Operation Selection 2 by PID Output — PDF page 144
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b5-47 | Reverse Operation Selection 2 by PID Output | 0 or 1 | 1 |
Manual — Dwell references and Energy Saving settings — page 145
Source reference: SIEP C71060618F, December 2016, physical PDF page 145. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Run Command OFF → ON → OFF; Output Frequency; start reference b6-01 held for b6-02; stop reference b6-03 held for b6-04. Dwell stopping conditions require b1-03=0 in adjacent source prose. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
n b6-01/b6-02: Dwell Reference/Time at Start
b6-01 sets the frequency that is kept for the time set in b6-02 during acceleration.
No. Name Setting Range Default
n b6-03/b6-04: Dwell Reference/Time at Stop
Parameter b6-03 sets the frequency that is kept for the time set in b6-04 during deceleration.
u b8: Energy Saving
The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient level. This is accomplished by continuously monitoring the motor load and controlling the motor so that it always operates near its rated slip frequency.
Note: Energy Saving is mainly designed for applications with variable torque (Normal Duty) but is not appropriate for applications where the load may suddenly increase.
n b8-01: Energy Saving Control Selection
Enables or disables the Energy Saving function.
No. Parameter Name Setting Range Default
Setting 0: Disabled
Setting 1: Enabled
n b8-02: Energy Saving Gain (OLV only)
Sets the gain that is used to for magnetizing current reduction during Energy Saving. A higher value results in lower magnetization of the motor and thereby less energy consumption. However, if b8-02 is too high the motor might stall.
n b8-03: Energy Saving Control Filter Time Constant (OLV only)
Parameter b8-03 sets the response time for Energy Saving. Although lowering this value allows for a quicker response, instability may result if it is too low.
5.2 b: Application
Parameter Details
b6-01 / b6-02 — Dwell Reference at Start — PDF page 145
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b6-01 | Dwell Reference at Start | 0.0 to 400.0 Hz | 0.0 Hz |
| 2 | b6-02 | Dwell Time at Start | 0.0 to 10.0 s | 0.0 s |
b6-03 / b6-04 — Dwell Reference at Stop — PDF page 145
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b6-03 | Dwell Reference at Stop | 0.0 to 400.0 Hz | 0.0 Hz |
| 2 | b6-04 | Dwell Time at Stop | 0.0 to 10.0 s | 0.0 s |
b8-01 / Energy Saving Control Selection — PDF page 145
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b8-01 | Energy Saving Control Selection | 0 or 1 | 0 |
b8-02 / Energy Saving Gain — PDF page 145
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b8-02 | Energy Saving Gain | 0.00 to 10.0 | 0.7 |
b8-03 / Energy Saving Control Filter Time Constant — PDF page 145
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b8-03 | Energy Saving Control Filter Time Constant | 0.00 to 10.00 | Determined by o2-04 |
Manual — Energy Saving coefficients, filtering and motor parameters — page 146
Source reference: SIEP C71060618F, December 2016, physical PDF page 146. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n b8-04: Energy Saving Coefficient Value (V/f Control)
Fine tunes Energy Saving control. The default setting is for a standard Yaskawa motor. When using a different motor, adjust this parameter in 5% increments while running the drive with a light load until output power monitor U1-08 is at the minimum value. A low setting results in less output voltage and less energy consumption. If the value is set too low the motor may stall. The default setting depends on the capacity of the drive.
No. Name Setting Range Default
Note: This default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically when Auto-Tuning for Energy Saving is performed (Refer to Auto-Tuning on page 102).
n b8-05: Power Detection Filter Time (V/f Control only)
The Energy Saving function continuously searches out the lowest output voltage in order to achieve minimum output power. Parameter b8-05 determines how often the output power is measured and the output voltage is adjusted.
n b8-06: Search Operation Voltage Limit (V/f Control only)
Sets the voltage limit for the optimal output voltage detection of Speed Search as a percentage of the maximum output voltage. During the search operation the drive will keep the output voltage above this level to prevent motor stalling.
Note: If set too low, the motor may stall with a sudden increase to the load. Disabled when b8-06 = 0. Setting this value to 0 does not disable Energy Saving.
n Parameters Related to the Energy Saving Function
Open Loop Vector Control
No. Parameter Name Setting Range Default
<1> Automatically set when Rotational Auto-Tuning is performed. <2> Default setting is determined by drive capacity (o2-04).
V/f Control
<1> Automatically set when Auto-Tuning is performed. <2> Default setting is determined by drive capacity (o2-04).
5.2 b: Application
b8-04 / Energy Saving Coefficient Value — PDF page 146
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b8-04 | Energy Saving Coefficient Value | 0.00 to 655.00 | Determined by C6-01, E2-11, and o2-04 |
b8-05 / Power Detection Filter Time — PDF page 146
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b8-05 | Power Detection Filter Time | 0 to 2000 ms | 20 ms |
b8-06 / Search Operation Voltage Limit — PDF page 146
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | b8-06 | Search Operation Voltage Limit | 0 to 100% | 0% |
E2-02 <1> / Motor Rated Slip — PDF page 146
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-02 <1> | Motor Rated Slip | 0.00 to 20.00 | <2> |
E2-11 <1> / Motor Rated Capacity — PDF page 146
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-11 <1> | Motor Rated Capacity | 0.00 to 650.00 kW | <2> |
Manual — Acceleration/deceleration parameter groups and input selection — page 147
Source reference: SIEP C71060618F, December 2016, physical PDF page 147. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency / Time; Accel Time 1 C1-01, Decel Time 1 C1-02; Accel Time 2 C1-03, Decel Time 2 C1-04; Accel Time 3 C1-05, Decel Time 3 C1-06; Accel Time 4 C1-07, Decel Time 4 C1-08; further Decel Time 1 C1-02. FWD (REV) Run command ON/OFF transitions. Accel/Decel Time Selection 1 (Terminals S3 to S8, H1-0x=“7”); Selection 2 (Terminals S3 to S8, H1-0x=“1A”); ON/OFF source states. Numerical truth table is Table5.9 above; no timing durations inferred. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
5.3 C: Tuning
C parameters are used to set the acceleration and deceleration characteristics, as well as S-curves. Other parameters in this group cover settings for slip compensation, torque compensation, and carrier frequency.
u C1: Acceleration and Deceleration Times
n C1-01 to C1-08: Accel/Decel Times 1 to 4
Four different sets of acceleration and deceleration times can be set in the drive. They can be selected by digital inputs, by the motor selection, or can be switched automatically. Acceleration time parameters always set the time to accelerate from 0 to the maximum output frequency (E1-04). Deceleration time parameters always set the time to decelerate from maximum output frequency to 0. C1-01 and C1-02 are the default active accel/decel settings.
No. Parameter Name Setting Range Default
<1> The setting range for the acceleration and deceleration times is determined by C1-10 (Accel/Decel Time Setting Units). For example, if the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
Switching Acceleration Times by Digital Input Accel/decel times 1 are active by default if no input is set. The accel/decel times 2, 3, and 4 can be activated by digital inputs (H1-□□= 7 and 1A) as explained in Table 5.9.
Table 5.9 Accel/Decel Time Selection by Digital Input
Accel/Decel Time Sel. 1 H1-□□ = 7 | Accel/Decel Time Sel. 2 H1-□□ = 1A
Active Times: Acceleration | Deceleration
Figure 5.22 shows an operation example for changing accel/decel. times. The example below requires that the stopping method be set for "Ramp to Stop" (b1-03 = 0).
Parameter Details
C1-01 / C1-02 / C1-03 / C1-04 / C1-05 / C1-06 / C1-07 / C1-08 — Acceleration Time 1 — PDF page 147
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C1-01 | Acceleration Time 1 | 0.0 to 6000.0 s <1> | 10.0 s |
| 2 | C1-02 | Deceleration Time 1 | 0.0 to 6000.0 s <1> | 10.0 s |
| 3 | C1-03 | Acceleration Time 2 | 0.0 to 6000.0 s <1> | 10.0 s |
| 4 | C1-04 | Deceleration Time 2 | 0.0 to 6000.0 s <1> | 10.0 s |
| 5 | C1-05 | Acceleration Time 3 (Motor 2 Accel Time 1) | 0.0 to 6000.0 s <1> | 10.0 s |
| 6 | C1-06 | Deceleration Time 3 (Motor 2 Decel Time 1) | 0.0 to 6000.0 s <1> | 10.0 s |
| 7 | C1-07 | Acceleration Time 4 (Motor 2 Accel Time 2) | 0.0 to 6000.0 s <1> | 10.0 s |
| 8 | C1-08 | Deceleration Time 4 (Motor 2 Accel Time 2) | 0.0 to 6000.0 s <1> | 10.0 s |
Table5.9 Accel/Decel Time Selection by Digital Input — PDF page 147
| Source row | Accel/Decel Time Sel.1 H1-□□=7 | Accel/Decel Time Sel.2 H1-□□=1A | Active Times:Acceleration | Active Times:Deceleration |
|---|---|---|---|---|
| 1 | 0 | 0 | C1-01 | C1-02 |
| 2 | 1 | 0 | C1-03 | C1-04 |
| 3 | 0 | 1 | C1-05 | C1-06 |
| 4 | 1 | 1 | C1-07 | C1-08 |
Manual — Frequency/motor selection and fast-stop timing — page 148
Source reference: SIEP C71060618F, December 2016, physical PDF page 148. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C1-03 = [(accel time from 0 Hz to C1-11) × (E1-04)] / C1-11. C1-01 = [(accel time between C1-11 and E1-04) × (E1-04)] / (E1-04 - C1-11). C1-02 = [(decel time between E1-04 and C1-11) × (E1-04)] / (E1-04 - C1-11). C1-04 = [(decel time from C1-11 to 0 Hz) × (E1-04)] / C1-11. Graph Output Frequency; C1-11 Accel/Decel Time Switch Frequency; segments C1-03 setting, C1-01 setting, C1-02 setting, C1-04 setting. Printed caption statements: output frequency ≥ C1-11 uses Accel/Decel Time 1 (C1-01,-02); output frequency < C1-11 uses Accel/Decel Time 2 (C1-03,-04). These labels conflict with adjacent prose describing low-frequency C1-07/08; both preserved. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Switching Accel/decel Times by a Frequency Level The drive can automatically switch from accel/decel times 4 (C1-07 and C1-08) to the default accel/decel times (C1-01/02 for motor 1, C1-05/06 for motor 2) when the output frequency exceeds the frequency level set in parameter C1-11. When it falls below this level, the accel/decel times are switched back. Figure 5.23 shows an operation example.
Note: Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by a frequency level. For example, if accel/decel time 2 is selected, the drive will use this time only and not switch from accel/decel time 4 to the selected one.
Switching Acceleration and Deceleration Times by Motor Selection When switching between motor 1 and 2 using a digital input (H1-□□ = 16) parameters C1-01 to C1-04 become accel/decel time 1/2 for motor 1 and C1-05 to C1-08 become accel/decel time 1/2 for motor 2. In this case the digital input “Accel/Decel Time 2 Selection” cannot be used (this would trigger an oPE03 error, indicating a contradictory multi-function input settings). Table 5.10 explains the activation of accel/decel times depending on the motor selection and accel/decel time selection.
Table 5.10 Motor Switching and Accel/Decel Time Combinations
Accel/Decel Time 1 (H1-□□ = 7) | Motor 1 Selected: Accel, Decel | Motor 2 Selected: Accel, Decel
n C1-09: Fast-stop Time
Parameter C1-09 will set a special deceleration that is used when certain faults occur or that can be operated by closing a digital input configured as H1-□□ = 15 (N.O. input) or H1-□□ = 17 (N.C. input). The input does not have to be closed continuously, even a momentary closure will trigger the Fast-stop operation. Unlike standard deceleration, once the Fast-stop operation is initiated, the drive cannot be restarted until the deceleration is complete, the Fast-stop input is cleared, and the Run command is cycled. A digital output programmed for “During Fast-stop” (H2-01/02/03 = 4C) will be closed as long as Fast-stop is active.
No. Parameter Name Setting Range Default
<1> The setting range for the acceleration and deceleration times is determined by C1-10 (Accel/Decel Time Setting Units). For example, if the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast-stop time to C1-09.
n C1-10: Accel/Decel Time Setting Units
Determines the units for the acceleration and deceleration times set to C1-01 through C1-09 using parameter C1-10.
Setting 0: 0.01 s Units The accel/decel. times are set in 0.01 s units. The setting range will be 0.00 to 600.00 s. If any of the parameters C1-01 to C1-09 is set to 600.1 seconds or more, then C1-10 cannot be set to 0.
Setting 1: 0.1 s Units The accel/decel. times are set in 0.1 s units. The setting range will be 0.0 to 6000.0 s.
5.3 C: Tuning
C1-09 / Fast-stop Time — PDF page 148
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C1-09 | Fast-stop Time | 0.0 to 6000.0 s <1> | 10.0 s |
C1-10 / Accel/Decel Time Setting Units — PDF page 148
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C1-10 | Accel/Decel Time Setting Units | 0 or 1 | 1 |
Table5.10 Motor Switching and Accel/Decel Time Combinations — PDF page 148
| Source row | Accel/Decel Time1 H1-□□=7 | Motor1:Accel | Motor1:Decel | Motor2:Accel | Motor2:Decel |
|---|---|---|---|---|---|
| 1 | Open | C1-01 | C1-02 | C1-05 | C1-06 |
| 2 | Closed | C1-03 | C1-04 | C1-07 | C1-08 |
Manual — Accel/decel switch and base-rate frequency — page 149
Source reference: SIEP C71060618F, December 2016, physical PDF page 149. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C1-14=0 Hz; E1-04=60 Hz; Frequency Reference=60 Hz. Output frequency / Time, 0; Accel Times 1 to 4; Decel Times 1 to 4. Values are illustrative source example, not installed drive settings. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
n C1-11: Accel/Decel Switch Frequency
Sets the switching frequency for automation accel/decel time change over. Refer to Switching Accel/decel Times by a Frequency Level on page 148 for details.
No. Parameter Name Setting Range Default
Note: Setting C1-11 to 0.0 Hz disables this function.
n C1-14: Accel/Decel Rate Frequency
Sets the base frequency used to calculate acceleration and deceleration times.
Note: The accel/decel rates set to parameters C1-01 to C1-09 change in response to the value set to C1-14. When C1-14 = 0.0 Hz Operation example is shown in Figure 5.24. • Accel Times 1 through 4 determine the time required to accelerate from 0 to the maximum output frequency (E1-04) • Decel Times 1 through 4 and the Fast-stop Time determine the time required to decelerate from the Maximum Output Frequency (E1-04) to 0 Hz.
When C1-14 ≠ 0.0 Hz Operation examples are shown in Figure 5.25 and Figure 5.26. • Accel Times 1 through 4 determine the time required to accelerate from 0 to the value set in C1-14 (Accel/Decel Rate Frequency) • Decel Times 1 through 4 and the Fast-stop Time determine the time required to decelerate from the value set in C1-14 (Accel/ Decel Rate Frequency ) to 0 Hz.
5.3 C: Tuning
Parameter Details
C1-11 / Accel/Decel Switch Frequency — PDF page 149
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C1-11 | Accel/Decel Switch Frequency | 0.0 to 400.0 Hz | 0.0 Hz |
C1-14 / Accel/Decel Rate Frequency — PDF page 149
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C1-14 | Accel/Decel Rate Frequency | 0.0 to 400.0 Hz | 0.0 Hz |
Manual — Rate examples, qualifications and S-curve parameters — page 150
Source reference: SIEP C71060618F, December 2016, physical PDF page 150. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C1-14=40 Hz; E1-04=60 Hz; Frequency reference=60 Hz. Output frequency / Time,0; Accel Times 1 to 4 shown to40 Hz; Decel Times 1 to 4 shown from40 Hz. Values are illustrative source example; no calculated elapsed times. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
C1-14=80 Hz; E1-04=60 Hz; Frequency reference=60 Hz. Output frequency / Time,0; Accel Times 1 to 4 and Decel Times 1 to 4 shown against extended dashed80 Hz ramp. Actual reference plateau is60 Hz. No calculated elapsed time or operating recommendation. Source figure geometry, electrical connections and unprinted numerical values remain original-only.
Note: 1. The accel/decel times shown in Figure 5.24 to Figure 5.26 assume S-curve characteristic time during accel/decel at start and accel/ decel at stop of 0.00 s (parameters C2-01 to C2-04). 2. When Stall Prevention during acceleration is enabled (L3-01 ≠ 0), the accel time may take longer than the set value. 3. When Stall Prevention during deceleration is enabled (L3-04 ≠ 0), the decel time may take longer than the set value. 4. When performing Rotational Auto-Tuning for OLV Control (T1-01 = 0) and Rotational Auto-Tuning for V/f Control (T1-04 = 3), the drive uses the maximum output frequency set in E1-04 to determine the base accel/decel rate, regardless of the C1-14 value.
u C2: S-Curve Characteristics
Use S-curve characteristics to smooth acceleration and deceleration and to minimize abrupt shock to the load. Set S-curve characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop. If a STo fault (Step Out Detection) occurs when starting a PM motor, try increasing the value set to C2-01.
n C2-01 to C2-04: S-Curve Characteristics
C2-01 through C2-04 set separate S-curves for each section of the acceleration or deceleration.
No. Parameter Name Setting Range Default
5.3 C: Tuning
C2-01 / C2-02 / C2-03 / C2-04 — S-Curve Characteristic at Accel Start — PDF page 150
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C2-01 | S-Curve Characteristic at Accel Start | 0.00 to 10.00 s | Determined by A1-02 |
| 2 | C2-02 | S-Curve Characteristic at Accel End | 0.00 to 10.00 s | 0.20 s |
| 3 | C2-03 | S-Curve Characteristic at Decel Start | 0.00 to 10.00 s | 0.20 s |
| 4 | C2-04 | S-Curve Characteristic at Decel End | 0.00 to 10.00 s | 0.00 s |
Manual — S-curve and Slip Compensation — page 151
Source reference: SIEP C71060618F, December 2016, physical PDF page 151. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Forward Run command; Reverse Run command; Output frequency positive and negative. C2-01 acceleration start, C2-02 acceleration end; C2-03 deceleration start, C2-04 deceleration end are labeled on the curves. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Setting the S-curve will increase the acceleration and deceleration times. Actual accel time = accel time setting + (C2-01 + C2-02)/2. Actual decel time = decel time setting + (C2-03 + C2-04)/2. Parentheses and fraction groupings restored from source; no calculated times. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Figure 5.27 explains how S-curves are applied.
u C3: Slip Compensation
The Slip Compensation function prevents motor speed loss due to an increase in load.
Note: Before making changes to the Slip Compensation parameters, make sure the motor parameters and V/f pattern are set properly or perform Auto-Tuning.
n C3-01: Slip Compensation Gain
This parameter sets the gain for the motor slip compensation function. Although this parameter rarely needs to be changed, adjustments might be needed under the following situations: • If the speed at constant frequency reference is lower than the frequency reference, increase C3-01. • If the speed at constant frequency reference is higher than the frequency reference, decrease C3-01.
No. Parameter Name Setting Range Default
Note: Default setting is 0.0 in V/f Control (A1-02 = 0). Default setting is 1.0 in Open Loop Vector Control (A1-02 = 2). This parameter is disabled when using V/f Control with Simple PG Feedback (H6-01 = 3).
n C3-02: Slip Compensation Primary Delay Time
Adjusts the filter on the output of the slip compensation function. Although this parameter rarely needs to be changed, adjustments might be needed under the following situations: • Decrease the setting when the slip compensation response is too slow. • Increase this setting when the speed is not stable.
Note: When using V/f Control (A1-02 = 0), the default setting becomes 2000 ms. When using Open Loop Vector Control (A1-02 = 2), the default setting becomes 200 ms. This function is not available when using V/f Control with Simple PG Feedback.
n C3-03: Slip Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E2-02).
5.3 C: Tuning
Parameter Details
C3-01 / Slip Compensation Gain — PDF page 151
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C3-01 | Slip Compensation Gain | 0.0 to 2.5 | Determined by A1-02 |
C3-02 / Slip Compensation Primary Delay Time — PDF page 151
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C3-02 | Slip Compensation Primary Delay Time | 0 to 10000 ms | Determined by A1-02 |
C3-03 / Slip Compensation Limit — PDF page 151
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C3-03 | Slip Compensation Limit | 0 to 250% | 200% |
Manual — Slip limits and Torque Compensation — page 152
Source reference: SIEP C71060618F, December 2016, physical PDF page 152. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Slip compensation limit; Output frequency; C3-03 level held to E1-06 Base frequency; rising to (E1-04/E1-06) × C3-03 at E1-04 Maximum output frequency. No additional formula inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
The slip compensation limit is constant throughout the constant torque range. In the constant power range it is increased based on C3-03 and the output frequency as shown in the following diagram.
Note: This parameter is disabled when using V/f Control with Simple PG Feedback Control (H6-01 = 3).
n C3-04: Slip Compensation Selection during Regeneration
When the slip compensation during regeneration function has been activated and regenerative load is applied, it might be necessary to use a braking option (braking resistor, braking resistor unit, or braking unit). Even if enabled, this function does not operate when the output frequency is too low.
No. Parameter Name Setting Range Default
Setting 0: Disabled Slip compensation is not provided. Depending on the load and operation mode (motoring or regenerative) the actual motor speed will be lower or higher than the frequency reference.
Setting 1: Enabled Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
n C3-05: Output Voltage Limit Operation Selection
Determines if the motor flux reference is automatically reduced when output voltage reaches the saturation range.
Setting 0: Disabled
Setting 1: Enabled
n C3-18: Output Voltage Limit Level
Sets the maximum percentage of output voltage reduction when C3-05 is set to 1 (Enabled).
u C4: Torque Compensation
The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.
Note: Before making changes to the torque compensation parameters make sure the motor parameters and V/f pattern are set properly or perform Auto-Tuning.
n C4-01: Torque Compensation Gain
Sets the gain for the torque compensation function.
5.3 C: Tuning
C3-04 / Slip Compensation Selection during Regeneration — PDF page 152
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C3-04 | Slip Compensation Selection during Regeneration | 0 or 1 | 0 |
C3-05 / Output Voltage Limit Operation Selection — PDF page 152
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C3-05 | Output Voltage Limit Operation Selection | 0 or 1 | 0 |
C3-18 / Output Voltage Limit Level — PDF page 152
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C3-18 | Output Voltage Limit Level | 70.0 to 100.0% | 90.0% |
C4-01 / Torque Compensation Gain — PDF page 152
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C4-01 | Torque Compensation Gain | 0.00 to 2.50 | Determined by A1-02 |
Manual — Torque compensation modes and offsets — page 153
Source reference: SIEP C71060618F, December 2016, physical PDF page 153. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Torque Compensation in V/f Control: The drive calculates the motor primary voltage loss using the output current and the terminal resistance value (E2-05) and then adjusts the output voltage to compensate insufficient torque at start or when load is applied. The effect of this voltage compensation can be increased or decreased using parameter C4-01.
Torque Compensation in Open Loop Vector Control: The drive controls the motor excitation current and torque producing current separately. Torque compensation affects the torque producing current only. C4-01 works as a factor of the torque reference value that builds the torque producing current reference.
Adjustment Although this parameter rarely needs to be adjusted, small changes in increments of 0.05 may help in the following situations: • Increase this setting when using a long motor cable. • Decrease this setting when motor oscillation occurs. Adjust C4-01 so that the output current does not exceed the drive rated current.
n C4-02: Torque Compensation Primary Delay Time 1
Sets the delay time used for applying torque compensation.
No. Parameter Name Setting Range Default
Adjustment Although C4-02 rarely needs to be changed, adjustments may help in the following situations: • If the motor vibrates, increase C4-02. • If the motor responds too slowly to changes in the load, decrease C4-02.
n C4-03: Torque Compensation at Forward Start (OLV only)
Sets the amount of torque at start in the forward direction in order to improve motor performance during start with heavy load. Compensation is applied using the time constant set in parameter C4-05. A setting of 0.0% disables this feature.
n C4-04: Torque Compensation at Reverse Start (OLV only)
Sets the amount of torque reference at start in the reverse direction in order to improve motor performance during start with heavy load. Compensation is applied using the time constant set in parameter C4-05. A setting of 0.0% disables this feature.
n C4-05: Torque Compensation at Start Time Constant (OLV only)
This parameter is the time constant for applying the torque compensation at start set in parameters C4-03 and C4-04.
n C4-06: Torque Compensation Primary Delay Time 2 (OLV only)
This time constant is used during Speed Search or during regenerative operation when the actual motor slip is higher than 50% of the rated slip. Adjust the value if an overvoltage fault occurs with sudden changes in the load or at the end of acceleration with high inertia load.
Note: 1. If C4-06 is set to a relatively large value, be sure to also increase the setting in n2-03 (AFR Time Constant 2) proportionally. 2. C4-06 will not be active if L3-04 is 0, 3 or 4, the output frequency is below 5 Hz, or Speed Search after momentary power loss is active.
5.3 C: Tuning
Parameter Details
C4-02 / Torque Compensation Primary Delay Time 1 — PDF page 153
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C4-02 | Torque Compensation Primary Delay Time 1 | 0 to 60000 ms | Determined by A1-02 |
C4-03 / Torque Compensation at Forward Start — PDF page 153
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C4-03 | Torque Compensation at Forward Start | 0.0 to 200.0% | 0.0% |
C4-04 / Torque Compensation at Reverse Start — PDF page 153
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C4-04 | Torque Compensation at Reverse Start | -200.0 to 0.0% | 0.0% |
C4-05 / Torque Compensation Time Constant — PDF page 153
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C4-05 | Torque Compensation Time Constant | 0 to 200 ms | 10 ms |
C4-06 / Torque Compensation Primary Delay Time 2 — PDF page 153
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C4-06 | Torque Compensation Primary Delay Time 2 | 0 to 10000 ms | 150 ms |
Manual — ASR pulse-feedback control and activation — page 154
Source reference: SIEP C71060618F, December 2016, physical PDF page 154. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Frequency Reference U1-01; Soft Starter; Soft Starter Output U1-16; multiplication; Output Frequency U1-02. Direction input Digital Input H1-□□=7E: 1/0. External PG pulse converter takes A/B signals and outputs Direction FWD/REV and 1-track speed pulses. Pulse Input; unsigned motor speed feedback; multiplication by direction yields Motor Speed (signed) U1-05. ASR Input U6-03; P control C5-01/C5-03; I control C5-02/C5-04; ASR Limit C5-05; ASR Output U6-04. Summing signs and arrows are visible; complete executable control topology is not reconstructed. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
u C5: Automatic Speed Regulator (ASR)
The ASR is a PI controller that adjusts the output frequency in order to compensate the motor slip when load is applied. It is active only when V/f Control is used in combination with a speed feedback signal connected to the drive pulse input RP (V/ f Control with Simple Speed Feedback). The pulse input provides one track only and cannot detect the direction of motor rotation. A separate motor speed direction signal must therefore be input to the ASR by: 1. Using a Digital Input This method is automatically enabled when a digital input is programmed for “Forward/Reverse direction” (H1-□□= 7E). If the input is closed, the drive assumes reverse rotation. If open, then the drive assumes that the motor is rotating forwards. When a 2 track encoder is used, an external unit that converts the 2 tracks into 1 track and a digital direction signal can be used. 2. Using the Frequency Reference Direction When no digital input is set for “Forward/Reverse direction” (H1-□□≠ 7E), ASR uses the direction of the frequency reference. Figure 5.29 illustrates the ASR function when using V/f with Simple Speed Feedback.
To activate V/f Control with PG feedback: 1. Set the drive to V/f Control (A1-02 = 0). 2. Connect the motor speed pulse signal to the pulse input RP, set H6-01 = 3, and set the pulse signal frequency that is equal to the maximum speed to H6-02 (pulse input scaling). Make sure the pulse input bias (H6-04) is 0% and the gain (H6-03) is 100%. 3. Decide the signal used for detecting the direction. If a digital input is used set H1-□□ = 7E. 4. Use the ASR gain and integral time parameters described below for adjusting the ASR responsiveness. Note: 1. C5 parameters will appear only when using V/f Control (A1-02 = 0) and when the pulse input RP function is set for PG feedback in V/ f Control (H6-01 = 3). 2. V/f Control with PG feedback can be used for motor 1 only. ASR Tuning Parameters ASR provides two sets of gain and integral time. Set 1 is active at the maximum output frequency, set 2 is active at the minimum output frequency. The settings are changed linearly depending on the output frequency as shown in Figure 5.30.
5.3 C: Tuning
Manual — ASR gains, limits and Drive Duty — page 155
Source reference: SIEP C71060618F, December 2016, physical PDF page 155. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
P gain / I time; Motor Speed; 0; E1-09 Minimum output frequency; E1-04 Maximum output frequency. Low-speed gains C5-03 and C5-04; high-speed gains C5-01 and C5-02; transition drawn between speed thresholds. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
n C5-01/02: ASR Proportional Gain/Integral Time 1
These parameters determine the responsiveness of ASR at maximum output frequency. • Increase the gain and/or reduce the integral time if the response is slow at maximum output frequency. • Reduce the gain and/or increase the integral time when vibrations occur at the maximum output frequency. • When adjusting ASR always first adjust the P gain, then adjust the integral time.
No. Parameter Name Setting Range Default
n C5-03/04: ASR Proportional Gain/Integral Time 2
These parameters determine the responsiveness of ASR at the minimum output frequency. Use the same setting rules as described for C5-01/02
n C5-05: ASR Limit
Sets the ASR output limit as a percentage of the maximum output frequency (E1-04). If the motor slip is high, the setting might need to be increased to provide proper slip compensation. Use the ASR output monitor U6-04 to determine if ASR is working at the limit and make settings if necessary. If ASR is operating at the ASR limit, check the pulse signal and the pulse input settings prior to changes in C5-05.
u C6: Carrier Frequency
n C6-01: Drive Duty Selection
The drive has two different duty modes from which to select based on the load characteristics. The drive rated current, overload capacity, and carrier frequency will change depending upon the duty mode selection. Use parameter C6-01 to select Heavy Duty (HD) or Normal Duty (ND) for the application. The default setting is ND. Refer to Heavy Duty and Normal Duty Ratings on page 342 for details about the rated current.
<1> Model BA0018 does not have a Normal Duty mode. The default setting is 0.
5.3 C: Tuning
Parameter Details
C5-01 / C5-02 — ASR Proportional Gain 1 — PDF page 155
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C5-01 | ASR Proportional Gain 1 | 0.00 to 300.00 | 0.20 |
| 2 | C5-02 | ASR Integral Time 1 | 0.000 to 10.000 s | 0.200 s |
C5-03 / C5-04 — ASR Proportional Gain 2 — PDF page 155
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C5-03 | ASR Proportional Gain 2 | 0.00 to 300.00 | 0.02 |
| 2 | C5-04 | ASR Integral Time 2 | 0.000 to 10.000 s | 0.050 s |
C5-05 / ASR Limit — PDF page 155
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C5-05 | ASR Limit | 0.0 to 20.0% | 5.0% |
C6-01 / Drive Duty Selection — PDF page 155
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C6-01 | Drive Duty Selection | 0 or 1 | 1 <1> |
Manual — Heavy/Normal Duty and Carrier Frequency — page 156
Source reference: SIEP C71060618F, December 2016, physical PDF page 156. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table 5.11 Differences between Heavy and Normal Duty
Mode Heavy Duty Rating (HD) Normal Duty Rating (ND)
Note: By changing the Drive Duty, the drive maximum applicable motor power changes and the E2-□□ and E4-□□ parameters are automatically set to appropriate values.
n C6-02: Carrier Frequency Selection
Parameter C6-02 sets the switching frequency of the drive’s output transistors. It can be changed in order to reduce audible noise and also reduce leakage current.
Note: The drive rated current is reduced when the carrier frequency is set higher than the default value. Refer to Rated Current Depending on Carrier Frequency on page 158.
No. Parameter Name Setting Range Default
<1> Setting range is determined by the drive software version. PRG: 1020 and later: 1 to B; F PRG: 1018 and earlier: 1 to A; F
Settings:
C6-02 Carrier Frequency
<1> Available in drive software versions PRG: 1020 and later. Setting B uses a PWM pattern that reduces the amount of leakage current detected over long wiring distances. This can help reduce alarm detection and problems with the current monitor that result from leakage current over long wiring distances. This is the same as setting the carrier frequency to 2 kHz.
Note: Swing PWM uses 2.0 kHz carrier frequency as a base. Applying special PWM patterns minimizes the audible noise of the motor. Guidelines for Carrier Frequency Parameter Setup
Symptom Remedy
5.3 C: Tuning
Table5.11 Differences between Heavy and Normal Duty — PDF page 156
| Source row | Mode | Heavy Duty Rating (HD) | Normal Duty Rating (ND) |
|---|---|---|---|
| 1 | C6-01 | 0 | 1 |
| 2 | Characteristics | Heavy Duty graph: Overload 150%; Rated Load 100%; Motor Speed 0 to 100%. Rated-load line is constant. Source characteristic diagram only; no intermediate values or measured geometry inferred. | Normal Duty graph: Overload 120%; Rated Load 100%; Motor Speed 0 to 100%. Rated-load curve rises toward 100%. Source characteristic diagram only; no intermediate values or measured geometry inferred. |
| 3 | Application | Use Heavy Duty Rating for applications requiring a high overload tolerance with constant load torque. Such applications include extruders and conveyors. | Use Normal Duty Rating for applications in which the torque requirements drop along with the speed. Examples include fans or pumps where a high overload tolerance is not required. |
| 4 | Over load capability (oL2) | 150% of drive rated Heavy Duty current for 60 s | 120% of drive rated Normal Duty current for 60 s |
| 5 | L3-02 Stall Prevention during Acceleration | 150% | 120% |
| 6 | L3-06 Stall Prevention during Run | 150% | 120% |
| 7 | Default Carrier Frequency | 8/10 kHz | 2 kHz Swing PWM |
C6-02 / Carrier Frequency Selection — PDF page 156
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C6-02 | Carrier Frequency Selection | <1> | Determined by A1-02 and o2-04. Reset when C6-01 is changed. |
C6-02 Carrier Frequency settings 1–7 — PDF page 156
| Source row | C6-02 | Carrier Frequency |
|---|---|---|
| 1 | 1 | 2.0 kHz |
| 2 | 2 | 5.0 kHz |
| 3 | 3 | 8.0 kHz |
| 4 | 4 | 10.0 kHz |
| 5 | 5 | 12.5 kHz |
| 6 | 6 | 15.0 kHz |
| 7 | 7 | Swing PWM 1 |
C6-02 Carrier Frequency settings 8–B and F — PDF page 156
| Source row | C6-02 | Carrier Frequency |
|---|---|---|
| 1 | 8 | Swing PWM 2 |
| 2 | 9 | Swing PWM 3 |
| 3 | A | Swing PWM 4 |
| 4 | B <1> | Leakage Current Rejection PWM |
| 5 | F | User-defined (C6-03 to C6-05) |
Guidelines for Carrier Frequency Parameter Setup — PDF page 156
| Source row | Symptom | Remedy |
|---|---|---|
| 1 | Speed and torque are unstable at low speeds. | Lower the carrier frequency. |
| 2 | Noise from the drive is affecting peripheral devices. | Lower the carrier frequency. |
| 3 | Excessive leakage current from the drive. | Lower the carrier frequency. |
Manual — Cable length and variable Carrier Frequency — page 157
Source reference: SIEP C71060618F, December 2016, physical PDF page 157. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Carrier Frequency; Output Frequency; lower C6-04; upper C6-03; maximum E1-04. Slope label Output Frequency × C6-05 × K*. K=2 when 10>C6-03≥5; K=1 when 5>C6-03; K=3 when C6-03≥10. Exact source inequalities retained. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Symptom Remedy
<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to the table below. <2> In Normal Duty default setting is 7 (Swing PWM), equivalent to setting 2 kHz. Increasing the carrier frequency is fine when using the drive is set for Normal Duty, but remember that the drive rated current falls when the carrier frequency is increased.
Wiring Distance Up to 50 m Up to 100 m Greater than 100 m
Note: If the motor cable is fairly long when using PM Open Loop Vector, set the carrier frequency to 2 kHz (C6-02 = 1). Switch to V/f Control if the cable is longer than 100 m.
n C6-03/C6-04/C6-05: Carrier Frequency Upper Limit/Lower Limit/Proportional Gain
Use these parameters to set a user defined or a variable carrier frequency. To set the upper and lower limits, first set C6-02 to “F”.
No. Parameter Name Setting Range Default
<1> The default value is determined by the control method (A1-02) as well as the drive capacity (o2-04), and is reinitialized when the value set to C6-01 is changed.
Setting a Fixed User Defined Carrier Frequency A carrier frequency between the fixed selectable values can be entered in parameter C6-03 when C6-02 is set to “F”. In V/f Control, parameter C6-04 must also be adjusted to the same value as C6-03.
Setting a Variable Carrier Frequency (V/f Control only) In V/f Control, the carrier frequency can be set up to change linearly with the output frequency. In this case the upper and lower limits for the carrier frequency and the carrier frequency proportional gain (C6-03, C6-04, C6-05) have to be set as shown in Figure 5.31.
K is a coefficient determined by the value of C6-03: • 10.0 kHz > C6-03 ≥ to 5.0 kHz: K = 2 • 5.0 kHz > C6-03: K = 1 • C6-03 ≥ 10.0 kHz: K = 3 Note: 1. A carrier frequency error (oPE11) will occur when the carrier frequency proportional gain is greater than 6 while C6-03 is less than C6-04. 2. When C6-05 is set lower than 7, C6-04 is disabled and the carrier frequency will be fixed to the value set in C6-03.
5.3 C: Tuning
Parameter Details
Guidelines for Carrier Frequency Parameter Setup continued — PDF page 157
| Source row | Symptom | Remedy |
|---|---|---|
| 1 | Wiring between the drive and motor is too long. <1> | • Lower the carrier frequency • Set C6-02 to B if an alarm is detected or if leakage current causes a problem with the current monitor. |
| 2 | Audible motor noise is too loud. | Increase the carrier frequency or use Swing PWM. <2> |
Wiring distance and carrier selection — PDF page 157
| Source row | Wiring Distance | Up to 50 m | Up to 100 m | Greater than 100 m |
|---|---|---|---|---|
| 1 | C6-02 (Carrier Frequency Selection) | 0 to 6 (15 kHz) | 0 to 4 (10 kHz) | 1, 7 to A (2 kHz) |
C6-03 / C6-04 / C6-05 — Carrier Frequency Upper Limit — PDF page 157
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | C6-03 | Carrier Frequency Upper Limit | 1.0 to 15.0 kHz | <1> |
| 2 | C6-04 | Carrier Frequency Lower Limit (V/f only) | 1.0 to 15.0 kHz | <1> |
| 3 | C6-05 | Carrier Frequency Proportional Gain (V/f only) | 0 to 99 | <1> |
Manual — Carrier Frequency rating tables — page 158
Source reference: SIEP C71060618F, December 2016, physical PDF page 158. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n Rated Current Depending on Carrier Frequency
The tables below show the drive output current depending on the carrier frequency settings. The 2 kHz value is equal to the Normal Duty rated current, the 8/10 kHz value is equal to the Heavy Duty rated current. The carrier frequency determines the output current linearly. Use the data below to calculate output current values for carrier frequencies not listed in the tables.
Note: In Heavy Duty mode the maximum rated output current is equal to the 8/10 kHz value, even if the carrier frequency is reduced.
Table 5.12 200 V Class Drives with 10 kHz Heavy Duty Default Carrier Frequency
Model | Rated Current (A): 2 kHz, 10 kHz, 15 kHz
Table 5.13 200 V Class Drives with 8 kHz Heavy Duty Default Carrier Frequency
Model | Rated Current (A): 2 kHz, 8 kHz, 15 kHz
Table 5.14 400 V Class Drives with 8 kHz Heavy Duty Default Carrier Frequency
5.3 C: Tuning
Table5.12 200Vclass drives with 10kHz Heavy Duty default carrier frequency — PDF page 158
| Source row | Model | Rated Current(A) at2kHz | Rated Current(A) at10kHz | Rated Current(A) at15kHz |
|---|---|---|---|---|
| 1 | BA0001 2A0001 | 1.2 | 0.8 | 0.6 |
| 2 | BA0002 2A0002 | 1.9 | 1.6 | 1.3 |
| 3 | BA0003 2A0004 | 3.5 | 3.0 | 2.4 |
| 4 | BA0006 2A0006 | 6.0 | 5.0 | 4.0 |
Table5.13 200Vclass drives with 8kHz Heavy Duty default carrier frequency — PDF page 158
| Source row | Model | Rated Current(A) at2kHz | Rated Current(A) at8kHz | Rated Current(A) at15kHz |
|---|---|---|---|---|
| 1 | BA0010 2A0010 | 9.6 | 8.0 | 6.4 |
| 2 | BA0012 2A0012 | 12.0 | 11.0 | 8.8 |
| 3 | BA0018 | 17.5 | 17.5 | 14.0 |
| 4 | 2A0020 | 19.6 | 17.5 | 14.0 |
| 5 | 2A0030 | 30.0 | 25.0 | 20.0 |
| 6 | 2A0040 | 40.0 | 33.0 | 26.4 |
| 7 | 2A0056 | 56.0 | 47.0 | 37.6 |
| 8 | 2A0069 | 69.0 | 60.0 | 48.0 |
Table5.14 400Vclass drives with 8kHz Heavy Duty default carrier frequency — PDF page 158
| Source row | Model | Rated Current(A) at2kHz | Rated Current(A) at8kHz | Rated Current(A) at15kHz |
|---|---|---|---|---|
| 1 | 4A0001 | 1.2 | 1.2 | 0.7 |
| 2 | 4A0002 | 2.1 | 1.8 | 1.1 |
| 3 | 4A0004 | 4.1 | 3.4 | 2.0 |
| 4 | 4A0005 | 5.4 | 4.8 | 2.9 |
| 5 | 4A0007 | 6.9 | 5.5 | 3.3 |
| 6 | 4A0009 | 8.8 | 7.2 | 4.3 |
| 7 | 4A0011 | 11.1 | 9.2 | 5.5 |
| 8 | 4A0018 | 17.5 | 14.8 | 8.9 |
| 9 | 4A0023 | 23.0 | 18.0 | 10.8 |
| 10 | 4A0031 | 31.0 | 24.0 | 14.4 |
| 11 | 4A0038 | 38.0 | 31.0 | 18.6 |
Manual — Frequency Reference selection hierarchy — page 159
Source reference: SIEP C71060618F, December 2016, physical PDF page 159. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Frequency Reference Source1 b1-01 / Source2 b1-15: 0 Frequency Reference1 d1-01;1 Terminal A1/A2;2 MEMOBUS communications;3 Option Card;4 Pulse Train Input. Digital Input H1-□□=2 branches0/1; Remote/Local; d2-03 Frequency Reference Lower Limit. Terminal A2 auxiliary H3-10=2/not2 selects d1-02 Multi-Step Speed2. d1-03/04 through d1-15/16 Multi-Step Speed3 to16; d1-17 Jog. Jog Digital Input H1-□□=6; FJOG H1-□□=12; RJOG H1-□□=13. Multi-Step Speed. NetRef0/1 determined by communications option card; Option Card Signal is Off branch. ComRef0/1, MEMOBUS Register0001h bit4 when standard2-wire sequence used. Frequency Reference output. All source branch labels preserved; exact switch hierarchy requires original diagram. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
5.4 d: Reference Settings
The drive offers various ways of entering the frequency reference. The figure below gives an overview of the reference input, selections, and priorities.
Parameter Details
Manual — Multi-Step Speed and Jog selection — page 160
Source reference: SIEP C71060618F, December 2016, physical PDF page 160. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u d1: Frequency Reference
n d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference
Up to 17 preset references (including Jog reference) can be programmed in the drive. The references can be switched during Run by digital inputs. The acceleration/deceleration to the new reference is performed using the active acceleration/deceleration time. The Jog frequency must be selected by a separate digital input and has priority over the references 1 to 16. The multi-speed references 1 and 2 can be provided by analog inputs.
No. Parameter Name Setting Range Default
<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
Multi-Step Speed Selection Depending on how many speeds are used, some digital inputs have to be programmed for Multi-Step Speed Reference 1, 2, 3 and 4 (H1-□□ = 3, 4, 5, 32). For the Jog reference a digital input must be set to H1-□□ = 6. Notes on using analog inputs as multi-speed 1 and 2: • If the frequency reference source is assigned to analog input A1 (b1-01 = 1), then this input will be used for Frequency Reference 1 instead of d1-01. If the reference source is assigned to the digital operator (b1-01 = 0), then d1-01 will be used as Frequency Reference 1. • When the analog input A2 function is set to “Auxiliary Frequency” (H3-10 = 2), then the value input to terminal A2 will be used as the Frequency Reference 2 instead of the value set to parameter d1-02. When H3-10 does not equal 2, then d1-02 becomes the reference for Frequency Reference 2. The different speed references can be selected as shown in Table 5.15. Figure 5.33 illustrates the multi-step speed selection.
Table 5.15 Multi-Step Speed Reference and Terminal Switch Combinations
Reference
Multi-Step Speed H1-□□=3
Multi-Step Speed 2 H1-□□=4
Multi-Step Speed 3 H1-□□=5
Multi-Step Speed 4 H1-□□=32
Jog Reference H1-□□=6
<1> The Jog frequency overrides the frequency reference being used.
5.4 d: Reference Settings
d1-01 to d1-16 / d1-17 — Frequency Reference 1 to 16 — PDF page 160
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d1-01 to d1-16 | Frequency Reference 1 to 16 | 0.00 to 400.00 Hz <1> | 0.00 Hz |
| 2 | d1-17 | Jog Frequency Reference | 0.00 to 400.00 Hz <1> | 6.00 Hz |
Table5.15 Multi-Step Speed Reference and Terminal Switch Combinations — PDF page 160
| Source row | Reference | Multi-Step Speed H1-□□=3 | Multi-Step Speed 2 H1-□□=4 | Multi-Step Speed 3 H1-□□=5 | Multi-Step Speed 4 H1-□□=32 | Jog Reference H1-□□=6 |
|---|---|---|---|---|---|---|
| 1 | Frequency Reference 1 (d1-01/A1) | OFF | OFF | OFF | OFF | OFF |
| 2 | Frequency Reference 2 (d1-02/A2) | ON | OFF | OFF | OFF | OFF |
| 3 | Frequency Reference 3 (d1-03) | OFF | ON | OFF | OFF | OFF |
| 4 | Frequency Reference 4 (d1-04) | ON | ON | OFF | OFF | OFF |
| 5 | Frequency Reference 5 (d1-05) | OFF | OFF | ON | OFF | OFF |
| 6 | Frequency Reference 6 (d1-06) | ON | OFF | ON | OFF | OFF |
| 7 | Frequency Reference 7 (d1-07) | OFF | ON | ON | OFF | OFF |
| 8 | Frequency Reference 8 (d1-08) | ON | ON | ON | OFF | OFF |
| 9 | Frequency Reference 9 (d1-09) | OFF | OFF | OFF | ON | OFF |
| 10 | Frequency Reference 10 (d1-10) | ON | OFF | OFF | ON | OFF |
| 11 | Frequency Reference 11 (d1-11) | OFF | ON | OFF | ON | OFF |
| 12 | Frequency Reference 12 (d1-12) | ON | ON | OFF | ON | OFF |
| 13 | Frequency Reference 13 (d1-13) | OFF | OFF | ON | ON | OFF |
| 14 | Frequency Reference 14 (d1-14) | ON | OFF | ON | ON | OFF |
| 15 | Frequency Reference 15 (d1-15) | OFF | ON | ON | ON | OFF |
| 16 | Frequency Reference 16 (d1-16) | ON | ON | ON | ON | OFF |
| 17 | Jog Frequency Reference (d1-17) <1> | − | − | − | − | ON |
Manual — Reference waveforms and frequency limits — page 161
Source reference: SIEP C71060618F, December 2016, physical PDF page 161. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency; d1-01 (A1),d1-02 (A2),d1-03,d1-04,d1-05,d1-06,d1-07; continuation break;d1-12,d1-13,d1-14,d1-15,d1-16,d1-17. FWD/REV Run command; Multi-Step Speed references1,2,3,4; Jog command; ON intervals. Exact selector truth table retained onPDF160; unprinted pulse durations not inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Internal frequency reference; Set frequency reference; Frequency Reference Upper Limit d2-01; Lower Limit d2-02; Operating range. Illustrated reference is clamped between printed limits; no numeric limits supplied by graph. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
u d2: Frequency Upper/Lower Limits
By entering upper or lower frequency limits, the drive programmer can prevent operation of the drive above or below levels that may cause resonance and or equipment damage.
n d2-01: Frequency Reference Upper Limit
Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency references. Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No. Parameter Name Setting Range Default
n d2-02: Frequency Reference Lower Limit
Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency references. If a lower reference than this value is input, the drive will run at the d2-02 level. If the drive is started with a lower reference than d2-02, it will accelerate up to d2-02.
5.4 d: Reference Settings
Parameter Details
d2-01 / Frequency Reference Upper Limit — PDF page 161
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d2-01 | Frequency Reference Upper Limit | 0.0 to 110.0% | 100.0% |
d2-02 / Frequency Reference Lower Limit — PDF page 161
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d2-02 | Frequency Reference Lower Limit | 0.0 to 110.0% | 0.0% |
Manual — Master limits, Jump Frequency and Hold — page 162
Source reference: SIEP C71060618F, December 2016, physical PDF page 162. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output Frequency; Frequency Reference; Increasing frequency reference / Decreasing frequency reference. Jump Frequency3 d3-03, Jump Frequency2 d3-02, Jump Frequency1 d3-01; each Jump Frequency Width d3-04. Source stepped/hysteresis path retained as diagram; no derived switching values. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
n d2-03: Master Speed Reference Lower Limit
Unlike frequency reference lower limit (d2-02) which will affect the frequency reference no matter where it is sourced from (i.e., analog input, preset speed, Jog speed, etc.), the master speed lower limit (d2-03) sets a lower limit that will only affect the analog input (terminals A1 and A2) that is the active master speed frequency. Set as a percentage of the maximum output frequency.
Note: The lower limits for the Jog frequency, multi-step speed settings, and 2-step speed settings do not change. When lower limits are set to both the frequency reference (d2-02) and the main frequency reference (d2-03), the drive uses the greater of those two values as the lower limit.
No. Parameter Name Setting Range Default
u d3: Jump Frequency
n d3-01 to d3-04: Jump Frequencies 1, 2, 3, and Jump Frequency Width
In order to avoid continuous operation at a speed that causes resonance in driven machinery, the drive can be programmed with three separate Jump frequencies that will not allow continued operation within specific frequency ranges. If the speed reference falls within a Jump frequency dead band, the drive will clamp the frequency reference just below the dead band and only accelerate past it when the frequency reference rises above the upper end of the dead band. Setting parameters d3-01 through d3-03 to 0.0 Hz disables the Jump frequency function.
Figure 5.35 shows the relationship between the Jump frequency and the output frequency.
Note: 1. The drive will use the active accel/decel time to pass through the specified dead band range but will not allow continuous operation in that range. 2. When using more than one Jump frequency, make sure that d3-01 ≥ d3-02 ≥ d3-03.
u d4: Frequency Hold and Up/Down 2 Function
n d4-01: Frequency Reference Hold Function Selection
This parameter is effective when either of the digital input functions listed below is used. • Accel/decel ramp hold function (H1-□□= A)
5.4 d: Reference Settings
d2-03 / Master Speed Reference Lower Limit — PDF page 162
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d2-03 | Master Speed Reference Lower Limit | 0.0 to 110.0% | 0.0% |
d3-01 / d3-02 / d3-03 / d3-04 — Jump Frequency 1 — PDF page 162
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d3-01 | Jump Frequency 1 | 0.0 to 400.0 Hz | 0.0 Hz |
| 2 | d3-02 | Jump Frequency 2 | 0.0 to 400.0 Hz | 0.0 Hz |
| 3 | d3-03 | Jump Frequency 3 | 0.0 to 400.0 Hz | 0.0 Hz |
| 4 | d3-04 | Jump Frequency Width | 0.0 to 20.0 Hz | 1.0 Hz |
Manual — Frequency-reference memory modes — page 163
Source reference: SIEP C71060618F, December 2016, physical PDF page 163. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Power supply ON/OFF/ON; Run command OFF/ON/OFF/ON; Accel/Decel Hold input OFF/ON/OFF/ON; Frequency reference / Output frequency; Hold intervals. After power returns, d4-01=1 restores held reference; d4-01=0 line at0. Adjacent source requires hold enabled for restoration. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
• Up/Down function (H1-□□ = 10 and 11, sets the frequency reference by digital inputs) • Up/Down 2 function (H1-□□ = 75/76, adds a bias to the frequency reference using digital inputs) Parameter d4-01 determines whether the frequency reference or the frequency bias (Up/Down 2) value is saved when the Run command is cleared or the power supply is shut down.
No. Parameter Name Setting Range Default
The operation depends on with what function parameter d4-01 is used.
Setting 0: Disabled • Acceleration Hold The hold value will be reset to 0 Hz when the Run command is canceled or the drive power is switched off. The active frequency reference will be the value the drive uses when it restarts. • Up/Down The frequency reference value will be reset to 0 Hz when the Run command is canceled or the drive power is switched off. The drive will start from 0 Hz when restarted. • Up/Down 2 The frequency bias is not saved when the Run command is switched off or 5 s after the Up/Down 2 command has been released. The Up/Down 2 function will start with a bias of 0% when the drive is restarted.
Setting 1: Enabled • Acceleration Hold The last hold value will be saved when the Run command or the drive power is switched off. The drive will use the value that was saved as the frequency reference when it restarts. The accel/decel hold input must be enabled the entire time or else the hold value will be cleared.
• Up/Down The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will use the frequency reference that was saved when it restarts. • Up/Down 2 with Frequency Reference from Digital Operator When the digital operator is selected as the frequency reference source, the bias will be added to the frequency reference that was selected 5 s after the Up/Down 2 command has been released, and then reset to 0 afterwards. The new frequency reference value is then saved. When the Run command or the power supply is switched off, the drive will use the value that was when it restarts.
5.4 d: Reference Settings
Parameter Details
d4-01 / Frequency Reference Hold Function Selection — PDF page 163
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-01 | Frequency Reference Hold Function Selection | 0 or 1 | 0 |
Manual — Up/Down2 bias memory diagrams — page 164
Source reference: SIEP C71060618F, December 2016, physical PDF page 164. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Frequency reference, Output frequency, Bias, Up2 input; 5s. With d4-01=1, bias is added to the frequency reference5s after release, bias reset to0, and new reference saved. Graph values are conceptual; no unprinted setting inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Frequency reference, Output frequency, Bias, Up2 input;5s; d4-01=1; d4-06 value. Other source bias saved to d4-06 five seconds after release; retained at restart. Actual source-limit settings remain separately qualified. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
• Up/Down 2 with Frequency Reference from Other Input Sources When the frequency reference is set by an another source than the digital operator, the bias value will be saved in parameter d4-06 exactly 5 s after the Up/Down 2 command has been released. When the Run command is turned off or the power is switched off, the drive will use the value saved in d4-06 when it restarts.
Note: Make sure to set the Up/Down 2 limits properly when using d4-01 = 1 in combination with the Up/Down 2 function. Refer to d4-08: Frequency Reference Bias Upper Limit (Up/Down 2) on page 166 and Refer to d4-09: Frequency Reference Bias Lower Limit (Up/ Down 2) on page 167 for details on the limit settings.
Clearing the Value that was Saved Depending on which function is used, the frequency reference value that was saved can be cleared by:
5.4 d: Reference Settings
Manual — Up/Down2 steps and selected ramp time — page 165
Source reference: SIEP C71060618F, December 2016, physical PDF page 165. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency; Bias; Up2 input. Bias ramps while input active; acceleration/deceleration time selected by d4-04. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Output frequency; Bias; Up2 input. Bias changes in d4-03 steps; output frequency ramps according to d4-04. No unprinted step count or rate inferred. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
• Releasing the acceleration hold input. • Setting an Up or Down command while no Run command is active.
n d4-03: Frequency Reference Bias Step (Up/Down 2)
Sets the bias that is added to or subtracted from the frequency reference by the Up/Down 2 function.
No. Parameter Name Setting Range Default
The operation depends on the set value:
Setting d4-03 = 0.0 Hz While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel time determined by parameter d4-04.
Setting d4-03 > 0.0 Hz When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The frequency reference changes with the accel/decel times determined by parameter d4-04.
n d4-04: Frequency Reference Bias Accel/Decel (Up/Down 2)
Parameter d4-04 determines the accel/decel times that are used for increasing/decreasing the frequency reference or bias when the Up/Down 2 function is used.
5.4 d: Reference Settings
Parameter Details
d4-03 / Frequency Reference Bias Step — PDF page 165
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-03 | Frequency Reference Bias Step | 0.00 to 99.99 Hz | 0.00 Hz |
d4-04 / Frequency Reference Bias Accel/Decel — PDF page 165
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-04 | Frequency Reference Bias Accel/Decel | 0 or 1 | 0 |
Manual — Bias reset, memory and change thresholds — page 166
Source reference: SIEP C71060618F, December 2016, physical PDF page 166. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 0: Current Accel/Decel Time The drive uses the currently active accel/decel time.
Setting 1: Accel/Decel Time 4 The drive uses accel/decel time 4 set to parameters C1-07 and C1-08.
n d4-05: Frequency Reference Bias Operation Mode Selection (Up/Down 2)
Determines if the bias value is held or not when the Up/Down 2 inputs are both released or both enabled. The parameter is effective only when parameter d4-03 is set to 0.00.
No. Parameter Name Setting Range Default
Setting 0: Hold Bias Value The bias value will be held if no input Up 2 or Down 2 is active.
Setting 1: Reset Bias Value The bias is reset to 0% when both inputs Up 2 and Down 2 are either on or off. The drive will use the accel/decel time as selected in d4-04 to accelerate or decelerate to the frequency reference value.
n d4-06: Frequency Reference Bias (Up/Down 2)
This parameter is used to save the frequency reference bias value set by the Up/Down 2 function. It is set as a percentage of the maximum output frequency. The function of d4-06 depends on how the Up/Down 2 function is configured. • This parameter is not normally used when the frequency reference is set by the digital operator. The user can set d4-06 to a certain value that will be applied when the operation is started, but it will be reset when the frequency reference changes (including multi-step references) or will be disabled when d4-01 = 0 and the Run command is removed. • When d4-01 = 0 and the frequency reference is set by an analog or pulse input, the value set in d4-06 is generally added to or subtracted from the frequency reference. • When d4-01 = 1 and the frequency reference is set by a different source than the digital operator, the bias value adjusted with the Up/Down 2 inputs is stored in d4-06 when 5 s have passed after the Up 2 or Down 2 command release.
Conditions that Generally Reset or Disable Parameter d4-06 • When the Up/Down 2 function has not been assigned to the multi-function terminals • When the frequency reference source has been changed (including LOCAL/REMOTE or external reference 1/external reference 2 switch over by digital inputs) • If d4-03 = 0 Hz, d4-05 = 1 and the Up/Down 2 commands are both open or both closed • Any changes to the maximum frequency set to E1-04
n d4-07: Analog Frequency Reference Fluctuation Limit (Up/Down 2)
This parameter is for handling changes in the frequency reference while the terminal set for Up 2 or Down 2 is enabled. If the frequency reference changes for more than the level set to d4-07, then the bias value will be held, and the drive will accelerate or decelerate following the frequency reference. When the frequency reference is reached, the bias hold is released and the bias follows the Up/Down 2 input commands. Parameter d4-07 is applicable only if the frequency reference is set by an analog or pulse input.
n d4-08: Frequency Reference Bias Upper Limit (Up/Down 2)
Parameter d4-08 sets the upper limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter d4-06. Set this parameter to an appropriate value before using the Up/Down 2 function.
Note: When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the frequency reference if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. From that point the bias can be increased up to the limit set in d4-08 again.
5.4 d: Reference Settings
d4-05 / Frequency Reference Bias Operation Mode Selection — PDF page 166
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-05 | Frequency Reference Bias Operation Mode Selection | 0 or 1 | 0 |
d4-06 / Frequency Reference Bias — PDF page 166
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-06 | Frequency Reference Bias | -99.9 to 100.0% | 0.0% |
d4-07 / Analog Frequency Reference Fluctuation Limit — PDF page 166
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-07 | Analog Frequency Reference Fluctuation Limit | 0.1 to 100.0% | 1.0% |
Manual — Bias limits and Offset Frequencies — page 167
Source reference: SIEP C71060618F, December 2016, physical PDF page 167. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name Setting Range Default
<1> Default setting is determined by the software version. PRG: 1016 and later: 100.00% PRG: 1015 and earlier: 0.00%
n d4-09: Frequency Reference Bias Lower Limit (Up/Down 2)
Parameter d4-08 sets the lower limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter d4-06. Set this parameter to an appropriate value before using the Up/Down 2 function.
Note: When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the frequency reference if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. If the bias is increased using the Up 2 command, once it is added to the frequency reference the speed cannot be reduced with a Down 2 command if the limit set in d4-09 is 0. In this case make sure to set a negative lower limit in d4-09 to allow speed reduction.
n d4-10: Up/Down Frequency Reference Limit Selection
Selects how the lower frequency limit is set when the Up/Down function is used. Refer to Setting 10/11: Up/Down Command on page 187 for details on the Up/Down function in combination with frequency reference limits.
Setting 0: Lower Limit is Determined by d2-02 or Analog Input The lower frequency reference limit is determined by the higher value of both, parameter d2-02 or an analog input that is programmed for “Frequency Bias” (H3-02/10 = 0).
Note: If the external reference change over function (H1-□□ = 2) used to switch between Up/Down function and analog input as reference source, the analog value would become the lower reference limit when the Up/Down reference is active. Change d4-10 to 1 to make the Up/Down function independent of the analog input value.
Setting 1: Lower Limit is Determined by Parameter d2-02 Only parameter d2-02 sets the lower frequency reference limit.
u d7: Offset Frequencies
n d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed for Offset frequency 1, 2 and 3 (H1-□□ = 44, 45, 46). The selected offset values are added if two or all three inputs are closed at the same time.
Note: This function can be used to replace the “Trim Control” function (H1-□□ = 1C/1D) of earlier Yaskawa drives.
Figure 5.41 illustrates the Offset Frequency Function.
5.4 d: Reference Settings
Parameter Details
d4-08 / Frequency Reference Bias Upper Limit — PDF page 167
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-08 | Frequency Reference Bias Upper Limit | 0.0 to 100.0% | <1> |
d4-09 / Frequency Reference Bias Lower Limit — PDF page 167
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d4-09 | Frequency Reference Bias Lower Limit | -99.9 to 0.0% | 0.0% |
d7-01 / d7-02 / d7-03 — Offset Frequency 1 — PDF page 167
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | d7-01 | Offset Frequency 1 | -100.0 to 100.0% | 0% |
| 2 | d7-02 | Offset Frequency 2 | -100.0 to 100.0% | 0% |
| 3 | d7-03 | Offset Frequency 3 | -100.0 to 100.0% | 0% |
Manual — Additive Offset Frequency diagram — page 168
Source reference: SIEP C71060618F, December 2016, physical PDF page 168. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Frequency Reference; Frequency Reference Bias1 d7-01 controlled by Digital Input H1-□□=44; Bias2 d7-02 controlled by H1-□□=45; Bias3 d7-03 controlled by H1-□□=46. Additions to reference; SFS; Frequency reference after Soft Starter. Signed offsets combine when multiple inputs active; exact routing remains original. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
5.4 d: Reference Settings
Manual — Input Voltage and V/f Pattern selection — page 169
Source reference: SIEP C71060618F, December 2016, physical PDF page 169. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
5.5 E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
u E1: V/f Characteristics
n E1-01: Input Voltage Setting
Set the input voltage parameter to the nominal voltage of the AC power supply. This parameter adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.).
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. Failure to comply could result in improper drive operation.
No. Parameter Name Setting Range Default
<1> The setting range and default value shown here are for 200 V class drives. Double this for 400 V class units.
E1-01 Related Values The input voltage setting determines the over-/undervoltage detection level and the operation levels of the braking transistor as well as the KEB function and the overvoltage suppression function.
Voltage | Setting Value of E1-01
(Approximate Values)
ov Detection Level
BTR Operation Level
Uv Detection Level (L2-05)
Desired DC Bus Voltage during KEB (L2-11)
ov Suppression / Stall Prevention Level (L3-17)
Note: The braking transistor operation levels are valid for the drive internal braking transistor. If an external CDBR braking chopper is used, refer to the instruction manual of that unit.
n V/f Pattern Settings
The drive utilizes a set V/f pattern to determine the appropriate output voltage level for each relative to the frequency reference. There are 15 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern can be set up by programming parameters E1-04 through E1-10. V/f Pattern Setup for V/f Control 1. Set the input voltage for the drive. Refer to E1-01: Input Voltage Setting on page 169. 2. Set the V/f pattern by:
a) choosing one of the 15 preset V/f patterns (E1-03 = 0 to E).
b) select the custom V/f pattern (E1-03 = F, default setting). 3. When using one of the 15 presets, E1-04 through E1-13 are automatically set. Refer to the description below.
For a custom V/f pattern, E1-04 through E1-13 must be adjusted manually. Refer to V/f Pattern Settings E1-04 to E1-13 on page 172. Open Loop Vector Control Setup for IM and PM Motors In OLV only the user defined V/f pattern can be used. Refer to V/f Pattern Settings E1-04 to E1-13 on page 172.
n E1-03: V/f Pattern Selection
This parameter can only be changed when the drive is operating in V/f Control. It allows the user to select the V/f pattern from 15 predefined patterns or to create a custom V/f pattern.
Parameter Details
200 V Class | all settings
400 V Class | setting ≥ 400 V
400 V Class | setting < 400 V
E1-01 <1> / Input Voltage Setting — PDF page 169
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E1-01 <1> | Input Voltage Setting | 155 to 255 V | 230 V |
E1-01 Related Values (Approximate Values) — PDF page 169
| Source row | Voltage class | Setting value E1-01 | Approximate ov detection | Approximate BTR operation | Approximate Uv detection L2-05 | Approximate DC bus KEB L2-11 | Approximate ov suppression/Stall Prevention L3-17 |
|---|---|---|---|---|---|---|---|
| 1 | 200 V Class | all settings | 410 V | 394 V | 190 V (single-phase = 160 V) | 240 V | 370 V |
| 2 | 400 V Class | setting ≥ 400 V | 820 V | 788 V | 380 V | 480 V | 740 V |
| 3 | 400 V Class | setting < 400 V | 740 V | 708 V | 350 V | 440 V | 660 V |
E1-03 / V/f Pattern Selection — PDF page 169
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E1-03 | V/f Pattern Selection | 0 to F | F |
Manual — Preset V/f patterns and small-power graphs — page 170
Source reference: SIEP C71060618F, December 2016, physical PDF page 170. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
200V class 0.1–3.7kW, setting0. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting1. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting2. Frequency-axis printed labels (Hz):0,1.5,3,50,60. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting3. Frequency-axis printed labels (Hz):0,1.5,3,60,72. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting4. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):8,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting5. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):9,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting6. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):8,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting7. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):9,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Setting the V/f Pattern Choose the V/f pattern that meets the application demands from the table below. Set the correct value to E1-03. The V/f parameters E1-04 to E1-13 can only be monitored, not changed.
Note: 1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation. 2. Parameter E1-03 is not reset when the drive is initialized.
Table 5.16 Predefined V/f Patterns
Setting Specification Characteristic Application
The following tables show details on predefined V/f patterns. The following graphs are for 200 V class drives; double the values for 400 V class drives.
Predefined V/f Patterns for 0.1 to 3.7 kW Drives Table 5.17 Constant Torque Characteristics, Settings 0 to 3
Table 5.18 Derated Torque Characteristics, Settings 4 to 7
5.5 E: Motor Parameters
Table5.16 Predefined V/f Patterns — PDF page 170
| Source row | Setting | Specification | Characteristic | Application |
|---|---|---|---|---|
| 1 | 0 | 50 Hz | Constant torque | For general purpose applications. Torque remains constant regardless of changes to speed. |
| 2 | 1 | 60 Hz (default setting) | Constant torque | For general purpose applications. Torque remains constant regardless of changes to speed. |
| 3 | 2 | 60 Hz (with 50 Hz base) | Constant torque | For general purpose applications. Torque remains constant regardless of changes to speed. |
| 4 | 3 | 72 Hz (with 60 Hz base) | Constant torque | For general purpose applications. Torque remains constant regardless of changes to speed. |
| 5 | 4 | 50 Hz, Heavy Duty 2 | Derated torque | For fans, pumps, and other applications that require torque derating relative to the load. |
| 6 | 5 | 50 Hz, Heavy Duty 1 | Derated torque | For fans, pumps, and other applications that require torque derating relative to the load. |
| 7 | 6 | 60 Hz, Heavy Duty 1 | Derated torque | For fans, pumps, and other applications that require torque derating relative to the load. |
| 8 | 7 | 60 Hz, Heavy Duty 2 | Derated torque | For fans, pumps, and other applications that require torque derating relative to the load. |
| 9 | 8 | 50 Hz, mid starting torque | High starting torque | Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed |
| 10 | 9 | 50 Hz, high starting torque | High starting torque | Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed |
| 11 | A | 60 Hz, mid starting torque | High starting torque | Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed |
| 12 | B | 60 Hz, high starting torque | High starting torque | Select high starting torque when: • Wiring between the drive and motor exceeds 150 m • A large amount of starting torque is required • An AC reactor is installed |
| 13 | C | 90 Hz (with 60 Hz base) | Constant output | When operating at greater than 60 Hz the output voltage will be constant. |
| 14 | D | 120 Hz (with 60 Hz base) | Constant output | When operating at greater than 60 Hz the output voltage will be constant. |
| 15 | E | 180 Hz (with 60 Hz base) | Constant output | When operating at greater than 60 Hz the output voltage will be constant. |
Manual — Power-specific V/f pattern graphs — page 171
Source reference: SIEP C71060618F, December 2016, physical PDF page 171. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
200V class 0.1–3.7kW, setting8. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):12,19,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, setting9. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):13,24,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, settingA. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):12,19,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, settingB. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):15,24,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, settingC. Frequency-axis printed labels (Hz):0,1.5,3,60,90. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, settingD. Frequency-axis printed labels (Hz):0,1.5,3,60,120. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, settingE. Frequency-axis printed labels (Hz):0,1.5,3,60,180. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 0.1–3.7kW, settingF. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):12,16,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting0. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting1. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting2. Frequency-axis printed labels (Hz):0,1.5,3,50,60. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting3. Frequency-axis printed labels (Hz):0,1.5,3,60,72. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting4. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):6,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting5. Frequency-axis printed labels (Hz):0,1.3,25,50. Voltage-axis printed labels (V):7,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting6. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):6,35,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting7. Frequency-axis printed labels (Hz):0,1.5,30,60. Voltage-axis printed labels (V):7,50,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting8. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):9,18,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, setting9. Frequency-axis printed labels (Hz):0,1.3,2.5,50. Voltage-axis printed labels (V):11,23,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, settingA. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):9,18,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, settingB. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):13,23,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Table 5.19 High Starting Torque, Settings 8 to B
Table 5.20 Rated Output Operation, Settings C to F
Predefined V/f Patterns for 5.5 to 18.5 kW Drives The following graphs are for 200 V class drives. Double values when using a 400 V class drive.
Table 5.21 Rated Torque Characteristics, Settings 0 to 3
Table 5.22 Derated Torque Characteristics, Settings 4 to 7
Table 5.23 High Starting Torque, Settings 8 to B
5.5 E: Motor Parameters
Parameter Details
Manual — Custom V/f settings, graphs and qualifications — page 172
Source reference: SIEP C71060618F, December 2016, physical PDF page 172. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output Voltage: E1-05,E1-12,E1-13,E1-08,E1-10; Frequency:E1-09,E1-07,E1-06,E1-11,E1-04. Visible point pairs E1-09/E1-10, E1-07/E1-08, E1-06/E1-13, E1-11/E1-12, E1-04/E1-05. Full unit and mode footnotes apply; no interpolated values. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, settingC. Frequency-axis printed labels (Hz):0,1.5,3,60,90. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, settingD. Frequency-axis printed labels (Hz):0,1.5,3,60,120. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, settingE. Frequency-axis printed labels (Hz):0,1.5,3,60,180. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
200V class 5.5–18.5kW, settingF. Frequency-axis printed labels (Hz):0,1.5,3,60. Voltage-axis printed labels (V):7,14,200. Source says double voltage values for400V class; frequencies are not doubled. Values are preset figure labels, not measured motor outputs or separately inferred coordinates. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
Table 5.24 Constant Output, Settings C to F
Setting a Custom V/f Pattern Setting parameter E1-03 to “F” allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13. When E1-03 is changed to “F”, the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 1 of the predefined patterns.
n V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if E1-03 =< 15 or set up a custom V/f pattern as shown in Figure 5.42 when E1-03 = F.
No. Parameter Name Setting Range Default
<1> Default setting is determined by the control mode. <2> Values shown are for 200 V class drives; double the value when using 400 V class drives. <3> In OLV for PM E1-09 specifies the start frequency for short circuit braking at stop. Refer to b2-13: Short Circuit Brake Time at Stop on page 129 for details. <4> When E1-13 is set to 0.0 V, the drive uses the value set in E1-05 to control the voltage. <5> Default setting is determined by E5-01 in OLV/PM. When E5-01 is set to FFFFH, the setting range for E1-04 and E1-06 is 10.0 to 40.0 Hz and the setting range for E1-09 is 0.0 to 400.0 Hz.
Note: 1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
5.5 E: Motor Parameters
E1-04 / E1-05 / E1-06 / E1-07 / E1-08 / E1-09 <3> / E1-10 / E1-11 / E1-12 / E1-13 <4> — Maximum Output Frequency — PDF page 172
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E1-04 | Maximum Output Frequency | 40.0 to 400.0 Hz <5> | <1> |
| 2 | E1-05 | Maximum Voltage | 0.0 to 255.0 V <2> | <1> |
| 3 | E1-06 | Base Frequency | 0.0 to 400.0 Hz <5> | <1> |
| 4 | E1-07 | Middle Output Frequency | 0.0 to 400.0 Hz | <1> |
| 5 | E1-08 | Middle Output Frequency Voltage | 0.0 to 255.0 V <2> | <1> |
| 6 | E1-09 <3> | Minimum Output Frequency | 0.0 to 400.0 Hz <5> | <1> |
| 7 | E1-10 | Minimum Output Frequency Voltage | 0.0 to 255.0 V <2> | <1> |
| 8 | E1-11 | Middle Output Frequency 2 | 0.0 to 400.0 Hz | 0.0 Hz |
| 9 | E1-12 | Middle Output Frequency Voltage 2 | 0.0 to 255.0 V <2> | 0.0 V |
| 10 | E1-13 <4> | Base Voltage | 0.0 to 255.0 Hz | 0.0 V |
Manual — Motor1 data, slip and resistance — page 173
Source reference: SIEP C71060618F, December 2016, physical PDF page 173. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
- Setting E1-11 to 0 disables both E1-11 and E1-12 and the above conditions do not apply. 3. To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded. 4. E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned to their default values.
u E2: Motor 1 Parameters
These parameters contain the most important motor data needed for optimal motor control. The parameters are set automatically during Auto-Tuning. Set the parameters manually when Auto-Tuning cannot be performed.
n E2-01: Motor Rated Current
Set E2-01 to the full load amps (FLA) stamped on the motor nameplate. During Auto-Tuning the value must be entered to parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E2-01.
No. Parameter Name Setting Range Default
Note: 1. Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. 2. Change E2-01 only after changing the value set to E2-03. Setting E2-01 < E2-03 will trigger an oPE02 error.
n E2-02: Motor Rated Slip
Sets the motor rated slip in Hz. This value is automatically set during Rotational Auto-Tuning.
If Auto-Tuning cannot be performed calculate the motor rated slip using the information written on the motor nameplate and the formula below: E2-02 = f - (n x p)/120 (f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)
n E2-03: Motor No-Load Current
Set E2-03 to the motor no-load current at rated voltage and rated frequency. If Rotational Auto-Tuning completes successfully, this value is automatically calculated. If Auto-Tuning cannot be performed, contact the motor manufacturer for information about the no-load current.
Note: Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.
n E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. This value must be entered during Auto-Tuning, and will automatically be saved to E2-04 if Auto-Tuning completes successfully.
n E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. If the Auto-Tuning completes successfully, this value is automatically calculated. Remember this value must be entered as line-line and not line-neutral.
Note: The setting range becomes 0.00 to 130.00 when using BA0002, 2A0002, 4A0001 and smaller.
5.5 E: Motor Parameters
Parameter Details
E2-01 / Motor Rated Current — PDF page 173
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-01 | Motor Rated Current | 10% to 200% of the drive rated current. (unit: 0.01 A) | Depending on o2-04 |
E2-02 / Motor Rated Slip — PDF page 173
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-02 | Motor Rated Slip | 0.00 to 20.00 Hz | Depending on o2-04 |
E2-03 / Motor No-Load Current — PDF page 173
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-03 | Motor No-Load Current | 0 to [E2-01] (unit: 0.01 A) | Depending on o2-04 |
E2-04 / Number of Motor Poles — PDF page 173
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-04 | Number of Motor Poles | 2 to 48 poles | 4 poles |
E2-05 / Motor Line-to-Line Resistance — PDF page 173
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-05 | Motor Line-to-Line Resistance | 0.000 to 65.000 Ω | Depending on o2-04 |
Manual — Motor1 loss and saturation parameters — page 174
Source reference: SIEP C71060618F, December 2016, physical PDF page 174. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
If Auto-Tuning is not possible, then contact the motor manufacturer to find out the line-to-line resistance or measure it manually. When using the manufacturer Motor Test Report, calculate E2-05 by the formulas below. • E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C • B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the Test Report at 75 °C. • F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the Test Report at 115 °C.
n E2-06: Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage.
No. Parameter Name Setting Range Default
n E2-07: Motor Iron-Core Saturation Coefficient 1
This parameter sets the motor iron saturation coefficient at 50% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then this value is automatically calculated.
n E2-08: Motor Iron-Core Saturation Coefficient 2
This parameter sets the motor iron saturation coefficient at 75% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then this value is automatically calculated.
n E2-09: Motor Mechanical Loss
This parameter sets to the motor mechanical loss as a percentage of motor rated power (kW) capacity.
Adjust this setting in the following circumstances: • When there is a large amount of torque loss due to motor bearing friction. • When there is a large amount of torque loss in a fan or pump application. The setting for the mechanical loss is added to the torque.
n E2-10: Motor Iron Loss for Torque Compensation
This parameter sets the motor iron loss in watts.
n E2-11: Motor Rated Power
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto- Tuning completes successfully, the value entered will automatically be saved to E2-11.
n E2-12: Motor Iron-Core Saturation Coefficient 3
This parameter sets the motor iron saturation coefficient at 130% of the magnetic flux.
5.5 E: Motor Parameters
E2-06 / Motor Leakage Inductance — PDF page 174
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-06 | Motor Leakage Inductance | 0.0 to 40.0% | Depending on o2-04 |
E2-07 / Motor Iron-Core Saturation Coefficient 1 — PDF page 174
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-07 | Motor Iron-Core Saturation Coefficient 1 | 0.00 to 0.50 | 0.50 |
E2-08 / Motor Iron-Core Saturation Coefficient 2 — PDF page 174
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-08 | Motor Iron-Core Saturation Coefficient 2 | E2-07 to 0.75 | 0.75 |
E2-09 / Motor Mechanical Loss — PDF page 174
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-09 | Motor Mechanical Loss | 0.0 to 10.0% | 0.0% |
E2-10 / Motor Iron Loss for Torque Compensation — PDF page 174
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-10 | Motor Iron Loss for Torque Compensation | 0 to 65535 W | Depending on o2-04 |
E2-11 / Motor Rated Power — PDF page 174
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-11 | Motor Rated Power | 0.00 to 650.00 kW | Depending on o2-04 |
E2-12 / Motor Iron-Core Saturation Coefficient 3 — PDF page 174
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E2-12 | Motor Iron-Core Saturation Coefficient 3 | 1.30 to 5.00 | 1.30 |
Manual — Motor2 control and V/f pattern — page 175
Source reference: SIEP C71060618F, December 2016, physical PDF page 175. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output Voltage:E3-05,E3-12,E3-13,E3-08,E3-10; Frequency:E3-09,E3-07,E3-06,E3-11,E3-04. Point labels retained without deriving intermediate voltage; source voltage-class and mode footnotes apply. Source diagram geometry, exact routing and unprinted numerical values remain original-only.
u E3: V/f Characteristics for Motor 2
These parameters set the V/f pattern used for motor 2. Refer to Setting 16: Motor 2 Selection on page 189 for details on switching motors.
n E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. Motor 2 cannot be used in OLV/PM control mode.
No. Parameter Name Setting Range Default
Setting 0: V/f Control
Setting 2: Open Loop Vector Control
n E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 like shown in Figure 5.43.
<1> Values shown here are for 200 V class drives. Multiply voltage values by 1.15 for U-spec drives. Double the value when using 400 V class drives. <2> Default setting is determined by the control mode for motor 2.
Note: 1. The following condition must be true when setting up the V/f pattern: E3-09 ≤ E3-07 ≤ E3-06 ≤ E3-11 ≤ E3-04 2. To make the V/f pattern a straight line set E3-09 = E3-07. In this case the E3-08 setting is disregarded.
5.5 E: Motor Parameters
Parameter Details
E3-01 / Motor 2 Control Mode Selection — PDF page 175
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E3-01 | Motor 2 Control Mode Selection | 0 or 2 | 0 |
E3-04 / E3-05 / E3-06 / E3-07 / E3-08 / E3-09 / E3-10 / E3-11 / E3-12 / E3-13 — Motor 2 Max Output Frequency — PDF page 175
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E3-04 | Motor 2 Max Output Frequency | 40.0 to 400.0 Hz | 60.0 Hz |
| 2 | E3-05 | Motor 2 Max Voltage | 0.0 to 255.0 V <1> | 230.0 V <1> |
| 3 | E3-06 | Motor 2 Base Frequency | 0.0 to 400.0 Hz | 60.0 Hz |
| 4 | E3-07 | Motor 2 Mid Output Frequency | 0.0 to 400.0 Hz | <2> |
| 5 | E3-08 | Motor 2 Mid Output Frequency Voltage | 0.0 to 255.0 V <1> | <2> |
| 6 | E3-09 | Motor 2 Minimum Output Frequency | 0.0 to 400.0 Hz | <2> |
| 7 | E3-10 | Motor 2 Minimum Output Frequency Voltage | 0.0 to 255.0 V <1> | <2> |
| 8 | E3-11 | Motor 2 Mid Output Frequency 2 | 0.0 to 400.0 Hz | 0.0 Hz |
| 9 | E3-12 | Motor 2 Mid Output Frequency Voltage 2 | 0.0 to 255.0 V <1> | 0.0 Vac |
| 10 | E3-13 | Motor 2 Base Voltage | 0.0 to 255.0 V <1> | 0.0 Vac |
Manual — Motor2 current, slip and resistance — page 176
Source reference: SIEP C71060618F, December 2016, physical PDF page 176. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u E4: Motor 2 Parameters
E4 parameters contain the motor data for motor 2. These parameters are usually set automatically during the Auto-Tuning process. They may need to be set manually if there is a problem performing Auto-Tuning.
n E4-01: Motor 2 Rated Current
Set E4-01 to the full load amps (FLA) stamped on the nameplate of motor 2. During Auto-Tuning the value must be entered to parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E4-01.
No. Parameter Name Setting Range Default
Note: Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units.
n E4-02: Motor 2 Rated Slip
This parameter sets the motor 2 rated slip frequency. The drive calculates this value automatically during Rotational Auto- Tuning. For information on calculating the motor rated slip, see the description for E2-02.
n E4-03: Motor 2 Rated No-Load Current
Set E4-03 to the motor no-load current at rated voltage and rated frequency. If Rotational Auto-Tuning completes successfully, this value is automatically calculated. If Auto-Tuning cannot be performed contact the motor manufacturer for information about the no-load current.
n E4-04: Motor 2 Motor Poles
Set the pole number of motor 2 to E4-04. During Auto-Tuning the value must entered to parameter T1-06. If Auto-Tuning completes successfully, the entered value will automatically be saved to E4-04.
n E4-05: Motor 2 Line-to-Line Resistance
Sets the line-to-line resistance of motor 2 stator winding. If the Auto-tuning completes successfully, this value is automatically calculated. Remember this value must be entered as line-line and not line-neutral.
Note: The setting range is 0.00 to 130.00 when using a drive capacity of 0.2 kW or less. Refer to E2-05: Motor Line-to-Line Resistance on page 173 to manually enter this parameter setting.
n E4-06: Motor 2 Leakage Inductance
Sets the voltage drop due to motor leakage inductance of motor 2. The value is set as a percentage of the rated voltage.
5.5 E: Motor Parameters
E4-01 / Motor 2 Rated Current — PDF page 176
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-01 | Motor 2 Rated Current | 10 to 200% of the drive rated current. | Depending on o2-04 |
E4-02 / Motor 2 Rated Slip — PDF page 176
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-02 | Motor 2 Rated Slip | 0.00 to 20.00 Hz | Depending on o2-04 |
E4-03 / Motor 2 Rated No-Load Current — PDF page 176
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-03 | Motor 2 Rated No-Load Current | 0 to [E4-01] | Depending on o2-04 |
E4-04 / Motor 2 Motor Poles — PDF page 176
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-04 | Motor 2 Motor Poles | 2 to 48 | 4 |
E4-05 / Motor 2 Line-to-Line Resistance — PDF page 176
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-05 | Motor 2 Line-to-Line Resistance | 0.000 to 65.000 Ω | Depending on o2-04 |
E4-06 / Motor 2 Leakage Inductance — PDF page 176
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-06 | Motor 2 Leakage Inductance | 0.0 to 40.0% | Depending on o2-04 |
Manual — Motor2 losses, saturation and compensation — page 177
Source reference: SIEP C71060618F, December 2016, physical PDF page 177. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n E4-07: Motor 2 Motor Iron-Core Saturation Coefficient 1
Sets the motor 2 iron saturation coefficient at 50% of magnetic flux. This value is automatically set during Rotational Auto- Tuning.
No. Parameter Name Setting Range Default
n E4-08: Motor 2 Motor Iron-Core Saturation Coefficient 2
Sets the motor iron saturation coefficient at 75% of magnetic flux. This value is automatically set during Rotational Auto- Tuning.
n E4-09: Motor 2 Mechanical Loss
Sets the motor mechanical loss as a percentage of motor rated power (kW).
This parameter seldom needs to be changed, but may need to be adjusted in the following circumstances: • When there is a large amount of torque loss due to motor bearing friction. • When there is a large amount of torque loss in a fan or pump application.
n E4-10: Motor 2 Iron Loss
Sets the motor 2 iron loss in watts.
n E4-11: Motor 2 Rated Power
Sets the motor 2 rated power. During Auto-Tuning the value must entered to parameter T1-02. If Auto-Tuning completes successfully, the entered value will automatically be saved to E4-11.
n E4-12: Motor 2 Iron-Core Saturation Coefficient 3
Sets the motor 2 iron saturation coefficient at 130% of magnetic flux.
n E4-14: Motor 2 Slip Compensation Gain
Instead of C3-01 the value of E4-14 is used as gain for slip compensation when motor 2 is selected. Refer to C3-01: Slip Compensation Gain on page 151 for details and setting instructions.
n E4-15: Motor 2 Torque Compensation Gain
Instead of C4-01 the value of E4-15 is used as gain for torque compensation when motor 2 is selected. Refer to C4-01: Torque Compensation Gain on page 152 for details and setting instructions.
5.5 E: Motor Parameters
Parameter Details
E4-07 / Motor 2 Motor Iron-Core Saturation Coefficient 1 — PDF page 177
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-07 | Motor 2 Motor Iron-Core Saturation Coefficient 1 | 0.00 to 0.50 | 0.50 |
E4-08 / Motor 2 Motor Iron-Core Saturation Coefficient 2 — PDF page 177
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-08 | Motor 2 Motor Iron-Core Saturation Coefficient 2 | [E4-07] to 0.75 | 0.75 |
E4-09 / Motor 2 Mechanical Loss — PDF page 177
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-09 | Motor 2 Mechanical Loss | 0.00 to 10.0% | 0.0% |
E4-10 / Motor 2 Iron Loss — PDF page 177
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-10 | Motor 2 Iron Loss | 0 to 65535 W | Depending on o2-04 |
E4-11 / Motor 2 Rated Power — PDF page 177
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-11 | Motor 2 Rated Power | 0.00 to 650.00 kW | Depending on o2-04 |
E4-12 / Motor 2 Iron-Core Saturation Coefficient 3 — PDF page 177
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-12 | Motor 2 Iron-Core Saturation Coefficient 3 | 1.30 to 5.00 | 1.30 |
E4-14 / Motor 2 Slip Compensation Gain — PDF page 177
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-14 | Motor 2 Slip Compensation Gain | 0.0 to 2.50 | Depending on E3-01 |
Manual — PM motor code and basic ratings — page 178
Source reference: SIEP C71060618F, December 2016, physical PDF page 178. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Illustration 0000. First character:0 Pico Motor (SMRA Series);1 Derated Torque for IPM Motors (SSR1 Series). Second character:0 1800r/min Series;1 3600r/min Series;2 1750r/min Series;3 1450r/min Series;4 1150r/min Series;F Special Motor. Remaining two characters: Motor Voltage Class and Capacity. No unprinted voltage/capacity code mappings inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
No. Parameter Name Setting Range Default
u E5: PM Motor Settings
These parameters set the motor data of a PM motor used in OLV for PM (A1-02 = 5). When Yaskawa motors are used, entering the motor code written on the motor nameplate will set up the E5-□□ parameters. For all other PM motors, the data must be entered manually.
n E5-01: PM Motor Code Selection
Set the motor code for the PM motor being used. Depending on the motor code entered, the drive automatically sets several parameters to appropriate values. Refer to Parameters that Change with the Motor Code Selection on page 417 for details on the supported motor codes and their parameter settings.
Note: 1. This parameter is not reset when the drive is initialized using parameter A1-03. 2. The default setting is for a Yaskawa SMRA Series SPM Motor with a speed rating of 1800 r/min. 3. Changing the motor code setting resets all E5-□□ settings to their default values. 4. Set to “FFFF” when using a non-Yaskawa PM motor or one that is not supported by the motor code settings. Figure 5.44 explains the motor code setting.
n E5-02: Motor Rated Power (PM OLV)
Sets the rated power of the motor.
Note: This parameter is not reset when the drive is initialized using A1-03.
n E5-03: Motor Rated Current (PM OLV)
Sets the motor rated current in amps.
Note: 1. Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. 2. This parameter is not reset when the drive is initialized using A1-03.
n E5-04: Number of Motor Poles (PM OLV)
Sets the number of motor poles.
5.5 E: Motor Parameters
E4-15 / Motor 2 Torque Compensation Gain — PDF page 178
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E4-15 | Motor 2 Torque Compensation Gain | 0.0 to 2.50 | 1.00 |
E5-01 / PM Motor Code Selection — PDF page 178
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-01 | PM Motor Code Selection | 0000 to FFFF | Depending on o2-04 |
E5-02 / Motor Rated Power — PDF page 178
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-02 | Motor Rated Power | 0.10 to 18.50 kW | Depending on E5-01 |
E5-03 / Motor Rated Current — PDF page 178
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-03 | Motor Rated Current | 10 to 200% of drive rated current | Depending on E5-01 |
E5-04 / Number of Motor Poles — PDF page 178
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-04 | Number of Motor Poles | 2 to 48 | Depending on E5-01 |
Manual — PM resistance, inductance and voltage constants — page 179
Source reference: SIEP C71060618F, December 2016, physical PDF page 179. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n E5-05: Motor Stator Resistance (PM OLV)
Set the resistance for each motor phase (not line-to-line resistance). When measuring the resistance manually make sure to enter the resistance of one phase into E5-05.
No. Parameter Name Setting Range Default
Note: This parameter is not reset when the drive is initialized using A1-03.
n E5-06: Motor d Axis Inductance (PM OLV)
Sets the d axis inductance in units of 0.01 mH. Contact the motor manufacturer for d-axis inductance. If an LCR meter is available, enter half the value of the measurement taken.
n E5-07: Motor q Axis Inductance (PM OLV)
Sets the q axis inductance in units of 0.01 mH. Contact the motor manufacturer for d-axis inductance. If an LCR meter is available, enter half the value of the measurement taken.
n E5-09: Motor Induction Voltage Constant 1 (PM OLV)
Set the induced phase peak voltage in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an SSR1 series IPM motor with derated torque or an SST4 series motor with constant torque. When E5-01 is set to “FFFF” use either E5-09 or E5-24 for setting the voltage constant.
Note: 1. Ensure that E5-24 = 0 when setting parameter E5-09. An alarm will be triggered, however, if both E5-09 and E5-24 are set 0, or if neither parameter is set to 0. 2. This parameter is not reset when the drive is initialized using A1-03.
n E5-24: Motor Induction Voltage Constant 2 (PM OLV)
Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter to 0 when using an SMRA Series SPM Motor. When E5-01 is set to “FFFF” use either E5-09 or E5-24 for setting the voltage constant.
<1> Range depends on the drive software version. PRG: 1018 and later: 0.0 to 6500.0 mV/(r/min) PRG: 1017 and earlier: 0.0 to 2000.0 mV/(r/min)
Note: 1. If E5-03 is not set to 0, then setting both E5-09 and E5-24 to 0, or setting neither E5-09 nor E5-24 to 0, will trigger an oPE08 error. However, if E5-03 is set to 0, setting both E5-09 and E5-24 to 0 will not trigger the error. 2. This parameter is not reset when the drive is initialized using A1-03. 3. The values for the electrical and mechanical angle should be set using the same units specified by the manufacturer of the motor.
n E5-39: Current Detection Delay Time
Sets the current detection delay time of d-Axis and q-Axis current feedback calculation.
5.5 E: Motor Parameters
Parameter Details
E5-05 / Motor Stator Resistance — PDF page 179
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-05 | Motor Stator Resistance | 0.000 to 65.000 Ω | Depending on E5-01 |
E5-06 / Motor d Axis Inductance — PDF page 179
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-06 | Motor d Axis Inductance | 0.00 to 300.00 mH | Depending on E5-01 |
E5-07 / Motor q Axis Inductance — PDF page 179
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-07 | Motor q Axis Inductance | 0.00 to 600.00 mH | Depending on E5-01 |
E5-09 / Motor Induction Voltage Constant 1 — PDF page 179
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-09 | Motor Induction Voltage Constant 1 | 0.0 to 2000.0 mV/(rad/s) | Depending on E5-01 |
E5-24 / Motor Induction Voltage Constant 2 (PM OLV) — PDF page 179
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-24 | Motor Induction Voltage Constant 2 (PM OLV) | <1> | Depending on E5-01 |
Manual — PM current calculation delay — page 180
Source reference: SIEP C71060618F, December 2016, physical PDF page 180. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Changing this parameter from the default setting is not normally required.
Note: Parameter available in drive software versions PRG: 1022 and later.
No. Parameter Name Setting Range Default
5.5 E: Motor Parameters
E5-39 / Current Detection Delay Time — PDF page 180
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | E5-39 | Current Detection Delay Time | -1000 to 1000 µs | 0 µs |
Manual — PG fault operations and detection thresholds — page 181
Source reference: SIEP C71060618F, December 2016, physical PDF page 181. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
5.6 F: Option Settings
u F1: Error Detection for V/f Control with PG
A one-track pulse signal can be connected to the drive pulse train input RP as speed feedback. Using this signal for slip compensation improves the speed control accuracy. This function is only available for motor 1. The F1 parameters determine how the error detection for the speed feedback signal works. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details on how to activate and tune the function.
n Operation at PG Fault Detection
The drive lets the user select from one of four possible operations when a fault occurs with the PG encoder. The operation can be set up separately for each fault using parameters F1-02/03/04. The table below list the stopping methods and the parameter setting values.
Table 5.25 Stopping Methods for PGo, oS, dEv Detection
Description Setting
NOTICE: Setting = 3: Alarm only will provide an alarm only while continuing to run the motor during abnormal PG fault conditions. This may cause damage to machinery. Use caution when selecting this setting.
n F1-02: Operation Selection at PG Open Circuit (PGo)
Sets the stopping method when a PG open circuit fault (PGo) occurs. Refer to Table 5.25 for setting explanations.
No. Parameter Name Setting Range Default
n F1-03: Operation Selection at Overspeed
Sets the stopping method when an overspeed (oS) fault occurs. Refer to Table 5.25 for setting explanations.
n F1-04: Operation Selection at Deviation
Sets the stopping method when a speed deviation (dEv) fault occurs. Refer to Table 5.25 for setting explanations.
n F1-08/F1-09: Overspeed Detection Level/Delay Time
F1-08 sets the detection level for an overspeed (oS) fault as a percentage of the maximum output frequency. The speed feedback has to exceed this level for longer than the time set in F1-09 before a fault is detected.
n F1-10/F1-11: Excessive Speed Deviation Detection Level/Delay Time
F1-10 sets the detection level for a speed deviation (dEv) fault as a percentage of the maximum output frequency. The speed feedback has to exceed this level for longer than the time set in F1-11 before a fault is detected. Speed deviation is the difference between actual motor speed and the frequency reference command.
Parameter Details
Table5.25 Stopping Methods for PGo, oS, dEv Detection — PDF page 181
| Source row | Description | Setting |
|---|---|---|
| 1 | Ramp to Stop (uses the deceleration time set to C1-02) | 0 |
| 2 | Coast to Stop | 1 |
| 3 | Fast-stop (uses the Fast-stop time set to C1-09) | 2 |
| 4 | Alarm only | 3 |
F1-02 / Operation Selection at PG Open Circuit (PGo) — PDF page 181
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F1-02 | Operation Selection at PG Open Circuit (PGo) | 0 to 3 | 1 |
F1-03 / Operation Selection at Overspeed (oS) — PDF page 181
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F1-03 | Operation Selection at Overspeed (oS) | 0 to 3 | 1 |
F1-04 / Operation Selection at Deviation (dEv) — PDF page 181
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F1-04 | Operation Selection at Deviation (dEv) | 0 to 3 | 3 |
F1-08 / F1-09 — Overspeed Detection Level — PDF page 181
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F1-08 | Overspeed Detection Level | 0 to 120% | 115% |
| 2 | F1-09 | Overspeed Detection Delay Time | 0.0 to 2.0 s | 1.0 s |
Manual — Communications fault actions and detection — page 182
Source reference: SIEP C71060618F, December 2016, physical PDF page 182. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name Setting Range Default
n F1-14: PG Open-Circuit Detection Time
Sets the time required to detect PGo if no pulse signal is present at terminal RP.
u F6: Serial Communications Option Card Settings
These parameters configure communication option cards and communication fault detection methods.
n F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
Setting 4: Alarm and Run at d1-04 Note: Take proper safety measures, such as installing an emergency stop switch, as the drive will continue operation when detecting an bUS error.
Setting 5: Alarm and Ramp to stop
n F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
Setting 0: Always Detected
Setting 1: Detection During Run Only
n F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
n F6-07: NetRef/ComRef Function Selection
Selects how multi-step speed inputs are treated when the NetRef command is set.
5.6 F: Option Settings
F1-10 / F1-11 — Excessive Speed Deviation Detection Level — PDF page 182
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F1-10 | Excessive Speed Deviation Detection Level | 0 to 50% | 10% |
| 2 | F1-11 | Excessive Speed Deviation Detection Delay Time | 0.0 to 10.0 s | 0.5 s |
F1-14 / PG Open-Circuit Detection Time — PDF page 182
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F1-14 | PG Open-Circuit Detection Time | 0.0 to 10.0 s | 2.0 s |
F6-01 / Communications Error Operation Selection — PDF page 182
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F6-01 | Communications Error Operation Selection | 0 to 5 | 1 |
F6-02 / External Fault from Comm. Option Selection — PDF page 182
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F6-02 | External Fault from Comm. Option Selection | 0 or 1 | 0 |
F6-03 / External Fault from Comm. Option Operation Selection — PDF page 182
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F6-03 | External Fault from Comm. Option Operation Selection | 0 to 3 | 1 |
Manual — Option resets and communications scopes — page 183
Source reference: SIEP C71060618F, December 2016, physical PDF page 183. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Parameter Name Setting Range Default
Setting 0: Multi-Step Speed Operation Disabled If the NetRef command is selected, multi-step speed input frequency references are disabled. This is the same as Yaskawa F7 drives.
Setting 1: Multi-Step Speed Operation Enabled Multi-step speed inputs are active and can override the frequency reference from the communications option even when the NetRef command is selected. This is the same as Yaskawa F7 drives.
n F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-□□ and F7-□□) are reset when the drive is initialized using A1-03.
Setting 0: Do Not Reset Parameters F6-□□ and F7-□□ when the Drive Is Initialized with A1-03 Setting 1: Reset F6-□□ and F7-□□ when the Drive Is Initialized with A1-03 Note: F6-08 is not reset when the drive is initialized, but does determine whether initializing the drive with A1-03 resets communication parameters F6-□□ and F7-□□.
u MECHATROLINK-II Parameters
Parameters F6-20 through F6-26 set up the drive to operate on a MECHATROLINK-II network. Refer to the option manual for details on parameter settings.
u MECHATROLINK-III Parameters
Parameters F6-20, F6-21, and F6-23 through F6-26 set up the drive to operate on a MECHATROLINK-III network. Refer to the option manual for details on parameter settings.
u PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network. Refer to the option manual for details on parameter settings.
u DeviceNet Parameters
Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network. Refer to the option manual for details on parameter settings.
u F7-01 to F7-42: EtherNet/IP and Modbus TCP/IP Option Parameters
F7-□□ parameters are reserved for use with SI-EN3/V and SI-EM3/V options. Refer to the Option Installation Manuals for details.
5.6 F: Option Settings
Parameter Details
F6-07 / NetRef/ComRef Function Selection — PDF page 183
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F6-07 | NetRef/ComRef Function Selection | 0 or 1 | 0 |
F6-08 / Reset Communication Parameters — PDF page 183
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | F6-08 | Reset Communication Parameters | 0 or 1 | 0 |
Manual — Digital-input assignments and function index — page 184
Source reference: SIEP C71060618F, December 2016, physical PDF page 184. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
5.7 H: Terminal Functions
H parameters are used to assign functions to the external terminals.
u H1: Multi-Function Digital Inputs
n H1-01 to H1-07: Functions for Terminals S1 to S7
These parameters assign functions to the multi-function digital inputs. Settings 0 to 9F determine function for each terminal and are explained below.
Note: 1. Terminals that are not used and terminals using the through-mode should be set to “F”. 2. Drive software versions PRG: 1013 and later require that the Forward run and Reverse Run commands be set simultaneously.
No. | Parameter Name | Setting Range | Default
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Table 5.26 Digital Multi-Function Input Settings
Setting Function Page
H1-01 to H1-07 Digital Input Terminal Assignments — PDF page 184
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H1-01 | Digital Input S1 Function Selection | 1 to 9F | 40: Forward Run Command (2-wire sequence) |
| 2 | H1-02 | Digital Input S2 Function Selection | 1 to 9F | 41: Reverse Run Command (2-wire sequence) |
| 3 | H1-03 | Digital Input S3 Function Selection | 0 to 9F | 24: External Fault (N.O., always detected, coast to stop) |
| 4 | H1-04 | Digital Input S4 Function Selection | 0 to 9F | 14: Fault Reset |
| 5 | H1-05 | Digital Input S5 Function Selection | 0 to 9F | 3 (0) <1> : Multi-Step Speed Reference 1 |
| 6 | H1-06 | Digital Input S6 Function Selection | 0 to 9F | 4 (3) <1> : Multi-Step Speed Reference 2 |
| 7 | H1-07 | Digital Input S7 Function Selection | 0 to 9F | 6 (4) <1> : Jog Reference Selection |
Table5.26 Digital Multi-Function Input Settings left — PDF page 184
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 0 | 3-Wire Sequence | 185 |
| 2 | 1 | LOCAL/REMOTE Selection | 185 |
| 3 | 2 | External Reference 1/2 | 186 |
| 4 | 3 | Multi-Step Speed Reference 1 | 186 |
| 5 | 4 | Multi-Step Speed Reference 2 | 186 |
| 6 | 5 | Multi-Step Speed Reference 3 | 186 |
| 7 | 6 | Jog Reference Selection | 186 |
| 8 | 7 | Accel/Decel Time 1 | 186 |
| 9 | 8 | Baseblock Command (N.O.) | 186 |
| 10 | 9 | Baseblock Command (N.C.) | 186 |
| 11 | A | Accel/Decel Ramp Hold | 186 |
| 12 | B | Drive Overheat Alarm (oH2) | 187 |
| 13 | C | Terminal A1/A2 Enable/Disable | 187 |
| 14 | F | Not used/Through Mode | 187 |
| 15 | 10 | Up Command | 187 |
| 16 | 11 | Down Command | 187 |
| 17 | 12 | Forward Jog | 188 |
| 18 | 13 | Reverse Jog | 188 |
| 19 | 14 | Fault Reset | 188 |
| 20 | 15 | Fast-Stop (N.O.) | 188 |
| 21 | 16 | Motor 2 Selection | 189 |
| 22 | 17 | Fast-stop (N.C.) | 188 |
| 23 | 18 | Timer Function Input | 189 |
| 24 | 19 | PID Disable | 189 |
| 25 | 1A | Accel/Decel Time Selection 2 | 189 |
| 26 | 1B | Program Lockout | 189 |
| 27 | 1E | Reference Sample Hold | 190 |
| 28 | 20 to 2F | External Fault | 190 |
Table5.26 Digital Multi-Function Input Settings right — PDF page 184
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 30 | PID Integral Reset | 191 |
| 2 | 31 | PID Integral Hold | 191 |
| 3 | 32 | Multi-Step Speed Reference 4 | 191 |
| 4 | 34 | PID Soft Starter Cancel | 191 |
| 5 | 35 | PID Input Level Selection | 191 |
| 6 | 40 | Forward Run/Stop (2-wire sequence) | 191 |
| 7 | 41 | Reverse Run/Stop (2-wire sequence) | 191 |
| 8 | 42 | Run/Stop (2-Wire sequence 2) | 191 |
| 9 | 43 | FWD/REV (2-Wire sequence 2) | 191 |
| 10 | 44 | Offset Frequency 1 Addition | 192 |
| 11 | 45 | Offset Frequency 2 Addition | 192 |
| 12 | 46 | Offset Frequency 3 Addition | 192 |
| 13 | 47 <1> | Node Setup | 192 |
| 14 | 60 | DC Injection Braking Command | 192 |
| 15 | 61 | External Speed Search Command 1 | 192 |
| 16 | 62 | External Speed Search Command 2 | 192 |
| 17 | 65 | KEB Ride-Thru 1 (N.C.) | 192 |
| 18 | 66 | KEB Ride-Thru 1 (N.O.) | 192 |
| 19 | 67 | Communications Test Mode | 192 |
| 20 | 68 | High-Slip Braking | 192 |
| 21 | 6A | Drive Enable | 192 |
| 22 | 75 | Up 2 Command | 193 |
| 23 | 76 | Down 2 Command | 193 |
| 24 | 7A | KEB Ride-Thru 2 (N.C.) | 194 |
| 25 | 7B | KEB Ride-Thru 2 (N.O.) | 194 |
| 26 | 7C | Short-Circuit Braking (N.O.) | 194 |
| 27 | 7D | Short-Circuit Braking (N.C.) | 194 |
Manual — Three-wire sequence and LOCAL/REMOTE — page 185
Source reference: SIEP C71060618F, December 2016, physical PDF page 185. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Stop Switch(N.C.); Run Switch(N.O.); DRIVE; S1 Run Command (Runs when Closed); S2 Stop Command (Stops when Open); S5 FWD/REV Multi-Function Input H1-05=0; SC Sequence Input Common. Wiring sketch is illustrative; complete installation and exact connectivity require original. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Run command with2ms min pulse; Can be either ON or OFF; Stop command2ms min; Can be ON or OFF; Forward/reverse command OFF(forward),ON(reverse); Motor speed; Stop,Forward,Reverse,Stop,Forward intervals. Source paragraph saysS1 closed longer than50ms, while this figure prints2ms min; both retained without selecting a preferred value. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Setting Function Page
<1> Available in drive software versions PRG: 1016 and later.
Setting 0: 3-Wire Sequence When one of the digital inputs is programmed for 3-Wire control, that input becomes a forward/reverse directional input, S1 becomes the Run command input, and S2 becomes the Stop command input. The drive will start the motor when the Run input S1 is closed for longer than 50 ms. The drive will stop the operation when the Stop input S2 is released. When the input programmed for 3-Wire sequence is open, the drive will be set for forward direction. If the input is closed, the drive is set for reverse direction.
Note: When 3-Wire sequence is selected the Run and Stop command must be input at S1 and S2.
Note: 1. The Run and Stop command must be open/closed for a short moment only to start and stop the drive. 2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the Run LED will flash to indicate that protective functions are operating. If required by the application, set b1-17 to “1” to have the Run command issued automatically as soon as the drive is powered up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence but set up for 2-Wire sequence (default). When using 3-Wire sequence first set the drive properly (H1-□□ = 0) and then connect the control wires. Make sure b1-17 is set to “0” (drive does not accept Run command active at power up). When initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.
Setting 1: LOCAL/REMOTE Selection This setting allows the input terminal to determine if the drive will run in LOCAL mode or REMOTE mode.
Status Description
Note: 1. If one of the multi-function input terminals is set to for LOCAL/REMOTE, then the LO/RE key on the operator will be disabled. 2. When the drive is set to LOCAL, the LO/RE LED will light. 3. The default setting of the drive is not to allow switching between LOCAL and REMOTE during run. to Refer to b1-07: LOCAL/ REMOTE Run Selection on page 127 if this feature is required by the application.
5.7 H: Terminal Functions
Parameter Details
Table5.26 Digital Input Settings continued left — PDF page 185
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 7E | Forward/Reverse Detection (V/f Control with Simple PG Feedback) | 194 |
| 2 | 90 to 96 | DriveWorksEZ Digital Inputs 1 to 7 | 194 |
Table5.26 Digital Input Settings continued right — PDF page 185
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 9F | DriveWorksEZ Disable | 194 |
Input Setting1 LOCAL/REMOTE Selection — PDF page 185
| Source row | Status | Description |
|---|---|---|
| 1 | Closed | LOCAL: Frequency reference and Run command are input from the digital operator. |
| 2 | Open | REMOTE: Frequency reference and Run command are input from the selected external reference in accordance with the b1-01 and b1-02 or b1-15 and b1-16 settings. |
Manual — Reference switching, Baseblock and Hold — page 186
Source reference: SIEP C71060618F, December 2016, physical PDF page 186. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Run command OFF/ON; Baseblock input ON and Baseblock release; Frequency reference; Output frequency. Begin Speed Search from the previous frequency reference; Output off,motor coasts. Exact waveforms are illustrative; adjacent elevator-brake notice retained. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Setting 2: External Reference 1/2 Selection The external reference 1/external reference 2 selection function allows the user to switch between the frequency reference and Run command source between external reference 1 and 2.
Status Description
Note: The default setting of the drive is not to allow switching between external reference 1 and 2 during run. Refer to b1-07: LOCAL/REMOTE Run Selection on page 127 if this feature is required by the application.
Setting 3 to 5: Multi-Step Speed Reference 1 to 3 Used to switch Multi-Step Speed frequency references d1-01 to d1-08 by digital inputs. Refer to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference on page 160 for details.
Setting 6: Jog Frequency Reference Selection Used to select the Jog frequency set in parameter d1-17 as active frequency reference. Refer to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference on page 160 for details.
Setting 7: Accel/Decel Time Selection 1 Used to switch between accel/decel times 1 and 2. Refer to C1-01 to C1-08: Accel/Decel Times 1 to 4 on page 147 for details.
Setting 8/9: External Baseblock (N.O.) and External Baseblock (N.C.) Setting 8 or 9 assign the Baseblock command to digital input terminals. When the drive receives a Baseblock command, the output transistor stop switching and the motor coasts to stop. During this time, the alarm “bb” will flash on the LED operator to indicate baseblock. For more information on alarms, Refer to Alarm Detection on page 282. When baseblock ends and a Run command is active, the drive performs Speed Search to get the motor running again (Refer to b3: Speed Search on page 130 for details).
Inputs Operation Setting 8 (N.O.) Setting 9 (N.C.)
NOTICE: If using baseblock in elevator applications, make sure the brake closes when the drive output is cut off by a Baseblock input. Failure to do so will result in the motor suddenly coasting when the Baseblock command is entered, causing the load to slip.
Setting A: Accel/Decel Ramp Hold When the digital input programmed for the Accel/Decel Ramp Hold function closes, the drive will lock ("hold") the output frequency. All acceleration or deceleration will cease, and the drive will hold the current speed. Acceleration or deceleration will resume once the input is opened again.
5.7 H: Terminal Functions
Input Setting2 External Reference1/2 Selection — PDF page 186
| Source row | Status | Description |
|---|---|---|
| 1 | Open | External reference 1 is used (defined by parameters b1-01 and b1-02) |
| 2 | Closed | External reference 2 is used (defined by parameters b1-15 and b1-16) |
Input Setting8/9 External Baseblock N.O./N.C. — PDF page 186
| Source row | Operation | Setting 8 (N.O.) | Setting 9 (N.C.) |
|---|---|---|---|
| 1 | Normal operation | Open | Closed |
| 2 | Baseblock (Interrupt output) | Closed | Open |
Manual — Analog enable and Up/Down conditions — page 187
Source reference: SIEP C71060618F, December 2016, physical PDF page 187. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
If the Accel/Decel Ramp Hold function is enabled (d4-01 = 1), the drive will save the output frequency to memory whenever the Ramp Hold input is closed. When the drive is restarted after stop or after power supply interruption, the output frequency that was saved will become the frequency reference (provided that the Accel/Decel Ramp Hold input is still closed). Refer to d4-01: Frequency Reference Hold Function Selection on page 162 for details.
Setting B: Drive Overheat Alarm (oH2) Triggers an oH2 alarm when the contact closes. Because this is an alarm, drive operation is not affected.
Setting C: Analog Inputs A1/A2 Enable If a digital input programmed for this function is open, both analog inputs A1 and A2 are disabled. Close the input to enable the inputs. The drive disregards the input value selected by parameter H3-14 when this terminal closes.
Note: In drive software versions PRG: 1015 and earlier, input values to terminals A1 and A2 are both disregarded when this terminal closes.
Setting F: Not Used/Through Mode Any digital input that is not used should be set to F. When set to “F”, an input does not trigger any function in the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/Modbus communications (through mode). This way external sensors can be connected to unused drive digital inputs, thus reducing the need for separate PLC I/O units.
Setting 10/11: Up/Down Command Using the Up/Down function allows the frequency reference to be set by two push buttons. One digital input must be programmed as the Up input (H1-□□= 10) to increase the frequency reference, the other one must be programmed as the Down input (H1-□□= 11) to decrease the frequency reference. The Up/Down function has priority over the frequency references digital operator, analog inputs, and pulse input (b1-01 = 0, 1, 4). If the Up/Down function is used, then references provided by these sources will be disregarded. The inputs operate as shown in the table below.
Status: Up (10) | Down (11) | Description
Note: 1. An oPE03 alarm will occur when only one of the functions Up/Down is programmed for a digital input. 2. An oPE03 alarm will occur if the Up/Down function is assigned to the terminals while another input is programmed for the Accel/Decel Ramp Hold function. For more information on alarms, Refer to Drive Alarms, Faults, and Errors on page 263. 3. The Up/Down function can only be used for External Reference 1 for parameter b1-01. This should be taken into account when using Up/Down and the external reference parameter b1-15 switching command (H1-□□ = 2). Using the Up/Down Function with Frequency Reference Hold (d4-01) • When the frequency reference hold function is disabled (d4-01 = 0), the Up/Down frequency reference will be reset to 0 when the Run command is cleared or the power is cycled. • When d4-01 = 1, the drive will save the frequency reference set by the Up/Down function. When the Run command or the power is cycled, the drive will restart with the reference value that was saved. The value that was saved can be reset by closing either the Up or Down input without having a Run command active. Refer to d4-01: Frequency Reference Hold Function Selection on page 162. Using the Up/Down Function with Frequency Reference Limits The upper frequency reference limit is determined by parameter d2-01. The value for the lower frequency reference limit depends on the setting of parameter d4-10 and can be set by an analog input or parameter d2-02. Refer to d4-10: Up/Down Frequency Reference Limit Selection on page 167 for details. When a Run command is applied, the lower limits work as follows: • If the lower limit is set by parameter d2-02 only, the drive will accelerate to this limit as soon as a Run command is entered. • If the lower limit is determined by an analog input only, the drive will accelerate to the limit as long as the Run command and an Up or Down command are active. It will not start running if only the Run command is on. • If the lower limit is set by both an analog input and d2-02, and the analog limit is higher than the d2-02 value, the drive will accelerate to the d2-02 value when a Run command is input. Once the d2-02 value is reached, it will continue acceleration to the analog limit only if an Up or Down command is set.
5.7 H: Terminal Functions
Parameter Details
Up10=Open | Down11=Open
Up10=Closed | Down11=Open
Up10=Open | Down11=Closed
Up10=Closed | Down11=Closed
Input Setting10/11 Up/Down Command — PDF page 187
| Source row | Up(10) | Down(11) | Description |
|---|---|---|---|
| 1 | Open | Open | Hold current frequency reference |
| 2 | Closed | Open | Increase frequency reference |
| 3 | Open | Closed | Decrease frequency reference |
| 4 | Closed | Closed | Hold current frequency reference |
Manual — Jog, Fault Reset and Fast Stop — page 188
Source reference: SIEP C71060618F, December 2016, physical PDF page 188. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency upper limit; Lower limit; Accelerates to lower limit; Same frequency; d4-01=1 andd4-01=0 trajectories. FWD run/stop ON; Up command ON; Down command ON; Hold frequency reset; Power supply ON/ON. No unprinted time or frequency inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Output Frequency; positive and negative d1-17 plateaus; FJOG ON then RJOG ON. Adjacent source500ms simultaneous-command fault and b1-04 reverse prohibition apply. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Figure 5.48 shows an Up/Down function example with a lower frequency reference limit set by d2-02 and the frequency reference hold function both enabled (d4-01 = 1) and disabled (d4-01 = 0).
Setting 12/13: FJOG/RJOG Reference Digital inputs programmed as Forward Jog (H1-□□ = 12) and Reverse Jog (H1-□□ = 13) will be Jog inputs that do not require a Run command. Closing the terminal set for Forward Jog input will cause the drive to ramp to the Jog Frequency Reference (d1-17) in the forward direction. The Reverse Jog will cause the same action in the reverse direction. The Forward Jog and Reverse Jog command can be set independently.
Note: The Forward Jog and Reverse Jog commands override all other frequency references. However, if the drive is set to prohibit reverse rotation (b1-04 = 1), then activating Reverse Jog will have no effect. If both the Forward Jog and Reverse Jog are input simultaneously for 500 ms or more, an external fault will occur and the drive will stop using the method set by b1-03.
Setting 14: Fault Reset Whenever the drive detects a fault condition, the fault output contact will close and the drive’s output will shut off. The motor then coasts to stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). Once the Run command is removed, the fault can be cleared by either the RESET key on the digital operator or by closing a digital input configured as a Fault Reset (H1-□□ = 14).
Note: Fault Reset commands are ignored as long as the Run command is present. To reset a fault, first remove the Run command.
Setting 15/17: Fast-stop (N.O./N.C.) The Fast-stop function operates much like an emergency stop input to the drive. If a Fast-stop command is input while the drive is running, the drive will decelerate to a stop by the deceleration time set to C1-09 (Refer to C1-09: Fast-stop Time on page 148). The drive can only be restarted after is has come to a complete stop, the Fast-stop input is off, and the Run command has been switched off. • To trigger the Fast-stop function with a N.O. switch, set H1-□□ = 15 • To trigger the Fast-stop function with a N.C. switch, set H1-□□ = 17 Figure 5.50 shows an operation example of Fast-stop.
5.7 H: Terminal Functions
Manual — Motor selection and related input functions — page 189
Source reference: SIEP C71060618F, December 2016, physical PDF page 189. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Run/Stop ON/ON; Fast-Stop H1-□□=17 ON/ON; Output Frequency; TIME; Decelerates atC1-09. Source shows Run cycling before restart after fast stop; no exact unprinted timing inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Drive; Motor switch input; Motor1 M and Motor2 M; selection contacts and three-phase line markings. Motor selection during run prohibited in adjacent source; wiring topology remains original-only. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast-stop time to C1-09.
Setting 16: Motor 2 Selection The drive has the capability to control two motors independently. A second motor may be selected using a multi-function digital input (H1-□□ = 16) as shown in Figure 5.51.
Motor 2 is selected when the input set for Motor 2 Selection closes. When operating motor 2, • E3-□□ and E4-□□ become valid for motor control. Refer to E3: V/f Characteristics for Motor 2 on page 175 and Refer to E4: Motor 2 Parameters on page 176 for details. • Accel/decel times set in parameters C1-05/06/07/08 are activated ( Refer to C1-01 to C1-08: Accel/Decel Times 1 to 4 on page 147 for details). • E4-14 is used as gain for slip compensation instead of C3-01. • E4-15 is used as gain for torque compensation instead of C4-01. • A digital output programmed for “Motor 2 Selection” (H2-01/02/03 = 1C) will be switched on. Note: 1. When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2. 2. It is not possible to switch between motor 1 and motor 2 during run. Doing so will trigger a "rUn" alarm.
Setting 18: Timer Function Input This setting configures a digital input terminal as the input for the timer function. Refer to b4: Delay Timers on page 135 for details.
Setting 19: PID Control Cancel When the PID Function has been enabled by b5-01 (PID Mode Selection), it can be indefinitely disabled by closing a digital input configured as a PID Disable (H1-□□ = 19). When the input is released, the drive resumes PID operation. Refer to PID Block Diagram on page 138 for more information on this function.
Setting 1A: Accel/Decel Time Selection 2 Used to select accel/decel times 3 and 4 in combination with the Accel/Decel Time Selection 1 command. Refer to C1-01 to C1-08: Accel/Decel Times 1 to 4 on page 147 for details.
Setting 1B: Program Lockout When an input is programmed for Program Lockout, parameters values can be monitored but not changed as long as this input is open.
5.7 H: Terminal Functions
Parameter Details
Manual — Sample/Hold and external fault matrix — page 190
Source reference: SIEP C71060618F, December 2016, physical PDF page 190. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Analog signal ramp; Frequency reference stair steps; Reference Sample Hold Input; ON(closed),OFF(open);100ms minimum sample intervals shown twice;Time. Power-off clears saved reference to0 per adjacent prose; no inferred sampled values. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Setting 1E: Analog Frequency Reference Sample/Hold This function allows the user to sample an analog frequency reference signal being input to terminal A1 or A2 and hold the frequency reference at the sampled level. Once the Analog Frequency Reference Sample/Hold function is held for at least 100 ms, the drive reads the analog input and changes the frequency reference to the newly sampled speed as illustrated in Figure 5.52. When the power is shut off and the sampled analog frequency reference is cleared, the frequency reference is reset to 0.
An oPE03 error will occur when one of the following functions is used simultaneously with the Analog Frequency Reference Sample/Hold function. • Hold Accel/Decel Stop (setting: A) • Up command, Down command (setting: 10, 11) • Offset Frequency (setting: 44 to 46) • Up or Down functions (setting: 75, 76)
Setting 20 to 2F: External Fault By using the External Fault function, the drive can be stopped when problems occur with external devices. To use the external fault function, set one of the multi-function digital inputs to any value between 20 to 2F. The operator will display EF□ where □ is the number of the terminal (terminal S□) to which the external fault signal is assigned. For example, if an external fault signal is input to terminal S3, “EF3” will be displayed. Select the value to be set in H1-□□ from a combination of any of the following three conditions: • Signal input level from peripheral devices (N.O./N.C.) • External fault detection method • Operation after external fault detection The following table shows the relationship between the conditions and the value set to H1-□□:
Setting
Terminal Status <1> Detection Method <2> Stopping Method
N.O. | N.C. | Always Detected
Detected during Run only
Ramp to Stop (fault)
Coast to Stop (fault)
Fast-stop (fault)
Setting | Terminal Status: N.O., N.C. | Detection Method: Always Detected, Detected during Run only | Stopping Method: Ramp to Stop (fault), Coast to Stop (fault), Fast-stop (fault), Alarm Only (continue running)
5.7 H: Terminal Functions
Input Setting20–2F External Fault matrix first — PDF page 190
| Source row | Setting | Terminal N.O. <1> | Terminal N.C. <1> | Always Detected <2> | Detected during Run only <2> | Ramp to Stop (fault) | Coast to Stop (fault) | Fast-stop (fault) | Alarm Only (continue running) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 20 | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 21 | ⟦blank source cell⟧ | O | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | 22 | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 4 | 23 | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | O | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 5 | 24 | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 6 | 25 | ⟦blank source cell⟧ | O | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 7 | 26 | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 8 | 27 | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 9 | 28 | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ |
| 10 | 29 | ⟦blank source cell⟧ | O | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ |
| 11 | 2A | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ |
| 12 | 2B | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ |
Manual — External fault matrix and two-wire sequences — page 191
Source reference: SIEP C71060618F, December 2016, physical PDF page 191. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive; Forward Run atS1; Reverse Run atS2; SC Digital Input Common. Both inputs closed causes external fault per adjacent prose. No wiring installation inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Setting
Terminal Status <1> Detection Method <2> Stopping Method
N.O. | N.C. | Always Detected
Detected during Run only
Ramp to Stop (fault)
Coast to Stop (fault)
Fast-stop (fault)
Setting | Terminal Status: N.O., N.C. | Detection Method: Always Detected, Detected during Run only | Stopping Method: Ramp to Stop (fault), Coast to Stop (fault), Fast-stop (fault), Alarm Only (continue running)
<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed. <2> Determine whether detection for each fault should be enabled only during run or always detected.
Setting 30: PID Integral Reset By configuring one of the digital inputs as an Integral Reset Input, (H1-□□ = 30), the value of the integral component of PID control can be reset to 0 whenever the configured input is closed. The integral component of PID control will be held at 0 as long as the configured digital input is held closed. Refer to PID Block Diagram on page 138 for details.
Setting 31: PID Integral Hold By configuring a digital input for Integral Hold (H1-0□ = 31), the value of the integral component of the PID control is locked as long as the input is active. The PID controller resumes integral operation from the hold value as soon as the integral hold input is released. Refer to PID Block Diagram on page 138 for details.
Setting 32: Multi-Step Speed 4 Used to select the Multi-Step Speeds d1-09 to d1-16 in combination with the Multi-Step Speed inputs 1, 2 and 3. Refer to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Reference on page 160 for details.
Setting 34: PID SFS Cancel A digital input configured as a PID SFS Cancel input (H1-0□ = 34) can be used to enable or disable the PID soft starter and thereby canceling the Accel/Decel time b5-17. Refer to PID Block Diagram on page 138 for details.
Function 35: PID Input Level Selection An input programmed for this function can be used to switch the sign of the PID input. Refer to PID Block Diagram on page 138 for more information on this function.
Setting 40/41: Forward Run/Reverse Run Command for 2-Wire Sequence Sets the drive for 2-Wire sequence. When the input set to 40 is closed, the drive operates in the forward direction. When the input set for 41 is closed, the drive will operate in reverse. Closing both inputs at the same time will result in an external fault.
Note: 1. This function cannot be used simultaneously with settings 42 and 43. 2. These functions are assigned to the terminals S1 and S2 when the drive is initialized for 2-Wire sequence. 3. Software versions PRG: 1013 and later require that both Forward run and Reverse Run commands be set at the same time.
Figure
Setting 42/43: Run and Direction Command for 2-Wire Sequence 2 Sets the drive for 2-Wire sequence 2. When the input programmed for 42 is closed, the drive will operate in the selected direction. When the input opens, the drive will stop. The input programmed for 43 selects the direction. If it is open, forward direction is selected; if it is closed, reverse direction is selected.
Note: This function cannot be used simultaneously with settings 40 and 41.
5.7 H: Terminal Functions
Parameter Details
Input Setting20–2F External Fault matrix continued — PDF page 191
| Source row | Setting | Terminal N.O. <1> | Terminal N.C. <1> | Always Detected <2> | Detected during Run only <2> | Ramp to Stop (fault) | Coast to Stop (fault) | Fast-stop (fault) | Alarm Only (continue running) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 2C | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O |
| 2 | 2D | ⟦blank source cell⟧ | O | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O |
| 3 | 2E | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O |
| 4 | 2F | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | O | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O |
Manual — Braking, Speed Search, KEB and Drive Enable — page 192
Source reference: SIEP C71060618F, December 2016, physical PDF page 192. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
DC Injection braking command OFF/ON/OFF; FWD Run command OFF/ON/OFF; Output frequency; DC Injection braking before and after run; DC Injection Braking Start Frequency b2-01. Run/Jog releases braking per adjacent prose; no unprinted duration inferred. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Setting 44/45/46: Offset Frequency 1/2/3 Addition These inputs can be used to add offset frequencies d7-01, d7-02, and d7-03 to the frequency reference. Refer to d7-01 to d7-03: Offset Frequency 1 to 3 on page 167 for details.
Setting 47: Node Setup If the SI-S3/V option unit is connected, closing this terminal sets a node address for operation on a CANopen network.
Setting 60: DC Injection Braking When a DC Injection Braking command is input while the drive is stopped, DC Injection Braking operation is activated. When a Run command or a Jog command is input, DC Injection Braking is released. Refer to b2: DC Injection Braking on page 128 for details on setting up the DC braking function. The diagram below illustrates the DC Injection Braking function.
Setting 61/62: Speed Search 1/2 These input functions can be used to enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start. Refer to Activation of Speed Search on page 132 for details on how to use the input signals. If b3-24 is set to 0 and b3-01 is set to 0, when the input terminal set for Speed Search 1 (H1-□□ = 61) is enabled, Speed Search will begin looking for the motor speed from the maximum output frequency. If the Speed Search 2 input (H1-□□ = 62) is enabled, Speed Search starts looking for the motor speed starting at the frequency reference. Refer to b3: Speed Search on page 130 for more information about Speed Search.
Note: Operator error oPE03 will result if both Speed Search 1 and Speed Search 2 are set to the input terminals at the same time.
Setting 65/66: KEB Ride-Thru 1 (N.C.)/2 (N.O.) A digital input programmed for this function can be used to activate the KEB 1 function and detect power supply return.
Description | Digital Inputs: Setting 65 (N.C.), Setting 66 (N.O.)
Refer to Kinetic Energy Backup (KEB) Function on page 219 for details on how to use these input settings.
Setting 67: Communication Test Mode The drive has a built-in function for self-diagnosing the serial communications operation. The test involves wiring the send and receive terminals of the RS-485/RS-422 port together. The drive transmits data and then confirms the communications are received normally. Refer to Self-Diagnostics on page 461 for details on how to use this function.
Setting 68: High Slip Braking Closing an input programmed for this function triggers High Slip Braking. Once HSB is started, the drive has to completely stop and the HSB input has to be removed before a restart can be performed. Refer to n3: High Slip Braking (HSB)/ Overexcitation Deceleration on page 241 for details on High Slip Braking.
Setting 6A: Drive Enable A digital input configured as a Drive Enable input (H1-□□ = 6A) will prevent the drive from executing a Run command until the input is closed. When the Drive Enable input is open, the digital operator will display “dnE” to indicate that the drive is disabled.
5.7 H: Terminal Functions
Input Setting65/66 KEB Ride-Thru1 N.C./N.O. — PDF page 192
| Source row | Description | Setting 65 (N.C.) | Setting 66 (N.O.) |
|---|---|---|---|
| 1 | KEB 1 deceleration | Open | Closed |
| 2 | Normal operation | Closed | Open |
Manual — Up/Down2 conditional operation matrix — page 193
Source reference: SIEP C71060618F, December 2016, physical PDF page 193. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
If a Run command is closed prior to the Drive Enable input being closed, then the drive will not run until the Run command is cycled. If the Drive Enable input is opened while the drive is running, the drive will stop using the method set by parameter b1-03 (Refer to b1-03: Stopping Method Selection on page 124 for details).
Setting 75/76: Up/Down 2 The Up/Down 2 function can be used to add a bias to the frequency reference. The input programmed for 75 will increase the bias and the input programmed for 76 will decrease it. Table 5.27 explains how the Up/Down 2 function works depending on the frequency reference source and parameters d4-01, d5-03 and d4-05. Refer to d4: Frequency Hold and Up/Down 2 Function on page 162 for detailed explanations of these and other Up/Down 2 related parameters.
Note: 1. The Up 2 and Down 2 functions must be set as a pair. 2. When using the Up/Down 2 function, set appropriate bias limit values in parameters d4-08 and d4-09.
Table 5.27 Up/Down 2 Operations
Condition | Freq. Ref. Source | d4-03 | d4-05 | d4-01 | Operation | Frequency Saved
5.7 H: Terminal Functions
Parameter Details
Condition 1 | source Multi-Step Speed Reference | d4-03=0 | d4-05=0 | d4-01=0
Condition 2 | source Multi-Step Speed Reference | d4-03=0 | d4-05=0 | d4-01=1
Condition 3 | source Multi-Step Speed Reference | d4-03=0 | d4-05=1 | d4-01=--
Condition 4 | source Multi-Step Speed Reference | d4-03=Value other than 0 | d4-05=-- | d4-01=0
Condition 5 | source Multi-Step Speed Reference | d4-03=Value other than 0 | d4-05=-- | d4-01=1
Condition 6 | source Other (analog communicati ons, etc.) | d4-03=0 | d4-05=0 | d4-01=0
Condition 7 | source Other (analog communicati ons, etc.) | d4-03=0 | d4-05=0 | d4-01=1
Table5.27 Up/Down2 Operations conditions1–7 — PDF page 193
| Source row | Condition | Freq. Ref. Source | d4-03 | d4-05 | d4-01 | Operation | Frequency Saved |
|---|---|---|---|---|---|---|---|
| 1 | 1 | Multi-Step Speed Reference | 0 | 0 | 0 | • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. | Not saved |
| 2 | 2 | Multi-Step Speed Reference | 0 | 0 | 1 | • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. | If the bias and frequency reference are constant for 5 s, the bias is added to the active frequency reference and reset afterwards. |
| 3 | 3 | Multi-Step Speed Reference | 0 | 1 | -- | • Accelerates (increases the bias) while the Up 2 function is closed, • Decelerates (decreases the bias) while Down 2 is closed. • Otherwise operates at the frequency reference | Not saved |
| 4 | 4 | Multi-Step Speed Reference | Value other than 0 | -- | 0 | • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (bias is increased for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (bias is decreased for d4-03). • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. | Not saved |
| 5 | 5 | Multi-Step Speed Reference | Value other than 0 | -- | 1 | • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (bias is increased for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (bias is decreased for d4-03). • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • Resets the bias when the reference changes • Operates with the frequency reference in all other situations. | If the bias and frequency reference are constant for 5 s, the bias is added to the active frequency reference and reset afterwards. |
| 6 | 6 | Other (analog communicati ons, etc.) | 0 | 0 | 0 | • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • When during accel/decel. the frequency reference changes for more than d4-07, bias value is held until the output frequency meets the reference (speed agree). | Not saved |
| 7 | 7 | Other (analog communicati ons, etc.) | 0 | 0 | 1 | • Accelerates (increases the bias) while the Up 2 function is closed • Decelerates (decreases the bias) while Down 2 is closed • Holds output frequency (holds the bias) when no Up 2 or Down 2 input or both active. • When during accel/decel. the frequency reference changes for more than d4-07, bias value is held until the output frequency meets the reference (speed agree). | If the bias is constant for 5 s, it is saved to parameter d4-06. The frequency reference cannot be overwritten, so only the bias is saved. |
Manual — Up/Down2 continuation and PM/DriveWorksEZ inputs — page 194
Source reference: SIEP C71060618F, December 2016, physical PDF page 194. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Condition | Freq. Ref. Source | d4-03 | d4-05 | d4-01 | Operation | Frequency Saved
Setting 7A/7B: KEB Ride-Thru 2 (N.C./N.O.) A digital input programmed for this function can be used to activate the KEB 2 function and detect power supply return.
Description | Digital Inputs: Setting 7A (N.C.), Setting 7B (N.O.)
Refer to Kinetic Energy Backup (KEB) Function on page 219 for details on how to use these input settings.
Setting 7C/7D: Short Circuit Braking (N.O./N.C.) (OLV/PM only) An input programmed for this function can be used to activate Short Circuit Braking in Open Loop Vector Control for PM motors. By linking all three phases of a PM motor it creates a braking torque in a rotating motor and can be used to stop a rotating motor or prevent a motor from coasting by external forces (like windmill effect in fan applications etc.).
Description | Digital Inputs: Setting 7C (N.O.), Setting 7D (N.C.)
Setting 7E: Forward Reverse Detection (V/f Control with Simple PG Feedback) When a digital input is programmed for this function, the input determines the direction of the speed feedback signal for V/f Control with PG feedback. If the input is open, the speed feedback signal is considered to be forward, if the input is closed, it is considered to be in reverse. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details.
Setting 90 to 96: DriveWorksEZ Digital Inputs 1 to 7 These settings are for digital inputs functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.
Setting 9F: DriveWorksEZ Function Disable This function is used to enable or disable a DriveWorksEZ program in the drive. An input programmed for this function is effective only if A1-07 = 2.
Status Description
5.7 H: Terminal Functions
Condition 8 | source Other (analog comms, etc.) | d4-03=0 | d4-05=1 | d4-01=--
Condition 9 | source Other (analog comms, etc.) | d4-03=Value than other 0 | d4-05=-- | d4-01=0
Condition 9 | source Other (analog comms, etc.) | d4-03=Value other than 0 | d4-05=-- | d4-01=0
Condition 10 | source Other (analog comms, etc.) | d4-03=Value than other 0 | d4-05=-- | d4-01=1
Condition 10 | source Other (analog comms, etc.) | d4-03=Value other than 0 | d4-05=-- | d4-01=1
Table5.27 Up/Down2 Operations conditions8–10 — PDF page 194
| Source row | Condition | Freq. Ref. Source | d4-03 | d4-05 | d4-01 | Operation | Frequency Saved |
|---|---|---|---|---|---|---|---|
| 1 | 8 | Other (analog comms, etc.) | 0 | 1 | -- | • Accelerates (increases the bias) while the Up 2 function is closed, • Decelerates (decreases the bias) while Down 2 is closed. • Otherwise operates at the frequency reference | Not saved |
| 2 | 9 | Other (analog comms, etc.) | Value other than 0 | -- | 0 | • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (increases the bias for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (decreases the bias for d4-03). • When during accel/decel the frequency reference changes for more then d4-07, bias value is held until the output frequency meets the reference (speed agree). | Not saved |
| 3 | 10 | Other (analog comms, etc.) | Value other than 0 | -- | 1 | • When the Up 2 is enabled, drive accelerates up to the frequency reference plus d4-03 (increases the bias for d4-03). • When Down 2 is enabled, drive decelerates down to the frequency reference minus d4-03 (decreases the bias for d4-03). • When during accel/decel the frequency reference changes for more then d4-07, bias value is held until the output frequency meets the reference (speed agree). | If the bias is constant for 5 s, it is saved to parameter d4-06. The frequency reference cannot be overwritten, so only the bias is saved. |
Input Setting7A/7B KEB Ride-Thru2 N.C./N.O. — PDF page 194
| Source row | Description | Setting 7A (N.C.) | Setting 7B (N.O.) |
|---|---|---|---|
| 1 | KEB 2 deceleration | Open | Closed |
| 2 | Normal operation | Closed | Open |
Input Setting7C/7D Short-Circuit Braking N.O./N.C. OLV/PM only — PDF page 194
| Source row | Description | Setting 7C (N.O.) | Setting 7D (N.C.) |
|---|---|---|---|
| 1 | Normal operation | Open | Closed |
| 2 | Short-Circuit Braking | Closed | Open |
Input Setting9F DriveWorksEZ Disable — PDF page 194
| Source row | Status | Description |
|---|---|---|
| 1 | Open | DriveWorksEZ enabled |
| 2 | Closed | DriveWorksEZ disabled |
Manual — Output assignments and function index — page 195
Source reference: SIEP C71060618F, December 2016, physical PDF page 195. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u H2: Multi-Function Output
n H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection
The drive has three multi-function output terminals. Set parameters H2-01 to H2-03 to values between 0 and 192 to assign functions to these terminals. Default values are listed in the following table.
No. Parameter Name Setting Range Default
Note: Terminals that are not used and terminals using the through-mode should be set to “F”.
Table 5.28 Multi-Function Output Terminal Settings
Setting Function Page
<1> Available in drive software versions PRG: 1016 and later.
Setting 0: During Run Output closes when the drive is outputting a voltage.
Status Description
5.7 H: Terminal Functions
Parameter Details
H2-01 to H2-03 Output Function Selection — PDF page 195
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H2-01 | Terminal MA, MB and MC Function Selection (relay) | 0 to 192 | E: Fault |
| 2 | H2-02 | Terminal P1 Function Selection (open-collector) | 0 to 192 | 0: During Run |
| 3 | H2-03 | Terminal P2 Function Selection (open-collector) | 0 to 192 | 2: Speed Agree 1 |
Table5.28 Multi-Function Output Terminal Settings left — PDF page 195
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 0 | During Run | 195 |
| 2 | 1 | Zero Speed | 196 |
| 3 | 2 | Speed Agree 1 | 196 |
| 4 | 3 | User Set Speed Agree 1 | 196 |
| 5 | 4 | Frequency Detection 1 | 197 |
| 6 | 5 | Frequency Detection 2 | 197 |
| 7 | 6 | Drive Ready | 198 |
| 8 | 7 | DC Bus Undervoltage | 198 |
| 9 | 8 | During Baseblock (N.O.) | 198 |
| 10 | 9 | Frequency Reference Source | 198 |
| 11 | A | Run Command Source | 198 |
| 12 | B | Torque Detection 1 (N.O.) | 198 |
| 13 | C | Frequency Reference Loss | 199 |
| 14 | D | Braking Resistor Fault | 199 |
| 15 | E | Fault | 199 |
| 16 | F | Not used/Through Mode | 199 |
| 17 | 10 | Alarm | 199 |
| 18 | 11 | Reset Command Active | 199 |
| 19 | 12 | Timer Output | 199 |
| 20 | 13 | Speed Agree 2 | 199 |
| 21 | 14 | User Set Speed Agree 2 | 200 |
| 22 | 15 | Frequency Detection 3 | 200 |
| 23 | 16 | Frequency Detection 4 | 201 |
| 24 | 17 | Torque Detection 1 (N.C.) | 198 |
| 25 | 18 | Torque Detection 2 (N.O.) | 198 |
| 26 | 19 | Torque Detection 2 (N.C.) | 198 |
| 27 | 1A | During Reverse Operation | 201 |
Table5.28 Multi-Function Output Terminal Settings right — PDF page 195
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 1B | During Baseblock (N.C.) | 202 |
| 2 | 1C | Motor 2 Selection | 202 |
| 3 | 1E | Restart Enabled | 202 |
| 4 | 1F | Motor Overload Alarm (oL1) | 202 |
| 5 | 20 | Drive Overheat Pre alarm (oH) | 202 |
| 6 | 22 | Mechanical Weakening | 202 |
| 7 | 2F <1> | Maintenance Period | 202 |
| 8 | 30 | During Torque Limit | 202 |
| 9 | 37 | During Frequency Output | 202 |
| 10 | 38 | Drive Enable | 203 |
| 11 | 39 | Watt Hour Pulse Output | 203 |
| 12 | 3C | LOCAL/REMOTE Status | 203 |
| 13 | 3D | During Speed Search | 203 |
| 14 | 3E | PID Feedback Low | 203 |
| 15 | 3F | PID Feedback High | 203 |
| 16 | 4A | During KEB Operation | 203 |
| 17 | 4B | During Short-Circuit Braking | 203 |
| 18 | 4C | During Fast-stop | 203 |
| 19 | 4D | oH Pre-Alarm Time Limit | 203 |
| 20 | 4E <1> | Braking Transistor Fault (rr) | 203 |
| 21 | 4F <1> | Braking Resistor Overheat (rH) | 204 |
| 22 | 90 | DriveWorksEZ Digital Output 1 | 204 |
| 23 | 91 | DriveWorksEZ Digital Output 2 | 204 |
| 24 | 92 | DriveWorksEZ Digital Output 3 | 204 |
| 25 | 100 to 192 | H2 Parameter Functions Reversed Output Switching of 0 to 92 | 204 |
Output Setting0 During Run — PDF page 195
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Drive is stopped. |
| 2 | Closed | A Run command is input or the drive is during deceleration or during DC injection. |
Manual — During Run, Zero Speed and Speed Agree1 — page 196
Source reference: SIEP C71060618F, December 2016, physical PDF page 196. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Run command OFF/ON; Baseblock command OFF/ON; Output frequency including interruption; During Run OFF/ON remains asserted through depicted baseblock interval, ramp stop and ending DC injection. Conceptual timing only. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Output frequency or motor speed; E1-09 (Max. Output Frequency) [literal source label]; Zero Speed OFF/ON as waveform falls below threshold. Adjacent text/table callE1-09 minimum output frequency; conflict retained. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Frequency reference; Output frequency positive/negative; L4-02 widths in both directions; Speed agree1 OFF/ON. Source detects reference±L4-02 independent of direction; no thresholds calculated. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Setting 1: Zero Speed Terminal closes whenever the output frequency falls below the minimum output frequency set to E1-09.
Status Description
Setting 2: Speed Agree 1 (fref/fout Agree 1) Closes whenever the actual output frequency is within the Speed Agree Width (L4-02) of the current frequency reference regardless of the direction.
Note: Detection works in both directions, forward and reverse.
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.
Setting 3: User Set Speed Agree 1 (fref/fset Agree 1) Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-02) of the programmed Speed Agree Level (L4-01).
5.7 H: Terminal Functions
Output Setting1 Zero Speed — PDF page 196
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency is above the minimum output frequency set to E1-09 |
| 2 | Closed | Output frequency is less than or equal to the minimum output frequency set to E1-09 |
Output Setting2 Speed Agree1 — PDF page 196
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency does not match the frequency reference while the drive is running. |
| 2 | Closed | Output frequency is within the range of frequency reference ± L4-02. |
Manual — User speed and frequency detection — page 197
Source reference: SIEP C71060618F, December 2016, physical PDF page 197. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency; Frequency reference; L4-01 threshold with±L4-02 bands in both directions; User Set Speed Agree1 OFF/ON/OFF/ON. Both reference and output within band condition retained in table. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Output frequency positive/negative; L4-01 levels; L4-02 hysteresis; Frequency Detection1 <1> ON/OFF intervals. Footnote appliesL4-07=1 detection always enabled; default0 excludes baseblock. No invented edge timing. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Status Description
Note: The detection works in both forward and reverse. The value of L4-01 will be used as the detection level for both directions.
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.
Setting 4: Frequency Detection 1 Output is closed as long as the output frequency is below the detection level set in L4-01 plus the hysteresis set in L4-02. It closes when the output frequency falls below L4-01.
<1> This is the time chart when L4-07, Speed Agree Detection Selection, is set to 1 (Detection always enabled). The default setting for L4-07 is 0 (No detection during baseblock). When L4-07 is set to 0, the terminal opens during baseblock. Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.
Setting 5: Frequency Detection 2 Output closes whenever the output frequency is equal to or above the detection level set in L4-01. The output opens when the output frequency falls below L4-01 minus the hysteresis set in L4-02.
5.7 H: Terminal Functions
Parameter Details
Output Setting3 User Set Speed Agree1 — PDF page 197
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency or frequency reference are outside the range of L4-01 ± L4-02. |
| 2 | Closed | Output frequency and the frequency reference are both within the range of L4-01 ± L4-02. |
Output Setting4 Frequency Detection1 — PDF page 197
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency exceeded L4-01 + L4-02. |
| 2 | Closed | Output frequency is below L4-01 or has not exceeded L4-01 + L4-02. |
Output Setting5 Frequency Detection2 — PDF page 197
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency is below L4-01 minus L4-02 or has not exceeded L4-01. |
| 2 | Closed | Output frequency exceeded L4-01. |
Manual — Drive Ready, voltage and source outputs — page 198
Source reference: SIEP C71060618F, December 2016, physical PDF page 198. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency positive/negative; L4-01 levels; L4-02 hysteresis; Frequency Detection2 OFF/ON intervals in both directions. Read withPDF197 source table and exact threshold wording. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Refer to L4-01/02: Speed Agreement Detection Level and Detection Width on page 227 for details on setting the detection width.
Setting 6: Drive Ready Output closes whenever the drive is ready to operate the motor.
Status Description
Refer to b1-08: Run Command Selection while in Programming Mode on page 127 for details on the setting of b1-08.
Setting 7: DC Bus Undervoltage Output closes whenever the DC bus voltage or control circuit power supply drops below the trip level. The undervoltage trip level is determined by L2-05. A fault in the DC bus charge circuit will also cause the DC Bus Undervoltage output to close.
Setting 8: During Baseblock (N.O.) Output closes to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors are not switched and no voltage will be output.
Setting 9: Frequency Reference Source A digital output programmed for this function shows the frequency reference source that is currently selected.
Setting A: Run Command Source A digital output programmed for this function shows the Run command source that is currently selected.
Setting B/17/18/19: Torque Detection 1 (N.O./N.C.) and Torque Detection 2 (N.O./N.C.) These digital output functions can be used to signal an overtorque or undertorque situation to an external device. Set up the torque detection and select the output function from the table below. Refer to L6: Torque Detection on page 231 for details.
5.7 H: Terminal Functions
Output Setting6 Drive Ready — PDF page 198
| Source row | Status | Description |
|---|---|---|
| 1 | Open | During power up, initialization, fault or in Programming Mode (while b1-08 = 0 or 2). |
| 2 | Closed | Drive is ready for operation. |
Output Setting7 DC Bus Undervoltage — PDF page 198
| Source row | Status | Description |
|---|---|---|
| 1 | Open | DC bus voltage is above the level set to L2-05 |
| 2 | Closed | DC bus voltage has fallen below the trip level set to L2-05. |
Output Setting8 During Baseblock N.O. — PDF page 198
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Drive is not in a baseblock state. |
| 2 | Closed | Baseblock is being executed. |
Output Setting9 Frequency Reference Source — PDF page 198
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Frequency reference is provided from External Reference 1 (b1-01) or 2 (b1-15) |
| 2 | Closed | Frequency reference is being sourced from the digital operator. |
Output SettingA Run Command Source — PDF page 198
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Run command is provided from External Reference 1 (b1-02) or 2 (b1-16) |
| 2 | Closed | Run command is being sourced from the digital operator. |
Manual — Torque detection and fault/status outputs — page 199
Source reference: SIEP C71060618F, December 2016, physical PDF page 199. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting Status Description
Setting C: Frequency Reference Loss An output set for this function will be closed if frequency reference loss is detected. Refer to L4-05: Frequency Reference Loss Detection Selection on page 227 for details.
Setting D: Dynamic Braking Resistor Overheat An output programmed for this function will close when the dynamic braking resistor (DB) overheats or the braking transistor is in a fault condition.
Setting E: Fault The Fault configured digital output will close whenever the drive experiences a fault (this excludes faults CPF00 and CPF01).
Setting F: Not Used Use this setting when the terminal is not used or when using the terminal as a throughput. When set to “F”, the output is not set by any drive function but it can be switched by a PLC via a communication option or MEMOBUS/Modbus communications (through mode).
Setting 10: Minor Fault Output closes when a minor fault condition is present.
Setting 11: Reset Command Active Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial communications, or using a communications option card.
Setting 12: Timer Output This setting configures a digital output terminal as output for the timer function. Refer to b4: Delay Timers on page 135 for details.
Setting 13: Speed Agree 2 (fref /fout Agree 2) Closes whenever the actual output frequency is within the Speed Agree Width (L4-04) of the current frequency reference regardless of the direction.
Status Description
Note: The detection works in both forward and reverse.
5.7 H: Terminal Functions
Parameter Details
Output SettingB/17/18/19 Torque Detection1/2 N.O./N.C. — PDF page 199
| Source row | Setting | Status | Description |
|---|---|---|---|
| 1 | B | Closed | Torque Detection 1 (N.O.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-02 for longer than the time specified in parameter L6-03. |
| 2 | 17 | Open | Torque Detection 1 (N.C.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-02 for longer than the time specified in parameter L6-03. |
| 3 | 18 | Closed | Torque Detection 2 (N.O.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-05 for longer than the time specified in parameter L6-06. |
| 4 | 19 | Open | Torque Detection 2 (N.C.): Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-05 for longer than the time specified in parameter L6-06. |
Output Setting13 Speed Agree2 — PDF page 199
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency does not match the frequency reference while the drive is running |
| 2 | Closed | Output frequency is within the range of frequency reference ± L4-04 |
Manual — Speed Agree2 and Frequency Detection3 — page 200
Source reference: SIEP C71060618F, December 2016, physical PDF page 200. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Frequency reference; Output frequency positive/negative; L4-04 widths; Speed Agree2 OFF/ON. Detects both directions; no unprinted numerical value. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Caption literally saysPositive L3-04 Value. Graph threshold labelL4-03 with±L4-04, Output frequency,Frequency reference, User Set Speed Agree2 OFF/ON; no output assertion in reverse example. Adjacent prose describes signedL4-03 and specified-direction-only detection; caption conflict retained. Source diagram/wiring geometry, exact routing and unprinted numerical values remain original-only.
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227 for details on setting the detection width.
Setting 14: User Set Speed Agree 2 (fref /fset Agree 2) Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-04) of the programmed Speed Agree Level (L4-03). As the detection level L4-03 is a signed value, detection works in the specified direction only.
Status Description
Setting 15: Frequency Detection 3 Output is closed as long as the output frequency is below the detection level set in L4-03 plus the hysteresis set in L4-04. It closes when the output frequency falls below L4-03. As the detection level L4-03 is a signed value, the detection works in the specified direction only.
5.7 H: Terminal Functions
Output Setting14 User Set Speed Agree2 — PDF page 200
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency or frequency reference are outside the range of L4-03 ± L4-04 |
| 2 | Closed | Output frequency and the frequency reference are both within the range of L4-03 ± L4-04 |
Output Setting15 Frequency Detection3 — PDF page 200
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency exceeded L4-03 plus L4-04. |
| 2 | Closed | Output frequency is below L4-03 or has not exceeded L4-03 plus L4-04 yet. |
Manual — Frequency detection and reverse output — page 201
Source reference: SIEP C71060618F, December 2016, physical PDF page 201. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency, positive and negative; L4-03 threshold and L4-04 hysteresis; Frequency detection 3 <1> ON/OFF. Caption says Positive L3-04 Value, unlike L4-03 graph. Figure closes PDF200 continuation. Exact source geometry, routing and unprinted numerical values remain original-only.
Output frequency, positive and negative; L4-03 threshold, L4-04 hysteresis; Frequency Detection 4 OFF/ON in positive portion. Caption says Positive L3-04 Value, unlike L4-03 graph. Signed-direction detection per adjacent prose. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.63 Frequency Detection 3 Example with Positive L3-04 Value
<1> This is the time chart when L4-07, Speed Agree Detection Selection, is set to 1 (Detection always enabled). The default setting for L4-07 is 0 (No detection during baseblock). When L4-07 is set to 0, the terminal opens during baseblock. Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227 for details on setting the detection width.
Setting 16: Frequency Detection 4 Output closes whenever the output frequency is equal to or above the detection level set in L4-03. The output opens when the output frequency falls below L4-03 minus the hysteresis set in L4-04. As the detection level L4-03 is a signed value, the detection works in the specified direction only.
Status Description
Figure 5.64 Frequency Detection 4 Example with Positive L3-04 Value
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 227 for details on setting the detection width.
Setting 1A: During Reverse The During Reverse digital output will close whenever the drive is turning the motor in the reverse direction.
5.7 H: Terminal Functions
Parameter Details
Frequency Detection4 — PDF page 201
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Output frequency is below L4-03 minus L4-04 or has not exceeded L4-03 yet. |
| 2 | Closed | Output frequency exceeded L4-03. |
During Reverse — PDF page 201
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Motor is driven in the forward direction or stopped. |
| 2 | Closed | Motor is driven in reverse. |
Manual — Output status and motor selection — page 202
Source reference: SIEP C71060618F, December 2016, physical PDF page 202. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency positive then negative; FWD Run command, REV Run command; During Reverse OFF/ON; time. Output remains ON through reverse deceleration until zero-frequency crossing; no unprinted time inferred. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.65 Reverse Direction Output Example Time Chart
Setting 1B: During Baseblock (N.C.) Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors are not switched and no voltage is output.
Status Description
Setting 1C: Motor 2 Selected This output function shows the motor 1/2 selection status. Refer to Setting 16: Motor 2 Selection on page 189 for details on switching motors.
Setting 1E: Restart Enabled The Restart Enabled output will be closed once the fault restart function becomes active and will remain closed until a successful restart is accomplished or the number of Auto Restart attempts as specified by L5-01 is reached. Refer to L5: Fault Restart on page 230 for details on automatic fault restart.
Setting 1F: Motor Overload Alarm oL1 An output programmed for this function will be closed when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level. Refer to L1-01: Motor Overload Protection Selection on page 213 for details.
Setting 20: Drive Overheat Pre-alarm (oH) Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02. Refer to L8-02: Overheat Alarm Level on page 235 for details on drive overheat detection.
Setting 22: Mechanical Weakening Detection Output closes when mechanical weakening is detected. Refer to Mechanical Weakening Detection on page 233 for details.
Setting 2F: Maintenance Period The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined by the estimated performance life span of those components.
Setting 30: During Torque Limit Output closes when the motor is operating at the torque limit specified by the L7-□□ parameters or an analog input. This setting is only valid when using Open Loop Vector Control (A1-02 = 2). Refer to L7-01/02/03/04: Torque Limits on page 234 for details.
Setting 37: During Frequency Output Output closes when the drive is outputting a frequency.
5.7 H: Terminal Functions
Baseblock N.C. — PDF page 202
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Baseblock is being executed. |
| 2 | Closed | Drive is not in a baseblock state. |
Motor2 Selected — PDF page 202
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Motor 1 is selected. |
| 2 | Closed | Motor 2 is selected. |
During Frequency Output — PDF page 202
| Source row | Status | Description |
|---|---|---|
| 1 | Open | Drive is not outputting a frequency. One of the following functions is being performed: Stop, baseblock, DC injection braking (during initial excitation), short circuit braking. |
| 2 | Closed | Drive is outputting frequency. |
Manual — Output conditions and protection status — page 203
Source reference: SIEP C71060618F, December 2016, physical PDF page 203. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Run command OFF/ON; baseblock command OFF/ON; output frequency with shaded beginning/ending braking portions; During Run OFF/ON spanning braking and baseblock; During Frequency Output OFF/ON only during the depicted frequency-output segments. No duration inferred. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.66 During Frequency Output Time Chart
Setting 38: Drive Enabled A Drive Enable digital output will reflect the status of a digital input configured as a Drive Enable input (H1-□□ = 6A). If the Drive Enable digital input is closed then the Drive Enabled digital output will also close.
Setting 39: Watt Hour Pulse Output Outputs a pulse to indicate the watt hours. Refer to H2-06: Watt Hour Output Unit Selection on page 204 for details.
Setting 3C: LOCAL/REMOTE Status Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status Description
Setting 3D: During Speed Search Output terminal closes while Speed Search is being performed. Refer to b3: Speed Search on page 130 for details on the Speed Search function.
Setting 3E: PID Feedback Low Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the level set to b5-13 for longer than the time set to b5-14. Refer to PID Feedback Loss Detection on page 141 for details.
Setting 3F: PID Feedback High Output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the level set to b5-36 for longer than the time set to b5-37. Refer to PID Feedback Loss Detection on page 141 for details.
Setting 4A: During KEB Operation Output terminal closes while KEB is being performed. Refer to Kinetic Energy Backup (KEB) Function on page 219 for a KEB function description.
Setting 4B: During Short Circuit Braking Closes the output terminal while Short Circuit Braking is being executed.
Setting 4C: During Fast-stop Output terminal closes when a Fast-stop is being executed. C1-09: Fast-stop Time for details.
Setting 4D: oH Pre-Alarm Time Limit Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat alarm has not disappeared after ten frequency reduction operation cycles. Refer to L8-03: Overheat Pre-Alarm Operation Selection on page 235 for details.
Setting 4E: Braking Transistor Fault (rr) The output closes when the internal braking transistor reaches the overheat level.
5.7 H: Terminal Functions
Parameter Details
LOCAL/REMOTE — PDF page 203
| Source row | Status | Description |
|---|---|---|
| 1 | Open | REMOTE: The selected external reference (b1-01/b1-02 or b1-15/b1-16) is used as frequency reference and Run command source |
| 2 | Closed | LOCAL: The digital operator is used as frequency reference and Run command source |
Manual — Pulse energy unit and analog input selection — page 204
Source reference: SIEP C71060618F, December 2016, physical PDF page 204. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 4F: Braking Resistor Overheat (rH) The output closes when the braking resistor exceeds the overheat level. the braking resistor may overheat due to the motor regeneration or short deceleration time setting.
Setting 90 to 92: DriveWorksEZ Digital Output 1 to 3 These settings are for digital output functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.
Setting 100 to 192: Reverse Switching for Functions 0 to 92 These settings reverse the switching status of the specified function. Set as 1□□, where the last two digits specify the setting number of the function to be reversed. Examples: • To reverse the output for “8: During Baseblock”, set “108”. • To reverse the output for “4A: During KEB” set “14A” .
n H2-06: Watt Hour Output Unit Selection
When one of the multi-function terminals is set to output the number of watt hours (H2-01/02/03 = 39), parameter H2-06 determines the units for the output signal. The output is intended to drive a watt hour meter or a PLC input by a 200 ms pulse signal. A pulse is output according to the kWh unit selected in H2-06.
No. Parameter Name Setting Range Default
u H3: Multi-Function Analog Input Terminals
The drive is equipped with 2 multi-function analog input terminals, A1 and A2. The user can assign functions to these terminals by setting parameters H3-02 and H3-10 between 0 and 31.
n H3-01: Terminal A1 Signal Level Selection
Selects the input signal level for analog input A1.
No. Name Setting Range Default
Setting 0: 0 to 10 Vdc with Limit The input level is 0 to 10 Vdc. Negative input values will be limited to 0. Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency reference can be set from 0 to 100% with an analog input of 5 to 10 V. The frequency reference will be zero when the analog input is between 0 and 5 V.
5.7 H: Terminal Functions
H2-06 — Watt Hour Output Unit Selection — PDF page 204
| Source row | No. | Parameter Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H2-06 | Watt Hour Output Unit Selection | 0: 0.1 kWh units 1: 1 kWh units 2: 10 kWh units 3: 100 kWh units 4: 1000 kWh units | 0 |
H3-01 — Terminal A1 Signal Level Selection — PDF page 204
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-01 | Terminal A1 Signal Level Selection | 0 to 1 | 0 |
Manual — A1 gain, bias and reverse-reference behavior — page 205
Source reference: SIEP C71060618F, December 2016, physical PDF page 205. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Analog input value −100%, 0, 100%; input voltage 0, 10 V. Negative input is limited to 0; solid positive line and dashed below-zero extension. Read with PDF204 example, not a new device setting. Exact source geometry, routing and unprinted numerical values remain original-only.
Analog input value −100%, 0, 100%; input voltage 0 V, 10 V; line from−100% at 0 V to 100% at 10 V. Negative reference reverses rotation per adjacent source example. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.67 Analog Input with Limit (Bias Setting -100%)
Setting 1: 0 to 10 Vdc without Limit The input level is 0 to 10 Vdc. Negative input values will be accepted. Example: Terminal A1 is set to supply the frequency reference, and the bias (H3-04) is set to -100%. The frequency reference can be set from 0 to 100% with an analog input of 5 to 10 V. With an input of 0 to 5 V, the frequency reference can be set from -100% to 0%. The drive reverses the motor rotation with negative input.
Figure 5.68 Analog Input without Limit (Bias Setting -100%)
n H3-02: Terminal A1 Function Selection
Determines the function assigned to analog input terminal A1. Refer to Multi-Function Analog Input Terminal Settings on page 208 for a list of functions and descriptions.
No. Name Setting Range Default
Note: If not using an input terminal or if using it in the through-mode, be sure to set that terminal to “F”.
n H3-03/H3-04: Terminal A1 Gain/Bias Setting
Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (Gain). Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1. Both can be used to adjust the analog input A1 characteristics.
5.7 H: Terminal Functions
Parameter Details
H3-02 — Terminal A1 Function Selection — PDF page 205
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-02 | Terminal A1 Function Selection | 0 to 31 | 0 |
H3-03 / H3-04 — Terminal A1 Gain Setting — PDF page 205
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-03 | Terminal A1 Gain Setting | -999.9 to 999.9% | 100.0% |
| 2 | H3-04 | Terminal A1 Bias Setting | -999.9 to 999.9% | 0.0% |
Manual — Analog gain and bias examples — page 206
Source reference: SIEP C71060618F, December 2016, physical PDF page 206. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Gain=100%, Bias=0%; Frequency reference versus 0 V to 10 V input. Linear example, not measured calibration. Exact source geometry, routing and unprinted numerical values remain original-only.
Gain=200%, Bias=0%; Frequency reference; 100% / E1-04 plateau from 5 V to 10 V; dashed extension reaches 200% at 10 V. Input 0 V, 5 V, 10 V. Exact source geometry, routing and unprinted numerical values remain original-only.
Gain=100%; Bias=−25%; Frequency reference; H3-01=0 clips at 0, H3-01=1 allows negative reference; input crossing is labeled 2.0 V, endpoint 10 V. Adjacent prose instead says 2.5 V; preserve both, do not resolve by calculation. Exact source geometry, routing and unprinted numerical values remain original-only.
Default Settings Using the factory default settings for the analog input’s function, gain, and bias, the 0 to 10 Vdc signal at the analog input will yield a 0 to 100% frequency reference span.
Figure 5.69 Analog Input A1 Default Characteristics
Setting Examples • Gain H3-03 = 200%, A1 as frequency reference input: An input 10 Vdc will be equivalent to a 200% frequency reference and 5 Vdc will be equivalent to a 100% frequency reference. Since the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04 above 5 Vdc.
Figure 5.70 Frequency Reference Setting by Analog Input with Increased Gain
• Bias H3-04 = -25%, A1 as frequency reference input An input of 0 Vdc will be equivalent to a -25% frequency reference. When parameter H3-01 = 0 the minimum frequency reference is 0% between 0 and 2.5 Vdc input. An analog input of 2.5 to 10 Vdc will now be the same as 0 to 100% of the frequency reference span. When parameter H3-01 = 1, the motor will rotate in reverse between 0 and 2.5 Vdc input.
Figure 5.71 Frequency Reference Setting by Analog Input with Negative Bias
• Gain = 0%, Bias = 100%, A1 as frequency reference input This setting leads to an inverse-acting frequency reference. The minimum analog input level (0 Vdc) will produce a 100% frequency reference and the maximum analog input level (10 Vdc) will produce a 0% frequency reference.
5.7 H: Terminal Functions
Manual — A2 signal selection and filter — page 207
Source reference: SIEP C71060618F, December 2016, physical PDF page 207. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Bias=100%, Gain=0%; Frequency reference from 100% at 0 V to 0% at 10 V. Inverse example. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.72 Frequency Reference Setting by Analog Input with Inverse Gain and Bias Settings
n H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Be sure to also set DIP switch S1 on the terminal board accordingly for a voltage input or current input.
No. Name Setting Range Default
Setting 0: 0 to 10 Vdc with Lower Limit The input level is 0 to 10 Vdc. Negative input values will be limited to 0. Refer to the explanation of H3-01, Setting 0. Refer to Setting 0: 0 to 10 Vdc with Limit on page 204
Setting 1: 0 to 10 Vdc without Lower Limit The input level is 0 to 10 Vdc. Negative input values will be accepted. Refer to the explanation of H3-01, Setting 1. Refer to Setting 1: 0 to 10 Vdc without Limit on page 205
Setting 2: 4 to 20 mA Current Input The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
Setting 3: 0 to 20 mA Current Input The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0 (like setting 0).
n H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2. Refer to Multi-Function Analog Input Terminal Settings on page 208 for a list of functions and descriptions.
n H3-11/H3-12: Terminal A2 Gain/Bias Setting
Parameter H3-11 sets the level of the selected input value that is equal to 10 Vdc/20 mA input at terminal A2 (Gain). Parameter H3-12 sets the level of the selected input value that is equal to 0 Vdc/4 mA/0 mA input at terminal A2. Both can be used to adjust the analog input A2 characteristics. The setting works in the same way as parameters H3-03/04 for analog input A1.
n H3-13: Analog Input Filter Time Constant
Parameter H3-13 sets the time constant for a first order filter that will be applied to both analog inputs A1 and A2.
An analog input filter can be used to prevent erratic drive control when a “noisy” analog reference is used. The drive operation becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.
5.7 H: Terminal Functions
Parameter Details
H3-09 — Terminal A2 Signal Level Selection — PDF page 207
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-09 | Terminal A2 Signal Level Selection | 0 to 3 | 2 |
H3-10 — Terminal A2 Function Selection — PDF page 207
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-10 | Terminal A2 Function Selection | 0 to 31 | 0 |
H3-11 / H3-12 — Terminal A2 Gain Setting — PDF page 207
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-11 | Terminal A2 Gain Setting | -999.9 to 999.9% | 100.0% |
| 2 | H3-12 | Terminal A2 Bias Setting | -999.9 to 999.9% | 0.0% |
H3-13 — Analog Input Filter Time Constant — PDF page 207
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-13 | Analog Input Filter Time Constant | 0.00 to 2.00 s | 0.03 s |
Manual — Analog function index and scaling — page 208
Source reference: SIEP C71060618F, December 2016, physical PDF page 208. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n Multi-Function Analog Input Terminal Settings
This section describes the various functions that can be assigned to terminals A1 and A2 by setting H3-02 and H3-10.
Note: The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting and adjusting analog input functions.
Table 5.29 Multi-Function Input Terminal Settings
Setting Function Page
<1> Available in drive software versions PRG: 1016 and later.
Setting 0: Frequency Bias The input value of an analog input set to this function will be added to the analog frequency reference value. Use this setting also when only one analog input is used to supply the frequency reference. By default both analog inputs A1 and A2 are set for this function. Using both A1 and A2 at the same time increases the frequency reference by the total of both inputs. Example: If the analog frequency reference by analog input A1 is 50% and a bias of 20% is applied by analog input A2, the resulting frequency reference will be 70% of the maximum output frequency.
Setting 1: Frequency Gain The input value of an analog input set to this function will be multiplied with the analog frequency reference value. Example: If the analog frequency reference from analog input A1 is 80% and a gain of 50% is applied from analog input A2, the resulting frequency reference will be 40% of the maximum output frequency.
Setting 2: Auxiliary Reference Sets the auxiliary frequency reference when Multi-Step Speed operation is selected. Refer to Multi-Step Speed Selection on page 160 for details.
Setting 4: Voltage Bias Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available only when using V/f Control.
Setting 7: Overtorque/Undertorque Level Overtorque level sets the overtorque/undertorque detection level using the analog input. This works with Torque Detection Selection 1 (L6-01) and will take the place of the torque detection level set to L6-02. For general Open Loop Vector Control, this function is based on 100% of the motor rated torque. For V/f Control and PM Open Loop Vector, this function is based on 100% of the drive rated current. Refer to L6: Torque Detection on page 231 for details on torque detection.
Setting B: PID Feedback An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01. Refer to PID Feedback Input Methods on page 137.
Setting C: PID Setpoint An input set for this function supplies the PID setpoint value. The frequency reference selected in parameter b1-01 no longer becomes the PID se point. This setting requires PID operation to be enabled in b5-01. Refer to PID Setpoint Input Methods on page 137.
Setting E: Motor Temperature In addition to or in place of the oL1 (motor overload) fault detection, it is possible to use a PTC (Positive Temperature Coefficient) thermistor for motor insulation protection. Refer to Motor Protection Using a Positive Temperature Coefficient (PTC) on page 215 for detailed explanations.
5.7 H: Terminal Functions
Table5.29 Analog input functions left — PDF page 208
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 0 | Frequency Bias | 208 |
| 2 | 1 | Frequency Gain | 208 |
| 3 | 2 | Auxiliary Frequency Reference | 208 |
| 4 | 4 | Output Voltage Bias | 208 |
| 5 | 7 | Overtorque/Undertorque Detection Level | 208 |
| 6 | B | PID Feedback | 208 |
| 7 | C | PID Set Point | 208 |
| 8 | E | Motor Temperature (PTC input) | 208 |
| 9 | F | Not used/Through Mode | 209 |
Table5.29 Analog input functions right — PDF page 208
| Source row | Setting | Function | Page |
|---|---|---|---|
| 1 | 10 | Forward Torque Limit | 209 |
| 2 | 11 | Reverse Torque Limit | 209 |
| 3 | 12 | Regenerative Torque Limit | 209 |
| 4 | 15 | General Torque Limit | 209 |
| 5 | 16 | Differential PID Feedback | 209 |
| 6 | 30 | DriveWorksEZ Analog Input 1 | 209 |
| 7 | 31 | DriveWorksEZ Analog Input 2 | 209 |
| 8 | 41 <1> | Output Voltage Gain | 209 |
Manual — Torque limits and analog enable — page 209
Source reference: SIEP C71060618F, December 2016, physical PDF page 209. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Axes positive/negative torque reference and REV/FWD motor rotation. Quadrant 1 FWD motoring:10 Positive Torque Limit, 15 Torque Limit, Parameter L7-01. Quadrant 2 REV regenerative:10 Positive, 12 Regenerative, 15 Torque Limit, Parameter L7-04. Quadrant 3 REV motoring:11 Negative, 15 Torque Limit, Parameter L7-03. Quadrant 4 FWD regenerative:11 Negative, 12 Regenerative, 15 Torque Limit, Parameter L7-02. Lowest applicable limit applies per prose; OLV only. Exact source geometry, routing and unprinted numerical values remain original-only.
Setting F: Not Used Any analog input that is not used should be set to F. When set to “F”, an input does not affect any drive function but the input level can be read out by a PLC via a communication option or MEMOBUS/Modbus communications (through mode). This way drive analog inputs can be used to read out external sensor values if there is a lack of PLC analog inputs.
Setting 10/11/12/15: Positive/Negative/Regenerative/General Torque Limit (OLV only) These functions make it possible to limit the torque reference with an analog input. The limit can either be set as a general value for all operation conditions (setting 15) or can be programmed separately for each operation condition (quadrants 1, 2, 3, and 4). Figure 5.73 shows which limit is applied in each quadrant. The lowest of the values will always be used as the limit. The value is set as a percentage of the motor rated torque. Refer to L7: Torque Limit on page 234 for information how torque limits work.
Figure 5.73 Analog Input Torque Limits
Setting 16: Differential PID Feedback If an analog value is set for this function, the PID controller is set for differential feedback. The subtraction of the PID feedback input value and the differential feedback input value builds the feedback value that is used to calculate the PID input. Refer to PID Feedback Input Methods on page 137.
Setting 30/31: DriveWorksEZ Analog Input 1/2 These settings are for analog output functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.
Setting 41: Output Voltage Gain Allows the user to change the output voltage by adjusting the voltage reference via one of the analog input terminals or with MEMOBUS/Modbus. An internal 0.3 second delay has been added to prevent sudden, drastic change to the V/f pattern.
Note: When an input terminal is assigned to adjust the Output Voltage Gain (H3-□□ = 41), a voltage reference from MEMOBUS/Modbus is ignored.
n H3-14: Analog Input Terminal Enable Selection
Note: Parameter available in drive software versions PRG: 1016 and later. Determines which of the analog input terminals will be enabled or disabled when a digital input programmed for “Analog input enable” (H1-□□ = C) is closed. When H1-□□ ≠ C, all of the input terminals are enabled all of the time. Terminals not set as the target are not influenced by input signals.
No. Name Setting Range Default
Setting 1: Terminal A1 only Setting 2: Terminal A2 only Setting 7: All Terminals Enabled n H3-16/H3-17: Terminal A1/A2 Offset
Note: Parameters available in drive software versions PRG: 1016 and later. Determines the amount of offset to be used to calibrate analog input signals from the terminals A1 and A2.
5.7 H: Terminal Functions
Parameter Details
H3-14 — Analog Input Terminal Enable Selection — PDF page 209
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-14 | Analog Input Terminal Enable Selection | 1, 2, 7 | 7 |
Manual — Analog output and terminal calibration — page 210
Source reference: SIEP C71060618F, December 2016, physical PDF page 210. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Left graph: terminal AM output voltage 0 V, 5 V, 10 V; monitor value 0–100%; Bias 0%; Gain 150%, 100%, 50% lines. Right graph: monitor 0–100%; terminal AM0 V, 3 V, 10 V; Gain 100% with Bias 30% versus Bias 0%. Output constrained 0–10 Vdc per source. Exact source geometry, routing and unprinted numerical values remain original-only.
Enter a 0 V signal to terminal A1. Next adjust the offset in H3-16 until the monitor U1-13 for the terminal A1 input voltage reads 0.0%. The process is the same for terminal A2. Enter a 0 V signal, and adjust the offset for terminal A2 in H3-17 until the monitor U1-14 for terminal A2 input voltage reads 0.0%.
No. Name Setting Range Default
u H4: Multi-Function Analog Output Terminals
These parameters assign a function to analog output terminal AM for monitoring a specific aspect of drive performance.
n H4-01: Multi-Function Analog Terminal AM Monitor Selection
Sets the desired drive monitor parameter U□-□□ to output as an analog value via terminal AM. Refer to U: Monitors on page 399 for a list of all monitors. The “Analog Output Level” columns indicates if a monitor can be applied for analog output. Example: Enter “103” for U1-03.
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting the terminal AM output level can be set by a PLC via a communication option or MEMOBUS/Modbus communications (through mode).
n H4-02/H4-03: Multi-Function Analog Output Terminal AM Gain/Bias
Parameter H4-02 sets the output voltage that is equal to 100% of the monitor value. Parameter H4-03 sets the output voltage equal to 0% of the monitor value. Both values are set as a percentage of 10 V. The minimum output voltage for terminal AM is 0 V, the maximum is 10 Vdc. Figure 5.74 illustrates the function of the gain and bias settings.
Figure 5.74 Analog Output Gain/Bias Setting
When viewing the settings for H4-02, terminal AM will output a voltage that is equal to 100% of the monitor value (considering the present setting). When viewing the settings for H4-03, terminal AM will output a voltage that is equal to 0% of the monitor value.
u H5: MEMOBUS/Modbus Serial Communication
Through the drives built in RS-422/485 port (terminals R+, R-, S+, S-), serial communication can be performed with programmable logic controllers (PLCs) or similar devices using the MEMOBUS/Modbus protocol. The H5-□□ parameters are used to set up the drive for MEMOBUS/Modbus Communications. Refer to MEMOBUS/Modbus Serial Communication on page 439 for detailed descriptions of the H5-□□ parameters.
5.7 H: Terminal Functions
H3-16 / H3-17 — Terminal A1 Offset — PDF page 210
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H3-16 | Terminal A1 Offset | -500 to 500 | 0 |
| 2 | H3-17 | Terminal A2 Offset | -500 to 500 | 0 |
H4-01 — Multi-Function Analog 1 (Terminal AM Monitor Selection) — PDF page 210
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H4-01 | Multi-Function Analog 1 (Terminal AM Monitor Selection) | 000 to 999 | 102 |
H4-02 / H4-03 — Multi-Function Analog Output Terminal AM Gain — PDF page 210
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H4-02 | Multi-Function Analog Output Terminal AM Gain | -999.9 to 999.9% | 100.0% |
| 2 | H4-03 | Multi-Function Analog Output Terminal AM Bias | -999.9 to 999.9% | 0.0% |
Manual — Pulse input functions and scaling — page 211
Source reference: SIEP C71060618F, December 2016, physical PDF page 211. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u H6: Pulse Train Input/Output
A one track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse train signal can be used as the frequency reference, for PID functions, or as the speed feedback signal in V/f Control. The pulse output monitor terminal MP, which can be used in sinking or sourcing mode, can output drive monitors values as a pulse train signal with a maximum frequency of 32 kHz. Use parameters H6-□□ to scale and set up the function for the pulse input terminal RP and pulse output terminal MP.
n H6-01: Pulse Train Input Terminal RP Function Selection
Selects the function of pulse train input terminal RP.
No. Name Setting Range Default
Setting 0: Frequency Reference If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01/15 = 4), the drive reads the frequency value from terminal RP.
Setting 1: PID Feedback Value Using this setting, the feedback value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID Control on page 136 for details on PID control.
Setting 2: PID Setpoint Value Using this setting, the setpoint value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID Control on page 136 for details on PID control.
Setting 3: Speed Feedback for V/f Control (V/f Control only, Motor 1 only) This setting enables simple speed feedback for V/f Control. A pulse signal can be used to input the motor speed to the drive and thereby improve the speed control accuracy. Note that this speed feedback can only be a one track signal that cannot be used for direction detection. The drive needs a separate motor rotation direction signal. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details on using Simple V/f Control with Speed Feedback.
n H6-02: Pulse Train Input Terminal RP Scaling
The pulse train input scaling parameter sets the terminal RP input frequency that is equal to 100% of the signal selected as the input value in parameter H6-01.
<1> Setting range is determined by drive software version. PRG: 1016 and later: 100 to 32000 Hz PRG: 1015 and earlier: 1000 to 32000 Hz
n H6-03: Pulse Train Input Terminal RP Gain
Sets the level of the value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to terminal RP.
n H6-04: Pulse Train Input Terminal RP Bias
Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.
n H6-05: Pulse Train Input Terminal RP Filter Time
Sets the pulse train input filter time constant in seconds. The pulse train input filter helps prevent noise interference from causing erroneous operation when operating the drive within the pulse train signal.
5.7 H: Terminal Functions
Parameter Details
H6-01 — Pulse Train Input Terminal RP Function Selection — PDF page 211
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H6-01 | Pulse Train Input Terminal RP Function Selection | 0 to 4 | 0 |
H6-02 — Pulse Train Input Scaling — PDF page 211
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H6-02 | Pulse Train Input Scaling | <1> | 1440 Hz |
H6-03 — Pulse Train Input Gain — PDF page 211
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H6-03 | Pulse Train Input Gain | 0.0 to 1000.0% | 100.0% |
H6-04 — Pulse Train Input Bias — PDF page 211
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H6-04 | Pulse Train Input Bias | -100.0 to 100.0% | 0.0% |
Manual — Pulse output selection and scaling — page 212
Source reference: SIEP C71060618F, December 2016, physical PDF page 212. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Increasing the filter setting time increases the effectiveness of the noise prevention, however, this also increasingly slows drive response time.
No. Name Setting Range Default
n H6-06: Pulse Train Output Terminal MP Monitor Selection
Selects the pulse train monitor output terminal MP function. The set value □□□ is equal to the numerals in U□-□□ of the selected monitor. Refer to U: Monitors on page 399 for a complete list of monitors. Selectable monitor items are listed below.
n H6-07: Pulse Train Output Terminal MP Monitor Scaling
Pulse train monitor scaling sets the output frequency at terminal MP when the monitor item is 100%. Set H6-06 to 102 and H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
5.7 H: Terminal Functions
H6-05 — Pulse Train Input Filter Time — PDF page 212
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H6-05 | Pulse Train Input Filter Time | 0.00 to 2.00 s | 0.10 s |
H6-06 — Pulse Train Output Terminal MP Monitor Selection — PDF page 212
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H6-06 | Pulse Train Output Terminal MP Monitor Selection | 000, 031, 101, 102, 105, 116, 501, 502, 801 to 809 | 102 |
H6-07 — Pulse Train Input Monitor Scaling — PDF page 212
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | H6-07 | Pulse Train Input Monitor Scaling | 0 to 32000 Hz | 1440 Hz |
Manual — Motor overload selection and multiple motors — page 213
Source reference: SIEP C71060618F, December 2016, physical PDF page 213. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Power supply; Drive; M1/M2; MC1/MC2 magnetic contactors; L10/L20 thermal relays. Example circuit supports adjacent requirement for individual thermal overloads when multiple motors share a drive; not an inferred installation diagram. Exact source geometry, routing and unprinted numerical values remain original-only.
Torque (%) ticks 50, 60, 90, 100, 150; Speed (%) ticks 0, 5, 33, 100, 120, 167, 200; 100 speed corresponds 60 Hz. Rated Speed=100% Speed; 60 sec.; Continuous; curves A/B/C. No unprinted curve values or letter applicability inferred. Same row cooling/overload prose captured in V1000-P213-T2. Exact source geometry, routing and unprinted numerical values remain original-only.
5.8 L: Protection Functions
u L1: Motor Protection Functions
n L1-01: Motor Overload Protection Selection
The drive has an electronic overload protection function that estimates the motor overload level based on output current, output frequency, thermal motor characteristics, and time. An oL1 fault will be triggered when motor overload is detected. L1-01 sets the overload protection function characteristics according to the motor being used.
No. Name Setting Range Default
<1> Setting 6 is available in drive software versions PRG: 1016 and later.
Note: 1. When the motor protection function is enabled (L1-01 is not set to zero), an oL1 alarm can be output through one of the multi-function outputs by setting H2-01 to 1F. The output will close when the motor overload level reaches 90% of the oL1 detection level. 2. Select a method to protect the motor from overheat by setting L1-01 to a value between 1 and 4; use setting 6 when running a single motor from the drive. An external thermal relay is not required.
Setting 0: Disabled - Motor Overload Protection is not Provided This setting should be used if no motor overheat protection is desired or if multiple motors are connected to one drive. In this case it is recommended that you install a thermal relay for each motor as show in Figure 5.75
Figure 5.75 Example of Protection Circuit Design for Multiple Motors
NOTICE: Protect each motor with individual thermal overloads when multiple motors are connected to one drive. Failure to comply could result in motor damage. Disable the electronic overload protection of the drive (L1-01 = “0: Disabled”) and protect each motor with individual motor thermal overloads.
Setting 1: General Purpose Motor (standard self-cooled) Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the motor from overheat throughout the entire speed range.
Overload Tolerance Cooling Ability Overload Characteristics
Setting 2: Drive Dedicated Motor (constant torque, 1:10) Use this setting when operating a drive duty motor with a torque ratio of 1:10. This motor type is allowed to run with 100% load from 10% up to 100% speed. Running slower speeds with full load can trigger an overload fault.
Parameter Details
Read with same-row overload graph captured separately; no graph values inferred.
L1-01 — Motor Overload Protection Selection — PDF page 213
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-01 | Motor Overload Protection Selection | 0 to 4; 6 <1> | A1-02 dependent |
L1-01 Setting1 General Purpose Motor — PDF page 213
| Source row | Cooling Ability | Overload Characteristics |
|---|---|---|
| 1 | Motor designed to operate from line power. Motor cooling is most effective when running at rated nameplate base frequency (check the motor specifications). | Continuous operation at less than line power frequency with 100% load can trigger motor overload protection (oL1). A fault is output and the motor will coast to stop. |
Manual — Motor-specific overload characteristics — page 214
Source reference: SIEP C71060618F, December 2016, physical PDF page 214. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Torque (%) ticks 50, 55, 100, 150; Speed (%) ticks 0, 1, 10, 100, 120, 167, 200; 100 speed corresponds 60 Hz. Rated Speed=100% Speed; 60 sec.; Continuous; curves A/D/B. Read with 1:10 and 100% load 10–100% speed prose and same-row 6 Hz cooling statement. No curve interpolation. Exact source geometry, routing and unprinted numerical values remain original-only.
Torque (%) ticks 0, 50, 90, 100, 150; Speed (%) ticks 1, 100, 120, 167, 200; 100 speed corresponds 60 Hz. Rated Speed=100% Speed; 60 sec.; Continuous; curves A/B/D. Read with 1:100 and 100% load 1–100% speed prose and approximately 0.6 Hz cooling statement. No curve interpolation. Exact source geometry, routing and unprinted numerical values remain original-only.
Torque (%) ticks 50, 80, 100, 120, 150; Motor Speed (%) ticks 0, 10, 33, 100.60 sec. upper curve; Continuous lower curve. Same-row PM cooling/overload prose retained separately. No intermediate curve value inferred. Exact source geometry, routing and unprinted numerical values remain original-only.
Overload Tolerance Cooling Ability Overload Characteristics
Setting 3: Vector Motor (constant torque, 1:100) Use this setting when operating a drive dedicated motor with a torque ratio of 1:100. This motor type is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload fault.
Setting 4: PM Derated Torque Motor This setting is for operating a PM motor. PM motors for derated torque have a self-cooling design, so the overload tolerance drops as the motor slows. Electronic thermal overload is triggered in accordance with the motor overload characteristics, providing overheat protection across the entire speed range.
Setting 6: General-Purpose Motor Note: General-purpose motors are designed with a base speed that operates at line frequency (50/60 Hz depending on geographic region). Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately adjusts the electrothermal trigger point according to the motor overload characteristics and protects the motor from overheat throughout the entire speed range.
5.8 L: Protection Functions
Read with same-row overload graph captured separately; no graph values inferred.
L1-01 Setting2 Drive Dedicated Motor — PDF page 214
| Source row | Cooling Ability | Overload Characteristics |
|---|---|---|
| 1 | Motor is designed to effectively cool itself at speeds as low as 6 Hz. | Continuous operation with 100% load from 6 Hz to 50/60 Hz. |
L1-01 Setting3 Vector Motor — PDF page 214
| Source row | Cooling Ability | Overload Characteristics |
|---|---|---|
| 1 | Motor is designed to effectively cool itself at speeds as low as approximately 0.6 Hz. | Continuous operation with 100% load from 0.6 Hz to 50/60 Hz. |
L1-01 Setting4 PM Derated Torque — PDF page 214
| Source row | Cooling Ability | Overload Characteristics |
|---|---|---|
| 1 | Motor is designed to produce 100% torque at base speed. Built with effective cooling capabilities. | Reaching 100% when operating at below the base frequency causes a motor overload fault (oL1). The drive fault output closes and the motor coasts to stop. |
Manual — Overload time and PTC introduction — page 215
Source reference: SIEP C71060618F, December 2016, physical PDF page 215. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Rated Speed=100% Speed; 60 s; Torque (%)50, 60, 90, 100, 150; Speed (%)0, 5, 33, 100, 120, 167, 200. A:Max.speed for 200LJ and above; B:Max.speed for 160MJ to 180 LJ; C:Max.speed for 132MJ and below; Continuous. Only literal printed letter legend retained; no applicability inferred for other plot letters. Exact source geometry, routing and unprinted numerical values remain original-only.
Operation time(minutes)0.1, 0.4, 1, 3, 7, 10; Motor current(%)0, 100, 150, 200; E2-01=100% motor current. Cold start curve: marked 150%/7 min and 200%/3 min; Hot start:marked 150%/1 min and 200%/0.4 min. Shaded region between curves. Example at E1-06 rated output frequency with L1-02=1 minute; not a universal overload guarantee. Exact source geometry, routing and unprinted numerical values remain original-only.
Overload Tolerance Cooling Ability Overload Characteristics
n L1-02: Motor Overload Protection Time
Sets the time for the drive to shut down on motor overload (oL1) when the motor is running with excessive current. Enter the time the motor can withstand operating at 150% current after previously running at 100% current (hot motor overload condition). This parameter rarely requires adjustment.
No. Name Setting Range Default
Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start after continuous operation at 100%. Figure 5.76 illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at the value of E1-06, Motor Base Speed, with L1-02 set to one minute. Motor overload protection operates in the area between a cold start and a hot start. • Cold start: Characteristics of motor protection operation time in response to an overload situation that was suddenly reached when starting a stationary motor. • Hot start: Characteristics of motor protection operation time in response to an overload situation that occurred while the motor was operating continuously at or below its rated current.
Figure 5.76 Protection Operation Time for General Purpose Motors at the Rated Output Frequency
n Motor Protection Using a Positive Temperature Coefficient (PTC)
A motor PTC can be connected to an analog input of the drive. This input is used by the drive for motor overheat protection. When the motor overheat alarm level is reached, an oH3 alarm will be triggered and the drive will continue operation as selected in L1-03. When the overheat fault level is reached an oH4 fault is triggered, a fault signal will be output and the drive will stop the motor using the stop method determined in L1-04. Figure 5.77 shows a PTC connection example for analog input A2. If using analog input A2, make sure to set DIP switch S1 on the terminal board for voltage input when using this function.
5.8 L: Protection Functions
Parameter Details
Read with same-row overload graph captured separately; no graph values inferred.
L1-02 — Motor Overload Protection Time — PDF page 215
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-02 | Motor Overload Protection Time | 0.1 to 5.0 minutes | 1.0 minutes |
L1-01 Setting6 General-Purpose Motor — PDF page 215
| Source row | Cooling Ability | Overload Characteristics |
|---|---|---|
| 1 | Motor designed to operate from line power. Motor cooling is most effective when running at rated base frequency (check the motor nameplate or specifications) | Continuous operation at less than line power frequency with 100% load can trigger motor overload protection (oL1). A fault is output and the motor will coast to stop. |
Manual — PTC circuit, characteristics and alarm — page 216
Source reference: SIEP C71060618F, December 2016, physical PDF page 216. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive; Multi-function input; +V(+10.5 V, 20 mA); branch resistor 12 kΩ; PTC thermistor; A2(0–10 V); AC. MA/MB/MC multi-function output(contact); P1/P2/PC multi-function output(photocoupler). Source wiring example, exact connectivity original-only. Exact source geometry, routing and unprinted numerical values remain original-only.
Resistance(Ω)550, 1330; Temperature°C; Class F150°C, Class H180°C; Tr:threshold value; Tr−5, Tr, Tr+5, Tr′. Solid/dashed characteristics; one motor phase, normally three PTCs in series per prose. No interpolation of curves. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.77 Connection of a Motor PTC
The PTC must have the following characteristics for one motor phase. Normally a motor is protected by three PTCs connected in series.
Figure 5.78 Motor PTC Characteristics
Overheat detection using a PTC can be set up by parameters L1-03/04/05 as explained below.
n L1-03: Motor Overheat Alarm (oH3) Operation Selection
Sets the drive operation when the PTC input signal reaches the motor overheat alarm level. (PTC input level: Tr - 5 °C)
No. Name Setting Range Default
Setting 0: Ramp to Stop The drive stops the motor using the active deceleration time.
Setting 1: Coast to Stop The drive output is switched off and the motor coasts to stop.
Setting 2: Fast-stop The drive stops the motor using the Fast-stop time set in parameter C1-09.
Setting 3: Alarm Only The operation is continued and an oH3 alarm is displayed on the digital operator
5.8 L: Protection Functions
L1-03 — Motor Overheat Alarm Operation Selection — PDF page 216
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-03 | Motor Overheat Alarm Operation Selection | 0 to 3 | 3 |
Manual — PTC fault and leakage-current filters — page 217
Source reference: SIEP C71060618F, December 2016, physical PDF page 217. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n L1-04: Motor Overheat Fault (oH4) Operation Selection
Sets the drive operation when the PTC input signal reaches the motor overheat fault level. (PTC input level: Tr + 5 °C)
No. Name Setting Range Default
Setting 0: Ramp to Stop The drive stops the motor using the active deceleration time.
Setting 1: Coast to Stop The drive output is switched off and the motor coasts to stop.
Setting 2: Fast-stop The drive stops the motor using the Fast-stop time set in parameter C1-09.
n L1-05: Motor Temperature Input Filter Time
Used to set a filter on the PTC signal in order to prevent a motor overheat fault from being mistakenly detected.
n L1-13: Continuous Electrothermal Operation Selection
Determines whether to hold the current value of the electrothermal motor protection (L1-01) when the power supply is interrupted.
Setting 0: Disabled Setting 1: Enabled n L1-22: Leakage Current Filter Time Constant 1
Note: 1. Available in drive software versions PRG: 1021 and later. 2. Available only when C6-02 is set to B. To display this parameter, first set C6-02 to B. Sets the time constant for the filter applied to motor overload detection current or monitor current for constant speed operation. Leakage current can incorrectly trigger motor overload fault oL1 or result in incorrect monitor reading. Increase this setting if erroneous detection occurs or if the monitor display is incorrect.
NOTICE: Setting parameter L1-22 too high may cause the drive to detect motor overload too slowly and burn out the motor. Be sure to set L1-22 to an appropriate value for the application.
n L1-23: Leakage Current Filter Time Constant 2
Note: 1. Available in drive software versions PRG: 1021 and later. 2. Available only when C6-02 is set to B. To display this parameter, first set C6-02 to B. Sets the time constant for the filter applied to monitor current during acceleration and deceleration. Leakage current can result in incorrect monitor reading. Increase this setting if the monitor display is incorrect.
Note: Setting parameter L1-23 too high may cause the current monitor to take too long to read the initial current level. Check the operation sequence being used if this is a problem.
5.8 L: Protection Functions
Parameter Details
L1-04 — Motor Overheat Fault Operation Selection — PDF page 217
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-04 | Motor Overheat Fault Operation Selection | 0 to 2 | 1 |
L1-05 — Motor Temperature Input Filter Time — PDF page 217
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-05 | Motor Temperature Input Filter Time | 0.00 to 10.00 s | 0.20 s |
L1-13 — Continuous Electrothermal Operation Selection — PDF page 217
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-13 | Continuous Electrothermal Operation Selection | 0 or 1 | 1 |
L1-22 — Leakage Current Filter Time Constant 1 — PDF page 217
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-22 | Leakage Current Filter Time Constant 1 | 0.0 to 60.0 s | 20.0 s |
L1-23 — Leakage Current Filter Time Constant 2 — PDF page 217
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L1-23 | Leakage Current Filter Time Constant 2 | 0.0 to 60.0 s | 1.0 s |
Manual — Momentary power-loss recovery — page 218
Source reference: SIEP C71060618F, December 2016, physical PDF page 218. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u L2: Momentary Power Loss Ride-Thru
n L2-01: Momentary Power Loss Operation Selection
When a momentary power loss occurs (DC bus voltage falls below the level set in L2-05), the drive can be set to automatically return to the operation it was performing when the power went out based on certain conditions.
No. Name Setting Range Default
Setting 0: Disabled (default) If power is not restored within 15 ms, a Uv1 fault will result and the drive will stop the motor.
Setting 1: Enabled, Recover Within L2-02 When a momentary power loss occurs, the drive will attempt to restart and perform Speed Search if power is restored within the period of time set to parameter L2-02. If power is not restored within the time set to L2-02 (i.e. DC bus voltage level remains below Uv1 detection level L2-05), then a Uv1 fault is triggered and the drive output will be shut off.
Setting 2: Recover as Long as CPU has Power Drive will try to restart as long as the CPU still has power. This allows for a longer ride-through time than setting L2-01 to 1. A Uv1 fault is not triggered. This setting should also be used if the KEB function is utilized.
Note: 1. The amount of time the drive is capable of recovering after a power loss is determined by the capacity of the drive. Drive capacity determines the upper limit for L2-02. 2. When L2-01 is set to 1 or 2, and a magnetic contactor between motor and drive is used, be sure that the magnetic contactor is kept close as long as the drive attempts to restart. 3. When L2-01 is set to 1 or 2, “Uv” will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not output at this time.
n L2-02: Momentary Power Loss Ride-Thru Time
Set the time in which the power has to return before a Uv fault is tripped. This parameter is valid only if L2-01 = 1.
n L2-03: Momentary Power Loss Minimum Baseblock Time
Sets the minimum baseblock time when power is restored following a momentary power loss. This determines the time it takes for the leftover voltage in the motor to dissipate. Increase this setting if overcurrent or overvoltage occur at the beginning of Speed Search after a power loss or DC Injection Braking. If L2-03 > L2-02, then the drive will restart after the time set to L2-03 has passed from the beginning of the power loss.
n L2-04: Momentary Power Loss Voltage Recovery Ramp Time
Sets the time constant used to ramp up the voltage during Speed Search. The setting value determines the time for a change from zero to the maximum voltage.
n L2-05: Undervoltage Detection Level
Determines the voltage at which a Uv1 fault is triggered or at which the KEB function is activated.
<1> Values are for 200 V class drives and must be doubled for 400 V class drives. <2> This value is initialized when E1-01 is changed.
5.8 L: Protection Functions
L2-01 — Momentary Power Loss Operation Selection — PDF page 218
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-01 | Momentary Power Loss Operation Selection | 0 to 2 | 0 |
L2-02 — Momentary Power Loss Ride-Thru Time — PDF page 218
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-02 | Momentary Power Loss Ride-Thru Time | 0.0 to 25.5 s | Determined by o2-04. |
L2-03 — Momentary Power Loss Minimum Baseblock Time — PDF page 218
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-03 | Momentary Power Loss Minimum Baseblock Time | 0.1 to 5.0 s | Determined by o2-04 |
L2-04 — Momentary Power Loss Voltage Recovery Ramp Time — PDF page 218
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-04 | Momentary Power Loss Voltage Recovery Ramp Time | 0.0 to 5.0 s | Determined by o2-04 |
L2-05 <1> — Undervoltage Detection Level — PDF page 218
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-05 <1> | Undervoltage Detection Level | 150 to 210 V | 190 V <2> |
Manual — KEB modes and activation — page 219
Source reference: SIEP C71060618F, December 2016, physical PDF page 219. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
KEB Ride-Thru(H1-□□=65 or 66) OFF/ON/OFF; Output frequency; L2-06 deceleration interval followed by L2-07 acceleration. Run and activation conditions in adjacent prose apply; no numeric time inferred. Exact source geometry, routing and unprinted numerical values remain original-only.
This setting rarely needs to be changed. When setting L2-05 is lower than the default setting, be sure to install an AC reactor option to the input side of the power supply to prevent damage to drive circuitry.
n Kinetic Energy Backup (KEB) Function
In case of a power loss, the KEB function can decelerate the motor and use the rotational energy of the machine to backup/ maintain the drive DC bus for a certain period of time. This allows the drive to continue running without interrupting the output power during a momentary power loss. Once the power is restored, the drive smoothly returns to the same operational state before the power loss occurred. The KEB function supports two different operation modes.
KEB 1 In this mode the drive decelerates the motor based on the deceleration time set in parameter L2-06/C1-09 in order to keep the DC bus voltage level high. When the power supply returns, it uses the time set to L2-07 or the selected acceleration time to accelerate back to the frequency reference.
Figure 5.79 KEB Ride-Thru Timing Diagram for Multiple Drives
Note: If L2-06 is set to 0.0 s, C1-09 is used instead. If L2-07 is set to 0.0 s, the drive reaccelerates using the selected acceleration time. Use this method with setting parameters L2-06 and L2-07 if multiple drives must decelerate but still keep the speed ratio between the drives constant during power loss. In this case, a braking resistor is required in order to avoid overvoltage trips.
KEB 2 In this mode the drive decelerates the motor by calculating the energy of the rotating system. The deceleration rate is continuously adjusted so that the DC bus voltage meets the level set in parameter L2-11. The rotational energy is estimated using the parameters L3-24 and L3-25. When the power supply returns, the drive accelerates back to the frequency reference using the selected acceleration time.
Activation and Deactivation of the KEB Function The KEB function requires parameter L2-01 to be set to 1 or 2 and a digital input has to be configured for the KEB 1 (H1-□□ = 65/66) or KEB 2 (H1-□□ = 7A/7B) command. The input has to be enabled during KEB. Refer to Setting 65/66: KEB Ride-Thru 1 (N.C.)/2 (N.O.) on page 192 and Refer to Setting 7A/7B: KEB Ride-Thru 2 (N.C./N.O.) on page 194 for details on setting the KEB input commands. The KEB function is automatically activated when one of the conditions below becomes true. • The DC bus voltage falls below the level set in parameter L2-05. The KEB input has to be set within 50 ms after the KEB function was activated, or the drive will assume the power supply has returned and attempt to restart. • The input programmed for KEB 1 or 2 is activated. This input should be triggered by an external undervoltage detection relay. The KEB function ends when one of the conditions below become true. • The KEB input was released or • The function was activated by DC bus voltage detection and no KEB input was set within 50 ms after the KEB activation. Figure 5.80 shows a wiring example for triggering the KEB function at power loss using digital input S6.
5.8 L: Protection Functions
Parameter Details
Manual — KEB wiring example and adjustment scope — page 220
Source reference: SIEP C71060618F, December 2016, physical PDF page 220. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Braking Resistor atB1/B2; L1/L2/L3; driveR/L1, S/L2, T/L3 andU/T1, V/T2, W/T3; M; UV Detection Relay; S6 KEB command 1 or 2; S1 Start command; SC. Original topology retained; no new wiring recommendations. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.80 KEB Function Wiring Example
Note: Make sure the Run command is not switched off when momentary power loss occurs. If the Run command is shut off, the drive will not accelerate back to speed when the power is restored.
KEB Related Adjustment Parameters The KEB 1 functions can be adjusted using the following parameters: • L2-05, Undervoltage Detection Level • L2-06 or C1-09, KEB Deceleration Time or Fast-stop Time • L2-07, KEB Acceleration Time • L2-08, Frequency Gain at KEB Start Use the following parameters when adjusting the KEB 2 function: • L2-05, Undervoltage Detection Level • L2-08, Frequency Gain at KEB Start • L2-11, Desired DC Bus Voltage during KEB • L3-20, Main Circuit DC Voltage Adjustment Gain Sets the proportional gain for controlling the DC bus voltage and keeping it at the desired level during KEB 2 operation. • L3-21, Accel/Decel Rate Calculation Gain Sets the gain used to calculate the acceleration or deceleration rate when KEB 2 is active. • L3-24, Motor Acceleration Time This value is used to estimate the regenerative power fed back from the mechanics to the drive DC bus during KEB 2. • L3-25, Load Inertia Ratio This value is used to estimate the regenerative power fed back from the mechanics to the drive DC bus during KEB 2.
n L2-06: KEB Deceleration Time (KEB 1 only)
Sets the time to decelerate from the frequency reference when the KEB command was input down to zero speed. It can be used to decelerate different drives down to zero in the same time and thereby keep a constant speed ratio. When L2-06 is set to 0.0 s, the time set in parameter C1-09 (set for deceleration from maximum frequency to zero) is used for the deceleration.
No. Name Setting Range Default
n L2-07: KEB Acceleration Time (KEB 1 only)
Sets the time to reaccelerate from the speed when KEB was deactivated to the frequency reference. It can be used to accelerate different drives up to their frequency reference in the same time and thereby keep a constant speed ratio. When set to 0, the drive will accelerate back up to speed according to parameters C1-01 through C1-08 (set for acceleration from zero to maximum frequency).
5.8 L: Protection Functions
L2-06 — KEB Deceleration Time — PDF page 220
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-06 | KEB Deceleration Time | 0.0 to 200.0 s | 0.0 s |
Manual — KEB gains and acceleration stall prevention — page 221
Source reference: SIEP C71060618F, December 2016, physical PDF page 221. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
n L2-08: Frequency Gain at KEB Start (KEB 1 only)
When KEB 1 is activated, the output frequency is reduced in a single step in order to quickly get the motor into a regenerative state. The amount of this frequency reduction can be calculated using the following formula: Amount of reduction = Slip frequency prior to KEB x (L2-08/100) x 2
n L2-11: Desired DC Bus Voltage during KEB (KEB 2 only)
Sets the desired voltage in the DC bus during KEB 2 operation.
<1> Values are for 200 V class drives and must be doubled for 400 V class drives.
u L3: Stall Prevention
When the load is too high or acceleration and deceleration times are too short, the motor may be unable to keep up with the frequency reference, resulting in excessive slip. This “stalling” makes it impossible to decelerate or accelerate. The drive can prevent the motor from stalling and still reach the desired speed without the user needing to change the acceleration or deceleration time settings. The Stall Prevention function can be set separately for acceleration, operating at constant speeds, and deceleration.
n L3-01: Stall Prevention Selection during Acceleration
Stall Prevention during acceleration is used when the motor loses speed during acceleration due to a relatively large load. It prevents overcurrent and motor overload (oL1) from occurring. This parameter sets the Stall Prevention method for acceleration.
<1> Setting 2 is not available for PM OLV.
Setting 0: Disabled No Stall Prevention is provided. If the acceleration time setting is too short, the drive may not be able to accelerate within the set time and the motor may stall.
Setting 1: Enabled Enables Stall Prevention during acceleration. The operation depends on the selected control mode. • V/f or Open Loop Vector Control: When the output current exceeds 85% of the level set in parameter L3-02, the acceleration rate is reduced. The acceleration is stopped when the current exceeds L3-02. Acceleration continues when the current falls below L3-02. The Stall Prevention level is automatically reduced in the field weakening area. Refer to L3-03: Stall Prevention Limit During Acceleration on page 223.
5.8 L: Protection Functions
Parameter Details
L2-07 — KEB Acceleration Time — PDF page 221
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-07 | KEB Acceleration Time | 0.0 to 25.5 s | 0.0 s |
L2-08 — Minimum Frequency Gain at KEB Start — PDF page 221
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-08 | Minimum Frequency Gain at KEB Start | 0 to 300% | 100% |
L2-11 — Desired DC Bus Voltage during KEB — PDF page 221
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L2-11 | Desired DC Bus Voltage during KEB | 150 to 400 V <1> | E1-01 x 1.22 |
L3-01 — Stall Prevention Selection during Acceleration — PDF page 221
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-01 | Stall Prevention Selection during Acceleration | 0 to 2 <1> | 1 |
Manual — Induction and PM acceleration stall behavior — page 222
Source reference: SIEP C71060618F, December 2016, physical PDF page 222. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output current; Stall Prevention Level During Acceleration L3-02 andL3-02−15%; Time. Output frequency pauses while current above threshold; Controls the output frequency to prevent the motor from stalling. Qualitative waveform; no unprinted timing inferred. Exact source geometry, routing and unprinted numerical values remain original-only.
Output current; L3-02; 15% ofL3-02; Time. Output frequency; 100 ms before deceleration and 100 ms before reacceleration; Deceleration usingL3-22. Source PM operation conditions andL3-01=1 retained. Exact source geometry, routing and unprinted numerical values remain original-only.
Figure 5.81 Stall Prevention During Acceleration for Induction Motors
• Open Loop Vector Control for PM: Acceleration is stopped when the output current reaches the level set in parameter L3-02, and after 100 ms the drive decelerates using the deceleration time set in parameter L3-22 (Refer to L3-22: Deceleration Time at Stall Prevention During Acceleration on page 223). When the current falls below 85% of L3-02, deceleration is stopped. The drive will attempt to reaccelerate again after 100 ms.
Figure 5.82 Stall Prevention During Acceleration for Permanent Magnet Motors
Setting 2: Intelligent Stall Prevention When L3-01 = 2, the drive will disregard the selected acceleration time and try to accelerate in the minimum time. The acceleration rate is adjusted so that the current does not exceed the value set in parameter L3-02.
n L3-02: Stall Prevention Level During Acceleration
Sets the output current level at which the Stall Prevention during acceleration is activated.
No. Name Setting Range Default
<1> The upper limit and default value is determined by the duty rating and the carrier frequency derating selection (C6-01 and L8-38 respectively).
• If stalling occurs with L3-02 set to its default value when using a motor that is relatively small compared to the drive, try lowering L3-02. • When operating the motor in the constant power range, also set parameter L3-03.
5.8 L: Protection Functions
L3-02 — Stall Prevention Level during Acceleration — PDF page 222
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-02 | Stall Prevention Level during Acceleration | 0 to 150% <1> | <1> |
Manual — Deceleration stall limits and voltage levels — page 223
Source reference: SIEP C71060618F, December 2016, physical PDF page 223. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Stall Prevention level during Acceleration; L3-02 upper level, L3-03 lower limit; E1-06 Base frequency; Output frequency. Solid declining curve bounded by lower limit and dashed extension; no unprinted curve values. Exact source geometry, routing and unprinted numerical values remain original-only.
n L3-03: Stall Prevention Limit During Acceleration
The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets the lower limit for this reduction as a percentage of the drive rated current.
No. Name Setting Range Default
Figure 5.83 Stall Prevention Level and Limit During Acceleration
n L3-22: Deceleration Time at Stall Prevention During Acceleration
Sets the brief deceleration time used when stalling occurs while accelerating a PM motor. When set to 0, this function is disabled and the drive will decelerate at the selected deceleration time when stalling occurs. The function is effective only in Open Loop Vector Control for PM motors and if parameter L3-01 is set to 1.
n L3-04: Stall Prevention Selection during Deceleration
Stall Prevention during deceleration can control the deceleration based on the DC bus voltage and prevent an overvoltage fault caused by high inertia or rapid deceleration. Selects the Stall Prevention method during deceleration.
<1> Settings 3 and 4 are not available in OLV/PM control mode. <2> Setting 7 is available in drive software versions PRG: 1020 and later.
Setting 0: Disabled When this setting is used, the drive decelerates according to the set deceleration time. With high inertia loads or rapid deceleration, an overvoltage (ov) fault may occur. In this case use braking options or switch to another L3-04 selection.
Note: Use this setting or set L3-04 to 3 whenever a Dynamic Braking Resistor or another braking option is used.
Setting 1: General Purpose Stall Prevention With this setting the drive tries to decelerate in the set deceleration time. When the DC bus voltage exceeds the Stall Prevention level, the drive pauses deceleration. Deceleration continues as soon as the DC bus voltage drops below that level. Stall Prevention may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall Prevention depends on the input voltage setting E1-01.
Drive Input Voltage Stall Prevention Level during Deceleration
Note: 1. This setting should not be used in combination with a Dynamic Braking Resistor or other braking options. If Stall Prevention during deceleration is enabled, it will be triggered before the braking resistor option can operate.
5.8 L: Protection Functions
Parameter Details
200 V Class | 200 V Class
400 V Class | E1-01 ≥ 400 V
400 V Class | E1-01 < 400 V
L3-03 — Stall Prevention Limit during Acceleration — PDF page 223
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-03 | Stall Prevention Limit during Acceleration | 0 to 100% | 50% |
L3-22 — Deceleration Time at Stall Prevention During Acceleration — PDF page 223
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-22 | Deceleration Time at Stall Prevention During Acceleration | 0 to 6000.0 s | 0.0 s |
L3-04 — Stall Prevention Selection During Deceleration Selection — PDF page 223
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-04 | Stall Prevention Selection During Deceleration Selection | 0 to 4; 7 <1> <2> | 1 |
Stall prevention during deceleration by input voltage — PDF page 223
| Source row | Drive Input Voltage class | E1-01 condition (merged 200 V cell retained) | Stall Prevention Level during Deceleration |
|---|---|---|---|
| 1 | 200 V Class | 200 V Class | Vdc = 380 V |
| 2 | 400 V Class | E1-01 ≥ 400 V | Vdc = 760 V |
| 3 | 400 V Class | E1-01 < 400 V | Vdc = 660 V |
Manual — Intelligent deceleration and run stall prevention — page 224
Source reference: SIEP C71060618F, December 2016, physical PDF page 224. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output Frequency; Time; specified deceleration time; stair-step Deceleration characteristics when Stall Prevention was triggered during deceleration, compared with dashed direct ramp. No numeric time inferred. Exact source geometry, routing and unprinted numerical values remain original-only.
- This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider using a braking option. Figure 5.84 illustrates the function of Stall Prevention during deceleration.
Figure 5.84 Stall Prevention During Deceleration
Setting 2: Intelligent Stall Prevention With this setting the drive adjusts the deceleration rate so that the DC bus voltage is kept at the level set in parameter L3-17. This way the shortest possible deceleration time is achieved while the motor is protected from stalling. The deceleration time that has been selected is disregarded, but the achievable deceleration time cannot be smaller than 1/10 of the set deceleration time. This function uses the following parameters for adjusting the deceleration rate: • DC bus voltage gain L3-20 • Deceleration rate calculations gain L3-21 • Inertia calculations for motor acceleration time L3-24 • Load inertia ratio L3-25 Refer to these parameter descriptions for details.
Note: As the deceleration time is not constant, Intelligent Stall Prevention should not be used in applications where stopping accuracy is a concern. Use braking options instead.
Setting 3: Stall Prevention with Braking Option Enables the Stall Prevention function while using a braking resistor. Use this setting if overvoltage occurs with L3-04 disabled when using a braking resistor. This makes it possible to reduce the deceleration time.
Setting 4: Overexcitation Deceleration Enables overexcitation deceleration. Overexcitation Deceleration (increasing the motor flux) shortens the deceleration time compared to deceleration with no Stall Prevention (L3-04 = 0). Repetitive or long overexcitation deceleration can result in motor overheat. In such situations, either shorten the deceleration time setting or use a braking resistor option. Use parameters n3-13 and n3-23 for fine-tuning this function.
Note: Because the allowable flux level for overexcitation varies based on the flux saturation characteristics of the motor, set the proper overexcitation level by adjusting the excitation gain in parameter n3-13. Motor characteristics and inertia of the machine influence the deceleration time during overexcitation deceleration.
Setting 7: Overexcitation Deceleration 3 Provides faster deceleration than normal Overexcitation Deceleration (L3-04 = 4) by increasing the amount of overexcitation current applied to the motor.
Note: When operation permits, use normal Overexcitation Deceleration (L3-04 = 4).
n L3-05: Stall Prevention Selection During Run
Stall Prevention During Run can prevent a motor from stalling by automatically reducing the speed when a transient overload occurs while the motor is running at constant speed. This parameter selects the Stall Prevention During Run method.
No. Name Setting Range Default
Note: 1. This function is not available in Open Loop Vector Control. Use the torque limit function instead. 2. When output frequency is 6 Hz or less, Stall Prevention During Run is disabled regardless of the setting in L3-05/06.
5.8 L: Protection Functions
L3-05 — Stall Prevention Selection During Run — PDF page 224
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-05 | Stall Prevention Selection During Run | 0 to 2 | 1 |
Manual — Run stall settings and overvoltage suppression — page 225
Source reference: SIEP C71060618F, December 2016, physical PDF page 225. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 0: Disabled Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an oC or oL fault.
Setting 1: Decelerate Using C1-02 If the current exceeds the Stall Prevention level set in parameter L3-06, the drive decelerates at Decel Time 1 (C1-02). Once the current level drops below the value of L3-06 minus 2% for 100 ms it accelerates back to the frequency reference at the active acceleration time.
Setting 2: Decelerate Using C1-04 Same as setting 1 except the drive decelerates at decel time 2 (C1-04).
n L3-06: Stall Prevention Level During Run
Sets the current level for Stall Prevention During Run. Depending on the setting of parameter L3-23 the level is automatically reduced in the constant power range (speed beyond base speed).
No. Name Setting Range Default
<1> The upper limit and default value for this setting are determined by C6-01, Drive Duty Selection, and L8-38, Carrier Frequency Reduction Selection.
n L3-23: Automatic Stall Prevention Level Reduction
This function reduces the Stall Prevention during run level in the constant power range.
Setting 0: Disabled The level set in L3-06 is used throughout the entire speed range.
Setting 1: Enabled The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.
n Overvoltage Suppression Function
This function suppresses overvoltage faults by slightly increasing the output frequency when the DC bus voltage rises. It can be used to drive loads with cyclic regenerative operation, such as punch presses or other applications that involve repetitive crank movements. The output frequency is adjusted during ov suppression so that the DC bus voltage does not exceed the level set in parameter L3-17. In addition to the parameters explained below, ov suppression also uses these settings for frequency adjustment: • DC bus voltage gain L3-20 • Deceleration rate calculations gain L3-21 • Inertia calculations for motor acceleration time L3-24 • Load inertia ratio L3-25 Note: 1. The motor speed will exceed the frequency reference when overvoltage suppression is triggered. Consequently, overvoltage suppression is not appropriate in applications that require a perfect match between the frequency reference and the actual motor speed. 2. Disable overvoltage suppression when using a braking resistor. 3. Overvoltage may still occur if there is a sudden increase to a regenerative load. 4. This function is enabled only when operating just below the maximum frequency. Overvoltage suppression does not increase the output frequency beyond the maximum frequency. If this is required by the application increase the maximum frequency and change the base frequency setting.
n L3-11: Overvoltage Suppression Function Selection
Enables or disables the overvoltage suppression function.
Setting 0: Disabled The output frequency is not adjusted. A regenerative load may trip the drive with an overvoltage fault. Use this setting if braking options are installed.
5.8 L: Protection Functions
Parameter Details
Run
L3-06 — Stall Prevention Level During Run — PDF page 225
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-06 | Stall Prevention Level During Run | 30 to 150 <1> | <1> |
L3-23 — Automatic Reduction Function Selection for Stall Prevention during — PDF page 225
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-23 | Automatic Reduction Function Selection for Stall Prevention during Run | 0 or 1 | 0 |
L3-11 — ov Suppression Function Selection — PDF page 225
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-11 | ov Suppression Function Selection | 0 or 1 | 0 |
Manual — Suppression voltage and inertia gains — page 226
Source reference: SIEP C71060618F, December 2016, physical PDF page 226. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 1: Enabled When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by increasing the output frequency.
n L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention
Sets the target DC bus voltage target level used by the overvoltage suppression function (L3-11 = 1) and Intelligent Stall Prevention during deceleration (L3-04 = 2).
No. Name Setting Range Default
<1> Values are for 200 V class drives and must be doubled for 400 V class drives. <2> This value is initialized when E1-01 is changed.
n L3-20: DC Bus Voltage Adjustment Gain
Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Kinetic Energy Backup 2, and Intelligent Stall Prevention during deceleration (L3-04 = 2) in order to control the DC bus voltage.
Adjustment for KEB 2 and Intelligent Stall Prevention During Deceleration • Increase this setting slowly in steps of 0.1 if overvoltage (ov) or undervoltage (Uv1) occurs at the beginning of deceleration while KEB Ride-Thru 2 is enabled or Intelligent Stall Prevention during deceleration is activated. • If this setting is too high, then a fair amount of speed or torque ripple can result.
Adjustment for Overvoltage Suppression • Increase this setting slowly in steps of 0.1 if overvoltage suppression is enabled (L3-11 = 1) and a sudden increase in a regenerative load results in an overvoltage (ov) fault. • If this setting is too high, excessive speed or torque ripple can result.
n L3-21: Accel/Decel Rate Calculation Gain
Determines the proportional gain used by overvoltage suppression (L3-11 = 1), Kinetic Energy Backup 2, and Intelligent Stall Prevention during deceleration (L3-04 = 2) in order to calculate acceleration and deceleration rates.
<1> This value is reset to its default value when the control mode is changed (A1-02). The value shown here is for Open Loop Vector Control.
Adjustment for KEB 2 and Intelligent Stall Prevention During Deceleration • Reduce the setting in steps of 0.05 if there is a fairly large speed or current ripple during KEB Ride-Thru 2 or when using Intelligent Stall Prevention during deceleration. • Small reductions in the acceleration gain can also help solve problems with overvoltage and overcurrent. • Decreasing this setting too much can result in a slow DC bus voltage control response and may also lengthen deceleration times beyond optimal levels.
Adjustment for Overvoltage Suppression • Increase this setting in steps of 0.1 if overvoltage occurs as a result of a regenerative load when overvoltage suppression is enabled (L3-11 = 1). • If there is a fairly large speed ripple when overvoltage suppression is enabled, then decrease L3-21 in steps of 0.05.
n L3-24: Motor Acceleration Time for Inertia Calculations
Sets the time it takes to accelerate the motor from stop to the maximum speed at motor rated torque. This parameter should be set when using KEB Ride-Thru 2, Intelligent Stall Prevention during deceleration (L2-04 = 2), or the overvoltage suppression function (L3-11 = 1).
5.8 L: Protection Functions
Intelligent Stall Prevention During Deceleration
L3-17 — Target DC Bus Voltage for Overvoltage Suppression, and — PDF page 226
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-17 | Target DC Bus Voltage for Overvoltage Suppression, and Intelligent Stall Prevention During Deceleration | <1> 150 to 400 | <1> <2> 370 V |
L3-20 — DC Bus Voltage Adjustment Gain — PDF page 226
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-20 | DC Bus Voltage Adjustment Gain | 0.00 to 5.00 | 1.00 |
L3-21 — Accel/Decel Rate Calculation Gain — PDF page 226
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-21 | Accel/Decel Rate Calculation Gain | 0.00 to 200.00 | 1.00 <1> |
L3-24 — Motor Acceleration Time for Inertia Calculations — PDF page 226
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-24 | Motor Acceleration Time for Inertia Calculations | 0.001 to 10.000 | Determined by o2-04, E2-11, and <1> E5-01 |
Manual — Inertia calculations and speed detection — page 227
Source reference: SIEP C71060618F, December 2016, physical PDF page 227. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
L3-24 = (2 · π · J [kgm²] · n_rated [r/min]) / (60 · T_rated [Nm]). Source fraction transcribed as a parenthesized ratio; no computed value inferred. Exact geometry, routing and unprinted numerical values remain original-only.
T_rated [Nm] = (60 · P_Motor [kW] · 10³) / (2 · π · n_rated [r/min]). Source fraction transcribed as a parenthesized ratio. Exact geometry, routing and unprinted numerical values remain original-only.
L3-25 = Machine Inertia / Motor Inertia. No machine inertia inferred. Exact geometry, routing and unprinted numerical values remain original-only.
<1> Parameter L3-24 is defaulted for a Yaskawa standard 4-pole motor. During Auto-Tuning, L3-24 will be initialized to a Yaskawa standard 4-pole motor if parameter E2-11 is changed. This value also changes based on the motor code set to E5-01 when using the Open Loop Vector Control Mode for PM motors.
Calculations are made as follows:
The rated torque can be calculated as follows:
n L3-25: Load Inertia Ratio
Determines the ratio between the rotor inertia and the load. Set this parameter when using KEB Ride-Thru 2, Intelligent Stall Prevention during deceleration (L3-04 = 2), or the overvoltage suppression function (L3-11 = 1).
No. Name Setting Range Default
When set incorrectly, a fairly large current ripple can result during KEB Ride-Thru 2 and overvoltage suppression (L3-11 = 1) or other faults such as ov, Uv1, and oC may occur. Parameter L3-25 can be calculated by:
u L4: Speed Agree/Frequency Reference Loss Detection
These parameters set up the speed agree and speed detection functions which can be assigned to the multi-function output terminals.
n L4-01/02: Speed Agreement Detection Level and Detection Width
Parameter L4-01 sets the detection level for the digital output functions “Speed Agree 1”, “User Set Speed Agree 1”, “Frequency Detection 1”, and “Frequency Detection 2”. Parameter L4-02 sets the hysteresis level for these functions.
Refer to H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection on page 195, Settings 2, 3, 4, and 5.
n L4-03/04: Speed Agreement Detection Level and Detection Width (+/-)
Parameter L4-03 sets the detection level for the digital output functions “Speed Agree 2”, “User Set Speed Agree 2”, “Frequency Detection 3”, and “Frequency Detection 4”. Parameter L4-04 sets the hysteresis level for these functions.
Refer to H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection on page 195, Settings 13, 14, 15, and 16.
n L4-05: Frequency Reference Loss Detection Selection
The drive can detect a loss of an analog frequency reference from input A1 or A2. Reference loss is detected when the frequency reference value reduces for 90% within 400 ms.
5.8 L: Protection Functions
Parameter Details
L3-25 — Load Inertia Ratio — PDF page 227
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L3-25 | Load Inertia Ratio | 0.0 to 1000.0 | 1.0 |
L4-01 / L4-02 — Speed Agreement Detection Level — PDF page 227
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L4-01 | Speed Agreement Detection Level | 0.0 to 400.0 Hz | 0.0 Hz |
| 2 | L4-02 | Speed Agreement Detection Width | 0.0 to 20.0 Hz | 2.0 Hz |
L4-03 / L4-04 — Speed Agreement Detection Level (+/-) — PDF page 227
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L4-03 | Speed Agreement Detection Level (+/-) | 0.0 to 400.0 Hz | 0.0 Hz |
| 2 | L4-04 | Speed Agreement Detection Width (+/-) | 0.0 to 20.0 Hz | 2.0 Hz |
Manual — Reference-loss and speed agreement conditions — page 228
Source reference: SIEP C71060618F, December 2016, physical PDF page 228. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Analog frequency reference 100%,80%,10%; decline 400 ms; Loss of Reference output OFF/ON/OFF; time. Output shown ON after the reference reaches 10%, and OFF as the recovered reference rises above the 80% line. No unprinted timing inferred. Exact geometry, routing and unprinted numerical values remain original-only.
Figure 5.85 Loss of Reference Function
To have a fault output trigger when frequency reference loss occurs, set H2-01, H2-02, or H2-03 to “C”. Refer to Setting C: Frequency Reference Loss on page 199 for details on setting the output function. Parameter L4-05 selects the operation when a frequency reference loss is detected.
No. Name Setting Range Default
Setting 0: Stop The drive will stop the motor.
Setting 1: Continue Operation with Reduced Frequency Reference The drive will continue operation at the frequency reference value set in parameter L4-06. When the external frequency reference value is restored, the operation is continued with the frequency reference.
n L4-06: Frequency Reference at Reference Loss
Sets the frequency reference level the drive runs with when L4-05 = 1 and a reference loss was detected. The value is set as a percentage of the frequency reference before the loss was detected.
n L4-07: Speed Agreement Detection Selection
Determines when frequency detection is active using parameters L4-01 through L4-04.
Setting 0: No Detection During Baseblock
Setting 1: Detection Always Enabled
n L4-08: Speed Agreement Detection Conditions
Note: Parameter available in drive software versions PRG: 1016 and later. Determines whether soft-starter output or estimated motor speed constitutes a speed agreement situation.
Setting 0: Match Speed with the Soft-Starter Output
Setting 1: Match Frequency Reference and Motor Speed
Note: In V/f control the drive ignores the value set to L4-08 and refers to the soft-starter output to determine whether a speed agreement situation has been reached. The following functions are influenced by the speed agree condition: • Overtorque alarms oL3 and oL4 when parameters L6-01 or L6-04 are set to 1, 3, 5, or 7. • DriveWorksEZ functions that use speed agree output • The Up 2/Down 2 functions • Multi-Function Digital Output Settings
5.8 L: Protection Functions
L4-05 — Frequency Reference Loss Detection Selection — PDF page 228
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L4-05 | Frequency Reference Loss Detection Selection | 0 or 1 | 0 |
L4-06 — Frequency Reference at Reference Loss — PDF page 228
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L4-06 | Frequency Reference at Reference Loss | 0.0 to 100.0% | 80.0% |
L4-07 — Speed Agreement Detection Selection — PDF page 228
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L4-07 | Speed Agreement Detection Selection | 0, 1 | 0 |
L4-08 — Speed Agreement Detection Conditions — PDF page 228
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L4-08 | Speed Agreement Detection Conditions | 0, 1 | 0 |
Manual — Holding-brake conditions and status registers — page 229
Source reference: SIEP C71060618F, December 2016, physical PDF page 229. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output Frequency; L4-01;2.0 Hz(fixed) hysteresis; Time; Frequency Detection 2 ON/OFF. Rising waveform crosses L4-01; output releases at the lower hysteresis threshold. Source holding-brake conditions retained in table and prose. Exact geometry, routing and unprinted numerical values remain original-only.
Setting Value Function
• MEMOBUS/Modbus Monitor Data
Register No. Description
Drive Status 2
Drive Status (U1-12)
• U: Monitor
No. Name Description
n Notes on Drive Control for Holding Brake Applications
The frequency detection function is used for controlling the brake. When an external Baseblock command is present while a Run command is active, the frequency reference will be kept as long as the Run command is active. To avoid improper brake operation make sure that frequency detection is set so that the brake does not open during Baseblock (L4-07 = “0”, default).
Brake Open/Close Brake Activation Level Function Parameter Signal Parameter
<1> If the load slips during stop, make it greater than E1-09 or 2.0 Hz until the load no longer slips.
Figure 5.86 Frequency Detection 2
The braking sequence should be designed as follows: • A normally open signal (N.O.) should be used to control the brake so that it is released when terminal MA-MC closes. • An external circuit should be added to ensure the brake is fully applied in case of a fault or emergency condition. • An additional external circuit should also be added to ensure the brake releases properly when an Up/Down Command is entered. When changing the speed using an analog signal, make sure that the source of the frequency reference is assigned to the control circuit terminals (b1-01 = 1). A sequence to open and close the holding brake appears in the diagram below.
5.8 L: Protection Functions
Parameter Details
002CH | Bit 2
002CH | Bit 3
002CH | Bit 4
002CH | Bit 5
004BH | Bit 4
L4-08 affected digital output functions — PDF page 229
| Source row | Setting Value | Function |
|---|---|---|
| 1 | 2 | Frequency (Speed) Agree 1 |
| 2 | 3 | User-set Frequency (Speed) Agree 1 |
| 3 | 4 | Frequency (FOUT) Detection 1 |
| 4 | 5 | Frequency (FOUT) Detection 2 |
| 5 | 13 | Frequency (Speed) Agree 2 |
| 6 | 14 | User-set Frequency (Speed) Agree 2 |
| 7 | 15 | Frequency (FOUT) Detection 3 |
| 8 | 16 | Frequency (FOUT) Detection 4 |
U1-12 — Drive Status — PDF page 229
| Source row | No. | Name | Description |
|---|---|---|---|
| 1 | U1-12 | Drive Status | The fifth digit from the right side: During Speed Agree |
L4-08 MEMOBUS monitor bits — PDF page 229
| Source row | Register No. | Status bit | Description |
|---|---|---|---|
| 1 | 002CH | Bit 2 | Speed Agree, 1: During Agree |
| 2 | 002CH | Bit 3 | User-set Speed Agree, 1: During Agree |
| 3 | 002CH | Bit 4 | Frequency Detection 1, 1: Output Frequency ≤ L4-01 |
| 4 | 002CH | Bit 5 | Frequency Detection 2, 1: Output Frequency ≥ L4-01 |
| 5 | 004BH | Bit 4 | 1: During Speed Agree |
Holding brake frequency detection conditions — PDF page 229
| Source row | Brake function | Brake parameter | Activation signal | Activation parameter |
|---|---|---|---|---|
| 1 | Frequency Detection Conditions | L4-07 = 0 | Frequency Detection Level | <1> L4-01 = 2.0 to 3.0 Hz |
| 2 | Frequency Detection 2 | H2-01 = 5 | Frequency Detection Width | 2.0 Hz (fixed) |
Manual — Holding-brake timing and fault restart — page 230
Source reference: SIEP C71060618F, December 2016, physical PDF page 230. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
S1-SC UP OFF/ON; Output frequency 0; b6-02, b6-01, L4-01, d1-03, d1-01(Enabled when b1-01=0); b4-01 printed next to DC Injection braking. MA-MC Frequency Detection 2(H2-01=5) ON/OFF; Holding brake Closed/Open/Closed; Time. Parameter b4-01 retained literally, not substituted with a DC-braking parameter. Exact geometry, routing and unprinted numerical values remain original-only.
Figure 5.87 Holding Brake Time Chart
u L5: Fault Restart
The drive can be set up to perform a self-diagnostic check and resume the operation after a fault has occurred. If the self-check is successful and the cause of the fault has disappeared, the drive restarts by performing Speed Search (Refer to b3: Speed Search on page 130 for details). The drive can attempt to restart itself following the faults listed below.
Table 5.30 Restart Faults
Setting Function
<1> When L2-01 is set to 1 or 2 (continue operation during momentary power loss)
Use parameters L5-01 to L5-05 to set up automatic fault restart. To output a signal during fault restart, set H2-01, H2-02, or H2-03 to 1E. Do not use the fault restart function in elevator applications.
n L5-01: Number of Auto Restart Attempts
Sets the number of times that the drive may attempt to restart itself.
No. Name Setting Range Default
The method of incrementing the restart counter is determined by the setting of parameter L5-05. When the counter reaches the number set in L5-01 the operation stops and the fault has to be reset manually after correcting the cause. The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter reaches the number set in L5-01 the operation stops and the fault has to be reset manually after correcting the cause. The number of fault restarts is reset back to zero when: • The drive operates normally for ten minutes following a fault restart. • A fault is cleared manually after protective functions are triggered. • The power supply is cycled.
n L5-02: Auto Restart Fault Output Operation Selection
Selects if the fault output (H2-01/02/03 = E) is set when the drive attempts to restart.
5.8 L: Protection Functions
Table5.30 Restart Faults left — PDF page 230
| Source row | Setting | Function |
|---|---|---|
| 1 | GF | (Ground Fault) |
| 2 | LF | (Output Open Phase) |
| 3 | oC | (Overcurrent) |
| 4 | oH1 | (Drive Overheat) |
| 5 | oL1 | (Motor Overload) |
| 6 | oL2 | (Drive Overload) |
| 7 | oL3 | (Overtorque 1) |
| 8 | oL4 | (Overtorque 2) |
Table5.30 Restart Faults right — PDF page 230
| Source row | Setting | Function |
|---|---|---|
| 1 | ov | (DC Bus Overvoltage) |
| 2 | PF | (Input Phase Loss) |
| 3 | rH | (Braking Resistor Fault) |
| 4 | rr | (Braking Transistor Fault) |
| 5 | STo | (Step Out Detection) |
| 6 | Uv1 | (DC Bus Undervoltage) <1> |
L5-01 — Number of Auto Restarts — PDF page 230
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L5-01 | Number of Auto Restarts | 0 to 10 | 0 |
L5-02 — Auto Restart Fault Output Operation Selection — PDF page 230
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L5-02 | Auto Restart Fault Output Operation Selection | 0 or 1 | 0 |
Manual — Fault restart counter and torque detection — page 231
Source reference: SIEP C71060618F, December 2016, physical PDF page 231. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Motor current/torque; threshold L6-02/05;10% hysteresis; L6-03/06 delay at both rising crossings; Torque detection 1(NO) / Torque detection 2(NO) ON pulses. No current or torque values inferred beyond source labels. Exact geometry, routing and unprinted numerical values remain original-only.
Setting 0: No Fault Output
Setting 1: Fault Output is Set
n L5-04: Fault Reset Interval Time
Determines the amount of time to wait between attempts to restart the drive when parameter L5-05 is set to 1.
No. Name Setting Range Default
n L5-05: Fault Reset Operation Selection
Setting 0: Count Successful Restarts The drive will continuously attempt to restart. If a restart trial is successful, the restart counter is increased. This operation is repeated each time a fault occurs until the counter reaches the value set in L5-01.
Setting 1: Count Restart Attempts The drive will try to restart using the time interval set in parameter L5-04. Each attempt is counted, whether it was successful or not.
u L6: Torque Detection
The drive provides two independent torque detection functions that trigger an alarm or fault signal when the load is too heavy (oL), or suddenly drops (UL). They are set up using the L6-□□ parameters. To indicate the underload or overload condition to an external device, digital outputs should be programmed as shown below.
H2-01 /02/03 Setting Description
Figure 5.88 and Figure 5.89 show the function of overtorque and undertorque detection.
Figure 5.88 Overtorque Detection Operation
5.8 L: Protection Functions
Parameter Details
L5-04 — Fault Reset Interval Time — PDF page 231
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L5-04 | Fault Reset Interval Time | 0.5 to 600.0 s | 10.0 s |
L5-05 — Fault Reset Operation Selection — PDF page 231
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L5-05 | Fault Reset Operation Selection | 0 or 1 | 0 |
Torque detection output N.O./N.C. assignments — PDF page 231
| Source row | H2-01 /02/03 Setting | Description |
|---|---|---|
| 1 | B | Torque detection 1, N.O. (output close when over-/underload is detected) |
| 2 | 17 | Torque detection 1, N.C. (output opens when over-/underload is detected) |
| 3 | 18 | Torque detection 2, N.O. (output close when over-/underload is detected) |
| 4 | 19 | Torque detection 2, N.C. (output opens when over-/underload is detected) |
Manual — Torque detection modes and fault codes — page 232
Source reference: SIEP C71060618F, December 2016, physical PDF page 232. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Motor current/torque; threshold L6-02/05;10% hysteresis; L6-03/06 delay at both downward crossings; Torque detection 1(NO) or Torque detection 2(NO) ON pulses. No unprinted threshold inferred. Exact geometry, routing and unprinted numerical values remain original-only.
Figure 5.89 Undertorque Detection Operation
Note: 1. The torque detection function uses a hysteresis of 10% of the drive rated output current/motor rated torque. 2. In V/f Control and Open Loop Vector Control for PM, the level is set as a percentage of the drive rated output current. In Open Loop Vector, it is set as a percentage of the motor rated torque.
Note: When overtorque occurs in the application, the drive may stop due to overcurrent (oC) or overload (oL1). To prevent this, an overload situation should be indicated to the controller before oC or oL1 occur in the drive. Use the torque detection for this purpose. Use undertorque detection to discover application problems like a torn belt, a pump shutting off, or other similar trouble.
n L6-01/L6-04: Torque Detection Selection 1/2
The torque detection function is triggered when the current/torque exceeds the levels set in parameter L6-02/L6-05 for longer than the time set in L6-03L6-/06. The parameters L6-01/L6-04 select the detection condition and the operation at detection.
No. Name Setting Range Default
Setting 0: Disabled
Setting 1: oL3/oL4 at Speed Agree - Alarm Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation continues after detection and an oL3/oL4 alarm is triggered.
Setting 2: oL3/oL4 at Run - Alarm Overtorque detection works whenever a Run command is active. The operation continues after detection and an oL3/oL4 alarm is triggered.
Setting 3: oL3/oL4 at Speed Agree - Fault Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation is stopped and an oL3/oL4 fault is triggered.
Setting 4: oL3/oL4 at Run - Fault Overtorque detection works whenever a Run command is active. The operation is stopped and an oL3/oL4 fault is triggered.
Setting 5: UL3/UL4 at Speed Agree - Alarm Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation continues after detection and a UL3/UL4 alarm is triggered.
Setting 6: oL5/UL5 at Run - Alarm Undertorque detection works whenever a Run command is active. The operation continues after detection and an oL5/UL5 alarm is triggered.
Setting 7: UL5 at Speed Agree - Fault Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during acceleration and deceleration. The operation is stopped and a UL5 fault is triggered.
Setting 8: oL3/oL4 at Run - Fault Undertorque detection works whenever a Run command is active. The operation is stopped and an oL3/oL4 fault is triggered.
n L6-02/L6-05: Torque Detection Level 1/2
These parameters the detection levels for the torque detection functions 1 and 2.
5.8 L: Protection Functions
L6-01/ L6-04 — Torque Detection Selection 1/2 — PDF page 232
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L6-01/ L6-04 | Torque Detection Selection 1/2 | 0 to 8 | 0 |
Manual — Torque levels and mechanical weakening — page 233
Source reference: SIEP C71060618F, December 2016, physical PDF page 233. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
Note: 1. The torque detection level 1 (L6-02) can also be supplied by an analog input set to H3-02/10 = 7. In this case the analog value has priority and the setting L6-02 is disregarded. Torque detection level 2 (L6-05) cannot be set by an analog input. 2. The detection levels for overtorque and undertorque are set as a percentage of the drive rated current when using V/f Control or Open Loop Vector Control. When using Closed Loop Vector Control, the drive sets torque detection as a percentage of the motor rated current.
n L6-03/L6-06: Torque Detection Time 1/2
These parameters set the time that the levels set in L6-02/05 have to be exceeded before an alarm/fault is triggered.
n Mechanical Weakening Detection
This function can be used to detect mechanical weakening of a machine that leads to overtorque or undertorque situations after a certain machine operation time has elapsed. The function is activated in the drive when the cumulative operation counter U4-01 exceeds the time set in parameter L6-11. Mechanical weakening detection uses the torque detection 1 settings (L6-01/02/03) and triggers an oL5 fault when overtorque or undertorque occurs in the speed range determined by parameter L6-08/09. The oL5 operation is set by parameter L6-08. To output a signal for mechanical weakening detection, set H2-01, H2-02, or H2-03 to 22.
n L6-08: Mechanical Weakening Detection Operation
Decides which speed range the function is active and sets the mechanical weakening detection operation.
Setting 0: Disabled
Setting 1: Continue Running if the Speed is Greater than L6-09 (signed) - Alarm Detection when the speed is above L6-09 (signed). Upon detection the operation is continued but an oL5 alarm is output.
Setting 2: Continue Running if the Speed is Greater than L6-09 - Alarm Detection when the speed is above L6-09 (unsigned). Upon detection the operation is continued but an oL5 alarm is output.
Setting 3: Stop when Motor Speed is Greater than L6-09 (signed) Detection when the speed is above L6-09 (signed). Upon detection the operation is stopped and an oL5 fault is output.
Setting 4: Stop when Motor Speed is Greater than L6-09 Detection when the speed is above L6-09 (unsigned). Upon detection the operation is stopped and an fault is output.
Setting 5: Continue Running if the Speed is less than L6-09 (signed) - Alarm Detection when the speed is below L6-09 (signed). Upon detection the operation is continued but an oL5 alarm is output.
Setting 6: Continue Running if the Speed is less than L6-09 - Alarm Detection when the speed is below L6-09 (unsigned). Upon detection the operation is continued but an oL5 alarm is output.
Setting 7: Stop when Motor Speed is less than L6-09 (signed) Detection when the speed is below L6-09 (signed). Upon detection the operation is stopped and an oL5 fault is output.
Setting 8: Stop when Motor Speed is less than L6-09 Detection when the speed is below L6-09 (unsigned). Upon detection the operation is stopped and an oL5 fault is output.
n L6-09: Mechanical Weakening Detection Speed Level
Sets the speed level that defines the speed range for mechanical weakening detection.
5.8 L: Protection Functions
Parameter Details
L6-02 / L6-05 — Torque Detection Level 1 — PDF page 233
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L6-02 | Torque Detection Level 1 | 0 to 300% | 150% |
| 2 | L6-05 | Torque Detection Level 2 | 0 to 300% | 150% |
L6-03 / L6-06 — Torque Detection Time 1 — PDF page 233
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L6-03 | Torque Detection Time 1 | 0.0 to 10.0 s | 0.1 s |
| 2 | L6-06 | Torque Detection Time 2 | 0.0 to 10.0 s | 0.1 s |
L6-08 — Mechanical Weakening Detection — PDF page 233
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L6-08 | Mechanical Weakening Detection | 0 to 8 | 0 |
L6-09 — Mechanical Weakening Detection Speed Level — PDF page 233
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L6-09 | Mechanical Weakening Detection Speed Level | -110.0 to 110.0% | 110% |
Manual — Torque limits and control methods — page 234
Source reference: SIEP C71060618F, December 2016, physical PDF page 234. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
The value is set as a percentage of the maximum frequency. If L6-08 is set for unsigned speed detection (L6-08 = 2, 4, 6, 8) then the absolute value of L6-09 is used, i.e., negative settings will be treated as positive.
n L6-10: Mechanical Weakening Detection Time
Sets the time permitted for the situation selected in parameter L6-08 to arise before mechanical weakening is detected.
No. Name Setting Range Default
n L6-11: Mechanical Weakening Detection Start Time
Sets the drives cumulative operation time at which mechanical weakening detection is activated. If U4-01 reaches the L6-11 value, the function is activated.
u L7: Torque Limit
The torque limit function can be used to limit the torque in each of the four quadrants individually and thereby protect the machinery. It can be used in the Open Loop Vector Control mode. A digital output programmed for “During Torque Limit” (H2-01/02/03 = 30) can be switched when the drive is operating at the torque limit.
n L7-01/02/03/04: Torque Limits
These parameters set the torque limits in each operation mode.
Note: If the multi-function analog input is programmed for “10: Positive Torque Limit”, “11: Negative Torque Limit”, “12: Regenerative Torque Limit”, or “15: General Torque Limit”, the drive uses the lower value of either L7-01 through L7-04, or analog input torque limit. Refer to Setting 10/11/12/15: Positive/Negative/Regenerative/General Torque Limit (OLV only) on page 209 for details on using analog torque limits.
n L7-06: Torque Limit Integral Time Constant
Sets the integral time constant for the torque limit function.
n L7-07: Torque Limit Control Method Selection during Accel/Decel
Selects the function of torque limit during acceleration and deceleration.
Setting 0: Proportional Control The torque limit function works with P-control during acceleration and deceleration and switches to I-control at constant speed. Use this setting when acceleration or deceleration to the desired speed has priority over torque limitation during speed changes.
Setting 1: Integral Control The torque limit function always uses I-control. Use this setting when high accuracy torque limitation is required even during speed changes. Using this function may increase the acceleration time, or may prevent the motor speed from reaching the frequency reference when the torque limit is reached before.
u L8: Hardware Protection
5.8 L: Protection Functions
Deceleration
L6-10 — Mechanical Weakening Detection Time — PDF page 234
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L6-10 | Mechanical Weakening Detection Time | 0.0 to 10.0 s | 0.1 s |
L6-11 — Mechanical Weakening Detection Start Time — PDF page 234
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L6-11 | Mechanical Weakening Detection Start Time | 0 to 65535 h | 0 h |
L7-01 / L7-02 / L7-03 / L7-04 — Forward Torque Limit — PDF page 234
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L7-01 | Forward Torque Limit | 0 to 300% | 200% |
| 2 | L7-02 | Reverse Torque Limit | 0 to 300% | 200% |
| 3 | L7-03 | Forward Regenerative Torque Limit | 0 to 300% | 200% |
| 4 | L7-04 | Reverse Regenerative Torque Limit | 0 to 300% | 200% |
L7-06 — Torque Limit Integral Time Constant — PDF page 234
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L7-06 | Torque Limit Integral Time Constant | 5 to 10000 ms | 200 ms |
L7-07 — Torque Limit Control Method Selection during Acceleration/ — PDF page 234
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L7-07 | Torque Limit Control Method Selection during Acceleration/ Deceleration | 0 or 1 | 0 |
Manual — Braking resistor and overheat protection — page 235
Source reference: SIEP C71060618F, December 2016, physical PDF page 235. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n L8-01: Internal Dynamic Braking Resistor Protection Selection (ERF type)
This parameter selects the dynamic braking resistor protection when using an optional heatsink mounted braking resistor (ERF type, 3% ED).
No. Name Setting Range Default
Setting 0: Disabled Disables the braking resistor protection. Use this setting for any braking option other than the Yaskawa ERF Type resistor.
Setting 1: Enabled Enables the protection for ERF type resistors.
n L8-02: Overheat Alarm Level
Sets the overheat alarm (oH) detection level. The drive will output an alarm when the heatsink temperature exceeds the alarm level set in parameter L8-02. If the temperature reaches the overheat fault level, the drive will trigger an oH1 fault and stop operation. When an output terminal is set for the oH pre-alarm (H2-01/02/03 = 20), the switch will close when the heatsink temperature rises above L8-02.
n L8-03: Overheat Pre-Alarm Operation Selection
Sets the operation when an overheat pre-alarm is detected.
Setting 0: Ramp to Stop If an overheat alarm occurs, the drive decelerates to stop using the selected deceleration time. If a digital output is programmed for “fault” (H2-01/02/03 = E), this output will be triggered.
Setting 1: Coast to Stop If an overheat alarm occurs, the drive switches off the output and the motor coasts to stop. If a digital output is programmed for “fault” (H2-01/02/03 = E), this output will be triggered.
Setting 2: Fast-stop If an overheat alarm occurs, the drive decelerates to stop using the Fast-stop time (C1-09). If a digital output is programmed for “fault” (H2-01/02/03 = E), this output will be triggered.
Setting 3: Alarm Only If an overheat alarm occurs, an alarm is output and the drive continues operation.
Setting 4: Operation with Reduced Speed If an overheat alarm occurs, the operation is continued but the speed is reduced to the level set in parameter L8-19. If after 10 s the oH alarm is still present, the speed is reduced once more. The amount of reduction depends on how often the alarm repeats. If the oH alarm disappears while the drive is operating at a reduced speed, then the drive will switch back to the previous speed it was reduced to before. Figure 5.90 explains the operation with reduced speed during an oH alarm. A digital output programmed for 4D is switched when the oH alarm is still active after ten reduction cycles.
5.8 L: Protection Functions
Parameter Details
L8-01 — Internal Braking Resistor Protection — PDF page 235
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-01 | Internal Braking Resistor Protection | 0 or 1 | 0 |
L8-02 — Overheat Alarm Level — PDF page 235
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-02 | Overheat Alarm Level | 50 to 130 °C | Depending on size |
L8-03 — Overheat Pre-Alarm Operation — PDF page 235
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-03 | Overheat Pre-Alarm Operation | 0 to 4 | 3 |
Manual — Overheat reduction and phase-loss detection — page 236
Source reference: SIEP C71060618F, December 2016, physical PDF page 236. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Output frequency; f_ref; f_ref ×(L8-19), f_ref ×(L8-19)², f_ref ×(L8-19)³, f_ref ×(L8-19)⁴;10 s intervals; oH Alarm; Reset oH Alarm; oH Alarm number 1,2,3,4,5,6,...10; Time; Digital output(4D). Frequency is reduced with successive alarms;4D rises at the tenth depicted cycle. No unprinted values calculated. Exact geometry, routing and unprinted numerical values remain original-only.
Figure 5.90 Output Frequency Reduction During Overheat Alarm
n L8-19: Frequency Reduction Rate During Overheat Pre-Alarm
Specifies how much the output frequency is reduced when L8-03 is set to 4 and an oH alarm is present. Set as a factor of the maximum output frequency.
No. Name Setting Range Default
n L8-05: Input Phase Loss Protection Selection
Enables or disables the input phase loss detection.
Setting 0: Disabled
Setting 1: Enabled Enables the input phase loss detection. As detection is performed by measuring the DC bus ripple, a phase loss fault (PF) can also be triggered by power supply voltage imbalance or main circuit capacitor deterioration. Detection is disabled when: • The drive is decelerating. • No Run command is active. • Output current is less than or equal to 30% of the drive rated current.
n L8-07: Output Phase Loss Protection Selection
Enables or disables the output phase loss detection, which is triggered when the output current falls below 5% of the drive rated current.
Note: Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable this parameter in such cases.
Setting 1: Fault when One Phase is Lost An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.
5.8 L: Protection Functions
L8-19 — Frequency Reduction Rate During oH Pre-Alarm — PDF page 236
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-19 | Frequency Reduction Rate During oH Pre-Alarm | 0.1 to 0.9 | 0.8 |
L8-05 — Input Phase Loss Detection Selection — PDF page 236
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-05 | Input Phase Loss Detection Selection | 0 or 1 | 1 |
L8-07 — Output Phase Loss Protection Selection — PDF page 236
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-07 | Output Phase Loss Protection Selection | 0 to 2 | 1 |
Manual — Fan, ambient and low-speed protection — page 237
Source reference: SIEP C71060618F, December 2016, physical PDF page 237. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 2: Fault when Two Phases are Lost An output phase loss fault (LF) is triggered when two output phases are lost. The output shuts off and the motor coasts to stop.
n L8-09: Output Ground Fault Detection Selection
Enables or disables the output ground fault detection.
No. Name Setting Range Default
Setting 0: Disabled Ground faults are not detected.
Setting 1: Enabled A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.
n L8-10: Heatsink Cooling Fan Operation Selection
Selects the heatsink cooling fan operation.
Setting 0: Run with Timer The fan is switched on when a Run command is active. It is switched off with the delay set in parameter L8-11 after the Run command has been released. Using this setting extends the fan lifetime.
Setting 1: Run always The fan runs whenever power is supplied to the drive.
n L8-11: Heatsink Cooling Fan Off Delay Time
Sets the cooling fan switch off delay time if parameter L8-10 is set to 0.
n L8-12: Ambient Temperature Setting
If the temperature where the drive is mounted is above the specified values, the drive rated current must be reduced for optimal performance life. By setting the ambient temperature to parameter L8-12 and adjusting the installation method setting in L8-35, the drive rating automatically adapts to safe values.
n L8-15: oL2 Characteristics Selection at Low Speeds
Selects whether the drive overload capability (oL fault detection level) is reduced at low speeds in order to prevent premature output transistor failures.
Setting 0: Disabled The overload protection level is not reduced. Frequently operating the drive with high output current at low speed can lead to premature drive faults.
Setting 1: Enabled The overload protection level (oL2 fault detection level) is automatically reduced at speeds below 6 Hz.
5.8 L: Protection Functions
Parameter Details
L8-09 — Output Ground Fault Detection — PDF page 237
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-09 | Output Ground Fault Detection | 0 or 1 | 1 |
L8-10 — Fan Operation Selection — PDF page 237
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-10 | Fan Operation Selection | 0 or 1 | 0 |
L8-11 — Cooling Fan Switch Off Delay — PDF page 237
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-11 | Cooling Fan Switch Off Delay | 0 to 300 s | 60 s |
L8-12 — Ambient Temperature Setting — PDF page 237
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-12 | Ambient Temperature Setting | -10 to +50 °C | 40 °C |
L8-15 — oL2 Characteristics at Low Speed — PDF page 237
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-15 | oL2 Characteristics at Low Speed | 0 or 1 | 1 |
Manual — CLA, PM imbalance and installation — page 238
Source reference: SIEP C71060618F, December 2016, physical PDF page 238. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n L8-18: Software Current Limit Selection
The Software Current Limit (CLA) is a drive protection function that prevents output transistor failures caused by high current. Parameter L8-18 enables or disables this function.
Note: This setting should not be changed unless absolutely necessary. For proper drive protection and operation leave the Software CLA function enabled.
No. Name Setting Range Default
<1> Default setting is determined by drive software version and C6-02 setting. Drive software versions PRG: 1021 and later have a default setting of 0 when the carrier frequency is set for Leakage Current Rejection PWM (C6-02 = B), and 1 when C6-02 is set to any other value.
Setting 0: Disabled The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.
Setting 1: Enabled When the soft CLA current level is reached, the drive reduces the output voltage in order to reduce the current. If the current level drops below the Software CLA level, then normal operation will continue.
n L8-29: Current Unbalance Detection (PM OLV only)
Current unbalance can heat up a PM motor and lead to demagnetization of the magnets from heat. The current imbalance detection function prevents such motor damage by monitoring output currents and triggering a LF2 fault in case of current unbalance.
Setting 0: Disabled The drive does not protect the motor.
Setting 1: Enabled When an output current imbalance is detected, a LF2 fault is triggered, the output is switched off, and the motor coasts to stop.
n L8-35: Installation Method Selection
Selects the type of installation and changes the drive overload (oL2) limits accordingly.
Note: 1. This parameter is not reset when the drive is initialized. 2. The value is preset to the appropriate value when the drive is shipped. Change the value only when using Side-by-Side installation or when mounting a standard drive with the heatsink outside the cabinet.
Setting 0: IP20/IP00 Drive Must be selected if an IP20/IP00 drive is installed with a minimum of 30 mm space to the next drive or a cabinet wall.
Setting 1: Side-by-Side Mounting Must be selected if drives are Side-by-Side mounted with a minimum space of 2 mm.
Setting 2: NEMA Type 1 Drive Must be selected if the drive has a NEMA Type 1 enclosure or an IP20/Open-Chassis drive fitted with the NEMA Type 1 Kit option.
Setting 3: Finless Drive or External Heatsink Installation Must be selected for finless drives or if a standard drive is mounted with the heatsink outside the cabinet.
n L8-38: Carrier Frequency Reduction Selection
The drive can reduce the carrier frequency when the output current exceeds a certain level. This temporarily increases the overload capability (oL2 detection) and the drive can run through transient load peaks without tripping. L8-38 selects the operation of the carrier frequency reduction function.
Note: This function cannot be used in Open Loop Vector for PM motors.
5.8 L: Protection Functions
L8-18 — Software Current Limit Selection — PDF page 238
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-18 | Software Current Limit Selection | 0 or 1 | <1> |
L8-29 — Current Unbalance Detection (LF2) — PDF page 238
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-29 | Current Unbalance Detection (LF2) | 0 or 1 | 1 |
L8-35 — Installation Method Selection — PDF page 238
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-35 | Installation Method Selection | 0 to 3 | Determined by o2-04 |
Manual — Carrier reduction and step-out detection — page 239
Source reference: SIEP C71060618F, December 2016, physical PDF page 239. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
Setting 0: Disabled No carrier frequency reduction at high current.
Setting 1: Enabled for Output Frequencies below 6 Hz The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive returns to its normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.
Setting 2: Enabled for Entire Frequency Range The carrier frequency is reduced at the following speeds: • Below 6 Hz when the current exceeds 100% of the drive rated current. • Above 7 Hz when the current exceeds 112% of the drive rated current. The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to the set value.
n L8-40: Carrier Frequency Reduction Off Delay Time
Sets the delay time which is used to switch back to the normal carrier frequency. The carrier frequency reduction function is disabled if this value is 0 s.
n L8-41: High Current Alarm Selection
The drive can be set to trigger a high current alarm (HCA) when the output current rises too high.
Setting 0: Disabled No alarm is output.
Setting 1: Enabled An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output indicating an alarm (H2-01/02/03 = 10) can be programmed.
n L8-51: STo Fault Detection Level
Note: Parameter available in drive software versions PRG: 1018 and later. Sets the STo detection level as a percentage of the motor rated current. Increase this value for faster detection of pull-out during acceleration. The drive calculates this value automatically when L8-51 is set to 0.0%. There is normally no need to change this parameter from the default value.
n L8-54: STo Deviation Detection
Note: Parameter available in drive software versions PRG: 1018 and later. Enables or disables the STo Deviation fault detection. There is normally no need to change this parameter from the default value.
Setting 0: Disabled Setting 1: Enabled
5.8 L: Protection Functions
Parameter Details
L8-38 — Carrier Frequency Reduction Selection — PDF page 239
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-38 | Carrier Frequency Reduction Selection | 0 to 2 | Determined by o2-04 |
L8-40 — Low Carrier Frequency Off Delay Time — PDF page 239
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-40 | Low Carrier Frequency Off Delay Time | 0.00 or 2.00 s | 0.50 s |
L8-41 — High Current Alarm Selection — PDF page 239
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-41 | High Current Alarm Selection | 0 or 1 | 0 |
L8-51 — STo Fault Detection Level — PDF page 239
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-51 | STo Fault Detection Level | 0.0 to 150. % | 0.0% |
L8-54 — STo Deviation Detection — PDF page 239
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | L8-54 | STo Deviation Detection | 0 or 1 | 1 |
Manual — Hunting prevention and AFR introduction — page 240
Source reference: SIEP C71060618F, December 2016, physical PDF page 240. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
5.9 n: Special Adjustments
The n parameters handle a variety of specialized adjustments and functions, including Hunting Prevention, AFR Control, High Slip Braking, resistance between motor lines, and PM motor control functions.
u n1: Hunting Prevention
Hunting Prevention keeps the drive from hunting as a result of low inertia and operating with light load. It is available in V/f Control only.
n n1-01: Hunting Prevention Selection
Enables or disables the Hunting Prevention function.
Note: This function is available only when using V/f Control. Hunting Prevention should be disabled when drive response is need over suppressing motor oscillation. This function can also be disabled without any problems in applications with high inertia loads or relatively heavy loads.
No. Name Setting Range Default
Setting 0: Disabled
Setting 1: Enabled
n n1-02: Hunting Prevention Gain Setting
Sets the gain for the Hunting Prevention Function.
Normally, n1-02 does not need to be changed, but adjustment may help under the following conditions: • If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases. • If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.
n n1-03: Hunting Prevention Time Constant
Determines how responsive the Hunting Prevention function is (affects the primary delay time for Hunting Prevention).
n n1-05: Hunting Prevention Gain while in Reverse
This parameter is the same as n1-02, except that it is used when the motor rotates in reverse. See the setting instructions for n1-02.
Note: When set to 0 ms, n1-02 is enabled even when the drive is operating in reverse.
u n2: Automatic Frequency Regulator (AFR) Tuning
These parameters are used to achieve speed stability when a load is suddenly applied or removed by calculating changes in the torque current feedback and then compensating the output frequency.
Note: Before making changes to the AFR parameters, make sure the motor parameters are set properly or perform Auto-Tuning.
n n2-01: Speed Feedback Detection Control (AFR) Gain
Sets the internal speed feedback detection control gain in the AFR.
<1> Default setting is determined by drive model.
n1-01 — Hunting Prevention Selection — PDF page 240
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n1-01 | Hunting Prevention Selection | 0 or 1 | 1 |
n1-02 — Hunting Prevention Gain Setting — PDF page 240
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n1-02 | Hunting Prevention Gain Setting | 0.00 to 2.50 | 1.00 |
n1-03 — Hunting Prevention Time Constant — PDF page 240
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n1-03 | Hunting Prevention Time Constant | 0 to 500 ms | Determined by o2-04 |
n1-05 — Hunting Prevention Gain while in Reverse — PDF page 240
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n1-05 | Hunting Prevention Gain while in Reverse | 0.00 to 2.50 | 0.00 |
n2-01 — Speed Feedback Detection Control (AFR) Gain — PDF page 240
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n2-01 | Speed Feedback Detection Control (AFR) Gain | 0.00 to 10.00 | <1> |
Manual — AFR constants and braking restrictions — page 241
Source reference: SIEP C71060618F, December 2016, physical PDF page 241. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00. Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50.
Normally there is no need to adjust n2-01 from the default setting. Make adjustments in the following cases: • If hunting occurs, increase the set value in steps of 0.05 while checking the response. • If response is low, decrease the set value in steps of 0.05 while checking the response.
n n2-02/n2-03: AFR Time Constant 1/2
Parameter n2-02 sets the time constant normally used by AFR. Parameter n2-03 sets the time constant during Speed Search or when during regenerative operation the actual motor slip exceeds 50% of the rated slip.
No. Name Setting Range Default
Note: Parameter n2-02 cannot be set higher than n2-03 or an oPE08 error will result. These parameters rarely need to be changed. Adjust settings only under the following conditions. • If hunting occurs, increase n2-02. If response is low, decrease it. • Increase the setting of n2-03 if overvoltage (ov) failures occur with high inertia loads at the end of acceleration or when the load changes radically. • When increasing n2-02, make sure to increase C4-02 (Torque Compensation Delay Time Constant 1) proportionally. • When increasing n2-03, make sure to increase C4-06 (Torque Compensation Delay Time Constant 2) proportionally.
u n3: High Slip Braking (HSB)/Overexcitation Deceleration
High Slip Braking (V/f Control) HSB works in V/f Control only and is used to decrease the stopping time compared to normal deceleration without using braking resistor options. HSB stops the motor by reducing the output frequency in large steps, thus producing a high slip. Regenerative energy created from decelerating the load is dissipated in the motor windings through increased motor slip. Because of the increased temperature of the motor windings, HSB should not be used for frequently stopping the motor. The duty cycle should be around 5% or less. Notes on using High Slip Braking: • The deceleration time that has been set is ignored during HSB. • Braking time varies based on the load inertia and motor characteristics. • HSB must be triggered by a digital input set to H1-□□ = 68. Once the HSB command is given, it is not possible to restart the drive until the motor is stopped and the Run command is cycled. Use parameters n3-01 through n3-04 for adjusting HSB. Overexcitation Deceleration (V/f Control and Open Loop Vector) Overexcitation deceleration increases the flux during deceleration and allows shorter deceleration time settings than with normal deceleration without the use of a braking resistor. Enabled by setting L3-04 = 4. Notes on Overexcitation Deceleration • As regenerative energy is mainly dissipated as heat in the motor, the motor temperature will rise if overexcitation deceleration is applied frequently. In such cases, make sure the motor temperature does not exceed the maximum allowable value or consider using a braking resistor option instead. • The drive decelerates at the active deceleration time. Make sure to set this time so that no overvoltage (ov) fault occurs. • When a Run command is entered during overexcitation deceleration, overexcitation operation is cancelled and the drive will reaccelerate to the specified speed. • Do not use overexcitation deceleration in combination with a braking resistor option. • Overexcitation deceleration cannot be used in OLV/PM control mode. Use parameters n3-13 through n3-23 for adjusting overexcitation deceleration.
n n3-01: High Slip Braking Deceleration Frequency Width
Sets the step width for frequency reduction during HSB. Increase this value if DC bus overvoltage (ov) occurs during HSB.
5.9 n: Special Adjustments
Parameter Details
n2-02 / n2-03 — AFR Time Constant 1 — PDF page 241
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n2-02 | AFR Time Constant 1 | 0 to 2000 ms | 50 ms |
| 2 | n2-03 | AFR Time Constant 2 | 0 to 2000 ms | 750 ms |
Manual — High-slip and overexcitation settings — page 242
Source reference: SIEP C71060618F, December 2016, physical PDF page 242. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
n n3-02: High Slip Braking Current Limit
Sets the maximum current to be output during an HSB stop as a percentage of motor rated current (E2-01). Reducing the current limit increases the deceleration time. Make sure that this value does not exceed 150% of the drive’s current rating.
n n3-03: High Slip Braking Dwell Time at Stop
When the motor reaches a relatively low speed at the end of HSB, the output frequency is kept at the minimum output frequency E1-09 for the time set in n3-03. Increase this time if the inertia is very high and the motor is still coasting after HSB is complete.
n n3-04: High Slip Braking Overload Time
Sets the time required for an HSB overload fault (oL7) to occur when the drive output frequency does not change for some reason during an HSB stop.
n n3-13: Overexcitation Deceleration Gain
Applies a gain to the V/f pattern output value during overexcitation deceleration, thereby determining the level of overexcitation. The drive returns to the normal V/f value after the motor has stopped or when it is accelerating to the frequency reference.
The optimum setting for n3-13 depends on the motor flux saturation characteristics. • Increase the gain by 1.25 to 1.30 to improve the breaking power of overexcitation. • Reduce the value when the motor slip gets too high, which can trigger overcurrent (oC), motor overload (oL1), or drive overload (oL2) faults. Alternatively reduce n3-21.
n n3-21: High Slip Suppression Current Level
If overcurrent, oL1, or oL2 occur during overexcitation deceleration, reduce the overslip suppression current level. Set as a percentage of the drive rated current. Reduce this setting if the current during overexcitation deceleration exceeds the overslip suppression current set in n3-21 as a result of flux saturation and excessive slip. Alternatively reduce the overexcitation gain n3-13.
n n3-23: Overexcitation Operation Selection
Determines which direction overexcitation can be used in. However, parameter L3-04 must be set to 4 in order for n3-23 to be enabled.
Setting 0: Enabled in Both Directions
Setting 1: Enabled in Forward Direction Only
Setting 2: Enabled in Reverse Direction Only
5.9 n: Special Adjustments
n3-01 — High Slip Braking Deceleration Frequency Width — PDF page 242
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n3-01 | High Slip Braking Deceleration Frequency Width | 1 to 20% | 5% |
n3-02 — High Slip Braking Current Limit — PDF page 242
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n3-02 | High Slip Braking Current Limit | 100 to 200% | 150% |
n3-03 — High Slip Braking Dwell Time at Stop — PDF page 242
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n3-03 | High Slip Braking Dwell Time at Stop | 0.0 to 10.0 s | 1.0 s |
n3-04 — High Slip Braking Overload Time — PDF page 242
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n3-04 | High Slip Braking Overload Time | 30 to 1200 s | 40 s |
n3-13 — Overexcitation Deceleration Gain — PDF page 242
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n3-13 | Overexcitation Deceleration Gain | 1.00 to 1.40 | 1.10 |
n3-21 — Overslip Suppression Current Level — PDF page 242
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n3-21 | Overslip Suppression Current Level | 0 to 150% | 100% |
n3-23 — Overexcitation Operation Selection — PDF page 242
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n3-23 | Overexcitation Operation Selection | 0 to 2 | 0 |
Manual — Online resistance and PM current settings — page 243
Source reference: SIEP C71060618F, December 2016, physical PDF page 243. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u n6: Motor Line-to-Line Resistance Online Tuning
The drive can tune the motor line-to-line resistance during run in order to prevent torque loss due to a rise in motor temperature increase, especially at low speeds.
n n6-01: Motor Line-to-Line Resistance Online Tuning Selection
No. Name Setting Range Default
Setting 0: Disabled
Setting 1: Enabled
u n8: PM Motor Control
These parameters are available when using the special Open Loop Vector Control for permanent magnet motors and can be used to adjust the control performance.
n n8-45: Speed Feedback Detection Control Gain (for PM OLV)
Sets the gain for internal speed feedback detection control. Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions: • Increase this setting if motor oscillation or hunting occurs. • Decrease this setting in increments of 0.05 to decrease the drive responsiveness.
n n8-47: Pull-In Current Compensation Time Constant (for PM OLV)
Sets the time constant for making the actual current and the pull-in current agree. Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions: • Increase this setting when it takes too long for the reference value for the pull-in current to match the target value. • Decrease this setting if motor oscillation occurs.
n n8-48: Pull-In Current (for PM OLV)
Tells the drive the amount of d-axis current to be provided to the motor during no-load operation at a constant speed. Set as a percentage of the motor rated current. • Increase this setting when hunting occurs or the motor speed is unstable while running at a constant speed. • If there is too much current when driving a light load at a constant speed, then reduce this level slightly.
<1> Setting range varies depending on drive software version. Software versions PRG: 1018 and later disable pull-in current when n8-48 = 0, and allow the pull-in current to be changed during Run. PRG: 1018 and later: 0% or 20 to 200% PRG: 1017 and earlier: 20 to 200%
n n8-49: d Axis Current for High Efficiency Control (for PM OLV)
Sets the amount of d axis current when using Energy Saving control as a percentage of the motor rated current. Although this setting seldom needs to be changed, please note the following: • If motor operation is unstable when driving heavy loads, try increasing this setting (towards 0). • If motor parameters (E5) have been changed, this value will be reset to 0 and has to be readjusted.
5.9 n: Special Adjustments
Parameter Details
n6-01 — Motor Line-to-Line Resistance Online Tuning — PDF page 243
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n6-01 | Motor Line-to-Line Resistance Online Tuning | 0 or 1 | 1 |
n8-45 — Speed Feedback Detection Control Gain — PDF page 243
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-45 | Speed Feedback Detection Control Gain | 0.00 to 10.00 | 0.80 |
n8-47 — Pull-In Current Compensation Time Constant — PDF page 243
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-47 | Pull-In Current Compensation Time Constant | 0.0 to 100.0 s | 5.0 s |
n8-48 — Pull-In Current — PDF page 243
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-48 | Pull-In Current | <1> | Determined by E5-01 |
Manual — PM current, inertia and voltage limit — page 244
Source reference: SIEP C71060618F, December 2016, physical PDF page 244. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
<1> Setting range varies depending on drive software version. Software versions PRG: 1018 and later allow this parameter to be changed during Run. PRG: 1018 and later: -200.0 to 200.0% PRG: 1017 and earlier: -200.0 to 0.0%
n n8-51: Acceleration/Deceleration Time Pull-In Current (for PM OLV)
Sets the d-axis current during acceleration and deceleration as a percentage of the motor rated current (E5-03). Adjustments to this setting may help in the following situations: • Increase this setting when a large amount of starting torque is required. • Lower this setting if there is excessive current during acceleration and deceleration.
n n8-54: Voltage Error Compensation Time Constant (for PM OLV)
Sets the time constant for voltage error compensation. Make changes to this parameter under the following conditions: • Adjust the value when hunting occurs at low speed. • Increase the value in steps of 0.1 when hunting occurs with sudden load changes. Try to disable the compensation by setting n8-51 = 0 if increasing does not help. • Increase the value when oscillations occur at start.
n n8-55: Load Inertia (for PM OLV)
Sets the ratio between motor inertia and the inertia of the connected machinery. If this value is set too low, the motor may not start very smoothly, and a STo fault (Motor Step-Out) might occur.
Setting 0: Below 1:10 The inertia ratio between the motor and the load is just less than 1:10.
Setting 1: Between 1:10 and 1:30 The inertia ratio between the motor and the load is between 1:10 and 1:30. Set n8-55 to 1 if a STo fault occurs as a result of impact load or sudden acceleration/deceleration when n8-55 = 0.
Setting 2: Between 1:30 and 1:50 The inertia ratio between the motor and the load is between 1:30 and 1:50. Set n8-55 to 2 if a STo fault occurs as a result of impact load or sudden acceleration/deceleration when n8-55 = 1.
Setting 3: Beyond 1:50 The inertia ratio between the motor and the load is higher than 1:50. Set n8-55 to 3 if a STo fault occurs as a result of impact load or sudden acceleration/deceleration when n8-55 = 2.
n n8-62: Output Voltage Limit (for PM OLV)
Sets the output voltage limit to prevent output voltage saturation. This value should not be set higher than the actual input voltage.
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class drive.
5.9 n: Special Adjustments
n8-49 — d Axis Current for High Efficiency Control — PDF page 244
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-49 | d Axis Current for High Efficiency Control | <1> | Determined by E5-01 |
n8-51 — Acceleration/Deceleration Time Pull-In Current — PDF page 244
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-51 | Acceleration/Deceleration Time Pull-In Current | 0 to 200% | Determined by E5-01 |
n8-54 — Voltage Error Compensation Time Constant — PDF page 244
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-54 | Voltage Error Compensation Time Constant | 0.00 to 10.00 | 1.00 |
n8-55 — Motor/Load Inertia Ratio — PDF page 244
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-55 | Motor/Load Inertia Ratio | 0 to 3 | 0 |
n8-62 — Output Voltage Limit — PDF page 244
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-62 | Output Voltage Limit | 0.0 to 230.0 Vac <1> | 230 Vac <1> |
Manual — PM output voltage and suppression gains — page 245
Source reference: SIEP C71060618F, December 2016, physical PDF page 245. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n n8-63/n8-68: Output Voltage Limit Gain 1/2
n8-63 sets the gain for the output voltage limit in 0.01 units. n8-68 sets the voltage detection level adjustment gain. There is normally no need to change these parameters from their default values.
No. Name Setting Range Default
n n8-65: Speed Feedback Detection Control Gain during ov Suppression (for PM OLV)
Sets the gain for internal speed feedback detection control when overvoltage suppression is active. Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions: • Increase this setting if motor oscillation or hunting occurs when ov suppression is active. • Decrease this setting in increments of 0.05 to decrease the drive responsiveness during ov suppression.
n n8-87: Output Voltage Limit Selection
Note: Parameter available in drive software versions PRG: 1018 and later. Determines the method of the output voltage limit. Use the feed-forward method if oscillation occurs in the constant output range. There is normally no need to change this parameter from its default value.
Setting 0: Feedback Method Setting 1: Feed-Forward Method
n n8-88: Output Voltage Limit Switching Current Level
Note: Parameter available in drive software versions PRG: 1018 and later. Sets the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03). There is normally no need to change this parameter from its default value.
n n8-89: Output Voltage Limit Switching Current Hysteresis Width
Note: Parameter available in drive software versions PRG: 1018 and later. Determines the hysteresis of the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03).
n n8-90: Output Voltage Limit Switching Speed
Note: Parameter available in drive software versions PRG: 1018 and later. Sets the speed level to switch the output voltage limit sequence. Set as a percentage of the maximum output frequency (E1-04).
5.9 n: Special Adjustments
Parameter Details
during Overvoltage Suppression
n8-63 / n8-68 — Output Voltage Limit Gain 1 — PDF page 245
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-63 | Output Voltage Limit Gain 1 | 0.00 to 100.00 | 1.00 |
| 2 | n8-68 | Output Voltage Limit Gain 2 | 0.50 to 1.50 | 0.95 |
n8-65 — Speed Feedback Detection Control Gain — PDF page 245
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-65 | Speed Feedback Detection Control Gain during Overvoltage Suppression | 0.00 to 10.00 | 1.50 |
n8-87 — Output Voltage Limit Selection — PDF page 245
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-87 | Output Voltage Limit Selection | 0 or 1 | 0 |
n8-88 — Output Voltage Limit Switching Current Level — PDF page 245
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-88 | Output Voltage Limit Switching Current Level | 0 to 400% | 400% |
n8-89 — Output Voltage Limit Switching Current Hysteresis Width — PDF page 245
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-89 | Output Voltage Limit Switching Current Hysteresis Width | 0 to [n8-88] | 3% |
n8-90 — Output Voltage Limit Switching Speed — PDF page 245
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-90 | Output Voltage Limit Switching Speed | 0 to 200% | 200% |
Manual — PM constant-speed current limit — page 246
Source reference: SIEP C71060618F, December 2016, physical PDF page 246. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n n8-91: Id Limit for Output Voltage Limit Control
Note: Parameter available in drive software versions PRG: 1018 and later. Sets the amount of pull-in current that flows through the motor while operating at constant speed. Set as a percentage of the motor rated current (E5-03). Increase this setting if hunting occurs at constant speed.
No. Name Setting Range Default
5.9 n: Special Adjustments
n8-91 — Id Limit for Output Voltage Limit Control — PDF page 246
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | n8-91 | Id Limit for Output Voltage Limit Control | -200 to 0% | -50% |
Manual — Operator monitor and display selections — page 247
Source reference: SIEP C71060618F, December 2016, physical PDF page 247. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
5.10 o: Operator Related Settings
These parameters concern the various functions and features of the digital operator.
u o1: Display Settings and Selections
These parameters determine how data is shown on the operator display.
n o1-01: Drive Mode Unit Monitor Selection
When using an LED operator, pressing the up arrow key on the drive will display the following data: frequency reference → rotational direction → output frequency → output current → o1-01 selection. Parameter o1-01 selects the content of the last monitor in this sequence. There is no effect like this on an LCD operator.
No. Name Setting Range Default
<1> U2-□□ and U3-□□ parameters cannot be selected.
To select a monitor parameter, set the three numeric digits that make up that monitor. This is done by entering the □-□□ part of U□-□□. For a list of monitors, Refer to U: Monitor Parameters on page 254.
n o1-02: User Monitor Selection after Power Up
Selects which monitor parameter will be displayed upon power up. Defaulted to show the frequency reference when the drive is first turned on.
Setting 1: Frequency Reference (U1-01)
Setting 2: Forward/Reverse
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Selected Monitor (set by o1-01) Setting 5 displays the monitor selected from the U parameter by o1-01.
n o1-03: Digital Operator Display Selection
Sets the units used to display the frequency reference and output frequency. Set this parameter to 3 for user-set units before setting parameters o1-10 and o1-11.
Setting 0: 0.01 Hz Units Setting 1: 0.01% Units 100% = max output frequency.
Setting 2: r/min Units Calculated by the max output frequency and the number of motor poles.
Note: Setting 2 requires entering the number of motor poles to E2-04, E4-04, and E5-04.
Setting 3: User-Set Units (use o1-01 and 01-11) Set the value used for the maximum frequency reference to o1-10, then set the placement of the decimal point in this number to o1-11. For example, to display the maximum output frequency as “100.00”, set o1-10 to 10000 and o1-11 to 2 (i.e., 10000 with two numbers to the right of the decimal point).
Note: Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
Parameter Details
o1-01 — Drive Mode Unit Monitor Selection — PDF page 247
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o1-01 | Drive Mode Unit Monitor Selection | 104 to 810 <1> (U1-04 to U8-10) | 106 (U1-06) |
o1-02 — User Monitor Selection after Power Up — PDF page 247
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o1-02 | User Monitor Selection after Power Up | 1 to 5 | 1 |
o1-03 — Digital Operator Display Selection — PDF page 247
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o1-03 | Digital Operator Display Selection | 0 to 3 | 0 |
Manual — Display units and operator key selections — page 248
Source reference: SIEP C71060618F, December 2016, physical PDF page 248. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
U1-01: Frequency Reference U1-02: Output Frequency U1-05: Motor Speed U1-16: Output Frequency after Soft-Starter (Accel/Decel Ramp Generator) d1-01 to d1-17: Frequency References
n o1-05: LCD Contrast Control
Note: Parameter available in drive software versions PRG: 1022 and later. Sets the brightness of the optional LCD operator. The lower the setting, the brighter the LCD contrast. The higher the setting, the darker the LCD contrast.
No. Name Setting Range Default
n o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency. The decimal number is defined by parameter o1-11.
Note: This setting changes automatically when o1-03 is changed. o1-10 can only be adjusted when o1-03 is set to 3.
n o1-11: User-Set Display Units Decimal Display
Determines the number of digits for user-set display if o1-03 is set to 3. The setting value is equal to the number of decimal places. The maximum display value is defined by o1-10.
Note: This setting changes automatically when o1-03 is changed. o1-11 can only be adjusted when o1-03 is set to 3.
u o2: Operator Key Selections
These parameters determine the functions assigned to the operator keys.
n o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Parameter o2-01 determines whether the LO/RE key on the digital operator will be enabled or not for switching between LOCAL and REMOTE.
Setting 0: Disabled The LO/RE key is disabled.
Setting 1: Enabled The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switching between LOCAL mode and REMOTE mode.
n o2-02: STOP Key Function Selection
Selects if the STOP key on the digital operator can be used to stop the operation when the drive is controlled from a remote source (i.e., not from digital operator).
5.10 o: Operator Related Settings
o1-05 — LCD Contrast Control — PDF page 248
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o1-05 | LCD Contrast Control | 0 to 5 | 3 |
o1-10 — User-Set Display Units Maximum Value — PDF page 248
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o1-10 | User-Set Display Units Maximum Value | 1 to 60000 | Determined by o1-03 |
o1-11 — User-Set Display Units Decimal Display — PDF page 248
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o1-11 | User-Set Display Units Decimal Display | 0 to 3 | Determined by o1-03 |
o2-01 — LO/RE Key Function Selection — PDF page 248
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o2-01 | LO/RE Key Function Selection | 0 or 1 | 1 |
o2-02 — STOP Key Function Selection — PDF page 248
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o2-02 | STOP Key Function Selection | 0 or 1 | 1 |
Manual — User defaults and reference input methods — page 249
Source reference: SIEP C71060618F, December 2016, physical PDF page 249. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 0: Disabled The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only be stopped from the Run command source that has been selected.
Setting 1: Enabled The STOP key can be used to terminate the operation, even if the Run command source is not assigned to the digital operator. If operation has been interrupted by pressing the STOP key, the Run command must be cycled to restart the drive.
n o2-03: User Parameter Default Value
Once drive parameters are set up completely, the values set can be saved as “User Initialization Values” by setting parameter o2-03. Once this has been done, the “Initialize Parameters” parameter (A1-03) will offer the choice of “1110: User Initialize”. Choosing A1-03 = “1110: User Initialize”, will reset all parameters to the values saved as “User Initialization Values”. Refer to A1-03: Initialize Parameters on page 117 for details on drive initialization.
No. Name Setting Range Default
Setting 0: No Change All “User Initialization Values” are saved as they are.
Setting 1: Set User Initialization Values The current parameter settings are saved as “User Initialization Values”. After setting o2-03 to 1 and pressing the ENTER key, the values are saved and the display returns to 0.
Setting 2: Clear User Initialization Values All “User Initialization Values” are cleared. After setting o2-03 to 2 and pressing the ENTER key, the values are erased and the display returns to 0. A1-03 = 1110 becomes invalid.
n o2-04: Drive Model Selection
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal performance and proper protection for the drive hardware. This parameter is configured at the factory and does not normally require adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.
Note: 1. Refer to Defaults by Drive Model and Duty Rating (ND/HD) on page 409 for a list of o2-04 settings and parameters that change depending on the drive model selection. 2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly. 3. This parameter is not reset to the default value when the drive is initialized using A1-03.
n o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be used to input a frequency reference from the digital operator.
Setting 0: ENTER Key Required Every change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key before it becomes effective.
Setting 1: ENTER Key Not Required The output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator. The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key has been released. If an undervoltage error (Uv) occurs within 5 seconds of pressing the ENTER key, the frequency reference will not be saved to memory. The digital operator display flashes when settings can be made to the frequency reference.
5.10 o: Operator Related Settings
Parameter Details
o2-03 — User Parameter Default Value — PDF page 249
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o2-03 | User Parameter Default Value | 0 to 2 | 0 |
o2-04 — Drive Model Selection — PDF page 249
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o2-04 | Drive Model Selection | - | Depending on drive size |
o2-05 — Frequency Reference Setting Method Selection — PDF page 249
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o2-05 | Frequency Reference Setting Method Selection | 0 or 1 | 0 |
Manual — Operator loss and copy functions — page 250
Source reference: SIEP C71060618F, December 2016, physical PDF page 250. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
LED graphic shows F00.00 with three flash marks above. This is the illustrated display only, not an actual drive setting. Exact geometry, routing and unprinted numerical values remain original-only.
Figure 5.91 Ready to Set Frequency Reference
n o2-06: Operation Selection when Digital LCD Operator is Disconnected
Determines if the drive will stop when an external LCD operator is removed in LOCAL mode or with b1-02 set to 0.
Note: An LCD operator is available as an option. This setting is not applicable to the standard LED operator that comes with the drive.
No. Name Setting Range Default
Setting 0: Continue Operation The operation is continued.
Setting 1: Trigger a Fault The operation is stopped and an oPr fault is triggered. The motor coasts to stop.
n o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up when the Run command is set to be given from the digital operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02/16 = 0).
Setting 0: Forward
Setting 1: Reverse
u o3: Copy Function
Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive.
n o3-01: Copy Function Selection
This parameter controls the copying of parameters to and from the LED operator (option). The copy function will change certain parameter default settings depending on the regional specification of the drive.
0: COPY SELECT (no function)
1: INV --> OP READ All parameters are copied from the drive to the digital operator.
Note: Set o3-02 to 1 to unlock copy protection.
2: OP --> INV WRITE All parameters are copied from the digital operator to the drive.
3: OP<-->INV VERIFY Parameter settings in the drive are compared to those in the digital operator.
Note: When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur.
n o3-02 Copy Allowed Selection
Enables and disables the digital operator copy functions.
5.10 o: Operator Related Settings
o2-06 — Digital Operator Disconnection Operation — PDF page 250
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o2-06 | Digital Operator Disconnection Operation | 0 or 1 | 0 |
o2-07 — Motor Direction at Power Up when Using Operator — PDF page 250
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o2-07 | Motor Direction at Power Up when Using Operator | 0 or 1 | 0 |
o3-01 — Copy Function Selection — PDF page 250
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o3-01 | Copy Function Selection | 0 to 3 | 0 |
Manual — Copy permission and maintenance counters — page 251
Source reference: SIEP C71060618F, December 2016, physical PDF page 251. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
0: Disabled No digital operator copy functions are allowed
1: Enabled Copying allowed
u o4: Maintenance Monitor Settings
n o4-01: Accumulated Operation Time Setting
Parameter o4-01 sets the cumulative operation time and allows the user to set the starting value of the accumulated operation time displayed in monitor U4-01.
Note: The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also be displayed in monitor U4-01.
n o4-02: Accumulated Operation Time Selection
Selects the conditions for what is to be considered “accumulated operation time.” Accumulated operation time is displayed in U4-01.
Setting 0: Power On Time The drive logs the time it is connected to a power supply, no matter if the motor is running or not.
Setting 1: Run Time The drive logs the time that the output is active, i.e., whenever a Run command is active (even if the motor is not rotating) or a voltage is output.
n o4-03: Cooling Fan Operation Time/Maintenance Setting
Sets the value of the cooling fan operation time counter displayed in monitor U4-03. Parameter o4-03 also sets the base value used for the cooling fan maintenance value displayed in U4-04. Be sure to reset this parameter back to 0 if the cooling fan is replaced.
Note: 1. The value in o4-03 is set in 10 h units. For example, a setting of 30 will set the cooling fan operation time counter to 300 h. “300” will be displayed in monitor U4-03. 2. The actual maintenance time depends on the environment the drive is used in.
n o4-05: Capacitor Maintenance Setting
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected performance life. This value should be reset to 0 when the DC bus capacitors have been replaced.
Note: The actual maintenance time will depend on the environment the drive is used in.
n o4-07: DC Bus Pre-charge Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected performance life. This value should be reset to 0 when the relay has been replaced.
Note: The maintenance actual time depends on the environment the drive is used in.
5.10 o: Operator Related Settings
Parameter Details
Operator and maintenance setting | o3-02
Operator and maintenance setting | o4-01
Operator and maintenance setting | o4-02
Operator and maintenance setting | o4-03
Operator and maintenance setting | o4-05
Operator and maintenance setting — PDF page 251
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o3-02 | Copy Allowed Selection | 0, 1 | 0 |
Operator and maintenance setting — PDF page 251
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-01 | Accumulated Operation Time Setting | 0 to 9999 | 0 |
Operator and maintenance setting — PDF page 251
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-02 | Accumulated Operation Time Selection | 0 or 1 | 0 |
Operator and maintenance setting — PDF page 251
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-03 | Cooling Fan Operation Time | 0 to 9999 | 0 |
Operator and maintenance setting — PDF page 251
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-05 | Capacitor Maintenance Setting | 0 to 150% | 0% |
Manual — Counter reset and user parameters — page 252
Source reference: SIEP C71060618F, December 2016, physical PDF page 252. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Setting Range Default
n o4-09: IGBT Maintenance Setting
Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. This value should be reset to 0 when the IGBTs have been replaced.
Note: The actual maintenance time depends on the environment the drive is used in.
n o4-11: U2, U3 Initialization
When the drive is initialized, the fault trace and fault history monitors (U2-□□ and U3-□□) are not reset. Parameter o4-11 can be used to initialize them.
Setting 0: No Action The drive keeps a record of the fault trace and fault history.
Setting 1: Reset Fault Data Resets the data for the U2-□□ and U3-□□ monitors. Once o4-11 is set to 1 and the ENTER key is pressed, the fault data are erased and the display returns to 0.
n o4-12: kWh Monitor Initialization
The kWh monitors U4-10 and U4-11 are not initialized when the power is cycled or the drive is initialized. o4-12 can be used to manually reset them.
Setting 0: No Action The kWh data are kept as they are.
Setting 1: Reset kWh Data Resets the kWh counter. The monitors U4-10 and U4-11 will show 0. Once o4-12 is set to 1 and the ENTER key is pressed, the kWh data are erased and the display returns to 0.
n o4-13: Number of Run Commands Counter Initialization
The Run command counter displayed in U4-02 is not reset when the power is cycled or the drive is initialized. Using o4-13 it can be manually reset to 0.
Setting 0: No Action The Run command data are kept as they are.
Setting 1: Reset Run Commands Counter Resets the Run commands counter. The monitor U4-02 will show 0. Once o4-13 is set to 1 and the ENTER key is pressed, the counter value is erased and the display returns to 0.
u q: DriveWorksEZ Parameters
n q1-01 to q6-07: Reserved for Use by DriveWorksEZ
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
5.10 o: Operator Related Settings
Operator and maintenance setting | o4-07
Operator and maintenance setting | o4-09
Operator and maintenance setting | o4-11
Operator and maintenance setting | o4-12
Operator and maintenance setting | o4-13
Operator and maintenance setting — PDF page 252
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-07 | DC Bus Pre-charge Relay Maintenance Setting | 0 to 150% | 0% |
Operator and maintenance setting — PDF page 252
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-09 | IGBT Maintenance Setting | 0 to 150% | 0% |
Operator and maintenance setting — PDF page 252
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-11 | U2, U3 Initialization | 0 or 1 | 0 |
Operator and maintenance setting — PDF page 252
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-12 | kWh Monitor Initialization | 0 or 1 | 0 |
Operator and maintenance setting — PDF page 252
| Source row | No. | Name | Setting Range | Default |
|---|---|---|---|---|
| 1 | o4-13 | Number of Run Commands Counter Reset | 0 or 1 | 0 |
Manual — DriveWorksEZ and auto-tuning references — page 253
Source reference: SIEP C71060618F, December 2016, physical PDF page 253. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u r: DriveWorksEZ Connection Parameters
n r1-01 to r1-40: DriveWorksEZ Connection Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.
u T: Motor Tuning
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance. Refer to Auto-Tuning on page 102 for details on Auto-Tuning parameters.
5.10 o: Operator Related Settings
Parameter Details
Manual — Status, fault and maintenance monitor groups — page 254
Source reference: SIEP C71060618F, December 2016, physical PDF page 254. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
5.11 U: Monitor Parameters
Monitor parameters let the user view various aspects of drive performance as it is shown on the operator display. Some monitors can be output from terminal AM by assigning the specific monitor parameter number to H4-01. Refer to H4-01: Multi-Function Analog Terminal AM Monitor Selection on page 210 for details on assigning functions to the analog output.
u U1: Operation Status Monitors
Status monitors display drive status like output frequency, current etc. Refer to U1: Operation Status Monitors on page 399 for a complete list of U1-□□ monitors and descriptions.
u U2: Fault Trace
These monitor parameters are used to view the status of various drive aspects when a fault occurs. This information is helpful for finding out why a fault occurred. Refer to U2: Fault Trace on page 400 for a complete list of U2-□□ monitors and descriptions. U2-□□ monitors are not reset when the drive is initialized. Refer to o4-11: U2, U3 Initialization on page 252 for instructions to initialize the fault trace.
u U3: Fault History
These parameters display faults that have occurred during operation as well as the drive operation time when those faults occurred. Refer to U3: Fault History on page 401 for a complete list of U3-□□ monitors and descriptions. U3-□□ monitors are not reset when the drive is initialized. Refer to o4-11: U2, U3 Initialization on page 252 for instructions to initialize the fault trace.
u U4: Maintenance Monitors
Maintenance monitors show: • Runtime data of the drive and cooling fans, and number of Run commands issued. • Maintenance data and replacement information for various drive components. • kWh data. • Highest peak current that has occurred and output frequency at the time the peak current occurred. • Motor overload status information. • Detailed information about the present Run command and frequency reference source selection. Refer to U4: Maintenance Monitors on page 402 for a complete list of U4-□□ monitors and descriptions.
u U5: PID Monitors
These monitors display various aspects of PID control. Refer to PID Block Diagram on page 138 for a description of where each monitor is located in the PID control block. Refer to U5: PID Monitors on page 403 for a complete list of U5-□□ monitors and descriptions.
u U6: Control Monitors
Control monitors show: • Reference data for the output voltage and vector control. • ASR monitors. Refer to C5: Automatic Speed Regulator (ASR) on page 154 for details and an illustration that shows where in the ASR block the monitors are located. • The offset value added to the frequency reference by the Frequency Offset function. Refer to Setting 44/45/46: Offset Frequency 1/2/3 Addition on page 192. • The bias value added to the frequency reference by the Up/Down 2 function. Refer to Setting 75/76: Up/Down 2 on page 193. Refer to U6: Control Monitors on page 404 for a complete list of U6-□□ monitors and descriptions.
Note: Fix monitors U6-80 to U6-99 for communication options. Monitor content will vary based on the communication option card connected to the drive. Refer to the option manual for more information.
Manual — DriveWorksEZ monitors — page 255
Source reference: SIEP C71060618F, December 2016, physical PDF page 255. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u U8: DriveWorksEZ Monitors
These monitors are reserved for use with DriveWorksEZ.
5.11 U: Monitor Parameters
Parameter Details
Manual — Troubleshooting safety warnings — page 258
Source reference: SIEP C71060618F, December 2016, physical PDF page 258. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
6.1 Section Safety
DANGER
Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may illustrate drives without covers or safety shields to display details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not touch terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the drive input power is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry, or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming drive input power before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material.
Manual — ESD, wiring and braking notices — page 259
Source reference: SIEP C71060618F, December 2016, physical PDF page 259. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for modification of the product made by the user. Check all the wiring after installing the drive and connecting other devices to ensure that all connections are correct. Failure to comply could result in damage to the drive.
6.1 Section Safety
Troubleshooting
Manual — V/f tuning suggestions — page 260
Source reference: SIEP C71060618F, December 2016, physical PDF page 260. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
6.2 Motor Performance Fine Tuning
This section offers helpful information for counteracting oscillation, hunting, or other faults that occur while performing a trial run. Refer to the section below that corresponds to the motor control method used.
Note: This section describes parameters that are commonly edited. Consult Yaskawa for more information on detailed settings and fine-tuning the drive.
u V/f Motor Control Method Tuning
Table 6.1 Parameters for Tuning the Drive in V/f Motor Control Method
Problem | Parameter | Corrective Action | Default Value
Suggested Setting
<1> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default setting shown is for V/f Control.
Note: Use slip compensation to improve speed precision in V/f Control. First make sure that the proper values have been set for the motor rated current to E2-01, motor rated slip (E2-02), and motor no-load current (E2-03). Next, adjust the slip compensation gain set to C3-01 so that it is between 0.5 to 1.5.
V/f tuning | • Motor hunting and oscillation at speeds between 10 and 40 Hz
V/f tuning | • Motor noise • Motor hunting and oscillation at speeds up to 40 Hz
V/f tuning | • Poor torque or speed response • Motor hunting and oscillation
V/f tuning | • Poor motor torque at speeds below 10 Hz • Motor hunting and oscillation
V/f tuning | • Poor motor torque at low speeds • Motor instability at motor start
V/f tuning | • Poor speed precision
V/f tuning — PDF page 260
| Source row | Problem | Parameter | Corrective Action | Default Value | Suggested Setting |
|---|---|---|---|---|---|
| 1 | • Motor hunting and oscillation at speeds between 10 and 40 Hz | Hunting Prevention Gain (n1-02) | • If insufficient motor torque relative to the size of the load causes hunting, reduce the setting. • When motor hunting and oscillation occur with a light load, increase the setting. • Lower this setting if hunting occurs when using a motor with a relatively low inductance, such as a high-frequency motor or a motor with a larger frame size. | 1.00 | 0.10 to 2.00 |
| 2 | • Motor noise • Motor hunting and oscillation at speeds up to 40 Hz | Carrier Frequency Selection (C6-02) | • If the motor noise is too loud, increase the carrier frequency. • When motor hunting and oscillation occur at speeds up to 40 Hz, lower the carrier frequency. • The default setting for the carrier frequency depends on the drive capacity (o2-04) and the Drive Duty Selection (C6-01). | 7 (Swing PWM 1) | 1 to A |
| 3 | • Poor torque or speed response • Motor hunting and oscillation | Torque Compensation Primary Delay Time (C4-02) | • If motor torque and speed response are too slow, decrease the setting. • If motor hunting and oscillation occur, increase the setting. | 200 ms <1> | 100 to 1000 ms |
| 4 | • Poor motor torque at speeds below 10 Hz • Motor hunting and oscillation | Torque Compensation Gain (C4-01) | • If motor torque is insufficient at speeds below 10 Hz, increase the setting. • If motor hunting and oscillation with a relatively light load, decrease the setting. | 1.00 | 0.50 to 1.50 |
| 5 | • Poor motor torque at low speeds • Motor instability at motor start | Mid Output Voltage A (E1-08) Minimum Output Voltage (E1-10) | • If torque is insufficient at speeds below 10 Hz, increase the setting. • If motor instability occurs at motor start, decrease the setting. Note: The recommended setting value is for 200 V class drives. Double this value when using a 400 V class drive. | E1-08: 18.4 V E1-10: 13.8 V <1> | Initial value ±5 V |
| 6 | • Poor speed precision | Slip Compensation Gain (C3-01) | • After setting the motor-rated current (E2-01), motor-rated slip (E2-02) and motor no-load current (E2-03), adjust the slip compensation gain (C3-01). | - | 0.5 to 1.5 |
Manual — OLV tuning suggestions — page 261
Source reference: SIEP C71060618F, December 2016, physical PDF page 261. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u Open Loop Vector (OLV) Motor Control Method Tuning
Table 6.2 Parameters for Tuning the Drive in OLV Motor Control Method
Problem | Parameter No. | Corrective Action | Default Value | Suggested Setting
6.2 Motor Performance Fine Tuning
Troubleshooting
OLV tuning continuation | • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz.
OLV tuning continuation | • Overvoltage trips when accelerating, decelerating, or during sudden speed or load changes.
OLV tuning continuation | • Poor motor torque and speed response • Motor hunting and oscillation.
OLV tuning continuation | • Poor speed response and stability
OLV tuning continuation | • Poor speed precision
OLV tuning continuation | • Motor noise • Control motor hunting and oscillation occur at speeds below 10 Hz.
OLV tuning continuation — PDF page 261
| Source row | Problem | Parameter No. | Corrective Action | Default Value | Suggested Setting |
|---|---|---|---|---|---|
| 1 | • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz. | AFR Gain (n2-01) | • If motor torque and speed response are too slow, gradually decrease the setting by 0.05. • If motor hunting and oscillation occur, gradually increase the setting by 0.05. | <1> | 0.50 to 2.00 |
| 2 | • Poor motor torque and speed response • Control motor hunting and oscillation at speeds between 10 and 40 Hz. | AFR Time Constant 1 (n2-02) | • To improve motor torque speed response, gradually reduce this setting by 10 ms and check the performance. • If motor hunting and oscillation occur as a result of load inertia, gradually increase the setting by 50 ms and check the performance. Note: Ensure that n2-02 ≤ n2-03. When making adjustments to n2-02, set C4-02 (Torque Compensation Primary Delay Time Constant 1) accordingly. | 50 ms | 50 to 2000 ms |
| 3 | • Overvoltage trips when accelerating, decelerating, or during sudden speed or load changes. | AFR Time Constant 2 (n2-03) | • If overvoltage trips occur, gradually increase this setting by 50 ms. • If response is slow, gradually reduce this setting by 10 ms. Note: Ensure that n2-02 ≤ n2-03. When making adjustments to n2-03, increase the value of C4-06 (Torque Compensation Primary Delay Time 2) proportionally. | 750 ms | 750 to 2000 ms |
| 4 | • Overvoltage trips when accelerating, decelerating, or during sudden speed or load changes. | Torque Compensation Primary Delay Time Constant 2 (C4-06) | • If overvoltage trips occur, gradually increase this setting by 10 ms and check the performance. • If response is slow, gradually reduce this setting by 2 ms and check the performance. Note: Ensure that C4-02 ≤ C4-06. When changing C4-06 (Torque Compensation Primary Delay Time Constant 2), increase the value of n2-03 proportionally. | 150 ms | 150 to 750 ms |
| 5 | • Poor motor torque and speed response • Motor hunting and oscillation. | Torque Compensation Primary Delay Time Constant 1 (C4-02) | • To improve motor torque speed response, gradually reduce this setting by 2 ms and check the performance. • If motor hunting and oscillation occur, gradually increase this setting by 10 ms. Note: Ensure that C4-02 ≤ C4-06. When making adjustments to C4-02, increase n2-02 (AFR Time Constant) proportionally. | 20 ms <2> | 20 to 100 ms |
| 6 | • Poor speed response and stability | Slip Compensation Primary Delay Time Constant (C3-02) | • If response is slow, gradually decrease the setting by 10 ms. • If speed is unstable, gradually increase the setting by 10 ms. | 200 ms <2> | 100 to 500 ms |
| 7 | • Poor speed precision | Slip Compensation Gain (C3-01) | • If speed is too slow, gradually increase the setting by 0.1 ms. • If speed is too fast, gradually decrease the setting by 0.1 ms. | 1.0 <2> | 0.5 to 1.5 |
| 8 | • Motor noise • Control motor hunting and oscillation occur at speeds below 10 Hz. | Carrier Frequency Selection (C6-02) | • If there is too much motor noise, the carrier frequency is too high. • If motor hunting and oscillation occur at low speeds, reduce the carrier frequency. • The default setting for the carrier frequency depends on the drive capacity (o2-04) and Drive Duty Selection (C6-01). | 7 (Swing PWM 1) | 0 to the default setting |
Manual — OLV footnotes and application tuning — page 262
Source reference: SIEP C71060618F, December 2016, physical PDF page 262. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Problem | Parameter No. | Corrective Action | Default Value | Suggested Setting
<1> Default setting is determined by drive model. Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00. Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50. <2> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using parameter E1-03. The default setting shown is for V/f Control.
When using OLV Motor Control, leave the torque compensation gain (C4-01) at its default setting of 1.00. To increase speed precision during regeneration in OLV Motor Control, enable slip compensation during regeneration (C3-04 = “1”).
u Motor Hunting and Oscillation Control Parameters
In addition to the parameters discussed on page 169, the following parameters indirectly affect motor hunting and oscillation.
Table 6.3 Parameters that Affect Control Performance in Applications
Name (Parameter No.) Application
6.2 Motor Performance Fine Tuning
OLV tuning continuation | • Poor motor torque at low speeds • Poor speed response • Motor instability at motor start.
Application tuning parameters | Dwell Function (b6-01 through b6-04)
Application tuning parameters | Accel/Decel Time (C1-01 through C1-09)
Application tuning parameters | S-Curve Characteristics (C2-01 through C2-04)
Application tuning parameters | Jump Frequency (d3-01 through d3-04)
Application tuning parameters | Analog Filter Time Constant (H3-13)
Application tuning parameters | Stall Prevention (L3-01 through L3-06, L3-11)
Application tuning parameters | Torque Limits (L7-01 through L7-04, L7-06, L7-07)
OLV tuning continuation — PDF page 262
| Source row | Problem | Parameter No. | Corrective Action | Default Value | Suggested Setting |
|---|---|---|---|---|---|
| 1 | • Poor motor torque at low speeds • Poor speed response • Motor instability at motor start. | Mid Output Voltage A (E1-08) Minimum Output Voltage (E1-10) | • If motor torque and speed response are too slow, increase the setting. • If the motor exhibits excessive instability at start- up, reduce the setting. Note: The default value is for 200 V class units. Double this value when using a 400 V class drive. When working with a relatively light load, increasing this value too much can create an excessively high of a torque reference. | E1-08: <2> 12.0 V E1-10: 2.5 V <2> | Initial ±2 V |
Application tuning parameters — PDF page 262
| Source row | Name (Parameter No.) | Application |
|---|---|---|
| 1 | Dwell Function (b6-01 through b6-04) | Prevents motor speed loss by maintaining the output frequency when working with heavy loads or when there is powerful backlash on the machine side. |
| 2 | Accel/Decel Time (C1-01 through C1-09) | Adjusting accel and decel times will affect the torque presented to the motor during acceleration or deceleration. |
| 3 | S-Curve Characteristics (C2-01 through C2-04) | Prevents shock at the beginning and end of acceleration and deceleration. |
| 4 | Jump Frequency (d3-01 through d3-04) | Skips over the resonant frequencies of connected machinery. |
| 5 | Analog Filter Time Constant (H3-13) | Prevents fluctuation in the analog input signal due to noise. |
| 6 | Stall Prevention (L3-01 through L3-06, L3-11) | • Prevents motor speed loss and overvoltage. Used when the load is too heavy and also during sudden acceleration/deceleration. • Adjustment is not normally required because Stall Prevention is enabled as a default. Disable Stall Prevention during deceleration (L3-04 = “0”) when using a braking resistor. |
| 7 | Torque Limits (L7-01 through L7-04, L7-06, L7-07) | • Sets the maximum torque for Open Loop Vector Control. • Ensure that the drive capacity is greater than the motor capacity when increasing this setting. Be careful when reducing this value because motor speed loss may occur with heavy loads. |
Manual — Alarm, fault and error responses — page 263
Source reference: SIEP C71060618F, December 2016, physical PDF page 263. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
6.3 Drive Alarms, Faults, and Errors
u Types of Alarms, Faults, and Errors
Check the LED operator for information about possible faults if the drive or motor fails to operate. Refer to Using the Digital LED Operator on page 80. If problems occur that are not covered in this manual, contact the nearest Yaskawa representative with the following information: • Drive model • Software version • Date of purchase • Description of the problem Table 6.4 contains descriptions of the various types of alarms, faults, and errors that may occur while operating the drive. Contact Yaskawa in the event of drive failure.
Table 6.4 Types of Alarms, Faults, and Errors
Type Drive Responses to Alarms, Faults, and Errors
Troubleshooting
Alarm, fault and error response | Faults
Alarm, fault and error response | Minor Faults and Alarms
Alarm, fault and error response | Operation Errors
Alarm, fault and error response | Tuning Errors
Alarm, fault and error response — PDF page 263
| Source row | Type | Drive Responses to Alarms, Faults, and Errors |
|---|---|---|
| 1 | Faults | When the drive detects a fault: • The digital operator displays text that indicates the specific fault and the ALM indicator LED remains lit until the fault is reset. • The fault interrupts drive output and the motor coasts to a stop. • Depending on the setting, the drive and motor may stop via different methods than listed. • If a digital output is programmed for fault output (H2-□□ = E), it will close if a fault occurs. When the drive detects a fault, it will remain inoperable until that fault has been reset. Refer to Fault Reset Methods on page 298. |
| 2 | Minor Faults and Alarms | When the drive detects an alarm or a minor fault: • The digital operator displays text that indicates the specific alarm or minor fault and the ALM indicator LED flashes. • The motor does not stop. • One of the multi-function contact outputs closes if set to be tripped by a minor fault (H2-□□ = 10), but not by an alarm. • The digital operator displays text indicating a specific alarm and ALM indicator LED flashes. Remove the cause of an alarm or minor fault to automatically reset. |
| 3 | Operation Errors | When parameter settings conflict with one another or do not match hardware settings (such as with an option card), it results in an operation error. When the drive detects an operation error: • The digital operator displays text that indicates the specific error. • Multi-function contact outputs do not operate. When the drive detects an operation error, it will not operate the motor until the error has been reset. Correct the settings that caused the operation error to reset. |
| 4 | Tuning Errors | Tuning errors occur while performing Auto-Tuning. When the drive detects a tuning error: • The digital operator displays text indicating the specific error. • Multi-function contact outputs do not operate. • Motor coasts to stop. • Remove the cause of the error and repeat the Auto-Tuning process. |
Manual — Complete fault display index — page 264
Source reference: SIEP C71060618F, December 2016, physical PDF page 264. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
bUS. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CE. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CoF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF02. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF03. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF06. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF07. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF08. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF11. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF12. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF13. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF14. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF16. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF17. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF18. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF19. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF20 or CPF21. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF22. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF23. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF24. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
CPF25. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
dEv. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
dWAL. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
dWFL. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
E5. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
EF0. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
EF1 to EF7. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
Err. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
FbH. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
FbL. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
GF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
LF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
LF2. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
nSE. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oC. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oFA00. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oFA01. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oFA03. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oFA04. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oFA30 to oFA43. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oH. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oH1. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oH3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oH4. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oL1. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oL2. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oL3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oL4. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oL5. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oL7. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oPr. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
oS. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
ov. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
PF. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
PGo. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
rH. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
rr. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
SC. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
SEr. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
STo. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
UL3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
UL4. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
UL5. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
Uv1. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
Uv2. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
Uv3. Visible LED segment form is paired with the adjacent literal code; only printed code is transcribed, not reconstructed display geometry.
u Alarm and Error Displays
n Faults
When the drive detects a fault, the ALM indicator LEDs remain lit without flashing. If the LEDs flash, the drive has detected a minor fault or alarm. Refer to Minor Faults and Alarms on page 265 for more information. Conditions such as overvoltage or external faults can trip both faults and minor faults, therefore it is important to note whether the LEDs remain lit or if the LEDs flash.
Table 6.5 Fault Displays
Digital Operator Display | Name | Pg.
6.3 Drive Alarms, Faults, and Errors
Literal index only; named faults, page references and minor-fault output availability are distinct. Read complete fault cause and solution sections. LED segment geometry remains original-only.
Fault index | bUS
Fault index | CE
Fault index | CF
Fault index | CoF
Fault index | CPF02
Fault index | CPF03
Fault index | CPF06
Fault index | CPF07
Fault index | CPF08
Fault index | CPF11
Fault index | CPF12
Fault index | CPF13
Fault index | CPF14
Fault index | CPF16
Fault index | CPF17
Fault index | CPF18
Fault index | CPF19
Fault index | CPF20 or CPF21
Fault index | CPF22
Fault index | CPF23
Fault index | CPF24
Fault index | CPF25
Fault index | dEv
Fault index | dWAL
Fault index | dWFL
Fault index | E5
Fault index | EF0
Fault index | EF1 to EF7
Fault index | Err
Fault index | FbH
Fault index | FbL
Fault index | GF
Fault index | LF
Fault index | LF2
Fault index | nSE
Fault index | oC
Fault index | oFA00
Fault index | oFA01
Fault index | oFA03
Fault index | oFA04
Fault index | oFA30 to oFA43
Fault index | oH
Fault index | oH1
Fault index | oH3
Fault index | oH4
Fault index | oL1
Fault index | oL2
Fault index | oL3
Fault index | oL4
Fault index | oL5
Fault index | oL7
Fault index | oPr
Fault index | oS
Fault index | ov
Fault index | PF
Fault index | PGo
Fault index | rH
Fault index | rr
Fault index | SC
Fault index | SEr
Fault index | STo
Fault index | UL3
Fault index | UL4
Fault index | UL5
Fault index | Uv1
Fault index | Uv2
Fault index | Uv3
Fault index — PDF page 264
| Source row | Literal display code | Name | Page |
|---|---|---|---|
| 1 | bUS | Option Communication Error | 267 |
| 2 | CE | MEMOBUS/Modbus Communication Error | 267 |
| 3 | CF | Control Fault | 267 |
| 4 | CoF | Current Offset Fault | 267 |
| 5 | CPF02 | A/D Conversion Error | 268 |
| 6 | CPF03 | PWM Data Fault | 268 |
| 7 | CPF06 | Drive Specification Mismatch during Terminal Board or Control Board Replacement | 268 |
| 8 | CPF07 | Terminal Board Communication Fault | 268 |
| 9 | CPF08 | EEPROM Serial Communications Fault | 268 |
| 10 | CPF11 | RAM Fault | 268 |
| 11 | CPF12 | FLASH Memory Fault | 268 |
| 12 | CPF13 | Watchdog Circuit Exception | 269 |
| 13 | CPF14 | Control Circuit Fault | 269 |
| 14 | CPF16 | Clock Fault | 269 |
| 15 | CPF17 | Timing Fault | 269 |
| 16 | CPF18 | Control Circuit Fault | 269 |
| 17 | CPF19 | Control Circuit Fault | 269 |
| 18 | CPF20 or CPF21 | RAM Fault | 269 |
| 19 | CPF20 or CPF21 | FLASH Memory Fault | 269 |
| 20 | CPF20 or CPF21 | Watchdog Circuit Exception | 269 |
| 21 | CPF20 or CPF21 | Clock Fault | 269 |
| 22 | CPF22 | A/D Conversion Error | 269 |
| 23 | CPF23 | PWM Feedback Data Fault | 269 |
| 24 | CPF24 | Drive Capacity Signal Fault | 270 |
| 25 | CPF25 | Terminal Board Not Connected | 270 |
| 26 | dEv | Excessive Speed Deviation (for Simple V/f with PG) | 270 |
| 27 | dWAL | DriveWorksEZ Program Error Output | 270 |
| 28 | dWFL | DriveWorksEZ Fault | 270 |
| 29 | E5 | MECHATROLINK Watchdog Timer Error | 270 |
| 30 | EF0 | Option External Fault | 270 |
| 31 | EF1 to EF7 | External Fault (input terminal S1 to S7) | 270 |
| 32 | Err | EEPROM Write Error | 271 |
| 33 | FbH | Excessive PID Feedback | 271 |
| 34 | FbL | PID Feedback Loss | 271 |
Fault index — PDF page 264
| Source row | Literal display code | Name | Page |
|---|---|---|---|
| 1 | GF | Ground Fault | 271 |
| 2 | LF | Output Phase Loss | 272 |
| 3 | LF2 | Current Imbalance | 272 |
| 4 | nSE | Node Setup Error | 272 |
| 5 | oC | Overcurrent | 272 |
| 6 | oFA00 | Option Card Connection Error | 273 |
| 7 | oFA01 | Option Unit Fault | 273 |
| 8 | oFA03 | Option Card Fault | 273 |
| 9 | oFA04 | Option Card Fault | 273 |
| 10 | oFA30 to oFA43 | Option Card Fault | 273 |
| 11 | oH | Heatsink Overheat | 274 |
| 12 | oH1 | Heatsink Overheat | 274 |
| 13 | oH3 | Motor Overheat 1 (PTC input) | 274 |
| 14 | oH4 | Motor Overheat 2 (PTC input) | 275 |
| 15 | oL1 | Motor Overload | 275 |
| 16 | oL2 | Drive Overload | 275 |
| 17 | oL3 | Overtorque Detection 1 | 276 |
| 18 | oL4 | Overtorque Detection 2 | 276 |
| 19 | oL5 | Mechanical Weakening Detection 1 | 276 |
| 20 | oL7 | High Slip Braking oL | 276 |
| 21 | oPr | Operator Connection Fault | 277 |
| 22 | oS | Overspeed (for Simple V/f with PG) | 277 |
| 23 | ov | Overvoltage | 277 |
| 24 | PF | Input Phase Loss | 278 |
| 25 | PGo | PG Disconnect (for Simple V/f with PG) | 278 |
| 26 | rH | Dynamic Braking Resistor | 278 |
| 27 | rr | Dynamic Braking Transistor | 279 |
| 28 | SC | IGBT Short Circuit | 279 |
| 29 | SEr | Too Many Speed Search Restarts | 279 |
| 30 | STo | Pull-Out Detection | 279 |
| 31 | UL3 | Undertorque Detection 1 | 279 |
| 32 | UL4 | Undertorque Detection 2 | 280 |
| 33 | UL5 | Mechanical Weakening Detection 2 | 280 |
| 34 | Uv1 | Undervoltage | 280 |
| 35 | Uv2 | Control Power Supply Undervoltage | 280 |
| 36 | Uv3 | Soft Charge Circuit Fault | 280 |
Manual — Minor-fault index and fault footnotes — page 265
Source reference: SIEP C71060618F, December 2016, physical PDF page 265. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
AEr. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
bb. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
bUS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CALL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CrST. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CyC. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
dEv. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
dnE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
dWAL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
E5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF0. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF1 to EF7. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
FbH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
FbL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Hbb. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
HbbF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
HCA. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
LT-1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
LT-2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
LT-3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
LT-4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oH2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oH3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oL3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oL4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oL5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
ov. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
PASS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
PGo. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
rUn. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
<1> Displayed as CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show CPF21. <2> Available in drive software versions PRG: 1020 and later. <3> Uv1 and Uv2 faults are not saved to the fault history
n Minor Faults and Alarms
When a minor fault or alarm occurs, the ALM LED flashes and the text display shows an alarm code. A fault has occurred if the text remains lit and does not flash. Refer to Alarm Detection on page 282. An overvoltage situation, for example, can trigger both faults and minor faults. It is therefore important to note whether the LEDs remain lit or if the LEDs flash.
Table 6.6 Minor Fault and Alarm Displays
Digital Operator Display | Name | Minor Fault Output (H2-□□ = 10) | Pg.
6.3 Drive Alarms, Faults, and Errors
Troubleshooting
Literal index only; named faults, page references and minor-fault output availability are distinct. Read complete fault cause and solution sections. LED segment geometry remains original-only.
Minor fault/alarm index | AEr
Minor fault/alarm index | bb
Minor fault/alarm index | bUS
Minor fault/alarm index | CALL
Minor fault/alarm index | CE
Minor fault/alarm index | CrST
Minor fault/alarm index | CyC
Minor fault/alarm index | dEv
Minor fault/alarm index | dnE
Minor fault/alarm index | dWAL
Minor fault/alarm index | E5
Minor fault/alarm index | EF
Minor fault/alarm index | EF0
Minor fault/alarm index | EF1 to EF7
Minor fault/alarm index | FbH
Minor fault/alarm index | FbL
Minor fault/alarm index | Hbb
Minor fault/alarm index | HbbF
Minor fault/alarm index | HCA
Minor fault/alarm index | LT-1
Minor fault/alarm index | LT-2
Minor fault/alarm index | LT-3
Minor fault/alarm index | LT-4
Minor fault/alarm index | oH
Minor fault/alarm index | oH2
Minor fault/alarm index | oH3
Minor fault/alarm index | oL3
Minor fault/alarm index | oL4
Minor fault/alarm index | oL5
Minor fault/alarm index | oS
Minor fault/alarm index | ov
Minor fault/alarm index | PASS
Minor fault/alarm index | PGo
Minor fault/alarm index | rUn
Minor fault/alarm index — PDF page 265
| Source row | Literal display code | Name | Minor Fault Output (H2-□□=10) | Page |
|---|---|---|---|---|
| 1 | AEr | Station Address Setting Error (CC-Link, CANopen, MECHATROLINK) | YES | 282 |
| 2 | bb | Drive Baseblock | No output | 282 |
| 3 | bUS | Option Card Communications Error | YES | 282 |
| 4 | CALL | Serial Communication Transmission Error | YES | 282 |
| 5 | CE | MEMOBUS/Modbus Communication Error | YES | 283 |
| 6 | CrST | Can Not Reset | YES | 283 |
| 7 | CyC | MECHATROLINK Comm. Cycle Setting Error | YES | 283 |
| 8 | dEv | Excessive Speed Deviation (for Simple V/f with PG) | YES | 283 |
| 9 | dnE | Drive Disabled | YES | 284 |
| 10 | dWAL | DriveWorksEZ Alarm | YES | 270 |
| 11 | E5 | MECHATROLINK Watchdog Timer Error | YES | 284 |
| 12 | EF | Run Command Input Error | YES | 284 |
| 13 | EF0 | Option Card External Fault | YES | 284 |
| 14 | EF1 to EF7 | External Fault (input terminal S1 to S7) | YES | 284 |
| 15 | FbH | Excessive PID Feedback | YES | 285 |
| 16 | FbL | PID Feedback Loss | YES | 285 |
| 17 | Hbb | Safe Disable Signal Input | YES | 285 |
| 18 | HbbF | Safe Disable Signal Input | YES | 285 |
| 19 | HCA | Current Alarm | YES | 285 |
| 20 | LT-1 | Cooling Fan Maintenance Alarm | No output <1> | 286 |
| 21 | LT-2 | Capacitor Maintenance Alarm | No output <1> | 286 |
| 22 | LT-3 | Soft Charge Bypass Relay Maintenance Time | No output <1> | 286 |
| 23 | LT-4 | IGBT Maintenance Time (50%) | No output <1> | 286 |
| 24 | oH | Heatsink Overheat | YES | 286 |
| 25 | oH2 | Drive Overheat | YES | 287 |
| 26 | oH3 | Motor Overheat | YES | 287 |
| 27 | oL3 | Overtorque 1 | YES | 287 |
| 28 | oL4 | Overtorque 2 | YES | 287 |
| 29 | oL5 | Mechanical Weakening Detection 1 | YES | 288 |
| 30 | oS | Overspeed (for Simple V/f with PG) | YES | 288 |
| 31 | ov | Overvoltage | YES | 288 |
| 32 | PASS | MEMOBUS/Modbus Test Mode Complete | No output | 288 |
| 33 | PGo | PG Disconnect (for Simple V/f with PG) | YES | 288 |
| 34 | rUn | During Run 2, Motor Switch Command Input | YES | 289 |
Manual — Minor, operation and tuning error indices — page 266
Source reference: SIEP C71060618F, December 2016, physical PDF page 266. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
SE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
TrPC. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
UL3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
UL4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
UL5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Uv. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE01. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE02. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE04. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE05. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE07. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE08. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE09. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE10. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE11. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oPE13. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
End1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
End2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
End3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-01. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-02. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-04. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-05. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-08. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-09. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-11. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Er-12. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display | Name | Minor Fault Output (H2-□□ = 10) | Pg.
<1> Output when H2-□□ = F
n Operation Errors
Table 6.7 Operation Error Displays
Digital Operator Display | Name | Pg.
n Auto-Tuning Errors
Table 6.8 Auto-Tuning Error Displays
6.3 Drive Alarms, Faults, and Errors
Literal index only; named faults, page references and minor-fault output availability are distinct. Read complete fault cause and solution sections. LED segment geometry remains original-only.
Minor fault/alarm index | SE
Minor fault/alarm index | TrPC
Minor fault/alarm index | UL3
Minor fault/alarm index | UL4
Minor fault/alarm index | UL5
Minor fault/alarm index | Uv
Operation error index | oPE01
Operation error index | oPE02
Operation error index | oPE03
Operation error index | oPE04
Operation error index | oPE05
Operation error index | oPE07
Operation error index | oPE08
Operation error index | oPE09
Operation error index | oPE10
Operation error index | oPE11
Operation error index | oPE13
Auto-Tuning error index | End1
Auto-Tuning error index | End2
Auto-Tuning error index | End3
Auto-Tuning error index | Er-01
Auto-Tuning error index | Er-02
Auto-Tuning error index | Er-03
Auto-Tuning error index | Er-04
Auto-Tuning error index | Er-05
Auto-Tuning error index | Er-08
Auto-Tuning error index | Er-09
Auto-Tuning error index | Er-11
Auto-Tuning error index | Er-12
Minor fault/alarm index — PDF page 266
| Source row | Literal display code | Name | Minor Fault Output (H2-□□=10) | Page |
|---|---|---|---|---|
| 1 | SE | MEMOBUS/Modbus Test Mode Fault | YES | 289 |
| 2 | TrPC | IGBT Maintenance Time (90%) | YES | 289 |
| 3 | UL3 | Undertorque 1 | YES | 289 |
| 4 | UL4 | Undertorque 2 | YES | 289 |
| 5 | UL5 | Mechanical Weakening Detection 2 | YES | 280 |
| 6 | Uv | Undervoltage | YES | 290 |
Operation error index — PDF page 266
| Source row | Literal display code | Name | Page |
|---|---|---|---|
| 1 | oPE01 | Drive Unit Setting Error | 291 |
| 2 | oPE02 | Parameter Setting Range Error | 291 |
| 3 | oPE03 | Multi-Function Input Setting Error | 291 |
| 4 | oPE04 | Terminal Board Mismatch Error | 292 |
| 5 | oPE05 | Run Command Selection Error | 292 |
| 6 | oPE07 | Multi-Function Analog Input Selection Error | 292 |
Operation error index — PDF page 266
| Source row | Literal display code | Name | Page |
|---|---|---|---|
| 1 | oPE08 | Parameter Selection Error | 293 |
| 2 | oPE09 | PID Control Selection Error | 293 |
| 3 | oPE10 | V/f Data Setting Error | 294 |
| 4 | oPE11 | Carrier Frequency Setting Error | 294 |
| 5 | oPE13 | Pulse Train Monitor Selection Error | 294 |
Auto-Tuning error index — PDF page 266
| Source row | Literal display code | Name | Page |
|---|---|---|---|
| 1 | End1 | Excessive V/f Setting | 295 |
| 2 | End2 | Motor Iron Core Saturation Coefficient Error | 295 |
| 3 | End3 | Rated Current Setting Alarm | 295 |
| 4 | Er-01 | Motor Data Error | 295 |
| 5 | Er-02 | Alarm | 295 |
| 6 | Er-03 | STOP button Input | 296 |
Auto-Tuning error index — PDF page 266
| Source row | Literal display code | Name | Page |
|---|---|---|---|
| 1 | Er-04 | Line-to-Line Resistance Error | 296 |
| 2 | Er-05 | No-Load Current Error | 296 |
| 3 | Er-08 | Rated Slip Error | 296 |
| 4 | Er-09 | Acceleration Error | 296 |
| 5 | Er-11 | Motor Speed Error | 296 |
| 6 | Er-12 | Current Detection Error | 296 |
Manual — Communication and control faults — page 267
Source reference: SIEP C71060618F, December 2016, physical PDF page 267. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
bUS. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CoF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
6.4 Fault Detection
u Fault Displays, Causes, and Possible Solutions
Table 6.9 Detailed Fault Displays, Causes, and Possible Solutions
Digital Operator Display Fault Name
Cause Possible Solution
Troubleshooting
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
bUS fault definition | bUS
Fault code scope bUS. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
bUS causes and possible solutions | No signal received from the PLC.
bUS causes and possible solutions | The communication cable is faulty or a short circuit exists.
bUS causes and possible solutions | A communications data error occurred due to noise.
bUS causes and possible solutions | The option card is damaged.
bUS causes and possible solutions | The option card is not properly connected to the drive.
CE fault definition | CE
Fault code scope CE. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CE causes and possible solutions | Faulty communications wiring, or a short circuit exists.
CE causes and possible solutions | A communications data error occurred due to noise.
CF fault definition | CF
Fault code scope CF. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CF causes and possible solutions | Motor parameters are not set properly.
CF causes and possible solutions | Torque limit is too low.
CF causes and possible solutions | Load inertia is too big.
CoF fault definition | CoF
bUS fault definition — PDF page 267
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | bUS | Option Communication Error |
| 2 | bUS | • After establishing initial communication, the connection was lost. • Only detected when the run command frequency reference is assigned to an option card. |
bUS causes and possible solutions — PDF page 267
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | No signal received from the PLC. | • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed. |
| 2 | The communication cable is faulty or a short circuit exists. | • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed. |
| 3 | A communications data error occurred due to noise. | • Check the various options available to minimize the effects of noise. • Counteract noise in control circuit, main circuit, and ground wiring. • Ensure that other equipment such as switches or relays do not cause noise and use surge suppressors if required. • Use cables recommended by Yaskawa or another type of shielded line. Ground the shield on the controller side or on the drive input power side. • Separate all wiring for communications devices from drive input power lines. Install an EMC noise filter to the input side of the drive input power. |
| 4 | The option card is damaged. | • Replace the option card if there are no problems with the wiring and the error continues to occur. |
| 5 | The option card is not properly connected to the drive. | • The connector pins on the option card are not properly lined up with the connector pins on the drive. • Reinstall the option card. |
CE fault definition — PDF page 267
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CE | MEMOBUS/Modbus Communication Error |
| 2 | CE | Control data was not received for the CE detection time set to H5-09. |
CE causes and possible solutions — PDF page 267
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Faulty communications wiring, or a short circuit exists. | • Check for faulty wiring. • Correct the wiring. • Check for loose wiring and short circuits. Repair as needed. |
| 2 | A communications data error occurred due to noise. | • Check the various options available to minimize the effects of noise. • Counteract noise in control circuit, main circuit, and ground wiring. • Use Yaskawa-recommended cables, or another type of shielded line. Ground the shield on the controller side or on the drive input power side. • Ensure that other equipment such as switches or relays do not cause noise and use surge suppressors if required. • Separate all wiring for communications devices from drive input power lines. Install an EMC noise filter to the input side of the drive input power. |
CF fault definition — PDF page 267
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CF | Control Fault |
| 2 | CF | A torque limit was reached continuously for three seconds or longer during a ramp to stop while in Open Loop Vector Control. |
CF causes and possible solutions — PDF page 267
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor parameters are not set properly. | Check the motor parameter settings and repeat Auto-Tuning. |
| 2 | Torque limit is too low. | Set the torque limit to the most appropriate setting (L7-01 through L7-04). |
| 3 | Load inertia is too big. | • Adjust the deceleration time (C1-02, -04, -06, -08). • Set the frequency to the minimum value and interrupt the run command when the drive finishes decelerating. |
CoF fault definition — PDF page 267
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CoF | Current Offset Fault |
| 2 | CoF | The current sensor is damaged or there was residual induction current in the motor (e.g., during sudden deceleration or when coasting) when the drive attempted to start the motor. |
Manual — Current offset and control-board faults — page 268
Source reference: SIEP C71060618F, December 2016, physical PDF page 268. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
CPF02. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF06. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF07. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF08. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF11. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF12. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.
CoF continued from PDF267 causes and possible solutions | Due to residual induction current in the motor when the drive attempted to start the motor, the drive attempted to adjust the current offset value beyond the allowable range.
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
CPF02 fault definition | CPF02
Fault code scope CPF02. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF02 causes and possible solutions | Control circuit is damaged.
CPF02 causes and possible solutions | Control circuit terminals have shorted out (+V, AC).
CPF02 causes and possible solutions | Control terminal input current has exceeded allowable levels.
CPF03 fault definition | CPF03
Fault code scope CPF03. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF03 causes and possible solutions | Drive hardware is damaged.
CPF06 fault definition | CPF06
Fault code scope CPF06. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF06 causes and possible solutions | Control circuit is damaged.
CPF06 causes and possible solutions | The power supply was switched off when parameters were written (e.g., using a communications option card).
CPF07 fault definition | CPF07
Fault code scope CPF07. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF07 causes and possible solutions | There is a fault connection between the terminal board and control board.
CPF08 fault definition | CPF08
Fault code scope CPF08. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF08 causes and possible solutions | Terminal board or control board is not connected properly.
CPF11 fault definition | CPF11
Fault code scope CPF11. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF11 causes and possible solutions | Hardware is damaged.
CPF12 fault definition | CPF12
Fault code scope CPF12. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF12 causes and possible solutions | Hardware is damaged.
CoF continued from PDF267 causes and possible solutions — PDF page 268
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Due to residual induction current in the motor when the drive attempted to start the motor, the drive attempted to adjust the current offset value beyond the allowable range. | • Create a motor restart sequence that allows enough time for the residual induction voltage to dissipate. • Enable Speed Search at start (b3-01 = 1). Use the multi-function terminals to execute External Speed Search 1 and 2 (H1-□□ = 61 or 62). Note: When using a PM motor, both External Speed Search 1 and 2 perform the same operation. |
CPF02 fault definition — PDF page 268
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF02 | A/D Conversion Error |
| 2 | CPF02 | An A/D conversion error occurred. |
CPF02 causes and possible solutions — PDF page 268
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Control circuit is damaged. | Cycle power to the drive. If the problem continues, replace the drive. |
| 2 | Control circuit terminals have shorted out (+V, AC). | • Check for wiring errors along the control circuit terminals. • Correct the wiring. |
| 3 | Control circuit terminals have shorted out (+V, AC). | Check the resistance of the speed potentiometer and related wiring. |
| 4 | Control terminal input current has exceeded allowable levels. | • Check the input current. • Reduce the current input to control circuit terminal (+V) to 20 mA. |
CPF03 fault definition — PDF page 268
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF03 | PWM Data Error |
| 2 | CPF03 | There is a problem with the PWM data. |
CPF03 causes and possible solutions — PDF page 268
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Drive hardware is damaged. | Replace the drive. |
CPF06 fault definition — PDF page 268
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF06 | EEPROM Data Error |
| 2 | CPF06 | There is an error in the data saved to EEPROM. |
CPF06 causes and possible solutions — PDF page 268
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Control circuit is damaged. | Cycle power to the drive. If the problem continues, replace the drive. |
| 2 | The power supply was switched off when parameters were written (e.g., using a communications option card). | • Cycle power to the drive and check operation again. • Initialize the drive using A1-03. • If the problem persists after initializing the drive, replace the drive. |
CPF07 fault definition — PDF page 268
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF07 | Terminal Board Communications Error |
| 2 | CPF07 | A communication error occurred at the terminal board. |
CPF07 causes and possible solutions — PDF page 268
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | There is a fault connection between the terminal board and control board. | Turn the power off and reconnect the control circuit terminals. |
CPF08 fault definition — PDF page 268
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF08 | EEPROM Serial Communication Fault |
| 2 | CPF08 | EEPROM communications are not functioning properly. |
CPF08 causes and possible solutions — PDF page 268
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Terminal board or control board is not connected properly. | Turn the power off and check the control terminal connections. |
CPF11 fault definition — PDF page 268
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF11 | RAM Fault |
CPF11 causes and possible solutions — PDF page 268
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Hardware is damaged. | Replace the drive. |
CPF12 fault definition — PDF page 268
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF12 | FLASH Memory Fault |
| 2 | CPF12 | Problem with the ROM (FLASH memory). |
Manual — CPU and internal drive faults — page 269
Source reference: SIEP C71060618F, December 2016, physical PDF page 269. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
CPF13. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF14. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF16. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF17. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF18. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF19. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF20 or CPF21. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF22. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF23. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Troubleshooting
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
CPF13 fault definition | CPF13
Fault code scope CPF13. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF13 causes and possible solutions | Hardware is damaged.
CPF14 fault definition | CPF14
Fault code scope CPF14. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF14 causes and possible solutions | Hardware is damaged.
CPF16 fault definition | CPF16
Fault code scope CPF16. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF16 causes and possible solutions | Hardware is damaged.
CPF17 fault definition | CPF17
Fault code scope CPF17. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF17 causes and possible solutions | Hardware is damaged.
CPF18 fault definition | CPF18
Fault code scope CPF18. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF18 causes and possible solutions | Hardware is damaged.
CPF19 fault definition | CPF19
Fault code scope CPF19. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF19 causes and possible solutions | Hardware is damaged.
CPF20 or CPF21 fault definition | CPF20 or CPF21
Fault code scope CPF20 or CPF21. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF20 or CPF21 causes and possible solutions | Hardware is damaged.
CPF22 fault definition | CPF22
Fault code scope CPF22. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF22 causes and possible solutions | Control circuit is damaged.
CPF23 fault definition | CPF23
CPF13 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF13 | Watchdog Circuit Exception |
| 2 | CPF13 | Self-diagnostics problem. |
CPF13 causes and possible solutions — PDF page 269
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Hardware is damaged. | Replace the drive. |
CPF14 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF14 | Control Circuit Fault |
| 2 | CPF14 | CPU error (CPU operates incorrectly due to noise, etc.) |
CPF16 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF16 | Clock Fault |
| 2 | CPF16 | Standard clock error. |
CPF17 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF17 | Timing Fault |
| 2 | CPF17 | A timing error occurred during an internal process. |
CPF18 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF18 | Control Circuit Fault |
| 2 | CPF18 | CPU error. Non-Maskable Interrupt (An unusual interrupt was triggered by noise, etc.) |
CPF19 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF19 | Control Circuit Fault |
| 2 | CPF19 | CPU error (Manual reset due to noise, etc.) |
CPF20 or CPF21 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF20 or CPF21 | One of the following faults occurred: RAM fault, FLASH memory error, watchdog circuit exception, clock error |
| 2 | CPF20 or CPF21 | • RAM fault. • FLASH memory error (ROM error). • Watchdog circuit exception (self-diagnostic error). • Clock error. |
CPF22 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF22 | A/D Conversion Fault |
| 2 | CPF22 | A/D conversion error. |
CPF22 causes and possible solutions — PDF page 269
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Control circuit is damaged. | • Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 298. • If the problem continues, replace the drive. |
CPF23 fault definition — PDF page 269
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF23 | PWM Feedback Fault |
| 2 | CPF23 | PWM feedback error. |
Manual — Capacity, board, option and external faults — page 270
Source reference: SIEP C71060618F, December 2016, physical PDF page 270. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
CPF24. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
CPF25. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
dEv. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
dWFL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
dWAL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
E5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF0. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name Cause Possible Solution
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.
CPF23 continued from PDF269 causes and possible solutions | Hardware is damaged.
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
CPF24 fault definition | CPF24
Fault code scope CPF24. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF24 causes and possible solutions | Hardware is damaged.
CPF25 fault definition | CPF25
Fault code scope CPF25. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
CPF25 causes and possible solutions | Terminal board is not connected correctly.
dEv fault definition | dEv
Fault code scope dEv. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
dEv causes and possible solutions | Load is too heavy.
dEv causes and possible solutions | Acceleration and deceleration times are set too short.
dEv causes and possible solutions | The load is locked up.
dEv causes and possible solutions | Parameters are not set appropriately.
dEv causes and possible solutions | Motor brake engaged.
dWFL / dWAL fault definition | dWFL
dWFL / dWAL fault definition | dWAL
Fault code scope dWFL / dWAL. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
dWFL / dWAL causes and possible solutions | Fault output by DriveWorksEZ
E5 fault definition | E5
Fault code scope E5. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
E5 causes and possible solutions | Data has not been received from the PLC, triggering the watchdog timer.
EF0 fault definition | EF0
Fault code scope EF0. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
EF0 causes and possible solutions | An external fault was received from the PLC with other than F6-03 = 3 “alarm only” (the drive continued to run after external fault).
EF0 causes and possible solutions | Problem with the PLC program.
EF1 / EF2 / EF3 fault definition | EF1
EF1 / EF2 / EF3 fault definition | EF2
EF1 / EF2 / EF3 fault definition | EF3
CPF23 continued from PDF269 causes and possible solutions — PDF page 270
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Hardware is damaged. | Replace the drive. |
CPF24 fault definition — PDF page 270
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF24 | Drive Capacity Signal Fault |
| 2 | CPF24 | Entered a capacity that does not exist. (Checked when the drive is powered up.) |
CPF25 fault definition — PDF page 270
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | CPF25 | Terminal Board Not Connected |
CPF25 causes and possible solutions — PDF page 270
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Terminal board is not connected correctly. | Reconnect the terminal board to the connector on the drive, then cycle the power to the drive. |
dEv fault definition — PDF page 270
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | dEv | Speed Deviation (for Simple V/f with PG) |
| 2 | dEv | According to the pulse input (RP), the speed deviation is greater than the setting in F1-10 for longer than the time set to F1-11. |
dEv causes and possible solutions — PDF page 270
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Load is too heavy. | Reduce the load. |
| 2 | Acceleration and deceleration times are set too short. | Increase the acceleration and deceleration times (C1-01 through C1-08). |
| 3 | The load is locked up. | Check the machine. |
| 4 | Parameters are not set appropriately. | Check the settings of parameters F1-10 and F1-11. |
| 5 | Motor brake engaged. | Ensure the motor brake releases properly. |
dWFL / dWAL fault definition — PDF page 270
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | dWFL | DriveWorksEZ Fault |
| 2 | dWAL | DriveWorksEZ Program Error Output |
dWFL / dWAL causes and possible solutions — PDF page 270
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Fault output by DriveWorksEZ | Correct the cause of the fault. |
E5 fault definition — PDF page 270
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | E5 | MECHATROLINK Watchdog Timer Error |
| 2 | E5 | The watchdog timed out. |
E5 causes and possible solutions — PDF page 270
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Data has not been received from the PLC, triggering the watchdog timer. | Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and proceed to phase 3. |
EF0 fault definition — PDF page 270
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | EF0 | Option Card External Fault |
| 2 | EF0 | An external fault condition is present. |
EF0 causes and possible solutions — PDF page 270
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | An external fault was received from the PLC with other than F6-03 = 3 “alarm only” (the drive continued to run after external fault). | • Remove the cause of the external fault. • Remove the external fault input from the PLC. |
| 2 | Problem with the PLC program. | Check the PLC program and correct problems. |
EF1 / EF2 / EF3 fault definition — PDF page 270
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | EF1 | External Fault (input terminal S1) |
| 2 | EF1 | External fault at multi-function input terminal S1. |
| 3 | EF2 | External Fault (input terminal S2) |
| 4 | EF2 | External fault at multi-function input terminal S2. |
| 5 | EF3 | External Fault (input terminal S3) |
| 6 | EF3 | External fault at multi-function input terminal S3. |
Manual — External, EEPROM, PID and ground faults — page 271
Source reference: SIEP C71060618F, December 2016, physical PDF page 271. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
EF4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF5. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF6. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
EF7. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Err. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
FbH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
FbL. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
GF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Troubleshooting
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
EF4 / EF5 / EF6 / EF7 fault definition | EF4
EF4 / EF5 / EF6 / EF7 fault definition | EF5
EF4 / EF5 / EF6 / EF7 fault definition | EF6
EF4 / EF5 / EF6 / EF7 fault definition | EF7
Fault code scope EF4 / EF5 / EF6 / EF7. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
EF4 / EF5 / EF6 / EF7 causes and possible solutions | An external device has tripped an alarm function.
EF4 / EF5 / EF6 / EF7 causes and possible solutions | Wiring is incorrect.
EF4 / EF5 / EF6 / EF7 causes and possible solutions | Incorrect setting of multi-function contact inputs.
Err fault definition | Err
Fault code scope Err. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
Err causes and possible solutions | -
FbH fault definition | FbH
Fault code scope FbH. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
FbH causes and possible solutions | Parameters are not set appropriately.
FbH causes and possible solutions | Wiring for PID feedback is incorrect.
FbH causes and possible solutions | There is a problem with the feedback sensor.
FbL fault definition | FbL
Fault code scope FbL. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
FbL causes and possible solutions | Parameters are not set appropriately.
FbL causes and possible solutions | Wiring for PID feedback is incorrect.
FbL causes and possible solutions | There is a problem with the feedback sensor.
GF fault definition | GF
Fault code scope GF. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
GF causes and possible solutions | Motor insulation is damaged.
EF4 / EF5 / EF6 / EF7 fault definition — PDF page 271
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | EF4 | External Fault (input terminal S4) |
| 2 | EF4 | External fault at multi-function input terminal S4. |
| 3 | EF5 | External Fault (input terminal S5) |
| 4 | EF5 | External fault at multi-function input terminal S5. |
| 5 | EF6 | External Fault (input terminal S6) |
| 6 | EF6 | External fault at multi-function input terminal S6. |
| 7 | EF7 | External Fault (input terminal S7) |
| 8 | EF7 | External fault at multi-function input terminal S7 |
EF4 / EF5 / EF6 / EF7 causes and possible solutions — PDF page 271
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | An external device has tripped an alarm function. | Remove the cause of the external fault and reset the fault. |
| 2 | Wiring is incorrect. | • Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1-□□ = 20 to 2F). • Reconnect the signal line. |
| 3 | Incorrect setting of multi-function contact inputs. | • Check if the unused terminals set for H1-□□ = 20 to 2F (External Fault). • Change the terminal settings. |
Err fault definition — PDF page 271
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | Err | EEPROM Write Error |
| 2 | Err | Data does not match the EEPROM being written to. |
Err causes and possible solutions — PDF page 271
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | - | • Press the ENTER button. • Correct the parameter settings. • Cycle power to the drive. Refer to Diagnosing and Resetting Faults on page 298. |
FbH fault definition — PDF page 271
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | FbH | Excessive PID Feedback |
| 2 | FbH | PID feedback input is greater than the level set b5-36 for longer than the time set to b5-37. Set b5-12 to 2 or 5 to enable fault detection. |
FbH causes and possible solutions — PDF page 271
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Parameters are not set appropriately. | Check the settings of parameters b5-36 and b5-37. |
| 2 | Wiring for PID feedback is incorrect. | Correct the wiring. |
| 3 | There is a problem with the feedback sensor. | • Check the sensor on the control side. • Replace the sensor if damaged. |
FbL fault definition — PDF page 271
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | FbL | PID Feedback Loss |
| 2 | FbL | This fault occurs when PID Feedback Loss Detection is programmed to fault (b5-12 = 2) and the PID Feedback < PID Feedback Loss Detection Level (b5-13) for the PID Feedback Loss Detection Time (b5-14). |
FbL causes and possible solutions — PDF page 271
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Parameters are not set appropriately. | Check the settings of parameters b5-13 and b5-14. |
| 2 | Wiring for PID feedback is incorrect. | Correct the wiring. |
| 3 | There is a problem with the feedback sensor. | Check the sensor on the controller side. If damaged, replace the sensor. |
GF fault definition — PDF page 271
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | GF | Ground Fault |
| 2 | GF | • Current shorted to ground exceeded 50% of rated current on output side of the drive. • Setting L8-09 to 1 enables ground fault detection in models 2A0020 to 2A0069 and 4A0011 to 4A0038. |
GF causes and possible solutions — PDF page 271
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor insulation is damaged. | • Check the insulation resistance of the motor. • Replace the motor. |
Manual — Ground, phase, node and overcurrent faults — page 272
Source reference: SIEP C71060618F, December 2016, physical PDF page 272. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
LF. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
LF2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
nSE. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oC. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.
GF continued from PDF271 causes and possible solutions | A damaged motor cable is creating a short circuit.
GF continued from PDF271 causes and possible solutions | The leakage current at the drive output is too high.
GF continued from PDF271 causes and possible solutions | The drive started to run during Current Offset Fault or while coasting to a stop.
GF continued from PDF271 causes and possible solutions | Hardware problem.
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
LF fault definition | LF
Fault code scope LF. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
LF causes and possible solutions | The output cable is disconnected.
LF causes and possible solutions | The motor winding is damaged.
LF causes and possible solutions | The output terminal is loose.
LF causes and possible solutions | The motor being used is less than 5% of the drive rated current.
LF causes and possible solutions | An output transistor is damaged.
LF causes and possible solutions | A single-phase motor is being used.
LF2 fault definition | LF2
Fault code scope LF2. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
LF2 causes and possible solutions | Phase loss has occurred on the output side of the drive.
LF2 causes and possible solutions | Terminal wires on the output side of the drive are loose.
LF2 causes and possible solutions | No signal displays from the gate driver board.
LF2 causes and possible solutions | Motor impedance or motor phases are uneven.
nSE fault definition | nSE
Fault code scope nSE. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
nSE causes and possible solutions | The node setup terminal closed during Run.
nSE causes and possible solutions | A Run command was issued while the node setup function was active.
oC fault definition | oC
Fault code scope oC. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oC causes and possible solutions | The motor has been damaged due to overheating or the motor insulation is damaged.
GF continued from PDF271 causes and possible solutions — PDF page 272
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | A damaged motor cable is creating a short circuit. | • Check the motor cable. • Remove the short circuit and turn the power back on. |
| 2 | A damaged motor cable is creating a short circuit. | • Check the resistance between the cable and the ground terminal ⏚. • Replace the cable. |
| 3 | The leakage current at the drive output is too high. | • Reduce the carrier frequency. • Reduce the amount of stray capacitance. |
| 4 | The drive started to run during Current Offset Fault or while coasting to a stop. | • The value set exceeds the allowable setting range while the drive automatically adjusts the current offset (this happens only attempting to restart a PM motor that is coasting to stop). • Enable Speed Search at start (b3-01 = 1). • Perform Speed Search 1 or 2 (H1-□□ = 61 or 62) via one of the external terminals. Note: Speed Search 1 and 2 are the same when using OLV/PM control mode. |
| 5 | Hardware problem. | • Replace the drive. |
LF fault definition — PDF page 272
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | LF | Output Phase Loss |
| 2 | LF | • Phase loss on the output side of the drive. • Phase Loss Detection is enabled when L8-07 is set to 1 or 2. |
LF causes and possible solutions — PDF page 272
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The output cable is disconnected. | • Check for wiring errors and ensure the output cable is connected properly. • Correct the wiring. |
| 2 | The motor winding is damaged. | • Check the resistance between motor lines. • Replace the motor if the winding is damaged. |
| 3 | The output terminal is loose. | • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Size and Torque Specifications on page 66. |
| 4 | The motor being used is less than 5% of the drive rated current. | Check the drive and motor capacities. |
| 5 | An output transistor is damaged. | Replace the drive. |
| 6 | A single-phase motor is being used. | The drive being used cannot operate a single phase motor. |
LF2 fault definition — PDF page 272
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | LF2 | Output current imbalance |
| 2 | LF2 | One or more of the phases in the output current is lost. |
LF2 causes and possible solutions — PDF page 272
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Phase loss has occurred on the output side of the drive. | • Check for faulty wiring or poor connections on the output side of the drive. • Correct the wiring. |
| 2 | Terminal wires on the output side of the drive are loose. | Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Size and Torque Specifications on page 66. |
| 3 | No signal displays from the gate driver board. | Replace the drive. Contact Yaskawa for assistance. |
| 4 | Motor impedance or motor phases are uneven. | • Measure the line-to-line resistance for each motor phase. Ensure all values are the same. • Replace the motor. Contact Yaskawa for assistance. |
nSE fault definition — PDF page 272
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | nSE | Node Setup Error |
| 2 | nSE | A terminal assigned to the node setup function closed during Run. |
nSE causes and possible solutions — PDF page 272
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The node setup terminal closed during Run. | • Check whether a Run command was accidentally entered via the terminals or from a comm. option unit. • Turn off the Run command when using the node setup function. |
| 2 | A Run command was issued while the node setup function was active. | • Check whether a Run command was accidentally entered via the terminals or from a comm. option unit. • Turn off the Run command when using the node setup function. |
oC fault definition — PDF page 272
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oC | Overcurrent |
| 2 | oC | Drive sensors have detected an output current greater than the specified overcurrent level. |
oC causes and possible solutions — PDF page 272
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The motor has been damaged due to overheating or the motor insulation is damaged. | • Check the insulation resistance. • Replace the motor. |
Manual — Overcurrent and option card faults — page 273
Source reference: SIEP C71060618F, December 2016, physical PDF page 273. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oFA00. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oFA01. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oFA03. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Troubleshooting
Continuation with misleading repeated source header Digital Operator Display/Fault Name. Actual physical columns read as Cause/Possible Solution, based on preceding page and adjacent rows. No inferred cause.
oC continued from PDF272 causes and possible solutions | One of the motor cables has shorted out or there is a grounding problem.
oC continued from PDF272 causes and possible solutions | The load is too heavy.
oC continued from PDF272 causes and possible solutions | The acceleration or deceleration times are too short.
oC continued from PDF272 causes and possible solutions | The drive is attempting to operate a specialized motor or a motor larger than the maximum size allowed.
oC continued from PDF272 causes and possible solutions | Magnetic contactor (MC) on the output side of the drive has turned on or off.
oC continued from PDF272 causes and possible solutions | V/f setting is not operating as expected.
oC continued from PDF272 causes and possible solutions | Excessive torque compensation.
oC continued from PDF272 causes and possible solutions | Drive fails to operate properly due to noise interference.
oC continued from PDF272 causes and possible solutions | Overexcitation gain is set too high.
oC continued from PDF272 causes and possible solutions | Run command applied while motor was coasting.
oC continued from PDF272 causes and possible solutions | The wrong motor code has been entered for in OLV/PM (Yaskawa motors only).
oC continued from PDF272 causes and possible solutions | The motor control method and motor do not match.
oC continued from PDF272 causes and possible solutions | The motor cable is too long
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
oFA00 fault definition | oFA00
Fault code scope oFA00. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oFA00 causes and possible solutions | The option card is incompatible with the drive.
oFA01 fault definition | oFA01
Fault code scope oFA01. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oFA01 causes and possible solutions | The option card is not connected properly to the drive.
oFA03 fault definition | oFA03
oC continued from PDF272 causes and possible solutions — PDF page 273
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | One of the motor cables has shorted out or there is a grounding problem. | • Check the motor cables. • Remove the short circuit and power the drive back up. |
| 2 | One of the motor cables has shorted out or there is a grounding problem. | • Check the resistance between the motor cables and the ground terminal ⏚. • Replace damaged cables. |
| 3 | The load is too heavy. | • Measure the current flowing into the motor. • Replace the drive with a larger capacity unit if the current value exceeds the rated current of the drive. • Determine if there is sudden fluctuation in the current level. • Reduce the load to avoid sudden changes in the current level or switch to a larger drive. |
| 4 | The acceleration or deceleration times are too short. | Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration time. If the right amount of torque cannot be set, make the following changes: • Increase the acceleration time (C1-01, C1-03, C1-05, C1-07) • Increase the S-curve characteristics (C2-01 through C2-04) • Increase the capacity of the drive. |
| 5 | The drive is attempting to operate a specialized motor or a motor larger than the maximum size allowed. | • Check the motor capacity. • Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the motor nameplate. |
| 6 | Magnetic contactor (MC) on the output side of the drive has turned on or off. | Set up the operation sequence so that the MC is not tripped while the drive is outputting current. |
| 7 | V/f setting is not operating as expected. | • Check the ratios between the voltage and frequency. • Set parameter E1-04 through E1-10 appropriately. Set E3-04 through E3-10 when using a second motor. • Lower the voltage if it is too high relative to the frequency. |
| 8 | Excessive torque compensation. | • Check the amount of torque compensation. • Reduce the torque compensation gain (C4-01) until there is no speed loss and less current. |
| 9 | Drive fails to operate properly due to noise interference. | • Review the possible solutions provided for handling noise interference. • Review the section on handling noise interference and check the control circuit lines, main circuit lines and ground wiring. |
| 10 | Overexcitation gain is set too high. | • Check if fault occurs simultaneously to overexcitation function operation. • Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain). |
| 11 | Run command applied while motor was coasting. | • Set b3-01 to 1 to enable Speed Search at Start. • Program the Speed Search command input through one of the multi-function contact input terminals (H1-□□ = “61” or “62”). |
| 12 | The wrong motor code has been entered for in OLV/PM (Yaskawa motors only). | Enter the correct motor code to E5-01 to indicate that a PM motor is connected. |
| 13 | The motor control method and motor do not match. | Check which motor control method the drive is set to in A1-02. • For IM motors, set A1-02 to 0 or 2. • For PM motors, set A1-02 to 5. |
| 14 | The motor cable is too long | Use a larger drive. |
oFA00 fault definition — PDF page 273
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oFA00 | Option Card Connection Error at Option Port CN5 |
| 2 | oFA00 | The option card is incompatible with the drive. |
oFA00 causes and possible solutions — PDF page 273
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The option card is incompatible with the drive. | Use a compatible option card. |
oFA01 fault definition — PDF page 273
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oFA01 | Option Card Fault |
| 2 | oFA01 | Replace the option card. |
oFA01 causes and possible solutions — PDF page 273
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The option card is not connected properly to the drive. | Turn the power off and reconnect the option card. |
oFA03 fault definition — PDF page 273
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oFA03 | Option Card Fault |
| 2 | oFA03 | Option card self-diagnostic error |
Manual — Option and heatsink/PTC faults — page 274
Source reference: SIEP C71060618F, December 2016, physical PDF page 274. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oFA04. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oFA30 to oFA43. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oH. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oH1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oH3. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
oFA04 / oFA30 to oFA43 fault definition | oFA04
oFA04 / oFA30 to oFA43 fault definition | oFA30 to oFA43
Fault code scope oFA04 / oFA30 to oFA43. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oFA04 / oFA30 to oFA43 causes and possible solutions | Option card or hardware is damaged.
oH fault definition | oH
Fault code scope oH. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oH causes and possible solutions | Surrounding temperature is too high.
oH causes and possible solutions | Load is too heavy.
oH causes and possible solutions | Internal cooling fan is stopped.
oH1 fault definition | oH1
Fault code scope oH1. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oH1 causes and possible solutions | Surrounding temperature is too high.
oH1 causes and possible solutions | Load is too heavy.
oH1 causes and possible solutions | The internal cooling fan has reached its performance life or has malfunctioned.
oH1 causes and possible solutions | Current flowing to control circuit terminal +V exceeded the tolerance level.
oH3 fault definition | oH3
Fault code scope oH3. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oH3 causes and possible solutions | Motor has overheated
oFA04 / oFA30 to oFA43 fault definition — PDF page 274
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oFA04 | Option Card Fault |
| 2 | oFA04 | An error occurred attempting to write to the option card memory. |
| 3 | oFA30 to oFA43 | Option Card Fault |
| 4 | oFA30 to oFA43 | Communication ID error |
oFA04 / oFA30 to oFA43 causes and possible solutions — PDF page 274
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Option card or hardware is damaged. | Replace the option card. Contact Yaskawa for consultation. |
oH fault definition — PDF page 274
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oH | Heatsink Overheat |
| 2 | oH | The temperature of the heatsink exceeded the value set to L8-02. Default value for L8-02 is determined by drive capacity (o2-04). |
oH causes and possible solutions — PDF page 274
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Surrounding temperature is too high. | • Check the temperature surrounding the drive. Verify temperature is within drive specifications. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool the surrounding area. • Remove anything near the drive that might be producing excessive heat. |
| 2 | Load is too heavy. | • Measure the output current. • Decrease the load. • Lower the carrier frequency in C6-02. |
| 3 | Internal cooling fan is stopped. | • After replacing the fan, set o4-03 to 0 to reset cooling fan maintenance. |
oH1 fault definition — PDF page 274
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oH1 | Overheat 1 (Heatsink Overheat) |
| 2 | oH1 | The temperature of the heatsink has exceeded 10 °C plus the default value of L8-02. |
oH1 causes and possible solutions — PDF page 274
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Surrounding temperature is too high. | • Check the temperature surrounding the drive. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool the surrounding area. • Remove anything near the drive that might be producing excessive heat. |
| 2 | Load is too heavy. | • Measure the output current. • Lower the carrier frequency (C6-02). • Reduce the load. |
| 3 | The internal cooling fan has reached its performance life or has malfunctioned. | • Check the maintenance time for the cooling fan (U4-04). • After replacing the fan, set o4-03 to 0 to reset cooling fan maintenance. |
| 4 | Current flowing to control circuit terminal +V exceeded the tolerance level. | • Check the current level of the terminal. • Set the current to the control circuit terminal to be 20 mA or less. |
oH3 fault definition — PDF page 274
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oH3 | Motor Overheat Alarm (PTC Input) |
| 2 | oH3 | • The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level. • Detection requires multi-function analog input H3-02 or H3-10 be set to E. |
oH3 causes and possible solutions — PDF page 274
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor has overheated | • Check the size of the load, the accel/decel times and the cycle times. • Decrease the load. • Increase the acceleration and deceleration times (C1-01 through C1-08). |
| 2 | Motor has overheated | • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. • Be careful not to lower E1-08 and E1-10 excessively, as this reduces load tolerance at low speeds. |
| 3 | Motor has overheated | • Check the motor-rated current. • Enter the motor-rated current as indicated on the motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system. |
Manual — PTC, motor overload and drive-overload definition — page 275
Source reference: SIEP C71060618F, December 2016, physical PDF page 275. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oH4. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oL1. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
oL2. Visible LED-segment rendering alongside the separately captured literal code. Segment geometry and graphical styling remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Troubleshooting
Separate name and description rows retained with exact same physical merged code. Repetition is source row association, not separate variants.
oH4 fault definition | oH4
Fault code scope oH4. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oH4 causes and possible solutions | Motor has overheated.
oL1 fault definition | oL1
Fault code scope oL1. Same-row cause/possible solution preserved. Merged cause text repeats only over actual source extent. All safety conditions on PDF258–259 apply; not an authorization to perform maintenance.
oL1 causes and possible solutions | Cycle times are too short during acceleration and deceleration.
oL1 causes and possible solutions | • Drive overloaded at low speeds. • Overload may occur at low speeds when using a general-purpose motor, even if operating within the rated current limitation.
oL1 causes and possible solutions | Although a special type of motor is being used, the motor protection selection is set for a general-purpose motor (L1-01 = 1).
oL1 causes and possible solutions | Voltage is too high for the V/f characteristics.
oL1 causes and possible solutions | The wrong motor-rated current is set to E2-01.
oL1 causes and possible solutions | The motor base frequency for the drive input power is set too low.
oL1 causes and possible solutions | Multiple motors are running off the same drive.
oL1 causes and possible solutions | The electrical thermal protection characteristics and motor overload characteristics do not match.
oL1 causes and possible solutions | The electrical thermal relay is operating at the wrong level.
oL1 causes and possible solutions | Motor overheated by overexcitation operation.
oL1 causes and possible solutions | Speed Search related parameters are not set to the proper values.
oL1 causes and possible solutions | Output current fluctuation due to input phase loss
oL2 fault definition | oL2
oH4 fault definition — PDF page 275
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oH4 | Motor Overheat Fault (PTC Input) |
| 2 | oH4 | • The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level. • Detection requires multi-function analog input H3-02 or H3-10 be set to E. |
oH4 causes and possible solutions — PDF page 275
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor has overheated. | • Check the size of the load, the accel/decel times and the cycle times. • Decrease the load. • Increase the acceleration and deceleration times (C1-01 through C1-08). |
| 2 | Motor has overheated. | • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds |
| 3 | Motor has overheated. | • Check the motor-rated current. • Enter the motor-rated current as indicated on the motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system. |
oL1 fault definition — PDF page 275
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oL1 | Motor Overload |
| 2 | oL1 | The electrothermal sensor tripped overload protection. Note: The U4-16 value must be less than 100 before oL1 can be reset. |
oL1 causes and possible solutions — PDF page 275
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Cycle times are too short during acceleration and deceleration. | Increase the acceleration and deceleration times (C1-01 through C1-08). |
| 2 | • Drive overloaded at low speeds. • Overload may occur at low speeds when using a general-purpose motor, even if operating within the rated current limitation. | • Reduce the load. • Increase the speed. • If the drive is supposed to operate at low speeds, either increase the motor capacity or use a motor specifically designed to operate with the drive. |
| 3 | Although a special type of motor is being used, the motor protection selection is set for a general-purpose motor (L1-01 = 1). | Set L1-01 to 2. |
| 4 | Voltage is too high for the V/f characteristics. | • Adjust the user set V/f patterns (E1-04 through E1-10). Parameters E1-08 and E1-10 may need to be reduced. • If E1-08 and E1-10 are set too high, there may be very little load tolerance at low speed. |
| 5 | The wrong motor-rated current is set to E2-01. | • Check the motor-rated current. • Enter the value written on the motor nameplate to parameter E2-01. |
| 6 | The motor base frequency for the drive input power is set too low. | • Check the rated frequency indicated on the motor nameplate. • Enter the rated frequency to E1-06 (Base Frequency). |
| 7 | Multiple motors are running off the same drive. | Set L1-01 to 0 to disable the Motor Protection function and install a thermal relay to each motor. |
| 8 | The electrical thermal protection characteristics and motor overload characteristics do not match. | • Check the motor characteristics. • Correct the value set to L1-01 (Motor Protection Function). • Install an external thermal relay. |
| 9 | The electrical thermal relay is operating at the wrong level. | • Check the current rating listed on the motor nameplate. • Check the value set for the motor-rated current (E2-01). |
| 10 | Motor overheated by overexcitation operation. | • Overexcitation increases the motor losses and the motor temperature. If applied too long, motor damage can occur. Prevent excessive overexcitation operation or apply proper cooling to the motor • Reduce the excitation deceleration gain (n3-13). • Set L3-04 (Stall Prevention during Deceleration) to a value other than 4. |
| 11 | Speed Search related parameters are not set to the proper values. | • Check values set to Speed Search related parameters. • Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively). • After Auto-Tuning, enable Speed Estimation Type Search (b3-24 = “1”). |
| 12 | Output current fluctuation due to input phase loss | Check the power supply for phase loss. |
oL2 fault definition — PDF page 275
| Source row | Literal display code | Source fault name or description |
|---|---|---|
| 1 | oL2 | Drive Overload |
| 2 | oL2 | The thermal sensor of the drive triggered overload protection. |
Manual — Drive overload, torque and high-slip faults — page 276
Source reference: SIEP C71060618F, December 2016, physical PDF page 276. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oL7. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name Cause Possible Solution
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
oL2 from PDF275 cause/solution continuation | Load is too heavy.
oL2 from PDF275 cause/solution continuation | Cycle times are too short during acceleration and deceleration.
oL2 from PDF275 cause/solution continuation | Voltage is too high for the V/f characteristics.
oL2 from PDF275 cause/solution continuation | Drive capacity is too small.
oL2 from PDF275 cause/solution continuation | Overload occurred when operating at low speeds.
oL2 from PDF275 cause/solution continuation | Excessive torque compensation.
oL2 from PDF275 cause/solution continuation | Speed Search related parameters are not set correctly.
oL2 from PDF275 cause/solution continuation | Output current fluctuation due to input phase loss
Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.
oL3 fault definition | oL3
Fault/error code scope: oL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oL3 fault causes and solutions | Parameter settings are not appropriate for the type of load.
oL3 fault causes and solutions | There is a fault on the machine side (e.g., the machine is locked up).
oL4 fault definition | oL4
Fault/error code scope: oL4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oL4 fault causes and solutions | Parameter settings are not appropriate for the type of load.
oL5 fault definition | oL5
Fault/error code scope: oL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oL5 fault causes and solutions | Overtorque occurred, triggering the mechanical weakening level set to L6-08.
oL7 fault definition | oL7
Fault/error code scope: oL7. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oL7 fault causes and solutions | Excessive load inertia.
oL7 fault causes and solutions | Motor is driven by the load.
oL7 fault causes and solutions | Something on the load side is restricting deceleration.
oL7 fault causes and solutions | The overload time during High-slip Braking is too short.
oL2 from PDF275 cause/solution continuation — PDF page 276
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Load is too heavy. | Reduce the load. |
| 2 | Cycle times are too short during acceleration and deceleration. | Increase the settings for the acceleration and deceleration times (C1-01 through C1-08). |
| 3 | Voltage is too high for the V/f characteristics. | • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. • Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds. |
| 4 | Drive capacity is too small. | Replace the drive with a larger model. |
| 5 | Overload occurred when operating at low speeds. | • Reduce the load when operating at low speeds. • Replace the drive with a model that is one frame size larger. • Lower the carrier frequency (C6-02). |
| 6 | Excessive torque compensation. | Reduce the torque compensation gain (C4-01) until there is no speed loss but less current. |
| 7 | Speed Search related parameters are not set correctly. | • Check the settings for all Speed Search related parameters. • Adjust the current used during Speed Search and the Speed Search deceleration time (b3-03 and b3-02 respectively). • After Auto-Tuning the drive, enable the Speed Search Estimation Type (b3-24 = “1”). |
| 8 | Output current fluctuation due to input phase loss | Check the power supply for phase loss. |
oL3 fault definition — PDF page 276
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oL3 | Overtorque Detection 1 |
| 2 | oL3 | The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03). |
oL3 fault causes and solutions — PDF page 276
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Parameter settings are not appropriate for the type of load. | Check the settings of parameters L6-02 and L6-03. |
| 2 | There is a fault on the machine side (e.g., the machine is locked up). | Check the status of the load. Remove the cause of the fault. |
oL4 fault definition — PDF page 276
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oL4 | Overtorque Detection 2 |
| 2 | oL4 | The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable time (L6-06). |
oL4 fault causes and solutions — PDF page 276
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Parameter settings are not appropriate for the type of load. | Check the settings of parameters L6-05 and L6-06. |
oL5 fault definition — PDF page 276
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oL5 | Mechanical Weakening Detection 1 |
| 2 | oL5 | Overtorque occurred, matching the conditions specified in L6-08. |
oL5 fault causes and solutions — PDF page 276
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Overtorque occurred, triggering the mechanical weakening level set to L6-08. | Check for the cause of mechanical weakening. |
oL7 fault definition — PDF page 276
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oL7 | High-Slip Braking oL |
| 2 | oL7 | The output frequency stayed constant for longer than the time set in n3-04 during High-slip Braking. |
oL7 fault causes and solutions — PDF page 276
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Excessive load inertia. | • Reduce deceleration times using parameters C1-02, C1-04, C1-06 and C1-08 in applications that do not use High-slip Braking. • Use a braking resistor to shorten deceleration time. |
| 2 | Motor is driven by the load. | • Reduce deceleration times using parameters C1-02, C1-04, C1-06 and C1-08 in applications that do not use High-slip Braking. • Use a braking resistor to shorten deceleration time. |
| 3 | Something on the load side is restricting deceleration. | • Reduce deceleration times using parameters C1-02, C1-04, C1-06 and C1-08 in applications that do not use High-slip Braking. • Use a braking resistor to shorten deceleration time. |
| 4 | The overload time during High-slip Braking is too short. | • Increase parameter n3-04 (High-slip Braking Overload Time). • Install a thermal relay and increase the parameter setting of n3-04 to the maximum value. |
Manual — Operator, overspeed and overvoltage faults — page 277
Source reference: SIEP C71060618F, December 2016, physical PDF page 277. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oPr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
ov. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Troubleshooting
Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.
oPr fault definition | oPr
Fault/error code scope: oPr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPr fault causes and solutions | External operator is not properly connected to the drive.
oS fault definition | oS
Fault/error code scope: oS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oS fault causes and solutions | Overshoot or undershoot is occurring.
oS fault causes and solutions | Incorrect PG pulse settings.
oS fault causes and solutions | Inappropriate parameter settings.
ov fault definition | ov
Fault/error code scope: ov. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
ov fault causes and solutions | Deceleration time is too short and regenerative energy flows from the motor into the drive.
ov fault causes and solutions | Fast acceleration time causes the motor to overshoot the speed reference.
ov fault causes and solutions | Excessive braking load.
ov fault causes and solutions | Surge voltage entering from the drive input power.
ov fault causes and solutions | Ground fault in the output circuit causing the DC bus capacitor to overcharge.
ov fault causes and solutions | Improper Setting of Speed Search related parameters. (Includes Speed Search after a momentary power loss and after a fault restart.)
ov fault causes and solutions | Excessive regeneration when overshoot occurs after acceleration.
ov fault causes and solutions | Drive input power voltage is too high.
ov fault causes and solutions | The dynamic braking transistor is damaged.
ov fault causes and solutions | The braking transistor is wired incorrectly.
oPr fault definition — PDF page 277
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPr | External Digital Operator Connection Fault |
| 2 | oPr | • The external operator has been disconnected from the drive. Note: An oPr fault will occur when all of the following conditions are true: • Output is interrupted when the operator is disconnected (o2-06 = 1). • The run command is assigned to the operator (b1-02 = 0 and LOCAL has been selected). |
oPr fault causes and solutions — PDF page 277
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | External operator is not properly connected to the drive. | • Check the connection between the operator and the drive. • Replace the cable if damaged. • Turn off the drive input power and disconnect the operator. Next reconnect the operator and turn the drive input power back on. |
oS fault definition — PDF page 277
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oS | Overspeed (Simple V/f with PG) |
| 2 | oS | Pulse input (RP) indicates that motor speed feedback exceeded F1-08 setting. |
oS fault causes and solutions — PDF page 277
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Overshoot or undershoot is occurring. | • Adjust the gain by using the pulse train input parameters (H6-02 through H6-05). • Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1). |
| 2 | Incorrect PG pulse settings. | Set the H6-02 (Pulse Train Input Scaling) = 100%, the frequency of the PG pulses at maximum motor speed. |
| 3 | Inappropriate parameter settings. | Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09). |
ov fault definition — PDF page 277
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | ov | Overvoltage |
| 2 | ov | Voltage in the DC bus has exceeded the overvoltage detection level. • For 200 V class: approximately 410 V • For 400 V class: approximately 820 V (740 V when E1-01 is less than 400) |
ov fault causes and solutions — PDF page 277
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Deceleration time is too short and regenerative energy flows from the motor into the drive. | • Increase the deceleration time (C1-02, C1-04, C1-06, C1-08). • Install a braking resistor or a dynamic braking resistor unit. • Enable stall prevention during deceleration (L3-04 = “1”). Stall prevention is enabled as the default setting. |
| 2 | Fast acceleration time causes the motor to overshoot the speed reference. | • Check if sudden drive acceleration triggers an overvoltage alarm. • Increase the acceleration time. • Use longer S-curve acceleration and deceleration times. |
| 3 | Excessive braking load. | The braking torque was too high, causing regenerative energy to charge the DC bus. Reduce the braking torque, use a braking option, or lengthen decel time. |
| 4 | Surge voltage entering from the drive input power. | Install a DC link choke. Note: Voltage surge can result from thyristor convertor and phase advancing capacitor using same drive main input power supply. |
| 5 | Ground fault in the output circuit causing the DC bus capacitor to overcharge. | • Check the motor wiring for ground faults. • Correct grounding shorts and turn the power back on. |
| 6 | Improper Setting of Speed Search related parameters. (Includes Speed Search after a momentary power loss and after a fault restart.) | • Check the settings for Speed Search related parameters. • Enable Speed Search Retry function (b3-19 greater than or equal to 1 to 10). • Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03 respectively). • Perform Line-to-Line Resistance Auto-Tuning and then enable Speed Estimation Type Speed Search (b3-24 = 1). |
| 7 | Excessive regeneration when overshoot occurs after acceleration. | • Enable the Overvoltage Suppression function (L3-11 = 1). • Lengthen the S-curve at acceleration end. |
| 8 | Drive input power voltage is too high. | • Check the voltage. • Lower drive input power voltage within the limits listed in the specifications. |
| 9 | The dynamic braking transistor is damaged. | Replace the drive. |
| 10 | The braking transistor is wired incorrectly. | • Check braking transistor wiring for errors. • Properly rewire the braking resistor device. |
Manual — Overvoltage, phase-loss and braking faults — page 278
Source reference: SIEP C71060618F, December 2016, physical PDF page 278. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
PF. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
PGo. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
rH. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
ov from PDF277 cause/solution continuation | Drive fails to operate properly due to noise interference.
ov from PDF277 cause/solution continuation | Load inertia has been set incorrectly.
ov from PDF277 cause/solution continuation | Braking function is being used in PM Open Loop Vector Control.
ov from PDF277 cause/solution continuation | Motor hunting occurs.
Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.
PF fault definition | PF
Fault/error code scope: PF. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
PF fault causes and solutions | There is phase loss in the drive input power.
PF fault causes and solutions | There is loose wiring in the drive input power terminals.
PF fault causes and solutions | There is excessive fluctuation in the drive input power voltage.
PF fault causes and solutions | There is poor balance between voltage phases.
PF fault causes and solutions | The main circuit capacitors are worn.
PGo fault definition | PGo
Fault/error code scope: PGo. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
PGo fault causes and solutions | Pulse input (RP) is disconnected.
PGo fault causes and solutions | Pulse input (RP) wiring is wrong.
PGo fault causes and solutions | Motor brake engaged.
rH fault definition | rH
Fault/error code scope: rH. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
rH fault causes and solutions | Deceleration time is too short and excessive regenerative energy is flowing back into the drive.
ov from PDF277 cause/solution continuation — PDF page 278
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Drive fails to operate properly due to noise interference. | • Review the list of possible solutions provided for controlling noise. • Review the section on handling noise interference and check the control circuit lines, main circuit lines and ground wiring. |
| 2 | Load inertia has been set incorrectly. | • Check the load inertia settings when using KEB, overvoltage suppression or Stall Prevention during deceleration. • Adjust L3-25 (Load Inertia Ratio) in accordance with the load. |
| 3 | Braking function is being used in PM Open Loop Vector Control. | Connect a braking resistor. |
| 4 | Motor hunting occurs. | • Adjust the parameters that control hunting. • Set the hunting prevention gain (n1-02). • Adjust the AFR time constant 1 (n2-02) and the AFR time constant 2 (n2-03) when in OLV Control. • Use parameters n8-45 (PM Speed Feedback Detection Suppression Gain) and n8-47 (Pull-In Current Compensation Time Constant). |
PF fault definition — PDF page 278
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | PF | Input Phase Loss |
| 2 | PF | Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when L8-05 = 1 (enabled). |
PF fault causes and solutions — PDF page 278
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | There is phase loss in the drive input power. | • Check for wiring errors in the main circuit drive input power. • Correct the wiring. |
| 2 | There is loose wiring in the drive input power terminals. | • Ensure the terminals are tightened properly. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torques on page 58 for details. |
| 3 | There is excessive fluctuation in the drive input power voltage. | • Check the voltage from the drive input power. • Review the possible solutions for stabilizing the drive input power. • Disable Input Phase Loss Detection (L8-05 = “0”). PF is detected if DC bus ripple is too high. If it is disabled, there is no fault but the ripple is still too high, thereby the capacitors are stressed more and lose lifetime. |
| 4 | There is poor balance between voltage phases. | • Stabilize drive input power or disable phase loss detection. |
| 5 | The main circuit capacitors are worn. | • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 is greater than 90%. |
| 6 | The main circuit capacitors are worn. | • Check for anything wrong with the drive input power. • If nothing is wrong with the drive input power, try the following solutions if the alarm continues: • Disable Input Phase Loss Protection selection (L8-05 = “0”). PF is detected if DC bus ripple is too high. If it is disabled, there is no fault but the ripple is still too high, thereby the capacitors are stressed more and lose lifetime. • Replace the drive. |
PGo fault definition — PDF page 278
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | PGo | PG Disconnect (for Simple V/f with PG) |
| 2 | PGo | No PG pulses are received for longer than the time set to F1-14. |
PGo fault causes and solutions — PDF page 278
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Pulse input (RP) is disconnected. | Reconnect the pulse input (RP). |
| 2 | Pulse input (RP) wiring is wrong. | Correct the wiring. |
| 3 | Motor brake engaged. | Ensure the motor brake releases properly. |
rH fault definition — PDF page 278
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | rH | Braking Resistor Overheat |
| 2 | rH | Braking resistor protection was triggered. Fault detection is enabled when L8-01 = 1 (disabled as a default). |
rH fault causes and solutions — PDF page 278
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Deceleration time is too short and excessive regenerative energy is flowing back into the drive. | • Check the load, deceleration time and speed. • Reduce the load. • Increase the acceleration and deceleration times (C1-01 through C1-08). • Replace the braking option with a larger device that can handle the power that is discharged. |
Manual — Brake, short, speed-search and pull-out faults — page 279
Source reference: SIEP C71060618F, December 2016, physical PDF page 279. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
rr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
SC. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
SEr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
STo. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
UL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more frequently than its rating trips the alarm even when the braking resistor surface is not very hot.
Cause Possible Solution
6.4 Fault Detection
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
rH from PDF278 cause/solution continuation | Excessive braking inertia.
rH from PDF278 cause/solution continuation | The proper braking resistor has not been installed.
Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.
rr fault definition | rr
Fault/error code scope: rr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
rr fault causes and solutions | The braking transistor is damaged.
rr fault causes and solutions | The control circuit is damaged.
SC fault definition | SC
Fault/error code scope: SC. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
SC fault causes and solutions | IGBT fault
SC fault causes and solutions | IGBT short circuit detection and circuit fault
SEr fault definition | SEr
Fault/error code scope: SEr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
SEr fault causes and solutions | Speed Search parameters are set to the wrong values.
SEr fault causes and solutions | The motor is coasting in the opposite direction of the Run command.
STo fault definition | STo
Fault/error code scope: STo. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
STo fault causes and solutions | The wrong motor code has been set (Yaskawa motors only).
STo fault causes and solutions | Load is too heavy.
STo fault causes and solutions | Load inertia is too heavy.
STo fault causes and solutions | Acceleration and deceleration times are too short.
UL3 fault definition | UL3
Fault/error code scope: UL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
UL3 fault causes and solutions | Parameter settings are not appropriate for the type of load.
UL3 fault causes and solutions | There is a fault on the machine side.
rH from PDF278 cause/solution continuation — PDF page 279
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Excessive braking inertia. | Recalculate braking load and braking power. Then try reducing the braking load and checking the braking resistor settings and improve braking capacity. |
| 2 | The proper braking resistor has not been installed. | • Check the specifications and conditions for the braking resistor device. • Select the optimal braking resistor. |
rr fault definition — PDF page 279
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | rr | Dynamic Braking Transistor |
| 2 | rr | The built-in dynamic braking transistor failed. |
rr fault causes and solutions — PDF page 279
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The braking transistor is damaged. | • Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing and Resetting Faults on page 298. • Replace the drive if the fault continues. |
| 2 | The control circuit is damaged. | • Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing and Resetting Faults on page 298. • Replace the drive if the fault continues. |
SC fault definition — PDF page 279
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | SC | IGBT Short Circuit |
SC fault causes and solutions — PDF page 279
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | IGBT fault | • Check motor wiring • Cycle power to the drive. • If the problem continues, contact your Yaskawa representative or the nearest Yaskawa sales office. |
| 2 | IGBT short circuit detection and circuit fault | • Check motor wiring • Cycle power to the drive. • If the problem continues, contact your Yaskawa representative or the nearest Yaskawa sales office. |
SEr fault definition — PDF page 279
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | SEr | Too Many Speed Search Restarts |
| 2 | SEr | The number of speed search restarts exceeded the number set to b3-19. |
SEr fault causes and solutions — PDF page 279
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Speed Search parameters are set to the wrong values. | • Reduce the detection compensation gain during Speed Search (b3-10). • Increase the current level when attempting Speed Search (b3-17). • Increase the detection time during Speed Search (b3-18). • Repeat Auto-Tuning. |
| 2 | The motor is coasting in the opposite direction of the Run command. | Set b3-14 to 1 to enable Bi-directional Speed Search. |
STo fault definition — PDF page 279
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | STo | Motor Pull Out or Step Out Detection |
| 2 | STo | Motor pull out or step out has occurred. Motor has exceeded its pull out torque. |
STo fault causes and solutions — PDF page 279
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The wrong motor code has been set (Yaskawa motors only). | • Enter the correct motor code for the PM being used into E5-01. • For special-purpose motors, enter the correct data to all E5 parameters according to the Test Report provided for the motor. |
| 2 | Load is too heavy. | • Increase the value set to n8-55 (Load Inertia for PM). • Increase the value set to n8-51 (Pull-In Current during Accel/Decel for PM). • Reduce the load. • Increase the motor or drive capacity. |
| 3 | Load inertia is too heavy. | Increase n8-55 (Load Inertia for PM). |
| 4 | Acceleration and deceleration times are too short. | • Increase the acceleration and deceleration times (C1-01 through C1-08). • Increase the S-curve acceleration and deceleration times (C2-01). |
UL3 fault definition — PDF page 279
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | UL3 | Undertorque Detection 1 |
| 2 | UL3 | The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable time (L6-03). |
UL3 fault causes and solutions — PDF page 279
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Parameter settings are not appropriate for the type of load. | Check the settings of parameters L6-02 and L6-03. |
| 2 | There is a fault on the machine side. | Check the load for any problems. |
Manual — Undertorque and undervoltage faults — page 280
Source reference: SIEP C71060618F, December 2016, physical PDF page 280. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
UL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
UL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Uv1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Uv2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Uv3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.4 Fault Detection
Literal source name/definition; code shared only in physical merged source extent. fault is distinct from other diagnostic categories.
UL4 fault definition | UL4
Fault/error code scope: UL4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
UL4 fault causes and solutions | Parameter settings are not appropriate for the type of load.
UL4 fault causes and solutions | There is a fault on the machine side.
UL5 fault definition | UL5
Fault/error code scope: UL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
UL5 fault causes and solutions | Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08).
Uv1 fault definition | Uv1
Fault/error code scope: Uv1. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Uv1 fault causes and solutions | Input power phase loss.
Uv1 fault causes and solutions | One of the drive input power wiring terminals is loose.
Uv1 fault causes and solutions | There is a problem with the voltage from the drive input power.
Uv1 fault causes and solutions | The power has been interrupted.
Uv1 fault causes and solutions | Drive internal circuitry has become worn.
Uv1 fault causes and solutions | The drive input power transformer is not large enough and voltage drops after switching on power.
Uv1 fault causes and solutions | Air inside the drive is too hot.
Uv1 fault causes and solutions | Problem with the CHARGE indicator.
Uv2 fault definition | Uv2
Fault/error code scope: Uv2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Uv2 fault causes and solutions | L2-02 changed from its default value in drive that is 7.5 kW or smaller without installing a Momentary Power Loss Ride-Thru.
Uv2 fault causes and solutions | The wiring for the control power supply is damaged.
Uv2 fault causes and solutions | Internal circuitry is damaged.
Uv3 fault definition | Uv3
UL4 fault definition — PDF page 280
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | UL4 | Undertorque Detection 2 |
| 2 | UL4 | The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable time (L6-06). |
UL4 fault causes and solutions — PDF page 280
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Parameter settings are not appropriate for the type of load. | Check the settings of parameters L6-05 and L6-06. |
| 2 | There is a fault on the machine side. | Check the load for any problems. |
UL5 fault definition — PDF page 280
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | UL5 | Mechanical Weakening Detection 2 |
| 2 | UL5 | The operation conditions matched the conditions set to L6-08. |
UL5 fault causes and solutions — PDF page 280
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08). | Check the load side for any problems. |
Uv1 fault definition — PDF page 280
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Uv1 | DC Bus Undervoltage |
| 2 | Uv1 | One of the following conditions occurred while the drive was in operation: • Voltage in the DC bus fell below the undervoltage detection level (L2-05). • For 200 V class: approximately 190 V (160 V for single phase drives) • For 400 V class: approximately 380 V (350 V when E1-01 is less than 400) The fault is output only if L2-01 = 0 or L2-01 = 1 and the DC bus voltage is under L2-05 for longer than L2-02. |
Uv1 fault causes and solutions — PDF page 280
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Input power phase loss. | • The main circuit drive input power is wired incorrectly. • Correct the wiring. |
| 2 | One of the drive input power wiring terminals is loose. | • Ensure there are no loose terminals. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torques on page 58 for details. |
| 3 | There is a problem with the voltage from the drive input power. | • Check the voltage. • Correct the voltage to within range listed in drive input power specifications. |
| 4 | The power has been interrupted. | Correct the drive input power. |
| 5 | Drive internal circuitry has become worn. | • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 exceeds 90%. |
| 6 | The drive input power transformer is not large enough and voltage drops after switching on power. | Check the capacity of the drive input power transformer. |
| 7 | Air inside the drive is too hot. | Check the drive internal temperature. |
| 8 | Problem with the CHARGE indicator. | Replace the drive. |
Uv2 fault definition — PDF page 280
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Uv2 | Control Power Supply Voltage Fault |
| 2 | Uv2 | Voltage is too low for the control drive input power. |
Uv2 fault causes and solutions — PDF page 280
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | L2-02 changed from its default value in drive that is 7.5 kW or smaller without installing a Momentary Power Loss Ride-Thru. | Correct parameter L2-02 setting or install optional Momentary Power Loss Ride-Thru unit. |
| 2 | The wiring for the control power supply is damaged. | • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur. |
| 3 | Internal circuitry is damaged. | • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur. |
Uv3 fault definition — PDF page 280
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Uv3 | Undervoltage 3 (Inrush Prevention Circuit Fault) |
| 2 | Uv3 | The inrush prevention circuit has failed. |
Manual — Inrush circuit fault continuation — page 281
Source reference: SIEP C71060618F, December 2016, physical PDF page 281. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Digital Operator Display Fault Name
6.4 Fault Detection
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
Uv3 from PDF280 cause/solution continuation | The contactor on the inrush prevention circuit is damaged.
Uv3 from PDF280 cause/solution continuation — PDF page 281
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The contactor on the inrush prevention circuit is damaged. | • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur. • Check monitor U4-06 for the performance life of the inrush prevention circuit. • Replace the drive if U4-06 exceeds 90%. |
Manual — Alarms and communication definitions — page 282
Source reference: SIEP C71060618F, December 2016, physical PDF page 282. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
AEr. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
bb. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
bUS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
CALL. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
6.5 Alarm Detection
Alarms are drive protection functions that do not operate the fault contact. The drive will return to original status when the cause of the alarm has been removed. During an alarm condition, the Digital Operator display flashes and an alarm output is generated at the multi-function outputs (H2-01 to H2-03), if programmed. Investigate the cause of the alarm and Refer to Detailed Alarm Codes, Causes, and Possible Solutions on page 282 for the appropriate action.
u Alarm Codes, Causes, and Possible Solutions
Table 6.10 Detailed Alarm Codes, Causes, and Possible Solutions
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
AEr minor fault/alarm definition | AEr
Fault/error code scope: AEr. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
AEr minor fault/alarm causes and solutions | Station number is set outside the possible setting range.
bb minor fault/alarm definition | bb
Fault/error code scope: bb. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
bb minor fault/alarm causes and solutions | External baseblock signal entered via multi- function input terminal (S1 to S7).
bUS minor fault/alarm definition | bUS
Fault/error code scope: bUS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
bUS minor fault/alarm causes and solutions | Connection is broken or master controller stopped communicating.
bUS minor fault/alarm causes and solutions | Option card is damaged.
bUS minor fault/alarm causes and solutions | The option card is not properly connected to the drive.
bUS minor fault/alarm causes and solutions | A data error occurred due to noise.
CALL minor fault/alarm definition | CALL
AEr minor fault/alarm definition — PDF page 282
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | AEr | Station Address Setting Error (CC-Link, CANopen, MECHATROLINK) |
| 2 | AEr | Option card node address is outside the acceptable setting range. |
AEr minor fault/alarm causes and solutions — PDF page 282
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Station number is set outside the possible setting range. | • Set parameter F6-10 to the proper value if a CC-Link option card is used • Set parameter F6-20 to the proper value if a MECHATROLINK option card is used. • Set parameter F6-35 to the proper value if a CANopen option card is used. | YES |
bb minor fault/alarm definition — PDF page 282
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | bb | Baseblock |
| 2 | bb | Drive output interrupted as indicated by an external baseblock signal. |
bb minor fault/alarm causes and solutions — PDF page 282
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | External baseblock signal entered via multi- function input terminal (S1 to S7). | Check external sequence and baseblock signal input timing. | No output |
bUS minor fault/alarm definition — PDF page 282
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | bUS | Option Communication Error |
| 2 | bUS | • After initial communication was established, the connection was lost. • Assign a run command frequency reference to the option card. |
bUS minor fault/alarm causes and solutions — PDF page 282
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Connection is broken or master controller stopped communicating. | • Check for faulty wiring. • Correct the wiring. • Repair ground wiring or disconnected cables. | YES |
| 2 | Option card is damaged. | If there are no problems with the wiring and the fault continues to occur, replace the option card. | YES |
| 3 | The option card is not properly connected to the drive. | • The connector pins on the option card are not properly lined up with the connector pins on the drive. • Reinstall the option card. | YES |
| 4 | A data error occurred due to noise. | • Check options available to minimize the effects of noise. • Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring. • Try to reduce noise on the controller side. • Use surge absorbers on magnetic contactors or other equipment causing the disturbance. • Use cables recommended by Yaskawa, or another type of shielded line. The shield should be grounded on the controller side or on the drive input power side. • All wiring for communications devices should be separated from drive input power lines. Install an EMC noise filter to the input side of the drive input power. | YES |
CALL minor fault/alarm definition — PDF page 282
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | CALL | Serial Communication Transmission Error |
| 2 | CALL | Communication has not yet been established. |
Manual — Communication, reset and speed-deviation alarms — page 283
Source reference: SIEP C71060618F, December 2016, physical PDF page 283. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
CE. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
CrST. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
CyC. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
dEv. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
CALL from PDF282 cause/solution continuation | Communications wiring is faulty, there is a short circuit, or something is not connected properly.
CALL from PDF282 cause/solution continuation | Programming error on the master side.
CALL from PDF282 cause/solution continuation | Communications circuitry is damaged.
CALL from PDF282 cause/solution continuation | Terminal resistance setting is incorrect.
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
CE minor fault/alarm definition | CE
Fault/error code scope: CE. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
CE minor fault/alarm causes and solutions | A data error occurred due to noise.
CE minor fault/alarm causes and solutions | Communication protocol is incompatible.
CE minor fault/alarm causes and solutions | The CE detection time (H5-09) is set shorter than the time required for a communication cycle to take place.
CE minor fault/alarm causes and solutions | Incompatible PLC software settings or there is a hardware problem.
CE minor fault/alarm causes and solutions | Communications cable is disconnected or damaged.
CrST minor fault/alarm definition | CrST
Fault/error code scope: CrST. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
CrST minor fault/alarm causes and solutions | Fault reset was being executed when a run command was entered.
CyC minor fault/alarm definition | CyC
Fault/error code scope: CyC. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
CyC minor fault/alarm causes and solutions | The controller is using a comm. cycle beyond the allowable setting range for the MECHATROLINK option unit.
dEv minor fault/alarm definition | dEv
CALL from PDF282 cause/solution continuation — PDF page 283
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Communications wiring is faulty, there is a short circuit, or something is not connected properly. | • Check for wiring errors. • Correct the wiring. • Remove and ground shorts and reconnect loose wires. | YES |
| 2 | Programming error on the master side. | Check communications at start-up and correct programming errors. | YES |
| 3 | Communications circuitry is damaged. | • Perform a self-diagnostics check. • Replace the drive if the fault continues to occurs. | YES |
| 4 | Terminal resistance setting is incorrect. | The terminal slave drive must have the internal terminal resistance switch set correctly. Place DIP switch S2 to the ON position. | YES |
CE minor fault/alarm definition — PDF page 283
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | CE | MEMOBUS/Modbus Communication Error |
| 2 | CE | Control data was not received correctly for two seconds. |
CE minor fault/alarm causes and solutions — PDF page 283
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | A data error occurred due to noise. | • Check options available to minimize the effects of noise. • Counteract noise in the control circuit wiring, main circuit lines and ground wiring. • Reduce noise on the controller side. • Use surge absorbers on magnetic contactors or other equipment causing the disturbance. • Use cables recommended by Yaskawa or another type of shielded line. The shield should be grounded on the controller side or on the drive input power side. • Separate all wiring for communications devices from drive input power lines. Install an EMC noise filter to the input side of the drive input power. | YES |
| 2 | Communication protocol is incompatible. | • Check the H5 parameter settings as well as the protocol setting in the controller. • Ensure settings are compatible. | YES |
| 3 | The CE detection time (H5-09) is set shorter than the time required for a communication cycle to take place. | • Check the PLC. • Change the software settings in the PLC. • Set a longer CE detection time (H5-09). | YES |
| 4 | Incompatible PLC software settings or there is a hardware problem. | • Check the PLC. • Remove the cause of the error on the controller side. | YES |
| 5 | Communications cable is disconnected or damaged. | • Check the connector for a signal through the cable. • Replace the communications cable. | YES |
CrST minor fault/alarm definition — PDF page 283
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | CrST | Can Not Reset |
CrST minor fault/alarm causes and solutions — PDF page 283
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Fault reset was being executed when a run command was entered. | • Ensure that a run command cannot be entered from the external terminals or option card during fault reset. • Turn off the run command. | YES |
CyC minor fault/alarm definition — PDF page 283
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | CyC | MECHATROLINK Comm. Cycle Setting Error |
| 2 | CyC | Comm. Cycle Setting Error was detected. |
CyC minor fault/alarm causes and solutions — PDF page 283
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | The controller is using a comm. cycle beyond the allowable setting range for the MECHATROLINK option unit. | Set the comm. cycle for the upper controller within the allowable setting range for the MECHATROLINK option unit. | YES |
dEv minor fault/alarm definition — PDF page 283
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | dEv | Speed Deviation (for Simple V/f with PG) |
| 2 | dEv | According to the pulse input (RP), the speed deviation is greater than the setting in F1-10 for a time longer than the setting in F1-11. |
Manual — External and enable alarms — page 284
Source reference: SIEP C71060618F, December 2016, physical PDF page 284. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
dnE. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
E5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF0. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF6. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
EF7. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
dEv from PDF283 cause/solution continuation | Load is too heavy
dEv from PDF283 cause/solution continuation | Acceleration and deceleration times are set too short.
dEv from PDF283 cause/solution continuation | The load is locked up.
dEv from PDF283 cause/solution continuation | Parameter settings are inappropriate.
dEv from PDF283 cause/solution continuation | The motor brake engaged.
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
dnE minor fault/alarm definition | dnE
Fault/error code scope: dnE. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
dnE minor fault/alarm causes and solutions | “Drive Enable” is set to a multi-function contact input (H1-oo = 6A) and that signal was switched off.
dnE minor fault/alarm causes and solutions | “Drive Enable” is set to a multi-function contact input (H1-□□ = 6A) and that signal was switched off.
E5 minor fault/alarm definition | E5
Fault/error code scope: E5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
E5 minor fault/alarm causes and solutions | The watchdog timer expired while waiting for data from the controller.
EF minor fault/alarm definition | EF
Fault/error code scope: EF. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
EF minor fault/alarm causes and solutions | Sequence error
EF0 minor fault/alarm definition | EF0
Fault/error code scope: EF0. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
EF0 minor fault/alarm causes and solutions | An external fault was received from the PLC with F6-03 = 3 (causing the drive to continue running when an external fault occurs).
EF0 minor fault/alarm causes and solutions | There is a problem with the PLC program.
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF1
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF2
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF3
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF4
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF5
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF6
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition | EF7
dEv from PDF283 cause/solution continuation — PDF page 284
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Load is too heavy | Reduce the load. | YES |
| 2 | Acceleration and deceleration times are set too short. | Increase the acceleration and deceleration times (C1-01 through C1-08). | YES |
| 3 | The load is locked up. | Check the machine. | YES |
| 4 | Parameter settings are inappropriate. | Check the settings of parameters F1-10 and F1-11. | YES |
| 5 | The motor brake engaged. | Ensure the brake releases properly. | YES |
dnE minor fault/alarm definition — PDF page 284
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | dnE | Drive Disabled |
dnE minor fault/alarm causes and solutions — PDF page 284
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | “Drive Enable” is set to a multi-function contact input (H1-□□ = 6A) and that signal was switched off. | Check the operation sequence. | YES |
E5 minor fault/alarm definition — PDF page 284
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | E5 | MECHATROLINK Watchdog Timer Error |
E5 minor fault/alarm causes and solutions — PDF page 284
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | The watchdog timer expired while waiting for data from the controller. | Issue a DISCONNECT or ALM_CLR command, followed by a CONNECT or SYNC_SET command and move to phase 3. | YES |
EF minor fault/alarm definition — PDF page 284
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | EF | Forward/Reverse Run Command Input Error |
| 2 | EF | Both forward run and reverse run closed simultaneously for over 0.5 s. |
EF minor fault/alarm causes and solutions — PDF page 284
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Sequence error | Check the forward and reverse command sequence and correct the problem. Note: Motor ramps to stop when minor fault EF is detected. | YES |
EF0 minor fault/alarm definition — PDF page 284
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | EF0 | Option Card External Fault |
| 2 | EF0 | An external fault condition is present. |
EF0 minor fault/alarm causes and solutions — PDF page 284
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | An external fault was received from the PLC with F6-03 = 3 (causing the drive to continue running when an external fault occurs). | • Remove the cause of the external fault. • Remove the external fault input from the PLC. | YES |
| 2 | There is a problem with the PLC program. | Check the PLC program and correct problems. | YES |
EF1 / EF2 / EF3 / EF4 / EF5 / EF6 / EF7 minor fault/alarm definition — PDF page 284
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | EF1 | External fault (input terminal S1) |
| 2 | EF1 | External fault at multi-function input terminal S1. |
| 3 | EF2 | External fault (input terminal S2) |
| 4 | EF2 | External fault at multi-function input terminal S2. |
| 5 | EF3 | External fault (input terminal S3) |
| 6 | EF3 | External fault at multi-function input terminal S3. |
| 7 | EF4 | External fault (input terminal S4) |
| 8 | EF4 | External fault at multi-function input terminal S4. |
| 9 | EF5 | External fault (input terminal S5) |
| 10 | EF5 | External fault at multi-function input terminal S5. |
| 11 | EF6 | External fault (input terminal S6) |
| 12 | EF6 | External fault at multi-function input terminal S6. |
| 13 | EF7 | External fault (input terminal S7) |
| 14 | EF7 | External fault at multi-function input terminal S7. |
Manual — PID, safety and current alarms — page 285
Source reference: SIEP C71060618F, December 2016, physical PDF page 285. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
FbH. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
FbL. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Hbb. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
HbbF. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
HCA. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
EF1 through EF7 from PDF284 cause/solution continuation | An external device has tripped an alarm function.
EF1 through EF7 from PDF284 cause/solution continuation | Wiring is incorrect.
EF1 through EF7 from PDF284 cause/solution continuation | Multi-function contact inputs are set incorrectly.
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
FbH minor fault/alarm definition | FbH
Fault/error code scope: FbH. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
FbH minor fault/alarm causes and solutions | Parameters settings for b5-36 and b5-37 are incorrect.
FbH minor fault/alarm causes and solutions | PID feedback wiring is faulty.
FbH minor fault/alarm causes and solutions | Feedback sensor has malfunctioned.
FbH minor fault/alarm causes and solutions | Feedback input circuit is damaged.
FbL minor fault/alarm definition | FbL
Fault/error code scope: FbL. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
FbL minor fault/alarm causes and solutions | Parameters settings for b5-13 and b5-14 are incorrect.
FbL minor fault/alarm causes and solutions | PID feedback wiring is faulty.
FbL minor fault/alarm causes and solutions | Feedback sensor has malfunctioned.
FbL minor fault/alarm causes and solutions | Feedback input circuit is damaged.
Hbb minor fault/alarm definition | Hbb
Fault/error code scope: Hbb. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Hbb minor fault/alarm causes and solutions | There is no signal at terminal H1.
Hbb minor fault/alarm causes and solutions | Internally, the Safe Disable channel is broken.
HbbF minor fault/alarm definition | HbbF
Fault/error code scope: HbbF. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
HbbF minor fault/alarm causes and solutions | One of the Safe Disable channels is faulty.
HCA minor fault/alarm definition | HCA
EF1 through EF7 from PDF284 cause/solution continuation — PDF page 285
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | An external device has tripped an alarm function. | Remove the cause of the external fault and reset the multi-function input value. | YES |
| 2 | Wiring is incorrect. | • Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1-□□ = 20 to 2F). • Reconnect the signal line. | YES |
| 3 | Multi-function contact inputs are set incorrectly. | • Check if the unused terminals have been set for H1-□□ = 20 to 2F (External Fault). • Change the terminal settings. | YES |
FbH minor fault/alarm definition — PDF page 285
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | FbH | Excessive PID Feedback |
| 2 | FbH | The PID feedback input is higher than the level set in b5-36 for longer than the time set in b5-37, and b5-12 is set to 1 or 4. |
FbH minor fault/alarm causes and solutions — PDF page 285
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Parameters settings for b5-36 and b5-37 are incorrect. | Check parameters b5-36 and b5-37. | YES |
| 2 | PID feedback wiring is faulty. | Correct the wiring. | YES |
| 3 | Feedback sensor has malfunctioned. | Check the sensor and replace it if damaged. | YES |
| 4 | Feedback input circuit is damaged. | Replace the drive. | YES |
FbL minor fault/alarm definition — PDF page 285
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | FbL | PID Feedback Loss |
| 2 | FbL | The PID feedback input is lower than the level set in b5-13 for longer than the time set in b5-14, and b5-12 is set to 1 or 4. |
FbL minor fault/alarm causes and solutions — PDF page 285
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Parameters settings for b5-13 and b5-14 are incorrect. | Check parameters b5-13 and b5-14. | YES |
| 2 | PID feedback wiring is faulty. | Correct the wiring. | YES |
| 3 | Feedback sensor has malfunctioned. | Check the sensor and replace it if damaged. | YES |
| 4 | Feedback input circuit is damaged. | Replace the drive. | YES |
Hbb minor fault/alarm definition — PDF page 285
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Hbb | Safe Disable Signal Input |
| 2 | Hbb | The Safe Disable Input channel is open. |
Hbb minor fault/alarm causes and solutions — PDF page 285
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | There is no signal at terminal H1. | Check if external safety circuit tripped and disabled the drive. If the Safe Disable function is not utilized, check if the terminals HC, H1, and H2 are linked. | YES |
| 2 | Internally, the Safe Disable channel is broken. | Replace the drive. | YES |
HbbF minor fault/alarm definition — PDF page 285
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | HbbF | Safe Disable Signal Input |
| 2 | HbbF | The safe disable input hardware is defective. |
HbbF minor fault/alarm causes and solutions — PDF page 285
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | One of the Safe Disable channels is faulty. | Replace the drive. | YES |
HCA minor fault/alarm definition — PDF page 285
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | HCA | Current Alarm |
| 2 | HCA | Drive current exceeded overcurrent warning level (150% of the rated current). |
Manual — Maintenance and heatsink alarms — page 286
Source reference: SIEP C71060618F, December 2016, physical PDF page 286. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
LT-1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
LT-2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
LT-3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
LT-4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oH. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
HCA from PDF285 cause/solution continuation | Load is too heavy.
HCA from PDF285 cause/solution continuation | Acceleration and deceleration times are too short.
HCA from PDF285 cause/solution continuation | A special-purpose motor is being used, or the drive is attempting to run a motor greater than the maximum allowable capacity.
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
LT-1 minor fault/alarm definition | LT-1
Fault/error code scope: LT-1. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
LT-1 minor fault/alarm causes and solutions | The cooling fan has reached 90% of its expected performance life.
LT-2 minor fault/alarm definition | LT-2
Fault/error code scope: LT-2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
LT-2 minor fault/alarm causes and solutions | The main circuit and control circuit capacitors have reached 90% of their expected performance life.
LT-3 minor fault/alarm definition | LT-3
Fault/error code scope: LT-3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
LT-3 minor fault/alarm causes and solutions | The DC bus soft charge relay has reached 90% of their expected performance life.
LT-4 minor fault/alarm definition | LT-4
Fault/error code scope: LT-4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
LT-4 minor fault/alarm causes and solutions | IGBTs have reached 50% of their expected performance life.
oH minor fault/alarm definition | oH
HCA from PDF285 cause/solution continuation — PDF page 286
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Load is too heavy. | • Measure the current flowing through the motor. • Reduce the load or increase the capacity of the drive. | YES |
| 2 | Acceleration and deceleration times are too short. | • Calculate the torque required during acceleration and for the inertia moment. • If the torque level is not right for the load, take the following steps: • Increase the acceleration and deceleration times (C1-01 through C1-08). • Increase the capacity of the drive. | YES |
| 3 | A special-purpose motor is being used, or the drive is attempting to run a motor greater than the maximum allowable capacity. | • Check the motor capacity. • Use a motor appropriate for the drive. Ensure the motor is within the allowable capacity range. | YES |
LT-1 minor fault/alarm definition — PDF page 286
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | LT-1 | Cooling Fan Maintenance Time |
| 2 | LT-1 | The cooling fan has reached its expected maintenance period and may need to be replaced. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F. |
LT-1 minor fault/alarm causes and solutions — PDF page 286
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | The cooling fan has reached 90% of its expected performance life. | Replace the cooling fan and reset the Maintenance Monitor by setting o4-03 to 0. | – |
LT-2 minor fault/alarm definition — PDF page 286
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | LT-2 | Capacitor Maintenance Time |
| 2 | LT-2 | The main circuit and control circuit capacitors are nearing the end of their expected performance life. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F. |
LT-2 minor fault/alarm causes and solutions — PDF page 286
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | The main circuit and control circuit capacitors have reached 90% of their expected performance life. | Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. | – |
LT-3 minor fault/alarm definition — PDF page 286
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | LT-3 | Soft Charge Bypass Relay Maintenance Time |
| 2 | LT-3 | The DC bus soft charge relay is nearing the end of its expected performance life. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F. |
LT-3 minor fault/alarm causes and solutions — PDF page 286
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | The DC bus soft charge relay has reached 90% of their expected performance life. | Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. | – |
LT-4 minor fault/alarm definition — PDF page 286
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | LT-4 | IGBT Maintenance Time (50%) |
| 2 | LT-4 | IGBTs have reached 50% of their expected performance life. Note: An alarm output (H2-□□ = 10) will only be triggered if H2-□□ = 2F. |
LT-4 minor fault/alarm causes and solutions — PDF page 286
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | IGBTs have reached 50% of their expected performance life. | Check the load, carrier frequency, and output frequency. | – |
oH minor fault/alarm definition — PDF page 286
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oH | Heatsink Overheat |
| 2 | oH | The temperature exceeded the value set to L8-02. |
Manual — Heat and overtorque alarms — page 287
Source reference: SIEP C71060618F, December 2016, physical PDF page 287. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oH2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oH3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
oH from PDF286 cause/solution continuation | Surrounding temperature is too high
oH from PDF286 cause/solution continuation | Internal cooling fan has stopped.
oH from PDF286 cause/solution continuation | Airflow around the drive is restricted.
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
oH2 minor fault/alarm definition | oH2
Fault/error code scope: oH2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oH2 minor fault/alarm causes and solutions | An external device triggered and overheat warning in the drive.
oH3 minor fault/alarm definition | oH3
Fault/error code scope: oH3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oH3 minor fault/alarm causes and solutions | Motor thermostat wiring is fault (PTC input).
oH3 minor fault/alarm causes and solutions | There is a fault on the machine side (e.g., the machine is locked up).
oH3 minor fault/alarm causes and solutions | Motor has overheated.
oL3 minor fault/alarm definition | oL3
Fault/error code scope: oL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oL3 minor fault/alarm causes and solutions | Inappropriate parameter settings.
oL3 minor fault/alarm causes and solutions | There is a fault on the machine side (e.g., the machine is locked up).
oL4 minor fault/alarm definition | oL4
oH from PDF286 cause/solution continuation — PDF page 287
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Surrounding temperature is too high | • Check the surrounding temperature. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool surrounding area. • Remove anything near drive that may cause extra heat. | YES |
| 2 | Internal cooling fan has stopped. | • Replace the cooling fan. Refer to Cooling Fan Replacement on page 317. • After replacing the fan, reset the cooling fan maintenance parameter to (o4-03 = “0”). | YES |
| 3 | Airflow around the drive is restricted. | • Provide proper installation space around the drive as indicated in the manual. Refer to Correct Installation Orientation on page 38. • Allow for the specified space and ensure that there is sufficient circulation around the control panel. | YES |
| 4 | Airflow around the drive is restricted. | • Check for dust or foreign materials clogging cooling fan. • Clear debris caught in the fan that restricts air circulation. | YES |
oH2 minor fault/alarm definition — PDF page 287
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oH2 | Drive Overheat Warning |
| 2 | oH2 | “Drive Overheat Warning” was input to a multi-function input terminal, S1 through S7 (H1-□□= B) |
oH2 minor fault/alarm causes and solutions — PDF page 287
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | An external device triggered and overheat warning in the drive. | • Search for the device that tripped the overheat warning. • Solving the problem will clear the warning. | YES |
oH3 minor fault/alarm definition — PDF page 287
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oH3 | Motor Overheat |
| 2 | oH3 | The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02 or H3-10 = E). |
oH3 minor fault/alarm causes and solutions — PDF page 287
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Motor thermostat wiring is fault (PTC input). | Repair the PTC input wiring. | YES |
| 2 | There is a fault on the machine side (e.g., the machine is locked up). | • Check the status of the machine. • Remove the cause of the fault. | YES |
| 3 | Motor has overheated. | • Check the load size, accel/decel times, and cycle times. • Decrease the load. • Increase accel and decel times (C1-01 to C1-08). • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. Note: Do not lower E1-08 and E1-10 excessively, because this reduces load tolerance at low speeds. • Check the motor-rated current. • Enter motor-rated current on motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system. | YES |
oL3 minor fault/alarm definition — PDF page 287
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oL3 | Overtorque 1 |
| 2 | oL3 | Drive output current (or torque in OLV) was greater than L6-02 for longer than the time set in L6-03. |
oL3 minor fault/alarm causes and solutions — PDF page 287
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Inappropriate parameter settings. | Check parameters L6-02 and L6-03. | YES |
| 2 | There is a fault on the machine side (e.g., the machine is locked up). | • Check the status of the machine. • Remove the cause of the fault. | YES |
oL4 minor fault/alarm definition — PDF page 287
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oL4 | Overtorque 2 |
| 2 | oL4 | Drive output current (or torque in OLV) was greater than L6-05 for longer than the time set in L6-06. |
Manual — Overtorque, overspeed and voltage alarms — page 288
Source reference: SIEP C71060618F, December 2016, physical PDF page 288. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
ov. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
PASS. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
PGo. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
oL4 from PDF287 cause/solution continuation | Parameter settings are not appropriate.
oL4 from PDF287 cause/solution continuation | There is a fault on the machine side (e.g., the machine is locked up).
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
oL5 minor fault/alarm definition | oL5
Fault/error code scope: oL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oL5 minor fault/alarm causes and solutions | Overtorque occurred, triggering the mechanical weakening level set to L6-08.
oS minor fault/alarm definition | oS
Fault/error code scope: oS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oS minor fault/alarm causes and solutions | Overshoot or undershoot is occurring.
oS minor fault/alarm causes and solutions | PG pulse settings are incorrect.
oS minor fault/alarm causes and solutions | Parameter settings are inappropriate.
ov minor fault/alarm definition | ov
Fault/error code scope: ov. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
ov minor fault/alarm causes and solutions | Surge voltage present in the drive input power.
ov minor fault/alarm causes and solutions | • The motor is short-circuited. • Ground current has over-charged the main circuit capacitors via the drive input power.
ov minor fault/alarm causes and solutions | Noise interference causes the drive to operate incorrectly.
PASS minor fault/alarm definition | PASS
Fault/error code scope: PASS. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
PASS minor fault/alarm causes and solutions | MEMOBUS/Modbus test has finished normally.
PGo minor fault/alarm definition | PGo
oL4 from PDF287 cause/solution continuation — PDF page 288
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Parameter settings are not appropriate. | Check parameters L6-05 and L6-06. | YES |
| 2 | There is a fault on the machine side (e.g., the machine is locked up). | • Check the status of the machine being used. • Remove the cause of the fault. | YES |
oL5 minor fault/alarm definition — PDF page 288
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oL5 | Mechanical Weakening Detection 1 |
| 2 | oL5 | Overtorque occurred, matching the conditions specified in L6-08. |
oL5 minor fault/alarm causes and solutions — PDF page 288
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Overtorque occurred, triggering the mechanical weakening level set to L6-08. | Check for the cause of mechanical weakening. | YES |
oS minor fault/alarm definition — PDF page 288
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oS | Overspeed (for Simple V/f with PG) |
| 2 | oS | Pulse input (RP) indicates that motor speed feedback exceeded F1-08 setting. |
oS minor fault/alarm causes and solutions — PDF page 288
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Overshoot or undershoot is occurring. | • Adjust the gain by using the pulse train input parameters (H6-02 through H6-05). • Adjust the speed feedback accuracy. • Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1). | YES |
| 2 | PG pulse settings are incorrect. | Set the H6-02 (Pulse Train Input Scaling) to the frequency of PG pulses at maximum motor speed. | YES |
| 3 | Parameter settings are inappropriate. | Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09). | YES |
ov minor fault/alarm definition — PDF page 288
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | ov | DC Bus Overvoltage |
| 2 | ov | The DC bus voltage exceeded the trip point. For 200 V class: approximately 410 V For 400 V class: approximately 820 V (740 V when E1-01 < 400) |
ov minor fault/alarm causes and solutions — PDF page 288
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Surge voltage present in the drive input power. | • Install an AC reactor or DC link choke. • Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on the same drive input power system. | YES |
| 2 | • The motor is short-circuited. • Ground current has over-charged the main circuit capacitors via the drive input power. | • Check the motor power cable, relay terminals and motor terminal box for short circuits. • Correct grounding shorts and turn the power back on. | YES |
| 3 | Noise interference causes the drive to operate incorrectly. | • Review possible solutions for handling noise interference. • Review section on handling noise interference and check control circuit lines, main circuit lines and ground wiring. • If the magnetic contactor is identified as a source of noise, install a surge protector to the MC coil. | YES |
| 4 | Noise interference causes the drive to operate incorrectly. | Set number of fault restarts (L5-01) to a value other than 0. | YES |
PASS minor fault/alarm definition — PDF page 288
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | PASS | MEMOBUS/Modbus Comm. Test Mode Complete |
PASS minor fault/alarm causes and solutions — PDF page 288
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | MEMOBUS/Modbus test has finished normally. | This verifies that the test was successful. | No output |
PGo minor fault/alarm definition — PDF page 288
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | PGo | PG Disconnect (for Simple V/f with PG) |
| 2 | PGo | Detected when no PG pulses received for a time longer than setting in F1-14. |
Manual — PG, switch, maintenance and undertorque alarms — page 289
Source reference: SIEP C71060618F, December 2016, physical PDF page 289. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
rUn. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
SE. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
TrPC. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
UL3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
UL4. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
UL5. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
PGo from PDF288 cause/solution continuation | Pulse input (RP) is disconnected.
PGo from PDF288 cause/solution continuation | Pulse input (RP) wiring is wrong.
PGo from PDF288 cause/solution continuation | Motor brake is engaged.
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
rUn minor fault/alarm definition | rUn
Fault/error code scope: rUn. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
rUn minor fault/alarm causes and solutions | A motor switch command was entered during run.
SE minor fault/alarm definition | SE
Fault/error code scope: SE. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
SE minor fault/alarm causes and solutions | A digital input programmed to 67H (MEMOBUS/Modbus test) was closed while the drive was running.
TrPC minor fault/alarm definition | TrPC
Fault/error code scope: TrPC. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
TrPC minor fault/alarm causes and solutions | IGBTs have reached 90% of their expected performance life.
UL3 minor fault/alarm definition | UL3
Fault/error code scope: UL3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
UL3 minor fault/alarm causes and solutions | Inappropriate parameter settings.
UL3 minor fault/alarm causes and solutions | Load has dropped or decreased significantly.
UL4 minor fault/alarm definition | UL4
Fault/error code scope: UL4. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
UL4 minor fault/alarm causes and solutions | Inappropriate parameter settings.
UL4 minor fault/alarm causes and solutions | The load has dropped or decreased significantly.
UL5 minor fault/alarm definition | UL5
Fault/error code scope: UL5. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
UL5 minor fault/alarm causes and solutions | Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08).
PGo from PDF288 cause/solution continuation — PDF page 289
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Pulse input (RP) is disconnected. | Reconnect the pulse input (RP). | YES |
| 2 | Pulse input (RP) wiring is wrong. | Correct the wiring. | YES |
| 3 | Motor brake is engaged. | Ensure the brake releases properly | YES |
rUn minor fault/alarm definition — PDF page 289
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | rUn | Motor Switch during Run |
| 2 | rUn | A command to switch motors was entered during run. |
rUn minor fault/alarm causes and solutions — PDF page 289
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | A motor switch command was entered during run. | Change the operation pattern so that the motor switch command is entered while the drive is stopped. | YES |
SE minor fault/alarm definition — PDF page 289
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | SE | MEMOBUS/Modbus Communication Test Mode Error |
SE minor fault/alarm causes and solutions — PDF page 289
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | A digital input programmed to 67H (MEMOBUS/Modbus test) was closed while the drive was running. | Stop the drive and run the test again. | No output |
TrPC minor fault/alarm definition — PDF page 289
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | TrPC | IGBT Maintenance Time (90%) |
| 2 | TrPC | IGBTs have reached 90% of their expected performance life. |
TrPC minor fault/alarm causes and solutions — PDF page 289
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | IGBTs have reached 90% of their expected performance life. | Replace the drive. | YES |
UL3 minor fault/alarm definition — PDF page 289
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | UL3 | Undertorque Detection 1 |
| 2 | UL3 | Drive output current (or torque in OLV) less than L6-02 for longer than L6-03 time. |
UL3 minor fault/alarm causes and solutions — PDF page 289
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Inappropriate parameter settings. | Check parameters L6-02 and L6-03. | YES |
| 2 | Load has dropped or decreased significantly. | Check for broken parts in the transmission system. | YES |
UL4 minor fault/alarm definition — PDF page 289
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | UL4 | Undertorque Detection 2 |
| 2 | UL4 | Drive output current (or torque in OLV) less than L6-05 for longer than L6-06 time. |
UL4 minor fault/alarm causes and solutions — PDF page 289
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Inappropriate parameter settings. | Check parameters L6-05 and L6-06. | YES |
| 2 | The load has dropped or decreased significantly. | Check for broken parts in the transmission system. | YES |
UL5 minor fault/alarm definition — PDF page 289
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | UL5 | Mechanical Weakening Detection 2 |
| 2 | UL5 | The operation conditions matched the conditions set to L6-08. |
UL5 minor fault/alarm causes and solutions — PDF page 289
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Undertorque was detected and matched the condition of mechanical loss detection operation selection (L6-08). | Check the load side for any problems. | YES |
Manual — Undervoltage alarm — page 290
Source reference: SIEP C71060618F, December 2016, physical PDF page 290. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Uv. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Minor Fault Name
Minor Fault Cause Possible Solution (H2-□□ = 10)
6.5 Alarm Detection
Literal source name/definition; code shared only in physical merged source extent. minor fault/alarm is distinct from other diagnostic categories.
Uv minor fault/alarm definition | Uv
Fault/error code scope: Uv. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Uv minor fault/alarm causes and solutions | Phase loss in the drive input power.
Uv minor fault/alarm causes and solutions | Loose wiring in the drive input power terminals.
Uv minor fault/alarm causes and solutions | There is a problem with the drive input power voltage.
Uv minor fault/alarm causes and solutions | Drive internal circuitry is worn.
Uv minor fault/alarm causes and solutions | The drive input power transformer is not large enough and voltage drops when the power is switched on.
Uv minor fault/alarm causes and solutions | Air inside the drive is too hot.
Uv minor fault/alarm causes and solutions | The CHARGE indicator light is broken or disconnected.
Uv minor fault/alarm definition — PDF page 290
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Uv | Undervoltage |
| 2 | Uv | One of the following conditions was true when the drive was stopped and a run command was entered: • DC bus voltage dropped below the level specified in L2-05. • Contactor to suppress inrush current in the drive was open. • Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage is under L2-05. |
Uv minor fault/alarm causes and solutions — PDF page 290
| Source row | Cause | Possible solution | Minor fault output (H2-□□=10) |
|---|---|---|---|
| 1 | Phase loss in the drive input power. | Check for wiring errors in the main circuit drive input power. Correct the wiring. | YES |
| 2 | Loose wiring in the drive input power terminals. | • Ensure the terminals have been properly tightened. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torques on page 58. | YES |
| 3 | There is a problem with the drive input power voltage. | • Check the voltage. • Lower the voltage of the drive input power so that it is within the limits listed in the specifications. | YES |
| 4 | Drive internal circuitry is worn. | • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 exceeds 90%. | YES |
| 5 | The drive input power transformer is not large enough and voltage drops when the power is switched on. | • Check for a tripped alarm when the magnetic contactor, line breaker and leakage breaker are turned on. • Check the capacity of the drive input power transformer. | YES |
| 6 | Air inside the drive is too hot. | • Check the temperature inside the drive. | YES |
| 7 | The CHARGE indicator light is broken or disconnected. | • Replace the drive. | YES |
Manual — Operation errors and input conflicts — page 291
Source reference: SIEP C71060618F, December 2016, physical PDF page 291. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oPE01. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oPE02. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oPE03. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
6.6 Operator Programming Errors
An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter setting is inappropriate. The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPE occurs, investigate the cause and Refer to oPE Codes, Causes, and Possible Solutions on page 291 for the appropriate action. When an oPE error is displayed, press the ENTER button to display U1-18 (oPE fault constant). This monitor displays the parameter causing the oPE error.
u oPE Codes, Causes, and Possible Solutions
Table 6.11 Detailed oPE Codes, Causes, and Possible Solutions
Digital Operator Display Error Name
Cause Possible Solution
Digital Operator Display Fault Name
Note: Other errors are given precedence over oPE02 when multiple errors occur at the same time.
Troubleshooting
Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.
oPE01 operator error definition | oPE01
Fault/error code scope: oPE01. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE01 operator error causes and solutions | The drive capacity setting (o2-04) and the actual capacity of the drive are not the same.
oPE02 operator error definition | oPE02
Fault/error code scope: oPE02. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE02 operator error causes and solutions | Parameters were set outside the possible setting range.
oPE03 operator error definition | oPE03
Fault/error code scope: oPE03. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE03 operator error causes and solutions | • The same function is assigned to two multi-function inputs. • Excludes “Not used” and “External Fault.”
oPE03 operator error causes and solutions | The Up command was set but the Down command was not, or vice versa (settings 10 vs. 11).
oPE03 operator error causes and solutions | The Up 2 command was set but the Down 2 command was not, or vice versa (settings 75 vs. 76).
oPE03 operator error causes and solutions | • Run/Stop command for a 2-Wire sequence 2 was set (H1-oo = 42), but forward/ reverse command (H1-oo = 43) was not. • “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A).
oPE03 operator error causes and solutions | • Run/Stop command for a 2-Wire sequence 2 was set (H1-□□ = 42), but forward/ reverse command (H1-□□ = 43) was not. • “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A).
oPE03 operator error causes and solutions | Two of the following functions are set at the same time: • Up/Down Command (10 vs. 11) • Up 2/Down 2 Command (75 vs. 76) • Hold Accel/Decel Stop (A) • Analog Frequency Reference Sample/Hold (1E) • Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
oPE03 operator error causes and solutions | The Up/Down command (10, 11) is enabled at the same time as PID control (b5-01).
oPE01 operator error definition — PDF page 291
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE01 | Drive Capacity Setting Fault |
| 2 | oPE01 | Drive capacity and the value set to o2-04 do not match. |
oPE01 operator error causes and solutions — PDF page 291
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The drive capacity setting (o2-04) and the actual capacity of the drive are not the same. | Correct the value set to o2-04. |
oPE02 operator error definition — PDF page 291
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE02 | Parameter Range Setting Error |
| 2 | oPE02 | Use U1-18 to find parameters set outside the range. |
oPE02 operator error causes and solutions — PDF page 291
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Parameters were set outside the possible setting range. | Set parameters to the proper values. |
oPE03 operator error definition — PDF page 291
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE03 | Multi-Function Input Selection Error |
| 2 | oPE03 | A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-07. |
oPE03 operator error causes and solutions — PDF page 291
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | • The same function is assigned to two multi-function inputs. • Excludes “Not used” and “External Fault.” | • Ensure all multi-function inputs are assigned to different functions. • Re-enter the multi-function settings to ensure this does not occur. |
| 2 | The Up command was set but the Down command was not, or vice versa (settings 10 vs. 11). | Correctly set functions that need to be enabled in combination with other functions. |
| 3 | The Up 2 command was set but the Down 2 command was not, or vice versa (settings 75 vs. 76). | Correctly set functions that need to be enabled in combination with other functions. |
| 4 | • Run/Stop command for a 2-Wire sequence 2 was set (H1-□□ = 42), but forward/ reverse command (H1-□□ = 43) was not. • “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or H1-02 = 6A). | Correctly set functions that need to be enabled in combination with other functions. |
| 5 | Two of the following functions are set at the same time: • Up/Down Command (10 vs. 11) • Up 2/Down 2 Command (75 vs. 76) • Hold Accel/Decel Stop (A) • Analog Frequency Reference Sample/Hold (1E) • Offset Frequency 1, 2, 3 Calculations (44, 45, 46) | • Check if contradictory settings have been assigned to the multi-function input terminals at the same time. • Correct setting errors. |
| 6 | The Up/Down command (10, 11) is enabled at the same time as PID control (b5-01). | Set b5-01 to 0 to disable PID control or disable the Up/Down command. |
Manual — Input conflicts and initialization errors — page 292
Source reference: SIEP C71060618F, December 2016, physical PDF page 292. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oPE04. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oPE05. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oPE07. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.6 Operator Programming Errors
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
oPE03 from PDF291 cause/solution continuation | Settings for NC and NO input for the following functions were selected at the same time: • External Search Command 1 and External Search Command 2 (61 vs. 62) • Fast-Stop N.O. and Fast-Stop N.C. (15 vs. 17) • KEB for Momentary Power Loss and High Slip Braking (65, 66, 7A, 7B vs. 68) • Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A) • KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B) • FWD Run Command (or REV) and FWD/ REV Run Command (2-wire) (40, 41 vs. 42, 43) • External DB Command and Drive Enable (60 vs. 6A) • Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76)
oPE03 from PDF291 cause/solution continuation | One of the following settings was entered while H1-oo = 2 (External Reference 1/2): • b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train Input Function Selection) not = 0 (Frequency Reference) • b1-15 or b1-16 set to 3 but no option card connected • Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias).
oPE03 from PDF291 cause/solution continuation | One of the following settings was entered while H1-□□ = 2 (External Reference 1/2): • b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train Input Function Selection) not = 0 (Frequency Reference) • b1-15 or b1-16 set to 3 but no option card connected • Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias).
oPE03 from PDF291 cause/solution continuation | H2-oo = 38 (Drive Enabled) but H1-oo is not set to 6A (Drive Enable).
oPE03 from PDF291 cause/solution continuation | H2-□□ = 38 (Drive Enabled) but H1-□□ is not set to 6A (Drive Enable).
oPE03 from PDF291 cause/solution continuation | H1-oo = 7E (Direction Detection) although H6-01 is not set to 3 (Simple V/f with PG).
oPE03 from PDF291 cause/solution continuation | H1-□□ = 7E (Direction Detection) although H6-01 is not set to 3 (Simple V/f with PG).
Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.
oPE04 operator error definition | oPE04
Fault/error code scope: oPE04. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE04 operator error causes and solutions | The drive, control board, or terminal board has been replaced and the parameter settings between the control board and the terminal board no longer match.
oPE05 operator error definition | oPE05
Fault/error code scope: oPE05. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE05 operator error causes and solutions | Frequency reference is assigned to an option card (b1-01 = 3) that is not connected to the drive.
oPE05 operator error causes and solutions | The Run command is assigned to an option card (b1-02 = 3) that is not connected to the drive.
oPE05 operator error causes and solutions | Frequency reference is assigned to the pulse train input (b1-01 = 4), but terminal RP is not set for pulse train input (H6-01 > 0)
oPE07 operator error definition | oPE07
oPE03 from PDF291 cause/solution continuation — PDF page 292
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Settings for NC and NO input for the following functions were selected at the same time: • External Search Command 1 and External Search Command 2 (61 vs. 62) • Fast-Stop N.O. and Fast-Stop N.C. (15 vs. 17) • KEB for Momentary Power Loss and High Slip Braking (65, 66, 7A, 7B vs. 68) • Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A) • KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B) • FWD Run Command (or REV) and FWD/ REV Run Command (2-wire) (40, 41 vs. 42, 43) • External DB Command and Drive Enable (60 vs. 6A) • Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76) | Check for contradictory settings assigned to the multi-function input terminals at the same time. Correct setting errors. |
| 2 | One of the following settings was entered while H1-□□ = 2 (External Reference 1/2): • b1-15 = 4 (Pulse Train Input) and H6-01 (Pulse Train Input Function Selection) not = 0 (Frequency Reference) • b1-15 or b1-16 set to 3 but no option card connected • Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0 (Frequency Bias). | Correct the settings for the multi-function input terminal parameters. |
| 3 | H2-□□ = 38 (Drive Enabled) but H1-□□ is not set to 6A (Drive Enable). | Correct the settings for the multi-function input terminal parameters. |
| 4 | H1-□□ = 7E (Direction Detection) although H6-01 is not set to 3 (Simple V/f with PG). | Correct the settings for the multi-function input terminal parameters. |
oPE04 operator error definition — PDF page 292
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE04 | Initialization required. |
oPE04 operator error causes and solutions — PDF page 292
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The drive, control board, or terminal board has been replaced and the parameter settings between the control board and the terminal board no longer match. | To load the parameter settings to the drive that are stored in the terminal board, set A1-03 to 5550. Initialize parameters after drive replacement by setting A1-03 to 1110 or 2220. |
oPE05 operator error definition — PDF page 292
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE05 | Run Command/Frequency Reference Source Selection Error |
oPE05 operator error causes and solutions — PDF page 292
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Frequency reference is assigned to an option card (b1-01 = 3) that is not connected to the drive. | Reconnect the option card to the drive. |
| 2 | The Run command is assigned to an option card (b1-02 = 3) that is not connected to the drive. | Reconnect the option card to the drive. |
| 3 | Frequency reference is assigned to the pulse train input (b1-01 = 4), but terminal RP is not set for pulse train input (H6-01 > 0) | Set H6-01 to 0. |
oPE07 operator error definition — PDF page 292
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE07 | Multi-Function Analog Input Selection Error |
| 2 | oPE07 | A contradictory setting is assigned to multi-function analog inputs H3-02 through to H3-10 and PID functions conflict. |
Manual — Analog, mode and PID errors — page 293
Source reference: SIEP C71060618F, December 2016, physical PDF page 293. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oPE08. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oPE09. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
Note: Use U1-18 to find parameters set outside of the specified setting range. Other errors are given precedence over oPE08 when multiple errors occur simultaneously.
6.6 Operator Programming Errors
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
oPE07 from PDF292 cause/solution continuation | H3-02 and H3-10 are set to the same value.
oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H3-02 or H3-10 = B (PID Feedback) H6-01 (Pulse Train Input) = 1 (PID Feedback)
oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) H6-01 = 2 (pulse train input sets the PID target value)
oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value)
oPE07 from PDF292 cause/solution continuation | The following simultaneous contradictory settings: H6-01 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value)
Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.
oPE08 operator error definition | oPE08
Fault/error code scope: oPE08. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE08 operator error causes and solutions | Attempted to use a function in the V/f motor control method that is only possible in Open Loop Vector Control.
oPE08 operator error causes and solutions | Simple V/f with PG was enabled while not in V/f Control (H6-01 = 3).
oPE08 operator error causes and solutions | In Open Loop Vector Control, n2-02 is greater than n2-03
oPE08 operator error causes and solutions | In Open Loop Vector Control, C4-02 is greater than C4-06
oPE08 operator error causes and solutions | In OLV/PMl, parameters E5-02 to E5-07 are set to 0.
oPE08 operator error causes and solutions | The following conditions are true in PM Open Loop Vector Control: • E5-03 does not equal 0 • E5-09 and E5-24 are both equal to 0, or neither equals 0
oPE09 operator error definition | oPE09
Fault/error code scope: oPE09. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE09 operator error causes and solutions | The following simultaneous contradictory settings: • b5-15 not 0.0 (PID Sleep Function Operation Level) • The stopping method is set to either DC injection braking or coast to stop with a timer (b1-03 = 2 or 3).
oPE09 operator error causes and solutions | • D control is being used on the setpoint deviation (b5-01 = 1) or on the feedback value (b5-01 = 2). • A negative PID output value is set to operate the drive in reverse (b5-11 = 1) and the frequency reference lower limit greater than 0 (d2-02 > 0).
oPE07 from PDF292 cause/solution continuation — PDF page 293
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | H3-02 and H3-10 are set to the same value. | Change the settings to H3-02 and H3-10 so that functions no longer conflict. Note: Both 0 (primary analog frequency reference) and F (Not Used) can be set to H3-02 and H3-10 at the same time. |
| 2 | The following simultaneous contradictory settings: H3-02 or H3-10 = B (PID Feedback) H6-01 (Pulse Train Input) = 1 (PID Feedback) | Disable one of the PID selections. |
| 3 | The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) H6-01 = 2 (pulse train input sets the PID target value) | Disable one of the PID selections. |
| 4 | The following simultaneous contradictory settings: H3-02 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value) | Disable one of the PID selections. |
| 5 | The following simultaneous contradictory settings: H6-01 or H3-10 = C (PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value) | Disable one of the PID selections. |
oPE08 operator error definition — PDF page 293
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE08 | Parameter Selection Error |
| 2 | oPE08 | A function has been set that cannot be used in the motor control method selected. |
oPE08 operator error causes and solutions — PDF page 293
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Attempted to use a function in the V/f motor control method that is only possible in Open Loop Vector Control. | Check the motor control method and the functions available. |
| 2 | Simple V/f with PG was enabled while not in V/f Control (H6-01 = 3). | To use Simple V/f with PG, ensure the motor control method has been set to V/f Control (A1-02 = 0). |
| 3 | In Open Loop Vector Control, n2-02 is greater than n2-03 | Correct parameter settings so that n2-02 is less than n2-03. |
| 4 | In Open Loop Vector Control, C4-02 is greater than C4-06 | Correct parameter settings so that C4-02 is less than C4-06. |
| 5 | In OLV/PMl, parameters E5-02 to E5-07 are set to 0. | • Set the correct motor code in accordance with the motor being used (E5-01). • When using a special-purpose motor, set E5-□□ in accordance with the Test Report provided. |
| 6 | The following conditions are true in PM Open Loop Vector Control: • E5-03 does not equal 0 • E5-09 and E5-24 are both equal to 0, or neither equals 0 | • Set E5-09 or E5-24 to the correct value, and set the other to “0”. • Set the motor-rated current for PM to “0” (E5-03). |
oPE09 operator error definition — PDF page 293
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE09 | PID Control Selection Fault |
| 2 | oPE09 | PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 to 4). |
oPE09 operator error causes and solutions — PDF page 293
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The following simultaneous contradictory settings: • b5-15 not 0.0 (PID Sleep Function Operation Level) • The stopping method is set to either DC injection braking or coast to stop with a timer (b1-03 = 2 or 3). | • Set b5-15 to a value other than 0. • Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1). |
| 2 | • D control is being used on the setpoint deviation (b5-01 = 1) or on the feedback value (b5-01 = 2). • A negative PID output value is set to operate the drive in reverse (b5-11 = 1) and the frequency reference lower limit greater than 0 (d2-02 > 0). | Set parameters b5-01, b5-11, and d2-02 to the proper values. |
Manual — PID, V/f, carrier and pulse errors — page 294
Source reference: SIEP C71060618F, December 2016, physical PDF page 294. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
oPE10. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oPE11. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
oPE13. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.6 Operator Programming Errors
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
oPE09 from PDF293 cause/solution continuation | • D control is being used on the setpoint deviation and the frequency reference plus the PID output (b5-01 = 4), D control is being used on the feedback value and the frequency reference plus the PID output (b5-01 = 4). • The frequency reference lower limit is set to a value greater than 0 (d2-02 > 0).
oPE09 from PDF293 cause/solution continuation | The absolute value of the lower limit for PID output is greater than the PID upper limit (b5-34 > b5-06).
Literal source name/definition; code shared only in physical merged source extent. operator error is distinct from other diagnostic categories.
oPE10 operator error definition | oPE10
Fault/error code scope: oPE10. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE10 operator error causes and solutions | V/f pattern setting error.
oPE11 operator error definition | oPE11
Fault/error code scope: oPE11. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE11 operator error causes and solutions | The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is less than or equal to 6, the drive operates at C6-03.
oPE11 operator error causes and solutions | Upper and lower limits between C6-02 and C6-05 contradict each other.
oPE13 operator error definition | oPE13
Fault/error code scope: oPE13. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
oPE13 operator error causes and solutions | Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 000, 031, 101, 102, 105, or 116.
oPE09 from PDF293 cause/solution continuation — PDF page 294
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | • D control is being used on the setpoint deviation and the frequency reference plus the PID output (b5-01 = 4), D control is being used on the feedback value and the frequency reference plus the PID output (b5-01 = 4). • The frequency reference lower limit is set to a value greater than 0 (d2-02 > 0). | Set parameters b5-01 and d2-02 to the proper values. |
| 2 | The absolute value of the lower limit for PID output is greater than the PID upper limit (b5-34 > b5-06). | Set parameters b5-34 and b5-06 to the proper values. |
oPE10 operator error definition — PDF page 294
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE10 | V/f Data Setting Error |
| 2 | oPE10 | One or more of the parameters listed below are not set according to the formula: • E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 • E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 |
oPE10 operator error causes and solutions — PDF page 294
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | V/f pattern setting error. | Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11. For motor 2, correct E3-04, E3-06, E3-07, E3-09, and E3-11. |
oPE11 operator error definition — PDF page 294
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE11 | Carrier Frequency Setting Error |
| 2 | oPE11 | Correct the setting for the carrier frequency. |
oPE11 operator error causes and solutions — PDF page 294
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is less than or equal to 6, the drive operates at C6-03. | Correct the parameter settings. |
| 2 | Upper and lower limits between C6-02 and C6-05 contradict each other. | Correct the parameter settings. |
oPE13 operator error definition — PDF page 294
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | oPE13 | Pulse Monitor Selection Error |
| 2 | oPE13 | Incorrect setting of monitor selection for Pulse Train (H6-06). |
oPE13 operator error causes and solutions — PDF page 294
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Scaling for the Pulse Train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 000, 031, 101, 102, 105, or 116. | Change scaling for the Pulse Train monitor or set H6-06 to 000, 031, 101, 102, 105, or 116. |
Manual — Auto-Tuning result and data errors — page 295
Source reference: SIEP C71060618F, December 2016, physical PDF page 295. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
End1. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
End2. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
End3. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-01. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-02. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
6.7 Auto-Tuning Fault Detection
Auto-Tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor coasts to a stop. No fault or alarm outputs will occur
u Auto-Tuning Codes, Causes, and Possible Solutions
Table 6.12 Detailed Auto-Tuning Codes, Causes, and Possible Solutions
Digital Operator Display Error Name
Cause Possible Solution
Digital Operator Display Fault Name
Troubleshooting
Literal source name/definition; code shared only in physical merged source extent. Auto-Tuning error is distinct from other diagnostic categories.
End1 Auto-Tuning error definition | End1
Fault/error code scope: End1. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
End1 Auto-Tuning error causes and solutions | The torque reference exceeded 20% during Auto-Tuning.
End1 Auto-Tuning error causes and solutions | The no-load current exceeded 80% of the drive rated current during Auto-Tuning.
End2 Auto-Tuning error definition | End2
Fault/error code scope: End2. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
End2 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.
End2 Auto-Tuning error causes and solutions | Auto-Tuning calculated values outside the parameter setting range, assigning the iron- core saturation coefficient (E2-07, E2-08) a temporary value.
End3 Auto-Tuning error definition | End3
Fault/error code scope: End3. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
End3 Auto-Tuning error causes and solutions | • The motor line-to-line resistance and the motor-rated current are not consistent with one another. • The correct current rating printed on the nameplate was not entered into T1-04.
Er-01 Auto-Tuning error definition | Er-01
Fault/error code scope: Er-01. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-01 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.
Er-01 Auto-Tuning error causes and solutions | Motor output and motor-rated current settings (T1-02 and T1-04) do not match.
Er-01 Auto-Tuning error causes and solutions | Motor output and no-load current settings (T1-04 and E2-03) do not match. Data required when Auto-Tuning for OLV Control or Stationary Auto-Tuning.
Er-01 Auto-Tuning error causes and solutions | Base frequency and base motor rotations (T1-05 and T1-07) do not match.
Er-02 Auto-Tuning error definition | Er-02
Fault/error code scope: Er-02. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-02 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.
Er-02 Auto-Tuning error causes and solutions | The wiring is faulty.
Er-02 Auto-Tuning error causes and solutions | Load is too heavy.
End1 Auto-Tuning error definition — PDF page 295
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | End1 | Excessive V/f Setting. Displayed after Auto-Tuning is complete. |
End1 Auto-Tuning error causes and solutions — PDF page 295
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The torque reference exceeded 20% during Auto-Tuning. | • Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter that data to T1-03 through T1-05. • Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning. • If possible, disconnect the motor from the load and perform Auto-Tuning. |
| 2 | The no-load current exceeded 80% of the drive rated current during Auto-Tuning. | • Before Auto-Tuning the drive, verify the information written on the motor nameplate and enter that data to T1-03 through T1-05. • Enter proper information to parameters T1-03 to T1-05 and repeat Auto-Tuning. • If possible, disconnect the motor from the load and perform Auto-Tuning. |
End2 Auto-Tuning error definition — PDF page 295
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | End2 | Motor Iron-Core Saturation Coefficient. Detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is complete. |
End2 Auto-Tuning error causes and solutions — PDF page 295
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor data entered during Auto-Tuning was incorrect. | • Enter the correct data. • Restart Auto-Tuning and enter the correct information. |
| 2 | Auto-Tuning calculated values outside the parameter setting range, assigning the iron- core saturation coefficient (E2-07, E2-08) a temporary value. | • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Rotational Auto-Tuning. |
End3 Auto-Tuning error definition — PDF page 295
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | End3 | Rated Current Setting Alarm (displayed after Auto-Tuning is complete) |
End3 Auto-Tuning error causes and solutions — PDF page 295
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | • The motor line-to-line resistance and the motor-rated current are not consistent with one another. • The correct current rating printed on the nameplate was not entered into T1-04. | • Check T1-04 setting. • Check the motor data and repeat Auto-Tuning. |
Er-01 Auto-Tuning error definition — PDF page 295
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-01 | Motor Data Error |
Er-01 Auto-Tuning error causes and solutions — PDF page 295
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor data entered during Auto-Tuning was incorrect. | • Enter the correct data. • Restart Auto-Tuning and enter the correct information. |
| 2 | Motor output and motor-rated current settings (T1-02 and T1-04) do not match. | • Check the drive and motor capacities. • Correct the settings of parameters T1-02 and T1-04. |
| 3 | Motor output and no-load current settings (T1-04 and E2-03) do not match. Data required when Auto-Tuning for OLV Control or Stationary Auto-Tuning. | • Check the motor-rated current and no-load current. • Correct the settings of parameters T1-04 and E2-03. |
| 4 | Base frequency and base motor rotations (T1-05 and T1-07) do not match. | Set T1-05 and T1-07 to the correct values. |
Er-02 Auto-Tuning error definition — PDF page 295
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-02 | Minor Fault |
Er-02 Auto-Tuning error causes and solutions — PDF page 295
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor data entered during Auto-Tuning was incorrect. | • Enter the correct data. • Restart Auto-Tuning and enter the correct information. |
| 2 | The wiring is faulty. | • Check the wiring and correct defective connections. • Check around the machine. • Check the load. |
| 3 | Load is too heavy. | • Check the wiring and correct defective connections. • Check around the machine. • Check the load. |
Manual — Auto-Tuning resistance, slip and speed errors — page 296
Source reference: SIEP C71060618F, December 2016, physical PDF page 296. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Er-03. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-04. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-05. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-08. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-09. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-11. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Er-12. Visible seven-segment example beside independently captured literal diagnostic code; exact segment shape and operator geometry remain original-only.
Digital Operator Display Fault Name
Cause Possible Solution
6.7 Auto-Tuning Fault Detection
Literal source name/definition; code shared only in physical merged source extent. Auto-Tuning error is distinct from other diagnostic categories.
Er-03 Auto-Tuning error definition | Er-03
Fault/error code scope: Er-03. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-03 Auto-Tuning error causes and solutions | Auto-Tuning canceled by pressing STOP button.
Er-04 Auto-Tuning error definition | Er-04
Fault/error code scope: Er-04. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-04 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.
Er-04 Auto-Tuning error causes and solutions | Auto-Tuning did not complete within designated time frame.
Er-04 Auto-Tuning error causes and solutions | Drive-calculated values outside parameter setting range.
Er-05 Auto-Tuning error definition | Er-05
Fault/error code scope: Er-05. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-05 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.
Er-05 Auto-Tuning error causes and solutions | Auto-Tuning did not complete within designated time frame.
Er-05 Auto-Tuning error causes and solutions | Drive-calculated values outside parameter setting range.
Er-08 Auto-Tuning error definition | Er-08
Fault/error code scope: Er-08. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-08 Auto-Tuning error causes and solutions | Motor data entered during Auto-Tuning was incorrect.
Er-08 Auto-Tuning error causes and solutions | Auto-Tuning did not complete within designated time frame.
Er-08 Auto-Tuning error causes and solutions | Values calculated by the drive are outside the allowable parameter setting ranges.
Er-09 Auto-Tuning error definition | Er-09
Fault/error code scope: Er-09. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-09 Auto-Tuning error causes and solutions | The motor did not accelerate for the specified acceleration time.
Er-09 Auto-Tuning error causes and solutions | Torque limit when motoring is too low (L7-01 and L7-02).
Er-11 Auto-Tuning error definition | Er-11
Fault/error code scope: Er-11. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-11 Auto-Tuning error causes and solutions | Torque reference is too high. (Enabled in OLV only.)
Er-12 Auto-Tuning error definition | Er-12
Fault/error code scope: Er-12. Full safety prerequisites remain applicable. Output availability repeats only over actual physical merged cell extent. Source instructions not commissioning approval.
Er-12 Auto-Tuning error causes and solutions | One of the motor phases is missing (U/T1, V/T2, W/T3).
Er-03 Auto-Tuning error definition — PDF page 296
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-03 | STOP Button Input |
Er-03 Auto-Tuning error causes and solutions — PDF page 296
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Auto-Tuning canceled by pressing STOP button. | Auto-Tuning did not complete properly and will have to be performed again. |
Er-04 Auto-Tuning error definition — PDF page 296
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-04 | Line-to-Line Resistance Error |
Er-04 Auto-Tuning error causes and solutions — PDF page 296
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor data entered during Auto-Tuning was incorrect. | • Enter the correct data. • Restart Auto-Tuning and enter the correct information. |
| 2 | Auto-Tuning did not complete within designated time frame. | • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Rotational Auto-Tuning. |
| 3 | Drive-calculated values outside parameter setting range. | • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Rotational Auto-Tuning. |
Er-05 Auto-Tuning error definition — PDF page 296
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-05 | No-Load Current Error |
Er-08 Auto-Tuning error definition — PDF page 296
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-08 | Rated Slip Error |
Er-08 Auto-Tuning error causes and solutions — PDF page 296
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Motor data entered during Auto-Tuning was incorrect. | • Enter the correct data. • Restart Auto-Tuning and enter the correct information. |
| 2 | Auto-Tuning did not complete within designated time frame. | • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Auto-Tuning. |
| 3 | Values calculated by the drive are outside the allowable parameter setting ranges. | • Check and correct faulty motor wiring. • Disconnect the motor from machine and perform Auto-Tuning. |
Er-09 Auto-Tuning error definition — PDF page 296
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-09 | Acceleration Error (detected only during Rotational Auto-Tuning) |
Er-09 Auto-Tuning error causes and solutions — PDF page 296
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | The motor did not accelerate for the specified acceleration time. | • Increase the acceleration time (C1-01). • Check if it is possible to disconnect the machine from the motor. |
| 2 | Torque limit when motoring is too low (L7-01 and L7-02). | • Check the settings of parameters L7-01 and L7-02. • Increase the setting. |
Er-11 Auto-Tuning error definition — PDF page 296
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-11 | Motor Speed Fault (detected only when Auto-Tuning is enabled) |
Er-11 Auto-Tuning error causes and solutions — PDF page 296
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Torque reference is too high. (Enabled in OLV only.) | • Increase the acceleration time in C1-01. • Disconnect the machine from the motor, if possible. |
Er-12 Auto-Tuning error definition — PDF page 296
| Source row | Literal display code | Name or definition |
|---|---|---|
| 1 | Er-12 | Current Detection Error |
Er-12 Auto-Tuning error causes and solutions — PDF page 296
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | One of the motor phases is missing (U/T1, V/T2, W/T3). | Check motor wiring and correct problems. |
Manual — Auto-Tuning current error continuation — page 297
Source reference: SIEP C71060618F, December 2016, physical PDF page 297. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Digital Operator Display Fault Name
6.7 Auto-Tuning Fault Detection
Troubleshooting
Continuation from previous physical page; repeated Digital Operator Display/Fault Name header is not a new fault. Merged cells repeat only over actual extent. Read full warnings and complete source condition.
Er-12 from PDF296 cause/solution continuation | Current exceeded the current rating of the drive.
Er-12 from PDF296 cause/solution continuation | The current is too low.
Er-12 from PDF296 cause/solution continuation | Attempted Auto-Tuning without motor connected to the drive.
Er-12 from PDF296 cause/solution continuation | Current detection signal error.
Er-12 from PDF296 cause/solution continuation — PDF page 297
| Source row | Cause | Possible solution |
|---|---|---|
| 1 | Current exceeded the current rating of the drive. | • Check the motor wiring for a short between motor lines. • If a magnetic contactor is used between motors, ensure it is on. • Replace the drive. |
| 2 | The current is too low. | • Check the motor wiring for a short between motor lines. • If a magnetic contactor is used between motors, ensure it is on. • Replace the drive. |
| 3 | Attempted Auto-Tuning without motor connected to the drive. | Connect the motor and perform Auto-Tuning. |
| 4 | Current detection signal error. | Replace the drive. |
Manual — Fault diagnosis, trace and reset — page 298
Source reference: SIEP C71060618F, December 2016, physical PDF page 298. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Turn on the drive input power. The first screen displays. Illustration shows F00.00. Source example only; key and operator geometry original-only.
Press [UP] until the monitor screen is displayed. Illustration shows Mon. Source example only; key and operator geometry original-only.
Press [ENTER] to display the parameter setting screen. Illustration shows U1-01. Source example only; key and operator geometry original-only.
Press [UP] and > until U2-02 (Fault History) is displayed. Illustration shows U2-02. Source example only; key and operator geometry original-only.
Press [ENTER] to view most recent fault (here, EF3). Illustration shows F EF3. Source example only; key and operator geometry original-only.
Press [UP] to view drive status information when fault occurred. Source example only; key and operator geometry original-only.
Parameters U2-03 through U2-17 help determine cause of fault. Illustration shows U2-03 to U2-17. Source example only; key and operator geometry original-only.
6.8 Diagnosing and Resetting Faults
When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault, then restart the drive.
u Fault Occurs Simultaneously with Power Loss
WARNING! Electrical Shock Hazard. Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or between the ground and main circuit terminals before restarting the drive. Failure to comply may result in serious injury or death and will cause damage to equipment. 1. Turn on the drive input power. 2. Use monitor parameters U2-□□ to display data on the operating status of the drive just before the fault occurred. 3. Remove the cause of the fault and reset.
Note: To find out what faults were triggered, check U2-02 (Fault History). Information on drive status when the fault occurred such as the frequency, current and voltage, can be found in U2-03 through U2-17. Refer to Viewing Fault Trace Data After Fault on page 298 for information on how to view fault trace data.
Note: When the fault continues to be displayed after cycling power, remove the cause of the fault and reset.
u If the Drive Still has Power After a Fault Occurs 1. Look at the LED operator for information on the fault that occurred. 2. Refer to Fault Displays, Causes, and Possible Solutions on page 267 3. Reset the fault. Refer to Fault Reset Methods on page 298.
u Viewing Fault Trace Data After Fault
Step Display/Result
u Fault Reset Methods
After the Fault Occurs Procedure
Fault reset procedures | Fix the cause of the fault, restart the drive, and reset the fault
Fault reset procedures | Fix the cause of the fault and reset via Fault Reset Digital Input S4.
Fault reset procedures — PDF page 298
| Source row | Fault condition | Procedure | Graphic labels |
|---|---|---|---|
| 1 | Fix the cause of the fault, restart the drive, and reset the fault | Press [RESET >] on the digital operator. | [RESET >] button and illustrated operator displaying EF3. Example only; device and key geometry original-only. |
| 2 | Fix the cause of the fault and reset via Fault Reset Digital Input S4. | Close then open the fault signal digital input via terminal S4. S4 is set fault reset as default (H1-04 = 12) | Drive; Fault Reset Switch; S4 Fault Reset Digital Input; SC Digital Input Common. Illustration labels only; exact wiring geometry remains original-only. |
Manual — Power-cycle reset continuation — page 299
Source reference: SIEP C71060618F, December 2016, physical PDF page 299. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
① OFF then ② ON. Source instruction alongside: reapply power after LED display is out. Switch geometry remains original-only; full electrical safety prerequisites retained.
After the Fault Occurs Procedure
If the above methods do not reset the fault, turn off the drive main power supply. Reapply power after LED operator display is out.
6.8 Diagnosing and Resetting Faults
Troubleshooting
Manual — Parameter access and motor-not-running troubleshooting — page 300
Source reference: SIEP C71060618F, December 2016, physical PDF page 300. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
6.9 Troubleshooting without Fault Display
This section describes troubleshooting problems that do not trip an alarm or fault.
u Cannot Change Parameter Settings
Cause Possible Solutions
u Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External Run Command
n Motor Does Not Rotate
Cannot change parameters | The drive is running the motor (i.e., the Run command is present).
Cannot change parameters | The Access Level is set to restrict access to parameter settings.
Cannot change parameters | The operator is not in the Parameter Setup Mode (the LED screen will display “PAr”).
Cannot change parameters | A multi-function contact input terminal is set to allow or restrict parameter editing (H1-01 through H1-07 = 1B).
Cannot change parameters | The wrong password was entered.
Cannot change parameters | Undervoltage was detected.
Motor does not rotate | The drive is not in the Drive Mode.
Motor does not rotate | The button was pushed.
Motor does not rotate | The [LO/RE] button was pushed.
Motor does not rotate | Auto-Tuning has just completed.
Motor does not rotate | A Fast-Stop was executed and has not yet been reset.
Motor does not rotate | Settings are incorrect for the source that provides the run command.
Motor does not rotate | One of the Safety Inputs is open.
Motor does not rotate | There is faulty wiring in the control circuit terminals.
Cannot change parameters — PDF page 300
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The drive is running the motor (i.e., the Run command is present). | • Stop the drive and switch over to the Programming Mode. • Most parameters cannot be edited during run. |
| 2 | The Access Level is set to restrict access to parameter settings. | • Set the Access Level to allow parameters to be edited (A1-01 = 2). |
| 3 | The operator is not in the Parameter Setup Mode (the LED screen will display “PAr”). | • See what mode the LED parameter is current set for. • Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr” appears on the screen. |
| 4 | A multi-function contact input terminal is set to allow or restrict parameter editing (H1-01 through H1-07 = 1B). | • When the terminal is open, parameters cannot be edited. • Turn on the multi-function contact input set to 1B. |
| 5 | The wrong password was entered. | • If the password entered to A1-04 does not match the password saved to A1-05, then drive settings cannot be changed. • Reset the password. If you cannot remember the password: • Display parameter A1-04. Press the [STOP] button while pressing [UP] at the same time. Parameter A1-05 will appear. • Set a new password to parameter A1-05. |
| 6 | Undervoltage was detected. | • Check the drive input power voltage by looking at the DC bus voltage (U1-07). • Check all main circuit wiring. |
Motor does not rotate — PDF page 300
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The drive is not in the Drive Mode. | • Check if the DRV light on the LED operator is lit. • Enter the Drive Mode to begin operating the motor. Refer to The Drive and Programming Modes on page 84. |
| 2 | The [LO/RE] button was pushed. | Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the source, the LO/RE button LED must be on, if the source is REMOTE, it must be off. Take the following steps to solve the problem: • Push the [LO/RE] button. • If o2-01 is set to 0, then the LO/RE button will be disabled. |
| 3 | Auto-Tuning has just completed. | • When Auto-Tuning has completed, the drive is switched back to the Programming Mode. The Run command will not be accepted unless the drive is in the Drive Mode. • Use the LED operator to enter the Drive Mode. Refer to The Drive and Programming Modes on page 84. |
| 4 | A Fast-Stop was executed and has not yet been reset. | Reset the Fast-Stop command. |
| 5 | Settings are incorrect for the source that provides the run command. | Check parameter b1-02 (Run Command Selection). Set b1-02 so that it corresponds with the correct run command source. 0: LED/LCD operator 1: Control circuit terminal (default setting) 2: MEMOBUS/Modbus communications 3: Option card |
| 6 | One of the Safety Inputs is open. | • Check for a short-circuit between terminals H1 and HC. • See if one of the Safety Inputs is open. • Correct any faulty wiring. |
| 7 | There is faulty wiring in the control circuit terminals. | • Check the wiring for the control terminal. • Correct wiring mistakes. • Check the input terminal status monitor (U1-10). |
Manual — Motor not running and direction troubleshooting — page 301
Source reference: SIEP C71060618F, December 2016, physical PDF page 301. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Cause Possible Solutions
n Motor Rotates in the Opposite Direction from the Run Command
6.9 Troubleshooting without Fault Display
Troubleshooting
Motor does not rotate continued from PDF300 | The drive has been set to accept the frequency reference from the incorrect source.
Motor does not rotate continued from PDF300 | The terminal set to accept the main speed reference is set to the incorrect voltage and/or current.
Motor does not rotate continued from PDF300 | Selection for the sink/source mode is incorrect.
Motor does not rotate continued from PDF300 | Frequency reference is too low.
Motor does not rotate continued from PDF300 | Multi-function analog input is set up to accept gain for the frequency reference, but no voltage (current) has been provided.
Motor does not rotate continued from PDF300 | The STOP button was pressed when the drive was started from a REMOTE source.
Motor does not rotate continued from PDF300 | The [STOP] button was pressed when the drive was started from a REMOTE source.
Motor does not rotate continued from PDF300 | Motor is not producing enough torque in the V/f motor control method.
Motor does not rotate continued from PDF300 | Motor is not producing enough torque in Open Loop Vector Control.
Motor does not rotate continued from PDF300 | The drive is set for both 2-Wire and 3-Wire sequence at the same time.
Motor Rotates in the Opposite Direction from the Run Command | Phase wiring between the drive and motor is incorrect.
Motor Rotates in the Opposite Direction from the Run Command | The forward direction for the motor is setup incorrectly.
Motor does not rotate continued from PDF300 — PDF page 301
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The drive has been set to accept the frequency reference from the incorrect source. | Check parameter b1-01 (Frequency Reference Selection 1). Set b1-01 to the correct source of the frequency reference. 0: LED operator 1: Control circuit terminal (default setting) 2: MEMOBUS/Modbus communications 3: Option card 4: Pulse train input (RP) |
| 2 | The terminal set to accept the main speed reference is set to the incorrect voltage and/or current. | If the frequency reference is set at terminal A1, check parameter H3-01 for the correct signal level selection. If terminal A2 is used, check DIP switch S1. Then select the correct input level for terminal A2 in parameter H3-08. Refer to DIP Switch S1 Analog Input Signal Selection on page 70. |
| 3 | Selection for the sink/source mode is incorrect. | Check DIP switch S3. Refer to Sinking/Sourcing Mode Switch on page 68. |
| 4 | Frequency reference is too low. | • Check the frequency reference monitor (U1-01). • Increase the frequency by changing the maximum output frequency (E1-09). |
| 5 | Multi-function analog input is set up to accept gain for the frequency reference, but no voltage (current) has been provided. | • Check the multi-function analog input settings. • Check if analog input A1 or A2 is set for frequency reference gain (H3-02/10 = 1). If so, check if the correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is applied to the gain input. • Check if H3-02 and H3-10 have been set to the proper values. • Check if the analog input value has been set properly. |
| 6 | The [STOP] button was pressed when the drive was started from a REMOTE source. | • When the [STOP] button is pressed, the drive will decelerate to stop. • Switch off the run command and then re-enter a run command. • The [STOP] button is disabled when o2-02 is set to 0. |
| 7 | Motor is not producing enough torque in the V/f motor control method. | • Ensure the selected V/f pattern corresponds with the characteristics of the motor being used. • Set the correct V/f pattern to E1-03. • When E1-03 = F, increase both the minimum and mid output frequency voltages (E1-08, E1-10). |
| 8 | Motor is not producing enough torque in the V/f motor control method. | Increase the frequency reference so that it is higher than the minimum frequency reference (E1-09). |
| 9 | Motor is not producing enough torque in the V/f motor control method. | Perform Line-to-Line Resistance Auto-Tuning when using particularly long motor cables. |
| 10 | Motor is not producing enough torque in the V/f motor control method. | Increase the torque compensation gain (C4-01). |
| 11 | Motor is not producing enough torque in Open Loop Vector Control. | • Execute Rotational Auto-Tuning. • If the motor cables are replaced with longer cables after Rotational Auto-Tuning was performed, Auto-Tuning may need to be repeated due to voltage drop across the line. |
| 12 | Motor is not producing enough torque in Open Loop Vector Control. | • Check if the torque limit parameters have been set too low (L7-01 through L7-04). • Reset the torque limit back to its default setting (200%). |
| 13 | Motor is not producing enough torque in Open Loop Vector Control. | Increase both the minimum and mid output frequency voltages (E1-08 and E1-10). |
| 14 | The drive is set for both 2-Wire and 3-Wire sequence at the same time. | • The drive is set for a 3-Wire sequence when one of parameters H1-03 through H1-07 is set to 0. • If the drive is supposed to be set up for a 2-Wire sequence, then ensure parameters H1-03 through H1-07 are not set to 0. • If the drive is supposed to be set up for a 3-Wire sequence, then H1-□□ must be set to 0. |
Motor Rotates in the Opposite Direction from the Run Command — PDF page 301
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Phase wiring between the drive and motor is incorrect. | • Check the motor wiring. • Switch two motor cables (U, V, and W) to reverse motor direction. • Connect drive output terminals U/T1, V/T2 and W/T3 in the right order to the corresponding motor terminals U, V, and W. • Change the setting of parameter b1-14. |
| 2 | The forward direction for the motor is setup incorrectly. | Typically, forward is designated as being counterclockwise when looking from the motor shaft (refer to the figure below). Figure labels: 1. Forward Rotating Motor (looking down the motor shaft); 2. Motor Shaft. Exact figure geometry original-only; manufacturer-specific note continues PDF302. |
Manual — Direction, heat and tuning troubleshooting — page 302
Source reference: SIEP C71060618F, December 2016, physical PDF page 302. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Cause Possible Solutions
Note: Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the manufacturer of the motor.
n Motor Rotates in One Direction Only
n Motor is Too Hot
n Drive Does Not Allow Selection of Rotational Auto-Tuning
n Motor Hunting Occurs at Low Speeds
6.9 Troubleshooting without Fault Display
Motor rotates opposite to Run command continued from PDF301 | The motor is running at almost 0 Hz and the Speed Search estimated the speed to be in the opposite direction.
Motor Rotates in One Direction Only | The drive prohibits reverse rotation.
Motor Rotates in One Direction Only | A Reverse run signal has not been entered, although 3-Wire sequence is selected.
Motor is Too Hot | The load is too heavy.
Motor is Too Hot | The air around the motor is too hot.
Motor is Too Hot | The drive is operating in a vector control mode but Auto-Tuning has not yet been performed.
Motor is Too Hot | Insufficient voltage insulation between motor phases.
Motor is Too Hot | The motor fan has stopped or is clogged.
Drive Does Not Allow Selection of Rotational Auto-Tuning | The drive is in the incorrect motor control method for Rotational Auto-Tuning.
Motor Hunting Occurs at Low Speeds | Excessive load inertia in Open Loop Vector Control.
Motor rotates opposite to Run command continued from PDF301 — PDF page 302
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The motor is running at almost 0 Hz and the Speed Search estimated the speed to be in the opposite direction. | • Disable bi-directional search (b3-14 = “0”) so that Speed Search is performed only in the specified direction. |
Motor Rotates in One Direction Only — PDF page 302
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The drive prohibits reverse rotation. | • Check parameter b1-04. • Set the drive to allow the motor to rotate in reverse (b1-04 = “0”). |
| 2 | A Reverse run signal has not been entered, although 3-Wire sequence is selected. | • Make sure that one of the input terminals S3 to S7 used for the 3-Wire sequence has been set for reverse. |
Motor is Too Hot — PDF page 302
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The load is too heavy. | If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque value for an extended period of time. Keep in mind that the motor also has a short-term overload rating in addition to the possible solutions provided below: • Reduce the load. • Increase the acceleration and deceleration times. • Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current (E2-01). • Increase motor capacity. |
| 2 | The air around the motor is too hot. | • Check the ambient temperature. • Cool the area until it is within the specified temperature range. |
| 3 | The drive is operating in a vector control mode but Auto-Tuning has not yet been performed. | • Perform Auto-Tuning. • Calculate the motor value and reset the motor parameters. • Change the motor control method to V/f Control (A1-02 = “0”). |
| 4 | Insufficient voltage insulation between motor phases. | When the motor is connected to terminals U/T1, V/T2, and W/T3, voltage surges occur between the motor coils and drive switching. Normally, surges can reach up to three times the drive input power supply voltage (600 V for 200 V class, and 1200 V for 400 V class). • Use a motor with voltage tolerance higher than the max voltage surge. • Use a motor designed to work specifically with a drive when using a 400 V class unit. • Install an AC reactor on the output side of the drive. |
| 5 | The motor fan has stopped or is clogged. | Check the motor fan. |
Drive Does Not Allow Selection of Rotational Auto-Tuning — PDF page 302
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The drive is in the incorrect motor control method for Rotational Auto-Tuning. | • Check if the drive is set to V/f Control by accident (A1-02 = 0). • Change the motor control method to Open Loop Vector Control (A1-02 = “2”). |
Motor Hunting Occurs at Low Speeds — PDF page 302
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Excessive load inertia in Open Loop Vector Control. | • Excess load inertia can cause motor hunting in Open Loop Vector Control due to slow motor response. • Increase the speed feedback detection control time constant (n2-02) from its default value of 50 ms to an appropriate level between 200 and 1000 ms. Adjust this setting in combination with n2-03 (Feedback Detection Control Time Constant 2). |
Manual — Current, overvoltage and acceleration troubleshooting — page 303
Source reference: SIEP C71060618F, December 2016, physical PDF page 303. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n oPE02 Error Occurs when Lowering the Motor Rated Current Setting
Cause Possible Solutions
n Overvoltage Occurs When Running at a Constant Speed
n Motor Stalls During Acceleration or With Large Loads
n Motor Will Not Accelerate or the Acceleration Time is Too Long
6.9 Troubleshooting without Fault Display
Troubleshooting
oPE02 Error Occurs when Lowering the Motor Rated Current Setting | The motor rated current and the motor no-load current settings in the drive are incorrect.
Overvoltage Occurs When Running at a Constant Speed | Excessive load inertia in Open Loop Vector Control.
Motor Stalls During Acceleration or With Large Loads | Load is too heavy.
Motor Will Not Accelerate or the Acceleration Time is Too Long | Frequency reference is too low.
Motor Will Not Accelerate or the Acceleration Time is Too Long | Load is too heavy.
Motor Will Not Accelerate or the Acceleration Time is Too Long | The torque limit function is operating in Open Loop Vector Control.
Motor Will Not Accelerate or the Acceleration Time is Too Long | Acceleration time has been set too long.
Motor Will Not Accelerate or the Acceleration Time is Too Long | Motor characteristics and drive parameter settings are incompatible with one another in V/f Control.
Motor Will Not Accelerate or the Acceleration Time is Too Long | The right combination of motor characteristics have not been set in Open Loop Vector Control.
Motor Will Not Accelerate or the Acceleration Time is Too Long | Incorrect frequency reference setting.
Motor Will Not Accelerate or the Acceleration Time is Too Long | The Stall Prevention level during acceleration and deceleration set too low.
Motor Will Not Accelerate or the Acceleration Time is Too Long | The Stall Prevention level during run has been set too low.
oPE02 Error Occurs when Lowering the Motor Rated Current Setting — PDF page 303
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The motor rated current and the motor no-load current settings in the drive are incorrect. | The user is trying to set the motor rated current in E2-01 to a value lower than the no-load current set in E2-03. • Make sure that value set in E2-01 is higher than E2-03. Setting E2-01 < E2-03 will trigger an oPE02 error. • If it is necessary to set E2-01 lower than E2-03, first lower the value set to E2-03, then change the setting in E2-01 as needed. |
Overvoltage Occurs When Running at a Constant Speed — PDF page 303
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Excessive load inertia in Open Loop Vector Control. | • Loads with a lot of inertia (fans, etc.) can trigger an overvoltage fault when operating in Open Loop Vector Control. • Switch to the V/f motor control method. • Adjust the values set for the speed feedback detection control time constant (n2-02, n2-03). |
Motor Stalls During Acceleration or With Large Loads — PDF page 303
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Load is too heavy. | Take the following steps to resolve the problem: • Reduce the load. • Increase the acceleration time. • Increase motor capacity. • Although the drive has a Stall Prevention function and a Torque Compensation Limit function, accelerating too quickly or trying to drive an excessively large load can exceed the capabilities of the motor. |
Motor Will Not Accelerate or the Acceleration Time is Too Long — PDF page 303
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Frequency reference is too low. | • Check the maximum output frequency (E1-04). • Increase E1-04 if it is set too low. |
| 2 | Frequency reference is too low. | Check U1-01 for proper frequency reference. |
| 3 | Frequency reference is too low. | Check if a frequency reference signal switch has been set to one of the multi-function input terminals. |
| 4 | Frequency reference is too low. | Check for low gain level set to terminals A1 or A2 (H3-03, H3-11). |
| 5 | Load is too heavy. | • Reduce the load so that the output current remains within the motor-rated current. • In extruder and mixer applications, the load will sometimes increase as the temperature drops. |
| 6 | Load is too heavy. | Check if the mechanical brake is fully releasing as it should. |
| 7 | The torque limit function is operating in Open Loop Vector Control. | • Check the torque limit setting. It may be too low. (L7-01 through L7-04). • Reset the torque limit to its default value (200%). |
| 8 | Acceleration time has been set too long. | Check if the acceleration time parameters have been set too long (C1-01, -03, -05, -07). |
| 9 | Motor characteristics and drive parameter settings are incompatible with one another in V/f Control. | • Set the correct V/f pattern so that it matches the characteristics of the motor being used. • Check E1-03 (V/f Pattern Selection). |
| 10 | The right combination of motor characteristics have not been set in Open Loop Vector Control. | Execute Rotational Auto-Tuning. |
| 11 | Incorrect frequency reference setting. | • Check the multi-function analog input settings. • Check if multi-function analog input terminal A1 or A2 is set for frequency gain (H3-02 or H3-10 = “1”). If so, the frequency reference will be 0 if there is no voltage (current) input provided. • Ensure H3-02 and H3-10 are set to the proper values. • Ensure the analog input value is set to the right value (U1-13, U1-14). |
| 12 | The Stall Prevention level during acceleration and deceleration set too low. | • Check the Stall Prevention level during acceleration (L3-02). • If L3-02 is set too low, acceleration will take a fair amount of time. • Increase L3-02. |
| 13 | The Stall Prevention level during run has been set too low. | • Check the Stall Prevention level during run (L3-06). • If L3-06 is set too low, speed will drop as the drive outputs torque. • Increase the setting value. |
Manual — Acceleration, reference and deceleration troubleshooting — page 304
Source reference: SIEP C71060618F, December 2016, physical PDF page 304. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Cause Possible Solutions
n Drive Frequency Reference Differs from the Controller Frequency Reference Command
n Poor Speed Control Accuracy
n Deceleration Takes Longer Than Expected with Dynamic Braking Enabled
6.9 Troubleshooting without Fault Display
Motor will not accelerate or acceleration time too long continued from PDF303 | Although the drive is operating in Open Loop Vector motor control method, Auto-Tuning has not been performed.
Motor will not accelerate or acceleration time too long continued from PDF303 | Drive reached the limitations of the V/f motor control method.
Drive Frequency Reference Differs from the Controller Frequency Reference Command | The analog input frequency gain and bias are set to incorrect values.
Drive Frequency Reference Differs from the Controller Frequency Reference Command | A frequency bias signal is being entered via analog input terminals A1 or A2.
Poor Speed Control Accuracy | Drive reached the slip compensation limit.
Poor Speed Control Accuracy | Motor-rated voltage is set too high in Open Loop Vector Control.
Poor Speed Control Accuracy | Auto-Tuning did not complete properly for Open Loop Vector Control.
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | L3-04 is set incorrectly.
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | The deceleration time is set too long.
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | Insufficient motor torque.
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | Reaching the torque limit.
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled | Load exceeded the internal torque limit determined by the drive rated current.
Motor will not accelerate or acceleration time too long continued from PDF303 — PDF page 304
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Although the drive is operating in Open Loop Vector motor control method, Auto-Tuning has not been performed. | • Perform Auto-Tuning. • Calculate motor data and reset motor parameters. • Switch to the V/f motor control method (A1-02 = “0”). |
| 2 | Drive reached the limitations of the V/f motor control method. | • The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line resistance. • Be aware that V/f Control is comparatively limited when it comes to producing torque at low speeds. • Consider switching to Open Loop Vector Control. |
Drive Frequency Reference Differs from the Controller Frequency Reference Command — PDF page 304
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The analog input frequency gain and bias are set to incorrect values. | • Check the main speed frequency reference terminal input gain level assigned to terminals A1 and A2, as well as the frequency reference input bias to terminals A1 and A2 (parameters H3-03, H3-04, and H3-12). • Set these parameters to the appropriate values. |
| 2 | A frequency bias signal is being entered via analog input terminals A1 or A2. | • If multi-function analog input terminals A1 and A2 are set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both signals builds the frequency reference. • Ensure that H3-02 and H3-10 are set appropriately. • Check the input level set for terminals A1 and A2 (U1-13, U1-14). |
Poor Speed Control Accuracy — PDF page 304
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Drive reached the slip compensation limit. | • Check the slip compensation limit (C3-03). • Increase the value set to C3-03. |
| 2 | Motor-rated voltage is set too high in Open Loop Vector Control. | • The input voltage for the drive determines the maximum output voltage. A drive with an input of 200 Vac can only output a maximum of 200 Vac. Open Loop Vector Control sometimes calculates an output voltage reference value that exceeds the maximum drive output voltage level, resulting in a loss of speed control accuracy. • Use a motor with a lower voltage rating (a vector control motor). • Increase the input power voltage. |
| 3 | Auto-Tuning did not complete properly for Open Loop Vector Control. | • Perform Auto-Tuning again. |
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled — PDF page 304
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | L3-04 is set incorrectly. | • Check the Stall Prevention Level during deceleration (L3-04). • If a braking resistor option has been installed, disable Stall Prevention during deceleration (L3-04 = “0”). |
| 2 | The deceleration time is set too long. | Set deceleration to more appropriate time (C1-02, C1-04, C1-06, C1-08). |
| 3 | Insufficient motor torque. | • Assuming parameter settings are normal and that no overvoltage occurs when there is insufficient torque, it is likely that the demand on the motor has exceeded the motor capacity. • Use a larger motor. |
| 4 | Reaching the torque limit. | • Check the settings for the torque limit (L7-01 through L7-04). • If the torque limit is enabled, deceleration might take longer than expected because the drive cannot output more torque than the limit setting. Ensure the torque limit is set to a large enough value. • Increase the torque limit setting. |
| 5 | Reaching the torque limit. | • If multi-function analog input terminal A1 or A2 is set to torque limit (H3-02 or H3-10 equals 10, 11, 12, or 15), ensure that the analog input levels are set to the correct levels. • Ensure H3-02 and H3-10 are set to the right levels. • Ensure the analog input is set to the correct value. |
| 6 | Load exceeded the internal torque limit determined by the drive rated current. | Switch to a larger capacity drive. |
Manual — Hunting, elevator brake, noise and GFCI troubleshooting — page 305
Source reference: SIEP C71060618F, December 2016, physical PDF page 305. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n Motor Hunting Occurs When Operating With a Light Load
Cause Possible Solutions
n Load Falls When Brake is Applied (Elevator-Type Applications)
n Noise From Drive or Output Lines When the Drive is Powered On
n Ground Fault Circuit Interrupter (GFCI) Trips During Run
n Connected Machinery Vibrates When Motor Rotates
Excessive Motor Oscillation and Erratic Rotation
Cause Possible Solution
Unexpected Noise from Connected Machinery
Note: The drive may have trouble assessing the status of the load due to white noise generated when using Swing PWM (C6-02 = 7 to A).
6.9 Troubleshooting without Fault Display
Troubleshooting
Motor Hunting Occurs When Operating With a Light Load | Carrier frequency is too high.
Motor Hunting Occurs When Operating With a Light Load | Large V/f setting value at low speeds triggers overexcitation.
Motor Hunting Occurs When Operating With a Light Load | The maximum output frequency and the base frequency reference are not set properly in relationship to each other.
Motor Hunting Occurs When Operating With a Light Load | Hunting Prevention is disabled (V/f control only).
Load Falls When Brake is Applied (Elevator-Type Applications) | The timing for the brake to close and release is not set properly.
Load Falls When Brake is Applied (Elevator-Type Applications) | Insufficient DC Injection Braking.
Noise From Drive or Output Lines When the Drive is Powered On | Relay switching in the drive generates excessive noise.
Ground Fault Circuit Interrupter (GFCI) Trips During Run | Excessive leakage current trips MCCB.
Excessive Motor Oscillation and Erratic Rotation | Poor balance between motor phases.
Unexpected Noise from Connected Machinery | The carrier frequency is at the resonant frequency of the connected machinery.
Unexpected Noise from Connected Machinery | The drive output frequency is the same as the resonant frequency of the connected machinery.
Motor Hunting Occurs When Operating With a Light Load — PDF page 305
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Carrier frequency is too high. | Lower the carrier frequency setting C6-02. |
| 2 | Large V/f setting value at low speeds triggers overexcitation. | • Select the proper V/f pattern (E1-03). • Use parameters E1-04 through E1-10 to set the V/f pattern in relation to the load characteristics. |
| 3 | The maximum output frequency and the base frequency reference are not set properly in relationship to each other. | Set the proper values for the maximum output frequency and base frequency (E1-04, E1-06). |
| 4 | Hunting Prevention is disabled (V/f control only). | • Enable Hunting Prevention by setting n1-01 = “1”. • (OLV only) Increase the speed feedback detection control gain and time constant (n2-01, n2-02). |
Load Falls When Brake is Applied (Elevator-Type Applications) — PDF page 305
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The timing for the brake to close and release is not set properly. | Use frequency reference detection for closing and releasing the brake. • At start: Release the brake after creating enough torque. • At stop: Close the brake when the motor still produces torque. Make the following setting changes to hold the brake: • Set the frequency detection inactive during baseblock (L4-07 = 0). • Multi-function contact output terminal will switch on when the output frequency is greater than the frequency detection level set in L4-01. Set L4-01 between 1.0 and 3.0 Hz. • Slipping may occur when stopping because hysteresis is used in Frequency Reference 2 (where the frequency agree setting in L4-02 is 2.0 Hz). To prevent this, change the setting to 0.1 Hz. • Do not use the multi-function contact output setting “During Run” (H2-01 = 0) for the brake signal. |
| 2 | Insufficient DC Injection Braking. | Increase the amount of DC Injection Braking (b2-02). |
Noise From Drive or Output Lines When the Drive is Powered On — PDF page 305
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Relay switching in the drive generates excessive noise. | • Lower the carrier frequency (C6-02). • Install a noise filter on the input side of drive input power. • Install a noise filter on the output side of the drive. • Place the wiring inside a metal conduit to shield it from switching noise. • Ground the drive and motor properly. • Separate the main circuit wiring and the control lines. |
Ground Fault Circuit Interrupter (GFCI) Trips During Run — PDF page 305
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Excessive leakage current trips MCCB. | • Increase the GFCI sensitivity or use GFCI with a higher threshold. • Lower the carrier frequency (C6-02). • Reduce the length of the cable used between the drive and the motor. • Install a noise filter or reactor on the output side of the drive. |
Excessive Motor Oscillation and Erratic Rotation — PDF page 305
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Poor balance between motor phases. | Check drive input power voltage to ensure that it provides stable power. |
Unexpected Noise from Connected Machinery — PDF page 305
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The carrier frequency is at the resonant frequency of the connected machinery. | Adjust the carrier frequency using parameters C6-02 through C6-05. |
| 2 | The drive output frequency is the same as the resonant frequency of the connected machinery. | • Adjust the parameters used for the Jump Frequency function (d3-01 through d3-04) to skip the problem-causing bandwidth. • Place the motor on a rubber pad to reduce vibration. |
Manual — Oscillation, PID, torque and stopping troubleshooting — page 306
Source reference: SIEP C71060618F, December 2016, physical PDF page 306. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n Oscillation or Hunting
Cause Possible Solutions
n PID Output Fault
n Insufficient Motor Torque
n Motor Rotates After the Drive Output is Shut Off
6.9 Troubleshooting without Fault Display
Oscillation or Hunting | Insufficient tuning in Open Loop Vector Control
Oscillation or Hunting | Auto-Tuning has not yet been performed (required for Open Loop Vector Control).
Oscillation or Hunting | Insufficient tuning in V/f Control.
Oscillation or Hunting | Gain is too low when using PID control.
Oscillation or Hunting | The frequency reference is assigned to an external source and the signal is noisy.
Oscillation or Hunting | The cable between the drive and motor is too long.
PID Output Fault | No PID feedback input.
PID Output Fault | The level of detection and the target value do not correspond with each other.
PID Output Fault | Reverse drive output frequency and speed detection. When output frequency rises, the sensor detects a speed decrease.
Insufficient Motor Torque | Auto-Tuning has not yet been performed (required for OLV Control).
Insufficient Motor Torque | The control mode was changed after performing Auto- Tuning.
Insufficient Motor Torque | Only Line-to-Line Resistance Auto-Tuning was performed.
Motor Rotates After the Drive Output is Shut Off | Low DC Injection Braking and the drive cannot decelerate properly.
Oscillation or Hunting — PDF page 306
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Insufficient tuning in Open Loop Vector Control | Adjust the following parameters in the order listed. An increase in gain should be followed with an increase in the primary delay time constant. • C4-02 (Torque Compensation Primary Delay Time) • n2-01 (Speed Feedback Detection Control [AFR] Time Constant 1) • C3-02 (Slip Compensation Primary Delay Time) The response for torque compensation and slip compensation will drop as the time constant is increased. |
| 2 | Auto-Tuning has not yet been performed (required for Open Loop Vector Control). | Perform Auto-Tuning. Set motor parameters after calculating the proper values. Change the motor control method to V/f Control (A1-02 = “0”). |
| 3 | Insufficient tuning in V/f Control. | Reduce the gain. • n1-02 (Hunting Prevention Gain Setting) • n1-03 (Hunting Prevention Time Constant Setting) |
| 4 | Gain is too low when using PID control. | Check the period of oscillation and adjust P, I, and D settings accordingly. |
| 5 | The frequency reference is assigned to an external source and the signal is noisy. | • Ensure that noise is not affecting the signal lines. • Separate main circuit wiring and control circuit wiring. • Use twisted-pair cables or shielded wiring for the control circuit. • Increase the analog input time filter constant (H3-13). |
| 6 | The cable between the drive and motor is too long. | • Perform Auto-Tuning. • Reduce the length of the cable. |
PID Output Fault — PDF page 306
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | No PID feedback input. | • Check the multi-function analog input terminal settings. • Set multi-function analog input terminal A1 or A2 for PID feedback (H3-02 or H3-10 = “B”). • A signal input to the terminal selection for PID feedback is necessary. • Check the connection of the feedback signal. • Check the various PID-related parameter settings. • No PID feedback input to the terminal causes the value detected to be 0, causing a PID fault and the drive to operate at max frequency. |
| 2 | The level of detection and the target value do not correspond with each other. | • PID control keeps the difference between target and detection values at 0. Set the input level for the values relative to one another. • Use analog input gains H3-03/11 to adjust PID target and feedback signal scaling. |
| 3 | Reverse drive output frequency and speed detection. When output frequency rises, the sensor detects a speed decrease. | Set PID output for reverse characteristics (b5-09 = “1”). |
Insufficient Motor Torque — PDF page 306
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Auto-Tuning has not yet been performed (required for OLV Control). | Perform Auto-Tuning. |
| 2 | The control mode was changed after performing Auto- Tuning. | Perform Auto-Tuning again. |
| 3 | Only Line-to-Line Resistance Auto-Tuning was performed. | Perform Rotational Auto-Tuning. |
Motor Rotates After the Drive Output is Shut Off — PDF page 306
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Low DC Injection Braking and the drive cannot decelerate properly. | • Adjust the DC Injection braking settings. • Increase the value of b2-02 (DC Injection Braking Current). • Increase the b2-04 (DC Injection Braking Time at Stop). |
Manual — Rotating load, frequency, PM and Run troubleshooting — page 307
Source reference: SIEP C71060618F, December 2016, physical PDF page 307. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n ov or Speed Loss Occurs When Starting into a Rotating Load
Cause Possible Solutions
n Output Frequency is not as High as Frequency Reference
n Buzzing Sound from Motor at 2 kHz
n Unstable Motor Speed when Using PM or IPM
n Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed
n Motor Does Not Operate When an External Run Command is Input
6.9 Troubleshooting without Fault Display
Troubleshooting
ov or Speed Loss Occurs When Starting into a Rotating Load | The load is already rotating when the drive is trying to start it.
Output Frequency is not as High as Frequency Reference | Frequency reference is set within the range of the Jump Frequency.
Output Frequency is not as High as Frequency Reference | Upper limit for the frequency reference has been exceeded.
Output Frequency is not as High as Frequency Reference | Large load triggered Stall Prevention function during acceleration.
Buzzing Sound from Motor at 2 kHz | Exceeded 110% of the rated output current of the drive while operating at low speeds.
Unstable Motor Speed when Using PM or IPM | The motor code for PM (E5-01) is set incorrectly. (Yaskawa motors only)
Unstable Motor Speed when Using PM or IPM | The drive is operating at less than 10% of the speed reference.
Unstable Motor Speed when Using PM or IPM | Motor hunting occurs.
Unstable Motor Speed when Using PM or IPM | Hunting occurs at start.
Unstable Motor Speed when Using PM or IPM | Too much current is flowing through the drive.
Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed | The LOCAL/REMOTE mode is not selected properly.
Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed | The drive is not in drive mode.
Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed | The frequency reference is too low.
Motor Does Not Operate When an External Run Command is Input | The LOCAL/REMOTE mode is not selected properly.
Motor Does Not Operate When an External Run Command is Input | The drive is not in Drive Mode.
ov or Speed Loss Occurs When Starting into a Rotating Load — PDF page 307
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The load is already rotating when the drive is trying to start it. | • Stop the motor using DC Injection braking. Restart the motor. • Increase the value of b2-03 (DC Injection Braking Time at start). • Enable Speed Search at start (b3-01 = “1”). • Set a multi-function input terminal for external Speed Search command (H1-□□=“61” or “62” during restart). |
Output Frequency is not as High as Frequency Reference — PDF page 307
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Frequency reference is set within the range of the Jump Frequency. | • Adjust the parameters used for the Jump Frequency function (d3-01, d3-02, d3-03). • Enabling the Jump Frequency prevents the drive from outputting the frequencies specified in the Jump Frequency range. |
| 2 | Upper limit for the frequency reference has been exceeded. | • Set the maximum output frequency and the upper limit for the frequency reference to more appropriate values (E1-04, d2-01). • The following calculation yields the upper value for the output frequency = E1-04 x d2-01 / 100 |
| 3 | Large load triggered Stall Prevention function during acceleration. | • Reduce the load. • Adjust the Stall Prevention level during acceleration (L3-02). |
Buzzing Sound from Motor at 2 kHz — PDF page 307
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Exceeded 110% of the rated output current of the drive while operating at low speeds. | • If the output current rises too high at low speeds, the carrier frequency automatically reduces and causes a whining or buzzing sound. • If the sound is coming from the motor, disable carrier frequency derating (L8-38 = “0”). • Disabling the automatic carrier frequency derating increases the chances of an overload fault (oL2). Switch to a larger capacity motor if oL2 faults occur too frequently. |
Unstable Motor Speed when Using PM or IPM — PDF page 307
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The motor code for PM (E5-01) is set incorrectly. (Yaskawa motors only) | Set parameter E5-01 in accordance with the motor being used. |
| 2 | The drive is operating at less than 10% of the speed reference. | Consult with Yaskawa about using a different type of motor when attempting to operate at 10% of the speed reference. |
| 3 | Motor hunting occurs. | Set and carefully adjust the following parameters in the order listed: • n8-45 (Speed Feedback Detection Suppression Gain) • n8-55 (Load Inertia for PM Motors) • C4-02 (Torque Compensation Primary Delay Time) |
| 4 | Hunting occurs at start. | Increase the S-curve time at the start of acceleration (C2-01). |
| 5 | Too much current is flowing through the drive. | • If using a PM motor, set the correct motor code to E5-01. • If using a specialized motor, set parameter E5-xx to the correct value according to the Motor Test Report. |
Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed — PDF page 307
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The LOCAL/REMOTE mode is not selected properly. | Press the LOCAL/REMOTE button to switch. The LO/RE LED should be on for LOCAL mode. |
| 2 | The drive is not in drive mode. | A run command will not be issued. Exit to the drive mode and cycle the run command. |
| 3 | The frequency reference is too low. | • If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the drive will not operate. • Raise the frequency reference to at least the minimum output frequency. |
Motor Does Not Operate When an External Run Command is Input — PDF page 307
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The LOCAL/REMOTE mode is not selected properly. | Press the LOCAL/REMOTE button to switch. The LO/RE LED should be off for REMOTE mode. |
| 2 | The drive is not in Drive Mode. | A run command will not be issued. Exit to the Drive mode and cycle the run command. |
Manual — External Run, direction, PID and interference troubleshooting — page 308
Source reference: SIEP C71060618F, December 2016, physical PDF page 308. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Cause Possible Solutions
n Motor Stops During Acceleration or When a Load is Connected
Cause Possible Solution
n Motor Rotates in One Direction Only
n Motor Operates at a Higher Speed than the Speed Command
n Poor Speed Control Accuracy Above Base Speed in Open Loop Vector Motor Control Method
n Peripheral Devices Affected by Drive Operation
n Ground Fault Interrupter Activates When Drive is Running
6.9 Troubleshooting without Fault Display
Motor does not operate on external Run continued from PDF307 | The frequency reference is too low.
Motor Stops During Acceleration or When a Load is Connected | • The load is too heavy. • The limit of motor response may be reached during rapid acceleration. This may be a result of improper stall prevention or automatic torque boost function adjustment.
Motor Rotates in One Direction Only | "Reverse run prohibited" is selected. If b1-04 (Reverse Prohibit Operation) is set to 1 (reverse run prohibited), the drive will not accept a reverse run command.
Motor Rotates in One Direction Only | The drive prohibits reverse rotation.
Motor Rotates in One Direction Only | A Reverse run signal has not been entered, although 3- Wire sequence is selected.
Motor Operates at a Higher Speed than the Speed Command | PID is enabled. If the PID mode is enabled (b5-01 = 1 to 4), the drive output frequency will change to regulate the process variable to the target setpoint. The PID can command a speed up to maximum output frequency (E1-04).
Poor Speed Control Accuracy Above Base Speed in Open Loop Vector Motor Control Method | The maximum output voltage of the drive is determined by its input voltage. Vector control uses voltage to control the currents within the motor. If the vector control voltage reference value exceeds the drive output voltage capability, the speed control accuracy will decrease because the motor currents cannot be properly controlled.
Peripheral Devices Affected by Drive Operation | Radio frequency interference may be generated by drive output PWM waveform.
Ground Fault Interrupter Activates When Drive is Running | The output of the drive is a series of high frequency pulses (PWM), so there is a certain amount of leakage current. This may cause the ground fault interrupter to operate and cut off the drive input power.
Motor does not operate on external Run continued from PDF307 — PDF page 308
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The frequency reference is too low. | • If the frequency reference is set below the frequency set in E1-09 (Minimum Output Frequency), the drive will not operate. • Raise the frequency reference to at least the minimum output frequency. |
Motor Stops During Acceleration or When a Load is Connected — PDF page 308
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | • The load is too heavy. • The limit of motor response may be reached during rapid acceleration. This may be a result of improper stall prevention or automatic torque boost function adjustment. | Increase the acceleration time (C1-01) or reduce the motor load. Also, consider increasing the motor size and/or drive size. |
Motor Rotates in One Direction Only — PDF page 308
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | "Reverse run prohibited" is selected. If b1-04 (Reverse Prohibit Operation) is set to 1 (reverse run prohibited), the drive will not accept a reverse run command. | Set b1-04 = “0” to allow reverse run operation. |
| 2 | The drive prohibits reverse rotation. | • Check parameter b1-04. • Set the drive to allow the motor to rotate in reverse (b1-04 = “0”). |
| 3 | A Reverse run signal has not been entered, although 3- Wire sequence is selected. | • Make sure that one of the input terminals S3 to S5 used for the 3-Wire sequence has been set for reverse. |
Motor Operates at a Higher Speed than the Speed Command — PDF page 308
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | PID is enabled. If the PID mode is enabled (b5-01 = 1 to 4), the drive output frequency will change to regulate the process variable to the target setpoint. The PID can command a speed up to maximum output frequency (E1-04). | If PID operation is not target, disable PID by setting b5-01 = “0”. |
Poor Speed Control Accuracy Above Base Speed in Open Loop Vector Motor Control Method — PDF page 308
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The maximum output voltage of the drive is determined by its input voltage. Vector control uses voltage to control the currents within the motor. If the vector control voltage reference value exceeds the drive output voltage capability, the speed control accuracy will decrease because the motor currents cannot be properly controlled. | Use a motor with a lower rated voltage compared to the input voltage. |
Peripheral Devices Affected by Drive Operation — PDF page 308
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | Radio frequency interference may be generated by drive output PWM waveform. | • Change the Carrier Frequency Selection (C6-02) to lower the carrier frequency. This will help to reduce the amount of transistor switching noise. • Install an Input Noise Filter at the input power terminals. • Install an Output Noise Filter at the motor terminals. • Use conduit. Metal can shield electrical noise. • Ground the drive and motor. • Separate main circuit wiring from control wiring. |
Ground Fault Interrupter Activates When Drive is Running — PDF page 308
| Source row | Cause | Possible solutions |
|---|---|---|
| 1 | The output of the drive is a series of high frequency pulses (PWM), so there is a certain amount of leakage current. This may cause the ground fault interrupter to operate and cut off the drive input power. | • Change to a ground fault interrupter with a higher leakage current detection level (such as, a sensitivity current of 200 mA or greater per Unit, with an operating time of 0.1 s or more), or one that incorporates high-frequency corrective actions. • Change the Carrier Frequency Selection (C6-02) to lower the carrier frequency. Note: Leakage current increases in proportion to cable length. |
Manual — Maintenance section safety — page 310
Source reference: SIEP C71060618F, December 2016, physical PDF page 310. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
7.1 Section Safety
DANGER
Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material.
Manual — Maintenance equipment notices — page 311
Source reference: SIEP C71060618F, December 2016, physical PDF page 311. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive.
7.1 Section Safety
Periodic Inspection & Maintenance
Manual — Inspection conditions and daily checklist — page 312
Source reference: SIEP C71060618F, December 2016, physical PDF page 312. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
7.2 Inspection
Power electronics have limited life and may exhibit changed characteristics or performance deterioration after years of use under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and periodic inspection on the drive. Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and relays. The electronics in the drive serve a critical role in maintaining proper motor control. Follow the inspection lists provided in this chapter as a part of a regular maintenance program. Note: The drive will require more frequent inspection if it is placed in harsh environments, such as: • High ambient temperatures • Frequent starting and stopping • Fluctuations in the AC supply or load • Excessive vibrations or shock loading • Dust, metal dust, salt, sulfuric acid, chlorine atmospheres • Poor storage conditions. Perform the first equipment inspection 3 months after installation.
u Recommended Daily Inspection
Table 7.1 outlines the recommended daily inspection for Yaskawa drives. Check the following items on a daily basis to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection.
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
Table 7.1 General Recommended Daily Inspection Checklist
Inspection Category Inspection Points Corrective Action Checked
Daily Inspection checklist — blank Checked cells are template, not completed inspections | Motor
Daily Inspection checklist — blank Checked cells are template, not completed inspections | Cooling
Daily Inspection checklist — blank Checked cells are template, not completed inspections | Cooling Fan
Daily Inspection checklist — blank Checked cells are template, not completed inspections | Environment
Daily Inspection checklist — blank Checked cells are template, not completed inspections | Load
Daily Inspection checklist — blank Checked cells are template, not completed inspections | Power Supply Voltage
Daily Inspection checklist — blank Checked cells are template, not completed inspections — PDF page 312
| Source row | Inspection category | Inspection points | Corrective action | Checked (blank template) |
|---|---|---|---|---|
| 1 | Motor | • Inspect for abnormal oscillation or noise coming from the motor. | • Check the load coupling. • Measure motor vibration. • Tighten all loose components. | ⟦blank source cell⟧ |
| 2 | Cooling | • Inspect for abnormal heat generated from the drive or motor and visible discoloration. | • Check for excessive load. • Loose connections • Check for dirty heatsink or motor. • Ambient temperature | ⟦blank source cell⟧ |
| 3 | Cooling Fan | • Inspect drive cooling fan operation. | • Check for clogged or dirty fan. • Check fan operation drive parameter. | ⟦blank source cell⟧ |
| 4 | Environment | • Verify the drive environment complies with the specifications listed in the Installation section of this manual. | • Eliminate the source of contaminants or correct poor environment. | ⟦blank source cell⟧ |
| 5 | Load | • The drive output current should not be higher than the motor or drive rating for an extended period of time. | • Check for excessive load. • Check the motor parameter settings of the drive. | ⟦blank source cell⟧ |
| 6 | Power Supply Voltage | • Check main power supply and control voltages. | • Correct the voltage or power supply to within nameplate specifications. • Verify all main circuit phases. | ⟦blank source cell⟧ |
Manual — Periodic inspection checklist — page 313
Source reference: SIEP C71060618F, December 2016, physical PDF page 313. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u Recommended Periodic Inspection
Table 7.2 outlines the recommended periodic inspections for Yaskawa drive installations. Periodic inspections should generally be checked every 3-6 months; however, the drive may require more frequent inspection due to poor environments or rigorous use. Operating and environmental conditions, along with experience in each application, will determine the actual inspection frequency for each installation. Periodic inspection will help to avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column after each inspection.
n Periodic Inspection
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
Table 7.2 Periodic Inspection Checklist
Inspection Area Inspection Points Corrective Action Checked Main Circuit Periodic Inspection
Motor Periodic Inspection
Control Circuit Periodic Inspection
Cooling System Periodic Inspection
LED Periodic Inspection
Note: Periodic inspections should be performed every one or two years. The drive, however, may require more frequent inspection due to poor environments or rigorous use.
7.2 Inspection
Periodic Inspection & Maintenance
Periodic Inspection — Main Circuit — blank Checked cells are template | General
Periodic Inspection — Main Circuit — blank Checked cells are template | Conductors and Wiring
Periodic Inspection — Main Circuit — blank Checked cells are template | Terminals
Periodic Inspection — Main Circuit — blank Checked cells are template | Relays and Contactors
Periodic Inspection — Main Circuit — blank Checked cells are template | Braking Resistors
Periodic Inspection — Motor — blank Checked cells are template | Operation Check
Periodic Inspection — Control Circuit — blank Checked cells are template | General
Periodic Inspection — Cooling System — blank Checked cells are template | Cooling Fan
Periodic Inspection — Cooling System — blank Checked cells are template | Heatsink
Periodic Inspection — Cooling System — blank Checked cells are template | Air Duct
Periodic Inspection — LED — blank Checked cells are template | LEDs
Periodic Inspection — Main Circuit — blank Checked cells are template — PDF page 313
| Source row | Inspection area | Inspection points | Corrective action | Checked (blank template) |
|---|---|---|---|---|
| 1 | General | • Overall check of the main power circuit and ground terminals | Take appropriate actions (e.g., tightening loose connections). | ⟦blank source cell⟧ |
| 2 | General | • Inspect equipment for discoloration from overheating or deterioration. • Inspect for damaged or deformed parts. | • Replace damaged components as required. • The drive has few serviceable parts and may require complete drive replacement. | ⟦blank source cell⟧ |
| 3 | General | • Inspect for dirt, foreign particles, or dust collection on components. | • Inspect enclosure door seal if present. Replace components if cleaning is not possible. • Remove foreign particles and dust with a vacuum cleaner to avoid touching parts. | ⟦blank source cell⟧ |
| 4 | Conductors and Wiring | • Inspect wiring and connections for discoloration, damage, or heat stress. • Inspect wire insulation and shielding for wear. | • Repair or replace damaged wiring. | ⟦blank source cell⟧ |
| 5 | Terminals | • Inspect terminals for stripped, damaged, or loose connections. | • Tighten loose screws and replace damaged screws or terminals. | ⟦blank source cell⟧ |
| 6 | Relays and Contactors | • Inspect contactors and relays for excessive noise during operation. • Inspect coils for signs of overheating such as melted or cracked insulation. | • Check coil voltage for over or under voltage conditions. • Replace damaged removable relays contactors or circuit board. | ⟦blank source cell⟧ |
| 7 | Braking Resistors | • Inspect for discoloration of heat stress on or around resistors. | • Minor discoloration may be acceptable. • If discoloration exists check for loose connections. | ⟦blank source cell⟧ |
Periodic Inspection — Motor — blank Checked cells are template — PDF page 313
| Source row | Inspection area | Inspection points | Corrective action | Checked (blank template) |
|---|---|---|---|---|
| 1 | Operation Check | • Check for increased vibration or abnormal noise. | • Stop the motor and contact qualified maintenance personnel as required. | ⟦blank source cell⟧ |
Periodic Inspection — Control Circuit — blank Checked cells are template — PDF page 313
| Source row | Inspection area | Inspection points | Corrective action | Checked (blank template) |
|---|---|---|---|---|
| 1 | General | • Inspect terminals for stripped, damaged or loose connections. • Check for tightness. | • Tighten loose screws and replace damaged screws or terminals. • If terminals are integral to a circuit board then board or drive replacement may be required. | ⟦blank source cell⟧ |
Periodic Inspection — Cooling System — blank Checked cells are template — PDF page 313
| Source row | Inspection area | Inspection points | Corrective action | Checked (blank template) |
|---|---|---|---|---|
| 1 | Cooling Fan | • Check for abnormal oscillation or unusual noise. • Check for damaged or missing fan blades. | • Replace as required. • Refer to Drive Cooling Fans on page 316 for information on cleaning or replacing the cooling fan. | ⟦blank source cell⟧ |
| 2 | Heatsink | • Inspect for dust or other foreign material collected on the surface. | • Remove foreign particles and dust with a vacuum cleaner to avoid touching parts. | ⟦blank source cell⟧ |
| 3 | Air Duct | • Inspect air intake and exhaust openings. They must be free from obstruction and properly installed. | • Visually inspect the area. • Clear obstructions and clean air duct as required. | ⟦blank source cell⟧ |
Periodic Inspection — LED — blank Checked cells are template — PDF page 313
| Source row | Inspection area | Inspection points | Corrective action | Checked (blank template) |
|---|---|---|---|---|
| 1 | LEDs | • Make sure the LED lights correctly. • Inspect for dust or other foreign material that may have collected on surrounding components. | • Contact your Yaskawa representative if there is any trouble with the LED or keypad. • Clean the LED. | ⟦blank source cell⟧ |
Manual — Estimated component life and monitors — page 314
Source reference: SIEP C71060618F, December 2016, physical PDF page 314. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
7.3 Periodic Maintenance
The drive has various "maintenance monitors." This feature provides advance maintenance warning and eliminates the need to shut down the entire system for unexpected problems. The drive allows the user to check the following maintenance periods. • Cooling Fan • Electrolytic Capacitors (Main Circuit) • Inrush Prevention Circuit • IGBT
u Replacement Parts
Table 7.3 contains the estimated performance life of components that require replacement during the life of the drive. Only use Yaskawa replacement parts for the appropriate drive model and revision.
Table 7.3 Estimated Performance Life
Component Estimated Performance Life
<1> The drive has few serviceable parts and may require complete drive replacement.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing parts to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use. Usage conditions for estimated performance life: • Ambient temperature: Yearly average of 40 °C • Load factor: 80% maximum • Operation time: 24 hours a day
n Performance Life Monitors
The drive calculates the maintenance period for components that may require replacement during the life of the drive. A percentage of the maintenance period is displayed on the LED digital operator by viewing the appropriate monitor parameter. When the maintenance period reaches 100%, there is increased risk that the drive may malfunction. Yaskawa recommends checking the maintenance period regularly to ensure maximum performance life. Refer to Recommended Periodic Inspection on page 313 for more details.
Table 7.4 Performance Life Monitors Used for Component Replacement
Parameter Component Contents
Estimated Performance Life under stated annual average40°C,80%loadmaximum,24h/day conditions | Cooling Fan
Estimated Performance Life under stated annual average40°C,80%loadmaximum,24h/day conditions | Electrolytic Capacitors (Main Circuit)
Maintenance Monitors | U4-03
Maintenance Monitors | U4-04
Maintenance Monitors | U4-05
Maintenance Monitors | U4-06
Maintenance Monitors | U4-07
Estimated Performance Life under stated annual average40°C,80%loadmaximum,24h/day conditions — PDF page 314
| Source row | Component | Estimated performance life |
|---|---|---|
| 1 | Cooling Fan | 10 years |
| 2 | Electrolytic Capacitors (Main Circuit) | 10 years <1> |
Maintenance Monitors — PDF page 314
| Source row | Parameter | Component | Contents |
|---|---|---|---|
| 1 | U4-03 | Cooling Fan | Displays the accumulated operation time of the cooling fan, from 0 to 99999 hours. This value is automatically reset to 0 once it reaches 99999. |
| 2 | U4-04 | Cooling Fan | Displays the accumulated cooling fan operation time as a percentage of the specified maintenance period (displayed in percent %). |
| 3 | U4-05 | Main Circuit (DC bus) Electrolytic Capacitors | Displays the accumulated time the capacitors are used as a percentage of the specified maintenance period. |
| 4 | U4-06 | Inrush (pre-charge) relay | Displays the number of times the drive is powered up as a percentage of the performance life of the inrush circuit. |
| 5 | U4-07 | IGBT | Displays the percentage of the maintenance period reached by the IGBTs. |
Manual — Maintenance alarms and counter reset — page 315
Source reference: SIEP C71060618F, December 2016, physical PDF page 315. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
n Alarm Outputs for Maintenance Monitors
An output can be set up to inform the user when a specific components has neared its expected performance life. When one of multi-function digital output terminals has been assigned the maintenance monitor function (H2-□□ = 2F), the terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected performance life, or when the IGBTs have reached 50% of their expected performance life. Additionally the digital operator will display an alarm like shown in Table 7.5 to indicate the specific components that may need maintenance.
Table 7.5 Maintenance Alarms Digital Operator Alarm Display Function Corrective Action
<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2-□□ = 2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2-□□ = 10). <2> This alarm message will always be output, even if the Maintenance Monitor function is not assigned to any of the digital outputs (H2-□□ = 2F). The alarm will also trigger a digital output that is programmed for alarm indication (H2-□□ = 10).
n Related Drive Parameters
Use parameters o4-03, o4-05, o4-07, and o4-09 to reset a Maintenance Monitor to zero after replacing a specific component. Refer to Parameter List on page 353 for details on parameter settings.
NOTICE: If these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will continue to count down the performance life from the value that was reached with the old part. If the Maintenance Monitor is not reset, the drive will not have the correct value of the performance life for the new component.
7.3 Periodic Maintenance
Periodic Inspection & Maintenance
Maintenance Alarms | <1>
Maintenance Alarms | LT-1 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.
Maintenance Alarms | LT-2 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.
Maintenance Alarms | LT-3 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.
Maintenance Alarms | LT-4 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only.
Maintenance Alarms | <2>
Maintenance Alarms | TrPC <2>; visible seven-segment graphic beside literal code, exact segment geometry original-only.
Maintenance Alarms — PDF page 315
| Source row | Seven-segment graphic / footnote | Literal alarm display | Function | Corrective action |
|---|---|---|---|---|
| 1 | LT-1 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. | LT-1 | The cooling fans have reached 90% of their designated life time. | Replace the cooling fan. |
| 2 | LT-2 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. | LT-2 | The DC bus capacitors have reached 90% of their designated life time. | Contact a Yaskawa representative or the nearest Yaskawa sales office on possible drive replacement. |
| 3 | LT-3 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. | LT-3 | The DC bus charge circuit has reached 90% of its designated life time. | Contact a Yaskawa representative or the nearest Yaskawa sales office on possible drive replacement. |
| 4 | LT-4 <1>; visible seven-segment graphic beside literal code, exact segment geometry original-only. | LT-4 | The IGBTs have reached 50% of their designated life time. | Check the load, carrier frequency, and output frequency. |
| 5 | TrPC <2>; visible seven-segment graphic beside literal code, exact segment geometry original-only. | TrPC | The IGBTs have reached 90% of their designated life time. | Contact a Yaskawa representative or the nearest Yaskawa sales office on possible drive replacement. |
Manual — Cooling fan counts by model and class — page 316
Source reference: SIEP C71060618F, December 2016, physical PDF page 316. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
7.4 Drive Cooling Fans
NOTICE: Follow cooling fan replacement instructions. The cooling fan cannot operate properly when installed incorrectly and could seriously damage the drive. To ensure maximum useful product life, replace all cooling fans when performing maintenance. Contact your Yaskawa representative or supplier to order replacement cooling fans as required. Some drive models have multiple cooling fans. For drives with multiple cooling fans, replace all the fans when performing maintenance to ensure maximum useful product life.
u Number of Cooling Fans
Drive Model Cooling Fans Single-Phase 200 V Class
Three-Phase 200 V Class
Three-Phase 400 V Class
Cooling fans — Single-Phase 200 V Class | BA0001
Cooling fans — Single-Phase 200 V Class | BA0002
Cooling fans — Single-Phase 200 V Class | BA0003
Cooling fans — Single-Phase 200 V Class | BA0006
Cooling fans — Single-Phase 200 V Class | BA0010
Cooling fans — Single-Phase 200 V Class | BA0012
Cooling fans — Single-Phase 200 V Class | BA0018
Cooling fans — Three-Phase 200 V Class | 2A0001
Cooling fans — Three-Phase 200 V Class | 2A0002
Cooling fans — Three-Phase 200 V Class | 2A0004
Cooling fans — Three-Phase 200 V Class | 2A0006
Cooling fans — Three-Phase 200 V Class | 2A0010
Cooling fans — Three-Phase 200 V Class | 2A0012
Cooling fans — Three-Phase 200 V Class | 2A0020
Cooling fans — Three-Phase 200 V Class | 2A0030
Cooling fans — Three-Phase 200 V Class | 2A0040
Cooling fans — Three-Phase 200 V Class | 2A0056
Cooling fans — Three-Phase 200 V Class | 2A0069
Cooling fans — Three-Phase 400 V Class | 4A0001
Cooling fans — Three-Phase 400 V Class | 4A0002
Cooling fans — Three-Phase 400 V Class | 4A0004
Cooling fans — Three-Phase 400 V Class | 4A0005
Cooling fans — Three-Phase 400 V Class | 4A0007
Cooling fans — Three-Phase 400 V Class | 4A0009
Cooling fans — Three-Phase 400 V Class | 4A0011
Cooling fans — Three-Phase 400 V Class | 4A0018
Cooling fans — Three-Phase 400 V Class | 4A0023
Cooling fans — Three-Phase 400 V Class | 4A0031
Cooling fans — Three-Phase 400 V Class | 4A0038
Cooling fans — Single-Phase 200 V Class — PDF page 316
| Source row | Drive model | Cooling fans |
|---|---|---|
| 1 | BA0001 | – |
| 2 | BA0002 | – |
| 3 | BA0003 | – |
| 4 | BA0006 | – |
| 5 | BA0010 | 1 |
| 6 | BA0012 | 1 |
| 7 | BA0018 | 2 |
Cooling fans — Three-Phase 200 V Class — PDF page 316
| Source row | Drive model | Cooling fans |
|---|---|---|
| 1 | 2A0001 | – |
| 2 | 2A0002 | – |
| 3 | 2A0004 | – |
| 4 | 2A0006 | 1 |
| 5 | 2A0010 | 1 |
| 6 | 2A0012 | 1 |
| 7 | 2A0020 | 1 |
| 8 | 2A0030 | 2 |
| 9 | 2A0040 | 2 |
| 10 | 2A0056 | 2 |
| 11 | 2A0069 | 2 |
Cooling fans — Three-Phase 400 V Class — PDF page 316
| Source row | Drive model | Cooling fans |
|---|---|---|
| 1 | 4A0001 | – |
| 2 | 4A0002 | – |
| 3 | 4A0004 | – |
| 4 | 4A0005 | 1 |
| 5 | 4A0007 | 1 |
| 6 | 4A0009 | 1 |
| 7 | 4A0011 | 1 |
| 8 | 4A0018 | 2 |
| 9 | 4A0023 | 2 |
| 10 | 4A0031 | 2 |
| 11 | 4A0038 | 2 |
Manual — Cooling fan removal and warnings — page 317
Source reference: SIEP C71060618F, December 2016, physical PDF page 317. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure 7.1 Remove the Cooling Fan Cover. A – Fan cover; B – Cooling fan; C – Tab. Illustration shows a single fan; removal step1 and all warnings retained outside this region. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
Figure 7.2 Disconnect and Remove the Fan. Removal step2 and electrical/burn warnings retained outside this region. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
u Cooling Fan Replacement
The cooling fan is installed on the top of the drive. The cooling fan can easily be replaced without tools or removal of the drive or enclosure parts.
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled down.
n Removing the Cooling Fan 1. Depress the right and left sides of the fan cover tabs and pull upward. Remove the fan cover from the top of the drive. The following figure illustrates a drive with a single cooling fan.
- Remove the fan cable carefully, disconnect the pluggable connector and remove the fan.
7.4 Drive Cooling Fans
Periodic Inspection & Maintenance
Manual — Cooling fan installation — page 318
Source reference: SIEP C71060618F, December 2016, physical PDF page 318. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure 7.3 Cooling Fan Orientation. A – Label facing up; B – Back; C – Front. Installation step1 and notice retained outside this region. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
Figure 7.4 Connectors. A – Push the connectors together so no space remains between them. Step2 separately retains proper connection and cable recess instruction. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
n Installing the Cooling Fan
NOTICE: Prevent Equipment Damage. Follow cooling fan replacement instructions. Improper cooling fan replacement could result in damage to equipment. When installing the replacement cooling fan into the drive, make sure the fan is facing upwards. To ensure maximum useful product life, replace all cooling fans when performing maintenance. 1. Install the replacement cooling fan into the drive, ensuring the alignment pins line up, as shown in the figure below:
- Ensure the connectors are properly connected and place the cable back into the recess of the drive.
Note: Ensure that the left and right tabs are locked back into place. 3. Align the left and right cover tabs to install the fan cover back on the top of the drive.
7.4 Drive Cooling Fans
Manual — Drive replacement and terminal board — page 319
Source reference: SIEP C71060618F, December 2016, physical PDF page 319. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure 7.5 Terminal Board. A – Charge LED; B – Terminal Board Locking Pin; C – Removable Terminal Board. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
7.5 Drive Replacement
u Serviceable Parts
The drive contains few serviceable parts. The following parts are considered replacement parts on the drive: • Main control board and I/O Terminal board I/O PCBs. • Cooling fan(s) • Front cover Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa representative before replacing parts if the drive is still under warranty. Yaskawa reserves the right to replace or repair the drive according to Yaskawa warranty policy.
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious personal injury. Before servicing the drive, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
u Terminal Board Overview
The drive has a modular I/O terminal block that facilitates quick drive replacement. The terminal board contains on-board memory that stores all drive parameter settings and allows the parameters to be saved and transferred to the replacement drive by disconnecting the terminal board from the damaged drive then reconnecting the terminal board to the replacement drive. There is no need to manually reprogram the replacement drive.
Note: When transferring the removable terminal block with backup memory to a drive with a different voltage class or different output capacity, set A1-03 to 2220 to initialize the drive after installing the terminal block.
u Dismantling the Removable Terminal Block
WARNING! Electrical Shock Hazard. Never connect or disconnect wiring, remove connectors or option cards, or replace the cooling fan while the power is on. Failure to comply may result in serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off.
WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. 1. Loosen the screw on the front of the drive and remove the front cover.
Periodic Inspection & Maintenance
Manual — Terminal board dismantling continuation — page 320
Source reference: SIEP C71060618F, December 2016, physical PDF page 320. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure 7.6 Remove the Front Cover. Step1 is on PDF319; warnings and ESD requirements remain applicable. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
Figure 7.7 Pull Out the Ground Terminal. Source callout: Pull out the ground terminal pin in the direction indicated by the arrow. Labels: Cable; Terminal. Step2 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
Figure 7.8 Depress the Plastic Tab. Source callout: Push down the terminal board locking pin with a screwdriver. Step3 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
Pull the pin on the ground terminal out of the removable terminal block.
Push down the installation pin on the terminal board with a screwdriver
While holding down the locking pin from step 3, slide the removable terminal block in the direction of the arrows in
Figure 7.9.
7.5 Drive Replacement
Manual — Terminal board removal and reinstallation — page 321
Source reference: SIEP C71060618F, December 2016, physical PDF page 321. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure 7.9 Remove the Terminal Board. Step4 on PDF320 refers to arrows in this figure. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
Figure 7.10 Removable Terminal Board Disconnected from the Drive. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
Figure 7.11 Terminal Board Reinstallation. Source callout: Place the terminal board below the guide tracks in the plastic case of the drive. Then push it gently down and slide it toward the keypad until the locking pin clicks into place. Reinstallation step1 and step2 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
n Reinstalling the Terminal Board 1. Reinstall the removable terminal block on the drive according to Figure 7.11.
- Ensure the terminal block is firmly fastened to the connector.
7.5 Drive Replacement
Periodic Inspection & Maintenance
Manual — Terminal board reinstallation and parameter transfer — page 322
Source reference: SIEP C71060618F, December 2016, physical PDF page 322. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure 7.12 Terminal Board Reinstalled. Label: Connector. Reinstallation steps3–5 separately retained. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
- Put the lower cover and the terminal cover back in place. 4. After replacing the drive, check the drive unit selection setting in o2-04. Refer to Defaults by Drive Model and Duty Rating (ND/HD) on page 409 for more information. 5. An oPE04 error may occur when replacing the drive or the removable terminal block. If the data saved to the terminal block is compatible, set A1-03 to 5550 to write the parameter settings stored in the terminal block to the new drive. Reset the appropriate maintenance monitors using parameters o4-01 to o4-13.
u Details on Terminal Board (TB) or Control Board (CNT) Replacement
The drive Terminal Board retains drive parameter settings to significantly improve the ease of drive replacement. Refer to Troubleshooting Terminal Board or Control Board Replacement on page 323 for a flowchart to assist in board replacement. When replacing the drive, or changing the Control Board or Terminal Board, the following error codes may be encountered upon application of power: • oPE04 Drive parameter settings need to be initialized or uploaded from the TB. • CPF06 Drive specification does not match the replaced drive. • oPE01 Drive parameter o2-04 kVA requires setting. Procedural Notes: 1. When replacing the drive, control board or terminal board, make sure to confirm the kVA setting, parameter o2-04 is correct upon initial power-up. 2. Perform an initialization (via parameter A1-03) to obtain the desired parameter settings. 3. In cases where a previously programmed terminal board is retained, initializing the drive with a setting of A1-03 = 5550 may be desired to program the drive with previously programmed settings (settings used prior to replacing the drive or control board).
7.5 Drive Replacement
Manual — Terminal board replacement fault flowchart — page 323
Source reference: SIEP C71060618F, December 2016, physical PDF page 323. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Figure 7.13 Troubleshooting Terminal Board or Control Board Replacement. START: CPF06 fault displayed upon drive replacement? YES → initialize A1-03=2220 or3330, then Ready. NO → fault oPE01? YES → set o2-04 to match drive nameplate rating, then oPE04 decision; NO → oPE04 decision. Note: Drive kVA Setting o2-04="FF" inside a new Terminal Board. Fault oPE04? NO → Ready. YES → drive parameter settings need initialization or upload from TB; initialize using A1-03: set2220 or3330 → Ready; set5550 → parameter setting values copied TB to CNT → Ready. Ready → END. These are literal visible branch labels, not inferred wiring or authorization to initialize equipment. Exact illustration geometry remains in the original PDF; this is a source transcription, not a service instruction independent of the full manual.
7.5 Drive Replacement
Periodic Inspection & Maintenance
Manual — Peripheral safety — page 326
Source reference: SIEP C71060618F, December 2016, physical PDF page 326. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
8.1 Section Safety
DANGER
Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Disconnect all power to the drive, wait at least five minutes after all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc.
WARNING
Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work on the drive. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not change wiring or remove option unit while power is running through the drive. Failure to comply could result in death or serious injury. Disconnect all power to the drive and check for unsafe voltages before servicing. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive.
Manual — Options and models — page 327
Source reference: SIEP C71060618F, December 2016, physical PDF page 327. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
8.2 Drive Options and Peripheral Devices
The following table of peripheral devices lists the names of the various devices/options available for Yaskawa drives. Contact Yaskawa or your Yaskawa agent to order these peripheral devices. • Peripheral Device Selection: Refer to Yaskawa catalog for selection and part numbers. • Peripheral Device Installation: Refer to option manual for option installation instructions.
Table 8.1 Available Peripheral Devices
Option Model Number Description Power Options
Interface Options
Mechanical Options
Others
Communication Options
& Devices Peripheral Options
Power Options | Option
Power Options | Model number
Power Options | Description
Interface Options | Option
Interface Options | Model number
Interface Options | Description
Mechanical Options | Option
Mechanical Options | Model number
Mechanical Options | Description
Others | Option
Others | Model number
Others | Description
Communication Options | Option
Communication Options | Model number
Communication Options | Description
Power Options — PDF page 327
| Source row | Option | Model number | Description |
|---|---|---|---|
| 1 | DC Link Choke | UZDA Series | DC link choke to improve power factor |
| 2 | AC Reactor | UZBA Series | AC reactor to improve power factor |
| 3 | Braking Resistor | ERF-150WJ Series | 3% ED, 150 W braking resistor |
| 4 | Braking Chopper | CDBR Series | External braking transistor |
| 5 | Surge Absorber | 200 V class: DCR2-□A 400 V class: RFN3AL-504KD | Suppresses surge voltage caused by switching magnetic contactors |
| 6 | Molded Case Circuit Breaker | NF Series | Circuit breaker for short circuit or overload protection Note: Yaskawa recommends installing an MCCB to the power supply side to protect drive wiring and to prevent other damage in the event of component failure. Install an MCCB if permitted by the power system. |
| 7 | Ground Fault Circuit Interrupter (GFCI) | NV, EG, or SG Series | Provides protection against potentially harmful leakage currents Note: Yaskawa recommends installing a GFCI to the power supply side to protect drive wiring and to prevent other damage in the event of component failure. An MCCB can also be used if permitted by the power system. |
| 8 | Magnetic Contactor (Input) | SC Series | Prevents potential damage to the braking resistor and other internal circuitry by ensuring that power to drive is completely shut off when necessary. Install an MCCB when using a braking resistor to prevent the braking resistor from overheating. Wire the MC so that it opens when a fault output terminal is triggered to protect internal components from sudden high levels of input current. |
Interface Options — PDF page 327
| Source row | Option | Model number | Description |
|---|---|---|---|
| 1 | Remote LCD Operator | JVOP-180 | Remote operator with 8 languages clear text LCD display and copy function; Cable length max. 3 m |
| 2 | USB/Copy Unit | JVOP-181 | Allows the user to copy and verify parameter settings between drives. Can also be used as adapter to connect the drive to a PC USB port |
Mechanical Options — PDF page 327
| Source row | Option | Model number | Description |
|---|---|---|---|
| 1 | Heatsink External Mounting Attachment | EZZ020568□ | Installation kit for mounting the drive with the heatsink outside of the panel (side-by-side mounting possible) |
| 2 | DIN Rail Attachment | EZZ08122□ | Installation kit for mounting the drive on a DIN rail |
| 3 | NEMA Type 1 Kit <1> | EZZ020564□ | Parts to make the drive conform to NEMA Type 1 enclosure |
Others — PDF page 327
| Source row | Option | Model number | Description |
|---|---|---|---|
| 1 | 24 Vdc Control Power Supply Option | PS-V10□ | Provides power to the control circuit and option boards in the event of a power loss. Allows the user to monitor drive settings and fault information when the main circuit has no power. |
| 2 | Drive Wizard Plus | — | PC tool for drive setup and parameter management The installation files can be obtained at no charge from: http://www.yaskawa.com |
| 3 | DriveWorksEZ | — | PC tool for enhanced programming of the drive |
Communication Options — PDF page 327
| Source row | Option | Model number | Description |
|---|---|---|---|
| 1 | CANopen Communications Option | SI-S3/V | Connects to a CANopen network |
| 2 | CC-Link Communications Option | SI-C3/V | Connects to a CC-Link network |
Manual — Communication options and kit footnote — page 328
Source reference: SIEP C71060618F, December 2016, physical PDF page 328. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Option Model Number Description
<1> Available for models: BA0001 to BA0018, 2A0001 to 2A0020, and 4A0001 to 4A0011.
8.2 Drive Options and Peripheral Devices
Communication options continued from PDF327 | Option
Communication options continued from PDF327 | Model number
Communication options continued from PDF327 | Description
Communication options continued from PDF327 — PDF page 328
| Source row | Option | Model number | Description |
|---|---|---|---|
| 1 | CompoNet Communications Option | SI-M3/V | Connects to a CompoNet network |
| 2 | DeviceNet Communications Option | SI-N3/V | Connects to a DeviceNet network |
| 3 | EtherCAT Communications Option | SI-ES3/V | Connects to an EtherCAT network |
| 4 | EtherNet/IP Communications Option | SI-EN3/V | Connects to an EtherNet/IP network |
| 5 | MECHATROLINK-II Communications Option | SI-T3/V | Connects to a MECHATROLINK-II network |
| 6 | MECHATROLINK-III Communications Option | SI-ET3/V | Connects to a MECHATROLINK-III network |
| 7 | Modbus TCP/IP Communications Option | SI-EM3/V | Connects to a Modbus/TCP network |
| 8 | PROFIBUS-DP Communications Option | SI-P3/V | Connects to a PROFIBUS-DP network |
| 9 | PROFINET Communications Option | SI-EP3/V | Connects to a PROFINET network |
Manual — Peripheral connection overview — page 329
Source reference: SIEP C71060618F, December 2016, physical PDF page 329. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Labels: Power supply; Line breaker(MCCB) or Leakage breaker; Surge absorber; AC reactor; Input side noise filter; DC link choke; Drive; Ground; Output side noise filter; Motor; Magnetic Contactor(MC); Braking resistor unit;24V power supply option;24V option connector;B1,B2;R/L1,S/L2,T/L3,U/T1,V/T2,W/T3,+1,+2. USB Copy Unit(RJ-45/USB adapter),RJ-45 cable,USB cable,Dedicated cable(RJ-45/D-sub adapter),PC;Engineering software tools DriveSelect,DriveWizard,DriveWorksEZ. Incidental JVOP-181 labels:Copy,Verify,Read,LOCK,USB Copy Unit,COM,ERR,YASKAWA. Figure8.1 Connecting Peripheral Devices. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
8.3 Connecting Peripheral Devices
Figure 8.1 illustrates how the drive and motor connect together with various peripheral devices. Refer to peripheral device option manual for detailed installation instructions.
<1> NOTICE: Do not connect the LAN port on a PC and the comm. port of the drive. Failure to comply may damage the drive and the PC.
Note: If the drive is set to trigger an output terminal when performing a fault restart (L5-02 = 1), the power supply will be shut off during fault restart as the drive outputs a fault signal. Keep this in mind when designing a wiring sequence to interrupt the power to the drive. The default setting for the drive is to not trigger an output terminal that indicates a fault restart is being performed (L5-02 = 0).
& Devices Peripheral Options
Manual — Protection and breakers — page 330
Source reference: SIEP C71060618F, December 2016, physical PDF page 330. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
8.4 Installing Peripheral Devices
This section describes the proper steps and precautions to take when installing or connecting various peripheral devices to the drive. Refer to peripheral device manual for detailed installation instructions.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper application of peripheral devices could result in drive performance degradation due to improper power supply.
u Installing a Molded Case Circuit Breaker (MCCB) and Earth Leakage Circuit Breaker (ELCB)
Install an MCCB or ELCB for line protection between the power supply and the main circuit power supply input terminals R/ L1, S/L2 and T/L3. This protects the main circuit and devices wired to the main circuit while also providing overload protection. Consider the following when selecting and installing an MCCB or ELCB: • The rated current of the MCCB or ELCB should be 1.5 to 2 times the rated output current of the drive. Use an MCCB or ELCB with operation characteristics that do not trip the MCCB or ELCB faster than the drive overload protection (shuts off the drive after 1 minute of operation at 150% of the drive rated current). • If several drives are connected to one MCCB or an ELCB that is shared with other equipment, use a sequence that shuts the power OFF when errors are output by using magnetic contactor (MC) as shown in the following figure.
Drive
Power Supply
R/L1
MB
MCCB MC
MC
S/L2 T/L3
SA
Figure 8.2 Connecting an MCCB
WARNING! Electrical Shock Hazard. Disconnect the MCCB (or ELCB) and MC before wiring terminals. Failure to comply may result in serious injury or death.
u Installing a Leakage Breaker
Drive outputs generate high-frequency leakage current as a result of high-speed switching. Install a GFCI on the input side of the drive to switch off potentially harmful leakage current. Factors in determining leakage current: • Size of the AC drive • AC drive carrier frequency • Motor cable type and length • EMI/RFI filter If the GFCI trips spuriously, consider changing these items or use a GFCI with a higher trip level.
Note: Choose a GFCI designed specifically for an AC drive. The operation time should be at least 0.1 s with sensitivity amperage of at least 200 mA per drive. The output waveform of the drive may cause an increase in leakage current. This may in turn cause the leakage breaker to malfunction. Increase the sensitivity amperage or lower the carrier frequency to correct the problem.
Manual — Magnetic contactors and reactors — page 331
Source reference: SIEP C71060618F, December 2016, physical PDF page 331. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A Power supply;B MCCB;C AC reactor;D Drive. Source terminals U,V,W,X,Y,Z,R/L1,S/L2,T/L3. Figure8.3 Connecting an AC Reactor. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
u Installing a Magnetic Contactor
n Disconnecting the Power Supply
The drive should be shut off in the case of a fault in external equipment such as braking resistors through use of a Magnetic Contactor (MC).
NOTICE: Do not connect electromagnetic switches or MCs to the output motor circuits without proper sequencing. Improper sequencing of output motor circuits may cause damage to the drive.
NOTICE: Install an MC on the input side of the drive when the drive should not automatically restart after power loss. To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the MC more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.
Note: 1. Install an MC to the drive output to prevent the drive from restarting automatically when the power is restored after momentary power loss. 2. Set up a delay for the MC so that it does not open prematurely for the drive to continue operating through momentary power loss.
n Protecting the Braking Resistor or Braking Resistor Unit
Use an MC on the input side of the drive to protect a braking resistor or braking resistor unit from overheat or fire.
WARNING! Fire Hazard. When using a braking unit, use a thermal relay on the braking resistors and configure a fault contact output for the braking resistor unit to disconnect drive main power via an input contactor. Inadequate braking circuit protection could result in death or serious injury by fire from overheating resistors.
u Connecting an AC Reactor or DC Link Choke
AC reactors and DC link chokes suppress surges in current and improve the power factor on the input side of the drive. Use an AC reactor, DC link choke, or both: • To suppress harmonic current or improve the power factor of the power supply. • When using a phase advancing capacitor switch. • With a large capacity power supply transformer (over 600 kVA).
Note: Use an AC reactor or DC link choke when also connecting a thyristor converter (such as a DC drive) to the same power supply system, regardless of the conditions of the power supply.
n Connecting an AC Reactor
8.4 Installing Peripheral Devices
& Devices Peripheral Options
Manual — DC choke and input filter — page 332
Source reference: SIEP C71060618F, December 2016, physical PDF page 332. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A Power supply;B MCCB;C Drive;D DC link choke. Terminals R/L1,S/L2,T/L3,+1,+2. Figure8.4 Connecting a DC Link Choke. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
A Power supply;B Input-side noise filter(Model LNFB-□□);C Drive;D Other control device. MCCB;R/L1,S/L2;filter labels1,2,3,4,E. Figure8.5 Input-Side Noise Filter(Single-Phase200V). Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
n Connecting a DC Link Choke
Ensure the jumper between terminals +1 and +2 (terminals are jumpered for shipment) is removed when connecting a DC link choke. The jumper must be installed if no DC link choke is used. Refer to Connecting a DC Link Choke on page 332 for an example of DC link choke wiring.
u Connecting a Surge Suppressor
A surge suppressor suppresses transient voltages generated from switching an inductive load near the drive. Inductive loads include magnetic contactors, relays, valves, solenoids and brakes. Always use a surge suppressor or diode when operating with an inductive load.
Note: Never connect a surge suppressor to the drive output.
u Connecting a Noise Filter
n Input-Side Noise Filter
Drive outputs generate noise as a result of high-speed switching. This noise flows from inside the drive back toward the power supply, possibly affecting other equipment. Installing a noise filter to the input side of the drive can reduce the amount of noise flowing back into the power supply. This also prevents noise from entering the drive from the power supply. • Use a noise filter specifically designed for AC drives. • Install the noise filter as close as possible to the drive.
8.4 Installing Peripheral Devices
Manual — Input and output filtering — page 333
Source reference: SIEP C71060618F, December 2016, physical PDF page 333. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A Power supply;B Input-side noise filter(Model LNFD-□□);C Drive;D Other control device. MCCB;R,L1 terminal shown R/L1;S/L2,T/L3;filter R,S,T,U,V,W,E. Figure8.6 Input-Side Noise Filter(Three-Phase200/400V). Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
A Power supply;B Drive;C Output-side noise filter;D Motor. MCCB;R/L1,S/L2,T/L3,U/T1,V/T2,W/T3;filter labels1,2,3,4,5,6. Figure8.7 Output-Side Noise Filter. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
Refer to EMC Filter Installation on page 469 for details about EMC filter selection and installation in order to make the drive compliant with European standards EN 61800-3:2004/A1:2012 and the EMC guidelines.
n Output-Side Noise Filter
A noise filter on the output side of the drive reduces inductive noise and radiated noise. Figure 8.7 illustrates an example of output-side noise filter wiring.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper application of noise filters could result in damage to the drive.
• Radiated Noise: Electromagnetic waves radiated from the drive and cables create noise throughout the radio bandwidth that can affect devices. • Induced Noise: Noise generated by electromagnetic induction can affect the signal line and may cause the controller to malfunction.
Preventing Induced Noise Use a noise filter on the output side or use shielded cables. Lay the cables at least 30 cm away from the signal line to prevent induced noise.
8.4 Installing Peripheral Devices
& Devices Peripheral Options
Manual — Noise suppression and reactor passes — page 334
Source reference: SIEP C71060618F, December 2016, physical PDF page 334. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A Power supply;B Drive;C Shielded motor cable;D Motor;E Separate at least30cm;F Controller;G Signal line. MCCB,R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Figure8.8 Preventing Induced Noise. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
A Metal enclosure;B Power supply;C Noise filter;D Drive;E Noise filter;F Shielded motor cable;G Motor. MCCB,R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Figure8.9 Reducing Radio Frequency Noise. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
A Power supply;B MCCB;C Zero-phase reactor on input side;D Drive;E Zero-phase reactor on output side;F Motor. R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Close-up of V/T2-phase wiring:1st pass,2nd pass,3rd pass,4th pass. Pass each wire(U/T1,V/T2,W/T3)through the core4times. Figure8.10 Zero-Phase Reactor. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
Reducing Radiated/Radio Frequency Noise The drive, input lines, and output lines generate radio frequency noise. Use noise filters on input and output sides and install the drive in a metal enclosure panel to reduce radio frequency noise.
Note: The cable running between the drive and motor should be as short as possible.
u EMC Filter Installation
This drive is tested according to European standards IEC/EN 61800-5-1 and it complies with the EMC guidelines. Refer to EMC Filter Installation on page 469 for details about EMC filter selection and installation.
u Zero-Phase Reactor
A zero-phase reactor can be used to reduce the noise on the input and output sides of the drive.
8.4 Installing Peripheral Devices
Manual — Fuses heatsinks and thermal relays — page 335
Source reference: SIEP C71060618F, December 2016, physical PDF page 335. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u Installing Fuses on the Input Side
Always install input fuses to the input side of the as a protective measure against damage caused by a short circuit. Refer to Standards Compliance on page 463 for details on input fuse selection.
u Attachment for External Heatsink
An external attachment can be used to project the heatsink outside of an enclosure to ensure that there is sufficient air circulation around the heatsink. This installation method still requires a certain amount of airflow over the drive case. Refer to Output Current Derating Due to Ambient Temperature on page 351 if derating is required. Contact a Yaskawa sales representative for more information.
u Noise Filter Installation
This drive has undergone testing in conformance with IEC/EN 61800-5-1 and is in compliance with low voltage directives. Refer to EMC Guidelines Compliance on page 469 for information on selecting a noise filter.
u Installing a Motor Thermal Overload (oL) Relay on the Drive Output
Motor thermal overload relays protect the motor by disconnecting power lines to the motor due to a motor overload condition. Install a motor thermal overload relay between the drive and motor: • When operating multiple motors on a single AC drive. • When using a power line bypass to operate the motor directly from the power line. It is not necessary to install a motor thermal overload relay when operating a single motor from a single AC drive. The AC drive has UL recognized electronic motor overload protection built into the drive software.
Note: Disable the motor protection function (L1-0 1 = “0”) when using an external motor thermal overload relay. The relay should shut off main power on the input side of the main circuit when triggered.
n General Precautions when Using Thermal Overload Relays
The following application precautions should be considered when using motor thermal overload relays on the output of AC drives in order to prevent nuisance trips or overheat of the motor at low speeds: • Low speed motor operation • Use of multiple motors on a single AC drive • Motor cable length • Nuisance tripping resulting from high AC drive carrier frequency
Low Speed Operation and Motor Thermal oL Relays Generally, thermal relays are applied on general-purpose motors. When general-purpose motors are driven by AC drives, the motor current is approximately 5 to 10% greater than if driven by the commercial power supply. In addition, the cooling capacity of a motor with a shaft-driven fan decreases when operating at low speeds. Even if the load current is within the motor rated value, motor overheating may occur. A thermal relay cannot effectively protect the motor due to the reduction of cooling at low speeds. For this reason, apply the UL recognized electronic thermal overload protection function built into the drive whenever possible. UL recognized electronic thermal overload function of the drive: Speed-dependent heat characteristics are simulated using data from standard motors and force-ventilated motors. The motor is protected from overload using this function.
Using One Drive with Multiple Motors Turn off the electronic thermal overload function. Please refer to the appropriate product instruction manual to determine which parameter disables this function. The UL recognized electronic thermal overload function of the drive cannot be applied when using multiple motors on one drive.
Long Motor Cables When long motor cables and high carrier frequency are used, nuisance tripping of the thermal relay may occur due to increased leakage current. Therefore, reduce the carrier frequency or increase the tripping level of the thermal overload relay.
Nuisance Tripping Resulting from High AC Drive Carrier Frequency Current waveforms generated by high carrier frequency PWM drives tend to create additional temperature rise in overload relays. Therefore, it may be necessary to increase the trip level setting when encountering nuisance triggering of the relay.
8.4 Installing Peripheral Devices
& Devices Peripheral Options
Manual — Thermal relay fire warning — page 336
Source reference: SIEP C71060618F, December 2016, physical PDF page 336. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
WARNING! Fire Hazard. Confirm an actual motor overload condition is not present prior to increasing the thermal oL trip setting. Check local electrical codes before making adjustments to motor thermal overload settings.
8.4 Installing Peripheral Devices
Manual — Communication card options — page 337
Source reference: SIEP C71060618F, December 2016, physical PDF page 337. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
8.5 Communication Options
Table 8.2 gives detailed information about the available options that allow Yaskawa drives to connect to communication networks. A host controller can control and monitor the drive, read and change parameters by using a communication option. Contact Yaskawa or your Yaskawa agent to order options. • Option Selection: Refer to Yaskawa catalog for more details on option selection and part numbers. • Option Installation: Refer to option manual for option installation instructions.
Table 8.2 Available Communication Options
Option Model Function
& Devices Peripheral Options
Available communication options | Option
Available communication options | Model
Available communication options | Function
Available communication options — PDF page 337
| Source row | Option | Model | Function |
|---|---|---|---|
| 1 | PROFIBUS-DP Communications Option | SI-P3/V | Connects to a PROFIBUS-DP network |
| 2 | CC-Link Communications Option | SI-C3/V | Connects to a CC-Link network |
| 3 | DeviceNet Communications Option | SI-N3/V | Connects to a DeviceNet network |
| 4 | CompoNet Communications Option | SI-M3/V | Connects to a CompoNet network |
| 5 | CANopen Communications Option | SI-S3/V | Connects to a CANopen network |
| 6 | EtherNet/IP Communications Option | SI-EN3/V | Connects to an EtherNet/IP network |
| 7 | MECHATROLINK-II Communications Option | SI-T3/V | Connects to a MECHATROLINK-II network |
| 8 | MECHATROLINK-III Communications Option | SI-ET3/V | Connects to a MECHATROLINK-III network |
| 9 | EtherCAT Communications Option | SI-ES3/V | Connects to an EtherCAT network |
| 10 | PROFINET Communications Option | SI-EP3/V | Connects to a PROFINET network |
| 11 | Modbus TCP/IP Communications Option | SI-EM3/V | Connects to a Modbus TCP network |
Manual — Option card installation — page 338
Source reference: SIEP C71060618F, December 2016, physical PDF page 338. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A Option card;B Option card cover installation screw holes;C Tabs for mounting front cover;D Comm.connector(CN1);E Ground lead connection screw holes;F Wire through-hole;G Option card cover;H Cover screw;I Ground lead. Figure8.11 Option Card. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
Figure8.12 Remove Cover; full numberedstep1 separately retained. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
A Ground terminal;B Ground lead;C Terminal cover. Figure8.13 Connect Lead; full numberedstep2 separately retained. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
8.6 Connecting an Option Card
The drive can communicate with other devices through a specially designed option card. The following section describes how to install an option card. Refer to option card manual for detailed installation instructions.
Note: Refer to Available Communication Options on page 337 for a list of option cards for use with this product.
u Verifying the Option Card and Product Type
u Connecting the Option Card 1. Loosen the screw on the front cover of the drive to remove the cover.
Remove the terminal cover. Connect the lead from the option card to the drive ground terminal.
Reattach the terminal cover.
Manual — Option card installation continuation — page 339
Source reference: SIEP C71060618F, December 2016, physical PDF page 339. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A Line up the tab with the mounting hole;B Line up the tab with the mounting hole. Figure8.14 Attach Option Card. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
A Drive ground terminal;B Route the lead wire on the inside of the lower cover;C Ground lead;D Ground lead through-hole;E Ground lead. Figure8.15 Lead Wire Connection. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
A Align the tab with the mounting hole. Figure8.16 Reattach Cover. Exact wiring topology, dimensions and hardware geometry remain in the original PDF. Read full adjacent procedures and warnings.
- Attach the option card to the drive.
Note: Gently pack wires to fit behind the left and right side of the cover into the provided recess. 5. Connect the lead from the drive ground terminal to the same terminal as the option card lead.
The option card lead should exit through the holes provided on the underside of the drive as it gets routed passed the ground terminal.
- Reattach the option card cover.
8.6 Connecting an Option Card
& Devices Peripheral Options
Manual — Heavy and normal duty — page 342
Source reference: SIEP C71060618F, December 2016, physical PDF page 342. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A.1 Heavy Duty and Normal Duty Ratings
The capacity of the drive is based on two types of load characteristics: Heavy Duty (HD) and Normal Duty (ND). Refer to Selecting the Appropriate Load Rating on page 342 for the differences between HD and ND. Specifications for capacity ratings are listed on the following pages.
Table A.1 Selecting the Appropriate Load Rating
Setting Parameter Rated Output Current Overload Tolerance Default Carrier Frequency C6-01
<1> The following pages list information on rating changes based on drive model.
TERMS • HD and ND: HD refers to applications requiring constant torque output, while ND refers to applications with variable torque needs. The drive allows the user to select HD or ND torque depending on the application. Fans, pumps, and blowers should use ND (C6-01 = 1), and other applications generally use HD (C6-01 = 0). • Swing PWM: Swing PWM equivalent to a 2 kHz audible noise. This function turns the motor noise into a less obtrusive white noise.
Note: Differences between HD ratings and ND ratings for the drive include rated input and output current, overload capacity, carrier frequency, and current limit. The default setting is for ND (C6-01 = 1).
Selecting the appropriate load rating | Setting parameter C6-01
Selecting the appropriate load rating | Rated output current
Selecting the appropriate load rating | Overload tolerance
Selecting the appropriate load rating | Default carrier frequency
Selecting the appropriate load rating — PDF page 342
| Source row | Setting parameter C6-01 | Rated output current | Overload tolerance | Default carrier frequency |
|---|---|---|---|---|
| 1 | 0: Heavy Duty | HD Rating varies by model <1> | 150% rated output current for 60 s | 8/10 kHz varies by model |
| 2 | 1: Normal Duty (default) | ND Rating varies by model <1> | 120% rated output current for 60 s varies by model | 2 kHz, Swing PWM |
Manual — 200 V small frame ratings — page 343
Source reference: SIEP C71060618F, December 2016, physical PDF page 343. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A.2 Single/Three-Phase 200 V Class Drives
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to 0 for HD or 1 for ND (default).
Table A.2 Power Ratings
Item Specification Three-Phase Drive Model 2A0001 2A0002 2A0004 2A0006 2A0010 2A0012 2A0020
Single-Phase Drive Model <1> BA0001 BA0002 BA0003 BA0006 BA0010 BA0012 BA0018
Maximum Motor Size Allowed (HP)
<3>
ND Rating
HD Rating
Input Current Input <4> (A)
Three- phase
Single- phase
ND Rating HD Rating
Output
Rated Output Capacity (kVA) <5>
ND Rating <6> Output Current (A)
Overload Tolerance Carrier Frequency
Max Output Voltage (V) Max Output Frequency (Hz)
Power Supply
Rated Voltage Rated Frequency
Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective DC Link Choke Actions
<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor. <2> 2A0020 only. BA0018 is available with a Heavy Duty rating only. <3> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <4> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance. <5> Rated motor capacity is calculated with a rated output voltage of 230 V. <6> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier frequency. <7> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency. <8> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency. <9> DC is not available for UL standards.
A
Specifications
Actual physical source row; model columns 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0001 / BA0001
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0002 / BA0002
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0004 / BA0003
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0006 / BA0006
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0010 / BA0010
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0012 / BA0012
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating | 2A0020 / BA0018
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0001 / BA0001
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0002 / BA0002
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0004 / BA0003
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0006 / BA0006
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0010 / BA0010
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0012 / BA0012
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating | 2A0020 / BA0018
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0001 / BA0001
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0002 / BA0002
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0004 / BA0003
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0006 / BA0006
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0010 / BA0010
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0012 / BA0012
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating | 2A0020 / BA0018
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0001 / BA0001
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0002 / BA0002
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0004 / BA0003
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0006 / BA0006
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0010 / BA0010
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0012 / BA0012
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating | 2A0020 / BA0018
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0001 / BA0001
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0002 / BA0002
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0004 / BA0003
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0006 / BA0006
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0010 / BA0010
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0012 / BA0012
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating | 2A0020 / BA0018
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0001 / BA0001
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0002 / BA0002
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0004 / BA0003
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0006 / BA0006
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0010 / BA0010
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0012 / BA0012
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating | 2A0020 / BA0018
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0001 / BA0001
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0002 / BA0002
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0004 / BA0003
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0006 / BA0006
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0010 / BA0010
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0012 / BA0012
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating | 2A0020 / BA0018
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0001 / BA0001
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0002 / BA0002
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0004 / BA0003
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0006 / BA0006
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0010 / BA0010
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0012 / BA0012
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating | 2A0020 / BA0018
Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0001 / BA0001
Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0002 / BA0002
Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0004 / BA0003
Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0006 / BA0006
Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0010 / BA0010
Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0012 / BA0012
Power ratings 200 V — Output Current (A) | ND Rating <6> | 2A0020 / BA0018
Power ratings 200 V — Output Current (A) | HD Rating | 2A0001 / BA0001
Power ratings 200 V — Output Current (A) | HD Rating | 2A0002 / BA0002
Power ratings 200 V — Output Current (A) | HD Rating | 2A0004 / BA0003
Power ratings 200 V — Output Current (A) | HD Rating | 2A0006 / BA0006
Power ratings 200 V — Output Current (A) | HD Rating | 2A0010 / BA0010
Power ratings 200 V — Output Current (A) | HD Rating | 2A0012 / BA0012
Power ratings 200 V — Output Current (A) | HD Rating | 2A0020 / BA0018
Power ratings 200 V — Overload Tolerance | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Carrier Frequency | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Max Output Voltage (V) | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Max Output Frequency (Hz) | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Allowable Voltage Fluctuation | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Allowable Frequency Fluctuation | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | ND Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 0.13 | 0.25 | 0.5/ 0.75 | 1.0/ 1.5 | 2.0/ 3.0 | 3.0 | 5.0 <2> |
Power ratings 200 V — Maximum Motor Size Allowed (HP) <3> | HD Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 0.13 | 0.25 | 0.5 | 0.75/ 1.0 | 1.5/ 2.0 | 3.0 | 5.0 |
Power ratings 200 V — Input | Input Current <4> (A) | Three- phase | ND Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 1.1 | 1.9 | 3.9 | 7.3 | 10.8 | 13.9 | 24.0 <2> |
Power ratings 200 V — Three- phase | Input Current <4> (A) | HD Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 0.7 | 1.5 | 2.9 | 5.8 | 7.5 | 11.0 | 18.9 |
Power ratings 200 V — Single- phase | Input Current <4> (A) | ND Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 2.0 | 3.6 | 7.3 | 13.8 | 20.2 | 24.0 | – |
Power ratings 200 V — Single- phase | Input Current <4> (A) | HD Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 1.4 | 2.8 | 5.5 | 11.0 | 14.1 | 20.6 | 35.0 |
Power ratings 200 V — Output | Rated Output Capacity (kVA) <5> | ND Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 0.5 | 0.7 | 1.3 | 2.3 | 3.7 | 4.6 | 7.5 <2> |
Power ratings 200 V — Rated Output Capacity (kVA) <5> | HD Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 0.3 | 0.6 | 1.1 | 1.9 | 3.0 | 4.2 | 6.7 |
Power ratings 200 V — Output Current (A) | ND Rating <6> — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 1.2 | 1.9 | 3.5 (3.3) | 6.0 | 9.6 | 12.0 | 19.6 <2> |
Power ratings 200 V — Output Current (A) | HD Rating — PDF page 343
| Source row | 2A0001 / BA0001 | 2A0002 / BA0002 | 2A0004 / BA0003 | 2A0006 / BA0006 | 2A0010 / BA0010 | 2A0012 / BA0012 | 2A0020 / BA0018 |
|---|---|---|---|---|---|---|---|
| 1 | 0.8 <7> | 1.6 <7> | 3.0 <7> | 5.0 <7> | 8.0 <8> | 11.0 <8> | 17.5 <8> |
Power ratings 200 V — Overload Tolerance — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | ND Rating: 120% of rated output current for 1 minute HD Rating: 150% of rated output current for 1 minute (Derating may be required for applications that start and stop frequently) |
Power ratings 200 V — Carrier Frequency — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | User-adjustable 2 to 15 kHz |
Power ratings 200 V — Max Output Voltage (V) — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | Three-phase power: 200 to 240 V Single-phase power: 200 to 240 V (both proportional to input voltage) |
Power ratings 200 V — Max Output Frequency (Hz) — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | 400 Hz (user-adjustable) |
Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | Three-phase power: 200 to 240 V 50/60 Hz Single-phase power: 200 to 240 V 50/60 Hz DC power supply: 270 to 340 V <9> |
Power ratings 200 V — Allowable Voltage Fluctuation — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | -15 to 10% |
Power ratings 200 V — Allowable Frequency Fluctuation — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | ±5% |
Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke — PDF page 343
| Source row | All listed model columns: 2A0001 / BA0001, 2A0002 / BA0002, 2A0004 / BA0003, 2A0006 / BA0006, 2A0010 / BA0010, 2A0012 / BA0012, 2A0020 / BA0018 |
|---|---|
| 1 | Optional |
Manual — 200 V larger frame ratings — page 344
Source reference: SIEP C71060618F, December 2016, physical PDF page 344. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table A.3 Power Ratings Continued
Item Specification Three-Phase Model 2A0030 2A0040 2A0056 2A0069
Single-Phase Model <1> - - - -
ND Rating Maximum Motor Size Allowed (HP) <2> HD Rating
Input Input Current (A) <3>
Three- Phase
ND Rating HD Rating
Single- Phase
Output
ND Rating Rated Output Capacity (kVA) <4> HD Rating
ND Rating <5> Output Current (A)
HD Rating
Overload Tolerance Carrier Frequency
Max Output Voltage (V) Max Output Frequency (Hz)
Power Supply
Rated Voltage Rated Frequency
Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective Actions DC Link Choke
<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor. <2> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance. <4> Rated motor capacity is calculated with a rated output voltage of 220 V. <5> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required in order to raise the carrier frequency. <6> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency. <7> DC is not available for UL standards.
A.2 Single/Three-Phase 200 V Class Drives
Actual physical source row; model columns 2A0030, 2A0040, 2A0056, 2A0069. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0030
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0040
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0056
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating | 2A0069
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0030
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0040
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0056
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating | 2A0069
Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0030
Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0040
Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0056
Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating | 2A0069
Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0030
Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0040
Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0056
Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating | 2A0069
Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0030
Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0040
Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0056
Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating | 2A0069
Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0030
Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0040
Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0056
Power ratings 200 V — Input Current (A) <3> | Single- Phase | HD Rating | 2A0069
Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0030
Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0040
Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0056
Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating | 2A0069
Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0030
Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0040
Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0056
Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating | 2A0069
Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0030
Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0040
Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0056
Power ratings 200 V — Output Current (A) | ND Rating <5> | 2A0069
Power ratings 200 V — Output Current (A) | HD Rating | 2A0030
Power ratings 200 V — Output Current (A) | HD Rating | 2A0040
Power ratings 200 V — Output Current (A) | HD Rating | 2A0056
Power ratings 200 V — Output Current (A) | HD Rating | 2A0069
Power ratings 200 V — Overload Tolerance | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Carrier Frequency | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Max Output Voltage (V) | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Max Output Frequency (Hz) | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Allowable Voltage Fluctuation | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Allowable Frequency Fluctuation | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | ND Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 7.5/10.0 | 10.0 | 20.0 | 25.0 |
Power ratings 200 V — Maximum Motor Size Allowed (HP) <2> | HD Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 7.5 | 10.0 | 15.0 | 20.0 |
Power ratings 200 V — Input | Input Current (A) <3> | Three- Phase | ND Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 37.0 | 52.0 | 68.0 | 80.0 |
Power ratings 200 V — Input Current (A) <3> | Three- Phase | HD Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 24.0 | 37.0 | 52.0 | 68.0 |
Power ratings 200 V — Input Current (A) <3> | Single- Phase | ND Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | - | - | - | - |
Power ratings 200 V — Output | Rated Output Capacity (kVA) <4> | ND Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 11.4 | 15.2 | 21.3 | 26.3 |
Power ratings 200 V — Rated Output Capacity (kVA) <4> | HD Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 9.5 | 12.6 | 17.9 | 22.9 |
Power ratings 200 V — Output Current (A) | ND Rating <5> — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 30.0 | 40.0 | 56.0 | 69.0 |
Power ratings 200 V — Output Current (A) | HD Rating — PDF page 344
| Source row | 2A0030 | 2A0040 | 2A0056 | 2A0069 |
|---|---|---|---|---|
| 1 | 25.0 <6> | 33.0 <6> | 47. 0 <6> | 60.0 <6> |
Power ratings 200 V — Overload Tolerance — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | ND Rating: 120% of rated output current for 1 minute HD Rating: 150% of rated output current for 1 minute (Derating may be required for applications that start and stop frequently) |
Power ratings 200 V — Carrier Frequency — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | User-adjustable 2 to 15 kHz |
Power ratings 200 V — Max Output Voltage (V) — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | Three-phase power: 200 to 240 V Single-phase power: 200 to 240 V (both proportional to input voltage) |
Power ratings 200 V — Max Output Frequency (Hz) — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | 400 Hz (user-adjustable) |
Power ratings 200 V — Power Supply | Rated Voltage Rated Frequency — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | Three-phase power: 200 to 240 V 50/60 Hz Single-phase power: 200 to 240 V 50/60 Hz DC power supply: 270 to 340 V <7> |
Power ratings 200 V — Allowable Voltage Fluctuation — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | -15 to 10% |
Power ratings 200 V — Allowable Frequency Fluctuation — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | ±5% |
Power ratings 200 V — Harmonic Corrective Actions | DC Link Choke — PDF page 344
| Source row | All listed model columns: 2A0030, 2A0040, 2A0056, 2A0069 |
|---|---|
| 1 | Optional |
Manual — 400 V small frame ratings — page 345
Source reference: SIEP C71060618F, December 2016, physical PDF page 345. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A.3 Three-Phase 400 V Class Drives
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to 0 for HD or 1 for ND (default).
Table A.4 Power Ratings
Item Specification Three-Phase Model 4A0001 4A0002 4A0004 4A0005 4A0007 4A0009
Maximum Applicable Motor Capacity (HP) <1>
ND Rating HD Rating
Input Current Input <2> (A)
Output
Output Current (kVA) <3>
ND Rating <4>
HD Rating <5>
Output Current (A)
Overload Tolerance Carrier Frequency Max Output Voltage (V) Max Output Frequency (Hz)
Power Supply
Rated Voltage Rated Frequency
Supply Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective Actions DC Link Choke
<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance. <3> Rated motor capacity is calculated with a rated output voltage of 460 V. <4> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency. <5> Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency. <6> DC is not available for UL standards.
A
Specifications
Actual physical source row; model columns 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0001
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0002
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0004
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0005
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0007
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0009
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0001
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0002
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0004
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0005
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0007
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0009
Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0001
Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0002
Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0004
Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0005
Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0007
Power ratings 400 V — Input | Input Current <2> (A) | ND Rating | 4A0009
Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0001
Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0002
Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0004
Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0005
Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0007
Power ratings 400 V — Input Current <2> (A) | HD Rating | 4A0009
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0001
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0002
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0004
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0005
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0007
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0009
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0001
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0002
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0004
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0005
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0007
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0009
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0001
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0002
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0004
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0005
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0007
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0009
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0001
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0002
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0004
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0005
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0007
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0009
Power ratings 400 V — Overload Tolerance | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Carrier Frequency | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Max Output Voltage (V) | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Max Output Frequency (Hz) | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Allowable Voltage Fluctuation | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Allowable Frequency Fluctuation | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 0.5 | 0.75/1.0 | 1.5/2.0 | 3.0 | 3.0 | 5.0 |
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 0.5 | 0.75 | 1.0/1.5/2.0 | 3.0 | 3.0 | 3.0 |
Power ratings 400 V — Input | Input Current <2> (A) | ND Rating — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 1.2 | 2.1 | 4.3 | 5.9 | 8.1 | 9.4 |
Power ratings 400 V — Input Current <2> (A) | HD Rating — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 1.2 | 1.8 | 3.2 | 4.4 | 6.0 | 8.2 |
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 0.9 | 1.6 | 3.1 | 4.1 | 5.3 | 6.7 |
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 0.9 | 1.4 | 2.6 | 3.7 | 4.2 | 5.5 |
Power ratings 400 V — Output Current (A) | ND Rating <4> — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 1.2 | 2.1 | 4.1 | 5.4 | 6.9 | 8.8 |
Power ratings 400 V — Output Current (A) | HD Rating <5> — PDF page 345
| Source row | 4A0001 | 4A0002 | 4A0004 | 4A0005 | 4A0007 | 4A0009 |
|---|---|---|---|---|---|---|
| 1 | 1.2 | 1.8 | 3.4 | 4.8 | 5.5 | 7.2 |
Power ratings 400 V — Overload Tolerance — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | ND Rating: 120% of rated output current for 60 s HD Rating: 150% of rated output current for 60 s (Derating may be required for applications that start and stop frequently) |
Power ratings 400 V — Carrier Frequency — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | User-adjustable 2 to 15 kHz |
Power ratings 400 V — Max Output Voltage (V) — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | Three-phase power: 380 to 480 V (proportional to input voltage) |
Power ratings 400 V — Max Output Frequency (Hz) — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | 400 Hz (user-adjustable) |
Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | Three-phase power: 380 to 480 V 50/60 Hz DC power supply: 510 to 680 V <6> |
Power ratings 400 V — Allowable Voltage Fluctuation — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | -15 to 10% |
Power ratings 400 V — Allowable Frequency Fluctuation — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | ±5% |
Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke — PDF page 345
| Source row | All listed model columns: 4A0001, 4A0002, 4A0004, 4A0005, 4A0007, 4A0009 |
|---|---|
| 1 | Optional |
Manual — 400 V larger frame ratings — page 346
Source reference: SIEP C71060618F, December 2016, physical PDF page 346. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table A.5 Power Ratings Continued
Item Specification Three-Phase Model 4A0011 4A0018 4A0023 4A0031 4A0038
Maximum Applicable Motor Capacity (HP) <1>
ND Rating HD Rating
ND Rating Input Input Current (A) <2> HD Rating
Output
ND Rating <4> Output Current (kVA) <3>
HD Rating <5>
ND Rating <4> Output Current (A)
Overload Tolerance Carrier Frequency Max Output Voltage (V) Max Output Frequency (Hz)
Power Supply
Rated Voltage Rated Frequency
Supply Allowable Voltage Fluctuation Allowable Frequency Fluctuation Harmonic Corrective Actions DC Link Choke
<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current. <2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance. <3> Rated motor capacity is calculated with a rated output voltage of 440 V. <4> Carrier frequency is set to 2 kHz (Swing PWM). Current derating is required to raise the carrier frequency. <5> Carrier frequency is set to 8 kHz. Current derating is required to raise the carrier frequency. <6> DC is not available for UL standards.
A.3 Three-Phase 400 V Class Drives
Actual physical source row; model columns 4A0011, 4A0018, 4A0023, 4A0031, 4A0038. HD/ND and phase labels retained in title. Literal source footnotes restrict applicability, especially BA0018 HD only on343. Values in shared cells do not create unlisted models or single-phase variants. See all same-page qualifications.
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0011
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0018
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0023
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0031
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating | 4A0038
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0011
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0018
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0023
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0031
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating | 4A0038
Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0011
Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0018
Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0023
Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0031
Power ratings 400 V — Input | Input Current (A) <2> | ND Rating | 4A0038
Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0011
Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0018
Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0023
Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0031
Power ratings 400 V — Input Current (A) <2> | HD Rating | 4A0038
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0011
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0018
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0023
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0031
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> | 4A0038
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0011
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0018
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0023
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0031
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> | 4A0038
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0011
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0018
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0023
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0031
Power ratings 400 V — Output Current (A) | ND Rating <4> | 4A0038
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0011
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0018
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0023
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0031
Power ratings 400 V — Output Current (A) | HD Rating <5> | 4A0038
Power ratings 400 V — Overload Tolerance | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Carrier Frequency | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Max Output Voltage (V) | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Max Output Frequency (Hz) | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Allowable Voltage Fluctuation | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Allowable Frequency Fluctuation | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | ND Rating — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 7.5 | 10.0 | 15.0 | 20.0 | 25.0 |
Power ratings 400 V — Maximum Applicable Motor Capacity (HP) <1> | HD Rating — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 5.0 | 10.0 | 10.0 | 15.0 | 20.0 |
Power ratings 400 V — Input | Input Current (A) <2> | ND Rating — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 14.0 | 20.0 | 24.0 | 38.0 | 44.0 |
Power ratings 400 V — Input Current (A) <2> | HD Rating — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 10.4 | 15.0 | 20.0 | 29.0 | 39.0 |
Power ratings 400 V — Output | Output Current (kVA) <3> | ND Rating <4> — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 8.5 | 13.3 | 17.5 | 23.6 | 29.0 |
Power ratings 400 V — Output Current (kVA) <3> | HD Rating <5> — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 7.0 | 11.3 | 13.7 | 18.3 | 23.6 |
Power ratings 400 V — Output Current (A) | ND Rating <4> — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 11.1 | 17.5 | 23.0 | 31.0 | 38.0 |
Power ratings 400 V — Output Current (A) | HD Rating <5> — PDF page 346
| Source row | 4A0011 | 4A0018 | 4A0023 | 4A0031 | 4A0038 |
|---|---|---|---|---|---|
| 1 | 9.2 | 14.8 | 18.0 | 24.0 | 31.0 |
Power ratings 400 V — Overload Tolerance — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | ND Rating: 120% of rated output current for 60 s HD Rating: 150% of rated output current for 60 s (Derating may be required for applications that start and stop frequently) |
Power ratings 400 V — Carrier Frequency — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | User-adjustable 2 to 15 kHz |
Power ratings 400 V — Max Output Voltage (V) — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | Three-phase power: 380 to 480 V (proportional to input voltage) |
Power ratings 400 V — Max Output Frequency (Hz) — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | 400 Hz (user-adjustable) |
Power ratings 400 V — Power Supply | Rated Voltage Rated Frequency — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | Three-phase power: 380 to 480 V 50/60 Hz DC power supply: 510 to 680 V <6> |
Power ratings 400 V — Allowable Voltage Fluctuation — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | -15 to 10% |
Power ratings 400 V — Allowable Frequency Fluctuation — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | ±5% |
Power ratings 400 V — Harmonic Corrective Actions | DC Link Choke — PDF page 346
| Source row | All listed model columns: 4A0011, 4A0018, 4A0023, 4A0031, 4A0038 |
|---|---|
| 1 | Optional |
Manual — Control specifications — page 347
Source reference: SIEP C71060618F, December 2016, physical PDF page 347. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A.4 Drive Specifications
Note: 1. Perform rotational Auto-Tuning to obtain OLV performance specifications. 2. For optimum performance life of the drive, install the drive in an environment that meets the environmental conditions.
Item Specification
Control Character- istics
Control Method
Frequency Control Range
Frequency Accuracy
Frequency Setting Resolution
Output Frequency Calculation Resolution
Frequency Setting Signal
Starting Torque
Speed Control Range
Speed Control Accuracy
Speed Response
Torque Limit
Accel/Decel Time
Braking Torque
V/f Characteristics
Functions
A
Specifications
Literal source row. Full PDF347–349 footnotes apply; historical compliance claims not validated certification. No installation approval inferred.
Drive specifications — Control Character- istics | Control Method | Specification
Drive specifications — Control Character- istics | Frequency Control Range | Specification
Drive specifications — Control Character- istics | Frequency Accuracy | Specification
Drive specifications — Control Character- istics | Frequency Setting Resolution | Specification
Drive specifications — Control Character- istics | Output Frequency Calculation Resolution | Specification
Drive specifications — Control Character- istics | Frequency Setting Signal | Specification
Drive specifications — Control Character- istics | Starting Torque | Specification
Drive specifications — Control Character- istics | Speed Control Range | Specification
Drive specifications — Control Character- istics | Speed Control Accuracy | Specification
Drive specifications — Control Character- istics | Speed Response | Specification
Drive specifications — Control Character- istics | Torque Limit | Specification
Drive specifications — Control Character- istics | Accel/Decel Time | Specification
Drive specifications — Control Character- istics | Braking Torque | Specification
Drive specifications — Control Character- istics | V/f Characteristics | Specification
Drive specifications — Control Character- istics | Functions | Specification
Drive specifications — Control Character- istics | Control Method — PDF page 347
| Source row | Specification |
|---|---|
| 1 | The following control methods are available: Open Loop Vector Control (current vector), V/f Control, and PM Open Loop Vector (for use with SPM and IPM) |
Drive specifications — Control Character- istics | Frequency Control Range — PDF page 347
| Source row | Specification |
|---|---|
| 1 | 0.01 to 400 Hz |
Drive specifications — Control Character- istics | Frequency Accuracy — PDF page 347
| Source row | Specification |
|---|---|
| 1 | Digital input: within ±0.01% of the max output frequency (-10 to +50 °C) Analog input: within ±0.5% of the max output frequency (25 °C ±10 °C) |
Drive specifications — Control Character- istics | Frequency Setting Resolution — PDF page 347
| Source row | Specification |
|---|---|
| 1 | Digital inputs: 0.01 Hz Analog inputs: 1/1000 of maximum output frequency |
Drive specifications — Control Character- istics | Output Frequency Calculation Resolution — PDF page 347
| Source row | Specification |
|---|---|
| 1 | 1/(2^20) x Maximum output frequency (E1-04) |
Drive specifications — Control Character- istics | Frequency Setting Signal — PDF page 347
| Source row | Specification |
|---|---|
| 1 | Main frequency reference: 0 to +10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω) Main speed reference: Pulse Train Input (max 32 kHz) |
Drive specifications — Control Character- istics | Starting Torque — PDF page 347
| Source row | Specification |
|---|---|
| 1 | 200%/0.5 Hz (OLV Control, HD rating, IM of 3.7 kW or smaller), 50%/6 Hz (OLV/PM Control) |
Drive specifications — Control Character- istics | Speed Control Range — PDF page 347
| Source row | Specification |
|---|---|
| 1 | 1:100 (OLV Control), 1:40 (V/f Control), 1:10 (OLV/PM Control) |
Drive specifications — Control Character- istics | Speed Control Accuracy — PDF page 347
| Source row | Specification |
|---|---|
| 1 | ±0.2% in Open Loop Vector Control <1> |
Drive specifications — Control Character- istics | Speed Response — PDF page 347
| Source row | Specification |
|---|---|
| 1 | 5 Hz (25 °C ±10 °C) in Open Loop Vector Control (excludes temperature fluctuation when performing Rotational Auto-Tuning) |
Drive specifications — Control Character- istics | Torque Limit — PDF page 347
| Source row | Specification |
|---|---|
| 1 | Open Loop Vector Control only. Adjustable in 4 quadrants. |
Drive specifications — Control Character- istics | Accel/Decel Time — PDF page 347
| Source row | Specification |
|---|---|
| 1 | 0.00 to 6000.0 s (allows four separate settings for accel and decel) |
Drive specifications — Control Character- istics | Braking Torque — PDF page 347
| Source row | Specification |
|---|---|
| 1 | Instantaneous Average Decel Torque <2> : 0.1/0.2 kW: over 150%, 0.4/0.75 kW: over 100%, 1.5 kW: over 50%, 2.2 kW and above: over 20% Continuous Regen Torque: 20%, 125% with a Braking Resistor Unit <3> : (10% ED) 10 s with an internal braking transistor. |
Drive specifications — Control Character- istics | V/f Characteristics — PDF page 347
| Source row | Specification |
|---|---|
| 1 | Preset V/f patterns and user-set program available. |
Drive specifications — Control Character- istics | Functions — PDF page 347
| Source row | Specification |
|---|---|
| 1 | Momentary Power Loss Ride-Thru Speed Search Over/Undertorque Detection Torque Limit, Multi-Step Speed (17 steps max) Accel/Decel Time Switch S-Curve Accel/Decel, 2-Wire/3-Wire Sequence Rotational Auto-Tuning Stationary Auto-Tuning of Line-to-Line Resistance Dwell Cooling Fan ON/OFF Slip Compensation Torque Compensation Jump Frequencies (reference dead band) Frequency Reference Upper/Lower Limit DC Injection Braking (start and stop), High Slip Braking PID Control (with Sleep Function) Energy Saving MEMOBUS/Modbus (RS-485/RS-422 Max 115.2 kbps) Fault Reset Parameter Copy DriveWorksEZ Fault Restart Removable Terminals with Parameter Backup Function |
Manual — Protection and environment specifications — page 348
Source reference: SIEP C71060618F, December 2016, physical PDF page 348. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Item Specification
Protection Functions
Motor Protection
Overcurrent Protection
Overload Protection
Overvoltage Specification
Low Voltage Protection
Momentary Power Loss Ride-Thru
Heatsink Overheat Protection
Braking Resistor Overheat Protection
Stall Prevention
Cooling Fan Failure Protection
Ground Fault Protection
DC Bus Charge LED
Environment
Storage/Installation Area
Ambient Temperature
Humidity
Storage Temperature
Altitude
Shock, Impact
Surrounding Area
Orientation
Standards
Protective Enclosure
Cooling Method
<1> Speed control accuracy varies somewhat according to the type of motor and drive settings. <2> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed down to zero in the shortest time. <3> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a braking resistor or the Braking Resistor Unit. The default setting for the stall prevention function will interfere with the braking transistor. <4> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
A.4 Drive Specifications
Literal source row. Full PDF347–349 footnotes apply; historical compliance claims not validated certification. No installation approval inferred.
Drive specifications — Protection Functions | Motor Protection | Specification
Drive specifications — Protection Functions | Overcurrent Protection | Specification
Drive specifications — Protection Functions | Overload Protection | Specification
Drive specifications — Protection Functions | Overvoltage Specification | Specification
Drive specifications — Protection Functions | Low Voltage Protection | Specification
Drive specifications — Protection Functions | Momentary Power Loss Ride-Thru | Specification
Drive specifications — Protection Functions | Heatsink Overheat Protection | Specification
Drive specifications — Protection Functions | Braking Resistor Overheat Protection | Specification
Drive specifications — Protection Functions | Stall Prevention | Specification
Drive specifications — Protection Functions | Cooling Fan Failure Protection | Specification
Drive specifications — Protection Functions | Ground Fault Protection | Specification
Drive specifications — Protection Functions | DC Bus Charge LED | Specification
Drive specifications — Environment | Storage/Installation Area | Specification
Drive specifications — Environment | Ambient Temperature | Specification
Drive specifications — Environment | Humidity | Specification
Drive specifications — Environment | Storage Temperature | Specification
Drive specifications — Environment | Altitude | Specification
Drive specifications — Environment | Shock, Impact | Specification
Drive specifications — Environment | Surrounding Area | Specification
Drive specifications — Environment | Orientation | Specification
Drive specifications — Standards | Specification
Drive specifications — Protective Enclosure | Specification
Drive specifications — Cooling Method | Specification
Drive specifications — Protection Functions | Motor Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Motor overheat protection via output current sensor |
Drive specifications — Protection Functions | Overcurrent Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Drives stops when output exceeds 200% of the rated current (Heavy Duty) |
Drive specifications — Protection Functions | Overload Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | A stop command will be entered after operating at 150% for 60 s (Heavy Duty) <4> |
Drive specifications — Protection Functions | Overvoltage Specification — PDF page 348
| Source row | Specification |
|---|---|
| 1 | 200 V Class: Stops when DC bus voltage exceeds approx. 410 V 400 V Class: Stops when DC bus voltage exceeds approx. 820 V |
Drive specifications — Protection Functions | Low Voltage Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Drive stops when DC bus voltage falls below the levels indicated: <5> 190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V), 350 V (3-phase 380 V) |
Drive specifications — Protection Functions | Momentary Power Loss Ride-Thru — PDF page 348
| Source row | Specification |
|---|---|
| 1 | 3 selections available: Ride-Thru disabled (stops after 15 ms), time <6> base of 0.5 s, and continue running as long as the drive control board is powered up. |
Drive specifications — Protection Functions | Heatsink Overheat Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Protected by thermistor |
Drive specifications — Protection Functions | Braking Resistor Overheat Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Overheat input signal for braking resistor (Optional ERF-type, 3% ED) |
Drive specifications — Protection Functions | Stall Prevention — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Stall prevention is available during acceleration, deceleration, and during run. Separate settings for each type of stall prevention determine the current level at which stall prevention is triggered. |
Drive specifications — Protection Functions | Cooling Fan Failure Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Circuit protection (“fan-lock” sensor) |
Drive specifications — Protection Functions | Ground Fault Protection — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Electronic circuit protection <7> |
Drive specifications — Protection Functions | DC Bus Charge LED — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Remains lit until DC bus voltage falls below 50 V |
Drive specifications — Environment | Storage/Installation Area — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Indoors |
Drive specifications — Environment | Ambient Temperature — PDF page 348
| Source row | Specification |
|---|---|
| 1 | IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F) IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F) Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F) NEMA Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F) |
Drive specifications — Environment | Humidity — PDF page 348
| Source row | Specification |
|---|---|
| 1 | 95% RH or less with no condensation |
Drive specifications — Environment | Storage Temperature — PDF page 348
| Source row | Specification |
|---|---|
| 1 | -20 to +60 °C (-4 to +140 °F) allowed for short-term transport of the product |
Drive specifications — Environment | Altitude — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Up to 1000 meters without derating; up to 3000 meters with output current and voltage derating. Refer to Altitude Derating on page 352 for details. |
Drive specifications — Environment | Shock, Impact — PDF page 348
| Source row | Specification |
|---|---|
| 1 | 10 to 20 Hz: 9.8 m/s2 20 to 55 Hz: 5.9 m/s2 |
Drive specifications — Environment | Surrounding Area — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Install the drive in an area free from: • oil mist and dust • metal shavings, oil, water or other foreign materials • radioactive materials • combustible materials • harmful gases and liquids • excessive vibration • chlorides • direct sunlight |
Drive specifications — Environment | Orientation — PDF page 348
| Source row | Specification |
|---|---|
| 1 | Install the drive vertically to maintain maximum cooling effects |
Drive specifications — Standards — PDF page 348
| Source row | Specification |
|---|---|
| 1 | • UL508C • EN 61800-3:2004/A1:2012, IEC/EN 61800-5-1 • ISO/EN 13849-1 Cat.3 PLd, IEC/EN 61508 SIL2 Time from input open to drive output stop is less than 1 ms. |
Drive specifications — Protective Enclosure — PDF page 348
| Source row | Specification |
|---|---|
| 1 | IP20/Open-Chassis or IP00/Open-Chassis <8> IP20/NEMA Type 1 <9> |
Drive specifications — Cooling Method — PDF page 348
| Source row | Specification |
|---|---|
| 1 | BA0001 to BA0006: self-cooled BA0010 to BA0018: cooling fan 2A0001 to 2A0004: self-cooled 2A0006 to 2A0069: cooling fan 4A0001 to 4A0004: self-cooled 4A0005 to 4A0038: cooling fan |
Manual — Specification footnotes — page 349
Source reference: SIEP C71060618F, December 2016, physical PDF page 349. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
<5> Parameter settings allow up to 150 V. <6> A Momentary Power Loss Ride-Thru Unit is required for 200/400 V class drives 7.5 kW and less if the application needs to continue running during a momentary power loss up to 2 seconds. <7> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the motor windings during run: Low ground resistance for the motor cable and terminal block; low ground resistance for the motor cable and terminal block; or the drive is powered up from a ground short. <8> The following models have an IP20/Open-Chassis enclosure as standard. Customers may convert these models to IP20/NEMA Type 1 enclosures using the IP20/NEMA Type 1 Kit Option: 2A0030 to 2A0069 4A0018 to 4A0038 <9> The following models have an IP20/NEMA Type 1 enclosure as standard. For an IP20/Open-Chassis or IP00/Open-Chassis design, remove the top and bottom covers: BA0001 to BA0018 2A0001 to 2A0020 4A0001 to 4A0011
Note: Time from input open to drive output stop is less than 1 ms.
A.4 Drive Specifications
A
Specifications
Manual — Watt loss by model and duty — page 350
Source reference: SIEP C71060618F, December 2016, physical PDF page 350. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
A.5 Drive Watt Loss Data
Table A.6 Watt Loss 200 V Class Single-Phase Models
Drive Model
Heavy Duty (Carrier Frequency 8 kHz) <1> Normal Duty (Swing PWM equal 2 kHz)
Rated Amps (A)
Heatsink Loss (W)
Interior Unit Loss (W)
Total Loss (W)
Drive Model Rated Amps Heatsink Interior Unit Total Loss Rated Amps Heatsink Interior Unit Total Loss (A) Loss (W) Loss (W) (W) (A) Loss (W) Loss (W) (W)
<1> 10 kHz for BA0001 to BA0006
Table A.7 Watt Loss 200 V Class Three-Phase Models
<1> 10 kHz for 2A0001 to 2A0006
Table A.8 Watt Loss 400 V Class Three-Phase Models
Heavy Duty (Carrier Frequency 8 kHz) Normal Duty (Swing PWM equal 2 kHz) Rated Amps Heatsink Interior Unit Total Loss Rated Amps Heatsink Interior Unit Total (A) Loss (W) Loss (W) (W) (A) Loss (W) Loss (W)
Watt loss — 200 V single-phase | Drive model
Watt loss — 200 V single-phase | HD rated amps (A)
Watt loss — 200 V single-phase | HD heatsink loss (W)
Watt loss — 200 V single-phase | HD interior unit loss (W)
Watt loss — 200 V single-phase | HD total loss (W)
Watt loss — 200 V single-phase | ND rated amps (A)
Watt loss — 200 V single-phase | ND heatsink loss (W)
Watt loss — 200 V single-phase | ND interior unit loss (W)
Watt loss — 200 V single-phase | ND total loss (W)
Watt loss — 200 V three-phase | Drive model
Watt loss — 200 V three-phase | HD rated amps (A)
Watt loss — 200 V three-phase | HD heatsink loss (W)
Watt loss — 200 V three-phase | HD interior unit loss (W)
Watt loss — 200 V three-phase | HD total loss (W)
Watt loss — 200 V three-phase | ND rated amps (A)
Watt loss — 200 V three-phase | ND heatsink loss (W)
Watt loss — 200 V three-phase | ND interior unit loss (W)
Watt loss — 200 V three-phase | ND total loss (W)
Watt loss — 400 V three-phase | Drive model
Watt loss — 400 V three-phase | HD rated amps (A)
Watt loss — 400 V three-phase | HD heatsink loss (W)
Watt loss — 400 V three-phase | HD interior unit loss (W)
Watt loss — 400 V three-phase | HD total loss (W)
Watt loss — 400 V three-phase | ND rated amps (A)
Watt loss — 400 V three-phase | ND heatsink loss (W)
Watt loss — 400 V three-phase | ND interior unit loss (W)
Watt loss — 400 V three-phase | ND total loss (W)
Watt loss — 200 V single-phase — PDF page 350
| Source row | Drive model | HD rated amps (A) | HD heatsink loss (W) | HD interior unit loss (W) | HD total loss (W) | ND rated amps (A) | ND heatsink loss (W) | ND interior unit loss (W) | ND total loss (W) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | BA0001 | 0.8 | 4.3 | 7.4 | 11.7 | 1.2 | 5.0 | 8.5 | 13.5 |
| 2 | BA0002 | 1.6 | 7.9 | 8.9 | 16.7 | 1.9 | 7.6 | 9.7 | 17.3 |
| 3 | BA0003 | 3.0 | 16.1 | 11.5 | 27.7 | 3.2 | 14.6 | 14.4 | 29.1 |
| 4 | BA0006 | 5.0 | 33.7 | 16.8 | 50.5 | 6.0 | 30.1 | 19.4 | 49.5 |
| 5 | BA0010 | 8.0 | 54.8 | 25.9 | 80.7 | 9.6 | 51.7 | 29.8 | 81.4 |
| 6 | BA0012 | 11.0 | 70.7 | 34.1 | 104.8 | 12.0 | 61.3 | 37.1 | 98.4 |
| 7 | BA0018 | 17.5 | 110.5 | 51.4 | 161.9 | — | — | — | — |
Watt loss — 200 V three-phase — PDF page 350
| Source row | Drive model | HD rated amps (A) | HD heatsink loss (W) | HD interior unit loss (W) | HD total loss (W) | ND rated amps (A) | ND heatsink loss (W) | ND interior unit loss (W) | ND total loss (W) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 2A0001 | 0.8 | 4.3 | 7.3 | 11.6 | 1.2 | 5.0 | 8.0 | 13.0 |
| 2 | 2A0002 | 1.6 | 7.9 | 8.8 | 16.7 | 1.9 | 7.6 | 9.5 | 17.1 |
| 3 | 2A0004 | 3.0 | 16.2 | 11.5 | 27.7 | 3.5 | 15.8 | 13.6 | 29.4 |
| 4 | 2A0006 | 5.0 | 27.4 | 15.9 | 43.3 | 6.0 | 27.5 | 17.2 | 44.7 |
| 5 | 2A0010 | 8.0 | 54.8 | 23.8 | 78.6 | 9.6 | 51.7 | 25.8 | 77.5 |
| 6 | 2A0012 | 11.0 | 70.7 | 29.9 | 100.6 | 12.0 | 61.3 | 30.4 | 91.7 |
| 7 | 2A0020 | 17.5 | 110.5 | 43.3 | 153.8 | 19.6 | 98.7 | 46.3 | 145.0 |
| 8 | 2A0030 | 25.0 | 231.5 | 72.2 | 303.7 | 30.0 | 246.4 | 88.9 | 335.3 |
| 9 | 2A0040 | 33.0 | 339.5 | 82.8 | 321.3 | 40.0 | 266.7 | 112.8 | 379.6 |
| 10 | 2A0056 | 47.0 | 347.6 | 117.6 | 465.2 | 56.0 | 357.9 | 151.8 | 509.7 |
| 11 | 2A0069 | 60.0 | 437.7 | 151.4 | 589.1 | 69.0 | 461.7 | 184.5 | 646.2 |
Watt loss — 400 V three-phase — PDF page 350
| Source row | Drive model | HD rated amps (A) | HD heatsink loss (W) | HD interior unit loss (W) | HD total loss (W) | ND rated amps (A) | ND heatsink loss (W) | ND interior unit loss (W) | ND total loss (W) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 4A0001 | 1.2 | 19.2 | 11.5 | 30.7 | 1.2 | 10.0 | 9.6 | 19.6 |
| 2 | 4A0002 | 1.8 | 28.9 | 14.8 | 43.7 | 2.1 | 18.5 | 13.9 | 32.4 |
| 3 | 4A0004 | 3.4 | 42.3 | 17.9 | 60.2 | 4.1 | 30.5 | 16.8 | 47.3 |
| 4 | 4A0005 | 4.8 | 70.7 | 26.2 | 96.9 | 5.4 | 44.5 | 21.8 | 66.3 |
| 5 | 4A0007 | 5.5 | 81.0 | 30.7 | 111.7 | 6.9 | 58.5 | 28.4 | 86.9 |
| 6 | 4A0009 | 7.2 | 84.6 | 32.9 | 117.5 | 8.8 | 63.7 | 31.4 | 95.1 |
| 7 | 4A0011 | 9.2 | 107.2 | 41.5 | 148.7 | 11.1 | 81.7 | 46.0 | 127.7 |
| 8 | 4A0018 | 14.8 | 166.0 | 62.7 | 228.7 | 17.5 | 181.2 | 80.1 | 261.3 |
| 9 | 4A0023 | 18.0 | 207.1 | 78.1 | 285.2 | 23.0 | 213.4 | 107.7 | 321.1 |
| 10 | 4A0031 | 24.0 | 266.9 | 105.9 | 372.8 | 31.0 | 287.5 | 146.1 | 433.6 |
| 11 | 4A0038 | 31.0 | 319.1 | 126.6 | 445.7 | 38.0 | 319.2 | 155.8 | 475.0 |
Manual — Carrier and ambient derating — page 351
Source reference: SIEP C71060618F, December 2016, physical PDF page 351. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive Rating vertical0,HD,ND;horizontalCarrier Frequency(C6-02)ticks2,10(8),15. At15,source marks200VClass80%ofHD and400VClass60%ofHD;HDflatto10(8),NDflatto2thenlinefalls toHD at10(8). FigureA.1 Carrier Frequency Derating. Carrierfrequencyaxis itself prints no unit; kHz context comes from surrounding specification tables, not inferred into axis. Exact curves remain original-only; no intermediate value interpolation or operating approval.
Drive Rating axis0%,50%,70%,80%,85%,100%;Ambienttemp°C,ParameterL8-12 ticks-10°,30°,35°,40°,50°. CurvelabelsL8-35=0(IP20/IP00Drive),=2(NEMAType1Drive),=3(Finless Drive orExternalHeatsinkInstallation),=1(Side-by-SideMounting). FigureA.2 Ambient Temperature and Installation Method Derating; exact curve intersections remain original-only. Exact curves remain original-only; no intermediate value interpolation or operating approval.
A.6 Drive Derating Data
The drive can be operated at above rated temperature, altitude and default carrier frequency by derating the drive capacity.
u Carrier Frequency Derating
Derate drive capacity using Figure A.1 as the carrier frequency of the drive increases above the factory setting.
u Temperature Derating
As the ambient temperature for the drive is increased above the drive specification the drive should be derated. Additionally parameter L8-35 Installation Method Selection on page 351 should be set according to enclosure type and mounting method as illustrated in Figure A.2.
n Output Current Derating Due to Ambient Temperature
Set L8-12 and L8-35 according to the installation conditions when the ambient temperature is above the drive specification or when drives are mounted side-by-side in a cabinet. The output current is derated as shown in Figure A.2.
No. Name Description Range Def.
A
Specifications
L8-12 | Ambient Temperature Setting
L8-35 | Installation Method Selection
Temperature and installation derating parameters — PDF page 351
| Source row | Parameter | Name | Description | Range | Default |
|---|---|---|---|---|---|
| 1 | L8-12 | Ambient Temperature Setting | Adjust the drive overload (oL2) protection level when the drive is installed in an environment that exceeds its ambient temperature rating. | -10 to 50 | 40 °C |
| 2 | L8-35 | Installation Method Selection | 0: IP20/IP00 Drive 1: Side-by-Side Mounting 2: NEMA Type 1 Drive 3: Finless Drive or External Heatsink Installation | 0 to 3 | 0 |
Manual — Altitude derating — page 352
Source reference: SIEP C71060618F, December 2016, physical PDF page 352. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u Altitude Derating
The drive standard ratings are valid for an installation altitude up to 1000 m. If the altitude exceeds 1000 m, both the drive input voltage and the rated output current must be derated for 1% per 100 m. The maximum altitude is 3000 m.
A.6 Drive Derating Data
Manual — Parameter group index — page 354
Source reference: SIEP C71060618F, December 2016, physical PDF page 354. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
B.1 Parameter Groups
Parameter Name Page Group
A1 | Initialization
A2 | User Parameters
b1 | Operation Mode Selection
b2 | DC Injection Braking
b3 | Speed Search
b4 | Delay Timer
b5 | PID Control
b6 | Dwell Function
b8 | Energy Saving
C1 | Acceleration/Deceleration Time
C2 | S-Curve Accel/Decel
C3 | Motor Slip Compensation
C4 | Motor Torque Compensation
C5 | Speed Control (ASR)
C6 | Carrier Frequency
d1 | Frequency Reference
d2 | Reference Limits
d3 | Jump Frequencies
d4 | Frequency Reference Hold
d7 | Off-Set Frequency
E1 | V/f Pattern
E2 | Motor Setup
E3 | Motor 2 V/f Pattern
E4 | Motor Setup 2
E5 | PM Motor Setup
F1 | Fault Detection during PG Speed Control
F6 | Network Communications
F7 | EtherNet/IP and Modbus TCP/IP Communications
H1 | Digital Inputs
H2 | Digital Outputs
H3 | Analog Inputs
H4 | Analog Outputs
H5 | Serial Communications Setup
H6 | Pulse Train I/O Setup
L1 | Motor Overload
L2 | Power Loss Ride-Thru
L3 | Stall Prevention
L4 | Reference Detection
L5 | Fault Restart
L6 | Overtorque Detection
L7 | Torque Limit
L8 | Hardware Protection
n1 | Hunting Prevention
n2 | Speed Feedback Detection
n3 | High-Slip Braking
n6 | Motor Line-to-Line Resistance Online Tuning
n8 | PM Motor Control
o1 | Monitor Display Selection
o2 | Operator Keypad Functions
o4 | Maintenance Functions
q | DWEZ Parameters
r | DriveWorksEZ Connection
T1 | Auto-Tuning
U1 | Status Monitor
U2 | Fault Trace
U3 | Fault History
U4 | Maintenance Monitor
U5 | PID Monitor
U6 | Control Monitor
U8 | Custom Monitors for DriveWorksEZ
Parameter group index 1 — PDF page 354
| Source row | Parameter group | Name | Reference page |
|---|---|---|---|
| 1 | A1 | Initialization | 355 |
| 2 | A2 | User Parameters | 356 |
| 3 | b1 | Operation Mode Selection | 356 |
| 4 | b2 | DC Injection Braking | 357 |
| 5 | b3 | Speed Search | 358 |
| 6 | b4 | Delay Timer | 358 |
| 7 | b5 | PID Control | 358 |
| 8 | b6 | Dwell Function | 360 |
| 9 | b8 | Energy Saving | 360 |
| 10 | C1 | Acceleration/Deceleration Time | 361 |
| 11 | C2 | S-Curve Accel/Decel | 362 |
| 12 | C3 | Motor Slip Compensation | 362 |
| 13 | C4 | Motor Torque Compensation | 362 |
| 14 | C5 | Speed Control (ASR) | 363 |
| 15 | C6 | Carrier Frequency | 363 |
| 16 | d1 | Frequency Reference | 364 |
| 17 | d2 | Reference Limits | 365 |
| 18 | d3 | Jump Frequencies | 365 |
| 19 | d4 | Frequency Reference Hold | 365 |
| 20 | d7 | Off-Set Frequency | 366 |
| 21 | E1 | V/f Pattern | 367 |
| 22 | E2 | Motor Setup | 367 |
| 23 | E3 | Motor 2 V/f Pattern | 368 |
| 24 | E4 | Motor Setup 2 | 369 |
| 25 | E5 | PM Motor Setup | 370 |
| 26 | F1 | Fault Detection during PG Speed Control | 371 |
| 27 | F6 | Network Communications | 372 |
| 28 | F7 | EtherNet/IP and Modbus TCP/IP Communications | 374 |
| 29 | H1 | Digital Inputs | 376 |
| 30 | H2 | Digital Outputs | 378 |
Parameter group index 2 — PDF page 354
| Source row | Parameter group | Name | Reference page |
|---|---|---|---|
| 1 | H3 | Analog Inputs | 381 |
| 2 | H4 | Analog Outputs | 382 |
| 3 | H5 | Serial Communications Setup | 382 |
| 4 | H6 | Pulse Train I/O Setup | 383 |
| 5 | L1 | Motor Overload | 384 |
| 6 | L2 | Power Loss Ride-Thru | 384 |
| 7 | L3 | Stall Prevention | 385 |
| 8 | L4 | Reference Detection | 387 |
| 9 | L5 | Fault Restart | 387 |
| 10 | L6 | Overtorque Detection | 387 |
| 11 | L7 | Torque Limit | 389 |
| 12 | L8 | Hardware Protection | 389 |
| 13 | n1 | Hunting Prevention | 391 |
| 14 | n2 | Speed Feedback Detection | 392 |
| 15 | n3 | High-Slip Braking | 392 |
| 16 | n6 | Motor Line-to-Line Resistance Online Tuning | 392 |
| 17 | n8 | PM Motor Control | 392 |
| 18 | o1 | Monitor Display Selection | 394 |
| 19 | o2 | Operator Keypad Functions | 394 |
| 20 | o4 | Maintenance Functions | 395 |
| 21 | q | DWEZ Parameters | 396 |
| 22 | r | DriveWorksEZ Connection | 396 |
| 23 | T1 | Auto-Tuning | 398 |
| 24 | U1 | Status Monitor | 399 |
| 25 | U2 | Fault Trace | 400 |
| 26 | U3 | Fault History | 401 |
| 27 | U4 | Maintenance Monitor | 402 |
| 28 | U5 | PID Monitor | 403 |
| 29 | U6 | Control Monitor | 404 |
| 30 | U8 | Custom Monitors for DriveWorksEZ | 404 |
Manual — Control mode legend and initialization — page 355
Source reference: SIEP C71060618F, December 2016, physical PDF page 355. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
B.2 Parameter Table
An “A” in the “Control Mode” column indicates that the parameter is available in the Advanced menu of the respective control mode. An “S” in the “Control Mode” column indicates that the parameter is available in the Startup menu of the respective control mode. A “–” in the “Control Mode” column indicates that the parameter is NOT available in the respective control mode. An “O” in the “Control Mode” column indicates that the multi-function selection is available in the respective control mode.
u A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor Control Method, Password, User Parameters and more.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
A1: Initialization Parameters Use A1 parameters to configure the basic environment for drive operation.
The following parameters are not reset when the performing initialization: A1-00, A1-02, A1-07, E1-03, E5-□□, F6-08, L8-35, o2-04, o2-09, and all U2 and U3 monitors.
This parameter is hidden from view. To access A1-05, first display A1-04. Then press the STOP key while holding down — the up arrow key. Parameter A1-05 will appear.
—
B
List Parameter
A1-00 <1> <2> | Language Selection
A1-01 <1> <3> | Access Level Selection
A1-02 <2> | Control Method Selection
A1-03 | Initialize Parameters
A1-04 | Password
A1-05 | Password Setting
Parameter catalogue PDF355 section1 — PDF page 355
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | A1-00 <1> <2> | Language Selection | 0: English 1: Japanese 2: German 3: French 4: Italian 5: Spanish 6: Portuguese 7: Chinese | 0 to 7 | 0 | A | A | A | 100 | 116 |
| 2 | A1-01 <1> <3> | Access Level Selection | Selects which parameters are accessible via the digital operator. 0: Operation only 1: User Parameters (access to a set of parameters selected by the user) 2: Advanced Access Level | 0 to 2 | 2 | A | A | A | 101 | 116 |
| 3 | A1-02 <2> | Control Method Selection | Selects the Control Method of the drive. Auto-Tuning must be performed when selecting one of the vector control modes. 0: V/f Control without PG 2: Open Loop Vector (OLV) 5: PM Open Loop Vector (PM) Note: 1. Does not return to the default setting after initialization. 2. If using Open Loop Vector Control (A1-02 = 2), then Auto-Tuning must be performed again after the drive is initialized. Refer to Auto- Tuning on page 102 for details. | 0, 2, 5 | 0 | S | S | S | 102 | 116 |
| 4 | A1-03 | Initialize Parameters | Resets all parameters to factory default settings. (Initializes the drive then returns A1-03 to 0) 0: No Initialization 1110: User Initialize (First set user parameter values must be stored using parameter o2-03) 2220: 2-Wire Initialization 3330: 3-Wire Initialization 5550: oPE04 Error Reset | 0 to 5550 | 0 | A | A | A | 103 | 117 |
| 5 | A1-04 | Password | When the value set into A1-04 does not match the value set into A1-05, parameters A1-01 through A1-03, A1-06, and A2-01 through A2-32 cannot be changed. | 0 to 9999 | 0 | A | A | A | 104 | 118 |
| 6 | A1-05 | Password Setting | When the value set into A1-04 does not match the value set into A1-05, parameters A1-01 through A1-03, A1-06, and A2-01 through A2-32 cannot be changed. | 0 to 9999 | 0 | A | A | A | 105 | 118 |
Manual — Application presets and run sources — page 356
Source reference: SIEP C71060618F, December 2016, physical PDF page 356. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
A2: User Parameters Use A2 parameters to program the drive.
<1> Parameter can be changed during run. <2> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <3> Default setting value is dependent on parameter A1-06, Application Selection. <4> Available in drive software versions PRG: 1020 and later. <5> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0.
u b: Application
Application parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID control, the Dwell function, Energy Savings and a variety of other application-related settings.
b1: Operation Mode Selection Use b1 parameters to configure the operation mode.
B.2 Parameter Table
A1-06 | Application Preset
A1-07 <2> | DriveWorksEZ Function Selection
A2-01 to A2-32 | User Parameters, 1 to 32
A2-33 | User Parameter Automatic Selection
b1-01 | Frequency Reference Selection 1
b1-02 | Run Command Selection 1
Parameter catalogue PDF356 section1 — PDF page 356
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | A1-06 | Application Preset | Sets parameters that are commonly used in certain applications to A2-01 through A2-16 for easier access. 0: General-purpose (A2 parameters are not affected) 1: Water supply pump 2: Conveyor 3: Exhaust fan 4: HVAC fan 5: Air compressor 8: Conveyor 2 <4> Note: Application Preset settings 6 and 7 are only present in drive software versions PRG: 1011 and earlier. | 0 to 5; 8 | 0 | A | A | A | 127 | 96 |
| 2 | A1-07 <2> | DriveWorksEZ Function Selection | 0: Disabled 1: Enabled 2: Multi-function input (enabled when H1-□□ = 9F) | 0 to 2 | 0 | A | A | A | 128 | 119 |
| 3 | A2-01 to A2-32 | User Parameters, 1 to 32 | Parameters that were recently edited are listed here. The user can also select parameters to appear here for quick access. Parameters will be stored here for quick access when A1-01 = 1. | A1-00 to o2-08 | <3> | A | A | A | 106 to 125 | 120 |
| 4 | A2-33 | User Parameter Automatic Selection | 0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters. 1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for quick access. | 0, 1 | <5> | A | A | A | 126 | 120 |
Parameter catalogue PDF356 section2 — PDF page 356
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | b1-01 | Frequency Reference Selection 1 | Selects the frequency reference input source. 0: Digital operator - Digital preset speed d1-01 to d1-17. 1: Terminals - Analog input terminal A1 or A2. 2: MEMOBUS communications 3: Option PCB 4: Pulse Input (Terminal RP) | 0 to 4 | 1 | S | S | S | 180 | 121 |
| 2 | b1-02 | Run Command Selection 1 | Selects the run command input source. 0: Digital operator - RUN and STOP keys on the digital operator. 1: Digital input terminals 2: MEMOBUS communications 3: Option PCB. | 0 to 3 | 1 | S | S | S | 181 | 123 |
Manual — Run and braking parameters — page 357
Source reference: SIEP C71060618F, December 2016, physical PDF page 357. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
DC Injection Braking at Stop cannot be selected when using Open Loop Vector for PM motors.
b2: DC Injection Braking Use b2 parameters to configure DC Injection Braking operation
B.2 Parameter Table
B
List Parameter
b1-03 | Stopping Method Selection
b1-04 | Reverse Operation Selection
b1-07 | LOCAL/REMOTE Run Selection
b1-08 | Run Command Selection while in Programming Mode
b1-14 | Phase Order Selection
b1-15 | Frequency Reference Selection 2
b1-16 | Run Command Selection 2
b1-17 | Run Command at Power Up
b2-01 | DC Injection Braking Start Frequency
b2-02 | DC Injection Braking Current
b2-03 | DC Injection Braking Time/ DC Excitation Time at Start
b2-04 | DC Injection Braking Time at Stop
b2-08 | Magnetic Flux Compensation Value
b2-12 | Short Circuit Brake Time at Start
Parameter catalogue PDF357 section1 — PDF page 357
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | b1-03 | Stopping Method Selection | Selects the stopping method when the run command is removed. 0: Ramp to Stop 1: Coast to Stop 2: DC Injection Braking to Stop 3: Coast with Timer (A new run command is ignored if received before the timer expires) | 0 to 3 | 0 | S | S | S | 182 | 124 |
| 2 | b1-04 | Reverse Operation Selection | Permits or prohibits reverse operation. 0: Reverse enabled. 1: Reverse disabled. | 0, 1 | 0 | A | A | A | 183 | 126 |
| 3 | b1-07 | LOCAL/REMOTE Run Selection | Determines the operation when the Run command source is switched from LOCAL to REMOTE or between Run source 1 and 2 while an external Run command is active at the new source. 0: External Run command has to be cycled at the new source to be activated. 1: External Run command at new source is accepted immediately. | 0, 1 | 0 | A | A | A | 186 | 127 |
| 4 | b1-08 | Run Command Selection while in Programming Mode | 0: Run command accepted only in the operation menu. 1: Run command accepted in all menus. 2: Prohibit entering Programming Mode during Run | 0 to 2 | 0 | A | A | A | 187 | 127 |
| 5 | b1-14 | Phase Order Selection | Sets the phase order for drive output terminals U/T1, V/T2 and W/T3. 0 : Standard 1 : Switch phase order | 0, 1 | 0 | A | A | A | 1C3 | 127 |
| 6 | b1-15 | Frequency Reference Selection 2 | Selects the frequency reference input source 2. 0: Operator - Digital preset speed d1-01 to d1-17. 1: Terminals - Analog input terminal A1 or A2 2: MEMOBUS communications 3: Option PCB 4: Pulse Input (Terminal RP) | 0 to 4 | 0 | A | A | A | 1C4 | 128 |
| 7 | b1-16 | Run Command Selection 2 | Selects the run command input source 2. 0: Operator - RUN and STOP keys on the digital operator. 1: Digital input terminals 2: MEMOBUS communications 3: Option PCB | 0 to 3 | 0 | A | A | A | 1C5 | 128 |
| 8 | b1-17 | Run Command at Power Up | Determines the operation when a Run command is active at power up of the drive. 0: Run command not issued, needs to be cycled 1: Run command issued, motor operation start | 0, 1 | 0 | A | A | A | 1C6 | 128 |
| 9 | b2-01 | DC Injection Braking Start Frequency | Sets the frequency at which DC Injection Braking starts when Ramp to Stop (b1-03 = 0) is selected. If b2-01< E1-09, DC Injection Braking starts at E1-09. | 0.0 to 10.0 | 0.5 Hz | A | A | A | 189 | 128 |
| 10 | b2-02 | DC Injection Braking Current | Sets the DC Injection Braking current as a percentage of the drive rated current. | 0 to 75 | 50% | A | A | A | 18A | 129 |
| 11 | b2-03 | DC Injection Braking Time/ DC Excitation Time at Start | Sets DC Injection Braking time at start. Disabled when set to 0.00 seconds. | 0.00 to 10.00 | 0.00 s <1> | A | A | A | 18B | 129 |
| 12 | b2-04 | DC Injection Braking Time at Stop | Sets DC Injection Braking time at stop. When b1-03 = 2, actual DC Injection time is calculated as follows: (b2-04) x 10 x (Output Freq)/(E1-04). When b1-03 = 0, this parameter sets the amount of DC Injection time applied to the motor at the end of the decel ramp or High Slip Braking. Disabled when set to 0.00. | 0.00 to 10.00 | 0.50 s | A | A | − | 18C | 129 |
| 13 | b2-08 | Magnetic Flux Compensation Value | Sets the magnetic flux compensation as a percentage of the no- load current value (E2-03). | 0 to 1000 | 0% | − | A | − | 190 | 129 |
| 14 | b2-12 | Short Circuit Brake Time at Start | Sets the time for Short-Circuit brake operation at start. Disabled when set to 0.00. <2> | 0.00 to 25.50 | 0.00 s | − | − | A | 1BA | 129 |
Manual — Speed search and timer parameters — page 358
Source reference: SIEP C71060618F, December 2016, physical PDF page 358. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
b3: Speed Search Use b3 parameters to configure Speed Search function operation.
b4: Timer Function Use b4 parameters to configure timer function operation.
b5: PID Control Use b5 parameters to configure the PID control drive function.
B.2 Parameter Table
b2-13 | Short Circuit Brake Time at Stop
b3-01 | Speed Search Selection at Start
b3-02 | Speed Search Deactivation Current
b3-03 | Speed Search Deceleration Time
b3-05 | Speed Search Delay Time
b3-06 | Output Current 1 during Speed Search
b3-08 <11> | Current Control Gain during Speed Search (Speed Estimation Type)
b3-10 | Speed Search Detection Compensation Gain
b3-14 | Bi-Directional Speed Search Selection
b3-17 | Speed Search Restart Current Level
b3-18 | Speed Search Restart Detection Time
b3-19 | Number of Speed Search Restarts
b3-24 | Speed Search Method Selection
b3-25 | Speed Search Retry Interval Time
b3-29 <5> | Speed Search Induced Voltage Level
b4-01 | Timer Function On-Delay Time
b4-02 | Timer Function Off-Delay Time
Parameter catalogue PDF358 section1 — PDF page 358
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | b2-13 | Short Circuit Brake Time at Stop | Sets the Short-Circuit brake operation time at stop. Used to stop a motor rotating due to inertia. Disabled when set to 0.00 seconds. <2> | 0.00 to 25.50 | 0.50 s | − | − | A | 1BB | 129 |
| 2 | b3-01 | Speed Search Selection at Start | Enables/disables the Speed Search function at start. 0: Disabled - Speed Search is not automatically performed at start. 1: Enabled - Speed Search is automatically performed at start. | 0, 1 | 0 | A | A | A | 191 | 133 |
| 3 | b3-02 | Speed Search Deactivation Current | Sets the current level at which the speed is assumed to be detected and Speed Search is ended. Set as a percentage of the drive rated current. | 0 to 200 | 120 <3> | A | A | − | 192 | 133 |
| 4 | b3-03 | Speed Search Deceleration Time | Sets the time constant used to reduce the output frequency during Speed Search. Related to a change from max. output frequency to 0. | 0.1 to 10.0 | 2.0 s | A | A | − | 193 | 133 |
| 5 | b3-05 | Speed Search Delay Time | Delays the Speed Search operation after a momentary power loss to allow time for an external output contactor to close. | 0.0 to 100 | 0.2 s | A | A | A | 195 | 133 |
| 6 | b3-06 | Output Current 1 during Speed Search | Sets the current injected to the motor at the beginning of Estimation type Speed Search. Set as a factor of the motor rated current. | 0.0 to 2.0 | <4> | A | A | − | 196 | 134 |
| 7 | b3-08 <11> | Current Control Gain during Speed Search (Speed Estimation Type) | Sets the proportional gain for the current controller during Speed Search. There is normally no need to change this parameter from the default value. | 0.00 to 6.00 | <12> | A | A | A | 198 | 134 |
| 8 | b3-10 | Speed Search Detection Compensation Gain | Sets the gain which is applied to the speed detected by Speed Estimation Speed Search before the motor is reaccelerated. Increase this setting if ov occurs when performing Speed Search. | 1.00 to 1.20 | 1.05 | A | A | − | 19A | 134 |
| 9 | b3-14 | Bi-Directional Speed Search Selection | Selects if Speed Search detects the motor rotation direction during Speed Search. 0: Disabled–Frequency reference direction used 1: Enabled–Detected direction used | 0, 1 | 0 | A | A | − | 19E | 134 |
| 10 | b3-17 | Speed Search Restart Current Level | Sets the Speed Search restart current level as a percentage of the drive rated current. | 0 to 200 | 150% | A | A | − | 1F0 | 134 |
| 11 | b3-18 | Speed Search Restart Detection Time | Sets the time in seconds for Speed Search restart to be detected. | 0.00 to 1.00 | 0.10 s | A | A | − | 1F1 | 134 |
| 12 | b3-19 | Number of Speed Search Restarts | Sets the number of restarts possible for Speed Search restart operations. | 0 to 10 | 3 | A | A | − | 1F2 | 135 |
| 13 | b3-24 | Speed Search Method Selection | Sets the Speed Search detection mode. 0: Current Detection Type 1: Speed Estimation Type | 0, 1 | 0 | A | A | − | 1C0 | 135 |
| 14 | b3-25 | Speed Search Retry Interval Time | Sets the wait time before Speed Search restarts. | 0 to 30.0 | 0.5 s | A | A | A | 1C8 | 135 |
| 15 | b3-29 <5> | Speed Search Induced Voltage Level | Performs Speed Search when the motor induced voltage exceeds the set level. This setting rarely needs to be changed. If changes are necessary, try lowering this value in small increments. If set too low, then the drive will not perform Speed Search. | 0 to 10 | 10% | – | – | A | 77C | 135 |
| 16 | b4-01 | Timer Function On-Delay Time | Used in conjunction with a multi-function digital input (H1- oo = 18) and a multi-function digital output (H2-□□ = 12) programmed for the timer function. This sets the amount of time between digital input closure and digital output activation. | 0.0 to 300.0 | 0.0 s | A | A | A | 1A3 | 135 |
| 17 | b4-02 | Timer Function Off-Delay Time | Used in conjunction with a multi-function digital input (H1- oo = 18) and a multi-function digital output programmed for the timer function. This sets the amount of time the output remains activated after the digital input is opened. | 0.0 to 300.0 | 0.0 s | A | A | A | 1A4 | 135 |
Manual — PID parameters — page 359
Source reference: SIEP C71060618F, December 2016, physical PDF page 359. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
B.2 Parameter Table
B
List Parameter
b5-01 | PID Function Setting
b5-02 <6> | Proportional Gain Setting (P)
b5-03 <6> | Integral Time Setting (I)
b5-04 <6> | Integral Limit Setting
b5-05 <6> | Derivative Time (D)
b5-06 <6> | PID Output Limit
b5-07 <6> | PID Offset Adjustment
b5-08 <6> | PID Primary Delay Time Constant
b5-09 | PID Output Level Selection
b5-10 | PID Output Gain Setting
b5-11 | PID Output Reverse Selection
b5-12 | PID Feedback Reference Missing Detection Selection
b5-13 | PID Feedback Loss Detection Level
b5-14 | PID Feedback Loss Detection Time
b5-15 | PID Sleep Function Start Level
b5-16 | PID Sleep Delay Time
b5-17 | PID Accel/Decel Time
b5-18 | PID Setpoint Selection
Parameter catalogue PDF359 section1 — PDF page 359
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | b5-01 | PID Function Setting | Sets the PID control mode. 0: Disabled 1: Enable (PID output = freq. ref., PID input is D-controlled) 2: (PID output = freq. ref., PID feedback is D-controlled) 3: Enable (PID output added to freq. ref., PID input is D- controlled) 4: Enable (PID output added to freq. ref., PID feedback is D- controlled) | 0 to 4 | 0 | A | A | A | 1A5 | 139 |
| 2 | b5-02 <6> | Proportional Gain Setting (P) | Sets the proportional gain of the PID controller. A setting of 0.00 disables P control. | 0.00 to 25.00 | 1.00 | A | A | A | 1A6 | 139 |
| 3 | b5-03 <6> | Integral Time Setting (I) | Sets the integral time for the PID controller. A setting of 0.0 s disables integral control. | 0.0 to 360.0 | 1.0 s | A | A | A | 1A7 | 139 |
| 4 | b5-04 <6> | Integral Limit Setting | Sets the maximum output possible from the integrator. | 0.0 to 100.0 | 100.0 % | A | A | A | 1A8 | 139 |
| 5 | b5-05 <6> | Derivative Time (D) | Sets D control derivative time. A setting of 0.00 s disables derivative control. | 0.00 to 10.00 | 0.00 s | A | A | A | 1A9 | 140 |
| 6 | b5-06 <6> | PID Output Limit | Sets the maximum output possible from the entire PID controller. | 0.0 to 100.0 | 100.0 % | A | A | A | 1AA | 140 |
| 7 | b5-07 <6> | PID Offset Adjustment | Applies an offset to the PID controller output. | -100.0 to +100.0 | 0.0% | A | A | A | 1AB | 140 |
| 8 | b5-08 <6> | PID Primary Delay Time Constant | Sets the amount of time for the filter on the output of the PID controller. | 0.00 to 10.00 | 0.00 s | A | A | A | 1AC | 140 |
| 9 | b5-09 | PID Output Level Selection | Sets the PID controller output direction. 0: Normal Output (direct acting) 1: Reverse Output (reverse acting) | 0, 1 | 0 | A | A | A | 1AD | 140 |
| 10 | b5-10 | PID Output Gain Setting | Sets the gain applied to the PID output. | 0.00 to 25.00 | 1.00 | A | A | A | 1AE | 140 |
| 11 | b5-11 | PID Output Reverse Selection | Sets the drive operation with negative PID output. 0: Negative PID output triggers zero limit and drive stops. 1: Rotation direction reverses with negative PID output. When using setting 1 make sure, reverse operation is permitted by parameter b1-04. | 0, 1 | 0 | A | A | A | 1AF | 140 |
| 12 | b5-12 | PID Feedback Reference Missing Detection Selection | Configures the PID feedback loss detection. With all setting a digital output programmed for H2-01/02/03 = 3E/3F (PID feedback low/PID feedback high) is operated when the detection condition becomes true. 0: Digital output only. 1: Feedback loss detected when PID enabled. Alarm output, operation is continued without triggering a fault contact. 2: Feedback loss detected when PID enabled. Fault output, operation is stopped and a fault contact is triggered. 3: Feedback loss detection even when PID is disabled by digital input. No alarm/fault output. 4: PID Feedback error detection even when PID is disabled by digital input. An alarm is triggered and the drive continues to run. 5: PID Feedback error detection even when PID is disabled by digital input. Fault is triggered and output is shut off. | 0 to 5 | 0 | A | A | A | 1B0 | 141 |
| 13 | b5-13 | PID Feedback Loss Detection Level | Sets the PID feedback loss detection level. | 0 to 100 | 0% | A | A | A | 1B1 | 142 |
| 14 | b5-14 | PID Feedback Loss Detection Time | Sets the PID feedback loss detection delay time in terms of seconds. | 0.0 to 25.5 | 1.0 s | A | A | A | 1B2 | 142 |
| 15 | b5-15 | PID Sleep Function Start Level | Sets the sleep function start frequency. Note: Also enabled when PID is not active. | 0.0 to 400.0 | 0.0 Hz | A | A | A | 1B3 | 142 |
| 16 | b5-16 | PID Sleep Delay Time | Sets the sleep function delay time. | 0.0 to 25.5 | 0.0 s | A | A | A | 1B4 | 143 |
| 17 | b5-17 | PID Accel/Decel Time | Applies an accel/decel time to the PID setpoint. | 0 to 255 | 0 s | A | A | A | 1B5 | 143 |
| 18 | b5-18 | PID Setpoint Selection | Selects b5-19 as PID setpoint value. 0: Disabled 1: Enabled, b5-19 becomes PID target | 0, 1 | 0 | A | A | A | 1DC | 143 |
Manual — PID dwell and energy savings — page 360
Source reference: SIEP C71060618F, December 2016, physical PDF page 360. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
b6: Dwell Function Use b6 parameters to configure dwell function operation.
b8: Energy Saving Use b8 parameters to configure the energy saving/conservation drive function.
B.2 Parameter Table
b5-19 | PID Setpoint Value
b5-20 | PID Setpoint Scaling
b5-34 <6> | PID Output Lower Limit
b5-35 <6> | PID Input Limit
b5-36 | PID Feedback High Detection Level
b5-37 | PID Feedback High Level Detection Time
b5-38 | PID Setpoint / User Display
b5-39 | PID Setpoint Display Digits
b5-40 <8> | Frequency Reference Monitor Content during PID
b5-47 <5> | Reverse Operation Selection 2 by PID Output
b6-01 | Dwell Reference at Start
b6-02 | Dwell Time at Start
b6-03 | Dwell Frequency at Stop
b6-04 | Dwell Time at Stop
b8-01 | Energy Saving Control Selection
b8-02 <6> | Energy Saving Gain
b8-03 <6> | Energy Saving Control Filter Time Constant
b8-04 | Energy Saving Coefficient Value
Parameter catalogue PDF360 section1 — PDF page 360
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | b5-19 | PID Setpoint Value | Sets the PID target value when b5-18 = 1. | 0.00 to 100.00 | 0.00 % | A | A | A | 1DD | 143 |
| 2 | b5-20 | PID Setpoint Scaling | Sets the units for setting/display b5-19, and for parameter monitors U5-01 (PID Feedback) and U5-04 (PID Setpoint). 0: 0.01Hz units 1: 0.01% units (100% = max output frequency) 2: r/min (number of motor poles must be set up) 3: User-set (set to b5-38 and b5-39) | 0 to 3 | 1 | A | A | A | 1E2 | 143 |
| 3 | b5-34 <6> | PID Output Lower Limit | Sets the minimum output possible from the PID controller. | -100.0 to +100.0 | 0.00 % | A | A | A | 19F | 144 |
| 4 | b5-35 <6> | PID Input Limit | Limits the PID control input (deviation signal). Acts as a bipolar limit. | 0.0 to 1000.0 | 1000. 0% | A | A | A | 1A0 | 144 |
| 5 | b5-36 | PID Feedback High Detection Level | Sets the PID feedback high detection level. | 0 to 100 | 100% | A | A | A | 1A1 | 142 |
| 6 | b5-37 | PID Feedback High Level Detection Time | Sets the PID feedback high level detection delay time. | 0.0 to 25.5 | 1.0 s | A | A | A | 1A2 | 142 |
| 7 | b5-38 | PID Setpoint / User Display | Sets the display value of U5-01 and U5-04 when the maximum frequency is output. Changeable only if b5-20 = 3. 0 to 60000: User-Set Display if b5-20 = 3 | 1 to 60000 | <7> | A | A | A | 1FE | 144 |
| 8 | b5-39 | PID Setpoint Display Digits | Sets the number of digits of U5-01 and U5-04. Changeable only if b5-20 = 3. 0: No decimal places 1: One decimal places 2: Two decimal places 3: Three decimal places | 0 to 3 | <7> | A | A | A | 1FF | 144 |
| 9 | b5-40 <8> | Frequency Reference Monitor Content during PID | 0: Display the frequency reference (U1-01) after PID compensation has been added. 1: Display the frequency reference (U1-01) before PID compensation has been added. | 0, 1 | 0 | A | A | A | 17F | 144 |
| 10 | b5-47 <5> | Reverse Operation Selection 2 by PID Output | Reverses operation selection when b5-01 = 3 or 4 0: Zero limit when PID output is a negative value 1: Reverse operation when PID output is a negative value (Zero limit if the reverse operation is prohibited by b1-04) | 0, 1 | 1 | A | A | A | 17D | 144 |
| 11 | b6-01 | Dwell Reference at Start | The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. | 0.0 to 400.0 | 0.0 Hz | A | A | A | 1B6 | 145 |
| 12 | b6-02 | Dwell Time at Start | The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. | 0.0 to 10.0 | 0.0 s | A | A | A | 1B7 | 145 |
| 13 | b6-03 | Dwell Frequency at Stop | The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. | 0.0 to 400.0 | 0.0 Hz | A | A | A | 1B8 | 145 |
| 14 | b6-04 | Dwell Time at Stop | The Dwell function is used to temporarily hold the frequency when driving a motor with a heavy load. Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain that frequency at start. Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain that frequency at stop. Diagram labels: Run command ON/OFF, Output Frequency, Time, b6-01 and b6-03 frequency holds, b6-02 and b6-04 dwell times. Exact curve geometry original-only. | 0.0 to 10.0 | 0.0 s | A | A | A | 1B9 | 145 |
| 15 | b8-01 | Energy Saving Control Selection | Selects the Energy Savings function. 0: Disabled 1: Enabled | 0, 1 | 0 | A | A | − | 1CC | 145 |
| 16 | b8-02 <6> | Energy Saving Gain | Sets energy savings control gain when in Open Loop Vector Control. | 0.0 to 10.0 | 0.7 | − | A | − | 1CD | 145 |
| 17 | b8-03 <6> | Energy Saving Control Filter Time Constant | Sets energy saving control filter time constant when in Open Loop Vector Control. | 0.00 to 10.00 | 0.50 <4> | − | A | − | 1CE | 145 |
| 18 | b8-04 | Energy Saving Coefficient Value | Sets the Energy Saving coefficient and is used to fine adjustments in V/f Control. | 0.0 to 655.00 | <9> <10> | A | − | − | 1CF | 146 |
Manual — Energy notes and acceleration parameters — page 361
Source reference: SIEP C71060618F, December 2016, physical PDF page 361. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control. <2> A coasting motor may require a braking resistor circuit to bring the motor to a stop in the required time. <3> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <4> Default setting value is dependent on parameter o2-04, Drive Model Selection. <5> Available in drive software versions PRG: 1020 and later. <6> Parameter can be changed during Run. <7> Default setting is dependent on parameter b5-20, PID Setpoint Scaling. <8> Available in drive software versions PRG: 1014 and later. <9> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. <10> Parameter value is changed if E2-11 is manually changed or changed by Auto-Tuning. <11> Available in drive software versions PRG: 1022 and later. <12> Default setting is determined by A1-02, Control Method Selection
u C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, slip and torque compensation functions and carrier frequency selections.
C1: Acceleration and Deceleration Times Use C1 parameters to configure motor acceleration and deceleration.
B.2 Parameter Table
B
List Parameter
b8-05 | Power Detection Filter Time
b8-06 | Search Operation Voltage Limit
C1-01 <1> | Acceleration Time 1
C1-02 <1> | Deceleration Time 1
C1-03 <1> | Acceleration Time 2
C1-04 <1> | Deceleration Time 2
C1-05 <1> | Acceleration Time 3 (Motor 2 Accel Time 1)
C1-06 <1> | Deceleration Time 3 (Motor 2 Decel Time 1)
C1-07 <1> | Acceleration Time 4 (Motor 2 Accel Time 2)
C1-08 <1> | Deceleration Time 4 (Motor 2 Decel Time 2)
C1-09 | Fast-Stop Time
C1-10 | Accel/Decel Time Setting Units
Parameter catalogue PDF361 section1 — PDF page 361
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | b8-05 | Power Detection Filter Time | Sets a filter time for the Power Detection used by Energy Savings in V/f Control. | 0 to 2000 | 20 ms | A | − | − | 1D0 | 146 |
| 2 | b8-06 | Search Operation Voltage Limit | Sets the limit for the voltage search operation performed by Energy Savings in V/f Control. Set as a percentage of the motor base voltage. Disabled when set to 0%. | 0 to 100 | 0% | A | − | − | 1D1 | 146 |
Parameter catalogue PDF361 section2 — PDF page 361
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | C1-01 <1> | Acceleration Time 1 | Sets the time to accelerate from 0 to maximum frequency. | 0.0 to 6000.0 <2> | 10.0 s | S | S | S | 200 | 147 |
| 2 | C1-02 <1> | Deceleration Time 1 | Sets the time to decelerate from maximum frequency to 0. | 0.0 to 6000.0 <2> | 10.0 s | S | S | S | 201 | 147 |
| 3 | C1-03 <1> | Acceleration Time 2 | Sets the time to accelerate from 0 to maximum frequency when Accel/Decel times 2 are selected by a digital input. | 0.0 to 6000.0 <2> | 10.0 s | A | A | A | 202 | 147 |
| 4 | C1-04 <1> | Deceleration Time 2 | Sets the time to decelerate from maximum frequency to 0 when Accel/Decel times 2 are selected by a digital input. | 0.0 to 6000.0 <2> | 10.0 s | A | A | A | 203 | 147 |
| 5 | C1-05 <1> | Acceleration Time 3 (Motor 2 Accel Time 1) | Sets the time to accelerate from 0 to maximum frequency when Accel/Decel times 3 are selected by a digital input. | 0.0 to 6000.0 <2> | 10.0 s | A | A | A | 204 | 147 |
| 6 | C1-06 <1> | Deceleration Time 3 (Motor 2 Decel Time 1) | Sets the time to decelerate from maximum frequency to 0 when Accel/Decel times 3 are selected by a digital input. | 0.0 to 6000.0 <2> | 10.0 s | A | A | A | 205 | 147 |
| 7 | C1-07 <1> | Acceleration Time 4 (Motor 2 Accel Time 2) | Sets the time to accelerate from 0 to maximum frequency when Accel/Decel times 4 are selected by a digital input. | 0.0 to 6000.0 <2> | 10.0 s | A | A | A | 206 | 147 |
| 8 | C1-08 <1> | Deceleration Time 4 (Motor 2 Decel Time 2) | Sets the time to decelerate from maximum frequency to 0 when Accel/Decel times 4 are selected by a digital input. | 0.0 to 6000.0 <2> | 10.0 s | A | A | A | 207 | 147 |
| 9 | C1-09 | Fast-Stop Time | Sets the time to decelerate from maximum frequency to 0 for the multi-function input fast-stop function. Note: This parameter is also used by selecting “Fast-Stop” as a Stop Method when a fault is detected. | 0.0 to 6000.0 <2> | 10.0 s | A | A | A | 208 | 148 |
| 10 | C1-10 | Accel/Decel Time Setting Units | Sets the resolution of C1-01 to C1-09. 0: 0.01 s (0.00 to 600.00 s) 1: 0.1 s (0.0 to 6000.0 s) | 0, 1 | 1 | A | A | A | 209 | 148 |
Manual — S-curve and slip compensation — page 362
Source reference: SIEP C71060618F, December 2016, physical PDF page 362. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
C2: S-Curve Characteristics Use C2 parameters to configure S-curve operation.
C3: Slip Compensation Use C3 parameters to configure the slip compensation function.
C4: Torque Compensation Use C4 parameters to configure Torque Compensation function.
B.2 Parameter Table
C1-11 | Accel/Decel Time Switching Frequency
C1-14 <3> | Accel/Decel Rate Frequency
C2-01 | S-Curve Characteristic at Accel Start
C2-02 | S-Curve Accel End Characteristic at
C2-03 | S-Curve Characteristic at Decel Start
C2-04 | S-Curve Characteristic at Decel End
C3-01 <1> | Slip Compensation Gain
C3-02 | Slip Compensation Primary Delay Time
C3-03 | Slip Compensation Limit
C3-04 | Slip Compensation Selection during Regeneration
C3-05 | Output Voltage Limit Operation Selection
C3-18 <10> | Output Voltage Limit Level
Parameter catalogue PDF362 section1 — PDF page 362
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | C1-11 | Accel/Decel Time Switching Frequency | Sets the frequency for automatic acceleration/deceleration switching. Below set frequency: Accel/Decel Time 4 Above set frequency: Accel/Decel Time 1 The multi-function input “Accel/Decel Time 1” or “Accel/ Decel Time 2” take priority. | 0.0 to 400.0 Hz | 0.0 Hz | A | A | A | 20A | 149 |
| 2 | C1-14 <3> | Accel/Decel Rate Frequency | Sets the base frequency used to calculate acceleration and deceleration times. When set to 0.0 Hz, the drive calculates the time required to accelerate from 0 Hz to E1-04, and decelerate from E1-04 down to 0 Hz (conventional setting). When set to any other value above 0.0 Hz, the drive calculates the time required to accelerate from 0 Hz to C1-14, and to decelerate from C1-14 down to 0 Hz. | 0.0 to 400.0 Hz | 0.0 Hz | A | A | A | 264 | 149 |
| 3 | C2-01 | S-Curve Characteristic at Accel Start | The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. | 0.00 to 10.00 | 0.20 s <4> | A | A | A | 20B | 150 |
| 4 | C2-02 | S-Curve Characteristic at Accel End | The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. | 0.00 to 10.0 | 0.20 s | A | A | A | 20C | 150 |
| 5 | C2-03 | S-Curve Characteristic at Decel Start | The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. | 0.00 to 10.0 | 0.20 s | A | A | A | 20D | 150 |
| 6 | C2-04 | S-Curve Characteristic at Decel End | The S-curve can be controlled in the four points shown below. Diagram labels: Run command ON/OFF; Output frequency; Time; C2-01 accel start,C2-02 accel end,C2-03 decel start,C2-04 decel end. S-curve is used to further soften the starting and stopping ramp. The longer the S-curve time, the softer the starting and stopping ramp. Exact curve geometry original-only. | 0.00 to 10.0 | 0.00 s | A | A | A | 20E | 150 |
| 7 | C3-01 <1> | Slip Compensation Gain | Sets the slip compensation gain. Decides for what amount the output frequency is boosted in order to compensate the slip. Note: Adjustment is not normally required. | 0.0 to 2.5 | 0.0 <4> | A | A | − | 20F | 151 |
| 8 | C3-02 | Slip Compensation Primary Delay Time | Adjusts the slip compensation function delay time. Decrease the setting when the slip compensation response is too slow, increase it when the speed is not stable. Disabled when Simple V/f Control with PG (H6-01 = 3) is used. | 0 to 10000 | 2000 ms <4> | A | A | − | 210 | 151 |
| 9 | C3-03 | Slip Compensation Limit | Sets the slip compensation upper limit. Set as a percentage of motor rated slip (E2-02). Disabled when Simple V/f Control with PG (H6-01 = 3) is used. | 0 to 250 | 200% | A | A | − | 211 | 151 |
| 10 | C3-04 | Slip Compensation Selection during Regeneration | Selects slip compensation during regenerative operation. 0: Disabled 1: Enabled Using the Slip Compensation function during regeneration may require a braking option to handle momentary increasing regenerative energy. | 0, 1 | 0 | A | A | − | 212 | 152 |
| 11 | C3-05 | Output Voltage Limit Operation Selection | Selects if the motor magnetic flux is reduced during output voltage saturation. 0: Disabled 1: Enabled | 0, 1 | 0 <4> | − | A | − | 213 | 152 |
| 12 | C3-18 <10> | Output Voltage Limit Level | Sets the maximum percentage of output voltage reduction when C3-05 is enabled. | 70.0 to 100.0 | 90.0% | − | A | − | 263 | 152 |
Manual — Torque speed and carrier controls — page 363
Source reference: SIEP C71060618F, December 2016, physical PDF page 363. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
C5: Speed Control (ASR) Use C5 parameters to configure the Automatic Speed Regulator (ASR). C5 parameters are available only when using V/f Control with Simple PG Feedback (H6-01 = 3).
C6: Carrier Frequency Use C6 parameters to configure the carrier frequency drive settings.
B.2 Parameter Table
B
List Parameter
C4-01 <5> | Torque Compensation Gain
C4-02 | Torque Compensation Primary Delay Time
C4-03 | Torque Compensation at Forward Start
C4-04 | Torque Compensation at Reverse Start
C4-05 | Torque Compensation Time Constant
C4-06 | Torque Compensation Primary Delay Time 2
C5-01 <1> | ASR Proportional Gain 1
C5-02 <1> | ASR Integral Time 1
C5-03 <1> | ASR Proportional Gain 2
C5-04 <1> | ASR Integral Time 2
C5-05 <1> | ASR Limit
C6-01 | Drive Duty Selection
C6-02 | Carrier Frequency Selection
Parameter catalogue PDF363 section1 — PDF page 363
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | C4-01 <5> | Torque Compensation Gain | V/f Control: Sets the gain for the automatic torque (voltage) boost function and helps to produce better starting torque. Increase this setting when using a long motor cable or when the motor is significantly smaller than the drive capacity. Decrease this setting when motor oscillation occurs. Set the value so that the current at low speed does not exceeds the drives rated current. Open Loop Vector: Sets the torque compensation function gain. Normally no change is required. | 0.00 to 2.50 | 1.00 <4> | A | A | A | 215 | 152 |
| 2 | C4-02 | Torque Compensation Primary Delay Time | Sets the torque compensation filter time. Increase this setting when motor oscillation occurs. Reduce the setting if there is not enough response from the motor. | 0 to 60000 | 200 ms <6> | A | A | A | 216 | 153 |
| 3 | C4-03 | Torque Compensation at Forward Start | Sets torque compensation at forward start as a percentage of motor torque. | 0.0 to 200.0 | 0.0% | − | A | − | 217 | 153 |
| 4 | C4-04 | Torque Compensation at Reverse Start | Sets torque compensation at reverse start as a percentage of motor torque. | -200.0 to 0.0 | 0.0% | − | A | − | 218 | 153 |
| 5 | C4-05 | Torque Compensation Time Constant | Sets the time constant for torque compensation at forward start and reverse start (C4-03 and C4-04). The filter is disabled if the time is set to 4 ms or less. | 0 to 200 | 10 ms | – | A | – | 219 | 153 |
| 6 | C4-06 | Torque Compensation Primary Delay Time 2 | Sets the torque compensation time 2. When an ov fault occurs with sudden load changes or at the and of an acceleration, increase the setting. Note: Adjustment is not normally required. If adjusted then AFR time 2 (n2-03) should be adjusted too. | 0 to 10000 | 150 ms | – | A | – | 21AH | 153 |
| 7 | C5-01 <1> | ASR Proportional Gain 1 | Sets the proportional gain of the speed control loop (ASR). | 0.00 to 300.00 | 0.20 | A | – | – | 21B | 155 |
| 8 | C5-02 <1> | ASR Integral Time 1 | Sets the integral time of the speed control loop (ASR). | 0.000 to 10.000 | 0.200 | A | – | – | 21C | 155 |
| 9 | C5-03 <1> | ASR Proportional Gain 2 | Sets the speed control gain 2 of the speed control loop (ASR). | 0.00 to 300.00 | 0.02 | A | − | − | 21D | 155 |
| 10 | C5-04 <1> | ASR Integral Time 2 | Sets the integral time 2 of the speed control loop (ASR). | 0.000 to 10.000 | 0.050 s | A | – | – | 21E | 155 |
| 11 | C5-05 <1> | ASR Limit | Sets the upper limit for the speed control loop (ASR) as a percentage of the maximum output frequency (E1-04). | 0.0 to 20.0 | 5.0% | A | – | – | 21F | 155 |
| 12 | C6-01 | Drive Duty Selection | Selects the load rating for the drive. 0: Heavy Duty (HD) for constant torque applications. 1: Normal Duty (ND) for variable torque applications. This setting affects the Rated output current and overload tolerance of the drive. | 0, 1 | 1 | S | S | S | 223 | 155 |
| 13 | C6-02 | Carrier Frequency Selection | Selects the carrier frequency 1 : 2.0 kHz 2 : 5.0 kHz 3 : 8.0 kHz 4 : 10.0 kHz 5 : 12.5 kHz 6 : 15.0 kHz 7 : Swing PWM1 (Audible sound 1) 8 : Swing PWM2 (Audible sound 2) 9 : Swing PWM3 (Audible sound 3) A : Swing PWM4 (Audible sound 4) <3> B: Leakage Current Rejection PWM C to E: No setting possible F : User defined (determined by C6-03 through C6-05) | <7> | <8> | S | S | S | 224 | 156 |
Manual — Carrier conditions and frequency references — page 364
Source reference: SIEP C71060618F, December 2016, physical PDF page 364. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
<1> Parameter can be changed during run. <2> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range becomes 0.00 to 600.00 seconds. <3> Available in drive software versions PRG: 1020 and later. <4> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <5> Parameter cannot be changed during run when parameter A1-02 = 5-PM OLV Control. <6> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control. <7> Setting range is determined by the drive software version. PRG: 1020 and later: 1 to B; F PRG: 1018 and earlier: 1 to A; F <8> Default setting value is dependent on parameters o2-04, Drive Model Selection, A1-02, Control Method Selection and C6-01, Drive Duty Selection. <9> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection. <10> Available in drive software versions PRG: 1024 and later.
u d: References
Reference parameters are used to set the various frequency reference values during operation.
d1: Frequency Reference Use d1 parameters to configure the drive frequency reference.
B.2 Parameter Table
C6-03 | Carrier Frequency Upper Limit
C6-04 | Carrier Frequency Lower Limit
C6-05 | Carrier Frequency Proportional Gain
d1-01 <1> | Frequency Reference 1
d1-02 <1> | Frequency Reference 2
d1-03 <1> | Frequency Reference 3
d1-04 <1> | Frequency Reference 4
d1-05 <1> | Frequency Reference 5
d1-06 <1> | Frequency Reference 6
Parameter catalogue PDF364 section1 — PDF page 364
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | C6-03 | Carrier Frequency Upper Limit | Note: Set C6-02 to F before setting C6-03. Open Loop Vector: C6-03 defines the fixed carrier frequency if C6-02 = F. V/f Control: C6-03 and C6-04 set upper and lower limits for the carrier frequency. Diagram labels: carrier frequency,C6-03,C6-04; output frequency,E1-04 max output frequency; slope label output frequency ×(C6-05)×K. The coefficient K depends on C6-03: C6-03 ≥ 10.0 kHz: K = 3 10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2 5.0 kHz > C6-03: K = 1 When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value). Exact graph geometry original-only. | 1.0 to 15.0 | <9> | A | A | A | 225 | 157 |
| 2 | C6-04 | Carrier Frequency Lower Limit | Note: Set C6-02 to F before setting C6-03. Open Loop Vector: C6-03 defines the fixed carrier frequency if C6-02 = F. V/f Control: C6-03 and C6-04 set upper and lower limits for the carrier frequency. Diagram labels: carrier frequency,C6-03,C6-04; output frequency,E1-04 max output frequency; slope label output frequency ×(C6-05)×K. The coefficient K depends on C6-03: C6-03 ≥ 10.0 kHz: K = 3 10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2 5.0 kHz > C6-03: K = 1 When C6-05 ≤ 6, C6-04 is disabled (makes the carrier frequency C6-03 value). Exact graph geometry original-only. | 1.0 to 15.0 | <9> | A | - | - | 226 | 157 |
| 3 | C6-05 | Carrier Frequency Proportional Gain | Sets the relationship of output frequency to carrier frequency when C6-02 = F. | 00 to 99 | <9> | A | - | - | 227 | 157 |
Parameter catalogue PDF364 section2 — PDF page 364
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | d1-01 <1> | Frequency Reference 1 | Frequency reference. Refer to b1-01: Frequency Reference Selection 1 on page 121 for instructions to use d1-01 as the main frequency reference. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | S | S | S | 280 | 160 |
| 2 | d1-02 <1> | Frequency Reference 2 | Frequency reference when digital input "Multi-Step Speed Reference 1" (H1-□□ = 3) is on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | S | S | S | 281 | 160 |
| 3 | d1-03 <1> | Frequency Reference 3 | Frequency reference when digital input "Multi-Step Speed Reference 2” (H1-□□ = 4) is on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | S | S | S | 282 | 160 |
| 4 | d1-04 <1> | Frequency Reference 4 | Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2" (H1-□□ = 3 and 4) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | S | S | S | 283 | 160 |
| 5 | d1-05 <1> | Frequency Reference 5 | Frequency reference when digital input "Multi-Step Speed Reference 3" (H1-□□ = 5) is on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 284 | 160 |
| 6 | d1-06 <1> | Frequency Reference 6 | Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3 " (H1-□□ = 3 and 5) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 285 | 160 |
Manual — Frequency limits and jump controls — page 365
Source reference: SIEP C71060618F, December 2016, physical PDF page 365. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
d2: Frequency Upper and Lower Limits Use d2 parameters to configure the frequency reference limits.
d3: Jump Frequency Use d3 parameters to configure the drive Jump Frequency settings.
d4: Frequency Reference Hold Use d4 parameters to configure the drive frequency reference hold function.
B.2 Parameter Table
B
List Parameter
d1-07 <1> | Frequency Reference 7
d1-08 <1> | Frequency Reference 8
d1-09 <1> | Frequency Reference 9
d1-10 <1> | Frequency Reference 10
d1-11 <1> | Frequency Reference 11
d1-12 <1> | Frequency Reference 12
d1-13 <1> | Frequency Reference 13
d1-14 <1> | Frequency Reference 14
d1-15 <1> | Frequency Reference 15
d1-16 <1> | Frequency Reference 16
d1-17 <1> | Jog Frequency Reference
d2-01 | Frequency Reference Upper Limit
d2-02 | Frequency Reference Lower Limit
d2-03 | Master Speed Reference Lower Limit
d3-01 | Jump Frequency 1
d3-02 | Jump Frequency 2
d3-03 | Jump Frequency 3
d3-04 | Jump Frequency Width
Parameter catalogue PDF365 section1 — PDF page 365
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | d1-07 <1> | Frequency Reference 7 | Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3" (H1-□□ = 4 and 5) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 286 | 160 |
| 2 | d1-08 <1> | Frequency Reference 8 | Frequency reference when multi-function input "Multi-Step speed reference 1, 2, 3" (H1-□□ = 3, 4, 5) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 287 | 160 |
| 3 | d1-09 <1> | Frequency Reference 9 | Frequency reference when multi-function input "Multi-Step Speed Reference 4" (H1-□□= 32) is on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 288 | 160 |
| 4 | d1-10 <1> | Frequency Reference 10 | Frequency reference when digital input "Multi-Step Speed Reference 1, 4" (H1-□□ = 3 and 32) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 28B | 160 |
| 5 | d1-11 <1> | Frequency Reference 11 | Frequency reference when digital inputs "Multi-Step Speed Reference 2, 4" (H1-□□ = 4 and 32) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 28C | 160 |
| 6 | d1-12 <1> | Frequency Reference 12 | Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2, 4" (H1-□□ = 3, 4, 32) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 28D | 160 |
| 7 | d1-13 <1> | Frequency Reference 13 | Frequency reference when digital inputs "Multi-Step Speed Reference 3, 4" (H1-□□ = 5 and 32) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 28E | 160 |
| 8 | d1-14 <1> | Frequency Reference 14 | Frequency reference when digital inputs "Multi-Step Speed Reference 1, 3, 4" (H1-□□ = 3, 5, 32) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 28F | 160 |
| 9 | d1-15 <1> | Frequency Reference 15 | Frequency reference when digital inputs "Multi-Step Speed Reference 2, 3, 4" (H1-□□ = 4, 5, 32) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 290 | 160 |
| 10 | d1-16 <1> | Frequency Reference 16 | Frequency reference when digital inputs "Multi-Step Speed Reference 1, 2, 3, 4" (H1-□□ = 3, 4, 5, 32) are on. | 0.00 to 400.00 Hz <2> <3> | 0.00 Hz | A | A | A | 291 | 160 |
| 11 | d1-17 <1> | Jog Frequency Reference | Frequency reference when digital inputs "Jog Frequency Reference", "Forward Jog", or "Reverse Jog." are on. "Jog Frequency Reference" has priority over "Multi-Step Speed Reference 1 to 16”. | 0.00 to 400.00 <2> <3> Hz | 6.00 Hz | S | S | S | 292 | 160 |
| 12 | d2-01 | Frequency Reference Upper Limit | Sets the frequency reference upper limit as a percentage of maximum output frequency (E1-04). Output speed is limited to this value even if the frequency reference is higher. This limit applies to all frequency reference sources. | 0.0 to 110.0 | 100.0 % | A | A | A | 289 | 161 |
| 13 | d2-02 | Frequency Reference Lower Limit | Sets the frequency reference lower limit as a percentage of maximum output frequency (E1-04). Output speed is limited to this value even if the frequency reference is lower. This limit applies to all frequency reference sources. | 0.0 to 110.0 | 0.0% | A | A | A | 28A | 161 |
| 14 | d2-03 | Master Speed Reference Lower Limit | Sets the minimum frequency reference lower limit if the frequency reference is input using an analog input. Set as a percentage of maximum output frequency (E1-04). The higher of both values d2-02 and d2-03 will be the lower limit. | 0.0 to 110.0 | 0.0% | A | A | A | 293 | 162 |
| 15 | d3-01 | Jump Frequency 1 | d3-01 to d3-04 allow programming of three prohibited frequency reference points for eliminating problems with resonant vibration of the motor / machine. This feature does not eliminate the selected frequency values, but accelerates and decelerates the motor through the prohibited bandwidth. The parameters must be according to the rule d3-01 ≥ d3-02 ≥ d3-03. | 0.0 to 400.0 | 0.0 Hz | A | A | A | 294 | 162 |
| 16 | d3-02 | Jump Frequency 2 | d3-01 to d3-04 allow programming of three prohibited frequency reference points for eliminating problems with resonant vibration of the motor / machine. This feature does not eliminate the selected frequency values, but accelerates and decelerates the motor through the prohibited bandwidth. The parameters must be according to the rule d3-01 ≥ d3-02 ≥ d3-03. | 0.0 to 400.0 | 0.0 Hz | A | A | A | 295 | 162 |
| 17 | d3-03 | Jump Frequency 3 | d3-01 to d3-04 allow programming of three prohibited frequency reference points for eliminating problems with resonant vibration of the motor / machine. This feature does not eliminate the selected frequency values, but accelerates and decelerates the motor through the prohibited bandwidth. The parameters must be according to the rule d3-01 ≥ d3-02 ≥ d3-03. | 0.0 to 400.0 | 0.0 Hz | A | A | A | 296 | 162 |
| 18 | d3-04 | Jump Frequency Width | This parameter sets the dead-band width around each selected prohibited frequency reference point. The bandwidth becomes the designated Jump frequency, plus or minus d3-04. | 0.0 to 20.0 | 1.0 Hz | A | A | A | 297 | 162 |
Manual — Frequency hold and offset — page 366
Source reference: SIEP C71060618F, December 2016, physical PDF page 366. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
d7: Offset Frequency Use d7 parameters to set the offset frequency.
<1> Parameter can be changed during Run. <2> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection. <3> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit. <4> Default setting is determined by the drive software version. PRG: 1016 and later: 100.00% PRG: 1015 and earlier: 0.00 %
B.2 Parameter Table
d4-01 | Frequency Reference Hold Function Selection
d4-03 <1> | Frequency Reference Bias Step (Up/Down 2)
d4-04 <1> | Frequency Reference Bias Accel/Decel (Up/Down 2)
d4-05 <1> | Frequency Reference Bias Operation Mode Selection (Up/Down 2)
d4-06 | Frequency Reference Bias (Up/Down 2)
d4-07 <1> | Analog Frequency Reference Fluctuation Limit (Up/Down 2)
d4-08 <1> | Frequency Upper Limit Reference (Up/Down Bias 2)
d4-09 <1> | Frequency Reference Bias Lower Limit (Up/Down 2)
d4-10 | Up/Down Frequency Reference Limit Selection
d7-01 <1> | Offset Frequency 1
d7-02 <1> | Offset Frequency 2
d7-03 <1> | Offset Frequency 3
Parameter catalogue PDF366 section1 — PDF page 366
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | d4-01 | Frequency Reference Hold Function Selection | Determines if the frequency reference or frequency reference bias is saved when the Run command is removed or the power goes off. 0: Disabled 1: Enabled This parameter is effective when the multi-function inputs “Accel/Decel Ramp Hold”, “Up/Down” or “Up/Down 2” commands are selected (H1-□□ = A or 10/11 or 75/76). | 0, 1 | 0 | A | A | A | 298 | 162 |
| 2 | d4-03 <1> | Frequency Reference Bias Step (Up/Down 2) | Sets the bias added to the frequency reference when the Up/ Down 2 digital inputs are set. When set to 0.00 Hz, the bias value is increased or decreased according to d4-04. When greater than 0.0 Hz, the bias value d4-03 is added or subtracted to/from the frequency reference. The acceleration or deceleration rate is ultimately determined by d4-04. | 0.00 to 99.99 Hz | 0.00 Hz | A | A | A | 2AA | 165 |
| 3 | d4-04 <1> | Frequency Reference Bias Accel/Decel (Up/Down 2) | Selects how the bias or frequency reference is increased when using the Up/Down 2 function. 0: Use selected accel/decel time. 1: Use Accel/Decel Time 4 (C1-07 and C1-08). | 0, 1 | 0 | A | A | A | 2AB | 165 |
| 4 | d4-05 <1> | Frequency Reference Bias Operation Mode Selection (Up/Down 2) | 0: Bias value is held if no input Up 2 or Down 2 is active. 1: When the Up 2 reference and Down 2 reference are both on or both off, the applied bias becomes 0. Currently selected accel / decel. times are used. Enabled only when d4-03 = 0. | 0, 1 | 0 | A | A | A | 2AC | 166 |
| 5 | d4-06 | Frequency Reference Bias (Up/Down 2) | The Up/Down 2 bias value is saved in d4-06 when the frequency reference is not input by the digital operator. The function depends on the setting of d4-01. It is limited by d4-08 and d4-09. | -99.9 to +100.0 | 0.0% | A | A | A | 2AD | 166 |
| 6 | d4-07 <1> | Analog Frequency Reference Fluctuation Limit (Up/Down 2) | When an Up 2 or Down 2 input is active and the frequency reference value from analog or pulse input changes for more than the level set in d4-07, the bias value is hold and the frequency reference is changed to the new value. After the speed reaches the frequency reference the bias hold is released. | 0.1 to +100.0 | 1.0% | A | A | A | 2AE | 166 |
| 7 | d4-08 <1> | Frequency Reference Bias Upper Limit (Up/Down 2) | Sets the upper limit for the bias and the value that can be saved in d4-06. Set as a percentage of the maximum output frequency E1-04. | 0.1 100.0 to | <4> | A | A | A | 2AF | 166 |
| 8 | d4-09 <1> | Frequency Reference Bias Lower Limit (Up/Down 2) | Sets the lower limit for the bias and the value that can be saved in d4-06. Set as a percentage of the maximum output frequency E1-04. | -99.9 to 0.0 | 0.0% | A | A | A | 2B0 | 167 |
| 9 | d4-10 | Up/Down Frequency Reference Limit Selection | Selects which value is used as frequency reference lower limit if the Up/Down function is used. 0: The lower limit is determined by d2-02 or analog input (H3-02/10 = 0). The higher of both values becomes the reference limit. 1: The lower limit is determined by d2-02. | 0 or 1 | 0 | A | A | A | 2B6 | 167 |
| 10 | d7-01 <1> | Offset Frequency 1 | Added to the frequency reference when the digital input “Frequency Offset 1” (H1-□□ = 44) is switched on. | -100.0 to +100.0 | 0.0% | A | A | A | 2B2 | 167 |
| 11 | d7-02 <1> | Offset Frequency 2 | Added to the frequency reference when the digital input “Frequency Offset 2” (H1-□□ = 45) is switched on. | -100.0 to +100.0 | 0.0% | A | A | A | 2B3 | 167 |
| 12 | d7-03 <1> | Offset Frequency 3 | Added to the frequency reference when the digital input “Frequency Offset 3” (H1-□□ = 46) is switched on. | -100.0 to +100.0 | 0.0% | A | A | A | 2B4 | 167 |
Manual — Motor voltage pattern and current — page 367
Source reference: SIEP C71060618F, December 2016, physical PDF page 367. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
u E: Motor Parameters
No. Name Description Range Def.
Control Mode Addr. Hex Pg. O V/f PM LV
E1: V/f Pattern Characteristics Use E1 parameters to set V/f characteristics for the motor.
E2: Motor Parameters Use E2 parameters to set motor-related data.
B.2 Parameter Table
B
List Parameter
E1-01 <1> | Input Voltage Setting
E1-03 <2> | V/f Pattern Selection
E1-04 | Maximum Output Frequency
E1-05 <1> | Maximum Output Voltage
E1-06 | Base Frequency
E1-07 | Middle Output Frequency
E1-08 <1> | Middle Output Frequency Voltage
E1-09 | Minimum Output Frequency
E1-10 <1> | Minimum Output Frequency Voltage
E1-11 | Middle Output Frequency 2
E1-12 <1> <7> | Middle Output Frequency Voltage 2
E1-13 <1> <9> | Base Voltage
E2-01 <8> | Motor Current Rated
E2-02 | Motor Rated Slip
Parameter catalogue PDF367 section1 — PDF page 367
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E1-01 <1> | Input Voltage Setting | This parameter must be set to the power supply voltage. It sets the maximum and base voltage used by preset V/f patterns (E1-03 = 0 to E) and adjusts levels used by certain functions. WARNING! Electrical Shock Hazard. Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. failure to do so may result in equipment damage and/or death or personal injury. | 155 to 255 | 230 V | S | S | S | 300 | 169 |
| 2 | E1-03 <2> | V/f Pattern Selection | Selects a preset V/f pattern. 0: 50 Hz Constant torque 1 1: 60 Hz Constant torque 2 2: 60 Hz Constant torque 3 (50 Hz base) 3: 72 Hz Constant torque 4 (60 Hz base) 4: 50 Hz Variable torque 1 5: 50 Hz Variable torque 2 6: 60 Hz Variable torque 3 7: 60 Hz Variable torque 4 8: 50 Hz High starting torque 1 9: 50 Hz High starting torque 2 A: 60 Hz High starting torque 3 B: 60 Hz High starting torque 4 C: 90 Hz (60 Hz base) D: 120 Hz (60 Hz base) E: 180 Hz (60 Hz base) F: Custom V/f. E1-04 through E1-13 settings define the V/f pattern | 0 to F | F | A | A | − | 302 | 169 |
| 3 | E1-04 | Maximum Output Frequency | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 40.0 to 400.0 <3> | 60 Hz <4> | S | S | S | 303 | 172 |
| 4 | E1-05 <1> | Maximum Output Voltage | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to 255.0 | 230 V <4> | S | S | S | 304 | 172 |
| 5 | E1-06 | Base Frequency | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | E1-04 0.0 to | 60 <4> Hz | S | S | S | 305 | 172 |
| 6 | E1-07 | Middle Output Frequency | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to E1-04 | 3.0 Hz <3> | A | A | - | 306 | 172 |
| 7 | E1-08 <1> | Middle Output Frequency Voltage | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to 255.0 | 18.4 V <5> <6> | A | A | - | 307 | 172 |
| 8 | E1-09 | Minimum Output Frequency | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to E1-04 | 1.5 Hz <5> <4> | S | S | S | 308 | 172 |
| 9 | E1-10 <1> | Minimum Output Frequency Voltage | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to 255.0 | 13.8 V <5> <6> | A | A | - | 309 | 172 |
| 10 | E1-11 | Middle Output Frequency 2 | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to E1-04 | 0.0 Hz | A | A | - | 30A | 172 |
| 11 | E1-12 <1> <7> | Middle Output Frequency Voltage 2 | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to 255.0 | 0.0 V | A | A | - | 30B | 172 |
| 12 | E1-13 <1> <9> | Base Voltage | E1-04 and E1-06 to E1-13 can only be changed when E1-03 is set to F. To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. When E1-13 = 0.0 V, then the drive uses the value set to E1-05 to control the voltage level. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04. Note: Setting E1-11 to 0 disables both E1-11 and E1-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E1-05,E1-12,E1-13,E1-08,E1-10;Frequency(Hz);E1-09,E1-07,E1-06,E1-11,E1-04. Exact curve geometry original-only. | 0.0 to 255.0 | 0.0 V | A | S | - | 30C | 172 |
| 13 | E2-01 <8> | Motor Rated Current | Sets the motor nameplate full load current in amperes (A). Automatically set during Auto-Tuning. Note: Set E2-03 (Motor No-Load Current) before making changes to E2-01. An oPE01 error will be triggered if E2-01 < E2-03. | 10 to 200% of drive rated current <9> | <10> | S | S | − | 30E | 173 |
| 14 | E2-02 | Motor Rated Slip | Sets the motor rated slip in Hertz. Automatically set during rotational Auto-Tuning. | 0.00 to 20.00 | <10> | A | A | − | 30F | 173 |
Manual — Motor1 values and Motor2 selection — page 368
Source reference: SIEP C71060618F, December 2016, physical PDF page 368. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. Hex Pg. O V/f PM LV
E3: Motor 2 V/f Characteristics Use E3 parameters to set the V/f pattern for a second motor.
B.2 Parameter Table
E2-03 | Motor No-Load Current
E2-04 | Number of Motor Poles
E2-05 | Motor Line-to-Line Resistance
E2-06 | Motor Leakage Inductance
E2-07 | Motor Iron-Core Saturation Coefficient 1
E2-08 | Motor Iron-Core Saturation Coefficient 2
E2-09 | Motor Mechanical Loss
E2-10 | Motor Iron Loss for Torque Compensation
E2-11 | Motor Rated Output
E2-12 | Motor Iron-Core Saturation Coefficient 3
E3-01 | Motor 2 Control Method
Parameter catalogue PDF368 section1 — PDF page 368
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E2-03 | Motor No-Load Current | Sets the magnetizing current of the motor in Ampere. Automatically set during rotational Auto-Tuning. Note: Set E2-03 (Motor No-Load Current) before making changes to E2-01. An oPE01 error will be triggered if E2-01 < E2-03. | 0 to less than E2-01 | <10> | A | A | − | 310 | 173 |
| 2 | E2-04 | Number of Motor Poles | Sets the number of motor poles. Automatically set during Auto-Tuning. | 2 to 48 | 4 poles | A | A | − | 311 | 173 |
| 3 | E2-05 | Motor Line-to-Line Resistance | Sets the phase-to-phase motor resistance in ohms. Automatically set during Auto-Tuning. | 0.000 to 65.000 <11> | <10> | A | A | − | 312 | 173 |
| 4 | E2-06 | Motor Leakage Inductance | Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. Automatically set during Auto-Tuning. | 0.0 to 40.0 | <10> | A | A | − | 313 | 174 |
| 5 | E2-07 | Motor Iron-Core Saturation Coefficient 1 | Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during Auto-Tuning. | 0.00 to 0.50 | 0.50 | − | A | − | 314 | 174 |
| 6 | E2-08 | Motor Iron-Core Saturation Coefficient 2 | Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set during Auto-Tuning. | E2-07 to 0.75 | 0.75 | − | A | − | 315 | 174 |
| 7 | E2-09 | Motor Mechanical Loss | Sets the motor mechanical loss as a percentage of motor rated power (kW). Adjust in the following circumstances: When there is a large amount of torque loss due to motor bearing friction. When there is a large amount of torque loss. | 0.0 to 10.0 | 0.0% | − | A | − | 316 | 174 |
| 8 | E2-10 | Motor Iron Loss for Torque Compensation | Sets the motor iron loss in watts (W). | 0 to 65535 | <10> | A | − | − | 317 | 174 |
| 9 | E2-11 | Motor Rated Output | Sets the motor rated power in kilowatts (kW). Automatically set during Auto-Tuning. (1 HP = 0.746 kW). | 0.00 to 650.00 | 0.40 kW <6> | S | S | − | 318 | 174 |
| 10 | E2-12 | Motor Iron-Core Saturation Coefficient 3 | Set to the motor iron saturation coefficient at 130% of magnetic flux. Automatically set during rotational Auto-Tuning. | 1.30 to 5.00 | 1.30 | − | A | − | 328 | 174 |
| 11 | E3-01 | Motor 2 Control Method | 0: V/f Control 2: Open Loop Vector (OLV) | 0 or 2 | 0 | A | A | − | 319 | 175 |
Manual — Motor2 parameters — page 369
Source reference: SIEP C71060618F, December 2016, physical PDF page 369. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. Hex Pg. O V/f PM LV
E4: Motor 2 Parameters Use E4 parameters to control a second motor operating on the same drive.
B.2 Parameter Table
B
List Parameter
E3-04 | Motor 2 Max Output Frequency
E3-05 <1> | Motor 2 Max Voltage
E3-06 | Motor 2 Base Frequency
E3-07 | Motor 2 Mid Output Freq.
E3-08 <1> | Motor 2 Mid Output Freq. Voltage
E3-09 | Motor 2 Min. Output Freq.
E3-10 <1> | Motor 2 Min. Output Freq. Voltage
E3-11 <7> | Motor 2 Mid Output Frequency 2
E3-12 <1> <13> | Motor 2 Mid Output Frequency Voltage 2
E3-13 <1> <9> | Motor 2 Base Voltage
E4-01 | Motor 2 Rated Current
E4-02 | Motor 2 Rated Slip
E4-03 | Motor 2 Rated No- Load Current
E4-04 | Motor 2 Motor Poles
E4-05 | Motor 2 Line-to- Line Resistance
E4-06 | Motor 2 Leakage Inductance
E4-07 | Motor 2 Motor Iron- Core Saturation Coefficient 1
E4-08 | Motor 2 Motor Iron- Core Saturation Coefficient 2
E4-09 | Motor 2 Mechanical Loss
E4-10 | Motor 2 Iron Loss
E4-11 | Motor 2 Rated Capacity
Parameter catalogue PDF369 section1 — PDF page 369
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E3-04 | Motor 2 Max Output Frequency | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 40.0 to 400.0 | 60 Hz | A | A | − | 31A | 175 |
| 2 | E3-05 <1> | Motor 2 Max Voltage | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to 255.0 | 230.0 V | A | A | − | 31B | 175 |
| 3 | E3-06 | Motor 2 Base Frequency | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to E3-04 | 60 Hz | A | A | − | 31C | 175 |
| 4 | E3-07 | Motor 2 Mid Output Freq. | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to E3-04 | 3.0 Hz <12> | A | A | − | 31D | 175 |
| 5 | E3-08 <1> | Motor 2 Mid Output Freq. Voltage | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to 255.0 | 18.4 V <6> <12> | A | A | − | 31E | 175 |
| 6 | E3-09 | Motor 2 Min. Output Freq. | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to E3-04 | 1.5 Hz <12> | A | A | − | 31F | 175 |
| 7 | E3-10 <1> | Motor 2 Min. Output Freq. Voltage | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to 255.0 | 13.8 V <6> <12> | A | A | − | 320 | 175 |
| 8 | E3-11 <7> | Motor 2 Mid Output Frequency 2 | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to E3-04 | 0.0 Hz | A | A | − | 345 | 175 |
| 9 | E3-12 <1> <13> | Motor 2 Mid Output Frequency Voltage 2 | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to <1> 255.0 | 0.0 Vac | A | A | − | 346 | 175 |
| 10 | E3-13 <1> <9> | Motor 2 Base Voltage | To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these rules to prevent triggering an oPE10 fault: E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 Note: Setting E3-11 to 0 disables both E3-11 and E3-12, and the above conditions do not apply. Graph labels: VACrms Out(V);E3-05,E3-12,E3-13,E3-08,E3-10;Frequency(Hz);E3-09,E3-07,E3-06,E3-11,E3-04. Exact curve geometry original-only. | 0.0 to 255.0 <1> | 0.0 Vac | A | S | − | 347 | 175 |
| 11 | E4-01 | Motor 2 Rated Current | Sets the motor 2 nameplate full load current in amperes (A). This value is automatically set during Auto-Tuning. | 10 to 200% of drive rated current | <10> | A | A | − | 321 | 176 |
| 12 | E4-02 | Motor 2 Rated Slip | Sets the motor 2 rated slip in Hz. Automatically set during Auto-Tuning. | 0.00 to 20.00 | <10> | A | A | − | 322 | 176 |
| 13 | E4-03 | Motor 2 Rated No- Load Current | Sets the magnetizing current of motor 2 in Ampere. Automatically set during Rotational Auto-Tuning. | 0 to less than E4-01 <9> | <10> | A | A | − | 323 | 176 |
| 14 | E4-04 | Motor 2 Motor Poles | Sets the number of poles of motor 2. This value is automatically set during Auto-Tuning. | 2 to 48 | 4 poles | A | A | − | 324 | 176 |
| 15 | E4-05 | Motor 2 Line-to- Line Resistance | Sets the phase-to-phase resistance of motor 2 in ohms. Automatically during Auto-Tuning. | 0.000 to 65.000 <11> | <10> | A | A | − | 325 | 176 |
| 16 | E4-06 | Motor 2 Leakage Inductance | Sets the voltage drop due to motor leakage inductance as a percentage of rated voltage of motor 2. Automatically set during Auto-Tuning. | 0.0 to 40.0 | <10> | A | A | − | 326 | 176 |
| 17 | E4-07 | Motor 2 Motor Iron- Core Saturation Coefficient 1 | Set to the motor iron saturation coefficient at 50% of magnetic flux. Automatically set during Rotational Auto-Tuning. | 0.00 to 0.50 | 0.50 | − | A | − | 343 | 177 |
| 18 | E4-08 | Motor 2 Motor Iron- Core Saturation Coefficient 2 | Set to the motor iron saturation coefficient at 75% of magnetic flux. This value is automatically set during Rotational Auto-Tuning. | Setting for E4-07 to 0.75 | 0.75 | − | A | − | 344 | 177 |
| 19 | E4-09 | Motor 2 Mechanical Loss | Sets the motor mechanical loss as a percentage of motor rated power (kW) capacity. Adjust in the following circumstances: • When there is a large amount of torque loss due to motor bearing friction. • When there is a large amount of torque loss. | 0.00 to 10.0 | 0.0 | − | A | − | 33F | 177 |
| 20 | E4-10 | Motor 2 Iron Loss | Sets the motor iron loss in watts. | 0 to 65535 | <10> | Α | − | − | 340 | 177 |
| 21 | E4-11 | Motor 2 Rated Capacity | Sets the motor rated capacity in kW. Automatically set during Auto-Tuning. | 0.00 to 650.00 | <6> | A | A | − | 327 | 177 |
Manual — PM motor parameters — page 370
Source reference: SIEP C71060618F, December 2016, physical PDF page 370. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. Hex Pg. O V/f PM LV
E5: PM Motor Parameters
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
B.2 Parameter Table
E4-12 | Motor 2 Iron-Core Saturation Coefficient 3
E4-14 <14> | Motor 2 Slip Compensation Gain
E4-15 | Torque Compensation Gain - Motor 2
E5-01 <2> | Motor Code Selection (for PM motor)
E5-02 <2> | Motor Rated Capacity (for PM motor)
E5-03 <2> | Motor Current Rated
E5-04 <2> | Motor Poles
E5-05 <2> | Motor Resistance Stator
E5-06 <2> | Motor Inductance d Axis
E5-07 <2> | Motor Inductance q Axis
E5-09 <2> | Motor Voltage Induction Constant 1
E5-24 <2> | Motor Voltage Induction Constant 2
E5-39 <18> | Current Detection Delay Time
Parameter catalogue PDF370 section1 — PDF page 370
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E4-12 | Motor 2 Iron-Core Saturation Coefficient 3 | Set to the motor iron saturation coefficient at 130% of magnetic flux. Automatically set during Rotational Auto-Tuning. | 1.30 to 5.00 | 1.30 | − | A | − | 342 | 177 |
| 2 | E4-14 <14> | Motor 2 Slip Compensation Gain | Sets the slip compensation gain for motor 2. The function is the same as C3-01 for motor 1. Refer to C3-01: Slip Compensation Gain on page 151. | 0.0 to 2.5 | 0.0 <12> | A | A | − | 341 | 177 |
| 3 | E4-15 | Torque Compensation Gain - Motor 2 | Sets the torque compensation gain for motor 2. The function is the same as C4-01 for motor 1. Refer to C4-01: Torque Compensation Gain on page 152. | 1.00 to 2.50 | 1.00 | A | A | − | 341 | 177 |
| 4 | E5-01 <2> | Motor Code Selection (for PM motor) | Enter the Yaskawa motor code for the PM motor being used. Various motor parameters are automatically set based on the value of this parameter. Note: Set to FFFF when using a specialized, custom, or non- Yaskawa motor. For all other motors: diagram0000 with Motor Voltage Class and Capacity callout;motor series0:Pico Motor(SMRA Series),1:Derated Torque for IPM Motors(SSR1 Series);speed series0:1800r/min,1:3600r/min,2:1750r/min,3:1450r/min,4:1150r/min,F:Special Motor. Exact digit/bracket layout original-only; no motor code inferred. All motor parameters are reinitialized to factory settings when this parameter is set. | 0000 to FFFF | <6> <15> | − | − | S | 329 | 178 |
| 5 | E5-02 <2> | Motor Rated Capacity (for PM motor) | Sets the rated capacity of the motor. | 0.10 18.50 to | <4> | − | − | S | 32A | 178 |
| 6 | E5-03 <2> | Motor Current Rated | Sets the motor rated current in amps. | 10 to 200% of drive rated current <9> | <16> | − | − | S | 32B | 178 |
| 7 | E5-04 <2> | Motor Poles | Sets the number of motor poles. | 2 to 48 | <4> | − | − | S | 32C | 178 |
| 8 | E5-05 <2> | Motor Stator Resistance | Set the resistance for each motor phase in units of 0.001 Ω. | 0.000 65.000 to | <4> | − | − | S | 32D | 179 |
| 9 | E5-06 <2> | Motor d Axis Inductance | Sets the d axis inductance in units of 0.01 mH. | 0.00 300.00 to | <4> | − | − | S | 32E | 179 |
| 10 | E5-07 <2> | Motor q Axis Inductance | Sets the q axis inductance in units of 0.01 mH. | 0.00 600.00 to | <4> | − | − | S | 32F | 179 |
| 11 | E5-09 <2> | Motor Induction Voltage Constant 1 | Set the induced phase peak voltage in units of 0.1 mV (rad/ s) [electrical angle]. Set this parameter when using a Yaskawa SSR1 series PM motor with derate torque, or a Yaskawa SST4 series motor with constant torque. When setting this parameter, E5-24 should be set to 0. An alarm will be triggered if both E5-09 and E5-24 are set to 0, or if neither parameter is set to 0. | 2000.0 0.0 to | <4> | − | − | S | 331 | 179 |
| 12 | E5-24 <2> | Motor Induction Voltage Constant 2 | Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using a Yaskawa SMRA Series SPM Motor. When setting this parameter, E5-09 should be set to 0. An alarm will be triggered if both E5-09 and E5-24 are set to 0, or if neither parameter is set to 0. If E5-03 (Motor Rated Current) is set to 0, however, then an alarm will not be triggered when both E5-09 and E5-24 are set to 0. | <17> | <4> | − | − | S | 353 | 179 |
| 13 | E5-39 <18> | Current Detection Delay Time | Sets the current detection delay time at the time of d-Axis and q-Axis current feedback calculation. Changing this parameter from the default setting is not normally required. | -1000 to 1000 | 0 µs | A | A | A | 5E2 | 179 |
Manual — Motor notes and PG options — page 371
Source reference: SIEP C71060618F, December 2016, physical PDF page 371. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
<2> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <3> Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current. <4> Default setting value is dependent on parameter E5-01, Motor Code Selection. <5> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <6> Default setting value is dependent on parameter o2-04, Drive Model Selection. <7> Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency Voltage 2, are set to 0.0. <8> When setting motor parameters, the motor rated current must be set to a value greater than the motor no-load current (E2-01 > E2-03). <9> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. <10> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. <11> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller. <12> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f Control. <13> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0. <14> Parameter can be changed during Run. <15> If using a Yaskawa SMRA Series SPM Motor, the default setting is 1800 r/min. <16> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 ≠ 0. <17> Default setting is determined by drive software version. PRG: 1018 and later: 0.0 to 6500.0 mV/(r/min) PRG: 1017 and earlier: 0.0 to 2000.0 mV/(r/min) <18> Available in drive software versions PRG: 1022 and later.
u F: Options
F parameters are used to program the drive for PG feedback and to function with option cards.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
F1: V/f Control with Simple PG Feedback - PG Setup Parameters Use F1 parameters to set up the drive for V/f Control with Simple PG Feedback. These parameters are enabled only when H6-01 = 03
B.2 Parameter Table
B
List Parameter
F1-02 | Operation Selection at PG Open Circuit (PGo)
F1-03 | Operation Selection at Overspeed (oS)
F1-04 | Operation Selection at Deviation
F1-08 | Overspeed Detection Level
F1-09 | Overspeed Detection Delay Time
Parameter catalogue PDF371 section1 — PDF page 371
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | F1-02 | Operation Selection at PG Open Circuit (PGo) | Sets stopping method when a PG open circuit fault (PGo) occurs. Refer to parameter F1-14. 0: Ramp to Stop - Decelerate to stop using the active deceleration time. 1: Coast to Stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm only - Drive continues operation. | 0 to 3 | 1 | A | − | − | 381 | 181 |
| 2 | F1-03 | Operation Selection at Overspeed (oS) | Sets the stopping method when an overspeed (oS) fault occurs. Refer to F1-08 and F1-09. 0: Ramp to stop - Decelerate to stop using the active deceleration time. 1: Coast to stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm Only - Drive continues operation. | 0 to 3 | 1 | A | − | − | 382 | 181 |
| 3 | F1-04 | Operation Selection at Deviation | Sets the stopping method when a speed deviation (dEv) fault occurs. Refer to F1-10 and F1-11. 0: Ramp to stop - Decelerate to stop using the active deceleration time. 1: Coast to stop 2: Fast-stop - Decelerate to stop using the deceleration time in C1-09. 3: Alarm only - Drive continues operation. | 0 to 3 | 3 | A | − | − | 383 | 181 |
| 4 | F1-08 | Overspeed Detection Level | Sets the speed feedback level which has to be exceeded for the time set in F1-09 before an oS fault will occur. Set as a percentage of the maximum output frequency (E1-04). | 0 to 120 | 115% | A | − | − | 387 | 181 |
| 5 | F1-09 | Overspeed Detection Delay Time | Sets the time in seconds for which the speed feedback has to exceed the overspeed detection level F1-08 before an oS fault will occur. | 0.0 to 2.0 | 1.0 | A | − | − | 388 | 181 |
Manual — PG and communication options — page 372
Source reference: SIEP C71060618F, December 2016, physical PDF page 372. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
F6: Serial Communications Option Card Settings Use F6 parameters to program the drive for serial communication.
B.2 Parameter Table
F1-10 | Excessive Speed Deviation Detection Level
F1-11 | Excessive Speed Deviation Detection Delay Time
F1-14 | PG Open-Circuit Detection Time
F6-01 | Communications Error operation Selection
F6-02 | External fault from comm. option selection
F6-03 | External fault from comm. option operation selection
F6-04 | Bus Error Detection Time
F6-07 <6> | NetRef/ComRef Function Selection
F6-08 <6> | Reset Communication Parameters
F6-10 | CC-Link Node Address
F6-11 | CC-Link communications speed
F6-14 | BUS Error Auto Reset
F6-20 <7> | MECHATROLINK Address Station
F6-21 <7> | MECHATROLINK Frame Size
F6-22 <7> | MECHATROLINK Speed Link
F6-23 <7> | MECHATROLINK Monitor Selection (E)
F6-24 <7> | MECHATROLINK Monitor Selection (F)
Parameter catalogue PDF372 section1 — PDF page 372
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | F1-10 | Excessive Speed Deviation Detection Level | Sets the allowable deviation between motor speed and frequency reference before a speed deviation fault (dEv) is triggered. Set as a percentage of the maximum output frequency (E1-04). | 0 to 50 | 10% | A | − | − | 389 | 181 |
| 2 | F1-11 | Excessive Speed Deviation Detection Delay Time | Sets the time in seconds for which a deviation between motor speed and frequency reference has to exceed the speed deviation detection level F1-10 before a dEv fault will occur. | 0.0 to 10.0 | 0.5 s | A | − | − | 38A | 181 |
| 3 | F1-14 | PG Open-Circuit Detection Time | Sets the time for which no PG pulses must be detected before a PG Open (PGo) fault is triggered. | 0.0 to 10.0 | 2.0 s | A | − | − | 38D | 182 |
| 4 | F6-01 | Communications Error operation Selection | Selects the operation after a communications error occurred. 0: Ramp to stop using current accel/decel time 1: Coast to stop 2: Fast-stop using C1-09 3: Alarm only 4: Alarm and Run at d1-04 <9> <10> 5: Alarm and Ramp to stop <9> | 0 to 5 | 1 | A | A | A | 3A2 | 182 |
| 5 | F6-02 | External fault from comm. option selection | Sets when an external fault from a comm option is detected. 0: Always detected 1: Detection during Run only | 0, 1 | 0 | A | A | A | 3A3 | 182 |
| 6 | F6-03 | External fault from comm. option operation selection | Selects the operation after an external fault set by a communications option (EF0). 0: Ramp to stop using current accel/decel time 1: Coast to stop 2: Fast-stop using C1-09 3: Alarm only | 0 to 3 | 1 | A | A | A | 3A4 | 182 |
| 7 | F6-04 | Bus Error Detection Time | Set the delay time for error detection if a bus error occurs. | 0.0 to 5.0 | 2.0 s | A | A | A | 3A5 | – |
| 8 | F6-07 <6> | NetRef/ComRef Function Selection | 0: Multi-step reference disabled (same as F7) 1: Multi-step reference enabled (same as V7) | 0, 1 | 0 | A | A | A | 3A8 | 182 |
| 9 | F6-08 <6> | Reset Communication Parameters | 0: Communication-related parameters (F6-□□ and F7-□□) are not reset when the drive is initialized using A1-03. 1: Reset all communication-related parameters (F6-□□ and F7-□□) when the drive is initialized using A1-03. | 0, 1 | 0 <1> | A | A | A | 36A | 183 |
| 10 | F6-10 | CC-Link Node Address | Sets the node address if a CC-Link option card is installed. | 0 to 63 | 0 | A | A | A | 3E6 | – |
| 11 | F6-11 | CC-Link communications speed | 0: 156 Kbps 1: 625 Kbps 2: 2.5 Mbps 3: 5 Mbps 4: 10 Mbps | 0 to 4 | 0 | A | A | A | 3E7 | – |
| 12 | F6-14 | BUS Error Auto Reset | Selects if a BUS fault can be automatically reset. 0: Disabled 1: Enabled | 0, 1 | 0 | A | A | A | 3BB | – |
| 13 | F6-20 <7> | MECHATROLINK Station Address | Sets the station address when the MECHATROLINK option has been installed. | <8> | 21 | A | A | A | 36B | – |
| 14 | F6-21 <7> | MECHATROLINK Frame Size | MECHATROLINK-II 0: 32 byte 1: 17 byte MECHATROLINK-III 0: 64 byte 1: 32 byte | 0, 1 | 0 | A | A | A | 36C | – |
| 15 | F6-22 <7> | MECHATROLINK Link Speed | 0: 10 Mbps 1: 4 Mbps Note: Available only for MECHATROLINK-II. | 0, 1 | 0 | A | A | A | 36D | – |
| 16 | F6-23 <7> | MECHATROLINK Monitor Selection (E) | Sets the MECHATROLINK monitor (E). | 0 to FFFFH | 0 | A | A | A | 36E | – |
| 17 | F6-24 <7> | MECHATROLINK Monitor Selection (F) | Sets the MECHATROLINK monitor (F). | 0 to FFFFH | 0 | A | A | A | 36F | – |
Manual — Communication option parameters — page 373
Source reference: SIEP C71060618F, December 2016, physical PDF page 373. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
B.2 Parameter Table
B
List Parameter
F6-25 <7> | Operation Selection at MECHATROLINK Watchdog Timer Error (E5)
F6-26 <7> | MECHATROLINK bUS Errors Detected
F6-30 | PROFIBUS node address
F6-31 | PROFIBUS Clear Mode Selection
F6-32 | PROFIBUS Data Format Selections
F6-35 | CANopen Node ID selection
F6-36 | CANopen Communications speed
F6-40 | CompoNet Node ID
F6-41 | CompoNet Speed
F6-50 <3> | DeviceNet MAC Address
F6-51 <3> | Device Net Communications Speed
F6-52 <3> | DeviceNet PCA setting
F6-53 <3> | DeviceNet PPA setting
F6-54 <3> | DeviceNet Idle Mode Fault Detection
F6-55 | DeviceNet Baud Rate Monitor
F6-56 <3> | DeviceNet Speed Scaling Factor
F6-57 <3> | DeviceNet Current Scaling Factor
F6-58 <3> | DeviceNet Torque Scaling Factor
F6-59 <3> | DeviceNet Power Scaling Factor
Parameter catalogue PDF373 section1 — PDF page 373
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | F6-25 <7> | Operation Selection at MECHATROLINK Watchdog Timer Error (E5) | 0: Ramp to stop. Decelerate using the deceleration time in C1-02. 1: Coast to stop 2: Fast stop. Decelerate using the deceleration time in C1-09. 3: Alarm only | 0 to 3 | 1 | A | A | A | 3C9 | – |
| 2 | F6-26 <7> | MECHATROLINK bUS Errors Detected | Sets the number of option communication errors (bUS). | 2 to 10 | 2 | A | A | A | 3CA | – |
| 3 | F6-30 | PROFIBUS node address | Sets the node address for a PROFIBUS option. | 0 to 125 | 0 | A | A | A | 3CB | – |
| 4 | F6-31 | PROFIBUS Clear Mode Selection | Selects the operation when a "Clear Mode" command is received. 0: Resets drive operation. 1: Maintains the previous operation state. | 0, 1 | 0 | A | A | A | 3CC | – |
| 5 | F6-32 | PROFIBUS Data Format Selections | 0: PPO Type 1: Conventional | 0, 1 | 0 | A | A | A | 3CD | – |
| 6 | F6-35 | CANopen Node ID selection | Sets the Node ID for a CANopen option | <2> | 99 | A | A | A | 3D0 | – |
| 7 | F6-36 | CANopen Communications speed | 0: Auto-adjust 1: 10 kbps 2: 20 kbps 3: 50 kbps 4: 125 kbps 5: 250 kbps 6: 500 kbps 7: 800 kbps 8: 1 Mbps | 0 to 8 | 6 | A | A | A | 3D1 | – |
| 8 | F6-40 | CompoNet Node ID | Sets the Node ID for a CompoNet option. | 0 to 63 | 0 | A | A | A | 3D5 | – |
| 9 | F6-41 | CompoNet Speed | 0: 93.75 kbps 1: Reserved 2: 1.5 Mbps 3: 3 Mbps 4: 4 Mbps 5-255: Reserved | 0 to 255 | 0 | A | A | A | 3D6 | – |
| 10 | F6-50 <3> | DeviceNet MAC Address | Selects the drives MAC address for DeviceNet. | 0 to 64 | 64 | A | A | A | 3C1 | – |
| 11 | F6-51 <3> | Device Net Communications Speed | 0: 125 kbps 1: 250 kbps 2: 500 kbps 3: Adjustable from Network 4: Detect automatically | 0 to 4 | 4 | A | A | A | 3C2 | – |
| 12 | F6-52 <3> | DeviceNet PCA setting | I/O Polled Consuming Assembly Data Instance | 0 to 255 | 21 | A | A | A | 3C3 | – |
| 13 | F6-53 <3> | DeviceNet PPA setting | I/O Polled Producing Assembly Data Instance | 0 to 255 | 71 | A | A | A | 3C4 | – |
| 14 | F6-54 <3> | DeviceNet Idle Mode Fault Detection | Selects if an EF0 fault is detected when no data are received from the master. <4> 0: Detection enabled 1: No detection | 0, 1 | 0 | A | A | A | 3C5 | – |
| 15 | F6-55 | DeviceNet Baud Rate Monitor | Verifies the baud rate running on the network. 0: 125 kbps 1: 250 kbps 2: 500 kbps | 0 to 2 | 0 | A | A | A | 3C6 | – |
| 16 | F6-56 <3> | DeviceNet Speed Scaling Factor | Sets the scaling factor for the speed monitor in DeviceNet Class ID 2AH Object. | -15 to 15 | 0 | A | A | A | 3D7 | – |
| 17 | F6-57 <3> | DeviceNet Current Scaling Factor | Sets the scaling factor for the output current monitor in DeviceNet Class ID 2AH Object. | -15 to 15 | 0 | A | A | A | 3D8 | – |
| 18 | F6-58 <3> | DeviceNet Torque Scaling Factor | Sets the scaling factor for the torque monitor in DeviceNet Class ID 2AH Object. | -15 to 15 | 0 | A | A | A | 3D9 | – |
| 19 | F6-59 <3> | DeviceNet Power Scaling Factor | Sets the scaling factor for the power monitor in DeviceNet Class ID 2AH Object. | -15 to 15 | 0 | A | A | A | 3DA | – |
Manual — Software-dependent assembly mappings — page 374
Source reference: SIEP C71060618F, December 2016, physical PDF page 374. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
F7: EtherNet/IP and Modbus TCP/IP Option Parameters Use F7 parameters to program the drive for EtherNet communication.
B.2 Parameter Table
F6-60 <3> | DeviceNet Voltage Scaling Factor
F6-61 <3> | DeviceNet Time Scaling Factor
F6-62 <3> | DeviceNet Heartbeat Interval
F6-63 | Dynamic Output Assembly 109 Parameter 1 <5>
F6-63 | MAC ID Memory <6>
F6-64 | Dynamic Output Assembly 109 Parameter 2 <5>
F6-64 | Dynamic Output Assembly 109 Parameter 1 <6>
F6-65 | Dynamic Output Assembly 109 Parameter 3 <5>
F6-65 | Dynamic Output Assembly 109 Parameter 2 <6>
F6-66 | Dynamic Output Assembly 109 Parameter 4 <5>
F6-66 | Dynamic Output Assembly 109 Parameter 3 <6>
F6-67 | Dynamic Output Assembly 159 Parameter 1 <5>
F6-67 | Dynamic Output Assembly 109 Parameter 4 <6>
F6-68 | Dynamic Output Assembly 159 Parameter 2 <5>
F6-68 | Dynamic Output Assembly 159 Parameter 1 <6>
F6-69 | Dynamic Output Assembly 159 Parameter 3 <5>
F6-69 | Dynamic Output Assembly 159 Parameter 2 <6>
F6-70 | Dynamic Output Assembly 159 Parameter 4 <5>
F6-70 | Dynamic Output Assembly 159 Parameter 3 <6>
F6-71 | Dynamic Output Assembly 159 Parameter 4 <6>
Parameter catalogue PDF374 section1 — PDF page 374
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | F6-60 <3> | DeviceNet Voltage Scaling Factor | Sets the scaling factor for the voltage monitor in DeviceNet Class ID 2AH Object. | -15 to 15 | 0 | A | A | A | 3DB | – |
| 2 | F6-61 <3> | DeviceNet Time Scaling Factor | Sets the scaling factor for the time monitor in DeviceNet Class ID 2AH Object. | -15 to 15 | 0 | A | A | A | 3DC | – |
| 3 | F6-62 <3> | DeviceNet Heartbeat Interval | Sets the heartbeat interval for DeviceNet communications. | 0 to 10 | 0 | A | A | A | 3DD | – |
| 4 | F6-63 | Dynamic Output Assembly 109 Parameter 1 <5> | Dynamic Output Assembly 109 Parameter 1 | 0x0 to 0xFFFF | 0 | A | A | A | 3DE | – |
| 5 | F6-63 | MAC ID Memory <6> | Sets the MAC ID memory (Read only) | 0 to 63 | – | A | A | A | 3DE | – |
| 6 | F6-64 | Dynamic Output Assembly 109 Parameter 2 <5> | Dynamic Output Assembly 109 Parameter 2 | 0x0 to 0xFFFF | 0 | A | A | A | 3DF | – |
| 7 | F6-64 | Dynamic Output Assembly 109 Parameter 1 <6> | Dynamic Output Assembly 109 Parameter 1 | 0x0 to 0xFFFF | 0 | A | A | A | 3DF | – |
| 8 | F6-65 | Dynamic Output Assembly 109 Parameter 3 <5> | Dynamic Output Assembly 109 Parameter 3 | 0x0 to 0xFFFF | 0 | A | A | A | 3E0 | – |
| 9 | F6-65 | Dynamic Output Assembly 109 Parameter 2 <6> | Dynamic Output Assembly 109 Parameter 2 | 0x0 to 0xFFFF | 0 | A | A | A | 3E0 | – |
| 10 | F6-66 | Dynamic Output Assembly 109 Parameter 4 <5> | Dynamic Output Assembly 109 Parameter 4 | 0x0 to 0xFFFF | 0 | A | A | A | 3E1 | – |
| 11 | F6-66 | Dynamic Output Assembly 109 Parameter 3 <6> | Dynamic Output Assembly 109 Parameter 3 | 0x0 to 0xFFFF | 0 | A | A | A | 3E1 | – |
| 12 | F6-67 | Dynamic Output Assembly 159 Parameter 1 <5> | Dynamic Output Assembly 159 Parameter 1 | 0x0 to 0xFFFF | 0 | A | A | A | 3E2 | – |
| 13 | F6-67 | Dynamic Output Assembly 109 Parameter 4 <6> | Dynamic Output Assembly 109 Parameter 4 | 0x0 to 0xFFFF | 0 | A | A | A | 3E2 | – |
| 14 | F6-68 | Dynamic Output Assembly 159 Parameter 2 <5> | Dynamic Output Assembly 159 Parameter 2 | 0x0 to 0xFFFF | 0 | A | A | A | 3E3 | – |
| 15 | F6-68 | Dynamic Output Assembly 159 Parameter 1 <6> | Dynamic Output Assembly 159 Parameter 1 | 0x0 to 0xFFFF | 0 | A | A | A | 3E3 | – |
| 16 | F6-69 | Dynamic Output Assembly 159 Parameter 3 <5> | Dynamic Output Assembly 159 Parameter 3 | 0x0 to 0xFFFF | 0 | A | A | A | 3E4 | – |
| 17 | F6-69 | Dynamic Output Assembly 159 Parameter 2 <6> | Dynamic Output Assembly 159 Parameter 2 | 0x0 to 0xFFFF | 0 | A | A | A | 3E4 | – |
| 18 | F6-70 | Dynamic Output Assembly 159 Parameter 4 <5> | Dynamic Output Assembly 159 Parameter 4 | 0x0 to 0xFFFF | 0 | A | A | A | 3C7 | – |
| 19 | F6-70 | Dynamic Output Assembly 159 Parameter 3 <6> | Dynamic Output Assembly 159 Parameter 3 | 0x0 to 0xFFFF | 0 | A | A | A | 3C7 | – |
| 20 | F6-71 | Dynamic Output Assembly 159 Parameter 4 <6> | Dynamic Output Assembly 159 Parameter 4 | 0x0 to 0xFFFF | 0 | A | A | A | 3C8 | – |
Manual — Ethernet options and communication footnotes — page 375
Source reference: SIEP C71060618F, December 2016, physical PDF page 375. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode Addr. V/ O P Hex Pg. L f M V
O L V
P M
<1> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <2> Setting range is determined by the drive software version. PRG: 1016 and later: 0 to 126 PRG: 1015 and earlier: 0 to 127 <3> Parameter available in drive software versions PRG: 1011 and later. <4> The following parameter settings apply to drive software versions 1015 and earlier: 0: Disabled 1: Enabled <5> Parameter available in drive software versions PRG: 1012 and later. <6> Parameter available in drive software versions PRG: 1014 and later. <7> Parameter available in drive software versions PRG: 1023 and later. <8> Setting range is determined by the option. MECHATROLINK-II: 20H to 3FH MECHATROLINK-III: 03H to EFH <9> Available in drive software version PRG: 1024 and later. <10> Take proper safety measures, such as installing an emergency stop switch, as the drive will continue operation when detecting an bUS error.
B.2 Parameter Table
B
List Parameter
F7-01 to F7-42 | EtherNet/IP and Modbus TCP/IP Option Parameters
Parameter catalogue PDF375 section1 — PDF page 375
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | F7-01 to F7-42 | EtherNet/IP and Modbus TCP/IP Option Parameters | F7 parameters are reserved for use with SI-EN3/V and SI- EM3/V options. Refer to the respective Option Installation Manuals for details. | – | – | – | – | – | – | – |
Manual — Digital input parameters and selections — page 376
Source reference: SIEP C71060618F, December 2016, physical PDF page 376. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ H Parameters: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
H1: Multi-Function Digital Input H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".
<1> The availability of certain functions depends on the control method used. <2> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.
H1 Multi-Function Digital Input Selections
H1-□□ Setting Function Description
Control Mode
Control modes: V/f, OLV, PM; Pg.
B.2 Parameter Table
H1-01 | Multi-Function Digital Input Terminal S1 Function Selection
H1-02 | Multi-Function Digital Input Terminal S2 Function Selection
H1-03 | Multi-Function Digital Input Terminal S3 Function Selection
H1-04 | Multi-Function Digital Input Terminal S4 Function Selection
H1-05 | Multi-Function Digital Input Terminal S5 Function Selection
H1-06 | Multi-Function Digital Input Terminal S6 Function Selection
H1-07 | Multi-Function Digital Input Terminal S7 Function Selection
0 | 3-Wire Sequence
1 | LOCAL/REMOTE Selection
2 | External Reference 1/2
3 | Multi-Step Speed Reference 1
4 | Multi-Step Speed Reference 2
5 | Multi-Step Speed Reference 3
6 | Jog Reference Selection
7 | Accel/Decel Time 1
8 | Baseblock Command (N.O.)
9 | Baseblock Command (N.C.)
A | Accel/Decel Ramp Hold
B | Drive Overheat Alarm (oH2)
C | Terminal A1/A2 Enable
Parameter catalogue PDF376 section1 — PDF page 376
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | H1-01 | Multi-Function Digital Input Terminal S1 Function Selection | Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. | 1 to 9F <1> | 40 | A | A | A | 438 | 184 |
| 2 | H1-02 | Multi-Function Digital Input Terminal S2 Function Selection | Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. | 1 to 9F <1> | 41 | A | A | A | 439 | 184 |
| 3 | H1-03 | Multi-Function Digital Input Terminal S3 Function Selection | Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. | 1 to 9F <1> | 24 | A | A | A | 400 | 184 |
| 4 | H1-04 | Multi-Function Digital Input Terminal S4 Function Selection | Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. | 1 to 9F <1> | 14 | A | A | A | 401 | 184 |
| 5 | H1-05 | Multi-Function Digital Input Terminal S5 Function Selection | Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. | 1 to 9F <1> | 3 (0) <2> | A | A | A | 402 | 184 |
| 6 | H1-06 | Multi-Function Digital Input Terminal S6 Function Selection | Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. | 1 to 9F <1> | 4 (3) <2> | A | A | A | 403 | 184 |
| 7 | H1-07 | Multi-Function Digital Input Terminal S7 Function Selection | Assigns a function to the multi- function digital inputs. Refer to H1 Multi-Function Digital Input Selections on page 376 for a description of setting values. | 1 to 9F <1> | 6 (4) <2> | A | A | A | 404 | 184 |
Multi-function selections PDF376 — PDF page 376
| Source row | Function setting | Function | Description | Control mode V/f | Control mode OLV | Control mode PM | Reference page |
|---|---|---|---|---|---|---|---|
| 1 | 0 | 3-Wire Sequence | Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence) | O | O | O | 185 |
| 2 | 1 | LOCAL/REMOTE Selection | Open: REMOTE, Reference 1 or 2 (b1-01/02 or b1-15/16) Closed: LOCAL, LED operator is run and reference source | O | O | O | 185 |
| 3 | 2 | External Reference 1/2 | Open: Run and frequency reference source 1 (b1-01/02) Closed: Run and frequency reference source 2 (b1-15/16) | O | O | O | 186 |
| 4 | 3 | Multi-Step Speed Reference 1 | Used to select Multi-Step Speeds set in d1-01 to d1-16 | O | O | O | 186 |
| 5 | 4 | Multi-Step Speed Reference 2 | Used to select Multi-Step Speeds set in d1-01 to d1-16 | O | O | O | 186 |
| 6 | 5 | Multi-Step Speed Reference 3 | Used to select Multi-Step Speeds set in d1-01 to d1-16 | O | O | O | 186 |
| 7 | 6 | Jog Reference Selection | Open: Selected speed reference Closed: Jog Frequency reference (d1-17). Jog has priority over all other reference sources. | O | O | O | 186 |
| 8 | 7 | Accel/Decel Time 1 | Used to switch between Accel/Decel. Time 1/2 | O | O | O | 186 |
| 9 | 8 | Baseblock Command (N.O.) | Open: Normal operation Closed: No drive output | O | O | O | 186 |
| 10 | 9 | Baseblock Command (N.C.) | Open: No drive output Closed: Normal operation | O | O | O | 186 |
| 11 | A | Accel/Decel Ramp Hold | Closed: The drive pauses during acceleration or deceleration and maintains the output frequency. | O | O | O | 186 |
| 12 | B | Drive Overheat Alarm (oH2) | Closed: Closes when an oH2 alarm occurs. | O | O | O | 187 |
| 13 | C | Terminal A1/A2 Enable | Terminal status differs depending on drive software version. PRG: 1016 and later: Open: Analog input selected by H3-14 is disabled. Closed: Analog input selected by H3-14 is enabled. PRG: 1015 and earlier: Open: Analog inputs selected for terminals A1 and A2 are disabled. Closed: Analog inputs selected for terminals A1 and A2 are enabled. | O | O | O | 187 |
Manual — Digital input function restrictions — page 377
Source reference: SIEP C71060618F, December 2016, physical PDF page 377. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
H1 Multi-Function Digital Input Selections
H1-□□ Setting Function Description
Control Mode
Control modes: V/f, OLV, PM; Pg.
OLV
PM
B.2 Parameter Table
B
Parameter List
F | Not used
10 | Up Command
11 | Down Command
12 | Forward Jog
13 | Reverse Jog
14 | Fault Reset
15 | Fast-Stop (N.O.)
16 | Motor 2 Selection
17 | Fast-stop (N.C.)
18 | Timer Function Input
19 | PID Disable
1A | Accel/Decel Time Selection 2
1B | Program Lockout
1E | Reference Sample Hold
20 to 2F | External Fault
30 | PID Integral Reset
31 | PID Integral Hold
32 | Multi-Step Speed Reference 4
34 | PID Soft Starter
35 | PID Input Switch
40 | Forward Run Command (2-Wire sequence)
41 | Reverse Run Command (2-Wire sequence)
42 | Run Command (2-Wire sequence 2)
43 | FWD/REV Command (2-Wire sequence 2)
Multi-function selections PDF377 — PDF page 377
| Source row | Function setting | Function | Description | Control mode V/f | Control mode OLV | Control mode PM | Reference page |
|---|---|---|---|---|---|---|---|
| 1 | F | Not used | Select this setting when not using the terminal or when using the terminal in a pass-through mode. | O | O | O | 187 |
| 2 | 10 | Up Command | Open: Maintains the current frequency reference Closed: Increases or decreases the current frequency reference. Ensure that the increase and decrease commands are set in conjunction with one another. | O | O | O | 187 |
| 3 | 11 | Down Command | Open: Maintains the current frequency reference Closed: Increases or decreases the current frequency reference. Ensure that the increase and decrease commands are set in conjunction with one another. | O | O | O | 187 |
| 4 | 12 | Forward Jog | Closed: Runs forward at the Jog Frequency d1-17. | O | O | O | 188 |
| 5 | 13 | Reverse Jog | Closed: Runs reverse at the Jog Frequency d1-17. | O | O | O | 188 |
| 6 | 14 | Fault Reset | Closed: Resets faults if the cause is cleared and the Run command is removed. | O | O | O | 188 |
| 7 | 15 | Fast-Stop (N.O.) | Closed: Decelerates at the Fast-Stop time C1-09. To restart the Fast-Stop input must be released and Run must be cycled. | O | O | O | 188 |
| 8 | 16 | Motor 2 Selection | Open: Motor 1 (E1-□□, E2-□□) Closed: Motor 2 (E3-□□, E4-□□) | O | O | O | 189 |
| 9 | 17 | Fast-stop (N.C.) | Open: Decelerates according to C1-09 (Fast-stop Time) | O | O | O | 188 |
| 10 | 18 | Timer Function Input | Set the timer delay using parameters b4-01 and b4-02. Ensure this function is set in conjunction with the multi-function output timer (H2-□□ = 12). | O | O | O | 189 |
| 11 | 19 | PID Disable | Closed: PID control disabled | O | O | O | 189 |
| 12 | 1A | Accel/Decel Time Selection 2 | Switches Accel/Decel times. | O | O | O | 189 |
| 13 | 1B | Program Lockout | Open: Parameters can not be edited. (except U1-01 if reference source is set for operator) Closed: Parameters may be edited and saved. | O | O | O | 189 |
| 14 | 1E | Reference Sample Hold | Closed: Samples the analog frequency reference and operates the drive at that speed. | O | O | O | 190 |
| 15 | 20 to 2F | External Fault | 20: N.O., Always Detected, Ramp To Stop 21: N.C., Always Detected, Ramp To Stop 22: N.O., During Run, Ramp To Stop 23: N.C., During Run, Ramp To Stop 24: N.O., Always Detected, Coast To Stop 25: N.C., Always Detected, Coast To Stop 26: N.O., During Run, Coast To Stop 27: N.C., During Run, Coast To Stop 28: N.O., Always Detected, Fast-stop 29: N.C., Always Detected, Fast-stop 2A: N.O., During Run, Fast-stop 2B: N.C., During Run, Fast-stop 2C: N.O., Always Detected, Alarm Only (continue running) 2D: N.C., Always Detected, Alarm Only (continue running) 2E: N.O., During Run, Alarm Only (continue running) 2F: N.C., During Run, Alarm Only (continue running) | O | O | O | 190 |
| 16 | 30 | PID Integral Reset | Closed: Resets the PID control integral value. | O | O | O | 191 |
| 17 | 31 | PID Integral Hold | Closed: Maintains the current PID control integral value. | O | O | O | 191 |
| 18 | 32 | Multi-Step Speed Reference 4 | Used to select Multi-Step Speeds set in d1-01 to d1-16 | O | O | O | 191 |
| 19 | 34 | PID Soft Starter | Closed: Disables the PID soft starter b5-17. | O | O | O | 191 |
| 20 | 35 | PID Input Switch | Closed: Inverses the PID input signal | O | O | O | 191 |
| 21 | 40 | Forward Run Command (2-Wire sequence) | Open: Stop Closed: Forward run Note: Can not be set together with Settings 42 or 43. | O | O | O | 191 |
| 22 | 41 | Reverse Run Command (2-Wire sequence) | Open: Stop Closed: Reverse run Note: Can not be set together with Settings 42 or 43. | O | O | O | 191 |
| 23 | 42 | Run Command (2-Wire sequence 2) | Open: Stop Closed: Run Note: Can not be set together with Settings 40 or 41. | O | O | O | 191 |
| 24 | 43 | FWD/REV Command (2-Wire sequence 2) | Open: Forward Closed: Reverse Note: Can not be set together with Settings 40 or 41. | O | O | O | 191 |
Manual — Digital input continuations and outputs — page 378
Source reference: SIEP C71060618F, December 2016, physical PDF page 378. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
H1 Multi-Function Digital Input Selections
H1-□□ Setting Function Description
Control Mode
Control modes: V/f, OLV, PM; Pg.
OLV
PM
<1> Available in drive software versions PRG: 1016 and later.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
H2: Multi-Function Digital Outputs Use H2 parameters to assign functions to the multi-function digital outputs.
B.2 Parameter Table
44 | Offset Frequency 1 Addition
45 | Offset Frequency 2 Addition
46 | Offset Frequency 3 Addition
47 <1> | Node Setup
60 | DC Injection Braking Command
61 | External Search Command 1
62 | External Search Command 2
65 | KEB Ride-Thru 1 (N.C.)
66 | KEB Ride-Thru 1 (N.O.)
67 | Communications Test Mode
68 | High-Slip Braking
6A | Drive Enable
75 | Up 2 Command
76 | Down 2 Command
7A | KEB Ride-Thru 2 (N.C.)
7B | KEB Ride-Thru 2 (N.O.)
7C | Short-Circuit Braking (N.O.)
7D | Short-Circuit Braking (N.C.)
7E | Forward/Reverse Detection
90 to 96 | DWEZ Digital Inputs 1 to 7
9F | DriveWorksEZ enable
H2-01 | Terminal MA, MB and MC Function Selection (relay)
H2-02 | Terminal P1 Function Selection (open- collector)
H2-03 | Terminal P2 Function Selection (open- collector)
Multi-function selections PDF378 — PDF page 378
| Source row | Function setting | Function | Description | Control mode V/f | Control mode OLV | Control mode PM | Reference page |
|---|---|---|---|---|---|---|---|
| 1 | 44 | Offset Frequency 1 Addition | Closed: Adds d7-01 to the frequency reference. | O | O | O | 192 |
| 2 | 45 | Offset Frequency 2 Addition | Closed: Adds d7-02 to the frequency reference. | O | O | O | 192 |
| 3 | 46 | Offset Frequency 3 Addition | Closed: Adds d7-03 to the frequency reference. | O | O | O | 192 |
| 4 | 47 <1> | Node Setup | Closed: Node setup for SI-S3/V enabled. | O | O | O | 192 |
| 5 | 60 | DC Injection Braking Command | Closed: Triggers DC Injection Braking (b2-02) | O | O | - | 192 |
| 6 | 61 | External Search Command 1 | Closed: Activates Current Detection Speed Search from the max. output frequency (E1-04) if b3-01 = 0. Activates Speed Estimation Type Speed search if b3-01 = 0. | O | O | O | 192 |
| 7 | 62 | External Search Command 2 | Closed: Activates Current Detection Speed Search from the frequency reference b3-01 = 0. Activates Speed Estimation Type Speed search if b3-01 = 0. | O | O | O | 192 |
| 8 | 65 | KEB Ride-Thru 1 (N.C.) | Open: KEB Ride-Thru 1 enabled Closed: Normal operation | O | O | O | 192 |
| 9 | 66 | KEB Ride-Thru 1 (N.O.) | Open: Normal operation Closed: KEB Ride-Thru 1 enabled | O | O | O | 192 |
| 10 | 67 | Communications Test Mode | Tests the MEMOBUS/Modbus RS-485/422 interface. | O | O | O | 192 |
| 11 | 68 | High-Slip Braking | Closed: High-Slip braking is executed. Drive stops. | O | - | - | 192 |
| 12 | 6A | Drive Enable | Open: Drive disabled. If this input is opened during run, then the drive will stop as specified by parameter b1-03. Closed: Ready for operation. | O | O | O | 192 |
| 13 | 75 | Up 2 Command | Open: Maintains the current frequency reference. Closed: Increases or decreases the frequency reference. UP 2 and Down 2 commands must be set in combination with each other. The frequency reference source must be assigned to the operator (b1-01 = “0”). | O | O | O | 193 |
| 14 | 76 | Down 2 Command | Open: Maintains the current frequency reference. Closed: Increases or decreases the frequency reference. UP 2 and Down 2 commands must be set in combination with each other. The frequency reference source must be assigned to the operator (b1-01 = “0”). | O | O | O | 193 |
| 15 | 7A | KEB Ride-Thru 2 (N.C.) | Open: KEB Ride-Thru 2 enabled Closed: Normal operation | O | O | O | 194 |
| 16 | 7B | KEB Ride-Thru 2 (N.O.) | Open: Normal operation Closed: KEB Ride-Thru 2 enabled | O | O | O | 194 |
| 17 | 7C | Short-Circuit Braking (N.O.) | Open: Normal operation Closed: Short-Circuit Braking | - | - | O | 194 |
| 18 | 7D | Short-Circuit Braking (N.C.) | Open: Short-Circuit Braking Closed: Normal operation | - | - | O | 194 |
| 19 | 7E | Forward/Reverse Detection | Direction of rotation detection (for V/f with Simple PG Feedback) | O | - | - | 194 |
| 20 | 90 to 96 | DWEZ Digital Inputs 1 to 7 | Reserved for DWEZ input functions | O | O | O | 194 |
| 21 | 9F | DriveWorksEZ enable | Open: DWEZ enabled Closed: DWEZ disabled | O | O | O | 194 |
Parameter catalogue PDF378 section2 — PDF page 378
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | H2-01 | Terminal MA, MB and MC Function Selection (relay) | Refer to H2 Multi-Function Digital Output Settings on page 379 for a description of setting values. | 0 to 192 <1> | E | A | A | A | 40B | 195 |
| 2 | H2-02 | Terminal P1 Function Selection (open- collector) | Refer to H2 Multi-Function Digital Output Settings on page 379 for a description of setting values. | 0 to 192 <1> | 0 | A | A | A | 40C | 195 |
| 3 | H2-03 | Terminal P2 Function Selection (open- collector) | Refer to H2 Multi-Function Digital Output Settings on page 379 for a description of setting values. | 0 to 192 <1> | 2 | A | A | A | 40D | 195 |
Manual — Digital output settings and functions — page 379
Source reference: SIEP C71060618F, December 2016, physical PDF page 379. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
<1> The availability of certain functions depends on the control method used.
H2 Multi-Function Digital Output Settings
H2-□□ Setting Function Description
Control Mode
Control modes: V/f, OLV, PM; Pg.
B.2 Parameter Table
B
Parameter List
H2-06 | Watt Hour Output Unit Selection
0 | During Run
1 | Zero Speed
2 | Speed Agree 1
3 | User Set Speed Agree 1
4 | Frequency Detection 1
5 | Frequency Detection 2
6 | Drive Ready
7 | DC Bus Undervoltage
8 | During Baseblock (N.O.)
9 | Frequency reference selection
A | Run command selection
B | Torque Detection 1 (N.O.)
C | Frequency Reference Loss
D | Braking Resistor Fault
E | Fault
F | Not used/Through Mode
10 | Minor Fault
11 | Reset Command Active
12 | Timer Output
13 | Speed Agree 2
14 | User Set Speed Agree 2
15 | Frequency Detection 3
16 | Frequency Detection 4
Parameter catalogue PDF379 section1 — PDF page 379
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | H2-06 | Watt Hour Output Unit Selection | Sets the output units for the watt hours when Watt Hour Pulse Output is selected as the digital output (H2-01, H2-02, or H2-03 = 39). Outputs a 200 ms pulse signal when the watt- hour counter increases by the units selected. 0: 0.1 kWh units 1: 1 kWh units 2: 10 kWh units 3: 100 kWh units 4: 1000 kWh units | 0 to 4 | 0 | A | A | A | 437 | 204 |
Multi-function selections PDF379 — PDF page 379
| Source row | Function setting | Function | Description | Control mode V/f | Control mode OLV | Control mode PM | Reference page |
|---|---|---|---|---|---|---|---|
| 1 | 0 | During Run | Closed: A Run command is active or voltage is output. | O | O | O | 195 |
| 2 | 1 | Zero Speed | Closed: Output frequency is 0. | O | O | O | 196 |
| 3 | 2 | Speed Agree 1 | Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02). | O | O | O | 196 |
| 4 | 3 | User Set Speed Agree 1 | Closed: Output frequency and speed reference equal the value in L4-01 (plus or minus the hysteresis of L4-02). | O | O | O | 196 |
| 5 | 4 | Frequency Detection 1 | Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined by L4-02. | O | O | O | 197 |
| 6 | 5 | Frequency Detection 2 | Closed: Output frequency is greater than or equal to the value in L4-01, with hysteresis determined by L4-02. | O | O | O | 197 |
| 7 | 6 | Drive Ready | Closed: Drive Ready. The drive is powered up, not in a fault state, and in the Drive mode. | O | O | O | 198 |
| 8 | 7 | DC Bus Undervoltage | Closed: DC bus voltage is below the Uv trip level set in L2-05. | O | O | O | 198 |
| 9 | 8 | During Baseblock (N.O.) | Closed: There is no output voltage | O | O | O | 198 |
| 10 | 9 | Frequency reference selection | Open: External Reference 1 or 2 supplies the frequency reference Closed: Digital operator supplies the frequency reference. | O | O | O | 198 |
| 11 | A | Run command selection | Open: External Reference 1 or 2 supplies the Run command Closed: Digital operator supplies the Run command. | O | O | O | 198 |
| 12 | B | Torque Detection 1 (N.O.) | Closed: Output current/torque exceeds the torque value set in parameter L6-02 for longer than the time set in parameter L6-03. | O | O | O | 198 |
| 13 | C | Frequency Reference Loss | Closed: Loss of the analog frequency reference detected. Enabled when L4-05 = 1. | O | O | O | 199 |
| 14 | D | Braking Resistor Fault | Closed: Braking resistor or transistor is overheated or faulted out. This selection requires that braking resistor protection parameter be set for ERF (L8-01 = “1”). | O | O | O | 199 |
| 15 | E | Fault | Closed: Fault occurred (other than CPF00 and CPF01). | O | O | O | 199 |
| 16 | F | Not used/Through Mode | Set this value when the terminal is not used, or when using the terminal in the pass- through mode. | O | O | O | 199 |
| 17 | 10 | Minor Fault | Closed: An alarm is triggered. | O | O | O | 199 |
| 18 | 11 | Reset Command Active | Closed: The drive has received a reset command from the multi-function input terminals or from serial network, or the digital operator RESET key has been pressed. | O | O | O | 199 |
| 19 | 12 | Timer Output | Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital input (H1-□□ = 18 “timer function”). | O | O | O | 199 |
| 20 | 13 | Speed Agree 2 | Closed: When drive output frequency equals the frequency reference +/- L4-04. | O | O | O | 199 |
| 21 | 14 | User Set Speed Agree 2 | Closed: When the drive output frequency is equal to the value in L4-03 (plus or minus L4-04). | O | O | O | 200 |
| 22 | 15 | Frequency Detection 3 | Closed: When the drive output frequency is less than or equal to the value in L4-03 with the hysteresis determined by L4-04. | O | O | O | 200 |
| 23 | 16 | Frequency Detection 4 | Closed: When the output frequency is greater than or equal to the value in L4-03 with the hysteresis determined by L4-04. | O | O | O | 201 |
Manual — Output function continuations — page 380
Source reference: SIEP C71060618F, December 2016, physical PDF page 380. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
H2 Multi-Function Digital Output Settings
H2-□□ Setting Function Description
Control Mode
Control modes: V/f, OLV, PM; Pg.
OLV
PM
<1> Available in drive software versions PRG: 1016 and later.
B.2 Parameter Table
17 | Torque Detection 1 (N.C.)
18 | Torque Detection 2 (N.O.)
19 | Torque Detection 2 (N.C.)
1A | Reverse Direction
1B | During Baseblock (N.C.)
1C | Motor 2 Selection
1E | Restart Enabled
1F | Overload Alarm oL1
20 | oH Pre alarm
22 | Mechanical Weakening (N.O.)
2F <1> | Maintenance Period
30 | During Torque Limit
37 | During Frequency Output
38 | Drive Enable
39 | Watt Hour Pulse Output
3C | LOCAL/REMOTE Status
3D | Speed Search
3E | PID Feedback Loss Low
3F | PID Feedback Loss High
4A | KEB Operation
4B | Short-Circuit Brake
4C | During Fast-stop
4D | oH Pre-alarm Time Limit
4E <1> | Braking Transistor Fault (rr)
4F <1> | Braking Resistor Overheat (oH)
90 to 92 | DWEZ Digital Outputs 1 to 3
100 to 192 | H2 Parameter Functions Reversed Output Switching of 0 to 92
Multi-function selections PDF380 — PDF page 380
| Source row | Function setting | Function | Description | Control mode V/f | Control mode OLV | Control mode PM | Reference page |
|---|---|---|---|---|---|---|---|
| 1 | 17 | Torque Detection 1 (N.C.) | Open: When the output current/torque exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03. | O | O | O | 198 |
| 2 | 18 | Torque Detection 2 (N.O.) | Closed: When the output current/torque exceeds the value set in parameter L6-05 for more time than is set in parameter L6-06. | O | O | O | 198 |
| 3 | 19 | Torque Detection 2 (N.C.) | Open: Output current/torque exceeds the value set in parameter L6-05 for more time than is set in parameter L6-06. | O | O | O | 198 |
| 4 | 1A | Reverse Direction | Closed: Drive is running in the reverse direction. | O | O | O | 201 |
| 5 | 1B | During Baseblock (N.C.) | Open: Drive is in Baseblock condition. Output is disabled. | O | O | O | 202 |
| 6 | 1C | Motor 2 Selection | Closed: Motor 2 is selected by a digital input (H1-□□ = 16) | O | O | − | 202 |
| 7 | 1E | Restart Enabled | Closed: An automatic restart is performed | O | O | O | 202 |
| 8 | 1F | Overload Alarm oL1 | Closed: oL1 is at 90% of its trip point or greater. | O | O | O | 202 |
| 9 | 20 | oH Pre alarm | Closed: Heatsink temperature exceeds the parameter L8-02 value. | O | O | O | 202 |
| 10 | 22 | Mechanical Weakening (N.O.) | Closed: Mechanical Weakening detected. | O | O | O | 202 |
| 11 | 2F <1> | Maintenance Period | Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require maintenance. | O | O | O | 202 |
| 12 | 30 | During Torque Limit | Closed: When the torque limit has been reached. | − | O | − | 202 |
| 13 | 37 | During Frequency Output | Open: No frequency output from drive if stopped, with baseblock, with DC injection braking during initial excitation, or with short-circuit braking. Closed: Drive is outputting a frequency | O | O | O | 202 |
| 14 | 38 | Drive Enable | Closed: Multi-function input closes (H1-□□ = 6A) | O | O | O | 203 |
| 15 | 39 | Watt Hour Pulse Output | Output units are determined by H2-06, outputs 200 ms pulse for each incremented kWh count. | O | O | O | 203 |
| 16 | 3C | LOCAL/REMOTE Status | Closed: LOCAL Open: REMOTE | O | O | O | 203 |
| 17 | 3D | Speed Search | Closed: Speed search is being executed. | O | O | O | 203 |
| 18 | 3E | PID Feedback Loss Low | Closed: PID Feedback Loss Low. PID feedback value is below the level set to b5-13 for longer than the time set in b5-14. | O | O | O | 203 |
| 19 | 3F | PID Feedback Loss High | Closed: PID Feedback Loss High. PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37. | O | O | O | 203 |
| 20 | 4A | KEB Operation | Closed: KEB is being performed. | O | O | O | 203 |
| 21 | 4B | Short-Circuit Brake | Closed: Short-Circuit Braking is active. | − | − | O | 203 |
| 22 | 4C | During Fast-stop | Closed: Fast-stop command is entered | O | O | O | 203 |
| 23 | 4D | oH Pre-alarm Time Limit | Closed: oH Pre-alarm time limit is passed. | O | O | O | 203 |
| 24 | 4E <1> | Braking Transistor Fault (rr) | Closed: The built-in dynamic braking transistor failed. | O | O | O | 203 |
| 25 | 4F <1> | Braking Resistor Overheat (oH) | Closed: The dynamic braking resistor has overheated. | O | O | O | 203 |
| 26 | 90 to 92 | DWEZ Digital Outputs 1 to 3 | Reserved for DWEZ digital output functions. | O | O | O | 204 |
| 27 | 100 to 192 | H2 Parameter Functions Reversed Output Switching of 0 to 92 | Reverse the output switching of the multi-function output functions. Set the last two digits of 1□□ to reverse the output signal of that specific function. Examples: Setting “108” reverses the output of “During baseblock,” which is setting value 08. Setting “14A” reverses the output of “During KEB operation”, which is setting “4A”. | O | O | O | 204 |
Manual — Analog input parameters and selections — page 381
Source reference: SIEP C71060618F, December 2016, physical PDF page 381. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
H3: Analog Inputs Use H3 parameters to set the multi-function analog input terminals.
Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
<1> The availability of certain parameters depends on the control method used. <2> Parameter can be changed during Run. <3> Parameter available in drive software versions PRG: 1016 and later.
H3 Multi-Function Analog Input Settings
H3-□□ Setting Function Maximum Input Level Possible
Control Mode
Control modes: V/f, OLV, PM; Pg.
B.2 Parameter Table
B
Parameter List
H3-01 | Terminal A1 Signal Level Selection
H3-02 | Terminal A1 Function Selection
H3-03 <2> | Terminal A1 Gain Setting
H3-04 <2> | Terminal A1 Bias Setting
H3-09 | Terminal A2 Signal Level Selection
H3-10 | Terminal A2 Function Selection
H3-11 <2> | Terminal A2 Gain Setting
H3-12 <2> | Terminal A2 Bias Setting
H3-13 | Analog Input Filter Time Constant
H3-14 <3> | Analog Input Terminal Enable Selection
H3-16 <3> | Terminal A1 Offset
H3-17 <3> | Terminal A2 offset
0 | Frequency Bias
1 | Frequency Gain
2 | Auxiliary Frequency Reference (used as a Multi-Step Speed 2)
4 | Output Voltage Bias
7 | Overtorque/Undertorque Detection Level
B | PID Feedback
Parameter catalogue PDF381 section1 — PDF page 381
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | H3-01 | Terminal A1 Signal Level Selection | Sets the input level for terminal A1. 0: 0 to +10 V (lower limit) 1: 0 to +10 V (no lower limit) | 0, 1 | 0 | A | A | A | 410 | 204 |
| 2 | H3-02 | Terminal A1 Function Selection | Sets the function of terminal A1. When terminal A1 is not used or is used as a through terminal, this parameter must be set to “F”. | 0 to 31 <1> | 0 | A | A | A | 434 | 205 |
| 3 | H3-03 <2> | Terminal A1 Gain Setting | Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1. | -999.9 to 999.9 | 100.0 % | A | A | A | 411 | 205 |
| 4 | H3-04 <2> | Terminal A1 Bias Setting | Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1. | -999.9 to 999.9 | 0.0% | A | A | A | 412 | 205 |
| 5 | H3-09 | Terminal A2 Signal Level Selection | Sets the input signal level for terminal A2. 0: 0 to +10 V (with lower limit) 1: 0 to +10 V (no lower limit) 2: 4 to 20 mA 3: 0 to 20 mA | 0 to 3 | 2 | A | A | A | 417 | 207 |
| 6 | H3-10 | Terminal A2 Function Selection | Sets the function of terminal A2. When terminal A2 is not used or is used as a through terminal, this parameter must be set to “F”. | 0 to 31 <1> | 0 | A | A | A | 418 | 207 |
| 7 | H3-11 <2> | Terminal A2 Gain Setting | Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input at terminal A2. | -999.9 to 999.9 | 100.0 % | A | A | A | 419 | 207 |
| 8 | H3-12 <2> | Terminal A2 Bias Setting | Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is input at terminal A2. | -999.9 to 999.9 | 0.0% | A | A | A | 41A | 207 |
| 9 | H3-13 | Analog Input Filter Time Constant | Sets the primary delay filter time constant for terminals A1 and A2. Used for noise filtering. | 0.00 to 2.00 | 0.03 s | A | A | A | 41B | 207 |
| 10 | H3-14 <3> | Analog Input Terminal Enable Selection | Determines which analog input terminal will be enabled when a digital input programmed for “Analog input enable” (H1- oo = C) is activated. 1: Terminal A1 only 2: Terminal A2 only 7: All terminals enabled | 1, 2, 7 | 7 | A | A | A | 41C | 209 |
| 11 | H3-16 <3> | Terminal A1 Offset | Enter a 0 V signal to terminal A1. Next adjust the offset in H3-16 until the monitor U1-13 for the terminal A1 input voltage reads 0.0%. The process is the same for terminal A2. | -500 to 500 | 0 | A | A | A | 440 | 209 |
| 12 | H3-17 <3> | Terminal A2 offset | Enter a 0 V signal, and adjust the offset for terminal A2 in H3-17 until the monitor U1-14 for terminal A2 input voltage reads 0.0%. | -500 to 500 | 0 | A | A | A | 441 | 209 |
Multi-function selections PDF381 — PDF page 381
| Source row | Function setting | Function | Maximum input level possible | Control mode V/f | Control mode OLV | Control mode PM | Reference page |
|---|---|---|---|---|---|---|---|
| 1 | 0 | Frequency Bias | Max output frequency (E1-04). Same value can be set using H3-02 and H3-10. | O | O | O | 208 |
| 2 | 1 | Frequency Gain | 10 V = 100% | O | O | O | 208 |
| 3 | 2 | Auxiliary Frequency Reference (used as a Multi-Step Speed 2) | Maximum output frequency (E1-04) | O | O | O | 208 |
| 4 | 4 | Output Voltage Bias | Motor rated voltage (E1-05). | O | – | − | 208 |
| 5 | 7 | Overtorque/Undertorque Detection Level | Open Loop Vector: Motor rated torque V/f Control: Drive rated current | O | O | O | 208 |
| 6 | B | PID Feedback | 10 V = 100% | O | O | O | 208 |
Manual — Analog output and communication parameters — page 382
Source reference: SIEP C71060618F, December 2016, physical PDF page 382. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
H3 Multi-Function Analog Input Settings
H3-□□ Setting Function Maximum Input Level Possible
Control Mode
Control modes: V/f, OLV, PM; Pg.
OLV
PM
<1> Parameter available in drive software versions PRG: 1016 and later.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
H4: Multi-Function Analog Outputs Use H4 parameters to configure the multi-function analog output terminals.
H5: MEMOBUS/Modbus Communications Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network. The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.
B.2 Parameter Table
C | PID Set Point
E | Motor Temperature (PTC input)
F | Not used/Through Mode
10 | FWD Torque Limit
11 | REV Torque Limit
12 | Regenerative Torque Limit
15 | FWD/REV Torque Limit
16 | Differential PID Feedback
30/31 | DWEZ Analog Input 1/2
41 <1> | Output Voltage Gain
H4-01 | Multi-Function Analog Output Terminal AM
H4-02 <2> | Multi-Function Analog Output Terminal AM Gain
H4-03 <2> | Multi-Function Analog Output Terminal AM Bias
H5-01 <3> | Drive Node Address
H5-02 | Communication Speed Selection
H5-03 | Communication Parity Selection
Multi-function selections PDF382 — PDF page 382
| Source row | Function setting | Function | Maximum input level possible | Control mode V/f | Control mode OLV | Control mode PM | Reference page |
|---|---|---|---|---|---|---|---|
| 1 | C | PID Set Point | 10 V = 100% | O | O | O | 208 |
| 2 | E | Motor Temperature (PTC input) | 10 V = 100.00% | O | O | O | 208 |
| 3 | F | Not used/Through Mode | – | O | O | O | 209 |
| 4 | 10 | FWD Torque Limit | Motor rated torque | − | O | − | 209 |
| 5 | 11 | REV Torque Limit | Motor rated torque | − | O | − | 209 |
| 6 | 12 | Regenerative Torque Limit | Motor rated torque | − | O | − | 209 |
| 7 | 15 | FWD/REV Torque Limit | Motor rated torque | − | O | − | 209 |
| 8 | 16 | Differential PID Feedback | 10 V = 100% | O | O | O | 209 |
| 9 | 30/31 | DWEZ Analog Input 1/2 | Depending on function. | O | O | O | 209 |
| 10 | 41 <1> | Output Voltage Gain | 10 V = 100% | O | − | − | 209 |
Parameter catalogue PDF382 section2 — PDF page 382
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | H4-01 | Multi-Function Analog Output Terminal AM | Selects the data to be output through multi-function analog output terminal AM. Set the desired monitor parameter to the digits available in U□-□□. For example, enter “103” for U1-03. When using this terminal in through mode or when not using it at all, set “000” or “031”. | 000 to 999 <1> | 102 | A | A | A | 41D | 210 |
| 2 | H4-02 <2> | Multi-Function Analog Output Terminal AM Gain | Sets terminal AM output gain. Maximum output voltage is 10 V. | -999.9 to 999.9 | 100.0 % | S | S | S | 41E | 210 |
| 3 | H4-03 <2> | Multi-Function Analog Output Terminal AM Bias | Sets terminal AM output bias. | -999.9 to 999.9 | 0.0% | A | A | A | 41F | 210 |
| 4 | H5-01 <3> | Drive Node Address | Selects drive station node number (address) for MEMOBUS/ Modbus terminals R+, R-, S+, S-. Cycle power for the setting to take effect. | 0 to 20 H | 1F | A | A | A | 425 | 439 |
| 5 | H5-02 | Communication Speed Selection | Selects the baud rate for MEMOBUS/Modbus terminals R+, R-, S+ and S-. Cycle power for the setting to take effect. 0 : 1200 bps 1 : 2400 bps 2 : 4800 bps 3 : 9600 bps 4 : 19200 bps 5 : 38400 bps 6 : 57600 bps 7 : 76800 bps 8 : 115200 bps | 0 to 8 | 3 | A | A | A | 426 | 439 |
| 6 | H5-03 | Communication Parity Selection | Selects the communication parity for MEMOBUS/Modbus terminals R+, R-, S+ and S-. Cycle power for the setting to take effect. 0: No parity 1: Even parity 2: Odd parity | 0 to 2 | 0 | A | A | A | 427 | 439 |
Manual — Communications and pulse I/O — page 383
Source reference: SIEP C71060618F, December 2016, physical PDF page 383. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
H6: Pulse Train Input/Output Use H6 parameters to configure Pulse Train I/O operation.
<1> The availability of certain functions depends on the control method used. <2> Parameter can be changed during Run. <3> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands. <4> Default setting is determined by drive software version. PRG: 1016 and later: 100 to 32000 Hz
B.2 Parameter Table
B
Parameter List
H5-04 | Stopping Method After Communication Error
H5-05 | Communication Fault Detection Selection
H5-06 | Drive Transmit Wait Time
H5-07 | RTS Control Selection
H5-09 | CE Detection Time
H5-10 | Unit Selection for MEMOBUS/Modbus Register 0025H
H5-11 | Communications ENTER Function Selection
H5-12 | Run Command Method Selection
H6-01 | Pulse Train Input Terminal RP Function Selection
H6-02 <2> | Pulse Train Input Scaling
H6-03 <2> | Pulse Train Input Gain
H6-04 <2> | Pulse Train Input Bias
H6-05 <2> | Pulse Train Input Filter Time
H6-06 <2> | Pulse Train Monitor Terminal MP Selection
H6-07 <2> | Pulse Train Monitor Scaling
Parameter catalogue PDF383 section1 — PDF page 383
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | H5-04 | Stopping Method After Communication Error | Selects the stopping method when a communication time-out fault (CE) is detected. 0: Ramp to stop 1: Coast to stop 2: Fast-stop 3: Alarm only | 0 to 3 | 3 | A | A | A | 428 | 439 |
| 2 | H5-05 | Communication Fault Detection Selection | Enables or disables the communications time-out fault (CE) detection. 0: Disabled 1: Enabled - If communication is lost for more than two seconds, a CE fault will occur. | 0, 1 | 1 | A | A | A | 429 | 440 |
| 3 | H5-06 | Drive Transmit Wait Time | Set the wait time between receiving and sending data. | 5 to 65 | 5 ms | A | A | A | 42A | 440 |
| 4 | H5-07 | RTS Control Selection | Selects "request to send" (RTS) control: 0: Disabled - RTS is always on. 1: Enabled - RTS turns on only when sending. | 0, 1 | 1 | A | A | A | 42B | 440 |
| 5 | H5-09 | CE Detection Time | Sets the time required to detect a communications error. Adjustment may be need when networking several drives. | 0.0 to 10.0 s | 2.0 s | A | A | A | 435 | 440 |
| 6 | H5-10 | Unit Selection for MEMOBUS/Modbus Register 0025H | Selects the units used for MEMOBUS/Modbus register 0025H (Output Voltage Reference Monitor). 0: 0.1 V units 1: 1 V units | 0, 1 | 0 | A | A | A | 436 | 440 |
| 7 | H5-11 | Communications ENTER Function Selection | Select the function for the enter command that saves parameter data to the drive. 0: Parameter changes are activated when ENTER command is entered. 1: Parameter changes are activated immediately without ENTER command (compatible with Varispeed VS606-V7). | 0, 1 | 1 | A | A | A | 43C | 441 |
| 8 | H5-12 | Run Command Method Selection | 0: FWD/STOP, REV/STOP Method 1: RUN/STOP, FWD/REV Method | 0, 1 | 0 | A | A | A | 43D | 441 |
| 9 | H6-01 | Pulse Train Input Terminal RP Function Selection | Selects pulse train input function. 0: Frequency reference 1: PID feedback value 2: PID setpoint value 3: V/f Control with Simple PG Feedback (can be set only when using motor 1 in V/f Control) | 0 to 3 | 0 | A | A | A | 42C | 211 |
| 10 | H6-02 <2> | Pulse Train Input Scaling | Sets 100% the of terminal the value RP selected input signal in H6-01. frequency that is equal to | <4> | 1440 Hz | A | A | A | 42D | 211 |
| 11 | H6-03 <2> | Pulse Train Input Gain | Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is input. | 0.0 to 1000.0 | 100.0 % | A | A | A | 42E | 211 |
| 12 | H6-04 <2> | Pulse Train Input Bias | Sets the level of the value selected in H6-01 when 0 Hz is input. | -100.0 to +100.0 | 0.0% | A | A | A | 42F | 211 |
| 13 | H6-05 <2> | Pulse Train Input Filter Time | Sets the pulse train input filter time constant. | 0.00 to 2.00 | 0.10 s | A | A | A | 430 | 211 |
| 14 | H6-06 <2> | Pulse Train Monitor Terminal MP Selection | Select the pulse train monitor output function (value of the o-□□ part of U□-□□). Refer to U: Monitors on page 399 for the list of U monitors. Example: To select U5-01, set “501. ”When not using this parameter or when using in the through mode, set “000”. <5> | 000, 031, 101, 102, 501, 105, 502; 116, 801 to 809 | 102 | A | A | A | 431 | 212 |
| 15 | H6-07 <2> | Pulse Train Monitor Scaling | Sets the terminal MP output signal frequency when the monitor value is 100%. Set H6-06 to 102 and H6-07 to 0 to make the pulse train monitor output equal to the output frequency. | 0 to 32000 | 1440 Hz | A | A | A | 432 | 212 |
Manual — Pulse electrical notes and motor protection — page 384
Source reference: SIEP C71060618F, December 2016, physical PDF page 384. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
PRG: 1015 and earlier: 1000 to 32000 Hz <5> When set for sourcing, +5 V/1.5 kΩ or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher. When set for sinking, the external power supply should be +12 Vdc, ±5% with 16 mA or less.
Note: Cycle power to the drive to enable MEMOBUS/Modbus settings.
◆ L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary power loss, Stall Prevention, frequency detection, fault restarts, overtorque detection, torque limits and other types of hardware protection.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
L1: Motor Protection Functions Use L1 parameters to configure motor protective functions.
L2: Momentary Power Loss Use L2 parameters to configure drive functions for momentary power loss conditions.
B.2 Parameter Table
L1-01 | Motor Overload Protection Selection
L1-02 | Motor Overload Protection Time
L1-03 | Motor Overheat Alarm Operation Selection (PTC input)
L1-04 | Motor Overheat Fault Operation Selection (PTC input)
L1-05 | Motor Temperature Input Filter Time (PTC input)
L1-13 | Continuous Electrothermal Operation Selection
L1-22 <16> <17> | Leakage Current Filter Time Constant 1
L1-23 <16> <17> | Leakage Current Filter Time Constant 2
Parameter catalogue PDF384 section1 — PDF page 384
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L1-01 | Motor Overload Protection Selection | Sets the motor thermal overload protection (oL1) based on the cooling capacity of the motor. 0: Disabled 1: General Purpose Motor (Standard Fan Cooled) 2: Drive Dedicated Motor with a Speed Range of 1:10 3: Vector Motor with a Speed Range of 1:100 4: PM Motor with Variable Torque 6: General Purpose Motor (50 Hz) <1> Note: When using multiple motors the drive may not be able to provide protection, even if overload is enabled in L1-01. Set L1-01 to 0 and ensure each motor has separate thermal relays installed. | 0 to 4; 6 | 1 <2> | S | S | S | 480 | 213 |
| 2 | L1-02 | Motor Overload Protection Time | Sets the motor thermal overload protection (oL1) time. A larger L1-02 time will increase the time for an oL1 fault to occur. This parameter does not typically require adjustment. Should be set in accordance with the overload tolerance of the motor. | 0.1 to 20.0 | 8.0 min | A | A | A | 481 | 215 |
| 3 | L1-03 | Motor Overheat Alarm Operation Selection (PTC input) | Sets operation when the motor temperature analog input (H3-02/10 = E) exceeds the oH3 alarm level. 0: Ramp to Stop 1: Coast to Stop 2: Fast-stop using C1-09 3: Alarm Only (“oH3” will flash) | 0 to 3 | 3 | A | A | A | 482 | 216 |
| 4 | L1-04 | Motor Overheat Fault Operation Selection (PTC input) | Sets stopping method when the motor temperature analog input (H3-02/10 = E) exceeds the oH4 fault level. 0: Ramp to Stop 1: Coast to Stop 2: Fast-stop | 0 to 2 | 1 | A | A | A | 483 | 217 |
| 5 | L1-05 | Motor Temperature Input Filter Time (PTC input) | This parameter adjusts the filter on the motor temperature analog input (H3-02 or H3-10 = E). Increase to add stability, decrease to improve response. | 0.00 to 10.00 | 0.20 s | A | A | A | 484 | 217 |
| 6 | L1-13 | Continuous Electrothermal Operation Selection | Determines whether or not to hold the electrothermal value when the power supply is interrupted. 0: Disabled 1: Enabled | 0, 1 | 1 | A | A | A | 46D | 217 |
| 7 | L1-22 <16> <17> | Leakage Current Filter Time Constant 1 | Sets the time constant for reducing the sensitivity level when detecting leakage current. Set in seconds and used when operating at constant speed. Note: This parameter is available only when C6-02 is set to B. To display this parameter, first set C6-02 = B. | 0.0 to 60.0 | 20.0 s | A | A | A | 768 | 217 |
| 8 | L1-23 <16> <17> | Leakage Current Filter Time Constant 2 | Sets the time constant for reducing the sensitivity level when detecting leakage current. Set in seconds and used during acceleration and deceleration operation. Note: This parameter is available only when C6-02 is set to B. To display this parameter, first set C6-02 = B. | 0.0 to 60.0 | 1.0 s | A | A | A | 769 | 217 |
Manual — Power loss and acceleration stall prevention — page 385
Source reference: SIEP C71060618F, December 2016, physical PDF page 385. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
For a restart to occur, the run command must be maintained throughout the Ride- Thru period.
L3: Stall Prevention Function Use L3 parameters to configure the Stall Prevention function.
B.2 Parameter Table
B
Parameter List
L2-01 | Momentary Power Loss Operation Selection
L2-02 | Momentary Power Loss Ride- Thru Time
L2-03 | Momentary Power Loss Minimum Baseblock Time
L2-04 | Momentary Power Loss Voltage Recovery Ramp Time
L2-05 <5> | Undervoltage Detection Level (Uv)
L2-06 | KEB Deceleration Time
L2-07 | KEB Acceleration Time
L2-08 | KEB Start Output Frequency Reduction
L2-11 <5> | Desired DC Bus Voltage during KEB
L3-01 | Stall Prevention Selection during Acceleration
L3-02 | Stall Prevention Level during Acceleration
L3-03 | Stall Prevention Limit during Acceleration
Parameter catalogue PDF385 section1 — PDF page 385
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L2-01 | Momentary Power Loss Operation Selection | Enables and disables the momentary power loss function. 0: Disabled - Drive trips on (Uv1) fault when power is lost. 1: Power Loss Ride-Thru Time - Drive will restart if power returns within the time set in L2-02. 2: CPU Power Active - Drive will restart if power returns as long as the CPU is working. | 0 to 2 | 0 | A | A | A | 485 | 218 |
| 2 | L2-02 | Momentary Power Loss Ride- Thru Time | Sets the Power Loss Ride-Thru time. Only effective when L2-01 = 1. | 0.0 to 25.5 | <3> | A | A | A | 486 | 218 |
| 3 | L2-03 | Momentary Power Loss Minimum Baseblock Time | Sets the minimum wait time for residual motor voltage decay before the drive output reenergizes after power loss Ride-Thru. If L2-03 is greater than L2-02, operation resumes after the time set in L2-03. | 0.1 to 5.0 | <4> | A | A | A | 487 | 218 |
| 4 | L2-04 | Momentary Power Loss Voltage Recovery Ramp Time | Sets the time for the output voltage to return to the preset V/f pattern during Speed Search. | 0.0 to 5.0 | <3> | A | A | A | 488 | 218 |
| 5 | L2-05 <5> | Undervoltage Detection Level (Uv) | Sets the DC Bus undervoltage trip level. If this is set lower than the default setting, additional AC input impedance or DC bus reactance may be necessary. This value is used for KEB activation if L2-01 > 0. | 150 to 210 | <3> <6> | A | A | A | 489 | 218 |
| 6 | L2-06 | KEB Deceleration Time | Sets the time required to decelerate from the speed when KEB was activated to zero speed. | 0.0 to 200.0 | 0.0 s | A | A | A | 48A | 220 |
| 7 | L2-07 | KEB Acceleration Time | Sets the time to accelerate to the frequency reference when momentary power loss is over. If set to 0.0, the active acceleration time (C1-01, C1-03, C1-05, or C1-07) is used. | 0.0 to 25.5 | 0.0 s | A | A | A | 48B | 220 |
| 8 | L2-08 | KEB Start Output Frequency Reduction | Sets the percentage of output frequency reduction at the beginning of deceleration when the KEB function is started. Reduction = (slip frequency before KEB) x (L2-08/100) x 2 | 0 to 300 | 100% | A | A | A | 48C | 221 |
| 9 | L2-11 <5> | Desired DC Bus Voltage during KEB | Sets the desired value of the DC bus voltage during KEB. | 150 to 400 V | E1-01 x 1.22 | A | A | A | 461 | 221 |
| 10 | L3-01 | Stall Prevention Selection during Acceleration | Selects the Stall Prevention method used to prevent excessive current during acceleration. 0: Disabled - Motor accelerates at active acceleration rate. The motor may stall if load is too heavy or accel time is too short. 1: General Purpose - When output current exceeds L3-02 level, acceleration stops. Acceleration will continue when the output current level falls below the L3-02 level. 2: Intelligent - The active acceleration rate is ignored. Acceleration is completed in the shortest amount of time without exceeding the current value set in L3-02. | 0 to 2 <7> | 1 | A | A | A | 48F | 221 |
| 11 | L3-02 | Stall Prevention Level during Acceleration | Used when L3-01 = 1 or 2. 100% is equal to the drive rated current. Decrease the set value if stalling or excessive current occurs with default setting. | 0 to 150 <18> | <8> <18> | A | A | A | 490 | 222 |
| 12 | L3-03 | Stall Prevention Limit during Acceleration | Sets Stall Prevention lower limit during acceleration when operating in the constant power range. Set as a percentage of the drive's rated current. | 0 to 100 | 50% | A | A | A | 491 | 223 |
Manual — Stall prevention and overvoltage suppression — page 386
Source reference: SIEP C71060618F, December 2016, physical PDF page 386. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
B.2 Parameter Table
L3-04 | Stall Prevention Selection during Deceleration
L3-05 | Stall Prevention Selection during Run
L3-06 | Stall Prevention Level during Run
L3-11 | ov Suppression Function Selection
L3-17 <5> | Overvoltage Suppression and Stall Prevention Desired DC Bus Voltage
L3-20 | Main Power Circuit Voltage Adjustment Gain
L3-21 | Accel/Decel Rate Calculation Gain
L3-22 | Deceleration Time at Stall Prevention during Acceleration
Parameter catalogue PDF386 section1 — PDF page 386
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L3-04 | Stall Prevention Selection during Deceleration | When using a braking resistor, use setting "0". Setting "3" is used in specific applications. 0: Disabled - The drive decelerates at the active deceleration rate. If the load is too large or the deceleration time is too short, an ov fault may occur. 1: General Purpose - The drive decelerates at the active deceleration rate, but if the main circuit DC bus voltage reaches the Stall Prevention level, deceleration will stop. Deceleration will continue once the DC bus level drops below the Stall Prevention level. 2: Intelligent - The active deceleration rate is ignored and the drive decelerates as fast as possible without hitting ov fault level. Range: C1-02 / 10. 3: Stall Prevention with Braking Resistor - Stall Prevention during deceleration is enabled in coordination with dynamic braking. 4: Overexcitation Deceleration - Decelerates with the flux level determined by n3-13 (Overexcitation Gain). 7: Overexcitation Deceleration 3 - Applies more braking power than normal overexcitation deceleration. Yaskawa recommends extra caution due to the heavy load on the motor. | 0 to 4; 7 <9> | 1 | S | S | S | 492 | 223 |
| 2 | L3-05 | Stall Prevention Selection during Run | Selects the Stall Prevention method to use to prevent drive faults during run. 0: Disabled - Drive runs a set frequency. A heavy load may cause the drive to trip on an oC or oL fault. 1: Decel Time 1 - The drive will decelerate at Decel Time 1 (C1-02) if the output current exceeds the level set by L3-06. Once the current level drops below the L3-06 level, the drive will accelerate back to its frequency reference at the active acceleration rate. 2: Decel Time 2 - Same as setting 1 except the drive decelerates at Decel Time 2 (C1-04). When output frequency is 6 Hz or less, Stall Prevention during run is disabled regardless of the setting in L3-05. | 0 to 2 | 1 | A | − | A | 493 | 224 |
| 3 | L3-06 | Stall Prevention Level during Run | Enabled when L3-05 is set to "1" or "2". 100% is equal to the drive rated current. Decrease the set value if stalling or excessive current occurs with the default settings. | 30 to 150 <18> | <8> <18> | A | − | A | 494 | 225 |
| 4 | L3-11 | ov Suppression Function Selection | Enables or disables ov suppression function, which allows the drive to change the output frequency as the load changes, thus preventing an ov fault. 0: Disabled 1: Enabled Note: The frequency reference and motor speed diverge as the regenerative energy begins to flow back into the DC bus and triggers the ov suppression function. Disable this function when using a braking resistor. | 0, 1 | 0 | A | A | A | 4C7 | 225 |
| 5 | L3-17 <5> | Overvoltage Suppression and Stall Prevention Desired DC Bus Voltage | Sets the desired value for the DC bus voltage during overvoltage suppression and Stall Prevention during deceleration. Enabled only when L3-04 = 2 or L3-11 = 1. | 150 to 400 V | 370 V <6> | A | A | A | 462 | 226 |
| 6 | L3-20 | Main Power Circuit Voltage Adjustment Gain | Sets the proportional gain used by KEB, Stall Prevention and overvoltage suppression. If ov or Uv1 occurs at the beginning of KEB deceleration, slowly increase this setting by 0.1. | 0.00 to 5.00 | 1.00 | A | A | A | 465 | 226 |
| 7 | L3-21 | Accel/Decel Rate Calculation Gain | Sets the proportional gain used to calculate the deceleration rate during KEB, ov suppression function and Stall Prevention during deceleration (L3-04 = 2). This parameter does not typically require adjustment. Increase the value in steps of 1.0 if overcurrent and overvoltage occur. | 0.00 to 200.00 | 1.00 | A | A | A | 466 | 226 |
| 8 | L3-22 | Deceleration Time at Stall Prevention during Acceleration | Sets the deceleration time used for Stall Prevention during acceleration in Open Loop Vector Control for PM motors. When set to 0, the drive decelerates at the normal deceleration time. | 0.0 to 6000.0 | 0.0 s | − | − | A | 4F9 | 223 |
Manual — Frequency detection and fault restart — page 387
Source reference: SIEP C71060618F, December 2016, physical PDF page 387. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
L4: Frequency Detection Use L4 parameters to configure frequency detection operation.
L5: Fault Reset Use L5 parameters to configure Automatic Restart after fault.
L6: Overtorque Detection Use L6 parameters to configure overtorque detection.
B.2 Parameter Table
B
Parameter List
L3-23 | Automatic Reduction Selection for Stall Prevention during Run
L3-24 | Motor Acceleration Time for Inertia Calculations
L3-25 | Load Inertia Ratio
L4-01 | Speed Agreement Detection Level
L4-02 | Speed Agreement Detection Width
L4-03 | Speed Agreement Detection Level (+/-)
L4-04 | Speed Agreement Detection Width (+/-)
L4-05 | Frequency Reference Loss Detection Selection
L4-06 | Frequency Reference at Reference Loss
L4-07 | Frequency Detection Conditions
L4-08 <12> | Speed Agreement Detection Conditions
L5-01 | Number of Auto Restart Attempts
L5-02 | Auto Restart Operation Selection
L5-04 | Fault Reset Interval Time
L5-05 | Fault Reset Operation Selection
Parameter catalogue PDF387 section1 — PDF page 387
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L3-23 | Automatic Reduction Selection for Stall Prevention during Run | 0: Sets the Stall Prevention level throughout the entire frequency range to the value in parameter L3-06. 1: Automatically lowers the Stall Prevention level in the constant output range. The lower limit value is 40% of L3-06. | 0, 1 | 0 | A | A | Α | 4FD | 225 |
| 2 | L3-24 | Motor Acceleration Time for Inertia Calculations | Sets the time needed to accelerate the uncoupled motor at rated torque from stop to the maximum frequency. Setting the drive capacity to parameter o2-04 or changing E2-11 will automatically set this parameter for a 4-pole motor. | 0.001 to 10.000 | <4> <10> <11> | A | A | A | 46E | 226 |
| 3 | L3-25 | Load Inertia Ratio | Sets the ratio between the motor and machine inertia. | 0.0 to 1000.0 | 1.0 | A | A | A | 46F | 227 |
| 4 | L4-01 | Speed Agreement Detection Level | These parameters configure the multi-function output (H2- oo = 2, 3, 4, 5) settings "Speed Agree 1", "User Set Speed Agree 1", "Frequency Detection 1," and "Frequency detection 2". Parameter L4-01 sets the level while parameter L4-02 sets the hysteresis for the Speed Detection Output Function. | 0.0 to 400.0 | 0.0 Hz | A | A | A | 499 | 227 |
| 5 | L4-02 | Speed Agreement Detection Width | These parameters configure the multi-function output (H2- oo = 2, 3, 4, 5) settings "Speed Agree 1", "User Set Speed Agree 1", "Frequency Detection 1," and "Frequency detection 2". Parameter L4-01 sets the level while parameter L4-02 sets the hysteresis for the Speed Detection Output Function. | 0.0 to 20.0 | 2.0 Hz | A | A | A | 49A | 227 |
| 6 | L4-03 | Speed Agreement Detection Level (+/-) | These parameters configure the Multi-Function Output (H2- oo = 13, 14, 15, 16) settings "Speed Agree 2", "User Set Speed Agree 2", "Frequency Detection 3," or "Frequency Detection 4". Parameter L4-03 sets the level while parameter L4-04 sets the hysteresis for the Speed Detection Output Function. | -400.0 to +400.0 | 0.0 Hz | A | A | A | 49B | 227 |
| 7 | L4-04 | Speed Agreement Detection Width (+/-) | These parameters configure the Multi-Function Output (H2- oo = 13, 14, 15, 16) settings "Speed Agree 2", "User Set Speed Agree 2", "Frequency Detection 3," or "Frequency Detection 4". Parameter L4-03 sets the level while parameter L4-04 sets the hysteresis for the Speed Detection Output Function. | 0.0 to 20.0 | 2.0 Hz | A | A | A | 49C | 227 |
| 8 | L4-05 | Frequency Reference Loss Detection Selection | Sets operation when the frequency reference is lost (reference drops 90% or more within 400 ms). 0: Stop - Drive will stop. 1: Run at L4-06 Level - Drive will run at the percentage set in L4-06 of the frequency reference before loss. | 0, 1 | 0 | A | A | A | 49D | 227 |
| 9 | L4-06 | Frequency Reference at Reference Loss | Sets the frequency reference when a reference loss was detected and L4-05 = 1. Reference will be: Fref = Fref at time of loss x L4-06. | 0.0 to 100.0 | 80.0% | A | A | A | 4C2 | 228 |
| 10 | L4-07 | Frequency Detection Conditions | 0: No detection during baseblock. 1: Detection always enabled. | 0, 1 | 0 | A | A | A | 470 | 228 |
| 11 | L4-08 <12> | Speed Agreement Detection Conditions | 0: Match speed with the soft-starter output 1: Match frequency reference and motor speed Note: In V/f Control, the drive ignores the value set to L4-08 and refers to the soft-starter output to determine whether a speed agree situation has been reached. | 0, 1 | 0 | A | A | A | 47F | 228 |
| 12 | L5-01 | Number of Auto Restart Attempts | Sets the counter for the number of times the drive attempts to restart when one of the following faults occurs: GF, LF, oC, oH1, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1. Parameter L5-05 determines the how the restart counter is incremented. When the drive operates without fault for 10 minutes, the counter will be reset. | 0 to 10 | 0 | A | A | A | 49E | 230 |
| 13 | L5-02 | Auto Restart Operation Selection | Sets fault contact (H2-□□ = E) activation during automatic restart attempts. 0: Fault output not active. 1: Fault output active during restart attempt. | 0, 1 | 0 | A | A | A | 49F | 230 |
| 14 | L5-04 | Fault Reset Interval Time | Sets the amount of time to wait between performing fault restarts. Enabled when L5-05 is set to 1. | 0.5 to 600.0 s | 10.0 s | A | A | A | 46C | 231 |
| 15 | L5-05 | Fault Reset Operation Selection | Selects the method of incrementing the restart counter. 0: Continuously attempt to restart and increment counter after successful restart (same as Varispeed VS616-F7/G7) 1: Attempt to restart with the interval time set in L5-04. Every trial increments the counter. (same as Varispeed VS606-V7) | 0, 1 | 0 | A | A | A | 467 | 231 |
Manual — Torque detection selection and levels — page 388
Source reference: SIEP C71060618F, December 2016, physical PDF page 388. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
B.2 Parameter Table
L6-01 | Torque Detection Selection 1
L6-02 | Torque Detection Level 1
L6-03 | Torque Detection Time 1
L6-04 | Torque Detection Selection 2
L6-05 | Torque Detection Level 2
L6-06 | Torque Detection Time 2
Parameter catalogue PDF388 section1 — PDF page 388
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L6-01 | Torque Detection Selection 1 | Selects the overtorque/undertorque operation. overtorque and undertorque are determined by the settings in parameters L6-02 and L6-03. The multi-function output settings (H2- oo= B and 17) are also active if programmed. 0: Disabled 1: oL3 at Speed Agree - Alarm (overtorque detection only active during Speed Agree and operation continues after detection). 2: oL3 at RUN - Alarm (overtorque detection is always active and operation continues after detection). 3: oL3 at Speed Agree - Fault (overtorque detection only active during Speed Agree and drive output will shut down on an oL3 fault). 4: oL3 at RUN - Fault (overtorque detection is always active and drive output will shut down on an oL3 fault). 5: UL3 at Speed Agree - Alarm (undertorque detection is only active during Speed Agree and operation continues after detection). 6: UL3 at RUN - Alarm (undertorque detection is always active and operation continues after detection). 7: UL3 at Speed Agree - Fault (undertorque detection only active during Speed Agree and drive output will shut down on an oL3 fault). 8: UL3 at RUN - Fault (undertorque detection is always active and drive output will shut down on an oL3 fault). | 0 to 8 | 0 | A | A | A | 4A1 | 231 |
| 2 | L6-02 | Torque Detection Level 1 | Sets the overtorque/undertorque detection level. 100% is equal to the motor rated current in V/f Control and the motor rated torque in Open Loop Vector Control. | 0 to 300 | 150% | A | A | A | 4A2 | 232 |
| 3 | L6-03 | Torque Detection Time 1 | Sets the length of time an overtorque/undertorque condition must exist before Torque Detection 1 is triggered. | 0.0 to 10.0 | 0.1 s | A | A | A | 4A3 | 233 |
| 4 | L6-04 | Torque Detection Selection 2 | Sets the response to an overtorque/undertorque condition. overtorque and undertorque are determined by the settings in parameters L6-05 and L6-06. The multi-function output settings (H2-□□ = 18 and 19). 0: Disabled 1: oL4 at Speed Agree - Alarm (overtorque Detection only active during Speed Agree and Operation continues after detection). 2: oL4 at RUN - Alarm (overtorque Detection is always active and operation continues after detection). 3: oL4 at Speed Agree - Fault (overtorque Detection only active during Speed Agree and drive output will shut down on an oL4 fault). 4: oL4 at RUN - Fault (overtorque Detection is always active and drive output will shut down on an oL4 fault). 5: UL4 at Speed Agree - Alarm (undertorque Detection is only active during Speed Agree and operation continues after detection). 6: UL4 at RUN - Alarm (undertorque Detection is always active and operation continues after detection). 7: UL4 at Speed Agree - Fault (undertorque Detection only active during Speed Agree and drive output will shut down on an oL4 fault). 8: UL4 at RUN - Fault (undertorque Detection is always active and drive output will shut down on an oL4 fault). | 0 to 8 | 0 | A | A | A | 4A4 | 232 |
| 5 | L6-05 | Torque Detection Level 2 | Sets the overtorque/undertorque detection level. 100% is equal to the motor rated current in V/f Control or PM OLV and equal to the motor rated torque in Open Loop Vector Control. | 0 to 300 | 150% | A | A | A | 4A5 | 232 |
| 6 | L6-06 | Torque Detection Time 2 | Sets the length of time an overtorque/undertorque condition must exist before torque detection 2 is recognized by the drive. | 0.0 to 10.0 | 0.1 s | A | A | A | 4A6 | 233 |
Manual — Mechanical weakening and torque limits — page 389
Source reference: SIEP C71060618F, December 2016, physical PDF page 389. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
L7: Torque Limit Use L7 parameters to configure the torque limit function.
L8: Hardware Protection Use L8 parameters to configure hardware protection functions.
B.2 Parameter Table
B
Parameter List
L6-08 | Mechanical Weakening (oL5) Detection Operation
L6-09 | Mechanical Weakening Detection Speed Level
L6-10 | Mechanical Weakening Detection Time
L6-11 | Mechanical Weakening Detection Start Time
L7-01 | Forward Torque Limit
L7-02 | Reverse Torque Limit
L7-03 | Forward Regenerative Torque Limit
L7-04 | Reverse Regenerative Torque Limit
L7-06 | Torque Limit Integral Time Constant
L7-07 | Torque Limit Control Method Selection during Accel/ Decel
L8-01 | Internal Dynamic Braking Resistor Protection Selection (ERF type)
L8-02 | Overheat Alarm Level
Parameter catalogue PDF389 section1 — PDF page 389
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L6-08 | Mechanical Weakening (oL5) Detection Operation | This function can detect an over/undertorque in a certain speed range as a result of machine fatigue. It is triggered by a certain operation time and uses the oL1 detection settings (L6-01 to L6-02) 0: Mechanical Weakening Detection disabled. 1: Continue running (alarm only). Detected when the speed (signed) is greater than L6-09. 2: Continue running (alarm only). Detected when the speed (not signed) is greater than L6-09. 3: Interrupt drive output (fault). Detected when the speed (signed) is greater than L6-09. 4: Interrupt drive output (fault). Detected when the speed (not signed) is greater than L6-09. 5: Continue running (alarm only). Detected when the speed (signed) is less than L6-09. 6: Continue running (alarm only). Detected when the speed (not signed) is less than L6-09. 7: Interrupt drive output (fault). Detected when the speed (signed) is less than L6-09. 8: Interrupt drive output (fault). Detected when the speed (not signed) is less than L6-09. | 0 to 8 | 0 | A | A | A | 468 | 233 |
| 2 | L6-09 | Mechanical Weakening Detection Speed Level | Sets the speed that triggers mechanical weakening detection. When L6-08 is set for an unsigned value, the absolute value is used even if the setting is negative. | -110.0 to +110.0% | 110% | A | A | A | 469 | 233 |
| 3 | L6-10 | Mechanical Weakening Detection Time | Sets the time a mechanical weakening has to be detected before an Alarm/Fault is triggered. | 0.0 to 10.0 s | 0.1 s | A | A | A | 46A | 234 |
| 4 | L6-11 | Mechanical Weakening Detection Start Time | Sets the operation time (U1-04) that has to be passed before Mechanical weakening detection is active. | 0 to 65535 | 0 | A | A | A | 46B | 234 |
| 5 | L7-01 | Forward Torque Limit | Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. | 0 to 300 | 200% | − | A | − | 4A7 | 234 |
| 6 | L7-02 | Reverse Torque Limit | Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. | 0 to 300 | 200% | − | A | − | 4A8 | 234 |
| 7 | L7-03 | Forward Regenerative Torque Limit | Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. | 0 to 300 | 200% | − | A | − | 4A9 | 234 |
| 8 | L7-04 | Reverse Regenerative Torque Limit | Sets the torque limit value as a percentage of the motor rated torque. Four individual quadrants can be set. Graph labels: output torque, positive torque, negative torque; motor r/min; REV left, FWD right. L7-01 upper right; L7-04 upper left regeneration; L7-02 lower left; L7-03 lower right regeneration. Exact graph geometry original-only. | 0 to 300 | 200% | − | A | − | 4AA | 234 |
| 9 | L7-06 | Torque Limit Integral Time Constant | Sets the integral time constant for the torque limit. | 5 to 10000 | 200 ms | − | A | − | 4AC | 234 |
| 10 | L7-07 | Torque Limit Control Method Selection during Accel/ Decel | Selects the method of torque limit control during accel/decel. 0: Proportional Control (change to integral controls at fixed speeds). Use this setting when acceleration to the desired speed has priority over torque limitation. 1: Integral Control. Use this setting if the torque limitation has priority. When torque limit is applied to the motor, accel/decel time may increase and motor speed may not meet the speed reference. | 0, 1 | 0 | − | A | − | 4C9 | 234 |
| 11 | L8-01 | Internal Dynamic Braking Resistor Protection Selection (ERF type) | Selects the Braking resistor when using a 3% duty cycle heatsink mounted braking resistor. This parameter does not enable or disable the braking transistor of the drive. 0: Resistor overheat protection disabled 1: Resistor overheat protection enabled | 0, 1 | 0 | A | A | A | 4AD | 235 |
| 12 | L8-02 | Overheat Alarm Level | When the heatsink temperature exceeds the value set in this parameter, an Overheat Alarm (oH) will occur. | 50 to 130 | <3> | A | A | A | 4AE | 235 |
Manual — Hardware protection parameters — page 390
Source reference: SIEP C71060618F, December 2016, physical PDF page 390. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
B.2 Parameter Table
L8-03 | Overheat Pre-Alarm Operation Selection
L8-05 | Input Phase Loss Protection Selection
L8-07 | Output Phase Loss Protection Selection
L8-09 | Output Ground Fault Detection Selection
L8-10 | Heatsink Cooling Fan Operation Selection
L8-11 | Heatsink Cooling Fan Operation Delay Time
L8-12 | Ambient Temperature Setting
L8-15 | oL2 Characteristics Selection at Low Speeds
L8-18 | Soft Current Limit Selection
L8-19 | Frequency Reduction Rate during oH Pre-Alarm
L8-29 | Current Unbalance Detection (LF2)
L8-35 | Installation Method Selection
L8-38 | Carrier Frequency Reduction
Parameter catalogue PDF390 section1 — PDF page 390
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L8-03 | Overheat Pre-Alarm Operation Selection | Sets the drive operation when an overheat alarm oH is detected. 0: Ramp to Stop using the active decel time. 1: Coast to Stop. 2: Fast-stop using the time set in C1-09. 3: Alarm Only. Drive continues running, but displays an alarm. 4: Reduced Speed Operation. Drive continues to run with reduced frequency reference as specified in L8-19. Settings 0 through 2 trigger a fault relay if the heatsink becomes too hot. | 0 to 4 | 3 | A | A | A | 4AF | 235 |
| 2 | L8-05 | Input Phase Loss Protection Selection | Selects the detection of input current phase loss, power supply voltage imbalance, or main circuit electrolytic capacitor deterioration. 0: Disabled 1: Enabled Note: This parameter is disabled in 200 V single-phase drives. | 0, 1 | 1 | A | A | A | 4B1 | 236 |
| 3 | L8-07 | Output Phase Loss Protection Selection | Selects the output phase loss detection. 0: Disabled 1: Enabled (triggered by a single phase loss) 2: Enabled (triggered when two phases are lost) Output phase loss is detected when operating with less than 5% of the drive rated current. Detection can mistakenly occur if the motor is small relative to the drive capacity rating (this parameter should be disabled in such cases). | 0 to 2 | 1 | A | A | A | 4B3 | 236 |
| 4 | L8-09 | Output Ground Fault Detection Selection | Selects the output ground fault detection. 0: Disabled 1: Enabled | 0, 1 | <3> | A | A | A | 4B5 | 237 |
| 5 | L8-10 | Heatsink Cooling Fan Operation Selection | Controls the heatsink cooling fan operation. 0: Run with timer (Fan operates only during run and for L8-11 seconds after stop.) 1: Run always (Cooling fan operates whenever the drive is powered up.) | 0, 1 | 0 | A | A | A | 4B6 | 237 |
| 6 | L8-11 | Heatsink Cooling Fan Operation Delay Time | This parameter sets the delay time for the cooling fan to shut off after the run command is removed when L8-10 = 0. | 0 to 300 | 60 s | A | A | A | 4B7 | 237 |
| 7 | L8-12 | Ambient Temperature Setting | Used to input the ambient temperature. This value adjusts the drives oL2 detection level. | -10 to 50 | 40 °C | A | A | A | 4B8 | 237 |
| 8 | L8-15 | oL2 Characteristics Selection at Low Speeds | Sets the oL2 characteristics at output frequencies below 6 Hz. 0: No oL2 level reduction below 6 Hz. 1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz. | 0, 1 | 1 | A | A | A | 4BB | 237 |
| 9 | L8-18 | Soft Current Limit Selection | Selects the software current limit function. Typically no adjustment is required. 0: Disabled 1: Enabled | 0, 1 | <15> | A | A | − | 4BE | 238 |
| 10 | L8-19 | Frequency Reduction Rate during oH Pre-Alarm | Specifies the frequency reference reduction gain at overheat pre-alarm when L8-03 = 4. | 0.1 to 1.0 | 0.8 | A | A | A | 4BF | 236 |
| 11 | L8-29 | Current Unbalance Detection (LF2) | Selects the detection of unbalanced output currents caused by faulty devices in the output circuit. 0: Disabled 1: Enabled | 0, 1 | 1 | − | − | A | 4DF | 238 |
| 12 | L8-35 | Installation Method Selection | Selects the installation type: 0: IP20/Open-Chassis Drive, IP00/Open-Chassis Drive 1: Side-by-Side Mounting 2: NEMA Type 1 Drive 3: Finless Drive or External Heatsink Installation | 0 to 3 | 2 <13> | Α | Α | A | 4EC | 238 |
| 13 | L8-38 | Carrier Frequency Reduction | Provides protection to the IGBTs by reducing the carrier frequency at low speeds. 0: Disabled 1: Enabled below 6 Hz 2: Enabled for the whole speed range | 0 to 2 | <3> | A | A | A | 4EF | 238 |
Manual — Protection footnotes and hunting control — page 391
Source reference: SIEP C71060618F, December 2016, physical PDF page 391. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
<1> Setting 6 available in drive software versions PRG: 1016 and later. <2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control. <3> Default setting value is dependent on parameter o2-04, Drive Model Selection. <4> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. <5> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. <6> Default setting value is dependent on parameter E1-01, Input Voltage Setting. <7> Setting value 2 is not available A1-02 = 5-PM OLV Control. When enabled, the drive stops accelerating when it exceeds the value of L3-02, Stall Prevention Level. The drive decelerates after 100 ms and begins accelerating again after restoring the current level. <8> Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD). <9> The setting range depends on the control mode set in A1-02. For PM OLV Control the setting range is 0 to 2 and 7. <10> Default setting value is dependent on parameter E5-01, Motor Code Selection. <11> Parameter value is changed if E2-11 is manually changed or changed by Auto-Tuning. <12> Available in drive software versions PRG: 1016 and later. <13> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330. <14> Available in drive software versions PRG: 1018 and later. There is normally no need to change this parameter from the default value. <15> Default setting is determined by drive software version and C6-02 setting. Drive software versions PRG: 1021 and later have a default setting of 0 when the carrier frequency is set for Leakage Current Rejection PWM (C6-02 = B), and 1 when C6-02 is set to any other value. <16> Parameter can be changed during Run. <17> Available in drive software versions PRG: 1021 and later. <18> The default setting and the upper limit of the setting range are determined by C6-01, Drive Duty Mode, and L8-38, Carrier Frequency Reduction Selection.
◆ n: Advanced Performance Set-Up
The n parameters are used to adjust more advanced performance characteristics such as hunting prevention, speed feedback detection, high-slip braking and R1 online tuning.
n1: Hunting Prevention Use n1 parameters to configure hunting prevention operation.
B.2 Parameter Table
B
Parameter List
L8-40 | Carrier Frequency Reduction Time
L8-41 | High Current Alarm Selection
L8-51 <14> | STo Fault Detection Level
L8-54 <14> | STo Deviation Detection
n1-01 | Hunting Prevention Selection
Parameter catalogue PDF391 section1 — PDF page 391
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | L8-40 | Carrier Frequency Reduction Time | Sets the time for that the drive continues running with reduced carrier frequency after the carrier reduction condition has gone (see also L8-38). A setting of 0.00 s disables the carrier frequency reduction time. | 0.00 to 2.00 | 0.50 | A | A | A | 4F1 | 239 |
| 2 | L8-41 | High Current Alarm Selection | Configures an alarm when the output current exceeds 150% of the drive rated current. 0: Alarm disabled. 1: Alarm enabled. | 0, 1 | 0 | A | A | A | 4F2 | 239 |
| 3 | L8-51 <14> | STo Fault Detection Level | Sets the STo detection level as a percentage of the motor rated current. Increase this value to detect pull-out more quickly during acceleration. The drive calculates this value automatically when L8-51 is set to 0.0%. | 0.0 to 150.0% | 0.0% | – | – | A | 471 | 239 |
| 4 | L8-54 <14> | STo Deviation Detection | 0: Disabled. 1: Enabled. | 0, 1 | 1 | – | – | A | 474 | 239 |
Parameter catalogue PDF391 section2 — PDF page 391
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | n1-01 | Hunting Prevention Selection | If the motor vibrates while lightly loaded, Hunting Prevention may reduce the vibration. 0: Disabled 1: Enabled When quick response is needed disable Hunting Prevention. | 0, 1 | 1 | A | − | − | 580 | 240 |
Manual — Speed feedback braking and online tuning — page 392
Source reference: SIEP C71060618F, December 2016, physical PDF page 392. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
n2: Speed Feedback Detection Control Function Use n2 parameters to configure the Speed Feedback Detection Control function operation.
Adjust the setting by 0.05 units at a time, while checking the response.
n3: High-Slip Braking Use n3 parameters to configure the high-slip braking function.
n6: Online Tuning of Motor Line-to-Line Resistance Use n6 parameters to adjust the motor line-to-line resistance while the drive is online.
n8: Permanent Magnet (PM) Motor Control Use n8 parameters to control the PM motor control.
B.2 Parameter Table
n1-02 | Hunting Prevention Gain Setting
n1-03 | Hunting Prevention Time Constant
n1-05 | Hunting Prevention Gain while in Reverse
n2-01 | Speed Feedback Detection Control (AFR) Gain
n2-02 | Speed Feedback Detection Control (AFR) Time Constant
n2-03 | Speed Feedback Detection Control (AFR) Time Constant 2
n3-01 | High-Slip Braking Deceleration Frequency Width
n3-02 | High-Slip Braking Current Limit
n3-03 | High-Slip Braking Dwell Time at Stop
n3-04 | High-Slip Braking Overload Time
n3-13 | Overexcitation Deceleration Gain
n3-21 | High-Slip Suppression Current Level
n3-23 | Overexcitation Operation Selection
n6-01 | Line-to-Line Motor Resistance Online Tuning
Parameter catalogue PDF392 section1 — PDF page 392
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | n1-02 | Hunting Prevention Gain Setting | Sets the gain for the Hunting Prevention Function. If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases. If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases. | 0.00 to 2.50 | 1.00 | A | − | − | 581 | 240 |
| 2 | n1-03 | Hunting Prevention Time Constant | Sets the time constant used for hunting prevention. | 0 to 500 | <1> | A | − | − | 582 | 240 |
| 3 | n1-05 | Hunting Prevention Gain while in Reverse | Sets the gain used for Hunting Prevention. When set to 0, the gain n1-02 is used for operation in reverse direction. | 0.00 to 2.50 | 0.00 | A | − | − | 530 | 240 |
| 4 | n2-01 | Speed Feedback Detection Control (AFR) Gain | Sets the internal speed feedback detection control gain in the automatic frequency regulator (AFR). This parameter does not typically require adjustment. Adjust this parameter as follows: If hunting occurs, increase the set value. If response is low, decrease the set value. | 0.00 to 10.00 | <8> | − | A | − | 584 | 240 |
| 5 | n2-02 | Speed Feedback Detection Control (AFR) Time Constant | Sets the AFR time constant 1. | 0 to 2000 | 50 ms | − | A | − | 585 | 241 |
| 6 | n2-03 | Speed Feedback Detection Control (AFR) Time Constant 2 | Sets the AFR time constant 2. Increase the setting if overvoltage occurs during sudden load changes or the speed overshoots during fast acceleration. | 0 to 2000 | 750 ms | − | A | − | 586 | 241 |
| 7 | n3-01 | High-Slip Braking Deceleration Frequency Width | Sets the output frequency reduction step width when the drive stops the motor using high-slip braking (HSB). If Overvoltage (ov) faults occur during HSB, this parameter may need to be increased. | 1 to 20 | 5% | A | − | − | 588 | 241 |
| 8 | n3-02 | High-Slip Braking Current Limit | Sets the current limit during HSB. Higher n3-02 settings will shorten motor stopping times but increase the motor current, and therefore motor heating. | 100 to 200 | 150% | A | − | − | 589 | 242 |
| 9 | n3-03 | High-Slip Braking Dwell Time at Stop | Sets the time the drive will run with minimum frequency (E1-09) at the end of deceleration. If this time is set too low, the machine inertia can cause the motor to rotate slightly after HSB completion. | 0.0 to 10.0 | 1.0 s | A | − | − | 58A | 242 |
| 10 | n3-04 | High-Slip Braking Overload Time | Sets the time required for an HSB overload fault (oL7) to occur when the drive output frequency does not change during an HSB stop. This parameter does not typically require adjustment. | 30 to 1200 | 40 s | A | − | − | 58B | 242 |
| 11 | n3-13 | Overexcitation Deceleration Gain | Applies a gain to the V/f pattern during deceleration (L3-04 = 4). Returns to normal values after ramp to stop or at re- acceleration. To increase the braking power of overexcitation, increase the gain by 1.25 to 1.30. | 1.00 to 1.40 | 1.10 | A | A | − | 531 | 242 |
| 12 | n3-21 | High-Slip Suppression Current Level | If overcurrent or overload occur during high-slip deceleration, reduce the high-slip suppression current level. Set as a percentage of the drive rated current. | 0 to 150 | 100% | A | A | − | 579 | 242 |
| 13 | n3-23 | Overexcitation Operation Selection | 0: Enabled in both directions 1: Enabled only when rotating forward 2: Enabled only when in reverse | 0 to 2 | 0 | A | A | − | 57B | 242 |
| 14 | n6-01 | Line-to-Line Motor Resistance Online Tuning | Tunes the line-to-line motor resistance continuously during operation. 0: Disabled 1: Enabled | 0, 1 | 1 | − | A | − | 570 | 243 |
Manual — PM performance controls — page 393
Source reference: SIEP C71060618F, December 2016, physical PDF page 393. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection. <2> Parameter can be changed during Run. <3> Setting range varies depending on drive software version. Software versions PRG: 1018 and later disable pull-in current when n8-48 = 0 and allow this parameter to be changed during run. PRG: 1018 and later: 0% or 20 to 200% PRG: 1017 and earlier: 20 to 200%
B.2 Parameter Table
B
Parameter List
n8-45 | Speed Feedback Detection Control Gain
n8-47 | Pull-In Current Compensation Time Constant
n8-48 <2> | Pull-In Current
n8-49 <2> | d-Axis Efficiency Current Control for High-
n8-51 | Acceleration Pull-In Current
n8-54 | Voltage Error Compensation Time Constant
n8-55 | Load Inertia
n8-62 <5> | Output Voltage Limit
n8-63 <6> | Output Voltage Limit Gain 1
n8-65 <7> | Speed Feedback Detection Control Gain during ov Suppression
n8-68 <6> | Output Voltage Limit Gain 2
n8-87 <6> | Output Voltage Limit Selection
n8-88 <6> | Output Voltage Limit Switching Current Level
n8-89 <6> | Output Voltage Limit Switching Current Hysteresis Width
n8-90 <6> | Output Voltage Limit Switching Speed
n8-91 <6> | Id Limit for Output Voltage Limit Control
Parameter catalogue PDF393 section1 — PDF page 393
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | n8-45 | Speed Feedback Detection Control Gain | Sets the gain for internal speed feedback detection control. This parameter does not typically require adjustment. Increase this setting if hunting occurs. Decrease to lower the response. | 0.00 to 10.00 | 0.80 | − | − | A | 538 | 243 |
| 2 | n8-47 | Pull-In Current Compensation Time Constant | Sets the time constant to make the pull-in current and actual current value agree. Decrease the value if the motor begins to oscillate. Increase the value if it takes too long for the current reference to equal the output current. | 0.0 to 100.0 s | 5.0 s | − | − | A | 53A | 243 |
| 3 | n8-48 <2> | Pull-In Current | Defines the amount of current provided to the motor during no-load operation at a constant speed. Set as a percentage of the motor rated current. Increase this setting when hunting occurs while running at a constant speed. | <3> | 30% | − | − | A | 53B | 243 |
| 4 | n8-49 <2> | d-Axis Current for High- Efficiency Control | Sets control. the amount of d-Axis current when using Energy Saving | <4> | 0% | − | − | A | 53C | 243 |
| 5 | n8-51 | Acceleration Pull-In Current | Sets the pull-in current during acceleration as a percentage of the motor rated current (E5-03). Set to a high value when more starting torque is needed. | 0 to 200% | 50% | − | − | A | 53E | 244 |
| 6 | n8-54 | Voltage Error Compensation Time Constant | Sets the time constant for voltage error compensation. Adjust the value when hunting occurs at low speed. Increase in steps of 0.1 or disable the compensation by setting n8-45 to 0 when hunting occurs with sudden load changes or when oscillations occur at start. | 0.00 to 10.00 s | 1.00 s | − | − | A | 56D | 244 |
| 7 | n8-55 | Load Inertia | Sets the ratio between motor and machine inertia. 0: less than 1:10. 1: between 1:10 to 1:30. 2: between 1:30 to 1:50. 3: higher than 1:50. | 0 to 3 | 0 | − | − | A | 56E | 244 |
| 8 | n8-62 <5> | Output Voltage Limit | Sets the limit for the output voltage. Adjustment is normally needed only if the input voltage is below the n8-62 set value. In this case set n8-62 to the input voltage. | 0.0 to 230.0 | 200 Vac | − | − | A | 57D | 244 |
| 9 | n8-63 <6> | Output Voltage Limit Gain 1 | Sets the gain used for output voltage limit. | 0.00 to 100.00 | 1.00 | – | – | A | 57E | 245 |
| 10 | n8-65 <7> | Speed Feedback Detection Control Gain during ov Suppression | Sets the gain used for internal speed feedback detection during ov Suppression | 0.00 to 10.00 | 1.50 | − | − | A | 65C | 245 |
| 11 | n8-68 <6> | Output Voltage Limit Gain 2 | Sets the voltage detection level adjustment gain. | 0.50 to 1.50 | 0.95 | – | – | A | 237 | 245 |
| 12 | n8-87 <6> | Output Voltage Limit Selection | Determines the method of the output voltage limit. 0: Feedback method 1: Feed forward method Use the feed forward method if oscillation occurs in the constant output range. | 0, 1 | 0 | – | – | A | 2BC | 245 |
| 13 | n8-88 <6> | Output Voltage Limit Switching Current Level | Sets the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03). | 0 to 400% | 400% | – | – | A | 2BD | 245 |
| 14 | n8-89 <6> | Output Voltage Limit Switching Current Hysteresis Width | Determines the hysteresis of the current level to switch the output voltage limit sequence. Set as a percentage of the motor rated current (E5-03). | 0 to [n8-88] | 3% | – | – | A | 2BE | 245 |
| 15 | n8-90 <6> | Output Voltage Limit Switching Speed | Sets the speed level to switch the output voltage limit sequence. Set as a percentage of the maximum output frequency (E1-04). | 0 to 200% | 200% | – | – | A | 2BF | 245 |
| 16 | n8-91 <6> | Id Limit for Output Voltage Limit Control | Sets the amount of pull-in current that flows through the motor while operating at constant speed. Set as a percentage of the motor rated current (E5-03). Increase this setting if hunting occurs at constant speed. | -200 to 0% | -50% | – | – | A | 2F7 | 246 |
Manual — Advanced footnotes and operator displays — page 394
Source reference: SIEP C71060618F, December 2016, physical PDF page 394. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
<4> Setting range varies depending on drive software version. Software versions PRG: 1018 and later allow this parameter to be changed during run. PRG: 1018 and later: -200.0 to 200.0% PRG: 1017 and earlier: -200.0 to 0.0% <5> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. <6> Available in drive software versions PRG: 1018 and later. There is normally no need to change this parameter from the default value. <7> Parameter available in drive software versions PRG: 1011 and later. <8> Default setting is determined by drive model. Models BA0001 to BA0012, 2A0001 to 2A0020, and 4A0001 to 4A0011: Setting 1.00. Models BA0018, 2A0030 to 2A0069, and 4A0018 to 4A0038: Setting 1.50.
◆ o: Operator Related Parameters
o parameters are used to set up the LED digital operator displays.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
o1: Display Settings Use o1 parameters to configure the digital operator display.
Set to U1-06 as a default (Output Voltage Reference).
o2: Operator Keypad Functions Use o2 parameters to configure LED digital operator key functions.
B.2 Parameter Table
o1-01 <1> | Drive Mode Unit Monitor Selection
o1-02 <1> | User Monitor Selection After Power Up
o1-03 | Digital Operator Display Selection
o1-05 <1> <7> | LCD Contrast Control
o1-10 | Frequency Reference Setting and User-Set Display
o1-11 | Frequency Reference Setting / Decimal Display
o2-01 | LO/RE Key Function Selection
o2-02 | STOP Key Function Selection
Parameter catalogue PDF394 section1 — PDF page 394
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | o1-01 <1> | Drive Mode Unit Monitor Selection | Switches the display after the power has been turned on. When using an LED operator, pressing the up arrow key will display the following data: frequency reference → rotational direction → output frequency → output current → output voltage → U1-□□. (This is done by entering the 1□□ part of U1-□□. Certain monitors are not available in some control modes.) | <2> | 106 | A | A | A | 500 | 247 |
| 2 | o1-02 <1> | User Monitor Selection After Power Up | Selects the information that is displayed when the power is turned on. 1: Frequency Reference (U1-01) 2: Forward/Reverse 3: Output Frequency (U1-02) 4: Output Current (U1-03) 5: User Monitor (set by o1-01) | 1 to 5 | 1 | A | A | A | 501 | 247 |
| 3 | o1-03 | Digital Operator Display Selection | Sets the units to display the frequency reference and output frequency. 0: Hz 1: % (100% = E1-04) 2: r/min (enter the number of motor poles into E2-04/E4-04/ E5-04) 3: User defined by parameters o1-10 and o1-11 | 0 to 3 | 0 | A | A | A | 502 | 247 |
| 4 | o1-05 <1> <7> | LCD Contrast Control | Sets the brightness of the optional LCD operator. | 0 to 5 | 3 | A | A | A | 504 | 248 |
| 5 | o1-10 | Frequency Reference Setting and User-Set Display | These settings define the display values when o1-03 is set to 3. o1-10 sets display values when operating at the maximum output frequency. o1-11 sets the position of the decimal positions. | 1 to 60000 | <3> | A | A | A | 520 | 248 |
| 6 | o1-11 | Frequency Reference Setting / Decimal Display | These settings define the display values when o1-03 is set to 3. o1-10 sets display values when operating at the maximum output frequency. o1-11 sets the position of the decimal positions. | 0 to 3 | <3> | A | A | A | 521 | 248 |
| 7 | o2-01 | LO/RE Key Function Selection | Enables/Disables the digital operator LO/RE key. 0: Disabled 1: Enabled | 0, 1 | 1 | A | A | A | 505 | 248 |
| 8 | o2-02 | STOP Key Function Selection | Enables/Disables the operator panel STOP key when the drive is operated form external sources (not operator). 0: Disabled 1: Enabled | 0, 1 | 1 | A | A | A | 506 | 248 |
Manual — Operator copy and maintenance parameters — page 395
Source reference: SIEP C71060618F, December 2016, physical PDF page 395. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
o3: Copy Function Use o3 parameters to Read, Copy and Verify the parameter settings to and from the drive.
o4: Maintenance Period Use o4 parameters to perform maintenance.
B.2 Parameter Table
B
Parameter List
o2-03 | User Parameter Default Value
o2-04 <4> | Drive Model Selection
o2-05 | Frequency Reference Setting Method Selection
o2-06 | Operation Selection when Digital Operator is Disconnected
o2-07 | Motor Direction at Power Up when Using Operator
o2-09 | –
o3-01 | Copy Function Selection
o3-02 | Copy Allowed Selection
o4-01 | Accumulated Operation Time Setting
o4-02 | Accumulated Operation Time Selection
o4-03 | Cooling Fan Operation Time Setting
o4-05 | Capacitor Maintenance Setting
o4-07 | DC Bus Pre-Charge Relay Maintenance Setting
o4-09 | IGBT Maintenance Setting
Parameter catalogue PDF395 section1 — PDF page 395
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | o2-03 | User Parameter Default Value | Allows storing of parameter settings as a User Initialization Selection (value 1110 for A1-03). The value returns to 0 after entering 1 or 2. 0: No Change 1: Set Defaults - Saves current parameter settings as user initialization. 2: Clear All - Clears the currently saved user initialization. | 0 to 2 | 0 | A | A | A | 507 | 249 |
| 2 | o2-04 <4> | Drive Model Selection | Sets the drive model. This parameter only needs to be set when installing a new control board. Do not change for other reason. | 0 to FF | <5> | A | A | A | 508 | 249 |
| 3 | o2-05 | Frequency Reference Setting Method Selection | Selects if the ENTER key must be pressed when inputting the frequency reference by the operator keypad. 0: Data/Enter key must be pressed to enter a frequency reference. 1: Data/Enter key is not required. The output frequency changes immediately when the reference is changed by the UP or DOWN keys on the digital operator. The ENTER key does not need to be pressed. | 0, 1 | 0 | A | A | A | 509 | 249 |
| 4 | o2-06 | Operation Selection when Digital Operator is Disconnected | Sets drive action when the digital operator is removed in LOCAL mode or with b1-02 = 0. 0: The drive will continue operation 1: The drive will trigger a fault (oPr) and the motor will coast to stop | 0, 1 | 0 | A | A | A | 50A | 250 |
| 5 | o2-07 | Motor Direction at Power Up when Using Operator | 0: Forward 1: Reverse This parameter requires that drive operation be assigned to the digital operator. | 0, 1 | 0 | A | A | A | 527 | 250 |
| 6 | o2-09 | – | Factory use. | – | – | – | – | – | – | – |
| 7 | o3-01 | Copy Function Selection | 0: Copy select 1: INV → OP READ (Read parameters from the drive, saving them onto the digital operator.) 2: OP → INV WRITE (Copy parameters from the digital operator, writing them to the drive.) 3: OP → INV VERIFY (Verify parameter settings on the drive to check if they match the data saved on the operator.) To read the drive parameter settings into the digital operator, set o3-02 to 1 (to allow reading). | 0 to 3 | 0 | A | A | A | 515 | — |
| 8 | o3-02 | Copy Allowed Selection | Locks the READ operation to prevent accidental overwriting of the data stored in the LED operator. 0: READ operation prohibited 1: READ operation allowed | 0, 1 | 0 | A | A | A | 516 | — |
| 9 | o4-01 | Accumulated Operation Time Setting | Sets the value for the cumulative operation time of the drive in units of 10 h. | 0 to 9999 | 0 | A | A | A | 50B | 251 |
| 10 | o4-02 | Accumulated Operation Time Selection | Determines, how the cumulative operation time (U4-01) is counted. 0: Logs power-on time 1: Logs operation time when the drive output is active (output operation time). | 0, 1 | 0 | A | A | A | 50C | 251 |
| 11 | o4-03 | Cooling Fan Operation Time Setting | Sets the value of the fan operation time monitor U4-03 in units of 10 h. <6> | 0 to 9999 | 0 | A | A | A | 50E | 251 |
| 12 | o4-05 | Capacitor Maintenance Setting | Sets the value of the capacitor maintenance time monitor U4-05. | 0 to 150 | 0% | A | A | A | 51D | 251 |
| 13 | o4-07 | DC Bus Pre-Charge Relay Maintenance Setting | Sets the value of the Soft Charge Bypass Relay Maintenance monitor U4-06. | 0 to 150 | 0% | A | A | A | 523 | 251 |
| 14 | o4-09 | IGBT Maintenance Setting | Sets the value of the IGBT Maintenance monitor U4-07. | 0 to 150 | 0% | A | A | A | 525 | 252 |
Manual — Operator notes and DriveWorksEZ connections — page 396
Source reference: SIEP C71060618F, December 2016, physical PDF page 396. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
<1> Parameter can be changed during run. <2> Setting range is determined by drive software version. PRG: 1016 and later: 104 to 810 PRG: 1015 and earlier: 104 to 621 <3> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection. <4> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330 <5> Default setting value is dependent on parameter o2-04, Drive Model Selection. <6> Available in drive software versions PRG: 1011 and later. Parameter o4-03 is set in 10 h units. When o4-03 = 30, the operation time for the cooling fan will start counting from 300 hours, and monitor U4-03 will display “300 H”. Earlier software versions set o4-03 in 1 h units. <7> Available in drive software versions PRG: 1022 and later.
◆ q: DriveWorksEZ Parameters
◆ r: DriveWorksEZ Connection Parameters
B.2 Parameter Table
o4-11 | U2, U3 Initialization
o4-12 | kWh Monitor Initialization
o4-13 | Number of Run Commands Initialize Selection
q1-01 to q6-07 | DriveWorksEZ Parameters
r1-01 | DriveWorksEZ Connection Parameter 1 (upper)
r1-02 | DriveWorksEZ Connection Parameter 1 (lower)
r1-03 | DriveWorksEZ Connection Parameter 2 (upper)
r1-04 | DriveWorksEZ Connection Parameter 2 (lower)
r1-05 | DriveWorksEZ Connection Parameter 3 (upper)
r1-06 | DriveWorksEZ Connection Parameter 3 (lower)
r1-07 | DriveWorksEZ Connection Parameter 4 (upper)
Parameter catalogue PDF396 section1 — PDF page 396
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | o4-11 | U2, U3 Initialization | 0: U2-□□ and U3-□□ monitor data are not reset when the drive is initialized using A1-03. 1: U2-□□ and U3-□□ monitor data are reset when the drive is initialized using A1-03. (The value of o4-11 is automatically returned to 0.) | 0, 1 | 0 | A | A | A | 510 | 252 |
| 2 | o4-12 | kWh Monitor Initialization | 0: U4-10 and U4-11 monitor data are not reset when the drive is initialized using A1-03. 1: U4-10 and U4-11 monitor data are reset when the drive is initialized using A1-03. (The value of o4-12 is automatically returned to 0.) | 0, 1 | 0 | A | A | A | 512 | 252 |
| 3 | o4-13 | Number of Run Commands Initialize Selection | 0: U4-02 monitor data is not reset when the drive is initialized using A1-03. 1: U4-02 monitor data is reset when the drive is initialized using A1-03. (The value of o4-13 is automatically returned to 0.) | 0, 1 | 0 | A | A | A | 528 | 252 |
Parameter catalogue PDF396 section2 — PDF page 396
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | q1-01 to q6-07 | DriveWorksEZ Parameters | Reserved for DriveWorksEZ. | - | - | A | A | Α | - | — |
Parameter catalogue PDF396 section3 — PDF page 396
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | r1-01 | DriveWorksEZ Connection Parameter 1 (upper) | Parameter 1 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1840 | — |
| 2 | r1-02 | DriveWorksEZ Connection Parameter 1 (lower) | Parameter 1 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1841 | — |
| 3 | r1-03 | DriveWorksEZ Connection Parameter 2 (upper) | Parameter 2 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1842 | — |
| 4 | r1-04 | DriveWorksEZ Connection Parameter 2 (lower) | Parameter 1 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1843 | — |
| 5 | r1-05 | DriveWorksEZ Connection Parameter 3 (upper) | Parameter 1 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1844 | — |
| 6 | r1-06 | DriveWorksEZ Connection Parameter 3 (lower) | Parameter 3 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1845 | — |
| 7 | r1-07 | DriveWorksEZ Connection Parameter 4 (upper) | Parameter 4 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1846 | — |
Manual — DriveWorksEZ connection register pairs — page 397
Source reference: SIEP C71060618F, December 2016, physical PDF page 397. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
B.2 Parameter Table
B
Parameter List
r1-08 | DriveWorksEZ Connection Parameter 4 (lower)
r1-09 | DriveWorksEZ Connection Parameter 5 (upper)
r1-10 | DriveWorksEZ Connection Parameter 5 (lower)
r1-11 | DriveWorksEZ Connection Parameter 6 (upper)
r1-12 | DriveWorksEZ Connection Parameter 6 (lower)
r1-13 | DriveWorksEZ Connection Parameter 7 (upper)
r1-14 | DriveWorksEZ Connection Parameter 7 (lower)
r1-15 | DriveWorksEZ Connection Parameter 8 (upper)
r1-16 | DriveWorksEZ Connection Parameter 8 (lower)
r1-17 | DriveWorksEZ Connection Parameter 9 (upper)
r1-18 | DriveWorksEZ Connection Parameter 9 (lower)
r1-19 | DriveWorksEZ Connection Parameter 10 (upper)
r1-20 | DriveWorksEZ Connection Parameter 10 (lower)
r1-21 | DriveWorksEZ Connection Parameter 11 (upper)
r1-22 | DriveWorksEZ Connection Parameter 11 (lower)
r1-23 | DriveWorksEZ Connection Parameter 12 (upper)
r1-24 | DriveWorksEZ Connection Parameter 12 (lower)
r1-25 | DriveWorksEZ Connection Parameter 13 (upper)
r1-26 | DriveWorksEZ Connection Parameter 13 (lower)
r1-27 | DriveWorksEZ Connection Parameter 14 (upper)
r1-28 | DriveWorksEZ Connection Parameter 14 (lower)
r1-29 | DriveWorksEZ Connection Parameter 15 (upper)
r1-30 | DriveWorksEZ Connection Parameter 15 (lower)
r1-31 | DriveWorksEZ Connection Parameter 16 (upper)
r1-32 | DriveWorksEZ Connection Parameter 16 (lower)
r1-33 | DriveWorksEZ Connection Parameter 17 (upper)
r1-34 | DriveWorksEZ Connection Parameter 17 (lower)
r1-35 | DriveWorksEZ Connection Parameter 18 (upper)
Parameter catalogue PDF397 section1 — PDF page 397
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | r1-08 | DriveWorksEZ Connection Parameter 4 (lower) | Parameter 4 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1847 | — |
| 2 | r1-09 | DriveWorksEZ Connection Parameter 5 (upper) | Parameter 5 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1848 | — |
| 3 | r1-10 | DriveWorksEZ Connection Parameter 5 (lower) | Parameter 5 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1849 | — |
| 4 | r1-11 | DriveWorksEZ Connection Parameter 6 (upper) | Parameter 6 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 184A | — |
| 5 | r1-12 | DriveWorksEZ Connection Parameter 6 (lower) | Parameter 6 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 184BH | — |
| 6 | r1-13 | DriveWorksEZ Connection Parameter 7 (upper) | Parameter 7 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 184C | — |
| 7 | r1-14 | DriveWorksEZ Connection Parameter 7 (lower) | Parameter 7 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 184D | — |
| 8 | r1-15 | DriveWorksEZ Connection Parameter 8 (upper) | Parameter 8 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 184E | — |
| 9 | r1-16 | DriveWorksEZ Connection Parameter 8 (lower) | Parameter 8 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 184F | — |
| 10 | r1-17 | DriveWorksEZ Connection Parameter 9 (upper) | Parameter 9 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1850 | — |
| 11 | r1-18 | DriveWorksEZ Connection Parameter 9 (lower) | Parameter 9 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1851 | — |
| 12 | r1-19 | DriveWorksEZ Connection Parameter 10 (upper) | Parameter 10 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1852 | — |
| 13 | r1-20 | DriveWorksEZ Connection Parameter 10 (lower) | Parameter 10 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1853 | — |
| 14 | r1-21 | DriveWorksEZ Connection Parameter 11 (upper) | Parameter 11 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1854 | — |
| 15 | r1-22 | DriveWorksEZ Connection Parameter 11 (lower) | Parameter 11 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1855 | — |
| 16 | r1-23 | DriveWorksEZ Connection Parameter 12 (upper) | Parameter 12 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1856 | — |
| 17 | r1-24 | DriveWorksEZ Connection Parameter 12 (lower) | Parameter 12 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1857 | — |
| 18 | r1-25 | DriveWorksEZ Connection Parameter 13 (upper) | Parameter 13 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1858 | — |
| 19 | r1-26 | DriveWorksEZ Connection Parameter 13 (lower) | Parameter 13 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1859 | — |
| 20 | r1-27 | DriveWorksEZ Connection Parameter 14 (upper) | Parameter 14 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 185A | — |
| 21 | r1-28 | DriveWorksEZ Connection Parameter 14 (lower) | Parameter 14 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 185B | — |
| 22 | r1-29 | DriveWorksEZ Connection Parameter 15 (upper) | Parameter 15 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 185C | — |
| 23 | r1-30 | DriveWorksEZ Connection Parameter 15 (lower) | Parameter 15 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 185D | — |
| 24 | r1-31 | DriveWorksEZ Connection Parameter 16 (upper) | Parameter 16 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 185E | — |
| 25 | r1-32 | DriveWorksEZ Connection Parameter 16 (lower) | Parameter 16 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 185F | — |
| 26 | r1-33 | DriveWorksEZ Connection Parameter 17 (upper) | Parameter 17 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1860 | — |
| 27 | r1-34 | DriveWorksEZ Connection Parameter 17 (lower) | Parameter 17 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1861 | — |
| 28 | r1-35 | DriveWorksEZ Connection Parameter 18 (upper) | Parameter 18 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1862 | — |
Manual — Connection continuations and motor tuning — page 398
Source reference: SIEP C71060618F, December 2016, physical PDF page 398. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Name Description Range Def.
Control Mode: V/f, OLV, PM; Addr. Hex; Pg.
OLV
PM
◆ T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
These values differ depending on the motor code value and motor parameter settings.
<1> The available tuning methods depend on control mode. Select values 2 or 3 in V/f Control, 0 or 2 in OLV control, and 2 for Motor 2 control. <2> Setting range varies depending on drive software version. PRG: 1016 and later: 0.03 to 650.00 kW PRG: 1015 and earlier: 0.00 to 650.00 kW <3> Default setting value is dependent on parameter o2-04, Drive Model Selection. <4> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
B.2 Parameter Table
r1-36 | DriveWorksEZ Connection Parameter 18 (lower)
r1-37 | DriveWorksEZ Connection Parameter 19 (upper)
r1-38 | DriveWorksEZ Connection Parameter 19 (lower)
r1-39 | DriveWorksEZ Connection Parameter 20 (upper)
r1-40 | DriveWorksEZ Connection Parameter 20 (lower)
T1-00 | Motor Selection 1/2
T1-01 | Auto-Tuning Mode Selection
T1-02 | Motor Rated Power
T1-03 <4> | Motor Rated Voltage
T1-04 | Motor Rated Current
T1-05 | Motor Base Frequency
T1-06 | Number of Motor Poles
T1-07 | Motor Base Speed
T1-11 | Motor Iron Loss
Parameter catalogue PDF398 section1 — PDF page 398
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | r1-36 | DriveWorksEZ Connection Parameter 18 (lower) | Parameter 18 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1863 | — |
| 2 | r1-37 | DriveWorksEZ Connection Parameter 19 (upper) | Parameter 19 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1864 | — |
| 3 | r1-38 | DriveWorksEZ Connection Parameter 19 (lower) | Parameter 19 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1865 | — |
| 4 | r1-39 | DriveWorksEZ Connection Parameter 20 (upper) | Parameter 20 for connecting DriveWorksEZ (upper). | 0 to FFFFH | 0 | – | A | A | 1866 | — |
| 5 | r1-40 | DriveWorksEZ Connection Parameter 20 (lower) | Parameter 20 for connecting DriveWorksEZ (lower). | 0 to FFFFH | 0 | – | A | A | 1867 | — |
Parameter catalogue PDF398 section2 — PDF page 398
| Source row | Parameter | Name | Description | Range | Default | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) | Reference page |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | T1-00 | Motor Selection 1/2 | Selects which set of motor parameters are used and set during Auto-Tuning. If Motor 2 selection (H1-□□ = 16) is not selected, this parameter will not be displayed. 1: Motor 1 (sets E1-□□, E2-□□) 2: Motor 2 (sets E3-□□, E4-□□. This selection is not displayed if motor 2 has not been selected.) | 1, 2 | 1 | A | A | − | 700 | 106 |
| 2 | T1-01 | Auto-Tuning Mode Selection | Selects the Auto-Tuning mode. 0: Rotational Auto-Tuning 2: Stationary Auto-Tuning for Line-to-Line Resistance 3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Speed Estimation type Speed Search) | 0, 2, 3 <1> | 2 or 3 in V/f 0 or 2 in OLV 2 in Motor 2 | A | A | − | 701 | 106 |
| 3 | T1-02 | Motor Rated Power | Sets the motor rated power in kilowatts (kW). Note: If motor power is given in horsepower, power in kW can be calculated using the following formula: kW = HP x 0.746. | <2> | <3> | A | A | − | 702 | 106 |
| 4 | T1-03 <4> | Motor Rated Voltage | Sets the motor rated voltage in volts (V). | 0.0 to 255.5 | 200.0 V | A | A | − | 703 | 107 |
| 5 | T1-04 | Motor Rated Current | Sets the motor rated current in amperes (A). | 10 to 200% of drive rated current | <3> | A | A | − | 704 | 107 |
| 6 | T1-05 | Motor Base Frequency | Sets the base frequency of the motor in Hertz (Hz). | 0.0 to 400.0 | 60.0 Hz | A | A | − | 705 | 107 |
| 7 | T1-06 | Number of Motor Poles | Sets the number of motor poles. | 2 to 48 | 4 | A | A | − | 706 | 107 |
| 8 | T1-07 | Motor Base Speed | Sets the base speed of the motor in revolutions per minute r/min (RPM). | 0 to 24000 | 1750 r/ min | A | A | − | 707 | 107 |
| 9 | T1-11 | Motor Iron Loss | Provides the iron loss for determining the Energy Saving coefficient. The value set to E2-10 (motor iron loss) when the power is cycled. If T1-02 is changed, an initial value valid for the selected capacity will be shown. | 0 to 65535 | 14 W | A | − | − | 70B | 107 |
Manual — Operation status monitors — page 399
Source reference: SIEP C71060618F, December 2016, physical PDF page 399. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other information about drive operation.
No.; Name; Description; Analog Output Level; Unit
Control Mode: V/f, OLV, PM; Addr. Hex.
OLV
PM
U1: Operation Status Monitors Use U1 monitors to display the operation status of the drive.
B.2 Parameter Table
B
Parameter List
U1-01 | Frequency Reference
U1-02 | Output Frequency
U1-03 | Output Current
U1-04 | Control Mode
U1-05 | Motor Speed
U1-06 | Output Voltage Reference
U1-07 | DC Bus Voltage
U1-08 | Output Power
U1-09 | Torque Reference
U1-10 | Input Terminal Status
Monitor catalogue PDF399 — PDF page 399
| Source row | Monitor | Name | Description | Analog output level | Unit | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | U1-01 | Frequency Reference | Monitors the frequency | 10 V: Max frequency | 0.01 Hz | A | A | A | 40 |
| 2 | U1-02 | Output Frequency | Displays the output frequency. Display units are determined by o1-03. | 10 V: Max frequency | 0.01 Hz | A | A | A | 41 |
| 3 | U1-03 | Output Current | Displays the output current. | 10 V: Drive rated current | 0.01 A <1> <2> | A | A | A | 42 |
| 4 | U1-04 | Control Mode | Control method set in A1-02. 0: V/f without PG 2: Open Loop Vector (OLV) 5: PM Open Loop Vector (PM) | No output signal available | – | A | A | A | 43 |
| 5 | U1-05 | Motor Speed | Displays the motor speed feedback. Display units are determined by o1-03. | 10 V: Maximum speed | 0.01 Hz | – | A | – | 44 |
| 6 | U1-06 | Output Voltage Reference | Displays the output voltage. | 10 V: 200 Vrms (400 Vrms) | 0.1 V | A | A | A | 45 |
| 7 | U1-07 | DC Bus Voltage | Displays the DC bus voltage. | 10 V: 400 V (800 V) | 1 V | A | A | A | 46 |
| 8 | U1-08 | Output Power | Displays the output power (this value is determined internally). | 10 V: Drive capacity (kW) (rated motor capacity) | <1> | A | A | A | 47 |
| 9 | U1-09 | Torque Reference | Monitor of internal torque reference value for Open Loop Vector (OLV) control | 10 V: Motor rated torque | – | – | A | – | 48 |
| 10 | U1-10 | Input Terminal Status | Displays the input terminal status. LED callout labels, top to bottom: Digital input terminal S1 enabled; S2 enabled; S3 enabled; S4 enabled; S5 enabled; S6 enabled; S7 enabled. Exact LED segment geometry and callout-to-segment position remain in source image; no numeric bit assignment inferred. | No output signal available | – | A | A | A | 49 |
Manual — Status and error monitors and fault trace — page 400
Source reference: SIEP C71060618F, December 2016, physical PDF page 400. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No.; Name; Description; Analog Output Level; Unit
Control Mode: V/f, OLV, PM; Addr. Hex.
OLV
PM
U2: Fault Trace Use U2 monitors to view fault trace data. <3>
B.2 Parameter Table
U1-11 | Output Terminal Status
U1-12 | Drive Status
U1-13 | Terminal A1 Input Level
U1-14 | Terminal A2 Input Level
U1-16 | Output Frequency after Soft Starter
U1-18 | oPE Fault Parameter
U1-19 | MEMOBUS/Modbus Error Code
U1-24 | Input Pulse Monitor
U1-25 | Software No. (Flash)
U1-26 | Software No. (ROM)
U1-27 | Operator Message ID
U1-28 | Drive Message ID
U2-01 | Current Fault
Monitor catalogue PDF400 — PDF page 400
| Source row | Monitor | Name | Description | Analog output level | Unit | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | U1-11 | Output Terminal Status | Displays the output terminal status. Multi-Function Digital Output (fault) (terminal MA/MB-MC) Multi-Function Digital Output 1 (terminal P1) enabled Multi-Function Digital Output 2 (terminal P2) enabled LED diagram labels retained in printed top-to-bottom order. Exact segment geometry and callout-to-segment position remain original-only; no numeric bit assignment inferred. | No output signal available | – | A | A | A | 4A |
| 2 | U1-12 | Drive Status | Verifies the drive operation status. During run During zero-speed During REV During fault reset signal input During speed agree Drive ready During alarm detection During fault detection LED diagram labels retained in printed top-to-bottom order. Exact segment geometry and callout-to-segment position remain original-only; no numeric bit assignment inferred. | No output signal available | – | A | A | A | 4B |
| 3 | U1-13 | Terminal A1 Input Level | Displays analog input A1 level: 100% when input is 10 V. | 10 V: 100% | 0.1% | A | A | A | 4E |
| 4 | U1-14 | Terminal A2 Input Level | Displays analog input A2 level: 100% when input is 10 V. | 10 V: 100% | 0.1% | A | A | A | 4F |
| 5 | U1-16 | Output Frequency after Soft Starter | Displays output frequency with ramp time and S-curves. Units determined by o1-03. | 10 V: Max frequency | 0.01 Hz | A | A | A | 53 |
| 6 | U1-18 | oPE Fault Parameter | Displays parameter no. for oPEoo or Err where error occurred. | No output signal available | – | A | A | A | 61 |
| 7 | U1-19 | MEMOBUS/Modbus Error Code | Displays the contents of a MEMOBUS/Modbus error. CRC Error Data Length Error Not Used Parity Error Overrun Error Framing Error Timed Out Not Used LED diagram labels retained in printed top-to-bottom order. Exact segment geometry and callout-to-segment position remain original-only; no numeric bit assignment inferred. | No output signal available | – | A | A | A | 66 |
| 8 | U1-24 | Input Pulse Monitor | Displays the Pulse Train input RP frequency. | 32000 | 1 Hz | A | A | A | 7D |
| 9 | U1-25 | Software No. (Flash) | Flash ID | No signal output avail. | – | A | A | A | 4D |
| 10 | U1-26 | Software No. (ROM) | ROM ID | No signal output avail. | – | A | A | A | 5B |
| 11 | U1-27 | Operator Message ID | Displays the numeric code of the remote operator (for use by the manufacturer). | No signal output avail. | – | A | A | A | 7A8 |
| 12 | U1-28 | Drive Message ID | Displays the numeric code of the drive (for use by the manufacturer) | No signal output avail. | – | A | A | A | 7A9 |
| 13 | U2-01 | Current Fault | Displays the current fault. | No signal output avail. | – | A | A | A | 80 |
Manual — Previous fault snapshots and fault history — page 401
Source reference: SIEP C71060618F, December 2016, physical PDF page 401. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No.; Name; Description; Analog Output Level; Unit
Control Mode: V/f, OLV, PM; Addr. Hex.
OLV
PM
U3: Fault History Use U3 monitors to display fault data. <3>
B.2 Parameter Table
B
Parameter List
U2-02 | Previous Fault
U2-03 | Frequency Reference at Previous Fault
U2-04 | Output Frequency at Previous Fault
U2-05 | Output Current at Previous Fault
U2-06 | Motor Speed at Previous Fault
U2-07 | Output Voltage at Previous Fault
U2-08 | DC Bus Voltage at Previous Fault
U2-09 | Output Power at Previous Fault
U2-10 | Torque Reference at Previous Fault
U2-11 | Input Terminal Status at Previous Fault
U2-12 | Output Terminal Status at Previous Fault
U2-13 | Drive Operation Status at Previous Fault
U2-14 | Cumulative Operation Time at Previous Fault
U2-15 | Soft Starter Speed Reference at Previous Fault
U2-16 | Motor q-Axis Current at Previous Fault
U2-17 | Motor d-Axis Current at Previous Fault
U3-01 | Most Recent Fault
U3-02 | 2nd Most Recent Fault
U3-03 | 3rd Most Recent Fault
U3-04 | 4th Most Recent Fault
U3-05 | 5th Most Recent Fault
U3-06 | 6th Most Recent Fault
U3-07 | 7th Most Recent Fault
U3-08 | 8th Most Recent Fault
U3-09 | 9th Most Recent Fault
U3-10 | 10th Most Recent Fault
U3-11 | Cumulative Operation Time at Most Recent Fault
Monitor catalogue PDF401 — PDF page 401
| Source row | Monitor | Name | Description | Analog output level | Unit | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | U2-02 | Previous Fault | Displays the previous fault. | No signal output avail. | – | A | A | A | 81 |
| 2 | U2-03 | Frequency Reference at Previous Fault | Displays the frequency reference at the previous fault. | No signal output avail. | 0.01 Hz | A | A | A | 82 |
| 3 | U2-04 | Output Frequency at Previous Fault | Displays the output frequency at the previous fault. | No signal output avail. | 0.01 Hz | A | A | A | 83 |
| 4 | U2-05 | Output Current at Previous Fault | Displays the output current at the previous fault. | No signal output avail. | <1> <2> | A | A | A | 84 |
| 5 | U2-06 | Motor Speed at Previous Fault | Displays the motor speed at the previous fault. | No signal output avail. | 0.01 Hz | − | A | − | 85 |
| 6 | U2-07 | Output Voltage at Previous Fault | Displays the output voltage at the previous fault. | No signal output avail. | 0.1 V | A | A | A | 86 |
| 7 | U2-08 | DC Bus Voltage at Previous Fault | Displays the DC bus voltage at the previous fault. | No signal output avail. | 1 V | A | A | A | 87 |
| 8 | U2-09 | Output Power at Previous Fault | Displays the output power at the previous fault. | No signal output avail. | 0.1 kW | A | A | A | 88 |
| 9 | U2-10 | Torque Reference at Previous Fault | Displays the torque reference at the previous fault. | No signal output avail. | 0.1% | − | Α | − | 89 |
| 10 | U2-11 | Input Terminal Status at Previous Fault | Displays the input terminal status at the previous fault. Displayed as in U1-10. | No signal output avail. | – | A | A | A | 8A |
| 11 | U2-12 | Output Terminal Status at Previous Fault | Displays the output status at the previous fault. Displays the same status displayed in U1-11. | No signal output avail. | – | A | A | A | 8B |
| 12 | U2-13 | Drive Operation Status at Previous Fault | Displays the operation status of the drive at the previous fault. Displays the same status displayed in U1-12. | No signal output avail. | – | A | A | A | 8C |
| 13 | U2-14 | Cumulative Operation Time at Previous Fault | Displays the cumulative operation time at the previous fault. | No signal output avail. | 1 H | A | A | A | 8D |
| 14 | U2-15 | Soft Starter Speed Reference at Previous Fault | Displays the run speed after a soft start when a previous fault occurred. Displayed as in U1-16. | No signal output avail. | 0.01 % | A | A | A | 7E0 |
| 15 | U2-16 | Motor q-Axis Current at Previous Fault | Displays the q-axis current for the motor at the previous fault. | No signal output avail. | 0.10 % | A | A | A | 7E1 |
| 16 | U2-17 | Motor d-Axis Current at Previous Fault | Displays the d-axis current for the motor at the previous fault. | No signal output avail. | 0.10 % | − | A | A | 7E2 |
| 17 | U3-01 | Most Recent Fault | Displays the most recent fault. | No signal output avail. | – | A | A | A | 90 (800) |
| 18 | U3-02 | 2nd Most Recent Fault | Displays the second most recent fault. | No signal output avail. | – | A | A | A | 91 (801) |
| 19 | U3-03 | 3rd Most Recent Fault | Displays the third most recent fault. | No signal output avail. | – | A | A | A | 92 (802) |
| 20 | U3-04 | 4th Most Recent Fault | Displays the fourth most recent fault. | No signal output avail. | – | A | A | A | 93 (803) |
| 21 | U3-05 | 5th Most Recent Fault | Displays the fifth most recent fault. | No signal output avail. | – | A | A | A | 804 |
| 22 | U3-06 | 6th Most Recent Fault | Displays the sixth most recent fault. | No signal output avail. | – | A | A | A | 805 |
| 23 | U3-07 | 7th Most Recent Fault | Displays the seventh most recent fault. | No signal output avail. | – | A | A | A | 806 |
| 24 | U3-08 | 8th Most Recent Fault | Displays the eighth most recent fault. | No signal output avail. | – | A | A | A | 807 |
| 25 | U3-09 | 9th Most Recent Fault | Displays the ninth most recent fault. | No signal output avail. | – | A | A | A | 808 |
| 26 | U3-10 | 10th Most Recent Fault | Displays the tenth most recent fault. | No signal output avail. | – | A | A | A | 809 |
| 27 | U3-11 | Cumulative Operation Time at Most Recent Fault | Displays the cumulative operation time at the most recent fault. | No signal output avail. | 1 h | A | A | A | 94 (80A) |
Manual — Fault times and maintenance monitors — page 402
Source reference: SIEP C71060618F, December 2016, physical PDF page 402. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No.; Name; Description; Analog Output Level; Unit
Control Mode: V/f, OLV, PM; Addr. Hex.
OLV
PM
U4: Maintenance Monitors Use U4 monitors to display drive maintenance information.
B.2 Parameter Table
U3-12 | Cumulative Operation Time at 2nd Most Recent Fault
U3-13 | Cumulative Operation Time at 3rd Most Recent Fault
U3-14 | Cumulative Operation Time at 4th Most Recent Fault
U3-15 | Cumulative Operation Time at 5th Most Recent Fault
U3-16 | Cumulative Operation Time at 6th Most Recent Fault
U3-17 | Cumulative Operation Time at 7th Most Recent Fault
U3-18 | Cumulative Operation Time at 8th Most Recent Fault
U3-19 | Cumulative Operation Time at 9th Most Recent Fault
U3-20 | Cumulative Operation Time at 10th Most Recent Fault
U4-01 <7> | Accumulated Operation Time
U4-02 | Number of Run Commands
U4-03 <5> <8> | Cooling Fan Operation Time
U4-04 | Cooling Fan Maintenance
U4-05 | Capacitor Maintenance
U4-06 <5> | Soft Charge Bypass Relay Maintenance
U4-07 <5> | IGBT Maintenance
U4-08 <6> | Heatsink Temperature
U4-09 | LED Check
U4-10 | kWh, Lower 4 Digits
U4-11 | kWh, Upper 5 Digits
Monitor catalogue PDF402 — PDF page 402
| Source row | Monitor | Name | Description | Analog output level | Unit | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | U3-12 | Cumulative Operation Time at 2nd Most Recent Fault | Displays the cumulative operation time at the second most recent fault. | No signal output avail. | 1 h | A | A | A | 95 (80B) |
| 2 | U3-13 | Cumulative Operation Time at 3rd Most Recent Fault | Displays the cumulative operation time at the third most recent fault. | No signal output avail. | 1 h | A | A | A | 96 (80C) |
| 3 | U3-14 | Cumulative Operation Time at 4th Most Recent Fault | Displays the cumulative operation time at the fourth most recent fault. | No signal output avail. | 1 h | A | A | A | 97 (80D) |
| 4 | U3-15 | Cumulative Operation Time at 5th Most Recent Fault | Displays the cumulative operation time at the fifth most recent fault. | No signal output avail. | 1 h | A | A | A | 80E |
| 5 | U3-16 | Cumulative Operation Time at 6th Most Recent Fault | Displays the cumulative operation time at the sixth most recent fault. | No signal output avail. | 1 h | A | A | A | 80F |
| 6 | U3-17 | Cumulative Operation Time at 7th Most Recent Fault | Displays the cumulative operation time at the seventh most recent fault. | No signal output avail. | 1 h | A | A | A | 810 |
| 7 | U3-18 | Cumulative Operation Time at 8th Most Recent Fault | Displays the cumulative operation time at the eighth most recent fault. | No signal output avail. | 1 h | A | A | A | 811 |
| 8 | U3-19 | Cumulative Operation Time at 9th Most Recent Fault | Displays the cumulative operation time at the ninth most recent fault. | No signal output avail. | 1 h | A | A | A | 812 |
| 9 | U3-20 | Cumulative Operation Time at 10th Most Recent Fault | Displays the cumulative operation time at the tenth most recent fault. | No signal output avail. | 1 h | A | A | A | 813 |
| 10 | U4-01 <7> | Accumulated Operation Time | Displays the cumulative operation time of the drive. The value for the cumulative operation time counter can be reset in parameter o4-01. Use parameter o4-02 to determine if the operation time should start as soon as the power is switched on or only while the run command is present. The maximum number displayed is 99999, after which the value is reset to 0. | No signal output avail. | 1 h | A | A | A | 4C |
| 11 | U4-02 | Number of Run Commands | Displays the number of times the run command is entered. Reset the number of run commands using parameter o4-13. This value will reset to 0 and start counting again after reaching 65535. | No signal output avail. | – | A | A | A | 75 |
| 12 | U4-03 <5> <8> | Cooling Fan Operation Time | Displays the cumulative operation time of the cooling fan. The default value for the fan operation time is reset in parameter o4-03. This value will reset to 0 and start counting again after reaching 99999. <4> | No signal output avail. | 1 h | A | A | A | 67 |
| 13 | U4-04 | Cooling Fan Maintenance | Displays main cooling fan usage time in as a percentage of their expected performance life. Parameter o4-03 can be used to reset this monitor. | No signal output avail. | 1% | A | A | A | 7E |
| 14 | U4-05 | Capacitor Maintenance | Displays main circuit capacitor usage time in as a percentage of their expected performance life. Parameter o4-05 can be used to reset this monitor. | No signal output avail. | 1% | A | A | A | 7C |
| 15 | U4-06 <5> | Soft Charge Bypass Relay Maintenance | Displays the soft charge bypass relay maintenance time as a percentage of the estimated product life. Parameter o4-07 can be used to reset this monitor. | No signal output avail. | 1% | A | A | A | 7D6 |
| 16 | U4-07 <5> | IGBT Maintenance | Displays IGBT usage time as a percent of expected performance life. Parameter o4-09 can be used to reset this monitor. | No signal output avail. | 1% | A | A | A | 7D7 |
| 17 | U4-08 <6> | Heatsink Temperature | Displays the heatsink temperature. | 10 V: 100 °C | 1 °C | A | A | A | 68 |
| 18 | U4-09 | LED Check | Lights all segments of the LED to verify that the display is working properly. | No signal output avail. | – | A | A | A | 3C |
| 19 | U4-10 | kWh, Lower 4 Digits | Monitors the drive output power. The value is shown as a 9 digit number displayed across two monitor parameters, U4-10 and U4-11. Example: 12345678.9 kWh is displayed as: U4-10: 678.9 kWh U4-11: 12345 MWh | No signal output avail. | kWh | A | A | A | 5C |
| 20 | U4-11 | kWh, Upper 5 Digits | Monitors the drive output power. The value is shown as a 9 digit number displayed across two monitor parameters, U4-10 and U4-11. Example: 12345678.9 kWh is displayed as: U4-10: 678.9 kWh U4-11: 12345 MWh | No signal output avail. | MWh | A | A | A | 5D |
Manual — Reference source and run state monitors — page 403
Source reference: SIEP C71060618F, December 2016, physical PDF page 403. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No.; Name; Description; Analog Output Level; Unit
Control Mode: V/f, OLV, PM; Addr. Hex.
OLV
PM
U5: PID Monitor Use U5 monitors to view application-specific settings.
B.2 Parameter Table
B
Parameter List
U4-13 | Peak Hold Current
U4-14 | Peak Hold Output Frequency
U4-16 | Motor Overload Estimate (oL1)
U4-18 | Frequency Reference Source Selection
U4-19 | Frequency Reference from MEMOBUS/Modbus Comm.
U4-20 | Option Frequency Reference
U4-21 | Run Command Source Selection
U4-22 | MEMOBUS/Modbus Communications Reference
U4-23 | Option Card Reference
Monitor catalogue PDF403 — PDF page 403
| Source row | Monitor | Name | Description | Analog output level | Unit | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | U4-13 | Peak Hold Current | Displays the peak hold current during run. | No signal output avail. | 0.01 A <2> | A | A | A | 7CF |
| 2 | U4-14 | Peak Hold Output Frequency | Displays the output frequency when operating at the peak hold current. | No signal output avail. | 0.01 Hz | A | A | A | 7D0 |
| 3 | U4-16 | Motor Overload Estimate (oL1) | 100% = oL1 detection level | 100% = oL1 detection level | 0.1% | A | A | A | 7D8 |
| 4 | U4-18 | Frequency Reference Source Selection | Displays the source for the frequency reference as XY-nn. X: indicates which reference is used: 1 = Reference 1 (b1-01) 2 = Reference 2 (b1-15) Y-nn: indicates the reference source 0-01 = Operator (d1-01) 1-01 = Analog (terminal A1) 1-02 = Analog (terminal A2) 2-02 to 17 = Multi-step speed (d1-02 to 17) 3-01 = MEMOBUS/Modbus comm. 4-01 = Option 5-01 = Pulse Input 6-01 = CASE 7-01 = DWEZ | – | – | A | A | A | 7DA |
| 5 | U4-19 | Frequency Reference from MEMOBUS/Modbus Comm. | Displays the frequency reference provided by MEMOBUS/ Modbus (decimal). | – | – | A | A | A | 7DB |
| 6 | U4-20 | Option Frequency Reference | Displays the frequency reference input by an option card (decimal). | – | – | A | A | A | 7DD |
| 7 | U4-21 | Run Command Source Selection | Displays the source for the Run command as XY-nn. X: Indicates which Run source is used: 1 = Reference 1 (b1-02) 2 = Reference 2 (b1-16) Y: Input power supply data 0 = Operator 1 = External terminals 2 = Not used 3 = MEMOBUS/Modbus communications 4 = Option 5 = Not used 6 = CASE 7 = DWEZ nn: Run command limit status data 00: No limit status. 01: Run command was left on when stopped in the PRG mode. 02: Run command was left on when switching from LOCAL to REMOTE operation. 03: Waiting for the soft charge bypass contactor after the power is switched on (Uv or Uv1 flashes after 10 seconds). 04: Waiting for “Run Command Prohibited” time period to end. 05: Fast-stop (digital input (H1-□□ = 15), operator) 06: b1-17 (run command given at power-up). 07: During Baseblock while coast to stop with timer 08: Frequency reference is below minimal reference during Baseblock 09: Waiting for Enter command 10: Run command was switched on while copying parameters | – | – | A | A | A | 7DD |
| 8 | U4-22 | MEMOBUS/Modbus Communications Reference | Displays the drive control data set by MEMOBUS/Modbus communications register No. 0001H as a 4 digit hexadecimal number. | – | – | A | A | A | 7DE |
| 9 | U4-23 | Option Card Reference | Displays drive control data set by an option card as a 4 digit hexadecimal number. | – | – | A | A | A | 7DF |
Manual — PID, control and custom monitors — page 404
Source reference: SIEP C71060618F, December 2016, physical PDF page 404. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No.; Name; Description; Analog Output Level; Unit
Control Mode: V/f, OLV, PM; Addr. Hex.
OLV
PM
U6: Control Monitor Use U6 monitors to display drive control information.
U8: Custom Monitors for DriveWorksEZ U8 monitors are reserved for DriveWorksEZ
B.2 Parameter Table
U5-01 | PID Feedback
U5-02 | PID Input
U5-03 | PID Output
U5-04 | PID Setpoint
U5-05 | PID Differential Feedback
U5-06 | PID Adjusted Feedback
U6-01 | Motor Secondary Current (Iq)
U6-02 | Motor Excitation Current (ld)
U6-03 | ASR Input
U6-04 | ASR Output
U6-05 | Output voltage reference (Vq)
U6-06 | Output Voltage Reference (Vd)
U6-07 | q-axis ACR Output
U6-08 | d-Axis ACR Output
U6-20 | Frequency Reference Bias (Up/Down 2)
U6-21 | Offset Frequency
U6-80 to U6-99 | Option Monitors 1 to 20
U8-01 | –
U8-02 | –
U8-03 | –
U8-04 | –
U8-05 | –
U8-06 | –
U8-07 | –
Monitor catalogue PDF404 — PDF page 404
| Source row | Monitor | Name | Description | Analog output level | Unit | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | U5-01 | PID Feedback | Displays the PID feedback value in. | 10 V: 100% (max. freq.) | 0.01 % | A | A | A | 57 |
| 2 | U5-02 | PID Input | Displays the amount of PID input (deviation between PID target and feedback). | 10 V: 100% (max. freq.) | 0.01 % | A | A | A | 63 |
| 3 | U5-03 | PID Output | Displays PID control output. | 10 V: 100% (max. freq.) | 0.01 % | A | A | A | 64 |
| 4 | U5-04 | PID Setpoint | Displays the PID setpoint. | 10 V: 100% (max. freq.) | 0.01 % | A | A | A | 65 |
| 5 | U5-05 | PID Differential Feedback | Displays the 2nd PID feedback value if differential feedback is used. | 10 V: 100% (max. freq.) | 0.01 % | A | A | A | 7D2 |
| 6 | U5-06 | PID Adjusted Feedback | Displays the difference of both feedback values if differential feedback is used (U5-01) - (U5-05). If differential feedback is not used, then U5-01 and U5-06 will be the same. | 10 V: 100% (max. freq.) | 0.01 % | A | A | A | 7D3 |
| 7 | U6-01 | Motor Secondary Current (Iq) | Displays the value of the motor secondary current (Iq). | 10 V: 100% | 0.1% | A | A | A | 51 |
| 8 | U6-02 | Motor Excitation Current (ld) | Displays the value calculated for the motor excitation current (Id). | 10 V: 100% | 0.1% | − | A | A | 52 |
| 9 | U6-03 | ASR Input | Displays the ASR input value if V/f Control with Simple PG Feedback is enabled. | 10 V: 100% (max. freq.) | 0.1% | A | − | − | 54 |
| 10 | U6-04 | ASR Output | Displays the ASR output value if V/f Control with Simple PG Feedback is enabled. | 10 V: 100% (max. freq.) | 0.1% | A | − | − | 55 |
| 11 | U6-05 | Output voltage reference (Vq) | Output voltage reference (Vq). (q-axis) | 10 V: 200 V (400 V) | 0.1 Vac | − | A | A | 59 |
| 12 | U6-06 | Output Voltage Reference (Vd) | Output voltage reference (Vd). (d-axis) | 10 V: 200 V (400 V) | 0.1 Vac | − | A | A | 5A |
| 13 | U6-07 | q-axis ACR Output | Displays the current control (ACR) output of for the motor secondary current (Iq). | 10 V: 100% | 0.1% | − | A | − | 5F |
| 14 | U6-08 | d-Axis ACR Output | Displays the current control (ACR) output of for the motor excitation current (Id). | 10 V: 100% | 0.1% | − | A | − | 60 |
| 15 | U6-20 | Frequency Reference Bias (Up/Down 2) | Displays the bias value used to adjust the frequency reference. | 10 V: max. frequency | 0.1% | A | A | A | 7D4 |
| 16 | U6-21 | Offset Frequency | The total value of the offset frequencies d7-01, d7-02 and d7-03 selected with digital inputs 44 to 46 is displayed. | 10 V: max. frequency | 0.1% | A | A | A | 7D5 |
| 17 | U6-80 to U6-99 | Option Monitors 1 to 20 | Monitors reserved for use by the communication option card. Monitor content varies based on the communication option connected to the drive. Refer to the instruction manual for the option card for more information.. | No signal output avail. | – | A | A | A | 7B0 to 7F9 |
| 18 | U8-01 | – | Reserved for DriveWorksEZ, Monitor 1. | – | 0.01 % | Α | A | Α | 1950 |
| 19 | U8-02 | – | Reserved for DriveWorksEZ, Monitor 2. | – | 0.01 % | A | A | A | 1951 |
| 20 | U8-03 | – | Reserved for DriveWorksEZ, Monitor 3. | – | 0.01 % | A | A | A | 1952 |
| 21 | U8-04 | – | Reserved for DriveWorksEZ, Monitor 4. | – | 0.01 % | A | A | A | 1953 |
| 22 | U8-05 | – | Reserved for DriveWorksEZ, Monitor 5. | – | 0.01 % | A | A | A | 1954 |
| 23 | U8-06 | – | Reserved for DriveWorksEZ, Monitor 6. | – | 0.01 % | A | A | A | 1955 |
| 24 | U8-07 | – | Reserved for DriveWorksEZ, Monitor 7. | – | 0.01 % | A | A | A | 1956 |
Manual — Custom monitor continuation and monitor footnotes — page 405
Source reference: SIEP C71060618F, December 2016, physical PDF page 405. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No.; Name; Description; Analog Output Level; Unit
Control Mode: V/f, OLV, PM; Addr. Hex.
OLV
PM
<1> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. <2> U1-03, U2-05, and U4-13 display monitor contents in amp units. When reading the value of these monitors via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current. <3> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330 <4> Available in drive software versions PRG: 1011 and later. Maximum value is 65536 in drive software versions PRG: 1010 and earlier. <5> When this value reaches 100%, the maintenance period has been reached for the component in question and the drive is at risk of faulting out due to component failure. Periodically check the maintenance monitors to avoid this situation. <6> Available in drive software versions PRG: 1011 and later. <7> MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register 0099H. <8> MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register 009BH.
B.2 Parameter Table
B
Parameter List
U8-08 | –
U8-09 | –
U8-10 | –
Monitor catalogue PDF405 — PDF page 405
| Source row | Monitor | Name | Description | Analog output level | Unit | Control mode V/f | Control mode OLV | Control mode PM | Address (hex) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | U8-08 | – | Reserved for DriveWorksEZ, Monitor 8. | – | 0.01 % | A | A | A | 1957 |
| 2 | U8-09 | – | Reserved for DriveWorksEZ, Monitor 9. | – | 0.01 % | A | A | A | 1958 |
| 3 | U8-10 | – | Reserved for DriveWorksEZ, Monitor 10. | – | 0.01 % | A | A | A | 1959 |
Manual — Motor 1 control-dependent defaults — page 406
Source reference: SIEP C71060618F, December 2016, physical PDF page 406. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
B.3 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2). These parameters are initialized to the shown values if the control mode is changed.
◆ A1-02 (Motor 1 Control Mode) Dependent Parameters
Table B.1 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
Parameter Description Setting Range Resolution
Control Modes (A1-02)
V/f (0) OLV (2) PM (5)
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection. <2> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. <3> Default setting value is dependent on parameter E5-01, Motor Code Selection.
b3-02 | Speed Search deactivation current
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type)
b8-02 | Energy Saving gain
C2-01 | S-curve time at acceleration start
C3-01 | Slip compensation gain
C3-02 | Slip compensation time constant
C4-01 | Torque compensation gain
C4-02 | Torque comp. primary delay time
C6-02 | Carrier frequency
E1-04 | Maximum output frequency
E1-05 | Maximum output voltage <2>
E1-06 | Base Frequency
E1-07 | Middle output frequency
E1-08 | Middle output freq. voltage <2>
E1-09 | Minimum output frequency
E1-10 | Minimum output voltage <2>
E1-11 | Middle output frequency 2
E1-12 | Middle output freq. voltage 2 <2>
E1-13 | Base voltage <2>
L1-01 | Motor protection selection
L3-20 | Main power circuit voltage adjustment gain
L3-21 | Accel/decel rate calculation gain
Table B.1 A1-02 Motor1 control-mode-dependent defaults — PDF page 406
| Source row | Parameter | Description | Setting range | Resolution | V/f (0) default | OLV (2) default | PM (5) default |
|---|---|---|---|---|---|---|---|
| 1 | b3-02 | Speed Search deactivation current | 0 to 200 | 1% | 120 | 100 | – |
| 2 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | 0.00 to 6.00 | – | 0.50 <1> | 0.50 <1> | 0.30 |
| 3 | b8-02 | Energy Saving gain | 0.0 to 10.0 | 0.1 | – | 0.7 | – |
| 4 | C2-01 | S-curve time at acceleration start | 0.00 to 10.00 | 0.01 s | 0.20 | 0.20 | 1.00 |
| 5 | C3-01 | Slip compensation gain | 0.0 to 2.5 | 0.1 | 0.0 | 1.0 | – |
| 6 | C3-02 | Slip compensation time constant | 0 to 10000 | 1 ms | 2000 | 200 | – |
| 7 | C4-01 | Torque compensation gain | 0.00 to 2.50 | 0.01 | 1.00 | 1.00 | 0.00 |
| 8 | C4-02 | Torque comp. primary delay time | 0 to 10000 | 1 ms | 200 | 20 | 100 |
| 9 | C6-02 | Carrier frequency | 1 to F | 1 | 7 <1> | 7 <1> | 2 |
| 10 | E1-04 | Maximum output frequency | 40.0 to 400.0 | 0.1 Hz | 60.0 | 60.0 | <3> |
| 11 | E1-05 | Maximum output voltage <2> | 0.0 to 255.0 | 0.1 V | 230.0 | 230.0 | <3> |
| 12 | E1-06 | Base Frequency | 0.0 to 400.0 | 0.1 Hz | 60.0 | 60.0 | <3> |
| 13 | E1-07 | Middle output frequency | 0.0 to 400.0 | 0.1 Hz | 3.0 | 3.0 | – |
| 14 | E1-08 | Middle output freq. voltage <2> | 0.0 to 255.0 | 0.1 V | 18.4 | 13.8 | – |
| 15 | E1-09 | Minimum output frequency | 0.0 to 400.0 | 0.1 Hz | 1.5 | 0.5 | <3> |
| 16 | E1-10 | Minimum output voltage <2> | 0.0 to 255.0 | 0.1 V | 13.8 | 2.9 | – |
| 17 | E1-11 | Middle output frequency 2 | 0.0 to 400.0 | 0.1 Hz | 0.0 | 0.0 | – |
| 18 | E1-12 | Middle output freq. voltage 2 <2> | 0.0 to 255.0 | 0.1 V | 0.0 | 0.0 | – |
| 19 | E1-13 | Base voltage <2> | 0.0 to 255.0 | 0.1 V | 0.0 | 0.0 | – |
| 20 | L1-01 | Motor protection selection | 0 to 4 | – | 1 | 1 | 4 |
| 21 | L3-20 | Main power circuit voltage adjustment gain | 0.00 to 5.00 | 0.01 | 1.00 | 0.30 | 0.65 |
| 22 | L3-21 | Accel/decel rate calculation gain | 0.00 to 200.00 | 0.01 | 1.00 | 1.00 | 2.50 |
Manual — Motor 2 control-dependent defaults — page 407
Source reference: SIEP C71060618F, December 2016, physical PDF page 407. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ E3-01 (Motor 2 Control Mode) Dependent Parameters
Table B.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
Parameter Description Setting Range Resolution
Control Modes (E3-01)
V/f (0) OLV (2)
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
B.3 Control Mode Dependent Parameter Default Values
B
Parameter List
E3-04 | Maximum output frequency
E3-05 | Maximum output voltage <1>
E3-06 | Base Frequency
E3-07 | Middle output frequency
E3-08 | Middle output freq. voltage <1>
E3-09 | Minimum output frequency
E3-10 | Minimum output voltage <1>
E3-11 | Middle output frequency 2
E3-12 | Middle output freq. voltage 2 <1>
E3-13 | Base voltage <1>
E3-14 | Motor 2 Slip compensation gain
Table B.2 E3-01 Motor2 control-mode-dependent defaults — PDF page 407
| Source row | Parameter | Description | Setting range | Resolution | V/f (0) default | OLV (2) default |
|---|---|---|---|---|---|---|
| 1 | E3-04 | Maximum output frequency | 40.0 to 400.0 | 0.1 Hz | 60.0 | 60.0 |
| 2 | E3-05 | Maximum output voltage <1> | 0.0 to 255.0 | 0.1 V | 200.0 | 230.0 |
| 3 | E3-06 | Base Frequency | 0.0 to 400.0 | 0.1 Hz | 60.0 | 60.0 |
| 4 | E3-07 | Middle output frequency | 0.0 to 400.0 | 0.1 Hz | 3.0 | 3.0 |
| 5 | E3-08 | Middle output freq. voltage <1> | 0.0 to 255.0 | 0.1 V | 18.4 | 13.8 |
| 6 | E3-09 | Minimum output frequency | 0.0 to 400.0 | 0.1 Hz | 1.5 | 0.5 |
| 7 | E3-10 | Minimum output voltage <1> | 0.0 to 255.0 | 0.1 V | 13.8 | 2.9 |
| 8 | E3-11 | Middle output frequency 2 | 0.0 to 400.0 | 0.1 Hz | 0.0 | 0.0 |
| 9 | E3-12 | Middle output freq. voltage 2 <1> | 0.0 to 255.0 | 0.1 V | 0.0 | 0.0 |
| 10 | E3-13 | Base voltage <1> | 0.0 to 255.0 | 0.1 V | 0.0 | 0.0 |
| 11 | E3-14 | Motor 2 Slip compensation gain | 0.0 to 2.5 | 0.1 | 0.0 | 1.0 |
Manual — V/f patterns by drive model range — page 408
Source reference: SIEP C71060618F, December 2016, physical PDF page 408. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
B.4 V/f Pattern Default Values
The tables below show the V/f pattern settings default values depending on the control mode (A1-02) and the V/f pattern selection (E1-03 in V/f Control).
Table B.3 E1-03 V/f Pattern Settings for Drive Capacity: Models BA0001 to BA0010, 2A0001 to 2A0010, and 4A0001 to 4A0005
No.; Unit; V/f Control E1-03 settings0,1,2,3,4,5,6,7,8,9,A,B,C,D,E,F; OLV
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Table B.4 E1-03 V/f Pattern Settings for Drive Capacity: Models BA0012 to BA0018, 2A0012 to 2A0069, and 4A0007 to 4A0038
E1-04 | Hz | 50.0
E1-05 <1> | V | 200
E1-06 | Hz | 50.0
E1-07 | Hz | 2.5
E1-08 <1> | V | 16.0
E1-09 | Hz | 1.3
E1-10 <1> | V | 12.0
E1-08 <1> | V | 14.0
E1-10 <1> | V | 7.0
Table B.3 V/f default patterns models BA0001–BA0010;2A0001–2A0010;4A0001–4A0005 — PDF page 408
| Source row | Parameter | Unit | V/f E1-03=0 | V/f E1-03=1 | V/f E1-03=2 | V/f E1-03=3 | V/f E1-03=4 | V/f E1-03=5 | V/f E1-03=6 | V/f E1-03=7 | V/f E1-03=8 | V/f E1-03=9 | V/f E1-03=A | V/f E1-03=B | V/f E1-03=C | V/f E1-03=D | V/f E1-03=E | V/f E1-03=F | OLV |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E1-04 | Hz | 50.0 | 60.0 | 60.0 | 72.0 | 50.0 | 50.0 | 60.0 | 60.0 | 50.0 | 50.0 | 60.0 | 60.0 | 90.0 | 120 | 180 | 60.0 | 60.0 |
| 2 | E1-05 <1> | V | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 230 | 230 |
| 3 | E1-06 | Hz | 50.0 | 60.0 | 50.0 | 60.0 | 50.0 | 50.0 | 60.0 | 60.0 | 50.0 | 50.0 | 60.0 | 60.0 | 60.0 | 60.0 | 60.0 | 60.0 | 60.0 |
| 4 | E1-07 | Hz | 2.5 | 3.0 | 3.0 | 3.0 | 25.0 | 25.0 | 30.0 | 30.0 | 2.5 | 2.5 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 |
| 5 | E1-08 <1> | V | 16.0 | 16.0 | 16.0 | 16.0 | 35.0 | 50.0 | 35.0 | 50.0 | 19.0 | 24.0 | 19.0 | 24.0 | 16.0 | 16.0 | 16.0 | 18.4 | 13.8 |
| 6 | E1-09 | Hz | 1.3 | 1.5 | 1.5 | 1.5 | 1.3 | 1.3 | 1.5 | 1.5 | 1.3 | 1.3 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 0.5 |
| 7 | E1-10 <1> | V | 12.0 | 12.0 | 12.0 | 12.0 | 8.0 | 9.0 | 8.0 | 9.0 | 12.0 | 13.0 | 12.0 | 15.0 | 12.0 | 12.0 | 12.0 | 13.8 | 2.9 |
Table B.4 V/f default patterns models BA0012–BA0018;2A0012–2A0069;4A0007–4A0038 — PDF page 408
| Source row | Parameter | Unit | V/f E1-03=0 | V/f E1-03=1 | V/f E1-03=2 | V/f E1-03=3 | V/f E1-03=4 | V/f E1-03=5 | V/f E1-03=6 | V/f E1-03=7 | V/f E1-03=8 | V/f E1-03=9 | V/f E1-03=A | V/f E1-03=B | V/f E1-03=C | V/f E1-03=D | V/f E1-03=E | V/f E1-03=F | OLV |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E1-04 | Hz | 50.0 | 60.0 | 60.0 | 72.0 | 50.0 | 50.0 | 60.0 | 60.0 | 50.0 | 50.0 | 60.0 | 60.0 | 90.0 | 120 | 180 | 60.0 | 60.0 |
| 2 | E1-05 <1> | V | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 200 | 230 | 230 |
| 3 | E1-06 | Hz | 50.0 | 60.0 | 50.0 | 60.0 | 50.0 | 50.0 | 60.0 | 60.0 | 50.0 | 50.0 | 60.0 | 60.0 | 60.0 | 60.0 | 60.0 | 60.0 | 60.0 |
| 4 | E1-07 | Hz | 2.5 | 3.0 | 3.0 | 3.0 | 25.0 | 25.0 | 30.0 | 30.0 | 2.5 | 2.5 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 |
| 5 | E1-08 <1> | V | 14.0 | 14.0 | 14.0 | 14.0 | 35.0 | 50.0 | 35.0 | 50.0 | 18.0 | 23.0 | 18.0 | 23.0 | 14.0 | 14.0 | 14.0 | 16.1 | 12.7 |
| 6 | E1-09 | Hz | 1.3 | 1.5 | 1.5 | 1.5 | 1.3 | 1.3 | 1.5 | 1.5 | 1.3 | 1.3 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 0.5 |
| 7 | E1-10 <1> | V | 7.0 | 7.0 | 7.0 | 7.0 | 6.0 | 7.0 | 6.0 | 7.0 | 9.0 | 11.0 | 9.0 | 13.0 | 7.0 | 7.0 | 7.0 | 7.0 | 2.3 |
Manual — Single-phase 200V small-model defaults — page 409
Source reference: SIEP C71060618F, December 2016, physical PDF page 409. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
Table B.5 Single-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Settings
No. Description Unit Default Settings
B
Parameter List
− | Model | −
o2-04 | Drive Model Selection | Hex
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor code | hex
L2-02 | Momentary power loss ride-through time | s
L2-03 | Mom. power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier freq. reduction sel. | −
n1-03 | Hunting Prev. Time Const. | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults single-phase 200V PDF409 — PDF page 409
| Source row | Parameter | Description | Unit | BA0001 / HD (C6-01=0) | BA0001 / ND (C6-01=1) | BA0002 / HD (C6-01=0) | BA0002 / ND (C6-01=1) | BA0003 / HD (C6-01=0) | BA0003 / ND (C6-01=1) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | BA0001 | BA0001 | BA0002 | BA0002 | BA0003 | BA0003 |
| 2 | o2-04 | Drive Model Selection | Hex | 30 | 30 | 31 | 31 | 32 | 32 |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 0.1 | 0.2 | 0.2 | 0.4 | 0.4 | 0.75 |
| 6 | b3-06 | Speed Search current 1 | − | 1 | 1 | 1 | 1 | 1 | 1 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 481.7 | 356.9 | 356.9 | 288.2 | 288.2 | 223.7 |
| 9 | C6-02 | Carrier frequency | − | 4 | 7 | 4 | 7 | 4 | 7 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 0.6 | 1.1 | 1.1 | 1.9 | 1.9 | 3.3 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 2.5 | 2.6 | 2.6 | 2.9 | 2.9 | 2.5 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 0.4 | 0.8 | 0.8 | 1.2 | 1.2 | 1.8 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 35.98 | 20.56 | 20.56 | 9.84 | 9.842 | 5.156 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 21.6 | 20.1 | 20.1 | 18.2 | 18.2 | 13.8 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 6 | 11 | 11 | 14 | 14 | 26 |
| 16 | E5-01 | Motor code | hex | FFFF | FFFF | FFFF | FFFF | 0002 | 0002 |
| 17 | L2-02 | Momentary power loss ride-through time | s | 0.1 | 0.1 | 0.1 | 0.1 | 0.1 | 0.1 |
| 18 | L2-03 | Mom. power loss Baseblock time | s | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.3 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 |
| 20 | L2-05 | Uv detection voltage | V dc | 160 | 160 | 160 | 160 | 160 | 160 |
| 21 | L3-24 | Motor acceleration time | s | 0.178 | 0.178 | 0.178 | 0.178 | 0.178 | 0.142 |
| 22 | L8-02 | Overheat alarm level | °C | 115 | 115 | 115 | 115 | 110 | 110 |
| 23 | L8-09 | Ground fault selection | − | 0 | 0 | 0 | 0 | 0 | 0 |
| 24 | L8-38 | Carrier freq. reduction sel. | − | 1 | 1 | 1 | 1 | 1 | 1 |
| 25 | n1-03 | Hunting Prev. Time Const. | ms | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Manual — Single-phase 200V large-model defaults and HD-only model — page 410
Source reference: SIEP C71060618F, December 2016, physical PDF page 410. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Description Unit Default Settings
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
− | Model | −
o2-04 | Drive Model Selection | Hex
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor Code | hex
L2-02 | Momentary power loss ride-through time | s
L2-03 | Momentary power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier frequency reduction selection | −
n1-03 | Hunting Prevention Time Constant | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults single-phase 200V PDF410 — PDF page 410
| Source row | Parameter | Description | Unit | BA0006 / HD (C6-01=0) | BA0006 / ND (C6-01=1) | BA0010 / HD (C6-01=0) | BA0010 / ND (C6-01=1) | BA0012 / HD (C6-01=0) | BA0012 / ND (C6-01=1) | BA0018 / HD (C6-01=0) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | BA0006 | BA0006 | BA0010 | BA0010 | BA0012 | BA0012 | BA0018 |
| 2 | o2-04 | Drive Model Selection | Hex | 33 | 33 | 34 | 34 | 35 | 35 | 37 |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND | HD |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 | 0 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 0.75 | 1.1 | 1.5 | 2.2 | 2.2 | 3.0 | 3.7 |
| 6 | b3-06 | Speed Search current 1 | − | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 223.7 | 169.4 | 169.4 | 156.8 | 156.8 | 136.4 | 122.9 |
| 9 | C6-02 | Carrier frequency | − | 4 | 7 | 3 | 7 | 3 | 7 | 3 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 3.3 | 6.2 | 6.2 | 8.5 | 8.5 | 11.4 | 14.0 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 2.5 | 2.6 | 2.6 | 2.9 | 2.9 | 2.7 | 2.73 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 1.8 | 2.8 | 2.8 | 3 | 3 | 3.7 | 4.5 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 5.156 | 1.997 | 1.997 | 1.601 | 1.601 | 1.034 | 0.771 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 13.8 | 18.5 | 18.5 | 18.4 | 18.4 | 19 | 19.6 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 26 | 53 | 53 | 77 | 77 | 91 | 112 |
| 16 | E5-01 | Motor Code | hex | 0003 | 0003 | 0005 | 0005 | 0006 | 0006 | 0008 |
| 17 | L2-02 | Momentary power loss ride-through time | s | 0.2 | 0.2 | 0.3 | 0.3 | 0.5 | 0.5 | 1.0 |
| 18 | L2-03 | Momentary power loss Baseblock time | s | 0.3 | 0.4 | 0.4 | 0.5 | 0.5 | 0.5 | 0.6 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 |
| 20 | L2-05 | Uv detection voltage | V dc | 160 | 160 | 160 | 160 | 160 | 160 | 160 |
| 21 | L3-24 | Motor acceleration time | s | 0.142 | 0.142 | 0.166 | 0.145 | 0.145 | 0.145 | 0.154 |
| 22 | L8-02 | Overheat alarm level | °C | 105 | 105 | 100 | 100 | 95 | 95 | 100 |
| 23 | L8-09 | Ground fault selection | − | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 24 | L8-38 | Carrier frequency reduction selection | − | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 25 | n1-03 | Hunting Prevention Time Constant | ms | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.50 |
Manual — Three-phase 200V small-model defaults — page 411
Source reference: SIEP C71060618F, December 2016, physical PDF page 411. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table B.6 Three-Phase, 200 V Class Drives Default Settings by Drive Capacity and ND/HD Setting
No. Description Unit Default Settings
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
B
Parameter List
− | Model | −
o2-04 | Drive Model Selection | Hex
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor Code | hex
L2-02 | Momentary power loss ride-through time | s
L2-03 | Momentary power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier frequency reduction selection | −
n1-03 | Hunting Prevention Time Constant | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults three-phase 200V PDF411 — PDF page 411
| Source row | Parameter | Description | Unit | 2A0001 / HD (C6-01=0) | 2A0001 / ND (C6-01=1) | 2A0002 / HD (C6-01=0) | 2A0002 / ND (C6-01=1) | 2A0004 / HD (C6-01=0) | 2A0004 / ND (C6-01=1) | 2A0006 / HD (C6-01=0) | 2A0006 / ND (C6-01=1) | 2A0010 / HD (C6-01=0) | 2A0010 / ND (C6-01=1) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | 2A0001 | 2A0001 | 2A0002 | 2A0002 | 2A0004 | 2A0004 | 2A0006 | 2A0006 | 2A0010 | 2A0010 |
| 2 | o2-04 | Drive Model Selection | Hex | 60 | 60 | 61 | 61 | 62 | 62 | 63 | 63 | 65 | 65 |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND | HD | ND | HD | ND |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 0.1 | 0.2 | 0.2 | 0.4 | 0.4 | 0.75 | 0.75 | 1.1 | 1.5 | 2.2 |
| 6 | b3-06 | Speed Search current 1 | − | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 0.5 | 0.5 | 0.5 | 0.5 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 481.7 | 356.9 | 356.9 | 288.2 | 288.2 | 223.7 | 223.7 | 196.6 | 169.4 | 156.8 |
| 9 | C6-02 | Carrier frequency | − | 4 | 7 | 4 | 7 | 4 | 7 | 4 | 7 | 3 | 7 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 0.6 | 1.1 | 1.1 | 1.9 | 1.9 | 3.3 | 3.3 | 4.9 | 6.2 | 8.5 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 2.5 | 2.6 | 2.6 | 2.9 | 2.9 | 2.5 | 2.5 | 2.6 | 2.6 | 2.9 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 0.4 | 0.8 | 0.8 | 1.2 | 1.2 | 1.8 | 1.8 | 2.3 | 2.8 | 3.0 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 35.98 | 20.56 | 20.56 | 9.84 | 9.842 | 5.156 | 5.156 | 3.577 | 1.997 | 1.601 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 21.6 | 20.1 | 20.1 | 18.2 | 18.2 | 13.8 | 13.8 | 18.5 | 18.5 | 18.4 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 6 | 11 | 11 | 14 | 14 | 26 | 26 | 38 | 53 | 77 |
| 16 | E5-01 | Motor Code | hex | FFFF | FFFF | FFFF | FFFF | 0002 | 0002 | 0003 | 0003 | 0005 | 0005 |
| 17 | L2-02 | Momentary power loss ride-through time | s | 0.1 | 0.1 | 0.1 | 0.1 | 0.1 | 0.1 | 0.2 | 0.2 | 0.3 | 0.3 |
| 18 | L2-03 | Momentary power loss Baseblock time | s | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | 0.3 | 0.3 | 0.4 | 0.4 | 0.5 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 |
| 20 | L2-05 | Uv detection voltage | V dc | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 |
| 21 | L3-24 | Motor acceleration time | s | 0.178 | 0.178 | 0.178 | 0.178 | 0.178 | 0.142 | 0.142 | 0.142 | 0.166 | 0.145 |
| 22 | L8-02 | Overheat alarm level | °C | 110 | 110 | 110 | 110 | 115 | 115 | 100 | 100 | 100 | 100 |
| 23 | L8-09 | Ground fault selection | − | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 24 | L8-38 | Carrier frequency reduction selection | − | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 25 | n1-03 | Hunting Prevention Time Constant | ms | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Manual — Three-phase 200V middle-model defaults — page 412
Source reference: SIEP C71060618F, December 2016, physical PDF page 412. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Description Unit Default Settings
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
− | Model | −
o2-04 | Drive Model Selection | Hex
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor Code | hex
L2-02 | Momentary power loss ride- through time | s
L2-03 | Momentary power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier frequency reduction selection | −
n1-03 | Hunting Prevention Time Constant | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults three-phase 200V PDF412 — PDF page 412
| Source row | Parameter | Description | Unit | 2A0012 / HD (C6-01=0) | 2A0012 / ND (C6-01=1) | 2A0020 / HD (C6-01=0) | 2A0020 / ND (C6-01=1) | 2A0030 / HD (C6-01=0) | 2A0030 / ND (C6-01=1) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | 2A0012 | 2A0012 | 2A0020 | 2A0020 | 2A0030 | 2A0030 |
| 2 | o2-04 | Drive Model Selection | Hex | 66 | 66 | 68 | 68 | 6A | 6A |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 2.2 | 3.0 | 3.7 | 5.5 | 5.5 | 7.5 |
| 6 | b3-06 | Speed Search current 1 | − | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 156.8 | 136.4 | 122.9 | 94.8 | 94.75 | 72.69 |
| 9 | C6-02 | Carrier frequency | − | 3 | 7 | 3 | 7 | 3 | 7 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 8.5 | 11.4 | 14 | 19.6 | 19.6 | 26.6 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 2.9 | 2.7 | 2.73 | 1.5 | 1.5 | 1.3 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 3.0 | 3.7 | 4.5 | 5.1 | 5.1 | 8.0 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 1.601 | 1.034 | 0.771 | 0.399 | 0.399 | 0.288 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 18.4 | 19 | 19.6 | 18.2 | 18.2 | 15.5 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 77 | 91 | 112 | 172 | 172 | 262 |
| 16 | E5-01 | Motor Code | hex | 0006 | 0006 | 0008 | 0008 | FFFF | FFFF |
| 17 | L2-02 | Momentary power loss ride- through time | s | 0.5 | 0.5 | 1 | 1 | 1.0 | 1.0 |
| 18 | L2-03 | Momentary power loss Baseblock time | s | 0.5 | 0.5 | 0.6 | 0.7 | 0.7 | 0.8 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.6 | 0.3 | 0.6 |
| 20 | L2-05 | Uv detection voltage | V dc | 190 | 190 | 190 | 190 | 190 | 190 |
| 21 | L3-24 | Motor acceleration time | s | 0.145 | 0.145 | 0.154 | 0.168 | 0.168 | 0.175 |
| 22 | L8-02 | Overheat alarm level | °C | 100 | 100 | 110 | 110 | 115 | 115 |
| 23 | L8-09 | Ground fault selection | − | 0 | 0 | 0 | 0 | 1 | 1 |
| 24 | L8-38 | Carrier frequency reduction selection | − | 1 | 1 | 1 | 1 | 2 | 2 |
| 25 | n1-03 | Hunting Prevention Time Constant | ms | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.00 | 1.00 | 1.00 | 1.00 | 1.50 | 1.50 |
Manual — Three-phase 200V large-model defaults — page 413
Source reference: SIEP C71060618F, December 2016, physical PDF page 413. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Description Unit Default Settings
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
B
Parameter List
− | Model | −
o2-04 | Drive Model Selection | Hex
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor Code | hex
L2-02 | Momentary power loss ride-through time | s
L2-03 | Momentary power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier frequency reduction selection | −
n1-03 | Hunting Prevention Time Constant | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults three-phase 200V PDF413 — PDF page 413
| Source row | Parameter | Description | Unit | 2A0040 / HD (C6-01=0) | 2A0040 / ND (C6-01=1) | 2A0056 / HD (C6-01=0) | 2A0056 / ND (C6-01=1) | 2A0069 / HD (C6-01=0) | 2A0069 / ND (C6-01=1) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | 2A0040 | 2A0040 | 2A0056 | 2A0056 | 2A0069 | 2A0069 |
| 2 | o2-04 | Drive Model Selection | Hex | 6B | 6B | 6D | 6D | 6E | 6E |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 7.5 | 11.0 | 11.0 | 15.0 | 15.0 | 18.5 |
| 6 | b3-06 | Speed Search current 1 | − | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 72.69 | 70.44 | 70.44 | 63.13 | 63.13 | 57.87 |
| 9 | C6-02 | Carrier frequency | − | 3 | 7 | 3 | 7 | 3 | 7 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 26.6 | 39.7 | 39.7 | 53 | 53 | 65.8 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 1.3 | 1.7 | 1.7 | 1.6 | 1.6 | 1.67 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 8.0 | 11.2 | 11.2 | 15.2 | 15.2 | 15.7 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 0.288 | 0.230 | 0.230 | 0.138 | 0.138 | 0.101 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 15.5 | 19.5 | 19.5 | 17.2 | 17.2 | 15.7 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 262 | 245 | 245 | 272 | 272 | 505 |
| 16 | E5-01 | Motor Code | hex | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF |
| 17 | L2-02 | Momentary power loss ride-through time | s | 1.0 | 1.0 | 2.0 | 2.0 | 2.0 | 2.0 |
| 18 | L2-03 | Momentary power loss Baseblock time | s | 0.8 | 0.9 | 0.9 | 1.0 | 1.0 | 1.0 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.3 | 0.6 | 0.6 |
| 20 | L2-05 | Uv detection voltage | V dc | 190 | 190 | 190 | 190 | 190 | 190 |
| 21 | L3-24 | Motor acceleration time | s | 0.175 | 0.265 | 0.265 | 0.244 | 0.244 | 0.317 |
| 22 | L8-02 | Overheat alarm level | °C | 121 | 121 | 120 | 120 | 120 | 120 |
| 23 | L8-09 | Ground fault selection | − | 1 | 1 | 1 | 1 | 1 | 1 |
| 24 | L8-38 | Carrier frequency reduction selection | − | 2 | 2 | 2 | 2 | 2 | 2 |
| 25 | n1-03 | Hunting Prevention Time Constant | ms | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 |
Manual — Three-phase 400V small-model defaults — page 414
Source reference: SIEP C71060618F, December 2016, physical PDF page 414. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table B.7 Three-Phase 400 V Class Drives Default Settings by Drive Capacity and ND/HD Setting
No. Description Unit Default Settings
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
− | Model | −
o2-04 | Drive Model Selection | Hex
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor Code | hex
L2-02 | Momentary power loss ride-through time | s
L2-03 | Momentary power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier frequency reduction selection | −
n1-03 | Hunting Prevention Time Constant | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults three-phase 400V PDF414 — PDF page 414
| Source row | Parameter | Description | Unit | 4A0001 / HD (C6-01=0) | 4A0001 / ND (C6-01=1) | 4A0002 / HD (C6-01=0) | 4A0002 / ND (C6-01=1) | 4A0004 / HD (C6-01=0) | 4A0004 / ND (C6-01=1) | 4A0005 / HD (C6-01=0) | 4A0005 / ND (C6-01=1) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | 4A0001 | 4A0001 | 4A0002 | 4A0002 | 4A0004 | 4A0004 | 4A0005 | 4A0005 |
| 2 | o2-04 | Drive Model Selection | Hex | 91 | 91 | 92 | 92 | 93 | 93 | 94 | 94 |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND | HD | ND |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 0.2 | 0.4 | 0.4 | 0.75 | 0.75 | 1.5 | 1.5 | 2.2 |
| 6 | b3-06 | Speed Search current 1 | − | 1.0 | 1.0 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 713.8 | 576.4 | 576.4 | 447.4 | 447.4 | 338.8 | 338.8 | 313.6 |
| 9 | C6-02 | Carrier frequency | − | 3 | 7 | 3 | 7 | 3 | 7 | 3 | 7 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 0.6 | 1 | 1 | 1.6 | 1.6 | 3.1 | 3.1 | 4.2 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 2.5 | 2.9 | 2.9 | 2.6 | 2.6 | 2.5 | 2.5 | 3 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 0.4 | 0.6 | 0.6 | 0.8 | 0.8 | 1.4 | 1.4 | 1.5 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 83.94 | 38.20 | 38.198 | 22.459 | 22.459 | 10.1 | 10.1 | 6.495 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 21.9 | 18.2 | 18.2 | 14.3 | 14.3 | 18.3 | 18.3 | 18.7 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 12 | 14 | 14 | 26 | 26 | 53 | 53 | 77 |
| 16 | E5-01 | Motor Code | hex | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF |
| 17 | L2-02 | Momentary power loss ride-through time | s | 0.1 | 0.1 | 0.1 | 0.1 | 0.2 | 0.2 | 0.3 | 0.3 |
| 18 | L2-03 | Momentary power loss Baseblock time | s | 0.2 | 0.2 | 0.2 | 0.3 | 0.3 | 0.4 | 0.4 | 0.5 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 |
| 20 | L2-05 | Uv detection voltage | V dc | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 |
| 21 | L3-24 | Motor acceleration time | s | 0.178 | 0.178 | 0.178 | 0.142 | 0.142 | 0.166 | 0.166 | 0.145 |
| 22 | L8-02 | Overheat alarm level | °C | 110 | 110 | 110 | 110 | 110 | 110 | 90 | 90 |
| 23 | L8-09 | Ground fault selection | − | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 24 | L8-38 | Carrier frequency reduction selection | − | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| 25 | n1-03 | Hunting Prevention Time Constant | ms | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Manual — Three-phase 400V middle-model defaults — page 415
Source reference: SIEP C71060618F, December 2016, physical PDF page 415. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Description Unit Setting Range
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
B
Parameter List
− | Model | −
o2-04 | Drive Model Selection | −
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor Code | hex
L2-02 | Momentary power loss ride-through time | s
L2-03 | Momentary power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier frequency reduction selection | −
n1-03 | Hunting Prevention Time Constant | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults three-phase 400V PDF415 — PDF page 415
| Source row | Parameter | Description | Unit | 4A0007 / HD (C6-01=0) | 4A0007 / ND (C6-01=1) | 4A0009 / HD (C6-01=0) | 4A0009 / ND (C6-01=1) | 4A0011 / HD (C6-01=0) | 4A0011 / ND (C6-01=1) | 4A0018 / HD (C6-01=0) | 4A0018 / ND (C6-01=1) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | 4A0007 | 4A0007 | 4A0009 | 4A0009 | 4A0011 | 4A0011 | 4A0018 | 4A0018 |
| 2 | o2-04 | Drive Model Selection | − | 95 | 95 | 96 | 96 | 97 | 97 | 99 | 99 |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND | HD | ND |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 2.2 | 3.0 | 3.0 | 3.7 | 4.0 | 5.5 | 5.5 | 7.5 |
| 6 | b3-06 | Speed Search current 1 | − | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 313.6 | 265.7 | 265.7 | 245.8 | 245.8 | 189.5 | 189.5 | 145.38 |
| 9 | C6-02 | Carrier frequency | − | 3 | 7 | 3 | 7 | 3 | 7 | 3 | 7 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 4.2 | 5.7 | 5.7 | 7 | 7 | 9.8 | 9.8 | 13.30 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 3 | 2.7 | 2.7 | 2.7 | 2.7 | 1.5 | 1.5 | 1.3 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 1.5 | 1.9 | 1.9 | 2.3 | 2.3 | 2.6 | 2.6 | 4.0 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 6.495 | 4.360 | 4.360 | 3.333 | 3.333 | 1.595 | 1.595 | 1.152 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 18.7 | 19 | 19 | 19.3 | 19.3 | 18.2 | 18.2 | 15.5 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 77 | 105 | 105 | 130 | 130 | 193 | 193 | 263 |
| 16 | E5-01 | Motor Code | hex | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF |
| 17 | L2-02 | Momentary power loss ride-through time | s | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.8 | 0.8 |
| 18 | L2-03 | Momentary power loss Baseblock time | s | 0.5 | 0.5 | 0.5 | 0.6 | 0.6 | 0.7 | 0.7 | 0.8 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 | 0.3 |
| 20 | L2-05 | Uv detection voltage | V dc | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 |
| 21 | L3-24 | Motor acceleration time | s | 0.145 | 0.145 | 0.145 | 0.154 | 0.154 | 0.154 | 0.168 | 0.175 |
| 22 | L8-02 | Overheat alarm level | °C | 100 | 100 | 100 | 100 | 100 | 100 | 110 | 110 |
| 23 | L8-09 | Ground fault selection | − | 0 | 0 | 0 | 0 | 0 | 0 | 1 | 1 |
| 24 | L8-38 | Carrier frequency reduction selection | − | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 |
| 25 | n1-03 | Hunting Prevention Time Constant | ms | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.50 | 1.50 |
Manual — Three-phase 400V large-model defaults — page 416
Source reference: SIEP C71060618F, December 2016, physical PDF page 416. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
No. Description Unit Setting Range
B.5 Defaults by Drive Model and Duty Rating (ND/HD)
− | Model | −
o2-04 | Drive Model Selection | −
C6-01 | Normal/Heavy Duty | −
E2-11 (E4-11, T1-02) | Motor rated power | kW
b3-06 | Speed Search current 1 | −
b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | –
b8-04 | Energy saving coefficient | −
C6-02 | Carrier frequency | −
E2-01 (E4-01, T1-04) | Motor rated current | A
E2-02 (E4-02) | Motor rated slip | Hz
E2-03 (E4-03) | Motor no-load current | A
E2-05 (E4-05) | Motor line-to-line resistance | Ω
E2-06 (E4-06) | Motor leakage inductance | %
E2-10 (E4-10) | Motor Iron Loss | W
E5-01 | Motor Code | hex
L2-02 | Momentary power loss ride-through time | s
L2-03 | Momentary power loss Baseblock time | s
L2-04 | Momentary power loss voltage recovery time | s
L2-05 | Uv detection voltage | V dc
L3-24 | Motor acceleration time | s
L8-02 | Overheat alarm level | °C
L8-09 | Ground fault selection | −
L8-38 | Carrier frequency reduction selection | −
n1-03 | Hunting Prevention Time Constant | ms
n2-01 | Speed Feedback Detection Control (AFR) Gain | –
Drive-model/duty-dependent defaults three-phase 400V PDF416 — PDF page 416
| Source row | Parameter | Description | Unit | 4A0023 / HD (C6-01=0) | 4A0023 / ND (C6-01=1) | 4A0031 / HD (C6-01=0) | 4A0031 / ND (C6-01=1) | 4A0038 / HD (C6-01=0) | 4A0038 / ND (C6-01=1) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | − | Model | − | 4A0023 | 4A0023 | 4A0031 | 4A0031 | 4A0038 | 4A0038 |
| 2 | o2-04 | Drive Model Selection | − | 9A | 9A | 9C | 9C | 9D | 9D |
| 3 | C6-01 | Normal/Heavy Duty | − | HD | ND | HD | ND | HD | ND |
| 4 | C6-01 | Normal/Heavy Duty | − | 0 | 1 | 0 | 1 | 0 | 1 |
| 5 | E2-11 (E4-11, T1-02) | Motor rated power | kW | 7.5 | 11.0 | 11.0 | 15.0 | 15.0 | 18.5 |
| 6 | b3-06 | Speed Search current 1 | − | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 7 | b3-08 | Current Control Gain during Speed Search (Speed Estimation Type) | – | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| 8 | b8-04 | Energy saving coefficient | − | 145.38 | 140.88 | 140.88 | 126.26 | 126.26 | 115.74 |
| 9 | C6-02 | Carrier frequency | − | 3 | 7 | 3 | 7 | 3 | 7 |
| 10 | E2-01 (E4-01, T1-04) | Motor rated current | A | 13.3 | 19.9 | 19.9 | 26.5 | 26.5 | 32.9 |
| 11 | E2-02 (E4-02) | Motor rated slip | Hz | 1.30 | 1.70 | 1.70 | 1.60 | 1.60 | 1.67 |
| 12 | E2-03 (E4-03) | Motor no-load current | A | 4.0 | 5.6 | 5.6 | 7.6 | 7.6 | 7.8 |
| 13 | E2-05 (E4-05) | Motor line-to-line resistance | Ω | 1.152 | 0.922 | 0.922 | 0.550 | 0.550 | 0.403 |
| 14 | E2-06 (E4-06) | Motor leakage inductance | % | 15.5 | 19.6 | 19.6 | 17.2 | 17.2 | 20.1 |
| 15 | E2-10 (E4-10) | Motor Iron Loss | W | 263 | 385 | 385 | 440 | 440 | 508 |
| 16 | E5-01 | Motor Code | hex | FFFF | FFFF | FFFF | FFFF | FFFF | FFFF |
| 17 | L2-02 | Momentary power loss ride-through time | s | 1 | 1 | 2 | 2 | 2 | 2 |
| 18 | L2-03 | Momentary power loss Baseblock time | s | 0.8 | 0.9 | 0.9 | 1.0 | 1.0 | 1.0 |
| 19 | L2-04 | Momentary power loss voltage recovery time | s | 0.3 | 0.3 | 0.3 | 0.6 | 0.6 | 0.6 |
| 20 | L2-05 | Uv detection voltage | V dc | 380 | 380 | 380 | 380 | 380 | 380 |
| 21 | L3-24 | Motor acceleration time | s | 0.175 | 0.265 | 0.265 | 0.244 | 0.244 | 0.317 |
| 22 | L8-02 | Overheat alarm level | °C | 110 | 110 | 110 | 110 | 110 | 110 |
| 23 | L8-09 | Ground fault selection | − | 1 | 1 | 1 | 1 | 1 | 1 |
| 24 | L8-38 | Carrier frequency reduction selection | − | 2 | 2 | 2 | 2 | 2 | 2 |
| 25 | n1-03 | Hunting Prevention Time Constant | ms | 10 | 10 | 10 | 10 | 10 | 10 |
| 26 | n2-01 | Speed Feedback Detection Control (AFR) Gain | – | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 | 1.50 |
Manual — SMRA SPM motor-code defaults at 1800 and 3600 r/min — page 417
Source reference: SIEP C71060618F, December 2016, physical PDF page 417. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
B.6 Parameters that Change with the Motor Code Selection
The following tables show parameters and default settings that change with the motor code selection E5-01 when Open Loop Vector for PM motors is used.
◆ Yaskawa SMRA Series SPM Motor
Table B.8 1800 rpm Type Yaskawa SMRA Series SPM Motor Settings
Par. Description Unit Default Settings
Table B.9 3600 rpm Type Yaskawa SMRA Series SPM Motor Settings
B
Parameter List
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Motor-code defaults SMRA SPM;200 Vac;1800r/min;not specified in table — PDF page 417
| Source row | Parameter | Description | Unit | E5-01 motor code 0002 | E5-01 motor code 0003 | E5-01 motor code 0005 | E5-01 motor code 0006 | E5-01 motor code 0008 |
|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 0002 | 0003 | 0005 | 0006 | 0008 |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW |
| 4 | E5-01 | Rated Speed | r/min | 1800 | 1800 | 1800 | 1800 | 1800 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 |
| 6 | E5-03 | Motor Rated Current | A | 2.1 | 4.0 | 6.9 | 10.8 | 17.4 |
| 7 | E5-04 | Motor Pole Number | – | 8 | 8 | 8 | 8 | 8 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 2.47 | 1.02 | 0.679 | 0.291 | 0.169 |
| 9 | E5-06 | d-Axis Inductance | mH | 12.7 | 4.8 | 3.9 | 3.6 | 2.5 |
| 10 | E5-07 | q-Axis Inductance | mH | 12.7 | 4.8 | 3.9 | 3.6 | 2.5 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 0 | 0 | 0 | 0 | 0 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/min) | 62.0 | 64.1 | 73.4 | 69.6 | 72.2 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 120 | 120 | 120 | 120 | 120 |
| 14 | E1-05 | Maximum Output Voltage | V | 200.0 | 200.0 | 200.0 | 200.0 | 200.0 |
| 15 | E1-06 | Base Frequency | Hz | 120 | 120 | 120 | 120 | 120 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 6 | 6 | 6 | 6 | 6 |
| 17 | L3-24 | Motor Acceleration Time for Inertia Calculations | s | 0.064 | 0.066 | 0.049 | 0.051 | 0.044 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | 0 | 0 | 0 | 0 | 0 |
Motor-code defaults SMRA SPM;200 Vac;3600r/min;not specified in table — PDF page 417
| Source row | Parameter | Description | Unit | E5-01 motor code 0103 | E5-01 motor code 0105 | E5-01 motor code 0106 | E5-01 motor code 0108 |
|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 0103 | 0105 | 0106 | 0108 |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW |
| 4 | E5-01 | Rated Speed | r/min | 3600 | 3600 | 3600 | 3600 |
| 5 | E5-02 | Motor Rated Power | kW | 0.75 | 1.5 | 2.2 | 3.7 |
| 6 | E5-03 | Motor Rated Current | A | 4.1 | 8.0 | 10.5 | 16.5 |
| 7 | E5-04 | Motor Pole Number | – | 8 | 8 | 8 | 8 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 0.538 | 0.20 | 0.15 | 0.097 |
| 9 | E5-06 | d-Axis Inductance | mH | 3.2 | 1.3 | 1.1 | 1.1 |
| 10 | E5-07 | q-Axis Inductance | mH | 3.2 | 1.3 | 1.1 | 1.1 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 0 | 0 | 0 | 0 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/min) | 32.4 | 32.7 | 36.7 | 39.7 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 240 | 240 | 240 | 240 |
| 14 | E1-05 | Maximum Output Voltage | V | 200.0 | 200.0 | 200.0 | 200.0 |
| 15 | E1-06 | Base Frequency | Hz | 240 | 240 | 240 | 240 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 12 | 12 | 12 | 12 |
| 17 | L3-24 | Motor Acceleration Time for Inertia Calculations | s | 0.137 | 0.132 | 0.132 | 0.122 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | 0 | 0 | 0 | 0 |
Manual — SSR1 200V 1750 r/min PRG1017 and earlier — page 418
Source reference: SIEP C71060618F, December 2016, physical PDF page 418. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ SS5 Motor: Yaskawa SSR1 Series IPM Motor
Default values vary based on drive software version.
■ Drive Software Version PRG: 1017 and Earlier
Table B.10 200 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High- Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;200 Vac;1750r/min;PRG1017 and earlier — PDF page 418
| Source row | Parameter | Description | Unit | E5-01 motor code 1202 | E5-01 motor code 1203 | E5-01 motor code 1205 | E5-01 motor code 1206 | E5-01 motor code 1208 | E5-01 motor code 120A | E5-01 motor code 120B | E5-01 motor code 120D | E5-01 motor code 120E | E5-01 motor code 120F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1202 | 1203 | 1205 | 1206 | 1208 | 120A | 120B | 120D | 120E | 120F |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11.0 | 15 | 18.0 |
| 6 | E5-03 | Motor Rated Current | A | 1.65 | 2.97 | 5.50 | 8.10 | 13.40 | 19.80 | 27.00 | 39.7 | 53.2 | 65.5 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 8.233 | 2.284 | 1.501 | 0.827 | 0.455 | 0.246 | 0.198 | 0.094 | 0.066 | 0.052 |
| 9 | E5-06 | d-Axis Inductance | mH | 54.84 | 23.02 | 17.08 | 8.61 | 7.20 | 4.86 | 4.15 | 3.40 | 2.65 | 2.17 |
| 10 | E5-07 | q-Axis Inductance | mH | 64.10 | 29.89 | 21.39 | 13.50 | 10.02 | 7.43 | 5.91 | 3.91 | 3.11 | 2.55 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 233.0 | 229.5 | 250.9 | 247.9 | 248.6 | 249.6 | 269.0 | 249.3 | 266.6 | 265.1 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/min) | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 |
| 15 | E1-06 | Base Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.092 | 0.076 | 0.051 | 0.066 | 0.075 | 0.083 | 0.077 | 0.084 | 0.102 | 0.103 |
| 18 | n8-49 | d-Axis Current for High- Efficiency Control | % | –7.2 | –10.8 | –11.1 | –17.8 | –17.5 | –22.0 | –17.3 | –10.1 | –10.3 | –10.1 |
Manual — SSR1 200V 1750 r/min PRG1018 and later — page 419
Source reference: SIEP C71060618F, December 2016, physical PDF page 419. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1018 and Later
Table B.11 200 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
B
Parameter List
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High- Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;200 Vac;1750r/min;PRG1018 and later — PDF page 419
| Source row | Parameter | Description | Unit | E5-01 motor code 1202 | E5-01 motor code 1203 | E5-01 motor code 1205 | E5-01 motor code 1206 | E5-01 motor code 1208 | E5-01 motor code 120A | E5-01 motor code 120B | E5-01 motor code 120D | E5-01 motor code 120E | E5-01 motor code 120F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1202 | 1203 | 1205 | 1206 | 1208 | 120A | 120B | 120D | 120E | 120F |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 |
| 6 | E5-03 | Motor Rated Current | A | 1.77 | 3.13 | 5.73 | 8.44 | 13.96 | 20.63 | 28.13 | 41.4 | 55.4 | 68.2 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 8.233 | 2.284 | 1.470 | 0.827 | 0.455 | 0.246 | 0.198 | 0.094 | 0.066 | 0.051 |
| 9 | E5-06 | d-Axis Inductance | mH | 54.84 | 23.02 | 17.22 | 8.61 | 7.2 | 4.86 | 4.15 | 3.4 | 2.45 | 2.18 |
| 10 | E5-07 | q-Axis Inductance | mH | 64.1 | 29.89 | 20.41 | 13.5 | 10.02 | 7.43 | 5.91 | 3.91 | 3.11 | 2.55 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 223.7 | 220.3 | 240.8 | 238 | 238.7 | 239.6 | 258.2 | 239.3 | 248.1 | 253.6 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/min) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 |
| 15 | E1-06 | Base Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.092 | 0.076 | 0.051 | 0.066 | 0.075 | 0.083 | 0.077 | 0.084 | 0.102 | 0.101 |
| 18 | n8-49 | d-Axis Current for High- Efficiency Control | % | –7.6 | –11.5 | –9.1 | –19 | –18.7 | –23.4 | –18.5 | –10.9 | –16.5 | –11.3 |
Manual — SSR1 400V 1750 r/min PRG1017 and earlier — page 420
Source reference: SIEP C71060618F, December 2016, physical PDF page 420. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1017 and Earlier
Table B.12 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;400 Vac;1750r/min;PRG1017 and earlier — PDF page 420
| Source row | Parameter | Description | Unit | E5-01 motor code 1232 | E5-01 motor code 1233 | E5-01 motor code 1235 | E5-01 motor code 1236 | E5-01 motor code 1238 | E5-01 motor code 123A | E5-01 motor code 123B | E5-01 motor code 123D | E5-01 motor code 123E | E5-01 motor code 123F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1232 | 1233 | 1235 | 1236 | 1238 | 123A | 123B | 123D | 123E | 123F |
| 2 | E5-01 | Voltage Class | − | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11.0 | 15 | 18.0 |
| 6 | E5-03 | Motor Rated Current | A | 0.83 | 1.49 | 2.75 | 4.05 | 6.80 | 9.90 | 13.10 | 19.9 | 26.4 | 32.1 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 32.932 | 9.136 | 6.004 | 3.297 | 1.798 | 0.982 | 0.786 | 0.368 | 0.263 | 0.202 |
| 9 | E5-06 | d-Axis Inductance | mH | 219.36 | 92.08 | 68.32 | 40.39 | 32.93 | 22.7 | 16.49 | 13.38 | 10.51 | 8.56 |
| 10 | E5-07 | q-Axis Inductance | mH | 256.40 | 119.56 | 85.56 | 48.82 | 37.70 | 26.80 | 23.46 | 16.99 | 12.77 | 11.22 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 466.0 | 459.0 | 501.8 | 485.7 | 498.7 | 498.0 | 541.7 | 508.7 | 531.9 | 536.4 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 |
| 15 | E1-06 | Base Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.092 | 0.076 | 0.051 | 0.066 | 0.075 | 0.083 | 0.077 | 0.084 | 0.102 | 0.103 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –7.2 | –10.7 | –11.1 | –8.9 | –7.9 | –10.2 | –17.4 | –15.8 | –12.6 | –16.3 |
Manual — SSR1 400V 1750 r/min PRG1018 and later — page 421
Source reference: SIEP C71060618F, December 2016, physical PDF page 421. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1018 and Later
Table B.13 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
B
Parameter List
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;400 Vac;1750r/min;PRG1018 and later — PDF page 421
| Source row | Parameter | Description | Unit | E5-01 motor code 1232 | E5-01 motor code 1233 | E5-01 motor code 1235 | E5-01 motor code 1236 | E5-01 motor code 1238 | E5-01 motor code 123A | E5-01 motor code 123B | E5-01 motor code 123D | E5-01 motor code 123E | E5-01 motor code 123F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1232 | 1233 | 1235 | 1236 | 1238 | 123A | 123B | 123D | 123E | 123F |
| 2 | E5-01 | Voltage Class | − | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 | 1750 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 |
| 6 | E5-03 | Motor Rated Current | A | 0.89 | 1.56 | 2.81 | 4.27 | 7.08 | 10.31 | 13.65 | 20.7 | 27.5 | 33.4 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 25.370 | 9.136 | 6.010 | 3.297 | 1.798 | 0.982 | 0.786 | 0.349 | 0.272 | 0.207 |
| 9 | E5-06 | d-Axis Inductance | mH | 169.00 | 92.08 | 67.71 | 34.40 | 32.93 | 22.7 | 16.49 | 13.17 | 10.30 | 8.72 |
| 10 | E5-07 | q-Axis Inductance | mH | 197.5 | 119.56 | 81.71 | 54.00 | 37.7 | 26.8 | 23.46 | 15.60 | 12.77 | 11.22 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 392.6 | 440.6 | 478.3 | 466.3 | 478.8 | 478.1 | 520.0 | 481.5 | 498.8 | 509.5 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 |
| 15 | E1-06 | Base Frequency | Hz | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 | 87.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 | 4.4 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.092 | 0.076 | 0.051 | 0.066 | 0.075 | 0.083 | 0.077 | 0.084 | 0.102 | 0.101 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –8.6 | –11.5 | –10.3 | –19.8 | –8.5 | –11 | –18.6 | –12.5 | –15.5 | –17.9 |
Manual — SSR1 200V 1450 r/min PRG1017 and earlier — page 422
Source reference: SIEP C71060618F, December 2016, physical PDF page 422. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1017 and Earlier
Table B.14 200 V, 1450 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;200 Vac;1450r/min;PRG1017 and earlier — PDF page 422
| Source row | Parameter | Description | Unit | E5-01 motor code 1302 | E5-01 motor code 1303 | E5-01 motor code 1305 | E5-01 motor code 1306 | E5-01 motor code 1308 | E5-01 motor code 130A | E5-01 motor code 130B | E5-01 motor code 130D | E5-01 motor code 130E | E5-01 motor code 130F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1302 | 1303 | 1305 | 1306 | 1308 | 130A | 130B | 130D | 130E | 130F |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11.0 | 15 | 18.0 |
| 6 | E5-03 | Motor Rated Current | A | 1.78 | 3.12 | 5.88 | 8.00 | 14.10 | 20.00 | 26.60 | 38.0 | 53.3 | 63.0 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 4.405 | 2.425 | 1.647 | 0.665 | 0.452 | 0.341 | 0.184 | 0.099 | 0.075 | 0.057 |
| 9 | E5-06 | d-Axis Inductance | mH | 26.62 | 19.14 | 14.53 | 12.27 | 7.10 | 5.90 | 6.91 | 4.07 | 3.29 | 2.53 |
| 10 | E5-07 | q-Axis Inductance | mH | 41.70 | 29.98 | 19.98 | 14.77 | 10.14 | 8.42 | 8.37 | 5.25 | 4.57 | 3.01 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 262.6 | 276.3 | 291.0 | 299.1 | 294.3 | 306.6 | 325.1 | 316.6 | 332.2 | 313.4 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 |
| 15 | E1-06 | Base Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.098 | 0.071 | 0.066 | 0.087 | 0.085 | 0.072 | 0.084 | 0.096 | 0.085 | 0.082 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –10.8 | –13.1 | –12.1 | –8.4 | –16.0 | –17.8 | –12.8 | –16.3 | –19.1 | –11.6 |
Manual — SSR1 200V 1450 r/min PRG1018 and later — page 423
Source reference: SIEP C71060618F, December 2016, physical PDF page 423. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1018 and Later
Table B.15 200 V, 1450 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
B
Parameter List
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;200 Vac;1450r/min;PRG1018 and later — PDF page 423
| Source row | Parameter | Description | Unit | E5-01 motor code 1302 | E5-01 motor code 1303 | E5-01 motor code 1305 | E5-01 motor code 1306 | E5-01 motor code 1308 | E5-01 motor code 130A | E5-01 motor code 130B | E5-01 motor code 130D | E5-01 motor code 130E | E5-01 motor code 130F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1302 | 1303 | 1305 | 1306 | 1308 | 130A | 130B | 130D | 130E | 130F |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 |
| 6 | E5-03 | Motor Rated Current | A | 1.88 | 3.13 | 5.63 | 8.33 | 14.17 | 20.63 | 27.71 | 39.6 | 55.5 | 65.6 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 3.190 | 1.940 | 1.206 | 0.665 | 0.341 | 0.252 | 0.184 | 0.099 | 0.075 | 0.057 |
| 9 | E5-06 | d-Axis Inductance | mH | 32.15 | 26.12 | 14.72 | 12.27 | 8.27 | 6.49 | 6.91 | 4.07 | 3.29 | 2.53 |
| 10 | E5-07 | q-Axis Inductance | mH | 41.74 | 34.3 | 20.15 | 14.77 | 9.81 | 7.74 | 7.66 | 4.65 | 3.84 | 3.01 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 264.3 | 269.6 | 284.3 | 287.1 | 284.5 | 298.0 | 335.0 | 303.9 | 311.2 | 300.9 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 |
| 15 | E1-06 | Base Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.098 | 0.071 | 0.066 | 0.087 | 0.085 | 0.072 | 0.084 | 0.096 | 0.085 | 0.08 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –6.6 | –10.9 | –13.5 | –9 | –9.5 | –10.1 | –6 | –9.3 | –10.7 | –13.2 |
Manual — SSR1 400V 1450 r/min PRG1017 and earlier — page 424
Source reference: SIEP C71060618F, December 2016, physical PDF page 424. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1017 and Earlier
Table B.16 400 V, 1450 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;400 Vac;1450r/min;PRG1017 and earlier — PDF page 424
| Source row | Parameter | Description | Unit | E5-01 motor code 1332 | E5-01 motor code 1333 | E5-01 motor code 1335 | E5-01 motor code 1336 | E5-01 motor code 1338 | E5-01 motor code 133A | E5-01 motor code 133B | E5-01 motor code 133D | E5-01 motor code 133E | E5-01 motor code 133F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1332 | 1333 | 1335 | 1336 | 1338 | 133A | 133B | 133D | 133E | 133F |
| 2 | E5-01 | Voltage Class | − | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11.0 | 15 | 18.0 |
| 6 | E5-03 | Motor Rated Current | A | 0.89 | 1.50 | 2.70 | 4.10 | 6.70 | 9.80 | 13.30 | 18.7 | 26.3 | 31.5 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 17.620 | 7.421 | 4.825 | 2.656 | 1.353 | 0.999 | 0.713 | 0.396 | 0.295 | 0.223 |
| 9 | E5-06 | d-Axis Inductance | mH | 106.50 | 85.11 | 58.87 | 46.42 | 31.73 | 26.20 | 27.06 | 15.22 | 12.65 | 9.87 |
| 10 | E5-07 | q-Axis Inductance | mH | 166.80 | 113.19 | 80.59 | 60.32 | 40.45 | 30.94 | 33.45 | 19.63 | 15.87 | 12.40 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 525.2 | 566.9 | 592.2 | 579.4 | 586.4 | 612.1 | 640.4 | 643.5 | 650.6 | 635.8 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 |
| 15 | E1-06 | Base Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.098 | 0.071 | 0.066 | 0.087 | 0.085 | 0.072 | 0.084 | 0.096 | 0.085 | 0.082 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –10.8 | –8.5 | –12.5 | –12.2 | –12.7 | –9.4 | –14.4 | –15.0 | –14.1 | –14.3 |
Manual — SSR1 400V 1450 r/min PRG1018 and later — page 425
Source reference: SIEP C71060618F, December 2016, physical PDF page 425. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1018 and Later
Table B.17 400 V, 1450 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
B
Parameter List
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Motor-code defaults SS5 SSR1 IPM;400 Vac;1450r/min;PRG1018 and later — PDF page 425
| Source row | Parameter | Description | Unit | E5-01 motor code 1332 | E5-01 motor code 1333 | E5-01 motor code 1335 | E5-01 motor code 1336 | E5-01 motor code 1338 | E5-01 motor code 133A | E5-01 motor code 133B | E5-01 motor code 133D | E5-01 motor code 133E | E5-01 motor code 133F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1332 | 1333 | 1335 | 1336 | 1338 | 133A | 133B | 133D | 133E | 133F |
| 2 | E5-01 | Voltage Class | − | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 | 1450 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 |
| 6 | E5-03 | Motor Rated Current | A | 0.94 | 1.56 | 2.81 | 4.27 | 6.98 | 10.21 | 13.85 | 19.5 | 27.4 | 32.9 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 12.76 | 7.421 | 4.825 | 2.656 | 1.353 | 0.999 | 0.713 | 0.393 | 0.295 | 0.223 |
| 9 | E5-06 | d-Axis Inductance | mH | 128.6 | 85.11 | 58.87 | 46.42 | 31.73 | 26.2 | 27.06 | 15.51 | 12.65 | 9.87 |
| 10 | E5-07 | q-Axis Inductance | mH | 166.96 | 113.19 | 80.59 | 60.32 | 40.45 | 30.94 | 33.45 | 19.63 | 15.87 | 12.4 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 528.6 | 544.2 | 568.5 | 572.8 | 562.9 | 587.6 | 670.1 | 612.7 | 624.6 | 610.4 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 |
| 15 | E1-06 | Base Frequency | Hz | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 | 72.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 | 3.6 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.098 | 0.071 | 0.066 | 0.087 | 0.085 | 0.072 | 0.084 | 0.096 | 0.085 | 0.08 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –6.6 | –9.2 | –13.5 | –12.1 | –13.7 | –10.1 | –12.2 | –15.5 | –15.1 | –16 |
Manual — SSR1 200V 1150 r/min PRG1017 and earlier — page 426
Source reference: SIEP C71060618F, December 2016, physical PDF page 426. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1017 and Earlier
Table B.18 200 V, 1150 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Table B.18 SS5 SSR1 IPM;200Vac;1150r/min;PRG1017 and earlier — PDF page 426
| Source row | Parameter | Description | Unit | E5-01 motor code 1402 | E5-01 motor code 1403 | E5-01 motor code 1405 | E5-01 motor code 1406 | E5-01 motor code 1408 | E5-01 motor code 140A | E5-01 motor code 140B | E5-01 motor code 140D | E5-01 motor code 140E | E5-01 motor code 140F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1402 | 1403 | 1405 | 1406 | 1408 | 140A | 140B | 140D | 140E | 140F |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11.0 | 15.0 | 18.0 |
| 6 | E5-03 | Motor Rated Current | A | 1.74 | 3.17 | 5.9 | 8.84 | 13.7 | 18.6 | 25.8 | 38.6 | 53.4 | 63.8 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 6.763 | 3.660 | 1.480 | 0.696 | 0.412 | 0.414 | 0.262 | 0.149 | 0.084 | 0.083 |
| 9 | E5-06 | d-Axis Inductance | mH | 42.88 | 28.59 | 17.64 | 10.40 | 7.94 | 10.60 | 7.53 | 4.49 | 3.83 | 2.78 |
| 10 | E5-07 | q-Axis Inductance | mH | 67.17 | 44.78 | 24.23 | 14.85 | 11.86 | 14.92 | 10.97 | 6.82 | 4.65 | 4.39 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 333.3 | 337.7 | 365.5 | 356.2 | 359.2 | 428.2 | 410.0 | 389.8 | 387.6 | 392.6 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 | 190.0 |
| 15 | E1-06 | Base Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.062 | 0.044 | 0.080 | 0.090 | 0.067 | 0.072 | 0.088 | 0.073 | 0.063 | 0.093 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –13.5 | –16.3 | –11.8 | –12.3 | –18.2 | –18.7 | –21.8 | –24.0 | –13.4 | –25.4 |
Manual — SSR1 200V 1150 r/min PRG1018 and later — page 427
Source reference: SIEP C71060618F, December 2016, physical PDF page 427. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1018 and Later
Table B.19 200 V, 1150 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
B
Parameter List
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Table B.19 SS5 SSR1 IPM;200Vac;1150r/min;PRG1018 and later — PDF page 427
| Source row | Parameter | Description | Unit | E5-01 motor code 1402 | E5-01 motor code 1403 | E5-01 motor code 1405 | E5-01 motor code 1406 | E5-01 motor code 1408 | E5-01 motor code 140A | E5-01 motor code 140B | E5-01 motor code 140D | E5-01 motor code 140E | E5-01 motor code 140F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1402 | 1403 | 1405 | 1406 | 1408 | 140A | 140B | 140D | 140E | 140F |
| 2 | E5-01 | Voltage Class | − | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac | 200 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 |
| 6 | E5-03 | Motor Rated Current | A | 1.88 | 3.02 | 6.00 | 8.85 | 14.27 | 20.21 | 26.67 | 39.9 | 55.6 | 63.5 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 4.832 | 2.704 | 1.114 | 0.511 | 0.412 | 0.303 | 0.165 | 0.113 | 0.084 | 0.066 |
| 9 | E5-06 | d-Axis Inductance | mH | 48.68 | 32.31 | 19.22 | 12.15 | 7.94 | 11.13 | 6.59 | 4.96 | 3.83 | 3.33 |
| 10 | E5-07 | q-Axis Inductance | mH | 63.21 | 40.24 | 24.38 | 15.35 | 11.86 | 14.06 | 8.55 | 6.12 | 4.65 | 4.5 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 320.4 | 327.1 | 364.4 | 344.4 | 357.5 | 430.8 | 391.5 | 384.4 | 372.1 | 421.3 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 | 190 |
| 15 | E1-06 | Base Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.062 | 0.044 | 0.08 | 0.09 | 0.067 | 0.072 | 0.088 | 0.073 | 0.062 | 0.091 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –8.8 | –9.9 | –9.3 | –10 | –17.7 | –12.3 | –15.3 | –13.9 | –14.4 | –17.9 |
Manual — SSR1 400V 1150 r/min PRG1017 and earlier — page 428
Source reference: SIEP C71060618F, December 2016, physical PDF page 428. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1017 and Earlier
Table B.20 400 V, 1150 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Table B.20 SS5 SSR1 IPM;400Vac;1150r/min;PRG1017 and earlier — PDF page 428
| Source row | Parameter | Description | Unit | E5-01 motor code 1432 | E5-01 motor code 1433 | E5-01 motor code 1435 | E5-01 motor code 1436 | E5-01 motor code 1438 | E5-01 motor code 143A | E5-01 motor code 143B | E5-01 motor code 143D | E5-01 motor code 143E | E5-01 motor code 143F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1432 | 1433 | 1435 | 1436 | 1438 | 143A | 143B | 143D | 143E | 143F |
| 2 | E5-01 | Voltage Class | − | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11.0 | 15 | 18.0 |
| 6 | E5-03 | Motor Rated Current | A | 0.87 | 1.59 | 2.95 | 4.42 | 6.80 | 9.70 | 12.60 | 19.1 | 26.7 | 31.9 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 27.050 | 14.640 | 5.291 | 2.783 | 1.480 | 1.220 | 0.655 | 0.443 | 0.334 | 0.332 |
| 9 | E5-06 | d-Axis Inductance | mH | 171.50 | 114.40 | 70.56 | 41.61 | 38.39 | 45.97 | 25.46 | 18.84 | 15.27 | 11.10 |
| 10 | E5-07 | q-Axis Inductance | mH | 268.70 | 179.10 | 96.90 | 59.41 | 47.65 | 56.26 | 33.63 | 24.68 | 18.56 | 17.56 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 666.9 | 675.5 | 731.0 | 712.4 | 792.7 | 859.9 | 820.2 | 805.4 | 796.4 | 785.1 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 | 380.0 |
| 15 | E1-06 | Base Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.062 | 0.044 | 0.080 | 0.090 | 0.067 | 0.072 | 0.088 | 0.073 | 0.062 | 0.093 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –13.5 | –16.2 | –11.8 | –12.3 | –8.8 | –11.5 | –14.8 | –15.6 | –12.5 | –25.4 |
Manual — SSR1 400V 1150 r/min PRG1018 and later — page 429
Source reference: SIEP C71060618F, December 2016, physical PDF page 429. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Drive Software Version PRG: 1018 and Later
Table B.21 400 V, 1150 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
B.6 Parameters that Change with the Motor Code Selection
B
Parameter List
E5-01 | Motor Code | −
E5-01 | Voltage Class | −
E5-01 | Rated Power | −
E5-01 | Rated Speed | r/min
E5-02 | Motor Rated Power | kW
E5-03 | Motor Rated Current | A
E5-04 | Motor Pole Number | –
E5-05 | Motor Winding Resistance | Ω
E5-06 | d-Axis Inductance | mH
E5-07 | q-Axis Inductance | mH
E5-09 | Induction Voltage Constant 1 | mVs/rad
E5-24 | Induction Voltage Constant 2 | mV/(r/ min)
E1-04 | Maximum Output Frequency | Hz
E1-05 | Maximum Output Voltage | V
E1-06 | Base Frequency | Hz
E1-09 | Minimum Output Frequency | Hz
L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s
n8-49 | d-Axis Current for High-Efficiency Control | %
Table B.21 SS5 SSR1 IPM;400Vac;1150r/min;PRG1018 and later — PDF page 429
| Source row | Parameter | Description | Unit | E5-01 motor code 1432 | E5-01 motor code 1433 | E5-01 motor code 1435 | E5-01 motor code 1436 | E5-01 motor code 1438 | E5-01 motor code 143A | E5-01 motor code 143B | E5-01 motor code 143D | E5-01 motor code 143E | E5-01 motor code 143F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | E5-01 | Motor Code | − | 1432 | 1433 | 1435 | 1436 | 1438 | 143A | 143B | 143D | 143E | 143F |
| 2 | E5-01 | Voltage Class | − | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac | 400 Vac |
| 3 | E5-01 | Rated Power | − | 0.4 kW | 0.75 kW | 1.5 kW | 2.2 kW | 3.7 kW | 5.5 kW | 7.5 kW | 11 kW | 15 kW | 18 kW |
| 4 | E5-01 | Rated Speed | r/min | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 | 1150 |
| 5 | E5-02 | Motor Rated Power | kW | 0.4 | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 |
| 6 | E5-03 | Motor Rated Current | A | 0.94 | 1.51 | 3.00 | 4.43 | 7.08 | 10.1 | 13.33 | 19.9 | 27.8 | 31.8 |
| 7 | E5-04 | Motor Pole Number | – | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| 8 | E5-05 | Motor Winding Resistance | Ω | 19.32 | 10.8 | 4.456 | 2.044 | 1.483 | 1.215 | 0.66 | 0.443 | 0.331 | 0.264 |
| 9 | E5-06 | d-Axis Inductance | mH | 194.7 | 129.2 | 76.88 | 48.6 | 37.58 | 44.54 | 26.36 | 19.1 | 15.09 | 13.32 |
| 10 | E5-07 | q-Axis Inductance | mH | 252.84 | 160.9 | 97.52 | 61.4 | 47.65 | 56.26 | 34.2 | 24.67 | 18.56 | 18 |
| 11 | E5-09 | Induction Voltage Constant 1 | mVs/rad | 640.9 | 654.1 | 728.8 | 688.9 | 702.0 | 861.5 | 783.0 | 762.2 | 749.6 | 842.7 |
| 12 | E5-24 | Induction Voltage Constant 2 | mV/(r/ min) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 13 | E1-04 | Maximum Output Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 14 | E1-05 | Maximum Output Voltage | V | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 | 380 |
| 15 | E1-06 | Base Frequency | Hz | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 | 57.5 |
| 16 | E1-09 | Minimum Output Frequency | Hz | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 | 2.9 |
| 17 | L3-24 <1> | Motor Acceleration Time for Inertia Calculations | s | 0.062 | 0.044 | 0.08 | 0.09 | 0.067 | 0.072 | 0.088 | 0.073 | 0.062 | 0.091 |
| 18 | n8-49 | d-Axis Current for High-Efficiency Control | % | –8.8 | –9.9 | –9.3 | –10 | –12.8 | –12.3 | –15.3 | –16.7 | –14.9 | –17.9 |
Manual — Communications section safety — page 432
Source reference: SIEP C71060618F, December 2016, physical PDF page 432. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.1 Section Safety
DANGER
Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
WARNING
Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Do not allow unqualified personnel to use equipment. Failure to comply could result in death or serious injury. Maintenance, inspection and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
CAUTION
Crush Hazard Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive.
Manual — MEMOBUS/Modbus configuration — page 433
Source reference: SIEP C71060618F, December 2016, physical PDF page 433. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.2 MEMOBUS/Modbus Configuration
Drives can be controlled from a PLC or other master device via serial communications using the MEMOBUS/Modbus protocol. MEMOBUS/Modbus communication can be configured using one master (PLC) and a maximum of 255 slaves. The drive has slave functionality only, meaning that serial communication is normally initiated from the master and responded to by the slaves. The master performs serial communications with only one slave at a time. The address or node for each slave must be set beforehand so that the master can communicate with the slave at that address. A slave that receives a command from the master will perform the specified function and then send a response back to the master.
Figure C.1 Connecting Multiple Drives to a PLC
C
MEMOBUS/Modbus Communications
Figure C.1 labels: Master (PLC or other); DRIVE; DRIVE; DRIVE. Network illustration topology remains original-only; no physical wiring inferred.
Manual — Communication specifications — page 434
Source reference: SIEP C71060618F, December 2016, physical PDF page 434. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.3 Communication Specifications
MEMOBUS/Modbus specifications appear in the following table:
Item Specifications
Interface | RS-422, RS-485
Communications Cycle | Asynchronous (Start-stop synchronization)
Communication Parameters | Communication Speeds Available
Communication Parameters | Data length
Communication Parameters | Parity
Communication Parameters | Stop bit
Protocol | MEMOBUS/Modbus (using RTU mode only)
Max Number of Slaves | 31 drives
MEMOBUS/Modbus communication specifications — PDF page 434
| Source row | Item | Subitem / merged specification | Specification |
|---|---|---|---|
| 1 | Interface | RS-422, RS-485 | RS-422, RS-485 |
| 2 | Communications Cycle | Asynchronous (Start-stop synchronization) | Asynchronous (Start-stop synchronization) |
| 3 | Communication Parameters | Communication Speeds Available | 1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 76.8; 115.2 kbps |
| 4 | Communication Parameters | Data length | 8 bit (fixed) |
| 5 | Communication Parameters | Parity | Select even, odd, or none |
| 6 | Communication Parameters | Stop bit | 1 bit (fixed) |
| 7 | Protocol | MEMOBUS/Modbus (using RTU mode only) | MEMOBUS/Modbus (using RTU mode only) |
| 8 | Max Number of Slaves | 31 drives | 31 drives |
Manual — Network cable connection procedure — page 435
Source reference: SIEP C71060618F, December 2016, physical PDF page 435. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.4 Connecting to a Network
This section explains the connection of a drive to a MEMOBUS/Modbus network and the network termination.
◆ Network Cable Connection
Follow the instructions below to connect the drive to a MEMOBUS/Modbus network. 1. With the power shut off, connect the communications cable to the drive and the master. Use the terminals shown in the figure below for network cable connections.
Figure C.2 Serial Communications Cable Connection Terminals
Note: Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for the communications cables, and properly shielded clamps to prevent problems with noise. When using RS-485 communications, connect S+ to R+, and S- to R- as shown in the diagram below. 2. Check or set the terminating resistance at all slaves. Use the description in Network Termination for slaves that are 1000 series drives. 3. Switch the power on. 4. Set the parameters needed for serial communications (H5-01 through H5-12) using the LED operator. 5. Shut the power off and wait until the display on the LED operator goes out completely. 6. Turn the power back on. 7. The drive is now ready to begin communicating with the master.
C
MEMOBUS/Modbus Communications
Figure C.2 labels: R+ Receive (+); R− Receive (−); S+ Send (+); S− Send (−); IG Shield Ground. Enlarged terminal labels R+, R−, S+, S−, IG. Background miniature terminal legends remain in raw evidence and original image; exact board placement and wiring geometry are original-only.
Manual — RS-485 network figure and conditions — page 436
Source reference: SIEP C71060618F, December 2016, physical PDF page 436. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ Wiring Diagram for Multiple Connections
Figure C.3 and Figure C.4 explain the wiring diagrams for multiple connections using MEMOBUS/Modbus communication.
■ RS-485 Interface
Note: The isolated ground (IG) connection is optional but strongly recommended to improve network immunity to electrical interference.
<1> The Ground symbol represents a direct electrical connection to the Earth. Connect the shield to ground at the controller side only if common mode noise issues are suspected.
<2> The IG terminal is the signal common point for the RS-485 transceiver chip power supply. Connect the isolated ground IG between all nodes to help prevent the coupling of external noise to the bus and to limit bus emissions if desired.
Figure C.3 RS-485 Interface
Note: 1. Set DIP switch S2 to the ON position on the drive located at the end of the network. Set DIP switch S2 to the OFF positions on all other slave devices. 2. Set H5-07 to 1 when using the RS-485 interface.
C.4 Connecting to a Network
Figure C.3 RS-485 labels: Controller R−,R+,S−,S+,IG; three Drive terminal groups S−,S+,R−,R+,IG; S2 OFF on first and middle illustrated drives, S2 ON on end drive. Ground symbols and footnote markers1/2 retained in original. Exact network wiring, shields, junctions and topology remain original-only; source prose and footnotes separately retained.
Manual — RS-422 network figure and conditions — page 437
Source reference: SIEP C71060618F, December 2016, physical PDF page 437. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ RS-422 Interface
Figure C.4 RS-422 Interface
Note: 1. Set DIP switch S2 to the ON position on the drive located at the end of the network. Set DIP switch S2 to the OFF positions on all other slave devices. 2. Set H5-07 to 1 when using the RS-422 interface in a multi-drop circuit. Set H5-07 to 0 when using the RS-422 interface in a point-to-point circuit.
C.4 Connecting to a Network
C
MEMOBUS/Modbus Communications
Figure C.4 RS-422 labels: PLC R−,R+,S−,S+,IG; three Drive terminal groups S−,S+,R−,R+,IG; S2 OFF on first and middle illustrated drives, S2 ON on end drive. Exact network wiring, shield, junction and ground topology remain original-only; same-page notes preserved separately.
Manual — Network termination and resistance — page 438
Source reference: SIEP C71060618F, December 2016, physical PDF page 438. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ Network Termination
The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in terminating resistance that can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the terminating resistance by setting DIP switch S2 to the ON position. Disable the terminating resistance on all slaves that are not located at the network line end. Figure C.5 illustrates the setting of DIP switch S2.
Figure C.5 Serial Communications Terminal and DIP Switch S2
C.4 Connecting to a Network
Figure C.5 labels: DIP switch S2 (in the ON position); OFF; ON; enlarged terminals R+,R−,S+,S−,IG. RS-422A or RS-485; S+,S−,R+,R−; +,−; DIP switch S2; terminal resistance (1/2 W, 120 Ω). Source Ω symbol restored from image. Miniature background-board legends remain in raw evidence; exact switch orientation, connections and circuit topology are original-only.
Manual — Communication address speed parity and fault action — page 439
Source reference: SIEP C71060618F, December 2016, physical PDF page 439. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.5 MEMOBUS/Modbus Setup Parameters
◆ MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.
■ H5-01: Drive Slave Address
Sets the drive slave address used for MEMOBUS/Modbus communications.
Note: After changing this parameter, the power must be cycled to enable the new setting.
No. Name Setting Range Default
<1> If the address is set to 0, no response will be provided during communications.
For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01 to any value besides 0 assigns the drive its address in the network. Slave address don't need to be assigned in sequential order, but each address needs to be unique so that no two drives have the same address.
■ H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
H5-02 Communication Speed H5-02 Communication Speed
■ H5-03: Communication Parity Selection
Sets the parity used for MEMOBUS/Modbus communications.
Setting 0: No Parity
Setting 1: Even Parity
Setting 2: Odd Parity
■ H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
C
MEMOBUS/Modbus Communications
H5-01 | Drive Slave Address
H5-02 | Communication Speed Selection
0 | 1200 bps
1 | 2400 bps
2 | 4800 bps
3 | 9600 bps
4 | 19200 bps
H5-03 | Communication Parity Selection
H5-04 | Stopping Method after Communication Error
H5-01 communications setup — PDF page 439
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-01 | Drive Slave Address | 0 to 20 H <1> | 1F |
H5-02 communications setup — PDF page 439
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-02 | Communication Speed Selection | 0 to 5 | 3 |
H5-02 communication speed choices — PDF page 439
| Source row | H5-02 first column | Communication speed first column | H5-02 second column | Communication speed second column |
|---|---|---|---|---|
| 1 | 0 | 1200 bps | 5 | 38400 bps |
| 2 | 1 | 2400 bps | 6 | 57600 bps |
| 3 | 2 | 4800 bps | 7 | 76800 bps |
| 4 | 3 | 9600 bps | 8 | 115200 bps |
| 5 | 4 | 19200 bps | – | – |
H5-03 communications setup — PDF page 439
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-03 | Communication Parity Selection | 0 to 2 | 0 |
H5-04 communications setup — PDF page 439
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-04 | Stopping Method after Communication Error | 0 to 3 | 3 |
Manual — Communication fault wait RTS and voltage units — page 440
Source reference: SIEP C71060618F, December 2016, physical PDF page 440. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Setting 3: Alarm Only, Continue Operation
■ H5-05: Communication Fault Detection Selection
Enables or disabled the communication error (CE) detection for MEMOBUS/Modbus communications.
No. Name Setting Range Default
Setting 0: Disabled No error detection. The drive continues operation.
Setting 1: Enabled If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and the drive will operate as determined by parameter H5-04.
■ H5-06: Drive Transmit Wait Time
Sets the time the drive waits after receiving data from a master until responding data.
Figure C.6 Drive Transmit Wait Time Setting
■ H5-07: RTS Control Selection
Enables or disables RTS control.
Setting 0: Disabled - RTS is Always ON Use this setting when using RS-422 signals for communications (1:1).
Setting 1: Enabled - RTS Switches while Sending Use this setting when using RS-485 signals for communications or when using the RS-422 signals for multi-drop communications.
■ H5-09: CE Detection Time
Sets the time the communications must be lost before the drive triggers a CE fault.
■ H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H
Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
Setting 0: 0.1 V Units
Setting 1: 1 V Units
C.5 MEMOBUS/Modbus Setup Parameters
Figure C.6 labels in time order: PLC→Drive Command message; Drive→PLC Response message; PLC→Drive Command message; Time. Gap labels 24 bit length and H5-06 setting. Exact arrow/gap geometry original-only; no additional numerical time inferred.
H5-05 | Communication Fault Detection Selection
H5-06 | Drive Transmit Wait Time
H5-07 | RTS Control Selection
H5-09 | CE Detection Time
H5-10 | Unit Selection for MEMOBUS/Modbus Register 0025H
H5-05 communications setup — PDF page 440
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-05 | Communication Fault Detection Selection | 0 or 1 | 1 |
H5-06 communications setup — PDF page 440
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-06 | Drive Transmit Wait Time | 5 to 65 ms | 5 ms |
H5-07 communications setup — PDF page 440
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-07 | RTS Control Selection | 0 or 1 | 1 |
H5-09 communications setup — PDF page 440
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-09 | CE Detection Time | 0.0 to 10.0 s | 2.0 s |
H5-10 communications setup — PDF page 440
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-10 | Unit Selection for MEMOBUS/Modbus Register 0025H | 0 or 1 | 0 |
Manual — Enter command and run sequence settings — page 441
Source reference: SIEP C71060618F, December 2016, physical PDF page 441. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ H5-11: Communications Enter Function Selection
Selects if an Enter command is needed to change parameter values via MEMOBUS/Modbus communications. Refer to Enter Command on page 459.
No. Name Setting Range Default
Setting 0: Enter Command Necessary Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter change, not for each single parameter (such as in Varispeed F7).
Setting 1: Enter Command not Necessary Parameter value changes become effective immediately without the need to send an Enter command (such as in Varispeed VS606-V7)
■ H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications (b1-02/16 = 2).
Setting 0: FWD/Stop, REV/Stop Bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Bit 1 will start and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV Bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Bit 1 changes the direction.
C.5 MEMOBUS/Modbus Setup Parameters
C
MEMOBUS/Modbus Communications
H5-11 | Communications Enter Function Selection
H5-12 | Run Command Method Selection
H5-11 communications setup — PDF page 441
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-11 | Communications Enter Function Selection | 0 or 1 | 1 |
H5-12 communications setup — PDF page 441
| Source row | Parameter | Name | Setting range | Default |
|---|---|---|---|---|
| 1 | H5-12 | Run Command Method Selection | 0 or 1 | 0 |
Manual — Observing and controlling the drive — page 442
Source reference: SIEP C71060618F, December 2016, physical PDF page 442. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.6 Drive Operations by MEMOBUS/Modbus
The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings. This section explains the functions that can be used and related parameter settings.
◆ Observing the Drive Operation
A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter settings (except H5-□□). • Observe drive status and drive control terminal status from a PLC. • Read and write parameters. • Set and reset faults. • Set multi-function inputs. Inputs settings from the input terminals S□ and from MEMOBUS/Modbus communications are both linked by an OR operation.
◆ Controlling the Drive
To start and stop the drive or set the frequency reference using MEMOBUS/Modbus communications, an external reference must be selected and the parameters listed below must be adjusted accordingly.
Table C.1 Setting Parameters for Drive Control from MEMOBUS/Modbus
Reference Source Parameter Name Required Setting
Refer to b1-01: Frequency Reference Selection 1 on page 121 and Refer to b1-02: Run Command Selection 1 on page 123 for details on external reference parameter selections. Refer to Setting 2: External Reference 1/2 Selection on page 186 for instructions on how to select external reference 1 and 2.
External Reference 1 | b1-01
External Reference 1 | b1-02
External Reference 2 | b1-15
External Reference 2 | b1-16
Table C.1 external reference settings for communication drive control — PDF page 442
| Source row | Reference source | Parameter | Name | Required setting |
|---|---|---|---|---|
| 1 | External Reference 1 | b1-01 | Frequency Reference Selection 1 | 2 |
| 2 | External Reference 1 | b1-02 | Run Command Selection 1 | 2 |
| 3 | External Reference 2 | b1-15 | Frequency Reference Selection 2 | 2 |
| 4 | External Reference 2 | b1-16 | Run Command Selection 2 | 2 |
Manual — Command and response timing — page 443
Source reference: SIEP C71060618F, December 2016, physical PDF page 443. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.7 Communications Timing
To prevent overrun in the slave drive, the master should wait a certain time between sending messages to the same drive. In the same way, the slave drive must wait before sending response messages to prevent an overrun in the master. This section explains the message timing.
◆ Command Messages from Master to Drive
In order to prevent overrun and data loss, the master must wait between receiving a response and sending the same type of command as before to the same slave drive. The minimum wait time depends on the command as shown in the table below.
Table C.2 Minimum Wait Time for Sending Messages Command Type Example Minimum Wait Time
<1> If the drive receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it receives a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.
Figure C.7 Minimum Wait Time for Sending Messages
A timer should be set in the master to check how long it takes for the slave drive(s) to respond to the master. If no response is received within a certain amount of time, the master should try resending the message.
◆ Response Messages from Drive to Master
If the drive receives a command from the master, it will process the data received and wait for the time set in H5-06 until it responds. Increase H5-06 if the drive response causes overrun in the master.
Figure C.8 Minimum Response Wait Time
C
MEMOBUS/Modbus Communications
Figure C.7 labels in time order: PLC→Drive Command message; Drive→PLC Response message; PLC→Drive Command message; Time. Gap labels24 bit length; Master Send Wait Time. Original arrow/gap geometry retained; table C.2 supplies numerical conditions separately.
Figure C.8 labels in time order: PLC→Drive Command message; Drive→PLC Response message; PLC→Drive Command message; Time. Gap labels24 bit length; H5-06 setting. Exact arrow/gap geometry original-only.
1 | • Control command (Run, Stop) • Set inputs/outputs • Read monitors and parameter values
2 | • Write parameters
3 | • Save changes using an Enter command
Table C.2 minimum wait for sending messages — PDF page 443
| Source row | Command type | Example | Minimum wait time |
|---|---|---|---|
| 1 | 1 | • Control command (Run, Stop) • Set inputs/outputs • Read monitors and parameter values | 5 ms |
| 2 | 2 | • Write parameters | H5-11 = 0: 50 ms; H5-11 = 1: 200 ms <1> |
| 3 | 3 | • Save changes using an Enter command | 200 ms to 2 s, depending on the number of changed parameters <1> |
Manual — Message format and CRC calculation procedure — page 444
Source reference: SIEP C71060618F, December 2016, physical PDF page 444. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.8 Message Format
◆ Message Content
In MEMOBUS/Modbus communications, the master sends commands to the slave, and the slave responds. The message format is configured for both sending and receiving as shown below, and the length of data packets depends on the command (function) content.
SLAVE ADDRESS FUNCTION CODE DATA ERROR CHECK
◆ Slave Address
The slave address in the message defines the note the message is sent to. Use addresses between 0 and 20H. If a message with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves do not provide a response to a broadcast type message.
◆ Function Code
The three types of function codes are shown in the table below.
Function Code; Function Name
Function Code; Function Name; Data Length (bytes): Command Message Minimum/Maximum; Response Message Minimum/Maximum
◆ Data
Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test) and the data the register contains. The data length changes depending on the command details.
A drive MEMOBUS/Modbus register always has a data length of two bytes. Therefore data written into drive registers must also always have a length of two bytes. Register data read out from the drive will always consist of two bytes.
◆ Error Check
The drive uses a CRC-16 (cyclic redundancy check, checksum method) for checking data validity. Use the procedure described below when calculating the CRC-16 checksum for command data or when verifying response data.
■ Command Data
When the drive receives data, it calculates the CRC-16 checksum from the data and compares it to the CRC-16 value received within the message. Both must match before a command is processed. An initial value of FFFFH (i.e., all 16 bits equal 1) must be used for CRC-16 calculations for the MEMOBUS/Modbus protocol. Calculate the CRC-16 checksum using the following steps: • The starting value is FFFFH. • Perform an XOR operation of this value and the slave address. • Right shift the result. • When the overflow bit of the shift operation becomes 1, perform an XOR operation of the result from step 3 above and the fix value A001H. • Repeat steps 3 and 4 until eight shift operations have been performed. • After eight shift operations, perform an XOR operation with the result and the next data in the message (function code, register address, data). Continue with steps 3 to 5 until the last data has been processed. • The result of the last shift or XOR operation is the checksum.
03H | Read MEMOBUS/Modbus registers
08H | Loopback test
10H | Write to multiple MEMOBUS/Modbus registers
Function codes and message length limits in bytes — PDF page 444
| Source row | Function code | Function name | Command minimum bytes | Command maximum bytes | Response minimum bytes | Response maximum bytes |
|---|---|---|---|---|---|---|
| 1 | 03H | Read MEMOBUS/Modbus registers | 8 | 8 | 7 | 37 |
| 2 | 08H | Loopback test | 8 | 8 | 8 | 8 |
| 3 | 10H | Write to multiple MEMOBUS/Modbus registers | 11 | 41 | 8 | 8 |
Manual — CRC example and response validation — page 445
Source reference: SIEP C71060618F, December 2016, physical PDF page 445. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
The example in Table C.3 shows the CRC-16 calculation of the slave address 02H and the function code 03H, yielding the result D140H.
Note: This example does not show the calculation for a complete MEMOBUS/Modbus command. Normally data would follow in the calculation.
Table C.3 CRC-16 Checksum Calculation Example Description Calculation Overflow Description Calculation Overflow
Perform operations with next data (function code)
Continue from here with next data.
■ Response Data
To be sure that the data is valid, perform a CRC-16 calculation on the response message data as described above. Compare the result to the CRC-16 checksum that was received within the response message. Both should match.
C.8 Message Format
C
MEMOBUS/Modbus Communications
CRC-16 example result: 1101 0001 0100 0000; D 1 labelled (Lower); 4 0 labelled (Upper). The source labels are preserved literally without a byte-order correction. This incomplete command example continues with next data.
Illustrative incomplete message CRC calculation only. The right-hand source block continues the left-hand block; no running-device value. Final D140H and lower/upper labels retained separately as source context, no reimplementation or inferred byte correction.
Initial Value (FFFFH) | 1111 1111 1111 1111
Address 02H | 0000 0000 0000 0010
XOR w initial value | 1111 1111 1111 1101
Shift 1 | 0111 1111 1111 1110
XOR w A001H | 1010 0000 0000 0001
XOR result | 1101 1111 1111 1111
Shift 2 | 0110 1111 1111 1111
XOR result | 1100 1111 1111 1110
Shift 3 | 0110 0111 1111 1111
Shift 4 | 0011 0011 1111 1111
XOR result | 1001 0011 1111 1110
Shift 5 | 0100 1001 1111 1111
Shift 6 | 0010 0100 1111 1111
XOR result | 1000 0100 1111 1110
Shift 7 | 0100 0010 0111 1111
Shift 8 | 0010 0001 0011 1111
XOR result | 1000 0001 0011 1110
Function Code 03H | 0000 0000 0000 0011
XOR w result | 1000 0001 0011 1101
Shift 1 | 0100 0000 1001 1110
XOR result | 1110 0000 1001 1111
Shift 2 | 0111 0000 0100 1111
XOR result | 1101 0000 0100 1110
Shift 3 | 0110 1000 0010 0111
Shift 4 | 0011 0100 0001 0011
XOR result | 1001 0100 0001 0010
Shift 5 | 0100 1010 0000 1001
Shift 6 | 0010 0101 0000 0100
XOR result | 1000 0101 0000 0101
Shift 7 | 0100 0010 1000 0010
XOR result | 1110 0010 1000 0011
Shift 8 | 0111 0001 0100 0001
XOR result | 1101 0001 0100 0000
Table C.3 CRC16 example first stage slave address02H — PDF page 445
| Source row | Description | Calculation | Overflow |
|---|---|---|---|
| 1 | Initial Value (FFFFH) | 1111 1111 1111 1111 | ⟦blank source cell⟧ |
| 2 | Address 02H | 0000 0000 0000 0010 | ⟦blank source cell⟧ |
| 3 | XOR w initial value | 1111 1111 1111 1101 | ⟦blank source cell⟧ |
| 4 | Shift 1 | 0111 1111 1111 1110 | 1 |
| 5 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 6 | XOR result | 1101 1111 1111 1111 | ⟦blank source cell⟧ |
| 7 | Shift 2 | 0110 1111 1111 1111 | 1 |
| 8 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 9 | XOR result | 1100 1111 1111 1110 | ⟦blank source cell⟧ |
| 10 | Shift 3 | 0110 0111 1111 1111 | 0 |
| 11 | Shift 4 | 0011 0011 1111 1111 | 1 |
| 12 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 13 | XOR result | 1001 0011 1111 1110 | ⟦blank source cell⟧ |
| 14 | Shift 5 | 0100 1001 1111 1111 | 0 |
| 15 | Shift 6 | 0010 0100 1111 1111 | 1 |
| 16 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 17 | XOR result | 1000 0100 1111 1110 | ⟦blank source cell⟧ |
| 18 | Shift 7 | 0100 0010 0111 1111 | 0 |
| 19 | Shift 8 | 0010 0001 0011 1111 | 1 |
| 20 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 21 | XOR result | 1000 0001 0011 1110 | ⟦blank source cell⟧ |
Table C.3 CRC16 example continuation function code03H — PDF page 445
| Source row | Description | Calculation | Overflow |
|---|---|---|---|
| 1 | Function Code 03H | 0000 0000 0000 0011 | ⟦blank source cell⟧ |
| 2 | XOR w result | 1000 0001 0011 1101 | ⟦blank source cell⟧ |
| 3 | Shift 1 | 0100 0000 1001 1110 | 1 |
| 4 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 5 | XOR result | 1110 0000 1001 1111 | ⟦blank source cell⟧ |
| 6 | Shift 2 | 0111 0000 0100 1111 | 1 |
| 7 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 8 | XOR result | 1101 0000 0100 1110 | ⟦blank source cell⟧ |
| 9 | Shift 3 | 0110 1000 0010 0111 | 0 |
| 10 | Shift 4 | 0011 0100 0001 0011 | 0 |
| 11 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 12 | XOR result | 1001 0100 0001 0010 | ⟦blank source cell⟧ |
| 13 | Shift 5 | 0100 1010 0000 1001 | 0 |
| 14 | Shift 6 | 0010 0101 0000 0100 | 1 |
| 15 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 16 | XOR result | 1000 0101 0000 0101 | ⟦blank source cell⟧ |
| 17 | Shift 7 | 0100 0010 1000 0010 | 1 |
| 18 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 19 | XOR result | 1110 0010 1000 0011 | ⟦blank source cell⟧ |
| 20 | Shift 8 | 0111 0001 0100 0001 | 1 |
| 21 | XOR w A001H | 1010 0000 0000 0001 | ⟦blank source cell⟧ |
| 22 | XOR result | 1101 0001 0100 0000 | ⟦blank source cell⟧ |
Manual — Read and loopback message examples — page 446
Source reference: SIEP C71060618F, December 2016, physical PDF page 446. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.9 Message Examples
Below are some examples of command and response messages.
◆ Reading Drive MEMOBUS/Modbus Register Contents
Using the function code 03H (Read), a maximum of 16 MEMOBUS/Modbus registers can be read out at a time. The following table shows message examples when reading status signals, error details, data link status, and frequency references from the slave 2 drive.
Command Message Response Message (normal) Response Message (fault)
◆ Loopback Test
Function code 08H performs a loopback test. This test returns a response message with exactly the same content as the command message and can be used to check the communications between the master and slave. User-defined test code and data values can be set. The following table shows a message example when performing a loopback test with the slave 1 drive.
Separate physical message panel; content is an example, not current settings. Exact source upper/lower labels retained. Shared item labels span only their actual physical extent; empty end panels omitted. Read with same-page protocol and Enter-command conditions.
Slave Address | Slave Address
Function Code | Function Code
Starting No. | Upper
Starting No. | Lower
Data Quantity | Upper
Data Quantity | Lower
CRC-16 | Upper
CRC-16 | Lower
Data Quantity | Data Quantity
1st storage register | Upper
1st storage register | Lower
Next storage register | Upper
Next storage register | Lower
Error Code | Error Code
Test Code | Upper
Test Code | Lower
Data | Upper
Data | Lower
Read registers example — Command — PDF page 446
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 02H |
| 2 | Function Code | Function Code | 03H |
| 3 | Starting No. | Upper | 00H |
| 4 | Starting No. | Lower | 20H |
| 5 | Data Quantity | Upper | 00H |
| 6 | Data Quantity | Lower | 04H |
| 7 | CRC-16 | Upper | 45H |
| 8 | CRC-16 | Lower | F0H |
Read registers example — Normal response — PDF page 446
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 02H |
| 2 | Function Code | Function Code | 03H |
| 3 | Data Quantity | Data Quantity | 08H |
| 4 | 1st storage register | Upper | 00H |
| 5 | 1st storage register | Lower | 65H |
| 6 | Next storage register | Upper | 00H |
| 7 | Next storage register | Lower | 00H |
| 8 | Next storage register | Upper | 00H |
| 9 | Next storage register | Lower | 00H |
| 10 | Next storage register | Upper | 01H |
| 11 | Next storage register | Lower | F4H |
| 12 | CRC-16 | Upper | AFH |
| 13 | CRC-16 | Lower | 82H |
Read registers example — Fault response — PDF page 446
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 02H |
| 2 | Function Code | Function Code | 83H |
| 3 | Error Code | Error Code | 03H |
| 4 | CRC-16 | Upper | F1H |
| 5 | CRC-16 | Lower | 31H |
Loopback example — Command — PDF page 446
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 01H |
| 2 | Function Code | Function Code | 08H |
| 3 | Test Code | Upper | 00H |
| 4 | Test Code | Lower | 00H |
| 5 | Data | Upper | A5H |
| 6 | Data | Lower | 37H |
| 7 | CRC-16 | Upper | DAH |
| 8 | CRC-16 | Lower | 8DH |
Loopback example — Fault response — PDF page 446
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 01H |
| 2 | Function Code | Function Code | 89H |
| 3 | Error Code | Error Code | 01H |
| 4 | CRC-16 | Upper | 86H |
| 5 | CRC-16 | Lower | 50H |
Manual — Multiple-register write example — page 447
Source reference: SIEP C71060618F, December 2016, physical PDF page 447. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ Writing to Multiple Registers
Function code 10h allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process works similar to reading registers, i.e., the address of the first register that is to be written and the data quantity must be set in the command message. The data to be written must be consecutive so that the register addresses are in order, starting from the specified address in the command message. The data order must be high byte, then lower byte. The following table shows an example of a message where a forward operation has been set with a frequency reference of 60.00 Hz for the slave 1 drive. If parameter values are changed using the Write command, depending on the setting of H5-11, an Enter command will be necessary to activate the data or save them. Refer to H5-11: Communications Enter Function Selection on page 441 and Refer to Enter Command on page 459 for detailed descriptions.
Command Message Response Message (normal) Response Message (fault)
Note: For the number of bytes in the command message, take double the number of the data quantity.
C.9 Message Examples
C
MEMOBUS/Modbus Communications
Separate physical message panel; content is an example, not current settings. Exact source upper/lower labels retained. Shared item labels span only their actual physical extent; empty end panels omitted. Read with same-page protocol and Enter-command conditions.
Slave Address | Slave Address
Function Code | Function Code
Starting No. | Upper
Starting No. | Lower
Data Quantity | Upper
Data Quantity | Lower
Number of Bytes | Number of Bytes
Starting Data | Upper
Starting Data | Lower
Next Data | Upper
Next Data | Lower
CRC-16 | Upper
CRC-16 | Lower
Error Code | Error Code
Write registers example — Command — PDF page 447
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 01H |
| 2 | Function Code | Function Code | 10H |
| 3 | Starting No. | Upper | 00H |
| 4 | Starting No. | Lower | 01H |
| 5 | Data Quantity | Upper | 00H |
| 6 | Data Quantity | Lower | 02H |
| 7 | Number of Bytes | Number of Bytes | 04H |
| 8 | Starting Data | Upper | 00H |
| 9 | Starting Data | Lower | 01H |
| 10 | Next Data | Upper | 17H |
| 11 | Next Data | Lower | 70H |
| 12 | CRC-16 | Upper | 6DH |
| 13 | CRC-16 | Lower | 67H |
Write registers example — Normal response — PDF page 447
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 01H |
| 2 | Function Code | Function Code | 10H |
| 3 | Starting No. | Upper | 00H |
| 4 | Starting No. | Lower | 01H |
| 5 | Data Quantity | Upper | 00H |
| 6 | Data Quantity | Lower | 02H |
| 7 | CRC-16 | Upper | 10H |
| 8 | CRC-16 | Lower | 08H |
Write registers example — Fault response — PDF page 447
| Source row | Item | Upper/lower byte or shared item | Hexadecimal value |
|---|---|---|---|
| 1 | Slave Address | Slave Address | 01H |
| 2 | Function Code | Function Code | 90H |
| 3 | Error Code | Error Code | 02H |
| 4 | CRC-16 | Upper | CDH |
| 5 | CRC-16 | Lower | C1H |
Manual — Command register and bit map — page 448
Source reference: SIEP C71060618F, December 2016, physical PDF page 448. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.10 MEMOBUS/Modbus Data Table
Table below lists all MEMOBUS/Modbus data. There are three types of data: command data, monitor data, and broadcast data.
◆ Command Data
It is possible to both read and write command data.
Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.
Register No. Contents
0000H | Reserved
0001H | Operation Signals and Multi-function Inputs
0001H | bit 0
0001H | bit 1
0001H | bit 2
0001H | bit 3
0001H | bit 4
0001H | bit 5
0001H | bit 6
0001H | bit 7
0001H | bit 8
0001H | bit 9
0001H | bit A
0001H | bit B to F
0002H | Frequency Reference
0003H | Output Voltage Gain
0004H-0005H | Reserved
0006H | PID Target, 0.01% units, signed
0007H | Analog Output Terminal AM Setting (10 V / 4000 H)
0008H | Reserved
0009H | Settings for Multi-Function Digital Outputs
0009H | bit 0
0009H | bit 1
0009H | bit 2
0009H | bit 3 to F
000AH | Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000
000BH-000EH | Reserved
000FH | Control Selection Setting
000FH | bit 0
000FH | bit 1
000FH | bit 2 to B
000FH | bit C
000FH | bit D
000FH | bit E
000FH | bit F
Command register map — PDF page 448
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 0000H | Reserved | Reserved |
| 2 | 0001H | Operation Signals and Multi-function Inputs | Operation Signals and Multi-function Inputs |
| 3 | 0001H | bit 0 | H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run) H5-12 = 1: Run Command (0 = Stop, 1 = Run) |
| 4 | 0001H | bit 1 | H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Reverse Run) H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse) |
| 5 | 0001H | bit 2 | External Fault (EF0) |
| 6 | 0001H | bit 3 | Fault Reset |
| 7 | 0001H | bit 4 | Multi-Function Input 1 Function is ComRef when H1-01 = 40 (Forward/Stop). Note: When the bit at ComRef is turned on, commands from MEMOBUS/Modbus communications take control of the frequency. When a communications option card is connected, that option card is given priority. |
| 8 | 0001H | bit 5 | Multi-Function Input 2 Function is ComCtrl when H1-02 = 41 (Reverse/Stop). |
| 9 | 0001H | bit 6 | Multi-Function Input 3 |
| 10 | 0001H | bit 7 | Multi-Function Input 4 |
| 11 | 0001H | bit 8 | Multi-Function Input 5 |
| 12 | 0001H | bit 9 | Multi-Function Input 6 |
| 13 | 0001H | bit A | Multi-Function Input 7 |
| 14 | 0001H | bit B to F | Reserved |
| 15 | 0002H | Frequency Reference | Units are determined by parameter o1-03 |
| 16 | 0003H | Output Voltage Gain | Set in units of 1 (0.1%) with a setting range of 20 to 2000 (2.0% to 200.0%) Note: Initial value at power up: 1000 (100.0%) |
| 17 | 0004H-0005H | Reserved | Reserved |
| 18 | 0006H | PID Target, 0.01% units, signed | PID Target, 0.01% units, signed |
| 19 | 0007H | Analog Output Terminal AM Setting (10 V / 4000 H) | Analog Output Terminal AM Setting (10 V / 4000 H) |
| 20 | 0008H | Reserved | Reserved |
| 21 | 0009H | Settings for Multi-Function Digital Outputs | Settings for Multi-Function Digital Outputs |
| 22 | 0009H | bit 0 | Contact Output (terminal MA/MB-MC) |
| 23 | 0009H | bit 1 | Photocoupler Output 1 (terminal P1-PC) |
| 24 | 0009H | bit 2 | Photocoupler Output 2 (terminal P2-PC) |
| 25 | 0009H | bit 3 to F | Reserved |
| 26 | 000AH | Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000 | Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000 |
| 27 | 000BH-000EH | Reserved | Reserved |
| 28 | 000FH | Control Selection Setting | Control Selection Setting |
| 29 | 000FH | bit 0 | Reserved |
| 30 | 000FH | bit 1 | PID Target Input |
| 31 | 000FH | bit 2 to B | Reserved |
| 32 | 000FH | bit C | Enable Terminal S5 Input for Broadcast Data |
| 33 | 000FH | bit D | Enable Terminal S6 Input for Broadcast Data |
| 34 | 000FH | bit E | Enable Terminal S7 Input for Broadcast Data |
| 35 | 000FH | bit F | Reserved |
Manual — Read-only status fault and monitor register map — page 449
Source reference: SIEP C71060618F, December 2016, physical PDF page 449. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ Monitor Data
Monitor data can be read only.
Register No. Contents
C.10 MEMOBUS/Modbus Data Table
C
MEMOBUS/Modbus Communications
0020H | Drive Status 1
0020H | bit 0
0020H | bit 1
0020H | bit 2
0020H | bit 3
0020H | bit 4
0020H | bit 5
0020H | bit 6
0020H | bit 7
0020H | bit 8 to bit D
0020H | bit E
0020H | bit F
0021H | Fault Contents 1
0021H | bit 0
0021H | bit 1
0021H | bit 2
0021H | bit 3
0021H | bit 4
0021H | bit 5
0021H | bit 6
0021H | bit 7
0021H | bit 8
0021H | bit 9
0021H | bit A
0021H | bit B
0021H | bit C
0021H | bit D
0021H | bit E
0021H | bit F
0022H | Data Link Status
0022H | bit 0
0022H | bit 1
0022H | bit 2
0022H | bit 3
0022H | bit 4
0022H | bit 5
0022H | bit 6 to bit F
0023H | Frequency Reference, <1>
0024H | Output Frequency, <1>
0025H | Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)
0026H | Output Current, <2>
0027H | Output Power
0028H | Torque Reference (OLV only)
Monitor register map (read only) — PDF page 449
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 0020H | Drive Status 1 | Drive Status 1 |
| 2 | 0020H | bit 0 | During Run |
| 3 | 0020H | bit 1 | During Reverse |
| 4 | 0020H | bit 2 | Drive Ready |
| 5 | 0020H | bit 3 | Fault |
| 6 | 0020H | bit 4 | Data Setting Error |
| 7 | 0020H | bit 5 | Multi-Function Contact Output (terminal MA/MB-MC) |
| 8 | 0020H | bit 6 | Multi-Function Photocoupler Output 1 (terminal P1 - PC) |
| 9 | 0020H | bit 7 | Multi-Function Photocoupler Output 2 (terminal P2 - PC) |
| 10 | 0020H | bit 8 to bit D | Reserved |
| 11 | 0020H | bit E | When ComRef has been enabled |
| 12 | 0020H | bit F | When ComCtrl has been enabled |
| 13 | 0021H | Fault Contents 1 | Fault Contents 1 |
| 14 | 0021H | bit 0 | Overcurrent (oC), Ground fault (GF), IGBT Short Circuit or Ground Fault (SC) |
| 15 | 0021H | bit 1 | Overvoltage (ov) |
| 16 | 0021H | bit 2 | Drive Overload (oL2) |
| 17 | 0021H | bit 3 | Overheat 1 (oH1), Drive Overheat Warning (oH2) |
| 18 | 0021H | bit 4 | Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH) |
| 19 | 0021H | bit 5 | Reserved |
| 20 | 0021H | bit 6 | PID Feedback Loss (FbL/FbH) |
| 21 | 0021H | bit 7 | EF0 to 7: External Fault |
| 22 | 0021H | bit 8 | CPF□□: Hardware Fault (includes oFA□□) |
| 23 | 0021H | bit 9 | Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/ UL4) |
| 24 | 0021H | bit A | PG Disconnected (PGo), Overspeed (oS), Excessive Speed Deviation (dEv), |
| 25 | 0021H | bit B | Main Circuit Undervoltage (Uv) |
| 26 | 0021H | bit C | Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3) |
| 27 | 0021H | bit D | Output Phase Loss (LF), Input Phase Loss (PF) |
| 28 | 0021H | bit E | MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS) |
| 29 | 0021H | bit F | Operator Connection Fault (oPr) |
| 30 | 0022H | Data Link Status | Data Link Status |
| 31 | 0022H | bit 0 | Writing data or switching motors |
| 32 | 0022H | bit 1 | Reserved |
| 33 | 0022H | bit 2 | Reserved |
| 34 | 0022H | bit 3 | Upper or lower limit error |
| 35 | 0022H | bit 4 | Data conformity error |
| 36 | 0022H | bit 5 | Writing to EEPROM |
| 37 | 0022H | bit 6 to bit F | Reserved |
| 38 | 0023H | Frequency Reference, <1> | Frequency Reference, <1> |
| 39 | 0024H | Output Frequency, <1> | Output Frequency, <1> |
| 40 | 0025H | Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10) | Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10) |
| 41 | 0026H | Output Current, <2> | Output Current, <2> |
| 42 | 0027H | Output Power | Output Power |
| 43 | 0028H | Torque Reference (OLV only) | Torque Reference (OLV only) |
Manual — Read-only fault alarm and input register map — page 450
Source reference: SIEP C71060618F, December 2016, physical PDF page 450. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Register No. Contents
C.10 MEMOBUS/Modbus Data Table
0029H | Fault Contents 2
0029H | bit 0
0029H | bit 1
0029H | bit 2
0029H | bit 3
0029H | bit 4
0029H | bit 5
0029H | bit 6
0029H | bit 7 to bit F
002AH | Alarm Contents1
002AH | bit 0 to bit 1
002AH | bit 2
002AH | bit 3
002AH | bit 4
002AH | bit 5
002AH | bit 6
002AH | bit 7
002AH | bit 8
002AH | bit 9
002AH | bit A
002AH | bit B
002AH | bit C
002AH | bit D
002AH | bit E
002AH | bit F
002BH | Input Terminal Status
002BH | bit 0
002BH | bit 1
002BH | bit 2
002BH | bit 3
002BH | bit 4
002BH | bit 5
002BH | bit 6
002BH | bit 7 to bit F
Monitor register map (read only) — PDF page 450
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 0029H | Fault Contents 2 | Fault Contents 2 |
| 2 | 0029H | bit 0 | IGBT Short Circuit or Ground Fault (SC) |
| 3 | 0029H | bit 1 | Ground Fault (GF) |
| 4 | 0029H | bit 2 | Input Phase Loss (PF) |
| 5 | 0029H | bit 3 | Output Phase Loss (LF) |
| 6 | 0029H | bit 4 | Braking Resistor Overheat (rH) |
| 7 | 0029H | bit 5 | Reserved |
| 8 | 0029H | bit 6 | Motor Overheat 2 (PTC input) (oH4) |
| 9 | 0029H | bit 7 to bit F | Reserved |
| 10 | 002AH | Alarm Contents1 | Alarm Contents1 |
| 11 | 002AH | bit 0 to bit 1 | Reserved |
| 12 | 002AH | bit 2 | Run Command Input Error (EF) |
| 13 | 002AH | bit 3 | Drive Baseblock (bb) |
| 14 | 002AH | bit 4 | Overtorque Detection 1 (oL3) |
| 15 | 002AH | bit 5 | Heatsink Overheat (oH) |
| 16 | 002AH | bit 6 | Overvoltage (ov) |
| 17 | 002AH | bit 7 | Undervoltage (Uv) |
| 18 | 002AH | bit 8 | Reserved |
| 19 | 002AH | bit 9 | MEMOBUS/Modbus Communication Error (CE) |
| 20 | 002AH | bit A | Option Communication Error (bUS) |
| 21 | 002AH | bit B | Undertorque Detection 1/2 (UL3/UL4) |
| 22 | 002AH | bit C | Motor Overheat (oH3) |
| 23 | 002AH | bit D | PID Feedback Loss (FbL, FbH) |
| 24 | 002AH | bit E | Reserved |
| 25 | 002AH | bit F | Serial Communication Transmission Error (CALL) |
| 26 | 002BH | Input Terminal Status | Input Terminal Status |
| 27 | 002BH | bit 0 | Terminal S1 Closed |
| 28 | 002BH | bit 1 | Terminal S2 Closed |
| 29 | 002BH | bit 2 | Terminal S3 Closed |
| 30 | 002BH | bit 3 | Terminal S4 Closed |
| 31 | 002BH | bit 4 | Terminal S5 Closed |
| 32 | 002BH | bit 5 | Terminal S6 Closed |
| 33 | 002BH | bit 6 | Terminal S7 Closed |
| 34 | 002BH | bit 7 to bit F | Reserved |
Manual — Monitor status and output registers — page 451
Source reference: SIEP C71060618F, December 2016, physical PDF page 451. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Register No. Contents
C.10 MEMOBUS/Modbus Data Table
C
MEMOBUS/Modbus Communications
002CH | Drive Status 2
002CH | bit 0
002CH | bit 1
002CH | bit 2
002CH | bit 3
002CH | bit 4
002CH | bit 5
002CH | bit 6
002CH | bit 7
002CH | bit 8
002CH | bit 9
002CH | bit A
002CH | bit B
002CH | bit C
002CH | bit D
002CH | bit E
002CH | bit F
002DH | Output Terminal Status
002DH | bit 0
002DH | bit 1
002DH | bit 2
002DH | bit 3 to bit F
002EH | Reserved
002FH | Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H | Reserved
0031H | DC Bus Voltage, 1 Vdc units
0032H | Torque Monitor, 1% units
0033H | Reserved
0034H | Product Code 1 [ASCII], Product Type (V0 for V1000)
0035H | Product Code 2 [ASCII], Region Code
0036H to 0037H | Reserved
0038H | PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H | PID Input, 0.1% units, signed, 100% / max. output frequency
003AH | PID Output, 0.1% units, signed, 100% / max. output frequency
003BH to 003CH | Reserved
003DH | Communications Error Log <3>
003DH | bit 0
003DH | bit 1
003DH | bit 2
003DH | bit 3
003DH | bit 4
003DH | bit 5
003DH | bit 6
003DH | bit 7 to bit F
003EH | Output Frequency
003FH | Output Frequency
0040H to 004AH | Used for various monitors U1-□□. Refer to U: Monitors on page 399 for parameter details.
C10 read-only monitor register and bit map — PDF page 451
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 002CH | Drive Status 2 | Drive Status 2 |
| 2 | 002CH | bit 0 | During Run |
| 3 | 002CH | bit 1 | Zero Speed |
| 4 | 002CH | bit 2 | Speed Agree |
| 5 | 002CH | bit 3 | User Speed Agree |
| 6 | 002CH | bit 4 | Frequency Detection 1 |
| 7 | 002CH | bit 5 | Frequency Detection 2 |
| 8 | 002CH | bit 6 | Drive Ready |
| 9 | 002CH | bit 7 | During Undervoltage |
| 10 | 002CH | bit 8 | During Baseblock |
| 11 | 002CH | bit 9 | Frequency Reference from Operator Keypad |
| 12 | 002CH | bit A | Run Command from Operator Keypad |
| 13 | 002CH | bit B | Over/Undertorque 1, 2 |
| 14 | 002CH | bit C | Frequency Reference Loss |
| 15 | 002CH | bit D | During Fault Restart |
| 16 | 002CH | bit E | Fault |
| 17 | 002CH | bit F | Communication Timeout |
| 18 | 002DH | Output Terminal Status | Output Terminal Status |
| 19 | 002DH | bit 0 | Multi-Function Contact Output (terminal MA/MB-MC) |
| 20 | 002DH | bit 1 | Multi-Function Photocoupler Output 1 (terminal P1 - PC) |
| 21 | 002DH | bit 2 | Multi-Function Photocoupler Output 2 (terminal P2 - PC) |
| 22 | 002DH | bit 3 to bit F | Reserved |
| 23 | 002EH | Reserved | Reserved |
| 24 | 002FH | Frequency Reference Bias (from Up/Down 2 Function), 0.1% units | Frequency Reference Bias (from Up/Down 2 Function), 0.1% units |
| 25 | 0030H | Reserved | Reserved |
| 26 | 0031H | DC Bus Voltage, 1 Vdc units | DC Bus Voltage, 1 Vdc units |
| 27 | 0032H | Torque Monitor, 1% units | Torque Monitor, 1% units |
| 28 | 0033H | Reserved | Reserved |
| 29 | 0034H | Product Code 1 [ASCII], Product Type (V0 for V1000) | Product Code 1 [ASCII], Product Type (V0 for V1000) |
| 30 | 0035H | Product Code 2 [ASCII], Region Code | Product Code 2 [ASCII], Region Code |
| 31 | 0036H to 0037H | Reserved | Reserved |
| 32 | 0038H | PID Feedback, 0.1% units, unsigned, 100% / max. output frequency | PID Feedback, 0.1% units, unsigned, 100% / max. output frequency |
| 33 | 0039H | PID Input, 0.1% units, signed, 100% / max. output frequency | PID Input, 0.1% units, signed, 100% / max. output frequency |
| 34 | 003AH | PID Output, 0.1% units, signed, 100% / max. output frequency | PID Output, 0.1% units, signed, 100% / max. output frequency |
| 35 | 003BH to 003CH | Reserved | Reserved |
| 36 | 003DH | Communications Error Log <3> | Communications Error Log <3> |
| 37 | 003DH | bit 0 | CRC Error |
| 38 | 003DH | bit 1 | Data Length Error |
| 39 | 003DH | bit 2 | Reserved |
| 40 | 003DH | bit 3 | Parity Error |
| 41 | 003DH | bit 4 | Overrun Error |
| 42 | 003DH | bit 5 | Framing Error |
| 43 | 003DH | bit 6 | Timeout |
| 44 | 003DH | bit 7 to bit F | Reserved |
| 45 | 003EH | Output Frequency | r/min <4> |
| 46 | 003FH | Output Frequency | 0.01% units |
| 47 | 0040H to 004AH | Used for various monitors U1-□□. Refer to U: Monitors on page 399 for parameter details. | Used for various monitors U1-□□. Refer to U: Monitors on page 399 for parameter details. |
Manual — Monitor codes hours and option identifiers — page 452
Source reference: SIEP C71060618F, December 2016, physical PDF page 452. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Register No. Contents
C.10 MEMOBUS/Modbus Data Table
004BH | Drive status (U1-12)
004BH | bit 0
004BH | bit 1
004BH | bit 2
004BH | bit 3
004BH | bit 4
004BH | bit 5
004BH | bit 6
004BH | bit 7
004BH | bit 8
004BH | bit 9
004BH | bit A
004BH | bit B to D
004BH | bit E
004BH | bit F
004CH to 007EH | Used for various monitors U1-□□, U4-□□, U5-□□ and U6-□□. Refer to U: Monitors on page 399 for parameter details.
007FH | Alarm Code, Refer to Alarm Register Contents on page 458 for alarm codes.
0080H to 0097H | Used for monitors U2-□□, U3-□□. Refer to U: Monitors on page 399 for parameter details and Refer to Fault Trace Contents on page 457 for register value descriptions.
0098H, 0099H | U4-01 (Cumulative Operation Time) Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.
009AH, 009BH | U4-03 (Cooling Fan Operation Time) Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.
00ABH | Drive Rated Current <2>
00ACH | Motor Speed (Open Loop Vector only)
00ADH | Motor Speed (Open Loop Vector only)
00AEH, 00AFH | Reserved
00B0H | Option Code
00B1H to 00B4H | Reserved
00B5H | Frequency Reference After Soft-starter
00B6H | Frequency Reference After Soft-starter
00B7H | Frequency Reference
00B8H | Frequency Reference
00BFH | oPE Error Number
C10 read-only monitor register and bit map — PDF page 452
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 004BH | Drive status (U1-12) | Drive status (U1-12) |
| 2 | 004BH | bit 0 | During Run |
| 3 | 004BH | bit 1 | During Zero Speed |
| 4 | 004BH | bit 2 | During Reverse Run |
| 5 | 004BH | bit 3 | During Fault Reset Signal Input |
| 6 | 004BH | bit 4 | During Speed Agree |
| 7 | 004BH | bit 5 | Drive Ready |
| 8 | 004BH | bit 6 | Alarm |
| 9 | 004BH | bit 7 | Fault |
| 10 | 004BH | bit 8 | During Operation Error (oPE□□) |
| 11 | 004BH | bit 9 | During Momentary Power Loss |
| 12 | 004BH | bit A | Motor 2 selected |
| 13 | 004BH | bit B to D | Reserved |
| 14 | 004BH | bit E | ComRef status, NetRef status |
| 15 | 004BH | bit F | ComCtrl status, NetCtrl status |
| 16 | 004CH to 007EH | Used for various monitors U1-□□, U4-□□, U5-□□ and U6-□□. Refer to U: Monitors on page 399 for parameter details. | Used for various monitors U1-□□, U4-□□, U5-□□ and U6-□□. Refer to U: Monitors on page 399 for parameter details. |
| 17 | 007FH | Alarm Code, Refer to Alarm Register Contents on page 458 for alarm codes. | Alarm Code, Refer to Alarm Register Contents on page 458 for alarm codes. |
| 18 | 0080H to 0097H | Used for monitors U2-□□, U3-□□. Refer to U: Monitors on page 399 for parameter details and Refer to Fault Trace Contents on page 457 for register value descriptions. | Used for monitors U2-□□, U3-□□. Refer to U: Monitors on page 399 for parameter details and Refer to Fault Trace Contents on page 457 for register value descriptions. |
| 19 | 0098H, 0099H | U4-01 (Cumulative Operation Time) Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5. | U4-01 (Cumulative Operation Time) Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5. |
| 20 | 009AH, 009BH | U4-03 (Cooling Fan Operation Time) Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5. | U4-03 (Cooling Fan Operation Time) Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5. |
| 21 | 00ABH | Drive Rated Current <2> | Drive Rated Current <2> |
| 22 | 00ACH | Motor Speed (Open Loop Vector only) | r/min units <4> |
| 23 | 00ADH | Motor Speed (Open Loop Vector only) | 0.01% units |
| 24 | 00AEH, 00AFH | Reserved | Reserved |
| 25 | 00B0H | Option Code | The following lists the 3 and 4 letter ASCII codes stored for each serial communication option: CANopen (Model: SI-S3/V): 5353H CC-Link (Model: SI-C3/V): 5343H DeviceNet (Model: SI-N3/V): 534EH PROFIBUS-DP (Model: SI-P3/V): 5350H MECHATROLINK-II (Model: SI-T3/V): 5354H MECHATROLINK-III (Model: SI-ET3/V): 1004H CompoNet (Model: SI-M3/V): 434EH Other options use their own unique codes. Refer to the communication option instruction manual for the option code. |
| 26 | 00B1H to 00B4H | Reserved | Reserved |
| 27 | 00B5H | Frequency Reference After Soft-starter | r/min units <4> |
| 28 | 00B6H | Frequency Reference After Soft-starter | 0.01% units |
| 29 | 00B7H | Frequency Reference | r/min <4> |
| 30 | 00B8H | Frequency Reference | 0.01% units |
| 31 | 00BFH | oPE Error Number | oPE Error Number |
Manual — Fault contents registers3–5 — page 453
Source reference: SIEP C71060618F, December 2016, physical PDF page 453. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Register No. Contents
C.10 MEMOBUS/Modbus Data Table
C
MEMOBUS/Modbus Communications
00C0H | Fault contents 3
00C0H | bit 0
00C0H | bit 1
00C0H | bit 2
00C0H | bit 3
00C0H | bit 4
00C0H | bit 5
00C0H | bit 6
00C0H | bit 7
00C0H | bit 8
00C0H | bit 9
00C0H | bit A
00C0H | bit B
00C0H | bit C
00C0H | bit D
00C0H | bit E
00C0H | bit F
00C1H | Fault contents 4
00C1H | bit 0
00C1H | bit 1
00C1H | bit 2
00C1H | bit 3
00C1H | bit 4
00C1H | bit 5 to 6
00C1H | bit 7
00C1H | bit 8
00C1H | bit 9
00C1H | bit A
00C1H | bit B
00C1H | bit C
00C1H | bit D
00C1H | bit E
00C1H | bit F
00C2H | Fault contents 5
00C2H | bit 0
00C2H | bit 1
00C2H | bit 2 to 3
00C2H | bit 4
00C2H | bit 5
00C2H | bit 6
00C2H | bit 7
00C2H | bit 8
00C2H | bit 9
00C2H | bit A
00C2H | bit B to E
00C2H | bit F
C10 read-only monitor register and bit map — PDF page 453
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 00C0H | Fault contents 3 | Fault contents 3 |
| 2 | 00C0H | bit 0 | Reserved |
| 3 | 00C0H | bit 1 | Undervoltage (Uv1) |
| 4 | 00C0H | bit 2 | Control Power Supply Undervoltage (Uv2) |
| 5 | 00C0H | bit 3 | Soft Charge Circuit Fault (Uv3) |
| 6 | 00C0H | bit 4 | IGBT Short Circuit or Ground Fault (SC) |
| 7 | 00C0H | bit 5 | Ground Fault (GF) |
| 8 | 00C0H | bit 6 | Overcurrent (oC) |
| 9 | 00C0H | bit 7 | Overvoltage (ov) |
| 10 | 00C0H | bit 8 | Heatsink Overheat (oH) |
| 11 | 00C0H | bit 9 | Heatsink Overheat (oH1) |
| 12 | 00C0H | bit A | Motor Overload (oL1) |
| 13 | 00C0H | bit B | Drive Overload (oL2) |
| 14 | 00C0H | bit C | Overtorque Detection 1 (oL3) |
| 15 | 00C0H | bit D | Overtorque Detection 2 (oL4) |
| 16 | 00C0H | bit E | Dynamic Braking Transistor Fault (rr) |
| 17 | 00C0H | bit F | Braking Resistor Overheat (rH) |
| 18 | 00C1H | Fault contents 4 | Fault contents 4 |
| 19 | 00C1H | bit 0 | External Fault at input terminal S3 (EF3) |
| 20 | 00C1H | bit 1 | External Fault at input terminal S4 (EF4) |
| 21 | 00C1H | bit 2 | External Fault at input terminal S5 (EF5) |
| 22 | 00C1H | bit 3 | External Fault at input terminal S6 (EF6) |
| 23 | 00C1H | bit 4 | External Fault at input terminal S7 (EF7) |
| 24 | 00C1H | bit 5 to 6 | Reserved |
| 25 | 00C1H | bit 7 | Overspeed (oS) |
| 26 | 00C1H | bit 8 | Excessive Speed Deviation (dEv) |
| 27 | 00C1H | bit 9 | PG Disconnected (PGo) |
| 28 | 00C1H | bit A | Input Phase Loss (PF) |
| 29 | 00C1H | bit B | Output Phase Loss (LF) |
| 30 | 00C1H | bit C | Motor Overheat Alarm (PTC input) (oH3) |
| 31 | 00C1H | bit D | Digital Operator Connection Fault (oPr) |
| 32 | 00C1H | bit E | EEPROM Write Error (Err) |
| 33 | 00C1H | bit F | Motor Overheat Fault (PTC input) (oH4) |
| 34 | 00C2H | Fault contents 5 | Fault contents 5 |
| 35 | 00C2H | bit 0 | MEMOBUS/Modbus Communication Error (CE) |
| 36 | 00C2H | bit 1 | Option Communication Error (bUS) |
| 37 | 00C2H | bit 2 to 3 | Reserved |
| 38 | 00C2H | bit 4 | Control Fault (CF) |
| 39 | 00C2H | bit 5 | Reserved |
| 40 | 00C2H | bit 6 | Option External Fault (EF0) |
| 41 | 00C2H | bit 7 | PID Feedback Loss (FbL) |
| 42 | 00C2H | bit 8 | Undertorque Detection 1 (UL3) |
| 43 | 00C2H | bit 9 | Undertorque Detection 2 (UL4) |
| 44 | 00C2H | bit A | High Slip Braking Overload (oL7) |
| 45 | 00C2H | bit B to E | Reserved |
| 46 | 00C2H | bit F | Hardware fault (includes oFA□□) |
Manual — Fault contents6–7 and alarm2 — page 454
Source reference: SIEP C71060618F, December 2016, physical PDF page 454. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Register No. Contents
C.10 MEMOBUS/Modbus Data Table
00C3H | Fault contents 6
00C3H | bit 0 to 4
00C3H | bit 5
00C3H | bit 6
00C3H | bit 7
00C3H | bit 8
00C3H | bit 9
00C3H | bit A
00C3H | bit B to F
00C4H | Fault contents 7
00C4H | bit 0
00C4H | bit 1
00C4H | bit 2
00C4H | bit 3
00C4H | bit 4
00C4H | bit 5
00C4H | bit 6
00C4H | bit 7
00C4H | bit 8
00C4H | bit 9 to F
00C8H | Alarm contents 2
00C8H | bit 0
00C8H | bit 1
00C8H | bit 2
00C8H | bit 3
00C8H | bit 4
00C8H | bit 5
00C8H | bit 6
00C8H | bit 7
00C8H | bit 8
00C8H | bit 9
00C8H | bit A
00C8H | bit B
00C8H | bit C
00C8H | bit D, E
00C8H | bit F
C10 read-only monitor register and bit map — PDF page 454
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 00C3H | Fault contents 6 | Fault contents 6 |
| 2 | 00C3H | bit 0 to 4 | Reserved |
| 3 | 00C3H | bit 5 | Output Current Imbalance (LF2) |
| 4 | 00C3H | bit 6 | Pullout Detection (STo) |
| 5 | 00C3H | bit 7 | PG Disconnected (PGo) |
| 6 | 00C3H | bit 8 | MECHATROLINK Watchdog Timer Error (E5) |
| 7 | 00C3H | bit 9 | Reserved |
| 8 | 00C3H | bit A | Too many speed search restarts (SEr) |
| 9 | 00C3H | bit B to F | Reserved |
| 10 | 00C4H | Fault contents 7 | Fault contents 7 |
| 11 | 00C4H | bit 0 | PID Feedback Loss (FbH) |
| 12 | 00C4H | bit 1 | External Fault 1, input terminal S1 (EF1) |
| 13 | 00C4H | bit 2 | External Fault 2, input terminal S2 (EF2) |
| 14 | 00C4H | bit 3 | Mechanical Weakening Detection 1 (oL5) |
| 15 | 00C4H | bit 4 | Mechanical Weakening Detection 2 (UL5) |
| 16 | 00C4H | bit 5 | Current Offset Fault (CoF) |
| 17 | 00C4H | bit 6 | Reserved |
| 18 | 00C4H | bit 7 | Reserved |
| 19 | 00C4H | bit 8 | DriveWorksEZ fault (dWFL) |
| 20 | 00C4H | bit 9 to F | Reserved |
| 21 | 00C8H | Alarm contents 2 | Alarm contents 2 |
| 22 | 00C8H | bit 0 | Undervoltage (Uv) |
| 23 | 00C8H | bit 1 | Overvoltage (ov) |
| 24 | 00C8H | bit 2 | Heatsink Overheat (oH) |
| 25 | 00C8H | bit 3 | Drive Overheat (oH2) |
| 26 | 00C8H | bit 4 | Overtorque 1 (oL3) |
| 27 | 00C8H | bit 5 | Overtorque 2 (oL4) |
| 28 | 00C8H | bit 6 | Run Commands Input Error (EF) |
| 29 | 00C8H | bit 7 | Drive Baseblock (bb) |
| 30 | 00C8H | bit 8 | External Fault 3, input terminal S3 (EF3) |
| 31 | 00C8H | bit 9 | External Fault 4, input terminal S4 (EF4) |
| 32 | 00C8H | bit A | External Fault 5, input terminal S5 (EF5) |
| 33 | 00C8H | bit B | External Fault 6, input terminal S6 (EF6) |
| 34 | 00C8H | bit C | External Fault 7, input terminal S7 (EF7) |
| 35 | 00C8H | bit D, E | Reserved |
| 36 | 00C8H | bit F | Overspeed (oS) |
Manual — Alarm contents3–5 — page 455
Source reference: SIEP C71060618F, December 2016, physical PDF page 455. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Register No. Contents
C.10 MEMOBUS/Modbus Data Table
C
MEMOBUS/Modbus Communications
00C9H | Alarm contents 3
00C9H | bit 0
00C9H | bit 1
00C9H | bit 2
00C9H | bit 3
00C9H | bit 4
00C9H | bit 5
00C9H | bit 6
00C9H | bit 7
00C9H | bit 8
00C9H | bit 9
00C9H | bit A
00C9H | bit B
00C9H | bit C
00C9H | bit D
00C9H | bit E
00C9H | bit F
00CAH | Alarm contents 4
00CAH | bit 0
00CAH | bit 1
00CAH | bit 2 to 5
00CAH | bit 6
00CAH | bit 7
00CAH | bit 9
00CAH | bit A to F
00CBH | Alarm contents 5
00CBH | bit 0
00CBH | bit 1
00CBH | bit 2
00CBH | bit 3
00CBH | bit 4
00CBH | bit 5
00CBH | bit 6
00CBH | bit 7
00CBH | bit 8
00CBH | bit 9
00CBH | bit A
00CBH | bit B
00CBH | bit C
00CBH | bit D
00CBH | bit E to F
C10 read-only monitor register and bit map — PDF page 455
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 00C9H | Alarm contents 3 | Alarm contents 3 |
| 2 | 00C9H | bit 0 | Excessive Speed Deviation (dEv) |
| 3 | 00C9H | bit 1 | PG Disconnected (PGo) |
| 4 | 00C9H | bit 2 | Digital Operator Connection Fault (oPr) |
| 5 | 00C9H | bit 3 | MEMOBUS/Modbus Communication Error (CE) |
| 6 | 00C9H | bit 4 | Option Communication Error (bUS) |
| 7 | 00C9H | bit 5 | Serial Communication Transmission Error (CALL) |
| 8 | 00C9H | bit 6 | Motor Overload (oL1) |
| 9 | 00C9H | bit 7 | Drive Overload (oL2) |
| 10 | 00C9H | bit 8 | Reserved |
| 11 | 00C9H | bit 9 | Option Card External fault (EF0) |
| 12 | 00C9H | bit A | Motor 2 Switch command input during run (rUn) |
| 13 | 00C9H | bit B | Reserved |
| 14 | 00C9H | bit C | Serial Communication Transmission Error (CALL) |
| 15 | 00C9H | bit D | Undertorque Detection 1 (UL3) |
| 16 | 00C9H | bit E | Undertorque Detection 2 (UL4) |
| 17 | 00C9H | bit F | MEMOBUS/Modbus Test Mode Fault (SE) |
| 18 | 00CAH | Alarm contents 4 | Alarm contents 4 |
| 19 | 00CAH | bit 0 | Reserved |
| 20 | 00CAH | bit 1 | Motor Overheat 1 (PTC Input) (oH3) |
| 21 | 00CAH | bit 2 to 5 | Reserved |
| 22 | 00CAH | bit 6 | PID Feedback Loss (FbL) |
| 23 | 00CAH | bit 7 | PID Feedback Loss (FbH) |
| 24 | 00CAH | bit 9 | Drive Disabled (dnE) |
| 25 | 00CAH | bit A to F | Reserved |
| 26 | 00CBH | Alarm contents 5 | Alarm contents 5 |
| 27 | 00CBH | bit 0 | MECHATROLINK Watchdog Timer Error (E5) |
| 28 | 00CBH | bit 1 | Reserved |
| 29 | 00CBH | bit 2 | MECHATROLINK Comm. Cycle Setting Error (CyC) |
| 30 | 00CBH | bit 3 | High Current Alarm (HCA) |
| 31 | 00CBH | bit 4 | Cooling Fan Maintenance Time (LT-1) |
| 32 | 00CBH | bit 5 | Soft Charge Bypass Relay Maintenance Time (LT-2) |
| 33 | 00CBH | bit 6 | Reserved |
| 34 | 00CBH | bit 7 | SI-S/V EEPROM Error (EEP) |
| 35 | 00CBH | bit 8 | External Fault 1 (input terminal S1) (EF1) |
| 36 | 00CBH | bit 9 | External Fault 2 (input terminal S2) (EF2) |
| 37 | 00CBH | bit A | Safe Disable Input (HbbF) |
| 38 | 00CBH | bit B | Safe Disable Input (Hbb) |
| 39 | 00CBH | bit C | Mechanical Weakening Detection 1 (oL5) |
| 40 | 00CBH | bit D | Mechanical Weakening Detection 2 (UL5) |
| 41 | 00CBH | bit E to F | Reserved |
Manual — Control and option fault bits; register footnotes — page 456
Source reference: SIEP C71060618F, December 2016, physical PDF page 456. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Register No. Contents
<1> Units are determined by parameter o1-03. <2> Display is in the following units: BA0001 to BA0018, 2A0001 to 2A0040, and 4A0001 to 4A0023: 0.01 A units. 2A0056 to 2A0069, 4A0031 to 4A0038: 0.1 A units. <3> The communication error log is stored until the fault is reset. <4> Depending on the motor used the correct motor pole number must be set to parameter E2-04, E4-04 or E5-05. <5> Available in drive software versions PRG: 1011 and later.
C.10 MEMOBUS/Modbus Data Table
00D0H | CPF Contents 1
00D0H | bit 0 to 1
00D0H | bit 2
00D0H | bit 3
00D0H | bit 4 to 5
00D0H | bit 6
00D0H | bit 7
00D0H | bit 8
00D0H | bit 9 to A
00D0H | bit B
00D0H | bit C
00D0H | bit D
00D0H | bit E
00D0H | bit F
00D1H | CPF Contents 2
00D1H | bit 0
00D1H | bit 1
00D1H | bit 2
00D1H | bit 3
00D1H | bit 4
00D1H | bit 5
00D1H | bit 6
00D1H | bit 7
00D1H | bit 8
00D1H | bit 9
00D1H | bit A to F
00D8H | Option Card Fault Contents
00D8H | bit 0
00D8H | bit 1
00D8H | bit 3
00D8H | bit 4
00D8H | bit 5 to F
00FBH | Output Current <2>
C10 read-only monitor register and bit map — PDF page 456
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 00D0H | CPF Contents 1 | CPF Contents 1 |
| 2 | 00D0H | bit 0 to 1 | Reserved |
| 3 | 00D0H | bit 2 | A/D Conversion Error (CPF02) |
| 4 | 00D0H | bit 3 | PWM Data Fault (CPF03) |
| 5 | 00D0H | bit 4 to 5 | Reserved |
| 6 | 00D0H | bit 6 | Drive specification mismatch during Terminal Board or Control Board replacement (CPF06) |
| 7 | 00D0H | bit 7 | Terminal Board Communications Fault (CPF07) |
| 8 | 00D0H | bit 8 | EEPROM Serial Communications Fault (CPF08) |
| 9 | 00D0H | bit 9 to A | Reserved |
| 10 | 00D0H | bit B | RAM Fault (CPF11) |
| 11 | 00D0H | bit C | FLASH Memory Fault (CPF12) |
| 12 | 00D0H | bit D | Watchdog Circuit Exception (CPF13) |
| 13 | 00D0H | bit E | Control Circuit Fault (CPF14) |
| 14 | 00D0H | bit F | Reserved |
| 15 | 00D1H | CPF Contents 2 | CPF Contents 2 |
| 16 | 00D1H | bit 0 | Clock Fault (CPF16) |
| 17 | 00D1H | bit 1 | Timing Fault (CPF17) |
| 18 | 00D1H | bit 2 | Control Circuit Fault (CPF18) |
| 19 | 00D1H | bit 3 | Control Circuit Fault (CPF19) |
| 20 | 00D1H | bit 4 | Hardware fault at power up (CPF20) |
| 21 | 00D1H | bit 5 | Hardware fault at communication start up (CPF21) |
| 22 | 00D1H | bit 6 | A/D Conversion Fault (CPF22) |
| 23 | 00D1H | bit 7 | PWM Feedback Fault (CPF23) |
| 24 | 00D1H | bit 8 | Drive capacity signal fault (CPF24) |
| 25 | 00D1H | bit 9 | Terminal board is not properly connected (CPF25) |
| 26 | 00D1H | bit A to F | Reserved |
| 27 | 00D8H | Option Card Fault Contents | Option Card Fault Contents |
| 28 | 00D8H | bit 0 | Option Compatibility Error (oFA00) |
| 29 | 00D8H | bit 1 | Option not properly connected (oFA01) |
| 30 | 00D8H | bit 3 | Option Self-diagnostics Error (oFA03) |
| 31 | 00D8H | bit 4 | Option Flash Write Mode Error (oFA04) |
| 32 | 00D8H | bit 5 to F | Reserved |
| 33 | 00FBH | Output Current <2> | Output Current <2> |
Manual — Broadcast and fault trace codes — page 457
Source reference: SIEP C71060618F, December 2016, physical PDF page 457. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ Broadcast Messages
Data can be written from the master to all slave devices at the same time. The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not respond.
Register No. Contents
◆ Fault Trace Contents
The table below shows the fault codes that can be read out by MEMOBUS/Modbus commands from the U2-□□ monitor parameters.
Note: Uv1 and Uv2 faults are not saved to the fault history.
Table C.4 Fault Trace / History Register Contents
Fault Code Fault Name
C.10 MEMOBUS/Modbus Data Table
C
MEMOBUS/Modbus Communications
0001H | Digital Input Command
0001H | bit 0
0001H | bit 1
0001H | bit 2, 3
0001H | bit 4
0001H | bit 5
0001H | bit 6 to B
0001H | bit C
0001H | bit D
0001H | bit E
0001H | bit F
0002H | Frequency Reference
0002H | Undervoltage (Uv1)
0003H | Control Power Supply Undervoltage (Uv2)
0004H | Soft Charge Circuit Fault (Uv3)
0005H <1> | IGBT Short Circuit (SC)
0006H | Ground Fault (GF)
0007H | Overcurrent (oC)
0008H | Overvoltage (ov)
0009H | Heatsink Overheat (oH)
000AH | Heatsink Overheat (oH1)
000BH | Motor Overload (oL1)
000CH | Drive Overload (oL2)
000DH | Overtorque Detection 1 (oL3)
000EH | Overtorque Detection 2 (oL4)
000FH | Dynamic Braking Transistor (rr)
0010H | Braking Resistor Overheat (rH)
0011H | External Fault at input terminal S3 (EF3)
0012H | External Fault at input terminal S4 (EF4)
0013H | External Fault at input terminal S5 (EF5)
0014H | External Fault at input terminal S6 (EF6)
0015H | External Fault at input terminal S7 (EF7)
0018H | Overspeed (oS)
0019H | Excessive Speed Deviation (dEv)
001AH | PG Disconnect (PGo)
001BH | Input Phase Loss (PF)
001CH | Output Phase Loss (LF)
001DH | Motor Overheat (PTC input) (oH3)
001EH | Digital Operator Connection (oPr)
001FH | EEPROM Write Error (Err)
0020H | Motor Overheat (PTC input) (oH4)
0021H | MEMOBUS/Modbus Communication Error (CE)
0022H | Option Communication Error (bUS)
0025H | Control fault (CF)
0027H | PROFIBUS-DP Option External Fault (EF0)
0028H | PID Feedback Loss (FbL)
0029H | Undertorque Detection 1 (UL3)
002AH | Undertorque Detection 2 (UL4)
002BH | High Slip Braking Overload (oL7)
0030H | Hardware Fault (including oFx)
0036H | Output Current Imbalance (LF2)
0037H | Pullout Detection (Sto)
0038H | PG Disconnected (PGo)
0039H | MECHATROLINK Watchdog Timer Error (E5)
003BH | Too many speed search restarts (SEr)
0041H | PID Feedback Loss (FbH)
0042H | External Fault 1, input terminal S1 (EF1)
0043H | External Fault 2, input terminal S2 (EF2)
0044H | Mechanical Weakening Detection 1 (oL5)
0045H | Mechanical Weakening Detection 2 (UL5)
0046H | Current Offset Fault (CoF)
0049H | DriveWorksEZ Fault (dWFL)
0083H | A/D Conversion Error (CPF02)
Broadcast command registers — PDF page 457
| Source row | Register number hex | Bit / subitem / merged contents | Contents |
|---|---|---|---|
| 1 | 0001H | Digital Input Command | Digital Input Command |
| 2 | 0001H | bit 0 | Forward Run (0: Stop 1: Run) |
| 3 | 0001H | bit 1 | Direction Command (0: Forward, 1: Reverse) |
| 4 | 0001H | bit 2, 3 | Reserved |
| 5 | 0001H | bit 4 | External Fault |
| 6 | 0001H | bit 5 | Fault Reset |
| 7 | 0001H | bit 6 to B | Reserved |
| 8 | 0001H | bit C | Multi-Function Digital Input S5 (enabled when bit C of register 000FH is on) |
| 9 | 0001H | bit D | Multi-Function Digital Input S6 (enabled when bit D of register 000FH is on) |
| 10 | 0001H | bit E | Multi-Function Digital Input S7 (enabled when bit E of register 000FH is on) |
| 11 | 0001H | bit F | Reserved |
| 12 | 0002H | Frequency Reference | 30000/100% |
C4 fault trace/history column 1 — PDF page 457
| Source row | Code hex | Name |
|---|---|---|
| 1 | 0002H | Undervoltage (Uv1) |
| 2 | 0003H | Control Power Supply Undervoltage (Uv2) |
| 3 | 0004H | Soft Charge Circuit Fault (Uv3) |
| 4 | 0005H <1> | IGBT Short Circuit (SC) |
| 5 | 0006H | Ground Fault (GF) |
| 6 | 0007H | Overcurrent (oC) |
| 7 | 0008H | Overvoltage (ov) |
| 8 | 0009H | Heatsink Overheat (oH) |
| 9 | 000AH | Heatsink Overheat (oH1) |
| 10 | 000BH | Motor Overload (oL1) |
| 11 | 000CH | Drive Overload (oL2) |
| 12 | 000DH | Overtorque Detection 1 (oL3) |
| 13 | 000EH | Overtorque Detection 2 (oL4) |
| 14 | 000FH | Dynamic Braking Transistor (rr) |
| 15 | 0010H | Braking Resistor Overheat (rH) |
| 16 | 0011H | External Fault at input terminal S3 (EF3) |
| 17 | 0012H | External Fault at input terminal S4 (EF4) |
| 18 | 0013H | External Fault at input terminal S5 (EF5) |
| 19 | 0014H | External Fault at input terminal S6 (EF6) |
| 20 | 0015H | External Fault at input terminal S7 (EF7) |
| 21 | 0018H | Overspeed (oS) |
| 22 | 0019H | Excessive Speed Deviation (dEv) |
| 23 | 001AH | PG Disconnect (PGo) |
| 24 | 001BH | Input Phase Loss (PF) |
| 25 | 001CH | Output Phase Loss (LF) |
C4 fault trace/history column 2 — PDF page 457
| Source row | Code hex | Name |
|---|---|---|
| 1 | 001DH | Motor Overheat (PTC input) (oH3) |
| 2 | 001EH | Digital Operator Connection (oPr) |
| 3 | 001FH | EEPROM Write Error (Err) |
| 4 | 0020H | Motor Overheat (PTC input) (oH4) |
| 5 | 0021H | MEMOBUS/Modbus Communication Error (CE) |
| 6 | 0022H | Option Communication Error (bUS) |
| 7 | 0025H | Control fault (CF) |
| 8 | 0027H | PROFIBUS-DP Option External Fault (EF0) |
| 9 | 0028H | PID Feedback Loss (FbL) |
| 10 | 0029H | Undertorque Detection 1 (UL3) |
| 11 | 002AH | Undertorque Detection 2 (UL4) |
| 12 | 002BH | High Slip Braking Overload (oL7) |
| 13 | 0030H | Hardware Fault (including oFx) |
| 14 | 0036H | Output Current Imbalance (LF2) |
| 15 | 0037H | Pullout Detection (Sto) |
| 16 | 0038H | PG Disconnected (PGo) |
| 17 | 0039H | MECHATROLINK Watchdog Timer Error (E5) |
| 18 | 003BH | Too many speed search restarts (SEr) |
| 19 | 0041H | PID Feedback Loss (FbH) |
| 20 | 0042H | External Fault 1, input terminal S1 (EF1) |
| 21 | 0043H | External Fault 2, input terminal S2 (EF2) |
| 22 | 0044H | Mechanical Weakening Detection 1 (oL5) |
| 23 | 0045H | Mechanical Weakening Detection 2 (UL5) |
| 24 | 0046H | Current Offset Fault (CoF) |
| 25 | 0049H | DriveWorksEZ Fault (dWFL) |
| 26 | 0083H | A/D Conversion Error (CPF02) |
Manual — Fault trace continuation and alarm codes — page 458
Source reference: SIEP C71060618F, December 2016, physical PDF page 458. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Fault Code Fault Name
<1> Available in drive software versions PRG: 1020 and later.
◆ Alarm Register Contents
The table below shows the alarm codes that can be read out from MEMOBUS/Modbus register 007FH.
Table C.5 Alarm Register 007FH Contents
Alarm Code Fault Name
C.10 MEMOBUS/Modbus Data Table
0084H | PWM Data Fault (CPF03)
0087H | Drive specification mismatch during Terminal Board or Control Board replacement (CPF06)
0088H | Terminal Board Communication Fault (CPF07)
0089H | EEPROM Serial Communication Fault (CPF08)
008CH | RAM fault (CPF11)
008DH | Flash memory circuit exception (CPF12)
008EH | Watchdog circuit exception (CPF13)
008FH | Control Circuit Fault (CPF14)
0091H | Clock Fault (CPF16)
0092H | Timing Fault (CPF17)
0093H | Control Circuit Fault (CPF18)
0094H | Control Circuit Fault (CPF19)
0095H | Hardware fault at power up (CPF20)
0096H | Hardware fault at communication start up (CPF21)
0097H | A/D Conversion Fault (CPF22)
0098H | PWM Feedback Fault (CPF23)
0099H | Drive capacity signal fault (CPF24)
0101H | Option compatibility error (oFA00)
0102H | Option not properly connected (oFA01)
0104H | Option Self-diagnostics Error (oFA03)
0105H | Option Flash Write Mode Error (oFA04)
0001H | Undervoltage (Uv)
0002H | Overvoltage (ov)
0003H | Heatsink Overheat (oH)
0004H | Drive Overheat (oH2)
0005H | Overtorque 1 (oL3)
0006H | Overtorque 2 (oL4)
0007H | Run commands input error (EF)
0008H | Drive Baseblock (bb)
0009H | External Fault 3, input terminal S3 (EF3)
000AH | External Fault 4, input terminal S4 (EF4)
000BH | External Fault 5, input terminal S5 (EF5)
000CH | External Fault 6, input terminal S6 (EF6)
000DH | External Fault 7, input terminal S7 (EF7)
000FH | Reserved
0010H | Overspeed (oS)
0011H | Excessive Speed Deviation (dEv)
0012H | PG Disconnected (PGo)
0013H | Digital operator connection fault (oPr)
0014H | MEMOBUS/Modbus Communication Error (CE)
0015H | Option Communication Error (bUS)
0016H | Serial Communication Transmission Error (CALL)
0017H | Motor Overload (oL1)
0018H | Drive Overload (oL2)
001AH | Option Card External Fault (EF0)
001BH | Motor Switch command input during run (rUn)
001DH | Serial Communication Transmission Error (CALL)
001EH | Undertorque Detection 1 (UL3)
001FH | Undertorque Detection 2 (UL4)
0020H | MEMOBUS/Modbus Test Mode Fault (SE)
0022H | Motor Overheat (oH3)
0027H | PID Feedback Loss (FbL)
0028H | PID Feedback Loss (FbH)
002AH | Drive Disabled (dnE)
002BH | PG Disconnected (PGo)
0031H | MECHATROLINK Watchdog Timer Error (E5)
0032H | Station Address Setting Error (AEr)
0033H | MECHATROLINK Comm. Cycle Setting Error (CyC)
0034H | High Current Alarm (HCA)
0039H | External Fault (input terminal S1) (EF1)
003AH | External Fault (input terminal S2) (EF2)
003BH | Safe Disable Input (HbbF)
003CH | Safe Disable Input (Hbb)
003DH | Mechanical Weakening Detection 1 (oL5)
003EH | Mechanical Weakening Detection 2 (UL5)
0049H | DriveWorksEZ Alarm (dWAL)
C4 fault trace/history column 0 — PDF page 458
| Source row | Code hex | Name |
|---|---|---|
| 1 | 0084H | PWM Data Fault (CPF03) |
| 2 | 0087H | Drive specification mismatch during Terminal Board or Control Board replacement (CPF06) |
| 3 | 0088H | Terminal Board Communication Fault (CPF07) |
| 4 | 0089H | EEPROM Serial Communication Fault (CPF08) |
| 5 | 008CH | RAM fault (CPF11) |
| 6 | 008DH | Flash memory circuit exception (CPF12) |
| 7 | 008EH | Watchdog circuit exception (CPF13) |
| 8 | 008FH | Control Circuit Fault (CPF14) |
| 9 | 0091H | Clock Fault (CPF16) |
| 10 | 0092H | Timing Fault (CPF17) |
| 11 | 0093H | Control Circuit Fault (CPF18) |
C4 fault trace/history column 1 — PDF page 458
| Source row | Code hex | Name |
|---|---|---|
| 1 | 0094H | Control Circuit Fault (CPF19) |
| 2 | 0095H | Hardware fault at power up (CPF20) |
| 3 | 0096H | Hardware fault at communication start up (CPF21) |
| 4 | 0097H | A/D Conversion Fault (CPF22) |
| 5 | 0098H | PWM Feedback Fault (CPF23) |
| 6 | 0099H | Drive capacity signal fault (CPF24) |
| 7 | 0101H | Option compatibility error (oFA00) |
| 8 | 0102H | Option not properly connected (oFA01) |
| 9 | 0104H | Option Self-diagnostics Error (oFA03) |
| 10 | 0105H | Option Flash Write Mode Error (oFA04) |
C5 alarm register007FH column 2 — PDF page 458
| Source row | Code hex | Name |
|---|---|---|
| 1 | 0001H | Undervoltage (Uv) |
| 2 | 0002H | Overvoltage (ov) |
| 3 | 0003H | Heatsink Overheat (oH) |
| 4 | 0004H | Drive Overheat (oH2) |
| 5 | 0005H | Overtorque 1 (oL3) |
| 6 | 0006H | Overtorque 2 (oL4) |
| 7 | 0007H | Run commands input error (EF) |
| 8 | 0008H | Drive Baseblock (bb) |
| 9 | 0009H | External Fault 3, input terminal S3 (EF3) |
| 10 | 000AH | External Fault 4, input terminal S4 (EF4) |
| 11 | 000BH | External Fault 5, input terminal S5 (EF5) |
| 12 | 000CH | External Fault 6, input terminal S6 (EF6) |
| 13 | 000DH | External Fault 7, input terminal S7 (EF7) |
| 14 | 000FH | Reserved |
| 15 | 0010H | Overspeed (oS) |
| 16 | 0011H | Excessive Speed Deviation (dEv) |
| 17 | 0012H | PG Disconnected (PGo) |
| 18 | 0013H | Digital operator connection fault (oPr) |
| 19 | 0014H | MEMOBUS/Modbus Communication Error (CE) |
| 20 | 0015H | Option Communication Error (bUS) |
| 21 | 0016H | Serial Communication Transmission Error (CALL) |
| 22 | 0017H | Motor Overload (oL1) |
| 23 | 0018H | Drive Overload (oL2) |
C5 alarm register007FH column 3 — PDF page 458
| Source row | Code hex | Name |
|---|---|---|
| 1 | 001AH | Option Card External Fault (EF0) |
| 2 | 001BH | Motor Switch command input during run (rUn) |
| 3 | 001DH | Serial Communication Transmission Error (CALL) |
| 4 | 001EH | Undertorque Detection 1 (UL3) |
| 5 | 001FH | Undertorque Detection 2 (UL4) |
| 6 | 0020H | MEMOBUS/Modbus Test Mode Fault (SE) |
| 7 | 0022H | Motor Overheat (oH3) |
| 8 | 0027H | PID Feedback Loss (FbL) |
| 9 | 0028H | PID Feedback Loss (FbH) |
| 10 | 002AH | Drive Disabled (dnE) |
| 11 | 002BH | PG Disconnected (PGo) |
| 12 | 0031H | MECHATROLINK Watchdog Timer Error (E5) |
| 13 | 0032H | Station Address Setting Error (AEr) |
| 14 | 0033H | MECHATROLINK Comm. Cycle Setting Error (CyC) |
| 15 | 0034H | High Current Alarm (HCA) |
| 16 | 0039H | External Fault (input terminal S1) (EF1) |
| 17 | 003AH | External Fault (input terminal S2) (EF2) |
| 18 | 003BH | Safe Disable Input (HbbF) |
| 19 | 003CH | Safe Disable Input (Hbb) |
| 20 | 003DH | Mechanical Weakening Detection 1 (oL5) |
| 21 | 003EH | Mechanical Weakening Detection 2 (UL5) |
| 22 | 0049H | DriveWorksEZ Alarm (dWAL) |
Manual — Enter commands and H5-11 behavior — page 459
Source reference: SIEP C71060618F, December 2016, physical PDF page 459. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.11 Enter Command
When writing parameters to the drive from the PLC using MEMOBUS/Modbus communication it depends on the setting of parameter H5-11 if an Enter command must be used to enable these parameters or not. This sections explains Enter commands.
◆ Enter Command Types
The drive supports two types of Enter commands as shown in Table C.6. An Enter command is enabled by writing 0 to register number 0900H or 0910H. These registers can be written to only. An error will occur if the user attempts to read from these registers.
Table C.6 Enter Command Types
Register No. Description
Note: 1. Because the EEPROM can be written to a maximum of 100,000 times, refrain from writing to the EEPROM too often. The Enter command registers are write-only. Consequently, if these registers are read, then the register address will be invalid (Error code: 02H). An Enter command is not required if reference or broadcast data are sent to the drive. 2. Parameter data cannot be written to EEPROM during undervoltage, even using 0900H. 3. If undervoltage occurs when a making several parameter changes issued with a single ENTER command, the writing process may be aborted before all of the new changes have been written. Because all of the data has not yet been written, the EEPROM data error “CPF06” will be displayed the next time power to the drive is cycled. To prevent this problem, wait approximately 5 seconds after issuing the ENTER command before shutting off drive power.
◆ Enter Command Settings when Upgrading the Drive
When replacing earlier Yaskawa drive models with a V1000 and keeping the MEMOBUS/Modbus communications settings, parameter H5-11 needs to be set in accordance with how the Enter command functions in the older drive. H5-11 determines if an Enter command is needed to activate parameter changes in the drive. • Set H5-11 to 0 when upgrading from a G7 or F7 series drive to V1000 series drive. • Set H5-11 to 1 when upgrading from a V7 series drive to V1000 series drive.
■ H5-11 and the Enter Command
H5-11 Settings H5-11 = 0 H5-11 = 1
C
MEMOBUS/Modbus Communications
0900H | Writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM at the same time. Parameter changes remain even if the power supply is cycled.
0910H | Writes data in the RAM only. Parameter changes are lost when the drive is shut off.
Drive being replaced | G7, F7
How parameter settings are enabled | When the Enter command is received from the master.
Upper/lower limit check | Upper/lower limit check takes the settings of related parameters into account.
Default value of related parameters | Not affected. The settings of related parameters remain unchanged. They must be changed manually if needed.
Error handling when setting multiple parameters | Data is accepted even if one setting is invalid. The invalid setting will be discarded. No error message occurs.
C6 Enter command types — PDF page 459
| Source row | Register hex | Description |
|---|---|---|
| 1 | 0900H | Writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM at the same time. Parameter changes remain even if the power supply is cycled. |
| 2 | 0910H | Writes data in the RAM only. Parameter changes are lost when the drive is shut off. |
H5-11 Enter command behavior comparison — PDF page 459
| Source row | H5-11 behavior | H5-11=0 | H5-11=1 |
|---|---|---|---|
| 1 | Drive being replaced | G7, F7 | V7 |
| 2 | How parameter settings are enabled | When the Enter command is received from the master. | As soon as the value is changed. |
| 3 | Upper/lower limit check | Upper/lower limit check takes the settings of related parameters into account. | The upper/lower limit of the changed parameter is checked only. |
| 4 | Default value of related parameters | Not affected. The settings of related parameters remain unchanged. They must be changed manually if needed. | The default settings of related parameters are changed automatically. |
| 5 | Error handling when setting multiple parameters | Data is accepted even if one setting is invalid. The invalid setting will be discarded. No error message occurs. | Error occurs if only one setting is invalid. All data sent are discarded. |
Manual — Communication errors and no-response conditions — page 460
Source reference: SIEP C71060618F, December 2016, physical PDF page 460. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.12 Communication Errors
◆ MEMOBUS/Modbus Error Codes
A list of MEMOBUS/Modbus errors appears below. When an error occurs, remove whatever caused the error and restart communications.
Error Name Error Code
Cause
◆ Slave Not Responding
In the following situations, the slave drive will ignore the command message sent from the master, and not send a response message: • When a communications error (overrun, framing, parity or CRC-16) is detected in the command message. • When the slave address in the command message and the slave address in the drive do not match (remember to set the slave address for the drive using H5-01). • When the gap between two blocks (8 bit) of a message exceeds 24 bits. • When the command message data length is invalid.
Note: If the slave address specified in the command message is 00H, all slaves execute the write function, but do not return response messages to the master.
01H | Function Code Error
01H | • Attempted to set a function code from a PLC other than 03H, 08H, and 10H.
02H | Register Number Error
02H | • A register number specified in the command message does not exist. • Attempted to send a broadcast message using other register numbers than 0001H or 0002H.
03H | Bit Count Error
03H | • Read data or write data is greater than 16 bits. Invalid command message quantity. • In a write message, the “Number of Data Items” contained within the message does not equal twice the amount of data words (i.e., the total of Data 1+ Data 2, etc.).
21H | Data Setting Error
21H | • Control data or parameter write data is outside the allowable setting range. • Attempted to write a contradictory parameter setting.
22H | Write Mode Error
22H | • Attempted to write while the drive was operating to a parameter that cannot be written to during run. • During an EEPROM data error (CPF06), the master attempted to write to a parameter other than A1-00 to -05, E1-03, or o2-04. • Attempted to write to read-only data.
23H | DC Bus Undervoltage Write Error
23H | • Attempted to write from the master during an undervoltage fault (Uv1). • Attempted to execute and Enter command during Uv1.
24H | Write Error During Parameter Process
24H | • Master attempted writing to the drive while the drive was processing parameter data.
MEMOBUS/Modbus error codes and causes — PDF page 460
| Source row | Error code hex | Error name / cause |
|---|---|---|
| 1 | 01H | Function Code Error |
| 2 | 01H | • Attempted to set a function code from a PLC other than 03H, 08H, and 10H. |
| 3 | 02H | Register Number Error |
| 4 | 02H | • A register number specified in the command message does not exist. • Attempted to send a broadcast message using other register numbers than 0001H or 0002H. |
| 5 | 03H | Bit Count Error |
| 6 | 03H | • Read data or write data is greater than 16 bits. Invalid command message quantity. • In a write message, the “Number of Data Items” contained within the message does not equal twice the amount of data words (i.e., the total of Data 1+ Data 2, etc.). |
| 7 | 21H | Data Setting Error |
| 8 | 21H | • Control data or parameter write data is outside the allowable setting range. • Attempted to write a contradictory parameter setting. |
| 9 | 22H | Write Mode Error |
| 10 | 22H | • Attempted to write while the drive was operating to a parameter that cannot be written to during run. • During an EEPROM data error (CPF06), the master attempted to write to a parameter other than A1-00 to -05, E1-03, or o2-04. • Attempted to write to read-only data. |
| 11 | 23H | DC Bus Undervoltage Write Error |
| 12 | 23H | • Attempted to write from the master during an undervoltage fault (Uv1). • Attempted to execute and Enter command during Uv1. |
| 13 | 24H | Write Error During Parameter Process |
| 14 | 24H | • Master attempted writing to the drive while the drive was processing parameter data. |
Manual — Communication self-diagnostics and safety — page 461
Source reference: SIEP C71060618F, December 2016, physical PDF page 461. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
C.13 Self-Diagnostics
The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosis function, use the following procedure.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level. 1. Turn on the power to the drive. 2. Note the present terminal S6 function selection setting (H1-06) and set it for the communications test mode (H1-06 = 67). 3. Turn off the power to the drive. 4. With the power off, wire the drive as shown in the following figure:
Figure C.9 Terminal Connections for Communication Self-Diagnostics
- Check and note the setting of DIP switch S3. Set it to NPN if it is in the PNP position. 6. Turn the power to the drive back on. 7. During normal operation, the drive will display PASS. This indicates that the communications test mode is operating normally.
When a fault occurs, the drive will display “CE” on the keypad display. 8. Turn off the power supply. 9. Remove the wire jumpers from terminal R+, R-, S+, S- and, S6-SC and set back DIP switch S3 to its original position. Set terminal S6 to its original function. 10.Return to normal operation.
C
MEMOBUS/Modbus Communications
Figure C.9 enlarged terminal labels: R+, R−, S+, S−, IG; P1, P2, PC, A1, A2, +V, AC, AM, AC, MP; S1, S2, S3, S4, S5, S6, S7, HC, SC, H1, RP. Exact jumper paths and board geometry remain original-only. Follow complete numbered self-diagnostics procedure and safety; this text is not a wiring substitute.
Manual — Standards section safety — page 464
Source reference: SIEP C71060618F, December 2016, physical PDF page 464. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
D.1 Section Safety
DANGER
Electrical Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the drives and run the drives according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level. Do not allow unqualified personnel to perform work on the drive. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives. Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the drive. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury. Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the drive to metal or other noncombustible material. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes, 240 Vac maximum (200 V class) and 480 Vac maximum (400 V class) when protected by branch circuit protection devices specified in this manual.
Manual — Standards section notices — page 465
Source reference: SIEP C71060618F, December 2016, physical PDF page 465. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry. Never connect or disconnect the motor from the drive while the drive is outputting voltage. Improper equipment sequencing could result in damage to the drive. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive. Do not allow unqualified personnel to use the product. Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBPC72060000 when connecting a braking option to the drive. Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting other devices. Failure to comply could result in damage to the drive.
D.1 Section Safety
D
Standards Compliance
Manual — European standards and AC branch fuses — page 466
Source reference: SIEP C71060618F, December 2016, physical PDF page 466. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
D.2 European Standards
Figure D.1 CE Mark
The CE mark indicates compliance with European safety and environmental regulations and is required for engaging in business and commerce in Europe. European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics manufacturers and the EMC guidelines for controlling noise. This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive. • Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE standards. After setting up the device, verify that conditions meet European standards. • Low Voltage Directive: 73/23/EEC, 93/68/EEC
◆ CE Low Voltage Directive Compliance
This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage Directive. To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with other devices:
■ Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN 664.
■ Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in Table D.1.
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Table D.1 Factory Recommended Drive Branch Circuit Protection
Drive Model
Fuse Type
Manufacturer: Bussmann
Model Fuse Ampere Rating (A)
Figure D.1 CE mark. Graphic logo only; no inference of current certification validity.
Single-Phase 200 V Class | Single-Phase 200 V Class
BA0001 | FWH-25A14F
BA0002 | FWH-25A14F
BA0003 | FWH-60B
BA0006 | FWH-80B
BA0010 | FWH-100B
BA0012 | FWH-125B
BA0018 | FWH-175B
Three-Phase 200 V Class | Three-Phase 200 V Class
2A0001 | FWH-25A14F
2A0002 | FWH-25A14F
2A0004 | FWH-25A14F
2A0006 | FWH-25A14F
2A0010 | FWH-70B
2A0012 | FWH-70B
2A0020 | FWH-90B
2A0030 | FWH-100B
D1 Bussmann AC branch protection — 466 — PDF page 466
| Source row | Drive model or phase class | Bussmann fuse model | Fuse ampere rating (A) |
|---|---|---|---|
| 1 | Single-Phase 200 V Class | Single-Phase 200 V Class | Single-Phase 200 V Class |
| 2 | BA0001 | FWH-25A14F | 25 |
| 3 | BA0002 | FWH-25A14F | 25 |
| 4 | BA0003 | FWH-60B | 60 |
| 5 | BA0006 | FWH-80B | 80 |
| 6 | BA0010 | FWH-100B | 100 |
| 7 | BA0012 | FWH-125B | 125 |
| 8 | BA0018 | FWH-175B | 175 |
| 9 | Three-Phase 200 V Class | Three-Phase 200 V Class | Three-Phase 200 V Class |
| 10 | 2A0001 | FWH-25A14F | 25 |
| 11 | 2A0002 | FWH-25A14F | 25 |
| 12 | 2A0004 | FWH-25A14F | 25 |
| 13 | 2A0006 | FWH-25A14F | 25 |
| 14 | 2A0010 | FWH-70B | 70 |
| 15 | 2A0012 | FWH-70B | 70 |
| 16 | 2A0020 | FWH-90B | 90 |
| 17 | 2A0030 | FWH-100B | 100 |
Manual — AC fuses continuation and DC input conditions — page 467
Source reference: SIEP C71060618F, December 2016, physical PDF page 467. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive Model
Fuse Type
Manufacturer: Bussmann
Model Fuse Ampere Rating (A)
■ Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded systems, contact your dealer or Yaskawa for instructions.
■ CE Standards Compliance for DC Power Supply Input
Install the fuses in the following tables to meet CE standards.
Figure D.2 Example of DC Power Supply Input (Two Drives Connected in Series)
Note: 1. When connecting multiple drives together, make sure that each drive has its own fuse. Replace all fuses when one fuse blows. 2. Refer to on page 50 for an AC power supply. 3. The recommended fuses and fuse holders are made by Fuji Electric.
D.2 European Standards
D
Standards Compliance
Figure D.2 labels: DC power supply (converter); plus/minus; two Fuse labels; two Drive blocks with +1 and minus, outputs U/T1, V/T2, W/T3; two motors M. Source caption says Two Drives Connected in Series; exact circuit topology remains original-only and is not corrected or inferred.
2A0040 | FWH-200B
2A0056 | FWH-200B
2A0069 | FWH-200B
Three-Phase 400 V Class | Three-Phase 400 V Class
4A0001 | FWH-40B
4A0002 | FWH-40B
4A0004 | FWH-50B
4A0005 | FWH-70B
4A0007 | FWH-70B
4A0009 | FWH-90B
4A0011 | FWH-90B
4A0018 | FWH-80B
4A0023 | FWH-100B
4A0031 | FWH-125B
4A0038 | FWH-200B
D1 Bussmann AC branch protection — 467 — PDF page 467
| Source row | Drive model or phase class | Bussmann fuse model | Fuse ampere rating (A) |
|---|---|---|---|
| 1 | 2A0040 | FWH-200B | 200 |
| 2 | 2A0056 | FWH-200B | 200 |
| 3 | 2A0069 | FWH-200B | 200 |
| 4 | Three-Phase 400 V Class | Three-Phase 400 V Class | Three-Phase 400 V Class |
| 5 | 4A0001 | FWH-40B | 40 |
| 6 | 4A0002 | FWH-40B | 40 |
| 7 | 4A0004 | FWH-50B | 50 |
| 8 | 4A0005 | FWH-70B | 70 |
| 9 | 4A0007 | FWH-70B | 70 |
| 10 | 4A0009 | FWH-90B | 90 |
| 11 | 4A0011 | FWH-90B | 90 |
| 12 | 4A0018 | FWH-80B | 80 |
| 13 | 4A0023 | FWH-100B | 100 |
| 14 | 4A0031 | FWH-125B | 125 |
| 15 | 4A0038 | FWH-200B | 200 |
Manual — DC input fuses and holders — page 468
Source reference: SIEP C71060618F, December 2016, physical PDF page 468. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Table D.2 Single-Phase 200 V Class Fuses and Fuse Holders
Drive Model
DC Power Supply Input Fuse Fuse Holder Manufacturer: Fuji Electric
Type
Rated Short Circuit Braking Current (kA)
Qty. Type Qty.
Table D.3 Three-Phase 200 V Class Fuses and Fuse Holders
<1> Manufacturer does not recommend a specific fuse holder for this fuse. Contact Yaskawa or your nearest sales representative for fuse dimensions.
Table D.4 Three-Phase 400 V Class Fuses and Fuse Holders
D.2 European Standards
BA0001 | CR6L-20/UL
BA0002 | CR6L-30/UL
BA0003 | CR6L-50/UL
BA0006 | CR6L-75/UL
BA0010 | CR6L-100/UL
BA0012 | CR6L-100/UL
BA0018 | CR6L-150/UL
2A0001 | CR6L-20/UL
2A0002 | CR6L-20/UL
2A0004 | CR6L-20/UL
2A0006 | CR6L-30/UL
2A0010 | CR6L-50/UL
2A0012 | CR6L-50/UL
2A0020 | CR6L-75/UL
2A0030 | CR6L-100/UL
2A0040 | CR6L-150/UL
2A0056 | CR6L-150/UL
2A0069 | CR6L-200/UL
4A0001 | CR6L-20/UL
4A0002 | CR6L-20/UL
4A0004 | CR6L-50/UL
4A0005 | CR6L-50/UL
4A0007 | CR6L-50/UL
4A0009 | CR6L-50/UL
4A0011 | CR6L-50/UL
4A0018 | CR6L-50/UL
4A0023 | CR6L-75/UL
4A0031 | CR6L-100/UL
4A0038 | CR6L-150/UL
D2 Single-phase200V Fuji Electric DC-input fuses and holders — PDF page 468
| Source row | Drive model | Fuse type | Rated short circuit braking current (kA) | Fuse quantity | Fuse holder type | Fuse holder quantity |
|---|---|---|---|---|---|---|
| 1 | BA0001 | CR6L-20/UL | 100 | 2 | CMS-4 | 2 |
| 2 | BA0002 | CR6L-30/UL | 100 | 2 | CMS-4 | 2 |
| 3 | BA0003 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 4 | BA0006 | CR6L-75/UL | 100 | 2 | CMS-5 | 2 |
| 5 | BA0010 | CR6L-100/UL | 100 | 2 | CMS-5 | 2 |
| 6 | BA0012 | CR6L-100/UL | 100 | 2 | CMS-5 | 2 |
| 7 | BA0018 | CR6L-150/UL | 100 | 2 | CMS-5 | 2 |
D3 Three-phase200V Fuji Electric DC-input fuses and holders — PDF page 468
| Source row | Drive model | Fuse type | Rated short circuit braking current (kA) | Fuse quantity | Fuse holder type | Fuse holder quantity |
|---|---|---|---|---|---|---|
| 1 | 2A0001 | CR6L-20/UL | 100 | 2 | CMS-4 | 2 |
| 2 | 2A0002 | CR6L-20/UL | 100 | 2 | CMS-4 | 2 |
| 3 | 2A0004 | CR6L-20/UL | 100 | 2 | CMS-4 | 2 |
| 4 | 2A0006 | CR6L-30/UL | 100 | 2 | CMS-4 | 2 |
| 5 | 2A0010 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 6 | 2A0012 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 7 | 2A0020 | CR6L-75/UL | 100 | 2 | CMS–5 | 2 |
| 8 | 2A0030 | CR6L-100/UL | 100 | 2 | CMS–5 | 2 |
| 9 | 2A0040 | CR6L-150/UL | 100 | 2 | CMS–5 | 2 |
| 10 | 2A0056 | CR6L-150/UL | 100 | 2 | CMS–5 | 2 |
| 11 | 2A0069 | CR6L-200/UL | 100 | 2 | <1> | – |
D4 Three-phase400V Fuji Electric DC-input fuses and holders — PDF page 468
| Source row | Drive model | Fuse type | Rated short circuit braking current (kA) | Fuse quantity | Fuse holder type | Fuse holder quantity |
|---|---|---|---|---|---|---|
| 1 | 4A0001 | CR6L-20/UL | 100 | 2 | CMS-4 | 2 |
| 2 | 4A0002 | CR6L-20/UL | 100 | 2 | CMS-4 | 2 |
| 3 | 4A0004 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 4 | 4A0005 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 5 | 4A0007 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 6 | 4A0009 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 7 | 4A0011 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 8 | 4A0018 | CR6L-50/UL | 100 | 2 | CMS-4 | 2 |
| 9 | 4A0023 | CR6L-75/UL | 100 | 2 | CMS–5 | 2 |
| 10 | 4A0031 | CR6L-100/UL | 100 | 2 | CMS–5 | 2 |
| 11 | 4A0038 | CR6L-150/UL | 100 | 2 | CMS–5 | 2 |
Manual — EMC installation and grounding — page 469
Source reference: SIEP C71060618F, December 2016, physical PDF page 469. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Guarding Against Harmful Materials
When installing IP20/Open-Chassis enclosure drives, use an enclosure that prevents foreign material from entering the drive from above or below.
◆ EMC Guidelines Compliance
This drive is tested according to European standards EN 61800-3:2004/A1:2012 and it complies with the EMC guidelines.
■ EMC Filter Installation
The following conditions must be met to ensure continued compliance with guidelines. Refer to EMC Filters on page 471 for EMC filter selection.
Installation Method Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive also comply with EMC guidelines. 1. Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards. 2. Place the drive and EMC noise filter in the same enclosure. 3. Use braided shield cable for the drive and motor wiring or run the wiring through a metal conduit. 4. Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
A – Drive B – 20 m max cable length between drive and motor C – Motor
D – Metal conduit E – Ground wire should be as short as possible.
Figure D.3 Installation Method
- Ground the largest possible surface area of the shield to the metal conduit when using braided shield cable. Yaskawa recommends using a cable clamp.
A – Braided shield cable; B – Metal panel; C – Cable clamp (conductive)
Figure D.4 Ground Area
D.2 European Standards
D
Standards Compliance
Figure D.3 diagram labels A,B,C,D,E; U/T1,V/T2,W/T3 andU,V,W;M;groundsymbols. Geometry and wiring original-only. Explicit A–E legend captured separately.
Figure D.4 diagram labels A,B,C. Braided shield/cable clamp drawing original-only; explicit A–C legend captured separately.
Manual — Three-phase EMC illustration and legend — page 470
Source reference: SIEP C71060618F, December 2016, physical PDF page 470. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Three-Phase 200 V / 400 V Class
A – Ground the cable shield B – Enclosure panel C – Metal plate D – Grounding surface (remove any paint or sealant) E – Drive
F – Motor cable (braided shield cable, max. 20 m) G – Motor H – Cable clamp I – Wiring distance as short as possible J – EMC noise filter
Figure D.5 EMC Filter and Drive Installation for CE Compliance (Three-Phase 200 V / 400 V Class)
D.2 European Standards
Figure D.5 diagram labels L1,L2,L3,PE; A–J; E; L3,L2,L1; R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Three-phase200/400V source figure; miniature drive-face detail retained in raw source, no additional terminal association inferred. Exact wiring/ground/shieldgeometry original-only; A–J legend separate.
Manual — Single-phase EMC illustration and filter table — page 471
Source reference: SIEP C71060618F, December 2016, physical PDF page 471. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Single-Phase 200 V Class
A – Ground the cable shield B – Enclosure panel C – Metal plate D – Grounding surface (remove any paint or sealant) E – Drive
F – Motor cable (braided shield cable, max. 20 m) G – Motor H – Cable clamp I – Wiring distance as short as possible J – EMC noise filter
Figure D.6 EMC Filter and Drive Installation for CE Compliance (Single-Phase 200 V Class)
■ EMC Filters
The drive should be installed with the EMC filters listed below in order to comply with the EN 61800-3:2004/A1:2012, category C1 requirements.
Table D.5 EN 61800-3:2004/A1:2012 Category C1 Filters
Drive Model
Filter Data (Manufacturer: Schaffner)
Type
Rated Current (A)
Weight (lb)
Dimensions [W x L x H] (in)
Mounting Dimensions [Y x X] (in)
Drive Mounting Screw A
Drive Model; Type; Rated Current (A); Weight (lb); Dimensions [W x L x H] (in); Mounting Dimensions [Y x X] (in); Drive Mounting Screw A; Filter Mounting Screw
D.2 European Standards
D
Standards Compliance
Figure D.6 diagram labels N,L1,PE; A–J; E; N,L1; R/L1,S/L2,T/L3,U/T1,V/T2,W/T3. Single-phase200V source figure; miniature drive-face details retained in raw source. Exact wiring,ground andshieldgeometry original-only; A–J legend separately captured.
200 V Class Single-Phase | 200 V Class Single-Phase
BA0001 | FS23638-10-07
BA0002 | FS23638-10-07
BA0003 | FS23638-10-07
BA0006 | FS23638-20-07
BA0010 | FS23638-20-07
BA0012 | FS23638-30-07
BA0018 | FS23638-40-07
200 V Three-Phase | 200 V Three-Phase
2A0001 | FS23637-8-07
2A0002 | FS23637-8-07
2A0004 | FS23637-8-07
2A0006 | FS23637-8-07
D5 Schaffner EMC filters 471 — PDF page 471
| Source row | Drive model or phase class | Filter type | Rated current A | Weight lb | Dimensions W x L x H in | Mounting Y x X in | Drive mounting screw A | Filter mounting screw |
|---|---|---|---|---|---|---|---|---|
| 1 | 200 V Class Single-Phase | 200 V Class Single-Phase | 200 V Class Single-Phase | 200 V Class Single-Phase | 200 V Class Single-Phase | 200 V Class Single-Phase | 200 V Class Single-Phase | 200 V Class Single-Phase |
| 2 | BA0001 | FS23638-10-07 | 10 | 0.97 | 2.8 x 6.7 x 1.8 | 2.0 x 6.1 | M4 | M5 |
| 3 | BA0002 | FS23638-10-07 | 10 | 0.97 | 2.8 x 6.7 x 1.8 | 2.0 x 6.1 | M4 | M5 |
| 4 | BA0003 | FS23638-10-07 | 10 | 0.97 | 2.8 x 6.7 x 1.8 | 2.0 x 6.1 | M4 | M5 |
| 5 | BA0006 | FS23638-20-07 | 20 | 1.65 | 4.4 x 6.7 x 2.0 | 3.6 x 6.1 | M4 | M5 |
| 6 | BA0010 | FS23638-20-07 | 20 | 1.65 | 4.4 x 6.7 x 2.0 | 3.6 x 6.1 | M4 | M5 |
| 7 | BA0012 | FS23638-30-07 | 30 | 2.42 | 5.7 x 6.9 x 2.0 | 4.7 x 6.3 | M4 | M5 |
| 8 | BA0018 | FS23638-40-07 | 40 | 2.87 | 6.9 x 6.9 x 2.0 | 5.9 x 6.3 | M4 | M5 |
| 9 | 200 V Three-Phase | 200 V Three-Phase | 200 V Three-Phase | 200 V Three-Phase | 200 V Three-Phase | 200 V Three-Phase | 200 V Three-Phase | 200 V Three-Phase |
| 10 | 2A0001 | FS23637-8-07 | 7.3 | 0.88 | 2.8 x 6.7 x 1.6 | 2.0 x 6.1 | M4 | M5 |
| 11 | 2A0002 | FS23637-8-07 | 7.3 | 0.88 | 2.8 x 6.7 x 1.6 | 2.0 x 6.1 | M4 | M5 |
| 12 | 2A0004 | FS23637-8-07 | 7.3 | 0.88 | 2.8 x 6.7 x 1.6 | 2.0 x 6.1 | M4 | M5 |
| 13 | 2A0006 | FS23637-8-07 | 7.3 | 0.88 | 2.8 x 6.7 x 1.6 | 2.0 x 6.1 | M4 | M5 |
Manual — EMC filter continuation and category exceptions — page 472
Source reference: SIEP C71060618F, December 2016, physical PDF page 472. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive Model
Filter Data (Manufacturer: Schaffner)
Type
Rated Current (A)
Weight (lb)
Dimensions [W x L x H] (in)
Mounting Dimensions [Y x X] (in)
Drive Mounting Screw A
Drive Model; Type; Rated Current (A); Weight (lb); Dimensions [W x L x H] (in); Mounting Dimensions [Y x X] (in); Drive Mounting Screw A; Filter Mounting Screw
Note: EMC filters for models BA0018 and 2A0030 through 2A0069 are in compliance with EN 61800-3:2004/A1:2012, Category 2. All other models comply with Category 1.
Figure D.7 EMC Filter Dimensions
D.2 European Standards
Figure D.7 labels W,Y,L,X,H,A,PE,LINE,LOAD. W×L×H andY×X dimensions supplied in D5 tables; exact drawinggeometry,mounting positions andcable lengths not inferred.
2A0010 | FS23637-14-07
2A0012 | FS23637-14-07
2A0020 | FS23637-24-07
2A0030 | FS23637-52-07
2A0040 | FS23637-52-07
2A0056 | FS23637-68-07
2A0069 | FS23637-80-07
400 V Class Three-Phase | 400 V Class Three-Phase
4A0001 | FS23639-5-07
4A0002 | FS23639-5-07
4A0004 | FS23639-5-07
4A0005 | FS23639-10-07
4A0007 | FS23639-10-07
4A0009 | FS23639-10-07
4A0011 | FS23639-15-07
4A0018 | FS23639-30-07
4A0023 | FS23639-30-07
4A0031 | FS23639-50-07
4A0038 | FS23639-50-07
D5 Schaffner EMC filters 472 — PDF page 472
| Source row | Drive model or phase class | Filter type | Rated current A | Weight lb | Dimensions W x L x H in | Mounting Y x X in | Drive mounting screw A | Filter mounting screw |
|---|---|---|---|---|---|---|---|---|
| 1 | 2A0010 | FS23637-14-07 | 14 | 1.28 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 2 | 2A0012 | FS23637-14-07 | 14 | 1.28 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 3 | 2A0020 | FS23637-24-07 | 24 | 1.98 | 5.7 x 6.9 x 2.0 | 4.7 x 6.3 | M4 | M5 |
| 4 | 2A0030 | FS23637-52-07 | 52 | 4.41 | 5.4 x 12.0 x 2.2 | 3.9 x 11.4 | M5 | M5 |
| 5 | 2A0040 | FS23637-52-07 | 52 | 4.41 | 5.4 x 12.0 x 2.2 | 3.9 x 11.4 | M5 | M5 |
| 6 | 2A0056 | FS23637-68-07 | 68 | 5.73 | 6.9 x 13.4 x 2.6 | 5.1 x 12.8 | M5 | M6 |
| 7 | 2A0069 | FS23637-80-07 | 80 | 6.83 | 8.3 x 15.5 x 2.6 | 6.6 x 14.9 | M6 | M8 |
| 8 | 400 V Class Three-Phase | 400 V Class Three-Phase | 400 V Class Three-Phase | 400 V Class Three-Phase | 400 V Class Three-Phase | 400 V Class Three-Phase | 400 V Class Three-Phase | 400 V Class Three-Phase |
| 9 | 4A0001 | FS23639-5-07 | 5 | 1.10 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 10 | 4A0002 | FS23639-5-07 | 5 | 1.10 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 11 | 4A0004 | FS23639-5-07 | 5 | 1.10 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 12 | 4A0005 | FS23639-10-07 | 10 | 1.54 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 13 | 4A0007 | FS23639-10-07 | 10 | 1.54 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 14 | 4A0009 | FS23639-10-07 | 10 | 1.54 | 4.4 x 6.7 x 1.8 | 3.6 x 6.1 | M4 | M5 |
| 15 | 4A0011 | FS23639-15-07 | 15 | 1.98 | 5.7 x 6.9 x 2.0 | 4.7 x 6.3 | M4 | M5 |
| 16 | 4A0018 | FS23639-30-07 | 30 | 4.0 | 5.4 x 12.0 x 2.2 | 3.9 x 11.4 | M5 | M5 |
| 17 | 4A0023 | FS23639-30-07 | 30 | 4.0 | 5.4 x 12.0 x 2.2 | 3.9 x 11.4 | M5 | M5 |
| 18 | 4A0031 | FS23639-50-07 | 50 | 6.0 | 6.9 x 13.4 x 2.6 | 5.1 x 12.8 | M5 | M6 |
| 19 | 4A0038 | FS23639-50-07 | 50 | 6.0 | 6.9 x 13.4 x 2.6 | 5.1 x 12.8 | M5 | M6 |
Manual — DC link choke table — page 473
Source reference: SIEP C71060618F, December 2016, physical PDF page 473. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ DC Link Chokes for IEC/EN 61000-3-2 Compliance
DC Link Choke Drive Model Model Rating
Note: Models not listed in the above table do not require a DC link choke for EMC compliance.
D.2 European Standards
D
Standards Compliance
200V Three-Phase Units | 200V Three-Phase Units
2A0004 | UZDA-B
2A0006 | UZDA-B
400 V Three-Phase Units | 400 V Three-Phase Units
4A0002 | UZDA-B
4A0004 | UZDA-B
DC link chokes for IEC/EN61000-3-2 compliance — PDF page 473
| Source row | Drive model or phase class | Choke model | Rating |
|---|---|---|---|
| 1 | 200V Three-Phase Units | 200V Three-Phase Units | 200V Three-Phase Units |
| 2 | 2A0004 | UZDA-B | 5.4 A 8 mH |
| 3 | 2A0006 | UZDA-B | 5.4 A 8 mH |
| 4 | 400 V Three-Phase Units | 400 V Three-Phase Units | 400 V Three-Phase Units |
| 5 | 4A0002 | UZDA-B | 3.2 A 28 mH |
| 6 | 4A0004 | UZDA-B | 3.2 A 28 mH |
Manual — UL conditions and wire gauge table — page 474
Source reference: SIEP C71060618F, December 2016, physical PDF page 474. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
D.3 UL and CSA Standards
◆ UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada and indicates that UL has performed product testing and evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL certification, all components inside that product must also receive UL certification.
Figure D.8 UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The following conditions must be met to maintain compliance when using this drive in combination with other equipment:
■ Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
■ Ambient Temperature
IP20/NEMA 1, UL Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F) IP20/IP00 Open-Chassis enclosure: -10 °C to +50 °C (14 °F to 122 °F) Finless Type: IP20/IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F) NEMA 4X, UL Type 4X/IP66 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
■ Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL Listed closed-loop crimp terminals when wiring the drive main circuit terminals. Use only the tools recommended by the terminal manufacturer for crimping. The wire gauges listed in Table D.6, Table D.7, and Table D.8 are Yaskawa recommendations. Refer to local codes for proper wire gauge selections.
Table D.6 Wire Gauge and Torque Specifications
Drive Model; Terminal
Recomm. Gauge AWG, kcmil
Wire Range AWG, kcmil
Screw Size
Tightening Torque N•m (lb.in.)
Figure D.8 UL/cUL mark; c UL US LISTED. Historical graphic logo,not currentcertificate validation.
BA0001 BA0002 BA0003 | R/L1, S/L2, T/L3
BA0001 BA0002 BA0003 | U/T1, V/T2, W/T3
BA0001 BA0002 BA0003 | ⊖, ⊕1, ⊕2
BA0001 BA0002 BA0003 | B1, B2
BA0001 BA0002 BA0003 | ⏚ (ground symbol)
BA0006 | R/L1, S/L2, T/L3
BA0006 | U/T1, V/T2, W/T3
BA0006 | ⊖, ⊕1, ⊕2
BA0006 | B1, B2
BA0006 | ⏚ (ground symbol)
BA0010 | R/L1, S/L2, T/L3
BA0010 | U/T1, V/T2, W/T3
BA0010 | ⊖, ⊕1, ⊕2
BA0010 | B1, B2
BA0010 | ⏚ (ground symbol)
D6 single-phase wire gauge and torque — PDF page 474
| Source row | Drive model | Terminal | Recommended gauge AWG/kcmil | Wire range AWG/kcmil | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | BA0001 BA0002 BA0003 | R/L1, S/L2, T/L3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 2 | BA0001 BA0002 BA0003 | U/T1, V/T2, W/T3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 3 | BA0001 BA0002 BA0003 | ⊖, ⊕1, ⊕2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 4 | BA0001 BA0002 BA0003 | B1, B2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 5 | BA0001 BA0002 BA0003 | ⏚ (ground symbol) | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 6 | BA0006 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 7 | BA0006 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 8 | BA0006 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 9 | BA0006 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 10 | BA0006 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 11 | BA0010 | R/L1, S/L2, T/L3 | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 12 | BA0010 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 13 | BA0010 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 14 | BA0010 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 15 | BA0010 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
Manual — Wire gauge and torque continuation — page 475
Source reference: SIEP C71060618F, December 2016, physical PDF page 475. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive Model; Terminal
Recomm. Gauge AWG, kcmil
Wire Range AWG, kcmil
Screw Size
Tightening Torque N•m (lb.in.)
Table D.7 Wire Gauge and Torque Specifications
D.3 UL and CSA Standards
D
Standards Compliance
BA0012 | R/L1, S/L2, T/L3
BA0012 | U/T1, V/T2, W/T3
BA0012 | ⊖, ⊕1, ⊕2
BA0012 | B1, B2
BA0012 | ⏚ (ground symbol)
BA0018 | R/L1, S/L2, T/L3
BA0018 | U/T1, V/T2, W/T3
BA0018 | ⊖, ⊕1, ⊕2
BA0018 | B1, B2
BA0018 | ⏚ (ground symbol)
2A0001 2A0002 2A0004 2A0006 | R/L1, S/L2, T/L3
2A0001 2A0002 2A0004 2A0006 | U/T1, V/T2, W/T3
2A0001 2A0002 2A0004 2A0006 | ⊖, ⊕1, ⊕2
2A0001 2A0002 2A0004 2A0006 | B1, B2
2A0001 2A0002 2A0004 2A0006 | ⏚ (ground symbol)
2A0010 | R/L1, S/L2, T/L3
2A0010 | U/T1, V/T2, W/T3
2A0010 | ⊖, ⊕1, ⊕2
2A0010 | B1, B2
2A0010 | ⏚ (ground symbol)
2A0012 | R/L1, S/L2, T/L3
2A0012 | U/T1, V/T2, W/T3
2A0012 | ⊖, ⊕1, ⊕2
2A0012 | B1, B2
2A0012 | ⏚ (ground symbol)
2A0020 | R/L1, S/L2, T/L3
2A0020 | U/T1, V/T2, W/T3
2A0020 | ⊖, ⊕1, ⊕2
2A0020 | B1, B2
2A0020 | ⏚ (ground symbol)
2A0030 | R/L1, S/L2, T/L3
2A0030 | U/T1, V/T2, W/T3
2A0030 | ⊖, ⊕1, ⊕2
2A0030 | B1, B2
2A0030 | ⏚ (ground symbol)
2A0040 | R/L1, S/L2, T/L3
2A0040 | U/T1, V/T2, W/T3
2A0040 | –, +1, +2
2A0040 | B1, B2
2A0040 | ⏚ (ground symbol)
D6 single-phase wire gauge and torque — PDF page 475
| Source row | Drive model | Terminal | Recommended gauge AWG/kcmil | Wire range AWG/kcmil | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | BA0012 | R/L1, S/L2, T/L3 | 10 | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 2 | BA0012 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 3 | BA0012 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 4 | BA0012 | B1, B2 | – | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 5 | BA0012 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 2.3 to 2.5 (20.4 to 22.1) |
| 6 | BA0018 | R/L1, S/L2, T/L3 | 8 | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 7 | BA0018 | U/T1, V/T2, W/T3 | 10 | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 8 | BA0018 | ⊖, ⊕1, ⊕2 | – | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 9 | BA0018 | B1, B2 | – | 12 to 8 | M5 | 2.3 to 2.5 (20.4 to 22.1) |
| 10 | BA0018 | ⏚ (ground symbol) | 8 | 12 to 8 | M5 | 2 to 2.5 (17.7 to 22.1) |
D7 three-phase200V wire gauge and torque — PDF page 475
| Source row | Drive model | Terminal | Recommended gauge AWG/kcmil | Wire range AWG/kcmil | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 2A0001 2A0002 2A0004 2A0006 | R/L1, S/L2, T/L3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 2 | 2A0001 2A0002 2A0004 2A0006 | U/T1, V/T2, W/T3 | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 3 | 2A0001 2A0002 2A0004 2A0006 | ⊖, ⊕1, ⊕2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 4 | 2A0001 2A0002 2A0004 2A0006 | B1, B2 | – | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 5 | 2A0001 2A0002 2A0004 2A0006 | ⏚ (ground symbol) | 14 | 18 to 14 | M3.5 | 0.8 to 1.0 (7.1 to 8.9) |
| 6 | 2A0010 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 7 | 2A0010 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 8 | 2A0010 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 9 | 2A0010 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 10 | 2A0010 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 11 | 2A0012 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 12 | 2A0012 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 13 | 2A0012 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 14 | 2A0012 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 15 | 2A0012 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 16 | 2A0020 | R/L1, S/L2, T/L3 | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 17 | 2A0020 | U/T1, V/T2, W/T3 | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 18 | 2A0020 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 19 | 2A0020 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 20 | 2A0020 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 21 | 2A0030 | R/L1, S/L2, T/L3 | 8 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 22 | 2A0030 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 23 | 2A0030 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 24 | 2A0030 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 25 | 2A0030 | ⏚ (ground symbol) | 8 <1> | 10 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
| 26 | 2A0040 | R/L1, S/L2, T/L3 | 6 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 27 | 2A0040 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 28 | 2A0040 | –, +1, +2 | – | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 29 | 2A0040 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 30 | 2A0040 | ⏚ (ground symbol) | 6 | 10 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
Manual — Wire gauges and torque D7–D8 — page 476
Source reference: SIEP C71060618F, December 2016, physical PDF page 476. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive Model; Terminal
Recomm. Gauge AWG, kcmil
Wire Range AWG, kcmil
Screw Size
Tightening Torque N•m (lb.in.)
<1> When an EMC filter is installed, additional measures must be taken to comply with IEC/EN 61800-5-1. Refer to EMC Filter Installation on page 469 for details.
Table D.8 Wire Gauge and Torque Specifications
D.3 UL and CSA Standards
2A0056 | R/L1, S/L2, T/L3
2A0056 | U/T1, V/T2, W/T3
2A0056 | ⊖, ⊕1, ⊕2
2A0056 | B1, B2
2A0056 | ⏚ (ground symbol)
2A0069 | R/L1, S/L2, T/L3
2A0069 | U/T1, V/T2, W/T3
2A0069 | ⊖, ⊕1, ⊕2
2A0069 | B1, B2
2A0069 | ⏚ (ground symbol)
4A0001 4A0002 4A0004 | R/L1, S/L2, T/L3
4A0001 4A0002 4A0004 | U/T1, V/T2, W/T3
4A0001 4A0002 4A0004 | ⊖, ⊕1, ⊕2
4A0001 4A0002 4A0004 | B1, B2
4A0001 4A0002 4A0004 | ⏚ (ground symbol)
4A0005 4A0007 4A0009 | R/L1, S/L2, T/L3
4A0005 4A0007 4A0009 | U/T1, V/T2, W/T3
4A0005 4A0007 4A0009 | ⊖, ⊕1, ⊕2
4A0005 4A0007 4A0009 | B1, B2
4A0005 4A0007 4A0009 | ⏚ (ground symbol)
4A0011 | R/L1, S/L2, T/L3
4A0011 | U/T1, V/T2, W/T3
4A0011 | ⊖, ⊕1, ⊕2
4A0011 | B1, B2
4A0011 | ⏚ (ground symbol)
4A0018 | R/L1, S/L2, T/L3
4A0018 | U/T1, V/T2, W/T3
4A0018 | ⊖, ⊕1, ⊕2
4A0018 | B1, B2
4A0018 | ⏚ (ground symbol)
4A0023 | R/L1, S/L2, T/L3
4A0023 | U/T1, V/T2, W/T3
4A0023 | ⊖, ⊕1, ⊕2
4A0023 | B1, B2
4A0023 | ⏚ (ground symbol)
D7 three-phase200V wire gauge and torque — PDF page 476
| Source row | Drive model | Terminal | Recommended gauge AWG/kcmil | Wire range AWG/kcmil | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 2A0056 | R/L1, S/L2, T/L3 | 4 | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 2 | 2A0056 | U/T1, V/T2, W/T3 | 4 | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 3 | 2A0056 | ⊖, ⊕1, ⊕2 | – | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 4 | 2A0056 | B1, B2 | – | 10 to 6 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 5 | 2A0056 | ⏚ (ground symbol) | 6 | 8 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 6 | 2A0069 | R/L1, S/L2, T/L3 | 3 | 8 to 2 | M8 | 9.9 to 11 (87.6 to 97.4) |
| 7 | 2A0069 | U/T1, V/T2, W/T3 | 3 | 8 to 2 | M8 | 9.9 to 11 (87.6 to 97.4) |
| 8 | 2A0069 | ⊖, ⊕1, ⊕2 | – | 8 to 2 | M8 | 9.9 to 11 (87.6 to 97.4) |
| 9 | 2A0069 | B1, B2 | – | 8 to 6 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 10 | 2A0069 | ⏚ (ground symbol) | 6 | 6 to 4 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
D8 three-phase400V wire gauge and torque — PDF page 476
| Source row | Drive model | Terminal | Recommended gauge AWG/kcmil | Wire range AWG/kcmil | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 4A0001 4A0002 4A0004 | R/L1, S/L2, T/L3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 2 | 4A0001 4A0002 4A0004 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 3 | 4A0001 4A0002 4A0004 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 4 | 4A0001 4A0002 4A0004 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 5 | 4A0001 4A0002 4A0004 | ⏚ (ground symbol) | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 6 | 4A0005 4A0007 4A0009 | R/L1, S/L2, T/L3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 7 | 4A0005 4A0007 4A0009 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 8 | 4A0005 4A0007 4A0009 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 9 | 4A0005 4A0007 4A0009 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 10 | 4A0005 4A0007 4A0009 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 11 | 4A0011 | R/L1, S/L2, T/L3 | 12 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 12 | 4A0011 | U/T1, V/T2, W/T3 | 14 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 13 | 4A0011 | ⊖, ⊕1, ⊕2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 14 | 4A0011 | B1, B2 | – | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 15 | 4A0011 | ⏚ (ground symbol) | 10 | 14 to 10 | M4 | 1.2 to 1.5 (10.6 to 13.3) |
| 16 | 4A0018 | R/L1, S/L2, T/L3 | 10 | 14 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 17 | 4A0018 | U/T1, V/T2, W/T3 | 10 | 14 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 18 | 4A0018 | ⊖, ⊕1, ⊕2 | – | 14 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 19 | 4A0018 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 20 | 4A0018 | ⏚ (ground symbol) | 8 | 14 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
| 21 | 4A0023 | R/L1, S/L2, T/L3 | 10 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 22 | 4A0023 | U/T1, V/T2, W/T3 | 10 | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 23 | 4A0023 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 24 | 4A0023 | B1, B2 | – | 14 to 10 | M4 | 2.1 to 2.3 (18.6 to 20.4) |
| 25 | 4A0023 | ⏚ (ground symbol) | 8 | 10 to 6 | M5 | 2 to 2.5 (17.7 to 22.1) |
Manual — D8 continuation, crimp terminals and voltage drop — page 477
Source reference: SIEP C71060618F, December 2016, physical PDF page 477. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
Drive Model; Terminal
Recomm. Gauge AWG, kcmil
Wire Range AWG, kcmil
Screw Size
Tightening Torque N•m (lb.in.)
<1> When an EMC filter is installed, additional measures must be taken to comply with IEC/EN 61800-5-1. Refer to EMC Filter Installation on page 469 for details.
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable temperature of 75 °C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 30 °C. Closed-Loop Crimp Terminal Recommendations Yaskawa recommends crimp terminals made by JST and Tokyo DIP for the insulation cap. Table D.9 matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department. The closed-loop crimp terminal sizes and values listed in Table D.9 are Yaskawa recommendations. Refer to local codes for proper selections.
Table D.9 Closed-Loop Crimp Terminal Sizes
Wire Gauge Terminal Screws
Crimp Terminal Model Number
Tool Insulation Cap Die Jaw Model No.
Cap Code <1> Machine No. Die Jaw Model No.
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection. Example: Models with 14 AWG for both input and output require one set for input terminals and one set for output terminals, so the user should order two sets of [100-066-218].
Note: Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater than 2% of motor
D.3 UL and CSA Standards
D
Standards Compliance
Source formula: Line drop voltage (V) = √3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10⁻³. Increase wire gauge when voltage drop exceeds2% of motor rated voltage; no calculation performed. Formula reconstructed from visible root, multiplication and exponent, raw retained.
4A0031 | R/L1, S/L2, T/L3
4A0031 | U/T1, V/T2, W/T3
4A0031 | ⊖, ⊕1, ⊕2
4A0031 | B1, B2
4A0031 | ⏚ (ground symbol)
4A0038 | R/L1, S/L2, T/L3
4A0038 | U/T1, V/T2, W/T3
4A0038 | ⊖, ⊕1, ⊕2
4A0038 | B1, B2
4A0038 | ⏚ (ground symbol)
18 AWG | M3.5
16 AWG | M3.5
14 AWG | M3.5
14 AWG | M4
12 / 10 AWG | M4
12 / 10 AWG | M5
8 AWG | M4
8 AWG | M5
8 AWG | M8
6 AWG | M4
6 AWG | M5
6 AWG | M6
6 AWG | M8
4 AWG | M6
4 AWG | M8
3 AWG | M8
2 AWG | M8
D8 three-phase400V wire gauge and torque — PDF page 477
| Source row | Drive model | Terminal | Recommended gauge AWG/kcmil | Wire range AWG/kcmil | Screw size | Tightening torque N·m (lb.in.) |
|---|---|---|---|---|---|---|
| 1 | 4A0031 | R/L1, S/L2, T/L3 | 8 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 2 | 4A0031 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 3 | 4A0031 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 4 | 4A0031 | B1, B2 | – | 14 to 10 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 5 | 4A0031 | ⏚ (ground symbol) | 6 <1> | 10 to 6 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
| 6 | 4A0038 | R/L1, S/L2, T/L3 | 6 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 7 | 4A0038 | U/T1, V/T2, W/T3 | 8 | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 8 | 4A0038 | ⊖, ⊕1, ⊕2 | – | 10 to 6 | M5 | 3.6 to 4.0 (31.8 to 35.4) |
| 9 | 4A0038 | B1, B2 | – | 10 to 8 | M5 | 2.7 to 3.0 (23.9 to 26.6) |
| 10 | 4A0038 | ⏚ (ground symbol) | 6 | 10 to 6 | M6 | 5.4 to 6.0 (47.8 to 53.1) |
D9 closed-loop crimp terminal sizes — PDF page 477
| Source row | Wire gauge | Terminal screw | Crimp terminal model | Tool machine number | Tool die jaw | Insulation cap model | Order code footnote1 |
|---|---|---|---|---|---|---|---|
| 1 | 18 AWG | M3.5 | R1.25-3.5 | YA-4 | AD-900 | TP-003 | 100-066-217 |
| 2 | 16 AWG | M3.5 | R1.25-3.5 | YA-4 | AD-900 | TP-003 | 100-066-217 |
| 3 | 14 AWG | M3.5 | R2-3.5 | YA-4 | AD-900 | TP-003 | 100-066-218 |
| 4 | 14 AWG | M4 | R2-4 | YA-4 | AD-900 | TP-003 | 100-054-028 |
| 5 | 12 / 10 AWG | M4 | R5.5-4 | YA-4 | AD-900 | TP-005 | 100-054-029 |
| 6 | 12 / 10 AWG | M5 | R5.5-5 | YA-4 | AD-900 | TP-005 | 100-054-030 |
| 7 | 8 AWG | M4 | 8-4 | YA-4 | AD-901 | TP-008 | 100-054-031 |
| 8 | 8 AWG | M5 | R8-5 | YA-4 | AD-901 | TP-008 | 100-054-032 |
| 9 | 8 AWG | M8 | R8-8 | YA-4 | AD-901 | TP-008 | 100-061-111 |
| 10 | 6 AWG | M4 | 14-4 | YA-4 | AD-902 | TP-014 | 100-66-220 |
| 11 | 6 AWG | M5 | R14-5 | YA-4 | AD-902 | TP-014 | 100-054-034 |
| 12 | 6 AWG | M6 | R14-6 | YA-5 | AD-952 | TP-014 | 100-051-261 |
| 13 | 6 AWG | M8 | R14-8 | YA-5 | AD-952 | TP-014 | 100-054-035 |
| 14 | 4 AWG | M6 | R22-6 | YA-5 | AD-953 | TP-022 | 100-051-262 |
| 15 | 4 AWG | M8 | R22-8 | YA-5 | AD-953 | TP-022 | 100-051-263 |
| 16 | 3 AWG | M8 | R38-8 | YA-5 | AD-954 | TP-038 | 100-051-264 |
| 17 | 2 AWG | M8 | R38-8 | YA-5 | AD-954 | TP-038 | 100-051-264 |
Manual — Recommended circuit protection D10 — page 478
Source reference: SIEP C71060618F, December 2016, physical PDF page 478. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
■ Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C. Semiconductor protective type fuses are preferred. Branch circuit protection shall be provided by any of the following according to Table D.10. • Non-time Delay Class J, T, or CC fuses. • Time Delay Class J, T, CC, or RK5 fuses. • Semiconductor fuses. • Molded Case Circuit Breakers (MCCB).
Table D.10 Factory Recommended Drive Branch Circuit Protection
Drive Model
Non-time Delay Fuse Rating (A)
<1>
Time Delay Fuses Bussmann T, or CC Class RK5 Semiconductor Fuse Part Number Rating (A) Fuse Rating (A) <2> <3> (Fuse Ampere) <4>
MCCB <5>
Class J, T, or CC Fuse Rating (A)
<2>
Class RK5 Fuse Rating (A)
<3>
Rating (A)
Minimum Enclosure Volume (in3)
<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 2A0002, 2A0004, 4A0004, 4A0005, and 4A0007. <2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse. <3> Maximum 225% of drive input current rating for any Class RK5 fuse. <4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
D.3 UL and CSA Standards
200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives
BA0001 | 6
BA0002 | 10
BA0003 | 20
BA0006 | 40
BA0010 | 40
BA0012 | 50
BA0018 | 80
200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives
2A0001 | 3
2A0002 | 6 <6>
2A0004 | 15 <7>
2A0006 | 20
2A0010 | 25
2A0012 | 25
2A0020 | 40
2A0030 | –
2A0040 | –
2A0056 | –
2A0069 | –
400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives
4A0001 | 3
4A0002 | 6
4A0004 | 15 <7>
4A0005 | 20 <8>
4A0007 | 25 <9>
4A0009 | 25
4A0011 | 30
4A0018 | –
4A0023 | –
4A0031 | –
4A0038 | –
D10 factory-recommended branch protection — PDF page 478
| Source row | Drive model or phase class | Non-time-delay fuse A foot1 | Time-delay ClassJ/T/CC A foot2 | Time-delay ClassRK5 A foot3 | Bussmann semiconductor fuse model andA foot4 | MCCB A foot5 | Minimum enclosure volume in³ foot5 |
|---|---|---|---|---|---|---|---|
| 1 | 200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives | 200 V Class Single-Phase Drives |
| 2 | BA0001 | 6 | 3.5 | 4 | FWH-25A14F (25) | 15 | 600 |
| 3 | BA0002 | 10 | 6 | 8 | FWH-25A14F (25) | 15 | 600 |
| 4 | BA0003 | 20 | 10 | 15 | FWH-60B (60) | 15 | 600 |
| 5 | BA0006 | 40 | 20 | 30 | FWH-80B (80) | 30 | 1152 |
| 6 | BA0010 | 40 | 35 | 45 | FWH-100B (100) | 50 | 1152 |
| 7 | BA0012 | 50 | 40 | 50 | FWH-125B (125) | 60 | 1152 |
| 8 | BA0018 | 80 | 60 | 70 | FWH-175B (175) | 80 | 1152 |
| 9 | 200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives | 200 V Class Three-Phase Drives |
| 10 | 2A0001 | 3 | 1.5 | 2 | FWH-25A14F (25) | 15 | 600 |
| 11 | 2A0002 | 6 <6> | 3 | 3 | FWH-25A14F (25) | 15 | 600 |
| 12 | 2A0004 | 15 <7> | 6 | 8 | FWH-25A14F (25) | 15 | 600 |
| 13 | 2A0006 | 20 | 10 | 15 | FWH-25A14F (25) | 15 | 1152 |
| 14 | 2A0010 | 25 | 15 | 20 | FWH-70B (70) | 25 | 1152 |
| 15 | 2A0012 | 25 | 20 | 30 | FWH-70B (70) | 30 | 1152 |
| 16 | 2A0020 | 40 | 40 | 50 | FWH-90B (90) | 60 | 1152 |
| 17 | 2A0030 | – | 60 | 80 | FWH-100B (100) | 90 | 1152 |
| 18 | 2A0040 | – | 90 | 110 | FWH-200B (200) | 125 | 1152 |
| 19 | 2A0056 | – | 110 | 150 | FWH-200B (200) | 150 | 2560 |
| 20 | 2A0069 | – | 125 | 175 | FWH-200B (200) | 200 | 2560 |
| 21 | 400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives | 400 V Class Three-Phase Drives |
| 22 | 4A0001 | 3 | 2 | 2 | FWH-40B (40) | 15 | 1152 |
| 23 | 4A0002 | 6 | 3.5 | 3 | FWH-40B (40) | 15 | 1152 |
| 24 | 4A0004 | 15 <7> | 7 | 8 | FWH-50B (50) | 15 | 1152 |
| 25 | 4A0005 | 20 <8> | 10 | 10 | FWH-70B (70) | 15 | 1152 |
| 26 | 4A0007 | 25 <9> | 12 | 15 | FWH-70B (70) | 20 | 1152 |
| 27 | 4A0009 | 25 | 15 | 20 | FWH-90B (90) | 20 | 1152 |
| 28 | 4A0011 | 30 | 20 | 30 | FWH-90B (90) | 35 | 1152 |
| 29 | 4A0018 | – | 35 | 45 | FWH-80B (80) | 50 | 1152 |
| 30 | 4A0023 | – | 40 | 50 | FWH-100B (100) | 60 | 1152 |
| 31 | 4A0031 | – | 60 | 80 | FWH-125B (125) | 90 | 1152 |
| 32 | 4A0038 | – | 70 | 90 | FWH-200B (200) | 110 | 1152 |
Manual — Fuse footnotes, control wiring, CSA and overload — page 479
Source reference: SIEP C71060618F, December 2016, physical PDF page 479. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater. Additionally, when using MCCBs for protection, the drive must be installed in a ventilated enclosure with minimum volume according the “Minimum Enclosure Volume” column. <6> Model 2A0002 requires Mersen (Ferraz) part number A6T6 for compliance. <7> Models 2A0004 and 4A0004 require Mersen (Ferraz) part number A6T15 for compliance. <8> Model 4A0005 requires Mersen (Ferraz) part number A6T20 for compliance. <9> Model 4A0007 requires Mersen (Ferraz) part number A6T25 for compliance.
■ Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external power supply shall be a UL-Listed Class 2 power source or equivalent.
Table D.11 Control Circuit Terminal Power Supply
Input / Output Terminal Signal Power Supply Specifications
■ Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise above 31,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives. • The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the power supply being used. • Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes for 240 V in 200 V class drives (up to 480 V for 400 V class drives) motor overload protection.
◆ CSA Standards Compliance
Figure D.9 CSA Mark
■ CSA for Industrial Control Equipment
The drive is CSA-certified as Industrial Control Equipment Class 3211. Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.
◆ Drive Motor Overload Protection
Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload protection is UL listed and in accordance with the NEC and CEC.
■ E2-01: Motor Rated Current
Setting Range: Model Dependent Default Setting: Model Dependent Parameter E2-01 (motor rated current) protects the motor if parameter L1-01 is not set to 0 (default is 1, standard induction motor protection enabled).
D.3 UL and CSA Standards
D
Standards Compliance
Figure D.9 CSA mark and registration symbol. Historical logo only; no current certification validity inferred.
Multi-function photocoupler output | P1, P2, PC
Multi-function digital inputs | S1, S2, S3, S4, S5, S6, S7, SC
Multi-function analog inputs | A1, A2, AC
Pulse train input | RP
Pulse train output | MP
D11 control circuit terminal power supply — PDF page 479
| Source row | Input/output | Terminal signal | Power supply specification |
|---|---|---|---|
| 1 | Multi-function photocoupler output | P1, P2, PC | Requires class 2 power supply |
| 2 | Multi-function digital inputs | S1, S2, S3, S4, S5, S6, S7, SC | Use the internal power supply of the drive. Use class 2 for external power supply. |
| 3 | Multi-function analog inputs | A1, A2, AC | Use the internal power supply of the drive. Use class 2 for external power supply. |
| 4 | Pulse train input | RP | Use the internal LVLC power supply of the drive. Use class 2 for external power supply. |
| 5 | Pulse train output | MP | Use the internal LVLC power supply of the drive. Use class 2 for external power supply. |
Manual — Motor overload selection and timing — page 480
Source reference: SIEP C71060618F, December 2016, physical PDF page 480. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
If Auto-Tuning has been performed successfully, the motor data that was entered in T1-04 is automatically written into parameter E2-01. If Auto-Tuning has not been performed, manually enter the correct motor rated current in parameter E2-01.
■ L1-01: Motor Overload Protection Selection
The drive has an electronic overload protection function (oL1) based on time, output current and output frequency, which protects the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external thermal overload relay for single motor operation. This parameter selects the motor overload curve used according to the type of motor applied.
Table D.12 Overload Protection Settings
Setting Description
Disable the electronic overload protection (L1-01 = 0: Disabled) and wire each motor with its own motor thermal overload when connecting the drive to more than one motor for simultaneous operation. Enable the motor overload protection (L1-01 = “1”, “2”, or “3”) when connecting the drive to a single motor unless there is another means of preventing motor thermal overload. The electronic thermal overload function causes an oL1 fault, which shuts off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated as long as the drive is powered up. Setting L1-01 = 1 selects a motor with limited cooling capability below rated (base) speed when running at 100% load. The oL1 function derates the motor when it is running below base speed. Setting L1-01 = 2 selects a motor capable of cooling itself over a 10:1 speed range when running at 100% load. The oL1 function derates the motor when it is running at 1/10 or less of its rated speed. Setting L1-01 = 3 selects a motor capable of cooling itself at any speed — including zero speed — when running at 100% load. The oL1 function does not derate the motor at any speed. Setting L1-01 = 4 selects protection for a PM motor with variable torque.
■ L1-02: Motor Overload Protection Time
Setting Range: 0.1 to 5.0 Minutes Factory Default: 1.0 Minutes The L1-02 parameter sets the allowed operation time before the oL1 fault occurs when the drive is running at 60 Hz and 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the set of oL1 curves up the Y-axis of the diagram below but will not change the shape of the curves.
Figure D.10 Motor Overload Protection Time
D.3 UL and CSA Standards
Figure D.10: Operation time (minutes), ticks0.1,0.4,1,3,7,10; Motor current (%), ticks0,100,150,200; E2-01=100% motor current. Cold start: characteristics when an overload occurs at a complete stop. Hot start: characteristics when an overload occurs during continuous operation at100%. Curves, shaded region and points retained only in original figure, no interpolated trip times.
0 | Disabled
1 | Standard Fan-Cooled Motor (Default)
2 | Drive Duty Motor with a Speed Range of 1:10
3 | Vector Motor with a Speed Range of 1:100
4 | Permanent Magnet Motor with Variable Torque
6 | Standard Fan-Cooled Motor (50 Hz)
D12 L1-01 motor overload protection choices — PDF page 480
| Source row | Setting | Description |
|---|---|---|
| 1 | 0 | Disabled |
| 2 | 1 | Standard Fan-Cooled Motor (Default) |
| 3 | 2 | Drive Duty Motor with a Speed Range of 1:10 |
| 4 | 3 | Vector Motor with a Speed Range of 1:100 |
| 5 | 4 | Permanent Magnet Motor with Variable Torque |
| 6 | 6 | Standard Fan-Cooled Motor (50 Hz) |
Manual — Safe Disable standards and specifications — page 481
Source reference: SIEP C71060618F, December 2016, physical PDF page 481. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
D.4 Safe Disable Input
Figure D.11 TUV Mark
The TUV Mark indicates compliance with safety standards. This section explains precautions regarding the Safe Disable input. Contact Yaskawa or your nearest sales representative for more information. The Safety Disable function complies with the standards listed in Table D.13.
Table D.13 Safety Standards and Applicable EU Standards
Safety Standards Applicable EU Standards
Note: SIL stands for Safety Integrity Level.
◆ Specifications
The Safe Disable input provides a stop function in compliance with the “Safe Torque Off” function defined in IEC/EN 61800-5-2:2007. The Safe Disable input satisfies the requirements in EN ISO 13849-1 and IEC/EN 61508, SIL2. Table D. 14 lists the specifications for the Safety Disable function.
Table D.14 Specifications for Safe Disable Function
Note: PFD = Probability of Failure on Demand PFH = Probability of Dangerous Failure per Hour
D
Standards Compliance
Figure D.11 TÜV SÜD mark, Functional Safety. Historical logo, not current certification validity.
Functional Safety | IEC 61508:2000/EN 61508:2001(SIL2)
Functional Safety | IEC/EN 61800-5-2: 2007 (SIL2)
Mechanical Safety | ISO 13849-1:2006 (Cat.III, PL d) / EN ISO 13849-1/AC:2009 (Cat.III, PL d)
EMC | EN 61800-3:2004/A1:2012
EMC | EN 61800-5-1:2007
Inputs/Outputs | Inputs/Outputs
Response Time from Input Open to Drive Output Stop | Response Time from Input Open to Drive Output Stop
Failure Probability | Demand Rate Low
Failure Probability | Demand Rate High/ Continuous
Performance Level | Performance Level
HFT (Hardware Fault Tolerance) | HFT (Hardware Fault Tolerance)
Classification of Subsystem | Classification of Subsystem
D13 historical safety and applicable EU standards — PDF page 481
| Source row | Safety category | Applicable standard |
|---|---|---|
| 1 | Functional Safety | IEC 61508:2000/EN 61508:2001(SIL2) |
| 2 | Functional Safety | IEC/EN 61800-5-2: 2007 (SIL2) |
| 3 | Mechanical Safety | ISO 13849-1:2006 (Cat.III, PL d) / EN ISO 13849-1/AC:2009 (Cat.III, PL d) |
| 4 | EMC | EN 61800-3:2004/A1:2012 |
| 5 | EMC | EN 61800-5-1:2007 |
D14 safe-disable function specification — PDF page 481
| Source row | Specification | Subitem or shared specification | Value |
|---|---|---|---|
| 1 | Inputs/Outputs | Inputs/Outputs | • Inputs: 1 Safe Disable input H1 • Outputs: 0 |
| 2 | Response Time from Input Open to Drive Output Stop | Response Time from Input Open to Drive Output Stop | Shorter than 1 ms |
| 3 | Failure Probability | Demand Rate Low | PFD = 1.24E−7 |
| 4 | Failure Probability | Demand Rate High/ Continuous | PFH = 5.17E−10 |
| 5 | Performance Level | Performance Level | The Safe Disable inputs satisfy the following requirements in consideration of the self-diagnostic function. Performance Level (PL) d according to EN ISO 13849-1 |
| 6 | HFT (Hardware Fault Tolerance) | HFT (Hardware Fault Tolerance) | N = 1 |
| 7 | Classification of Subsystem | Classification of Subsystem | Type B |
Manual — Safe Disable full precautions — page 482
Source reference: SIEP C71060618F, December 2016, physical PDF page 482. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ Precautions
DANGER! Sudden Movement Hazard. Make sure the whole system or machinery in which the Safe Disable function is used complies with safety requirements. When implementing the Safe Disable function into the safety system of a machine, perform a thorough risk assessment for the entire system to assure compliance with relevant safety norms. Improper use of the Safe Disable function will cause serious injury or even death.
DANGER! Sudden Movement Hazard. An external holding brake and dynamic break are not considered to be safety components for drives. Even when using an external holding brake or dynamic brake with a drive output signal, it is still not considered a safe system because the drive output signal is not a safety component. A system is required that satisfies safety requirements. Failure to comply will cause death or serious injury.
DANGER! Sudden Movement Hazard. Connect the Safe Disable inputs to the devices in compliance with safety requirements. Failure to comply will cause death or serious injury.
WARNING! Sudden Movement Hazard. When using a PM motor, even if the drive output is shut off by the Safe Disable function, a breakdown of two output transistors can cause current to flow through the motor winding, resulting in a motor output axis movement for a maximum angle of 180 degrees (electrically). Make sure such a situation would have no effect on the safety of the application when using the Safe Disable function. Failure to comply could cause serious injury or death.
WARNING! Electrical Shock Hazard. The Safe Disable function can switch off the drive output, but does not cut the drive power supply and cannot electrically isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or installations on the drive input side as well as the drive output side. Failure to comply could cause serious injury or death.
WARNING! Sudden Movement Hazard. The motor will move when an external gravitational force in the vertical axis is applied even if the Safe Disable function is in operation. Failure to comply could cause serious injury or death.
WARNING! Sudden Movement Hazard. When using the Safe Disable inputs, make sure to remove the wire links between terminals H1 and HC that were installed prior to shipment. Failure to do so will keep the Safe Disable circuit from operating properly and could cause death or serious injury.
WARNING! Sudden Movement Hazard. All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating normally, this could cause death or serious injury.
WARNING! Sudden Movement Hazard. Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should be permitted to wire, inspect, and maintain the Safe Disable input. Failure to comply could cause death or serious injury.
NOTICE: From the moment terminal inputs H1 and HC have opened, it takes up to 1 ms for drive output to shut off completely. The sequence set up to trigger terminals H1-HC should make sure that terminals H1-HC remain open for at least 1 ms in order to properly interrupt drive output.
NOTICE: Drives with safety-related functions need to be replaced after 10 years of use.
D.4 Safe Disable Input
Manual — Safe Disable wiring and operation — page 483
Source reference: SIEP C71060618F, December 2016, physical PDF page 483. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
◆ Using the Safe Disable Function
■ Safe Disable Wiring
If the Safe Disable function is utilized, the wire link between the terminals HC and H1 that is installed at shipment must be removed entirely. Connect the drive to an ISO/EN 13849-1, Safety Category 3 interrupting device so that in case of a Safe Disable request the connection between the terminals HC and H1 is opened.
Figure D.12 Safe Disable Wiring Example
■ Disabling and Enabling the Drive Output (“Safe Torque Off”)
Refer to Figure D.13 for an example of drive operation when switching from the “Safe Torque Off” status until reaching normal operation.
Figure D.13 Safe Disable Operation
Switching from Normal Operation to “Safe Torque Off” Turning OFF (opening) safety input terminal H1-HC will enable the Safe Disable function. Triggering the Safe Disable function while the motor is running will shut off the drive output and motor torque and the motor will coast to stop regardless of the b1-03 setting value. The “Safe Torque Off” status is only possible when using the Safe Disable function. Clear the Run command to stop the drive. Shutting off the drive output, as in a baseblock condition, is not the same as "Safe Torque Off".
Note: Switch OFF terminals H1-HC after the motor has come to a complete stop to prevent the motor from coasting to stop during normal operation.
Returning to Normal Operation from “Safe Torque Off” The safety input releases only when the Run command is not present. • During Stop: Place short circuit between terminals H1 and HC to disable “Safe Torque Off” when the Safe Disable function is triggered during stop. Enter the Run command after the drive stops normally.
D.4 Safe Disable Input
D
Standards Compliance
Figure D.12 Safe Disable wiring example: ISO/EN13849-1 Safety Cat,3 Device; Drive; Power Supply; Controller; HC; H1; M. Exact wiring, semiconductor topology and interlocks remain original-only; full precautions and qualified-personnel conditions mandatory.
Figure D.13: Output Frequency; Motor coasts to stop. Run Command: Run thenStop; Run Command must be released to deactivate Safe Disable. H1 Input: ON (Safe Disable off), OFF (Safe Disable activated); Drive is ready for operation. Drive Output: Normal operation; Safe Torque-Off; Baseblock (Not Safe!). Actual timing/arrow geometry remains original-only; no interval inferred.
Manual — Safe Disable recovery and validation — page 484
Source reference: SIEP C71060618F, December 2016, physical PDF page 484. The following source notes and tables retain the manual’s terminology. Use its complete procedures, diagrams and adjacent-page conditions; this reference is not an independent installation or safety approval.
• During run: Place short circuit between terminals H1 and HC to disable "Safe Torque Off" after clearing the Run command when the Safe Disable function is triggered during stop. Enter the Run command after entering the STOP command regardless of whether terminals H1-HC are ON.
■ Validating Safe Disable Function
Always perform the validation test on the Safe Disable inputs after completing the wiring after start-up, when replacing parts, or when conducting maintenance. Maintain check results as a record of tests performed.
D.4 Safe Disable Input
Selection checks and source differences
Manual communication configuration says255slaves but specificationtable says31drives. Website/catalogue SCCR30kA differs from manual ULsection31kA under statedvoltage/protectionconditions. Do not merge these into a single unqualified rating.
Catalogue CA.VJ.01 (2011) and manual SIEP C71060618F (2016) remain separate. US HP/code schedules do not establish current Australian availability. Shared J1000/VSmini data are excluded from V1000 specifications.
BA0018 appears in both duty columns of the older catalogue; the manual explicitly calls it HD-only. The combined cover and detailed V1000-4X single-phase range differ. No automatic stock or range expansion.
Catalogue pulse input33kHz differs from manual32kHz. Catalogue ramp minimum0.01s differs from manual0.00s; standard frequency0–400 differs from0.01–400Hz. Special1167Hz software is a separate configuration.
Catalogue dimensional summaries, rating pages and drawing tables contain different suffixes, weights or dimensions. Inches,mm(in),kg(lb),thread sizes and wildcard model positions remain literal; no invented conversion or outline equivalence.
Catalogue4X service table repeats NEMA1/OpenChassis headings. Dedicated4X installation manual is referenced but not separately supplied. Manual general enclosure footnotes also differ from its larger-frame IP00 model schedule; confirm exact hardware.
Catalogue calls a hardwire baseblock EN954-1Cat.3, while the later manual distinguishes baseblock from Safe Disable/STO. Use the full later safety section, selected hardware and machine assessment; no current certification claim is made.
Website vibration claim20–50Hz/0.65G differs from manual20–55Hz/5.9m/s². Website28yearMTBF/failure-rate and catalogue historical lead times are not warranties, current availability or maintenance intervals.
DriveWorksEZ standard section118blocks differs from4X119blocks and different access/training language. Catalogue guide calls120VAC interface D1-100 in one reference versusDI-100 in option prose. Confirm exact accessory.
C1 filter section explicitly gives C2 exceptions for some200Vmodels. Manual reactor note referring22kWandhigher lies beyond its stated18.5kWcover range; no larger V1000 model inferred. Historical safety/EMC standards and source logos are not independent current-validity proof.
The collected set contains a60-page shared catalogue and512-page manual, not dedicated dimension PDFs for every catalogue row. All supplied models/parameter tables remain represented; separately referenced option manuals are not treated as downloaded documents.
Product documents
- Yaskawa-V1000-catalogue.pdf — Product page
- Yaskawa-V1000-manual.pdf — Product page
- TAC-EMD-Standard-Conditions-of-Sale-Final-May-2022.pdf — Shared website
- ISO9001-Intertek-SAI-Global-Certificate-QEC3088-Expiry-25-May-2029.pdf — Shared website
- ISO45001-Intertek-SAI-Global-Certificate-0185118-Expiry-22-August-2027.pdf — Shared website
Our company certificates and conditions of sale remain separate from the selected product’s ratings and approvals.
Talk to our team about your application, supply, motor rating and configuration.