TECO L510s Compact V/F and Sensorless Vector Drive

Our L510s brings compact motor control to conveyors, packaging machinery, fans, pumps and small industrial equipment. We combine V/F control with torque compensation, sensorless vector control (SLV), PID, built-in communications and a straightforward keypad to help you match the drive to the application.

The local range page describes 200–240 V single-phase input and 400 V-class three-phase input, with three-phase motor output. Select the complete model, motor current and supply together: a power rating alone does not identify a compatible drive.

Select the supply and exact model

Our website introduction describes 0.2–2.2 kW single-phase-input and 0.75–2.2 kW three-phase-input models. Its feature list and the short brochure instead state 0.75–2.2 kW single-phase input. The broader March 2016 catalogue and January 2016 manual include additional voltage classes and larger ratings. We retain those as catalogue configurations, without representing them all as current Australian stock.

Source family Input supply Broader catalogue output range Motor output
100 V class Single-phase 100–120 V, 50/60 Hz 0.2–0.75 kW Three-phase 0–240 V
200 V class, single-phase Single-phase 200–240 V, 50/60 Hz 0.2–2.2 kW Three-phase 0–240 V
200 V class, three-phase Three-phase 200–240 V, 50/60 Hz 0.2–7.5 kW Three-phase 0–240 V
400 V class Three-phase 380–480 V, 50/60 Hz 0.75–11 kW Three-phase 0–480 V

The catalogue specifies +10%/−15% input-voltage tolerance. Exact output current, input current, kVA, weight and allowable momentary power-loss time remain with each model table below. These limits are not interchangeable across voltage classes. Confirm availability and the supplied nameplate with us.

The code distinguishes supply class, horsepower code, single- or three-phase input, filter and input logic. F identifies the built-in EMC filter; a blank filter position means no filter. The range-page filter description therefore does not apply to every model in the wider catalogue. Frames 1/2 use separate NPN/PNP versions; frames 3/4 have selectable input logic. Do not construct an unlisted model by combining independent code options.

Our collected website register has eight rows linked to seven distinct six-page datasheets. Its 0.37 kW row links to the 0.2 kW L510-2P2-SH1F-P sheet, which also serves the 0.2 kW row. We retain both link associations and flag the mismatch; that PDF does not establish a 0.37 kW configuration. The broader catalogue uses 0.4 kW in its 2P5 column. These values have not been silently substituted.

Motor control and application features

V/F mode provides six preset curves and one adjustable curve. SLV supports more demanding low-speed and changing-load applications. The datasheets state 150% starting torque at 3 Hz in V/F and at 1 Hz in vector control; these are supplier performance statements for the stated mode, not a guarantee for every motor and load.

Published output frequency is 0.01–599.00 Hz and carrier-frequency selection is 1–16 kHz, with 5 kHz shown as the catalogue default. Always respect the motor and machine speed limits and the drive's model-specific carrier/ambient derating curves. The manual contains a 650.00 Hz figure label alongside 599.00 Hz parameter limits; we do not use the figure to extend the operating range.

Features include eight preset speeds, jog, external up/down frequency adjustment, two acceleration/deceleration settings, four S-curve settings, three skip-frequency bands and an automatic sequencer. The sequencer can run a single cycle, repeat a cycle or hold its final speed; its resume-from-step and restart-new-cycle modes are different. Group 05 controls preset speeds and individual ramps; Group 06 controls sequence frequencies, dwell times and directions. Source examples are illustrations, not recommended machine settings.

Torque boost, slip compensation and low-frequency compensation depend on the selected control mode and motor data. In SLV, the manual requires motor-nameplate parameters and an appropriate autotune; autotune is not available for multiple motors on one drive and must be repeated when replacing the motor. We retain the mode-specific parameter descriptions rather than applying a single set of gains to every application.

Keypad, inputs and communications

The built-in LED display and keypad provide run/stop, parameter entry and a speed potentiometer. Monitoring includes output frequency/current/voltage, DC-bus voltage, line speed, PID feedback, I/O state, heatsink temperature, software version, accumulated operating time and the latest three faults. Key layouts differ between frame groups. Display examples in the manual are not operating measurements.

The source describes five multifunction digital inputs, voltage and current analogue inputs, one 0–10 V analogue output and a multifunction relay. Terminal arrangements vary: the smaller frames show RA/RB, while frames 3/4 show RA/RB/RC and the additional logic-selection terminals. Confirm the complete source wiring diagram; terminal names and tabulated functions alone are not a wiring design.

RS485 Modbus is built in, with ASCII and RTU covered by the manual. BACnet MS/TP is also described in the catalogue/manual. Profibus-DP, DeviceNet, CANopen and TCP/IP require the listed optional interface/gateway arrangements; they are not all native ports. The RJ45 interface supports the specified PC/copy accessories, not an assumed Ethernet connection.

The manual separates station address, communication mode, baud rate, parity, stop bits, timeout response, error tolerance and transmit delay. Its Modbus examples cover read registers, single/multiple register writes and loopback. Keep read-only monitor registers distinct from command registers, write zero to unused command bits and do not write reserved registers. The source lists a maximum frame length of 80 bytes, read limits of 37 RTU / 17 ASCII registers, and multiple-write limits of 35 RTU / 15 ASCII, within the stated same-group restrictions. The 10H section calls these “read” limits despite describing writes; the original wording remains flagged.

PID and process control

PID supports selectable target and feedback sources, proportional/integral/derivative settings, offset, filtering, feedback-loss detection, integration limits and sleep/wake thresholds with delays. PID selection depends on the main/alternative frequency source; the manual says the target and feedback selections must not be identical. Feedback-loss behaviour can either continue running with a warning or stop, depending on configuration.

Use source-specific analogue gain, bias, polarity and scan settings. A longer scan interval can smooth unstable signals but slows response. The manual's Group 04 index reverses the AVI/ACI column headings relative to its detailed description: AVI is described as voltage and ACI as current in the detailed section. Both source tables remain visible. Confirm the selected hardware and settings rather than relying on the inconsistent index heading.

Installation environment, dimensions and protection

The enclosure is IP20. It is not an outdoor, dust-tight or washdown enclosure. Published operating ambient is −10°C to +50°C with a fan and −10°C to +40°C without a fan, with −20°C to +60°C storage and non-condensing humidity as specified in the source. Protect the drive from sunlight, rain, moisture, oil mist, salt, conductive dust, corrosive gases and excessive vibration.

Install vertically on suitable non-combustible material with adequate heat removal. The manual illustrates 12 cm above/below and 5 cm side clearance, including side-by-side spacing; actual panel cooling must suit its heat losses and ambient conditions. DIN-rail kits are frame-specific options. Use the exact model's approved outline: dimensions and mounting-hole labels are retained in the source tables, with no dimensions inferred from drawing scale.

There are real outline differences between documents. For example, the L510-2P2-SH1F-P datasheet gives H1 = 122 mm and H2 = 131 mm, while the catalogue frame-1 table gives H1 = 131 and H2 = 122. The source drawings and labels must be checked together for installation. Catalogue frame-2 grouping also differs from the manual's separate voltage-class dimension groups.

Overload capability is described as 150% for one minute in the catalogue; individual sheets add every ten minutes. Protection functions include over/undervoltage, overcurrent/stall prevention, heatsink overtemperature, motor electronic overload and PTC-related functions. Auto-restart, continued running after an overload warning and communication/PID failure responses depend on settings. A feature list is not proof that every protection is enabled or suitable for the motor.

The PTC circuit has frame-dependent input impedance and sensor/divider requirements. Use the complete instructions and actual sensor characteristics. For multiple motors, the manual requires separate motor overload protection; its general and UL-appendix internal-overload instructions differ and must be resolved for the installation.

Commissioning, stopping and maintenance

We recommend commissioning by personnel qualified for the drive and machine. Verify the supply, motor nameplate, earthing, cable/terminal ratings, input logic, protective devices and command sources before energising. Keep input power separate from T1/T2/T3 motor outputs. The full manual governs wiring, EMC, discharge and testing requirements; this guide does not replace it.

The quick guide directs users to enter motor current, speed, power and frequency in Group 02, choose run-command source with 00-02, external two-/three-wire mode with 00-04, and speed source with 00-05. It calls external control the default for 00-02, while manual page 53 prints 0, keypad as the factory setting. Check the actual unit before applying a run signal. The quick guide shows a two-second hold to save; the manual describes a long press without the same numerical duration.

Direct run on power-up, recovery after a supply interruption and fault auto-restart can cause unexpected movement. The manual's 07-04 = 0 permits direct running under its specified external-command conditions. A software stop, base block or rapid-stop input is not an independently validated machine emergency-stop or electrical isolation function. Three-wire control requires the stated normally closed stop contact and its own terminal allocation; use the full model-specific diagram.

DC-injection braking settings differ by frame: the manual describes a voltage-based level for frames 1/2 and a current-based level for frames 3/4. Dynamic-braking terminals, resistor sizes and permissible duty are model-specific. The braking table prints 3.5 kW for 205/405 where the rating tables print 3.7 kW; it is preserved as a source discrepancy. Do not derive a new resistor selection from that conflict. Regeneration-prevention functions may change output frequency or deceleration time and need application review.

Before inspection, isolate all supplies, wait the specified discharge time—at least five minutes in the main manual—and verify the safe condition using the complete procedure and drive label. The maintenance chapter requires clean cooling paths, secure earth/terminal connections and appropriate temperature/humidity; it prohibits insulation testing on the control circuit. Fault tables distinguish automatic/manual recovery and non-recoverable faults. Repair flowcharts remain in the complete manual for qualified service work, not as instructions to probe energised circuitry from this page.

For a drive stored for a long period, follow the source's time-dependent capacitor-reforming procedure before service. The reference table is included below. Do not infer that normal power-up is appropriate for every storage interval.

Accessories and documentation

Options include JN5-CU copy unit/remote keypad, JN5-CM-USB PC cable, JN5-CM-PDP/DNET/CAN/TCPIP communication modules, JN5-GK-L01/L02 grounding kits and JN5-DIN-L01/L02 DIN kits for the stated frames. Reactors, contactors, breakers, fuses and braking resistors have separate selection tables. Listing an accessory does not mean it is included in the supplied drive.

The DriveLink V1.935 ZIP is preserved as a software download, separate from manuals and specifications. We have not treated its executable as technical text or tested its compatibility. The manual prints Ver.02, January 2016; the filename's V02_1 suffix is retained without inventing a newer edition date. Historical UL/cUL/CE/RCM and EMC statements remain supplier claims for the stated models and conditions, not independent confirmation of current certification.

The reference sections below retain the model sheets, catalogue and manual tables, parameter ranges/defaults/notes, fault codes, accessories and communication registers. Repeated overlap pages appear once. Complete wiring, curves, worked setup examples, repair procedures and blank parameter-record forms remain linked in the original documents. Ask us to confirm the exact model, motor duty, supply, environment, I/O, communications and braking requirements for your application.

Catalogue — L510s-Catalogue.pdf, page 2: SRC-8caa3ee543f5f86e-SS17-P2-T3 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

L510s-Catalogue.pdf · P005 · source page 2

Context: 100V1phase0.2–0.75kW;200V1phase0.2–2.2kW;200V3phase0.2–7.5kW;400V3phase0.75–11kW, as endpoints of colored source bands. Red extends200V3phase from3.7–7.5kW and400V3phase from3.7–11kW. Source labels5.5kW/8HP on band, while basic table208states7.5HP; retain discrepancy.

Table conditions: L510s-Catalogue.pdf PDF2; full original header row retained; model/parameter units and blanks govern each column.

SRC-8caa3ee543f5f86e-SS17-P2-T3 — reviewed source table — PDF page 2

Source column 1 Source column 2 Source column 3 Source column 4
Model : L510-□□□-SH1-N/P 1P2 1P5 101
Horse power (HP) 0.25 0.5 1
Suitable motor capacity (kW) 0.2 0.4 0.75
Rated output current (A) 1.8 2.6 4.3
Rated capacity (kVA) 0.7 1.0 1.7
Input voltage range(V) Single Phase : 100~120V(+10%-15%),50/60HZ None None
Output voltage range(V) Three phase 0~240V None None
Input current (A)* 9.5 13 19
weight(kG) 0.9 0.9 1.4
Allowable momentary
power loss time (S)
1.0 1.0 1.0
Enclosure IP20 None None

Catalogue — L510s-Catalogue.pdf, page 2: SRC-8caa3ee543f5f86e-SS17-P2-T4 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

SRC-8caa3ee543f5f86e-SS17-P2-T4 — reviewed source table — PDF page 2

Source column 1 Source column 2 Source column 3 Source column 4 Source column 5 Source column 6 Source column 7
Model : L510-□□□-SH1-N/P
(L510-□□□-SH1F-P)
2P2 2P5 2P7 201 202 203
Horse power (HP) 0.25 0.5 0.75 1 2 3
Suitable motor capacity (kW) 0.2 0.4 0.55 0.75 1.5 2.2
Rated output current (A) 1.8 2.6 3.4 4.3 7.5 10.5
Rated capacity (kVA) 0.7 1.0 1.3 1.7 3.0 4.0
Input voltage range(V) Single Phase : 200~240V(+10%-15%),50/60HZ None None None None None
Output voltage range(V) Three phase 0~240V None None None None None
Input current (A)* 4.9 7.2 9 11 15.5 21
weight(kG)
weight with filter(kG)
0.9
1.0
0.9
1.0
0.9
1.0
0.9
1.0
1.4
1.5
1.4
1.5
Allowable momentary
power loss time (S)
1.0 1.0 1.0 1.0 2.0 2.0
Enclosure IP20 None None None None None

Catalogue — L510s-Catalogue.pdf, page 2: SRC-8caa3ee543f5f86e-SS17-P2-T5 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

SRC-8caa3ee543f5f86e-SS17-P2-T5 — reviewed source table — PDF page 2

Source column 1 Source column 2 Source column 3 Source column 4 Source column 5 Source column 6
Model : L510-□□□-SH3-N/P 2P2 2P5 201 202 203
Horse power (HP) 0.25 0.5 1 2 3
Suitable motor capacity (kW) 0.2 0.4 0.75 1.5 2.2
Rated output current (A) 1.8 2.6 4.3 7.5 10.5
Rated capacity (kVA) 0.7 1.0 1.7 3.0 4.0
Input voltage range(V) Three phase : 200~240V(+10%-15%),50/60HZ None None None None
Output voltage range(V) Three phase 0~240V None None None None
Input current (A)* 3.0 4.0 6.4 9.4 12.2
weight(kG) 0.9 0.9 0.9 1.4 1.4
Allowable momentary
power loss time (S)
1.0 1.0 1.0 2.0 2.0
Enclosure IP20 None None None None

Catalogue — L510s-Catalogue.pdf, page 2: SRC-8caa3ee543f5f86e-SS17-P2-T6 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

SRC-8caa3ee543f5f86e-SS17-P2-T6 — reviewed source table — PDF page 2

Source column 1 Source column 2 Source column 3 Source column 4
Model : L510-□□□-SH3 205 208 210
Horse power (HP) 5 7.5 10
Suitable motor capacity (kW) 3.7 5.5 7.5
Rated output current (A) 17.5 26 35
Rated capacity (kVA) 6.7 9.9 13.3
Input voltage range(V) Three phase : 200∼240V (+10%-15%),50/60HZ None None
Output voltage range(V) Three phase 0~240V None None
Input current (A)* 19.3 28.6 38.5
weight(kG) 2.5 6 6
Allowable momentary
power loss time (S)
2.0 2.0 2.0
Enclosure IP20

Catalogue — L510s-Catalogue.pdf, page 2: SRC-8caa3ee543f5f86e-SS17-P2-T7 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

SRC-8caa3ee543f5f86e-SS17-P2-T7 — reviewed source table — PDF page 2

Source column 1 Source column 2 Source column 3 Source column 4
Model : L510-□□□-SH3-N/P 401 402 403
(L510-□□□-SH3F-P)
Horse power (HP) 1 2 3
Suitable motor capacity (kW) 0.75 1.5 2.2
Rated output current (A) 2.3 3.8 5.2
Rated capacity (kVA) 1.7 2.9 4.0
Input voltage range(V) Three Phase : 380~480V (+10%-15%),50/60HZ None None
Output voltage range(V) Three phase 0~480V None None
Input current (A)* 4.2 5.6 7.3
weight(kG)
weight with filter(kG)
1.4
1.5
1.4
1.5
1.4
1.5
Allowable momentary
power loss time (S)
2.0 2.0 2.0
Enclosure IP20 None None

Catalogue — L510s-Catalogue.pdf, page 2: SRC-8caa3ee543f5f86e-SS17-P2-T8 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

SRC-8caa3ee543f5f86e-SS17-P2-T8 — reviewed source table — PDF page 2

Source column 1 Source column 2 Source column 3 Source column 4 Source column 5
Model : L510-□□□- SH3
(L510-□□□- SH3F)
405 408 410 415
Horse power (HP) 5 7.5 10 15
Suitable motor capacity (kW) 3.7 5.5 7.5 11
Rated output current (A) 9.2 13.0 17.5 24
Rated capacity (kVA) 7.0 9.9 13.3 18.3
Input voltage range(V) Three Phase :380∼480V (+10%-15%),50/60HZ None None None
Output voltage range(V) Three Phase 0∼480V None None None
Input current (A)* 10.1 14.3 19.3 26.4
weight(kG)
weight with filter(kG)
2.5
2.7
2.5
2.7
6
6.3
6
6.3
Allowable momentary
power loss time (S)
2.0 2.0 2.0 2.0
Enclosure IP20 None None None

Catalogue — L510s-Catalogue.pdf, page 3: SRC-8caa3ee543f5f86e-SS17-P3-T3 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

L510s-Catalogue.pdf · P005 · source page 3

Context: Model identification source labels grouped by their drawn legend boxes; no valid model combinations inferred. Example: L510 - 1 P2 - S H 1 [blank filter slot] - N. Supply voltage:1=100V Class;2=200V Class;4=400V Class. Horsepower,100V Class:P2=0.25HP;P5=0.5HP;01=1HP. Horsepower,200V Class:P2=0.25HP;P5=0.5HP;P7=0.75HP;01=1HP;02=2HP;03=3HP;05=5HP;08=7.5HP;10=10HP. Horsepower,400V Class:01=1HP;02=2HP;03=3HP;05=5HP;08=7.5HP;10=10HP;15=15HP. Series Name:S=510s series. Specification:H=Standard Type. Power supply:1=Single phase;3=Three phase. Filter:F=Built-in;Blank=None. P=PNP;N=NPN. Original diagram governs code-position geometry.

Context: Drawing labels only; no connection topology inferred. NPN Input. AC Power source; Main Switch; Fuse; Power input L1(L),L2,L3(N); Inverter output T1,T2,T3; M; E; Ground. P,BR for400V class. Multi-function input labels:S1,S2,S3,S4,S5,COM. CON2 RS485 Pin1 to Pin8:1=Data+;2=Data-;3=Data+;4=RXD0;5=TXD0;6=Data-;7=5V;8=GND. Relay output labels:RA,RB;250VAC/1A;(30VDC/1A). Analog input-side labels:+10V;AVI(0~10V);ACI(0~20mA/4~20mA);AGND;Frequency reference or PID;External speed potentiometer=10Kohm or PID input. Separate output-side labels:AO;AGND;Multi-function output0~10V;positive/negative polarity symbols. Original image governs all wiring geometry.

Context: Drawing labels only; no connection topology inferred. PNP Input. AC Power source; Main Switch; Fuse; Power input L1(L),L2,L3(N); Inverter output T1,T2,T3; M; E; Ground. P,BR for400V class. Multi-function input labels:S1,S2,S3,S4,S5,+24V. CON2 RS485 Pin1 to Pin8:1=Data+;2=Data-;3=Data+;4=RXD0;5=TXD0;6=Data-;7=5V;8=GND. Relay output labels:RA,RB;250VAC/1A;(30VDC/1A). Analog input-side labels:+10V;AVI(0~10V);ACI(0~20mA/4~20mA);AGND;Frequency reference or PID;External speed potentiometer=10Kohm or PID input. Separate output-side labels:AO;AGND;Multi-function output0~10V;positive/negative polarity symbols. Original image governs all wiring geometry.

Context: Frame3 & Frame4 series. Drawing labels only; no connection topology inferred. AC Power source; Main Switch;Fuse;Power input L1,L2,L3;Inverter output T1,T2,T3;M;P;BR;E;Ground. Multi-function input labels:S1,S2,S3,S4,S5;COM:NPN/+24V:PNP;COM:PNP/+24V:NPN(1);SC(2). CON2 RS485 Pin1 to Pin8:1=Data+;2=Data-;3=Data+;4=Reserved;5=Reserved;6=Data-;7=5V;8=GND. Relay Output labels:RA,RB,RC. Input-side labels:+10V;AVI(0~10V);ACI(0~20mA/4~20mA);AGND;External speed potentiometer=10Kohm or PID input. Separate output-side labels:AO;AGND;Multi-function output0~10V;positive/negative polarity symbols. Source note1:NPN:24V connected to SC;PNP:COM connected to SC. Source note2:If SC is not connected,inverter parameter group03-XX can’t be enabled. Original image governs all wiring geometry.

Table conditions: L510s-Catalogue.pdf PDF3; full original header row retained; model/parameter units and blanks govern each column.

SRC-8caa3ee543f5f86e-SS17-P3-T3 — reviewed source table — PDF page 3

Source column 1 Source column 2 Source column 3
Item None L510s
Control Mode None V/F Control + SLV control
Frequency Range 0.01~599.00Hz
None Setting resolution Digital input : 0.01Hz
None None Analog input : 0.015Hz/60Hz or 0.012Hz/50Hz
None Setting Keypad : Set directly with ▲▼ keys or the VR (Potentiometer) on the keypad
None None External Input Terminals: AVI(0/2~10V), ACI(0/4~20mA)input
None None Multifunction input up/down function(Group3)
None None Setting frequency by communication method.
None Frequency limit Lower and upper frequency limits
None None 3 -skip frequency settings.
Run Frequency limit Keypad run, stop button
None None External terminals:
Multi- operation-mode 2 / 3 wire selection
Jog operation
None None Run signal by communication method.
Main
Controls
V / F curve setting 6 fixed curves and one customized curve
None Carrier frequency 1~16kHz(default 5kHz)
None Acceleration and
deceleration control
2 off Acc / dec time parameters.
4 off S curve parameters.
None Multifunction input 19 functions (refer to description on group3)
None None 5 points, Frame1/2 : NPN&PNP by separate models, Frame 3/4 : NPN&PNP switchable
None Multifunction output 16 functions (refer to description on group3)
None Multifunction analog
output
5 functions (refer to description on group4)
None None 1 point (0~10V)
None Main features Overload Detection, 8 preset speeds, Auto-run, Acc/Dec Switch (2 Stages), Main/Alt run Command select,
Main/Alt Frequency Command select, PID control, torque boost, V/F start Frequency ,Fault reset.
Display LED Display: parameter/parameter value/frequency/line speed/DC voltage/output voltage/output current/PID
feedback/input and output terminal status/Heat sink temperature/Program Version/Fault Log.
Display LED Status Indicator For run/stop/forward and reverse.
Protective
Functions
Overload Capacity and
maximum current
150% of rated current under 60 seconds (150%/1min)
Protective
Functions
Over voltage 100V/200V : Over 410V, 400V : Over 820V
Protective
Functions
Under voltage 100V/200V : Under 190V, 400V : Under 380V
Protective
Functions
Momentary Power
Loss Restart
Inverter auto-restart after a momentary power loss.
None Stall Prevention Stall prevention for Acceleration/ Deceleration/ and continuous Run.
None Short-circuit output
terminal
Electronic Circuit Protection
None Grounding Fault Electronic Circuit Protection
None Additional protective
functions
heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, fault
output, reverse prohibit, Number of auto restart attempts, Parameter lock, motor PTC over-temperature
protection,over voltage suppression function.
International Certification None CE/UL/cUL/RCM
Communication None RS485 (Modbus) built in, with one to one or one to many control.
Built-in BACnet communication.
Profibus, DeviceNet, CANopen, TCP/IP by gateway.
Environment Operating temperature -10~50°C(with fan), -10~40°C(without fan)
None Storage temperature -20~60°C
None Humidity Under 95%RH ( no condensation)
None Vibration 2G(19.6m/s²)for 57~150Hz and below. 0.3mm for 10~57Hz (According to IEC60068-2-6 standard)
None EMC Compliance EN61800-3, First Environment
None LVD Compliance EN50178
None Electrical Safety UL508C
None Protection level IP20

Catalogue — L510s-Catalogue.pdf, page 4: SRC-8caa3ee543f5f86e-SS17-P4-FRAME1 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

L510s-Catalogue.pdf · P005 · source page 4

Table conditions: Frame1 dimensions; source heading Unit:mm(inch), one numeric series printed. No inch conversion inferred. F means built-in EMC filter. Each exact listed model retained; dimensions share the physically merged body.

SRC-8caa3ee543f5f86e-SS17-P4-FRAME1 — reviewed source table — PDF page 4

Listed models (one physical group) W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2
L510-1P2-SH1-N/P
L510-1P5-SH1-N/P
L510-2P2-SH1-N/P
L510-2P5-SH1-N/P
L510-201-SH1-N/P
L510-2P2-SH1F-P
L510-2P5-SH1F-P
L510-2P7-SH1F-P
L510-201-SH1F-P
L510-2P2-SH3-N/P
L510-2P5-SH3-N/P
L510-201-SH3-N/P
72 63 61 141 131 122 114 141 136 128.2 86.3 81.1 55 4.4 2.2

Catalogue — L510s-Catalogue.pdf, page 4: SRC-8caa3ee543f5f86e-SS17-P4-FRAME2 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

Table conditions: Frame2 dimensions; source heading Unit:mm(inch), one numeric series printed. No inch conversion inferred. F means built-in EMC filter. Each exact listed model retained; dimensions share the physically merged body.

SRC-8caa3ee543f5f86e-SS17-P4-FRAME2 — reviewed source table — PDF page 4

Listed models (one physical group) W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2
L510-101-SH1-N/P
L510-202-SH1-N/P
L510-203-SH1-N/P
L510-202-SH1F-P
L510-203-SH1F-P
L510-202-SH3-N/P
L510-203-SH3-N/P
L510-401-SH3-N/P
L510-402-SH3-N/P
L510-403-SH3-N/P
L510-401-SH3F-P
L510-402-SH3F-P
L510-403-SH3F-P
118 108 108 144 131 121 114 150 144.2 136.4 101.32 96.73 51.5 4.3 2.2

Catalogue — L510s-Catalogue.pdf, page 4: SRC-8caa3ee543f5f86e-SS17-P4-FRAME3 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

Table conditions: Frame3 dimensions; source heading Unit:mm(inch), one numeric series printed. No inch conversion inferred. F means built-in EMC filter. Each exact listed model retained; dimensions share the physically merged body.

SRC-8caa3ee543f5f86e-SS17-P4-FRAME3 — reviewed source table — PDF page 4

Listed models (one physical group) W W1 H H1 H2 H3 D D1 D2 E E1 E2 Q
L510-205-SH3
L510-405-SH3
L510-408-SH3
L510-405-SH3F
L510-408-SH3F
129 118 197.5 177.6 188 154.7 148 143.7 136 102.6 96 48.2 4.5

Catalogue — L510s-Catalogue.pdf, page 4: SRC-8caa3ee543f5f86e-SS17-P4-FRAME4 — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

Table conditions: Frame4 dimensions; source heading Unit:mm(inch), one numeric series printed. No inch conversion inferred. F means built-in EMC filter. Each exact listed model retained; dimensions share the physically merged body.

SRC-8caa3ee543f5f86e-SS17-P4-FRAME4 — reviewed source table — PDF page 4

Listed models (one physical group) W W1 H H1 H2 H3 D D1 D2 E E1 Q
L510-208-SH3
L510-210-SH3
L510-410-SH3
L510-415-SH3
L510-410-SH3F
L510-415-SH3F
187 176 273 249.8 261 228.6 190 185.6 177.9 136 84.7 4.5

Catalogue — L510s-Catalogue.pdf, page 4: SRC-8caa3ee543f5f86e-SS17-P4-ACCESSORIES — reviewed source table

Original PDF. This table belongs to this source edition and its stated configuration.

Table conditions: Accessories as printed; optional products, not assumed included. Source physically merged cells repeat only with explicit shared-row evidence.

SRC-8caa3ee543f5f86e-SS17-P4-ACCESSORIES — reviewed source table — PDF page 4

Accessories Model Function Notes
Copy module JN5-CU ① Duplicating parameters setting in one inverter to
another inverter
② As a remote keypad to be used
③ Using RJ45 line to connect inverter
Communication
modules
JN5-CM-PDP For connection of Profibus-DP communication protocol For 510 series
Communication
modules
JN5-CM-TCPIP For connection of TCP-IP communication protocol For 510 series
Communication
modules
JN5-CM-DNET For connection of DeviceNet communication protocol For 510 series
Communication
modules
JN5-CM-CAN For connection of CANopen communication protocol For 510 series
RJ45 to USB connection cable JN5-CM-USB Using the TECO exclusive PC-software line 1.8m
EMC Grounding kit(Frame 1) JN5-GK-L01 To enhance the EMC ability by enlarging the grounding
area
For frame 1
EMC Grounding kit(Frame 2) JN5-GK-L02 To enhance the EMC ability by enlarging the grounding
area
For frame 2
Din rail kit (Frame1) JN5-DIN-L01 Used for mounting on the din rail For frame 1
Din rail kit (Frame2) JN5-DIN-L02 Used for mounting on the din rail For frame 2

Manual — L510s operating manual cover — page 1

Manual reference: Ver.02, January 2016, physical PDF page 1. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Microprocessor Controlled IGBT Drive;Inverter Motor Speed Regulator;Operating Manual.

Product photo nameplate not independently transcribed; cover ranges are family-level statements.

Class voltage, not each model actual input supply range. Model-specific source tables below.

Cover voltage-class ranges — PDF page 1

Source row Voltage class kW range HP range
1 100V 0.2~0.75 0.25~1
2 200V 0.2~7.5 0.25~10
3 400V 0.75~11 1~15

Manual — Model part-number diagram — page 8

Manual reference: Ver.02, January 2016, physical PDF page 8. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Example printed L510-1P2-SH1□-N. Connector lines map segments to separate code definitions.

Blank filter position is a meaningful source code,not missing OCR. Do not construct unlisted combinations from this code diagram. Code08 horsepower differs from page9 model-list HP.

Diagram arrow associations visually read. Editorial segment Control type identifies P/N box;no topology inference.

19 voltage-class/code associations;08 is7.5HP here. Literal code retained,not normalized to page9 value8.

Part-number segment definitions — PDF page 8

Source row Segment Code Meaning
1 Supply voltage 1 100V Class
2 Supply voltage 2 200V Class
3 Supply voltage 4 400V Class
4 Series name S 510s series
5 Specification H Standard Type
6 Power supply 1 Single phase
7 Power supply 3 Three phase
8 Filter F Built-in
9 Filter [blank code] None
10 Control type P PNP
11 Control type N NPN

Horsepower code legend — PDF page 8

Source row Voltage class Code HP
1 100V P2 0.25
2 100V P5 0.5
3 100V 01 1
4 200V P2 0.25
5 200V P5 0.5
6 200V P7 0.75
7 200V 01 1
8 200V 02 2
9 200V 03 3
10 200V 05 5
11 200V 08 7.5
12 200V 10 10
13 400V 01 1
14 400V 02 2
15 400V 03 3
16 400V 05 5
17 400V 08 7.5
18 400V 10 10
19 400V 15 15

Manual — Standard product specification and model options — page 9

Manual reference: Ver.02, January 2016, physical PDF page 9. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Source short-circuit capacity is below5000A/120V,5000A/240V or5000A/480V;100~120V models use120V,200~240V models240V,380~480V models480V.

◎ source selection marks and truly blank option cells preserved separately. Merged supply/frequency cells expanded only over their visible source rows. NPN+PNP marks on same row are not two newly invented model IDs. Leading-zero HP05/08 retained.

37 literal models,including combined NPN/PNP rows. Blank cells stayblank. Model-list horsepower8/08 differs fromcode08=7.5HP inpage8 andratingspage27. No correction inferred.

Printed37model rows — PDF page 9

Source row Model Supply Vac Frequency HP kW NPN mark PNP mark Built-in filter mark None filter mark
1 L510-1P2-SH1-N 1ph100~120V +10%/-15% 50/60Hz 0.25 0.2 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
2 L510-1P5-SH1-N 1ph100~120V +10%/-15% 50/60Hz 0.5 0.4 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
3 L510-101-SH1-N 1ph100~120V +10%/-15% 50/60Hz 1 0.75 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
4 L510-2P2-SH1F-P 1ph200~240V +10%/-15% 50/60Hz 0.25 0.2 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
5 L510-2P5-SH1F-P 1ph200~240V +10%/-15% 50/60Hz 0.5 0.4 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
6 L510-2P7-SH1F-P 1ph200~240V +10%/-15% 50/60Hz 0.75 0.55 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
7 L510-201-SH1F-P 1ph200~240V +10%/-15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
8 L510-202-SH1F-P 1ph200~240V +10%/-15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
9 L510-203-SH1F-P 1ph200~240V +10%/-15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
10 L510-2P2-SH1-N 1ph200~240V +10%/-15% 50/60Hz 0.25 0.2 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
11 L510-2P5-SH1-N 1ph200~240V +10%/-15% 50/60Hz 0.5 0.4 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
12 L510-2P7-SH1-N 1ph200~240V +10%/-15% 50/60Hz 0.75 0.55 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
13 L510-201-SH1-N 1ph200~240V +10%/-15% 50/60Hz 1 0.75 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
14 L510-202-SH1-N 1ph200~240V +10%/-15% 50/60Hz 2 1.5 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
15 L510-203-SH1-N 1ph200~240V +10%/-15% 50/60Hz 3 2.2 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
16 L510-2P2-SH3-N 3ph200~240V +10%/-15% 50/60Hz 0.25 0.2 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
17 L510-2P5-SH3-N 3ph200~240V +10%/-15% 50/60Hz 0.5 0.4 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
18 L510-201-SH3-N 3ph200~240V +10%/-15% 50/60Hz 1 0.75 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
19 L510-202-SH3-N 3ph200~240V +10%/-15% 50/60Hz 2 1.5 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
20 L510-203-SH3-N 3ph200~240V +10%/-15% 50/60Hz 3 2.2 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
21 L510-205-SH3 3ph200~240V +10%/-15% 50/60Hz 5 3.7 ◎ ◎ ⟦blank source cell⟧ ◎
22 L510-208-SH3 3ph200~240V +10%/-15% 50/60Hz 8 5.5 ◎ ◎ ⟦blank source cell⟧ ◎
23 L510-210-SH3 3ph200~240V +10%/-15% 50/60Hz 10 7.5 ◎ ◎ ⟦blank source cell⟧ ◎
24 L510-401-SH3-N 3ph380~480V +10%/-15% 50/60Hz 1 0.75 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
25 L510-402-SH3-N 3ph380~480V +10%/-15% 50/60Hz 2 1.5 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
26 L510-403-SH3-N 3ph380~480V +10%/-15% 50/60Hz 3 2.2 ◎ ⟦blank source cell⟧ ⟦blank source cell⟧ ◎
27 L510-401-SH3F-P 3ph380~480V +10%/-15% 50/60Hz 1 0.75 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
28 L510-402-SH3F-P 3ph380~480V +10%/-15% 50/60Hz 2 1.5 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
29 L510-403-SH3F-P 3ph380~480V +10%/-15% 50/60Hz 3 2.2 ⟦blank source cell⟧ ◎ ◎ ⟦blank source cell⟧
30 L510-405-SH3 3ph380~480V +10%/-15% 50/60Hz 5 3.7 ◎ ◎ ⟦blank source cell⟧ ◎
31 L510-408-SH3 3ph380~480V +10%/-15% 50/60Hz 8 5.5 ◎ ◎ ⟦blank source cell⟧ ◎
32 L510-410-SH3 3ph380~480V +10%/-15% 50/60Hz 10 7.5 ◎ ◎ ⟦blank source cell⟧ ◎
33 L510-415-SH3 3ph380~480V +10%/-15% 50/60Hz 15 11 ◎ ◎ ⟦blank source cell⟧ ◎
34 L510-405-SH3F 3ph380~480V +10%/-15% 50/60Hz 05 3.7 ◎ ◎ ◎ ⟦blank source cell⟧
35 L510-408-SH3F 3ph380~480V +10%/-15% 50/60Hz 08 5.5 ◎ ◎ ◎ ⟦blank source cell⟧
36 L510-410-SH3F 3ph380~480V +10%/-15% 50/60Hz 10 7.5 ◎ ◎ ◎ ⟦blank source cell⟧
37 L510-415-SH3F 3ph380~480V +10%/-15% 50/60Hz 15 11 ◎ ◎ ◎ ⟦blank source cell⟧

Manual — Installation environment and exclusions — page 10

Manual reference: Ver.02, January 2016, physical PDF page 10. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Chapter 3 Environment & Installation 3.1 Environment Installation environment has a direct effect on the correct operation and the life expectancy of the inverter, Install the inverter in an environment complying with the following conditions:

Installation site Install in an environment that will not have an adverse effect on the operation of the unit and ensure that there is no exposure to areas such as that listed below:-  Direct sunlight, Rain or moisture  Oil mist and salt  Dust, lint fibres, small metal filings and corrosive liquid and gas  Electromagnetic interference from sources such as welding equipment  Radioactive and flammable materials  Excessive vibration from machines such as stamping, punching machines  Add vibration-proof pads if necessary

Installation environment and exclusions

Protection — PDF page 10

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Protection Protection
2 Protection class IP20 Open Type
3 Suitable environment Suitable environment
4 Operating temperature -10~40°C (-10~50°C with fan) (non-freezing) If several inverters are installed in the same control panel, ensure adequate spacing and provide the necessary cooling and ventilation for successful operation.
5 Storage temperature -20~60°C
6 Relative Humidity Max 95% (without condensation)
7 Shock 2G (19.6m/s²) for 57~150Hz and below. 0.3mm for 10~57Hz (According to IEC60068-2-6 standard)

Manual — Derating continuation and capacitor reforming after storage — page 19

Manual reference: Ver.02, January 2016, physical PDF page 19. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Note: 101 and 205 type does not need to decrease the current rating in 50 degrees ambient temperature. 3.2.4 Capacitor reforming Guide after long storage For correct performance of this product after long storage before use it is important that Inverter Capacitors are reformed according to the guide below:

Note1:Rated voltage: please refer the rated voltage according to model label of inverter.

Derating plot415(50°C). Vertical Rated Current(In); horizontal Carrier Frequency(kHz). Visible labelled points:5kHz/100%;10kHz/70%;16kHz/55%. Curves retained, no interpolated values.

Derating continuation and capacitor reforming after storage

Storage time / Procedure to re-apply voltage — PDF page 19

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Storage time Procedure to re-apply voltage
2 ≦1year Apply rated voltage(Note1) of inverter in the normal way
3 Between 1-2 years Apply rated voltage of inverter to the product for one hour before using the inverter
4 ≧2 years Use a variable AC power supply to 1. Connecting 25% rated voltage of inverter for 30 minutes. 2. Connecting 50% rated voltage of inverter for 30 minutes. 3. Connecting 75% rated voltage of inverter for 30 minutes. 4. Connecting 100% rated voltage of inverter for 210 minutes. Once the procedures completed, inverter just can be used normally.

Manual — Wiring cables, torques, short-circuit and terminal ratings — page 20

Manual reference: Ver.02, January 2016, physical PDF page 20. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

3.3 Wiring Guidelines 3.3.1 Main considerations 1 Tightening Torque for Screw terminals:Refer to the tables 3-1, when using a screwdriver or any other suitable tools to make connections. 2 Power terminals: Single phase : L1 (L), L3 (N) Three-phase 200V models: L1 (L), L2, L3 (N) 400V models: L1, L2, L3 3 For all cabling use copper wires and the cable size shall be according to the table below rated at 105 degrees Celsius. 4 Power & Control cable Minimum rated voltage 240V AC system, 300V AC. 480V AC system, 600V AC. 5 Control cables should be separated from the power cables. Do not place them in the same cable tray or cable trunking to prevent against electrical interference. Table 3-1

6 The maximum RMS symmetrical Current Ratings and voltage are listed as below:

7 Electrical ratings of terminals:

Wiring cables, torques, short-circuit and terminal ratings

Frame size / TM1 / TM2 — PDF page 20

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows) Physical column 11 (source headings retained in rows)
1 Frame size TM1 TM1 TM1 TM1 TM1 TM2 TM2 TM2 TM2 TM2
2 Frame size Cable Size Cable Size Tightening torque Tightening torque Tightening torque Cable Size Cable Size Tightening torque Tightening torque Tightening torque
3 Frame size AWG mm² kgf.cm Ibf.in Nm AWG mm² kgf.cm Ibf.in Nm
4 Frame1 22~10 0.34~6 14 12.15 1.37 24~12 0.5~2.5 4.08 3.54 0.4
5 Frame2 22~10 0.34~6 12.24 10.62 1.2 24~12 0.5~2.5 4.08 3.54 0.4
6 Frame3 18~8 0.82~8.4 18 15.58 1.76 24~12 0.5~2.5 5.1 4.43 0.5
7 Frame4 14~6 2~13.3 24.48 21.24 2.4 24~12 0.5~2.5 5.1 4.43 0.5

Device Rating / Short circuit Rating / Maximum Voltage — PDF page 20

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Device Rating Device Rating Short circuit Rating Maximum Voltage
2 voltage HP Short circuit Rating Maximum Voltage
3 110V 0.2~1 5000A 120V
4 220V 0.2~10 5000A 240V
5 440V 1~15 5000A 480V

Horsepower / Power Specification / Voltage (Volt) / Current(A) — PDF page 20

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Horsepower Power Specification Voltage (Volt) Current(A)
2 0.25/0.5/1 220~240V 300 30
3 1 100~120V 300 20
4 2/3 220~240V 300 30
5 1/2/3 380~480V 600 28
6 5 220~240V 300 45
7 7.5/10 220~240V 300 65
8 5.5/7.5 380~480V 600 45
9 10/15 380~480V 600 65

Manual — Peripheral equipment considerations — page 24

Manual reference: Ver.02, January 2016, physical PDF page 24. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Source limitation for this page: Tiny drive-picture inscriptions in left illustration unresolved; complete adjacent equipment table reviewed.

3.3.6 Considerations for peripheral equipment (For detailed information for the above peripheral equipment refer to Chapter 6)

Peripheral equipment vertical illustration has power symbol, breaker, contactor, reactor, filter box, drive, ground symbols and motor in positions aligned with the adjacent source table. No new specifications inferred. Tiny drive picture inscriptions remain partial.

Peripheral equipment considerations

Power / Ensure that the supply voltage is correct. A molded-case circuit breaker or fused disconnect must be installed between the AC source and the inverter — PDF page 24

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Power Ensure that the supply voltage is correct. A molded-case circuit breaker or fused disconnect must be installed between the AC source and the inverter
2 Circuit Breaker & RCD Use a molded-case circuit breaker that conforms to the rated voltage and current of the inverter. Do not use the circuit breaker as the run/stop switch for the inverter. Residual Current Circuit Breaker(RCD) Current setting should be 200mA or above and the operating time at 0.1 second or longer to prevent malfunctions.
3 Magnetic contactor Normally a magnetic contactor is not needed. A contactor can be used to perform functions such as external control and auto restart after power failure. Do not use the magnetic contactor as the run/stop switch for the inverter.
4 AC reactor for power quality improvement When a 200V/400V inverter with rating below 15KW is connected to a high capacity power source (600kVA or above) then an AC reactor can be connected for power factor improvement and reducing harmonics.
5 Input noise filter L510 inverter has a built-in filter to Class “A” first Environment. (CategoryC2) To satisfy the required EMC regulations for your specific application you may require an additional EMC filter.
6 Inverter Connect the single phase power to Terminals, L1(L) & L3(N) and three phase power to Terminals : (200V : L1(L),L2,L3(N) or 400V : L1,L2,L3) Warning! Connecting the input terminals T1, T2, and T3 to AC input power will damage the inverter. Output terminals T1, T2, and T3 are connected to U, V, and W terminals of the motor. To reverse the motor rotation direction just swap any two wires at terminals T1, T2, and T3. Ground the Inverter and motor correctly. Ground Resistance for 200V power<100 Ohms.
7 Motor Three-phase induction motor. Voltage drop on motor due to long cable can be calculated. Volts drop should be < 10%. Phase-to-phase voltage drop (V) = √3 ×resistance of wire (Ω/km)×length of line (m)×current×10^-3

Manual — Product ratings100V and200V smaller models — page 26

Manual reference: Ver.02, January 2016, physical PDF page 26. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

F:stands for built-in filter.100V input-current row has footnote*.

Tables show N/P template scope broader than some individual page9list entries;preserve both source scopes ratherthan inventing additionalmodels.

L510-□□□-SH1-N/P;Input:Single phase100~120V(+10%/-15%),50/60Hz;Output:Three phase0~240V;EnclosureIP20. Values transposed from printed model columns;templateN/P is retained,not proof all combinations sold. No filtered-weight row printed in this source table.

L510-□□□-SH1-N/P (L510-□□□-SH1F-P);Input:Single phase200~240V(+10%/-15%),50/60Hz;Output:Three phase0~240V;EnclosureIP20. Values transposed from printed model columns;templateN/P is retained,not proof all combinations sold. Filtered/nonfiltered weights separate.

L510-□□□-SH3-N/P;Input:Three phase200~240V(+10%/-15%),50/60Hz;Output:Three phase0~240V;EnclosureIP20. Values transposed from printed model columns;templateN/P is retained,not proof all combinations sold. Filtered/nonfiltered weights separate.

100V single-phase ratings — PDF page 26

Source row Model code HP Suitable motor kW Rated output A Rated capacity kVA Input A Weight kg Momentary loss time s
1 1P2 0.25 0.2 1.8 0.68 9.5 0.85 1.0
2 1P5 0.5 0.4 2.6 1.00 13 0.85 1.0
3 101 1 0.75 4.3 1.65 19 1.35 1.0

200V single-phase ratings — PDF page 26

Source row Model code HP Suitable motor kW Rated output A Rated capacity kVA Input A Weight kg Weight with filter kg Momentary loss time s
1 2P2 0.25 0.2 1.8 0.68 4.9 0.85 0.95 1.0
2 2P5 0.5 0.4 2.6 1.00 7.2 0.85 0.95 1.0
3 2P7 0.75 0.55 3.4 1.30 9 0.85 0.95 1.0
4 201 1 0.75 4.3 1.65 11 0.85 0.95 1.0
5 202 2 1.5 7.5 2.90 15.5 1.35 1.45 2.0
6 203 3 2.2 10.5 4.00 21 1.35 1.45 2.0

200V three-phase smaller ratings — PDF page 26

Source row Model code HP Suitable motor kW Rated output A Rated capacity kVA Input A Weight kg Weight with filter kg Momentary loss time s
1 2P2 0.25 0.2 1.8 0.68 3.0 0.85 0.95 1.0
2 2P5 0.5 0.4 2.6 1.00 4.0 0.85 0.95 1.0
3 201 1 0.75 4.3 1.65 6.4 0.85 0.95 1.0
4 202 2 1.5 7.5 2.90 9.4 1.35 1.45 2.0
5 203 3 2.2 10.5 4.00 12.2 1.35 1.45 2.0

Manual — Product ratings200V larger and400V models — page 27

Manual reference: Ver.02, January 2016, physical PDF page 27. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

The input current is calculated value at full rated output current. Printed footnote appears below400V smaller table;200Vlarger table instead marks Input voltage range(V). Preserve mismatch.

F:Built-in EMC filter.

No rated capacity recalculated from voltage/current;literal sourcekVAvalues retained. Page9 HP8/08 differs from7.5HP here.

L510-□□□-SH3;Input:Three phase200~240V(+10%/-15%),50/60Hz;Output:Three phase0~240V;EnclosureIP20. Values transposed from printed model columns;templateN/P is retained,not proof all combinations sold. No filtered-weight row printed in this source table.

L510-□□□-SH3-N/P (L510-□□□-SH3F-P);Input:Three phase380~480V(+10%/-15%),50/60Hz;Output:Three phase0~480V;EnclosureIP20. Values transposed from printed model columns;templateN/P is retained,not proof all combinations sold. Filtered/nonfiltered weights separate.

L510-□□□-SH3 (L510-□□□-SH3F);Input:Three phase380~480V(+10%/-15%),50/60Hz;Output:Three phase0~480V;EnclosureIP20. Values transposed from printed model columns;templateN/P is retained,not proof all combinations sold. Filtered/nonfiltered weights separate.

200V three-phase larger ratings — PDF page 27

Source row Model code HP Suitable motor kW Rated output A Rated capacity kVA Input A Weight kg Momentary loss time s
1 205 5 3.7 17.5 6.67 19.3 2.5 2.0
2 208 7.5 5.5 26 9.91 28.6 6 2.0
3 210 10 7.5 35 13.34 38.5 6 2.0

400V three-phase smaller ratings — PDF page 27

Source row Model code HP Suitable motor kW Rated output A Rated capacity kVA Input A Weight kg Weight with filter kg Momentary loss time s
1 401 1 0.75 2.3 1.7 4.2 1.35 1.45 2.0
2 402 2 1.5 3.8 2.9 5.6 1.35 1.45 2.0
3 403 3 2.2 5.2 4.0 7.3 1.35 1.45 2.0

400V three-phase larger ratings — PDF page 27

Source row Model code HP Suitable motor kW Rated output A Rated capacity kVA Input A Weight kg Weight with filter kg Momentary loss time s
1 405 5 3.7 9.2 7.01 10.1 2.5 2.7 2
2 408 7.5 5.5 13.0 9.91 14.3 2.5 2.7 2
3 410 10 7.5 17.5 13.34 19.3 6 6.3 2
4 415 15 11 24 18.29 26.4 6 6.3 2

Manual — General specifications control display and protective functions — page 28

Manual reference: Ver.02, January 2016, physical PDF page 28. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Frame1/2 separate NPN/PNP models versus Frame3/4 switchable preserved;do not apply switchable claim to every model. Features are supplier statements,not tested performance.

Hierarchical headers flattened with group context;manufacturer performance/protection claims only. Auto-restart safety context retained frompage7.

General specifications first page — PDF page 28

Source row Group Item Source value
1 Control Control mode V/F Control+SLV control
2 Frequency Range 0.01~599.00Hz
3 Frequency Speed accuracy(100% torque) V/F:3%;SLV:1%
4 Frequency Starting torque V/F:3Hz/100%;SLV:3Hz/150%
5 Frequency Setting resolution Digital input:0.01Hz;Analog input:0.015Hz/60Hz
6 Frequency Setting Keypad▲▼keys orVR potentiometer;externalAVI(0/2~10V),ACI(0/4~20mA);multifunctionup/down(Group3);communication
7 Frequency Frequency limit Lower/upper limits;3skip-frequency settings
8 Run Operation set Keypad run/stop;external2/3wire selection;Jog;communication run
9 Main controls V/F curve 6fixed curves and1customized
10 Main controls Carrier frequency 1~16kHz(default5kHz)
11 Main controls Acceleration/deceleration 2offAcc/dec time parameters,4offS-curve parameters
12 Main controls Multifunction input 19functions(Group3);5points;Frame1/2:NPN&PNP separate models;Frame3/4:NPN&PNP switchable
13 Main controls Multifunction output 16functions(Group3)
14 Main controls Multifunction analogue output 5functions(Group4),1point(0~10V)
15 Main controls Main features Overload Detection;8preset speeds;Auto-run;Acc/DecSwitch(2Stages);Main/Alt run command;Main/Alt frequencycommand;PID;torque boost;V/F startFrequency;Fault reset
16 Display LED Parameter/value/frequency/line speed/DCvoltage/outputvoltage/outputcurrent/PIDfeedback/input-outputterminalstatus/heatsinktemperature/programversion/faultlog
17 Display LED status Run/stop/forward/reverse
18 Protective functions Overload Integrated motor/inverter overload:150%ratedcurrent for60sec,every10minutes
19 Protective functions Overvoltage 100V/200V:Over410V;400V:Over820V
20 Protective functions Undervoltage 100V/200V:Under190V;400V:Under380V
21 Protective functions Momentary loss restart Inverter auto-restart after momentary power loss
22 Protective functions Stall prevention Acceleration/deceleration/continuous run

Manual — General specifications protection communication and environment — page 29

Manual reference: Ver.02, January 2016, physical PDF page 29. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Source shock statement says57~150Hz and below;retain wording without imposing a boundary not printed. C1 claim applies only to portion ofmodels withgroundingkit;not all models. Certification/standards references are historical supplier statements,not verification of current validity.

Qualification and source wording preserved;no current compliance/certificate claim inferred.

General specifications continuation — PDF page 29

Source row Group Item Source value
1 Protective functions Short-circuit output terminal Electronic Circuit Protection
2 Protective functions Grounding fault Electronic Circuit Protection
3 Protective functions Additional Heatsink overtemperature;auto carrierfrequency reduction withtemperature rise;faultoutput;reverseprohibit;numberofautorestartattempts;parameterlock;OVP;motorPTCovertemperature
4 Certification International certification CE/UL/cUL/RCM
5 Communication Protocols RS485(Modbus)built-in,one-to-one orone-to-many;built-inBacNet;Profibus,DeviceNet,CANopen,TCP/IP bygateways
6 Environment Operating temperature -10~50°C(with fan),-10~40°C(without fan)
7 Environment Storage temperature -20~60°C
8 Environment Humidity Under95%RH(no condensation)
9 Environment Shock 2G(19.6m/s²)for57~150Hz andbelow;0.3mm for10~57Hz
10 Environment EMC compliance EN61800-3,First Environment;portion models canpassC1level withgroundingkit
11 Environment LVD compliance EN61800-5-1
12 Environment Electrical safety UL508C
13 Environment Protection level IP20

Manual — Main circuit terminals and layouts — page 35

Manual reference: Ver.02, January 2016, physical PDF page 35. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

3.6 Terminal Description 3.6.1 Description of main circuit terminals

*P,BR for 205/208/210/401/402/403/405/408/410/415 series Single phase

Note: the screw on L2 terminal is removed for the single phase input supply models. Three phase (200V series)

Three phase (205 & 208 & 210 & 400V series)

Single phase terminal layout, left to right:L1(L),L2,L3(N),T1,T2,T3. L2 screw absent as separately printed note.

Three phase(200V series) terminal layout:L1(L),L2,L3(N),T1,T2,T3.

Three phase(205&208&210&400V series) terminal layout:L1,L2,L3,P,BR,T1,T2,T3.

Main circuit terminals and layouts

Terminal symbols / TM1 Function Description — PDF page 35

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Terminal symbols TM1 Function Description
2 L1(L) Main power input, single phase: L1(L) / L3(N) three phase(200V): L1(L) / L2 / L3(N) three phase(400V): L1 / L2 / L3
3 L2 Main power input, single phase: L1(L) / L3(N) three phase(200V): L1(L) / L2 / L3(N) three phase(400V): L1 / L2 / L3
4 L3(N) Main power input, single phase: L1(L) / L3(N) three phase(200V): L1(L) / L2 / L3(N) three phase(400V): L1 / L2 / L3
5 P* externally connected braking resistor
6 BR* externally connected braking resistor
7 T1 Inverter output, connect to U, V, W terminals of motor
8 T2 Inverter output, connect to U, V, W terminals of motor
9 T3 Inverter output, connect to U, V, W terminals of motor
10 [ground symbol] Ground terminal

Manual — Frame1/2 control terminals — page 36

Manual reference: Ver.02, January 2016, physical PDF page 36. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

3.6.2 Description of control circuit terminals Frame1&Frame2

NPN:

PNP:

NPN terminal layout:RA,RB,COM,S1,S2,S3,S4,S5,10V,AVI,ACI,AO,AGND.

PNP terminal layout:RA,RB,+24V,S1,S2,S3,S4,S5,10V,AVI,ACI,AO,AGND.

Frame1/2 control terminals

Terminal symbols / TM2 Function Description / Signal Level — PDF page 36

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Terminal symbols TM2 Function Description Signal Level
2 RA Relay output terminal, Specification: 250VAC/1A(30VDC/1A) 250VAC/1A(30VDC/1A)
3 RB Relay output terminal, Specification: 250VAC/1A(30VDC/1A) 250VAC/1A(30VDC/1A)
4 COM S1~S5 (COMMON) 【NPN】 ±15%,Max output current 30mA
5 24V S1~S5 (COMMON) 【PNP】 ±15%,Max output current 30mA
6 S1~S5 Multi-function input terminals(refer to group3) 24 VDC, 4.5 mA, optical coupling isolation (Max,voltage30 VDC, Input impedance 6kΩ)
7 10V Built in power for an external speed potentiometer 10V,(Max current:20mA)
8 AVI Analog voltage input, Specification : 0/2~10VDC (choose by parameter 04-00) 0~10V(Input impedance 200kΩ)
9 ACI Analog current input, Specification : 0/4~20mA (choose by parameter 04-00) 0~20mA(Input impedance 499Ω)
10 AO Multi-function analog output terminal. Maximum output 10VDC/1mA 0~10V(Max current 2mA)
11 AGND Analog ground terminal ⟦blank source cell⟧

Manual — Frame3/4 control terminals — page 37

Manual reference: Ver.02, January 2016, physical PDF page 37. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Frame3&Frame4

NPN/PNP control terminals:

NPN/PNP control terminal layouts:TM1 RA,RB,RC;TM2 +24V,SC,COM,S1,S2,S3,S4,S5,10V,AVI/PTC,ACI,AO,AGND. Original positions retained.

Frame3/4 control terminals

Terminal symbols / TM1 Function Description — PDF page 37

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Terminal symbols TM1 Function Description
2 RA Relay output terminal, Specification: 250VAC/5A(30VDC/5A) RA: Normally open RB: Normally close RC: common point
3 RB Relay output terminal, Specification: 250VAC/5A(30VDC/5A) RA: Normally open RB: Normally close RC: common point
4 RC Relay output terminal, Specification: 250VAC/5A(30VDC/5A) RA: Normally open RB: Normally close RC: common point

Terminal symbols / TM2 Function Description / Signal Level — PDF page 37

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Terminal symbols TM2 Function Description Signal Level
2 +24V Common point of PNP input ±15%,Max output current 30mA
3 SC NPN/PNP selectable terminal. NPN input: +24V&SC need to be shorted. PNP input: COM&SC need to be shorted. ±15%,Max output current 30mA
4 COM voltage reference point for S1~S5 ±15%,Max output current 30mA
5 S1~S5 Multi-function input terminals(refer to group3) 24 VDC, 4.5 mA, Optical coupling isolation (Max,voltage30 Vdc, Input impedance 6kΩ)
6 10V Built in Power for an external speed potentiometer (Max output : 20mA) 10V,(Max current:20mA)
7 AVI/PTC Analog voltage input/motor over temperature protection signal input, Specification : 0/2~10VDC 0~10V(Input impedance 200kΩ)
8 ACI Analog current input, Specification : 0 /4~20mA(choose by parameter 04-00) 0~20mA(Input impedance 499Ω)
9 AO Multi function analog output terminal. Maximum output 10VDC/1mA 0~10V(Max current 2mA)
10 AGND Analog ground terminal ⟦blank source cell⟧

Manual — Frame1 outline dimensions — page 38

Manual reference: Ver.02, January 2016, physical PDF page 38. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Dimensions inmm;original drawing remains authority for geometry. F:Built-in EMC filter.

Merged dimensions kept once for exactprintedmodelgroup. N/P slashnotation preserved;no missing model added.

Frame1 list does not include L510-2P7-SH1-N/P although page9 lists2P7-SH1-N;do not infer its dimensions.

Source range boundaries kept literally;no inferred inclusive/exclusive boundary or computedlimits.

All dimensionsmm. Exactsource modelgroup preserved. Labels W,W1,W2,H,H1,H2,H3,D,D1,D2,E,E1,E2,Q1,Q2 refer to originalfigure;do not infer geometry fromlabels alone.

Tolerance table — PDF page 38

Source row Dimension range mm Tolerance mm
1 0~6 ±0.8
2 6~30 ±1.5
3 30~120 ±2.5
4 120~315 ±4.0
5 315~1000 ±6.0

Frame1 dimension group — PDF page 38

Source row Model group W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2
1 L510-1P2-SH1-N/P; L510-1P5-SH1-N/P; L510-2P2-SH1-N/P; L510-2P5-SH1-N/P; L510-201-SH1-N/P; L510-2P2-SH1F-P; L510-2P5-SH1F-P; L510-2P7-SH1F-P; L510-201-SH1F-P; L510-2P2-SH3-N/P; L510-2P5-SH3-N/P; L510-201-SH3-N/P 72 63 61 141 131 122 114 141 136 128.2 86.3 81.1 55 4.4 2.2

Manual — Frame2 100V/200V outline dimensions — page 39

Manual reference: Ver.02, January 2016, physical PDF page 39. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Dimensions inmm;original drawing remains authority for geometry. F:Built-in EMC filter.

Merged dimensions kept once for exactprintedmodelgroup. N/P slashnotation preserved;no missing model added.

All dimensionsmm. Exactsource modelgroup preserved. Labels W,W1,W2,H,H1,H2,H3,D,D1,D2,E,E1,E2,Q1,Q2 refer to originalfigure;do not infer geometry fromlabels alone.

Frame2 100V/200V dimension group — PDF page 39

Source row Model group W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2
1 L510-101-SH1-N/P; L510-202-SH1-N/P; L510-203-SH1-N/P; L510-202-SH1F-P; L510-203-SH1F-P; L510-202-SH3-N/P; L510-203-SH3-N/P 118 108 108 144 131 121 114 150 144.2 136.4 101.32 96.73 51.5 4.4 2.2

Manual — Frame2 400V outline dimensions — page 40

Manual reference: Ver.02, January 2016, physical PDF page 40. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Dimensions inmm;original drawing remains authority for geometry. F:Built-in EMC filter.

Merged dimensions kept once for exactprintedmodelgroup. N/P slashnotation preserved;no missing model added.

Q1 is4.3 here versus4.4 inFrame2 100V/200V;retain distinction. Source spaces in402/403-SH3F- P retained.

All dimensionsmm. Exactsource modelgroup preserved. Labels W,W1,W2,H,H1,H2,H3,D,D1,D2,E,E1,E2,Q1,Q2 refer to originalfigure;do not infer geometry fromlabels alone.

Frame2 400V dimension group — PDF page 40

Source row Model group W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2
1 L510-401-SH3-N/P; L510-402-SH3-N/P; L510-403-SH3-N/P; L510-401-SH3F-P; L510-402-SH3F- P; L510-403-SH3F- P 118 108 108 144 131 121 114 150 144.2 136.4 101.32 96.73 51.5 4.3 2.2

Manual — Frame3 outline dimensions — page 41

Manual reference: Ver.02, January 2016, physical PDF page 41. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Dimensions inmm;original drawing remains authority for geometry. Diagram2-Q label retained;no hole geometry inferred.

Merged dimensions kept once for exactprintedmodelgroup. N/P slashnotation preserved;no missing model added.

All dimensionsmm. Exactsource modelgroup preserved. Labels W,W1,H,H1,H2,H3,D,D1,D2,E,E1,E2,Q refer to originalfigure;do not infer geometry fromlabels alone.

Frame3 dimension group — PDF page 41

Source row Model group W W1 H H1 H2 H3 D D1 D2 E E1 E2 Q
1 L510-205-SH3; L510-405-SH3; L510-408-SH3; L510-405-SH3F; L510-408-SH3F 129 118 197.5 177.6 188 154.7 148 143.7 136 102.6 96 48.2 4.5

Manual — Frame4 outline dimensions — page 42

Manual reference: Ver.02, January 2016, physical PDF page 42. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Dimensions inmm;original drawing remains authority for geometry. Diagram2-Q label retained;no hole geometry inferred.

Merged dimensions kept once for exactprintedmodelgroup. N/P slashnotation preserved;no missing model added.

All dimensionsmm. Exactsource modelgroup preserved. Labels W,W1,H,H1,H2,H3,D,D1,D2,E,E1,Q refer to originalfigure;do not infer geometry fromlabels alone.

Frame4 dimension group — PDF page 42

Source row Model group W W1 H H1 H2 H3 D D1 D2 E E1 Q
1 L510-208-SH3; L510-210-SH3; L510-410-SH3; L510-415-SH3; L510-410-SH3F; L510-415-SH3F 187 176 273 249.8 261 228.6 190 185.6 177.9 136 84.7 4.5

Manual — Operator panel functions — page 44

Manual reference: Ver.02, January 2016, physical PDF page 44. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Chapter4 Software Index 4.1 Keypad Description 4.1.1 Operator Panel Functions

TECO L510s operator panel. Hz/RPM,FWD,REV,FUN;MODE;ENT withleftarrow;FREQ.SET;RUN;STOP RESET;up/downtriangle keys. Blank display is a pictogram, not an operating value.

Operator panel functions

Type / Item / Function — PDF page 44

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Type Item Function
2 Digital display & LEDs Main digital displays Frequency Display, Parameter, voltage, Current, Temperature, Fault messages.
3 Digital display & LEDs LED Status Hz/RPM: ON when the frequency or line speed is displayed. OFF when the parameters are displayed. FWD: ON while the inverter is running forward. Flashes while stopped. REV: ON while the inverter is running reverse. Flashes while stopped. FUN: ON when the parameters are displayed. OFF when the frequency is displayed.
4 Variable Resistor FREQ SET Used to set the frequency
5 Keys On Keypad RUN RUN: Run at the set frequency.
6 Keys On Keypad STOP/RESET (Dual function keys) STOP: Decelerate or Coast to Stop. RESET: Use to Reset alarms or resettable faults.
7 Keys On Keypad ▲ Increment parameter number and preset values.
8 Keys On Keypad ▼ Decrement parameter number and preset values.
9 Keys On Keypad MODE Switch between available displays
10 Keys On Keypad </ENTER (Dual function keys, a short press for left shift function, a long press for ENTER function) “<” Left Shift: Used while changing the parameters or parameter values ENTER: Used to display the preset value of parameters and for saving the changed parameter values.

Manual — Digital display setup and12-00 example1 — page 47

Manual reference: Ver.02, January 2016, physical PDF page 47. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

4.1.3 Digital display setup On power up digital display screens will be as shown below.

User selectable display formats:

The highest bit of 12-00 sets the power on the display, other bits set the selected display from range 0-7.as Listed above. Example1: Set parameter 12- 00=【10000】to obtain display format shown below.

Power-up display sequence:220u (Power supply),2sec later5.00(frequency),MODE to00-01(parameter); MODE return arrow shown. Flash rays are shown over supply and frequency examples. These are printed examples, not measured readings.

Example1 parameter12-00=[10000]. Display Power supply220u;2sec later Output Current0.0A. MODE arrows connect Output Current→Set frequency5.00→parameter00-01→Output Current. Flash rays shown over power supply and setfrequency. Original arrows retained.

Digital display setup and12-00 example1

12- 00 / Display Mode — PDF page 47

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 00 Display Mode
2 Range 0 0 0 0 0 high Low Each of the above 5 digits can be set to any of the selections below from 0 to 7 【0】:Disable display 【1】:output Current 【2】:output Voltage 【3】:DC voltage 【4】:Temperature 【5】:PID feedback 【6】:AVI 【7】:ACI

Manual — Programmable groups and parameter note legend — page 52

Manual reference: Ver.02, January 2016, physical PDF page 52. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

4.2 Programmable Parameter Groups

Programmable groups and parameter note legend

Parameter Group No. / Description — PDF page 52

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Parameter Group No. Description
2 Group 00 Basic parameters
3 Group 01 V/F Pattern selections & setup
4 Group 02 Motor parameters
5 Group 03 Multi function digital Inputs/Outputs
6 Group 04 Analog signal inputs/ Analog output
7 Group 05 Preset Frequency Selections.
8 Group 06 Auto Run(Auto Sequencer) function
9 Group 07 Start/Stop command setup
10 Group 08 Drive and motor Protection
11 Group 09 Communication function setup
12 Group 10 PID function setup
13 Group 11 Performance control functions
14 Group 12 Digital Display & Monitor functions
15 Group 13 Inspection & Maintenance function

Parameter notes for Parameter Groups — PDF page 52

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Parameter notes for Parameter Groups Parameter notes for Parameter Groups
2 *1 Parameter can be adjusted during running mode
3 *2 Cannot be modified in communication mode
4 *3 Does not change with factory reset
5 *4 Read only

Manual — Group00 basic parameters — page 53

Manual reference: Ver.02, January 2016, physical PDF page 53. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group00 basic parameters

Group 00- The basic parameters group — PDF page 53

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 00- The basic parameters group Group 00- The basic parameters group Group 00- The basic parameters group Group 00- The basic parameters group Group 00- The basic parameters group Group 00- The basic parameters group
2 No. Description Range Factory Setting Unit Note
3 00-00 control mode 0:V/F mode 0 - ⟦blank source cell⟧
4 00-00 control mode 1:SLV mode 0 - ⟦blank source cell⟧
5 00-01 Motor rotation 0:Forward 1:Reverse 0 - *1
6 00-02 Main Run Source Selection 0:Keypad 0 - ⟦blank source cell⟧
7 00-02 Main Run Source Selection 1:External Run/Stop Control 0 - ⟦blank source cell⟧
8 00-02 Main Run Source Selection 2:Communication 0 - ⟦blank source cell⟧
9 00-03 Alternative Run Source Selection 0:Keypad 0 - ⟦blank source cell⟧
10 00-03 Alternative Run Source Selection 1:External Run/Stop Control 0 - ⟦blank source cell⟧
11 00-03 Alternative Run Source Selection 2:Communication 0 - ⟦blank source cell⟧
12 00-04 Operation modes for external terminals 0: Forward/Stop-Reverse/Stop 0 - ⟦blank source cell⟧
13 00-04 Operation modes for external terminals 1: Run/Stop-Reverse/Forward 0 - ⟦blank source cell⟧
14 00-04 Operation modes for external terminals 2: 3-Wire Control Mode-Run/Stop 0 - ⟦blank source cell⟧
15 00-05 Main Frequency Source Selection 0:Keypad 0 - ⟦blank source cell⟧
16 00-05 Main Frequency Source Selection 1:Potentiometer on Keypad 0 - ⟦blank source cell⟧
17 00-05 Main Frequency Source Selection 2:External AVI Analog Signal Input 0 - ⟦blank source cell⟧
18 00-05 Main Frequency Source Selection 3:External ACI Analog Signal Input 0 - ⟦blank source cell⟧
19 00-05 Main Frequency Source Selection 4:External Up/Down Frequency Control 0 - ⟦blank source cell⟧
20 00-05 Main Frequency Source Selection 5:Communication setting Frequency 0 - ⟦blank source cell⟧
21 00-05 Main Frequency Source Selection 6:PID output frequency 0 - ⟦blank source cell⟧
22 00-06 Alternative Frequency Source Selection 0:Keypad 4 - ⟦blank source cell⟧
23 00-06 Alternative Frequency Source Selection 1:Potentiometer on Keypad 4 - ⟦blank source cell⟧
24 00-06 Alternative Frequency Source Selection 2:External AVI Analog Signal Input 4 - ⟦blank source cell⟧
25 00-06 Alternative Frequency Source Selection 3:External ACI Analog Signal Input 4 - ⟦blank source cell⟧
26 00-06 Alternative Frequency Source Selection 4:External Up/Down Frequency Control 4 - ⟦blank source cell⟧
27 00-06 Alternative Frequency Source Selection 5:Communication setting Frequency 4 - ⟦blank source cell⟧
28 00-06 Alternative Frequency Source Selection 6:PID output frequency. 4 - ⟦blank source cell⟧
29 00-07 Main and Alternative Frequency Command modes 0: Main Or Alternative Frequency 1: Main frequency+Alternative Frequency 0 - ⟦blank source cell⟧
30 00-08 Communication Frequency Command 0.00~599.00 ⟦blank source cell⟧ Hz *4
31 00-09 Frequency command Save mode (Communication mode) 0:Save the frequency before power down 1:Save the communication frequency 0 - ⟦blank source cell⟧
32 00-10 Initial Frequency Selection ( keypad mode) 0:by Current Frequency Command 0 - ⟦blank source cell⟧
33 00-10 Initial Frequency Selection ( keypad mode) 1:by 0 Frequency Command 0 - ⟦blank source cell⟧
34 00-10 Initial Frequency Selection ( keypad mode) 2:by 00-11 0 - ⟦blank source cell⟧
35 00-11 Initial Frequency Keypad mode 0.00~599.00 50.00/60.00 Hz ⟦blank source cell⟧
36 00-12 Frequency Upper Limit 0.01~599.00 50.00/60.00 Hz ⟦blank source cell⟧
37 00-13 Frequency Lower Limit 0.00~598.99 0.00 Hz ⟦blank source cell⟧
38 00-14 Acceleration Time 1 0.1~3600.0 10.0 s *1
39 00-15 Deceleration Time 1 0.1~3600.0 10.0 s *1
40 00-16 Acceleration Time 2 0.1~3600.0 10.0 s *1
41 00-17 Deceleration Time 2 0.1~3600.0 10.0 s *1
42 00-18 Jog Frequency 1.00~25.00 2.00 Hz *1
43 00-19 Jog Acceleration Time 0.1~25.5 0.5 s *1
44 00-20 Jog Deceleration Time 0.1~25.5 0.5 s *1

Manual — Group01V/F andGroup02motor parameters — page 54

Manual reference: Ver.02, January 2016, physical PDF page 54. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group01V/F andGroup02motor parameters

Group 01- V/F Pattern selection & Setup — PDF page 54

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 01- V/F Pattern selection & Setup Group 01- V/F Pattern selection & Setup Group 01- V/F Pattern selection & Setup Group 01- V/F Pattern selection & Setup Group 01- V/F Pattern selection & Setup Group 01- V/F Pattern selection & Setup
2 No. Description Range Factory Setting Unit Note
3 01-00 Volts/Hz Patterns 1~7 1/4 - ⟦blank source cell⟧
4 01-01 V/F Max voltage 200V:170.0~264.0 400V:323.0~528.0 Based on 13-08 Vac ⟦blank source cell⟧
5 01-02 Max Frequency 1.40 ~ 599.00 50.00/60.00 Hz ⟦blank source cell⟧
6 01-03 Max Frequency Voltage Ratio 0.0 ~ 100.0 100.0 % ⟦blank source cell⟧
7 01-04 Mid Frequency 2 1.30 ~ 599.00 2.50/3.00 Hz ⟦blank source cell⟧
8 01-05 Mid Frequency Voltage Ratio 2 0.0 ~ 100.0 10.0/6.8 % ⟦blank source cell⟧
9 01-06 Mid Frequency 1 1.30 ~ 599.00 2.50/3.00 Hz ⟦blank source cell⟧
10 01-07 Mid Frequency Voltage Ratio 1 0.0 ~ 100.0 10.0/6.8 % ⟦blank source cell⟧
11 01-08 Min Frequency 1.30 ~ 599.00 1.30/1.50 Hz ⟦blank source cell⟧
12 01-09 Min Frequency Voltage Ratio 0.0 ~ 100.0 8.0/3.4 % ⟦blank source cell⟧
13 01-10 Volts/Hz Curve Modification (Torque Boost) 0 ~ 10.0 0.0 % *1
14 01-11 V/F start Frequency 0.00~10.00 0.00 Hz ⟦blank source cell⟧
15 01-12 No-load oscillation suppression gain 0.0~200.0 0 % ⟦blank source cell⟧
16 01-13 Motor Hunting Prevention Coefficient 1~8192 800 ⟦blank source cell⟧ ⟦blank source cell⟧
17 01-14 Motor Hunting Prevention Gain 0~100 Frame1/2 100V/200V series: 7 others: 0 % ⟦blank source cell⟧
18 01-15 Motor Hunting Prevention Limit 0~100.0 5.0 % ⟦blank source cell⟧
19 01-16 Auto-Torque Compensation Filter Coefficient 0.1~1000.0 0.1 ms ⟦blank source cell⟧
20 01-17 Auto-torque Compensation Gain 0~100 0 % ⟦blank source cell⟧
21 01-18 Auto-torque Compensation Frequency 1.30~5.00 2 Hz ⟦blank source cell⟧

Group 02- Motor parameters — PDF page 54

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters
2 No. Description Range Factory Setting Unit Note
3 02-00 Motor No Load Current ---- by motor nameplate A ⟦blank source cell⟧
4 02-01 Motor Rated Current (OL1) ---- by motor nameplate A ⟦blank source cell⟧
5 02-02 V/F Slip Compensation 0.0 ~ 100.0 0.0 % *1
6 02-03 Motor Rated Speed ---- by motor nameplate Rpm ⟦blank source cell⟧
7 02-04 Motor Rated Voltage ---- by motor nameplate Vac ⟦blank source cell⟧
8 02-05 Motor Rated Power 0~22.0 by motor nameplate kW ⟦blank source cell⟧
9 02-06 Motor Rated Frequency 0~599.0 by motor nameplate ⟦blank source cell⟧ ⟦blank source cell⟧
10 02-07 Motor Auto Tuning 0: Disable 1: Static auto tuning 0 ⟦blank source cell⟧ ⟦blank source cell⟧
11 02-08 Stator Resistor Gain 0~600 by series ⟦blank source cell⟧ ⟦blank source cell⟧
12 02-09 Rotor Resistor Gain 0~600 by series ⟦blank source cell⟧ ⟦blank source cell⟧
13 02-10 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 02-11 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 02-12 Reserved ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 02-13 SLV Slip Compensation Gain 0~200 by series % ⟦blank source cell⟧
17 02-14 SLV Torque Compensation Gain 0~200 100 % ⟦blank source cell⟧

Manual — Group02continuation andGroup03digitalI/O — page 55

Manual reference: Ver.02, January 2016, physical PDF page 55. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group02continuation andGroup03digitalI/O

Group 02- Motor parameters — PDF page 55

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters Group 02- Motor parameters
2 No. Description Range Factory Setting Unit Note
3 02-15 Low Frequency Torque Gain 0~100 50 % ⟦blank source cell⟧
4 02-16 SLV Without Load Slip Compensation Gain 0~200 by series % ⟦blank source cell⟧
5 02-17 SLV With Load Slip Compensation Gain 0~200 150 % ⟦blank source cell⟧
6 02-18 SLV With Load Torque Compensation Gain 0~200 100 % ⟦blank source cell⟧
7 02-19 SLV Slip Compensation Select 0: Slip Compensation 1 2: Slip Compensation 2 0 ⟦blank source cell⟧ ⟦blank source cell⟧

Group 03- Multi function Digital Inputs/Outputs — PDF page 55

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs
2 No. Description Range Factory Setting Unit Note
3 03-00 Multifunction Input Term. S1 0:Forward/Stop Command or Run /Stop 0 - ⟦blank source cell⟧
4 03-01 Multifunction Input Term. S2 1:Reverse/Stop Command Or REV/FWD 1 - ⟦blank source cell⟧
5 03-02 Multifunction Input Term. S3 2:Preset Speed 1 (5-02) 2 - ⟦blank source cell⟧
6 03-03 Multifunction Input Term. S4 3:Preset Speed 2 (5-03) 3 - ⟦blank source cell⟧
7 03-04 Multifunction Input Term. S5 4:Preset Speed 4 (5-05) 17 - ⟦blank source cell⟧
8 03-04 Multifunction Input Term. S5 6:Jog Forward Command 17 - ⟦blank source cell⟧
9 03-04 Multifunction Input Term. S5 7:Jog Reverse Command 17 - ⟦blank source cell⟧
10 03-04 Multifunction Input Term. S5 8:Up Command 17 - ⟦blank source cell⟧
11 03-04 Multifunction Input Term. S5 9:Down Command 17 - ⟦blank source cell⟧
12 03-04 Multifunction Input Term. S5 10:Acc/Dec 2 17 - ⟦blank source cell⟧
13 03-04 Multifunction Input Term. S5 11:Acc/Dec Disabled 17 - ⟦blank source cell⟧
14 03-04 Multifunction Input Term. S5 12:Main/Alternative Run Command select 17 - ⟦blank source cell⟧
15 03-04 Multifunction Input Term. S5 13:Main/Alternative Frequency Command select 17 - ⟦blank source cell⟧
16 03-04 Multifunction Input Term. S5 14:Rapid Stop ( Decel to stop) 17 - ⟦blank source cell⟧
17 03-04 Multifunction Input Term. S5 15:Base Block 17 - ⟦blank source cell⟧
18 03-04 Multifunction Input Term. S5 16:Disable PID Function 17 - ⟦blank source cell⟧
19 03-04 Multifunction Input Term. S5 17:Reset 17 - ⟦blank source cell⟧
20 03-04 Multifunction Input Term. S5 18:Auto Run Mode enable 17 - ⟦blank source cell⟧
21 03-05 Reserved Reserved Reserved Reserved Reserved
22 03-06 Up/Down frequency band 0.00~5.00 0.00 Hz ⟦blank source cell⟧
23 03-07 Up/Down Frequency modes 0:Preset frequency is held as the inverter stops, and the UP/Down function is disabled. 0 - ⟦blank source cell⟧
24 03-07 Up/Down Frequency modes 1:Preset frequency is reset to 0 Hz as the inverter stops. 0 - ⟦blank source cell⟧
25 03-07 Up/Down Frequency modes 2:Preset frequency is held as the inverter stops, and the UP/Down is available. 0 - ⟦blank source cell⟧
26 03-08 S1~S5 scan confirmation 1~200. Number of Scan cycles 10 2ms ⟦blank source cell⟧
27 03-09 S1~ S5 switch type select xxxx0:S1 NO xxxx1:S1 NC 00000 - ⟦blank source cell⟧
28 03-09 S1~ S5 switch type select xxx0x:S2 NO xxx1x:S2 NC 00000 - ⟦blank source cell⟧
29 03-09 S1~ S5 switch type select xx0xx:S3 NO xx1xx:S3 NC 00000 - ⟦blank source cell⟧
30 03-09 S1~ S5 switch type select x0xxx:S4 NO x1xxx:S4 NC 00000 - ⟦blank source cell⟧

Manual — Group03digitalI/O continuation — page 56

Manual reference: Ver.02, January 2016, physical PDF page 56. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

※ “NO” indicates normally open, “NC” indicates normally closed.

Group03digitalI/O continuation. First unlabelled range row continues parameter03-09 from physical55; physical blank cells retained and not filled.

Group 03- Multi function Digital Inputs/Outputs — PDF page 56

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs Group 03- Multi function Digital Inputs/Outputs
2 No. Description Description Range Range Factory Setting Unit Note
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 0xxxx:S5 NO 1xxxx:S5 NC 0xxxx:S5 NO 1xxxx:S5 NC ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 03-10 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
5 03-11 Output Relay(RY1) Output Relay(RY1) 0:Run 0:Run 0 - ⟦blank source cell⟧
6 03-11 Output Relay(RY1) Output Relay(RY1) 1:Fault 1:Fault 0 - ⟦blank source cell⟧
7 03-11 Output Relay(RY1) Output Relay(RY1) 2:Setting Frequency Reached 2:Setting Frequency Reached 0 - ⟦blank source cell⟧
8 03-11 Output Relay(RY1) Output Relay(RY1) 3:Frequency Reached (3-13±3-14) 3:Frequency Reached (3-13±3-14) 0 - ⟦blank source cell⟧
9 03-11 Output Relay(RY1) Output Relay(RY1) 4:Output Frequency Detection1(> 3-13) 4:Output Frequency Detection1(> 3-13) 0 - ⟦blank source cell⟧
10 03-11 Output Relay(RY1) Output Relay(RY1) 5:Output Frequency Detection2(< 3-13) 5:Output Frequency Detection2(< 3-13) 0 - ⟦blank source cell⟧
11 03-11 Output Relay(RY1) Output Relay(RY1) 6:Auto-Restart 6:Auto-Restart 0 - ⟦blank source cell⟧
12 03-11 Output Relay(RY1) Output Relay(RY1) 7:Momentary AC Power Loss 7:Momentary AC Power Loss 0 - ⟦blank source cell⟧
13 03-11 Output Relay(RY1) Output Relay(RY1) 8:Rapid Stop 8:Rapid Stop 0 - ⟦blank source cell⟧
14 03-11 Output Relay(RY1) Output Relay(RY1) 9:Base Block 9:Base Block 0 - ⟦blank source cell⟧
15 03-11 Output Relay(RY1) Output Relay(RY1) 10:Motor Overload Protection(OL1) 10:Motor Overload Protection(OL1) 0 - ⟦blank source cell⟧
16 03-11 Output Relay(RY1) Output Relay(RY1) 11:Drive Overload Protection(OL2) 11:Drive Overload Protection(OL2) 0 - ⟦blank source cell⟧
17 03-11 Output Relay(RY1) Output Relay(RY1) 12:Reserved 12:Reserved 0 - ⟦blank source cell⟧
18 03-11 Output Relay(RY1) Output Relay(RY1) 13:Output Current Reached 13:Output Current Reached 0 - ⟦blank source cell⟧
19 03-11 Output Relay(RY1) Output Relay(RY1) 14:Brake Control 14:Brake Control 0 - ⟦blank source cell⟧
20 03-11 Output Relay(RY1) Output Relay(RY1) 15:PID feedback disconnection detection 15:PID feedback disconnection detection ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 03-12 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
22 03-13 Output frequency detection level (Hz) 0.00~599.00 0.00~599.00 0.00~599.00 0.00 Hz *1
23 03-14 Frequency Detection band 0.00~30.00 0.00~30.00 0.00~30.00 2.00 Hz *1
24 03-15 Output Current Detection Level 0.1~15.0 0.1~15.0 0.1~15.0 0.1 A ⟦blank source cell⟧
25 03-16 Output Current Detection Period 0.1~10.0 0.1~10.0 0.1~10.0 0.1 s ⟦blank source cell⟧
26 03-17 External Brake Release level 0.00~20.00 0.00~20.00 0.00~20.00 0.00 Hz ⟦blank source cell⟧
27 03-18 External Brake Engage Level 0.00~20.00 0.00~20.00 0.00~20.00 0.00 Hz ⟦blank source cell⟧
28 03-19 Relay Output function type 0:A (Normally open) 1:B (Normally close) 0:A (Normally open) 1:B (Normally close) 0:A (Normally open) 1:B (Normally close) 0 - ⟦blank source cell⟧
29 03-20 Braking Transistor On Level 100/200V: 240.0~400.0V 400V: 500.0~800.0V 100/200V: 240.0~400.0V 400V: 500.0~800.0V 220/230V: 380 VDC ⟦blank source cell⟧
30 03-20 Braking Transistor On Level 100/200V: 240.0~400.0V 400V: 500.0~800.0V 100/200V: 240.0~400.0V 400V: 500.0~800.0V 380/400V: 690 VDC ⟦blank source cell⟧
31 03-20 Braking Transistor On Level 100/200V: 240.0~400.0V 400V: 500.0~800.0V 100/200V: 240.0~400.0V 400V: 500.0~800.0V 415/460V: 780 VDC ⟦blank source cell⟧
32 03-21 Brake Transistor Off Level 100/200V: 240.0~400.0V 400V: 500.0~800.0V 100/200V: 240.0~400.0V 400V: 500.0~800.0V 220/230V: 360 VDC ⟦blank source cell⟧
33 03-21 Brake Transistor Off Level 100/200V: 240.0~400.0V 400V: 500.0~800.0V 100/200V: 240.0~400.0V 400V: 500.0~800.0V 380/400V: 670 VDC ⟦blank source cell⟧
34 03-21 Brake Transistor Off Level 100/200V: 240.0~400.0V 400V: 500.0~800.0V 100/200V: 240.0~400.0V 400V: 500.0~800.0V 415/460V: 760 VDC ⟦blank source cell⟧

Manual — Group04analog inputs/output — page 57

Manual reference: Ver.02, January 2016, physical PDF page 57. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group04analog inputs/output

Group 04- Analog signal inputs/ Analogue output functions — PDF page 57

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Group 04- Analog signal inputs/ Analogue output functions Group 04- Analog signal inputs/ Analogue output functions Group 04- Analog signal inputs/ Analogue output functions Group 04- Analog signal inputs/ Analogue output functions Group 04- Analog signal inputs/ Analogue output functions Group 04- Analog signal inputs/ Analogue output functions Group 04- Analog signal inputs/ Analogue output functions Group 04- Analog signal inputs/ Analogue output functions
2 No. Description Range Range Range Factory Setting Unit Note
3 04-00 AVI/ACI analog Input signal type select ⟦blank source cell⟧ ACI AVI 0 - ⟦blank source cell⟧
4 04-00 AVI/ACI analog Input signal type select 0: 0~10V 0~20mA 0 - ⟦blank source cell⟧
5 04-00 AVI/ACI analog Input signal type select 1: 0~10V 4~20mA 0 - ⟦blank source cell⟧
6 04-00 AVI/ACI analog Input signal type select 2: 2~10V 0~20mA 0 - ⟦blank source cell⟧
7 04-00 AVI/ACI analog Input signal type select 3: 2~10V 4~20mA 0 - ⟦blank source cell⟧
8 04-01 AVI Signal Verification Scan rate 1~200 1~200 1~200 50 2ms ⟦blank source cell⟧
9 04-02 AVI Gain 0~1000 0~1000 0~1000 100 % *1
10 04-03 AVI Bias 0~100 0~100 0~100 0 % *1
11 04-04 AVI Bias Selection 0: Positive 1: Negative 0: Positive 1: Negative 0: Positive 1: Negative 0 - *1
12 04-05 AVI Slope 0: Positive 1: Negative 0: Positive 1: Negative 0: Positive 1: Negative 0 - *1
13 04-06 ACI Signal Verification Scan rate 1~200 1~200 1~200 50 2ms ⟦blank source cell⟧
14 04-07 ACI Gain 0~1000 0~1000 0~1000 100 % *1
15 04-08 ACIBias 0~100 0~100 0~100 0 % *1
16 04-09 ACI Bias Selection 0: Positive 1: Negative 0: Positive 1: Negative 0: Positive 1: Negative 0 - *1
17 04-10 ACI Slope 0: Positive 1: Negative 0: Positive 1: Negative 0: Positive 1: Negative 0 - *1
18 04-11 Analog Output mode (AO) 0: Output Frequency 0: Output Frequency 0: Output Frequency 0 - *1
19 04-11 Analog Output mode (AO) 1: Frequency Command 1: Frequency Command 1: Frequency Command 0 - *1
20 04-11 Analog Output mode (AO) 2: Output Voltage 2: Output Voltage 2: Output Voltage 0 - *1
21 04-11 Analog Output mode (AO) 3: DC Bus Voltage 3: DC Bus Voltage 3: DC Bus Voltage 0 - *1
22 04-11 Analog Output mode (AO) 4: Motor Current 4: Motor Current 4: Motor Current 0 - *1
23 04-12 Analog Output AO Gain (%) 0~1000 0~1000 0~1000 100 % *1
24 04-13 Analog Output AO Bias (%) 0~1000 0~1000 0~1000 0 % *1
25 04-14 AO Bias Selection 0: Positive 1: Negative 0: Positive 1: Negative 0: Positive 1: Negative 0 - *1
26 04-15 AO Slope 0: Positive 1: Negative 0: Positive 1: Negative 0: Positive 1: Negative 0 - *1

Manual — Group05preset frequencies — page 58

Manual reference: Ver.02, January 2016, physical PDF page 58. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group05preset frequencies

Group 05- Preset Frequency Selections. — PDF page 58

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 05- Preset Frequency Selections. Group 05- Preset Frequency Selections. Group 05- Preset Frequency Selections. Group 05- Preset Frequency Selections. Group 05- Preset Frequency Selections. Group 05- Preset Frequency Selections.
2 No. Description Range Factory Setting Unit Note
3 05-00 Preset Speed Control mode Selection 0: Common Accel/Decel Accel/Decel 1 or 2 apply to all speeds 0 - ⟦blank source cell⟧
4 05-00 Preset Speed Control mode Selection 1: Individual Accel/Decel Accel/ Decel 0-7 apply to the selected preset speeds (Acc0/Dec0~ Acc7/Dec7) 0 - ⟦blank source cell⟧
5 05-01 Preset Speed 0 (Keypad Freq) 0.00 ~ 599.00 5.00 Hz *1
6 05-02 Preset Speed1 (Hz) 0.00 ~ 599.00 5.00 Hz *1
7 05-03 Preset Speed2 (Hz) 0.00 ~ 599.00 10.00 Hz *1
8 05-04 Preset Speed3 (Hz) 0.00 ~ 599.00 20.00 Hz *1
9 05-05 Preset Speed4 (Hz) 0.00 ~ 599.00 30.00 Hz *1
10 05-06 Preset Speed5 (Hz) 0.00 ~ 599.00 40.00 Hz *1
11 05-07 Preset Speed6 (Hz) 0.00 ~ 599.00 50.00 Hz *1
12 05-08 Preset Speed7 (Hz) 0.00 ~ 599.00 50.00 Hz *1
13 05-09 ~ 05-16 Reserved Reserved Reserved Reserved Reserved
14 05-17 Preset Speed0-Acctime 0.1 ~ 3600.0 10.0 s *1
15 05-18 Preset Speed0-Dectime 0.1 ~ 3600.0 10.0 s *1
16 05-19 Preset Speed1-Acctime 0.1 ~ 3600.0 10.0 s *1
17 05-20 Preset Speed1-Dectime 0.1 ~ 3600.0 10.0 s *1
18 05-21 Preset Speed2-Acctime 0.1 ~ 3600.0 10.0 s *1
19 05-22 Preset Speed2-Dectime 0.1 ~ 3600.0 10.0 s *1
20 05-23 Preset Speed3-Acctime 0.1 ~ 3600.0 10.0 s *1
21 05-24 Preset Speed3-Dectime 0.1 ~ 3600.0 10.0 s *1
22 05-25 Preset Speed4-Acctime 0.1 ~ 3600.0 10.0 s *1
23 05-26 Preset Speed4-Dectime 0.1 ~ 3600.0 10.0 s *1
24 05-27 Preset Speed5-Acctime 0.1 ~ 3600.0 10.0 s *1
25 05-28 Preset Speed5-Dectime 0.1 ~ 3600.0 10.0 s *1
26 05-29 Preset Speed6-Acctime 0.1 ~ 3600.0 10.0 s *1
27 05-30 Preset Speed6-Dectime 0.1 ~ 3600.0 10.0 s *1
28 05-31 Preset Speed7-Acctime 0.1 ~ 3600.0 10.0 s *1
29 05-32 Preset Speed7-Dectime 0.1 ~ 3600.0 10.0 s *1

Manual — Group06auto sequencer — page 59

Manual reference: Ver.02, January 2016, physical PDF page 59. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group06auto sequencer

Group 06- Auto Run(Auto Sequencer) function — PDF page 59

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function
2 No. Description Range Factory Setting Unit Note
3 06-00 Auto Run (sequencer) mode selection 0: Disabled. 1: Single cycle. (Continues to run from the Unfinished step if restarted). 2: Periodic cycle. (Continues to run from the unfinished step if restarted). 3: Single cycle, then holds the speed Of final step to run. (Continues to run from the unfinished step if restarted). 4: Single cycle. (Starts a new cycle if restarted). 5: Periodic cycle. (Starts a new cycle if restarted). 6: Single cycle, then hold the speed of final step to run (Starts a new cycle if restarted). 0 - ⟦blank source cell⟧
4 06-01 Auto _ Run Mode frequency command 1 0.00~599.00 0.00 Hz *1
5 06-02 Auto _ Run Mode frequency command 2 0.00~599.00 0.00 Hz *1
6 06-03 Auto _ Run Mode frequency command 3 0.00~599.00 0.00 Hz *1
7 06-04 Auto _ Run Mode frequency command 4 0.00~599.00 0.00 Hz *1
8 06-05 Auto _ Run Mode frequency command 5 0.00~599.00 0.00 Hz *1
9 06-06 Auto _ Run Mode frequency command 6 0.00~599.00 0.00 Hz *1
10 06-07 Auto _ Run Mode frequency command 7 0.00~599.00 0.00 Hz *1
11 06-08 ~ 06-15 Reserved Reserved Reserved Reserved Reserved
12 06-16 Auto_ Run Mode running time setting 0 0.0 ~ 3600.0 0.0 s *1
13 06-17 Auto_ Run Mode running time setting 1 0.0 ~ 3600.0 0.0 s *1
14 06-18 Auto_ Run Mode running time setting 2 0.0 ~ 3600.0 0.0 s *1
15 06-19 Auto_ Run Mode running time setting 3 0.0 ~ 3600.0 0.0 s *1
16 06-20 Auto_ Run Mode running time setting 4 0.0 ~ 3600.0 0.0 s *1
17 06-21 Auto_ Run Mode running time setting 5 0.0 ~ 3600.0 0.0 s *1
18 06-22 Auto_ Run Mode running time setting 6 0.0 ~ 3600.0 0.0 s *1
19 06-23 Auto_ Run Mode running time setting 7 0.0 ~ 3600.0 0.0 s *1
20 06-24 ~ 06-31 Reserved Reserved Reserved Reserved Reserved
21 06-32 Auto_ Run Mode running direction 0 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧
22 06-33 Auto_ Run Mode running direction 1 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧

Manual — Group06continuation andGroup07start/stop — page 60

Manual reference: Ver.02, January 2016, physical PDF page 60. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group06continuation andGroup07start/stop

Group 06- Auto Run(Auto Sequencer) function — PDF page 60

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function Group 06- Auto Run(Auto Sequencer) function
2 No. Description Range Factory Setting Unit Note
3 06-34 Auto_ Run Mode running direction 2 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧
4 06-35 Auto_ Run Mode running direction 3 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧
5 06-36 Auto_ Run Mode running direction 4 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧
6 06-37 Auto_ Run Mode running direction 5 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧
7 06-38 Auto_ Run Mode running direction 6 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧
8 06-39 Auto_ Run Mode running direction 7 0: Stop 1: Forward 2: Reverse 0 - ⟦blank source cell⟧

Group 07- Start/Stop command setup — PDF page 60

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 07- Start/Stop command setup Group 07- Start/Stop command setup Group 07- Start/Stop command setup Group 07- Start/Stop command setup Group 07- Start/Stop command setup Group 07- Start/Stop command setup
2 No. Description Range Factory Setting Unit Note
3 07-00 Momentary Power Loss and Restart 0: Momentary Power Loss and Restart disable 1: Momentary power loss and restart enable 0 s ⟦blank source cell⟧
4 07-01 Auto Restart Delay Time 0.0~800.0 0.0 s ⟦blank source cell⟧
5 07-02 Number of Auto Restart Attempts 0~10 0 - ⟦blank source cell⟧
6 07-03 Reset Mode Setting 0: Enable Reset Only when Run Command is Off 1: Enable Reset when Run Command is On or Off 0 - ⟦blank source cell⟧
7 07-04 Direct Running After Power Up 0: Enable Direct run on power up 1: Disable Direct run on power up 1 - ⟦blank source cell⟧
8 07-05 Delay-ON Timer 1.0~300.0 1.0 s ⟦blank source cell⟧
9 07-06 DC Injection Brake Start Frequency (Hz) In Stop mode 0.10 ~ 10.00 1.5 Hz ⟦blank source cell⟧
10 07-07 DC Injection Brake Level (%) In stop mode 0 ~ 20 (Frame1/2). Based on the 20% of maximum output voltage 5 % ⟦blank source cell⟧
11 07-07 DC Injection Brake Level (%) In stop mode 0 ~ 100 (Frame3/4) based on the rated current 50 % ⟦blank source cell⟧
12 07-08 DC Injection Brake Time (Seconds) In stop mode 0.0 ~ 25.5 0.5 s ⟦blank source cell⟧
13 07-09 Stopping Method 0: Deceleration to stop 1: Coast to stop 0 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Group08drive/motor protection — page 61

Manual reference: Ver.02, January 2016, physical PDF page 61. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group08drive/motor protection

Group 08- Drive & Motor Protection functions — PDF page 61

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions
2 No. Description Range Factory Setting Unit Note
3 08-00 Trip Prevention Selection xxxx0: Enable Trip Prevention During Acceleration xxxx1: Disable Trip Prevention During Acceleration xxx0x: Enable Trip Prevention During Deceleration xxx1x: Disable Trip Prevention During Deceleration xx0xx: Enable Trip Prevention in Run Mode xx1xx: Disable Trip Prevention in Run Mode x0xxx: Enable over voltage Prevention in Run Mode x1xxx: Disable over voltage Prevention in Run Mode 00000 - ⟦blank source cell⟧
4 08-01 Trip Prevention Level During Acceleration (%) 50 ~ 200 by series Inverter Rated Current 100% ⟦blank source cell⟧
5 08-02 Trip Prevention Level During Deceleration (%) 50 ~ 200 by series Inverter Rated Current 100% ⟦blank source cell⟧
6 08-03 Trip Prevention Level In Run Mode (%) 50 ~ 200 by series Inverter Rated Current 100% ⟦blank source cell⟧
7 08-04 over voltage Prevention Level in Run Mode 200V: 350.0~390.0 400V: 700.0~780.0 380.0/760.0 VDC *1
8 08-05 Electronic Motor Overload Protection Operation Mode xxxx0: Disable Electronic Motor Overload Protection 00001 - ⟦blank source cell⟧
9 08-05 Electronic Motor Overload Protection Operation Mode xxxx1: Enable Electronic Motor Overload Protection 00001 - ⟦blank source cell⟧
10 08-05 Electronic Motor Overload Protection Operation Mode xxx0x: Motor Overload Cold Start 00001 - ⟦blank source cell⟧
11 08-05 Electronic Motor Overload Protection Operation Mode xxx1x: Motor Overload Hot Start 00001 - ⟦blank source cell⟧
12 08-05 Electronic Motor Overload Protection Operation Mode xx0xx: Standard Motor 00001 - ⟦blank source cell⟧
13 08-05 Electronic Motor Overload Protection Operation Mode xx1xx: Invertor Duty Motor 00001 - ⟦blank source cell⟧
14 08-06 Operation After Overload Protection is Activated 0: Coast-to-Stop After Overload Protection is Activated 0 - ⟦blank source cell⟧
15 08-06 Operation After Overload Protection is Activated 1: Drive Will Not Trip when Overload Protection is Activated (OL1) 0 - ⟦blank source cell⟧
16 08-07 Over heat Protection (cooling fan control) 0: Auto (Depends on temp.) 1 - ⟦blank source cell⟧
17 08-07 Over heat Protection (cooling fan control) 1: Operate while in RUN mode 1 - ⟦blank source cell⟧
18 08-07 Over heat Protection (cooling fan control) 2: Always Run 1 - ⟦blank source cell⟧
19 08-07 Over heat Protection (cooling fan control) 3: Disabled 1 - ⟦blank source cell⟧
20 08-08 AVR Function (Auto Voltage Regulation) 0: AVR function enable 4 - ⟦blank source cell⟧
21 08-08 AVR Function (Auto Voltage Regulation) 1: AVR function Disable 4 - ⟦blank source cell⟧
22 08-08 AVR Function (Auto Voltage Regulation) 2: AVR function disable for stop 4 - ⟦blank source cell⟧
23 08-08 AVR Function (Auto Voltage Regulation) 3: AVR function disable for deceleration 4 - ⟦blank source cell⟧
24 08-08 AVR Function (Auto Voltage Regulation) 4: AVR function disable for stop and deceleration. 4 - ⟦blank source cell⟧
25 08-08 AVR Function (Auto Voltage Regulation) 5: When VDC>(360V/740V), AVR function disable for stop and deceleration. 4 - ⟦blank source cell⟧
26 08-09 Input phase lost protection 0: Disabled 0 - ⟦blank source cell⟧
27 08-09 Input phase lost protection 1: Enabled 0 - ⟦blank source cell⟧
28 08-10 PTC Overheat Function 0: Disable 0 ⟦blank source cell⟧ ⟦blank source cell⟧
29 08-10 PTC Overheat Function 1: Decelerate to stop ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 08-10 PTC Overheat Function 2: Coast to stop ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Group08continuation andGroup09communications — page 62

Manual reference: Ver.02, January 2016, physical PDF page 62. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group08continuation andGroup09communications. First unlabelled range row continues parameter08-10 from physical61; physical blank cells retained and not filled.

Group08continuation andGroup09communications

Group 08- Drive & Motor Protection functions — PDF page 62

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions Group 08- Drive & Motor Protection functions
2 No. Description Range Factory Setting Unit Note
3 ⟦blank source cell⟧ ⟦blank source cell⟧ 3: Continue running, when warning level is reached. Coast to stop, when protection level is reached. ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 08-11 PTC Signal Smoothing Time 0.01~10.00 0.2 Sec ⟦blank source cell⟧
5 08-12 PTC Detection Time Delay 1~300 60 Sec ⟦blank source cell⟧
6 08-13 PTC Protection Level 0.1~10.0 0.7 V ⟦blank source cell⟧
7 08-14 PTC Detection Level Reset 0.1~10.0 0.3 V ⟦blank source cell⟧
8 08-15 PTC Warning Level 0.1~10.0 0.5 V ⟦blank source cell⟧
9 08-16 Fan Control Temperature Level 10.0~50.0 50.0 °C ⟦blank source cell⟧

Group 09- Communication function setup — PDF page 62

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 09- Communication function setup Group 09- Communication function setup Group 09- Communication function setup Group 09- Communication function setup Group 09- Communication function setup Group 09- Communication function setup
2 No. Description Range Factory Setting Unit Note
3 09-00 Assigned Communication Station Number 1 ~ 32 1 - *2*3
4 09-01 Communication Mode Select 0:Modbus RTU code 1:Modbus ASCII code 2:BACnet 0 - *2*3
5 09-02 Baud Rate Setting (bps) 0:4800 1:9600 2:19200 3:38400 2 bps *2*3
6 09-03 Stop Bit Selection 0:1 Stop Bit 1:2 Stop Bits 0 - *2*3
7 09-04 Parity Selection 0:Without Parity 1:With Even Parity 2:With Odd Parity 0 - *2*3
8 09-05 Data Format Selection 0: 8-Bits Data 1: 7-Bits Data 0 - *2*3
9 09-06 Communication time-out detection time 0.0 ~ 25.5 0.0 s ⟦blank source cell⟧
10 09-07 Communication time-out operation selection 0:Deceleration to stop (set by 00-15) 1: Coast to stop 2: Deceleration to stop (set by 00-17) 3: continue operating 0 - ⟦blank source cell⟧
11 09-08 Error 6 verification time. 1 ~ 20 3 ⟦blank source cell⟧ ⟦blank source cell⟧
12 09-09 Drive Transmit delay Time(ms) 5 ~ 65 5 2ms ⟦blank source cell⟧
13 09-10 BACnet stations 1~254 1 ⟦blank source cell⟧ *2*3

Manual — Group10PID parameters — page 63

Manual reference: Ver.02, January 2016, physical PDF page 63. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group10PID parameters

Group10- PID function Setup — PDF page 63

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group10- PID function Setup Group10- PID function Setup Group10- PID function Setup Group10- PID function Setup Group10- PID function Setup Group10- PID function Setup
2 No. Description Range Factory Setting Unit Note
3 10-00 PID target value selection (when 00-05\00-06=6 ,this function is enabled) 0:Potentiometer on Keypad 1 - *1
4 10-00 PID target value selection (when 00-05\00-06=6 ,this function is enabled) 1: Analog Signal Input. (AVI) 1 - *1
5 10-00 PID target value selection (when 00-05\00-06=6 ,this function is enabled) 2: Analog Signal Input. (ACI) 1 - *1
6 10-00 PID target value selection (when 00-05\00-06=6 ,this function is enabled) 3: Frequency set by communication 1 - *1
7 10-00 PID target value selection (when 00-05\00-06=6 ,this function is enabled) 4: 10-02 given 1 - *1
8 10-01 PID feedback value selection 0: Potentiometer on Keypad 2 - *1
9 10-01 PID feedback value selection 1: Analog Signal Input. (AVI) 2 - *1
10 10-01 PID feedback value selection 2: Analog Signal Input. (ACI) 2 - *1
11 10-01 PID feedback value selection 3: Communication Setting Frequency 2 - *1
12 10-02 PID Target (keypad input) 0.0~100.0 50.0 % *1
13 10-03 PID Mode Selection 0: Disabled. 0 - ⟦blank source cell⟧
14 10-03 PID Mode Selection 1: Deviation D Control. FWD Characteristic. 0 - ⟦blank source cell⟧
15 10-03 PID Mode Selection 2: Feedback D Control. FWD Characteristic 0 - ⟦blank source cell⟧
16 10-03 PID Mode Selection 3: Deviation D Control. Reverse Characteristic. 0 - ⟦blank source cell⟧
17 10-03 PID Mode Selection 4: Feedback D Control. Reverse Characteristic 0 - ⟦blank source cell⟧
18 10-03 PID Mode Selection 5: Frequency Command + Deviation D Control. FWD Characteristic 0 - ⟦blank source cell⟧
19 10-03 PID Mode Selection 6: Frequency Command + Feedback D Control FWD Characteristic. 0 - ⟦blank source cell⟧
20 10-03 PID Mode Selection 7: Frequency Command + Deviation D Control Reverse Characteristic. 0 - ⟦blank source cell⟧
21 10-03 PID Mode Selection 8: Frequency Command + Feedback D Control Reverse Characteristic 0 - ⟦blank source cell⟧
22 10-04 Feedback Gain Coefficient 0.00 ~ 10.00 1.00 % *1
23 10-05 Proportional Gain 0.0 ~ 10.0 1.0 % *1
24 10-06 Integral Time 0.0 ~ 100.0 10.0 s *1
25 10-07 Derivative Time 0.00 ~ 10.00 0.00 s *1
26 10-08 PID Offset 0: Positive 0 - *1
27 10-08 PID Offset 1: Negative 0 - *1
28 10-09 PID Offset Adjust 0 ~ 109 0 % *1
29 10-10 PID Output Lag Filter Time 0.0 ~ 2.5 0.0 s *1
30 10-11 Feedback Loss Detection Mode 0: Disabled 0 - ⟦blank source cell⟧
31 10-11 Feedback Loss Detection Mode 1: Drive keeps running after feedback loss 0 - ⟦blank source cell⟧
32 10-11 Feedback Loss Detection Mode 2: Drive stops after feedback loss 0 - ⟦blank source cell⟧
33 10-12 Feedback Loss Detection Level 0 ~ 100 0 % ⟦blank source cell⟧
34 10-13 Feedback Loss Detection Delay Time 0.0 ~25.5 1.0 s ⟦blank source cell⟧
35 10-14 Integration Limit Value 0 ~ 109 100 % *1
36 10-15 Integral Value Resets to Zero when Feedback Signal Equals the Target Value 0: Disabled 0 - ⟦blank source cell⟧
37 10-15 Integral Value Resets to Zero when Feedback Signal Equals the Target Value 1: 1 Second 0 - ⟦blank source cell⟧
38 10-15 Integral Value Resets to Zero when Feedback Signal Equals the Target Value 30: 30 Seconds (0 ~ 30) 0 - ⟦blank source cell⟧
39 10-16 Allowable Integration Error. Margin (units)(1unit = 1/8192) 0 ~ 100 0 - ⟦blank source cell⟧
40 10-17 PID Sleep Frequency Level 0.00~599.00 0.00 Hz ⟦blank source cell⟧
41 10-18 PID Sleep Function Delay Time 0.0 ~25.5 0.0 s ⟦blank source cell⟧
42 10-19 PID Wake up frequency Level 0.00 ~ 599.00 0.00 Hz ⟦blank source cell⟧
43 10-20 PID Wake up function Delay Time 0.0 ~ 25.5 0.0 s ⟦blank source cell⟧
44 10-21 Max PID Feedback Setting 0 ~999 100 - *1
45 10-22 Min PID Feedback Setting 0 ~999 0 - *1

Manual — Group11 performance parameters — page 64

Manual reference: Ver.02, January 2016, physical PDF page 64. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group11 performance parameters

Group11- Performance Control functions — PDF page 64

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group11- Performance Control functions Group11- Performance Control functions Group11- Performance Control functions Group11- Performance Control functions Group11- Performance Control functions Group11- Performance Control functions
2 No. Description Range Factory Setting unit Note
3 11-00 Reverse operation control 0: Reverse command is valid 0 - ⟦blank source cell⟧
4 11-00 Reverse operation control 1: Reverse command is invalid 0 - ⟦blank source cell⟧
5 11-01 Carrier Frequency (kHz) 1~16 5 KHz ⟦blank source cell⟧
6 11-02 Carrier mode Selection 0: Mode0, 3phase PWM modulation 1 - ⟦blank source cell⟧
7 11-02 Carrier mode Selection 1: Mode1, 2phase PWM modulation 1 - ⟦blank source cell⟧
8 11-02 Carrier mode Selection 2: Mode2, random PWM modulation 1 - ⟦blank source cell⟧
9 11-03 Carrier Frequency Reduction by temperature rise 0: Disabled 0 - ⟦blank source cell⟧
10 11-03 Carrier Frequency Reduction by temperature rise 1: Enabled 0 - ⟦blank source cell⟧
11 11-04 S-Curve Acc 1 0.0 ~ 4.0 0.00 s ⟦blank source cell⟧
12 11-05 S-Curve Acc 2 0.0 ~ 4.0 0.00 s ⟦blank source cell⟧
13 11-06 S-Curve Dec 3 0.0 ~ 4.0 0.00 s ⟦blank source cell⟧
14 11-07 S-Curve Dec 4 0.0 ~ 4.0 0.00 s ⟦blank source cell⟧
15 11-08 Skip Frequency 1 0.00 ~ 599.00 0.00 Hz *1
16 11-09 Skip Frequency 2 0.00 ~ 599.00 0.00 Hz *1
17 11-10 Skip Frequency 3 0.00 ~ 599.00 0.00 Hz *1
18 11-11 Skip Frequency Bandwidth (±) 0.00 ~ 30.00 0.00 Hz *1
19 11-12 Reserved Reserved Reserved Reserved Reserved
20 11-13 Regeneration Prevention Function 0: Disable 0 - ⟦blank source cell⟧
21 11-13 Regeneration Prevention Function 1: Enable 0 - ⟦blank source cell⟧
22 11-13 Regeneration Prevention Function 2: Enable (during constant speed only) 0 - ⟦blank source cell⟧
23 11-14 Regeneration Prevention Voltage Level 200v: 300.0~400.0 380/760 V ⟦blank source cell⟧
24 11-14 Regeneration Prevention Voltage Level 400v: 600.0~800.0 380/760 V ⟦blank source cell⟧
25 11-15 Regeneration Prevention Frequency Limit 0.00~15.00 3.00 Hz ⟦blank source cell⟧
26 11-16 Regeneration Prevention Voltage Gain 0~200 100 % ⟦blank source cell⟧
27 11-17 Regeneration Prevention Frequency Gain 0~200 100 % ⟦blank source cell⟧
28 11-18 Speed loop proportion gain 0~65535 10000 ⟦blank source cell⟧ ⟦blank source cell⟧
29 11-19 Speed loop integration gain 0 ~65535 800 ⟦blank source cell⟧ ⟦blank source cell⟧
30 11-20 Speed loop differential gain 0 ~65535 0 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Group12 display and terminal status — page 65

Manual reference: Ver.02, January 2016, physical PDF page 65. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Group12 display and terminal status

Group12 Digital Display & Monitor functions — PDF page 65

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group12 Digital Display & Monitor functions Group12 Digital Display & Monitor functions Group12 Digital Display & Monitor functions Group12 Digital Display & Monitor functions Group12 Digital Display & Monitor functions Group12 Digital Display & Monitor functions
2 No. Description Range Factory Setting Unit Note
3 12-00 Extended Display Mode 00000 ~77777. Each digit can be set to 0 to 7 00000 - *1
4 12-00 Extended Display Mode 0: Default display (frequency&parameters) 00000 - *1
5 12-00 Extended Display Mode 1:Output Current 00000 - *1
6 12-00 Extended Display Mode 2:Output Voltage 00000 - *1
7 12-00 Extended Display Mode 3:DC voltage 00000 - *1
8 12-00 Extended Display Mode 4:Temperature of Heat sink 00000 - *1
9 12-00 Extended Display Mode 5:PID feedback 00000 - *1
10 12-00 Extended Display Mode 6:Analog Signal Input. (AVI) 00000 - *1
11 12-00 Extended Display Mode 7:Analog Signal Input. (ACI) 00000 - *1
12 12-01 PID Feedback Display format 0: Integer (xxx) 0 - *1
13 12-01 PID Feedback Display format 1:One decimal Place (xx.x) 0 - *1
14 12-01 PID Feedback Display format 2:Two Decimal Places (x.xx) 0 - *1
15 12-02 PID Feedback Display Unit Setting 0:xxx-- 0 - *1
16 12-02 PID Feedback Display Unit Setting 1:xxxpb (pressure) 0 - *1
17 12-02 PID Feedback Display Unit Setting 2:xxxfl (flow) 0 - *1
18 12-03 Custom Units (Line Speed) Value 0~65535 1500/1800 RPM *1
19 12-04 Custom Units (Line Speed) Display Mode 0:Drive Output Frequency is Displayed 0 - *1
20 12-04 Custom Units (Line Speed) Display Mode 1:Line Speed. Integer.(xxxxx) 0 - *1
21 12-04 Custom Units (Line Speed) Display Mode 2:Line Speed..One Decimal Place (xxxx.x) 0 - *1
22 12-04 Custom Units (Line Speed) Display Mode 3:Line Speed.Two Decimal Places (xxx.xx) 0 - *1
23 12-04 Custom Units (Line Speed) Display Mode 4:Line Speed.Three Decimal Places (xx.xxx) 0 - *1
24 12-05 Inputs and output Logic status display ( S1 to S5) & RY1 S1 S2 S3 S4 S5 RY1 ----- - *4

Manual — Group13 inspection and factory reset — page 66

Manual reference: Ver.02, January 2016, physical PDF page 66. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Notes: For built-in EMC filter models, the default setting of 13-08 is “1250”. For without built-in EMC filter models, the default setting of 13-08 is “1360”

Group13 inspection and factory reset

Group 13 Inspection & Maintenance functions — PDF page 66

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Group 13 Inspection & Maintenance functions Group 13 Inspection & Maintenance functions Group 13 Inspection & Maintenance functions Group 13 Inspection & Maintenance functions Group 13 Inspection & Maintenance functions Group 13 Inspection & Maintenance functions
2 No. Description Range Factory Setting unit Note
3 13-00 Drive Horsepower Code ---- - - *3
4 13-01 Software Version ---- - - *3*4
5 13-02 Fault Log (Last 3 Faults) ---- - - *3*4
6 13-03 Accumulated Operation Time1 1 0~23 - hour *3
7 13-04 Accumulated Operation Time1 2 0~65535 ---- day *3
8 13-05 Accumulated Operation Time Mode 0:Time Under Power 0 - *3
9 13-05 Accumulated Operation Time Mode 1:Run Mode Time Only 0 - *3
10 13-06 Parameter Lock 0: Enable all Functions 0 - ⟦blank source cell⟧
11 13-06 Parameter Lock 1: Preset speeds 05-01~05-08 cannot be changed 0 - ⟦blank source cell⟧
12 13-06 Parameter Lock 2: All Functions cannot be changed Except for Preset speeds 05-01~05-08 0 - ⟦blank source cell⟧
13 13-06 Parameter Lock 3: Disable All Function 0 - ⟦blank source cell⟧
14 13-07 Parameter Lock Code 00000~65535 00000 - ⟦blank source cell⟧
15 13-08 Restore Factory Settings 1150: Initialization (50Hz,220V/380V) 1160: Initialization (60Hz,220V/380V) 1250: Initialization (50Hz,230V/400V) 1260: Initialization (60Hz,230V/460V) 1350: Initialization (50Hz,220V/415V) 1360: Initialization (60Hz,230V/400V) 1250/1360 (Note) - ⟦blank source cell⟧

Manual — Basic operating mode and command sources — page 67

Manual reference: Ver.02, January 2016, physical PDF page 67. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

4.3 Parameter Function Description

00- Basic parameter group

Select the relevant control mode for the application, using parameter 00-00 Control mode. Default control mode is V/F.  V/F mode can be used for most applications specifically multi-motor or applications where auto tune is not successful or when a customized V/F pattern may be required. Several V/f patterns are available selectable by parameter 01-00. Select the appropriate V/f pattern based on the application load type and the motor base frequency of 50 or 60 Hz. For selections of the V/f patterns. Refer to description of parameter 01-00  SLV ( Sensor less vector) is used for obtaining best performance from a motor. Specially at low speeds or for applications with dynamic speed change.

 00 - 01 Is valid in key pad mode only.

※Note: When Reverse function is disabled by parameter 11- 00=1 setting 00-01 to 1 .” LOC” will be

displayed

 Parameter 00 - 02/00- 03 sets the inverter operation command source. For switching between 00-02 and 00-03, use any of the external inputs S1 to S5 and set the relevant parameters (03-00~03-04) to [12]. refer to parameter group3.

 Parameter 00-04 sets the function of the External Run/Stop and it is used in conjunction with Parameters. 00-02(Main Run Source) = 1 or 00-03(Alternative Run source) = 1 (When 00-02/00-03=1, the command comes from External Run /Stop) Parameters 03-00 to 03-04, which are used to set the required function for the digital inputs S1 to S5. Note1: Parameters 03-00 to 03-04 are only Required for External Run/stop (Two wire control mode). Note2: For External Run /Stop control set parameters in the following order:

Basic operating mode and command sources

00- 00 / Control mode — PDF page 67

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 00 Control mode
2 Range 【0】: V/F mode 【1】: SLV mode

00- 01 / Motor Direction Control — PDF page 67

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 01 Motor Direction Control
2 Range 【0】: Forward 【1】: Reverse

00- 02 / Main Run Command Source selection — PDF page 67

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 02 Main Run Command Source selection
2 00- 03 Alternative Run Command Source selection
3 Range 【0】: Keypad 【1】: External Run/Stop Control 【2】: Communication

00- 04 / Operation modes for external terminals — PDF page 67

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 04 Operation modes for external terminals
2 Range 【0】: Forward/stop-reverse/stop 【1】: Run/stop-forward/reverse 【2】: 3-wire control mode -run/stop

Manual — Frequency command source selections — page 69

Manual reference: Ver.02, January 2016, physical PDF page 69. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 When 00-06 =[6], frequency command source is output of the PID.

 When 00-07=【0】, the frequency source is set by the Main frequency parameter 00-05 (Default) or by the Alternative frequency parameter 00-06. Use any of the external terminals S1 to S5 and set the relevant parameter 03-00 to 03-04 =【13】 to switch from main to Alternative source.  When 00 - 07 =【1】The Frequency command will be the result of setting of Main & alternative frequencies.

 This parameter can be used to read the set frequency in communication mode  This parameter is only effective in the communication mode.

 00-09=【0】 Keypad frequency is saved.  00-09=【1】 Frequency set by communication is saved.

 This parameter is only effective in keypad mode..  When 00-10=【0】,the initial frequency will be current frequency.  When 00-10=【1】,the initial frequency will be 0.  When 00-10=【2】,the initial frequency will be as set by parameter 00-11.

Frequency command source selections

00- 05 / Main Frequency Command Source Selection — PDF page 69

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 05 Main Frequency Command Source Selection
2 00- 06 Alternative Frequency Command Source Selection
3 Range 【0】:UP/DOWN of Keypad 【1】:Potentiometer on Keypad 【2】:External AVI Analog Signal Input 【3】:External ACI Analog Signal Input 【4】:External Up/Down Frequency Control 【5】:Communication setting Frequency 【6】:PID Output frequency

00- 07 / Main and Alternative Frequency Command Modes — PDF page 69

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 07 Main and Alternative Frequency Command Modes
2 Range 【0】:Main Or Alternative Frequency. 【1】:Main frequency + Alternative Frequency

00- 08 / Communication Frequency Command — PDF page 69

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 08 Communication Frequency Command
2 Range 【0.00~599.00】Hz

00- 09 / Frequency Command save on power down (Communication mode) — PDF page 69

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00- 09 Frequency Command save on power down (Communication mode)
2 Range 【0】:Disable 【1】:Enable

00-10 / Initial Frequency Selection — PDF page 69

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00-10 Initial Frequency Selection
2 Range 【0】:By Current Freq Command 【1】:By Zero Freq Command 【2】:By 00-11
3 00-11 Initial Frequency Set point
4 Range 【0.00~599.00】Hz

Manual — Frequency limits, acceleration and deceleration — page 70

Manual reference: Ver.02, January 2016, physical PDF page 70. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 When 00-13 and the command frequency are both set to 0.00, if RUN is pressed ” Stpo” is displayed.  When Frequency command is > than preset in 00-13 inverter output will ramp up from 0.00 to the command frequency.  When 00-13> 0, and the frequency command value ≤ 00-13, inverter output will ramp up from preset in lower limit to the command frequency.

 Preset Acceleration and Deceleration times by above parameters are the time taken for the output frequency to ramp up or ramp down between the Upper and the lower V/F frequency limits.  Actual acceleration and deceleration time is calculated as follows: V/F mode:

SLV mode:

Frequency limits, acceleration and deceleration

00-12 / Frequency Upper limit — PDF page 70

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00-12 Frequency Upper limit
2 Range 【0.01~599.00】Hz
3 00-13 Frequency Lower limit
4 Range 【0.00~598.99】Hz

00-14 / Acceleration time 1 — PDF page 70

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00-14 Acceleration time 1
2 Range 【0.1~3600.0】s
3 00-15 Deceleration time 1
4 Range 【0.1~3600.0】s
5 00-16 Acceleration time 2
6 Range 【0.1~3600.0】s
7 00-17 Deceleration time 2
8 Range 【0.1~3600.0】s

Manual — Acceleration/deceleration graph and jog parameters — page 71

Manual reference: Ver.02, January 2016, physical PDF page 71. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

V/F Maximum output frequency is for VF curve, which can be checked from table when VF curve is fixed. Maximum output frequency is 01-02 when VF curve is customized, or motor rated frequency 02-06

 The JOG function is operational by using the multi-function input terminals S1 to S5 and setting the relevant parameters 03-00~03-04 to 【6】JOG FWD or【7】JOG REV. Refer to parameter group 3.

Acceleration/deceleration graph and jog parameters

00-18 / Jog Frequency — PDF page 71

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 00-18 Jog Frequency
2 Range 【1.00~25.00】Hz
3 00-19 Jog Acceleration Time
4 Range 【0.1~25.5】sec
5 00-20 Jog Deceleration Time
6 Range 【0.1~25.5】sec

Manual — Preset V/F curves and voltage percentages — page 72

Manual reference: Ver.02, January 2016, physical PDF page 72. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Set 01-00 to one of the following preset V/f selections【1~6】according to the required application.  Parameters 01-02~01-09 can not be modified (read only).  Six fixed V/f patterns are shown below.【1~3】for 50 Hz systems and【4~6】for 60 Hz.

 (V) 100% is the maximum output voltage. B, C point preset % settings will be as table below:-

 Setting 01-00 =[7] provides a flexible V/F curve which can be selected by experienced users by setting parameters (01-02~01-09).

Preset V/F curves and voltage percentages

01-V/F command group — PDF page 72

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-V/F command group 01-V/F command group
2 01- 00 Volts/Hz Patterns (V/F)
3 Range 【1~7】

01- 00 / Frame1/2 / Frame3/4 — PDF page 72

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 01- 00 Frame1/2 Frame1/2 Frame3/4 Frame3/4
2 01- 00 B(Xb) C(Xc) B(Xb) C(Xc)
3 1/4 10% 8% 6.8% 3.4%
4 2/5 12% 9.5% 6.9% 3.5%
5 3/6 25% 7.7% 40% 3.4%

Manual — Flexible V/F curve, boost and ramp parameters — page 73

Manual reference: Ver.02, January 2016, physical PDF page 73. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Max output frequency depends on parameter 01-00, for 01-00=【7】It can be set by parameter 01-02.  For 01-00 ≠【7】, the maximum output frequency depends on parameter 00-12, frequency upper limit.

 Inverter output V / F curve settings for points B, C can be adjusted by parameter 01-10 to improve the output torque.  Calculation of B, C point voltage: B point voltage = Xb × maximum output voltage, C point voltage = Xc × maximum output voltage (Xb, Xc see Page 4-26). When 01-10 = 0, the torque improvement is disabled.

Flexible V/F curve, boost and ramp parameters

01- 01 / v/f Maximum voltage — PDF page 73

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01- 01 v/f Maximum voltage
2 Range 200:【170.0~264.0】V 400:【323.0~528.0】V
3 01- 02 Maximum Frequency (base frequency)
4 Range 【1.40~ 599.00】Hz
5 01- 03 Maximum Frequency Voltage Ratio
6 Range 【0.0 ~ 100.0】%
7 01- 04 Medium Frequency 2
8 Range 【1.30~599.00】Hz
9 01- 05 Medium Frequency Voltage Ratio 2
10 Range 【0.0 ~ 100.0】%
11 01- 06 Medium Frequency 1
12 Range 【1.30~599.00】Hz
13 01- 07 Medium Frequency Voltage Ratio 1
14 Range 【0.0 ~ 100.0】%
15 01- 08 Minimum Frequency
16 Range 【1.30~599.00】Hz
17 01- 09 Minimum Frequency Voltage Ratio
18 Range 【0.0 ~ 100.0】%

01-10 / Volts/Hz Curve Modification (Torque Boost) — PDF page 73

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-10 Volts/Hz Curve Modification (Torque Boost)
2 Range 【0 ~ 10.0】%

Manual — Torque, slip and low-frequency compensation — page 74

Manual reference: Ver.02, January 2016, physical PDF page 74. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

VF Start Frequency is for occasion where Start Frequency higher than zero Hz is needed.

 In the situation of no power and no-load that damping is low, active and reactive energy fluctuations will greatly stimulate the inverter output current oscillations. Appropriately adjusting 01-12 can suppress oscillation by frequency gain. Compensation is based on the percentage of the load current corresponds to the motor rated current. The adjustment for 01-14 can be increased or decreased every time about 5% to 10%.

 In the situation of no power and no-load that damping is low, active and reactive energy fluctuations will greatly stimulate the inverter output current oscillations. Appropriately adjusting 01-12 can suppress oscillation by compensating V/F voltage command. Compensation is based on high-pass filtering and the load current value, then it is multiplied by the gain limiting, finally, it is added by the V / F output voltage. The adjustment for 01-14 can be increased or decreased every time about 5% to 10%.  01-13 filter coefficients corresponding filter time = 2048 / set point ms, such as 01-13 = 800, then filtering time = 2048/800 = 2.56ms.  01-15 of 100% corresponds to 150V (100,200V series) / 300V (400V series).

 Auto-torque Compensation function must be in SLV mode to auto tune so that inverter can get the value of stator resistor. Inverter Without Auto-Torque Compensation If 01-17=0. 01-17 compensation is based on V/F maximum output voltage and the load current, The adjustment for 01-14 can be increased or decreased every time about 5% to 10%.  Parameter 01-16~01-18 is for V/F mode only. SLV mode doesn’t need to adjust these parameter because auto-tune in SLV mode will get the value of motor parameter.

Torque, slip and low-frequency compensation

01-11 / V/F start Frequency — PDF page 74

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-11 V/F start Frequency
2 Range 【0.00 ~10.00】Hz

01-12 / No-load oscillation suppression gain — PDF page 74

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-12 No-load oscillation suppression gain
2 Range 【0.0~200.0】%

01-13 / Motor Hunting Prevention Coefficient — PDF page 74

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01-13 Motor Hunting Prevention Coefficient
2 Range 【1~8192】
3 01-14 Motor Hunting Prevention Gain
4 Range 【0~100】%
5 01-15 Motor Hunting Prevention Limit
6 Range 【0.0~100.0】%

01- 16 / Auto-Torque Compensation Filter Coefficient — PDF page 74

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 01- 16 Auto-Torque Compensation Filter Coefficient
2 Range 【0.1 ~ 1000.0】ms
3 01- 17 Auto-torque Compensation Gain
4 Range 【0~ 100】%
5 01- 18 Auto-torque Compensation Frequency
6 Range 【1.30 ~ 5.00】Hz

Manual — Compensation and motor slip formulas — page 75

Manual reference: Ver.02, January 2016, physical PDF page 75. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

02- Motor parameter group

 When the load causes the actual motor speed to be reduced below the speed set by inverter output frequency (Slip) , parameter 02-02 Slip compensation can be used to correct the speed. Slip compensation calculation in V/F mode:

※Note: Parameters 02- 00/02- 01 have to be set according to the specific motor data and in relation to the Inverter rating model parameter (13- 00).

Compensation and motor slip formulas

02- 00 / Motor no load current. (For slip compensation calculation) — PDF page 75

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 00 Motor no load current. (For slip compensation calculation)
2 Range ----
3 02- 01 Motor Rated Current
4 Range ----
5 02- 02 Slip Compensation Gain. (V/f mode only)
6 Range 【0.0 ~ 100.0】(%)

Manual — Motor parameters and autotune — page 76

Manual reference: Ver.02, January 2016, physical PDF page 76. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Slide compensation limit, inverter will calculate the motor slide according to 02-03. V/F slide compensation will not be higher than 02-03. Note: Please set the value according to motor’s nameplate.

 In order to prevent the output voltage of inverter is too high. The output voltage value will not be higher than 02-04. 02-04 can be changed during operation. Note: Please set the value according to motor’s nameplate.

 When inverter executes auto tuning function, Fmax value sets by 02-06 When inverter does not execute auto tuning function, Fmax value sets by 01-02

Auto tune function in SLV mode. 00-00=【1】  Set motor parameters 02-01 and 02-03~02-06,then set 02-07 to【1】to start the auto tune function.  During the Auto tune function the display will show AT and show END briefly when auto tune is completed then the display will return to the frequency display.  Following an auto tune the motor test data are stored in parameters 02-08&02-09 then the setting in 02-07 will automatically reset to 0. Notes:  Carry out Auto tune again whenever replacing the motor.  Auto tune function is not possible for applications with multi-motor connected to one inverter.  Auto tune can be used on motors of equivalent size to the inverter or one size smaller(or one size bigger). Just need to set the motor parameter and set 02-07 to be 1.  Parameters 02-00 ~ 02-06 are available both for V/F & SLV mode (Except parameter 02-02 which is for V/F).

SLV Slip compensation  When the load causes the actual motor speed to be reduced below the speed set by inverter

Motor parameters and autotune

02- 03 / Motor Rated Speed — PDF page 76

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 03 Motor Rated Speed
2 Range ----

02- 04 / Motor Rated Voltage — PDF page 76

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 04 Motor Rated Voltage
2 Range ----

02- 05 / Motor Rated Power — PDF page 76

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 05 Motor Rated Power
2 Range 【0~22.0】kW
3 02- 06 Motor Rated Frequency
4 Range 【0~599.0】Hz
5 02- 07 Motor Auto Tuning
6 Range 【0】: Disable 【1】: Static auto tuning

02- 08 / Stator Resistor Gain — PDF page 76

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 08 Stator Resistor Gain
2 Range ----
3 02- 09 Rotor Resistor Gain
4 Range ----

02- 13 / SLV Slip Compensation Gain — PDF page 76

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 13 SLV Slip Compensation Gain
2 Range 【0~200】%
3 02- 14 SLV Torque Compensation Gain
4 Range 【0~200】%

Manual — Slip compensation and motor parameter setting — page 77

Manual reference: Ver.02, January 2016, physical PDF page 77. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

output frequency (Slip), parameter 02-13 SLV Slip compensation can be used to correct the speed. SLV Torque compensation:  When torque is reduced due to load conditions, parameter 02-14 can be used to correct the torque. Torque producing current adjusted to compensate for the reduced torque.  02-13、02-14 compensation is based on the load current. The unit of 02-13 is based on rated slip frequency; The unit of 02-14 is based on rated torque difference.  The adjustment for 01-14 can be increased or decreased every time about 5% to 10%.

 Inverter of dead zone (IGBT on short) will lower the torque of output in the system, leading to lower motor efficiency. Setting 02-15 can not only reduce this situation but also increase torque of output in low frequency. Default setting is 50, means 50% voltage compensation. 100% of 02-15 according to output voltage that is less affected by dead zone.

 1. When output current <= 02-00 (Motor current without load) Slip compensation gain : = [ SLV slip compensation gain(02-13)]* [Normal Duty slip compensation gain (02-16)]  2. When output current > 02-00 (Motor current with load) Slip compensation gain: = [ SLV slip compensation gain(02-13)] * Slip compensation gain 1(as bellowed figure)

 Please refer the contents as parameter 02-13/02-14

 When output current lower or equal to 02-00(no load), the value of slip compensation will be equal to (02-13)(02-16)(slip compensation select 1)  When output current higher than 02-00(with load), the value of slip compensation will be equal to (02-13)(02-17)(slip compensation select 2) Note: If inverter worked at lower speed with load, please use slip compensation select 2

Slip compensation and motor parameter setting

02- 15 / Low Frequency Torque Gain — PDF page 77

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 15 Low Frequency Torque Gain
2 Range 【0~100】%

02- 16 / SLV Without Load Slip Compensation Gain — PDF page 77

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 16 SLV Without Load Slip Compensation Gain
2 Range 【0~200】%
3 02- 17 SLV With Load Slip Compensation Gain
4 Range 【0~200】%

02- 18 / SLV With Load Torque Compensation Gain — PDF page 77

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 18 SLV With Load Torque Compensation Gain
2 Range 【0~200】%

02- 19 / SLV Slip Compensation Select — PDF page 77

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 02- 19 SLV Slip Compensation Select
2 Range 0: Slip Compensation Select 1 1: Slip Compensation Select 2

Manual — Multifunction inputs and two-wire mode1 — page 78

Manual reference: Ver.02, January 2016, physical PDF page 78. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

03- External digital inputs & Relay Output functions

Various example settings and descriptions for Parameters 03-00 to 03-04 are noted in the following pages seconds from 1 to 13. 1) For setting parameters 03- 00~03- 04 to【0, 1】External Run/Stop Control, refer to 00- 04. 2-wire method. Mode 1. Example: FWD/STOP and REV/STOP from two inputs ( S1&S2) Set 00- 04=【0】, S1: 03- 00=【0】(FWD/STOP) , S2: 03- 01=【1】(REV/STOP);

Multifunction inputs and two-wire mode1

03- 00 / Multifunction Input Term. S1 — PDF page 78

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 00 Multifunction Input Term. S1
2 03- 01 Multifunction Input Term. S2
3 03- 02 Multifunction Input Term. S3
4 03- 03 Multifunction Input Term. S4
5 03- 04 Multifunction Input Term. S5
6 Range 【0】:Forward/Stop Command-----------------(Parameters 00- 02/00-03=1 & 00-04) 【1】:Reverse/Stop Command-----------------(Parameters 00-02/00-03=1 & 00-04) 【2】:Preset Speed 1 (5- 02)--------------------(Parameter Group5) 【3】:Preset Speed 2 (5- 03)--------------------(Parameter Group5) 【4】:Preset Speed 4 (5- 05) -------------------(Parameter Group5) 【6】:JOG Forward Command-----------------(Parameters 00-18~00-20) 【7】:JOG Reverse Command-----------------(Parameters 00-18~00-20) 【8】:Up Command------------------------------- (Parameters 00- 05/00- 06=4& 03-06/03-07) 【9】:Down Command--------------------------- (Parameters 00- 05/00- 06=4& 03-06/03-07) 【10】: 2nd Acc/Dec times 【11】: Disable Acc/Dec 【12】: Main/ Alternative run source Select-----------------(Parameters 00- 02/00- 03) 【13】: Main/Alternative Frequency Command Select----(Parameters 00- 05/00- 06) 【14】: Rapid Stop (controlled deceleration stop) 【15】: Base Block (Coast to stop) 【16】: Disable PID Function.------------------(Parameter Goup10) 【17】: Reset 【18】: Enable Auto Run Mode----------------(Parameter Group 6)

Manual — Preset speed truth table and input functions — page 80

Manual reference: Ver.02, January 2016, physical PDF page 80. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

3) 03- 00~03- 04=【6 ,7】Forward/ Reverse JOG When an input terminal is set to function【6】and is turned on, inverter will work in jog forward mode. When an input terminal is set to function【7】and is turned on, inverter will work in jog reverse mode. Note: If jog forward and jog reverse function is enabled at the same time, inverter will enter stop mode. 4) 03- 00~03- 04=【8, 9】UP/DOWN When an input terminal is set to function【8】and is turned on ,frequency command is increased according to the UP/DOWN , increment/decrement step set in parameter 03-06. If the input is kept on continuously, the frequency command increases accordingly until the upper frequency limit is reached. When an input terminal is set to function【9】and is turned on , frequency command decreases according to the UP/DOWN increment/decrement step set in parameter 03-06. If the input is kept on continuously, the frequency command decreases accordingly and in relation to settings for parameter 03-06 and 3-07 until Zero speed is reached. Refer to group 3 parameter description. 5) 03- 00~03- 04=【10】 2nd Acc/Dec time When an input terminal is set to function【10】and is turned on ,the actual acceleration and deceleration time will be according to the time for 2nd Accel/Decel set in parameters 00-16 and 00-17. if the input is turned off, the acceleration and deceleration times will be according to the default accel/decal 1 set in parameters 00-14 & 00-15. 6) 03- 00~03- 04=【11】 Disable Acc/Dec function When an input terminal is set to function【11】and is turned on, acceleration and deceleration function will be disabled and the frequency at the time is maintained. (constant speed mode) If the input is turned off, acceleration and deceleration function is enabled again. For an example see the following diagram. Accel/Decel & Enable/Disable timing diagram using terminal S1 and parameter 03-00 = 11.

Preset speed truth table and input functions

Preset speed / Function setting and state of any three (A,B,C) of terminal S1~S5 / Frequency / Acc-time / Dec-time — PDF page 80

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Preset speed Function setting and state of any three (A,B,C) of terminal S1~S5 Function setting and state of any three (A,B,C) of terminal S1~S5 Function setting and state of any three (A,B,C) of terminal S1~S5 Frequency Acc-time Dec-time
2 Preset speed terminal A=4 terminal B =3 terminal C =2 Frequency Acc-time Dec-time
3 speed 0 OFF OFF OFF 05- 01 05- 17 05-18
4 speed 1 OFF OFF ON 05- 02 05- 19 05-20
5 speed 2 OFF ON OFF 05- 03 05- 21 05-22
6 speed 3 OFF ON ON 05- 04 05- 23 05-24
7 speed 4 ON OFF OFF 05- 05 05- 25 05-26
8 speed 5 ON OFF ON 05- 06 05- 27 05-28
9 speed 6 ON ON OFF 05- 07 05- 29 05-30
10 speed 7 ON ON ON 05- 08 05- 31 05-32

Manual — Up/down increment and command behavior — page 82

Manual reference: Ver.02, January 2016, physical PDF page 82. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Example: S1: 03- 00=【8】Up frequency command, S2:03- 01=【9】Down frequency command, 03- 06=【△】Hz Mode1: If UP or DOWN input terminals are turned on for less than 2 seconds, for every On operation frequency changes by △ Hz.

Mode 2: If UP or DOWN input terminals are turned on for more than 2Seconds, the original

UP/DOWN mode is restored Output frequency Ramps up or down as long as the input is kept ON. As shown in the diagram below.

 03 - 07 =【0】,【2】When run signal is removed (Stop Command), the output frequency is stored in parameter 05-01( Key pad Frequency).  03 - 07 =【0】 In stop mode since frequency can not be increased or decreased from Up/Down terminals then keypad can be used to change the frequency by modifying parameter 05-01.  03 - 07 =【1】In Up/down frequency mode inverter will ramp up from 0Hz on Run command and Ramp down to 0 Hz on stop command.

Up/down increment and command behavior

03- 06 / Up/Down frequency step — PDF page 82

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 06 Up/Down frequency step
2 Range 【0.00~5.00】Hz

03- 07 / Up/Down keep Frequency status after a stop command — PDF page 82

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 07 Up/Down keep Frequency status after a stop command
2 Range 【0】: After a stop command in Up/Down mode, the preset frequency is held as the inverter stops, and the UP/Down function is disabled. 【1】: After a stop command in Up/Down mode, the preset frequency is reset to 0 Hz as the inverter stops. 【2】: After a stop command in Up/Down mode, the preset frequency is held as the inverter stops, and the UP/Down function remains enabled.

Manual — Scan time, input polarity and relay functions — page 83

Manual reference: Ver.02, January 2016, physical PDF page 83. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Multifunction input terminal On/Off periods will be scanned for the number of cycles according to the set value in parameter 03-08. If the signal status for On or off period is less than the set period it will be treated as noise.  Scan period unit is 1ms.  Use this parameter if unstable input signal is expected, however setting long scan time periods results in slower response times.

 (NO) Normally open, (NC) Normally closed. Select as required.  For selecting Normally Open (NO) or Normally Closed(NC) set the relevant digit in parameter 03-09 to 0 or 1 as required.  Set Parameter 03-09 first before you use the Parameters 00-02/00-03=1 to set the inverter run mode to External multifunction inputs.

Scan time, input polarity and relay functions

03- 08 / Multifunction terminals S1~S5 scan time — PDF page 83

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 08 Multifunction terminals S1~S5 scan time
2 Range 【1~200】 2ms

03- 09 / s1~s5 Input type selection NO & NC — PDF page 83

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 09 s1~s5 Input type selection NO & NC
2 Range 【xxxx0】:S1 NO 【xxxx1】:S1 NC 【xxx0x】:S2 NO 【xxx1x】:S2 NC 【xx0xx】:S3 NO 【xx1xx】:S3 NC 【x0xxx】:S4 NO 【x1xxx】:S4 NC 【0xxxx】:S5 NO 【1xxxx】:S5 NC

03-11 / Multifunction Output Relay RY1 functions. ( Terminals RB, RA ) — PDF page 83

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-11 Multifunction Output Relay RY1 functions. ( Terminals RB, RA )
2 Range 【0】:Run 【1】:Fault 【2】:Setting Frequency Reached ---------------------------( refer to 03-14) 【3】:Frequency Reached (3-13±3-14) ---------------------( refer to 03-13/03-14) 【4】:Output Frequency Detection 1 (> 03-13) ----------( refer to 03-13) 【5】:Output Frequency Detection 2 (< 03-13) ----------( refer to 03-13) 【6】:Auto-Restart 【7】:Momentary AC Power Loss----------------------------( refer to 07-00) 【8】:Rapid Stop (Decelerate to Stop) 【9】:Base Block 【10】:Motor Overload Protection (OL1) 【11】:Drive Overload Protection (OL2) 【12】:Reserved 【13】:Output Current Reached ----------------------------(refer to 03-15/03-16) 【14】:Brake Control--------------------------------------------(refer to 03-17/03-18) 【15】:PID Feedback Disconnection Detection --------(refer to 10-11/10-13)
3 03-13 Frequency Detection Level
4 Range 【0.00~599.00】 Hz
5 03-14 Frequency Detection Width
6 Range 【0.00~30.00】 Hz

Manual — Relay level and current detection timing — page 85

Manual reference: Ver.02, January 2016, physical PDF page 85. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

5) 03-11=【4】. RY1 will be on while Output Freq. > Frequency Detection Level (03-13).

6) 03-11=【5】. RY1 will be on while Output Freq. < Frequency Detection Level (03-13).

 03-11=【13】.RY1 will be on as soon as the output current value > Output current detection level (03-15).  03-15: Setting range (0.1~15.0 Amps) as required according to the rated motor current.  03-16: Setting range (0.1~10.0) unit: seconds.

Relay level and current detection timing

03-15 / Output Current Detection Level — PDF page 85

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-15 Output Current Detection Level
2 Range 【0.1~15.0】 A
3 03-16 Output Current Detection Period
4 Range 【0.1~10.0】Sec

Manual — External brake release and engage timing — page 86

Manual reference: Ver.02, January 2016, physical PDF page 86. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 If 03-11 =【14】  In accelerating mode. RY1 will be ON as soon as the actual output frequency reaches the external Brake release level set in parameter 03-17.  In decelerating mode, RY1 will be OFF as soon as the actual output frequency reaches the external Brake engage level set in parameter 03-18. Timing diagram for 03-17 < 03-18 is shown below:

Timing diagram for 03-17 > 03-18 is shown below:

External brake release and engage timing

03-17 / Brake Release Level — PDF page 86

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03-17 Brake Release Level
2 Range 【0.00~20.00】 Hz
3 03-18 Brake Engage Level
4 Range 【0.00~20.00】 Hz

Manual — Relay type, brake transistor and analog scaling — page 87

Manual reference: Ver.02, January 2016, physical PDF page 87. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

When DC bus voltage >03-20, Excess voltage will be applied to the external brake resistor. When DC bus voltage <= 03-21, Braking transistor will be switched off. Do not set 03-21 > 03-20, or display will show Err2, which means parameter setting error.

04- External analog signal input / output functions

 Analog Input Scaling formulas:-

Detailed04-00 table read in physical columns: AVI/ACI for choice0=0~10V/0~20mA;choice1=0~10V/4~20mA;choice2=2~10V/0~20mA;choice3=2~10V/4~20mA. Source index57 has reversed headings and is separately flagged.

Relay type, brake transistor and analog scaling

03- 19 / Relay Output Status type — PDF page 87

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 19 Relay Output Status type
2 Range 【0】:A (Normally open) 【1】:B (Normally close)

03- 20 / Brake Transistor ON Level — PDF page 87

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 03- 20 Brake Transistor ON Level
2 Range 100V/200V:【240.0~400.0】VDC 400V:【500.0~800.0】VDC
3 03- 21 Brake Transistor OFF Level
4 Range 100V/200V:【240.0~400.0】VDC 400V:【500.0~800.0】VDC

04- 00 / Analog Voltage & Current input s lections — PDF page 87

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04- 00 Analog Voltage & Current input s lections
2 Range AVI ACI 【0】:0~10V 0~20mA 【1】:0~10V 4~20mA 【2】:2~10V 0~20mA 【3】:2~10V 4~20mA

Manual — Analog input verification, gain and bias — page 88

Manual reference: Ver.02, January 2016, physical PDF page 88. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Set 04- 01 and 04- 06 for Analog signal verification. Inverter reads the average values of A/D signal once per (04- 01/04- 06 x 2ms). Set scan intervals according to the application and with consideration for signal instability or interference effects on the signal by external sources. Long scan times will result in slower response time. AVI. Analog Voltage input scaling examples by adjusting Gain, Bias & Slope parameters (04-02~04-05). (1) Positive Bias type (04-04= 0) and effects of modifying Bias amount by parameter 04-03 and Slope type with parameter 04-05 are shown in Fig 1&2. Figure 1. Figure 2.

Negative Bias type and effects of modifying Bias amount by parameter 04-03 and Slope type with parameter 04-05 are shown in Fig 3&4.

Analog input verification, gain and bias

04- 01 / AVI signal verification Scan Time — PDF page 88

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04- 01 AVI signal verification Scan Time
2 Range 【1~200】2ms
3 04- 02 AVI Gain
4 Range 【0 ~ 1000】%
5 04- 03 AVI Bias
6 Range 【0~ 100】%
7 04- 04 AVI Bias Selection
8 Range 【0】: Positive 【1】: Negative
9 04- 05 AVI Slope
10 Range 【0】: Positive 【1】: Negative
11 04- 06 ACI signal verification Scan Time
12 Range 【1~200】2ms
13 04- 07 ACIGain
14 Range 【0 ~ 1000】%
15 04- 08 ACI Bias
16 Range 【0 ~ 100】%
17 04- 09 ACI Bias Selection
18 Range 【0】: Positive 【1】: Negative
19 04-10 ACI Slope
20 Range 【0】: Positive 【1】: Negative

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 88

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 A 100% 50% 0 0
3 B 100% 0% 0 0

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 88

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 C 100% 50% 0 1
3 D 100% 0% 0 1

Manual — Analog scaling examples3–8 — page 89

Manual reference: Ver.02, January 2016, physical PDF page 89. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Figure3: Figure4:

(2) Offset bias set to 0% (04-03) and effect of modifying Analog Gain ( 04-02), Bias type ( 04-04) and slope type( 04-05) are shown in shown Fig 5&6. Figure 5 Figure 6

(3) Various other examples of analog input scaling and modification are shown in following figures 7,8,9 & 10. Figure7 Figure 8

Analog scaling examples3–8

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 89

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 E 100% 20% 1 0

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 89

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 F 100% 50% 1 1

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 89

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 A' 50% 0% 0/1 0
3 B' 200% 0% 0/1 0

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 89

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 C' 50% 0% 0/1 1
3 D' 200% 0% 0/1 1

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 89

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 a 50% 50% 0 0
3 b 200% 50% 0 0

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 89

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 c 50% 50% 0 1
3 d 200% 50% 0 1

Manual — Analog scaling examples9–10 and AO selection — page 90

Manual reference: Ver.02, January 2016, physical PDF page 90. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Figure 9 Figure 10

Example: Set 04-11 required according to the following table.

Analog scaling examples9–10 and AO selection

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 90

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 e 50% 20% 1 0
3 f 200% 20% 1 0

/ 04- 02 / 04- 03 / 04- 04 / 04- 05 — PDF page 90

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows)
1 ⟦blank source cell⟧ 04- 02 04- 03 04- 04 04- 05
2 g 50% 50% 1 1
3 h 200% 0% 0 1

04-11 / Analog Output (AO) function selection. — PDF page 90

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04-11 Analog Output (AO) function selection.
2 Range 【0】:Output frequency 【1】:Frequency Setting 【2】:Output voltage 【3】:DC Bus Voltage 【4】:Output current

04-11 / A / Xmax — PDF page 90

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 04-11 A Xmax
2 【0】 Output frequency upper frequency limit
3 【1】 Frequency Setting upper frequency limit
4 【2】 Output voltage Motor Rated Voltage
5 【3】 DC Bus Voltage 220V:0~400V 380V:0~800V
6 【4】 Output current 2 times rated current of inverter

Manual — AO scaling and preset speeds — page 91

Manual reference: Ver.02, January 2016, physical PDF page 91. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Select the Analog output type for the multifunction analog output on terminal (TM2) as required by parameter 04-11. Output format is 0-10V dc. The output voltage level can be scaled and modified by parameters 04-12 to 04-15 If necessary.  The modification format will be same as the examples shown previously for Analog Voltage Input (AVI) parameters 4-02 to 4-05. Note: the max output voltage is 10V due to the hardware of the circuit. Use external devices that require a maximum of 10V dc signal.

05- Preset Frequency Selections.

AO scaling and preset speeds

04-12 / AO Gain — PDF page 91

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 04-12 AO Gain
2 Range 【0 ~ 1000】%
3 04-13 AO Bias
4 Range 【0 ~ 100】%
5 04-14 AO Bias Selection
6 Range 【0】: Positive 【1】: Negative
7 04-15 AO Slope
8 Range 【0】: Positive 【1】: Negative

05- 00 / Preset Speed Control mode Selection — PDF page 91

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 05- 00 Preset Speed Control mode Selection
2 Range 【0】:Common Acceleration / Deceleration. 【1】: Individual Acceleration / Deceleration for each preset speed 0-7.

05- 01 / Preset Speed 0 (Keypad Freq) — PDF page 91

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 05- 01 Preset Speed 0 (Keypad Freq)
2 05- 02 Preset Speed 1
3 05- 03 Preset Speed 2
4 05- 04 Preset Speed 3
5 05- 05 Preset Speed 4
6 05- 06 Preset Speed 5
7 05- 07 Preset Speed 6
8 05- 08 Preset Speed 7
9 Range 【0.00 ~ 599.00】 Hz
10 05-17 Preset Speed 0 Acceleration time
11 05-18 Preset Speed 0 Deceleration time
12 05-19 Preset Speed 1 Acceleration time
13 05- 20 Preset Speed 1 Deceleration time
14 05- 21 Preset Speed 2 Acceleration time
15 05- 22 Preset Speed 2 Deceleration time
16 05- 23 Preset Speed 3 Acceleration time
17 05- 24 Preset Speed 3 Deceleration time
18 05- 25 Preset Speed 4 Acceleration time
19 05- 26 Preset Speed 4 Deceleration time
20 05- 27 Preset Speed 5 Acceleration time
21 05- 28 Preset Speed 5 Deceleration time

Manual — Preset speed acceleration formulas — page 92

Manual reference: Ver.02, January 2016, physical PDF page 92. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 When 05- 00 =【0】Acceleration /Deceleration 1 or 2 set by parameters 00-14/00-15 or 00-16/00-17 apply to all speeds.  When 05- 00 =【1】Individual Acceleration /Deceleration apply to each preset speed 0-7. Parameters 05-17 to 05-32.  Formula for calculating acceleration and deceleration time: V/F mode:

SLV mode:

 V/F Maximum output frequency = parameter 01-02 when programmable V/F is selected by 01- 00=【7】. Motor rated output frequency is set by parameter 02-06.  V/F Maximum output frequency = 50.00 hz or 60.00 hz when preset V/F patterns are selected. 01- 00≠【7】. Bellowing examples is in V/F mode:

 Multi speed run/stop cycles with Individual acceleration/deceleration time. 05-00=【1】  Two modes are shown below:-  Mode1 = On/Off run command  Mode2= Continuous run command Mode1 Example: 00- 02=【1】(External Run/Stop Control). 00- 04=【1】(Operation Mode:Run/stop-forward/reverse). S1: 03- 00=【0】(RUN/STOP ); S2: 03- 01=【1】(Forward/Reverse); S3: 03- 02=【2】(Preset speed 1); S4: 03- 03=【3】(Preset speed 2); S5: 03- 04=【4】(Preset speed 4);

Preset speed acceleration formulas Continuation of preset acceleration/deceleration times05-17..05-28onphysical91;range on92retained only asprinted.

05- 29 / Preset Speed 6 Acceleration time — PDF page 92

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 05- 29 Preset Speed 6 Acceleration time
2 05- 30 Preset Speed 6 Deceleration time
3 05- 31 Preset Speed 7 Acceleration time
4 05- 32 Preset Speed 7 Deceleration time
5 Range 【0.1 ~ 3600.0】s

Manual — Sequence timing formulas and auto run parameters — page 94

Manual reference: Ver.02, January 2016, physical PDF page 94. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Source limitation for this page: Malformed separator immediately following leading Ex in the formula graphic remains unidentified. All formula symbols, parameter references and units are transcribed; source image retained.

06- Auto Run(Auto Sequencer) function

Sequence timing formulas and auto run parameters

06- 00 / Auto Run( sequencer) mode selection — PDF page 94

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 06- 00 Auto Run( sequencer) mode selection
2 Range 【0】:Disabled 【1】:Single cycle, continues to run from the unfinished step if restarted. 【2】:Periodic cycle, continues to run from the unfinished step if restarted. 【3】:Single cycle, then holds the speed of final step to run. Continues to run from the unfinished step if restarted. 【4】:Single cycle, starts a new cycle if restarted. 【5】:Periodic cycle, starts a new cycle if restarted. 【6】:Single cycle, then hold the speed of final step to run, starts a new cycle if restarted.

Frequency of the step 0 is set by parameter 05-01 keypad Frequency. — PDF page 94

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Frequency of the step 0 is set by parameter 05-01 keypad Frequency. Frequency of the step 0 is set by parameter 05-01 keypad Frequency.
2 06- 01 Auto Run Mode Frequency Command 1
3 06- 02 Auto Run Mode Frequency Command 2
4 06- 03 Auto Run Mode Frequency Command 3
5 06- 04 Auto Run Mode Frequency Command 4
6 06- 05 Auto Run Mode Frequency Command 5
7 06- 06 Auto Run Mode Frequency Command 6
8 06- 07 Auto Run Mode Frequency Command 7
9 Range 【0.00 ~ 599.00】Hz

06- 16 / Auto Run Mode Running Time Setting0 — PDF page 94

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 06- 16 Auto Run Mode Running Time Setting0
2 06- 17 Auto Run Mode Running Time Setting1
3 06- 18 Auto Run Mode Running Time Setting2
4 06- 19 Auto Run Mode Running Time Setting3
5 06- 20 Auto Run Mode Running Time Setting4
6 06- 21 Auto Run Mode Running Time Setting5
7 06- 22 Auto Run Mode Running Time Setting6
8 06- 23 Auto Run Mode Running Time Setting7
9 Range 【0.00 ~ 3600.0】Sec

06- 32 / Auto Run Mode Running Direction0 — PDF page 94

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 06- 32 Auto Run Mode Running Direction0
2 06- 33 Auto Run Mode Running Direction1
3 06- 34 Auto Run Mode Running Direction2
4 06- 35 Auto Run Mode Running Direction3

Manual — Auto run single-cycle example — page 95

Manual reference: Ver.02, January 2016, physical PDF page 95. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Auto Run sequencer mode has to be enabled by using one of the multifunctional inputs S1 to S5 and setting the relevant parameter 03-00 to 03-04 to selection【18】.  Various Auto Run (sequencer) modes can be selected by parameter (06-00) as listed above.  7 Auto Run (sequencer) modes can be selected by parameters (06-01~06-39)  Auto Run frequency commands1 to 7 are set with Parameters (06-01 ~ 06-07),  Sequence run times are set with parameters (06-17 ~ 06-23)  FWD/REV Direction for each sequence can be set with parameters (06-33 ~ 06-39).  Auto sequence 0, frequency is set from keypad by parameter 05-01, sequence run time and direction are set by parameters 06-16 and 06-32. Auto RUN (Auto Sequencer) examples are shown in the following pages:- Example 1. Single Cycle (06- 00=1,4) The inverter will run for a single full cycle based on the specified number of sequences, then it will stop. In this example 4 sequences are set, three in forward direction and one in Reverse. Auto Run Mode. 06- 00=【1】or【4】, Frequency 05- 01=【15】Hz, 06- 01=【30】Hz, 06- 02=【50】Hz, 06- 03=【20】Hz Sequence Run Time 06-16=【20】s, 06-17 =【25】s, 06-18=【30】s, 06-19=【40】s, Direction 06-32=【1】FWD, 06-33 =【1】FWD, 06-34=【1】(FWD), 06-35=【2】(REV) Unused Sequence Parameters 06-04~ 06-07=【0】Hz , 06-20~06-23=【0】s , 06-36~06-39=【0】

Auto run single-cycle example Continuation of auto-run direction0..3onphysical94;choices on95retained asprinted.

06- 36 / Auto Run Mode Running Direction4 — PDF page 95

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 06- 36 Auto Run Mode Running Direction4
2 06- 37 Auto Run Mode Running Direction5
3 06- 38 Auto Run Mode Running Direction6
4 06- 39 Auto Run Mode Running Direction7
5 Range 【0】: STOP 【1】: Forward 【2】: Reverse

Manual — Restart sequence and power-loss restart — page 97

Manual reference: Ver.02, January 2016, physical PDF page 97. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Example 4&5 . Auto Run Mode 06-00=【1~3】. After a restart continues to run from the unfinished step. Auto Run Mode 06-00=【4~6】. After a restart, it will begin a new cycle.

 ACC/DEC time in Auto run mode will be according to the setting of 00-14/00-15 or 00-16/00-17.  For Auto sequence 0.The run frequency will be according to keypad frequency set by parameter 05-01.Parameters 06-16 and 06-32 are used to set the sequence Run time and Run direction.

 If the input power supply due to sudden increase in supply demand by other equipment results in voltage drops below the under voltage level, the inverter will stop its output at once.  When 07-00 =【0】.On power loss, the inverter will not start.  When 07-00 =【1】.Aafter a momentary power loss, inverter will restart with the same frequency before power loss, and there is no limitation on number of restarts.  On power loss, as long as the inverter CPU power is not completely lost, the momentary power loss restart will be effective, restart will be according to setting of parameters 00-02 & 07-04 and status of External run switch. Caution:- After any power loss if the Run mode is set to External by parameter 00-02=1 and if Direct start on power up is also selected by parameter 07-04=0, please note that the inverter will run on resumption of power. To ensure safety of operators and to avoid any damages to the machinery, all necessary safety measure must be considered, including disconnection of power to the inverter.

 07- 02=【0】: The inverter will not auto restart after trips due to fault.  07- 02>【0】, 07- 01=【0】.After a trip due to fault the inverter will run with the same frequency before power loss, and restarts after an internal delay of 0.5 seconds.  07- 02>【0】, 07- 01>【0】, After a fault trip the inverter will run with the same frequency before power loss, and restart with a delay according the preset in parameter 07-01.

Restart sequence and power-loss restart

07- Start/Stop command setup — PDF page 97

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- Start/Stop command setup 07- Start/Stop command setup
2 07- 00 Momentary power loss and restart
3 Range 【0】:Momentary Power Loss and Restart disable 【1】:Momentary power loss and restart enable

07- 01 / Auto Restart Delay Time — PDF page 97

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 01 Auto Restart Delay Time
2 Range 【0.0~800.0】Sec
3 07- 02 Number of Auto Restart Attempts
4 Range 【0~10】

Manual — Reset, direct run and DC braking — page 98

Manual reference: Ver.02, January 2016, physical PDF page 98. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Note:- Auto restart after a fault will not function while DC injection braking or decelerating to stop

 07-03=0 Once the inverter is detected a fault, please turn Run switch Off and then On again to perform reset, otherwise restarting will not be possible.

 When direct run on power up is selected by 07-04=0 and the inverter is set to external run by (00-02/00-03=1), if the run switch is ON as power is applied, the inverter will auto start. It is recommend that the power is turned off and the run switch is also off to avoid possibility of injury to operators and damage to machines as the power is reapplied. Note: If this mode is required all safety measures must be considered including warning labels.  When direct run on power up is disabled by 07-04=1and if the inverter is set to external run by (00-02/00-03=1), if the run switch is ON as power is applied, the inverter will not auto start and the display will flash with STP1. It will be necessary to turn OFF the run switch and then ON again to start normally.

 When DC Injection braking is active DC voltage is applied to the motor, increasing the braking current and resulting in an increase in the strength of the magnetic field trying to lock the motor shaft.  To enable DC injection braking during a stop operation set the DC injection braking current (07-07) and the DC injection braking time at stop (07-08) to a value greater than 0. Notes: - Increasing the DC braking time (07-08) can reduce the motor stop time - Increasing the DC braking current (07-07) can reduce the motor stop time. - During stop operation: If the DC braking start frequency < minimum output frequency (01-08), DC braking is activated when the output frequency reaches the minimum output frequency level.

 Frame 1/2 models, please refer the formula below. In V/F mode, the value is equal to 0~20% of max output voltage(01-01) In SLV mode, the value is equal to 0~20% of max output voltage(02-04)  Frame 3/4 models, the value is the equal to 0~100% of inverter rated output current.

Reset, direct run and DC braking

07- 03 / Reset Mode Setting — PDF page 98

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 03 Reset Mode Setting
2 Range 【0】:Enable Reset Only when Run Command is Off 【1】:Enable Reset when Run Command is On or Off

07- 04 / Direct Running on Power Up — PDF page 98

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 04 Direct Running on Power Up
2 Range 【0】:Enable Direct running after power up 【1】:Disable Direct running after power up
3 07- 05 Delay-ON Timer (Seconds)
4 Range 【1.0~300.0】Sec

07- 06 / DC Injection Brake Start Frequency (Hz) — PDF page 98

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 06 DC Injection Brake Start Frequency (Hz)
2 Range 【0.10 ~ 10.00】Hz

07- 07 / DC Injection Brake Level (%) — PDF page 98

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 07 DC Injection Brake Level (%)
2 Range 【0~ 20】 % (Frame1/2) Based on the 20% of maximum output voltage 【0~ 100】% (Frame3/4) Based on invertor rated current

Manual — DC brake timing and trip prevention — page 99

Manual reference: Ver.02, January 2016, physical PDF page 99. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 07- 08/07- 06 set the DC injection brake duration and the brake start frequency as shown below.

 07- 09 = 【0】: after receiving stop command, the motor will decelerate to stop according to setting of 00-15, deceleration time 1.  07- 09 = 【1】: after receiving stop command, the motor will free-run (Coast) to stop.

 Trip prevention adjustment level during acceleration to prevent over current (OC-A) trips.  If trip prevention during acceleration is enabled and an over current occurs due to the load, then the acceleration is interrupted until the over current level is dropped below the setting in 08-01 then the acceleration is resumed.

 Trip prevention adjustment level during deceleration to prevent over Voltage (OV-C) trips.  If trip prevention during deceleration is enabled and an over voltage occurs during stopping due to the load, then the deceleration is interrupted until the over voltage level is dropped below the setting in 08-02 then the deceleration is resumed.

DC brake timing and trip prevention

07- 08 / DC Injection Brake Time (Sec) — PDF page 99

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 08 DC Injection Brake Time (Sec)
2 Range 【0.0 ~ 25.5】Sec

07- 09 / Stopping Method — PDF page 99

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 07- 09 Stopping Method
2 Range 【0】:Deceleration to stop. 【1】:Coast to stop.

08- Protection function group — PDF page 99

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- Protection function group 08- Protection function group
2 08- 00 Trip Prevention Selection
3 Range 【xxxx0】:Enable Trip Prevention During Acceleration 【xxxx1】:Disable Trip Prevention During Acceleration 【xxx0x】:Enable Trip Prevention During Deceleration 【xxx1x】:Disable Trip Prevention During Deceleration 【xx0xx】:Enable Trip Prevention in Run Mode 【xx1xx】:Disable Trip Prevention in Run Mode 【x0xxx】:Enable over voltage Prevention in Run Mode 【x1xxx】:Disable over voltage Prevention in Run Mode

08- 01 / Trip Prevention Level During Acceleration — PDF page 99

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 01 Trip Prevention Level During Acceleration
2 Range 【50 ~ 200】%

08- 02 / Trip Prevention Level During Deceleration — PDF page 99

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 02 Trip Prevention Level During Deceleration
2 Range 【50 ~ 200】%

Manual — Overload protection — page 100

Manual reference: Ver.02, January 2016, physical PDF page 100. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Trip prevention adjustment level during continuous Run to prevent over current (OC-C) trips.  If trip prevention during continuous Run is enabled and an over current occurs due the load such as a sudden transient load, then the output frequency is reduced by decelerating to a lower speed until the over current level is dropped below the preset in 08-03, then the output frequency accelerates back to the normal running frequency.

 Over voltage prevention level can be set by parameter 08-04 when necessary. When the DC bus voltage is higher than 08-04, inverter will keep running, the output frequency will be decreased once the DC bus voltage reduced. It’s the over voltage prevention function, inverter will not appear any error message. (If the DC bus voltage higher than OV protection level, inverter will appear “OV” message)

Electronic Motor Overload Protection OL1 (08-05)  When more than one motor is connected to the inverter set the Overload protection level parameter 02-01 to the total current of all motors and provide external overload relay protection for each motor.  When using normal power supply switch, motor overload protection 08-05=xxx1x (hot start protection curve) . Because whenever power is turned off, value of heat will return to default setting.  08-05 = xx0xx. (Standard motor Overload protection). For standard motors with integrated cooling fan when running at low speeds the heat dissipation is not very effective, consider Force vent cooling then set parameter 08-05=xx1xx for the correct overload protection.  08-05 = xxxx1: Enable electronic overload protection for motor according to Setting in parameter 02-01(motor rated current).  Refer to the curve below as an example for overload protection for a standard motor. (08-05=xx0xx)

Overload protection

08- 03 / Trip Prevention Level during continuous Run Mode — PDF page 100

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 03 Trip Prevention Level during continuous Run Mode
2 Range 【50 ~ 200】%

08- 04 / Over voltage Prevention Level during Run Mode — PDF page 100

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 04 Over voltage Prevention Level during Run Mode
2 Range 200:【350~390】VDC 400:【700~780】VDC

08- 05 / Electronic Motor Overload Protection Operation Mode(OL1) — PDF page 100

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 05 Electronic Motor Overload Protection Operation Mode(OL1)
2 Range xxxx0: Disable Electronic Motor Overload Protection xxxx1: Enable Electronic Motor Overload Protection xxx0x: Motor Overload Cold Start xxx1x: Motor Overload Hot Start xx0xx: Standard Motor xx1xx: Invertor Duty Motor ( Force Vent)

Manual — Overload response, fan and AVR — page 101

Manual reference: Ver.02, January 2016, physical PDF page 101. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 08- 06 = 【0】: On overload condition the inverter coast to stop as the thermal relay detects the overload and the display will flash OL1.To reset Press the ‘Reset’ key or use an external reset to continue to run.  08- 06 = 【1】: On overload condition the inverter continues to run, display flash with OL1, until the current falls below the overload level.

 08- 07=【0】: Cooling fan runs as the inverter detects temperature rise.  08- 07=【1】: Cooling fan runs while the inverter is running.  08- 07=【2】: Cooling fan runs continuously.  08- 07=【3】: Cooling fan is Disabled.

 Automatic voltage regulator function provides a level of output voltage stability when there is input voltage instability. So when 08-08=0, Input voltage fluctuations will not effect the output voltage.  08-08=1, Input voltage fluctuations will cause fluctuations on output voltage.  08-08=2, AVR is disabled during stopping to avoid an increase in stopping time.  08-08=3, AVR is disabled only during deceleration from one speed to another speed. This will avoid longer than required deceleration time.  08-08=4, AVR function disabled for stop & Deceleration from one speed to another speed.  08-08=5, When VDC>360(200V series) or VDC>740V(400V series), AVR function is disabled for stop and deceleration

When 08-09=【1】:On phase loss warring message PF is displayed.

Overload response, fan and AVR

08- 06 / Operation After Overload Protection is Activated — PDF page 101

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 06 Operation After Overload Protection is Activated
2 Range 【0】:Coast-to-Stop After Overload Protection is Activated 【1】:Drive Will Not Trip when Overload Protection is Activated (OL1)

08- 07 / OH over heat Protection — PDF page 101

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 07 OH over heat Protection
2 Range 【0】:Auto (Depends on heat sink temp.) 【1】:Operate while in RUN mode 【2】:Always Run 【3】:Disabled

08- 08 / AVR function — PDF page 101

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 08 AVR function
2 Range 【0】:AVR function enable 【1】:AVR function disable 【2】:AVR function disable for stop 【3】:AVR function disable for Deceleration 【4】:AVR function disabled for stop & Deceleration from one speed to another speed. 【5】:when VDC>(360V/740V), AVR function is disabled for stop and deceleration

08- 09 / Input phase loss protection — PDF page 101

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 09 Input phase loss protection
2 Range 【0】:Disabled 【1】:Enabled

Manual — PTC motor overheat protection — page 102

Manual reference: Ver.02, January 2016, physical PDF page 102. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Selection for motor overheat protection: PTC (Positive temperature coefficient) sensors are used in motor windings to provide additional motor protection from overheat. PTC thermistor can be connected to terminals AVI and AGND. A voltage divider resistor R is necessary to be connected as shown below in figure (b). 1) If 08-10 =1 or 2 (Decelerate or Cost to stop on over temperature detection). When over temperature is detected by signal at terminal AVI increasing above the warning detection limit set in parameter 08-15 and the delay time set in parameter. 08-12 is reached, the display will show ”OH4”( motor over heat detection), then output frequency will decelerate or coast to stop according to the selection 1 or 2. 2) If 08-10 = 3 Continue running when warning level is reached.(08-15). Coast to stop when protection level is reached.(08-13).When over temperature is detected by signal at terminal AVI increasing above the Warning detection limit set in parameter 08-15, then the display will show “OH3”(motor over heat warning level) and the motor will continue to run. If temperature detected increases above the set limit in parameter 08-13 and for the delay time set in parameter 08-12 then the display will show “OH4” (motor over heat detection), and the motor will coast to stop. 3) Motor over heat detection “OH4” can be reset when the temperature detection level at terminal AVI becomes lower then the set level in parameter【08-14 PTC reset level】. 4) External PTC thermistor characteristics Diagram in figure (a) shows two curves for Class F and Class H temperatures. Tr = 150°C in class F, Tr = 180°C in class H. Tr - 5℃:RPTC≦ 550Ω, put value of RPTC into formula to calculate the value of V to be set in parameter【08-14 PTC reset level】。

PTC motor overheat protection

08- 10 / PTC Motor Overheat Function — PDF page 102

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 10 PTC Motor Overheat Function
2 Range 【0】: Disable 【1】: Decelerate to stop 【2】: Coast to stop 【3】: Continue running, when warning level is reached. Coast to stop, when protection level is reached.
3 08- 11 PTC Signal Smoothing Time
4 Range 【0.00 ~ 10.00】Sec
5 08- 12 PTC Detection Time Delay
6 Range 【1 ~ 300】Sec
7 08- 13 PTC Protection Level
8 Range 【0.1 ~ 10.0】V
9 08- 14 PTC Detection Level Reset
10 Range 【0.1 ~ 10.0】V
11 08- 15 PTC Warning Level
12 Range 【0.1 ~ 10.0】V

Manual — PTC formulas and communication settings — page 103

Manual reference: Ver.02, January 2016, physical PDF page 103. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Tr+ 5℃:RPTC≧1330Ω, put value of RPTC into formula to calculate, the value of V to be set in parameter【08-13 PTC protection level】。 5) For different specifications of PTC thermistor, set the values for parameters 08-13 and 08-14 by calculating from the formula shown below.

 When 08-07=【0】 ( Heat sink temperature detection control for cooling fan). Fan will run when temperature of heat sink is higher than 08-16; When temperature of heat sink decrease below ”setting value of 08-16 minus 20°C”, fan will stop.

09- Communication function group

 09-00 sets the communication station number when there are more than one unit on the communication network. Up to 32 Slave units can be controlled from one master controller such as a PLC.

PTC formulas and communication settings

08- 16 / Fan Control Temperature Level — PDF page 103

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 08- 16 Fan Control Temperature Level
2 Range 【10.0~50.0】°C

09- 00 / Assigned Communication Station Number — PDF page 103

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 00 Assigned Communication Station Number
2 Range 【1 ~ 32】

09- 01 / Communication Mode Select — PDF page 103

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 01 Communication Mode Select
2 Range 【0】:RTU 【1】:ASCII 【2】:BACnet
3 09- 02 Baud Rate Setting (bps)
4 Range 【0】:4800 【1】:9600 【2】:19200 【3】:38400

Manual — Communication formats and timeout — page 104

Manual reference: Ver.02, January 2016, physical PDF page 104. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 09-06 is against communication test messages. When a test message is not responded within the time specified by 09-06, Inverter will be stopped according to the setting of 09-07, and then appear “COT” on keypad display. Once the 09-06=0, inverter will not appear “time-out”.

 Time-out detection time: 00.0~25.5 seconds; setting 00.0 seconds: disables time-out function.

 09-08 is against real communication messages. When a real message does not pass error check, that message is resent. The number of errors for the same message are counted and accumulated and if it reaches the setting of 09-08, L510s will show Err6 and stop according to the setting of 07-09.

 This parameter is used to set the converter to receive data from the sending date to the beginning of the time.

Communication formats and timeout

09- 03 / Stop Bit Selection — PDF page 104

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 03 Stop Bit Selection
2 Range 【0】:1 stop bit 【1】:2 stop bit
3 09- 04 Parity Selection
4 Range 【0】:no parity 【1】:even parity 【2】:odd parity
5 09- 05 Data Format Selection
6 Range 【0】:8 bit data 【1】:7 bit data
7 09- 06 Communication time-out detection time
8 Range 【0.0~25.5】Sec

09- 07 / Communication time-out operation selection — PDF page 104

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 07 Communication time-out operation selection
2 Range 【0】:Stop in deceleration time 1 and show COT after communication timeout 【1】:Stop in free run mode and show COT after communication timeout 【2】:Stop in deceleration time 2 and show COT after communication timeout 【3】:Keep running and show COT after communication timeout

09- 08 / Err6 fault tolerance times — PDF page 104

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 08 Err6 fault tolerance times
2 Range 【1~20】

09- 09 / Drive Transmit Wait Time — PDF page 104

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 09 Drive Transmit Wait Time
2 Range 【5~65】2ms

09- 10 / BACnet stations — PDF page 104

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 09- 10 BACnet stations
2 Range 【1~254】

Manual — PID block diagram and selections — page 105

Manual reference: Ver.02, January 2016, physical PDF page 105. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

10-PID function Setup PID block diagram

 10-00 selections are only effective when frequency source selection is set to PID by parameters 00 - 05 \ 00 - 06= 6.

 !Note: 10-00 and 10-01 can not be set to the same value.

 10- 03 =【1】.

10-03 shared range cell visually read line by line:1FWDdeviationD,2FWDfeedbackD,3REVdeviationD,4REVfeedbackD,5FWDfrequencycommand+deviationD,6FWDfrequencycommand+feedbackD,7reversefrequencycommand+deviationD,8reversefrequencycommand+feedbackD. Independent parser orders the right-side parentheticals after all left-side labels; source row associations retained.

PID block diagram and selections

10- 00 / PID target value selection — PDF page 105

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 00 PID target value selection
2 Range 【0】:Potentiometer on Keypad 【1】:External AVI Analog Signal Input 【2】:External ACI Analog Signal Input 【3】:Target Frequency set by Communication method. 【4】:Set from keypad by parameter 10-02.

10- 01 / PID feedback value selection — PDF page 105

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 01 PID feedback value selection
2 Range 【0】:Potentiometer on Keypad 【1】:External AVI Analog Signal Input 【2】:External ACI Analog Signal Input 【3】:Communication setting Frequency

10- 02 / PID keypad input — PDF page 105

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 02 PID keypad input
2 Range 【0.0~100.0】%
3 10- 03 PID operation selection
4 Range 【0】: PID Function disabled 【1】: FWD Characteristic. (Deviation is D-controlled) 【2】: FWD Characteristic. (Feedback is D-controlled) 【3】: REV Characteristic. (Deviation is D-controlled) 【4】: REV Characteristic. (Feedback is D-controlled) 【5】:FWD Characteristic. (Frequency Command +Deviation D Control) 【6】:FWD Characteristic. (Frequency Command + Feedback D Control) 【7】:Reverse Characteristic. (Frequency Command + Deviation D Control) 【8】:Reverse Characteristic. (Frequency Command + Feedback D Control)

Manual — PID gains and feedback loss — page 106

Manual reference: Ver.02, January 2016, physical PDF page 106. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Ddeviation (target - detected value) is derivative controlled in unit time set in parameter 10-07.  10- 03 =【2】 Feedback (detected value) is derivative controlled in unit time set in parameter 10- 07.  10- 03 =【3】 Ddeviation (target value - detected value) is derivative controlled in unit time set in parameter 10- 07. If the deviation is positive, the output frequency decreases, vice versa.  10- 03 =【4】 Feed back (detected value) is derivative controlled in unit time set in parameter 10- 07. If the deviation is positive, the output frequency decreases, vice versa. Note: For 10-03 = 1 or 2, If the deviation is positive, the output frequency increases and, vice versa. For 10-03 = 3 or 4, If the deviation is positive, the output frequency decreases, vice versa.  When 10-03= 【5~8】, Output frequency = PID output frequency + frequency command (10- 03 = 【1~4】) .

 10-04 is the calibration gain. Deviation = set point – (feedback signal×10-04)

 10- 05: Proportion gain for P control.

 10- 06: Integration time for I control

 10- 07: Differential time for D control

 10- 08 /10- 09: Calculated PID output is offset by 10-09 (the polarity of offset is according to10-08)  10-10: Update time for output frequency.

PID gains and feedback loss

10- 04 / Feedback Gain coefficient — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 04 Feedback Gain coefficient
2 Range 【0.00 ~ 10.00】

10- 05 / Proportional Gain — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 05 Proportional Gain
2 Range 【0.0 ~ 10.0】

10- 06 / Integral Time — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 06 Integral Time
2 Range 【0.0 ~ 100.0】s

10- 07 / Derivative Time — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 07 Derivative Time
2 Range 【0.00 ~ 10.00】s

10- 08 / PID Offset — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10- 08 PID Offset
2 Range 【0】: Positive Direction 【1】: Negative Direction
3 10- 09 PID Offset Adjust
4 Range 【0 ~ 109】%

10-10 / PID Output Lag Filter Time — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-10 PID Output Lag Filter Time
2 Range 【0.0 ~ 2.5】s

10-11 / Feedback Loss Detection Mode — PDF page 106

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-11 Feedback Loss Detection Mode
2 Range 【0】: Disable 【1】: Drive keeps running After Feedback Loss 【2】: Drive Stops After Feedback Loss

Manual — PID integration and sleep settings — page 107

Manual reference: Ver.02, January 2016, physical PDF page 107. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 10-11= 【1】: On feed back loss detection, continue running, and display ‘PDER’;  10-11= 【2】: On feed back loss detection, stop, and display ‘PDER’。

 10-12 is the level for signal loss. Error = (Set point – Feedback value). When the error is larger than the loss level setting, the feedback signal is considered lost.

 10-13:The minimum time delay before feedback signal loss is determined.

 10-14: the Limiter to prevent the PID from saturating.

 10-15=0.As PID feedback value reaches the set point, the integral value will not be reset.  10-15=1~30.As PID feedback value reaches the set point, reset to 0 in 1~30 seconds and inverter stops. The inverter will run again when the feedback value differs from the set point value.

 10-16 = 0 ~ 100% unit value: Restart the tolerance after the integrator reset to 0.

 When PID output frequency is less than the sleep threshold frequency and exceeds the time of sleep delay, the inverter will decelerate to 0 and enters PID sleep mode.  When PID output frequency is larger than the Wake up threshold frequency inverter will enter the PID mode again as shown in the timing diagram below.

PID integration and sleep settings

10-12 / Feedback Loss Detection Level — PDF page 107

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-12 Feedback Loss Detection Level
2 Range 【0 ~ 100】

10-13 / Feedback Loss Detection Delay Time — PDF page 107

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-13 Feedback Loss Detection Delay Time
2 Range 【0.0 ~25.5】s

10-14 / Integration Limit Value — PDF page 107

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-14 Integration Limit Value
2 Range 【0 ~ 109】%

10-15 / Integration Value Resets to Zero when Feedback Signal Equals the target Value — PDF page 107

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-15 Integration Value Resets to Zero when Feedback Signal Equals the target Value
2 Range 【0】: Disabled 【1】: After 1 Sec 【30】: After 30 Sec ( Range:- 1 ~ 30 Sec)

10-16 / Allowable Integration Error Margin (Unit) (1 Unit = 1/8192) — PDF page 107

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-16 Allowable Integration Error Margin (Unit) (1 Unit = 1/8192)
2 Range 【0 ~ 100】%

10-17 / PID Sleep Frequency Level — PDF page 107

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-17 PID Sleep Frequency Level
2 Range 【0.00~599.00】Hz
3 10-18 PID Sleep Function Delay Time
4 Range 【0.0 ~25.5】s
5 10-19 PID Wake up frequency Level
6 Range 【0.00 ~ 599.00】Hz
7 10-20 PID Wake up function Delay Time
8 Range 【0.0 ~ 25.5】s

Manual — PID wakeup, display scaling and reverse — page 108

Manual reference: Ver.02, January 2016, physical PDF page 108. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Example: If 10-21=100 and 10-22=50 and the unit for the range from 0 to 999 will be defined with the parameters setting of 12-02 , actual feedback value variation range, will be scaled to 50 and 100 only for display, as Shown below.

11 Performance control functions

PID wakeup, display scaling and reverse

10-21 / Max PID Feedback Level. — PDF page 108

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 10-21 Max PID Feedback Level.
2 Range 【0 ~ 999】
3 10-22 Min PID Feedback Level.
4 Range 【0 ~ 999】

11- 00 / Prevention of Reverse operation — PDF page 108

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 00 Prevention of Reverse operation
2 Range 【0】:Reverse command is valid 【1】:Reverse command is invalid

11- 01 / Carrier Frequency — PDF page 108

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 01 Carrier Frequency
2 Range 【1~16】KHz

Manual — PWM modes and thermal carrier reduction — page 109

Manual reference: Ver.02, January 2016, physical PDF page 109. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

The function can be used for audible noise reduction from a motor. It can be used in cases where the 100% torque from motor is not critical but it is necessary to reduce the audible noise.  Mode 0: 3‐phase PWM Modulation. Three Output transistors are ON at the same time (Full Duty).Carrier frequency is set according to Parameter 11-01  Mode 1: 2‐phase PWM Modulation. Two output transistors are ON at the same time (2/3 Duty). This mode is suitable for variable torque applications such as Fan & pump. It reduces the output transistor switching losses. Carrier frequency will be according to parameter 11‐01 with the exception noted below: Note: If 11‐01 > 2KHz and 11‐03=0 ( Auto carrier frequency change is disabled) and the listed conditions below apply then 2‐phase PWM will automatically change to 3‐ phase PWM with The carrier frequency = 2/3 (11‐01) Conditions:  During Acceleration If Output frequency is < 0.7Fmax.  During Deceleration when output frequency is < 0.6*Fmax  Fmax = (01‐02) In V/f control mode (00‐00) = 0  Fmax = (02‐06) In SLV mode (00‐00) = 1  Mode 2: Mode 2: 2‐phase soft PWM modulation (Random PWM Modulation).

This modulation method will use 3‐phase PWM and 2‐phase PWM modulation in a random combination. Carrier frequency will be according to parameter 11‐01 PWM mode selection considerations:

 If inverter (heat sink) temperature rises above 80°C the carrier frequency is reduced by 4K.  If the temperature falls below less than 70°C, carrier frequency is restore to the value of 11-01.  Temperature can be displayed by setting parameter 12-00=04000.

PWM modes and thermal carrier reduction

11- 02 / Carrier mode selection — PDF page 109

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 02 Carrier mode selection
2 Range 【0】:Carrier mode0 3-phase PWM modulation 【1】:Carrier mode1 2-phase PWM modulation 【2】:Carrier mode2 random PWM modulation

Modes / Name / IGBT Duty / Heat Losses / Torque Performance / Waveform Distortion / Motor Noise — PDF page 109

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Modes Name IGBT Duty Heat Losses Torque Performance Waveform Distortion Motor Noise
2 0 3-Phase PWM 100% High High Low Low
3 1 2-Phase PWM 66.6% Low Low High High
4 2 2-Phase Random PWM 66.6% Low Low High Mid

11- 03 / Carrier Frequency auto reduction due to temperature rise — PDF page 109

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 03 Carrier Frequency auto reduction due to temperature rise
2 Range 【0】:Disable 【1】:Enable

Manual — Thermal carrier graph and S-curves — page 110

Manual reference: Ver.02, January 2016, physical PDF page 110. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Use S Curve parameters where a smooth acceleration or deceleration action is required, this will prevent possible damage to driven machines by sudden acceleration/deceleration.

Note:  Regardless of the stall prevention period, actual acceleration and deceleration time =preset acceleration / deceleration time + S curve time.  Please set the required individual S curve times in the parameters (11-04~11-07).  When S curve time (11-04~11-07) is set as 0, the S curve function is disabled.  The calculation of S curve time is based on the Maximum output frequency of motor (01-02), Please refer to the parameters (00-14/00-15/00-16/00-17).

Thermal carrier graph and S-curves

11- 04 / S-Curve Acc 1 — PDF page 110

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 04 S-Curve Acc 1
2 11- 05 S-Curve Acc 2
3 11- 06 S-Curve Dec 3
4 11- 07 S-Curve Dec 4
5 Range 【0.0 ~ 4.0】s

11- 08 / Skip frequency 1 — PDF page 110

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11- 08 Skip frequency 1
2 11- 09 Skip frequency 2
3 11-10 Skip frequency 3
4 Range 【0.00 ~ 599.00】Hz
5 11-11 Skip frequency range. (± frequency band)
6 Range 【0.00 ~ 30.00】Hz

Manual — Skip frequency and regeneration examples — page 111

Manual reference: Ver.02, January 2016, physical PDF page 111. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Skip frequency parameters can be used to avoid mechanical resonance in certain applications. Example: 11-08=10.00(Hz); 11-09=20.00(Hz); 11-10=30.00(Hz); 11-11=2.00(Hz).

 Regeneration Prevention Function: During excessive energy regeneration, the Vpn (DC bus) voltage will Increase and lead to OV (over voltage), to avoid over voltage due to regeneration the output frequency will be increased.. Regeneration prevention function can be set according to the selections above. Example: Regeneration prevention during acceleration.

Example: Regeneration prevention during constant speed.

Skip frequency and regeneration examples

11-11 11-10 11-09 11-08 — PDF page 111

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-11 11-10 11-09 11-08 11-11 11-10 11-09 11-08
2 11-13 Regeneration Prevention Function
3 Range 【0】: Regeneration prevention function is disabled 【1】: Regeneration prevention function is enabled 【2】: Regeneration prevention function is enabled only during constant speed

Manual — Regeneration prevention and speed-loop gains — page 112

Manual reference: Ver.02, January 2016, physical PDF page 112. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Example: Regeneration prevention during deceleration.

 Regeneration prevention voltage level: if the DC bus voltage level is set too low, then over-voltage protection will not be reached, but the actual deceleration time will be extended.

 Sets the regeneration prevention frequency limit.

 11-16/11-17 represent the effect for regeneration prevention. It will enhance the response of DC bus voltage variation by enlarging the setting. However, it will lead to instability of output frequency.  If setting 11-16 to be smaller still can’t suppress the shake, please set 11-17 to be smaller.

 SLV control mode use a output speed estimator as speed feedback value. Speed control system to adjust the output frequency to follow the value of speed feedback command. The output torque command is by the controller output with a limiter.

Regeneration prevention and speed-loop gains

11-14 / Regeneration Prevention Voltage Level — PDF page 112

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-14 Regeneration Prevention Voltage Level
2 Range 200v: 300.0~400.0 V 400v: 600.0~800.0 V

11-15 / Regeneration Prevention Frequency Limit — PDF page 112

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-15 Regeneration Prevention Frequency Limit
2 Range 【0.00~15.00】Hz

11-16 / Regeneration Prevention Voltage Gain — PDF page 112

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-16 Regeneration Prevention Voltage Gain
2 Range 【0~200】%
3 11-17 Regeneration Prevention Frequency Gain
4 Range 【0~200】%

11-18 / Speed loop proportion gain — PDF page 112

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 11-18 Speed loop proportion gain
2 Range 【0~65535】
3 11-19 Speed loop integration gain
4 Range 【0~65535】
5 11-20 Speed loop differential gain
6 Range 【0~65535】

Manual — Speed-loop block diagram and monitor modes — page 113

Manual reference: Ver.02, January 2016, physical PDF page 113. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

12 Monitor function group

 MSD= Most significant digit. LSD= Least significant digit.  Note: MSD of parameter 12-00 sets the power on display, other digits set user selected displays. (refer to P4-4)

 Set motor rated RPM in this parameter if required then the display will show this value when inverter output frequency reaches the motor name plate frequency. 50Hz or 60 Hz as appropriate.  The line speed display is linearly proportional to the output frequency 0 to 50Hz or 0-60 Hz as appropriate. Motor synchronous speed = 120 x Rated frequency/Number of poles.

12-00 digit illustration hasMSDonleft andLSDonright. Native table retains that visible order; independent parser emittedLSDbeforeMSD. No value change.

Speed-loop block diagram and monitor modes

12- 00 / Display Mode — PDF page 113

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 00 Display Mode
2 Range 0 0 0 0 0 MSD LSD 00000~77777 Each digit can be set from 0 to 7 as listed below. 【0】:Disable display 【1】:Output Current 【2】:Output Voltage 【3】:DC voltage 【4】:Heat Sink Temperature 【5】:PID feedback 【6】:AVI 【7】:ACI

12- 01 / PID Feedback Display Mode — PDF page 113

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 01 PID Feedback Display Mode
2 Range 【0】:Displayed in Integer (xxx) 【1】:Displayed with One Decimal Place (xx.x) 【2】:Displayed with Two Decimal Places (x.xx)
3 12- 02 PID Feedback Display Unit Setting
4 Range 【0】:----- 【1】:xxxpb(pressure) 【2】:xxxfl(flow)

12- 03 / Custom Units (Line Speed) Display Mode — PDF page 113

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 03 Custom Units (Line Speed) Display Mode
2 Range 【0~65535】rpm

Manual — Monitor I/O and horsepower codes — page 114

Manual reference: Ver.02, January 2016, physical PDF page 114. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 12- 04≠0, line speed is displayed while the inverter is running or stopped.

 When any of S1~S5 is turned on, corresponding segments on the digital display will be on.  When relay output RY1 is on, the corresponding digit will be on as shown below.  When no Digital input and no relay output, they will show - - - - - . Example 1: The following figure shows 12 - 05 display status, when S1, S3, S5 Inputs are ON and S2, S4 and RY1 are OFF.

Example 2: The following figure shows 12 - 05 display status when S2, S3, S4 inputs are ON and S1, S5 are OFF but RY1 is ON.

13 Inspection & Maintenance functions

Monitor I/O and horsepower codes

12- 04 / Custom Units (Line Speed) Display Mode — PDF page 114

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 04 Custom Units (Line Speed) Display Mode
2 Range 【0】:Drive Output Frequency is Displayed 【1】:Line Speed is Displayed in Integer (xxxxx) 【2】:Line Speed is Displayed with One Decimal Place (xxxx.x) 【3】:Line Speed is Displayed with Two Decimal Places (xxx.xx) 【4】:Line Speed is Displayed with Three Decimal Places (xx.xxx)

12- 05 / Input and output terminal status display — PDF page 114

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 12- 05 Input and output terminal status display
2 Range Read only(Panel read only)

13- 00 / Drive Horsepower Code — PDF page 114

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 00 Drive Horsepower Code
2 Range ----

Inverter Model: / 13- 00 show — PDF page 114

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Inverter Model: 13- 00 show Inverter Model: 13- 00 show Inverter Model: 13- 00 show
2 L510-1P2-SXX 1P2 L510-2P2-SXX 2P2 L510-401-SXX 401
3 L510-1P5-SXX 1P5 L510-2P5-SXX 2P5 L510-402-SXX 402
4 L510-101-SXX 101 L510-2P7-SXX 2P7 L510-403-SXX 403
5 ⟦blank source cell⟧ ⟦blank source cell⟧ L510-201-SXX 201 L510-405-SXX 405
6 ⟦blank source cell⟧ ⟦blank source cell⟧ L510-202-SXX 202 L510-408-SXX 408
7 ⟦blank source cell⟧ ⟦blank source cell⟧ L510-203-SXX 203 L510-410-SXX 410
8 ⟦blank source cell⟧ ⟦blank source cell⟧ L510-205-SXX 205 L510-415-SXX 415
9 ⟦blank source cell⟧ ⟦blank source cell⟧ L510-208-SXX 208 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ L510-210-SXX 210 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Software versions, lock and password setup — page 115

Manual reference: Ver.02, January 2016, physical PDF page 115. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

 Last three faults are stored in a stack and whenever there is a new fault the previous faults are pushed down the stack. So the fault stored in 2.xxx will be transferred to 3.xxx, and the one in 1.xxx to 2.xxx. The recent fault will be stored in the empty register 1.xxx.  Use Up▲and Down▼ keys to scroll between the fault registers.  Pressing reset key when parameter 13-02 is displayed then all three fault registers will be cleared and the display for each register will change to 1. ---, 2. ---, 3. ---.  E.g. fault log content is ‘1.OC-C’; this indicates the latest fault is OC-C, etc.

 When the operation time recorded in accumulator 1(Parameter 13-03) reaches 24 hours  The recorded value in accumulator 2 parameter 13-04 changes to 1 day and the value in accumulator 1 is reset to 0000.

 When the 13-07=00000 (not set a password), you can adjust the parameters 05-01~05-08 from 13-06.

 When a parameter lock key number is entered in parameter 13-07. For any parameter modification the key number has to be entered. See following Parameter lock key setting example:-  Setting Parameter lock key number example:- Step1:

Software versions, lock and password setup

13- 01 / Software Version — PDF page 115

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 01 Software Version
2 Range ----

13- 02 / Fault Log Display (Latest 3 faults) — PDF page 115

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 02 Fault Log Display (Latest 3 faults)
2 Range ----

13- 03 / Accumulated Inverter Operation Time 1 — PDF page 115

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 03 Accumulated Inverter Operation Time 1
2 Range 【0~23】Hours
3 13- 04 Accumulated Inverter Operation Time 2
4 Range 【0~65535】Days
5 13- 05 Accumulated Inverter Operation Time Mode
6 Range 【0】:Power on time 【1】:Operation time

13- 06 / Parameter lock — PDF page 115

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 06 Parameter lock
2 Range 【0】: Enable all Functions 【1】: Preset speeds 05- 01~05- 08 cannot be changed 【2】: All Functions cannot be changed Except for preset speeds set in 05-01~05- 08 【3】: Disable All Function Except 13-06

13- 07 / Parameter Lock Key Code — PDF page 115

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 07 Parameter Lock Key Code
2 Range 【00000~65535】

Manual — Password confirmation and factory reset — page 116

Manual reference: Ver.02, January 2016, physical PDF page 116. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Step2:

Key code ( password) unlock

 When a Parameter lock key number has been entered in parameter 13 – 07. This key number must be entered first before parameter 13-08 can be used.  Reset 13-08 to default setting will reset parameter 02 group.  For built-in EMC filter models, the default setting of 13-08 is “1250”. For without built-in EMC filter models, the default setting of 13-08 is “1360”

Password confirmation and factory reset

13- 08 / Reset Drive to Factory Settings — PDF page 116

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 13- 08 Reset Drive to Factory Settings
2 Range 【1150】: Initialization (50Hz,220V/380V system) 【1160】: Initialization (60Hz,220V/380V system) 【1250】: Initialization (50Hz,230V/400V system) 【1260】: Initialization (60Hz,230V/460V system) 【1350】: Initialization (50Hz,220V/415V system) 【1360】: Initialization (60Hz,230V/400V system)

Manual — Unrecoverable fault table — page 117

Manual reference: Ver.02, January 2016, physical PDF page 117. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Chapter 5 Troubleshooting and maintenance 5.1 Error display and corrective action 5.1.1 Manual Reset and Auto-Reset

Unrecoverable fault table

Faults which cannot be recovered manually — PDF page 117

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Faults which cannot be recovered manually Faults which cannot be recovered manually Faults which cannot be recovered manually Faults which cannot be recovered manually
2 Display content Cause Corrective action
3 -OV- Voltage too high when stopped Detection circuit malfunction Consult with the supplier
4 -LV- Voltage too low when stopped 1. Power voltage too low 2. Pre-charge resistor or fuse burnt out. 3. Detection circuit malfunction 1. Check if the power voltage is correct 2. failed resistor or fuse 3. Consult with the supplier
5 -OH- The inverter is overheated when stopped 1. Detection circuit malfunction 2. Ambient temperature too high or bad ventilation Improve the ventilation conditions, if no result then replace the inverter
6 OH-C The inverter is overheated during running 1. IGBT temperature is too high or poor ventilation 2. temperature sensor error or circuit malfunctions 1. Reduce carrier frequency 2. Improve the ventilation conditions, if no result then replace the inverter
7 CtEr Current Sensor detection error Current sensor error or circuit malfunction Consult with the supplier
8 HPErr Inverter capacity setting error: Inverter capacity setting 13-00 does not match the rated voltage. The inverter capacity setting (13-00) does not match the hardware voltage levels Check the inverter capacity setting (13-00) to meet the hardware voltage levels.
9 Err4 CPU Unusual interruption External noise interference 1. Remove the interference source then restart by switching power OFF/ON 2. If not resolved then Consult with the supplier
10 EPr EEPROM problem Faulty EEPROM Consult with the supplier
11 COt Communication error Communications disruption Check the wiring

Manual — Recoverable/manual fault tables — page 118

Manual reference: Ver.02, January 2016, physical PDF page 118. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Recoverable/manual fault tables

Faults which can be recovered manually and automatically — PDF page 118

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Faults which can be recovered manually and automatically Faults which can be recovered manually and automatically Faults which can be recovered manually and automatically Faults which can be recovered manually and automatically
2 Display content Cause Corrective action
3 OC-A Over-current at acceleration 1.Acceleration time too short 2.The capacity of the motor exceeds the capacity of the inverter 3.Short circuit between the motor coil and the case 4.Short circuit between motor wiring and ground 5.IGBT module damaged 1.Set a longer acceleration time 2.Replace inverter with one that has the same rating as that of the motor 3.Check the motor 4.Check the wiring 5.Consult with the supplier
4 OC-C Over-current at fixed speed 1. Transient load change 2. Transient power change 1.Increase the capacity of the inverter 2.Install inductor on the power supply input side
5 OC-d Over-current at deceleration The preset deceleration time is too short. Set a longer deceleration time
6 OC-S Over current at start 1.Short circuit between the motor coil and the case 2.Short circuit between motor coil and ground 3.IGBT module damaged 1.Inspect the motor 2.Inspect the wiring 3.Consult with the supplier
7 OV-C Excessive Voltage during operation/ deceleration 1.Deceleration time setting too short or excessive load inertia 2.Power voltage varies widely (fluctuates) 1.Set a longer deceleration time 2.Consider use of a brake resistor and/or brake module (For 400V models or 200V 5hp~15hp models) 3.Consider use of a reactor at the power input side
8 PF Input phase Loss Abnormal fluctuations in the main circuit voltage 1.Check the main circuit power supply wiring. 2.Check the power supply voltage

Faults which can be recovered manually but not automatically — PDF page 118

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Faults which can be recovered manually but not automatically Faults which can be recovered manually but not automatically Faults which can be recovered manually but not automatically Faults which can be recovered manually but not automatically
2 Display content Cause Corrective action
3 OC Over-current during stop Detection circuit malfunction Consult with the supplier
4 OL1 Motor overload loading too large Consider increasing the Motor capacity
5 OL2 Inverter overload Excessive Load Consider increasing the inverter capacity

Manual — Manual fault and overheat table — page 119

Manual reference: Ver.02, January 2016, physical PDF page 119. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Manual fault and overheat table

Faults which can be recovered manually but not automatically — PDF page 119

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Faults which can be recovered manually but not automatically Faults which can be recovered manually but not automatically Faults which can be recovered manually but not automatically Faults which can be recovered manually but not automatically
2 Display content Cause Corrective action
3 CL Inverter over current: Wait 1 minute to reset .If it occurs CL or OL2 up to 4 successive times then wait 5 mins to reset inverter over current warning: inverter current reach the level of over current protection Check load condition and running period time.
4 LV-C Voltage too low during operation 1.Power voltage too low 2.Power voltage varies widely (fluctuates) 1.Improve power quality 2.Consider adding a reactor at the power input side
5 OVSP motor rotation over speed The actual rotation speed is different to the set speed. 1.Check for excessive load 2.Check weather frequency setting signal is right or not
6 OH4 motor over heat error 1.If temperature detected increases above the set limit in parameter 08-13 and for the delay time set in parameter 08-12 then the display will show “OH4” (motor over heat detection), and the motor will coast to stop. 2.Motor over heat detection “OH4” can be reset when the temperature detection level is lower than the set level in parameter【08-14 PTC reset level】. 1.To improve the ventilation condition 2. Adjust parameter 08-15

Manual — Keypad operation errors — page 120

Manual reference: Ver.02, January 2016, physical PDF page 120. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

5.1.2 Keypad Operation Error Instruction

Keypad operation errors

Display / content / Cause / Corrective action — PDF page 120

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Display content Cause Corrective action
2 LOC 1.Parameter already locked 2.Motor direction locked 3.Parameter password (13-07) enabled 1.Attempt to modify frequency parameter while 13-06>0. 2.Attempt to reverse direction when 11- 00=1. 3.Parameter (13 - 07) enabled, set the correct password will show LOC. 1.Adjust 13-06 2.Adjust 11-00
3 Err1 Keypad operation error 1.Press ▲ or ▼while 00-05/00-06 > 0 or running at preset speed. 2.Attempt to modify the parameter. can not be modified during operation (refer to the parameter list) 1.The ▲ or▼ is available for modifying the parameter only when 00-05/00-06=0 2.Modify the parameter in STOP mode.
4 Err2 Parameter setting error 1. 00-13 is within the range of (11-08 ±11-11) OR (11-09 ±11-11) OR (11-10 ±11-11) 2. 00-12 ≦ 00-13 3. 00-05/00-06 or 10-00/10-01 set the same value 4. Modifying parameters 01-01 to 01-09 when 01-00≠7. 5. a.If this parameter is parameterized for both functions (AVI/PTC) at the same time. b.PTC function is enabled by setting 08-10≠0; 6. Parameter password (13-07) set incorrect 1.modify 11-08~11-10 or 11-11 2.00-12>00-13 3.set 00-05 / 00-06 or 10-00 / 10-01 to be different value 4.set 01-00=7 5.PTC function source can not be the same as frequency source or PID command via AVI. 6.Please set correct password
5 Err5 Modification of parameter is not available in communication 1.Control command sent during communication. 2.Attempt to modify the function 09-02~ 09-05 during communication 1.Issue enable command before communication 2.Set parameters 09-02~ 09-05 function before communication
6 Err6 Communication failed 1.Wiring error 2.Communication Parameter setting error. 3.Incorrect communication protocol 1. Check hardware and wiring 2.Check Functions(09-00~ 09- 05).
7 Err7 Parameter conflict 1.Attempt to modify the function 13-00/13-08. 2. Voltage and current detection circuit is abnormal. If reset is not possible, please consult with the supplier.

Manual — Special operating conditions — page 121

Manual reference: Ver.02, January 2016, physical PDF page 121. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

5.1.3 Special conditions

Special operating conditions

Display / Fault / Description — PDF page 121

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Display Fault Description
2 StP0 Zero speed at stop In V/f mode, STP0 comes out at less than 1.3Hz (50Hz set) or at less than 1.5Hz (60Hz set) In SLV mode, STP0 comes out at less than 1Hz
3 StP1 Fail to start directly On power up. 1. If the inverter is set for external terminal control mode (00-02/00-03=1) and direct start is disabled (07-04=1) 2. The inverter cannot be started and will flash STP1. 3. The run input is active at power-up, refer to descriptions of (07-04).
4 StP2 Keypad Stop Operated when inverter in external Control mode. 1. If the Stop key is pressed while the inverter is set to external control mode (00-02/00-03=1) then‘STP2’flashes after stop. 2. Release and re-activate the run contact to restart the inverter.
5 E.S. External Rapid stop When external rapid stop input is activated the inverter will decelerate to stop and the display will flash with E.S. message.
6 b.b. External base block When external base block input is activated the inverter stops immediately and then the display will flash with b.b. message.
7 PdEr PID feedback loss PID feedback loss is detected.
8 Alter auto tuning error other errors show up in the process of auto tuning.
9 OH3 motor over heat warning If 08-10 = 3,When over temperature is detected by signal at terminal AVI increasing above the warning detection limit set in parameter 08-15, then the display will show “OH3”(motor over heat warning level) and the motor will continue to run.

Manual — General troubleshooting — page 122

Manual reference: Ver.02, January 2016, physical PDF page 122. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

5.2 General troubleshooting

General troubleshooting

Status / Checking point / Remedy — PDF page 122

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Status Checking point Remedy
2 Motor runs in wrong direction Is the wiring for the output terminals correct? Wiring must match U, V, and W terminals of the motor.
3 Motor runs in wrong direction Is the wiring for forward and reverse signals correct? Check for correct wiring.
4 The motor speed can not be regulated. Is the wiring for the analog frequency inputs correct? Check for correct wiring.
5 The motor speed can not be regulated. Is the setting of operation mode correct? Check the Frequency Source set in parameters 00-05/00-06.
6 The motor speed can not be regulated. Is the load too excessive? Reduce the load.
7 Motor running speed too high or too low Check the motor specifications (poles, voltage…) correct? Confirm the motor specifications.
8 Motor running speed too high or too low Is the gear ratio correct? Confirm the gear ratio.
9 Motor running speed too high or too low Is the setting of the highest output frequency correct? Confirm the highest output frequency
10 Motor speed varies unusually Is the load too excessive? Reduce the load.
11 Motor speed varies unusually Does the load vary excessively? 1.Minimize the variation of the load. 2.Consider increasing the capacities of the inverter and the motor.
12 Motor speed varies unusually Is the input power unstable or is there a phase loss ? 1.Consider adding an AC reactor at the power input side if using single-phase power.
13 Motor speed varies unusually Is the input power unstable or is there a phase loss ? 2.Check wiring if using three-phase power
14 Motor can not run Is the power connected to the correct L1, L2, and L3 terminals? is the charging indicator lit ? 1.Is the power applied? 2.Turn the power OFF and then ON again. 3.Make sure the power voltage is correct. 4.Make sure screws are secured firmly.
15 Motor can not run Is there voltage across the output terminals T1, T2, and T3? Turn the power OFF and then ON again.
16 Motor can not run Is overload causing the motor to stall? Reduce the load so the motor will run.
17 Motor can not run Are there any abnormalities in the inverter? See error descriptions to check wiring and correct if necessary.
18 Motor can not run Is there a forward or reverse run command ? See error descriptions to check wiring and correct if necessary.
19 Motor can not run Has the analog frequency signal been input? 1.Is analog frequency input signal wiring correct? 2.Is voltage of frequency input correct?
20 Motor can not run Is the operation mode setting correct? Operate through the digital keypad

Manual — Routine inspection checklist — page 130

Manual reference: Ver.02, January 2016, physical PDF page 130. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

5.4 Routine and periodic inspection To ensure stable and safe operations, check and maintain the inverter at regular intervals. Use the checklist below to carry out inspection. Disconnect power after approximately 5 minutes to make sure no voltage is present on the output terminals before any inspection or maintenance.

Routine inspection checklist

Items / Details / Checking period / Methods / Criteria / Remedies — PDF page 130

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Items Details Checking period Checking period Methods Criteria Remedies
2 Items Details Daily 1Year Methods Criteria Remedies
3 Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection Environment & Ground connection
4 Ambient conditions at the installation Confirm the temperature and humidity at the machine ◎ ⟦blank source cell⟧ Measure with thermometer and hygrometer Temperature: -10 ~40°C (14~120°F) Humidity: Below 95%RH Improve the ambient or relocate the drive to a better area.
5 Installation Grounding Is the grounding resistance correct? ⟦blank source cell⟧ ◎ Measure the resistance with a multi-tester 200Vclass: below 100Ω Improve the grounding if needed.
6 Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring Terminals & Wiring
7 Connection terminals Any loose parts or terminals? ⟦blank source cell⟧ ◎ Visual check Check with a screwdriver Correct installation requirement Secure terminals and remove rust
8 Connection terminals Any damage to the base ? ⟦blank source cell⟧ ◎ Visual check Check with a screwdriver Correct installation requirement Secure terminals and remove rust
9 Connection terminals Any corroded Terminals? ⟦blank source cell⟧ ◎ Visual check Check with a screwdriver Correct installation requirement Secure terminals and remove rust
10 Wiring Any broken wires? ⟦blank source cell⟧ ◎ Visual check Correct wiring requirement Rectify as necessary
11 Wiring Any damage to the wire insulation? ⟦blank source cell⟧ ◎ Visual check Correct wiring requirement Rectify as necessary
12 voltage voltage voltage voltage voltage voltage voltage
13 Input power voltage Is the voltage of the main circuit correct? ◎ ⟦blank source cell⟧ Measure the voltage with a multi-tester Voltage must conform with the spec. Improve input voltage if necessary.
14 Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components Circuit boards and components
15 Printed circuit board Any contamination or damage to printed circuit board? ⟦blank source cell⟧ ◎ Visual check Correct component condition Clean or replace the circuit board
16 Power component Any dust or debris ⟦blank source cell⟧ ◎ Visual check Correct component condition Clean components
17 Power component Check resistance between terminals ⟦blank source cell⟧ ◎ Measure with a multi-tester No short circuit or broken circuit in three phase output Consult with the supplier
18 Cooling System Cooling System Cooling System Cooling System Cooling System Cooling System Cooling System
19 Cooling fan Unusual vibration and noise? ⟦blank source cell⟧ ◎ Visual and sound check Correct cooling Consult with the supplier
20 Cooling fan Excessive dust or debris ◎ ⟦blank source cell⟧ Visual check Correct cooling Clean the fan
21 Heat sink Excessive dust or debris ◎ ⟦blank source cell⟧ Visual check Correct cooling Clean up debris or dust
22 Ventilation Path Is the ventilation path blocked? ◎ ⟦blank source cell⟧ Visual check Correct cooling Clear the path

Manual — Reactor and contactor/breaker specifications — page 132

Manual reference: Ver.02, January 2016, physical PDF page 132. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Chapter 6 Peripherals Components 6.1 Reactor Specifications

Specification Note1 : Calculated inductance based on 3% reactance 6.2 Electromagnetic Contactor and No fuse circuit breaker

Reactor and contactor/breaker specifications

Model: L510-□□□-SHXX-X / Specification — PDF page 132

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Model: L510-□□□-SHXX-X Specification Specification
2 Model: L510-□□□-SHXX-X Current (A) Inductance (mH)(Note1)
3 2P2 4.9 4.48
4 2P5 7.2 3.05
5 2P7 9.0 2.44
6 201 11.0 2.00
7 202 15.5 1.42
8 203 21.0 1.05
9 205 20.0 0.63
10 208 33.0 0.38
11 210 42.0 0.30
12 401 4.2 5.25
13 402 5.6 3.94
14 403 7.3 3.02
15 405 12.0 1.84
16 408 17.0 1.30
17 410 23.0 0.96
18 415 31.0 0.71

Model: L510-□□□-SHXX-X / Molded-case circuit breaker made by TECO / Magnetic contactor (MC) made by TECO — PDF page 132

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Model: L510-□□□-SHXX-X Molded-case circuit breaker made by TECO Magnetic contactor (MC) made by TECO
2 1P2/1P5/2P2/2P5 TO-50E 15A CN-11
3 101/2P7/201/202 TO-50E 20A CN-11
4 203/205 TO-50E 30A CN-11
5 401/402/403/405 TO-50EC 15A CN-11
6 208 TO-50E 50A CN-11
7 210 TO-100S 60A CN-11
8 408 TO-50E 20A CN-11
9 410 TO-50E 30A CN-11
10 415 TO-50E 50A CN-11

Manual reference: Ver.02, January 2016, physical PDF page 133. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

6.3 Fuse Specification 6.4 Fuse Specification(UL Model Recommended)

Fuse and UL recommended fuse specifications

Model: L510-□□□-SHXX-X / HP / KW / Rating — PDF page 133

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Model: L510-□□□-SHXX-X HP KW Rating
2 1P2 0.25 0.2 15A, 300VAC
3 1P5 0.5 0.4 15A, 300VAC
4 101 1 0.75 20A, 300VAC
5 2P2 0.25 0.2 10A, 300VAC
6 2P5 0.5 0.4 15A, 300VAC
7 2P7 0.75 0.55 15A, 300VAC
8 201 1 0.75 15A, 300VAC
9 202 2 1.5 30A, 300VAC
10 203 3 2.2 30A, 300VAC
11 205 5 3.7 30A, 300VAC
12 208 7.5 5.5 60A, 300VAC
13 210 10 7.5 60A, 300VAC
14 401 1 0.75 5A, 600VAC
15 402 2 1.5 15A, 600VAC
16 403 3 2.2 20A, 600VAC
17 405 5 3.7 20A, 600VAC
18 408 7.5 5.5 40A, 600VAC
19 410 10 7.5 40A, 600VAC
20 415 15 11 70A, 600VAC

Model / Manufacture / Type / Rating — PDF page 133

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Model Manufacture Type Rating
2 L510-1P2-SH1X Bussmann 16CT 690V 16A
3 L510-1P5-SH1X Bussmann 20CT 690V 20A
4 L510-101-SH1X Bussmann 25ET 690V 25A
5 L510-2P2-SH1/SH1F Bussmann 10CT 690V 10A
6 L510-2P5-SH1/SH1F Bussmann 10CT/16CT 690V 10A/690V 16A
7 L510-2P7-SH1/SH1F Bussmann 16CT/20CT 690V 16A/690V 20A
8 L510-201-SH1/SH1F Bussmann 16CT/20CT 690V 16A/690V 20A
9 L510-202-SH1/SH1F Bussmann 30FE 690V 30A
10 L510-203-SH1/SH1F Bussmann 50FE 690V 50A
11 L510-2P2-SH3 Bussmann 10CT 690V 10A
12 L510-2P5-SH3 Bussmann 10CT 690V 10A
13 L510-201-SH3 Bussmann 10CT 690V 10A
14 L510-202-SH3 Bussmann 16CT 690V 16A
15 L510-203-SH3 Bussmann 20CT 690V 20A
16 L510-205-SH3 Bussmann 50FE 690V 50V
17 L510-208-SH3 Bussmann 63/100 FE 690V 63A
18 L510-210-SH3 Bussmann 80/100 FE 690V 80/690V100A
19 L510-401-SH3 Bussmann 10CT 690V 10A
20 L510-402-SH3 Bussmann 16CT 690V 16A
21 L510-403-SH3 Bussmann 20CT 690V 20A
22 L510-405-SH3 (F) Bussmann 25ET 690V 25A
23 L510-408-SH3 (F) Bussmann 40FE 690V 40A
24 L510-410-SH3 (F) Bussmann 50ET 690V 50A
25 L510-415-SH3 (F) Bussmann 63ET 690V 63A

Manual — Braking resistors and copy unit — page 134

Manual reference: Ver.02, January 2016, physical PDF page 134. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Source limitation for this page: Tiny pixelated copy-unit keypad lettering and some hardware inscriptions unresolved after5x crop; all legible dimension labels and source table cells retained; no unit inferred.

6.5 Braking Resistor

※Note: Braking resistor : W= ( Vpnb * Vpnb ) * ED% / Rmin 1. W: The power consumption of braking action 2. Vpnb: The voltage of braking action (220V=380VDC, 440V=760VDC) 3. ED%: The effective period of braking action 4. Rmin: braking resistor minimum value (ohms) 6.6 Copy Unit(JN5-CU) The copy unit is used to copy an inverter parameter setup to another inverter. The copy unit saves time in applications with multiple inverters requiring the same parameter setup Copy Unit (JN5-CU) dimensions

Braking resistor table; model patternL510-□□□-SH3X, blank detection module and parallel-number cells retained. No table-value corrections inferred. Source thin vertical rules at316.2and384.6points restore distinctkW/W/ohm/parallel-number columns.

Braking Resistor / original10physical columns — PDF page 134

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows) Physical column 10 (source headings retained in rows)
1 Model: L510-□□□-SH 3X Braking detection module Braking detection module (HP) (KW) Braking resistor Braking resistor Braking resistor ED(%) braking torque (%)
2 Model: L510-□□□-SH 3X Model Parallel Number (HP) (KW) (W) (Ω) Parallel Number ED(%) braking torque (%)
3 205 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 3.5 390 40 ⟦blank source cell⟧ 10 117
4 208 ⟦blank source cell⟧ ⟦blank source cell⟧ 7.5 5.5 600 25 ⟦blank source cell⟧ 10 123
5 210 ⟦blank source cell⟧ ⟦blank source cell⟧ 10 7.5 780 20 ⟦blank source cell⟧ 10 117
6 401 ⟦blank source cell⟧ ⟦blank source cell⟧ 1 0.75 60 750 - 8 123
7 402 ⟦blank source cell⟧ ⟦blank source cell⟧ 2 1.5 150 400 - 10 117
8 403 ⟦blank source cell⟧ ⟦blank source cell⟧ 3 2.2 200 250 - 8 123
9 405 ⟦blank source cell⟧ ⟦blank source cell⟧ 5 3.5 400 150 ⟦blank source cell⟧ 10 123
10 408 ⟦blank source cell⟧ ⟦blank source cell⟧ 7.5 5.5 600 100 ⟦blank source cell⟧ 10 123
11 410 ⟦blank source cell⟧ ⟦blank source cell⟧ 10 7.5 750 80 ⟦blank source cell⟧ 10 117
12 415 ⟦blank source cell⟧ ⟦blank source cell⟧ 15 11 1600 50 ⟦blank source cell⟧ 10 123

Manual — UL source claims and crimp terminal sizes — page 139

Manual reference: Ver.02, January 2016, physical PDF page 139. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Appendix-2 Instructions for UL NOTICE Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. Teco is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other devices. Failure to comply could result in damage to the drive. ◆ UL Standards The UL/cUL mark applies to products in the United States and Canada and it means that UL has performed product testing and evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL certification, all components inside that product must also receive UL certification. ◆ UL Standards Compliance This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued compliance when using this drive in combination with other equipment, meet the following conditions: ■ Installation Area Do not install the drive to an area greater than pollution severity 2 (UL standard). ■ Main Circuit Terminal Wiring UL approval requires crimp terminals when wiring the drive’s main circuit terminals. Use crimping tools as specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches drives models with crimp terminals and insulation caps. Orders can be placed with a Teco representative or directly with the Teco sales department. Closed-Loop Crimp Terminal Size

Wire Gauge

◆ Type 1 During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.

UL source claims and crimp terminal sizes

Drive Model / Wire Gauge / Terminal / Crimp Terminal / Tool / Insulation Cap — PDF page 139

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows)
1 Drive Model Wire Gauge Wire Gauge Terminal Crimp Terminal Tool Insulation Cap
2 Drive Model mm2 , (AWG) mm2 , (AWG) Terminal Crimp Terminal Tool Insulation Cap
3 L510 R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 Screws Model No. Machine No. Model No.
4 1P2 1.3(16) 1.3(16) M3.5 R2-3.5 Nichifu NH 1 / 9 TIC 2
5 1P5 2.1 (14) 2.1 (14) M3.5 R2-3.5 Nichifu NH 1 / 9 TIC 2
6 101 3.3(12) 3.3(12) M4 R3.5-4 Nichifu NH 1 / 9 TIC 3.5
7 2P2 1.3(16) 1.3(16) M3.5 R2-3.5 Nichifu NH 1 / 9 TIC 2
8 2P5 1.3 (16) 1.3 (16) M3.5 R2-3.5 Nichifu NH 1 / 9 TIC 2
9 2P7 2.1(14) 2.1(14) M3.5 R2-3.5 Nichifu NH 1 / 9 TIC 2
10 201 2.1 (14) 2.1 (14) M3.5 R2-3.5 Nichifu NH 1 / 9 TIC 2
11 202 3.3(12) 3.3(12) M4 R3.5-4 Nichifu NH 1 / 9 TIC 3.5
12 203 5.3(10) 5.3(10) M4 R5.5-4 Nichifu NH 1 / 9 TIC 3.5
13 205 5.3(10) 5.3(10) M4 R5.5-4 Nichifu NH 1 / 9 TIC 5.5
14 208/210 8.4(14) 8.4(14) M5 R8-5 Nichifu NH 1 / 9 TIC 8
15 401 2.1 (14) 2.1 (14) M4 R3.5-4 Nichifu NH 1 / 9 TIC 2
16 402 2.1 (14) 2.1 (14) M4 R3.5-4 Nichifu NH 1 / 9 TIC 2
17 403 2.1 (14) 2.1 (14) M4 R3.5-4 Nichifu NH 1 / 9 TIC 2
18 405 2.1(14) 2.1(14) M4 R2-3.5 Nichifu NH 1 / 9 TIC 2
19 408/410/415 8.4(8) 8.4(8) M5 R8-5 Nichifu NH 1 / 9 TIC 8

Manual — UL input fuse selections and short-circuit source rating — page 140

Manual reference: Ver.02, January 2016, physical PDF page 140. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Appendix-2 Instructions for UL

Recommended Input Fuse Selection

■Field Wiring Terminals All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to be made to each terminal and indicate that copper conductors, rated 80°C are to be used. ■ Drive Short-Circuit Rating This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise above value. Please see electrical ratings for maximum voltage and table below for current. • The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit tolerance of the power supply being used. • Suitable for use on a circuit capable of delivering not more than ( A ) RMS symmetrical amperes for ( Hp ) Hp in 240 / 480 V class drives motor ■ overload protection. •

UL input fuse selections and short-circuit source rating

Drive Model L510 1P2 1P5 101 / / Fuse Type — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Drive Model L510 1P2 1P5 101 ⟦blank source cell⟧ Fuse Type Fuse Type
2 Drive Model L510 1P2 1P5 101 Manufacturer: Bussmann Manufacturer: Bussmann Manufacturer: Bussmann
3 Drive Model L510 1P2 1P5 101 Model ⟦blank source cell⟧ Fuse Ampere Rating (A)
4 Drive Model L510 1P2 1P5 101 100 V Class Single-Phase Drives 100 V Class Single-Phase Drives 100 V Class Single-Phase Drives
5 Drive Model L510 1P2 1P5 101 Bussmann 16CT 690V 16A 690V 16A
6 Drive Model L510 1P2 1P5 101 Bussmann 20CT 690V 20A 690V 20A
7 Drive Model L510 1P2 1P5 101 Bussmann 25ET 690V 25A 690V 25A

/ Fuse Type — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 ⟦blank source cell⟧ ⟦blank source cell⟧ Fuse Type Fuse Type
2 Drive Model L510 Manufacturer: Bussmann Manufacturer: Bussmann Manufacturer: Bussmann
3 Drive Model L510 Model ⟦blank source cell⟧ Fuse Ampere Rating (A)
4 ⟦blank source cell⟧ 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives 200 V Class Single-Phase Drives
5 2P2 Bussmann 10CT 690V 10A 690V 10A
6 2P5 Bussmann 10CT/16CT 690V 10A / 690V 16A 690V 10A / 690V 16A
7 2P7 Bussmann 16CT/20CT 690V 16A / 690V 20A 690V 16A / 690V 20A
8 201 Bussmann 16CT/20CT 690V 16A / 690V 20A 690V 16A / 690V 20A
9 202 Bussmann 30FE 690V 30A 690V 30A
10 203 Bussmann 50FE 690V 50A 690V 50A

/ Fuse Type — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 ⟦blank source cell⟧ ⟦blank source cell⟧ Fuse Type Fuse Type
2 Drive Model L510 Manufacturer: Bussmann Manufacturer: Bussmann Manufacturer: Bussmann
3 Drive Model L510 Model ⟦blank source cell⟧ Fuse Ampere Rating (A)
4 ⟦blank source cell⟧ 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives 200 V Class Three-Phase Drives
5 2P2 Bussmann 10CT Bussmann 10CT 690V 10A
6 2P5 Bussmann 10CT Bussmann 10CT 690V 10A
7 201 Bussmann 10CT Bussmann 10CT 690V 10A
8 202 Bussmann 16CT Bussmann 16CT 690V 16A
9 203 Bussmann 20CT Bussmann 20CT 690V 20A
10 205 Bussmann 50FE Bussmann 50FE 690V 50A
11 208 Bussmann 63CT/100FE Bussmann 63CT/100FE 690V 63A
12 210 Bussmann 80CT/100FE Bussmann 80CT/100FE 690V 80A/690V 100A

/ Fuse Type — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 ⟦blank source cell⟧ ⟦blank source cell⟧ Fuse Type Fuse Type
2 Drive Model L510 Manufacturer: Bussmann Manufacturer: Bussmann Manufacturer: Bussmann
3 ⟦blank source cell⟧ Model ⟦blank source cell⟧ Fuse Ampere Rating (A)
4 ⟦blank source cell⟧ 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives 400 V Class Three-Phase Drives
5 401 Bussmann 10CT Bussmann 10CT 690V10A
6 402 Bussmann 16CT Bussmann 16CT 690V 16A
7 403 Bussmann 20CT Bussmann 20CT 690V 20A
8 405 Bussmann 25ET Bussmann 25ET 690V 25A
9 408 Bussmann 40FE Bussmann 40FE 690V 40A
10 410 Bussmann 50ET Bussmann 50ET 690V 50A
11 415 Bussmann 63ET Bussmann 63ET 690V 63A

Horse Power ( Hp ) / Current ( A ) / Voltage ( V ) — PDF page 140

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Horse Power ( Hp ) Current ( A ) Voltage ( V )
2 0- 50 5,000 240 / 480

Manual — UL motor overload settings — page 141

Manual reference: Ver.02, January 2016, physical PDF page 141. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Appendix-2 Instructions for UL ◆ Drive Motor Overload Protection Set parameter 02-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload protection is UL listed and in accordance with the NEC and CEC. ■ 02-01 Motor Rated Current Setting Range: Model Dependent Factory Default: Model Dependent Set 02-01 to the full load amps (FLA) stamped on the nameplate of the motor. ■ 08-05 Motor Overload Protection Selection The drive has an electronic overload protection function (OL1) based on time, output current, and output frequency, which protects the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external thermal overload relay for single motor operation. This parameter selects the motor overload curve used according to the type of motor applied. Overload Protection Settings

Sets the motor overload protection function in 08-05 according to the applicable motor. Setting 08-05 = XXXX0. Disables the motor overload protection function when two or more motors are connected to a single inverter. Use an alternative method to provide separate overload protection for each motor such as connecting a thermal overload relay to the power line of each motor. ■

Motor Overload Protection Time ■ 08-06 Motor Overload Operation Selection

UL motor overload settings

Setting / Description — PDF page 141

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Setting Description
2 XXXX0 Disabled
3 XXXX1 Enabled

Setting / Description — PDF page 141

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Setting Description
2 0 Free Run to Stop (default setting)
3 1 Alarm Only

Manual — Modbus hardware and ASCII frame — page 142

Manual reference: Ver.02, January 2016, physical PDF page 142. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Appendix 3 L510s Communication protocol Modbus communication protocol 1. Communication Data Frame L510s series inverter can be controlled by a PC or other controller with the Communication protocol, Modbus ASCII Mode & Mode RTU, RS485 or RS232. Frame length maximum 80 bytes.

1.1 Hardware installation

** The network is terminated at each end with an external terminating resistor (120Ω,1/4w)** 1.2 Data format ASCII MODE

Modbus hardware and ASCII frame

STX(3AH) / Start bit = 3AH — PDF page 142

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 STX(3AH) Start bit = 3AH
2 Address Hi Communication Address(Station): 2-digit ASCII Code
3 Address Lo Communication Address(Station): 2-digit ASCII Code
4 Function Hi Function Code (command): 2-digit ASCII Code
5 Function Lo Function Code (command): 2-digit ASCII Code
6 Command Start Address Command Start byte: 4-digit ASCII Code
7 Command Start Address Command Start byte: 4-digit ASCII Code
8 Command Start Address Command Start byte: 4-digit ASCII Code
9 Command Start Address Command Start byte: 4-digit ASCII Code
10 Data length The length of the command: 4-digit ASCII Code
11 Data length The length of the command: 4-digit ASCII Code
12 Data length The length of the command: 4-digit ASCII Code
13 Data length The length of the command: 4-digit ASCII Code
14 LRC Check Hi LRC Check Code: 2-digit ASCII Code
15 LRC Check Lo LRC Check Code: 2-digit ASCII Code
16 END Hi End Byte : END Hi = CR(0DH) , END Lo= LF(0AH)
17 END L End Byte : END Hi = CR(0DH) , END Lo= LF(0AH)

Manual — Modbus error frames and exception codes — page 145

Manual reference: Ver.02, January 2016, physical PDF page 145. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

  1. Error code

ASCII Mode RTU Mode

Under communication linking, the driver responses the Exception Code and send Function Code AND 80H to main system if there is error happened.

Independent parser word order differences were checked against actual second visual source reading; source row/column context retained without changing literal values.

Modbus error frames and exception codes

STX / ‘:’ — PDF page 145

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 STX ‘:’
2 Address ‘0’
3 Address ‘1’
4 Function ‘8’
5 Function ‘6’
6 Exception code ‘5’
7 Exception code ‘1’
8 LRC Check ‘2’
9 LRC Check ‘8’
10 END ‘CR’
11 END ‘LF’

SLAVE Address / 02H — PDF page 145

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 02H
2 Function Function 83H
3 Exception code Exception code 52H
4 CRC-16 High C0H
5 CRC-16 Low CDH

Error Code / Description — PDF page 145

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Error Code Description
2 51 Function Code Error
3 52 Address Error
4 53 Data Amount Error
5 54 DATA Over Range
6 55 Writing Mode Error

Manual — Command and monitor register bit maps — page 146

Manual reference: Ver.02, January 2016, physical PDF page 146. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

  1. Inverter Control 4.1 Command Data (Readable and Writable)

*** Write in zero for Not used BIT, do not write in data for the reserved register.

Note : Bit 2 of 2501H is not for fault indication. EFO is for “external abnormity.” When there is external abnormity, controller may changes the bit value from 0 to 1 through, inverter will stop according to the setting in 09-07, inverter appears “EFO”. 4.2 Monitor Data (Only for reading)

Independent parser word order differences were checked against actual second visual source reading; source row/column context retained without changing literal values.

Command and monitor register bit maps

Register No. / Bit / Content — PDF page 146

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Register No. Bit Content
2 2500H Reserved Reserved
3 2501H ⟦blank source cell⟧ Operation Signal
4 2501H 0 Operation Command 1 : Run 0 : Stop
5 2501H 1 Reverse Command 1 :Reverse 0 :Forward
6 2501H 2 Abnormal 1 : EFO (Note)
7 2501H 3 Fault Reset 1 : Reset
8 2501H 4 Jog Forward Command 1 : Jog Forward
9 2501H 5 Jog Reverse Command 1 : Jog Reverse
10 2501H 6 Multi-function CommandS1 1 :“ON” 0:“OFF”
11 2501H 7 Multi-function CommandS2 1 :“ON” 0:“OFF”
12 2501H 8 Multi-function CommandS3 1 :“ON” 0:“OFF”
13 2501H 9 Multi-function CommandS4 1 :“ON” 0:“OFF”
14 2501H A Multi-function CommandS5 1 :“ON” 0:“OFF”
15 2501H B Reserved
16 2501H C Relay R1 1 :“ON” 0:“OFF”
17 2501H D Reserved
18 2501H E~F Reserved
19 2502H Frequency Command Frequency Command
20 2503~251FH Reserved Reserved

Register No. / Bit / Content — PDF page 146

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 Register No. Bit Content
2 2520H ⟦blank source cell⟧ ⟦blank source cell⟧
3 2520H 0 Operation state 1 : Run 0 : Stop
4 2520H 1 Direction state 1 : Reverse 0 : Forward
5 2520H 2 Inverter operation prepare state 1:ready 0 : unready
6 2520H 3 Abnormal 1 : Abnormal
7 2520H 4 DATA setting error 1 : Error
8 2520H 5-F Reserved

Manual — Abnormality monitor codes2521H — page 147

Manual reference: Ver.02, January 2016, physical PDF page 147. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Abnormality monitor codes2521H

Register No. / Contents — PDF page 147

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Register No. Contents Contents Contents Contents Contents
2 2521H ⟦blank source cell⟧ abnormity abnormity abnormity abnormity
3 2521H ⟦blank source cell⟧ 00 The inverter is normal 24 Over voltage during decelerating(OV-C)
4 2521H ⟦blank source cell⟧ 01 Inverter over heat(OH) 25 Inverter over heat during running(OH-C)
5 2521H ⟦blank source cell⟧ 02 Over current at stop(OC) 26 Stop at 0 speed(STP0)
6 2521H ⟦blank source cell⟧ 03 Under voltage(LV) 27 Direct start malfunction(STP1)
7 2521H ⟦blank source cell⟧ 04 Over voltage(OV) 28 Control panel emergency stop(STP2)
8 2521H ⟦blank source cell⟧ 05 Reserved 29 Keypad operation error)(Err1)
9 2521H ⟦blank source cell⟧ 06 External BB(bb) 30 Parameter setting error(Err2)
10 2521H ⟦blank source cell⟧ 07 CPU error by external signal(CTE ) 31 Analog transferred error(Err4)
11 2521H ⟦blank source cell⟧ 08 PID feedback signal lost(PDER) 32 Parameter changed during Communication (Err5)
12 2521H ⟦blank source cell⟧ 09 EEPROM abnormal(EPR) 33 Communication failure(Err6) (Note)
13 2521H ⟦blank source cell⟧ 10 Parameters auto measure error(ATER ) 34 Parameter setting error(Err7)
14 2521H ⟦blank source cell⟧ 11 Over Torque(OL3) 35 Restore factory setting error(Err8)
15 2521H ⟦blank source cell⟧ 12 Inverter over load( OL2 ) 36 Reserved
16 2521H ⟦blank source cell⟧ 13 Motor over load(OL1) 37 Reserved
17 2521H ⟦blank source cell⟧ 14 External communication error(EFO) 38 Parameters copy error via copy unit (EPR1)
18 2521H ⟦blank source cell⟧ 15 External stop( E.S ) 39 Parameters copy incorrect via copy unit (EPR2)
19 2521H ⟦blank source cell⟧ 16 Parameters locked(LOC) 40 Inverter over speed(OVSP)
20 2521H ⟦blank source cell⟧ 17 Reserved 41 Input phase lost(PF)
21 2521H ⟦blank source cell⟧ 18 Over current at constant speed (OC-C) 42 Horsepower setting error(HPERR)
22 2521H ⟦blank source cell⟧ 19 Over current during accelerating (OC-A) 43 Reserved
23 2521H ⟦blank source cell⟧ 20 Over current during decelerating (OC-D) 44 Motor temperature overheat error(OH4)
24 2521H ⟦blank source cell⟧ 21 Over current at starting to run (OC-S) 45 Motor temperature overheat alarm(OH3)
25 2521H ⟦blank source cell⟧ 22 Reserved 46 Output current reaches current limit level(CL)
26 2521H ⟦blank source cell⟧ 23 Under voltage during running(LV-C) ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — I/O and numeric monitor registers — page 148

Manual reference: Ver.02, January 2016, physical PDF page 148. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

(Note) Err6 error: Inverter gets communication error with external devices. When inverter gets communication error: If the controller writes “1” to “2501H bit 2”, inverter appears “EFO” on display. If the controller does not write “1” to “2501H bit 2”, inverter appears “Err6” on display

I/O and numeric monitor registers

2522H / / Sequence input status — PDF page 148

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 2522H ⟦blank source cell⟧ Sequence input status Sequence input status
2 2522H ⟦blank source cell⟧ 0 Terminal S1 1 :“ON” 0:“OFF”
3 2522H ⟦blank source cell⟧ 1 Terminal S2 1 :“ON” 0:“OFF”
4 2522H ⟦blank source cell⟧ 2 Terminal S3 1 :“ON” 0:“OFF”
5 2522H ⟦blank source cell⟧ 3 Terminal S4 1 :“ON” 0:“OFF”
6 2522H ⟦blank source cell⟧ 4 Terminal S5 1 :“ON” 0:“OFF”
7 2522H ⟦blank source cell⟧ 5 Terminal S6 1 :“ON” 0:“OFF”
8 2522H ⟦blank source cell⟧ Contact output Contact output
9 2522H ⟦blank source cell⟧ 6 Relay R1 1 :“ON” 0:“OFF”
10 2522H ⟦blank source cell⟧ 7 Relay R2 1 :“ON” 0:“OFF”
11 2522H ⟦blank source cell⟧ 9~F Reserved

Register No. / Content — PDF page 148

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Register No. Content
2 2523H frequency command(100/1Hz)
3 2524H Output frequency (100/1Hz)
4 2525H Output voltage command (10/1V)
5 2526H DC voltage command (1/1V)
6 2527H Output current (10/1A)
7 2528H reserved
8 2529H reserved
9 252AH PID feedback (100% / fmax , 10/1% )
10 252BH PID input (100% / fmax, 10/1%)
11 252CH TM2 AVI input value (1000 / 10V) *1
12 252DH TM2 ACI input value (1000 / 10V) *1
13 252EH reserved
14 252FH A510s / L510s / E510s identification: L510s: 0x0110

Manual — Read holding-register examples03H — page 149

Manual reference: Ver.02, January 2016, physical PDF page 149. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

4.3 Read the data in the holding register [03H] Master unit reads the contents of the holding register with the continuous number for the specified quantity. Note:1. Limit number of read data,RTU: 37,ASCII:17. 2. Can only Continuous read the address of the same Group 3. Read data Quantity≥1. (Example) Read the SLAVE station No:01 ,L510s drive’s frequency command.

ASCII Mode Instruction Message Response Message (Normal) Response(Fault)

RTU Mode Instruction Message Response Message (Normal) Response(Fault)

Read holding-register examples03H

3AH / STX — PDF page 149

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 30H Function Code
5 33H Function Code
6 32H Start Address
7 35H Start Address
8 32H Start Address
9 33H Start Address
10 32H Quantity
11 35H Quantity
12 30H Quantity
13 31H Quantity
14 ? LRC CHECK
15 ? LRC CHECK
16 0DH END
17 0AH END

3AH / STX — PDF page 149

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 30H Function Code
5 33H Function Code
6 30H DATA Number
7 32H DATA Number
8 31H First holding register
9 37H First holding register
10 37H First holding register
11 30H First holding register
12 ? LRC CHECK
13 ? LRC CHECK
14 0DH END
15 0AH END

3AH / STX — PDF page 149

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 38H Function Code
5 33H Function Code
6 35H Error Code
7 32H Error Code
8 ? LRC CHECK
9 ? LRC CHECK
10 0DH END
11 0AH END

SLAVE Address / 01H — PDF page 149

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 03H
3 Start Address High 25H
4 Start Address Low 23H
5 Quantity High 00H
6 Quantity Low 01H
7 CRC-16 High 7EH
8 CRC-16 Low CCH

SLAVE Address / 01H — PDF page 149

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 03H
3 DATA Number DATA Number 02H
4 First holding register High 07H
5 First holding register Low D0H
6 CRC-16 High BBH
7 CRC-16 Low E8H

SLAVE Address / 01H — PDF page 149

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 83H
3 Error Code Error Code 52H
4 CRC-16 High C0H
5 CRC-16 Low CDH

Manual — Loopback examples08H — page 150

Manual reference: Ver.02, January 2016, physical PDF page 150. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

4.4 LOOP BACK testing [08H] The function code checks communication between MASTER and SLAVE, the Instruction message is returned as a response message without being changed, Any values can be used for test codes or data.

ASCII Mode Instruction Message Response Message (Normal) Response(Fault)

RTU Mode Instruction Message Response Message (Normal) Response(Fault)

Independent parser word order differences were checked against actual second visual source reading; source row/column context retained without changing literal values.

Loopback examples08H

3AH / STX — PDF page 150

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 30H Function Code
5 38H Function Code
6 30H Test Code
7 30H Test Code
8 30H Test Code
9 30H Test Code
10 41H DATA
11 35H DATA
12 33H DATA
13 37H DATA
14 31H LRC CHECK
15 42H LRC CHECK
16 0DH END
17 0AH END

3AH / STX — PDF page 150

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 30H Function Code
5 38H Function Code
6 30H Test Code
7 30H Test Code
8 30H Test Code
9 30H Test Code
10 41H DATA
11 35H DATA
12 33H DATA
13 37H DATA
14 31H LRC CHECK
15 42H LRC CHECK
16 0DH 0AH END

3AH / STX — PDF page 150

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 38H Function Code
5 38H Function Code
6 32H Error Code
7 30H Error Code
8 37H LRC CHEC
9 35H LRC CHEC
10 0DH END
11 0AH END

SLAVE Address / 01H — PDF page 150

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 08H
3 Test Code High 00H
4 Test Code Low 00H
5 DATA High A5H
6 DATA Low 37H
7 CRC-16 High DAH
8 CRC-16 Low 8DH

SLAVE Address / 01H — PDF page 150

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 88H
3 Error Code Error Code 20H
4 CRC-16 High 47H
5 CRC-16 Low D8H

Manual — Write holding-register examples06H — page 151

Manual reference: Ver.02, January 2016, physical PDF page 151. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

4.5 Write holding register [06H] Specified data are written into the several specified holding registers from the Specified respectively. (Example)Set SLAVE station No:01, write L510s drive frequency reference 60.0HZ.

ASCII Mode

Instruction Message Response Message (Normal) Response(Fault)

RTU Mode Instruction Message Response Message (Normal) Response(Fault)

Write holding-register examples06H

3AH / STX — PDF page 151

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 30H Function Code
5 36H Function Code
6 32H Start Address
7 35H Start Address
8 30H Start Address
9 32H Start Address
10 31H DATA
11 37H DATA
12 37H DATA
13 30H DATA
14 ? LRC CHECK
15 ? LRC CHECK
16 0DH END
17 0AH END

3AH / STX — PDF page 151

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 30H Function Code
5 36H Function Code
6 32H Start Address
7 35H Start Address
8 30H Start Address
9 32H Start Address
10 31H DATA
11 37H DATA
12 37H DATA
13 30H DATA
14 ? LRC CHECK
15 ? LRC CHECK
16 0DH 0AH END

3AH / STX — PDF page 151

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 38H Function Code
5 36H Function Code
6 35H Error Code
7 32H Error Code
8 ? LRC CHECK
9 ? LRC CHECK
10 0DH END
11 0AH END

SLAVE Address / 01H — PDF page 151

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 06H
3 Start Address High 25H
4 Start Address Low 02H
5 DATA High 17H
6 DATA Low 70H
7 CRC-16 High 2DH
8 CRC-16 Low 12H

SLAVE Address / 01H — PDF page 151

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 86H
3 Error Code Error Code 52H
4 CRC-16 High C3H
5 CRC-16 Low 9DH

Manual — Multiple-register write ASCII10H — page 152

Manual reference: Ver.02, January 2016, physical PDF page 152. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

4.6 Write in several holding registers [10H] Specified data are written into the several specified holding registers from the Specified number respectively. Note:1. Limit number of read data,RTU: 35,ASCII:15. 2. Can only Continuous read the address of the same Group. 3. Read data Quantity≥1. (Example)Set SLAVE station No:01, L510s drive as forward run at frequency reference 60.0HZ. ASCII Mode

Instruction Message Response Message (Normal) Response(Fault)

Independent parser word order differences were checked against actual second visual source reading; source row/column context retained without changing literal values.

Multiple-register write ASCII10H

3AH / STX — PDF page 152

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 31H Function Code
5 30H Function Code
6 32H Start Address
7 35H Start Address
8 30H Start Address
9 31H Start Address
10 30H Quantity
11 30H Quantity
12 30H Quantity
13 32H Quantity
14 30H DATA Number *
15 34H DATA Number *
16 30H First DATA
17 30H First DATA
18 30H First DATA
19 31H First DATA
20 31H Next DATA
21 37H Next DATA
22 37H Next DATA
23 30H Next DATA
24 ? LRC CHECK
25 ? LRC CHECK
26 0DH END
27 0AH END

3AH / STX — PDF page 152

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 31H Function Code
5 30H Function Code
6 32H Start Address
7 35H Start Address
8 30H Start Address
9 31H Start Address
10 30H Quantity
11 30H Quantity
12 30H Quantity
13 32H Quantity
14 ? LRC CHECK
15 ? LRC CHECK
16 0DH END
17 0AH END

3AH / STX — PDF page 152

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 3AH STX
2 30H SLAVE Address
3 31H SLAVE Address
4 39H Function Code
5 30H Function Code
6 35H Error Code
7 32H Error Code
8 ? LRC CHECK
9 ? LRC CHECK
10 0DH END
11 0AH END

Manual — Multiple-register write RTU10H — page 153

Manual reference: Ver.02, January 2016, physical PDF page 153. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

RTU Mode Instruction Message Response Message (Normal) Response(Fault)

Multiple-register write RTU10H

SLAVE Address / 01H — PDF page 153

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 10H
3 Start Address High 25H
4 Start Address Low 01H
5 Quantity High 00H
6 Quantity Low 02H
7 DATA Number * DATA Number * 04H
8 First DATA High 00H
9 First DATA Low 01H
10 Next DATA High 17H
11 Next DATA Low 70H
12 CRC-16 High CBH
13 CRC-16 Low 26H

SLAVE Address / 01H — PDF page 153

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 10H
3 Start Address High 25H
4 Start Address Low 01H
5 Quantity High 00H
6 Quantity Low 02H
7 CRC-16 High 1BH
8 CRC-16 Low 04H

SLAVE Address / 01H — PDF page 153

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows)
1 SLAVE Address SLAVE Address 01H
2 Function Code Function Code 90H
3 Error Code Error Code 52H
4 CRC-16 High CDH
5 CRC-16 Low FDH

Manual — Parameter/register mapping groups00–02 — page 154

Manual reference: Ver.02, January 2016, physical PDF page 154. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

  1. Comparison list between parameter and register Note: Parameter register No.: GGnnH, “GG”means Group number, “nn” means Parameter number for example: the address of Pr 08-03 is 0803H. the address of Pr 10-11 is 0A0BH

Parameter/register mapping groups00–02

Register No. / Function — PDF page 154

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Register No. Function Register No. Function Register No. Function
2 Group00 Group00 Group01 Group01 Group02 Group02
3 0000H 00-00 0100H 01-00 0200H 02-00
4 0001H 00-01 0101H 01-01 0201H 02-01
5 0002H 00-02 0102H 01-02 0202H 02-02
6 0003H 00-03 0103H 01-03 0203H 02-03
7 0004H 00-04 0104H 01-04 0204H 02-04
8 0005H 00-05 0105H 01-05 0205H 02-05
9 0006H 00-06 0106H 01-06 0206H 02-06
10 0007H 00-07 0107H 01-07 0207H 02-07
11 0008H 00-08 0108H 01-08 0208H 02-08
12 0009H 00-09 0109H 01-09 0209H 02-09
13 000AH 00-10 010AH 01-10 020AH 02-10
14 000BH 00-11 010BH 01-11 020BH 02-11
15 000CH 00-12 010CH 01-12 020CH 02-12
16 000DH 00-13 010DH 01-13 020DH 02-13
17 000EH 00-14 010EH 01-14 020EH 02-14
18 000FH 00-15 010FH 01-15 020FH 02-15
19 0010H 00-16 0110H 01-16 0210H 02-16
20 0011H 00-17 0111H 01-17 0211H 02-17
21 0012H 00-18 0112H 01-18 ⟦blank source cell⟧ ⟦blank source cell⟧
22 0013H 00-19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 0014H 00-20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter/register mapping groups03–05 — page 155

Manual reference: Ver.02, January 2016, physical PDF page 155. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Parameter/register mapping groups03–05

Register No. / Function — PDF page 155

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Register No. Function Register No. Function Register No. Function
2 Group03 Group03 Group04 Group04 Group05 Group05
3 0300H 03-00 0400H 04-00 0500H 05-00
4 0301H 03-01 0401H 04-01 0501H 05-01
5 0302H 03-02 0402H 04-02 0502H 05-02
6 0303H 03-03 0403H 04-03 0503H 05-03
7 0304H 03-04 0404H 04-04 0504H 05-04
8 0305H 03-05 0405H 04-05 0505H 05-05
9 0306H 03-06 0406H 04-06 0506H 05-06
10 0307H 03-07 0407H 04-07 0507H 05-07
11 0308H 03-08 0408H 04-08 0508H 05-08
12 0309H 03-09 0409H 04-09 0509H 05-09
13 030AH 03-10 040AH 04-10 050AH 05-10
14 030BH 03-11 040BH 04-11 050BH 05-11
15 030CH 03-12 040CH 04-12 050CH 05-12
16 030DH 03-13 040DH 04-13 050DH 05-13
17 030EH 03-14 040EH 04-14 050EH 05-14
18 030FH 03-15 040FH 04-15 050FH 05-15
19 0310H 03-16 ⟦blank source cell⟧ ⟦blank source cell⟧ 0510H 05-16
20 0311H 03-17 ⟦blank source cell⟧ ⟦blank source cell⟧ 0511H 05-17
21 0312H 03-18 ⟦blank source cell⟧ ⟦blank source cell⟧ 0512H 05-18
22 0313H 03-19 ⟦blank source cell⟧ ⟦blank source cell⟧ 0513H 05-19
23 0314H 03-20 ⟦blank source cell⟧ ⟦blank source cell⟧ 0514H 05-20
24 0315H 03-21 ⟦blank source cell⟧ ⟦blank source cell⟧ 0515H 05-21
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 0516H 05-22
26 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 0517H 05-23
27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 0518H 05-24
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 0519H 05-25
29 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 051AH 05-26
30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 051BH 05-27
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 051CH 05-28
32 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 051DH 05-29
33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 051EH 05-30
34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 051FH 05-31
35 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 0520H 05-32

Manual — Parameter/register mapping groups06–08 — page 156

Manual reference: Ver.02, January 2016, physical PDF page 156. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Parameter/register mapping groups06–08

Register No. / Function — PDF page 156

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Register No. Function Register No. Function Register No. Function
2 Group06 Group06 Group07 Group07 Group08 Group08
3 0600H 06-00 0700H 07-00 0800H 08-00
4 0601H 06-01 0701H 07-01 0801H 08-01
5 0602H 06-02 0702H 07-02 0802H 08-02
6 0603H 06-03 0703H 07-03 0803H 08-03
7 0604H 06-04 0704H 07-04 0804H 08-04
8 0605H 06-05 0705H 07-05 0805H 08-05
9 0606H 06-06 0706H 07-06 0806H 08-06
10 0607H 06-07 0707H 07-07 0807H 08-07
11 0608H 06-08 0708H 07-08 0808H 08-08
12 0609H 06-09 0709H 07-09 0809H 08-09
13 060AH 06-10 ⟦blank source cell⟧ ⟦blank source cell⟧ 080AH 08-10
14 060BH 06-11 ⟦blank source cell⟧ ⟦blank source cell⟧ 080BH 08-11
15 060CH 06-12 ⟦blank source cell⟧ ⟦blank source cell⟧ 080CH 08-12
16 060DH 06-13 ⟦blank source cell⟧ ⟦blank source cell⟧ 080DH 08-13
17 060EH 06-14 ⟦blank source cell⟧ ⟦blank source cell⟧ 080EH 08-14
18 060FH 06-15 ⟦blank source cell⟧ ⟦blank source cell⟧ 080FH 08-15
19 0610H 06-16 ⟦blank source cell⟧ ⟦blank source cell⟧ 0810H 08-16
20 0611H 06-17 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 0612H 06-18 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 0613H 06-19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 0614H 06-20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 0615H 06-21 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
25 0616H 06-22 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 0617H 06-23 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 0618H 06-24 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 0619H 06-25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 061AH 06-26 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 061BH 06-27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 061CH 06-28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 061DH 06-29 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 061EH 06-30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 061FH 06-31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
35 0620H 06-32 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
36 0621H 06-33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
37 0622H 06-34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
38 0623H 06-35 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
39 0624H 06-36 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 0625H 06-37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Mapping group06continuation and09–11 — page 157

Manual reference: Ver.02, January 2016, physical PDF page 157. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Mapping group06continuation and09–11

Register No. / Function — PDF page 157

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Register No. Function Register No. Function Register No. Function
2 Group06 Group06 Group07 Group07 Group08 Group08
3 0626H 06-38 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
4 0627H 06-39 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Register No. / Function — PDF page 157

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Register No. Function Register No. Function Register No. Function
2 Group09 Group09 Group10 Group10 Group11 Group11
3 0900H 09-00 0A00H 10-00 0B00H 11-00
4 0901H 09-01 0A01H 10-01 0B01H 11-01
5 0902H 09-02 0A02H 10-02 0B02H 11-02
6 0903H 09-03 0A03H 10-03 0B03H 11-03
7 0904H 09-04 0A04H 10-04 0B04H 11-04
8 0905H 09-05 0A05H 10-05 0B05H 11-05
9 0906H 09-06 0A06H 10-06 0B06H 11-06
10 0907H 09-07 0A07H 10-07 0B07H 11-07
11 0908H 09-08 0A08H 10-08 0B08H 11-08
12 0909H 09-09 0A09H 10-09 0B09H 11-09
13 090AH 09-10 0A0AH 10-10 0B0AH 11-10
14 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A0BH 10-11 0B0BH 11-11
15 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A0CH 10-12 0B0CH 11-12
16 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A0DH 10-13 0B0DH 11-13
17 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A0EH 10-14 0B0EH 11-14
18 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A0FH 10-15 0B0FH 11-15
19 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A10H 10-16 0B10H 11-16
20 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A11H 10-17 0B11H 11-17
21 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A12H 10-18 0B12H 11-18
22 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A13H 10-19 0B13H 11-19
23 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A14H 10-20 0B14H 11-20
24 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A15H 10-21 ⟦blank source cell⟧ ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ 0A16H 10-22 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — Parameter/register mapping groups12–13 — page 158

Manual reference: Ver.02, January 2016, physical PDF page 158. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Parameter/register mapping groups12–13

Register No. / Function — PDF page 158

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 Register No. Function Register No. Function Register No. Function
2 Group12 Group12 Group13 Group13 ⟦blank source cell⟧ ⟦blank source cell⟧
3 0C00H 12-00 0D00H 13-00 ⟦blank source cell⟧ ⟦blank source cell⟧
4 0C01H 12-01 0D01H 13-01 ⟦blank source cell⟧ ⟦blank source cell⟧
5 0C02H 12-02 0D02H 13-02 ⟦blank source cell⟧ ⟦blank source cell⟧
6 0C03H 12-03 0D03H 13-03 ⟦blank source cell⟧ ⟦blank source cell⟧
7 0C04H 12-04 0D04H 13-04 ⟦blank source cell⟧ ⟦blank source cell⟧
8 0C05H 12-05 0D05H 13-05 ⟦blank source cell⟧ ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ 0D06H 13-06 ⟦blank source cell⟧ ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ 0D07H 13-07 ⟦blank source cell⟧ ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ 0D08H 13-08 ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — BACnet supported object-property matrix — page 161

Manual reference: Ver.02, January 2016, physical PDF page 161. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

  1. BACnet Specifications Inverter L510s model is built-in standard BACnet MS/TP communication protocol structure to meet the demand of automatic communication equipment. Control or monitor L510s via BACnet to be allowable to read and modify specific parameter. L510s includes the following supports of standard objects: ■ Inverter Objects ■ Analog Input ■ Analog Output ■ Analog Value ■ Digital Input ■ Digital Output ■ Digital Value Refer to Table 3.1 for L510s supporting the property information of object classification. User can collect related properties of objects required via the dedicated communication software of BACnet to give control or monitor command for each object.

Table 3.1 Object and property supporting list

BACnet supported object-property matrix

Proerty / Inverter (VFD) / Analog Input (AI) / Analog Output (AO) / Analog Value (AV) / Digital Input (BI) / Digital Output (BO) / Digital Value (BV) — PDF page 161

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows)
1 Proerty Inverter (VFD) Analog Input (AI) Analog Output (AO) Analog Value (AV) Digital Input (BI) Digital Output (BO) Digital Value (BV)
2 Object_Identifier V V V V V V V
3 Object_Name V V V V V V V
4 Object_Type V V V V V V V
5 System_Status V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 Vendor_Name V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
7 Vendor_ Identifier V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
8 Model_Name V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
9 Firmware_Revision V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
10 Applocation_Software_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
11 Protocol_Version V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
12 Protocol_Revision V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
13 Protocol_Services_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
14 Protocol_Object_Type_Supported V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
15 Object_List V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
16 Max_APDU_Length_Accepted ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
17 Segmentation_Supported ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
18 APDU_Timeout ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 Number_Of_APDU_Retries ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
20 Max_Masters V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
21 Max_Info_Frames V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
22 Device_Address_Binding ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
23 Location V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
24 Presnent_Value ⟦blank source cell⟧ V V V V V V
25 Status_Flags ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
26 Event_State ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
27 Relibility ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
28 Out_Of_Service ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
29 Units ⟦blank source cell⟧ V V V ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
30 Priority_Array ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
31 Relinquish_Default ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
32 Polarity ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
33 Inactive_Text ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
34 Active_Text ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧

Manual — BACnet inverter object properties — page 162

Manual reference: Ver.02, January 2016, physical PDF page 162. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

  1. BACnet Object Properties

This section provides the predetermined configuration of the inverter. User can achieve the optimizazed situation at any necessary modification. Refer to Table 4.1 for the property information of inverter objects and user can learn the inverter messages from the inverter objects. Refer to Table 4.2 ~ Table 4.7 for the related object information that inverter supports. User can control/ read each object with the application requirements.

Table 4.1 – Inverter property list

BACnet inverter object properties

Property / Inverter — PDF page 162

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows)
1 Property Inverter
2 Object_Identifier VFD
3 Object_Name TECO L510s
4 Object_Type 8
5 System_Status 0
6 Vendor_Name TECO L510s
7 Vendor_ Identifier 461
8 Model_Name TECO.Inc
9 Firmware_Revision 0.14
10 Applocation_Software_Supported 0.14
11 Protocol_Version 1
12 Protocol_Revision 5
13 Protocol_Services_Supported { readProperty , writeProperty , who is }
14 Protocol_Object_Type_Supported { Analog_Input , Analog_Output, Analog_Value Binary_ Input, Binary_Output, Binary_Value, Device}
15 Max_Masters 127
16 Max_Info_Frames 1
17 Location R.O.C

Manual — BACnet analog input/output property lists — page 163

Manual reference: Ver.02, January 2016, physical PDF page 163. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Table 4.2 Analog input property list (READ)

Table 4.3 – Analog output property list (READ/ WRITE)

BACnet analog input/output property lists

No. / Object Name / Description / Unit / Classification / Range — PDF page 163

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 AI0 TM2 AVI AVI input Percent R 0 - 100
3 AI1 TM2 ACI ACI input Percent R 0 - 100
4 AI2 Error code Recent fault message No Units R 0 –43
5 AI3 Freq cmd Frequency command HZ R 0 - 599
6 AI4 Frequency Output frequency HZ R 0 -599
7 AI5 Current Output current Amps R ⟦blank source cell⟧
8 AI6 Control Mode Control mode No Units R 0 - 1
9 AI7 Motor R-Volt Motor rated voltage Volt R ⟦blank source cell⟧
10 AI8 Motor R-HP Motor rated power horsepower R ⟦blank source cell⟧
11 AI9 Motor R-RPM Motor rated rotation speed rpm R ⟦blank source cell⟧
12 AI10 Motor R-Hz Motor rated frequency HZ R ⟦blank source cell⟧
13 AI11 CarrierFreq Carrier frequency KiloHertz R 1 - 16
14 AI12 Comm Station INV communication station No Units R 1 – 32
15 AI13 BaudRate Baudrate setting No Units R 0 – 3
16 AI14 BacnetSel Communication mode selection No Units R 0 – 2
17 AI15 DevInstance Inverter number No Units R 1 - 254

No. / Object Name / Description / Unit / Classifica tion / Range — PDF page 163

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classifica tion Range
2 AO0 Set Frequency Frequency command HZ R/W 0 - 599
3 AO1 AO Output voltage Volt R 0 - 10
4 AO3 Motor R-Amp Motor rated current Amps R/W 0-65535
5 AO4 PwrL Sel Momentary stop and restart selection No Units R 0 - 1
6 AO5 RestartSel Number of Fault Auto-Restart Attempts No Units R 0 – 10
7 AO6 RestartDelay Fault Auto-Restart Time seconds R 0 - 800
8 AO7 FreqCommand1 Speed frequency setting-stage 0 HZ R/W 0 - 599
9 AO8 FreqCommand2 Speed frequency setting-stage 1 HZ R/W 0 - 599
10 AO9 FreqCommand3 Speed frequency setting-stage 2 HZ R/W 0 - 599
11 AO10 FreqCommand4 Speed frequency setting-stage 3 HZ R/W 0 - 599
12 AO11 FreqCommand5 Speed frequency setting-stage 4 HZ R/W 0 - 599
13 AO12 FreqCommand6 Speed frequency setting-stage 5 HZ R/W 0 - 599

Manual — BACnet analog/digital property lists — page 164

Manual reference: Ver.02, January 2016, physical PDF page 164. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Table 4.4 Analog value property list (READ/ WRITE)

Table 4.5 Digital input property list (READ)

Table 4.6 Digital output property list (READ/ WRITE)

Table 4.7 Digital value property list (READ/ WRITE)

BACnet analog/digital property lists

No. / Object Name / Description / Unit / Classifica tion / Range — PDF page 164

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classifica tion Range
2 AO13 FreqCommand7 Speed frequency setting-stage 6 HZ R/W 0 - 599
3 AO14 FreqCommand8 Speed frequency setting-stage 7 HZ R/W 0 - 599
4 AO23 RunMode Main run command source selection No Units R/W 0 - 2
5 AO24 ReverseOper Direction locked command No Units R/W 0 - 1
6 AO25 StoppingSel Stop modes selection No Units R/W 0 - 1
7 AO26 FrequenceComm Main frequency command source selection No Units R/W 0 - 6
8 AO27 FreqUpperLim Upper limit frequency HZ R/W 0.01 - 599
9 AO28 FreqLowerLim Lower limit frequency HZ R/W 0 – 598.99
10 AO29 Acc Time1 Acceleration time 1 seconds R/W 0.1 - 3600
11 AO30 Dec Time1 Deceleration time 1 seconds R/W 0.1 - 3600

No. / Object Name / Description / Unit / Classifica tion / Range — PDF page 164

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classifica tion Range
2 AV0 PID – P Gain Proportional gain (P) No Units R/W 0 - 10
3 AV1 PID – I Time Integral time (I) No Units R/W 0 - 100
4 AV2 PID – D Time Differential time (D) No Units R/W 0 – 10

No. / Object Name / Description / Unit / Classifi cation / Range — PDF page 164

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classifi cation Range
2 BI0 Run/Stop Operation status Stop / Run R 0 - 1
3 BI1 Direction Operation direction FWD/REV R 0 - 1
4 BI2 ststus Inverter status OK/Fault R 0 - 1
5 BI3 Abnormal Error occurs Close/Open R 0 - 1
6 BI4 DI_1 status S1 status Close/Open R 0 - 1
7 BI5 DI_2 status S2 status Close/Open R 0 - 1
8 BI6 DI_3 status S3 status Close/Open R 0 - 1
9 BI7 DI_4 status S4 status Close/Open R 0 - 1
10 BI8 DI_5 status S5 status Close/Open R 0 - 1

No. / Object Name / Description / Unit / Classification / Range — PDF page 164

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 BO0 RY1 status Relay output 1 status Close/Open R 0 - 1

No. / Object Name / Description / Unit / Classification / Range — PDF page 164

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows)
1 No. Object Name Description Unit Classification Range
2 BV0 RUN/STOP RUN/STOP Stop / Run R/W 0 - 1
3 BV1 FWD/REV FWD/REV FWD/REV R/W 0 - 1

Manual — USB/RJ45 pin definitions and notices — page 166

Manual reference: Ver.02, January 2016, physical PDF page 166. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

  1. USB Interface Cable Pin Definition

2.1 RS232/USB at PC side.

RS485/RJ45 connector at inverter side.

2.2 RS485/RJ45 Pin Definition.

Note: 1. A/B phase signal (Pin1&Pin2) is differential mode data signal of RS485. 2. VCC&GND is the +5Vdc power supply provided by inverter internal power source.

  1. Notice

3-1. Please turn off the power before you connect the cable.. 3-2. Once inverter is powered off during communication. PC software will show “communication error”. 3-3. If there is any error during communication, please check the wiring connection and restart the pc software.

USB/RJ45 pin definitions and notices

Pin No. / Pin 1 / Pin 2 / Pin 3 / Pin 4 / Pin 5 / Pin 6 / Pin 7 / Pin 8 — PDF page 166

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows) Physical column 5 (source headings retained in rows) Physical column 6 (source headings retained in rows) Physical column 7 (source headings retained in rows) Physical column 8 (source headings retained in rows) Physical column 9 (source headings retained in rows)
1 Pin No. Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8
2 Define A B NC NC NC NC VCC GND

Manual — 510series accessory list — page 167

Manual reference: Ver.02, January 2016, physical PDF page 167. Read these settings with their model/mode, safety requirements and the complete source procedure. These tables are reference data, not a standalone commissioning or repair sequence.

Appendix 5: 510 series accessories manual

510series accessory list

Accessories / Model / Function / Notes — PDF page 167

Source row Physical column 1 (source headings retained in rows) Physical column 2 (source headings retained in rows) Physical column 3 (source headings retained in rows) Physical column 4 (source headings retained in rows)
1 Accessories Model Function Notes
2 Keypad extension cable JN5-CB-01M Keypad extension cable for 510 series 1m
3 Keypad extension cable JN5-CB-02M Keypad extension cable for 510 series 2m
4 Keypad extension cable JN5-CB-03M Keypad extension cable for 510 series 3m
5 Keypad extension cable JN5-CB-05M Keypad extension cable for 510 series 5m
6 Copy module JN5-CU ① Duplicating parameters setting from one inverter to another inverter ② As a remote keypad to be used ③ Using RJ45 line to connect inverter ⟦blank source cell⟧
7 Communication modules JN5-CM-PDP For connection of Profibus-DP communication protocol For 510 series
8 Communication modules JN5-CM-TCP-IP For connection of TCP-IP communication protocol For 510 series
9 Communication modules JN5-CM-DNET For connection of DeviceNet communication protocol For 510 series
10 Communication modules JN5-CM-CAN For connection of CANopen communication protocol For 510 series
11 RJ45 to USB connection cable JN5-CM-USB Using the TECO exclusive PC-software cable 1.8m
12 RJ45 to USB connection cable JN6-CM-USB-3 Using the TECO exclusive PC-software cable 3m
13 EMC Grounding kit(Frame 1) JN5-GK-L01 to enhance the EMC ability by enlarge the ground For frame 1
14 EMC Grounding kit(Frame 2) JN5-GK-L02 to enhance the EMC ability by enlarge the ground For frame 2
15 Din rail (Frame1) JN5-DIN-L01 mounting rails to support the drive For frame 1
16 Din rail (Frame2) JN5-DIN-L02 mounting rails to support the drive For frame 2

Quick setup — parameter groups

The quick setup guide is a summary, not the complete safety or installation manual. Its run-command default differs from the manual, as noted above.

Parameter groups — PDF page 1

Source column 1 Source column 2
PARAMENTER GROUP No. Description
Group 00 Basic parameter
Group 01 V/F Pattern selections and set up
Group 02 Motor parameters
Group 03 Multi function digital Inputs/Outputs
Group 04 Analog signal inputs / Analog output
Group 05 Present frequency selections
Group 06 Auto Run (auto sequencer) function
Group 07 Start/Stop command setup
Group 08 Drive and motor protection
Group 09 Communication function setup
Group 10 PID function setup
Group 11 Performance control functions
Group 12 Digital display & monitor functions
Group 13 Inspector and maintenance function

Technical source 001 — Variable speed drive L510s-2P2-SH1F-P /IP20/ 0.2KW/ 0.25HP/ 200-240V

Source download: DataSheet_of_L510-2P2-SH1F-P.pdf.

Source differences and limitations

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P005, Variable speed drive L510s-2P2-SH1F-P /IP20/ 0.2KW/ 0.25HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
92 / 1 / 1 Constant Torque (kW/A): 0.2 / 1.8; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 0.20 Datasheet / DataSheet_of_L510-2P2-SH1F-P.pdf
92 / 2 / 2 Constant Torque (kW/A): 0.37 / 2.6; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 0.37 Datasheet / DataSheet_of_L510-2P2-SH1F-P.pdf

P005 / Variable speed drive L510s-2P2-SH1F-P /IP20/ 0.2KW/ 0.25HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name L510s as printed in field/value —
Horse Power(HP) 0.25 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.2 as printed in field/value —
Rated Output Current(A) 1.8 as printed in field/value —
Rated Capacity(KVA) 0.7 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 4.9 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.15Hz/60Hz or 0.012Hz/50Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR (potentiometer) on the keypad External input terminals:AVI(0/2-10V), ACI(0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 6 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz (default 5kHz) as printed in field/value —
Main Control Features / Acceleration and / Deceleration / Control 2 sections of acceleration /deceleration. 4 of S curve parameters. as printed in field/value —
Main Control Features / Multifunction Input 19 functions (refer to group3 in the manual). as printed in field/value —
Main Control Features / Multifunction / Relay Output 16 functions (refer to group3 in the manual). as printed in field/value —

P005 / Variable speed drive L510s-2P2-SH1F-P /IP20/ 0.2KW/ 0.25HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction 5 functions (refer to group4 in the manual), as printed in field/value —
Analog Output 1 point (0-10V). as printed in field/value —
Main Features Overload detection, 8 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset. as printed in field/value —
Display / LED Display: Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse. as printed in field/value —
Protective Functions / Overload Capacity 150% for 1min every 10 min. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, Fault output, Reverse prohibit, Number of restart attempt, Parameter lock, PTC over temperature protection, Over voltage suppression function. as printed in field/value —
Environment / Operating –10 ~ 50℃ with fan, as printed in field/value —
Environment / temperature –10 ~ 40℃ without fan, as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Vibration Frequency: 10Hz - 150Hz - 10Hz Amplitude(0.3mm): 10Hz ≦f ≦57Hz Acceleration(2G): 57Hz ≦f ≦150Hz (According to IEC60068-2-6 standard) as printed in field/value —
Environment / EMC Compliance EN61800-3, First Environment. as printed in field/value —
Environment / LVD Compliance EN50178 as printed in field/value —
Environment / Electrical Safety UL508C as printed in field/value —
Environment / Protection Level IP 20 as printed in field/value —

P005 / Variable speed drive L510s-2P2-SH1F-P /IP20/ 0.2KW/ 0.25HP/ 200-240V — source page 4 — PDF page 4

Specification Value Unit / basis Conditions
Terminal symbols TM1 Function Description as printed in field/value —
L1(L) / L2 / L3(N) Main power input, single phase: L1(L) / L3(N) as printed in field/value —
P* / BR* N/A as printed in field/value —
T1 / T2 / T3 Inverter output, connect to U, V, W terminals of motor as printed in field/value —

P005 / Variable speed drive L510s-2P2-SH1F-P /IP20/ 0.2KW/ 0.25HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2 NW (kg) Conditions
L510-2P2-SH1F-P 72 mm 63 mm 61 mm 141 mm 122 mm 131 mm 114 mm 141 mm 136 mm 128.2 mm 86.3 mm 81.1 mm 55 mm 4.4 mm 2.2 mm 1.0 kg —

Technical source 002 — Variable speed drive L510s-201-SH1F-P /IP20/ 0.75KW/ 1HP/ 200-240V

Source download: DataSheet_of_L510-201-SH1F-P.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P005, Variable speed drive L510s-201-SH1F-P /IP20/ 0.75KW/ 1HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
92 / 3 / 3 Constant Torque (kW/A): 0.75 / 4.3; Supply: 200-240V 1PH; IP Rating: IP20; kW Rating: 0.75 Datasheet / DataSheet_of_L510-201-SH1F-P.pdf

P005 / Variable speed drive L510s-201-SH1F-P /IP20/ 0.75KW/ 1HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name L510s as printed in field/value —
Horse Power(HP) 1 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.75 as printed in field/value —
Rated Output Current(A) 4.3 as printed in field/value —
Rated Capacity(KVA) 1.7 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 11 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.15Hz/60Hz or 0.012Hz/50Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR (potentiometer) on the keypad External input terminals:AVI(0/2-10V), ACI(0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 6 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz (default 5kHz) as printed in field/value —
Main Control Features / Acceleration and / Deceleration / Control 2 sections of acceleration /deceleration. 4 of S curve parameters. as printed in field/value —
Main Control Features / Multifunction Input 19 functions (refer to group3 in the manual). as printed in field/value —
Main Control Features / Multifunction / Relay Output 16 functions (refer to group3 in the manual). as printed in field/value —

P005 / Variable speed drive L510s-201-SH1F-P /IP20/ 0.75KW/ 1HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction 5 functions (refer to group4 in the manual), as printed in field/value —
Analog Output 1 point (0-10V). as printed in field/value —
Main Features Overload detection, 8 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset. as printed in field/value —
Display / LED Display: Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse. as printed in field/value —
Protective Functions / Overload Capacity 150% for 1min every 10 min. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, Fault output, Reverse prohibit, Number of restart attempt, Parameter lock, PTC over temperature protection, Over voltage suppression function. as printed in field/value —
Environment / Operating –10 ~ 50℃ with fan, as printed in field/value —
Environment / temperature –10 ~ 40℃ without fan, as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Vibration Frequency: 10Hz - 150Hz - 10Hz Amplitude(0.3mm): 10Hz ≦f ≦57Hz Acceleration(2G): 57Hz ≦f ≦150Hz (According to IEC60068-2-6 standard) as printed in field/value —
Environment / EMC Compliance EN61800-3, First Environment. as printed in field/value —
Environment / LVD Compliance EN50178 as printed in field/value —
Environment / Electrical Safety UL508C as printed in field/value —
Environment / Protection Level IP 20 as printed in field/value —

P005 / Variable speed drive L510s-201-SH1F-P /IP20/ 0.75KW/ 1HP/ 200-240V — source page 4 — PDF page 4

Specification Value Unit / basis Conditions
Terminal symbols TM1 Function Description as printed in field/value —
L1(L) / L2 / L3(N) Main power input, single phase: L1(L) / L3(N) as printed in field/value —
P* / BR* N/A as printed in field/value —
T1 / T2 / T3 Inverter output, connect to U, V, W terminals of motor as printed in field/value —

P005 / Variable speed drive L510s-201-SH1F-P /IP20/ 0.75KW/ 1HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2 NW (kg) Conditions
L510-201-SH1F-P 72 mm 63 mm 61 mm 141 mm 122 mm 131 mm 114 mm 141 mm 136 mm 128.2 mm 86.3 mm 81.1 mm 55 mm 4.4 mm 2.2 mm 1.0 kg —

Technical source 003 — Variable speed drive L510s-202-SH1F-P /IP20/ 1.5KW/ 2HP/ 200-240V

Source download: DataSheet_of_L510-202-SH1F-P.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P005, Variable speed drive L510s-202-SH1F-P /IP20/ 1.5KW/ 2HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
92 / 4 / 4 Constant Torque (kW/A): 1.5 / 7.5; Supply: 200-240v 1PH; IP Rating: IP20; kW Rating: 1.50 Datasheet / DataSheet_of_L510-202-SH1F-P.pdf

P005 / Variable speed drive L510s-202-SH1F-P /IP20/ 1.5KW/ 2HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name L510s as printed in field/value —
Horse Power(HP) 2 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value —
Rated Output Current(A) 7.5 as printed in field/value —
Rated Capacity(KVA) 3.0 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 15.5 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.15Hz/60Hz or 0.012Hz/50Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR (potentiometer) on the keypad External input terminals:AVI(0/2-10V), ACI(0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 6 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz (default 5kHz) as printed in field/value —
Main Control Features / Acceleration and / Deceleration / Control 2 sections of acceleration /deceleration. 4 of S curve parameters. as printed in field/value —
Main Control Features / Multifunction Input 19 functions (refer to group3 in the manual). as printed in field/value —
Main Control Features / Multifunction / Relay Output 16 functions (refer to group3 in the manual). as printed in field/value —

P005 / Variable speed drive L510s-202-SH1F-P /IP20/ 1.5KW/ 2HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction 5 functions (refer to group4 in the manual), as printed in field/value —
Analog Output 1 point (0-10V). as printed in field/value —
Main Features Overload detection, 8 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset. as printed in field/value —
Display / LED Display: Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse. as printed in field/value —
Protective Functions / Overload Capacity 150% for 1min every 10 min. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, Fault output, Reverse prohibit, Number of restart attempt, Parameter lock, PTC over temperature protection, Over voltage suppression function. as printed in field/value —
Environment / Operating –10 ~ 50℃ with fan, as printed in field/value —
Environment / temperature –10 ~ 40℃ without fan, as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Vibration Frequency: 10Hz - 150Hz - 10Hz Amplitude(0.3mm): 10Hz ≦f ≦57Hz Acceleration(2G): 57Hz ≦f ≦150Hz (According to IEC60068-2-6 standard) as printed in field/value —
Environment / EMC Compliance EN61800-3, First Environment. as printed in field/value —
Environment / LVD Compliance EN50178 as printed in field/value —
Environment / Electrical Safety UL508C as printed in field/value —
Environment / Protection Level IP 20 as printed in field/value —

P005 / Variable speed drive L510s-202-SH1F-P /IP20/ 1.5KW/ 2HP/ 200-240V — source page 4 — PDF page 4

Specification Value Unit / basis Conditions
Terminal symbols TM1 Function Description as printed in field/value —
L1(L) / L2 / L3(N) Main power input, single phase: L1(L) / L3(N) as printed in field/value —
P* / BR* N/A as printed in field/value —
T1 / T2 / T3 Inverter output, connect to U, V, W terminals of motor as printed in field/value —

P005 / Variable speed drive L510s-202-SH1F-P /IP20/ 1.5KW/ 2HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2 NW (kg) Conditions
L510-202-SH1F-P 118 mm 108 mm 108 mm 144 mm 121 mm 131 mm 114 mm 150 mm 144.2 mm 136.4 mm 101.32 mm 96.73 mm 51.5 mm 4.4 mm 2.2 mm 1.5 kg —

Technical source 004 — Variable speed drive L510s-203-SH1F-P /IP20/ 2.2KW/ 3HP/ 200-240V

Source download: DataSheet_of_L510-203-SH1F-P.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P005, Variable speed drive L510s-203-SH1F-P /IP20/ 2.2KW/ 3HP/ 200-240V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
92 / 5 / 5 Constant Torque (kW/A): 2.2 / 10.5; Supply: 200-240v 1PH; IP Rating: IP20; kW Rating: 2.20 Datasheet / DataSheet_of_L510-203-SH1F-P.pdf

P005 / Variable speed drive L510s-203-SH1F-P /IP20/ 2.2KW/ 3HP/ 200-240V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name L510s as printed in field/value —
Horse Power(HP) 3 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 2.2 as printed in field/value —
Rated Output Current(A) 10.5 as printed in field/value —
Rated Capacity(KVA) 4.0 as printed in field/value —
Input Voltage Range(V) Single-phase 200~ 240V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~240V as printed in field/value —
Input current(A) 21 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.15Hz/60Hz or 0.012Hz/50Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR (potentiometer) on the keypad External input terminals:AVI(0/2-10V), ACI(0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 6 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz (default 5kHz) as printed in field/value —
Main Control Features / Acceleration and / Deceleration / Control 2 sections of acceleration /deceleration. 4 of S curve parameters. as printed in field/value —
Main Control Features / Multifunction Input 19 functions (refer to group3 in the manual). as printed in field/value —
Main Control Features / Multifunction / Relay Output 16 functions (refer to group3 in the manual). as printed in field/value —

P005 / Variable speed drive L510s-203-SH1F-P /IP20/ 2.2KW/ 3HP/ 200-240V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction 5 functions (refer to group4 in the manual), as printed in field/value —
Analog Output 1 point (0-10V). as printed in field/value —
Main Features Overload detection, 8 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset. as printed in field/value —
Display / LED Display: Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse. as printed in field/value —
Protective Functions / Overload Capacity 150% for 1min every 10 min. as printed in field/value —
Protective Functions / Over Voltage 200V class :DC>410V, as printed in field/value —
Protective Functions / Under Voltage 200V class :DC<190V, as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, Fault output, Reverse prohibit, Number of restart attempt, Parameter lock, PTC over temperature protection, Over voltage suppression function. as printed in field/value —
Environment / Operating –10 ~ 50℃ with fan, as printed in field/value —
Environment / temperature –10 ~ 40℃ without fan, as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Vibration Frequency: 10Hz - 150Hz - 10Hz Amplitude(0.3mm): 10Hz ≦f ≦57Hz Acceleration(2G): 57Hz ≦f ≦150Hz (According to IEC60068-2-6 standard) as printed in field/value —
Environment / EMC Compliance EN61800-3, First Environment. as printed in field/value —
Environment / LVD Compliance EN50178 as printed in field/value —
Environment / Electrical Safety UL508C as printed in field/value —
Environment / Protection Level IP 20 as printed in field/value —

P005 / Variable speed drive L510s-203-SH1F-P /IP20/ 2.2KW/ 3HP/ 200-240V — source page 4 — PDF page 4

Specification Value Unit / basis Conditions
Terminal symbols TM1 Function Description as printed in field/value —
L1(L) / L2 / L3(N) Main power input, single phase: L1(L) / L3(N) as printed in field/value —
P* / BR* N/A as printed in field/value —
T1 / T2 / T3 Inverter output, connect to U, V, W terminals of motor as printed in field/value —

P005 / Variable speed drive L510s-203-SH1F-P /IP20/ 2.2KW/ 3HP/ 200-240V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2 NW (kg) Conditions
L510-203-SH1F-P 118 mm 108 mm 108 mm 144 mm 121 mm 131 mm 114 mm 150 mm 144.2 mm 136.4 mm 101.32 mm 96.73 mm 51.5 mm 4.4 mm 2.2 mm 1.5 kg —

Technical source 005 — Variable speed drive L510s-401-SH3F-P /IP20/ 0.75KW/ 1HP/ 380-480V

Source download: DataSheet_of_L510-401-SH3F-P.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P005, Variable speed drive L510s-401-SH3F-P /IP20/ 0.75KW/ 1HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
92 / 6 / 6 Constant Torque (kW/A): 0.75 / 2.3; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 0.75 Datasheet / DataSheet_of_L510-401-SH3F-P.pdf

P005 / Variable speed drive L510s-401-SH3F-P /IP20/ 0.75KW/ 1HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name L510s as printed in field/value —
Horse Power(HP) 1 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 0.75 as printed in field/value —
Rated Output Current(A) 2.3 as printed in field/value —
Rated Capacity(KVA) 1.7 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 4.2 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.15Hz/60Hz or 0.012Hz/50Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR (potentiometer) on the keypad External input terminals:AVI(0/2-10V), ACI(0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 6 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz (default 5kHz) as printed in field/value —
Main Control Features / Acceleration and / Deceleration / Control 2 sections of acceleration /deceleration. 4 of S curve parameters. as printed in field/value —
Main Control Features / Multifunction Input 19 functions (refer to group3 in the manual). as printed in field/value —
Main Control Features / Multifunction / Relay Output 16 functions (refer to group3 in the manual). as printed in field/value —

P005 / Variable speed drive L510s-401-SH3F-P /IP20/ 0.75KW/ 1HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction 5 functions (refer to group4 in the manual), as printed in field/value —
Analog Output 1 point (0-10V). as printed in field/value —
Main Features Overload detection, 8 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset. as printed in field/value —
Display / LED Display: Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse. as printed in field/value —
Protective Functions / Overload Capacity 150% for 1min every 10 min. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, Fault output, Reverse prohibit, Number of restart attempt, Parameter lock, PTC over temperature protection, Over voltage suppression function. as printed in field/value —
Environment / Operating –10 ~ 50℃ with fan, as printed in field/value —
Environment / temperature –10 ~ 40℃ without fan, as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Vibration Frequency: 10Hz - 150Hz - 10Hz Amplitude(0.3mm): 10Hz ≦f ≦57Hz Acceleration(2G): 57Hz ≦f ≦150Hz (According to IEC60068-2-6 standard) as printed in field/value —
Environment / EMC Compliance EN61800-3, First Environment. as printed in field/value —
Environment / LVD Compliance EN50178 as printed in field/value —
Environment / Electrical Safety UL508C as printed in field/value —
Environment / Protection Level IP 20 as printed in field/value —

P005 / Variable speed drive L510s-401-SH3F-P /IP20/ 0.75KW/ 1HP/ 380-480V — source page 4 — PDF page 4

Specification Value Unit / basis Conditions
Terminal symbols TM1 Function Description as printed in field/value —
L1(L) / L2 / L3(N) Main power input, three phase(400V): L1 / L2 / L3 as printed in field/value —
P* / BR* External braking resistor as printed in field/value —
T1 / T2 / T3 Inverter output, connect to U, V, W terminals of motor as printed in field/value —

P005 / Variable speed drive L510s-401-SH3F-P /IP20/ 0.75KW/ 1HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2 NW (kg) Conditions
L510-401-SH3F-P 118 mm 108 mm 108 mm 144 mm 121 mm 131 mm 114 mm 150 mm 144.2 mm 136.4 mm 101.32 mm 96.73 mm 51.5 mm 4.3 mm 118 mm 1.5 kg —

Technical source 006 — Variable speed drive L510s-402-SH3F-P /IP20/ 1.5KW/ 2HP/ 380-480V

Source download: DataSheet_of_L510-402-SH3F-P.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P005, Variable speed drive L510s-402-SH3F-P /IP20/ 1.5KW/ 2HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
92 / 7 / 7 Constant Torque (kW/A): 1.5 / 3.8; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 1.50 Datasheet / DataSheet_of_L510-402-SH3F-P.pdf

P005 / Variable speed drive L510s-402-SH3F-P /IP20/ 1.5KW/ 2HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name L510s as printed in field/value —
Horse Power(HP) 2 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 1.5 as printed in field/value —
Rated Output Current(A) 3.8 as printed in field/value —
Rated Capacity(KVA) 2.9 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 5.6 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.15Hz/60Hz or 0.012Hz/50Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR (potentiometer) on the keypad External input terminals:AVI(0/2-10V), ACI(0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 6 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz (default 5kHz) as printed in field/value —
Main Control Features / Acceleration and / Deceleration / Control 2 sections of acceleration /deceleration. 4 of S curve parameters. as printed in field/value —
Main Control Features / Multifunction Input 19 functions (refer to group3 in the manual). as printed in field/value —

P005 / Variable speed drive L510s-402-SH3F-P /IP20/ 1.5KW/ 2HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction / Relay Output 16 functions (refer to group3 in the manual). as printed in field/value —
Multifunction 5 functions (refer to group4 in the manual), as printed in field/value —
Analog Output 1 point (0-10V). as printed in field/value —
Main Features Overload detection, 8 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset. as printed in field/value —
Display / LED Display: Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse. as printed in field/value —
Protective Functions / Overload Capacity 150% for 1min every 10 min. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Momentary Power / Loss Restart Inverter auto-restart after a momentary power loss. as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Short-circuit Output / Terminal Electronic Circuit Protection. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, Fault output, Reverse prohibit, Number of restart attempt, Parameter lock, PTC over temperature protection, Over voltage suppression function. as printed in field/value —
Environment / Operating –10 ~ 50℃ with fan, as printed in field/value —
Environment / temperature –10 ~ 40℃ without fan, as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Vibration Frequency: 10Hz - 150Hz - 10Hz Amplitude(0.3mm): 10Hz ≦f ≦57Hz Acceleration(2G): 57Hz ≦f ≦150Hz (According to IEC60068-2-6 standard) as printed in field/value —
Environment / EMC Compliance EN61800-3, First Environment. as printed in field/value —
Environment / LVD Compliance EN50178 as printed in field/value —
Environment / Electrical Safety UL508C as printed in field/value —
Environment / Protection Level IP 20 as printed in field/value —

P005 / Variable speed drive L510s-402-SH3F-P /IP20/ 1.5KW/ 2HP/ 380-480V — source page 4 — PDF page 4

Specification Value Unit / basis Conditions
Terminal symbols TM1 Function Description as printed in field/value —
L1(L) / L2 / L3(N) Main power input, three phase(400V): L1 / L2 / L3 as printed in field/value —
P* / BR* External braking resistor as printed in field/value —
T1 / T2 / T3 Inverter output, connect to U, V, W terminals of motor as printed in field/value —

P005 / Variable speed drive L510s-402-SH3F-P /IP20/ 1.5KW/ 2HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2 NW (kg) Conditions
L510-402-SH3F-P 118 mm 108 mm 108 mm 144 mm 121 mm 131 mm 114 mm 150 mm 144.2 mm 136.4 mm 101.32 mm 96.73 mm 51.5 mm 4.3 mm 118 mm 1.5 kg —

Technical source 007 — Variable speed drive L510s-403-SH3F-P /IP20/ 2.2KW/ 3HP/ 380-480V

Source download: DataSheet_of_L510-403-SH3F-P.pdf.

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Dimensions by printed model — P005, Variable speed drive L510s-403-SH3F-P /IP20/ 2.2KW/ 3HP/ 380-480V, page 5

No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.

Website associations for this source

Table / row / row ID Listed specification Document role / member
92 / 8 / 8 Constant Torque (kW/A): 2.2 / 5.2; Supply: 380-480V 3PH; IP Rating: IP20; kW Rating: 2.20 Datasheet / DataSheet_of_L510-403-SH3F-P.pdf

P005 / Variable speed drive L510s-403-SH3F-P /IP20/ 2.2KW/ 3HP/ 380-480V — source page 1 — PDF page 1

Specification Value Unit / basis Conditions
Component name L510s as printed in field/value —
Horse Power(HP) 3 as printed in field/value —
Suitable Motor Capacity Capacity(KW) 2.2 as printed in field/value —
Rated Output Current(A) 5.2 as printed in field/value —
Rated Capacity(KVA) 4.0 as printed in field/value —
Input Voltage Range(V) Three-phase 380~ 480V, 50/60Hz as printed in field/value —
Allowable Voltage Fluctuation -15%~ +10% as printed in field/value —
Output Voltage range(V) Three-phase 0~480V as printed in field/value —
Input current(A) 7.3 as printed in field/value —
Enclosure IP 20 as printed in field/value —
Control Mode V/F, SLV, as printed in field/value —
Frequency / Output Frequency 0.01~599.00Hz (V/Hz) as printed in field/value —
Frequency / Starting Torque 150%/3Hz(V/F), 150%/1Hz(Vector) as printed in field/value —
Frequency / Setting Resolution Digital input: 0.01Hz Analog input:0.15Hz/60Hz or 0.012Hz/50Hz as printed in field/value —
Frequency / Setting Keypad: Set directly with▲▼ keys or the VR (potentiometer) on the keypad External input terminals:AVI(0/2-10V), ACI(0/4-20mA), Embedded potentiometer, Multifunction input UP/DOWN, Setting frequency by communication method. as printed in field/value —
Frequency / Frequency Limit Lower and upper frequency limits, 3 skip frequency settings. as printed in field/value —
Run / Operation Set Keypad Run, Stop button. External terminals: Multi- operation-mode(2 or 3 wire selection), Jog operation. Run signal by communication method. as printed in field/value —
Main Control Features / V/F Curve Setting 6 fixed curves and 1 customized curve. as printed in field/value —
Main Control Features / Carrier Frequency 1~16KHz (default 5kHz) as printed in field/value —
Main Control Features / Acceleration and / Deceleration / Control 2 sections of acceleration /deceleration. 4 of S curve parameters. as printed in field/value —
Main Control Features / Multifunction Input 19 functions (refer to group3 in the manual). as printed in field/value —
Main Control Features / Multifunction / Relay Output 16 functions (refer to group3 in the manual). as printed in field/value —

P005 / Variable speed drive L510s-403-SH3F-P /IP20/ 2.2KW/ 3HP/ 380-480V — source page 2 — PDF page 2

Specification Value Unit / basis Conditions
Multifunction 5 functions (refer to group4 in the manual), as printed in field/value —
Analog Output 1 point (0-10V). as printed in field/value —
Main Features Overload detection, 8 pre-set speeds, Auto-run, Acc/Dec switch(2 stages), Main/Alt run command select, Main/Alt frequency command select, PID control, Torque boost, V/F Start frequency, Fault reset. as printed in field/value —
Display / LED Display: Parameter, Parameter value, Frequency, Line speed, DC voltage, Output voltage, Output current, PID feedback, Input and output terminal status, Heat sink temperature, Firmware version, Fault list. as printed in field/value —
Display / LED Status Indicador Run / Stop / Forward / Reverse. as printed in field/value —
Protective Functions / Overload Capacity 150% for 1min every 10 min. as printed in field/value —
Protective Functions / Over Voltage 400V class :DC>820V, as printed in field/value —
Protective Functions / Under Voltage 400V class :DC<380V, as printed in field/value —
Protective Functions / Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation. as printed in field/value —
Protective Functions / Grounding Fault Electronic Circuit Protection. as printed in field/value —
Protective Functions / Other Protection Functions Heatsink over temperature protection, Auto carrier frequency reduction with temperature rise, Fault output, Reverse prohibit, Number of restart attempt, Parameter lock, PTC over temperature protection, Over voltage suppression function. as printed in field/value —
Environment / Operating –10 ~ 50℃ with fan, as printed in field/value —
Environment / temperature –10 ~ 40℃ without fan, as printed in field/value —
Environment / Storage temperature -20~ 60℃ as printed in field/value —
Environment / Humidity 95% RH or less (no condensation) Compliance with IEC 60068 -2-78. as printed in field/value —
Environment / Vibration Frequency: 10Hz - 150Hz - 10Hz Amplitude(0.3mm): 10Hz ≦f ≦57Hz Acceleration(2G): 57Hz ≦f ≦150Hz (According to IEC60068-2-6 standard) as printed in field/value —
Environment / EMC Compliance EN61800-3, First Environment. as printed in field/value —
Environment / LVD Compliance EN50178 as printed in field/value —
Environment / Electrical Safety UL508C as printed in field/value —
Environment / Protection Level IP 20 as printed in field/value —

P005 / Variable speed drive L510s-403-SH3F-P /IP20/ 2.2KW/ 3HP/ 380-480V — source page 4 — PDF page 4

Specification Value Unit / basis Conditions
Terminal symbols TM1 Function Description as printed in field/value —
L1(L) / L2 / L3(N) Main power input, three phase(400V): L1 / L2 / L3 as printed in field/value —
P* / BR* External braking resistor as printed in field/value —
T1 / T2 / T3 Inverter output, connect to U, V, W terminals of motor as printed in field/value —

P005 / Variable speed drive L510s-403-SH3F-P /IP20/ 2.2KW/ 3HP/ 380-480V — source page 5 — PDF page 5

Configuration / printed row W W1 W2 H H1 H2 H3 D D1 D2 E E1 E2 Q1 Q2 NW (kg) Conditions
L510-403-SH3F-P 118 mm 108 mm 108 mm 144 mm 121 mm 131 mm 114 mm 150 mm 144.2 mm 136.4 mm 101.32 mm 96.73 mm 51.5 mm 4.3 mm 118 mm 1.5 kg —

Selection checks and source differences

Website row 2 (0.37 kW) links to the 0.2 kW 2P2 sheet; the catalogue 2P5 rating is 0.4 kW. All eight associations remain intact; no missing 0.37 kW datasheet has been invented.

Local range and short-brochure limits differ from the global catalogue/manual. Built-in filter wording is conditional on the F suffix, and NPN/PNP arrangements differ by frame.

Manual 00-02 factory default is keypad (0); quick guide says external control (1) is default. Verify the actual unit before a run command.

Manual Group 04 index reverses AVI/ACI column headings versus the detailed page. Frequency figure 650.00 differs from 599.00 Hz limits. HP code08 has 7.5 versus8 HP wording. Thermal carrier prose says reduced by4K while its figure shows10K to4K. No invented reconciliation.

Dimensions retain edition-specific H1/H2 order, frame-2 voltage groups and hole sizes. Some listed models have no matching outline row; no missing dimensions or model suffixes are inferred.

Cable-temperature statements differ:105°C in general wiring,60/75°C in control-cable prose and80°C in the UL appendix. EMC C1/C2 statements, optional grounding-kit conditions and filter disconnection require the actual installation requirements.

Analogue resolution is0.15Hz/60Hz in individual sheets versus0.015Hz/60Hz in catalogue/manual. Braking-table205/405 power is3.5kW versus3.7kW ratings. Retain source-specific values.

Manual general multi-motor overload instructions differ from the UL appendix. Stop/emergency-stop wording is ambiguous; none is promoted as a certified machine safety function.

Manual cable diagram135 prints180.0±1.5 without units whereas165 prints1800±1.5mm; prose says1.8m. CAN module manual reference also contains VAN spelling. Preserve literal references and confirm accessories.

Small raster labels, a garbled troubleshooting decision and malformed figure glyphs remain unresolved in the source audit. No unprinted wiring, chart interpolation, certificate validity or engineering approval is inferred.

Product documents