TECO E710 Compact Current Vector Control Drives

Our E710 combines compact installation, flexible motor control and practical commissioning tools for industrial machinery and process equipment. We offer a local IP20 range covering 0.37–2.2 kW at 200–240 V single-phase input and 0.75–7.5 kW at 380–480 V three-phase input, with separate Basic E and Standard S configurations. We can help select the drive, motor technology and controls for your application.

Select the exact configuration

The local catalogue lists ten complete model numbers. Its wider code legends and the manual cover additional configurations, so a code dictionary is not evidence that every possible combination is available locally.

Configuration Local catalogue model groups Selection boundary
Basic E, single-phase input E710-2P5-H1EF and E710-201-H1EF 0.37 and 0.75 kW; confirm against the individual sheet and motor nameplate.
Standard S, single-phase input E710-202-H1SF and E710-203-H1SF 1.5 and 2.2 kW in the catalogue; the collected 202 datasheet has a conflicting lower-power block.
Basic E, three-phase input E710-401-H3EF and E710-402-H3EF 0.75 and 1.5 kW. The catalogue states no STO for Basic E.
Standard S, three-phase input E710-403-H3SF, 405-H3SF, 408-H3SF and 410-H3SF 2.2, 3.7, 5.5 and 7.5 kW respectively; check model-specific interfaces and safety instructions.

Our collected register has 10 website rows, 20 PDF memberships and 13 distinct technical PDFs, including three shared outline drawings. Every collected association is retained below. The drawings do not print an electrical model-to-frame schedule, so their website associations must be used with the matching datasheet and exact model.

Selection discrepancy: the sheet headed E710-202-H1SF, 1.5 kW, 2 HP prints 0.5 HP, 0.4 kW and 2.8 A in its rating block. The catalogue lists 1.5 kW and 7.5 A. Please obtain confirmation for this model; we have preserved both sources without substituting one into the other. Some datasheets also label the motor output “Single Phase”, whereas the manual's electrical schedules specify three-phase output. Do not select a single-phase motor from that disputed wording.

Motor control and application choices

Our local material describes induction and permanent-magnet motor control, with synchronous-reluctance motor support on request. The headline starting-torque figure is 150% at 0.5 Hz in SLV mode; the V/F figure is 150% at 3 Hz. The heavy-duty overload reference is 150% for one minute, subject to the model and operating conditions.

The website describes six control modes and the catalogue describes seven. The manual separates E and S capabilities and marks V/F+PG, SV and PMSV as special-project functions. Its parameter table retains reserved selections. We therefore confirm encoder, firmware and motor requirements before promising closed-loop or SynRM operation. The general 0.01–599 Hz range is qualified by mode: the manual's SLV maximum is 150 Hz under the stated model/carrier conditions.

Applications described in our catalogue include pumps, fans, conveyors, mixers and machine building across water treatment, materials handling, food processing and other industries. Load duty, speed range, braking, environment and safety requirements govern suitability. Features include auto-tuning, PID, preset speeds, programmable control, speed search, soft PWM, acceleration/deceleration profiles and diagnostic history, according to configuration. A listed motor efficiency class is not the drive's efficiency at every operating point.

A compact fit, with clear installation conditions

The E710 offers DIN-rail installation features, spring-loaded control terminals, selectable NPN/PNP interfaces and a removable cooling fan. We describe a compact dual-CPU design; use the actual outline for panel design rather than a percentage size-reduction claim.

Zero-gap side-by-side mounting is conditional. The manual allows 40°C maximum at C=0 mm, compared with 50°C at C≥30 mm, and shows 150 mm above and below. Dust stickers and enclosure arrangements also change the temperature limits. Zero side gap does not mean zero ventilation clearance in every direction.

The local catalogue states an operating minimum of −20°C, while the manual and website use −10°C. Confirm the supplied drive's environmental rating with us. The manual's base IP20 range extends to +50°C, with load reduction for higher temperatures and model/carrier-specific curves; its general altitude reference is full load up to 1,000 m and current reduction above that, up to 3,000 m. These conditions must be read together.

The brochure's built-in-filter dimension tables give separate Frame 1, 2 and 3 sizes and weights, while other narrative mentions different depths. We preserve every dimension schedule by configuration. The original drawings define mounting holes and geometry. IP20 is not weatherproof or hazardous-area approval.

Interfaces and commissioning tools

Built-in Modbus RTU over RS485 is described across the range. Other protocols require the appropriate optional interface: our sources list Profibus DP, CANopen, EtherCAT, EtherNet/IP, Profinet, Modbus TCP, TCP/IP, BACnet IP, OPC UA and DeviceNet. The catalogue describes one communication expansion card per drive. The accessory tables distinguish cards from modules; confirm compatibility and obtain the relevant protocol manual and device-description files.

DriveLink provides parameter editing, saving, comparison, monitoring and logging; the catalogue specifies the JN5-CM-USB connection accessory. The optional JN7-CU copy module supports parameter transfer between matching units. The optional JN5-OP-BTH Bluetooth operator provides wireless access, subject to the selected hardware and project configuration. Keep commissioning records and check the copied motor and application settings rather than assuming a transferred parameter set is suitable for a different machine.

The F suffix identifies a built-in filter in the local code legend. EMC performance depends on installation and cabling. Braking-transistor and resistor options retain their exact model and duty conditions; a transistor specification is not a resistor-selection calculation. Digital and analog I/O differ between E and S types. Use the terminal-function tables and original wiring diagrams, not a combined headline I/O count.

Safety and system protection

Our catalogue assigns STO to applicable Standard S models and explicitly lists none for Basic E. STO removes torque-producing output and allows the load to coast; it is not a mechanical brake or electrical isolation. The published SIL2/PLd and related standard statements describe the specified product function, not certification of the complete machine. The necessary external safety devices, reset behaviour and testing depend on the machine's risk assessment and applicable instructions. We do not promise that every installation can omit contactors or restart immediately.

The manual also includes a separate Fire mode that can override commands and protections. It is a specialist configuration, not a substitute for STO or a general emergency-stop instruction. Refer to the complete fire-mode warnings and application requirements before considering it.

Maintenance information you can act on

Our marketing material describes predictive diagnosis of the cooling fan and DC-bus capacitors. The manual gives configurable capacitor monitoring, fan operating-time and IGBT lifespan settings, with monitoring values and reset requirements after replacement. Configure and maintain these correctly. The fan/IGBT replacement reference is conditional on operating environment; monitoring is not a guarantee that every failure will be predicted or prevented.

The catalogue also describes PM demagnetisation prevention and induction-motor fault detection. Confirm the supported function, mode and settings for the actual motor and drive. These features do not replace inspection, protection coordination or fault investigation.

Use qualified personnel and the complete isolation, discharge and voltage-verification procedure before installation or maintenance. Auto-restart and reset functions can restart equipment when enabled. The source set includes daily/periodic inspection tables, long-storage capacitor activation, troubleshooting, fuse/reactor/filter schedules, communication references and operating-point loss data. The detailed references below retain those conditions and their original page numbers.

Read the source-specific references together

The 2026 local catalogue, E710 English V01 manual, individual datasheets and outline drawings remain distinct. Original parameter defaults, reserved values, mode markings, units and blank fields are retained. Adjacent-page notes and original diagram geometry still apply. We have not converted the manual's loss table into one universal efficiency claim, nor used a generic catalogue heading to create additional orderable models. Speak with our team to confirm any unresolved selection detail.

Catalogue — Cover identity — page 1

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 1

TECO E710

Next Gen Compact Current Vector Control Variable Speed Drive

200-240V 1/3Ph 0.37kW - 2.2kW 380-480V 3Ph 0.75kW - 7.5kW IP20

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Contents — page 2

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 2

Contents

Introduction 3

  1. Product Overview 4

  2. Where it’s used 10

  3. Motor Control 13

  4. Design and Performance 15

  5. Installation and Commissioning 16

  6. Safety Function 20

  7. System Protection 21

  8. Catalogue Number Identification 26

  9. Dimensions 29

  10. Accessories and Part Numbers 30

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Corporate introduction — page 3

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 3

Rotating the World Sustainably and Reliably with TECO’s Industrial Solutions.

TECO is a global leader specialising in manufacturing and distribution of industrial Electric Motors and Variable Speed Drives.

Our extensive product range includes high-quality Low & Medium Voltage Motors from fractional kW to 22,000 kW for supplies up to 14,200 Volts, energy-efficient Variable Speed Drives and reliable automation equipment.

Our commitment to excellence is evident in our longstanding ISO 9001 and ISO 14001 certifications. Furthermore, our recent acquisition of the EPACT Energy Efficiency Certificate solidifies our position as an exemplary player in the global marketplace.

TECO‘s commitment to technological advancement and sustainable practice has earned a reputation for delivering superior products and exceptional customer service.

With TECO, you can trust in industry-leading performance, reliability, and a commitment to sustainable practices.

GLOBAL EXPERTISE WITH LOCAL SUPPORT

Operating in over 30 countries across all five continents.

VAST STOCK AVAILABILITY

Large stock range across Australia & New Zealand.

LOCAL IN-HOUSE WORKSHOP

Full range of mechanical and electrical modifications ensuring adherence to TECO’s stringent QA procedures and relevant standards.

INTRODUCTION

TECO E710 | 3

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Context: Corporate range22,000kW/14,200V and company certifications are corporate scope, not E710 ratings.

Context: Corporate certification logo also reads ISO 45001. The body separately claims ISO 9001/ISO 14001; these remain corporate historical statements rather than E710 product certification.

Catalogue — Control characteristics — page 4

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 4

The TECO E710 is a Next Gen Compact Current Vector Control variable speed drive (VSD) for controlling the speed and torque of AC motors. It replaces fixed-speed or direct-on-line motor operation with precise, adjustable speed control across a wide range of industrial applications.

  1. Product Overview

PRODUCT OVERVIEW

4 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Context: Keypad frequency-setting cell includes visible up/down triangle keys (▲/▼) before the words “keys or the VR on the keypad”; text layer omits the triangle icons.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Values spanning both printed model columns repeated only from the same physical shared cell. Standard403–430/202–220 versus Basic401–402/2P5–201 as printed.

Control characteristics — PDF page 4

Parameter Standard S type / shared specification Basic E type / shared specification
CONTROL CHARACTERISTICS IM: V/F, V/F+PG, SLV, SV IM: V/F, SLV
CONTROL CHARACTERISTICS PM: SV, SLV PM: SLV
CONTROL CHARACTERISTICS SRM: PMA-SyRM-SLV, SyRM-SLV (on request) -
Frequency control range 0.01Hz~599Hz 0.01Hz~599Hz
Starting torque 150%/3Hz(VF) , 150% / 0.5Hz (SLV) 150%/3Hz(VF) , 150% / 0.5Hz (SLV)
Frequency setting resolution Digital references: 0.01Hz Digital references: 0.01Hz
Frequency setting resolution Analog references: 0.06Hz/60Hz Analog references: 0.06Hz/60Hz
Frequency setting keypad: Set directly with keys or the VR on the keypad keypad: Set directly with keys or the VR on the keypad
Frequency setting External Input Terminals: AI1/AI2 (0~10V / 2~10V / 0~20mA / 4~20mA) input Multifunction input up/down function External Input Terminals: AI1/AI2 (0~10V / 2~10V / 0~20mA / 4~20mA) input Multifunction input up/down function
Frequency setting Setting frequency by communication method Setting frequency by communication method
Frequency limit Lower and upper frequency limits 3 skip frequency settings Lower and upper frequency limits 3 skip frequency settings
Speed control accuracy V/F :±2~3%, SLV :± 1% V/F :±2~3%, SLV :± 1%
Operation set Keypad run, stop button Keypad run, stop button
Operation set External terminals: Multi-operation-mode2/3 wire selection, Jog operation External terminals: Multi-operation-mode2/3 wire selection, Jog operation
Operation set Run signal by communication method Run signal by communication method
V / F curve setting 18 fixed curves and one customised curve 18 fixed curves and one customised curve
Carrier frequency 2kHz~16kHz (default value : 4kHz) 2kHz~16kHz (default value : 4kHz)
Acceleration and deceleration control 2 off Acc / dec time parameters 2 off Acc / dec time parameters
Acceleration and deceleration control 4 off S curve parameters 4 off S curve parameters
Multifunction input 29 functions (refer to description on group 3) 29 functions (refer to description on group 3)
Multifunction output 21 functions (refer to description on group 3) 21 functions (refer to description on group 3)
Multifunction analog output 5 functions (refer to description on group 4) 5 functions (refer to description on group 4)
Main features Overload Detection, 16 preset speeds, Auto-run, Acc/Dec Switch (2 Stages), PID control, Torque boost, Main/Alt run Command select, Main/Alt Frequency Command select, V/F start Frequency, Fault reset Overload Detection, 16 preset speeds, Auto-run, Acc/Dec Switch (2 Stages), PID control, Torque boost, Main/Alt run Command select, Main/Alt Frequency Command select, V/F start Frequency, Fault reset
LED Display: Parameter / Parameter value / Frequency / Line speed / DC voltage / Output voltage / Output current / PID feedback / input and output terminal status / Heat sink temperature / Program Version / Fault Log Display: Parameter / Parameter value / Frequency / Line speed / DC voltage / Output voltage / Output current / PID feedback / input and output terminal status / Heat sink temperature / Program Version / Fault Log
LED Status Indicator Run / Stop / Forward / Reverse etc Run / Stop / Forward / Reverse etc

Catalogue — Protection and environment — page 5

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 5

PRODUCT OVERVIEW

TECO E710 | 5

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Values spanning both printed model columns repeated only from the same physical shared cell. Standard403–430/202–220 versus Basic401–402/2P5–201 as printed.

Protection, environment and conformity — PDF page 5

Parameter Standard S type / shared specification Basic E type / shared specification
Overload Protection To protect the motor and the inverter. (150%/1min) To protect the motor and the inverter. (150%/1min)
Over voltage 220V: >410V, 380V: >820V 220V: >410V, 380V: >820V
Under Voltage 220V: <190V, 380V: <380V 220V: <190V, 380V: <380V
Momentary Power Loss Restart Inverter automatically restarts after a momentary power loss Inverter automatically restarts after a momentary power loss
Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation Stall prevention for Acceleration/ Deceleration/ Operation
Short-circuit output terminal Electronic Circuit Protection Electronic Circuit Protection
STO Functions Standard S type (403~430/202~220):Output quick break Basic E type (401~402/2P5~201):None
Other protection features Protection for overheating of heat sink, the carrier frequency decreasing with the temperature function, fault output, reverse prohibit, prohibit for direct start after power up and error recovery, parameter lock up Protection for overheating of heat sink, the carrier frequency decreasing with the temperature function, fault output, reverse prohibit, prohibit for direct start after power up and error recovery, parameter lock up
Communication control Standard built-in RS485 communication (Modbus), one to one or one to many control Standard built-in RS485 communication (Modbus), one to one or one to many control
Operating temperature Type IP20/NEMA 1 inside switchboard: Without dustproof sticker: -20°C - 50°C / With dustproof sticker: -20°C - 40°C Side-by-side installation: -20°C - 40°C *Derating: For usage between 50°C - 60°C, there is a 2% decrease in current for every 1°C increase Type IP20/NEMA 1 inside switchboard: Without dustproof sticker: -20°C - 50°C / With dustproof sticker: -20°C - 40°C Side-by-side installation: -20°C - 40°C *Derating: For usage between 50°C - 60°C, there is a 2% decrease in current for every 1°C increase
Storage temperature -20°C - 70°C -20°C - 70°C
Humidity 95% RH or less (no condensation) (Compliance with IEC 60068 - 2-78) 95% RH or less (no condensation) (Compliance with IEC 60068 - 2-78)
Shock 10Hz ≤ f ≤ 57Hz: ±0.075mm Amplitude; 57Hz ≤ f ≤ 150Hz: 1.0G Acceleration: (Compliance with IEC60068-2-6) 10Hz ≤ f ≤ 57Hz: ±0.075mm Amplitude; 57Hz ≤ f ≤ 150Hz: 1.0G Acceleration: (Compliance with IEC60068-2-6)
Protection class IP20 / NEMA1 IP20 / NEMA1
Certification UL / cUL / CE / RoHS / REACH UL / cUL / CE / RoHS / REACH

Catalogue — DECORATIVE_PHOTO — page 6

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 6

This page contains no separately transcribed product values. The original illustration or source page remains the authority for its visual content.

Catalogue — Design priorities — page 7

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 7

Five Design Priorities

The TECO E710 is built around five design priorities that address the most common requirements in industrial VSD applications:

  1. Simple, Reliable Operation

The cooling fan is removable without disturbing wiring or pulling the unit from the panel. Spring-loaded terminals accept tool-free wiring and are clearly labelled. The keypad is replaceable with an optional Bluetooth panel for wireless smartphone or tablet access. DriveLink PC software (free) provides full parameter access, monitoring, and data logging.

PRODUCT OVERVIEW

  1. Predictive Maintenance

The TECO E710 tracks service life on two internal components: the cooling fan and DC bus electrolytic capacitors. A pre-failure advisory converts unplanned breakdowns into scheduled maintenance stops. For the connected motor: PM types are flagged for demagnetisation risk, induction types for early-stage winding faults, with pre-fault warnings before motor damage occurs.

• Predictive diagnosis

• Multiple protection

• Advanced process

• Demagnetisation

• Life prediction

• Built-in filter

  1. Global Certifications

Safe Torque Off (STO) is built in as standard on applicable models, certified to EN ISO 13849-1 Cat/PLd, EN 61508 SIL2, and EN 62061 SIL CL2. External safety contactors are not required in most machine safety applications at this integrity level.

• Global sales: UL, cUL, CE

• Responsible: RoHS, REACH

  1. Compact Installation

Dual-CPU architecture cuts enclosure size by 50%, at 150–169 mm depending on frame size. Zero thermal clearance gap between drives reduces panel width in multi-drive installations. Buckle-lock DIN rail mounting and spring-loaded quick-disconnect control terminals deliver fast installation and wiring in standard switchboard builds.

Size reduction

  1. High-Performance Motor Control

Seven motor control modes cover three motor technologies: induction (IM), permanent magnet (PM), and synchronous reluctance (SynRM, on request).

IM

PM

SynRM

IPM SPM

Multi-type PG feedback / Low motor noise / Bluetooth remote connection

TECO E710 | 7

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Features and benefits — page 8

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 8

PRODUCT OVERVIEW

8 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Supplier benefit statements do not establish engineering suitability.

Features and claimed benefits — PDF page 8

Feature What it does Benefit to you
Side-by-Side Installation Dual-CPU design reduces drive size by 50% versus previous range. Drives mount directly adjacent with no thermal clearance gap required (up to 50°C standard; up to 40°C with anti-dust stickers applied). Halves horizontal panel footprint on multi-drive installations. Smaller cabinet, less steel, lower build cost.
Seven Motor Control Modes V/F, V/F+PG, SLV, SV for induction motors; PM SV, PM SLV for permanent magnet motors; on request-SLV, PMA-SynRM-SLV on request. One drive platform covers every motor type commonly used in Australian industrial projects. No need to qualify, stock, and commission separate drive platforms for different motor types. Supports IE4/IE5 motor upgrades without changing the drive.
Starting Torque 150% at 0.5 Hz (SLV) Sensorless vector control mode delivers 150% of rated torque at 0.5 Hz output frequency — from near standstill. No encoder required. Handles heavy starting loads: loaded conveyors, screw feeders, loaded compressors, mixers with viscous product — applications where a basic V/F drive would trip or stall on start.
Predictive Diagnosis Continuously monitors the internal cooling fan and DC bus electrolytic capacitors. Notifies when either component approaches its end-of-service-life threshold — before failure. Converts unplanned drive failures into scheduled maintenance stops. Eliminates emergency callout cost and unplanned production downtime.
Motor Protection — PM and IM PM demagnetisation protection prevents the rotor magnets of a PM motor from exceeding safe temperature limits under sustained overload. IM fault detection identifies early-stage winding faults in induction motors and generates a pre-fault warning before motor damage occurs. Protects the motor, not just the drive. PM demagnetisation is irreversible — prevention is the only remedy. Early warning of IM winding faults reduces the risk of a motor failure causing a production stop.
Soft PWM — Motor Noise Reduction Proprietary algorithm that reshapes the PWM switching waveform to reduce audible motor noise and mechanical vibration. Operates across all carrier frequency settings. No manual adjustment required. Reduces motor noise on sensitive machinery — food processing, packaging, pharmaceutical — without additional hardware or parameter configuration.
Built-in EMI Filter Built-in EMI filter compliant with EN 61800-3 Class I, C2 level (compliance achieved when cabling guidelines are followed). Reduces conducted and radiated electromagnetic interference to levels compatible with sensitive industrial environments. No separate external EMI filter component required in most standard installations. Lower Bill Of Materials cost and simpler panel design.
Built-in Safe Torque Off (STO) — SIL2 STO certified to EN ISO 13849-1 Cat/PLd, SIL2, and EN 62061 SIL CL2. Disables PWM output on safety input actuation. Safety input connects directly to F1/ F2 terminals. Eliminates the cost and wiring of external safety contactors in machine safety applications meeting AS 4024 / AS/NZS 62061 at SIL2.
Built-in RS485 Modbus RTU Built-in RS485 Modbus RTU on all models as standard. One-to-one and one-to-many (multi-drop) configurations. Covers the majority of SCADA and PLC integration requirements without additional hardware. Additional fieldbus expansion cards available for Profibus DP, EtherCAT, Profinet, Ethernet/IP, Modbus TCP, BACnet IP, OPC UA, CANopen and DeviceNet.
Full Output to 50°C — No Derating Full rated output from -10°C to +50°C (standard installation, without anti-dust stickers). Derating applies only above 50°C: 2% per 1°C. No drive oversizing required for hot plant rooms, outdoor enclosures, Queensland summer conditions, or mining sites.
DriveLink PC Software (free) Free PC software for full parameter read/write, real- time monitoring, data logging, firmware updates, and parameter comparison. Connection via RJ45 port and JN5-CM-USB cable. No licence cost. Faster than keypad entry. Full parameter documentation from a laptop. Parameters can be prepared off-site and loaded on site.
Copy Module (JN7-CU) Stores the complete parameter set from one TECO E710 and writes it to any replacement or additional unit in a single operation. On sites with 5 or more identical drives, eliminates repetitive manual programming. Reduces fleet commissioning time and removes the risk of individual entry errors.
UL / cUL / CE / RoHS / REACH Compliant with North American (UL/cUL), European (CE), and international environmental standards. Supports export machine certification and project specifications requiring international compliance documentation.

Catalogue — DECORATIVE_PHOTO — page 9

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 9

This page contains no separately transcribed product values. The original illustration or source page remains the authority for its visual content.

Catalogue — Industries — page 10

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 10

  1. Where it’s used

TECO E710 is designed for general-purpose industrial use across machinery and process applications. Flexible motor control, compact installation and global certifications support deployment from OEM machine builds to site-level process equipment.

WHERE IT’S USED

SOLAR ENERGY

POWER GENERATION

RUBBER & PLASTICS

WATER & WASTEWATER

TIMBER PULP & PAPER

OIL & GAS

MINING & METALS

MATERIALS HANDLING

FOOD & BEVERAGE

OEM - MACHINE BUILDING

10 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Application examples — page 11

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 11

WHERE IT’S USED

TECO E710 | 11

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Supplier benefit statements do not establish engineering suitability.

Application examples — PDF page 11

Industry Typical applications Challenge TECO E710 solution
Mining & Metals Conveyors, crushers, pumps, ventilation fans. High-inertia loads demand high torque at low speed. Remote sites make unplanned downtime costly. 150% torque at 0.5Hz (SLV mode). Predictive diagnosis flags cooling and capacitor faults before failure. Full rated power to +50°C.
Water & Wastewater Centrifugal pumps, blowers, dosing systems. Variable flow demand requires accurate speed control to avoid water hammer and reduce energy use. V/F and SLV modes for pump optimisation. Fieldbus integration for multi-pump and SCADA control. Built- in STO for safe maintenance isolation.
OEM Machine Building Automated machinery, test rigs, specialty equipment. OEMs need compact, flexible drives that integrate quickly and support multiple motor types. Zero-gap side-by-side installation. 7 control modes including PM and SynRM (on request). 10 optional fieldbus protocols. Copy Module for fleet commissioning.
Food & Beverage Mixers, conveyors, packaging lines, pumps. Variable speed control across mixed line equipment. Operation must be consistent and reliable. Precise speed control across all motor types. Soft PWM reduces motor stress and audible noise. Multiple control modes for varied process requirements.
Materials Handling Conveyors, sortation systems, palletisers, hoists, wrapping machines. Loaded starts and high cycle counts. Multi-drive synchronisation across long conveyor lines. Reliable operation in distribution and warehouse environments. 150% torque at 0.5Hz for loaded conveyor starts. Fieldbus integration for synchronised multi-drive control. Predictive diagnosis suited to unmanned distribution centres. Copy Module for fleet commissioning.
Power Generation Cooling fans, pumps, auxiliary drives. Auxiliary systems require reliable, energy-efficient speed control in continuous-duty environments. Full rated power -10°C to +50°C with no derating. Soft PWM for reduced motor wear. Fieldbus for plant SCADA integration.
Solar Energy Solar-powered pumping, irrigation, water treatment. Variable DC supply from solar panels must produce stable motor output under fluctuating conditions. Wide input voltage tolerance. Consistent, stable output across varying supply conditions.
Timber, Pulp & Paper Saws, chippers, conveyors, pulp mixers. High-inertia loads and continuous duty demand reliable torque control and proactive maintenance. SLV mode for high-torque starts. Predictive diagnosis for planned maintenance scheduling. Robust thermal performance.
Oil & Gas Pumps, fans, compressors (safe area). Drives must perform reliably in harsh conditions with minimal maintenance intervention. Compact footprint for tight panel installations. Predictive diagnosis reduces unplanned downtime. STO for safety circuit integration.
Rubber & Plastics Extruders, mixers, injection moulding, calendering. Consistent torque and speed are critical. Process variation directly affects product quality. Vector control with 7 selectable modes. Adapts from light to heavy process loads without manual adjustment.

Catalogue — DECORATIVE_PHOTO — page 12

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 12

This page contains no separately transcribed product values. The original illustration or source page remains the authority for its visual content.

Catalogue — Motor modes — page 13

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 13

  1. Motor Control – Seven Modes, One Drive

The TECO E710 supports seven motor control modes, covering induction motors, permanent magnet motors and synchronous reluctance motors (on request), from basic V/F to full closed-loop vector control.

Induction Motor

Permanent Magnet Motor

Line-Start Synchronous Reluctance Motor

Selecting the right control mode depends on three factors: the motor technology, the load profile, and whether an encoder is fitted to the motor shaft.

MOTOR CONTROL

TECO E710 | 13

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Supplier benefit statements do not establish engineering suitability.

Motor control modes — PDF page 13

Control mode What it does Best for
V/F Volts per Hertz — fixed voltage-to-frequency ratio. Standard open-loop control. Fans, pumps, simple conveyors with smooth, predictable loads.
V/F + PG Same as V/F, with encoder feedback to confirm actual shaft speed. Applications requiring confirmed speed accuracy without full vector control (encoder required).
SLV — Sensorless Vector (IM) Calculates motor speed and position mathematically — no encoder required. Delivers high torque at low speed: 150% torque at 0.5 Hz. Conveyors, mixers, extruders, loaded starts — any application with variable load and no encoder.
SV — Closed Loop Vector (IM) Full vector control with encoder feedback. Highest speed accuracy under varying load. 150% torque at 3 Hz. Hoists, winders, precision axis — where speed must be held exactly as load changes (encoder required).
PM SV — Permanent Magnet, Closed Loop Designed for PM motors (IE4/IE5). Encoder feedback for full precision and maximum efficiency. High-efficiency PM motors where full performance and accuracy are required (encoder required).
PM SLV — Permanent Magnet, Sensorless PM motor control calculated mathematically — no encoder required. IE4/IE5 motor support. PM motors in standard applications where full precision is not required.
SynRM-SLV / PMA- SynRM-SLV (on request) Designed for synchronous reluctance motors — the latest generation of ultra-high efficiency (IE4/IE5) motors. No encoder required. SynRM motors, IE4/IE5 high-efficiency projects.

Catalogue — SynRM and noise reduction — page 14

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 14

Rotating speed

Initial magnetic pole; precise estimation

High-speed control ratio, output motor maximum torque, smooth accelerataion without torque pulsation

High-efficiency field weakening control, controls motor magnetic fields and achieves energy efficiency optimisation

Load change can maintain speed stability in the non-sensing state

SynRM Motor Support

The TECO E710 supports synchronous reluctance (SynRM*) motors rated IE4/IE5 — the latest generation of ultra-high efficiency motors.

If your project specifies SynRM motors for energy efficiency compliance or premium efficiency ratings, the TECO E710 provides the complete motor control solution at a compact drive price point.

Contact TECO Australia to confirm the correct drive selection for your motor specification.

Motor Noise Reduction (Soft PWM)

Exclusive Soft PWM control technology reduces the radio frequency interference and motor noise.

Traditional PWM output Soft PWM output

Acoustic Noise Reduction

The TECO E710’s Soft PWM algorithm reshapes the switching waveform to reduce audible motor noise and mechanical vibration, without increasing heat dissipation or EMI output.

Soft PWM is available across all TECO E710 models and carrier frequency settings.

Built-in EMI Filter

TECO E710 models with suffix ‘F’ in the catalogue number include a built-in EMI filter compliant with EN 61800-3 Class I environmental restrictions (C2 level). This reduces conducted and radiated electromagnetic interference from the drive to levels that are compatible with sensitive industrial environments — typically eliminating the need for a separate external EMI filter component in standard installations.

MOTOR CONTROL

14 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Installation dimensions and temperature — page 15

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 15

Miniaturisation

Space saving new technology and dual CPU design.

Ambient temperature -20 °C ~50°C without derating.

Seamless side-by-side installation

Significantly reduces installation space requirements and installation costs.

Install side-by-side or add dust-proof stickers: ambient temperature -20 °C ~40°C without derating.

Reduced Drive Depth

The TECO E710 uses a dual-CPU architecture that reduces drive enclosure depth by 50% compared to the previous TECO compact range. Frame sizes are:

• Frame 1: 72mm wide, 195.5mm deep

• Frame 2: 87mm wide, 207mm deep

• Frame 3: 109mm wide, 210mm deep

This is a physical reduction in the drive enclosure, not a change in mounting method. Shallower drives allow more compact switchboard construction and are particularly advantageous where panel depth is constrained by the installation location.

Zero-Gap Side-by-Side Mounting

TECO E710 drives can be mounted directly adjacent with no thermal clearance gap required, subject to the following ambient temperature limits:

• Standard installation, without anti-dust stickers: full rated output up to 50°C ambient

• Side-by-side installation, with anti-dust stickers applied: full rated output up to 40°C ambient

On a multi-drive panel, zero-gap side-by-side mounting significantly reduces the horizontal cabinet footprint compared to drives that require spacing between units. The practical result is a smaller switchboard with lower cabinet build cost, on any installation with two or more drives. Anti-dust stickers for side-by-side installation are included with the TECO E710.

The 50°C upper limit without derating is directly relevant to Australian conditions. Switchboard temperatures in Queensland and Western Australia regularly approach 45-50°C on summer days. Drives with a lower derating threshold require the engineer to oversize the drive selection to maintain full rated output — adding cost and panel space for no engineering benefit. The TECO E710 eliminates this requirement for the majority of Australia and New Zealand industrial installations.

  1. Design and Performance

Ultimate space experience

DESIGN AND PERFORMANCE

50%

Size reduction

TECO E710 | 15

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Installation features — page 16

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 16

Easy to use

Communication accessories are easy to install, network interfaces and terminals coexist.

  1. Installation and Commissioning

Hardware installation features

INSTALLATION AND COMMISSIONING

The TECO E710 is designed for straightforward switchboard installation:

• DIN rail mounting with buckle locking: standard installation without additional fasteners or brackets

• Spring-loaded quick-disconnect control terminals: tool-free wiring

• Removable cooling fan: the fan can be removed for cleaning or replacement without disturbing drive wiring or removing the unit from the panel

• Anti-dust stickers included: applied to side ventilation slots for side-by-side installation

Standard equipment includes extendable LED panel

Compatible with TECO A510s LCD panel

The fan disassembles easily for cleaning and maintenance

Anti-dust stickers for added protection

The buckle design is convenient for installation

Spring-loaded quick-disconnect terminals save installation time

Buckle-lock DIN rail mounting. Fast and secure.

16 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — DriveLink and copy module — page 17

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 17

INSTALLATION AND COMMISSIONING

DriveLink PC Software (Free)

DriveLink intuitive interface

Users can use PC software to conveniently and efficiently edit E710 inverter parameters, save, and compare, etc. Improves efficiency of customer parameter settings and on-site debugging.

Copy Module (JN7-CU) — Fleet Commissioning

Features

• It is possible to copy the inverter parameter settings and write them to other inverters

• Standard RJ45 network cable

DriveLink is TECO’s free PC software for full TECO E710 parameter access, monitoring, and maintenance. Connection via RJ45 port on the drive (JN5-CM-USB cable required). No licence fee. Key functions:

• Full parameter read/write: faster and more reliable than keypad entry on any multi-parameter or multi-drive project

• Real-time operating status monitoring: full visibility of drive and process parameters

• Data logging: records operating parameters over time for performance analysis and fault investigation

• Firmware updates: applied directly from the laptop

• Parameter save and compare: store parameter sets as files, compare configurations between drives, and document commissioning records for handover

Parameters can be prepared and verified off-site, then loaded directly on site from the laptop without keypad entry.

The JN7-CU Copy Module connects to the TECO E710’s RJ45 port and stores the complete parameter set from one unit. The stored set can then be written to any other TECO E710 of the same model in a single operation.

On sites with multiple identical drives such as a water treatment plant with 15 pump drives, a distribution centre with 20 conveyor drives, a food processing line with 10 identical mixer drives, the Copy Module eliminates manual keypad programming for each unit after the first. This reduces commissioning time substantially and removes the risk of individual parameter entry errors across the fleet.

TECO E710 | 17

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Communications and Bluetooth — page 18

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 18

Wireless Access — Bluetooth Operator Panel

Smart Factory - Smartphone remote connection

The optional LCD Bluetooth panel remotely connects inverters with mobile phones so customers can conveniently monitor and adjust machines remotely. Smartphones can be remotely connected to machines by installing the TECO Bluetooth operator (project-specific option) on the panel to edit parameters and confirm monitoring information in real time.

• Monitor operating conditions

• Parameter setting

• Confirm error records

• Troubleshooting when errors occur

The optional Bluetooth operator panel (Part No. JN5-OP-BTH) replaces the standard LED keypad and provides wireless access to the TECO E710 from a smartphone or tablet.

Typical Use Cases

The JN5-OP-BTH Bluetooth operator panel provides full wireless access to all TECO E710 operating functions from a smartphone or tablet, without opening the panel or touching the physical keypad. The panel fits the TECO E710’s standard operator panel slot with no modification to the drive enclosure required.

• Parameter reading and editing: full commissioning and parameter adjustment from any position

• Real-time operating status: output frequency, current, voltage, PID feedback, heatsink temperature

• Fault and error record review: full fault history accessible remotely

• Troubleshooting: diagnose a tripped drive without opening the panel

The JN5-OP-BTH is well suited to drives installed in ceiling plant rooms, high switchboard columns, or deep enclosures where physical keypad access is restricted.

INSTALLATION AND COMMISSIONING

Communication — Fieldbus Integration

Ten Fieldbus Protocols Supported

• Through the inverter RS485 expansion slot, the following communication protocols are supported: Profibus DP, Profinet, EtherCAT, EtherNet/IP, Modbus TCP, TCP/IP, BACnet IP, OPC UA, CANopen and DeviceNet.

RS485 Modbus RTU is built in as standard on all TECO E710 models. For integration with PLC, SCADA, or automation systems using other protocols, ten optional fieldbus expansion cards are available::

• Profibus DP

• CANopen

• EtherNet/IP

• EtherCAT

• TCP/IP (Ethernet)

• Profinet

• OPC UA

• Modbus TCP

• BACnet IP

• DeviceNet

All expansion cards fit the TECO E710’s single option card slot. One communication expansion card per drive.

18 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — DECORATIVE_PHOTO — page 19

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 19

This page contains no separately transcribed product values. The original illustration or source page remains the authority for its visual content.

Catalogue — STO source claims — page 20

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 20

Traditional

  1. Safety Function — Built-in Safe Torque Off (STO)

The TECO E710 includes integrated Safe Torque Off (STO), certified to:

• EN 60204-1 Category 0

• EN ISO 13849-1 Category/PLd

• EN 61508 SIL2

• EN 62061 SIL CL2

How STO Works

STO removes the electrical source of torque to the motor. It is not a mechanical brake — the motor and connected load are free to coast after STO is activated. STO ensures that the drive cannot apply torque to the motor shaft in response to a safety input event, such as an emergency stop actuation or a safety guard opening.

Elimination of External Safety Contactors

Conventional SIL2 safety circuits require two external safety contactors, safety relay hardware, and periodic proof testing to maintain the required safety integrity level.

With STO built into the TECO E710, the safety input connects directly to the drive’s F1/F2 terminals. External safety contactors are not required for most machine safety applications at SIL2, eliminating:

• External safety contactor hardware and procurement cost

• Additional panel wiring for the contactor safety circuit

• Contactor wear and periodic proof testing on high-cycle safety stop applications

• Additional failure points in the safety chain

The STO response is faster than a contactor-based circuit because gate signals are disabled in firmware without contactor mechanical actuation time.

• Protection action is faster

• Saves contactors

• Reduces points of failure

SAFETY FUNCTION

E710

Emergency Stop Controller Contactor 1 Contactor 2 Drive Motor

Emergency Stop Controller Motor

20 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Predictive diagnosis — page 21

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 21

  1. System Protection

Predictive Diagnosis — Advance Warning Before Drive Failure

The TECO E710 includes Predictive Diagnosis as standard. This is a continuous monitoring function that tracks the service life of two critical internal components and provides advance warning before either reaches the point of failure.

Monitored Components

The TECO E710 monitors the following components continuously from the moment power is first applied:

• Internal cooling fan: the drive monitors fan performance and generates a maintenance advisory before end of service life.

• DC bus electrolytic capacitors: the drive monitors capacitor condition and generates a maintenance advisory before end of service life.

These are the two components most likely to cause an unplanned drive failure as the unit ages. The drive tracks both parameters from first power-on and generates the advisory while the drive is still operating normally — not after the failure has already occurred.

SYSTEM PROTECTION

Service life prediction of main parts

Monitors the deterioration status of main part service life (fans, electrolytic capacitors, etc.) and immediately notifies replacement time to ensure continuous and stable operation of the equipment.

Fault warning and diagnosis functions

• Inverter life prediction diagnosis

• Multiple protection and alarm functions ensure stable operation of equipment

• Running state

• Real-time motor protection monitoring

TECO E710 | 21

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Catalogue — Motor protection — page 22

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 22

Early Warning vs No Warning

Where It Matters Most

• Any production environment where unplanned downtime has a measurable cost. The advance warning converts reactive emergency response into planned maintenance action.

• Remote and unmanned sites — water treatment plants, pump stations, irrigation systems, car park ventilation — where a drive failure triggers an extended response time before anyone attends site. Predictive Diagnosis means the advisory arrives before the failure, not after.

Motor Protection — PM Demagnetisation and IM Fault Detection

In addition to protecting the drive itself, the TECO E710 includes two motor protection functions that monitor the condition of the connected motor and provide advance warning before motor damage occurs.

PM Motor Demagnetisation Prevention

Demagnetisation is irreversible — the motor cannot be restored to rated performance without rotor replacement.

The TECO E710 monitors operating conditions and modulates output before the rotor temperature approaches the demagnetisation threshold. This protection operates in all PM control modes (PM SV and PM SLV) and prevents the condition that causes permanent motor damage.

Induction Motor Winding Fault Detection

Winding faults in induction motors — inter-turn shorts, insulation degradation, or early-stage winding breakdown — typically develop gradually rather than appearing suddenly.

The TECO E710 monitors the motor current signature for indicators of early-stage winding faults. When a fault condition is detected, the drive generates a pre-fault warning before the fault deteriorates to a motor failure event. This gives the maintenance team time to schedule a motor inspection and, if necessary, arrange a motor replacement or rewind during a planned stop — rather than responding to an unplanned motor failure.

Motor and drive protection combined

The TECO E710’s motor protection functions (PM demagnetisation prevention and IM winding fault detection) work alongside Predictive Diagnosis (drive component monitoring) to provide a comprehensive picture of both drive and motor health. This combination gives the maintenance team early warning of potential failures in both the drive and the motor it controls.

SYSTEM PROTECTION

22 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Supplier benefit statements do not establish engineering suitability.

Predictive diagnosis comparison — PDF page 22

Without predictive diagnosis With TECO E710 predictive diagnosis
Drive fails without warning. Production stops immediately. Drive generates a maintenance advisory. Planned stop is scheduled. Production continues.
Emergency callout, overtime labour, express parts freight. Replacement component ordered during normal lead time. Work carried out at normal labour rates and working hours.
Root cause unknown at the moment of failure. Diagnosis takes time. Component identified by the drive before failure. Fast, accurate repair. Known cause.
Reactive maintenance. No historical data. Failure may repeat. Predictive maintenance. Component service life tracked from first power-on. Failure prevented.
Unplanned downtime cost typically exceeds the cost of the drive itself. Downtime cost reduced to a scheduled stop — at a time of your choosing.

Catalogue — Standard S wiring diagram — page 23

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 23

Wiring Diagram (TECO E710 Standard S type) 403~410 / 202~203

The wiring diagram of the TECO E710 inverter standard model ( indicates the main circuit terminal / indicates the control circuit terminal). The position and symbols of the wiring terminal socket of the TECO E710 varies slightly depending on the model.

Note

*1: Use SW5 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multifunction digital input terminals S1~S7.

*2: Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for multifunction analog input 1/2 (AI1/AI2).Besides please also check parameter 04-00 for proper setting.

*3: When S7 is used as pulse input, connecting an external resistor is unnecessary due to the built-in pull-up resistor.

*4: The safety input contacts F1&F2 are short-circuited to the SG inverter for normal output. When using safety input, remove the short-circuit wires between F1-SG and F2-SG.

*5: AO1/AO2 presets a 0~10V output can be set to voltage output (0~10V) or current output (4~20mA) through switch SW1/SW2 to match parameter settings.

*6: When DO2 uses pulse output functions, pull-up resistance is recommended to be 200Ω.

SYSTEM PROTECTION

TECO E710 | 23

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Context: Visible wiring labels are grouped by their source location; the text does not reconstruct wiring topology. Wiring topology is not reconstructed; refer to original circuit and model-specific installation instructions.

Table conditions: Standard S type 403–410 / 202–203. Model-specific labels only; no inferred wiring topology. Dimensions/ratings are not transferred between S and E types. Printed notes retained separately.

Visible wiring-diagram annotations — Standard S type 403–410 / 202–203 — PDF page 23

Printed terminal/label group Visible annotation
Main circuit labels Main circuit power; R/L1, S/L2, T/L3; NFB; MC; External high-speed fuse; P, BR; Brake Resistor; U/T1, V/T2, W/T3; M; E
Grounding annotation Type 3 grounding resistance 100Ω or less
S1 factory setting Forward operation/stop
S2 factory setting Reverse operation/stop
S3 factory setting Multi-speed command 1
S4 factory setting Multi-speed command 2
S5 factory setting Multi-speed command 3
S6 factory setting Failure reset
S7 factory setting Jog command
SW5 source/sink Source (PNP); Sink (NPN), default factory setting
24V / 24VG Digital signal power terminal (PNP) / Digital signal common terminal (NPN)
S7 pulse annotation Multi-function contact input 7; Pulse input 32K Hz. Max.
+10V analog input power +10V, 20mA
AI1 multi-function analog input -10~10V / 0~10V, 500KΩ / 4~20mA, 500Ω
AI2 multi-function analog input 0~10V, 900KΩ / 4~20mA, 250Ω
GND Analog signal common terminal
V/I switches AI1 SW3; AI2 SW4; AO1 SW1; AO2 SW2
AO1 / AO2 / GND Analog signal output 1, 2; DC 0~10V / 4~20mA
CN3 Optional expansion card slot (PG card/Communication card)
R1A / R1B / R1C Multi-function relay output; 250VAC, 1A or less; 30VDC, 1A or less; Default setting: Fault indication
DO1 / DOG Multi-function optocoupler output 1; DC 48V/50mA, Open Collector; Default setting: Operation duration
DO2 / DOG Multi-function optocoupler output 2; DC 48V/50mA, Open Collector; Default setting: Operation duration; Multi-function pulse output (32k Hz. Max.)
SF1 / SG / SF2 Safety input contact
CN2 (RJ45), RS485 SGND, A, B; Pin1 to Pin8: 1 S(+), 2 S(-), 3 S(+), 4 Reserved, 5 Reserved, 6 S(-), 7 5V, 8 GND
Drawing legend Screened Cable, Twisted Pair (P); Screened Cable, Terminal symbol; main circuit symbol; control circuit symbol

Catalogue — DECORATIVE_PHOTO — page 24

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 24

This page contains no separately transcribed product values. The original illustration or source page remains the authority for its visual content.

Catalogue — Simple E wiring diagram — page 25

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 25

Wiring Diagram (TECO E710 Simple E type) 401~402/2P5~201

The wiring diagram of the TECO E710 inverter simple model ( indicates the main circuit terminal / indicates the control circuit terminal). The position and symbols of the wiring terminal socket of the TECO E710 varies slightly depending on the model.

Note

*1: Use SW5 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multifunction digital input terminals S1~S6.

*2: Use SW3 to switch between voltage (0~10V) and current (4~20mA) input for multifunction analog input 1 (AI1). Besides please also check parameter 04-00 for proper setting.

*3: AO1/AO2 presets a 0~10V output can be set to voltage output (0~10V) or current output (4~20mA) through switch SW1/SW2 to match parameter settings.

SYSTEM PROTECTION

TECO E710 | 25

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Context: Visible wiring labels are grouped by their source location; the text does not reconstruct wiring topology. Wiring topology is not reconstructed; refer to original circuit and model-specific installation instructions.

Table conditions: Simple E type 401–402 / 2P5–201. Model-specific labels only; no inferred wiring topology. Dimensions/ratings are not transferred between S and E types. Printed notes retained separately.

Visible wiring-diagram annotations — Simple E type 401–402 / 2P5–201 — PDF page 25

Printed terminal/label group Visible annotation
Main circuit labels Main circuit power; R/L1, S/L2, T/L3; NFB; MC; External high-speed fuse; P, BR; Brake Resistor; U/T1, V/T2, W/T3; M; E
Grounding annotation Type 3 grounding resistance 100Ω or less
S1 factory setting Forward operation/stop
S2 factory setting Reverse operation/stop
S3 factory setting Multi-speed command 1
S4 factory setting Multi-speed command 2
S5 factory setting Failure reset
S6 factory setting Jog command
SW5 source/sink Source (PNP); Sink (NPN), default factory setting
24V / 24VG Digital signal power terminal (PNP) / Digital signal common terminal (NPN)
+10V analog input power +10V, 20mA
AI1 multi-function analog input 0~10V, 180KΩ / 4~20mA, 250Ω
GND Analog signal common terminal
V/I switches AI1 SW3; AO1 SW1; AO2 SW2
AO1 / AO2 / GND Analog signal output 1, 2; DC 0~10V / 4~20mA
R1A / R1B / R1C Multi-function relay output; 250VAC, 1A or less; 30VDC, 1A or less; Default setting: Fault indication
DO1 / DOG Multi-function optocoupler output 1; DC 48V/50mA, Open Collector; Default setting: Operation duration
CN2 (RJ45), RS485 SGND, A, B; Pin1 to Pin8: 1 S(+), 2 S(-), 3 S(+), 4 Reserved, 5 Reserved, 6 S(-), 7 5V, 8 GND
Drawing legend Screened Cable, Twisted Pair (P); Screened Cable, Terminal symbol; main circuit symbol; control circuit symbol

Catalogue — Catalogue code and model list — page 26

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 26

CATALOGUE NUMBER IDENTIFICATION

  1. Catalogue Number Identification

E710 2 01 H 1 S F

Input Voltage kW Rating equivalents Type Power Supply E: Basic Noise Filter

2: 200V~240V 4: 380V~480V P5: 0.37kW (0.5 HP) 01: 0.75 kW (1.0 HP) 02: 1.5 kW (2.0 HP) 03: 2.2 kW (3.0 HP) 05: 3.7 kW (5.0 HP) 08: 5.5 kW (7.5 HP) 10: 7.5 kW (10 HP)

Blank : None H: LED Keypad 1: Single-Phase 3: Three-Phase 401~402 2P5~201 Blank: None F: Built-in

S: Standard

403~410 202~208

Full Model List

All standard TECO E710 catalogue numbers, input ratings, and frame sizes.

26 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Context: Catalogue-number legend remains literal source text with bounded provenance. Standard range here403–410/202–208 differs from overview403–430/202–220 and wiring403–410/202–203. Do not generate unseen model combinations.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Only ten explicit models; code legend does not authorise additional combinations.

Table conditions: Example E710 2 01 H 1 S F. Printed code components retained; not a Cartesian list of offered combinations. Only the separate full model list establishes explicitly listed models.

Full model list — PDF page 26

Model no. Output power kW Supply voltage V 50/60Hz Rated current A Frame size IP rating
E710-2P5-H1EF 0.37 200 – 240V 1ph 2.8 Frame 1 IP20
E710-201-H1EF 0.75 200 – 240V 1ph 4.8 Frame 1 IP20
E710-202-H1SF 1.5 200 – 240V 1ph 7.5 Frame 2 IP20
E710-203-H1SF 2.2 200 – 240V 1ph 11 Frame 2 IP20
E710-401-H3EF 0.75 380 – 480V 3ph 2.7 Frame 1 IP20
E710-402-H3EF 1.5 380 – 480V 3ph 4.2 Frame 1 IP20
E710-403-H3SF 2.2 380 – 480V 3ph 5.5 Frame 2 IP20
E710-405-H3SF 3.7 380 – 480V 3ph 9 Frame 2 IP20
E710-408-H3SF 5.5 380 – 480V 3ph 13 Frame 3 IP20
E710-410-H3SF 7.5 380 – 480V 3ph 17 Frame 3 IP20

Catalogue-number legend — separate printed code columns — PDF page 26

Example code and heading Printed meaning
2 — Input Voltage 2: 200V~240V; 4: 380V~480V
01 — kW Rating equivalents P5: 0.37kW (0.5 HP); 01: 0.75kW (1.0 HP); 02: 1.5kW (2.0 HP); 03: 2.2kW (3.0 HP); 05: 3.7kW (5.0 HP); 08: 5.5kW (7.5 HP); 10: 7.5kW (10 HP)
H — Type Blank: None; H: LED Keypad
1 — Power Supply 1: Single-Phase; 3: Three-Phase
S — Type range E: Basic — 401~402, 2P5~201; S: Standard — 403~410, 202~208
F — Noise Filter Blank: None; F: Built-in

Catalogue — DECORATIVE_PHOTO — page 27

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 27

This page contains no separately transcribed product values. The original illustration or source page remains the authority for its visual content.

Catalogue — DECORATIVE_PHOTO — page 28

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 28

This page contains no separately transcribed product values. The original illustration or source page remains the authority for its visual content.

Catalogue — Dimensions — page 29

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 29

DIMENSIONS

  1. Dimensions

Use the dimensions below for panel and cabinet design. All measurements in millimetres. Net weight in kilograms. IP20 enclosure. Refer to the installation manual for mounting hole layout.

Built-in filter type

220V : 0.37-0.75KW / 440V : 0.75-1.5KW

220V : 1.5-2.2KW / 440V : 2.2-3.7KW

440V : 5.5-7.5KW

TECO E710 | 29

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Source prints D twice; second D column holds M4. Literal heading retained rather than assuming a diameter/thread meaning. Refer manual for mounting hole layout.

Built-in filter dimensions / 220V0.37–0.75kW /440V0.75–1.5kW — PDF page 29

Catalog no. W mm H mm D mm W1 mm H1 mm T mm Second printed D (M4 values) Net weight kg
E710-2P5-H1EF 72 169.5 195.5 60 156 1.2 M4 1.9
E710-201-H1EF 72 169.5 195.5 60 156 1.2 M4 1.9
E710-401-H3EF 72 169.5 195.5 60 156 1.2 M4 1.9
E710-402-H3EF 72 169.5 195.5 60 156 1.2 M4 1.9

Built-in filter dimensions / 220V1.5–2.2kW /440V2.2–3.7kW — PDF page 29

Catalog no. W mm H mm D mm W1 mm H1 mm T mm Second printed D (M4 values) Net weight kg
E710-202-H1SF 87 184 207 73 171 1.2 M4 2.4
E710-203-H1SF 87 184 207 73 171 1.2 M4 2.4
E710-403-H3SF 87 184 207 73 171 1.2 M4 2.4
E710-405-H3SF 87 184 207 73 171 1.2 M4 2.4

Built-in filter dimensions / 440V5.5–7.5kW — PDF page 29

Catalog no. W mm H mm D mm W1 mm H1 mm T mm Second printed D (M4 values) Net weight kg
E710-408-H3SF 109 232 210 94 222.5 1.2 M4 3.6
E710-410-H3SF 109 232 210 94 222.5 1.2 M4 3.6

Catalogue — Accessories — page 30

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 30

ACCESSORIES AND PART NUMBERS

  1. Accessories and Part Numbers

30 | TECO Australia and New Zealand | teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Distinct modules and cards remain separate even where protocols match.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Only original shared group/description cells expand across rows.

Accessories / individual entries — PDF page 30

Accessories Catalog no. Description
710 Series Copy Module JN7-CU Stores the complete parameter set from one TECO E710 drive. Writes the stored set to other TECO E710 units of the same model in a single operation. Eliminates repeated manual programming on multi-drive installations. Does not function as an operator panel. Refer to the TECO E710 instruction manual for the operating procedure.
Profibus DP Communication Module JN5-CM-PDP Development of the JN5-CM-PDP module is for Profibus-DP factory automation applications.
TCP-IP Communication Module JN5-CM-TCPIP For communicating with devices such as inverters/servo drives that support RS485 communication protocols to achieve remote control.
DeviceNet Communication Module JN5-CM-DNET Applicable in automatic control systems using DeviceNet industrial network communication protocols and enables E710 series inverters without DeviceNet functions to run on the DeviceNet network.
CANopen Communication Module JN5-CM-CAN Applicable in automatic control systems adopting CANopen industrial network communication protocols, so that E710 series inverters can run on the CANopen network.
RJ45 to USB Communication cable (1.8m) JN5-CM-USB Converts USB communication formats to RS485 communication formats, allowing communication control between the inverter and PC (or other control equipment with USB interfaces), diversifying inverter control.
Profinet Communication Card JN7-CMCS-PFNET Applicable in automatic control systems adopting Profinet industrial network communication protocols, so that E710 series inverters can run on the Profinet network.
OPC UA Communication Card JN7-CMCS-OPCUA Applicable in automatic control systems adopting OPC UA industrial network communication protocols, so that E710 series inverters can run on the OPC UA network, and support data exchange with upper-level monitoring systems.
EtherCAT Communication Card JN7-CMCS-ECAT Applicable in automatic control systems adopting EtherCAT industrial network communication protocols, so that E710 series inverters can run on the EtherCAT network, achieving high-speed and real-time communication control.
MODBUS TCP Communication Card JN7-CMCS-MBTCP Applicable in automatic control systems adopting MODBUS TCP industrial network communication protocols, so that E710 series inverters can run on the MODBUS TCP network.
Ethernet IP Communication Card JN7-CMCS-EIP Applicable in automatic control systems adopting EtherNet/IP industrial network communication protocols, so that E710 series inverters can run on the EtherNet/IP network.
BACnet IP Communication Card JN7-CMCS-BACIP Applicable in building automation systems adopting BACnet IP industrial network communication protocols, so that E710 series inverters can run on the BACnet IP network and integrate with building management systems.
EtherCAT Communication Card JN7-CMHI-ECAT Applicable in automatic control systems adopting EtherCAT industrial network communication protocols, so that E710 series inverters can run on the EtherCAT network, achieving high-speed and real-time communication control.
CANopen Communication Card JN7-CMHI-CAN Applicable in automatic control systems adopting CANopen industrial network communication protocols, so that E710 series inverters can run on the CANopen network.
Profibus DP Communication Card JN7-CMHI-PDP Development of the JN7-CMHI-PDP communication card is for Profibus DP factory automation applications.

Operator extension cables — PDF page 30

Accessories Length / frame Catalog no. Description
Digital Operator Extension Cable 1m JN5-CB-01M The digital operator can be detached from the inverter unit and operated remotely using a digitaloperator extension cable. Available in four lengths: 1m, 2m, 3m, and 5m.
Digital Operator Extension Cable 2m JN5-CB-02M The digital operator can be detached from the inverter unit and operated remotely using a digitaloperator extension cable. Available in four lengths: 1m, 2m, 3m, and 5m.
Digital Operator Extension Cable 3m JN5-CB-03M The digital operator can be detached from the inverter unit and operated remotely using a digitaloperator extension cable. Available in four lengths: 1m, 2m, 3m, and 5m.
Digital Operator Extension Cable 5m JN5-CB-05M The digital operator can be detached from the inverter unit and operated remotely using a digitaloperator extension cable. Available in four lengths: 1m, 2m, 3m, and 5m.

Catalogue — Accessories continued — page 31

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 31

ACCESSORIES AND PART NUMBERS

TECO E710 | 31

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Distinct modules and cards remain separate even where protocols match.

Table conditions: Literal source table. Keep all model, installation and protection qualifications; no missing ratings or applicability inferred. Only original shared group/description cells expand across rows.

Accessories / individual entries — PDF page 31

Accessories Catalog no. Description
TCP-IP Communication Card JN7-CMI-TCPIP For communicating with devices such as inverters/servo drives that support RS485 communication protocols to achieve remote control.
Speed Feedback Card JN7-PG-PMR Speed feedback card with TAMAGAWA Resolver.
Speed Feedback Card JN7-PG-L PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options.
Bluetooth Keypad JN5-OP-BTH For wireless remote connection to control the inverter, which can monitor the real- time status and diagnose faults quickly. Note: With the smartphone APP ”BT DriveLink”, it can be downloaded from Apple App Store or Google Play.
DIN RAIL Accessories (Frame 1&2) JN7-DIN-L01 For DIN RAIL Mounting (Frame 1 & 2 models only), it is recommended to purchase the DIN RAIL Accessory and install it beneath the inverter.

NEMA1 wiring boxes — PDF page 31

Accessories Length / frame Catalog no. Description
NEMA1 Wiring Box Frame 1 JN7-NK-E01 To upgrade protection to NEMA1 level, it is recommended to purchase a NEMA1 wiring box and install it below the inverter.
NEMA1 Wiring Box Frame 2 JN7-NK-E02 To upgrade protection to NEMA1 level, it is recommended to purchase a NEMA1 wiring box and install it below the inverter.
NEMA1 Wiring Box Frame 3 JN7-NK-E03 To upgrade protection to NEMA1 level, it is recommended to purchase a NEMA1 wiring box and install it below the inverter.

Catalogue — Regional contacts — page 32

TECO-E710-Variable-Speed-Drives.pdf · P017 · source page 32

TECO E710

Next Gen Compact Current Vector Control Variable Speed Drive

The information in this catalogue is subject to change without notice. © 2026 TECO Australia and New Zealand All Rights Reserved.

HEAD OFFICE AUSTRALIA

TECO Australia Pty Limited 335-337 Woodpark Road, Smithfield NSW 2164

P: +61 2 9765 8118 F: +61 2 9765 8185

E: sales.nsw@teco.com.au W: www.teco.com.au

VIC/TAS

TECO Australia Pty Limited 16 Longstaff Road,Bayswater VIC 3153

P: +61 3 9720 4411 E: vicsales@teco.com.au

WA

TECO Australia Pty Limited 18 Hazelhurst Street,Kewdale WA 6105

P: + 61 8 9479 4879 E: sales.wa@teco.com.au

NEW ZEALAND

TECO New Zealand Ltd 11 Container Drive, Rolleston, Canterbury 7614

P: + 64 3 271 8480 E: sales@teco.co.nz

TECO New Zealand Ltd 4 Autumn Place, Penrose, Auckland 1061

P: + 64 9 526 8480 E: sales@teco.co.nz

QLD

TECO Australia Pty Limited 50 Murdoch Circuit, Acacia Ridge QLD 4110

P: + 61 7 3373 9600 E: sales.qld@teco.com.au

SA/NT

TECO Australia Pty Limited

M: +61 423 480 965 P: +61 3 9720 4411 E: vicsales@teco.com.au

Context: TECO E710 catalogue ©2026 retained as a separate source. All supplier claims, model scopes, conditions and conflicts preserved. No current certification, engineering approval or installation topology inferred.

Context: Printed ©2026 and regional contact directory retained as historical source details, not verified current.

Manual — TECO E710 Series Instruction Manual — page 1

Manual reference: physical PDF page 1. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

INSTRUCTION MANUAL

TECO INVERTER

E710 Series

Cover product illustrations retained; no numeric ratings or applicability derived from pictured equipment.

Manual — 3.5.2.1 Main circuit ............................................................................................................................ 3-21 — page 3

Manual reference: physical PDF page 3. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.5.2.1 Main circuit ............................................................................................................................ 3-21

3.6 Inverter specifications ................................................................................................................. 3-23

3.7 Dimensions diagram ................................................................................................................... 3-29

3.7.1 Standard type .......................................................................................................................... 3-29

3.7.2 Built-in filter type (220V 0.5~3HP, 440V 1~10HP) ............................................................... 3-35

3.7.3 KEYPAD dimensions diagram ............................................................................................... 3-38

3.8 The appearance and component names of the E710 inverter ...................................................... 3-39

3.9 Disassembling steps of the E710 model ..................................................................................... 3-41

Chapter 4 Software index ......................................................................................................................... 4-1

4.1 Panel use ....................................................................................................................................... 4-1

4.1.1 Descriptions of panel functions ................................................................................................ 4-1

4.1.2 Show description ...................................................................................................................... 4-2

4.1.3 Functional structure of the LED seven-stage display screen .................................................... 4-5

4.1.4 Examples of button panel operations ........................................................................................ 4-6

4.1.5 Description of operation statuses .............................................................................................. 4-8

4.1.6 Appearance of the digital operator ........................................................................................... 4-9

4.1.7 Display method ....................................................................................................................... 4-10

4.1.8 Monitor mode ......................................................................................................................... 4-11

4.1.9 Advanced setting .................................................................................................................... 4-12

4.1.10 Automatic tuning display ........................................................................................................ 4-13

4.2 Parameters list ............................................................................................................................ 4-14

4.3 Descriptions of parameter functions ........................................................................................... 4-72

4.4 Built-in PLC Function Description ........................................................................................... 4-324

4.5 Modbus Communication Protocol Description ........................................................................ 4-337

Chapter 5 Fault Diagnosis and Troubleshooting .................................................................................... 5-1

5.1 General Overview ......................................................................................................................... 5-1

5.2 Fault Detection Function .............................................................................................................. 5-1

5.3 Warning / Self-Diagnosis Detection Function .............................................................................. 5-6

5.4 Auto tuning error ........................................................................................................................ 5-16

5.5 PM Motor Auto Tuning Error ..................................................................................................... 5-16

5.6 General troubleshooting methods ............................................................................................... 5-17

5.7 Troubleshooting steps ................................................................................................................. 5-18

5.7.1 Basic inverter fault troubleshooting ........................................................................................ 5-18

5.7.2 OC, OL fault troubleshooting ................................................................................................. 5-20

5.7.3 OV, LV fault troubleshooting .................................................................................................. 5-21

5.7.4 Motor abnormality troubleshooting ........................................................................................ 5-22

5.7.5 Motor overheating cause troubleshooting ............................................................................... 5-23

5.7.6 Motor uneven operation cause troubleshooting ...................................................................... 5-24

Manual — 5.8 Daily and periodic inspection checklist ...................................................................................... 5-25 — page 4

Manual reference: physical PDF page 4. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.8 Daily and periodic inspection checklist ...................................................................................... 5-25

5.9 Maintenance ............................................................................................................................... 5-26

Chapter 6 Peripheral Devices and Optional Items ................................................................................ 6-1

6.1 Brake Resistor List ....................................................................................................................... 6-1

6.2 AC Reactor ................................................................................................................................... 6-2

6.3 Noise filter .................................................................................................................................... 6-5

6.4 Input Power Side Fuse Ratings ..................................................................................................... 6-7

6.5 Others ........................................................................................................................................... 6-8

6.6 NEMA1 Wiring Box ..................................................................................................................... 6-9

6.7 DIN RAIL Accessories ................................................................................................................. 6-9

6.8 RJ45 to USB Cable ....................................................................................................................... 6-9

6.9 PROFIBUS High-Speed Communication Expansion Module ................................................... 6-10

6.10 CANopen High-Speed Communication Expansion Card ........................................................... 6-19

6.11 Introduction to the EtherCAT High Speed Communication Expansion Module ........................ 6-32

6.12 Introduction to the TCP/IP Communication Expansion Module ................................................ 6-37

6.13 Communication Interface Modules ............................................................................................ 6-38

Chapter 7 Appendix A: UL Instructions .............................................................................................. 7-1

Préface .................................................................................................................................................. 7-3

Chapitre 8 Consignes de sécurité .............................................................................................................. 8-1

Appendix A:Product Documentation Appendix ................................................................................... A-1

Appendix B:CDM losses and efficiency table ........................................................................................B-1

Manual — Chapter 1 Safety Precautions — page 5

Manual reference: physical PDF page 5. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 1 Safety Precautions

1.1 Before supplying the power

Warning  The terminals of the main circuit need to be wired correctly; the single-phase (R/L1 and S/L2)/three-

phase (R/L1, S/L2, T/L3) are the power input terminals, and absolutely must not be mixed with U/T1, V/T2 and W/T3. When they are mixed, supplying power will damage the inverter.

Caution  The power voltage used must be the same specifications as the input voltage of the inverter. When moving the inverter, do not lift it by the front cover directly. The inverter should be moved by moving it from the body of the inverter itself to prevent the front cover from calling off, and causing the inverter to fall and resulting in personnel injuries or inverter damages.  Please install the inverter on metal or other non-combustible materials; do not install in on or near

flammable materials to prevent fires from occurring.  If multiple inverters are placed in the same control plan, please install additional cooling fans to keep

the temperature within the control panel below 40°C (under 50°C if there is no dust-proof covers) to prevent overheating or fire.  Please disassemble or install the operator after switching off the power, and operate and fix the

operator in place by following the diagram to prevent poor contact and causing the operator to malfunction or do not display.

Warning  This product complies with the IEC 61800-3 restricted area usage level. When this product is used

under certain environments, it may cause electromagnetic interference; therefore, please perform appropriate testing and make sure to ground it properly before use.  Motor over-temperature protection function is provided.

Caution  The installation and usage of the product must be performed by professional electricians with proper

qualifications.  The installation of the product must be performed with fixed wiring methods.

1.2 Wiring

Warning  Before implementing any inverter installation or wiring, please make sure to switch off the master

power to prevent electric shocks and fires. The wiring engineering personnel must have the relevant professional knowledge to prevent electric shocks and fires. Make sure that the grounding wire is connected to earth properly. (220V class: The grounding impedance must be less than 100 ohms; 440V class: The grounding impedance must be less than 10 ohms). Please ground the inverter in accordance with the requirements of the EN61800-5-1 specifications. The cable size may need to reach at least 10mm2 (6AWG) in order to meet the standard for limiting leakage current.  Make sure the ground the grounding terminal of the inverter properly. If it is not grounded correctly,

please make sure to unplug the ground cable of the control board to prevent surges from damaging the electronic components.  The RCD must meet the protection specifications of type-B leakage current.  After wiring is complete, confirm that the emergency stop function is effective. (Wiring is the

responsibility of the user)  Please do not touch the input/output power cable directly, and prevent all wiring from coming in

contact with the outer case of the inverter, as well as short-circuits.  Do not perform Hipot test to the inverter as doing so can easily damage the semiconductor components.

Manual — Caution  Confirm that the input master power complies with the inverter to prevent injuries or fires.  Please connect the braking resistor and braking unit in — page 6

Manual reference: physical PDF page 6. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Caution  Confirm that the input master power complies with the inverter to prevent injuries or fires.  Please connect the braking resistor and braking unit in accordance with the relevant wiring diagram,

otherwise it may cause fire hazards.  Please tighten the terminal screws in accordance with the specified torque to prevent fire hazards.  Do not connect the input power to the output terminal of the inverter.  Do not connect the electromagnetic contactors or magnetic switch contacts to the output terminal.  Do not connect the power factor correction capacitors or LC/RC filters to the output circuit.  Make sure that the interference generated by the inverter and motor will not affect the surrounding

sensors or devices.

1.3 Before operation

Warning  Please verify that the model capacity of the inverter and the model capacities set for the functional

parameters 13-00 of the inverter are consistent before connecting the power.  If the length of the cable between the inverter and motor is more than 25 meters, the carrier frequency

(parameter 11-01) must be reduced or an output filter needs to be installed to suppress over-voltage or oscillation at the load side, in order to prevent motor damage.

1.4 Parameter setting

Caution  Do not connect the motor to the load (mechanical equipment) when performing rotational automatic

tuning.  The motor will rotate when performing rotational automatic tuning; confirm the space around the

motor to prevent causing danger.

1.5 Operate

Warning  Please confirm that the front cover is installed before turning on the power.  Do not connect or disconnect the motor unit while the inverter is operating, as this may cause an over-

current trip; this may even damage the main circuit of the inverter in severe cases.  Do not get close to the machine when reseting functions as the machine will restart after the

malfunction is eliminated.  Do not operate the machine while both hands are wet.  Provide an independent emergency stop switch; this switch is activated when the function parameter

is set (please refer to 11-55).  Provide an independent external hardware emergency switch so that the inverter output can be shut

down immediately in case of danger.  Please make sure that the operation command is off before resetting warnings.  If automatic restart (07-00) after power is restored is selected, the inverter will restart after power is

restored.  Please confirm the status of the surrounding systems and mechanical devices before performing

automatic tuning to ensure personnel safety.  Avoid touching the relevant terminals regardless of whether the inverter is operating or stopped to

prevent danger.  The fan may still rotate for a while even after the power is disconnected.

Caution  Please do not touch the heating components such as the heat sink and brake resistor.  The inverter can easily make the motor operate from low-speed to high-speed; please confirm the

Manual — allowable range of the motor and the machine.  Please pay attention to the relevant settings when using brake modules and other compatible products.  Please d — page 7

Manual reference: physical PDF page 7. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

allowable range of the motor and the machine.  Please pay attention to the relevant settings when using brake modules and other compatible products.  Please do not check the signals on the circuit boards while the inverter is operating.

Warning Avoid electric shocks! The DC capacitor inside the inverter will completely discharge 5 minutes after the power is disconnected; please disassemble or conduct inspections 5 minutes after the power is disconnected.

1.6 While inspecting, maintaining and replacing

Warning  Please confirm that the power is off and that the DC voltage is no more than 25 volts before performing

maintenance or inspection.  The inverter terminals contain high-voltage terminals; please do not touch them arbitrarily.  Make sure to install the protective cover while the power is on; also, please make sure to disconnect

the power through the breaker after the protective cover is removed.  Please do not allow people other than the designated professionals to perform maintenance, inspection

or replace components.

Caution  The inverter should be used in environments with an ambient temperature between 14° ~ 104 (140)°F

(-10 ~ +40 (60)°C) 95%RH without condensation, and make sure that are no water drips and metal dust in the surrounding environment.

1.7 Precautions when disposing the inverter

Caution

Please dispose of the inverter as industrial waste, and pay attention to the followings:  The electrolytic capacitors on the main circuit and those on the printed circuit boards of the inverter

may explode if incinerated.  Toxic gases may be produced when the plastic components of the inverter, such as its casing, are

incinerated.

Devices that contain electronic components cannot be processed with daily garbage; they must be recycled separately with electrical and electronic waste in accordance with the local regulations in effect.

1.8 Exemption from warranty liability Our warranty does not cover losses of opportunities caused to your company or the customers of your company due to failure of our company’s product, damages caused by products not made by our company, or the compensation of other businesses regardless of whether it is still within the warranty period or not.

Manual — Chapter 2 Nameplate and model number — page 8

Manual reference: physical PDF page 8. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 2 Nameplate and model number

2.1 Inverter nameplate

2.2 Model No.

The basic model is 2P5/201/401/402, Standard is the remaining models

Inverter model number

Input specifications

Output specifications

Safety model

UL and CE marks

E710 series

Input voltage:

2: 200V class

4: 400V class

Noise filter (RFI):

F: Built-in EMC filter

Blank: No filter

Power input:

1: Single-phase input

3: Three-phase input

Blank: Single/three-phase shared

Product type:

H: Standard type (LED operator)

C: Standard type (LCD operator

Blank: No operator.

Maximum applicable motor capacity:

F: Built-in

PRODUCT: E710-401-H3E; MOTOR RATING: 0.75kW; INPUT: AC 3PH 380-480V (+10%,-15%) 50/60Hz 2.8A; OUTPUT: AC 3PH 0-480V 0-599Hz 2.7A; MODEL: 11-701-43-2P7-000; IP20; SCCR: 5kA; IE2; P.L.: 2.8%; TECO Electric & Machinery Co., Ltd.

Example model: E710-401-H3EF. E: Basic; S: Standard. Maximum applicable motor capacity examples: P5: 0.5HP; 01: 1HP; 02: 2HP; 10: 10HP.

Manual — Models list: — page 9

Manual reference: physical PDF page 9. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Models list:

Exact source table with physical merged-cell scope; empty cell is blank, not inferred absence. All units and edition-specific conditions retained.

Models list — PDF page 9

Source row Inverter model (Standard model) Applicable voltage (Vac) Applicable frequency (Hz) Horse power (HP) Applicable motor (KW) Filter built-in included Filter built-in not included
1 E710-2P5- HE 1ph/3ph, 200~240V +10%/- 15% 50/60Hz 0.5 0.4 ⟦blank source cell⟧ ◎
2 E710-201- HE 1ph/3ph, 200~240V +10%/- 15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ◎
3 E710-202- HS 1ph/3ph, 200~240V +10%/- 15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ◎
4 E710-203- HS 1ph/3ph, 200~240V +10%/- 15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ◎
5 E710-2P5- H1EF 1ph, 200~240V +10%/- 15% 50/60Hz 0.5 0.4 ◎ ⟦blank source cell⟧
6 E710-201- H1EF 1ph, 200~240V +10%/- 15% 50/60Hz 1 0.75 ◎ ⟦blank source cell⟧
7 E710-202- H1SF 1ph, 200~240V +10%/- 15% 50/60Hz 2 1.5 ◎ ⟦blank source cell⟧
8 E710-203- H1SF 1ph, 200~240V +10%/- 15% 50/60Hz 3 2.2 ◎ ⟦blank source cell⟧
9 E710-205- H3S 3ph, 200~240V +10%/- 15% 50/60Hz 5 3.7 ⟦blank source cell⟧ ◎
10 E710-208- H3S 3ph, 200~240V +10%/- 15% 50/60Hz 7.5 5.5 ⟦blank source cell⟧ ◎
11 E710-401- H3E 3ph, 380~480V +10%/- 15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ◎
12 E710-402- H3E 3ph, 380~480V +10%/- 15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ◎
13 E710-403- H3S 3ph, 380~480V +10%/- 15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ◎
14 E710-405- H3S 3ph, 380~480V +10%/- 15% 50/60Hz 5 3.7 ⟦blank source cell⟧ ◎
15 E710-408- H3S 3ph, 380~480V +10%/- 15% 50/60Hz 7.5 5.5 ⟦blank source cell⟧ ◎
16 E710-410- H3S 3ph, 380~480V +10%/- 15% 50/60Hz 10 7.5 ⟦blank source cell⟧ ◎
17 E710-401- H3EF 3ph, 380~480V +10%/- 15% 50/60Hz 1 0.75 ◎ ⟦blank source cell⟧
18 E710-402- H3EF 3ph, 380~480V +10%/- 15% 50/60Hz 2 1.5 ◎ ⟦blank source cell⟧
19 E710-403- H3SF 3ph, 380~480V +10%/- 15% 50/60Hz 3 2.2 ◎ ⟦blank source cell⟧
20 E710-405- H3SF 3ph, 380~480V +10%/- 15% 50/60Hz 5 3.7 ◎ ⟦blank source cell⟧
21 E710-408- H3SF 3ph, 380~480V +10%/- 15% 50/60Hz 7.5 5.5 ◎ ⟦blank source cell⟧
22 E710-410- H3SF 3ph, 380~480V +10%/- 15% 50/60Hz 10 7.5 ◎ ⟦blank source cell⟧

Manual — Chapter 3 Ambient temperature and installation — page 10

Manual reference: physical PDF page 10. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 3 Ambient temperature and installation

3.1 Environment

The installation environment of the inverter has direct impact to the normal functioning and usage life of the inverter; therefore, the installation environment of the inverter must comply with the following conditions:

Installation location The product must be installed in an environment that is easy to operate, and avoid being exposed to the following environments:  Avoid direct sunlight exposure  Prevent exposure to rain or humid environments  Prevent exposure to oil mist and salt corrosion  Prevent exposure to corrosive liquids and gases  Prevent entering of dust, lint and metal particles  Prevent electromagnetic interference (Welding machines or power machinery)  Keep away from radioactive substances and flammable objects  Prevent vibrations (punch press); if it cannot be prevented; if unavoidable, install vibration-absorbing pads to reduce the impact

When multiple inverters are installed in parallel in the panel, please pay attention to the placement to ensure proper heat dissipation

Exact source table with physical merged-cell scope; empty cell is blank, not inferred absence. All units and edition-specific conditions retained.

Applicable environment — PDF page 10

Source row Property Value / condition
1 Protection category IP20 / NEMA 1
2 IP20 / UL OPEN TYPE: -10~50°C -10~60°C (must be used with reduced load)
3 NEMA 1 / UL TYPE 1: -10~40°C -10~50°C (must be used with reduced load)
4 Storage temperature -20~70°C
5 Humidity 5% to 95% relative humidity RH with no condensation or water droplets; non- condensing (In compliance with IEC60068-2-78 standards)
6 Vibration Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards)
7 Altitude It can operate with full load under altitude 1000m or less, and the rated current needs to be reduced by 1% every 100m for altitudes 1000m and above, with a maximum limit of 3000m

Manual — Terminal screw torque To comply with UL standards, when wiring the main circuit terminals, please use UL-approved copper wires (rated 75°C) and ring-type crimp — page 11

Manual reference: physical PDF page 11. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Terminal screw torque To comply with UL standards, when wiring the main circuit terminals, please use UL-approved copper wires (rated 75°C) and ring-type crimp terminals with the specifications shown in the table below (UL-compliant products). It is recommended to use the crimp terminals manufactured by NICHIFU Co., Ltd. as shown in the table below, and use the crimping tools recommended by the terminal manufacturer for crimping the terminals and insulating sleeves.

Exact source table with physical merged-cell scope; empty cell is blank, not inferred absence. All units and edition-specific conditions retained.

Terminal screw torque — PDF page 11

Source row Cable size mm2 (AWG) Terminal screw specifications Ring-type crimp terminal model Locking torque kgf.cm (in.lbs) Insulating sleeve model Crimping tool model
1 0.75 (18) M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
2 0.75 (18) M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
3 1.25 (16) M3.5 R1.25-3.5 8.2 to 10 (7.1 to 8.7) TIC 1.25 NH 1
4 1.25 (16) M4 R1.25-4 12.2 to 14 (10.4 to 12.1) TIC 1.25 NH 1
5 2 (14) M3.5 R2-3.5 8.2 to 10 (7.1 to 8.7) TIC 2 NH 1 / 9
6 2 (14) M4 R2-4 12.2 to 14 (10.4 to 12.1) TIC 2 NH 1 / 9
7 2 (14) M5 R2-5 22.1 to 24 (17.7 to 20.8) TIC 2 NH 1 / 9
8 2 (14) M6 R2-6 25.5 to 30.0 (22.1 to 26.0) TIC 2 NH 1 / 9
9 3.5/5.5 (12/10) M4 R5.5-4 12.2 to 14 (10.4 to 12.1) TIC 3.5/5.5 NH 1 / 9
10 3.5/5.5 (12/10) M5 R5.5-5 20.4 to 24 (17.7 to 20.8) TIC 3.5/5.5 NH 1 / 9
11 3.5/5.5 (12/10) M6 R5.5-6 25.5 to 30.0 (22.1 to 26.0) TIC 3.5/5.5 NH 1 / 9
12 3.5/5.5 (12/10) M8 R5.5-8 61.2 to 66.0 (53.0 to 57.2) TIC 3.5/5.5 NH 1 / 9
13 8 (8) M4 R8-4 12.2 to 14 (10.4 to 12.1) TIC 8 NOP 60
14 8 (8) M5 R8-5 20.4 to 24 (17.7 to 20.8) TIC 8 NOP 60
15 8 (8) M6 R8-6 25.5 to 30.0 (22.1 to 26.0) TIC 8 NOP 60
16 8 (8) M8 R8-8 61.2 to 66.0 (53.0 to 57.2) TIC 8 NOP 60
17 14 (6) M4 R14-4 12.2 to 14 (10.4 to 12.1) TIC 14 NH 1 / 9
18 14 (6) M5 R14-5 20.4 to 24 (17.7 to 20.8) TIC 14 NH 1 / 9
19 14 (6) M6 R14-6 25.5 to 30.0 (22.1 to 26.0) TIC 14 NH 1 / 9
20 14 (6) M8 R14-8 61.2 to 66.0 (53.0 to 57.2) TIC 14 NH 1 / 9
21 22 (4) M6 R22-6 25.5 to 30.0 (22.1 to 26.0) TIC 22 NOP 60/ 150H
22 22 (4) M8 R22-8 61.2 to 66.0 (53.0 to 57.2) TIC 22 NOP 60/ 150H
23 30/38 (3 / 2) M6 R38-6 25.5 to 30.0 (22.1 to 26.0) TIC 38 NOP 60/ 150H
24 30/38 (3 / 2) M8 R38-8 61.2 to 66.0 (53.0 to 57.2) TIC 38 NOP 60/ 150H
25 50 / 60 (1 / 1/ 0) M8 R60-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 60/ 150H
26 50 / 60 (1 / 1/ 0) M10 R60-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
27 70 (2/0) M8 R70-8 61.2 to 66.0 (53.0 to 57.2) TIC 60 NOP 150H
28 70 (2/0) M10 R70-10 102 to 120 (88.5 to 104) TIC 60 NOP 150H
29 80 (3/0) M10 R80-10 102 to 120 (88.5 to 104) TIC 80 NOP 150H
30 80 (3/0) M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H
31 100 (4/0) M10 R100-10 102 to 120 (88.5 to 104) TIC 100 NOP 150H
32 100 (4/0) M12 R100-12 143 to 157 (124 to 136) TIC 100 NOP 150H
33 100 (4/0) M16 R80-16 255 to 280 (221 to 243) TIC 80 NOP 150H

Manual — 3.2 Installation — page 12

Manual reference: physical PDF page 12. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.2 Installation

3.2.1

Installation space

(1) Please install the E710 inverter vertically and leave sufficient space to ensure cooling effects, as shown

in Figure 3.1.

Avoid installing it up-side down or horizontally.

(2) The multiple inverters are installed in parallel, please make sure the follow the installation configuration

in the figure below to ensure cooling effects.

(3) The cooling fins of the heat sink may reach temperatures up to 90°C during inverter operation.

Therefore, the mounting surface of the inverter must be made of materials capable of withstanding

relatively high temperatures. When the inverter is operating inside a distribution box, the environment

must be well-ventilated and the ambient temperature must not exceed +50°C.

X=The inverter capacity is 7.5HP(and below), the minimum rec-

ommended width is 30mm

▲Figure 3.1 Installation space of E710

When C≥30mm, the allowed maximum ambient temperature is 50°C.

When C=0mm, the allowed maximum ambient temperature is 40°C.

▲Figure 3.2 Installation space for multiple E710s installed in parallel

Right

Left

Top

Bottom

Figure3.1: top150mm; bottom150mm.

Figure3.2:150mm above and below each inverter.

Manual — 3.2.2 Appearance diagram and warning label information — page 13

Manual reference: physical PDF page 13. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.2.2 Appearance diagram and warning label information

Make sure to check the warning messages on the front outer cover of the inverter. Refer to Figure 3.2 below.

200V: 0.5-7.5HP/400V: 1-10HP

Figure 3.2 Warning labels

3.2.3 Disassembly and assembly of the product

Caution

The installation environment of the inverter has direct impact to the functions and usage

life of the inverter; therefore, the installation environment must be considered when installing

the E710 inverter:

• Ambient temperature: -10°C ~ +50°C (Models with the NEMA 1 panel installed externally:

-10°C ~ +40°C)

• Prevent exposure to rain, humidity, or direct sunlight.

• Prevent exposure to corrosive liquids or gases, dust, and metal particles.

• Avoid locations with vibration or electromagnetic interference.

• If multiple inverters are installed within the same control panel, please add cooling fans to

keep the ambient temperature around the inverters below 50°C.

The digital operator does not need to be disassembled when wiring the E710. Simply loosen the screws

on the outer cover of the terminal, remove the outer cover of the terminal and then wire the terminals

inside the inverter.

WARNING/AVERTISSEMENT. Risk of electrical shock. Shut off main power and wait for 10 minutes before servicing. Risque de choc électrique. Coupez l'alimentation principale et attendez 10 minutes avant l'entretien. CAUTION/ATTENTION. See manual before operation. Consultez le manuel avant l'utilisation.

Manual — 3.3 Wiring and precautions of inverter peripherals — page 14

Manual reference: physical PDF page 14. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3 Wiring and precautions of inverter peripherals

Caution

  1. Please do not touch the circuit or replace the components before the capacitors have completely

discharged after disconnecting the input power. 2. Do not perform wiring or disassemble the connectors inside the inverter while power is supplied. 3. Never connect the inverter output terminals U, V and W to the AC power. 4. The grounding terminal E of the inverter must be grounded. 5. Make sure to disconnect the grounding cable of the control panel when the inverter is not grounded or

connected to a floating grid. 6. Since semiconductor components can easily be damaged by high voltages, do not perform Hipot tests

to the internal components of the E710 inverter. 7. The CMOS ICs on the inverter’s control board are easily affected and damaged by static electricity.

Please do not touch the control board.

  1. Please refer to 3.5.1 of Chapter Three and select appropriate cable diameters when wiring; when the

wiring of the main circuit is long, consider the fact that voltage drop cannot exceed 2% of the rated voltage. passing through (A) × 10-3

  1. When the wiring between the inverter and motor is long, please reduce the carrier frequency

appropriately (parameter 11-01) appropriately.

To ensure peripheral safety, it is recommended to install a high-speed fuse on the input side of the inverter, especially for high-power systems. Please refer to the descriptions in 6.4 of Chapter Six for the specifications of the high-speed fuse adopted.

Manual — 3.3.1 Standard wiring example of E710 peripherals ■ Power ‧ Please confirm whether the voltage class is correct to — page 15

Manual reference: physical PDF page 15. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.1 Standard wiring example of E710 peripherals ■ Power ‧ Please confirm whether the voltage class is correct to

avoid damaging the inverter. ■ No fuse breaker (NFB) and residual current circuit breaker ‧ Please refer to the user manual and select a NFB with

appropriate rated current. ‧ Please do not use the NFB as the operate/stop control of

the inverter. ‧ When installing a residual current circuit breaker for

current leakage fault protection, select one with a sensitivity of 200ௗmA or higher and a trigger time of 0.1ௗseconds or longer (V-type) to prevent high frequency malfunctions.

■ Electromagnetic contactor ‧ An electromagnetic contactor is not required for general

use; however, it is required for functions such as external sequential control or automatic restart after power failure. ‧ Please avoid using electromagnetic contactors to

operate/stop the inverter directly whenever possible. ■ AC reactor ‧ An additional AC reactor can be installed to further

improve the power factor or suppress external surges. ■ High-speed fuse ‧ To ensure the safety of peripherals, make sure to add an

additional high-speed fuse. Please refer to the descriptions in the user manual for the fuse specifications. ■ Input-side noise filter ‧ A filter must be installed when there are inductive loads

affecting the inverter. The inverter meets EN55011 Class A, EN 61800-3 category C2 when the TECO special filter is used. ■ Inverter ‧ There is no phase sequence distinction among the input

terminals R, S, and T; they can be changed arbitrarily. ‧ Please ground the grounding terminal E properly. ■ Output-side noise filter ‧ Installing an additional dedicated noise filter on the

output-side of the inverter can reduce radiation interference and induction noise. ■ Motor ‧ When one inverter is used to drive multiple motors, the

rated current of the inverter must be greater than the total current when the motors operate simultaneously. ‧ The motor and inverter must be grounded separately.

Power

No fuse breaker

NFB

(and residual current circuit breaker)

Electromagnetic contactor

AC

Reactor

Input-side noise filter

Inverter

Output-side noise filter

Three-phase motor

High-speed fuse

Manual — 3.3.2 — page 16

Manual reference: physical PDF page 16. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.2

Pump wiring diagram

3.3.2.1 The wiring diagram of the pump voltage type pressure sensor

is as follows: (Applicable to simple version E)

Single pump operation:

Operation Switch

Pressure

Converter

-

+

PNP

SW5

NPN

V

I

SW3

Multiple pump operation:

E710 Single Pump Operation 00-02 = 1 (Control Circuit Terminal) 04-00 = 0 (0~10V); 10-00=0 (Target Source: Pump) 10-01 = 1 (Feedback Source: AI1) 10-03 = XXX1B (PID is enabled) 23-00 = 1 (PUMP); 23-01 = 0 (Single Pump)

E710 Multi-Pump Operation: Master 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=1 (Master)

E710 Multi-Pump Operation:Slave 1 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=2(Slave 1)

E710 Multi-Pump Operation: Slave 2 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=3(Slave 2)

E710 Multi-Pump Operation: Slave 3 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=4(Slave 3)

Manual — 3.3.2.2 The wiring diagram of the pump current type pressure sensor — page 17

Manual reference: physical PDF page 17. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.2.2 The wiring diagram of the pump current type pressure sensor

is as follows: (Applicable to simple version E)

Single pump operation:

Operation Switch

Pressure

Converter

SW5

NPN

V

I

PNP

SW3

Multiple pump operation:

主

機

副

Note 1: The position of the flip switch must be correct (SW3 and SW5).

Note 2: The power must be disconnected and then reconnected after setting the master/slave machine.

Note 3: 24VG and GND need to be short-circuited

Note 4: Choose 09-01=3 (PUMP parallel communication) for multi-pump parallel communication mode,

make sure that the 09-02 (baud rate setting) of the master and slave machines are consistent, and refer to

the descriptions of the 23-31 (multi-pump parallel synchronization selection) parameters to perform

parallel operation mode.

Note 5: Please note that the slave machine’s 04-02 (AI1 gain) = 252.0%.04 - 03 (AI1 bias) = -25.0%

(approximately ±5% adjustment) need to be adjusted when wiring the multi-pump current type pressure sensor.

Note 6: When operating multiple pumps, if any of the inverters do not supply power, the 24V of the

inverter also needs to be disconnected from the other inverters to avoid impedance effects.

E710 Single Pump Operation 00-02 = 1 (Control Circuit Terminal) 04-00 = 5 (4~20mA); 10-00=0 (Target Source: Pump) 10-01 = 1 (Feedback Source: AI1) 10-03 = XXX1B (PID is enabled) 23-00 = 1 (PUMP); 23-01 = 0 (Single Pump)

E710 Multi-Pump Operation: Master 00-02=1 (Control Circuit Terminal); 04-00=5 (4~20mA) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=1 (Master)

E710 Multi-Pump Operation: Slave 1 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=2(Slave 1)

E710 Multi-Pump Operation: Slave 2 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=3(Slave 2)

E710 Multi-Pump Operation: Slave 3 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=1 (Feedback Source: AI1) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=4(Slave 3)

Manual — 3.3.2.3 The wiring diagram of the pump voltage type pressure sensor — page 18

Manual reference: physical PDF page 18. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.2.3 The wiring diagram of the pump voltage type pressure sensor

is as follows: (Applicable to standard version S)

Single pump operation:

Operation Switch

Pressure

Converter

-

+

PNP

SW5

NPN

V

I

SW4

Multiple pump operation:

E710 Single Pump Operation 00-02 = 1 (Control Circuit Terminal) 04-00 = 0 (0~10V); 10-00=0 (Target Source: Pump) 10-01 = 2 (Feedback Source: AI2) 10-03 = XXX1B (PID is enabled) 23-00 = 1 (PUMP); 23-01 = 0 (Single Pump)

E710 Multi-Pump Operation: Master 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=1 (Master)

E710 Multi-Pump Operation: Slave 1 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=2(Slave 1)

E710 Multi-Pump Operation: Slave 2 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=3(Slave 2)

E710 Multi-Pump Operation: Slave 3 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=4(Slave 3)

Manual — 3.3.2.4 The wiring diagram of the pump current type pressure sensor — page 19

Manual reference: physical PDF page 19. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.2.4 The wiring diagram of the pump current type pressure sensor

is as follows: (Applicable to standard version S)

Single pump operation:

Operation Switch

Pressure

Converter

PNP

SW5

NPN

V

I

SW4

Multiple pump operation:

主

機

副

Note 1: The position of the flip switch must be correct (SW4 and SW5).

Note 2: The power must be disconnected and then reconnected after setting the master/slave machine.

E710 Single Pump Operation 00-02 = 1 (Control Circuit Terminal) 04-00 = 5 (4~20mA); 10-00=0 (Target Source: Pump) 10-01 = 2 (Feedback Source: AI2) 10-03 = XXX1B (PID is enabled) 23-00 = 1 (PUMP); 23-01 = 0 (Single Pump)

E710 Multi-Pump Operation: Master 00-02=1 (Control Circuit Terminal); 04-00=5 (4~20mA) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=1 (Master)

E710 Multi-Pump Operation: Slave 1 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=2(Slave 1)

E710 Multi-Pump Operation: Slave 2 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=3(Slave 2)

E710 Multi-Pump Operation: Slave 3 00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V) 10-00=0 (Target Source: Pump); 10-01=2 (Feedback Source: AI2) 10-03=XXX1b (PID is enabled); 23-00=1 (Pump); 23-01=4(Slave 3)

Manual — Note 3: 24VG and GND need to be short-circuited Note 4: Choose 09-01=3 (PUMP parallel communication) for multi-pump parallel communication mode, make sure that — page 20

Manual reference: physical PDF page 20. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note 3: 24VG and GND need to be short-circuited Note 4: Choose 09-01=3 (PUMP parallel communication) for multi-pump parallel communication mode, make sure that the 09-02 (baud rate setting) of the master and slave machines are consistent, and refer to the descriptions of the 23-31 (multi-pump parallel synchronization selection) parameters to perform parallel operation mode. Note 5: Please note that the slave machine’s 04-02 (AI1 gain) = 252.0%.04 - 03 (AI1 bias) = -25.0% (approximately ±5% adjustment) need to be adjusted when wiring the multi-pump current type pressure sensor. Note 6: When operating multiple pumps, if any of the inverters do not supply power, the 24V of the inverter also needs to be disconnected from the other inverters to avoid impedance effects.

Manual — 3.3.3 — page 21

Manual reference: physical PDF page 21. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Private-font unit U+F057 adjacent to input values is blank in both source renders; unit unresolved, no ohm expansion or capability inferred.

3.3.3

Wiring diagram (Applicable to simple version E)

The following is the wiring diagram of a simple model of the E710 inverter

(◎represents the main circuit terminals, and ○ represents the control circuit terminals); the

locations and symbols of the wiring terminal block may vary according to the different

E710 models. Please refer to the contents in the later chapters for descriptions on the main

circuit terminals and control circuit terminals.

MC

NFB

External high-speed fuse

P

BR

Brake Resistor

R/L1

S/L2

S1

S2

S6

S5

S4

S3

Analog output 1

Multi-

function

contact

input

24V

Digital signal power terminal (PNP)

24VG

Digital signal common terminal (NPN)

Failure reset

Forward operation/Stop

Multi-speed command 3

Source(PNP)

SW5

AO1

AO2

GND

E

Analog output 2

T/L3

U/T1

V/T2

W/T3

CN2 (RJ45)

GND analog signal common terminal

+10V Analog input power

AI1 Multi-function analog input

(0~10V, 500K

/

4~20mA, 500

)

M

R1A

R1B

R1C

+10V, 20mA

Main circuit power

Factory settings

External analog input

0~10V/4~20mA

0V

Sink (NPN), default factory

setting

Reverse operation/Stop

Multi-speed command 1

Multi-speed command 2

Type 3 grounding resistance

or less

Analog signal output 1, 2

DC 0~10V/4~20mA

Multi-function relay output

250VAC, 1A or less

30VDC, 1A or less

Multi-function optocoupler output 1

(DC 48V/50mA, Open Collector)

Surface-

mounted

isolation wire,

Surface-mounted shielded

twisted pair cable

Terminal symbol

Represents the

main circuit,

Represents

Control circuit

RS485

1 : S(+)

2 : S(-)

3 : S(+)

4 : Reserved

5 : Reserved

6 : S(-)

7 : 5V

8: GND

A

B

V

I

AI1

SW3

SW1

SW2

DOG

DO1

SGND

Notes:

*1: The multi-function digital input contacts S1~S6 can be set to Source (PNP, with +24V common) or Sink (NPN, with

24VG common) through switch SW5.

*2: The multi-function analog input AI1 can be set to voltage command input (0~10V) or current command input

(4~20mA) through switch SW3 and be used with parameter 04-00 settings.

*3: When using open collector input mode, no external resistor is required because a built-in pull-up resistor is provided.

*4: AO1 preset 0~+10V output, AO2 preset 0~+10V output.

Simple E diagram: +10V analog input power +10V,20mA. AI1:0~10V,500K[source unit glyph U+F057; blank in rendering] /4~20mA,500[source unit glyph U+F057; blank in rendering].

Manual — 3.3.4 — page 22

Manual reference: physical PDF page 22. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Private-font unit U+F057 adjacent to input values is blank in both source renders; unit unresolved, no ohm expansion or capability inferred.

3.3.4

Wiring diagram (Applicable to standard version S)

The following is the wiring diagram of a standard model of the E710 inverter

(◎represents the main circuit terminals, and ○ represents the control circuit terminals); the

locations and symbols of the wiring terminal block may vary according to the different

E710 models. Please refer to the contents in the later chapters for descriptions on the main

circuit terminals and control circuit terminals.

MC

NFB

External high-speed fuse

P

BR

Brake Resistor

R/L1

S/L2

S1

S2

S7

S6

S5

S4

S3

Analog output 1

Multi-

function

contact

input

24V

Digital signal power terminal (PNP)

24VG

Digital signal common terminal (NPN)

Failure reset

Forward

operation/Stop

Multi-speed

command 3

Jog command

Source(PNP)

SW5

AO1

AO2

GND

E

CN3

Analog output 2

T/L3

U/T1

V/T2

W/T3

CN2 (RJ45)

GND analog signal common

terminal

+10V Analog input power +10V, 20mA

AI1 Multi-function analog input

(-10~10V/0~10V, 500K

/

4~20mA, 500

)

AI2 Multi-function analog input

M

R1A

R1B

R1C

SG

SF2

Safety input contact

Main circuit power

Factory settings

External analog input

-10V~10V/4~20mA

4~20mA/0~10V

0V

Sink (NPN), default

factory setting

Reverse

command 1

command 2

Type 3 grounding resistance

or less

Analog signal output 1, 2

DC 0~10V/4~20mA

Optional expansion card slot

(PG card/Communication card)

Multi-function relay output

250VAC, 1A or less

30VDC, 1A or less

Multi-function optocoupler output 1

(DC 48V/50mA, Open Collector)

Multi-function optocoupler output 2

/Multi-function pulse output (32k Hz. Max.)

DO1

Surface-mounted

isolation wire,

Surface-mounted shielded

twisted pair cable

Terminal symbol

Represents the main

circuit,

Represents

Control circuit

RS485

1 : S(+)

2 : S(-)

3 : S(+)

4 : Reserved

5 : Reserved

6 : S(-)

7 : 5V

8: GND

A

B

V

I

AI1

SW3

SF1

AI2

SW4

SW1

SW2

DOG

DO2

Multi-function contact input 7

/ Pulse input 32K Hz. Max.

(0~10V, 900K

4~20mA, 250

SGND

Notes:

*1: The multi-function digital input contacts S1~S6 can be set to Source (PNP, with +24V common) or Sink (NPN, with 24VG common)

through switch SW5.

*2: The multi-function analog input AI1/AI2 can be set to voltage command input (0~10V/-10~10V) or current command input (4~20mA)

through switch SW3/SW4 and be used with parameter 04-00 settings.

*3: When using open collector input mode, no external resistor is required because a built-in pull-up resistor is provided.

*4: The inverter will only output normally when the safety input contacts SF1 and SF2 are short-circuited to SG. When using safety input,

make sure to remove the shorting cables between SF1-SG and SF2-SG.

*5: AO1 preset 0~+10V output, AO2 preset 0~+10V output.

*6:When DO2 uses the pulse out function, a pull-up resistor of 200 ohms is recommended

Standard S diagram: +10V analog input power +10V,20mA. AI1:-10~10V/0~10V,500K[source unit glyph U+F057; blank in rendering] /4~20mA,500[source unit glyph U+F057; blank in rendering]. AI2:0~10V,900K[source unit glyph U+F057; blank in rendering] /4~20mA,250[source unit glyph U+F057; blank in rendering].

Manual — 3.3.5 — page 23

Manual reference: physical PDF page 23. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3.5

Description of control circuit terminals (applicable to simple

version E)

220V: 0.5~1HP/440V: 1~2HP

3.3.6

Description of control circuit terminals (applicable to standard

version S)

220V: 2~7.5HP/440V: 3~10HP

Simple E terminal drawing: TB1 labels24V,S1,S2,S3,S4,S5,S6,24VG,DO1,DOG,A,B,SGND,E. TB2 labels+10V,GND,AI1,AO1,AO2,GND. TB3 labelsR1A,R1B,R1C. CN2:RS485. SW3(AI1),SW1(AO1),SW2(AO2):V/I;SW5:SOURCE/SINK.

Standard S terminal drawing: TB1 labelsR1A,R1B,R1C. TB2 labelsA,B,SGND,F1,SG,F2,+10V,GND,AI1,AI2,AO1,AO2,GND. TB3 labels24V,S1,S2,S3,S4,S5,S6,S7,24VG,DO1,DO2,DOG. CN2:RS485. SW3(AI1),SW4(AI2),SW1(AO1),SW2(AO2):V/I;SW5:SOURCE/SINK.

Manual — 3.4 Description of terminal functions (applicable to simple version E) — page 24

Manual reference: physical PDF page 24. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.4 Description of terminal functions (applicable to simple version E)

Table 3.4.1 Definitions of main circuit terminals

 Main circuit terminal configuration

220V: 0.5~1HP/440V: 1~2HP

220V: 2~7.5HP/440V:

3~10HP

FILTER terminal block terminal configuration 220V: 0.5~3HP/440V: 1~10HP

Smaller-frame main terminal labels:R/L1,S/L2,T/L3,U/T1,V/T2,W/T3,BR,P.

Larger-frame main terminal labels:R/L1,S/L2,T/L3,U/T1,V/T2,W/T3,BR,P and earth symbols.

FILTER terminal labels:L1,L2,L3 and earth symbols.

Exact source table with physical merged-cell scope; empty cell is blank, not inferred absence. All units and edition-specific conditions retained.

Table3.4.1 main circuit terminals;200V0.5–7.5HP/400V1–10HP — PDF page 24

Source row Terminal mark Function
1 R/L1 Main circuit power input (single-phase input, only connects to R-S) The FILTER model is locked on the filter terminal block L1, L2, L3, (single- phase input, only connects to L1 and L3)
2 S/L2 Main circuit power input (single-phase input, only connects to R-S) The FILTER model is locked on the filter terminal block L1, L2, L3, (single- phase input, only connects to L1 and L3)
3 T/L3 Main circuit power input (single-phase input, only connects to R-S) The FILTER model is locked on the filter terminal block L1, L2, L3, (single- phase input, only connects to L1 and L3)
4 P P-BR: External braking resistor
5 BR P-BR: External braking resistor
6 U/T1 Inverter output
7 V/T2 Inverter output
8 W/T3 Inverter output
9 E/PE/[earth symbol] Grounding terminal (type-three grounding)

Terminal screw size;220V0.5–1HP/440V1–2HP — PDF page 24

Source row T
1 M3.5

Terminal screw size;220V2–7.5HP/440V3–10HP — PDF page 24

Source row T Earth symbol
1 M4 M4

Manual — Table 3.4.2 Definitions of control circuit terminals (applicable to simple — page 25

Manual reference: physical PDF page 25. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 3.4.2 Definitions of control circuit terminals (applicable to simple

version E)

Exact source table with physical merged-cell scope; empty cell is blank, not inferred absence. All units and edition-specific conditions retained.

Table3.4.2 simple E digital inputs — PDF page 25

Source row Type Terminal Terminal functions
1 Digital input signal S1 Multi-function input terminal
2 Digital input signal S2 Multi-function input terminal
3 Digital input signal S3 Multi-function input terminal
4 Digital input signal S4 Multi-function input terminal
5 Digital input signal S5 Multi-function input terminal
6 Digital input signal S6 Multi-function input terminal
7 24V power supply 24V Common point of digital signal source
8 24V power supply 24VG Common point of digital signal sink

Table3.4.2 simple E analog and output terminals — PDF page 25

Source row Type Terminal Terminal functions
1 Analog input signal +10V Speed setting power
2 Analog input signal AI1 Multi-function analog input 1 can be switched between voltage or current input (0~10V)/(4-20mA)
3 Analog input signal GND Analog signal shared terminal
4 Analog input signal E Shielded cable connection terminal (earth)
5 Analog output signal AO1 Multi-function analog output terminal can be switched between voltage or current output (0~10V output)/(4-20mA output)
6 Analog output signal AO2 Multi-function analog output terminal can be switched between voltage or current output (0~10V output)/(4-20mA output)
7 Analog output signal GND Analog signal shared terminal
8 Digital output D01 Multi-function (open-collector transistor) output
9 Digital output DOG Open collector transistor shared terminal
10 Relay output R1A Relay A contact (multi-function output terminal)
11 Relay output R1B Relay B contact (multi-function output terminal)
12 Relay output R1C Relay shared terminal
13 RS-485 A RS485/MODBUS
14 RS-485 B RS485/MODBUS
15 RS-485 SGND Signal ground

Manual — Table 3.4.3 Definitions of control circuit terminals (applicable to standard — page 26

Manual reference: physical PDF page 26. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 3.4.3 Definitions of control circuit terminals (applicable to standard

version S)

Caution

‧ The maximum capacity of the terminal’s +10V output current is 20mA. ‧ The multi-function analog outputs A01 and A02 are analog outputs exclusively for connecting to ammeters;

please do not use them as analog output signals for feedback control, etc. ‧ The 24V and +10V power of the control panel are for internal control use only; do not connect them externally

to other devices for power supply.

Exact source table with physical merged-cell scope; empty cell is blank, not inferred absence. All units and edition-specific conditions retained.

Table3.4.3 standard S digital inputs — PDF page 26

Source row Type Terminal Terminal functions
1 Digital input Signal S1 Multi-function input terminal
2 Digital input Signal S2 Multi-function input terminal
3 Digital input Signal S3 Multi-function input terminal
4 Digital input Signal S4 Multi-function input terminal
5 Digital input Signal S5 Multi-function input terminal
6 Digital input Signal S6 Multi-function input terminal
7 Digital input Signal S7 Multi-function input terminal/optional pulse input, BW 32KHz
8 24V Power supply 24V Common point of digital signal source
9 24V Power supply 24VG Common point of digital signal sink

Table3.4.3 standard S analog and output terminals — PDF page 26

Source row Type Terminal Terminal functions
1 Analog input signal +10V Speed setting power
2 Analog input signal AI1 Multi-function analog input 1 can be switched between voltage or current input (0~10V)/(4-20mA)
3 Analog input signal AI2 Multi-function analog input 2 can be switched between voltage or current input (0~10V)/(4-20mA)
4 Analog input signal GND Analog signal shared terminal
5 Analog output signal AO1 Multi-function analog output terminal can be switched between voltage or current output (0~10V output)/(4-20mA output)
6 Analog output signal AO2 Multi-function analog output terminal can be switched between voltage or current output (0~10V output)/(4-20mA output)
7 Analog output signal GND Analog signal shared terminal
8 Digital output signal DO1 Multi-function (open-collector transistor) output
9 Digital output signal DO2 Multi-function (open collector transistor) output/switchable pulse output, BW 32KHz
10 Digital output signal DOG Open collector transistor shared terminal
11 Relay output R1A Relay A contact (multi-function output terminal)
12 Relay output R1B Relay B contact (multi-function output terminal)
13 Relay output R1C Relay shared terminal
14 Safety input F1 On: Operates freely with safety input; Off: General operation (Make sure to disconnect the short-circuit cable when stopping with an external safety switch)
15 Safety input F2 On: Operates freely with safety input; Off: General operation (Make sure to disconnect the short-circuit cable when stopping with an external safety switch)
16 Safety input SG Safety command shared terminal
17 RS-485 A RS485/MODBUS
18 RS-485 B RS485/MODBUS
19 RS-485 SGND Signal ground

Manual — 3.5 Appliances for wiring the main circuit and wiring precautions — page 27

Manual reference: physical PDF page 27. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.5 Appliances for wiring the main circuit and wiring precautions

3.5.1 Appliances for wiring the main circuit A no fuse breaker must be installed between the AC power supply and the power input terminals R, S, T of E710, and an electromagnetic contactor (MC) is installed as needed. When a residual current circuit breaker is installed for leakage fault protection, to prevent the residual current circuit breaker from malfunctioning, select one with a sensitivity current of 200mA or higher and a trigger time of 0.1 seconds or more.

Wiring specifications

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Main wiring specifications; E710 voltage/HP rows — PDF page 27

Source row Power Applicable HP *1 Rated current A Main circuit AWG(mm2) *2 Earth AWG(mm2) Control AWG(mm2) *3 No fuse breaker NFB *4 Electromagnetic contactor MC *4
1 200V 0.5HP 2.8 14~12 (2~3.5) 14~12 (2~3.5) 24~16 (0.2~1.5) TO-50EC(15A) CU-11
2 200V 1HP 4.8 14~12 (2~3.5) 14~12 (2~3.5) 24~16 (0.2~1.5) TO-50EC(15A) CU-11
3 200V 2HP 7.5 12~10 (3.5~5.3) 12~10 (3.5~5.3) 24~16 (0.2~1.5) TO-50EC(20A) CU-11
4 200V 3HP 11 10 (5.3) 10 (5.3) 24~16 (0.2~1.5) TO-50EC(30A) CU-11
5 200V 5HP 17 8 (8.4) 8 (8.4) 24~16 (0.2~1.5) TO-50EC(30A) CU-16
6 200V 7.5HP 25 8 (8.4) 8 (8.4) 24~16 (0.2~1.5) TO-100S(50A) CU-18
7 400V 3 Ø 1HP 2.7 14~12 (2~5.3) 14~12 (2~5.3) 24~16 (0.2~1.5) TO-50EC(15A) CU-11
8 400V 3 Ø 2HP 4.2 14~12 (2~5.3) 14~12 (2~5.3) 24~16 (0.2~1.5) TO-50EC(15A) CU-11
9 400V 3 Ø 3HP 5.5 14~10 (2~5.3) 14~10 (2~5.3) 24~16 (0.2~1.5) TO-50EC(15A) CU-11
10 400V 3 Ø 5HP 9 12~10 (3.5~5.3) 12~10 (3.5~5.3) 24~16 (0.2~1.5) TO-50EC(15A) CU-18
11 400V 3 Ø 7.5HP 13 10 (5.3) 10 (5.3) 24~16 (0.2~1.5) TO-50EC(20A) CU-18
12 400V 3 Ø 10HP 17 8 (8.4) 8 (8.4) 24~16 (0.2~1.5) TO-50EC(30A) CU-25

Manual — Pay attention to the following for external wiring: — page 28

Manual reference: physical PDF page 28. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Pay attention to the following for external wiring:

(A) Control circuit wiring:

(1) The control circuit wiring (control terminal) must be wired separately from the main circuit wiring

(R, S, T, U, V, W) and other power cables to avoid noise interference.

(2) The contact output terminals R1A, R1B, R1C must be wired separately from terminals ①~⑦, AO1,

AO2, GND, DO1, DO2, DOG, +10V, -10V, AI1, AI2 and GND.

(3) To prevent noise interference, shielded twisted-pair cables with isolation must be used for the control

circuit wiring. Please refer to the figure below; the wiring distance must not exceed 50m.

Figure 3.5 Handling condition of the shielded twisted pair cable

When connecting a multi-function photocoupler output to a relay, a flywheel diode must be connected in

parallel across the relay coil, as shown in the figure below.

Figure 3.6 Connect the optical coupling output contact to the inductive load

(B) Main circuit wiring:

(1) Phase sequence does not need to be considered for the input powers R, S and T.

(2) The input power cannot be connected to output terminals U, V and W of the inverter.

(3) Connect the output terminals U, V and W of the inverter to the U, V and W terminals of the motor.

If the forward command is executed on the inverter but the motor rotates in reverse, just swap any

two of the U, V and W cables of the motor.

(4) Do not connect the capacitors used to improve the power factor or the LC and RC noise filters to the

output terminal of the inverter.

g

Flywheel diode

(100V 100mA or more)

48V max.

50 mA max.

E710

External wiring circuit

Sheath

Shielded isolation cable

Connect to the control terminal E

of the inverter

Wrap with insulating tape

Do not connect this

end of the shielded

cable

Manual — (C) Grounding cable: — page 29

Manual reference: physical PDF page 29. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(C) Grounding cable:

(1) Ground the grounding terminal (E) with the type-three grounding method (connect to a grounding

resistance less than 100Ω)

(2) The grounding cable of the inverter must not be grounded together with the electric welding machine,

high horse power motor or other current loads; they must be grounded separately.

(3) The size of the grounding cable shall comply with the technical standards for electrical equipment,

and try to make the grounding cable as short as possible.

(4) When multiple inverters are grounded together, please refer to the figure below and do not for one

grounding circuit.

Figure 3.7 Grounding method for multiple E710s

◎ When deciding the cable size and choosing the cable, consider the voltage drops caused by the cables.

The formula for calculating voltage drop is as shown below; usually the voltage drop must be within

2% of the rated voltage

◎ Use AC reactor for series power coordination

When the power capacity exceeds 600kVA, please connect an AC reactor in series on the input-side of

the inverter. This AC reactor not only can be used for power coordination, it can also improve power

factors.

◎ Wiring length between the inverter and motor

When the total wiring distance between the inverter and motor is long, because of the high frequency

carrier frequency (the ON/OFF switching frequency of IGBT) of the inverter, the leakage current

between the wiring and earth will increase and affect the inverter itself and other peripherals.

Therefore, when the wiring distance between the inverter and motor is long, please reduce the carrier

frequency appropriately as shown in the figure below.

(a) Good

(b) Good

(c) Poor

Voltage drop between cables (V) = √3 × cable impedance (Ω/km) × wiring distance (m) × current (A) ×10^-3

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Motor cable distance and maximum carrier frequency — PDF page 29

Source row Parameter <30m 30m~50m 50m~100m >=100m
1 Allowable carrier frequency (the setting value of parameter 11-01) 16kHz(max) 10kHz(max) 5kHz(max) 2kHz(max)

Manual — 3.5.2 — page 30

Manual reference: physical PDF page 30. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.5.2

Terminal specification recommendations

3.5.2.1 Main circuit

Ring terminal size chart

Recommended vendor for the table below - K.S.TERMINALS INC. The part numbers are for reference only,

users may select any ring terminals that match the dimensions of each frame size.

Unit:mm

Diagram labels: Ring lug; Heat shrink tube; Wire; W,d2,B,C,A,D,t,E,F.

Dimensions are maximum/minimum exactly as source; K.S.TERMINALS references only, equivalent matching dimensions permitted. No inverter-frame mapping inferred.

Main-circuit ring terminals; K.S.TERMINALS INC. recommended reference only — PDF page 30

Source row Frame AWG Kit P/N A max mm B max mm C min mm D max mm d2 min mm E min mm F min mm W max mm t max mm
1 A 18 RNBS 1-3.7 9.8 3.2 4.8 4.1 3.7 13.0 4.2 6.6 0.8
2 A 16 RNBS 2-3.7 9.8 3.2 4.8 4.1 3.7 13.0 4.2 6.6 0.8
3 A 14 RNBS 2-3.7 9.8 3.2 4.8 4.1 3.7 13.0 4.2 6.6 0.8
4 B 18 RNBS1-4 12.1 3.6 6.1 5.6 4.3 13.0 4.5 7.2 1
5 B 16 RNBS1-4 12.1 3.6 6.1 5.6 4.3 13.0 4.5 7.2 1
6 B 14 RNBS2-4 12.1 3.6 6.1 5.6 4.3 13.0 4.5 7.2 1
7 B 12 RNBS5-4 12.1 3.6 6.1 5.6 4.3 13.0 4.5 7.2 1
8 C 14 RNBS2-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 10.5 1.2
9 C 12 RNBS5-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 10.5 1.2
10 C 10 RNBS5-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 10.5 1.2
11 C 8 RNBS8-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 10.5 1.2
12 D 10 RNBS5-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 10.5 1.2
13 D 8 RNBS8-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 10.5 1.2
14 E 6 RNB14-5 27.1 6.1 10.5 11.5 5.3 13.0 6.5 12.6 1.7
15 E 4 RNBS22-5 27.1 6.1 10.5 11.5 5.3 13.0 6.5 12.6 1.7
16 F 6 RNBS14-6 35.0 9.0 13.3 14.0 6.2 13.0 10.0 19.5 1.8
17 F 4 RNBS22-6 35.0 9.0 13.3 14.0 6.2 13.0 10.0 19.5 1.8
18 F 2 RNBS38-6 35.0 9.0 13.3 14.0 6.2 13.0 10.0 19.5 1.8

Manual — 3.5.2.2 Control terminal and filter — page 31

Manual reference: physical PDF page 31. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.5.2.2 Control terminal and filter

Model input terminal

Unit

Recommended model or size table for control board crimping terminals

Cable diameter

Manufacturer

Manufacturer material

number

Recommended specifications and model number of crimping tools

Recommended model or size table for filter model input crimping terminals

Crimp-terminal diagram labels: A,B,D,W.

CRIMPFOX 10S-1212045, Manufacturer: PHOENIX CONTACT; DNT13-0101, Manufacturer: DINKLE.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Control board crimping terminals — PDF page 31

Source row Cable diameter Manufacturer Manufacturer material number A max mm B max mm D max mm W max mm
1 0.2mm2 (24AWG) PHOENIX CONTACT AI 0.25-8 YE 12.5 8 2.6 1.4
2 0.34mm2 (22AWG) PHOENIX CONTACT AI 0.34-8 TQ 12.5 8 3.3 1.3
3 0.5mm2 (20AWG) PHOENIX CONTACT AI 0.5-8 WH 14 8 3.5 1.4

Filter input crimping terminals — PDF page 31

Source row Cable diameter Manufacturer Manufacturer material number A max mm B max mm D max mm W max mm
1 4mm2 (12AWG) PHOENIX CONTACT AI 4-10 GY 17 10 4.8 2.8
2 6mm2 (10AWG) PHOENIX CONTACT AI 6-12 YE 20 12 6.2 3.5
3 10mm2 (8AWG) PHOENIX CONTACT AI 10-12 RD 22 12 7.5 4.6

Manual — 3.6 Inverter specifications — page 32

Manual reference: physical PDF page 32. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.6 Inverter specifications

■ Basic specifications

(a) 200V class:

(b) 400V class:

1. Based on the TECO standard 4-pole induction motor. 2. If the control mode is SLV and the maximum frequency (01-02) is set to greater than 80Hz, the carrier

frequency range limit is 2~8KHz The followings are the maximum frequencies under different control modes

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

200V basic specifications — PDF page 32

Source row Property 2P5 201 202 203 205 208
1 Horse power (HP) 0.5 1 2 3 5 7.5
2 Applicable motor capacity (kW) 0.4 0.75 1.5 2.2 3.7 5.5
3 Rated output current (A) 2.8 4.8 7.5 11 17 25
4 Rated capacity (kVA) 1.2 1.7 2.9 4.0 6.7 9.9
5 Input voltage range Single/three-phase 200~240V (+10%-15%), 50/60HZ Single/three-phase 200~240V (+10%-15%), 50/60HZ Single/three-phase 200~240V (+10%-15%), 50/60HZ Single/three-phase 200~240V (+10%-15%), 50/60HZ Single/three-phase 200~240V (+10%-15%), 50/60HZ Single/three-phase 200~240V (+10%-15%), 50/60HZ
6 Output voltage range Three phase 0~240V Three phase 0~240V Three phase 0~240V Three phase 0~240V Three phase 0~240V Three phase 0~240V
7 Input current (A) 5.0/2.9 8.7/5.0 13.7/7.9 20.1/11.6 17.9 26.3
8 Allowable momentary outage time (Sec) 2.0 2.0 2.0 2.0 2.0 2.0
9 Protection category IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

400V basic specifications — PDF page 32

Source row Property 401 402 403 405 408 410
1 Horse power (HP) 1 2 3 5 7.5 10
2 Applicable motor capacity (kW) 0.75 1.5 2.2 3.7 5.5 7.5
3 Rated output current (A) 2.7 4.2 5.5 9.0 13 17
4 Rated capacity (kVA) 1.7 2.9 4.0 6.7 9.9 13.3
5 Input voltage range Three-phase 380~480V (+10%-15%), 50/60HZ Three-phase 380~480V (+10%-15%), 50/60HZ Three-phase 380~480V (+10%-15%), 50/60HZ Three-phase 380~480V (+10%-15%), 50/60HZ Three-phase 380~480V (+10%-15%), 50/60HZ Three-phase 380~480V (+10%-15%), 50/60HZ
6 Output voltage range Three-phase 0~480V Three-phase 0~480V Three-phase 0~480V Three-phase 0~480V Three-phase 0~480V Three-phase 0~480V
7 Input current (A) 2.8 4.4 5.8 9.5 13.7 17.9
8 Allowable momentary outage time (Sec) 1.5 2.0 2.0 2.0 2.0 2.0
9 Protection category IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1 IP20/NEMA1

Control mode maximum frequency — PDF page 32

Source row Control mode Other settings Maximum frequency
1 V/F SLV2 The maximum frequency is set to 599Hz 599Hz
2 SLV 200V 0.5~7.5HP, 400V 1~10HP 150Hz
3 PMSLV Unlimited 599Hz

Manual — ■ Product specifications (Applicable to simple version E) — page 33

Manual reference: physical PDF page 33. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ Product specifications (Applicable to simple version E)

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Simple version E product specifications — PDF page 33

Source row Item category (merged) Item / continued subitem Basic specifications
1 Control method Control method IM: V/F、SLV PM: SLV
2 Frequency Frequency control range 0.01~599Hz
3 Frequency Starting torque 150%/3Hz (VF mode), 150% / 0.5Hz (SLV mode)
4 Frequency Frequency resolution Digital input: 0.01 Hz
5 Frequency Frequency resolution Analog input: 0.06Hz/60Hz
6 Frequency Frequency setting Panel: Use the ▲▼ keys on the panel to set the frequency, use the panel knob to set the frequency
7 Frequency Frequency setting External terminals: ·AI1, AI2 (0~10V / 2~10V / 0~20mA / 4~20mA) Input up/down frequency setting
8 Frequency Frequency setting Communication setting
9 Frequency Frequency limit Frequency upper and lower limit ·3 skip frequencies can be set
10 Frequency Speed accuracy V/F :±2~3% SLV :± 1%
11 Operate Operation setting Panel: run, stop button control
12 Operate Operation setting External terminals: ·Multi-function operation mode operation (2-wire/3-wire control selection), jog operation
13 Operate Operation setting Communication operation
14 General controls V/F curve setting 18 fixed curves and 1 arbitrary curve
15 General controls Carrier frequency 2~16KHz (factory default value: 4kHz)
16 General controls Acceleration/deceleration control 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) 4-stage S curve can be set
17 General controls Multi-function input There are 29 functions that can be set (Refer to the descriptions of group3)
18 General controls Multi-function output There are 21 functions that can be set (Refer to the descriptions of group3)
19 General controls Multi-function simulated output There are 5 functions that can be set (Refer to the descriptions of group4)
20 General controls Other functions Overload detected, 16-stage speed, automatic program function, acceleration/deceleration time switch, master/slave operation signal switching, master/slave frequency source switching, PID control, torque compensation, starting frequency, slip compensation and fault reset, etc.
21 Display 5-digit LED Display: Parameter/parameter value/frequency/cable speed/DC voltage/output voltage/PID feedback/input and output terminal status/heatsink temperature/program version/fault record/etc.
22 Display Status indicator Indication: FWD, REV, SEQ, REF
23 Protection features Overload protection Electronic relay protection motor and inverter (150%/60s)
24 Protection features Over voltage 200V class: DC voltage>410V, 400V class: DC voltage>820V
25 Protection features Under-voltage 200V class: DC voltage <190V, 400Vclass: DC voltage <380V
26 Protection features Momentary power interruption then start Able to restart again within a short time after momentary power interruption
27 Protection features Stall prevention There is stall prevention protection during acceleration/deceleration/operation
28 Protection features Output-end short circuit Electronic circuit protection
29 Protection features Grounding failure Protection using current detector
30 Protection features Other protection functions Heatsink overheat protection, carrier frequency reduction with temperature decrease function, fault contact output, reverse limitation, direct start after boot up and fault reset restrictions, parameter locking, motor PTC overheat protection and other functions
31 Communication control Communication control Standard built-in RS485 communication (Modbus) for 1to1 or 1to many control
32 Environment Operating temperature IP20 type/NEMA 1:

Manual — ■ Product specifications (applicable to standard version S) — page 34

Manual reference: physical PDF page 34. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ Product specifications (applicable to standard version S)

Simple E continuation from PDF33. First blank item row continues Operating temperature; category remains blank as printed. Source claims/conditions not current certification approval.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Simple version E product specifications continuation — PDF page 34

Source row Item category (merged) Item / continued subitem Basic specifications
1 ⟦blank source cell⟧ ⟦blank source cell⟧ Inside the distribution panel: -10~50° (no dust-proof sticker) (de-rating from 50, 50~60°C) 2% current needs to be reduced with every increase of 1°C) -10~40°C (with dust-proof sticker) Parallel installation is -10~40°C
2 ⟦blank source cell⟧ Storage temperature -20~70°C
3 ⟦blank source cell⟧ Humidity Under 95% relative humidity RH, no condensation or water droplet (In compliance with IEC60068-2-78 standards)
4 ⟦blank source cell⟧ Vibration 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards)
5 ⟦blank source cell⟧ Protection category IP20/NEMA1
6 ⟦blank source cell⟧ Pollution degree Level 2, after coating meets IEC 60721-3-3 Class 3C3.
7 International certification International certification UL, CE, RoHS, REACH, UKCA, cUL

Standard version S product specifications — PDF page 34

Source row Item category (merged) Item / continued subitem Basic specifications
1 Control method Control method IM: V/F, *V/F+PG, SLV, *SV, SLV2 PM: *SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV *IM/PM: V/F+PG, SV only for special projects
2 Frequency Frequency control range 0.01~599Hz
3 Frequency Starting torque 150%/3Hz (VF mode), 150% / 0.5Hz (SLV mode)
4 Frequency Frequency resolution Digital input: 0.01 Hz
5 Frequency Frequency resolution Analog input: 0.06Hz/60Hz
6 Frequency Frequency setting Panel: Use the ▲▼ keys on the panel to set the frequency, use the panel knob to set the frequency
7 Frequency Frequency setting External terminals: ·AI1, AI2 (0~10V / 2~10V / 0~20mA / 4~20mA) Input up/down frequency setting
8 Frequency Frequency setting Communication setting
9 Frequency Frequency limit Frequency upper and lower limit ·3 skip frequencies can be set
10 Frequency Speed accuracy V/F :±2~3% SLV :± 1%
11 Operate Operation setting Panel: run, stop button control
12 Operate Operation setting External terminals: ·Multi-function operation mode operation (2-wire/3-wire control selection), jog operation
13 Operate Operation setting Communication operation
14 General controls V/F curve setting 18 fixed curves and 1 arbitrary curve
15 General controls Carrier frequency 1. 2~16KHz (the factory default value is: 4kHz, 205/208/410 except for the carrier frequency of 2kHz)
16 General controls Acceleration/deceleration control 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) 4-stage S curve can be set
17 General controls Multi-function input There are 29 functions that can be set (Refer to the descriptions of group3)
18 General controls Multi-function output There are 21 functions that can be set (Refer to the descriptions of group3)
19 General controls Multi-function simulated output There are 5 functions that can be set (Refer to the descriptions of group4)
20 General controls Other functions Overload detected, 16-stage speed, automatic program function, acceleration/deceleration time switch, master/slave operation signal switching, master/slave frequency source switching, PID control, torque compensation, starting frequency, slip compensation and fault reset, etc.
21 Display 5-digit LED Display: Parameter/parameter value/frequency/cable speed/DC voltage/output voltage/PID feedback/input and output terminal status/heatsink temperature/program version/fault record/etc.

Manual — ■ Derating curve according to the carrier size — page 35

Manual reference: physical PDF page 35. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ Derating curve according to the carrier size

(a) 200V models

Output current (Iout)

Carrier frequency (Fc)

200V 0.5~7.5HP

100% Ir

80% Ir

0 4KHz 12KHz

4kHz:100%Ir;12kHz:80%Ir.

Standard S continuation from PDF34. First blank category continues Display/status indicators. Subsequent categories are source-specific. Source claims are not current certification approval.

Standard version S product specifications continuation — PDF page 35

Source row Item category (merged) Item / continued subitem Basic specifications
1 ⟦blank source cell⟧ Status indicator Indication: FWD, REV, SEQ, REF
2 Protection features Overload protection Electronic relay protection motor and inverter (150%/60s)
3 Protection features Over voltage 200V class: DC voltage>410V, 400V class: DC voltage>820V
4 Protection features Under-voltage 200V class: DC voltage <190V, 400Vclass: DC voltage <380V
5 Protection features Momentary power interruption then start Able to restart again within a short time after momentary power interruption
6 Protection features Stall prevention There is stall prevention protection during acceleration/deceleration/operation
7 Protection features Output-end short circuit Electronic circuit protection
8 Protection features STO function Fast output cut-off protection
9 Protection features Grounding failure Protection using current detector
10 Protection features Other protection functions Heatsink overheat protection, carrier frequency reduction with temperature decrease function, fault contact output, reverse limitation, direct start after boot up and fault reset restrictions, parameter locking, motor PTC overheat protection and other functions
11 Communication control Communication control Standard built-in RS485 communication (Modbus) for 1to1 or 1to many control
12 Environment Operating temperature IP20 type/NEMA 1 inside the distribution panel: No dust-proof sticker: -10~50°C / with dust-proof sticker: - 10~40°C / parallel installation: -10~40°C *De-rating: When used between 50~60°C, reduce 2% current for every increase of 1°C.
13 Environment Storage temperature -20~70°C
14 Environment Humidity Under 95% relative humidity RH, no condensation or water droplets (in compliance with IEC60068-2-78 standards)
15 Environment Vibration 10Hz≦f≦57Hz:±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards)
16 Environment Protection category IP20/NEMA1
17 Environment Pollution degree Level 2, after coating meets IEC 60721-3-3 Class 3C3.
18 International certification International certification UL, CE, RoHS, REACH, UKCA, cUL

Manual — (b) 400V models — page 36

Manual reference: physical PDF page 36. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(b) 400V models

Output current (Iout)

400V 1~10HP (except for 5HP)

100% Ir

80% Ir

0 4KHz 12KHz

Carrier frequency (Fc)

400V 5HP

70% Ir

4kHz:100%Ir;12kHz:80%Ir.

4kHz:100%Ir;12kHz:70%Ir.

Manual — Based on the temperature derating curve* — page 37

Manual reference: physical PDF page 37. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Based on the temperature derating curve*

*Users should adjust the load size appropriately according to the ambient temperature

of the inverter to avoid damaging the inverter.

*The carrier of models 205/208/410 is 2kHz, and the carrier of the remaining models is

the default factory 4kHz.

■ Instructions for activation of capacitors after long-term storage

After this product has been stored for long periods of time, to allow the inverter to operate normally,

*1: The rated voltage value is in accordance with the value on the inverter label sticker

0 40°C 60°C

Rated current

80%Ir

100%Ir

Output current (Iout)

Ambient temperature

40°C:100%Ir;60°C:80%Ir.

please activate the capacitors by following the storage conditions below:

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Long-term storage capacitor activation — PDF page 37

Source row Storage time Capacitor activation process
1 ≦1 year Use when the inverter can supply power normally
2 1-2 years Pre-charge the capacitors using 100% rated voltage (*1); the inverter can only be used normally after charging for 1 hour
3 ≧2 years I. Pre-charge the capacitors with 25% rated voltage for 30 minutes II. Pre-charge the capacitors with 50% rated voltage for 30 minutes III. Pre-charge the capacitors with 75% rated voltage for 30 minutes IV. Pre-charge the capacitors with 100% rated voltage for 210 minutes After completing the four steps mentioned above, then can the inverter be used normally

Manual — 3.7 Dimensions diagram — page 38

Manual reference: physical PDF page 38. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.7 Dimensions diagram

3.7.1 Standard type

(a) 220V : 0.5~1HP/440V : 1~2HP (IP20)

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-29 3.7 Dimensions diagram 3.7.1 Standard type (a) 220V : 0.5~1HP/440V : 1~2HP (IP20) — PDF page 38

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-2P5-HE 72 142 150 60 130.5 5 M4 1.2 ⟦blank source cell⟧
2 E710-201-HE 72 142 150 60 130.5 5 M4 1.2 ⟦blank source cell⟧
3 E710-401-H3E 72 142 150 60 130.5 5 M4 1.2 ⟦blank source cell⟧
4 E710-402-H3E 72 142 150 60 130.5 5 M4 1.2 ⟦blank source cell⟧

Manual — (b) 220V : 0.5~1HP/440V : 1~2HP (NEMA1) — page 39

Manual reference: physical PDF page 39. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(b) 220V : 0.5~1HP/440V : 1~2HP (NEMA1)

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-30 (b) 220V : 0.5~1HP/440V : 1~2HP (NEMA1) Inverter model number Dimensions (mm) — PDF page 39

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-2P5-HE 72 220 150 60 130.5 5 M4 1.5 ⟦blank source cell⟧
2 E710-201-HE 72 220 150 60 130.5 5 M4 1.5 ⟦blank source cell⟧
3 E710-401-H3E 72 220 150 60 130.5 5 M4 1.5 ⟦blank source cell⟧
4 E710-402-H3E 72 220 150 60 130.5 5 M4 1.5 ⟦blank source cell⟧

Manual — (c) 220V : 2~5HP/440V : 3~5HP (IP20) — page 40

Manual reference: physical PDF page 40. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(c) 220V : 2~5HP/440V : 3~5HP (IP20)

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-31 (c) 220V : 2~5HP/440V : 3~5HP (IP20) Inverter model number Dimensions (mm) — PDF page 40

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-202-HS 87 157 164 73 145 5 M4 1.6 ⟦blank source cell⟧
2 E710-203-HS 87 157 164 73 145 5 M4 1.6 ⟦blank source cell⟧
3 E710-205-H3S 87 157 164 73 145 5 M4 1.6 ⟦blank source cell⟧
4 E710-403-H3S 87 157 164 73 145 5 M4 1.6 ⟦blank source cell⟧
5 E710-405-H3S 87 157 164 73 145 5 M4 1.6 ⟦blank source cell⟧

Manual — (d) 220V : 2~5HP/440V : 3~5HP (NEMA1) — page 41

Manual reference: physical PDF page 41. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(d) 220V : 2~5HP/440V : 3~5HP (NEMA1)

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-32 (d) 220V : 2~5HP/440V : 3~5HP (NEMA1) Inverter model number Dimensions (mm) W — PDF page 41

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-202-HS 87 220 164 73 145 5 M4 2.0 ⟦blank source cell⟧
2 E710-203-HS 87 220 164 73 145 5 M4 2.0 ⟦blank source cell⟧
3 E710-205-H3S 87 220 164 73 145 5 M4 2.0 ⟦blank source cell⟧
4 E710-403-H3S 87 220 164 73 145 5 M4 2.0 ⟦blank source cell⟧
5 E710-405-H3S 87 220 164 73 145 5 M4 2.0 ⟦blank source cell⟧

Manual — (e) 220V : 7.5HP/440V :7.5-10HP (IP00) — page 42

Manual reference: physical PDF page 42. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(e) 220V : 7.5HP/440V :7.5-10HP (IP00)

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-33 (e) 220V : 7.5HP/440V :7.5-10HP (IP00) Inverter model number — PDF page 42

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-208-H3S 109 207 169 94 194.5 6 M4 2.3 ⟦blank source cell⟧
2 E710-408-H3S 109 207 169 94 194.5 6 M4 2.3 ⟦blank source cell⟧
3 E710-410-H3S 109 207 169 94 194.5 6 M4 2.3 ⟦blank source cell⟧

Manual — (f) 220V : 7.5HP/440V : 7.5-10HP (NEMA1) — page 43

Manual reference: physical PDF page 43. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(f) 220V : 7.5HP/440V : 7.5-10HP (NEMA1)

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-34 (f) 220V : 7.5HP/440V : 7.5-10HP (NEMA1) Inverter model number Dimensions (mm) W — PDF page 43

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-208-H3S 109 250 169 94 194.5 6 M4 2.3 ⟦blank source cell⟧
2 E710-408-H3S 109 250 169 94 194.5 6 M4 2.3 ⟦blank source cell⟧
3 E710-410-H3S 109 250 169 94 194.5 6 M4 2.3 ⟦blank source cell⟧

Manual — 3.7.2 Built-in filter type (220V 0.5~3HP, 440V 1~10HP) — page 44

Manual reference: physical PDF page 44. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.7.2 Built-in filter type (220V 0.5~3HP, 440V 1~10HP)

(a)220V : 2P5~201HP/440V : 401~402HP

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-35 3.7.2 Built-in filter type (220V 0.5~3HP, 440V 1~10HP) (a)220V : 2P5~201HP/440V : 401~402HP Inverter model — PDF page 44

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-2P5-H1EF 72 169.5 195.5 60 156 1.2 M4 1.9 ⟦blank source cell⟧
2 E710-201-H1EF 72 169.5 195.5 60 156 1.2 M4 1.9 ⟦blank source cell⟧
3 E710-401-H3EF 72 169.5 195.5 60 156 1.2 M4 1.9 ⟦blank source cell⟧
4 E710-402-H3EF 72 169.5 195.5 60 156 1.2 M4 1.9 ⟦blank source cell⟧

Manual — (b)220V : 202~203HP/440V : 403~405HP — page 45

Manual reference: physical PDF page 45. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(b)220V : 202~203HP/440V : 403~405HP

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-36 (b)220V : 202~203HP/440V : 403~405HP Inverter model number Dimensions (mm) — PDF page 45

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-202-H1SF 87 184 207 73 171 1.2 M4 2.4 ⟦blank source cell⟧
2 E710-203-H1SF 87 184 207 73 171 1.2 M4 2.4 ⟦blank source cell⟧
3 E710-403-H3SF 87 184 207 73 171 1.2 M4 2.4 ⟦blank source cell⟧
4 E710-405-H3SF 87 184 207 73 171 1.2 M4 2.4 ⟦blank source cell⟧

Manual — (c) 440V: 7.5-10HP — page 46

Manual reference: physical PDF page 46. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(c) 440V: 7.5-10HP

Dimension drawing symbols: W,W1,H,H1,D,t,d.

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Inverter dimensions: 3-37 (c) 440V: 7.5-10HP Inverter model number — PDF page 46

Source row Model W mm H mm D mm W1 mm H1 mm t mm d Net weight kg Remarks
1 E710-408-H3SF 109 232 210 94 222.5 1.2 M4 3.6 ⟦blank source cell⟧
2 E710-410-H3SF 109 232 210 94 222.5 1.2 M4 3.6 ⟦blank source cell⟧

Manual — 3.7.3 — page 47

Manual reference: physical PDF page 47. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.7.3

KEYPAD dimensions diagram

KeyPad panel external connection dimensions diagram

Installation mount-

ing plate

Thickness≤3mm

Opening size

Keypad front view: horizontal label72;vertical label47.

Keypad side view dimension labels:22.5,20.5,23.5.

Keypad rear view labels: horizontal66.8,64.4,47;vertical14.9,16.3,32,43.4;lower17.7,28.7;fastener calloutM3*6.

Opening size: horizontal65.4±0.2;vertical44.4±0.2;cornerR≤0.5.

Manual — 3.8 The appearance and component names of the E710 inverter — page 48

Manual reference: physical PDF page 48. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.8 The appearance and component names of the E710 inverter

(a) 220V : 0.5~1HP/440V : 1~2HP

(wall-mounted type, IEC IP00)

(Wall-mounted type, IEC IP20,NEMA1)

(b) 220V : 2~5HP/440V : 3~5HP

Digital operator

Upper casing

Mounting hole

Lower casing

Nameplate and

barcode

Quick-release

fan cover

Bottom

cover

Bottom cover

Dust-proof sticker

Wiring box

Dust-proof

sticker

Manual — (c) 220V : 7.5HP/440V : 7.5~10HP — page 49

Manual reference: physical PDF page 49. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(c) 220V : 7.5HP/440V : 7.5~10HP

(wall-mounted type, IEC IP00)

(Wall-mounted type, IEC IP20,NEMA1)

Digital

operator

Upper casing

Mounting hole

Lower casing

Nameplate and

barcode

Quick-release

fan cover

Bottom cover

Dust-proof

sticker

Wiring box

Digital operator

Manual — 3.9 Disassembling steps of the E710 model — page 50

Manual reference: physical PDF page 50. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.9 Disassembling steps of the E710 model

(a) 200V 0.5~1HP/400V 1~2HP

Step One: Remove the bottom cover Step Two: Assembling the wiring and reinstall

(b) 200V 2~7.5HP/400V 3~10HP

Adjacent source context — repeated to preserve continuation:

Manual — Chapter 4 Software index — page 51

Manual reference: physical PDF page 51. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 4 Software index

4.1 Panel use

4.1.1

Descriptions of panel functions

Physical source cells and headers retained; repeated merged cells explicit; blanks remain blanks.

Adjacent source context — repeated to preserve continuation:

Panel functions — PDF page 51

Source row Type Name Function
1 Display Main display area Displays the frequency, parameters, voltage, current, temperature and abnormalities, etc.
2 Display LED status display FWD: When the inverter is in forward status, this indicator lights up. (It will flash during downtime and will remain constantly on while operating) REV: When the inverter is in reverse status, this indicator lights up. (It will flash during downtime and will remain constantly on while operating) SEQ: When the command source of the inverter operations is set to external control, this indicator will light up. REF: When the command source of the inverter frequency is set to external control, this indicator will light up.
3 Buttons (8 buttons) RUN button RUN button: Inverter operation.
4 Buttons (8 buttons) STOP button STOP button: Inverter stops operating.
5 Buttons (8 buttons) [up-chevron button] Used for frequency and parameter setting.
6 Buttons (8 buttons) [down-chevron button] Used for frequency and parameter setting.
7 Buttons (8 buttons) FWD/REV button (LED type) Switching button for setting the motor operation direction; when the FWD display light is on, it means the motor is rotating forward, and when the REV display light is on, it means the motor is rotating in reverse.
8 Buttons (8 buttons) DSP/FUN button Switches the display screen, it cycles according to the frequency screen →function menu→ monitor parameters→ frequency screen.
9 Buttons (8 buttons) <</RESET button “<<” Move left button: Used to change parameters or parameter values. RESET button: It changes to the reset button when faults are detected.
10 Buttons (8 buttons) READ/ENTER button This button switches and enters functions, sets internal values, modifies parameter settings, and confirms the input.
11 Panel knob VR FREQ.SET When 00-05=8, the panel knob can be used to adjust and set the frequency.

Manual — 4.1.2 — page 52

Manual reference: physical PDF page 52. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.2

Show description

Digits and letter display

Description of the seven-stage monitor display

Actual output frequency

Frequency command display

mode

Frequency command

modification mode

LED lights up

All LED flashes

The selected position flashes

(modified location)

Under shutdown status: The seven-stage monitor displays the set frequency, and all of the LEDs flashes. If the UP/DOWN buttons are operated at this time, it will enter the frequency command modification mode, and the flashing position will change in accordance with the <</RESET button. Press the READ/ENTER button to write the frequency command and switch to frequency display mode status, or do not press the READ/ENTER button for five seconds under frequency modification mode to switch back to the frequency display mode. Under operation status: The seven-stage monitor displays the actual output frequency, and the LED lights remain constantly on. If the UP/DOWN buttons are operated at this time, it will enter the frequency command modification mode, and its flashing position will change in accordance with the <</RESET button. If the inverter is under operation process, press the READ/ENTER button to write the frequency command and then switch to the actual output frequency mode status.

Actual output frequency: LED lights up. Frequency command display mode: all LEDs flash. Frequency command modification mode: selected modified position flashes. Illustration shows 005.00.

Characters paired with visual display glyphs; segment geometry remains in original PDF.

Digits and letter display pairs — PDF page 52

Source row Actual LED display image
1 0 [Seven-segment glyph representing 0; exact segment geometry in source image]
2 1 [Seven-segment glyph representing 1; exact segment geometry in source image]
3 2 [Seven-segment glyph representing 2; exact segment geometry in source image]
4 3 [Seven-segment glyph representing 3; exact segment geometry in source image]
5 4 [Seven-segment glyph representing 4; exact segment geometry in source image]
6 5 [Seven-segment glyph representing 5; exact segment geometry in source image]
7 6 [Seven-segment glyph representing 6; exact segment geometry in source image]
8 7 [Seven-segment glyph representing 7; exact segment geometry in source image]
9 8 [Seven-segment glyph representing 8; exact segment geometry in source image]
10 9 [Seven-segment glyph representing 9; exact segment geometry in source image]
11 A [Seven-segment glyph representing A; exact segment geometry in source image]
12 B [Seven-segment glyph representing B; exact segment geometry in source image]
13 C [Seven-segment glyph representing C; exact segment geometry in source image]
14 D [Seven-segment glyph representing D; exact segment geometry in source image]
15 E [Seven-segment glyph representing E; exact segment geometry in source image]
16 F [Seven-segment glyph representing F; exact segment geometry in source image]
17 G [Seven-segment glyph representing G; exact segment geometry in source image]
18 H [Seven-segment glyph representing H; exact segment geometry in source image]
19 I [Seven-segment glyph representing I; exact segment geometry in source image]
20 J [Seven-segment glyph representing J; exact segment geometry in source image]
21 L [Seven-segment glyph representing L; exact segment geometry in source image]
22 n [Seven-segment glyph representing n; exact segment geometry in source image]
23 o [Seven-segment glyph representing o; exact segment geometry in source image]
24 P [Seven-segment glyph representing P; exact segment geometry in source image]
25 q [Seven-segment glyph representing q; exact segment geometry in source image]
26 r [Seven-segment glyph representing r; exact segment geometry in source image]
27 S [Seven-segment glyph representing S; exact segment geometry in source image]
28 t [Seven-segment glyph representing t; exact segment geometry in source image]
29 u [Seven-segment glyph representing u; exact segment geometry in source image]
30 V [Seven-segment glyph representing V; exact segment geometry in source image]
31 Y [Seven-segment glyph representing Y; exact segment geometry in source image]
32 - [Seven-segment glyph representing -; exact segment geometry in source image]
33 ° [Seven-segment glyph representing °; exact segment geometry in source image]
34 _ [Seven-segment glyph representing _; exact segment geometry in source image]
35 . [Seven-segment glyph representing .; exact segment geometry in source image]

Manual — LED digital tube display — page 53

Manual reference: physical PDF page 53. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

LED digital tube display

Illustrative screens only, not default settings, operating readings or motor ratings. Text approximates seven-segment glyphs; exact lit/dim segments remain in image.

LED screen illustrative examples — PDF page 53

Source row Illustrative seven-segment screen Description
1 005.00 1. Displays the set frequency during shutdown 2. Displays the actual output frequency during operation
2 00-01 Displays the parameter code
3 00000 Displays the parameter setting value
4 220u Displays the input voltage
5 001.1A Displays the inverter current
6 03100 Displays the inverter DC Bus voltage
7 024°C Displays the temperature
8 00000 Displays the PID feedback value; the displayed number of digits is set through 12-01.
9 Err1 Abnormality display, refer to Chapter 5 Troubleshooting and Maintenance
10 000P Displays the AI1input/Displays the AI2input(0~100%)

Manual — Description of indicator light illumination and flashing — page 54

Manual reference: physical PDF page 54. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Description of indicator light illumination and flashing

LCD-only qualifications retained. Crossed/blank flashing cells do not invent a flashing state.

Indicator steady and flashing states — PDF page 54

Source row Indicator Steady label Steady condition Flashing label Flashing condition
1 Failure signal display light (only for LCD models) FAULT Lights up when failure signals occur [No flashing label shown] ⟦blank source cell⟧
2 Forward indicator FWD Lights up during forward operations FWD Flashes when there is no operation for the forward command
3 Reverse indicator REV Lights up during reverse operation REV Flashes when there is no operation for the reverse command
4 External control operation command indicator SEQ Lights up when the operation command is set as external control [No flashing label shown] ⟦blank source cell⟧
5 External control frequency command indicator REF Lights up when the frequency command is set as external control [No flashing label shown] ⟦blank source cell⟧
6 Operation indicator (only for LCD models) RUN Lights up under operation status RUN Flashes during the shutdown process
7 Shutdown indicator (only for LCD models) STOP Lights up under shutdown status STOP Flashes during the DC braking process

Manual — 4.1.3 — page 55

Manual reference: physical PDF page 55. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.3

Functional structure of the LED seven-stage display screen

The basic display screen is as follows:

After 3

seconds

Power voltage

Frequency

Parameter menu

DSP/FUN

Mode

switch

The display screen with user settings is as follows:

The highest digit of 12- 00 represents the default boot-up screen, and the remaining digits represents the

display screen set by the user.

Example 1: Set 12 - 00 =[10000]

Power On indicator: Power

voltage

Inverter output current

Set frequency

Example 2: Set 12 - 00 =[12345]

Heatsink

temperature< 4 >

PID

Feedback < 5 >

Inverter output

current

< 1 >

Inverter DC

< 3 >

< 2 >

Basic screen example: power voltage 220u; after 3seconds frequency 005.00; DSP/FUN switches to 00-01 parameter menu and back.

Example 12-00=[10000]: power voltage 220u; after 3seconds inverter output current 0000A; DSP/FUN cycles through set frequency 005.00 and parameter menu 00-01.

Example 12-00=[12345]: power voltage 220u; after 3seconds output current 0000A; displayed DSP/FUN sequence includes set frequency 005.00, parameter menu 00-01, output voltage 0000u, DC voltage 03100, heatsink temperature 024°C, PID feedback 00000, returning to current.

Five digits 0–7, highest digit selects boot-up screen. Illustrated sequence separate from settings.

12-00 display selection — PDF page 55

Source row Code/category Description
1 12- 00 Display screen selection
2 Scope 0 0 0 0 0 Highest digit Lowest digit From the highest digit to the lowest digit, the range set for each of them is 0~7: [0]Do not display screen [1]Inverter output current [2]Inverter output voltage [3]Inverter DC voltage [4]Temperature [5]PID Feedback [6]AI1 value [7]AI2 value

Manual — Description of special buttons — page 56

Manual reference: physical PDF page 56. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Description of special buttons

1, “▲button”/ “▼button”:

Short-press

Long-press

T1

T2

Selects the digit position with short presses, and only changes the unit digit; changes the selected digit

continuously when long pressed.

4.1.4

Examples of button panel operations

Example 1: Modifying parameter values

< / RESET

button once

▲

Button once

DSP/FUN

DATA/ENTER

Button

once

After flashing

for 3 seconds

Frequency display interface

Example 1: frequency 005.00 → DSP/FUN once →00-01; two < /RESET presses select digit; ▲ once changes 00-01 to 00-02; DATA/ENTER once shows 00001;▲ once gives 00002; DATA/ENTER once shows -End-; after 3seconds shows 00002; DSP/FUN once returns 00-02.

Manual — Example 2: Modifying frequency directly from the panel during — page 57

Manual reference: physical PDF page 57. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 2: Modifying frequency directly from the panel during

shutdown/operation

Modifying set frequency during shutdown

Modifying frequency during operation

After flashing for

3 seconds

Power voltage display

Actual frequency

▲

Set frequency display

The set frequency has been modified

The set frequency can be modified

<Single digit>

The set frequency can be

modified<Tens>

< / RESET

button once

READ / ENTER

< / RESET button once

Returns to the

frequency value

before modification if

no modifications were

made after 5 seconds

Press the ▲

button 1 time

Press the O

Press the ▼

modified<Hundreds>

modified<Hundreds+1>

Note: When modifying the frequency on the panel directly during shutdown, when the “▲ button” is used to increase the frequency and exceeded the upper limit of the frequency, it will change to the lower limit of the frequency, and when using the “▼ button” to reduce the frequency, if the frequency goes lower than the lower limit of the frequency, it will change to the upper limit of the frequency.

Shutdown/operation examples begin 220u and, after 3seconds,005.00. Shutdown ▲ once illustrates 005.01; subsequent shown sequence 005.00→006.00 and READ/ENTER confirms 006.00. Operation column shows 005.00→006.00 and READ/ENTER confirms 006.00; source return path says return to previous frequency after 5seconds without modifications.

Manual — 4.1.5 — page 58

Manual reference: physical PDF page 58. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.5

Description of operation statuses

Input reverse

command

Input forward

Input operation

Input stop

Actual frequency

FWD

indicator

REV

Shutdown

Operating

Power

supply

RUN

STOP

STOP STOP

Transcribed visible status symbols in seven illustrated intervals. Filled circle=on, open circle=off, rays=flashing. RUN/STOP LCD-only. No timing or frequency scale inferred.

Operation-status indicator example intervals — PDF page 58

Source row Indicator Power supplied Reverse command before run Forward command before run Operating forward interval Operating reverse interval Operating forward again Stop-command interval
1 FWD flashing off flashing on off on on
2 REV off flashing off off on off off
3 RUN (LCD only) off off off on on on flashing
4 STOP (LCD only) on on on off off off on

Manual — 4.1.6 Appearance of the digital operator — page 59

Manual reference: physical PDF page 59. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.6 Appearance of the digital operator

LCD digital operator The digital operator (JN5-OP-F02) is equipped with internal memory that can be used to upload parameter settings from the digital operator to the inverter, or download parameter settings from the inverter to the digital operator. Descriptions of the name and functions of the JN5-OP-F02 LCD digital operator is as shown below.

Figure 4.1.6.2 LCD digital operator

LOC/REM button (LCD model): Switches the frequency and operation command source REMOTE

mode: Set according to the parameters, controlled by the control circuit terminal, communication or

other methods according to parameter settings; local mode: controlled from the operator. Fixed at

REMOTE mode after power is supplied; if the LOC/REM button is pressed while the inverter stopped,

it can switch between LOCAL mode and REMOTE mode. Parameters 11-79 can determine whether the

LOC/REM function is enabled.

Driving mode indicator

•FAULT: Lights up when faults or warnings occur.

•FWD: Lights up when forward operation command is

entered.

•REV:

Lights up when reverse operation command is

•SEQ:

Lights up when the start operation command is

issued from the control circuit or the RS-485

communication command (REMOTE mode).

•REF:

Lights up when the start frequency command

is issued from the control circuit terminal or

the RS-485 communication command (RE-

MOTE mode).

LCD screen (maximum 8 rows * 25 letters)

•Displays the monitor data, parameters and settings

•Mode display (displays at the top-left of the LCD screen)

Monitor: Displays in driving mode

Group: Displays in all group setting mode

PARA: Displays in group parameter setting mode

Edit:

Displays in edit mode or automatic tuning mode

LCD operator visible controls: LOC/REM,▲,DSP/FUN,<RESET,▼,READ/ENTER,RUN,STOP. Indicator labels FAULT,FWD,REV,SEQ,REF;REMOTE over SEQ/REF.

Manual — 4.1.7 Display method ■ Operation method — page 60

Manual reference: physical PDF page 60. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.7 Display method ■ Operation method

The parameters of E710 are modularized to make the browsing and setting of these parameters easier. The inverter has four operation modes; press the DSP/FUN button during power on to display the operation mode. Pressing the DSP/FUN button repeatedly allows browsing of these four operation modes, and when the READ/ENTER button is pressed, the operation mode required can be selected. (Refer to Figure 4.1.7.1)

Boot up

Boot up display screen

Monitor mode

Group setting mode

Sub-group edit mode

Edit parameter mode

. Inverter can operate in this mode.

. Displays status, failure message or real-time tracking.

. Inverter can edit groups in this mode.

. Sets or reads frequently used/customized parameters.

. Inverter can edit sub-group parameters in this mode.

. Sets or reads all group parameters.

. Inverter can edit parameters in this mode.

. Adjusts motor parameters automatically.

*Make sure to execute automatic adjustment of motor parameters before

executing vector control (Sensorless vector control or current vector control).

*Inverter will not display automatic adjustment mode options while operating or

when failures occur.

DSP

FUN

RUN

READ

ENTER

Automatic commissioning display

Figure 4.1.7.1 Operation mode structure

Note: Pressing and holding down the decrease or increase button will perform automatic increase (decrease)

to make it easier to browse operation modes, parameter groups or parameter tables.

Manual — 4.1.8 Monitor mode When the inverter is operating in drive mode, the output frequency command, output current and voltage can be displayed in drive mode. Fault — page 61

Manual reference: physical PDF page 61. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.8 Monitor mode When the inverter is operating in drive mode, the output frequency command, output current and voltage can be displayed in drive mode. Fault messages can also be displayed. The main operation method of drive mode is as shown in Figure 4.1.8.1 below.

Power ON

Monitor

Freq Ref

12-17=000.00Hz

12-18=0000.0A

12-16=005.00Hz

Flt Freq Ref

12-15=000.00Hz

Flt DC Voltage

00 Basic Func.

01 V/F Pattern.

02 Motor Parameter

Group

DSP

FUN

12-14=0000.0V

Monitor mode screen

Group setting mode screen

Figure 4.1.8.1 Operation method of monitor mode

Monitor / Freq Ref /12-16=005.00Hz; footer 12-17=000.00Hz and 12-18=0000.0A

Monitor / Flt Freq Ref /12-15=000.00Hz; footer 12-17=000.00Hz and 12-18=0000.0A

Monitor / Flt DC Voltage /12-14=0000.0V; footer 12-17=000.00Hz and 12-18=0000.0A

Manual — 4.1.9 Advanced setting — page 62

Manual reference: physical PDF page 62. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.9 Advanced setting

Advanced setting includes Group, sub-group (PARA) and parameter setting (Edit) modes; all inverter parameters can be browsed and changed. The main operation method of advanced setting is as shown in Figure 4.1.9.1 below.

Figure 4.1.9.1 Operation method of advanced setting

Note -

  1. Use the increase/decrease button, jog/move left button or RESET/< move button to set the parameters in

the data setting (browsing) screen. The parameters will be saved when the READ/ENTER button is pressed, and the screen will return to the previous sub-menu screen when the DSP/FUN button is pressed. 2. Use the increase and decrease buttons to browse the various mode

screens in advanced setting. For example, when the DSP/FUN button is pressed in parameter setting mode, the screen will return to the previous sub-group setting mode screen. When the DSP/FUN button is pressed on the sub-group setting mode screen, the screen will return to the previous group setting mode screen. 3. Please refer to Chapter 4 (Parameters) for detailed advanced

setting parameter display screen. 4. Data setting/browsing screen ** Use the increase/decrease and (or) RIGHT (LEFT) moving key to

change and select the parameter (cursor flashes) and change its setting value. Press the READ/ENTER button to save the setting value. The cursor will start flashing again after a few seconds.

Figure 4.1.9.2 Group setting mode screen

[Monitor mode screen]

[Group setting mode]

[Sub-group setting mode]

[Parameter setting mode]

The button operation methods

are as same as above

Group setting mode

Parameter code

Parameter name Settings Setting range Factory settings

Monitor / Freq Ref /12-16=000.00Hz;12-17=000.00Hz;12-18=000.00Hz

Group: 00 Basic Fun.;01 V/F Pattern;02 Motor Parameter

PARA 00:-00 Control Method;-01 Motor Direction;-02 Run Source

Edit 00-00 / Control Method /0 V/F /(0~4) /<0>

Edit 00-01 / Motor Direction /0 Forward /(0~1) /<0>

Edit 00-02 / Run Source /0 Digital Op /(0~4) /<0>

Group /G01-01 /Language /0 English /(0~0) /<0>

Manual — 4.1.10 Automatic tuning display The main operations of the automatic tuning mode is as shown in Figure 4.1.10.1 below. — page 63

Manual reference: physical PDF page 63. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.1.10 Automatic tuning display The main operations of the automatic tuning mode is as shown in Figure 4.1.10.1 below.

Tune Mode Sel

READ

ENT ER

Motor Rated Power

0 Rotational

(0 ~ 2)

< 0 >

5.50 KW

(0.00 – 600.00)

< 5.50>

Edit 17-00

000.00Hz-000.0A

Auto-tuning Run

(Press Run Key)

0.0Hz – 0.0A

Autotuning

Aborted

>>>>>>>>>>>>>>>

0006.8 A

(0000.9~0009.2)

< 0006.8 >

Motor Sel

48.0Hz – 14.0A

Successful

>>>>>>>>>>>>>>>>>>>>>>>

(Rotational)

Motor Data Error

ATE01

Uncompleted

Edit 17-01

Edit 17-02

DSP

FUN

Edit 17-10

Edit

1 Enable

(0~1)

<0>

Autotuning ?

-01 Tune Mode Sel

-02 Motor Rated Power

-03 Motor Rated Curr.

PARA 17

-08 Mtr No-Load Volt

-10 Auto-tuning Run

-11 Auto-tuning Err

Group

17 Auto-tuning

18 Slip Compen

19 Traverse Func.

Press ▲ or ▼ key to change the value.

Warning: Do not use “0”, Rotation

Auto-tune, when load is coupled with

the motor.

*1HP = 0.746KW

STOP

RUN

Tuning

successful

fault

Figure 4.1.10.1 Operation instructions for automatic tuning

Note:

  1. Use the increase and decrease buttons to browse the automatic tuning parameter table. According to the different control methods,

specific parameters cannot be set. (Refer to automatic tuning 17 group parameters). 2. After entering the rated output power (17-01), rated current (17-02), rated voltage (17-03), rated frequency (17-04), rated speed (17-

05), number of motor poles (17-06) and selecting motor automatic tuning mode (17-00), enter (17-10) and select OK, then press the RUN button to perform automatic tuning. When automatic tuning has been executed correctly, the calculated motor parameter will be saved in parameter group 02 (motor parameters). 3. (a) In rotational automatic tuning (17-00=0), “Rotational” will be displayed, and the motor will operate during automatic tuning.

Before executing this function, make sure that the motor can operate safely first. (b) During stationary automatic tuning (17-00=1), “Stationary” will be displayed and the motor will not operate. (c) During stationary automatic tuning (17-00=2), “R1 Tuning” will be displayed and the motor will not operate. (d) During automatic tuning, the RUN LED light (at the top-left of the RUN button) will light up. (e) During automatic tuning, the “>>>” signal represents the automatic tuning process. 4. During automatic tuning, pressing the STOP button will stop the automatic tuning process. Make sure to use the STOP button on the

digital operator to stop the automatic tuning process. 5. When automatic tuning malfunctions, the digital operator will display the malfunction message and incomplete message. The RUN

LED light will stop, and the motor will operate freely until it stops. (Refer to Chapter 5.4 automatic tuning malfunctions) Press the RESET button to clear the malfunction screen, and it will return to the mode screen. 6. After automatic tuning is completed, the RUN LED light will go off. Press the DSP/FUN button to return to the mode screen, then

perform the next operation. The complete automatic tuning operation takes approximately 50 seconds.

Manual — 4.2 Parameters list — page 64

Manual reference: physical PDF page 64. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.2 Parameters list

Literal physical source cells; blanks retained.

Reserved attributes remain reserved. I/O expansion marked in development; no current availability inferred.

Parameter groups — PDF page 64

Source row Parameter group Name
1 Group 00 Basic function group
2 Group 01 V/F control function group
3 Group 02 IM motor parameter group
4 Group 03 External terminal digital input/output function group
5 Group 04 External terminal analog input/output function group
6 Group 05 Multi-speed function group
7 Group 06 Automatic operation function group
8 Group 07 Operation stop function group
9 Group 08 Protection function group
10 Group 09 Communication function group
11 Group 10 PID function group
12 Group 11 Auxiliary function group
13 Group 12 Monitor function group
14 Group 13 Maintenance function group
15 Group 14 PLC setting group
16 Group 15 PLC monitor group
17 Group 16 LCD function group
18 Group 17 Automatic tuning function group
19 Group 18 Slip compensation function group
20 Group 19 Frequency skipping function group
21 Group 20 Speed control function group
22 Group 21 Torque and position control function group
23 Group 22 PM motor group
24 Group 23 Pump and HVAC group

Parameter attributes — PDF page 64

Source row Attribute Meaning
1 *1 Modifiable parameters during operation
2 *2 Reserved
3 *3 When resetting to factory settings, the value of this parameter (value set by user) will not be restored to the factory default value
4 *4 The parameter is read-only and cannot be modified
5 *5 The parameter will only be displayed when it needs to be used with the optional card.
6 *6 Only displayed when the LED digital operator is used
7 *7 Only displayed when the LCD digital operator is used
8 *8 Its setting value will change according to the setting of 13-08
9 *9 Reserved
10 *10 Parameter opened after installing the I/O expansion card (the I/O card is still in development)

Manual — Group 00 basic function group — page 65

Manual reference: physical PDF page 65. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 00 basic function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 00 basic function group — PDF page 65

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 00-00 Motor control mode 0: V/F 0 - O O O O O O O *3
2 00-00 Motor control mode 1: Reserved 0 - O O O O O O O *3
3 00-00 Motor control mode 2: SLV 0 - O O O O O O O *3
4 00-00 Motor control mode 3: Reserved 0 - O O O O O O O *3
5 00-00 Motor control mode 4: Reserved 0 - O O O O O O O *3
6 00-00 Motor control mode 5: PMSLV 0 - O O O O O O O *3
7 00-00 Motor control mode 6: SLV2 0 - O O O O O O O *3
8 00-01 Motor rotation direction 0: Forward 0 - O O O O O O O *1
9 00-01 Motor rotation direction 1: Reverse 0 - O O O O O O O *1
10 00-02 Primary operation command source Select 0: Button panel 0 - O O O O O O O ⟦blank source cell⟧
11 00-02 Primary operation command source Select 1: External control 0 - O O O O O O O ⟦blank source cell⟧
12 00-02 Primary operation command source Select 2: Communication control 0 - O O O O O O O ⟦blank source cell⟧
13 00-02 Primary operation command source Select 3: PLC 0 - O O O O O O O ⟦blank source cell⟧
14 00-02 Primary operation command source Select 4: RTC [struck-through: (in development)] only for special projects 0 - O O O O O O O ⟦blank source cell⟧
15 00-03 Secondary operation command source selection 0: Button panel 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
16 00-03 Secondary operation command source selection 1: External control 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
17 00-03 Secondary operation command source selection 2: Communication control 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
18 00-03 Secondary operation command source selection 3: PLC 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
19 00-03 Secondary operation command source selection 4: RTC [struck-through: (in development)] only for special projects 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
20 00-04 Language selection 0: English 0 - O O O O O O O *7
21 00-04 Language selection 1: Simplified Chinese 0 - O O O O O O O *7
22 00-04 Language selection 2: Traditional Chinese 0 - O O O O O O O *7
23 00-04 Language selection 3: Turkish 0 - O O O O O O O *7
24 00-05 Primary frequency command source selection 0: Button panel 1 - O O O O O O O ⟦blank source cell⟧
25 00-05 Primary frequency command source selection 1: External control (analog AI1) 1 - O O O O O O O ⟦blank source cell⟧
26 00-05 Primary frequency command source selection 2: Terminal UP/DOWN 1 - O O O O O O O ⟦blank source cell⟧
27 00-05 Primary frequency command source selection 3: Communication control 1 - O O O O O O O ⟦blank source cell⟧
28 00-05 Primary frequency command source selection 4: Pulse input 1 - O O O O O O O ⟦blank source cell⟧
29 00-05 Primary frequency command source selection 5: Reserved 1 - O O O O O O O ⟦blank source cell⟧
30 00-05 Primary frequency command source selection 6: RTC (in development) 1 - O O O O O O O ⟦blank source cell⟧
31 00-05 Primary frequency command source selection 7: AI2 auxiliary frequency 1 - O O O O O O O ⟦blank source cell⟧
32 00-05 Primary frequency command source selection 8: Panel knob VR 1 - O O O O O O O ⟦blank source cell⟧
33 00-05 Primary frequency command source selection 9: Handwheel frequency (in development) 1 - O O O O O O O ⟦blank source cell⟧
34 00-06 Secondary frequency command source selection 0: Button panel 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
35 00-06 Secondary frequency command source selection 1: External control (analog AI1) 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
36 00-06 Secondary frequency command source selection 2: Terminal UP/DOWN 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
37 00-06 Secondary frequency command source selection 3: Communication control 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
38 00-06 Secondary frequency command source selection 4: Pulse input 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
39 00-06 Secondary frequency command source selection 5: Reserved 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
40 00-06 Secondary frequency command source selection 6: RTC (in development) 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
41 00-06 Secondary frequency command source selection 7: AI2 auxiliary frequency 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
42 00-06 Secondary frequency command source selection 8: Panel knob VR 0 (Note 4) - O O O O O O O ⟦blank source cell⟧
43 00-07 Frequency source combination mode selection 0: Primary frequency source 0 - O O O O O O O ⟦blank source cell⟧
44 00-07 Frequency source combination mode selection 1: Primary frequency source + secondary frequency source 0 - O O O O O O O ⟦blank source cell⟧

Manual — V/F+PG, SV, PMSV are only for special projects. — page 66

Manual reference: physical PDF page 66. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group00 continuation — PDF page 66

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 00-08 Communication frequency command 0.00~599.00 0.00 Hz O O O O O O O ⟦blank source cell⟧
2 00-09 Frequency command memory mode 0: Do not memorize communication frequency command before power failure (00-08) 0 - O O O O O - ⟦blank source cell⟧ ⟦blank source cell⟧
3 00-09 Frequency command memory mode 1: Memorize communication frequency command before power failure (00-08) 0 - O O O O O - ⟦blank source cell⟧ ⟦blank source cell⟧
4 00-10 Minimum frequency detection action 0: Warning will pop up when lower than the minimum frequency 0 - O O O O O O O [struck-through: Note 1]
5 00-10 Minimum frequency detection action 1: Operate with minimum frequency when lower than minimum frequency 0 - O O O O O O O [struck-through: Note 1]
6 00-10 Minimum frequency detection action 2: No stp0 warning, output frequency command 0 - O O O O O O O [struck-through: Note 1]
7 00-10 Minimum frequency detection action 3: No stp0 warning, lower than minimum frequency output 0 0 - O O O O O O O [struck-through: Note 1]
8 00-11 PID frequency lower limit selection 0: PID sleep limit frequency lower limit 0 - O O O O O O O ⟦blank source cell⟧
9 00-11 PID frequency lower limit selection 1: PID sleep limit 0Hz 0 - O O O O O O O ⟦blank source cell⟧
10 00-12 Frequency upper limit 0.1~109.0 100.0 % O O O O O O O ⟦blank source cell⟧
11 00-13 Frequency lower limit 0.0~109.0 0.0 % O O O O O O O ⟦blank source cell⟧
12 00-14 Acceleration time 1 0.1~6000.0 * s O O O O O O O *1
13 00-15 Deceleration time 1 0.1~6000.0 * s O O O O O O O *1
14 00-16 Acceleration time 2 0.1~6000.0 * s O O O O O O O *1
15 00-17 Deceleration time 2 0.1~6000.0 * s O O O O O O O *1
16 00-18 Jog frequency**** 0.00~599.00 6.00 Hz O O O O O O O *1
17 00-19 Jog acceleration time 0.1~0600.0 * s O O O O O O O *1
18 00-20 Jog deceleration time 0.1~0600.0 * s O O O O O O O *1
19 00-21 Acceleration time 3 0.1~6000.0 * s O O O O O O O *1
20 00-22 Deceleration time 3 0.1~6000.0 * s O O O O O O O *1
21 00-23 Acceleration time 4 0.1~6000.0 * s O O O O O O O *1
22 00-24 Deceleration time 4 0.1~6000.0 * s O O O O O O O *1
23 00-25 Acceleration/deceleration switching frequency 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
24 00-26 Emergency stop time 0.1~6000.0 5.0 s O O O O O O O ⟦blank source cell⟧
25 00-27 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 00-28 Primary frequency command characteristic selection 0: Positive characteristic (0~10V/4~20mA corresponds to 0~100%) 0 - O O O O O O O ⟦blank source cell⟧
27 00-28 Primary frequency command characteristic selection 1: Negative characteristic (0~10V/4~20mA corresponds to 100~0%) 0 - O O O O O O O ⟦blank source cell⟧
28 00-29 Zero-speed operation selection 0: Operate according to frequency command 0 - X X X O O X X ⟦blank source cell⟧
29 00-29 Zero-speed operation selection 1: Stop 0 - X X X O O X X ⟦blank source cell⟧
30 00-29 Zero-speed operation selection 2: Operate according to minimum frequency 0 - X X X O O X X ⟦blank source cell⟧
31 00-29 Zero-speed operation selection 3: Zero-speed operation 0 - X X X O O X X ⟦blank source cell⟧
32 00-30 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 00-31 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — V/F+PG, SV, PMSV are only for special projects. — page 67

Manual reference: physical PDF page 67. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

V/F+PG, SV, PMSV are only for special projects.

** : Before setting the parameter 00-32 application adjustment, please perform 13-08 initialization setting first.

Warning: If parameter 00-32 (application adjustment) is set, then the input/output terminal setting function will change automatically according to the setting value. Before trial run, please confirm the input/output signal of the inverter and the external sequence control first. Failure to confirm may result in personal accidents.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group00 continuation — PDF page 67

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 00-32 Application adjustment** 0: Universal 0 - O O O O O O O ⟦blank source cell⟧
2 00-32 Application adjustment** 1: Reserved 0 - O O O O O O O ⟦blank source cell⟧
3 00-32 Application adjustment** 2: Conveyor-specific parameters 0 - O O O O O O O ⟦blank source cell⟧
4 00-32 Application adjustment** 3: Exhaust fan-specific parameters 0 - O O O O O O O ⟦blank source cell⟧
5 00-32 Application adjustment** 4: Reserved 0 - O O O O O O O ⟦blank source cell⟧
6 00-32 Application adjustment** 5: Air compressor-specific parameters 0 - O O O O O O O ⟦blank source cell⟧
7 00-32 Application adjustment** 6: Hoist-specific (for lifting and lowering) parameters 0 - O O O O O O O ⟦blank source cell⟧
8 00-32 Application adjustment** 7: Crane-specific (for lateral movement) parameters 0 - O O O O O O O ⟦blank source cell⟧
9 00-32 Application adjustment** 8: Handwheel-specific parameters (Note 4) 0 - O O O O O O O ⟦blank source cell⟧
10 00-32 Application adjustment** 9: EVERISING sawing machine-specific parameters 0 - O O O O O O O ⟦blank source cell⟧
11 00-32 Application adjustment** 10: Punch press-specific parameters 0 - O O O O O O O ⟦blank source cell⟧
12 00-32 Application adjustment** 11: Textile machine-specific parameters 0 - O O O O O O O ⟦blank source cell⟧
13 00-33 Change parameters (for LCD use only) 0: Invalid 0 - O O O O O O O *7
14 00-33 Change parameters (for LCD use only) 1: Valid 0 - O O O O O O O *7
15 00-34 Multi-function terminal operation mode selection 0: Forward /stop-reverse /stop 0 - O O O O O O O ⟦blank source cell⟧
16 00-34 Multi-function terminal operation mode selection 1: Operate/stop-reverse /forward 0 - O O O O O O O ⟦blank source cell⟧
17 00-34 Multi-function terminal operation mode selection 2: 3-wire operation/stop 0 - O O O O O O O ⟦blank source cell⟧
18 00-35 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 00-36 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 00-37 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 00-38 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 00-39 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 00-40 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 00-41 User parameter 0 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-41 - O O O O O O O *7
25 00-42 User parameter 1 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-42 - O O O O O O O *7
26 00-43 User parameter 2 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-43 - O O O O O O O *7
27 00-44 User parameter 3 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-44 - O O O O O O O *7
28 00-45 User parameter 4 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-45 - O O O O O O O *7
29 00-46 User parameter 5 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-46 - O O O O O O O *7
30 00-47 User parameter 6 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-47 - O O O O O O O *7
31 00-48 User parameter 7 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-48 - O O O O O O O *7
32 00-49 User parameter 8 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-49 - O O O O O O O *7
33 00-50 User parameter 9 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-50 - O O O O O O O *7
34 00-51 User parameter 10 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-51 - O O O O O O O *7
35 00-52 User parameter 11 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-52 - O O O O O O O *7
36 00-53 User parameter 12 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-53 - O O O O O O O *7
37 00-54 User parameter 13 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-54 - O O O O O O O *7
38 00-55 User parameter 14 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-55 - O O O O O O O *7
39 00-56 User parameter 15 Select 13-06 = 1 to enable user parameter Setting range: 00-01 ~ 22-31, however, excluding 00-41~00- 56 and group 17 (for LCD use only) 00-56 - O O O O O O O *7
40 00-57 SV high-speed mode 0: SV high-speed mode 1 0 - X X X O X X X ⟦blank source cell⟧
41 00-57 SV high-speed mode 1: SV high-speed mode 2 0 - X X X O X X X ⟦blank source cell⟧
42 00-63 Frequency upper and lower limit setting selection 0: Percentage 0 - O O O O O O O ⟦blank source cell⟧
43 00-63 Frequency upper and lower limit setting selection 1: Frequency 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 01 V/F control function group — page 68

Manual reference: physical PDF page 68. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 01 V/F control function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 01 V/F control function group — PDF page 68

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 01-00 V/F curve selection 0~FF F - O O X X X X O *3
2 01-01 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 01-02 Motor 1 maximum output frequency 4.8~599.0 50.0/ 60.0 Hz O O O O O O O *8
4 01-03 Motor 1 maximum output voltage 200V: 0.1~255.0 - V O O X X X X O *8
5 01-03 Motor 1 maximum output voltage 400V: 0.2~510.0 - V O O X X X X O *8
6 01-04 Motor 1 intermediate output frequency 2 0.0~599.0 0.0 Hz O O X X X X O ⟦blank source cell⟧
7 01-05 Motor 1 intermediate output voltage 2 200V: 0.0~255.0 0.0 V O O X X X X O *8
8 01-05 Motor 1 intermediate output voltage 2 400V: 0.0~510.0 0.0 V O O X X X X O *8
9 01-06 Motor 1 intermediate output frequency 1 0.0~599.0 3.0 Hz O O X X X X O ⟦blank source cell⟧
10 01-07 Motor 1 intermediate output voltage 1 200V: 0.0~255.0 * V O O X X X X O *8
11 01-07 Motor 1 intermediate output voltage 1 400V: 0.0~510.0 * V O O X X X X O *8
12 01-08 Motor 1 minimum output frequency 0.0~599.0 VF:1.3/1.5 Hz O O O O O O O ⟦blank source cell⟧
13 01-08 Motor 1 minimum output frequency 0.0~599.0 VF+PG:- Hz O O O O O O O ⟦blank source cell⟧
14 01-08 Motor 1 minimum output frequency 0.0~599.0 SLV:0.5/0.6 Hz O O O O O O O ⟦blank source cell⟧
15 01-08 Motor 1 minimum output frequency 0.0~599.0 SV:- Hz O O O O O O O ⟦blank source cell⟧
16 01-08 Motor 1 minimum output frequency 0.0~599.0 PMSV:- Hz O O O O O O O ⟦blank source cell⟧
17 01-08 Motor 1 minimum output frequency 0.0~599.0 PMSLV:0.8 Hz O O O O O O O ⟦blank source cell⟧
18 01-08 Motor 1 minimum output frequency 0.0~599.0 SLV2: 1.3/1.5 Hz O O O O O O O ⟦blank source cell⟧
19 01-09 Motor 1 minimum output voltage 200V: 0.0~255.0 - V O O X X X X O *8
20 01-09 Motor 1 minimum output voltage 400V: 0.0~510.0 - V O O X X X X O *8
21 01-10 Torque compensation gain 0.0~2.0 0.5 - O O X X X X O *1
22 01-11 Torque compensation mode selection 0: Torque compensation mode 0 0 - O O X X X X X ⟦blank source cell⟧
23 01-11 Torque compensation mode selection 1: Torque compensation mode 1 0 - O O X X X X X ⟦blank source cell⟧
24 01-12 Motor 1 base frequency 4.8~599.0 50.0/ 60.0 Hz O O O O O O O *8
25 01-13 Motor 1 base output voltage 200V: 0.0~255.0 - V O O X X X X O *8
26 01-13 Motor 1 base output voltage 400V: 0.0~510.0 - V O O X X X X O *8
27 01-14 Input voltage setting 200V: 155.0~255.0 - V O O O O O O O *8
28 01-14 Input voltage setting 400V: 310.0~510.0 - V O O O O O O O *8
29 01-15 Torque compensation time 0~10000 200 ms O O X X X X O ⟦blank source cell⟧
30 01-16 Motor 2 maximum output frequency 4.8~599.0 50.0/ 60.0 Hz O X X X X X X *8
31 01-17 Motor 2 maximum output voltage 200V: 0.1~255.0 - V O X X X X X X *8
32 01-17 Motor 2 maximum output voltage 400V: 0.2~510.0 - V O X X X X X X *8
33 01-18 Motor 2 intermediate output frequency 2 0.0~599.0 0.0 Hz O X X X X X X ⟦blank source cell⟧
34 01-19 Motor 2 intermediate output voltage 2 200V: 0.0~255.0 0.0 V O X X X X X X ⟦blank source cell⟧
35 01-19 Motor 2 intermediate output voltage 2 400V: 0.0~510.0 0.0 V O X X X X X X ⟦blank source cell⟧
36 01-20 Motor 2 intermediate output frequency 1 0.0~599.0 - Hz O X X X X X X ⟦blank source cell⟧
37 01-21 Motor 2 intermediate output voltage 1 200V: 0.0~255.0 KVA V O X X X X X X ⟦blank source cell⟧
38 01-21 Motor 2 intermediate output voltage 1 400V: 0.0~510.0 KVA V O X X X X X X ⟦blank source cell⟧
39 01-22 Motor 2 minimum output frequency 0.0~599.0 - Hz O X X X X X X ⟦blank source cell⟧
40 01-23 Motor 2 minimum output voltage 200V: 0.0~255.0 KVA V O X X X X X X ⟦blank source cell⟧
41 01-23 Motor 2 minimum output voltage 400V: 0.0~510.0 KVA V O X X X X X X ⟦blank source cell⟧
42 01-24 Motor 2 base frequency 4.8~599.0 50.0/ 60.0 Hz O X X X X X X *8
43 01-25 Motor 2 base output voltage 200V: 0.0~255.0 - V O X X X X X X *8

Manual — Group 01 V/F control function group — page 69

Manual reference: physical PDF page 69. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 01 V/F control function group

V/F+PG, SV, PMSV are only for special projects.

KVA: This parameter varies according to the different inverter capacities.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 01 V/F control function group — PDF page 69

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 400V: 0.0~510.0 - ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 01-26 Motor 2 V/F curve selection 0~FF F - O X X X X X X *3

Manual — Group 02 IM motor parameter group — page 70

Manual reference: physical PDF page 70. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 02 IM motor parameter group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 02 IM motor parameter group — PDF page 70

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 02-00 Motor 1 no-load current 0.01~600.00 - A O X X X X X O ⟦blank source cell⟧
2 02-01 Motor 1 rated current 25%~200% inverter rated current. - A O O O O X X O ⟦blank source cell⟧
3 02-02 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 02-03 Motor 1 rated rotation speed 0~60000 - Rpm O O O O X X O ⟦blank source cell⟧
5 02-04 Motor 1 rated voltage 200V: 50.0~240.0 - V O O O O X X O *8
6 02-04 Motor 1 rated voltage 400V: 100.0~480.0 - V O O O O X X O *8
7 02-05 Motor 1 rated power 0.01~600.00 - kW O O O O X X O ⟦blank source cell⟧
8 02-06 Motor 1 rated frequency 4.8~599.0 50.0/ 60.0 Hz O O O O X X O *8
9 02-07 Motor 1 number of poles 2~16 (even number) 4 - O O O O X X O ⟦blank source cell⟧
10 02-08 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 02-09 Motor 1 excitation current 15%~70% motor rated current - % X X O O X X X ⟦blank source cell⟧
12 02-10 Motor 1 magnetic core saturation factor 1 1~100 - % X X O O X X X ⟦blank source cell⟧
13 02-11 Motor 1 magnetic core saturation factor 2 1~100 - % X X O O X X X ⟦blank source cell⟧
14 02-12 Motor 1 magnetic core saturation factor 3 80~300 - % X X O O X X X ⟦blank source cell⟧
15 02-13 Motor 1 magnetic core loss 0.0~15.0 - % O O X X X X O ⟦blank source cell⟧
16 02-14 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 02-15 Motor 1 line-to-line resistance 0.001~60.000 - Ω O O O O X X O ⟦blank source cell⟧
18 02-16 Motor 1 rotor resistance 0.001~60.000 - Ω X X O X X X X ⟦blank source cell⟧
19 02-17 Motor 1 leakage inductance 0.01~200.00 - mH X X O X X X X ⟦blank source cell⟧
20 02-18 Motor 1 mutual inductance 0.1~6553.4 - mH X X O X X X X ⟦blank source cell⟧
21 02-19 Motor 1 no-load voltage 200V: 50~240 - V X X O O X X X ⟦blank source cell⟧
22 02-19 Motor 1 no-load voltage 400V: 100~480 - V X X O O X X X ⟦blank source cell⟧
23 02-20 Motor 2 no-load current 0.01~600.00 - A O X X X X X X ⟦blank source cell⟧
24 02-21 Motor 2 rated current 25%~200% inverter rated current - A O X X X X X X ⟦blank source cell⟧
25 02-22 Motor 2 rated rotation speed 0~60000 - Rpm O X X X X X X ⟦blank source cell⟧
26 02-23 Motor 2 rated voltage 200V: 50.0~240.0 - V O X X X X X X *8
27 02-23 Motor 2 rated voltage 400V: 100.0~480.0 - V O X X X X X X *8
28 02-24 Motor 2 rated power 0.01~600.00 - kW O X X X X X X ⟦blank source cell⟧
29 02-25 Motor 2 rated frequency 4.8~599.0 50.0/ 60.0 Hz O X X X X X X *8
30 02-26 Motor 2 number of poles 2~16 (even number) 4 - O X X X X X X ⟦blank source cell⟧
31 02-27 ~ 02-31 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 02-32 Motor 2 line-to-line resistance 0.001~60.000 - Ω O X X X X X X ⟦blank source cell⟧
33 02-33 Motor 1 leakage inductance ratio 0.1~15.0 - % X X O O X X X ⟦blank source cell⟧
34 02-34 Motor 1 slip frequency 0.10~20.00 - Hz X X O O X X X ⟦blank source cell⟧
35 02-35 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
36 02-36 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
37 02-37 Motor mechanical loss 0.0~10.0 4.0 % X X X O O X X ⟦blank source cell⟧

Manual — Group 03 external terminal digital input/output function group — page 71

Manual reference: physical PDF page 71. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 03 external terminal digital input/output function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds. Neighboring option-list rows do not limit applicability to that printed code.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds. Source option list is separately represented from adjacent parameter metadata. No option-to-parameter relationship inferred from vertical alignment.

Digital terminal parameter metadata; separate from function-option list — PDF page 71

Source row Code Parameter name Factory settings Unit
1 03-00 Multi-function terminal S1 function setting 0 -
2 03-01 Multi-function terminal S2 function setting 1 -
3 03-02 Multi-function terminal S3 function setting 2 -
4 03-03 Multi-function terminal S4 function setting 3 -
5 03-04 Multi-function terminal S5 function setting 4 -
6 03-05 Multi-function terminal S6 function setting 17 -

Digital input/output function options; source list portion — PDF page 71

Source row Function option or continuation V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 0: Two-wire forward /stop O O O O O O O ⟦blank source cell⟧
2 1: Two-wire reverse rotation/stop O O O O O O O ⟦blank source cell⟧
3 2: Multi-speed/location setting command 1 O O O O O O O ⟦blank source cell⟧
4 3: Multi-speed/location setting command 2 O O O O O O O ⟦blank source cell⟧
5 4: Multi-speed/location setting command 3 O O O O O O O ⟦blank source cell⟧
6 5: Multi-speed/location setting command 4 O O O O O O O ⟦blank source cell⟧
7 6: Jog forward command O O O O O O O ⟦blank source cell⟧
8 7: Jog reverse rotation command O O O O O O O ⟦blank source cell⟧
9 8: UP increase frequency command O O O O O O O ⟦blank source cell⟧
10 9: DOWN decrease frequency command O O O O O O O ⟦blank source cell⟧
11 10: Acceleration/deceleration time selection 1 O O O O O O O ⟦blank source cell⟧
12 11: Acceleration/deceleration prohibited O O O O O O O ⟦blank source cell⟧
13 12: Primary/secondary operation switching function O O O O O O O ⟦blank source cell⟧
14 13: Primary/secondary frequency switching function O O O O O O O ⟦blank source cell⟧
15 14: Emergency stop (decelerate to zero and stop) O O O O O O O ⟦blank source cell⟧
16 15: Cut-off stop (freely operate and stop) O O O O O O O ⟦blank source cell⟧
17 16: PID function prohibited O O O O O O O ⟦blank source cell⟧
18 17: Fault reset (RESET) O O O O O O O ⟦blank source cell⟧
19 18: Reserved - - - - - - - ⟦blank source cell⟧
20 19: Speed search 1 (from maximum frequency) O O O O O X O ⟦blank source cell⟧
21 20: Manual energy-saving function O O X X X X X ⟦blank source cell⟧
22 21: PID integral reset O O O O O O O ⟦blank source cell⟧
23 22: Reserved - - - - - - - ⟦blank source cell⟧
24 23: Reserved - - - - - - - ⟦blank source cell⟧
25 24: PLC input O O O O O O O ⟦blank source cell⟧
26 25: External fault O O O O O O O ⟦blank source cell⟧
27 26: Three-wire forward /reverse O O O O O O O ⟦blank source cell⟧
28 27: Local/remote selection O O O O O O O ⟦blank source cell⟧
29 28: Remote mode selection O O O O O O O ⟦blank source cell⟧
30 29: Jog frequency selection O O O O O O O ⟦blank source cell⟧
31 30: Acceleration/deceleration time selection 2 O O O O O O O ⟦blank source cell⟧
32 31: Inverter overheat early warning O O O O O O O ⟦blank source cell⟧
33 32: Synchronization command O O O O O O O ⟦blank source cell⟧
34 33: DC brake O O O O X X O ⟦blank source cell⟧
35 34: Speed search 2 (from frequency command) O O O O O X O ⟦blank source cell⟧
36 35: Timer function input O O O O O O O ⟦blank source cell⟧
37 36: PID soft start invalid O O O O O O O ⟦blank source cell⟧
38 37: Frequency skipping operation O O X X X X O ⟦blank source cell⟧
39 38: Frequency skipping upper offset O O X X X X O ⟦blank source cell⟧
40 39: Frequency skipping lower offset O O X X X X O ⟦blank source cell⟧
41 40: Motor 1/motor 2 switching O O X X X X X ⟦blank source cell⟧
42 41: PID sleep O O O O O O O ⟦blank source cell⟧
43 42: PG invalid X O X X X X X ⟦blank source cell⟧
44 43: PG integral reset X O X O O X X ⟦blank source cell⟧

Manual — Group 03 external terminal digital input/output function group — page 72

Manual reference: physical PDF page 72. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 03 external terminal digital input/output function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds. Neighboring option-list rows do not limit applicability to that printed code.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds. Source option list is separately represented from adjacent parameter metadata. No option-to-parameter relationship inferred from vertical alignment.

E710 parameter reference: Group 03 external terminal digital input/output function group — PDF page 72

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 03-08 (S1~S7) DI scan time 0: Scan time 4ms 1: Scan time 8ms 1 - O O O O O O O ⟦blank source cell⟧
2 03-09 Multi-function terminal S1-S4 type selection xxx0b: S1 A contact xxx1b:S1 B contact 0000b - O O O O O O O ⟦blank source cell⟧
3 03-09 Multi-function terminal S1-S4 type selection xx0xb: S2 A contact xx1xb:S2 B contact 0000b - O O O O O O O ⟦blank source cell⟧
4 03-09 Multi-function terminal S1-S4 type selection x0xxb: S3 A contact x1xxb:S3 B contact 0000b - O O O O O O O ⟦blank source cell⟧
5 03-09 Multi-function terminal S1-S4 type selection 0xxxb: S4 A contact 1xxxb:S4 B contact 0000b - O O O O O O O ⟦blank source cell⟧
6 03-10 Multi-function terminal S5-S7 type selection xxx0b: S5 A contact xxx1b:S5 B contact 0000b - O O O O O O O ⟦blank source cell⟧
7 03-10 Multi-function terminal S5-S7 type selection xx0xb: S6 A contact xx1xb:S6 B contact 0000b - O O O O O O O ⟦blank source cell⟧
8 03-10 Multi-function terminal S5-S7 type selection x0xxb: S7 A contact x1xxb:S7 B contact 0000b - O O O O O O O ⟦blank source cell⟧

Digital terminal parameter metadata; separate from function-option list — PDF page 72

Source row Code Parameter name Factory settings Unit
1 03-06 Multi-function terminal S7 function setting (Frame1 no S7) Two- wire: 29 Three- wire: 26 -
2 03-07 Reserved 15 -
3 03-11 Relay (R1A-R1C) output 1 [struck-through: (Note 4)] -

Digital input/output function options; source list portion — PDF page 72

Source row Function option or continuation V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 44: Speed/torque mode switching X X X O O X X ⟦blank source cell⟧
2 45: Negative torque command X X X O O X X ⟦blank source cell⟧
3 46: Zero-speed servo X X X O O X X ⟦blank source cell⟧
4 47: Fire mode (forced operation mode) O O O O O O O ⟦blank source cell⟧
5 48: KEB acceleration O O X X X X O ⟦blank source cell⟧
6 49: Allow parameter writing O O O O O O O ⟦blank source cell⟧
7 50: Direct operation protection after power is supplied (USP) O O O O O O O ⟦blank source cell⟧
8 51: Multi-speed and multi-point positioning command switching X X X O O X X ⟦blank source cell⟧
9 52: Position command enable X X X O O X X ⟦blank source cell⟧
10 53: Two-wire self-holding (stop command) O O O O O O O ⟦blank source cell⟧
11 54: Reserved - - - - - - - ⟦blank source cell⟧
12 55: RTC time enable O O O O O O O [struck-through: Note 8]
13 56: RTC offset enable O O O O O O O [struck-through: Note 8]
14 57: Reserved - - - - - - - ⟦blank source cell⟧
15 58: Safety function O O O O O O O ⟦blank source cell⟧
16 59: Reserved - - - - - - - ⟦blank source cell⟧
17 60: Reserved - - - - - - - ⟦blank source cell⟧
18 61: Reserved - - - - - - - ⟦blank source cell⟧
19 62: EPS input O O O O O O O ⟦blank source cell⟧
20 63: Switch to second set of pressure Range error O O O O O O O ⟦blank source cell⟧
21 64: Reserved - - - - - - - ⟦blank source cell⟧
22 65: Short-circuit brake command X X X X X O X [struck-through: Note 1]
23 66: PID function prohibited 2 O O O O O O O [struck-through: Note 4]
24 67: Handwheel mode switching O X X X X X X [struck-through: Note 4]
25 68: External fault 2 O O O O O O O [struck-through: Note 4]
26 69: External overload O O O O O O O [struck-through: Note 4]
27 70: Jog frequency operation O O O O O O O ⟦blank source cell⟧
28 0: Operation duration O O O O O O O ⟦blank source cell⟧
29 1: Fault indication O O O O O O O ⟦blank source cell⟧
30 2: Frequency reached O O O O O O O ⟦blank source cell⟧
31 3: Any frequency reached (03-13±03-14) O O O O O O O ⟦blank source cell⟧
32 4: Frequency detection 1 (Output frequency≧(03-13+03-14)) O O O O O O O ⟦blank source cell⟧
33 5: Frequency detection 2 (Output frequency≦(03-13+03-14)) O O O O O O O ⟦blank source cell⟧
34 6: Automatic restart O O O O O O O ⟦blank source cell⟧
35 7: Emergency stop O O O O O O O ⟦blank source cell⟧

Manual — Group 03 external terminal digital input/output function group — page 73

Manual reference: physical PDF page 73. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 03 external terminal digital input/output function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds. Neighboring option-list rows do not limit applicability to that printed code.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds. Source option list is separately represented from adjacent parameter metadata. No option-to-parameter relationship inferred from vertical alignment.

Digital terminal parameter metadata; separate from function-option list — PDF page 73

Source row Code Parameter name Factory settings Unit
1 03-12 (Note) Optocoupler output (DO1-DOG) 0 [struck-through: (Note 4)] -

Digital input/output function options; source list portion — PDF page 73

Source row Function option or continuation V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 8: Reserved - - - - - - - ⟦blank source cell⟧
2 9: Cut-off stop O O O O O O O ⟦blank source cell⟧
3 10~11: Reserved - - - - - - - ⟦blank source cell⟧
4 12: Over-torque detected O O O O O O O ⟦blank source cell⟧
5 13: Current reached O O O O O O O ⟦blank source cell⟧
6 14: Mechanical brake control (03-17~18) O O O O O O O ⟦blank source cell⟧
7 15~17: Reserved - - - - - - - ⟦blank source cell⟧
8 18: PLC status* O O O O O O O ⟦blank source cell⟧
9 19: PLC control* O O O O O O O ⟦blank source cell⟧
10 20: Zero speed O O O O O O O ⟦blank source cell⟧
11 21: Inverter standby O O O O O O O ⟦blank source cell⟧
12 22: Low voltage detected O O O O O O O ⟦blank source cell⟧
13 23: Operation command source O O O O O O O ⟦blank source cell⟧
14 24: Frequency command source O O O O O O O ⟦blank source cell⟧
15 25: Low-torque detected O O O O O O O ⟦blank source cell⟧
16 26: Frequency disconnected O O O O O O O ⟦blank source cell⟧
17 27: Timer function output O O O O O O O ⟦blank source cell⟧
18 28: Frequency skipping upper offset status O O X X X X O ⟦blank source cell⟧
19 29: Frequency skipping operation active O O X X X X O ⟦blank source cell⟧
20 30: Select motor 2 O O O O O O O ⟦blank source cell⟧
21 31: Zero-speed servo status (position mode) X X X O O X X ⟦blank source cell⟧
22 32: Communication control O O O O O O O ⟦blank source cell⟧
23 33: RTC timer 1 O O O O O O O [struck-through: Note 8]
24 34: RTC timer 2 O O O O O O O [struck-through: Note 8]
25 35: RTC timer 3 O O O O O O O [struck-through: Note 8]
26 36: RTC timer 4 O O O O O O O [struck-through: Note 8]
27 37: PID feedback disconnection detection output O O O O O O O ⟦blank source cell⟧
28 38: Brake release X X O O O X X ⟦blank source cell⟧
29 39: Frequency detected 1 (for overhead crane use) O O O X X X X ⟦blank source cell⟧
30 40: Frequency outputting X X X O O X X ⟦blank source cell⟧
31 41: Position reached (position mode) X X X O O X X ⟦blank source cell⟧
32 42: Overpressure O O X X X X X ⟦blank source cell⟧
33 43: Underpressure O O X X X X X ⟦blank source cell⟧
34 44: Pressure loss detection O O X X X X X ⟦blank source cell⟧
35 45: PID sleep O O O O O O O ⟦blank source cell⟧
36 46~49: Reserved - - - - - - - ⟦blank source cell⟧
37 50: Frequency detection 3 O O O O O O O ⟦blank source cell⟧

Manual — Group 03 external terminal digital input/output function group — page 74

Manual reference: physical PDF page 74. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 03 external terminal digital input/output function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds. Source option list is separately represented from adjacent parameter metadata. No option-to-parameter relationship inferred from vertical alignment.

E710 parameter reference: Group 03 external terminal digital input/output function group — PDF page 74

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 03-13 Frequency detection threshold 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
2 03-14 Frequency detection width 0.1~25.5 2.0 Hz O O O O O O O ⟦blank source cell⟧
3 03-15 Current reached threshold 0.1~999.9 0.1 A O O O O O O O ⟦blank source cell⟧
4 03-16 Current reached detection delay time 0.1~10.0 0.1 s O O O O O O O ⟦blank source cell⟧
5 03-17 *Mechanical brake release threshold setting 0.00~599.00 0.00 Hz O O O O O O O ⟦blank source cell⟧
6 03-18 *Mechanical brake action threshold setting 0.00~599.00 0.00 Hz O O O O O O O ⟦blank source cell⟧
7 03-19 Relay and DO1 type selection xxx0b: R1 A contact xxx1b: R1 B contact 0000b - O O O O O O O ⟦blank source cell⟧
8 03-19 Relay and DO1 type selection xx0xb: Optocoupler 1 A contact xx1xb: optocoupler 1 B contact 0000b - O O O O O O O ⟦blank source cell⟧
9 03-20 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 03-21 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 03-22 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 03-23 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
13 03-24 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 03-25 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 03-26 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 03-27 UP/DOWN frequency hold selection 0: Hold UP/DOWN frequency when stopped 0 - O O O O O O O ⟦blank source cell⟧
17 03-27 UP/DOWN frequency hold selection 1: Clear UP/DOWN frequency when stopped 0 - O O O O O O O ⟦blank source cell⟧
18 03-27 UP/DOWN frequency hold selection 2: Allow frequency UP/DOWN when stopped 0 - O O O O O O O ⟦blank source cell⟧
19 03-27 UP/DOWN frequency hold selection 3: Update frequency while accelerating. 0 - O O O O O O O ⟦blank source cell⟧
20 03-28 Optocoupler output (DO2-DOG) (Frame1 no DO2) The scope and definition are the same as 03-11, 03-12 (03-28 is set as 8 is the pulse output function) 0 - O O O O O O O ⟦blank source cell⟧
21 03-29 Optocoupler output type selection (DO2-DOG) xx0xb: Optocoupler 2 A contact xx1xb: Optocoupler 2 B contact 0000b - O O O O O O O ⟦blank source cell⟧
22 03-30 Pulse input selection 0: General pulse input 0 - O O O O O O O ⟦blank source cell⟧
23 03-30 Pulse input selection 1: PWM method 0 - O O O O O O O ⟦blank source cell⟧
24 03-31 Pulse input scale Set and adjust according to 03-30 03-30 set to 0: 50~32000Hz 1000 Hz O O O O O O O *1

Digital input/output function options; source list portion — PDF page 74

Source row Function option or continuation V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 (Output frequency≧(03-44+03-45)) ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 51: Frequency detection 4 (Output frequency≦(03-44+03-45)) O O O O O O O ⟦blank source cell⟧
3 52: Frequency detection 5 (Output frequency≧(03-46+03-47) O O O O O O O ⟦blank source cell⟧
4 53: Frequency detection 6 (Output frequency≦03-46+03-47) O O O O O O O ⟦blank source cell⟧
5 54: Short-circuit braking O O O O O O O [struck-through: Note 1]
6 57: Low current detected X X X X X O X [struck-through: Note 2]
7 58: Frequency deceleration detection O O O O O O O [struck-through: Note 4]
8 59: Over-temperature detected O O O O O O O [struck-through: Note 4]
9 60: Lifetime warning period O O O O O O O ⟦blank source cell⟧

Manual — Group 03 external terminal digital input/output function group — page 75

Manual reference: physical PDF page 75. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 03 external terminal digital input/output function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 03 external terminal digital input/output function group — PDF page 75

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 03-30 set to 1:10~1000Hz ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 03-32 Pulse input gain 0.0~1000.0 100 % O O O O O O O *1
3 03-33 Pulse input bias voltage -100.0~100.0 0.0 % O O O O O O O *1
4 03-34 Pulse input filter time 0.00~2.00 0.1 Sec O O O O O O O *1
5 03-35 Pulse output function setting 1: Frequency command 2 - O O O O O O O *1
6 03-35 Pulse output function setting 2: Output frequency 2 - O O O O O O O *1
7 03-35 Pulse output function setting 3: Output frequency after soft start 2 - O O O O O O O *1
8 03-35 Pulse output function setting 4: Motor speed 2 - O O O O O O O *1
9 03-35 Pulse output function setting 5: PID feedback 2 - O O O O O O O *1
10 03-35 Pulse output function setting 6: PID input 2 - O O O O O O O *1
11 03-35 Pulse output function setting 7: PG output (must be used with PG card) *Only for special cases 2 - O O O O O O O *1
12 03-36 Pulse input scale 1~32000 1000 Hz O O O O O O O *1
13 03-37 Timer ON delay (DI/DO) 0.0~6000.0 0.0 s O O O O O O O ⟦blank source cell⟧
14 03-38 Timer OFF delay (DI/DO) 0.0~6000.0 0.0 s O O O O O O O ⟦blank source cell⟧
15 03-39 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 03-40 Up/Down frequency bandwidth setting 0.00~5.00 0.00 Hz O O O O O O O ⟦blank source cell⟧
17 03-41 Torque detection threshold 0~150 10 % X X O O O X X ⟦blank source cell⟧
18 03-42 Braking action delay out 0.00~65.00 0.00 s X X O O O X X ⟦blank source cell⟧
19 03-43 UP/DOWN acceleration/deceler ation selection 0: Acceleration/deceleration time 1 0 - O O O O O O O ⟦blank source cell⟧
20 03-43 UP/DOWN acceleration/deceler ation selection 1: Acceleration/deceleration time 2 0 - O O O O O O O ⟦blank source cell⟧
21 03-44 Frequency detection threshold 2 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
22 03-45 Frequency detection width 2 0.1~25.5 2.0 Hz O O O O O O O ⟦blank source cell⟧
23 03-46 Frequency detection threshold 3 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
24 03-47 Frequency detection width 3 0.1~25.5 2.0 Hz O O O O O O O ⟦blank source cell⟧
25 03-48 Low current detected threshold 0.0~999.9 0.1 A O O O O O O O [struck-through: Note 2]
26 03-49 Low current detected delay time 0.00~655.34 (Note 4) 0.01 Sec O O O O O O O [struck-through: Note 2]
27 03-50 Frequency detection threshold 4 0.0~599.0 0.0 Hz O O O O O O O [struck-through: Note 3]
28 03-51 Frequency detection threshold 5 0.0~599.0 0.0 Hz O O O O O O O [struck-through: Note 3]
29 03-52 Frequency detection threshold 6 0.0~599.0 0.0 Hz O O O O O O O [struck-through: Note 3]
30 03-53 Current reached threshold 2 0.0~999.9 0 A O O O O O O O [struck-through: Note 4]
31 03-54 Counter ON delay. 0~12 0 Hr O O O O O O O ⟦blank source cell⟧
32 03-55 Counter OFF delay. 0~12 0 Hr O O O O O O O ⟦blank source cell⟧
33 03-57 Emergency stop action setting 0: Automatically reset ES after stopped 0 - O O O O O O O ⟦blank source cell⟧
34 03-57 Emergency stop action setting 1: ES reset command: DI 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 03 external terminal digital input/output function group — page 76

Manual reference: physical PDF page 76. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 03 external terminal digital input/output function group

V/F+PG, SV, PMSV are only for special projects.

Group 04 external terminal analog input/output function group

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 03 external terminal digital input/output function group — PDF page 76

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 03-58 Communication control S1~S4 type selection xxx0b: S1 external input xxx1b: S1 communication control 0000b - O O O O O O O ⟦blank source cell⟧
2 03-58 Communication control S1~S4 type selection xx0xb: S2 external input xx1xb: S2 communication control 0000b - O O O O O O O ⟦blank source cell⟧
3 03-58 Communication control S1~S4 type selection x0xxb: S3 external input x1xxb: S3 communication control 0000b - O O O O O O O ⟦blank source cell⟧
4 03-58 Communication control S1~S4 type selection 0xxxb: S4 external input 1xxxb: S4 communication control 0000b - O O O O O O O ⟦blank source cell⟧
5 03-59 Communication control S5~S7 type selection (Frame1 no S7) xxx0b: S5 external input xxx1b: S5 communication control 0000b - O O O O O O O ⟦blank source cell⟧
6 03-59 Communication control S5~S7 type selection (Frame1 no S7) xx0xb: S6 external input xx1xb: S6 communication control 0000b - O O O O O O O ⟦blank source cell⟧
7 03-59 Communication control S5~S7 type selection (Frame1 no S7) x0xxb: S7 external input x1xxb: S7 communication control 0000b - O O O O O O O ⟦blank source cell⟧

Group04 external terminal analog input/output function group — PDF page 76

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 04-00 AI input signal type (Frame1 no AI2) 0: AI1:0~10V AI2: 0~10V 1 - O O O O O O O ⟦blank source cell⟧
2 04-00 AI input signal type (Frame1 no AI2) 1: AI1:0~10V AI2: 4~20mA 1 - O O O O O O O ⟦blank source cell⟧
3 04-00 AI input signal type (Frame1 no AI2) 2: Reserved 1 - O O O O O O O ⟦blank source cell⟧
4 04-00 AI input signal type (Frame1 no AI2) 3: Reserved 1 - O O O O O O O ⟦blank source cell⟧
5 04-00 AI input signal type (Frame1 no AI2) 4: AI1: 4~20mA AI2: 0~10V 1 - O O O O O O O *9
6 04-00 AI input signal type (Frame1 no AI2) 5: AI1: 4~20mA AI2: 4~20mA 1 - O O O O O O O *9
7 04-01 AI1 signal scan filter time 0.00~2.00 0.03 s O O O O O O O ⟦blank source cell⟧
8 04-02 AI1 gain 0.0~1000.0 100.0 % O O O O O O O *1
9 04-03 AI1 bias voltage -100.0~100.0 0 % O O O O O O O *1
10 04-04 AI negative characteristic 0: Invalid 0 - O O O O O O O [struck-through: Note 4]
11 04-04 AI negative characteristic 1: Valid 0 - O O O O O O O [struck-through: Note 4]
12 04-05 AI2 function setting (Frame1 no AI2) 0: Auxiliary frequency 10 - O O O O O O O ⟦blank source cell⟧
13 04-05 AI2 function setting (Frame1 no AI2) 1: Frequency gain 10 - O O O O O O O ⟦blank source cell⟧
14 04-05 AI2 function setting (Frame1 no AI2) 2: Frequency bias voltage 10 - O O O O O O O ⟦blank source cell⟧
15 04-05 AI2 function setting (Frame1 no AI2) 3: Voltage bias voltage 10 - O O X X O O O ⟦blank source cell⟧
16 04-05 AI2 function setting (Frame1 no AI2) 4: Acceleration/deceleration shortening coefficient 10 - O O O O O O O ⟦blank source cell⟧
17 04-05 AI2 function setting (Frame1 no AI2) 5: DC brake current 10 - O O O O X X O ⟦blank source cell⟧
18 04-05 AI2 function setting (Frame1 no AI2) 6: Overtorque detection threshold 10 - O O O O O O O ⟦blank source cell⟧
19 04-05 AI2 function setting (Frame1 no AI2) 7: Stall threshold during operation 10 - O O X X X X O ⟦blank source cell⟧
20 04-05 AI2 function setting (Frame1 no AI2) 8: Frequency lower limit 10 - O O O O O O O ⟦blank source cell⟧
21 04-05 AI2 function setting (Frame1 no AI2) 9: Jump frequency 4 10 - O O O O O O O ⟦blank source cell⟧
22 04-05 AI2 function setting (Frame1 no AI2) 10: Add to AI1 10 - O O O O O O O ⟦blank source cell⟧
23 04-05 AI2 function setting (Frame1 no AI2) 11: Forward torque limit 10 - X X O O O O X ⟦blank source cell⟧
24 04-05 AI2 function setting (Frame1 no AI2) 12: Negative torque limit 10 - X X O O O O X ⟦blank source cell⟧
25 04-05 AI2 function setting (Frame1 no AI2) 13: Regenerative torque limit 10 - X X O O O O X ⟦blank source cell⟧
26 04-05 AI2 function setting (Frame1 no AI2) 14: Positive/negative torque limit 10 - X X O O O O X ⟦blank source cell⟧
27 04-05 AI2 function setting (Frame1 no AI2) 15: Torque command/torque limit 10 - X X X O O X X ⟦blank source cell⟧

Manual — Group 04 external terminal analog input/output function group — page 77

Manual reference: physical PDF page 77. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 04 external terminal analog input/output function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 04 external terminal analog input/output function group — PDF page 77

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 16: Torque command/torque compensation ⟦blank source cell⟧ ⟦blank source cell⟧ X X O O O X X ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ 17: PTC overheat protection ⟦blank source cell⟧ ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
3 04-06 AI2 signal scan filter time 0.00~2.00 0.03 s O O O O O O O ⟦blank source cell⟧
4 04-07 AI2 gain 0.0~1000.0 100.0 % O O O O O O O *1
5 04-08 AI2 bias voltage -100.0~100.0 0 % O O O O O O O *1
6 04-09 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 04-10 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 04-11 AO1 function setting 0: Output frequency 0 - O O O O O O O ⟦blank source cell⟧
9 04-11 AO1 function setting 1: Frequency command 0 - O O O O O O O ⟦blank source cell⟧
10 04-11 AO1 function setting 2: Output voltage 0 - O O O O O O O ⟦blank source cell⟧
11 04-11 AO1 function setting 3: DC voltage 0 - O O O O O O O ⟦blank source cell⟧
12 04-11 AO1 function setting 4: Output current 0 - O O O O O O O ⟦blank source cell⟧
13 04-11 AO1 function setting 5: Output power 0 - O O O O O O O ⟦blank source cell⟧
14 04-11 AO1 function setting 6: Motor speed 0 - O O O O O O O ⟦blank source cell⟧
15 04-11 AO1 function setting 7: Output power factor 0 - O O O O O O O ⟦blank source cell⟧
16 04-11 AO1 function setting 8: AI1 input 0 - O O O O O O O ⟦blank source cell⟧
17 04-11 AO1 function setting 9: AI2 input 0 - O O O O O O O ⟦blank source cell⟧
18 04-11 AO1 function setting 10: Torque command 0 - X X O O O O X ⟦blank source cell⟧
19 04-11 AO1 function setting 11: q-axis current (Frame2 and above reserved) 0 - X X O O O O X ⟦blank source cell⟧
20 04-11 AO1 function setting 12: d-axis current (Frame2 and above reserved) 0 - X X O O O O X ⟦blank source cell⟧
21 04-11 AO1 function setting 13: Speed deviation 0 - X X X O O X X ⟦blank source cell⟧
22 04-11 AO1 function setting 14: Reserved 0 - - - - - - - - ⟦blank source cell⟧
23 04-11 AO1 function setting 15: ASR output 0 - X O X O O X X ⟦blank source cell⟧
24 04-11 AO1 function setting 16: Reserved 0 - - - - - - - - ⟦blank source cell⟧
25 04-11 AO1 function setting 17: q-axis voltage (Frame2 and above reserved) 0 - X X O O O O X ⟦blank source cell⟧
26 04-11 AO1 function setting 18: d-axis voltage (Frame2 and above reserved) 0 - X X O O O O X ⟦blank source cell⟧
27 04-11 AO1 function setting 19~20: Reserved 0 - - - - - - - - ⟦blank source cell⟧
28 04-11 AO1 function setting 21: PID input 0 - O O O O O O O ⟦blank source cell⟧
29 04-11 AO1 function setting 22: PID output 0 - O O O O O O O ⟦blank source cell⟧
30 04-11 AO1 function setting 23: PID target value 0 - O O O O O O O ⟦blank source cell⟧
31 04-11 AO1 function setting 24: PID feedback value 0 - O O O O O O O ⟦blank source cell⟧
32 04-11 AO1 function setting 25: Soft starter output frequency 0 - O O O O O O O ⟦blank source cell⟧
33 04-11 AO1 function setting 26: PG feedback 0 - X O X O O X X ⟦blank source cell⟧
34 04-11 AO1 function setting 27: Reserved 0 - - - - - - - - ⟦blank source cell⟧
35 04-11 AO1 function setting 28: Communication control 0 - O O O O O O O ⟦blank source cell⟧
36 04-12 AO1 gain 0.0~1000.0 100.0 % O O O O O O O *1
37 04-13 AO1 bias voltage -100.0~100.0 0 % O O O O O O O *1
38 04-14 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
39 04-15 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 04-16 AO2 function setting The scope and definition are the same as 04-11 3 - O O O O O O O ⟦blank source cell⟧
41 04-17 AO2 gain 0.0~1000.0 100.0 % O O O O O O O *1
42 04-18 AO2 bias voltage -100.0~100.0 0 % O O O O O - ⟦blank source cell⟧ *1
43 04-19 AO output signal type 0: AO1 0~10V AO2 0~10V 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 04 external terminal analog input/output function group — page 78

Manual reference: physical PDF page 78. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 04 external terminal analog input/output function group

V/F+PG, SV, PMSV are only for special projects.

Group 05 multi-stage function group

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 04 external terminal analog input/output function group — PDF page 78

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 1: AO1 0~10V AO2 4~20mA ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ 2: AO1 4~20mA AO2 0~10V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ *9
3 ⟦blank source cell⟧ ⟦blank source cell⟧ 3: AO1 4~20mA AO2 4~20mA ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ *9
4 04-20 AO signal scan filter time 0.00~0.50 0.00 s O O O O O O O *1
5 04-21 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 04-22 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 04-23 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 04-24 Frequency display filter 0.00~3.00 0.00 - O O O O O O O ⟦blank source cell⟧
9 04-25 AI1 filter parameter 0.00~3.00 0.00 - O O O O O O O ⟦blank source cell⟧
10 04-26 AI1 value average filter 0 ~255 0 - O O O O O O O ⟦blank source cell⟧
11 04-27 Output frequency display value average filter 0 ~255 0 - O O O O O O O ⟦blank source cell⟧

Group05 multi-stage function group — PDF page 78

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 05-00 Multi-speed acceleration/deceleration mode selection 0: Segment speed acceleration/deceleration time set by acceleration/deceleration time 1~4 0 - O O O O O O O ⟦blank source cell⟧
2 05-00 Multi-speed acceleration/deceleration mode selection 1: Segment speed acceleration/deceleration time independent setting 0 - O O O O O O O ⟦blank source cell⟧
3 05-01 *Segment 0 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
4 05-02 *Segment 1 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
5 05-03 *Segment 2 speed frequency setting 0.00~599.00 10.00 Hz O O O O O O O *1
6 05-04 *Segment 3 speed frequency setting 0.00~599.00 20.00 Hz O O O O O O O *1
7 05-05 *Segment 4 speed frequency setting 0.00~599.00 30.00 Hz O O O O O O O *1
8 05-06 *Segment 5 speed frequency setting 0.00~599.00 40.00 Hz O O O O O O O *1
9 05-07 *Segment 6 speed frequency setting 0.00~599.00 50.00 Hz O O O O O O O *1
10 05-08 *Segment 7 speed frequency setting 0.00~599.00 50.00 Hz O O O O O O O *1
11 05-09 *Segment 8 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
12 05-10 *Segment 9 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
13 05-11 *Segment 10 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
14 05-12 *Segment 11 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
15 05-13 *Segment 12 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1

Manual — Group 05 multi-stage function group — page 79

Manual reference: physical PDF page 79. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 05 multi-stage function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 05 multi-stage function group — PDF page 79

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 05-14 *Segment 13 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
2 05-15 *Segment 14 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
3 05-16 *Segment 15 speed frequency setting 0.00~599.00 5.00 Hz O O O O O O O *1
4 05-17 Multi-speed 0 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
5 05-18 Multi-speed 0 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
6 05-19 Multi-speed 1 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
7 05-20 Multi-speed 1 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
8 05-21 Multi-speed 2 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
9 05-22 Multi-speed 2 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
10 05-23 Multi-speed 3 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
11 05-24 Multi-speed 3 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
12 05-25 Multi-speed 4 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
13 05-26 Multi-speed 4 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
14 05-27 Multi-speed 5 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
15 05-28 Multi-speed 5 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
16 05-29 Multi-speed 6 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
17 05-30 Multi-speed 6 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
18 05-31 Multi-speed 7 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
19 05-32 Multi-speed 7 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
20 05-33 Multi-speed 8 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
21 05-34 Multi-speed 8 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
22 05-35 Multi-speed 9 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
23 05-36 Multi-speed 9 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
24 05-37 Multi-speed 10 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
25 05-38 Multi-speed 10 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
26 05-39 Multi-speed 11 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
27 05-40 Multi-speed 11 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
28 05-41 Multi-speed 12 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
29 05-42 Multi-speed 12 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
30 05-43 Multi-speed 13 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
31 05-44 Multi-speed 13 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧

Manual — Group 05 multi-stage function group — page 80

Manual reference: physical PDF page 80. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 05 multi-stage function group

V/F+PG, SV, PMSV are only for special projects.

Group 06 automatic operation function group

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 05 multi-stage function group — PDF page 80

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 05-45 Multi-speed 14 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
2 05-46 Multi-speed 14 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
3 05-47 Multi-speed 15 acceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧
4 05-48 Multi-speed 15 deceleration time setting 0.1~6000.0 10.0 s O O O O O O O ⟦blank source cell⟧

Group06 automatic operation function group — PDF page 80

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 06-00 Automatic operation mode selection 0: Invalid 0 - O O O X X X O ⟦blank source cell⟧
2 06-00 Automatic operation mode selection 1: Execute a single cycle of operation mode, then after stopped, it will continue to operate with the speed before stopping 0 - O O O X X X O ⟦blank source cell⟧
3 06-00 Automatic operation mode selection 2: Continuous cycle operation mode, after it stopped, it will continue to operate with the speed before stopping 0 - O O O X X X O ⟦blank source cell⟧
4 06-00 Automatic operation mode selection 3: After a single cycle ends, it will continue operating with the last segment of operation speed, then after it stopped, it will continue operating with the speed before it stopped 0 - O O O X X X O ⟦blank source cell⟧
5 06-00 Automatic operation mode selection 4: Execute a single cycle operation mode, after it stopped, it will start operating from the zero segment speed 0 - O O O X X X O ⟦blank source cell⟧
6 06-00 Automatic operation mode selection 5: Continuous cycle operation mode, after it stopped, it will start operating from the zero segment speed 0 - O O O X X X O ⟦blank source cell⟧
7 06-00 Automatic operation mode selection 6: After a single cycle ends, continue operating using the final segment of operation speed, then after it stops, start operating from the zero segment speed 0 - O O O X X X O ⟦blank source cell⟧
8 06-01 *Segment 1 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
9 06-02 *Segment 2 operation frequency setting 0.00~599.00 10.00 Hz O O O X X X O *1
10 06-03 *Segment 3 operation frequency setting 0.00~599.00 20.00 Hz O O O X X X O *1
11 06-04 *Segment 4 operation frequency setting 0.00~599.00 30.00 Hz O O O X X X O *1
12 06-05 *Segment 5 operation frequency setting 0.00~599.00 40.00 Hz O O O X X X O *1
13 06-06 *Segment 6 operation frequency setting 0.00~599.00 50.00 Hz O O O X X X O *1
14 06-07 *Segment 7 operation frequency setting 0.00~599.00 50.00 Hz O O O X X X O *1
15 06-08 *Segment 8 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
16 06-09 *Segment 9 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1

Manual — Group 06 automatic operation function group — page 81

Manual reference: physical PDF page 81. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 06 automatic operation function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 06 automatic operation function group — PDF page 81

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 06-10 *Segment 10 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
2 06-11 *Segment 11 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
3 06-12 *Segment 12 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
4 06-13 *Segment 13 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
5 06-14 *Segment 14 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
6 06-15 *Segment 15 operation frequency setting 0.00~599.00 5.00 Hz O O O X X X O *1
7 06-16 Segment 0 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
8 06-17 Segment 1 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
9 06-18 Segment 2 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
10 06-19 Segment 3 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
11 06-20 Segment 4 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
12 06-21 Segment 5 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
13 06-22 Segment 6 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
14 06-23 Segment 7 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
15 06-24 Segment 8 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
16 06-25 Segment 9 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
17 06-26 Segment 10 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
18 06-27 Segment 11 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
19 06-28 Segment 12 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
20 06-29 Segment 13 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
21 06-30 Segment 14 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
22 06-31 Segment 15 operation time setting 0.0~6000.0 0.0 s O O O X X X O *1
23 06-32 Segment 0 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
24 06-33 Segment 1 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
25 06-34 Segment 2 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
26 06-35 Segment 3 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
27 06-36 Segment 4 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
28 06-37 Segment 5 operation 0: Stop 1: Forward operation 2: 0 - O O O X X X O ⟦blank source cell⟧

Manual — Group 06 automatic operation function group — page 82

Manual reference: physical PDF page 82. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 06 automatic operation function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 06 automatic operation function group — PDF page 82

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ direction selection Reverse ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 06-38 Segment 6 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
3 06-39 Segment 7 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
4 06-40 Segment 8 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
5 06-41 Segment 9 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
6 06-42 Segment 10 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
7 06-43 Segment 11 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
8 06-44 Segment 12 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
9 06-45 Segment 13 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
10 06-46 Segment 14 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧
11 06-47 Segment 15 operation direction selection 0: Stop 1: Forward operation 2: Reverse 0 - O O O X X X O ⟦blank source cell⟧

Manual — Group 07 operation stop function group — page 83

Manual reference: physical PDF page 83. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 07 operation stop function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 07 operation stop function group — PDF page 83

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 07-00 Instantaneously stop and restart selection 0: Instantaneously stop and restart invalid 0 - O O O O X O O ⟦blank source cell⟧
2 07-00 Instantaneously stop and restart selection 1: Instantaneously stop and restart effective 0 - O O O O X O O ⟦blank source cell⟧
3 07-01 Automatic reset restart time 0~7200 0 s O O O O O O O ⟦blank source cell⟧
4 07-02 Automatic reset restart count 0~10 0 - O O O O O O O ⟦blank source cell⟧
5 07-03 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 07-04 Start directly after power on 0: When the external operation command is valid, start directly after power is supplied 1 - O O O O O O O ⟦blank source cell⟧
7 07-04 Start directly after power on 1: When external operation command is valid, do not start directly after power is supplied 1 - O O O O O O O ⟦blank source cell⟧
8 07-05 Start delay directly after power on 1.0~300.0 3.5 s O O O O O O O ⟦blank source cell⟧
9 07-06 Brake start frequency 0.0~10.0 0.5 Hz O O O O O O O ⟦blank source cell⟧
10 07-07 DC brake current threshold 0~100 50 % O O O X X O O ⟦blank source cell⟧
11 07-08 DC braking time during stop 0.00~100.00 0.50 s O O O O O O O ⟦blank source cell⟧
12 07-09 Stop mode selection 0: Decelerate to stop 0 - O O O O O O O ⟦blank source cell⟧
13 07-09 Stop mode selection 1: Free-run stop 0 - O O O O O O O ⟦blank source cell⟧
14 07-09 Stop mode selection 2: Full-range DC brake stop 0 - O O O O X X O ⟦blank source cell⟧
15 07-09 Stop mode selection 3: Free-run stop with timer 0 - O O O O O O O ⟦blank source cell⟧
16 07-10 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 07-11 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 07-12 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 07-13 Low voltage detection threshold 200V models: 150~300 190 V O O O O O O O ⟦blank source cell⟧
20 07-13 Low voltage detection threshold 400V models: 250~600 380 V O O O O O O O ⟦blank source cell⟧
21 07-14 Pre-excitation time 0.00~10.00 2.00 s X X O X X X X ⟦blank source cell⟧
22 07-15 Pre-excitation threshold 50~200 100 % X X O X X X X ⟦blank source cell⟧
23 07-16 DC braking time during start 0.00~100.00 0.00 s O O O O O O O ⟦blank source cell⟧
24 07-17 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 07-18 Minimum cut-off time 0.1~5.0 - Sec O O O O X O O ⟦blank source cell⟧
26 07-19 Direction seeking current 0~100 50 % O X O X X X O ⟦blank source cell⟧
27 07-20 Speed seeking current 0~100 20 % O X O X X X O ⟦blank source cell⟧
28 07-21 Speed seeking integral time 0.1~10.0 2.0 Sec O X O X X X O ⟦blank source cell⟧
29 07-22 Speed seeking delay time 0.0~20.0 0.2 Sec O O O O O X O ⟦blank source cell⟧
30 07-23 Voltage recovery time 0.1~5.0 2.0 Sec O O O X X X O ⟦blank source cell⟧
31 07-24 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 07-25 Low voltage detection time 0.00~1.00 0.02 Sec O O O O O O O ⟦blank source cell⟧
33 07-26 SLV selection of starting method after free-run stop 0: Speed seeking start 0 - X X O X X X X ⟦blank source cell⟧
34 07-26 SLV selection of starting method after free-run stop 1: Normal start 0 - X X O X X X X ⟦blank source cell⟧
35 07-27 SLV start method selection after malfunction 0: Speed seeking start 0 - X X O X X X X ⟦blank source cell⟧
36 07-27 SLV start method selection after malfunction 1: Normal start 0 - X X O X X X X ⟦blank source cell⟧

Manual — Group 07 operation stop function group — page 84

Manual reference: physical PDF page 84. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 07 operation stop function group

V/F+PG, SV, PMSV are only for special projects.

Note: 07-13 low voltage detection threshold 440V models need to select and set the 07-30 low voltage threshold as valid, and then adjust the lower limit to 250V. This applies to elevator function with EPS system (Emergency power supply) use.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 07 operation stop function group — PDF page 84

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 07-28 Start method selection after cut-off 0: Speed seeking start 0 - O X O X X X O ⟦blank source cell⟧
2 07-28 Start method selection after cut-off 1: Normal start 0 - O X O X X X O ⟦blank source cell⟧
3 07-29 Operation command selection during DC braking 0: Not allowed to start during the process 0 - O O X X X X X ⟦blank source cell⟧
4 07-29 Operation command selection during DC braking 1: Allowed to start during the process 0 - O O X X X X X ⟦blank source cell⟧
5 07-30 Low voltage threshold selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
6 07-30 Low voltage threshold selection 1: Valid 0 - O O O O O O O ⟦blank source cell⟧
7 07-31 *Low voltage operation frequency 0.00~599.00 10.00 Hz X X X O O X X ⟦blank source cell⟧
8 07-32 Speed seeking mode selection 0: Invalid 0 - O O O O X O X ⟦blank source cell⟧
9 07-32 Speed seeking mode selection 1: Mode1: Execute speed seeking once after power on 0 - O O O O X O X ⟦blank source cell⟧
10 07-32 Speed seeking mode selection 2: Mode2: Execute speed seeking every time 0 - O O O O X O X ⟦blank source cell⟧
11 07-33 Speed seeking start frequency selection 0: Motor maximum output frequency 0 - O O O O X X X ⟦blank source cell⟧
12 07-33 Speed seeking start frequency selection 1: Frequency command 0 - O O O O X X X ⟦blank source cell⟧
13 07-34 Short-circuit brake time while starting 0.00~100.00 0.00 Sec X X X X X O X [struck-through: Note 1]
14 07-35 Short-circuit brake time while stopping 0.00~100.00 0.50 Sec X X X X X O X [struck-through: Note 1]
15 07-36 Short-circuit brake current limit 0.0~200.0 100.0 % X X X X X O X [struck-through: Note 1]
16 07-37 ~ 07-41 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 07-42 Voltage limit gain 0.0~50.0 0 % X X O O X X X [struck-through: Note 2]
18 07-43 PM speed seeking short- circuit brake time 0.00~100.00 0.00 Sec X X X X X O X [struck-through: Note 3]
19 07-44 PM speed seeking DC brake time 0.00~100.00 0.00 Sec X X X X X O X [struck-through: Note 3]
20 07-45 STP2 function selection 0: Valid 0 - O O O O O O O [struck-through: Note 4]
21 07-45 STP2 function selection 1: Invalid 0 - O O O O O O O [struck-through: Note 4]
22 07-46 DC injection current limit 0~150 100 % O X X X X X X [struck-through: Note 5]
23 07-47 PM speed switching frequency mode 0: Invalid 0 - X X X X X O X [struck-through: Note 8]
24 07-47 PM speed switching frequency mode 1: Mode 1 0 - X X X X X O X [struck-through: Note 8]
25 07-47 PM speed switching frequency mode 2: Mode 2 0 - X X X X X O X [struck-through: Note 8]

Manual — Group 08 protection function group — page 85

Manual reference: physical PDF page 85. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 08 protection function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 08 protection function group — PDF page 85

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 08-00 Stall prevention function xxx0b: Stall prevention effective during acceleration 0000b - O O O O O O O ⟦blank source cell⟧
2 08-00 Stall prevention function xxx1b: Stall prevention ineffective during acceleration 0000b - O O O O O O O ⟦blank source cell⟧
3 08-00 Stall prevention function xx0xb: Stall prevention effective during deceleration 0000b - O O O O O O O ⟦blank source cell⟧
4 08-00 Stall prevention function xx1xb: Stall prevention ineffective during deceleration 0000b - O O O O O O O ⟦blank source cell⟧
5 08-00 Stall prevention function x0xxb: Stall prevention effective during operation 0000b - O O O O O O O ⟦blank source cell⟧
6 08-00 Stall prevention function x1xxb: Stall prevention ineffective during operation 0000b - O O O O O O O ⟦blank source cell⟧
7 08-00 Stall prevention function 0xxxb: Stall prevention during operation is in accordance with stage one deceleration time 0000b - O O O O O O O ⟦blank source cell⟧
8 08-00 Stall prevention function 1xxxb: Stall prevention during operation is in accordance with stage two deceleration time 0000b - O O O O O O O ⟦blank source cell⟧
9 08-01 Acceleration stall prevention threshold 20~200 150 % O O O X X O O ⟦blank source cell⟧
10 08-02 Deceleration stall prevention threshold 200V: 330V~410V 385V V O O O O X O O ⟦blank source cell⟧
11 08-02 Deceleration stall prevention threshold 400V: 660V~820V 770V V O O O O X O O ⟦blank source cell⟧
12 08-03 Stall prevention threshold during operation 30~200 160 % O O X X X X O ⟦blank source cell⟧
13 08-04 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 08-05 Motor overload (OL1) protection selection xxx0b: Motor overload ineffective 0001b - O O O O O O O ⟦blank source cell⟧
15 08-05 Motor overload (OL1) protection selection xxx1b: Motor overload effective 0001b - O O O O O O O ⟦blank source cell⟧
16 08-05 Motor overload (OL1) protection selection xx0xb: Motor overload cold start 0001b - O O O O O O O ⟦blank source cell⟧
17 08-05 Motor overload (OL1) protection selection xx1xb: Motor overload hot start 0001b - O O O O O O O ⟦blank source cell⟧
18 08-05 Motor overload (OL1) protection selection x0xxb: Standard motor 0001b - O O O O O O O ⟦blank source cell⟧
19 08-05 Motor overload (OL1) protection selection x1xxb: Variable frequency motor 0001b - O O O O O O O ⟦blank source cell⟧
20 08-05 Motor overload (OL1) protection selection 0xxxb: Reserved 0001b - O O O O O O O ⟦blank source cell⟧
21 08-05 Motor overload (OL1) protection selection 1xxxb: Reserved 0001b - O O O O O O O ⟦blank source cell⟧
22 08-06 Overload (OL1) protection action start method 0: Stop output after overload protection 0 - O O O O O O O ⟦blank source cell⟧
23 08-06 Overload (OL1) protection action start method 1: Continue operation after overload protection 0 - O O O O O O O ⟦blank source cell⟧
24 08-07 Motor overload (OL1) protection threshold 0: Motor overload (OL1) protection 0 0 - O O O O O O O [struck-through: Note 2]
25 08-07 Motor overload (OL1) protection threshold 1: Motor overload (OL1) protection 1 0 - O O O O O O O [struck-through: Note 2]
26 08-07 Motor overload (OL1) protection threshold 2: Motor overload (OL1) protection 2 0 - O O O O O O O [struck-through: Note 2]
27 08-08 Automatic voltage regulation function (AVR) 0: Valid 0 - O O O O O O O ⟦blank source cell⟧
28 08-08 Automatic voltage regulation function (AVR) 1: Invalid 0 - O O O O O O O ⟦blank source cell⟧
29 08-09 Input phase loss protection selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
30 08-09 Input phase loss protection selection 1: Valid 0 - O O O O O O O ⟦blank source cell⟧
31 08-10 Output phase loss protection selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
32 08-10 Output phase loss protection selection 1: Valid 0 - O O O O O O O ⟦blank source cell⟧
33 08-11 08-12 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 08-13 Overtorque detection selection 0: Overtorque detection ineffective 0 - O O O O O O O ⟦blank source cell⟧
35 08-13 Overtorque detection selection 1: Detection begins after 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 08 protection function group — page 86

Manual reference: physical PDF page 86. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 08 protection function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 08 protection function group — PDF page 86

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ reaching set frequency ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ 2: Detection during operation ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 08-14 Overtorque action selection 0: Deceleration stop after detection 0 - O O O O O O O ⟦blank source cell⟧
4 08-14 Overtorque action selection 1: Display warning and continue operation after detection 0 - O O O O O O O ⟦blank source cell⟧
5 08-14 Overtorque action selection 2: Free-run stop after detection 0 - O O O O O O O ⟦blank source cell⟧
6 08-15 Overtorque detection threshold 0~300 150 % O O O O O O O ⟦blank source cell⟧
7 08-16 Overtorque detection time 0.0~10.0 0.1 Sec O O O O O O O ⟦blank source cell⟧
8 08-17 Undertorque detection selection 0: Undertorque detection ineffective 0 - O O O O O O O ⟦blank source cell⟧
9 08-17 Undertorque detection selection 1: Detection begins after reaching set frequency 0 - O O O O O O O ⟦blank source cell⟧
10 08-17 Undertorque detection selection 2: Detection during operation 0 - O O O O O O O ⟦blank source cell⟧
11 08-18 Undertorque action selection 0: Deceleration stop after detection 0 - O O O O O O O ⟦blank source cell⟧
12 08-18 Undertorque action selection 1: Display warning and continue operation after detection 0 - O O O O O O O ⟦blank source cell⟧
13 08-18 Undertorque action selection 2: Free-run stop after detection 0 - O O O O O O O ⟦blank source cell⟧
14 08-19 Undertorque detection threshold 0~300 30 % O O O O O O O ⟦blank source cell⟧
15 08-20 Undertorque detection time 0.0~10.0 0.1 Sec O O O O O O O ⟦blank source cell⟧
16 08-21 Acceleration stall prevention limit 1~100 50 % O O O X X O O ⟦blank source cell⟧
17 08-22 Operation stall detection time 2~100 100 ms O O O X X O O ⟦blank source cell⟧
18 08-23 Grounding failure (GF) selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
19 08-23 Grounding failure (GF) selection 1: Valid 0 - O O O O O O O ⟦blank source cell⟧
20 08-24 External fault operation selection 0: Decelerate to stop 0 - O O O O O O O ⟦blank source cell⟧
21 08-24 External fault operation selection 1: Free-run stop 0 - O O O O O O O ⟦blank source cell⟧
22 08-24 External fault operation selection 2: Continues operation 0 - O O O O O O O ⟦blank source cell⟧
23 08-25 External fault detection selection 0: Detection upon power-on 0 - O O O O O O O ⟦blank source cell⟧
24 08-25 External fault detection selection 1: Detection active only during operation 0 - O O O O O O O ⟦blank source cell⟧
25 08-26 ~ 08-29 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 08-30 Safety function selection 0: Decelerate to stop 0 - O O O O O O O ⟦blank source cell⟧
27 08-30 Safety function selection 1: Free-run stop 0 - O O O O O O O ⟦blank source cell⟧
28 08-31 ~ 08-34 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 08-35 Motor overheat fault selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
30 08-35 Motor overheat fault selection 1: Decelerate to stop 0 - O O O O O O O ⟦blank source cell⟧
31 08-35 Motor overheat fault selection 2: Free-run stop 0 - O O O O O O O ⟦blank source cell⟧
32 08-35 Motor overheat fault selection 3: Continue operating 0 - O O O O O O O ⟦blank source cell⟧
33 08-36 PTC input filter time constant 0.00 ~ 5.00 2.00 Sec O O O O O O O ⟦blank source cell⟧
34 08-37 Fan control function 0: Start during operation 2 [source strikes through 0] ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
35 08-37 Fan control function 1: Always start 2 [source strikes through 0] ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
36 08-37 Fan control function 2: Start during high temperature (note) 2 [source strikes through 0] ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
37 08-38 Fan close delay time 0~600 60 sec O O O O O O O ⟦blank source cell⟧
38 08-39 Motor overheat 1~300 60 sec O O O O O O O ⟦blank source cell⟧

Manual — Group 08 protection function group — page 87

Manual reference: physical PDF page 87. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 08 protection function group

V/F+PG, SV, PMSV are only for special projects.

Note: 200V 50HP and above and 400V 100HP and above models do not have the option to start fan control when there is high temperature

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 08 protection function group — PDF page 87

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ protection delay time ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 08-40 Motor 2 acceleration stall prevention threshold 20~200 150 % O O X X X X O ⟦blank source cell⟧
3 08-41 Motor 2 acceleration stall prevention limit 1~100 50 % O O X X X X O ⟦blank source cell⟧
4 08-42 PTC protection threshold 0.1~10.0V 0.7 V O O O O O O O ⟦blank source cell⟧
5 08-43 PTC reset threshold 0.1~10.0V 0.3 V O O O O O O O ⟦blank source cell⟧
6 08-44 PTC warning threshold 0.1~10.0V 0.5 V O O O O O O O ⟦blank source cell⟧
7 08-45 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 08-46 Over-temperature protection threshold 0~254 0 °C O O O O O O O ⟦blank source cell⟧
9 08-47 Over-temperature reset threshold 0~254 0 °C O O O O O O O ⟦blank source cell⟧
10 08-48 Fire mode selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
11 08-48 Fire mode selection 1: Valid 0 - O O O O O O O ⟦blank source cell⟧
12 08-49 Fire mode digital input type 0: Power failure reset 0 - O O O O O O O ⟦blank source cell⟧
13 08-49 Fire mode digital input type 1: Terminal removal reset 0 - O O O O O O O ⟦blank source cell⟧
14 08-50 Fire mode digital terminal status XXX0B: S6 A contact XXX1B: S6 B contact 0000b - O O O O O O O ⟦blank source cell⟧
15 08-51 Fire mode motor rotation speed selection 0: Fire mode operation 0 - O O O O O O O ⟦blank source cell⟧
16 08-51 Fire mode motor rotation speed selection 1: PID frequency command 0 - O O O O O O O ⟦blank source cell⟧
17 08-51 Fire mode motor rotation speed selection 2: AI2 frequency command 0 - O O O O O O O ⟦blank source cell⟧
18 08-52 Fire mode motor rotation speed 0~100.00 100.00 % O O O O O O O ⟦blank source cell⟧
19 08-53 Fire mode PID detection threshold 0~100 0 % O O O O O O O ⟦blank source cell⟧
20 08-54 Fire mode PID disconnection delay 0~10.0 1.0 s O O O O O O O ⟦blank source cell⟧
21 08-55 Fire mode PID disconnection action selection 0: Current speed 1 - O O O O O O O ⟦blank source cell⟧
22 08-55 Fire mode PID disconnection action selection 1: Fire mode speed (08-52) 1 - O O O O O O O ⟦blank source cell⟧
23 08-55 Fire mode PID disconnection action selection 2: Motor 1 maximum frequency (01-02) 1 - O O O O O O O ⟦blank source cell⟧
24 08-56 Fire mode AI2 type detection threshold 0.0~100.0 80.0 % O O O O O O O ⟦blank source cell⟧
25 08-57 Fire mode AI2 mode disconnection delay 0.0~10.0 1.0 s O O O O O O O ⟦blank source cell⟧
26 08-58 Fire mode AI2 mode disconnection action selection 0: Current speed 1 - O O O O O O O ⟦blank source cell⟧
27 08-58 Fire mode AI2 mode disconnection action selection 1: Fire mode speed (08-52) 1 - O O O O O O O ⟦blank source cell⟧
28 08-58 Fire mode AI2 mode disconnection action selection 2: Motor 1 maximum frequency (01-02) 1 - O O O O O O O ⟦blank source cell⟧
29 08-59 Fire mode motor direction 0: Forward 0 - O O O O O O O ⟦blank source cell⟧
30 08-59 Fire mode motor direction 1: Reverse 0 - O O O O O O O ⟦blank source cell⟧
31 08-60 Fire mode password 0~65534 0 - O O O O O O O ⟦blank source cell⟧
32 08-61 Capacitor maintenance setting 0: Invalid 0 - ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 08-61 Capacitor maintenance setting 1: Valid 0 - ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 08-64 Keypad selection 0:E710 Keypad 1:T310 Keypad 2:A510S Keypad 0 - O O O O O O O ⟦blank source cell⟧
35 08-65 Cooling fan maintenance setting 0~9999 0 - O O O O O O O ⟦blank source cell⟧
36 08-66 IGBT maintenance setting 0~150 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 09 communication function group — page 88

Manual reference: physical PDF page 88. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 09 communication function group

V/F+PG, SV, PMSV are only for special projects.

*3 09 group not affected by 13-08 initialization.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 09 communication function group — PDF page 88

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 09-00 Inverter communication station 1~31 1 - O O O O O O O *3
2 09-01 Communication mode selection 0: MODBUS 0 ⟦blank source cell⟧ O O O O O O O *3
3 09-01 Communication mode selection 3: PUMP parallel communication 0 ⟦blank source cell⟧ O O O O O O O *3
4 09-02 Serial transmission speed setting (bps) 0:1200 4 - O O O O O O O *3
5 09-02 Serial transmission speed setting (bps) 1:2400 4 - O O O O O O O *3
6 09-02 Serial transmission speed setting (bps) 2:4800 4 - O O O O O O O *3
7 09-02 Serial transmission speed setting (bps) 3:9600 4 - O O O O O O O *3
8 09-02 Serial transmission speed setting (bps) 4:19200 4 - O O O O O O O *3
9 09-02 Serial transmission speed setting (bps) 5:38400 4 - O O O O O O O *3
10 09-03 Stop bit selection 0: 1 Stop bit 0 - O O O O O O O *3
11 09-03 Stop bit selection 1: 2 Stop bit 0 - O O O O O O O *3
12 09-04 Parity bit selection 0: No parity 0 - O O O O O O O *3
13 09-04 Parity bit selection 1: Even parity bit selection 0 - O O O O O O O *3
14 09-04 Parity bit selection 2: Odd parity selection 0 - O O O O O O O *3
15 09-05 Communication data bit selection 0: 8-bit data 0 - O O O O O O O *3
16 09-05 Communication data bit selection 1: 7-bit data 0 - O O O O O O O *3
17 09-06 Communication abnormality detection time 0.0~25.5 0.0 S O O O O O O O *3
18 09-07 Fault stop selection 0: Decelerates to stop using deceleration time 1 after communication failure 3 - O O O O O O O *3
19 09-07 Fault stop selection 1: Free-run stop after communication failure 3 - O O O O O O O *3
20 09-07 Fault stop selection 2: Decelerates to stop using deceleration time 2 after communication failure 3 - O O O O O O O *3
21 09-07 Fault stop selection 3: Continues operation after communication failure 3 - O O O O O O O *3
22 09-08 Communication fault tolerance count 1~20 1 - O O O O O O O *3
23 09-09 Wait time 5~65 5 ms O O O O O O O *3
24 09-10 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 09-11 Bluetooth communication selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
26 09-11 Bluetooth communication selection 1: Valid 0 - O O O O O O O ⟦blank source cell⟧
27 09-15 Communication expansion card selection (Frame1 has no communication expansion card) 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
28 09-15 Communication expansion card selection (Frame1 has no communication expansion card) 1: Valid 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 10 PID function group — page 89

Manual reference: physical PDF page 89. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 10 PID function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 parameter reference: Group 10 PID function group — PDF page 89

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 10-00 PID target value source setting 0: Assigned by PUMP function target (see Group 23) 1 - O O O O O O O ⟦blank source cell⟧
2 10-00 PID target value source setting 1: Assigned via AI1 1 - O O O O O O O ⟦blank source cell⟧
3 10-00 PID target value source setting 2: Assigned via AI2 1 - O O O O O O O ⟦blank source cell⟧
4 10-00 PID target value source setting 3: Assigned via pulse input 1 - O O O O O O O ⟦blank source cell⟧
5 10-00 PID target value source setting 4: Assigned via parameter 10-02 1 - O O O O O O O ⟦blank source cell⟧
6 10-00 PID target value source setting 5: Reserved 1 - O O O O O O O ⟦blank source cell⟧
7 10-00 PID target value source setting 6: Frequency command (00-05) 1 - O O O O O O O ⟦blank source cell⟧
8 10-00 PID target value source setting 8: Assigned via panel VR 1 - O O O O O O O ⟦blank source cell⟧
9 10-01 PID feedback value source setting 1: Assigned via AI1 2 - O O O O O O O ⟦blank source cell⟧
10 10-01 PID feedback value source setting 2: Assigned via AI2 2 - O O O O O O O ⟦blank source cell⟧
11 10-01 PID feedback value source setting 3: Assigned via pulse input 2 - O O O O O O O ⟦blank source cell⟧
12 10-02 PID target value 0.00~100.00 0.00 % O O O O O O O *1
13 10-03 PID control mode xxx0b: PID invalid 0000b - O O O O O O O ⟦blank source cell⟧
14 10-03 PID control mode xxx1b: PID valid 0000b - O O O O O O O ⟦blank source cell⟧
15 10-03 PID control mode xx0xb: PID positive characteristic 0000b - O O O O O O O ⟦blank source cell⟧
16 10-03 PID control mode xx1xb: PID negative characteristic 0000b - O O O O O O O ⟦blank source cell⟧
17 10-03 PID control mode x0xxb: PID error value D control 0000b - O O O O O O O ⟦blank source cell⟧
18 10-03 PID control mode x1xxb: PID feedback value D control 0000b - O O O O O O O ⟦blank source cell⟧
19 10-03 PID control mode 0xxxb: PID output 0000b - O O O O O O O ⟦blank source cell⟧
20 10-03 PID control mode 1xxxb: PID output + frequency command 0000b - O O O O O O O ⟦blank source cell⟧
21 10-04 Feedback gain 0.01~10.00 1.00 - O O O O O O O *1
22 10-05 Proportional gain (P) 0.00~10.00 1.00 - O O O O O O O *1
23 10-06 Integral time (I) 0.00~100.00 1.00 s O O O O O O O *1
24 10-07 Derivative time (D) 0.00~10.00 0.00 s O O O O O O O *1
25 10-08 AI1 frequency limit 0.00~599.00 0 Hz O O O O O O O Note 2
26 10-09 PID bias voltage -100.0~100.0 0 % O O O O O O O *1
27 10-10 PID output delay time 0.00~10.00 0.00 s O O O O O O O *1
28 10-11 PID feedback disconnection detection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
29 10-11 PID feedback disconnection detection 1: Warning 0 - O O O O O O O ⟦blank source cell⟧
30 10-11 PID feedback disconnection detection 2: Failure 0 - O O O O O O O ⟦blank source cell⟧
31 10-12 PID feedback disconnection detection threshold 0~100 0 % O O O O O O O ⟦blank source cell⟧
32 10-13 PID feedback disconnection detection time 0.0~10.0 1.0 s O O O O O O O ⟦blank source cell⟧
33 10-14 PID integral limit 0.0~100.0 100.0 % O O O O O O O *1
34 10-15 PID change mode 0~2 0 - O O O O O O O [struck-through: Note 2]
35 10-16 PID change scale 0~100 100 % O O O O O O O *1 [struck-through: Note 2]
36 10-17 *PID sleep start frequency 0.00~599.00 0.00 Hz O O O O O O O ⟦blank source cell⟧
37 10-18 PID sleep delay time 0.0~255.5 0.0 s O O O O O O O ⟦blank source cell⟧
38 10-19 *PID wake-up start frequency 0.00~599.00 0.00 Hz O O O O O O O ⟦blank source cell⟧
39 10-20 PID wake-up delay time 0.0~255.5 0.0 s O O O O O O O ⟦blank source cell⟧
40 10-21 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
41 10-22 PID1/PID2 frequency switching point 0.00~599.00 0.00 Hz O O O O O O O ⟦blank source cell⟧
42 10-23 PID output limit 0.00~100.0 100.0 % O O O O O O O *1
43 10-24 PID output gain 0.0~25.0 1.0 - O O O O O O O ⟦blank source cell⟧
44 10-25 PID reverse output 0: Reverse output not 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 10 PID function group — page 90

Manual reference: physical PDF page 90. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 10 PID function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 10 parameter reference — PDF page 90

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ selection allowed ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦blank source cell⟧ selection 1: Reverse output allowed ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 10-26 PID target acceleration/deceleration time 0.0~25.5 0.0 s O O O O O O O ⟦blank source cell⟧
4 10-27 PID feedback display bias voltage 0~9999 0 - O O O O O O O ⟦blank source cell⟧
5 10-28 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 10-29 PID sleep selection 0: Invalid 1 - O O O O O O O ⟦blank source cell⟧
7 10-29 PID sleep selection 1: Valid 1 - O O O O O O O ⟦blank source cell⟧
8 10-29 PID sleep selection 2: Set by DI 1 - O O O O O O O ⟦blank source cell⟧
9 10-30 PID target upper limit 0.0 ~ 100.0 100.0 % O O O O O O O ⟦blank source cell⟧
10 10-31 PID target lower limit 0.0 ~ 100.0 0.0 % O O O O O O O ⟦blank source cell⟧
11 10-32 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 10-33 PID feedback maximum value 1 ~ 10000 999 - O O O O O O O ⟦blank source cell⟧
13 10-34 PID decimal width 0 ~ 4 1 ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
14 10-35 PID unit 0:% 0 ⟦blank source cell⟧ O O O O O O O *7
15 10-35 PID unit 1:FPM 0 ⟦blank source cell⟧ O O O O O O O *7
16 10-35 PID unit 2:CFM 0 ⟦blank source cell⟧ O O O O O O O *7
17 10-35 PID unit 3:SPI 0 ⟦blank source cell⟧ O O O O O O O *7
18 10-35 PID unit 4:GPH 0 ⟦blank source cell⟧ O O O O O O O *7
19 10-35 PID unit 5:GPM 0 ⟦blank source cell⟧ O O O O O O O *7
20 10-35 PID unit 6:IN 0 ⟦blank source cell⟧ O O O O O O O *7
21 10-35 PID unit 7:FT 0 ⟦blank source cell⟧ O O O O O O O *7
22 10-35 PID unit 8:/s 0 ⟦blank source cell⟧ O O O O O O O *7
23 10-35 PID unit 9:/m 0 ⟦blank source cell⟧ O O O O O O O *7
24 10-35 PID unit 10:/h 0 ⟦blank source cell⟧ O O O O O O O *7
25 10-35 PID unit 11:°F 0 ⟦blank source cell⟧ O O O O O O O *7
26 10-35 PID unit 12:inW 0 ⟦blank source cell⟧ O O O O O O O *7
27 10-35 PID unit 13:HP 0 ⟦blank source cell⟧ O O O O O O O *7
28 10-35 PID unit 14:m/s 0 ⟦blank source cell⟧ O O O O O O O *7
29 10-35 PID unit 15:MPM 0 ⟦blank source cell⟧ O O O O O O O *7
30 10-35 PID unit 16:CMM 0 ⟦blank source cell⟧ O O O O O O O *7
31 10-35 PID unit 17:W 0 ⟦blank source cell⟧ O O O O O O O *7
32 10-35 PID unit 18:KW 0 ⟦blank source cell⟧ O O O O O O O *7
33 10-35 PID unit 19:m 0 ⟦blank source cell⟧ O O O O O O O *7
34 10-35 PID unit 20:°C 0 ⟦blank source cell⟧ O O O O O O O *7
35 10-35 PID unit 21:RPM 0 ⟦blank source cell⟧ O O O O O O O *7
36 10-35 PID unit 22:Bar 0 ⟦blank source cell⟧ O O O O O O O *7
37 10-35 PID unit 23:Pa 0 ⟦blank source cell⟧ O O O O O O O *7
38 10-35 PID unit 24:KPa 0 ⟦blank source cell⟧ O O O O O O O *7
39 10-36 PID2 proportional gain (P) 0.00~10.00 3.00 - O O O O O O O *1 [struck-through: Note 2]
40 10-37 PID2 integral time (I) 0.00~100.00 0.50 Sec O O O O O O O *1 [struck-through: Note 2]
41 10-38 PID2 derivative time (D) 0.00~10.00 0.00 Sec O O O O O O O *1 [struck-through: Note 2]
42 10-39 *PID disconnection output frequency setting 00.00~599.00 30.00 Hz O O O O O O O ⟦blank source cell⟧

Manual — Group 10 PID function group — page 91

Manual reference: physical PDF page 91. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 10 PID function group

V/F+PG, SV, PMSV are only for special projects.

Group 11 auxiliary function group

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 10 parameter reference — PDF page 91

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 10-40 PID forced sleep frequency operation selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
2 10-40 PID forced sleep frequency operation selection 1: Valid 0 - O O O O O O O ⟦blank source cell⟧
3 10-41 PID mode switch 0: General PID 0 - O O O O O O O [struck-through: Note 2]
4 10-41 PID mode switch 1:D-type PID 0 - O O O O O O O [struck-through: Note 2]
5 10-42 ~ 10-46 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 10-47 Proportional gain 3 (P) 0.00~10.00 1.00 ⟦blank source cell⟧ O O O O O O O Note 4
7 10-48 Integral time 3 (I) 0.00~100.00 1.00 Sec O O O O O O O [struck-through: Note 4]
8 10-49 Derivative time 3 (D) 0.00~10.00 0.00 Sec O O O O O O O [struck-through: Note 4]

E710 Group 11 parameter reference — PDF page 91

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 11-00 Motor direction locking command 0: Allow forward and reverse rotation 0 - O O O O O O O ⟦blank source cell⟧
2 11-00 Motor direction locking command 1: Only allow forward 0 - O O O O O O O ⟦blank source cell⟧
3 11-00 Motor direction locking command 2: Only allow reverse rotation 0 - O O O O O O O ⟦blank source cell⟧
4 11-01 Carrier frequency 2~16: 2~16KHz 4 - O O O O O O O ⟦blank source cell⟧
5 11-02 Soft modulation selection 0: Invalid 0 - O O O O O O O ⟦blank source cell⟧
6 11-02 Soft modulation selection 1: Soft modulation 1 0 - O O O O O O O ⟦blank source cell⟧
7 11-02 Soft modulation selection 2: Soft modulation 2 0 - O O O O O O O ⟦blank source cell⟧
8 11-03 Automatic carrier reduction selection 0: Invalid 0 - O O X X X X O ⟦blank source cell⟧
9 11-03 Automatic carrier reduction selection 1: Valid 0 - O O X X X X O ⟦blank source cell⟧
10 11-04 Acceleration start S curve time setting 0.00~2.50 0.20 s O O O O O O O ⟦blank source cell⟧
11 11-05 Acceleration end S curve time setting 0.00~2.50 0.20 s O O O O O O O ⟦blank source cell⟧
12 11-06 Deceleration start S curve time setting 0.00~2.50 0.20 s O O O O O O O ⟦blank source cell⟧
13 11-07 Deceleration end S curve time setting 0.00~2.50 0.20 s O O O O O O O ⟦blank source cell⟧
14 11-08 Jump frequency 1 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
15 11-09 Jump frequency 2 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
16 11-10 Jump frequency 3 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
17 11-11 Jump frequency width 0.0~25.5 1.0 Hz O O O O O O O ⟦blank source cell⟧
18 11-12 Manual energy-saving gain 0~100 80 % O O X X X X X ⟦blank source cell⟧
19 11-13 Automatic return time 0~120 60 Sec O O O O O O O *1
20 11-14 ~ 11-17 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 11-18 Manual energy-saving frequency 0.0~599.0 0.00 Hz O O X X X X X ⟦blank source cell⟧
22 11-19 Automatic energy-saving function 0: Automatic energy- saving ineffective 0 - O X X X X X X ⟦blank source cell⟧
23 11-19 Automatic energy-saving function 1: Automatic energy- saving effective 0 - O X X X X X X ⟦blank source cell⟧
24 11-20 Automatic energy-saving filter time 0~200 140 ms O X X X X X X ⟦blank source cell⟧
25 11-21 Energy-saving adjustment voltage upper limit 0~100 100 % O X X X X X X ⟦blank source cell⟧
26 11-22 Energy-saving adjustment time 0~5000 20 ms O X X X X X X *1

Manual — Group 11 auxiliary function group — page 92

Manual reference: physical PDF page 92. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 11 auxiliary function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 11 parameter reference — PDF page 92

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 11-23 Energy-saving detection threshold 0~100 10 % O X X X X X X ⟦blank source cell⟧
2 11-24 Automatic energy-saving coefficient 0.00~655.34 (Note 4) - - O X X X X X X ⟦blank source cell⟧
3 11-25 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 11-26 Carrier frequency adjustment upper limit with output frequency (%) 10~100 80 % X X X X X O X ⟦blank source cell⟧
5 11-27 Carrier frequency adjustment lower limit with output frequency (%) 2~100 20 % X X X X X O X ⟦blank source cell⟧
6 11-28 Over-voltage prevention 2 frequency gain 1~200 100 % O O X X X X X ⟦blank source cell⟧
7 11-29 Automatic output frequency reduction selection 0: Invalid 0 - O X X X X X O ⟦blank source cell⟧
8 11-29 Automatic output frequency reduction selection 1: Valid 0 - O X X X X X O ⟦blank source cell⟧
9 11-30 Variable carrier frequency maximum limit 2~16 - KHz O O X X X X O ⟦blank source cell⟧
10 11-31 Variable carrier frequency minimum limit 1~16 - KHz O O X X X X O ⟦blank source cell⟧
11 11-32 Variable carrier frequency gain 00~99 00 - O O X X X X O ⟦blank source cell⟧
12 11-33 DC voltage filter rise rate 0.1~10.0 0.1 Vdc O O X X X X X *1
13 11-34 DC voltage filter drop rate 0.1~10.0 5.0 Vdc O O X X X X X *1
14 11-35 DC voltage filter dead zone threshold 0.0~99.0 10.0 Vdc O O X X X X X *1
15 11-36 Over-voltage prevention frequency gain 0.000~1.000 0.050 - O O X X X X X *1
16 11-37 **Over-voltage prevention frequency limit *0.00~599.00 5.00 Hz O O X X X X X ⟦blank source cell⟧
17 11-38 Over-voltage prevention deceleration start voltage 200V: 200~400V 300 V O O X X X X X ⟦blank source cell⟧
18 11-38 Over-voltage prevention deceleration start voltage 400V: 400~800V 700 V O O X X X X X ⟦blank source cell⟧
19 11-39 Over-voltage prevention deceleration stop voltage 200V: 300~400V 350 V O O X X X X X ⟦blank source cell⟧
20 11-39 Over-voltage prevention deceleration stop voltage 400V: 600~800V 750 V O O X X X X X ⟦blank source cell⟧
21 11-40 Over-voltage prevention selection 0: Invalid 0 - O O X X X X X ⟦blank source cell⟧
22 11-40 Over-voltage prevention selection 1: Over-voltage prevention mode 1 0 - O O X X X X X ⟦blank source cell⟧
23 11-40 Over-voltage prevention selection 2: Over-voltage prevention mode 2 0 - O O X X X X X ⟦blank source cell⟧
24 11-40 Over-voltage prevention selection 3: Over-voltage prevention mode 3 0 - O O X X X X X ⟦blank source cell⟧
25 11-40 Over-voltage prevention selection 4: Over-voltage prevention mode 4 0 - O O X X X X X ⟦blank source cell⟧
26 11-41 Reference frequency loss detection selection 0: When reference frequency is lost, deceleration stops 0 - O O O O O O O ⟦blank source cell⟧
27 11-41 Reference frequency loss detection selection 1: When reference frequency is lost, operate according to the setting of 11-42 0 - O O O O O O O ⟦blank source cell⟧
28 11-42 Frequency command when the reference frequency is lost 0.0~100.0 80.0 % O O O O O O O ⟦blank source cell⟧
29 11-43 Lock frequency during startup 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
30 11-44 Start-Up Frequency 0.0~10.0 0.0 s O O O O O O O ⟦blank source cell⟧

Manual — Group 11 auxiliary function group — page 93

Manual reference: physical PDF page 93. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 11 auxiliary function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 11 parameter reference — PDF page 93

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ Hold Time ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 11-45 Lock frequency when stopped 0.0~599.0 0.0 Hz O O O O O O O ⟦blank source cell⟧
3 11-46 Lock time of frequency when stopped 0.0~10.0 0.0 s O O O O O O O ⟦blank source cell⟧
4 11-47 KEB deceleration time 0.0~25.5 0.0 s O O X X X X O *1
5 11-48 KEB detection threshold 200V: 190~210 200 V O O X X X X O ⟦blank source cell⟧
6 11-48 KEB detection threshold 400V: 380~420 400 V O O X X X X O ⟦blank source cell⟧
7 11-49 Zero servo gain 0.01~5.00 1.00 - X X X O O X X ⟦blank source cell⟧
8 11-50 Zero servo count 0~4096 12 - X X X O O X X ⟦blank source cell⟧
9 11-51 Zero speed brake selection 0: Zero speed DC brake ineffective 0 - O X X X X X O ⟦blank source cell⟧
10 11-51 Zero speed brake selection 1: Zero speed DC brake effective 0 - O X X X X X O ⟦blank source cell⟧
11 11-52 Droop control threshold 0.0~100.0% 0.0 % X X O [struck-through: (Note 4)] O O O [struck-through: (Note 4)] X *1
12 11-53 Droop control delay 0.01~2.00 0.2 s X X O [struck-through: (Note 4)] O O O [struck-through: (Note 4)] X *1
13 11-54 Cumulative energy initialization 0: Do not clear cumulative energy 1: Clear cumulative energy 0 - O O O O O O O *1
14 11-55 STOP button selection 0: When the operation command is not provided by the operator, the stop button is ineffective 1: When the operation command is not provided by the operator, the stop button is effective 1 - O O O O O O O ⟦blank source cell⟧
15 11-56 UP/DOWN selection 0: When the operator UP/DOWN is effective, ENTER must be pressed after modifying the frequency in order for it to become effective 1: When the operator UP/DOWN is effective, the frequency is effective immediately after it is modified 0 - O O O O O O O ⟦blank source cell⟧
16 11-57 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 11-58 Record reference frequency 0: Invalid 1: Valid 0 - O O O O O O O *1
18 11-59 Prevent oscillation gain 0.00~2.50 * ⟦blank source cell⟧ O O X X X X O ⟦blank source cell⟧
19 11-60 Prevent oscillation upper limit 1~100 * % O O X X X X O ⟦blank source cell⟧
20 11-61 Prevent oscillation time parameter 0~100 0 ⟦blank source cell⟧ O O X X X X O ⟦blank source cell⟧
21 11-62 Prevent oscillation selection 0: Mode 1 1: Mode 2 2: Mode 3 2 - O O X X X X O ⟦blank source cell⟧
22 11-63 Strong magnetic selection 0: Invalid 1: Valid 1 - X X O O X X X ⟦blank source cell⟧
23 11-64 Acceleration rate adjustment gain 0.1~10.0 1.0 - O X X X X X O ⟦blank source cell⟧
24 11-65 Target main circuit voltage 200V: 200V~400V 370 - O X X X X X O ⟦blank source cell⟧
25 11-65 Target main circuit voltage 400V: 400V~800V 740 - O X X X X X O ⟦blank source cell⟧

Manual — Group 11 auxiliary function group — page 94

Manual reference: physical PDF page 94. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 11 auxiliary function group

V/F+PG, SV, PMSV are only for special projects.

*: Please refer to the descriptions in Appendix One

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 11 parameter reference — PDF page 94

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 11-66 Modulation mode switching starting frequency 6.00~60.00 20 Hz O O O O X O O *1 [struck-through: Note 2]
2 11-67 Soft modulation 2 detection range 0~12000 0 Hz X X O O O O X [struck-through: Note 2]
3 11-68 Soft modulation 2 detection starting frequency 6.00~60.00 20 Hz X X O O O O X [struck-through: Note 2]
4 11-69 Prevent oscillation gain 0.00~200.00 2.00 % O O X X X X X [struck-through: Note 1]
5 11-70 Prevent oscillation upper limit 0.01~100.00 5.00 % O O X X X X X [struck-through: Note 1]
6 11-71 Prevent oscillation time constant 0~30000 100 ms O O X X X X X [struck-through: Note 1]
7 11-72 Prevent oscillation gain switching frequency 1 0.01~300.00 2.00 Hz O O X X X X X [struck-through: Note 1]
8 11-73 Prevent oscillation gain switching frequency 2 0.01~300.00 7.00 Hz O O X X X X X [struck-through: Note 1]
9 11-76 Droop frequency threshold 1 0.00~599.00 0.00 Hz X X O O O O X [struck-through: Note 4]
10 11-77 Droop frequency threshold 2 0.00~599.00 0.00 Hz X X O O O O X [struck-through: Note 4]
11 11-78 Droop torque offset 0.00~100.00 0.00 % X X O O O O X [struck-through: Note 4]
12 11-79 LOC/REM panel button selection 0: Forward and reverse rotation control 1: Local/remote control 0 - O O O O O O O ⟦blank source cell⟧
13 11-80 Local/remote selection mode 0: Allow switching directly 1: Switching prohibited during operation 2: Stop operation after switching [struck-through: 0; no replacement printed] [struck-through: -; no replacement printed] O O O O O O O ⟦blank source cell⟧
14 11-81 OVP4 threshold (%) 1.00~2.00 1.10 [struck-through: %; no replacement printed] O O O O X X O ⟦blank source cell⟧
15 11-82 OVP4 gain 0~256 64 - O O O O X X O ⟦blank source cell⟧

Manual — Group 12 monitor function group — page 95

Manual reference: physical PDF page 95. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 12 monitor function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 12 parameter reference — PDF page 95

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 12-00 Display screen selection (LED) 00000~77777 Starting from the left-most number, this is the sequence of the screens that will be displayed after pressing the DSP buttons 1: Output current 2: Output voltage 3: DC bus voltage 4: Heatsink temperature* 5: PID feedback 6: AI1 value 7: AI2 value 00321 (Note 4) - O O O O O O O *1 *6
2 12-01 PID feedback display mode (LED) 0: Use integers to display the feedback value (xxx) 0 ⟦blank source cell⟧ O O O O O O O *6
3 12-01 PID feedback display mode (LED) 1: Use one decimal place to show the feedback value (xx.x) 0 ⟦blank source cell⟧ O O O O O O O *6
4 12-01 PID feedback display mode (LED) 2: Use two decimal places to show the feedback value (x.xx) 0 ⟦blank source cell⟧ O O O O O O O *6
5 12-02 PID feedback display unit setting (LED) 0: xxxxx (no unit) 0 ⟦blank source cell⟧ O O O O O O O *6
6 12-02 PID feedback display unit setting (LED) 1: xxxPb (pressure) 0 ⟦blank source cell⟧ O O O O O O O *6
7 12-02 PID feedback display unit setting (LED) 2: xxxFL (flow rate) 0 ⟦blank source cell⟧ O O O O O O O *6
8 12-03 Linear speed display (LED) 0~60000 1500/ 1800 RPM O O O O O O O *6
9 12-04 Linear speed display mode (LED) 0: Display inverter output frequency 0 - O O O O O O O *6
10 12-04 Linear speed display mode (LED) 1: Use integers to display the linear speed (xxxxx) 0 - O O O O O O O *6
11 12-04 Linear speed display mode (LED) 2: Use 1 decimal place to display the linear speed (xxxx.x) 0 - O O O O O O O *6
12 12-04 Linear speed display mode (LED) 3: Use 2 decimal places to display the linear speed (xxx.xx) 0 - O O O O O O O *6
13 12-04 Linear speed display mode (LED) 4: Use 3 decimal places to display the linear speed (xx.xxx) 0 - O O O O O O O *6
14 12-05 Display the digital input/output terminal status (LED/LCD) The LED display is as follows. When there is no input/output, the illustration shows five illuminated middle horizontal segments. Correspondence when there is input/output: input labels left-to-right S1, S2, S3, S4, S5, S6, S7; output labels left-to-right RY1, DO1, DO2, PLC. The LCD display is as follows: 0: OPEN; 1: CLOSE. Labels top-to-bottom: Input Terminal(S7), Input Terminal(S6), Input Terminal(S5), Input Terminal(S4), Input Terminal(S3), Input Terminal(S2), Input Terminal(S1), Output Terminal(PLC), Output Terminal(DO2), Output Terminal(DO1), Output Terminal(RY1). Display illustrations are examples, not live measured states. Refer to original diagram for segment and position geometry; no unprinted bit numbers assigned. - ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧

Manual — Group 12 monitor function group — page 96

Manual reference: physical PDF page 96. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 12 monitor function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 12 parameter reference — PDF page 96

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 12-06 ~ 12-10 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 12-11 Output current during current failure Displays the output current during the current failure - A O O O O O O O ⟦blank source cell⟧
3 12-12 Output voltage during current failure Displays the output voltage during the current failure - V O O O O O O O ⟦blank source cell⟧
4 12-13 Output frequency during current failure Displays the output frequency during the current failure - Hz O O O O O O O ⟦blank source cell⟧
5 12-14 DC voltage during current failure Displays the DC voltage during the current failure - V O O O O O O O ⟦blank source cell⟧
6 12-15 Frequency command during current failure Displays the frequency command during the current failure - Hz O O O O O O O ⟦blank source cell⟧
7 12-16 Frequency command When the LED enters this parameter, only monitor frequency commands are allowed - Hz O O O O O O O ⟦blank source cell⟧
8 12-17 Output frequency Displays the current output frequency - Hz O O O O O O O ⟦blank source cell⟧
9 12-18 Output current Displays the current output current - A O O O O O O O ⟦blank source cell⟧
10 12-19 Output voltage Displays the current output voltage - V O O O O O O O ⟦blank source cell⟧
11 12-20 DC voltage (Vdc) Displays the current DC voltage - V O O O O O O O ⟦blank source cell⟧
12 12-21 Output power (kw) Displays the current output power - kW O O O O O O O ⟦blank source cell⟧
13 12-22 Motor speed (rpm) Displays the current motor speed. In VF/SLV mode: motor speed = output frequency x 120 / Motor number of poles. In PG/SV/PMSV mode, the motor speed is calculated based on the feedback frequency. (The maximum limit of motor speed (rpm) is 65535) - rpm O O O O O O O ⟦blank source cell⟧
14 12-23 Output power factor (Pfo) Displays the current output power factor - - O O O O O O O ⟦blank source cell⟧
15 12-24 Control mode Displays the control mode 0: VF 1: PG 2: SLV 3: SV 4: PSV 5: PMSLV 6: SLV2 - - O O O O O O O ⟦blank source cell⟧
16 12-25 AI1 input Displays the current AI1 input (-10V corresponds to -100%, 10V corresponds to 100%,) - % O O O O O O O ⟦blank source cell⟧
17 12-26 AI2 input Displays the current AI2 input (0V or 4mA corresponds to 0%, 10V or 20mA corresponds to 100%) - % O O O O O O O ⟦blank source cell⟧
18 12-27 Motor torque Displays the current torque command (100% corresponds to the motor torque) - % X X O O O O X ⟦blank source cell⟧
19 12-28 Motor torque current (Iq) Displays the current q-axis current - % X X O O O O X ⟦blank source cell⟧
20 12-29 Motor excitation current (Id) Displays the current d-axis current - % X X O O O O X ⟦blank source cell⟧
21 12-30 ASR deviation amount Displays the deviation amount of the speed controller (speed command - feedback speed) (100% corresponds to the maximum frequency set for 01-02) - % X O X O O X X ⟦blank source cell⟧
22 12-31 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 12-32 ASR output Displays the output value of the speed controller (100% corresponds to the maximum - % X O X O O X X ⟦blank source cell⟧

Manual — Group 12 monitor function group — page 97

Manual reference: physical PDF page 97. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 12 monitor function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 12 parameter reference — PDF page 97

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ frequency set for 01-02) ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 12-33 PG feedback Displays the speed feedback value of the speed controller (100% corresponds to the maximum frequency set for 01-02) - % X O X O O X X ⟦blank source cell⟧
3 12-34 PG pulse count Displays the pulse count of the speed controller - Pulse X O X O O X X [struck-through: Note 4]
4 12-35 Zero servo pulse count Displays the zero speed servo position error pulse count in SV position mode (The resolution is four times the 20-27 PG pulse count) - Pulse X X X O O X X ⟦blank source cell⟧
5 12-36 PID control input Displays the error input of the PID controller (PID target value - PID feedback) (100% corresponds to the maximum frequency set for 01-02 or 01-16) - % O O O O O O O ⟦blank source cell⟧
6 12-37 PID output Displays the output of the PID controller (100% corresponds to the maximum frequency set for 01-02 or 01-16) - % O O O O O O O ⟦blank source cell⟧
7 12-38 PID setting Displays the target value of the PID controller (100% corresponds to the maximum frequency set for 01-02 or 01-16) - % O O O O O O O ⟦blank source cell⟧
8 12-39 PID feedback Displays the feedback value of the PID controller (100% corresponds to the maximum frequency set for 01-02 or 01-16) - % O O O O O O O ⟦blank source cell⟧
9 12-40 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 12-41 Inverter temperature display Displays the temperature of the heatsink or IGBT** * ℃ O O O O O O O ⟦blank source cell⟧
11 12-42 RS-485 error code Diagram shows eight zero positions as an example. Callout labels top-to-bottom: 1: CRC Error; 1: Data length Error; 1: Data Function Error; 1: Parity Error; 1: Overrun Error; 1: Framing Error; 1: Time out Error; Reserved. Refer to original diagram for position geometry; no unprinted bit numbers assigned. - - O O O O O O O ⟦blank source cell⟧
12 12-43 Inverter status Diagram shows eight zero positions as an example. Callout labels top-to-bottom: 1: Inverter ready; 1: During running; 1: During zero speed; 1: During speed agree; 1: During fault detection (minor fault); 1: During fault detection (major fault); Reserved. Refer to original diagram for position geometry; no unprinted bit numbers assigned. - - O O O O O O O ⟦blank source cell⟧
13 12-44 Pulse input frequency Displays the frequency value of the pulse input - Hz O O O O O O O ⟦blank source cell⟧
14 12-45 Recent failure information Displays information on the current failure - - O O O O O O O ⟦blank source cell⟧
15 12-46 Previous failure information Displays information on the previous failure - - O O O O O O O ⟦blank source cell⟧
16 12-47 Previous two failure information Displays information on the previous two failures - - O O O O O O O ⟦blank source cell⟧
17 12-48 Previous three failure information Displays information on the previous three failures - - O O O O O O O ⟦blank source cell⟧

Manual — Group 12 monitor function group — page 98

Manual reference: physical PDF page 98. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 12 monitor function group

V/F+PG, SV, PMSV are only for special projects.

*: Please refer to the descriptions in Appendix One

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 12 parameter reference — PDF page 98

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 12-49 Previous four failure information Displays information on the previous four failures - - O O O O O O O ⟦blank source cell⟧
2 12-50 DI/DO status of the current failure Displays the DI/DO status of the current failure; the description is the same as 12-05 - - O O O O O O O ⟦blank source cell⟧
3 12-51 Inverter status of the current failure Displays the inverter status during the current failure; the description is the same as 12-43 - - O O O O O O O ⟦blank source cell⟧
4 12-52 Fault trip time 1 of the current failure Displays the operation time during the current failure; 12-53 is its number of days and 12-52 is the number of hours if it is less than a day. - Hr O O O O O O O ⟦blank source cell⟧
5 12-53 Fault trip time 2 of the current failure Displays the operation time during the current failure; 12-53 is its number of days and 12-52 is the number of hours if it is less than a day. - day O O O O O O O ⟦blank source cell⟧
6 12-54 Frequency command of the previous failure Displays the frequency command during the previous failure - Hz O O O O O O O ⟦blank source cell⟧
7 12-55 Output frequency of the previous failure Displays the output frequency during the previous failure - Hz O O O O O O O ⟦blank source cell⟧
8 12-56 Output current of the previous failure Displays the output current during the previous failure - A O O O O O O O ⟦blank source cell⟧
9 12-57 Output voltage of the previous failure Displays the output voltage during the previous failure - V O O O O O O O ⟦blank source cell⟧
10 12-58 DC voltage of the previous failure Displays the DC voltage during the previous failure - V O O O O O O O ⟦blank source cell⟧
11 12-59 DI/DO status of the previous failure Displays the DI/DO status of the previous failure; the description is the same as 12-05 - - O O O O O O O ⟦blank source cell⟧
12 12-60 Inverter status of the previous failure Displays the inverter status during the previous failure; the description is the same as 12-43 - - O O O O O O O ⟦blank source cell⟧
13 12-61 Fault trip time 1 of the previous failure Displays the operation time during the previous failure; 12-62 is its number of days and 12-61 is the number of hours if it is less than a day. - Hr O O O O O O O ⟦blank source cell⟧
14 12-62 Fault trip time 2 of the previous failure Displays the operation time during the previous failure; 12-62 is its number of days and 12-61 is the number of hours if it is less than a day. - day O O O O O O O ⟦blank source cell⟧
15 12-63 Recent warning messages Displays the current warning message - - O O O O O O O ⟦blank source cell⟧
16 12-64 Previous warning message Displays the previous warning message - - O O O O O O O ⟦blank source cell⟧
17 12-65 Motor starting angle 0~360 - - X X X X O X X ⟦blank source cell⟧
18 12-66 Encoder angle 0~360 - - X O X O O X X ⟦blank source cell⟧
19 12-67 Cumulative energy (KWHr) 0.0 ~ 999.9 ⟦blank source cell⟧ kWH r O O O O O O O ⟦blank source cell⟧
20 12-68 Cumulative energy (MWHr) 0 ~ 60000 ⟦blank source cell⟧ MW Hr O O O O O O O ⟦blank source cell⟧
21 12-69 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 12-70 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 12-71 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 12-72 RTC date 12.01.01 ~ 99.12.31 - ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
25 12-73 RTC time 00:00 ~ 23:59 00:00 ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
26 12-74 Work pressure setting 0.01 ~ 25.50 2.00 PSI O X X X X X O ⟦blank source cell⟧
27 12-75 Feedback pressure value 0.01 ~ 25.50 - PSI O X X X X X O ⟦blank source cell⟧
28 12-76 Actual no-load voltage 0.0~600.0 - V X X O X X X X ⟦blank source cell⟧
29 12-77 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 12-78 Z-phase deviation value -9999~9999 - Pulse X X X O O X X ⟦blank source cell⟧
31 12-79 Pulse input percentage 0.0~100.0 - % O O O O O O O ⟦blank source cell⟧
32 12-80 AI1 frequency command 0.0~599.0 0 Hz O O O O O O O [struck-through: Note 2]
33 12-81 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 12-82 Motor load 0~200.0 - % O O O O O O O [struck-through: Note 4]
35 12-85 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
36 12-86 Error status during alarm 0~65534 - - O O O O O O O ⟦blank source cell⟧
37 12-87 Capacitor life inspection percentage 0.0~200.0 0 % O O O O O O O ⟦blank source cell⟧

Manual — Group 13 maintenance function group — page 99

Manual reference: physical PDF page 99. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 13 maintenance function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 13 parameter reference — PDF page 99

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 13-00 Inverter horse power ---- - - O O O O O O O *4
2 13-01 Software version 0.00-9.99 - - O O O O O O O *4
3 13-02 Cumulative working time clearing function 0: Do not clear the cumulative working time 0 - O O O O O O O *1
4 13-02 Cumulative working time clearing function 1: Clear the cumulative working time 0 - O O O O O O O *1
5 13-03 Cumulative working time 1 0~23 - hr O O O O O O O *4
6 13-04 Cumulative working time 2 0~65534 (Note 4) - day O O O O O O O *4
7 13-05 Cumulative working time selection 0: Cumulative time while power is connected 0 - O O O O O O O *1
8 13-05 Cumulative working time selection 1: Cumulative time during operation 0 - O O O O O O O *1
9 13-06 Parameter lock 0: All parameters besides 13- 06 and frequency 05-01 on the home page cannot be written 2 - O O O O O O O *1
10 13-06 Parameter lock 1: User-defined parameter 2 - O O O O O O O *1
11 13-06 Parameter lock 2: All parameters are writable 2 - O O O O O O O *1
12 13-07 Password function 00000~65534 00000 - O O O O O O O [struck-through: Note 2]
13 13-08 Restore factory settings 0: Do not initialize - - O O O O O O O ⟦blank source cell⟧
14 13-08 Restore factory settings 2: 2-wire type initialization (60Hz) (220/440V) - - O O O O O O O ⟦blank source cell⟧
15 13-08 Restore factory settings 3: 3-wire type initialization (60Hz) (220/440V) - - O O O O O O O ⟦blank source cell⟧
16 13-08 Restore factory settings 4: 2-wire type initialization (50Hz) (230/415V) - - O O O O O O O ⟦blank source cell⟧
17 13-08 Restore factory settings 5: 3-wire type initialization (50Hz) (230/415V) - - O O O O O O O ⟦blank source cell⟧
18 13-08 Restore factory settings 6: 2-wire type initialization (50Hz) (200/380V) - - O O O O O O O ⟦blank source cell⟧
19 13-08 Restore factory settings 7: 3-wire type initialization (50Hz) (200/380V) - - O O O O O O O ⟦blank source cell⟧
20 13-08 Restore factory settings 8: PLC initialization - - O O O O O O O ⟦blank source cell⟧
21 13-08 Restore factory settings 9: 2-wire type initialization (60Hz) (230\/460V) - - O O O O O O O ⟦blank source cell⟧
22 13-08 Restore factory settings 10: 3-wire type initialization (60Hz) (230/460V) - - O O O O O O O ⟦blank source cell⟧
23 13-08 Restore factory settings 11: 2-wire type initialization (60Hz)(230/400V) - - O O O O O O O ⟦blank source cell⟧
24 13-08 Restore factory settings 12: 3-wire type initialization (60Hz)(230/400V) - - O O O O O O O ⟦blank source cell⟧
25 13-08 Restore factory settings 13: 2-wire type initialization (50Hz)(230/400V) - - O O O O O O O ⟦blank source cell⟧
26 13-08 Restore factory settings 14: 3-wire type initialization (50Hz)(230/400V) - - O O O O O O O ⟦blank source cell⟧
27 13-08 Restore factory settings 15: 2-wire type initialization (Note 4) (50Hz)(220/380V) - - O O O O O O O ⟦blank source cell⟧
28 13-08 Restore factory settings 16: 3-wire type initialization (Note 4) (50Hz)(220/380V) - - O O O O O O O ⟦blank source cell⟧
29 13-08 Restore factory settings 17: 2-wire type initialization (60Hz)(200/380V) - - O O O O O O O ⟦blank source cell⟧
30 13-08 Restore factory settings 18: 3-wire type initialization (60Hz)(200/380V) - - O O O O O O O ⟦blank source cell⟧
31 13-09 Failure history clearing 0: Do not clear the failure 0 - O O O O O O O *1

Manual — Group 13 maintenance function group — page 100

Manual reference: physical PDF page 100. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 13 maintenance function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

Adjacent source context — repeated to preserve continuation:

E710 Group 13 parameter reference — PDF page 100

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ function history ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦blank source cell⟧ function 1: Clear the failure history ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 13-10 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 13-11 CB2 software version 0.00~9.99 - - O O O O O O O *4
5 13-12 Optional card Id 0~255 0 ⟦blank source cell⟧ O O O O O O O *5
6 13-13 Optional card CPLD software version. 0.00~9.99 - ⟦blank source cell⟧ O O O O O O O *5
7 13-14 Failure saving selection 0: Automatic reset and restart failure messages are not saved in the failure history 1 ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
8 13-14 Failure saving selection 1: Automatic reset and restart failure messages are saved in the failure history 1 ⟦blank source cell⟧ O O O O O O O ⟦blank source cell⟧
9 13-15 ~ 13-20 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 13-21 Previous failure information Displays information on the previous failure - - O O O O O O O [struck-through: Note 1]
11 13-22 Previous two failure information Displays information on the previous two failures - - O O O O O O O [struck-through: Note 1]
12 13-23 Previous three failure information Displays information on the previous three failures - - O O O O O O O [struck-through: Note 1]
13 13-24 Previous four failure information Displays information on the previous four failures - - O O O O O O O [struck-through: Note 1]
14 13-25 Previous five failure information Displays information on the previous five failures - - O O O O O O O [struck-through: Note 1]
15 13-26 Previous six failure information Displays information on the previous six failures - - O O O O O O O [struck-through: Note 1]
16 13-27 Previous seven failure information Displays information on the previous seven failures - - O O O O O O O [struck-through: Note 1]
17 13-28 Previous eight failure information Displays information on the previous eight failures - - O O O O O O O [struck-through: Note 1]
18 13-29 Previous nine failure information Displays information on the previous nine failures - - O O O O O O O [struck-through: Note 1]
19 13-30 Previous ten failure information Displays information on the previous ten failures - - O O O O O O O [struck-through: Note 1]
20 13-31 Previous eleven failure information Displays information on the previous eleven failures - - O O O O O O O [struck-through: Note 1]
21 13-32 Previous twelve failure information Displays information on the previous twelve failures - - O O O O O O O [struck-through: Note 1]
22 13-33 Previous thirteen failure information Displays information on the previous thirteen failures - - O O O O O O O [struck-through: Note 1]
23 13-34 Previous fourteen failure information Displays information on the previous fourteen failures - - O O O O O O O [struck-through: Note 1]
24 13-35 Previous fifteen failure information Displays information on the previous fifteen failures - - O O O O O O O [struck-through: Note 1]
25 13-36 Previous sixteen failure information Displays information on the previous sixteen failures - - O O O O O O O [struck-through: Note 1]
26 13-37 Previous seventeen failure information Displays information on the previous seventeen failures - - O O O O O O O [struck-through: Note 1]
27 13-38 Previous eighteen failure information Displays information on the previous eighteen failures - - O O O O O O O [struck-through: Note 1]
28 13-39 Previous nineteen failure information Displays information on the previous nineteen failures - - O O O O O O O [struck-through: Note 1]
29 13-40 Previous twenty failure information Displays information on the previous twenty failures - - O O O O O O O [struck-through: Note 1]
30 13-41 Previous twenty-one failure information Displays information on the previous twenty-one failures - - O O O O O O O [struck-through: Note 1]
31 13-42 Previous twenty-two failure information Displays information on the previous twenty-two failures - - O O O O O O O [struck-through: Note 1]
32 13-43 Previous twenty-three failure information Displays information on the previous twenty-three failures - - O O O O O O O [struck-through: Note 1]
33 13-44 Previous twenty-four Displays information on the - - O O O O O O O [struck-through: Note 1]

Manual — Group 13 maintenance function group — page 101

Manual reference: physical PDF page 101. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 13 maintenance function group

V/F+PG, SV, PMSV are only for special projects.

Note: The LCD primary frequency setting page is 12-16, which is the same as segment 0 speed frequency command 05-01.

Group 14 PLC setting group

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

Adjacent source context — repeated to preserve continuation:

E710 Group 13 parameter reference — PDF page 101

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ failure information previous twenty-four failures ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 13-45 Previous twenty-five failure information Displays information on the previous twenty-five failures - - O O O O O O O [struck-through: Note 1]
3 13-46 Previous twenty-six failure information Displays information on the previous twenty-six failures - - O O O O O O O [struck-through: Note 1]
4 13-47 Previous twenty-seven failure information Displays information on the previous twenty-seven failures - - O O O O O O O [struck-through: Note 1]
5 13-48 Previous twenty-eight failure information Displays information on the previous twenty-eight failures - - O O O O O O O [struck-through: Note 1]
6 13-49 Previous twenty-nine failure information Displays information on the previous twenty-nine failures - - O O O O O O O [struck-through: Note 1]
7 13-50 Previous thirty failure information Displays information on the previous thirty failures - - O O O O O O O [struck-through: Note 1]
8 13-51 Cooling fan cumulative operation time 0~99999 0 - O O O O O O O ⟦blank source cell⟧
9 13-52 Cooling fan life inspection percentage 0~150 0 % O O O O O O O ⟦blank source cell⟧
10 13-53 IGBT life inspection percentage 0~150 0 % O O O O O O O ⟦blank source cell⟧

E710 Group 14 parameter reference — PDF page 101

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 14-00 T1 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
2 14-01 T1 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
3 14-02 T2 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
4 14-03 T2 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
5 14-04 T3 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
6 14-05 T3 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
7 14-06 T4 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
8 14-07 T4 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
9 14-08 T5 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
10 14-09 T5 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
11 14-10 T6 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
12 14-11 T6 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
13 14-12 T7 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
14 14-13 T7 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
15 14-14 T8 setting value 1 0~9999 0 - O O O O O O O [struck-through: Note 6]
16 14-15 T8 setting value 2 (mode 7) 0~9999 0 - O O O O O O O [struck-through: Note 6]
17 14-16 C1 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
18 14-17 C2 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
19 14-18 C3 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
20 14-19 C4 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
21 14-20 C5 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
22 14-21 C6 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
23 14-22 C7 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
24 14-23 C8 setting value 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
25 14-24 AS1 setting value 1 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
26 14-25 AS1 setting value 2 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
27 14-26 AS1 setting value 3 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
28 14-27 AS2 setting value 1 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]

Manual — Group 14 PLC setting group — page 102

Manual reference: physical PDF page 102. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 14 PLC setting group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 14 parameter reference — PDF page 102

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 14-28 AS2 setting value 2 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
2 14-29 AS2 setting value 3 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
3 14-30 AS3 setting value 1 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
4 14-31 AS3 setting value 2 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
5 14-32 AS3 setting value 3 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
6 14-33 AS4 setting value 1 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
7 14-34 AS4 setting value 2 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
8 14-35 AS4 setting value 3 0~65534 (Note 4) 0 - O O O O O O O [struck-through: Note 6]
9 14-36 MD1 setting value 1 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
10 14-37 MD1 setting value 2 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
11 14-38 MD1 setting value 3 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
12 14-39 MD2 setting value 1 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
13 14-40 MD2 setting value 2 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
14 14-41 MD2 setting value 3 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
15 14-42 MD3 setting value 1 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
16 14-43 MD3 setting value 2 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
17 14-44 MD3 setting value 3 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
18 14-45 MD4 setting value 1 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
19 14-46 MD4 setting value 2 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]
20 14-47 MD4 setting value 3 0~65534 (Note 4) 1 - O O O O O O O [struck-through: Note 6]

Manual — Group 15 PLC monitoring group — page 103

Manual reference: physical PDF page 103. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 15 PLC monitoring group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 15 parameter reference — PDF page 103

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 15-00 T1 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
2 15-01 T1 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
3 15-02 T2 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
4 15-03 T2 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
5 15-04 T3 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
6 15-05 T3 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
7 15-06 T4 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
8 15-07 T4 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
9 15-08 T5 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
10 15-09 T5 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
11 15-10 T6 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
12 15-11 T6 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
13 15-12 T7 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
14 15-13 T7 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
15 15-14 T8 current value 1 0~9999 0 - O O O O O O O ⟦blank source cell⟧
16 15-15 T8 current value 2 (mode 7) 0~9999 0 - O O O O O O O ⟦blank source cell⟧
17 15-16 C1 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
18 15-17 C2 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
19 15-18 C3 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
20 15-19 C4 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
21 15-20 C5 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
22 15-21 C6 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
23 15-22 C7 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
24 15-23 C8 current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
25 15-24 AS1 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
26 15-25 AS2 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
27 15-26 AS3 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
28 15-27 AS4 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
29 15-28 MD1 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
30 15-29 MD2 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
31 15-30 MD3 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
32 15-31 MD4 calculation result 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧
33 15-32 TD current value 0~65534 [struck-through: (Note 4)] 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 16 LCD function group — page 104

Manual reference: physical PDF page 104. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 16 LCD function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 16 parameter reference — PDF page 104

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 16-00 Main screen monitoring 5~82 (Note 4) When using the LCD operator, the monitoring item displayed on the first row (the initial value is frequency command) 16 - O O O O O O O *1
2 16-01 Sub-screen monitoring 1 5~82 (Note 4) When using the LCD operator, the monitoring item displayed on the second row (the initial value is output frequency) 17 - O O O O O O O *1
3 16-02 Sub-screen monitoring 2 5~82 (Note 4) When using the LCD operator, the monitoring item displayed on the third row (the initial value is output current) 18 - O O O O O O O *1
4 16-03 Display unit selection 0~39999 determines the display method and unit of the frequency command 0 - O O O O O O O ⟦blank source cell⟧
5 16-03 Display unit selection 0: The frequency display unit is 0.01 Hz 0 - O O O O O O O ⟦blank source cell⟧
6 16-03 Display unit selection 1: The frequency display unit is 0.01% 0 - O O O O O O O ⟦blank source cell⟧
7 16-03 Display unit selection 2: The frequency display unit is rpm 0 - O O O O O O O ⟦blank source cell⟧
8 16-03 Display unit selection 3~39: Reserved 0 - O O O O O O O ⟦blank source cell⟧
9 16-03 Display unit selection 40~9999: User-specified format. Entering 0XXXX means displayed as XXXX when 100% 0 - O O O O O O O ⟦blank source cell⟧
10 16-03 Display unit selection 10001~19999: User-specified format. Entering 1XXXX means displayed as XXX.X when 100% 0 - O O O O O O O ⟦blank source cell⟧
11 16-03 Display unit selection 20001~29999: User-specified format. Entering 2XXXX means displayed as XX.XX when 100% 0 - O O O O O O O ⟦blank source cell⟧
12 16-03 Display unit selection 30001~39999: User-specified format. Entering 3XXXX means displayed as X.XXX when 100% 0 - O O O O O O O ⟦blank source cell⟧
13 16-04 Engineering unit selection 0: Do not use engineering unit 0 - O O O O O O O ⟦blank source cell⟧
14 16-04 Engineering unit selection 1:FPM 0 - O O O O O O O ⟦blank source cell⟧
15 16-04 Engineering unit selection 2:CFM 0 - O O O O O O O ⟦blank source cell⟧
16 16-04 Engineering unit selection 3:PSI 0 - O O O O O O O ⟦blank source cell⟧
17 16-04 Engineering unit selection 4:GPH 0 - O O O O O O O ⟦blank source cell⟧

Manual — Group 16 LCD function group — page 105

Manual reference: physical PDF page 105. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 16 LCD function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 16 parameter reference — PDF page 105

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 5:GPM ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ 6:IN ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧ 7:FT ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 ⟦blank source cell⟧ ⟦blank source cell⟧ 8:/s ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧ 9:/m ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ 10:/h ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧ 11:°F ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧ 12:inW ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ 13:HP ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ 14:m/s ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ 15:MPM ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ 16:CMM ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ 17:W ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ 18:KW ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧ 19:m ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ 20:°C ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ 21:RPM ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ 22:Bar ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ 23:Pa ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ 24:KPa ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ 25: PRS ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧ 26: SPM ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 16-05 LCD backlight 0~7 5 - O O O O O O O *1
24 16-06 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 16-07 Copy function selection 0: Do not copy parameter 1: Read the inverter parameter and save it to the operator 2: Write the operator parameter into the inverter 3: Compare the inverter and operator parameters 0 - O O O O O O O ⟦blank source cell⟧
26 16-08 Allow read selection 0: Do not allow reading of the inverter parameter and saving to the operator 1: Allow reading of the inverter parameter and saving to the operator 0 - O O O O O O O ⟦blank source cell⟧
27 16-09 Operator disconnection selection 0: Continue operating when the LCD operator is disconnected 1: Display failure when the LCD operator is disconnected 0 - O O O O O O O *1
28 16-10 RTC time display setting 0: Hide 1: Display 0 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
29 16-11 RTC date setting 12.01.01 ~ 99.12.31 12.01.01 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
30 16-12 RTC time setting 00:00 ~ 23:59 00:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
31 16-13 RTC timer function 0: Invalid 1: Valid 2: Set according to DI 0 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]

Manual — Group 16 LCD function group — page 106

Manual reference: physical PDF page 106. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 16 LCD function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 16 parameter reference — PDF page 106

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 16-14 P1 start time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
2 16-15 P1 end time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
3 16-16 P1 start day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 1 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
4 16-17 P1 end day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 5 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
5 16-18 P2 start time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
6 16-19 P2 end time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
7 16-20 P2 start day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 1 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
8 16-21 P2 end day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 5 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
9 16-22 P3 start time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
10 16-23 P3 end time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
11 16-24 P3 start day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 1 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
12 16-25 P3 end day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 5 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
13 16-26 P4 start time 00:00 ~ 23:59 08:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
14 16-27 P4 end time 00:00 ~ 23:59 18:00 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
15 16-28 P4 start day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 1 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
16 16-29 P4 end day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Sunday 5 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
17 16-30 RTC offset selection 0: Invalid 1: Valid 2: Set according to DI 0 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
18 16-31 RTC offset time setting 00:00 ~ 23:59 00:00 - O O O O O O O [struck-through: Note 8]
19 16-32 Timer 1 source 0: None, 1: P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 1 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
20 16-33 Timer 2 source 0: None, 1: P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 2 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
21 16-34 Timer 3 source 0: None, 1: P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 4 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
22 16-35 Timer 4 source 0: None, 1: P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 8 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]

Manual — Group 16 LCD function group — page 107

Manual reference: physical PDF page 107. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 16 LCD function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 16 parameter reference — PDF page 107

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 15:P1+P2+P3+P4, 16:Off, 17:Off+P1 18:Off+P2, 19:Off+P1+P2 20:Off+P3, 21:Off+P1+P3 22:Off+P2+P3 23:Off+P1+P2+P3 24:Off+P4 25:Off+P1+P4 26:Off+P2+P4 27:Off+P1+P2+P4 28:Off+P3+P4 29:Off+P1+P3+P4 30:Off+P2+P3+P4 31:Off+P1+P2+P3+P4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 16-36 RTC speed selection 0: Off 1: Selected by timer 1 2: Selected by timer 2 3: Selected by timer 3 4: Selected by timer 4 5: Selected by timer 1 + 2 0 ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]
3 16-37 RTC operation direction selection xxx0b: RTC Run1 forward xxx1b: RTC Run1 reverse xx0xb: RTC Run2 forward xx1xb: RTC Run2 reverse x0xxb: RTC Run3 forward x1xxb: RTC Run3 reverse 0xxxb: RTC Run4 forward 1xxxb: RTC Run4 reverse 0000b ⟦blank source cell⟧ O O O O O O O [struck-through: Note 8]

Manual — Group 17 automatic tuning function group — page 108

Manual reference: physical PDF page 108. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 17 automatic tuning function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 17 parameter reference — PDF page 108

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 17-00 *Automatic tuning mode selection 0: Rotational automatic tuning 1: Static automatic tuning 2: Stator resistance measurement 3: Reserved 4: Circuit tuning 5: Rotational automatic tuning integration (option: 4+2+0) 6: Static automatic tuning integration (option: 4+2+1) VF:2 VF+PG:2 SLV:6 SV:6 SLV2:6 - O O O O X X O ⟦blank source cell⟧
2 17-01 Motor rated output power 0.00~600.00 KVA KW O O O O X X O ⟦blank source cell⟧
3 17-02 Motor rated current [struck-through: 0.1~1200.0] 25%~120% inverter Rated current KVA A O O O O X X O ⟦blank source cell⟧
4 17-03 Motor rated voltage 200V: 50.0~240.0 400V: 100.0~480.0 - - V O O O O X X O ⟦blank source cell⟧
5 17-04 Motor rated frequency 4.8~599.0 50.0/60.0 Hz O O O O X X O ⟦blank source cell⟧
6 17-05 Motor rated speed 0~24000 KVA rpm O O O O X X O ⟦blank source cell⟧
7 17-06 Motor number of poles 2~16 (even number) 4 Pole O O O O X X O ⟦blank source cell⟧
8 17-07 PG pulse count 0~60000 1024 ppr O O O O X X O ⟦blank source cell⟧

Manual — V/F+PG, SV, PMSV are only for special projects. — page 109

Manual reference: physical PDF page 109. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

V/F+PG, SV, PMSV are only for special projects.

KVA: This parameter varies according to the different inverter capacities.

*Before using motor automatic tuning, it is recommended to first select 00-32 application adjustment.

Note: The default factory value of vector-based 17-00 is 6 static automatic tuning integration (option: 4+2+1). If the motor is unloaded and rotational tuning can be performed, it is recommended to perform 5: rotational automatic tuning integration (option: 4+2+0)

■It will only appear to be settable when 1:17-00=1, 2, 6

Group 18 slip compensation function group

*: Please refer to the descriptions in Appendix One

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 17 parameter reference — PDF page 109

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 17-08 Motor no-load voltage 200V: 50~240 - V O O O O X X O ⟦blank source cell⟧
2 17-08 Motor no-load voltage 400V:100~480 - V O O O O X X O ⟦blank source cell⟧
3 17-09 Motor excitation current 15%~70% motor rating Constant current - A X X O O X X X *1
4 17-10 Automatic tuning start 0: Invalid 1: Valid 0 - O O O O X X O ⟦blank source cell⟧
5 17-11 Automatic tuning error history 0: No errors 1: Motor data error 2: Stator resistance tuning error 3: Leakage inductance tuning error 4: Rotor resistance tuning error 5: Mutual inductance tuning error 6: DT error 7: Encoder error 8: Motor acceleration error 9: Warning 0 - O O O O X X O ⟦blank source cell⟧
6 17-12 Motor leakage inductance ratio 0.1~15.0 3.4 % X X O O X X X ⟦blank source cell⟧
7 17-13 Motor slip frequency 0.10~20.00 1.00 Hz X X O O X X X ⟦blank source cell⟧
8 17-14 Rotational tuning mode selection 0: VF-based rotational automatic tuning 1: Vector-based rotational automatic tuning 0 - O O O O X X O ⟦blank source cell⟧

E710 Group 18 parameter reference — PDF page 109

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 18-00 Low-speed slip compensation gain 0.00~2.50 VF:0.00 - O X O O X X O *1
2 18-00 Low-speed slip compensation gain 0.00~2.50 SLV* - O X O O X X O *1
3 18-01 High-speed slip compensation gain -1.00~1.00 0.0 - O X O X X X X *1
4 18-02 Slip compensation limit 0~250 200 % O X X X X X X ⟦blank source cell⟧
5 18-03 Slip compensation filter time 0.0~10.0 1.0 Sec O X X X X X X ⟦blank source cell⟧
6 18-04 Regenerative slip compensation selection 0: Invalid 1: Valid 0 - O X X X X X X ⟦blank source cell⟧
7 18-05 FOC delay time 1~1000 100 ms X X O X X X X ⟦blank source cell⟧
8 18-06 FOC gain 0.00~2.00 0.1 - X X O X X X X ⟦blank source cell⟧

Manual — Group 19 frequency skipping function group — page 110

Manual reference: physical PDF page 110. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 19 frequency skipping function group

V/F+PG, SV, PMSV are only for special projects.

Group 20 speed control function ground

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 19 parameter reference — PDF page 110

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 19-00 Frequency skipping center frequency 5.00~100.00 20.00 % O O X X X X O *1
2 19-01 Frequency skipping amplitude 0.1~20.0 10.0 % O O X X X X O *1
3 19-02 Frequency skipping oscillation frequency 0.0~50.0 0.0 % O O X X X X O *1
4 19-03 Frequency skipping oscillation time 0~50 0 ms O O X X X X O *1
5 19-04 Frequency skipping cycle 0.0~1000.0 10.0 Sec O O X X X X O *1
6 19-05 Frequency skipping ratio 0.1~10.0 1.0 ⟦blank source cell⟧ O O X X X X O *1
7 19-06 Frequency skipping upper offset amplitude 0.0~20.0 0.0 % O O X X X X O *1
8 19-07 Frequency skipping lower offset amplitude 0.0~20.0 0.0 % O O X X X X O *1

E710 Group 20 parameter reference — PDF page 110

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 20-00 ASR gain 1 0.00~250.00 - - X O O O O O X *1
2 20-01 ASR integral time 1 0.001~10.000 - Sec X O O O O O X *1
3 20-02 ASR gain 2 0.00~250.00 - - X O O O O O X *1
4 20-03 ASR integral time 2 0.001~10.000 - Sec X O O O O O X *1
5 20-04 ASR integral time limit 0~300 200 % X X O O O O X ⟦blank source cell⟧
6 20-05 ASR positive limit 0.1 ~ 10.0 5.0 % X O X X X X X ⟦blank source cell⟧
7 20-06 ASR negative limit 0.1 ~ 10.0 1.0 % X O X X X X X ⟦blank source cell⟧
8 20-07 Acceleration/deceleratio n P/PI selection 0: PI speed control is only effective at constant speed; only P is used for control during acceleration and deceleration. 1: PI speed control is effective in both constant speed and acceleration/decelerat ion 0 - X O O O O X X ⟦blank source cell⟧
9 20-08 ASR delay time 0.000~0.500 0.004 Sec O X O O O O X [struck-through: Note 5]
10 20-09 Speed observer gain 1 0.00~2.55 0.61 - X X O X X X X *1
11 20-10 Speed observer integral time 1 0.01~10.00 0.05 Sec X X O X X X X *1
12 20-11 Speed observer gain 2 0.00~2.55 0.61 - X X O X X X X *1
13 20-12 Speed observer integral time 2 0.01~10.00 0.06 Sec X X O X X X X *1
14 20-13 Speed feedback low filter constant 1 1~1000 4 ms X X O X X X X ⟦blank source cell⟧
15 20-14 Speed feedback low filter constant 2 1~1000 30 ms X X O X X X X ⟦blank source cell⟧
16 20-15 ASR gain change frequency 1 0.0~599.0 4.0 Hz X O O O O X O ⟦blank source cell⟧
17 20-16 ASR gain change frequency 2 0.0~599.0 8.0 Hz X X O O O X O ⟦blank source cell⟧
18 20-17 Low-speed torque compensation gain 0.00~2.50 1.00 - X X O X X X X *1
19 20-18 High-speed torque compensation gain -10~10 0 % X X O X X X X *1
20 20-19 Overspeed (OS) selection 0: Deceleration stop 1: Free-run stop 2: Continue operating 1 ⟦blank source cell⟧ X O X O O X X ⟦blank source cell⟧
21 20-20 Overspeed (OS) 0~120 115 % X O X O O X X ⟦blank source cell⟧

Manual — Group 20 speed control function ground — page 111

Manual reference: physical PDF page 111. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 20 speed control function ground

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 20 parameter reference — PDF page 111

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ detection threshold ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 20-21 Overspeed (OS) detection time 0.0~2.0 0.5 Sec X O X O O X X ⟦blank source cell⟧
3 20-22 Speed deviation (DEV) selection 0: Deceleration stop 1: Free-run stop 2: Continue operating 2 ⟦blank source cell⟧ X O X O O X X ⟦blank source cell⟧
4 20-23 Speed deviation (DEV) detection threshold 0~50 10 % X O X O O X X ⟦blank source cell⟧
5 20-24 Speed deviation (DEV) detection time 0.0~10.0 0.5 Sec X O X O O X X ⟦blank source cell⟧
6 20-25 PG disconnection selection 0: Deceleration stop 1: Free-run stop 2: Continue operating 1 - X O X O O X X ⟦blank source cell⟧
7 20-26 PG disconnection detection time 0.0~10.0 2.0 Sec X O X O O X X ⟦blank source cell⟧
8 20-27 PG pulse count 0~9999 1024 ppr O O X O O X X [struck-through: Note 5]
9 20-28 PG rotation direction selection 0: Forward is counter- clockwise 1: Forward is clockwise 0 - O O X O O X X [struck-through: Note 5]
10 20-29 PG pulse frequency division ratio 001~132 1 - X O X O O X X ⟦blank source cell⟧
11 20-30 PG gear ratio 1 1~1000 1 - X O X O X X X ⟦blank source cell⟧
12 20-31 PG gear ratio 2 1~1000 1 - X O X O X X X ⟦blank source cell⟧
13 20-32 Special encoder selection 0: None 1: Resolver 0 ⟦blank source cell⟧ X X X O O X X ⟦blank source cell⟧
14 20-33 Constant speed detection threshold 0.1~5.0 1.0 ⟦blank source cell⟧ X O O O O O X *1
15 20-34 Speed reduction compensation gain 0~25600 0 ⟦blank source cell⟧ X X O O O X X *1
16 20-35 Speed reduction compensation time 0~30000 100 ms X X O O O X X *1
17 20-36 ~ 20-42 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 20-43 Speed multiplier 1~500 20 ⟦blank source cell⟧ O O X O X X X [struck-through: Note 5]
19 20-44 Speed command limit 0.1~30.0 6.0 Hz O X X X X X X [struck-through: Note 5]

Manual — Group 21 torque and position control function group — page 112

Manual reference: physical PDF page 112. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 21 torque and position control function group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 21 parameter reference — PDF page 112

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 21-00 Torque control selection 0: Speed control 0 - X X X O O X X ⟦blank source cell⟧
2 21-00 Torque control selection 1: Torque control 0 - X X X O O X X ⟦blank source cell⟧
3 21-01 Torque reference filter time 0~1000 0 ms X X X O O X X ⟦blank source cell⟧
4 21-02 Speed limit selection 0: According to AI input 1: According to the setting value of 21-03 2: According to the communication position input (2502H) 0 - X X X O O X X ⟦blank source cell⟧
5 21-03 Speed limit value -120~120 0 % X X X O O X X *1
6 21-04 Speed limit bias voltage 0~120 10 % X X X O O X X *1
7 21-05 Forward torque limit 0~300 * % X X O O O O X ⟦blank source cell⟧
8 21-06 Negative torque limit 0~300 * % X X O O O O X ⟦blank source cell⟧
9 21-07 Forward regenerative torque limit 0~300 * % X X O O O O X ⟦blank source cell⟧
10 21-08 Reverse regenerative torque limit 0~300 * % X X O O O O X ⟦blank source cell⟧
11 21-09 Position control maximum frequency 0.1~100.0 20.0 Hz X X X O O X X ⟦blank source cell⟧
12 21-10 Segment 0 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
13 21-11 Segment 0 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
14 21-12 Segment 1 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
15 21-13 Segment 1 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
16 21-14 Segment 2 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
17 21-15 Segment 2 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
18 21-16 Segment 3 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
19 21-17 Segment 3 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
20 21-18 Segment 4 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
21 21-19 Segment 4 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
22 21-20 Segment 5 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
23 21-21 Segment 5 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
24 21-22 Segment 6 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
25 21-23 Segment 6 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
26 21-24 Segment 7 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
27 21-25 Segment 7 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
28 21-26 Segment 8 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
29 21-27 Segment 8 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
30 21-28 Segment 9 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
31 21-29 Segment 9 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
32 21-30 Segment 10 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
33 21-31 Segment 10 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧

Manual — Group 21 torque and position control function group — page 113

Manual reference: physical PDF page 113. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 21 torque and position control function group

V/F+PG, SV, PMSV are only for special projects.

*: Please refer to the descriptions in Appendix One

Group 22 PM motor group

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 21 parameter reference — PDF page 113

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 21-32 Segment 11 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
2 21-33 Segment 11 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
3 21-34 Segment 12 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
4 21-35 Segment 12 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
5 21-36 Segment 13 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
6 21-37 Segment 13 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
7 21-38 Segment 14 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
8 21-39 Segment 14 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
9 21-40 Segment 15 rotation count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
10 21-41 Segment 15 pulse count command -9999 ~ 9999 0 - X X X O O X X ⟦blank source cell⟧
11 21-42 Position mode selection 0: Enter position mode when the speed is lower than the minimum frequency 1: Z-phase locking function 0 ⟦blank source cell⟧ X X X O O X X ⟦blank source cell⟧
12 21-43 Offset angle 0 ~9999 0 Pulse X X X O O X X ⟦blank source cell⟧

E710 Group 22 parameter reference — PDF page 113

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 22-00 PM motor rated power 0.00~600.00 KVA kW X X X X O O X ⟦blank source cell⟧
2 22-01 PM motor rated voltage 200V: 50.0~240.0 400V: 100.0~480.0 220.0 440.0 V X X X X O O X [struck-through: Note 7]
3 22-02 PM motor rated current 25%~200% of the inverter’s rated current KVA A X X X X O O X ⟦blank source cell⟧
4 22-03 PM motor number of poles 2~96 6 poles X X X X O O X ⟦blank source cell⟧
5 22-04 PM motor rated rotation speed 6~60000 1500 rpm X X X X O O X ⟦blank source cell⟧
6 22-05 PM motor maximum rotation speed 6~60000 1500 rpm X X X X O O X ⟦blank source cell⟧
7 22-06 PM motor rated frequency 4.8~599.0 75.0 Hz X X X X O O X ⟦blank source cell⟧
8 22-07 PM type selection 0:SPM 1:IPM 0 ⟦blank source cell⟧ X X X X X O X [struck-through: Note 7]
9 22-08 PM encoder type 0: Tamagawa non-less wiring type cable 1: Tamagawa less wiring type cable 2: SUMTAK less wiring type cable 3: General differential incremental type cable 4: Sine wave type cable 0 ⟦blank source cell⟧ X X X X O X X ⟦blank source cell⟧
10 22-09 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 22-10 PM SLV starting current 20% ~ 200% Motor rated current 100 % X X X X X O X ⟦blank source cell⟧
12 22-11 I/F mode starting frequency switching point 10 ~ 100 (Note 7) 10 % X X X X X O X ⟦blank source cell⟧

Manual — Group 22 PM motor group — page 114

Manual reference: physical PDF page 114. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 22 PM motor group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 22 parameter reference — PDF page 114

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 22-12 22-13 Reserved (Note 4) ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 22-14 PM motor armature resistance 0.001 ~ 30.000 1.000 Ω X X X X O O X ⟦blank source cell⟧
3 22-15 PM motor D-axis inductance 0.01 ~300.00 10.00 mH X X X X O O X ⟦blank source cell⟧
4 22-16 PM motor Q-axis inductance 0.01 ~ 300.00 10.00 mH X X X X O O X ⟦blank source cell⟧
5 22-17 PM no-load voltage 200V: 0~250 400V: 0~500 150 300 V X X X X O O X [struck-through: Note 7]
6 22-18 Weak magnetic limit 0~120 90 % X X X X O O X ⟦blank source cell⟧
7 22-19 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 22-20 Pole shift angle 0~360 0 deg X X X X O X X *4
9 22-21 PM motor tuning 0: Do not perform PM motor tuning 1: Parameter automatic tuning (applicable to PMSLV) 2: Pole alignment and circuit adjustment (applicable to PMSV) 3: Rotational automatic tuning 0 - X X X X O O X ⟦blank source cell⟧
10 22-22 PM motor tuning failure history 0. No error 1. Stationary pole alignment failure 2. No PG option card 3. Rotational pole alignment forced stop 4. Encoder feedback direction error 5. Circuit tuning timeout 6. Encoder error 7. Other motor tuning error 8. Current abnormal during rotational pole alignment 9. Current abnormal during circuit adjustment 10. Reserved 11. Stator resistance measurement timeout 0 - X X X X O O X *4
11 22-23 22-24 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 22-25 Initial pole detection method selection 0. Use the angle before stopping 1. Method 1 2. Method 2 3. Method 3 1 (Note 7) - X X X X O O X ⟦blank source cell⟧
13 22-26 High-Speed Control Ratio Enable (applicable to PMSLV) 0. Low-speed open-circuit control 1. Low-speed high- frequency estimation control 2. Fully closed-circuit control 0 - X X X X X O X ⟦blank source cell⟧
14 22-27 Method 2 voltage command 5~120 (Note 7) (22-25=2 or 22-26=1 valid) 50 % X X X X O O X ⟦blank source cell⟧
15 22-28 Method 2 frequency division ratio 0~8 (Note 7) (22-25=2 or 22-26=1 valid) 2 - X X X X O O X ⟦blank source cell⟧
16 22-29 Weak magnetic voltage command limit 80~110 (Note 7) (related to 22-18) 100 % X X X X O O X [struck-through: Note 9]

Manual — Group 22 PM motor group — page 115

Manual reference: physical PDF page 115. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 22 PM motor group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 22 parameter reference — PDF page 115

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 22-30 SPM speed estimation gain (Note 7) 1~150 85 % X X X X X O X [struck-through: Note 4]
2 22-31 SPM speed estimation filter frequency (Note 7) 1~2000 60 Hz X X X X X O X [struck-through: Note 4]
3 22-32 MTPA selection 0: Invalid 1: Method 1 2: Method 2 3: Method 3 0 - X X X X O O X [struck-through: Note 7]
4 22-33 MTPA gain 0~400% 200 % X X X X O O X [struck-through: Note 7]
5 22-34 IPM estimator gain 1~300.0 180 - X X X X X O X [struck-through: Note 7]
6 22-35 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 22-36 PM motor type selection 0: General PM motor 1: DVEN motor 0 - X X X X X O X [struck-through: Note 8]
8 22-37 PM motor horse power and rotation speed 1: 0.75KW 1800RPM 4: 1.5KW 1800RPM 7: 2.2KW 1800RPM 10: 3.7KW 1800RPM 13: 5.5KW 1800RPM 16: 7.5KW 1800RPM 19: 11KW 1800RPM 22: 15KW 1800RPM 25: 18.5KW 800RPM 28: 22KW 1800RPM 0 - X X X X X O X [struck-through: Note 8]
9 22-38 Open-loop to closed- loop switching point frequency width (%) 1.0~40.0 5.0 % X X X X X O X ⟦blank source cell⟧
10 22-39 Pre-DC injection time 0~20.00 0.10 Sec X X X X X O X ⟦blank source cell⟧
11 22-40 High-frequency angle detection time 0.01~1.00 0.10 - X X X X X O X [struck-through: Note 9]
12 22-41 PM stopping method 0: Brake directly when deceleration or shutdown is lower than 22-11 1: Open-circuit stop when deceleration or shutdown is less than 22-11. 0 - X X X X X O X ⟦blank source cell⟧
13 22-42 Fully closed circuit low-speed segment calibration constant Ka 64~8192 200 - X X X X X O X [struck-through: Note 9]
14 22-43 Fully closed circuit high-speed segment calibration constant Kb 64~8192 500 - X X X X X O X [struck-through: Note 9]
15 22-44 Fully closed circuit high-speed position filter constant 1~256 4 - X X X X X O X ⟦blank source cell⟧
16 22-45 PM magnetic flux 0.001~10.000 0.700 - X X X X X O X ⟦blank source cell⟧
17 22-52 Low-speed coefficient 3000~60000 4000 - X X X X X O X ⟦blank source cell⟧
18 22-53 Low-speed integral filter time 1~256 32 V X X X X X O X ⟦blank source cell⟧
19 22-54 Motor voltage standard 50.0~600.0 300 - X X X X X O X ⟦blank source cell⟧
20 22-55 Fully closed circuit high-speed filter coefficient 1~256 32 - X X X X X O X ⟦blank source cell⟧
21 22-56 Fully closed circuit low-speed filter coefficient 1~256 64 - X X X X X O X ⟦blank source cell⟧

Manual — Group 23 pump and HVAC group — page 116

Manual reference: physical PDF page 116. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 23 pump and HVAC group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 23 parameter reference — PDF page 116

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 23-00 Function selection 0: Invalid 1: Pump selection 2: HVAC selection (in development) 3. Compressor selection (in development) 0 - O X X X X X O ⟦blank source cell⟧
2 23-01 Single/multiple pump and primary/secondary unit setting 0: Single Pump 1: Host 2: Auxiliary pump 1 3: Auxiliary pump 2 4: Auxiliary pump 3 0 - O X X X X X O ⟦blank source cell⟧
3 23-02 Work pressure setting 0.10 ~ 650.00 2.00 PSI O X X X X X O ⟦blank source cell⟧
4 23-03 Maximum pressure of pressure transmitter 0.10 ~ 650.00 10.00 PSI O X X X X X O ⟦blank source cell⟧
5 23-04 Pump pressure command source 0: Set by parameter 23-02 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
6 23-04 Pump pressure command source 1: Set by AI 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
7 23-05 Display method selection 0: Display target pressure and feedback pressure 1: Only display current pressure 2: Only display feedback pressure 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
8 23-06 Proportional gain (P) 0.00~10.00 0.10 - O X X X X X O *1
9 23-07 Integral time (I) 0.0~100.0 0.5 Sec O X X X X X O *1
10 23-08 Derivative time (D) 0.00~10.00 0.00 Sec O X X X X X O *1
11 23-09 Constant pressure error range 23-20=0 : 0.01 ~ 650.00 23-20=1 : 1~100 5 %/ PSI O X X X X X O ⟦blank source cell⟧
12 23-10 Constant pressure sleep frequency 0.00 ~ 599.00 30.00 Hz O X X X X X O ⟦blank source cell⟧
13 23-11 Constant pressure sleep time 0.0 ~ 255.5 1.0 Sec O X X X X X O ⟦blank source cell⟧
14 23-12 Maximum pressure limit 23-20=0 : 0.00 ~ 650.00 23-20=1 : 0~100 50 %/ PSI O X X X X X O ⟦blank source cell⟧
15 23-13 High pressure warning time 0.0 ~ 600.0 10.0 Sec O X X X X X O ⟦blank source cell⟧
16 23-14 High-pressure shutdown time 0.0 ~ 600.0 20.0 Sec O X X X X X O ⟦blank source cell⟧
17 23-15 Minimum pressure limit 23-20=0 : 0.00 ~ 650.00 23-20=1 : 0~100 5 %/ PSI O X X X X X O ⟦blank source cell⟧
18 23-16 Low-pressure warning time 0.0 ~ 600.0 0.0 Sec O X X X X X O ⟦blank source cell⟧
19 23-17 Low-pressure failure shutdown time 0.0 ~ 600.0 0.0 Sec O X X X X X O ⟦blank source cell⟧
20 23-18 Pressure loss detection time 0.0 ~ 600.0 0.0 Sec O X X X X X O ⟦blank source cell⟧
21 23-19 Pressure loss detection ratio 0 ~ 100 0 % O X X X X X O ⟦blank source cell⟧
22 23-20 Pressure percentage switching 0: Pressure 1 - O X X X X X O ⟦blank source cell⟧
23 23-20 Pressure percentage switching 1: Percentage 1 - O X X X X X O ⟦blank source cell⟧
24 23-22 Auxiliary machine 0.00 ~ 599.00 45.00 Hz O X X X X X O ⟦blank source cell⟧

Manual — Group 23 pump and HVAC group — page 117

Manual reference: physical PDF page 117. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 23 pump and HVAC group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 23 parameter reference — PDF page 117

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ trip frequency ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 23-23 Water usage detection direction 0: Detect upwards 1: Detect downwards 1 - O X X X X X O ⟦blank source cell⟧
3 23-24 Water use inspection pressure range 23-20=0 : 0.00 ~ 65.00 23-20=1 : 0~10 1 %/ PSI O X X X X X O ⟦blank source cell⟧
4 23-25 Water usage detection cycle 0.0 ~ 200.0 30.0 Sec O X X X X X O ⟦blank source cell⟧
5 23-26 Water usage detection acceleration time 0.1 ~ 6000.0 KVA Sec O X X X X X O *1
6 23-27 Water usage detection deceleration time 0.1 ~ 6000.0 KVA Sec O X X X X X O *1
7 23-28 Forced operation frequency 0.00 ~ 599.00 0.00 Hz O X X X X X O ⟦blank source cell⟧
8 23-29 Multi-pump parallel alternating time 0 ~ 240 3 Hr/min O X X X X X O ⟦blank source cell⟧
9 23-30 Multi-pump parallel auxiliary water pumping detection time 0.0 ~ 30.0 0.0 Sec O X X X X X O ⟦blank source cell⟧
10 23-31 Multi-pump parallel synchronization selection 0: Off 1: Pressure setting and Run/Stop synchronization 2: Pressure setting synchronization 3: Run/Stop synchronization 1 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
11 23-34 Constant pressure error range 2 23-20=0: 0.01 ~ 650.00 23-20=1: 1~100 5 %/ PSI O X X X X X O ⟦blank source cell⟧
12 23-35 Multi-unit parallel connection switching selection 0: Do not perform function 1: Timer alternation selection 2: Sleep stop alternation selection 3: Timer and sleep stop alternation selection 4: Multi-unit parallel testing mode 1 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
13 23-36 PUMP unit display 0: PSI 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
14 23-36 PUMP unit display 1: FPM 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
15 23-36 PUMP unit display 2: CFM 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
16 23-36 PUMP unit display 3: PSI 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
17 23-36 PUMP unit display 4: GPH 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
18 23-36 PUMP unit display 5: GPM 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
19 23-36 PUMP unit display 6: IN 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
20 23-36 PUMP unit display 7: FT 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
21 23-36 PUMP unit display 8: /s 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
22 23-36 PUMP unit display 9: /m 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
23 23-36 PUMP unit display 10: /h 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
24 23-36 PUMP unit display 11: °F 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
25 23-36 PUMP unit display 12: inW 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
26 23-36 PUMP unit display 13: HP 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
27 23-36 PUMP unit display 14: m/s 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
28 23-36 PUMP unit display 15: MPM 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
29 23-36 PUMP unit display 16: CMM 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
30 23-36 PUMP unit display 17: W 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
31 23-36 PUMP unit display 18: KW 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
32 23-36 PUMP unit display 19: m 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
33 23-36 PUMP unit display 20: °C 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
34 23-36 PUMP unit display 21: RPM 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
35 23-36 PUMP unit display 22: Bar 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧

Manual — Group 23 pump and HVAC group — page 118

Manual reference: physical PDF page 118. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Group 23 pump and HVAC group

V/F+PG, SV, PMSV are only for special projects.

Literal supplier values and O/X/- markings. V/F+PG,SV,PMSV are only for special projects. Attribute meanings on PDF64. Blank continued cells are not filled by inference; horizontally merged reserved cells stored once. Cross-page continuations retain page bounds.

E710 Group 23 parameter reference — PDF page 118

Source row Code Parameter name Scope Factory settings Unit V/F V/F+PG (special projects) SLV SV (special projects) PMSV (special projects) PMSLV SLV2 Attribute
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 23: Pa ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ 24: KPa ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 23-37 Water leakage detection time 0.0~100.0 0.0 Sec O X X X X X O ⟦blank source cell⟧
4 23-38 Water leakage detection restart pressure change amount 23-20=0 : 0.01 ~ 65.00 23-20=1 : 1~10 1 %/ PSI O X X X X X O ⟦blank source cell⟧
5 23-39 Water leakage detection restart error range 23-20=0 : 0.01 ~ 650.00 23-20=1 : 1~100 5 %/ PSI O X X X X X O ⟦blank source cell⟧
6 23-41~ 23-70 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 23-71 Pressure setting maximum value 0.10~650.00 10.00 PSI O X X X X X O ⟦blank source cell⟧
8 23-72 Parallel alternating time switching 0: Hour 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
9 23-72 Parallel alternating time switching 1: Minute 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
10 23-73 Secondary unit wakeup selection 0: Invalid 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
11 23-73 Secondary unit wakeup selection 1: Valid 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
12 23-74 High-pressure action setting 0: Invalid 2 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
13 23-74 High-pressure action setting 1: High-pressure warning only 2 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
14 23-74 High-pressure action setting 2: High-pressure warning error all effective 2 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
15 23-75 Low-pressure action setting 0: Invalid 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
16 23-75 Low-pressure action setting 1: Low-pressure warning only 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
17 23-75 Low-pressure action setting 2: Low-pressure warning error all effective 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
18 23-78 Pressure loss detection action selection 0: Invalid 1: Pressure loss warning 2: Pressure loss error 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧
19 23-79 Multi-pump parallel alternating time day 0~254 0 ⟦blank source cell⟧ O X X X X X O ⟦blank source cell⟧

Manual — Appendix One: Default factory value and parameter upper limit value adjusted according to different horse powers — page 119

Manual reference: physical PDF page 119. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix One: Default factory value and parameter upper limit value adjusted according to different horse powers

Model | Frame | 11-01 maximum SLV frequency (Hz), carrier wave <= 8K | 11-01 maximum SLV frequency (Hz), carrier wave > 8K | 18-00 SLV/SV initial value (low-speed slip compensation)

Model | 21-05 ~ 21-08 torque limit initial value | 20-08 ASR filter time initial value (s) | 00-14~00-17 and00-21~00-24 acceleration/deceleration initial time (s) | 11-01 default factory carrier wave kHz | 11-01 maximum carrier wave (SLV,PMSLV maximum frequency >80Hz) kHz | 11-01 maximum carrier wave (other mode) kHz

Shared source group cells explicitly projected to their enclosed model rows; original bounds retained. Not independent engineering ratings.

Appendix One: model-specific initial values and upper limits — PDF page 119

Source row Model Frame 11-01 maximum SLV frequency (Hz), carrier wave <= 8K 11-01 maximum SLV frequency (Hz), carrier wave > 8K 18-00 SLV/SV initial value (low-speed slip compensation)
1 2P5 1 150 150 1.00
2 201 1 150 150 1.00
3 202 2 150 150 1.00
4 203 2 150 150 1.00
5 205 2 150 150 1.00
6 208 3 150 150 1.00
7 401 1 150 150 1.00
8 402 1 150 150 1.00
9 403 2 150 150 1.00
10 405 2 150 150 1.00
11 408 3 150 150 1.00
12 410 3 150 150 1.00

Appendix One: model-specific initial values and upper limits — PDF page 119

Source row Model 21-05 ~ 21-08 torque limit initial value 20-08 ASR filter time initial value (s) 00-14~00-17 and00-21~00-24 acceleration/deceleration initial time (s) 11-01 default factory carrier wave kHz 11-01 maximum carrier wave (SLV,PMSLV maximum frequency >80Hz) kHz 11-01 maximum carrier wave (other mode) kHz
1 2P5 200% 0.001 10.0 4 8 16
2 201 200% 0.001 10.0 4 8 16
3 202 200% 0.001 10.0 4 8 16
4 203 200% 0.001 10.0 4 8 16
5 205 200% 0.001 10.0 4 8 16
6 208 200% 0.001 10.0 4 8 16
7 401 200% 0.001 10.0 4 8 16
8 402 200% 0.001 10.0 4 8 16
9 403 200% 0.001 10.0 4 8 16
10 405 200% 0.001 10.0 4 8 16
11 408 200% 0.001 10.0 4 8 16
12 410 200% 0.001 10.0 4 8 16

Manual — Low-voltage start function description: Wiring schematic diagram: — page 120

Manual reference: physical PDF page 120. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Low-voltage start function description: Wiring schematic diagram:

Motor AC driver

R/L1

Single-phase

UPS or

S/L2

~

battery

T/L3

Single-phase UPS and

battery specifications

440V Vac: 207~380

Vdc: 292~537

S1~S7

Low-voltage start-up

24VG

function action input

Electromagnetic contactor

action timing diagram

Before inputting the backup power, electromagnetic contactors ① and ③ must be turned on, and electromagnetic contactor ② must remain open. Electromagnetic contactor ③ can only be turned on after electromagnetic contactor ① is turned on. When the backup power is about to be removed and before electromagnetic contactor ② is turned on, electromagnetic contactors ① and ③ must remain open.

Notes for low-voltage start-up operation: 1. Start the low-voltage start-up function (DI=62), the fan will not operate to prevent a drop in emergency power voltage. 2. When starting the low-voltage start-up function, there is no input phase loss protection. 3. When starting the low-voltage start-up function, the operating frequency of the motor will operate according to the 07-31 low-voltage operation frequency.

Related parameter descriptions: 07-30 Low-voltage threshold selection setting enabled. 07-13 Low-voltage detection threshold 400V model parameter lower limit can be set to 250V. 03-00~03-06 setting 62 low-voltage startup function action input. 07-31 sets the low-voltage operation frequency.

Manual — Reduce the acceleration and deceleration impacts during the start and stop of equipment such as elevators In passenger elevators, if there are acceleration or d — page 121

Manual reference: physical PDF page 121. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Reduce the acceleration and deceleration impacts during the start and stop of equipment such as elevators In passenger elevators, if there are acceleration or deceleration impact (discomfort) during startup or stopping, please adjust the following parameters

Output

Frequency

t

Apply DC brake while stopping

Deceleration time 1

(It is zero-speed control during PG vector control)

Acceleration time 1

Remark: In the low-speed deceleration S curve characteristic time, when the output frequency did not reach the value set for the minimum output frequency of 01-08 motor 1, the S curve characteristic will be terminated, and change to stop DC braking (zero speed control). DC braking and zero speed control functions while stopping

07-08DC brake time while stopping

Output frequency

(zero-speed brake time when stopping)

0.3 ~0.5 s

Frequency outputting

OFF

ON

Brake operation

When the mechanical action of the brake is slower, to prevent dropping while stopping, please perform DC brake (zero-speed control when using PG vector control) until the brake is fully closed. Remark 1: Regulations in various countries across Europe states that when elevators stop, the inverter and motor has to be separated through a contactor. Except for emergency situations, separation can only occur when the brake is fully closed and the inverter is in base-emitter cut-off (the signal in the base-emitter cut-off is ON). Remark 2: When separating in motor control or DC brake (zero-speed control), sometimes the inverter may malfunction due to surges. In addition, when there is contactor set between the inverter and motor, please set the 08-10 output phase loss protection as 1 (effective).

Manual — 4.3 Descriptions of parameter functions — page 122

Manual reference: physical PDF page 122. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.3 Descriptions of parameter functions

00-Basic function group

The control algorithm of the inverter is as described below:

Table 4.3. 1 Inverter control algorithm

(1). 00-00=0

. Select the V/F curve (01-00) according to the motor and application requirements. . If the motor wiring length is more than 50 meters, stationary motor parameter tuning (17-00=2) needs

to be performed. Please refer to the descriptions in parameter 17-automatic tuning function group to understand descriptions related to motor parameter tuning. (2). 00-00=2

. Confirm that the inverter capacity and motor power corresponds to one another, and use the motor

parameter tuning function to measure and save the motor parameters. . Perform rotational motor parameter tuning before operating to improve the SLV mode performance. . Please refer to the descriptions in parameter 17-automatic tuning function group to learn the

descriptions regarding motor parameter tuning. (3) 00-00=5

Confirm that the inverter capacity and motor power corresponds to one another, and use the motor parameter tuning function to measure and save the motor parameters. Perform automatic tuning before operation to improve the PMSLV mode performance. Please refer to the descriptions in parameter 22-21 PM motor tuning function. Please choose a brake resistor with appropriate power and resistance according to the motor power and application scenario. (4) 00-00=6

. Confirm that the inverter capacitor and motor power corresponds to one another. Use the motor

parameter tuning function to measure and save the motor parameters. . Please refer to the descriptions in parameter 17-automatic tuning function group to learn the

descriptions regarding motor parameter tuning. . Select and adjust the V/F curve (01-00) according to the motor and application requirements.

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Exact source table values. Application presets are not universal defaults; preceding application-reset and I/O warnings remain authoritative.

Group00 detailed parameter definitions — PDF page 122

Source row Code Parameter name Scope/options as printed
1 00- 00 Motor control mode [0]: V/F [1]: Reserved [2]: SLV [3]: Reserved [4]: Reserved [5]: PMSLV [6]: SLV2

Inverter control algorithms — PDF page 122

Source row 00-00 setting Control algorithm Control fundamentals Application example
1 0 V/F . V/F mode without PG (open circuit). . Drives general motor. . Replaces existing inverter. . Location that does not require automatic tuning. . Applicable to ND (general load) mode.
2 2 SLV . Current vector control without PG (Sensorless vector control) Used in application situations without PG, able to provide higher precision in speed and torque requirements.
3 5 PMSLV . Sensorless current vector control without PG for permanent magnet motors). . Used in application situations without PG, able to provide higher precision in speed and torque requirements.
4 6 SLV2 . Voltage vector control without PG. Used in application situations without PG, vector control can provide higher rotation speed operations, and provide higher precision speed and torque requirements than V/F.

Manual — ◇ This 00-00 parameter is not affected by the initialization parameter setting. — page 123

Manual reference: physical PDF page 123. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

◇ This 00-00 parameter is not affected by the initialization parameter setting.

If the operation command is controlled by the button panel (the setting of 00-02 is 0), the button panel can be used to control forward and reverse, and the control results will be saved in 00-01. Users can also modify the 00-01 parameter to control forward and reverse directly. This parameter will be selected by the 11-00 motor direction locking command and restricted to whether it can rotate forward/reverse.

(1) 00-02=0: By setting 00-02=0, use the digital operator button (stop, run and forward/reverse buttons) to execute inverter operations. →(Please use by referring to Chapter 4-1 panels) (2) 00-02=1: By setting 00-02=1, use the control circuit terminals to execute inverter operations.

(1) 00-03=0: By setting 00-03=0, use the digital operator button (stop, run and forward/reverse buttons) to execute inverter operations. →(Please use by referring to Chapter 4-1 panels) (2) 00-03=1: By setting 00-03=1, use the control circuit terminals to execute inverter operations. It must be used with the multi-function digital input function (12: Primary/secondary operation switching function)

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Group00 detailed parameter definitions — PDF page 123

Source row Code Parameter name Scope/options as printed
1 00- 01 Motor operation direction [0]: Forward [1]: Reverse

Group00 detailed parameter definitions — PDF page 123

Source row Code Parameter name Scope/options as printed
1 00- 02 Primary operation command source selection [0]: Button panel control [1]: External terminal control [2]: Communication control [3]: PLC [4]: RTC (in development)

Group00 detailed parameter definitions — PDF page 123

Source row Code Parameter name Scope/options as printed
1 00- 03 Secondary operation command source selection [0]: Button panel control [1]: External terminal control [2]: Communication control [3]: PLC [4]: RTC (in development)

Manual — ■ 2-wire operation — page 124

Manual reference: physical PDF page 124. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ 2-wire operation

‧ The use of 2-wire operation is through execution by setting 03-00 (S1 terminal function selection) to 0 (forward operation/stop) and set 03-01 (S2 terminal function selection) as 1 (reverse operation/stop). ‧ When the control circuit terminal S1 is ON and S2 is OFF, the inverter will rotate forward; and when S1 is OFF, the inverter will stop. ‧ When the control circuit terminal S1 is OFF and S2 is ON, the inverter will rotate in reverse; and when S2 is OFF, the inverter will stop. ‧ 2-wire control is as shown in Figure 4.3.1; if S1 and S2 are both ON simultaneously for more than 500 milliseconds, the warning “EF9 (flashing) FWD-REV error” will pop up and the inverter will stop. After the situation is released, the inverter will resume normal operation.

Forward

operation / stop

S1

Reverse operation /

stop

S2

24VG

Figure 4.3. 1 Example of 2-wire wiring

‧ When the inverter parameter 13-08 (initialization) is set to 2, 4 or 6 and is 2-wire program initialization, the multi-function input terminal S1 will operate in forward direction/stop command, and S2 will be reverse operation/stop command. ■ 3-wire operation ‧ When any of the parameters (multi-function digital input terminal S3~S7) between 03-02 to 03- 06 is set as 26, and the multi-function digital input terminal is set as forward /reverse command, the S1 and S2 terminals will be set as 3-wire control operation command and stop command, and their original functions will be off. ‧ When the inverter parameter 13-08 (initialization) is set to 3, 5 or 7 is 3-wire program initialization. The multi-function digital input terminal S7 is the forward /reverse command. ‧ Figure 4.3.2 below is an example of 3-wire control. The multi-function input terminal S7 is the forward /reverse command terminal.

Operate (Normally

Stop

opened switch)

(Normally closed switch)

Operation command

(On: Operate)

Stop command

(Off: Stop)

Forward / Reverse

S7

command

Figure 4.3. 2 Example of 3-wire wiring

Manual — ‧ The S1 terminal must remain conducted for 50 milliseconds or more for the operation command to self-hold. Please refer to Figure 4.3.3. — page 125

Manual reference: physical PDF page 125. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ The S1 terminal must remain conducted for 50 milliseconds or more for the operation command to self-hold. Please refer to Figure 4.3.3.

3-wire operation program.

≧50 ms

Turn

Turn off

on

Operation command

Time

(Stop)

Stop command

(forward )

Turn on(Reverse)

Forward / Reverse

command

Motor speed

Stop

Forward

Reverse

Figure 4.3. 3 3-wire operation program

Manual — 2-wire operation with self-hold function — page 126

Manual reference: physical PDF page 126. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2-wire operation with self-hold function

‧ When any of the parameters between 03-00 to 03-06 (multi-function digital input terminal S1~S7) is set to 53 (two-wire self-holding stop command), its external operation is 2-wire forward /reverse method but includes the self-holding function. Therefore, the multi-function digital terminal must be set as the stop command (also with self-holding function). ‧ The figure below is an example of 2-wire self-holding wiring; the multi-function input terminal S1 is forward operation (03-00=0), the multi-function input terminal S2 is the reverse operation (03-01=1), and S5 is the 2-wire self-holding stop command (03-04=53).

Self-holding 2-wire wiring example: S1 Forward operation command (with self-holding function); S2 Reverse operation command (with self-holding function); S5 Stop command (with self-holding function); 24VG. Original diagram retains geometry; no unprinted dimensions, timing values or connection details inferred.

Figure 4.3. 4Self-holding 2-wire wiring example

S1, S2 and S5 terminals must remain conducted for 50 milliseconds or more in order for the forward , reverse and stop commands to self-hold.

Please refer to the 2-wire self-holding operation program below.

Self-holding 2-wire operation programme: Forward command, Reverse command, Stop command, Motor speed; Time axes. Three pulse labels read >50 ms. Pulse labels Turn on and Turn off; stop-command inactive label Turn off (inverter operation); final forward pulse note It can be both turned on or off. Lower sequence labels Stop, Forward, Reverse, Stop, Forward. These are example timing diagrams, not live states. Original diagram retains geometry; no unprinted dimensions, timing values or connection details inferred.

Figure 4.3. 5 Self-holding 2-wire operation program

2-wire operation with self-holding function (multi-function digital input terminal S1~S7 set as 53) cannot be set with 3-wire operation(multi-function digital input terminals S1~S7 set as 26) simultaneously. If set simultaneously, the SE02 error will occur.

(3) 00-02=2

‧ Inverter operations can be controlled through the RS-485 communication port. Please refer to parameter 09-communication function group to understand detailed descriptions on RS-422/485 communication.

Manual — (4) 00-02=3 — page 127

Manual reference: physical PDF page 127. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(4) 00-02=3

‧ The inverter operation stop and frequency command can be controlled using the built-in PLC

function of the inverter; the setting values of 00-05 is ineffective at this time. ‧ At this time, the RUN and STOP buttons on the operator can be used to start and stop the built-in

PLC function of the inverter. (5) 00-02=4

‧ When the primary operation command is set as RTC, the inverter operation command will be

executed according to the RTC timer actions.

The 00-04 language selection parameters must be used with the LCD digital operator in order to be displayed.

‧ When 00-04 is set as 0, the string on the LCD digital operator will be displayed in English. ‧ When 00-04 is set as 1, the string on the LCD digital operator will be displayed in Simplified Chinese. ‧ When 00-04 is set as 2, the string on the LCD digital operator will be displayed in Traditional Chinese. ‧ When 00-04 is set as 3, the string on the LCD digital operator will be displayed in Turkish. Remark: When initializing parameters, this parameter will not be restored to the default factory value.

(1) 00-05/00-06=0:

‧ The digital operator inputs the frequency reference command directly, or is set by changing the parameter

05-01 (frequency reference 1). Please refer to section 4.1.4, screen mode - frequency reference setting details. ‧ If the secondary frequency is set as the digital operator (00-06 = 0), the frequency command of the

secondary frequency can only be modified in parameter 05-01.

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Group00 detailed parameter definitions — PDF page 127

Source row Code Parameter name Scope/options as printed
1 00- 04 Language selection [0]: English [1]: Simplified Chinese [2]: Traditional Chinese [3]: Turkish

Group00 detailed parameter definitions — PDF page 127

Source row Code Parameter name Scope/options as printed
1 00- 05 Primary frequency command source selection [0]: Set with the up and down button on the button panel [1]: External control (analog AI1) [2]: Terminal UP/DOWN [3]: Communication control [4]: Pulse input [5]: Reserved [6]: RTC(in development) [7]: AI2 auxiliary frequency [8]: Panel knob VR [9]: Handwheel frequency (in development) (only 00-05 has this option)
2 00- 06 Secondary frequency command source selection [0]: Set with the up and down button on the button panel [1]: External control (analog AI1) [2]: Terminal UP/DOWN [3]: Communication control [4]: Pulse input [5]: Reserved [6]: RTC(in development) [7]: AI2 auxiliary frequency [8]: Panel knob VR [9]: Handwheel frequency (in development) (only 00-05 has this option)

Manual — (2) 00-05/00-06=1: ‧ Enter the frequency reference command from the control circuit terminal AI1 (voltage/current input) or AI2 (voltage/current input, set thro — page 128

Manual reference: physical PDF page 128. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(2) 00-05/00-06=1: ‧ Enter the frequency reference command from the control circuit terminal AI1 (voltage/current input) or AI2 (voltage/current input, set through 04-00). ‧ When the input voltage signal is the primary frequency reference command, use the AI1 terminal. ‧ When the input current signal (4-20mA) is the primary frequency reference command, then use the AI2 terminal; the setting steps are as shown below: ① Input 0V to the AI1 terminal ② Set 04-00=1: (Choose 4~20mA input as the multi-function analog input terminal AI2 signal) ③ Set the flip switch SW4 to the I (current) position. ④ Set 04-05=10 (add the AI2 signal to AI1). ‧ Refer to Figure 4.3.6 to understand the details for selecting analog terminal setting as the primary speed frequency source.

Analog input for the primary speed frequency reference command: +10V, AI1, AI2, GND, 2KΩ. AI1 callout: Primary speed frequency reference command (Voltage input). AI2 callout: Primary speed frequency reference command (Current input). Switch labels AI1/SW3 and AI2/SW4. Original source notes separately specify the switching conditions; switch geometry is not reconstructed. Original diagram retains geometry; no unprinted dimensions, timing values or connection details inferred.

Figure 4.3. 6 Analog input for the primary speed frequency reference command Remarks

  1. When the current signal is entered to the AI2 terminal, select the voltage/current switching switch SW4 to I (original factory setting), and set 04-00= 1 or 3 (AI2=4~20mA). 2. When the voltage is entered to the AI2 terminal, select the voltage/current switching switch SW4 to the V (original factory setting) position and set 04-00= 0 or 2 or 4 (AI2 = 0~10V). 3. Follow the AI1 input signal and set 04-00 correctly.

Manual — (3) 00-05/00-06=2: — page 129

Manual reference: physical PDF page 129. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(3) 00-05/00-06=2:

Use the frequency increase and decrease functions of the DI terminal to control the frequency command. Please refer to the parameter descriptions 03-00 to 03-06 to understand related functions. (4) 00-05/00-06=3:

Use PLC or other MODBUS protocol related devices to input the frequency reference from the RS-485 communication port. Please refer to parameter 09-communication function group to understand more communication

descriptions on RS-485. (5) 00-05/00-06=4:

Use pulse input as the frequency command. Please refer to the descriptions of parameters 03-30~03-34 to understand the details on using pulse input. Use the frequency reference function of pulse input, as shown in Figure 4.3.7. Since the PI input terminal has built-in pull-up resistance, if the open collector input method is used, external resistors are not required.

Serial pulse input

PI

(Internal impedance: 3.89 K)

Specifications

L level - 0.0 to 0.5 V

H level - 4.0 to 13.5 V

Duty cycle - (ON / OFF) 30 % to 70%

GND

Pulse frequency - 50 to 32 KHz

0V

Figure 4.3. 7 Frequency reference function of pulse input

(6) 00-05/00-06=6:

Use the RTC function as the source of frequency command; please refer to the related descriptions of the RTC function in group 16. (7) 00-05/00-06=7:

When 04-05 is set to 0 (auxiliary frequency), the frequency command can be provided through the multi- function analog input AI2, with a maximum output frequency of (01-02, Fmax) = 100%. If 04-05 is not set to 0 and the frequency is 0, please refer to the descriptions of multi-speed in parameter 03-00~03-06. (8) 00-05/00-06=8:

Use the FREQ.SET knob on the panel as the frequency command. (9) 00-05=9:

Use the handwheel as the frequency command; the rotation speed of the handwheel is multiplied by the speed calculation multiplier (20-43), then limited by the parameter speed command limit (20-44), and used as the inverter's operating command. Selecting this option requires the installation of an induction motor with a PG card (JN7-PG-L or JN7-PG-O).* PG card is only available for special projects

Manual — (1) When 00-07= 0, the frequency source is set by parameter 00- 05. (2) When 00-07= 1, the frequency source is the primary frequency source set by parameter 00- — page 130

Manual reference: physical PDF page 130. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1) When 00-07= 0, the frequency source is set by parameter 00- 05. (2) When 00-07= 1, the frequency source is the primary frequency source set by parameter 00- 05 plus the

secondary frequency source set by 00- 06. At this time, 00-05 and 00-06 cannot have the same frequency source set, otherwise the error message SE01 will be displayed. If the primary frequency source is from external control and the secondary frequency source is from the digital operator, the frequency of the secondary frequency source is set by the 0 segment speed frequency (05-01) setting.

‧ This parameter is used to read communication frequency commands (read only). ‧ This parameter is only effective in communication mode.

‧ This parameter is only effective in communication mode.

‧ When 00-10=0: When the frequency command is lower than 01-08 (minimum output frequency), the STP0 warning will pop up. ‧ When 00-10=1: When the frequency command is lower than 01-08 (minimum output frequency), it will operate with the minimum output frequency. ‧ When 00-10=1: When the frequency command is lower than 01-08 (minimum output frequency), there is no stp0 warning and it will output the frequency command. ‧ When 00-10=1: When the frequency command is lower than 01-08 (minimum output frequency), there is no stp0 warning and it will output 0 when it is lower than the minimum frequency.

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Group00 detailed parameter definitions — PDF page 130

Source row Code Parameter name Scope/options as printed
1 00- 07 Frequency source combination mode selection [0]: Primary frequency source [1]: Primary frequency source + secondary frequency source

Group00 detailed parameter definitions — PDF page 130

Source row Code Parameter name Scope/options as printed
1 00- 08 Communication frequency command 【0.00~599.00】Hz

Group00 detailed parameter definitions — PDF page 130

Source row Code Parameter name Scope/options as printed
1 00- 09 Communication frequency command memory [0]: Do not memorize the communication frequency command before power failure (00- 08) [1]: Memorize the communication frequency command before power failure (00-08)

Group00 detailed parameter definitions — PDF page 130

Source row Code Parameter name Scope/options as printed
1 00- 10 Minimum frequency detection action [0]: A warning will pop up when lower than the minimum frequency [1]: Operates with minimum frequency when lower than the minimum frequency [2]: No stp0 warning, output frequency command [3]: No stp0 warning, output 0 when lower than the minimum frequency

Manual — ‧ When the PID frequency lower limit is in sleep mode (please refer to parameter descriptions 10-17 to — page 131

Manual reference: physical PDF page 131. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ When the PID frequency lower limit is in sleep mode (please refer to parameter descriptions 10-17 to

10-20), if 00-11 = 0, the PID sleep mode will limit the frequency lower limit. If 00-11 = 1, PID sleep mode will limit the frequency to 0 Hz.

The upper and lower limits of the frequency reference are based on the maximum 100% output reference, either 01-02 (Fmax) or 01-16, with a base increment of 0.1%.

‧ The setting value of 00-12 must be greater than 00-13, otherwise the “SE01” set range error message

will be displayed. ‧ When the frequency reference is zero and the operation command is inputted, the motor operates at the lower limit of the frequency reference, determined by 00-13 and the minimum frequency of 01- 08 (or 01-22). Please refer to Figure 4.3.8.

Reference-frequency upper/lower-limit diagram labels: Output Frequency; 100%; 00-12 upper plateau; 00-13 lower plateau; Frequency Reference; 100%. The adjoining prose defines the limits and conditions. Original diagram retains geometry; no unprinted dimensions, timing values or connection details inferred.

Figure 4.3. 8 Reference frequency upper and lower limits

The maximum set frequency on the panel is based on 01-02 combined with 00-12, with the frequency upper limit not exceeding 599 Hz. And the AI analog input frequency is 100% of 01-02.

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Group00 detailed parameter definitions — PDF page 131

Source row Code Parameter name Scope/options as printed
1 00- 11 PID frequency lower limit selection [0]: PID sleep limit frequency lower limit [1]: PID sleep limit 0Hz

Group00 detailed parameter definitions — PDF page 131

Source row Code Parameter name Scope/options as printed
1 00-12 Frequency upper limit 【0.1~109.0】%
2 00-13 Frequency lower limit 【0.0~109.0】%

Manual — Set the various acceleration/deceleration time; the original acceleration time set by the manufacturer was 00- 14, and the deceleration time is 00-15. — page 132

Manual reference: physical PDF page 132. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Set the various acceleration/deceleration time; the original acceleration time set by the manufacturer was 00- 14, and the deceleration time is 00-15.

‧ Acceleration time: The maximum output frequency (01-02) or (01-16) time required from 0% to 100% ‧ Deceleration time: The maximum output frequency (01-02) or (01-16) time required from 0% to 100% The default factory settings of the acceleration/deceleration time and jog acceleration/deceleration time vary from model to model.

Table 4.3. 2The default factory acceleration/deceleration times of the various models

A. Switch between acceleration/deceleration time through multi-function digital input terminals. Use the multi-function digital input terminals (S1 ~S7), in combination with the ON/OFF status of the terminals to choose the acceleration/deceleration times during operation. The table below shoes the switching combinations of the acceleration/deceleration times (binary).

Table 4.3. 3 Conversion combinations of acceleration/deceleration times

0 : OFF 1 : ON

Digital-input acceleration/deceleration switching example: Output Frequency; Tacc1 Rate, Tacc2 Rate, Tdec2 Rate, Tdec1 Rate; Digital Input Terminal S5 (03-04=10); time axes. The source selection table separately specifies which parameters each binary combination selects. Original diagram retains geometry; no unprinted dimensions, timing values or connection details inferred.

Figure 4.3. 9 Switching between acceleration/deceleration times through the multi-function digital input (example)

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Exact source table values. Application presets are not universal defaults; preceding application-reset and I/O warnings remain authoritative.

Group00 detailed parameter definitions — PDF page 132

Source row Code Parameter name Scope/options as printed
1 00-14 Acceleration time 1 【0.1~6000.0】 Sec
2 00-22 Deceleration time 3 【0.1~6000.0】 Sec
3 00-15 Deceleration time 1 【0.1~6000.0】 Sec
4 00-23 Acceleration time 4 【0.1~6000.0】 Sec
5 00-16 Acceleration time 2 【0.1~6000.0】 Sec
6 00-24 Deceleration time 4 【0.1~6000.0】 Sec
7 00-17 Deceleration time 2 【0.1~6000.0】 Sec
8 00-25 Acceleration/deceleration switching frequency 【0.00~599.00】Hz
9 00-21 Acceleration time 3 【0.1~6000.0】 Sec

Model acceleration/deceleration default — PDF page 132

Source row Horse power (200V class) Horse power (400V class) Default acceleration/deceleration time
1 0.5~7.5HP 1~10HP 10s

Multi-function digital input acceleration/deceleration selection — PDF page 132

Source row Selection2 (03-00 to03-06=30) Selection1 (03-00 to03-06=10) Acceleration time Deceleration time
1 0 0 Taccc1(00-14) Tdec1(00-15)
2 0 1 Taccc2(00-16) Tdec2(00-17)
3 1 0 Taccc3(00-21) Tdec3(00-22)
4 1 1 Taccc4(00-23) Tdec4(00-24)

Manual — B. Switch between the acceleration/deceleration times according to the motor selection — page 133

Manual reference: physical PDF page 133. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

B. Switch between the acceleration/deceleration times according to the motor selection

Set the function of the multi-function terminal to 40 motor1/motor2 switching, and the input terminal switch can be used to switch between motors. The switching of motor1/motor2 is limited to VF control mode an VF with PG control mode only.* PG card is only available for special projects

When motor1 is selected, the multi-stage acceleration/deceleration time switches in accordance with Table 4.3.3.

When motor2 is selected, the multi-stage acceleration/deceleration time switches in accordance with Table 4.3.4.

Table 4.3. 4Motor2 acceleration/deceleration time selection

Exact source table values. Application presets are not universal defaults; preceding application-reset and I/O warnings remain authoritative.

Motor2 acceleration/deceleration selection — PDF page 133

Source row Selection1 (03-00 to03-06=10) Acceleration time Deceleration time
1 0 Taccc3(00-21) Tdec3(00-22)
2 1 Taccc4(00-23) Tdec4(00-24)

Manual — C. Automatically switches acceleration/deceleration times — page 134

Manual reference: physical PDF page 134. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

C. Automatically switches acceleration/deceleration times

‧ When the setting value of the output frequency reaches 00-25, the first and forth acceleration/deceleration times are switched automatically according to the set frequency in 00-25. Please refer to Figure 4.3.10 below.

Automatic acceleration/deceleration switching diagram labels: Output Frequency; 00-25 switching level; Tacc1 Rate (00-14), Tacc4 Rate (00-23), Tdec4 Rate (00-24), Tdec1 Rate (00-15); time. Original diagram retains geometry; no unprinted dimensions, timing values or connection details inferred.

Figure 4.3. 10 Automatic acceleration/deceleration switching

‧ When the output frequency Fout<00-25: The acceleration/deceleration time = first acceleration time/first deceleration time (00-14 and 00-15). ‧ When the output frequency Fout ≧ 00-25: The acceleration/deceleration time = the fourth acceleration time/fourth acceleration time (00-23 and 00-24) ‧ The priority of multi-function digital input acceleration/deceleration time selection 1 (03-00~03-06 set as 10) and acceleration/deceleration time selection 2 (set to 30) is higher than 00-25.

00-19 (jog acceleration time) The acceleration time set from zero to the maximum output frequency (01-02) or (01-16), and the acceleration time 00-20 (jog deceleration time) is set from the maximum output frequency (01-02) or (01-16) to zero. Set the operation command source (00-02) to 1 for external terminal control. Set the jog frequency in 00-18 (default factory setting is 6.0Hz), and configure the multi-function terminal settings 03-00 to 03-06 and set them to the jog forward command (6) or jog reverse command (7), and the motor will operate according to the configured settings.

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Group00 detailed parameter definitions — PDF page 134

Source row Code Parameter name Scope/options as printed
1 00-18 Jog frequency 【0.00~599.00】Hz
2 00-19 Jog acceleration time 【0.1~600.0】Sec
3 00-20 Jog deceleration time 【0.1~600.0】Sec

Manual — Use the multi-function digital input terminal (S1~S7) to decelerate and stop within the time set in 00-26 ● Set the multi-function digital input terminal (03-00 — page 135

Manual reference: physical PDF page 135. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Use the multi-function digital input terminal (S1~S7) to decelerate and stop within the time set in 00-26 ● Set the multi-function digital input terminal (03-00~03-06) to 14: When the emergency stop contact is ON (it is usually ON), decelerate and stop within the time set in 00-26. ● Set the multi-function digital input terminal (03-00~03-06) to 15: When the emergency stop contact is OFF (it is usually OFF), it will stop freely. ● After the emergency stop command is entered, the inverter cannot be restarted before it stops. To cancel emergency stop, please close the operation command and emergency stop command. Please refer to Figure 4.3.11 below. ● When error is detected, this function can be used as a way of stopping.

Emergency-stop example diagram: Emergency stop command S5 (03-04=14), ON and OFF; Run command, ON; Output Frequency; Emergency stop deceleration time; time axes. Source prose and drawn ON/OFF timing are both retained without resolving their apparent discrepancy. Original diagram retains geometry; no unprinted dimensions, timing values or connection details inferred.

Figure 4.3. 11 An example of emergency stop operation

‧ When the analog frequency reference signal is entered from the control terminal AI1 or AI2, select the

characteristic of the primary frequency reference command for the corresponding analog signal. ‧ 00-28 = 0: The positive characteristic of the primary frequency reference command. (0-10V or 4-20mA /0-100%, -10-0V/-100%-0) = 1: Inverse characteristics of the primary frequency reference. ‧ Please refer to Figure 4.3.12 below for the characteristics of the primary frequency reference ‧ When analog frequency reference signal is inputted into AI2, it must be below 04-05=0 (auxiliary frequency) in order to be effective.

( % )

100%

Analog input

signal

0V

10V

(4 mA)

(20 mA)

(b) Reverse Characteristics

(a) Forward Characteristics

Figure 4.3. 12Positive/inverse characteristics of the primary frequency reference

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Group00 detailed parameter definitions — PDF page 135

Source row Code Parameter name Scope/options as printed
1 00- 26 Emergency stop time 【0.0~6000.0】 Sec

Group00 detailed parameter definitions — PDF page 135

Source row Code Parameter name Scope/options as printed
1 00- 28 Primary frequency command characteristic selection [0]: Positive characteristic (0~10V/4~20mA corresponds to 0~100%) [1]: Negative characteristic (0~10V/4~20mA corresponds to 100~0%)

Manual — Under sensor vector mode (SV/PMSV) (00- 00=3/4 ), when the operating frequency is lower than the minimum output frequency, as shown in Figure 4.3.13. — page 136

Manual reference: physical PDF page 136. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Under sensor vector mode (SV/PMSV) (00- 00=3/4 ), when the operating frequency is lower than the minimum output frequency, as shown in Figure 4.3.13.

Operation

command

Time

Frequency

Reference

Fmin ( 01 - 08)

( Fref)

Output

after softstart

( Fout ( SFS))

B.B

07 - 16

07 - 08

pre- excite

time

Fmin

coast to

stop

zero

07 - 08

speed

07- 16

operation

Figure 4.3. 13 Zero speed operation of vector control (SV/PMSV) mode

‧ When the operation command (forward or reverse) is OFF, when the output frequency reduces to the

activation frequency of the DC brake (07-06), and the DC brake executes this function according to the execution time of the DC brake (07-08), please refer to Figure 4.3.84 for details on pre-excitation operations.

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Group00 detailed parameter definitions — PDF page 136

Source row Code Parameter name Scope/options as printed
1 00- 29 Zero-speed operation selection [0]: Operates according to the frequency command [1]: Stop [2]: Operates according to the minimum frequency [3]: Zero speed operation

Manual — Note 1: If the setting value is changed back to 0 (off) by other setting values, 2-wire initialization will be performed (230/400V)(60Hz) Note 2: Before setting — page 137

Manual reference: physical PDF page 137. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note 1: If the setting value is changed back to 0 (off) by other setting values, 2-wire initialization will be performed (230/400V)(60Hz) Note 2: Before setting the parameter 00-32 application adjustment, please perform 13-08 initialization setting first. Warning: If parameter 00-32 (application adjustment) is set, then the input/output terminal setting function will change automatically according to the setting value. Before trial run, please confirm the input/output signal of the inverter and the external sequence control first. Failure to confirm may result in personal accidents. (1). Reserved (2). Conveyor-specific parameters

(3) : Exhaust fan-specific parameters

Detailed source definitions, not catalogue ratings or independent commissioning guidance. Shared option bounds retained for00-05/06; special-project/development qualifications and source discrepancies remain explicit.

Exact source table values. Application presets are not universal defaults; preceding application-reset and I/O warnings remain authoritative.

Group00 detailed parameter definitions — PDF page 137

Source row Code Parameter name Scope/options as printed
1 00- 32 Application adjustment [0]: Universal [1]: Reserved [2]: Conveyor-specific parameters [3]: Exhaust fan-specific parameters [4]: Reserved [5]: Air compressor-specific parameters [6]: Hoist-specific (for lifting and lowering) parameters [7]: Crane-specific (for lateral movement) parameters [8]: Handwheel-specific parameters [9]: EVERISING sawing machine-specific parameters [10]: Punch press-specific parameters [11]: Textile machine-specific parameters

Conveyor-specific parameters — PDF page 137

Source row Parameters Name Settings
1 00-00 Control mode selection 0 : V/F
2 00-14 Acceleration time 1 3.0 sec
3 00-15 Deceleration time 1 3.0 sec
4 08-00 Stall prevention function xx0x: Stall prevention effective during deceleration

Exhaust fan-specific parameters — PDF page 137

Source row Parameters Name Settings
1 00-00 Control mode selection 0 : V/F
2 11-00 Direction locking command 1: Reverse prohibited
3 00-27 Reserved -
4 01-00 V/F curve selection F
5 07-00 Instantaneously stop and restart selection 1: Effective
6 08-00 Stall prevention function xx0x: Stall prevention effective during deceleration

Manual — (5). Air compressor-specific parameters — page 138

Manual reference: physical PDF page 138. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(5). Air compressor-specific parameters

(6). Hoist-specific (for lifting and lowering) parameters

Exact source table values. Application presets are not universal defaults; preceding application-reset and I/O warnings remain authoritative.

Air compressor-specific parameters — PDF page 138

Source row Parameters Name Settings
1 00-00 Control mode selection 0 : V/F
2 11-00 Direction locking command 1: Reverse prohibited
3 00-14 Acceleration time 1 5.0 sec
4 00-15 Deceleration time 1 5.0 sec
5 01-00 V/F curve selection F
6 07-00 Instantaneously stop and restart selection 1: Effective
7 08-00 Stall prevention function xx0x: Stall prevention effective during deceleration

Hoist-specific lifting/lowering parameters — PDF page 138

Source row Parameters Name Settings
1 00-00 Control mode selection 2: SLV
2 00-05 Primary frequency command source selection 0: Button panel
3 11-43 Frequency holding during startup 3.0 Hz
4 11-44 Time holding during startup 0.3 sec
5 00-14 Acceleration time 1 3.0 sec
6 00-15 Deceleration time 1 3.0 sec
7 11-01 Carrier frequency 5.0kHz
8 05-01 Segment 0 speed frequency setting 6.0 Hz
9 05-02 Segment 1 speed frequency setting 30.0 Hz
10 05-03 Segment 2 speed frequency setting 60.0 Hz / 50Hz
11 03-28 Optocoupler output 5: Frequency detected 2
12 07-18 Cut-off time 0.3 sec
13 08-00 Stall prevention function xx1x: Stall prevention ineffective during deceleration
14 03-13 Frequency detection threshold 2.0 Hz
15 03-14 Frequency detection width 0.1 Hz
16 08-18 Undertorque action selection 0: Deceleration stop after detection
17 08-19 Undertorque detection threshold 2%
18 08-20 Undertorque detection time 0.5 sec
19 08-09 Input phase loss protection selection 1: Effective
20 08-10 Output phase loss protection selection 1: Effective

Manual — (7). Crane-specific (for lateral movement) parameters — page 139

Manual reference: physical PDF page 139. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(7). Crane-specific (for lateral movement) parameters

(8). Handwheel-specific parameters [struck-through: (in development)] only for special cases

Exact source table values. Application presets are not universal defaults; preceding application-reset and I/O warnings remain authoritative.

Crane-specific lateral movement parameters — PDF page 139

Source row Parameters Name Settings
1 00-00 Control mode selection 0: V/F
2 00-05 Primary frequency command source selection 0: Button panel
3 00-14 Acceleration time 1 3.0 sec
4 00-15 Deceleration time 1 3.0 sec
5 11-01 Carrier frequency 5.0kHz
6 05-01 Segment 0 speed frequency setting 6.0 Hz
7 05-02 Segment 1 speed frequency setting 30.0 Hz
8 05-03 Segment 2 speed frequency setting 60.0 Hz/50.0Hz
9 03-04 Multi-function terminal S5 function setting 2: Multi-speed command 1
10 03-05 Multi-function terminal S6 function setting 3: Multi-speed command 2
11 03-28 Optocoupler output 23: Frequency command source
12 08-00 Stall prevention function xx1x: Stall prevention ineffective during deceleration
13 08-09 Input phase loss protection selection 1: Effective
14 08-10 Output phase loss protection selection 1: Effective

Handwheel-specific parameters; source strikes in-development and restricts to special cases — PDF page 139

Source row Parameters Name Settings
1 00-00 Control mode selection 0 : V/F
2 00-02 Primary operation command source selection 1: External control
3 00-05 Primary frequency command source selection 9: Handwheel frequency
4 00-16 Acceleration time 2 0.1 sec
5 00-17 Deceleration time 2 0.1 sec
6 01-00 V/F curve selection F
7 07-09 Stop mode selection 1: Free-run stop
8 07-18 Minimum cut-off time 0.1 sec
9 07-46 DC injection current limit 100%
10 08-00 Stall prevention function xx1x: Stall prevention ineffective during deceleration
11 11-62 Prevent oscillation selection 2: Mode 3
12 20-08 ASR delay time 0
13 20-27 PG pulse count 100
14 20-43 Speed multiplier 20
15 20-44 Speed command limit 6.0 Hz

Manual — Application presets: sawing, punch press, textile — page 140

Manual reference: physical PDF page 140. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(9). EVERISING sawing machine-specific parameters

(10). Punch press-specific parameters

(11). Textile machine-specific parameters

Exact source table. Application preset values are not universal defaults; screen numbers are historical examples, not current device settings. Empty source cells retained without inference.

EVERISING sawing machine-specific parameters — PDF page 140

Source row Parameter code Name Setting as printed
1 00-00 Control mode selection 5 :PMSLV
2 00-02 Primary operation command source selection 1: External control
3 00-05 Primary frequency command source selection 1: External control AI1 frequency
4 00-13 Frequency lower limit 20.0%
5 00-14 Acceleration time 1 10.0 sec
6 00-15 Deceleration time 1 7.0 sec
7 00-23 Acceleration time 4 4.5 sec
8 00-25 Acceleration/deceleration switching frequency 13.5Hz
9 01-14 Motor 1 input voltage setting 220/440V
10 07-00 Instantaneously stop and restart selection 0: Ineffective
11 08-00 Stall prevention function Xx0x: Stall prevention effective during deceleration
12 11-00 Motor direction locking command 0: Allow forward and reverse
13 11-55 STOP button selection 1: When the run command is not issued via the digital operator, the STOP key is enabled.
14 12-03 Linear speed display (LED) 100
15 12-04 Display speed display mode (LED) 2: Use 1 decimal place to display the linear speed (XXXX.X)
16 22-05 PM motor maximum rotation speed 2700 rpm
17 22-04 PM motor rotation speed 1800 rpm
18 22-36 PM motor type selection 1 : IPM
19 22-37 PM motor horse power Choose according to model
20 13-06 Parameter lock 0: Read only

Punch press-specific parameters — PDF page 140

Source row Parameter code Name Setting as printed
1 00-14 Acceleration time 1 3.0
2 00-15 Deceleration time 1 3.0
3 00-23 Acceleration time 4 10.0
4 00-24 Deceleration time 4 10.0
5 00-25 Acceleration/deceleration switching frequency 30.0Hz
6 07-09 Stop mode selection 1
7 07-34 Short-circuit brake time while starting 0
8 20-00 ASR gain 1 0.30
9 20-01 ASR integral time 1 0.100
10 20-02 ASR gain 2 0.10
11 20-03 ASR integral time 2 0.100
12 20-04 ASR integral time limit 200
13 20-15 ASR gain change frequency 1 4.0
14 20-16 ASR gain change frequency 2 8.0
15 22-29 Weak magnetic voltage command limit 100

Textile machine-specific parameters — PDF page 140

Source row Parameter code Name Setting as printed
1 00-63 Frequency upper and lower limit setting selection 1: Frequency
2 00-02 Primary operation command source selection 1: External control
3 00-05 Primary frequency command source selection 1: External control AI1 frequency
4 00-14 Acceleration time 1 3.0 sec
5 00-15 Deceleration time 1 0.5 sec
6 00-19 Jog acceleration time 3.0 sec
7 00-20 Jog deceleration time 0.5 sec
8 00-18 Jog frequency 10.00Hz
9 00-34 Multi-function terminal operation mode selection 1: Operate/stop-reverse/forward

Manual — Textile presets and changed-parameter display — page 141

Manual reference: physical PDF page 141. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note: for LCD use only. ‧ Changing the parameter will list all changed parameters automatically; when the default factory setting value was changed, and the change parameter 00-33=1 is set as effective, advanced mode will list all different default factory parameters one by one at this time, and these parameters can be edited directly. Changing the parameter list items is determined only when 00-33 is set from 0 to 1 or when 00-33 is 1 at power-on. ‧ To return to the normal editing page, simply set the changed parameter 00-33 = 0 to make it invalid. ‧ The display function for displaying the changed parameters can list up to 250 changed parameters. If there are more than 250, only the first 250 changed parameters will be listed. For example: Set 00-03 (secondary operation command source selection) to something different from the default factory setting.

Exact source table. Application preset values are not universal defaults; screen numbers are historical examples, not current device settings. Empty source cells retained without inference.

Source parameter definition; development or special-project restrictions elsewhere in the manual remain applicable.

Textile machine-specific parameters continued — PDF page 141

Source row Parameter code Name Setting as printed
1 03-00 Multi-function terminal S1 function setting 0: Two-wire forward /stop
2 03-01 Multi-function terminal S2 function setting 1: Two-wire reverse/stop
3 03-02 Multi-function terminal S3 function setting 70: Jog frequency operation

Changed-parameter display procedure; LCD example — PDF page 141

Source row Step LCD display text (example only) Procedure
1 1 ⟦blank source cell⟧ The increase/decrease buttons are used to select the starting parameter group (00) under group setting mode.
2 2 PARA 00 -01. Motor Direction -02. RUN Source --03. Sub RUN Source Press the READ/Enter button and increase/decrease buttons to select the secondary operation command source selection (00-03) under sub-group editing. .
3 3 Edit 00-00 Sub RUN Source 1 Terminal (0 ~4) <2> Press the READ /ENTER button to enter the data setting/read screen and change the values. (the selected setting value will flash)
4 4 PARA 00 -33. Modify parameter -41. User P1 -42. User P2 Press the DSP/FUN button once to return to change parameters (00-33) under sub-group editing.
5 5 Edit 00-33 Modify parameter 1 Enable (0 ~1) <0> Press the READ /ENTER button to enter the data setting/read screen, and change the value to 1 (changed parameter effective). (the selected setting value will flash).
6 6 Modify 00 00-03. Sub RUN Source 00-33. Modify parameter Press the DSP/FUN button once to return to advanced mode.

Detailed parameter definition — PDF page 141

Source row Parameter code Name Scope/options as printed
1 00- 33 Change parameters [0]: Ineffective [1]: Effective

Manual — Terminal modes and user parameter definitions — page 142

Manual reference: physical PDF page 142. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1) When 00-34=0: When the multi-function terminal setting is selected as 0 or 1, it will perform the forward/stop and reverse/stop functions, respectively. (2) When 00-34=1: When the multi-function terminal setting is selected as 0 or 1, it will perform the operate/stop and reverse/forward functions, respectively. (3) When 00-34=2: When multi-function terminals S3 ~ S6 are set to 26, the multi-function digital input terminals will be set to forward /reverse commands. Terminals S1 and S2 will be set to 3-wire control operation and stop commands, with the original functions disabled. User parameter setting (00-41 to 00-56) (for LCD use only)

‧ Any 16 parameters (except for 00-00, 00-41~00-56, and the parameters from group 0 to group 22 other than group 17) can be planned (selected) for user parameters (00-41 to 00-56) and placed in the same list. This feature allows frequently used parameters to be accessed and set quicker.

‧ When the access level (13-06) is set to 1 (user level), user parameters 00-41 to 00-56 can be displayed and changed.

‧ User parameters 00-41 to 00-56 can only be changed under advanced mode, and cannot be changed while operating.

‧ Usage method: Set the parameter values you want from 00-41 to 00-56, then set 13-06 to 1.

‧ When 13-06=1 (user level), only the parameters from 00-00 to 00-56 can be set or can be read under advanced mode, and 13-06=1 can only be performed when 00-41 to 00-56 is set.

‧ When in user level, to exit, first press RESET on the home page, and then press the hotkey DSP / FUN to call group 13.

Exact source table. Application preset values are not universal defaults; screen numbers are historical examples, not current device settings. Empty source cells retained without inference.

Source parameter definition; development or special-project restrictions elsewhere in the manual remain applicable.

User parameter function definitions; LCD only — PDF page 142

Source row Parameter code Function name
1 00- 41 User parameter 0 Function setting
2 00- 42 User parameter 1 Function setting
3 00- 43 User parameter 2 Function setting
4 00- 44 User parameter 3 Function setting
5 00- 45 User parameter 4 Function setting
6 00- 46 User parameter 5 Function setting
7 00- 47 User parameter 6 Function setting
8 00- 48 User parameter 7 Function setting
9 00- 48 User parameter 8 Function setting
10 00- 50 User parameter 9 Function setting
11 00- 51 User parameter 10 Function setting
12 00- 52 User parameter 11 Function setting
13 00- 53 User parameter 12 Function setting
14 00- 54 User parameter 13 Function setting
15 00- 55 User parameter 14 Function setting
16 00- 56 User parameter 15 Function setting

Detailed parameter definition — PDF page 142

Source row Parameter code Name Scope/options as printed
1 00- 34 Multi-function terminal operation mode selection [0]: Forward /stop-reverse/stop [1]: Operate/stop-reverse/forward [2]: 3-wire operation/stop

Manual — User parameter assignment examples — page 143

Manual reference: physical PDF page 143. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 1: Set 03-00 (multi-function terminal S1 function setting) to user parameter 0 (00-41)

Example 2: After one or multiple parameters from 00-41 to 00-56 is set, set the user set parameter, as shown in the example below:

Exact source table. Application preset values are not universal defaults; screen numbers are historical examples, not current device settings. Empty source cells retained without inference.

Example1: assign03-00 to user parameter0 (00-41) — PDF page 143

Source row Step LCD display text (example only) Procedure
1 1 ⟦blank source cell⟧ Select start parameter group (00) under advanced mode.
2 2 PARA 00 -41. User P0 -42. User P1 -43. User P2 Press the READ / Enter buttons and accelerate / decelerate buttons to select user parameter 0 (00-41). .
3 3 Edit 00- 1 User P0=00 41 00-41 User P0 <00-01 - 24-07> Press the READ / ENTER button to enter the data setting/read screen. (the selected setting value will flash)
4 4 Edit 00-41 User P0=00-41 03-00 S1 Function Sel <00-01 - 24-07> Use the left / right buttons and accelerate / decelerate buttons to set the setting value to 03-00 (multi-function terminal S1 function setting).
5 5 Edit 00-41 User P0= 03-00 03-00 S1 Function Sel <00-01 - 24-07> Press the READ / Enter button to save the setting value (03-00), and the number will stop flashing and display User P0 = 03-00; 03-00 (multi-function terminal S1 function setting) is defined as 00-41. The number selected will start flashing again a few seconds later.
6 6 Monitor Freq Ref 12-16=000.00Hz ----- ------------- ----------- ------- 12-17=000.00Hz 12-18=0000.0A Press the DSP / FUN button once to return to the home page of the operator. (If the DSP / FUN button was not pressed within one minute, the display screen will return to the monitor mode screen in the left figure automatically. The automatic return time can be set with 16-06).

Example2: access configured user parameters, step1 — PDF page 143

Source row Step LCD display text (example only) Procedure
1 1 Group 13 Driver Status 14 PLC Setting 15 PLC Monitor Select start parameter group (03) under advanced mode.

Manual — User level access and editing procedure — page 144

Manual reference: physical PDF page 144. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact source table. Application preset values are not universal defaults; screen numbers are historical examples, not current device settings. Empty source cells retained without inference.

Example2 continued, step2 — PDF page 144

Source row Step LCD display text (example only) Procedure
1 2 PARA 13 -06. Access Level -07. Password 1 -08. Initialize Press the READ / Enter button and accelerate / decelerate buttons to enter the parameter access level (13-06) display screen.

Example2 continued, steps3–11 — PDF page 144

Source row Step LCD display text (example only) Procedure
1 3 Edit 13-06 Access Level --------------------------------------- 1 User Level (0~2) < 2 > Press the READ / ENTER button to enter the data setting/read screen. (the selected setting value will flash)
2 4 ─ADV─ G01-02 Access Level 1 User Level (0-2) < 2 > ‧Use the accelerate / decelerate button to change the setting value to 1 (13- 06=1, user level), and press the READ / ENTER button to save the setting value (03-00), and the number will stop flashing and be displayed. (The number selected will start flashing again a few seconds after being set). ‧ User level (13-06=1) can be set using one or multiple parameter settings from 00-41 to 00-56. If user parameter was not set, 13-06 does not need to be set for user level (setting value=1).
3 5 PARA 13 -06. Access Level Press the DSP / FUN button once to return to the display sub-menu of the operator.
4 6 Group 00.User Function Press the DSP / FUN button once to return to the group menu. The up button needs to be pressed at this time to select the 00 User Function group.
5 7 Monitor Freq Ref 12-16=000.00Hz --------------------------------------- 12-17=000.00Hz 12-18=0000.0A Press the DSP / FUN button one time to return to the home page; to exit user parameters, first press RESET and then press the DSP / FUN hotkey to call group 13.
6 8 Group 00.User Function00 User 13.Driver Status Group 13 will appear at this time and the parameter 13-06 can be changed to exit parameters, or enter group 00 to edit user parameters.
7 9 PARA 00 -41. S1 Function Sel When in 00 user parameter, press the READ / Enter buttons and accelerate /decelerate buttons to select user parameter 0 (00-41) display.
8 10 Edit 00-41 S1 Function Sel 00 2-Wire (FWD-RUN) (00~57) < 00 > < 03-00 > Press the READ / ENTER button to enter the data setting/read screen. (the selected setting value will flash). In this example, 03-00 (multi-function terminal S1 function setting) has been defined as user parameter 00-41, and the original parameter group position is displayed at the bottom-right.
9 11 Edit 00-41 S1 Function Sel 06 FJOG (00~57) < 00 > < 03-00 > Use the accelerate / decelerate buttons to change the setting value to 6, and use the READ / ENTER button to save the setting value. When the selected setting value no longer flashes, the setting value will also be saved to 00-41 and 03-00.

Manual — User parameter procedure and menu flow — page 145

Manual reference: physical PDF page 145. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Source LCD example is clipped; visible labels retained but complete LCD content unresolved. No missing digits or labels inferred.

User parameter operation mode structure

A. Define any other parameter (except for 00-00 and 00-41~00-56 and the parameters from group 0 to group 22) as user parameters

User-parameter operation-mode flowchart. Screen columns: Home screen, Main menu, Sub menu, Data setting/read screen. Home example: Monitor; Freq Ref; 12-16=000.00Hz; 12-17=000.00Hz; 12-18=0000.0A. Main Group: 00 Basic Func., 01 V/F Pattern, 02 Motor Parameter. PARA 00 submenus: -00 Control Method, -01 Motor Direction, -02 RUN Source; -41 User P0, -42 User P1, -43 User P2; -54 User P13, -55 User P14, -56 User P15. Edit screen 00-41: User P0; 01-00 V/F Pattern. Sel (01-00–24-06). Buttons read DSP/FUN and READ/ENTER; up/down triangle buttons and circled continuation markers ① and ② are shown. Dashes are display separators. These are illustrative screen labels; original arrows and geometry remain authoritative.

Exact source table. Application preset values are not universal defaults; screen numbers are historical examples, not current device settings. Empty source cells retained without inference.

Example2 continued, step12 — PDF page 145

Source row Step LCD display text (example only) Procedure
1 12 Monitor Freq Ref 12-16=000.00Hz --------------------------------- ------ 12-17=000.00Hz Press the DSP / FUN button once to return to the display home page of the operator. (If the DSP / FUN button was not pressed within one minute, the display screen will return to the monitor mode screen in the left figure automatically. The automatic return time can be set with 16-06).

Manual — User level flow and V/F definitions — page 146

Manual reference: physical PDF page 146. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

User-level access flowchart. Screen columns: Home screen, Main menu, Sub menu, Data setting/read screen. Home example: Monitor; Freq Ref; 12-16=000.00Hz; 12-17=000.00Hz; 12-18=0000.0A. Main Group: 13 Driver Status, 14 PLC Setting, 15 PLC Monitor. PARA 13: -00 KVA Sel, -01 S/W Version 1, -02 Elapsed Time1; -06 Access Level, -07 Password 1, -08 Initialize. Edit 13-06: Access Level, 1 User Level, (0~2), <2>. Additional Group screens show 00 User Function and 13 Driver Status; PARA 13 -06 Access Level; PARA 00 -41 S1 Function Sel. Buttons: DSP/FUN, READ/ENTER, left-arrow RESET plus DSP/FUN; up/down triangles and circled continuation markers ① and ②. Dashes are display separators. These are illustrative screen labels; original arrows and geometry remain authoritative.

‧ When operating under SV mode, SV high-speed mode 2 can be used when acceleration and deceleration is required urgently.

(1) When 00-63=0: The upper and lower limits of the frequency, parameters 00-12 and 00-13, will be displayed with percentages. (2) When 00-63=1: The upper and lower limits of the frequency, parameters 00-12 and 00-13, will be displayed with frequency Hz.

01-V/F control function group

When using V/F mode without PG or VF mode with PG and SLV2 mode, the V/F characteristic of the inverter output can be set with 01-00. . When the V/f curve is used, the inverter input voltage needs to be set with 01-14. . There are three ways to set the V/f curve:

(1) 01-00 = 0 to E: Select from the 15 preset types (0 to E). (2) 01-00 =0F, use 01-02~01-09 and 01-12~01-13 to define the V/f curve for users with voltage limitations. (3) 01-00 = FF: Use 01-02~01-09 and 01-12~01-13 to define the V/f curve for users without voltage limitations. References are as shown in the figure below.

Source parameter definition; development or special-project restrictions elsewhere in the manual remain applicable.

Detailed parameter definition — PDF page 146

Source row Parameter code Name Scope/options as printed
1 00- 57 SV high-speed mode [0]SV high-speed mode 1 [1]SV high-speed mode 2

Detailed parameter definition — PDF page 146

Source row Parameter code Name Scope/options as printed
1 00- 63 Frequency upper and lower limit setting selection [0] Percentage [1] Frequency

Detailed parameter definition — PDF page 146

Source row Parameter code Name Scope/options as printed
1 01- 00 V/F curve selection 【0~FF】

Manual — User-defined V/F voltage limit and conditions — page 147

Manual reference: physical PDF page 147. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.14 voltage-limit graph labels: Output voltage and Output frequency. Vertical labels are 5V, 40V and 250V; origin label 0. The intermediate horizontal position is labelled Parameters 01-02 divided by 40; the right position is 01-02 (Output frequency during maximum voltage). The caption inside the graph states Output voltage limit curve (The voltage limit for the 440V class is 2 times the value). This transcribes printed labels and fraction placement; no unprinted slope, interpolation or operating voltage is inferred.

Figure 4.3. 14 References for user-defined V/f curves . The default factory setting of 01-00 is F, and when 01-00 is set to 1, the contents of 01-02~01-09 and 01-12~01-13 are the same. . When one of the 15 preset types is selected, the setting values of 01-02 to 01-13 are changed automatically. There are three types of values for 01-02~01-09 and 01-12~01-13 here; the value depends on the capacity of the inverter. . V/F characteristics of reference tables 4.3.5~4.3.20. * This parameter is not affected by the initialization parameter (13-08).

Manual — Table 4.3. 5 0.5 - 2HP V/f curve (200V) — page 148

Manual reference: physical PDF page 148. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 5 0.5 - 2HP V/f curve (200V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 5 0.5 - 2HP V/f curve (200V) — PDF page 148

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 200, 50, 35, 7.2, 6.5; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 200, 50, 35, 7.2, 6.5; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 200, 50, 35, 7.2, 6.5; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 200, 50, 35, 7.2, 6.5; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 200, 14.6, 14, 7.4, 7.3; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 200, 14.6, 14, 7.4, 7.3; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 200, 14.6, 14, 7.4, 7.3; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 200, 14.6, 14, 7.4, 7.3; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 200, 13.5, 7.2; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 6 3 ~ 10HP V/f curve (200V) — page 149

Manual reference: physical PDF page 149. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 6 3 ~ 10HP V/f curve (200V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 6 3 ~ 10HP V/f curve (200V) — PDF page 149

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 200, 50, 35, 6.8, 6; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 200, 50, 35, 6.8, 6; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 200, 50, 35, 6.8, 6; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 200, 50, 35, 6.8, 6; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 200, 13.8, 13.3, 6.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 200, 13.8, 13.3, 6.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 200, 13.8, 13.3, 6.9; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 200, 13.8, 13.3, 6.9; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 200, 12.7, 6.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 7 0.5 ~ 2HP V/f curve (220V) — page 150

Manual reference: physical PDF page 150. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 7 0.5 ~ 2HP V/f curve (220V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Adjacent source context — repeated to preserve continuation:

Table 4.3. 7 0.5 ~ 2HP V/f curve (220V) — PDF page 150

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 220, 55, 38.5, 7.9, 7.1; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 220, 55, 38.5, 7.9, 7.1; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 220, 55, 38.5, 7.9, 7.1; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 220, 55, 38.5, 7.9, 7.1; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 220, 16.1, 15.4, 8.1, 8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 220, 16.1, 15.4, 8.1, 8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 220, 16.1, 15.4, 8.1, 8; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 220, 16.1, 15.4, 8.1, 8; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 220, 14.8, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 8 3 ~ 10HP V/f curve (220V) — page 151

Manual reference: physical PDF page 151. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 8 3 ~ 10HP V/f curve (220V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Adjacent source context — repeated to preserve continuation:

Table 4.3. 8 3 ~ 10HP V/f curve (220V) — PDF page 151

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 220, 55, 38.5, 7.5, 6.6; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 220, 55, 38.5, 7.5, 6.6; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 220, 55, 38.5, 7.5, 6.6; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 220, 55, 38.5, 7.5, 6.6; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 220, 15.2, 14.6, 7.7, 7.6; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 220, 15.2, 14.6, 7.7, 7.6; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 220, 15.2, 14.6, 7.7, 7.6; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 220, 15.2, 14.6, 7.7, 7.6; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 220, 14, 7.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 9 0.5 ~ 2HP V/f curve (230V) — page 152

Manual reference: physical PDF page 152. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 9 0.5 ~ 2HP V/f curve (230V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 9 0.5 ~ 2HP V/f curve (230V) — PDF page 152

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 230, 57.5, 40.3, 8.3, 7.4; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 230, 57.5, 40.3, 8.3, 7.4; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 230, 57.5, 40.3, 8.3, 7.4; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 230, 57.5, 40.3, 8.3, 7.4; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 230, 16.8, 16.1, 8.5, 8.4; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 230, 16.8, 16.1, 8.5, 8.4; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 230, 16.8, 16.1, 8.5, 8.4; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 230, 16.8, 16.1, 8.5, 8.4; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 230, 15.5, 8.3; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 10 3 - 10HP V/f curve (230V) — page 153

Manual reference: physical PDF page 153. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 10 3 - 10HP V/f curve (230V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 10 3 - 10HP V/f curve (230V) — PDF page 153

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 230, 57.5, 40.3, 7.8, 6.9; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 230, 57.5, 40.3, 7.8, 6.9; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 230, 57.5, 40.3, 7.8, 6.9; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 230, 57.5, 40.3, 7.8, 6.9; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 230, 15.9, 15.3, 8.1, 7.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 230, 15.9, 15.3, 8.1, 7.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 230, 15.9, 15.3, 8.7, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 230, 15.9, 15.3, 8.7, 7.9; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 230, 14.6, 7.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 11 1 - 2HP V/f curve (380V) — page 154

Manual reference: physical PDF page 154. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 11 1 - 2HP V/f curve (380V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 11 1 - 2HP V/f curve (380V) — PDF page 154

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 380, 95, 66.5, 13.6, 12.3; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 380, 95, 66.5, 13.6, 12.3; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 380, 95, 66.5, 13.6, 12.3; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 380, 95, 66.5, 13.6, 12.3; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 380, 27.8, 26.6, 14, 13.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 380, 27.8, 26.6, 14, 13.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 380, 27.8, 26.6, 14, 13.8; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 380, 27.8, 26.6, 14, 13.8; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 380, 25.6, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 12 3 - 10HP V/f curve (380V) — page 155

Manual reference: physical PDF page 155. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 12 3 - 10HP V/f curve (380V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 12 3 - 10HP V/f curve (380V) — PDF page 155

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 380, 95, 66.5, 13, 11.4; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 380, 95, 66.5, 13, 11.4; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 380, 95, 66.5, 13, 11.4; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 380, 95, 66.5, 13, 11.4; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 380, 26.3, 25.2, 13.3, 13.1; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 380, 26.3, 25.2, 13.3, 13.1; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 380, 26.3, 25.2, 13.3, 13.1; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 380, 26.3, 25.2, 13.3, 13.1; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 380, 24.2, 13; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 13 1 - 2HP V/f curve (400V) — page 156

Manual reference: physical PDF page 156. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 13 1 - 2HP V/f curve (400V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 13 1 - 2HP V/f curve (400V) — PDF page 156

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 400, 100, 70, 14.4, 12.9; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 400, 100, 70, 14.4, 12.9; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 400, 100, 70, 14.4, 12.9; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 400, 100, 70, 14.4, 12.9; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 400, 29.3, 28, 14.7, 14.5; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 400, 29.3, 28, 14.7, 14.5; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 400, 29.3, 28, 14.7, 14.5; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 400, 29.3, 28, 14.7, 14.5; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 400, 26.9, 14.4; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 14 3 - 10HP V/f curve (400V) — page 157

Manual reference: physical PDF page 157. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 14 3 - 10HP V/f curve (400V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 14 3 - 10HP V/f curve (400V) — PDF page 157

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 400, 100, 70, 13.6, 12; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 400, 100, 70, 13.6, 12; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 400, 100, 70, 13.6, 12; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 400, 100, 70, 13.6, 12; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 400, 27.6, 26.5, 14, 13.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 400, 27.6, 26.5, 14, 13.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 400, 27.6, 26.5, 14, 13.8; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 400, 27.6, 26.5, 14, 13.8; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 400, 25.5, 13.6; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 15 1 - 2HP V/f curve (415V) — page 158

Manual reference: physical PDF page 158. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 15 1 - 2HP V/f curve (415V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50 Hz / Cubic deceleration curve

5 / 50 Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 15 1 - 2HP V/f curve (415V) — PDF page 158

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50 Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 415, 103.8, 72.6, 14.9, 13.4; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50 Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 415, 103.8, 72.6, 14.9, 13.4; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 415, 103.8, 72.6, 14.9, 13.4; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 415, 103.8, 72.6, 14.9, 13.4; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 415, 30.4, 29.1, 15.3, 15.1; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 415, 30.4, 29.1, 15.3, 15.1; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 415, 30.4, 29.1, 15.3, 15.1; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 415, 30.4, 29.1, 15.3, 15.1; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 415, 27.9, 14.9; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 16 3 - 10HP V/f curve (415V) — page 159

Manual reference: physical PDF page 159. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 16 3 - 10HP V/f curve (415V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 16 3 - 10HP V/f curve (415V) — PDF page 159

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 415, 103.8, 72.6, 14.1, 12.5; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 415, 103.8, 72.6, 14.1, 12.5; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 415, 103.8, 72.6, 14.1, 12.5; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 415, 103.8, 72.6, 14.1, 12.5; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 415, 28.7, 27.5, 14.5, 14.3; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 415, 28.7, 27.5, 14.5, 14.3; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 415, 28.7, 27.5, 14.5, 14.3; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 415, 28.7, 27.5, 14.5, 14.3; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 415, 26.4, 14.1; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 17 1 - 2HP V/f curve (440V) — page 160

Manual reference: physical PDF page 160. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 17 1 - 2HP V/f curve (440V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 17 1 - 2HP V/f curve (440V) — PDF page 160

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 440, 110, 77, 15.8, 14.2; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 440, 110, 77, 15.8, 14.2; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 440, 110, 77, 15.8, 14.2; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 440, 110, 77, 15.8, 14.2; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 440, 32.2, 30.8, 16.2, 16; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 440, 32.2, 30.8, 16.2, 16; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 440, 32.2, 30.8, 16.2, 16; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 440, 32.2, 30.8, 16.2, 16; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 440, 29.6, 15.8; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 18 3 - 10HP V/f curve (440V) — page 161

Manual reference: physical PDF page 161. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 18 3 - 10HP V/f curve (440V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 18 3 - 10HP V/f curve (440V) — PDF page 161

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 440, 110, 77, 15, 13.2; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 440, 110, 77, 15, 13.2; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 440, 110, 77, 15, 13.2; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 440, 110, 77, 15, 13.2; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 440, 30.4, 29.2, 15.4, 15.2; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 440, 30.4, 29.2, 15.4, 15.2; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 440, 30.4, 29.2, 15.4, 15.2; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 440, 30.4, 29.2, 15.4, 15.2; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 440, 28, 15; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 19 1 - 2HP V/f curve (460V) — page 162

Manual reference: physical PDF page 162. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 19 1 - 2HP V/f curve (460V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60Hz / 60 Hz Saturated

F (60Hz default factory value) / 60Hz / 60 Hz Saturated

2 / 60Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 19 1 - 2HP V/f curve (460V) — PDF page 162

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 460, 115, 80.5, 16.5, 14.8; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 460, 115, 80.5, 16.5, 14.8; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 460, 115, 80.5, 16.5, 14.8; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 460, 115, 80.5, 16.5, 14.8; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 460, 33.7, 32.2, 16.9, 16.7; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 460, 33.7, 32.2, 16.9, 16.7; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 460, 33.7, 32.2, 16.9, 16.7; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 460, 33.7, 32.2, 16.9, 16.7; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 460, 30.9, 16.5; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Table 4.3. 20 3 - 10HP V/f curve (460V) — page 163

Manual reference: physical PDF page 163. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 20 3 - 10HP V/f curve (460V)

Source V/F reference for the voltage and horsepower class printed in the title. Separate F rows preserve50Hz/60Hz default conditions. Graph labels are not interpolated coordinates or approval to use a drive/motor configuration.

0 / 50Hz

F (50Hz default factory value) / 50Hz

1 / 60 Hz / 60 Hz Saturated

F (60Hz default factory value) / 60 Hz / 60 Hz Saturated

2 / 60 Hz / 50 Hz Saturated

3 / 72Hz

4 / 50Hz / Cubic deceleration curve

5 / 50Hz / Quadratic deceleration curve

6 / 60Hz / Cubic deceleration curve

7 / 60Hz / Quadratic deceleration curve

8 / 50Hz / Low starting torque

9 / 50Hz / High starting torque

A / 60Hz / Low starting torque

B / 60Hz / High starting torque

C / 90Hz

D / 120Hz

E / 180Hz

Table 4.3. 20 3 - 10HP V/f curve (460V) — PDF page 163

Source row Type Specifications 01-00 setting V/F curve labels
1 General use 50Hz 0 Graph L1; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
2 General use 50Hz F (50Hz default factory value) Graph L1; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (0), (F). Labels only; no interpolated points or unstated operating values.
3 General use 60 Hz / 60 Hz Saturated 1 Graph L2; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
4 General use 60 Hz / 60 Hz Saturated F (60Hz default factory value) Graph L2; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
5 General use 60 Hz / 50 Hz Saturated 2 Graph L2; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.5, 3, 50, 60; curve identifiers: (2), (1), (F). Labels only; no interpolated points or unstated operating values.
6 Deceleration torque (wind and hydraulic machinery) 72Hz 3 Graph L3; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.5, 3, 60, 72; curve identifiers: (3). Labels only; no interpolated points or unstated operating values.
7 Deceleration torque (wind and hydraulic machinery) 50Hz / Cubic deceleration curve 4 Graph L4; printed vertical labels (V): 460, 115, 80.5, 15.7, 13.8; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
8 Deceleration torque (wind and hydraulic machinery) 50Hz / Quadratic deceleration curve 5 Graph L4; printed vertical labels (V): 460, 115, 80.5, 15.7, 13.8; printed horizontal labels (Hz): 0, 1.3, 25, 50; curve identifiers: (5), (4). Labels only; no interpolated points or unstated operating values.
9 Deceleration torque (wind and hydraulic machinery) 60Hz / Cubic deceleration curve 6 Graph L5; printed vertical labels (V): 460, 115, 80.5, 15.7, 13.8; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
10 Deceleration torque (wind and hydraulic machinery) 60Hz / Quadratic deceleration curve 7 Graph L5; printed vertical labels (V): 460, 115, 80.5, 15.7, 13.8; printed horizontal labels (Hz): 0, 1.5, 30, 60; curve identifiers: (7), (6). Labels only; no interpolated points or unstated operating values.
11 High starting torque 50Hz / Low starting torque 8 Graph R1; printed vertical labels (V): 460, 31.8, 30.5, 16.1, 15.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
12 High starting torque 50Hz / High starting torque 9 Graph R1; printed vertical labels (V): 460, 31.8, 30.5, 16.1, 15.9; printed horizontal labels (Hz): 0, 1.3, 2.5, 50; curve identifiers: (9), (8). Labels only; no interpolated points or unstated operating values.
13 High starting torque 60Hz / Low starting torque A Graph R2; printed vertical labels (V): 460, 31.8, 30.5, 16.1, 15.9; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
14 High starting torque 60Hz / High starting torque B Graph R2; printed vertical labels (V): 460, 31.8, 30.5, 16.1, 15.9; printed horizontal labels (Hz): 0, 1.5, 3, 60; curve identifiers: (B), (A). Labels only; no interpolated points or unstated operating values.
15 Constant horsepower torque (reducer) 90Hz C Graph R3; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.5, 3, 60, 90; curve identifiers: (C). Labels only; no interpolated points or unstated operating values.
16 Constant horsepower torque (reducer) 120Hz D Graph R4; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.5, 3, 60, 120; curve identifiers: (D). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.
17 Constant horsepower torque (reducer) 180Hz E Graph R5; printed vertical labels (V): 460, 29.3, 15.7; printed horizontal labels (Hz): 0, 1.5, 3, 60, 180; curve identifiers: (E). Horizontal axis includes a drawn break; do not infer a continuous scale. Labels only; no interpolated points or unstated operating values.

Manual — Motor1 V/F detailed parameter ranges — page 164

Manual reference: physical PDF page 164. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Detailed source parameter definitions. Shared bounds remain explicit; no missing scope invented.

Group01 V/F detailed parameter definitions — PDF page 164

Source row Code Parameter name Scope/options as printed
1 01- 02 Motor 1 maximum output frequency 【4.8~599.0】Hz
2 01- 03 Motor 1 maximum output voltage 200V:【0.1~255.0】V 400V:【0.2~510.0】V
3 01- 04 Motor 1 intermediate output frequency 2 【0.0~599.0】Hz
4 01- 05 Motor 1 intermediate output voltage 2 200V:【0.0~255.0】V 400V:【0.0~510.0】V
5 01- 06 Motor 1 intermediate output frequency 1 【0.0~599.0】Hz
6 01- 07 Motor 1 intermediate output voltage 1 200V:【0.0~255.0】V 400V:【0.0~510.0】V
7 01- 08 Motor 1 minimum output frequency 【0.0~599.0】Hz
8 01- 09 Motor 1 minimum output voltage 200V:【0.0~255.0】V 400V:【0.0~510.0】V
9 01- 12 Motor 1 base frequency 【4.8~599.0】Hz
10 01- 13 Motor 1 base output voltage 200V:【0.0~255.0】V 400V:【0.0~510.0】V

Manual — V/F curve eligibility and frequency ordering — page 165

Manual reference: physical PDF page 165. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

V/f curve setting (01-02~01-09 and 01-12~01-13) ‧ Only when 01-00 is set to “F” or “FF”, can 01-02~01-09 and 01-12~01-13 be set by users. If 01-00 was set to any value other than F or FF, the parameter cannot be changed. ‧ Please follow the frequency setting rules described below, otherwise the warning message “SE03” V/f curve error will be displayed.

Fmax (01-02) ≥ Fbase (01-12) > Fmid2 (01-04) > Fmid1 (01-06) > Fmin (01-08)

‧ If 01-04 and 01-05 (or 01-18 and 01-19) was set to 0, the program will ignore the setting values of Fmid2 and Vmid2. ‧ The maximum frequency of 01-02 motor 1 must not exceed 4 times the base frequency of 01-12 motor 1. ‧ There are no related standards for the voltage setting values of parameter 01-02 to parameter 01-09. ‧ The values of parameters 01-03, maximum output voltage of motor 1, and 01-13, basic output voltage of motor 1, will be restored to the default factory settings based on the option configured in parameter 13-08. ‧ When the control method 00-00 is changed, parameters 01-08(Fmin) and 01-09 (Vmin) will change the default factory settings of the various control methods. ‧ Refer to the user-defined V/F curve in the figure below.

Output Voltage (V); (01-03) Vmax; (01-13) Vbase; (01-05) Vmid2; (01-07) Vmid1; (01-09) Vmin; Fmin (01-08); Fmid1 (01-06); Fmid2 (01-04); Fbase (01-12); Fmax (01-02); Output Frequency (Hz).

Figure 4.3. 15 User-defined V/F curve

‧ Set the V/F curve based on the allowed load characteristics of the motor. In low-torque high-speed applications, the motor may overheat. If the motor operates for long periods of time under such condition, special attention is required for motor cooling. ‧ If parameter 01-10 was used to enable the automatic torque boost function, under low-frequency starting and operation, the motor voltage will change automatically in order to provide sufficient motor torque.

Manual — SV/SLV voltage and curve control — page 166

Manual reference: physical PDF page 166. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

SV (flux vector control) V/F curve setting . Under normal circumstances, the V/F curve does not need to be adjusted in SLV control mode. The V/F curve is adjusted by changing the maximum output frequency setting 01-02 (Fmax), the basic frequency 01-12 (Fbase), the minimum output frequency 01-08 (Fmin), the maximum output voltage 01-03 (Vmax), or the basic output voltage 01-13 (Vbase). . Since the current controller is used for SV/SLV mode, therefore, group 01 can only adjust the frequency curve under SV/SLV mode, and the voltage is already adjusted by the current controller. Regardless of whether the motor is operating in applications within the constant power range or higher than the rated frequency of the motor, the parameters 02-19 or 17-04 can be used to reduce the setting value of the no-load voltage, and restart to perform automatic parameter adjustment to achieve pre-magnetic weakening mode. The adjustment range of the no-load voltage is approximately 10~40V. After the no- load voltage is reduced, motor oscillation can be prevented. The only disadvantage of field weakening control is that it will cause the current to increase. . Under SLV mode, the basic frequency (01-12,Fbase) needs to be set to the rated frequency on the motor nameplate.

Output Voltage (V); Vmax; Vmid2; Vmid1; Vmin; Fmin (01-08); Fmid1 (01-06); Fmid2 (01-04); Fbase (01-12); Fmax (01-02).

Figure 4.3. 16 Torque increase

*The setting method of SLV2’s V/F curve is the same as VF mode

Manual — Torque compensation and input voltage — page 167

Manual reference: physical PDF page 167. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Torque compensation gain (01-10) *V/F + PG is for special projects only .V/F or V/F+PG and SLV2 mode: The inverter calculates the compensation voltage based on the motor voltage drop. . The torque compensation gain (01-10) can be modified during operation, but usually does not need to be adjusted, except in the following situations: ─ If the wiring between the inverter and motor is too long, add setting values. ─ If the motor capacity is smaller than the inverter capacity, increase the setting value. ─ If the motor vibrates, reduce the setting value. . Gradually increase the setting value of 01-10 and confirm that the current increase is not too much. . Confirm that the output current during low-speed will not exceed the rated output current of the inverter; make adjustments by referring to the torque compensation gain in Figure 4.3.17. Torque compensation mode selection (01-11) Torque compensation mode 0 is general torque compensation mode. Torque compensation mode 1 is the high-speed torque compensation mode (120~160Hz). The compensation amount will decrease with the increase of the frequency, and the compensation for 0~120Hz will be the same as torque compensation mode 0.

Output Voltage; 100%; Torque Increase (up arrow); Torque Decrease (down arrow); Base frequency.

Figure 4.3. 17 Adjust the torque compensation gain to increase output torque

The minimum unit of the inverter input voltage is 0.1V. (For example: 200V / 208V / 230V / 240V or 380V / 415V / 440V / 460V / 480V). This setting value is used to pre-define a reference value of the V/f curve (01-00 = 0 to E), and protect against incidents such as over voltage and stalls Note: The input voltage setting will be restored to the default factory setting based on the option configured in parameter 13-08. If the setting value of parameter 01-14 is lower than the actual input voltage, then the output voltage (parameter 12-19) and output power (parameter 12-21) will be displayed incorrectly.

. The setting of the torque compensation delay time uses millisecond as the unit. . It can be adjusted under the following conditions: - If the motor vibrates, increase the setting value. - If the motor responds too slowly, reduce the setting value.

Detailed source parameter definitions. Shared bounds remain explicit; no missing scope invented.

Group01 V/F detailed parameter definitions — PDF page 167

Source row Code Parameter name Scope/options as printed
1 01-10 Torque compensation gain 【0.0~2.0】
2 01-11 Torque compensation mode selection 0: Torque compensation mode 0 1: Torque compensation mode 1

Group01 V/F detailed parameter definitions — PDF page 167

Source row Code Parameter name Scope/options as printed
1 01-14 Input voltage setting 200V:【155.0~255.0】V 400V:【310.0~510.0】V

Group01 V/F detailed parameter definitions — PDF page 167

Source row Code Parameter name Scope/options as printed
1 01-15 Torque compensation time 【0~10000】ms

Manual — Motor2 V/F detailed parameter ranges — page 168

Manual reference: physical PDF page 168. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Set the motor 2 V/F curve; its setting method is the same as motor 1 The motor 2 V/F curve is the same as the motor 1 V/F curve; please refer to tables 4.3.5~4.3.20.

Detailed source parameter definitions. Shared bounds remain explicit; no missing scope invented.

Group01 V/F detailed parameter definitions — PDF page 168

Source row Code Parameter name Scope/options as printed
1 01- 16 Motor 2 maximum output frequency 【4.8~599.0】Hz
2 01- 17 Motor 2 maximum output voltage 200V:【0.1~255.0】V 400V:【0.2~510.0】V
3 01- 18 Motor 2 intermediate output frequency 2 【0.0~599.0】Hz
4 01- 19 Motor 2 intermediate output voltage 2 200V:【0.0~255.0】V 400V:【0.0~510.0】V
5 01- 20 Motor 2 intermediate output frequency 1 【0.0~599.0】Hz
6 01- 21 Motor 2 intermediate output voltage 1 200V:【0.0~255.0】V 400V:【0.0~510.0】V
7 01- 22 Motor 2 minimum output frequency [0.0~599.0] Hz
8 01-23 Motor 2 minimum output voltage 200V:【0.0~255.0】V 400V:【0.0~510.0】V
9 01- 24 Motor 2 base frequency 【4.8~599.0】Hz
10 01- 25 Motor 2 base output voltage 200V:【0.0~255.0】V 400V:【0.0~510.0】V
11 01- 26 Motor 2 V/F curve selection 【0~FF】

Manual — IM motor1 parameter definitions and tuning — page 169

Manual reference: physical PDF page 169. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

02-IM motor parameter group

The motor parameter settings are as shown below. When motor 1 is selected during motor parameter tuning, these motor parameters are set to (17-10=1) automatically, and usually do not need to be further adjusted, except for some special applications, such as constant horsepower control for spindle motors of tools. Please refer to reference group 22 for the parameter settings of permanent magnet motors (1) Set (02-07) for the number of poles for the motor. ‧ Set the number of poles for the motor as indicated on the motor nameplate. (2) Motor rated power (02-05) ‧ Set it to the power value on the motor nameplate. (3) Motor rated current (02-01) ‧ Set it to the motor nameplate full load current. ‧ If under SLV and SV control modes, to adjust the rated current of the motor, please adjust 17-02 in the automatic tuning function group and restart the automatic tuning function. (4) Motor rated voltage (02-04) ‧ Set it to the rated voltage on the motor nameplate. ‧ When setting the rated voltage of the motor, the maximum output voltage of the VF curve will be adjusted. (5) Motor 1 rated frequency (02-06) ‧ Set it to the motor nameplate frequency. (6) Motor 1 rated rotation speed (02-03) ‧ Set it to the motor nameplate rotation speed. (7) Motor no-load voltage (02-19) ‧ When parameter 17-08 or 02-19 is set, this parameter is the same as 17-08. This parameter determines the rated flux of the motor under the rated rotation speed in SLV or SV control mode. Using setting values 10~50V lower than the input voltage can ensure that the motor provides torque performances at the rated (or higher) rotation speed. ‧ Smaller no-load voltage can reduce the no-load current, reduce flux and increase the load current,

Detailed source parameter definitions. Shared bounds remain explicit; no missing scope invented.

Group02 IM motor detailed parameter definitions — PDF page 169

Source row Code Parameter name Scope/options as printed
1 02- 00 Motor 1 no-load current 【0.01~600.00】A
2 02- 01 Motor 1 rated current V/F and V/F+PG modes are 10%~200% of the inverter’s rated current, and the SLV and SV modes are 25%~200% of the inverter’s rated current.* (V/F+PG, SV and PMSV are only for special projects
3 02-03 Motor 1 rated rotation speed 【0~60000】rpm
4 02-11 Motor 1 magnetic core saturation factor 2 <1> 【1~100】%
5 02- 04 Motor 1 rated voltage 200V:【50.0~240.0】V 400V:【100.0~480.0】V
6 02-12 Motor 1 magnetic core saturation factor 3 <1> 【80~300】%
7 02- 05 Motor 1 rated power 【0.01~600.00】KW
8 02-13 Motor 1 magnetic core loss 【0.0~15.0】%
9 02-06 Motor 1 rated frequency 【4.8~599.0】Hz
10 02-15 Motor 1 line-to-line resistance <1> 【0.001~60.000】Ω
11 02-07 Motor 1 number of poles 【2~16】
12 02-16 Motor 1 rotor resistance 【0.001~60.000】Ω
13 02-09 Motor 1 excitation current <1> [15~70]% motor rated current
14 02-17 Motor 1 leakage inductance 【0.01~200.00】mH
15 02-10 Motor 1 magnetic core saturation factor 1 <1> 【1~100】%
16 02-18 Motor 1 mutual inductance 【0.1~6553.4】mH

Manual — Excitation, saturation and loss settings — page 170

Manual reference: physical PDF page 170. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

and larger no-load voltages are the opposite. (8) Motor excitation current (02-09) ‧ This data can be obtained from automatic tuning. Manual tuning needs to be performed in situations where automatic tuning without rotation is not possible. ‧ During manual tuning, start tuning from 33% and observe the no-load voltage (actual value) of 12- 67. If 12-67 is greater than the no-load voltage (setting value) of 17-08, reduce 02-09; and if 12-67 is smaller than 17-08, then increase 02-09. ‧ Adjust 02-09 motor excitation current while monitoring 12-76 actual no-load voltage because when the excitation current changes, the changes of 12-76 actual no-load voltage will also be affected. Therefore, it needs to be adjusted close to the no-load voltage 17-08 set. (9) Settings for motor magnetic core saturation 1, 2, and 3 (02-10, 02-11, 02-12). ‧ This parameter is set automatically by the automatic tuning function, and usually does not need to be adjusted. ‧ This parameter sets the motor magnetic core saturation coefficients at flux levels of 50% (02-10), 75% (02-11), and 137.5% (02-12) to reduce the effects of core saturation. ‧ The magnetic core saturation coefficient is a percentage of the motor excitation current. When the flux reaches 137.5%, the core saturation coefficient needs to be greater than 137.5%. When the flux is 50% or 75%, the magnetic core saturation coefficient needs to be less than 50% and 75% respectively.

Ks3Im; Im; Ks2Im; Ks1*Im; Flux: 50%, 75%, 100%, 137.5%.

Im: 02-09 excitation current Ks1: 02-10 motor magnetic core saturation coefficient 1 Ks2: 02-11 motor magnetic core saturation coefficient 2 Ks3: 02-12 motor magnetic core saturation coefficient 3

Figure 4.3. 18 Y-equivalent model of an induction motor

(10) Motor magnetic core loss setting (02-13) ‧ Set the motor magnetic core loss to a percentage of the motor’s rated output power.

% Wcore (02-13) = [3 × motor magnetic loss (watt) × 100%] / [Motor rated output power (watt, 02-05)]

‧ When in V/F control mode, the motor magnetic loss setting (02-13) is used to compensate for torque accuracy. (11) Motor line-to-line impedance R1 (02-15). (12) Motor no-load current (02-00). ‧ Calculate this setting value according to the motor’s rated frequency (17-05) and the motor’s rated current (17-03). ‧ In V/F control mode, when the output current is greater than the motor’s no-load current, the slip compensation is enabled. ‧ 02-01 must be greater than 02-00, otherwise the warning message “SE01” setting range error will appear. ‧ Refer to Figure 4.3.19 Y-equivalent model motor inductance.

R1; Llkg; Iq; Id; Lm; R2/s; s: slip.

Figure 4.3. 19 Y-equivalent model of an induction motor

Manual — Motor2 and motor1 mechanical settings; formulas — page 171

Manual reference: physical PDF page 171. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

02-34 Motor 1 slip <1>

02-37 Motor mechanical loss

Motor 2 parameter setting is the same as the control modes of motor 1 and motor 2; they are fixed at V/f mode, therefore, there are fewer parameters that need to be set (13) Motor 1 leakage inductance ratio (02-33) ‧ This data is converted and set by the manual tuning parameter function and usually does not need to be adjusted. This tuning has no field strengthening function.

ξ = LlKg / Lr

‧ The definition of leakage inductance ratio is the ratio of leakage inductance to rotor inductance; the default factory setting is 3.4%. Adjusting this leakage inductance ratio will change the motor leakage inductance parameter. ‧ When the leakage inductance ratio is adjusted too large or too small, it will cause the motor to vibrate, have strange noises, and the motor is unable to rotate. The typical adjustment range is 3.0% to 5.0%, with 4.0% being a universal value that allows motors to operate properly on their own. But with the difference in motor structures, the leakage inductance ratio size can be adjusted accordingly. (14) Motor 1 slip (02-34)

‧ This data is converted and set by the manual tuning parameter function and usually does not need to be adjusted. This tuning has no field strengthening function. ‧ The default factory setting of the motor slip is 1Hz. The motor slip can be roughly calculated first from the motor nameplate; Using 60Hz, 4-pole motor for example, the synchronous rotation speed is

N = (120 × Frequence) / Pole = (120 × 60) / 4 = 1800 rpm

And the rated rotation speed labeled on the motor nameplate is 1700 rpm, therefore, the slip is

Slip = (1800 − 1700) / 60 = 1.67 Hz.

‧ Adjusting the motor slip will change the rotor resistance parameter, and the slip size can be adjusted according to the different motor characteristics. (15) Motor mechanical loss (02-37)

‧ The adjustment range of mechanical loss is 0.0~10.0%; this parameter is only effective under speed mode and the speed command must be zero. ‧ If the speed command is equal to zero but the shaft drifts slowly and cannot come to a complete stop, the 02-37 mechanical loss parameter can be adjusted upwards until the shaft comes to a complete stop. <1>After executing the automatic tuning function, the parameter marked in group 02 will be updated to an automatic tuning value. Please refer to the description of group 17’s automatic tuning function for details on parameter changes.

Detailed source parameter definitions. Shared bounds remain explicit; no missing scope invented.

Group02 IM motor detailed parameter definitions — PDF page 171

Source row Code Parameter name Scope/options as printed
1 02- 20 Motor 2 no-load current 【0.01~600.00】A
2 02-26 Motor 2 number of poles 【2~16】
3 02- 21 Motor 2 rated current 25%~200% inverter rated current.
4 02-32 Motor 2 line-to-line resistance 【0.001~60.000】Ω
5 02-22 Motor 2 rated rotation speed 【0~60000】rpm
6 02-33 Motor 1 leakage inductance ratio <1> 【0.1~15.0】%
7 02- 23 Motor 2 rated voltage 200V:【50.0~240.0】V 400V:【100.0~480.0】V
8 02-34 Motor 1 slip <1> 【0.1~20.0】Hz
9 02- 24 Motor 2 rated power 【0.01~600.00】KW
10 02-37 Motor mechanical loss [0.0~10.0]%
11 02-25 Motor 2 rated frequency 【4.8~599.0】Hz

Manual — Digital input terminal settings and shared options — page 172

Manual reference: physical PDF page 172. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

03-external terminal digital input/output function group

Refer to Figure 4.3.20 below multi-function parameter input and related parameters.

Related Parameters

S1 03-00

S2 03-01

S3 03-02

S4 03-03

S5 03-04

S6 03-05

S7 03-06

24VG

Figure 4.3. 20 Multi-function digital input and related parameters

03-00 to03-06 share the following option list. S7 explicitly unavailable for Frame1.

Options0–70 apply to preceding03-00 to03-06 cards subject to control-mode table and special-project restrictions.

Digital input terminal parameter definitions — PDF page 172

Source row Parameter code Terminal and function name
1 03- 00 Multi-function terminal S1 function setting
2 03- 01 Multi-function terminal S2 function setting
3 03- 02 Multi-function terminal S3 function setting
4 03- 03 Multi-function terminal S4 function setting
5 03- 04 Multi-function terminal S5 function setting
6 03-05 Multi-function terminal S6 function setting
7 03-06 Multi-function terminal S7 function setting (S7 not available for Frame1)

Shared digital input option list — PDF page 172

Source row Setting and option as printed
1 [0]: Two-wire forward /stop
2 [1]: Two-wire reverse/stop
3 [2]: Multi-speed/location setting command 1
4 [3]: Multi-speed/location setting command 2
5 [4]: Multi-speed/location setting command 3
6 [5]: Multi-speed/location setting command 4
7 [6]: Jog forward command
8 [7]: Jog reverse command
9 [8]: UP increase frequency command
10 [9]: DOWN decrease frequency command
11 [10]: Acceleration/deceleration setting command 1
12 [11]: Acceleration/deceleration prohibited
13 [12]: Primary/secondary operation switching function
14 [13]: Primary/secondary frequency switching function
15 [14]: Emergency stop (decelerate to zero and stop)
16 [15]: Cut-off stop (freely operate and stop)
17 [16]: PID function prohibited
18 [17]: Fault reset (RESET)
19 [18]: Reserved
20 [19]: Speed search 1 (from maximum frequency)
21 [20]: Manual energy-saving function
22 [21]: PID integral reset
23 [22]: Reserved
24 [23]: Reserved
25 [24]: PLC input
26 [25]: External fault
27 [26]: Three-wire forward /reverse
28 [27]: Local/remote selection
29 [28]: Remote mode selection
30 [29]: Jog frequency selection
31 [30]: Acceleration/deceleration time selection 2
32 [31]: Inverter overheat early warning
33 [32]: Synchronization command
34 [33]: DC brake
35 [34]: Speed search 2 (from frequency command)
36 [35]: Timer function input
37 [36]: PID soft start invalid
38 [37]: Frequency skipping operation
39 [38]: Frequency skipping upper offset
40 [39]: Frequency skipping lower offset
41 [40]: Motor 1/motor 2 switching
42 [41]: PID sleep
43 [42]: PG invalid
44 [43]: PG integral reset
45 [44]: Speed/torque mode switching
46 [45]: Negative torque command
47 [46]: Zero-speed servo
48 [47]: Fire mode (Forced operation mode)
49 [48]: KEB acceleration
50 [49]: Allow parameter writing
51 [50]: Direct operation protection after power is supplied (USP)
52 [51]: Multi-speed and multi- point positioning command switching
53 [52]: Position command enable
54 [53]: Two-wire self-holding (stop command)
55 [54]: Reserved
56 [55]: RTC time enable
57 [56]: RTC offset enable
58 [57]: Reserved
59 [58]: Safety function
60 [59]: Reserved
61 [60]: Reserved
62 [61]: Reserved
63 [62]: EPS input
64 [63]: Switch to second set of pressure range error
65 [64]: Reserved
66 [65]: Short-circuit brake command
67 [66]: PID function prohibited 2
68 [67]: Handwheel mode switching
69 [68]: External fault 2
70 [69]: External overload
71 [70]: Jog frequency operation

Manual — Digital input control-mode effectiveness options0–31 — page 173

Manual reference: physical PDF page 173. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3. 21 Multi-function digital input setting ( 03-00 to 03-06 ) (“O”: Effective, “X”: ineffective)

O:Effective; X:ineffective. Dash retained literally. V/F+PG, SV and PMSV only for special projects. Separate source function descriptions preserved.

Table4.3.21 digital input settings and control-mode applicability — PDF page 173

Source row Setting Function name LCD display Description V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 0 2-wire type (clockwise operation) 2-Wire (FWD-RUN) 2-wire type (ON: Forward operation command). O O O O O O O
2 1 2-wire type (Reverse rotation operation) 2-Wire (REV-RUN) 2-wire type (ON: Reverse direction operation command). O O O O O O O
3 2 Multi-speed/position setting instructions 1 Muti-Spd/Pos Ref 1 Multi-speed/location command selection 1. O O O O O O O
4 3 Multi-speed/position setting instructions 2 Muti-Spd/Pos Ref 2 Multi-speed/location command selection 2. O O O O O O O
5 4 Multi-speed/position setting instructions 3 Muti-Spd/Pos Ref 3 Multi-speed/location command selection 3. O O O O O O O
6 5 Multi-speed/position setting instructions 4 Muti-Spd/Pos Ref 4 Multi-speed/location command selection 4. O O O O O O O
7 6 FJOG command FJOG ON: Jog mode forward operation (00-18). O O O O O O O
8 7 RJOG command RJOG ON: Jog mode reverse operation (00-18). O O O O O O O
9 8 UP command UP command ON: Output frequency increase command (can only be used with the DOWN command). O O O O O O O
10 9 DOWN command DOWN command ON: Output frequency decrease command (can only be used with the UP command). O O O O O O O
11 10 Acceleration/deceleration time selection 1 Acc/Decel Time Selection 1 Acceleration/deceleration time selection command 1 O O O O O O O
12 11 Acceleration/deceleration prohibited ACC/DEC Inhibit ON: Acceleration/deceleration prohibited O O O O O O O
13 12 Primary/secondary operation switching function Run Change Sel The source of the operate command is from the secondary frequency command parameter setting (00 - 03) O O O O O O O
14 13 Primary/secondary frequency switching function Freq Change Sel The source of the frequency command is from the secondary frequency command parameter setting (00 - 06) O O O O O O O
15 14 Emergency stop E-Stop ON: Emergency stop input O O O O O O O
16 15 External base cut-off command Ext. BB ON: Inverter base cut-off O O O O O O O
17 16 PID control off PID Disable ON: PID control off O O O O O O O
18 17 Failure reset Fault Reset Failure reset O O O O O O O
19 18 Reserved Reserved Reserved - - - - - - -
20 19 Speed search command 1 Speed Search 1 ON: Search speed from maximum output frequency O O O O O X O
21 20 Manual energy-saving command Energy saving ON: Set the manual energy-saving control with 11-12 and 11-18 O O X X X X X
22 21 PID integral reset PID I-Reset ON: PID control integral reset O O O O O O O
23 22 Reserved Reserved Reserved - - - - - - -
24 23 Reserved Reserved Reserved - - - - - - -
25 24 PLC input PLC Input ON: Digital PLC input O O O O O O O
26 25 External fault Ext. Fault ON: External fault warning O O O O O O O
27 26 3-wire control (Forward /reverse command) 3-Wire (FWD/REV) 3-wire (forward /reverse command). ON is reverse and OFF is forward. When the parameter is set to 26, terminals S1 and S2 will become the operate command and stop command respectively, and the original function will be disabled. O O O O O O O
28 27 Local/Remote control selection Local/Remote ON: Local mode (through the digital operator) OFF: The frequency command and operation command are determined through the parameter (00-02 and 00-05) settings. O O O O O O O
29 28 Remote mode operation selection Remote Mode Sel ON: RS-485 communication OFF: Control circuit terminal O O O O O O O
30 29 Jog frequency selection JOG Freq sel ON: Select jog frequency command O O O O O O O
31 30 Acceleration/deceleration time selection 2 Acc/Decel Time Selection 2 Acceleration/deceleration time selection command 2 O O O O O O O
32 31 Inverter overheat alarm (OH2) Overheat Alarm ON: Inverter overheat (OH2) alarm input (OH2 will be displayed) O O O O O O O

Manual — Digital input control-mode effectiveness options32–66 — page 174

Manual reference: physical PDF page 174. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

O:Effective; X:ineffective. Dash retained literally. V/F+PG, SV and PMSV only for special projects. Separate source function descriptions preserved.

Table4.3.21 digital input settings and control-mode applicability — PDF page 174

Source row Setting Function name LCD display Description V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 32 Synchronization command Sync Command ON: Speed synchronization enabled. OFF: Speed synchronization disabled (other frequency command enabled). O O O O O O O
2 33 DC brake command DC Brake Command ON: Execute DC brake O O O O X X O
3 34 Speed search command 2 Speed Search 2 ON: Search speed from set frequency O O O O X O O
4 35 Timer function input Timer Input .Set the timer function in 03-33 and 03-34 .Set the timer function output in 03-11 and 03-12 O O O O O O O
5 36 PID soft start disabled PID SFS Disable ON: PID soft start disabled O O O O O O O
6 37 Frequency skipping operation Traverse Run ON: Frequency skipping operation O O X X X X O
7 38 Frequency skipping upper offset Upper Dev Run ON: Upper offset frequency skipping O O X X X X O
8 39 Frequency skipping lower offset Lower Dev Run ON: Lower offset frequency skipping O O X X X X O
9 40 Motor 1/motor 2 switching Motor 2 Switch ON: Start motor 2 O O O O O O O
10 41 PID sleep PID Sleep ON: PID sleep O O O O O O O
11 42 Speed command without PG PG Invaid ON: Speed control without PG X O X X X X X
12 43 Speed control integral reset I-Time Reset ON: Integral reset with PG speed control X O X O O X X
13 44 Speed / torque control mode change Speed/Torque Control change ON: Torque control mode X X X O O X X
14 45 Reverse torque command Reverse Tref ON: Reverse external torque command X X X O O X X
15 46 Zero servo command Zero-Servo ON: Zero servo operation X X X O O X X
16 47 Fire mode (Forced operation mode) Fire Mode ON: Inverter will operate with the maximum frequency of 01-02 motor 1 (when there are hardware failures such as C, SC, CUV, FUL and STO, the FIRE MODE function will stop.) O O O O O O O
17 48 KEB acceleration command KEB Accel. ON: KEB acceleration start O O X X X X O
18 49 Parameter writing start Write Enabled ON: All parameters are writable OFF: Except for the reference frequency (00-05), all parameters are write- protected O O O O O O O
19 50 Direct operation protection after power is supplied (USP) USP ON: After power is inputted, the inverter will ignore the operation commands OFF: After power is inputted, the inverter will return to the operation status before the power outage O O O O O O O
20 51 Multi-speed and multi- point positioning command switching Multi Pos. Switch ON: Multi-point positioning position command OFF: Multi-speed frequency command X X X O O X X
21 52 Position command enable Multi Pos. Enable ON: Position command effective OFF: Position command ineffective X X X O O X X
22 53 2-wire self-holding (stop command) 2-Wire (STOP) 2-wire self-holding mode (ON: Stop command). O O O O O O O
23 54 Reserved Reserved Reserved - - - - - - -
24 55 RTC time enabled RTC Timer Switch ON: RTC timer function enabled O O O O O O O
25 56 RTC offset enabled Offset Time Switch ON: RTC offset enabled O O O O O O O
26 57 Reserved Reserved Reserved - - - - - - -
27 58 Safety function Safety Function ON: Stops according to the 08-30 setting O O O O O O O
28 59 Reserved Reserved Reserved - - - - - - -
29 60 Reserved Reserved Reserved - - - - - - -
30 61 Reserved Reserved Reserved - - - - - - -
31 62 EPS input EPS Input ON: EPS terminal input X X X O O X X
32 63 Switch to second set of pressure range error Switch Const.P. 2 ON: Use second set (23-34) for the PUMP error range OFF: Use first set (23-09) for the PUMP error range O O O O O O O
33 64 Reserved Reserved Reserved - - - - - - -
34 65 Short-circuit brake command SC Brk ON: Execute short-circuit brake X X X X X O X
35 66 PID function prohibited 2 PID Disable 2 ON: PID control disabled, the previous frequency integral will be remembered. O O O O O O O

Manual — Digital input options67–70 and multi-speed selection table — page 175

Manual reference: physical PDF page 175. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1). 2-wire forward operation (setting=00). (2). 2-wire reverse operation (setting=01). . Refer to Figure 4.3.1 2-wire operation mode. (3). Multi-speed/position command 1 (setting=02). (4). Multi-speed/position command 2 (setting=03). (5). Multi-speed/position command 3 (setting=04). (6). Multi-speed/position command 4 (setting=05). (7). Jog frequency command (setting=29). Switch frequency reference via the multi-function digital input. If under SV or PMSV mode (00-00=3,4), and 03-00~07 is set to 51, the multi-position command is set with the multi-speed command. Refer to the 21-09~21-41 parameter descriptions. Table 4.3.22 below represents the corresponding combinations of multi-speed.

Table 4.3. 22 Multi-speed operation combinations

0: OFF, 1: ON, ─: Simply ignore 1. The priority of the jog frequency terminal is higher than multi-speed frequencies 1 to 4. 2. When parameter 00-05=0 (frequency reference input = digital operator), the multi-speed frequency command 1 is set by 05-01 (frequency reference 0). When parameter 00-05=1 (frequency reference input = control circuit terminal), the multi-speed frequency command 1 receives input from the analog command terminal (AI1 or AI2). *3. The default factory setting of the analog input (AI2) is the auxiliary frequency, only when 04-05≠0 is set can it be the segment one speed of the multi-speed. However, when PID control 10-03=XXX1B, even if the PID function prohibit (multi-function digital input setting=16) is enabled, you cannot switch to the auxiliary frequency. Wiring example Figures 4.3.21 and 4.3.22 below represents the operation example of segment 9 speed.

O:Effective; X:ineffective. Dash retained literally. V/F+PG, SV and PMSV only for special projects. Separate source function descriptions preserved.

Digital inputS1toS7;0OFF,1ON,dash simply ignore. Footnotes1,2,*3 and PID conditions retained with page prose; no switch-state inference.

Table4.3.21 digital input settings and control-mode applicability — PDF page 175

Source row Setting Function name LCD display Description V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 67 Handwheel mode switching HMPG Mode Switch ON: General mode, the frequency command is inputted via analog input AI1 OFF: Handwheel mode O X X X X X X
2 68 External fault 2 Ext. Fault 2 ON: External fault warning O O O O O O O
3 69 External overload Ext. Overload ON: External overload input O O O O O O O
4 70 Jog frequency operation JOG Direction Switch ON: Select according to jog frequency command O O O O O O O

Table4.3.22 multi-speed operation combinations — PDF page 175

Source row Speed Jog frequency reference Multi-speed frequency4 Multi-speed frequency3 Multi-speed frequency2 Multi-speed frequency1 Frequency selection
1 1 0 0 0 0 0 Segment 0 speed frequency (05-01) or primary speed frequency *2
2 2 0 0 0 0 1 (04-05 = 0): Determined by the auxiliary speed frequency set or (04-05≠0): Determined by the segment 1 speed frequency (05-02) *3
3 3 0 0 0 1 0 Segment 2 speed frequency (05-03)
4 4 0 0 0 1 1 Segment 3 speed frequency (05-04)
5 5 0 0 1 0 0 Segment 4 speed frequency (05-05)
6 6 0 0 1 0 1 Segment 5 speed frequency (05-06)
7 7 0 0 1 1 0 Segment 6 speed frequency (05-07)
8 8 0 0 1 1 1 Segment 7 speed frequency (05-08)
9 9 0 1 0 0 0 Segment 8 speed frequency (05-09)
10 10 0 1 0 0 1 Segment 9 speed frequency (05-10)
11 11 0 1 0 1 0 Segment 10 speed frequency (05-11)
12 12 0 1 0 1 1 Segment 11 speed frequency (05-12)
13 13 0 1 1 0 0 Segment 12 speed frequency (05-13)
14 14 0 1 1 0 1 Segment 13 speed frequency (05-14)
15 15 0 1 1 1 0 Segment 14 speed frequency (05-15)
16 16 0 1 1 1 1 Segment 15 speed frequency (05-16)
17 17 1*1 ─ ─ ─ ─ Jog frequency command (00-18)

Manual — Terminal and nine-speed timing examples — page 176

Manual reference: physical PDF page 176. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

S1 Forward RUN / STOP ( 03 - 00 = 0 )

S2 Reverse RUN / STOP ( 03 - 01 = 1 )

S3 External Fault ( 03 - 02= 25)

S4 JOG Frequency Ref ( 03 - 03 = 29)

S5 Multi - step Speed Ref 1 ( 03 - 04 = 2 )

S6 Multi - step Speed Ref 2 ( 03 - 05 = 3)

S7 Multi - step Speed Ref 3 ( 03 - 06 = 4)

24VG

Figure 4.3. 21Control terminal wiring example

Frequency Reference

Speed1: (05-01), 1 master speed ref; Speed2: (05-02), 2 aux. speed ref; Speed3: (05-03); Speed4: (05-04); Speed5: (05-05); Speed6: (05-06); Speed7: (05-07); Speed8: (05-08); Speed9: (00-18). Only printed label associations; waveform geometry is retained in the original.

speed speed speed speed speed speed speed speed speed 1 2 3 4 5 6 7 8 9

Terminal; Forward RUN (S1).

t

Figure 4.3. 22 Segment 9 speed timing diagram

Blank means no numeral printed, never inferred OFF. Diagrams are illustrative and no waveform timing geometry is reconstructed.

Figure4.3.22 explicit printed state numerals — PDF page 176

Source row Source row label Speed1 printed state Speed2 printed state Speed3 printed state Speed4 printed state Speed5 printed state Speed6 printed state Speed7 printed state Speed8 printed state Speed9 printed state
1 Multi- step (S5) speed Ref 1 0 1 0 1 0 1 0 1 0
2 Multi- step (S6) speed Ref 2 0 0 1 1 0 0 1 1 0
3 Multi- step (S7) speed Ref 3 0 0 0 0 1 1 1 1 0
4 JOG Frequency (S4) Ref ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 1

Manual — Multi-speed footnotes and jog procedure — page 177

Manual reference: physical PDF page 177. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1. When 00-05 = 1, the multi-speed frequency reference value is inputted from AI1 or AI2; when 00-05 = 0, the multi-speed frequency reference value is determined by 05-01. 2. When 04-05 = 0, the multi-speed frequency command 2 is determined by the auxiliary speed frequency set; when 04-05≠0, it is determined by the segment 1 speed frequency (05-02).

(8). Jog forward command (FJOG) command (setting=06). (9). Jog reverse command (RJOG) command (setting=07). The jog execution direction can be forward or reverse. Setting = 06: FJOG command (ON: Jog frequency forward is set by 00-18). = 07: RJOG command (ON: Jog frequency reverse is set by 00-18). The execution priority of the FJOG and RJOG commands are higher than other frequency commands. When the FJOG and RJOG command are executed more than 500 milliseconds, they will stop operating using the stopping method set by 07-09 (stop method selection). *1. When the primary frequency is AI2 (00-05=7) and 04-05 = 0, the primary frequency is determined by the auxiliary speed frequency of AI2; when 04-05≠0, it is determined by 00-18.

Manual — UP/DOWN command conditions and truth table — page 178

Manual reference: physical PDF page 178. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(10). Accelerate (UP) command (setting=08). (11). Decelerate (DOWN) command (setting=09). ‧ The inverter can increase or decrease the changes of the output frequency while the motor is operating by using the digital operator (refer to parameter 11-56) or an external multi-function digital input (terminal S1 to S7). ‧ When operations are performed using external multi-function digital input terminals, set 00-02 (operation command option) to 1 (control terminal), set 00-05 (terminal UP/DOWN) to 2, and set any one of the parameters from 03-00 to 03-06 to 08 (UP command) and 09 (DOWN command). 2 terminals need to be paired to perform the UP command and DOWN command. ‧ The output frequency will go UP or DOWN with the acceleration and deceleration time set. ‧ The error message “SE02 DI terminal Error” (SE02) will be displayed when the following situations occur: (1) Only a single UP or Down command was set. (2) The UP command and acceleration/deceleration prohibited command were enabled simultaneously. (3) The Down command and acceleration/deceleration prohibited command were enabled simultaneously. ‧ Please refer to Figure 4.3.23 and Figure 4.3.24 on the wiring and timing example of UP/DOWN.

Figure 4.3. 23 UP/DOWN wiring example

Figure 4.3. 24 Up / Down command timing example

S1 Forward Run (03-00=0); S5 Up command (03-04=08); S6 Down command (03-05=09); 24VG.

1: ON, 0: OFF

Power Supply; Forward Run; Up Command; Down Command; FUL (00-12); Output Frequency; FLL (00-13); 1; 2; Hold; Hold; time axes t. Timing and waveform geometry remain in original.

Source image cases transcribed literally.1ON/0OFF. Both0 and both1 print Hold.

UP/DOWN printed truth table — PDF page 178

Source row Source label First printed case Second printed case Third printed case Fourth printed case
1 UP Command (terminal S5) 1 0 0 1
2 DOWN Command (terminal S6) 0 1 0 1
3 Operation Status Accel (UP) Decel (DWN) Hold Hold

Manual — Frequency memory and acceleration/deceleration inhibition — page 179

Manual reference: physical PDF page 179. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ When using the UP / Down command, if operation commands are inputted, the output frequency will accelerate to the frequency reference lower limit (00-13). ‧ When using the UP / Down commands, the output frequency is limited to the frequency reference upper limit (00-12) and the frequency reference lower limit (00-13). ‧ The acceleration/deceleration time used by this function is the same as normal operations: Tacc1 /Tdec1 (00-14,15) or Tacc2 / Tdec 2 (00-16, 17). ‧ Refer to 03/40 UP / Down frequency bandwidth setting for using the other functions of UP / Down. ‧ 1. When 11-58 =1 and operation commands are inputted, the output frequency will accelerate to the previously saved frequency command. ‧ 2. When 11-58 =0 and operation commands are inputted, the output frequency will accelerate to the frequency reference lower limit (00-13). (12). Acceleration/deceleration time selection 1 (setting=10). (13). Acceleration/deceleration time selection 2 (setting=30). Refer to the chapter on page 4-42 “Multi-function digital input terminal switching acceleration/deceleration time”. (14). Acceleration/deceleration prohibited command (setting=11). Refer to Figure 4.3.25 below for the operation method of acceleration/deceleration prohibited. When the acceleration/deceleration prohibited command is input, the inverter will pause the acceleration/deceleration speed of the motor and maintain the output frequency. This function can be used with 11-58 to record the reference frequency. When 11-58=0: When ACC/DEC prohibited is ON during the motor acceleration/deceleration process, the motor will stop at the output frequency at that moment and use the output frequency as the frequency command. When ACC/DEC prohibited is changed to OFF or when a shutdown command is given, the frequency command will be restored to the frequency originally set. In addition, when the stop command and power-off is reset, the frequency command will be set to 0 Hz. Note: If ACC/DEC prohibited is ON before operating, STP0 will appear after operation starts because there is no recorded reference frequency. When 11-58=1: When ACC/DEC prohibited is ON during the motor acceleration/deceleration process, the motor will stop at the output frequency at that moment and use the output frequency as the frequency command. If switched to the stop status or cut the power of the inverter to reset at this time, when ACC/DEC prohibited is still ON, the output frequency will still be saved, and the frequency command will be set as the saved frequency.

Figure 4.3. 25 Acceleration/Deceleration prohibited instructions

(15) Primary/secondary operation switching function (setting=12) When the function terminal is on, the operation command source is determined by the secondary operation command parameter setting (00-03), and when the function terminal is set to 27 (Local/Remote control selection), the priority will be higher than the primary/secondary operation switching at this time.

Power Supply: ON, OFF, ON; Forward Run: ON, OFF, ON; Inhibit ACC/DEC Command: OFF, ON, OFF, ON; Frequency Reference; Output Frequency; Hold; Hold; time axes t.

Manual — Frequency switching, emergency stop and base-block conditions — page 180

Manual reference: physical PDF page 180. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(16) Primary/secondary frequency switching function (setting=13) When the function terminal is on, the frequency command source is determined by the secondary frequency command parameter setting (00-06), and when the function terminal is set to 27 (Local/Remote control selection), the priority will be higher than the primary/secondary operation switching at this time. When the PID function is enabled (10-03=XXX1B), this function will become invalid, and the primary frequency will switch to the PID function automatically. When failed to enable PID or when PID is off, then can the primary and secondary frequency be switched; refer to the diagram. (17) Emergency stop (setting=14). Decelerates and stops by referring to the “Emergency stop deceleration time” of parameter 00-26 and not 07-09 “Stop mode selection”. (18) External hardware base block command (setting=15). The base block command is executed using the multi-function digital input terminal ON/OFF, and prohibits inverter output. During operation: When an external base block signal is detected, “BBn BaseBlock (Sn)” will be displayed on the digital operator; if n=1-8 here, it means that the inverter output has been cut. After the base block signal is released, the motor will resume operation according to the reference signal. Before the previous base block command is inputted, perform speed search in frequency reference to confirm the current frequency and continue operating. During deceleration: When an external base block signal is entered, “BBn BaseBlock (SN)” will be displayed on the digital operator, and if n=1-8 here, it means cut the inverter output. The motor will usually stop at this time. After releasing the base block signal, the inverter will remain in stop mode. During acceleration: The operation method is the same as during operation. Refer to Figure 4.3.26 below for the timing when using the base block command.

Figure 4.3. 26 External base block operation

Run Command; External Baseblock; Output Frequency; (Speed search); Coast to stop; Coast to stop; time axes t.

Manual — Fault reset, PLC and external-failure procedures — page 181

Manual reference: physical PDF page 181. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(19). Disable PID control (setting=16). (20). Failure reset (setting=17). When the inverter detects failure, failure output starts, and the inverter will output base block. The digital operator displays the failure message. ‧ When failures occur, the following methods can be used to reset the failure: a. Set one of the multi-function digital input (03-00 to 03-06) to 17 (failure reset), and enable the failure reset signal. b. Press the RESET button on the digital operator. c Turn off the power then turn it back on. (21). External speed search command 1 (setting=19). (22). External speed search command 2 (setting=34). ‧ Refer to the “Speed search” function in 07-operation stop control function group. (23). Manual energy-saving command (setting=20). ‧ Enable: Enable the manual energy-saving function with the 11-12 and 11-18 settings. Please refer to Figure 4.3.115 for manual energy-saving operations. (24). PID integral reset (setting=21). (25). PLC input (setting=24) Must be used with the Drive Link software program, and use the PLC software program in it to edit the ladder diagram. When the signal passes through and the output is turned on, the signal will be sent to the inverter at this time to turn the inverter on. (26). External failure (setting=25). ‧ When external failures occur, the external failure input terminal is activated, the inverter will be turned off and the motor will come to a free-run stop. ‧ If the external input terminal S3 is set to (03-02=25) external failure, the “EF3 Ext. Fault (S3)” (EF3) message will be displayed. ‧ All eight input terminals (S1 to S7) can be assigned as external failure input. (27). 3-wire (forward /reverse command) (setting=26). When parameters (S3~S6) is set to 26 (forward /reverse command), terminals S1 and S2 will become the operation command and stop command respectively. Refer to Figure 4.3.2 for details.

Manual — Local/remote control and jog selection — page 182

Manual reference: physical PDF page 182. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(28). Local / Remote control selection (setting=27). ‧ Users can switch the inverter frequency reference and input operation commands in Local (controlled with the digital operator) or Remote mode (controlled with the control circuit terminal or RS485 connection). Using 00-05 (frequency reference ) and 00-02 (operation method) to determine the input source selection. ‧ Local/Remote mode can be controlled by one of the multi-function digital input terminals S3 to S7 by setting one of the parameters from 03-02 to 03-06 to 27 (Local/Remote control selection). If 03-00 to 03-01 is 3-wire control, S1 & S2 will be set to operate & stop input by force. Refer to Table 4.3.23 below.

Table 4.3. 23 Local / Remote control selection

To switch between Local/Remote modes, the inverter must be in a stopped operation status. (29). Remote mode operation selection (setting=28). ‧ Under Remote mode, the SEQ and REF indicators light up, and the frequency command can be controlled with terminals AI1 and AI2, and the operation commands are controlled through terminals S1, S2 or RS-485 communication terminals. ‧ Set one of the parameters from 03-02 to 03-06 to 28 (Remote mode operation selection), or set the control terminals (S1~S7), or set the RS-485 communication. Refer to Figure 4.3.27.

Figure 4.3. 27 Remote mode operation selection

(30). Jog frequency selection (setting=29) When ON, the 00-18 (jog frequency) frequency is used as the command.

Local Mode; LCD Digital Operator; ON; OFF; Set one of03-00 to03-06=27; Frequency Reference and Run Command. Remote Mode; RS-422/485 communications; ON; Control circuit terminals; OFF; Set one of03-00 to03-06=28. Diagram branch geometry remains in source.

Exact source settings and qualifications; no engineering inference.

Table4.3.23 Local/Remote control selection — PDF page 182

Source row Input terminal Mode Content
1 ON Local mode . Executes frequency commands and operation commands through the digital operator. . SEQ and REF indicators go off.
2 OFF Remote mode . Executes frequency commands and operation commands through the control terminals or RS-485 communication. Can use 00-05 (frequency command) and 00-02 (operation command). . SEQ and REF indicators light up.

Manual — Synchronization, DC brake and timer references — page 183

Manual reference: physical PDF page 183. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(31). Acceleration/deceleration time selection 2 (setting=30) When acceleration/deceleration time selection 2 is ON, 00-16 acceleration time 2 and 00-17 deceleration time 2 are followed. (32). Inverter overheat warning (setting=31). When the inverter detects overheat signals, the “OH2” warning message will be displayed on the digital operator, and the inverter will continue operating. After the overheat signal of the inverter is released, the digital operate will automatically return to its original display without the need to press the reset button. (33). Synchronization command (setting=32). ‧ This function switches between the frequency reference converted from the pulse serial input and other frequency references (according to the setting of 00-05). ‧ When Local/Remote mode control section (setting value 27) or Remote mode (setting value 28) is selected and their corresponding input is enabled, this function is invalid. ‧ The set/clear synchronization command can only be set while the inverter stopped operating. (34). DC brake command (setting=33). When the inverter is stopped, use this setting to execute the DC brake function through terminals that have been set. If operation command or jog command was inputted, the DC brake operation will be cleared and the motor will start operating. Only either the short-circuit brake command or the DC brake command can be used each time. If both were set simultaneously, the SE02 error (DI Terminal Error) will pop up Refer to Figure 4.3.28 DC brake timing figure below.

Figure 4.3. 28 DC brake timing figure

(35). Timer function input (setting=35). The “timer function” of reference parameters 03-37 & 03-38. (36). Disable PID SFS (setting=36). The “PID control” function of the reference parameter 10-PID function group. (37). Frequency skipping command (setting=37). (38). Frequency skipping upper offset (setting=38). (39). Frequency skipping lower offset (setting=39). Refer to the “frequency skipping operation” function of reference group 19-frequency skipping function. (40). Motor 2 switch command function (setting=40).

Run Command (or Jog command): OFF, ON; DC injection Braking Command: OFF, ON; Output Frequency; 01-08 (Fmin); The larger of01-08 or07-06; DC injection Brake (two marked intervals); time axes t.

Manual — PID, torque, fire mode and power-up protection — page 184

Manual reference: physical PDF page 184. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(41). PID sleep (setting=41) Please set the activation of 10-29 setting 2 PID sleep mode to activate from the multi-function digital input, and use by referring to the descriptions of parameters 10-17~10-20. (42). Speed control without PG (setting=42). Used to release/activate speed control. When the multi-function digital input is on, disable speed control (general V/f control). (43). Speed control integral reset (setting=43). Used to switch between proportional (P) control and proportional-integral (PI) control in speed control. When the multi-function digital input is enabled, use the proportional (P) control (integral reset). (44). Speed/torque control changing (setting=44). Used to switch between speed control and torque control of SV (sensing vector) control mode. It is torque control when enabled and speed control when disabled. For more details, please refer to parameter 21-torque control function group. (45). External torque reference polarity inversion command (Setting = 45). Enable: External torque reference command reverse. For more details, please refer to the relevant description of parameter 21-00 “Torque control selection”. (46). Zero servo command (setting=46). Enable: Zero servo operation. ‧ Please refer to Figure 4.3.124. (47). Fire mode operation (setting=47). Enable: Release hardware and software failure or warning protection. Mainly used for special applications such as exhaust fans. (48). KEB accelerated command (setting=48). Enables KEB acceleration commands (when 11-47 is not zero). Refer to the parameter descriptions of 11-47 and 11-48 (49). Parameter write protect (setting=49). Refer to the descriptions of 13-06. If one of the parameters from 03-00 to 03-06 is set to 49 (parameter write protection), when the corresponding control terminal is enabled, the parameters can be accessed from the digital operator; otherwise, it would be write protection. (50). Direct operation protection after power is supplied (setting=50). If the operation command (controlled with the terminal) has been preset and when the power is on, the inverter will start operating immediately. Direct operation protection after power is supplied (USP) function (when any one of the parameters from 03-00 to 03-06 is set to 50), it will prevent automatic starting; therefore, the inverter will not start operating because of external signals. Refer to the figure below.

Figure 4.3. 29 Example of direct operation protection after power is supplied

(51). Multi-speed and multi-point positioning command switching (setting=51). (52). Position command enabling (setting=52) Refer to the parameter descriptions of 21-09 and 21-41

Power Supply; Run command; Fault (Alarm); Fault Reset; USP; Output Frequency; time axes t.

When UPS is on after powerup, the UPS warning will clear when the RUN command turns off.

If the alarm is cleared during RUN command, the inverter output restarts automatically.

If the RUN command is already OFF at powerup, the inverter output starts normally.

Manual — RTC, safety input, EPS and pump pressure error — page 185

Manual reference: physical PDF page 185. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(53). 2-wire self-holding stop command (setting=53) Refer to the description “2-wire operations with self-hold function” of parameter 00-02 (54). RTC time enabled (setting=55) When 16-13(RTC timer function) is 2 (DI setting) and the RTC time enabled is ON, the RTC timer function can be triggered and used. (55). RTC offset enabled (setting=56) When 16-30 (RTC offset selection) is 2 (DI setting) and the RTC offset enabled is ON, it will refer to 16-31 (RTC offset time setting) and operate until this set time is completed. (56). Safety mechanism (setting=58). After the safety function is set, when the digital terminal starts operating, the inverter will stop according to the 08-30 setting. (57). EPS input (setting=62) The EPS input terminal must be used with the low-voltage starting function. (58). Switch to second set of pressure error range (setting=63) In PUMP mode (when 23-00=1), the constant pressure error range is used. This is the pressure deviation threshold used to wake up the inverter from sleep mode. When switch to second set of pressure error range is ON, it will switch from the original constant pressure error range (23-09) to constant pressure error range 2 (23-34).

Manual — Short-circuit braking and handwheel behavior — page 186

Manual reference: physical PDF page 186. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(59). Short-circuit brake command (setting=65) When stopping the inverter, use this setting to execute the short-circuit brake function through set terminals. For example, if operation command or jog command was inputted, the short-circuit brake operation will be cleared and the motor will start operating. Only either the short-circuit brake command or the DC brake command can be used each time. If both were set simultaneously, the SE02 error (DI Terminal Error) will pop up Please refer to the following figure for the short-circuit brake action timing.

Figure 4.3. 30 Example of short-circuit brake action timing

(60). PID function prohibited 2 (setting=66). When PID is DISABLED, it will switch to the 00-05 frequency source, and when DISABLE is cancelled, the previous frequency command is integrated and PID mode operation will resume. (61). Handwheel mode switching (setting=67) When 8 is selected for parameter 00-32 (application adjustment): After handwheel is applied (HMPG), the function set for this terminal can start operating, and to switch between general mode job or handwheel mode job, when used in general mode, the frequency command is determined by the analog input AI1, and when handwheel mode is used, the frequency command is determined by the pulse it inputted. ➢ Please refer to the following figure for the action of this function:

Figure 4.3. 31 Handwheel movement example

Description of handwheel movement serial number: ‧ Area 1: When inputted in the run command, DC current is injected into the motor to perform the brake action, and the current injected is determined by 07-46. Cancel the run command and

Run Command (or Jog command): OFF, ON; Short Circuit Braking Command: OFF, ON; Output Frequency; 01-08 (Fmin); The larger of01-08 or07-06; Short Circuit Brake (two marked intervals); time axes t.

Action serial number, left to right:1,2,3,2,4,1. Rotation speed of handwheel;20-44;01-08;Time;00-17. Area descriptions retained onPDF186–187; curve geometry not interpolated.

Manual — Handwheel areas and setup flowchart — page 187

Manual reference: physical PDF page 187. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

the inverter will stop the DC current injection action. ‧ Area 2: When the handwheel rotation speed is greater than the parameter (01-08) motor 1 minimum output frequency, the inverter will start outputting according to the V/f curve. If the output torque was insufficient, please set the 01-06, 01-07, 01-08 and 01-09 V/f curve parameters appropriately. ‧ Area 3: When the handwheel rotation speed exceeds the speed command limit of the parameter (20-44), the inverter output will be limited at the rotation speed set in the parameter. ‧ Area 4: When the handwheel stops rotating (stops pulse input), the speed command will follow the setting of parameter (00-17) deceleration time 2, and the motor will start decelerating. When the motor speed is less than the minimum output frequency of parameter (01-08) motor 1, DC current injection braking action will be performed. ps: After the handwheel generates pulses and inputs them to the PG card to calculate the speed command, it will be multiplied by the speed multiplier of the parameter (20-43) speed, then filtered based on the ASR delay time set in parameter (20-08). In addition, the parameter (20-28) PG rotation direction selection can be set to determine whether the rotation directions of the handwheel and motor are the same. ps: When adjusting the 01-06, 01-07, 01-08 and 01-09 V/f curve parameters, pay attention to the parameter (12-18) inverter output current to prevent the occurrence of various failures that may cause industrial safety accidents. ➢ Please refer to the following flowcharts for the parameter settings:

Handwheel application basic parameter settings

Application selection 00-32 = 8: Handwheel application

The default value will be loaded for the following parameters: 00-02: External terminal 00-05: Handwheel frequency 00-16: Acceleration time 2 00-17: Deceleration time 2 01-00: V/f curve 03-07: Run mode switch 07-09: Stop mode selection 07-18: Minimum bb time 08-00: Stall prevention function 11-62: Prevent oscillation selection 20-08: ASR delay time 20-27: Handwheel pulse count

Input motor nameplate data 02-01: Rated current 02-03: Rated rotation speed 02-04: Rated voltage 02-05: Rated power 02-06: Rated frequency 02-07: Number of motor poles

Perform motor automatic tuning 17-00 = 6: Static automatic tuning integration (option 4+2+1) 17-10 = 1: Automatic tuning start

Manual — Handwheel tuning, overload conditions and DI scanning — page 188

Manual reference: physical PDF page 188. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(62). External failure 2 (setting=68). ‧ When external failures occur, the external failure input terminal is activated, the inverter will be turned off and the motor will come to a free-run stop. ‧ If the external input terminal S3 is set to (03-02=68) external failure, the “EF3 Ext. Fault (S3)” (EF3) message will be displayed. ‧ All eight input terminals (S1 to S7) can be assigned as external failure input. (63). External overload (setting=69), the input terminal is a normally closed switch. ‧ When an external overload occurs and the external overload input terminal is off, the inverter will be turned off and the operation of the motor will decelerate and stop. ‧ If the external input terminal S5 is set to (03-04=69) external overload, the “TOL Ext. OverLoad” message ‧ will be displayed. ‧ To enable the external overload function, fire mode (08-48=1) needs to be enabled first. Only the external input terminal S5 can be assigned as external overload input. ‧ Setting the external input terminal as the external overload will set the input terminal as normally closed; therefore, before setting the external overload function, do not set operation command to come from external terminals, otherwise it will cause unnecessary harm. (64). Jog frequency operation (setting=70). ‧ When ON, operation will be performed according to the jog frequency command and according to the 00-18 setting.

‧ If 03-08 is set to 0, when the inverter’s CPU chip scans the TM2 terminal, all signals are viewed as normal execution signals. ‧ If 03-08 is set to 1, 8ms continuous input of the same signal is required in order for the inverter to view this signal as a normal execution signal, otherwise it will be viewed as noise. ‧ User can decide the scan interval according to the impact level of the noise in the usage environment. When the noise is severe, set 03- 08 to 1, but the response speed will be slower at this time.

Handwheel application tuning parameter setting

General mode

Handwheel mode

Mode selection (DI input)

00-14: Acceleration time 1 00-15: Deceleration time 1 04-02: AI1 gain value 04-03: AI1 bias voltage

07-46: DC injection current limit 20-27: PG pulse count 20-28: PG rotation direction selection

Other adjustment parameter-needs to be modified according to machine operation 01-02: Motor 1 maximum output frequency 01-03: Motor 1 maximum output voltage 01-06: Motor 1 intermediate output frequency 1 01-07: Motor 1 intermediate output voltage 1 01-08: Motor 1 minimum output frequency 01-09: Motor 1 minimum output voltage 08-00: Stall prevention function

Handwheel application feel parameter setting

00-17: Deceleration time 20-08: Speed excitation time 20-43: Speed calculation multiplier 20-44: Speed command limit

Exact source settings and qualifications; no engineering inference.

DI scan time definition — PDF page 188

Source row Code Parameter Scope/options
1 03- 08 (S1~S7) DI scan time 【0】 Scan time 4ms 【1】 Scan time 8ms

Manual — Digital input contact types and switch precautions — page 189

Manual reference: physical PDF page 189. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Usually when using external terminals, switches need to be connected. There are different types of switches, including normally off switches and normally on switches, so pay attention when selecting because the working status of the two types of switches are different. This parameter determines whether normally open switch or normally closed switch input is required.

The definitions of each 03-09/03-10 bit are as follows:

03-09=0 0 0 0; bit labels left to right:s4,s3,s2,s1. 03-10=0 0 0 0; bit labels left to right:[unlabelled],s7,s6,s5. For each diagram:0 means connect to normally on switch;1 means connect to normally closed switch. Literal source normally on wording retained; no correction inferred.

User selects the type of switch input required For example: If S1 and S2 connect to normally closed switch is required, set 03- 09=0011. Note: Before setting the terminal to connect to normally on/normally closed switches, do not set the operation command to come from external terminals, otherwise it will cause unnecessary harm.

Literal A/B bit options; ambiguous normally-on wording separately flagged.

Input terminal contact type selection — PDF page 189

Source row Code Parameter Scope/options
1 03- 09 Multi-function terminal S1-S4 type selection [xxx0b]: S1 A contact [xxx1b]: S1 B contact [xx0xb]: S2 A contact [xx1xb]: S2 B contact [x0xxb]: S3 A contact [x1xxb]: S3 B contact [0xxxb]: S4 A contact [1xxxb]: S4 B contact

Input terminal contact type selection — PDF page 189

Source row Code Parameter Scope/options
1 03- 10 Multi-function terminal S5-S7 type selection [xxx0b]: S5 A contact [xxx1b]: S5 B contact [xx0xb]: S6 A contact [xx1xb]: S6 B contact [x0xxb]: S7 A contact [x1xxb]: S7 B contact

Manual — Digital output parameters and option list — page 190

Manual reference: physical PDF page 190. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Three parameters share the following options; Frame1 has noDO2.

Options0–54 and57–60 are explicitly listed;55/56 are not supplied. Conditions inTable4.3.25 and detailed procedures remain applicable.

Digital output terminal parameter definitions — PDF page 190

Source row Code Terminal/function
1 03-11 Relay (R1A-R1C) output
2 03-12 Optocoupler output (DO1-DOG)
3 03-28 Optocoupler output (DO2-DOG) (Frame1 no DO2)

Shared digital output options — PDF page 190

Source row Setting and function as printed
1 [0]: Operation duration
2 [1]: Fault indication
3 [2]: Frequency reached
4 [3]: Any frequency reached (03-13±03- 14)
5 [4]: Frequency detected 1 (≧ 03-13, the hysteresis range is the setting value of 03-14)
6 [5]: Frequency detected 2 (≦ 03-13, the hysteresis range is the setting value of 03-14)
7 [6]: Automatic restart
8 [7]: Emergency stop
9 [8]: Reserved
10 [9]: Cut-off stop
11 [10]: Reserved
12 [11]: Reserved
13 [12]: Over-torque detected
14 [13]: Current reached
15 [14]: Mechanism brake control (03- 17~03-18)
16 [15]: Reserved
17 [16]: Reserved
18 [17]: Reserved
19 [18]: PLC status
20 [19]: PLC control
21 [20]: Zero speed
22 [21]: Inverter standby
23 [22]: Low voltage detected
24 [23]: Operation command source
25 [24]: Frequency command source
26 [25]: Low-torque detected
27 [26]: Frequency disconnected
28 [27]: Timer function output
29 [28]: Frequency skipping upper offset status
30 [29]: Frequency skipping operation active
31 [30]: Select motor 2

Shared digital output options — PDF page 190

Source row Setting and function as printed
1 [31]: Zero-speed servo status (position mode)
2 [32]: Communication control
3 [33]: RTC timer 1
4 [34]: RTC timer 2
5 [35]: RTC timer 3
6 [36]: RTC timer 4
7 [37]: PID feedback disconnection detection output
8 [38]: Brake release
9 [39]: Frequency detected 1 (for overhead crane use)
10 [40]: Frequency outputting
11 [41]: Position reached (position mode)
12 [42]: Overpressure
13 [43]: Underpressure
14 [44]: Pressure loss detection
15 [45]: PID sleep
16 [46]: Reserved
17 [47]: Reserved
18 [48]: Reserved
19 [49]: Reserved
20 [50]: Frequency detected 3 (≧ 03-44 the hysteresis range is the setting value of 03-45)
21 [51]: Frequency detected 4 (≦ 03-44, the hysteresis range is the setting value of 03-45)
22 [52]: Frequency detected 5 (≧ 03-46, the hysteresis range is the setting value of 03-47)
23 [53]: Frequency detected 6 (≦ 03-46, the hysteresis range is the setting value of 03-47)
24 [54]: Short-circuit braking
25 [57]: Low current detected
26 [58]: Frequency deceleration detected
27 [59]: Over-temperature detected
28 [60]: Lifetime warning period

Manual — Output terminals by frame and output function matrix0–14 — page 191

Manual reference: physical PDF page 191. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Factory settings;Parameters. Upper diagram:R1A,R1B,R1C;Fault indication;03-11. Central labels:DO1,DOG. Lower diagram:R2A,R2C;Operation duration;03-12. Literal labels retained; table4.3.24 separately definesDO1/DO2. No wiring geometry inferred.

Figure 4.3. 32 Multi-function digital output and related parameters

Table 4.3. 24 Control panel and optical coupling individual parameter setting

Table 4.3. 25 Multi-function digital output function table

Exact source mapping, diagram terminal conflict separately flagged.

Mode symbols retained literally. V/F+PG,SV andPMSV only for special projects. Setting descriptions and exact ON/OFF thresholds retained without engineering interpretation.

Table4.3.24 digital output terminals by frame — PDF page 191

Source row Terminal Frame1 Frame2 and above
1 R1A-R1C 03-11=R1A-R1C 03-11=R1A-R1C
2 DO1 03-12=DO1 03-12=DO1
3 DO2 None 03-28=DO2

Table4.3.25 digital output functions and control methods — PDF page 191

Source row Setting Name LCD display Content V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 0 Operation duration Running ON: Operation duration (Run command is ON) O O O O O O O
2 1 Fault indication Fault ON: Failure occurred O O O O O O O
3 2 Frequency reached Freq. Agree ON: Allowed frequency (The allowed frequency width detection is set by 03-14) O O O O O O O
4 3 Any frequency reached Setting Freq Agree ON: Output frequency = allowed frequency detection threshold (03-13) ± allowed frequency detection width (03-14) O O O O O O O
5 4 Frequency detection 1 Freq. Detect 1 ON: Output frequency > 03-13, hysteresis range 03-14 O O O O O O O
6 5 Frequency detection 2 Freq. Detect 2 OFF: Output frequency > 03-13, hysteresis range 03- 14 O O O O O O O
7 6 Automatic restart Auto Restart ON: Automatic restart period O O O O O O O
8 7 Emergency stop Dec to Stop ON: Emergency stop period O O O O O O O
9 8 Reserved Reserved Reserved - - - - - - -
10 9 Cut-off stop Baseblock ON: Baseblock period O O O O O O O
11 10 Reserved Reserved Reserved - - - - - - -
12 11 Reserved Reserved Reserved - - - - - - -
13 12 Over-torque detected Over Torque ON: Over-torque detection is ON O O O O O O O
14 13 Current reached Currebt Agree ON: ON when the output current > 03-15 O O O O O O O
15 14 Mechanical brake control (03-17~03- 18) Mechanical Brake Control ON: Mechanical brake release frequency OFF: Mechanical brake action frequency O O O O O O O

Manual — Output function matrix15–45 — page 192

Manual reference: physical PDF page 192. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Mode symbols retained literally. V/F+PG,SV andPMSV only for special projects. Setting descriptions and exact ON/OFF thresholds retained without engineering interpretation.

Table4.3.25 digital output functions and control methods — PDF page 192

Source row Setting Name LCD display Content V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 15 Reserved Reserved Reserved - - - - - - -
2 16 Reserved Reserved Reserved - - - - - - -
3 17 Reserved Reserved Reserved - - - - - - -
4 18 PLC status PLC statement ON: When 00-02 is set to 3 (PLC operation command source) O O O O O O O
5 19 PLC control Control From PLC ON: The control command source is PLC control O O O O O O O
6 20 Zero speed Zero Speed ON: Output frequency < minimum output frequency (Fmin) O O O O O O O
7 21 Inverter standby Ready ON: Inverter standby (no failure after starting) O O O O O O O
8 22 Low voltage detection Low Volt Detected ON: DC bus voltage = < low voltage warning detection threshold (07-13) O O O O O O O
9 23 Operation command source Run Cmd Status ON: Operation command from the LED digital operator (local mode) O O O O O O O
10 24 Reference frequency source Freq Ref Status ON: Reference frequency from the LED digital operator (local mode) O O O O O O O
11 25 Low-torque detected Under Torque ON: Low torque detection is ON O O O O O O O
12 26 Frequency disconnected Ref. Loss. ON: Reference frequency lost O O O O O O O
13 27 Timer function output Timer Output The parameters to set the timer function are 03-33 and 03-34, and the timer function input is set by parameters 03-00 to 03-06 O O O O O O O
14 28 Frequency skipping upper offset status Traverse UP ON: Acceleration period (when frequency skipping is upwards) O O X X X X O
15 29 Frequency skipping operation active During Traverse ON: During frequency skipping operation (while frequency skipping operation is executing) O O X X X X O
16 30 Motor 2 selection Motor 2 Selection ON: Switch to motor 2 O O O O O O O
17 31 Zero-speed servo status (Position mode) Zero Servo ON: Move during position mode X X X O O X X
18 32 Communication control Control From Comm ON: Communication control (communication position: 2507H) O O O O O O O
19 33 RTC timer 1 RTC Timer 1 ON: When 16-36 (RTC speed selection) is set to timer 1 and there is activity within the time set in 16-32 (timer 1 source) . O O O O O O O
20 34 RTC timer 2 RTC Timer 2 ON: When 16-36 (RTC speed selection) is set to timer 2 and there is activity within the time set in 16-33 (timer 2 source) . O O O O O O O
21 35 RTC timer 3 RTC Timer 3 ON: When 16-36 (RTC speed selection) is set to timer 3 and there is activity within the time set in 16-34 (timer 3 source) . O O O O O O O
22 36 RTC timer 4 RTC Timer 4 ON: When 16-36 (RTC speed selection) is set to timer 4 and there is activity within the time set in 16-35 (timer 4 source) . O O O O O O O
23 37 PID feedback disconnection detection output PID Fbk Loss ON: PID feedback disconnected O O O O O O O
24 38 Brake release Brake Relase ON: Release brake X X O O O X X
25 39 Frequency detection 1 (For overhead crane use) Freq. Detect 1 (Dedicated crane) ON: Output frequency > 03-13, hysteresis range 03-14 O O O X X X X
26 40 Frequency outputting Frequency output Ing ON: The inverter status is DC braking, base block of stopped status. X X X O O X X
27 41 Position reached (Position mode) Multi Pos. Ready ON: Complete position search under mode X X X O O X X
28 42 Overpressure High PSI ON: Overpressure warning or error O O X X X X X
29 43 Underpressure Low PSI ON: Underpressure warning or error O O X X X X X
30 44 Pressure loss detection Fb PSI ON: Under-voltage error O O X X X X X
31 45 PID sleep PID Sleep ON: During PID Sleep O O O O O O O

Manual — Output function matrix46–60 and detailed contact conditions — page 193

Manual reference: physical PDF page 193. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1). Operation duration (setting= 0).

(2). Fault indication (setting=1). ‧ When failures occur, the output contact is in ON status. (3). Frequency reached (setting=2). (4). Any frequency reached (setting=3). (5). Frequency detected 1 (setting=4). (6). Frequency detected 2 (setting=5). (7). Frequency detected 3 (setting=50). (8). Frequency detected 4 (setting=51). (9). Frequency detected 5 (setting=52). (10). Frequency detected 6 (setting=53). ‧ Refer to Table 4.3.26 frequency detection operation. (11). Automatic restart (setting=6). ‧ During the automatic restart operation period, the output contact is in ON status. (12). Emergency stop (setting=7). ‧ During emergency stop, the output contact is in ON status. (13). Base block (B.B.) period (setting=9). ‧ Inverter output base block. (14). Over-torque detected (no contact point) (setting=12). (15). Low-torque detected (no contact point) (setting=25). ‧ By setting any one of the parameters 03-11 or 03-12 to 12 or 25, the over-torque/low-torque signal can output the detected signal from the multi-function digital output terminal, and the threshold action of this function can be set through 8-13~8-20. (16). Current reached (setting=13). ‧ When the output current > 03-15 and the duration of the output current > 03-15 is > 03-16, it is in ON status. (17). PLC status (setting=18). ‧ When the 00-02 operation command source is set to 3 (PLC control), it is in ON status. (18). PLC control (setting=19). ‧ When the inverter control command source is PLC control status, it is in ON status. (19). Zero-speed (setting=20).

Mode symbols retained literally. V/F+PG,SV andPMSV only for special projects. Setting descriptions and exact ON/OFF thresholds retained without engineering interpretation.

ON also applies when command isoff but output remains.

Table4.3.25 digital output functions and control methods — PDF page 193

Source row Setting Name LCD display Content V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 46 Reserved Reserved Reserved - - - - - - -
2 47 Reserved Reserved Reserved - - - - - - -
3 48 Reserved Reserved Reserved - - - - - - -
4 49 Reserved Reserved Reserved - - - - - - -
5 50 Frequency detection 3 Freq. Detect 3 ON: Output frequency > 03-44, hysteresis range 03-45 O O O O O O O
6 51 Frequency detection 4 Freq. Detect 4 OFF: Output frequency > 03-44, hysteresis range 03- 45 O O O O O O O
7 52 Frequency detection 5 Freq. Detect 5 ON: Output frequency > 03-46, hysteresis range 03-47 O O O O O O O
8 53 Frequency detection 6 Freq. Detect 6 OFF: Output frequency > 03-46, hysteresis range 03- 47 O O O O O O O
9 54 Short-circuit braking SC Brk ON: Short-circuit braking X X X X X O X
10 57 Low current detected Low Current Detect ON: Output current≦ 03-48 low current detected threshold O O O O O O O
11 58 Frequency deceleration detection Freq. Decel to ON: When the output frequency < frequency command - 03-14 and currently decelerating O O O O O O O
12 59 Over-temperature detected OH Detect ON: Heatsink temperature >08-46, hysteresis range 08-47 O O O O O O O
13 60 End-of-life warning period - ON: While “Cyear”, “FLIFE” and “ILIFE” is displayed O O O O O O O

Operation duration setting0 contact status — PDF page 193

Source row State Condition
1 Off The operation command is off and the inverter is in off status.
2 On The operation command is on, or the operation command is off but there is still residual output.

Manual — Output contact conditions and communication control — page 194

Manual reference: physical PDF page 194. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Output Frequency;01-08(Fmin);Zero Speed;OFF;ON;time axes t. Explicit conditions retained in zero-speed contact table; no waveform interpolation.

Figure 4.3. 33 Zero-speed operation (20). Inverter standby (setting=21). ‧ When started and no failures occurred, the inverter will be in standby status. (21). Low voltage detection (setting=22). ‧ ON = The DC bus voltage of the main circuit is below the under-voltage detection threshold (07-13). (22). Operation command source (setting=23).

(23). Frequency reference source (setting=24).

(24). Frequency disconnected (setting=26). ‧ The operation command is on and the frequency reference is 0, and when 11-41 is set to 1 (operating under multiplying 11-42 by the previous frequency reference), the output contact point is in ON status. (25). Timer function output (setting=27). ‧ Refer to the descriptions of parameters 03-37 and 03-38 for the operation of the timer function. (26). Frequency skipping upper offset (setting=28). ‧ Refer to parameter 19-frequency skipping function group for the operation of frequency skipping. (27). Frequency skipping operating (setting=29). ‧ By setting 28 or 29, the acceleration period or frequency skipping operation can be outputted to the multi-function digital output terminal. Refer to parameter 19-frequency skipping function group for the control of frequency skipping. (28). Motor 2 selection (setting=30). (29). Zero-speed servo status (position mode) (setting=31). ‧ Under zero servo status, it is in ON status. (30). Communication control (setting=32). Communication position: 2507H, the control method is DO2 DO1 RY1. If DO2 DO1 and RY1 are all set to communication control, then set 2507H to 5 (101), then DO2 and RY1 will move.

Exact source contact conditions. Literal setting5 and output-terminal wording retained and flagged.

Zero-speed contact setting20 — PDF page 194

Source row State Condition
1 Off Output frequency = > minimum output frequency (01-08, Fmin)
2 On Output frequency < minimum output frequency

Operation command source contact setting23 — PDF page 194

Source row State Condition
1 Off Remote mode: When 00-02=1 or 2, or when any one of the multi-function digital output terminals (S1 to S7) is set to LOCAL/REMOTE control (setting value=5). The contact point is OFF, and the SEQ indicator on the digital operator lights up.
2 On Local mode: When 00-02=0, or when any one of the multi-function digital output terminal (S1 to S7) is set to LOCAL/REMOTE control (setting value=5). The contact point is ON, and the SEQ indicator on the digital operator is off.

Frequency reference source contact setting24 — PDF page 194

Source row State Condition
1 Off Remote mode: When 00-05=1 or 2, or when any one of the multi-function digital output terminal (S1 to S7) is set to LOCAL/REMOTE control (setting value=5). The contact point is OFF, and the REF indicator on the digital operator lights up.
2 On Local mode: When 00-05=0, or when any one of the multi-function digital output terminal (S1 to S7) is set to LOCAL/REMOTE control (setting value=5). The contact point is ON, and the REF indicator on the digital operator is off.

Manual — Output signal conditions and model restrictions — page 195

Manual reference: physical PDF page 195. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(※ E710 Frame1 no DO2) (31) RTC timer 1~4 (setting=33~36)ON: When timer 1 is selected for 16-36 (RTC speed selection) and there is action within the time set by 16-32~16-35 (timer 1~4 source). (32). PID feedback disconnection detection output (setting=37) When PID feedback is disconnected (please refer to the settings of parameter 10-11~10-13), it is in ON status. (33). Brake release (setting=38) ON status is release brake. Please refer to parameters 03-41~42 for the conditions and descriptions of brake release. (34). Frequency detected 1 (for overhead crane use) (setting=39) (35). Frequency outputting (setting=40) ‧ Refer to Table 4.3.26 frequency detection operation. (36). Position reached (position mode) (setting=41) ‧ Perform position search under position mode, and it will become ON status after completed. (37). Overpressure warning/error (setting=42) ‧ Please refer to the settings of parameters 23-12~23-14. (38). Underpressure warning/error (setting=43) ‧ Please refer to the settings of parameters 23-15~23-17. (39). Pressure loss detection warning/error (setting=44) ‧ Please refer to the settings of parameters 23-18~23-19. (40). PID sleep (setting=45) ‧ Notify during PID sleep. (41). Short-circuit braking (setting=54) ‧ While executing short-circuit brake, the output terminal closes. (42) When low current (set as 57) is detected: When the output current <= 03-48, the relay operates. (43) Frequency deceleration detection (set as 58) ‧ When the output frequency < frequency command - 03-14, and is currently decelerating, the relay operates. Please refer to Table 4.3.26 frequency detection operation. (44) Over-temperature detected (setting is 59) ‧ Heatsink temperature > 08-46 relay operates, the hysteresis range is 08-47. (45) End-of-life warning period (setting is 60) ‧ When the end-of-life warnings “Cyear”, “FLIFE”, “ILIFE” appears, the relay is in ON status.

Manual — Frequency thresholds and detection operation — page 196

Manual reference: physical PDF page 196. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ Frequency detection function: Set the multi-function output terminals R1A-R1C, DO1 or DO2 (03-11, 03-12 or 03-28) as the output frequency confirmation signal and set frequency confirmation and output frequency detection 1~6. ‧ The frequency detection operation time table is as described in Table 4.3.26 below.

Table 4.3. 26 Frequency detection operation

Output Frequency;Freq Reference;03-14;FWD;REV;Frequency Agree Signal;OFF;ON;ON;time axes.

Output Frequency;03-14;03-13;FWD;REV;Setting Frequency Agree Signal;03-13;03-14;OFF;ON;ON;time axes.

Output Frequency;03-14;03-13;03-50;Output Frequency Detection 1 Signal;03-13;03-14;03-50;printed contact states left to right:OFF,ON,OFF,ON;time axes.

Separate thresholds and widths retained; no equivalent switching behavior inferred from a range.

Full source conditions, comparator wording, acceleration/deceleration period and settings retained. Diagram visible labels separately linked by row; geometry remains original.

Frequency detection parameter ranges — PDF page 196

Source row Parameter Name Scope and unit
1 03-13 Frequency detection threshold 【0.0~599.0】 Hz
2 03-14 Frequency detection width 【0.1~25.5】 Hz
3 03-44 Frequency detection threshold 2 【0.0~599.0】 Hz
4 03-45 Frequency detection width 2 【0.1~25.5】 Hz
5 03-46 Frequency detection threshold 3 【0.0~599.0】 Hz
6 03-47 Frequency detection width 3 【0.1~25.5】 Hz
7 03-50 Frequency detection threshold 4 【0.0~599.0】 Hz
8 03-51 Frequency detection threshold 5 【0.0~599.0】 Hz
9 03-52 Frequency detection threshold 6 【0.0~599.0】 Hz

Table4.3.26 frequency detection operation — PDF page 196

Source row Function Source description
1 Frequency reached . When the output frequency is in the frequency reference ± frequency detection width (03-14) range, the frequency reached output signal is ON. . Set any one of the parameters 03-11, 03-12 or 03-28 to 2 (frequency reached).
2 Any frequency reached . When the output frequency reached the frequency confirmation detection threshold (03-13) and is within the frequency confirmation detection width (03-14) range during the acceleration period, any frequency reached signal set is ON. . Set any one of the parameters 03-11, 03-12 or 03-28 to 3 (any frequency reached).
3 Frequency detection 1 . During the acceleration period, if its output frequency is greater than the frequency detection threshold (03-13) + frequency detection width (03-14), then the frequency detected 1 signal will change to ON. . During the deceleration period, if its output frequency is less than the frequency detection threshold 4 (03- 50), then the frequency detected 1 signal will change to OFF. . Set any one of the parameters 03-11, 03-12 or 03-28 to 4 (frequency detected 1).

Manual — Frequency detection2–5 switching conditions — page 197

Manual reference: physical PDF page 197. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Output Frequency;03-14;03-13;03-50;Output Frequency Detection 2 Signal;03-13;03-14;03-50;printed contact states left to right:ON,OFF,ON,OFF,ON;time axes.

Output Frequency;03-45;03-44;03-51;Output Frequency Detection 3 Signal;03-44;03-45;03-51;printed contact states left to right:OFF,ON,OFF,ON;time axes.

Output Frequency;03-45;03-44;03-51;Output Frequency Detection 4 Signal;03-44;03-45;03-51;printed contact states left to right:ON,OFF,ON,OFF,ON;time axes.

Output Frequency;03-47;03-46;03-52;Output Frequency Detection 5 Signal;03-46;03-47;03-52;printed contact states left to right:OFF,ON,OFF,ON;time axes.

Full source conditions, comparator wording, acceleration/deceleration period and settings retained. Diagram visible labels separately linked by row; geometry remains original.

Table4.3.26 frequency detection operation — PDF page 197

Source row Function Source description
1 Frequency detected 2 . During the acceleration period, if its output frequency is greater than or equal to the frequency detection threshold (03-13) + frequency detection width (03-14), then the frequency detected 2 signal will change to OFF. . During the deceleration period, if its output frequency is less than or equal to the frequency detection threshold 4 (03- 50), then the frequency detected 2 signal will change to ON. . Set any one of the parameters 03-11, 03-12 or 03-28 to 5 (frequency detected 2).
2 Frequency detection 3 . During the acceleration period, if its output frequency is greater than or equal to the frequency detection threshold 2 (03-44) + frequency detection width 2 (03-45), then the frequency detected 3 signal will change to ON. . During the deceleration period, if its output frequency is less than or equal to the frequency detection threshold 5 (03- 51), then the frequency detected 3 signal will change to OFF. . Set any one of the parameters 03-11, 03-12 or 03-28 to 50 (frequency detected 3).
3 Frequency detected 4 . During the acceleration period, if its output frequency is greater than or equal to the frequency detection threshold 2 (03-44) + frequency detection width 2 (03-45), then the frequency detected 4 signal will change to OFF. . During the deceleration period, if its output frequency is less than or equal to the frequency detection threshold 5 (03- 51), then the frequency detected 4 signal will change to ON. . Set any one of the parameters 03-11, 03-12 or 03-28 to 51 (frequency detected 4).
4 Frequency detection 5 . During the acceleration period, if its output frequency is greater than or equal to the frequency detection threshold 3 (03-46) + frequency detection width 3 (03-47), then the frequency detected 5 signal will change to ON. . During the deceleration period, if its output frequency is less than or equal to the frequency detection threshold 6 (03- 52), then the frequency detected 5 signal will change to OFF. . Set any one of the parameters 03-11, 03-12 or 03-28 to 52 (frequency detected 5).

Manual — Frequency detection6, crane and output/deceleration signals — page 198

Manual reference: physical PDF page 198. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Output Frequency;03-47;03-46;03-52;Output Frequency Detection 6 Signal;03-46;03-47;03-52;printed contact states left to right:ON,OFF,ON,OFF,ON;time axes.

Output Frequency;03-14;03-13;03-50;Output Frequency Detection 1 Signal;03-13;03-14;03-50;printed contact states left to right:OFF,ON,OFF,ON;time axes.

Run command:OFF,ON,OFF;Base Block:OFF,ON,OFF;Output Frequency;DC Brake(two labels);Frequency Output Ing:OFF,ON,OFF,ON,OFF. Labels only; waveform geometry remains in source.

Output Frequency;Freq Reference;03-14;FWD;REV;Frequency Agree Signal;03-14;Freq Reference;OFF;ON;OFF;ON;time axes.

Full source conditions, comparator wording, acceleration/deceleration period and settings retained. Diagram visible labels separately linked by row; geometry remains original.

Table4.3.26 frequency detection operation — PDF page 198

Source row Function Source description
1 Frequency detected 6 . During the acceleration period, if its output frequency is greater than or equal to the frequency detection threshold 3 (03-46) + frequency detection width 3 (03-47), then the frequency detected 6 signal will change to OFF. . During the deceleration period, if its output frequency is less than or equal to the frequency detection threshold 6 (03-52), then the frequency detected 6 signal will change to ON. . Set any one of the parameters 03-11, 03-12 or 03-28 to 53 (frequency detected 6).
2 Frequency detection 1 (For overhead crane use) . During the acceleration period, if its output frequency is greater than the frequency detection threshold (03-13) + frequency detection width (03-14), then the frequency detected 1 (overhead crane use) signal will change to ON. . During the deceleration period, if its output frequency is less than the frequency detection threshold 4 (03- 50), then the frequency detected 1 (overhead crane use) signal will change to OFF. . Set any one of the parameters 03-11, 03-12 or 03-28 to 39 (frequency detected 1 (overhead crane use)).
3 Frequency outputting . When the inverter outputs frequency, the output terminal closes.
4 Frequency deceleration detection . When the output frequency is outside the range of the frequency reference ± frequency detection width (03-14) range, and the output signal is ON when the frequency is decelerating. . Set any one of the parameters 03-11, 03-12 or 03-28 to 58 (frequency deceleration detection).

Manual — Current threshold and detection delays — page 199

Manual reference: physical PDF page 199. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note: The maximum value of 03-53 will be limited to the setting value of 03-15 ‧ When 03-11 is set to [13]: When the output current > 03-15, the relay operates. ‧ 03-15: Setting value 0.1~ according to the rated current of the motor. ‧ 03-16: Setting value (0.1~10.0) unit seconds, in addition when the output current ≤ 03-53, also the delay time of the relay signal from ON to OFF is 100ms (fixed). Timing diagram:

Figure 4.3. 34 Example of current reached

➢ When 03-11 is set to [57]: When the output current <= 03-48, the relay operates. ➢ When 03-48 is set to 0.0, the low current detection function is off. ➢ If the current is continuously lower than the setting value of 03-48 within the 03-49 time, the relay operates. Also, the delay time for the relay signal to change from ON to OFF is 100ms (fixed). The timing diagram is as follows:

100%;I load current;03-15;03-53;T;03-16;Fixed100msec;03-11Relay;ON. Labels only; thresholds and delay conditions remain in source prose.

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Current, brake, output or pulse parameter definitions — PDF page 199

Source row Parameter Name Scope/options and unit
1 03-15 Current reached threshold 【0.1~999.9】 A
2 03-16 Current reached detection delay time 【0.1~10.0】 Sec
3 03-53 Current reached threshold 2 【0.0~999.9】A

Current, brake, output or pulse parameter definitions — PDF page 199

Source row Parameter Name Scope/options and unit
1 03-48 Low current detected threshold 【0.0~999.9】 A
2 03-49 Low current detected delay time 【0.00~655.34】 Sec

Manual — Low-current timing and mechanical brake thresholds — page 200

Manual reference: physical PDF page 200. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 35 Example of low current detected

➢ When 03-11 = [14], During acceleration, when the actual frequency reached 03-17 mechanical brake release frequency, the relay outputs; During deceleration, when the actual frequency reached 03-18 mechanical brake operation frequency, the relay stops outputting. ➢ When 03-17 ≤ 03-18, the timing diagram is as follows:

Figure 4.3. 36 Example of mechanical brake release (03-17≤03-18)

➢ When 03-17 ≥ 03-18, the timing diagram is as follows:

100%;I load current;03-48;T;Operation command;ON;03-49;Continuous03-49time not reached;The relay does not operate;03-11Relay;ON;Fixed100msec. Labels only; no waveform interpolation.

Hz;03-18;03-17;T;Operate;RUN;STOP;03-11=14;ON;OFF. Caption and prose specify03-17≤03-18.

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Adjacent source context — repeated to preserve continuation:

Current, brake, output or pulse parameter definitions — PDF page 200

Source row Parameter Name Scope/options and unit
1 03-17 Mechanical brake release threshold setting 【0.00~599.00】 Hz
2 03-18 Mechanical brake action threshold setting 【0.00~599.00】 Hz

Manual — Relay contact types and UP/DOWN hold behavior — page 201

Manual reference: physical PDF page 201. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 37 Example of mechanical brake release (03-17≥03-18)

‧ Set 03-27 to 0, when the Run Command is removed, its frequency command before deceleration will be retained and not cleared, and the next run command will output according to the frequency previously recorded. ‧ When 03-27 is set to 1, if Run Command is removed, its frequency command will be cleared before deceleration. ‧ When 03-27 is set to 2, if there is no Run Command, its UP/DOWN command is valid and is written into the frequency command. ‧ When 03-27 is set to 3, the frequency command will remain in uncleared status, and when the Run Command is sent again, if the UP/DOWN button is pressed before the operation command caught up with the frequency command, the frequency command will be set according to the operation frequency. When 03-40 is set to 0Hz, the original up/down function will be retained. When 03-40 is no 0, the frequency command will be set according to the original frequency plus the frequency set in 03-40 For example: Set terminal S1: 03- 00=[8] Up increase frequency command, terminal S2: 03- 01=[9] Down decrease frequency command, 03- 40=[△]Hz Mode 1: When 03-40 is set to 0Hz, the original up/down function will be retained, as shown in Figure 4.3.24. Mode 2: When the 03-40 setting is not 0Hz, and the terminal conduction time is <2Sec, for each conduction, the frequency changes by △Hz (the frequency set in 03-40).

Hz;03-17;03-18;T;Operate;RUN;STOP;03-11=14;ON;OFF. Caption and preceding prose specify03-17≥03-18.

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Adjacent source context — repeated to preserve continuation:

Current, brake, output or pulse parameter definitions — PDF page 201

Source row Parameter Name Scope/options and unit
1 03-19 Relay (R1A-R1C) and DO1 type selection [xxx0b]: R1 A contact [xxx1b]: R1 B contact [xx0xb]: Optocoupler 1 A contact [xx1xb]: Optocoupler 1 B contact

Current, brake, output or pulse parameter definitions — PDF page 201

Source row Parameter Name Scope/options and unit
1 03-27 UP/DOWN frequency hold selection [0]: Maintain UP/DOWN frequency when stopped [1]: Clear Up/DOWN frequency when stopped [2]: Allow frequency UP/DOWN when stopped. [3]: Update frequency during acceleration.
2 03-40 Up/Down frequency bandwidth setting 【0.00~5.00】Hz

Manual — UP/DOWN timing and literal source formulas — page 202

Manual reference: physical PDF page 202. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 38 Example of UP/DOWN timing (mode 2)

Mode 3: When the 03-40 setting is not 0Hz, and the terminal conduction time is >2Sec, the frequency changes based on general acceleration and deceleration.

Figure 4.3. 39 Example of UP/DOWN timing (mode 3)

※Description: △H1: Set the frequency increase during acceleration, t1: Terminal conduction time during acceleration, △H2: Set frequency increase during deceleration, t2:Terminal conduction time during deceleration

Hz;Frequency reference upper limit;Frequency reference lower limit;△Hz;Actual output frequency;T;TerminalS1:ON,ON,ON;TerminalS2:ON,ON,ON. Only printed labels; timing/curve geometry remains in original.

Set frequency(Hz);Frequency reference upper limit;Frequency reference lower limit;Actual output frequency;△H1;△Hz;△H2;T;2Sec;t1;2Sec;t2;TerminalS1:LongON,OFF;TerminalS2:OFF,LongON. No interpolation of waveform geometry.

△H1=(Maximum frequency / Acceleration time2) × Terminal channel time t1. Literal printed numerator and denominator retained.

△H2=(Maximum frequency / Acceleration time2) × Terminal channel time t2. Source also prints Acceleration time2 here; not replaced by deceleration time.

Manual — Optocoupler output and normal/PWM pulse input — page 203

Manual reference: physical PDF page 203. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

There are two types of pulse input selection: (1) General pulse input: The calculation method of PI input is to divide the captured frequency by the pulse input scale set in 03-31, and then map it to the maximum output frequency of 01-02 motor 1. The percentage displayed when monitoring the pulse input of parameter 12-79 is the ratio between the input signal and the 03-31 pulse input scale. (2) PWM method: The correct frequency needs to be entered first, the calculation method is to divide the duration of the rising edge pulse by the time period of the previous pulse, then map it to the maximum output frequency of 01-02 motor 1. The percentage displayed when monitoring the pulse input of parameter 12-79 is the ratio between the rising edge of the input signal and the time period. Note: The pulse period error of the PWM method is plus or minus 12.5%, and no actions will be taken if exceeded the error range. The schematic diagram of pulse input selection is as follows:

Figure 4.3. 40 Schematic diagram of pulse input selection

03-30=0;Normal Mode;Sample Pulse train;T:Period;PI;Frequency=1/(T:Period).

Pulse Input Command=(Frequency / Scaling factor(using03-31)) ×100%(01-02).

03-30=1;PWMMode;T:Period;T1:Period;Sample Pulse train;PI.

Pulse Input Command=(T1:Period / T:Period) ×100%(01-02).

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Current, brake, output or pulse parameter definitions — PDF page 203

Source row Parameter Name Scope/options and unit
1 03- 28 Optocoupler output (DO2-DOG) (Frame1 no DO2) The scope and definition are the same as 03-11, 03-12 (03-28 is set as 8 is the pulse output function)
2 03-29 Optocoupler output type selection (DO2-DOG) (Frame1 no DO2) [xx0xb]: Optocoupler 2 A contact [xx1xb]: Optocoupler 2 B contact

Current, brake, output or pulse parameter definitions — PDF page 203

Source row Parameter Name Scope/options and unit
1 03- 30 Pulse input selection [0]: General pulse input [1]: PWM method

Manual — Pulse input scaling, PID and output function options — page 204

Manual reference: physical PDF page 204. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Refer to Table 3.4.3 control circuit terminal. ‧ Figure 4.3.41 is the schematic diagram of using pulse input function adjustment.

Figure 4.3. 41 Pulse input adjustment

(1). Pulse input frequency command methods. ‧ First set the 00-05 primary frequency command source selection to 4 pulse input, and then use the format of setting 03-30 pulse input selection as pulse input to connect the pulse input terminal PI with serial connection as the frequency reference. Please refer to Figure 4.3.7 for using pulse input as frequency reference. ‧ Connect the pulse input terminal PI with serial connection as the frequency reference function, and set the number of pulses through parameter 03-31 (pulse input scale), which is equal to the maximum output frequency (01-02). If there is performance interference, increase the value of 03- 34 (pulse input filter time). (2). PID input method of pulse input. ‧ First set the primary frequency command source selection of 00-05 to given by 5 PID, and then use 03-30 pulse input selection to set the pulse input format. ➢ When 10-01 is set to 3 (PID feedback value source setting), the pulse train input to the control terminal PI is used as the PID feedback value. ➢ When 10-00 is set to 3 (PID target value source setting), the serial pulse input to the control terminal PI is used as the PID target value. Refer to Figure 4.3.42 on PID control. ‧ Use parameter 10-03 (PID control mode) to execute PID control, and set the PID feedback value and target value.

Figure 4.3. 42 PID control

Pulse train;PI;Filter1/(1+ST);T:Pulse input filter time(using03-34);Scaling1/K;K:Scaling factor(Using03-31);Gain and Bias;03-32;03-33;0%;10%;00-05=4:Frequency Reference;10-01=3:PID Feedback;10-00=3:PID Target. Literal10%label retained.

Target value(Set-point);+;Feedback value(Actual);−;PID Regulator;Frequency Reference. Printed labels only; diagram geometry remains in original.

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

03-35option7requiresPGcardandonlyforspecialprojects.

Source column order preserved asoptions1–7. PGoutputrequiresPGcardandonlyforspecialprojects.

Current, brake, output or pulse parameter definitions — PDF page 204

Source row Parameter Name Scope/options and unit
1 03-31 Pulse input scale Set and adjust according to 03-30 【0】50~32000Hz 【1】10~1000Hz
2 03- 32 Pulse input gain 【0.0~1000.0】%
3 03-33 Pulse input bias voltage 【-100.0~100.0】%
4 03-34 Pulse input filter time 【0.00~2.00】Sec

Pulse output function parameter — PDF page 204

Source row Code Name
1 03- 35 Pulse output function setting

Pulse output function options — PDF page 204

Source row Setting and function as printed
1 [1] Frequency command
2 [2] Output frequency
3 [3] Output frequency after soft start
4 [4] Motor speed
5 [5] PID feedback
6 [6] PID input
7 [7] PG output (must be used with PG card) (only for special projects)

Manual — Pulse function selection and output scale — page 205

Manual reference: physical PDF page 205. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1). Pulse input function selection (03-35) ‧ Refer to Table 4.3.27 on pulse input function selection. Table 4.3. 27 Pulse input function selection

. 1~4 are speed related items, 5 and 6 are PID related items, and 7 is PG related item that needs to be used with PG card.* (V/F+PG, SV and PMSV are only for special projects (2). Adjust pulse output scale (03-36). ‧ Use 03-36 (pulse output scale) to adjust PO and set the number of pulse outputs to map 100% of the selected item. Refer to Figure 4.3.43 below.

Figure 4.3. 43 Pulse output ratio

‧ If 03-35 is set to 2 (output frequency), the pulse output of PO and the output frequency of the inverter are synchronized. The pulse output scale is set according to parameter 03-36.

Pulse output;(Hz);03-36;0%;100%;Pulse output items. No inferred curve interpolation.

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Source heading saysinputwhileprecedingcard/prose referoutput;literalnamesandnormalizationretained.PGcard/specialprojectqualificationsretainedwithpageprose.

Current, brake, output or pulse parameter definitions — PDF page 205

Source row Parameter Name Scope/options and unit
1 03-36 Pulse input scale 【1~32000】Hz

Table4.3.27 pulse input function selection — PDF page 205

Source row 03-35setting Function Screen display(LCD) Unlabelled source column Remarks
1 1 Frequency reference (Fref) Freq Ref 12-16 100% = Maximum output frequency (01-02)
2 2 Output frequency (Fout) Output Freq 12-17 100% = Maximum output frequency (01-02)
3 3 Output frequency after soft start Output Freq (SFS) - 100% = Maximum output frequency (01-02)
4 4 Motor rotation speed (rpm) Motor Speed 12-22 100% = Maximum output frequency (01-02)
5 5 PID feedback PID Feedback 12-39 100% = Maximum output frequency (01-02)
6 6 PID control input PID Input 12-36 100% = Maximum output frequency (01-02)
7 7 PG monitor output PG Pulse Output ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Pulse electrical limits and PG application — page 206

Manual reference: physical PDF page 206. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ Refer to Figure 4.3.44 below on pulse output signal level.

Figure 4.3. 44 Pulse output signal level

‧ When 03-35 = 7 (PG pulse monitor output), the PG pulse output ratio is 1:1, and the setting value of 03-36 is ignored. Note: An external pull-up resistor and voltage can be connected to the PO terminal and adjusted according to the customer's environment. (The design of the external power supply and pull-up resistor connected to the PO terminal must comply with the requirements of a voltage below 48V and a current below 50mA) (3). Application example Example A. PG connection and operation. ‧ Operation (or synchronization operation) can be performed by inputting a serial pulse signal as the frequency reference directly. Refer to Figure 4.3.45.

Figure 4.3. 45 PG connection and operation

‧ Related parameter settings: 1. Frequency reference selection: 00-05=4 (pulse input). 2. Pulse input selection: 03-30=0 (general pulse input). 3. Pulse input scale: 03-31 (the number of pulses with Hz as the unit is set to the same as the maximum output frequency, 01-02). 4. Pulse input gain: 03-32 (Set the pulse frequency input gain as set in 03-31). 5. Pulse input bias voltage: 03-33 (Set the pulse frequency input bias voltage as set in 03-31) 6. Pulse input filter time: 03-34 (if the pulse input is unstable due to interference, increase the setting value). ‧ Use the forward command and reverse command of the multi-function digital input to change the operation direction. ‧ If higher accuracy is required, use the SV or V/f + PG control method.* (V/F+PG, SV and PMSV are only for special projects

+5V;2.2KΩ;PO;GND;0V;5V;0V;T1;T2;Pulse duty:T1=T2;Pulse train output:0to32KHz,2.2KΩ. Electrical application limits are separately preserved from prose.

INV1;M;Fwd Run/Stop;S1;Rev Run/Stop;S2;24VG;(*1);PG;PI;GND. Labels only; no inferred wiring instructions.

Manual — Two-inverter tracking application — page 207

Manual reference: physical PDF page 207. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example B: Connection and operation of 2 inverters ‧ Refer to Figure 4.3.46 on using 2 inverters for “tracking” or synchronization operations.

Figure 4.3. 46 Connection and operation of 2 inverters

‧ INV 1 related parameter settings: 1. Frequency reference input: Case 1: Set the parameters related to pulse input to the same as in the previous Example 1 to operate INV 1 with pulse input (for example the primary PG). Case 2: Select the primary frequency reference with 00-05 to operate INV1 with analog frequency reference. 2. Frequency reference pulse output: a. Pulse output function selection: 03-35=2 (Output frequency reference from the pulse output terminal PO). b. Pulse output scale: 03-36 (when the speed is full speed, set the number of output pulses). ‧ INV 2 related parameter settings: 1. Frequency reference selection: 00-05=4 (pulse input). 2. Pulse input selection: 03-30=0 (general pulse input). 3. Pulse input scale: 03-31 (Set the number of pulses with Hz as the unit to the same as the maximum output frequency, 01-02; basically, set this value to the same as 03-31 of INV 1). 4. Pulse input gain: 03-32 (Set the pulse frequency input gain as set in 03-31. Adjust 03-32 after confirming the proportional setting of INV 2). 5. Pulse input bias voltage: 03-33 (Set the pulse frequency input bias voltage as set in 03-31. Adjust 03- 33 after setting the INV 2 bias voltage). 6. Pulse input filter time: 03-34 (if the pulse input is unstable due to interference, increase the value set). Note: An external pull-up resistor and voltage can be connected to the PO terminal and adjusted according to the customer's environment. (The current limit of PO is 50mA)

INV1;M1;FWD Run/Stop;S1;REV Run/Stop;S2;24VG;Master PG etcs.;PI;GND;PO;GND. INV2;M2;FWD Run/Stop;S1;REV Run/Stop;S2;24VG;PI;GND. Supply labels:+5V;2.2KΩ. Wiring geometry remains in source.

Manual — Pulse input/output synchronization examples — page 208

Manual reference: physical PDF page 208. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example C: Synchronization operation using pulse input.

Figure 4.3. 47Synchronization operation with pulse input

‧ Applies the pulse signals generated by external pulse generators to the pulse input terminal PI of multiple inverters for synchronization. ‧ Set 00-05 to 4 (pulse input frequency command), and set 03-30 to 0 (general pulse input). ‧ By setting the corresponding parameters (03-00 to 03-06) to 32, assign any terminal of the multi- function digital input (S1 to S7) as the synchronization command. ‧ Convert the serial pulses received by the pulse input (terminal PI) to a synchronization frequency command, and the synchronization command (SYNC) allows the frequency reference to be executed. Refer to Figure 4.3.47 on synchronization operation using pulse input. Example D. Synchronization operation using pulse output

Figure 4.3. 48 Synchronization operation with pulse output

‧ Set 03-35 to 1 (uses the pulse output function as the frequency command). The internal frequency reference of the primary inverter is converted to pulse output signals (terminal PO). ‧ Set 00-05 to 4 (pulse input frequency command), and set 03-30 to 0 (general pulse input). Adjust the ratio, gain and bias voltage of 03-31 to 03-33 on the inverter sequentially. ‧ The pulse output signal converted by the master inverter can be inputted into the pulse input terminal of the slave inverter, allowing the master and slave inverters to operate synchronously. ‧ Refer to Figure 4.3.48 on synchronization operation using pulse output.

Slave;PI;Pulse Input;SYNC;Slave;PI;A/B;PG;IM;IM;PG;A/B;Synchronized Operation. Labels only; no geometry or applicability inferred.

Frequency Reference;Master;PO;Pulse Input;SYNC;Slave;PI;A/B;PG;IM;IM;PG;A/B;Synchronized Operation. Labels only; no geometry or applicability inferred.

Manual — Timer delays and brake-release conditions — page 209

Manual reference: physical PDF page 209. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ When any one of the multi-function input parameters 03-00 to 03-06 (S1 to S7) is set to 35 (count function input), and any one of the multi-function output parameters 03-11 or 03-12 is set to 27 (count function output), the timer function is enabled. ‧ These inputs and outputs are used as general-purpose I/O to set on/off delay times. ‧ The timer parameters (03-37/03-38) can prevent frequent noises caused by detectors and switches, etc. ‧ When the on time of the timer function input is higher than the setting value of 03-37, the counter function output will change to on. ‧ When the off time of the timer function input is higher than the setting value of 03-38, the counter function output will change to off. ‧ The following figure shows an example

Figure 4.3. 49 Example of counter OFF delay

Brake release function: Must be used with the frequency arrival function, as shown in the figure below: When the inverter starts operating and the output frequency is greater than the 03-13 frequency detection threshold, and the output torque is greater than the 03-41 torque detection threshold, the brake will be released after delaying for the 03-42 braking action delay time.

Figure 4.3. 50 Example of using the brake release function with the frequency arrival function

It is recommended to use with the 11-43~11-46 start and stop frequency lock function, as shown in the figure below:

Timer function input;ON;ON;Timer function output;ON;ON;03-37;03-38;03-37;03-38. Conditions retained in pageprose; waveform geometry remains original.

Motor Speed(Output Frequency);Output Freq>03-13 andOutput Torque>03-41;Output Freq<03-13 orOutput Torque<03-41;t;DO03-11,03-12,03-28;set38Brake Release;03-42Brake Release delay time(two intervals). Separator glyphs betweenDOparameter numbers are degraded in source; individual numbers legible.

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Seconds andhours distinct; relationship not inferred.

Current, brake, output or pulse parameter definitions — PDF page 209

Source row Parameter Name Scope/options and unit
1 03- 41 Torque detection threshold 【0~150】%
2 03-42 Braking action delay out 【0.00~65.00】Sec

Timer delay definitions — PDF page 209

Source row Parameter Name Scope and unit
1 03- 37 Timer ON delay (DI/DO) 【0.0~6000.0】Sec
2 03-38 Timer OFF delay (DI/DO) 【0.0~6000.0】Sec
3 03- 54 Timer ON delay 【0~12】hour
4 03-55 Timer OFF delay 【0~12】hour

Manual — Brake frequency lock, reset modes and communication inputs — page 210

Manual reference: physical PDF page 210. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 51 Example of using the brake release function with the frequency lock function

When using the UP/DOWN function, the 03-43 parameter can be used to switch between the acceleration/deceleration time of the calculate frequency command (ex:△H1 (set frequency increase during acceleration) and △H2(set frequency increase during deceleration)).

After the emergency stop function (DI setting=14) is activated: (1) When 03-57=0: After removing the operation command and emergency stop command DI, the panel ES will disappear and ES resets automatically. (2) When 03-57=1: After removing the operation command and emergency stop command DI, the panel ES will not disappear, and an external reset command (DI setting=17) needs to be used to reset ES.

When communication register addresses need to be used to write multi-function terminal statuses, the corresponding terminals of 03-58 and 03-59 needs to be set as communication control functions.

Motor Speed(Output Frequency);Output Torque>03-41;Output Torque<03-41;11-43;11-44;11-45;11-46;t;DO03-11,03-12,03-28set38Brake Release;03-42Brake Release delay time(two intervals). Degraded separator glyphs retained by sourceimage; no invented engineering meaning.

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Current, brake, output or pulse parameter definitions — PDF page 210

Source row Parameter Name Scope/options and unit
1 03-43 UP/DOWN acceleration/deceleration selection [0] Acceleration/deceleration time 1 [1] Acceleration/deceleration time 2

Current, brake, output or pulse parameter definitions — PDF page 210

Source row Parameter Name Scope/options and unit
1 03-57 Emergency stop action setting [0] Automatic reset ES after stopped [1]ES reset command: DI

Current, brake, output or pulse parameter definitions — PDF page 210

Source row Parameter Name Scope/options and unit
1 03-58 Communication control S1~S4 type selection [xxx0b]: S1 external input[xxx1b]: S1 communication control [xx0xb]: S2 external input[xx1xb]: S2 communication control [x0xxb]: S3 external input[x1xxb]: S3 communication control [0xxxb]: S4 external input[1xxxb]: S4 communication control
2 03-59 Communication control S5~S7 type selection (Frame1 no S7) [xxx0b]: S5 external input[xxx1b]: S5 communication control [xx0xb]: S6 external input[xx1xb]: S6 communication control [x0xxb]: S7 external input[x1xxb]: S7 communication control

Manual — Analogue input types, ranges and functions — page 211

Manual reference: physical PDF page 211. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

004-External terminal analog input/output function group

Exact source conditions, associated procedures and model restrictions retained. No waveform geometry inferred.

Frame1noAI2restriction retained.

Source pairedAI1/AI2values orfunctionoptions retained byrow; Frame1noAI2.

Current, brake, output or pulse parameter definitions — PDF page 211

Source row Parameter Name Scope/options and unit
1 04- 01 AI1 signal scan filter time 【0.00~2.00】Sec
2 04- 02 AI1 gain 【0.0~1000.0】%
3 04- 03 AI1 bias voltage 【-100~100.0】%
4 04- 04 AI negative characteristic [0]: Disabled [1]: Enabled
5 04- 06 AI2 signal scan filter time 【0.00~2.00】Sec
6 04- 07 AI2 gain 【0.0~1000.0】%
7 04- 08 AI2 bias voltage 【-100.0~100.0】%

Analogue input parameter definition — PDF page 211

Source row Code Name
1 04- 00 AI input signal type (Frame1 no AI2)

04-00 signal-type options — PDF page 211

Source row Setting and source option
1 [0]: AI1 0~10V AI2 0~10V
2 [1]: AI1 0~10V AI2 4~20mA
3 [2]: Reserved
4 [3]: Reserved
5 [4]: AI1 4~20mA AI2 0~10V
6 [5]: AI1 4~20mA AI2 4~20mA

Analogue input parameter definition — PDF page 211

Source row Code Name
1 04- 05 AI2 function setting (Frame1 no AI2)

04-05 AI2function options — PDF page 211

Source row Setting and source option
1 [0]: Auxiliary frequency
2 [1]: Frequency gain
3 [2]: Frequency bias voltage
4 [3]: Voltage bias voltage
5 [4]: Acceleration/deceleration shortening coefficient
6 [5]: DC brake current
7 [6]: Overtorque detection threshold
8 [7]: Stall threshold during operation
9 [8]: Frequency lower limit
10 [9]: Jump frequency 4
11 [10]: Add to AI1
12 [11]: Forward torque limit
13 [12]: Negative torque limit
14 [13]: Regenerative torque limit
15 [14]: Positive/negative torque limit
16 [15]: Torque command/torque limit
17 [16]: Torque command/torque compensation
18 [17]: PTC overheat protection

Manual — Analogue configuration, gain/bias and source diagram conflicts — page 212

Manual reference: physical PDF page 212. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The usage methods of the 04-00 AI input signal type are as follows: For AI1 to use 0~10V, set the 04-00 parameter to 0 or 1. Adjust the SW3 on the control panel to V For AI1 to use 4~20mA, set the 04-00 parameter to 4 or 5, and adjust the SW3 on the control panel to I. For AI2 to use 0~10V, set the 04-00 parameter to 0 or 4, and adjust the SW4 on the control panel to V. For AI2 to use 4~20mA, set the 04-00 parameter to 1 or 5, and adjust the SW4 on the control panel to I. (1) Analog threshold adjustment inputs AI1 and AI2 (04-02, 04-03, 04-04, 04-07, 04-08) • For each different analog input AI1 and AI2, its corresponding gain and bias voltage should be listed separately. AI1 uses 04-02 and 04-03 for adjustment, AI2 uses 04-07 and 04-08 for adjustment. Refer to Figure 4.3.52 on analog input and related parameters.

Figure 4.3. 52 Analog input and related parameters

• Refer to Figure 4.3.53 on gain and bias voltage settings. Gain: Set the frequency reference that corresponds to the 10V or 20mA input as the maximum output frequency ratio (set the maximum output frequency 01-02 to 100%). Bias voltage: Set the frequency reference that corresponds to the 0V or 4mA input as the maximum output frequency ratio (set the maximum output frequency 01-02 to 100%).

Figure 4.3. 53 Incremental and bias voltage operations (used for frequency reference signal)

04-04(AI negative characteristic) It can be seen from the following negative characteristic curve that the corresponding frequency reference of the AI input 10V or 20mA input is used as the maximum output frequency ratio (set the maximum output frequency 01-02 to 100%), and the ratio will be presented in reverse.

+10V;Related Parameters;AI1:04-00(Level Selection),04-02(Gain),04-03(Bias);AI2:04-06(Level Selection),04-07(Function Selection),04-08(Gain),04-09(Bias);GND;AI1,AI2;V,I;SW3,SW4. AI1input labels physically fragmented:0 -;0-10V;.20mA;4-20mA/2-10V. AI2input labels:0-10V/0-20mA;4-20mA/2-10V. Literal fragments retained; no reconstruction of missing text.

Frequency Reference;200%;100%;Gain:200%;Gain:100%;TerminalAI1,AI2analog input;0V(4mA);10V(20mA);-100%;(a)Gain. Explicit labels only; no curve interpolation.

Frequency Reference;+100%;Bias=positive;Bias=0%;Bias=Negative;TerminalAI1,AI2analog input;Leftaxislabel has a separate minus glyph on the axis above10V;0V(4mA);10V(20mA);(b)Bias. Spatially separated minus/10V retained, no numeric inference.

Manual — Analogue filtering and AI2function matrix start — page 213

Manual reference: physical PDF page 213. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 54 AI negative characteristic (2) AI1 analog input filter time constant (04-01) (3) AI2 analog input filter time constant (04-06) • All analog inputs (AI1 and AI2) have individual digital filter with delay. This setting is used to filter the sudden fluctuations or noises in analog input signals. When this setting is increased, the system response will decrease, but protection against interference will increase. • The definition of filter time constant (setting range: 0.00 to 2.00 seconds) is the time required for the input step signal to reach 63% of its final value.

Figure 4.3. 55 Filter time constant

(4) Multi-function analog input function selection (04-05). • AI2 is a multi-function analog input terminal. Refer to Table 4.3.28 on function settings. Table 4.3. 28 Multi-function analog input function menu (04-05 setting)

100%;0%;0V(4mA);10V(20mA). Geometry retained in source.

%;100;63;Unfiltered signal;Filtered signal;t;Filter time constant(04-01). Explicit63%definition retained in sourceprose.

V/F+PG,SV,PMSVspecialprojectsonly. Thispacketrows0–3; laterrowscontinuePDF214.

Table4.3.28 AI2function control-mode matrix — PDF page 213

Source row Setting Name Screen display Description V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 0 Auxiliary reference frequency AUX.Freq Ref Maximum output frequency (01-02, Fmax) = 100% O O O O O O O
2 1 Reference frequency gain (FGAIN) Freq Ref Gain Total gain = AI1 = 04-02 * FGAIN O O O O O O O
3 2 Reference frequency bias voltage (FBIAS) Freq Ref Bias Total bias voltage = AI1 = 04-03 * FBIAS O O O O O O O
4 3 Output voltage bias voltage (VBIAS) Output Volt Bias Total output voltage = V/F curve voltage + VBIAS O O X X O O O

Manual — AI2 function matrix continuation and frequency gain — page 214

Manual reference: physical PDF page 214. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1). Auxiliary reference frequency (setting= 0). • When 00-05 is set to 1 (primary frequency provided by external control) and multi-speed command is set as the auxiliary frequency, the frequency command can be provided by the multi-function analog input AI2, and the maximum output frequency (01-02, Fmax) =100%. Please refer to page 4-100 for the description of multi-speed operation.

(2) Reference frequency gain (FGAIN) (setting=1). • When 04-05 is set to 1 (frequency reference gain), the multi-function analog input AI2 can be used to adjust the frequency reference gain of AI1. • The total frequency reference gain of terminal AI1 is the internal gain (04-02) × FGAIN. • The frequency reference value of AI1 is 100%. • Refer to Figure 4.3.56 on FGAIN adjustment.

Headers and special-project qualification continue from PDF213; V/F+PG,SV,PMSV only for special projects. Rows4–17 here; rows0–3 in immutable part17. No mode applicability inferred.

Table4.3.28 AI2 function control-mode matrix continuation — PDF page 214

Source row Setting Name Screen display Description V/F V/F+PG SLV SV PM SV PM SLV SLV2
1 4 Acceleration/deceleration time ratio (K) Tacc/Tdec Scaling Actual acceleration/deceleration time = acceleration/deceleration time / K O O O O O O O
2 5 DC brake current DC Inj Current Adjust the DC brake current (0~100%) according to the analog input, the inverter’s rated current = 100%. The DC brake current 07-07 is ineffective at this time. O O O O X X O
3 6 Overtorque detection threshold Over Tq Level Change the over-torque detected threshold according to the analog input. 08-15 is ineffective at this time. O O O O O O O
4 7 Operation duration Stall prevention threshold Run Stall Level Adjust the action threshold for stall prevention during operation (30%~200%) according to the analog input. The inverter’s rated current = 100%. O O X X X X O
5 8 Reference frequency lower limit Ref. Low Bound Adjust the frequency command lower limit (0~100%) according to the analog input. The maximum output frequency = 100%. The actual frequency command lower limit is based on the larger value between 00- 13 or the multi-function analog input as the frequency command lower limit. O O O O O O O
6 9 Jump frequency 4 Jump Freq 4 Jump frequency 4. 100% = Maximum output frequency O O O O O O O
7 10 Add to AI1 Add to AI1 Add to AI1. 100% = Maximum output frequency O O O O O O O
8 11 Forward torque limit Positive Tq Limit 100% = motor rated torque X X O O O O X
9 12 Negative torque limit Negative Tq Limit 100% = motor rated torque X X O O O O X
10 13 Regenerative torque limit Regen. Tq Limit 100% = motor rated torque X X O O O O X
11 14 Positive/negative torque limit +/- Tq Limit 100% = motor rated torque X X O O O O X
12 15 Torque reference/torque limit of speed control Tref/Tq Limit 100% = motor rated torque X X X O O X X
13 16 Torque reference/torque compensation of speed control Tq Compensation 100% = motor rated torque X X O O O X X
14 17 PTC overheat protection PTC overheat Stall This function uses a sensor with a Positive Temperature Coefficient (PTC) thermal resistance characteristic built into the motor to perform motor overheat protection. O O O O O O O

Manual — Frequency gain example and bias formula conflict — page 215

Manual reference: physical PDF page 215. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 56 Frequency gain adjustment . Example: When the internal gain of AI1 (04-02) is set to 100% and 5V for AI2 (such as FGAIN=50%), the frequency reference of terminal AI1 will be 50%, as shown in Figure 4.3.57 below.

Figure 4.3. 57 Frequency reference gain adjustment (example) (3) Frequency reference bias voltage (FBIAS) (setting = 2). • When 04-05 is set to 2 (frequency reference bias voltage, FBIAS), the multi-function analog input AI2 can be used to adjust the frequency reference bias voltage of AI1. • The total frequency reference bias voltage of terminal AI1 is the sum of the terminal AI1 and the internal bias voltage (04-03) of FBIAS (for example, the total bias voltage = 04-03 + FBIAS). • AI1 frequency reference value = 100%. Refer to Figure 4.3.58 below on FBIAS adjustment.

Figure 4.3. 58 Bias voltage adjustment

FGAIN;100%;0V(4mA);+10V(20mA);Terminal AI2 analog input. Printed labels only; no curve interpolation.

Frequency Reference;100%;50%;0%;0V;10V;04-02=100%;04-02×FGAIN=50%;Terminal AI1 input voltage. Source graphic only; no interpolated values.

FBIAS;100%;0V(4mA);10V(20mA);Terminal AI2 analog input.

Manual — Frequency bias example and voltage bias — page 216

Manual reference: physical PDF page 216. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example: When 04-02=100% (AI1 gain), 04-03=0% (AI1 bias voltage), and terminal AI2 is set to 3V, when the input terminal AI1 is 0V, the frequency reference of terminal AI1 will be 30%, as shown in Figure 4.3.59 below.

Figure 4.3. 59 Frequency reference bias voltage adjustment (example) (4) Output voltage bias voltage (VBIAS) (setting= 3). • When 04-05 is set to 3 (output voltage bias voltage), use the multi-function analog input AI2 to adjust the output voltage. • The total output voltage of the inverter is the sum of the boosted V/F curve and the VBIAS. • Maximum output voltage (01-03, Vmax) = 100%. • Refer to Figure 4.3.60 below on VBIAS adjustment.

Figure 4.3. 60 Bias voltage adjustment

Frequency Reference;100%;30% Bias;0V;10V;Terminal AI1 input voltage. Brace identifies bias graphically; no curve reconstruction.

VBIAS;100%;0V(4mA);10V(20mA);Terminal AI2 analog input.

Manual — Acceleration ratio and DC brake current — page 217

Manual reference: physical PDF page 217. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(5) Acceleration/deceleration time ratio (K) (setting= 4). • When 04-05 is set to 4 (acceleration/deceleration time ratio), use the multi-function analog input AI2 to adjust the acceleration/deceleration time. • The actual acceleration/deceleration time is as described below:

• Acceleration/deceleration time (00-14~00-17, 00-21~00-24) = 100%. • The acceleration/deceleration time ratio is as shown in Figure 4.3.61 below.

Figure 4.3. 61 Acceleration/deceleration time ratio operation (6) DC brake current (setting=5). • When 04-05 is set to 5 (DC brake current), use the multi-function analog input AI2 to adjust the DC brake current. • Inverter’s rated current=100%. • The setting value of the DC brake current 07-07 is off. • DC brake current adjustment is as shown in Figure 4.3.62 below.

Figure 4.3. 62 DC brake current adjustment

Actual acceleration/deceleration time = [actual acceleration/deceleration (00-14~00-17,00-21~00-24)] / K. Literal numerator wording retained; bracket andslash represent the printed fraction, not an inferred formula.

Upper graph:K;10;1;0V(4mA);1;2;3;4;5;6;7;8;9;10V(20mA);Terminal AI2 analog input. Lower graph:Real Accel/Decel time;100%;Terminal AI2 analog input. Printed labels only; no curve interpolation or unprinted coordinates.

DC Injection Braking Current;100%;0V(4mA);10V(20mA);Terminal AI2 analog input.

Manual — Overtorque detection and operation stall thresholds — page 218

Manual reference: physical PDF page 218. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(7) Overtorque detection threshold (setting=6).* (V/F+PG, SV and PMSV are only for special projects • When 04-05 is set to 6 (overtorque detection threshold), use the multi-function analog input AI2 to adjust the overtorque detection threshold. • 100% inverter rated current (V/F or V/F+PG control mode). • 100% motor rated torque (SLV or SV control mode). • If the multi-function analog input is used to adjust the overtorque detection threshold, the internal overtorque detection threshold (08-15) setting becomes invalid. Refer to Figure 4.3.63 below.

Figure 4.3. 63Overtorque detection threshold adjustment (8) Stall prevention threshold during operation (setting=7). • When 04-05 is set to 7 (stall prevention threshold during operation), use the multi-function analog input AI2 to adjust the stall prevention threshold during operation. • Inverter’s rated current = 100%. • When AI2 is assigned (04-05=7) and parameter 08-03 (stall prevention threshold during operation) is set, the lower value of the two will be used as the stall prevention threshold during operation. • Application example: If the motor capacity is smaller than the inverter capacity, and operation was performed using the default factory setting and the motor stalled, use the multi-function analog input AI2 to reduce the stall prevention threshold during operation. Refer to Figure 4.3.64 below.

Figure 4.3. 64 Adjustment of stall prevention threshold during operation

Detection Level;100%;0V(4mA);10V(20mA);Terminal AI2 analog input.

Stall Prevention Level;200%;30%;0V(4mA);1.5V(6.4mA);10V(20mA);Terminal AI2 analog input. Printed labels only; no extra curve points.

Manual — Reference frequency bound and jump frequency — page 219

Manual reference: physical PDF page 219. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(9) Reference frequency lower limit (setting=8). • When 04-07 is set to 8 (frequency reference lower limit), use the multi-function analog output AI2 to adjust the frequency reference lower limit. • Maximum output frequency (Fmax, 01-02) = 100%. • Determine the actual lower limit with the setting value of 00-13 (frequency reference lower limit) and the corresponding maximum value of the multi-function analog input AI2. Refer to Figure 4.3.65 below.

Figure 4.3. 65 Frequency reference lower limit adjustment (10) Jump frequency 4 (setting=9). • When 04-05 is set to 9 (jump frequency 4), use the multi-function analog input AI2 to adjust the jump frequency 4. • Maximum output frequency (01-02, Fmax) = 100%. • When 11-08 to 11-10 is set to 0.0Hz, the jump frequency function is off. Refer to Figure 4.3.66 below.

Figure 4.3. 66 Jump frequency 4 setting operation

Frequency Reference Lower Bound;100%;0V(4mA);10V(20mA);Terminal AI2 analog input. Printed labels only.

Jump Frequency4;100%;0V(4mA);10V(20mA);Terminal AI2 analog input;(a) Jump Frequency4 Adjustment.

Output Frequency;Jump Frequency Reference;Jump Freq4(Using analog input);Jump Freq3(11-10);Jump Freq2(11-09);Jump Freq1(11-08);(b) Jump Frequency Hierarchy. Geometry andhysteresis not reconstructed.

Manual — AI2 additions, torque/PTC and AO1 options — page 220

Manual reference: physical PDF page 220. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(11) Add to terminal AI1 (setting=10). • When 04-05 (AI2 function selection) is set to 10 (add to AI1), it is the same as adding the frequency reference value of the AI2 analog input signal to AI1 as a bias voltage. Refer to Figure 4.3.67 below.

Figure 4.3. 67 Add to AI1 as a bias voltage operation Example: When 04-02 (AI1 gain)=100%, 04-03 (AI2 gain)=0%, and terminal AI2 is set to 2V and the input terminal AI1 as 0V, the frequency reference of AI1 will be 20%.

(12) Forward torque limit (setting=11). (13) Negative torque limit (setting=12). (14) Regenerative torque limit (setting=13). (15) Forward/negative torque limit (setting=14). • For more details on torque limit, please refer to the parameter 21-torque function group. (16) Torque reference/torque limit during speed control (setting=15). (17) Torque reference/torque compensation during speed control (setting=16). • For more details on the torque control function, please refer to the parameter 21-torque function group. (18) This function uses a sensor with a Positive Temperature Coefficient (PTC) thermal resistance characteristic built into the motor to perform motor overheat protection. (setting=17). • Please refer to the descriptions of parameters 08-42~08-44 for detailed settings.

Frequency Reference Bias;100%;0V(4mA);10V(20mA);Terminal AI2 analog input.

Full option list below. Frame2 and above reserved for specified options only.

Each option retained with its own model restriction; options11,12,17,18 Frame2 and above reserved.

AO1 function parameter — PDF page 220

Source row Code Name
1 04-11 AO1 function setting

04-11 AO1 function options — PDF page 220

Source row Setting and source option
1 [0]: Output frequency
2 [1]: Frequency command
3 [2]: Output voltage
4 [3]: DC voltage
5 [4]: Output current
6 [5]: Output power
7 [6]: Motor speed
8 [7]: Output power factor
9 [8]: AI1 input
10 [9]: AI2 input
11 [10]: Torque command
12 [11]: q-axis current (Frame2 and above are reserved)
13 [12]: d-axis current (Frame2 and above are reserved)
14 [13]: Speed deviation
15 [14]: Reserved
16 [15]: ASR output
17 [16]: Reserved
18 [17]: q-axis voltage (Frame2 and above are reserved)
19 [18]: d-axis voltage (Frame2 and above are reserved)
20 [19]: Reserved
21 [20]: Reserved
22 [21]: PID input
23 [22]: PID output
24 [23]: PID target value
25 [24]: PID feedback value
26 [25]: Soft start output frequency
27 [26]: PG feedback
28 [27]: Reserved
29 [28]: Communication control

Manual — AO gain, bias and shared function parameters — page 221

Manual reference: physical PDF page 221. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Missing printed units are not inferred.04-16 explicitly refers to04-11 options.

Analogue output andfilter parameter definitions — PDF page 221

Source row Parameter Name Scope andprinted unit
1 04-12 AO1 gain 【0.0~1000.0】%
2 04-13 AO1 bias voltage 【-100.0~100.0】%
3 04-16 AO2 function setting The scope and definition are the same as 04-11
4 04-17 AO2 gain 【0.0~1000.0】%
5 04-18 AO2 bias voltage 【-100.0~100.0】%

Manual — AO adjustment and output control-mode matrix — page 222

Manual reference: physical PDF page 222. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Refer to Figure 4.3.68 below on analog output and related parameters.

Figure 4.3. 68 Analog output and related parameters (1). Analog threshold adjustment for analog outputs AO1 and AO2 (04-12, 04-13 and 04-17, 04-18). • Use 04-12 to adjust AO1 and 04-17 to adjust the AO2 gain, and use 04-13 to adjust AO1 and 04-18 to adjust the AO2 bias voltage to use as the output voltage or current to adjust the multi-function analog output terminals AO1 and AO2. • Set the gain adjustment to make the output (10V) correspond 100% with the monitor option output. • For the bias voltage, its output characteristic will mutually cancel the ratio that corresponds 10V to 100%. • Refer to Figure 4.3.69 for analog output level adjustment.

Figure 4.3. 69 Analog output threshold adjustment (2). Analog output terminal function selection (04-11 and 04-16). • Refer to Table 4.3.29 for function options. Table 4.3. 29 Multi-function analog output terminal function selection (04-11 and 04-16)

Related parameters;AO1:04-11(AO1 function setting),04-12(AO1 gain value),04-13(AO1 bias value);AO2:04-16(AO2 function setting),04-17(AO2 gain value),04-18(AO2 bias value). No wiring geometry inferred.

Analog Output Signal;10V(or20mA)×Gain;(20mA)10V;Bias;(4mA)0V;0%;100%;Monitored items. Printed labels only; no curve interpolation.

VF+PG,SV,PMSV special-project modes only; Frame2+ restrictions from04-11 option list remain applicable. Blank cells andliteral dash retained separately.

Table4.3.29 analogue output mode matrix — PDF page 222

Source row 04-11/04-16 setting Function screen display Monitor parameter group12 VF VF+PG SLV SV PM SV PM SLV SLV2
1 0 Output Freq 12-17 O O O O O O O
2 1 Freq Ref 12-16 O O O O O O O
3 2 Output Voltage 12-19 O O O O O O O
4 3 DC Voltage 12-20 O O O O O O O
5 4 Output Current 12-18 O O O O O O O
6 5 Output KW 12-21 O O O O O O O
7 6 Motor Speed 12-22 O O O O O O O
8 7 Output PF 12-23 O O O O O O O
9 8 AI1 Input 12-25 O O O O O O O
10 9 AI2 Input 12-26 O O O O O O O
11 10 Torque Ref 12-27 X X O O O O X
12 11 Current Iq 12-28 X X O O O O X
13 12 Current Id 12-29 X X O O O O X
14 13 Speed Deviation 12-30 X X X O O X X
15 14 Reserved ⟦blank source cell⟧ X X X X X X X
16 15 ASR Output 12-32 X O X O O X X
17 16 Reserved - X X X X X X X
18 17 Voltage Ref Vq - X X O O O O X
19 18 Voltage Ref Vd - X X O O O O X
20 19 Reserved - X X X X X X X
21 20 Reserved - X X X X X X X

Manual — AO matrix continuation, output types and filters — page 223

Manual reference: physical PDF page 223. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

For standard H & C type: • When using parameter 04-19 AO2 analog output signal type, it must be used with the setting of the SW6 switch on the control panel. • When parameter 04-19 is set to 0 and AO2 is 0~10V, the SW6 switch of the control panel is V, and the AO2 output signal type is voltage. • When parameter 04-19 is set to 1 and AO2 is 4~20V, the SW6 switch of the control panel is I, and the AO2 output signal type is current.

For advanced E & G type: • When using parameter 04-19 AO analog output signal type, it must be used with the setting of the SW1 and SW2 switches on the control panel. • When parameter 04-19 is set to 0 and AO1 is 0~10V, the SW1 switch of the control panel is V, and the AO1 output signal type is voltage. When AO2 is 0~10V, the SW2 switch of the control panel is V, and the AO2 output signal type is voltage. • When parameter 04-19 is set to 1 and AO1 is 0~10V, the SW1 switch of the control panel is V, and the AO1 output signal type is voltage. When AO2 is 4~20mA, the SW2 switch of the control panel is I, and the AO2 output signal type is current. • When parameter 04-19 is set to 2 and AO1 is 4~20V, the SW1 switch of the control panel is I, and the AO1 output signal type is current. When AO2 is 0~10V, the SW2 switch of the control panel is V, and the AO2 output signal type is voltage. • When parameter 04-19 is set to 3 and AO1 is 4~20V, the SW1 switch of the control panel is I, and the AO1 output signal type is current. When AO2 is 4~20mA, the SW2 switch of the control panel is I, and the AO2 output signal type is current.

This setting is used to filter the sudden fluctuations in analog output signals. When this setting is increased, the system response will decrease, but protection against interference will increase.

When the frequency source is AI1 and Keypad VR, 04-24 can be adjusted to filter the displayed frequency

Missing printed units are not inferred.04-16 explicitly refers to04-11 options.

VF+PG,SV,PMSV special-project modes only; Frame2+ restrictions from04-11 option list remain applicable. Blank cells andliteral dash retained separately.

Code cell visibly blank. Subsequent prose cites04-19; blank retained.

Four settings0–3. Source prose switches and4~20V conflicts preserved separately.

Analogue output andfilter parameter definitions — PDF page 223

Source row Parameter Name Scope andprinted unit
1 04-20 AO signal scan filter time 【0.00~0.50】Sec

Analogue output andfilter parameter definitions — PDF page 223

Source row Parameter Name Scope andprinted unit
1 04-24 Frequency display filter 【0.00~3.00】
2 04-25 AI1 filter parameter 【0.00~3.00】

Table4.3.29 analogue output mode matrix — PDF page 223

Source row 04-11/04-16 setting Function screen display Monitor parameter group12 VF VF+PG SLV SV PM SV PM SLV SLV2
1 21 PID Input 12-36 O O O O O O O
2 22 PID Output 12-37 O O O O O O O
3 23 PID Setpoint 12-38 O O O O O O O
4 24 PID Feedback 12-39 O O O O O O O
5 25 Output Freq (SFS) - O O O O O O O
6 26 PG Feedback 12-33 X O X O O X X
7 27 Reserved - X X X X X X X
8 28 Comm Control - O O O O O O O

AO output signal type header — PDF page 223

Source row Code as printed Name
1 ⟦blank source cell⟧ AO output signal type

AO output signal type options — PDF page 223

Source row Setting andpaired output ranges
1 【0】: AO1 0~10V ; AO2 0~10V
2 【1】: AO1 0~10V ; AO2 4~20mA
3 【2】: AO1 4~20mA ; AO2 0~10V
4 【3】: AO1 4~20mA ; AO2 4~20mA

Manual — Average filters and multi-speed parameter ranges — page 224

Manual reference: physical PDF page 224. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

fluctuations. When the frequency source is AI1, 04-25 can be adjusted to filter AI1 signals.

04-26: The average filtering count for AI1 sampling is once every 4ms. 04-27: The average filtering count for the displayed value of the output frequency is once every 4ms.

05-Multi-speed function group

*: (When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz) • When 05-00=[0], multi-speed (0~ 15) segment 16 speed acceleration/deceleration times are both determined by 00-14~00-17/00-21~00-24. • When 05-00=[1], multi-speed (0~ 15) 16 segment speed acceleration/deceleration times are calculated according to 05-17~05-48, and not determined by 00-14~00-17/00-21~00-24. Function Description: ➢ The formula for calculating acceleration/deceleration times during operation is: The denominator

04-26/27 source range count0–255; sampling period described inprose, not rangeunit.

Repeated scope cells reference same physical shared sourceheader: frequency0.0–599.00Hz for05-01–16; time0.0–6000.0Sec for05-17–48. Above300Hzfrequency resolution0.1Hz footnote retained.

Averagefilter andmulti-speed parameter definitions — PDF page 224

Source row Parameter Name Scope/options
1 04-26 AI1 value average filter 【0 ~255】
2 04-27 Output frequency display value average filter 【0 ~255】

Averagefilter andmulti-speed parameter definitions — PDF page 224

Source row Parameter Name Scope/options
1 05- 00 Multi-speed acceleration/deceleration mode selection [0]: The acceleration/deceleration time of the segment speed is set by acceleration/deceleration times 1~4 [1]: The acceleration/deceleration times are set independently

Multi-speed frequency andacceleration/deceleration parameters — PDF page 224

Source row Parameter Name Shared header scope andunit
1 05-01 *Segment 0 speed frequency setting 【0.0~599.00】 Hz
2 05-17 Multi-speed 0 acceleration time setting 【0.0~6000.0】 Sec
3 05-33 Multi-speed 8 acceleration time setting 【0.0~6000.0】 Sec
4 05-02 *Segment 1 speed frequency setting 【0.0~599.00】 Hz
5 05-18 Multi-speed 0 deceleration time setting 【0.0~6000.0】 Sec
6 05-34 Multi-speed 8 deceleration time setting 【0.0~6000.0】 Sec
7 05-03 *Segment 2 speed frequency setting 【0.0~599.00】 Hz
8 05-19 Multi-speed 1 acceleration time setting 【0.0~6000.0】 Sec
9 05-35 Multi-speed 9 acceleration time setting 【0.0~6000.0】 Sec
10 05-04 *Segment 3 speed frequency setting 【0.0~599.00】 Hz
11 05-20 Multi-speed 1 deceleration time setting 【0.0~6000.0】 Sec
12 05-36 Multi-speed 9 deceleration time setting 【0.0~6000.0】 Sec
13 05-05 *Segment 4 speed frequency setting 【0.0~599.00】 Hz
14 05-21 Multi-speed 2 acceleration time setting 【0.0~6000.0】 Sec
15 05-37 Multi-speed 10 acceleration time setting 【0.0~6000.0】 Sec
16 05-06 *Segment 5 speed frequency setting 【0.0~599.00】 Hz
17 05-22 Multi-speed 2 deceleration time setting 【0.0~6000.0】 Sec
18 05-38 Multi-speed 10 deceleration time setting 【0.0~6000.0】 Sec
19 05-07 *Segment 6 speed frequency setting 【0.0~599.00】 Hz
20 05-23 Multi-speed 3 acceleration time setting 【0.0~6000.0】 Sec
21 05-39 Multi-speed 11 acceleration time setting 【0.0~6000.0】 Sec
22 05-08 *Segment 7 speed frequency setting 【0.0~599.00】 Hz
23 05-24 Multi-speed 3 deceleration time setting 【0.0~6000.0】 Sec
24 05-40 Multi-speed 11 deceleration time setting 【0.0~6000.0】 Sec
25 05-09 *Segment 8 speed frequency setting 【0.0~599.00】 Hz
26 05-25 Multi-speed 4 acceleration time setting 【0.0~6000.0】 Sec
27 05-41 Multi-speed 12 acceleration time setting 【0.0~6000.0】 Sec
28 05-10 *Segment 9 speed frequency setting 【0.0~599.00】 Hz
29 05-26 Multi-speed 4 deceleration time setting 【0.0~6000.0】 Sec
30 05-42 Multi-speed 12 deceleration time setting 【0.0~6000.0】 Sec
31 05-11 *Segment 10 speed frequency setting 【0.0~599.00】 Hz
32 05-27 Multi-speed 5 acceleration time setting 【0.0~6000.0】 Sec
33 05-43 Multi-speed 13 acceleration time setting 【0.0~6000.0】 Sec
34 05-12 *Segment 11 speed frequency setting 【0.0~599.00】 Hz
35 05-28 Multi-speed 5 deceleration time setting 【0.0~6000.0】 Sec
36 05-44 Multi-speed 13 deceleration time setting 【0.0~6000.0】 Sec
37 05-13 *Segment 12 speed frequency setting 【0.0~599.00】 Hz
38 05-29 Multi-speed 6 acceleration time setting 【0.0~6000.0】 Sec
39 05-45 Multi-speed 14 acceleration time setting 【0.0~6000.0】 Sec
40 05-14 *Segment 13 speed frequency setting 【0.0~599.00】 Hz
41 05-30 Multi-speed 6 deceleration time setting 【0.0~6000.0】 Sec
42 05-46 Multi-speed 14 deceleration time setting 【0.0~6000.0】 Sec
43 05-15 *Segment 14 speed frequency setting 【0.0~599.00】 Hz
44 05-31 Multi-speed 7 acceleration time setting 【0.0~6000.0】 Sec
45 05-47 Multi-speed 15 acceleration time setting 【0.0~6000.0】 Sec
46 05-16 *Segment 15 speed frequency setting 【0.0~599.00】 Hz
47 05-32 Multi-speed 7 deceleration time setting 【0.0~6000.0】 Sec
48 05-48 Multi-speed 15 deceleration time setting 【0.0~6000.0】 Sec

Manual — Multi-speed timing formulas and example conditions — page 225

Manual reference: physical PDF page 225. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

is based on the maximum output frequency

➢ When 01-00=[F], the maximum output frequency=01-02 setting, when 01-00≠[F], the maximum output frequency =50.00 (or60.00/90.00/120.0/180.0) For example: 01-00≠[F] , 01- 02=[50] hz (maximum output frequency), 05- 02=[10] hz (multi-speed 0), 05-17=[5] s (acceleration time), 05-18=[20] s (deceleration time), then

➢ when 05-00=[1], there are two types of time setting modes For example: Set: 00-02=[1] (external terminal operation); terminal S1: 03-00=[0] (forward /stop); terminal S2: 03-01=[1] (reverse/stop); terminal S3: 03-02=[2] (segment speed1); terminal S4: 03-03=[3] (segment speed 2); terminal S5: 03- 03=[4] (segment speed 3);

*Segment speed 1 needs to confirm whether the AI2 function setting (04-05) is set to 0 auxiliary frequency. If it is set to auxiliary frequency, it will cause the frequency of segment speed 1 to be set as AI2 auxiliary frequency, and AI2 will determine its frequency value. To use the function of the normal segment speed 1, change the AI2 function setting to any function other than 0 (recommended value: set to 10 ADD to AI1).

Acceleration time for reaching the set frequency = [Acceleration time × set frequency of0group] / Maximum output frequency. Slash denotes printed fraction.

Deceleration time for reaching the set frequency = [Deceleration time × set frequency of0group] / Maximum output frequency. Slash denotes printed fraction.

Actual acceleration time ofspeed0 = [(Parameters05-17)×10(Hz)] / Parameters01-02 =1(s).

Actual deceleration time ofspeed0 = [(Parameters05-18)×10(Hz)] / Parameters01-02 =4(s).

Manual — Intermittent multi-speed timing example — page 226

Manual reference: physical PDF page 226. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Mode 1:

Figure 4.3. 70 Example of multi-speed timing (intermittent operation command) During intermittent operation command, the basis for the calculation of the acceleration/deceleration times of each segment speed (a~f)

Hz;Forward;T;05-01 Segment speed Command0;05-02 Segment speed Command1;05-03 Segment speed Command2;a;b;c;d;e;f;TerminalS1:RUN,STOP,RUN,STOP,RUN,STOP;TerminalS2:OFF;TerminalS3:ON,OFF;TerminalS4:OFF,ON. Printed label sequences only; no waveform-state ortransition interpolation.

Example:a=[(05-17)×(05-01)]/01-02;b=[(05-18)×(05-01)]/01-02;c=[(05-19)×(05-02)]/01-02. Fractions asprinted.

d=[(05-20)×(05-02)]/01-02.

e=[(05-21)×(05-03)]/01-02;f=[(05-22)×(05-03)]/01-02;Unit(sec).

Manual — Continuous multi-speed timing example — page 227

Manual reference: physical PDF page 227. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Mode 2:

Figure 4.3. 71 Example of multi-speed timing (continuous operation command) During continuous operation command, the basis for the calculation of the acceleration/deceleration times of each segment speed (a~h)

Hz;Forward;T;05-01 Speed command0;05-02 Speed command1;05-03 Speed command2;05-04 Speed command3;05-05 Speed command4;05-06 Speed command5;a;b;c;d;e;f;g;h;i;TerminalS1:ON,OFF,STOP;TerminalS2:OFF,ON;TerminalS3:OFF,ON,OFF,ON,OFF,ON,ON;TerminalS4:OFF,OFF,ON,ON,OFF,OFF,OFF;TerminalS5:OFF,OFF,OFF,OFF,ON,ON,OFF;17/18;19/20;21/22;23/24;25/26;27/28;19/20. Printed label sequences only; unlabelled strokes remain sourcegeometry.

Example:a=[(05-17)×(05-01)]/01-02;b=[(05-19)×((05-02)-(05-01))]/01-02.

c=[(05-21)×((05-03)-(05-02))]/01-02;d=[(05-24)×((05-03)-(05-04))]/01-02.

e=[(05-26)×(05-04)]/01-02;f=[(05-25)×(05-05)]/01-02;g=[(05-27)×(05-05)]/01-02.

h=[(05-27)×(05-06)]/01-02;i=[(05-19)×(05-06)]/01-02;Unit(sec).

Manual — Automatic operation modes, frequencies and times — page 228

Manual reference: physical PDF page 228. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

06-Automatic operation function group

The operating frequency for segment 0 is set through parameter 05-01

*: (When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz)

Exact source restart wording retained inoptions.

Single/continuouscycles andresume-speed orzero-segment conditions are distinct; awkward supplier phrasing retained.

Segment0frequency setby05-01; frequencies06-01–15 forsegments1–15. Operatingtimes06-16–31 forsegments0–15; no inferredmissingsegment frequency.

Automatic operation mode parameter — PDF page 228

Source row Parameter Name
1 06- 00 Automatic operation mode selection

06-00 automatic operation mode options — PDF page 228

Source row Setting andliteral source procedure
1 [0]: Disabled
2 [1]: Execute a single cycle of operation mode, then after stopping, it will continue to operate at the same speed before stopping
3 [2]: Continuous cycle operation mode, after it stopped, it will continue to operate with the speed before stopping
4 [3]: After a single cycle ends, it will continue operating with the last segment of operation speed, then after it stopped, it will continue operating with the speed before it stopped
5 [4]: Execute a single cycle operation mode, after it stopped, it will start operating from the zero segment speed
6 [5]: Continuous cycle operation mode, after it stopped, it will start operating from the zero segment speed
7 [6]: After a single cycle ends, continue operating using the final segment of operation speed, then after it stops, start operating from the zero segment speed

Automatic segment frequencies — PDF page 228

Source row Parameter Name Shared header scope andunit
1 06- 01 *Segment 1 operation frequency setting 【0.00~599.00】Hz
2 06- 09 *Segment 9 operation frequency setting 【0.00~599.00】Hz
3 06- 02 *Segment 2 operation frequency setting 【0.00~599.00】Hz
4 06- 10 *Segment 10 operation frequency setting 【0.00~599.00】Hz
5 06- 03 *Segment 3 operation frequency setting 【0.00~599.00】Hz
6 06- 11 *Segment 11 operation frequency setting 【0.00~599.00】Hz
7 06- 04 *Segment 4 operation frequency setting 【0.00~599.00】Hz
8 06- 12 *Segment 12 operation frequency setting 【0.00~599.00】Hz
9 06- 05 *Segment 5 operation frequency setting 【0.00~599.00】Hz
10 06- 13 *Segment 13 operation frequency setting 【0.00~599.00】Hz
11 06- 06 *Segment 6 operation frequency setting 【0.00~599.00】Hz
12 06- 14 *Segment 14 operation frequency setting 【0.00~599.00】Hz
13 06- 07 *Segment 7 operation frequency setting 【0.00~599.00】Hz
14 06- 15 *Segment 15 operation frequency setting 【0.00~599.00】Hz
15 06- 08 *Segment 8 operation frequency setting 【0.00~599.00】Hz

Automatic segment operation times — PDF page 228

Source row Parameter Name Shared header scope andunit
1 06- 16 Segment 0 speed operation time setting 【0.0~6000.0】Sec
2 06- 24 Segment 8 speed operation time setting 【0.0~6000.0】Sec
3 06- 17 Segment 1 speed operation time setting 【0.0~6000.0】Sec
4 06- 25 Segment 9 speed operation time setting 【0.0~6000.0】Sec
5 06- 18 Segment 2 speed operation time setting 【0.0~6000.0】Sec
6 06- 26 Segment 10 speed operation time setting 【0.0~6000.0】Sec
7 06- 19 Segment 3 speed operation time setting 【0.0~6000.0】Sec
8 06- 27 Segment 11 speed operation time setting 【0.0~6000.0】Sec
9 06- 20 Segment 4 speed operation time setting 【0.0~6000.0】Sec
10 06- 28 Segment 12 speed operation time setting 【0.0~6000.0】Sec
11 06- 21 Segment 5 speed operation time setting 【0.0~6000.0】Sec
12 06- 29 Segment 13 speed operation time setting 【0.0~6000.0】Sec
13 06- 22 Segment 6 speed operation time setting 【0.0~6000.0】Sec
14 06- 30 Segment 14 speed operation time setting 【0.0~6000.0】Sec
15 06- 23 Segment 7 speed operation time setting 【0.0~6000.0】Sec
16 06- 31 Segment 15 speed operation time setting 【0.0~6000.0】Sec

Manual — Automatic segment directions and exclusions — page 229

Manual reference: physical PDF page 229. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Automatic operation mode can be achieved by setting multi-segment operation frequency reference commands (05-01, 06-01~06-15), while linking the automatic operation mode time setting (06-16~06- 31). Automatic operation mode can be selected by setting (06-00). This automatic operation direction can be set using parameters 06-32~06-47. • Automatic operation mode is invalid while the functions mentioned below are enabled: 1. Frequency skipping function. 2. PID function. • Under automatic operation mode, the multi-speed reference commands 1~4 (03-00~03-07=2~5) of the external terminal are invalid.

Options0Stop,1Forward,2reverse shared by06-32–47; physicalsharedheaderreused withprovenance.

Automatic segment direction selection — PDF page 229

Source row Parameter Segment name Shared source options
1 06- 32 Segment 0 operation direction selection [0]: Stop [1]: Forward [2]: reverse
2 06- 40 Segment 8 operation direction selection [0]: Stop [1]: Forward [2]: reverse
3 06- 33 Segment 1 operation direction selection [0]: Stop [1]: Forward [2]: reverse
4 06- 41 Segment 9 operation direction selection [0]: Stop [1]: Forward [2]: reverse
5 06- 34 Segment 2 operation direction selection [0]: Stop [1]: Forward [2]: reverse
6 06- 42 Segment 10 operation direction selection [0]: Stop [1]: Forward [2]: reverse
7 06- 35 Segment 3 operation direction selection [0]: Stop [1]: Forward [2]: reverse
8 06- 43 Segment 11 operation direction selection [0]: Stop [1]: Forward [2]: reverse
9 06- 36 Segment 4 operation direction selection [0]: Stop [1]: Forward [2]: reverse
10 06- 44 Segment 12 operation direction selection [0]: Stop [1]: Forward [2]: reverse
11 06- 37 Segment 5 operation direction selection [0]: Stop [1]: Forward [2]: reverse
12 06- 45 Segment 13 operation direction selection [0]: Stop [1]: Forward [2]: reverse
13 06- 38 Segment 6 operation direction selection [0]: Stop [1]: Forward [2]: reverse
14 06- 46 Segment 14 operation direction selection [0]: Stop [1]: Forward [2]: reverse
15 06- 39 Segment 7 operation direction selection [0]: Stop [1]: Forward [2]: reverse
16 06- 47 Segment 15 operation direction selection [0]: Stop [1]: Forward [2]: reverse

Manual — Single-cycle and periodic automatic examples — page 230

Manual reference: physical PDF page 230. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example of automatic operation mode: (1) Single-cycle operation (06-00 = 1,4) Under specific settings, the inverter will perform a single-cycle operation and then stop.

Cycle Operation Parameter Setting

Figure 4.3. 72 Single-cycle automatic operation (stop) (2) Periodic operation (06-00 = 2,5) The inverter will repeat the same cycle periodically. It is the same setting as example 1.

Figure 4.3. 73 Periodic automatic operation

Freq.;50Hz;30Hz;15Hz;20Hz;05-01;06-01;06-02;06-15;20s;25s;30s;40s;06-16;06-17;06-18;06-31. Explicit labels only; belowaxis20Hz notsilentlysigned negative.

Freq.;50Hz;30Hz;15Hz;20Hz;two repeated sequences:05-01,06-01,06-02,06-03;20s,25s,30s,40s;06-16,06-17,06-18,06-19. Source diagram references retained separately fromstage15 example.

Example only, notfactorydefaults orcustomerconfiguration. Diagramreferences retained independently.

Cycle operation parameter example — PDF page 230

Source row Parameter Example value andcondition
1 06-00 = 1 (Single cycle automatic operation mode)
2 06-32~06-34 =1 (Stage 0 - 2 operation is forward )
3 06-47 = 2 (Stage 15 operation is reversed rotation)
4 06-35~06-46 = 0 (Frequency 3 - 14 is stop)
5 05-01 = 15Hz (Stage 0 operation frequency: 15Hz)
6 06-01 = 30Hz (Stage 1 operation frequency: 30Hz)
7 06-02 = 50Hz (Stage 2 operation frequency: 50Hz)
8 06-15 = 20Hz (Stage 15 operation frequency: 20Hz)
9 06-16 = 20sec (Stage 0 operation time: 20seconds)
10 06-17 = 25sec (Stage 1 operation time: 25seconds)
11 06-18 = 30sec (Stage 2 operation time: 30seconds)
12 06-31 = 40sec (Stage 15 operation time: 40seconds)

Manual — Final-speed operation and restart behavior — page 231

Manual reference: physical PDF page 231. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(3) Single-cycle automatic operation mode (06-00=3,6) The driver will continue operating with the speed of the final step (the final step must be placed on the segment 15 operation frequency). The other related parameters have the same settings as in example 1.

Figure 4.3. 74 Single-cycle automatic operation (continuous) 06-00 = 1 to 3: If the inverter stopped and then restarted, it will continue operating from the uncompleted step. = 4 to 6: If the inverter stopped and then restarted, it will start a new cycle of operation.

∙ The acceleration/deceleration time depends on the setting of 00-14 and 00-15 in automatic operation mode. ∙ If the setting values of 06-16 to 06-31 are all 0, the automatic operation mode will not start.

Freq.;50Hz;30Hz;15Hz;20Hz;05-01;06-01;06-02;06-15;20s;25s;30s;40s;06-16;06-17;06-18;06-31. Printed labels only; no additional waveformvalues.

06-00 Setting;1to3:Operation command,RUN,STOP,RUN;Output frequency;t.4to6:Operation command,RUN,STOP,RUN;Output frequency;A new cycle starts;t. Overall Output frequency label. Geometry remains original.

Manual — Power-loss restart and permitted malfunction list — page 232

Manual reference: physical PDF page 232. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

07-operation stop function group

When setting 07-00 to 1 instantaneously stop and then restart is effective, if there is temporary power outage, the inverter can automatically resume motor operation once power is reconnected. • 07-00=0: When the instantaneous power loss exceeds 8 milliseconds, a “UV” failure (primary circuit undervoltage) will be detected. • 07-00=1: If there is temporary power outage, after power is reconnected, the inverter will restart.

The automatic reset and restart function will restart the inverter when the inverter malfunctioned while operating. This function should only be used when it does not pose a safety risk or cause possible damage to the equipment. The table below summarizes contents on restarting after failures; if the inverter malfunctioned during operation, the inverter will restart according to the speed search method selected. If the malfunction is not in the table below, then the restart after malfunction function cannot be used. Table 4.3. 30 Descriptions on restarting after malfunction contents

Note 1: The failure restart function includes the instantaneous stop and restart function and automatic reset and restart function. Note 2: Please refer to Chapter Five Troubleshooting and Diagnosis for details on failure messages. Note 3: Please refer to the speed search function (07-19~07-23) on the selection of speed search methods

Restart safety conditions andfailure exclusions retained inprose; notengineering recommendation.

Sharedparameter/count cells repeated perexplicitfault; twofaultcolumns independent list order. No rowwisepairing inferred betweenleft/right faults. Unlistedmalfunctions excluded bysource.

Operation stop andrestart parameters — PDF page 232

Source row Parameter Name Scope/options andprinted unit
1 07- 00 Instantaneously stop and restart selection [0]: Instantaneously stop and restart ineffective [1]: Instantaneously stop and restart effective
2 07- 01 Automatic reset restart time 【0~7200】 Sec
3 07- 02 Automatic reset restart count 【0~10】

Table4.3.30 restartable failures — PDF page 232

Source row Parameter name Failure content Number ofrestarts
1 07-00 instantaneously stop and restart selection UV (undervoltage) Unlimited times
2 07-01 automatic reset and restart time 07-02 automatic reset and restart count OC (over-current) According to parameter 07- 02
3 07-01 automatic reset and restart time 07-02 automatic reset and restart count OCA (over-current during acceleration) According to parameter 07- 02
4 07-01 automatic reset and restart time 07-02 automatic reset and restart count OCC (over-current during constant speed) According to parameter 07- 02
5 07-01 automatic reset and restart time 07-02 automatic reset and restart count OCd (over-current during deceleration) According to parameter 07- 02
6 07-01 automatic reset and restart time 07-02 automatic reset and restart count OL1 (motor overload) According to parameter 07- 02
7 07-01 automatic reset and restart time 07-02 automatic reset and restart count UT (under-torque detection) According to parameter 07- 02
8 07-01 automatic reset and restart time 07-02 automatic reset and restart count IPL (input phase loss) According to parameter 07- 02
9 07-01 automatic reset and restart time 07-02 automatic reset and restart count GF (grounding fault) According to parameter 07- 02
10 07-01 automatic reset and restart time 07-02 automatic reset and restart count OV (over-voltage) According to parameter 07- 02
11 07-01 automatic reset and restart time 07-02 automatic reset and restart count OL2 (Frequency converter overload) According to parameter 07- 02
12 07-01 automatic reset and restart time 07-02 automatic reset and restart count OT (over-torque detection) According to parameter 07- 02
13 07-01 automatic reset and restart time 07-02 automatic reset and restart count OPL (output phase loss) According to parameter 07- 02
14 07-01 automatic reset and restart time 07-02 automatic reset and restart count CF07 (SLV parameter setting abnormal) According to parameter 07- 02
15 07-01 automatic reset and restart time 07-02 automatic reset and restart count CF08 (PMSLV parameter setting abnormal) According to parameter 07- 02

Manual — Restart count, intervals, warnings and power-on start — page 233

Manual reference: physical PDF page 233. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1) Automatic reset and restart count (07-02) If the automatic reset and restart count reached the number of times set in parameter 07-02, the inverter will stop operating. Please troubleshoot first and then restart the inverter manually. The automatic reset and restart count will be reset to 0 under the following circumstances. a. No errors occurred after 10 minutes of restarting. b. Failure cleared input received after the protection action started and confirmed the failure. (For example: The reset/left button was pressed or failure cleared terminal was activated). c. Switching power on and off.

. Note: To output an automatic restart signal to one of the multi-function digital output, R1A-R1C, DO1 or DO2, please set the corresponding parameters 03-11, 03-12 and 03-28.

Automatic reset and restart operation: a. When failure message is detected, the failure message will be displayed on the digital operator. b. The inverter will enter free-run stop status, and after the minimum cut-ff time (07-18) and speed search delay time (07-22) have passed, the inverter will restart the program and execute speed search automatically. c. If the failure still was not eliminated, when the total failure count exceeded the automatic reset and restart count (07-02), the automatic reset and restart function will not execute and the inverter will stop outputting at this time. The failure contact point will activate. . Please refer to Figure 4.3.75 below automatic reset and restart operation

Figure 4.3. 75 Automatic reset and restart operation (2) Automatic reset and restart time (07-01) The instantaneous stop and restart time is the same as the automatic reset and restart time. . When 07-01<07-18, the automatic restart interval is set by 07-18. . When 07-01>07-18, the automatic restart interval is set by 07-01. . The automatic restart interval is the larger number between the minimum cut-off time (07-18) and the automatic reset and restart time (07-01), plus the speed search delay time (07-22). . Refer to Figure 4.3.76 automatic restart interval.

Figure 4.3. 76 Automatic restart interval Important - Using the automatic restart function too frequently will damage the inverter.

Fault Message;Output Frequency;t;t;07-18+07-22. Source timingdiagram only; no extra elapsedvalues inferred.

1;2;3;4;5;6;7;8;9;10;07-02;07-01+07-22 or07-18+07-22. Source labels only; no unprintedpulsewidths inferred.

Restart safety conditions andfailure exclusions retained inprose; notengineering recommendation.

Operation stop andrestart parameters — PDF page 233

Source row Parameter Name Scope/options andprinted unit
1 07- 04 Start directly after power on [0]: When the external operation command is valid, start directly after power is supplied [1]: When external operation command is valid, do not start directly after power is supplied
2 07- 05 Start delay directly after power on 【1.0~300.0】 Sec

Manual — Power-on start safety and braking threshold — page 234

Manual reference: physical PDF page 234. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1) Start directly after power on (07-04) 07-04=[0] If when power is connected, the operation switch is at the on status, the inverter will start automatically. 07-04=[1] If when power is connected, the operation switch is at the off status, it cannot start and STP1 will start flashing at this time. The operation switch needs to be turned off first, and then reconnect the power in order to start. (2) Start delay directly after power on (07-05) When 07-04=[0], if power is connected, start directly after power on will start counting the delay time set in 07- 05 and start operating after the time is reached. ! Danger: ➢ When 07- 04=[0] and the inverter is set to external operation (00- 02/00- 03=[1]), if power is connected and the operation switch is at the on status, the inverter will start automatically. It is recommended for customers to switch off the power switch and operation switch while power is disconnected so that the inverter will not operate directly and cause harm to personnel and machines when power is resumed. ➢ When 07- 04=[1] and the inverter is set to external operation (00- 02/00- 03=[1]), if power is connected and the operation switch is at the on status, it cannot start and STP1 will start flashing at this time. The operation switch must first be turned off and the start delay directly after power on timer must finish counting down, then connect the power in order to start up.

Brake related operations may vary according to the different control modes (00-00). Please refer to the descriptions below on related operation programs. • When the control mode is VF, VF+PG, SLV and SLV2 (00-00 = 0, 1, 2, 6) Startup will execute the DC brake first according to the time set in 07-16. When deceleration stops, parameters 07-06 and 07-08 can be used to set the DC brake start frequency while stopping and the DC brake time while stopping. When the output frequency during deceleration is lower that the setting value of 07-06, DC brake will be performed according to the time set in 07-08.

Figure 4.3. 77 Brake actions for VF, VF+PG, SLV and SLV2

(Note) When 07-06 < 01-08, DC brake will start from the frequency set in 01-08. * (V/F + PG, SV and PMSV are only for special projects

Output frequency; DC brake at startup and stop; 07-06 (Brake start frequency) or 01-08 (Fmin); Time; 07-16; 07-08. Source labels only; no inferred time or waveform geometry.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Stopping, power and speed-search parameters — PDF page 234

Source row Parameter Name Scope/options and printed unit
1 07- 06 Brake start frequency [0.0~10.0] Hz

Manual — PMSLV and vector-mode braking sequences — page 235

Manual reference: physical PDF page 235. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• When the control mode is PMSLV (00-00=5), parameters 07-34 and 07-16 can be used to set the short-circuit brake time during startup and DC brake time during startup respectively. The braking action during startup executes the short-circuit brake according to the time set in 07-34 first, and then executes the DC brake according to the time set in parameter 07-16. When deceleration stops, parameters 07-35 and 07-08 can be used to set the short-circuit brake time while stopping and DC brake time while stopping respectively. When the output frequency during deceleration is lower than 07-06, short-circuit brake will be executed first according to the time set in 07-35, and the execute DC brake according to the time set in 07-08 (if 07-06 < 01-08, the braking function will start being executed from the frequency set in 01-08). Detailed action program is as shown in Figure 4.3.78. Whether starting or stopping, the DC brake current threshold is set by parameter 07-07 with the rated current of the inverter at 100%. In addition, if the DC brake current threshold set by 07-07 exceeds the rated current value of the motor, the DC brake current threshold will be limited to the rated value of the motor. Whether starting or stopping, the short-circuit brake current limit is set by parameter 07-36 with the rated current of the motor at 100%.

Figure 4.3. 78 PMSLV braking action (Note) When 07-06 < 01-08, short-circuit brake starts from the frequency set in 01-08.

• When the control mode is SV and PMSV (00-00=3, 4) Startup will execute zero-speed operation first according to the time set in 07-16. When deceleration stops, parameters 07-06 and 07-08 can be used to set the zero-speed operation start frequency while stopping and the zero-speed operation time while stopping. When the output frequency during deceleration is lower that the setting value of 07-06, zero-speed operation will be performed according to the time set in 07-08.

Figure 4.3. 79 SV and PMSV braking action (Note) When 07-06 < 01-08, zero-speed operation will start from the frequency set in 01-08.

Output frequency; Short-circuit brake and DC brake at startup and stop; 07-06 (Brake start frequency) or 01-08 (Fmin); Time; 07-34; 07-16; 07-35; 07-08. Source sequence labels only.

Output frequency; Zero-speed operation at startup and stop; 07-06 (Brake start frequency) or 01-08 (Fmin); Time; 07-16; 07-08. Source labels only.

Manual — DC braking current and durations — page 236

Manual reference: physical PDF page 236. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• If DC voltage is applied on an operating motor, the motor will generate braking torque. This is DC brake, and parameters 07-06 to 07-08 and 07-16 are used to configure these settings. • Executing the speed search function should release the DC brake. • The DC brake function can be started by supplying DC current to the motor. This occurs during DC brake time before startup 07-16 and the DC brake time while stopping 07-08. • For the starting point of the DC brake time 07-16, set the DC brake activation time when the motor starts. This will prevent the load from driving the motor and generating a “windmill effect”, ensuring that the motor will stop. • If 07-16 is set to 0 (release brake during startup), the inverter will start with the minimum output frequency. • For the DC brake time while stopping 07-08, set the DC brake operation time when the motor stops. If 07-08 is set to 0 (DC brake during shutdown), when the output frequency is smaller than the DC brake start frequency 07-06, the inverter output will turn off and the DC brake will start. • If the DC brake start frequency 07-06 set is lower than the minimum output frequency 01-08, when the output frequency is smaller than the minimum output frequency 01-08, the DC brake will start. • Whether starting or stopping, the DC brake current threshold is set by parameter 07-07. Set the DC brake current (07-07) as a part of the inverter’s allowable output current (the inverter’s allowable output current is set to 100%). • Increase the DC brake time (07-08, 07-16) or increase the DC brake current (07-07) to shorten the stop time. • Set any of the terminals (03-00 to 07) to 33 allows controlling the DC brake operations through the multi-function digital input. Please to Figures 4.3.77~4.3.79 on the DC brake timetable. • If 04-05 (multi-function analog input AI2 function option) is set to 5 (DC brake current), analog input can be used to adjust the DC brake current. Refer to Figure 4.3.62 on DC brake current adjustment.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Stopping, power and speed-search parameters — PDF page 236

Source row Parameter Name Scope/options and printed unit
1 07- 07 DC brake current threshold 【0~100】%
2 07- 08 DC brake time while stopping 【0.00~100.00】Sec
3 07- 16 DC brake time while starting 【0.00~100.00】Sec

Manual — Short-circuit braking and deceleration stop — page 237

Manual reference: physical PDF page 237. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• The short-circuit brake function is used on PMSLV control mode. The braking method is using IGBT switching to cause the motor’s three-phase to short-circuit and generate brake torque. The brake action program can be adjusted by setting parameters 07-06 and 07-34 to 07-36. • If 07-35 is set to 0, the inverter will start with the minimum output frequency. • Parameter 07-36 uses the rated current of the motor as 100%, and uses it to limit the maximum current during short-circuit braking. • Set any of the terminals (03-00 to 07) to 65 allows controlling the short-circuit brake operations through the multi-function digital input

Selects the stopping method to use when executing stop commands. There is a total of four stopping methods, and under SV mode, DC brake and free-run stop with timer cannot be used.

(1) 07-09=0: ‧ Decelerates and stops according to the setting of 07-09. When the operation command is removed, the motor will decelerate to the minimum output frequency 01-08 (Fmin) and then stops. ‧ The deceleration speed is determined by the deceleration time (default factory setting: 00-15). When the output frequency has been reduced to the DC brake start frequency (07-06) or minimum output frequency (01-08), the DC brake will start using the larger setting value and the motor will stop.

. If the S curve has been set, it will be added to the total stop time. ‧ Refer to Figure 4.3.80

Figure 4.3. 80 Decelerate and stop

Actual deceleration time = [Output frequency when stop command starts / Maximum output frequency Fmax (01-02)] × setting value of deceleration time. Printed fraction association preserved; no calculated value supplied.

Operation command; Start; Stop; Time; Output frequency; Deceleration time; 07-06; Time; T; T: DC brake time when stopping (07-08). Source labels only.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Stopping, power and speed-search parameters — PDF page 237

Source row Parameter Name Scope/options and printed unit
1 07- 34 Short-circuit brake time while starting 【0.00~100.00】Sec
2 07- 35 Short-circuit brake time while stopping 【0.00~100.00】Sec
3 07- 36 Short-circuit brake current limit 【0.0~200.0】%

Stopping, power and speed-search parameters — PDF page 237

Source row Parameter Name Scope/options and printed unit
1 07- 09 Stop mode selection [0]: Deceleration stop [1]: Free-run stop [2]: Full-range DC brake stop [3]: Free-run stop with timer

Manual — Free-run and full-range DC stop — page 238

Manual reference: physical PDF page 238. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(2) 07-09=1: • If the operation command is removed, the inverter turns off and the motor enters a free-run stop decelerating with the friction of the drive system. • After the operation command is removed, the subsequent operation command will be ignored until the minimum base block time (07-18) ends. • Please refer to Figure 4.3.81. • If under SLV mode (00-00 = 2), the next startup after free-run will start the speed search function automatically. If the equipment will use the mechanical brake to stop the motor after the operation command is removed, please change parameter 07-26 to 1 (effective) (parameter 07-26 is only effective in software version 1.3 and later).

Figure 4.3. 81 Free-run stop

(3) 07-09=2: • If the operation command is removed, the inverter will perform base block (b.b.) with the minimum base block time (07-18), and then the 07-07 setting DC brake will stop the motor. • The DC brake time (tDCDB) in Figure 4.3.82 is determined by the setting value of 07-08 (DC brake time while stopping) and the frequency when the operation command is removed.

• If over-current protection occurred during the DC braking process, increase the minimum b.b. time (07-18) until protection no longer occurs. • Please refer to Figure 4.3.82 to understand the DC brake stop function.

Figure 4.3. 82 DC brake stop

Operation command; Turn on; Turn off; Turn on; Time; Output frequency; Time; t_b.b; Minimum base cut-off time (07-18). Source labels only.

tDCDB = [(07-08) × 10 × output frequency] / Fmax (01-02). Printed numerator and denominator retained; no computed duration.

Left: Output frequency; Turn on; Turn off; Time; Time; t_b.b; tDCDB; t_b.b: Minimum base cut-off time (07-18); tDCDB: DC brake time. Right: tDCDB; 07-08 × 10; 07-08 × 1; 10%; 100%; Maximum output frequency (Fmax 01-02); output frequency when executing stop. Labels only; no inferred geometry.

Manual — Timed free-run and undervoltage controls — page 239

Manual reference: physical PDF page 239. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(4) 07-09=3 • If the operation command is removed, the inverter will base block and the motor will free-run stop. If operation command was inputted before the operation wait time is reached, the inverter will not operate and the operation command will be ignored. • When the operation command is removed, the operation wait time (T1) is determined by the deceleration time (00-15,17, 22 or 24) and the output frequency. • Please refer to Figure 4.3.83

Figure 4.3. 83 Timer free-run stop

*: When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz

Low voltage detection (07-13). Adjust the 07-13 voltage threshold 150 to 210 Vdc (220 V class models) or 250 to 420 Vdc (for 440V class models). When the voltage is lower than the setting value of 07-13 (07-13 setting value / 1.414 is the AC voltage detection threshold) and the time exceeds the setting value of 07-25, the low voltage error “UV” will activate. If 07-25=0.00s, once it is detected that the voltage is too low, UV will activate. Set preventive measures: ①. The input voltage will limit the inverter output voltage; if the voltage decreased or the load is too big, the motor may stall. ②. When the input voltage is lower than the setting value of 07-13, the output will be shut off immediately; it will not start automatically when power is restored.

Low voltage threshold selection (07-30) When the low voltage threshold selection setting is 1 (effective), the 07-13 voltage threshold lower limit of the 440V class models is adjusted to 250V.

Low voltage operation frequency (07-31) When DI terminal-62 EPS input is used, the frequency command will run according to parameter 07-31. Please refer to page 4-114 on the description of low voltage start.

Left: operation command; Turn on; Turn off; Turn on; Turn off; Turn on; Output frequency; Time; Time; T1: operation waiting time. Right: T1; Deceleration time (for example 00-15); Minimum base cut-off time t_b.b (07-18); 10%; 100%; Maximum output frequency (Fmax 01-02); Output frequency when executing stop. Source labels only.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Stopping, power and speed-search parameters — PDF page 239

Source row Parameter Name Scope/options and printed unit
1 07- 13 Low voltage detection threshold [200V model: 150~300V] [400V model:250~600V]
2 07- 25 Low voltage detection time 【0.00~1.00】Sec
3 07- 30 Low voltage threshold selection [0]: Disabled [1]: Enabled
4 07- 31 *Low voltage operation frequency 【0.00~599.00】Hz

Manual — Pre-excitation current and time — page 240

Manual reference: physical PDF page 240. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

If higher start torque is required, especially for driving large-powered motors, pre-excitation time 07-14 can be set to use pre-excitation operation to generate motor flux. (1) Pre-excitation time (07-14) • When inputting operation commands (forward or reverse), the inverter will automatically perform pre- excitation with the pre-excitation time (07-14) set. • As shown in Figure 4.3.84, after the flux reaches 100%, set the pre-excitation time. The time required to establish magnetic flux is the function value of the motor’s electrical time constant. (2) Pre-excitation threshold (07-15) • Use the pre-excitation threshold (07-15) to provide a higher excitation current within the pre-excitation time (07-14). This will increase the motor’s speed and stability. • To quickly establish magnetic flux, the pre-excitation time (07-14) can be reduced and set the pre- excitation threshold (07-15) at a high point. • If the pre-excitation threshold (07-15) set is higher than 100%, a higher excitation current will be provided during pre-excitation time (07-14), and the time required to establish magnetic flux inside the motor can be shortened. When the pre-excitation threshold (07-15) set reaches 200%, the time required to establish magnetic flux can be reduced to approximately half. • If the pre-excitation threshold (07-15) is set to a higher value, the motor may generate larger noises during the pre-excitation time period. • When 100% magnetic flux is established and the excitation current has returned to 100%, pre-excitation has ended. Refer to Figure 4.3.84 below.

Figure 4.3. 84 Pre-excitation operation

Run Command; t; Magnetic flux And Exciting current; 100%; Exciting current; Pre-exciting initial Level (07-15); Magnetic flux; t; Motor Speed; t; Pre-excitation Time (07-14). Source labels only; no waveform reconstruction.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Stopping, power and speed-search parameters — PDF page 240

Source row Parameter Name Scope/options and printed unit
1 07- 14 Pre-excitation time 【0.00~10.00】Sec
2 07- 15 Pre-excitation threshold 【50~200】%

Manual — Minimum base-block interval — page 241

Manual reference: physical PDF page 241. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• During a momentary power loss and the inverter continues to operate (07-00=1) after the power resumes, the operation command must always exist. • Failure output signal contact output. • When momentary power loss is detected, the inverter will turn off the output and retain B.B. for a set period of time automatically. When setting the time 07-18, the residual voltage is expected to be almost zero. • When the momentary power loss time exceeds the minimum base block time (07-18), operation will start immediately after speed search. Please refer to Figure 4.3.85 below.

Figure 4.3. 85 Minimum B.B time and momentary power loss time

• Minimum base block time (07-18) is also used for speed search and DC brake functions. • Set the minimum base block time (07-18) required. • Execute the speed search or DC brake function, and if over-current “OC” occurs, increase the setting. • Momentary power loss and normal speed search after search is completed for the speed used to start this equipment.

Two panels each: Momentary power loss; Minimum B.B. Time (07-18); Inverter B.B. time; t on each timeline. (a) minimum base-block time longer than momentary power loss; (b) minimum base-block time shorter than momentary power loss. Source comparison labels only.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Stopping, power and speed-search parameters — PDF page 241

Source row Parameter Name Scope/options and printed unit
1 07- 18 Minimum cut-off time 【0.1~5.0】Sec

Manual — Speed-search settings and limitations — page 242

Manual reference: physical PDF page 242. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• The speed search function is used to search for the actual speed, and start successfully with the detected speed. Effective when power is resumed after momentary power loss and when restarted after failures. • If start speed search is selected under V/F+PG or SV control mode (with PG control), the inverter will be started with the frequency detected.* (V/F+PG, SV and PMSV are only for special projects • Set the multi-function digital input terminal to external speed search command 1 or 2. The external speed search command 1 (setting value=19) and 2 (setting value=34) cannot be set simultaneously, otherwise the “SE02” (digital input terminal error) may occur. • If external search command is used to execute speed search, make sure that the speed search command comes before the operation command, or at least must become effective simultaneously with the operation command. A typical operation order is displayed in Figure 4.3.86 below.

Figure 4.3. 86 Speed search and operation commands

• Speed search is not applicable to motors and high-speed motors with capacities two classes higher or lower than the inverter. • To use the speed search function and when the control mode is V/F, it is recommended to execute static motor parameter tuning.

Ry1; Ry2; Rv1; Speed search command; Run command. Electrical diagram labels only; contact connectivity and wiring geometry retained in original.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Stopping, power and speed-search parameters — PDF page 242

Source row Parameter Name Scope/options and printed unit
1 07- 19 Direction seeking current 【0~100】%
2 07- 20 Speed seeking current 【0~100】%
3 07- 21 Speed seeking integral time 【0.1~10.0】Sec
4 07- 22 Speed seeking delay time 【0.0~20.0】Sec
5 07-23 Voltage recovery time 【0.1~5.0】Sec
6 07- 26 SLV selection of starting method after free-run stop [0]: Speed search start [1]: Normal start
7 07- 27 SLV start method selection after malfunction [0]: Speed search start [1]: Normal start
8 07- 28 Start method selection after cut-off [0]: Speed search start [1]: Normal start
9 07- 32 Speed seeking mode selection [0]: Disabled [1]: Mode 1 (execute speed search once after power up) [2]: Mode 2 (execute speed search every time)
10 07- 33 Speed seeking start frequency selection [0]: Motor maximum output frequency [1]: Frequency command

Manual — Speed-search procedure and parameter conditions — page 243

Manual reference: physical PDF page 243. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• To use the speed search function and when the control mode is SLV mode, rotational motor parameter tuning needs to be executed. If longer motor wiring was replaced after executing parameter tuning, static parameter tuning needs to be executed also. • Speed search uses the current detection principles.

(1). Direction search current (07-19) • Set the bidirectional current threshold • If speed search failed on low-speed (5Hz or more), increase the setting value Please note that if the setting value is too big, slight DC brake effects will be generated.

(2). Speed search current (07-20) • Set the speed search current threshold. • The setting value must be lower than the excitation current (02-09) or equal to the no-load current. If the no-load current is unknown, it is recommended to start setting at 20%. Excessive speed search current will cause inverter output saturation. • To use speed search under momentary power loss situations, if over-current (OC) is detected, increase the minimum base block time (07-18).

(3). Speed search integral time (07-21) • Set the integral time during speed search. • If OV occurred, increase the setting value to make the speed search time longer. If quick start is required, the setting value can be decreased.

(4). Speed search delay time (07-22) • If the output-side of the inverter has contactors, the 07-22 speed search delay time can be set. • The default factory setting is 0.2 seconds; the inverter will start performing speed search after the delay time has passed. Set 07-22 = 0.0 seconds and the speed search delay function will be disabled.

(5). Voltage recovery time (07-23). • Set the voltage recovery time. • Set the time for the inverter output voltage to be restored to the normal voltage.

(6). Selection of start method after SLV free-run stop (07-26) . =0 speed search start. =1 normal start. (the default factory value is speed search start) • If under SLV mode (00-00=2), the stop mode is set as free-run stop (07-09=1) or free-run stop with timer function (07-09=3), the next startup after free-run will start the speed search function automatically. If the equipment will use the mechanical brake to stop the motor after the operation command is removed, please change this parameter to 1 normal start.

(7). Starting method when SLV mode malfunctions (07-27) . =0 speed search start. =1 normal start. (the default factory value is speed search start) • Under SLV mode (00-00=2), if malfunction occurs, speed search will be used to start automatically. If the equipment will use the mechanical brake to stop the motor after the operation command is removed, please change this parameter to 1 normal start.

(8). Start method selection after external cut-off ends (07-28) . =0 speed search start. =1 normal start. (the default factory value is speed search start) • After external cut-off ends, the inverter usually will start with the speed search method. • If under VF (00-00 = 0) or SLV mode (00-00=2), the external cut-off time is long, and the motor has already stopped when external cut-off ends, this parameter can be set to 1, and the inverter will start accelerating with the minimum frequency after external cut-off ends.

(9). Speed search mode selection (07-32) 0: Invalid After inputting the operation command, operation will start from the minimum output frequency. However, other functions that will trigger speed search will not be restricted

Manual — Speed-search modes and timing illustrations — page 244

Manual reference: physical PDF page 244. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1: Execute speed seeking once after power on When the inverter supplies power, after the operation command is inputted for the first time, speed search will be executed first, and the motor will be started with the frequency found. 2: Speed search will be executed during every operation, and the motor will be started with the frequency found. Note: If the motor started vibrating when the PM motor is performing speed search, it is recommended to reduce the setting values of 20-00 & 20-02.

(10). Speed search start frequency selection (07-33) Used to set the speed search starting frequency 0: Motor maximum output frequency The inverter will start performing speed search from the maximum frequency of the motor 1: Frequency command The inverter will start performing speed search from the frequency command set ■ Current detection method speed search (a) Speed search during startup

Figure 4.3. 87 Speed search during startup

(b) Speed search during momentary power loss recovery period

Figure 4.3. 88 Speed search during momentary power loss

Run command; Search command; Output frequency; Output voltage; Output current; t on each timeline; Speed search decel time (07-21); (07-18); V/f during speed search; Return to the voltage at normal running; Voltage recovery time (07-23); (07-20); Speed search operation. Explicit labels only; no time or waveform geometry inferred.

Momentary power loss; Minimum b.b. time (07-18); Run command; Search command; Output frequency; Output voltage; Output current; t on each timeline; (07-18); Speed search decel time (07-21); V/f during speed search; Return to the voltage at normal running; Voltage recovery time (07-23); (07-20); Speed search operation. Explicit labels only.

Manual — Momentary-loss restart interval conditions — page 245

Manual reference: physical PDF page 245. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ When the minimum base block time (07-18) is longer than the momentary power loss time, the search speed operation starts after the minimum base block time (07-18). ‧ When the minimum base block time (07-18) is shorter, speed search operation will start resuming immediately after power is recovered.

Manual — DC braking, PM search, STP2 and handwheel current — page 246

Manual reference: physical PDF page 246. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

After starting DC brake, if 0 was set for the operation command while the DC brake is activated, operation will only start again after the DC brake has ended. If it was set to 1, operation can start again during the DC brake process without the need until the braking ends.

• When output voltage saturation occurs and caused the motor operation to vibrate abnormally, this parameter can be gradually increased to suppress and limit the output voltage. • When this parameter is too big, insufficient torque may occur. Please reduce this parameter at this time.

If the motor is rotating due to inertia or other factors at a speed significantly lower than the minimum speed control range, parameters 07-43 and 07-44 can be used to perform braking and stop the motor then restart. If the motor is rotating due to inertia or other factors at a speed significantly higher than the minimum speed control range, no matter what the values of 07-43 and 07-44 are, it will start with the frequency found directly. If 07-43 and 07-44 are set to 0, no matter what the actual rotation speed of the motor is, it will start with the frequency found after speed search ends.

• If the STP2 function is enabled and the 00-02 primary operation command source is set to external control and there is operation signals inputted, if the digital operator is used to stop the operation, the digital operator will display the flashing warning message of “Terminal STOP” (STP2). • If the STP2 function is cancelled and the 00-02 primary operation command source is set to external control and there is operation signals inputted, if the digital operator is used to stop the operation, the digital operator will not display the STP2 flashing warning message.

Under handwheel mode, when the handwheel output frequency is less than the minimum output frequency (01-08) of motor 1, DC current will be injected to perform braking. The unit of this parameter is a percentage of the motor 1 rated current (02-01).

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Motor control and protection parameters — PDF page 246

Source row Parameter Name Scope/options and printed unit
1 07- 29 Operation command selection during DC braking [0]: Not allowed to start during the process [1]: Allowed to start during the process

Motor control and protection parameters — PDF page 246

Source row Parameter Name Scope/options and printed unit
1 07- 42 Voltage limit gain 0.0 ~ 50.0%

Motor control and protection parameters — PDF page 246

Source row Parameter Name Scope/options and printed unit
1 07- 43 PM motor speed search short-circuit brake time 【0.00~100.00】Sec
2 07- 44 PM motor speed search DC brake time 【0.00~100.00】Sec

Motor control and protection parameters — PDF page 246

Source row Parameter Name Scope/options and printed unit
1 07- 45 STP2 function selection [0]: Enable STP2 [1]: Cancel STP2

Motor control and protection parameters — PDF page 246

Source row Parameter Name Scope/options and printed unit
1 07- 46 DC injection current limit 0 ~ 150%

Manual — PM three-segment speed switching — page 247

Manual reference: physical PDF page 247. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

According to the mode shown in the figure below, three-segment speed switching can be performed by using parameter 00-25 (acceleration/deceleration switching frequency) when ≠0, along with parameter 22-11 (I/f mode start frequency switching point) for frequency switching acceleration/deceleration. Invalid: Please refer to 00-25 parameter frequency to perform speed switching. Mode 1: Speed switching can be performed after startup; perform speed switching by following Figure 4.3.89. Mode 2: Speed switching as shown in the figure below can only be achieved during the first operation, but switching will become invalid when decelerating 22-11.

Figure 4.3. 89 PM speed switching

Note: When 00-25≠0, frequency switching cannot be less than the frequency setting of parameter 22-11, and this parameter can only be under PMSLV mode.

Output Frequency; 00-25; 22-11; time. Left-to-right rate labels: Tacc3 Rate (00-21); Tacc1 Rate (00-14); Tacc4 Rate (00-23); Tacc4 Rate (00-25); Tdec1 Rate (00-15); Tdec3 Rate (00-22). Source label Tacc4(00-25) on descending side retained literally; no corrected parameter inferred.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Motor control and protection parameters — PDF page 247

Source row Parameter Name Scope/options and printed unit
1 07- 47 PM speed switching frequency mode [0]: Disabled [1]: Mode 1 [2]: Mode 2

Manual — Stall-prevention parameter definitions — page 248

Manual reference: physical PDF page 248. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

08-Protection function group

*Note: The stall prevention function is only effective under V/F control mode. Stall prevention during acceleration (08-00=xxx0b) • This function is used to prevent the generation of excessive current during the acceleration period due to greater loads of the motor or the need of faster acceleration times. • When the stall prevention function (08-00=xxx0b) was enabled during acceleration, and the output current of the inverter exceeded -15% of the acceleration stall prevention threshold (08-01), the acceleration speed will start reducing. If the setting value of the acceleration stall prevention threshold (08-01) is reached, the motor will stop accelerating. • This parameter is the rated percentage of the inverter, therefore, when the motor capacity is smaller than the inverter and the motor stalled during acceleration, the setting value of parameter 08-01 can be reduced.

Figure 4.3. 90 Stall prevention during acceleration

Inverter Output Current; 08-01; 15%; t; Output Frequency; t; Stall prevention. Source labels only; no derived curve values.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Motor control and protection parameters — PDF page 248

Source row Parameter Name Scope/options and printed unit
1 08- 00 Stall prevention function [xxx0b]: Stall prevention effective during acceleration [xxx1b]: Stall prevention ineffective during acceleration [xx0xb]: Stall prevention effective during deceleration [xx1xb]: Stall prevention ineffective during deceleration [x0xxb]: Stall prevention effective during operation [x1xxb]: Stall prevention ineffective during operation [0xxxb]: Stall prevention during operation is in accordance with stage one deceleration time [1xxxb]: Stall prevention during operation is in accordance with stage two deceleration time
2 08- 01 Acceleration stall prevention threshold 【20~200】%
3 08- 02 Deceleration stall prevention threshold 200V :【330V~410V】 400V :【660V~820V】
4 08- 03 Stall prevention threshold during operation 【30~200】%
5 08-21 Acceleration stall prevention limit 【1~100】%
6 08-22 Operation stall detection time 【2~100】mSec
7 08- 40 Motor 2 acceleration stall prevention threshold 【20~200】%
8 08-41 Motor 2 acceleration stall prevention limit 【1~100】%

Manual — Constant-power limits and deceleration defaults — page 249

Manual reference: physical PDF page 249. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• If the motor is used at a constant power (CH) area, the stall prevention threshold (08-01) will automatically reduce to prevent stalling, The stall prevention threshold during acceleration in a constant power area is as shown below:

08-21 reduces the stall prevention threshold in the constant power area down to the limit value required by the needed threshold. Refer to the figure below.

Figure 4.3. 91 Stall prevention threshold and limit during acceleration 08-40 motor 2 acceleration stall prevention threshold and 08-41 motor 2 acceleration stall prevention limit are used to switch between motor 1/motor 2 when the external terminal DI-40 is used.

Stall prevention selection during deceleration (08-00=xx0xb) • The stall prevention function during deceleration automatically extends the deceleration time based on the DC voltage level to prevent over voltage during deceleration. • During deceleration, when the DC voltage exceeds the stall prevention threshold, deceleration stops; when the DC voltage is lower than the detection threshold, deceleration continues. • The stall prevention threshold can be set with 08-02; refer to Table 4.3.31.

Figure 4.3. 31 Stall prevention threshold during deceleration

Acceleration stall prevention threshold (in constant power area) = [acceleration stall prevention threshold (08-01) × Fbase (01-12)] / Output frequency. Printed fraction association retained; no computed value.

Stall prevention level during acceleration; 08-01; 08-21; C.T region; C.H region; Output frequency. Explicit labels only; no curve interpolation.

Source caption says Figure4.3.31 although prose refers to Table4.3.31. Values are source factory defaults, not verified installation thresholds.

Stall prevention during deceleration factory defaults — PDF page 249

Source row Inverter type 08-02 default factory value (DC voltage)
1 200V class model 385VDC
2 400V class model 770VDC

Manual — Deceleration and running stall prevention — page 250

Manual reference: physical PDF page 250. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Refer to Figure 4.3.92 stall prevention during deceleration • When the brake starts (braking resistor or braking module), set 08-00=xx1xb (invalid).

Figure 4.3. 92 Stall prevention during deceleration

Stall prevention during operation (08-00=x0xxb) Stall prevention is only effective under V/F control mode with or without PG during operation. • This function reduces the output frequency of the inverter automatically to prevent motor stalling. • If the inverter’s output current exceeds the time set with 08-22 and the threshold set with 08-03, the inverter’s output frequency will decelerate with deceleration time 1 (00-15) or deceleration time 2 (00- 17). When the inverter’s output current drops below -2% of the threshold (08-03), the output frequency will accelerate again. • Refer to Figure 4.3.93 below.

Figure 4.3. 93 Stall prevention during operation Note: The stall prevention threshold during operation can be set with the multi-function analog input AI2 (04-05=7).

Output frequency; Deceleration time is extended to prevent overvoltage.; Deceleration time; t. Explicit labels only.

Load; t; Inverter Output Current; 08-03; 2% (Hysteresis); t; Output Frequency; Tdec1(00-15); Tdec2(00-17); t; 08-22 (detection time). Explicit labels only.

Adjacent source context — repeated to preserve continuation:

Manual — Motor overload selection and protection0 curves — page 251

Manual reference: physical PDF page 251. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor overload protection selection (08-05). ‧ Set the motor overload protection function with 08-05 according to the motor used. ‧ When two or more motors are connected to the same inverter, disable the motor overload protection function (set 08-05=xxx0b) and provide overload protection using other methods separately. For example, connect a thermal overload relay at the power of each motor. ‧ When the power supply is turned on and off normally, the motor overload protection function 08- 05=xx1xb (hot start protection characteristic curve) resets the thermal value every time the power is turned off. ‧ For motors without cooling fans (general standard motor), when operating at low speeds, the thermal consumption capacity is lower, set 08-05=x0xxb. ‧ For motors with cooling fans (dedicated motors for inverters or V/F motors), the thermal consumption capability is not related to the rotation speed, set 08-05= x1xxb. ‧ Use electronic overload protection to protect the motor from overloading. Set the parameter 02-01 according to the rated current on the motor’s nameplate. ‧ Refer to Figure 4.3.94 below Example of standard motor overload protection curve (08-05 = x0xxb). The overload curve delay time varies according to the difference in 08-07 (motor overload (OL1) protection threshold).

08-07=0:

08-07=1:

08-07=0; Low Speed (1.5Hz); Hot Start; Overload Protect Time (min) printed ticks: 7.9;2.9;1.5; Motor Load Current (%) (02-01=100%) printed ticks: 100%;150%;200%. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

08-07=0; Low Speed (1.5Hz); Cold Start; Overload Protect Time (min) printed ticks: 12.4;4.5;2.4; Motor Load Current (%) (02-01=100%) printed ticks: 100%;150%;200%. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

08-07=0; High Speed (60Hz); Hot Start; Overload Protect Time (min) printed ticks: 15.7;3.9;1.7; Motor Load Current (%) (02-01=100%) printed ticks: 117%;150%;200%. Printed annotation: start activacted point. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

08-07=0; High Speed (60Hz); Cold Start; Overload Protect Time (min) printed ticks: 27.7;6.1;2.7; Motor Load Current (%) (02-01=100%) printed ticks: 117%;150%;200%. Printed annotation: start activacted point. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Adjacent source context — repeated to preserve continuation:

Motor control and protection parameters — PDF page 251

Source row Parameter Name Scope/options and printed unit
1 08- 05 Motor overload (OL1) protection selection [xxx0b]: Motor overload ineffective [xxx1b]: Motor overload effective [xx0xb]: Motor overload cold start [xx1xb]: Motor overload hot start [x0xxb]: Standard motor [x1xxb]: Inverter motor [0xxxb]: Reserved [1xxxb]: Reserved
2 08-07 Motor overload (OL1) protection threshold [0]: Motor overload (OL1) protection 0 [1]: Motor overload (OL1) protection 1 [2]: Motor overload (OL1) protection 2

Manual — Protection1 and2 curves and OL1 action — page 252

Manual reference: physical PDF page 252. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

08-0=2:

Figure 4.3. 94 Motor overload protection curve (example of a standard motor)

• 08-06 = [0]: After the motor electronic relay protection is triggered, the inverter immediately shuts off and displays OL1. To resume operation, press the RESET key or use an external reset terminal. • 08-06 = [1]: After the motor electronic relay protection is triggered, operation continues, but the inverter flashes OL1 until the current drops below the normal level, at which point the OL1 display disappears.

08-07=1 (heading on PDF251); Low Speed (1.5Hz); Hot Star.; Overload Protect Time (min) printed ticks: 8.9;3.2;1.7; Motor Load Current (%) (02-01=100%) printed ticks: 100%;150%;200%. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

08-07=1 (heading on PDF251); Low Speed (1.5Hz); Cold Start; Overload Protect Time (min) printed ticks: 14.9;5.3;2.8; Motor Load Current (%) (02-01=100%) printed ticks: 100%;150%;200%. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

08-07=1 (heading on PDF251); High Speed (60Hz); Hot Start; Overload Protect Time (min) printed ticks: 19.28;4.2;1.9; Motor Load Current (%) (02-01=100%) printed ticks: 117%;150%;200%. Printed annotation: start activacted point. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

08-07=1 (heading on PDF251); High Speed (60Hz); Cold Start; Overload Protect Time (min) printed ticks: 32.33;7.1;3.2; Motor Load Current (%) (02-01=100%) printed ticks: 117%;150%;200%. Printed annotation: start activacted point. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

literal heading08-0=2; Low Speed (1.5Hz); Hot Star.; Overload Protect Time (min) printed ticks: 9.9;3.5;1.9; Motor Load Current (%) (02-01=100%) printed ticks: 100%;150%;200%. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

literal heading08-0=2; Low Speed (1.5Hz); Cold Star.; Overload Protect Time (min) printed ticks: 17.8;6.3;3.4; Motor Load Current (%) (02-01=100%) printed ticks: 100%;150%;200%. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

literal heading08-0=2; High Speed (60Hz); Hot Start; Overload Protect Time (min) printed ticks: 21.72;4.7;2.1; Motor Load Current (%) (02-01=100%) printed ticks: 117%;150%;200%. Printed annotation: start activacted point. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

literal heading08-0=2; High Speed (60Hz); Cold Start; Overload Protect Time (min) printed ticks: 39.06;8.5;3.8; Motor Load Current (%) (02-01=100%) printed ticks: 117%;150%;200%. Printed annotation: start activacted point. Source standard-motor example labels only; no curve interpolation or inferred engineering rating.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

Motor control and protection parameters — PDF page 252

Source row Parameter Name Scope/options and printed unit
1 08- 0 Overload (OL1) protection action start method [0]: Stops output after overload protection [1]: Continues operation after overload protection

Manual — AVR, phase-loss and torque detection parameters — page 253

Manual reference: physical PDF page 253. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• The automatic voltage regulation (AVR) function is designed to address output voltage instability caused by fluctuations in input voltage. When 08-08 = [0], the maximum output voltage is limited. If the three-phase input voltage fluctuates and is lower than the input voltage set in parameter 01-14, the output voltage will also fluctuate accordingly. When 08-08 = [1], the maximum output voltage is not limited, and output voltage will remain stable regardless of input voltage variations.

Input phase loss protection selection (08-09). • Set 08-09 to enable or disable the input phase loss function. 08-09 = 0: Disables input phase loss function. =1: Enables input phase loss function. • When enabled and input phase loss is detected, the digital operator will display the “IPL Input Phase Loss” (IPL) fault message. The fault contact activates and the inverter stops with free-run deceleration. • If output current is below 30% of the rated inverter current, input phase loss detection has no effect.

Output phase loss protection selection (08-10). • Set 08-10 to enable or disable the output phase loss function. Disables input phase loss function.08-10 = 0: Disables output phase loss function. = 1: Enables output phase loss function. • When enabled and output phase loss is detected, the digital operator displays the “OPL Output Phase Loss” (OPL) fault message. The fault contact activates and the inverter stops with free-run deceleration. • If output current is below 10% of the rated inverter current, output phase loss detection has no effect.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation.

All printed mode restrictions, warnings, conditional ranges and software qualifications retained in page context; no engineering recommendation. 08-18 option list continues PDF254; only page-local content recorded here.

Motor control and protection parameters — PDF page 253

Source row Parameter Name Scope/options and printed unit
1 08- 08 Automatic Voltage Regulation Function (AVR) [0]:AVR Enabled [1]:AVR Disabled

Motor control and protection parameters — PDF page 253

Source row Parameter Name Scope/options and printed unit
1 08- 09 Input phase loss protection selection [0]: Disabled [1]: Enabled

Motor control and protection parameters — PDF page 253

Source row Parameter Name Scope/options and printed unit
1 08- 10 Output phase loss protection selection [0]: Disabled [1]: Enabled

Motor control and protection parameters — PDF page 253

Source row Parameter Name Scope/options and printed unit
1 08- 13 Overtorque detection selection [0]: Overtorque detection disabled [1]: Detection begins after reaching set frequency [2]: Detection during operation
2 08- 14 Overtorque action selection [0]: Decelerates to stop upon detection [1]: Displays warning and continues operation [2]: Free-run stop upon detection
3 08- 15 Overtorque detection threshold 【0~300】%
4 08- 16 Overtorque detection time 【0.0~10.0】Sec
5 08- 17 Undertorque detection selection [0]: Undertorque detection disabled [1]: Detection begins after reaching set frequency [2]: Detection during operation
6 08- 18 Undertorque action selection [0]: Decelerates to stop upon detection

Manual — Undertorque options and detection signal outputs — page 254

Manual reference: physical PDF page 254. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• The overtorque detection function monitors increased inverter output current or motor torque due to increased mechanical load. The undertorque detection function monitors decreases in mechanical load (e.g., belt breakage) that reduce inverter output current or motor torque. • Torque detection parameters determine how to respond to overtorque (08-13~14) or undertorque (08- 17~18) conditions. • Overtorque (08-15) / Undertorque (08-19) detection level settings depend on the control method: * (V/F+PG, SV, PMSV are only for special projects) (1) In V/f control or V/f+PG mode, detection is based on 100% of the inverter’s rated output current. (2) In SLV or SV control mode, detection is based on 100% of the motor's rated torque. • Overtorque/undertorque detection signals can be output to multifunction digital output terminals (R1A– R1C, DO1), configured using parameters 03-11 to 03-12 (Multifunction Digital Output Terminal Function Selection) set to 12 or 25. Refer to the parameters in Figure 4.3.95.

Figure 4.3.95 Overtorque/Undertorque detection signals using multifunction digital output terminals

R1A; R1B; R1C; 03-11; DO1; DOG; 03-12. Explicit terminal and parameter labels only; wiring/contact connectivity stays in original.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Physical continuation of08-18undertorqueaction:PDF253option0 preserved inpart23; thispage containsoptions1and2. Do not replace prioroptions or infer newparameterID.

Protection, thermal and fire-mode parameters — PDF page 254

Source row Parameter Name Scope/options and printed unit
1 08- 19 Undertorque detection threshold 【0~300】%
2 08- 20 Undertorque detection time 【0.0~10.0】Sec

08-18 option continuation from PDF253 — PDF page 254

Source row 08-18 additional options
1 [1]: Displays warning and continues operation [2]: Free-run stop upon detection

Manual — Torque-detection examples and ground-fault setting — page 255

Manual reference: physical PDF page 255. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Overtorque Detection Setting Example:

Figure 4.3.96 Overtorque Detection Operation • Undertorque Detection Setting Example:

Figure 4.3.97 Undertorque Detection Operation

Ground fault protection setting (08-23). • Adjust 08-23 to enable or disable ground fault protection. 08-23 = 0: Disables ground fault function. = 1: Enables ground fault function. • If the inverter’s leakage current approaches 50% of the rated output current and the ground fault function is enabled (08-23), the digital operator will display the “GF Ground Fault” (GF) fault message. The fault contact will activate, and the inverter will stop by free-run deceleration.

Inverter output current (or motor output torque); Detect level1(08-15);10% hysteresis width;t;Overtorque detection signal;t;08-16;08-16. Source labels only; no inferred waveform values.

Inverter output current (or motor output torque);Detect level1(08-19);10% hysteresis width;t;Undertorque detection signal;t;08-20;08-20. Source labels only.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Protection, thermal and fire-mode parameters — PDF page 255

Source row Parameter Name Scope/options and printed unit
1 08- 23 Grounding failure (GF) selection [0]: Disabled [1]: Enabled

Manual — External faults, fan control and motor overheat parameters — page 256

Manual reference: physical PDF page 256. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

External Fault Operation Selection (08-24): When multifunction terminal is set to 25 for external fault and this terminal receives a signal, the stop method is determined by parameter 08-24. The stop options are as explained in parameter 07-09. External Fault Detection Selection (08-25): Parameter 08-25 determines under what conditions an external fault is detected. (1) When 08-25 = 0 (detection active immediately after power-on), the inverter begins fault detection as soon as it is powered on. (2) When 08-25 = 1 (detection active only during operation), fault detection begins only while the inverter is running.

When a digital multifunction terminal is set to 58 (Safety Function), the inverter will stop according to the setting of 08-30 when the switch is opened.

Fan Operation Selection (08-37): (1) When 08-37 = 0 (fan starts during operation), the fan runs when the inverter operates. If the inverter is stopped and remains so for longer than the fan delay time (08-38), the fan will turn off. (2) When 08-37 = 1 (fan starts immediately after power-on), the fan runs as soon as the inverter is powered on. (3) When 08-37 = 2 (fan starts when temperature is high), the fan runs when the heat sink temperature exceeds a preset internal threshold while the inverter is operating. Once the temperature drops or the delay time (08-38) expires, the fan will shut off. Note 1: When 08-37 = 0 (fan starts during operation), if the inverter is not running but the heat sink temperature rises too high, the fan will automatically turn on to reduce the temperature.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

08-43scope is onPDF257 inthispacket; headings andscope retain separatephysicalpage provenance.

Protection, thermal and fire-mode parameters — PDF page 256

Source row Parameter Name Scope/options and printed unit
1 08- 24 External fault operation selection [0]: Deceleration stop [1]: Free-run stop [2]: Continues operation
2 08- 25 External fault detection selection [0]: Detection active immediately after power-on [1]: Detection active only during operation

Protection, thermal and fire-mode parameters — PDF page 256

Source row Parameter Name Scope/options and printed unit
1 08- 30 Safety function selection [0]: Decelerates to stop [1]: Free-run stop

Protection, thermal and fire-mode parameters — PDF page 256

Source row Parameter Name Scope/options and printed unit
1 08- 37 Cooling Fan Operation Selection [0]: Starts when inverter is running [1]: Always on [2]: Starts when temperature is high
2 08- 38 Fan close delay time 【0~600】Sec

Protection, thermal and fire-mode parameters — PDF page 256

Source row Parameter Name Scope/options and printed unit
1 08 - 35 Motor overheat fault selection [0]: Disabled [1]: Decelerates to stop [2]: Free-run stop [3]: Continues operation
2 08 - 36 PTC Input Filter Time 【0.00 ~ 5.00】
3 08 - 39 Motor overheat protection delay time 【1 ~ 300】Sec
4 08 - 42 PTC protection threshold 【0.1 ~ 10.0】V

08-43 heading continued on PDF257 — PDF page 256

Source row Parameter Name
1 08 - 43 PTC reset threshold

Manual — PTC thresholds and motor overheat procedure — page 257

Manual reference: physical PDF page 257. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor Overheat Protection Selection: • This function uses a Positive Temperature Coefficient (PTC) thermistor built into the motor fan, which increases resistance with temperature, to protect the motor from overheating. • The PTC thermistor should be connected between terminal AI2 and GND, with a voltage- dividing resistor R added, as shown in Figure 4.3.98 (b). (1) The inverter behavior in response to motor overheat is as follows: 08-35 = 0: Motor overheat fault is disabled. 08-35 = 1: Inverter decelerates to stop when motor overheats. 08-35 = 2: Inverter performs a free-run stop when motor overheats. 08-35 = 3: Inverter continues running despite motor overheating until the “08-42 PTC Protection Level” is reached, at which point it free-runs to stop. (2) When parameter 08-35 = 0, motor overheat protection is disabled. (3) When parameter 08-35 = 1 or 2 (stop operation when motor overheats), and motor temperature increases such that the AI2 voltage level exceeds the value set in [08-44 PTC Warning Level], and the delay time set in parameter 08-39 has elapsed, the motor overheat protection activates. The digital operator displays the fault message “OH4 Motor overheat,” and the motor either decelerates to a stop (08-35 = 1) or performs a free-run stop (08-35 = 2). (4) When parameter 08-35 = 3 (continue operation when motor overheats), and the AI2 voltage level exceeds the [08-44 PTC Warning Level], the digital operator displays “OH3 Motor Temp Warning,” and the motor continues running. If the AI2 level exceeds [08-42 PTC Protection Level] and the delay time set in 08-39 has elapsed, overheat protection activates and the operator displays “OH4 Motor overheat,” after which the motor performs a free-run stop. (5) When parameter 08-35 = 1, 2, or 3, the fault “OH4 Motor overheat” can be cleared once the AI2 voltage level drops below [08-43 PTC Reset Level]. (6) External PTC Thermistor Characteristics (per British Standards): In the motor overheat protection diagram shown in Figure 4.3.98, the reference temperature (Tr) is 150°C for Class F insulation and 180°C for Class H insulation. Tr – 5°C: RT≦ 550Ω. Input the RT value into Equation (1) to calculate the corresponding voltage value for [08-43 PTC Reset Level]. Tr + 5°C: RT≧1330Ω. Input the RT value into Equation (1) to calculate the corresponding voltage value for [08-42 PTC Protection Level]. (7) For PTC thermistors of different specifications, the reference values for parameters 08- 42 and 08-43 can be calculated using Equation (1).

(9) Please follow the PTC level setting rule below to avoid parameter configuration errors. [08-43 PTC Reset Level] must be less than [08-42 PTC Protection Level].

(8) V = 10 × [(R_PTC // 200) / (R + (R_PTC // 200))]. Equation(1). Symbols retained as printed; no inferred resistance units or calculated voltage.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Physicalcontinuation of08-43 PTCresetthreshold heading onPDF256; exactprinted voltage range.

Protection, thermal and fire-mode parameters — PDF page 257

Source row Parameter Name Scope/options and printed unit
1 08 - 44 PTC warning threshold 【0.1 ~ 10.0】V

08-43 scope continued from PDF256 — PDF page 257

Source row 08-43 Scope
1 【0.1 ~ 10.0】V

Manual — PTC diagrams and inverter temperature relay — page 258

Manual reference: physical PDF page 258. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.98 (a) Positive temperature coefficient (PTC) thermistor resistance vs. temperature characteristics; (b) Terminal wiring diagram

Note: The maximum value of 08-47 is limited by the value set in 08-46. Inverter Temperature Trigger and Reset Level Selection • When parameter 03-11 is set to [59]: • 08-46: When inverter temperature exceeds 08-46, the relay activates. • 08-47: When output current is ≤ 08-47, the relay signal switches from ON to OFF. Timing Diagram Below:

Figure 4.3.99 Inverter Temperature Trigger and Reset Detection

(a) PTC Thermistor Characteristics:Resistance(ohms);1330;550;Class F150°C;Class H180°C;Temperature;Tr -5;Tr;Tr +5;Tr′;Tr:Temperature threshold value. (b) PTC Thermistor Connections:Voltage divider resistor R;PTC thermistor;+10V;AI2;200KΩ;GND;Internal circuit. Explicit labels only; electrical topology and curve geometry stay in original.

T(°C);08-46;08-47;Inverter temperature;Time;03-11 Relay;ON. Explicit labels only; no inferred transition temperatures.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Protection, thermal and fire-mode parameters — PDF page 258

Source row Parameter Name Scope/options and printed unit
1 08 - 46 Temperature Reached Level 【0 ~ 254】°C
2 08 - 47 Temperature Reset Level 【0 ~ 254】°C

Manual — Fire-mode selection, reset and masked faults — page 259

Manual reference: physical PDF page 259. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fire Mode Selection (08-48): • Adjust parameter 08-48 to enable or disable fire mode. 08-48 = 0: Fire mode disabled. 08-48 = 1: Fire mode enabled. • When fire mode is enabled, terminal S6 is automatically designated as the digital input source for fire mode command (DI Function 47). Once this DI is triggered, fire mode is activated. Regardless of whether the inverter is stopped or running, the normal frequency source will be overridden by the fire mode frequency source, and the inverter will operate and output frequency accordingly. The panel will simultaneously display “FIRE”. Certain faults (see Table 4.3.35) will be masked and will not cause the inverter to stop. Except for fire mode input (DI Function 47) and external overload input (DI Function 69), all other digital inputs (DI) will be ignored. During this state, only parameter reading is allowed via communication and panel; all parameter write commands will be ignored.

Fire Mode Reset Method (08-49): • Adjust parameter 08-49 to set the digital input type for fire mode reset. 08-49 = 0: Reset by power-off. • Reset method: Power off, remove the external trigger signal, then power on to reset. 08-49 = 1: Reset by terminal removal. • Reset method: No power-off required. Remove the external trigger signal and the inverter will return to normal mode. The fire mode frequency source will no longer override the normal frequency source.

Table 4.3.32 Faults masked during fire mode activation

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Source danger warning onPDF260 is essential:firemode maycontinue untilirreparabledamage; notapproval tousemode. Tablecontinues259–260. Prose259referencesTable4.3.35 whilecaption4.3.32.

Protection, thermal and fire-mode parameters — PDF page 259

Source row Parameter Name Scope/options and printed unit
1 08 - 48 Fire mode selection [0]: Disabled [1]: Enabled
2 08 - 49 Fire mode digital input type [0]: Reset by Power-off [1]: Reset by Terminal Removal
3 08 - 50 Fire mode digital terminal status [xxx0b]: S6 A-contact [xxx1b]: S6 B-contact
4 08 - 51 Fire mode motor rotation speed selection [0]: Fire Mode Speed [1]:PID Frequency Command [2]:AI2 Frequency Command
5 08 - 52 Fire mode motor rotation speed 【0.00~100.00】%
6 08 - 59 Fire mode motor direction [0]: Forward [1]: Reverse
7 08 - 60 Fire mode password 【00000 ~ 65534】

Table4.3.32 faults masked during fire mode — PDF page 259

Source row 0x2521H Fault Descriptions
1 4 OH1 (Heat sink overheat)
2 5 OL1 (Motor overload)
3 6 OL2 (Frequency converter overload)
4 7 OT (Over-torque)
5 25 FB (PID feedback signal error)
6 26 Keypad Removed
7 28 CE (Communication error)
8 46 OH4 (Motor overheat)

Manual — Fire-mode danger, switch input, speed and password — page 260

Manual reference: physical PDF page 260. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

! Danger: Fire Mode: This mode is designed to ensure uninterrupted operation of the inverter. When this mode is enabled, most errors and warnings will not stop the inverter, to ensure maximum operational reliability and allow people to evacuate in a smoke-free environment. The inverter will attempt to operate until it is irreparably damaged. If the inverter is set to fire mode, the manufacturer assumes no responsibility for any resulting faults, errors, personal injuries, or damage to the inverter, its components, or any other property.

Fire Mode Digital Input Terminal State (08-50): • Usually when using external terminals, switches need to be connected. There are different types of switches, including normally off switches and normally on switches, so pay attention when selecting because the working status of the two types of switches are different. This parameter determines whether normally open switch or normally closed switch input is required.

User selects the type of switch input required Note: Before configuring terminals for normally open/closed switches, set 08-48 = 0 to disable fire mode. Otherwise, unexpected motor operation from external terminal commands may cause injury.

Fire Mode Motor Speed Source Selection (08-51): • Adjust parameter 08-51 to select the frequency reference for fire mode motor speed. 08-51 = 0: Frequency reference is based on parameter 08-52 (Fire Mode Motor Speed Setting). • Set the speed as a percentage of the maximum frequency (parameter 01-02). When 08-52 = 100%, the inverter outputs its maximum frequency. 08-51 = 1: PID controller source. • The frequency reference is based on the PID controller’s output frequency command. When fire mode is activated, the PID controller’s response can be adjusted using 10-47 Proportional Gain 3 (P), 10-48 Integral Time 3 (I), and 10-49 Derivative Time 3 (D). Refer to Group 10 for related PID controller settings. 08-51 = 2: AI2 analog input source. • The frequency reference is based on analog input AI2. Input specification is defined in parameter 04- 00 (default: 4–20 mA).

Fire Mode Motor Direction (08-59): • Once fire mode is activated, the motor will run in the direction specified by parameter 08-59. This setting takes priority over the keypad and digital input terminals.

Fire Mode Password (08-60): • When fire mode is enabled, users can configure a password in parameter 08-60. For password setup and removal, refer to parameter 13-07 in Group 13. To prevent unintentional modification of fire mode parameters, once a password is set in 08-60 (> 0), only parameters 08-48 to 08-60 will be visible and they will be read-only. Note: Only one password can be set at a time—either 08-60 (Fire Mode Password) or 13-07 (General Parameter Password), not both.

08-50 printed bit example:0 0 0 0; S6:0 indicates normally open switch;1 indicates normally closed switch. Physical bit/switch association read visually; remaining bit meanings not inferred.

Source danger warning onPDF260 is essential:firemode maycontinue untilirreparabledamage; notapproval tousemode. Tablecontinues259–260. Prose259referencesTable4.3.35 whilecaption4.3.32.

Table4.3.32 faults masked during fire mode — PDF page 260

Source row 0x2521H Fault Descriptions
1 49 MtrSw (DI Motor Switch Fault)
2 58 PF (Protection fault)

Manual — Fire-mode PID feedback loss — page 261

Manual reference: physical PDF page 261. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When parameter 08-51 (Fire Mode Motor Speed Source Selection) is set to PID controller source, the PID feedback loss detection function will be automatically enabled, and settings 08-53 to 08-55 will be displayed. Fire Mode PID Feedback Loss Action Selection (08-55): 08-55 = 0: The frequency reference is held at the PID controller's last output frequency at the moment of signal loss. 08-55 = 1: Frequency reference is based on parameter 08-52 (Fire Mode Motor Speed Setting). 08-55 = 2: The frequency reference switches to the maximum frequency set in 01-02 (Motor 1 Maximum Frequency). If the PID feedback value drops below the level set in 08-53 (Fire Mode PID Feedback Loss Detection Level) and remains below this level for longer than the time set in 08-54 (Fire Mode PID Feedback Loss Delay), the inverter will continue to operate but the frequency reference will switch from the PID controller to the 08-55 setting. The output frequency will not fall below the value set in 08-52. Refer to the timing chart below:

Figure 4.3.100 PID Feedback Loss Detection Note: If no feedback signal is present and the detection level is also set to 0%, feedback loss detection will not be triggered.

Feedback value;08-53;t;FBL detection;t;t1;08-54;08-54. Explicit labels only; no unprinted timing values.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Protection, thermal and fire-mode parameters — PDF page 261

Source row Parameter Name Scope/options and printed unit
1 08 - 53 Fire Mode PID Feedback Loss Detection Level 【0~100】%
2 08 - 54 Fire mode PID disconnection delay 【0.0~10.0】Sec
3 08 - 55 Fire mode PID disconnection action selection [0]: Current speed [1]: Fire mode speed (08-52) [2]: Motor 1 maximum frequency (01-02)

Manual — Fire-mode AI2 signal loss — page 262

Manual reference: physical PDF page 262. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When parameter 08-51 (Fire Mode Motor Speed Source Selection) is set to analog input AI2, the AI2 signal loss detection function will be automatically enabled, and settings 08-56 to 08-58 will be displayed. Fire Mode AI2 Signal Loss Action Selection (08-58): 08-58 = 0: The frequency reference is held at the last output frequency of AI2 when the signal was lost. 08-58 = 1: Frequency reference is based on parameter 08-52 (Fire Mode Motor Speed Setting). 08-58 = 2: The frequency reference switches to the maximum frequency set in 01-02 (Motor 1 Maximum Frequency). If the analog command source AI2 drops below the value set in 08-56 (Fire Mode AI2 Signal Loss Detection Level) within a 360 ms interval, the frequency reference is considered lost. If the condition persists beyond the time set in 08-57 (Fire Mode AI2 Signal Loss Delay), the analog command source AI2 will continue to be compared with the previously sampled value recorded within the 360 ms window. Once frequency loss is confirmed, the inverter will operate based on the frequency reference set in 08-58. Explanation of Frequency Loss Function: When the inverter is operating and the selected analog command source AI2 signal disappears, the inverter responds according to the setting in 08-58. The following diagram illustrates the behavior of the analog frequency command AI2 during frequency loss:

Figure 4.3.101 AI2 Frequency Reference Loss Operation

By AI2 Setting;By08-58Setting;Frequency Command;08-56;t;360ms;AI2 Loss Detection;08-57;t. Explicit labels only.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Protection, thermal and fire-mode parameters — PDF page 262

Source row Parameter Name Scope/options and printed unit
1 08 – 56 Fire Mode AI2 Signal Loss Detection Level 【0~100】%
2 08 - 57 Fire Mode AI2 Signal Loss Delay 【0.0~10.0】Sec
3 08 - 58 Fire Mode AI2 Signal Loss Action Selection [0]: Current speed [1]: Fire mode speed (08-52) [2]: Motor 1 maximum frequency (01-02)

Manual — Capacitor, fan and IGBT maintenance monitoring — page 263

Manual reference: physical PDF page 263. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

08-61 = 1: Enables capacitor lifespan monitoring. 08-65 Cooling Fan Maintenance Setting (Expected Fan Lifetime): Set the value (in units of 10 hours) to begin accumulating the inverter cooling fan’s operating time. Note: If 08-65 is set to 5000, the fan maintenance time will be calculated as 50,000 hours. The accumulated cooling fan runtime can be checked via monitoring parameter 13-51. 08-66 IGBT Maintenance Setting (Expected IGBT Lifetime): Set the expected maintenance threshold for the IGBT as a percentage value. 100% corresponds to 99,999 hours. The accumulated IGBT operating time can be checked via monitoring parameter 13-53. Note: After replacing components or the inverter itself, be sure to restore factory settings. Failure to do so will result in continued lifespan tracking from the previous component, and the new component’s lifespan will not be monitored correctly.

Source mode restrictions, warnings and page continuations remain authoritative; no engineered recommendation or inferred units.

Protection, thermal and fire-mode parameters — PDF page 263

Source row Parameter Name Scope/options and printed unit
1 08 - 61 Capacitor maintenance setting [0]: Disabled [1]: Enabled
2 08 - 65 Cooling fan maintenance setting 【0~9999】
3 08 - 66 IGBT maintenance setting 【0~150】

Manual — Communication settings and Modbus specification — page 264

Manual reference: physical PDF page 264. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

09 – Communication Function Group

• PUMP Parallel Communication Protocol (Refer to Group 23 for related details) • The inverter includes a built-in Modbus (RS-485) communication port with an RJ45 connector, which can be used to monitor the inverter status, and to read and set parameters. • Modbus communication enables the following operations, regardless of the settings for 00-05 (Reference Frequency Selection) and 00-02 (Run Command Selection): – Monitor operating status from a controller (PLC). – Set and read parameters (Note: Avoid continuous and frequent parameter writing via communication to prevent EEPROM damage). – Input multifunction commands. The Modbus (RS-485) communication specifications are as follows: Table 4.3.33 Modbus (RS-485) Communication Specifications

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Data length fixed8bits andstopbitfixed1 conflictwithselectable09-03/09-05 cards. Preservebothwithoutresolution.

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 00 Inverter communication station 【1~31】

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 01 Communication mode selection 【0】 MODBUS [3] PUMP Parallel Communication

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options left column Scope/options right column
1 09- 02 Serial Transmission Speed Setting (bps) 【0】1200 【1】2400 【2】4800 【3】9600 【4】19200 【5】38400

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 03 Stop bit selection [0] 1 stop bit [1] 2 stop bit

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 04 Parity bit selection [0] No parity [1] Even parity [2] Odd parity

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 05 Communication data bit selection [0] 8 data bits [1] 7 data bits

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 06 Communication abnormality detection time [0.0~25.5] Sec

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 07 Fault stop selection [0] Decelerates to stop using deceleration time 1 after communication failure [1] Free-run stop after communication failure [2] Decelerates to stop using deceleration time 2 after communication failure [3] Continues operation after communication failure

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 08 Communication fault tolerance count [1~20] times

Communication and PID parameter card — PDF page 264

Source row Parameter Name Scope/options and printed unit
1 09- 09 Wait time 【5~65】mSec

Table4.3.33 Modbus specifications continued264–265 — PDF page 264

Source row Item Specifications
1 Interface RS-485
2 Communication Cycle Asynchronous (Start-Stop Synchronization)
3 Communication Parameters Selectable Baud Rates: 1200, 2400, 4800, 9600, 19200, and 38400 bps Data Length: Fixed at 8 bits Parity Bit: Select no parity, even parity, or odd parity. Stop Bit: Fixed at 1 bit

Manual — Modbus setup and fault behavior — page 265

Manual reference: physical PDF page 265. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

For further details on Modbus communication, including supported function codes and related register addresses, please refer to Section CH4.5 Modbus Communication Protocol Description.

• Communication Setup with Controller (1) Turn off the power supply and connect the communication cable between the controller and the inverter. (2) Turn on the power supply. (3) Use the digital operator to configure the desired communication parameters (parameter [09-00]). (4) Turn off the power supply again and confirm that the digital operator display is completely off. (5) Turn the power supply back on. (6) Begin communication with the controller. .

• Modbus (485) Communication Architecture (1) Modbus communication setup involves one master controller (e.g., PLC) and up to 31 slave inverters in a serial communication network. (2) The master controller connects directly to the inverter via the RS-485 interface. If the master controller does not have an RS-485 port, an RS-232 to RS-485 converter is required to connect the master controller to the inverter units. (3) Modbus can control up to 31 inverters using the standard Modbus communication protocol. ‧ Parameter Definitions:

(1) Inverter Station Address (09-00). ‧ Sets the communication address of the inverter, with settable range from 1 - 31. (2) RS-485 Communication Baud Rate Setting (09-02). ‧ 09-02 = 0: 1200 bps = 1: 2400 bps = 2: 4800 bps = 3: 9600 bps = 4: 19200 bps = 5: 38400 bps (3) RS-485 Communication Parity Bit Selection (Parameters (09-03, 09-04). ‧09-03 = 0:1 stop bit = 1:2 stop bits ‧09-04 = 0:No parity. = 1:even parity. = 2:odd parity. (4) Communication Data Bit Selection (09-05). ‧09-05 = 0:8 bits data = 1:7 bits data (5) RS-485 Communication Error Detection Time (09-06).

(6) RS-485 Communication Fault Stop Selection (09-07). = 0: Decelerate to stop using deceleration time 00-15 = 1: Free-run stop = 2: Decelerate to stop using deceleration time 00-26 (emergency stop time) = 3: Continue running (displays a warning only; stops only when Stop key is pressed)

(7) Communication Fault Tolerance Count (09-08). ‧ The communication error message will only be displayed when the number of communication errors exceeds the value set in parameter (09-08).

(8) Inverter Transmission Wait Time (09-09). ‧ Sets the response wait time (refer to Figure 4.3.102). If a response is not received after a command is sent, additional time may be required to switch from receive mode to transmit

Data length fixed8bits andstopbitfixed1 conflictwithselectable09-03/09-05 cards. Preservebothwithoutresolution.

Table4.3.33 Modbus specifications continued264–265 — PDF page 265

Source row Item Specifications
1 Communication protocols Modbus (supports both RTU and ASCII modes)
2 Number of Inverters Up to 31 units.

Manual — Message timing, Bluetooth and expansion card — page 266

Manual reference: physical PDF page 266. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

mode. This delay can be adjusted by setting 09-09.

Figure 4.3.102 Message Timing Window

• To enable Bluetooth communication, set inverter parameter 09-11 = 1 (Enabled). Afterward, even after power cycling, the inverter will automatically default to Bluetooth communication mode. Refer to the figure below:

To disable Bluetooth communication, press the DSP/FUN button at the top right to switch to the parameter page and turn off the Bluetooth function. • The Bluetooth app can be found by searching BT DriveLink in any app store.

If using an external communication expansion card, set inverter parameter 09-15 = 1.

Master to Inverter;Command Message;Inverter to Master;Response Message;t;09-09 setting;24 bits long. Only explicit labels, no inferred response durations.

FAULT;FWD;REV;SEQ;REF;REMOTE;Bluetooth Link...;LOC/REM;DSP/FUN;RESET;READ/ENTER;RUN;STOP;up/down arrows. Display example only.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Communication and PID parameter card — PDF page 266

Source row Parameter Name Scope/options and printed unit
1 09- 11 Bluetooth communication selection [0]: Disabled [1]: Enabled

Communication and PID parameter card — PDF page 266

Source row Parameter Name Scope/options and printed unit
1 09-15 Communication expansion card selection (Frame1 has no communication expansion card) [0]: Disabled [1]: Enabled

Manual — PID target, feedback and mode selection — page 267

Manual reference: physical PDF page 267. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

10 – PID Function Group

• When 10-00=0, this must be used in combination with 23-00=1 or 2 to activate PUMP function selection. Use parameter 23- 02 to set the working pressure, which acts as the PID target value. • When 10-00 = 1 or 2, the PID target can be assigned through an analog input terminal. The signal is linearly scaled—for example, 0~10V corresponds to a 0~100% target. If 2V is applied, it represents a 20% target value. • When 10-00 = 3, the PID target is a pulse input. The scaling and filtering of the pulse input are configured using related parameters from 03-30 (Pulse Input Scaling) to 03-34 (Pulse Input Filter Time). • For general PID applications, set 10-00 = 4 and use parameter 10-02 to configure the PID target value. • When 10-00 = 4, in addition to entering the percentage target via 10-02 (PID Target Value), you can monitor and adjust it from the main screen via parameter 12-38. The maximum target value can be set using 10-33 (PID Feedback Maximum Value). Decimal precision is determined by 10-34 (PID Decimal Width), and the display unit is defined by 10-35 (PID Unit). If 10-33 = 999, 10-34 = 1, and 10-35 = 3, and 10-02 is set to 10%, then the monitored value on the main screen (12-38) will display 9.9 PSI. Alternatively, the value can be edited directly through 12-38, but the maximum displayable value will be limited to 99.9 PSI (as constrained by the setting in 10-33). • When 10-00 = 6, the current frequency command (main frequency reference) will be proportionally mapped to the PID target. • When 10-00 = 8, the Keypad VR can be used to map its signal directly to the PID target.

Note: 10-00 and 10-01 cannot be assigned the same source. If the same value is set, the panel will display SE05.

PID Target Source Setting (10-00) / PID Feedback Source Setting (10-01) When using AI2 as the PID target or feedback input, ensure that parameter [04-00] matches the required input type (0 V~10 V or 4 mA~20 mA). Also, switch SW2 (for standard models H & C type) or SW4 (for advanced models E & G type) on the control board to the appropriate input type (V or I). Please refer to the inverter wiring diagram for details. PID Control Mode (10-03)

• When 10-03 is set to xxx0b, PID is disabled; when set to xxx1b, PID is enabled. The LCD operator will automatically switch: 16-00 (main screen) changes to PID Target Value (12-38); 16-01 (sub-monitor 1) changes to PID Feedback Value (12-39); 16-02 (sub-monitor 2) changes to Output Frequency (12-17). If the setting is invalid, the display will automatically revert to showing the frequency command as the main screen.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Communication and PID parameter card — PDF page 267

Source row Parameter Name Scope/options left column Scope/options right column
1 10- 00 PID target value source setting [0] Assigned by PUMP function target (see Group 23) [1] Assigned via AI1 [2] Assigned via AI2 [3] Assigned via pulse input [4] Assigned via parameter 10-02 [5] Reserved [6] Assigned via frequency command (00-05) [8] Assigned via panel VR

Communication and PID parameter card — PDF page 267

Source row Parameter Name Scope/options and printed unit
1 10- 01 PID feedback value source setting [1] Assigned via AI1 [2] Assigned via AI2 [3] Assigned via pulse input

Communication and PID parameter card — PDF page 267

Source row Parameter Name Scope/options and printed unit
1 10- 02 PID target value 【0.00~100.00】%

Communication and PID parameter card — PDF page 267

Source row Parameter Name Scope/options left column Scope/options right column
1 10- 03 PID control mode [xxx0b] PID disabled [xxx1b] PID enabled [xx0xb] PID with positive action [xx1xb] PID with negative action [x0xxb] PID controls based on error value (D control) [x1xxb] PID controls based on feedback value (D control) [0xxxb] PID output only [1xxxb]: PID output + frequency command

Manual — PID control parameters and definitions — page 268

Manual reference: physical PDF page 268. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• When 10-03 is set to xx0xb, PID output is forward; when set to xx1xb, PID output is reversed. When PID output is set to reversed, if the PID input is negative, the PID output frequency increases. Conversely, when PID output is set to forward and the PID input is negative, the PID output frequency decreases. • When 10-03 is set to x1xxb, the PID operates with derivative control based on the feedback value; when set to x0xxb, it performs standard PID control. See Figures 4.3.78 and 4.3.79 for detailed explanations. • When set to 0xxxb, the PID output alone determines the frequency, with 100% corresponding to the frequency set in parameter 01-02. When set to 1xxxb, the PID output is combined with the frequency command. At the start of operation, the output adds a percentage of the main frequency command (as selected by 00-05/00-06), and PID control begins thereafter.

Using PID Control The PID control function, consisting of Proportional (P), Integral (I), and Derivative (D), is used to reduce the error between the target command and the actual feedback value. PID Control Operation The characteristics of PID control are outlined below: ‧ P Control: The error between the input command (target value) and the actual control value (feedback value). This error is amplified by a configurable gain (P) to reduce system error. Even with increased gain, the system may still become unstable. ‧ I Control: This control integrates the proportional gain (P) over time, allowing higher gain to be applied to smaller errors. Increasing the integral time (I) reduces system responsiveness. ‧ D Control: This control works in contrast to integral control by applying the error signal to derivative control to increase system response speed. Be aware that using this function may easily lead to system instability and must be adjusted with care. ‧ PID Control: By combining the best characteristics of P, I, and D control, system performance can be optimized.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10- 04 Feedback gain 【0.01~10.00】

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10- 05 Proportional gain (P) 【0.00~10.00】

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10- 06 Integral time (I) 【0.0~100.0】Sec

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10- 07 Derivative time (D) 【0.00~10.00】Sec

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10- 09 PID bias voltage 【-100~100】%

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10- 10 PID First Delay Time 【0.00~10.00】%

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10-14 PID integral limit 【0.0~100.0】%

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10-23 PID Limits 【0.00~100.0】%

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10-24 PID output gain 【0.0~25.0】

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10-25 PID reverse output selection [0]: Reverse output not allowed [1]: Reverse output allowed

Communication and PID parameter card — PDF page 268

Source row Parameter Name Scope/options and printed unit
1 10-26 PID target acceleration/deceleration time 【0.0~25.5】Sec

Manual — PID control types and diagrams — page 269

Manual reference: physical PDF page 269. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Refer to Figure 4.3.103 PID Control Operation.

Figure 4.3.103 PID Control Operation

Types of PID Controllers The inverter supports two types of PID control: (a) Feedback-Derivative PID Control (when 10-03 = x1xxb) In feedback-derivative PID control, the feedback value is differentiated. By adjusting the target value and the control logic, different responses can be achieved. PID parameters should be carefully tuned to maintain system stability. Refer to Figure 4.3.104 Feedback-Derivative PID Control.

Figure 4.3.104 Feedback-Derivative PID Control

(b) Basic PID Control (when 10-03 = x0xxb) This is the standard form of PID control. Refer to Figure 4.3.105 Basic PID Control.

Figure 4.3.105 Basic PID Control

Deviation;t;Control;t;PID Control;I Control;P Control;D. Qualitative curve labels only, no unprinted numeric response.

Target value;P;I;D;Controlled process;Feedback value;printed plus and minus summation signs. Connectivity retained in original diagram.

Manual — PID input methods — page 270

Manual reference: physical PDF page 270. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ PID Input Method: To enable PID control, configure parameter 10-03 along with PID target value (10-00) and PID feedback value (10-01). (1) PID Target Value Input Method: ‧ Select the input method for the PID target value using parameter 10-00 from the following options: ‧ 10-00 = 1: Analog input AI1 (default) = 2: Analog input AI2 = 3: Pulse input = 4: Assigned via 10-02 = 6: Frequency command (00-05) (2) PID Feedback Value Input Method: ‧ Select the input method for the PID feedback value using parameter 10-01: ‧ 10-01 = 1: Analog input AI1 = 2: Analog input AI2 = 3: Pulse input

Figure 4.3.106 PID Input Method

Target inputs:AI1,10-00=1;AI2,10-00=2;Pulse Input,10-00=3;10-02 setting,10-00=4;Freq Command(00-05),10-00=6. PID Target SFS;10-26;ON;PID Setpoint;Target Value. Feedback inputs:AI1,10-01=1;AI2,10-01=2;Pulse Input,10-01=3. PID Feedback;10-27/10-33;PID feedback display unit conversion;Feedback Value. Labels only, no inferred topology.

Manual — PID block diagram with bounded raster uncertainty — page 271

Manual reference: physical PDF page 271. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Degraded raster numeric labels remain unreadable: upper limiter 0/9 digits and lower I-Limit sign not asserted. Source images retained; no inferred numeric labels.

PID Control Configuration ‧ PID Control Block Diagram The following diagram illustrates the PID control block structure.

Figure 4.3.107 PID Control Block Diagram

Bias10-09;10-03=xx0xb;×1;10-03=xx1xb;−1;PID output gain10-24;±200% Limit;PID Output;10-03=1xxxb;10-03=0xxxb;10-25=0;10-25=1;PID=OFF;PID=ON;Frequency Reference(Fref). PID=OFF:1.10-03=0(PID Disabled);2.during JOG mode;3.multi-function digital input(03-00–03-07 setting=29). Freq Command(00-05),10-00=6;AI1,10-00=1;AI2,10-00=2;Pulse Input,10-00=3;10-02,10-00=4;Target Value;Feedback Value10-01;Feedback Gain10-04;D10-07;10-03=x0xxb;10-03=x1xxb;PID Input(Deviation);P10-05;I10-06;10-14(I-Limit);D10-07;Integral Reset(using Multi-function Digital Input);10-23(PID Limit),100%,−100%;10-10(Primary delay). Upper limiter percentage labels and lower I-Limit sign are raster-ambiguous: retained as unresolved image evidence, not assigned a numerical value. Original topology authoritative.

Manual — PID tuning and fine adjustment — page 272

Manual reference: physical PDF page 272. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

PID Tuning Method ‧ Use the following procedure to start PID control: (1) Enable PID control (set 10-03 greater than “xxx0b”). (2) Increase gain (10-05) as much as possible until just before oscillation occurs. (3) Decrease integral time (10-06) as much as possible until just before oscillation occurs. (4) Increase derivative time (10-07) as much as possible until just before oscillation occurs. ‧ The proportional (P), integral (I), and derivative (D) functions provide a usable system for closed-loop control or for adjusting variables such as pressure or temperature. Adjustment is performed by comparing the target and feedback values to generate an error signal. ‧ The polarity of PID output can be selected using parameter 10-03 (set to xx0xb for forward output, or xx1xb for reverse output). When PID output is set to reversed, if the PID input is negative, the PID output frequency increases. Conversely, when PID output is set to forward and the PID input is negative, the PID output frequency decreases. ‧ PID feedback can be adjusted via parameter 10-04 (PID Feedback Gain), and through the analog input gain and bias of the feedback source (AI1 or AI2). In PID control, parameter 10-14 (PID Integral Limit) is used to prevent excessive integral accumulation. When a sudden load change occurs, it may damage the machine or cause motor stalling. In such cases, reducing the value of 10-14 speeds up inverter response. ‧ Parameter 10-23 (PID Limit) prevents overshoot due to PID calculation, capping output at 100% of maximum frequency. ‧ Parameter 10-10 (PID Output Low-Pass Filter Time Constant) prevents load resonance or lack of stiffness during high-load resistance. If this occurs, increase the filter time beyond the resonance period. To improve inverter response, decrease the setting. ‧ Parameter 10-09 (PID Bias) adjusts PID compensation. Increments are in 0.1% units. ‧ Parameter 10-24 (PID Output Gain) adjusts the compensation amount added to the frequency reference from the PID output. ‧ When PID output is negative, parameter 10-25 (PID Reverse Output Selection) can reverse inverter direction. However, if reverse output is disabled, PID output is limited to 0. ‧ 10-26 (PID Target SFS) sets rise/fall time for adjusting the PID target value. Inverter acceleration/deceleration is controlled by parameters 00-14~17 and 00-21~24. According to the settings of 00-14~17 to 00-21~24, use PID control when load resonance or instability occurs. If this occurs, reduce the acceleration/deceleration time (00-14~17 to 00-21~24) until the system stabilizes, and maintain the necessary acceleration/deceleration time. To disable this function, configure one of the multifunction digital inputs 03-00~03-07 to 36 (Disable PID Target SFS).

PID Fine Tuning ‧ All PID control parameters are interrelated and must be adjusted to appropriate values. Use the following procedure to tune the system to a more stable state. (1) Increase or decrease the proportional (P) gain until output fluctuation is minimized. (2) Increasing the integral (I) time, like increasing the proportional gain, reduces system stability. Therefore, the integral time should be adjusted to match the maximum usable proportional gain without compromising system stability. However, increasing the integral time will also increase system response time. (3) If deemed necessary, the derivative (D) time or the inverter acceleration/deceleration time can be adjusted to reduce overshoot during startup.

Manual — PID response examples — page 273

Manual reference: physical PDF page 273. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ Individual PID control parameters can be fine-tuned as follows:

(1) Reduce overshoot

(2) Stabilize control

(3) Reduce long-period oscillation

(4) Reduce short-period oscillation

If overshoot occurs, shorten the derivative time (D) and lengthen the integral time (I).

To stabilize the system quickly when overshoot occurs, shorten the integral time (I) and lengthen the derivative time (D).

If periodic oscillation occurs, adjusting the integral time (I) can effectively reduce long-period oscillation.

If short-period oscillation occurs, adjust both derivative (D) and proportional (P) gain to improve the response. The derivative (D) and proportional (P) gains can be adjusted simultaneously to improve performance.

Output;Before;After;t. Qualitative examples only; no inferred amplitude, period or gain.

Output;After;Before;t. Qualitative examples only; no inferred amplitude, period or gain.

Manual — PID feedback disconnection — page 274

Manual reference: physical PDF page 274. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• The PID control function provides a closed-loop control system. If the PID feedback is disconnected, the inverter output frequency may rise to the maximum frequency. Therefore, when using PID control, ensure the feedback disconnection detection feature is enabled. • If parameter 10-11 (PID Feedback Disconnection Detection Option) is set to 1, and the feedback signal drops below the value set in 10-12 (Detection Threshold) for longer than the time set in 10-13 (Detection Time), a warning message "Pb" will appear on the digital operator, and the inverter will continue running. • If parameter 10-11 = 2, a feedback disconnection fault message "Fb" will be displayed, the fault relay will activate, and the inverter will stop running. • Refer to the operation timing diagram in Figure 4.3.108.

Figure 4.3.108 PID Feedback Loss Detection

Feedback value;10-12;t;FBL detection;t;t1;10-13;10-13. Source labels only; no unprinted feedback amplitude or elapsed time.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

PID and auxiliary parameter card — PDF page 274

Source row Parameter Name Scope/options and printed unit
1 10-11 PID feedback disconnection detection [0]: Disabled [1]: Warning [2]: Fault

PID and auxiliary parameter card — PDF page 274

Source row Parameter Name Scope/options and printed unit
1 10-12 PID feedback disconnection detection threshold 【0~100】%

PID and auxiliary parameter card — PDF page 274

Source row Parameter Name Scope/options and printed unit
1 10-13 PID feedback disconnection detection time 【0.0~10.0】Sec

Manual — PID sleep/wake settings and diagrams — page 275

Manual reference: physical PDF page 275. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

*: (When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz) • Parameter 10-17 defines the sleep start frequency for general PID and is not shared with parameter 23- 10 (Constant Pressure Sleep Frequency) used by the PUMP function. • To improve energy efficiency, the PID sleep/wake function allows the motor to automatically start or stop • Refer to Figure 4.3.109 PID Sleep/Wake Operation:

(a) PID Control Block Diagram

(b) PID Sleep/Wake Timing Diagram

(c) PID Sleep Compensation Frequency / Wake Timing Diagram Figure 4.3.109 PID Sleep/Wake Operation

Target Value;Feedback Value;PID;Freq Reference(Fref);10-40=0;10-40=1;PID Sleep/Wake-up function;PID Sleep compen Frequency/Wake-up function;10-29=0;10-29=1 or2;PID=OFF;PID=ON;Soft Start;f;t;Output Frequency(Fout);plus/minus signs. Labels only, topology retainedinoriginal.

Output Frequency;Wake-up Frequency(10-19);Sleep Frequency(10-17);Frequency Reference(Fref);Output Frequency(Fout);sleep delay time(10-18);wake up delay time(10-20);t. Qualitative curves; no inferred amplitudes or delays.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

PID and auxiliary parameter card — PDF page 275

Source row Parameter Name Scope/options and printed unit
1 10-17 *PID sleep start frequency 【0.00~599.00】Hz

PID and auxiliary parameter card — PDF page 275

Source row Parameter Name Scope/options and printed unit
1 10-20 PID wake-up delay time 【0.0~255.5】Sec

PID and auxiliary parameter card — PDF page 275

Source row Parameter Name Scope/options and printed unit
1 10-18 PID sleep delay time 【0.0~255.5】Sec

PID and auxiliary parameter card — PDF page 275

Source row Parameter Name Scope/options and printed unit
1 10-29 PID sleep selection [0]: Disabled [1]: Enabled [2]: Controlled via DI

PID and auxiliary parameter card — PDF page 275

Source row Parameter Name Scope/options and printed unit
1 10-19 *PID wake-up start frequency 【0.00~599.00】Hz

PID and auxiliary parameter card — PDF page 275

Source row Parameter Name Scope/options and printed unit
1 10-40 PID forced sleep frequency operation selection [0]: Disabled [1]: Enabled

Manual — Sleep conditions andPID1/PID2switching — page 276

Manual reference: physical PDF page 276. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• If 10-40 = 0 (as shown in diagram b), when the output frequency (Fout) drops below the sleep frequency set in 10-17, the PID sleep mode timer starts. The output frequency follows the reference frequency (Fref) and decreases until it reaches the minimum frequency set in 01-08 (Fmin). After the delay time set in 10-18 (PID Sleep Delay Time) is reached, the inverter motor will gradually decelerate to a stop, and the inverter will enter sleep mode. • If parameter 10-40 = 1 (as shown in diagram c), when the output frequency (Fout) drops below the PID sleep frequency set in 10-17, the PID sleep mode timer will activate. The output frequency will follow the reference frequency (Fref) and decrease until it reaches the minimum output frequency (Fmin) set in 01-08. Once the delay time set in 10-18 (PID Sleep Delay Time) elapses, the motor will ramp up to the sleep frequency defined in 10-17. (This is used in applications requiring a fixed frequency.) • When the inverter enters sleep mode and stops the motor, the PID control function remains active. When the reference frequency increases and exceeds the wake frequency set in 10-19, and the delay time set in 10-20 elapses, the inverter motor will restart and ramp up to the reference frequency. Example: If wake frequency < sleep frequency: startup will follow the sleep frequency; sleep will follow the wake frequency. If wake frequency > sleep frequency: startup will follow the wake frequency; sleep will follow the sleep frequency. Ex Sleep is only valid in the forward direction. If 10-25 = 1 (Allow Reverse Output), sleep must be disabled. • 10-00 and 10-01 cannot be set to the same source. If the same value is assigned, the panel will display the “SE05” PID Selection Error message. • If PID sleep is enabled or set via DI (10-29 = 1 or 2), and PID Reverse Output Selection (10-25) is set to 1 (Allow Reverse Output), the panel will display the “SE05” PID Selection Error message. • If PID sleep is enabled or set via DI (10-29 = 1 or 2), and PID Control Mode 10-03 = 1xxxb (PID Output + Frequency Command), the panel will display the “SE05” PID Selection Error message. • Use parameter 10-29 to enable/disable the PID sleep function. 10-29 = 0: PID sleep function (sleep mode) is disabled. = 1: PID sleep behavior is controlled by parameters 10-17 and 10-18 as described above. = 2: PID sleep mode is triggered via a multifunction digital input.

If output frequency ≥ 10-22, PID1 (10-05~10-07) is used. If output frequency < 10-22, PID2 (10-36~10-38) is used.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

PID and auxiliary parameter card — PDF page 276

Source row Parameter Name Scope/options and printed unit
1 10-22 PID1/PID2 frequency switching point 【0.00~599.00】

Manual — Feedback display andlimits — page 277

Manual reference: physical PDF page 277. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ PID feedback value can be monitored via parameters. The display unit can be configured using 10-27 (PID Feedback Display Offset) and 10-33 (PID Feedback Maximum Value). ‧ For example, a 0–10V or 4–20mA feedback signal can be displayed as pressure. Use parameter 10-27 to set the baseline offset level for 0V or 4mA, and parameter 10-33 to define the corresponding value at 10V or 20mA. ‧ Refer to Figure 4.3.110 for display unit conversion.

Figure 4.3.110 Display Unit Conversion Example: Feedback signal: 0V = 0% = 1.0 PSI 10V = 100% = 20.0 PSI Parameter settings: 10-27 = 10 (0% feedback value) 10-33 = 200 (100% feedback value)

The PID target value is constrained within the upper and lower limits set by these parameters.

• When 10-33Feedback Maximum Value is set, it becomes the 100% reference value for parameter 10-02. • When 10-34 (PID Decimal Width) is set, it allows users to configure how values are displayed in decimal format. For example, setting it to 1 will display one decimal place (XXX.X), while setting it to 2 will display two decimal places (XX.XX). • Parameter 10-35 (PID Unit) can be set according to user needs. Note: When switching PID modes using the LED operator, 10-33 must be set to a value less than 1000 and 10-34 must be set to 1; otherwise, an “SE05” PID Setting Error will occur.

Display unit;10-33;10-27;Feedback signal;0V(4mA);10V(20mA). Explicit endpoint labels only.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

PID and auxiliary parameter card — PDF page 277

Source row Parameter Name Scope/options and printed unit
1 10-27 PID feedback display bias voltage 【0~9999】

PID and auxiliary parameter card — PDF page 277

Source row Parameter Name Scope/options and printed unit
1 10-30 PID target upper limit 【0 ~ 100】%

PID and auxiliary parameter card — PDF page 277

Source row Parameter Name Scope/options and printed unit
1 10-31 PID target lower limit 【0 ~ 100】%

PID and auxiliary parameter card — PDF page 277

Source row Parameter Name Scope/options and printed unit
1 10- 33 PID feedback maximum value 【1~10000】

PID and auxiliary parameter card — PDF page 277

Source row Parameter Name Scope/options and printed unit
1 10- 34 PID decimal width 【0~4】

PID and auxiliary parameter card — PDF page 277

Source row Parameter Name Scope/options and printed unit
1 10- 35 PID unit 【0~24】

Manual — D-type PID anddisconnection frequency — page 278

Manual reference: physical PDF page 278. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When a PID feedback disconnection warning occurs, the frequency command will follow the value set in 10- 39 (PID Disconnection Output Frequency Setting). Once the disconnection warning is cleared, PID control resumes as normal. *: When the motor’s maximum output frequency exceeds 300 Hz, the frequency resolution is 0.1 Hz.

Signal Input Type and Processing: When parameter 10-41 is set to 1 (D-type PID), external input signals can be proportionally converted, so that their minimum and maximum values correspond to the desired speed limits. Corrected Signal Control Diagram:

Figure 4.3.111 Corrected Signal Control Diagram for Input Signals

• Use the following procedure to activate D-type PID control: (1) 10-03: Set PID Control Mode to 1001b. (2) 10-00: Set PID Target Source to 4 (set via 10-02). (3) 10-01: Set PID Feedback Source to 2 (AI2). (4) 00-05: Set Primary Frequency Command Source to 1 (external analog input AI1). (5) 10-29: Set PID Sleep Selection to 0 (disabled). • The maximum frequency is limited by parameter 10-08. • Whether reverse is allowed is determined by parameter 10-25 (Reverse Output Restriction). • Whether to superimpose the frequency source from 00-05 depends on the most significant bit of the value set in 10-03. • PID controller responsiveness can be adjusted using 10-36: PID2 Proportional Gain; 10-37: PID2 Integral Time; 10-38: PID2 Derivative Time. • When parameter 10-15 (PID Variation Mode) is set to 1 (Proportional), the PID correction multiplier is calculated by multiplying the ratio of the Maximum Frequency (01-02) to the Base Frequency (01-12) by the frequency from the source defined in 00-05, and then multiplying the result by 10-16 (PID Scaling Factor). • When parameter 10-15 (PID Variation Mode) is set to 0 (Direct), the correction multiplier for PID is calculated by multiplying parameter 10-16 (PID Scaling Factor) by the Maximum Frequency (01-02).

Maximum frequency(01-02);Parameters10-15(adjustmode):0=Not select,1=Proportional,2=Direct;Parameters00-05Frequency source selection;Parameters10-16Adjustratio;PIDcommand;PIDfeedback;PID;Parameters00-05Frequency source superposition selection;Speed command;×;×;+. Original geometry authoritative; source option0/2conflict separatelyflagged.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

PID and auxiliary parameter card — PDF page 278

Source row Parameter Name Scope/options and printed unit
1 10- 39 PID Disconnection Output Frequency Setting 【0.00~599.00】Hz

PID and auxiliary parameter card — PDF page 278

Source row Parameter Name Scope/options and printed unit
1 10- 08 AI1 frequency limit 【0.00~599.00】Hz

PID and auxiliary parameter card — PDF page 278

Source row Parameter Name Scope/options and printed unit
1 10- 16 PID change scale 【0~100】

PID and auxiliary parameter card — PDF page 278

Source row Parameter Name Scope/options and printed unit
1 10- 15 PID change mode 【0~2】

PID and auxiliary parameter card — PDF page 278

Source row Parameter Name Scope/options and printed unit
1 10- 41 PID mode switch [0]:Standard PID [1]:D-type PID

Manual — Fire-modePID3parameters — page 279

Manual reference: physical PDF page 279. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• For descriptions of Fire Mode PID functions, please refer to the Fire Mode features in Group 08.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

PID and auxiliary parameter card — PDF page 279

Source row Parameter Name Scope/options and printed unit
1 10- 47 Proportional gain 3 (P) 【0.00~10.00】

PID and auxiliary parameter card — PDF page 279

Source row Parameter Name Scope/options and printed unit
1 10- 48 Integral time 3 (I) 【0.0~100.0】Sec

PID and auxiliary parameter card — PDF page 279

Source row Parameter Name Scope/options and printed unit
1 10- 49 Derivative time 3 (D) 【0.00~10.00】Sec

Manual — Carrier frequency,cables andsoftmodulation — page 280

Manual reference: physical PDF page 280. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11 – Auxiliary Function Group

• If the motor rotation direction is set to 1 or 2, the motor will only run in the specified direction and will not accept commands in the opposite direction. • Forward or reverse commands can be given via control terminals or the LED digital keypad. • This parameter is suitable for applications involving pumps or fans that rotate in reverse.

① When 11-01 = 2 to 16, the PWM carrier frequency is set in kHz. ② In SLV and SV modes, the minimum value for 11-01 is 2. Due to sampling rate, a setting of 4 kHz is recommended, and motor cable length should ideally be within 100 meters. ③ The available setting range depends on the inverter capacity (13-00). When the carrier frequency is set low, motor noise increases, but RFI, EMI, and leakage current are reduced. Refer to Table 4.3.34 for carrier frequency effects. Table 4.3.34 Carrier Frequency Effects

‧ The available range and default value for this parameter depend on inverter capacity. Please refer to Chapter 3 – Factory Default Specifications for the maximum selectable limit of this parameter. ‧ Inverters with lower capacity can support higher carrier frequencies. Refer to Chapter 3 – Derating Curve. ‧ Lowering the setting reduces motor loss and temperature; increasing it will result in greater loss and heat. ‧ If the cable length between the inverter and the motor is too long, high-frequency leakage current may increase inverter output current and interfere with peripheral equipment. To avoid such conditions, adjust the carrier frequency according to Table 4.3.35. Table 4.3.35 Cable Length and Carrier Frequency

‧ A larger energy-saving coefficient (11-24) results in a higher output voltage.

Set 11-02 = 1 to enable Soft Modulation 1, which improves motor noise quality. Soft modulation control can reduce the metallic sound generated by the motor, making it more comfortable to the human ear, while also minimizing RFI noise. The factory default setting has soft modulation disabled. When Soft Modulation 1 is enabled, the maximum carrier frequency is limited to 8 kHz. Set 11-02 = 2 to enable Soft Modulation 2. Users can adjust it according to acoustic preferences via 11-66 (Modulation Mode Switching Frequency), 11-67 (Soft Modulation 2 Detection Range), and 11-68 (Soft

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Qualitative source trends, no interpolated measurements. Header literal6KH retained; card11-01range2–16kHz separate.

Source limits depend oninvertercapacity and cablelength; exactprinted intervalboundaries retainedwithoutresolving50m overlap.

PID and auxiliary parameter card — PDF page 280

Source row Parameter Name Scope/options and printed unit
1 11- 00 Motor direction locking command [0]: Forward and reverse allowed [1]: Forward only [2]: Reverse only

PID and auxiliary parameter card — PDF page 280

Source row Parameter Name Scope/options and printed unit
1 11- 01 Carrier frequency 【2~16】:2~16 KHz

PID and auxiliary parameter card — PDF page 280

Source row Parameter Name Scope/options and printed unit
1 11- 02 Soft modulation selection [0]: Disabled [1]: Soft Modulation 1 [2]: Soft Modulation 2

Table4.3.34 Carrier frequency effects — PDF page 280

Source row Carrier frequency 1KHz--6KH—10KHz—16KHz
1 Motor Noise High -------------- Low
2 Output Current Waveform Poor ------- Good ----- Poor
3 Interface Noise Low ---------------- High
4 Leakage Current Low ---------------- High
5 Heat Loss Low ---------------- High

Table4.3.35 Cable length and carrier frequency — PDF page 280

Source row Cable length Carrier frequency11-01 maximum and setting
1 < 30 meters Maximum 16 kHz (11-01 = 16 kHz)
2 30 meters – 50 meters Maximum 10 kHz (11-01 = 10KHz)
3 50 meters – 100 meters Maximum 5 kHz (11-01 = 5KHz)
4 > 100 meters Maximum 2 kHz (11-01 = 2KHz)

Manual — Soft modulation interlocks andS-curve headings — page 281

Manual reference: physical PDF page 281. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Modulation 2 Detection Start Frequency).

Modulation Mode Switching Start Frequency (11-66): When the inverter output frequency exceeds the value set in parameter 11-66, the modulation mode will switch.

When the inverter output frequency exceeds the value set in parameter 11-68, the noise detection function is triggered. Based on the value of 11-67, the electromagnetic noise generated during motor operation is adjusted accordingly. Note: When Soft Modulation is set to 11-02 = 2, it cannot be enabled simultaneously with Estimator Mode 22-26 and Speed Search Mode Selection 07-32. Please verify the status of these two parameters. Note: When 11-02 = 2, the total value of parameters 11-01 and 11-67 must not exceed the carrier frequency upper limit of the inverter model. To ensure proper operation, the following interlock mechanisms apply: • If a parameter setting error occurs while configuring 11-01, and 11-02 = 2 with 11-01 + 11-67 > the model's carrier frequency upper limit, adjust either 11-02 or 11-67 to an appropriate value first. • If a parameter setting error occurs while configuring 11-67, and 11-02 = 2 with 11-01 + 11-67 > the model's carrier frequency upper limit, adjust either 11-02 or 11-01 to an appropriate value first. • If a parameter setting error occurs while configuring 11-01 or 11-67 under the condition 11-02 = 2, check whether the attempted combination exceeds the carrier frequency upper limit (i.e., 11-01 + 11-67 > model limit). • If a parameter setting error occurs while attempting to set 11-02 = 2, it indicates that the sum of 11-01 and 11-67 exceeds the carrier frequency limit for the inverter model. Adjust 11-01 or 11-67 to a suitable range before setting 11-02 = 2.

If the inverter’s internal protection detects overheating, the carrier frequency will automatically decrease. Once the temperature returns to normal, the carrier frequency will automatically return to the value set in parameter (11-01). (1). 11-03 = 0 When the automatic carrier frequency adjustment function is disabled, the carrier frequency operates according to the value set in 11-01. (2). 11-03 = 1 When the automatic carrier frequency adjustment function is enabled, if the heat sink temperature exceeds the set value, the inverter will automatically reduce the carrier frequency to minimize heat loss and prevent tripping due to overheating. This also helps extend the service life of the inverter.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

11-04/05/06 headings share scope continued beneath11-07 onPDF282; no scope cell fabricated on281.

PID and auxiliary parameter card — PDF page 281

Source row Parameter Name Scope/options and printed unit
1 11- 66 Modulation mode switching starting frequency 【6.00~60.00】

PID and auxiliary parameter card — PDF page 281

Source row Parameter Name Scope/options and printed unit
1 11- 67 Soft modulation 2 detection range 【0~12000】

PID and auxiliary parameter card — PDF page 281

Source row Parameter Name Scope/options and printed unit
1 11- 68 Soft modulation 2 detection starting frequency 【6.00~60.00】

PID and auxiliary parameter card — PDF page 281

Source row Parameter Name Scope/options and printed unit
1 11- 03 Automatic carrier reduction selection [0]: Disabled [1]: Enabled

S-curve headings continued on PDF282 — PDF page 281

Source row Parameter Name
1 11- 04 Acceleration start S curve time setting
2 11- 05 Acceleration end S curve time setting
3 11- 06 Deceleration start S curve time setting

Manual — S-curve scope andequations — page 282

Manual reference: physical PDF page 282. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Using S-curve characteristics for acceleration and deceleration helps reduce mechanical shocks generated at the start or stop of load operation. For the E710 inverter, the S-curve times can be set independently for acceleration start (11-04), acceleration end (11-05), deceleration start (11-06), and deceleration end (11-07). The relationship between the parameters is illustrated in Figure 4.3.112.

Figure 4.3.112 S-Curve Characteristics • After setting the S-curve times, the acceleration and deceleration characteristics are as follows:

Run Command;ON;OFF;t;Output Frequency;t;S1,11-04;S2,11-05;S3,11-06;S4,11-07. Explicit labels, no inferred time orfrequency values.

Acceleration Time = Acceleration Time1(or2) + [(11-04)+(11-05)] /2. Printedfraction grouping preserved, no computed duration.

Deceleration Time = Deceleration Time1(or2) + [(11-06)+(11-07)] /2. Printedfraction grouping preserved, no computed duration.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

PID and auxiliary parameter card — PDF page 282

Source row Parameter Name Scope/options and printed unit
1 11- 07 Deceleration end S curve time setting 【0.00~2.50】Sec

Manual — Frequency jump andautomaticreturn — page 283

Manual reference: physical PDF page 283. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• These settings allow for designated “jump” frequencies within the output frequency range of the inverter, enabling the motor to operate without interference from mechanical system resonance. • Within the jump frequency range, operation is prohibited; however, frequency increase/decrease during acceleration and deceleration is continuous and does not skip. • To disable this function, set Frequency Jump Points 1–3 (11-08 to 11-10) to 0.0 Hz. • For Frequency Jump Points 1–3 (11-08 to 11-10), the center frequencies can be designated as jump frequencies. • For parameter 11-11, set the frequency jump width. The jump range is defined as: Jump Frequency ± Frequency Jump Width. • The relationship between output frequency and jump frequencies is shown in Figure 4.3.113.

Figure 4.3.113 Frequency Jump Operation.

• When parameter 04-05 (Multi-function Analog Input AI2 Function Selection) is set to 9 (Jump Frequency Setting 4), a fourth jump frequency point can be configured. For Jump Frequency Setting 4 operation, refer to Figure 4.3.66. • When the configured jump speeds overlap, the total is treated as a combined jump frequency range. Refer to Figure 4.3.114.

Figure 4.3.114 Overlapping Jump Frequencies

• If no key is pressed on the digital operator within the time set in parameter 11-13 (Auto Return Key Time), the digital operator will automatically return to the main mode screen. • When set to 0, the auto return function is disabled. Pressing the return key returns to the previous menu.

Output Frequency;Frequency Reference;11-08;11-09;11-10;11-11;11-11;11-11. Source labels only, no inferred frequencyvalues.

Output Frequency;Frequency Reference;Actual jump width;Jump2;Jump1. Source labels only; no inferred overlap boundaries.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

11-08/09/10 share onephysical scope row below; shared range is separate record, no lost applicability.

Applies tothree preceding jump-frequencyheadings onthispage.

PID and auxiliary parameter card — PDF page 283

Source row Parameter Name Scope/options and printed unit
1 11- 11 Jump frequency width 【0.0~25.5】Hz

PID and auxiliary parameter card — PDF page 283

Source row Parameter Name Scope/options and printed unit
1 11- 13 Automatic return time 【0~120】Sec

Three jump-frequency headings and shared scope — PDF page 283

Source row Parameter Name
1 11- 08 Jump frequency 1
2 11- 09 Jump frequency 2
3 11- 10 Jump frequency 3

Shared scope for11-08/09/10 — PDF page 283

Source row Shared printed scope
1 【0.0~599.0】Hz

Manual — Manual energy saving — page 284

Manual reference: physical PDF page 284. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• When the manual energy-saving command is activated via multi-function digital input (03-00 to 03-07 = 20), the Manual Energy Saving (MES) control function starts. • When operating under light load, the inverter reduces output voltage to achieve energy saving. Therefore, under general load conditions, the manual energy-saving command should be turned off. (1) Manual Energy Saving Gain (11-12) ‧ When the manual energy-saving command is input, parameter 11-12 determines the inverter output voltage. ‧ When MES control is turned on or off, the voltage recovery time (07-23) depends on the change ratio of the output voltage. (2) Manual Energy Saving Frequency (11-18) ‧ When the reference frequency exceeds 11-18 and the motor speed is within the allowable range, the manual energy saving command is activated. Refer to Figure 4.3.115 Manual Energy Saving Operation.

Figure 4.3.115 Manual Energy Saving Operation.

RUN Command;OFF;ON;Manual Energy Saving Command;OFF;ON;Output Frequency;Frequency reference ≥11-18;Output Voltage;Voltage change rated=07-23(Voltage recovery time;V/f pattern(01-02 to01-09)×11-12. Literal labels; parenthesis appears unclosed in source. No waveform values inferred.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 284

Source row Parameter Name Scope/options and printed unit
1 11- 12 Manual energy-saving gain 【0~100】%

Auxiliary parameter card — PDF page 284

Source row Parameter Name Scope/options and printed unit
1 11- 18 Manual energy-saving frequency 【0.0~599.0】Hz

Manual — Automatic energy saving — page 285

Manual reference: physical PDF page 285. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• In V/F control mode, the automatic energy saving function (AES) automatically adjusts the optimal output voltage based on the load, reducing inverter output current, and the output power varies proportionally with the load. When the load exceeds 70%, energy saving is minimal; as the load decreases, energy saving increases. • The parameters of the automatic energy saving function are pre-configured at the factory and typically do not require adjustment. If the motor characteristics differ significantly from TECO’s standards, adjust the parameters as follows: (1) Auto Energy Saving Control Mode (11-19) Enable auto energy saving by setting 11-19 to 1. (2) Auto Energy Saving Filter Time (11-20) Sets the output filter time for the AES function. Typically does not require adjustment. (3) AES Tuning Parameters (11-21 to 11-22) In AES Control Mode, the optimal voltage is calculated based on the load power demand. However, the calculated value may vary due to temperature and motor characteristics. In some cases, the optimal voltage must be adjusted accordingly. To obtain the optimal voltage, configure the following AES tuning parameters: a. AES Tuning Voltage Limit (11-21) ‧ Sets the voltage limit range during tuning. ‧ Configure corresponding ranges for 220V and 440V models (100% = 220V or 440V). ‧ Close tuning operation. ‧ Refer to Figure 4.3.116.

Figure 4.3.116 Voltage Limit for Tuning Operation. b. AES Tuning Control Cycle Time (11-22) ‧ Time constant for detecting output power. ‧ When load variation is high, reduce the setting of 11-22 to improve response. ‧ If the load becomes lighter and 11-22 is set too low, the motor may become unstable. (4) Energy Saving Detection Level (11-23) When output power variation is less than the detection level, energy saving efficiency improves. (5) Energy Saving Coefficient (11-24). ‧ Calculates the optimal value when motor efficiency is maximized; the result is used as a voltage reference. ‧ The factory sets 11-24 based on the matching capacity of the motor and inverter. If the motor capacity differs, adjust parameter 13-00 (Motor Rated Output Power) and fine-tune 11-24 to reach the minimum required output voltage. ‧ A larger energy-saving coefficient (11-24) results in a higher output voltage.

Voltage Limit;11-21;Output Voltage. Qualitative graph, no unprinted axesvalues.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 285

Source row Parameter Name Scope/options and printed unit
1 11- 19 Automatic energy-saving function [0]: Auto Energy Saving Disabled [1]: Auto Energy Saving Enabled

Auxiliary parameter card — PDF page 285

Source row Parameter Name Scope/options and printed unit
1 11- 22 Energy-saving adjustment time 【0~5000】mSec

Auxiliary parameter card — PDF page 285

Source row Parameter Name Scope/options and printed unit
1 11- 20 Automatic energy-saving filter time 【0~200】mSec

Auxiliary parameter card — PDF page 285

Source row Parameter Name Scope/options and printed unit
1 11- 23 Energy-saving detection threshold 【0~100】%

Auxiliary parameter card — PDF page 285

Source row Parameter Name Scope/options and printed unit
1 11- 21 Energy-saving adjustment voltage upper limit 【0~100】%

Auxiliary parameter card — PDF page 285

Source row Parameter Name Scope/options and printed unit
1 11- 24 Automatic energy-saving coefficient 【0.00~655.34】

Manual — Thermal output-frequency reduction — page 286

Manual reference: physical PDF page 286. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

If the inverter detects excessive internal temperature and the automatic carrier frequency adjustment is not enabled (11-03 = 0), or is enabled (11-03 = 1) but the carrier frequency has already dropped to its minimum value, the inverter will automatically reduce the output frequency by 30% of its rated speed. (1) 11-29=0: Automatic output derating function is disabled. Carrier frequency follows 11-01 or 11-03 settings. (2) 11-29=1: Automatic output derating function is enabled. When the heatsink temperature is too high, the output frequency will be reduced to 70% of the rated speed.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 286

Source row Parameter Name Scope/options and printed unit
1 11- 29 Automatic output frequency reduction selection [0]: Disabled [1]: Enabled

Manual — Over-voltage settings andstamping example — page 287

Manual reference: physical PDF page 287. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

*: (When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz) Over-voltage suppression can be used in applications where energy feedback into the inverter is likely. Example: In stamping applications, there are two scenarios that cause excessive energy feedback into the inverter. (1) When the cam clutch is disengaged, the motor accelerates and drives the flywheel. As the motor decelerates, the large inertia of the flywheel causes it to spin faster than the motor, feeding energy back into the inverter. (2) When the cam clutch is engaged, the motor drives the flywheel and compresses the spring. Once the cam passes its peak, the spring releases energy to the flywheel, generating excessive feedback into the inverter.

Figure 4.3.117 Stamping Operation

Inverter;f_out;Motor;f_motor;Gear box;FLYWHEEL;cam clutch;Motoring:f_out>f_motor;Overhauling:f_out<f_motor. Mechanical/electrical diagram geometry retainedinoriginal.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

11-40 rightcolumnscope spansleft11-35and11-36rows; includesoptions0–4. Noverticalrowinference.

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 28 Over-voltage prevention 2 frequency gain 【1~200】%

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 33 DC voltage filter rise rate [0.1~10.0]V

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 34 DC voltage filter drop rate 【0.1~10.0】V

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 35 DC voltage filter dead zone threshold 【0.0~99.0】V

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 36 Over-voltage prevention frequency gain 【0.000~1.000】

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 37 * Over-voltage prevention frequency limit 【0.00~599.00】Hz

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 38 Over-voltage prevention deceleration start voltage 200V :【200~400】V 400V :【400~800】V

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 39 Over-voltage prevention deceleration stop voltage 200V :【300~400】V 400V :【600~800】V

Auxiliary parameter card — PDF page 287

Source row Parameter Name Scope/options and printed unit
1 11- 40 Over-voltage prevention selection [0]: Disabled [1]: Over-voltage Prevention Mode 1 [2]: Over-voltage Prevention Mode 2 [3]: Over-voltage Prevention Mode 3 [4]: Over-voltage Prevention Mode 4

Manual — OVP operation andtiming — page 288

Manual reference: physical PDF page 288. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The over-voltage protection (OVP) function monitors and adjusts energy feedback by modifying motor acceleration/deceleration rates. When speed reference is decreased, the motor begins to decelerate. Conversely, if the frequency is fixed and regenerative energy is detected, the inverter accelerates the motor to reduce the regenerated voltage. Refer to Figure 4.3.119 Over-voltage Protection (OVP) Operation.

Figure 4.3.118 OVP Operation When 11-40 is set to Over-voltage Prevention Mode 1 1) A DC voltage filter provides a stable reference value to determine voltage variation during energy regeneration. ‧ 11-33 (DC Voltage Filter Rise Rate) adjusts the filter’s gain. When the DC voltage exceeds 11-33 + 11-35 (DC voltage filter deadband), the filter output increases. ‧ 11-34 (DC Voltage Filter Fall Rate) adjusts the rate of descent of the DC voltage filter. When the DC voltage drops below 11-33 + 11-35 (DC voltage filter deadband), the filter output decreases. ‧ 12-20 (DC Voltage Filtered Value) allows monitoring of the filtered DC voltage output. ‧ The fall rate of the DC voltage filter can be set faster than the rise rate. For example, by setting 11- 34 higher than 11-33. 2) When the inverter is running and the frequency reference is fixed, the OVP function monitors excessive DC voltage. ‧ The excessive DC voltage is multiplied by 11-36 (OVP Frequency Gain) and converted into a frequency, causing the inverter to accelerate and suppress regenerative energy. ‧ When regenerative energy decreases, the inverter output returns to the input frequency reference, and the deceleration rate is determined by the DC voltage, as shown in Figure 4.3.120.

Figure 4.3.119 OVP Deceleration Timing

DC bus voltage;12-20;DC bus filter;11-33;11-34;11-35;11-36 Gain;11-37 Frequency Reference Limit;OVP accel/decel time;11-40=1;11-40=2;11-28 OVP2 Gain;OVP2 accel/decel time;11-37;Frequency Reference;SFS Fout;Output Frequency After SFS;11-40=0;11-40=1or2;Output Frequency;plus/minus andmultiplication signs. Labels only, original topology authoritative.

OVP Deceleration Time;00-24(Tdec4);00-22(Tdec3);DC bus voltage;700V;750V;OVP Deceleration Start(11-38);OVP Deceleration Stop(11-39). Printed graph examples only, not universal configured thresholds.

Manual — OVP modes andfrequencyloss settings — page 289

Manual reference: physical PDF page 289. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3) When the inverter is stopped, the deceleration rate is determined by 00-15 (Tdec1). If DC voltage is too high, the inverter decelerates based on the OVP deceleration timing shown in the above Figure 4.3.120. ‧ 11-38 (OVP Deceleration Start Voltage) defines the starting voltage for OVP deceleration, and 00-22 (Tdec3) sets the low deceleration slope. ‧ When the DC voltage rises to this level, immediate and faster deceleration is necessary to prevent large fluctuations in DC voltage. ‧ When the DC voltage reaches 11-39 (OVP Deceleration Stop Voltage), the inverter decelerates according to the value set in 00-24 (Tdec4). ‧ The deceleration slope transitions linearly between the starting point (11-38) and the stopping point (11-39). 4) The OVP function can be enabled or disabled via parameter 11-40. When the OVP function is enabled (11-40 = 1 or 2), the following parameters are changed to new default values: 00-14 (Tacc1) = 5.0 sec (acceleration rate when DC voltage is high) 00-22 (Tdec3) = 20.0 sec (lower deceleration slope for OVP) 00-24 (Tdec4) = 100.0 sec (upper deceleration slope for OVP) 11-04 = 0.0 Sec 11-05 = 0.0 sec (S-curve must be disabled when OVP is enabled) 11-06 = 0.0 sec 11-07 = 0.0 sec When 11-40 is set to Over-voltage Prevention Mode 2, its operation is the same as Mode 1 but enhances the response when the DC BUS voltage exceeds 11-39 (OVP Deceleration Stop Voltage) shown in Figure 4.3.120. By increasing 11-28 (OVP Mode 2 Frequency Gain), the system accelerates frequency compensation to prevent over-voltage (OV) faults. When 11-40 is set to Over-voltage Prevention Mode 3, the inverter avoids OV by temporarily increasing output frequency. This frequency will not exceed Motor 1’s maximum output frequency, so please adjust 01- 02 (Motor 1 Max. Output Frequency) according to your application. Adjustment Method If OV still occurs in Over-voltage Prevention Mode 3, increase 11-64 in increments of 0.1.

If the value of 11-64 is too large, it will increase speed and current ripple. 11-65 defines the target voltage for Over-voltage Prevention Mode 3 and should be set to suppress voltage within the specified level as much as possible.

• If the main frequency command drops by 90% within 360 ms, it is considered a reference frequency loss. • When 11-41 is set to 1, the main frequency command is continuously compared to the value within the preceding 360 ms. Once the loss is confirmed, the inverter estimates the current frequency command using the following formula: Frequency command after disconnection = Motor 1 Max. Output Frequency (01-02) × 11-42 • Explanation of Frequency Loss Function: When the inverter is running and the selected analog frequency command source is lost, the command will follow the proportion set in 11-42. Once the reference command returns to the pre-disconnection level, the inverter will resume its previous state.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 289

Source row Parameter Name Scope/options and printed unit
1 11- 64 Acceleration/Deceleration Adjustment Gain 【0.1~10.0】

Auxiliary parameter card — PDF page 289

Source row Parameter Name Scope/options and printed unit
1 11- 65 Target main circuit voltage 200V :[200~400] V 400V :[400~800] V

Auxiliary parameter card — PDF page 289

Source row Parameter Name Scope/options and printed unit
1 11- 41 Reference frequency loss detection selection [0]: Decelerate and stop when reference frequency is lost [1]: Operate according to the setting of 11-42 when reference frequency is lost

Auxiliary parameter card — PDF page 289

Source row Parameter Name Scope/options and printed unit
1 11- 42 Frequency command when the reference frequency is lost 【0.0~100.0】%

Manual — Analog frequencyloss restrictions — page 290

Manual reference: physical PDF page 290. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Note: 1. The frequency command when reference frequency is lost (11-42) corresponds to Motor 1 Max. Output Frequency (01-02). 2. This function currently only applies when 00-05 (Primary Frequency Command Source) is set to analog signal (selection 1: AI1 or 7: AI2). • Refer to the diagram below (Figure 4.3.121) for the behavior of multi-function digital outputs (03-11~03- 12) when the analog frequency command is lost.

Figure 4.3.120 Frequency Reference Loss Operation

Analog Frequency Command;100%;10%;360ms;t;Analog frequency command lossing digit output03-11=26or03-12=26;OFF;ON;OFF;t. Exact labels including lossing wording; no inferred delay.

Manual — Hold andKEB functions — page 291

Manual reference: physical PDF page 291. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• The hold function is used to temporarily maintain the reference frequency, preventing stalling caused by the load during inverter start-up or stop. • The inverter accelerates the motor using 11-44 (Hold Time, for flux generation) and 11-43 (Start Frequency). • The acceleration of the deceleration time does not include the start and stop of the hold time. Refer to Figure 4.3.122 below.

Figure 4.3.121 Hold Function

‧ When there is a high-inertia load, the hold function can be used to reduce over-current during acceleration. ‧ While the inverter is in stop mode, this function can also prevent wear on windmill-type loads. In addition, it allows the inverter to retain output frequency and extend voltage decay, enabling the motor to stop smoothly. You may also refer to the DC braking parameter at startup (07-16). ‧ If the startup hold frequency (11-43) or stop hold frequency (11-45) is set below Fmin (01-08), the hold function will be invalid.

‧ To prevent the motor from coasting for an extended period during operation due to instantaneous power loss or power failure under low voltage, the drive immediately detects such events and continues control using regenerative energy to decelerate the motor to a stop. (1) KEB Deceleration Time (11-47). ‧ The KEB function is disabled if 11-47 is set to 0.0. ‧ 11-47 can be set from 0.0 to 25.5 to specify the KEB deceleration time. (2) KEB Detection Level (11-48). ‧ If 11-47 is not 0.0, the KEB function will activate when the DC voltage falls below the value set in 11-48. ‧ The KEB function will initiate deceleration per 11-47 until the DC voltage exceeds 11-48 + 10V (220V series: +10V, 440V series: +20V). The digital input command (03-00 to 03-07) will then allow the drive to resume acceleration to the original frequency. Refer to Figure 4.3.123.

Output Frequency;11-43;11-45;11-44;11-46;t;RUN command;t. Labels only; no inferred frequency/time.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 291

Source row Parameter Name Scope/options and printed unit
1 11- 43 Lock frequency during startup 【0.0~599.0】Hz

Auxiliary parameter card — PDF page 291

Source row Parameter Name Scope/options and printed unit
1 11- 44 Start-Up Frequency Hold Time 【0.0~10.0】Sec

Auxiliary parameter card — PDF page 291

Source row Parameter Name Scope/options and printed unit
1 11- 45 Lock frequency when stopped 【0.0~599.0】Hz

Auxiliary parameter card — PDF page 291

Source row Parameter Name Scope/options and printed unit
1 11- 46 Lock time of frequency when stopped 【0.0~10.0】Sec

Auxiliary parameter card — PDF page 291

Source row Parameter Name Scope/options and printed unit
1 11- 47 KEB deceleration time 【0.0~25.5】Sec

Auxiliary parameter card — PDF page 291

Source row Parameter Name Scope/options and printed unit
1 11- 48 KEB detection threshold 200V :【190~210】V 400V :【380~420】V

Manual — KEB andzero servo — page 292

Manual reference: physical PDF page 292. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.122 KEB Operation

• When the motor is stopped, the zero servo function can be used to hold the motor shaft position. • Refer to Figure 4.3.124 Zero Servo Operation.

Figure 4.3. 123 Zero Servo Operation. • Zero servo command is executed via multifunction digital input (03-00 to 03-07 = 46). • When the frequency reference is below the zero-speed threshold (whichever is greater between 01-08 and 07-06, the DC braking start frequency), the zero servo state begins (zero servo start position), and the motor shaft position will be held even if the analog reference signal is not zero. • If the run command is turned off during zero servo mode, the zero servo function becomes invalid. • Zero servo completion can be signaled via multifunction digital output (03-11 or 03-12 = 31). – When any multifunction digital output is set to 31 (Zero Servo Complete signal), the zero servo count (11-50) is enabled. – The zero servo complete signal activates when the DC motor rotor position is within ± the value set in 11-50 from the zero servo start position. – The zero servo complete signal turns off when the zero servo or run command is activated. (1) Zero Servo Gain Setting (11-49). ‧ Use parameter 11-49 to adjust the holding torque of the zero servo operation.

DC Bus;KEB Detection Level;10Vfor220Vseries;20Vfor440Vseries;Re-acceleration;Output Frequency;KEB operation;Run Command;KEB Re-acceleration Command. Exact image labels; no unprinted timings.

Run command;t;Zero-servo command(03-00–07=46);t;Zero speed level(The greaterof01-08or07-06);t;Motor speed;t;Zero-servo Completion03-11–12=31);t;Zero-servo status. When the zero servo position error is within11-50,the zero servo completion signal is activated. VisibleEnglish annotation retained; hidden/overlaid Chinese text preserved onlyinraw.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 292

Source row Parameter Name Scope/options and printed unit
1 11- 49 Zero servo gain 【0.01~5.00】

Auxiliary parameter card — PDF page 292

Source row Parameter Name Scope/options and printed unit
1 11- 50 Zero servo count 【0~4096】

Auxiliary parameter card — PDF page 292

Source row Parameter Name Scope/options and printed unit
1 11- 51 Zero speed brake selection [0]: Zero-speed DC braking disabled [1]: Zero-speed DC braking enabled

Manual — Zero-speed brake warnings anddroop introduction — page 293

Manual reference: physical PDF page 293. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ The holding torque increases with higher values, which may lead to instability. ‧ The zero-servo gain parameter 11-49 is defined such that when the parameter is set to 1, a position error of one revolution will generate one rated motor speed. ‧ Do not use the zero-servo function at 100% of the inverter’s rated current, or it may trigger fault OH1 (heatsink overtemperature). For prolonged zero-servo holding torque, ensure that the output current stays below 50% to 60% of the inverter’s rated current, or increase the inverter capacity. (2) Zero Servo Count (11-50). ‧ The zero servo count is set to allow for position deviation at the zero-servo start position. ‧ Set the zero servo count (11-50) to four times the number of PG pulses (taking into account both the rising and falling edges of phases A and B, resulting in 4× PG resolution). (3) Zero-Speed Brake Operation Selection (11-51). ‧ In V/F control mode, DC braking (without PG feedback) can be used to generate holding torque. ‧ Set 11-51 to select the zero-speed braking operation. 11-51 = 0: Disabled; = 1: Enabled. • By setting 00-02 (Run Command Selection) to 1 and 00-05 (Frequency Reference Selection) to 1, both the run command and frequency reference are input via the control terminals. When the frequency reference is 0V (or less than 4mA) and the run command is enabled, the zero-speed braking function is activated (11-51 = 1), and holding torque will be generated in DC braking mode. Refer to Figure 4.3.125 Zero-Speed Braking Operation for operation details. DC braking (07-07) is limited to 20% of the inverter's rated current.

Figure 4.3. 124 Zero-Speed Braking Operation

When two motors drive the same load (e.g., crane or conveyor applications), high-slip motors are often used to achieve load balance. By using the droop function, standard motors can be configured to simulate high-slip motor characteristics. The droop function also helps mitigate torque fluctuations that may occur when two motors drive the same load. – (a) Load balancing using general-purpose motors. Motor A torque TA > Motor B torque TB

Run command;t;Frequency Reference;Zero speed level(The largerof01-08or07-06);t;DC Injection Braking(20%max.);t. Source labels only, no inferred phase durations.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 293

Source row Parameter Name Scope/options and printed unit
1 11- 52 Droop control threshold 【0.0~100.0】%

Auxiliary parameter card — PDF page 293

Source row Parameter Name Scope/options and printed unit
1 11- 53 Droop control delay 【0.01~2.00】Sec

Auxiliary parameter card — PDF page 293

Source row Parameter Name Scope/options and printed unit
1 11- 76 Droop frequency threshold 1 【0.00~599.00】Hz

Auxiliary parameter card — PDF page 293

Source row Parameter Name Scope/options and printed unit
1 11- 77 Droop frequency threshold 2 【0.00~599.00】Hz

Auxiliary parameter card — PDF page 293

Source row Parameter Name Scope/options and printed unit
1 11- 78 Droop torque offset 【0.00~100.00】%

Manual — Droop behavior and thresholds — page 294

Manual reference: physical PDF page 294. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

– (b) Load balancing using high-slip motors: Motor A torque TA ≈ Motor B torque TB

Refer to Figure 4.3.125 Load Balancing Status. ‧ The droop function simulates the slip characteristics of a motor. Set 11-52 to define the percentage of maximum frequency (01-02) by which speed decreases when 100% motor torque is reached. ‧ If 11-52 is set to 0.0%, the droop function is disabled.

Refer to Figure 4.3.126 Droop Function Characteristics. ‧ Parameter 11-53 adjusts the response speed of the droop function. Increase the value if current oscillation occurs. ‧ Parameters 11-76 and 11-77 define the frequency threshold above which the droop function becomes active. The speed gain adjustment curve is shown below:

Figure 4.3.127 Droop Function Speed Gain Adjustment Curve. ‧ Parameter 11-78 defines the torque offset level above which the droop function becomes active. The torque command adjustment curve is shown below:

Torque;Motor A’s torque characteristics;Motor B’s torque characteristics;Load torque;Reference Speed;Speed;TA;TB;case(a)TA>TB,TA−TB>>0;case(b)TA≅TB,TA−TB approximately0. Qualitative graph labels only; no curve interpolation or inferred motor values.

Frequency;Torque;−100%;0;100%;(11-52)*(01-02);Droop compensation frequency. Printed labels only; no unprinted slope calculated.

Set11-76<11-77;Gain;0;1;11-76;11-77;|f_ref|. Set11-76≥11-77;Gain;0;1;11-76;|f_ref|. Visible English labels retained; hidden Chinese annotation remains in raw. Original graph retains continuous/step geometry.

Manual — Torque offset and recording controls — page 295

Manual reference: physical PDF page 295. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.128 Droop Function Torque Command Adjustment Curve.

Use parameter 11-54 Accumulated Energy Initialization to reset the accumulated energy (KWHr) (12-67) and accumulated energy (MWHr) (12-68).

This parameter enables or disables the STOP key on the digital operator when the run command is issued via terminal (00-02 = 1) or communication (00-02 = 3). 11-55 = 0: Disabled (STOP key is disabled when the run command comes from terminal or communication). = 1: Enabled (STOP key is always active regardless of command source).

11-56 = 0: When adjusting the frequency via the UP/DOWN keys, the change takes effect only after pressing ENTER. = 1: When adjusting the frequency via the UP/DOWN keys, the change takes effect immediately without needing to press the ENTER key. ‧ The output frequency can be changed (up or down) via the digital operator or through multifunction digital input terminals (03-00 to 03-07) set to 8 or 9. Refer to the description for (03-00~03-07 = 8 or 9).

This function is only effective when paired with the ACC/DEC inhibit function (multifunction digital input terminal function 11), as described below. When 11-58=0: When ACC/DEC prohibited is ON during the motor acceleration/deceleration process, the motor will stop at the output frequency at that moment and use the output frequency as the frequency command. When ACC/DEC prohibited is changed to OFF or when a shutdown command is given, the frequency command will be restored to the frequency originally set.

Torque Ref.−(11-78);−(11-78);Torque Ref.;11-78;Torque Ref.+(11-78). Exact labels, no numerical or transfer-function inference.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 295

Source row Parameter Name Scope/options and printed unit
1 11- 54 Cumulative energy initialization [0]: Do not reset accumulated energy [1]: Reset accumulated energy

Auxiliary parameter card — PDF page 295

Source row Parameter Name Scope/options and printed unit
1 11- 55 STOP button selection [0]: When the run command is not issued via the digital operator, the STOP key is disabled [1]: When the run command is not issued via the digital operator, the STOP key is enabled

Auxiliary parameter card — PDF page 295

Source row Parameter Name Scope/options and printed unit
1 11- 56 UP/DOWN selection [0]: UP/DOWN on digital operator is disabled; frequency change takes effect only after pressing ENTER [1]: UP/DOWN on digital operator is enabled; frequency change takes effect immediately

Auxiliary parameter card — PDF page 295

Source row Parameter Name Scope/options and printed unit
1 11- 58 Record reference frequency [0]: Disabled [1]: Enabled

Manual — Recording continuation and oscillation — page 296

Manual reference: physical PDF page 296. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

In addition, when the stop command and power-off is reset, the frequency command will be set to 0 Hz. Note: If ACC/DEC prohibited is ON before operating, STP0 will appear after operation starts because there is no recorded reference frequency. When 11-58=1: When ACC/DEC prohibited is ON during the motor acceleration/deceleration process, the motor will stop at the output frequency at that moment and use the output frequency as the frequency command. If switched to the stop status or cut the power of the inverter to reset at this time, when ACC/DEC prohibited is still ON, the output frequency will still be saved, and the frequency command will be set as the saved frequency. Refer to the figure below:

Figure 4.3.129 Reference Frequency Record Example

Used to adjust the effectiveness of the anti-vibration function. If vibration occurs while driving the motor under light load, gradually increase the setting in increments of 0.01.

Limits the upper threshold of the anti-vibration function.

Adjusts the responsiveness of the anti-vibration function. (This is the first-order delay time constant for the anti-vibration function).

Set parameter 11-62 to 0 for Mode 1 and 2 to achieve slower response. Set parameter 11-62 to 2 for Mode 3 to achieve faster response.

When 11-63 is set to 0, strong magnet function is disabled, resulting in uniform no-load current across high and low speeds. When 11-63 is set to 1, strong magnet function is enabled, producing greater torque at low speeds but with higher no-load current—suitable for heavy loads at low speeds.

Power Supply:ON,OFF,ON;Forward Run:ON,OFF,ON;Inhibit ACC/DEC Command:OFF,ON,OFF,ON;Frequency Reference;Output Frequency;Hold;Hold;t. Waveform labels only; timings retained in original image.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 296

Source row Parameter Name Scope/options and printed unit
1 11- 59 Prevent oscillation gain 【0.00~2.50】

Auxiliary parameter card — PDF page 296

Source row Parameter Name Scope/options and printed unit
1 11- 60 Prevent oscillation upper limit 【0~100】%

Auxiliary parameter card — PDF page 296

Source row Parameter Name Scope/options and printed unit
1 11- 61 Prevent oscillation time parameter 【0~100】

Auxiliary parameter card — PDF page 296

Source row Parameter Name Scope/options and printed unit
1 11- 62 Prevent oscillation selection [0]: Mode 1 [1]: Mode 2 [2]: Mode 3

Auxiliary parameter card — PDF page 296

Source row Parameter Name Scope/options and printed unit
1 11- 63 Strong magnetic selection [0]: Disabled [1]: Enabled

Manual — Anti-vibration and local remote selection — page 297

Manual reference: physical PDF page 297. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Adjusts the responsiveness of the Anti-Vibration 3 function. If vibration occurs while driving the motor under light load, gradually increase the setting in increments of 0.01.

Limits the upper threshold of the Anti-Vibration 3 function.

Adjusts the responsiveness of the Anti-Vibration 3 function. (This is the first-order delay time constant for the anti-vibration function).

Parameters 11-72 and 11-73 are used to set Anti-Vibration Gain Switching Frequencies 1 and 2 respectively.

Figure 4.3.130 Anti-Vibration Gain Switching Frequency Setting

Users can configure the LOC/REM key function as needed. Set the parameter to [0]: Forward/Reverse Control Key to define the panel's operation direction. Set the parameter to [1]: Local/Remote Control to directly switch between panel and external control, in coordination with external control logic parameters for adjustment.

When users switch between local and remote modes based on operational needs, to protect personnel and equipment, switching restrictions can be configured via protection levels between modes to ensure safety during the transition process.

Anti-Vibration3 Gain;11-69;0;Frequency1:11-72;Frequency2:11-73;Output frequency. No inferred curve values.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 69 Anti-Vibration 3 Gain 【0.00~200.00】%

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 70 Anti-Vibration 3 Limit 【0.01~100】%

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 71 Anti-Vibration 3 Time Constant 【0~30000】mSec

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 72 Anti-Vibration 3 Frequency 1 【0.01~300.00】Hz

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 73 Anti-Vibration 3 Frequency 2 【0.01~300.00】Hz

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 79 LOC/REM Panel Key Function Selection [0]: Forward/Reverse Control [1]: Local/Remote Control

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 80 Local/remote selection mode [0]: Switching allowed directly [0]Switching prohibited during operation [2]: Stop after switching

Auxiliary parameter card — PDF page 297

Source row Parameter Name Scope/options and printed unit
1 11- 81 OVP4 threshold (%) 【100~200】%

Manual — OVP4 warning and monitoring display — page 298

Manual reference: physical PDF page 298. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

OVP mode is mainly used to suppress regenerative voltage generated during deceleration, which could otherwise exceed protection limits and trigger OV fault signals in the drive. OVP Mode 4 dissipates regenerative voltage by returning the energy to the motor as reactive power, thus reducing voltage levels and ensuring the drive continues to operate properly during rapid deceleration. However, since this method redirects energy back to the motor, it may impact motor lifespan. Evaluate the suitability of this mode for the application before enabling it. 12 - Monitoring Function Group

Note: The highest bit is the default screen upon startup. The remaining four bits are user-defined display bits that can be selected according to display preferences. (Refer to diagram on page P4-4)

When 12-00 = xxx5, the default LED screen displays the PID feedback. Parameter 12-01 uses the value from 10-33, converting it to a five-digit display in the format XXX.XX. Example: If 10-33 is set to 9999, 12-01 = 0 displays 99; 12-01 = 1 displays 99.9; 12-01 = 2 displays 99.99. When used in conjunction with 12-02, if 12-01 = 1 and 12-02 = 1, the display reads 99.9Pb; if 12-01 = 2 and 12-02 = 2, it reads 9.99FL, with the tens digit “9” hidden.

When 12-04 is set to a value other than 0, the inverter displays the line speed during stop mode or when frequency is being modified. 12-03 is the maximum value for line speed and corresponds to the maximum output frequency. Example: If 12-03 = [1800], when the output frequency is 30Hz, the display shows [900].

• When any of the terminals S1~S7 is ON, the corresponding segment on 12-05 will light up; otherwise, it remains off. • If the relay is active, the corresponding segment lights up; otherwise, it remains off. • When the run command is switched to PLC mode and the RUN button is pressed, the display lights up; otherwise, it remains off.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Five positions highest to lowest, each 0–7. Physical left/right option columns kept separate. Highest startup bit vs prose xxx5 discrepancy retained.

Auxiliary parameter card — PDF page 298

Source row Parameter Name Scope/options and printed unit
1 11- 82 OVP4 gain 【0~256】

Auxiliary parameter card — PDF page 298

Source row Parameter Name Scope/options and printed unit
1 12- 01 PID feedback display mode (LED) [0]: Display feedback as integer (xxx) [1]: Display feedback with 1 decimal place (xx.x) [2]: Display feedback with 2 decimal places (x.xx)

Auxiliary parameter card — PDF page 298

Source row Parameter Name Scope/options and printed unit
1 12- 02 PID feedback display unit setting (LED) [0]: xxxxx (No unit) [1]: xxxPb (Pressure) [2]: xxxFL (Flow)

Auxiliary parameter card — PDF page 298

Source row Parameter Name Scope/options and printed unit
1 12- 03 Linear speed display (LED) [0~60000] RPM

Auxiliary parameter card — PDF page 298

Source row Parameter Name Scope/options and printed unit
1 12- 04 Linear speed display mode (LED) [0]: Display inverter output frequency [1]: Display line speed as integer (xxxxx) [2]: Display line speed with 1 decimal place (xxxx.x) [3]: Display line speed with 2 decimal places (xxx.xx) [4]: Display line speed with 3 decimal places (xx.xxx)

Auxiliary parameter card — PDF page 298

Source row Parameter Name Scope/options and printed unit
1 12- 05 Display of Digital Input Terminal Status (LED/LCD) Read-only (panel display only)

Auxiliary parameter card — PDF page 298

Source row Parameter Name Scope: five bit positions and range Scope/options left column Scope/options right column
1 12- 00 Display screen selection (LED) 0 0 0 0 0 Highest bit Lowest bit Each bit from highest to lowest has a value range of 0~7 [0]: Do not display [2]: Output voltage [4]: Heatsink temperature [6]: AI1 value [1]: Output current [3]: DC bus voltage [5]: PID feedback [7]: AI2 value

Manual — Display diagrams and monitor restrictions — page 299

Manual reference: physical PDF page 299. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 1: The diagram below shows S1~S7 as ON, and RY1/DO1/DO2 are outputting, 12-05 displays on the LED panel.

Figure 4.3.131 LED Panel Display Example Example 2: The diagram below shows S1~S7 as OFF, and RY1/DO1/DO2 are not outputting, 12-05 displays on the LCD panel.

Figure 4.3.132 LCD Panel Display Example ■ Other monitoring parameters (12-11~12-64): Refer to Chapter 4.2 for simplified explanation. Monitoring parameter 12-34 is available only for J7-PG-L, JN7-PG-O, JN7-PG-PM encoder options * PG cards are limited to special projects. Monitoring parameter 12-66 (Encoder Angle): With correct PG Pulse Count (20-27) settings and wiring, rotating the motor one full turn forward while stopped will accumulate 360 degrees twice. Rotating it one full turn in reverse will decrement 360 degrees twice. Monitoring Parameter 12-67 (Accumulated Energy in KWHr) and 12-68 (in MWHr) display the accumulated energy consumption. (Use 11-54 Accumulated Energy Initialization to reset these monitoring parameters) Monitoring Parameter 12-38 allows PID setting (can be configured directly via the panel), and 12-39 displays PID feedback. Please refer to the settings of 10-33~10-35 to configure how the values are displayed. Monitoring Parameter 12-76 displays the no-load voltage and should be used in conjunction with Parameter 02-09 (Motor 1 Excitation Current) and Parameter 17-09 (Motor Excitation Current). Monitoring Parameter 12-78 (Z-Phase Deviation Value) is used in conjunction with Parameter 21-43 (Offset Angle). Monitoring Parameter 12-79 (Pulse Input Percentage) corresponds to Parameter 03-30 (Pulse Input Selection). Monitoring Parameter 12-87 allows monitoring of the capacitor lifespan as a percentage of usage time. * When viewing monitoring parameters (12-05~12-87), it is possible to execute the run command simultaneously.

S1;S2;S3;S4;S5;S6;S7;RY1;DO1;DO2;PLC. Two LED panel examples; physical segment mapping remains in original diagram.

0:OPEN;1:CLOSE;display contains twelve zero positions. Right-to-left labelled eleven lines:Input Terminal(S7),(S6),(S5),(S4),(S3),(S2),(S1);Output Terminal(PLC),(DO2),(DO1),(RY1). One unlabelled zero position remains unassigned; no assumed terminal.

Manual — Maintenance counters and model codes — page 300

Manual reference: physical PDF page 300. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13 – Maintenance Function Group

• If 13-02 is set to 1, then 13-03 and 13-04 (accumulated time values) will be cleared. • The time selected by 13-05 corresponds to 13-03/13-04 (historical runtime). 13-05 = 0: Time is accumulated while the inverter is powered on = 1: Time is accumulated only during inverter operation

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Two parallel source lists normalized into eleven distinct model/display rows; no power or rating inferred from display code.

Adjacent source context — repeated to preserve continuation:

Auxiliary parameter card — PDF page 300

Source row Parameter Name Scope/options and printed unit
1 13- 00 Inverter horse power ----

Auxiliary parameter card — PDF page 300

Source row Parameter Name Scope/options and printed unit
1 13- 01 Software version ----

Auxiliary parameter card — PDF page 300

Source row Parameter Name Scope/options and printed unit
1 13- 02 Cumulative working time clearing function [0]: Do not clear cumulative operation time [1]: Clear cumulative operation time

Auxiliary parameter card — PDF page 300

Source row Parameter Name Scope/options and printed unit
1 13- 03 Cumulative working time 1 [0~23] hours

Auxiliary parameter card — PDF page 300

Source row Parameter Name Scope/options and printed unit
1 13- 04 Cumulative working time 2 [ 0~65534]days

Auxiliary parameter card — PDF page 300

Source row Parameter Name Scope/options and printed unit
1 13- 05 Cumulative working time selection [0]: Cumulative time while powered on [1]: Cumulative time only while running

Inverter model and 13-00 display — PDF page 300

Source row Inverter Model 13-00 Display
1 E710-201-XXX 201
2 E710-202-XXX 202
3 E710-203-XXX 203
4 E710-205-XXX 205
5 E710-208-XXX 208
6 E710-401-XXX 401
7 E710-402-XXX 402
8 E710-403-XXX 403
9 E710-405-XXX 405
10 E710-408-XXX 408
11 E710-410-XXX 410

Manual — Parameter lock and password setting — page 301

Manual reference: physical PDF page 301. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When 13-06 = 0, only 13-06 and the main frequency command on the home page can be edited; all other parameters are locked. When 13-06 = 1, only user-defined parameters (00-41~00-56) are editable. Please refer to the description of parameters 00-41~00-56 for use. This option is only available on the LCD operator and not on the LED operator. When 13-06 = 2, parameters can be written normally, except those that are inherently read-only. Note: The main frequency setting parameter for the LCD operator is 12-16, which corresponds to Segment 0 Frequency Command (05-01). The main frequency for the LED operator can be set on the main frequency screen.

➢ When 13-07 is set to a valid password (>0), all parameters except the main screen frequency setting cannot be modified. Only by unlocking the password can parameters be edited. ➢ To Set a Password: Step 1:

Step 2:

Entering for the1st time;13-07;READ/ENTER;00000;▲or▼;12345;READ/ENTER;End;12345;DSP/FUN. Source example displays only, not a recommended password.

Entering for the2nd time;13-07;READ/ENTER;00001;▲or▼;10000;READ/ENTER;Err2;10000;Failed to set password;DSP/FUN. Other branch:12345;READ/ENTER;LOC;12345;Password set successfully;DSP/FUN. The final display is12345, matching the selected example. Primary4xsourcecrop corrects the earlier transcription12344.

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Adjacent source context — repeated to preserve continuation:

Auxiliary parameter card — PDF page 301

Source row Parameter Name Scope/options and printed unit
1 13- 06 Parameter lock [0]: All parameters are read-only except 13-06 and the main frequency setting on the home page [1]: Only user-defined parameters are writable [2]: All parameters are writable

Auxiliary parameter card — PDF page 301

Source row Parameter Name Scope/options and printed unit
1 13- 07 Parameter Password Function 【00000~65534】

Manual — Password unlock and factory initialization — page 302

Manual reference: physical PDF page 302. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

To Unlock the Password:

Figure 4.3.133 Password Setup/Unlock

Use parameter 13-08 to initialize inverter parameters. Once initialization is complete, the inverter will return to its factory default values. It is recommended that users record any modified parameter settings prior to initialization. After initialization, the value of 13-08 will automatically revert to 0.

13-08=2: 2-wire initialization (220V/440V) ─ Multifunction digital input terminal S1 controls the forward run/stop command, and S2 controls the reverse run/stop command. Please refer to Figure 4.3.1. ─ Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 60Hz.

13-08=3: 3-wire initialization (220V/440V) ─ Multifunction digital input terminal S7 controls the forward/reverse run command, while S1 and S2 terminals are assigned for 3-wire control to individually manage run and stop commands. Refer to Figure 4.3.2 and Figure 4.3.3 for 3-wire operation mode. ─ Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 60Hz.

13-08=4: 2-Wire Initialization (230V/415V) ─ Same as 2-wire operation mode (13-08 = 2). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 50Hz.

Remove password;13-07;READ/ENTER;00002;▲or▼;10000;READ/ENTER;LOC;10000;Failed to remove the password;DSP/FUN. Successful branch:12345;READ/ENTER;End;12345;Password removed successfully;DSP/FUN. Source example only.

Two physical columns; source omits option11 number/type before bare (230/400V)[60Hz]. Preserve exact omission; subsequent prose303 supplies separately labelled 13-08=11 explanation, not silent table repair.

Auxiliary parameter card — PDF page 302

Source row Parameter Name Scope/options left column Scope/options right column
1 13- 08 Restore factory settings [0]Do not initialize [1] Reserved [2] 2-wire initialization (220/440V) [60Hz] [3] 3-wire initialization (220/440V) [60Hz] [4] 2-wire initialization (230/415V) [50Hz] [5] 3-wire initialization (230/415V) [50Hz] [6] 2-wire initialization (200/380V) [50Hz] [7] 3-wire initialization (200/380V) [50Hz] [8] PLC initialization* [9] 2-wire initialization (230/460V) [60Hz][10]3-wire initialization (230/460V) [60Hz] (230/400V) [60Hz] [12] 3-wire initialization (230/400V) [60Hz] [13] 2-wire initialization (230/400V) [50Hz] [14] 3-wire initialization (230/400V) [50Hz] [15] 2-wire initialization (220/380V) [50Hz] [16] 3-wire initialization (220/380V) [50Hz] [17] 2-wire initialization (200/380V) [60Hz] [18] 3-wire initialization (200/380V) [60Hz]

Manual — Initialization modes and PMSV exception — page 303

Manual reference: physical PDF page 303. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13-08=5: 3-Wire Initialization (230V/415V) ─ Same as 3-wire operation mode (13-08 = 3). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 50Hz.

13-08=6: 2-wire initialization (200V/380V) ─ Same as 2-wire operation mode (13-08 = 2). Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 50Hz.

13-08=7: 3-wire initialization (200V/380V) ─ Same as 3-wire operation mode (13-08 = 3). Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 50Hz. If operating in PMSV mode (00-00 = 4), and 13-08 is set to 2 through 7, the motor maximum frequency will be automatically set according to the specific inverter model.

13-08=8: PLC Initialization – Clears the internal PLC program and values stored in the inverter.

13-08=9: 2-Wire Initialization (230V/460V) ─ Same as 2-wire operation mode (13-08 = 2). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 460V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 60Hz.

13-08=10: 3-Wire Initialization (230V/460V) ─ Same as 3-wire operation mode (13-08 = 3). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 460V (400V class). ─ When 01-00 (V/F Curve Setting) = F, the motor maximum frequency (01-02) is automatically set to 60Hz.

13-08=11: 2-Wire Initialization (230/400V, 60Hz) ─ Same as 2-wire operation mode (13-08 = 2). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 60Hz.

13-08=12: 3-Wire Initialization (230/400V, 60Hz) ─ Same as 3-wire operation mode (13-08 = 3). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 60Hz.

13-08=13: 2-Wire Initialization (230/400V, 50Hz) ─ Same as 2-wire operation mode (13-08 = 2). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 50Hz.

13-08=14: 3-Wire Initialization (230/400V, 50Hz) ─ Same as 3-wire operation mode (13-08 = 3). Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 50Hz.

13-08=15: 2-Wire Initialization (220/380V, 50Hz) ─ Same as 2-wire operation mode (13-08 = 2). Inverter input voltage (01-14) is automatically set

Manual — Factory reset exceptions and optional cards — page 304

Manual reference: physical PDF page 304. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

to 220V (200V class) or 380V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 50Hz.

13-08=16: 3-Wire Initialization (220/380V, 50Hz) – Same 3-wire operation mode as [13-08 = 3], and the inverter input voltage (01-14) will be automatically set to 220V (200V class) or 380V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 50Hz.

13-08=17: 2-Wire Initialization (200/380V, 60Hz) ─ Same as 2-wire operation mode (13-08 = 2). Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 60Hz.

13-08=18: 3-Wire Initialization (200/380V, 60Hz) – Same 3-wire operation mode as [13-08 = 3], and the inverter input voltage (01-14) will be automatically set to 200V (200V class) or 380V (400V class). – When 01-00 V/F curve is set to F, the inverter’s maximum frequency (01-12) will be automatically set to 60Hz.

Table 4.3.36 Parameters Not Affected by Initialization

If 13-09 = 1, the fault trace/fault history (12-11 to 12-15 / 12-45 to 12-64) will also be cleared.

Only available for Frame2/3 models to view the CB2 control board version.

‧ This parameter displays the ID of the optional card installed on the control board. It is only shown when an optional card is in use. 【0】:none 【1】:PG-L 【2】:PG-O 【3】:PG-PM 【4】:PG-PMS 【5】:PG-PMR

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Explicit reset exceptions to13-08 on302–304; not inferred from ordinary reset behavior.

Auxiliary parameter card — PDF page 304

Source row Parameter Name Scope/options and printed unit
1 13- 09 Failure history clearing function [0]: Do not clear fault history [1]: Clear fault history

Auxiliary parameter card — PDF page 304

Source row Parameter Name Scope/options and printed unit
1 13- 11 CB2 Software Version 【0.00~9.99】

Auxiliary parameter card — PDF page 304

Source row Parameter Name Scope/options and printed unit
1 13- 12 Optional Card ID 【0~255】

Table4.3.36 parameters not affected by initialization — PDF page 304

Source row Parameter Name
1 00-00 Motor control mode
2 00-04 Language selection
3 01-00 V/F curve selection
4 01-26 Motor 2 V/F curve selection
5 13-00 Inverter horse power
6 13-03 Cumulative working time 1
7 13-04 Cumulative working time 2
8 13-05 Cumulative working time selection

Manual — Maintenance lifespan and PLC settings — page 305

Manual reference: physical PDF page 305. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ This parameter shows the CPLD software version of the optional card on the control board. It is only displayed when an optional card is installed.

When parameter 13-14 is set to 0, fault messages that occur during the auto-restart process will not be stored in the fault history (12-46 to 12-49 & 13-21 to 13-50). When parameter 13-14 is set to 1, fault messages that occur during the auto-restart process will be stored in the fault history (12-46 to 12-49 & 13-21 to 13-50).

Parameters 13-51 and 13-52 can be redefined via 08-65 [Cooling Fan Maintenance Setting]. Parameter 13-52 displays the accumulated operating time of the cooling fan as a percentage, with 100% representing the expected lifespan of the cooling fan. Parameter 13-53 can be redefined via 08-66 [IGBT Maintenance Setting]. Parameter 13-53 displays the accumulated operating time of the IGBT as a percentage (%), with 100% representing the expected lifespan of the IGBT. Note: 1. 90% is the recommended reference value for replacing the cooling fan and IGBT. 2. The actual maintenance period may vary depending on the operating environment of the inverter.

14- PLC Settings Group

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Shared source scope 0~9999; no time/current engineering units inferred. Two physical parallel columns reordered into individual parameter rows; mode7 qualifications retained.

Applies to this printed PLC group only; distinct from engineering current.

Shared source scope 0~65535; no time/current engineering units inferred. Two physical parallel columns reordered into individual parameter rows; mode7 qualifications retained.

Auxiliary parameter card — PDF page 305

Source row Parameter Name Scope/options and printed unit
1 13- 13 Optional Card CPLD Software Version 【0.00~9.99】

Auxiliary parameter card — PDF page 305

Source row Parameter Name Scope/options and printed unit
1 13- 14 Failure saving selection [0]: Fault messages during auto-restart will not be stored in the fault history [1]: Fault messages during auto-restart will be stored in the fault history

Auxiliary parameter card — PDF page 305

Source row Parameter Name Scope/options and printed unit
1 13- 51 Cooling fan cumulative operation time 【0~99999】

Auxiliary parameter card — PDF page 305

Source row Parameter Name Scope/options and printed unit
1 13- 52 Cooling fan life inspection percentage 【0~150】

Auxiliary parameter card — PDF page 305

Source row Parameter Name Scope/options and printed unit
1 13- 53 IGBT life inspection percentage 【0~150】

PLC settings — PDF page 305

Source row Parameter Name
1 14- 00 T1 setting value 1
2 14- 08 T5 setting value 1
3 14- 01 T1 setting value 2 (Mode 7)
4 14- 09 T5 setting value 2 (Mode 7)
5 14- 02 T2 setting value 1
6 14- 10 T6 setting value 1
7 14- 03 T2 setting value 2 (Mode 7)
8 14- 11 T6 setting value 2 (Mode 7)
9 14- 04 T3 setting value 1
10 14- 12 T7 setting value 1
11 14- 05 T3 setting value 2 (Mode 7)
12 14- 13 T7 setting value 2 (Mode 7)
13 14- 06 T4 setting value 1
14 14- 14 T8 setting value 1
15 14- 07 T4 setting value 2 (Mode 7)
16 14- 15 T8 setting value 2 (Mode 7)

PLC shared scope — PDF page 305

Source row Scope label Value
1 Scope 【0~9999】

PLC settings — PDF page 305

Source row Parameter Name
1 14- 16 C1 setting value
2 14- 20 C5 setting value
3 14- 17 C2 setting value
4 14- 21 C6 setting value
5 14- 18 C3 setting value
6 14- 22 C7 setting value
7 14- 19 C4 setting value
8 14- 23 C8 setting value

PLC shared scope — PDF page 305

Source row Scope label Value
1 Scope 【0~65535】

PLC settings — PDF page 305

Source row Parameter Name
1 14- 24 AS1 setting value 1
2 14- 30 AS3 setting value 1
3 14- 25 AS1 setting value 2
4 14- 31 AS3 setting value 2
5 14- 26 AS1 setting value 3
6 14- 32 AS3 setting value 3

Manual — PLC setting continuation — page 306

Manual reference: physical PDF page 306. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Please refer to Chapter 4.4 for a detailed explanation of the built-in PLC functions.

Shared source scope 0~65535 from prior page305 AS scope; no time/current engineering units inferred. Two physical parallel columns reordered into individual parameter rows; mode7 qualifications retained.

Shared source scope 0~65535; no time/current engineering units inferred. Two physical parallel columns reordered into individual parameter rows; mode7 qualifications retained.

Applies to this printed PLC group only; distinct from engineering current.

PLC settings — PDF page 306

Source row Parameter Name
1 14- 27 AS2 setting value 1
2 14- 33 AS4 setting value 1
3 14- 28 AS2 setting value 2
4 14- 34 AS4 setting value 2
5 14- 29 AS2 setting value 3
6 14- 35 AS4 setting value 3

PLC settings — PDF page 306

Source row Parameter Name
1 14- 36 MD1 setting value 1
2 14- 42 MD3 setting value 1
3 14- 37 MD1 setting value 2
4 14- 43 MD3 setting value 2
5 14- 38 MD1 setting value 3
6 14- 44 MD3 setting value 3
7 14- 39 MD2 setting value 1
8 14- 45 MD4 setting value 1
9 14- 40 MD2 setting value 2
10 14- 46 MD4 setting value 2
11 14- 41 MD2 setting value 3
12 14- 47 MD4 setting value 3

PLC shared scope — PDF page 306

Source row Scope label Value
1 Scope 【0~65535】

Manual — PLC current-value monitoring — page 307

Manual reference: physical PDF page 307. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

15 – PLC Monitoring Group

Shared source scope 0~9999; no time/current engineering units inferred. Two physical parallel columns reordered into individual parameter rows; mode7 qualifications retained.

Applies to this printed PLC group only; distinct from engineering current.

Shared source scope 0~65535; no time/current engineering units inferred. Two physical parallel columns reordered into individual parameter rows; mode7 qualifications retained.

PLC monitoring — PDF page 307

Source row Parameter Name
1 15- 00 T1 current value 1
2 15- 08 T5 current value 1
3 15- 01 T1 current value 2 (Mode 7)
4 15- 09 T5 current value 2 (Mode 7)
5 15- 02 T2 current value 1
6 15- 10 T6 current value 1
7 15- 03 T2 current value 2 (Mode 7)
8 15- 11 T6 current value 2 (Mode 7)
9 15- 04 T3 current value 1
10 15- 12 T7 current value 1
11 15- 05 T3 current value 2 (Mode 7)
12 15- 13 T7 current value 2 (Mode 7)
13 15- 06 T4 current value 1
14 15- 14 T8 current value 1
15 15- 07 T4 current value 2 (Mode 7)
16 15- 15 T8 current value 2 (Mode 7)

PLC shared scope — PDF page 307

Source row Scope label Value
1 Scope 【0~9999】

PLC monitoring — PDF page 307

Source row Parameter Name
1 15-16 C1 current value
2 15-20 C5 current value
3 15-17 C2 current value
4 15-21 C6 current value
5 15-18 C3 current value
6 15-22 C7 current value
7 15-19 C4 current value
8 15-23 C8 current value

PLC shared scope — PDF page 307

Source row Scope label Value
1 Scope 【0~65535】

PLC monitoring — PDF page 307

Source row Parameter Name
1 15-24 AS1 current value
2 15-29 MD2 current value
3 15-25 AS2 current value
4 15-30 MD3 current value
5 15-26 AS3 current value
6 15-31 MD4 current value
7 15-27 AS4 current value
8 15-32 TD current value
9 15-28 MD1 current value

Manual — LCD unit choices and monitor settings — page 308

Manual reference: physical PDF page 308. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

16 – LCD Function Group

‧ When the power is turned on, two monitoring items are displayed: Main Monitoring and Secondary Monitoring. ‧ Use parameter 16-00 to select the item to be displayed on the main monitoring screen, and use parameters 16-01 and 16-02 to select secondary monitoring items to monitor parameters 12-5 to 12-82.

(1) Display Unit Selection (16-03) ‧ The following items can be configured to display with user-defined units: Stage 0 speed setting (05- 01), jog frequency (00-18), stage 1–15 speed settings (06-01 to 06-15), frequency command (12-16), and output frequency (12-17). (2) Engineering Unit Selection (16-04) ‧ Users can use parameters 16-03 and 16-04 to change display and engineering units. When the display unit selection (16-03) is set to a value between 00040 and 39999, the display unit range and engineering unit shown on the digital operator will change. The parameters affected by the settings of 16-03 and 16-04 include: stage 0 speed setting (05-01), jog frequency (00-18), stage 1–15 speed settings (06-01 to 06-15), frequency command (12-16), and output frequency (12-17).

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Physical three-column engineering-unit choices retained; case and spelling source-exact.

Auxiliary parameter card — PDF page 308

Source row Parameter Name Scope/options and printed unit
1 16- 00 Main screen monitoring 【5~82】

Auxiliary parameter card — PDF page 308

Source row Parameter Name Scope/options and printed unit
1 16- 01 Sub-screen monitoring 1 【5~82】

Auxiliary parameter card — PDF page 308

Source row Parameter Name Scope/options and printed unit
1 16- 02 Sub-screen monitoring 2 【5~82】

Auxiliary parameter card — PDF page 308

Source row Parameter Name Scope/options and printed unit
1 16- 03 Display unit selection [0]: Display unit in 0.01 Hz [1]: Display unit in 0.01% [2]: Display unit in rpm [3~39]: Reserved [40~9999]: User-defined format. Entering 0XXXX means displayed as XXXX when 100% [10001~19999]: User-defined format. Entering 1XXXX means displayed as XXX.X when 100% [20001~29999]: User-defined format. Entering 2XXXX means displayed as XX.XX when 100% [30001~39999]: User-defined format. Entering 3XXXX means displayed as X.XXX when 100%

Auxiliary parameter card — PDF page 308

Source row Parameter Name Options0–8 Options9–17 Options18–26
1 16- 04 Engineering unit selection [0]: Do not use engineering unit 【1】: FPM 【2】: CFM 【3】: PSI 【4】: GPH 【5】: GPM 【6】: IN 【7】: FT 【8】: /s 【9】: /m 【10】: /h 【11】: °F 【12】: inW 【13】: HP 【14】: m/s 【15】: MPM 【16】: CMM 【17】: W 【18】: KW 【19】: m 【20】: °C 【21】: RPM 【22】: Bar 【23】: Pa 【24】: Kpa 【25】: PRS 【26】: SPM

Manual — LCD display encoding examples — page 309

Manual reference: physical PDF page 309. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.37 16-03 Unit Setting and Display

00040 - 39999

Decimal point set to the fifth digit; i.e.□ □□□□. Set4digits excluding the decimal point;Define number of decimal places.00040–09999:□□□□(Decimal place:0digit);10001–19999:□□□.□(Decimal place:1digit);20001–29999:□□.□□(Decimal place:2digits);30001–39999:□.□□□(Decimal place:3digits);<Example>. Arrows link first box to decimal-place definition andremainingfour todisplayvalue; no unprinted engineering conversion.

Followin g the setting of 16-04

Source display option values, not added engineering ratings.

All four examples shareDisplayUnit Followingthe settingof16-04; the sharedcell is separately represented. Explicit display examples only, not measured motor performance.

Table4.3.37 unit setting basic options — PDF page 309

Source row 16-03 Setting / Display Content
1 0 0.01 Hz
2 1 0.01% (Maximum Output Frequency 01-02 = 100%)
3 2 Frequency display unit in rpm
4 3- 39 Reserved

Table4.3.37 user display examples — PDF page 309

Source row 16-03 Setting Display Display Examples
1 00040 - 09999 □□□□ To display 100% speed as “0200” → Set 16-03 = 00200 (for 05-01, 06-01 to 06-15, setting range: 0040 to 9999). → Set 16-04 = 0 (no unit).
2 10001 – 19999 □□□. □ To display 100% speed as “200.0 CFM” → Set 16-03 = 12000 (for 05-01, 06-01 to 06-15, setting range: 0000 to 9999) → Set 16-04 = 2 (CFM) → In this case, when speed is 60%, it will display as 120.0 CFM.
3 20001 – 29999 □□. □□ To display 100% speed as “65.00°C” → Set 16-03 = 26500 (for 05-01, 06-01 to 06-15, setting range: 0000 to 9999) → Set 16-04 = 20 (°C) → In this case, when speed is 60%, it will display as 39.00°C.
4 30001 - 39999 □. □□□ To display 100% speed as “2.555 m/s” → Set 16-03 = 32555 → Set 16-04 = 14 (m/s) → In this case, when speed is 60%, it will display as 1.533 m/s.

Manual — Parameter copy conditions and version limits — page 310

Manual reference: physical PDF page 310. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Adjusting the screen contrast of the digital operator: When set to 0, the screen backlight is turned off.

‧ The LCD digital operator has built-in memory (EEPROM) and supports the following functions: (1) Read: Store inverter parameters in the operator (INV → OP). (2) Write: Write parameter settings from the operator into the inverter (OP → INV). (3) Confirm: Compare the parameters stored in the operator with those in the inverter. ‧ 16-07= 0: Do not perform parameter copy = 1: Read (all parameters will be copied from the inverter to the digital operator) = 2: Write (all parameters will be copied from the digital operator to the inverter) = 3: Confirm (the parameters in the inverter will be compared with those in the digital operator)

‧ Set 16-08 = 0 to prevent accidental overwriting of data stored in the digital operator. If 16-07 = 1 and a read operation is executed (copying inverter parameter settings to the digital operator), a "RDP Read Prohibited" warning will appear on the operator screen and the read process will be terminated. ‧ Follow the steps below to operate the parameter copy function: ─ When using the write function, verify that the following settings are consistent: ① Inverter model ② Inverter capacity

Note 1: From version V1.20 onward, inverter data from an older version can be written into a newer inverter. After copying, cycle the power to complete the update. Note 2: From version V1.20 onward, the copy function is not restricted by parameter 00-00 (Control Mode Selection).

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Auxiliary parameter card — PDF page 310

Source row Parameter Name Scope/options and printed unit
1 16- 05 LCD backlight 【0~7】

Auxiliary parameter card — PDF page 310

Source row Parameter Name Scope/options and printed unit
1 16- 07 Copy function selection [0]: Do not perform parameter copying [1] Read inverter parameters to the digital operator [2]: Write operator parameters to the inverter [3]: Compare inverter and operator parameters

Auxiliary parameter card — PDF page 310

Source row Parameter Name Scope/options and printed unit
1 16- 08 Allow read selection [0]: Do not allow reading inverter parameters to the digital operator [1]: Allow reading of inverter parameters to the digital operator

Manual — READ copy procedure — page 311

Manual reference: physical PDF page 311. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ READ: Follow the steps below to store inverter parameter settings to the digital operator interface.

Group;14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func.

PARA16;-07:Copy Sel;-08:READ Sel;-09:Keypad Loss Sel

Edit16-07;Copy Sel;0 Normal;(0–3);<0>

Edit16-07;Copy Sel;1 READ;(0–3);<0>

-ADV-;READ;INV→OP;progress bar.

-ADV-;READ COMPLETE;full progress bar.

RDP;Read Prohibited

Source exact seven-step procedure including success/failure alternatives. Screens are separately bounded. Write source saysreadoperation andshowsINV→OP contrarytoconceptdescription310; bothflagged, not corrected.

Parameter copy read procedure — PDF page 311

Source row Step Description
1 1 From the group menu, select the Copy Function Parameter Group (Group 16).
2 2 Press the DATA/ENTER key and navigate to the Copy Function Selection parameter (16-07).
3 3 Press the DATA/ENTER key again to display the data setting/read screen (the number will be highlighted and blinking).
4 4 Use the UP key to change the setting value to 1 (Read).
5 5 ‧ Begin the read operation by pressing the DATA/ENTER key; the screen will display as shown on the left. ‧ A progress bar will appear at the bottom of the LCD screen to indicate the read status.
6 6 If the read is successful, “READ COMPLETE” will appear on the digital operator interface. ‧ If the message “RDP Read Prohibited” appears, it indicates the inverter parameters could not be saved to the memory of the digital operator interface. ‧ If an error is displayed, press any key to clear the error and return to the 16-07 screen.
7 7 ‧ Press the DSP/FUN key to return to the submenu (16-07).

Manual — WRITE copy procedure — page 312

Manual reference: physical PDF page 312. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ WRITE: Follow the steps below to write parameter settings stored in the digital operator interface to the inverter.

Group;14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func.

PARA16;-07:Copy Sel;-08:READ Sel;-09:Keypad Loss Sel

Edit16-07;Copy Sel;0 Normal;(0–3);<0>

Edit16-07;Copy Sel;2 WRITE;(0–3);<0>

-ADV-;WRITE;INV→OP;progress bar.

-ADV-;WRITE COMPLETE;full progress bar.

WRE;Write Error

Source exact seven-step procedure including success/failure alternatives. Screens are separately bounded. Write source saysreadoperation andshowsINV→OP contrarytoconceptdescription310; bothflagged, not corrected.

Parameter copy write procedure — PDF page 312

Source row Step Description
1 1 From the group menu, select the Copy Function Parameter Group (Group 16).
2 2 Press the DATA/ENTER key and navigate to the Copy Function Selection parameter (16-07).
3 3 Press the DATA/ENTER key to display the setting/read screen (the number will be highlighted and blinking).
4 4 Use the UP key to change the setting value to 2 (Write).
5 5 ‧ Press the DATA/ENTER key to begin the read operation. ‧ A progress bar will appear at the bottom of the screen to indicate the writing progress.
6 6 ‧ When the write is successful, “WRITE COMPLETE” will appear on the digital operator. ‧ Afterward, “SysInit” will be displayed. At this point please power off and restart the system. ‧ The error message “WRE Write Error” may appear if writing the parameter settings from the digital operator to the inverter fails. ‧ If an error is displayed, press any key to clear the error and return to the 16-07 screen.
7 7 ‧ Press the DSP/FUN key to return to the submenu (16-07).

Manual — Repeated WRITE procedure and operator loss — page 313

Manual reference: physical PDF page 313. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ WRITE: Follow the steps below to write parameter settings stored in the digital operator interface to the inverter.

If parameter 00-02 is set to 0 (Run/Stop command is controlled by the operator), this parameter determines whether the inverter will stop when the digital operator is removed.

Group;14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func.

PARA16;-07:Copy Sel;-08:READ Sel;-09:Keypad Loss Sel

Edit16-07;Copy Sel;0 Normal;(0–3);<0>

Edit16-07;Copy Sel;2 WRITE;(0–3);<0>

-ADV-;WRITE;INV→OP;progress bar.

-ADV-;WRITE COMPLETE;full progress bar.

WRE;Write Error

Page-local exact source options; no inferred units. Source restrictions and contradictory prose remain separately preserved.

Source exact seven-step procedure including success/failure alternatives. Screens are separately bounded. Write source saysreadoperation andshowsINV→OP contrarytoconceptdescription310; bothflagged, not corrected.

Auxiliary parameter card — PDF page 313

Source row Parameter Name Scope/options and printed unit
1 16- 09 Operator disconnection selection [0]: Continue operation when the LCD operator is disconnected [1]: Display a fault when the LCD operator is disconnected

Parameter copy write procedure — PDF page 313

Source row Step Description
1 1 From the group menu, select the Copy Function Parameter Group (Group 16).
2 2 Press the DATA/ENTER key and navigate to the Copy Function Selection parameter (16-07).
3 3 Press the DATA/ENTER key to display the setting/read screen (the number will be highlighted and blinking).
4 4 Use the UP key to change the setting value to 2 (Write).
5 5 ‧ Press the DATA/ENTER key to begin the read operation. ‧ A progress bar will appear at the bottom of the screen to indicate the writing progress.
6 6 ‧ When the write is successful, “WRITE COMPLETE” will appear on the digital operator. ‧ Afterward, “SysInit” will be displayed. At this point please power off and restart the system. ‧ The error message “WRE Write Error” may appear if writing the parameter settings from the digital operator to the inverter fails. ‧ If an error is displayed, press any key to clear the error and return to the 16-07 screen.
7 7 ‧ Press the DSP/FUN key to return to the submenu (16-07).

Manual — RTC clock and time display — page 314

Manual reference: physical PDF page 314. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Before using the real-time clock (RTC) function, the internal clock must be configured. • Year, month, and day are set via parameter 16-11 (RTC Date Setting), while hour and minute are set via parameter 16-12 (RTC Time Setting). • To use the RTC function, the digital operator must be connected to the inverter; the RTC only operates when the operator is attached. • Parameter 16-10 RTC Time Display Setting Hide/Show determines whether the RTC appears on the operator screen. This does not affect the RTC’s timekeeping. The RTC time appears at the top of the digital operator when parameter 16-10 is set to 1. Refer to Figure 4.3.135.

Figure 4.3.134 RTC Display (Example) • You may also monitor current RTC date and time using monitoring parameters 12-72 and 12-73. • RTC Features: ─ Up to 4 activations per day. ─ 4-week scheduling. ─ Timer offset function (preset time). ─ Timer activation via multi-function digital inputs. ─ Fixed-speed operation selection. ─ Multi-function digital output driven by timer.

Monitor 00:00;FreqRef;12-16 = 000.00Hz;12-17 = 000.00Hz;12-18 = 0000.0A. Example screen readings, not ratings.

Exact page-local options. RTC conditions314–321 and motor tuning qualifications322 onward remain attached; source conflicts not harmonized. No inferred units.

Parameter card — PDF page 314

Source row Parameter Name Scope/options and printed unit
1 16- 10 RTC Time Display Setting [0]: Hide [1]: Show

Parameter card — PDF page 314

Source row Parameter Name Scope/options and printed unit
1 16- 11 RTC date setting 【12.01.01 ~ 99.12.31】

Parameter card — PDF page 314

Source row Parameter Name Scope/options and printed unit
1 16- 12 RTC time setting 【00:00 ~ 23:59】

Manual — RTC time periods and source settings — page 315

Manual reference: physical PDF page 315. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Using the RTC Timer Function: • A single timer source can be linked to multiple time periods, and each time period can be assigned to multiple timers. • Timers can be set up through the following steps: ① Step 1: Enable the timer – the timer can be enabled via parameter 16-13 [RTC Timer Function Setting].

Exact page-local options. RTC conditions314–321 and motor tuning qualifications322 onward remain attached; source conflicts not harmonized. No inferred units.

Shared source scope [00:00 ~ 23:59] physically on PDF315; split parallel columns by parameter, no inferred distinct ratings.

Applies to immediately associated group of parameters on315 only.

Shared source scope [1]Monday [2]Tuesday [3]Wednesday [4]Thursday [5]Friday [6]Saturday [7]Sunday physically on PDF315; split parallel columns by parameter, no inferred distinct ratings.

Shared source scope [0 ~ 31] Refer to Table4.3.38 physically on PDF315; split parallel columns by parameter, no inferred distinct ratings.

Parameter card — PDF page 315

Source row Parameter Name Scope/options and printed unit
1 16- 13 RTC timer function [0]: Disabled [1]: Enabled [2]: Controlled via DI

Parameter card — PDF page 315

Source row Parameter Name Scope/options and printed unit
1 16- 30 RTC offset selection [0]: Disabled [1]: Enabled [2]: Controlled via DI

Parameter card — PDF page 315

Source row Parameter Name Scope/options and printed unit
1 16- 31 RTC offset time setting 【00:00 ~ 23:59】

Parameter card — PDF page 315

Source row Parameter Name Scope/options left column Scope/options right column
1 16- 36 RTC speed selection [0]: Disabled [1]: Selected by Timer 1 [2]: Selected by Timer 2 [3]: Selected by Timer 3 [4]: Selected by Timer 4 [5]: Selected by Timer 1 + Timer 2

Parameter card — PDF page 315

Source row Parameter Name Scope/options left column Scope/options right column
1 16- 37 RTC operation direction selection [xxx0 B]: RTC Operation 1 Forward [xx0x B]: RTC Operation 2 Forward [x0xx B]: RTC Operation 3 Forward [0xxx B]: RTC Operation 4 Forward [xxx1 B]: RTC Operation 1 Reverse [xx1x B]: RTC Operation 2 Reverse [x1xx B]: RTC Operation 3 Reverse [1xxx B]: RTC Operation 4 Reverse

RTC start and end time parameters — PDF page 315

Source row Parameter Name
1 16- 14 P1 Start Time
2 16- 22 P3 Start Time
3 16- 15 P1 end time
4 16- 23 P3 end time
5 16- 18 P2 Start Time
6 16- 26 P4 Start Time
7 16- 19 P2 end time
8 16- 27 P4 end time

RTC start and end time parameters shared scope — PDF page 315

Source row Label Shared scope
1 Scope [00:00 ~ 23:59]

RTC start and end weekday parameters — PDF page 315

Source row Parameter Name
1 16- 16 P1 Start Day
2 16- 24 P3 Start Day
3 16- 17 P1 end day
4 16- 25 P3 end day
5 16- 20 P2 Start Day
6 16- 28 P4 Start Day
7 16- 21 P2 end day
8 16- 29 P4 end day

RTC start and end weekday parameters shared scope — PDF page 315

Source row Label Shared scope
1 Scope [1]: Monday [2]: Tuesday [3]: Wednesday [4]: Thursday [5]: Friday [6]: Saturday [7]: Sunday

RTC timer-source parameters — PDF page 315

Source row Parameter Name
1 16- 32 Timer Source 1
2 16- 34 Timer Source 3
3 16- 33 Timer Source 2
4 16- 35 Timer Source 4

RTC timer-source parameters shared scope — PDF page 315

Source row Label Shared scope
1 Scope [0 ~ 31] Refer to Table 4.3.38

Manual — RTC configuration structure — page 316

Manual reference: physical PDF page 316. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

② Step 2: Set the time periods — You may configure the start/end time and date for each period using parameters 16-14 through 16-31. If the start time is equal to the end time, the timer period will be disabled. ③ Step 3: Assign timers — Allocate time periods to a specific timer using parameters 16-32 to 16- 35. ④ Step 4: Link to parameters — Timers can be linked to relay outputs. Each relay output may be linked to only one timer (e.g., parameters 03-11, 03-12, 03-28, and 16-36). • Refer to the RTC system architecture below.

Figure 4.3.135 RTC Structure • Timer Configuration (Parameters 16-32 to 16-35) • Assign the desired operation period based on Table 4.3.38.

Step1 Start timer;Step2 Time interval;Step3 Generate Timer;Step4 Link Parameters. Start/Stop16-13;Time Period1 16-14~16-17;Time Period2 16-18~16-21;Time Period3 16-22~16-25;Time Period4 16-26~16-29;Start/Stop Offset16-30;Offset Time16-31;Timer1(16-32);Timer2(16-33);Timer3(16-34);Timer4(16-35);RTC Speed Selection(16-36);Relay Output R1A-R1C(03-11);DO1(03-12);DO2(03-28). Block labels preserved; wiring geometry not inferred.

Manual — RTC source bit combination lookup — page 317

Manual reference: physical PDF page 317. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.38 Assigning Time Periods to Timers

• RTC Speed Selection (Parameter 16-36) 16-36 = 0: Off = 1: Reference frequency = Frequency for Step 0 (Parameter 05-01) when Timer 1 is active. = 2: Reference frequency = Frequency for Step 0 (Parameter 05-01) when Timer 2 is active. = 3: Reference frequency = Frequency for Step 0 (Parameter 05-01) when Timer 3 is active. = 4: Reference frequency = Frequency for Step 0 (Parameter 05-01) when Timer 4 is active. = 5: Reference frequency is selected via Timer 1 + Timer 2 combination.

• The reference frequency and motor rotation direction can be controlled via the RTC function. 1. When the designated timer is triggered, the inverter will start running. Other timers will not affect the operation. 2. When parameter 16-36 (RTC Speed Selection) is set to Timer 1 through 4, the actions of P1 to P4 correspond to parameter 16-37 Operation Direction Selection (RTC Operation 1 to 4).

  1. When RTC Speed Selection is set to 5 (selected by Timer 1 + 2), both 00-02 (Run Command Source) and 00-05 (Frequency Command Source) must be set to RTC. The reference frequency will be controlled by RTC Timer 1 and 2, and the inverter will continue executing the run command. • For details on the control of frequency sources, please refer to Table 4.3.39. * Parameter 11-00 (Motor Direction Lock) restricts the operation direction selection set in parameter 16-37. * When using offset, parameter 16-37 will follow the operation direction of Timer 1.

Literal source lookup. RTC restrictions on317/319, operation direction lock11-00 and offset direction qualifications retained. Table319 source00-02 meanings differ from earlier manual, flagged.

Table4.3.38 RTC timer source — PDF page 317

Source row 16-32 to16-35 setting O P4 P3 P2 P1 Timer Function Display
1 0 0 0 0 0 0 No Timer Selected None
2 1 0 0 0 0 1 Time Period 1 P1
3 2 0 0 0 1 0 Time Period 2 P2
4 3 0 0 0 1 1 Time Periods 1 & 2 P1+P2
5 4 0 0 1 0 0 Time Period 3 P3
6 5 0 0 1 0 1 Time Periods 1 & 3 P1+P3
7 6 0 0 1 1 0 Time Periods 2 & 3 P2+P3
8 7 0 0 1 1 1 Time Periods 1, 2 & 3 P1+P2+P3
9 8 0 1 0 0 0 Time Period 4 P4
10 9 0 1 0 0 1 Time Periods 1 & 4 P1+P4
11 10 0 1 0 1 0 Time Periods 2 & 4 P2+P4
12 11 0 1 0 1 1 Time Periods 1, 2 & 4 P1+P2+P4
13 12 0 1 1 0 0 Time Periods 3 & 4 P3+P4
14 13 0 1 1 0 1 Time Periods 1, 3 & 4 P1+P3+P4
15 14 0 1 1 1 0 Time Periods 2, 3 & 4 P2+P3+P4
16 15 0 1 1 1 1 Time Periods 1, 2, 3 & 4 P1+P2+P3+P4
17 16 1 0 0 0 0 Offset Selection Offset(O)
18 17 1 0 0 0 1 Offset + Time Period 1 O+P1
19 18 1 0 0 1 0 Offset + Time Period 2 O+P2
20 19 1 0 0 1 1 Offset + Time Periods 1 & 2 O+P1+P2
21 20 1 0 1 0 0 Offset + Time Period 3 O+P3
22 21 1 0 1 0 1 Offset + Time Periods 1 & 3 O+P1+P3
23 22 1 0 1 1 0 Offset + Time Periods 2 & 3 O+P2+P3
24 23 1 0 1 1 1 Offset + Time Periods 1, 2 & 3 O+P1+P2+P3
25 24 1 1 0 0 0 Offset + Time Period 4 O+P4
26 25 1 1 0 0 1 Offset + Time Periods 1 & 4 O+P1+P4
27 26 1 1 0 1 0 Offset + Time Periods 2 & 4 O+P2+P4
28 27 1 1 0 1 1 Offset + Time Periods 1, 2 & 4 O+P1+P2+P4
29 28 1 1 1 0 0 Offset + Time Periods 3 & 4 O+P3+P4
30 29 1 1 1 0 1 Offset + Time Periods 1, 3 & 4 O+P1+P3+P4
31 30 1 1 1 1 0 Offset + Time Periods 2, 3 & 4 O+P2+P3+P4
32 31 1 1 1 1 1 Offset + Time Periods 1, 2, 3 & 4 O+P1+P2+P3+P4

Manual — RTC speed combination lookup — page 318

Manual reference: physical PDF page 318. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.39 Reference Frequency Selected by Timer 1 and 2

Literal source lookup. RTC restrictions on317/319, operation direction lock11-00 and offset direction qualifications retained. Table319 source00-02 meanings differ from earlier manual, flagged.

Table4.3.39 timer combination speed — PDF page 318

Source row Timer2 Timer1 Primary frequency command source00-05 Frequency Source Operation Direction Selection
1 0 0 6(RTC) Parameter 05-01 0th Step Speed Setting Based on Parameter 16-37 (RTC 1)
2 0 1 6(RTC) Parameter 05-02 1st Step Speed Setting Based on Parameter 16-37 (RTC 2)
3 1 0 6(RTC) Parameter 05-03 2nd Step Speed Setting Based on Parameter 16-37 (RTC 3)
4 1 1 6(RTC) Parameter 05-04 3rd Step Speed Setting Based on Parameter 16-37 (RTC 4)

Manual — RTC run status and operating restrictions — page 319

Manual reference: physical PDF page 319. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

RTC function will not operate correctly under the following conditions: 1. Fire Mode is triggered via digital input terminal. 2. KEB function is active. (1) The main frequency command source for RTC function is primarily determined based on Table 4.3.39 above. However, you may also use frequency source combination mode selection (00-07) to apply a combination of primary and secondary frequency sources. (2) If the main run command source for RTC is set to 0–3 (0: Keypad, 1: External Control, 2: Communication Control, 3: PLC), the relationship between the main run command and RTC timer status is shown in Table 4.3.40 below.

Table 4.3.40 Main Run Command and RTC Timer Status

• 00-02=0~3 (0: Keypad, 1: External Control, 2: Communication Control, 3: PLC), while 4 indicates RTC. • Application Example: The following example illustrates how the RTC timer can be linked to different parameters. In this example, the motor operates from 6:00 AM to 10:00 PM on Monday, from 8:00 AM to 8:00 PM from Tuesday to Friday, from 8:00 AM to 6:00 PM on Saturday, and from 8:00 AM to 12:00 PM on Sunday. The motor runs at Speed 1 on weekdays (Monday through Friday), and at Speed 2 on weekends (Saturday and Sunday).

Figure 4.3.136 RTC Timer Application Example

Time;00:00,02:00,04:00,06:00,08:00,10:00,12:00,14:00,16:00,18:00,20:00,22:00,24:00;Day;Mon,Tue,Wed,Thu,Fri,Sat,Sun;weekdays;weekends;Time period1(P1);Time period2(P2);Time period3(P3);Time period4(P4). Explicit periods described in source prose; no interpolated values.

Literal source lookup. RTC restrictions on317/319, operation direction lock11-00 and offset direction qualifications retained. Table319 source00-02 meanings differ from earlier manual, flagged.

Table4.3.40 main run command and RTC timer — PDF page 319

Source row Main run command00-02 RTC Timer x Status Inverter status
1 0~3 0 The inverter will not operate (no run command).
2 0~3 1 The inverter will not operate (no run command).
3 4 0 The inverter will not operate (RTC timer disabled).
4 4 1 Inverter operating. The operation direction is determined by parameter 16-37 (Operation Direction Selection).

Manual — RTC weekday example configuration — page 320

Manual reference: physical PDF page 320. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

①. Go to parameter group 16 to enable the timer (to use the RTC timer function, the internal time must be set first). First, set parameters 16-11 and 16-12 to the correct date and time, then set parameter 16-13 (RTC timer function) to [1]: Enable.

②. Set Time Period 1 (P1) Start Time 1: Parameter 16-14 = 06:00:00 (6 AM) End Time 1: Parameter 16-15 = 22:00:00 (10 PM) Start Day 1: Parameter 16-16 = 1 (Monday) End Day 1: Parameter 16-17 = 1 (Monday)

③. Set Time Period 2 (P2) Start Time 2: Parameter 16-18 = 08:00:00 (8 AM) End Time 2: Parameter 16-19 = 20:00:00 (8 PM) Start Day 2: Parameter 16-20 = 2 (Tuesday) End Day 2: Parameter 16-21 = 5 (Friday)

④. Set Time Period 3 (P3) Start Time 3: Parameter 16-22 = 08:00:00 (8 AM) End Time 3: Parameter 16-23 = 18:00:00 (6 PM) Start Day 3: Parameter 16-24 = 6 (Saturday) End Day 3: Parameter 16-25 = 6 (Saturday)

⑤. Set Time Period 4 (P4) Start Time 4: Parameter 16-26 = 08:00:00 (8 AM) End Time 4: Parameter 16-27 = 12:00:00 (12 AM) Start Day 4: Parameter 16-28 = 7 (Sunday) End Day 4: Parameter 16-29 = 7 (Sunday)

⑥‧ Use Parameter 16-32 (Timer 1) Assign all time periods (P1, P2, P3, P4) to the timer Set Parameter 16-32 = 15 (Timer 1 Source = P1 + P2 + P3 + P4)

⑦‧ 16-36 RTC Speed Selection via Timer 1: Set Parameter 16-36 (Speed Selection) to 1: Selected by Timer 1. When Timer 1 is active, the frequency corresponds to Preset Speed 0. Set Parameter 16-37 (Run Direction Selection) to 0000b, so the run direction for Time Periods 1 to 4 (P1~P4) corresponds to the settings of 16- 37.

⑧‧ To select two preset speeds (Speed 1 and Speed 2), set Parameter 16-36 (RTC Speed Selection) to 5: Selected by Timers 1 + 2. When Timer 1 is active, the frequency corresponds to Preset Speed 1 (Parameter 05-02); when Timer 2 is active, it corresponds to Preset Speed 2. Set Parameter 16-37 (Run Direction Selection) to 0000b, so when Timers 1 and 2 are active, the motor will run forward.

Manual — RTC offset restart and accuracy — page 321

Manual reference: physical PDF page 321. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Before using the offset time function, make sure to select RTC Offset (Parameter 16-30) and set the RTC Offset Time (Parameter 16-31). The inverter will follow the configuration defined by the time period-to- counter assignment function, which varies depending on the setup. Refer to Figure 4.3.138 below for the configuration of time period assignment to counters.

Figure 4.3.137 Operation with Offset Time

• Example: • If Parameter 16-36 (RTC Speed Selection) is currently set to Timer 1, and Parameter 16-32 (Timer Source 1) is set to [17] Offset (O) + P1, and Parameter 16-30 (RTC Offset Selection) is set to "Triggered by DI." When the DI switch is turned ON, the RTC will activate immediately according to the offset time specified in Parameter 16-31 (RTC Offset Time). This function is especially useful when operation is needed outside of the scheduled P1 period.

• If the timer source is set to [15] (P1 + P2 + P3 + P4) and the STOP key is pressed during Time Period 1 (P1), normally the RTC function would wait until the next time period (P2) to resume operation. However, it is also possible to configure Parameter 16-30 (RTC Offset Selection) to "Triggered by DI." If the DI switch is turned on, the RTC function will be immediately activated, allowing the inverter to resume operation.

• Regardless of the timer source setting, if the STOP key is pressed during a scheduled time period and the inverter needs to resume operation within that same period, there are two options: 1. Set Parameter 16-30 (RTC Offset Selection) to "Triggered by DI," and assign DI function 56 to enable the offset. 2. As long as the RTC offset selection (16-30) has been toggled from OFF to ON, the RTC function will be reactivated.

★Remarks: RTC accuracy:

Multi-function digital input (G03-00 to05=56);Time difference effect;Time difference(G16-31);t;t. Pulse geometry remains in original source.

Supplier stated accuracy at source temperatures; not independent calibration or environmental approval.

RTC accuracy — PDF page 321

Source row Temperature Deviation
1 +25°C ±3 seconds/day
2 -20°C / +50°C ±6 seconds/day

Manual — Automatic tuning parameter cards — page 322

Manual reference: physical PDF page 322. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

17- Auto-Tuning Function Group

1. The motor rated voltage setting value is based on 220V class; doubling this gives the value for 440V class. 2. The setting range for the motor rated frequency is 0.0 to 599.0 Hz.

Set the following parameters before performing auto-tuning: Motor Rated Output Power (17-01), Motor Rated Current (17-02), Motor Rated Voltage (17-03), Motor Rated Frequency (17-04), Motor Rated Speed (17-05), and Number of Motor Poles (17-06).

■ Auto-Tuning Mode Selection (17-00) ‧ When using rotation-based auto-tuning (17-00=0), higher performance can be achieved. After completing the rotational auto-tuning, the following parameters will be automatically updated with the measured values: Motor 1 Magnetizing Current (02-09), Motor 1 Core Saturation Coefficient 1 (02-10), Motor 1 Core Saturation Coefficient 2 (02-11), and Motor 1 Core Saturation Coefficient 3

Exact page-local options. RTC conditions314–321 and motor tuning qualifications322 onward remain attached; source conflicts not harmonized. No inferred units.

Parameter card — PDF page 322

Source row Parameter Name Scope/options left column Scope/options right column
1 17- 00 Auto-Tuning Mode Selection [0]: Rotational automatic tuning [1]: Static automatic tuning [2]: Stator resistance measurement [3]: Reserved [4]: Loop tuning [5]: Integrated rotational automatic tuning (Options: 4 + 2 + 0) [6]: Integrated static automatic tuning (Options: 4 + 2 + 1)

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 01 Motor rated output power 【0.00~600.00】KW

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 02 Motor rated current 25%~120% inverter rated current

Parameter card — PDF page 322

Source row Parameter Name Scope/options left column Scope/options right column
1 17- 03 Motor rated voltage 200V:【50.0~240.0】V 400V:【100.0~480.0】V

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 04 Motor rated frequency 【4.8~599.00】 Hz

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 05 Motor rated speed 【0~24000】rpm

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 06 Motor number of poles 【2~16】pole

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 07 PG pulse count 【0~60000】PPR

Parameter card — PDF page 322

Source row Parameter Name Scope/options left column Scope/options right column
1 17- 08 Motor no-load voltage 200V:【50~240】V 400V:【100~480】V

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 09 Motor excitation current [15~70]% motor rated current

Parameter card — PDF page 322

Source row Parameter Name Scope/options left column Scope/options right column
1 17- 10 Automatic tuning start [0]: Disabled [1]: Enabled

Parameter card — PDF page 322

Source row Parameter Name Scope/options left column Scope/options right column
1 17- 11 Automatic tuning error history [0]: No error [1]: Motor data error [2]: Stator resistance tuning error [3]: Leakage inductance tuning error [4]: Rotor resistance tuning error [5]: Mutual inductance tuning error [6]: Encoder error [7]: DT error [8]: Motor acceleration error [9]: Warning

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 12 Motor leakage inductance ratio 【0.1~15.0】%

Parameter card — PDF page 322

Source row Parameter Name Scope/options and printed unit
1 17- 13 Motor slip frequency 【0.10~20.00】Hz

Parameter card — PDF page 322

Source row Parameter Name Scope/options left column Scope/options right column
1 17- 14 Rotational tuning mode selection [0]: VF-based rotational auto-tuning [1]: Vector-based rotational auto-tuning

Manual — Automatic tuning applicability and conditions — page 323

Manual reference: physical PDF page 323. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(02-12).

‧ Static Auto-Tuning (17-00 = 1): During static auto-tuning, the motor does not rotate. After completing the stationary auto-tuning, the Motor Leakage Inductance Ratio (02-33) and the Motor Slip (02-34) will be populated with the automatically measured values.

‧ Stator Resistance Measurement (17-00 = 2) is intended for applications with long motor cables (over 50 meters). After the measurement, the Motor 1 Line-to-Line Resistance (02-15) will be automatically filled with the measured value.

‧ Loop Tuning (17-00 = 4): This function optimizes the current loop response, improving the bandwidth of both current and torque control.

‧ Integrated Rotational Auto-Tuning (17-00 = 5): A three-in-one process that includes Loop Tuning (17- 00 = 4), Stator Resistance Measurement (17-00 = 2), and Rotational Auto-Tuning (17-00 = 0).

‧ Integrated Static Auto-Tuning (17-00 = 6): Also a three-in-one process including Loop Tuning (17-00 = 4), Stator Resistance Measurement (17-00 = 2), and Static Auto-Tuning (17-00 = 1).

■ Motor Rated Output Power (17-01) ‧ The initial value is based on the inverter capacity (13-00). Please configure this according to the motor nameplate specifications.

■ Motor Rated Current (17-02) ‧ The initial value is based on the inverter capacity (13-00). Please configure this according to the motor nameplate specifications. ‧ The setting range is from 10% to 120% of the inverter’s rated current. ‧ For SLV and SV modes, the setting range is from 25% to 120% of the inverter’s rated current.

■ Motor Rated Voltage (17-03) The initial value is determined by the inverter capacity (13-00). Please set it according to the motor nameplate specifications. If the motor rated voltage exceeds the inverter input voltage, you must prevent inverter output voltage saturation (see Example 1).

■ Motor Rated Frequency (17-04) Set according to the motor nameplate specifications.

■ Motor Rated Speed (17-05) Set according to the motor nameplate specifications.

■ Number of Motor Poles (17-06) Set the number of poles for the motor. The available settings are 2, 4, 6, and 8 poles.

■ PG Pulse Count (17-07) *(V/F+PG, SV, PMSV are only for special projects) Set the number of pulses per revolution. When operating in SV mode or V/f+PG mode, the encoder must be mounted directly on the motor shaft without any gear reduction ratio.

■ Motor No-Load Voltage (17-08) ‧ Motor no-load voltage is primarily for use in SV or SLV modes. Set the value to approximately 10– 50V below the input voltage to ensure torque performance at the rated frequency. ‧ The no-load voltage (17-08) is typically set to 85–95% of the motor’s rated voltage. In general, the higher the motor’s horsepower, the closer the no-load voltage setting can be to the rated voltage— however, it must not exceed the rated voltage. ‧ It is permissible to set the motor no-load voltage higher than the actual inverter input voltage, but in such cases, it is recommended to operate the motor at a lower frequency. Running at rated frequency may easily trigger over-voltage faults. ‧ The larger the motor capacity, the higher the no-load voltage. ‧ A lower no-load voltage reduces no-load current, but once the load is applied, it weakens the flux and increases the current. ‧ The higher the no-load voltage, the greater the no-load current. When a load is applied, magnetic flux increases and current decreases. Increasing magnetic flux may result in a stronger counter- electromotive force (back EMF), which can cause torque control failure.

Manual — Autotuning settings and higher-voltage example — page 324

Manual reference: physical PDF page 324. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ Motor Excitation Current (17-09) ‧ This parameter can only be set when performing static auto-tuning or stator resistance measurement (17-00 = 1 or 2). ‧ In rotational auto-tuning, the excitation current is automatically measured, so this parameter will not appear. ‧ The typical setting for motor excitation current is approximately 33%. During test operation, the display will show the message “Atune”. Once auto-tuning is complete, it will display “AtEnd.”

■ Auto-Tuning Error History (17-11) ‧ If an error occurs during the auto-tuning process, the message “AtErr” will appear. The specific error code can be found in parameter 17-11. ‧ For details on error causes and troubleshooting, please refer to Chapter 5. Note: Motor tuning error history (17-11) stores the result of the most recent tuning failure.

■ Motor Leakage Inductance Ratio (17-12) ‧ This parameter is only available when performing stator resistance measurement auto-tuning (17-00 = 2). ‧ In static and rotational auto-tuning modes, the leakage inductance ratio is automatically measured, so this parameter will not appear. ‧ Typical setting value is 4%. During test operation, adjust according to the instructions under parameter 02-33 Motor Leakage Inductance Ratio.

■ Motor Slip (17-13) ‧ This parameter is only available when performing stator resistance measurement auto-tuning (17-00 = 2). ‧ In static and rotational auto-tuning modes, the leakage inductance ratio is automatically measured, so this parameter will not appear. ‧ The setting value should be calculated according to the explanation for parameter 02-34 Motor Slip.

Example 1: Motor rated voltage (440V/60Hz) is higher than inverter input voltage (380V/50Hz).

Figure 4.3.138 Rated Voltage and Frequency Settings

Step 1: Set the Auto-Tuning Mode Selection (17-00) and, based on the motor nameplate, set Motor Rated Output Power (17-01) and Motor Rated Current (17-02).

Step 2: Set Motor Rated Voltage (17-03) = 440V according to the motor nameplate.

Step 3: Set Motor Rated Frequency (17-04) = 60Hz according to the motor nameplate.

Step 4: Set Motor Rated Speed (17-05), Motor Pole Number (17-06), and PG Pulse Count (17-07) according to the motor nameplate. PG Pulse Count (17-07) can be set in V/F+PG and SV modes.

Step 5: Set Motor No-Load Voltage (17-08) = 360V; for torque control, this value should be 20V below the inverter input voltage.

Step 6: Perform auto-tuning. After setting Auto-Tuning Start (17-10) to enable [1], the system will enter the preparation screen. Press the Run key to begin auto-tuning.

If a PG card is installed, the PG Rotation Direction Selection (20-28) will be automatically adjusted during the tuning process. During auto-tuning, the Motor Rated Frequency (17-04) will be automatically assigned as Motor 1 Base Frequency (01-12). If Motor 1 Maximum Output Frequency (01-02) is different from Motor 1 Base Frequency (01-12), upon completion of the auto-tuning process, the system will automatically update Motor 1 Maximum Output Frequency (01-02) to match the value of Motor 1 Base Frequency (01-12).

Output Voltage;0;17-03;440V;Output Frequency;17-04;60Hz. Motor rated voltage(for auto-tuning operation);Rated voltage(for motor nameplate);Motor rated frequency(for auto-tuning operation);Rated frequency(for motor nameplate). Inverter;380V/50Hz;440V/60Hz. Diagram labels only; example figures not product ratings.

Manual — Long-cable and rotational tuning — page 325

Manual reference: physical PDF page 325. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ When the inverter input voltage (or frequency) is higher than the motor rated voltage (or frequency), the Motor Rated Voltage (17-03) and Motor Rated Frequency (17-04) should be configured according to the motor nameplate.

Example 2: If the inverter input voltage and frequency are 440V/50Hz, and the motor rated voltage and frequency are 380V/33Hz, set 17-03 = 380V (motor rated voltage) and 17-04 = 33Hz (motor rated frequency).

■ Long Motor Cables between Inverter and Motor ‧ When the wiring length between the motor and inverter exceeds 50 meters, be sure to perform Long Cable Static Auto-Tuning (17-00 = 2). For optimal vector control performance, first perform Rotational Auto-Tuning with a short cable (17-00 = 0), then follow up with Long Cable Static Auto-Tuning (17-00 = 2). ‧ If Rotational Auto-Tuning (17-00 = 0) cannot be executed, manually input values for Motor 1 Mutual Inductance (02-18), Motor 1 Magnetizing Current (02-09), and Motor 1 Core Saturation Compensation Coefficients 1–3 (02-11 to 02-13). ‧ In V/F control applications using long cables, it is essential to perform Long Cable Static Auto-Tuning (17-00 = 2).

■ Rotational Auto-Tuning Type Selection (17-14) ‧ This parameter is only available when Rotational Auto-Tuning (17-00 = 0) or Integrated Rotational Auto- Tuning (17-00 = 5) is selected. ‧ V/F-Type Rotational Auto-Tuning (17-14=0) is applicable under VF mode for general standard induction motors that can operate stably without oscillation under no-load conditions. This option provides the highest versatility. ‧ Vector-Type Rotational Auto-Tuning (17-14=1) is applicable under V/F mode for special induction motors that are prone to oscillation under no-load conditions. These motors are often high-speed types. ‧ If the V/F-Type Rotational Auto-Tuning (17-14 = 0) fails, retry using Vector-Type Rotational Auto- Tuning (17-14 = 1). ‧ Vector-Type Rotational Auto-Tuning (17-14 = 1) uses an internal current vector control method to measure the motor’s no-load current, helping to avoid current oscillation issues under V/F mode with special induction motors.

Manual — Slip compensation cards and V/F adjustment — page 326

Manual reference: physical PDF page 326. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

18- Slip Compensation Function Group

‧ Regardless of load variation, the slip compensation function calculates motor torque based on output current and maintains constant motor speed. ‧ When operating under varying loads, slip compensation is used to enhance speed accuracy, primarily in V/F control mode.

V/F Mode Adjustment (1) Low-Speed Slip Compensation Gain (18-00). The factory default for 18-00 is 0.0 (When 18-00 = 0.0, the slip compensation function is disabled). ‧ Adjustment procedure for low-speed slip compensation gain (18-00): ① Properly set the rated slip and no-load current (02-00). ② Set the low-speed slip compensation gain (18-00). ③ When operating the motor under load, measure speed, and adjust the slow-speed slip compensation gain (18-00) by increasing in increments of 0.1. ─ If the motor speed is lower than the target speed, increase the low-speed slip compensation gain (18- 00). ─ If the motor speed is higher than the target speed, decrease the low-speed slip compensation gain (18- 00).

When the output current (12-18) exceeds the motor 1 no-load current (02-00), slip compensation activates, and the output frequency increases from f1 to f2. Refer to Figure 4.3.140. Slip compensation values follow the formula shown below:

Figure 4.3. 139 Output Frequency with Slip Compensation

Slip compensation value = Motor rated slip frequency × ([Output current(12-18) − Motor1 no-load current(02-00)] / [Motor1 rated current(02-01) − Motor1 no-load current(02-00)]). Source printed fraction grouped explicitly; not recalculated.

Motor rated slip frequency(f) = ((Motor no-load synchronous rotation speed)(N) × Number of motor poles(P)) /120. Source exact formula labels; no substituted engineering formula.

Load Torque;Smaller Load;f1;f2;Larger Load;Speed. Curves are qualitative; no digitized numerical values.

Literal printed parameter setting. Mode, operating-condition and warning qualifications in same source section retained. No inferred unit or engineering correction.

Parameter card — PDF page 326

Source row Parameter Name Scope/options and printed unit
1 18- 00 Low-speed slip compensation gain Range: [0.00~2.50]

Parameter card — PDF page 326

Source row Parameter Name Scope/options and printed unit
1 18- 01 High-speed slip compensation gain 【-1.00~1.00】

Parameter card — PDF page 326

Source row Parameter Name Scope/options and printed unit
1 18- 02 Slip compensation limit 【0~250】%

Parameter card — PDF page 326

Source row Parameter Name Scope/options and printed unit
1 18- 03 Slip compensation filter time 【0.0~10.0】Sec

Parameter card — PDF page 326

Source row Parameter Name Scope/options and printed unit
1 18- 04 Regenerative slip compensation selection [0]: Disabled [1]: Enabled

Parameter card — PDF page 326

Source row Parameter Name Scope/options and printed unit
1 18- 05 FOC delay time 【1~1000】mSec

Parameter card — PDF page 326

Source row Parameter Name Scope/options and printed unit
1 18- 06 FOC gain 【0.00~2.00】

Manual — Slip limits and SLV gain — page 327

Manual reference: physical PDF page 327. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(2) Slip Compensation Limit (18-02) ‧ Slip compensation limit 18-02 defines the torque and power limits, as shown in Figure 4.3.141. ‧ If 18-02 is set to 0%, the slip compensation function is disabled.

Figure 4.3. 140 Slip Compensation Limit

When adjusting the low-speed slip compensation gain 18-00, if the actual motor speed is still lower than the target speed, the motor may have reached the slip compensation limit. Ensure that the slip compensation limit (18-02) and reference frequency do not exceed the mechanical limitations of the equipment.

(3) Slip Compensation Filter Time (18-03). ‧ Filter time for slip compensation under V/F mode.

(4) Slip Compensation Selection during Regeneration (18-04) ‧ Select to enable or disable slip compensation during regenerative (deceleration) periods. ‧ In SLV mode, if speed accuracy is required during regeneration (deceleration), set 18-04 to 1 (enable). ‧ When slip compensation is enabled, regenerative energy may spike briefly (18-04 = 1), and a braking module (brake resistor) may be required.

SLV Mode Adjustment (1) Slip Compensation Gain ‧ For coupled loads, this gain can be used to maintain speed control accuracy across the full range. ‧ If speed drops below 2Hz and the motor slows down, increase 18-00. ‧ If speed drops below 2Hz and the motor speeds up, decrease 18-00. Since 18-00 is a fixed value across the full speed range, even if accuracy is adjusted at low speed, there may still be minor errors at high speed. If high-speed error is unacceptable, 18-01 (external compensation value) can be used, or continue fine-tuning 18-00—though this may compromise low-speed precision. The effect of 18-00 on torque-speed characteristics is illustrated in the figure below:

Figure 4.3. 141 Effect of 18-00 on Torque vs. Speed

(2) High-Speed Slip Compensation Gain (18-01) ‧ When the load is coupled, this parameter is used to control speed accuracy during medium to high-speed operation. In most cases, no adjustment is necessary. ‧ After adjusting 18-00, increase the reference frequency and observe any speed error. If speed error persists, increase the 18-01 setting to compensate.

Slip Compensation Limit;Slip compensation limit(18-02);upper reference (01-02/01-12)×18-02;Fbase(01-12);Fmax(01-02). Explicit fraction preserved; curve geometry remains in source.

Torque;Speed;Decrease18-00;Increase18-00. Qualitative lines and arrows only; no additional values inferred.

Manual — High-speed gain and FOC compensation — page 328

Manual reference: physical PDF page 328. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ To reduce speed error, increase the motor rated frequency (01-12 base frequency) and increase 18-01. ‧ If speed accuracy is degraded due to high motor temperature, it is recommended to adjust both 18-00 and 18-01 accordingly. ‧ Compared with 18-00, 18-01 differs in that it is a variable gain across the entire speed range. 18-01 defines the slip compensation at the motor rated speed. The formula is as follows:

Figure 4.3. 142 18-00 / 18-01 Slip Compensation Gain vs. Frequency Reference

Figure 4.3. 143 Effect of 18-01 on Torque-Speed Curve

(3) FOC (Flux-Oriented Control) Delay Time (18-05) ‧ In SLV mode, magnetic flux slip compensation depends on torque current and excitation current. ‧ When the motor is subjected to over 100% load at rated frequency, the voltage drop across the inductance and resistance may cause inverter output saturation and result in current oscillation. Flux slip compensation decouples torque current from excitation current, thereby resolving current oscillation issues. ‧ Parameter 18-05 defines the delay time for flux slip compensation. ‧ Increase 18-05 for slow or steady-state operation; adjust 18-06 for fast operation.

(4) Slip Compensation Gain Adjustment (18-06) ‧ If the motor vibrates at rated frequency and full load, gradually reduce the 18-06 setting value to zero until the vibration subsides.

Slip Compensation Gain = (Low-Speed Slip Compensation Gain + High-Speed Slip Compensation Gain) × [Reference Frequency / Motor Rated Frequency(01-12)]. Parentheses and fraction reflect the printed expression, not an independently approved control law.

Slip compensation;18-01;18-00;Frequency Reference. Explicit segment labels retained; graphical offset does not authorize rewriting printed formula.

Torque;Speed;Decrease18-01;Increase18-01;Decrease18-01;Increase18-01. Qualitative curves retained in source.

Manual — SLV2 gain and wobble settings — page 329

Manual reference: physical PDF page 329. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

SLV2 Mode Adjustment The factory default for 18-00 is 0.0 (When 18-00 = 0.0, the slip compensation function is disabled). ‧ Adjustment procedure for Slip Compensation Gain (18-00) is indicated below: ① Properly set the rated slip and no-load current (02-00). ② Set the Slip Compensation Gain (18-00) ③ When operating the motor under load, measure speed, and adjust the slip compensation gain (18-00) by increasing in increments of 0.1. ─ If the motor speed is lower than the target speed, increase the low-speed slip compensation gain (18-00). ─ If the motor speed is higher than the target speed, decrease the low-speed slip compensation gain (18-00).

19 – Wobble Function Group

‧ Wobble operation is only available in V/F and V/F+PG control modes. To compensate for rapid frequency changes in systems with inertia, frequency jumps can be incorporated.* (V/F+PG, SV, PMSV are only for special projects). ‧ Refer to Figure 4.3.145 for wobble operation and related parameter settings.

Figure 4.3. 144 Wobble Operation and Parameter Settings

‧ During wobble operation, the wobble run command input source for the inverter is a multi-function digital input (set 03-00 to 03-07 to 37: Wobble Run). Before the inverter output frequency reaches the wobble center frequency (19-00), the acceleration time will follow the default Acceleration Time 1 (00-14). When the wobble function is turned off or the run command is removed, the deceleration time will follow the default Deceleration Time 1 (00-15). However, during wobble operation, the acceleration and deceleration times are affected by the wobble period (19-04, tup + tdown) and wobble ratio (19-05, tup / tdown).

‧ Wobble activity can be monitored using relay output (R1A-R1C, DO1) set to 28: Wobble Upward Offset Status and 29: Wobble Active (set via 03-11 and 03-12). ‧ Refer to Figure 4.3.146 for wobble ON/OFF control.

Output frequency;Center Frequency19-00;Jump time19-03;Jump frequency19-02;amplitude labels19-01;offset labels19-06and19-07;t;Wobble time19-04;tup;tdown;Wobble Ratio = tup/tdown. Only explicit labels and printed ratio; no waveform digitization.

Literal printed parameter setting. Mode, operating-condition and warning qualifications in same source section retained. No inferred unit or engineering correction.

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 00 Frequency skipping center frequency 【5.00~100.00】%

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 04 Frequency skipping cycle 【0.0~1000.0】Sec

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 01 Frequency skipping amplitude 【0.1~20.0】%

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 05 Frequency skipping ratio 【0.1~10.0】mSec

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 02 Frequency skipping oscillation frequency 【0.0~50.0】%

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 06 Frequency skipping upper offset amplitude 【0.0~20.0】%

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 03 Frequency skipping oscillation time 【0~50】mSec

Parameter card — PDF page 329

Source row Parameter Name Scope/options and printed unit
1 19- 07 Frequency skipping lower offset amplitude 【0.0~20.0】%

Manual — Wobble offset and operating restrictions — page 330

Manual reference: physical PDF page 330. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 145 Wobble ON/OFF Control

‧ During wobble operation, the center frequency can be shifted upward or downward via multi-function digital input. The amplitudes for up/down offset are configured via 19-06 Wobble Upward Offset Amplitude and 19-07 Wobble Downward Offset Amplitude. However, the upward offset command (set 03-00 to 07 to 38: Wobble Upward Offset) and downward offset command (set 03-00 to 07 to 39: Wobble Downward Offset) must not be input simultaneously, or the inverter will maintain the previous center frequency (19-00). Refer to Figure 4.3.147 below.

Figure 4.3. 146 Up/Down Offset Operation

‧ During the acceleration and deceleration periods of wobble operation, the stall prevention function is disabled. Therefore, it is necessary to select an appropriate inverter capacity to meet the actual application needs. ‧ The frequency range of wobble operation spans from Motor 1 Minimum Output Frequency (01-08) to Motor 1 Maximum Output Frequency (01-02). If the Wobble Center Frequency (19-00) + Wobble Amplitude (19- 01) exceeds the Maximum Output Frequency (01-02), the maximum output frequency will be limited to 01- 02. If the Wobble Center Frequency (19-00) - Wobble Amplitude (19-01) is below the Minimum Output Frequency (01-08), the minimum output frequency will be limited to 01-08. ‧ All parameters within the Wobble Function Group (19-00 to 19-07) can be modified during wobble operation.

Run Command;t;Traverse Run(03-00–07=37);t;Traverse operation;Output frequency19-00;19-01;19-02;19-03;19-04;tup;tdown;taccel;tdecel;t;Traverse Up(03-11to03-12=28);t;During Traverse(03-11to03-12=29);t. Diagram timing remains in source; no measured durations inferred.

Output frequency19-00;19-01;19-06;19-07;t;Upper Deviation Command(03-00to03-07=38);t;Lower Deviation Command(03-00to03-07=39);t. Explicit labels only; simultaneous command behavior from prose.

Manual — Speed control parameter cards — page 331

Manual reference: physical PDF page 331. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

20 – Speed Control Function Group

Use of parameter 20-07 (P/PI selection during acceleration/deceleration) Parameter 20-33 (Constant Speed Detection Threshold) is primarily used when 20-07 is set to 0 and the frequency command source is analog input. Because analog signals can be affected by noise, the system may incorrectly judge that the motor has not reached constant speed, resulting in issues. Therefore, adjusting parameter 20-33 can help prevent such occurrences.

‧ The diagram below shows the speed control loop structure (ASR).* (V/F+PG, SV, PMSV are only for special projects)

(a) V/F + PG Control Mode: ‧ The speed control system (ASR) adjusts the output frequency so that the feedback speed follows the speed command (to reach zero error).

Literal printed parameter setting. Mode, operating-condition and warning qualifications in same source section retained. No inferred unit or engineering correction.

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 00 ASR gain 1 【0.00~250.00】

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 07 Acceleration/deceleration P/PI selection [0]: PI speed control is only effective during constant speed; only P control is used during acceleration and deceleration [1]: PI speed control is effective during both constant speed and acceleration/deceleration

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 01 ASR integral time 1 【0.001~10.000】Sec

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 04 ASR integral time limit 【0~300】%

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 02 ASR gain 2 【0.00~250.00】

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 05 ASR positive limit 【0.1 ~ 10】%

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 03 ASR integral time 2 【0.001~10.000】Sec

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 06 ASR negative limit 【0.1 ~ 10】%

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 08 ASR delay time 【0.000~0.500 】Sec

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 14 Speed feedback low filter constant 2 【1~1000】mSec

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 09 Speed observer gain 1 【0.00~2.55】

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 15 ASR gain change frequency 1 【0.0~599.0】Hz

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 10 Speed observer integral time 1 【0.01~10.00】Sec

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 16 ASR gain change frequency 2 【0.0~599.0】Hz

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 11 Speed observer gain 2 【0.00~2.55】

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 17 Low-speed torque compensation gain 【0.00~2.50】

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 12 Speed observer integral time 2 【0.01~10.00】Sec

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 18 High-speed torque compensation gain 【-10~10】%

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20- 13 Speed feedback low filter constant 1 【1~1000】mSec

Parameter card — PDF page 331

Source row Parameter Name Scope/options and printed unit
1 20-33 Constant speed detection threshold 【0.1~5.0】%

Manual — Speed control structures by mode — page 332

Manual reference: physical PDF page 332. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.147 Speed Control Structure (V/F + PG)

‧ When a multi-function digital input terminal (03-00 to 03-07) is set to 42 (Speed command without PG), the input can be used to enable or disable the ASR system.

(b) SLV Control Mode: ‧ The SLV control mode uses a speed estimator output as the feedback value. ‧ The speed control system (ASR) adjusts the output frequency so that the feedback speed follows the speed command (to reach zero error). ‧ The SLV mode includes a speed estimator used to estimate motor speed. To reduce noise interference, a low- pass filter and speed feedback compensator are added. ‧ The ASR integrator output can be cleared (03-00 to 03-07 = 43). The ASR controller output passes through a low-pass filter and limiter before generating the torque command.

Figure 4.3.148 Speed Control Structure (SLV Mode)

(c) SV and PMSV Control Modes: ‧ The speed control system (ASR) adjusts the output frequency so that the feedback speed follows the speed command (to reach zero error). ‧ The ASR integrator output can be cleared (03-00 to 03-07 = 43). The ASR controller output passes through a low-pass filter and limiter before generating the torque command.

Frequency Reference;Fref;SFS;Speed Feedback;P20-00/20-02;I20-01/20-03;ASR Limit20-05/20-06;PG valid;PG invalid(03-00to03-07=42);20-07=1(during accel/decel);20-07=0orSpeed control integral reset(03-00to03-07=43);Δf;Fout;Output Frequency. Plus/minus summing junctions remain graphical; not rewritten as an inferred wiring equation.

Frequency Reference;P20-00/20-02;I20-01/20-03;LP Filter20-35;P20-34;Primary delay time20-08;I Limit;Torque Limit;Torque Reference;20-07=1(during accel/decel);20-07=0;Speed Control Integral Reset03-00to03-07=43. Speed Observer Feedback;LP Filter20-13/20-14;Speed Feedback Compensator20-17/20-18;Speed Observer;Motor Voltage;Motor Current;Observer Error;P20-09/20-11;I20-10/20-12. Plus/minus feedback junctions remain graphical; no topology inferred.

Manual — ASR V/F PG adjustment and restrictions — page 333

Manual reference: physical PDF page 333. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.149 Speed Control Structure (SV and PMSV Modes)

(1) In V/F + PG mode, the proportional (P) gain and integral (I) time are set for both the minimum output frequency (parameters 20-02 and 20-03) and maximum output frequency (parameters 20-00 and 20-01). Refer to Figure 4.3.151.

Figure 4.3.150 ASR Gain Settings (V/F + PG)

(2) Adjusting the ASR Gain: Use the following steps to adjust the ASR Gain: a. Gain Adjustment for Minimum Output Frequency. ‧ Run the motor at the minimum output frequency (Fmin, 01-08). ‧ Increase the ASR proportional gain 2 (20-02) as much as possible without causing instability. ‧ Decrease the ASR integral time 2 (20-03) as much as possible without causing instability. ‧ Ensure that the output current is below 50% of the inverter rated current. If the output current exceeds 50% of the inverter rated current, reduce 20-02 and increase 20-03.

b. Gain Adjustment for Maximum Output Frequency. ‧ Run the motor at the maximum output frequency (Fmax, 01-02). ‧ Increase the ASR proportional gain 1 (20-00) as much as possible without causing instability. ‧ Decrease the ASR integral time 1 (20-02) as much as possible without causing instability.

c. Gain Adjustment for Acceleration/Deceleration PI Control (20-07). ‧ When 20-07 = 1, PI speed control is enabled during both constant speed and acceleration/deceleration, activating integral control. ‧ Integral control helps the motor reach the target speed more quickly but may cause overshoot or oscillation, as shown in Figures 4.3.154 and 4.3.155. ‧ If one of the multi-function digital inputs (03-00 to 03-07) is set to 43, it can be used to reset the

speed control integrator. When 20-07 is set to 1, both proportional (P) and integral (I) control of the ASR are active during acceleration/deceleration and steady-state operation. When set to 0, only P+I control is used during steady-state, while only P control is applied during acceleration/deceleration. – If speed overshoot occurs, decrease 20-00 (ASR Proportional Gain 1) and increase 20-01 (ASR Integral Time 1).

– If speed undershoot occurs, decrease 20-02 (ASR Proportional Gain 2) and increase 20-03 (ASR Integral Time 2). – If overshoot or undershoot cannot be resolved through gain tuning alone, adjust ASR Positive/Negative Limits (20-05 / 20-06) accordingly to increase or reduce the reference frequency

Frequency Reference;Speed Feedback;LP Filter20-35;P20-34;P20-00/20-02;I20-01/20-03;I Limit20-04;Primary delay time20-08;Torque Compensation from AI;Torque Limit21-05to21-08;Torque Reference;20-07=1(during accel/decel);20-07=0;Speed Control Integral reset03-00to03-07=43. Plus/minus summing junctions remain graphical; no inferred wiring topology.

P.I;P=20-00;I=20-01;P=20-02;I=20-03;0%;100%(Fmax,01-02);Output Frequency. Source prose separately describes minimum/maximum settings; line not digitized.

Manual — ASR limits and speed control tuning — page 334

Manual reference: physical PDF page 334. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

compensation (Δf) range for better speed response. Since parameters 20-05 and 20-06 cannot be modified during operation, the inverter must be stopped before adjusting the ASR positive/negative limits. ‧ Observe the motor speed waveform and adjust gains simultaneously as shown in Figure 4.3.152.

Figure 4.3.151 Analog Output Settings

d. ASR Positive/Negative Limits (20-05, 20-06) ‧ The ASR positive/negative limits define the frequency compensation boundaries for speed control. Set this frequency limit as a percentage of the maximum output frequency (01-02). ‧ If the frequency limit is set too low, the actual motor speed may fail to reach the target speed.

B. ASR Settings (SV / SLV / PMSV Control Modes) (1) SLV Mode:

‧ In SLV mode, the speed controller provides separate high-speed and low-speed gain settings— parameters 20-00/20-01 for high speed and 20-02/20-03 for low speed. The switching between high- speed and low-speed gains is defined by parameters 20-15 and 20-16. ‧ Similar to ASR gain settings, the speed estimator provides high-speed gains (20-09/20-10) and low- speed gains (20-11/20-12). The switching points for these gains are also set using parameters 20-15 and 20-16. ‧ The speed estimator includes a low-pass filter to reduce noise interference in the speed feedback. Parameters 20-13 and 20-14 define the low-pass filter time constants for high-speed and low-speed operation, respectively. The switching points for these gains are also set using parameters 20-15 and 20-16. ‧ Parameter 20-17 sets the low-speed compensation gain for speed feedback. ‧ Parameter 20-18 sets the high-speed compensation gain for speed feedback. ‧ When the reference frequency exceeds the value set in parameter 20-16, the high-speed ASR/estimator gains and low-pass filter time constants are fully applied. When the reference frequency is lower than the value set in parameter 20-15, the low-speed ASR/estimator gains and time constants are fully applied. When the speed command is between the values of 20-15 and 20- 16, the gains and time constants transition smoothly and linearly.

Figure 4.3.152 ASR Gain Settings in SLV Mode

(2) Gain settings in SV and PMSV modes ‧ In SV and PMSV modes, separate ASR gains are provided for high-speed (20-00/20-01) and low- speed (20-02/20-03) ranges. (3) Speed control gain adjustment ‧ During gain adjustment, multi-function analog output terminals (AO1 and AO2) can be used to monitor output frequency and motor speed (see Figure 4.3.153).

Related Parameters: AO1 group04-11=6(Motor Speed),04-12Gain,04-13Bias; AO2 group04-16=6(Motor Speed),04-17Gain,04-18Bias. Explicit connector and parameter labels only; wiring geometry stays in source.

P.I; low-frequency P=20-02/I=20-03; high-frequency P=20-00/I=20-01; thresholds20-15/20-16; Time Constant:20-14atlow-frequencyend,20-13athigh-frequencyend. Curves qualitative; no interpolated numerical values.

Manual — SV PMSV and SLV gain tuning — page 335

Manual reference: physical PDF page 335. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

➢ For full-speed-range ASR gain tuning in SV and PMSV modes (20-00 to 20-03): ‧ Adjust parameters during normal operation. ‧ Increase ASR proportional gain 1 (20-00) and gain 2 (20-02) as much as possible, but avoid system instability. ─ Parameters 20-00 and 20-02 affect the response of the speed control loop. ─ Adjusting the settings of 20-00 and 20-02 can improve system responsiveness but may also cause the entire system to become oscillatory. Please refer to the diagram below:

Figure 4.3.153 System Response of ASR Proportional Gain

‧ Reduce ASR integral time 1 (20-01) and ASR integral time 2 (20-02) with caution to avoid instability. ─ Longer integral times result in slower system response. ─ Excessively short integral times may cause system oscillation. Refer to the figure below. ‧ If system overshoot occurs while adjusting PI gain, over-voltage protection may be triggered. To prevent this issue, a braking unit (braking resistor) may be used.

Figure 4.3.154 ASR Integral Time Response

➢ SLV Mode Gain Adjustment (20-00 to 20-03, 20-09 to 20-18) and SLV2 Mode Gain Adjustment (20-15, 20-16) ‧ Adjust low-speed ASR PI gains 20-02 to 20-03 when the reference speed is lower than 20-15. The adjustment method for proportional gain (P) and integral time (I) is similar to 20-00 and 20-01 in SV mode. ‧ Adjust high-speed ASR PI gains 20-00 to 20-01 when the reference frequency is higher than 20-16. The adjustment method for proportional gain (P) and integral time (I) is similar to 20- 00 and 20-01 in SV mode. ‧ Generally, low-speed ASR gain can be set equal to the high-speed gain. If mechanical resonance causes oscillation, adjust either the low-speed or high-speed gain accordingly. ‧ If adjusting ASR PI gains 20-00 to 20-03 does not improve system response, reduce the low- pass filter time constants 20-13 to 20-14 to increase feedback bandwidth, then readjust the ASR gains. ‧ Adjust low-speed low-pass filter time constant 20-14 when the reference frequency is below 20-15. ‧ Adjust high-speed low-pass filter time constant 20-13 when the reference frequency is above 20-16. ‧ Increasing the low-pass filter time constant limits the speed feedback bandwidth and reduces overall system responsiveness. This approach reduces interference in the speed feedback signal but may hinder response to sudden load changes. It is suitable when load fluctuation is minimal and stable operation is desired. Low feedback bandwidth must be paired with low

Motor Speed;t;①20-00is too high, resulting in oscillations;②20-00is too low, resulting in slow response. Qualitative response only.

Motor Speed;t;①20-01is too short, resulting in oscillations;②20-01is too long, resulting in slow response. Qualitative response only.

Manual — Observer warnings thresholds and compensation — page 336

Manual reference: physical PDF page 336. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

ASR gain to ensure stable operation. ‧ Decreasing the low-pass filter time constant increases the speed feedback bandwidth and overall responsiveness. While this improves the system’s ability to react to rapid load changes, it also increases susceptibility to feedback noise. Use this method when rapid response is required and load fluctuations are frequent. High feedback bandwidth allows for higher ASR gain settings. ‧ If adjusting 20-00 to 20-03 and filter time constants 20-13 to 20-14 still does not yield a satisfactory response, the PI gain of the speed estimator (20-09 to 20-12) may need to be tuned. ‧ High estimator gain (larger P, shorter I) increases bandwidth but can lead to system instability due to noise. ‧ Low estimator gain (smaller P, longer I) reduces bandwidth but improves noise immunity and overall stability. ‧ Typically, default ASR settings are suitable for most applications. Adjusting low-pass filter constants and estimator gain is complex and risky; excessive tuning by the user is not recommended. If stable and high-speed response cannot be achieved in SLV mode, switch to SV mode.

‧ Parameter 20-15 defines the frequency threshold for switching to low-speed gain; 20-16 defines the high-speed gain threshold. ‧ When the reference speed is lower than 20-15, the inverter outputs a higher magnetizing current to improve low-speed control accuracy. When the frequency reference exceeds 20-16,

the inverter outputs the rated magnetizing current at no-load voltage (02-19). ‧ As a general guideline, 20-15 should be set at 5–50% of the motor base frequency. If set too high, the inverter output may saturate. 20-16 should be set at 4 Hz or above and higher than

20-08. ‧ If the motor operates stably under heavy load (above 100%) at mid-speed but oscillates at high speed, reduce the no-load voltage (02-19) or adjust FOC parameters (18-05 to 18-06).

‧ Parameters 20-17 and 20-18 compensate for speed feedback under low- and high-speed conditions, respectively. ‧ Parameter 20-17 is used to adjust no-load speed below 2 Hz. Adjusting 20-17 is similar to adding an offset to the torque-speed curve. When the no-load speed is below the frequency reference, increase 20-17. When the no-load speed is above the frequency reference, decrease 20-17. The effect of 20-17 on the torque-speed curve is illustrated below:

Figure 4.3.155 Effect of 20-17 on Torque-Speed Curve

Parameter 20-18 is used to adjust no-load speed in the mid- to high-speed range. Adjustment is typically unnecessary. Parameter 20-18 functions similarly to 20-17; its torque-speed curve is as follows:

Torque;Speed;Decrease20-17;Increase20-17. Qualitative curves only.

Torque;Speed;Decrease20-18;Increase20-18;Decrease20-18;Increase20-18. Qualitative curves; caption appears on physicalPDF337.

Manual — Feedback delay integral limit and bandwidth — page 337

Manual reference: physical PDF page 337. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.156 Effect of 20-18 on Torque-Speed Curve

➢ Main ASR Delay Time (20-08). ‧ Normally, adjustment is not required. ‧ A higher 20-08 setting reduces the speed response but improves system stability and reduces the likelihood of oscillation.

➢ ASR Integral Limit (20-04) ‧ Setting a smaller value helps prevent sudden load variations.

Note: Open-loop speed bandwidth specifications for vector control modes: 1. SV / PMSV control mode: 50 Hz 2. SLV / PMSLV control mode: 10 Hz Speed response may be affected by factors such as proportional gain (kp) tuning, system inertia, load, and motor temperature. Therefore, the practical bandwidth may be slightly reduced in real-world applications.

Manual — PG feedback and fault parameter cards — page 338

Manual reference: physical PDF page 338. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ PG interface card is required (JN7-PG-O / JN7-PG-L / JN7-PG-PM) *PG card is for special projects only ‧ The PG pulse division ratio can be configured via 20-29. ‧ PG Feedback Settings

(1) Overspeed Operation Settings (20-19 to 20-21) ‧ An error is detected when the motor speed exceeds the configured limit. ‧ An overspeed (OS) fault is triggered if the motor speed feedback exceeds the setting of 20-20 (Overspeed Detection Level) and persists longer than the time set in 20-21 (Overspeed Detection Delay Time). ‧ When an overspeed (OS) is detected, the inverter stops operation according to the setting in 20-19. ‧ Refer to the block diagram in Figure 4.3.158 for PG feedback fault detection.

(2) PG Speed Deviation Settings (20-22 to 20-24) ‧ An error is detected when the speed deviation (i.e., the difference between the command speed and the actual motor speed) exceeds the configured limit. ‧ Speed deviation (DEV) fault detection is triggered when the output frequency is outside the reference frequency ± the deviation detection tolerance (20-22), and the deviation exceeds the setting in 20-23 (Deviation Detection Level) or lasts longer than the time set in 20-24 (Deviation Detection Delay Time). ‧ Upon detecting a speed deviation, the inverter will stop according to the setting in 20-22. ‧ Refer to the block diagram in Figure 4.3.158 for PG feedback fault detection.

(3) PG Detection Settings (20-25 to 20-26). ‧ A PG (PGO) disconnection fault is detected if it lasts longer than the time specified by parameter 20- 26 (PG Open Circuit Detection Time). ‧ The inverter will stop according to the setting of parameter 20-25. ‧ Refer to the PG feedback fault detection block diagram in Figure 4.3.158.

Source-local exact options; PG special-project prerequisites and torque/ASR operating conditions remain attached. Unstated units not inferred.

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 19 Overspeed (OS) selection [0]: Decelerate to stop [1]: Free-run stop [2]: Continue operation

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 20 Overspeed (OS) detection threshold 【0~120】%

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 21 Overspeed (OS) detection time 【0.0~2.0】Sec

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 22 Speed deviation (DEV) selection [0]: Decelerate to stop [1]: Free-run stop [2]: Continue operation

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 23 Speed deviation (DEV) detection threshold 【0~50】%

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 24 Speed deviation (DEV) detection time 【0.0~10.0】Sec

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 25 PG disconnection selection [0]: Decelerate to stop [1]: Free-run stop [2]: Continue operation

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 26 PG disconnection detection time 【0.0~10.0】Sec

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 27 PG pulse count 【0~9999】PPR

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 28 PG rotation direction selection [0]: Forward is counterclockwise [1]: Forward is clockwise

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 29 PG pulse frequency division ratio 【001~132】

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 30 PG gear ratio 1 【1~1000】

Parameter card — PDF page 338

Source row Parameter Name Scope/options and printed unit
1 20- 31 PG gear ratio 2 【1~1000】

Manual — Feedback fault diagram and phase direction — page 339

Manual reference: physical PDF page 339. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 157 PG Feedback Fault Detection Block Diagram

(4) PG Pulse Setting (20-27). ‧ Sets the number of pulses from the PG or encoder. ‧ Parameter 20-27 specifies the number of A-phase or B-phase pulses per motor revolution. ‧ If a reduction gear is used between the motor and PG, configure the gear ratio using parameters 20-30 and 20-31.

(5) PG Rotation Direction (20-28) ‧ This parameter sets the PG rotation direction relative to the motor rotation direction. ‧ When the motor rotates forward, it defines which phase (A or B) leads. 20-28 = 0: A-phase leads during forward (B-phase leads during reverse). 20-28 = 1: B-phase leads during forward (A-phase leads during reverse).

Figure 4.3. 158 PG and Motor Rotation Direction Signals

Fout(after SFS);Speed feedback;ABSOLUTE;20-23;During momentary power loss;During B.B.;DEV Det Time20-24;DEV fault;(01-08)Fmin;0%SPEED;PGO Det Time20-26;PGO fault;20%SPEED;20-20;OS Det Time20-21;OS fault. Logic gate and junction geometry remains in source; not converted into inferred logic conditions.

Inverter;Forward Command;Motor;CCW Forward;20-28=0 phaseA/phaseB;20-28=1 phaseA/phaseB. Waveform timing remains qualitative; prose separately defines leading phases.

Manual — PG rotation divider and gear ratio — page 340

Manual reference: physical PDF page 340. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor direction is determined as follows: – Forward: When the motor shaft rotates counterclockwise in response to the inverter’s forward run command. Refer to Figure 4.3.160 below.

Figure 4.3. 159 Motor Rotation Direction

– Reverse: When the motor shaft rotates clockwise in response to the inverter’s run command. A typical PG signal is shown below in Figure 4.3.161.

Figure 4.3. 160 PG Rotation Direction

(6) PG Pulse Frequency Division Ratio (20-29) Use parameter 20-29 to set the pulse division ratio when the pulse output signal is connected to a pulse input device. ‧ The value of 20-29 is expressed by the first digit n (0 or 1) and the next two digits k (001 to 320). The output division ratio is calculated using the formula: – 20-29 = □ □□, valid ranges: n = 0 to 1 n k k :01 to 32 – Output ratio = (1 + n) / k e.g. 20-29=001 → n=0, k=1,Ratio = (1+0)/1=1 ①. 20-29=032 → n=0, k=32,Ratio = (1+0)/32=1/32 ②. 20-29=132 → n=1, k=32,Ratio = (1+1)/32=1/16

(7) PG and Motor Gear Ratio Settings (20-30, 20-31) ‧ In V/F+PG control mode, if a transmission mechanism exists between the motor and PG (Note: the speed response in V/F+PG mode is lower than in SV mode). ‧ Configure the gear ratio between the motor and PG as follows: – Set parameter 20-31 to define the gear ratio on the load side. – Set parameter 20-30 to define the gear ratio on the motor side. – The motor speed is calculated using the following formula:

Inverter;Forward Command;Motor;CCW Forward. Directional labels retained; wiring geometry not inferred.

PG;CW;Phase A;Phase B. Explicit labels and qualitative phase waveforms only.

Motor Speed(RPM) = [No. of input pulses from PG ×60 / PG pulses(20-27)] × [No. of PG gear teeth2(20-31) / No. of PG gear teeth1(20-30)]. Fractions and factors grouped from visible formula; no unstated sampling interval inferred.

Manual — Resolver and deceleration compensation — page 341

Manual reference: physical PDF page 341. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

If using a resolver, set this parameter to 1. Note: Resolver cards do not support position control mode.

Refer to Figures 4.3.149 and 4.3.150. The deceleration torque compensation function reduces ASR drop characteristics under sudden load conditions. Details are as follows: ‧ 20-34 Deceleration Compensation Gain: This gain functions similarly to the ASR proportional gain (20-00, 20-02). When used together with the low-pass filter time constant (20-35), it can help prevent oscillation. ‧ 20-35 Deceleration Compensation Time: This time constant is used to suppress oscillations caused by the deceleration compensation gain (20-34). However, if the time constant is set too high, the output response may become too slow, which is counterproductive to drop compensation. ‧ Recommended values for 20-34: 30 to 50, 20-35: 50 to 100 ms.

In handwheel mode, the speed calculated from the handwheel pulse input is multiplied by the speed ratio set in parameter (20-43), and then limited by the maximum speed command defined in parameter (20-44).

Source-local exact options; PG special-project prerequisites and torque/ASR operating conditions remain attached. Unstated units not inferred.

Parameter card — PDF page 341

Source row Parameter Name Scope/options and printed unit
1 20- 32 Special encoder selection [0]: None [1]: Resolver

Parameter card — PDF page 341

Source row Parameter Name Scope/options and printed unit
1 20- 34 Speed reduction compensation gain 【0 ~25600】

Parameter card — PDF page 341

Source row Parameter Name Scope/options and printed unit
1 20- 35 Speed reduction compensation time 【0~30000】mSec

Parameter card — PDF page 341

Source row Parameter Name Scope/options and printed unit
1 20- 43 Speed multiplier 【1 ~ 500】

Parameter card — PDF page 341

Source row Parameter Name Scope/options and printed unit
1 20- 44 Speed command limit 【0.1 ~ 30.0】Hz

Manual — Torque control parameter cards and structure — page 342

Manual reference: physical PDF page 342. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

21 – Torque Control Function Group

(1) Torque Control Selection (21-00) ‧ In SV or PMSV control mode, switching between speed and torque control is available: ‧ Use one of the multi-function digital input terminals 03-00 to 03-08 and set it to 44 (Speed/Torque Control Switch). ‧ When the terminal input is OFF, speed control is activated. When the terminal input is ON, torque control is activated. ‧ Use parameter 21-00 to select between speed control or torque control. 21-00 = 0: Speed control (parameters 20-00 to 20-08); ASR settings. Refer to Figure 4.3.149 Speed Control Block Diagram. = 1: Torque control (21-01 to 21-08); torque control settings. Refer to Figure 4.3.162 Torque Control Block Diagram.

Figure 4.3.161 Torque Control Block Diagram

Torque Reference(from AI2)Tref; Speed Limit AI1 selected by21-02=0; Speed Limit set by21-03 selected by21-02=1; Speed Limit communication address2502H selected by21-02=2; NLmt; Speed Controller & Speed Limiter; Speed Feedback NFB; Speed Limit Bias21-04; Torque Limit21-05to21-08; quadrantsI/II/III/IV on torque/rpm axes; Internal Torque Reference; Input Methods; Control Block. Junction geometry and torque quadrant behavior are not independently inferred.

Source-local exact options; PG special-project prerequisites and torque/ASR operating conditions remain attached. Unstated units not inferred.

Parameter card — PDF page 342

Source row Parameter Name Scope/options and printed unit
1 21- 00 Torque control selection [0]: Speed control [1]: Torque control

Parameter card — PDF page 342

Source row Parameter Name Scope/options and printed unit
1 21- 01 Torque reference filter time 【0~1000】mSec

Parameter card — PDF page 342

Source row Parameter Name Scope/options and printed unit
1 21- 02 Speed limit selection [0]: Based on AI input [1]: Based on parameter 21-03 [2]: Based on communication position input (2502H)

Parameter card — PDF page 342

Source row Parameter Name Scope/options and printed unit
1 21- 03 Speed limit value 【-120~120】%

Parameter card — PDF page 342

Source row Parameter Name Scope/options and printed unit
1 21- 04 Speed limit bias voltage 【0~120】%

Manual — Torque command inputs and speed limit direction — page 343

Manual reference: physical PDF page 343. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(2) Torque Settings (a) Torque Command (Tref) Input (AI2: 04-05) ‧ The torque command (Tref) cannot be set from the digital operator; it must be adjusted via multi- function analog input. ‧ Set 04-05 (AI2 Function Selection) to 15 (Torque Command) or 16 (Torque Compensation). – The motor torque output direction is determined by the polarity of the analog input signal (AI2), not by the direction of the run command. – When the analog input signal AI2 is a positive voltage (or current), a positive torque signal can be input (motor output shaft rotates counterclockwise). – To use negative torque, set one of the digital inputs 03-00 to 03-07 to parameter 45 (Negative Torque Command), and turn the corresponding digital input ON. (motor output shaft rotates clockwise)

Table 4.3.41 Torque Input Methods

(3) Torque Filter Time (21-01) ‧ The time constant is used to eliminate noise in the torque signal and to adjust response. ‧ If the system becomes unstable during control, increase this setting value.

(4) Speed Limit Input Settings (21-02 and 21-03): These parameters define a speed limit as a percentage of the maximum output frequency (01-02). ‧ During torque control, if the torque command exceeds the load, the motor may accelerate endlessly. The speed limit function prevents this, avoiding damage to the system or mechanical structure. ‧ There are two ways to set speed limits: through parameters or analog input. Refer to Table 4.3.42 Speed Limit Input Methods.

Table 4.3.42 Speed Limit Input Methods

─ The running direction in speed control depends on the speed limit signal: ‧ Positive torque: Forward, speed limit = (21-03) + (21-04). Reverse, speed is limited to zero or reverse direction (21-04). ‧ Negative torque: Reverse, speed limit = (–21-03) – (21-04). Forward, speed limit at Zero or in the Forward Direction (-21-04) ─ If the speed limit bias is set to 0, and the motor’s direction is opposite to the speed limit direction, the motor speed will be limited to 0. For example, if the speed limit signal is a positive voltage and the motor is operating in forward, the valid speed range for torque control is from 0 to the forward speed limit value.

Merged method/terminal scope and vertically aligned related-parameter/description sequences preserved together. Table4.3.41AI2 uses04-00 literals; Table4.3.42includescommunicationthirdmethod despiteprosesayingtwo. No invented mapping.

Table4.3.41 Torque Input Methods — PDF page 343

Source row Input method Input terminal Related parameter settings Description
1 Voltage Input (0–10 V) AI2 Select "V" 04-00=0,2 04-05=15 Terminal AI2 signal level: 0–10 V AI2 serves as torque input
2 Current Input (4 - 20mA) AI2 Select "I" 04-00=1,3 04-05=15 Terminal AI2 signal level: 4 - 20mA AI2 serves as torque input

Table4.3.42 Speed Limit Input Methods — PDF page 343

Source row Method number Input method Input terminal Related parameter settings Description
1 1 Voltage Input (-10V - 10V) AI1 21-02=0 00-05=1 04-00=2,3 Use analog input as speed limit Use analog input as reference frequency input Terminal AI1 signal level: -10V - 10V (If the speed limit is a positive value, set 04-00=0, 1)
2 2 Parameter 21-03 setting ─ 21-02=1 21-03 Set the speed limit controlled by parameter 21-03 Set the speed limit
3 3 Communication input (2502H) S+ and S- 21-02=2 Use communication as speed limit

Manual — Torque speed limit bias examples — page 344

Manual reference: physical PDF page 344. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(5) Speed Limit Bias Setting (Parameter 21-04):This parameter sets the speed limit bias as a percentage of the maximum output frequency (01-02). ‧The speed limit bias (21-04) is used to adjust the boundary of the speed limit. ‧The speed limit bias (21-04) can be set to define the bias values for both forward and reverse motor speeds.

Example 1 – Set 30% speed limit for both forward and reverse directions

Figure 4.3.162 Speed Limit Setting

Example 2 – Settings: 1. Speed Limit Value (21-03) = 100% (Forward Speed Limit) 2. Speed Limit Bias (21-04) = 20% ‧The torque control speed range is from -20% (21-04) to 120% (21-03 + 21-04)

Figure 4.3.163 Speed Limit Setting (Example 2)

Output torque(T);Torque reference(Tref);Motor speed(N);21-04;21-04;−100%;−30%;30%;100%;Effective range of torque control. Set speed limit value(21-03)=0, speed limit bias(21-04)=30%; speed range of Torque Control is from−30%to30%of maximum output frequency. Example only; no universal operating rating.

Output torque;Torque Limit;21-04;Torque reference(Tref);Motor speed;−100%;−20%;100%;120%;effective range of torque control;Speed limit(21-03)setting. When speed exceeds forward speed limit(120%), torque is increased in negative direction and limited by regenerative torque limit in4thquadrant. When speed exceeds reverse speed limit(−20%), torque is increased in positive direction and limited by regenerative torque limit in2ndquadrant. Source example labels/text; no extrapolated curve values.

Manual — Winding and unwinding examples — page 345

Manual reference: physical PDF page 345. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(6) Operation Examples of Torque Limit and Speed Limit ‧Torque and speed limit examples are applied in winding and unwinding operations. (a) Winding Operation ‧The line speed (N) and motor torque (T) are generated in the same direction by the motor. Refer to the below Figure 4.3.165

Figure 4.3.164 Winding Operation

①Speed Limit Bias (-21-04) < Motor Speed < Speed Limit (21-03 + 21-04) → Torque is controlled according to Tref. ②Motor Speed (N) > 21-03 + 21-04 → The speed limit will output negative torque to prevent speed increase. ③Motor Speed (N) < -21-04 → The speed limit will output positive torque to prevent further speed drop.

(b) Unwinding Operation ‧The line speed (N) and motor torque (T) are in opposite directions.

Figure 4.3.165 Unwinding Operation

Line direction;N;T;M;Output torque(T);Torque Limit21-08;Tref;21-04;21-04;Motor speed(N);Speed Limit Setting21-03;Torque Limit21-07;intervals③,①,②. Arrows and intervals remain schematic; explicit inequalities are retained in prose.

T;N;Line direction;M;output torque(T);Torque Limit(21-08);21-04;21-04;motor speed(N);Speed Limit Setting;Tref;Torque Limit(21-07). Qualitative structure only.

Manual — Winding signs and torque limit settings — page 346

Manual reference: physical PDF page 346. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

The relationship between Tref (Torque Reference), NLmt (Speed Limit), and N (Motor Speed) in winding and unwinding operations is as follows:

Figure 4.3.166 Winding and Unwinding Operation

‧When the torque limit function is used, torque control takes priority over motor speed control and compensation. As a result, acceleration and deceleration times may increase, and motor speed may decrease. There are two sources of torque limit in Speed Mode: (In SV control mode, and in torque mode, torque limit sources are only configurable via the digital operator.) 1. Torque limit values set via digital operator (21-05 to 21-08) 2. Torque limit values set via multifunction analog input (AI2).

(1) Setting Torque Limits Using Parameters (21-05 to 21-08) ‧There are four torque limit values that can be set individually: (I) Forward-Side Positive Torque Limit (21-05) (II) Reverse-Side Positive Torque Limit (21-08, Reverse Regenerative Torque Limit) (III) Reverse-Side Negative Torque Limit (21-06) (IV) Forward-Side Negative Torque Limit (21-07, Forward Regenerative Torque Limit) Refer to Figure 4.3.168.

‧Operation Winding Operation Unwinding Operation

T-N Curve

Structure

In each physical column(windingforward,windingreverse,unwindingforward,unwindingreverse):T,N,Tref,NLmt,21-08,21-07,and21-04biaslabels. Explicit signs and directions are separate table rows. Curve geometry not digitized.

Winding structure:Line direction,N,T. Unwinding structure:Line direction,N,T. Rotation arrows remain graphical; source prose defines relationship.

Physical signs and rotation columns preserved. Source diagram labels read separately; no mechanical topology inferred.

Source exact units and printed options; distinct physical columns preserved without interleaving.

Figure4.3.166 operation signs — PDF page 346

Source row Quantity Winding forward Winding reverse Unwinding forward Unwinding reverse
1 Rotation Direction Forward Reverse Forward Reverse
2 Tref (Torque Reference) + − − +
3 NLmt (Speed limit) + − + −

Parameter card — PDF page 346

Source row Parameter Name Scope/options column1
1 21- 05 Forward torque limit 【0~300】%

Parameter card — PDF page 346

Source row Parameter Name Scope/options column1
1 21- 07 Forward regenerative torque limit 【0~300】%

Parameter card — PDF page 346

Source row Parameter Name Scope/options column1
1 21- 06 Negative torque limit 【0~300】%

Parameter card — PDF page 346

Source row Parameter Name Scope/options column1
1 21- 08 Reverse regenerative torque limit 【0~300】%

Manual — Analog torque limits and position command settings — page 347

Manual reference: physical PDF page 347. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.167 Torque Limit Setting for Four Quadrants

(2) Setting Torque Limits Using Multifunction Analog Input AI2 ‧The multifunction analog input (AI2) can be configured for torque limit settings via the AI2 function setting (04-05). Refer to the below Table 4.3.43 for analog input settings for torque limit.

Table 4.3.43 Torque Limit Analog Input Settings

‧The analog input for torque limit can only be provided via AI2. The analog input signal type (04-00) can be set to 0, 2 (0–10V) or 1, 3 (4–20mA). A 10V or 20mA input corresponds to 100% of the rated motor torque limit.

When the torque limit source is set to multifunction analog input AI2, the actual torque limit value is the smaller of the values between the multifunction analog input AI2 and the parameter settings (21-05 to 21-05) via the digital operator.

─ When the analog input is at its maximum value (10V or 20mA), the torque limit is 100% of the rated motor torque. ‧To set the torque limit above 100%, increase the AI2 Gain (04-07) to above 100%. For example, when the AI2 Gain is set to 200.0% and the multifunction analog input AI2 is at maximum value (10V/20mA), the torque limit can be raised to 200%.

Note: When the torque limit source is set to multifunction analog input, the maximum torque limit value is 200%.

Output Torque(T);Motor Speed(N);Positive torque;Negative torque;Reverse direction;Forward direction;I:Forward rotation positive torque21-05;II:Reverse rotation positive torque21-08;III:Reverse rotation negative torque21-06;IV:Forward rotation negative torque21-07. Explicit quadrants and labels preserved.

Source saysAI2signaltype04-00; literal retained. Analog maximum200% restriction remains attached.

Source exact units and printed options; distinct physical columns preserved without interleaving.

Shared scope[-9999~9999] appears onPDF347 and continues348; rotation and pulse commands remain distinct.

Applies visually to21-10through21-41 group acrossPDF347–348. Units follow each command name, not inferred universally.

Table4.3.43 Torque limit analog input settings — PDF page 347

Source row AI2 function04-05 Function
1 11 Forward torque limit
2 12 Negative torque limit
3 13 Regenerative Torque Limit (for both forward and reverse)
4 14 Positive/Negative Torque Limit (detects both forward and reverse directions)

Parameter card — PDF page 347

Source row Parameter Name Scope/options column1
1 21- 09 Position control maximum frequency 【0.1~100】Hz

Segment position parameter names — PDF page 347

Source row Parameter Segment command
1 21- 10 Segment 0 rotation count command
2 21- 26 Segment 8 rotation count command
3 21- 11 Segment 0 pulse count command
4 21- 27 Segment 8 pulse count command
5 21- 12 Segment 1 rotation count command
6 21-28 Segment 9 rotation count command
7 21- 13 Segment 1 pulse count command
8 21- 29 Segment 9 pulse count command
9 21- 14 Segment 2 rotation count command
10 21- 30 Segment 10 rotation count command
11 21- 15 Segment 2 pulse count command
12 21- 31 Segment 10 pulse count command

Position shared scope — PDF page 347

Source row Scope
1 [-9999~9999]

Manual — Position control and digital input functions — page 348

Manual reference: physical PDF page 348. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Function Description: ‧ ‧Position Control Maximum Frequency (21-09): This is the speed frequency used for moving to the next position in multipoint positioning mode. ‧ ‧During the search for the next positioning point while the run command is active, the motor accelerates based on Acceleration Time 1 (00-14). ‧ ‧During the search for the next positioning point while a stop command is issued, the motor decelerates based on Deceleration Time 1 (00-15). ‧ ‧In SV or PMSV control modes, digital input terminals 03-00 to 03-07 can be used to select functions as defined in Table 4.3.44.

Figure 4.3.168 Zero-Servo Positioning Schematic

Table 4.3.44 Multipoint Positioning Function Settings

Output frequency;Fmin1(01-08);DI(Zero-Srvo);Run;t;t;t. Source spelling retained; timing and slopes not converted to numeric settings.

Source exact units and printed options; distinct physical columns preserved without interleaving.

Shared scope[-9999~9999] appears onPDF347 and continues348; rotation and pulse commands remain distinct.

SV/PMSV instruction and zero-servo schematic separate; preserve printedZero-Srvo.

Parameter card — PDF page 348

Source row Parameter Name Scope/options column1
1 21- 42 Position mode selection [0] Enter position mode when speed falls below the minimum frequency [1] Z-Phase Lock Function

Parameter card — PDF page 348

Source row Parameter Name Scope/options column1
1 21- 43 Offset angle 【0~9999】Pulse

Segment position parameter names — PDF page 348

Source row Parameter Segment command
1 21- 16 Segment 3 rotation count command
2 21- 32 Segment 11 rotation count command
3 21- 17 Segment 3 pulse count command
4 21- 33 Segment 11 pulse count command
5 21- 18 Segment 4 rotation count command
6 21- 34 Segment 12 rotation count command
7 21- 19 Segment 4 pulse count command
8 21- 35 Segment 12 pulse count command
9 21- 20 Segment 5 rotation count command
10 21- 36 Segment 13 rotation count command
11 21- 21 Segment 5 pulse count command
12 21- 37 Segment 13 pulse count command
13 21- 22 Segment 6 rotation count command
14 21- 38 Segment 14 rotation count command
15 21- 23 Segment 6 pulse count command
16 21-39 Segment 14 pulse count command
17 21- 24 Segment 7 rotation count command
18 21- 40 Segment 15 rotation count command
19 21- 25 Segment 7 pulse count command
20 21- 41 Segment 15 pulse count command

Table4.3.44 Multipoint positioning function settings — PDF page 348

Source row 03-00to03-07 DI setting Function
1 02 Multi-Speed Command 1 / Multi- Point Position Command 1
2 03 Multi-Speed Command 2 / Multi- Point Position Command 2
3 04 Multi-Speed Command 3 / Multi- Point Position Command 3
4 05 Multi-Speed Command 4 / Multi- Point Position Command 4
5 46 Zero-Speed Servo (Zero-Srvo)
6 51 Multi-Speed & Multi-Point Position Switch (Multi Pos. Switch)
7 52 Position Command Enable (Multi Pos. Enable)

Manual — Multipoint and Z-phase home positioning — page 349

Manual reference: physical PDF page 349. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ Multi-Point Positioning Function (MultiPosRef) Description: When parameter (21-42) is set to Option 0, the system enters position mode when the speed falls below the minimum frequency. In Zero-Servo positioning mode, if the multi-speed and multi-point position switch command is input (DI set to 51), Multi-Speed Commands 1 to 4 are converted into Multi-Point Position Commands 1 to 4. Including the home position of the Zero-Servo positioning mode, a total of 17 position points are available. Refer to Figure 4.3.170.

‧ Spindle Positioning Function (Z-Phase Lock Function) When parameter (21-42) is set to Option 1, the motor enters position mode upon detecting a Z-phase signal while rotating below the minimum frequency. The home position is determined by Z-phase signal + the value set in parameter (21-43). This can also be used in combination with the Multi-Point Positioning Function. Monitoring parameter 12-78 (Z-Phase Deviation) displays the deviation between the Z-phase signal and

the current position. To use this function, rotate the motor one full turn in the direction of future operation. Once the Z-point is captured, parameter 12-78 will show the deviation between the captured Z position and the actual one. After confirming, input this 12-78 value into parameter 21-43 as the offset angle. The home position will then be located at Z-phase signal + (21-43) setting.

Note: If the motor has not passed the Z-point upon startup, 12-78 will display 9999.

Figure 4.3.169 Multi-Point Positioning Function Schematic

PosRef0~15;Zero-Servo;Multi Pos.Enable;Multi Pos.Switch;S4;S3;S2;S1;Run;time axes t. Qualitative waveforms only; no unstated timing or pulse values inferred.

Manual — Position command enable and absolute counts — page 350

Manual reference: physical PDF page 350. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When using the Multi-Point Positioning Function, the Position Command Enable (Multi Pos. Enable, DI set to 52) must be ON for the inverter to accept external position commands. Refer to Figure 4.3.171.

Figure 4.3.170 Position Command Enable Schematic

The Multi-Point Positioning Mode is absolute. For example, if Position 1 is set to 100 pulses and the goal is to move another 100 pulses, then Position 2 must be set to 200 pulses. Refer to Figure 4.3.172.

Figure 4.3.171 Absolute Mode Diagram

Position Setting Description (21-10 to 21-41): Motor position for step N = Step N number of revolutions × PG pulse count (20-27) + Step N pulse count

Example: Motor encoder resolution: 2500 PPR To rotate the motor forward by half a revolution, set the number of revolutions to 0, and the pulse count to 1250.

Motor position = Number of revolutions × PG pulse count (20-27) + Pulse count = 0 × 2500 + 1250 = 1250

To rotate the motor in reverse by 1 and ¾ revolutions, set the number of revolutions to -1 and the pulse count to -1875.

Motor positioning position = Number of revolutions command × PG pulse count (20-27) + pulse count command = -1 × 2500 -1875 = -4375

Note: Motor rotation direction is based on PG rotation direction selection (20-28)

External Position Command:Position0,Position1,Position2,Position3,Position4,Position5;Position command enable;Inverter Position Command:first visible labelPosi-,thenPosition1,Position1,Position3,Position3,Position3;time axes t. First output label clipped in source; not completed by inference. DI52prose gives acceptance condition.

Position(pulse);100;200;increment arrows100and100. Qualitative example explicitly described by source; no arbitrary timing inferred.

Pulse count command = ½revolution × PG pulse count(20-27) = (1/2)×2500 =1250. Printed fraction grouped; example only.

Pulse count command = ¾revolution × PG pulse count(20-27) = (−3/4)×2500 =−1875. Source leading¾term lacks negative sign while fraction is−3/4; literal retained, not harmonized.

Adjacent source context — repeated to preserve continuation:

Manual — PM motor ratings and encoder settings — page 351

Manual reference: physical PDF page 351. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

22-PM Motor Parameter Group

The PM motor parameters are configured as follows. This parameter group can be reset to default values by setting parameter (13-08). Before initialization, please ensure that the motor model type is correctly set in parameter (13-00).

(01) PM Motor Rated Power (22-00), PM Motor Rated Voltage (22-01), and PM Motor Rated Current (22- 02) Set according to the motor nameplate.

(02) PM Motor Pole Count (22-03), PM Motor Rated Speed (22-04), and PM Motor Rated Frequency (22- 06) Set according to the motor nameplate. Either the rated speed (22-04) or rated frequency (22-06) needs to be set; the program will automatically calculate the other. When setting the rated speed (22-04), the PM Motor Maximum Speed (22-05) will be updated to the same value by default. If the field weakening function is used, the maximum speed (22-05) must be manually modified. The formula is as follows:

(03) PM Motor Maximum Rotation Speed (22-05) If the field weakening function is required, the PM Motor Maximum Speed (22-05) must be set to a value higher than the PM Motor Rated Speed (22-04).

(04) PM Type (22-07) When using an SPM motor, it is recommended to set this parameter to 0. Related adjustable parameters include Speed Estimation Gain (22-30) and Speed Estimation Filter Value (22-31). When using an IPM motor, it is recommended to set this parameter to 1. Related adjustable parameters include Speed Estimation Gain (22-34) and Speed Estimation Filter Value (22-35).

(PM motor rated rotation speed) N = [120×f(PM motor rated frequency)] / [P(Number of poles of the PM motor)]. Fraction grouped from source; not independently approved control equation.

Source exact units and printed options; distinct physical columns preserved without interleaving.

Adjacent source context — repeated to preserve continuation:

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 00 PM motor rated power [0.00~600.00] kW

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 04 PM motor rated rotation speed 【6~60000】rpm

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22-01 PM motor rated voltage 200V[50 ~ 240]V 400V[100 ~ 480]V

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 05 PM motor maximum rotation speed 【6~60000】rpm

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 02 PM motor rated current 25%~200% of the inverter’s rated current

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 06 PM motor rated frequency 【4.8~599.0】Hz

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 03 PM motor number of poles 【2~96】Poles

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 07 PM Type 【0】SPM 【1】IPM

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1 Scope/options column2
1 22- 08 PM Encoder Type [0]: Tamagawa – Non-reduced wiring [1]: Tamagawa – Reduced wiring [2]: SUMTAK – Reduced wiring [3]: General differential incremental type [4]: Sinusoidal type

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 10 PM SLV starting current 【20 ~ 200】%

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 11 I/f Mode Starting Frequency Switch Point 【10 ~ 100】%

Parameter card — PDF page 351

Source row Parameter Name Scope/options column1
1 22- 14 PM Stator Resistance 【0.001 ~ 30.000】Ω

Manual — PM motor tuning and estimator parameter options — page 352

Manual reference: physical PDF page 352. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source exact units and printed options; distinct physical columns preserved without interleaving.

22-36option1continuesphysical353. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22- 15 PM D-axis Inductance 【0.01 ~ 300.00】mH

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22- 16 PM Q-axis Inductance 【0.01 ~ 300.00】mH

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22- 17 PM No-Load Voltage 200V: 【0 ~ 250】V 400V: 【0 ~ 500】V

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-18 Field Weakening Current Limit [ 0 ~ 120 ]%

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22- 20 Pole shift angle 0–360 degrees

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1 Scope/options column2
1 22- 21 PM Motor Tuning [0]: Do not perform PM motor tuning [1]: Auto parameter tuning (for PMSLV) [2]: Pole alignment and loop tuning (for PMSV) [3]: Rotational auto-tuning

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1 Scope/options column2
1 22- 22 PM motor tuning failure history [0]: No error [1]:Stationary pole alignment failed [2]: No PG option card [3]:Rotational pole alignment forcibly stopped [4]:Encoder feedback direction error [5]:Loop tuning timeout [6]: Encoder error [7]:Other motor tuning error [8]:Current abnormal during rotational pole alignment [9]:Current abnormal during loop adjustment [11]: Stator resistance measurement timeout

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1 Scope/options column2 Scope/options column3 Scope/options column4
1 22-25 Initial pole detection method selection [0]: Use the angle before stopping 【1】 : Method 1 【2】 : Method 2 【3】 : Method 3

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1 Scope/options column2 Scope/options column3
1 22-26 High-Speed Control Ratio Enable (applicable to PMSLV) [0]: Low-speed open- loop control [1]: Low-speed high- frequency estimation control [2]: Full closed-loop control

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-27 Method 2 voltage command [5 ~ 120]% (Valid when 22-25 = 2 or 22-26 = 1)

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-28 Method 2 frequency division ratio [0 ~ 8] (Valid when 22-25 = 2 or 22-26 = 1)

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-29 Weak magnetic voltage command limit [80 ~ 110]% (Related to 22-18)

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-30 SPM Speed Estimation Gain 【1 ~ 150】%

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-31 SPM Speed Estimation Filter Value 【1 ~ 2000】Hz

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1 Scope/options column2 Scope/options column3 Scope/options column4
1 22-32 MTPA selection [0]: Disabled [1]: Method 1 [2]: Method 2 [3]: Method 3

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-33 MTPA gain 【0 ~ 400】%

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-34 IPM estimator gain 【1 ~ 180】%

Parameter card — PDF page 352

Source row Parameter Name Scope/options column1
1 22-36 PM motor type selection [0] General PM motor

Manual — PM encoder setup and tuning warnings — page 353

Manual reference: physical PDF page 353. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

[1] DVEN motor

(05) PM Encoder Type (22-08) 1. After changing the PM encoder type (22-08), the inverter must be powered off and on again for the system to update. 2. If using an incremental encoder type other than options 0–2, please select option 3 to avoid malfunction. When option 3 is selected, the motor will start with a strong magnetic field. The startup current will be approximately 100% of the rated current (22-02), and pole search will be performed according to parameter (22-25) or the motor will start from the last stop angle. If parameter (22-25) is set to 0, then on the first startup after power cycling, the inverter will start the motor from 0 degrees due to no stored previous stop angle, which may result in vibration. 3. The following encoders are compatible with the sinusoidal card: ERN1387, ECN1313, and ECN413.

Note: The sinusoidal card does not support position control mode. Note: If the PG card is incompatible with the PM encoder type, SE07 fault will be displayed.

Note: After reconfiguring the PM encoder type (22-08), the inverter must be powered off and on again. Then, perform PM motor tuning (22-21) and re-detect the magnetic pole offset angle (22-20). If the above steps are not performed again, the SE08 fault message will be displayed.

(06) PMSLV Startup Current (22-10) Sets the torque current at startup, expressed as a percentage of the rated motor current.

(07) I/f Mode Startup Frequency Switching Point (22-11) Sets the transition frequency point at which the permanent magnet motor switches from open-loop to closed-loop in sensorless vector control mode. Recommended setting values: Above 5% for 400V models and above 10% for 200V models.

(08) PM Motor Armature Resistance (22-14) Sets the per-phase motor resistance in 0.001 Ω units (note: do not confuse with line-to-line resistance). This parameter is automatically set during motor auto-tuning (22-21).

(09) PM Motor d-axis Inductance (22-15) Sets the motor’s d-axis inductance in 0.001 mH units. This parameter is automatically set during motor auto-tuning (22-21).

(10) PM Motor q-axis Inductance (22-16) Sets the motor’s q-axis inductance in 0.001 mH units. This parameter is automatically set during motor auto-tuning (22-21).

(11) Field Weakening Current Limit (22-18) 1. When MTPA Selection (22-32) is set to 0, and PM Motor Maximum Speed (22-05) is greater than PM Motor Rated Speed (22-04), field weakening control is automatically enabled. This parameter sets the limit for the maximum field weakening capability and is expressed as a percentage of the rated motor current. 2. When MTPA Selection (22-32) is set to 2 or 3, increase the field weakening current limit if the output voltage is too high.

(12) Magnetic Pole Offset Angle (22-20) Stores the zero-point compensation angle after pole alignment is completed.

(13) PM Motor Tuning (22-21) Warning! PM motor tuning is performed under powered conditions. Touching the motor may result in electric shock. Do not touch the motor before the tuning process is completed.

Printedhorsepower title but optionsstatekW1800RPM; exactsource kept. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 353

Source row Parameter Name Scope/options column1 Scope/options column2
1 22-37 PM motor horse power 【1】0.75KW 1800RPM 【4】1.5KW 1800RPM 【7】2.2KW 1800RPM 【10】3.7KW 1800RPM 【13】5.5KW 1800RPM 【16】7.5KW 1800RPM 【19】11KW 1800RPM 【22】15KW 1800RPM 【25】18.5KW 1800RPM 【28】22KW 1800RPM

Manual — PM motor tuning procedure and safety warnings — page 354

Manual reference: physical PDF page 354. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Warning! PM motor tuning may cause sudden motor startup and result in personal injury. Before performing Step 2 (Pole Alignment and Loop Tuning) or Step 3 (Rotational Auto-Tuning), ensure that the area around the motor and load is safe. Warning! Do not perform Step 2 (Pole Alignment and Loop Tuning) or Step 3 (Rotational Auto-Tuning) when the motor is connected to a load or when the brake is engaged. Doing so may result in inverter malfunction. Performing pole alignment with a motor connected to a load may result in incorrect motor parameter calculations. Disconnect the motor from the load and ensure that the motor can rotate smoothly and freely.

  1. Before selecting PM Motor Tuning, enter the motor nameplate values for parameters 22-00 to 22- 06. If Motor Control Mode (00-00) is set to 4 (PMSV), select 2 (Pole Alignment and Loop Tuning). If 00-00 is set to 5 (PMSLV), select 1 (Auto Parameter Tuning) to perform appropriate motor tuning.

  2. When Motor Control Mode (00-00) is set to 4 (PMSV) and the motor pole count (22-03) is unknown, select 2 (Pole Alignment and Loop Tuning). If Encoder Type (22-08) is set to option 4 (sinusoidal) — such as ECN1313, ECN413, or ERN1387 — or if Special Encoder Selection (20-32) is set to 1 (Resolver) and the motor pole count (22-03) is known, you may first perform 1 (Auto Parameter Tuning) and then proceed with 3 (Pole Alignment) to reduce motor dynamic tuning time. Note 1: If Encoder Type (22-08) is set to any of the incremental encoder options from 0 to 3, and Option 3 (Pole Alignment) is used during tuning, the system will display PM Tune Error03. Note 2: If Option 2 (Pole Alignment and Loop Tuning) or Option 3 (Pole Alignment) is used during PM motor tuning and a PM Tune Error04 occurs, the PG Rotation Direction Selection (20-28) will automatically reverse. Please repeat the PM motor tuning using the same option. If the same error occurs again, rewire the feedback phase or motor phase, and then perform the tuning again.

  3. If any error occurs during the tuning process, follow the troubleshooting instructions to resolve the issue and then repeat tuning using the appropriate control mode.

  4. When PM Motor Tuning (22-21) is set to 1 (Auto Parameter Tuning) or 2 (Pole Alignment and Loop Tuning) and ENTER is pressed, the system will enter the PM Motor Tuning screen. The operator display will show the message “IPrdy”. Press RUN to start tuning. The operator display will then show “IPtun”. If the tuning completes successfully, the message “IPEnd” will appear. If tuning is interrupted by pressing the stop button, the message “IPbrd” (PM Motor Tuning Interrupted) will appear. Note: If the inverter has already completed motor tuning, it does not need to be repeated after powering on again.

(14) PM Motor Tuning Fault History (22-22) If PM motor tuning fails, the display will show “IPErr” (PM Motor Tuning Failed). For possible causes and troubleshooting, please refer to Chapter 5. Note: PM Motor Tuning Fault History (22-22) records the result of the most recent automatic motor tuning. If tuning was canceled or completed successfully, the display will indicate no error.

(15) Initial Magnetic Pole Detection Method Selection (22-25) Specifies how the rotor position is detected during motor startup. 0: Do not detect rotor position; start using the angle from the last stop. 1: Method 1 – Detect rotor position using a pulse signal input. 2: Method 2 – Detect rotor position using a continuous variable-frequency signal input. 3. Method 3 – Detect rotor position using a voltage pulse signal.

(16) High-Speed Control Ratio Enable (22-26) When using an SPM motor, it is recommended to set this parameter to 0. The inverter will use I/f mode for startup. Related adjustable parameters are 22-10 and 22-11. When using an IPM motor, if you need to operate in speed control mode with a 1:50 speed ratio, set this parameter to 1. Under estimator mode 1, the inverter will input a continuous variable-frequency signal to the motor. The adjustable parameters are 22-27 and 22-28. When set to 2, both IPM and SPM motors can be used. Related adjustable parameters are 22-42 to 22-45.

(17) Method 2 Voltage Command (22-27) When Parameter 22-25 is set to Method 2 or Parameter 22-26 is enabled, this parameter sets the voltage amplitude of the continuous variable-frequency signal. If the rotor vibrates at startup, increase this voltage setting appropriately to improve detection accuracy. Note: Setting the voltage too high may result in over-current errors.

Manual — PM estimator MTPA and closed-loop settings — page 355

Manual reference: physical PDF page 355. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(18) Method 2 Frequency Division Ratio (22-28) When Parameter 22-25 is set to Method 2 or Parameter 22-26 is enabled, the frequency of the continuous signal is dependent on Carrier Frequency Setting (11-01). If a higher carrier frequency is set, it is recommended to increase the frequency division ratio to reduce the continuous signal frequency, ensuring accurate angle detection.

(19) Field Weakening Voltage Command Limit (22-29) This parameter sets the output voltage limit (as a percentage of the inverter’s input voltage) to prevent output voltage saturation during field weakening control. If Field Weakening Current Limit (22-18) is set too low, the inverter may still output voltage beyond the voltage command limit.

(20) Speed Estimation Gain (22-30) and Speed Estimation Filter Value (22-31) When Estimator Mode (22-26) is set to 0, these parameters adjust the speed response. A higher gain improves response but may cause system vibration and instability. A lower gain increases speed error. Adjust according to the on-site equipment for optimal performance.

(21) MTPA Selection (22-32) 0: MTPA disabled 1: Distributes d-q axis current commands based on the torque command. 2: Distributes d-q axis current commands based on the torque command and limits the output voltage (12-19) to below the motor rated voltage (22-01). 3: Distributes d-q axis current commands based on the torque command and maintains the output voltage (12-19) approximately equal to the motor rated voltage (22-01).

(22) MTPA Gain (22-33) The default value is 200%. When the PM motor’s d-axis inductance (22-15) or q-axis inductance (22-16) is modified (e.g., after completing PM motor tuning or directly adjusting inductance values), the MTPA gain (22-33) is recalculated automatically.

(23) IPM Estimator Gain (22-34) When Estimator Mode (22-26) is set to 1, this gain represents a multiplier of the bandwidth. A larger value results in faster motor response, but if set too high, may cause vibration and instability. If the value is too small, speed deviation may increase. Please adjust this parameter according to actual on-site equipment conditions.

(24) PM Motor Type Selection (22-36), PM Motor Horsepower and Speed (23-37) (22-36) allows selection between General PM Motor and DVEN Motor. After selection, you may configure PM Motor Horsepower using parameter (23-37). Once the horsepower is selected, motor parameters can be loaded without auto-tuning. However, if you later switch to a general motor, auto- tuning will be required.

(25) Open-Loop/Closed-Loop Switching Bandwidth (%) (22-38)

Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 38 Open-loop to closed-loop switching point frequency width (%) 【1.0~40.0】%

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 42 Full Closed-Loop Control Gain Ka 【64~8192】

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 39 Pre-DC injection time 【0.00~20.0】s

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 43 Full Closed-Loop Control Gain Kb 【64~8192】

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 40 High-frequency angle detection time 【0.01~1.00】s

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 44 Full Closed-Loop Control Gain – Speed Low-Pass Filter 【1~256】

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 41 PM stopping method [ 0 ] Deceleration or stop below 22- 11 triggers direct braking [ 1 ] Deceleration or stop below 22- 11 switches back to open-loop mode

Parameter card — PDF page 355

Source row Parameter Name Scope/options column1
1 22- 45 PM magnetic flux 【0.01~10.00】Wb

Manual — PM closed-loop control and filter conditions — page 356

Manual reference: physical PDF page 356. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When parameter 22-26 = 0 (Open-Loop Control), and the speed exceeds the I/f Mode Startup Frequency Switching Point (22-11), the system transitions from open-loop to closed-loop control. This parameter defines the bandwidth weighting ratio used during switching. Proper adjustment can suppress current instability caused by varying load devices during the transition and improve control stability and protection.

(26) Pre-Injection DC Time (22-39) When the PM motor starts in PMSLV mode, the system first estimates the rotor angle before operation begins. If this parameter is set, a DC injection will be applied after angle estimation to pull the motor into the estimated position before starting, effectively enhancing startup stability.

(27) High-Frequency Angle Search Time (22-40) When parameter 22-25 is set to 2, high-frequency signals are used to estimate the PM motor angle during startup, which may generate high-frequency noise. To effectively suppress this noise, users can adjust the high-frequency angle search time using this parameter. By appropriately shortening the search duration while maintaining reliable angle detection, the generation of high-frequency sound can be reduced.

(28) PM Stop Mode (22-41) In PMSLV mode, when the speed drops below the value set in parameter 22-11, the system will apply different deceleration modes based on the setting of parameter 22-41. When 22-41 = 0, the system performs DC braking below 22-11 during deceleration or stop. When 22-41 = 1, the system performs open-loop stopping below 22-11. Users can select between these modes based on their application needs to achieve better operational control.

(29) Full Closed-Loop Control Parameters (22-42 to 22-44, 22-52 to 22-53, 22-55 to 22-56) Used in conjunction with 22-26 = 2 (Full Closed-Loop Control). Full closed-loop control is primarily applied in situations requiring control under low speed ratios, enabling full-domain PMSLV closed-loop operation. It is suitable for various applications that demand low-speed performance. By adjusting the estimator gain parameters 22-42 to 22-44, stable low-speed ratio control can be achieved in PMSLV mode. Among these, 22-42, 22-43, and 22-52 correspond to the low-speed gain constant Ka, high-speed gain constant Kb, and ultra-low-speed gain constant Kb, respectively, for full closed-loop control. 22-44 and 22-53 correspond to the full closed-loop high-speed and low-speed position filter constants, respectively. 22-55 and 22-56 correspond to the full closed-loop high-speed and low-speed filter constants, respectively.

(30) Magnetic Flux of the PM Motor (22-45) This parameter sets the magnetic flux of the motor in units of 0.001 Wb. This parameter is automatically set during motor auto-tuning (22-21).

(31) 22-53: Position estimation filter value when 22-26 = 2.

(32) 22-54: This is the motor voltage calibration value used for position estimation. The factory default is typically sufficient and does not need adjustment.

(33) 22-55~22-56: When 22-26 is set to 2, these are the filter values for speed estimation. Parameter 22-55 is used when operating above 10% of the rated speed, while 22-56 is used when operating below 10% of the rated speed.

Manual — Pump HVAC function selection and pressure settings — page 357

Manual reference: physical PDF page 357. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

23 Pump/HVAC Function Parameter Group

For wiring methods of single/multi-pump setups, please refer to section 3.3 “Wiring and Precautions of Inverter Peripherals.”

(01) When parameter 23-00 is set to use either the pump or HVAC function, the selected function will affect the PID target value and enable relevant functions in Group 23. When 23-00 is set to 1 (pump selection) or 2 (HVAC selection), and 10-03 = 1 (PID enabled), this function will also be activated.

When 23-00 = 1, the LCD operator will automatically switch (16-00) the main screen monitoring to Working Pressure Setting (12-74), (16-01) Subscreen Monitor 1 to Pressure Feedback Value (12-75), and (16-02) Subscreen Monitor 2 to Output Frequency (12-17).

When 23-00 = 2, the LCD operator will automatically switch (16-00) the main screen monitoring to Flowmeter Target (12-77), (16-01) Subscreen Monitor 1 to Flowmeter Feedback Value (12-71), and (16- 02) Subscreen Monitor 2 to Output Frequency (12-17).

When 23-00 is set to 3 (compressor selection), PID mode is not supported. However, all other frequency command sources in 00-05 may be configured. Additionally, the V/F curve (01-00) will be limited to F, and the Mid-Output Voltage in 01-07 will be automatically set to half of the Maximum Output Voltage in 01-03. Parameter 01-00 will also be hidden.

Note 1: For LED operator display settings, please refer to parameter 23-05. Note 2: When switching operation modes via parameter 00-00, if the pump or compressor selection is not in V/F mode, parameter 23-00 will be reset to “Disabled.”

(02) Parameter 23-01 allows this inverter to be set as either the main or one of the auxiliary units (Auxiliary 1 to Auxiliary 3). Once configuration is complete, refer to Figure 4.3.181 “Dual Pump Start Function Flow” to operate multiple pumps. After completing the settings, power off the system to save the parameters.

(03) Parameter 23-02 sets the pressure value according to the pressure transmitter used in the pump system. However, parameter 10-00 must first be set to 0 (setpoint given by operator) for the feedback value to follow this setting.

(04) Parameter 23-03 sets the maximum pressure value based on the pressure transmitter used in the pump system. The value in 23-02 will be limited by this maximum.

(05) The command source for working pressure can be set via parameter 23-04, either from parameter 23-02 (Working Pressure Setting) or from the AI input. (If using the AI input, please refer to parameter 10-00.)

(06) Parameter 23-71 (Maximum Pressure Setting Value) defines the upper limit for the input value of parameter 23-02 (Working Pressure Setting). The maximum value of 23-71 is determined by parameter 23-03 (Maximum Pressure of the Pressure Transmitter).

Pump/HVACunderdevelopmentlabels, mode-specificranges andfootnotes retained; display units are not universal ratingunits. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 357

Source row Parameter Name Scope/options column1
1 23- 00 Function selection [0]: Disabled [1]: Pump selection [2]: HVAC selection (under development) [3]: Compressor selection *1 (under development)

Parameter card — PDF page 357

Source row Parameter Name Scope/options column1
1 23- 01 Single/multiple pump and primary/secondary unit setting [0]: Single pump [1]: Main [2]: Auxiliary 1 [3]: Auxiliary 2 [4]: Auxiliary 3

Parameter card — PDF page 357

Source row Parameter Name Scope/options column1
1 23- 02 Work pressure setting 【0.10 ~ 650.00】PSI

Parameter card — PDF page 357

Source row Parameter Name Scope/options column1
1 23- 03 Maximum pressure of pressure transmitter 【0.10 ~ 650.00】PSI

Parameter card — PDF page 357

Source row Parameter Name Scope/options column1
1 23- 04 Pump pressure command source [0]: Set via parameter 23-02 [1]: Set via AI

Parameter card — PDF page 357

Source row Parameter Name Scope/options column1
1 23-71 Pressure setting maximum value 【0.10 ~ 650.00】PSI

Manual — Pressure percentage conversion and LCD units — page 358

Manual reference: physical PDF page 358. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When parameter 23-20 (Pressure Percentage Switch) = 1, parameters 23-09, 23-24, 23-34, 23-38, and 23-39 are switched to percentage mode based on parameter 23-02, and parameters 23-12 and 23-15 are switched based on parameter 23-03. When 23-20 = 0, parameters 23-09, 23-24, 23-34, 23-38, 23-39, 23-12, and 23-15 are displayed and set using pressure units.

Example: 23-02 = 4.00 PSI, 23-03 = 10.00 PSI, 23-09 = 0.5 PSI, 23-12 = 5.00 PSI When 23-20 is changed from 0 to 1: ((23-09)/(23-02)) × 100 → 23-09 = 13% (rounded to the nearest whole number) ((23-15)/(23-03)) × 100 → 23-15 = 50% (rounded to the nearest whole number) When 23-20 is changed from 1 to 0: ((23-09)/100) 23-02 => 23-09 = 0.52PSI ((23-15)/100) 23-03 => 23-15 = 5.00PSI

When 23-00 = 1 and 23-20 = 0, the unit display will follow the unit set in parameter 23-36 (PUMP Unit Display). At this time, the display units for parameters 12-74, 12-75, 23-02, 23-03, 23-09, 23-12, 23-15, 23- 23, 23-24, 23-34, 23-38, and 23-39 are unified.

Pump/HVACunderdevelopmentlabels, mode-specificranges andfootnotes retained; display units are not universal ratingunits. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 358

Source row Parameter Name Scope/options column1
1 23- 20 Pressure percentage switching [0]: Pressure [1]: Percentage

Parameter card — PDF page 358

Source row Parameter Name Scope/options column1
1 23- 36 PUMP Unit Display (LCD use only) 【0】: PSI 【1】: FPM 【2】: CFM 【3】: PSI 【4】: GPH 【5】: GPM 【6】: IN 【7】: FT 【8】: /s 【9】: /m 【10】: /h 【11】: °F 【12】: inW 【13】: HP 【14】: m/s 【15】: MPM 【16】: CMM 【17】: W 【18】: KW 【19】: m 【20】: °C 【21】: RPM 【22】: Bar 【23】: Pa 【24】: KPa

Manual — Pressure display PID parameters and adjustment — page 359

Manual reference: physical PDF page 359. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Pressure-response graph labels Com-, Feed- and Steady- are visibly clipped; unseen suffixes remain unverified. No curve geometry inferred.

The display mode set in parameter 23-05 determines whether both the target pressure and feedback pressure are shown, or if only one of them is displayed. ① When 23-05 = 0000: The LED panel displays both the pressure setting and the feedback pressure.

The left two digits of the 7-segment display show the pressure setting, and the right two digits show the feedback pressure. When 23-00 = 2 (HVAC mode), values will be multiplied by 1000. For example, a display of 5.0 indicates 5000 GPM (available in version V1.4 and above). ②When 23-05 = 0001: The LED panel displays only the pressure setting.

③When 23-05 = 0002: The LED panel displays only the feedback pressure.

Note: 1. When used with the LED operator: In PUMP mode, parameter 23-03 must be ≤ 99.0 PSI. In PID mode, parameter 10-33 must be ≤ 999 and 10-34 must be set to 1.

Figure 4.3.172 Illustration of Pressure Feedback Value

Table 4.3.45 Parameter Adjustment Reference

Visible seven-segment example shows pressure setting2.0and feedback1.8. Source prose assigns lefttwo/righttwodigits; decimal markers retained, no product operating rating.

Target-only visible display shows2.0with leading zero and upper left marker. Mode23-05=0001; display example only.

Feedback-only visible display shows1.8with leading zero and lower left marker. Mode23-05=0002; display example only.

Visible annotations:Over-shoot(partially clipped);23-02:Com-;Pressure Feed-;Steady-;Stabilization. Source text boxes clip suffixes; no expansion to unprinted labels. Curve and settling interval qualitative only.

Pump/HVACunderdevelopmentlabels, mode-specificranges andfootnotes retained; display units are not universal ratingunits. Source exact units and printed options; distinct physical columns preserved without interleaving.

Table continues physical359→360; advantages and disadvantages retained separately per parameter. PID source guidance not independently approved.

Parameter card — PDF page 359

Source row Parameter Name Scope/options column1
1 23- 05 Display method selection [0]: Display target pressure and feedback pressure [1]: Display target pressure only [2]: Display feedback pressure only

Parameter card — PDF page 359

Source row Parameter Name Scope/options column1
1 23- 06 Proportional gain (P) 【0.00~10.00】

Parameter card — PDF page 359

Source row Parameter Name Scope/options column1
1 23- 07 Integral time (I) 【0.0~100.0】Sec

Parameter card — PDF page 359

Source row Parameter Name Scope/options column1
1 23- 08 Derivative time (D) 【0.00~10.00】Sec

Table4.3.45 Parameter Adjustment Reference — PDF page 359

Source row Parameter Increase effect Decrease effect Note
1 Proportional gain (P) (Advantage) Speeds up constant pressure control response (Disadvantage) Excessive value may cause water return vibration (Advantage) Reduces vibration (Disadvantage) Slower response Adjust stabilization time

Manual — PID adjustments and pressure sleep settings — page 360

Manual reference: physical PDF page 360. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: PID Output After Ad- graph annotation is visibly clipped; unseen suffix remains unverified.

Figure 4.3.173 Illustration of PID Parameter Adjustment

PID parameter adjustments can be made during operation. Parameter tuning should strike a balance between constant pressure control responsiveness and system stability.

: (When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz) 1: When 23-20 = 0, the displayed unit and range apply. *2: When 23-20 = 1, the displayed unit and range apply.

23-09 and 23-34 Constant Pressure Error Range: Within the constant pressure error range, the PID operation will gradually stop. When the pressure feedback value falls within the range of 23-02 (Operating Pressure Setting) ± 23-09 (Constant Pressure Error Range), the inverter frequency will slowly decrease, transitioning into sleep mode.

23-10 Constant Pressure Sleep Frequency: When the inverter’s output frequency drops below 23-10 (Constant Pressure Sleep Frequency), it will begin counting based on 23-11 (Constant Pressure Sleep Time).

PID Output After Ad-;PID Output Before. First label visibly clipped. Curves are qualitative comparisons; no measured error or response time inferred.

Pump/HVACunderdevelopmentlabels, mode-specificranges andfootnotes retained; display units are not universal ratingunits. Source exact units and printed options; distinct physical columns preserved without interleaving.

Table continues physical359→360; advantages and disadvantages retained separately per parameter. PID source guidance not independently approved.

Parameter card — PDF page 360

Source row Parameter Name Scope/options column1
1 23- 09 Constant pressure error range 【0.01 ~ 650.00】PSI *1 【1~100】% *2

Parameter card — PDF page 360

Source row Parameter Name Scope/options column1
1 23- 34 Constant pressure error range 2 【0.01 ~ 650.00】PSI *1 【1~100】% *2

Parameter card — PDF page 360

Source row Parameter Name Scope/options column1
1 23- 10 * Constant pressure sleep frequency 【0.00~599.00】Hz

Parameter card — PDF page 360

Source row Parameter Name Scope/options column1
1 23- 11 Constant pressure sleep time 【0.0~255.5】Sec

Table4.3.45 Parameter Adjustment Reference — PDF page 360

Source row Parameter Increase effect Decrease effect Note
1 Integral time (I) (Advantage) Reduces error value (Disadvantage) Degrades constant pressure control response (Advantage) Speeds up response (Disadvantage) Increases error Adjust steady-state error
2 Derivative time (D) (Advantage) Reduces speed overshoot (Disadvantage) Motor may be prone to vibration (Advantage) Reduces vibration (Disadvantage) Increases risk of overshoot Adjust overshoot amount

Manual — Pressure sleep operation and pressure limits — page 361

Manual reference: physical PDF page 361. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

23-11 Constant Pressure Sleep Time: After the 23-11 (Constant Pressure Sleep Time) countdown ends, the frequency will decrease based on 00-15 (Deceleration Time) and then enter sleep mode. 23-10 is the constant pressure sleep frequency used for PUMP mode and is not shared with the general PID setting 10-17 (Sleep Start Frequency).

Figure 4.3.174 Constant Pressure Sleep Diagram *The purpose of constant pressure sleep is to save energy.

1: When 23-20 = 0, the displayed unit and range apply. 2: When 23-20 = 1, the displayed unit and range apply.

23-12 Maximum Pressure Limit: For user convenience, a maximum pressure limit can be set as needed. If the pressure feedback exceeds this maximum, a warning will be issued and the system will shut down.

23-15 Minimum Pressure Limit: Similarly, a minimum pressure limit can be set. If the pressure feedback drops below this minimum, a warning will be issued and the system will shut down.

Bar;Hz;time;time;23-09Constant pressure error range;23-02Work pressure setting;Pressure Feedback Value;INV Output;23-11Constant pressure sleep time;23-10Constant pressure sleep frequency. Within the error range: |(23-02)−Pressure feedback| <23-09. Explicit formula and labels retained; no waveform time measurement.

Pump/HVACunderdevelopmentlabels, mode-specificranges andfootnotes retained; display units are not universal ratingunits. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 361

Source row Parameter Name Scope/options column1
1 23- 12 Maximum pressure limit 【0.00~ 650.00】PSI *1 【0~100】% *2

Parameter card — PDF page 361

Source row Parameter Name Scope/options column1
1 23- 15 Minimum pressure limit 【0.00~ 650.00】PSI *1 【0~100】% *2

Manual — High pressure warning and shutdown timing — page 362

Manual reference: physical PDF page 362. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.175 Pressure Feedback Limit Illustration

*Under PID control, the pressure will remain between the maximum pressure (23-12) and the minimum pressure (23-15).

23-13 High Pressure Warning Time: When the pressure feedback exceeds the maximum pressure limit, the high pressure warning time begins to count. If the feedback returns below the limit during this time, the counter resets. Once the countdown completes, warning HIPb will be triggered.

23-14 High Pressure Shutdown Time: If a high pressure warning is already triggered and the pressure feedback remains above the maximum pressure limit, the shutdown timer begins. If the pressure drops below the limit during this countdown, the timer resets. If the countdown completes, shutdown error OPbFt will be triggered. Note: If the user does not wish to apply the maximum pressure limit, set 23-74 = 0 (disabled) to deactivate the high pressure limit function.

Pb;time;23-12Maximum Pressure Limit;23-02Working Pressure Setting;23-15Minimum Pressure Limit;Pressure Feedback Value. Original trace not digitized; no numeric pressure inferred.

Pump/HVACunderdevelopmentlabels, mode-specificranges andfootnotes retained; display units are not universal ratingunits. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 362

Source row Parameter Name Scope/options column1
1 23- 13 High pressure warning time 【0.0 ~600.0】Sec

Parameter card — PDF page 362

Source row Parameter Name Scope/options column1
1 23- 14 High-pressure shutdown time 【0.0 ~ 600.0】Sec

Manual — High pressure action and low pressure timers — page 363

Manual reference: physical PDF page 363. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Pressure label boxes and T2 note visibly clipped; hidden native fragments are not accepted as visible text; T3 parameter assignment not inferred.

Figure 4.3.176 High Pressure Limit Warning and Shutdown Diagram

23-74 = 0: Both high pressure warning and fault are inactive. 23-74 = 1: Only high pressure warning is active; high pressure fault will not be triggered. 23-74 = 2: Both warning and fault are active, as illustrated in Figure 4.3.177.

23-16 Low Pressure Warning Time: When the pressure feedback drops below the minimum pressure limit, the low pressure warning time begins to count. If the feedback rises above the limit during this period, the timer resets. If the countdown completes, warning LoPb will be triggered.

23-17 Low Pressure Shutdown Time: If a low pressure warning is already triggered and the pressure feedback remains below the minimum pressure limit, the shutdown timer begins. If the feedback rises above the limit during this period, the timer resets. Once the countdown completes, shutdown error LPbFt will be triggered. Note: If the user does not wish to apply the minimum pressure limit, set 23-75 = 0 (disabled) to deactivate the low pressure limit function.

PSI;Hz;time;time;23-12:Maximum Pres-;23-02:Working Pres-;23-15:Minimum Pres-;Actual Feedback(partly clipped Pressure below);Free Deceleration Stop;T1;T2;T3;HIPb;OPbFt. Visible note:T1<(23-13High Pressure Warning Time);counter resets afterT1. T2=(23-13High Pressure Warning Time);panel... remainder visibly clipped. Native hidden text retained separately in raw_value, not treated as visibly verified. NoT3parameter mapping inferred from waveform.

Pump/HVACunderdevelopmentlabels, mode-specificranges andfootnotes retained; display units are not universal ratingunits. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 363

Source row Parameter Name Scope/options column1
1 23- 74 High-pressure action setting 【0】 Invalid 【1】 High-pressure warning only 【2】 High-pressure warning error all effective

Parameter card — PDF page 363

Source row Parameter Name Scope/options column1
1 23- 16 Low-pressure warning time 【0.0 ~ 600.0】Sec

Parameter card — PDF page 363

Source row Parameter Name Scope/options column1
1 23- 17 Low-pressure failure shutdown time 【0.0 ~ 600.0】Sec

Manual — Low pressure actions and water usage settings — page 364

Manual reference: physical PDF page 364. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.177 Low Pressure Limit Warning and Shutdown Diagram

23-75 = 0: Low pressure warning and fault are both disabled. 23-75 = 1: Only low pressure warning is enabled; fault will not be triggered. 23-75 = 2: Both low pressure warning and fault are enabled. Operation follows Figure 4.3.118.

(1) When 23-19 = 0 or 23-78 disables the pressure loss detection function.

(2) When 23-19 > 0, the inverter determines whether the feedback pressure is lower than the value calculated by (Transmitter Maximum Pressure (23-03) × Pressure Loss Ratio (23-19)). If this condition persists for a duration equal to the Pressure Loss Detection Time (23-18), a fault signal “FBLSS” will be triggered.

(3) 23-78 = 1: A pressure loss warning will be displayed when pressure loss is detected. (4) 23-78 = 2: A fault message will be triggered when pressure loss is detected.

PSI; Hz; time; Actual Feedback Pressure; 23-12: Maximum Pressure Limit; 23-02: Working Pressure Setting; 23-15: Minimum Pressure Limit; Free Deceleration Stop; T1; T2; T3; LoPb; LPbFt. T1 < (23-16 Low Pressure Warning Time); timer resets after T1. T2 = (23-16 Low Pressure Warning Time); panel flashes and displays LoPb. T3 = (23-17 Low Pressure Shutdown Time); panel displays LPbFt. Qualitative waveform only.

Source exact pump ranges; mode-dependent units and cross-page footnotes retained. 23-38 percent scope continues372. Source exact units and printed options; distinct physical columns preserved without interleaving.

Scope continues PDF365 top, 0.0–200.0Sec; physical page association preserved.

Parameter card — PDF page 364

Source row Parameter Name Scope/options column1
1 23- 75 Low-pressure action setting [0] Disabled [1] Warning Only [2] Both Warning and Fault Active

Parameter card — PDF page 364

Source row Parameter Name Scope/options column1
1 23- 18 Pressure loss detection time 【0.0 ~ 600.0】Sec

Parameter card — PDF page 364

Source row Parameter Name Scope/options column1
1 23- 19 Pressure loss detection ratio 【0 ~ 100.0】%

Parameter card — PDF page 364

Source row Parameter Name Scope/options column1
1 23- 78 Pressure loss detection action selection [0] Disabled [1] Warning on Pressure Loss [2] Fault on Pressure Loss

Parameter card — PDF page 364

Source row Parameter Name Scope/options column1
1 23-23 Water usage detection direction [0]: Upward Detection [1]: Downward Detection

Parameter card — PDF page 364

Source row Parameter Name Scope/options column1
1 23- 24 Water use inspection pressure range 【0.00 ~ 65.00】PSI *1 【0~10】% *2

23-25 heading continues365 — PDF page 364

Source row Parameter Name
1 23- 25 Water usage detection cycle

Manual — Upward water usage detection and shared acceleration — page 365

Manual reference: physical PDF page 365. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1: When 23-20 = 0, the displayed unit and range apply. 2: When 23-20 = 1, the displayed unit and range apply.

*Parameters 23-26 (Water Usage Detection Acceleration Time) and 23-27 (Water Usage Detection Deceleration Time) correspond to 00-16 (Acceleration Time 2) and 00-17 (Deceleration Time 2) respectively. These are shared parameters, so modifying 23-26 will also modify 00-16. Therefore, when using the PUMP function, it is recommended to avoid functions such as multi-speed operation.

Figure 4.3.178 Illustration of Upward Water Usage Detection Function

★When 23-25 = 0.0 (sec), the water usage detection function is disabled.

★Using the water usage detection function can effectively shorten the time for the inverter to enter sleep mode when there is no or minimal water usage.

★If water usage is frequent, it is recommended to increase the setting of 23-25 (Water Usage Detection Cycle) to reduce the number of detections. This helps avoid pressure fluctuations or instability during constant pressure operation caused by the detection process.

★Since upward water usage detection raises pressure slightly when active, if water continues to be used during this time, it may cause temporary pressure fluctuations or instability. It is recommended to reduce the value of 23-24 (Water Usage Detection Pressure Range) to mitigate this issue. However, doing so may also extend the time required for the inverter to enter sleep mode during low or no water usage.

23-23 = 0; Upward water test; Bar; Hz; time; 23-24 Water use inspection pressure range; 23-02 Work pressure setting; Pressure Feedback Value; Output frequency; 23-26 Water usage detection acceleration time; 23-25 Water usage detection cycle; 23-11 Constant pressure sleep time; 23-10 Sleep frequency; Continuously using water; Water not used. No curve geometry converted into ratings.

Source exact pump ranges; mode-dependent units and cross-page footnotes retained. 23-38 percent scope continues372. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter23-25 heading physically PDF364 bottom; scope physically365 top.

Parameter card — PDF page 365

Source row Parameter Name Scope/options column1
1 23- 26 Water usage detection acceleration time 【0.1 ~ 6000.0】Sec

Parameter card — PDF page 365

Source row Parameter Name Scope/options column1
1 23- 27 Water usage detection deceleration time 【0.1 ~ 6000.0】Sec

23-25 continued scope — PDF page 365

Source row Structural label Scope
1 Scope 【0.0 ~ 200.0】Sec

Manual — Downward water usage detection and sleep decisions — page 366

Manual reference: physical PDF page 366. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3.179 Illustration of Downward Water Usage Detection Function

★When 23-25 = 0.0 (sec), the water usage detection function is disabled.

★Using the water usage detection function can effectively shorten the time for the inverter to enter sleep mode when there is no or minimal water usage.

★If water usage is frequent, it is recommended to increase the setting of 23-25 (Water Usage Detection Cycle) to reduce the number of detections. This helps avoid pressure fluctuations or instability during constant pressure operation caused by the detection process.

★When the downward water usage detection function is activated, the output frequency will decrease based on parameter 23-27 [Water Usage Detection Deceleration Time]. If water usage continues during this process, the pressure will drop due to the reduced speed, and then the speed will immediately increase to recover the pressure—this determination is based on whether the feedback pressure falls below [Working Pressure Setting (23-02) – Water Usage Detection Pressure Range (23-24)]. During this process, temporary pressure fluctuations or instability may occur. It is recommended to properly adjust parameter 23-24 [Water Usage Detection Pressure Range] to avoid excessive pressure fluctuations. If there is minor water leakage during deceleration, causing pressure to drop, the system will determine whether to enter sleep mode based on whichever occurs first: reaching the sleep frequency or the feedback pressure falling below [23-02 – 23- 24]; if not, the system will accelerate again.

23-23 = 1; Downwards water test; Bar; Hz; time; 23-24 Water use inspection pressure range; 23-02 Work pressure setting; Pressure Feedback Value; Output frequency; 23-27 Water usage detection deceleration time; 23-25 Water usage detection cycle; 23-11 Constant pressure sleep time; 23-10 Sleep frequency; Continuously using water; Water not used. No curve geometry converted into ratings.

Manual — Detection tradeoffs forced operation and pump alternation — page 367

Manual reference: physical PDF page 367. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 4.3.46Reference of Pros and Cons for Water Usage Detection

*: (When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz)

The PID mode parameter 10-03 must be enabled for this function to be activated. When any of the DI terminals S1 to S6 is set to 16 (PID Function Disabled) and activated, the pump will no longer perform any PID output adjustment based on feedback and will operate according to the frequency source specified in parameter 00-05.

If another DI is set to 57 (Forced Frequency Operation) and activated, the inverter will operate at the frequency defined in parameter 23-28 (Forced Frequency Operation). Once the PID Function Disabled command is removed, control will return to PID operation. The Forced Frequency Operation function can be used when the pressure sensor is disconnected, allowing the inverter to be controlled by an external pressure sensor (e.g., a differential pressure switch).

23-29 Multi-pump parallel alternating time When multiple pumps are operated in parallel, alternation occurs in the sequence: Main → Auxiliary 1 → Auxiliary 2 → Auxiliary 3. This parameter is used to set the alternation interval

23-72 Parallel alternating time switching:

Source exact pump ranges; mode-dependent units and cross-page footnotes retained. 23-38 percent scope continues372. Source exact units and printed options; distinct physical columns preserved without interleaving.

Separate physical columns; supplier claims retain operating conditions and pump ordering.

Parameter card — PDF page 367

Source row Parameter Name Scope/options column1
1 23- 28 * Forced Operation Frequency 【0.00 ~ 599.00】Hz

Parameter card — PDF page 367

Source row Parameter Name Scope/options column1
1 23-29 Multi-pump parallel alternating time 【0 ~ 240】hour/min

Parameter card — PDF page 367

Source row Parameter Name Scope/options column1
1 23-72 Parallel alternating time switching [0]: Hours [1]: Minutes

Parameter card — PDF page 367

Source row Parameter Name Scope/options column1
1 23-35 Multi-unit parallel connection switching selection [0]: Do not perform function [1]: Timer alternation selection [2]: Sleep stop alternation selection [3]: Timer and sleep stop alternation selection [4]: Multi-unit parallel testing mode

Parameter card — PDF page 367

Source row Parameter Name Scope/options column1
1 23- 30 Multi-pump parallel auxiliary water pumping detection time [0.0 ~ 30.0] Sec

Parameter card — PDF page 367

Source row Parameter Name Scope/options column1
1 23- 31 Multi-pump parallel synchronization selection [0]: Disabled [1]: Pressure setting and Run/Stop synchronization [2]: Pressure setting synchronization [3]: Run/Stop synchronization

Table4.3.46 Water usage detection pros and cons — PDF page 367

Source row Direction Advantages Disadvantages
1 Water Usage Detection Direction: Upward 1. During the water usage detection process, pressure can always remain above the target pressure, making it suitable for more stringent and precise applications. 1. If the head is too high, the operating frequency may remain high under conditions of minimal or no water usage, making it harder for the upward water detection to enter sleep mode. 2. When multiple pumps are used in parallel, the energy-saving effect is insignificant, and auxiliary pumps are less likely to enter sleep mode.
2 Water Usage Detection Direction: Downward 1. Quickly enters sleep mode during minimal or no water usage. 2. When multiple pumps are used in parallel, the system effectively regulates the optimal online pump operation during downward water detection to achieve energy-saving goals. 3. Start-up sequence: Main → Auxiliary 1 → Auxiliary 2 → Auxiliary 3; water detection sleep sequence: Auxiliary 3 → Auxiliary 2 → Auxiliary 1 → Main. After the rotation interval, rotation among auxiliary pumps is performed to balance lifespan. If Water Usage Detection Pressure Range (23- 24) and Water Usage Detection Deceleration Time (23-27) are not properly adjusted, pressure fluctuations may occur during downward detection.

Manual — Pump synchronization priority and alternation conditions — page 368

Manual reference: physical PDF page 368. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

23-72 = 0: Parameters 23-29 and 24-08 use hours as the unit. 23-72 = 1: Parameters 23-29 and 24-08 use minutes as the unit.

23-35 Multi-unit parallel connection alternation selection: 1. Timer-Based Alternation: Alternation occurs based on the interval set in parameter 23-29. After the timer elapses, the roles of main and auxiliary pumps are switched.

  1. Alternation on Sleep Stop: When both the main and auxiliary pumps enter sleep mode in a multi-pump configuration, and the pump activation detection time (parameter [23-30]) is exceeded, an alternation will occur once. Each time multi-pump operation starts and this condition is met, alternation will take place. Please refer to the alternation-on-sleep-stop flowchart for detailed operation steps.

  2. Combined Timer and Sleep Stop Alternation: Alternation occurs by both timer and sleep stop conditions concurrently.

  3. Multi-Pump Parallel Test Mode: This setting is used when the main pump is stopped and the auxiliary pump must operate. It enables operation without alternation, intended for testing purposes.

23- 30 Multi-pump parallel auxiliary water pumping detection time: When 23-31 (Multi-Pump Synchronization Selection) is set to 1 or 3, this parameter becomes active. If the water pressure does not reach the target constant pressure deviation range and the detection time set in 23-30 is exceeded, the main pump will signal the auxiliary pump to start auxiliary pumping, initiating its operation.

23-31 Multi-pump parallel synchronization selection: 1. When 23-31 = 0: Disabled

  1. When 23-31 = 1: The pump designated as the main pump via 23-01 can modify the pressure setting and Run/Stop command. The auxiliary pump only follows the main pump’s commands; however, its own Run/Stop input can serve as an emergency stop with the highest priority.

  2. When 23-31 = 2: The main pump (set via 23-01) can modify the pressure setting, and the auxiliary pump will synchronize its setting accordingly.

  3. When 23-31 = 3: The main pump (set via 23-01) issues Run/Stop commands. The auxiliary pump follows these commands, but its own Run/Stop input can still serve as an emergency stop with the highest priority.

Note: When the main pump modifies the pressure setting, the ENTER key must be pressed for the change to apply to the auxiliary pump.

Note: If the alternating time setting in 23-29 is changed or power is restored, the timer will reset.

Manual — Dual pump startup sequence — page 369

Manual reference: physical PDF page 369. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Figure 4.3. 180 Dual-Pump Start Function Process Description:

A: Upon dual-pump startup, the main pump starts delivering water, while the auxiliary pump remains on standby, entering constant pressure operation.

B: As water consumption increases, the main pump’s frequency rises. If the pressure has not yet reached the constant pressure tolerance and the elapsed time is still within the 23-30 detection period, the auxiliary pump remains in standby.

C: If the 23-30 detection time is exceeded and the main pump reaches 60Hz, the main pump will command the auxiliary pump to assist. Once the auxiliary pump starts and the water usage stabilizes, both pumps reduce their frequency to maintain constant pressure.

D: When water consumption decreases, both pumps reduce their frequency. Since demand is lower than when both pumps were operating, the auxiliary pump stops and enters sleep mode (refer to 23-22 for auxiliary pump sleep conditions). The main pump alone maintains constant pressure operation.

Note 1: When 23-35 (Multi-unit Parallel Alternation Selection) is set to 3, and dual-pump operation exceeds the alternating time set in 23-29 or enters sleep-stop mode, the roles of main and auxiliary pumps will switch.

Bar; Hz; time; Host; Auxiliary pump; 23-09 Constant pressure error range; 23-02 Work pressure setting; 23-30 Detection time; Pressure Feedback Value; INV Output; INV output; 60 Hz; phases A, B, C, D. Example graph only; complete phase conditions retained in source prose.

Manual — Sleep stop alternation and pump role restrictions — page 370

Manual reference: physical PDF page 370. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note 2: When using dual-pump configuration (23-01 ≠ 0), both inverters must not simultaneously have 23- 01 set to 1 or both set to 2.

Sleep-Stop Alternation Function Process Description:

A: Dual-pump startup. If pressure becomes excessively high, the main pump continues water delivery while the auxiliary pump reduces its frequency output.

B: The main pump operates at full frequency. If pressure does not drop to the constant pressure target, the auxiliary pump continues to reduce speed until it reaches the dropout frequency specified in 23-22. At this point, the 23-30 detection timer starts, and the auxiliary pump decelerates to a full stop.

C: If water consumption decreases and pressure remains high, and the auxiliary pump is in sleep mode, the 23-30 timer ends and the main pump reduces output frequency to stabilize pressure within the target range.

D: When the main pump frequency falls to the constant pressure sleep frequency (23-10), it slows down and stops. With minimal water consumption, pressure gradually decreases.

E: Once water usage stops, the main pump enters sleep-stop mode, maintaining pressure. At this point, the 23-30 detection timer starts for the auxiliary pump.

F: When the 23-30 detection time completes, a stop-based alternation is triggered. The virtual main pump becomes the auxiliary pump. If pressure falls below the setpoint, constant pressure operation resumes.

Bar; Hz; time; Host; Auxiliary pump; 23-09 Constant pressure error range; 23-02 Work pressure setting; Pressure Feedback Value; INV Output; INV output; 60 Hz; 23-10 Constant pressure sleep frequency; 23-22 Auxiliary machine trip frequency; 23-30 Detection time; phases A, B, C, D, E, F. Diagram timing geometry not digitized.

Manual — Auxiliary startup conditions and leak detection settings — page 371

Manual reference: physical PDF page 371. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When operating in multi-pump parallel mode, if the feedback pressure remains within the tolerance range and the conditions for waking up the auxiliary pump are not met, set 23-73 = 1 to enable the following logic:

①When the main pump runs at full speed (reaches the maximum output frequency set in 01-02), but the feedback pressure still fails to reach the target value,

②after 30 seconds + the duration defined in 23-30, the system will forcibly start the auxiliary pump (even if the wake-up conditions and the feedback pressure being outside the tolerance range are not yet met), and both pumps will operate together until the pressure target is reached.

③However, to wake up the auxiliary pump, the conditions must still comply with the equation defined by Method 1, and the auxiliary pump start condition diagram must be referenced to properly configure the startup conditions.

When both the main and auxiliary pumps are operating, the conditions under which the auxiliary pump will stop assisting are as follows:

  1. When 23-22 = 0 Hz: The cut-out frequency condition is disabled. If the auxiliary pump’s output frequency drops below the sleep frequency (23-10) and remains so beyond the constant pressure sleep time (23-11), the auxiliary pump will stop automatically.

  2. When 23-22 = 1 to 400 Hz (with the maximum frequency determined by 01-02): The cut-out frequency condition is enabled.

If the auxiliary pump’s output frequency falls below the frequency set in 23-22, the main pump will command the auxiliary pump to stop and enter sleep mode. Alternatively, if the auxiliary pump’s output frequency drops below the sleep frequency (23-10) and remains so beyond the constant pressure sleep time (23-11), the auxiliary pump will also stop automatically.

F; T; 01-02 Maximum output frequency; 23-22 Auxiliary machine trip frequency; 00-14 Acceleration time 1. Explicit printed comparisons: (23-22)/(23-30) < (01-02)/(00-14); (23-22)/(23-30) = (01-02)/(00-14); NG: (23-22)/(23-30) > (01-02)/(00-14). Parameter identifiers remain identifiers, not arithmetic subtraction. Red note: When the value set for 23-22 (auxiliary pump trip frequency) is too big or that 23-30 (parallel auxiliary water pumping detection time) is too short, it will cause the auxiliary pump to go into sleep mode and cause the setting to become ineffective.

Auxiliary Pump Start Condition Diagram. Method Configuration 1: (23-22)/(23-30) ≤ (01-02)/(00-14). Identifiers denote source parameters. No numeric ratio computed and zero denominator behavior not inferred.

Source exact pump ranges; mode-dependent units and cross-page footnotes retained. 23-38 percent scope continues372. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter card — PDF page 371

Source row Parameter Name Scope/options column1
1 23-73 Secondary unit wakeup selection 【0】 Invalid 【1】 Valid

Parameter card — PDF page 371

Source row Parameter Name Scope/options column1
1 23- 22 Auxiliary machine trip frequency [0.00~599.00] Hz

Parameter card — PDF page 371

Source row Parameter Name Scope/options column1
1 23-37 Water leakage detection time [0.0~100.0] Sec

Parameter card — PDF page 371

Source row Parameter Name Scope/options column1
1 23-38 Leak Detection Restart Pressure Variation *3 【0.01~65.00】PSI *1

Manual — Leak detection pressure units and case1 — page 372

Manual reference: physical PDF page 372. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1: When 23-20 = 0, the displayed unit and range apply. 2: When 23-20 = 1, the displayed unit and range apply.

Pressure change for restarting water leak detection ∆P1 <23-38 ∆P2 > 23-38

✸This function is restricted for use in single-pump systems only. ✸When 23-37 = 0.0 (sec), this function is disabled. ✸If the pump is in sleep mode and pipeline leakage causes a gradual pressure drop, the inverter checks at each interval of 23-37. If the pressure drop exceeds the value set in 23-38 (Leak Detection Restart Pressure Variation), the pump will restart to supply water.

Water leak detection Case1: Pressure change greater than 23-38. Bar; Hz; time; ΔP1; ΔP2; 23-02 Work pressure setting; 23-37 Water leak detection unit time; Pressure Feedback Value; INV output; In sleep mode; Restart water leak detection. Qualitative curve; no measured pressure or duration inferred.

Source exact pump ranges; mode-dependent units and cross-page footnotes retained. 23-38 percent scope continues372. Source exact units and printed options; distinct physical columns preserved without interleaving.

Parameter23-38 physical371; percent scope372 applies23-20=1. PSI scope371 applies23-20=0.

Parameter card — PDF page 372

Source row Parameter Name Scope/options column1
1 23-39 Water leakage detection restart error range 【0.01~650.00】PSI *1 【1~100】% *2

23-38 continued percent scope — PDF page 372

Source row Scope
1 【1~10】% *2

Manual — Leak detection case2 and single pump restriction — page 373

Manual reference: physical PDF page 373. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Pressure change for restarting water leak detection ∆P1 < 23-38 ∆P2 < 23-38 ∆P3 < 23-38

✸When 23-37 = 0.0 (sec), this function is disabled.

✸If the pump is in sleep mode and pipeline leakage causes a gradual pressure drop, but during each 23-37 detection interval the pressure variation is less than 23-38, the inverter will remain in sleep mode. The pump will only restart if, within a given time, the pressure variation exceeds 23-38 or the pressure deviation exceeds the range set in 23-39 (Leak Detection Restart Error Range).

✸Appropriate adjustment of the leak detection parameters 23-37 / 23-38 / 23-39 can mitigate frequent pump start-stop cycles caused by pressure drops due to water leakage in the system.

✸The leak detection function is only effective in single-pump configurations.

Water leak detection Case2: Pressure change less than 23-38. Bar; Hz; time; ΔP1; ΔP2; ΔP3; 23-02 Work pressure setting; 23-37 Water leak detection unit time; 23-39 Pressure error range for restarting water leak detection; Pressure Feedback Value; INV output; In sleep mode; Restart water leak detection. Qualitative curve; no measured pressure or duration inferred.

Manual — Built in PLC basic commands and register descriptions — page 374

Manual reference: physical PDF page 374. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.4 Built-in PLC Function Description The E710 supports built-in basic PLC functionality by using TECO's Drive Link software to create ladder programs and upload them to the inverter.

4.4.1 Basic Commands

Special Register Descriptions

Exact printed cell scope and blanks preserved. Symbols normalized only to visible printable glyphs later; no unspecified PLC function inferred.

V8 explicitly listed despite matrixV1–V7. Frequency Hz andcurrentA retained; no unit invented for0–1000inputvalues.

PLC basic command matrix — PDF page 374

Source row Command family Unlabelled column2 SET symbol column RESET symbol column P Unlabelled column6 Unlabelled column7 NO / NC
1 Input Commands ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ I i I1~I8 / i1~i8
2 Output Commands Q Q Q Q Q q Q1~Q2 / q1~q2
3 Auxiliary Commands M M M M M m M1~MF / m1~mF
4 Special Registers ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ V1~V7
5 Counter Commands C ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ C c C1~C8 / c1~c8
6 Timer Commands T ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ T t T1~T8 / t1~t8
7 Analog Comparison Commands G ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ G g G1~G8 / g1~g8
8 Operation Control Commands F ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ F f F1~F8 / f1~f8
9 Addition and Subtraction Commands AS ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ AS1~4
10 Multiplication and Division Commands MD ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ MD1~4

Differential and other command symbols — PDF page 374

Source row Command Differential Up Differential Down Other Command Symbols
1 Differential Commands D d ⟦blank source cell⟧
2 SET Command ⟦blank source cell⟧ ⟦blank source cell⟧ ➚
3 RESET Command ⟦blank source cell⟧ ⟦blank source cell⟧ ➘
4 P Command ⟦blank source cell⟧ ⟦blank source cell⟧ P

Open short circuit notation — PDF page 374

Source row Circuit Symbol Blank source column
1 Open Circuit “ “ ⟦blank source cell⟧
2 Short Circuit “--” ⟦blank source cell⟧

PLC connection symbols — PDF page 374

Source row Connection Symbols Definition
1 ─ Connect components on the left and right sides
2 ┴ Connect components on the left, right, and upper sides
3 ┼ Connect components on the left, right, upper, and lower sides
4 ┬ Connect components on the left, right, and lower sides

Special register descriptions — PDF page 374

Source row Register and description Range
1 V1: Set Frequency Range: 0.1~599.0 Hz
2 V2: Operating Frequency Range: 0.1~599.0 Hz
3 V3: AI1 Input Value Range: 0~1000
4 V4: AI2 Input Value Range: 0~1000
5 V5: Keypad Input Value Range: 0~1000
6 V6: Output Current Range: 0.1~999.9 A
7 V7: Torque Value Range: 0.1~200.0%
8 V8: PID Target Value Range: 0.1~599.0 Hz

Manual — PLC differential and output command illustrations — page 375

Manual reference: physical PDF page 375. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.4.2 Basic Command Functions ◎ D (d) Command Function

Example1: I1 ─ D ───[ Q1. Visible rows I1, D, Q1 with ON/OFF labels; D andQ1annotation: Conducts for one scan cycle.

Example2: i1 ─ d ───[ Q1. i1 is the inverse of I1. Visible rows I1, i1, d1, Q1 withON/OFFlabels. Conducts for one scan cycle.

NORMAL(-[)Output Mode; I1───[Q1. I1 andQ1rows showOFF,ON,OFF.

SET(➚)Output Mode; I1───➚Q1. VisibleI1row OFF,ON,OFF;Q1row OFF,ON. PLC graphical symbol approximated by printablearrow; seeoriginal for exactsymbol.

RESET(➘)Output Mode; I1───➘Q1. VisibleI1rowOFF,ON,OFF;Q1rowON,OFF. PLC graphical symbol approximated by printablearrow; seeoriginal for exactsymbol.

P Output Mode; i1───PQ1. I1 row labels OFF,ON,OFF,ON,OFF,ON,OFF; i1is the inverse ofI1. Output continuation onpreservedbaselinePDF376,notduplicatedhere.

Manual — P Output Mode diagram continuation — page 376

Manual reference: physical PDF page 376. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

i1

Q1

ON

OFF

PreviousPDF375,printed4-325,labels P Output Mode and i1 is the inverse of I1; context only, not full375review. PDF376contains continuationwaveform, no numeric time scale. Original governs waveform geometry and switching relationships.

Qualitative diagram labels only. No timing, pulse widths or switching thresholds inferred from pixels; consult original375–376together.

Timing diagram labels — PDF page 376

Source row Element Printed label sequence
1 Upper input trace i1
2 Lower output trace Q1
3 Output state labels left to right ON; OFF; ON; OFF

Manual — Counter symbols modes and mode1 example — page 377

Manual reference: physical PDF page 377. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.4.3 Application Commands 1. Counter

Counter Mode Descriptions:

Mode 1: Counter value locks at setpoint. Value is not retained when powered off.

Mode 2: Counter value does not lock. Value is not retained when powered off.

Mode 3: Counter value locks and is retained when powered off.

Mode 4: Counter value does not lock but is retained when powered off.

(1) Counter Mode 1

①=1;⑤setpoint20;④visible numeric run 0,0,0,1,1,2,2,1,1,0,[blank],19,19,20,20,20,0,20,20. Input Count Pulse;②OFF/ON;③ON/OFF;⑥OFF/ON. Blank remains blank; waveform timing/edgegeometry not converted into engineeringdata.

Exact printed cell scope and blanks preserved. Symbols normalized only to visible printable glyphs later; no unspecified PLC function inferred.

Counter function symbol descriptions — PDF page 377

Source row Symbol Description
1 ① Counting Modes (1–4)
2 ② The up/down counting mode can be configured using (I1 ~ f8).
3 ⟦blank source cell⟧ OFF: Up count (0, 1, 2, 3…)
4 ⟦blank source cell⟧ ON: Down count (…3, 2, 1, 0)
5 ③ Counter Reset Configuration using (I1 and f8)
6 ⟦blank source cell⟧ ON: Resets the count and turns OFF ⑥
7 ⟦blank source cell⟧ OFF: Continues counting
8 ④ Current Counter Value
9 ⑤ Counter Setpoint (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V7, constants)
10 ⑥ Counter Number (C1~C8, total of 8 sets)

Manual — Counter ladder function example and mode2 — page 378

Manual reference: physical PDF page 378. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: FUNCTION input pro- and lower counter-setpoint annotation visibly clipped; unseen suffixes unverified. Ladder geometry remains original.

Example:

(2) Counter Mode 2

※Note: In this mode, the current count value can exceed 20 and will not lock at 20 like in Mode 1.

In the LADDER program: I1,i2,C3,Q1,m1,q1,M2. The ON/OFF state of count pulse input to C3 is determined by I1 & I2. In the FUNCTION input pro- [source label ends here]. Up/Down count; Current Counter Value; M2;0000;0020;C3;I3. When the counter reaches the setpoint,C3=ON;at the same time,C3input point inLADDER isalsoON. I3ON:Resets the counter. Setpoint configuration; following for the counter label is visibly clipped at lower edge. Exact ladder branches stay original.

①=2;⑤setpoint20;④numeric run0,19,19,20,20,21,21,20,20,19,19,18,18,19,19,20,0,20,20. Input count pulse;②OFF/ON;③OFF/ON;⑥OFF/ON. Illustration counts, not operating limit; waveform geometry retainedoriginal.

Manual — Retentive counters and timer configuration — page 379

Manual reference: physical PDF page 379. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(1) Counter Mode 3 is the same as Mode 1, but retains the current count value after power off. The value will be available the next time the power is turned on.

(2) Counter Mode 4 is the same as Mode 2, but retains the current count value after power off. The value will be available the next time the power is turned on.

  1. Timer

⑤setpoint20;④Mode1&2visible runs1,1,2,2 thenblankcells then0,1,1,2,2;④Mode3&4visible runs1,1,2,2,3 thenblankcells then3,4,4,5,5. Input Count Pulse; Power Switch;⑥. Blank cellsnotfilled;noedgeorwallclocktiminginferred.

Timer function symbol positions1,2,3,4,5,6; definitions inphysical379table. Original geometry authoritative.

Exact printed cell scope and blanks preserved. Symbols normalized only to visible printable glyphs later; no unspecified PLC function inferred.

Timer function symbol descriptions — PDF page 379

Source row Symbol Description
1 ① Timer Modes (0–7)
2 ② Time Units: 1: 0.0–999.9 seconds
3 ⟦blank source cell⟧ 2: 0–9999 seconds
4 ⟦blank source cell⟧ 3: 0–9999 minutes
5 ③ Timer Reset Configuration using (I1 and f8)
6 ⟦blank source cell⟧ ON: Resets the timer and turns⑥ OFF
7 ⟦blank source cell⟧ OFF: Continues timing
8 ④ Current Timer Value
9 ⑤ Timer Setpoint (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
10 ⑥ Timer Number (T1-T8, total of 8 sets)

Manual — Timer modes0 and1 with ladder example — page 380

Manual reference: physical PDF page 380. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Timer Mode Descriptions:

(1) Timer Mode 0 (ON-RTC Mode)

(2) Timer Mode 1 (ON-Delay Timer Mode 1)

Example:

③;④;⑥; Reset relay activates; Timer value=0; When RTC set time is reached; Starts timing relay operation; On time-up, output point(T1-T8)activates; OFF/ON/OFF. NoRTCcalendar capabilities inferred.

③;④;⑤;⑥; Reset relay activates; Timer value = 0; Timer value starts counting; Starts timing relay operation; On time-up, output point(T1-T8)activates; t=Timer setpoint;OFF/ON/OFF. Noadditional timing specification inferred.

In the LADDER program:I1,T5,Q1. WhenI1=ON,the fifth timer starts counting. In the FUNCTION program,input:Time unit0.1sec;Timer mode1;Current timer value000.0;Timer setpoint010.0;T5. When the timer reaches the setpoint10.0,T5turnsON. Original ladder geometry retained.

Manual — Timer modes2 and3 — page 381

Manual reference: physical PDF page 381. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(3) Timer Mode 2 (ON-Delay Timer Mode 2)

(4) Timer Mode 3 (OFF-Delay Timer Mode 1)

③;④;⑤;⑥; Reset relay activates; Timer value = 0; Timer value starts counting; Starts timing relay operation; On time-up, output point(T1-T8)activates; Reset relay activates;OFF;ON;t1;t2;t=t1+t2;t=Timer Action Value. Equality explicitly printed; no numeric durationinferred.

③;④;⑤;⑥; Reset relay activates; Timer value = 0; Timer value starts counting; Starts timing relay operation; On time-up, output point(T1-T8)activates; Reset relay activates;OFF;ON;t=Timer setpoint. Waveform notdigitized.

③;⑥;Starts timing relay operation;On time-up,output point(T1-T8)activates;Reset relay activates;OFF;ON;t=Timer setpoint. Repeated tlabels retained; noedgebehaviorinferred beyondsource.

Manual — Timer modes4 to6 — page 382

Manual reference: physical PDF page 382. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Timer mode5 output label suffix is visibly clipped; no missing word supplied from adjacent timer modes.

(5) Timer Mode 4 (OFF-Delay Timer Mode 2)

(6) Timer Mode 5 (FLASH Timer Mode 1)

(7) Timer Mode 6 (FLASH Timer Mode 2)

Reset relay activates; Timer value = 0; Timer value starts counting; Starts timing relay operation; On time-up, output point(T1-T8)activates; Reset relay activates;OFF;ON;t=Timer Setpoint. Source diagram only.

Reset relay activates;Timer value=0;Timer value starts counting;Starts timing relay operation;On time-up,output point(T1-T8);t=Timer Setpoint. Following output-label suffix visibly clipped; not reconstructed. Waveform geometry retained.

Reset relay activates; Timer value = 0; Timer value starts counting; Starts timing relay operation; On time-up, output point(T1-T8)activates; Reset relay activates;t=Timer Setpoint; repeated tintervals. Noadditional operating durationsinferred.

Manual — Timer mode7 distinct setpoints — page 383

Manual reference: physical PDF page 383. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(8) Timer Mode 7 (FLASH Timer Mode 3)

Reset relay activates; Timer value = 0; Timer value starts counting; Starts timing relay operation; On time-up, output point(T1-T8)activates; t1=First Timer Setpoint;t2=Second Timer Setpoint. Separate firstandsecondsetpoints retained; waveformgeometry staysoriginal.

Manual — Analog comparator modes and input sources — page 384

Manual reference: physical PDF page 384. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. Analog Comparator

Analog Comparison Mode Descriptions:

(1) Analog Comparison Mode 1: (③ ≤ ⑤, ⑥ ON)

(2) Analog Comparison Mode 2: (③ ≥ ④, ⑥ ON)

(3) Analog Comparison Mode 3: (⑤ ≤ ③ ≤ ④, ⑥ ON)

Comparison Input Source Selection (V1~V7):

(1) Comparison Input Source Selection = V1: Set Frequency

(2) Comparison Input Source Selection = V2: Operating Frequency

(3) Comparison Input Source Selection = V3: AI1 Input Value (4) Comparison Input Source Selection = V4: AI2 Input Value

(5) Comparison Input Source Selection = V5: Operation Panel Input Value

(6) Comparison Input Source Selection = V6: Operating Current

(7) Comparison Input Source Selection = V7: Torque Value

(8) Comparison Input Source Selection = V8: PID Target Value

Analog comparator function diagram identifiers1,2,3,4,5,6; table maps definitions. Original branch geometry nottranscribedaslogic.

Exact printed cell scope and blanks preserved. Symbols normalized only to visible printable glyphs later; no unspecified PLC function inferred.

Analog comparator symbol descriptions — PDF page 384

Source row Symbol Description
1 ① Analog Comparison Modes (1–3)
2 ② Comparison Input Source Selection (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8)
3 ③ Current Analog Input Value
4 ④ Reference Comparison Value (Upper Limit) (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
5 ⑤ Reference Comparison Value (Lower Limit) (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
6 ⑥ Analog Comparator Output Point (G1~G8)

Manual — Operation control command descriptions and example — page 385

Manual reference: physical PDF page 385. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. Operation Control Commands

Example:

In the LADDER program:I1,F1,Q1. In the LADDER program,the RUN/STOP status ofF1is controlled bytheON/OFFstate ofI1. Laddergeometrystaysoriginal.

In the FUNCTION input program: M1,M2,n,n;10.0,10.0,60.00,30.00;F1. When the inverter starts running,F1=ON. At the same time,theF1inputpointintheLADDERprogram also turnsON. Example values retainedwithpositionsinoriginalimage; no newunitsassigned.

Exact printed cell scope and blanks preserved. Symbols normalized only to visible printable glyphs later; no unspecified PLC function inferred.

Operation control command symbols — PDF page 385

Source row Symbol Description
1 ① Timer Reset Configuration using (I1~f8) OFF: Forward (FWD) ON: Reverse (REV)
2 ② Multi-Speed Terminal Control can be set using (I1-f8)
3 ⟦blank source cell⟧ OFF: Operates at the Set Frequency ③
4 ⟦blank source cell⟧ ON: Operates at the Multi-Speed Frequency ④
5 ③ Set Frequency (can be a constant or V3, V4, V5, V8)
6 ④ Multi-Speed Frequency (can be a constant or V3, V4, V5, V8)
7 ⑤ Acceleration Time (ACC Time)
8 ⑥ Deceleration Time (DEC Time)
9 ⑦ Operation Control Command Number (F1~F8, total of 8 groups)

Manual — PLC arithmetic operation symbols and formulas — page 386

Manual reference: physical PDF page 386. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

  1. Addition and Subtraction Mode

RESULT (Calculation Result) = V1 + V2 – V3

  1. Multiplication and Division Mode

RESULT (Calculation Result) = V1 × V2 ÷ V3

Function diagram identifiers1,2,3,4,5,6. Definitions supplied in adjacent source table; geometry remains original.

Exact printed source values and symbol references; no inferred function or connector orientation.

Addition and subtraction symbols — PDF page 386

Source row Symbol Description
1 ① Calculation Result
2 ② Addend V1 (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
3 ③ Addend V2 (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
4 ④ Subtrahend V3 (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
5 ⑤ Error signal coil output (M1~MF)
6 ⑥ Addition/Subtraction Mode Number (AS1~AS4)

Multiplication and division symbols — PDF page 386

Source row Symbol Description
1 ① Calculation Result
2 ② Multiplier V1 (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
3 ③ Multiplier V2 (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
4 ④ Divisor V3 (AS1~AS4, MD1~MD4, T1~T8, C1~C8, V1~V8, constants)
5 ⑤ Error signal coil output (M1~MF)
6 ⑥ Multiplication/Division Mode Number (MD1~MD4)

Manual — Modbus hardware interfaces and CN6 connections — page 387

Manual reference: physical PDF page 387. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.5 Modbus Communication Protocol Description

4.5.1 Communication Hardware and Data Structure The E710 series models accept commands from a computer or other upper-level controller via RS485 or RS232 communication interfaces. It supports Modbus RTU Mode and Modbus ASCII Mode protocols. The maximum receive size is 84 bytes, and the maximum send size is 80 bytes.

• Hardware Installation Method

A 120Ω, 1/4W termination resistor must be installed at both the starting and ending points of the communication line.

CN6 Pin definitions as indicated below:

When using RS-485 communication, S(+) corresponds to Pin 1 or Pin 3; S(–) corresponds to Pin 2 or Pin 6

Upper Controller (PLC / HMI or PC) RS-485 Interface Receiving Transmitting

Slave Station ID 01 CN6 S(+) S(-)

Slave Station ID 02 CN6 S(+) S(-)

Slave Station ID 03 CN6 S(+) S(-)

Slave Station ID FE CN6 S(+) S(-)

120Ω 1/4w

Exact printed source values and symbol references; no inferred function or connector orientation.

CN6 pin definitions — PDF page 387

Source row Pin left Signal name left Pin right Signal name right
1 1 RS-485 Data+ Signal 5 Reserved
2 2 RS-485 Data– Signal 6 RS-485 Data– Signal
3 3 RS-485 Data+ Signal 7 5V Power
4 4 Reserved 8 GND

Manual — ASCII RTU frames addressing and function codes — page 388

Manual reference: physical PDF page 388. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Data Frame Structure FOR ASCII MODE

FOR RTU MODE

• Communication Address 00H: Broadcast to all drives 01H: Address 01 drive 0FH: Address 15 drive 10H: Address 16 drive ..and so on, up to a maximum of 31 (1FH)

• Function Code 03H: Read holding register 06H: Write a single WORD to the register (single register write) 08H: Loopback test 10H: Write multiple registers (multiple register write)

In RTU Mode, the master device (e.g., PLC) sends a command to the slave, and the slave replies. Communication Sequence Structure As shown on the right, the length of the DATA section varies depending on the content of the command (function).

**A minimum interval of 10 ms must be maintained between command and response signals.

Slave Address Function Code DATA CRC CHECK Signal Interval

Repeated physical ASCII character fields grouped only inside source shared description cell. END Li literal preserved, not corrected to Lo.

ASCII frame structure — PDF page 388

Source row Frame field sequence Shared definition
1 STX(3AH) Start Character: 3AH
2 Address Hi Address Lo Communication Address (Station ID): 2 ASCII characters
3 Function Hi Function Lo Function Code (Command): 2 ASCII characters
4 Command Start Address Command Start Address Command Start Address Command Start Address Command Start Bit: 4 ASCII characters
5 Data length Data length Data length Data length Length from Command Start to End: 4 ASCII characters
6 LRC Check Hi LRC Check Lo LRC Checksum: 2 ASCII characters
7 END Hi END Lo End Character: END Hi = CR(0DH),END Li = LF(0AH)

Manual — LRC CRC instructions and literal code example — page 389

Manual reference: physical PDF page 389. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Checksum Calculation

LRC ex. ADDRESS 01H FUNCTION 03H COMMAND 01H 00H + DATA LENGTH 0AH ------------------------------------------ 0FH – Two’s complement Checksum = F1H CS(H) = 46H (ASCII) CS(L) = 31H (ASCII)

CRC CRC CHECK: The CRC checksum is calculated from the slave address to the end of the DATA section as follows:

(1) Set a 16-bit register to FFFFH (all bits set to 1) as the CRC register.

(2) Perform an exclusive OR (XOR) operation between the first byte of the command signal and the lower byte of the 16-bit CRC register, and store the result back into the CRC register.

(3) Shift the CRC register one bit to the right, filling the most significant bit (leftmost bit) with 0. Check the current value of the CRC register.

(4) If the result is 0, store the new value from step (3) into the CRC register. If not, perform an XOR operation between the CRC register and A001H (binary: 1010 0000 0000 0001), then store the result into the CRC register.

(5) Repeat steps (3) and (4) until all 8 bits are processed.

(6) Repeat steps (2) to (5) for the next 8-bit command byte, and continue until all command bytes have been processed. The final value in the CRC register is the CRC checksum. When transmitting, send the low-order byte first, followed by the high-order byte. For example, if the CRC checksum value is 1241hex, the CRC-16 high byte must be set to 41hex, and the low byte must be set to 12hex.

• CRC Calculation Application

UWORD ch_sum ( UBYTE long , UBYTE *rxdbuff ) {

BYTE i = 0;

UWORD wkg = 0xFFFF;

while ( long-- ) {

wkg ^= rxdbuff++;

for ( i = 0 ; i < 8; i++ ) {

if ( wkg & 0x0001 ) {

wkg = ( wkg >> 1 ) ^ 0xa001;

}

else {

wkg = wkg >> 1;

return( wkg );

Manual — Communication error response examples and codes — page 390

Manual reference: physical PDF page 390. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Error code ASCII Mode RTU Mode

When communication is established and an error occurs, the drive will respond with an error code and return the function code plus 80H to the master system, indicating that an error has occurred.

Exact printed source values and symbol references; no inferred function or connector orientation.

ASCII example separate from RTU example; character sequence and quotes preserved.

Separate RTU station and command, not normalized to ASCII example.

High/Low order exactly printed; source CRC naming contradiction flagged, no recomputation.

Communication exception codes — PDF page 390

Source row Error code Description
1 01 Invalid function code
2 02 Invalid register address
3 03 Invalid data setting
4 04 Number of registers exceeds 32

ASCII error response example — PDF page 390

Source row Field ASCII characters
1 STX ‘:’
2 Address ‘0’ ‘1’
3 Function ‘8’ ‘6’
4 Exception code ‘5’ ‘1’
5 LRC Check ‘2’ ‘8’
6 END ‘CR’ ‘LF’

RTU error response example — PDF page 390

Source row Field Value
1 Slave Address 02H
2 Function 83H
3 Exception code 52H

RTU error CRC example — PDF page 390

Source row Checksum Byte labels Byte values
1 CRC-16 High Low C0H CDH

Manual — Command register data format and bit meanings — page 391

Manual reference: physical PDF page 391. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.5.2 Register and Data Format • Command DATA (allows reading and writing)

2501H

Operation signal

Command DATA allows reading and writing; source frequency resolution exception on391footnote; reserved values preserved.

Physical merged parent register2501H / Operation signal. Frame1doesnotsupportS7; one-bit behavior onlyasprinted.

Command register scalar data — PDF page 391

Source row Register address Content
1 2500H Reserved
2 2502H *Frequency command (Unit: 0.01Hz)
3 2503H Torque Command (+/-8192 corresponds to rated torque +/-100%)
4 2504H Speed Limit (+/-120 corresponds to +/-120%)
5 2505H AO1 (0.00V~10.00V)
6 2506H AO2 (0 ~ 1000) Voltage (corresponds to 0.00~10.00V) Current (corresponds to 4mA~20mA)
7 2507H DO
8 2508H Reserved
9 2509H Reserved
10 250AH Reserved
11 250BH Reserved
12 250CH Reserved
13 250DH Reserved
14 250EH Reserved
15 250FH Reserved
16 2510H G12-00 H-WORD
17 2511H G12-00 L-WORD

2501H Operation signal bits — PDF page 391

Source row Bit Content
1 0 Operation Command 1: Run 0: Stop
2 1 Reverse Command 1: Reverse 0: Forward
3 2 External Error 1: Error
4 3 Error reset 1: Reset
5 4 Reserved
6 5 Reserved
7 6 Multi-function terminal S1 1: “ON”
8 7 Multi-function terminal S2 1: “ON”
9 8 Multi-function terminal S3 1: “ON”
10 9 Multi-function terminal S4 1: “ON”
11 A Multi-function terminal S5 1: “ON”
12 B Multi-function terminal S6 1: “ON”
13 C Multi-function terminal S7 1: “ON” (Frame1 does not support S7)
14 D Reserved
15 E Controller mode 1: “ON”
16 F Communication setting torque command 1: “ON”

Manual — Read-only monitor status errors and digital inputs — page 392

Manual reference: physical PDF page 392. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Monitor DATA (read only)

2520H

Status signal

2521H

Error description

2522H

DI status

Monitor DATA read only; physicalparent2520H. Model440literalpreserved.

Physicalparent2521H Error description. Empty descriptionsremainblank,notreserved. Code48Chinese保留exactsource retained.

Read-only DIstatus; continuation bits9–F on393. Frame1doesnotsupportS7.

2520H Status signal bits — PDF page 392

Source row Bit Content
1 0 Operation status 1: Operate 0: Stop
2 1 Direction status 1: Reverse 0: Forward
3 2 Frequency converter operation preparation status 1: Preparation complete 0: Preparation not yet complete
4 3 Error 1: Abnormal
5 4 Warning 1: “ON”
6 5 Zero speed 1: “ON”
7 6 Model 440 1: “ON”
8 7 Frequency reached 1: “ON”
9 8 Any frequency reached 1: “ON”
10 9 Frequency detection one 1: “ON”
11 A Frequency detection two 1: “ON”
12 B Low voltage 1: “ON”
13 C Frequency converter no output 1: “ON”
14 D Frequency not according to communication 1: “ON”
15 E Seq. not from Comm 1 :“ON”
16 F Over-torque 1: “ON”

2521H Error descriptions 0–29 — PDF page 392

Source row Error code Description
1 0 ⟦blank source cell⟧
2 1 UV
3 2 OC
4 3 OV
5 4 OH1
6 5 OL1
7 6 OL2
8 7 OT
9 8 UT
10 9 SC
11 10 Ground OC
12 11 Fuse broken
13 12 Input Phase Loss
14 13 Output Phase Loss
15 14 PG Overspeed
16 15 PG Open
17 16 PG Speed Deviation
18 17 External Fault 01
19 18 External Fault 02
20 19 External Fault 03
21 20 External Fault 04
22 21 External Fault 05
23 22 External Fault 06
24 23 External Fault 07
25 24 External Fault 08
26 25 FB
27 26 OPR
28 27 ⟦blank source cell⟧
29 28 CE
30 29 STO

2521H Error descriptions 30–59 — PDF page 392

Source row Error code Description
1 30 ⟦blank source cell⟧
2 31 ⟦blank source cell⟧
3 32 ⟦blank source cell⟧
4 33 ⟦blank source cell⟧
5 34 ⟦blank source cell⟧
6 35 ⟦blank source cell⟧
7 36 LSCFT
8 37 LSCFT(Rtry)
9 38 CF07
10 39 LOPBT
11 40 HIPBT
12 41 Reserved
13 42 LPBFT
14 43 OPBFT
15 44 FBLSS
16 45 ⟦blank source cell⟧
17 46 OH4
18 47 SS1
19 48 保留
20 49 RUN
21 50 OCA
22 51 OCD
23 52 OCC
24 53 CF08
25 54 ⟦blank source cell⟧
26 55 PF (Protection fault)
27 56 TOL (External overload)
28 57 STO2
29 58 ⟦blank source cell⟧
30 59 ⟦blank source cell⟧

2522H DI status bits0–8 — PDF page 392

Source row Bit Content
1 0 Multi-function terminal S1
2 1 Multi-function terminal S2
3 2 Multi-function terminal S3
4 3 Multi-function terminal S4
5 4 Multi-function terminal S5
6 5 Multi-function terminal S6
7 6 Multi-function terminal S7 (Frame1 does not support S7)
8 7 Reserved
9 8 Reserved

Manual — Monitor registers and warning codes — page 393

Manual reference: physical PDF page 393. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2528H

Warning description

Continuation ofphysical392parent2522H;393parentcellblank, sourcepage linkexplicit. AllrowsReserved.

Monitor read only. Frequencyresolutionfootnote394. Crossfamily252FHliteralpreserved,notnewproductapplicability.

Physicalparent2528H Warning description; four side-by-sidecodecolumns splitwithoutmixingcodesandlabels.

2522H DI status continuation bits9–F — PDF page 393

Source row Bit Content
1 9 Reserved
2 A Reserved
3 B Reserved
4 C Reserved
5 D Reserved
6 E Reserved
7 F Reserved

Monitor scalar registers — PDF page 393

Source row Register address Content
1 2523H * Frequency command (0.01Hz)
2 2524H * Output frequency (0.01Hz)
3 2525H Reserved
4 2526H DC voltage command (0.1V)
5 2527H Output current (0.1A)
6 2529H DO status
7 252AH AO1 (0.00V ~ 10.00V)
8 252BH AO2 (0 ~ 1000) Voltage (corresponds to 0.00~10.00V) Current (corresponds to 4mA~20mA)
9 252CH AI 1 input (0.1%)
10 252DH AI 2 input (0.1%)
11 252EH Reserved
12 252FH L510(s)/ E510(s)/ A510(s)/ F510 Check

2528H Warning descriptions 0–21 — PDF page 393

Source row Warning code Description
1 0 No alarm
2 1 OV
3 2 UV
4 3 OL2
5 4 OH2
6 5 OH3
7 6 OT
8 7 Reserved
9 8 Reserved
10 9 UT
11 10 OS
12 11 PGO
13 12 DEV
14 13 CE
15 14 Reserved
16 15 Reserved
17 16 EF0
18 17 EF1
19 18 EF2
20 19 EF3
21 20 EF4
22 21 EF5

2528H Warning descriptions 22–43 — PDF page 393

Source row Warning code Description
1 22 EF6
2 23 EF7
3 24 Reserved
4 25 CLA
5 26 CLB
6 27 Reserved
7 28 Reserved
8 29 USP
9 30 RDE
10 31 WRE
11 32 FB
12 33 VRYE
13 34 SE01
14 35 SE02
15 36 SE03
16 37 Reserved
17 38 SE05
18 39 HPERR
19 40 EF
20 41 Reserved
21 42 Reserved
22 43 RDP

2528H Warning descriptions 44–65 — PDF page 393

Source row Warning code Description
1 44 Reserved
2 45 OL1
3 46 HP_ER
4 47 SE10
5 48 COPUP
6 49 BB1
7 50 BB2
8 51 BB3
9 52 BB4
10 53 BB5
11 54 BB6
12 55 BB7
13 56 Reserved
14 57 LOPB
15 58 HIPB
16 59 LSCFT
17 60 LFPB
18 61 RETRY
19 62 SE07
20 63 SE08
21 64 HFPB
22 65 OH1

2528H Warning descriptions 66–87 — PDF page 393

Source row Warning code Description
1 66 FIRE
2 67 ES
3 68 STP1
4 69 Reserved
5 70 EPERR
6 71 ADCER
7 72 Reserved
8 73 STP0
9 74 ENC
10 75 STP2
11 76 RUNER
12 77 LOC
13 78 Reserved
14 79 Reserved
15 80 FBLSS
16 81 CYEAR
17 82 SE11
18 83 CBER1
19 84 FLIFE
20 85 ILIFE
21 86 CBER2
22 87 CBER3

Manual — Reserved-register warning and read03H examples — page 394

Manual reference: physical PDF page 394. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Note : Do not write in data for the reserved register. *: (When the maximum output frequency of the motor exceeds 300Hz, the frequency resolution is 0.1Hz)

• Read Holding Register Contents [03H] Reads a specified number of consecutive holding register contents starting from a designated address. (Example) Reading the frequency command from inverter A510 of SLAVE 1.

ASCII Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

RTU Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

Each example remains separate; merged fieldbytes grouped inphysicalsourceorder. Empty byte-ordercell indicates no separateHigh/Low source subcell. CRC/LRCvaluesnotrecomputed; examplesnotexecuted.

ASCII Command Signal — PDF page 394

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 30H 33H Function Code
4 30H 43H 31H 30H Starting Address
5 30H 30H 30H 31H Quantity
6 44H 46H LRC CHECK
7 0DH 0AH END

ASCII Response Signal Normal — PDF page 394

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 30H 33H Function Code
4 30H 32H Data Items
5 31H 37H 37H 30H First Holding Register
6 37H 33H LRC CHECK
7 0DH 0AH END

ASCII Response Signal Error Data Length Mismatch — PDF page 394

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 38H 33H Function Code
4 30H 34H Error Code
5 34H 30H LRC CHECK
6 0DH 0AH END

RTU Command Signal — PDF page 394

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01 H
2 Function Code ⟦blank source cell⟧ 03H
3 Starting Address High Low 0CH 10H
4 Quantity High Low 00H 01H
5 CRC-16 High Low 86H 9FH

RTU Response Signal Normal — PDF page 394

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 03H
3 Data Items ⟦blank source cell⟧ 02H
4 First Holding Register High Low 17H 70H
5 CRC-16 High Low B6H 50H

RTU Response Signal Error Data Length Mismatch — PDF page 394

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 83H
3 Error Code ⟦blank source cell⟧ 04H
4 CRC-16 High Low 40H F3H

Manual — Loopback08H ASCII and RTU examples — page 395

Manual reference: physical PDF page 395. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• LOOP BACK Test [08H]

The command message is returned as the response message. This test function is used between the MASTER and SLAVE to verify signal transmission. The data field can be set to any arbitrary value for testing purposes.

ASCII Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

RTU Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

Each example remains separate; merged fieldbytes grouped inphysicalsourceorder. Empty byte-ordercell indicates no separateHigh/Low source subcell. CRC/LRCvaluesnotrecomputed; examplesnotexecuted.

ASCII Command Signal — PDF page 395

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 30H 38H Function Code
4 30H 30H 30H 30H Testing Code
5 41H 35H 33H 37H DATA
6 31H 42H LRC CHECK
7 0DH 0AH END

ASCII Response Signal Error Data Length Mismatch — PDF page 395

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 38H 38H Function Code
4 30H 33H Error Code
5 30H 36H LRC CHECK
6 0DH 0AH END

RTU Command Signal — PDF page 395

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01 H
2 Function Code ⟦blank source cell⟧ 08H
3 Testing Code High Low 00H 00H
4 DATA High Low A5H 37H
5 CRC-16 High Low DAH 8DH

RTU Response Signal Normal — PDF page 395

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 08H
3 Testing Code High Low 00H 00H
4 DATA High Low A5H 37H
5 CRC-16 High Low DAH 8DH

RTU Response Signal Error Data Length Mismatch — PDF page 395

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 88H
3 Error Code ⟦blank source cell⟧ 03H
4 CRC-16 High Low 06H 01H

Manual — Single register write06H examples — page 396

Manual reference: physical PDF page 396. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Write to Holding Register [06H] Writes a specified value to a single holding register at the designated address. (Example) Set the frequency command to 60.00 Hz on the inverter of SLAVE 1 via PLC.

ASCII Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

RTU Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

Each example remains separate; merged fieldbytes grouped inphysicalsourceorder. Empty byte-ordercell indicates no separateHigh/Low source subcell. CRC/LRCvaluesnotrecomputed; examplesnotexecuted.

ASCII Command Signal — PDF page 396

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 30H 36H Function Code
4 32H 35H 30H 32H Starting Address
5 31H 37H 37H 30H DATA
6 34H 42H LRC CHECK
7 0DH 0AH END

ASCII Response Signal Error Data Length Mismatch — PDF page 396

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 38H 36H Function Code
4 30H 33H Error Code
5 30H 32H LRC CHECK
6 0DH 0AH END

RTU Command Signal — PDF page 396

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01 H
2 Function Code ⟦blank source cell⟧ 06H
3 Starting Address High Low 25H 02H
4 Quantity High Low 17H 70H
5 CRC-16 High Low 2DH 12H

RTU Response Signal Normal — PDF page 396

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 06H
3 Starting Address High Low 25H 02H
4 Quantity High Low 17H 70H
5 CRC-16 High Low 2DH 12H

RTU Response Signal Error Data Length Mismatch — PDF page 396

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 86H
3 Error Code ⟦blank source cell⟧ 03H
4 CRC-16 High Low 02H 61H

Manual — Multiple register write10H ASCII examples — page 397

Manual reference: physical PDF page 397. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

• Write to Multiple Holding Registers [10H] Writes specified data to a designated number of consecutive holding registers, starting from the specified address. (Example) Use a PLC to set the A510 inverter of SLAVE 1 to a frequency command of 60.00 Hz and run in the forward direction.

ASCII Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

Each example remains separate; merged fieldbytes grouped inphysicalsourceorder. Empty byte-ordercell indicates no separateHigh/Low source subcell. CRC/LRCvaluesnotrecomputed; examplesnotexecuted.

ASCII Command Signal — PDF page 397

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 31H 30H Function Code
4 32H 35H 30H 31H Starting Address
5 30H 30H 30H 32H Quantity
6 30H 34H DATA Count*
7 30H 30H 30H 31H First DATA
8 31H 37H 37H 30H Subsequent DATA
9 33H 42H LRC CHECK
10 0DH 0AH END

ASCII Response Signal Normal — PDF page 397

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 31H 30H Function Code
4 32H 35H 30H 31H Starting Address
5 30H 30H 30H 32H Quantity
6 43H 37H LRC CHECK
7 0DH 0AH END

ASCII Response Signal Error Data Length Mismatch — PDF page 397

Source row Character bytes in source order Field
1 3AH STX
2 30H 31H Slave Address
3 39H 30H Function Code
4 30H 33H Error Code
5 30H 43H LRC CHECK
6 0DH 0AH END

Manual — Write10H RTU examples and parameter register map — page 398

Manual reference: physical PDF page 398. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

RTU Mode Command Signal Response Signal (Normal) Response Signal (Error – Data Length Mismatch)

• Parameters and Corresponding Register Numbers

Each example remains separate; merged fieldbytes grouped inphysicalsourceorder. Empty byte-ordercell indicates no separateHigh/Low source subcell. CRC/LRCvaluesnotrecomputed; examplesnotexecuted.

Three physical columnpairs separated; trailingblankcellsretained. Group0indices37–44notlistedhere; no inventedmapping. Subsequentpage399baselinepreserved.

RTU Command Signal — PDF page 398

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01 H
2 Function Code ⟦blank source cell⟧ 10H
3 Starting Address High Low 25H 01H
4 Quantity High Low 00H 02H
5 DATA Count* ⟦blank source cell⟧ 04H
6 First DATA High Low 00H 01H
7 Subsequent DATA High Low 17H 70H
8 CRC-16 High Low 60H 27H

RTU Response Signal Normal — PDF page 398

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 10H
3 Starting Address High Low 25H 01H
4 Count High Low 00H 02H
5 CRC-16 High Low 1BH 04H

RTU Response Signal Error Data Length Mismatch — PDF page 398

Source row Field Byte order labels if separate Bytes in printed order
1 Slave Address ⟦blank source cell⟧ 01H
2 Function Code ⟦blank source cell⟧ 90H
3 Error Code ⟦blank source cell⟧ 03H
4 CRC-16 High Low 0CH 01H

Parameter register map Group0 functions00–36 — PDF page 398

Source row Function Register No
1 0 – 00 0000H
2 0 – 01 0001H
3 0 – 02 0002H
4 0 – 03 0003H
5 0 – 04 0004H
6 0 – 05 0005H
7 0 – 06 0006H
8 0 – 07 0007H
9 0 – 08 0008H
10 0 – 09 0009H
11 0 – 10 000AH
12 0 – 11 000BH
13 0 – 12 000CH
14 0 – 13 000DH
15 0 – 14 000EH
16 0 – 15 000FH
17 0 – 16 0010H
18 0 – 17 0011H
19 0 – 18 0012H
20 0 – 19 0013H
21 0 – 20 0014H
22 0 – 21 0015H
23 0 – 22 0016H
24 0 – 23 0017H
25 0 – 24 0018H
26 0 – 25 0019H
27 0 – 26 001AH
28 0 – 27 001BH
29 0 – 28 001CH
30 0 – 29 001DH
31 0 – 30 001EH
32 0 – 31 001FH
33 0 – 32 0020H
34 0 – 33 0021H
35 0 – 34 0022H
36 0 – 35 0023H
37 0 – 36 0024H

Parameter register map Group0 functions45–63 — PDF page 398

Source row Function Register No
1 0 – 45 002DH
2 0 – 46 002EH
3 0 – 47 002FH
4 0 – 48 0030H
5 0 – 49 0031H
6 0 – 50 0032H
7 0 – 51 0033H
8 0 – 52 0034H
9 0 – 53 0035H
10 0 – 54 0036H
11 0 – 55 0037H
12 0 – 56 0038H
13 0 – 57 0039H
14 0– 58 003AH
15 0– 59 003BH
16 0– 60 003CH
17 0– 61 003DH
18 0– 62 003EH
19 0– 63 003FH
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group1 functions00–26 — PDF page 398

Source row Function Register No
1 1 – 00 0100H
2 1 – 01 0101H
3 1 – 02 0102H
4 1 – 03 0103H
5 1 – 04 0104H
6 1 – 05 0105H
7 1 – 06 0106H
8 1 – 07 0107H
9 1 – 08 0108H
10 1 – 09 0109H
11 1 – 10 010AH
12 1 – 11 010BH
13 1 – 12 010CH
14 1 – 13 010DH
15 1 – 14 010EH
16 1 – 15 010FH
17 1 – 16 0110H
18 1 – 17 0111H
19 1 – 18 0112H
20 1 – 19 0113H
21 1 – 20 0114H
22 1 – 21 0115H
23 1 – 22 0116H
24 1 – 23 0117H
25 1 – 24 0118H
26 1 – 25 0119H
27 1 – 26 011AH
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameters and Corresponding Register Numbers — continuation — page 399

Manual reference: physical PDF page 399. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Headers carried from physical page 398 (printed 4-348): three Function/Register No. pairs. Only the first pair is populated on page 399. Four remaining cells per row are blank, not missing addresses to fill.

Group/headercontext from398; literal8rows and32blankcells on399 retained. No actual parameter values or factorysettings inferred.

Register mapping continuation — PDF page 399

Source row Function (left pair; Group0) Register No (left pair) Function (middle pair; Group0) Register No (middle pair) Function (right pair; Group1) Register No (right pair)
1 0 – 37 0025H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
2 0 – 38 0026H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
3 0 – 39 0027H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 0 – 40 0028H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
5 0 – 41 0029H ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 0 – 42 002AH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 0 – 43 002BH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 0 – 44 002CH ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 1 — page 400

Manual reference: physical PDF page 400. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Adjacent source context — repeated to preserve continuation:

Parameter register map Group 2 columnpair1 — PDF page 400

Source row Function Register No
1 2 – 00 0200H
2 2 – 01 0201H
3 2 – 02 0202H
4 2 – 03 0203H
5 2 – 04 0204H
6 2 – 05 0205H
7 2 – 06 0206H
8 2 – 07 0207H
9 2 – 08 0208H
10 2 – 09 0209H
11 2 – 10 020AH
12 2 – 11 020BH
13 2 – 12 020CH
14 2 – 13 020DH
15 2 – 14 020EH
16 2 – 15 020FH
17 2 – 16 0210H
18 2 – 17 0211H
19 2 – 18 0212H
20 2 – 19 0213H
21 2 – 20 0214H
22 2 – 21 0215H
23 2 – 22 0216H
24 2 – 23 0217H
25 2 – 24 0218H
26 2 – 25 0219H
27 2 – 26 021AH
28 2 – 27 021BH
29 2 – 28 021CH
30 2 – 29 021DH
31 2 – 30 021EH
32 2 – 31 021FH
33 2 – 32 0220H
34 2 – 33 0221H
35 2 – 34 0222H
36 2 – 35 0223H
37 2 – 36 0224H
38 2 – 37 0225H
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧
47 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 3 columnpair2 — PDF page 400

Source row Function Register No
1 3 – 00 0300H
2 3 – 01 0301H
3 3 – 02 0302H
4 3 – 03 0303H
5 3 – 04 0304H
6 3 – 05 0305H
7 3 – 06 0306H
8 3 – 07 0307H
9 3 – 08 0308H
10 3 – 09 0309H
11 3 – 10 030AH
12 3 – 11 030BH
13 3 – 12 030CH
14 3 – 13 030DH
15 3 – 14 030EH
16 3 – 15 030FH
17 3 – 16 0310H
18 3 – 17 0311H
19 3 – 18 0312H
20 3 – 19 0313H
21 3 – 20 0314H
22 3 – 21 0315H
23 3 – 22 0316H
24 3 – 23 0317H
25 3 – 24 0318H
26 3 – 25 0319H
27 3 – 26 031AH
28 3 – 27 031BH
29 3 – 28 031CH
30 3 – 29 031DH
31 3 – 30 031EH
32 3 – 31 031FH
33 3 – 32 0320H
34 3 – 33 0321H
35 3 – 34 0322H
36 3 – 35 0323H
37 3 – 36 0324H
38 3 – 37 0325H
39 3 – 38 0326H
40 3 – 39 0327H
41 3 – 40 0328H
42 3 – 41 0329H
43 3 – 42 032AH
44 3 – 43 032BH
45 3 – 44 032CH
46 3 – 45 032DH
47 3 – 46 032EH

Parameter register map Group 3 columnpair3 — PDF page 400

Source row Function Register No
1 3 – 47 032FH
2 3 – 48 0330H
3 3 – 49 0331H
4 3 – 50 0332H
5 3 – 51 0333H
6 3 – 52 0334H
7 3 – 53 0335H
8 3 – 54 0336H
9 3 – 55 0337H
10 3– 56 0338H
11 3– 57 0339H
12 3– 58 033AH
13 3– 59 033BH
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧
47 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 2 — page 401

Manual reference: physical PDF page 401. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Adjacent source context — repeated to preserve continuation:

Parameter register map Group 4 columnpair1 — PDF page 401

Source row Function Register No
1 4 – 00 0400H
2 4 – 01 0401H
3 4 – 02 0402H
4 4 – 03 0403H
5 4 – 04 0404H
6 4 – 05 0405H
7 4 – 06 0406H
8 4 – 07 0407H
9 4 – 08 0408H
10 4 – 09 0409H
11 4 – 10 040AH
12 4 – 11 040BH
13 4 – 12 040CH
14 4 – 13 040DH
15 4 – 14 040EH
16 4 – 15 040FH
17 4 – 16 0410H
18 4 – 17 0411H
19 4 – 18 0412H
20 4 – 19 0413H
21 4 – 20 0414H
22 4 – 21 0415H
23 4 – 22 0416H
24 4 – 23 0417H
25 4 – 24 0418H
26 4 – 25 0419H
27 4 – 26 041AH
28 4 – 27 041BH
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 5 columnpair2 — PDF page 401

Source row Function Register No
1 5 – 00 0500H
2 5 – 01 0501H
3 5 – 02 0502H
4 5 – 03 0503H
5 5 – 04 0504H
6 5 – 05 0505H
7 5 – 06 0506H
8 5 – 07 0507H
9 5 – 08 0508H
10 5 – 09 0509H
11 5 – 10 050AH
12 5 – 11 050BH
13 5 – 12 050CH
14 5 – 13 050DH
15 5 – 14 050EH
16 5 – 15 050FH
17 5 – 16 0510H
18 5 – 17 0511H
19 5 – 18 0512H
20 5 – 19 0513H
21 5 – 20 0514H
22 5 – 21 0515H
23 5 – 22 0516H
24 5 – 23 0517H
25 5 – 24 0518H
26 5 – 25 0519H
27 5 – 26 051AH
28 5 – 27 051BH
29 5 – 28 051CH
30 5 – 29 051DH
31 5 – 30 051EH
32 5 – 31 051FH
33 5 – 32 0520H

Parameter register map Group 5 columnpair3 — PDF page 401

Source row Function Register No
1 5 – 33 0521H
2 5 – 34 0522H
3 5 – 35 0523H
4 5 – 36 0524H
5 5 – 37 0525H
6 5 – 38 0526H
7 5 – 39 0527H
8 5 – 40 0528H
9 5 – 41 0529H
10 5 – 42 052AH
11 5 – 43 052BH
12 5 – 44 052CH
13 5 – 45 052DH
14 5 – 46 052EH
15 5 – 47 052FH
16 5 – 48 0530H
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 3 — page 402

Manual reference: physical PDF page 402. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 6 columnpair1 — PDF page 402

Source row Function Register No
1 6 – 00 0600H
2 6 – 01 0601H
3 6 – 02 0602H
4 6 – 03 0603H
5 6 – 04 0604H
6 6 – 05 0605H
7 6 – 06 0606H
8 6 – 07 0607H
9 6 – 08 0608H
10 6 – 09 0609H
11 6 – 10 060AH
12 6 – 11 060BH
13 6 – 12 060CH
14 6 – 13 060DH
15 6 – 14 060EH
16 6 – 15 060FH
17 6 – 16 0610H
18 6 – 17 0611H
19 6 – 18 0612H
20 6 – 19 0613H
21 6 – 20 0614H
22 6 – 21 0615H
23 6 – 22 0616H
24 6 – 23 0617H
25 6 – 24 0618H
26 6 – 25 0619H
27 6 – 26 061AH
28 6 – 27 061BH
29 6 – 28 061CH
30 6 – 29 061DH
31 6 – 30 061EH
32 6 – 31 061FH
33 6 – 32 0620H
34 6 – 33 0621H
35 6 – 34 0622H
36 6 – 35 0623H
37 6 – 36 0624H
38 6 – 37 0625H
39 6 – 38 0626H
40 6 – 39 0627H
41 6 – 40 0628H
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 6 columnpair2 — PDF page 402

Source row Function Register No
1 6 – 41 0629H
2 6 – 42 062AH
3 6 – 43 062BH
4 6 – 44 062CH
5 6 – 45 062DH
6 6 – 46 062EH
7 6 – 47 062FH
8 ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 7 columnpair3 — PDF page 402

Source row Function Register No
1 7 – 00 0700H
2 7 – 01 0701H
3 7 – 02 0702H
4 7 – 03 0703H
5 7 – 04 0704H
6 7 – 05 0705H
7 7 – 06 0706H
8 7 – 07 0707H
9 7 – 08 0708H
10 7 – 09 0709H
11 7 – 10 070AH
12 7 – 11 070BH
13 7 – 12 070CH
14 7 – 13 070DH
15 7 – 14 070EH
16 7 – 15 070FH
17 7 – 16 0710H
18 7 – 17 0711H
19 7 – 18 0712H
20 7 – 19 0713H
21 7 – 20 0714H
22 7 – 21 0715H
23 7 – 22 0716H
24 7 – 23 0717H
25 7 – 24 0718H
26 7 – 25 0719H
27 7 – 26 071AH
28 7 – 27 071BH
29 7 – 28 071CH
30 7 – 29 071DH
31 7 – 30 071EH
32 7 – 31 071FH
33 7 – 32 0720H
34 7 – 33 0721H
35 7 – 34 0722H
36 7 – 35 0723H
37 7 – 36 0724H
38 7 – 42 072AH
39 7 – 43 072BH
40 7 – 44 072CH
41 7 – 45 072DH
42 7 – 46 072EH
43 7 – 47 072FH

Manual — Parameter register mappings 4 — page 403

Manual reference: physical PDF page 403. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 8 columnpair1 — PDF page 403

Source row Function Register No
1 8 – 00 0800H
2 8 – 01 0801H
3 8 – 02 0802H
4 8 – 03 0803H
5 8 – 04 0804H
6 8 – 05 0805H
7 8 – 06 0806H
8 8 – 07 0807H
9 8 – 08 0808H
10 8 – 09 0809H
11 8 – 10 080AH
12 8 – 11 080BH
13 8 – 12 080CH
14 8 – 13 080DH
15 8 – 14 080EH
16 8 – 15 080FH
17 8 – 16 0810H
18 8 – 17 0811H
19 8 – 18 0812H
20 8 – 19 0813H
21 8 – 20 0814H
22 8 – 21 0815H
23 8 – 22 0816H
24 8 – 23 0817H
25 8 – 24 0818H
26 8 – 25 0819H
27 8 – 26 081AH
28 8 – 27 081BH
29 8 – 28 081CH
30 8 – 29 081DH
31 8 – 30 081EH
32 8 – 31 081FH
33 8 – 32 0820H
34 8 – 33 0821H
35 8 – 34 0822H
36 8 – 35 0823H
37 8 – 36 0824H
38 8 – 37 0825H
39 8 – 38 0826H
40 8 – 39 0827H
41 8 – 40 0828H
42 8 – 41 0829H
43 8 – 42 082AH
44 8 – 43 082BH
45 8 – 44 082CH
46 8 – 45 082DH

Parameter register map Group 8 columnpair2 — PDF page 403

Source row Function Register No
1 8 – 46 082EH
2 8 – 47 082FH
3 8 – 48 0830H
4 8 – 49 0831H
5 8 – 50 0832H
6 8 – 51 0833H
7 8 – 52 0834H
8 8 – 53 0835H
9 8 – 54 0836H
10 8 – 55 0837H
11 8 – 56 0838H
12 8 – 57 0839H
13 8 – 58 083AH
14 8 – 59 083BH
15 8 – 60 083CH
16 8 – 61 083DH
17 8 – 62 083EH
18 8 – 63 083FH
19 8 – 64 0840H
20 8 – 65 0841H
21 8 – 66 0842H
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 9 columnpair3 — PDF page 403

Source row Function Register No
1 9 – 00 0900H
2 9 – 01 0901H
3 9 – 02 0902H
4 9 – 03 0903H
5 9 – 04 0904H
6 9 – 05 0905H
7 9 – 06 0906H
8 9 – 07 0907H
9 9 – 08 0908H
10 9 – 09 0909H
11 9 – 10 090AH
12 9 – 11 090BH
13 9 – 12 090CH
14 9 – 13 090DH
15 9 – 14 090EH
16 9 – 15 090FH
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 5 — page 404

Manual reference: physical PDF page 404. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 10 columnpair1 — PDF page 404

Source row Function Register No
1 10 – 00 0A00H
2 10 – 01 0A01H
3 10 – 02 0A02H
4 10 – 03 0A03H
5 10 – 04 0A04H
6 10 – 05 0A05H
7 10 – 06 0A06H
8 10 – 07 0A07H
9 10 – 08 0A08H
10 10 – 09 0A09H
11 10 – 10 0A0AH
12 10 – 11 0A0BH
13 10 – 12 0A0CH
14 10 – 13 0A0DH
15 10 – 14 0A0EH
16 10 – 15 0A0FH
17 10 – 16 0A10H
18 10 – 17 0A11H
19 10 – 18 0A12H
20 10 – 19 0A13H
21 10 – 20 0A14H
22 10 – 21 0A15H
23 10 – 22 0A16H
24 10 – 23 0A17H
25 10 – 24 0A18H
26 10 – 25 0A19H
27 10 – 26 0A1AH
28 10 – 27 0A1BH
29 10 – 28 0A1CH
30 10 – 29 0A1DH
31 10 – 30 0A1EH
32 10 – 31 0A1FH
33 10 – 32 0A20H
34 10 – 33 0A21H
35 10 – 34 0A22H
36 10 – 35 0A23H
37 10 – 36 0A24H
38 10 – 37 0A25H
39 10 – 38 0A26H
40 10 – 39 0A27H
41 10 – 40 0A28H
42 10 – 41 0A29H
43 10 – 42 0A2AH
44 10 – 43 0A2BH
45 10 – 44 0A2CH
46 10 – 45 0A2DH

Parameter register map Group 10 columnpair2 — PDF page 404

Source row Function Register No
1 10 – 46 0A2EH
2 10 – 47 0A2FH
3 10 – 48 0A30H
4 10 – 49 0A31H
5 ⟦blank source cell⟧ ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Unlabelled empty column pair columnpair3 — PDF page 404

Source row Function Register No
1 ⟦blank source cell⟧ ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧
4 ⟦blank source cell⟧ ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 6 — page 405

Manual reference: physical PDF page 405. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 11 columnpair1 — PDF page 405

Source row Function Register No
1 11 – 00 0B00H
2 11 – 01 0B01H
3 11 – 02 0B02H
4 11 – 03 0B03H
5 11 – 04 0B04H
6 11 – 05 0B05H
7 11 – 06 0B06H
8 11 – 07 0B07H
9 11 – 08 0B08H
10 11 – 09 0B09H
11 11 – 10 0B0AH
12 11 – 11 0B0BH
13 11 – 12 0B0CH
14 11 – 13 0B0DH
15 11 – 14 0B0EH
16 11 – 15 0B0FH
17 11 – 16 0B10H
18 11 – 17 0B11H
19 11 – 18 0B12H
20 11 – 19 0B13H
21 11 – 20 0B14H
22 11 – 21 0B15H
23 11 – 22 0B16H
24 11 – 23 0B17H
25 11 – 24 0B18H
26 11 – 25 0B19H
27 11 – 26 0B1AH
28 11 – 27 0B1BH
29 11 – 28 0B1CH
30 11 – 29 0B1DH
31 11 – 30 0B1EH
32 11 – 31 0B1FH
33 11 – 32 0B20H
34 11 – 33 0B21H
35 11 – 34 0B22H
36 11 – 35 0B23H
37 11 – 36 0B24H
38 11 – 37 0B25H
39 11 – 38 0B26H
40 11 – 39 0B27H
41 11 – 40 0B28H
42 11 – 41 0B29H
43 11 – 42 0B2AH
44 11 – 43 0B2BH
45 11 – 44 0B2CH
46 11 – 45 0B2DH

Parameter register map Group 11 columnpair2 — PDF page 405

Source row Function Register No
1 11 – 46 0B2EH
2 11 – 47 0B2FH
3 11 – 48 0B30H
4 11 – 49 0B31H
5 11 - 50 0B32H
6 11 - 51 0B33H
7 11 – 52 0B34H
8 11 – 53 0B35H
9 11 – 54 0B36H
10 11 – 55 0B37H
11 11 – 56 0B38H
12 11 – 57 0B39H
13 11 – 58 0B3AH
14 11 – 59 0B3BH
15 11 – 60 0B3CH
16 11 – 61 0B3DH
17 11 – 62 0B3EH
18 11 – 63 0B3FH
19 11 – 64 0B40H
20 11 – 65 0B41H
21 11 – 66 0B42H
22 11 – 67 0B43H
23 11 – 68 0B44H
24 11 – 69 0B45H
25 11 – 70 0B46H
26 11 – 71 0B47H
27 11 – 72 0B48H
28 11 – 73 0B49H
29 11 – 74 0B4AH
30 11 – 75 0B4BH
31 11 – 76 0B4CH
32 11 – 77 0B4DH
33 11 – 78 0B4EH
34 11 – 79 0B4FH
35 11 – 80 0B50H
36 11 – 81 0B51H
37 11 – 82 0B52H
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 12 columnpair3 — PDF page 405

Source row Function Register No
1 12 – 00 High WORD: 2510H Low WORD: 2511H
2 12 – 01 0C01H
3 12 – 02 0C02H
4 12 – 03 0C03H
5 12 – 04 0C04H
6 12 – 05 0C05H
7 12 – 06 0C06H
8 12 – 07 0C07H
9 12 – 08 0C08H
10 12 – 09 0C09H
11 12 – 10 0C0AH
12 12 – 11 0C0BH
13 12 – 12 0C0CH
14 12 – 13 0C0DH
15 12 – 14 0C0EH
16 12 – 15 0C0FH
17 12 – 16 0C10H
18 12 – 17 0C11H
19 12 – 18 0C12H
20 12 – 19 0C13H
21 12 – 20 0C14H
22 12 – 21 0C15H
23 12 – 22 0C16H
24 12 – 23 0C17H
25 12 – 24 0C18H
26 12 – 25 0C19H
27 12 – 26 0C1AH
28 12 – 27 0C1BH
29 12 – 28 0C1CH
30 12 – 29 0C1DH
31 12 – 30 0C1EH
32 12 – 31 0C1FH
33 12 – 32 0C20H
34 12 – 33 0C21H
35 12 – 34 0C22H
36 12 – 35 0C23H
37 12 – 36 0C24H
38 12 – 37 0C25H
39 12 – 38 0C26H
40 12 – 39 0C27H
41 12 – 40 0C28H
42 12 – 41 0C29H
43 12 – 42 0C2AH
44 12 – 43 0C2BH
45 12 – 44 0C2CH
46 12 – 45 0C2DH

Manual — Parameter register mappings 7 — page 406

Manual reference: physical PDF page 406. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 12 columnpair1 — PDF page 406

Source row Function Register No
1 12 – 46 0C2EH
2 12 – 47 0C2FH
3 12 – 48 0C30H
4 12 – 49 0C31H
5 12 – 50 0C32H
6 12 – 51 0C33H
7 12 – 52 0C34H
8 12 – 53 0C35H
9 12 – 54 0C36H
10 12 – 55 0C37H
11 12 – 56 0C38H
12 12 – 57 0C39H
13 12 – 58 0C3AH
14 12 – 59 0C3BH
15 12 – 60 0C3CH
16 12 – 61 0C3DH
17 12 – 62 0C3EH
18 12 – 63 0C3FH
19 12 – 64 0C40H
20 12 – 65 0C41H
21 12 – 66 0C42H
22 12 – 67 0C43H
23 12 – 68 0C44H
24 12 – 69 0C45H
25 12 – 70 0C46H
26 12 – 71 0C47H
27 12 – 72 0C48H
28 12 – 73 0C49H
29 12 – 74 0C4AH
30 12 – 75 0C4BH
31 12 – 76 0C4CH
32 12 – 77 0C4DH
33 12 – 78 0C4EH
34 12 – 79 0C4FH
35 12 – 80 0C50H
36 12 – 81 0C51H
37 12 – 82 0C52H
38 12 – 83 0C53H
39 12 – 84 0C54H
40 12 – 85 0C55H
41 12 – 86 0C56H
42 12 – 87 0C57H
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 13 columnpair2 — PDF page 406

Source row Function Register No
1 13 – 00 0D00H
2 13 – 01 0D01H
3 13 – 02 0D02H
4 13 – 03 0D03H
5 13 – 04 0D04H
6 13 – 05 0D05H
7 13 – 06 0D06H
8 13 – 07 0D07H
9 13 – 08 0D08H
10 13 – 09 0D09H
11 13 – 10 0D0AH
12 13 – 11 0D0BH
13 13 – 12 0D0CH
14 13 – 13 0D0DH
15 13 – 14 0D0EH
16 13 – 15 0D0FH
17 13 – 16 0D10H
18 13 – 17 0D11H
19 13 – 18 0D12H
20 13 – 19 0D13H
21 13 – 20 0D14H
22 13 – 21 0D15H
23 13 – 22 0D16H
24 13 – 23 0D17H
25 13 – 24 0D18H
26 13 – 25 0D19H
27 13 – 26 0D1AH
28 13 – 27 0D1BH
29 13 – 28 0D1CH
30 13 – 29 0D1DH
31 13 – 30 0D1EH
32 13 – 31 0D1FH
33 13 – 32 0D20H
34 13 – 33 0D21H
35 13 – 34 0D22H
36 13 – 35 0D23H
37 13 – 36 0D24H
38 13 – 37 0D25H
39 13 – 38 0D26H
40 13 – 39 0D27H
41 13 – 40 0D28H
42 13 – 41 0D29H
43 13 – 42 0D2AH
44 13 – 43 0D2BH
45 13 – 44 0D2CH
46 13 – 45 0D2DH

Parameter register map Group 13 columnpair3 — PDF page 406

Source row Function Register No
1 13 – 46 0D2EH
2 13 – 47 0D2FH
3 13 – 48 0D30H
4 13 – 49 0D31H
5 13 – 50 0D32H
6 13 – 46 0D2EH
7 13 – 47 0D2FH
8 13 – 48 0D30H
9 13 – 49 0D31H
10 13 – 50 0D32H
11 13 – 51 0D33H
12 13 – 52 0D34H
13 13 – 53 0D35H
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 8 — page 407

Manual reference: physical PDF page 407. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 14 columnpair1 — PDF page 407

Source row Function Register No
1 14 – 00 0E00H
2 14 – 01 0E01H
3 14 – 02 0E02H
4 14 – 03 0E03H
5 14 – 04 0E04H
6 14 – 05 0E05H
7 14 – 06 0E06H
8 14 – 07 0E07H
9 14 – 08 0E08H
10 14 – 09 0E09H
11 14 – 10 0E0AH
12 14 – 11 0E0BH
13 14 – 12 0E0CH
14 14 – 13 0E0DH
15 14 – 14 0E0EH
16 14 – 15 0E0FH
17 14 – 16 0E10H
18 14 – 17 0E11H
19 14 – 18 0E12H
20 14 – 19 0E13H
21 14 – 20 0E14H
22 14 – 21 0E15H
23 14 – 22 0E16H
24 14 – 23 0E17H
25 14 – 24 0E18H
26 14 – 25 0E19H
27 14 – 26 0E1AH
28 14 – 27 0E1BH
29 14 – 28 0E1CH
30 14 – 29 0E1DH
31 14 – 30 0E1EH
32 14 – 31 0E1FH
33 14 – 32 0E20H
34 14 – 33 0E21H
35 14 – 34 0E22H

Parameter register map Group 14 columnpair2 — PDF page 407

Source row Function Register No
1 14 – 35 0E23H
2 14 – 36 0E24H
3 14 – 37 0E25H
4 14 – 38 0E26H
5 14 – 39 0E27H
6 14 – 40 0E28H
7 14 – 41 0E29H
8 14 – 42 0E2AH
9 14 – 43 0E2BH
10 14 – 44 0E2CH
11 14 – 45 0E2DH
12 14 – 46 0E2EH
13 14 – 47 0E2FH
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 15 columnpair3 — PDF page 407

Source row Function Register No
1 15 – 00 0F00H
2 15 – 01 0F01H
3 15 – 02 0F02H
4 15 – 03 0F03H
5 15 – 04 0F04H
6 15 – 05 0F05H
7 15 – 06 0F06H
8 15 – 07 0F07H
9 15 – 08 0F08H
10 15 – 09 0F09H
11 15 – 10 0F0AH
12 15 – 11 0F0BH
13 15 – 12 0F0CH
14 15 – 13 0F0DH
15 15 – 14 0F0EH
16 15 – 15 0F0FH
17 15 – 16 0F10H
18 15 – 17 0F11H
19 15 – 18 0F12H
20 15 – 19 0F13H
21 15 – 20 0F14H
22 15 – 21 0F15H
23 15 – 22 0F16H
24 15 – 23 0F17H
25 15 – 24 0F18H
26 15 – 25 0F19H
27 15 – 26 0F1AH
28 15 – 27 0F1BH
29 15 – 28 0F1CH
30 15 – 29 0F1DH
31 15 – 30 0F1EH
32 15 – 31 0F1FH
33 15 – 32 0F20H
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 9 — page 408

Manual reference: physical PDF page 408. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 16 columnpair1 — PDF page 408

Source row Function Register No
1 16 – 00 1000H
2 16 – 01 1001H
3 16 – 02 1002H
4 16 – 03 1003H
5 16 – 04 1004H
6 16 – 05 1005H
7 16 – 06 1006H
8 16– 07 1007H
9 16 – 08 1008H
10 16 – 09 1009H
11 16 – 10 100AH
12 16 – 11 100BH
13 16 – 12 100CH
14 16 – 13 100DH
15 16 – 14 100EH
16 16 – 15 100FH
17 16 – 16 1010H
18 16 – 17 1011H
19 16 – 18 1012H
20 16 – 19 1013H
21 16 – 20 1014H
22 16 – 21 1015H
23 16 – 22 1016H
24 16 – 23 1017H
25 16 – 24 1018H
26 16 – 25 1019H
27 16 – 26 101AH
28 16 – 27 101BH
29 16 – 28 101CH
30 16 – 29 101DH
31 16 – 30 101EH
32 16 – 31 101FH
33 16 – 32 1020H
34 16 – 33 1021H
35 16 – 34 1022H

Parameter register map Group 16 columnpair2 — PDF page 408

Source row Function Register No
1 16 – 35 1023H
2 16 – 36 1024H
3 16 – 37 1025H
4 ⟦blank source cell⟧ ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 17 columnpair3 — PDF page 408

Source row Function Register No
1 17 – 00 1100H
2 17 – 01 1101H
3 17 – 02 1102H
4 17 – 03 1103H
5 17 – 04 1104H
6 17 – 05 1105H
7 17 – 06 1106H
8 17 – 07 1107H
9 17 – 08 1108H
10 17– 09 1109H
11 17 – 10 110AH
12 17 – 11 110BH
13 17 – 12 110CH
14 17 – 13 110DH
15 17 – 14 110EH
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 10 — page 409

Manual reference: physical PDF page 409. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 18 columnpair1 — PDF page 409

Source row Function Register No
1 18 – 00 1200H
2 18 – 01 1201H
3 18 – 02 1202H
4 18 – 03 1203H
5 18 – 04 1204H
6 18 – 05 1205H
7 18 – 06 1206H
8 ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 19 columnpair2 — PDF page 409

Source row Function Register No
1 19 – 00 1300H
2 19 – 01 1301H
3 19 – 02 1302H
4 19 – 03 1303H
5 19 – 04 1304H
6 19 – 05 1305H
7 19 – 06 1306H
8 19 – 07 1307H
9 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 20 columnpair3 — PDF page 409

Source row Function Register No
1 20 – 00 1400H
2 20 – 01 1401H
3 20 – 02 1402H
4 20 – 03 1403H
5 20 – 04 1404H
6 20 – 05 1405H
7 20 – 06 1406H
8 20 – 07 1407H
9 20 – 08 1408H
10 20 – 09 1409H
11 20 – 10 140AH
12 20 – 11 140BH
13 20 – 12 140CH
14 20 – 13 140DH
15 20 – 14 140EH
16 20 – 15 140FH
17 20 – 16 1410H
18 20 – 17 1411H
19 20 – 18 1412H
20 20 – 19 1413H
21 20 – 20 1414H
22 20 – 21 1415H
23 20 – 22 1416H
24 20 – 23 1417H
25 20 – 24 1418H
26 20 – 25 1419H
27 20 – 26 141AH
28 20 – 27 141BH
29 20 – 28 141CH
30 20 – 29 141DH
31 20 – 30 141EH
32 20 – 31 141FH
33 20 – 32 1420H
34 20 – 33 1421H
35 20 – 34 1422H
36 20 – 35 1423H
37 20 – 36 1424H
38 20 – 37 1425H
39 20 – 38 1426H
40 20 – 39 1427H
41 20 – 40 1428H
42 20 – 41 1429H
43 20 – 42 142AH
44 20 – 43 142BH
45 20 – 44 142CH

Manual — Parameter register mappings 11 — page 410

Manual reference: physical PDF page 410. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 21 columnpair1 — PDF page 410

Source row Function Register No
1 21 – 00 1500H
2 21 – 01 1501H
3 21 – 02 1502H
4 21 – 03 1503H
5 21 – 04 1504H
6 21 – 05 1505H
7 21 – 06 1506H
8 21 – 07 1507H
9 21 – 08 1508H
10 21 – 09 1509H
11 21 – 10 150AH
12 21 – 11 150BH
13 21 – 12 150CH
14 21 – 13 150DH
15 21 – 14 150EH
16 21 – 15 150FH
17 21 – 16 1510H
18 21 – 17 1511H
19 21 – 18 1512H
20 21 – 19 1513H
21 21 – 20 1514H
22 21 – 21 1515H
23 21 – 22 1516H
24 21 – 23 1517H
25 21 – 24 1518H
26 21 – 25 1519H
27 21 – 26 151AH
28 21 – 27 151BH
29 21 – 28 151CH
30 21 – 29 151DH
31 21 – 30 151EH
32 21 – 31 151FH
33 21 – 32 1520H
34 21 – 33 1521H
35 21 – 34 1522H
36 21 – 35 1523H
37 21 – 36 1524H
38 21 – 37 1525H
39 21 – 38 1526H
40 21 – 39 1527H
41 21 – 40 1528H
42 21 – 41 1529H
43 21 – 42 152AH
44 21 – 43 152BH
45 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter register map Group 22 columnpair2 — PDF page 410

Source row Function Register No
1 22 – 00 1600H
2 22 – 01 1601H
3 22 – 02 1602H
4 22 – 03 1603H
5 22 – 04 1604H
6 22 – 05 1605H
7 22 – 06 1606H
8 22 – 07 1607H
9 22 – 08 1608H
10 22 – 09 1609H
11 22 – 10 160AH
12 22 – 11 160BH
13 22 – 12 160CH
14 22 – 13 160DH
15 22 – 14 160EH
16 22 – 15 160FH
17 22 – 16 1610H
18 22 – 17 1611H
19 22 – 18 1612H
20 22 – 19 1613H
21 22 – 20 1614H
22 22 – 21 1615H
23 22 – 22 1616H
24 22 – 23 1617H
25 22 – 24 1618H
26 22 – 25 1619H
27 22 – 26 161AH
28 22 – 27 161BH
29 22 – 28 161CH
30 22 – 29 161DH
31 22 – 30 161EH
32 22 – 31 161FH
33 22 – 32 1620H
34 22 – 33 1621H
35 22 – 34 1622H
36 22 – 35 1623H
37 22 – 36 1624H
38 22 – 37 1625H
39 22 – 38 1626H
40 22 – 39 1627H
41 22 – 40 1628H
42 22 – 41 1629H
43 22 – 42 162AH
44 22 – 43 162BH
45 22 – 44 162CH

Parameter register map Group 22 columnpair3 — PDF page 410

Source row Function Register No
1 22 – 45 162DH
2 22 – 46 162EH
3 22 – 47 162FH
4 22 – 48 1630H
5 22 – 49 1631H
6 22 – 50 1632H
7 22 – 51 1633H
8 22 – 52 1634H
9 22 – 53 1635H
10 22 – 54 1636H
11 22 – 55 1637H
12 22 – 56 1638H
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter register mappings 12 — page 411

Manual reference: physical PDF page 411. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Exact physical columnpair; mappings are not inferred from numerical sequence. Trailing blank cells retained. 12–00 special High/Low WORD mapping retained in one original cell. Duplicate source rows retained as separate row identities.

Parameter register map Group 23 columnpair1 — PDF page 411

Source row Function Register No
1 23 – 00 1700H
2 23 – 01 1701H
3 23 – 02 1702H
4 23 – 03 1703H
5 23 – 04 1704H
6 23 – 05 1705H
7 23 – 06 1706H
8 23 – 07 1707H
9 23 – 08 1708H
10 23 – 09 1709H
11 23 – 10 170AH
12 23 – 11 170BH
13 23 – 12 170CH
14 23 – 13 170DH
15 23 – 14 170EH
16 23 – 15 170FH
17 23 – 16 1710H
18 23 – 17 1711H
19 23 – 18 1712H
20 23 – 19 1713H
21 23 – 20 1714H
22 23 – 21 1715H
23 23 – 22 1716H
24 23 – 23 1717H
25 23 – 24 1718H
26 23 – 25 1719H
27 23 – 26 171AH
28 23 – 27 171BH
29 23 – 28 171CH
30 23 – 29 171DH
31 23 – 30 171EH
32 23 – 31 171FH
33 23– 32 1720H
34 23– 33 1721H
35 23– 34 1722H
36 23 – 35 1723H
37 23 – 36 1724H
38 23 – 37 1725H
39 23 – 38 1726H

Parameter register map Group 23 columnpair2 — PDF page 411

Source row Function Register No
1 23 – 39 1727H
2 23 – 40 1728H
3 23 – 41 1729H
4 23 – 42 172AH
5 23 – 43 172BH
6 23 – 44 172CH
7 23 – 45 172DH
8 23 – 46 172EH
9 23 – 47 172FH
10 23 – 48 1730H
11 23 – 49 1731H
12 23 – 50 1732H
13 23 – 51 1733H
14 23 – 52 1734H
15 23 – 53 1735H
16 23 – 54 1736H
17 23 – 55 1737H
18 23 – 56 1738H
19 23 – 57 1739H
20 23 – 58 173AH
21 23 – 59 173BH
22 23 – 60 173CH
23 23 – 61 173DH
24 23 – 62 173EH
25 23 – 63 173FH
26 23 – 64 1740H
27 23 – 65 1741H
28 23 – 66 1742H
29 23 – 67 1743H
30 23 – 68 1744H
31 23 – 69 1745H
32 23 – 70 1746H
33 23 – 71 1747H
34 23 – 72 1748H
35 23 – 73 1749H
36 23– 74 174AH
37 23– 75 174BH
38 23– 76 174CH
39 23– 77 174DH

Parameter register map Group 23 columnpair3 — PDF page 411

Source row Function Register No
1 23– 78 174EH
2 23– 79 174FH
3 ⟦blank source cell⟧ ⟦blank source cell⟧
4 ⟦blank source cell⟧ ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Fault diagnosis overview, reset methods and overcurrent faults — page 412

Manual reference: physical PDF page 412. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 5 Fault Diagnosis and Troubleshooting

5.1 General Overview The inverter is equipped with fault detection, warning, and self-diagnostic functions. When a fault is detected, the corresponding fault code is displayed on the digital operator, and the fault output relay is activated. The inverter output is cut off, and the motor coasts to a stop (in some cases, the stop method is configurable). When a warning or self-diagnostic alert is detected, a warning/self-diagnostic code appears on the digital operator, but the fault output relay does not activate. Once the warning condition is cleared, the system will automatically return to its normal state.

5.2 Fault Detection Function If a fault occurs, refer to Table 5.1 to identify possible causes and take the appropriate corrective actions. To restart the system, use one of the following methods: 1. Assign one of the multi-function digital input terminals (03-00 to 03-07) to code 17 (Fault Reset), and set the reset signal to ON. 2. Press the [Reset] key on the digital operator. 3. Power off the main circuit supply and then power it back on. When a fault occurs, relevant fault data is stored in the Monitoring Function Group (Group 12) and the Maintenance Function Group (Group 13).

Table 5.1 Fault Messages and Corrective Actions

Literal supplier fault instructions. LED text retained; seven-segment images remain in original. Cross-page FB continuation on415 and CF01 display continuation417 explicitly recorded. Shared STO/STO2 row kept together.

Table 5.1 fault display, causes and corrective actions — PDF page 412

Source row LED display Description Possible Cause Corrective Action
1 OC (Over- current) Over-current: The inverter output current exceeds the over-current detection level (approximately 200% of the rated current). ‧ Acceleration/deceleration time is too short. ‧ Operation of magnetic switch on inverter output side. ‧ Use of special motor or a motor rated above the inverter capacity. ‧ Short circuit or grounding fault occurred. ‧ Extend acceleration/ eceleration time ‧ Check load wiring ‧ Remove motor and test inverter operation
2 OCA (Over- current) Over-current during acceleration 1. Acceleration time setting is too short 2. Motor capacity exceeds inverter capacity 3. Motor winding shorted to casing 4. Motor wiring shorted to ground 5.IGBT Module failure 1. Set a longer acceleration time 2. Replace with inverter of appropriate capacity 3. Repair motor 4. Inspect wiring 5. Replace IGBT module
3 OCC (Over- current) Over-current during constant speed 1. Sudden change in load 2. Sudden change in power supply 1. Increase inverter capacity 2. Add reactor to power input side
4 OCD (Over- current) Over-current during deceleration Deceleration time is too short Set a longer deceleration time
5 SC (Short circuit) Short circuit: Short circuit on inverter output or load ‧ Short circuit or ground fault occurred (08-23 = 1) Caused by motor failure, insulation degradation, damaged cables, resulting in contact or ground short. ‧ Confirm load wiring

Manual — Ground, voltage, phase, heat and overload faults — page 413

Manual reference: physical PDF page 413. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal supplier fault instructions. LED text retained; seven-segment images remain in original. Cross-page FB continuation on415 and CF01 display continuation417 explicitly recorded. Shared STO/STO2 row kept together.

Table 5.1 fault display, causes and corrective actions — PDF page 413

Source row LED display Description Possible Cause Corrective Action
1 GF (Ground Fault) Ground fault: Ground fault current on output side exceeds 50% of inverter rated output current and 08-23 = 1 (GF function enabled). ‧ Motor grounding or DCCT current sensor failure. ‧ This protects equipment but not personnel. ‧ Check motor wiring and wiring impedance.
2 OV (Over- voltage) Main circuit over-voltage: DC voltage exceeds over-voltage detection level –- 200V class: 410Vdc 400V class: 820Vdc ‧ Deceleration time too short, resulting in excessive regenerative energy. ‧ Input voltage too high ‧ Use of power factor correction capacitors. ‧ Extend deceleration time ‧ Check input circuit and reduce input voltage to meet specifications ‧ Remove power factor correction capacitors.
3 UV (Undervoltage) Main circuit undervoltage: DC bus voltage falls below undervoltage detection level, or DC bus magnetic contactor not engaged while inverter is operating. Approx. 200V class: 190Vdc 400V class: 380Vdc (This detection value is adjustable via 07-13). ‧ Input voltage too low. ‧ Input power phase loss. ‧ Acceleration time set too short. ‧ Excessive fluctuation in input voltage. ‧ DC bus magnetic contactor not engaged or feedback signal abnormal. ‧ Check input circuit and power voltage. ‧ Extend acceleration time.
4 IPL Input Phase Loss Input phase loss: Phase loss or large voltage imbalance on inverter input side When 08-09=1 (enabled), this fault is detected. ‧ Input phase loss occurred ‧ Loose screws on R/L1, S/L2, or T/L3 terminals ‧ Excessive fluctuation in input voltage. ‧ Voltage imbalance between phases ‧ Aging of inverter’s internal main circuit capacitors. ‧ Verify main circuit power wiring is correct. ‧ Check if terminal screws are loose. ‧ Ensure stable power voltage or disable input phase loss detection. ‧ Replace circuit board or inverter
5 OPL (Output Phase Loss) Output phase loss: Inverter output phase loss Fault detection enabled when 08- 10=1. ‧ Damaged output cable or internal motor fault. ‧ Loose or missing screws on R/L1, S/L2, or T/L3 terminals. ‧ Motor capacity is below 10% of inverter rated output. ‧ Inspect motor wiring. ‧ Check motor and inverter capacity.
6 OH1 Heatsink overheat Heatsink overheat: Heatsink temperature is too high. If the heatsink overheat fault occurs three times within five minutes, the fault cannot be reset until 10 minutes have passed. ‧ Ambient temperature is too high. ‧ Cooling fan has stopped. ‧ Carrier frequency setting is too high. ‧ Check ambient temperature around inverter. ‧ Check for dust or dirt in fan or heatsink. ‧ Check carrier frequency setting.
7 OL1 Motor overload Motor overload: Motor overload protection activates according to the internal motor overload curve when 08- 05 = xxx1 (motor overload protection enabled). ‧ Voltage setting in V/F mode is too high, causing motor overexcitation. ‧ Incorrect motor rated current setting (02- 01). ‧ Motor is overloaded. ‧ Check V/F mode. ‧ Check motor rated current. ‧ Check load level and duty cycle time.
8 OL2 Frequency converter overload Frequency converter overload: Inverter overload protection activates according to the internal inverter overload curve. After the frequency converter overload fault is cleared, an frequency converter overload warning will appear. If the fault occurs four times within five minutes, a 4-minute wait is required before fault reset. ‧ Voltage setting in V/F mode is too high. ‧ Inverter capacity is too small. ‧ Motor is overloaded. ‧ Check V/F mode. ‧ Replace with a higher-capacity inverter. ‧ Check load level and duty cycle time.

Manual — Torque, speed, PG, communications and feedback faults — page 414

Manual reference: physical PDF page 414. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal supplier fault instructions. LED text retained; seven-segment images remain in original. Cross-page FB continuation on415 and CF01 display continuation417 explicitly recorded. Shared STO/STO2 row kept together.

Table 5.1 fault display, causes and corrective actions — PDF page 414

Source row LED display Description Possible Cause Corrective Action
1 OT Over-torque detection Over-torque detection: If the inverter output torque exceeds 08-15 (over-torque detection level) and the duration exceeds 08-16, the inverter triggers base block (08-14=0). Mechanical load is too large ‧ Check application or operating status ‧ Check whether 08-15 and 08- 16 are properly set
2 UT Under-torque detection Under-torque detection: If the inverter output torque drops below 08-19 (under-torque detection level) and the duration exceeds 08-20, the inverter triggers base block (08-18=0). Mechanical load has suddenly reduced (e.g., broken belt) ‧ Check application or operating status ‧ Check whether 08-19 and 08- 20 are properly set
3 run Motor 1/motor 2 switching Motor 1 and Motor 2 were switched during operation 1. Motor 2 switch command was input during operation. 2. Motor switching occurred during operation. ‧ Modify the sequence control so that motor switching only occurs when stopped.

Table 5.1 fault display, causes and corrective actions — PDF page 414

Source row LED display Description Possible Cause Corrective Action
1 OS Overspeed Motor overspeed: ‧ Motor speed exceeds 20-20 (PG overspeed level) and lasts longer than 20-21 (PG overspeed time). ‧ Per 20-19 (=0 or 1), inverter stops. ‧ This fault is valid only in V/F+PG and SV control modes (00-00 = 1, 3, or 4). ‧ Motor speed can be monitored via 12-22. ‧ Speed reference is too high. ‧ Excessive overshoot or insufficient response. ‧ Check whether speed reference gain and settings for 20-20 and 20- 21 are appropriate. ‧ Adjust ASR parameters in Group 21.
2 PGO PG open circuit PG open circuit detection: ‧ When inverter is operating, PG pulse not detected within PG open detection time (20- 26). ‧ Per 20-25 (=0 or 1), inverter stops. ‧ This fault is valid only in V/F+PG and SV control modes (00-00 = 1, 3, or 4). ‧ Incorrect PG wiring ‧ No power to PG ‧ PG cable is broken ‧ Brake mechanism activated ‧ Check PG wiring. ‧ Check PG power supply. ‧ Check PG wiring ‧ Check motor actuation mechanism.
3 DEV Speed deviation Speed deviation: ‧ Motor speed deviation exceeds 20-23 (PG speed deviation level) for a time longer than 20-24 (PG deviation time). ‧ Per 20-22 (=0 or 1), inverter stops ‧ This fault is valid only in V/F+PG and SV control modes (00-00 = 1, 3, or 4). ‧ Load is too high. ‧ Load is locked. (e.g., brake mechanism activated). ‧ PG wiring error. ‧ PG parameters (Group 20) are incorrectly set. ‧ Acceleration/deceleration time is too short. ‧ Check mechanical load. ‧ Check if brake mechanism is activated or reduce the load. ‧ Check PG wiring. ‧ Verify 20-23 and 20-24 parameter settings. ‧ Extend acceleration/deceleration time.
4 CE Communication error Modbus communication error: ‧ No communication received beyond 09-06 (communication timeout setting). ‧ Per 09-07 (= 0 to 2), this fault protection is triggered. ‧ Connection lost or host has stopped communicating. ‧ Check all connections and verify all client software settings.
5 FB PID feedback disconnected PID feedback disconnected: When PID feedback disconnection detection is enabled (10-11 = 2, motor coast-to-stop), and PID feedback input < PID disconnection detection level ‧ PID feedback sensor is malfunctioning or not installed properly. ‧ Check whether PID feedback configuration is correct. ‧ Ensure proper installation and PID feedback signal is functioning normally.

Manual — Feedback continuation and safety/external faults — page 415

Manual reference: physical PDF page 415. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

(10-12) for longer than the detection time (10-13).

Literal supplier fault instructions. LED text retained; seven-segment images remain in original. Cross-page FB continuation on415 and CF01 display continuation417 explicitly recorded. Shared STO/STO2 row kept together.

Table 5.1 fault display, causes and corrective actions — PDF page 415

Source row LED display Description Possible Cause Corrective Action
1 STO Safety switch STO2 Safety switch Inverter safety switch ‧ Check whether F1 and F2 on the inverter control board are shorted with SG. (Applicable to standard version S) ‧ 08-30 is set to 1 for free-run stop, and digital terminal switch (58) is open. ‧ Check whether F1 and F2 are shorted with SG. (Applicable to standard version S) ‧ Check whether digital terminal (58) is open.

Table 5.1 fault display, causes and corrective actions — PDF page 415

Source row LED display Description Possible Cause Corrective Action
1 SS1 Safety switch Inverter safety switch ‧ 08-30 is set to 0 for deceleration stop, and digital terminal switch (58) is open. ‧ Check whether digital terminal (58) is open.
2 EF0 External fault 0 External fault (Modbus) ‧ Bit 2 of Modbus register 0x2501 is set to "1" ‧ Check external fault cause ‧ Reset bit 2 of Modbus register 0x2501

Manual — Shared terminal external faults and control/operator faults — page 416

Manual reference: physical PDF page 416. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal supplier fault instructions. LED text retained; seven-segment images remain in original. Cross-page FB continuation on415 and CF01 display continuation417 explicitly recorded. Shared STO/STO2 row kept together.

All seven faults share the single cause/action cell below; no per-terminal condition invented.

Physical merged cells apply jointly to EF1 through EF7, S1 through S7. Parameter03-00 to03-07 literal; not proof of terminal availability for all frames.

Table 5.1 fault display, causes and corrective actions — PDF page 416

Source row LED display Description Possible Cause Corrective Action
1 CF07 Motor control fault Motor control fault Startup fault in SLV mode. ‧ Perform rotational motor auto- tuning. ‧ If rotational motor auto-tuning cannot be performed, execute stationary motor auto-tuning or increase the value of parameter 01- 08.
2 CF08 Motor control fault Motor control fault Startup or operation fault in PM SLV mode. ‧ Adjust and increase the value of parameter 22-10 appropriately. ‧ Re-execute 22-21 for auto-tuning. ‧ Check if the load is too large and whether the output torque limit needs to be increased.
3 CF00 Operator communicatio n error Digital operator data transmission error ‧ No data is transmitted between the LCM digital operator and inverter 5 seconds after power-on. ‧ Reconnect the digital operator connector ‧ Replace the control board
4 CF01 Operator communicatio n error 2 Digital operator data transmission error ‧ Data transmission between the digital operator and inverter fails for more than 3.5 seconds after power- on. ‧ Reconnect the digital operator connector ‧ Replace the control board

EF1–EF7 terminal fault identities — PDF page 416

Source row LED display Description
1 EF1 External Fault (S1) External fault (Terminal S1)
2 EF2 External Fault (S2) External Fault (Terminal S2)
3 EF3 External Fault (S3) External Fault (Terminal S3)
4 EF4 External Fault (S4) External Fault (Terminal S4)
5 EF5 External Fault (S5) External Fault (Terminal S5)
6 EF6 External Fault (S6) External fault (Terminal S6)
7 EF7 External Fault (S7) External Fault (Terminal S7)

Shared EF1–EF7 cause and action — PDF page 416

Source row Possible Cause Corrective Action
1 Received external fault input via multifunction digital input terminal. When 03-00 to 03-07 = 25 or 68 and external fault selection 08-24 = 0 or 1. ‧ Check external cause of fault. ‧ Reset external fault via multifunction digital input.

Manual — Operator continuation, pump faults and warning handling — page 417

Manual reference: physical PDF page 417. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.3 Warning / Self-Diagnosis Detection Function

When a warning is detected by the inverter, the digital operator will flash a warning code. Fault output contact does not activate. Once the warning clears, the system automatically returns to its original state. When a self-diagnostic error is detected (such as an invalid or conflicting parameter setting),the digital operator will display a self-diagnostic code. Fault output contact will not activate. The inverter cannot execute run commands until the parameters are correctly set. When a warning or self-diagnostic error occurs, refer to Table 5.2 to identify and correct the issue.

Literal supplier fault instructions. LED text retained; seven-segment images remain in original. Cross-page FB continuation on415 and CF01 display continuation417 explicitly recorded. Shared STO/STO2 row kept together.

Table 5.1 fault display, causes and corrective actions — PDF page 417

Source row LED display Description Possible Cause Corrective Action
1 PF Protection fault Occurs when OH1 fault appears three times within 5 minutes and no run command release is received via multifunction digital input terminal/communication. Run command via digital input/communication not removed. ‧ Remove run command from digital input/communication
2 TOL External overload External overload (Only active when fire mode is enabled) External overload input (e.g., fan overheat) received via multifunction digital input terminal. ‧ Check the cause of external overload. ‧ Reset external overload from multifunction digital input.
3 LOPBT Low flow fault Low flow fault. Feedback signal not connected ‧ Caused by HVAC flow feedback value falling below the set minimum flow limit. ‧ Check whether the feedback signal is properly connected. ‧ Verify if the flow feedback value is lower than the minimum limit (parameter 23‧51).
4 HIPBT High flow fault High flow fault. Caused by HVAC flow feedback value exceeding the set maximum flow limit. ‧ Check whether the feedback signal is correct. ‧ Verify if the flow feedback value exceeds the maximum limit (parameter 23‧48).
5 LPBFT Low pressure fault Low pressure fault. ‧ Feedback signal not connected. ‧ Caused by PUMP pressure feedback value falling below the set minimum pressure limit. ‧ Check whether the feedback signal is properly connected. ‧ Verify whether the feedback pressure is below the minimum pressure limit (parameter 23‧15).
6 OPBFT High pressure fault High pressure fault. Caused by the PUMP pressure feedback value exceeding the set maximum pressure limit. ‧ Check whether the feedback signal is correct. ‧ Verify whether the feedback pressure exceeds the maximum pressure limit (parameter 23‧12).
7 LSCFT Low suction fault Low suction fault. ‧ Caused by insufficient water in the outlet tank, resulting in low suction. ‧ PID error exceeds the PID error threshold or output current is below the suction current threshold. ‧ Check whether there is sufficient water in the outlet tank and whether water supply is normal. ‧ Verify whether PID error exceeds the PID error threshold or the output current is below the suction current threshold.
8 FBLSS PID feedback signal loss When 23-19 > 0, the inverter determines whether the feedback pressure is lower than (Operating Pressure Setting (23-02) × Pressure Loss Ratio (23-19)); if this condition persists beyond the Pressure Loss Detection Time (23- 18), a fault signal will be triggered. Excessively high pressure loss ratio setting in 23‧19 or improperly functioning/missing pressure sensor can cause fault. ‧ Check whether the pressure loss ratio set in 23‧19 is correct. ‧ Ensure the sensor is installed properly and the PID feedback signal is functioning normally.

Manual — Warning voltage, thermal and torque diagnostics — page 418

Manual reference: physical PDF page 418. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 5.2 Warnings / Self-Diagnostic Codes and Corrective Actions

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Table5.2 warnings and self-diagnostic actions — PDF page 418

Source row LED display Description Possible Cause Corrective Action
1 HPErr Incorrect model selection Inverter capacity setting error: Inverter capacity setting (13‧00) does not match the rated voltage. This inverter capacity setting (13‧00) does not match the hardware voltage class. Check that the inverter capacity setting (13‧00) matches the hardware voltage class.
2 OV (flashing) Over voltage Main circuit voltage: DC bus voltage exceeds the over-voltage detection level, and the inverter has shut down. 200V class: 410Vdc 400V class: 820Vdc Input power supply voltage is too high. ‧ Check the input power supply voltage.
3 UV (flashing) Low voltage Main circuit voltage: DC bus voltage falls below the undervoltage detection level, and the inverter has shut down. 200V class: 190Vdc 400V class: 380Vdc (The detection level can be set via 07‧13) ‧ Power supply voltage too low. .Momentary power loss occurred. ‧ Check the input power supply voltage. ‧ Check the input circuitry. ‧ Check the main circuit magnetic contactor (MC).
4 OH1 Heatsink overheat Heatsink overheat: Heatsink temperature is too high. If the overheat fault occurs three times within five minutes, a 10- minute wait is required before the fault can be reset. ‧ Ambient temperature is too high. ‧ Cooling fan has stopped. ‧ Carrier frequency setting is too high. ‧ Check ambient temperature around inverter. ‧ Check for dust or dirt in fan or heatsink. ‧ Check carrier frequency setting.
5 OH2 (flashing) Inverter overheat warning Inverter overheat warning: Inverter overheat warning signal is received via multifunction digital input terminals. (03-00 to 03-07 = 31) Multifunction digital input terminal receives an external overheat warning. ‧ Check external conditions.
6 OT (flashing) Over-torque detection Over-torque detection: Inverter output current exceeds 08-15 (overtorque detection level) for longer than the time set in 08-16. If 08-14 = 1, the inverter continues to operate. Mechanical load is too large ‧ Check application or machine operating condition. ‧ Check parameter settings for 08-15 and 08-16.

Manual — Undertorque and external-trip warning identities — page 419

Manual reference: physical PDF page 419. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Side-by-side vertical alignment does not assign individual cause/action paragraphs; original shared cell retained below.

Shared source scope: bb1–bb7

Table5.2 warnings and self-diagnostic actions — PDF page 419

Source row LED display Description Possible Cause Corrective Action
1 UT (flashing) Under-torque detection Under-torque detection: Inverter output current is lower than 08-19 (undertorque detection level) for longer than the time set in 08-20. If 08-18 = 1, the inverter continues to operate. Mechanical load has been momentarily removed. (e.g., broken belt) ‧ Check application or machine operating condition. ‧ Check parameter settings for 08-19 and 08-20.

Distinct identities with physically shared cause/action cells — PDF page 419

Source row LED display Description
1 bb1 (flashing) External trip External trip (Terminal S1)
2 bb2 (flashing) External trip External trip (Terminal S2)
3 bb3 (flashing) External trip External trip (Terminal S3)
4 bb4 (flashing) External trip External trip (Terminal S4)
5 bb5 (flashing) External trip External trip (Terminal S5)
6 bb6 (flashing) External trip External trip (Terminal S6)
7 bb7 (flashing) External trip External trip (Terminal S7)

Shared cause/action region 3 — PDF page 419

Source row Possible Cause Corrective Action
1 ‧ External trip signal received via multifunction digital input terminal. ‧ Remove the cause of the external trip.

Manual — Speed overload communications restart and emergency warnings — page 420

Manual reference: physical PDF page 420. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Side-by-side vertical alignment does not assign individual cause/action paragraphs; original shared cell retained below.

Shared source scope: OL1/OL2

Table5.2 warnings and self-diagnostic actions — PDF page 420

Source row LED display Description Possible Cause Corrective Action
1 DEV (flashing) Speed deviation Motor speed deviation: ‧ Motor speed deviation exceeds the level set in 20-23 (PG Speed Deviation Level) and persists longer than the time set in 20-24 (PG Deviation Time). ‧ Per 20-22 (=0 or 1), inverter stops ‧ This fault is valid only in V/F+PG and SV control modes (00-00 = 1, 3, or 4). ‧ Load is too high. ‧ Load is locked. (e.g., brake mechanism activated). ‧ PG wiring error. ‧ PG parameters (Group 20) are incorrectly set. ‧ Acceleration/deceleration time is too short. ‧ Check mechanical load. ‧ Check if brake mechanism is activated or reduce the load. ‧ Check PG wiring. ‧ Verify whether parameters 20- 23, 20-24, and 20-28 are correctly set. ‧ Extend acceleration/deceleration time.
2 CE (flashing) Communication error Modbus communication error: ‧ When 09-07 = 3, communication data is not received for more than two seconds. ‧ Communication cable is disconnected. ‧ Host has stopped data transmission. Check all connections and verify all client software settings.
3 CLA Current Protection Level A Inverter Over-current Warning: Inverter current has reached Current Protection Level A. Inverter current is too high ‧ Motor is overloaded. Check the load size and operating duty cycle.
4 CLB Current Protection Level B Inverter Over-current Warning: Inverter current has reached Current Protection Level B. Inverter current is too high ‧ Motor is overloaded. Check the load size and operating duty cycle.
5 Retry (flashing) Retry Auto-restart has been activated and is displayed until the time set in 07-01 has elapsed. 07-01 Auto Restart Time ≠ 0 07-02 Auto Restart Attempts ≠ 0 Display will disappear after the auto restart time has elapsed.
6 ES (flashing) External emergency stop External emergency stop: The external emergency stop function is activated Any parameter between 03-00 to 03-08 is set to 14, and the corresponding digital input is triggered. ‧ Remove the cause of the external emergency stop. ‧ Turn off the run command and reset the multifunction digital input for external emergency stop.
7 OS (flashing) Motor overspeed Motor overspeed: ‧ Motor speed exceeds 20-20 ‧ Speed reference value is too high. ‧ Speed response overshoot or ‧ Check speed reference gain and verify settings of 20-20

Distinct identities with physically shared cause/action cells — PDF page 420

Source row LED display Description
1 OL1 Motor overload Motor overload: Motor overload protection is activated according to the motor internal overload curve when 0805 = xxx1 (Motor Overload Protection Enabled).
2 OL2 Frequency converter overload Frequency converter overload: Frequency converter overload fault previously occurred, and less than 4 minutes have passed since then (if 4 minutes have passed, this warning will automatically clear).

Shared cause/action region 3 — PDF page 420

Source row Possible Cause Corrective Action
1 ‧ Voltage setting in V/F mode is too high, causing motor overexcitation. ‧ Incorrect motor rated current setting (02-01). ‧ Motor is overloaded. ‧ Voltage setting in V/F mode is too high. ‧ Inverter capacity is too small. ‧ Motor is overloaded. ‧ Check V/F mode. ‧ Check motor rated current. ‧ Check load level and duty cycle time. ‧ Check V/F mode. ‧ Replace with a higher- capacity inverter. ‧ Check load level and duty cycle time.

Manual — Overspeed continuation and external-fault warning shared cells — page 421

Manual reference: physical PDF page 421. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Side-by-side vertical alignment does not assign individual cause/action paragraphs; original shared cell retained below.

Shared source scope: EF1–EF5 only

Shared source scope: EF6–EF7 source cells blank, no carry-down inferred

Table5.2 warnings and self-diagnostic actions — PDF page 421

Source row LED display Description Possible Cause Corrective Action
1 ⟦blank source cell⟧ (PG overspeed level) and lasts longer than 20-21 (PG overspeed time). ‧ This fault is valid only in V/F+PG and SV control modes (00-00 = 1, 3, or 4). insufficient response occurred. and 20-21. ‧ Adjust ASR settings (Group 20 parameters).
2 PGO (flashing) PG open circuit PG open circuit detection: ‧ When inverter is operating, PG pulse not detected within PG open detection time (20-26). ‧ Per 20-25 (=0 or 1), inverter stops. ‧ This fault is valid only in V/F+PG and SV control modes (00-00 = 1, 3, or 4). ‧ PG wiring error. ‧ PG power supply disconnected. ‧ PG signal line disconnected. ‧ Brake mechanism activated. ‧ Check PG wiring. ‧ Check PG power supply.

Distinct identities with physically shared cause/action cells — PDF page 421

Source row LED display Description
1 EF1 (flashing) External Fault (S1) External fault (Terminal S1)
2 EF2 (flashing) External Fault (S2) External fault (Terminal S2)
3 EF3 (flashing) External Fault (S3) External fault (Terminal S3)
4 EF4 (flashing) External Fault (S4) External fault (Terminal S4)
5 EF5 (flashing) External Fault (S5) External fault (Terminal S5)
6 EF6 (flashing) External Fault (S6) External fault (Terminal S6)
7 EF7 (flashing) External Fault (S7) External fault (Terminal S7)

Shared cause/action region 1 — PDF page 421

Source row Possible Cause Corrective Action
1 ‧ External fault input received via multifunction digital input terminal. ‧ When 03-00 to 03-05 is set to 25 or 68, and inverter external fault selection 08-24 = 2. ‧ Remove the cause of the external fault. ‧ Reset the external fault on the multifunction digital input.

Shared cause/action region 11 — PDF page 421

Source row Possible Cause Corrective Action
1 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Forward reverse conflict and feedback warnings — page 422

Manual reference: physical PDF page 422. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Table5.2 warnings and self-diagnostic actions — PDF page 422

Source row LED display Description Possible Cause Corrective Action
1 EF9 (flashing) Forward/reverse command error ‧ Both forward and reverse commands (in 2-wire mode) are input simultaneously for 0.5 seconds or more. ‧ Inverter will respond according to motor stop method set in 07- 09. ‧ After the error is cleared, the inverter returns to normal operation. Forward and reverse commands were input at the same time. (Refer to 2-wire mode operation) Check external control logic
2 FB (flashing) PID feedback disconnected PID feedback disconnected: PID feedback disconnection detection is activated (when 10-11 = 1); inverter continues to operate. Detection is based on the PID feedback disconnection level (10-12) and detection time (10-13). PID feedback signal (e.g., transducer) not functioning or incorrectly installed. ‧ Check whether the selected PID feedback method is correct. ‧ Ensure proper installation and correct operation of the PID feedback signal.

Manual — Unattended protection and parameter setting diagnostics — page 423

Manual reference: physical PDF page 423. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Table5.2 warnings and self-diagnostic actions — PDF page 423

Source row LED display Description Possible Cause Corrective Action
1 USP (flashing) Unattended protection Unattended Protection (USP) activated at power-on ‧ When the unattended protection function (set via multifunction digital input) is enabled at power-on, the inverter will not accept any run command. ‧ The inverter will not enter operation mode until the warning message is cleared. (Refer to the full manual for detailed explanation when 03- 00 to 03-08 = 50). ‧ Turn off the run command, perform a reset via terminal input (03-00 to 03-07 = 3), or press the RESET key on the digital operator. ‧ Turn off the USP signal and cycle the power.
2 SE01 Setting range error Parameter setting exceeds allowable range: When parameter value exceeds permitted range ‧ When parameter value exceeds permitted range. ‧ In some cases, the parameter setting depends on the values of other parameters (e.g., 1. 02-00 > 02-01, or 02-20 > 02-21; 2. 00-12 > 00-13; 3.00-07 = 1, 00- 05 and 00-06 are the same). 4. 02-03, 02-05, 02-06, or 02-22, 02-25, 02-26 do not conform to motor speed formula; 5.20-16 < 20-15 Check parameter settings.
3 SE02 Digital input terminal error Multifunciton digital input terminal error Errors in multifunction digital input terminal settings (03-00 to 03-07), such as: 1. Up/Down commands not configured as a pair (must be used together). 2. Up/Down commands (08 and 09) and ACC/DEC command (11) all set at the same time. 3. Speed Search 1 (19, Maximum Frequency) and Speed Search 2 (34, from Set Frequency) both enabled. 4. Both 2-wire and 3-wire modes set simultaneously in 03-00 to 03-07. Check parameter settings
4 SE03 V/f curve error V/f curve setting error ‧ V/f curve settings not configured in accordance with required structure: ① 01-02 > 01-12 >01-06 > (Fmax) (Fbase) (Fmid1) 01-08; (Fmin) ②01-16 > 01-24 > 01-20 > 01-22; (Fmax(2)) (Fbase(2)) (Fmid(1)) (Fmin(2)) Check V/f parameters.
5 SE05 PID Selection Error PID Selection Error ①Both 10-00 and 10-01 are set to 1 (AI1) or both are set to 2 (AI2) ②If 10-29 = 1 or 2 and 10-25 = 1 (reverse operation allowed) ③If 10-29 = 1 or 2 and 10-03 = 1xxxb (PID output + target value) ①Check the values of parameters 10-00 and 10-01. ②Check the values of parameters 10-29 and 10-25. ③Check the values of parameters 10-29 and 10-03.
6 SE07 PG Card Error PG Card configuration error in the inverter Possible Cause 1: PG card is not installed in the inverter Possible Cause 2: Incorrect setting of PM encoder type (22- 08) Cause 1: Check the PG card installation and control mode Cause 2: After setting the PM encoder type (22-08), power must be cycled.

Manual — PM PI hardware stop and encoder warning diagnostics — page 424

Manual reference: physical PDF page 424. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

PArEr

StP1

AdCEr

EPErr

bdErr

StP0

StP2

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Table5.2 warnings and self-diagnostic actions — PDF page 424

Source row LED display Description Possible Cause Corrective Action
1 SE08 PM motor mode error Pole alignment not performed in PMSV mode In PM motor mode, if pole alignment has not been performed, the inverter will flash for 3 seconds after issuing the Run command and then automatically clear the warning. Perform magnetic pole alignment.

Table5.2 warnings and self-diagnostic actions — PDF page 424

Source row LED display Description Possible Cause Corrective Action
1 SE09 Invalid PI setting Inverter PI configuration error Conflict between inverter PI selection (03-30) and PID source (10-00 and 10-01) Check PI selection (03-30) and PID source settings (10-00 and 10-01)
2 Parameter setting error Parameter setting error The inverter parameters are incorrectly configured. Please refer to the manual for proper settings, or this option may be invalid.
3 Direct start warning When parameter 07-04 is set to 1, the inverter cannot perform a direct start and a warning will be issued. This occurs when the external run terminal is connected and set as the run source, while 07-04 is set to 1. Disconnect and reconnect the external run terminal. After power-on, wait for the time defined by parameter 07- 05 before issuing the run command.
4 FIRE Forced operation mode Forced operation mode. ‧ When entering Fire mode, check whether a fire has occurred near the equipment. ‧ Confirm if the area around the equipment is affected by fire. If this is a false trigger, power off and reset the system.
5 ADC Voltage Error Abnormal voltage level on the control board This may be caused by abnormal input voltage, excessive electrical noise, or a faulty control board. Check the input voltage signal and the voltage level on the control board.
6 EEPROM Storage error EEPROM data storage is faulty 1. Peripheral circuits of the EEPROM are faulty. 2. An error occurred during parameter check at power-on. 3. Both the DI error signal and the reset signal were activated at the same time. ‧ After initialization, power cycle the inverter. If the warning reappears, replace the circuit board or check whether there is a conflict on the DI input terminals.
7 Control Board Error Mismatch between control board and program Mismatch between control board and program. Mismatch between the control board and the program, please replace the control board.
8 Zero Speed Stop Warning There is a run signal, but the frequency command is lower than the minimum output frequency (01-08), and DC braking is not active. The frequency command is lower than the minimum motor output frequency. Adjust the frequency command. Note: If the frequency source (00-05) is set to digital operator, adjust the 0-speed frequency setting at 05-01.
9 External Stop Warning When 00-02 (main run command source) is set to external control, and the inverter is stopped using the digital operator while the run signal is active. Using the digital operator to stop while external run command is active. Remove the external run command.
10 Encoder Error Warning An encoder signal error was detected during motor auto- Encoder signal abnormal. 1. Check encoder wiring. 2. Ensure 17-07 (PG pulse

Manual — Encoder continuation, direction password and life warnings — page 425

Manual reference: physical PDF page 425. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

EnC

runEr

LOC

Err2

CyErr

FLIFE

ILIFE

Literal warning table. OS continues420→421, encoder warning424→425, HIPB425→426. Source code images separate from native labels. No assumed engineering validity.

Table5.2 warnings and self-diagnostic actions — PDF page 425

Source row LED display Description Possible Cause Corrective Action
1 ⟦blank source cell⟧ rotation tuning while a PG card was connected. ⟦blank source cell⟧ count) matches the encoder. 3. Replace the encoder. Note: Encoder errors do not affect the results of motor auto-tuning. Users may adjust 20-27 (PG pulse count) and 20-28 (PG rotation direction) manually without re- running motor auto-tuning.
2 Run Direction Error Warning The locked motor direction (11-00) differs from the current external run direction. Check whether 11-00 (motor direction lock command) is opposite to the direction issued by external DI control, JOG, or three-wire mode. Correct the 11-00 motor direction lock command to match the current direction command issued via external control DI, JOG, or three-wire operation.
3 Parameter lock Parameter password is locked The parameter password function (13-07) is enabled Enter the correct password in parameter 13-07
4 Password setting error When using the password lock function, the second entered password does not match the first. When using the password lock function, the second entered password does not match the first. When using the password lock function, the second entered password matches the first.
5 Capacitor Life Warning Capacitor service life has expired The operating hours have exceeded 90% of the expected service life. Once this threshold is surpassed, a CyErr warning will appear. Replace the capacitor and contact the manufacturer to update the inverter’s operation time counter.
6 Fan Life Warning Fan service life has expired The operating hours have exceeded 90% of the expected service life. Once this threshold is surpassed, a FLIFE warning will appear. Replace the fan and contact the manufacturer to update the inverter’s operation time counter.
7 IGBT Life Warning IGBT service life has expired The operating hours have exceeded 90% of the expected service life. Once this threshold is surpassed, a ILIFE warning will appear. Replace the IGBT and contact the manufacturer to update the inverter’s operation time counter.
8 LFPB Low flow error Low flow error. ‧ Feedback signal not connected. ‧ Caused by HVAC flow feedback value falling below the set minimum flow limit. ‧ Check whether the feedback signal is properly connected. ‧Check whether the feedback flow is below the minimum flow limit value.
9 HFPB High flow error High flow error. Caused by the HVAC feedback flow value falling below the configured maximum flow limit. ‧ Check whether the feedback signal is correct. ‧ Verify that the feedback flow is below the maximum flow limit value.
10 L0PB Low pressure error Low pressure error. ‧ Feedback signal not connected. ‧ Caused by PUMP pressure feedback value falling below the set minimum pressure limit. ‧ Check whether the feedback signal is properly connected. ‧Verify that the feedback pressure is below the minimum pressure limit value.
11 HIPB High pressure error High pressure error. Caused by the pump feedback pressure value falling below the ‧ Check whether the feedback signal is correct.

Manual — Pump pressure warning continuation and internal communication diagnostics — page 426

Manual reference: physical PDF page 426. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

HIPb

FbLSS

First blank LED/description row continues HIPB425; raster display retained. PID-feedback fault wording remains as printed in warning table.

Table5.2 warning continuation — PDF page 426

Source row LED display Description Possible Cause Corrective Action
1 ⟦blank source cell⟧ ⟦blank source cell⟧ configured maximum pressure limit. ‧Verify that the feedback pressure is below the maximum pressure limit value.
2 LSCFT Low suction error Low suction pressure error. ‧ Caused by insufficient water in the outlet tank, resulting in poor suction. ‧ PID error exceeds the PID error threshold or output current is below the suction current threshold. ‧ Check whether there is sufficient water in the outlet tank and whether water supply is normal. ‧ Verify whether PID error exceeds the PID error threshold or the output current is below the suction current threshold.
3 PID feedback signal loss When 23-19 > 0, the inverter determines whether the feedback pressure is lower than (Operating Pressure Setting (23-02) × Pressure Loss Ratio (23-19)); if this condition persists beyond the Pressure Loss Detection Time (23-18), a fault signal will be triggered. If the pressure loss ratio (23-19) is enabled and set too high, it may trigger a fault. The feedback sensor may not be functioning correctly or is improperly installed. ‧ Check whether the pressure loss ratio (23-19) is set correctly. ‧ Ensure the sensor is installed properly and the PID feedback signal is functioning normally.
4 COPUP Pump communication Disconnection error Multi-pump communication error. Communication is disconnected or not connected properly among multiple connected pumps. Check whether the communication is functioning or if any connections are loose or faulty.
5 SE10 PUMP/HVAC Setting error Incorrect inverter PUMP/HVAC settings. ① Inverter pump option (23-02) > (23-03). ② Inverter HVAC option (23- 46) < (23-47). ‧ Check the inverter pump setting (23-02) and verify against the maximum pressure setting (23-03). ‧ Check the inverter HVAC setting (23-46) and verify against the maximum pressure setting (23-47).
6 CbEr1 Internal communication error 1 Internal communication error 1. Internal communication error. Power cycle the inverter. If the warning reappears, please contact the manufacturer for support.
7 CbEr2 Internal communication error 2 Internal communication error 2. Internal communication error. Power cycle the inverter. If the warning reappears, please contact the manufacturer for support.
8 CbEr3 Internal communication error 3 Internal communication error 3 Internal communication error. Power cycle the inverter. If the warning reappears, please contact the manufacturer for support.

Manual — General and PM motor autotuning errors — page 427

Manual reference: physical PDF page 427. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.4 Auto tuning error When an auto tuning error occurs, “AtErr” will be displayed on the digital operator and the motor will stop. The error code will be shown in parameter 17-11. The digital output fault contact will not activate. Refer to Table 5.3 to identify and correct the cause of the error.

Table 5.3 Auto Tuning Errors and Corrective Actions

5.5 PM Motor Auto Tuning Error When a PM motor auto tuning error occurs, the fault message “IPErr” (PM motor tuning failed) will appear on the digital operator and the motor will stop. The error information will be displayed in 22-18. The digital output fault contact will not activate. Refer to Table 5.4 to identify and correct the cause of the error.

Table 5.4 PM Motor Auto Tuning Errors and Corrective Actions

Error07 precedes06 in original; physical source identity maintained. 08 only rotating autotuning.

All five identities share one physical cause/action region below; no individual paragraph inference.

Single shared cell applies jointly to source02/03/04/05/07 identities.

Same Table5.4 continues427→428, codes01–10. Same numbered general-autotune codes in Table5.3 remain separate namespaces.

Table5.3 independent autotuning error rows — PDF page 427

Source row Error Description Cause Corrective Action
1 01 Motor Data Input Error ‧ Incorrect data entered for auto tuning ‧ Mismatch between motor output current and rated motor current ‧ Check the input data for auto tuning (17-00 to 17-09). ‧ Check the inverter capacity.
2 06 Motor Encoder Error Motor Encoder Noise Too High Confirm the motor rated current (02-01, 02-21).
3 08 Motor acceleration error (applicable only to rotating auto tuning). The motor failed to accelerate within the specified time (00- 14 = 20 sec). ∙ Increase the acceleration time (00-14). ‧ Disconnect the load connected to the motor.
4 09 Other Auto Tuning Errors Other auto tuning errors not included in ATE-01 to ATE-08 (e.g., no-load current exceeds 70%, rated current or torque exceeds 100% of reference). ‧ Check motor wiring. ∙ Check auto tuning input data.

Table5.3 errors02/03/04/05/07 identities — PDF page 427

Source row Error Description
1 02 Motor Line-to-Line Resistance R1 Tuning Error
2 03 Motor leakage inductance tuning error.
3 04 Motor rotor resistance R2 tuning error.
4 05 Motor Mutual Inductance Lm Tuning Error
5 07 Deadtime Compensation Detection Error

Table5.3 shared02/03/04/05/07 cause/action — PDF page 427

Source row Cause Corrective Action
1 ‧ Auto tuning did not complete within the designated time. ‧ Tuning result exceeded parameter limits. ‧ Motor current exceeded rated value. ‧ One phase of the inverter’s three-phase output is disconnected. ‧ Check the input data for auto tuning (17-00 to 17-09). ‧ Check motor wiring. ‧ Disconnect the load connected to the motor. ‧ Inspect the inverter’s current detection circuit, including the current sensor. ‧ Check motor wiring. ‧ Check motor installation.

Table5.4 PM motor autotuning errors — PDF page 427

Source row Error Description Cause Corrective Action
1 01 Stationary pole alignment failed ∙ Mismatch between motor output current and rated current ∙Check the auto tuning input data (22-02). ‧ Check the inverter capacity. ∙Check motor wiring.
2 02 No PG option card ∙Pole alignment cannot be performed without a PG option card ∙ Check whether the PM PG card is properly installed.
3 03 Rotating pole alignment forcibly stopped ∙ System abnormality ∙ Check if other protection functions are active.
4 04 Rotating pole alignment timeout ∙ Motor cannot rotate normally ∙ Check motor wiring.

Manual — PM autotuning continuation and general troubleshooting groups — page 428

Manual reference: physical PDF page 428. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.6 General troubleshooting methods

Same Table5.4 continues427→428, codes01–10. Same numbered general-autotune codes in Table5.3 remain separate namespaces.

Physical merged abnormal-condition label applies to this whole table. Shared action/checkpoint cells grouped at exact boundary, not duplicated or assigned arbitrarily. Single/three-phase instructions retain source scope.

Table5.4 PM motor autotuning errors — PDF page 428

Source row Error Description Cause Corrective Action
1 05 Loop tuning timeout ∙ System abnormality during loop tuning ∙ Check if other protection functions are active.
2 06 Encoder error ∙Excessive motor encoder noise ∙Check if the PG card ground is connected.
3 07 Warning ∙ Other motor tuning errors ‧ Check motor wiring. ∙ Check auto tuning input data
4 08 Abnormal current during rotating pole alignment ∙ Motor cannot rotate normally at low speed ∙PG card A and B phases may be reversed. You may redo the process, and the system will automatically adjust the wiring definitions. ∙Check motor wiring.
5 09 Current abnormal during loop adjustment ∙Mismatch between motor output current and rated current ∙Check the auto tuning input data (22-02). ‧ Check the inverter capacity.
6 10 Retry pole alignment and loop tuning ∙ Auto tuning not completed Retry pole alignment and loop tuning

General troubleshooting: Motor rotation direction is reversed — PDF page 428

Source row Checkpoint Handling procedure
1 Are the output terminal wirings correct? They must match the motor’s U, V, and W
2 Are the forward/reverse signal wirings correct? Check and correct the wiring

General troubleshooting: Motor cannot vary its speed — PDF page 428

Source row Checkpoint Handling procedure
1 Is the analog frequency input wiring correct? Check and correct the wiring
2 Is the operation mode setting correct? Check the operation mode and frequency settings 00-05 / 00-06
3 Is the load too heavy? Reduce the load

General troubleshooting: Motor speed is too high or too low — PDF page 428

Source row Checkpoint Handling procedure
1 Are the motor specifications (number of poles, voltage) correct? Check the motor specifications
2 Is the gear ratio correct? Check the gear ratio
3 Is the maximum output frequency setting correct? Check the maximum output frequency

General troubleshooting: Motor speed fluctuates abnormally during operation — PDF page 428

Source row Checkpoint Handling procedure
1 Is the load too heavy? Reduce the load
2 Is the load variation significant? To reduce load variation, increase inverter and motor capacity
3 Is there a phase loss in the input power supply? 1. For single-phase models, add an AC reactor on the input side 2. For three-phase input models, check the wiring

General troubleshooting: Motor does not operate — PDF page 428

Source row Checkpoint Handling procedure
1 Is the power supply voltage correctly connected to the inverter input terminals (is the charge indicator light on?) 1. Is the power turned on? 2. Turn off the power and then turn it on again 3. Check the power supply voltage level 4. Are the terminal screws properly tightened?
2 Does the inverter have voltage output? Turn off the power and then turn it on again
3 Is the load too heavy, causing the motor to stall? Reduce the load so the motor can operate
4 Is there an inverter fault? Has the forward/reverse run command been sent to the inverter? Refer to the fault indicator for troubleshooting and correct any abnormal wiring
5 Has the analog frequency setting been input? 1. Is the frequency input voltage setting correct? 2. Is the analog frequency input signal wiring correct?
6 Is the run mode setting correct? Set the run mode from the operator panel

Manual — Basic inverter fault troubleshooting flowchart — page 429

Manual reference: physical PDF page 429. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Inverter failure

Are the details of the failure known?

Are there other abnormalities besides burnouts, damages and blown fuses?

Are there burnouts or damages?

Abnormal signal is displayed

Check according to the abnormality content displayed

Is the DM of the main circuit normal?

Is the fuse normal?

Is the I.G.B.T of the main circuit normal?

Perform visual inspection of the control board and driver board

Are there any abnormalities in the appearance?

Replace the abnormal board

Power input

Is there any display or indicator light on the operator?

Are there any abnormalities displayed?

What is the content of the abnormality displayed? Check the abnormal record parameters

Go to the next page

What is the content of the abnormality displayed?

Is the DC input voltage of the control power normal?

Is the +5V of the control power normal?

Replace the control board and operation panel

Is the replaced control board normal?

Inverter failure (Thorough inspection is required)

Check the burned out or damaged component

Replace the DM

Replace the fuse

Replace the I.G.B.T

Replace the inrush current absorber

Check the terminals and wirings

Replace the driver board

5.7 Troubleshooting steps

5.7.1 Basic inverter fault troubleshooting

[Unlabelled source arrow]

Yes

No

Manual — Basic inverter fault troubleshooting continuation — page 430

Manual reference: physical PDF page 430. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Continuing from the previous page

Check the inverter parameters

Specify the operation control method

FWD/REV, the LED changes from flashing to being constantly lit

Replace the control board

Set the frequency command

Did the operator display the frequency?

Does the inverter have voltage output?

Is the control board normal after it was replaced?

Operate with the motor connected

Are there any abnormalities displayed?

Are the output currents of each phase balanced?

Inverter normal

Inverter failure(Thorough inspection required)

[Unlabelled source arrow]

No

Yes

Manual — OC and OL troubleshooting flowchart — page 431

Manual reference: physical PDF page 431. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When the inverter failure shows OC and OL.

Is the I.G.B.T of the main circuit normal?

Are there any damages on the appearance?

Inputpower.

Are there any abnormal indications?

Operation command input.

FWD, did the LED change from flashing to constantly lit?

Frequency command input.

Is the output frequency of the operator displayed?

Does the inverter have voltage output?

Operate with the motor connected

Are there any abnormalities displayed?

Are the output currents of each phase balanced?

Inverteroutputnormal.

Replace the I.G.B.T

Replace the abnormal boards

Replace the control board

Did it get better after the control board was replaced?

Inverter failure (Thorough inspection required)

Is the current detector normal?

Replace the current detector

5.7.2 OC, OL fault troubleshooting

[Unlabelled source arrow]

No

Yes

Manual — OV and LV troubleshooting flowchart — page 432

Manual reference: physical PDF page 432. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When the inverter failure shows OV and LV.

Is the main circuit fuse normal?

Are there any damages on the appearance?

Inputpower.

Are there any abnormal indications?

Operation command input.

FWD, did the LED change from flashing to constantly lit?

Frequency command input.

Is the output frequency of the operator displayed?

Does the inverter have voltage output?

Operate with the motor connected

Are there abnormal output values?

Are the output currents of each phase balanced?

Inverteroutputnormal.

Replace the main circuit fuse

Replace the abnormal boards

Replace the control board

Is the replaced control board normal?

Inverter failure (Thorough inspection required)

5.7.3 OV, LV fault troubleshooting

[Unlabelled source arrow]

No

Yes

Manual — Motor abnormality troubleshooting flowchart — page 433

Manual reference: physical PDF page 433. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor not rotating

Is a circuit breaker (MCCB) installed?

Can a circuit breaker be installed?

Is the input power voltage normal?

Is the “LED” light on?

Is the operation switch at the RUN position?

Is there output between the motor UVW?

Is the inverter output voltage balanced?

Motor overload, motor failure, poor wiring

Wiring short circuited

Power source abnormal, poor wiring

Inverter failure

Flip the operation switch to the “RUN” position

5.7.4 Motor abnormality troubleshooting

[Unlabelled source arrow]

No

Yes

Manual — Motor overheating troubleshooting flowchart — page 434

Manual reference: physical PDF page 434. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor overheated

Did the overload exceed the rated current?

Did it operate at low speed for long periods of time?

Is the inverter output voltage balanced?

Are there obstacles that hinders motor cooling?

Poor contact betweenthe inverter and the motor

Reduced the load and increase the inverter and motor capacities

Re-select the motor

Inverter failure

Remove the obstacles

Correct theplaces with poor connection

5.7.5 Motor overheating cause troubleshooting

[Unlabelled source arrow]

Yes

No

Manual — Motor uneven operation troubleshooting flowchart — page 435

Manual reference: physical PDF page 435. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor does not operate smoothly

Is it accelerating or decelerating?

Is the acceleration and deceleration time appropriate?

Is the inverter output voltage balanced?

Does the load change greatly?

Is there excessive vibration in the gears and other transmission parts?

Inverter failure

Increase acceleration and decelerationtime

Reduced the load and increase the inverter and motor capacities

Reduce the load change or add flywheels

Improve the mechanical system

5.7.6 Motor uneven operation cause troubleshooting

[Unlabelled source arrow]

Yes

No

Manual — Daily and periodic inspection checklist and safety wait — page 436

Manual reference: physical PDF page 436. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.8 Daily and periodic inspection checklist The inverter requires daily and periodic maintenance inspections to ensure stable and safe operation. The following are essential inspection items to ensure the stable and safe operation of the inverter. Wait at least 5 minutes after the keypad panel on the inverter turns off before conducting inspections to avoid injury from residual charge in the inverter's capacitors.

Merged source cells repeat only where their physical bounding box spans the inspection row; exact shared bbox retained. Blank frequency or method cells stay blank, not inferred. Section boundaries in header-context-dispositions. 436 safety wait applies to both pages.

Daily and periodic inspection checklist — PDF page 436

Source row Inspection item Inspection content Daily marker Yearly marker Inspection method Acceptance criteria Countermeasures
1 Operating environment around the equipment Is the ambient temperature and humidity within specified limits? ○ ⟦blank source cell⟧ Measure with thermometer and hygrometer Temperature: -10 to 40°C / 50°C Humidity: Below 95% RH Improve the working environment
2 Operating environment around the equipment Is there any accumulation of flammable materials nearby? ○ ⟦blank source cell⟧ Visual inspection No foreign objects Improve the working environment
3 Inverter Installation and Grounding Is there abnormal shaking or vibration of the equipment? ○ ⟦blank source cell⟧ Visual and auditory inspection No foreign objects Tighten mounting screws
4 Inverter Installation and Grounding Is the grounding resistance value within specification? ⟦blank source cell⟧ ○ Measure resistance with multimeter Below 100Ω for 220V units Improve grounding
5 Terminal block Are the tightened parts loose or shaking? ⟦blank source cell⟧ ○ Visual inspection; check screws with screwdriver No abnormalities Tighten or send for repair
6 Terminal block Is there any damage to terminal blocks, etc.? ⟦blank source cell⟧ ○ Visual inspection; check screws with screwdriver No abnormalities Tighten or send for repair
7 Terminal block Any signs of obvious rust? ⟦blank source cell⟧ ○ Visual inspection; check screws with screwdriver No abnormalities Tighten or send for repair
8 Check inverter internal wiring Any deformation or misalignment? ⟦blank source cell⟧ ○ Visual inspection No abnormalities Replace or send for repair
9 Check inverter internal wiring Is the wire insulation damaged? ⟦blank source cell⟧ ○ Visual inspection No abnormalities Replace or send for repair
10 Input power voltage Is the main circuit voltage normal? ○ ⟦blank source cell⟧ Measure voltage with multimeter Voltage within specification Improve power input
11 PCBs Any conductive metal scattered on the PCB? ⟦blank source cell⟧ ○ Visual inspection No abnormalities Remove debris or replace the circuit board
12 PCBs Are there signs of rust, discoloration, or scorching from overheating? ⟦blank source cell⟧ ○ Visual inspection No abnormalities Remove debris or replace the circuit board
13 Capacitors Any unusual odors or electrolyte leakage? ○ ⟦blank source cell⟧ Visual inspection No abnormalities Replace the capacitor or inverter
14 Capacitors Are there signs of swelling or bulging? ○ ⟦blank source cell⟧ Visual inspection No abnormalities Replace the capacitor or inverter
15 Power Components Is there an accumulation of dust or debris? ⟦blank source cell⟧ ○ Visual inspection No abnormalities Clean
16 Power Components Check the resistance between each terminal ⟦blank source cell⟧ ○ Measure with a multimeter No short or open circuits on the three-phase output Replace power components or inverter
17 Variable Resistors Any unusual odor or damage to insulation? ⟦blank source cell⟧ ○ Olfactory and visual inspection No abnormalities Replace variable resistor
18 Variable Resistors Are the resistor wires or connection terminals damaged? ⟦blank source cell⟧ ○ Visual inspection No abnormalities Replace variable resistor

Manual — Checklist continuation, maintenance and single-phase test diagram — page 437

Manual reference: physical PDF page 437. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.9 Maintenance To ensure long-term reliability, conduct regular inspections as outlined below. Always turn off the power and wait until the keypad display is off before starting maintenance (due to residual voltage in large internal capacitors).

  1. Maintenance items indicated below: ➢ Ensure the ambient temperature and humidity around the inverter are suitable, with proper ventilation and away from heat sources. ➢Inspect the internal components of the inverter and replace any deteriorated or damaged parts. ➢ Remove any internal dust or foreign matter. ➢ Check the grounding to ensure proper connection. ➢ Tighten all terminal screws, especially on the inverter’s power input and output sides.

(! Never perform insulation withstand voltage tests on the control circuit.)

  1. Insulation Withstand Voltage Testing Method Single-phase:

Inverter

L1(L)

L3(N)

T1

T2

T3

Insulation withstand voltage and impedance tester

Input power

Motor

Merged source cells repeat only where their physical bounding box spans the inspection row; exact shared bbox retained. Blank frequency or method cells stay blank, not inferred. Section boundaries in header-context-dispositions. 436 safety wait applies to both pages.

Daily and periodic inspection checklist — PDF page 437

Source row Inspection item Inspection content Daily marker Yearly marker Inspection method Acceptance criteria Countermeasures
1 Electromagnetic contactor Are the contact points operating normally? ○ ⟦blank source cell⟧ ⟦blank source cell⟧ No abnormalities Replace contactor
2 Electromagnetic contactor Are there unusual noises? ○ ⟦blank source cell⟧ Auditory inspection No abnormalities Replace contactor
3 Reactor Any unusual odor or noise? ○ ⟦blank source cell⟧ Olfactory and auditory inspection No abnormalities Replace reactor
4 Cooling Fan Any unusual noise or vibration? ⟦blank source cell⟧ ○ Auditory inspection No abnormalities Replace cooling fan
5 Cooling Fan Any deformation or burnt smell? ○ ⟦blank source cell⟧ Visual and olfactory inspection No abnormalities Replace fan
6 Cooling Fan Are the fan mounting screws loose? ⟦blank source cell⟧ ⟦blank source cell⟧ Visual inspection; check with screwdriver No abnormalities Tighten or send for repair
7 Cooling Fan Are any fan blades missing or damaged? ⟦blank source cell⟧ ⟦blank source cell⟧ Visual inspection No abnormalities Replace fan
8 Heat Sink Is there an accumulation of dust or debris? ○ ⟦blank source cell⟧ Visual inspection No abnormalities Remove dust and debris
9 Ventilation Ducts Are the air intake and exhaust openings blocked? ○ ⟦blank source cell⟧ Visual inspection No abnormalities Clean

Manual — Three-phase insulation test diagram labels — page 438

Manual reference: physical PDF page 438. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Three-phase:

Inverter

L1(L)

L3(N)

L2

T1

T2

T3

Insulation withstand voltage and impedance tester

Input power

Motor

Manual — Brake resistors: models, values and safety — page 439

Manual reference: physical PDF page 439. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 6 Peripheral Devices and Optional Items

6.1 Brake Resistor List For models E710 200V 0.5~7.5HP / 400V 1-10HP, brake transistors are built-in as standard.

Table 6.1 Brake Resistor List

*1: The minimum allowable brake resistance is the lowest resistance value that can be connected.

Note 1: When installing brake resistors, ensure all resistors are mounted outside the inverter in a location with proper ventilation for heat dissipation.

Note 2: The surface temperature of the resistor becomes very high, and the air flowing from the resistor is extremely hot. Therefore, materials near the brake resistors must be non-combustible, and appropriate protection should be implemented to prevent accidental contact with the resistor.

Physical merged voltage cells repeated only over rows actually spanned by source bounds. Header units exactly scoped. No cross-table model equivalence inferred; drawings retained in original. Two Number of Units Used columns on439 preserved separately.

Table 6.1 Brake Resistor List — PDF page 439

Source row Inverter V/phase HP KW Part Number Resistance Specification Number of Units Used (resistor) Single Resistor Specification (W/Ω); Dimensions (L×W×H) mm Number of Units Used (single resistor) Approximate braking torque 10%ED Minimum Allowable Brake Resistance *1 (Ω) Minimum Allowable Brake Resistance *1 (W)
1 200V 1 Ø /3 Ø 0.5 0.4 JNBR-150W400 150W/400Ω 1 150W/400Ω (251x28x60) 1 119 50 350
2 200V 1 Ø /3 Ø 1 0.75 JNBR-150W200 150W/200Ω 1 150W/200Ω (251x28x60) 1 119 50 350
3 200V 1 Ø /3 Ø 2 1.5 JNBR-150W100 150W/100Ω 1 150W/100Ω (251x28x60) 1 119 50 350
4 200V 1 Ø /3 Ø 3 2.2 JNBR-260W70 260W/70Ω 1 260W/70Ω (274x40x78) 1 115 50 350
5 200V 3 Ø 5 3.7 JNBR-390W40 390W/40Ω 1 390W/40Ω (395x40x78) 1 119 19 1000
6 200V 3 Ø 7.5 5.5 JNBR-520W30 520W/30Ω 1 520W/30Ω (400x50x100) 1 108 10 1600
7 400V 3 Ø 1 0.75 JNBR-150W750 150W/750Ω 1 150W/750Ω (251x28x60) 1 126 125 600
8 400V 3 Ø 2 1.5 JNBR-150W400 150W/400Ω 1 150W/400Ω (251x28x60) 1 119 125 600
9 400V 3 Ø 3 2.2 JNBR-260W250 260W/250Ω 1 260W/250Ω (274x40x78) 1 126 84 800
10 400V 3 Ø 5 3.7 JNBR-400W150 400W/1500Ω 1 400W/150Ω (395x40x78) 1 126 56 1200
11 400V 3 Ø 7.5 5.5 JNBR-600W130 600W/130Ω 1 600W/130Ω (395x40x78) 1 102 67 1000
12 400V 3 Ø 10 7.5 JNBR-800W100 800W/100Ω 1 800W/100Ω (535x60x110) 1 99 67 1000

Manual — AC reactor selection and input-only restriction — page 440

Manual reference: physical PDF page 440. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.2 AC Reactor

‧ If the power system capacity is significantly larger than the inverter capacity, or if the inverter is connected close to the power source (within 10 meters), or to improve the power factor on the power supply side, an external AC reactor may be added.

‧ Please select an AC reactor according to the table below.

Table 6.2 AC Reactor List

The AC reactors listed in the table above are for inverter input side use only. Do not connect them to the output side.

Physical merged voltage cells repeated only over rows actually spanned by source bounds. Header units exactly scoped. No cross-table model equivalence inferred; drawings retained in original. Two Number of Units Used columns on439 preserved separately.

Table 6.2 AC Reactor List — PDF page 440

Source row Model V/phase Model HP Model rated current (A) AC Reactor 3% Impedance Inductance Value (mH) AC Reactor rated current (A)
1 200V 1 Ø /3 Ø 0.5 2.8 2.1 8.5
2 200V 1 Ø /3 Ø 1 4.8 2.1 12
3 200V 1 Ø /3 Ø 2 7.5 1.1 19.0
4 200V 1 Ø /3 Ø 3 11 0.71 25.0
5 200V 3 Ø 5 17 0.53 20
6 200V 3 Ø 7.5 25 0.35 33.0
7 400V 3 Ø 1 2.7 8.4 4.5
8 400V 3 Ø 2 4.2 4.2 6
9 400V 3 Ø 3 5.5 3.6 7.5
10 400V 3 Ø 5 9 2.2 12
11 400V 3 Ø 7.5 13 1.42 17.0
12 400V 3 Ø 10 17 1.06 23.0

Manual — 200V-class AC reactor dimensions — page 441

Manual reference: physical PDF page 441. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.2.1 Dimensions of 200V-Class AC Reactors 1. Basis Standard: JEC-2210 (1990 edition) 2. Insulation Class: Class H 3. Phases: 3-phase 4. System Voltage: 200–240V 5. Insulation Resistance: Below 0.2–1.1kV, withstand voltage AC4000V/1 minute 6. Model: MR-DL (For Input Side) 7. External Dimensions

Figure 1

Figure 2

A B C D E F

U V W X Y Z A B C C1 D E F

Physical merged voltage cells repeated only over rows actually spanned by source bounds. Header units exactly scoped. No cross-table model equivalence inferred; drawings retained in original. Two Number of Units Used columns on439 preserved separately.

3 220V

Dimensions of 200V-Class AC Reactors — PDF page 441

Source row Voltage (V) Inductance value (mH) Rated current (A) A (mm) B (mm) C (mm) C1 (mm) D (mm) E (mm) F (mm) Approx. Weight (Kg) Figure No.
1 3 220V 1.70 15 155 150 100 75 7 60 60 4 1
2 3 220V 1.10 20 155 150 100 75 7 60 60 4 1
3 3 220V 0.85 25 180 140 120 90 7 90 60 6 2
4 3 220V 0.46 25 155 150 100 75 7 60 60 3.5 1
5 3 220V 0.34 40 180 140 120 90 7 90 60 6 2
6 3 220V 0.24 50 180 140 120 90 7 90 60 6 2

Manual — 400V-class AC reactor dimensions — page 442

Manual reference: physical PDF page 442. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.2.2 Dimensions of 400V-Class AC Reactors 1. Basis Standard: JEC-2210 (1990 edition) 2. Insulation Class: Class H 3. Phases: 3-phase 4. System Voltage: 380–600V 5. Insulation Resistance: Below 0.2–1.1kV, withstand voltage AC4000V/1 minute 6. Model: MR-DL (For Input Side) 7. External Dimensions

Figure 1

A B C D E F

Physical merged voltage cells repeated only over rows actually spanned by source bounds. Header units exactly scoped. No cross-table model equivalence inferred; drawings retained in original. Two Number of Units Used columns on439 preserved separately.

3 440V

Dimensions of 400V-Class AC Reactors — PDF page 442

Source row Voltage (V) Inductance value (mH) Rated current (A) A (mm) B (mm) C (mm) C1 (mm) D (mm) E (mm) F (mm) Approx. Weight (Kg) Figure No.
1 3 440V 4.90 5 155 150 95 70 7 60 55 3 1
2 3 440V 3.70 6.5 155 150 95 70 7 60 55 3 1
3 3 440V 2.90 8.5 155 150 95 70 7 60 55 3 1
4 3 440V 1.70 15 155 150 100 75 7 60 60 3.5 1
5 3 440V 1.20 25 155 150 100 75 7 60 60 4 1

Manual — Noise filters and zero-core applicability — page 443

Manual reference: physical PDF page 443. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: Final horizontal graph tick visibly10 without exponent; source clipping unresolved. No exponent inferred.

6.3 Noise filter A. Input-side Noise Filter ‧ E710 200V models require an external dedicated noise filter. 400V models also require an external dedicated noise filter to comply with the EN61800-3 standard. Alternatively, 400V models with built-in filters are available, which also comply with EN61800-3.

Table 6.3. Input-side Noise Filters

B. Zero-Phase Noise Filter (EMI Suppression Zero Core)

‧ Product Part Number: 4H000D0250001

‧ Choose the appropriate zero-phase noise filter based on the horsepower and cable diameter.

‧ Utilizing the high attenuation characteristics of the zero-phase noise filter (effective from the AM frequency range of 100 kHz to approximately 50 MHz, as shown in the attenuation characteristic curve below), this filter effectively suppresses radiated noise emitted by the inverter.

‧ The zero-phase noise filter can be installed on either the input or output side of the inverter. For installation, loop each phase wire through the core in the same direction for several turns—the more turns, the better the attenuation effect. If the wires are too thick to loop, pass the U, V, and W phase wires straight through the core in the same direction and use multiple zero-phase noise filters in series.

‧ Attenuation Characteristic (with 10 loops)

Attenuation (dB)

0 -10 -20 -30 -40

10¹

10²

10³

10⁴

Frequency (kHz)

Physical merged cells repeated only over source-spanned rows; placeholders, X and exact model suffix/spacing preserved. No dimension unit inferred where source header has none. No electrical compatibility inferred beyond explicit source model rows.

Table6.3 Input-side Noise Filters — PDF page 443

Source row Input Voltage Horsepower Noise filter Model No. Dimensions (unit not stated)
1 200V 1Ø/3Ø 0.5HP/1HP FN258HV-7-29 254*49*125
2 200V 1Ø/3Ø 2HP/3HP FN3258-16-45 264*45*70
3 200V 3Ø 5HP FN431-0036 275*100*90
4 200V 3Ø 7.5HP FN431-0036 275*100*90
5 400V 3Ø 1HP/2HP FN3258-16-45 264*45*70
6 400V 3Ø 3HP/5HP FN3258-16-45 264*45*70
7 400V 3Ø 7.5HP/10HP FN431-0036 275*100*90

Manual — Zero-core use case condition — page 444

Manual reference: physical PDF page 444. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

‧ Use Cases

Note: The U, V, and W wires must pass through the same ZERO CORE and be wound in the same direction to be effective.

Manual — Input power side fuse ratings — page 445

Manual reference: physical PDF page 445. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.4 Input Power Side Fuse Ratings

200V Class

400V Class

Fuse Type: Please select UL-compliant semiconductor fuses. Voltage Range: For 220V-class inverters, use 300V-class fuses. For 440V-class inverters, use 500V-class fuses.

Physical merged cells repeated only over source-spanned rows; placeholders, X and exact model suffix/spacing preserved. No dimension unit inferred where source header has none. No electrical compatibility inferred beyond explicit source model rows.

200V Class input power side fuse ratings — PDF page 445

Source row Model No. Horsepower KVA 100% Rated Output Current (A) 3-Phase Rated Input Current (A) 3-Phase Fuse Rating (A) Single-Phase Rated Input Current (A)
1 E710-2P5-H□E□ 0.5 1.9 2.8 2.9 16 5.0
2 E710-201-H□E□ 1 1.9 4.8 5.0 20 8.7
3 E710-202-H□S 2 3 7.5 7.9 32 13.7
4 E710-203-H□S 3 4.2 11 11.6 50 20.1
5 E710-205-H3S 5 6.7 17 17.9 50 X
6 E710-208-H3S 7.5 9.5 25 26.3 63 X

400V Class input power side fuse ratings — PDF page 445

Source row Model No. Horsepower KVA 100% Rated Output Current (A) Rated Input Current (A) Fuse Rating (A)
1 E710-401- H3E(F) 1 2.6 2.7 2.8 10
2 E710-402- H3E(F) 2 3.2 4.2 4.4 16
3 E710-403- H3S(F) 3 4.2 5.5 5.8 16
4 E710-405- H3S (F) 5 7 9 9.5 25
5 E710-408- H3S (F) 7.5 11.3 13 13.7 40
6 E710-410- H3S (F) 10 13.7 17 17.9 50

Manual — Extension cables and LCD operator dimensions — page 446

Manual reference: physical PDF page 446. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.5 Others A. Digital Operator Extension Cable ‧ The digital operator can be detached from the inverter unit and operated remotely using a digital operator extension cable. Available in four lengths: 1m, 2m, 3m, and 5m.

The installation dimensions of the externally mounted LCD digital operator (JN5-OP-F02) are shown below.

85.0

74.0

4-M3

130.0

119.0

15.5

9.9

21.5

21.2

9.0

20.6

Physical merged cells repeated only over source-spanned rows; placeholders, X and exact model suffix/spacing preserved. No dimension unit inferred where source header has none. No electrical compatibility inferred beyond explicit source model rows.

Digital Operator Extension Cable — PDF page 446

Source row Name Model No. Configuration
1 Digital Operator Extension Cable JN5-CB-01M Length: 1m
2 Digital Operator Extension Cable JN5-CB-02M Length: 2m
3 Digital Operator Extension Cable JN5-CB-03M Length: 3m
4 Digital Operator Extension Cable JN5-CB-05M Length: 5m

Manual — Copy module, wiring box, DIN rail and USB cable — page 447

Manual reference: physical PDF page 447. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

B. Copy Module (JN5-CU)

‧ Copy Function: When multiple E710 inverters of the same model require identical parameter settings, you can configure one inverter, store the parameters using the copy module, and then copy the saved parameters to other inverters, thus reducing repetitive manual setup.

Copy Module(JN5-CU)Dimensions and Appearance

6.6 NEMA1 Wiring Box ‧ To upgrade protection to NEMA1 level, it is recommended to purchase a NEMA1 wiring box and install it above or below the inverter.

6.7 DIN RAIL Accessories ‧ For DIN RAIL mounting (Frame 1 & 2 models only), it is recommended to purchase the DIN RAIL accessory and install it beneath the inverter.

6.8 RJ45 to USB Cable ‧ RJ45 to USB cable (JN5-CM-USB), length: 1.8 meters. Converts USB communication format to RS485 format, enabling communication between the inverter and PC (or other USB interface control devices), thereby enhancing inverter control flexibility.

85.0

62.0

14.2

22.7

180.0±1.5

45.5

11.6

12.3

Physical merged cells repeated only over source-spanned rows; placeholders, X and exact model suffix/spacing preserved. No dimension unit inferred where source header has none. No electrical compatibility inferred beyond explicit source model rows.

NEMA1 Wiring Box — PDF page 447

Source row Enclosure Model No.
1 1 JN7-NK-E01
2 2 JN7-NK-E02
3 3 JN7-NK-E03

DIN RAIL Accessories — PDF page 447

Source row Enclosure Model No.
1 1&2 JN7-DIN-L01

Manual — PROFIBUS module hardware — page 448

Manual reference: physical PDF page 448. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.9 PROFIBUS High-Speed Communication Expansion Module 6.9.1 Communication Hardware and Data Structure This product is the PROFIBUS high-speed communication expansion module; it can perform remote setting and communication functions through the PROFIBUS bus. Used on the TECO E710 AC motor drive (hereinafter referred to as the "drive"), enabling the drive to operate on the PROFIBUSnetwork.

ID address switch

Expansion module screw mounting hole

COMM. indicator RUN indicator ERR indicator

Terminal resistor switch

D-SUB port

Manual — PROFIBUS module specifications — page 449

Manual reference: physical PDF page 449. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.9.2 Product Specifications PROFIBUS ports

AC motor driver port

Physical merged source cells repeated only over spanned rows; explicit blanks/dashes and ellipsis retained. Hexbit labels stayhex. No inferred protocol applicability beyond source.

PROFIBUS ports — PDF page 449

Source row Item Specifications
1 Connector DB-9
2 Transmission rate 9.6Kbit/s to 12Mbit/s (automatic detection of transmission rate)
3 Network protocols PROFIBUS communication protocol

AC motor driver port — PDF page 449

Source row Item Specifications
1 Connector Connection between Control Board CN5 and Communication Card CN2
2 Transmission method SPI high speed communication
3 Terminal functions 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface.
4 Communication protocols TECO communication protocol

Manual — Pin and DIP switch definitions — page 450

Manual reference: physical PDF page 450. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.9.3 Installation Instructions PROFIBUS network connection Definitions of PROFIBUS DP communication port pins are as shown in the figure below.

PROFIBUS network connection As shown in the figure below, the ID address range (1–125) corresponds to SW1 b1–b7.

Network address switch setting range: 1~125 (0, 128~255 cannot be used).

1 2 3 4 5 6 7 8 9

3 B-Line; 8 A-Line; 5 2 M

ON DIP 1 2 3 4 5 6 7 8

Physical merged source cells repeated only over spanned rows; explicit blanks/dashes and ellipsis retained. Hexbit labels stayhex. No inferred protocol applicability beyond source.

Adjacent source context — repeated to preserve continuation:

PROFIBUS DP port pin definitions — PDF page 450

Source row Pin Definition Description
1 1~2 Not assigned -
2 3 RXD/TXD-P (B- Line) Receive/Send data -P
3 4 Not assigned -
4 5 DGND (2M) Data reference potential
5 6~7 Not assigned -
6 8 RXD/TXD-N (A- Line) Receive/Send data -N
7 9 Not assigned -

SW1 DIP network address setting — PDF page 450

Source row Function DIP switch position DIP switch status Description
1 Network address setting b1~b7 1000000 Network address is 1
2 Network address setting b1~b7 0100000 Network address is 2
3 Network address setting b1~b7 1100000 Network address is 3
4 Network address setting b1~b7 ............ …….
5 Network address setting b1~b7 1011111 Network address is 125
6 No function b8 - -

Manual — Termination, bus length and module status LEDs — page 451

Manual reference: physical PDF page 451. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

PROFIBUS bus terminal resistor

The first and last station of the PROFIBUS bus must be connected to the bus, and the bus terminal resistor must be turned on.

6.9.4 LED Indicator Description The module has two dual-color LED indicators built-in used to quickly diagnose and monitor the communication statuses between the module itself and the bus. Module status LEDs (RUN LED & ERR LED) Used to monitor whether the equipment is operating normally.

5V 390Ω 220Ω 390Ω V- ON SW DIP-2 B+ A- Bus Terminating Resistors

ON OFF 1 2

4 3 above switch; 1 2 below switch

Physical merged source cells repeated only over spanned rows; explicit blanks/dashes and ellipsis retained. Hexbit labels stayhex. No inferred protocol applicability beyond source.

Adjacent source context — repeated to preserve continuation:

Serial rate versus maximum bus length — PDF page 451

Source row Serial Transmission Rate (kbps) Maximum Bus Length (m)
1 9.6 1200
2 19.2 1200
3 45.45 1200
4 93.75 1200
5 187.5 1000
6 500 400
7 1500 200
8 3000 100
9 6000 100
10 12000 100

Module status LEDs RUN and ERR — PDF page 451

Source row Indicator statuses Description
1 Does not light up Power not supplied
2 Orange light lights up Communication with the frequency converter not established
3 Red light flashes (1 Hz) Communication error with the frequency converter
4 Red light flashes (4 Hz) Flip-switch ID address error
5 Green light flashes (4 Hz) Power supply normal but DP communication not established
6 Green light lights up DP communication normal

Manual — COMM LED, driver parameters and PPO structure — page 452

Manual reference: physical PDF page 452. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Network status LED (COMM LED) Used to monitor the operability of the communication module PROFIBUS network.

6.9.5 Driver parameter setting description Used to monitor the operability of the communication module PROFIBUS network. Users must first confirm related parameter settings on the driver in order to ensure that the communication module can connect normally.

6.9.6 Connection operations PPO communication

PZD Structure default User parameters of the communication module configured through the GSD file. Default values of the PZD structure are as follows: STW1 Control character; mapped to the MODBUS address 0x2501 of the driver. HSW Main setting value; mapped to the MODBUS address 0x2502 of the driver. ZSW1 Status character; mapped to the MODBUS address 0x2520 of the driver. HIW Main actual value; mapped to the MODBUS address 0x2524 of the driver.

PKW

PZD

PKE

IND

PWE

PZD1 STW ZSW

PZD2 HSW HIW

PZD3

PZD4

PZD5

PZD6

PZD7

PZD8

PZD9

PZD10

1st word

2nd word

3rd word

4th word

5th word

6th word

7th word

8th word

9th word

10th word

PPO1

PPO2

PPO3

PPO4

PPO5

Physical merged source cells repeated only over spanned rows; explicit blanks/dashes and ellipsis retained. Hexbit labels stayhex. No inferred protocol applicability beyond source.

Network status COMM LED — PDF page 452

Source row Indicator statuses Description
1 Does not light up DP communication not established
2 Green light lights up DP communication established and normal

Driver parameter settings for PROFIBUS — PDF page 452

Source row Parameters Parameter name Settings Settings descriptions
1 00-02 Operation command source 2 Communication control
2 00-05 Frequency command source 3 Communication control

PPO abbreviations — PDF page 452

Source row Left source column Right source column
1 PKW: Parameter address/value STW: Control character
2 PZD: Process data ZSW: Status character
3 PKE: Parameter address HSW: Main settings
4 IND: Subindex HIW: Main actual value
5 PWE: Parameter value ⟦blank source cell⟧

Manual — PZD continuation and STW control bits — page 453

Manual reference: physical PDF page 453. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

PLC Master station→ driver slave station PZD3/ PZD4: Not used.

Driver slave station→ PLC master station Driver output status; mapped to the MODBUS addresses 0x2520~0x252F of the driver. The default values of PZD3/PZD4/PZD5/PZD6 are set as follows: PZD3: Default multi-function terminal block on/off status; mapped to the MODBUS address 0x2522 of the driver. PZD4: Default output current; mapped to the MODBUS address 0x2527 of the driver. PZD5: Default output current; mapped to the MODBUS address 0x2521 of the driver. PZD6: Default output current; mapped to the MODBUS address 0x2528 of the driver.

6.9.7 Meanings of each character Control Character (STW)

Physical merged source cells repeated only over spanned rows; explicit blanks/dashes and ellipsis retained. Hexbit labels stayhex. No inferred protocol applicability beyond source.

Control Character STW — PDF page 453

Source row Bit Description 1 0
1 0 Operation command Operate Stop
2 1 Reverse command Reverse Forward
3 2 External error Error -
4 3 Error reset Reset -
5 4~5 Reserved - -
6 6 Multi-function terminal S1 ON OFF
7 7 Multi-function terminal S2 ON OFF
8 8 Multi-function terminal S3 ON OFF
9 9 Multi-function terminal S4 ON OFF
10 A Multi-function terminal S5 ON OFF
11 B Multi-function terminal S6 ON OFF
12 C Multi-function terminal S7 ON OFF
13 D ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 E Controller mode ON OFF
15 F Communication setting torque command ON ⟦blank source cell⟧

Manual — PROFIBUS status and PKW request structure — page 454

Manual reference: physical PDF page 454. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Status Character (ZSW)

6.9.8 PKW area access parameters The driver can provide request and response information. Due to the request and response mechanism, the master station must send requests until a communication response is received. The 4 characters of the PKW region are as follows:

Parameter Address (PKE) Bits 0–11 (PNU): Contains the parameter address / MODBUS address of the related parameter. Parameter address/MODBUS address: Please refer to the MODBUS communication protocol description chapter in the driver manual for the register numbers, registers and data format that corresponds to the operation parameters. Bits 12–15 (AK): Contains the identifier characters for the request or response.

Request character AK PLC master station→ driver slave station

Word 1

Parameter ID(PKE)

bit

15 12 AK

11 0 Parameter number(PNU)

Word 2

IND Reserved

Word 3

PWE1

15 8 Reserved

7 0 Fault number

Word 4

PWE2 Read/Write parameters

Physical source cells and explicit protocol/table scope. Shared labels only repeated for actual merged cells. Leading zeros and exact bit order retained. Parallel rate/length pairs on460are independent pairs, not four measures of one cable.

PROFIBUS Status Character ZSW — PDF page 454

Source row Bit Meaning 1 0
1 0 Operation status Operate Stop
2 1 Direction status Reverse Forward
3 2 Frequency converter operation preparation status Preparation complete Not yet prepared
4 3 Error Abnormal Normal
5 4 Warning ON OFF
6 5 Zero speed ON OFF
7 6 Model 440 ON OFF
8 7 Frequency reached ON OFF
9 8 Any frequency reached ON OFF
10 9 Frequency detection one ON OFF
11 A Frequency detection two ON OFF
12 B Low voltage ON OFF
13 C Frequency converter no output ON OFF
14 D Frequency not according to communication ON OFF
15 E SeqNotFromComm ON OFF
16 F Over-torque ON OFF

PROFIBUS AK request master to slave — PDF page 454

Source row Request Identifier Description
1 0 No request
2 1 Read parameter value
3 2 Modify parameter value

Manual — PROFIBUS response and PKW example — page 455

Manual reference: physical PDF page 455. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Response character AK Driver slave station→ PLC master station

Error character If the request parameter value was not processed, then the error codes that will be kept in the low-bit PWE1 set are as follows:

Parameter Value (PWE) Driver parameters are sent through PWE2 (4th word). In the following example, PWEI (3rd word) must be set as 0 in the PROFIBUS master station.

Example of the PKW mechanism: For example: Read parameters 00-05 (frequency command source). Read the values of 00-05; first set the request identification character as 1, and then refer to the MODBUS communication protocol description chapter in the driver manual to find out that the address of 00-05 is 0x0005, then the data sequences are as follows:

PLC master station →driver slave station: 1000 0005 0000 0000 Driver slave station→ PLC master station: 1000 0005 0000 0004

Physical source cells and explicit protocol/table scope. Shared labels only repeated for actual merged cells. Leading zeros and exact bit order retained. Parallel rate/length pairs on460are independent pairs, not four measures of one cable.

PROFIBUS AK response slave to master — PDF page 455

Source row Request Identifier Description
1 0 No response
2 1 Request parameter value processed
3 7 Request parameter value cannot process

PROFIBUS Error character — PDF page 455

Source row Error code Description
1 0 Parameter does not exist
2 1 The current status parameter cannot be read/written
3 2 Parameter value not within range
4 101 Other SP communication error occurred, such as: response timeout

PROFIBUS PKW request example — PDF page 455

Source row Request word Request value
1 1st word (PKE) 1000
2 2nd word (IND) 0005
3 3rd word (PWE1) 0000
4 4th word (PWE2) 0000

PROFIBUS PKW response example — PDF page 455

Source row Response word Response value
1 1st word (PKE) 1000
2 2nd word (IND) 0005
3 3rd word (PWE1) 0000
4 4th word (PWE2) 0004

Manual — PROFIBUS troubleshooting and GSD dependency — page 456

Manual reference: physical PDF page 456. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.9.9 Troubleshooting There are two indicators on top of the PROFIBUS communication module; when malfunction occurs, the cause of the malfunction can be confirmed based on the indicator statuses, and troubleshoot the error by following the descriptions below. Indicator troubleshooting Module status LED

Network status LED

6.9.10 GSD File When using the Profibus communication module, if the GSD description file (JN7-CMHI- PDP_V (latest version).GSD) is needed, please download it from the TECO official website or request for it from your purchasing sales channel.

Physical source cells and explicit protocol/table scope. Shared labels only repeated for actual merged cells. Leading zeros and exact bit order retained. Parallel rate/length pairs on460are independent pairs, not four measures of one cable.

PROFIBUS module status troubleshooting — PDF page 456

Source row Indicator statuses Status name Troubleshooting method
1 Does not light up Power not supplied to the communication module 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.
2 Red and green light flashes alternately Self-check 1. The host is under self-check; if it flashes continuously, disconnect the power and then reconnect it. 2. Confirm whether the driver communication connection parameters are properly set (19200, 8, N, 1)
3 Green light flashes Communication module is in standby mode. 1. Not yet connected with the driver.

PROFIBUS network status troubleshooting — PDF page 456

Source row Indicator statuses Status name Description
1 Does not light up Power not supplied 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.
2 Does not light up Standby 1. Not yet connected with the PROFIBUS host terminal.

Manual — CANopen hardware and port specifications — page 457

Manual reference: physical PDF page 457. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.10 CANopen High-Speed Communication Expansion Card 6.10.1 Communication Hardware and Data Structure This product is the CANopen high-speed communication expansion module; it can perform remote setting and communication functions through the CANopen bus. This product is exclusively for use with the TECO E710 AC Motor Drive (hereinafter referred to as the “drive”), enabling the drive to operate on a CANopen network.

6.10.2 Product Specifications CANopen Port

Physical source cells and explicit protocol/table scope. Shared labels only repeated for actual merged cells. Leading zeros and exact bit order retained. Parallel rate/length pairs on460are independent pairs, not four measures of one cable.

CANopen port specifications — PDF page 457

Source row Item Specifications
1 Connector 5-pin open pluggable connector; pin spacing 5.08mm
2 Transmission rate 10kbps、20kbps、50kbps、125kbps、250kbps、500kbps、 800kbps、1Mbps
3 Network protocols CANopen communication protocol

Manual — CANopen installation and terminal definitions — page 458

Manual reference: physical PDF page 458. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AC motor driver port

6.10.3 Installation Instructions Communication module contact description As shown in the figure below, A – Terminal block (TB1) B, C – Mounting holes D - RUN LED E - ERR LED G – Baud Rate Configuration H – Node ID Configuration

Terminal block definition As shown in the figure below, the contact definitions in the order from left to right are GND, CAN_L, NC, CAN_H and NC.

ID address setting description As shown in the diagram below, the ID address (1–127) corresponds to SW1 b1–b7.

A B C D E G H

Physical source cells and explicit protocol/table scope. Shared labels only repeated for actual merged cells. Leading zeros and exact bit order retained. Parallel rate/length pairs on460are independent pairs, not four measures of one cable.

CANopen AC motor driver port — PDF page 458

Source row Item Specifications
1 Connector Connection between Control Board CN5 and Communication Card CN2
2 Transmission method SPI high speed communication
3 Terminal functions 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface.
4 Communication protocols TECO communication protocol

Manual — CANopen DIP settings and cable types — page 459

Manual reference: physical PDF page 459. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Transmission rate corresponds to SW2 b1~b3.

Network address switch setting range: 1~127 (0, 128~255 cannot be used). Transmission rate switch setting range: 0–7 (8–15 are not usable).

6.10.4 Transmission Rate, Maximum Distance, and Cable Type The maximum allowable bus length primarily depends on the type of cable used. The permissible cable types include: • Thin cable • Thick cable • Flat cable

ON DIP 1 2 3 4 5 6 7 8

ON DIP 1 2 3 4

Physical source cells and explicit protocol/table scope. Shared labels only repeated for actual merged cells. Leading zeros and exact bit order retained. Parallel rate/length pairs on460are independent pairs, not four measures of one cable.

CANopen SW1 network and SW2 baud rate settings — PDF page 459

Source row Function DIP switch position DIP switch status7654321 Description
1 Network address setting SW1 b7—b1 0000000 Cannot be used
2 Network address setting SW1 b7—b1 0000001 Network address is 1
3 Network address setting SW1 b7—b1 0000010 Network address is 2
4 Network address setting SW1 b7—b1 0000011 Network address is 3
5 Network address setting SW1 b7—b1 ............ ............
6 Network address setting SW1 b7—b1 1111110 Network address is 126
7 Network address setting SW1 b7—b1 1111111 Network address is 127
8 CANopen Transmission Rate Settings SW2 b3—b1 000 10K
9 CANopen Transmission Rate Settings SW2 b3—b1 001 20K
10 CANopen Transmission Rate Settings SW2 b3—b1 010 50K
11 CANopen Transmission Rate Settings SW2 b3—b1 011 125K
12 CANopen Transmission Rate Settings SW2 b3—b1 100 250K
13 CANopen Transmission Rate Settings SW2 b3—b1 101 500K
14 CANopen Transmission Rate Settings SW2 b3—b1 110 800K
15 CANopen Transmission Rate Settings SW2 b3—b1 111 1M

Manual — CANopen cable lengths, LEDs and driver settings — page 460

Manual reference: physical PDF page 460. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

According to ODVA specifications, the requirements for data transmission cables (thick cable) are as follows:

6.10.5 LED Indicator Description The module has RUN (green) and ERR (red) indicators built-in used to quickly diagnose and monitor the communication statuses between the module itself and the bus. Module status LED (RUN LED) Used to monitor whether the equipment is operating normally.

Error LED (ERR LED) Used to monitor the operability of the communication module CANopen network.

6.10.6 Driver parameter setting description Used to monitor the operability of the communication module CANopen network. Users must first confirm related parameter settings on the driver in order to ensure that the communication module can connect normally.

Physical source cells and explicit protocol/table scope. Shared labels only repeated for actual merged cells. Leading zeros and exact bit order retained. Parallel rate/length pairs on460are independent pairs, not four measures of one cable.

CANopen thick cable rate and bus length — PDF page 460

Source row Serial Transmission Rate (kbps) left Maximum Bus Length (m) left Serial Transmission Rate (kbps) right Maximum Bus Length (m) right
1 1000 25 125 500
2 800 50 50 1000
3 500 100 20 2500
4 250 250 10 5000

CANopen RUN LED — PDF page 460

Source row Indicator statuses Status name Description
1 Does not light up Initial status Power not supplied
2 Continuous flashing Pre-operation Preparation status
3 Single flash Stop Stopping
4 Green light lights up Operation Operating

CANopen ERR LED — PDF page 460

Source row Indicator statuses Status name Description
1 Does not light up No error Operating
2 Single flash Warning Packet error
3 Double flash Error Guard/Heartbeat error
4 Red light lights up Disconnected Bus closed

CANopen driver parameter settings — PDF page 460

Source row Parameters Parameter name Settings Settings descriptions
1 00-02 Operation command source 2 Communication control
2 00-05 Frequency command source 3 Communication control

Manual — CANopen SDO protocol layout — page 461

Manual reference: physical PDF page 461. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.10.7 Connection operations Service Data Object (SDO) This module supports 1 SDO server, which means it can provide SDO service, and the SDO uses the sending and receiving COB-ID of the predefined connection, 0x580 + NodeID (sending) and 0x600 + NodeID (receiving). Each SDO message includes a set of COB-ID (request SDO and response SDO); it allows performing of access actions within two nodes. SDO can transmit any size of data, but segment transmission must be used once it exceeds 4 bytes.

The COB IDs of SDO communication are as follows: Read: Master to slave (request code 0x40) / Master to slave: 600H + Node ID

Read: Slave response / slave to master: 580H + Node ID

Response code: 43H: Read 4-byte data / 4BH: read 2-byte data / 4FH: read 1-byte data

Write: Master to slave (4-byte data maximum)

Request code: 23H: Write a 4-byte data entry 2BH: Write a 2-byte data entry 2FH: Write a 1-byte data entry

Write: Slave to master (response code 0x60H)

When we use SDO to perform control to the group 25H of the driver control group, corresponding rules are as follows:

Index 25xxH (register address)

Two physical source rows: row1fieldcategory; row2detail. Merged category/reserved cells repeat across actual source-spanned byte headers with identical bounds, never fabricated per-byte values. Read response/request codes in nearby prose. Full byte layout retained.

SDO read master-to-slave request — PDF page 461

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (600H) + Node ID Request code Object index Object index Object subindex Request data Request data Request data Request data
2 (600H) + Node ID Request code LSB MSB Object subindex Reserved Reserved Reserved Reserved

SDO read slave-to-master response — PDF page 461

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (580H) + Node ID Request code Object index Object index Object subindex Request data Request data Request data Request data
2 (580H) + Node ID Request code LSB MSB Object subindex bit0~ bit7 Bit8~ bit15 Bit16~ bit23 Bit24~ bit31

SDO write master-to-slave request — PDF page 461

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (600H) + Node ID Request code Object index Object index Object subindex Request data Request data Request data Request data
2 (600H) + Node ID Request code LSB MSB Object subindex bit0~ bit7 Bit8~ bit15 Bit16~ bit23 Bit24~ bit31

SDO write slave-to-master response — PDF page 461

Source row COB-ID Byte0 Byte1 Byte2 Byte3 Byte4 Byte5 Byte6 Byte7
1 (580H) + Node ID Request code Object index Object index Object subindex Request data Request data Request data Request data
2 (580H) + Node ID Request code LSB MSB Object subindex Reserved Reserved Reserved Reserved

Manual — CANopen direct object mapping — page 462

Manual reference: physical PDF page 462. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

For example, when we want to perform write/read to 2501H of the control group, the corresponding SDO object index is the control group register address 2501H. Operate directly using Index 2501H, and the module will automatically convert it to access the control group register address 2501H of the E710.

Manual — CANopen basic object index — page 463

Manual reference: physical PDF page 463. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.10.8 Object Index Table Basic index

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

CANopen Basic Object Index — PDF page 463

Source row Index Sub Name Default R/W Size Remarks
1 1000H 0 Device type 00010192H R U32 ⟦blank source cell⟧
2 1001H 0 Error register 0 R U8 ⟦blank source cell⟧
3 1005H 0 COB-ID SYNC message 80H R U32 ⟦blank source cell⟧
4 1006H 0 Communication cycle period 0 RW U32 ⟦blank source cell⟧
5 1008H 0 Manufacturer device name E710 R U32 ⟦blank source cell⟧
6 1009H 0 Manufacturer hardware version 1.0 R U32 ⟦blank source cell⟧
7 100AH 0 Manufacturer software version 1.00 R U32 ⟦blank source cell⟧
8 1014H 0 COB-ID emergency 00000080H+Node-ID R U32 ⟦blank source cell⟧
9 1015H 0 Inhibit time EMCY 0 RW U16 ⟦blank source cell⟧
10 1016H 0 number of entries 1 R U8 ⟦blank source cell⟧
11 1016H 1 Consumer heartbeat time 0 RW U32 Not supported
12 1017H 0 Producer heartbeat time 0 RW U16 ⟦blank source cell⟧
13 1018H 0 number of entries 3 R U8 ⟦blank source cell⟧
14 1018H 1 Vender ID 00000373H R U32 ⟦blank source cell⟧
15 1018H 2 Product code 00000100H R U32 ⟦blank source cell⟧
16 1018H 3 Revision 00010000H R U32 ⟦blank source cell⟧
17 1200H 0 Server SDO Parameter 2 R U8 ⟦blank source cell⟧
18 1200H 1 COB-ID Client Server 0000600H+Node-ID R U32 ⟦blank source cell⟧
19 1200H 2 COB-ID Client Server 0000580H+Node-ID R U32 ⟦blank source cell⟧
20 1400H 0 Number of entries 2 R U8 ⟦blank source cell⟧
21 1400H 1 COB-ID used by PDO 00000200H+Node-ID RW U32 ⟦blank source cell⟧
22 1400H 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
23 1401H 0 Number of entries 2 R U8 ⟦blank source cell⟧
24 1401H 1 COB-ID used by PDO 00000300H+Node-ID RW U32 ⟦blank source cell⟧
25 1401H 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
26 1600H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
27 1600H 1 1.Mapped Object 60400010H RW U32 ⟦blank source cell⟧
28 1600H 2 2.Mapped Object 60420010H RW U32 ⟦blank source cell⟧
29 1600H 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
30 1600H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
31 1601H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
32 1601H 1 1.Mapped Object 604F0010H RW U32 ⟦blank source cell⟧
33 1601H 2 2.Mapped Object 60500010H RW U32 ⟦blank source cell⟧
34 1601H 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
35 1601H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
36 1800H 0 Number of entries 5 R U8 Number of entries
37 1800H 1 COB-ID used by PDO 180H+Node-ID RW U32 ⟦blank source cell⟧
38 1800H 2 Transmission Type 0xFF RW U8 Transmission type
39 1800H 3 Inhibit time 0x64 RW U16 Inhibit time
40 1800H 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧

Manual — CANopen object index continuation — page 464

Manual reference: physical PDF page 464. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

CANopen Basic Object Index continuation — PDF page 464

Source row Index Sub Name Default R/W Size Remarks
1 ⟦blank source cell⟧ 5 Event timer 0x64 RW U16 Event timer
2 1801H 0 Number of entries 5 R U8 Number of entries
3 1801H 1 COB-ID used by PDO 00000280H+Node-ID RW U32 ⟦blank source cell⟧
4 1801H 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
5 1801H 3 Inhibit time 0x64 RW U16 Inhibit time
6 1801H 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧
7 1801H 5 Event timer 0x64 RW U16 Event time
8 1801H 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧
9 1801H 5 Event timer 0x64 RW U16 Event time
10 1801H 2 Transmission Type 0xFF RW U8 ⟦blank source cell⟧
11 1801H 3 Inhibit time 0x64 RW U16 Inhibit time
12 1801H 4 CMS-Priority Group 0 RW U8 ⟦blank source cell⟧
13 1801H 5 Event timer 0x64 RW U16 Event time
14 1A00H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
15 1A00H 1 1.Mapped Object 60400010 RW U32 ⟦blank source cell⟧
16 1A00H 2 2.Mapped Object 60420010 RW U32 ⟦blank source cell⟧
17 1A00H 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
18 1A00H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
19 1A01H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
20 1A01H 1 1.Mapped Object 604F0010 RW U32 ⟦blank source cell⟧
21 1A01H 2 2.Mapped Object 60500010 RW U32 ⟦blank source cell⟧
22 1A01H 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
23 1A01H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧

Manual — CANopen DS402 objects — page 465

Manual reference: physical PDF page 465. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

DS402 part

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

CANopen DS402 Object Index — PDF page 465

Source row Index Sub Index Name Default R/W Size Unit PDO MAP
1 603F 0 Error code 0 RO U16 ⟦blank source cell⟧ Yes
2 6040 0 Control word 0 RW U16 ⟦blank source cell⟧ Yes
3 6041 0 Status word 0 RO U16 ⟦blank source cell⟧ Yes
4 6042 0 vl target velocity 0 RW S16 Hz Yes
5 6043 0 vl velocity demand 0 RO S16 Hz Yes
6 604F 0 vl ramp function time Acceleration time 100 RW U16 0.1S Yes
7 6050 0 vl slow down time Deceleration time 100 RW U16 0.1S Yes

Manual — CANopen command and monitor registers — page 466

Manual reference: physical PDF page 466. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Driver control group command index Command DATA (allows reading and writing)

Monitor DATA (read only)

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

CANopen reserved register — PDF page 466

Source row Register address Content
1 2500H Reserved

CANopen command operation signal — PDF page 466

Source row Register address Signal Bit Content
1 2501H Operation signal 0 Operation command 1: Operate 0: Stop
2 2501H Operation signal 1 Reverse command 1: Reverse 0: Forward
3 2501H Operation signal 2 External error 1: Error
4 2501H Operation signal 3 Error reset 1: Reset
5 2501H Operation signal 4 Reserved
6 2501H Operation signal 5 Reserved
7 2501H Operation signal 6 Multi-function terminal S1 1: “ON”
8 2501H Operation signal 7 Multi-function terminal S2 1: “ON”
9 2501H Operation signal 8 Multi-function terminal S3 1: “ON”
10 2501H Operation signal 9 Multi-function terminal S4 1: “ON”
11 2501H Operation signal A Multi-function terminal S5 1: “ON”
12 2501H Operation signal B Multi-function terminal S6 1: “ON”
13 2501H Operation signal C Multi-function terminal S7 1: “ON”
14 2501H Operation signal D ⟦blank source cell⟧
15 2501H Operation signal E Controller mode 1: “ON”
16 2501H Operation signal F Communication setting torque command 1: “ON”

CANopen command scalar registers — PDF page 466

Source row Register address Content
1 2502H *Frequency command (Unit: 0.01Hz)
2 2505H AO1 (0.00V ~ 10.00V)
3 2510H G12-00 H-WORD
4 2511H G12-00 L-WORD

CANopen monitor status signal — PDF page 466

Source row Register address Signal Bit Content
1 2520H Status signal 0 Operation status 1: Operate 0: Stop
2 2520H Status signal 1 Direction status 1: Reverse 0: Forward
3 2520H Status signal 2 Frequency converter operation preparation status 1: Preparation complete 0: Preparation not yet complete
4 2520H Status signal 3 Error 1: Abnormal
5 2520H Status signal 4 Warning 1: “ON”
6 2520H Status signal 5 Zero speed 1: “ON”
7 2520H Status signal 6 Model 440 1: “ON”
8 2520H Status signal 7 Frequency reached 1: “ON”
9 2520H Status signal 8 Any frequency reached 1: “ON”
10 2520H Status signal 9 Frequency detection one 1: “ON”
11 2520H Status signal A Frequency detection two 1: “ON”
12 2520H Status signal B Low voltage 1: “ON”
13 2520H Status signal C Frequency converter no output 1: “ON”

Manual — CANopen errors and digital input status — page 467

Manual reference: physical PDF page 467. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

CANopen monitor status continuation — PDF page 467

Source row Register address as printed Signal as printed Bit Content
1 ⟦blank source cell⟧ ⟦blank source cell⟧ D Frequency not according to communication 1: “ON”
2 ⟦blank source cell⟧ ⟦blank source cell⟧ E Operation not according to communication 1: “ON”
3 ⟦blank source cell⟧ ⟦blank source cell⟧ F Over-torque 1: “ON”

CANopen error description parallel pairs — PDF page 467

Source row Register address Signal Left code Left meaning Right code Right meaning
1 2521H Error description 0 Reserved 31 Reserved
2 2521H Error description 1 UV (Under-voltage) 32 Reserved
3 2521H Error description 2 OC (Over-current) 33 Reserved
4 2521H Error description 3 OV (Over-voltage) 34 Reserved
5 2521H Error description 4 OH1 (Heat sink overheat) 35 Reserved
6 2521H Error description 5 OL1 (Motor overload) 36 Reserved
7 2521H Error description 6 OL2 (Frequency converter overload) 37 Reserved
8 2521H Error description 7 OT (Over-torque) 38 CF07 (Motor control fault)
9 2521H Error description 8 UT (Under-torque) 39 Reserved
10 2521H Error description 9 SC (Short circuit) 40 Reserved
11 2521H Error description 10 GF (Ground fault) 41 Reserved
12 2521H Error description 11 FO 42 Reserved
13 2521H Error description 12 IPL (Input phase loss) 43 Reserved
14 2521H Error description 13 OPL (Output phase loss) 44 Reserved
15 2521H Error description 14 OS 45 Reserved
16 2521H Error description 15 PGO 46 OH4 (Motor overheat)
17 2521H Error description 16 DEV 47 Reserved
18 2521H Error description 17 EF1 48 Reserved
19 2521H Error description 18 EF2 49 MtrSw (DI Motor Switch Fault)
20 2521H Error description 19 EF3 50 OCA (Acceleration over-current)
21 2521H Error description 20 EF4 51 OCD (Deceleration over-current)
22 2521H Error description 21 EF5 52 OCC (Operation over-current)
23 2521H Error description 22 EF6 53 CF08
24 2521H Error description 23 EF7 54 PTCLS
25 2521H Error description 24 ⟦blank source cell⟧ 55 PF (Protection fault)
26 2521H Error description 25 FB (PID feedback signal error) 56 TOL
27 2521H Error description 26 OPR(Keypad Removed) 57 STO2 (Safety switch 2)
28 2521H Error description 27 Reserved 58 Reserved
29 2521H Error description 28 CE 59 Reserved
30 2521H Error description 29 STO (Safety switch 1) 60 Reserved
31 2521H Error description 30 Reserved 61 Reserved

CANopen DI status parallel pairs — PDF page 467

Source row Register address Signal Left bit Left meaning Middle bit Middle meaning Right bit Right meaning
1 2522H DI status 0 Multi-function terminal S1 4 Multi-function terminal S5 8~F Reserved
2 2522H DI status 1 Multi-function terminal S2 5 Multi-function terminal S6 ⟦blank source cell⟧ ⟦blank source cell⟧
3 2522H DI status 2 Multi-function terminal S3 6 Multi-function terminal S7 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — CANopen warnings and monitor registers — page 468

Manual reference: physical PDF page 468. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

CANopen DI status continuation — PDF page 468

Source row Register address as printed Signal as printed Left bit Left meaning Middle bit Middle meaning Right bit Right meaning
1 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 Multi-function terminal S4 7 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

CANopen monitor scalar registers — PDF page 468

Source row Register address Content
1 2523H Frequency command (0.01Hz)
2 2524H Output frequency (0.01Hz)
3 2526H DC voltage command (0.1V)
4 2527H Output current (0.1A)

CANopen warning description parallel pairs — PDF page 468

Source row Register address Signal Left code Left meaning Middle code Middle meaning Right code Right meaning
1 2528H Warning description 0 No alarm 30 RDE 60 Reserved
2 2528H Warning description 1 OV 31 WRE 61 RETRY
3 2528H Warning description 2 UV 32 FB 62 SE07
4 2528H Warning description 3 OL2 33 VRYE 63 Reserved
5 2528H Warning description 4 OH2 34 SE01 64 Reserved
6 2528H Warning description 5 Reserved 35 SE02 65 OH1
7 2528H Warning description 6 OT 36 SE03 66 FIRE
8 2528H Warning description 7 Reserved 37 Reserved 67 ES
9 2528H Warning description 8 Reserved 38 SE05 68 STP1
10 2528H Warning description 9 UT 39 HPERR 69 BDERR
11 2528H Warning description 10 OS 40 EF 70 EPERR
12 2528H Warning description 11 PGO 41 Reserved 71 Reserved
13 2528H Warning description 12 DEV 42 Reserved 72 Reserved
14 2528H Warning description 13 CE 43 RDP 73 STP0
15 2528H Warning description 14 CALL 44 Reserved 74 Reserved
16 2528H Warning description 15 Reserved 45 OL1 75 STP2
17 2528H Warning description 16 EF0 46 Reserved 76 RUNER
18 2528H Warning description 17 EF1 47 Reserved 77 LOC
19 2528H Warning description 18 EF2 48 Reserved 78 PTCLS
20 2528H Warning description 19 EF3 49 BB1 79 Sys Init
21 2528H Warning description 20 EF4 50 BB2 80 FBLSS
22 2528H Warning description 21 EF5 51 BB3 ⟦blank source cell⟧ ⟦blank source cell⟧
23 2528H Warning description 22 EF6 52 BB4 ⟦blank source cell⟧ ⟦blank source cell⟧
24 2528H Warning description 23 EF7 53 BB5 ⟦blank source cell⟧ ⟦blank source cell⟧
25 2528H Warning description 24 ⟦blank source cell⟧ 54 BB6 ⟦blank source cell⟧ ⟦blank source cell⟧
26 2528H Warning description 25 Reserved 55 BB7 ⟦blank source cell⟧ ⟦blank source cell⟧
27 2528H Warning description 26 Reserved 56 BB8 ⟦blank source cell⟧ ⟦blank source cell⟧
28 2528H Warning description 27 Reserved 57 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧
29 2528H Warning description 28 Reserved 58 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧
30 2528H Warning description 29 Reserved 59 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧

CANopen monitor output and input registers — PDF page 468

Source row Register address Content
1 2529H DO 狀態
2 252AH AO1
3 252BH AO2
4 252CH AI 1 input (0.1%)
5 252DH AI 2 input (0.1%)
6 252FH E710 Check

Manual — CANopen troubleshooting and EDS dependency — page 469

Manual reference: physical PDF page 469. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.10.9 Troubleshooting There are two indicators on top of the CANopen communication module; when malfunction occurs, the cause of the malfunction can be confirmed based on the indicator statuses, and troubleshoot the error by following the descriptions below. Indicator troubleshooting Module status LED (RUN LED)

Error LED (ERR LED)

6.10.10 EDS File When using the CANopen communication module, if the EDS description file (JN7-CMHI-CAN_V(latest version).eds) is needed, please download it from the TECO official website or request for it from your purchasing sales channel.

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

CANopen RUN LED troubleshooting — PDF page 469

Source row Indicator statuses Status name Troubleshooting methods
1 Does not light up Power not supplied to the communication module 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.

CANopen ERR LED troubleshooting — PDF page 469

Source row Indicator statuses Status name Troubleshooting methods
1 Single flash CANopen packet error Poor connection quality with the CANopen host terminal or host not connected when powered on. Continue transmission or power off inspection can be selected. Two results can be expected with continue transmission 1) Packet transmission returns to normal and the red light no longer flashes 2) Packet continues to have errors causing disconnection. When the power is off, check whether the TB1 terminal and cable are firmly connected, and whether the transmission rate, maximum transmission distance and cable length comply with ODVA specifications.
2 Double flash Guard/Heartbeat error User sends periodic heartbeat messages. If a message is not received after a specific time, please disconnect the power and check the connection status of that node.
3 Red light lights up Disconnected Unable to connect to the CANopen master. Please power off and check whether the TB1 terminal and wiring are securely connected, and whether the transmission rate, maximum transmission distance, and cable length comply with ODVA specifications.

Manual — EtherCAT hardware — page 470

Manual reference: physical PDF page 470. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.11 Introduction to the EtherCAT High Speed Communication Expansion Module

6.11.1 Communication Hardware and Data Structure This product is an EtherCAT high-speed communication expansion module (hereinafter referred to as the communication module), which enables remote configuration and communication functions over an EtherCAT network. This product is exclusively for use with the TECO E710 AC Motor Drive (hereinafter referred to as the “drive”), allowing the drive to operate within an EtherCAT network.

Manual — EtherCAT ports and installation — page 471

Manual reference: physical PDF page 471. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.11.2 Product Specifications EtherCAT ports

AC motor driver port

6.11.3 Installation Instructions Communication module contact description As shown in the figure below, the framed part is the CN2 connector that connects to the driver.

Communication module network socket As shown in the figure below, the left socket is input and the right socket is output.

Input

Output

Driver parameter setting description Users must first confirm related parameter settings on the driver in order to ensure that the communication module can connect normally.

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

EtherCAT port — PDF page 471

Source row Item Specifications
1 Connector Dual-port network socket
2 Network protocols EtherCAT communication protocol

EtherCAT drive port — PDF page 471

Source row Item Specifications
1 Connector Connection between Control Board CN5 and Communication Card CN2
2 Terminal functions 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface.

Manual — EtherCAT settings and indicators — page 472

Manual reference: physical PDF page 472. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.11.4 LED Indicator Description The module has two dual-color LED indicators built-in used to quickly diagnose and monitor the communication statuses between the module itself and the EtherCAT network.

Module status LED2 Used to monitor whether the communication module is operating normally.

Network status LED1 Used to monitor the operability of the communication module EtherCAT network.

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

EtherCAT driver settings — PDF page 472

Source row Parameters Parameter name Settings Settings descriptions
1 00-02 Operation command source 2 Communication control
2 00-05 Frequency command source 3 Communication control

EtherCAT moduleLED2 — PDF page 472

Source row Indicator statuses Status name Description
1 Does not light up Power not supplied Power not supplied
2 Red light flashes Data transmitting Driver and communication expansion module data transmitting
3 Red/green light lights up Driver data transmission error Data transmission error between the driver and communication expansion module

EtherCAT networkLED1 — PDF page 472

Source row Indicator statuses Status name Description
1 Does not light up Not connected / INIT EtherCAT network not connected (INIT)
2 Green light flashes Standby Pre-operational (Pre-OP)
3 Green light lights up Operation status Operational (OP)
4 Red light lights up Driver data transmission error Data transmission error between the driver and communication expansion module

Manual — EtherCAT object dictionary — page 473

Manual reference: physical PDF page 473. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.11.5 Object Index Table Basic index

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

EtherCAT Basic Object Index — PDF page 473

Source row Index Sub Index Name Default R/W Size Remarks
1 1000H 0 Device type 00000192H R U32 ⟦blank source cell⟧
2 1001H 0 Error register 0 R U8 ⟦blank source cell⟧
3 1008H 0 Manufacturer device name JN5-CM-CAN R U32 ⟦blank source cell⟧
4 1009H 0 Manufacturer hardware version Version R U32 ⟦blank source cell⟧
5 100AH 0 Manufacturer software version Version R U32 ⟦blank source cell⟧
6 1018H 0 number of entries 4 R U8 ⟦blank source cell⟧
7 1018H 1 Vender ID 0000081BH R U32 ⟦blank source cell⟧
8 1018H 2 Product code 00000001H R U32 ⟦blank source cell⟧
9 1018H 3 Revision 00000001H R U32 ⟦blank source cell⟧
10 1600H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
11 1600H 1 1.Mapped Object 60400010H RW U32 ⟦blank source cell⟧
12 1600H 2 2.Mapped Object 60420010H RW U32 ⟦blank source cell⟧
13 1600H 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
14 1600H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
15 1601H 0 Number of entries 2 RW U8 ⟦blank source cell⟧
16 1601H 1 1.Mapped Object 604F0010H RW U32 ⟦blank source cell⟧
17 1601H 2 2.Mapped Object 60500010H RW U32 ⟦blank source cell⟧
18 1601H 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
19 1601H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
20 1A00H 0 Number of entries 3 RW U8 ⟦blank source cell⟧
21 1A00H 1 1.Mapped Object 60400010 RW U32 ⟦blank source cell⟧
22 1A00H 2 2.Mapped Object 60420010 RW U32 ⟦blank source cell⟧
23 1A00H 3 3.Mapped Object 604F0020 RW U32 ⟦blank source cell⟧
24 1A00H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧
25 1A01H 0 Number of entries 3 RW U8 ⟦blank source cell⟧
26 1A01H 1 1.Mapped Object 604F0020 RW U32 ⟦blank source cell⟧
27 1A01H 2 2.Mapped Object 60500020 RW U32 ⟦blank source cell⟧
28 1A01H 3 3.Mapped Object 0 RW U32 ⟦blank source cell⟧
29 1A01H 4 4.Mapped Object 0 RW U32 ⟦blank source cell⟧

Manual — EtherCAT objects troubleshooting and XML — page 474

Manual reference: physical PDF page 474. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Object part

6.11.6 Troubleshooting There are two indicators on top of the EtherCAT communication module. When a malfunction occurs, the cause of the malfunction can be confirmed based on the indicator statuses, and troubleshoot the error by following the descriptions below. Indicator troubleshooting Module status LED2

Network status LED1

6.11.7 xml file When using the EtherCAT communication module, if the xml description file (JN7-CMHI-ECAT_V (latest version).xml) is needed, please download it from the TECO official website or request for it from your purchasing sales channel.

Physical source row/cell bounds. Parallel code/meaning pairs remain separate. Shared labels repeated only for actual merged cells. Cross-page blanks remain blank; continuation association recorded in source notes. Duplicated sub-index entries and empty code24 meanings retained without correction.

EtherCAT Object part — PDF page 474

Source row Index Sub Index Name Default R/W Size Unit PDO MAP
1 603F 0 Error code 0 RO U16 ⟦blank source cell⟧ Yes
2 6040 0 Control word 0 RW U16 ⟦blank source cell⟧ Yes
3 6041 0 Status word 0 RO U16 ⟦blank source cell⟧ Yes
4 6042 0 vl target velocity 0 RW S16 Hz Yes
5 6043 0 vl velocity demand 0 RO S16 Hz Yes
6 604F 0 vl ramp function time (acceleration time) Driver default value RW U32 0.1S Yes
7 6050 0 vl slow down time Deceleration time Driver default value RW U32 0.1S Yes

EtherCAT moduleLED2 troubleshooting — PDF page 474

Source row Indicator statuses Status name Troubleshooting method
1 Does not light up Power not supplied 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver.
2 Red/green light lights up Driver data transmission error 1. Confirm whether the communication module has proper contact. 2. Reconnect the power of the driver and confirm whether the error has been eliminated.

EtherCAT networkLED1 troubleshooting — PDF page 474

Source row Indicator statuses Status name Description
1 Does not light up Not connected / INIT 1. Confirm whether the driver power is normal. 2. If connected to EtherCAT, confirm whether it is in INIT mode.
2 Red light lights up Driver data transmission error 1. Confirm whether the communication module has proper contact. 2. Reconnect the power of the driver and confirm whether the error has been eliminated.

Manual — TCPIP hardware — page 475

Manual reference: physical PDF page 475. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.12 Introduction to the TCP/IP Communication Expansion Module

6.12.1 Communication Hardware and Data Structure This product is a TCP/IP communication expansion module (hereinafter referred to as the “communication module”), which enables remote configuration and communication via a TCP/IP network environment. This product is exclusively for use with the TECO E710 AC Motor Drive (hereinafter referred to as the “drive”), enabling the drive to operate on a TCP/IP network.

Expansion module screw mounting hole

TCP/IP port

Connects to the controller board via RJ45 connector

Manual — Communication application manual references — page 476

Manual reference: physical PDF page 476. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.13 Communication Interface Modules (a) PROFIBUS Communication Interface Module (JN5-CM-PDP) ‧ For wiring examples and communication program configuration, please refer to the "JN5-CM-PDP Communication Function Application Manual." (b) DeviceNet Communication Interface Module (JN5-CM-DNET) ‧ For wiring examples and communication program configuration, please refer to the "JN5-CM-DNET Communication Function Application Manual." (c) CANopen Communication Interface Module (JN5-CM-CAN) ‧ For wiring examples and communication program configuration, please refer to the "JN5-CM-CAN Communication Function Application Manual." (d) TCP/IP Communication Interface Module (JN5-CM-TCPIP) ‧ For wiring examples and communication program configuration, please refer to the "JN5-CM-TCPIP Communication Function Application Manual."

Manual — UL installation and terminal requirements — page 477

Manual reference: physical PDF page 477. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapter 7 Appendix A: UL Instructions

■ Maximum surrounding air temperature rating of 40(Enclosed Type) / 50 (Open Type)°C ■ This equipment is to be installed in an enclosure that provides a Pollution Degree 2 environment. ■ Main Circuit Terminal Wiring UL approval requires crimp terminals when wiring the inverter’s main circuit terminals. Use crimping tools as specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches inverter models with crimp terminals and insulation caps.

Closed-Loop Crimp Terminal Size

Terminal Block Wire Range and Torque Recommended

Physical model rows; three initial cap labels occupy an undivided cell but align one per source model row. Bounds explicitly split by those model row edges. Literal R84 for410retained; no assumed hyphen.

Merged wire/torque physical cells are shared by2P5/201and401/402 only. Exact raw Sol/Str,8.5lb.in(9.79kgf.cm),12lb.in(13.82kgf.cm) retained. No engineering conversion verified.

UL closed-loop crimp terminal size — PDF page 477

Source row Drive Product / Model E710 Wire Gauge AWG / mm² R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 Terminal screws Crimp terminal Model No. Tool Machine No. Insulation cap Model No.
1 2P5 (11-701-2□-2P8-□□□) 14 (2) M4 R2-4 Nichifu NH 1 / 9 TIC 2
2 201 (11-701-2□-4P8-□□□) 14 (2) M4 R2-4 Nichifu NH 1 / 9 TIC 2
3 202 (11-701-2□-7P5-□□□) 12 (3.5) M4 R3.5-4 Nichifu NH 1 / 9 TIC 3.5
4 203 (11-701-2□-011-□□□) 10 (5.5) M4 R5.5-4 Nichifu NH 1 / 9 TIC 5.5
5 205 (11-701-23-017-□□□) 8 (8) M4 R8-4 Nichifu NOP 60 ; NH 1 / 9 TIC 8
6 208 (11-701-23-025-□□□) 8 (8) M4 R8-4 Nichifu NOP 60 ; NH 1 / 9 TIC 8
7 401 (11-701-43-2P7-□□□) 14 (2) M4 R2-4 Nichifu NH 1 / 9 TIC 2
8 402 (11-701-43-4P2-□□□) 14 (2) M4 R2-4 Nichifu NH 1 / 9 TIC 2
9 403 (11-701-43-5P5-□□□) 14 (2) M4 R2-4 Nichifu NH 1 / 9 TIC 2
10 405 (11-701-43-009-□□□) 12 (3.5) M4 R3.5-4 Nichifu NH 1 / 9 TIC 3.5
11 408 (11-701-43-013-□□□) 10 (5.5) M4 R5.5-4 Nichifu NH 1 / 9 TIC 5.5
12 410 (11-701-43-017-□□□) 8 (8) M4 R84 Nichifu NH 1 / 9 TIC 8

UL terminal block wire and torque — PDF page 477

Source row Drive Product / Model E710 Input terminal block wire AWG and torque lb.in (kgf.cm) Output terminal block wire AWG and torque lb.in (kgf.cm)
1 2P5 (11-701-2□-2P8-□□□) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm)
2 201 (11-701-2□-4P8-□□□) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm)
3 202 (11-701-2□-7P5-□□□) 12AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 12AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)
4 203 (11-701-2□-011-□□□) 10AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 10AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)
5 205 (11-701-23-017-□□□) 8AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 8AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)
6 208 (11-701-23-025-□□□) 8AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 8AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)
7 401 (11-701-43-2P7-□□□) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm)
8 402 (11-701-43-4P2-□□□) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm) 14AWG(Sol/Str), 8.5 lb.in(9.79 kgf.cm)
9 403 (11-701-43-5P5-□□□) 14AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 14AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)
10 405 (11-701-43-009-□□□) 12AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 12AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)
11 408 (11-701-43-013-□□□) 10AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 10AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)
12 410 (11-701-43-017-□□□) 8AWG(Sol/Str), 12 lb.in(13.82 kgf.cm) 8AWG(Sol/Str), 12 lb.in(13.82 kgf.cm)

Manual — UL fuses and protection requirements — page 478

Manual reference: physical PDF page 478. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

■ Type 1 During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.

Recommended Input Fuse Selection

■ Motor Over-temperature Protection Motor over temperature protection is not provided. Motor over-temperature protection shall be provided in the end use application.

■ Solid State Motor Overload Protection Solid State Motor Overload Protection: 116% of motor FLA.

■ Field Wiring Terminals All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be used.

■ Branch circuit protection Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.

■ Inverter Short-Circuit Rating This inverter has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise above value. Please see electrical ratings for maximum voltage and table below for current.

• The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit tolerance of the power supply being used. • Suitable for use on a circuit capable of delivering not more than (A) RMS symmetrical amperes for right side table in 240 / 480 V class drives motor overload protection.

Physical source cells; shared categories only repeated across merged bounds. Fuse voltage/class and source manufacturer explicit. Substance O/X must be read with page485definitions, EPUPconditions and supplierdisclaimer; not independentcertification.

UL200Vclass single three phase Bussmann input fuses — PDF page 478

Source row Drive Product / Model E710 Bussmann Fuse Model Fuse Ampere Rating A (source includesV)
1 2P5 (11-701-2□-2P8-□□□) Bussmann FWC-16A10F 600V 16A
2 201 (11-701-2□-4P8-□□□) Bussmann FWC-20A10F 600V 20A
3 202 (11-701-2□-7P5-□□□) Bussmann FWC-32A10F 600V 32A
4 203 (11-701-2□-011-□□□) Bussmann 50FE 700V 50A
5 205 (11-701-23-017-□□□) Bussmann 50FE 700V 50A
6 208 (11-701-23-025-□□□) Bussmann 63FE 700V 63A

UL400Vclass three phase Bussmann input fuses — PDF page 478

Source row Drive Product / Model E710 Bussmann Fuse Model Fuse Ampere Rating A (source includesV)
1 401 (11-701-43-2P7-□□□) BussmannFWC-10A10F 600V 10A
2 402 (11-701-43-4P2-□□□) BussmannFWC-16A10F 600V 16A
3 403 (11-701-43-5P5-□□□) BussmannFWC-16A10F 600V 16A
4 405 (11-701-43-009-□□□) BussmannFWC-25A10F 600V 25A
5 408 (11-701-43-013-□□□) Bussmann 40FE 700V 40A
6 410 (11-701-43-017-□□□) Bussmann 50FE 700V 50A

UL short circuit rating — PDF page 478

Source row Horse Power Hp Current A Voltage V
1 1/4-50 5,000 240 / 480

Manual — French Preface — page 479

Manual reference: physical PDF page 479. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Préface

◆ Le produit est un lecteur conçu pour commander un moteur à induction triphasé. lire attentivement ce manuel pour garantir le bon fonctionnement, la sécurité et pour se familiariser avec les fonctions d'entraînement. ◆ Le lecteur est un appareil électrique / électronique et doit être installé et géré par un personnel qualifié ◆ Une mauvaise manipulation peut entraîner un fonctionnement incorrect, cycle de vie plus court, ou l'échec de ce produit ainsi que le moteur. ◆ Tous les documents sont sujets à changement sans préavis. Soyez sûr d'obtenir les dernières éditions de l'utilisation ou visitez notre site Web ◆ Lire le manuel d'instructions avant de procéder à l'installation, les connexions (câblage), le fonctionnement ou l'entretien et l'inspection. ◆ Vérifiez que vous avez une bonne connaissance de l'entraînement et de vous familiariser avec les consignes de sécurité et les précautions avant de procéder à fonctionner le lecteur. ◆ prêter attention aux consignes de sécurité indiquées par l'avertissement et symbole Attention .

Avertissement ignorer les informations indiquées par le symbole d'avertissement peut entraîner la mort ou des blessures graves.

Attention ignorer les informations indiquées par le symbole de mise en garde peut entraîner des blessures mineures ou modérées et / ou des dommages matériels importants.

Manual — French beforepower instructions — page 480

Manual reference: physical PDF page 480. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Chapitre 8 Consignes de sécurité 8.1 avant d'alimenter le disque dur

Avertissement ➢ Le circuit principal doit être correctement câblée. Pour les terminaux monophasés d'approvisionnement de l'utilisation des intrants (R/L1, T/L3) et de trois bornes d'entrée de l'utilisation de l'offre de phase (R/L1, S/L2, T/L3). U/T1, V/T2, W/T3 ne doivent être utilisés pour connecter le moteur. Raccordement de l'alimentation d'entrée à l'un des U/T1, V/T2 W/T3 ou bornes risque d'endommager le lecteur.

Attention ➢ Pour éviter que le couvercle ne se désengage ou de tout autre dommage physique, ne portez pas le lecteur par son couverture. Soutenir le groupe par son dissipateur de chaleur lors du transport. Une mauvaise manipulation peut endommager le lecteur ou blesser le personnel, et doit être évitée. ➢ Pour éviter que les risques d'incendie, ne pas installer le lecteur sur ou à proximité d'objets inflammables. Installer sur des objets ininflammables comme les surfaces métalliques. ➢ Si plusieurs disques sont placés dans le même panneau de contrôle, fournir une ventilation adéquate pour maintenir la température en dessous de 40 ° C/104 ° F (50 ° C/122 ° F sans housse de protection) pour éviter la surchauffe ou incendie. Lors d'un retrait ou d'installation de l'opérateur numérique, éteignez-le d'abord, puis de suivre les instructions de ce manuel pour éviter les erreurs de l'opérateur ou de la perte de l'affichage causé par des connexions défectueuses.

Avertissement ➢ Lors d'un retrait ou d'installation de l'opérateur numérique, éteignez-le d'abord, puis de suivre les instructions de ce manuel pour éviter les erreurs de l'opérateur ou de la perte de l'affichage causé par des connexions défectueuses....

Manual — French wiring and beforeoperation — page 481

Manual reference: physical PDF page 481. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.2 Câblage

Avertissement ➢ Coupez toujours l'alimentation électrique avant de procéder à l'installation d'entraînement et le câblage des terminaux utilisateurs. ➢ Le câblage doit être effectué par un personnel qualifié / électricien certifié. ➢ Assurez-vous que le lecteur est correctement mis à la terre. (220V Classe: impédance de mise à la terre doit être inférieure à 100Ω Classe 440V:. Impédance de mise à la terre doit être inférieure à 10Ω.) ➢ vérifier et tester mes circuits d'arrêt d'urgence après le câblage. (L’Installateur est responsable du câblage.) ➢ Ne touchez jamais de l'entrée ou de lignes électriques de sortie permettant directement ou toute entrée ou de lignes de puissance de sortie à venir en contact avec le boîtier d'entraînement. ➢ Ne pas effectuer un test de tenue en tension diélectrique (mégohmmètre) sur le disque dur ou cela va entraîner des dommages de lecture pour les composants semi-conducteurs.

Attention ➢ La tension d'alimentation appliquée doit se conformer à la tension d'entrée spécifiée par le lecteur. (Voir la section signalétique du produit) ➢ Raccorder la résistance de freinage et de l'unité de freinage sur les bornes assignées. ➢ Ne pas brancher une résistance de freinage directement sur les bornes CC P (+) et N (-), sinon risque d'incendie. ➢ Utilisez des recommandations de la jauge de fil et les spécifications de couple. (Voir Wire Gauge et la section de spécification de couple)。 ➢ Ne jamais brancher l'alimentation d'entrée aux bornes onduleur de sortie U/T1, V/T2, W/T3. ➢ Ne pas brancher un contacteur ou interrupteur en série avec le variateur et le moteur. ➢ Ne branchez pas un facteur condensateur de correction de puissance ou suppresseur de tension à la sortie du variateur。 ➢ S'assurer que l'interférence générée par l'entraînement et le moteur n'a pas d'incidence sur les périphériques.

8.3 Avant l'opération

Avertissement ➢ Assurez-vous que la capacité du disque correspond aux paramètres de notation avant d'alimenter. ➢ Réduire le paramètre de la fréquence porteuse si le câble du variateur au moteur est supérieure à 80 pi (25 m). Un courant de haute fréquence peut être générée par la capacité parasite entre les câbles et entraîner un déclenchement de surintensité du variateur, une augmentation du courant ou d'une lecture actuelle inexactes. ➢ Veillez à installer tous les couvercles avant de l'allumer. Ne retirez pas les capots pendant que l'alimentation du lecteur est allumé, un choc électrique peut se produire autrement. ➢ Ne pas actionner d'interrupteurs avec les mains mouillées, un choc électrique pourrait survenir autrement. ➢ Ne touchez pas les bornes d'entraînement lorsqu'il est alimenté, même si le lecteur est arrêté, un choc électrique pourrait survenir autrement.

Manual — French parameter setting — page 482

Manual reference: physical PDF page 482. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.4 Configuration Paramètre

Attention ➢ Ne branchez pas une charge pour le moteur tout en effectuant un auto-tune. ➢ Assurez-vous que le moteur peut fonctionner librement et il y a suffisamment d'espace autour du moteur lors de l'exécution d'un auto-tune rotation.

Manual — French operation and maintenance — page 483

Manual reference: physical PDF page 483. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.5 Opération

Avertissement ➢ Veillez à installer tous les couvercles avant de l'allumer. Ne retirez pas les capots pendant que l'alimentation du lecteur est allumé, un choc électrique peut se produire autrement. ➢ Ne pas brancher ou débrancher le moteur pendant le fonctionnement. Le variateur pourrai se déclencher et ainsi endommager le lecteur. ➢ Les opérations peuvent commencer soudainement si une alarme ou un défaut est réarmé avec un ordre de marche active. Assurez-vous qu'un ordre de marche est actif lors de la réinitialisation de l'alarme ou de défaut, autrement des accidents peuvent se produire. ➢ Ne pas actionner d'interrupteurs avec les mains mouillées, un choc électrique pourrait survenir . ➢ Un interrupteur d'urgence externe indépendant est fourni, qui s'arrête en urgence vers le bas la sortie de l'onduleur en cas de danger. ➢ Si le redémarrage automatique après une récupération d'énergie est activée, le variateur démarrera automatiquement après le rétablissement du courant. ➢ Assurez-vous qu'il est sûr de faire fonctionner le variateur et le moteur avant d'effectuer un auto-tune rotation. ➢ Ne touchez pas les bornes d'entraînement lorsqu'il est alimenté même si l’onduleur s'est arrêté, un choc électrique pourrait survenir . ➢ Ne pas contrôler les signaux sur les circuits pendant que le lecteur est en marche. ➢ Après la mise hors tension, le ventilateur de refroidissement peut continuer à fonctionner pendant un certain temps.

Attention ➢ Ne touchez pas les composants générant de la chaleur tels que radiateurs et des résistances de freinage. ➢ Vérifiez soigneusement la performance du moteur ou de la machine avant d'utiliser à grande vitesse, sous peine de blessure. ➢ Notez les réglages des paramètres liés à l'unité de freinage lorsque applicable. ➢ Ne pas utiliser la fonction de freinage d'entraînement pour un maintien mécanique, sous peine de blessure. ➢ Ne pas contrôler les signaux sur les circuits pendant que le lecteur est en marche.

8.6 Entretien, Inspection et remplacement

Avertissement ➢ Attendre un minimum de 5 minutes après que l'alimentation a été débranchée avant de commencer une inspection. Vérifiez également que le voyant de charge est éteint et que la tension du bus cc a chuté au-dessous de 25Vdc. ➢ Ne jamais toucher les bornes à haute tension dans le lecteur. ➢ Assurez-vous que l'alimentation du lecteur est débranché avant de démonter le lecteur. ➢ Seul le personnel autorisé peuvent faire l'entretien, l'inspection et les opérations de remplacement. (Enlevez les bijoux en métal tels que les montres et les bagues et utiliser des outils isolés.)

Attention ➢ Le variateur peut être utilisé dans un environnement avec une gamme de température allant de 14 ° -104 ° F (10-40 ° C) et l'humidité relative de 95% sans condensation. ➢ Le variateur doit être utilisé dans un environnement sans poussière, gaz, vapeur et humidité.

Manual — French disposal — page 484

Manual reference: physical PDF page 484. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.7 Mise au rebut du variateur

Attention ➢ jeter cet appareil avec soin comme un déchet industriel et selon les réglementations locales nécessaires. ➢ Les condensateurs du circuit principal d'entraînement et circuits imprimés sont considérés comme des déchets dangereux et ne doivent pas être brûlés. ➢ The Plastic enclosure and parts of the drive such as the top cover board will release harmful gases if burned.

Les équipements contenant des composants électriques ne doivent pas être éliminés avec les ordures ménagères. Il doit être collecté séparément avec les déchets électriques et électroniques conformément à la législation locale en vigueur.

Manual — Hazardous substances declaration and disclaimer — page 485

Manual reference: physical PDF page 485. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Product Documentation Appendix

Name and Content of Hazardous Substances in the Product

This table is compiled in accordance with the provisions of SJ/T 11364. O: Indicates that the content of the toxic or hazardous substance in all homogeneous materials of the component is below the limit requirements set forth in GB/T 26572. X: Indicates that the content of the toxic or hazardous substance in at least one of the homogeneous materials of the component exceeds the limit requirements set forth in GB/T 26572.

Definition of Component Categories in Major Components: Electronic Components – Includes electronic elements, soldered printed circuit boards, etc. Display – Includes display units, electronic components, or touchscreens. Wires and Cables – Includes terminals, connectors, shielding wires, sheaths, and electronic parts. Mechanical Parts – Refers to all parts excluding those already defined as electronic components, displays, and wires/cables.

Explanation of Environmental Protection Use Period (EPUP): Within the environmental protection use period, this product will not release or leak hazardous substances under normal usage, nor will it pose health risks to consumers. It can be used with confidence. TECO guarantees an EPUP of 10 years for this product. The “environmental protection use period” is valid only when the product is used under the conditions specified in this manual.

Disclaimer: The information provided by TECO regarding the content of substances in its products represents TECO’s knowledge and understanding of the product at the time such information is provided. TECO’s knowledge and understanding are based on information provided by third-party suppliers, and TECO makes no representations or warranties as to the accuracy of such third-party information. TECO may not have conducted destructive testing or chemical analysis on the materials or chemicals used. The use of the above products and TECO’s related responsibilities shall be governed by the Company’s standard contractual terms and conditions.

Physical source cells; shared categories only repeated across merged bounds. Fuse voltage/class and source manufacturer explicit. Substance O/X must be read with page485definitions, EPUPconditions and supplierdisclaimer; not independentcertification.

Product hazardous substances declaration — PDF page 485

Source row Component category Component name Lead and its compounds Pb Mercury and its compounds Hg Cadmium and its compounds Cd Hexavalent chromium compounds Cr(VI) Polybrominated biphenyls PBB Polybrominated diphenyl ethers PBDE
1 Electronic Components Electronic Parts X O O O O O
2 Electronic Components Electromagnetic contactor O O X O O O
3 Display Display O O O O O O
4 Wires and Cables Terminals X O O O O O
5 Wires and Cables Conductors O O O O O O
6 Wires and Cables Insulation Components O O O O O O
7 Mechanical Parts Conductive Copper Columns, Fans, Thermostats X O O O O O
8 Mechanical Parts Others O O O O O O

Manual — CDM losses and efficiency table — page 486

Manual reference: physical PDF page 486. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Scanned table composed of twoembeddedrasterimages; both retained. CDMtuple meanings are notdefined onthispage; preserve tuplelabels literally without inferring motorload/speed axes. Bluehighlightedpair isCDM(90,100),point1; not universalratedefficiency. StandbyLOSSunit isnotexplicit initsheader; no assumedunit. Source spelling Modul name andKVA retained.

Preserve each model and all10pointidentifiers in source order9,8,6,3,7,5,2,4,1,10. Point9standby hasonevalue; nineotherpoints havepLoss(W)andη(%). No frequency/enclosure/supplyphase inferred from model suffix. Printedunits andblankunit retained.

CDM losses and efficiency — PDF page 486

Source row Modul name Nominal voltage(V) Nominal Current(A) Nominal apparent KVA CDM STANDBY LOSS [point9; no printedunit] CDM (24,25) [point8] / p Loss(W) CDM (24,25) [point8] / η(%) CDM (24,50) [point6] / p Loss(W) CDM (24,50) [point6] / η(%) CDM (24,100) [point3] / p Loss(W) CDM (24,100) [point3] / η(%) CDM (50,25) [point7] / p Loss(W) CDM (50,25) [point7] / η(%) CDM (50,50) [point5] / p Loss(W) CDM (50,50) [point5] / η(%) CDM (50,100) [point2] / p Loss(W) CDM (50,100) [point2] / η(%) CDM (90,50) [point4] / p Loss(W) CDM (90,50) [point4] / η(%) CDM (90,100) [point1] / p Loss(W) CDM (90,100) [point1] / η(%) CDM (100,100) [point10] / p Loss(W) CDM (100,100) [point10] / η(%)
1 E710-401-H3 380 2.8 1.7 9.0 24.7 79.2 27.0 87.1 32.3 91.2 25.0 88.7 27.6 93.2 33.6 95.4 28.6 96.0 35.8 97.2 36.4 97.5
2 E710-402-H3 380 4.8 2.9 9.0 30.1 82.9 34.1 89.2 43.6 92.3 30.6 90.9 35.1 94.4 45.8 96.0 37.1 96.6 50.0 97.5 51.1 97.7
3 E710-403-H3 380 7.5 4.0 9.0 33.5 85.1 38.6 90.6 50.6 93.1 34.2 92.1 39.9 95.1 53.2 96.4 42.2 97.0 58.3 97.8 59.8 98.0
4 E710-405-H3 380 11 7.0 9.0 45.1 87.4 53.0 92.0 71.5 94.0 46.1 93.4 55.0 95.8 75.6 96.9 58.7 97.5 83.7 98.1 86.0 98.2
5 E710-408-H3 380 17 9.9 9.0 48.4 90.3 61.1 93.5 98.4 94.7 50.5 94.9 65.6 96.5 110.8 97.0 75.7 97.7 140.0 97.9 149.2 98.0
6 E710-410-H3 380 25 13.3 9.0 63.3 90.3 81.1 93.4 132.0 94.5 66.1 94.9 87.3 96.5 148.7 97.0 101.2 97.7 188.4 97.8 201.0 97.9
7 E710-2P5-H3 220 2.7 1.0 6.0 21.9 75.9 22.3 82.6 25.0 88.2 22.3 86.5 23.0 90.6 26.3 93.7 24.4 94.2 29.0 96.0 29.8 96.3
8 E710-201-H3 220 4.2 1.7 6.0 24.6 79.7 27.8 87.0 35.5 90.7 25.2 88.9 29.2 93.0 38.3 95.0 31.9 95.7 44.4 96.7 46.3 96.9
9 E710-202-H3 220 5.5 2.9 6.0 30.3 83.3 35.3 89.2 47.2 92.0 31.3 91.0 37.5 94.2 52.2 95.6 42.4 96.3 63.7 97.0 67.3 97.1
10 E710-203-H3 220 9 4.0 9.0 40.3 84.6 47.4 90.0 64.4 92.5 41.9 91.7 50.8 94.6 72.2 95.8 58.5 96.5 90.5 97.1 96.3 97.2
11 E710-205-H3 220 13 6.7 9.0 50.8 87.1 61.1 91.6 84.9 93.5 53.0 93.1 65.4 95.5 94.0 96.5 73.7 97.1 112.1 97.6 117.4 97.8
12 E710-208-H3 220 17 9.9 9.0 58.1 89.7 75.4 92.8 127.8 93.8 61.1 94.5 82.1 96.1 146.4 96.5 97.5 97.4 192.2 97.4 206.9 97.5
13 E710-2P5-H1 220 2.8 1.0 6.0 22.0 75.8 22.4 82.5 25.3 88.1 22.7 86.3 23.6 90.3 27.6 93.4 26.3 93.8 33.4 95.5 35.2 95.7
14 E710-201-H1 220 4.8 1.7 6.0 24.7 79.7 28.0 87.0 36.0 90.6 25.6 88.7 30.1 92.8 40.8 94.7 34.9 95.3 52.6 96.1 56.4 96.2
15 E710-202-H1 220 7.5 2.9 9.0 33.6 81.8 38.8 88.3 51.4 91.3 35.1 90.0 42.3 93.5 59.5 95.0 50.5 95.6 79.6 96.2 86.1 96.3
16 E710-203-H1 220 11 4.0 9.0 40.7 84.5 48.3 89.9 66.6 92.3 43.3 91.4 54.1 94.3 80.5 95.4 68.5 95.9 115.9 96.3 127.4 96.3

Manual — Manufacturer contacts, manual edition and notices — page 487

Manual reference: physical PDF page 487. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

TECO Electric & Machinery Co., Ltd.

東元電機股份有限公司

Please link to our website, to download the instruction manual of this product for proper use.

請連結至本公司官網,下載使用說明書,以能正確的使用本產品。

This manual may be modified when necessary because of improvement of the product, modification, or changes in specifications. This manual is subject to change without notice.

為持續改善產品,本公司保留變更設計規格之權利。

Historical contact and manualedition only; no current contactoperation asserted. Distributorbox blank. QRlocallydecoded at two scales to https://www.teco.com.tw/; printed URL withouttrailing slash retained separately; destination not fetched.

Source manufacturer/backcover only; date is printedmanualedition,not productmanufacture orpublicationverification.

Locally decoded at two scales; no remote request or current availability claim.

Manufacturer and edition — PDF page 487

Source row Printed label/context Source value
1 Address English 10F., No.3-1, Park St., Nangang District, Taipei City 115, Taiwan
2 Address Chinese 115台北市南港區園區街3-1號10樓
3 Tel +886-2-6615-9111
4 Fax +886-2-6615-0933
5 Web https://www.teco.com.tw
6 Manual number 4KA72X823T01
7 Version 01
8 Date 2025.06
9 Distributor [blank in source]

QR code payload — PDF page 487

Source row Encoded element Decoded payload
1 QR code https://www.teco.com.tw/

Technical source 001 — Variable speed drive E710-2P5-H1EF-IP20, 0.4KW, 0.5HP, 200-240V

Output-phase discrepancy: the individual wording conflicts with the manual three-phase output schedules. Do not infer a single-phase motor application. Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-2P5-H1EF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-2P5-H1EF-IP20, 0.4KW, 0.5HP, 200-240V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 1 / 1 Constant Torque (kW/A): 0.37 / 2.8; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 0.37 Datasheet PDF / E710-2P5-H1EF-IP20-datasheet.pdf

P017 / Variable speed drive E710-2P5-H1EF-IP20, 0.4KW, 0.5HP, 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity(HP) 0.5 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 1.2 as printed in field/value —
Output Rating / Rated Output Current(A) 2.8 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 0.5 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 0.37 as printed in field/value —
Output Rating / Maximum Output Voltage(V) Single Phase, 240V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Single Phase, 200V to 240V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-2P5-H1EF-IP20, 0.4KW, 0.5HP, 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-2P5-H1EF-IP20, 0.4KW, 0.5HP, 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Other Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-2P5-H1EF-IP20, 0.4KW, 0.5HP, 200-240V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-2P5-H1EF 72 (2.83) mm (inch) 220 (8.66) mm (inch) 150 (5.9) mm (inch) 60 (2.36) mm (inch) 130.5 (5.14) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 1.5 (3.3) kg (lbs) —

Technical source 002 — INV-E710-IP20-01.pdf

Source download: INV-E710-IP20-01.pdf.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 1 / 1 Constant Torque (kW/A): 0.37 / 2.8; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 0.37 2D Drawing PDF / INV-E710-IP20-01.pdf
93 / 2 / 2 Constant Torque (kW/A): 0.75 / 4.8; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 0.75 2D Drawing PDF / INV-E710-IP20-01.pdf
93 / 5 / 5 Constant Torque (kW/A): 0.75 / 2.7; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 0.75 2D Drawing PDF / INV-E710-IP20-01.pdf
93 / 6 / 6 Constant Torque (kW/A): 1.5 / 4.2; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 1.50 2D Drawing PDF / INV-E710-IP20-01.pdf

P017 / INV-E710-IP20-01.pdf — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Identity / type E710-IP20-F1 as printed —
Identity / drawing_number INV-E710-IP20-01 as printed —
Drawing / Front-view overall width 72 drawing units; not explicitly stated on this sheet C1
Drawing / Horizontal mounting-hole centres 60 drawing units; not explicitly stated on this sheet C1
Drawing / Front-view overall height 142 drawing units; not explicitly stated on this sheet C1
Drawing / Vertical mounting-hole centres 130.5 drawing units; not explicitly stated on this sheet C1
Drawing / Overall depth including projecting front control 150.5 drawing units; not explicitly stated on this sheet C1
Drawing / Body depth excluding projecting front control 144 drawing units; not explicitly stated on this sheet C1
Drawing / Mounting holes 4-M4 as printed C1
Drawing note / 1 No electrical rating or model-to-frame schedule is printed on this drawing. Use the matching E710 datasheet to establish applicability. as printed —
Drawing note / 2 Units are not explicitly stated on the supplied drawing; numeric values retained without asserting a conversion. as printed —

Technical source 003 — Variable speed drive E710-201-H1EF-IP20, 0.75KW, 1HP, 200-240V

Output-phase discrepancy: the individual wording conflicts with the manual three-phase output schedules. Do not infer a single-phase motor application. Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-201-H1EF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-201-H1EF-IP20, 0.75KW, 1HP, 200-240V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 2 / 2 Constant Torque (kW/A): 0.75 / 4.8; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 0.75 Datasheet PDF / E710-201-H1EF-IP20-datasheet.pdf

P017 / Variable speed drive E710-201-H1EF-IP20, 0.75KW, 1HP, 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 1 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 1.7 as printed in field/value —
Output Rating / Rated Output Current (A) 4.8 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 1 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 0.75 as printed in field/value —
Output Rating / Maximum Output Voltage (V) Single Phase, 240V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Single Phase, 200V to 240V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-201-H1EF-IP20, 0.75KW, 1HP, 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell,S curve acceleration and deceleration, Up/Down operation, Modbus, , Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-201-H1EF-IP20, 0.75KW, 1HP, 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Other Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-201-H1EF-IP20, 0.75KW, 1HP, 200-240V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-201-H1EF 72 (2.83) mm (inch) 220 (8.66) mm (inch) 150 (5.9) mm (inch) 60 (2.36) mm (inch) 130.5 (5.14) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 1.5 (3.3) kg (lbs) —

Technical source 004 — Variable speed drive E710-202-H1SF-IP20, 1.5KW, 2HP, 200-240V

Unresolved source conflict: this sheet is headed1.5kW/2HP but prints0.4kW/0.5HP/2.8A. The catalogue lists1.5kW/7.5A. Confirm before selection; no correction substituted. Output-phase discrepancy: the individual wording conflicts with the manual three-phase output schedules. Do not infer a single-phase motor application. Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-202-H1SF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-202-H1SF-IP20, 1.5KW, 2HP, 200-240V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 3 / 3 Constant Torque (kW/A): 1.5 / 7.5; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 1.50 Datasheet PDF / E710-202-H1SF-IP20-datasheet.pdf

P017 / Variable speed drive E710-202-H1SF-IP20, 1.5KW, 2HP, 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 0.5 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 1.2 as printed in field/value —
Output Rating / Rated Output Current (A) 2.8 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 0.5 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 0.4 as printed in field/value —
Output Rating / Maximum Output Voltage(V) Single Phase, 240V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Single Phase, 200V to 240V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-202-H1SF-IP20, 1.5KW, 2HP, 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-202-H1SF-IP20, 1.5KW, 2HP, 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Other Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-202-H1SF-IP20, 1.5KW, 2HP, 200-240V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-202-H1SF 87 (3.43) mm (inch) 220 (8.66) mm (inch) 164 (6.46) mm (inch) 73 (2.87) mm (inch) 145 (5.71) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 2 (4.41) kg (lbs) —

Technical source 005 — INV-E710-IP20-02.pdf

Source download: INV-E710-IP20-02.pdf.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 3 / 3 Constant Torque (kW/A): 1.5 / 7.5; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 1.50 2D Drawing PDF / INV-E710-IP20-02.pdf
93 / 4 / 4 Constant Torque (kW/A): 2.2 / 11; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 2.20 2D Drawing PDF / INV-E710-IP20-02.pdf
93 / 7 / 7 Constant Torque (kW/A): 2.2 / 5.5; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 2.20 2D Drawing PDF / INV-E710-IP20-02.pdf
93 / 8 / 8 Constant Torque (kW/A): 3.7 / 9; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 3.70 2D Drawing PDF / INV-E710-IP20-02.pdf

P017 / INV-E710-IP20-02.pdf — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Identity / type E710-IP20-F2 as printed —
Identity / drawing_number INV-E710-IP20-02 as printed —
Drawing / Front-view overall width 87 drawing units; not explicitly stated on this sheet C1
Drawing / Horizontal mounting-hole centres 73 drawing units; not explicitly stated on this sheet C1
Drawing / Front-view overall height 157 drawing units; not explicitly stated on this sheet C1
Drawing / Vertical mounting-hole centres 145.3 drawing units; not explicitly stated on this sheet C1
Drawing / Overall depth including projecting front control 164 drawing units; not explicitly stated on this sheet C1
Drawing / Body depth excluding projecting front control 158.1 drawing units; not explicitly stated on this sheet C1
Drawing / Mounting holes 4-M4 as printed C1
Drawing note / 1 No electrical rating or model-to-frame schedule is printed on this drawing. Use the matching E710 datasheet to establish applicability. as printed —
Drawing note / 2 Units are not explicitly stated on the supplied drawing; numeric values retained without asserting a conversion. as printed —

Technical source 006 — Variable speed drive E710-203-H1SF-IP20, 2.2KW, 3HP, 200-240V

Output-phase discrepancy: the individual wording conflicts with the manual three-phase output schedules. Do not infer a single-phase motor application. Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-203-H1SF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-203-H1SF-IP20, 2.2KW, 3HP, 200-240V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 4 / 4 Constant Torque (kW/A): 2.2 / 11; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 2.20 Datasheet PDF / E710-203-H1SF-IP20-datasheet.pdf

P017 / Variable speed drive E710-203-H1SF-IP20, 2.2KW, 3HP, 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity(HP) 3 as printed in field/value —
Out put Rati ng / Rated Output Capacity(KVA) 4 as printed in field/value —
Out put Rati ng / Rated Output Current(A) 11 as printed in field/value —
Out put Rati ng / Maximum Applicable Motor / (HP) 3 as printed in field/value —
Out put Rati ng / Maximum Applicable Motor / (KW) 2.2 as printed in field/value —
Out put Rati ng / Maximum Output Voltage(V) Single Phase, 240V as printed in field/value —
Out put Rati ng / Maximum Output Frequency(Hz) 599.0Hz as printed in field/value —
Inp ut Po wer / Rated Voltage, Frequency Single Phase, 200V to 240V, 50/60Hz as printed in field/value —
Inp ut Po wer / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Inp ut Po wer / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Display LED keypad as printed in field/value —
Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV only for special projects as printed in field/value —
Output Frequency 0.01~599.0Hz as printed in field/value —
Frequency Accuracy ±0.3Hz as printed in field/value —
Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Frequency setting resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Output Frequency Resolution 0.01Hz as printed in field/value —
Inverter Overload 150%/1 min as printed in field/value —
Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-203-H1SF-IP20, 2.2KW, 3HP, 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Voltage/Frequency Characteristics Custom V/F curve based on parameters as printed in field/value —
Braking Torque About 10% as printed in field/value —
Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS-485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell,S curve acceleration and deceleration, Up/Down operation, Modbus, , Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protec tion Functi ons / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protec tion Functi ons / Over Current(OC) and Output Short-circuit(SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protec tion Functi ons / Inverter Overload Protection(OL2) If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protec tion Functi ons / Motor Overload Protection(OL1) Electrical overload protection curve as printed in field/value —
Protec tion Functi ons / Over Voltage Protection(OV) If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V class), the motor stops running. as printed in field/value —
Protec tion Functi ons / Under Voltage Protection(UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protec tion Functi ons / Momentary power loss restart Power loss exceeds 8 milliseconds. Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protec tion Functi ons / Overheat Protection(OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protec tion Functi ons / Ground Fault Protection(GF) Protection by inverter software as printed in field/value —
Protec tion Functi ons / Charge Indicator None as printed in field/value —
Protec tion Functi ons / Output Phase Loss Protection(OPL) If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-203-H1SF-IP20, 2.2KW, 3HP, 200-240V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Envi ron men t Spe cific atio n / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Envi ron men t Spe cific atio n / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Envi ron men t Spe cific atio n / Storage Temperature -20~+70℃(-4℉~+158℉) as printed in field/value —
Envi ron men t Spe cific atio n / Humidity 95% RH or less (no condensation) as printed in field/value —
Envi ron men t Spe cific atio n / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference(EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Others Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-203-H1SF-IP20, 2.2KW, 3HP, 200-240V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-203-H1SF 87 (3.43) mm (inch) 220 (8.66) mm (inch) 164 (6.46) mm (inch) 73 (2.87) mm (inch) 145 (5.71) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 2 (4.41) kg (lbs) —

Technical source 007 — Variable speed drive E710-401-H3EF-IP20, 0.75KW, 1HP, 380-480V

Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-401-H3EF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-401-H3EF-IP20, 0.75KW, 1HP, 380-480V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 5 / 5 Constant Torque (kW/A): 0.75 / 2.7; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 0.75 Datasheet PDF / E710-401-H3EF-IP20-datasheet.pdf

P017 / Variable speed drive E710-401-H3EF-IP20, 0.75KW, 1HP, 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 1 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 1.7 as printed in field/value —
Output Rating / Rated Output Current(A) 2.7 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 1 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 0.75 as printed in field/value —
Output Rating / Maximum Output Voltage(V) Three Phase, 480V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V to 480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-401-H3EF-IP20, 0.75KW, 1HP, 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-401-H3EF-IP20, 0.75KW, 1HP, 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Others Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-401-H3EF-IP20, 0.75KW, 1HP, 380-480V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-401-H3EF 72 (2.83) mm (inch) 220 (8.66) mm (inch) 150 (5.9) mm (inch) 60 (2.36) mm (inch) 130.5 (5.14) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 1.5 (3.3) kg (lbs) —

Technical source 008 — Variable speed drive E710-402-H3EF-IP20, 1.5KW, 2HP, 380-480V

Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-402-H3EF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-402-H3EF-IP20, 1.5KW, 2HP, 380-480V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 6 / 6 Constant Torque (kW/A): 1.5 / 4.2; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 1.50 Datasheet PDF / E710-402-H3EF-IP20-datasheet.pdf

P017 / Variable speed drive E710-402-H3EF-IP20, 1.5KW, 2HP, 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 2 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 2.9 as printed in field/value —
Output Rating / Rated Output Current(A) 4.2 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 2 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 1.5 as printed in field/value —
Output Rating / Maximum Output Voltage(V) Three Phase, 480V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V to 480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-402-H3EF-IP20, 1.5KW, 2HP, 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-402-H3EF-IP20, 1.5KW, 2HP, 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Other Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-402-H3EF-IP20, 1.5KW, 2HP, 380-480V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-402-H3EF 72 (2.83) mm (inch) 220 (8.66) mm (inch) 150 (5.9) mm (inch) 60 (2.36) mm (inch) 130.5 (5.14) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 1.5 (3.3) kg (lbs) —

Technical source 009 — Variable speed drive E710-403F-H3S-IP20, 2.2KW, 3HP, 380-480V

Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-403-H3SF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-403F-H3S-IP20, 2.2KW, 3HP, 380-480V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 7 / 7 Constant Torque (kW/A): 2.2 / 5.5; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 2.20 Datasheet PDF / E710-403-H3SF-IP20-datasheet.pdf

P017 / Variable speed drive E710-403F-H3S-IP20, 2.2KW, 3HP, 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 3 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 4 as printed in field/value —
Output Rating / Rated Output Current(A) 5.5 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 3 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 2.2 as printed in field/value —
Output Rating / Maximum Output Voltage(V) Three Phase, 480V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V to 480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-403F-H3S-IP20, 2.2KW, 3HP, 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-403F-H3S-IP20, 2.2KW, 3HP, 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Other Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-403F-H3S-IP20, 2.2KW, 3HP, 380-480V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-403-H1SF 87 (3.43) mm (inch) 220 (8.66) mm (inch) 164 (6.46) mm (inch) 73 (2.87) mm (inch) 145 (5.71) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 2 (4.41) kg (lbs) —

Technical source 010 — Variable speed drive E710-405-H3SF-IP20, 3.7KW, 5HP, 380-480V

Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-405-H3SF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-405-H3SF-IP20, 3.7KW, 5HP, 380-480V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 8 / 8 Constant Torque (kW/A): 3.7 / 9; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 3.70 Datasheet PDF / E710-405-H3SF-IP20-datasheet.pdf

P017 / Variable speed drive E710-405-H3SF-IP20, 3.7KW, 5HP, 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 5 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 6.7 as printed in field/value —
Output Rating / Rated Output Current (A) 9 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 5 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 3.7 as printed in field/value —
Output Rating / Maximum Output Voltage(V) Three Phase, 480V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V to 480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-405-H3SF-IP20, 3.7KW, 5HP, 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-405-H3SF-IP20, 3.7KW, 5HP, 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Other Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-405-H3SF-IP20, 3.7KW, 5HP, 380-480V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-405-H1SF 87 (3.43) mm (inch) 220 (8.66) mm (inch) 164 (6.46) mm (inch) 73 (2.87) mm (inch) 145 (5.71) mm (inch) 5 (0.2) mm (inch) M4 mm (inch) 2 (4.41) kg (lbs) —

Technical source 011 — Variable speed drive E710-408-H3SF-IP20, 5.5KW, 7.5HP, 380-480V

Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-408-H3SF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-408-H3SF-IP20, 5.5KW, 7.5HP, 380-480V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 9 / 9 Constant Torque (kW/A): 5.5 / 13; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 5.50 Datasheet PDF / E710-408-H3SF-IP20-datasheet.pdf

P017 / Variable speed drive E710-408-H3SF-IP20, 5.5KW, 7.5HP, 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 7.5 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 9.9 as printed in field/value —
Output Rating / Rated Output Current(A) 13 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 7.5 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 5.5 as printed in field/value —
Output Rating / Maximum Output Voltage(V) Three Phase, 480V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V to 480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-408-H3SF-IP20, 5.5KW, 7.5HP, 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-408-H3SF-IP20, 5.5KW, 7.5HP, 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Other Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-408-H3SF-IP20, 5.5KW, 7.5HP, 380-480V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-408-H3SF 109 (4.29) mm (inch) 250 (9.84) mm (inch) 169 (6.65) mm (inch) 94 (37) mm (inch) 194.5 (7.66) mm (inch) 6 (0.24) mm (inch) M4 mm (inch) 2.3 (5.07) kg (lbs) —

Technical source 012 — INV-E710-IP20-03.pdf

Source download: INV-E710-IP20-03.pdf.

Conditions for this section:

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 9 / 9 Constant Torque (kW/A): 5.5 / 13; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 5.50 2D Drawing PDF / INV-E710-IP20-03.pdf
93 / 10 / 10 Constant Torque (kW/A): 7.5 / 17; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 7.50 2D Drawing PDF / INV-E710-IP20-03.pdf

P017 / INV-E710-IP20-03.pdf — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Identity / type E710-IP20-F3 as printed —
Identity / drawing_number INV-E710-IP20-03 as printed —
Drawing / Front-view overall width 109 drawing units; not explicitly stated on this sheet C1
Drawing / Horizontal mounting-hole centres 94 drawing units; not explicitly stated on this sheet C1
Drawing / Front-view overall height 207 drawing units; not explicitly stated on this sheet C1
Drawing / Vertical mounting-hole centres 194.5 drawing units; not explicitly stated on this sheet C1
Drawing / Overall depth including projecting front control 169.8 drawing units; not explicitly stated on this sheet C1
Drawing / Body depth excluding projecting front control 163.5 drawing units; not explicitly stated on this sheet C1
Drawing / Mounting holes 4-M4 as printed C1
Drawing note / 1 No electrical rating or model-to-frame schedule is printed on this drawing. Use the matching E710 datasheet to establish applicability. as printed —
Drawing note / 2 Units are not explicitly stated on the supplied drawing; numeric values retained without asserting a conversion. as printed —

Technical source 013 — Variable speed drive E710-410-H3SF-IP20, 7.5KW, 10HP, 380-480V

Source-label discrepancy: a temperature field contains vibration values. It does not establish an ambient rating.

Source download: E710-410-H3SF-IP20-datasheet.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P017, Variable speed drive E710-410-H3SF-IP20, 7.5KW, 10HP, 380-480V, page 6

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
93 / 10 / 10 Constant Torque (kW/A): 7.5 / 17; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 7.50 Datasheet PDF / E710-410-H3SF-IP20-datasheet.pdf

P017 / Variable speed drive E710-410-H3SF-IP20, 7.5KW, 10HP, 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name E710 as printed in field/value —
Inverter Capacity (HP) 10 as printed in field/value —
Output Rating / Rated Output Capacity (KVA) 13.3 as printed in field/value —
Output Rating / Rated Output Current(A) 17 as printed in field/value —
Output Rating / Maximum Applicable Motor / (HP) 10 as printed in field/value —
Output Rating / Maximum Applicable Motor / (KW) 7.5 as printed in field/value —
Output Rating / Maximum Output Voltage (V) Three Phase, 480V as printed in field/value —
Output Rating / Maximum Output Frequency (Hz) 599.0Hz as printed in field/value —
Input Power / Rated Voltage, Frequency Three Phase, 380V to 480V, 50/60Hz as printed in field/value —
Input Power / Allowable Voltage Fluctuation -15% ~ +10% as printed in field/value —
Input Power / Allowable Frequency Fluctuation ±5% as printed in field/value —
Braking transistor Built-in as printed in field/value —
Control characteristics / Display LED keypad as printed in field/value —
Control characteristics / Control Modes IM: V/F, V/F+PG, SLV, SV, SLV2 PM: SV, SLV SRM (only for special projects): PMA-SyRM-SLV, SyRM-SLV IM/PM: V/F+PG, SV (on request) as printed in field/value —
Control characteristics / Output Frequency 0.01~599.0Hz as printed in field/value —
Control characteristics / Frequency Accuracy ±0.3Hz as printed in field/value —
Control characteristics / Speed Control Accuracy 1% (Sensorless Vector Control Mode) 3%(VF) as printed in field/value —
Control characteristics / Frequency setting / resolution Digital references: 0.01Hz, Analog refrences:0.06Hz at 60Hz as printed in field/value —
Control characteristics / Output Frequency Resolution 0.01Hz as printed in field/value —
Control characteristics / Inverter Overload 150%/1 min as printed in field/value —
Control characteristics / Frequency Setting Signal DC 0~10V/4~20mA as printed in field/value —

P017 / Variable speed drive E710-410-H3SF-IP20, 7.5KW, 10HP, 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Control characteristics / Acceleration/Deceleration Time 2-stage acceleration/deceleration time can be set (0.1~3600.0 Sec) as printed in field/value —
Control characteristics / Voltage/Frequency / Characteristics Custom V/F curve based on parameters as printed in field/value —
Control characteristics / Braking Torque About 10% as printed in field/value —
Control characteristics / Main Control Functions Auto tuning, Soft-PWM, Over voltage protection, Speed search, Restart upon momentary power loss, 2 sets of PID control, Slip Compensation, RS- 485 communication standard, Simple PLC function, 2 sets of analog outputs, Safety switch. as printed in field/value —
Control characteristics / Other Functions Accumulated power-on/ run time, 30 sets of fault history records and latest fault record state, Energy-saving function setting, Phase loss protection, Smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up/Down operation, Modbus, Display of multi-engineering unit, Local/ Remote switch, SINK/SOURCE input interface selection, User parameter settings as printed in field/value —
Protection Functions / Stall Protection Current level can be setting (It can be set separately in acceleration or constant speed; it can be set with or without protection in deceleration) as printed in field/value —
Protection Functions / Over Current (OC) and Output Short-circuit (SC) Protection It stops when the output current exceeds 300% of the inverter rated current as printed in field/value —
Protection Functions / Inverter Overload If inverter rated current 150%/1min is exceeded, inverter stops. as printed in field/value —
Protection Functions / Motor Overload Protection (OL1) Electrical overload protection curve as printed in field/value —
Protection Functions / Over Voltage If the main circuit DC voltage rises over 410V (200V class)/ 820V (400V as printed in field/value —
Protection Functions / Protection (OV) class), the motor stops running. as printed in field/value —
Protection Functions / Under Voltage Protection (UV) If the main circuit DC voltage falls below 190V (200V class) /380V (400V class), the motor stops running. as printed in field/value —
Protection Functions / Momentary power loss Power loss exceeds 8 milliseconds. as printed in field/value —
Protection Functions / restart Auto-restart function available after momentary power loss in 2 sec.;3HP below for 1sec as printed in field/value —
Protection Functions / Overheat Protection (OH) Thermistor sensor built-in IGBT module as printed in field/value —
Protection Functions / Ground Fault Protection (GF) Protection by inverter software as printed in field/value —
Protection Functions / Charge Indicator None as printed in field/value —
Protection Functions / Output Phase Loss Protection If the OPL function acts, the motor stops rotation automatically as printed in field/value —
Input Phase Loss (IPL) Protection If the IPL is detected, the motor stops automatically as printed in field/value —

P017 / Variable speed drive E710-410-H3SF-IP20, 7.5KW, 10HP, 380-480V — source page 3 — PDF page 3

Specification Value Unit / basis Conditions
Environment Specification / Install location Indoor (Protected from corrosive gases and dust) as printed in field/value —
Environment Specification / Ambient Temperature 10Hz≦f≦57Hz: ±0.075mm Amplitude; 57Hz≦f≦150Hz: 1.0G Acceleration: (in accordance with IEC60068-2-6 standards) as printed in field/value —
Environment Specification / Storage Temperature -20~+70℃ (-4℉~+158℉) as printed in field/value —
Environment Specification / Humidity 95% RH or less (no condensation) as printed in field/value —
Environment Specification / Altitude and Vibration Altitude: Below 1000 m (3281 ft.), It is required to derate 1% of current at each additional 100 m, the maximum altitude is 3000 m. Vibration: Maximum acceleration: 1.0G (9.8m/s2), from 49.84 to 150 Hz Displacement amplitude: 0.3mm (peak value), between 10 to 49.84 Hz (In accordance with IEC60068-2-6 standards) as printed in field/value —
Communication Function Built-in RS-485 as standard (Modbus protocol with standard RJ45) as printed in field/value —
Electromagnetic Interference (EMI) In compliance with EN61800-3 standard as printed in field/value —
Electromagnetic / Compatibility (EMS) In compliance with EN61800-3 standard as printed in field/value —
Certification / CE In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) as printed in field/value —
Certification / UL EN61800-5-1 as printed in field/value —
Option Card 1.PG feedback card dedicated for IM (induction motor), available in Line Driver type and Open Collector type output options. 2.Ethernet communication expansion cards: Profinet/ OPC UA/ EtherCAT/ MODBUS TCP/ Ethernet IP/ BACnet IP 3.Others Protocols: TCP-IP/ Profibus DP/ CANopen as printed in field/value —

P017 / Variable speed drive E710-410-H3SF-IP20, 7.5KW, 10HP, 380-480V — source page 6 — PDF page 6

Configuration / printed row W H D W1 H1 t d NW in kg(lbs) Conditions
E710-410-H3SF 109 (4.29) mm (inch) 250 (9.84) mm (inch) 169 (6.65) mm (inch) 94 (37) mm (inch) 194.5 (7.66) mm (inch) 6 (0.24) mm (inch) M4 mm (inch) 2.3 (5.07) kg (lbs) —

Selection checks and source differences

E710-202-H1SF datasheet title1.5kW/2HP conflicts with its0.4kW/0.5HP/2.8A block. Catalogue gives1.5kW/7.5A. Verified visually in original page1; no correction substituted.

Some datasheets print Single Phase as maximum output voltage description, while manual schedules specify three-phase motor output. Several Ambient Temperature cells actually contain vibration data. Original PDF page3 confirms the misplaced vibration text; these are not valid temperature values.

Catalogue operating minimum−20°C conflicts with manual/website−10°C. Side-by-side zero gap is40°C maximum, not unconditional50°C operation. Carrier, enclosure and dust-sticker derating scopes remain separate.

Catalogue overview S-type range403–430/202–220 differs from code legend403–410/202–208, wiring403–410/202–203 and ten explicit local models. Manual includes additional200V models. No code combinations or local stock inferred.

Website six modes versus catalogue seven; manual marks V/F+PG,SV,PMSV special-project and retains reserved settings. Basic E and Standard S capabilities remain separate. Catalogue Basic E has no STO even where generic datasheet prose mentions a safety switch.

Catalogue narrative depth150–169mm differs from the built-in-filter tables'195.5/207/210mm. Manual has separate filtered/unfiltered/NEMA1 outlines and one larger-frameIP00 heading. Literal duplicate D heading withM4 values remains identified; dimensions are not mixed across constructions.

The catalogue0.37kW designation and manual/individual0.4kW description remain separately stated. Operating-point loss-table nominal currents differ from electrical rating schedules and CDMtuple definitions/standby units are not supplied; no universal efficiency or replacement current inferred.

Predictive diagnosis marketing describes continuous early warnings; manual requires configured capacitor/fan/IGBT monitoring and reset after replacement. No guaranteed failure prevention, unconditional90% replacement policy or guaranteed remaining life is stated in the editorial.

STO standards/certification and EMC claims are supplier statements, not independently current-validity proof or a machine-level safety approval. Removing contactors and immediate restart are not general recommendations. Special Fire mode remains separately scoped.

Manual sections include apparent wording, default and parameter-reference inconsistencies, source model codes and protocol-specific restrictions. Every unique table and substantive page note is retained with its physical page; unresolved material has not been silently normalized into an engineering instruction.

All collected PDF/archive associations reconcile, with ten website rows linked to thirteen distinct technical PDFs. Shared outline files have no printed electrical model/frame schedule. Current static-page refresh did not replace a full live pagination crawl; source coverage and engineering verification remain distinct.

Product documents

Our company certificates and conditions of sale remain separate from the selected product’s ratings and approvals.

Talk to our team about your application, supply, motor rating and configuration.