TECO Emotron Soft Starter — TSA Source Guide
Our Emotron TSA softstarter combines controlled starting and stopping with integrated bypass, load monitoring and operator functions for applications that do not require continuous variable-speed control.
Product identity needs confirmation: the TECO page is titled “TECO Emotron Soft Starter” and links to the TSA manual, but its feature text repeats the MSF range's 4 kW–1.6 MW and 17–835 A/1000–1400 A enclosure groups. This guide identifies TSA facts from the TSA documents and keeps the conflicting website description separate. We do not present MSF values as TSA ratings.
Select by current, supply and start duty
The shared catalogue's TSA headline is 4 kW–1.8 MW, 200–690 V, three-phase, with integrated bypass. Its detailed selection tables in this edition list 16–450 models, while broader feature text describes IP20 sizes 16–820 A and IP00 sizes 1000–1800 A. Those headlines do not supply missing model ratings or dimensions.
TSA selection uses AC53b duty. The catalogue defines normal duty at 3×In_soft and heavy duty at 5×In_soft, with 15-second starts for size 1, 30 seconds for sizes 2–4, and 10 starts/hour. The manual's corresponding footnote mentions sizes 2–6. Keep the relevant edition, frame and start conditions with each current/power value. kW columns at 400/525/690 V and hp columns at 460/575 V must not be combined or converted into unprovided ratings.
The 170-page TSA manual is 01-5980-01r0, software1.0X. Its size 1 examples show TSA52-016 at 16 A normal duty and 10 A heavy duty, illustrating why a model number alone is not a heavy-duty capacity. Use the supplied unit's software and type label before applying parameters or options.
Controlled starts, stops and monitoring
Three-phase torque control supports smooth starts and pump stops intended to reduce water hammer. The source also describes high-inertia braking, forward/reverse jog, real-time clock, multilingual control and load monitoring. Jog is a limited function, not a general variable-speed-drive capability. Braking and reversing require the correct system arrangement and load assessment.
Motor I²t protection and isolated thermistor input are listed as standard; PT100 capability requires the specified option. Parameter groups retain motor data, process scaling, torque/current control, protection, I/O, logic, timers, operating records and communication settings. Actual alarm actions, start permissions and reset behaviour must be commissioned for the installation. Sample display values do not establish live motor measurements.
Environment and installation dimensions
The shared catalogue's nominal ambient is 0–40°C. TSA's manual permits operation to 55°C with 2% current derating per°C above 40°C. It describes altitude to 1, 000m without derating, then1% per100m to 4, 000m. No combined derating calculation has been supplied here. Source coating and contamination classes do not override enclosure or site restrictions.
TSA dimensions distinguish H1 enclosure height from H2 total height. There is a concrete edition difference: the catalogue's size 1/2 schedule gives 246/340 mm, whereas the manual's size 1 table gives 246/296 mm. We preserve both and require the approved outline for mounting. The smallest convection-cooled units are vertical-only; larger fan-cooled groups have separate orientation limits.
Controls and expansion
The general catalogue table gives control supply 100–240 V+10%/−15%, while the interface page and manual connection table say 100–240VAC±10%. Confirm the actual nameplate and approved connection data rather than using the more permissive tolerance.
TSA supports two option boards plus one communication option in the catalogue. The maximum of two I/O boards or two PTC/PT100 boards sits within that total; it does not mean four boards can be installed together. Communications options include the separately identified Profibus, DeviceNet, Modbus/TCP, EtherCAT, Profinet, USB and RS485 modules. Listed10ms responses exclude the stated network delays.
The external-panel IP54 claim is for the cabinet-door kit. TSA's standard coated boards, supply outputs and relay-terminal mapping differ from MSF. In particular, TSA relay3 has32C/33NC; the MSF schedule reverses those roles. All relays must meet the manual's common external-supply constraints; no cross-family pinout has been inferred.
Source qualifications
The catalogue's TSA cULus logo is explicitly marked Pending. That historical statement is not promoted to certification. The MSF heading on the EmoSoftCom page conflicts with TSA wording below it. Product identity, control-supply tolerance, total height, software compatibility and approval scope remain checks for the selected assembly.
Installation and source references
Use qualified personnel and the complete selected-model manual for supply isolation, earthing, fuses, mounting clearances, cooling, connections and commissioning. A soft stop or disabled run command is not electrical isolation. The source fuse tables distinguish load protection, semiconductor protection and historical UL/cUL conditions; a part code printed under an ampere heading is not a numeric fuse rating.
The shared 24-page catalogue is 01-5552-01r1, English2014-09. Both named families remain in its reference section, clearly separated; association with this page does not transfer one family's terminals, options, ratings or approvals to the other. Diagrams remain in the original PDFs. Blank fields, unspecified units, pending approvals and unresolved source references remain explicit.
Our reference tables retain all collected model, voltage, duty, dimension, interface and parameter data, with exact source editions. No individual website drawing table was attached to this product in the collection. The catalogue's external CAD references do not prove that a model-specific CAD file was collected. Share the motor nameplate, load inertia, starting current/time, starts per hour, supply and environment so we can confirm your selection.
Catalogue — Technical Catalogue Softstarters cover — page 1
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 1
Context: Cover ranges are supplier headline ranges, not validated per-model ratings. Small photographic display details are outside this text rendition.
Table conditions: Literal cover ranges. Model selection/current tables elsewhere not reviewed in this batch; no extrapolation.
Cover family ranges — PDF page 1
| Family | Cover power range | Cover voltage range |
|---|---|---|
| Emotron TSA | 4–1800kW | 200–690V |
| Emotron MSF2.0 | 7.5–1500kW | 200–690V |
Catalogue — Emotron TSA / PDF 2 — page 2
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 2
Emotron TSA softstarter - with built-in bypass
Main features
16 - 56 A
70 - 100 A
140 - 200 A
240 - 450 A
(Pending)
GOST R
• Compact and robust softstarter with wide power range:
4kW - 1.8 MW, 200 - 690V, 3 ph.
• Integrated bypass with proven contactor technology.
• 3-phase torque control for optimal performance.
• Torque control start and stop modes for smooth low-current starts and
pump stops without water hammering.
• High capacity dynamic vector braking available for high inertia stopping.
• Coated boards as standard extends lifetime in harsh environments.
• Real-time clock.
• Multilingual control panel.
• Jog forward/reverse with adjustable speed.
• Motor I2t protection and isolated thermistor input as standard. PT100
inputs as option.
• Load monitor function for protection of your load machinery.
• IP20 protection for sizes 16-820 A, IP00 for sizes 1000 - 1800 A.
• Fulfills EMC First environment-category C2.
Emotron TSA softstarters take
motor control to a new level. Soft
torque starting, intelligent load
monitoring and smart stops are all
included and accompanied by a
robust and compact design. By
developing the Emotron TSA range
of electronic softstarters CG has
taken a major step towards the
ideal motor controller for
applications where variable speed
is not required. You simply get
everything except variable speed!
Supplier logo panel shows CE, cULus with the qualifier (Pending), and GOST R. The pending qualifier belongs to the UL logo, not to all feature claims. This is historical catalogue text, not evidence of current certification.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Catalogue — Emotron TSA / PDF 3 — page 3
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 3
Emotron TSA softstarter with integrated bypass
Typical motor power at mains voltage 400 V and 460 V
Rating according to AC53b norm.
(1) Normal duty: Start current = 3 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(2) Heavy duty: Start current = 5 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(3) H1= Height of enclosure, H2=Total height
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: Emotron TSA; 400 V / 460 V. AC53b: normal starting current 3 x In_soft; heavy 5 x In_soft. Start time 15 s for size1, 30 s for sizes2–4;10 starts/hour. H1 enclosure height; H2 total height.
Emotron TSA specifications — PDF page 3
| Model | Normal duty: Power @400 V (kW) | Normal duty: Power @460 V (hp) | Normal duty: Rated current (A) | Heavy duty: Power @400 V (kW) | Heavy duty: Power @460 V (hp) | Heavy duty: Rated current (A) | Frame size / dimensions H1/H2 x W x D (mm) |
|---|---|---|---|---|---|---|---|
| TSA52-016 | 7.5 | 10 | 16 | 4 | 5 | 10 | Frame size 1 246/340 x 126 x 188 |
| TSA52-022 | 11 | 15 | 22 | 5.5 | 7.5 | 12 | Frame size 1 246/340 x 126 x 188 |
| TSA52-030 | 15 | 20 | 30 | 7.5 | 10 | 18 | Frame size 1 246/340 x 126 x 188 |
| TSA52-036 | 18.5 | 25 | 36 | 7.5 | 15 | 21 | Frame size 1 246/340 x 126 x 188 |
| TSA52-042 | 22 | 30 | 42 | 11 | 20 | 25 | Frame size 1 246/340 x 126 x 188 |
| TSA52-056 | 30 | 40 | 56 | 15 | 25 | 33 | Frame size 1 246/340 x 126 x 188 |
| TSA52-070 | 37 | 50 | 70 | 22 | 30 | 42 | Frame size 2 246/340 x 126 x 188 |
| TSA52-085 | 45 | 60 | 85 | 22 | 40 | 51 | Frame size 2 246/340 x 126 x 188 |
| TSA52-100 | 55 | 75 | 100 | 30 | 40 | 60 | Frame size 2 246/340 x 126 x 188 |
| TSA52-140 | 75 | 100 | 140 | 45 | 60 | 84 | Frame size 3 285/380 x 196 x 235 |
| TSA52-170 | 90 | 125 | 170 | 55 | 75 | 102 | Frame size 3 285/380 x 196 x 235 |
| TSA52-200 | 110 | 150 | 200 | 55 | 100 | 120 | Frame size 3 285/380 x 196 x 235 |
| TSA52-240 | 132 | 200 | 240 | 75 | 100 | 144 | Frame size 4 373/512 x 254 x 260 |
| TSA52-300 | 160 | 250 | 300 | 90 | 125 | 180 | Frame size 4 373/512 x 254 x 260 |
| TSA52-360 | 200 | 300 | 360 | 110 | 150 | 216 | Frame size 4 373/512 x 254 x 260 |
| TSA52-450 | 250 | 350 | 450 | 160 | 200 | 270 | Frame size 4 373/512 x 254 x 260 |
Catalogue — Emotron TSA / PDF 4 — page 4
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 4
Emotron TSA softstarter with integrated bypass
Typical motor power at mains voltage 525 V
Rating according to AC53b norm.
(1) Normal duty: Start current = 3 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(2) Heavy duty: Start current = 5 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(3) H1= Height of enclosure, H2=Total height
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: Emotron TSA; 525 V. AC53b: normal starting current 3 x In_soft; heavy 5 x In_soft. Start time 15 s for size1, 30 s for sizes2–4;10 starts/hour. H1 enclosure height; H2 total height.
Emotron TSA specifications — PDF page 4
| Model | Normal duty: Power @525 V (kW) | Normal duty: Rated current (A) | Heavy duty: Power @525 V (kW) | Heavy duty: Rated current (A) | Frame size / dimensions H1/H2 x W x D (mm) |
|---|---|---|---|---|---|
| TSA52-016 | 11 | 16 | 5.5 | 10 | Frame size 1 246/340 x 126 x 188 |
| TSA52-022 | 15 | 22 | 7.5 | 12 | Frame size 1 246/340 x 126 x 188 |
| TSA52-030 | 18.5 | 30 | 11 | 18 | Frame size 1 246/340 x 126 x 188 |
| TSA52-036 | 22 | 36 | 11 | 21 | Frame size 1 246/340 x 126 x 188 |
| TSA52-042 | 30 | 42 | 15 | 25 | Frame size 1 246/340 x 126 x 188 |
| TSA52-056 | 37 | 56 | 22 | 33 | Frame size 1 246/340 x 126 x 188 |
| TSA52-070 | 45 | 70 | 22 | 42 | Frame size 2 246/340 x 126 x 188 |
| TSA52-085 | 55 | 85 | 30 | 51 | Frame size 2 246/340 x 126 x 188 |
| TSA52-100 | 75 | 100 | 37 | 60 | Frame size 2 246/340 x 126 x 188 |
| TSA52-140 | 90 | 140 | 55 | 84 | Frame size 3 285/380 x 196 x 235 |
| TSA52-170 | 110 | 170 | 75 | 102 | Frame size 3 285/380 x 196 x 235 |
| TSA52-200 | 132 | 200 | 75 | 120 | Frame size 3 285/380 x 196 x 235 |
| TSA52-240 | 160 | 240 | 90 | 144 | Frame size 4 373/512 x 254 x 260 |
| TSA52-300 | 200 | 300 | 132 | 180 | Frame size 4 373/512 x 254 x 260 |
| TSA52-360 | 250 | 360 | 160 | 216 | Frame size 4 373/512 x 254 x 260 |
| TSA52-450 | 315 | 450 | 180 | 270 | Frame size 4 373/512 x 254 x 260 |
Catalogue — Emotron TSA / PDF 5 — page 5
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 5
Emotron TSA softstarter with integrated bypass
Typical motor power at mains voltage 575 V and 690 V
Rating according to AC53b norm.
(1) Normal duty: Start current = 3 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(2) Heavy duty: Start current = 5 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(3) H1= Height of enclosure, H2=Total height
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: Emotron TSA; 575 V / 690 V. AC53b: normal starting current 3 x In_soft; heavy 5 x In_soft. Start time 15 s for size1, 30 s for sizes2–4;10 starts/hour. H1 enclosure height; H2 total height.
Emotron TSA specifications — PDF page 5
| Model | Normal duty: Power @575 V (hp) | Normal duty: Power @690 V (kW) | Normal duty: Rated current (A) | Heavy duty: Power @575 V (hp) | Heavy duty: Power @690 V (kW) | Heavy duty: Rated current (A) | Frame size / dimensions H1/H2 x W x D (mm) |
|---|---|---|---|---|---|---|---|
| TSA69-016 | 15 | 11 | 16 | 7.5 | 7.5 | 10 | Frame size 1 246/340 x 126 x 188 |
| TSA69-022 | 20 | 18.5 | 22 | 10 | 11 | 12 | Frame size 1 246/340 x 126 x 188 |
| TSA69-030 | 25 | 22 | 30 | 15 | 15 | 18 | Frame size 1 246/340 x 126 x 188 |
| TSA69-036 | 30 | 30 | 36 | 20 | 18.5 | 21 | Frame size 1 246/340 x 126 x 188 |
| TSA69-042 | 40 | 37 | 42 | 25 | 22 | 25 | Frame size 1 246/340 x 126 x 188 |
| TSA69-056 | 50 | 45 | 56 | 30 | 30 | 33 | Frame size 1 246/340 x 126 x 188 |
| TSA69-070 | 60 | 55 | 70 | 40 | 37 | 42 | Frame size 2 246/340 x 126 x 188 |
| TSA69-085 | 75 | 75 | 85 | 50 | 45 | 51 | Frame size 2 246/340 x 126 x 188 |
| TSA69-100 | 100 | 90 | 100 | 60 | 55 | 60 | Frame size 2 246/340 x 126 x 188 |
| TSA69-140 | 125 | 132 | 140 | 75 | 75 | 84 | Frame size 3 285/380 x 196 x 235 |
| TSA69-170 | 150 | 160 | 170 | 100 | 90 | 102 | Frame size 3 285/380 x 196 x 235 |
| TSA69-200 | 200 | 200 | 200 | 125 | 110 | 120 | Frame size 3 285/380 x 196 x 235 |
| TSA69-240 | 250 | 250 | 240 | 150 | 132 | 144 | Frame size 4 373/512 x 254 x 260 |
| TSA69-300 | 300 | 315 | 300 | 150 | 160 | 180 | Frame size 4 373/512 x 254 x 260 |
| TSA69-360 | 350 | 355 | 360 | 200 | 200 | 216 | Frame size 4 373/512 x 254 x 260 |
| TSA69-450 | 450 | 450 | 450 | 250 | 250 | 270 | Frame size 4 373/512 x 254 x 260 |
Catalogue — Emotron MSF / PDF 6 — page 6
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 6
Emotron MSF softstarter, the heavy duty solid state softstarter
Main features
UL 508
GOST R
• Robust metal enclosure softstarter with power range:
4 kW - 1.6 MW, 200 - 690 V, 3-ph.
• Solid state 3-phase control type softstarter with heavy duty nominal rating.
• Torque control start and stop modes for minimized start currents.
• Dynamic vector braking and counter current braking modes available.
• Motor I2t protection and isolated thermistor input as standard.
• Load monitor function for protection of load machinery.
• IP20 protection for sizes 17 - 835 A, IP00 for sizes 1000 - 1400 A.
Emotron MSF softstarter the
proven softstarter for heavy duty
applications.
Supplier logo panel shows CE, UL 508, cULus Listed and GOST R. Logos and named standards are historical source claims, not confirmation of current certification scope or validity.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Catalogue — Emotron MSF / PDF 7 — page 7
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 7
Emotron MSF softstarter, 525 V type
Typical motor power at mains voltage 400 V
Rating according to AC53a norm.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: Emotron MSF; 525 V type; typical power at 400 V / 460 V. AC53a normal3.0-30:50-10; heavy5.0-30:50-10. Model suffixes are literal within stated voltage type; do not combine voltage versions.
Emotron MSF specifications — PDF page 7
| Model | Normal duty: Power @400 V (kW) | Normal duty: Power @460 V (hp) | Normal duty: Rated current (A) | Heavy duty: Power @400 V (kW) | Heavy duty: Power @460 V (hp) | Heavy duty: Rated current (A) | Frame size / dimensions H x W x D (mm) |
|---|---|---|---|---|---|---|---|
| MSF-017 | 11 | 15 | 22 | 7.5 | 10 | 17 | Frame size 1 320 x 126 x 260 |
| -030 | 18.5 | 25 | 37 | 15 | 20 | 30 | Frame size 1 320 x 126 x 260 |
| -045 | 30 | 40 | 60 | 22 | 30 | 45 | Frame size 1 320 x 126 x 260 |
| -060 | 37 | 50 | 72 | 30 | 40 | 60 | Frame size 1 320 x 126 x 260 |
| -075 | 45 | 60 | 85 | 37 | 60 | 75 | Frame size 1 320 x 126 x 260 |
| -085 | 45 | 75 | 96 | 45 | 60 | 85 | Frame size 1 320 x 126 x 260 |
| -110 | 75 | 100 | 134 | 55 | 75 | 110 | Frame size 2 400 x 176 x 260 |
| -145 | 75 | 125 | 156 | 75 | 100 | 145 | Frame size 2 400 x 176 x 260 |
| -170 | 110 | 150 | 210 | 90 | 125 | 170 | Frame size 3B 500 x 260 x 260 |
| -210 | 132 | 200 | 250 | 110 | 150 | 210 | Frame size 3B 500 x 260 x 260 |
| -250 | 132 | 200 | 262 | 132 | 200 | 250 | Frame size 3B 500 x 260 x 260 |
| -310 | 200 | 300 | 370 | 160 | 250 | 310 | Frame size 4 532 x 547 x 278 |
| -370 | 250 | 350 | 450 | 200 | 300 | 370 | Frame size 4 532 x 547 x 278 |
| -450 | 315 | 450 | 549 | 250 | 350 | 450 | Frame size 4 532 x 547 x 278 |
| -570 | 400 | 600 | 710 | 315 | 500 | 570 | Frame size 5 687 x 640 x 302 |
| -710 | 450 | 700 | 835 | 400 | 600 | 710 | Frame size 5 687 x 640 x 302 |
| -835 | 500 | 800 | 960 | 450 | 700 | 835 | Frame size 5 687 x 640 x 302 |
| -1000 | 630 | 900 | 1125 | 560 | 800 | 1 000 | Frame size 6 900 x 875 x 336 |
| -1400 | 900 | 1250 | 1650 | 800 | 1000 | 1 400 | Frame size 6 900 x 875 x 336 |
Catalogue — Emotron MSF / PDF 8 — page 8
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 8
Emotron MSF softstarter, 525 V type
Typical motor power at mains voltage 525 V
Rating according to AC53a norm.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: Emotron MSF; 525 V. AC53a normal3.0-30:50-10; heavy5.0-30:50-10. Model suffixes are literal within stated voltage type; do not combine voltage versions.
Emotron MSF specifications — PDF page 8
| Model | Normal duty: Power @525 V (kW) | Normal duty: Rated current (A) | Heavy duty: Power @525 V (kW) | Heavy duty: Rated current (A) | Frame size / dimensions H x W x D (mm) |
|---|---|---|---|---|---|
| MSF-017 | 15 | 22 | 11 | 17 | Frame size 1 320 x 126 x 260 |
| -030 | 22 | 37 | 18,5 | 30 | Frame size 1 320 x 126 x 260 |
| -045 | 37 | 60 | 30 | 45 | Frame size 1 320 x 126 x 260 |
| -060 | 45 | 72 | 37 | 60 | Frame size 1 320 x 126 x 260 |
| -075 | 55 | 85 | 45 | 75 | Frame size 1 320 x 126 x 260 |
| -085 | 55 | 96 | 55 | 85 | Frame size 1 320 x 126 x 260 |
| -110 | 90 | 134 | 75 | 110 | Frame size 2 400 x 176 x 260 |
| -145 | 110 | 156 | 90 | 145 | Frame size 2 400 x 176 x 260 |
| -170 | 132 | 210 | 110 | 170 | Frame size 3B 500 x 260 x 260 |
| -210 | 160 | 250 | 132 | 210 | Frame size 3B 500 x 260 x 260 |
| -250 | 160 | 262 | 160 | 250 | Frame size 3B 500 x 260 x 260 |
| -310 | 250 | 370 | 200 | 310 | Frame size 4 532 x 547 x 278 |
| -370 | 315 | 450 | 250 | 370 | Frame size 4 532 x 547 x 278 |
| -450 | 400 | 549 | 315 | 450 | Frame size 4 532 x 547 x 278 |
| -570 | 500 | 710 | 400 | 570 | Frame size 5 687 x 640 x 302 |
| -710 | 560 | 835 | 500 | 710 | Frame size 5 687 x 640 x 302 |
| -835 | 710 | 960 | 560 | 835 | Frame size 5 687 x 640 x 302 |
| -1000 | 800 | 1125 | 710 | 1 000 | Frame size 6 900 x 875 x 336 |
| -1400 | 1250 | 1650 | 1000 | 1 400 | Frame size 6 900 x 875 x 336 |
Catalogue — Emotron MSF / PDF 9 — page 9
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 9
Emotron MSF softstarter, 690 V type
Typical motor power at mains voltage 575 V and 690 V
Rating according to AC53a norm.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: Emotron MSF; 575 V / 690 V. AC53a normal3.0-30:50-10; heavy5.0-30:50-10. Model suffixes are literal within stated voltage type; do not combine voltage versions.
Emotron MSF specifications — PDF page 9
| Model | Normal duty: Power @575 V (hp) | Normal duty: Power @690 V (kW) | Normal duty: Rated current (A) | Heavy duty: Power @575 V (hp) | Heavy duty: Power @690 V (kW) | Heavy duty: Rated current (A) | Frame size / dimensions H x W x D (mm) |
|---|---|---|---|---|---|---|---|
| MSF-017 | 20 | 18,5 | 22 | 15 | 15 | 17 | Frame size 1 320 x 126 x 260 |
| -030 | 30 | 30 | 37 | 25 | 22 | 30 | Frame size 1 320 x 126 x 260 |
| -045 | 50 | 55 | 60 | 40 | 37 | 45 | Frame size 1 320 x 126 x 260 |
| -060 | 60 | 55 | 72 | 50 | 55 | 60 | Frame size 1 320 x 126 x 260 |
| -075 | 75 | 75 | 85 | 75 | 55 | 75 | Frame size 1 320 x 126 x 260 |
| -085 | 75 | 90 | 90 | 75 | 75 | 85 | Frame size 1 320 x 126 x 260 |
| -110 | 125 | 110 | 134 | 100 | 90 | 110 | Frame size 2 400 x 176 x 260 |
| -145 | 150 | 132 | 156 | 150 | 132 | 145 | Frame size 2 400 x 176 x 260 |
| -170 | 200 | 200 | 210 | 150 | 160 | 170 | Frame size 3B 500 x 260 x 260 |
| -210 | 250 | 250 | 250 | 200 | 200 | 210 | Frame size 3B 500 x 260 x 260 |
| -250 | 250 | 250 | 262 | 250 | 250 | 250 | Frame size 3B 500 x 260 x 260 |
| -310 | 400 | 355 | 370 | 300 | 315 | 310 | Frame size 4 532 x 547 x 278 |
| -370 | 500 | 400 | 450 | 400 | 355 | 370 | Frame size 4 532 x 547 x 278 |
| -450 | 600 | 560 | 549 | 500 | 400 | 450 | Frame size 4 532 x 547 x 278 |
| -570 | 700 | 630 | 640 | 600 | 560 | 570 | Frame size 5 687 x 640 x 302 |
| -710 | 800 | 800 | 835 | 700 | 710 | 710 | Frame size 5 687 x 640 x 302 |
| -835 | 900 | 900 | 880 | 800 | 800 | 835 | Frame size 5 687 x 640 x 302 |
| -1000 | 1250 | 1120 | 1125 | 1000 | 1000 | 1 000 | Frame size 6 900 x 875 x 336 |
| -1400 | 1500 | 1600 | 1524 | 1500 | 1400 | 1 400 | Frame size 6 900 x 875 x 336 |
Catalogue — General and environmental specifications — page 10
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 10
TSA power-loss asterisk refers to Emotron TSA instruction manual chapter13 for details.
Context: Normal operation, storage and higher-temperature derating are separate scopes. IEC classes are source statements, not independent conformance verification.
Table conditions: Separate TSA/MSF columns. * TSA instruction manual chapter13. TSA control tolerance here differs from interface page14 ±10%; both retained.
Table conditions: Source environmental limits; no computed derated values or extended model applicability.
Table conditions: Storage only; not operating limits.
General specifications — PDF page 10
| Parameter | TSA | MSF |
|---|---|---|
| Mains voltage | 200–525V +10%/-15%;200–690V +10%/-15% | 200–525V ±10%;200–690V +5%/-10% |
| Control supply voltage | 100–240V +10%/-15%,single phase | 100–240V ±10%,single phase;380–500V ±10% |
| Number of fully controlled phases | 3 | 3 |
| Mains and control frequency | 50/60Hz ±10% | 50/60Hz ±10% |
| Power loss (% of Pmot) | 0.2%* if10starts/hour | 0.6% |
Environmental normal operation — PDF page 10
| Parameter | Normal operation |
|---|---|
| Nominal ambient temperature | 0°C–40°C (see Table1) |
| Atmospheric pressure | 86–106kPa |
| Relative humidity,non-condensing | Max95%,non-condensing |
| Contamination according to IEC60721-3-3 | Chemically active3C3: conformal coating on all TSA printed circuit boards, optional forMSF. Mechanically active3S1: no sand; dust<0.01mg/m³; deposited<0.4mg/(m²*h). Biological3B1: no harmful biological attacks from mould,fungus,animals,etc. |
| Vibrations | IEC60721-3-3 mechanical3M4:2–9Hz,3.0mm and9–20Hz,acc.1g(10m/s²) |
| Altitude | 0–1,000m;max4,000m with1%/100m derating above1,000m |
Storage conditions — PDF page 10
| Parameter | Storage condition |
|---|---|
| Temperature | -25 to+70°C |
| Atmospheric pressure | 86–106kPa |
| Relative humidity,non-condensing | Max95%,non-condensing |
Catalogue — Temperature derating and dimensions — page 11
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 11
Source nominal maximum operating ambient40°C. Higher temperatures require reduced output current according to Table1.
TSA H1=enclosure height;H2=total height including cable interface.
Context: Model ranges retained as printed ranges, not expanded to assumed individual model IDs. TSA weight23,5 uses source decimal comma.
Table conditions: Above nominal40°C only. Different upper-temperature limits retained; no combined altitude/temperature derating calculated.
Table conditions: H1 enclosure height;H2 total height including cable interface. Physical sizes as printed; no dimension geometry inferred.
Table conditions: MSF H is a single height, not TSA H1/H2. Range-specific convection/fan mounting retained.
Table1 ambient temperature and possible derating — PDF page 11
| Model | Rated max temp. | Possible output current derating |
|---|---|---|
| Emotron TSA | 40°C | -2%/°C to max+15°C(55°C) |
| Emotron MSF | 40°C | -2%/°C to max+10°C(50°C) |
TSA dimensions weights cooling mounting — PDF page 11
| Emotron TSA model | Frame size | H1/H2 x W x D mm | Weight kg | Cooling/Mounting |
|---|---|---|---|---|
| TSA-016 to-056 | 1 | 246/340 x126 x188 | 5.5 | Convection/Vertical |
| TSA-070 to-100 | 2 | 246/340 x126 x188 | 5.7 | Fan/Vertical & Horizontal |
| TSA-140 to-200 | 3 | 285/380 x196 x235 | 13 | Fan/Vertical & Horizontal |
| TSA-240 to-450 | 4 | 373/512 x254 x260 | 23,5 | Fan/Vertical & Horizontal |
MSF dimensions weights cooling mounting — PDF page 11
| Emotron MSF model | Frame size | H x W x D mm | Weight kg | Cooling/Mounting |
|---|---|---|---|---|
| MSF-017 to-030 | 1 | 320 x126 x260 | 6.7 | Convection/Vertical |
| MSF-045 to-085 | 1 | 320 x126 x260 | 6.9 | Fan/Vertical & Horizontal |
| MSF-110 to-145 | 2 | 400 x176 x260 | 12 | Fan/Vertical & Horizontal |
| MSF-170 to-250 | 3B | 500 x260 x260 | 20 | Fan/Vertical & Horizontal |
| MSF-310 to-450 | 4 | 532 x547 x278 | 46 | Fan/Vertical & Horizontal |
| MSF-570 to-835 | 5 | 687 x640 x302 | 80 | Fan/Vertical & Horizontal |
| MSF-1000 to-1400 | 6 | 900 x875 x336 | 175 | Fan/Vertical & Horizontal |
Catalogue — TSA/MSF comparison / PDF 12 — page 12
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 12
Basic I/O data
1) For max 1 % inaccuracy.
See “User interface data” on page 13 for connection data and default settings.
Emotron TSA recommended load fuse
Recommended slow fuses for protection against overload.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: Basic I/O comparison; multiline parameter/value groups retain source order. Printed empty cells are not zero. Footnote1: max1% inaccuracy. TSA recommended slow fuses protect against overload.
TSA/MSF comparison specifications — PDF page 12
| Parameter/context | Emotron TSA | Emotron MSF |
|---|---|---|
| Control signal inputs: Analogue (differential), 1 input |
||
| Analogue voltage/current Resolution Input impedance |
0-10V, 2-10V / 0-20 mA, 4-20 mA 12 bit Volt signal 20 kΩ, Current signal 250 Ω. |
0-10V, 2-10V / 0-20 mA, 4-20 mA 10 bit Volt signal 125 kΩ, Current signal 100 Ω. |
| Digital: 4 inputs | ||
| Input voltage Max. input voltage Input impedance |
0-4 V → 0; 8-27 V → 1. Max. 37 V for 10 sec. ≤3.3 VDC: 4.7 kΩ. - ≥3.3 VDC: 3.6 kΩ |
0-3 V → 0; 8-27 V → 1 Max. 37 V for 10 sec 0 VDC: 2.2 kΩ. |
| Control signal outputs: Analogue, 1 channel |
||
| Output voltage/current Min. load impedance for voltage signal 1) Maximum load impedance for current signal 1) Resolution |
0-10 V, 2-10 V / 0-20 mA, 4-20 mA 700 Ω 700 Ω 12 bit |
0-10V, 2-10V / 0-20 mA, 4-20 mA 700 Ω 750 Ω. 8 bits |
| Relays, 3 pcs | ||
| Contacts | Relay 1 and 2: 1-pole closing contact (NO). Relay 3: 1-pole change-over contact (NO/NC). 250 VAC 8A or 24 VDC 8A resistive. 250 VAC, 3A inductive. Min. 100 mA. |
Relay 1 and 2 : 1-pole closing contact (NO). Relay 3: 1-pole change-over contact (NO/NC). 8 A, 250 VAC or 24 VDC resistive load; 3 A, 250 VAC inductive load (PF 0.4). |
| Reference voltages | ||
| Output voltage Short-circuit current(∞) Output voltage (for AnIn) Short-circuit current(∞) |
+24 VDC+5% Max current 50 mA +10VDC ±5% Max 10 mA short circuit and overload proof. |
+12 VDC ±5% Max current 50 mA |
TSA/MSF comparison specifications — PDF page 12
| TSA model | Recommended slow load fuse (A) |
|---|---|
| - 016 | 35 |
| - 022 | 50 |
| - 030 | 63 |
| - 036 | 80 |
| - 042 | 100 |
| - 056 | 125 |
| - 070 | 160 |
| - 085 | 200 |
TSA/MSF comparison specifications — PDF page 12
| TSA model | Recommended slow load fuse (A) |
|---|---|
| - 100 | 250 |
| - 140 | 355 |
| - 170 | 400 |
| - 200 | 500 |
| - 240 | 630 |
| - 300 | 900 |
| - 360 | 1000 |
| - 450 | 1400 |
Catalogue — TSA/MSF comparison / PDF 13 — page 13
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 13
Emotron TSA semiconductor fuses
Emotron MSF semiconductor fuses
Emotron MSF UL/cUL fuses
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Table conditions: TSA/MSF semiconductor fuse selections and MSF UL/cUL fuse table are distinct scopes. Semiconductor i²t values apply at700V. Blank and dash cells are not substituted; source certification claims only.
TSA/MSF comparison specifications — PDF page 13
| TSA model | Maximum value fuse (A) | i²t fuse at700 V (A²s) |
|---|---|---|
| - 016 | 50 | 1 500 |
| - 022 | 70 | 2 800 |
| - 030 | 100 | 3 600 |
| - 036 | 125 | 6 900 |
| - 042 | 150 | 11 000 |
| - 056 | 175 | 14 000 |
| - 070 | 250 | 42 000 |
| - 085 | 300 | 55 000 |
| - 100 | 400 | 99 000 |
| - 140 | 500 | 160 000 |
| - 170 | 600 | 222 000 |
| - 200 | 700 | 332 000 |
| - 240 | 800 | 433 000 |
| - 300 | 1 000 | 950 000 |
| - 360 | 1 200 | 1 470 000 |
| - 450 | 1 400 | 1 890 000 |
TSA/MSF comparison specifications — PDF page 13
| MSF model | Maximum value fuse (source heading A; cells contain part codes) | i²t fuse at700 V (A²s) |
|---|---|---|
| - 017 | FWP-80A | 2 400 |
| - 030 | FWP-125A | 7 300 |
| - 045 | FWP-150A | 11 700 |
| - 060 | FWP-175A | 16 700 |
| - 075 | FWP-250A | 42 500 |
| - 085 | FWP-300A | 71 200 |
| - 110 | FWP-350A | 95 600 |
| - 145 | FWP-450A | 250 000 |
| - 170 | FWP-700A | 300 000 |
| - 210 | FWP-700A | 300 000 |
| - 250 | FWP-800A | 450 000 |
| - 310 | FWP-800A | 450 000 |
| - 370 | FWP-1000A | 600 000 |
| - 450 | FWJ-1200A | 1 470 000 |
| - 570 | FWJ-1400A | 1 890 000 |
| - 710 | FWJ-1800A | 3 710 000 |
| - 835 | FWJ-2000A | 5 320 000 |
| - 1000 | FWJ-2000A | 5 320 000 |
| - 1400 | <12 000 000 |
TSA/MSF comparison specifications — PDF page 13
| MSF model | Fuse type for UL | Maximum UL rating (A) | Fuse type for cUL | Maximum cUL rating (A) |
|---|---|---|---|---|
| - 017 | Any UL listed fuse | 80 | Bussman, FWP | 80 |
| - 030 | Any UL listed fuse | 125 | Bussman, FWP | 125 |
| - 045 | Any UL listed fuse | 225 | Bussman, FWP | 150 |
| - 060 | Any UL listed fuse | 250 | Bussman, FWP | 175 |
| - 075 | Any UL listed fuse | 300 | Bussman, FWP | 250 |
| - 085 | Any UL listed fuse | 350 | Bussman, FWP | 300 |
| - 110 | Any UL listed fuse | 500 | Bussman, FWP | 350 |
| - 145 | Any UL listed fuse | 600 | Bussman, FWP | 450 |
| - 170 | Any UL listed fuse | 800 | Bussman, FWP | 700 |
| - 210 | Any UL listed fuse | 1000 | Bussman, FWP | 700 |
| - 250 | Any UL listed fuse | 1000 | Bussman, FWP | 800 |
| - 310 | Any UL listed fuse or circuit breaker | 1400 | Any CSA listed fuse or circuit breaker | 1400 |
| - 370 | Any UL listed fuse or circuit breaker | 1800 | Any CSA listed fuse or circuit breaker | 1800 |
| - 450 | Any UL listed fuse or circuit breaker | 2100 | Any CSA listed fuse or circuit breaker | 2100 |
| - 570 | Any UL listed fuse or circuit breaker | 2100 | Any CSA listed fuse or circuit breaker | 2100 |
| - 710 | Any UL listed fuse or circuit breaker | 2500 | Any CSA listed fuse or circuit breaker | 2500 |
| - 835 | Any UL listed fuse or circuit breaker | 2800 | Any CSA listed fuse or circuit breaker | 2800 |
| - 1000 | - | - | - | |
| - 1400 | - | - | - |
Catalogue — TSA user interface terminal table — page 14
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 14
All analogue and digital inputs/outputs are programmable; asterisk denotes default selection.
Schematic annotations: motorT1/T2/T3;control supply100–240VAC ±10%;analogue0–10V/4–20mA;RS232(non-isol.) Ext.Panel/PC;option board communication options.
Context: Terminal mapping transcribed from printed table; source diagram remains authority for topology. Page14 TSA control-supply ±10% differs from general page10 +10%/-15%.
Table conditions: Default functions only; programmable. Literal voltage and terminal identity retained.
Table conditions: Merged name/function cells expanded by terminal only. Not-printed markers retain blank columns. Wiring topology not reconstructed.
TSA control board terminals — PDF page 14
| Terminal | Name | Function(default) |
|---|---|---|
| 11 | DigIn1 | Run FWD |
| 12 | DigIn2 | Stop |
| 13 | 10VDC | Supply voltage for analogue input |
| 14 | AnIn | Process value |
| 15 | GND | Signal ground(Common) |
| 16 | DigIn3 | Set Ctrl1 |
| 17 | DigIn4 | Reset |
| 18 | +24V | +24VDC supply voltage |
| 19 | AnOut | 0 to motor nom.current |
| 20 | +24V | +24VDC supply voltage |
TSA power board terminals — PDF page 14
| Terminal | Name/context | Contact designation | Function(default) |
|---|---|---|---|
| PE | [not printed] | [not printed] | Protective Earth |
| N | [not printed] | [not printed] | Control supply100–240VAC ±10% |
| L | [not printed] | [not printed] | Control supply100–240VAC ±10% |
| 21 | Relay1 | NO | Operation |
| 22 | Relay1 | C | Operation |
| 23 | Relay2 | NO | Not used |
| 24 | Relay2 | C | Not used |
| 31 | Relay3 | NO | Trip |
| 32 | Relay3 | C | Trip |
| 33 | Relay3 | NC | Trip |
| 69 | [not printed] | [not printed] | PTC thermistor input(isolated) |
| 70 | [not printed] | [not printed] | PTC thermistor input(isolated) |
Catalogue — MSF user interface terminal table — page 15
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 15
All analogue and digital inputs/outputs are programmable; asterisk denotes default selection.
Schematic annotations: motorT1/T2/T3;control supply100–240VAC ±10%;control-supply terminal labels01/02/PE;analogue0–10V/4–20mA;current transformer1/2/common75/76/77;communication options.
Context: Source power-board table usesN/L for control supply while diagram uses01/02. No inferred equivalence. Relay3 terminal32 isNC and33 isC here, unlike TSA32C/33NC.
Table conditions: MSF separate fromTSA; terminal14 function blank in source table. Do not copy TSA process-value function.
Table conditions: Merged table cells expanded only within visible boundaries. Diagram01/02 versus tableN/L unresolved. Source exact terminal mappings, not wiring instructions.
MSF control board terminals — PDF page 15
| Terminal | Name | Function(default) |
|---|---|---|
| 11 | DigIn1 | Start |
| 12 | DigIn2 | Stop |
| 13 | 12VDC | Supply voltage for analogue input |
| 14 | AnIn | [not printed] |
| 15 | GND | Signal ground |
| 16 | DigIn3 | Par set1 |
| 17 | DigIn4 | Par set2 |
| 18 | +12V | +12VDC supply voltage |
| 19 | AnOut | 0 to motor nominal current |
MSF power board terminals — PDF page 15
| Terminal | Name/context | Contact designation | Function(default) |
|---|---|---|---|
| PE | [not printed] | [not printed] | Protective Earth |
| N | [not printed] | [not printed] | Control supply100–240VAC ±10% |
| L | [not printed] | [not printed] | Control supply100–240VAC ±10% |
| 21 | Relay1 | NO | Operation |
| 22 | Relay1 | C | Operation |
| 23 | Relay2 | NO | Full voltage |
| 24 | Relay2 | C | Full voltage |
| 31 | Relay3 | NO | All alarms |
| 32 | Relay3 | NC | All alarms |
| 33 | Relay3 | C | All alarms |
| 69 | [not printed] | [not printed] | PTC thermistor input |
| 70 | [not printed] | [not printed] | PTC thermistor input |
| 75 | [not printed] | [not printed] | L1/T1 current transformer |
| 76 | [not printed] | [not printed] | L3/T3 current transformer |
| 77 | [not printed] | [not printed] | Common for75–76 |
Catalogue — Emotron TSA / PDF 16 — page 16
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 16
Standard options for Emotron TSA
Support for 2 option boards plus 1 communication option.
I/O board
3 extra relay outputs (230 VAC/5 A
NO/NC). 3 extra 24 V /3.2 kΩ (AC or
DC) differential digital inputs, all
programmable. Inputs providing
50 VAC/DC isolation between
channels.
Maximum 2 I/O boards can be
built -in per TSA softstarter.
Part no. 01-3876-51
PTC/PT100 board
1 PTC isolated input conforming DIN
44081/44082.
Max 6 PTC thermistors can be
connected in series to PTC input.
Also including 3 PT100 inputs,
2/3/4-wire, conforming EN 60751.
Maximum 2 PTC/PT100 boards can
be built -in per TSA softstarter
Part no. 01-3876-58
Fieldbus - Profibus
Fieldbus option module for Profibus
DP or DP V1 communication. Use
9-pin D-sub connector.
Baud rates: 9.6 kbits/s - 12 Mbits/s
supported.
Typical TSA response time = 10 ms
(not including any fieldbus delays).
Part no. 01-5385-55
Fieldbus - DeviceNet
Fieldbus option module for
DeviceNet communication.
Baud rates: 125 - 500 kbits/s
supported.
Typical TSA response time = 10 ms
(not including any fieldbus delays).
Part no. 01-5385-56
Ethernet - Modbus/TCP
Industrial Ethernet option module for
Modbus/TCP protocol. RJ45 type
connector.
Baud rates: 10 or 100 Mbits/s
supported.
Typical TSA response time = 10 ms
(not including any ethernet delays).
Part no. 01-5385-59
Ethernet - EtherCAT
Industrial Ethernet option module for
EtherCAT protocol.
Baud rate: 100 Mbits/s
Typical TSA response time = 10 ms
(not including any ethernet delays).
Part no. 01-5385-60
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Catalogue — Emotron TSA / PDF 17 — page 17
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 17
Ethernet - Profinet IO 1-port
Industrial Ethernet option module for
Profinet IO (RT) protocol.
Baud rate: 100 Mbits/s
Typical TSA response time = 10 ms
(not including any ethernet delays).
Part no. 01-5385-61
Ethernet - Profinet IO 2-port
Industrial Ethernet option module for
Profinet IO (RT) protocol.
Baud rate: 100 Mbits/s
Typical TSA response time = 10 ms
(not including any ethernet delays).
Part no. 01-5385-62
USB isolated
Isolated USB serial communication
module. For Modbus RTU
comm.protocol.
Baude rates: 2.4 - 115.2 kbits/s
supported.
Typical TSA response time = 10 ms
Part no. 01-5385-63
RS485 isolated
Isolated RS485 serial
communication module. For Modbus
RTU comm.protocol.
Baude rate: 2.4 - 115.2 kbits/s
supported.
Typical TSA response time = 10 ms
Part no. 01-5385-54
External control panel
External control panel IP54 suitable
for mounting on a cabinet door.
Kit complete with control panel,
mounting frame and 3 m cable
Part no. 01-5406-00
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Catalogue — EmoSoftCom scope ambiguous / PDF 18 — page 18
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 18
EmoSoftCom
Connect a PC with a standard RS232
cable to D-sub on top of TSA unit or
via USB/RS485 /Modbus - TCP
Comm. modules (Optional).
EmoSoftCom PC software makes it
possible to perform signal recordings
and save/load parameter backup
data, for example during
service & maintenance.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Catalogue — Emotron MSF / PDF 19 — page 19
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 19
Standard options for Emotron MSF
Support for 1 communication option.
External control panel (ECP)
External control panel IP54 suitable
for mounting on a cabinet door.
Part no. 01-3060-00
Serial communication
Modbus RTU (RS232/RS485) for
serial communication.
Part no. 01-1733-00
Fieldbus - Profibus
Fieldbus option for Profibus DP
communication.
Part no. 01-1734-01
Fieldbus - DeviceNet
Fieldbus option for DeviceNet
communication.
Part no. 01-1736-01
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Catalogue — Emotron MSF / PDF 20 — page 20
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 20
Cable entry box
Cable entry box for connection of
cable glands.
For MSF size 1 (017 - 085).
Part no. 01-2553-00
Cable set for external current transformers
Extension cable set for externally
mounted current transformers. Used
with bypass contactors.
Part no. 01-2020-00
Coated boards
All option boards are also available as
coated, recommended e.g. for sewer
pump applications (sulphide) or
installations with occasional high
humidity (if machine room
installation or tropical climate).
IEC60721-3-3 gases class 3C3, solid
particles class 3S2.
Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.
Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.
Catalogue — CAD reference — page 21
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 21
Source states2D/3D CAD drawings for Emotron AC drives, softstarters and monitors are available viawww.emotron.com. Intended users include consultants,installers and machine builders.
Context: Website reference not followed in local-only batch; this does not prove CAD collection completeness or current availability. Small illustration is not a dimensioned drawing.
Catalogue — Lined notes page — page 22
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 22
Context: Blank ruled note area with printed page21 and document footer; no technical values to extract.
Catalogue — Brand slogan — page 23
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 23
We put all our energy into saving yours.
Context: Marketing slogan and document footer only; no technical values.
Catalogue — Source edition and contact — page 24
Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 24
Emotron is now CG.
Context: Source-era identity and contacts only; not live-verified. Printed issue:2014-09. This is not a statement that it is the current edition.
Table conditions: Printed source values, not contact verification. Website string preserved as printed, not silently split into a route.
Printed edition and source contact — PDF page 24
| Source label/context | Source value |
|---|---|
| Publisher | CG Drives & Automation |
| Address | Mörsaregatan12,Box22225,SE-25024 Helsingborg,Sweden |
| Telephone | +46 42 16 99 00 |
| Fax | +46 42 16 99 49 |
| Website string | www.cgglobal.com/www.emotron.com |
| Document reference | 01-5552-01r1 |
| Language/date | English,2014-09 |
Manual — COVER — page 1
Manual reference: physical PDF page 1. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Cover title, softwareversion and product illustrations; example LCDvalues not treated as specifications. Reviewedtext: Emotron TSA | Softstarter | Instruction manual | English | Software version 1.0X No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — BLANK_PAGE — page 2
Manual reference: physical PDF page 2. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Blank page visually confirmed. Reviewedtext: No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Edition/frontmatter. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 3
Manual reference: physical PDF page 3. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Emotron TSA softstarter
INSTRUCTION MANUAL - ENGLISH
Software version 1.0X
Document number: 01-5980-01
Edition: R0
Date of release: 13-05-2013
© Copyright CG Drives & Automation Sweden AB 2013
CG Drives & Automation Sweden AB retains the right to change
specifications and illustrations in the text, without prior notification.
The contents of this document may not be copied without the explicit
permission of CG Drives & Automation Sweden AB.
Manual — BLANK_PAGE — page 4
Manual reference: physical PDF page 4. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Blank page visually confirmed. Reviewedtext: No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Safety instructions. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 5
Manual reference: physical PDF page 5. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Safety instructions
Congratulations for choosing a product from CG Drives &
Automation!
Before you begin with the installation, commissioning or
powering up the unit for the first time it is very important
that you carefully study this instruction manual.
The following symbols can appear in this manual or on the
product itself. Always read these first before continuing.
Safety
The softstarter should be installed in a cabinet or in an
electrical control room.
•
The device must be installed by trained personnel.
Disconnect all power sources before servicing.
Always use standard commercial fuses, slow blow e.g.
gl, gG types, to protect the wiring and prevent short
circuiting. To protect the thyristors against short-circuit
currents, superfast semiconductor fuses can be used if
preferred. The normal guarantee is valid even if superfast
semiconductor fuses are not used.
Operating and maintenance
personnel
- Read the whole instruction manual before installing and
putting the equipment into operation.
- During all work (operation, maintenance, repairs, etc.)
observe the switch-off procedures given in this
instruction as well as any other operating instruction for
the driven machine or system. See Emergency below.
- The operator must avoid any working methods which
reduce the safety of the device.
- The operator must do what he can to ensure that no
unauthorised person is working on the device.
- The operator must immediately report any changes to
the device which reduce its safety to the user.
- The user must undertake all necessary measures to
operate the device in perfect condition only.
Phase compensation capacitor
If a phase compensation capacitor is to be used, it must be
connected at the inlet of the softstarter, not between the
motor and the softstarter.
Installation of spare parts
We expressly point out that any spare parts and accessories
not supplied by us have also not been tested or approved by
us.
Installing and/or using such products can have a negative
effect on the characteristics designed for your device. The
manufacturer is not liable for damage arising as a result of
using non-original parts and accessories.
Emergency
You can switch the device off at any time with the mains
switch connected before the softstarter (both motor and
control supply voltage must be switched off).
General warnings
Alarms
Never disregard an alarm. Always check and remedy the
cause of an alarm.
NOTE: Additional information as an aid to avoid
problems.
CAUTION!
Failure to follow these instructions can result
in malfunction or damage to the softstarter.
WARNING!
in serious injury to the user in addition to
serious damage to the softstarter.
!
Make sure that all safety measures have
been taken before starting the motor in order
to avoid personal injury.
Never operate the softstarter with the front
cover removed.
been taken before switching on the power
supply.
Manual — FOOTER_ONLY_PAGE — page 6
Manual reference: physical PDF page 6. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 2 | CG Drives & Automation 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Contents navigation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 7
Manual reference: physical PDF page 7. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Contents
Safety instructions ......................................... 1
Contents.......................................................... 3
1.
Introduction..................................................... 5
1.1
Delivery and unpacking ............................................ 5
1.2
Using of the instruction manual............................... 5
1.3
Warranty .................................................................... 5
1.4
Type code number..................................................... 5
1.5
Standards .................................................................. 6
1.5.1
Product standard for EMC ........................................ 6
1.6
Dismantling and scrapping....................................... 6
1.6.1
Disposal of old electrical and electronic
equipment ................................................................. 6
1.7
Glossary ..................................................................... 7
1.7.1
Abbreviations and symbols....................................... 7
1.7.2
Definitions.................................................................. 7
2.
Mounting......................................................... 9
2.1
Installation in a cabinet ............................................ 9
2.1.1
Cooling ....................................................................... 9
2.1.2
Mechanical specifications and drawings .............. 10
3.
Connections................................................. 11
3.1
Mains and motor connections ............................... 12
3.2
Board layout and connectors ................................. 14
3.3
Control signal connections..................................... 15
3.4
Wiring examples...................................................... 16
4.
Application guidelines ................................ 21
4.1
Softstarter dimensioning according to AC-53b..... 21
4.2
Applications rating .................................................. 21
4.3
The Application Functions List ............................... 23
4.4
Special conditions................................................... 26
4.4.1
Small motor or low load.......................................... 26
4.4.2
Ambient temperature below 0°C........................... 26
4.4.3
Pump control with softstarter and AC drive
together ................................................................... 26
4.4.4
Starting with counter-clockwise (reverse) rotating
loads......................................................................... 26
4.4.5
Running motors connected in parallel................... 26
4.4.6
Running motors linked together ............................ 26
4.4.7
Heat dissipation in cabinets................................... 26
4.4.8
Insulation test on motor ......................................... 26
4.4.9
Operation above 1,000 m ...................................... 26
4.4.10
Aggressive environment conditions....................... 26
4.4.11
IT earthing system................................................... 26
4.4.12
Earth fault relay....................................................... 27
4.4.13
Other control voltage .............................................. 27
5.
Getting started............................................. 29
5.1
Check list ................................................................. 29
5.2
Mains and motor connection ................................. 29
5.2.1
Connect the mains cables...................................... 29
5.2.2
Connect the motor cables ...................................... 29
5.2.3
Connect the control supply voltage........................ 29
5.3
Default toggle loop.................................................. 30
5.4
Remote I/O operation............................................. 30
5.5
Control panel operation.......................................... 31
6.
Operation via the control panel .................. 33
6.1
Display ..................................................................... 33
6.2
LED indicators ......................................................... 34
6.3
Control keys............................................................. 34
6.4
Function keys .......................................................... 34
6.4.1
+/- key function....................................................... 35
6.4.2
Jog key function....................................................... 35
6.5
Toggle and Loc/Rem Key ....................................... 35
6.5.1
Toggle function........................................................ 35
6.5.2
Loc/Rem function ................................................... 36
6.6
The menu structure ................................................ 37
6.6.1
The main menu ....................................................... 37
7.
Main features ............................................... 39
7.1
Setting Start, Stop and Run functions................... 39
7.1.1
Start and stop control............................................. 39
7.1.2
Start and stop methods.......................................... 39
7.1.3
Jog functions ........................................................... 40
7.1.4
Start/Stop signal priority ........................................ 40
7.1.5
Setting motor data .................................................. 40
7.1.6
Process information................................................ 40
7.2
Working with parameter sets ................................. 41
7.2.1
Control of parameter sets ...................................... 41
7.2.2
Configuration of parameter sets............................ 42
7.2.3
Handling motor data in parameter sets ................ 42
7.2.4
Using the control panel memory............................ 42
7.3
Applying limitations, alarms and autoreset........... 45
7.3.1
Alarm types and actions ......................................... 45
7.3.2
Alarm settings.......................................................... 45
7.3.3
Alarm indications .................................................... 45
7.3.4
Load monitor function ............................................ 46
7.3.5
Reset and autoreset ............................................... 50
7.4
Programmable I/O .................................................. 51
7.5
Logical functions ..................................................... 51
7.6
Remote control functions....................................... 51
7.6.1
Default settings of the Run/Stop/Reset
functions.................................................................. 51
7.6.2
Enable and Stop functions ..................................... 52
7.6.3
Reset and Autoreset operation .............................. 52
8.
Functionality................................................. 55
8.1
Preferred View [100]............................................... 56
8.1.1
1st Line [110].......................................................... 57
8.1.2
2nd Line [120] ........................................................ 57
8.2
Main Setup [200].................................................... 57
8.2.1
Operation setup [210] ............................................ 57
8.2.2
Remote signal Level/Edge [21A] ........................... 60
8.2.3
Motor Data [220] .................................................... 60
8.2.4
Motor protection [230] ........................................... 62
8.2.5
Parameter set handling [240]................................ 66
8.2.6
Autoreset [250]....................................................... 69
Manual — P036; Contents navigation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 8
Manual reference: physical PDF page 8. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.2.7
Serial Communication [260].................................. 73
8.3
Process [300].......................................................... 76
8.3.1
View Process Value [310]....................................... 76
8.3.2
Process Settings [320] ........................................... 76
8.3.3
Start setting [330]................................................... 78
8.3.4
Stop Setting [340]................................................... 80
8.3.5
Jog [350].................................................................. 83
8.4
Load Monitor and Process Protection [400]......... 84
8.4.1
Load Monitor [410]................................................. 84
8.4.2
Process protection [420]........................................ 88
8.4.3
Mains Protection [430]........................................... 89
8.5
I/O [500].................................................................. 91
8.5.1
Analogue Input [510].............................................. 91
8.5.2
Digital Inputs [520]................................................. 94
8.5.3
Analogue Output [530] ........................................... 95
8.5.4
Relays [550] ............................................................ 97
8.5.5
Virtual I/Os [560] .................................................... 99
8.6
Logical Functions and Timers [600] .................... 100
8.6.1
Comparators [610] ............................................... 100
8.6.2
Logic outputs [620]............................................... 105
8.6.3
Timers [630].......................................................... 109
8.6.4
SR Flip-flops [640] ................................................ 110
8.6.5
Counters [650]...................................................... 112
8.6.6
Clock Logic [660] .................................................. 113
8.7
Operation/Status [700]........................................ 114
8.7.1
Operation values [710]......................................... 114
8.7.2
Status [720] .......................................................... 116
8.7.3
Stored Values [730].............................................. 119
8.7.4
Real time clock settings [740] ............................. 119
8.8
View Trip Log [800] ............................................... 120
8.8.1
Trip Message Log [810]........................................ 120
8.8.2
Trip Messages [820] - [890]................................. 121
8.8.3
Reset Trip Log [8A0] ............................................. 121
8.9
System Data [900]................................................ 121
8.9.1
TSA Data [920]...................................................... 121
9.
Serial communication ............................... 123
9.1
Modbus RTU .......................................................... 123
9.2
Parameter sets...................................................... 123
9.3
Motor data............................................................. 124
9.4
Start and stop commands.................................... 124
9.5
Process value ........................................................ 124
9.6
Description of the EInt formats............................ 125
10.
Softstarter theory ...................................... 127
10.1
Background theory................................................ 127
10.2
Reduced voltage starting...................................... 128
10.3
Other starting methods......................................... 130
10.4
Use of softstarters with torque control................ 132
11.
Troubleshooting, Diagnoses and
Maintenance.............................................. 133
11.1
Trip conditions, causes and remedial action ...... 133
11.1.1
Technically qualified personnel............................ 133
11.1.2
Opening the softstarter......................................... 133
11.2
Maintenance ......................................................... 133
11.3
Troubleshooting list............................................... 134
12.
Options........................................................ 137
12.1
External control panel........................................... 137
12.2
EmoSoftCom.......................................................... 137
12.3
I/O Board ............................................................... 137
12.4
PTC/PT100............................................................ 137
12.5
Serial communication and fieldbus..................... 137
13.
Technical data............................................ 139
13.1
General electrical specifications.......................... 141
13.2
Semi-conductor fuses........................................... 141
13.3
Environmental conditions..................................... 142
13.3.1
Derating at high temperature............................... 142
13.3.2
Derating at high altitude....................................... 143
13.4
Control power- and I/O signal connectors........... 144
Index ........................................................... 145
Appendix 1: Menu List............................... 147
Appendix 2: Trip message communication data 164
Manual — P036; Introduction and source claims. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 9
Manual reference: physical PDF page 9. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
1.
Introduction
The Emotron TSA softstarter is intended for controlling the
start and stop of standard three phase asynchronous motors.
A built-in powerful digital signal processor (DSP) gives the
softstarter high performance and very good control of the
starting and stopping of the application.
Several options are available, listed in chapter 12. page 137,
that enable you to customize the softstarter for your specific
needs.
Users
This instruction manual is intended for:
•
installation engineers
maintenance engineers
operators
service engineers
Motors
The softstarter is suitable for use with standard 3-phase
asynchronous motors. Contact your supplier for details.
1.1
Delivery and unpacking
Check for any visible signs of damage. Inform your supplier
immediately of any damage found. Do not install the
softstarter if damaged.
Check that all items are present and that the type number is
correct.
1.2
Using of the instruction
manual
Check that the software version number on the first page of
this manual matches the software version in the softstarter.
See chapter 8.9.1 page 121.
With help of the index and the table of contents it is easy to
track individual functions and find out how to use and set
them.
The Quick Start Guide can be put in a cabinet so that it is
always easy to access in case of an emergency.
1.3
Warranty
The warranty applies when the equipment is installed,
operated and maintained according to instructions in this
instruction manual. Duration of warranty is as per contract.
Faults that arise due to faulty installation or operation are
not covered by the warranty.
1.4
Type code number
Fig. 1 gives an example of the type code numbering used for
the Emotron TSA softstarter. This identification will be
required for type specific information when mounting and
installing. The code number is located on the product label,
on the right side of the unit (when viewed from the front).
Fig. 1
NOTE: Read this instruction manual carefully before
installing, connecting or working with the softstarter.
TSA 52 -016 -23 N N N
—
A
Position number:
10 11
Table 1
Figure1 type-code example positions1–11: TSA |52|016|23|N|N|N|—|A|A|—. The example is not a configured customer product; descriptions and option codes inTable1 govern.
Table1 type code; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Table1 type code — PDF page 9
| Source row | Position | Configuration | Description |
|---|---|---|---|
| 1 | 1 | Type | TSA |
| 2 | 2 | Main supply voltage | 52 = Max 525 V mains 69 = Max 690 V mains |
| 3 | 3 | Current rating | 016 = 16 A - - 1K8 = 1800 A |
| 4 | 4 | Control voltage | 23=230 V |
| 5 | 5 | Option position 1 | N=No option P=PTC/PT100 I=I/O board |
| 6 | 6 | Option position 2 | N=No option P=PTC/PT100 I=I/O board |
| 7 | 7 | Communication option |
N=No option A=Profinet IO 1-port B=Profinet IO 2-port D=DeviceNet M=Modbus/TCP P=Profibus R=RS485 U=USB |
| 8 | 8 | IT-net option | — =No option I=IT-net |
| 9 | 9 | Brand label | A=Standard |
| 10 | 10 | Software | A=Standard software |
| 11 | 11 | Standard | — =CE approved |
Manual — P036; Introduction and source claims. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 10
Manual reference: physical PDF page 10. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
1.5
Standards
The softstarters described in this instruction manual comply
with the standards listed in Table 2. For the declarations of
conformity and manufacturer’s certificate, contact your
supplier for more information or visit www.emotron.com or
www.cgglobal.com.
1.5.1Product standard for EMC
The Emotron TSA softstarter complies with the product
standard EN(IEC) 60947-4-2: 2007. The standard
Emotron TSA softstarter is designed to meet the EMC
requirements according to category C1.
1.6
Dismantling and scrapping
The enclosures of the Emotron TSA softstarters are made
from recyclable material such as aluminium, iron and
plastic. Each softstarter contains a number of components
demanding special treatment. The circuit boards contain
small amounts of tin and lead. Any local or national
regulations in force for the disposal and recycling of these
materials must be complied with.
1.6.1Disposal of old electrical and
electronic equipment
This symbol on the product or on its packaging indicates
that this product shall be taken to the applicable collection
point for the recycling of electrical and electronic
equipment. By ensuring this product is disposed of correctly,
you will help prevent potentially negative consequences for
the environment and human health, which could otherwise
be caused by inappropriate waste handling of this product.
The recycling of materials will help to conserve natural
resources. For more detailed information about recycling
this product, please contact the local distributor of the
product.
Table 2
Table2 standards source claims; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 2, column 1, row 3, column 1 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 5, column 1, row 6, column 1, row 7, column 1, row 8, column 1 share the source cell at row 4, column 1. Read its current text above; the child slots remain unpopulated.
Table2 standards source claims — PDF page 10
| Source row | Market | Standard | Description |
|---|---|---|---|
| 1 | European | EMC Directive | 2004/108/EC |
| 2 | ⟦null: no independent source value⟧ | Low Voltage Directive | 2006/95/EC |
| 3 | ⟦null: no independent source value⟧ | WEEE Directive | 2002/96/EC |
| 4 | All | EN 60204-1 | Safety of machinery - Electrical equipment of machines Part 1: General requirements. |
| 5 | ⟦null: no independent source value⟧ | EN(IEC)60947-4-2: 2007 |
Contactors and motor starters Part 3: EMC requirements and specific test methods. EMC Directive: Declaration of Conformity and CE marking |
| 6 | ⟦null: no independent source value⟧ | EN(IEC)60947-4-2: 2007 |
Contactors and motor starters Safety requirements - Electrical, thermal and energy. Low Voltage Directive: Declaration of Conformity and CE marking |
| 7 | ⟦null: no independent source value⟧ | IEC 60721-3-3 | Classification of environmental conditions. Air quality chemical vapours, unit in operation. Chemical gases 3C3, Solid particles 3S1. |
| 8 | ⟦null: no independent source value⟧ | UL508C | UL Safety standard for Power Conversion Equipment. Pending. |
| 9 | USA | UL 840 | UL Safety standard for Power Conversion Equipment. Pending. |
Manual — P036; Introduction and source claims. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 11
Manual reference: physical PDF page 11. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
1.7
Glossary
1.7.1 Abbreviations and symbols
In this manual the following abbreviations are used:
1.7.2 Definitions
In this manual the following definitions are used:
*) Calculation of nominal motor torque:
Table 3
Abbreviations
Table 4
Definitions
Tn Nm
[
]
Pn mot kW
×
nn mot rpm
=
Tn lb ft
Pn mot hp
Table3 last symbol is a padlock: the function cannot be changed in run mode. Printed torque formulas: T_n[Nm] = 9550 × P_n_mot[kW] / n_n_mot[rpm]; T_n[lb.ft] = 5252 × P_n_mot[hp] / n_n_mot[rpm]. These are source formulas; no design calculation performed.
Table4 definitions; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Table3 abbreviations; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Table4 definitions — PDF page 11
| Source row | Name | Description | Unit |
|---|---|---|---|
| 1 | I n_soft |
Nominal softstarter current | [A ] rms |
| 2 | I n_mot |
Nominal motor current | [A ] rms |
| 3 | P n_soft |
Nominal softstarter power | [kW] or [hp] |
| 4 | P n_mot |
Nominal motor power | [kW] or [hp] |
| 5 | T n |
Nominal motor torque* | [Nm] or [lb.ft] |
| 6 | n n_mot |
Nominal speed of motor | [rpm] |
| 7 | cosφ n |
Nominal motor power factor | (dimensionless) |
| 8 | U | 3-phase mains supply voltage | [V ] rms |
| 9 | U n_mot |
Nominal motor voltage | [V] |
Table3 abbreviations — PDF page 11
| Source row | Abbreviation/ symbol |
Description |
|---|---|---|
| 1 | CP | Control panel, the programming and presentation unit on the softstarter |
| 2 | CB | Control board |
| 3 | I2t | The amount of energy losses, heating up the motor. |
| 4 | PTC | Positive Temperature Coefficient (temperature sensor, also known as thermistor) |
| 5 | PB-PTC | Power board PTC input |
| 6 | RMS | Root Mean Square value |
| 7 | FLC | Full Load Current |
| 8 | DOL | Direct On-Line |
| 9 | EInt | Communication format |
| 10 | UInt | Communication format (Unsigned Integer) |
| 11 | Int | Communication format (Integer) |
| 12 | Long | Communication format (Integer Long) |
| 13 | ⟦blank source cell⟧ | The function cannot be changed in run mode |
Manual — FOOTER_ONLY_PAGE — page 12
Manual reference: physical PDF page 12. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 8 | Introduction | CG Drives & Automation 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Mounting specifications. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 13
Manual reference: physical PDF page 13. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
2.
Mounting
This chapter describes how to mount the Emotron TSA
softstarter. Before mounting it is recommended that the
installation is planned out:
•
Be sure that the softstarter suits the mounting location.
The mounting site must support the weight of the
softstarter.
Will the softstarter continuously withstand vibrations
and/or shocks?
Consider using a vibration damper.
Check ambient conditions, ratings, required cooling air
flow, compatibility of the motor, etc.
Do you know how the softstarter will be lifted and
transported?
Make sure that the installation is performed in accordance
with the local safety regulations, and in accordance with
DIN VDE 0100 for setting up power installations.
Care must be taken to ensure that personnel do not come
into contact with live circuit components.
2.1
Installation in a cabinet
When installing the softstarter:
Ensure that the cabinet will be sufficiently ventilated
after the installation.
Keep the minimum free space, as listed inTable 5.
Ensure that air can flow freely from the bottom to the
top.
The Emotron TSA softstarters are delivered as enclosed
versions with front access cover. The units have top and
bottom entry for cables etc., see Chapter 3. page 11.
2.1.1 Cooling
WARNING!
Never operate the softstarter with the front
cover removed.
NOTE: When installing the softstarter, make sure it does
not come into contact with live components. The heat
generated must be dispersed via the cooling fins to
prevent damage to the thyristors (free circulation of air).
Table 5
Minimum free space
*) Above: Cabinet roof to softstarter or softstarter to softstarter
Table5 minimum free space; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 2, column 2 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 2, column 3 share the source cell at row 1, column 3. Read its current text above; the child slots remain unpopulated.
-
row 2, column 4 share the source cell at row 1, column 4. Read its current text above; the child slots remain unpopulated.
Table5 minimum free space — PDF page 13
| Source row | TSA frame size | Minimum above[mm]* | Minimum below[mm] | Minimum side[mm] |
|---|---|---|---|---|
| 1 | 1 | 100 | 100 | 0 |
| 2 | 2 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
Manual — P036; Mounting specifications. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 14
Manual reference: physical PDF page 14. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
2.1.2 Mechanical specifications and drawings
*) H1 = Height of enclosure, H2 = Total height
Fig. 2
Dimensions for Emotron TSA frame size 1 and 2.
Fig. 3
Dimensions for Emotron TSA frame size 1 and 2,
bottom view.
Mounting schemes
Emotron TSA Size 1 - 2
Fig. 4
Hole pattern for Emotron TSA frame size 1 and 2.
On our websites www.cgglobal.com and www.emotron.com
it is possible to download a full-size template for positioning
of the fixing holes.
Table 6
H1
H2
104.5
Ø 6,5 (x 4)
Figures2/3 source dimensions frame1/2: H1enclosure246mm,H2total296mm,W126mm,D188mm. Figure4 mountinghole pattern labels11mmleftoffset,104.5mmhorizontalcentres,11mmtopoffset,273mmverticalcentres,diameter6.5mm×4holes. Originalgeometry/source template governs mounting; nogeometryinferredbeyondprintedlabels.
Table6 mechanical specifications; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.
Table6 mechanical specifications — PDF page 14
| Source row | TSA frame size | H1/H2×W×D[mm] | Mounting position | Weight[kg] | Connection busbars/pressnut[mm] | PE screw | Cooling system | Protection class |
|---|---|---|---|---|---|---|---|---|
| 1 | 1 | 246/296 x 126 x 188 | Vertical | 5.5 | 15 x 4, Cu (M6) | M5 | Convection | IP20 |
| 2 | 2 | 246/296 x 126 x 188 | Vertical | 5.7 | 15 x 4, Cu (M6) | M5 | Fan | IP20 |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 15
Manual reference: physical PDF page 15. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.
Connections
The installation description in this chapter follows the EMC
standards and the Machinery Directive.
If the softstarter is temporarily stored before being
connected, please check the technical data for environmental
conditions section 13.3, page 142. If the softstarter is moved
from a cold storage room to the location where it is to be
installed, condensation could appear on the unit. Allow the
softstarter to become fully acclimatised and wait until any
visible condensation has evaporated before connecting any
supply voltages.
Cables
Dimension the mains and motor cables according to local
regulations and the nominal current of the motor.
It is not necessary to use shielded motor cables together with
the Emotron TSA softstarter. This is due to its very low
radiated emissions.
Neither is it necessary to use shielded mains supply cables
for the Emotron TSA softstarter.
For the control connections, it is not necessary to use
shielded control cables, however with the exception of the
option board connections (see section 3.2, page 14) for
which it is recommended to use flexible wire with a braided
type of shield.
NOTE: For the Emotron TSA softstarter it is not
mandatory to use shielded cables to fulfil the EMC
regulations (section 1.5, page 6). The only exception is
when connecting option board cables, for which there is
an earthing plate that serves as an attachment for the
shielded control cables (see Fig. 9 on page 14).
NOTE: For UL-approval use 75°C copper wire only.
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 16
Manual reference: physical PDF page 16. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.1
Mains and motor connections
Fig. 5
Mains and motor connections for Emotron TSA Size 1-2.
Emotron TSA frame size 1 - 2
-
3-phase mains supply connection, L1, L2, L3
-
Protective earth (PE) connection for mains supply
-
Motor power supply connection T1, T2, T3
-
Motor earth,
connection
Fig. 6
Mains, motor and control supply voltage connection
PE
T1
T2
T3
L1
L2
L3
WARNING!
Leakage current may occur from the
thyristors when a 3-phase mains supply is
connected. Full voltage can be detected if no
motor is connected.
Table 7
Tightening torque for bolts [Nm].
100 - 240 VAC
Figure5 labels:1 mainsL1/L2/L3;2PE mains;3motorT1/T2/T3;4motor earth. Figure6control100–240VAC terminalsL,N,PE are distinct from3phasemains. MotorU,V,W,earth shown. Source wiring image retained; not independent installation approval.
Table7 bolt tightening torque; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.
Table7 bolt tightening torque — PDF page 16
| Source row | TSA frame size | Motor or mains cable bolt torque[Nm] | PE cable bolt torque[Nm] |
|---|---|---|---|
| 1 | 1 | 8 | 5 |
| 2 | 2 | 8 | 5 |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 17
Manual reference: physical PDF page 17. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 7
Busbar distances Emotron TSA Size 1 and 2
When the Mains and motor cables are connected, mount
the cable covers according to Fig. 8.
Fig. 8
Mount the cable covers.
Table 8
Busbar distances.
W3
W2 W1
W1
W2
Figure7 labels W3,W2,W1 aboveandbelow theunit, pairedwithTable8dimensions. Figure8 cablecoverfasteningarrow explicitly3Nm. It is separatefromTable7motor/main8Nm,PE5Nm.
Table8 busbar distances; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.
Table8 busbar distances — PDF page 17
| Source row | TSA frame size | Dist.W1[mm] | Dist.W2[mm] | Dist.W3[mm] |
|---|---|---|---|---|
| 1 | 1 | 23 | 40 | 40 |
| 2 | 2 | 23 | 40 | 40 |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 18
Manual reference: physical PDF page 18. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.2
Board layout and connectors
This section contains general information about the power
board and control board for each Emotron TSA size. For
additional information about special conditions refer to
section 4.4, page 26. For a description of the available
options, go to chapter 12. page 137.
Isolation
The control board in the Emotron TSA product is a
Separated Extra Low Voltage (SELV) circuit. This means
that this board is safely separated from other circuits that
carry higher voltages and is isolated from earth and
protective earth conductors of other circuits. The PTC
circuit on the power board is separated from the control
board SELV circuit with a separation rated for:
•
Double insulation when used in softstarters rated up to
525 VAC.
Basic insulation when used in softstarters rated up to
690 VAC.
It is recommended that the PTC/PT100 sensors are always
separated from live parts with at least basic insulation for the
relevant voltage.
Fig. 9
Board layout for Emotron TSA Size 1-2.
Emotron TSA Size 1 - 2
- Control supply voltage connection PE, N, L (power
board).
- Earthing plate with slots for tie wraps for fixation and
securing of control signal cables and option board cables.
This plate is connected to earth for earthing of shielded
cables.
-
S1 jumper for U/I selection of analogue input
-
Option board ribbon cable connector
-
Communication module (option)
-
LED indicators (visible through perforation):
-
Red and blue for communication signals
-
Green indicating power on
-
Clock battery, type CR 2032, 3 V
-
Terminals for DigIn/AnIn/AnOut signals (control
board)
- Terminals for relay output signals and PTC connection
(power board)
- RS232, using 9-pin female D-sub connector. For
temporary connection of a personal computer or
connection of external control panel (option)
WARNING!
For softstarters rated higher than 525 VAC, it
is mandatory to have at least basic insulation
from the temperature sensor towards live
voltage.
For safety reasons the protective earth (PE)
for the control supply must be connected.
Table 9
Control signal cable dimension and stripping lenght
- When using Ferrules, suitable Ferrule length is 10-12 mm.
Figure9 callouts1controlPE/N/L;2shield-earthingplate;3S1U/Ijumper;4optionribbon;5communicationsoption;6LEDs;7CR2032battery3V;8digital/analoguecontrolterminals;9relay/PTCterminals;10female9pinRS232. LabelassociationsareonlyforthesourceTSA1–2drawing.
Table9 control signal cable dimensions; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.
Table9 control signal cable dimensions — PDF page 18
| Source row | TSA size | Maximum cable dimension | Recommended stripping length |
|---|---|---|---|
| 1 | 1 - 2 | Flexible: 1.5 mm2 Solid: 2.5 mm2 |
6 mm* |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 19
Manual reference: physical PDF page 19. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.3
Control signal connections
Fig. 10 Control board and power board connections.
WARNING!
The same external supply
voltage level (max 24 VDC or
max 250 VAC) must be used
for all three output relays
(terminals 21-33).
Do not mix AC and DC voltage.
Make sure to use the same voltage level
within this terminal section, otherwise
the softstarter may be damaged.
Table 10
Power board connections
Table 11
Control board connections
Figure10 terminalrowspowerPE,N,L;21,22,23,24,31,32,33,69,70;control11–20andS1U/Ijumper. Table10row31NO,32C,33NC is retained even thoughfunctiontextandlaterdiagramR3switcharmat33conflict. No correctedterminalassignment.
Table10 power board connections; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 3, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
-
row 3, column 4 share the source cell at row 2, column 4. Read its current text above; the child slots remain unpopulated.
-
row 4, column 2, row 4, column 3, row 4, column 4 share the source cell at row 4, column 1. Read its current text above; the child slots remain unpopulated.
-
row 6, column 3 share the source cell at row 5, column 3. Read its current text above; the child slots remain unpopulated.
-
row 6, column 4 share the source cell at row 5, column 4. Read its current text above; the child slots remain unpopulated.
-
row 8, column 3 share the source cell at row 7, column 3. Read its current text above; the child slots remain unpopulated.
-
row 8, column 4 share the source cell at row 7, column 4. Read its current text above; the child slots remain unpopulated.
-
row 9, column 2, row 9, column 3, row 9, column 4 share the source cell at row 9, column 1. Read its current text above; the child slots remain unpopulated.
-
row 11, column 3, row 12, column 3 share the source cell at row 10, column 3. Read its current text above; the child slots remain unpopulated.
-
row 11, column 4, row 12, column 4 share the source cell at row 10, column 4. Read its current text above; the child slots remain unpopulated.
-
row 13, column 2, row 13, column 3, row 13, column 4 share the source cell at row 13, column 1. Read its current text above; the child slots remain unpopulated.
Table11 control board connections; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
-
row 2, column 4 share the source cell at row 1, column 4. Read its current text above; the child slots remain unpopulated.
-
row 7, column 4 share the source cell at row 6, column 4. Read its current text above; the child slots remain unpopulated.
Table10 power board connections — PDF page 19
| Source row | Terminal number | Contact designation | Function | Electrical characteristics |
|---|---|---|---|---|
| 1 | PE | ⟦blank source cell⟧ | Protective Earth | Protective grounding |
| 2 | N | ⟦blank source cell⟧ | Control supply voltage | 100-240 VAC ±10% |
| 3 | L | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 4 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 5 | 21 | NO | Programmable relay 1. Factory setting is “Operation” with indication by closing contact on terminals 21 to 22. |
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC 8 A resistive, 250 VAC, 3 A inductive. See Warning. |
| 6 | 22 | C | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 7 | 23 | NO | Programmable relay 2. Factory setting is “Off” with indication by closing contact on terminals 23 to 24. |
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC 8 A resistive, 250 VAC, 3 A inductive. See Warning. |
| 8 | 24 | C | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 9 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 10 | 31 | NO | Programmable relay 3. Factory setting is “Trip”. Indication by closing contact on terminals 31 to 33 and opening contact on 32 to 33. |
1-pole change-over contact (NO/NC), 250 VAC 8A or 24 VDC 8A resistive, 250 VAC, 3A inductive. See Warning. |
| 11 | 32 | C | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 12 | 33 | NC | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 13 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 14 | 69-70 | ⟦blank source cell⟧ | PTC Thermistor input | Alarm level 2.4 kΩ. Switch back level 2.2 kΩ. |
Table11 control board connections — PDF page 19
| Source row | Terminal number | Contact designation | Function | Electrical characteristics |
|---|---|---|---|---|
| 1 | 11 | ⟦blank source cell⟧ | Digital input 1. Factory setting is “Run FWD” | 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec. Impedance: <3.3 VDC: 4.7 kΩ. - >3.3 VDC: 3.6 kΩ |
| 2 | 12 | ⟦blank source cell⟧ | Digital input 2. Factory setting is “Stop”. | ⟦null: no independent source value⟧ |
| 3 | 13 | ⟦blank source cell⟧ | Control signal supply voltage to analogue input. | +10 VDC ±5%. Max. current from +10 VDC: 10 mA. Short circuit-proof and overload-proof. |
| 4 | 14 | ⟦blank source cell⟧ | Analogue input, 0-10 V, 2-10 V, 0-20 mA and 4-20 mA. Factory setting is “4-20 mA”. S1 jumper for U/I selection. |
Impedance to terminal 15 (0 VDC) voltage signal: 20 kΩ, current signal: 250 Ω. |
| 5 | 15 | ⟦blank source cell⟧ | GND (common) | 0 VDC signal ground |
| 6 | 16 | ⟦blank source cell⟧ | Digital input 3. Factory setting is “Set Ctrl 1” | 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec. Impedance: <3.3 VDC: 4.7 kΩ. - >3.3 VDC: 3.6 kΩ |
| 7 | 17 | ⟦blank source cell⟧ | Digital input 4. Factory setting is “Reset” | ⟦null: no independent source value⟧ |
| 8 | 18 | ⟦blank source cell⟧ | Control signal supply 1, voltage to digital input. | +24 VDC ±5%. Max. current from +24 VDC = 50 mA. Short circuit-proof and overload-proof. |
| 9 | 19 | ⟦blank source cell⟧ | Analogue output. Factory setting is “Current”. | Analogue output contact: 0-10 V, 2-10 V; min load impedance 700 Ω 0-20 mA and 4-20 mA; max load impedance 500 Ω |
| 10 | 20 | ⟦blank source cell⟧ | Control signal supply 2, voltage to digital input. | +24 VDC ±5%. Max. current from +24 VDC = 50 mA. Short circuit-proof and overload-proof. |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 20
Manual reference: physical PDF page 20. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 11 Control cable feedthrough.
3.4
Wiring examples
Always ensure the installation complies with the appropriate
local regulations.
Minimum wiring for remote controlled start is shown in Fig.
19, page 30, in which level control is applied, menu [21A].
Example 1: Standard type of start wiring
•
Connect Protective Earth (PE) to earth bar marked PE
and Motor earth the earth bar marked
see chapter
3.1 page 12.
Connect the softstarter between the 3-phase mains
supply (L1, L2 and L3) and the motor (T1, T2 and T3).
Connect the control supply voltage (100-240 VAC) to
terminals N and L and the protective earth wire to
terminal PE.
Connect start and stop control to DigIn 1 and 2
(terminals 11 and 12) with 24 V supplied from terminal
18.
Connect relay R1 (terminals 21 and 22) to the contactor
– the softstarter then controls the mains contactor (for
factory configuration of R1).
.
Fig. 12 Standard wiring example.
NOTE: Shielded control cable must be used for option
board connections.
U I
Shielded control signal cable
Earthing
plate with
slots for tie
wraps
NOTE: If local regulations state that a mains contactor should be used, relay R1 can control this. Always use standard
commercial, slow blow fuses, e.g. gl or gG types, to protect the wiring and prevent short circuiting. To protect the thyristors
against short-circuit currents, ultrafast semiconductor fuses can be used if preferred. The normal guarantee is valid even if
ultrafast semiconductor fuses are not used. All signal inputs and outputs are galvanically insulated from the mains supply.
DigIn 1
DigIn 2
+10 V
AnIn
GND
DigIn 3
DigIn 4
+24 V
AnOut
Relay 1
Relay 2
Relay 3
Stop
Run FWD
PTC
Figure11U/Ijumper,earthplate/tiewrapslots,shieldedcontrolcable. Figure12mainsL1,L2,L3/PE;separate100–240V~±10%L,N,PE;relayR1(21,22),R2(23,24),R3(33,31,32);PTC69,70;control11DigIn1RunFWD,12DigIn2Stop,13+10V,14AnIn,15GND,16DigIn3,17DigIn4,18+24V,19AnOut,20+24V. Figureisexample,notindependentvalidatedwiring.
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 21
Manual reference: physical PDF page 21. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example 2: Extended wiring
Fig. 13 gives a wiring example with the following functions:
•
Analogue start/stop via process value, see description on
page 91.
Analogue output, see section 8.5.3, page 95
Motor PTC input, see description of Thermal motor
protection in section 8.2.4, page 62.
Fig. 13 Extended wiring example, using digital and analogue inputs and outputs.
Reset
Stop
Measuring
Process value
DigIn 1
DigIn 2
+10 V
AnIn
GND
DigIn 3
DigIn 4
+24 V
AnOut
PTC
Relay 1
Relay 2
Relay 3
Run FWD
Figure13extendsstandardexample:Resetbetween17and18;processvalue+to14and−to15;Measuring+to19and−to20asdrawn;motorPTC69/70. Table11describes20as+24V,so measuredreturnlabelassociationisretainedasdiagramclaim,notapprovedconnection. RemainingterminalsandrelayssameprintedlabelsasFig12.
Extended wiring example settings; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Extended wiring example settings — PDF page 21
| Source row | Menu | Description | Setting |
|---|---|---|---|
| 1 | 521 | Digital input 1 (terminal 11) | Run FWD (default) |
| 2 | 522 | Digital input 2 (terminal 12) | Stop (default) |
| 3 | 524 | Digital input 4 (terminal 17) | Reset (default) |
| 4 | 511 | Analogue input function (terminal 14) |
Process Val (default) |
| 5 | 531 | Analogue output function (terminal 19) |
Current (default) |
| 6 | 2331 | PTC alarm action (terminal 69 and 70) |
Hard trip/Soft trip |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 22
Manual reference: physical PDF page 22. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example 3: Reverse current brake wiring
The example in Fig. 14 shows the wiring for a reverse
current brake functionality. For further settings, see the
description for “Dynamic Vector Brake” on page 81.
The contactors have to be controlled by the relay outputs of
the softstarter. For relay settings, see menu [550] and Fig. 54,
page 99. The relay (R1) for the first mains contactor (K1) is
set to “RunSignalFWD” in menu [551], and will control the
mains contactor (K1). The second mains contactor (K2) is
controlled by another relay (R2), that is set to
“RevCurrBrake” in menu [552]. During start and full voltage
operation the first contactor (K1) will be activated (Fig. 14,
page 18). For braking R1 will open and the second contactor
(K2) will be activated via R2 to change the phase sequence.
Fig. 14 Reverse current brake wiring example.
DigIn 1
DigIn 2
+10 V
AnIn
GND
DigIn 3
DigIn 4
+24 V
AnOut
Relay 1
Relay 2
Relay 3
Run FWD
Stop
PTC
Figure14showsK1mainandK2phase-reversingcontactors controlledbyR1(21/22)andR2(23/24);R3labels33,31,32;100–240V~±10%L,N,PE;PTC69/70;RunFWD11,Stop12,24V18. MainsL1/L2/L3,motorT1/T2/T3→U/V/W/earth. Physicalwiringgeometryremainssourceonly.
Reverse current brake example settings; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Reverse current brake example settings — PDF page 22
| Source row | Menu | Description | Setting |
|---|---|---|---|
| 1 | 521 | Digital input 1 (terminal 11) | Run FWD (default) |
| 2 | 522 | Digital input 2 (terminal 12) | Stop (default) |
| 3 | 551 | Relay 1 (terminals 21 and 22) | RunSignalFWD |
| 4 | 552 | Relay 2 (terminals 23 and 24) | RevCurrBrake |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 23
Manual reference: physical PDF page 23. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example 4: Reverse start functionality
The digital inputs can be configured to enable starting a
motor in two different directions with the use of the
programmable relays R1 and R2. A connection example is
shown in Fig. 15. For the following description of start
forward/reverse functionality, the following settings for the
digital inputs are assumed.
.
Fig. 15 Connection for start forward/reverse.
The configuration of the relays depends on the requirements
of the application. For applications which do not use the
reverse current brake functionality, the following settings
may be used.
The functionality for both applications (with or without
reverse current functionality) is as follows:
If DigIn 1 “RunFWD” is closed and DigIn 3 “RunREV” is
open, the mains contactor (K1) for running in forward
direction will be activated by relay R1, and the motor will
start in forward direction. DigIn 1 “RunFWD” can be
opened during forward running without any effect. If DigIn
2 “Stop” is opened, the stop settings in menu group [340]
CAUTION!
Very high torque/force can arise when the
motor is reversed from running at full speed
in one direction to running at full speed in the
opposite direction.
WARNING!
If configured according to the description,
relays R1 and R2 will never be activated at
the same time. There is a time delay of 100
ms for the change-over between the relays. However, if
the relays are not configured properly, they may be
activated at the same time.
!
Run FWD
Run REV
Stop
DigIn 1
DigIn 2
+10 V
AnIn
GND
DigIn 3
DigIn 4
+24 V
AnOut
PTC
Relay 1
Relay 2
Figure15forward/reverseexample:K1/K2contactors;RunFWDinput11,Stop12,RunREV16,switchcommons+24V18;sameR1/R2/R3/PTCterminalnumbersaspreviousfigures. Sourcewarnsofhighreversingtorqueand100mschangeoverconditionaloncorrectconfiguration. Figureisnotcertifiedsafetycircuit.
Reverse start digital input example settings; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Reverse start relay settings without reverse-current brake; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Reverse start digital input example settings — PDF page 23
| Source row | Menu | Description | Setting |
|---|---|---|---|
| 1 | 521 | Digital input 1 (terminal 11) | Run FWD (default) |
| 2 | 522 | Digital input 2 (terminal 12) | Stop (default) |
| 3 | 523 | Digital input 3 (terminal 16) | Run REV |
Reverse start relay settings without reverse-current brake — PDF page 23
| Source row | Menu | Description | Setting |
|---|---|---|---|
| 1 | 551 | Relay 1 (terminals 21 and 22) | Operation FWD |
| 2 | 552 | Relay 2 (terminals 23 and 24) | Operation REV |
Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 24
Manual reference: physical PDF page 24. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
will be performed. When the stop is finished, the mains
contactor for running forward (K1) will be deactivated by
relay R1.
If both DigIn 1 “Stop” and DigIn 3 “RunREV” are closed
while DigIn 1 “RunFWD” is open, the mains contactor for
running in reverse direction (K2) will be activated by relay
R2 and the motor will start in reverse direction. DigIn 3
“RunREV” can be opened during reverse running without
any effect. If DigIn 2 “Stop” is opened, a stop according to
the stop settings in menu group [340] will be performed.
When the stop is finished, the mains contactor for reverse
running (K2) will be deactivated by relay R2.
If both DigIn 1 “RunFWD” and DigIn 3 “RunREV” are
closed at the same time, a stop is performed according to the
stop settings in menu group [340]. In this case no start will
be allowed.
A motor can switch from forward to reverse direction as
follows: Open DigIn 1 “RunFWD” while the motor is
running in forward direction. Then close DigIn 3
“RunREV”. As a result the voltage to the motor is switched
off and the mains contactor for forward running (K1) is
deactivated by relay R1. After a time delay of 100
milliseconds, the mains contactor for reverse running (K2)
will be activated by relay R2, and a start in reverse direction
will be performed. The motor can switch from reverse to
forward running in the same way by opening DigIn 3
“RunREV” while running in reversed direction and then
closing DigIn 1 “RunFWD”.
Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 25
Manual reference: physical PDF page 25. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.
Application guidelines
This chapter is a guide to selecting the correct softstarter
rating and softstarter functionality for different applications.
To make the right choice the following tools are used:
The AC-53 norms
The AC-53 norms are defined in the EN(IEC) 60947-4-
2:2007 standard for electronic softstarters. The purpose of
these norms is to aid in selecting a softstarter with regards to
duty cycle, starts per hour and maximum starting current.
The Applications Rating List
With this list the Emotron TSA softstarter rating type can be
selected depending on the type of application uses, see Table
12, page 22.
The Applications Function List
This table gives an overview of the most common
applications and their challenges. For each application
Emotron TSA softstarter settings are proposed, with
references to the menus used. See Table 13, page 24.
4.1
Softstarter dimensioning
according to AC-53b
The EN(IEC) 60947-4-2:2007 standard defines AC-53b as
a norm for dimensioning of softstarters for continuous
running with a bypass contactor. This is the norm for which
the Emotron TSA is designed.
AC-53b rating example
Explanation of the rating designation (see also Fig. 16):
-
Rated current (FLC) of softstarter, [Ampere]
-
Classification (AC-53b for all Emotron TSA models)
-
Start current expressed as a multiple of FLC
-
Start time, [seconds]
-
Bypass time, [seconds]
The example concerns Emotron TSA model 52-056, used
for a pump application. The rating designation indicates a
current rating of 56 A with a start current ratio of 3.0 x FLC
(168 A) for 30 seconds, and with a 330 seconds (5.5
minutes) interval between starts (current via bypass
contactors).
Fig. 16 Duty cycle.
4.2
Applications rating
According to the AC-53b norm a softstarter can have several
current ratings. The Applications Rating List in Table 12,
page 22 shows which rating that is recommended for the
application.
The Emotron TSA model is selected depending on its model
size and on the duty cycle of the application:
AC-53b ratings for Emotron TSA size 1:
•
AC-53b 3.0-15:345 (normal duty with bypass)
AC-53b 5.0-15:345 (heavy duty with bypass)
AC-53b ratings for Emotron TSA size 2 - 6:
AC-53b 3.0-30:330 (normal duty with bypass)
AC-53b 5.0-30:330 (heavy duty with bypass)
Example:
In the previous example, in which the Emotron TSA 52-056
is used for a pump application, the recommended rating is
“normal duty” according to the Applications Rating List.
56 A: AC-53b 3.0 - 30 : 330
①
②
③
④
⑤
NOTE: To select softstarter size it is important to ensure
that not only FLC (Full Load Current) is checked but also
the starting requirements.
Start
Bypass
Time
Start current
Current
operation
Figure16dutycycle plotaxesCurrentI[A],TimeT[s];pulsesStartcurrent,StartintervalandBypassoperation. Rating56A:AC-53b3.0-30:330 examplecallouts1ratedFLC,2classification,3startcurrentmultiple,4startseconds,5bypassseconds;3×56=168A sourceexample. Noadditionalgraphthresholdsinferred.
Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 26
Manual reference: physical PDF page 26. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Applications Rating List
This list gives the typical rating type for the machine or
application, divided in “normal duty” and “heavy duty”
applications (both with bypass). If the machine or
application is not in this list, try to identify a similar
machine or application. If in doubt please contact your
Emotron TSA supplier.
Example:
If the Emotron TSA 52-056 from the previous example is
used in e.g. a roller mill application instead, it would be
rated differently according to the Applications Rating List.
Due to high starting current a roller mill is considered a
heavy duty application, which places greater demands on the
softstarter. The technical data (page 139) indicates that the
TSA 52-056 is downrated to 33 A FLC for heavy duty
applications. If an FLC current of about 56 A is required for
the roller mill, it would be recommended to choose TSA
model 52-100, for which the rated heavy duty current is 60
A.
Table 12
Table12 applications rating list; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Table12 applications rating list — PDF page 26
| Source row | Industry | Normal duty cycle AC53b-3.0 | Heavy duty cycle AC53b-5.0 |
|---|---|---|---|
| 1 | General & Water | Centrifugal pump Submersible pump Compressor, screw Compressor, reciprocating Fan Blower |
Conveyor Mixer Agitator |
| 2 | Metals & Mining | Dust collector Grinder |
Belt conveyor Hammer mill Rock crusher Roller conveyor Roller mill Tumbler Wire draw machine |
| 3 | Food processing | Bottle washer Slicer |
Centrifuge Dryer Mill Palletiser |
| 4 | Pulp & Paper | ⟦blank source cell⟧ | Repulper Shredder Trolley |
| 5 | Lumber & Wood | ⟦blank source cell⟧ | Bandsaw Chipper Circular saw Debarker Planer Sander |
| 6 | Petrochemical | ⟦blank source cell⟧ | Ball mill Centrifuge Extruder Screw conveyor |
| 7 | Transport & Machine | ⟦blank source cell⟧ | Ball mill Grinder Material conveyor Palletiser Press Roller mill Rotary table Trolley Escalator |
Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 27
Manual reference: physical PDF page 27. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.3
The Application Functions List
This list gives an overview of many different applications
with their challenges and a possible solution within the
functions of the Emotron TSA.
Description and use of the table:
“Application”
This column gives the various applications. If the machine
or application is not found in this list, try to identify a
similar machine or application. If in doubt please contact
your supplier.
“Challenge”
This column describes possible challenges that are familiar
for this kind of application.
“Emotron TSA Solution”
This column gives the possible solution for the challenge
using one of the functions of the Emotron TSA.
“Menu/Chapter”
This column guides you to the menu, menu group, or
manual section where you find a description of the settings
for the function.
For instance "331=Sqr Torq Ctr", means: set parameter
[331] to “Sqr Torq Ctr.”
Example: Hammer mill
•
Linear torque control (menu [331], selection ”Lin Torq
Ctr”) will give the best results.
Torque boost to overcome high breakaway torque (menu
[337], submenus [3371]and [3372]).
Overload alarm function for jamming protection (menu
[410] “Load Monitor”, with submenus for maximum
alarm)
Stop function reverse current brake (set “Stop Method”
[341] to “Brake”, and menu [344] to “Rev Curr Brk”). It is
possible to set a “Reversed Current Braking Delay” in menu
[346].
Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 28
Manual reference: physical PDF page 28. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
.
Table 13
Application Functions List
Table13 application functions; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 2, column 1, row 3, column 1, row 4, column 1, row 5, column 1, row 6, column 1 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 8, column 1, row 9, column 1, row 10, column 1, row 11, column 1 share the source cell at row 7, column 1. Read its current text above; the child slots remain unpopulated.
-
row 14, column 1, row 15, column 1, row 16, column 1, row 17, column 1, row 18, column 1 share the source cell at row 13, column 1. Read its current text above; the child slots remain unpopulated.
-
row 20, column 1, row 21, column 1, row 22, column 1, row 23, column 1 share the source cell at row 19, column 1. Read its current text above; the child slots remain unpopulated.
-
row 20, column 3 share the source cell at row 19, column 3. Read its current text above; the child slots remain unpopulated.
-
row 20, column 4 share the source cell at row 19, column 4. Read its current text above; the child slots remain unpopulated.
-
row 23, column 3 share the source cell at row 22, column 3. Read its current text above; the child slots remain unpopulated.
-
row 23, column 4 share the source cell at row 22, column 4. Read its current text above; the child slots remain unpopulated.
-
row 25, column 1, row 26, column 1, row 27, column 1, row 28, column 1, row 29, column 1 share the source cell at row 24, column 1. Read its current text above; the child slots remain unpopulated.
-
row 26, column 2 share the source cell at row 25, column 2. Read its current text above; the child slots remain unpopulated.
Table13 application functions — PDF page 28
| Source row | Application | Challenge | Emotron TSA Solution | Menu/Chapter |
|---|---|---|---|---|
| 1 | PUMP | Non-linear ramps | Square torque control for square loads | 331=Sqr Torq Ctr 341=Sqr Torq Ctr |
| 2 | ⟦null: no independent source value⟧ | Water hammer | Square torque control | 340 |
| 3 | ⟦null: no independent source value⟧ | High current and peaks during starts | Square torque control | 330 |
| 4 | ⟦null: no independent source value⟧ | Pump is going in wrong direction | Phase reversal alarm | 444 |
| 5 | ⟦null: no independent source value⟧ | Dry running | Use load monitor minimum alarm | 410 |
| 6 | ⟦null: no independent source value⟧ | High load due to dirt in pump | Use load monitor maximum alarm | 410 |
| 7 | COMPRESSOR | Mechanical shock for compressor, motor and transmissions |
Linear torque control | 330 |
| 8 | ⟦null: no independent source value⟧ | Small fuses and low current available. | Linear torque control and current limit at start. |
331=Lin Torq Ctr 335 |
| 9 | ⟦null: no independent source value⟧ | Screw compressor going in wrong direction | Phase reversal alarm | 444 |
| 10 | ⟦null: no independent source value⟧ | Damaged compressor if liquid ammonia enters the compressor screw. |
Use load monitor maximum alarm | 410 |
| 11 | ⟦null: no independent source value⟧ | Energy consumption due to compressor running unloaded |
Use load monitor minimum alarm | 410 |
| 12 | BLOWER | Mechanical shock for blower, motor and transmissions. High start current requires large cables and fuses. |
Torque control ensures smooth starts that minimise mechanical stress. Start current is minimised by torque- controlled start. |
331=Lin Torq Ctr |
| 13 | CONVEYOR | Mechanical shocks for transmissions and transported goods. |
Linear torque control | 330 |
| 14 | ⟦null: no independent source value⟧ | Loading or unloading conveyors | Slow speed and accurate position control. |
350 600 |
| 15 | ⟦null: no independent source value⟧ | Conveyor jammed | Use load monitor maximum alarm | 410 |
| 16 | ⟦null: no independent source value⟧ | Conveyor belt or chain is off but the motor is still running |
Use load monitor minimum alarm | 410 |
| 17 | ⟦null: no independent source value⟧ | Starting after screw conveyor has stopped due to overload. |
JOG in reverse direction and then starting in forward. |
7.1, p. 39 |
| 18 | ⟦null: no independent source value⟧ | Conveyor blocked when starting | Locked rotor function | 422 |
| 19 | FAN | High starting current in end of ramps | Square torque control for square load characteristics |
330 |
| 20 | ⟦null: no independent source value⟧ | Slivering belts. | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 21 | ⟦null: no independent source value⟧ | Fan is going in wrong direction when starting. | Catching the motor and stopping smoothly to zero speed and then starting in right direction. |
331=Sqr Torq Ctr |
| 22 | ⟦null: no independent source value⟧ | Belt or coupling broken | Use load monitor minimum alarm | 410 |
| 23 | ⟦null: no independent source value⟧ | Blocked filter or closed damper. | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 24 | PLANER | High inertia load with high demands on torque and current control. |
Linear torque control gives linear acceleration and low starting current. |
330 |
| 25 | ⟦null: no independent source value⟧ | Need to stop quickly both for emergency and production efficiency reasons. |
Dynamic vector brake without contactor for medium loads. |
341=Brake 344=Dyn Vect Brk 347 |
| 26 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Reverse current brake with external contactor for heavy loads. |
341=Brake 344=Rev Curr Brk |
| 27 | ⟦null: no independent source value⟧ | High speed lines | Conveyor speed set from planer shaft power analogue output. |
530 |
| 28 | ⟦null: no independent source value⟧ | Worn out tool | Use load monitor maximum alarm | 410 |
| 29 | ⟦null: no independent source value⟧ | Broken coupling | Use load monitor minimum alarm | 410 |
Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 29
Manual reference: physical PDF page 29. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 13
Application Functions List
Table13 application functions continued; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 2, column 1, row 3, column 1, row 4, column 1, row 5, column 1 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 7, column 1, row 8, column 1, row 9, column 1, row 10, column 1, row 11, column 1 share the source cell at row 6, column 1. Read its current text above; the child slots remain unpopulated.
-
row 8, column 2 share the source cell at row 7, column 2. Read its current text above; the child slots remain unpopulated.
-
row 13, column 1, row 14, column 1, row 15, column 1, row 16, column 1 share the source cell at row 12, column 1. Read its current text above; the child slots remain unpopulated.
-
row 15, column 2 share the source cell at row 14, column 2. Read its current text above; the child slots remain unpopulated.
-
row 18, column 1, row 19, column 1, row 20, column 1 share the source cell at row 17, column 1. Read its current text above; the child slots remain unpopulated.
-
row 22, column 1, row 23, column 1, row 24, column 1, row 25, column 1 share the source cell at row 21, column 1. Read its current text above; the child slots remain unpopulated.
-
row 22, column 2 share the source cell at row 21, column 2. Read its current text above; the child slots remain unpopulated.
Table13 application functions continued — PDF page 29
| Source row | Application | Challenge | Emotron TSA Solution | Menu/Chapter |
|---|---|---|---|---|
| 1 | ROCK CRUSHER | High inertia | Linear torque control gives linear acceleration and low starting current. |
330 |
| 2 | ⟦null: no independent source value⟧ | Heavy load when starting with material | Torque boost | 337 |
| 3 | ⟦null: no independent source value⟧ | Low power if a diesel powered generator is used. |
Current limit at start | 335 |
| 4 | ⟦null: no independent source value⟧ | Wrong material in crusher | Use load monitor maximum alarm | 410 |
| 5 | ⟦null: no independent source value⟧ | Vibrations during stop | Dynamic vector brake without contactor | 341=Brake 344=Dyn Vect Brk 347 |
| 6 | BANDSAW | High inertia load with high demands on torque and current control. |
Linear torque ramp gives linear acceleration and low starting current. |
330 |
| 7 | ⟦null: no independent source value⟧ | Need to stop quickly. | Dynamic vector brake without contactor for medium loads. |
341=Brake 344=Dyn Vect Brk 347 |
| 8 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Reverse current brake with external contactor for heavy loads. |
341=Brake 344=RevCurr Brk |
| 9 | ⟦null: no independent source value⟧ | High speed lines | Conveyor speed set from bandsaw shaft power analogue output. |
530 |
| 10 | ⟦null: no independent source value⟧ | Worn out saw blade | Use load monitor maximum alarm | 410 |
| 11 | ⟦null: no independent source value⟧ | Broken coupling, saw blade or belt | Use load monitor minimum alarm | 410 |
| 12 | CENTRIFUGE | High inertia load | Linear torque control gives linear acceleration and low starting current. |
330 |
| 13 | ⟦null: no independent source value⟧ | Too high load or unbalanced centrifuge | Use load monitor maximum alarm | 410 |
| 14 | ⟦null: no independent source value⟧ | Controlled stop | Dynamic vector brake without contactor for medium loads. |
341=Brake 344=Dyn Vect Brk 347 |
| 15 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Reverse current brake with external contactor for heavy loads. |
341=Brake 344=Rev Curr Brk |
| 16 | ⟦null: no independent source value⟧ | Need to open centrifuge in a certain position. | Braking down to slow speed and then positioning control. |
340, 350 600, 650 |
| 17 | MIXER | Different materials | Linear torque control gives linear acceleration and low starting current |
330 |
| 18 | ⟦null: no independent source value⟧ | Need to control material viscosity | Shaft power analogue output | 530 |
| 19 | ⟦null: no independent source value⟧ | Broken or damaged blades | Use load monitor maximum alarm | 410 |
| 20 | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | Use load monitor minimum alarm | 410 |
| 21 | HAMMER MILL | Heavy load with high breakaway torque | Linear torque control gives linear acceleration and low starting current. |
331=Lin Torq Ctr |
| 22 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Torque boost in beginning of ramp. | 337 |
| 23 | ⟦null: no independent source value⟧ | Jamming | Use load monitor maximum alarm | 410 |
| 24 | ⟦null: no independent source value⟧ | Fast stop | Reverse current brake with reversing contactor for heavy loads. |
341=Brake 344=Rev Curr Brk |
| 25 | ⟦null: no independent source value⟧ | Motor blocked | Locked rotor function | 422 |
Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 30
Manual reference: physical PDF page 30. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.4
Special conditions
4.4.1 Small motor or low load
The minimum load current for the Emotron TSA softstarter
is 10% of the rated current for the softstarter. An exception
is the TSA52-016 for which the minimum load current is
2 A.
Example: TSA52-056 with rated current of 56 A has a
minimum current of 5.6 A.
Please note that this is “minimum load current” and not
minimum rated motor current.
4.4.2 Ambient temperature below
0°C
For ambient temperatures below 0 °C an electric heater or
similar must be installed in the cabinet. The softstarter can
be mounted remotely from the motor since the distance
between the motor and the softstarter is not critical.
4.4.3 Pump control with softstarter
and AC drive together
It is possible, e.g. in a pump station with two or more
pumps, to use one Emotron FDU AC drive on one pump
and softstarters on each of the other pumps. The flow of the
pumps is then controlled by the pump control function in
the Emotron FDU.
4.4.4 Starting with counter-
clockwise (reverse) rotating
loads
It is possible to start a motor clockwise (forward direction),
even if the load and motor are rotating counterclockwise
(reverse direction), e.g. fans. Depending on the speed and
the load “in the wrong direction”. Pleas note that the current
can be quite high.
4.4.5 Running motors connected in
parallel
When starting and running motors connected in parallel,
the total amount of the motor current must be equal or
lower than the rating of the connected softstarter. Please
note that it is not possible to use the internal thermal motor
protection or use other individual settings for each motor.
For instance, the start ramp can only be set for an average
starting ramp for all the connected motors. This means that
the start time may differ from motor to motor. Similarly, the
load monitor alarm levels/margins are applied for the
average shaft power value of the connected motors. In order
to work around this kind of problem, it could be necessary
to deactivate a number of functions and alarms.
For motors connected in parallel, torque control is not
recommended because of the risk of oscillation between the
motors. Voltage control with or without current limit is
recommended instead. The use of the braking functionality
is not recommended for motors connected in parallel.
4.4.6 Running motors linked
together
When starting and running motors mechanically linked
together but with one softstarter connected to each motor,
there are two kinds of operations available. The first is to
start the motors at the same time using voltage control with
or without current limit. The second is to start one motor
first with torque or voltage control and after the motor has
reached full speed, the voltage to the other motors is ramped
up using voltage control.
4.4.7 Heat dissipation in cabinets
For guidelines regarding calculation of heat dissipation in
cabinets, please contact your cabinet supplier. The required
data is found in “Technical Data”, Chapter 13. page 139.
4.4.8 Insulation test on motor
When testing the motor with high voltage e.g. insulation
test, the softstarter must be disconnected from the motor.
This is due to the fact that the softstarter will be seriously
damaged by the high test voltage.
4.4.9 Operation above 1,000 m
All ratings are stated for operation at maximum 1,000 m
over sea level.
If the softstarter is operated at 3,000 m for example, it must
be derated, and it is likely that a higher rated model than
normal is required to fulfil the task. See further information
in section 13.3.2, page 143.
4.4.10 Aggressive environment
conditions
As standard the Emotron TSA is equipped with coated
boards in order to reduce the risk for corrosion. For
specification, see section 13.3, page 142.
4.4.11 IT earthing system
Distribution systems may be equipped with an IT isolated
earthing system, which allows for one earth fault to occur
without interruption of operation. For use in these systems,
the Emotron TSA should be ordered with IT-net option.
If you have a softstarter without IT net option, the
softstarter can be rebuilt. Contact your local CG Drives &
Automation service partner.
Manual — P036; Application guidelines continuation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 31
Manual reference: physical PDF page 31. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.4.12Earth fault relay
It is possible to use an earth fault relay to protect motor and
cables (not for human safety). To avoid undesired tripping
due to filter capacitor charging currents, choose a short-time
delayed residual current device rated for 30 mA leakage
current.
4.4.13Other control voltage
The power board must be connected to 100-240 VAC single
phase control supply. If this is not available a transformer
must be used. This transformer should be connected as in
Fig. 17.
The transformer should be capable of supplying a power of
50 VA or more. This item is not included in the range of
CG options.
Fig. 17 Example of wiring when using transformer for 380 - 500 VAC
Transformer
Emotron TSA
Figure17 source example transformer input380–500VAC, output100–240VAC toTSA control supply. Transformer minimum50VA per adjacenttext. Wiringgeometry remainsoriginal; no design inferred.
Manual — FOOTER_ONLY_PAGE — page 32
Manual reference: physical PDF page 32. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 28 | Application guidelines | CG Drives & Automation 01-5924-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Getting started. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 33
Manual reference: physical PDF page 33. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
5.
Getting started
This chapter is a step by step guide that will show you the
quickest way to get the motor shaft turning. We will show
you two examples: with remote control and control panel
operation.
5.1
Check list
•
Check that the motor and supply voltage corresponds to
the values on the rating plate of the softstarter.
Mount the softstarter (Chapter 2. page 9 ).
Connect the 3-phase mains supply cables to the connec-
tions on top of the softstarter (section 3.1, page 12).
Connect the motor cables to the connections in the
bottom of the softstarter (section 3.1, page 12).
Connect control supply voltage (section 3.1, page 12).
Ensure that the installation complies with the
appropriate local regulations.
Remote (I/O) operation:
Connect the I/O control cables (section 3.3, page 15).
Switch on the 3-phase mains supply voltage and control
supply voltage.
Select language (menu [211], section 8.2.1, page 57).
Set the motor data (menu [220] - [227], section 8.2.3,
page 60).
Set real time clock (menu [740], section 8.7.4, page 119)
Perform a test run with external I/O start command.
Control panel operation:
Select keyboard control (menu [2151], section 7.1.1,
page 39).
Perform a test run from the control panel.
5.2
Mains and motor
connection
Connect the softstarter between the 3-phase mains supply
and the motor. For the respective connections, see the table
below).
Dimension the mains and motor cables according to local
regulations. The cables must be able to carry the softstarter
load current (see “Technical data” on page 139).
5.2.1 Connect the mains cables
The connection of the mains cables is shown in section 3.1,
page 12. As standard the Emotron TSA softstarter has a
built-in RFI mains filter that complies with category C1
which is suited for environment B.
5.2.2 Connect the motor cables
The connection of the motor cables is shown in section 3.1,
page 12.
5.2.3 Connect the control supply
voltage
The control supply voltage is connected to the terminals
marked N and L on the power board (Fig. 19).
WARNING!
Mounting, wiring and setting the device into
operation must be carried out by properly
trained and qualified personnel.
Table 14
Mains and motor connection
In order to work safely the mains earth must
be connected to PE and the motor earth to
.
Table14 secondrow contains earthsymbol beneathT1,T2,T3, associated withMotor earth. Warning calls mains earthPE andmotor earthsymbol. Native symbol omission is not an absent protective-earth requirement.
Table14 mains and motor connections; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Table14 mains and motor connections — PDF page 33
| Source row | Terminal marking | Connection |
|---|---|---|
| 1 | L1, L2, L3 PE |
Mains supply, 3-phase Protective earth |
| 2 | T1, T2, T3 | Motor output, 3-phase Motor earth |
Manual — P036; Getting started. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 34
Manual reference: physical PDF page 34. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
5.3
Default toggle loop
In order to make it easier to setup the initial data, there is a
default toggle loop, see Fig. 18. This loop contains the
necessary menus that need to be set before starting the
softstarter the first time. Press the Toggle key to enter e.g.
menu [740], then use the next keys to go to the submenus
([741] and so forth) and enter the parameters. When you
press the Toggle key again, the next toggle menu is
displayed.
Fig. 18 Default toggle loop
5.4
Remote I/O operation
Generally, external signals are used to control the softstarter
and the motor. This example demonstrates the set-up for a
standard motor for which an external start button will be
used.
Connect the control signal cables
The minimum wiring for a remote controlled start is shown
in Fig. 19 below. In this example the motor/softstarter will
run with forward rotation. For other wiring examples, see
section 3.4, page 16.
It is recommended to use screened control signal cables with
flexible wire up to 1.5 mm2, or solid wire up to 2.5 mm2.
Connect an external start button between terminal 18 (+24
VDC) and 11 (DigIn 1, Run FWD). Change the setting in
menu [21A] to “Level” (level control). Change setting for
DigIn 2 in menu [522] to “Off”.
Fig. 19 Minimum wiring for remote controlled start using
level control.
Switch on the voltage
Once the 3-phase mains and control supply voltage is
switched on, the softstarter is started and the internal fan
(only in model sizes 2-6) will run for 5 seconds.
Set the basic data
Fig. 20 Default toggle loop
Enter the basic data, i.e. language, time, and motor data for
the connected motor. The motor data is used in the
calculation of complete operational data in the softstarter.
Change settings using the keys on the control panel. For
further information about the control panel and menu
structure, see Chapter 6. page 33.
NOTE: Default setting is edge control (menu [21A] set to
“Edge”) in order to comply with the Machine directive.
Toggle loop
To submenus
Start /Stop
Power board
Control board
100-240V
PE
Figures18/20 toggle loop:100→211→221→222→223→224→225→227→740→100, with740submenus741→… viaNEXT. Figure19 Start/Stop switch connects18(+24V) to11;21A→Level,522→Off. Power terminalsPE,01,02; diagramcontrol100–240V. Example only.
Manual — P036; Getting started. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 35
Manual reference: physical PDF page 35. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Menu [100], “Preferred View” is displayed at start.
- Press
to display menu [211] “Language”.
Select Language using the
and
keys.
Confirm with
.
- Press
to display menu [221] “Motor Volts” and set
nominal motor voltage. Change the value using the
keys. Confirm with
Perform in a similar way the following settings:
-
Set motor frequency [222].
-
Set motor power [223].
-
Set motor current [224].
-
Set motor speed [225].
-
Set power factor (cos φ) [227].
-
Press
to display menu [740]”Clock setting”.
- Press
to display menu [741]” Time”. Change the
time using the
keys. To activate setting of
hh.mm.ss respectively, use the
or
- Press
to display menu [742]” Date” and set date.
-
Switch off power supply.
-
Connect digital and analogue inputs/outputs as in
Fig. 19.
- Switch on power supply.
Test run with external start command
Now the installation is finished, press the external start
button (contact closed) to start the motor.
To stop the motor, disconnect the start command (contact
open).
5.5
Control panel operation
A manual test run can be executed via the control panel.
This example demonstrates the set-up to carry out for a
standard motor.
Switch on the voltage
Once the 3-phase mains and control supply voltage is
switched on, the softstarter is started and the internal fan
(only in sizes 2-6) will run for 5 seconds.
Set the basic data
Enter the basic data, i.e. language, time, and motor data for
the connected motor. Perform this the same way as for
“Remote I/O operation” on page 30.
Follow the steps 1 - 10.
Then press
until you return to menu [100],”Preferred
View”.
Select manual control
to display menu [200], “Main Setup”.
to display menu [210], “Operation”.
- Press
until you get to menu [215] “Action Control”,
then press
to go to submenu [2151] “Run/Stop
Control”.
- Select “Int keyb” using the key
Press
to confirm.
Test run from control panel
Press the
key on the control panel to run the motor
forward.
To stop the motor, press the
key on the control panel.
NOTE: For selection of other start method than the
default “linear torque control”, see section 7.1.2, page
NOTE: When the internal bypass contactor is activated,
three distinct clicks are heard.
NOTE: For selection of other stop method than the
default “Coast”, see section 7.1.2, page 35 and menu
[341].
NQE1
TGO
Graphic-key reading: setup1Toggle→211,Plus/Minusselect,Enterconfirm;2Toggle→221,Plus/Minus,Enter;3–7menus222/223/224/225/227.8Toggle→740;9Enter→741,Plus/Minuschange,Prev/Nextselecthh.mm.ss,Enterconfirm;10Enter→742,Enterconfirm. Manualcontrol:ESCto100,Nextto200,Enterto210,Nextto215,Enterto2151,PlusIntkeyb,Enter. TestStartFWDthenStop/Reset. These are literal supplier key instructions, not revised workflow.
Manual — FOOTER_ONLY_PAGE — page 36
Manual reference: physical PDF page 36. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 32 | Getting started | CG Drives & Automation 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 37
Manual reference: physical PDF page 37. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.
Operation via the control panel
The control panel displays the status of the softstarter and is
used to set all the parameters. It is also possible to control
the motor directly from the control panel.
Fig. 21 Control panel
6.1 Display
The display is back lit and consists of 2 rows, each with
space for 16 characters. The display is divided into six areas.
The different areas in the display are described below:
Fig. 22 LC display
LCD display
LEDs
Control keys
Toggle key
Function keys
Area A:
Shows the actual menu number (3 or 4 digits).
Area B:
Shows if the menu is in the Toggle loop
(page 35), indicated with
, and/or if the soft-
starter is set for “Local” operation (page 36),
indicated with
.
Area C:
Shows the abbreviated name of the active menu,
e.g. parameter or description of the contents.
Area D:
Shows the status of the softstarter (3 charac-
ters).
The following status indications are possible:
Acc: Motor starting
Dec: Motor stopping
I2t: Active I2t motor protection
Run: Motor runs at full speed
Jog: Motor runs at jog speed
Trp: Tripped
Stp: Motor is stopped
Area E:
Shows active parameter set:
,
, or
;
and if it is a motor parameter: M1, M2, M3, or
M4.
Shows a flashing cursor when a change is being
done to the actual menu parameter.
Also shows “S” to indicate soft trip, and “A” if
max number of autoreset attempts is exceeded.
Area F:
Shows the setting or selection in the active
menu (empty at 1st level and 2nd level menus).
Shows warnings and alarm messages.
221 T
Motor Volt
Stp A M1
400V
Figure21 controls:StartREV,Stop/Reset,StartFWD;ToggleLoc/Rem;Prev,Next,ESC;MinusJogREV,PlusJogFWD,Enter. Figure22 exampleAarea221;BareaT;CareaMotorVolt;DareaStp;EareaA/M1;Farea400V. AreaB showsTtoggle/Llocal, E parameterA/B/C/D and motorM1–M4. Sourceexample400Vnotrating.
Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 38
Manual reference: physical PDF page 38. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.2 LED indicators
The three light emitting diodes below the display indicate
the operation status of the softstarter and motor/machine
(see Fig. 23). Depending on the operating mode the TRIP
and RUN indicators will also flash to alert the user about a
coming event or action. A description of the different LED
signals is given in Table 15 below.
Fig. 23 LED indicators
*) Frequency: 1 Hz=1 flash per second; 2 Hz=2 flashes per second
6.3 Control keys
The control keys are used to give the START, STOP or
RESET commands directly. As default the START and
STOP keys are disabled and the commands are set remotely
(from digital input).
To enable START commands (reverse and forward run)
from the control keys, go to the description in section 7.1.1,
page 39, menu [2151].
The RESET key is activated by default. It will remain active
as long as one of the keyboard alternatives is selected in
menu [216]).
If the “Enable” function is programmed on one of the digital
inputs, this input must be active to allow START/STOP
commands from the control panel.
6.4 Function keys
The function keys operate the menus and are also used for
programming and read-outs of all the menu settings.
RUN
(green)
TRIP
(red)
POWER
Table 15
LED indication
Table 16
Control key commands.
NOTE: It is not possible to simultaneously activate the
Run/Stop commands from the keyboard and remotely
from the terminal strip. Exception is the Jog-function
which can give a start command, see “Jog functions” on
page 40.
Table 17
Function key commands.
Table16 graphic icons correspond inroworderStartREV,Stop/Reset,StartFWD. Table17 iconsEnter,ESC,Prev,Next,MinusJogREV,PlusJogFWD. Table15 slow1Hz cell is sharedTRIPandRUN awaitingautoreset simultaneousflashing; Power hasdash. Literalgraphiccellsremainrawempty withsemanticmap.
Table15 LED indication; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Shared source cells (coordinates refer to this table):
- row 3, column 4 share the source cell at row 2, column 4. Read its current text above; the child slots remain unpopulated.
Table17 function key commands; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Table16 control key commands; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Table15 LED indication — PDF page 38
| Source row | LED symbol | ON | Normal flashing2Hz | Slow flashing1Hz | OFF |
|---|---|---|---|---|---|
| 1 | POWER (green) |
Mains supply power on |
---------------- | --------------- | Power off |
| 2 | TRIP (red) |
Softstarter tripped | Warning | Awaiting autoreset of trip (simultaneously flashing RUN and TRIP LEDs) |
No trip |
| 3 | RUN (green) | Running at full speed | Start and stop ramp | ⟦null: no independent source value⟧ | Softstarter not active |
Table17 function key commands — PDF page 38
| Source row | Graphic key symbol | Function key | Commands |
|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ENTER | Step to lower menu level. Confirm a changed setting. |
| 2 | ⟦blank source cell⟧ | ESCAPE | Step to higher menu level. Ignore a changed setting (with- out confirming). |
| 3 | ⟦blank source cell⟧ | PREVIOUS | Step to previous menu within the same level. Move cursor one position to the left. |
| 4 | ⟦blank source cell⟧ | NEXT | Step to next menu within the same level. Move cursor one position to the right. |
| 5 | ⟦blank source cell⟧ | - (MINUS) or JOG REV |
Decrease a value. Change a selection. Or: Start reverse jog function. |
| 6 | ⟦blank source cell⟧ | + (PLUS) or JOG FWD |
Increase a value. Change a selection. Or: Start forward jog function. |
Table16 control key commands — PDF page 38
| Source row | Graphic key symbol | Control key | Commands |
|---|---|---|---|
| 1 | ⟦blank source cell⟧ | START REVERSE RUN | Start with reversed (left) rotation. (Requires reversing contactor). |
| 2 | ⟦blank source cell⟧ | STOP/RESET | Stop motor. Reset softstarter (after a trip). |
| 3 | ⟦blank source cell⟧ | START FORWARD RUN | Start with forward (right) rotation. |
Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 39
Manual reference: physical PDF page 39. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.4.1 +/- key function
To manually change a value or a selection, or to enter a new
value, the “+” and “-” keys are used. For this function to be
active, the keyboard must be unlocked (as it is by default),
menu [218].
Changing parameter selection
To change selection in a menu, press the “+” or “-” keys to
scroll between the available alternatives. The cursor to the
left (area E) is flashing while doing so. To confirm a
selection, press ENTER, and the cursor will stop flashing.
Editing parameter values
Most of the parameters can be changed during operation
without stopping the softstarter.
The parameters that can not be changed during operation
are in this manual marked with a lock symbol:
.
•
To change a parameter value, press the “+” or “-” keys.
The cursor to the left is flashing while the value is
increased or decreased. If you keep the “+” or “-” keys
pressed, the value will increase or decrease continuously.
For bigger changes you can also directly select a digit
with the cursor using the PREV and NEXT keys, and
change this with the “+” or “-” keys.
Press the Toggle key to change the sign of the entered
value (only valid for certain parameters). The sign of the
value will also change when zero is passed.
Press ENTER to confirm the value. The cursor to the
left will stop flashing.
Press ESC to leave the edit mode.
Entering lock code
The lock code in menu [218] is inserted from the right to
the left, the position indicated with a cursor. The digit is set
by scrolling with the +/- keys, and the cursor is moved with
the PREV key to the left, in order to enter the next symbol.
Then the NEXT key can be used to go to the right and
change something if needed. When finished this is
confirmed with ENTER.
This method is also used for new entries in e.g. User Unit, or
Unit Name. Digits or characters are added from right to left
in the same way as described above.
6.4.2 Jog key function
The “+” and “-” keys can be programmed for jogging,
enabling a manual jog start to be done from the control
panel by pressing and holding the key.
To activate the jog key function, see instructions in “Jog
functions” on page 40.
To deactivate the jog key function, unlock the keyboard in
6.5 Toggle and Loc/Rem Key
This key has two functions: toggling between
selected menus, and switching between local
and remote operation control.
If the key is programmed for “Toggle”
(default in menu [2171]), it will only have
the toggle function.
If the key is programmed for “Loc/Rem” in menu [2171], it
can only be used to switch between local and remote control
of the softstarter.
If the key is programmed for “Combined” in menu [2171],
the key can be used for both functions in the following
manner:
Press one second to use the toggle function.
Press and hold the toggle key for more than five seconds
to enable the choice between Local or Remote function,
see section “Loc/Rem function” on page 36.
When editing parameter values, the toggle key can be used
to change the sign of the value.
6.5.1 Toggle function
Using the toggle function makes it possible to easily step
through selected menus in a loop. The toggle loop can
contain a maximum of ten menus. As default the toggle loop
contains the menus needed for Getting Started. You can also
use the toggle loop to create a quick-menu for the
parameters that are most important to your specific
application.
Add a menu to the toggle loop
-
Go to the menu you want to add to the loop.
-
Press the Toggle key and keep it pressed while also press-
ing the “+” key.
- Check that a “
” is shown to the right of the menu
number (area B).
NOTE: If you try to change a function during operation
that only can be changed when the motor is stopped, the
message “Stop First” is displayed.
NOTE: When the control panel is locked, the only menu
in which it still is possible to use the +/- keys, is [218]
“Lock Code”.
NOTE: Do not keep the Toggle key pressed for more than
five seconds without pressing either the “+”, “-”, or ESC
key, as this may activate the Loc/Rem function of this
key instead. See menu [2171].
Padlock graphic marks parameters that cannot change whilemotoroperates. Toggleloop membership iconT appearsinareaB. Lockcodeediting remainsrighttoleft. Not an assurance of security or override authority.
Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 40
Manual reference: physical PDF page 40. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Delete a menu from the toggle loop
-
Go to the menu you want to delete using the toggle key.
-
Press the Toggle key and keep it pressed while pressing
the “-” key.
- Check that there is no longer a “
” symbol to the right
of the menu number.
Delete all menus from the toggle loop
- Press the Toggle key and keep it pressed while pressing
the ESC key.
- Confirm with ENTER.
Default toggle loop
Fig. 24 shows the default toggle loop. This loop contains the
necessary menus that need to be set before starting the
softstarter the first time. Press the Toggle key to enter e.g.
menu [211], then use the NEXT key to go to the submenus
([212] and so forth) and enter the parameters. When you
press the Toggle key again, the next toggle menu is
displayed.
Fig. 24 Default toggle loop
Indication of menus in toggle loop
Menus included in the toggle loop are indicated with a
in area B of the display.
6.5.2 Loc/Rem function
With the Loc/Rem function you can change between local
and remote control of the softstarter from the control panel.
The Loc/Rem function of the key is disabled as default.
Enable the function in menu [2171].
The function Loc/Rem can also be changed via DigIn, see
menu “Digital inputs [520]”.
Change control mode
- Press the Loc/Rem key for five seconds, until “Local?” or
“Remote?” is displayed,
-
then confirm with ENTER,
-
or cancel with ESC.
When using the LOC/REM key it is important to define
what “LOCAL” and “REMOTE” will mean:
Local mode
The “LOCAL” function is set up in the menu “Local Run
Control” [2173], for which the factory default selection is
“Keyboard”. The actual status of the softstarter will not
change, e.g. Run/Stop conditions will remain exactly the
same. When the softstarter is set to Local operation, the
display will show “
“ in area B of the display (alternating
with “
” if it is also a toggle loop menu).
Remote mode
The “REMOTE” function is defined in menu [2151]
“Run/Stop Control”, where default is “Remote”.
To monitor the actual Local or Remote status of the
softstarter control, a “Loc/Rem” signal is available for the
Relays [550]. When the softstarter is set to “LOCAL”, the
signal on the relay will be active/high. In “REMOTE” the
signal will be inactive/low.
Toggle loop
To submenus
Figure24 defaultloop100→211→221→222→223→224→225→227→740→100. NEXTfrom211to212then…;Tsymbolindicatesloop. LocalmodeLalternatesTifbothapply.
Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 41
Manual reference: physical PDF page 41. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.6 The menu structure
The menu structure consists of 4 levels:
This structure is consequently independent of the number
of menus per level.
For instance, a menu can have two selectable menus (Jog
[350]), or it can have 12 selectable menus (Motor Data
[220]).
Fig. 25 Menu structure
6.6.1 The main menu
This section gives you a short description of the functions in
the main menu. For a more detailed description of the
contents under each main menu, see chapter 8. page 55.
Preferred View
Displayed at power-up, this menu shows two actual process
signals (electrical power and current as default). The menu is
programmable for many other read-outs.
Main Setup
Here you find the main settings to get the softstarter
operable, the motor data settings being the most important.
The menu group also contains protection and
communication settings.
Process
This menu contains settings more relevant to the
application, such as start, stop, and jog mode settings.
Process Protection
To protect the machine and process from damage, a number
of protection settings, such as the load monitor, can be
configured under this menu.
I/Os and Virtual Connections
Settings for inputs and outputs are entered here.
Logical Functions and Timers
A set of freely programmable blocks are available in this
section.
View Operation and Status
In this menu you can view operational data (power, torque,
current, etc.), and get status information about e.g. inputs
and outputs.
View Trip Log
Here you can see the last 9 trips in the trip memory.
System Data
This menu contains information on softstarter model and
software version.
NOTE: If there are more than 9 menus within one level,
the numbering continues with alphabetic characters (A,
B, C, ...).
Main Menu
2nd level
3rd level
4th level
Figure25 navigation main100–900;Enter400→410,Enter410→411,Enter411→4121 asprinted;ESCbacksup. NEXT/PREVcycleeachlevel;shownsubmenus420,430,4x0;412,413,414,41x;4122,412x. Diagramsourcehierarchy retained without repairing menu numbers.
Menu structure levels; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Menu structure levels — PDF page 41
| Source row | Level | Description |
|---|---|---|
| 1 | Main Menu 1st level |
The first character in the menu number. |
| 2 | 2nd level | The second character in the menu number. |
| 3 | 3rd level | The third character in the menu number. |
| 4 | 4th level | The fourth character in the menu number. |
Manual — FOOTER_ONLY_PAGE — page 42
Manual reference: physical PDF page 42. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 38 | Operation via the control panel | CG Drives & Automation, 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 43
Manual reference: physical PDF page 43. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.
Main features
This chapter contains descriptions of the main features of
the Emotron TSA softstarter.
7.1
Setting Start, Stop and
Run functions
7.1.1 Start and stop control
The start and stop control signals can be given from the
control panel using the control keys, via remote control (i.e.
programmable I/O), or via serial communication. The start
commands from the respective control sources depend on
which motor rotation direction that has been selected for the
motor (see Fig. 26). Follow the procedure in Fig. 27 for
setting of the start and stop signals.
Fig. 26 Rotation direction.
Fig. 27 Run/Stop decision tree
For configuration of programmable I/O, see the description
for the respective input/output. For a list of the different
possibilities, see section 7.4, page 51.
Local and remote control mode
An additional possibility for start and stop control is given
with the LOC/REM function of the toggle key (setting
“LOC/REM” in “Function Key” menu [2171]). It is up to
the user to define the “REMOTE” and “LOCAL” functions
in the menus for “Run/Stop Control” [2151] and “Local
Run Control” [2173]. In that respect the LOC/REM key
becomes a tool not just to alternate between the control
panel and I/O control, but actually to quickly change
between any two start and stop control locations. See
description in section 6.5.2, page 36.
7.1.2 Start and stop methods
The methods for starting and stopping the motor can be
configured in the menus [330] “Start Setting” and [340]
“Stop Setting”. See descriptions in section 8.3.3, page 78.
It is also possible to apply a “Start Limitation” [235] as part
of the actions used for protecting the softstarter. The
functions for doing this are mainly related to time settings,
e.g. limiting the numbers of starts per hour or securing a
minimum time delay between starts. For guidelines
regarding specific applications, refer to “The Application
Functions List” on page 23.
If the load monitor function [410] is activated (page 46), it
could be necessary to apply a load monitor start delay time
[417] in order to avoid faulty alarms during start-up due to
the high start current.
Spinbrake
Spinbrake can be selected as a digital input [520], see section
8.5.2, page 94. Braking is then initiated from an inactive or
active state (when running), by activating input. This means
the softstarter can catch a freewheeling motor and brake it
down to standstill.
FWD (right)
REV (left)
Figure26 FWDright/REVleft. Figure27 selectsrotation219 defaultFWD,run/stop2151 defaultRemote;externalRemote/VirtualI/O/Com branch21AdefaultEdge;keyboardinternal/externalbranchstartkeys2174/2175defaultFWD. BothbranchesFinished. Spinbrake appliesfrominactiveoractive state peradjacenttext.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 44
Manual reference: physical PDF page 44. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.1.3 Jog functions
The jog (slow speed) function can be activated
independently from a start or stop, via the control panel
using the jog keys, via remote I/O control, or via serial
communication.
To select the method to activate the jog function, follow the
procedure described in Fig. 28.
Fig. 28 Jog decision tree
It is necessary that the rotation direction settings for all
parameters involved in the jog function correlate to each
other. See Table 18 below.
1) Default value that can be changed in the respec-
tive menu.
7.1.4 Start/Stop signal priority
A jog command has lower priority than a normal start
command, meaning that if the softstarter is already running,
the jog command is ignored. If the softstarter is in jog mode,
a normal start command will override this and start the
motor to full speed.
An “Enable” command (setting via Digin [520]) has the
highest priority and overrides both a normal start/stop
command and a jog command. If “Enable” is inactive it will
not be possible to execute a normal start or a jog start. The
total priority order is listed in Table 19 below.
7.1.5 Setting motor data
For optimal performance the Emotron TSA softstarter
should be configured according to the motor’s rating plate.
The menus for this are found in section 8.2.3, page 60;
menu group [220]. The motor data is handled as a
parameter set (one of four: M1- M4). Motor M1 is selected
as default and the motor data entered will be valid for motor
M1. If different motors are used, the motor data must be
saved under different motor data sets, selected in menu
[212]. See also “Handling motor data in parameter sets” on
page 42.
7.1.6 Process information
To set up the softstarter for a process value, menu group
[320] is used, under which a process signal and its limits can
be configured.
This can be used to create start and stop commands from
process value levels.
All the actual operational data can be viewed in the menu
group [700] Operation Status. The softstarter is by default
set to present the operational data using SI units. If needed,
this could be changed to US units in menu [21C].
Table 18
Jog settings depending on rotation direction
NOTE: To jog with the control panel jog keys, press and
hold.
Table 19
Signal priority for digital inputs
Figure28 jogdecision:219FWDdefault;351/352jogspeeddefault10%;2152JogControldefaultRemote;externalRemote/Com/VirtualI/O→Finished,keyboardinternal/external→218LockkeyboardCode291→Finished. Sourcegraphcode291 retained as printed.
Table19 digital input signal priority; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Table18 jog settings by rotation direction; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Table19 digital input signal priority — PDF page 44
| Source row | Priority | Digital Input selection |
|---|---|---|
| 1 | 1 | Enable |
| 2 | 2 | Spinbrake |
| 3 | 3 | Stop |
| 4 | 4 | Run FWD and Run REV |
| 5 | 5 | Jog FWD and Jog REV |
Table18 jog settings by rotation direction — PDF page 44
| Source row | Menu | Forward Jog | Reverse Jog | Forward and reverse jog |
|---|---|---|---|---|
| 1 | 219 | FWD | REV | FWD+REV |
| 2 | 351 | 10% 1) | Off | 10% 1) |
| 3 | 352 | Off | 10% (1) | 10% 1) |
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 45
Manual reference: physical PDF page 45. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.2
Working with parameter
sets
Parameter sets can be used to set the softstarter up for
different applications such as different motors used and
connected, start and stop methods, alarm settings, control
sources, etc.
With the four parameter sets different control options can
be configured with respect to quickly changing the
behaviour of the softstarter. It is possible to adapt the
softstarter online to altered behaviour. This is based on the
fact that at any desired moment any one of the four
parameter sets can be activated during operation; via the
digital inputs or the control panel.
A parameter set consists of virtually all changeable
parameters in the menu system. Exceptions are some
parameters that can only have one and the same value,
regardless of the selected parameter set:
[211] Language, [217] Key Functionality, [218] Lock Code,
and [260] Serial Communication. These parameter settings
are global, i.e. valid throughout the menu system.
The menus for parameter set handling are found in section
8.2.5, page 66, starting with menu [240].
The active parameter set is shown in the display to the lower
left, and can also be viewed in menu [721] TSA Status. The
detailed configuration for each set can be recorded in the
menu list that can be found in the end of this manual
alternatively be downloaded from the web at
www.cgglobal.com or www.emotron.com.
7.2.1 Control of parameter sets
The parameter sets can be changed via the control panel, via
digital inputs or via serial communication. This is decided in
menu [241] Select Set.
All digital and virtual inputs can be configured to select
parameter sets. Fig. 29 shows the way the parameter sets
could be activated via digital input, where for instance DigIn
3 [523] is set to “Set Ctrl 1” and DigIn 4 [524] is set to “Set
Ctrl 2”.
Fig. 29 Selecting the parameter sets via digital input
When the parameter sets are selected via digital inputs, they
are activated as in Table 20. Activate the parameter changes
via digital input by setting menu [241] to “DigIn”.
Example: Manual and automatic control
In an application manual control is used to prepare for
service position. After service the process is switched to
automaic control mode. This can be solved by using one set
of parameters to activate manual control mode (i.e. control
signals via I/O), and a second set of parameters to activate
running in automatic control mode (i.e. control signals from
PLC via fieldbus) .
NOTE: Actual timer values are common for all sets. When
a set is changed the timer functionality will change
according to the new set, but the timer value will stay
unchanged.
Table 20
Parameter set
NOTE: The selection via the digital inputs is immediately
activated. The new parameter settings will be activated
on-line, also during Run.
NOTE: The default parameter set is parameter set A.
{
Parameter Set A
B
C
D
DI3
DI4
Set Ctrl1
Set Ctrl2
+24 V
Run/Stop
Jog Control
Braking Method
Motor Protection
Load Monitor
Figure29 parameterA/B/C/D carriesRun/Stop,JogControl,BrakingMethod,MotorProtection,LoadMonitor. ExampleDI3SetCtrl1 andDI4SetCtrl2 connectedto+24V selectsTable20;notuniversaldefaultinputassignments.
Table20 parameter set digital input selection; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Table20 parameter set digital input selection — PDF page 45
| Source row | Parameter set | Set Ctrl 1 | Set Ctrl 2 |
|---|---|---|---|
| 1 | A | 0 | 0 |
| 2 | B | 1 | 0 |
| 3 | C | 0 | 1 |
| 4 | D | 1 | 1 |
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 46
Manual reference: physical PDF page 46. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.2.2 Configuration of parameter sets
When the parameter set selection is done in menu [241], the
settings for the particular application or control mode can be
done. Parameter set A is default, which means that all
changes done to the default settings in the menu system are
saved under parameter set A.
To reset a parameter set to the default values, go to menu
[243] Default>Set and choose the extent of the reset.
When working with several parameter sets it saves a lot of
work if menu [242] Copy Set is used for copying sets, e.g.
“A>B”, “C>D”, etc. This will copy the entire contents of a
single parameter set to another parameter set, and you only
need to change the differences in the new set.
7.2.3 Handling motor data in
parameter sets
“Motor Data” (M1-M4) is a kind of parameter set in itself,
see section 7.1.5, page 40. The motor data settings are
gathered under a designated motor and belong to this.
To change the parameter set to one that includes changes in
motor data it is therefore necessary to also change motor in
Select Motor [212]. The following cases may exist:
One motor and one parameter set
This is the most common case. As default, all entered data
will be saved under parameter set A and the motor data
under motor data M1.
One motor and two parameter sets
This case is useful if you want to alternate between for
instance two control sources, or two different starting or
braking requirements.
Once default motor M1 is selected:
-
Select parameter set A in menu [241].
-
Enter motor data in menu [220].
-
Enter the settings for other parameters in set A.
-
If there are only minor differences between the
parameter sets, you can copy parameter set A to
parameter set B, menu [242].
- Enter or change the settings for parameters, other than
motor data, in set B.
Two motors and two parameter sets
This is useful if you have two different motors that are not
intended to run at the same time. One motor must stop
before changing to another motor.
-
Select motor M1 in menu [212].
-
Enter motor data and settings for other parameters.
-
Select parameter set B in menu [241].
-
Select M2 in menu [212].
-
Enter motor data and settings for other parameters.
7.2.4 Using the control panel memory
The control panel memory could come in handy when more
than one Emotron TSA unit is used. The copy/load
functions allows for transfer of data between the internal
control board of the softstarter and the control panel,
offering a quick solution for copying parameter sets and
motor data to other softstarter units. The control panel can
also be used for temporary storage or back-up copy of
settings. For description of the menu selections and the
copy/load function, see menus [244] and [245], page 67.
In order to enable transfer of data between Emotron TSA
units, there are two different set-ups.
NOTE: The two softstarters must have the same software
version. Check software version in menu [922].
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 47
Manual reference: physical PDF page 47. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Copy by moving control panel between units
To transfer data from one TSA unit to a second TSA unit via
the standard TSA control panel (see Fig. 30):
- Copy the settings from the internal control board of
TSA unit 1 to the control panel, menu [244].
- Switch off power for both TSA units, and dismount the
front covers with built in control panel.
- Disconnect the control panel cable connections from the
control board sockets.
- Connect the control panel cable of front cover 1 to TSA
unit 2, using the socket for the internal control panel.
- Switch on TSA unit 2 and load the desired settings from
control panel 1 to the internal control board of TSA unit
2, using menu [245].
Fig. 30 Copy and load parameters between two Emotron TSA units via the control panel.
WARNING!
Switch off all power connections before
opening the front cover.
TSA unit 1
TSA unit 2
Figure30 sourcecopysequence1menu244TSAunit1 internalCP1;2removefront;3moveIntCP1;4attachTSAunit2;5menu245load. Textrequirespoweroffbothbeforeopening; diagramnotadditionalpermission.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 48
Manual reference: physical PDF page 48. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Copy via external control panel
If an external control panel is available (option, page 137)
there is no need to dismount the front covers when copying
and loading data between two or more Emotron TSA units
(see Fig. 31). The external control panel is usually mounted
on the cabinet door.
- Using the external control panel, copy the settings from
the softstarter control board to the external control
panel, menu [244].
- Detach the external control panel from the cabinet of the
source softstarter and attach it to the cabinet with the
target softstarter.
- Using the external control panel, load the settings from
this to the internal control board of the target softstarter,
menu [245].
Fig. 31 Copy and load parameters between two Emotron TSA units using an external control panel (optional).
NOTE: Loading from and copying to the softstarter is
only possible when the softstarter is in stop mode.
NOTE: Another solution for copying settings and data
between different softstarter units is via PC, using the
EmoSoftCom PC tool (option). See section 12.2, page
137.
TSA unit 1
TSA unit 2
Ext CP
Figure31 externalCPcopy step1menu244TSAunit1;2moveExtCPtounit2;3menu245load. Sourceoptionalexternalcontrolpanel, stopmodeonly.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 49
Manual reference: physical PDF page 49. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.3
Applying limitations,
alarms and autoreset
In order to protect the softstarter and the connected devices,
the principal operating variables are continuously monitored
by the system. If one of these variables exceeds the safety
limit an error/warning message is displayed. In order to
avoid any possibly dangerous situations, the softstarter sets
itself into a mode called “Trip” and the cause of the trip is
shown in the display. Trips will always stop the softstarter.
7.3.1 Alarm types and actions
In general, an alarm may only be triggered when the
softstarter is active (e.g. during ramping or full speed
operation or during jogging slow speed at stop). Exceptions
are the external alarm and the communications alarm, which
are always active.
For most alarms, different alarm actions can be chosen.
Common for all alarm actions is that the alarm condition is
shown in the display, via serial communication and at any
relay programmed for the appropriate alarm functionality.
An alarm condition is indicated on the LEDs as appropriate
(see Chapter 6.2, page 34). The alarm actions are:
7.3.2 Alarm settings
To protect the motor, use the alarm settings and operation
limitations in menu [230] “Motor Protection” with
submenus. See section 8.2.4, page 62.
For protection of process, mains, and other external devices,
you find load monitor functions and alarm settings in menu
group [400]. See section 8.3, page 76.
Alarm actions for communication faults are set in menu
[264].
7.3.3 Alarm indications
Depending on which alarm condition that is active, the
following indications are given:
Warning
•
The Trip LED indicator (red triangle) on the control
panel is flashing with 2 Hz (see Table 15, page 34).
One of the status indications is displayed (area D of the
display).
The accompanying warning message is displayed (area
F). See a list of possible warning messages in Table 32,
page 117. The most recent warning message is also
displayed in menu [722] “Warning”.
The Warning relay or output is active (if selected).
Hard Trip
The softstarter is in a tripped condition and the motor
coasts down to a standstill.
The Trip LED indicator (red triangle) is lit.
The “TRP” status indication is displayed (area D of the
The accompanying trip message is displayed.
The Trip relay or output is active (if selected).
Soft Trip
stops according to the set stop method for normal
operation.
The softstarter is making a controlled stop. During the
stopping:
The accompanying trip message is displayed, including
an additional soft trip indicator “S” in area E of the
display.
The Trip LED indicator (red triangle) is flashing with 2
Hz.
After standstill is reached:
Table 21
Alarm actions
Alarm trip warning definitions; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Table21 alarm actions; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Alarm trip warning definitions — PDF page 49
| Source row | Term | Definition |
|---|---|---|
| 1 | “Alarm” | Any faulty condition |
| 2 | “Trip” | Any action on a fault condition which leads to interruption of operation. Trips can be divided into hard and soft trips, see Table 21 |
| 3 | “Warning” | Any action on a fault condition which does not lead to interruption of operation |
Table21 alarm actions — PDF page 49
| Source row | Alarm action | Effect |
|---|---|---|
| 1 | No action | The alarm condition is ignored. |
| 2 | Warning | A warning message is shown. Operation continues as usual if no further measures are taken. |
| 3 | Hard Trip | Softstarter is tripped. Operation is interrupted and restart is inhibited: - if the softstarter is inactive: Activation will not be allowed - if the softstarter is in operation: The motor coasts to a stop. |
| 4 | Soft Trip | Softstarter is tripped. A stop is executed in the same way as for normal operation i.e. using the same stop method. Restart is inhibited. |
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 50
Manual reference: physical PDF page 50. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Trip message
The trip message can be viewed in the menu “View Trip
Log” [800], in which the nine most recent trip messages are
stored ([810] to [890]). For every logged trip the date and
time - from real time clock [740] - is displayed, along with
the actual trip message according to the denotations in Table
32, page 117. The cause of the most recent or actual trip is
indicated in menu [810].
To facilitate troubleshooting, data is copied from the
operation and status menu groups [710] - [730] when a trip
occurs. See a list of the stored parameters in Table 33, page
- The stored parameters and their values are shown
under menus [8X1] “Operation”, [8X2] “Status”, and [8X3]
“Stored Values”. To view the value, go down to menu level 4,
i.e. 8XXX.
7.3.4
Load monitor function
The load monitor settings in menu [410] can be used to
protect machines and processes against mechanical overload
and underload, such as a conveyor belt or screw conveyor
jamming, a belt failure on a fan, or a pump running dry.
The load is determined by calculating the motor shaft
power, while running.
There are two overload alarms, “Max Alarm” and “Max Pre-
Alarm”, and two underload alarms, “Min Alarm” and “Min
Pre-Alarm”. The load monitor function is not active during
stop ramps, jogging or braking. For the start ramp you can
choose to delay the activation of the load monitor by using
start delay, menu [416].
It is common that the minimum and maximum alarms are
set to give a soft or hard trip, while the pre-alarms are used
to give an indication that an over- or underload situation
may be close by displaying a warning message (e.g. “Mon
MinPreAl”).
If the operation has been interrupted due to a load monitor
alarm, a reset and a new start signal is needed to continue
operation. Autoreset for the load monitor alarms can be
activated under menu [254]. For manual reset see “Manual
reset” on page 50.
Load monitor alarm levels
There are two alternative ways to set the load monitor alarm
levels:
- Manual configuration, in which up to four “Alarm
Levels” are set directly (Fig. ).
“Autoset” configuration, for which the alarm levels are
automatically set, based on “Normal Load” + four “Alarm
Margins” (Fig. 33).
Common for both methods is that the resulting alarm levels
are given as a percentage that refers to the nominal motor
power [223] (being 100%). However, the way to set the
levels differs between the two methods:
NOTE: When the trip is reset the trip message will be
removed from the control panel display, but remains in
the trip message log [800].
NOTE: When using the load monitor, check that the
nominal motor power is set properly in menu [223].
Adjacent source context — repeated to preserve continuation:
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 51
Manual reference: physical PDF page 51. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Manually set alarm levels
See Fig. . For the manual load monitor settings, the “Alarm
Levels” [411] - [414] are set directly as a percentage of the
nominal motor power (menu [223]). The actual shaft power
signal value is displayed together with the Alarm Level value
to facilitate setting. See example on the right.
Example:
Fig. 32 Manually set load monitor alarm levels.
4112 MaxAlarmLev
Run
(104%) 116%
Figure32: yP[%] ofPn_mot, xt[s];manualmaxlevel4112,maxprelevel4122,minprelevel4132,minlevel4142. Startdelay416;minpreDelay4133/Action4131,minDelay4143/Action4141,maxpreDelay4123/Action4121,maxDelay4113/Action4111. Legendnormalzone/prealarmzone/minmaxalarmzone, Runcommand,startdelaytimer,alarmaction. Screen4112MaxAlarmLev,RunA,(104%)116%illustrative.
Adjacent source context — repeated to preserve continuation:
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 52
Manual reference: physical PDF page 52. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Autoset function with alarm margins
See Fig. 33. The quickest way to adapt the monitor to
different load situations is to use the “Autoset” function,
which automatically applies four “Alarm Margins” to a
registered “Normal Load” level whilst the motor is running.
The “Alarm Margins” are set as a percentage added to or
subtracted from the “Normal Load”, which is the shaft
power during normal operation conditions. See calculations
in Table 24, page 86. The “Normal Load” is expressed as a
percentage of the nominal motor power (i.e. 100% normal
load equals the motor power set in menu [223]).
The “Alarm Margins” are set under menu [417], and
“Normal Load” is automatically registered when activating
the autoset function in menu [4175] AutoSet Alarm. The
actual “Normal Load” value can then be viewed in menu
[4176].
Every time a new “Autoset Alarm” command is executed, the
actual shaft power value will be updated as the “Normal
Load” value, with the alarm levels following this.
Autoset can also be activated using a remote signal (edge-
triggered) by setting the function of any digital input to
“Autoset”.
Fig. 33 Autoset load monitor alarm margins.
NOTE: A manual change of any of the “Alarm Levels” in
[411] - [414] will override the “Autoset” monitor
settings, and the “Normal Load” will be reset to “Off”.
Figure33: yP[%]ofPn_mot,xt[s];Autoset4175,NormalLoad4176. Maxmargin4171,MaxPremargin4172,MinPremargin4173,Minmargin4174. Startdelay416;minpreDelay4133Action4131;minDelay4143Action4141;maxpreDelay4123Action4121;maxDelay4113Action4111. Legendruncommand/startdelaytimer/alarmaction andthreezonefills. No inferrednumericlimits.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 53
Manual reference: physical PDF page 53. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Load monitor alarm actions
All the alarms and pre-alarms can be independently
configured to affect operation by applying an alarm action,
e.g. a trip or a warning. See section 7.3.1, page 45. The
alarm or pre-alarm status is available on one of the
programmable relays if so configured (see menu [550] for
more information).
The alarm actions for both the autoset alarm margins and
the manually set alarm levels are configured in menu [4111],
[4121], [4131] and [4141].
The corresponding “Alarm Delays”, which will affect the
alarm response time, are set in menu [4113], [4123], [4133]
and [4143].
Load monitor during start-up
To avoid faulty alarms due to initial over- or underload
situations at start, a “Start Delay” time can be applied for the
load monitor. See menu [416], page 86.
Example 1: Configuring alarm levels manually
Assume that the load monitor is intended to be blocked
during the start-up procedure. A start delay of 30 seconds is
therefore selected in menu [416], in order to allow the
process to settle before the load monitoring becomes active.
In this case a pump must be protected from both overload
and underload (e.g. cavitation) conditions, but no pre-
alarms are needed. The alarm action for the pre-alarms
([4121] and [4131]) is therefore set to “No action”.
Furthermore, the alarm actions for Max alarm [4111] and
Min alarm [4141] are set to “Soft Trip”, with the
corresponding alarm delays; 10 seconds in menu [4113]
Max Alarm Delay, and 5 seconds in [4143] Min Alarm
Delay.
Since the normal load condition (shaft power) for the pump
is 50% of the nominal motor power [223], the Max Alarm
Level [4112] is set to 70%. Finally the Min Alarm Level
[4142] is set to 10%, which is reached during e.g. pump
cavitation conditions.
This configuration results in the following sequence of
events (as illustrated in Fig. 34):
A. The load monitor function is activated when the set start
delay time (30 seconds) has expired.
B. A maximum alarm condition is triggered, but since the
load returns to a safe level within the set alarm delay
time (i.e. <10 seconds) no alarm action is performed.
C. A new maximum alarm condition is triggered.
D. When the set alarm delay time (10 seconds) has expired,
the maximum alarm action is executed (in this case a soft
trip).
Fig. 34 Example 1: Manually set load monitor function.
Example 2: Auto-setting alarm margins
To block the load monitor during the start-up, a start delay
of 30 seconds is selected in menu [416].
In this case a motor used in a conveyor application must be
protected. It is only of interest to apply a maximum alarm
and maximum pre-alarm, therefore the alarm actions for the
minimum alarm [4141] and the minimum pre-alarm [4131]
are set to “No action” (default). The Max Pre-Alarm Action
[4122] is set to “Warning” and the Max Alarm Action
[4111] is set to “Hard Trip”. Then the Max Alarm Delay
[4113] is set to 3 seconds, and the Max Pre-Alarm Delay
[4123] to 0 seconds to get an instant warning when the load
is increased. Menu [4171] Max Alarm Margin is set to 10%,
and menu [4172] Max Pre-Alarm Margin is set to 5%, to
indicate that an overload condition is close.
The motor is started and the actual shaft power is viewed to
the left in menu [4175] Autoset Alarm. When the process
has stabilised, this indicates that the normal load conditions
take place at 60% of the nominal motor power [223]. The
autoset of the alarms is done by selecting “Yes”, followed by
pressing “ENTER”. “Autoset OK!” is displayed. The motor
is now fully protected with a maximum alarm set to 70%
(Normal Load + Max Alarm Margin, 60% + 10%) and a
pre-alarm at 65% (Normal Load + Max Pre-Alarm Margin,
60% + 5%). The “Normal Load” value is viewed in menu
[4176], along with the actual shaft power value.
The following events are noted (see Fig. 35):
B. A maximum pre-alarm condition is triggered, and
immediately results in a warning message: ”Mon
MaxPreAl”, as there is no alarm delay in this case.
C. A maximum alarm condition is triggered.
D. When the set maximum alarm delay time (3 seconds)
has passed, the set maximum alarm action, a hard trip, is
executed.
NOTE: The load monitor alarms are disabled during
jogging, braking, and stop ramp.
30 s.
10 s.
Pload
Time
Max
Min
Normal
Figure34 illustrativemanuallevelsMax70%,Normal50%,Min10%,start30s,maximumalarm10s;Aactivationafter30s,Btransientoverload shorterthan10s noaction,Crenewedoverload,Dsofttripafter10s. Originalchartandprosegovern; no newparameter.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 54
Manual reference: physical PDF page 54. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 35 Example 2: Autoset load monitor function.
7.3.5 Reset and autoreset
When the softstarter is tripped due to a failure, a reset
command is required to make it possible to restart the
softstarter. The reset command can come from any of the
selected sources in menu [216] “Reset Control”, or it can be
automatically generated through settings in menu group
[250] “Autoreset”.
For the following explanations it is important to distinguish
between “reset” and “restart”. “Reset” means that the
softstarter no longer is in a tripped condition, as confirmed
by a removal of the alarm message in the display. If the
operation has been interrupted due to a tripped condition,
the softstarter is prepared for a restart.
If an alarm occurs whose alarm action is configured for
“Warning” (see description of alarm actions in Table 21,
page 45), the indication will automatically be removed as
soon as the warning condition disappears, i.e. no reset
command is needed.
If the operation has been interrupted due to a trip, a reset
signal and a new start signal may be needed to restart the
motor. However, some alarms can be automatically reset
when a new start signal is given.
Manual reset
The control source for the reset signal is selected in [216]
“Reset Control”. The RESET key on the control panel is
activated by selecting one of the keyboard alternatives
(enabled as default).
If controlled by digital input [520], or by virtual I/O [560],
this is set by selecting “Reset” signal.
An output signal can be set by a relay [550] to “ManRst
Trip” which is defined as any active trip condition that needs
a manual reset.
Autoreset
For several alarms it is possible to automatically generate a
reset command to overcome the fault condition. Providing
that all other conditions are normal, the softstarter will then
attempt to restart the operation. Only when the failure keeps
on coming back, recurring at a defined number of times and
therefore cannot be solved by the softstarter, will the unit
give an alarm to inform the operator that attention is
required.
The autoreset configuration can be done in menu group
[250] Autoreset, with submenus for Motor Protection
Autoreset [252], Communication Error Autoreset [253],
Process Protection Autoreset [254], Softstarter Protection
Autoreset [255], and Mains Failure Autoreset [256].
To enable the Autoreset function, “Reset” is selected on one
of [520] Digital Inputs. The reset input must be constantly
activated.
To activate the autoreset function via Virtual I/O [560],
“Reset” is selected in the destination menu for the internal
connection.
In the menus for Relays [550] an output signal of the
autoreset trip can be set, “AutoRst Trip”. Relay is activated
when the maximum number of autoresets is reached.
See more about remote reset control in “Reset and Autoreset
operation” on page 52.
To activate the autoreset function, Allowed Autoreset
Attempts are set in [2511]. Once the maximum number of
autoresets is reached, the softstarter will stay in fault
condition, indicating that external assistance is required.
The details of the autoreset counter can be found in
“Autoreset Attempts [251]” on page 69.
Example: Autoreset for thermal overload
A motor is protected by an internal protection for thermal
overload. When the protection is activated, the softstarter
should wait until the motor has cooled down enough before
resuming normal operation. In this case the estimated time
for cooling down is 300 seconds. When the problem has
occurred three times in a short period of time, a call for
external assistance should be required.
To do this:
•
Enable the Autoreset function by making the reset input
continuously high.
Set maximum number of restarts to 3 in menu [2511].
Activate Motor I2t to be automatically reset; set menu
3 s.
30 s.
Pload
Time
Normal
Pre-Max
Max
WARNING!
If the “Run” input signal is active (high) and
level-controlled start mode is selected, the
motor will start at the reset command.
Note that “level control” is not fulfilling the
Machine directive
Figure35 illustrativeAutosetNormal60%,PreMax65%,Max70%;start30s,maximumalarmdelay3s. Amonitoractivation,Bimmediateprewarning,Cmaximumalarmtrigger,Dhardtripafter3s. ThermalexamplecontinuesonPDF55:3restartattempts,300sMotorI2t2521,551AutoRstTrip.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 55
Manual reference: physical PDF page 55. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
[2521]to 300 s.
•
Set relay 1, menu [551] to “AutoRst Trip”; output signal
will be active when the maximum number of restarts is
reached and the softstarter stays in fault condition.
Example: Autoreset for undervoltage
In an application it is known that the main supply voltage
sometimes disappears for a very short time, a so-called “dip”.
That will cause the softstarter to trip an “Undervoltage
alarm”. Using the Autoreset function, this trip will be reset
automatically.
Enable the Autoreset function by making the reset input
continuously high.
Activate the Autoreset function in menu [2511],
Allowed Autoreset Attempts.
The autoreset for the undervoltage alarm is activated in
menu [2564]. The set delay time starts counting when
the fault is gone. If the softstarter is stopped an
undervoltage cannot be detected, and the delay time
starts counting immediately after the alarm action has
been executed.
7.4
Programmable I/O
There are a number of selectable signals for analogue and
digital inputs and outputs, gathered under section 8.5, page
91.
1 analogue input [510]
1 analogue output [530]
4 digital inputs [520], with the possibility for up to 6
extra digital inputs if extended I/O option boards (max
2) are fitted.
No digital outputs are available.
3 relay outputs [550], with the possibility for up to 6
extra relays if extended I/O option boards (max 2) are
fitted.
There are also 8 virtual I/Os [560]
Parameters for serial communication are described in section
8.2.7, page 73, menu group [260].
7.5
Logical functions
To enable logic signals to be programmed for different
controlling or signalling functions (using AND/OR/EXOR
operators), there are a number of functions available:
4 analogue comparators and 4 digital comparators [610]
4 logic functions [620]
4 timers [630]
4 SR flip-flops [640}
2 counters [650]
2 clocks [660]
See how to configure the logical functions in Chapter 8.6,
page 100.
7.6
Remote control functions
Operation of the Run/Stop/Enable/Reset functions
As default, the run/stop commands are programmed for
remote operation via the inputs on the terminal strip on the
control board. Default for the reset control is both remote
and keyboard.
With the parameter “Run/Stop Control” [2151] and “Reset
Control” [216], these functions can also be selected for
keyboard or bus communication control.
7.6.1 Default settings of the Run/
Stop/Reset functions
The default settings are shown in Fig. 36. In this example
the softstarter is started with DigIn 1 (Run FWD) and
stopped with DigIn 2 (Stop). A reset after trip can be given
with DigIn 4. The inputs are default set for edge control.
Fig. 36 Default setting Run/Reset commands
NOTE: The examples in this paragraph do not cover all
possibilities. Only the default settings (factory) and the
most relevant combinations are given.
Reset
Control board
Run FWD
DigIn 1
DigIn 2
DigIn 4
Stop
+24 V
(pulse)
Figure36 defaultedgewiring:RunFWDpulseinput11(DigIn1),Stop12(DigIn2),Reset17(DigIn4);18and20+24V. Figureconnects18tocommonRun/Stop and20Reset. Sourceexampleonly.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 56
Manual reference: physical PDF page 56. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.6.2 Enable and Stop functions
Both functions can be used separately or simultaneously.
The choice of which function is to be used depends on the
application and the control mode of the inputs (Level/Edge
[21A]).
Enable
The enable function is used as a start interlock. This means
that if any input is set to “Enable”, this input must be set to
active (high) to allow any run command. When the input is
low, the motor will coast to stop.
Stop
If the input is set low (open), the softstarter will stop
according to the selected stop method in menu [341].
7.6.3 Reset and Autoreset operation
If the softstarter is in stop mode due to a trip condition, the
softstarter can be remotely reset by a pulse (“low” to “high”
transition) on the “Reset” input on DigIn 4.
Depending on the selected control method, a restart takes
place as follows:
Edge controlled “Run” inputs
After the “Reset” command is given a new “Run” command
must be applied to start the softstarter again. The inputs are
set for edge control as default. This means that an input is
activated by a “low” to “high” transition or vice versa.
The “Enable” and “Stop” inputs must be closed
continuously in order to accept any run forward or run
reverse command. The last edge (RunFWD or RunREV) is
valid. If an edge-controlled start is activated it is also
necessary to use an input for the stop command according to
Fig. 36, page 51. Fig. 37 gives an example of a possible
sequence.
Fig. 37 Input and output status for edge control
NOTE: In edge control mode, at least one digital input
must be programmed to “Stop”, because the “RunFWD”
and “RunREV” commands are only able to start the
softstarter.
CAUTION!
If the Enable function is not programmed to
a digital input, it is considered to be active
internally.
!
NOTE: Edge controlled inputs comply with the Machine
Directive (see Chapter 1.5.1, page 6), if the inputs are
directly used for starting and stopping the machine.
INPUTS
Run FWD
Run REV
Forward rotation
Reversed rotation
Standstill
MOTOR OPERATION
Edge control [21A]
Figure37 qualitativeedgecontroltracesEnable,Stop,RunFWD,RunREV andForwardrotation/Reversedrotation/Standstill. No time scale or numericaldelay specified. LastRunedgevalid whileEnable/Stopclosed;lowEnablecoastspertext.
Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 57
Manual reference: physical PDF page 57. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Level controlled “Run” inputs
If the “Run” inputs remain in their position the softstarter
will start immediately after the “Reset” command is given.
Autoreset is enabled if the “Reset” input is continuously
active. The autoreset functions are programmed in menu
“Autoreset” [240].
Menu “[21A] Start signal” Level/Edge must be set to “Level”
to activate level control. This means that an input is
activated by making the input continuously high. This
method should be applied if a PLC is used to operate the
softstarter, for instance.
The Enable input must be continuously active in order to
accept any run forward or run reverse command. If both
RunFWD and RunREV inputs are active, then the
softstarter stops according to the selected stop method in
menu [341]. Fig. 38 gives an example of a possible sequence.
Fig. 38 Input and output status for level control
NOTE: If the control commands are programmed for
keyboard control or serial communication control,
autoreset is not possible.
CAUTION!
Level-controlled inputs DO NOT comply with
the Machine Directive, if the inputs are
directly used to start and stop the machine.
!
Enable
Stop
Run FWD
Run REV
Forward rotation
Reversed rotation
Standstill
INPUTS
MOTOR OPERATION
Level control [21A]
Figure38 qualitativelevelcontroltracesEnable,Stop,RunFWD,RunREV andthreeoperationstates. BothRunactive causesconfiguredstop;RuninputspersistingthroughReset mayrestart. No numericaltiming inferred.
Manual — FOOTER_ONLY_PAGE — page 58
Manual reference: physical PDF page 58. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 54 | Main features | CG Drives & Automation, 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; Functionality menu overview. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 59
Manual reference: physical PDF page 59. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.
Functionality
This chapter describes the menus and parameters in the
software. You will find a short description of each function
and information about default values, ranges, etc.
A menu list with default values and the most important
communication settings is found in Appendix 1 at the end of
this manual.
At www.emotron.com or www.cgglobal.com, in the
download area, you can also find a complete communication
information list and a menu list with space for parameter set
notes.
Functionality menu overview; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.
Functionality menu overview — PDF page 59
| Source row | Function | Menu number | Description | See section |
|---|---|---|---|---|
| 1 | Preferred view | 100 | Menu display settings. | 8.1 |
| 2 | Operation setup | 210 | Basic settings for language, key functionality, control source. | 8.2.1 |
| 3 | Motor data | 220 | Setting of electrical data for the used motor. | 8.2.3 |
| 4 | Motor protection | 230 | Motor and softstarter thermal protections. | 8.2.4 |
| 5 | Parameter set handling | 240 | Selection and configuration of parameter sets. | 8.2.5 |
| 6 | Autoreset | 250 | Automatic reset of active alarms and restart of the softstarter. | 8.2.6 |
| 7 | Serial communication | 260 | Serial communication settings for the data transfer. | 8.2.7 |
| 8 | Process settings | 300 | Process value settings for analogue signal start/stop functions. | 8.3 |
| 9 | Process protection | 400 | Protection associated with the process and mains. Load monitor settings. |
8.4 |
| 10 | I/O settings | 500 | Input and output settings for control and monitoring. | 8.5 |
| 11 | Analogue input | 510 | ⟦blank source cell⟧ | 8.5.1 |
| 12 | Digital inputs | 520 | ⟦blank source cell⟧ | 8.5.2 |
| 13 | Analogue output | 530 | ⟦blank source cell⟧ | 8.5.3 |
| 14 | Relays | 550 | ⟦blank source cell⟧ | 8.5.4 |
| 15 | Virtual I/Os | 560 | ⟦blank source cell⟧ | 8.5.5 |
| 16 | Logic and timers | 600 | Settings for logical functions and timers. | 8.6 |
| 17 | Operation status | 700 | Viewing of operation parameter values. | 8.7 |
| 18 | Trip log | 800 | Viewing of trip messages and trip data. | 8.8 |
| 19 | System data | 900 | Emotron TSA model, software and hardware version. Service information. |
8.9 |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 60
Manual reference: physical PDF page 60. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Description of menu table layout
-
Parameter cannot be changed during operation.
-
Parameter only for viewing.
-
Menu information as displayed on control panel.
For explanation of display text and symbols, see section
6.1, page 33.
-
Factory setting of parameter (also showed on display).
-
Available settings for the menu, listed selections.
-
Communication integer value for the selection.
For use with communication bus interface (only if
selection type parameters).
- Description of selection alternative or range (min - max
value).
Example:
Menu [2175] “REV key” has two available selections, “Off”
and “REV”, that indicate if the REV key is activated or not.
The factory (default) setting is “Off”.
To change selection or value via the control panel, the “+”
and “-” keys are used (see section 6.4.1, page 35).
For bus communication, the integer value 0 is used to select
“Off” in the example. Integer 1 represents “REV”.
To change selection by bus communication refer to the
description in Chapter 9. page 123.
Resolution of settings
The resolution for all range settings described in this chapter
is 3 significant digits (unless stated otherwise). Table 22
shows the resolutions for 3 significant digits.
8.1
Preferred View [100]
This menu is displayed at every power-up. During
operation, the menu [100] will automatically be displayed
when the keyboard is not operated for 5 minutes. The
automatic return function will be switched off when the
Toggle and STOP/RESET keys are pressed simultaneously
for 5 seconds. As default the electrical power and current
values are displayed (example in the figure below):
Fig. 39 Default initial display.
Menu [100], “Preferred View” displays the settings made in
menu [110], “1st Line”, and [120], “2nd Line”.
①
Read-only ②
③
Default:
④
⑤
⑥
⑦
Init Torque
Stp
10%
Table 22
Read-only
0kW
0.0A
(1st Line)
(2nd Line)
Menu legend: padlock marks value not changeable during operation; Read-only distinct; display/default/selection/communication integer/range are separate parts. Illustrative332 InitTorque10% and2175REVOff0/REV1 do not set installed configuration. Default displays100 0kW/0.0A illustrative.
Table22 three significant digit resolution; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2175 REV key; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Table22 three significant digit resolution — PDF page 60
| Source row | 3 Digit | Resolution |
|---|---|---|
| 1 | 0.01-9.99 | 0.01 |
| 2 | 10.0-99.9 | 0.1 |
| 3 | 100-999 | 1 |
| 4 | 1,000-9,990 | 10 |
| 5 | 10,000-99,900 | 100 |
Parameter panel 2175 REV key — PDF page 60
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | REV key deactivated |
| 3 | REV | 1 | REV key activated |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 61
Manual reference: physical PDF page 61. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.1.1
1st Line [110]
This menu sets the content of the upper row in the menu
[100] “Preferred View. If “Process Value” is selected, the
menu shows the value of the selected process source in menu
[321].”
*
“Motor temp” is only visible if you have the option
PTC/PT100 board installed and a PT100 input is
selected in menu [2323].
8.1.2
2nd Line [120]
Sets the content of the lower row in the menu
[100] “Preferred View”. Same selection as in menu [110].
8.2
Main Setup [200]
The “Main Setup” menu contains the most important
settings to get the softstarter operational and set up for the
application. It includes different sub menus concerning the
control of the unit, motor data and protection, utilities and
automatic reset of faults. This menu will instantaneously
adapt to installed options and show the required settings.
8.2.1
Operation setup [210]
Selections concerning the used motor, softstarter mode,
control signals and serial communication are described in
this submenu and is used to set the softstarter up for the
application.
Language [211]
Select the language used in the control panel display. Once
the language is set, this selection will not be affected by the
“Load Default” command.
Select Motor [212]
This menu is used if you have more than one motor in your
application. Select the motor to define. It is possible to define
up to four different motors, M1 to M4, in the softstarter. For
parameter set handling including motor sets M1 - M4, see
section 8.2.5, page 66.
LCD set markersA andM1 are graphical.211 language list includes Cyrillic Russian and Greek names as source glyphs. Display120 shares110 list; MotorTemp11 conditional onPT100 option and2323.
Parameter panel 110 1st Line; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 2, column 2 share the source cell at row 2, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 211 Language; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 120 2nd Line; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 212 Select Motor; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
- row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 110 1st Line — PDF page 61
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | El Power |
| 2 | Dependent on menu | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 3 | Process Val | 0 | Process value |
| 4 | Torque | 2 | Torque |
| 5 | Shaft Power | 4 | Shaft power |
| 6 | El Power | 5 | Electrical power |
| 7 | Current | 6 | Current |
| 8 | Heatsink Tmp | 10 | Heatsink temperature |
| 9 | Motor Temp * | 11 | Motor temperature |
| 10 | SoftstStatus | 12 | Softstarter status |
| 11 | Run Time | 13 | Run Time |
| 12 | Energy | 14 | Energy |
Parameter panel 211 Language — PDF page 61
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | English |
| 2 | English | 0 | English selected |
| 3 | Svenska | 1 | Swedish selected |
| 4 | Nederlands | 2 | Dutch selected |
| 5 | Deutsch | 3 | German selected |
| 6 | Français | 4 | French selected |
| 7 | Español | 5 | Spanish selected |
| 8 | Ρусский | 6 | Russian selected |
| 9 | Italiano | 7 | Italian selected |
| 10 | Česky | 8 | Czech selected |
| 11 | Türkçe | 9 | Turkish selected |
Parameter panel 120 2nd Line — PDF page 61
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Current |
Parameter panel 212 Select Motor — PDF page 61
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | M1 |
| 2 | M1 | 0 | Motor Data is connected to selected motor. |
| 3 | M2 | 1 | ⟦null: no independent source value⟧ |
| 4 | M3 | 2 | ⟦null: no independent source value⟧ |
| 5 | M4 | 3 | ⟦null: no independent source value⟧ |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 62
Manual reference: physical PDF page 62. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Action Control [215]
This function is used to select the source for run and stop
commands and for jog control. This is described in section
7.1, page 39.
Run/Stop Control [2151]
Jog Control [2152]
In this menu the control source for the jog function is
selected. If the Jog FWD and Jog REV keys are to be used,
one of the keyboard alternatives must be selected in this
menu, and the keyboard must be locked in menu [218].
See section 7.1.3, page 40 for settings regarding the jog
functions.
Reset Control [216]
When the softstarter is in alarm condition, a reset
command is required to make it possible to restart the
softstarter. Use this function to select the source of the reset
signal. The keyboard alternatives in this menu enable both
external and internal control panels to be used. For autoreset
settings, see menu group [250] “Autoreset”. See also section
7.3.5, page 50 about reset and autoreset functions.
Key functionality [217]
Menu group that sets the functions of the keys on the control
panel. See section 6.4, page 34.
Function Key [2171]
The Toggle key on the keyboard (see section 6.5, page 35) has
two functions that can be activated in this menu. As default
the key is set to operate as a toggle key that moves you easily
through the selected menus in the toggle loop.
The “Loc/Rem” function of the key allows you to easily
switch between local and normal operation mode (see
page 36). If set to “Off”, the function is disabled.
The “Loc/Rem” function can also be changed via digital
input. See menu [520].
WARNING!
If the “Run” input signal is active (high) and
level-controlled, the motor will start at the
reset command.
Parameter panel 2151 Run/Stp Ctrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 216 Reset Ctrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
- row 1, column 2, row 1, column 3 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2152 Jog Ctrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2171 FunctionKey; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2151 Run/Stp Ctrl — PDF page 62
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Remote |
| 2 | Remote | 0 | Start/stop command via digital input. |
| 3 | Int+Ext keyb |
1 | Start/stop command via internal or external control panel. |
| 4 | Com | 2 | Start/stop command via serial communication. |
| 5 | Spare | 3 | (Reserved for future use) |
| 6 | Int keyb | 5 | Start/stop command via internal control panel. |
| 7 | Ext keyb | 6 | Start/stop command via external control panel. |
Parameter panel 216 Reset Ctrl — PDF page 62
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: Remote+Keyb | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 2 | Remote | 0 | Reset command via digital input. |
| 3 | Keyboard | 1 | Reset command via internal or external control panel (RESET key). |
| 4 | Com | 2 | Reset command via serial communication. |
| 5 | Remote+ keyb |
3 | Reset command via digital input or control panel (internal or external). |
| 6 | Com+keyb | 4 | Reset command via serial communication or control panel (internal or external). |
| 7 | Rem+keyb +com |
5 | Reset command via digital input, control panel (internal or external), or serial communication. |
Parameter panel 2152 Jog Ctrl — PDF page 62
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Remote |
| 2 | Remote | 0 | Jog command via digital input. |
| 3 | Int+Ext keyb |
1 | Jog command via internal or external control panel. |
| 4 | Com | 2 | Jog command via serial communication. |
| 5 | Spare | 3 | (Reserved for future use) |
| 6 | Int keyb | 5 | Jog command via internal control panel. |
| 7 | Ext keyb | 6 | Jog command via external control panel. |
Parameter panel 2171 FunctionKey — PDF page 62
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Toggle |
| 2 | Off | 0 | No function |
| 3 | Toggle | 1 | Toggle function |
| 4 | Loc/Rem | 2 | Local/Remote control mode function |
| 5 | Combined | 3 | Both Toggle function and Local/Remote control mode function. See explanation in 6.5.1. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 63
Manual reference: physical PDF page 63. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Local Run Control [2173]
The “Local” mode of the “Loc/Rem” functionality is defined
in this menu (see also page 36). When the softstarter is in
“Local” operation mode, the display shows “
“.
FWD key [2174]
The START/FWD key gives a start with forward (right)
rotation if the function is activated in this menu. The
rotation direction must also be permitted in menu [219]
“Rotation”
REV key [2175]
The REV key gives a start with reverse (left) rotation if
activated in this menu. The function requires a reversing
contactor.
The rotation direction must also be permitted in menu [219]
“Rotation”.
Lock Code [218]
To prevent the keyboard being used or to change the setup of
the softstarter and/or process control, the keyboard can be
locked with a password. This menu, “Lock Code” [218], is
used to lock and unlock the keyboard. Enter the password
“291” to lock/unlock the keyboard operation (see section
6.4.1, page 35). If the keyboard is not locked (default) the
selection “Lock Code?” will appear. If the keyboard is already
locked, the selection “Unlock Code?” will appear.
When the keyboard is locked, parameters can be viewed but
not changed. The control keys (START REV/FWD, and
STOP/RESET) and the jog keys (JOG REV/FWD) can still
be used if their functions are set to be controlled from the
keyboard.
Rotation [219]
Overall limitation of motor rotation direction
This function limits the overall rotation to reverse or forward
direction, or to allow both directions. This limit is prior to all
other selections, e.g. if the rotation is limited to forward
direction, a REV command will be ignored. To define reverse
and forward rotation we assume that the motor is connected
according to section 3.1, page 12.
In this menu you set the allowed rotation for the motor.
NOTE: When reversed rotation is selected (“REV” or
“FWD+REV” in menu [219]), this requires phase reversal
contactors. See Fig. 15, page 19.
2174/2175 key symbols show forward/right and reverse/left; reverse feature requires external reversing contactor. Lock218 default0 range0–9999, source password291. Lock does not disable configured control/jog keys.
Parameter panel 2173 LocRunCtrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 218 Lock Code?; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2174 FWD key; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 219 Rotation; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2175 REV key; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2173 LocRunCtrl — PDF page 63
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Keyboard |
| 2 | Remote | 1 | Local start/stop command via digital input. |
| 3 | Keyboard | 2 | Local start/stop command via control panel (internal or external). |
| 4 | Com | 3 | Local start/stop command via serial communication. |
Parameter panel 218 Lock Code? — PDF page 63
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0 |
| 2 | Range: | 0–9999 |
Parameter panel 2174 FWD key — PDF page 63
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | FWD |
| 2 | Off | 0 | FWD key deactivated |
| 3 | FWD | 1 | FWD key activated |
Parameter panel 219 Rotation — PDF page 63
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | FWD |
| 2 | FWD | 1 | Limited to forward (right) rotation. REV key, JOG REV key, and reverse commands are disabled. |
| 3 | REV | 2 | Limited to reverse (left) rotation. FWD key, JOG FWD key, and forward commands are disabled. See note below. |
| 4 | FWD+REV | 3 | Both rotation directions allowed. See note below. |
Parameter panel 2175 REV key — PDF page 63
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | REV key deactivated |
| 3 | REV | 1 | REV key activated |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 64
Manual reference: physical PDF page 64. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.2.2
Remote signal Level/Edge
[21A]
In this menu you select the type of control used for the input
signals for RunFWD, RunREV and RESET that are
operated via the digital inputs on the terminal strip. The
input signals are default set for edge-control, and the input
signals will be activated by the “low to high” or “high to low”
transition of the input. When level-control is selected, the
input signals will be active as long as the input is kept high or
low. See section 7.6, page 51.
Units [21C]
In this menu you select the units which will represent the
different parameter values in the menus, including those read
via serial communication.
SI units
When “SI” is selected, the default units will be:
•
Power [kW]
Torque [Nm]
Temperature [°C]
Nominal motor frequency is preset to 50 Hz, and the
nominal values on motor data are preset according to SI
standards.
US units
The corresponding default values for US-units will be:
Power [hp]
Torque [lb.ft]
Temperature [°F]
Nominal motor frequency will be preset to 60 Hz, and the
default nominal values on motor data (e.g. voltage) are
adapted to US standards.
See also 1.7.2 Definitions, and Table 23, page 61.
8.2.3
Motor Data [220]
In this menu you enter the motor data to adapt the softstarter
to the connected motor. This will increase the control
accuracy as well as different read-outs and analogue output
signals. Some of the default motor data is derived from the
setting in menu [21C].
Motor M1 is selected as default and motor data entered will
be valid for motor M1. If you have more than one motor you
need to select the correct motor in menu [212] before
entering motor data.
NOTE: In edge control mode, at least one digital input
must be programmed to “Stop”, because the “RunFWD”
and “RunREV” commands are only able to start the
softstarter.
CAUTION!
Level controlled inputs DO NOT comply with
the Machine Directive if the inputs are
directly used to start and stop the machine.
NOTE: Edge controlled inputs can comply with the
Machine Directive (see Chapter 1.5.1 page 6) if the
inputs are directly used to start and stop the machine.
!
WARNING!
When the “Units” setting is changed, this will
also affect the factory settings of the motor.
NOTE 1: The parameters for motor data cannot be
changed during operation (marked with a lock
symbol here).
NOTE 2: The default factory settings are for a standard 4-
pole motor according to the nominal current and power
of the softstarter. The softstarter will run even if motor
data is not adapted to the actual motor, but the
performance will not be optimal.
NOTE 3: Parameter sets cannot be changed during
operation if they are set for different motors.
NOTE 4: Motor Data in the different sets M1 to M4 can
be reverted to default setting in menu [243],
Default>Set.
Enter the correct motor data to prevent
dangerous situations and assure correct
control.
Padlock on21C and motor-data heading indicates stopped-only changes. SI/US selector changes nominal default50/60Hz and units, not actual installed motor approval.
Parameter panel 21C Units; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 21A Level/Edge; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 21C Units — PDF page 64
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | SI |
| 2 | SI | 0 | SI-units |
| 3 | US | 1 | US-units |
Parameter panel 21A Level/Edge — PDF page 64
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Edge |
| 2 | Level | 0 | The inputs are activated or deactivated by a continuous high or low signal. Is commonly used if, for example, a PLC is used to operate the softstarter. |
| 3 | Edge | 1 | The inputs are activated by a transition; for Run and Reset from “low” to “high” and for Stop from "high" to "low". |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 65
Manual reference: physical PDF page 65. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
For more information about handling of motor data and
parameter sets, see section 7.2.3, page 42.
For explanation of the different abbreviations used in this
chapter, see Chapter 1.7.2 page 7
Nominal Motor Voltage [221]
Set the nominal motor voltage, Un_mot.
Nominal Motor Frequency [222]
Set the nominal motor frequency.
Nominal Motor Power [223]
The range for Pn_mot depends on the nominal softstarter
power Pn_soft. It must be set within the range 25 - 400% of
the softstarter power Pn_soft. See nominal data for CG motors
in Table 23.
NOTE: The Motor Volts value will always be stored as a 3
digit value with a resolution of 1 V.
Table 23
Nominal data for CG motors complying to IE2 class
of IEC 60034-30.
Padlocks accompany221,222,223. Table23 column associations: current[A]; SI defaultnominalpower400V[kW]; SI defaultspeed50Hz[rpm]; US defaultpower460V[hp]; US defaultspeed60Hz[rpm]. All23 bodyrows retained.
Parameter panel 223 Motor Power; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 221 Motor Volts; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Table23 CG motor nominal defaults IE2 source claim; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 222 Motor Freq; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 223 Motor Power — PDF page 65
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | P n_soft |
| 2 | Range: | 25-400% x P , default see Table 23, n_soft page 61. |
| 3 | Resolution | 3 significant digits |
Parameter panel 221 Motor Volts — PDF page 65
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 400 V for SI-units 460 V for US-units |
| 2 | Range: | 100-700 V |
| 3 | Resolution | 1 V |
Table23 CG motor nominal defaults IE2 source claim — PDF page 65
| Source row | Softstarter nominal current [A] |
Default nominal power @ 400 V SI-units [kW] |
Default nominal speed @ 50 Hz SI-units [rpm] |
Default nominal power @ 460 V US-units [hp] |
Default nominal speed @ 60Hz US-units [rpm] |
|---|---|---|---|---|---|
| 1 | 16 | 7.5 | 1,440 | 10 | 1,730 |
| 2 | 22 | 11 | 1,460 | 15 | 1,750 |
| 3 | 30 | 15 | 1,460 | 20 | 1,750 |
| 4 | 36 | 18.5 | 1,465 | 25 | 1,760 |
| 5 | 42 | 22 | 1,465 | 30 | 1,760 |
| 6 | 56 | 30 | 1,465 | 40 | 1,760 |
| 7 | 70 | 37 | 1,480 | 50 | 1,780 |
| 8 | 85 | 45 | 1,475 | 60 | 1,770 |
| 9 | 100 | 55 | 1,480 | 75 | 1,780 |
| 10 | 140 | 75 | 1,480 | 100 | 1,780 |
| 11 | 170 | 90 | 1,480 | 125 | 1,780 |
| 12 | 200 | 110 | 1,485 | 150 | 1,780 |
| 13 | 240 | 132 | 1,485 | 200 | 1,780 |
| 14 | 300 | 160 | 1,490 | 250 | 1,790 |
| 15 | 360 | 200 | 1,490 | 300 | 1,790 |
| 16 | 450 | 250 | 1,490 | 350 | 1,790 |
| 17 | 560 | 315 | 1,490 | 450 | 1,790 |
| 18 | 630 | 355 | 1,490 | 500 | 1,790 |
| 19 | 710 | 400 | 1,490 | 600 | 1,790 |
| 20 | 820 | 450 | 1,490 | 700 | 1,790 |
| 21 | 1,000 | 560 | 1,490 | 800 | 1,790 |
| 22 | 1,400 | 800 | 1,490 | 1,000 | 1,790 |
| 23 | 1,800 | 1,000 | 1,490 | 1,500 | 1,790 |
Parameter panel 222 Motor Freq — PDF page 65
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 50 Hz for SI-units 60 Hz for US-units |
| 2 | Range: | 50 Hz - 60 Hz |
| 3 | Resolution | 1 Hz |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 66
Manual reference: physical PDF page 66. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Nominal Motor Current [224]
Set the nominal motor current. If parallel motors, set the
value as sum of motors current.
In_soft is the nominal softstarter current, value according to
Table 23.
Nominal Motor Speed [225]
Set the nominal (full load) asynchronous motor speed.
Nominal Motor Poles [226]
This menu appears only when the nominal speed of the
motor is ≤500 rpm. Here the actual number of poles can be
entered.
Nominal Motor Cos φ [227]
Set the nominal Motor cosphi (power factor).
Motor Ventilation [228]
Parameter for setting the type of motor ventilation. This
affects the characteristics of the I2t motor protection by
lowering the actual overload current.
When the motor has no cooling fan, select “None”. For a
motor with a shaft mounted fan, select “Self”. When the
motor has an external cooling fan, select “Forced”.
8.2.4
Motor protection [230]
This function protects the motor against overload based on
the standard IEC 60947-4-2. For general information on
different alarm settings, see section 7.3, page 45.
Predictive I2t function
Based on how much the used thermal capacity (I2t) has
increased during the most recent starts, a prediction of the
next start is made. If there is no room for another start, the
start will be delayed until a start attempt results in a successful
start.
Motor I2t Alarm [231]
This function makes it possible to protect the motor from
overload as published in the standard IEC 60947-4-2.
The alarm limit is set according to the levels defined by the
“Motor I2t Class” in menu [2313]. Once exceeded, an alarm
will occur and the action chosen in menu [2311] is
performed. The alarm remains active until the I²t value is
below 95% before allowing a reset or an autoreset (see more
detailed description in menu [2521]).
NOTE: The default settings are for a standard 4-pole
motor according to the nominal power of the softstarter.
WARNING!
If level-control is used (i.e. “Level” selection
in menu [21A]), the motor will automatically
continue to make a new start attempt,
without notice.
Padlocks224–228 mark stopped-only configuration.226 condition is ≤500rpm, not <500.228 Self cell physically Normal I then t overload curve; missing2 retained. Source I²t level-control warning means automatic new start without notice; no independent safety endorsement.
Parameter panel 224 Motor Curr; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 228 Motor Vent; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 225 Motor Speed; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 226 Motor Poles; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 227 Motor Cosφ; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 224 Motor Curr — PDF page 66
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | I =I (see Note 2, page 60 and n_mot n_soft Table 23 above) |
| 2 | Range: | 25 - 200% x I [A] depending on n_soft Emotron TSA model. |
Parameter panel 228 Motor Vent — PDF page 66
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Self |
| 2 | None | 0 | Limited I2t overload curve. |
| 3 | Self | 1 | Normal I t overload curve. |
| 4 | Forced | 2 | Expanded I2t overload curve. |
Parameter panel 225 Motor Speed — PDF page 66
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | n (see Note 2, page 60 and Table 23) n_mot |
| 2 | Range: | 500 - 3,600 rpm |
| 3 | Resolution | 1 rpm, 4 sign digits |
Parameter panel 226 Motor Poles — PDF page 66
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 4 |
| 2 | Range: | 2-144 |
Parameter panel 227 Motor Cosφ — PDF page 66
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Cosφ 0.86 n (see Note 2, page 60) |
| 2 | Range: | 0.50 - 1.00 |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 67
Manual reference: physical PDF page 67. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Motor I2t Alarm Action [2311]
Motor I2t Current [2312]
This menu enables both downrating and uprating (use of
motors with a service factor >1.00) of the thermal motor
protection.
Motor I2t Class [2313]
Classification according to IEC60947-4-2, defining the
starting capacities of the motor in order to avoid thermal
overload.
Used Thermal Capacity [2314)
This menu shows the used thermal capacity of the motor, i.e.
the actual I2t value divided by the maximum I2t value,
expressed in (%).
PT100 Alarm[232]
The PT100 menus are only shown if a PT100 option board
is connected.
PT100 Alarm Action [2321]
Motor Class [2322]
Only visible if the PTC/PT100 option board is installed. Set
the class of motor used. The trip levels for the PT100 sensor
will automatically be set according to the setting in this
menu.
Read-only
2314 Used Th Cap
Stp
M1:
XX%
Motor-I²t2314 read-only.2313 Size1 defaultClass10A, Size2upClass10. PT100232 only withoption; insulationclassF140°C default, FNema145°C separate.
Parameter panel 2311 Mot I2t AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2, row 1, column 3 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 4, column 3, row 5, column 3 share the source cell at row 3, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 2321 PT100 AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 2312 Mot I2tCurr; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2313 Mot I2t Class; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2322 Motor Class; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2311 Mot I2t AA — PDF page 67
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: Soft Trip | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 2 | No action | 0 | I2t motor protection is not active. |
| 3 | Hard Trip | 1 | For a definition, see Table 21, page 45 |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 2321 PT100 AA — PDF page 67
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Action |
| 2 | No Action | 0 | For a definition, see Table 21, page 45 |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 2312 Mot I2tCurr — PDF page 67
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 100% |
| 2 | Range: | 0-150% of the nominal motor current I [224] n_mot |
Parameter panel 2313 Mot I2t Class — PDF page 67
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Size 1: 10 A Size 2 and up: 10 |
| 2 | 2 | 0 | Class 2 |
| 3 | 3 | 1 | Class 3 |
| 4 | 5 | 2 | Class 5 |
| 5 | 10 A | 3 | Class 10 A |
| 6 | 10 | 4 | Class 10 |
| 7 | 20 | 5 | Class 20 |
| 8 | 30 | 6 | Class 30 |
| 9 | 40 | 7 | Class 40 |
Parameter panel 2322 Motor Class — PDF page 67
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | F 140°C |
| 2 | A 100°C | 0 | ⟦blank source cell⟧ |
| 3 | E 115°C | 1 | ⟦blank source cell⟧ |
| 4 | B 120°C | 2 | ⟦blank source cell⟧ |
| 5 | F 140°C | 3 | ⟦blank source cell⟧ |
| 6 | F Nema 145°C |
4 | ⟦blank source cell⟧ |
| 7 | H 165°C | 5 | ⟦blank source cell⟧ |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 68
Manual reference: physical PDF page 68. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PT100 Inputs [2323]
Two PT100 option boards (B1 and B2) may be connected,
enabling up to six PT100 inputs. With menu [2323] “PT100
Inputs”, you can select which PT100 inputs that should be
supervised, i.e. which are allowed to generate a trip/warning
when the temperature exceeds the limit set in menu [2322]
“Motor Class”.
PT100 input 1, 2 and 3 are equal to input 1, 2 and 3 on the
first PT100 option board (B1). PT100 input 4, 5 and 6 are
equal to input 1, 2 and 3 on the second PT100 option board
(B2).
Note that the supervised inputs must be selected in a
sequence without gaps, i.e. if you like to have only one input
supervised (selection PT100 1) you must use input 1 on
board one (B1).
If you wish to have four PT100 inputs supervised (selection
PT100 1-4) you must use input 1-3 on option board one
(corresponding to input 1-3) and the first input of board 2
(corresponding to input 4).
All PT100 inputs are displayed in operation menu [71B]
PT100 B1 1, 2, 3 and [71C] PT100 B2 1, 2, 3, regardless of
the menu selection.
PTC Alarm [233]
The PTC alarm menus are always shown as there is an
integrated PTC input on the power board (PB-PTC) as
standard.
PTC Alarm Action [2331]
PTC Inputs [2332]
Two additional PTC option inputs can be handled. The
settings are therefore “PB-PTC” for the on-board PTC, “PB-
PTC&Opt1”, and “PB-PTC&Opt1-2”.
Start Limitation [234]
The start limitation is used to protect the softstarter by
limiting the numbers of starts per hour or securing a
minimum time delay between starts.
A start limitation alarm is reset when the alarm condition is
gone and a new start signal is given.
The actual time left until the next start is allowed is shown in
the status menu [72G] “Time to Next Start”.
Start Limitation Alarm Action [2341]
Start limitation is enabled in this menu by choosing a proper
alarm action, used as thermal protection for the softstarter.
Autoreset is available for all start limitation alarms, menu
[2552].
PT1002323 contiguous channels1…3 or1…6; both71B/71C displays shown regardless monitoringselection.2341 table noSoftTrip code3; source table not expanded.
Parameter panel 2332 PTC Inputs; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2323 PT100Inputs; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2341 StartLim AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
- row 3, column 3, row 4, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 2331 PTC AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
- row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 2332 PTC Inputs — PDF page 68
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | PB-PTC |
| 2 | PB-PTC | 0 | On-board power board PTC used for protection |
| 3 | PB-PTC &Opt1 |
1 | PB-PTC and PTC input on option B1 used for protection |
| 4 | PB-PTC &Opt1-2 |
2 | PB-PTC and PTC input on options B1 and B2 used for protection |
Parameter panel 2323 PT100Inputs — PDF page 68
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | PT100 1-3 |
| 2 | PT100 1 | 0 | Channel 1 used for PT100 protection |
| 3 | PT100 1-2 | 1 | Channel 1-2 used for PT100 protection |
| 4 | PT100 1-3 | 2 | Channel 1-3 used for PT100 protection |
| 5 | PT100 1-4 | 3 | Channel 1-4 used for PT100 protection |
| 6 | PT100 1-5 | 4 | Channel 1-5 used for PT100 protection |
| 7 | PT100 1-6 | 5 | Channel 1-6 used for PT100 protection |
Parameter panel 2341 StartLim AA — PDF page 68
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No action |
| 2 | No action | 0 | For a definition, see Table 21, page 45 |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 2331 PTC AA — PDF page 68
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No action |
| 2 | No action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 69
Manual reference: physical PDF page 69. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Number of starts per hour [2342]
In this menu the allowed number of starts per hour can be
set. If this number is exceeded, an alarm occurs and the
action chosen in menu [2341] is performed.
The alarm is active until the hour has expired and a new start
is allowed. The first hour is counted directly from the first
start of the motor, whereas the following hour is counted not
directly, but from the moment a new start is done, i.e. no
rolling hour.
Minimum time between starts [2343]
In this menu a minimum time between consecutive starts can
be set. If a new start attempt is made before the minimum
time is expired an alarm will occur and the action chosen in
menu [2341] is performed. The alarm remains active until
the chosen minimum time has expired and a new start is
allowed.
Time to next start [2344]
In this menu the time to the next allowed start is shown.
Counts down from set value in menu [2343].
Phase Loss
Autoreset is available for single phase loss alarm, menu
[2561].
Multiple and internal phase loss
A multiple phase loss always results in a hard trip. If there is
an external phase loss (mains supply), this is not indicated
before an alarm delay of 2 seconds. If the phase loss is internal
(thyristor problem), the trip is activated immediately in order
to prevent faulty actions from damaging the softstarter and
motor.
If the lost phases reappear within 2 seconds an automatic
restart is performed.
Single phase loss
A single phase loss results in an immediate interruption of
operation if it occurs during start, jog or stop. If, for start
and jog, the lost phase should reappear within 2 seconds, an
automatic restart is performed.
For other functions, the alarm action on single phase loss can
be set in menu [235]. This will take place if the phase loss
lasts for more than 2 seconds.
Restart
The automatic restart is usually performed as for normal
operation, and according the set start method, menu [331].
Torque boost [337] is executed if enabled, however the jog
function at start [350] is not executed in this case.
Any automatic restart within 2 seconds is not counted for in
a start limitation protection [234].
For phase loss situations exceeding 2 seconds an automatic
restart can be accomplished by using autoreset [2561].
A phase loss alarm is reset when the alarm condition is gone
and a new start signal is given.
Single Phase Loss Alarm Action [235]
The action on a single phase loss is set in this menu. The
relevant action is performed when any phase is lost for more
than 2 seconds.
NOTE: Single phase loss is only detected for incoming
phases (L1, L2, and L3), and not for phases feeding the
2344 read-only TimeToStart minutes. Singlephase235FWD/REV/L1–3 condition onlyincoming; source restartin2seconds, startlimit exception and torque-boost inclusion retained.
Parameter panel 2342 Starts/h; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2343 MinTBtwStrt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2344 TimTNxtStrt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 235 SnglPhLossAA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 2342 Starts/h — PDF page 69
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10 |
| 2 | Range: | 1 - 99 |
Parameter panel 2343 MinTBtwStrt — PDF page 69
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Range: | 1 - 60 min |
Parameter panel 2344 TimTNxtStrt — PDF page 69
| Source row | Label | Value |
|---|---|---|
| 1 | Unit | minutes |
| 2 | Resolution: | 1 min |
Parameter panel 235 SnglPhLossAA — PDF page 69
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Hard Trip |
| 2 | No action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 70
Manual reference: physical PDF page 70. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Current Limit Alarm Action [236]
This alarm is only active if there is a current limit coupled to
the start method (settings in [331] and [335]). An alarm is
activated if the current still is at the current limit when the
start time has expired. This means that the motor has not
reached full speed. If no action is programmed, there will be
a current peak at the end of the start ramp.Autoreset is
available for this function, menu [2525].
8.2.5
Parameter set handling [240]
Parameter sets are used if an application requires different
settings for different modes. See detailed description in
"Working with parameter sets", page 41.
There are four available parameter sets that can be
individually configured and stored in the control panel.
The selected motor (M1 - M4) [212] decides the parameter
settings for the motor data in menu group [220]. See
instructions in Handling motor data in parameter sets, page
42.
Select Set [241]
Here you select the parameter set, directly or from where the
selection is going to be controlled. Every menu included in
the parameter sets is designated A, B, C or D depending on
the active parameter set. This is shown in the lower left area
of the display, i.e. with an
as default. The active set is also
showed in [721] “TSA Status”.
The parameter sets can be changed during operation.
However, if the sets are using different motors (M1 to M4)
the set will be changed only when the motor is stopped.
NOTE: The parameter set cannot be changed
during run if the parameter set includes change
of the motor set (M1-M4).
241 selection A0/B1/C2/D3/DigIn4/Com5/Option6; options conditional. Parameter A–D can be selected separately from motor M1–M4, which mustchange stopped.
Parameter panel 236 CurrLim AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 241 Select Set; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 236 CurrLim AA — PDF page 70
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Hard Trip |
| 2 | No action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 241 Select Set — PDF page 70
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦blank source cell⟧ | A |
| 2 | A | 0 | Fixed selection of one of the 4 parameter sets A, B, C or D. |
| 3 | B | 1 | ⟦null: no independent source value⟧ |
| 4 | C | 2 | ⟦null: no independent source value⟧ |
| 5 | D | 3 | ⟦null: no independent source value⟧ |
| 6 | DigIn | 4 | Parameter set is selected via a digital input. Define which digital input in menu [520], Digital Inputs. |
| 7 | Com | 5 | Parameter set is selected via serial communication. |
| 8 | Option | 6 | The parameter set is set via an option. Only available if the option can control the selection. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 71
Manual reference: physical PDF page 71. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Copy Set [242]
This function copies the content of a parameter set into
another parameter set, e.g. A>B means that the content of
parameter set A is copied into parameter set B.
Load Default Values Into Set [243]
With this function different levels of factory settings can be
selected for the four parameter sets. When loading the default
settings, all changes made on the Emotron TSA softstarter are
set to factory settings. This function also includes selections
for loading default settings to the four different motor data
sets.
Copy all settings to control panel [244]
All the settings, including the motor data, can be copied
between the control board memory and a control panel,
(external or internal). This can be useful when transferring
settings to a second softstarter unit, for instance.
To put the copy/load function into practice, see different
setups in section 7.2.4, page 42.
If two control panels are connected to the softstarter (using
an optional external control panel), only one at a time can be
used for copying or loading data. While transferring data to
one control panel, the other control panel is temporarily
disabled.
To copy settings from the control board to a control panel,
use the actual control panel and set [244] “Copy to CP” to
“Copy”. This will copy all user parameter settings stored in
the control board, and erase any corresponding settings
previously stored in the control panel. While the data is
NOTE: The actual value of menus for viewing will not be
copied into the other set.
NOTE: Start commands will be ignored during copying or
loading.
NOTE: If the on-board RS-232 port is connected to a PC
or to an external control panel this will be temporarily
locked while copying or loading data to the internal
control panel.
Padlock242 copy;243 defaults panel stopped-only.244 copy operation continuesPDF72, temporarily blocksotherCP/RS232/Start. Printed exceptions211/221–22D/261/923 retained.
Parameter panel 242 Copy Set; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 243 Default>Set; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
-
row 9, column 3, row 10, column 3, row 11, column 3 share the source cell at row 8, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 242 Copy Set — PDF page 71
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦blank source cell⟧ | A>B |
| 2 | A>B | 0 | Copy set A to set B |
| 3 | A>C | 1 | Copy set A to set C |
| 4 | A>D | 2 | Copy set A to set D |
| 5 | B>A | 3 | Copy set B to set A |
| 6 | B>C | 4 | Copy set B to set C |
| 7 | B>D | 5 | Copy set B to set D |
| 8 | C>A | 6 | Copy set C to set A |
| 9 | C>B | 7 | Copy set C to set B |
| 10 | C>D | 8 | Copy set C to set D |
| 11 | D>A | 9 | Copy set D to set A |
| 12 | D>B | 10 | Copy set D to set B |
| 13 | D>C | 11 | Copy set D to set C |
Parameter panel 243 Default>Set — PDF page 71
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | A |
| 2 | A | 0 | Only the selected parameter set will revert to its default settings. |
| 3 | B | 1 | ⟦null: no independent source value⟧ |
| 4 | C | 2 | ⟦null: no independent source value⟧ |
| 5 | D | 3 | ⟦null: no independent source value⟧ |
| 6 | ABCD | 4 | All four parameter sets will revert to the default settings. |
| 7 | Factory | 5 | All settings, except [211], [221]-[22D], [261] and [923], will revert to the default settings. |
| 8 | M1 | 6 | Only the selected motor set will revert to its default settings. |
| 9 | M2 | 7 | ⟦null: no independent source value⟧ |
| 10 | M3 | 8 | ⟦null: no independent source value⟧ |
| 11 | M4 | 9 | ⟦null: no independent source value⟧ |
| 12 | M1M2M3 M4 |
10 | All four motor sets will revert to default settings. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 72
Manual reference: physical PDF page 72. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
transferred, “Copy” is flashing on the control panel from
which the command was activated, while the other control
panel will be temporarily inactive. When finished, “Transfer
OK!” is displayed, and it will be possible to give a new
command from any of the control panels.
Load settings from control panel [245]
This function can load single or multiple parameter sets and
motor data from the actual control panel to the softstarter
control board memory. This is carried out much in the same
way as above. The selected parameter sets from the control
panel are copied to the corresponding parameter sets in the
softstarter control board, i.e. A to A, B to B, M1 to M1, and
so on. The different choices are listed below.
If a second control panel is connected, this will not be
affected when loading from the first control panel.
NOTE: The actual value of menus for viewing will not be
copied into control panel memory set.
NOTE: Loading or copying will not affect the value in
menus for viewing.
Padlock244/245 stopped-only.245 singleA/B/C/D,ABCD,A+Mot…D+Mot,ABCD+Mot,M1…M4,allmotors,All have distinct codes0–16. Read-only values not affected.
Parameter panel 244 Copy to CP; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 245 Load from CP; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 244 Copy to CP — PDF page 72
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Copy |
| 2 | No Copy | 0 | Nothing will be copied |
| 3 | Copy | 1 | Copy all settings |
Parameter panel 245 Load from CP — PDF page 72
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Copy |
| 2 | No Copy | 0 | Nothing will be loaded. |
| 3 | A | 1 | Data from parameter set A is loaded. |
| 4 | B | 2 | Data from parameter set B is loaded. |
| 5 | C | 3 | Data from parameter set C is loaded. |
| 6 | D | 4 | Data from parameter set D is loaded. |
| 7 | ABCD | 5 | Data from parameter sets A, B, C and D are loaded. |
| 8 | A+Mot | 6 | Parameter set A and Motor data are loaded. |
| 9 | B+Mot | 7 | Parameter set B and Motor data are loaded. |
| 10 | C+Mot | 8 | Parameter set C and Motor data are loaded. |
| 11 | D+Mot | 9 | Parameter set D and Motor data are loaded. |
| 12 | ABCD+Mot | 10 | Parameter sets A, B, C, D and Motor data are loaded. |
| 13 | M1 | 11 | Data from motor 1 is loaded. |
| 14 | M2 | 12 | Data from motor 2 is loaded. |
| 15 | M3 | 13 | Data from motor 3 is loaded. |
| 16 | M4 | 14 | Data from motor 4 is loaded. |
| 17 | M1M2M3 M4 |
15 | Data from motor 1, 2, 3 and 4 are loaded. |
| 18 | All | 16 | All data is loaded from the control panel. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 73
Manual reference: physical PDF page 73. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.2.6
Autoreset [250]
With these menus an autoreset can be configured. The
benefit of this feature is that occasional trips that do not affect
the process will be automatically reset.
See also section 7.6.3, page 52.
Autoreset Attempts [251]
Any number set above 0 activates the autoreset. This means
that after a trip, the softstarter will restart the operation
automatically according to the number of attempts selected.
No restart attempts will take place unless all conditions are
normal.
If the counter for “Actual Autoreset Attempts” [2512]
contains more trips than the allowed number of attempts
selected in menu [2511], the autoreset cycle will be
interrupted. No autoreset will then take place.
For every 10 minutes that have passed without any new trip
the autoreset counter is counting down one count.
If the maximum number of trips has been reached, the trip
message time is marked with an “A”:
The example above shows the 3rd trip memory menu [830].
An overvoltage trip took place after running for 345 hours,
45 minutes and 12 seconds, at which time the allowed
number of autoreset attempts was exceeded.
If the autoreset counter has reached the set maximum, the
softstarter must be reset by a normal reset. See example
below:
•
Number of allowed autoreset attempts [2511]= 5.
Within 10 minutes 6 trips occur.
At the 6th trip there is no autoreset, because the
autoreset counter allows only 5 attempts to autoreset a
trip.
To reset the autoreset counter, give a new reset command
(from one of the sources for reset control selected in
menu [216]).
The autoreset counter is now zeroed.
Number of Allowed Autoreset attempts
[2511]
Number of Actual Autoreset attempts
[2512]
In this menu the status of the internal autoreset counter is
shown. If no new trips occur, the autoreset counter is
decreased with one count for every tenth minute.
Motor Protection Autoreset [252]
Menu group for automatic reset of motor protection alarms.
Motor I²t protection autoreset [2521]
The delay counter starts counting when the I²t value is low
enough to allow for a new start. This means that first the
internal thermal motor model will require time for cooling
down to a thermal capacity of 95% (if internal thermal motor
protection is enabled). Then the delay time set in this menu
is added on to this time. When the delay time has elapsed, the
alarm will be reset and a restart attempt will automatically be
made.
WARNING!
If the “Run” input signal is active (high) and
level-controlled start mode is selected, the
motor will start at the reset command.
Note that “level control” is not fulfilling the
Machine directive.
830 OVERVOLT
Trp
A 345:45:12
NOTE: An autoreset is delayed by the remaining ramp
time.
Tripdisplay example830OverVoltA345:45:12 is historicalexample. Autoreset attempts defaultOff, time defaultOff, independent coolingthreshold beforedelay. Warning glyph indicates restart may occur withRunhigh.
Parameter panel 2511 AllowedArst; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2512 ActualArst; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2521 Motor I2t; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2511 AllowedArst — PDF page 73
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off (no autoreset) |
| 2 | Range: | 0–10 attempts |
Parameter panel 2512 ActualArst — PDF page 73
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0 |
Parameter panel 2521 Motor I2t — PDF page 73
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | Off |
| 3 | 1–3600 | 1–3600 | 1–3,600 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 74
Manual reference: physical PDF page 74. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PT100 autoreset [2522]
The delay counter starts counting when all PT100 inputs are
below the set temperature in menu [2322].
PTC autoreset [2523]
The delay counter starts counting when all PTC values are
below their respective limit. This means that if e.g. only the
internal power board PTC is present, the PB-PTC resistance
has to go down to 2,260 Ohm, which decides the minimum
time before autoreset. The time set in this menu is then
added on to the time for cooling down.
For corresponding resistance limits regarding PTC option
boards, please refer to the PTC/PT100 board 2.0 instruction
manual.
Locked Rotor autoreset [2524]
In this menu the delay time for an autoreset of a locked rotor
alarm is set. As a locked rotor cannot be detected in stopped
state, the delay time starts counting immediately after the
alarm action has been executed. When the delay time has
elapsed, the alarm will be reset and a restart attempt will
automatically be made.
Current Limit autoreset [2525]
In this menu the delay time for an autoreset of a current limit
alarm is set. As a current limit fault condition cannot be
detected in stopped state, the delay time starts counting
immediately after the alarm action has been executed. When
the delay time has elapsed, the alarm will be reset and a restart
attempt will automatically be made.
Communication Error autoreset [253]
The delay counter starts counting as soon as communication
is reestablished.
Process Protection Autoreset [254]
When the load monitor function is used, menu group [410],
the following settings for autoreset can be done.
Load Monitor Max Alarm autoreset
[2541]
The delay counter starts counting immediately.
NOTE: An autoreset is delayed by the remaining ramp
time.
PTC literal2,260Ohm in prose, not rounded2.2kΩ. All sixpanel ranges Off/code0 and1–3600s distinct; delaytrigger is specific to eachalarm.
Parameter panel 2522 PT100; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2525 Curr Lim; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 253 ComErrArst; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2523 PTC; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2524 LockedRotor; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2541 MaxAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2522 PT100 — PDF page 74
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | Off |
| 3 | 1–3600 | 1–3600 | 1–3,600 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 75
Manual reference: physical PDF page 75. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Load Monitor Max Pre-Alarm autoreset
[2542]
The delay counter starts counting immediately.
Load Monitor Min Pre-Alarm autoreset
[2543]
Load Monitor Min Alarm autoreset
[2544]
External Alarm 1 autoreset [2549]
The delay counter starts counting as soon as the relevant
external alarm input is inactive.
External Alarm 2 autoreset [254A]
Softstarter Protection autoreset [255]
For alarms that are present to protect the softstarter, the
following settings for autoreset can be done.
Overtemperature autoreset [2551]
In this menu the delay time for autoreset is set for a softstarter
overheated alarm. The delay time starts counting when the
fault is removed. This means the softstarter has to be cooled
down. When the delay time has elapsed, the alarm will be
reset and a restart attempt will automatically be made.
Start Limitation autoreset [2552]
The delay counter starts counting when the time to next
allowed start, set in menu [2354], has decreased to zero.
Time-to-start reference under2552 is visibly2354, while detailed2344 earlier remains separately retained. No correction to printedmenu supplied.
Parameter panel 254A Ext Alarm 2; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2542 MaxPAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2543 MinPAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2551 Overtemp; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2544 MinAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2552 Start Limit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2549 Ext Alarm 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 254A Ext Alarm 2 — PDF page 75
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | Off |
| 3 | 1–3600 | 1–3600 | 1–3,600 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 76
Manual reference: physical PDF page 76. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Mains failure autoreset [256]
The following menus are intended for autoreset of different
mains fault conditions.
Phase Input loss autoreset [2561]
As a phase input failure cannot be detected in a stopped state,
the delay time counter starts counting immediately after the
alarm action has been executed. When the delay time has
elapsed, the alarm will be reset and a restart attempt will
automatically be made.
Voltage Unbalance autoreset [2562]
In this menu the delay time for an autoreset of a voltage
unbalance alarm [441] is set. The delay time starts counting
when the fault is removed. Usually, the mains voltage will not
be available to the softstarter in a stopped state as the mains
contactor is deactivated. In this case a voltage unbalance
failure cannot be detected in a stopped state and the delay
time starts counting immediately after the alarm action has
been executed. When the delay time has elapsed, the alarm
will be reset and a restart attempt will automatically be made.
Overvoltage autoreset [2563]
In this menu the delay time for an autoreset of an overvoltage
alarm [442] is set. The delay time starts counting when the
fault is removed. Usually, the mains voltage will not be
available to the softstarter in a stopped state as the mains
contactor is deactivated. In this case an overvoltage failure
cannot be detected in stopped state and the delay time starts
counting immediately after the alarm action has been
executed. When the delay time has elapsed, the alarm will be
reset and a restart attempt will automatically be made.
Undervoltage autoreset [2564]
In this menu the delay time for an autoreset of an
undervoltage alarm [443] is set. The delay time starts
counting when the fault is removed. Usually, the mains
voltage will not be available to the softstarter in a stopped
state as the mains contactor is deactivated. In this case an
undervoltage failure cannot be detected in a stopped state
and the delay time starts counting immediately after the
Parameter panel 2561 Phase Input; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2564 Undervolt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2562 Volt unbal; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2563 Overvolt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2561 Phase Input — PDF page 76
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | Off |
| 3 | 1–3600 | 1–3600 | 1–3,600 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 77
Manual reference: physical PDF page 77. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.2.7
Serial Communication [260]
In this menu we configure parameters for the serial
communication options.
The RS485 and USB option (com type setting USB/RS485
in menu [261]) uses the standard Modbus RTU protocol
with a selectable baudrate in menu [2621] and Modbus
address [2622].
In addition to this, there are also a number of fieldbus
options available, e.g. Profibus/DeviceNet/ModbusTCP/
Profinet IO etc. When using a fieldbus option, menu [261]
Com Type must be set to Fieldbus. The detailed fieldbus
configuration is contained in menu [263] Fieldbus and its
Submenus.
The com type RS232, is reserved for future RS232 options
but is also used to perform a soft reset of the Fieldbus
module, which is required after e.g. node address
configuration in many cases (network dependant).
For more information see Chapter 9. page 123 and respective
option manual.
There is also the onboard (CB) RS232, which is always active
with fixed baudrate 9600 and fixed address =1, see Chapter
3.2 page 14.
Communication Type [261]
Valid communication option slot.
*) Future options.
Modbus RTU [262]
Set up the parameters for Modbus/RTU) communication.
Baudrate [2621]
Set the baud rate for the communication.
Address [2622]
Enter the unit address for the softstarter.
Fieldbus [263]
Set up the parameters for fieldbus communication.
NOTE: Toggling the setting from Fieldbus to RS232 in
this menu will perform a soft reset (re-boot) of the
Fieldbus module.
NOTE: This baud rate is valid only for communication via
the RS485 and USB options.
NOTE: This address is valid only for communication via
262 Modbus RTU
Stp
263 Fieldbus
OnboardRS232 fixed9600/address1 is not2621/2622 configuration; optioncommunication tables applyonly RS485/USB. Futureoptionasterisks applyEtherCATandBluetooth.
Parameter panel 2621 Baudrate; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3, row 6, column 3, row 7, column 3, row 8, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 261 Com Type; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2622 Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2621 Baudrate — PDF page 77
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | 9600 |
| 2 | 2400 | 0 | Selected baudrate |
| 3 | 4800 | 1 | ⟦null: no independent source value⟧ |
| 4 | 9600 | 2 | ⟦null: no independent source value⟧ |
| 5 | 19200 | 3 | ⟦null: no independent source value⟧ |
| 6 | 38400 | 4 | ⟦null: no independent source value⟧ |
| 7 | 57600 | 5 | ⟦null: no independent source value⟧ |
| 8 | 115200 | 6 | ⟦null: no independent source value⟧ |
Parameter panel 261 Com Type — PDF page 77
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | RS232 |
| 2 | RS232 | 0 | RS232 (Fieldbus reset, see note below) |
| 3 | Fieldbus | 1 | Fieldbus option mounted (e.g. Profibus, DeviceNet, Modbus/TCP or EtherCAT*) |
| 4 | USB/ RS485/BT |
2 | USB, RS485 or Bluetooth* option mounted |
Parameter panel 2622 Address — PDF page 77
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 1 |
| 2 | Selection: | 1–247 |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 78
Manual reference: physical PDF page 78. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Address [2631]
Enter or view the unit/node address of the softstarter. Read
& Write access for Profibus and DeviceNet. Read-only for
EtherCAT*.
*) Future option.
Process Data Mode [2632]
Enter the mode of process data (cyclic data). For further
information, see the Fieldbus option manual.
Read/Write [2633]
Select “Read/Write” to control the softstarter over a fieldbus
network. For further information, see the Fieldbus option
manual.
Additional Process Values [2634]
Define the number of additional process values sent in cyclic
messages.
Communication Fault [264]
Main menu for communication fault/warning settings. For
further details please see the Fieldbus option manual.
Communication Fault Alarm Action
[2641]
Selects action if a communication fault is detected.
The following applies:
If RS232/485 is selected, the softstarter will execute the
selected action if there is no communication for the time set
in parameter [2642] “ComFlt Time”.
If Fieldbus is selected, the softstarter will execute the selected
action if:
- the internal communication between the control board
and fieldbus option is lost for the time set in menu
[2642] “ComFlt Time”.
- a serious network error has occurred.
Communication Fault Time [2642]
Defines the delay time for the trip/warning.
NOTE: Menu [2151] or [2152] must be set to COM to
activate the communication fault function supervision.
Parameter panel 2631 Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 3, column 2 share the source cell at row 3, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2632 PrData Mode; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2641 ComFlt AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
-
row 1, column 2, row 1, column 3 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 4, column 3, row 5, column 3 share the source cell at row 3, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 2633 Read/Write; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 4, column 2, row 4, column 3 share the source cell at row 4, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 2642 ComFlt Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2634 AddPrValues; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2631 Address — PDF page 78
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 62 |
| 2 | Range: | Profibus 0–126, DeviceNet 0–63 |
| 3 | Node address valid for Profibus(RW), DeviceNet (RW) and EtherCAT* (RO). |
⟦null: no independent source value⟧ |
Parameter panel 2632 PrData Mode — PDF page 78
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦blank source cell⟧ | Basic |
| 2 | None | 0-3 | Control/status information is not used. |
| 3 | Basic | 4-7 | 4 byte process data control/status information is used. |
Parameter panel 2641 ComFlt AA — PDF page 78
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: No action | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 2 | No action | 0 | No communication supervision. |
| 3 | Hard Trip | 1 | For a definition, see Table 21, page 45. |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 2633 Read/Write — PDF page 78
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | RW |
| 2 | RW | 0 | Read & Write |
| 3 | Read | 1 | Read-only |
| 4 | Valid for process data. Select “Read” (read-only) for logging process without writing process data. Select “RW” in normal cases to control inverter. |
⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
Parameter panel 2642 ComFlt Time — PDF page 78
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.5 s |
| 2 | Range: | 0.1-15 s |
Parameter panel 2634 AddPrValues — PDF page 78
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0 |
| 2 | Range: | 0-8 |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 79
Manual reference: physical PDF page 79. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Ethernet [265]
Settings for Ethernet module (Modbus/TCP, Profinet IO).
For further information, see the Fieldbus option manual.
IP Address [2651]
MAC Address [2652]
Subnet Mask [2653]
Gateway [2654]
DHCP [2655]
Fieldbus Signals [266]
Defines modbus mapping for additional process values. For
further information, see the Fieldbus option manual.
FB Signal 1 - 16 [2661]-[266G]
Used to create a block of parameters which are read/written
via communication. 1 to 8 read + 1 to 8 write parameters
possible. Modbus addresses are entered, the actual numbers
are found in the Fieldbus option manual.
Fieldbus Status [269]
Sub menus showing status of fieldbus parameters. For
detailed information, please see the Fieldbus option manual.
NOTE: The Ethernet module must be re-booted to
activate the below settings, for example by toggling
parameter [261] from fieldbus to RS232 and back. Non-
initialised settings are indicated by a flashing display
text.
Read-only
269 FB Status
Stp
LCD dottedaddress0.0.0.0 examples not acquireddevicevalues.2652 MACdefault uniqueEthernetmodule number; zerosdisplay is illustrative.2661–266G mapping requires externaldefinedModbusaddresses.
Parameter panel 2661 FB Signal 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2651 IP Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2652 MAC Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2653 Subnet Mask; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2654 Gateway; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2655 DHCP; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 2661 FB Signal 1 — PDF page 79
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0 |
| 2 | Range: | 0-65535 |
Parameter panel 2651 IP Address — PDF page 79
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.0.0.0 |
Parameter panel 2652 MAC Address — PDF page 79
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | A unique number for the Ethernet module. |
Parameter panel 2655 DHCP — PDF page 79
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | On/Off |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 80
Manual reference: physical PDF page 80. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.3
Process [300]
These parameters are mainly adjusted to create a process
signal used for analogue start/stop. The input signal is
rescaled in order to be used for viewing or as a signal for the
analogue comparators. The read-out actual value depends on
the selected process source, [321}.
8.3.1
View Process Value [310]
This menu is only visible if a process source is selected in
menu [321] Process Source (i.e. by default the menu is not
shown).
When selected, the actual value of the active (on-line) process
signal is viewed here.
8.3.2
Process Settings [320]
With these settings, the softstarter process value can be set up
to fit the application. The process value in menus [110],
[120], [310], and [711] all use the process unit selected in
[322] for the application, e.g. rpm, bar, or m3/h.
Process Source [321]
Selection of the signal source for the process value used to
start and stop of the motor. The signal levels are given in
menus [324] and [325]. The process source can be set to act
as a function of the process signal on analogue input, via a
communication bus, or temperature input via a PT100
board.
The selection F(x) indicates that a process unit and scaling is
needed, set in menus [322]-[325]. This makes it possible to
e.g. use pressure sensors to measure flow etc. If F(AnIn) is
used, “Process Val” must be selected in menu [511].
Process Unit [322]
Selection of the unit for the process value. This menu is only
visible if a process source is selected in menu [321] “Process
Source”.
User-defined Unit [323]
This menu is only displayed if “User” is selected in menu
[322]. The function enables the user to define a unit with six
symbols. Use the PREV and NEXT keys to move the cursor
to the required position. Then use the + and - keys to scroll
down the character list. Confirm the character by moving the
cursor to the next position by pressing the NEXT key.
NOTE: If F (Bus) is chosen in menu [321], see
section 9.5 Process value, page 124.
322 displayed units m³/h andft³/h retain cubicmeaning although nativeplain text flattens superscript. Userunit323 has sixsymbols; code table continuesPDF81; no missingrows inferred.
Parameter panel 322 Proc Unit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 310 ProcessValue; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
User unit character codes; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 321 Proc Source; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 322 Proc Unit — PDF page 80
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | No unit selection |
| 3 | % | 1 | Percent |
| 4 | °C | 2 | Degrees Centigrade |
| 5 | °F | 3 | Degrees Fahrenheit |
| 6 | bar | 4 | Pressure in bar |
| 7 | Pa | 5 | Pressure in Pascal |
| 8 | Nm | 6 | Torque |
| 9 | Hz | 7 | Frequency |
| 10 | rpm | 8 | Revolutions per minute |
| 11 | m3/h | 9 | Cubic metres per hour |
| 12 | gal/h | 10 | Gallons per hour |
| 13 | ft3/h | 11 | Cubic feet per hour |
| 14 | User | 12 | User defined unit |
Parameter panel 310 ProcessValue — PDF page 80
| Source row | Label | Value |
|---|---|---|
| 1 | Dependent on: | Process Source [321] and Process Unit [322] |
| 2 | All modes | Min according to menu [324] - max according to menu [325] |
User unit character codes — PDF page 80
| Source row | Character | No. for serial comm. |
Character | No. for serial comm. |
|---|---|---|---|---|
| 1 | Space | 0 | m | 58 |
| 2 | 0–9 | 1–10 | n | 59 |
| 3 | A | 11 | ñ | 60 |
| 4 | B | 12 | o | 61 |
| 5 | C | 13 | ó | 62 |
| 6 | D | 14 | ô | 63 |
| 7 | E | 15 | p | 64 |
| 8 | F | 16 | q | 65 |
| 9 | G | 17 | r | 66 |
| 10 | H | 18 | s | 67 |
| 11 | I | 19 | t | 68 |
| 12 | J | 20 | u | 69 |
| 13 | K | 21 | ü | 70 |
| 14 | L | 22 | v | 71 |
| 15 | M | 23 | w | 72 |
| 16 | N | 24 | x | 73 |
Parameter panel 321 Proc Source — PDF page 80
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Off |
| 2 | Off | 0 | No process source selected. |
| 3 | F(AnIn) | 1 | Function of analogue input. E.g. via PID control, [380]. |
| 4 | PT100 | 4 | Temperature as process value |
| 5 | F(Bus) | 7 | Function of communication value. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 81
Manual reference: physical PDF page 81. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example:
Create a user unit named “kPa”.
- When in the menu [323] press
to show the cursor.
- Press
to move the cursor to the rightmost position.
- Press
until the character “a” is displayed.
- Press
.
- Then press the
until “P” is displayed and press
- Repeat until you have entered “kPa”. Confirm with
When sending a unit name you send one character at a time
starting at the rightmost position.
Process Minimum [324]
This menu is only visible if a process source is selected in
menu [321].
This function sets the process value that corresponds to the
minimum input signal.
Process Maximum [325]
The function sets process value that corresponds to the
maximum input signal.
323 kPa example keysequence:Plus showscursor;Next movesrightmost;Plus to a;Prev;Plus toP;Prev;repeat fork;Enterconfirms. Character103 degree symbol;104literal2,105literal3; code57l finalrightpair blank.324 negative range literalopenparenthesis retained.
User unit character codes continued; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 323 User Unit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 324 Process Min; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 325 Process Max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
User unit character codes continued — PDF page 81
| Source row | Character | No. for serial comm. |
Character | No. for serial comm. |
|---|---|---|---|---|
| 1 | O | 25 | y | 74 |
| 2 | P | 26 | z | 75 |
| 3 | Q | 27 | å | 76 |
| 4 | R | 28 | ä | 77 |
| 5 | S | 29 | ö | 78 |
| 6 | T | 30 | ! | 79 |
| 7 | U | 31 | ¨ | 80 |
| 8 | Ü | 32 | # | 81 |
| 9 | V | 33 | $ | 82 |
| 10 | W | 34 | % | 83 |
| 11 | X | 35 | & | 84 |
| 12 | Y | 36 | · | 85 |
| 13 | Z | 37 | ( | 86 |
| 14 | Å | 38 | ) | 87 |
| 15 | Ä | 39 | * | 88 |
| 16 | Ö | 40 | + | 89 |
| 17 | a | 41 | , | 90 |
| 18 | á | 42 | - | 91 |
| 19 | b | 43 | . | 92 |
| 20 | c | 44 | / | 93 |
| 21 | d | 45 | : | 94 |
| 22 | e | 46 | ; | 95 |
| 23 | é | 47 | < | 96 |
| 24 | ê | 48 | = | 97 |
| 25 | ë | 49 | > | 98 |
| 26 | f | 50 | ? | 99 |
| 27 | g | 51 | @ | 100 |
| 28 | h | 52 | ^ | 101 |
| 29 | i | 53 | _ | 102 |
| 30 | í | 54 | ° | 103 |
| 31 | j | 55 | 2 | 104 |
| 32 | k | 56 | 3 | 105 |
| 33 | l | 57 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Parameter panel 323 User Unit — PDF page 81
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | No characters shown |
Parameter panel 324 Process Min — PDF page 81
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.000 |
| 2 | Range: | 0.000-10000 -10000– +10000 (F(AnIn, F(Bus), PT100) |
Parameter panel 325 Process Max — PDF page 81
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10.00 |
| 2 | Range: | 0.000-10000 |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 82
Manual reference: physical PDF page 82. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.3.3
Start setting [330]
Submenu with all the functions for starting.
Start method [331]
The available start methods are:
Linear or Square Torque Control
A properly configured torque-controlled start will lead to a
linear speed increase and low starting current without current
peaks. Fig. 40 shows the torque ramps for linear torque
control and square torque control. The “Initial Torque” value
is set in menu [332] and the value for “End Torque at Start”
is set in menu [333].
Fig. 40 Torque control at start
Voltage Control
Voltage control is selected when a linear voltage ramp is
desired. The thyristor switch on time will be ramped up
linearly, from “Initial Voltage”, menu [334], up to full mains
voltage. See Fig. 41.
Fig. 41 Initial voltage and start time.
Direct on-line, DOL
If this alternative is selected the motor can be accelerated as if
it was connected directly to the mains, resulting in a very fast
ramp.
For this type of operation:
Check whether the motor can accelerate the required load
(DOL start). This function can also be used with shorted
thyristors.
Fig. 42 DOL start.
Initial Torque [332]
Used with start method linear/square torque control.
End Torque at Start [333]
Time
Torque
Start time
End torque
Nominal torque
Initial torque
1 Linear
2 Square
Voltage
Un_mot
6-7 x In_soft
FLC
Figure40 torque vsTime:curve1Linear,curve2Square;332initialtorque,333endtorque,Tnnominal,Starttime. Figure41 voltage vsTime:334initial,Un_mot,336Starttime. Figure42 DOL current6–7×In_soft peak,FLCsettled,Time;illustrative not guaranteed limit.
Parameter panel 331 Start Method; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 332 Init Torque; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 333 EndTorqueSt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 331 Start Method — PDF page 82
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦blank source cell⟧ | Lin Torq Ctr |
| 2 | Lin Torq Ctr | 1 | The motor torque is controlled according to a linear ramp, set in menu [332] and [333]. |
| 3 | Sqr Torq Ctr | 2 | The motor torque is controlled according to a square ramp, set in menu [332] and [333]. |
| 4 | Voltage Ctr | 3 | The motor voltage is controlled according to a linear voltage ramp, menu [334]. |
| 5 | DOL | 4 | Direct online |
Parameter panel 332 Init Torque — PDF page 82
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10% |
| 2 | Range: | 0 - 250% of T n |
Parameter panel 333 EndTorqueSt — PDF page 82
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 150% |
| 2 | Range: | 0 - 250% of T n |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 83
Manual reference: physical PDF page 83. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Initial Voltage [334]
Used with start method voltage control.
Current Limit [335]
A current limit can be added to all starting methods. This
regulates the current during the start ramp until full voltage
is reached. The start attempt is continued during the set start
time in menu [336]. Should the current still be at the current
limit when the start time has expired, this will be indicated
by a warning message “Current Limit” and an optional alarm
action as set in menu [236]”Current Limit Alarm Action”.
Linear or square torque ramp with current
limit
The motor torque is controlled according to either a linear or
a square ramp as selected in menu [331].
The current limit regulator is activated when the current is
reaching the chosen value in [335], and switched off when
full output voltage is reached, or the start time has expired
[336].
Should the current fall to a value below the set current limit,
the current controller will be deactivated, and the torque
ramp reactivated. The original slope remains for the
continued torque ramp, therefore the resulting total starting
time will in this case be longer than the set start time.
Voltage ramp with current limit
The voltage period is increased linearly during the set start
time, from a value corresponding to the minimum allowed
voltage period plus the value set as start voltage, to full mains
voltage.
reaching the chosen value in [335], to be switched off when
the current controller will be deactivated, and the voltage
ramp reactivated.
When the current controller is deactivated (below current
limit), the voltage ramp slope will increase above the original
slope to accomplish a start within the set start time. See Fig.
43.
Fig. 43 Voltage ramp with current limit period.
DOL with current limit
This could also be called “pure current limit start”.
The switch-on period is increased linearly during the set start
switch-on period plus the value set as start voltage, to full
voltage. The ramp time for the voltage ramp is 6 seconds.
approaching the chosen value, to be switched off when full
output voltage is reached, or the start time has expired [336].
Fig. 44 Direct on-line start in combination with current limit
at start.
If the regulator still is in active mode when the start time
expires, a “Current Limit” alarm is issued, and the alarm
action set in menu [236] is executed.
If the softstarter is not tripped for current limit time-out, the
current regulator is deactivated and the switch-on period is
increased to full-on with the slope of the 6 s ramp.
Current
Start time
Limit period
Current limit
FLC
Figure43 U[V] vs t[s],Un_mot,currentlimitperiod,Starttime; dashedand solid ramps qualitative. Figure44 I[A] vs t[s],currentlimit plateau,FLC,Starttime. DOL current-limit case6secondramp source text; graph not extra numeric evidence.
Parameter panel 334 Init Volt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 335 Curr Limit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 334 Init Volt — PDF page 83
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 30% |
| 2 | Range: | 0 - 90% of U [221] n_mot |
Parameter panel 335 Curr Limit — PDF page 83
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Range: | Off, 150 - 500% of I [224] n_mot |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 84
Manual reference: physical PDF page 84. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Start Time [336]
The start time is defined as the time during which a start
attempt is done.
This menu is directly accessible for all start methods in menu
[331] except “DOL”. However, if combined with a current
limit in menu [335], the start time function is also available
for “DOL”.
Torque Boost [337]
In specific applications torque boost is required for the start.
The torque boost parameter enables a high torque to be
obtained by providing a high current for 0.1-2 seconds at
start. This enables a soft start of the motor even if the break
away torque is high at the start. An example is crushing mills
applications etc.
Fig. 45 Torque boost principle.
Torque boost may be activated before the start ramp. The
current regulator is activated immediately, and the current is
controlled to be at the set “Torque Boost Current Limit”
[3371] for the set “Torque Boost Time” [3372]. See Fig. 45.
The switch-on period remains at the value assigned during
torque boost if the “Start Method” [331] is set to “torque
control” (linear or square), or if a current limit is applied in
menu [335]. In this case the torque or the current regulator
respectively will handle the transition from torque boost to
ramping. If voltage control is selected as start method - with
or without current limit - the switch-on period is set to the
correct initial value for the voltage ramp.
If “torque boost” is used, the total start time is prolonged with
the “Torque Boost Time” [3372].
Torque Boost Current Limit [3371]
Torque Boost Time [3372]
8.3.4
Stop Setting [340]
Stopping is always initiated by triggering of the thyristors to
take over the current when the bypass contact is opened.
When the current is correctly flowing through the thyristors,
the selected stop method is executed.
Stop Method [341]
The available stop methods are:
Linear or Square Torque Control
A torque-controlled stop could be used when a sudden stop
of the motor could harm the application. The motor torque
is controlled according to either a linear or a square ramp,
from the actual torque value to the set “End Torque at Stop”
in menu [342]. See Fig. 46 below.
NOTE: Even though the current limit can be set as low as
150% of the nominal motor current value [224], this
minimum value cannot be used generally. If the current
limit is set too low in relation to the application’s
requirements, the motor will not be able to accelerate
the load.
NOTE: Check that the nominal motor current is set
properly in menu [224] if the current limit functionality is
used.
Torque boost time
Torque boost current limit
FLC
Figure45 I[A] vs t[s],Torque boost current limit,FLC,Torque boost time.3372 boostduration extends totalstart. Stop341 introduction continuesPDF85; Figure46 referenced there not yet read in this packet.
Parameter panel 3371 TB CurrLim; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 336 Start Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 3372 TB Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 3371 TB CurrLim — PDF page 84
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Range: | Off, 300 - 700% of I [224] n_mot |
Parameter panel 336 Start Time — PDF page 84
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10 s |
| 2 | Range: | 1 - 60 s |
Parameter panel 3372 TB Time — PDF page 84
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 1.0 s |
| 2 | Range: | 0.1 - 2.0 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 85
Manual reference: physical PDF page 85. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 46 Torque control at stop
Voltage Control
If a linear voltage-ramp is preferred for the stop, “voltage
control” is selected. First the voltage is reduced to the set
“Step Down Voltage at Stop” [343]. Then a linear ramp will
be followed until the minimum allowed switch-on period is
reached, the duration decided by “Stop Time” [345]. See Fig.
47, page 81.
Coast
The voltage is switched off and the motor is allowed to coast
to a stop.
Brake
Braking may be used in applications where the motor needs
to be stopped quickly. When this selection is made, the
braking method (“Dynamic Vector Brake” or “Reverse
Current Brake”) can be activated in menu [344].
End Torque at Stop [342]
This menu sets the end torque value when one of the torque
control functions is chosen in menu [341].
Step Down Voltage at Stop [343]
This setting is available when “voltage control” is chosen in
[341]. The switch-on period will step down to an
intermediate value, from where it will follow a linear voltage
ramp down to the minimum allowed switch-on period. The
duration of the ramp is set in “Stop Time” [345].
Fig. 47 Step down voltage at stop.
Braking Method [344]
This menu is available when “Brake” is chosen in [341].
Dynamic Vector Brake
With dynamic vector brake, the braking torque applied to
the motor will increase with decreasing speed. Dynamic
vector brake can be used for all loads not rotating too close to
synchronous speed when the motor voltage is switched off.
This is valid for most applications, as the load speed usually
decreases because of frictional losses in gears or belt drives
when the voltage is switched off. However, this method is less
suitable for loads with very high inertia, in which case the
reverse current brake is more efficient.
When the dynamic vector brake is used, no additional
connections or contactors are needed.
The actual speed is detected, and if this is above a certain
limit the dynamic vector brake is executed. For lower speeds
the DC brake is activated.
Time
Torque
Stop time
Nominal torque
End torque
1 Linear
2 Square
Voltage
Un_mot
Figure46 completes84: Torque vsTime,1Linear/2Square, Tn nominaltorque,342Endtorque,Stoptime. Figure47 Voltage vsTime,Un_mot,343stepdown,345Stoptime. Diagramgeometrygoverns; nointermediatevoltage inferred.
Parameter panel 342 EndTorqueStp; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 343 StepDwnVolt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 341 Stop Method; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 342 EndTorqueStp — PDF page 85
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0% |
| 2 | Range: | 0 - 100% of T n |
Parameter panel 343 StepDwnVolt — PDF page 85
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 100% |
| 2 | Range: | 0 - 100% of U [221] n_mot |
Parameter panel 341 Stop Method — PDF page 85
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | 4 | Coast |
| 2 | Lin Torq Ctr | 1 | The motor torque is controlled according to a linear ramp. |
| 3 | Sqr Torq Ctr | 2 | The motor torque is controlled according to a square ramp. |
| 4 | Voltage Ctr | 3 | The motor voltage is controlled according to a linear voltage ramp. |
| 5 | Coast | 4 | The motor coasts to a stop. |
| 6 | Brake | 5 | Braking method as activated in menu [344]. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 86
Manual reference: physical PDF page 86. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Reverse Current Brake
This braking method is especially suitable for quickly
stopping heavy loads with high inertia. A very high braking
torque can be applied to the motor even close to synchronous
speed. However, before applying a high braking torque it
should be checked whether the motor, the gear or belt drive,
and the load can withstand the high mechanical forces. To
avoid harmful vibrations, it is generally recommended to
select the lowest braking torque possible that still fulfils the
demands for a short braking time.
The braking is accomplished by phase-reversal of the current.
To enable this, two external mains contactors are needed
which are controlled by the relay outputs of the softstarter
The connection is showed in Fig. 14, page 18.
During start and full voltage operation the first contactor
(K1) will be activated. For braking, K1 will be opened and
the second contactor (K2) will be activated to change the
phase sequence. For security reasons it is possible to set a
delay time between these two signals in menu [346].
To activate the braking method, “Reverse Current Brake”
must also be selected in menu [344]. The actual speed is
detected, and the reverse current brake is active until the
speed is below a set limit. For lower speeds the DC brake is
activated.
DC brake (at low speed)
At low speed the DC brake mode is activated until the stop
time in [345] has elapsed. In DC-brake mode only two
phases (L2 and L3) are active.
The DC brake will automatically be deactivated when the
motor has stopped or when the stop time has expired.
Optionally an external rotation sensor can be connected via
digital input [520], using logical functions to end the DC
braking. See section 8.6, page 100.
In addition to the braking methods described here, there is
also a spinbrake. functionality available as a digital input. See
Spinbrake, page 39.
Stop Time [345]
“Stop Time” is defined as the time during which a stop
attempt is done. This function is available for all stop
methods except for “Coast”.
Reverse Current Braking Delay [346]
A delay time for the reverse current brake function can be set
in this menu. When the relay configured for
“RunSignalFWD” has been deactivated, the relay configured
for “RevCurrBrake” will not be activated until after the set
time delay.
Dynamic Vector Brake Strength [347]
The strength of the dynamic vector brake is set in this menu.
The value is expressed as a percentage of the available vector
braking power (dependent on motor characteristics).
DC Braking Strength [348]
The strength of the DC brake is set here, the value expressed
as a percentage of the maximum available DC braking power.
NOTE: If several softstarters are supplied from the same
power line and the braking functionality is used, the
softstarters should be connected with different phase
sequences, i.e. L1-L2-L3 on the first unit, L2-L3-L1 on the
next and so on.
NOTE: The stop time given in menu [345] is NOT the time
during which a full stop is completed. It is a time-out
function for a stop attempt.
344defaultDynVectBrk0,RevCurrBrk1. Source distinguishesDynamicvector,noexternalcontactors,fromreversecurrentrequiringK1/K2anddelay346. DCmodeusesL2/L3. StopTime345timeoutnotguaranteedfullstop.
Parameter panel 345 Stop Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 346 RevC Brk Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 344 Brake Method; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 347 Brk Strength; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 348 DCB Strength; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 345 Stop Time — PDF page 86
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10 s |
| 2 | Range: | 0 – 120s |
Parameter panel 346 RevC Brk Dly — PDF page 86
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.5 s |
| 2 | Range: | 0 – 120s |
Parameter panel 344 Brake Method — PDF page 86
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | 0 | DynVectBrk |
| 2 | DynVectBrk | 0 | Dynamic Vector Brake |
| 3 | RevCurrBrk | 1 | Reverse Current Brake |
Parameter panel 347 Brk Strength — PDF page 86
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 75 % |
| 2 | Range: | 0 – 100% |
Parameter panel 348 DCB Strength — PDF page 86
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 15 % |
| 2 | Range: | 0 – 100% |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 87
Manual reference: physical PDF page 87. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Switch to DC Brake [349]
Here you set the speed at which the braking method should
be switched to DC brake. The speed is expressed as a
percentage of the nominal motor speed.
8.3.5
Jog [350]
For setting of the jog function, see section 7.1.3, page 40.
The jog function can be activated by a start via the keyboard,
digital input (“Remote”) or communication option, menu
[2152] “Jog Control”, page 58.
For the “Remote” activation of the jog command, the digital
input must be set to “Jog FWD” and/or “Jog REV” in menu
[520].
For information about the jog keys on the control panel, see
section 6.4.2, page 35.
The Jog function will automatically generate a run command
as long as the Jog function is active. This is independent of
the settings in menu [2151] “Run/Stop Control”.
Fig. 48 Jog command
Jog Speed Forward [351]
Jog Speed Reverse [352]
NOTE: For the jog function to be available, the rotation
direction must be allowed in [219].
Jog speed
Jog command
t [s]
n [rpm]
Figure48 n[rpm] vs t[s],Jogspeeddashedline;lowerJogcommandpulses. Curvesillustratejogtimecorrespondencewithoutnumericalaccelerationtime. Allowed219andJogcontrol2152apply.
Parameter panel 349 SwitchToDCB; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 351 JogSpd FWD; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 352 JogSpd REV; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 349 SwitchToDCB — PDF page 87
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 30 % |
| 2 | Range: | 0 – 100% of nominal motor speed [225] |
Parameter panel 351 JogSpd FWD — PDF page 87
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10% |
| 2 | Range: | Off, 1- 30% of nominal motor speed [225] |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 88
Manual reference: physical PDF page 88. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.4
Load Monitor and Process
Protection [400]
8.4.1
Load Monitor [410]
The functions in this menu enable the softstarter to be used
as a load monitor. See explanation in section 7.3.4, page 46.
The alarm actions for alarms and pre-alarms can be chosen
independently of each other in menus [4111], [4121],
[4131], and [4141]. The corresponding alarm delays are set
in menus [4113], [4123], [4133], and [4143].
•
Manual settings of the “Alarm Levels” are done in menus
[4112], [4122], [4132], and [4142].
Settings of the Autoset “Alarm Margins” are done in
menus [4171]- [4174], and the “Autoset Alarm” is
activated in menu [4175] when running at what is
considered to be the “Normal Load”.
All alarm levels are calculated and expressed as a percentage
that refers to the nominal motor power (menu [223]), i.e.
100% equals the nominal motor power.
It is possible to choose whether the load monitor shall be
active or not during start, using the start delay function in
menu [416].
See detailed explanation of the load monitor function
(including examples) in section 7.3.4, page 46. For more
information regarding alarms, trips and warning. See section
8.2.4, page 62.
Maximum Alarm [411]
These menus contain the settings for the load monitor
maximum alarm.
Maximum Alarm Action [4111]
Setting of the wanted alarm behaviour when a “Maximum
Alarm” has been detected.
Maximum Alarm Level [4112]
In this menu the set “Maximum Alarm Level” is shown (on
the right-hand side of the display - area F). At the same time
the actual value of the shaft power (%) is viewed on the left-
hand side of the display (area F), the value within brackets.
Since the actual shaft power is always visible in this menu, it
allows you to easily setup a suitable maximum alarm level.
The value of the maximum alarm level is given as a
percentage of the nominal motor power [223], i.e. a step of
1% is equal to 1% of the nominal motor power. When the
actual shaft power (shown within brackets in the display)
exceeds the set alarm level, the “Maximum Alarm Delay”
timer, menu [4113], will start counting down. When the
delay time has elapsed, an alarm will be generated according
to the selected “Maximum Alarm Action” in menu [4111].
This menu can be set manually to the required alarm level, or
it can be set indirectly, by performing an “Autoset”.
Example:
The “Max Alarm Level” is set to 80%. This means that when
the output shaft power exceeds 80% of the nominal motor
power, the alarm delay timer starts counting down.
Maximum Alarm Delay [4113]
When the load level exceeds the alarm level for a continuous
period longer than the set “Max Alarm Delay” time, the
selected “Maximum Alarm Action” in menu [4111] is
activated.
4112display RunA,(Pshaft%)leftcurrentvalue/116%rightsetting;116%defaultnotactualpowermeasurement.0–200%nominalmotorpower223 range.
Parameter panel 4112 MaxAlarmLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4113 MaxAlarmDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4111 MaxAlarmAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 4112 MaxAlarmLev — PDF page 88
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 116% |
| 2 | Range: | 0 - 200% of nominal motor power [223] |
Parameter panel 4113 MaxAlarmDel — PDF page 88
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.5 s |
| 2 | Range: | 0.1 - 90 s |
Parameter panel 4111 MaxAlarmAct — PDF page 88
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Action |
| 2 | No Action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 89
Manual reference: physical PDF page 89. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Maximum Pre-Alarm [412]
These menus contain the settings for the load monitor
maximum pre-alarm.
Maximum Pre-Alarm Action [4121]
Setting of the alarm behaviour when a “Maximum Pre-
Alarm” has been detected.
Maximum Pre-Alarm Level [4122]
The value of the maximum pre-alarm level is given as a
percentage of the nominal motor power [223]. When the
actual shaft power (shown within brackets in the display)
exceeds this level, the “Maximum Pre-Alarm Delay” timer,
menu [4123], will start counting down. When the delay time
has elapsed, an alarm will be generated according to the
selected “Maximum Pre-Alarm Action” in menu [4121].
This menu can be set manually to the required alarm level, or
it can be set indirectly, by performing an “Autoset”.
Maximum Pre-Alarm Delay [4123]
When the load level exceeds the alarm level for a continuous
period longer than the set “Max Pre-Alarm Delay” time, the
selected “Maximum Pre-Alarm Action” in menu [4121] is
activated.
Minimum Pre-Alarm [413]
minimum pre-alarm.
Minimum Pre-Alarm Action [4131]
Setting of the alarm behaviour when a “Minimum Pre-
Minimum Pre-Alarm Level [4132]
The value of the minimum pre-alarm level is given as a
actual shaft power (shown within brackets in the display) falls
to a value below this level, the “Minimum Pre-Alarm Delay”
timer, menu [4133], will start counting down. When the
delay time has elapsed, an alarm will be generated according
to the selected “Minimum Pre-Alarm Action” in menu
[4131].
Example:
The “Min Pre-Alarm Level” is set to 40%. This means that
when the shaft power falls to a value below 40% of the
nominal motor power, the alarm delay timer starts counting
down.
Minimum Pre-Alarm Delay [4133]
When the load level falls below the alarm level for a
continuous period longer than the set “Min Pre-Alarm
Delay” time, the selected “Minimum Pre-Alarm Action” in
menu [4131] is activated..
Parameter panel 4121 MaxPreAlAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 4131 MinPreAlAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4122 MaxPreAlLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4132 MinPreAlLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4123 MaxPreAlDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4133 MinPreAlDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4121 MaxPreAlAct — PDF page 89
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Action |
| 2 | No Action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 4122 MaxPreAlLev — PDF page 89
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 108% |
| 2 | Range: | 0 - 200% of nominal motor power [223] |
Parameter panel 4132 MinPreAlLev — PDF page 89
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 92% |
| 2 | Range: | 0 - 200% of nominal motor power [223] |
Parameter panel 4123 MaxPreAlDel — PDF page 89
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.5 s |
| 2 | Range: | 0.1–90 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 90
Manual reference: physical PDF page 90. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Minimum Alarm [414]
These menus contain the settings for the load monitor
minimum alarm.
Minimum Alarm Action [4141]
Setting of the alarm behaviour when a “Minimum Alarm”
has been detected.
Minimum Alarm Level [4142]
The value of the minimum alarm level is given as a
percentage of the nominal motor power [223]. When the
actual shaft power (shown within brackets in the display) falls
to a value below this level, the “Minimum Alarm Delay”
timer, menu [4143], will start counting down. When the
delay time has elapsed, an alarm will be generated according
to the selected “Minimum Alarm Action” in menu [4141].
This menu can be set manually to the required alarm level, or
it can be set indirectly, by performing an “Autoset”.
Minimum Alarm Delay [4143]
When the load level falls below the alarm level for a
continuous period longer than the set “Min Alarm Delay”
time, the selected “Minimum Alarm Action” in menu [4141]
is activated.
Start Delay [416]
This setting can be used to e.g. override an alarm during the
start-up procedure. The selected time will delay the
activation of the load monitor alarms after the run command.
Autoset [417]
This is an alternative procedure to set up the alarm levels
automatically which is based on the shaft power level at the
moment of the “Autoset”.
When autoset is performed, the actual value of the shaft
power is stored to menu [4176] Normal Load. The alarm
levels are then recalculated as follows:
After performing autoset, you can view the actual alarm level
settings in menus [4112], [4122], [4132], and [4142].
The alarm actions for all load monitor alarms, both manual
and autoset, are configured in menus [4111], [4121], [4131],
and [4141]; and the corresponding alarm delays are set in
menus [4113], [4123], [4133], and [4143].
Autoset is also available via digital input [520].
NOTE: If you have manually configured the alarm levels
in menus [4112], [4122], [4132], and [4142], you do not
need to do any settings in this menu or its sub-menus.
Table 24
Load monitor alarm levels
NOTE: Changing any alarm margin without performing
Autoset will NOT affect the alarm levels.
NOTE: A manual change of any alarm level will override
the last performed autoset, and menu [4176] Normal
Load will be set to “Off”.
Table24 physicallymergedOverloadspansmax/premax,Underloadspansmin/premin. Values4176±4171–4174add/subtractpercentagepoints; no multiplicativeinterpretation.
Parameter panel 416 Start Delay; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4141 MinAlarmAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Table24 load monitor alarm calculations; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
-
row 2, column 1 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 4, column 1 share the source cell at row 3, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 4142 MinAlarmLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4143 MinAlarmDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 416 Start Delay — PDF page 90
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10 s |
| 2 | Range: | 1 - 999 s |
Parameter panel 4141 MinAlarmAct — PDF page 90
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Action |
| 2 | No Action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Table24 load monitor alarm calculations — PDF page 90
| Source row | ⟦blank source cell⟧ | Alarm Level | Calculation |
|---|---|---|---|
| 1 | Overload | [4112] MaxAlarmLev | [4176] Normal Load + [4171] MaxAlarmMar |
| 2 | ⟦null: no independent source value⟧ | [4122] MaxPreAlLev | [4176] Normal Load + [4172] MaxPreAlMar |
| 3 | Underload | [4132] MinPreAlLev | [4176] Normal Load - [4173] MinPreAlMar |
| 4 | ⟦null: no independent source value⟧ | [4142] MinAlarmLev | [4176] Normal Load - [4174] MinAlarmMar |
Parameter panel 4142 MinAlarmLev — PDF page 90
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 84% |
| 2 | Range: | 0 - 200% of nominal motor power [223] |
Parameter panel 4143 MinAlarmDel — PDF page 90
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.5 s |
| 2 | Range: | 0.1 - 90 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 91
Manual reference: physical PDF page 91. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: 4172and4174 upperrange limits omitted in source; no value inferred.
Maximum Alarm Margin [4171]
This autoset menu sets the band above the Normal Load
[4176] that does not generate a maximum alarm. The set
“Max Alarm Margin” percentage is added on to the
percentage of the “Normal Load”. The resulting percentage
is where the maximum alarm level is put, related to nominal
motor power [223].
Example:
The “Maximum Alarm Margin” is set to 16%. The actual
shaft power at the moment of performing autoset is 45%.
The new maximum alarm will be set to 61%, which means
that the “Maximum Alarm Delay” timer in menu [4113] will
start counting down when the actual shaft power exceeds
61% (equal to 61% of the nominal motor power [223]).
When the alarm delay time has elapsed, a maximum alarm
could be generated, depending on the setting in menu [4111]
Max Alarm Action.
Maximum Pre-Alarm Margin [4172]
[4176] that does not generate a maximum pre-alarm. The set
Max Pre-Alarm Margin percentage is added on to the
is where the maximum pre-alarm level is put, related to
nominal motor power [223].
Minimum Pre-Alarm Margin [4173]
This autoset menu sets the band below the “Normal Load”
[4176] that does not generate a minimum pre-alarm. The set
Min Pre-Alarm Margin percentage is subtracted from the
is where the minimum pre-alarm level is put, related to
The “Min Pre-Alarm Margin” is set to 10%. In the above
example with a Normal Load of 45%, this will result in a
minimum pre-alarm level at 35% of the nominal motor
power. The “Minimum Pre-Alarm Delay” in menu [4133]
will start as soon as the actual shaft power has dropped to
below 35% of the nominal motor power [223], and the
action set in menu [4131] Min Pre-Alarm Action will be
executed when the delay time has elapsed.
Minimum Alarm Margin [4174]
This autoset menu sets the band below the Normal Load
[4176] that does not generate a minimum alarm. The set
Min Alarm Margin percentage is subtracted from the
is where the minimum alarm level is put, related to nominal
Autoset Alarm [4175]
When autoset is performed, the actual value of the shaft
power will be used as a basis when setting the alarm levels.
Autoset is performed by choosing “Yes” and confirming by
pressing “ENTER”. The message “Autoset OK!” is displayed
(alternatively “Failed!” if the command does not succeed). To
return to the menu display, press any key.
When autoset is performed, the actual shaft power, shown to
the left in the menu display, is stored to menu [4176] Normal
Load, and the alarm levels are recalculated according to the
description for menu [417] Autoset. A new autoset
command will overwrite previously used alarm levels.
Autoset can also be triggered by a remote signal, setting the
function of any digital input to “Autoset”. Note that this
signal is edge-triggered.
NOTE: Changing any margin without performing autoset
will NOT affect the alarm levels.
4172and4174rangevisibly0 - of nominal motor power[223]. Missingupperlimit leftunresolved;16/8%defaultsremainreadable. Example45+16=61,45−10=35isnotnewdefault.
Parameter panel 4173 MinPreAlMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4171 MaxAlarmMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4174 MinAlarmMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4172 MaxPreAlMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4173 MinPreAlMar — PDF page 91
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 8% |
| 2 | Range: | 0 - 100% of nominal motor power [223] |
Parameter panel 4171 MaxAlarmMar — PDF page 91
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 16% |
| 2 | Range: | 0–100% of nominal motor power [223] |
Parameter panel 4174 MinAlarmMar — PDF page 91
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 16% |
| 2 | Range: | 0 - of nominal motor power [223] |
Parameter panel 4172 MaxPreAlMar — PDF page 91
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 8% |
| 2 | Range: | 0 - of nominal motor power [223] |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 92
Manual reference: physical PDF page 92. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When performing an autoset the motor must be running
with the load that needs to be recorded.
Normal Load [4176]
This menu is read-only. If the menu shows “Off”, the
Autoset settings are deactivated, and the manually set alarm
levels in menu [4112], [4122], [4132], and [4142] are
applied.
If the menu shows a number, this is equal to the load level
(shaft power) at the time of performing the autoset. The
alarm levels have also been calculated based on this level ± the
autoset margins.
Example:
The menu shows 78%. This means that an autoset command
was last performed at a load level of 78% of the nominal
motor power [223], and the corresponding alarm levels have
been setup according to the margins set in menus [4171] -
[4174].
8.4.2
Process protection [420]
External Alarm [421]
The external alarm functionality is used to generate an alarm
depending on the state of an external alarm signal. Each of
the digital inputs can be configured for “Ext. Alarm 1” or
“Ext. Alarm 2”. If any digital input is configured for an
external alarm signal, activating (high) this input will cause
an external alarm to occur if the external alarm is enabled in
the corresponding menu ([4211] or [4212]).
External Alarm 1 Alarm Action [4211]
The following alarm actions are available for external alarm:
External Alarm 2 Alarm Action [4212]
Rotor Locked [422]
This alarm is used to avoid high motor current due to a
mechanically locked rotor. If the operation has been
interrupted due to a locked rotor alarm, the operation must
be reset to restart the motor. An autoreset command can be
set for the locked rotor alarm. See menu [2524].
NOTE: The motor must be running for the Autoset
procedure to succeed. A non-running motor or an
unfinished start delay generates a "Failed!" message.
NOTE: If more than one digital input is configured for the
same external alarm signal, activating (high) any of
these inputs will generate an alarm if this is enabled in
the corresponding menu for the external alarm.
4211/4212LCDNoAction andDefaultHardTrip remainseparate.4175No0/Yes1;4176read-onlyOff or0–200%. Sourcehigh-activeexternalalarmparagraph retaineddespiteoppositeselectionnotes99.
Parameter panel 4175 AutoSet Alrm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 4211 ExtAlarm1AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
- row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 4176 Normal Load; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4212 ExtAlarm2AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4175 AutoSet Alrm — PDF page 92
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No |
| 2 | No | 0 | ⟦blank source cell⟧ |
| 3 | Yes | 1 | ⟦blank source cell⟧ |
Parameter panel 4211 ExtAlarm1AA — PDF page 92
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Hard Trip |
| 2 | No Action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 4176 Normal Load — PDF page 92
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Range: | Off (Autoset deactivated) 0 - 200% of nominal motor power [223] |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 93
Manual reference: physical PDF page 93. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Locked Rotor Alarm Action [4221]
Locked Rotor Time [4222]
In this menu the time delay for detection of a locked rotor is
set. If the motor current exceeds its upper limit (menu
[4223]) for longer than the set “Locked Rotor Time”, this
will cause an alarm and the action selected in menu [4221]
will be executed.
Locked Rotor Current [4223]
The current limit is normally 4.8 times the nominal motor
current (menu [224]) but can be changed here.
8.4.3
Mains Protection [430]
The Emotron TSA continuously monitors the mains
voltage. This means the motor can easily be protected from
over- and undervoltage as well as from voltage unbalance
conditions. A phase reversal alarm is also available.
Voltage Unbalance Alarm [431]
Under this menu the settings for a voltage unbalance alarm
are selected.
Voltage Unbalance Alarm Action [4311]
In this menu the alarm action for a voltage unbalance alarm
is selected. The following alarm actions are available:
Voltage Unbalance Level [4312]
This menu is available if the voltage unbalance alarm is
enabled in menu [4311]. Here the maximum allowed voltage
unbalance level is entered, expressed as a percentage of the
nominal motor voltage. As soon as the difference between
any two line voltages exceeds this voltage level for a time
period equal to the delay time set in menu [4313], a voltage
unbalance alarm will occur and the action selected in menu
[4311] will be executed.
Voltage Unbalance Alarm Delay [4313]
In this menu the response delay for the voltage unbalance
alarm, as set in [4311] and [4312], is selected.
Parameter panel 4221 LockRot AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 4311 VoltUnbal AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4222 LockRotTime; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4223 LockRotCurr; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4312 UnbalLevel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4313 VoltUnbDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4221 LockRot AA — PDF page 93
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Action |
| 2 | No Action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 4222 LockRotTime — PDF page 93
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 5 s |
| 2 | Range: | 0.1 - 10 s |
Parameter panel 4223 LockRotCurr — PDF page 93
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 480% (4.8 x I ) n_mot |
| 2 | Range: | 100% - 1000% (1.0 x I - 10.0 x I ) n_mot n_mot |
Parameter panel 4312 UnbalLevel — PDF page 93
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 10% of the nominal motor voltage [221]. |
| 2 | Range: | 2 - 25% of the nominal motor voltage [221]. |
Parameter panel 4313 VoltUnbDel — PDF page 93
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 1 s |
| 2 | Range: | 1 - 90 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 94
Manual reference: physical PDF page 94. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Over-Voltage Alarm [432]
Under this menu the settings for an overvoltage alarm are
selected.
Over-Voltage Alarm Action [4321]
In this menu the alarm action for an overvoltage alarm is
selected. The following alarm actions are available:
Over-Voltage Level [4322]
This menu is available if overvoltage alarm is enabled in
menu [4321]. Here the voltage level for an overvoltage alarm
is entered, expressed as a percentage of the nominal motor
voltage. As soon as any line voltage exceeds this voltage level
for a time period equal to the set delay time in menu [4323],
an overvoltage alarm will occur and the action selected in
menu [4321] will be executed.
Over-Voltage Alarm Delay [4323]
In this menu the response delay for the voltage unbalance
alarm, as set in [4321] and [4322], is selected.
Under-Voltage Alarm [433]
In this menu group the settings for an undervoltage alarm are
Under-Voltage Alarm Action [4331]
In this menu the alarm action for the undervoltage alarm is
Under-Voltage Level [4332]
This menu is available if the undervoltage alarm is enabled in
menu [4331]. Here the voltage level for an undervoltage
alarm is entered, expressed as a percentage of the nominal
motor voltage. As soon as any line voltage falls below this
voltage level for a time period equal to the set delay time in
menu [4333], an undervoltage alarm will occur and the
action selected in menu [4331] will be executed.
Under-Voltage Alarm Delay [4333]
alarm, as set in [4431] and [4432], is selected
4333description literal4431/4432 andvoltageunbalance;4323alsoliteralunbalance. Tabledefaults/rangeskeptunderphysicalover/undervoltageheadings.
Parameter panel 4321 OverVolt AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 4331 UnderVolt AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4322 OverV Level; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4332 UnderV Level; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4323 OverV Del; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4333 UnderV Del; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 4321 OverVolt AA — PDF page 94
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Action |
| 2 | No Action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 4322 OverV Level — PDF page 94
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 115% of nominal motor voltage [221]. |
| 2 | Range: | 100 - 150% of nominal motor voltage [221]. |
Parameter panel 4332 UnderV Level — PDF page 94
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 85% of nominal motor voltage [221]. |
| 2 | Range: | 75 - 100% of nominal motor voltage [221]. |
Parameter panel 4323 OverV Del — PDF page 94
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 1s |
| 2 | Range: | 1 - 90 s |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 95
Manual reference: physical PDF page 95. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Phase Reversal Alarm [434]
If this function is activated, an alarm will be issued if the
wrong phase sequence is detected prior to a start.
Phase Reversal Alarm Action [4341]
In this menu the alarm action for a phase reversal alarm is
selected. The softstarter will detect the phase sequence prior
to each start attempt. If the actual phase sequence does not
match the allowed phase sequence set in menu [4342], the
action chosen in this menu will be executed.
To enable the phase reversal alarm, a motor has to be
connected and the mains voltage has to be switched on. The
alarm is only valid at starting attempts.
Allowed Phase Sequence [4342]
In this menu the allowed phase sequence is selected.
8.5
I/O [500]
Main menu with all the settings of the standard inputs and
outputs of the softstarter.
8.5.1
Analogue Input [510]
Submenu with all settings for the analogue inputs.
Analogue Input Function [511]
Sets the function for the Analogue input. Scale and range are
defined by “AnIn Advanced” settings in menu [513].
Analogue Input Setup [512]
The analogue input setup is used to configure the analogue
input in accordance with the signal used that will be
connected to the analogue input. With this selection the
input can be determined as current (4-20 mA) or voltage
(0-10 V) controlled input. Other selections are available for
using a threshold (live zero), or a user defined input range.
Fig. 49 Select voltage or current input with jumper S1.
NOTE: When “AnIn Fc” is set to ”Off”, the connected
signal will still be available for “Comparators” [610].
NOTE: The selection of voltage or current input is done
with S1. When the jumper is in voltage mode only the
voltage menu items are selectable. With the jumper in
current mode only the current menu items are
selectable.
S1
Figure49S1selectsU/I voltage/current. Illustrationterminalnumbers11–20,21–24,31–33,69–70 andPE/N/L remainoriginalgeometry; no topologyinferred. Correct511tableDefaultProcessVal;Off0;ProcessVal3.
Parameter panel 511 AnIn Fc; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 4341 PhaseRevAA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
- row 3, column 3, row 4, column 3, row 5, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
Parameter panel 4342 AllowedSequ; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 511 AnIn Fc — PDF page 95
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Process Val |
| 2 | Off | 0 | Input is not active. |
| 3 | Process Val | 3 | The input value equals an actual process value and can be used as comparator input for creating a start signal. It can also be used to display and view the actual process value. |
Parameter panel 4341 PhaseRevAA — PDF page 95
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No Action |
| 2 | No Action | 0 | For a definition, see Table 21, page 45. |
| 3 | Hard Trip | 1 | ⟦null: no independent source value⟧ |
| 4 | Soft Trip | 3 | ⟦null: no independent source value⟧ |
| 5 | Warning | 4 | ⟦null: no independent source value⟧ |
Parameter panel 4342 AllowedSequ — PDF page 95
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | L123 |
| 2 | Selection: | L123 and L321 |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 96
Manual reference: physical PDF page 96. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 50 Normal full-scale configuration
Fig. 51 2–10 V/4–20 mA (Live Zero)
Analogue Input Advanced [513]
AnIn Min [5131]
Parameter to set the minimum value of the external
reference signal. Only visible if [512] = “User mA/V”.
AnIn Max [5132]
Parameter to set the maximum value of the external
reference signal. Only visible if [512] = “User mA/V.”
Special function: Inverted signal
If the AnIn minimum value is higher than the AnIn
maximum value, the input will act as an inverted input. See
Fig. 52.
NOTE: Always check the needed set up when the setting
of S1 is changed; selection will not adapt automatically.
Reference input signal
NOTE: The different menus will automatically be set to
either “mA” or “V”, based on the selection in “AnIn
Setup” [512].
513 AnIn Advan
Stp
Figure50 fullscale n[rpm]0–100% against0–10V/0–20mA. Figure51livezero n[rpm]0–100% from2V/4mAto10V/20mA. Graphlabelsretainedasprinted,notgeneralconversionclaim. S1change needsselectioncheck.
Parameter panel 512 AnIn Setup; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
-
row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
-
row 2, column 2 share the source cell at row 2, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 5131 AnIn Min; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5132 AnIn Max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 512 AnIn Setup — PDF page 96
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | 4-20 mA |
| 2 | Dependent on | ⟦null: no independent source value⟧ | Setting of jumper S1 |
| 3 | 4–20mA | 0 | The current input has a fixed threshold (Live Zero) of 4 mA and controls the full range for the input signal. See Fig. 51. |
| 4 | 0–20mA | 1 | Normal full current scale configuration of the input that controls the full range for the input signal. See Fig. 50. |
| 5 | User mA | 2 | The scale of the current controlled input, that controls the full range for the input signal. Can be defined by the advanced AnIn Min and AnIn Max menus. |
| 6 | 0–10V | 4 | Normal full voltage scale configuration of the input that controls the full range for the input signal. See Fig. 50. |
| 7 | 2–10V | 5 | The voltage input has a fixed threshold (Live Zero) of 2 V and controls the full range for the input signal. See Fig. 51. |
| 8 | User V | 6 | The scale of the voltage controlled input, that controls the full range for the input signal. Can be defined by the advanced AnIn Min and AnIn Max menus. |
Parameter panel 5131 AnIn Min — PDF page 96
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Min (0 V/4.00 mA) |
| 2 | Range: | 0.00–20.00 mA 0–10.00 V |
Parameter panel 5132 AnIn Max — PDF page 96
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Max (10.00 V/20.00 mA) |
| 2 | Range: | 0.00–20.00 mA 0–10.00 V |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 97
Manual reference: physical PDF page 97. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 52 Inverted input
AnIn Function Min [5134]
With “AnIn Function Min” the physical minimum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn [511].
AnIn Function Value Min [5135]
With “AnIn Function VaMin” you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5134].
AnIn Function Max [5136]
With “AnIn Function Max” the physical maximum value is
AnIn Function Value Max [5137]
With “AnIn Function VaMax” you define a user-defined
selected in menu [5136].
Example:
Process sensor is a sensor with the following specification:
Range:
0–3 bar
Output:
2–10 mA
Analogue input should be set up according to:
[512] AnIn Setup = User mA
[5131] AnIn Min = 2 mA
[5132] AnIn Max = 10 mA
[5134] AnIn Function Min = User-defined
[5135] AnIn VaMin = 0.000 bar
[5136] AnIn Function Max = User-defined
[5137] AnIn VaMax = 3.000 bar
Input signal
Inverted signal:
AnIn Min > AnIn Max
NOTE: With “AnIn Min”, “AnIn Max”, “AnIn Function Min”
and “AnIn Function Max” settings, loss of feedback
signals (e.g. voltage drop due to long sensor wiring) can
be compensated to ensure an accurate process signal.
Figure52 invertedinput: n[rpm]100%atleft0,descendingtoright10V/20mA;AnInMin>AnInMax. Sourcegraphqualitative; noadditionalpointvalues.
Parameter panel 5136 AnIn FcMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 5137 AnIn VaMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5134 AnIn FcMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5135 AnIn VaMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5136 AnIn FcMax — PDF page 97
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Max |
| 2 | Min | 0 | Min value |
| 3 | Max | 1 | Max value |
| 4 | User-defined | 2 | Define user value in menu [5137] |
Parameter panel 5137 AnIn VaMax — PDF page 97
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.000 |
| 2 | Range: | -10,000.000 – 10,000.000 |
Parameter panel 5134 AnIn FcMin — PDF page 97
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Min |
| 2 | Min | 0 | Min value |
| 3 | Max | 1 | Max value |
| 4 | User- defined |
2 | Define user value in menu [5135] |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 98
Manual reference: physical PDF page 98. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
AnIn Filter [5139]
If the input signal is unstable (e.g. fluctuation reference
value), the filter can be used to stabilise the signal. See Fig.
- This will result in a 63% change of the input signal
within the set “AnIn Filter time” (T). After 5 times the set
time (i.e. 5xT), AnIn will have reached 100% of the input
change.
Fig. 53
AnIn Enable [513A]
Parameter for enable/disable analogue input selection via
digital inputs (DigIn set to function “AnIn Select”).
8.5.2
Digital Inputs [520]
Submenu with all the settings for the digital inputs.
Digital Input 1 [521]
To select the function of the digital input.
On the standard control board there are four digital inputs.
If the same function is programmed for more than one input,
that function will be activated according to “OR” logic if
nothing else is stated.
T
AnIn change
Original AnIn signal
Filtered AnIn signal
NOTE: Additional inputs will become available when the
I/O option boards are connected.
Figure53 AnInchange100%,63%;originalstepversusfilteredcurve;Tand5×T on t[s]. Sourceclaims100%at5T;notaltered. InputStop/EnableAND; otherfunctionsORunlessstated.
Parameter panel 5139 AnIn Filt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 521 DigIn 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 513A AnIn Enabl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5139 AnIn Filt — PDF page 98
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.100 s |
| 2 | Range: | 0.001 – 10.0 s |
Parameter panel 521 DigIn 1 — PDF page 98
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Run FWD |
| 2 | Off | 0 | The input is not active. |
| 3 | Stop | 1 | Stop command according to the selected Stop mode in menu [340]. NOTE: The Stop command is active low. NOTE: Activated according to “AND” logic. |
| 4 | Reset | 2 | Reset command. To reset a Trip condition and to enable the Autoreset function. |
| 5 | Enable | 3 | Enable command. General start condition to run the softstarter. If made low during running, the output of the softstarter is cut off immediately, causing the motor to coast to zero speed. NOTE: If none of the digital inputs are programmed to “Enable”, the internal enable signal is set active. NOTE: Activated according to “AND” logic. |
| 6 | Run FWD | 4 | Run forward command (positive speed). The output of the softstarter will be a clockwise rotary field. |
| 7 | Run REV | 5 | Run reverse command (negative speed). The output of the softstarter will be a counter-clockwise rotary field. External contactors required. |
| 8 | Jog FWD | 6 | Activates the Jog forward function. Gives a run command with set Jog speed and direction, menu [350]. NOTE: Always level controlled even though edge control may be chosen in menu [21A]. |
| 9 | Jog REV | 7 | Activates the Jog reverse function. Gives a run command with set Jog speed and direction, menu [350]. NOTE: Always level controlled even though edge control may be chosen in menu [21A]. |
| 10 | Set Ctrl 1 | 8 | Activates other parameter set. See Table 25 for selection possibilities. |
| 11 | Set Ctrl 2 | 9 | Activates other parameter set. See Table 25 for selection possibilities. |
| 12 | Loc/Rem | 10 | Activates local mode defined in [2173]. |
Parameter panel 513A AnIn Enabl — PDF page 98
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | On |
| 2 | On | 0 | AnIn is always active |
| 3 | !DigIn | 1 | AnIn is only active if the digital input is low. |
| 4 | DigIn | 2 | AnIn is only active if the digital input is high. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 99
Manual reference: physical PDF page 99. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Digital Input 2 [522] to Digital Input 4
[524]
Same function as DigIn 1[521]. Default setting for DigIn 2
[522] is “Stop”. For DigIn 3 [523] the default is “Set Ctrl 1”
and for DigIn 4 [524] the default is “Reset”.
Additional digital inputs [529] to [52E]
Additional digital inputs with I/O option board installed,
“B1 DigIn 1” [529] - “B2 DigIn 3” [52E]. “B” stands for
“board”, 1 and 2 is the number of the board which is related
to the position of the I/O option board on the option
mounting plate. The functions and selections are the same as
for “DigIn 1” [521]. Default settings are “Off”.
8.5.3
Analogue Output [530]
Submenu with all settings for the analogue output.
Selections can be made from application and softstarter
values, in order to visualise actual status. Analogue output
can also be used as a mirror of the analogue input.
Analogue Output Function [531]
Sets the function for the analogue output. Scale and range are
defined by “AnOut Advanced” settings [533].
Table 25
NOTE: To activate the parameter set selection, menu
241 must be set to DigIn.
Digital521continuation includescodes11,12,13,14reserved,16–21;no15. Timerrowsliteralreferences6343/6313/6323/6333 preserved. Table25 A00,B10,C01,D11;241mustDigIn.
Digital input521 continuation; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 531 AnOut Fc; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Table25 parameter set controls; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Digital input521 continuation — PDF page 99
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | AnIn Select | 11 | Activates/deactivates analogue input defined in [513A]. |
| 2 | Autoset | 12 | Activates autoset of load monitor alarm levels according to menu group [417]. NOTE: Always level controlled even though edge control may be chosen in menu [21A]. |
| 3 | Spinbrake | 13 | See description Spinbrake, page 39. Can be activated either from inactive state (softstarter stopped but motor rotating) or active state (when running). |
| 4 | --- | 14 | (Reserved for future use). |
| 5 | Ext. Alarm 1 | 16 | Be aware that if there is nothing connected to the input, the softstarter will trip at “External Alarm 1” immediately. NOTE: The External Trip is active low. NOTE: Activated according to “AND” logic. See menu [2549]. |
| 6 | Ext. Alarm 2 | 17 | Be aware that if there is nothing connected to the input, the softstarter will trip at “External Alarm 2” immediately. NOTE: The External Alarm 2 is active low. See menu [254A]. |
| 7 | Timer 1 | 18 | Timer 1 Delay [6343] will be activated on the rising edge of this signal. |
| 8 | Timer 2 | 19 | Timer 1 Delay [6313] will be activated on the rising edge of this signal. |
| 9 | Timer 3 | 20 | Timer 2 Delay [6323] will be activated on the rising edge of this signal. |
| 10 | Timer 4 | 21 | Timer 1 Delay [6333] will be activated on the rising edge of this signal. |
Parameter panel 531 AnOut Fc — PDF page 99
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Current |
| 2 | Off | 0 | Analogue output not active. |
| 3 | Torque | 2 | Actual torque. |
| 4 | Process Val | 3 | Actual process value according to Process feedback signal. |
| 5 | Shaft Power | 4 | Actual shaft power. |
| 6 | Current | 6 | Actual current. |
| 7 | El power | 7 | Actual electrical power. |
| 8 | AnIn | 10 | Mirror of received signal value on AnIn. |
| 9 | Line Voltage | 14 | Mains supply |
| 10 | Therm Cap | 15 | Used thermal capacity |
Table25 parameter set controls — PDF page 99
| Source row | Parameter Set | Set Ctrl 1 | Set Ctrl 2 |
|---|---|---|---|
| 1 | A | 0 | 0 |
| 2 | B | 1 | 0 |
| 3 | C | 0 | 1 |
| 4 | D | 1 | 1 |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 100
Manual reference: physical PDF page 100. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Analogue Output Setup [532]
Preset scaling and offset of the output configuration.
Analogue Output Advanced [533]
With the functions in the “AnOut Advanced” menu, the
output can be completely defined according to the
application needs. The menus will automatically be adapted
to “mA” or “V”, according to the selection in “AnOut Setup”
[532].
Analogue Output Minimum [5331]
This parameter is automatically displayed if “User mA” or
“User V” is selected in menu “AnOut Setup” [532]. The
menu will automatically adapt to current or voltage setting
according to the selected setup. Only visible if [532] = “User
mA/V”.
Analogue Output Maximum [5332]
AnOut Function Minimum [5334]
With “AnOut Function Min” the physical minimum value is
scaled to selected presentation. The default scaling is
dependent of the selected function of AnOut [531].
Table 26, page 96 shows corresponding values for the min
and max selections depending on the function of the
analogue output [531].
NOTE: When “AnIn” is selected, the setup of the “AnOut”
[532] has to be set to 0-10 V or 0-20 mA. When the
“AnOut Setup” is set to e.g. 4-20 mA, the mirroring is not
working correctly.
533 AnOut Advan
Stp
Table 26
Table26 rangeforProcessValue324→325,ShaftPower0%→223,Current0A→224,ElPower0W→223,OutputVoltage0V→221,Torque0%→250%,AnInFunctionMin→FunctionMax. Thesearefunctionscalesnotallproductratings.
Parameter panel 5331 AnOut Min; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 532 AnOut Setup; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5332 AnOut Max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5334 AnOutFcMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Table26 analogue output min/max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Adjacent source context — repeated to preserve continuation:
Parameter panel 5331 AnOut Min — PDF page 100
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 4.00 mA |
| 2 | Range: | 0.00 – 20.00 mA, 0 – 10.00 V |
Parameter panel 532 AnOut Setup — PDF page 100
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦blank source cell⟧ | 4-20mA |
| 2 | 4–20mA | 0 | The current output has a fixed threshold (Live Zero) of 4 mA and controls the full range for the output signal. See Fig. 51. |
| 3 | 0–20mA | 1 | Normal full current scale configuration of the output that controls the full range for the output signal. See Fig. 50. |
| 4 | User mA | 2 | The scale of the current controlled output that controls the full range for the output signal. Can be defined by the advanced AnOut Min and AnOut Max menus. |
| 5 | 0 - 10V | 4 | Normal full voltage scale configuration of the output that controls the full range for the output signal. See Fig. 50. |
| 6 | 2–10V | 5 | The voltage output has a fixed threshold (Live Zero) of 2 V and controls the full range for the output signal. See Fig. 51. |
| 7 | User V | 6 | The scale of the voltage controlled output that controls the full range for the output signal. Can be defined by the advanced AnOut Min and AnOut Max menus. |
Parameter panel 5332 AnOut Max — PDF page 100
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 20.00 mA |
| 2 | Range: | 0.00–20.00 mA, 0–10.00 V |
Parameter panel 5334 AnOutFcMin — PDF page 100
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Min |
| 2 | Min | 0 | Min value |
| 3 | Max | 1 | Max value |
| 4 | User-defined | 2 | Define user value in menu [5335] |
Table26 analogue output min/max — PDF page 100
| Source row | AnOut Function |
Min Value | Max Value |
|---|---|---|---|
| 1 | Process Value | Process Min [324] | Process Max [325] |
| 2 | Shaft Power | 0% | Motor Power [223] |
| 3 | Current | 0 A | Motor Current [224] |
| 4 | El Power | 0 W | Motor Power [223] |
| 5 | Output Voltage | 0 V | Motor Voltage [221] |
| 6 | Torque | 0 % | 250 % |
| 7 | AnIn | AnIn Function Min | AnIn Function Max |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 101
Manual reference: physical PDF page 101. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example
Set the AnOut function for “Motor Current” to 0 A, set
”AnOut Function Min” [5334] to “User-defined” and
“AnOut Function Value Min” [5335] = 0.0. This results in an
analogue output signal from 0/4 mA to 20mA: from 0 A to
the value for “Motor Current” that is set in menu [224].
This principle is valid for all Min to Max settings.
AnOut Function Value Minimum [5335]
With “AnOutVaMin” you define a user-defined value for the
signal. Only visible when “User-defined” is selected in menu
[5334].
AnOut Function Maximum [5336]
With “AnOut Function Min” the physical minimum value is
scaled to selected presentation. The default scaling is
dependent on the selected function of AnOut [531]. See
Table 26, page 96.
AnOut Function Value Maximum [5337]
With “AnOut FunctionVaMax” you define a user-defined
value for the signal. Only visible when “User-defined” is
selected in menu [5334].
8.5.4
Relays [550]
Submenu with all the settings for the relay outputs. The relay
mode selection makes it possible to establish a “fail safe” relay
operation by using the normal closed contact to function as
the normal open contact.
Relay 1 [551]
Sets the function for the relay output 1.
NOTE: It is possible to set AnOut up as an inverted
output signal by setting “AnOut Min” > “AnOut Max”.
See Fig. 52.
NOTE: Additional relays will become available when I/O
option boards are connected. Maximum 2 boards with 3
relays each.
551LCDTrip versusDefaultOperation; selectionscontinue102.5336sourcewordingFunctionMinand5337reference5334retained; noautomaticediting.
Parameter panel 5335 AnOutVaMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 551 Relay 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 5336 AnOutFcMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 5337 AnOutVaMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Adjacent source context — repeated to preserve continuation:
Parameter panel 5335 AnOutVaMin — PDF page 101
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0.000 |
| 2 | Range: | -10,000.000–10,000.000 |
Parameter panel 551 Relay 1 — PDF page 101
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Operation |
| 2 | Off | 0 | Output is not active and constantly low. |
| 3 | On | 1 | Output is made constantly high, i.e. for checking circuits and trouble shooting. |
| 4 | Operation | 2 | See Fig. 54 |
| 5 | No Operation | 3 | Inverted operation |
| 6 | Bypass mode | 4 | See Fig. 54 |
| 7 | Acc/Dec | 5 | The speed is increasing or decreasing along the acc. ramp/dec. ramp. |
| 8 | No Trip | 6 | No Trip condition active. |
| 9 | Trip | 7 | A Trip condition is active. |
| 10 | AutoRst Trip | 8 | Autoreset trip condition active. |
| 11 | Warning | 9 | A Warning condition is active. |
| 12 | Ready | 10 | The softstarter is ready for operation and to accept a start command. This means that the softstarter is powered up and in good working condition. |
| 13 | I>I n_mot |
11 | The output current is higher than the motor nominal current [224], reduced according to Motor ventilation [228]. See Fig. 8.2.4. |
| 14 | RevCurrBrake | 12 | The output is used to control a reverse current brake. |
| 15 | LoadMonAlarm | 13 | Max or min alarm condition active (trip or warning). |
| 16 | Pre Alarm | 14 | Max or min pre-alarm condition active (trip or warning). |
| 17 | Max Alarm | 15 | Max alarm condition active (trip or warning). |
| 18 | Max PreAlarm | 16 | Max pre-alarm condition active (trip or warning). |
| 19 | Min Alarm | 17 | Min alarm condition active (trip or warning). |
Parameter panel 5336 AnOutFcMax — PDF page 101
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Max |
| 2 | Min | 0 | Min value |
| 3 | Max | 1 | Max value |
| 4 | User defined | 2 | Define user value in menu [5337 ] |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 102
Manual reference: physical PDF page 102. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Relay551 continuation codes18–60left,61–81then90/97/98/101/103–107/112right. OperationREVliteralnegative speed<0.5%;missingminus notinferred. I²t105labelmayflattennative.
Relay551 selections continuation; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Relay551 selections continuation — PDF page 102
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Min PreAlarm | 18 | Min pre-alarm condition active (trip or warning). |
| 2 | CA 1 | 19 | Analogue comparator 1 output. |
| 3 | !A1 | 20 | Analogue comp 1 inverted output. |
| 4 | CA 2 | 21 | Analogue comparator 2 output. |
| 5 | !A2 | 22 | Analogue comp 2 inverted output. |
| 6 | CA 3 | 23 | Analogue comparator 3 output. |
| 7 | !A3 | 24 | Analogue comp 3 inverted output. |
| 8 | CA 4 | 25 | Analogue comparator 4 output. |
| 9 | !A4 | 26 | Analogue comp 4 inverted output. |
| 10 | CD 1 | 27 | Digital comparator 1 output. |
| 11 | !D1 | 28 | Digital comp 1 inverted output. |
| 12 | CD 2 | 29 | Digital comparator 2 output. |
| 13 | !D2 | 30 | Digital comp 2 inverted output. |
| 14 | CD 3 | 31 | Digital comparator 3 output. |
| 15 | !D3 | 32 | Digital comp 3 inverted output. |
| 16 | CD 4 | 33 | Digital comparator 4 output. |
| 17 | !D4 | 34 | Digital comp 4 inverted output. |
| 18 | T1Q | 35 | Logic timer 1 output |
| 19 | !T1Q | 36 | Inverted logic timer 1 output |
| 20 | T2Q | 37 | Logic timer 2 output |
| 21 | !T2Q | 38 | Inverted logic timer 2 output |
| 22 | T3Q | 39 | Logic timer 3 output |
| 23 | !T3Q | 40 | Inverted logic timer 3 output |
| 24 | T4Q | 41 | Logic timer 4 output |
| 25 | !T4Q | 42 | Inverted logic timer 4 output |
| 26 | L1 | 43 | Logic output 1. |
| 27 | !L1 | 44 | Logic output 1 inverted. |
| 28 | L2 | 45 | Logic output 2. |
| 29 | !L2 | 46 | Logic output 2 inverted. |
| 30 | L3 | 47 | Logic output 3. |
| 31 | !L3 | 48 | Logic output 3 inverted. |
| 32 | L4 | 49 | Logic output 4. |
| 33 | !L4 | 50 | Logic output 4 inverted. |
| 34 | F1 | 51 | Flip-flop output 1. |
| 35 | !F1 | 52 | Flip-flop output 1 inverted. |
| 36 | F2 | 53 | Flip-flop output 2. |
| 37 | !F2 | 54 | Flip-flop output 2 inverted. |
| 38 | F3 | 55 | Flip-flop output 3. |
| 39 | !F3 | 56 | Flip-flop output 3 inverted. |
| 40 | F4 | 57 | Flip-flop output 4. |
| 41 | !F4 | 58 | Flip-flop output 4 inverted. |
| 42 | CTR1 | 59 | Counter output 1. |
| 43 | !CTR1 | 60 | Counter output 1 inverted. |
Relay551 selections continuation — PDF page 102
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | CTR2 | 61 | Counter output 2. |
| 2 | !CTR2 | 62 | Counter output 2 inverted. |
| 3 | CLK1 | 63 | Clock output 1 (Clock logic [660]). |
| 4 | !CLK1 | 64 | Clock output 1 inverted. |
| 5 | CLK2 | 65 | Clock output 2 (Clock logic [660]). |
| 6 | !CLK2 | 66 | Clock output 2 inverted. |
| 7 | Run Signal | 67 | Run command is active. The signal can be used to control the mains contactor |
| 8 | Loc/Rem | 68 | Local/Rem function is active |
| 9 | Acc | 69 | Acceleration along the acc. ramp |
| 10 | Dec | 70 | Deceleration along the dec. ramp |
| 11 | DigIn 1 | 71 | Digital input 1 |
| 12 | DigIn 2 | 72 | Digital input 2 |
| 13 | DigIn 3 | 73 | Digital input 3 |
| 14 | DigIn 4 | 74 | Digital input 4 |
| 15 | RunSignalFWD | 75 | Relay signal used together with Run FWD signal |
| 16 | RunSignalREV | 76 | Relay signal used together with Run REV signal |
| 17 | OperationFWD | 77 | Positive speed (>0.5%), i.e. forward/ clockwise direction. |
| 18 | OperationREV | 78 | Negative speed (<0.5%), i.e. reverse counter clockwise direction. |
| 19 | ManRst Trip | 79 | Any active trip condition that needs a manual reset |
| 20 | Alarm | 80 | Alarm triggered |
| 21 | Alarm (ex LM) | 81 | Alarm triggered (except load monitor) |
| 22 | Overvolt | 90 | Overvoltage alarm active (trip or warning) |
| 23 | Com Error | 97 | Communication error active (trip or warning) |
| 24 | Com Active | 98 | Fieldbus communication active. |
| 25 | Overtemp | 101 | Softstarter overtemperature condition is active (trip) |
| 26 | PTC Alarm | 103 | PTC alarm active (trip or warning) |
| 27 | PT100 Alarm | 104 | PT100 alarm active (trip or warning) |
| 28 | I2t | 105 | I2t alarm active (trip or warning) |
| 29 | Ext Alarm 1 | 106 | Output active |
| 30 | Ext Alarm 2 | 107 | Output active |
| 31 | Option | 112 | Failure occurred in built-in option board |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 103
Manual reference: physical PDF page 103. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 54 Relay functions.
Relay 2 [552]
This menu sets the function for the relay output 2.
Relay 3 [553]
This menu sets the function for the relay output 3.
Board Relay [554] to [559]
These additional relays are only visible if an I/O option board
is fitted in slot 1 or 2. The outputs are named “B1 Relay 1” -
“B1 Relay 3” and “B2 Relay 1” - “B2 Relay 3”. “B” stands for
“board” and 1 and 2 is the number of the board which is
related to the position of the I/O option board on the option
mounting plate. The functions and selections are the same as
for “Relay 1” [551]. Default settings are “Off”.
Relay Advanced [55D]
This function makes it possible to ensure that the relay will
be closed also when the softstarter is malfunctioning or
powered down.
Relay 1 Mode [55D1]
Relay Modes [55D2] to [55DC]
Same function as for “Relay 1 Mode” [55D1]. Default
settings are “N.O”.
8.5.5
Virtual I/Os [560]
Virtual connections are used for wireless connection of a
digital output function to a digital input function. The
available signals and control functions can be used to create
your own specific functions.
In these menus you find functions to enable eight internal
connections of comparators, timers, SR flip-flops, counters,
and digital signals, without occupying physical digital inputs
or relay outputs.
NOTE: The definitions described here are valid for the
active output condition.
Bypass mode
Motor voltage
Operation
Reverse
Run
Stop time
Start time
Delay
Full voltage
current rake
NOTE: Visible only if optional board is detected or if any
input/output is activated.
55D Relay Advan
Stp
Figure54:Motorvoltage,Operation,Bypassmode,Run,Reverse current rake;all t[s]. Delay0.1s thenStarttime,Fullvoltage,Stoptime. Operationhighstartthroughstop;Bypasshighfullvoltage;Runhighstart/full;reversecurrenthighstop. Diagramillustrationnotuniversalmechanicalstopproof.
Parameter panel 55D1 Relay1 Mode; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 552 Relay 2; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 553 Relay 3; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 55D1 Relay1 Mode — PDF page 103
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | N.O |
| 2 | N.O | 0 | The normal open contact of the relay will be activated when the function is active. |
| 3 | N.C | 1 | The normally closed contact of the relay will act as a normal open contact. The contact will be opened when function is not active and closed when function is active. |
Parameter panel 552 Relay 2 — PDF page 103
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | Same selection as in menu Relay 1 [551], page 97. |
Parameter panel 553 Relay 3 — PDF page 103
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Trip |
| 2 | Selection: | Same selection as in menu Relay 1 [551], page 97. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 104
Manual reference: physical PDF page 104. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: Start delay
The motor will start in forward direction 10 seconds after
DigIn1 is activated (high). DigIn1 has a time delay of 10 s.
Virtual Connection 1 Destination [561]
With this function the destination of the virtual connection
is established. When a function can be controlled by several
sources, e.g. “VIO Destination” or “Digital Input”, the
function will be controlled in conformity with “OR logic”.
See section 8.5.2, page 94 (Digital Input) for descriptions of
the different selections.
Virtual Connection 1 Source [562]
With this function the source of the virtual connection is
defined. See "Relays [550]", page 97 for description of the
different selections.
Virtual Connections 2-8 [563] to [56G]
Same function as “Virtual Connection 1” [561] and [562].
Default settings are “Off”.
8.6
Logical Functions and
Timers [600]
In the “Logic&Timers” menu [600] you access comparators,
logic functions, SR flip-flops, timers, and counters, enabling
conditional signals to be programmed for control or
signalling features. This gives you the ability to compare
different signals and values in order to generate monitoring/
controlling features.
All these functions are updated in 8 milliseconds intervals.
8.6.1
Comparators [610]
The comparator function makes it possible to monitor
different internal signals and values, and to visualise (via
digital relay outputs) when a specific value or status is reached
or established. The output signals of the comparators can be
logically tied together to yield a logical output signal.
All the output signals can be programmed to the digital or
relay outputs or used as a source for the virtual connections
[560].
For each digital and analogue comparator it is possible to
apply a “Set Delay”, a “Reset Delay”, and a “Timer Value”;
functions that could be used to extend or delay the output
signal.
Analogue Comparator Setup [611] - [614]
There are 4 analogue comparators that compare any
available analogue value with two adjustable levels. The two
levels available are “Level HI” and “Level LO”. There are also
two analogue comparator types, selected in menu
“Comparator Type”, an analogue comparator with hysteresis
and an analogue window comparator.
The analogue hysteresis type comparator uses the two
available levels to create a hysteresis for the comparator
between setting and resetting the output. This function gives
a clear difference in switching levels, which lets the process
adapt until a certain action is started. With such a hysteresis,
even an unstable analogue signal can be monitored without
getting a nervous comparator output signal. Another feature
is the possibility to get a fixed indication that a certain level
has been passed. The comparator can latch by setting “Level
LO” to a higher value than “Level HI”.
The analogue window comparator uses the two available
levels to define the window in which the analogue value
should be within for setting the comparator output.
Digital Comparator Setup [615] - [618]
There are also 4 digital comparators that compare any
available digital signals.
NOTE: When a digital input and a virtual destination are
set to the same function, this function will act as an OR
logic function.
Example521Timer1,561RunFWD,562T1Q,6311DigIn1,6312Delay,63130:00:10. Eightinternalvirtualconnections distinguishfromphysicalrelays. Comparatorshysteresis/window distinct.
Start delay example; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 561 VIO 1 Dest; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 562 VIO 1 Source; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Start delay example — PDF page 104
| Source row | Menu | Parameter | Setting |
|---|---|---|---|
| 1 | [521] | DigIn1 | Timer 1 |
| 2 | [561] | VIO 1 Dest | Run FWD |
| 3 | [562] | VIO 1 Source | T1Q |
| 4 | [6311] | Timer1 Trig | DigIn 1 |
| 5 | [6312] | Timer1 Mode | Delay |
| 6 | [6313] | Timer1 Delay | 0:00:10 |
Parameter panel 561 VIO 1 Dest — PDF page 104
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | Same selections as in menu Digital Input 1 [521], page 94. |
Parameter panel 562 VIO 1 Source — PDF page 104
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | Same selection as in menu Relay 1 [551], page 97. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 105
Manual reference: physical PDF page 105. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Setup Analogue Comparator 1 [611]
Analogue comparator 1, parameter group.
Analogue Comparator 1, Value [6111]
Selection of the analogue value for “Analogue Comparator 1”
(CA1).
The analogue comparator compares the selectable analogue
value in menu [6111] with the constant “Level HI” in menu
[6112], and the constant “Level LO” in menu [6113].
In menu Comparator Type [6114] “Hysteresis” or
“Window” can be selected. For the hysteresis function, when
the value exceeds the upper limit level high, the output signal
CA1 is set high and !A1 low. See Fig. 55. When the value
decreases below the lower limit, the output signal CA1 is set
low and !A1 high.
Fig. 55 Analogue comparator type “Hysteresis”
For the window type comparator, when the value is between
the lower and upper levels, the output signal value CA1 is set
high and !A1 low. See Fig. 56. When the value is outside the
band of lower and upper levels, the output CA1 is set low and
!A1 high.
Fig. 56 Analogue comparator type “Window”
The output signal can be programmed as a virtual
connection source and to the relay outputs.
Example:
An analogue level sensor with current signal, 4-20 mA, is
connected to the analogue input. See table below.
When the signal on AnIn goes above 60%, the CA output
signal is activated (high), and when the signal on AnIn goes
below 40%, the CA output signal is deactivated (low) again.
The output of CA1 is used as a virtual connection source that
controls the virtual connection destination Run FWD.
CA1 Value [6111]
CA1 Level HI [6112]
CA1 Level LO [6113]
CA1
AND
Figure55 CA1Value6111,LevelHI6112,LevelLO6113 selector0/1 feedinghysteresisandCA1. Figure56high/lowcomparatorsAND→CA1. OutputCA1/!A1oppositeperprose;noelectricalwiringinferred.
Parameter panel 6111 CA1 Value; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Comparator current sensor example; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6111 CA1 Value — PDF page 105
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Current |
| 2 | Process Val | 0 | ⟦blank source cell⟧ |
| 3 | Torque | 1 | % |
| 4 | Shaft Power | 2 | kW |
| 5 | El Power | 3 | kW |
| 6 | Current | 4 | A |
| 7 | Heatsink Tmp | 5 | °C |
| 8 | PT100_1 | 6 | °C |
| 9 | PT100_2 | 7 | °C |
| 10 | PT100_3 | 8 | °C |
| 11 | Energy | 9 | kWh |
| 12 | Run Time | 10 | h |
| 13 | Mains Time | 11 | h |
| 14 | AnIn | 12 | % |
| 15 | PT100_4 | 13 | °C |
| 16 | PT100_5 | 14 | °C |
| 17 | PT100_6 | 15 | °C |
Comparator current sensor example — PDF page 105
| Source row | Menu | Function | Setting |
|---|---|---|---|
| 1 | 511 | AnIn Function | Process value |
| 2 | 512 | AnIn Setup | 4-20 mA |
| 3 | 6111 | CA1 Value | AnIn 1 |
| 4 | 6112 | CA1 Level HI | 60% (12 mA/20 mA x 100%) |
| 5 | 6113 | CA1 Level LO | 40% (8 mA/20 mA x 100%) |
| 6 | 6114 | CA1 Type | Hysteresis |
| 7 | 561 | VIO 1 Dest | Run FWD |
| 8 | 562 | VIO 1 Source | CA1 |
| 9 | 2151 | Run/Stp Ctrl | Remote |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 106
Manual reference: physical PDF page 106. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 57
Analogue Comparator 1,
Level High [6112]
Sets the analogue comparator high level, with range
according to the selected value in menu [6111].
Example
This example describes, both for hysteresis and window type
comparators, the normal use of the constant level high and
low. The function is used for temperature control. Follow the
step by step explanation in Table 27 and Table 28.
Fig. 58
t [s]
CA1 Level HI
CA1 Level LO
Reference signal AnIn
CA1
Mode
RUN
STOP
Max
Temp.
50°C
40°C
CA1 output
High
Low
Hysteresis
Window
Hysteresis/
window band
Figure57 referenceAnIn[mA],20/12/8/4,LevelHI12/LO8,t[s],events1–4;CA1andModeRUN/STOPtraces. Row1modeRUN conflictsplottedSTOP. Figure58MaxTemp50°C/40°Cband,t[s],events1–8;hysteresis/windowHigh/Lowtraces. Adjacenttable27/28governnumberedstates.
Parameter panel 6112 CA1 LevelHI; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Temperature control example; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Figure57 numbered states; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6112 CA1 LevelHI — PDF page 106
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 30.0 |
| 2 | Range: | 1=1 W, 0.1 A, 0.1 V, 1%, 0.1°C, 1 kWh, 1h, or 0.001 in [322] |
Temperature control example — PDF page 106
| Source row | Menu | Function | Setting |
|---|---|---|---|
| 1 | 325 | Process Max | Temperature: 100°C |
| 2 | 6111 | CA1 Value | PT100_1 (°C) |
| 3 | 6112 | CA1 Level HI | 50°C |
| 4 | 6113 | CA1 Level LO | 40°C |
| 5 | 6114 | CA1 Type | Window |
| 6 | 561 | VC1 Dest | Timer 1 |
| 7 | 562 | VC1 Source | CA1 |
Figure57 numbered states — PDF page 106
| Source row | No. | Description |
|---|---|---|
| 1 | 1 | The reference signal passes the Level LO value from below (positive edge), the comparator CA1 output stays low, mode = RUN. |
| 2 | 2 | The reference signal passes the Level HI value from below (positive edge), the comparator CA1 output is set high, mode = RUN. |
| 3 | 3 | The reference signal passes the Level HI value from above (negative edge), the comparator CA1 output stays high, mode = RUN. |
| 4 | 4 | The reference signal passes the Level LO value from above (negative edge), the comparator CA1 output = STOP. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 107
Manual reference: physical PDF page 107. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 27
Comments to Fig. 58 regarding “Hysteresis”
selection.
Table 28
Comments to Fig. 58 regarding “Window”
Table27 Hysteresis columnrow1–8 graphics:horizontalstroke,up,stroke,down,stroke,up,stroke,down. Table28Windowrow1–8:up,down,up,down,up,down,up,down. Nativeemptycells mappedtoexplicitgraphics,notemptydata.
Table27 hysteresis states; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Table28 window states; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Table27 hysteresis states — PDF page 107
| Source row | No. | Description | Hysteresis |
|---|---|---|---|
| 1 | 1 | The reference signal passes the Level LO value from below (positive edge), the comparator CA1 does not change, output stays low. |
⟦blank source cell⟧ |
| 2 | 2 | The reference signal passes the Level HI value from below (positive edge), the comparator CA1 output is set high. |
⟦blank source cell⟧ |
| 3 | 3 | The reference signal passes the Level HI value from above (negative edge), the comparator CA1 does not change, output stays high. |
⟦blank source cell⟧ |
| 4 | 4 | The reference signal passes the Level LO value from above (negative edge), the comparator CA1 is reset, output is set low. |
⟦blank source cell⟧ |
| 5 | 5 | The reference signal passes the Level LO value from below (positive edge), the comparator CA1 does not change, output stays low. |
⟦blank source cell⟧ |
| 6 | 6 | The reference signal passes the Level HI value from below (positive edge), the comparator CA1 output is set high. |
⟦blank source cell⟧ |
| 7 | 7 | The reference signal passes the Level HI value from above (negative edge), the comparator CA1 does not change, output stays high. |
⟦blank source cell⟧ |
| 8 | 8 | The reference signal passes the Level LO value from above (negative edge), the comparator CA1 is reset, output is set low. |
⟦blank source cell⟧ |
Table28 window states — PDF page 107
| Source row | No. | Description | Window |
|---|---|---|---|
| 1 | 1 | The reference signal passes the Level LO value from below (signal inside Window band), the comparator CA1 output is set high. |
⟦blank source cell⟧ |
| 2 | 2 | The reference signal passes the Level LO value from above (signal outside Window band), the comparator CA1 is reset, output is set low. |
⟦blank source cell⟧ |
| 3 | 3 | The reference signal passes the Level HI value from above (signal inside Window band), the comparator CA1 output is set high. |
⟦blank source cell⟧ |
| 4 | 4 | The reference signal passes the Level LO value from above (signal outside Window band), the comparator CA1 is reset, output is set low. |
⟦blank source cell⟧ |
| 5 | 5 | The reference signal passes the Level LO value from below (signal inside Window band), the comparator CA1 output is set high. |
⟦blank source cell⟧ |
| 6 | 6 | The reference signal passes the Level HI value from below (signal outside Window band),the comparator CA1 is reset, output is set low. |
⟦blank source cell⟧ |
| 7 | 7 | The reference signal passes the Level HI value from above (signal inside Window band), the comparator CA1 output is set high. |
⟦blank source cell⟧ |
| 8 | 8 | The reference signal passes the Level LO value from above (signal outside Window band), the comparator CA1 is reset, output is set low. |
⟦blank source cell⟧ |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 108
Manual reference: physical PDF page 108. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Analogue Comparator 1
Level Low [6113]
Sets the analogue comparator low level, with unit and range
according to the selected value in menu [6111].
Analogue Comparator 1 Type [6114]
Selects the analogue comparator type, i.e. hysteresis or
window type. See Fig. 55 and Fig. 56, page 101.
Analogue Comparator 1 Set Delay
[6116]
The output signal for the analogue comparator 1 is delayed
with the set value in this menu. See Fig. 59.
Fig. 59 Set/reset delay of output signal.
Analogue Comparator 1 Reset Delay
[6117]
The reset of the output signal for the analogue comparator 1
is delayed with the set time in this menu. See Fig. 59..
Analogue Comparator 1 Timer Value
[6118]
The actual timer value for analogue comparator 1 is viewed
in this menu.
Setup Analogue comparators 1 - 4
[612] - [614]
Refer to the descriptions for analogue comparator 1.
Setup Digital Comparator 1 [615]
Digital comparators, parameter group.
Digital Comparator 1 Input
[6151]page 120
Selection of the input signal for digital comparator 1 (CD1).
The output signal CD1 is set high if the selected input
signal is active. See Fig. 60.
The output signal can be programmed to the relay outputs or
used as a source for the virtual connections [560].
Set delay
Reset delay
Figure59 originalpulse anddelayedoutput withSetdelay/Resetdelayarrows;no numericaldelaydrawn.6151CD1defaultOperation.6118actualtimerdisplaydistinctfromset/resetvalues.
Parameter panel 6113 CA1 LevelLO; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6117 CA1 Res Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6114 CA1 Type; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6118 CA1 Tmr Val; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6116 CA1 Set Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6151 CD1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6113 CA1 LevelLO — PDF page 108
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 20.0 |
| 2 | Range: | See [6112]. |
Parameter panel 6117 CA1 Res Dly — PDF page 108
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Parameter panel 6114 CA1 Type — PDF page 108
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦blank source cell⟧ | Hysteresis |
| 2 | Hysteresis | 0 | Hysteresis type comparator |
| 3 | Window | 1 | Window type comparator |
Parameter panel 6151 CD1 — PDF page 108
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Operation |
| 2 | Selection: | Same selection as in menu Relay 1 [551], page 97. |
Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 109
Manual reference: physical PDF page 109. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 60 Digital comparator.
Digital Comparator 1 Set Delay [6152]
The activation of the output signal for the digital comparator
1 is delayed with the set value in this menu. See also Fig. 59,
page 104.
Digital Comparator 1 Reset Delay
[6153]
The reset of the output signal for the digital comparator 1 is
delayed with the set value in this menu. See also Fig. 59, page
104.
Digital Comparator 1 Timer Value
[6154]
The actual timer value for digital comparator 1 is viewed in
this menu.
Setup Digital Comparators 2 - 4 [616]-
[618]
Refer to the description of Digital Comparator 1. Default for
CD2 [6161] is “DigIn 1”. For CD3 [6171] the default is
“Trip”, and for CD4 [6181] the default is “Ready”.
8.6.2
Logic outputs [620]
Logic 1 [621]
By means of an expression editor, the input signals can be
logically combined into the logics function to create a logic
output signal.
The expression editor has the following features:
•
The following input signals can be used:
CA1-CA4, CD1-CD4, L1-L4, T1Q-T4Q, F1-F4, and
CTR1-CTR2.
The following inverted input signals can be used:
!A1-!A4, !D1-!D4, !L1- !L4, !T1Q-!T4Q, !F1-!F4, and
!CTR1-!CTR2.
The following logical operators are available:
"+" : OR operator
"&" : AND operator
"^" : EXOR operator
Expressions according to the following truth table can be
made (see also the example below):
The output signal can be programmed to the relay outputs or
used as a virtual connection source [560].
The logic expression must be programmed by means of the
menus [6211] to [621B], and its actual appearance can be
viewed in menu [621], with example below:
Input signal for CD1 [6151]
Digital comparator 1
CD1
Read-only
621 Logic 1
Stp
((1&2)&3)&4
Figure60 inputsignal6151→Digitalcomparator1→CD1;symbol+/−. Logic621readonlyexample((1&2)&3)&4;truth tableA/Binputs andAND/OR/EXORoutputs. No configurationsbeyondthispage inferred.
Parameter panel 6152 CD1 Set Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Logic truth table; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6153 CD1 Res Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6154 CD1 Tmr Val; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.
Parameter panel 6152 CD1 Set Dly — PDF page 109
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Logic truth table — PDF page 109
| Source row | A | B | & (AND) | + (OR) | ^(EXOR) |
|---|---|---|---|---|---|
| 1 | 0 | 0 | 0 | 0 | 0 |
| 2 | 0 | 1 | 0 | 1 | 1 |
| 3 | 1 | 0 | 0 | 1 | 1 |
| 4 | 1 | 1 | 1 | 1 | 0 |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 110
Manual reference: physical PDF page 110. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Logic 1 Expression [6211]
Selection of execution order of the logic expression for the
Logic 1 function:
•
Parentheses ( ) show the order in which the Logic 1
Inputs are combined, according to [6211].
1, 2, 3, and 4, represent the Logic 1 Input signals
selected in menu [6212], [6214], [6216], and [6218].
The dots stand for the Logic 1 Operators (&, +, or ^),
whose values are selected in menus [6213], [6215], and
[6217].
To build the Logic 1 expression using the default selection in
menu [6211], the execution order is as follows:
-
Input 1 is combined with Input 2 using Operator 1.
-
Input 3 is combined with the expression (1.2), using
Operator 2.
- Input 4 is combined with the result of (1.2).3, using
Operator 3.
The alternative execution order leads to:
-
Input 3 is combined with Input 4 using Operator 3.
-
Expression (1.2) is combined with expression (3.4),
using Operator 2.
Example:
Input 1 = CA1, set in menu [6212]
Input 2 = F1, menu [6214]
Input 3 = T1Q, menu [6216]
Input 4 = !A2, menu [6218]
Operator 1 = & (AND), set in menu [6213]
Operator 2 = + (OR), menu [6215]
Operator 3 = & (AND), menu [6217]
The following expression is created, using the menus above:
CA1&F1+T1Q&!A2
With the default setting for L1 Expression this is viewed in
[621] as:
representing:
((CA1&F1)+T1Q)&!A2
Let’s use the following values on the input signals as an
example:
CA1=1 (active/high)
F1= 1 (active/high)
T1Q = 1 (active/high)
!A2 = 0 (inactive/low)
With the respective values inserted the resulting logic
expression is:
((1&1)+1)&0
which is equal to 0.
With the alternative execution order for the L1 Expression
the expression is viewed in [621] as:
(CA1&F1)+(T1Q&!A2)
With the above values inserted the resulting logic expression
now becomes:
(1&1)+(1&0)
which is equal to 1.
621 Logic 1
Stp
((1&2)+3)&4
(1&2)+(3&4)
The LCD examples show ((1&2)+3)&4 and (1&2)+(3&4). The black A badge denotes the displayed parameter set; it is separate from the logic input labels.
Parameter panel 6211 L1 Expr; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 6211 L1 Expr — PDF page 110
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | ((1.2).3).4 |
| 2 | ((1.2).3).4 | 0 | Default execution order, see explanation below. |
| 3 | (1.2).(3.4) | 1 | Alternative execution order, see explanation below. |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 111
Manual reference: physical PDF page 111. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Logic 1 Input 1 [6212]
In this menu the first input for the Logic 1 function is
selected. The same selections are valid for [6214] L1 Input 2,
[6216] L1 Input 3, and [6218] L1 Input 4.
This table is also valid for the input signals in logic functions
2 [622], 3 [623], and 4 [624], however default values vary.
See Menu List in Appendix 1.
Note that a logic function can not directly use itself as an
input signal, e.g. for the L1 Input, it will not be possible to
choose L1 or !L1.
Logic 1 Operator 1 [6213]
In this menu the first operator for the Logic 1 function is
selected.
Logic 1 Input 2 [6214]
In this menu the second input for the Logic 1 function is
6212 source sequence: code0 CA1,1 !A1,2 CA2,3 !A2,4 CA1,5 !A1,6 CA2,7 !A2. Descriptions for4/5 refer comparator3 and6/7 comparator4. Continuation at upper right startsT2Q26 and ends!CTR243; no row omitted.
Logic6212 continuation; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6212 L1 Input 1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 6213 L1 Op 1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6214 L1 Input 2; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Logic6212 continuation — PDF page 111
| Source row | Input signal | Communication code | Description |
|---|---|---|---|
| 1 | T2Q | 26 | Logic timer 2 output |
| 2 | !T2Q | 27 | Inverted logic timer 2 output |
| 3 | T3Q | 28 | Logic timer 3 output |
| 4 | !T3Q | 29 | Inverted logic timer 3 output |
| 5 | T4Q | 30 | Logic timer 4 output |
| 6 | !T4Q | 31 | Inverted logic timer 4 output |
| 7 | F1 | 32 | Flip-flop output 1. |
| 8 | !F1 | 33 | Flip-flop output 1 inverted. |
| 9 | F2 | 34 | Flip-flop output 2. |
| 10 | !F2 | 35 | Flip-flop output 2 inverted. |
| 11 | F3 | 36 | Flip-flop output 3. |
| 12 | !F3 | 37 | Flip-flop output 3 inverted. |
| 13 | F4 | 38 | Flip-flop output 4. |
| 14 | !F4 | 39 | Flip-flop output 4 inverted. |
| 15 | CTR1 | 40 | Counter output 1. |
| 16 | !CTR1 | 41 | Counter output 1 inverted. |
| 17 | CTR2 | 42 | Counter 2 output. |
| 18 | !CTR2 | 43 | Counter output 2 inverted. |
Parameter panel 6212 L1 Input 1 — PDF page 111
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | CA1 |
| 2 | CA1 | 0 | Analogue comparator 1 output. |
| 3 | !A1 | 1 | Analogue comp 1 inverted output. |
| 4 | CA2 | 2 | Analogue comparator 2 output. |
| 5 | !A2 | 3 | Analogue comp 2 inverted output. |
| 6 | CA1 | 4 | Analogue comparator 3 output. |
| 7 | !A1 | 5 | Analogue comp 3 inverted output. |
| 8 | CA2 | 6 | Analogue comparator 4 output. |
| 9 | !A2 | 7 | Analogue comp 4 inverted output. |
| 10 | CD1 | 8 | Digital comparator 1 output. |
| 11 | !D1 | 9 | Digital comp 1 inverted output. |
| 12 | CD2 | 10 | Digital comparator 2 output. |
| 13 | !D2 | 11 | Digital comp 2 inverted output. |
| 14 | CD3 | 12 | Digital comparator 3 output. |
| 15 | !D3 | 13 | Digital comp 3 inverted output. |
| 16 | CD4 | 14 | Digital comparator 4 output. |
| 17 | !D4 | 15 | Digital comp 4 inverted output. |
| 18 | L1 | 16 | Logic output 1. Not used for Logic 1. |
| 19 | !L1 | 17 | Logic output 1 inverted. Not used for Logic 1. |
| 20 | L2 | 18 | Logic output 2. Not used for Logic 2. |
| 21 | !L2 | 19 | Logic output 2 inverted. Not used for Logic 2. |
| 22 | L3 | 20 | Logic output 3. Not used for Logic 3. |
| 23 | !L3 | 21 | Logic output 3 inverted. Not used for Logic 3. |
| 24 | L4 | 22 | Logic output 4. Not used for Logic 4. |
| 25 | !L4 | 23 | Logic output 4 inverted. Not used for Logic 4. |
| 26 | T1Q | 24 | Logic timer 1 output |
| 27 | !T1Q | 25 | Inverted logic timer 1 output |
Parameter panel 6213 L1 Op 1 — PDF page 111
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | & |
| 2 | · | 0 | When · (dot) is selected, the Logic 1 expression is finished (when two or three expressions are tied together). |
| 3 | & | 1 | &=AND |
| 4 | + | 2 | +=OR |
| 5 | ^ | 3 | ^=EXOR |
Parameter panel 6214 L1 Input 2 — PDF page 111
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | !A2 |
| 2 | Selection: | Same selection as in menu Logic 1 Input 1 [6212], page 107. |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 112
Manual reference: physical PDF page 112. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Logic 1 Operator 2 [6215]
In this menu the second operator for the Logic 1 function is
selected.
Logic 1 Input 3 [6216]
In this menu the third input for the Logic 1 function is
Logic 1 Operator 3 [6217]
In this menu the third operator for the Logic 1 function is
Logic 1 Input 4 [6218]
In this menu the fourth input for the Logic 1 function is
Logic 1 Set Delay [6219]
The activation of the output signal for the Logic 1 function
is delayed with the set value in this menu. Compare to Fig.
59, page 104.
Logic 1 Reset Delay [621A]
The reset of the output signal for the Logic 1 function is
delayed with the set value in this menu. Compare to Fig. 59,
page 104.
Logic 1 Timer Value [621B]
The actual timer value for logic 1 is viewed in this menu.
Logic 2 - 4 [622] - [624]
Refer to the descriptions for Logic 1. For default values see
Menu List in Appendix 1.
Parameter panel 6215 L1 Op 2; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 6218 L1 Input 4; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6219 L1 Set Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6216 L1 Input 3; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 621A L1 Res Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6217 L1 Op 3; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 621B L1 Tmr Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6215 L1 Op 2 — PDF page 112
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | & |
| 2 | · | 0 | When · (dot) is selected, the Logic 1 expression is finished (when two or three expressions are tied together). |
| 3 | & | 1 | &=AND |
| 4 | + | 2 | +=OR |
| 5 | ^ | 3 | ^=EXOR |
Parameter panel 6218 L1 Input 4 — PDF page 112
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | CA4 |
| 2 | Selection: | Same selection as in menu Logic 1 Input 1 [6212], page 107. |
Parameter panel 6219 L1 Set Dly — PDF page 112
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Parameter panel 6216 L1 Input 3 — PDF page 112
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | CA3 |
| 2 | Selection: | Same selection as in menu Logic 1 Input 1 [6212], page 107. |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 113
Manual reference: physical PDF page 113. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.6.3
Timers [630]
The timer function can be used as a delay timer, as an interval
timer with separate “on” and “off “ times (alternate mode), or
as a way to prolong a signal (on-time mode). The selected
trigger signal starts the timer function, and the signal is
converted according to the mode settings, resulting in the
timer output signal (T1Q - T4Q).
In “Delay” mode, the activation of the timer output signal
will be delayed in comparison to the trigger signal. The timer
output signal is activated (high) when the set delay time has
expired. See Fig. 61. The timer output signal will however
follow the trigger signal when this is deactivated (low) again.
Fig. 61 Delay timer mode.
In “Alternate” mode, the timer output signal will switch
automatically between high (Timer T1) and low (Timer T2),
according to set interval times. See Fig. 62. When the trigger
signal is deactivated (low) again, the timer output signal will
also be deactivated (low).
Fig. 62 Alternate timer mode.
The function of the “On-time” mode is to extend an
activated (high) timer output signal in comparison to the
trigger signal. See Fig. 63.
Fig. 63 On-time timer mode.
The timer output signals (T1Q - T4Q) can be programmed
to the relay outputs used in logic functions [620], or be used
as a virtual connection source [560].
Timer 1 [631]
Parameter group for Timer 1.
Timer 1 Trigger [6311]
Selection of the trigger signal for the timer function.
Timer 1 Mode [6312]
Selection of the conversion of the trigger signal, according to
the descriptions in Fig. 61 - Fig. 63.
Timer 1 Delay [6313]
This menu is only visible when “Timer Mode “[6312] is set
to “Delay”. When Timer 1 is triggered in menu [6311], the
set value in this menu will delay the activation of the Timer
1 output signal, T1Q.
Timer1 Trig
T1Q
Timer 1 Delay
Timer T2
Timer T1 Timer T2 Timer T1
Timer T1
NOTE: The actual timers are common for all parameter
sets. If the actual parameter set is changed, the timer
functionality will change according to the settings, but
the timer value will stay unchanged. So initialisation of
the timer might differ for a set change compared to
normal triggering of a timer.
Fig61 Timer1 Trig andT1Q: output rising edge delayed byTimer1Delay; fallingedges align. Fig62 alternating T2-low/T1-high intervals. Fig63 shorttriggerpulse leads T1Q highforTimerT1. Graphs are qualitative, withoutscalevalues.
Parameter panel 6311 Timer1 Trig; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6312 Timer1 Mode; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 6313 Timer1 Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6311 Timer1 Trig — PDF page 113
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | Same selections as in menu Relay 1 [551], page 97. |
Parameter panel 6312 Timer1 Mode — PDF page 113
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Delay |
| 2 | Off | 0 | Timer off. |
| 3 | Delay | 1 | Delays the activation of the output signal according to menu [6313]. |
| 4 | Alternate | 2 | Interval timer for output signal according to menus [6314] and [6315]. |
| 5 | On-time | 3 | Prolongs the activation of the output signal according to menu [6314]. |
Parameter panel 6313 Timer1 Dly — PDF page 113
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 114
Manual reference: physical PDF page 114. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Timer 1 T1 [6314]
This menu sets the “on” time for the “Alternate” and “On-
time” modes in menu [6312] (only visible when one of these
two modes has been selected).
If “Alternate” mode is selected and Timer 1 is triggered on
signal set up in [6311], the timer will automatically keep
switching from the “on” time ([6314] “Timer 1 T1”) to the
“off” time ([6315]”Timer 1 T2”). Hence the output signal
T1Q will alternate between active, “on”, and inactive, “off”.
See Fig. 62.
If “On-time” mode is selected in [6312] and Timer 1 is
triggered in [6311], the timer will extend the activation (“on”
time) of the output signal T1Q to the set value in
[6314]“Timer 1 T1”. See Fig. 63.
Timer 1 T2 [6315]
In this menu the “off” time in the “Alternate” mode is set.
Timer 1 Value [6316]
This menu shows the actual value of the timer.
Timer 2 - 4 [632] - [634]
Refer to the descriptions for Timer 1.
8.6.4
SR Flip-flops [640]
The flip-flop function is a memory circuit that can be used to
store data concerning state. The output from a flip-flop is
dependent not only on its current input, but also on its state
at the moment this is received (hence previous input status
also matters).
The set/reset flip-flop circuit has two input signals, SET and
RESET, that control the state of an output signal, OUT. The
flip-flop will only change output value when the input signal
is at a positive edge.
When none of the input signals are active (i.e. both are =0),
the output signal is consequently inactive (=0). In this case
the flip-flop will keep its current value.
When only one of the input signals is active (=1), this will
directly decide the status of the output signal. Consequently
if SET=1 (active) and RESET=0 (inactive), the SET
command is given to the output signal, OUT. This will result
in a signal change from inactive to active (=1), if not already
in an active state.
Conversely, if SET=0 (inactive) and RESET=1 (active), the
RESET command is given to the output signal, OUT,
causing this to be deactivated (=0).
Flip-flop priority mode
When both input signals are in an active state simultaneously,
i.e. SET=1 and RESET=1, a priority function decides which
signal will influence the output signal. There are three
different priority settings available for the flip-flop function,
selected in the menu for “Flip-flop Mode”. Examples of the
different priority settings are presented in Fig. 64.
Fig. 64 Programmable flip-flop modes.
RESET
SET
OUT
Reset priority
Set priority
Edge controlled without priority
Fig64 shows three separate timing diagrams labelled Reset priority, Set priority, Edge controlled without priority. Each has SET,RESET,OUT traces; no numeric time scale.
Parameter panel 6314 Timer1 T1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6315 Timer1 T2; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6316 Timer1 Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6314 Timer1 T1 — PDF page 114
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 115
Manual reference: physical PDF page 115. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Reset priority
“Reset priority” means that if both input signals are active, it
will be the RESET command that is obeyed, causing the
output signal to become inactive (=0). See Table 29.
Set priority
For “Set priority” the determining input signal is SET should
both input signals be active, resulting in an activated (=1)
output signal. See Table 30.
Edge controlled without priority
The third setting is “Edge controlled”, for which no input
signal has priority over the other. The output signal follows
any of the two input signals (still providing they are at a
positive edge). The most recent registered activity decides the
output. See Table 31.
Should both inputs become activated simultaneously, there
will not be any change; the output signal will just keep its
earlier status.
Flip-flop 1 [641]
Functions for SR flip-flop 1.
Flip-flop 1 Mode [6411]
Priority setting of input signals for flip-flop 1.
Flip-flop 1 Set [6412]
Selection of SET input signal for flip-flop 1.
Flip-flop 1 Reset [6413]
Selection of RESET input signal for flip-flop 1.
Flip-flop 1 Set Delay [6414]
The SET input signal for flip-flop 1 is delayed with the set
value in this menu.
Table 29
Truth table for Reset priority
Table 30
Truth table for Set priority
Table 31
Truth table for Edge control without priority
Table31 rising-edge glyph ↗ appears before1 in SETrow2, RESETrow3 and bothSET/RESETrow4; row2otherinput0/1,OUT1(set);row3otherinput0/1,OUT0(reset);row4OUTNochange. Raw private-use arrowglyph preserved in tablecells.
Table29 reset priority truth table; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6411 F1 Mode; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 6412 F1 Set; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Table30 set priority truth table; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6413 F1 Reset; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Table31 edge control truth table; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6414 F1 Set Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Table29 reset priority truth table — PDF page 115
| Source row | SET | RESET | OUT |
|---|---|---|---|
| 1 | 0 | 0 | 0 (reset) |
| 2 | 0 | 1 | 0 (reset) |
| 3 | 1 | 0 | 1 (set) |
| 4 | 1 | 1 | 0 (reset) |
Parameter panel 6411 F1 Mode — PDF page 115
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | Reset |
| 2 | Reset | 0 | Reset priority. |
| 3 | Set | 1 | Set priority. |
| 4 | Edge | 2 | Edge controlled without priority. |
Parameter panel 6412 F1 Set — PDF page 115
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | Same selections as in menu Relay 1 [551], page 97. |
Table30 set priority truth table — PDF page 115
| Source row | SET | RESET | OUT |
|---|---|---|---|
| 1 | 0 | 0 | 0 (reset) |
| 2 | 0 | 1 | 0 (reset) |
| 3 | 1 | 0 | 1 (set) |
| 4 | 1 | 1 | 1 (set) |
Table31 edge control truth table — PDF page 115
| Source row | SET | RESET | OUT |
|---|---|---|---|
| 1 | 0 | 0 | 0 (reset) |
| 2 | ↗ 1 |
0/1 | 1 (set) |
| 3 | 0/1 | ↗ 1 |
0 (reset) |
| 4 | ↗ 1 |
↗ 1 |
No change |
Parameter panel 6414 F1 Set Dly — PDF page 115
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 116
Manual reference: physical PDF page 116. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Flip-flop 1 Reset Delay [6415]
The RESET input signal for Flip-flop 1 is delayed with the
set value in this menu.
Flip-flop 1 Timer Value [6416]
This menu shows the actual value of the flip-flop 1 timer.
Flip-flop 2 - 4 [642] - [644]
Refer to the descriptions for flip-flop 1. Default for
[6421]”F2 Mode” is “Reset”. For [6431]”F3 Mode” the
default is “Set”, and for [6441] “F4 Mode” the default is
“Edge”.
8.6.5
Counters [650]
The counter function counts pulses and can signal on a
selected output when the counter reaches a specified level.
The counter counts up on the positive edges of the trigger
signal, and it is zeroed when the reset signal is active.
When the counter value equals the trip value, the counter
output signal (CTR1 or CTR2) is activated. See Fig. 65.
Fig. 65 Counters, principle.
Counter 1 [651]
Counter 1 parameter group.
Counter 1 Trigger [6511]
The selected signal is used as a trigger signal for counter 1.
Counter 1 is incremented by 1 on every positive edge of the
trigger signal.
NOTE: Maximum counting frequency is 8 Hz.
CTR1
CTR1= Counter 1 output signal
6511= Counter 1 Trigger
6512= Counter 1 Reset
6513= Counter 1 Trip Value
6519= Counter 1 Value
651 Counter 1
Stp
Fig65 printed waveform labels6513threshold,6519count,6511trigger,6512reset,CTR1output. Legend literally6519=Counter1Value; next page displays6514. No reference corrected.
Parameter panel 6415 F1 Res Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6416 F1 Tmr Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6511 C1 Trig; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6415 F1 Res Dly — PDF page 116
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Parameter panel 6511 C1 Trig — PDF page 116
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | Same selections as in menu Relay 1 [551], page 97. |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 117
Manual reference: physical PDF page 117. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Counter 1 Reset [6512]
The selected signal is used as a reset signal for counter 1.
When the reset signal is activated (high), this will zero
counter 1, and the counter will remain at zero as long as the
reset signal is active (high).
Counter 1 Trip Value [6513]
In this menu counter 1 is set to a trip value. When the
counter value equals the trip value, the counter 1 output
signal (CTR1) is activated (high).
Counter 1 Value [6514]
This menu shows the actual value of counter 1.
Counter 2 [652]
Refer to description for Counter 1 [651].
8.6.6
Clock Logic [660]
Clock 1 [661]
The actual value of clock 1 is viewed in this menu.
Clock 1 Time On [6611]
Time when the clock is activated.
Clock 1 Time Off [6612]
Time when the clock is deactivated.
Clock 1 Date On [6613]
Date when the clock is activated.
Clock 1 Date Off [6614]
Date when the clock is deactivated. Note that if
“Clk1DateOff” is set to an earlier date than “Clk1DateOn”,
the result will be that the clock is not deactivated at the set
date.
NOTE: Reset input has top priority.
NOTE: Value 0 means that counter output is always high.
NOTE: Counter 1 value is common for all parameter sets.
NOTE: The value is lost at power down.
Clock1 actual661 source body has separate Range label and0:00:00.0(hours:minutes:seconds) value; no numeric upperbound isprinted. Counter6514readonly;On/Off6611/6612 ranges are not rewritten.
Parameter panel Read-only 661 Clock 1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6512 C1 Reset; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6611 Clk1TimeOn; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6513 C1 Trip Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6612 Clk1TimeOff; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6613 Clk1DateOn; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6514 C1 Value; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6614 Clk1DateOff; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel Read-only 661 Clock 1 — PDF page 117
| Source row | Label | Value |
|---|---|---|
| 1 | Range: | 0:00:00.0 (hours:minutes:seconds) |
Parameter panel 6512 C1 Reset — PDF page 117
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | Off |
| 2 | Selection: | Same selections as in menu Relay 1 [551], page 97. |
Parameter panel 6611 Clk1TimeOn — PDF page 117
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0:00:00.0 (hours:minutes:seconds) |
| 2 | Range: | 0:00:00.0–9:59:59.9 |
Parameter panel 6513 C1 Trip Val — PDF page 117
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 0 |
| 2 | Range: | 0 - 10,000 |
Parameter panel 6613 Clk1DateOn — PDF page 117
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 2013-01-01 |
| 2 | Range: | YYYY-MM-DD (year-month-day) |
Parameter panel 6614 Clk1DateOff — PDF page 117
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | 2013-01-01 |
| 2 | Range: | YYYY-MM-DD |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 118
Manual reference: physical PDF page 118. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Clock 1 Weekday [6615]
Weekdays when the clock function is active. Having entered
the editing mode, select or unselect the desired weekdays
with the cursor using the PREV and NEXT keys on the
control panel. Confirm by pressing ENTER. Exit the editing
mode and the activated weekdays will be viewed in the menu
display. The deactivated weekdays are replaced by a dash
mark “-” (e.g. “MTWTF - -”).
Clock 2 [662]
Refer to the description for Clock 1 [661].
8.7
Operation/Status [700]
Menu with parameters for viewing all actual operational data,
such as speed, torque, power, etc.
8.7.1
Operation values [710]
Process Value [711]
This menu displays the actual value of the active process
signal, i.e. the same value as in menu [310].
Torque [713]-[714]
This menu displays the actual shaft torque, expressed with
different units in the two menus:
Shaft power [715]- [716]
This menu displays the actual shaft power, expressed with
NOTE: Please make sure that the correct time and date
settings are done for the real time clock, menu group
[740] “Clock”.
6615 Default MTWTFSS(allactivated),Range Monday throughSunday. Deactivated weekdays use dash, e.g.MTWTF--.713 and715 units are absolute Nm/W;714 and716 arepercent.
Parameter panel 6615 Clk1Weekday; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 711 Process Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 713 Torque; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 714 Torque; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 715 Shaft Power; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 716 Shaft Power; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 6615 Clk1Weekday — PDF page 118
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | MTWTFSS (all activated) |
| 2 | Range: | Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday. |
Parameter panel 711 Process Val — PDF page 118
| Source row | Label | Value |
|---|---|---|
| 1 | Unit | Depends on selected process unit [322]. |
| 2 | Resolution | Speed: 1 rpm, 4 digits Other units: 3 digits |
Parameter panel 713 Torque — PDF page 118
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | Nm |
| 2 | Resolution: | 0.1 Nm |
Parameter panel 714 Torque — PDF page 118
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | % |
| 2 | Resolution: | 1 % |
Parameter panel 715 Shaft Power — PDF page 118
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | W |
| 2 | Resolution: | 1W |
Parameter panel 716 Shaft Power — PDF page 118
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | % |
| 2 | Resolution: | 1% |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 119
Manual reference: physical PDF page 119. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Electrical Power [717]
This menu displays the actual electrical output power.
RMS Current [718]
This menu displays the RMS value of the output current.
Line Main Voltage [719]
This menu displays the RMS value of the mains voltage.
Heatsink Temperature [71A]
This menu displays the actual measured heatsink
temperature.
PT100B1 123 [71B]
This menu displays the actual PT100 temperature for the
first PT100 option board (B1), corresponding to input 1, 2,
and 3. See menu PT100 Inputs [2323], page 64.
PT100B2 123 [71C]
second PT100 option board (B2), corresponding to input 4,
5, and 6. See menu PT100 Inputs [2323], page 64.
Current I1- I3 [71D]-[71F]
This menu displays the actual output current in the three
phases.
L12, L13 and L23 Voltage [71G]-[71I]
This menu displays the actual voltage.
Phase Sequence [71J]
This menu displays the phase sequence of the mains voltage.
Used Thermal Capacity [71K]
This menu displays the used thermal capacity.
PT100B2 123 LCD label belongs to secondboard71C;prose saysinputs4,5,6. PhaseSequence71J Range valuecell and descriptioncellsL123/L321 are blank; displayedL123 is example status.
Parameter panel 717 El Power; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 71C PT100B2 123; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 718 RMS Current; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 71D Current I1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 719 L Main Volt; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 71G L12 Voltage; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 71A Heatsink Tmp; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 71J Phase Seq; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 71B PT100B1 123; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 71K Used Th Cap; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 717 El Power — PDF page 119
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | kW |
| 2 | Resolution: | 1 W |
Parameter panel 71C PT100B2 123 — PDF page 119
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | °C |
| 2 | Resolution: | 1°C |
Parameter panel 718 RMS Current — PDF page 119
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | A |
| 2 | Resolution: | 0.1 A |
Parameter panel 719 L Main Volt — PDF page 119
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | V |
| 2 | Resolution: | 1 V |
Parameter panel 71A Heatsink Tmp — PDF page 119
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | °C |
| 2 | Resolution: | 0.1°C |
Parameter panel 71J Phase Seq — PDF page 119
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Range: | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 2 | L - - - | 0 | Can not be detected. |
| 3 | L123 | 1 | ⟦blank source cell⟧ |
| 4 | L321 | 2 | ⟦blank source cell⟧ |
Parameter panel 71K Used Th Cap — PDF page 119
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | % |
| 2 | Resolution: | 1% |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 120
Manual reference: physical PDF page 120. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.7.2
Status [720]
TSA Status [721]
This menu indicates the overall status of the softstarter.
Fig. 66 Softstarter status
Integer values and bits used:
Example: “A/- - - /Key”
This means:
A:
Parameter Set A is active.
---:
Operation is stopped.
Key:
Run/Stop command source is both internal and
external keyboard (in this example bit 7-5 → 1).
Integer interpretation for “A/---/Key” is “0/0/1”.
In bit format this is presented as:
Warning [722]
This menu displays the actual or last warning condition. A
warning occurs if the softstarter is close to a trip condition
but still in operation. During a warning condition the red
trip LED will flash, as long as the warning is active.
The active warning message is displayed in menu [722]. If no
warning is active the message “No Error” is displayed.
The following warning or trip messages are possible:
Read-only
721 TSA Status
Stp
1/222/333
Warning
(warning message)
Figure66 bit-number columns7,6,5,4,3,2,1,0LSB hold0,0,1,0,0,0,0,0. Group7–5Key(1),4–2stopped(0),1–0A(0). Mergedgroupcells retained without copying values into blank/null placeholders.
Figure66 bit-format example; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
-
row 2, column 2, row 2, column 3 share the source cell at row 2, column 1. Read its current text above; the child slots remain unpopulated.
-
row 2, column 5, row 2, column 6 share the source cell at row 2, column 4. Read its current text above; the child slots remain unpopulated.
-
row 2, column 8 share the source cell at row 2, column 7. Read its current text above; the child slots remain unpopulated.
-
row 3, column 2, row 3, column 3 share the source cell at row 3, column 1. Read its current text above; the child slots remain unpopulated.
-
row 3, column 5, row 3, column 6 share the source cell at row 3, column 4. Read its current text above; the child slots remain unpopulated.
-
row 3, column 8 share the source cell at row 3, column 7. Read its current text above; the child slots remain unpopulated.
TSA721 status display positions; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
TSA721 status bit assignments; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Figure66 bit-format example — PDF page 120
| Source row | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 LSB |
|---|---|---|---|---|---|---|---|---|
| 1 | 0 | 0 | 1 | 0 | 0 | 0 | 0 | 0 |
| 2 | Key (1) | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | - - - (0) | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | A (0) | ⟦null: no independent source value⟧ |
| 3 | Source of Run/Stop command = Int + Ext keyboard (1) |
⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Operation = Stopped (0) |
⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Parameter Set= A (0) |
⟦null: no independent source value⟧ |
TSA721 status display positions — PDF page 120
| Source row | Display position |
Function | Status value |
|---|---|---|---|
| 1 | 1 | Parameter Set | A, B, C, D |
| 2 | 222 | Operation | - - - (stopped) -Thy (ramp/brake with thyristors) -Bpy (full speed reached, running with bypass enabled) |
| 3 | 333 | Source of Run/ Stop command |
-Rem (remote) -Key (keyboard - external or internal or both) -Com (communication option) |
TSA721 status bit assignments — PDF page 120
| Source row | Bit | Integer representation |
|---|---|---|
| 1 | 1 - 0 | Active Parameter Set, where: 0=A, 1=B, 2=C, 3=D. |
| 2 | 4 - 2 | Operation: 0=Stopped 1=Thyristor driven motor 2=Bypass driven motor |
| 3 | 7 - 5 | Source of Run/Stop command, where: 0=Rem, 1=Keyboard (internal + external), 2=Com, 3=Spare, 4=VIO, 5=Internal keyboard, 6=External keyboard. |
| 4 | 15 - 8 | Reserved for future use. |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 121
Manual reference: physical PDF page 121. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Digital Input Status [723]
This menu indicates the status of the digital inputs. See
example in Fig. 67.
DigIn 1
DigIn 2
DigIn 3
DigIn 4
The positions 1 - 4 (on the display, from left to right) indicate
the status of the associated input (DigIn 1 - DigIn 4):
High
Low
The example in Fig. 67 indicates that DigIn 2 and DigIn 4
are active at this moment.
Fig. 67 Digital input status example
Relay Status [724]
This menu indicates the status of the relays. See Fig. 68.
RE indicates the status of the relays on position:
Relay1
Relay2
Relay3
The status of the associated output is shown.
The example in Fig. 68 indicates that Relay 1 is active. Relay
2 and Relay 3 are not active.
Fig. 68 Relay status example
Analogue Input Status [725]
This menu indicates the status of the analogue input.
Fig. 69 Analogue input status example
The status of the input is shown in [%], so the example in
Fig. 69 indicates that AnIn is active and has a 65% input
value.
Table 32
Trip and warning messages
Read-only
NOTE: The shown percentage is an absolute value based
on the maximum value of the in- or output; so related to
either to 10 V or 20 mA.
723 DigIn Status
Stp
724 RelayStatus
RE 100
725 AnalogueIn
65%
Figures67–69 show723DigInStatus0101,724RelayStatusRE100,725AnalogueIn65%. Read-only examples, notdefaultsettings.
Table32 trip and warning messages; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Table32 trip and warning messages — PDF page 121
| Source row | Communication integer value |
Trip / warning message |
|---|---|---|
| 1 | 0 | No Error |
| 2 | 1 | Motor I²t |
| 3 | 2 | PTC |
| 4 | 3 | Locked rotor |
| 5 | 4 | Ext Alarm 1 |
| 6 | 5 | Ext Alarm 2 |
| 7 | 6 | Curr limit (current limit) |
| 8 | 7 | Start limit |
| 9 | 8 | Comm error (communication error) |
| 10 | 9 | Pt100 |
| 11 | 10 | Bypass open |
| 12 | 11 | BypassClosed |
| 13 | 12 | Mon MaxAlarm (load monitor max alarm) |
| 14 | 13 | Mon MaxPreAl (load monitor max pre- alarm) |
| 15 | 14 | Mon MinPreAl (load monitor min pre- alarm) |
| 16 | 15 | Mon MinAlarm (load monitor min alarm) |
| 17 | 16 | Over temp (over temperature) |
| 18 | 17 | Thyr open (thyristor open) |
| 19 | 18 | Thyr short (thyristor short) |
| 20 | 19 | Phase loss (single phase loss) |
| 21 | 20 | M Phase loss (multiple phase loss) |
| 22 | 21 | Under voltag (undervoltage) |
| 23 | 22 | Mot termOpen (motor terminal open) |
| 24 | 23 | Current Unbal (current unbalance) |
| 25 | 24 | CtrlSupFault (control voltage supply fault) |
| 26 | 25 | Spare25 (reserved for future use) |
| 27 | 26 | Int error1 (internal error 1) |
| 28 | 27 | Phase rev (phase reversal) |
| 29 | 28 | Spare28 (reserved for future use) |
| 30 | 29 | Int error2 (internal error 2) |
| 31 | 30 | Over voltag (overvoltage) |
| 32 | 31 | Volt Unbal (voltage unbalance) |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 122
Manual reference: physical PDF page 122. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Analogue Output Status [726]
This menu indicates the status of the analogue output. Fig.
70.
Fig. 70 Analogue output status example
The status of the output is shown in [%], so the example in
Fig. 70 indicates that AnOut is active and has a 65% output
value.
If 4-20 mA output is used for example, the value 20% equals
4 mA.
I/O Board Status B1 - B2 [727] - [728]
This menu indicates the status for the additional I/O on
option boards 1 (B1) and 2 (B2).
Fig. 71 I/O board status example
Analogue comparator status 1 - 4 [72A]
This menu indicates the active analogue comparators (CA1 -
CA4).
Digital comparator status 1 - 4 [72B]
This menu indicates the active digital comparators (CD1 -
CD4).
Logic function status 1 - 4 [72C]
This menu indicates the active logic outputs (L1 - L4).
Timer status 1- 4 [72D]
This menu indicates the active timers (T1Q - T4Q).
SR Flip-flop status 1 - 4 [72E]
This menu indicates the active flip-flops (F1 - F4).
Counter status 1 - 2 [72F]
This menu indicates the active counters (CTR1 - CTR2).
Time to next start [72G]
This menu indicates the time left to the next allowed start if
at least one of the choices under menu [235] Start Limitation
is activated (i.e. number of starts per hour or minimum time
between starts.
Read-only
NOTE: The shown percentage is an absolute value based
on the maximum value of the in- or output, so related to
either to 10 V or 20 mA.
726 AnalogueOut
Stp
65%
728 IO StatusB2
RE 000 DI100
72A CA1-4
72B CD1-4
72C Logic 1-4
72D Timer 1-4
72E FlipFlop1-4
72F Counter 1-2
72G TtoNxtStart
0Min
Figure70AnalogueOut65%;Figure71IOStatusB2RE000DI100. StatusLCDs72A/72B/72C/72D/72E0000;72F00;72G0Min. Read-onlyexamples.
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 123
Manual reference: physical PDF page 123. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.7.3
Stored Values [730]
The shown values are the actual values built up over time.
Values are stored at power down and updated again at power
up.
Run Time [731]
This menu displays the total time that the softstarter has been
in the run mode.
Reset Run Time [7311]
This menu resets the run time counter. The stored
information will be erased and a new registration period will
start.
Mains time [732]
connected to the mains supply. This timer cannot be reset.
Energy [733]
This menu displays the total energy consumption since the
last energy reset [7331] took place.
Reset Energy [7331]
This menu resets the energy counter. The stored information
will be erased and a new registration period will start.
8.7.4
Real time clock settings [740]
This menu group displays information on actual time and
date. The menus are quickly accessed from the default toggle
loop. See Fig. 24, page 36.
Time [741]
Actual time, displayed as HH:MM:SS. Adjustable setting.
Date [742]
Actual date, displayed as YYYY-MM-DD. Adjustable setting.
Weekday [743]
Display of actual weekday.
NOTE: After reset the setting automatically reverts to
“No”.
Unit:
hh:mm:ss (hours: minutes: seconds)
YYYY-MM-DD (year-month-day)
Read-only
741 Time
Stp
00:00:00
742 Date
743 Weekday
Monday
741TimeLCD00:00:00 andUnit hh:mm:ss;742DateLCD--- andUnitYYYY-MM-DD;743WeekdayLCDMonday,readonly. These single-bodyrow boxes are preserved in native text context.
Parameter panel 7331 Rst Energy; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 731 Run Time; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 7311 Reset RunTm; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Parameter panel 732 Mains Time; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 733 Energy; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 7331 Rst Energy — PDF page 123
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | No |
| 2 | Selection: | No, Yes |
Parameter panel 731 Run Time — PDF page 123
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | h: mm:ss (hours: minutes: seconds) |
| 2 | Range: | 00: 00: 00–262143: 59: 59 |
Parameter panel 7311 Reset RunTm — PDF page 123
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No |
| 2 | No | 0 | ⟦blank source cell⟧ |
| 3 | Yes | 1 | ⟦blank source cell⟧ |
Parameter panel 732 Mains Time — PDF page 123
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | hh: mm:ss (hours: minutes: seconds) |
| 2 | Range: | 00: 00: 00–262143: 59: 59 |
Parameter panel 733 Energy — PDF page 123
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: | Wh (shows Wh, kWh, MWh or GWh) |
| 2 | Range: | 0 Wh–999,999 GWh |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 124
Manual reference: physical PDF page 124. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.8
View Trip Log [800]
Main menu with parameters for viewing all the logged trip
data. In total the softstarter saves the last 9 trips in the trip
memory. The trip memory refreshes on the FIFO principle
(First In, First Out). Every trip in the memory is logged on
the time of the Run Time [731] counter. At every trip, the
actual values of several parameters are stored and available for
troubleshooting.
See section 7.3.1, page 45 for an explanation of the different
alarm types.
8.8.1
Trip Message Log [810]
The trip log displays the cause of the trip and what time it
occurred (based on the actual time in [740]). The display is
showing actual trip message and alternates between showing
date and time when the trip occured.
See a list of the possible trip messages in Table 32, page 117.
When a trip occurs the operation and status menus [710] and
[720]are copied to the trip message log. There are nine trip
message logs [810]–[890]. When the tenth trip occurs the
oldest trip message will be erased.
Example:
The display is showing actual trip message and alternates
between showing date and time when the trip occurred
For fieldbus integer value of trip message, see Table 32, page
117 (menu [722]).
Trip message [8111]-[8133]
The information from the status menus are copied to the trip
message log when a trip occurs.
NOTE: After the reset of a trip, the trip message will be
removed and menu [100] will appear.
830 Locked Rotor
Trp
09:12:14
2013-04-17
Table 33
Stored trip message parameters
Tripdisplayexample830LockedRotor alternates09:12:14 and2013-04-17. Table33 sectionheaderrows separateOperation710 andStatus720; table continues125.
Table33 trip-message mappings first page; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
-
row 1, column 3 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 21, column 3 share the source cell at row 21, column 2. Read its current text above; the child slots remain unpopulated.
Parameter panel 8x0 Trip Message; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Table33 trip-message mappings first page — PDF page 124
| Source row | Trip menu | Copied from | Description |
|---|---|---|---|
| 1 | ⟦blank source cell⟧ | 8.7.1 Operation values [710] | ⟦null: no independent source value⟧ |
| 2 | 8111 | 711 | Process Value |
| 3 | 8113 | 713 | Torque (Nm) |
| 4 | 8114 | 714 | Torque (%) |
| 5 | 8115 | 715 | Shaft Power (W) |
| 6 | 8116 | 716 | Shaft Power (%) |
| 7 | 8117 | 717 | El Power |
| 8 | 8118 | 718 | RMS Current |
| 9 | 8119 | 719 | L Main Volt |
| 10 | 811A | 71A | Heatsink Temp |
| 11 | 811B | 71B | PT100B1 123 |
| 12 | 811C | 71C | PT100B2 123 |
| 13 | 811D | 71D | Current I1 |
| 14 | 811E | 71E | Current I2 |
| 15 | 811F | 71F | Current I3 |
| 16 | 811G | 71G | L12 Voltage |
| 17 | 811H | 71H | L13 Voltage |
| 18 | 811I | 71I | L23 Voltage |
| 19 | 811J | 71J | Phase Seq |
| 20 | 811K | 71K | Used Thermal Cap |
| 21 | ⟦blank source cell⟧ | 8.7.2 Status [720] | ⟦null: no independent source value⟧ |
| 22 | 8121 | 721 | TSA Status |
| 23 | 8122 | 723 | Digital input status |
| 24 | 8123 | 724 | Relay status |
| 25 | 8124 | 725 | Analogue input status |
| 26 | 8125 | 726 | Analogue output status |
| 27 | 8126 | 727 | I/O status option board B1 |
| 28 | 8127 | 728 | I/O status option board B2 |
| 29 | 8129 | 72A | Analogue comparator 1 - 4 |
| 30 | 812A | 72B | Digital comparator 1 - 4 |
| 31 | 812B | 72C | Logic function status 1-4 |
| 32 | 812C | 72D | Timer status 1-4 |
| 33 | 812D | 72E | Flip-flop status 1-4 |
| 34 | 812E | 72F | Counter status 1-2 |
Parameter panel 8x0 Trip Message — PDF page 124
| Source row | Label | Value |
|---|---|---|
| 1 | Unit: Alternating |
hh:mm:ss (hours: minutes: seconds) YYYY-MM-DD (year-month-day) |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 125
Manual reference: physical PDF page 125. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.8.2
Trip Messages [820] - [890]
Same information as for menu [810].
8.8.3
Reset Trip Log [8A0]
This menu resets the content of the 10 trip memories.
8.9
System Data [900]
Main menu for viewing all the softstarter system data.
8.9.1
TSA Data [920]
TSA Type [921]
This menu shows the Emotron TSA type according to the
type code. The options are indicated on the product label of
the softstarter. See section 1.4, page 5.
Fig. 72 Type number example.
Example:
TSA-series suited for 525 V mains supply, and a rated output
current of 16 A.
Software [922]
This menu shows the software version number of the
softstarter. Fig. 73 gives an example.
Fig. 73 Software version example.
NOTE: After the reset the setting goes automatically
back to “NO”. The message “OK” is displayed for 2 sec.
Table 33
Stored trip message parameters
NOTE: If the control board is not configured, then type
shown is TSA52-XXX.
Table 34
Information for Modbus and Profibus number,
software version
Table 35
option version
TSA
Stp
TSA52-016
922 Software
V1.00
Table34 release-type codes0Vrelease,1Ppre-release,2βBeta,3αAlpha. Table35 minoroption07 andmajor03 retain leadingzeros. These areexamples, notinstalledfirmware evidence.
Table33 trip-message mappings continued; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Shared source cells (coordinates refer to this table):
- row 2, column 3 share the source cell at row 2, column 2. Read its current text above; the child slots remain unpopulated.
Parameter panel 8A0 Reset Trip L; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
- row 1, column 2 share the source cell at row 1, column 1. Read its current text above; the child slots remain unpopulated.
Table34 software version fieldbus bits; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Table35 option version fieldbus bits; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Table33 trip-message mappings continued — PDF page 125
| Source row | Trip menu | Copied from | Description |
|---|---|---|---|
| 1 | 812F | 72G | Time to next start |
| 2 | ⟦blank source cell⟧ | 8.7.3 Stored Values [730] | ⟦null: no independent source value⟧ |
| 3 | 8131 | 731 | Run time |
| 4 | 8132 | 732 | Mains time |
Parameter panel 8A0 Reset Trip L — PDF page 125
| Source row | Selection or label | Communication code or merged label | Description or default/range |
|---|---|---|---|
| 1 | Default: | ⟦null: no independent source value⟧ | No |
| 2 | No | 0 | ⟦blank source cell⟧ |
| 3 | Yes | 1 | ⟦blank source cell⟧ |
Table34 software version fieldbus bits — PDF page 125
| Source row | Bit | Example | Description |
|---|---|---|---|
| 1 | 7–0 | 30 | Minor version |
| 2 | 13–8 | 4 | Major version |
| 3 | 15–14 | 0 | Release type: 0: V, release version 1: P, pre-release version 2: β, Beta version 3: α, Alpha version |
Table35 option version fieldbus bits — PDF page 125
| Source row | Bit | Example | Description |
|---|---|---|---|
| 1 | 7–0 | 07 | Minor option version |
| 2 | 15–8 | 03 | Major option version |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 126
Manual reference: physical PDF page 126. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Build Info [9221]
Unit Name [923]
Option to enter a name of the unit for service use or
customer identity. The function enables the user to define a
name with max 12 characters. Press the + / - keys to enter
graphic symbols from the same list as for User-defined Unit
[323], page 76. See also "Editing parameter values", page 35.
NOTE: It is important that the software version displayed
in menu [922] is the same software version number as
the software version number written on the title page of
this instruction manual. If not, the functionality as
described in this manual may differ from the
functionality of the softstarter.
Parameter panel 9221 Build Info; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 923 USER 15; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter panel 9221 Build Info — PDF page 126
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | YY:MM:DD:HH:MM:SS |
Parameter panel 923 USER 15 — PDF page 126
| Source row | Label | Value |
|---|---|---|
| 1 | Default: | No characters shown |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 127
Manual reference: physical PDF page 127. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
9.
Serial communication
The softstarter provides the possibility of different types of
serial communication.
•
Modbus RTU via RS232, RS485, USB and BT
Fieldbuses such as Profibus DP and DeviceNet
Industrial Ethernet such as Modbus/TCP, Profinet IO
and EtherCAT
See “12. Options” on page 137 for available communication
option boards.
9.1
Modbus RTU
There is an asynchronous unisolated RS232 serial
communication interface on top of the Emotron TSA unit.
It is also possible to use the isolated RS485 or USB option
boards (if installed).
The protocol used for data exchange is based on the Modbus
RTU protocol, originally developed by Modicon. The
softstarter acts as a slave with address 1 in a master-slave
configuration. The communication is half-duplex. It has a
standard non return zero (NRZ) format.
The baud rate is fixed to 9600 with fixed address = 1
(on-board RS232 port), but it is adjustable for the USB and
RS485 option boards.
The character frame format (always 11 bits) has:
one start bit
eight data bits
two stop bits
no parity
It is possible to temporarily connect a personal computer
with for example the software EmoSoftCom (programming
and monitoring software) to the RS232 connector on top of
the Emotron TSA unit. This can be useful when copying
parameters between softstarters, etc. For permanent
connection of a personal computer you have to use one of
the communication option boards RS485 or USB.
9.2
Parameter sets
Communication information for the different parameter
sets.
The different parameter sets in the softstarter have the
following DeviceNet instance numbers, Profibus slot/index
numbers, Profinet IO index and EtherCAT index numbers:
Parameter set A contains parameters 43001 to 43899. The
parameter sets B, C and D contain the same type of
information. For example parameter 43123 in parameter set
A contains the same type of information as 44123 in
parameter set B.
NOTE: This RS232 port is not galvanically isolated.
WARNING!
Correct and safe use of a RS232 connection
depends on the ground pins of both ports
having the same potential. Problems can
occur when connecting two ports of e.g. machinery and
computers where both ground pins have not the same
potential. This may cause hazardous ground loops that
can destroy the RS232 ports.
The on-board RS232 connection is not galvanically
isolated.
The RS485 and USB option boards from CG Drives &
Automation are galvanically isolated.
Note that the on-board RS232 connection can safely be
used in combination with commercially available
isolated USB to RS232 converters.
Fivecolumn parameter-set table retains Param.set /Modbus-DeviceNetInstance/ProfibusSlot-Index/ProfinetIOindex/EtherCAThex. C endpoint5706 is visiblyprinted; no calculation substituted.
Parameter set communication address mappings; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Parameter set communication address mappings — PDF page 127
| Source row | Param. set |
Modbus/ DeviceNet Instance number |
Profibus Slot/Index |
Profinet IO index |
EtherCAT index (hex) |
|---|---|---|---|---|---|
| 1 | A | 43001– 43899 |
168/160 to 172/38 |
19385 - 20283 |
4bb9 - 4f3b |
| 2 | B | 44001– 44899 |
172/140 to 176/18 |
20385 - 21283 |
4fa1 - 5323 |
| 3 | C | 45001– 45899 |
176/120 to 179/253 |
21385 - 22283 |
5389 - 5706 |
| 4 | D | 46001– 46899 |
180/100 to 183/233 |
22385 - 23283 |
5771 - 5af3 |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 128
Manual reference: physical PDF page 128. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
9.3
Motor data
Communication information for the different motors.
M1 contains parameters 43041 to 43048. The M2, M3, and
M4 contain the same type of information. For example
parameter 43043 in motor M1 contains the same type of
information as 44043 in M2.
9.4
Start and stop commands
Set start and stop commands via serial communication.
Requires that menu [2151] Run/Stop Control is set to
“Com”.
9.5
Process value
It is also possible to send the Process value feedback
signal over a bus (e.g. from a process or temperature sensor).
Set menu “Process Source [321 ]” to F(Bus). Use following
parameter data for the process value:
Communication information
MotorM2Profibuscell visibly172/180 to174/187. Processvalueencodingtable beginsDefault0; communicationtable beginsModbus/DeviceNet42906. Both firstrowsaredata, notheaders.
Motor data communication address mappings; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Process value feedback encoding; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Process value communication information; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Serial start stop commands; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.
Motor data communication address mappings — PDF page 128
| Source row | Motor | Modbus/ DeviceNet Instance number |
Profibus Slot/ Index |
Profinet IO index |
EtherCAT index (hex) |
|---|---|---|---|---|---|
| 1 | M1 | 43041– 43048 |
168/200 to 168/207 |
19425 - 19432 |
4be1 - 4be8 |
| 2 | M2 | 44041– 44048 |
172/180 to 174/187 |
20425 - 20432 |
4fc9 - 4fd0 |
| 3 | M3 | 45041– 45048 |
176/160 to 176/167 |
21425 - 21432 |
53b1 - 53b8 |
| 4 | M4 | 46041– 46048 |
180/140 to 180/147 |
22425 - 22432 |
5799 - 57a0 |
Process value feedback encoding — PDF page 128
| Source row | Label | Value |
|---|---|---|
| 1 | Default | 0 |
| 2 | Range | -16384 to 16384 |
| 3 | Corresponding to | -100% to 100% process value |
Process value communication information — PDF page 128
| Source row | Label | Value |
|---|---|---|
| 1 | Modbus /DeviceNet Instance number | 42906 |
| 2 | Profibus slot /Index | 168/65 |
| 3 | Profinet IO index | 19290 |
| 4 | Fieldbus format | Int |
| 5 | Modbus format | Int |
Serial start stop commands — PDF page 128
| Source row | Modbus/DeviceNet Instance number |
Function |
|---|---|---|
| 1 | 42901 | Reset |
| 2 | 42902 | Run, active together with either Run FWD or Run REV to perform start. |
| 3 | 42903 | Run FWD |
| 4 | 42904 | Run REV |
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 129
Manual reference: physical PDF page 129. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
9.6
Description of the EInt
formats
A parameter with Eint format can be represented in two
different formats (F), either as a 15 bit unsigned integer
format (F= 0) or a Emotron floating point format (F=1).
The most significant bit (B15) indicates the format used.
See detailed description below.
All parameters written to a register may be rounded to the
number of significant digits used in the internal system.
The matrix below describes the contents of the 16-bit word
for the two different EInt formats:
If the format bit (B15) is 0, then all bits may be treated as a
standard unsigned integer (UInt).
If the format bit is 1, then the number is interpreted as:
Value = M * 10^E, where M=m10..m0 represents a
two- complement signed mantissa and E= e3..e0 represents a
two- complement signed exponent.
Example, resolution
If you write the value 1004 to a register and this register has
3 significant digits, it will be stored as 1000.
In the Emotron floating point format (F=1), one 16-bit
word is used to represent large (or very small numbers) with
3 significant digits.
If data is read or written as a fixed point (i.e. no decimals)
number between 0-32767, the 15 bit Unsigned integer
format (F=0) may be used.
Detailed description of Emotron floating point
format
A signed number should be represented as a two-
complement binary number, like below:
Value Binary
The value represented by the Emotron floating point format
is m·10e.
To convert a value from the Emotron floating point format
to a floating point value, use the formula above.
To convert a floating point value to the Emotron floating
point format, see the C-code example below.
Example, floating point format
The number 1.23 would be represented by this in Emotron
floating point format,
The value is then 123x10-2 = 1.23
Example 15bit unsigned integer format
The value 72.0 can be represented as the fixed point number
- It is within the range 0-32767, which means that the
15-bit fixed point format may be used.
The value will then be represented as:
Where bit 15 indicates that we are using the fixed point
format (F=0).
NOTE: Parameters with EInt format may return values
both as 15 bit unsigned integer (F=0) or in Emotron
floating point (F=1).
e3-e0 4-bit signed exponent. Gives a value
range:
-8..+7 (binary 1000 .. 0111)
m10-m0 11-bit signed mantissa. Gives a
value range:
-1024..+1023 (binary
10000000000..01111111111)
B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0
F=1 e3 e2 e1 e0 m10 m9 m8 m7 m6 m5 m4 m3 m2 m1 m0
F=0 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0
-8 1000
-7 1001
..
-2 1110
-1 1111
0 0000
1 0001
2 0010
6 0110
7 0111
F EEEE MMMMMMMMMMM
1 1110 00001111011
F=1 -> floating point format used
E=-2
M=123
0 0 0 0 0 0 0 0 0 1 0 0 1 0 0 0
Bit matrix F=1: B15F,B14e3,B13e2,B12e1,B11e0,B10m10 throughB0m0. F=0: B15F,B14..B0unsignedbits. Signedbinary examplepairs−8:1000,−7:1001,..,−2:1110,−1:1111,0:0000,1:0001,2:0010,..,6:0110,7:0111. Ellipsesretainomissions.1.23=123×10⁻²;72binary0000000001001000.
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 130
Manual reference: physical PDF page 130. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Programming example:
typedef struct
{
int m:11; // mantissa, -1024..1023
int e: 4; // exponent -8..7
unsigned int f: 1; // format, 1->special emoint format
}
eint16;
//---------------------------------------------------------------------------
unsigned short int float_to_eint16(float value)
eint16 etmp;
int dec=0;
while (floor(value) != value && dec<16)
dec++; value*=10;
if (value>=0 && value<=32767 && dec==0)
(short int )&etmp=(short int)value;
else if (value>=-1000 && value<0 && dec==0)
etmp.e=0;
etmp.f=1;
etmp.m=(short int)value;
else
etmp.m=0;
etmp.e=-dec;
if (value>=0)
etmp.m=1; // Set sign
etmp.m=-1; // Set sign
value=fabs(value);
while (value>1000)
etmp.e++; // increase exponent
value=value/10;
value+=0.5; // round
etmp.m=etmp.m*value; // make signed
return ((unsigned short int )&etmp);
float eint16_to_float(unsigned short int value)
float f;
eint16 evalue;
evalue=(eint16 )&value;
if (evalue.f)
if (evalue.e>=0)
f=(int)evalue.m*pow10(evalue.e);
f=(int)evalue.m/pow10(abs(evalue.e));
f=value;
return f;
Rendered firstfunction return statement is lowercase return ((unsigned short int )&etmp);. NativeRreturn retained as raw, not propagated as codevalue. Code is supplier example only, notexecuted.
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 131
Manual reference: physical PDF page 131. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.
Softstarter theory
In this chapter different starting methods for induction
motors are explained and compared. The functionality of
softstarters with torque control and their advantages and
limitations compared to other starting methods are
explained.
First a brief account of the background theory of starting
induction motors will be given in section 10.1. Thereafter
the different starting methods based on the usage of reduced
voltage will be described and compared. This chapter will
also cover softstarters with torque control. In section 10.3,
some common starting methods based on other physical
principles are explained. With this information some
limitations of the reduced voltage starters will become clear.
In section 10.4 there is a brief analysis of which applications
may benefit from using a softstarter.
10.1 Background theory
The following two sections deal with motors with squirrel-
cage rotors. In contrast to a wound rotor, the squirrel-cage
rotor consists of straight conductors, which are short-
circuited together at both ends.
When such a motor is connected directly to the line voltage
it will typically draw a starting current of about 5 to 8 times
its nominal current while the resulting starting torque will
be about 0.5 to 1.5 times its nominal torque. In the
following picture a typical starting characteristic is shown.
The x-axis represents the speed relative to the synchronous
speed while the y-axis shows the torque and the current
respectively, with those quantities normalised to their
nominal values. The dashed line indicates the nominal
values.
Fig. 74 Typical torque characteristics for the DOL start
Fig. 75 Typical current characteristics for the DOL start
For many industrial applications direct on-line starting is
not convenient, as the supply in this case has to be
dimensioned to deliver the unnecessarily high starting
current. Moreover, most applications do not gain anything
from the high starting torque. Instead there is a risk of
mechanical wear or even damage because of the resulting
jerk at speedup.
The acceleration torque is determined by the difference
between motor and load torque. The figure below shows
some typical torque characteristics for constant speed
applications. For comparative purposes, the induction
motors’ torque characteristic is added to the diagram.
Fig. 76 Typical load torque characteristics
0,5
1,5
2,5
Torque
T/Tn
n/ns
Current
I/In
Fig74torqueverticalT/Tn0,0.5,1,1.5,2,2.5;Fig75currentI/In0–8integersteps;bothhorizontaln/ns0,0.5,1. Fig76usesT/Tn sameaxiswithloadcurves;no curvevalues digitized.
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 132
Manual reference: physical PDF page 132. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Typical applications with constant load are elevators, cranes
and conveyors. Linear load characteristics are typical for
calender rollers and various smoothing machines, whereas
quadratic correlation between speed and torque is typical for
pumps and fans. Some applications like conveyors or screws
may need an initial torque boost. However, for many
applications it can be seen that the torque needed is much
lower than the torque delivered by the induction motor in a
DOL start.
A common method to reduce both starting torque and
current is to decrease the motor voltage during starting. The
following figure shows how the motor’s torque and current
characteristics are changed when the supply voltage is
reduced.
Fig. 77 Reduced voltage start
A general rule of thumb is that the torque at each operating
point is roughly proportional to the square of the current.
This means when the motor current is decreased by a factor
of two by means of reducing the supply voltage, the torque
delivered by the motor will be decreased by a factor of four
(approximately).
This relationship is the base for any starting method using
reduced voltage. It can be seen that the possibility of
reducing the starting current depends on the correlation
between the motor’s and the load’s torque characteristic. For
the combination of an application with very low starting
load and a motor with very high starting torque, the starting
current may be reduced significantly by means of decreasing
the voltage during start. However, for applications with high
starting load it may – depending on the actual motor – not
be possible to reduce the starting current at all.
10.2 Reduced voltage starting
This section describes different starting methods which are
based on the reduced-voltage principle explained above. A
pump and its quadratic torque characteristic are used as an
example.
The star-delta starter is the simplest example of a reduced
voltage starter. The motor phases are first star connected; at
about 75% of nominal speed the phase connection is then
changed to delta. To enable star-delta start, both ends of all
three motor windings have to be available for connection.
Moreover, the motor has to be dimensioned for the (higher)
voltage in the delta connection. The following figure shows
the resulting torque and current characteristics.
0,5
1,5
2,5
Torque
T/Tn
n/ns
Current
I/In
Un
U2<Un
U3<U2
T ~ I 2
ILV = 1/2 IDOL → TLV ≈ 1/4 TDOL
ILV = 1/3 IDOL → TLV ≈ 1/9 TDOL
LV=low voltage
DOL=Direct on line
Fig77 pairedT/Tn0–2.5halfsteps andI/In0–8integersteps versusn/ns0,0.5,1;curve labelsUn,U2<Un,U3<U2. Formula T~I²; I_LV=1/2 I_DOL→T_LV≈1/4 T_DOL;1/3→1/9. LVlowvoltage,DOLdirectonline.
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 133
Manual reference: physical PDF page 133. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 78 Star-delta start
The disadvantage of the star-delta start is that it cannot be
adapted to a special application. Both the voltage in star and
in delta connections are defined by the supply, and the
resulting starting performance depends on the motor’s DOL
characteristic. For some applications the star-delta starter
cannot be used as the resulting torque in a star connection is
too low to start rotating the load. On the other hand for low
load applications further savings of starting current are
impossible even though a big torque reserve is available.
Moreover, the resulting abrupt rise of torque first at start and
later when changing from star to delta connection may
contribute to mechanical wear. The high transient currents
during start-delta transition create unnecessary excess heat in
the motor.
Better performance is achieved with a voltage ramp start,
which a simple electronic softstarter can provide. The
voltage is increased linearly from an initial value to the full
supply voltage by means of phase angle control. The
resulting torque and current characteristics are shown in the
following figure.
Fig. 79 Soft starting – voltage ramp
Obviously a much smoother start is realised compared to the
star-delta start and the starting current is decreased.
A softstarter is often used to keep the starting current below
a desired level. For the example above, setting a current limit
of three times the nominal current may be desirable. The
following figure shows the resulting torque and current
characteristics.
0,5
I/In
n/ns
1,5
2,5
Torque
T/Tn
Current
Fig78star-deltastart(left) and79softstartingvoltage-ramp(right): torqueT/Tn0–2.5halfsteps/currentI/In0–8integersteps vsn/ns0,0.5,1. Curvesillustrative, unlabelledtracegeometryremainsPDF.
Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 134
Manual reference: physical PDF page 134. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 80 Soft starting – voltage ramp with current limit
Once again the figure illustrates that the resulting
performance depends on the combination of motor and load
characteristics. In the example above the motor torque is
close to the load torque at about half speed. This means for
some other applications with different load characteristics
(for example a linear torque-speed correlation) this
particular motor would need more than three times the
nominal current to start.
The most sophisticated electronic softstarters use torque
control, which results in an almost constant acceleration
during the start. A low starting current is also achieved.
However, this start method also uses reduced motor voltage
and the quadratic correlation between current and torque
described in the first section of this chapter is still valid. This
means, the lowest possible starting current is determined by
the combination of motor and load characteristics.
Fig. 81 Soft starting – torque control
For optimal starting performance, correct setting of the
softstarter’s parameters such as initial torque and end torque
at start and start time is important. The choice of parameters
is explained in detail in section 8.3.3, page 78.
10.3 Other starting methods
In contrast to the preceding sections of this chapter, which
focused on squirrel-cage motors, slip-ring motors are dealt
with later on. A slip-ring motor is equipped with a wound
rotor; one end of each rotor winding is available for external
connection via slip-rings. These motors are often optimised
for rotor resistance starting, i.e. with short-circuited rotor
windings they develop a very low torque at an extremely
high current. For starting, external resistances are connected
to the rotor windings. During the start, the resistance value
is decreased in several steps until the rotor windings are
short-circuited at nominal speed. The following figure
shows typical torque and current characteristics for a slip-
ring motor during the start with an external rotor-resistance
starter.
0,5
1,5
2,5
I/In
n/ns
Torque
T/Tn
Current
Fig80softstartingvoltage-rampwithcurrentlimit(left) and81torquecontrol(right);sameT/Tn0–2.5/I/In0–8,n/ns0,0.5,1axes. Currentlimitexamplelineat3; not productmaximum. Slip-ring illustration referred to is onnextpage135.
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 135
Manual reference: physical PDF page 135. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Fig. 82 Rotor-resistance starting
Because of the low starting torque it is often not possible to
short-circuit the rotor windings and replace the rotor-
resistance starter with a softstarter. However, it is always
possible to use a frequency inverter instead. The following
illustration shows how the torque and current characteristics
are affected when the stator frequency is changed.
Fig. 83 Voltage/frequency regulation
Thus, such a motor can be started with a quite simple
frequency inverter with voltage-frequency regulation. This
solution is also valid for all other applications, which for
some reason (high load torque compared to motor torque
etc.) cannot be started by a softstarter.
0,5
1,5
2,5
I/In
n/ns
Torque
T/Tn
Current
f3<f2
f2<fn
fn
Figures82/83: torque T/Tn axis0,0.5,1,1.5,2,2.5; current I/In axis0–8integer; speed n/ns0,0.5,1. Fig83 shows f3<f2, f2<fn, fn. Qualitative curves; no interpolated values.
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 136
Manual reference: physical PDF page 136. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.4 Use of softstarters with
torque control
To determine if a specific application benefits from using a
softstarter at all, the correlation between the motor’s torque
characteristic during the start and the load’s requirements
has to be evaluated. As it can be seen from the examples
above, the application will only benefit from using a
softstarter if the load torque during the start is clearly below
the motor’s starting capacity. However, loads with a high
initial release torque may also benefit from a softstarter. In
this case an initial torque boost can be used, thereafter the
start ramp is continued reducing the starting current
considerably.
The benefit can be maximised when using a softstarter with
torque control. To be able to configure the torque control
parameters for optimal performance, the load characteristics
(linear, square or constant load, need of initial release
torque) must be known. In this case a proper torque control
method (linear or square) can be chosen and torque boost
can be enabled if needed.
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 137
Manual reference: physical PDF page 137. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.
Troubleshooting, Diagnoses and Maintenance
For a description of the different alarm states, see “Alarm
indications” on page 45.
11.1 Trip conditions, causes and
remedial action
The table later on in this section must be seen as a basic aid
to find the cause of a system failure and how to solve any
problems that arise. Although the softstarter gives a certain
trip message it is not always easy to find the right cause of
the failure. Good knowledge of the complete system is
therefore necessary. Contact your supplier if you have any
questions.
The softstarter is designed in such a way that it tries to avoid
trips by limiting torque, overvoltage etc.
Failures occurring during commissioning or shortly after
commissioning are most likely to be caused by incorrect
settings or even bad connections.
Failures or problems occurring after a reasonable period of
failure-free operation can be caused by changes in the system
or in its environment (e.g. wear).
Failures that occur regularly for no obvious reasons are
generally caused by electromagnetic interference. Be sure
that the installation fulfils the demands for installation
stipulated in the EMC directives. See section 1.5.1, page 6.
Sometimes the so-called “Trial and error” method is a
quicker way to determine the cause of the failure. This can
be done at any level, from changing settings and functions to
disconnecting single control cables or replacing entire units.
The “Trip Message Log” [800] can be useful for determining
why certain trips recur at certain moments. The trip log
records the time of the trip in relation to the run time
counter. Under each trip message the values of a number of
parameters are saved. See Table 33, page 120.
11.1.1Technically qualified personnel
Installation, commissioning, demounting, making
measurements, etc., of or at the softstarter may only be
carried out by personnel technically qualified for the task.
11.1.2Opening the softstarter
The connections for the control signals and the switches are
isolated from the mains voltage. Always take adequate
precautions before opening the softstarter.
11.2 Maintenance
The Emotron TSA softstarter is designed to require a
minimum of servicing and maintenance. There are however
some things which must be checked regularly:
For model size 2 and up there is an internal fan that should
be inspected and cleaned from dust if necessary.
If softstarters are built into cabinets, also check and clean the
dust filters of the cabinets regularly.
Check external wiring, connections and control signals.
Tighten terminal screws if necessary. For more information
on maintenance, please contact your CG Drives &
Automation service partner.
Precautions to take with a connected motor
If work must be carried out on a connected motor or on the
driven machine, the mains voltage must always first be
disconnected from the softstarter.
WARNING!
If it is necessary to open the softstarter or
any part of the system (motor cable housing,
conduits, electrical panels, cabinets, etc.) in
order to inspect or take measurements as suggested in
this instruction manual, it is absolutely necessary to
read and follow the safety instructions in the manual.
Always switch off the mains and control
supply voltage if it is necessary to open the
softstarter.
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 138
Manual reference: physical PDF page 138. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.3 Troubleshooting list
Table 36
Alarms with possible causes and remedies.
Table36 alarm troubleshooting; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Shared source cells (coordinates refer to this table):
- row 14, column 5, row 15, column 5, row 16, column 5 share the source cell at row 13, column 5. Read its current text above; the child slots remain unpopulated.
Table36 alarm troubleshooting — PDF page 138
| Source row | Trip/warning message | Alarm action | Menu | Possible cause | Remedy |
|---|---|---|---|---|---|
| 1 | Bypass closed | Hard trip | ⟦blank source cell⟧ | Bypass contactor is permanently shortcircuited . |
Service needed. Contact your local Emotron TSA supplier. |
| 2 | Bypass open | Hard trip | ⟦blank source cell⟧ | Bypass contactor or its control is malfunctioning. |
Service needed. Contact your local Emotron TSA supplier. |
| 3 | Comm error | No action Hard trip Soft trip Warning |
2641 | Error on serial communication/ Fieldbus (option). |
Check cables and connection of the serial communication. Check all settings with regard to the communication. Restart the equipment including the softstarter. For details, see Fieldbus Manual. |
| 4 | CP locked! | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Control panel is locked for settings. |
Unlock control panel in menu [218]. Enter unlock code “291”. |
| 5 | CtrlSupFault | Hard trip | ⟦blank source cell⟧ | Control voltage supply fault. | Check control supply voltage level. |
| 6 | Curr limit | No action Hard trip Soft trip Warning |
236 | Current limit parameters are perhaps not matched to the load and motor. |
Increase the start time (menu [336]) and/or the current limit at start (menu [335]). |
| 7 | Curr Unbal | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Bypass or thyristor fault | Service needed. Contact your local Emotron TSA supplier. |
| 8 | Ext Alarm 1 | No action Hard trip Soft trip Warning |
4211 | External trip connected to digital input active: active low function on the input. |
Check the equipment that initiates the external input. Check the programming of the digital inputs, menu [520]. |
| 9 | Ext Alarm 2 | No action Hard trip Soft trip Warning |
4212 | External trip connected to digital input active: active low function on the input. |
Check the equipment that initiates the external input. Check the programming of the digital inputs, menu [520]. |
| 10 | Int phase loss | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Internal phase loss. | Service needed. Contact your local Emotron TSA supplier. |
| 11 | Internal alarm | Hard trip | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Service needed. Contact your local Emotron TSA supplier. |
| 12 | Locked rotor | No action Hard trip Soft trip Warning |
422 | Torque limit at motor standstill: Mechanical blocking of the rotor. |
Check for mechanical problems at the motor or the machinery connected to the motor. Set [4221] Locked rotor alarm to “No action”. Adjust Locked Rotor time [4222] and Locked Rotor Current [4223] |
| 13 | Mon MaxAlarm | No action Hard trip Soft trip Warning |
⟦blank source cell⟧ | Max alarm level (overload) has been reached [4112]. |
Check the load condition of the machine. Check the monitor setting in section 8.4, page 84. |
| 14 | Mon MaxPreAl | No action Hard trip Soft trip Warning |
⟦blank source cell⟧ | Max pre-alarm level (overload) has been reached [4122]. |
⟦null: no independent source value⟧ |
| 15 | Mon MinAlarm | No action Hard trip Soft trip Warning |
⟦blank source cell⟧ | Min alarm level (underload) has been reached [4142]. |
⟦null: no independent source value⟧ |
| 16 | Mon MinPreAl | No action Hard trip Soft trip Warning |
⟦blank source cell⟧ | Min pre-alarm level (underload) has been reached [4132]. |
⟦null: no independent source value⟧ |
| 17 | Motor I2t (Area D: I2t) |
No action Hard trip Soft trip Warning |
2311 | I2t value is exceeded. Overload on the motor according to the prog-rammed I2t settings. |
Check for mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.). Change the Motor I2t Current setting in menu [2312] |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 139
Manual reference: physical PDF page 139. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 36
Alarms with possible causes and remedies.
Table36 alarm troubleshooting; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Table36 alarm troubleshooting — PDF page 139
| Source row | Trip/warning message | Alarm action | Menu | Possible cause | Remedy |
|---|---|---|---|---|---|
| 1 | Motor term open (motor terminal open) |
Hard trip | ⟦blank source cell⟧ | Open motor contact, cable or motor winding. |
Check wiring between softstarter and motor. Initiate a restart. If the alarm appears again, contact your local Emotron TSA supplier. |
| 2 | Mul phase loss | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 2 or 3 phases lost in mains supply voltage. |
Check fuses and mains supply. |
| 3 | Over temp | Hard trip | ⟦blank source cell⟧ | Heatsink temperature too high: Too high ambient temperature of the softstarter. Insufficient cooling. Too high current. Blocked or stuffed fans. |
Check the cooling of the softstarter cabinet. Check the functionality of the built-in fans. The fans must switch on automatically if the heatsink temperature gets too high. At power up the fans are briefly switched on. Check softstarter and motor rating. Clean fans. |
| 4 | Over voltage | No action Hard trip Soft trip Warning |
4321 | Too high 3-phase mains supply voltage. |
Check the 3-phase main supply voltage. Remove the interference cause or use other main supply lines. |
| 5 | Phase loss | No action Hard trip Soft trip Warning |
235 | Single phase loss. Fuse broken. |
Check fuses and mains supply. Check that terminal screws are tightened. |
| 6 | Phase rev | No action Hard trip Soft trip Warning |
4341 | Incorrect phase sequence on 3- phase main supply. |
Swap L2 and L3 input phases. |
| 7 | PT100 | No action Hard trip Soft trip Warning |
2321 | Motor PT100 elements exceeds maximum level. NOTE: Only valid if option board PTC/PT100 is used. |
Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.). Check the motor cooling system. Self-cooled motor at low speed, too high load. Set alarm action to “Off”. |
| 8 | PTC | No action Hard trip Soft trip Warning |
2331 | Motor thermistor (PTC) exceeds maximum level. |
If motor overheated, wait for it to cool down. Check on mechanical overload on the motor or the machinery (bearings, gearboxes, chains, belts, etc.) Check the motor cooling system. Self-cooled motor at low speed, too high load. Set alarm action to “No action”. |
| 9 | Start limit | No action Hard trip Soft trip Warning |
2341 | Number of starts per hour exceeded, min time between starts not kept. |
Wait and start again. Perhaps the number of starts per hour could be decreased in menu [2342] or the min time between starts could be increased (menu [2343]). |
| 10 | Stop first! | ⟦blank source cell⟧ | ⟦blank source cell⟧ | During start, stop and jog, changing parameters is not permitted. |
Set parameters during standstill. |
| 11 | Thyristor open | Hard trip | ⟦blank source cell⟧ | Damaged thyristor or control wiring. |
Service needed. Contact your local Emotron TSA supplier. |
| 12 | Thyristor short | Hard trip | ⟦blank source cell⟧ | Damaged thyristor. | Service needed. Contact your local Emotron TSA supplier. |
| 13 | Under voltage | No action Hard trip Soft trip Warning |
4331 | Too low 3-phase mains supply voltage. Mains voltage dip due to starting other major power consuming machines on the same line. |
Make sure all three phases are properly connected and that the terminal screws are tightened. Check that the 3-phase mains supply voltage is within the limits set in menu group [433]. Use other mains supply lines if dip is caused by other machinery. |
| 14 | Volt unbalance | No action Hard trip Soft trip Warning |
4311 | Mains supply voltage unbalance. | Check 3-phase mains supply. Check settings in menu [4312] and [4313]. |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 140
Manual reference: physical PDF page 140. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Troubleshooting matrix; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Shared source cells (coordinates refer to this table):
-
row 4, column 1, row 5, column 1, row 6, column 1, row 7, column 1, row 8, column 1, row 9, column 1, row 10, column 1, row 11, column 1 share the source cell at row 3, column 1. Read its current text above; the child slots remain unpopulated.
-
row 4, column 2, row 5, column 2, row 6, column 2, row 7, column 2, row 8, column 2, row 9, column 2 share the source cell at row 3, column 2. Read its current text above; the child slots remain unpopulated.
-
row 9, column 3 share the source cell at row 8, column 3. Read its current text above; the child slots remain unpopulated.
-
row 11, column 2 share the source cell at row 10, column 2. Read its current text above; the child slots remain unpopulated.
Troubleshooting matrix — PDF page 140
| Source row | Observation | Fault indication | Cause | Solution |
|---|---|---|---|---|
| 1 | The display is not illuminated. |
None | No control supply voltage. | Switch on the control supply voltage. |
| 2 | Softstarter does not react to start command |
- - - - | Start command comes perhaps from incorrect control source. (I.e. start from control panel when remote control is selected). |
Give start command from correct control source as configured in menu [2151] and [2152]. |
| 3 | The motor jerks etc. | When starting, motor reaches full speed but it jerks or vibrates. |
If “Torque control” is selected, it is necessary to input motor data into the system. |
Configure nominal motor data in menu group [220]. Select the proper torque control alternative in menu [331] (linear or square) according to the load characteristic. Select a correct initial- and end torque at start in menus [332] and [333]. |
| 4 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Start time too short. | Increase start time [336]. |
| 5 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | If voltage control is used as start method, the initial voltage at start may be too low. Starting voltage incorrectly set. |
Adjust initial voltage at start [334]. |
| 6 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Motor too small in relation to rated current of softstarter. |
Use a smaller model of the softstarter. |
| 7 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Motor too large in relation to load of softstarter. |
Use larger model of softstarter. |
| 8 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Starting voltage not set correctly. |
Readjust the start ramp. |
| 9 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Select the current limit function. |
| 10 | ⟦null: no independent source value⟧ | Starting or stopping time too long. |
Ramp times not set correctly. | Readjust the start and/or stop ramp time. |
| 11 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Motor too large or too small in relation to load. |
Change to another motor size. |
| 12 | The monitor function does not work. |
No or false alarm or pre-alarm. | It is necessary to input nominal motor data for this function. Set alarm levels not valid. |
Input nominal motor data in menus [221]-[228]. Adjust alarm levels and response delays. |
| 13 | The alarm can not be reset. |
⟦blank source cell⟧ | ⟦blank source cell⟧ | Check reset control in menu [216]. The alarm can only be reset if the alarm condition is removed. e.g. PTC, PT100 or heatsink temperature alarm can only be reset after the temperature is decreased. |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 141
Manual reference: physical PDF page 141. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
12.
Options
The available standard options are briefly described here.
Some of the options have their own instruction or
installation manual. For more information please contact
your supplier.
12.1
External control panel
These options may be useful, for example for mounting
control panel in a cabinet door (Fig. 84). Maximum distance
between softstarter and external control panel is 3 metres.
Fig. 84 External control panel in mounting cassette.
12.2
EmoSoftCom
EmoSoftCom is an optional software that runs on a personal
computer. It can also be used to load parameter settings
from the softstarter to the PC for backup and printing.
Recording can be made in oscilloscope mode. Please contact
CG Drives & Automation sales for further information.
12.3
I/O Board
Each I/O option board 2.0 provides three extra relay outputs
and three extra isolated digital inputs (24V). This option is
described in a separate manual. Maximum two option
boards can be mounted (I/O or PTC/PT100)
12.4
PTC/PT100
The PTC/PT100 2.0 option board for connecting motor
thermistors and max 3 PT100 elements to the softstarter is
12.5
Serial communication
and fieldbus
For communication with the softstarter there are several
option modules. There are different options for Fieldbus
communication and one serial communication option with
RS485 interface which has galvanic isolation. These options
are described in a separate manual.
NOTE: Emotron TSA softstarters have as standard
coated control boards and coated option boards.
RITTAL
Softstarter
cabinet
Fig84: softstarter cabinet and external control panel in mounting cassette. Connection illustration only; dimensions not inferred.
Options part numbers; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Options part numbers — PDF page 141
| Source row | Part number | Description |
|---|---|---|
| 1 | 01-3876-51 | I/O option board 2.0 |
Options part numbers — PDF page 141
| Source row | Part number | Description |
|---|---|---|
| 1 | 01-5406-00 | Panel kit complete including panel |
Options part numbers — PDF page 141
| Source row | Part number | Description |
|---|---|---|
| 1 | 01-3876-58 | PTC/PT100 2.0 option board |
Options part numbers — PDF page 141
| Source row | Part number | Description |
|---|---|---|
| 1 | 01-5385-54 | TSA Isolated RS485 module |
| 2 | 01-5385-55 | TSA Profibus module |
| 3 | 01-5385-56 | TSA DeviceNet module |
| 4 | 01-5385-59 | TSA Modbus/TCP module |
| 5 | 01-5385-60 | TSA EtherCAT module |
| 6 | 01-5385-61 01-5385-62 |
TSA Profinet IO 1-port module TSA Profinet IO 2-port module |
| 7 | 01-5385-63 | TSA Isolated USB module |
Manual — FOOTER_ONLY_PAGE — page 142
Manual reference: physical PDF page 142. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 138 | Options | CG Drives & Automation 01-5980-01r00 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 143
Manual reference: physical PDF page 143. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13.
Technical data
1)
Normal duty: Start current = 3 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour,
Heavy duty: Start current = 5 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour.
2) Fuse data for Semi-conductor fuses, see Table 41.
3) H1=Height of enclosure, H2= Total height.
Table 37
Table 38
Table37 model and duty ratings; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Shared source cells (coordinates refer to this table):
-
row 4, column 2, row 4, column 3, row 4, column 4, row 4, column 5, row 4, column 6, row 4, column 7 share the source cell at row 4, column 1. Read its current text above; the child slots remain unpopulated.
-
row 9, column 2, row 9, column 3, row 9, column 4, row 9, column 5, row 9, column 6, row 9, column 7 share the source cell at row 9, column 1. Read its current text above; the child slots remain unpopulated.
-
row 10, column 3 share the source cell at row 10, column 2. Read its current text above; the child slots remain unpopulated.
-
row 10, column 5 share the source cell at row 10, column 4. Read its current text above; the child slots remain unpopulated.
-
row 10, column 7 share the source cell at row 10, column 6. Read its current text above; the child slots remain unpopulated.
-
row 11, column 3 share the source cell at row 11, column 2. Read its current text above; the child slots remain unpopulated.
-
row 11, column 5 share the source cell at row 11, column 4. Read its current text above; the child slots remain unpopulated.
-
row 11, column 7 share the source cell at row 11, column 6. Read its current text above; the child slots remain unpopulated.
-
row 12, column 3 share the source cell at row 12, column 2. Read its current text above; the child slots remain unpopulated.
-
row 12, column 5 share the source cell at row 12, column 4. Read its current text above; the child slots remain unpopulated.
-
row 12, column 7 share the source cell at row 12, column 6. Read its current text above; the child slots remain unpopulated.
-
row 13, column 3 share the source cell at row 13, column 2. Read its current text above; the child slots remain unpopulated.
-
row 13, column 5 share the source cell at row 13, column 4. Read its current text above; the child slots remain unpopulated.
-
row 13, column 7 share the source cell at row 13, column 6. Read its current text above; the child slots remain unpopulated.
-
row 14, column 3 share the source cell at row 14, column 2. Read its current text above; the child slots remain unpopulated.
-
row 14, column 5 share the source cell at row 14, column 4. Read its current text above; the child slots remain unpopulated.
-
row 14, column 7 share the source cell at row 14, column 6. Read its current text above; the child slots remain unpopulated.
-
row 15, column 3 share the source cell at row 15, column 2. Read its current text above; the child slots remain unpopulated.
-
row 15, column 5 share the source cell at row 15, column 4. Read its current text above; the child slots remain unpopulated.
-
row 15, column 7 share the source cell at row 15, column 6. Read its current text above; the child slots remain unpopulated.
Table38 model and duty ratings; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Table37 model and duty ratings — PDF page 143
| Source row | Parameter / units | TSA52-016 — Normal | TSA52-016 — Heavy | TSA52-022 — Normal | TSA52-022 — Heavy | TSA52-030 — Normal | TSA52-030 — Heavy |
|---|---|---|---|---|---|---|---|
| 1 | Rated current I [A] n_soft |
16 | 10 | 22 | 12 | 30 | 18 |
| 2 | Motor size P 400 V [kW] n_mot |
7.5 | 4 | 11 | 5.5 | 15 | 7.5 |
| 3 | Motor size P 460 V [hp] n_mot |
10 | 5 | 15 | 7.5 | 20 | 10 |
| 4 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 5 | Recommended load fuses [A](2) | 20 | 20 | 25 | 25 | 35 | 35 |
| 6 | Power loss at rated motor power, bypass mode [W] |
20 | 20 | 20 | 20 | 20 | 20 |
| 7 | Average power loss if 10 starts/hour [W] | 20 | 21 | 21 | 22 | 21 | 23 |
| 8 | Power consumption control supply [VA] | 20 | 20 | 20 | 20 | 20 | 20 |
| 9 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 10 | Dimensions H1/H2 x W x D [mm](3) | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ |
| 11 | Mounting position | Vertical | ⟦null: no independent source value⟧ | Vertical | ⟦null: no independent source value⟧ | Vertical | ⟦null: no independent source value⟧ |
| 12 | Weight [kg] | 5.5 | ⟦null: no independent source value⟧ | 5.5 | ⟦null: no independent source value⟧ | 5.5 | ⟦null: no independent source value⟧ |
| 13 | Busbar connection [mm] | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ |
| 14 | Cooling system | Convection | ⟦null: no independent source value⟧ | Convection | ⟦null: no independent source value⟧ | Convection | ⟦null: no independent source value⟧ |
| 15 | Protection class | IP20 | ⟦null: no independent source value⟧ | IP20 | ⟦null: no independent source value⟧ | IP20 | ⟦null: no independent source value⟧ |
Table38 model and duty ratings — PDF page 143
| Source row | Parameter / units | TSA52-036 — Normal | TSA52-036 — Heavy | TSA52-042 — Normal | TSA52-042 — Heavy | TSA52-056 — Normal | TSA52-056 — Heavy |
|---|---|---|---|---|---|---|---|
| 1 | Rated current I [A] n_soft |
36 | 21 | 42 | 25 | 56 | 33 |
| 2 | Motor size P 400 V [kW] n_mot |
18.5 | 7.5 | 22 | 11 | 30 | 15 |
| 3 | Motor size P 460 V [hp] n_mot |
25 | 15 | 30 | 20 | 40 | 25 |
| 4 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 5 | Recommended load fuses [A](2) | 40 | 40 | 50 | 50 | 63 | 63 |
| 6 | Power loss at rated motor power, bypass mode [W] |
20 | 20 | 20 | 20 | 20 | 20 |
| 7 | Average power loss if 10 starts/hour [W] | 22 | 24 | 22 | 26 | 23 | 27 |
| 8 | Power consumption control supply [VA] | 20 | 20 | 20 | 20 | 20 | 20 |
| 9 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 10 | Dimensions H1/H2 x W x D [mm](3) | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ |
| 11 | Mounting position | Vertical | ⟦null: no independent source value⟧ | Vertical | ⟦null: no independent source value⟧ | Vertical | ⟦null: no independent source value⟧ |
| 12 | Weight [kg] | 5.5 | ⟦null: no independent source value⟧ | 5.5 | ⟦null: no independent source value⟧ | 5.5 | ⟦null: no independent source value⟧ |
| 13 | Busbar connection [mm] | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ |
| 14 | Cooling system | Convection | ⟦null: no independent source value⟧ | Convection | ⟦null: no independent source value⟧ | Convection | ⟦null: no independent source value⟧ |
| 15 | Protection class | IP20 | ⟦null: no independent source value⟧ | IP20 | ⟦null: no independent source value⟧ | IP20 | ⟦null: no independent source value⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 144
Manual reference: physical PDF page 144. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
1)
Normal duty: Start current = 3 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour,
Heavy duty: Start current = 5 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour.
2) Fuse data for Semi-conductor fuses, see Table 41.
3) H1=Height of enclosure, H2= Total height.
Table 39
Table39 model and duty ratings; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Shared source cells (coordinates refer to this table):
-
row 4, column 2, row 4, column 3, row 4, column 4, row 4, column 5, row 4, column 6, row 4, column 7 share the source cell at row 4, column 1. Read its current text above; the child slots remain unpopulated.
-
row 9, column 2, row 9, column 3, row 9, column 4, row 9, column 5, row 9, column 6, row 9, column 7 share the source cell at row 9, column 1. Read its current text above; the child slots remain unpopulated.
-
row 10, column 3 share the source cell at row 10, column 2. Read its current text above; the child slots remain unpopulated.
-
row 10, column 5 share the source cell at row 10, column 4. Read its current text above; the child slots remain unpopulated.
-
row 10, column 7 share the source cell at row 10, column 6. Read its current text above; the child slots remain unpopulated.
-
row 11, column 3 share the source cell at row 11, column 2. Read its current text above; the child slots remain unpopulated.
-
row 11, column 5 share the source cell at row 11, column 4. Read its current text above; the child slots remain unpopulated.
-
row 11, column 7 share the source cell at row 11, column 6. Read its current text above; the child slots remain unpopulated.
-
row 12, column 3 share the source cell at row 12, column 2. Read its current text above; the child slots remain unpopulated.
-
row 12, column 5 share the source cell at row 12, column 4. Read its current text above; the child slots remain unpopulated.
-
row 12, column 7 share the source cell at row 12, column 6. Read its current text above; the child slots remain unpopulated.
-
row 13, column 3 share the source cell at row 13, column 2. Read its current text above; the child slots remain unpopulated.
-
row 13, column 5 share the source cell at row 13, column 4. Read its current text above; the child slots remain unpopulated.
-
row 13, column 7 share the source cell at row 13, column 6. Read its current text above; the child slots remain unpopulated.
-
row 14, column 3 share the source cell at row 14, column 2. Read its current text above; the child slots remain unpopulated.
-
row 14, column 5 share the source cell at row 14, column 4. Read its current text above; the child slots remain unpopulated.
-
row 14, column 7 share the source cell at row 14, column 6. Read its current text above; the child slots remain unpopulated.
-
row 15, column 3 share the source cell at row 15, column 2. Read its current text above; the child slots remain unpopulated.
-
row 15, column 5 share the source cell at row 15, column 4. Read its current text above; the child slots remain unpopulated.
-
row 15, column 7 share the source cell at row 15, column 6. Read its current text above; the child slots remain unpopulated.
Table39 model and duty ratings — PDF page 144
| Source row | Parameter / units | TSA52-070 — Normal | TSA52-070 — Heavy | TSA52-085 — Normal | TSA52-085 — Heavy | TSA52-100 — Normal | TSA52-100 — Heavy |
|---|---|---|---|---|---|---|---|
| 1 | Rated current I [A] n_soft |
70 | 42 | 85 | 51 | 100 | 60 |
| 2 | Motor size P 400 V [kW] n_mot |
37 | 22 | 45 | 22 | 55 | 30 |
| 3 | Motor size P 460 V [hp] n_mot |
50 | 30 | 60 | 40 | 75 | 40 |
| 4 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 5 | Recommended load fuses [A](2) | 80 | 80 | 80 | 80 | 100 | 100 |
| 6 | Power loss at rated motor power, bypass mode [W] |
25 | 25 | 25 | 25 | 25 | 25 |
| 7 | Average power loss if 10 starts/hour [W] | 33 | 44 | 37 | 51 | 38 | 55 |
| 8 | Power consumption control supply [VA] | 25 | 25 | 25 | 25 | 25 | 25 |
| 9 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 10 | Dimensions H1/H2 x W x D [mm](3) | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ | 246/296 x 126 x 188 | ⟦null: no independent source value⟧ |
| 11 | Mounting position | Vertical/Horizontal | ⟦null: no independent source value⟧ | Vertical/Horizontal | ⟦null: no independent source value⟧ | Vertical/Horizontal | ⟦null: no independent source value⟧ |
| 12 | Weight [kg] | 5.7 | ⟦null: no independent source value⟧ | 5.7 | ⟦null: no independent source value⟧ | 5.7 | ⟦null: no independent source value⟧ |
| 13 | Busbar connection [mm] | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ | 15 x 4, Cu (M6) | ⟦null: no independent source value⟧ |
| 14 | Cooling system | Fan | ⟦null: no independent source value⟧ | Fan | ⟦null: no independent source value⟧ | Fan | ⟦null: no independent source value⟧ |
| 15 | Protection class | IP20 | ⟦null: no independent source value⟧ | IP20 | ⟦null: no independent source value⟧ | IP20 | ⟦null: no independent source value⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 145
Manual reference: physical PDF page 145. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13.1 General electrical specifications
13.2 Semi-conductor fuses
Always use standard commercial fuses to protect the wiring
and prevent short circuiting. To protect the thyristors
against short-circuit currents, superfast semiconductor fuses
can be used if preferred.
Use fuses with I2t values lower or equal to Table 41.
Table 40
Parameter
Description
General
Control signal inputs
Control signal outputs
Control signal supply
Table 41
Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Technical data source table — PDF page 145
| Source row | Parameter | Description |
|---|---|---|
| 1 | Mains supply voltage | 200-525 V, +10%/-15% 200-690 V, +10%/-15% |
| 2 | Mains and Control supply frequency | 50/60 Hz, ±10% |
| 3 | Number of fully controlled phases | 3 |
| 4 | Control supply voltage | 100-240 V +10%/-15%, Single phase |
| 5 | Recommended fuse for control supply | Max 10 A |
Technical data source table — PDF page 145
| Source row | Parameter | Description |
|---|---|---|
| 1 | Digital input voltage | 0-4 V->0, 8 -27 V->1 |
| 2 | Digital input impedance to GND (0 VDC) | <3.3 VDC: 4.7 kΩ ≥3.3 VDC: 3.6 kΩ |
| 3 | Analogue input voltage/current | 0-10 V, 2-10 V, 0-20 mA, 4-20 mA |
| 4 | Analogue input impedance to GND (0 VDC) | Voltage signal 20 kΩ, Current signal 250 Ω |
Technical data source table — PDF page 145
| Source row | Parameter | Description |
|---|---|---|
| 1 | Output relays contact | 8 A, 250 VAC or 24 VDC resistive load; 3 A, 250 VAC inductive load |
| 2 | Analogue output voltage/current | 0-10 V, 2-10 V, 0-20 mA, 4-20 mA |
| 3 | Analogue output load impedance | Voltage signal min. load 700 Ω, current signal max. load 500 ΩΩ |
Technical data source table — PDF page 145
| Source row | Parameter | Description |
|---|---|---|
| 1 | +24 VDC | +24 VDC+5%. Max current 50 mA. Short circuit and overload proof. |
Technical data source table — PDF page 145
| Source row | TSA model | Semiconductor fuse A | I²t fuse at 700 V |
|---|---|---|---|
| 1 | -016 | 50 | 1,500 |
| 2 | -022 | 70 | 2,800 |
| 3 | -030 | 100 | 3,600 |
| 4 | -036 | 125 | 6,900 |
| 5 | -042 | 150 | 11,000 |
| 6 | -056 | 175 | 14,000 |
| 7 | -070 | 250 | 42,000 |
| 8 | -085 | 300 | 55,000 |
| 9 | -100 | 400 | 99,000 |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 146
Manual reference: physical PDF page 146. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13.3 Environmental conditions
13.3.1Derating at high temperature
The Emotron TSA softstarter is made for operating at
maximum 40°C ambient temperature without derating.
Above this temperature it is necessary to ensure that
insufficient cooling does not impair the performance of the
softstarter, therefore a derating is done.
At temperatures of above 40°C, the derating of the nominal
current is 2% per centigrade. The Emotron TSA softstarter
can be operated at an ambient temperature of up to 55°C, in
which case it can only be operated at 70% of the nominal
current.
Example:
A motor with the following data is going to be used in an
ambient temperature of 50°C:
Voltage: 400 V
Current: 70 A (normal duty)
Power: 37 kW
Due to the high temperature the TSA model 52-070 will no
longer be adequate for the purpose.
Derating 2%/°C is calculated for a temperature of 10°C
above the rated:
10°C x 2% = 20%
Hence the nominal current must be derated by 20%.
To select a model that is adapted to the derating demands,
the next higher rated model is checked, TSA52-085, rated
for 85 A nominal current:
85 A - (20% x 85 A) = 68 A, which is lower than the
required 70 A.
An even higher rated model is checked, TSA52-100, rated
for 100 A nominal current:
100 A - (20% x 100 A) = 80 A, which is well above the
required 70 A, and therefore TSA52-100 is the model to be
selected in this case.
WARNING!
To resist temperatures above 40°C, the clock
battery (see 3.2, page 14) must be changed
to a BR2032 type battery.
Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Normal operation
Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Storage
Shared source cells (coordinates refer to this table):
- row 7, column 2 share the source cell at row 7, column 1. Read its current text above; the child slots remain unpopulated.
Technical data source table — PDF page 146
| Source row | Condition | Specification |
|---|---|---|
| 1 | Ambient temperature | 0°C to 40°C (Max 55°C by derating 2%/°C in excess of 40°C, see 13.3.1). |
| 2 | Atmospheric pressure | 86 - 106 kPa |
| 3 | Relative humidity | Max 95%, non-condensing |
| 4 | Altitude | Max 1,000 m (Max 4,000 m by derating 1%/100 m in excess of 1,000 m; with I/O board max 2,000 m, see 13.3.2). |
| 5 | Vibrations | According to IEC 60721-3-3: Mechanical conditions, class 3M4 (2 - 9 Hz, 3.0 mm and 9 - 20 Hz, acc. 1 g (10 m/s2)) |
| 6 | Contamination | According to IEC 60721-3-3: Chemically active substances, class 3C3 (conformal coating - all printed circuit boards are coated) Mechanically active substances, class 3S1 (no sand; dust <0.01 mg/m3, deposited <0.4 mg/(m2*h)) Biological conditions, class 3B1 (no risk for harmful biological attacks - mould, fungus, animals, etc) |
| 7 | Storage | ⟦null: no independent source value⟧ |
| 8 | Ambient temperature | -25°C to +70°C |
| 9 | Atmospheric pressure | 86 - 106 kPa |
| 10 | Relative humidity | Max 95%, non-condensing |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 147
Manual reference: physical PDF page 147. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13.3.2Derating at high altitude
The Emotron TSA softstarter can operate at an altitude up
to 1,000 m without derating.
Above 1,000 m the thinner air will have several negative
effects on the performance of the softstarter, therefore a
derating is done.
For elevations in excess of 1,000 m, the derating of the
nominal current is 1% per 100 m. The Emotron TSA
softstarter can be operated up to 4,000 m, in which case it
can only be operated at 70% of the nominal current it was
originally constructed for.
Example:
A motor with the following data is going to be used at
2,100 m altitude:
Voltage: 400 V
Current: 42 A (normal duty)
Power: 22 kW
Due to the high altitude the TSA model 52-042 will no
longer be adequate for the purpose.
The derating 1%/100 m is calculated for the altitude above
the rated:
2,100 - 1,000 = 1,100 meters above rated altitude, that
gives:
(1,100 m/100 m) x 1% = 11%
Hence the nominal current must be derated by 11%.
The next higher rated model, TSA52-056, rated for 56 A
nominal current, will be derated to:
56 A - (11% x 56 A) = 49.8 A, which is well above the
required 42 A, and therefore TSA52-056 could be selected
in this case.
NOTE: If the unit has an I/O board the maximum altitude
with derating is 2,000 m.
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 148
Manual reference: physical PDF page 148. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13.4 Control power- and I/O signal connectors
Table 42
Power board connections
Table 43
Control board connections
WARNING!
The same external supply voltage level (max
24 VDC or max 250 VAC) must be used for all
three output relays (terminals 21-33).
Do not mix AC and DC voltage.
Make sure to use the same voltage level within this
terminal section, otherwise the softstarter may be
damaged.
Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Shared source cells (coordinates refer to this table):
-
row 3, column 3 share the source cell at row 2, column 3. Read its current text above; the child slots remain unpopulated.
-
row 3, column 4 share the source cell at row 2, column 4. Read its current text above; the child slots remain unpopulated.
-
row 4, column 2, row 4, column 3, row 4, column 4 share the source cell at row 4, column 1. Read its current text above; the child slots remain unpopulated.
-
row 6, column 3 share the source cell at row 5, column 3. Read its current text above; the child slots remain unpopulated.
-
row 6, column 4 share the source cell at row 5, column 4. Read its current text above; the child slots remain unpopulated.
-
row 7, column 2, row 7, column 3, row 7, column 4 share the source cell at row 7, column 1. Read its current text above; the child slots remain unpopulated.
-
row 9, column 3 share the source cell at row 8, column 3. Read its current text above; the child slots remain unpopulated.
-
row 9, column 4 share the source cell at row 8, column 4. Read its current text above; the child slots remain unpopulated.
-
row 10, column 2, row 10, column 3, row 10, column 4 share the source cell at row 10, column 1. Read its current text above; the child slots remain unpopulated.
-
row 12, column 3, row 13, column 3 share the source cell at row 11, column 3. Read its current text above; the child slots remain unpopulated.
-
row 12, column 4, row 13, column 4 share the source cell at row 11, column 4. Read its current text above; the child slots remain unpopulated.
-
row 14, column 2, row 14, column 3, row 14, column 4 share the source cell at row 14, column 1. Read its current text above; the child slots remain unpopulated.
-
row 2, column 4 share the source cell at row 1, column 4. Read its current text above; the child slots remain unpopulated.
-
row 7, column 4 share the source cell at row 6, column 4. Read its current text above; the child slots remain unpopulated.
Technical data source table — PDF page 148
| Source row | Terminal | Contact designation | Function | Electrical characteristics |
|---|---|---|---|---|
| 1 | PE | ⟦blank source cell⟧ | Protective Earth | Protective grounding |
| 2 | N | ⟦blank source cell⟧ | Control supply voltage | 100-240 VAC ±10% |
| 3 | L | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 4 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 5 | 21 | NO | Programmable relay 1. Factory setting is “Operation” with indication by closing contact on terminals 21 to 22. |
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC 8 A resistive, 250 VAC, 3 A inductive. See Warning. |
| 6 | 22 | C | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 7 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 8 | 23 | NO | Programmable relay 2. Factory setting is “Off” with indication by closing contact on terminals 23 to 24. |
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC 8 A resistive, 250 VAC, 3 A inductive. See Warning. |
| 9 | 24 | C | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 10 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 11 | 31 | NO | Programmable relay 3. Factory setting is “Trip”. Indication by closing contact on terminals 31 to 33 and opening contact on 32 to 33. |
1-pole change-over contact (NO/NC), 250 VAC 8A or 24 VDC 8A resistive, 250 VAC, 3A inductive. See Warning. |
| 12 | 32 | C | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 13 | 33 | NC | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 14 | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
| 15 | 69-70 | ⟦blank source cell⟧ | PTC Thermistor input | Alarm level 2.4 kΩ. Switch back level 2.2 kΩ. |
Technical data source table — PDF page 148
| Source row | Terminal | Contact designation | Function | Electrical characteristics |
|---|---|---|---|---|
| 1 | 11 | ⟦blank source cell⟧ | Digital input 1. Factory setting is “Run FWD” | 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec. Impedance: <3.3 VDC: 4.7 kΩ. - ≥3.3 VDC: 3.6 kΩ |
| 2 | 12 | ⟦blank source cell⟧ | Digital input 2. Factory setting is “Stop”. | ⟦null: no independent source value⟧ |
| 3 | 13 | ⟦blank source cell⟧ | Control signal supply voltage to analogue input. | +10 VDC ±5%. Max. current from +10 VDC: 10 mA. Short circuit-proof and overload-proof. |
| 4 | 14 | ⟦blank source cell⟧ | Analogue input, 0-10 V, 2-10 V, 0-20 mA and 4-20 mA/digital input. S1 jumper for U/I selection. |
Impedance to terminal 15 (0 VDC) voltage signal: 20 kΩ, current signal: 250 Ω. |
| 5 | 15 | ⟦blank source cell⟧ | GND (common) | 0 VDC signal ground |
| 6 | 16 | ⟦blank source cell⟧ | Digital input 3. Factory setting is “Set Ctrl 1” | 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec. Impedance: <3.3 VDC: 4.7 kΩ. - ≥3.3 VDC: 3.6 kΩ |
| 7 | 17 | ⟦blank source cell⟧ | Digital input 4. Factory setting is “Reset” | ⟦null: no independent source value⟧ |
| 8 | 18 | ⟦blank source cell⟧ | Control signal supply 1, voltage to digital input. | +24 VDC ±5%. Max. current from +24 VDC = 50 mA. Short circuit-proof and overload-proof. |
| 9 | 19 | ⟦blank source cell⟧ | Analogue output. Factory setting is “Current”. | Analogue output contact: 0-10 V, 2-10 V; min load impedance 700 Ω 0-20 mA and 4-20 mA; max load impedance 500 Ω |
| 10 | 20 | ⟦blank source cell⟧ | Control signal supply 2, voltage to digital input. | +24 VDC ±5%. Max. current from +24 VDC = 50 mA. Short circuit-proof and overload-proof. |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 149
Manual reference: physical PDF page 149. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Index
A
Abbreviations .....................................7
Aggressive environment conditions ..26
Alarm ...............................................45
Action ..45, 49, 63, 65, 84, 89, 90
Autoreset ..................................50
Autoset ...............................48, 87
Delay ........................................84
External ....................................88
Indication .................................45
Load monitor ...........................84
Mains .......................................89
Maximum ...........................84, 87
Minimum ...........................86, 87
Motor .......................................62
Over voltage .............................90
Phase reversal ............................91
PT100 ......................................63
PTC .........................................64
Reset .........................................50
Type .........................................45
Under voltage ...........................90
Ambient temperature below 0×C .....26
Analogue comparators ...................100
Analogue input ................................91
Configuration ...........................92
Status ......................................117
Analogue output ..............................95
Configuration ...........................96
Status ......................................118
AND operator ...............................105
Applications and functions selection 21
Autoreset ...................................52, 69
Autoset ................................48, 86, 87
B
Background theory ........................127
Bandsaw ..........................................25
Baudrate ..........................................74
Blower .............................................24
Brake ...............................................81
DC ...........................................82
Dynamic vector ........................81
Reversed current .......................81
Spinbrake .................................95
Brake chopper ................................137
Braking ............................................81
Busbar distances ...............................13
C
Cabinet mounting .............................9
CE-marking .......................................6
Centrifuge .......................................25
Checklist ..........................................29
Clock logic ....................................113
Clock settings ................................119
Clockwise rotary field ......................94
Coast ...............................................81
Com Type .......................................73
Comparator
Analogue .................................101
Digital ....................................104
Hysteresis type ........101, 102, 104
Window type ..........101, 102, 104
Comparators ..................................100
Compressor ......................................24
Connections .....................................11
Mains supply ............................29
Motor earth ..............................29
Motor output ............................29
Safety earth ...............................29
Virtual ......................................99
Control keys .....................................34
Control Panel memory .....................67
Control signals
Edge-controlled ........................60
Level-controlled ........................60
Conveyor .........................................24
Cooling ........................................9, 10
Counter-clockwise rotary field .........94
Counters ........................................112
Current ..........................................115
Current limit ....................................79
D
Date ...............................................119
DC brake .........................................82
Declaration of Conformity .................6
Default .............................................67
Definitions .........................................7
Derating
Altitude ...................................143
Temperature ...........................142
Derating at higher temperature ......142
Description ....................................127
Digital comparators ........................100
Digital inputs
Additional .................................95
Board Relay ..............................99
DigIn 1 .....................................94
DigIn 2 .....................................95
Dimensions ......................................10
Direct on-line, DOL ........................78
Dismantling and scrapping ................6
Display .............................................33
DOL ................................................78
Dynamic vector brake ................81, 82
E
Earth fault relay ................................27
ECP ...............................................137
Edge control ...............................52, 60
Electrical specifications ...................139
Emergency .........................................1
EN60204-1 ........................................6
EN61800-3 ........................................6
EN61800-5-1 .................................... 6
Enable ................................. 34, 51, 94
Energy consumption ..................... 119
ENTER key .................................... 34
Environmental conditions ............. 142
EtherCAT ..................................... 123
EXOR operator ............................. 105
Expression ..................................... 105
External Control Panel .................. 137
F
Factory settings .......................... 60, 67
Fan .................................................. 24
Fieldbus ........................... 73, 123, 137
Flip-flop
Status ..................................... 118
Flip-flops ....................................... 110
Function key ................................... 58
Function keys .................................. 34
Fuses and power losses ................... 141
G
General electrical specifications ..... 141
H
Hammer mill .................................. 25
Heatsink temperature .................... 115
Hole pattern .................................... 10
Hysteresis .............................. 100, 101
I
I/O Board ...................................... 137
I/O board status ............................ 118
I2t protection
Motor I2t Current ................... 63
Industrial Ethernet ........................ 123
Input
Logic .............................. 107, 108
Insulation test on motor .................. 26
IT earthing system ........................... 26
J
Jog ....................................... 40, 58, 83
JOG FWD key ......................... 34
JOG REV key .......................... 34
K
Keys ................................................ 34
L
Language ......................................... 57
LCD display .................................... 34
Level control ............................. 53, 60
Load default .................................... 67
Load monitor ............................ 46, 84
LOC/REM key ............................... 35
Local control ................................... 59
Logic ..................................... 100, 105
Low Voltage Directive ....................... 6
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 150
Manual reference: physical PDF page 150. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
M
Machine Directive .............................6
Mains supply ...................................29
Maintenance ..............................1, 136
Memory ...........................................42
Menu
100 ...........................................56
110 ...........................................57
234 ...........................................64
2341 .........................................64
2342 .........................................65
2343 .........................................65
235 ...........................................65
236 ...........................................66
Main menu ...............................37
Menu structure .........................37
Mixer ...............................................25
Modbus .........................................123
Modbus/TCP ........................123, 137
Monitor function
Auto set ....................................87
Motor ..........................................5, 57
Motor cos phi (power factor) ...........62
Motor data ..........................40, 42, 60
Motor poles .....................................62
Motor speed ....................................62
Motor ventilation ............................62
Mounting ..........................................9
Mounting schemes ...........................10
N
Nominal data ...................................61
Normal Load ...................................84
Normal load ....................................88
O
Operation ................................57, 114
Operation above 1000 m .................26
Options .........................................137
Brake chopper ........................137
External Control Panel (ECP) 137
I/O Board ...............................137
OR operator ..................................105
Over voltage ....................................90
P
Parameter sets ............................41, 66
Configuration ...........................42
Copy ........................................43
Copy settings ............................67
Default values ...........................67
DigIn .......................................95
Load settings .............................68
Motor .................................42, 60
PCB Terminals ........................15, 144
Phase compensation capacitor ............1
Phase loss .........................................65
Phase reversal ...................................91
Phase sequence .........................91, 115
Planer ..............................................24
Power- and signal connectors .........144
Product standard, EMC .....................6
Protection class ................................10
PT100 ..............................................64
PT100 temperature ........................115
PTC .................................................64
Q
Quick Setup Guide ............................5
R
Reduced voltage starting ................128
Relay output ....................................97
Relay 1 ......................................97
Relay 2 ......................................99
Relay 3 ......................................99
Status ......................................117
Remote control ................................51
Reset ................................................58
Resolution ........................................56
Reversed current brake ...............81, 82
Rock crusher ....................................25
Rotor ...............................................64
RS232/485 .......................................73
RUN ................................................34
Run command .................................34
Run time ........................................119
Running motors connected in
parallel .............................................26
Running motors linked together ......26
S
Safety .................................................1
Semi-conductor fuses .....................144
Service information ........................121
Set/reset delay ................................104
Shaft power ..............................47, 114
Shaft torque ...................................114
Shielded motor cable ........................26
Signal priority ..................................40
Small motor or low load ...................26
Soft trip ...........................................45
Softstarter rating ..............................21
Software .........................................121
Spare parts .........................................1
Special conditions ............................26
Spinbrake ...................................39, 95
SR Flip-flops ..................................110
Standards ...................................6, 144
Start limitation .................................64
Start right/left functionality ..............19
Start settings ....................................78
Starting with counter-clockwise
rotating loads ...................................26
Status .............................................116
Status indications .............................33
Step-up transformer for high
voltage motor ...................................26
Stop command .................................94
Stop settings .....................................80
STOP/RESET key ...........................34
T
Technical data ............................... 139
The Application Functions List ....... 23
Thermal capacity ............... 63, 69, 115
Thermal motor protection ... 33, 63, 69
Time ............................................. 119
Time to next start .......................... 118
Timer
logic ....................................... 109
status ...................................... 118
Toggle ............................................. 58
Toggle Key ...................................... 35
Torque
Actual ..................................... 114
Analogue output ...................... 95
Boost ........................................ 80
Braking .................................... 82
Control .............................. 78, 80
Initial ....................................... 78
Ramp ....................................... 78
Shaft ...................................... 114
Tightening ............................... 12
Units ........................................ 60
Torque control .............................. 132
Trip ........................................... 34, 45
Trip Message log ........................... 120
TSA Data ...................................... 121
Type code number ............................ 5
U
Unit ................................................ 76
Unit name ..................................... 122
Unlock Code ................................... 59
V
Ventilation ...................................... 62
Virtual I/O ...................................... 99
Voltage .......................................... 115
Voltage control .......................... 78, 81
Voltage unbalance ........................... 89
W
Warning .............................. 1, 45, 116
Weekday ....................................... 119
Weight ............................................ 10
Wireless connection ......................... 99
Wiring examples .............................. 16
Adjacent source context — repeated to preserve continuation:
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 151
Manual reference: physical PDF page 151. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1: Menu List
This is a list of the Emotron TSA menu parameters and their
factory settings, along with communication settings for the
most important bus formats.
Complete lists with communication data and parameter set
information could be downloaded from www. cgglobal.com
or www.emotron.com.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 100 StartWindow; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 110 1st Line; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 120 2nd Line; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 200 Main Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 210 Operation; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 211 Language; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 212 Select Motor; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 215 Action Ctrl; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 2151 Run/Stp Ctr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 2152 JogCtrl; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 216 Reset Ctrl; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 217 Key Func; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2171 FunctionKey; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2173 LocRunCtrl; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2174 FWD key; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2175 REV key; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 218 Lock Code?; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 219 Rotation; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 21A Level/Edge; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 21C Units; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 220 Motor Data; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 221 Motor Volts; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 222 Motor Freq; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 223 Motor Power; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 224 Motor Curr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 225 Motor Speed; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 226 Motor Poles; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 227 Motor Cosφ; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 228 Motor Vent; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 230 Mot Protect; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 231 Mot I²t Alrm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2311 Mot I²t AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2312 MotI²tCurr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2313 MotI²tClass; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2314 Used Th Cap; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 232 PT100 Alarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 2321 PT100 AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 2322 Motor Class; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 2323 PT100Inputs; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 233 PTC Alarm; displayed row association 233 PTC Alarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 233 PTC Alarm; displayed row association 2331 PTC AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 233 PTC Alarm; displayed row association 2332 PTC Inputs; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 1, column 3 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 1, column 5, row 1, column 6 share the source cell at row 1, column 4. Read its current text above; the child slots remain unpopulated.
-
row 4, column 3 share the source cell at row 4, column 2. Read its current text above; the child slots remain unpopulated.
-
row 4, column 5, row 4, column 6 share the source cell at row 4, column 4. Read its current text above; the child slots remain unpopulated.
-
row 5, column 3 share the source cell at row 5, column 2. Read its current text above; the child slots remain unpopulated.
-
row 5, column 5, row 5, column 6 share the source cell at row 5, column 4. Read its current text above; the child slots remain unpopulated.
-
row 8, column 3, row 8, column 4, row 8, column 5, row 8, column 6 share the source cell at row 8, column 2. Read its current text above; the child slots remain unpopulated.
-
row 12, column 3, row 12, column 4, row 12, column 5, row 12, column 6 share the source cell at row 12, column 2. Read its current text above; the child slots remain unpopulated.
-
row 21, column 3 share the source cell at row 21, column 2. Read its current text above; the child slots remain unpopulated.
-
row 21, column 5, row 21, column 6 share the source cell at row 21, column 4. Read its current text above; the child slots remain unpopulated.
-
row 30, column 3 share the source cell at row 30, column 2. Read its current text above; the child slots remain unpopulated.
-
row 30, column 5, row 30, column 6 share the source cell at row 30, column 4. Read its current text above; the child slots remain unpopulated.
-
row 31, column 3, row 31, column 4, row 31, column 5, row 31, column 6 share the source cell at row 31, column 2. Read its current text above; the child slots remain unpopulated.
-
row 36, column 3, row 36, column 4, row 36, column 5, row 36, column 6 share the source cell at row 36, column 2. Read its current text above; the child slots remain unpopulated.
-
row 40, column 3, row 40, column 4, row 40, column 5, row 40, column 6 share the source cell at row 40, column 2. Read its current text above; the child slots remain unpopulated.
Adjacent source context — repeated to preserve continuation:
Appendix 1 menu list — PDF page 151
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 100 | StartWindow | ⟦null: no independent source value⟧ | 9999 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 56 |
| 2 | 110 | 1st Line | El Power | 43001 | UInt | UInt | ⟦blank source cell⟧ |
| 3 | 120 | 2nd Line | Current | 43002 | UInt | UInt | ⟦blank source cell⟧ |
| 4 | 200 | Main Setup | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 57 |
| 5 | 210 | Operation | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 57 |
| 6 | 211 | Language | English | 43011 | UInt | UInt | ⟦blank source cell⟧ |
| 7 | 212 | Select Motor | M1 | 43012 | UInt | UInt | ⟦blank source cell⟧ |
| 8 | 215 | Action Ctrl | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 9 | 2151 | Run/Stp Ctr | Remote | 43015 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | 2152 | JogCtrl | Remote | 43008 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | 216 | Reset Ctrl | Remote+Keyb | 43016 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | 217 | Key Func | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 13 | 2171 | FunctionKey | Toggle | 43735 | UInt | UInt | ⟦blank source cell⟧ |
| 14 | 2173 | LocRunCtrl | Keyboard | 43010 | UInt | UInt | ⟦blank source cell⟧ |
| 15 | 2174 | FWD key | FWD | 43736 | UInt | UInt | ⟦blank source cell⟧ |
| 16 | 2175 | REV key | Off | 43737 | UInt | UInt | ⟦blank source cell⟧ |
| 17 | 218 | Lock Code? | 0 | 43018 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 18 | 219 | Rotation | FWD | 43019 | UInt | UInt | ⟦blank source cell⟧ |
| 19 | 21A | Level/Edge | Edge | 43020 | UInt | UInt | ⟦blank source cell⟧ |
| 20 | 21C | Units | SI | 43750 | UInt | UInt | ⟦blank source cell⟧ |
| 21 | 220 | Motor Data | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 60 |
| 22 | 221 | Motor Volts | [Motor] V | 43041 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 23 | 222 | Motor Freq | 50Hz | 43042 | Long, 1=1Hz | EInt | ⟦blank source cell⟧ |
| 24 | 223 | Motor Power | [Motor] W | 43043 | Long, 1=1W | EInt | ⟦blank source cell⟧ |
| 25 | 224 | Motor Curr | [Motor] A | 43044 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 26 | 225 | Motor Speed | [Motor] rpm | 43045 | UInt, 1=1rpm | UInt | ⟦blank source cell⟧ |
| 27 | 226 | Motor Poles | [Motor] | 43046 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 28 | 227 | Motor Cosφ | [Motor] | 43047 | Long, 1=0.01 | EInt | ⟦blank source cell⟧ |
| 29 | 228 | Motor Vent | Self | 43048 | UInt | UInt | ⟦blank source cell⟧ |
| 30 | 230 | Mot Protect | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 62 |
| 31 | 231 | Mot I²t Alrm | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 32 | 2311 | Mot I²t AA | Soft Trip | 43061 | UInt | UInt | ⟦blank source cell⟧ |
| 33 | 2312 | MotI²tCurr | 100% | 43062 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 34 | 2313 | MotI²tClass | 10 | 43758 | UInt | UInt | ⟦blank source cell⟧ |
| 35 | 2314 | Used Th Cap | ⟦blank source cell⟧ | 31021 | Long, 1=0.1% | EInt | ⟦blank source cell⟧ |
| 36 | 232 | PT100 Alarm | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 37 | 2321 | PT100 AA | No action | 43064 | UInt | UInt | ⟦blank source cell⟧ |
| 38 | 2322 | Motor Class | F 140°C | 43065 | UInt | UInt | ⟦blank source cell⟧ |
| 39 | 2323 | PT100Inputs | PT100 1-3 | 43761 | UInt | UInt | ⟦blank source cell⟧ |
| 40 | 233 | PTC Alarm | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 41 | 2331 | PTC AA | No action | 43762 | UInt | UInt | ⟦blank source cell⟧ |
| 42 | 2332 | PTC Inputs | PbPTC | 43763 | UInt | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 152
Manual reference: physical PDF page 152. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 234 StartLimit; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2341 StartLim AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2342 Starts/h; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2343 MinTBtwStrt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2344 TimTNxtStrt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 235 SnglPhLossAA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 236 CurrLim AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 240 Set Handling; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 241 Select Set; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 242 Copy Set; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 243 Default>Set; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 244 Copy to CP; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 245 Load from CP; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 250 Autoreset; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 251 AutorstAtt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2511 AllowedArst; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2512 ActualArst; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 252 MotProtArst; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2521 Motor I²t; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2522 PT100; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2523 PTC; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2524 LockedRotor; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2525 Curr Lim; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 253 ComErrArst; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 254 ProcProtArst; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2541 MaxAlarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2542 MaxPAlarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2543 MinPAlarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2544 MinAlarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2549 Ext Alarm 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 254A Ext Alarm 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 255 SoftStrtProt; displayed row association 255 SoftStrtProt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 255 SoftStrtProt; displayed row association 2551 Over temp; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 255 SoftStrtProt; displayed row association 2552 Start limit; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 256 MainsFailure; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2561 Phase input; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2562 Volt Unbal; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2563 OverVolt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2564 Undervolt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 260 Serial Com; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 261 Com Type; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 262 Modbus RTU; displayed row association 262 Modbus RTU; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 262 Modbus RTU; displayed row association 2621 Baudrate; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 262 Modbus RTU; displayed row association 2622 Address; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 263 Fieldbus; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2631 Address; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2632 PrData Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2633 Read/Write; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2634 AddPrValues; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 1, column 3, row 1, column 4, row 1, column 5, row 1, column 6 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 8, column 3 share the source cell at row 8, column 2. Read its current text above; the child slots remain unpopulated.
-
row 8, column 5, row 8, column 6 share the source cell at row 8, column 4. Read its current text above; the child slots remain unpopulated.
-
row 14, column 3 share the source cell at row 14, column 2. Read its current text above; the child slots remain unpopulated.
-
row 14, column 5, row 14, column 6 share the source cell at row 14, column 4. Read its current text above; the child slots remain unpopulated.
-
row 15, column 3, row 15, column 4, row 15, column 5, row 15, column 6 share the source cell at row 15, column 2. Read its current text above; the child slots remain unpopulated.
-
row 25, column 3, row 25, column 4, row 25, column 5, row 25, column 6 share the source cell at row 25, column 2. Read its current text above; the child slots remain unpopulated.
-
row 32, column 3, row 32, column 4, row 32, column 5, row 32, column 6 share the source cell at row 32, column 2. Read its current text above; the child slots remain unpopulated.
-
row 35, column 3, row 35, column 4, row 35, column 5, row 35, column 6 share the source cell at row 35, column 2. Read its current text above; the child slots remain unpopulated.
-
row 40, column 3 share the source cell at row 40, column 2. Read its current text above; the child slots remain unpopulated.
-
row 40, column 5, row 40, column 6 share the source cell at row 40, column 4. Read its current text above; the child slots remain unpopulated.
-
row 42, column 3, row 42, column 4, row 42, column 5, row 42, column 6 share the source cell at row 42, column 2. Read its current text above; the child slots remain unpopulated.
-
row 45, column 3, row 45, column 4, row 45, column 5, row 45, column 6 share the source cell at row 45, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 152
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 234 | StartLimit | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 2 | 2341 | StartLim AA | No action | 43751 | UInt | UInt | ⟦blank source cell⟧ |
| 3 | 2342 | Starts/h | 10 | 43752 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 4 | 2343 | MinTBtwStrt | Off | 43753 | UInt, 1=1min | UInt | ⟦blank source cell⟧ |
| 5 | 2344 | TimTNxtStrt | min | 43754 | UInt, 1=1min | UInt | ⟦blank source cell⟧ |
| 6 | 235 | SnglPhLossAA | Hard Trip | 43755 | UInt | UInt | ⟦blank source cell⟧ |
| 7 | 236 | CurrLim AA | Hard Trip | 43756 | UInt | UInt | ⟦blank source cell⟧ |
| 8 | 240 | Set Handling | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 69 |
| 9 | 241 | Select Set | A | 43022 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | 242 | Copy Set | A>B | 43021 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | 243 | Default>Set | A | 43023 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | 244 | Copy to CP | No Copy | 43024 | UInt | UInt | ⟦blank source cell⟧ |
| 13 | 245 | Load from CP | No Copy | 43025 | UInt | UInt | ⟦blank source cell⟧ |
| 14 | 250 | Autoreset | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 69 |
| 15 | 251 | AutorstAtt | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 16 | 2511 | AllowedArst | Off | 43071 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 17 | 2512 | ActualArst | 0 | 43069 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 18 | 252 | MotProtArst | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 19 | 2521 | Motor I²t | Off | 43073 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 20 | 2522 | PT100 | Off | 43078 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 21 | 2523 | PTC | Off | 43084 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 22 | 2524 | LockedRotor | Off | 43086 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 23 | 2525 | Curr Lim | Off | 43772 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 24 | 253 | ComErrArst | Off | 43089 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 25 | 254 | ProcProtArst | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 26 | 2541 | MaxAlarm | Off | 43093 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 27 | 2542 | MaxPAlarm | Off | 43099 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 28 | 2543 | MinPAlarm | Off | 43070 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 29 | 2544 | MinAlarm | Off | 43091 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 30 | 2549 | Ext Alarm 1 | Off | 43080 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 31 | 254A | Ext Alarm 2 | Off | 43097 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 32 | 255 | SoftStrtProt | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 33 | 2551 | Over temp | Off | 43072 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 34 | 2552 | Start limit | Off | 43771 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 35 | 256 | MainsFailure | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 36 | 2561 | Phase input | Off | 43773 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 37 | 2562 | Volt Unbal | Off | 43096 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 38 | 2563 | OverVolt | Off | 43077 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 39 | 2564 | Undervolt | Off | 43088 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 40 | 260 | Serial Com | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 73 |
| 41 | 261 | Com Type | RS232 | 43031 | UInt | UInt | ⟦blank source cell⟧ |
| 42 | 262 | Modbus RTU | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 43 | 2621 | Baudrate | 9600 | 43032 | UInt | UInt | ⟦blank source cell⟧ |
| 44 | 2622 | Address | 1 | 43033 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 45 | 263 | Fieldbus | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 46 | 2631 | Address | 62 | 43034 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 47 | 2632 | PrData Mode | Basic | 43035 | UInt | UInt | ⟦blank source cell⟧ |
| 48 | 2633 | Read/Write | RW | 43036 | UInt | UInt | ⟦blank source cell⟧ |
| 49 | 2634 | AddPrValues | 0 | 43039 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 153
Manual reference: physical PDF page 153. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 264 Com Fault; displayed row association 264 Com Fault; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 264 Com Fault; displayed row association 2641 ComFltAA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 264 Com Fault; displayed row association 2642 ComFlt Time; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 265 Ethernet; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2651 IP Address; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2652 MAC Address; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2653 Subnet Mask; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2654 Gateway; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2655 DHCP; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266 FB Signal; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2661 FB Signal 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2662 FB Signal 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2663 FB Signal 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2664 FB Signal 4; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2665 FB Signal 5; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2666 FB Signal 6; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2667 FB Signal 7; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2668 FB Signal 8; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2669 FB Signal 9; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266A FB Signal10; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266B FB Signal11; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266C FB Signal12; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266D FB Signal13; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266E FB Signal14; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266F FB Signal15; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266G FB Signal16; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 269 FB Status; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2691 Board Type; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2692 SUP-bit; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2693 State FB; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2694 Serial Nbr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2695 FirmwareVer; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2696 CRC errors; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2697 MSG errors; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2698 TOUT ctr; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 1, column 3, row 1, column 4, row 1, column 5, row 1, column 6 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 4, column 3, row 4, column 4, row 4, column 5, row 4, column 6 share the source cell at row 4, column 2. Read its current text above; the child slots remain unpopulated.
-
row 24, column 3, row 24, column 4, row 24, column 5, row 24, column 6 share the source cell at row 24, column 2. Read its current text above; the child slots remain unpopulated.
-
row 41, column 3, row 41, column 4, row 41, column 5, row 41, column 6 share the source cell at row 41, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 153
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 264 | Com Fault | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 74 |
| 2 | 2641 | ComFltAA | No action | 43037 | UInt | UInt | ⟦blank source cell⟧ |
| 3 | 2642 | ComFlt Time | 0,5s | 43038 | Long, 1=0.1s | EInt | ⟦blank source cell⟧ |
| 4 | 265 | Ethernet | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 75 |
| 5 | 2651 | IP Address | 0.0.0.0 | 42701 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42702 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42703 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42704 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 9 | 2652 | MAC Address | 000000000000 | 42705 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 000000000000 | 42706 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 11 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 000000000000 | 42707 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 000000000000 | 42708 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 000000000000 | 42709 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 000000000000 | 42710 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 15 | 2653 | Subnet Mask | 0.0.0.0 | 42711 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42712 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42713 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42714 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 19 | 2654 | Gateway | 0.0.0.0 | 42715 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42716 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42717 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0.0.0.0 | 42718 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 23 | 2655 | DHCP | Off | 42719 | UInt | UInt | ⟦blank source cell⟧ |
| 24 | 266 | FB Signal | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 75 |
| 25 | 2661 | FB Signal 1 | 0 | 42801 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 26 | 2662 | FB Signal 2 | 0 | 42802 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 27 | 2663 | FB Signal 3 | 0 | 42803 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 28 | 2664 | FB Signal 4 | 0 | 42804 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 29 | 2665 | FB Signal 5 | 0 | 42805 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 30 | 2666 | FB Signal 6 | 0 | 42806 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 31 | 2667 | FB Signal 7 | 0 | 42807 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 32 | 2668 | FB Signal 8 | 0 | 42808 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 33 | 2669 | FB Signal 9 | 0 | 42809 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 34 | 266A | FB Signal10 | 0 | 42810 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 35 | 266B | FB Signal11 | 0 | 42811 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 36 | 266C | FB Signal12 | 0 | 42812 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 37 | 266D | FB Signal13 | 0 | 42813 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 38 | 266E | FB Signal14 | 0 | 42814 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 39 | 266F | FB Signal15 | 0 | 42815 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 40 | 266G | FB Signal16 | 0 | 42816 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 41 | 269 | FB Status | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 75 |
| 42 | 2691 | Board Type | ⟦blank source cell⟧ | 31081 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 43 | 2692 | SUP-bit | ⟦blank source cell⟧ | 31082 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 44 | 2693 | State FB | ⟦blank source cell⟧ | 31083 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 45 | 2694 | Serial Nbr | ⟦blank source cell⟧ | 31084 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 46 | 2695 | FirmwareVer | ⟦blank source cell⟧ | 31085 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 47 | 2696 | CRC errors | ⟦blank source cell⟧ | 31086 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 48 | 2697 | MSG errors | ⟦blank source cell⟧ | 31087 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 49 | 2698 | TOUT ctr | ⟦blank source cell⟧ | 31088 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 154
Manual reference: physical PDF page 154. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 2699 FB Input; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 269A FB Output; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 269B Last instno; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 300 Process; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 310 ProcessValue; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 320 Proc Setting; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 321 Proc Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 322 Proc Unit; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 323 User Unit; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 324 Process Min; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 325 Process Max; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 330 StartSetting; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 331 Start Method; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 332 Init Torque; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 333 EndTorqueSt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 334 Init Volt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 335 Curr Limit; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 336 Start Time; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 337 Torque Boost; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 3371 TB CurrLim; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 3372 TB Time; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 340 StopSetting; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 341 Stop Method; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 342 EndTorqueStp; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 343 StepDwnVolt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 344 BrakeMethod; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 345 Stop Time; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 346 RevC Brk Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 347 Brk Strength; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 348 DCB Strength; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 349 SwitchToDCB; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 34A DCBrkPhases; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 350 Jog; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 351 JogSpd FWD; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 352 JogSpd REV; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 400 Monitor/Prot; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 410 Load Monitor; displayed row association 410 Load Monitor; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 411 Max Alarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 4111 MaxAlarmAct; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 4112 MaxAlarmLev; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 4113 MaxAlarmDel; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 4, column 3 share the source cell at row 4, column 2. Read its current text above; the child slots remain unpopulated.
-
row 4, column 5, row 4, column 6 share the source cell at row 4, column 4. Read its current text above; the child slots remain unpopulated.
-
row 6, column 3, row 6, column 4, row 6, column 5, row 6, column 6 share the source cell at row 6, column 2. Read its current text above; the child slots remain unpopulated.
-
row 17, column 5, row 17, column 6 share the source cell at row 17, column 4. Read its current text above; the child slots remain unpopulated.
-
row 24, column 3, row 24, column 4, row 24, column 5, row 24, column 6 share the source cell at row 24, column 2. Read its current text above; the child slots remain unpopulated.
-
row 27, column 5, row 27, column 6 share the source cell at row 27, column 4. Read its current text above; the child slots remain unpopulated.
-
row 38, column 5, row 38, column 6 share the source cell at row 38, column 4. Read its current text above; the child slots remain unpopulated.
-
row 41, column 5, row 41, column 6 share the source cell at row 41, column 4. Read its current text above; the child slots remain unpopulated.
-
row 42, column 3, row 42, column 4, row 42, column 5, row 42, column 6 share the source cell at row 42, column 2. Read its current text above; the child slots remain unpopulated.
-
row 43, column 3, row 43, column 4, row 43, column 5, row 43, column 6 share the source cell at row 43, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 154
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 2699 | FB Input | ⟦blank source cell⟧ | 31089 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 2 | 269A | FB Output | ⟦blank source cell⟧ | 31090 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 3 | 269B | Last instno | ⟦blank source cell⟧ | 31091 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 4 | 300 | Process | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 76 |
| 5 | 310 | ProcessValue | ⟦blank source cell⟧ | 31002 | Long, 1= see Notes |
EInt | 1=0.001, 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 6 | 320 | Proc Setting | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 7 | 321 | Proc Source | Off | 43302 | UInt | UInt | ⟦blank source cell⟧ |
| 8 | 322 | Proc Unit | Off | 43303 | UInt | UInt | ⟦blank source cell⟧ |
| 9 | 323 | User Unit | 0 | 43304 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43305 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43306 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43307 | UInt | UInt | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43308 | UInt | UInt | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43309 | UInt | UInt | ⟦blank source cell⟧ |
| 15 | 324 | Process Min | 0 | 43310 | Long, 1= see Notes |
EInt | 1=0.001, 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 16 | 325 | Process Max | 10 | 43311 | Long, 1= see Notes |
EInt | 1=0.001, 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 17 | 330 | StartSetting | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 78 |
| 18 | 331 | Start Method | Lin Torq Ctr | 43701 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 19 | 332 | Init Torque | 10% | 43702 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 20 | 333 | EndTorqueSt | 150% | 43703 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 21 | 334 | Init Volt | 30% | 43704 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 22 | 335 | Curr Limit | Off | 43705 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 23 | 336 | Start Time | 10s | 43706 | UInt, 1=1s | UInt | ⟦blank source cell⟧ |
| 24 | 337 | Torque Boost | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 25 | 3371 | TB CurrLim | Off | 43707 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 26 | 3372 | TB Time | 1s | 43708 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 27 | 340 | StopSetting | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 80 |
| 28 | 341 | Stop Method | Coast | 43721 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 29 | 342 | EndTorqueStp | 0% | 43722 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 30 | 343 | StepDwnVolt | 100% | 43723 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 31 | 344 | BrakeMethod | DynVectBrk | 43724 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 32 | 345 | Stop Time | 10s | 43725 | UInt, 1=1s | UInt | ⟦blank source cell⟧ |
| 33 | 346 | RevC Brk Dly | 0,5s | 43726 | UInt, | UInt | ⟦blank source cell⟧ |
| 34 | 347 | Brk Strength | 75% | 43727 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 35 | 348 | DCB Strength | 15% | 43728 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 36 | 349 | SwitchToDCB | 30% | 43729 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 37 | 34A | DCBrkPhases | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 38 | 350 | Jog | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 83 |
| 39 | 351 | JogSpd FWD | 10% | 43731 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 40 | 352 | JogSpd REV | 10% | 43732 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 41 | 400 | Monitor/Prot | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 84 |
| 42 | 410 | Load Monitor | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 43 | 411 | Max Alarm | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 44 | 4111 | MaxAlarmAct | No action | 43775 | UInt | UInt | ⟦blank source cell⟧ |
| 45 | 4112 | MaxAlarmLev | 116% | 43776 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 46 | 4113 | MaxAlarmDel | 0,5s | 43330 | Long, 1=0.1s | EInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 155
Manual reference: physical PDF page 155. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 412 MaxPreAlarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4121 MaxPreAlAct; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4122 MaxPreAlLev; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4123 MaxPreAlDel; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 413 MinPreAlarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4131 MinPreAlAct; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4132 MinPreAlLev; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4133 MinPreAlDel; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 414 Min Alarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 4141 MinAlarmAct; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 4142 MinAlarmLev; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 4143 MinAlarmDel; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 416 Start Delay; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 417 Autoset; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4171 MaxAlarmMar; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4172 MaxPreAlMar; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4173 MinPreAlMar; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4174 MinAlarmMar; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4175 AutosetAlrm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4176 Normal Load; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 420 Process prot; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 421 Ext Alarm; displayed row association 421 Ext Alarm; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 421 Ext Alarm; displayed row association 4211 ExtAlarm1AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 421 Ext Alarm; displayed row association 4212 ExtAlarm2AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 422 Rotor Locked; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 4221 LockRot AA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 4222 LockRotTime; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 4223 LockRotCurr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 430 Mains Prot; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 431 Volt Unbal; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 4311 VoltUnbalAA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 4312 UnbalLevel; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 4313 VoltUnbDel; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 432 OverVolt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 4321 OverVoltAA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 4322 OverV Level; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 4323 OverV Del; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 433 UnderVolt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4331 UnderVoltAA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4332 UnderVLevel; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4333 UnderV Del; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 434 PhseReversal; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4341 PhaseRevAA; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4342 AllowedSequ; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 500 I/Os; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 510 An Inputs; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 511 AnIn Fc; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 512 AnIn Setup; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 1, column 3, row 1, column 4, row 1, column 5, row 1, column 6 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 9, column 3, row 9, column 4, row 9, column 5, row 9, column 6 share the source cell at row 9, column 2. Read its current text above; the child slots remain unpopulated.
-
row 14, column 3, row 14, column 4, row 14, column 5, row 14, column 6 share the source cell at row 14, column 2. Read its current text above; the child slots remain unpopulated.
-
row 21, column 5, row 21, column 6 share the source cell at row 21, column 4. Read its current text above; the child slots remain unpopulated.
-
row 22, column 3, row 22, column 4, row 22, column 5, row 22, column 6 share the source cell at row 22, column 2. Read its current text above; the child slots remain unpopulated.
-
row 25, column 3, row 25, column 4, row 25, column 5, row 25, column 6 share the source cell at row 25, column 2. Read its current text above; the child slots remain unpopulated.
-
row 29, column 5, row 29, column 6 share the source cell at row 29, column 4. Read its current text above; the child slots remain unpopulated.
-
row 30, column 3, row 30, column 4, row 30, column 5, row 30, column 6 share the source cell at row 30, column 2. Read its current text above; the child slots remain unpopulated.
-
row 34, column 3, row 34, column 4, row 34, column 5, row 34, column 6 share the source cell at row 34, column 2. Read its current text above; the child slots remain unpopulated.
-
row 38, column 3, row 38, column 4, row 38, column 5, row 38, column 6 share the source cell at row 38, column 2. Read its current text above; the child slots remain unpopulated.
-
row 45, column 5, row 45, column 6 share the source cell at row 45, column 4. Read its current text above; the child slots remain unpopulated.
-
row 46, column 5, row 46, column 6 share the source cell at row 46, column 4. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 155
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 412 | MaxPreAlarm | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 85 |
| 2 | 4121 | MaxPreAlAct | No action | 43777 | UInt | UInt | ⟦blank source cell⟧ |
| 3 | 4122 | MaxPreAlLev | 108% | 43778 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 4 | 4123 | MaxPreAlDel | 0,5s | 43331 | Long, 1=0.1s | EInt | ⟦blank source cell⟧ |
| 5 | 413 | MinPreAlarm | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 6 | 4131 | MinPreAlAct | No action | 43779 | UInt | UInt | ⟦blank source cell⟧ |
| 7 | 4132 | MinPreAlLev | 92% | 43742 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 8 | 4133 | MinPreAlDel | 0,5s | 43332 | Long, 1=0.1s | EInt | ⟦blank source cell⟧ |
| 9 | 414 | Min Alarm | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 86 |
| 10 | 4141 | MinAlarmAct | No action | 43743 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | 4142 | MinAlarmLev | 84% | 43744 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 12 | 4143 | MinAlarmDel | 0,5s | 43333 | Long, 1=0.1s | EInt | ⟦blank source cell⟧ |
| 13 | 416 | Start Delay | 10s | 43324 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 14 | 417 | Autoset | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 15 | 4171 | MaxAlarmMar | 16% | 43326 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 16 | 4172 | MaxPreAlMar | 8% | 43327 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 17 | 4173 | MinPreAlMar | 8% | 43328 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 18 | 4174 | MinAlarmMar | 16% | 43329 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 19 | 4175 | AutosetAlrm | No | 43334 | UInt | UInt | ⟦blank source cell⟧ |
| 20 | 4176 | Normal Load | Off | 43335 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 21 | 420 | Process prot | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 88 |
| 22 | 421 | Ext Alarm | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 23 | 4211 | ExtAlarm1AA | Hard Trip | 43081 | UInt | UInt | ⟦blank source cell⟧ |
| 24 | 4212 | ExtAlarm2AA | Hard Trip | 43764 | UInt | UInt | ⟦blank source cell⟧ |
| 25 | 422 | Rotor Locked | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 26 | 4221 | LockRot AA | No action | 43362 | UInt | UInt | ⟦blank source cell⟧ |
| 27 | 4222 | LockRotTime | 5,0s | 43757 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 28 | 4223 | LockRotCurr | 480% | 43759 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 29 | 430 | Mains Prot | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 89 |
| 30 | 431 | Volt Unbal | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 31 | 4311 | VoltUnbalAA | No action | 43765 | UInt | UInt | ⟦blank source cell⟧ |
| 32 | 4312 | UnbalLevel | 10% | 43560 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 33 | 4313 | VoltUnbDel | 1s | 43561 | UInt, 1=1s | UInt | ⟦blank source cell⟧ |
| 34 | 432 | OverVolt | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 35 | 4321 | OverVoltAA | No action | 43766 | UInt | UInt | ⟦blank source cell⟧ |
| 36 | 4322 | OverV Level | 115% | 43562 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 37 | 4323 | OverV Del | 1s | 43563 | UInt, 1=1s | UInt | ⟦blank source cell⟧ |
| 38 | 433 | UnderVolt | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 39 | 4331 | UnderVoltAA | No action | 43767 | UInt | UInt | ⟦blank source cell⟧ |
| 40 | 4332 | UnderVLevel | 85% | 43564 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 41 | 4333 | UnderV Del | 1s | 43565 | UInt, 1=1s | UInt | ⟦blank source cell⟧ |
| 42 | 434 | PhseReversal | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 43 | 4341 | PhaseRevAA | No action | 43768 | UInt | UInt | ⟦blank source cell⟧ |
| 44 | 4342 | AllowedSequ | L123 | 43566 | 1=1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 45 | 500 | I/Os | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 91 |
| 46 | 510 | An Inputs | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 91 |
| 47 | 511 | AnIn Fc | Process Val | 43201 | UInt | UInt | ⟦blank source cell⟧ |
| 48 | 512 | AnIn Setup | 4-20mA | 43202 | UInt | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 156
Manual reference: physical PDF page 156. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 513 AnIn Advan; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5131 AnIn Min; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5132 AnIn Max; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5134 AnIn FcMin; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5135 AnIn VaMin; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5136 AnIn FcMax; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5137 AnIn VaMax; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5139 AnIn Filt; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 513A AnIn Enabl; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 520 Dig Inputs; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 521 DigIn 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 522 DigIn 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 523 DigIn 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 524 DigIn 4; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 529 B1 DigIn 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52A B1 DigIn 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52B B1 DigIn 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52C B2 DigIn 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52D B2 DigIn 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52E B2 DigIn 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 530 An Outputs; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 531 AnOut Fc; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 532 AnOut Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 533 AnOut Advan; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5331 AnOut Min; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5332 AnOut Max; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5334 AnOutFcMin; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5335 AnOutVaMin; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5336 AnOutFcMax; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5337 AnOutVaMax; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 550 Relays; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 551 Relay 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 552 Relay 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 553 Relay 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 554 B1 Relay 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 555 B1 Relay 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 556 B1 Relay 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 557 B2 Relay 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 558 B2 Relay 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 559 B2 Relay 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D Relay Advan; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D1 Relay1 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D2 Relay2 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D3 Relay3 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D4 B1R1 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D5 B1R2 Mode; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 1, column 3, row 1, column 4, row 1, column 5, row 1, column 6 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 10, column 5, row 10, column 6 share the source cell at row 10, column 4. Read its current text above; the child slots remain unpopulated.
-
row 21, column 5, row 21, column 6 share the source cell at row 21, column 4. Read its current text above; the child slots remain unpopulated.
-
row 24, column 3, row 24, column 4, row 24, column 5, row 24, column 6 share the source cell at row 24, column 2. Read its current text above; the child slots remain unpopulated.
-
row 31, column 5, row 31, column 6 share the source cell at row 31, column 4. Read its current text above; the child slots remain unpopulated.
-
row 41, column 3, row 41, column 4, row 41, column 5, row 41, column 6 share the source cell at row 41, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 156
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 513 | AnIn Advan | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 2 | 5131 | AnIn Min | 4mA | 43203 | Long, 1=0.01 | EInt | ⟦blank source cell⟧ |
| 3 | 5132 | AnIn Max | 20mA | 43204 | Long, 1=0.01 | EInt | ⟦blank source cell⟧ |
| 4 | 5134 | AnIn FcMin | Min | 43206 | UInt | UInt | ⟦blank source cell⟧ |
| 5 | 5135 | AnIn VaMin | 0 | 43541 | Long, 1= see Notes |
EInt | 1=0.001, 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 6 | 5136 | AnIn FcMax | Max | 43207 | UInt | UInt | ⟦blank source cell⟧ |
| 7 | 5137 | AnIn VaMax | 0 | 43551 | Long, 1= see Notes |
EInt | 1=0.001, 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 8 | 5139 | AnIn Filt | 0,1s | 43209 | Long, 1= 0.001s |
EInt | ⟦blank source cell⟧ |
| 9 | 513A | AnIn Enabl | On | 43210 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | 520 | Dig Inputs | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 94 |
| 11 | 521 | DigIn 1 | Run FWD | 43241 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | 522 | DigIn 2 | Stop | 43242 | UInt | UInt | ⟦blank source cell⟧ |
| 13 | 523 | DigIn 3 | Set Ctrl 1 | 43243 | UInt | UInt | ⟦blank source cell⟧ |
| 14 | 524 | DigIn 4 | Reset | 43244 | UInt | UInt | ⟦blank source cell⟧ |
| 15 | 529 | B1 DigIn 1 | Off | 43501 | UInt | UInt | ⟦blank source cell⟧ |
| 16 | 52A | B1 DigIn 2 | Off | 43502 | UInt | UInt | ⟦blank source cell⟧ |
| 17 | 52B | B1 DigIn 3 | Off | 43503 | UInt | UInt | ⟦blank source cell⟧ |
| 18 | 52C | B2 DigIn 1 | Off | 43504 | UInt | UInt | ⟦blank source cell⟧ |
| 19 | 52D | B2 DigIn 2 | Off | 43505 | UInt | UInt | ⟦blank source cell⟧ |
| 20 | 52E | B2 DigIn 3 | Off | 43506 | UInt | UInt | ⟦blank source cell⟧ |
| 21 | 530 | An Outputs | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 95 |
| 22 | 531 | AnOut Fc | Current | 43251 | UInt | UInt | ⟦blank source cell⟧ |
| 23 | 532 | AnOut Setup | 4-20mA | 43252 | UInt | UInt | ⟦blank source cell⟧ |
| 24 | 533 | AnOut Advan | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 25 | 5331 | AnOut Min | 4mA | 43253 | Long, 1=0.01 | EInt | ⟦blank source cell⟧ |
| 26 | 5332 | AnOut Max | 20mA | 43254 | Long, 1=0.01 | EInt | ⟦blank source cell⟧ |
| 27 | 5334 | AnOutFcMin | Min | 43256 | UInt | UInt | ⟦blank source cell⟧ |
| 28 | 5335 | AnOutVaMin | 0 | 43545 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1% or 0.001 as set in [322] |
| 29 | 5336 | AnOutFcMax | Max | 43257 | UInt | UInt | ⟦blank source cell⟧ |
| 30 | 5337 | AnOutVaMax | 0 | 43555 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1% or 0.001 as set in [322] |
| 31 | 550 | Relays | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 97 |
| 32 | 551 | Relay 1 | Operation | 43273 | UInt | UInt | ⟦blank source cell⟧ |
| 33 | 552 | Relay 2 | Off | 43274 | UInt | UInt | ⟦blank source cell⟧ |
| 34 | 553 | Relay 3 | Trip | 43275 | UInt | UInt | ⟦blank source cell⟧ |
| 35 | 554 | B1 Relay 1 | Off | 43511 | UInt | UInt | ⟦blank source cell⟧ |
| 36 | 555 | B1 Relay 2 | Off | 43512 | UInt | UInt | ⟦blank source cell⟧ |
| 37 | 556 | B1 Relay 3 | Off | 43513 | UInt | UInt | ⟦blank source cell⟧ |
| 38 | 557 | B2 Relay 1 | Off | 43514 | UInt | UInt | ⟦blank source cell⟧ |
| 39 | 558 | B2 Relay 2 | Off | 43515 | UInt | UInt | ⟦blank source cell⟧ |
| 40 | 559 | B2 Relay 3 | Off | 43516 | UInt | UInt | ⟦blank source cell⟧ |
| 41 | 55D | Relay Advan | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 42 | 55D1 | Relay1 Mode | N.O | 43276 | UInt | UInt | ⟦blank source cell⟧ |
| 43 | 55D2 | Relay2 Mode | N.O | 43277 | UInt | UInt | ⟦blank source cell⟧ |
| 44 | 55D3 | Relay3 Mode | N.O | 43278 | UInt | UInt | ⟦blank source cell⟧ |
| 45 | 55D4 | B1R1 Mode | N.O | 43521 | UInt | UInt | ⟦blank source cell⟧ |
| 46 | 55D5 | B1R2 Mode | N.O | 43522 | UInt | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 157
Manual reference: physical PDF page 157. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D6 B1R3 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D7 B2R1 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D8 B2R2 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D9 B2R3 Mode; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 560 Virtual I/Os; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 561 VIO 1 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 562 VIO 1 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 563 VIO 2 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 564 VIO 2 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 565 VIO 3 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 566 VIO 3 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 567 VIO 4 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 568 VIO 4 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 569 VIO 5 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56A VIO 5 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56B VIO 6 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56C VIO 6 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56D VIO 7 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56E VIO 7 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56F VIO 8 Dest; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56G VIO 8 Source; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 600 Logic&Timers; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 610 Comparators; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 611 CA1 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6111 CA1 Value; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6112 CA1 LevelHI; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6113 CA1 LevelLO; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6114 CA1 Type; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6116 CA1 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6117 CA1 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6118 CA1 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 612 CA2 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6121 CA2 Value; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6122 CA2 LevelHI; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6123 CA2 LevelLO; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6124 CA2 Type; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6126 CA2 Set Dly; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 5, column 5, row 5, column 6 share the source cell at row 5, column 4. Read its current text above; the child slots remain unpopulated.
-
row 22, column 5, row 22, column 6 share the source cell at row 22, column 4. Read its current text above; the child slots remain unpopulated.
-
row 23, column 5, row 23, column 6 share the source cell at row 23, column 4. Read its current text above; the child slots remain unpopulated.
-
row 24, column 3, row 24, column 4, row 24, column 5, row 24, column 6 share the source cell at row 24, column 2. Read its current text above; the child slots remain unpopulated.
-
row 38, column 3, row 38, column 4, row 38, column 5, row 38, column 6 share the source cell at row 38, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 157
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 55D6 | B1R3 Mode | N.O | 43523 | UInt | UInt | ⟦blank source cell⟧ |
| 2 | 55D7 | B2R1 Mode | N.O | 43524 | UInt | UInt | ⟦blank source cell⟧ |
| 3 | 55D8 | B2R2 Mode | N.O | 43525 | UInt | UInt | ⟦blank source cell⟧ |
| 4 | 55D9 | B2R3 Mode | N.O | 43526 | UInt | UInt | ⟦blank source cell⟧ |
| 5 | 560 | Virtual I/Os | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 99 |
| 6 | 561 | VIO 1 Dest | Off | 43281 | UInt | UInt | ⟦blank source cell⟧ |
| 7 | 562 | VIO 1 Source | Off | 43282 | UInt | UInt | ⟦blank source cell⟧ |
| 8 | 563 | VIO 2 Dest | Off | 43283 | UInt | UInt | ⟦blank source cell⟧ |
| 9 | 564 | VIO 2 Source | Off | 43284 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | 565 | VIO 3 Dest | Off | 43285 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | 566 | VIO 3 Source | Off | 43286 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | 567 | VIO 4 Dest | Off | 43287 | UInt | UInt | ⟦blank source cell⟧ |
| 13 | 568 | VIO 4 Source | Off | 43288 | UInt | UInt | ⟦blank source cell⟧ |
| 14 | 569 | VIO 5 Dest | Off | 43289 | UInt | UInt | ⟦blank source cell⟧ |
| 15 | 56A | VIO 5 Source | Off | 43290 | UInt | UInt | ⟦blank source cell⟧ |
| 16 | 56B | VIO 6 Dest | Off | 43291 | UInt | UInt | ⟦blank source cell⟧ |
| 17 | 56C | VIO 6 Source | Off | 43292 | UInt | UInt | ⟦blank source cell⟧ |
| 18 | 56D | VIO 7 Dest | Off | 43293 | UInt | UInt | ⟦blank source cell⟧ |
| 19 | 56E | VIO 7 Source | Off | 43294 | UInt | UInt | ⟦blank source cell⟧ |
| 20 | 56F | VIO 8 Dest | Off | 43295 | UInt | UInt | ⟦blank source cell⟧ |
| 21 | 56G | VIO 8 Source | Off | 43296 | UInt | UInt | ⟦blank source cell⟧ |
| 22 | 600 | Logic&Timers | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 100 |
| 23 | 610 | Comparators | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 24 | 611 | CA1 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 25 | 6111 | CA1 Value | Current | 43400 | UInt | UInt | ⟦blank source cell⟧ |
| 26 | 6112 | CA1 LevelHI | 30 | 43401 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 27 | 6113 | CA1 LevelLO | 20 | 43402 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 28 | 6114 | CA1 Type | Hysteresis | 43403 | UInt | UInt | ⟦blank source cell⟧ |
| 29 | 6116 | CA1 Set Dly | 00:00:00 | 43405 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43406 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43407 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 32 | 6117 | CA1 Res Dly | 00:00:00 | 43408 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43409 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43410 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 35 | 6118 | CA1 Tmr Val | 00:00:00 | 42600 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 36 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42601 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 37 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42602 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 38 | 612 | CA2 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 104 |
| 39 | 6121 | CA2 Value | Current | 43411 | UInt | UInt | ⟦blank source cell⟧ |
| 40 | 6122 | CA2 LevelHI | 30 | 43412 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 41 | 6123 | CA2 LevelLO | 20 | 43413 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 42 | 6124 | CA2 Type | Hysteresis | 43414 | UInt | UInt | ⟦blank source cell⟧ |
| 43 | 6126 | CA2 Set Dly | 00:00:00 | 43416 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 44 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43417 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43418 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 158
Manual reference: physical PDF page 158. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6127 CA2 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6128 CA2 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 613 CA3 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6131 CA3 Value; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6132 CA3 LevelHI; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6133 CA3 LevelLO; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6134 CA3 Type; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6136 CA3 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6137 CA3 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6138 CA3 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 614 CA4 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6141 CA4 Value; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6142 CA4 LevelHI; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6143 CA4 LevelLO; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6144 CA4 Type; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6146 CA4 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6147 CA4 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6148 CA4 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 615 CD1 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6151 CD1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6152 CD1 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6153 CD1 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6154 CD1 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 616 CD2 Setup; displayed row association 616 CD2 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 616 CD2 Setup; displayed row association 6161 CD2; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 7, column 3, row 7, column 4, row 7, column 5, row 7, column 6 share the source cell at row 7, column 2. Read its current text above; the child slots remain unpopulated.
-
row 21, column 3, row 21, column 4, row 21, column 5, row 21, column 6 share the source cell at row 21, column 2. Read its current text above; the child slots remain unpopulated.
-
row 35, column 3, row 35, column 4, row 35, column 5, row 35, column 6 share the source cell at row 35, column 2. Read its current text above; the child slots remain unpopulated.
-
row 46, column 3, row 46, column 4, row 46, column 5, row 46, column 6 share the source cell at row 46, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 158
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 6127 | CA2 Res Dly | 00:00:00 | 43419 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43420 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43421 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 4 | 6128 | CA2 Tmr Val | 00:00:00 | 42603 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42604 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42605 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 7 | 613 | CA3 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 104 |
| 8 | 6131 | CA3 Value | Current | 43422 | UInt | UInt | ⟦blank source cell⟧ |
| 9 | 6132 | CA3 LevelHI | 30 | 43423 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 10 | 6133 | CA3 LevelLO | 20 | 43424 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 11 | 6134 | CA3 Type | Hysteresis | 43425 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | 6136 | CA3 Set Dly | 00:00:00 | 43427 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43428 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43429 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 15 | 6137 | CA3 Res Dly | 00:00:00 | 43430 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43431 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43432 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 18 | 6138 | CA3 Tmr Val | 00:00:00 | 42606 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42607 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42608 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 21 | 614 | CA4 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 104 |
| 22 | 6141 | CA4 Value | Current | 43433 | UInt | UInt | ⟦blank source cell⟧ |
| 23 | 6142 | CA4 LevelHI | 30 | 43434 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 24 | 6143 | CA4 LevelLO | 20 | 43435 | Long, 1= see Notes |
EInt | 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C, 1kWh, 1h or 0.001 as set in [322] |
| 25 | 6144 | CA4 Type | Hysteresis | 43436 | UInt | UInt | ⟦blank source cell⟧ |
| 26 | 6146 | CA4 Set Dly | 00:00:00 | 43438 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43439 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43440 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 29 | 6147 | CA4 Res Dly | 00:00:00 | 43441 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43442 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43443 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 32 | 6148 | CA4 Tmr Val | 00:00:00 | 42609 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42610 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42611 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 35 | 615 | CD1 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 104 |
| 36 | 6151 | CD1 | Operation | 43444 | UInt | UInt | ⟦blank source cell⟧ |
| 37 | 6152 | CD1 Set Dly | 00:00:00 | 43445 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 38 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43446 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 39 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43447 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 40 | 6153 | CD1 Res Dly | 00:00:00 | 43448 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 41 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43449 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 42 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43450 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 43 | 6154 | CD1 Tmr Val | 00:00:00 | 42612 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 44 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42613 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42614 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 46 | 616 | CD2 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 105 |
| 47 | 6161 | CD2 | DigIn 1 | 43451 | UInt | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 159
Manual reference: physical PDF page 159. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6162 CD2 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6163 CD2 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6164 CD2 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 617 CD3 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6171 CD3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6172 CD3 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6173 CD3 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6174 CD3 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 618 CD4 Setup; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6181 CD4; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6182 CD4 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6183 CD4 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6184 CD4 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 620 Logics; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 621 Logic 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6211 L1 Expr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6212 L1 Input 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6213 L1 Op 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6214 L1 Input 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6215 L1 Op 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6216 L1 Input 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6217 L1 Op 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6218 L1 Input 4; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6219 L1 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 621A L1 Res Dly; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 10, column 3, row 10, column 4, row 10, column 5, row 10, column 6 share the source cell at row 10, column 2. Read its current text above; the child slots remain unpopulated.
-
row 21, column 3, row 21, column 4, row 21, column 5, row 21, column 6 share the source cell at row 21, column 2. Read its current text above; the child slots remain unpopulated.
-
row 32, column 5, row 32, column 6 share the source cell at row 32, column 4. Read its current text above; the child slots remain unpopulated.
-
row 33, column 3, row 33, column 4, row 33, column 5, row 33, column 6 share the source cell at row 33, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 159
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 6162 | CD2 Set Dly | 00:00:00 | 43452 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43453 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43454 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 4 | 6163 | CD2 Res Dly | 00:00:00 | 43455 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43456 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43457 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 7 | 6164 | CD2 Tmr Val | 00:00:00 | 42615 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42616 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42617 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 10 | 617 | CD3 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 105 |
| 11 | 6171 | CD3 | Trip | 43458 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | 6172 | CD3 Set Dly | 00:00:00 | 43459 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43460 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43461 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 15 | 6173 | CD3 Res Dly | 00:00:00 | 43462 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43463 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43464 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 18 | 6174 | CD3 Tmr Val | 00:00:00 | 42618 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42619 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42620 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 21 | 618 | CD4 Setup | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 105 |
| 22 | 6181 | CD4 | Ready | 43465 | UInt | UInt | ⟦blank source cell⟧ |
| 23 | 6182 | CD4 Set Dly | 00:00:00 | 43466 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43467 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43468 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 26 | 6183 | CD4 Res Dly | 00:00:00 | 43469 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43470 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43471 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 29 | 6184 | CD4 Tmr Val | 00:00:00 | 42621 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42622 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42623 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 32 | 620 | Logics | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 105 |
| 33 | 621 | Logic 1 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 34 | 6211 | L1 Expr | ((1.2).3).4 | 43472 | UInt | UInt | ⟦blank source cell⟧ |
| 35 | 6212 | L1 Input 1 | CA1 | 43473 | UInt | UInt | ⟦blank source cell⟧ |
| 36 | 6213 | L1 Op 1 | & | 43474 | UInt | UInt | ⟦blank source cell⟧ |
| 37 | 6214 | L1 Input 2 | !A2 | 43475 | UInt | UInt | ⟦blank source cell⟧ |
| 38 | 6215 | L1 Op 2 | & | 43476 | UInt | UInt | ⟦blank source cell⟧ |
| 39 | 6216 | L1 Input 3 | CA3 | 43477 | UInt | UInt | ⟦blank source cell⟧ |
| 40 | 6217 | L1 Op 3 | & | 43478 | UInt | UInt | ⟦blank source cell⟧ |
| 41 | 6218 | L1 Input 4 | CA4 | 43479 | UInt | UInt | ⟦blank source cell⟧ |
| 42 | 6219 | L1 Set Dly | 00:00:00 | 43480 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 43 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 00:00:00 | 43481 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 44 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 00:00:00 | 43482 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 45 | 621A | L1 Res Dly | ⟦blank source cell⟧ | 43483 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 46 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43484 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 47 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43485 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 160
Manual reference: physical PDF page 160. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 621B L1 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 622 Logic 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6221 L2 Expr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6222 L2 Input 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6223 L2 Op 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6224 L2 Input 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6225 L2 Op 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6226 L2 Input 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6227 L2 Op 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6228 L2 Input 4; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6229 L2 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 622A L2 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 622B L2 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 623 Logic 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6231 L3 Expr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6232 L3 Input 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6233 L3 Op 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6234 L3 Input 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6235 L3 Op 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6236 L3 Input 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6237 L3 Op 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6238 L3 Input 4; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6239 L3 Set Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 623A L3 Res Dly; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 623B L3 Tmr Val; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 624 Logic 4; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6241 L4 Expr; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6242 L4 Input 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6243 L4 Op 1; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6244 L4 Input 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6245 L4 Op 2; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6246 L4 Input 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6247 L4 Op 3; blanks remain unfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6248 L4 Input 4; blanks remain unfilled
Shared source cells (coordinates refer to this table):
-
row 4, column 3, row 4, column 4, row 4, column 5, row 4, column 6 share the source cell at row 4, column 2. Read its current text above; the child slots remain unpopulated.
-
row 22, column 3, row 22, column 4, row 22, column 5, row 22, column 6 share the source cell at row 22, column 2. Read its current text above; the child slots remain unpopulated.
-
row 40, column 3, row 40, column 4, row 40, column 5, row 40, column 6 share the source cell at row 40, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 160
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 621B | L1 Tmr Val | ⟦blank source cell⟧ | 42624 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42625 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42626 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 4 | 622 | Logic 2 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 108 |
| 5 | 6221 | L2 Expr | ((1.2).3).4 | 43486 | UInt | UInt | ⟦blank source cell⟧ |
| 6 | 6222 | L2 Input 1 | CA1 | 43487 | UInt | UInt | ⟦blank source cell⟧ |
| 7 | 6223 | L2 Op 1 | & | 43488 | UInt | UInt | ⟦blank source cell⟧ |
| 8 | 6224 | L2 Input 2 | !A2 | 43489 | UInt | UInt | ⟦blank source cell⟧ |
| 9 | 6225 | L2 Op 2 | & | 43490 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | 6226 | L2 Input 3 | CA1 | 43491 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | 6227 | L2 Op 3 | & | 43492 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | 6228 | L2 Input 4 | !A2 | 43493 | UInt | UInt | ⟦blank source cell⟧ |
| 13 | 6229 | L2 Set Dly | 00:00:00 | 43494 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43495 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43496 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 16 | 622A | L2 Res Dly | 00:00:00 | 43497 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43498 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43499 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 19 | 622B | L2 Tmr Val | 00:00:00 | 42627 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42628 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42629 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 22 | 623 | Logic 3 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 108 |
| 23 | 6231 | L3 Expr | ((1.2).3).4 | 43780 | UInt | UInt | ⟦blank source cell⟧ |
| 24 | 6232 | L3 Input 1 | CA1 | 43781 | UInt | UInt | ⟦blank source cell⟧ |
| 25 | 6233 | L3 Op 1 | & | 43782 | UInt | UInt | ⟦blank source cell⟧ |
| 26 | 6234 | L3 Input 2 | !A2 | 43783 | UInt | UInt | ⟦blank source cell⟧ |
| 27 | 6235 | L3 Op 2 | & | 43784 | UInt | UInt | ⟦blank source cell⟧ |
| 28 | 6236 | L3 Input 3 | CA3 | 43785 | UInt | UInt | ⟦blank source cell⟧ |
| 29 | 6237 | L3 Op 3 | & | 43786 | UInt | UInt | ⟦blank source cell⟧ |
| 30 | 6238 | L3 Input 4 | CA4 | 43787 | UInt | UInt | ⟦blank source cell⟧ |
| 31 | 6239 | L3 Set Dly | 00:00:00 | 43788 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 32 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43789 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43790 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 34 | 623A | L3 Res Dly | 00:00:00 | 43791 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 35 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43792 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 36 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43793 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 37 | 623B | L3 Tmr Val | 00:00:00 | 42630 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 38 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42631 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 39 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42632 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 40 | 624 | Logic 4 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 108 |
| 41 | 6241 | L4 Expr | ((1.2).3).4 | 43794 | UInt | UInt | ⟦blank source cell⟧ |
| 42 | 6242 | L4 Input 1 | CA1 | 43795 | UInt | UInt | ⟦blank source cell⟧ |
| 43 | 6243 | L4 Op 1 | & | 43796 | UInt | UInt | ⟦blank source cell⟧ |
| 44 | 6244 | L4 Input 2 | !A2 | 43797 | UInt | UInt | ⟦blank source cell⟧ |
| 45 | 6245 | L4 Op 2 | & | 43798 | UInt | UInt | ⟦blank source cell⟧ |
| 46 | 6246 | L4 Input 3 | CA1 | 43799 | UInt | UInt | ⟦blank source cell⟧ |
| 47 | 6247 | L4 Op 3 | & | 43800 | UInt | UInt | ⟦blank source cell⟧ |
| 48 | 6248 | L4 Input 4 | !A2 | 43801 | UInt | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 161
Manual reference: physical PDF page 161. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 6249 L4 Set Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 624A L4 Res Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 624B L4 Tmr Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 630 Timers; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 631 Timer1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6311 Timer1 Trig; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6312 Timer1 Mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6313 Timer1 Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6314 Timer1 T1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6315 Timer1 T2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6316 Timer1 Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 632 Timer2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6321 Timer2 Trig; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6322 Timer2 Mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6323 Timer2 Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6324 Timer2 T1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6325 Timer2 T2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6326 Timer2 Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 633 Timer3; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6331 Timer3 Trig; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6332 Timer3 Mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6333 Timer3 Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6334 Timer3 T1; blank values remainunfilled
Shared source cells (coordinates refer to this table):
-
row 10, column 5, row 10, column 6 share the source cell at row 10, column 4. Read its current text above; the child slots remain unpopulated.
-
row 11, column 3, row 11, column 4, row 11, column 5, row 11, column 6 share the source cell at row 11, column 2. Read its current text above; the child slots remain unpopulated.
-
row 26, column 3, row 26, column 4, row 26, column 5, row 26, column 6 share the source cell at row 26, column 2. Read its current text above; the child slots remain unpopulated.
-
row 41, column 3, row 41, column 4, row 41, column 5, row 41, column 6 share the source cell at row 41, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 161
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 6249 | L4 Set Dly | 00:00:00 | 43802 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43803 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43804 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 4 | 624A | L4 Res Dly | 00:00:00 | 43805 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43806 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43807 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 7 | 624B | L4 Tmr Val | 00:00:00 | 42633 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42634 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42635 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 10 | 630 | Timers | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 109 |
| 11 | 631 | Timer1 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 12 | 6311 | Timer1 Trig | Off | 43808 | UInt | UInt | ⟦blank source cell⟧ |
| 13 | 6312 | Timer1 Mode | Delay | 43809 | UInt | UInt | ⟦blank source cell⟧ |
| 14 | 6313 | Timer1 Dly | 00:00:00 | 43810 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43811 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43812 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 17 | 6314 | Timer1 T1 | 00:00:00 | 43813 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43814 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43815 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 20 | 6315 | Timer1 T2 | 00:00:00 | 43816 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43817 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43818 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 23 | 6316 | Timer1 Val | 00:00:00 | 42636 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42637 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42638 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 26 | 632 | Timer2 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 110 |
| 27 | 6321 | Timer2 Trig | Off | 43819 | UInt | UInt | ⟦blank source cell⟧ |
| 28 | 6322 | Timer2 Mode | Delay | 43820 | UInt | UInt | ⟦blank source cell⟧ |
| 29 | 6323 | Timer2 Dly | 00:00:00 | 43821 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43822 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43823 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 32 | 6324 | Timer2 T1 | 00:00:00 | 43824 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43825 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43826 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 35 | 6325 | Timer2 T2 | 00:00:00 | 43827 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 36 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43828 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 37 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43829 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 38 | 6326 | Timer2 Val | 00:00:00 | 42639 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 39 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42640 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 40 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42641 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 41 | 633 | Timer3 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 110 |
| 42 | 6331 | Timer3 Trig | Off | 43830 | UInt | UInt | ⟦blank source cell⟧ |
| 43 | 6332 | Timer3 Mode | Delay | 43831 | UInt | UInt | ⟦blank source cell⟧ |
| 44 | 6333 | Timer3 Dly | 00:00:00 | 43832 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43833 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 46 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43834 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 47 | 6334 | Timer3 T1 | 00:00:00 | 43835 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 48 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43836 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 49 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43837 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 162
Manual reference: physical PDF page 162. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 6335 Timer3 T2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 6336 Timer3 Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 634 Timer4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6341 Timer4 Trig; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6342 Timer4 Mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6343 Timer4 Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6344 Timer4 T1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6345 Timer4 T2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6346 Timer4 Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 640 Flip flops; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 641 Flip flop 1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6411 F1 mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6412 F1 set; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6413 F1 reset; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6414 F1 Set Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6415 F1 Res Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6416 F1 Tmr Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 642 Flip flop 2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6421 F2 mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6422 F2 set; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6423 F2 reset; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6424 F2 Set Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6425 F2 Res Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6426 F2 Tmr Val; blank values remainunfilled
Shared source cells (coordinates refer to this table):
-
row 7, column 3, row 7, column 4, row 7, column 5, row 7, column 6 share the source cell at row 7, column 2. Read its current text above; the child slots remain unpopulated.
-
row 22, column 5, row 22, column 6 share the source cell at row 22, column 4. Read its current text above; the child slots remain unpopulated.
-
row 23, column 3, row 23, column 4, row 23, column 5, row 23, column 6 share the source cell at row 23, column 2. Read its current text above; the child slots remain unpopulated.
-
row 36, column 3, row 36, column 4, row 36, column 5, row 36, column 6 share the source cell at row 36, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 162
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 6335 | Timer3 T2 | 00:00:00 | 43838 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43839 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43840 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 4 | 6336 | Timer3 Val | 00:00:00 | 42642 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42643 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42644 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 7 | 634 | Timer4 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 110 |
| 8 | 6341 | Timer4 Trig | Off | 43841 | UInt | UInt | ⟦blank source cell⟧ |
| 9 | 6342 | Timer4 Mode | Delay | 43842 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | 6343 | Timer4 Dly | 00:00:00 | 43843 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 11 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43844 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43845 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 13 | 6344 | Timer4 T1 | 00:00:00 | 43846 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43847 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43848 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 16 | 6345 | Timer4 T2 | 00:00:00 | 43849 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43850 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43851 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 19 | 6346 | Timer4 Val | 00:00:00 | 42645 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42646 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42647 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 22 | 640 | Flip flops | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 110 |
| 23 | 641 | Flip flop 1 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 24 | 6411 | F1 mode | Reset | 43852 | UInt | UInt | ⟦blank source cell⟧ |
| 25 | 6412 | F1 set | Off | 43853 | UInt | UInt | ⟦blank source cell⟧ |
| 26 | 6413 | F1 reset | Off | 43854 | UInt | UInt | ⟦blank source cell⟧ |
| 27 | 6414 | F1 Set Dly | 00:00:00 | 43855 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43856 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 29 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43857 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 30 | 6415 | F1 Res Dly | 00:00:00 | 43858 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43859 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 32 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43860 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 33 | 6416 | F1 Tmr Val | 00:00:00 | 42648 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42649 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 35 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42650 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 36 | 642 | Flip flop 2 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 112 |
| 37 | 6421 | F2 mode | Reset | 43861 | UInt | UInt | ⟦blank source cell⟧ |
| 38 | 6422 | F2 set | Off | 43862 | UInt | UInt | ⟦blank source cell⟧ |
| 39 | 6423 | F2 reset | Off | 43863 | UInt | UInt | ⟦blank source cell⟧ |
| 40 | 6424 | F2 Set Dly | 00:00:00 | 43864 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 41 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43865 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 42 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43866 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 43 | 6425 | F2 Res Dly | 00:00:00 | 43867 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 44 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43868 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43869 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 46 | 6426 | F2 Tmr Val | 00:00:00 | 42651 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 47 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42652 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 48 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42653 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 163
Manual reference: physical PDF page 163. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 643 Flip flop 3; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6431 F3 mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6432 F3 set; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6433 F3 reset; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6434 F3 Set Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6435 F3 Res Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6436 F3 Tmr Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 644 Flip flop 4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6441 F4 mode; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6442 F4 set; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6443 F4 reset; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6444 F4 Set Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6445 F4 Res Dly; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6446 F4 Tmr Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 650 Counters; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 651 Counter 1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6511 C1 Trig; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6512 C1 Reset; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6513 C1 Trip val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6514 C1 Value; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 652 Counter 2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6521 C2 Trig; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6522 C2 Reset; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6523 C2 Trip val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6524 C2 Value; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 660 Clock logic; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 661 Clock 1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6611 Clk1TimeON; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6612 Clk1TimeOff; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6613 Clk1DateOn; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6614 Clk1DateOff; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6615 Clk1Weekday; blank values remainunfilled
Shared source cells (coordinates refer to this table):
-
row 1, column 3, row 1, column 4, row 1, column 5, row 1, column 6 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 14, column 3, row 14, column 4, row 14, column 5, row 14, column 6 share the source cell at row 14, column 2. Read its current text above; the child slots remain unpopulated.
-
row 27, column 5, row 27, column 6 share the source cell at row 27, column 4. Read its current text above; the child slots remain unpopulated.
-
row 28, column 3, row 28, column 4, row 28, column 5, row 28, column 6 share the source cell at row 28, column 2. Read its current text above; the child slots remain unpopulated.
-
row 33, column 3, row 33, column 4, row 33, column 5, row 33, column 6 share the source cell at row 33, column 2. Read its current text above; the child slots remain unpopulated.
-
row 38, column 5, row 38, column 6 share the source cell at row 38, column 4. Read its current text above; the child slots remain unpopulated.
-
row 39, column 3, row 39, column 4, row 39, column 5, row 39, column 6 share the source cell at row 39, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 163
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 643 | Flip flop 3 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 112 |
| 2 | 6431 | F3 mode | Set | 43870 | UInt | UInt | ⟦blank source cell⟧ |
| 3 | 6432 | F3 set | Off | 43871 | UInt | UInt | ⟦blank source cell⟧ |
| 4 | 6433 | F3 reset | Off | 43872 | UInt | UInt | ⟦blank source cell⟧ |
| 5 | 6434 | F3 Set Dly | 00:00:00 | 43873 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43874 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43875 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 8 | 6435 | F3 Res Dly | 00:00:00 | 43876 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43877 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43878 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 11 | 6436 | F3 Tmr Val | 00:00:00 | 42654 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42655 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42656 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 14 | 644 | Flip flop 4 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 112 |
| 15 | 6441 | F4 mode | Edge | 43879 | UInt | UInt | ⟦blank source cell⟧ |
| 16 | 6442 | F4 set | Off | 43880 | UInt | UInt | ⟦blank source cell⟧ |
| 17 | 6443 | F4 reset | Off | 43881 | UInt | UInt | ⟦blank source cell⟧ |
| 18 | 6444 | F4 Set Dly | 00:00:00 | 43882 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43883 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43884 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 21 | 6445 | F4 Res Dly | 00:00:00 | 43885 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43886 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 23 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43887 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 24 | 6446 | F4 Tmr Val | 00:00:00 | 42657 | UInt, 1=1h | UInt | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42658 | UInt, 1=1m | UInt | ⟦blank source cell⟧ |
| 26 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42659 | UInt, 1=0.1s | UInt | ⟦blank source cell⟧ |
| 27 | 650 | Counters | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 112 |
| 28 | 651 | Counter 1 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 29 | 6511 | C1 Trig | Off | 43888 | UInt | UInt | ⟦blank source cell⟧ |
| 30 | 6512 | C1 Reset | Off | 43889 | UInt | UInt | ⟦blank source cell⟧ |
| 31 | 6513 | C1 Trip val | 0 | 43890 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 32 | 6514 | C1 Value | ⟦blank source cell⟧ | 31070 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 33 | 652 | Counter 2 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 34 | 6521 | C2 Trig | Off | 43891 | UInt | UInt | ⟦blank source cell⟧ |
| 35 | 6522 | C2 Reset | Off | 43892 | UInt | UInt | ⟦blank source cell⟧ |
| 36 | 6523 | C2 Trip val | 0 | 43893 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 37 | 6524 | C2 Value | ⟦blank source cell⟧ | 31071 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 38 | 660 | Clock logic | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 113 |
| 39 | 661 | Clock 1 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 40 | 6611 | Clk1TimeON | 00:00:00 | 43600 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 41 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43601 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 42 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43602 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 43 | 6612 | Clk1TimeOff | 00:00:00 | 43603 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 44 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43604 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43605 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 46 | 6613 | Clk1DateOn | 0 | 43606 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 47 | 6614 | Clk1DateOff | 0 | 43609 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 48 | 6615 | Clk1Weekday | 0 | 43612 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 164
Manual reference: physical PDF page 164. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 662 Clock 2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6621 Clk2TimeON; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6622 Clk2TimeOff; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6623 Clk2DateOn; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6624 Clk2DateOff; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6625 Clk2Weekday; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 700 Oper/Status; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 710 Operation; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71X Set/View ref; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 711 Process Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 713 Torque; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 714 Torque; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 715 Shaft Power; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 716 Shaft Power; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 717 El Power; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 718 RMS Current; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 719 L main volt; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71A Heatsnk Tmp; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71B PT100B1 123; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71C PT100B2 123; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71D Current I1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71E Current I2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71F Current I3; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71G L12 voltage; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71H L13 voltage; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71I L23 voltage; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71J Phase seq.; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71K Used Th Cap; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 720 Status; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 721 TSA Status; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 722 Warning; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 723 DigInStatus; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 724 RelayStatus; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 725 AnalogueIn; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 726 AnalogueOut; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 727 IO StatusB1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 728 IO StatusB2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 72A CA1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 72B CD1-4; blank values remainunfilled
Shared source cells (coordinates refer to this table):
-
row 1, column 3, row 1, column 4, row 1, column 5, row 1, column 6 share the source cell at row 1, column 2. Read its current text above; the child slots remain unpopulated.
-
row 11, column 5, row 11, column 6 share the source cell at row 11, column 4. Read its current text above; the child slots remain unpopulated.
-
row 12, column 5, row 12, column 6 share the source cell at row 12, column 4. Read its current text above; the child slots remain unpopulated.
-
row 37, column 5, row 37, column 6 share the source cell at row 37, column 4. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 164
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 662 | Clock 2 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 114 |
| 2 | 6621 | Clk2TimeON | 00:00:00 | 43615 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43616 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43617 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 5 | 6622 | Clk2TimeOff | 00:00:00 | 43618 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43619 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 43620 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 8 | 6623 | Clk2DateOn | 0 | 43621 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 9 | 6624 | Clk2DateOff | 0 | 43624 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 10 | 6625 | Clk2Weekday | 0 | 43627 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 11 | 700 | Oper/Status | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 114 |
| 12 | 710 | Operation | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 13 | 71X | Set/View ref | ⟦blank source cell⟧ | 31000 | Long, 1= see Notes |
EInt | 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 14 | 711 | Process Val | ⟦blank source cell⟧ | 31002 | Long, 1= see Notes |
EInt | 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 15 | 713 | Torque | ⟦blank source cell⟧ | 31003 | Long, 1=0.1Nm |
EInt | ⟦blank source cell⟧ |
| 16 | 714 | Torque | ⟦blank source cell⟧ | 31004 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 17 | 715 | Shaft Power | ⟦blank source cell⟧ | 31005 | Long, 1=1W | EInt | ⟦blank source cell⟧ |
| 18 | 716 | Shaft Power | ⟦blank source cell⟧ | 31006 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 19 | 717 | El Power | ⟦blank source cell⟧ | 31007 | Long, 1=1W | EInt | ⟦blank source cell⟧ |
| 20 | 718 | RMS Current | ⟦blank source cell⟧ | 31008 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 21 | 719 | L main volt | ⟦blank source cell⟧ | 31009 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 22 | 71A | Heatsnk Tmp | ⟦blank source cell⟧ | 31010 | Long, 1=0.1°C |
EInt | ⟦blank source cell⟧ |
| 23 | 71B | PT100B1 123 | ⟦blank source cell⟧ | 31011 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31012 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31013 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 26 | 71C | PT100B2 123 | ⟦blank source cell⟧ | 31014 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31015 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31016 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 29 | 71D | Current I1 | ⟦blank source cell⟧ | 31017 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 30 | 71E | Current I2 | ⟦blank source cell⟧ | 31018 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 31 | 71F | Current I3 | ⟦blank source cell⟧ | 31019 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 32 | 71G | L12 voltage | ⟦blank source cell⟧ | 31020 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 33 | 71H | L13 voltage | ⟦blank source cell⟧ | 31021 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 34 | 71I | L23 voltage | ⟦blank source cell⟧ | 31022 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 35 | 71J | Phase seq. | ⟦blank source cell⟧ | 31023 | UInt | UInt | ⟦blank source cell⟧ |
| 36 | 71K | Used Th Cap | ⟦blank source cell⟧ | 31024 | Long, 1=0.1% | EInt | ⟦blank source cell⟧ |
| 37 | 720 | Status | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 116 |
| 38 | 721 | TSA Status | ⟦blank source cell⟧ | 31025 | UInt | UInt | ⟦blank source cell⟧ |
| 39 | 722 | Warning | ⟦blank source cell⟧ | 31026 | UInt | UInt | ⟦blank source cell⟧ |
| 40 | 723 | DigInStatus | ⟦blank source cell⟧ | 31027 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 41 | 724 | RelayStatus | ⟦blank source cell⟧ | 31028 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 42 | 725 | AnalogueIn | ⟦blank source cell⟧ | 31029 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 43 | 726 | AnalogueOut | ⟦blank source cell⟧ | 31030 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 44 | 727 | IO StatusB1 | ⟦blank source cell⟧ | 31031 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 45 | 728 | IO StatusB2 | ⟦blank source cell⟧ | 31032 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 46 | 72A | CA1-4 | ⟦blank source cell⟧ | 31050 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 47 | 72B | CD1-4 | ⟦blank source cell⟧ | 31051 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 165
Manual reference: physical PDF page 165. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72C Logic 1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72D Timer 1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72E FlipFlop1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72F Counter 1-2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72G TtoNxtStart; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 730 Stored Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 731 Run Time; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 7311 Reset RunTm; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 732 Mains Time; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 733 Energy; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 7331 Rst Energy; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 740 Clock; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 741 Time; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 742 Date; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 743 Weekday; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 744 DST; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 800 View TripLog; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 810 (Trip log list 1); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 810 Trip Message; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811 Operation; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8111 Process Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8113 Torque; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8114 Torque; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8115 Shaft Power; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8116 ShaftPower%; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8117 El Power; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8118 RMS Current; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8119 L main volt; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811A Heatsnk Tmp; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811B PT100B1 123; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811C PT100B2 123; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811D Current I1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811E Current I2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811F Current I3; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811G L12 voltage; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811H L13 voltage; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811I L23 voltage; blank values remainunfilled
Shared source cells (coordinates refer to this table):
-
row 6, column 5, row 6, column 6 share the source cell at row 6, column 4. Read its current text above; the child slots remain unpopulated.
-
row 16, column 5, row 16, column 6 share the source cell at row 16, column 4. Read its current text above; the child slots remain unpopulated.
-
row 23, column 5, row 23, column 6 share the source cell at row 23, column 4. Read its current text above; the child slots remain unpopulated.
-
row 24, column 5, row 24, column 6 share the source cell at row 24, column 4. Read its current text above; the child slots remain unpopulated.
-
row 26, column 3, row 26, column 4, row 26, column 5, row 26, column 6 share the source cell at row 26, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 165
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 72C | Logic 1-4 | ⟦blank source cell⟧ | 31052 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 2 | 72D | Timer 1-4 | ⟦blank source cell⟧ | 31053 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 3 | 72E | FlipFlop1-4 | ⟦blank source cell⟧ | 31072 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 4 | 72F | Counter 1-2 | ⟦blank source cell⟧ | 31073 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 5 | 72G | TtoNxtStart | ⟦blank source cell⟧ | 31036 | UInt, 1=1min | UInt | ⟦blank source cell⟧ |
| 6 | 730 | Stored Val | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 119 |
| 7 | 731 | Run Time | 00:00:00 | 31074 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31075 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31076 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 10 | 7311 | Reset RunTm | No | 7 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | 732 | Mains Time | 00:00:00 | 31077 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31078 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31079 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 14 | 733 | Energy | ...kWh | 31080 | Long, 1=1Wh | EInt | ⟦blank source cell⟧ |
| 15 | 7331 | Rst Energy | No | 6 | UInt | UInt | ⟦blank source cell⟧ |
| 16 | 740 | Clock | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 119 |
| 17 | 741 | Time | 00:00:00 | 42920 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42921 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42922 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 20 | 742 | Date | 0 | 42923 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 21 | 743 | Weekday | Monday | 42926 | Long | EInt | ⟦blank source cell⟧ |
| 22 | 744 | DST | No | 43058 | UInt | UInt | ⟦blank source cell⟧ |
| 23 | 800 | View TripLog | ⟦blank source cell⟧ | See Appendix 2 | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 120 |
| 24 | 810 | (Trip log list 1) | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 25 | 810 | Trip Message | ⟦blank source cell⟧ | 31101 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 26 | 811 | Operation | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 27 | 8111 | Process Val | ⟦blank source cell⟧ | 31102 | Long, 1= see Notes |
EInt | 1rpm, 1%, 1°C, 0.001 as set in [322] |
| 28 | 8113 | Torque | ⟦blank source cell⟧ | 31104 | Long, 1=0.1Nm |
EInt | ⟦blank source cell⟧ |
| 29 | 8114 | Torque | ⟦blank source cell⟧ | 31105 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 30 | 8115 | Shaft Power | ⟦blank source cell⟧ | 31106 | Long, 1=1W | EInt | Page 120 |
| 31 | 8116 | ShaftPower% | ⟦blank source cell⟧ | 31107 | UInt, 1=1% | UInt | ⟦blank source cell⟧ |
| 32 | 8117 | El Power | ⟦blank source cell⟧ | 31108 | Long, 1=1W | EInt | ⟦blank source cell⟧ |
| 33 | 8118 | RMS Current | ⟦blank source cell⟧ | 31109 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 34 | 8119 | L main volt | ⟦blank source cell⟧ | 31110 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 35 | 811A | Heatsnk Tmp | ⟦blank source cell⟧ | 31111 | Long, 1=0.1°C |
EInt | ⟦blank source cell⟧ |
| 36 | 811B | PT100B1 123 | ⟦blank source cell⟧ | 31112 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 37 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31113 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 38 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31114 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 39 | 811C | PT100B2 123 | ⟦blank source cell⟧ | 31115 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 40 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31116 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 41 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31117 | Long, 1=1°C | EInt | ⟦blank source cell⟧ |
| 42 | 811D | Current I1 | ⟦blank source cell⟧ | 31118 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 43 | 811E | Current I2 | ⟦blank source cell⟧ | 31119 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 44 | 811F | Current I3 | ⟦blank source cell⟧ | 31120 | Long, 1=0.1A | EInt | ⟦blank source cell⟧ |
| 45 | 811G | L12 voltage | ⟦blank source cell⟧ | 31121 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 46 | 811H | L13 voltage | ⟦blank source cell⟧ | 31122 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
| 47 | 811I | L23 voltage | ⟦blank source cell⟧ | 31123 | Long, 1=0.1V | EInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 166
Manual reference: physical PDF page 166. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 811J Phase seq.; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 811K Used Th Cap; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812 Status; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8121 TSA Status; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8122 DigInStatus; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8123 RelayStatus; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8124 AnalogueIn; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8125 AnalogueOut; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8126 IO StatusB1; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8127 IO StatusB2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8129 CA1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812A CD1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812B Logic 1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812C Timer 1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812D FlipFlop1-4; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812E Counter 1-2; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812F TtoNxtStart; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812G Time; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812H Date; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 813 Stored Val; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 8131 Run Time; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 8132 Mains Time; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 820 (Trip log list 2); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 830 (Trip log list 3); displayed association 830 (Trip log list 3); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 840 (Trip log list 4); displayed association 840 (Trip log list 4); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 850 (Trip log list 5); displayed association 850 (Trip log list 5); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 860 (Trip log list 6); displayed association 860 (Trip log list 6); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 870 (Trip log list 7); displayed association 870 (Trip log list 7); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 880 (Trip log list 8); displayed association 880 (Trip log list 8); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 890 (Trip log list 9); blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 8A0 Reset Trip L; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 900 System Data; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 910 Service Info; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 911 Next Service; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 912 Service Cont; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 920 TSA Data; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 921 TSA Type; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 922 Software; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 9221 Build Info; blank values remainunfilled
Shared source cells (coordinates refer to this table):
-
row 3, column 3, row 3, column 4, row 3, column 5, row 3, column 6 share the source cell at row 3, column 2. Read its current text above; the child slots remain unpopulated.
-
row 22, column 3, row 22, column 4, row 22, column 5, row 22, column 6 share the source cell at row 22, column 2. Read its current text above; the child slots remain unpopulated.
-
row 29, column 5, row 29, column 6, row 30, column 4, row 30, column 5, row 30, column 6, row 31, column 4, row 31, column 5, row 31, column 6, row 32, column 4, row 32, column 5, row 32, column 6, row 33, column 4, row 33, column 5, row 33, column 6, row 34, column 4, row 34, column 5, row 34, column 6, row 35, column 4, row 35, column 5, row 35, column 6, row 36, column 4, row 36, column 5, row 36, column 6 share the source cell at row 29, column 4. Read its current text above; the child slots remain unpopulated.
-
row 38, column 5, row 38, column 6 share the source cell at row 38, column 4. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 166
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | 811J | Phase seq. | ⟦blank source cell⟧ | 31124 | UInt | UInt | ⟦blank source cell⟧ |
| 2 | 811K | Used Th Cap | ⟦blank source cell⟧ | 31125 | Long, 1=0.1% | EInt | ⟦blank source cell⟧ |
| 3 | 812 | Status | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 120 |
| 4 | 8121 | TSA Status | ⟦blank source cell⟧ | 31126 | UInt | UInt | ⟦blank source cell⟧ |
| 5 | 8122 | DigInStatus | ⟦blank source cell⟧ | 31127 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 6 | 8123 | RelayStatus | ⟦blank source cell⟧ | 31128 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 7 | 8124 | AnalogueIn | ⟦blank source cell⟧ | 31129 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 8 | 8125 | AnalogueOut | ⟦blank source cell⟧ | 31130 | Long, 1=1% | EInt | ⟦blank source cell⟧ |
| 9 | 8126 | IO StatusB1 | ⟦blank source cell⟧ | 31131 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 10 | 8127 | IO StatusB2 | ⟦blank source cell⟧ | 31132 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 11 | 8129 | CA1-4 | ⟦blank source cell⟧ | 31134 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 12 | 812A | CD1-4 | ⟦blank source cell⟧ | 31135 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 13 | 812B | Logic 1-4 | ⟦blank source cell⟧ | 31136 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 14 | 812C | Timer 1-4 | ⟦blank source cell⟧ | 31137 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 15 | 812D | FlipFlop1-4 | ⟦blank source cell⟧ | 31138 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 16 | 812E | Counter 1-2 | ⟦blank source cell⟧ | 31139 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 17 | 812F | TtoNxtStart | ⟦blank source cell⟧ | 31140 | UInt, 1=1min | UInt | ⟦blank source cell⟧ |
| 18 | 812G | Time | 00:00:00 | 31141 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31142 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31143 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 21 | 812H | Date | ⟦blank source cell⟧ | 31144 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 22 | 813 | Stored Val | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 120 |
| 23 | 8131 | Run Time | 00:00:00 | 31147 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31148 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31149 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 26 | 8132 | Mains Time | 00:00:00 | 31150 | Long, 1=1h | EInt | ⟦blank source cell⟧ |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31151 | Long, 1=1m | EInt | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31152 | Long, 1=1s | EInt | ⟦blank source cell⟧ |
| 29 | 820 | (Trip log list 2) | ⟦blank source cell⟧ | Same parameters as for menu group 810 (Trip log list 1). Communication data in Appendix 2. |
⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 121 |
| 30 | 830 | (Trip log list 3) | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 31 | 840 | (Trip log list 4) | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 32 | 850 | (Trip log list 5) | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 33 | 860 | (Trip log list 6) | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 34 | 870 | (Trip log list 7) | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 35 | 880 | (Trip log list 8) | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 36 | 890 | (Trip log list 9) | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 37 | 8A0 | Reset Trip L | No | 8 | UInt | UInt | Page 121 |
| 38 | 900 | System Data | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | Page 121 |
| 39 | 910 | Service Info | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 40 | 911 | Next Service | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 41 | 912 | Service Cont | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 42 | 920 | TSA Data | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 43 | 921 | TSA Type | - | 42300 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 44 | 922 | Software | ⟦blank source cell⟧ | 31038 | UInt | UInt | ⟦blank source cell⟧ |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31039 | UInt | UInt | ⟦blank source cell⟧ |
| 46 | 9221 | Build Info | ⟦blank source cell⟧ | 31040 | UInt | UInt | ⟦blank source cell⟧ |
| 47 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31041 | UInt | UInt | ⟦blank source cell⟧ |
| 48 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31042 | UInt | UInt | ⟦blank source cell⟧ |
| 49 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31043 | UInt | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 167
Manual reference: physical PDF page 167. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 9221 Build Info continuation from PDF166; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 923 Unit Name; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 924 Hardware; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9241 Power Board; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9242 CT; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9243 CTscale; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9244 Bypass; blank values remainunfilled
Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9245 Thyristor; blank values remainunfilled
Shared source cells (coordinates refer to this table):
- row 15, column 3, row 15, column 4, row 15, column 5, row 15, column 6 share the source cell at row 15, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 1 menu list — PDF page 167
| Source row | Menu number | Menu parameter | Default settings | Modbus Inst. DeviceNet no. | Fieldbus format | Modbus format | Notes |
|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31044 | UInt | UInt | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 31045 | UInt | UInt | ⟦blank source cell⟧ |
| 3 | 923 | Unit Name | 0 | 42301 | UInt | UInt | ⟦blank source cell⟧ |
| 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42302 | UInt | UInt | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42303 | UInt | UInt | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42304 | UInt | UInt | ⟦blank source cell⟧ |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42305 | UInt | UInt | ⟦blank source cell⟧ |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42306 | UInt | UInt | ⟦blank source cell⟧ |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42307 | UInt | UInt | ⟦blank source cell⟧ |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42308 | UInt | UInt | ⟦blank source cell⟧ |
| 11 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42309 | UInt | UInt | ⟦blank source cell⟧ |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42310 | UInt | UInt | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42311 | UInt | UInt | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 42312 | UInt | UInt | ⟦blank source cell⟧ |
| 15 | 924 | Hardware | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ | ⟦blank source cell⟧ |
| 16 | 9241 | Power Board | ⟦blank source cell⟧ | 33101 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 17 | 9242 | CT | ⟦blank source cell⟧ | 33102 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 18 | 9243 | CTscale | ⟦blank source cell⟧ | 33105 | Long, 1=1 | EInt | ⟦blank source cell⟧ |
| 19 | 9244 | Bypass | ⟦blank source cell⟧ | 33103 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
| 20 | 9245 | Thyristor | ⟦blank source cell⟧ | 33104 | UInt, 1=1 | UInt | ⟦blank source cell⟧ |
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 168
Manual reference: physical PDF page 168. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Appendix 2: Trip message
communication data
Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.
Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Modbus Instance no/
DeviceNet no:: 810 → 31101-31154; 820 → 31201-31254; 830 → 31301-31354; 840 → 31401-31454; 850 → 31501-31554; 860 → 31601-31654; 870 → 31701-31754; 880 → 31801-31854; 890 → 31901-31954
Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Profibus slot/index: 810 → 121/245-122/43; 820 → 122/90-122/143; 830 → 122/190-122/243; 840 → 123/35-123/88; 850 → 123/135--123/188; 860 → 123/235-124/33; 870 → 124/80-124/133; 880 → 124/180-124/233; 890 → 125/25-125/78
Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Profinet IO index: 810 → 1101-1154; 820 → 1201-1254; 830 → 1301-1354; 840 → 1401-1454; 850 → 1501-1554; 860 → 1601-1654; 870 → 1701-1754; 880 → 1801-1854; 890 → 1901-1954
Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Fieldbus format shares source merged See respective parameter.
Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Modbus format shares source merged See respective parameter.
Shared source cells (coordinates refer to this table):
- row 4, column 3, row 5, column 2, row 5, column 3 share the source cell at row 4, column 2. Read its current text above; the child slots remain unpopulated.
Appendix 2 trip communication mapping — PDF page 168
| Source row | Protocol or format | Source address ranges or format | Source trip log list |
|---|---|---|---|
| 1 | Modbus Instance no/ DeviceNet no: |
31101-31154 31201-31254 31301-31354 31401-31454 31501-31554 31601-31654 31701-31754 31801-31854 31901-31954 |
Trip log list 810 820 830 840 850 860 870 880 890 |
| 2 | Profibus slot/index | 121/245-122/43 122/90-122/143 122/190-122/243 123/35-123/88 123/135--123/188 123/235-124/33 124/80-124/133 124/180-124/233 125/25-125/78 |
Trip log list 810 820 830 840 850 860 870 880 890 |
| 3 | Profinet IO index | 1101-1154 1201-1254 1301-1354 1401-1454 1501-1554 1601-1654 1701-1754 1801-1854 1901-1954 |
Trip log list 810 820 830 840 850 860 870 880 890 |
| 4 | Fieldbus format | See respective parameter. | ⟦null: no independent source value⟧ |
| 5 | Modbus format | ⟦null: no independent source value⟧ | ⟦null: no independent source value⟧ |
Manual — BLANK_PAGE — page 169
Manual reference: physical PDF page 169. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source page content: Blank page visually confirmed. Reviewedtext: No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.
Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 170
Manual reference: physical PDF page 170. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
CG Drives & Automation Sweden AB
Mörsaregatan 12
Box 222 25
SE-250 24 Helsingborg
Sweden
T +46 42 16 99 00
F +46 42 16 99 49
www.emotron.com/www.cgglobal.com
CG Drives & Automation, 01-5980-01r0, 2013-05-13
Selection checks and source differences
Website repeats MSF facts despite linking TSA manual. TSA guide built from named TSA sources; product naming/identity remains supplier clarification.
TSA catalogue246/340mm versus manual246/296mm size1 total height. Control supply+10%/-15% versus±10%. No edition reconciliation by inference.
Catalogue broad16–820/1000–1800A feature groups exceed detailed16–450 schedule. Do not invent larger-model ratings or dimensions.
TSA cULus logo Pending retained; source part options, response times and slot counts are conditional. MSF hardware/terminals not substituted.
Shared EmoSoftCom section header says MSF but text says TSA. Menu/example/communication differences remain in source context and local exception ledger.
Product documents
- Emotron_Softstarter_Technical-catalogue_01-5552-01_English-1.pdf — Product page
- emotron_tsa_softstarter_manual_052013_en.pdf.pdf — Product page
- TAC-EMD-Standard-Conditions-of-Sale-Final-May-2022.pdf — Shared website
- ISO9001-Intertek-SAI-Global-Certificate-QEC3088-Expiry-25-May-2029.pdf — Shared website
- ISO45001-Intertek-SAI-Global-Certificate-0185118-Expiry-22-August-2027.pdf — Shared website