TECO Emotron Soft Starter — TSA Source Guide

Our Emotron TSA softstarter combines controlled starting and stopping with integrated bypass, load monitoring and operator functions for applications that do not require continuous variable-speed control.

Product identity needs confirmation: the TECO page is titled “TECO Emotron Soft Starter” and links to the TSA manual, but its feature text repeats the MSF range's 4 kW–1.6 MW and 17–835 A/1000–1400 A enclosure groups. This guide identifies TSA facts from the TSA documents and keeps the conflicting website description separate. We do not present MSF values as TSA ratings.

Select by current, supply and start duty

The shared catalogue's TSA headline is 4 kW–1.8 MW, 200–690 V, three-phase, with integrated bypass. Its detailed selection tables in this edition list 16–450 models, while broader feature text describes IP20 sizes 16–820 A and IP00 sizes 1000–1800 A. Those headlines do not supply missing model ratings or dimensions.

TSA selection uses AC53b duty. The catalogue defines normal duty at 3×In_soft and heavy duty at 5×In_soft, with 15-second starts for size 1, 30 seconds for sizes 2–4, and 10 starts/hour. The manual's corresponding footnote mentions sizes 2–6. Keep the relevant edition, frame and start conditions with each current/power value. kW columns at 400/525/690 V and hp columns at 460/575 V must not be combined or converted into unprovided ratings.

The 170-page TSA manual is 01-5980-01r0, software1.0X. Its size 1 examples show TSA52-016 at 16 A normal duty and 10 A heavy duty, illustrating why a model number alone is not a heavy-duty capacity. Use the supplied unit's software and type label before applying parameters or options.

Controlled starts, stops and monitoring

Three-phase torque control supports smooth starts and pump stops intended to reduce water hammer. The source also describes high-inertia braking, forward/reverse jog, real-time clock, multilingual control and load monitoring. Jog is a limited function, not a general variable-speed-drive capability. Braking and reversing require the correct system arrangement and load assessment.

Motor I²t protection and isolated thermistor input are listed as standard; PT100 capability requires the specified option. Parameter groups retain motor data, process scaling, torque/current control, protection, I/O, logic, timers, operating records and communication settings. Actual alarm actions, start permissions and reset behaviour must be commissioned for the installation. Sample display values do not establish live motor measurements.

Environment and installation dimensions

The shared catalogue's nominal ambient is 0–40°C. TSA's manual permits operation to 55°C with 2% current derating per°C above 40°C. It describes altitude to 1, 000m without derating, then1% per100m to 4, 000m. No combined derating calculation has been supplied here. Source coating and contamination classes do not override enclosure or site restrictions.

TSA dimensions distinguish H1 enclosure height from H2 total height. There is a concrete edition difference: the catalogue's size 1/2 schedule gives 246/340 mm, whereas the manual's size 1 table gives 246/296 mm. We preserve both and require the approved outline for mounting. The smallest convection-cooled units are vertical-only; larger fan-cooled groups have separate orientation limits.

Controls and expansion

The general catalogue table gives control supply 100–240 V+10%/−15%, while the interface page and manual connection table say 100–240VAC±10%. Confirm the actual nameplate and approved connection data rather than using the more permissive tolerance.

TSA supports two option boards plus one communication option in the catalogue. The maximum of two I/O boards or two PTC/PT100 boards sits within that total; it does not mean four boards can be installed together. Communications options include the separately identified Profibus, DeviceNet, Modbus/TCP, EtherCAT, Profinet, USB and RS485 modules. Listed10ms responses exclude the stated network delays.

The external-panel IP54 claim is for the cabinet-door kit. TSA's standard coated boards, supply outputs and relay-terminal mapping differ from MSF. In particular, TSA relay3 has32C/33NC; the MSF schedule reverses those roles. All relays must meet the manual's common external-supply constraints; no cross-family pinout has been inferred.

Source qualifications

The catalogue's TSA cULus logo is explicitly marked Pending. That historical statement is not promoted to certification. The MSF heading on the EmoSoftCom page conflicts with TSA wording below it. Product identity, control-supply tolerance, total height, software compatibility and approval scope remain checks for the selected assembly.

Installation and source references

Use qualified personnel and the complete selected-model manual for supply isolation, earthing, fuses, mounting clearances, cooling, connections and commissioning. A soft stop or disabled run command is not electrical isolation. The source fuse tables distinguish load protection, semiconductor protection and historical UL/cUL conditions; a part code printed under an ampere heading is not a numeric fuse rating.

The shared 24-page catalogue is 01-5552-01r1, English2014-09. Both named families remain in its reference section, clearly separated; association with this page does not transfer one family's terminals, options, ratings or approvals to the other. Diagrams remain in the original PDFs. Blank fields, unspecified units, pending approvals and unresolved source references remain explicit.

Our reference tables retain all collected model, voltage, duty, dimension, interface and parameter data, with exact source editions. No individual website drawing table was attached to this product in the collection. The catalogue's external CAD references do not prove that a model-specific CAD file was collected. Share the motor nameplate, load inertia, starting current/time, starts per hour, supply and environment so we can confirm your selection.

Catalogue — Technical Catalogue Softstarters cover — page 1

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 1

Context: Cover ranges are supplier headline ranges, not validated per-model ratings. Small photographic display details are outside this text rendition.

Table conditions: Literal cover ranges. Model selection/current tables elsewhere not reviewed in this batch; no extrapolation.

Cover family ranges — PDF page 1

Family Cover power range Cover voltage range
Emotron TSA 4–1800kW 200–690V
Emotron MSF2.0 7.5–1500kW 200–690V

Catalogue — Emotron TSA / PDF 2 — page 2

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 2

Emotron TSA softstarter - with built-in bypass

Main features

16 - 56 A
70 - 100 A
140 - 200 A
240 - 450 A

(Pending)

GOST R

• Compact and robust softstarter with wide power range:
4kW - 1.8 MW, 200 - 690V, 3 ph.
• Integrated bypass with proven contactor technology.
• 3-phase torque control for optimal performance.
• Torque control start and stop modes for smooth low-current starts and
pump stops without water hammering.
• High capacity dynamic vector braking available for high inertia stopping.
• Coated boards as standard extends lifetime in harsh environments.
• Real-time clock.
• Multilingual control panel.
• Jog forward/reverse with adjustable speed.

• Motor I2t protection and isolated thermistor input as standard. PT100
inputs as option.
• Load monitor function for protection of your load machinery.
• IP20 protection for sizes 16-820 A, IP00 for sizes 1000 - 1800 A.
• Fulfills EMC First environment-category C2.

Emotron TSA softstarters take
motor control to a new level. Soft
torque starting, intelligent load
monitoring and smart stops are all
included and accompanied by a
robust and compact design. By
developing the Emotron TSA range
of electronic softstarters CG has
taken a major step towards the
ideal motor controller for
applications where variable speed
is not required. You simply get
everything except variable speed!

Supplier logo panel shows CE, cULus with the qualifier (Pending), and GOST R. The pending qualifier belongs to the UL logo, not to all feature claims. This is historical catalogue text, not evidence of current certification.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Catalogue — Emotron TSA / PDF 3 — page 3

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 3

Emotron TSA softstarter with integrated bypass
Typical motor power at mains voltage 400 V and 460 V

Rating according to AC53b norm.

(1) Normal duty: Start current = 3 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(2) Heavy duty: Start current = 5 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(3) H1= Height of enclosure, H2=Total height

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: Emotron TSA; 400 V / 460 V. AC53b: normal starting current 3 x In_soft; heavy 5 x In_soft. Start time 15 s for size1, 30 s for sizes2–4;10 starts/hour. H1 enclosure height; H2 total height.

Emotron TSA specifications — PDF page 3

Model Normal duty: Power @400 V (kW) Normal duty: Power @460 V (hp) Normal duty: Rated current (A) Heavy duty: Power @400 V (kW) Heavy duty: Power @460 V (hp) Heavy duty: Rated current (A) Frame size / dimensions H1/H2 x W x D (mm)
TSA52-016 7.5 10 16 4 5 10 Frame size 1
246/340 x 126 x 188
TSA52-022 11 15 22 5.5 7.5 12 Frame size 1
246/340 x 126 x 188
TSA52-030 15 20 30 7.5 10 18 Frame size 1
246/340 x 126 x 188
TSA52-036 18.5 25 36 7.5 15 21 Frame size 1
246/340 x 126 x 188
TSA52-042 22 30 42 11 20 25 Frame size 1
246/340 x 126 x 188
TSA52-056 30 40 56 15 25 33 Frame size 1
246/340 x 126 x 188
TSA52-070 37 50 70 22 30 42 Frame size 2
246/340 x 126 x 188
TSA52-085 45 60 85 22 40 51 Frame size 2
246/340 x 126 x 188
TSA52-100 55 75 100 30 40 60 Frame size 2
246/340 x 126 x 188
TSA52-140 75 100 140 45 60 84 Frame size 3
285/380 x 196 x 235
TSA52-170 90 125 170 55 75 102 Frame size 3
285/380 x 196 x 235
TSA52-200 110 150 200 55 100 120 Frame size 3
285/380 x 196 x 235
TSA52-240 132 200 240 75 100 144 Frame size 4
373/512 x 254 x 260
TSA52-300 160 250 300 90 125 180 Frame size 4
373/512 x 254 x 260
TSA52-360 200 300 360 110 150 216 Frame size 4
373/512 x 254 x 260
TSA52-450 250 350 450 160 200 270 Frame size 4
373/512 x 254 x 260

Catalogue — Emotron TSA / PDF 4 — page 4

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 4

Emotron TSA softstarter with integrated bypass
Typical motor power at mains voltage 525 V

Rating according to AC53b norm.

(1) Normal duty: Start current = 3 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(2) Heavy duty: Start current = 5 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(3) H1= Height of enclosure, H2=Total height

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: Emotron TSA; 525 V. AC53b: normal starting current 3 x In_soft; heavy 5 x In_soft. Start time 15 s for size1, 30 s for sizes2–4;10 starts/hour. H1 enclosure height; H2 total height.

Emotron TSA specifications — PDF page 4

Model Normal duty: Power @525 V (kW) Normal duty: Rated current (A) Heavy duty: Power @525 V (kW) Heavy duty: Rated current (A) Frame size / dimensions H1/H2 x W x D (mm)
TSA52-016 11 16 5.5 10 Frame size 1
246/340 x 126 x 188
TSA52-022 15 22 7.5 12 Frame size 1
246/340 x 126 x 188
TSA52-030 18.5 30 11 18 Frame size 1
246/340 x 126 x 188
TSA52-036 22 36 11 21 Frame size 1
246/340 x 126 x 188
TSA52-042 30 42 15 25 Frame size 1
246/340 x 126 x 188
TSA52-056 37 56 22 33 Frame size 1
246/340 x 126 x 188
TSA52-070 45 70 22 42 Frame size 2
246/340 x 126 x 188
TSA52-085 55 85 30 51 Frame size 2
246/340 x 126 x 188
TSA52-100 75 100 37 60 Frame size 2
246/340 x 126 x 188
TSA52-140 90 140 55 84 Frame size 3
285/380 x 196 x 235
TSA52-170 110 170 75 102 Frame size 3
285/380 x 196 x 235
TSA52-200 132 200 75 120 Frame size 3
285/380 x 196 x 235
TSA52-240 160 240 90 144 Frame size 4
373/512 x 254 x 260
TSA52-300 200 300 132 180 Frame size 4
373/512 x 254 x 260
TSA52-360 250 360 160 216 Frame size 4
373/512 x 254 x 260
TSA52-450 315 450 180 270 Frame size 4
373/512 x 254 x 260

Catalogue — Emotron TSA / PDF 5 — page 5

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 5

Emotron TSA softstarter with integrated bypass
Typical motor power at mains voltage 575 V and 690 V

Rating according to AC53b norm.

(1) Normal duty: Start current = 3 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(2) Heavy duty: Start current = 5 x In.soft, Start time = 15 s (size 1) or 30 s (Size 2 - 4), 10 starts / hour.
(3) H1= Height of enclosure, H2=Total height

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: Emotron TSA; 575 V / 690 V. AC53b: normal starting current 3 x In_soft; heavy 5 x In_soft. Start time 15 s for size1, 30 s for sizes2–4;10 starts/hour. H1 enclosure height; H2 total height.

Emotron TSA specifications — PDF page 5

Model Normal duty: Power @575 V (hp) Normal duty: Power @690 V (kW) Normal duty: Rated current (A) Heavy duty: Power @575 V (hp) Heavy duty: Power @690 V (kW) Heavy duty: Rated current (A) Frame size / dimensions H1/H2 x W x D (mm)
TSA69-016 15 11 16 7.5 7.5 10 Frame size 1
246/340 x 126 x 188
TSA69-022 20 18.5 22 10 11 12 Frame size 1
246/340 x 126 x 188
TSA69-030 25 22 30 15 15 18 Frame size 1
246/340 x 126 x 188
TSA69-036 30 30 36 20 18.5 21 Frame size 1
246/340 x 126 x 188
TSA69-042 40 37 42 25 22 25 Frame size 1
246/340 x 126 x 188
TSA69-056 50 45 56 30 30 33 Frame size 1
246/340 x 126 x 188
TSA69-070 60 55 70 40 37 42 Frame size 2
246/340 x 126 x 188
TSA69-085 75 75 85 50 45 51 Frame size 2
246/340 x 126 x 188
TSA69-100 100 90 100 60 55 60 Frame size 2
246/340 x 126 x 188
TSA69-140 125 132 140 75 75 84 Frame size 3
285/380 x 196 x 235
TSA69-170 150 160 170 100 90 102 Frame size 3
285/380 x 196 x 235
TSA69-200 200 200 200 125 110 120 Frame size 3
285/380 x 196 x 235
TSA69-240 250 250 240 150 132 144 Frame size 4
373/512 x 254 x 260
TSA69-300 300 315 300 150 160 180 Frame size 4
373/512 x 254 x 260
TSA69-360 350 355 360 200 200 216 Frame size 4
373/512 x 254 x 260
TSA69-450 450 450 450 250 250 270 Frame size 4
373/512 x 254 x 260

Catalogue — Emotron MSF / PDF 6 — page 6

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 6

Emotron MSF softstarter, the heavy duty solid state softstarter

Main features

UL 508

GOST R

• Robust metal enclosure softstarter with power range:
4 kW - 1.6 MW, 200 - 690 V, 3-ph.
• Solid state 3-phase control type softstarter with heavy duty nominal rating.
• Torque control start and stop modes for minimized start currents.
• Dynamic vector braking and counter current braking modes available.

• Motor I2t protection and isolated thermistor input as standard.
• Load monitor function for protection of load machinery.
• IP20 protection for sizes 17 - 835 A, IP00 for sizes 1000 - 1400 A.

Emotron MSF softstarter the
proven softstarter for heavy duty
applications.

Supplier logo panel shows CE, UL 508, cULus Listed and GOST R. Logos and named standards are historical source claims, not confirmation of current certification scope or validity.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Catalogue — Emotron MSF / PDF 7 — page 7

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 7

Emotron MSF softstarter, 525 V type
Typical motor power at mains voltage 400 V

Rating according to AC53a norm.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: Emotron MSF; 525 V type; typical power at 400 V / 460 V. AC53a normal3.0-30:50-10; heavy5.0-30:50-10. Model suffixes are literal within stated voltage type; do not combine voltage versions.

Emotron MSF specifications — PDF page 7

Model Normal duty: Power @400 V (kW) Normal duty: Power @460 V (hp) Normal duty: Rated current (A) Heavy duty: Power @400 V (kW) Heavy duty: Power @460 V (hp) Heavy duty: Rated current (A) Frame size / dimensions H x W x D (mm)
MSF-017 11 15 22 7.5 10 17 Frame size 1
320 x 126 x 260
-030 18.5 25 37 15 20 30 Frame size 1
320 x 126 x 260
-045 30 40 60 22 30 45 Frame size 1
320 x 126 x 260
-060 37 50 72 30 40 60 Frame size 1
320 x 126 x 260
-075 45 60 85 37 60 75 Frame size 1
320 x 126 x 260
-085 45 75 96 45 60 85 Frame size 1
320 x 126 x 260
-110 75 100 134 55 75 110 Frame size 2
400 x 176 x 260
-145 75 125 156 75 100 145 Frame size 2
400 x 176 x 260
-170 110 150 210 90 125 170 Frame size 3B
500 x 260 x 260
-210 132 200 250 110 150 210 Frame size 3B
500 x 260 x 260
-250 132 200 262 132 200 250 Frame size 3B
500 x 260 x 260
-310 200 300 370 160 250 310 Frame size 4
532 x 547 x 278
-370 250 350 450 200 300 370 Frame size 4
532 x 547 x 278
-450 315 450 549 250 350 450 Frame size 4
532 x 547 x 278
-570 400 600 710 315 500 570 Frame size 5
687 x 640 x 302
-710 450 700 835 400 600 710 Frame size 5
687 x 640 x 302
-835 500 800 960 450 700 835 Frame size 5
687 x 640 x 302
-1000 630 900 1125 560 800 1 000 Frame size 6
900 x 875 x 336
-1400 900 1250 1650 800 1000 1 400 Frame size 6
900 x 875 x 336

Catalogue — Emotron MSF / PDF 8 — page 8

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 8

Emotron MSF softstarter, 525 V type
Typical motor power at mains voltage 525 V

Rating according to AC53a norm.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: Emotron MSF; 525 V. AC53a normal3.0-30:50-10; heavy5.0-30:50-10. Model suffixes are literal within stated voltage type; do not combine voltage versions.

Emotron MSF specifications — PDF page 8

Model Normal duty: Power @525 V (kW) Normal duty: Rated current (A) Heavy duty: Power @525 V (kW) Heavy duty: Rated current (A) Frame size / dimensions H x W x D (mm)
MSF-017 15 22 11 17 Frame size 1
320 x 126 x 260
-030 22 37 18,5 30 Frame size 1
320 x 126 x 260
-045 37 60 30 45 Frame size 1
320 x 126 x 260
-060 45 72 37 60 Frame size 1
320 x 126 x 260
-075 55 85 45 75 Frame size 1
320 x 126 x 260
-085 55 96 55 85 Frame size 1
320 x 126 x 260
-110 90 134 75 110 Frame size 2
400 x 176 x 260
-145 110 156 90 145 Frame size 2
400 x 176 x 260
-170 132 210 110 170 Frame size 3B
500 x 260 x 260
-210 160 250 132 210 Frame size 3B
500 x 260 x 260
-250 160 262 160 250 Frame size 3B
500 x 260 x 260
-310 250 370 200 310 Frame size 4
532 x 547 x 278
-370 315 450 250 370 Frame size 4
532 x 547 x 278
-450 400 549 315 450 Frame size 4
532 x 547 x 278
-570 500 710 400 570 Frame size 5
687 x 640 x 302
-710 560 835 500 710 Frame size 5
687 x 640 x 302
-835 710 960 560 835 Frame size 5
687 x 640 x 302
-1000 800 1125 710 1 000 Frame size 6
900 x 875 x 336
-1400 1250 1650 1000 1 400 Frame size 6
900 x 875 x 336

Catalogue — Emotron MSF / PDF 9 — page 9

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 9

Emotron MSF softstarter, 690 V type
Typical motor power at mains voltage 575 V and 690 V

Rating according to AC53a norm.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: Emotron MSF; 575 V / 690 V. AC53a normal3.0-30:50-10; heavy5.0-30:50-10. Model suffixes are literal within stated voltage type; do not combine voltage versions.

Emotron MSF specifications — PDF page 9

Model Normal duty: Power @575 V (hp) Normal duty: Power @690 V (kW) Normal duty: Rated current (A) Heavy duty: Power @575 V (hp) Heavy duty: Power @690 V (kW) Heavy duty: Rated current (A) Frame size / dimensions H x W x D (mm)
MSF-017 20 18,5 22 15 15 17 Frame size 1
320 x 126 x 260
-030 30 30 37 25 22 30 Frame size 1
320 x 126 x 260
-045 50 55 60 40 37 45 Frame size 1
320 x 126 x 260
-060 60 55 72 50 55 60 Frame size 1
320 x 126 x 260
-075 75 75 85 75 55 75 Frame size 1
320 x 126 x 260
-085 75 90 90 75 75 85 Frame size 1
320 x 126 x 260
-110 125 110 134 100 90 110 Frame size 2
400 x 176 x 260
-145 150 132 156 150 132 145 Frame size 2
400 x 176 x 260
-170 200 200 210 150 160 170 Frame size 3B
500 x 260 x 260
-210 250 250 250 200 200 210 Frame size 3B
500 x 260 x 260
-250 250 250 262 250 250 250 Frame size 3B
500 x 260 x 260
-310 400 355 370 300 315 310 Frame size 4
532 x 547 x 278
-370 500 400 450 400 355 370 Frame size 4
532 x 547 x 278
-450 600 560 549 500 400 450 Frame size 4
532 x 547 x 278
-570 700 630 640 600 560 570 Frame size 5
687 x 640 x 302
-710 800 800 835 700 710 710 Frame size 5
687 x 640 x 302
-835 900 900 880 800 800 835 Frame size 5
687 x 640 x 302
-1000 1250 1120 1125 1000 1000 1 000 Frame size 6
900 x 875 x 336
-1400 1500 1600 1524 1500 1400 1 400 Frame size 6
900 x 875 x 336

Catalogue — General and environmental specifications — page 10

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 10

TSA power-loss asterisk refers to Emotron TSA instruction manual chapter13 for details.

Context: Normal operation, storage and higher-temperature derating are separate scopes. IEC classes are source statements, not independent conformance verification.

Table conditions: Separate TSA/MSF columns. * TSA instruction manual chapter13. TSA control tolerance here differs from interface page14 ±10%; both retained.

Table conditions: Source environmental limits; no computed derated values or extended model applicability.

Table conditions: Storage only; not operating limits.

General specifications — PDF page 10

Parameter TSA MSF
Mains voltage 200–525V +10%/-15%;200–690V +10%/-15% 200–525V ±10%;200–690V +5%/-10%
Control supply voltage 100–240V +10%/-15%,single phase 100–240V ±10%,single phase;380–500V ±10%
Number of fully controlled phases 3 3
Mains and control frequency 50/60Hz ±10% 50/60Hz ±10%
Power loss (% of Pmot) 0.2%* if10starts/hour 0.6%

Environmental normal operation — PDF page 10

Parameter Normal operation
Nominal ambient temperature 0°C–40°C (see Table1)
Atmospheric pressure 86–106kPa
Relative humidity,non-condensing Max95%,non-condensing
Contamination according to IEC60721-3-3 Chemically active3C3: conformal coating on all TSA printed circuit boards, optional forMSF. Mechanically active3S1: no sand; dust<0.01mg/m³; deposited<0.4mg/(m²*h). Biological3B1: no harmful biological attacks from mould,fungus,animals,etc.
Vibrations IEC60721-3-3 mechanical3M4:2–9Hz,3.0mm and9–20Hz,acc.1g(10m/s²)
Altitude 0–1,000m;max4,000m with1%/100m derating above1,000m

Storage conditions — PDF page 10

Parameter Storage condition
Temperature -25 to+70°C
Atmospheric pressure 86–106kPa
Relative humidity,non-condensing Max95%,non-condensing

Catalogue — Temperature derating and dimensions — page 11

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 11

Source nominal maximum operating ambient40°C. Higher temperatures require reduced output current according to Table1.

TSA H1=enclosure height;H2=total height including cable interface.

Context: Model ranges retained as printed ranges, not expanded to assumed individual model IDs. TSA weight23,5 uses source decimal comma.

Table conditions: Above nominal40°C only. Different upper-temperature limits retained; no combined altitude/temperature derating calculated.

Table conditions: H1 enclosure height;H2 total height including cable interface. Physical sizes as printed; no dimension geometry inferred.

Table conditions: MSF H is a single height, not TSA H1/H2. Range-specific convection/fan mounting retained.

Table1 ambient temperature and possible derating — PDF page 11

Model Rated max temp. Possible output current derating
Emotron TSA 40°C -2%/°C to max+15°C(55°C)
Emotron MSF 40°C -2%/°C to max+10°C(50°C)

TSA dimensions weights cooling mounting — PDF page 11

Emotron TSA model Frame size H1/H2 x W x D mm Weight kg Cooling/Mounting
TSA-016 to-056 1 246/340 x126 x188 5.5 Convection/Vertical
TSA-070 to-100 2 246/340 x126 x188 5.7 Fan/Vertical & Horizontal
TSA-140 to-200 3 285/380 x196 x235 13 Fan/Vertical & Horizontal
TSA-240 to-450 4 373/512 x254 x260 23,5 Fan/Vertical & Horizontal

MSF dimensions weights cooling mounting — PDF page 11

Emotron MSF model Frame size H x W x D mm Weight kg Cooling/Mounting
MSF-017 to-030 1 320 x126 x260 6.7 Convection/Vertical
MSF-045 to-085 1 320 x126 x260 6.9 Fan/Vertical & Horizontal
MSF-110 to-145 2 400 x176 x260 12 Fan/Vertical & Horizontal
MSF-170 to-250 3B 500 x260 x260 20 Fan/Vertical & Horizontal
MSF-310 to-450 4 532 x547 x278 46 Fan/Vertical & Horizontal
MSF-570 to-835 5 687 x640 x302 80 Fan/Vertical & Horizontal
MSF-1000 to-1400 6 900 x875 x336 175 Fan/Vertical & Horizontal

Catalogue — TSA/MSF comparison / PDF 12 — page 12

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 12

Basic I/O data

1) For max 1 % inaccuracy.
See “User interface data” on page 13 for connection data and default settings.

Emotron TSA recommended load fuse

Recommended slow fuses for protection against overload.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: Basic I/O comparison; multiline parameter/value groups retain source order. Printed empty cells are not zero. Footnote1: max1% inaccuracy. TSA recommended slow fuses protect against overload.

TSA/MSF comparison specifications — PDF page 12

Parameter/context Emotron TSA Emotron MSF
Control signal inputs:
Analogue (differential), 1 input
Analogue voltage/current
Resolution
Input impedance
0-10V, 2-10V / 0-20 mA, 4-20 mA
12 bit
Volt signal 20 kΩ,
Current signal 250 Ω.
0-10V, 2-10V / 0-20 mA, 4-20 mA
10 bit
Volt signal 125 kΩ,
Current signal 100 Ω.
Digital: 4 inputs
Input voltage
Max. input voltage
Input impedance
0-4 V → 0; 8-27 V → 1.
Max. 37 V for 10 sec.
≤3.3 VDC: 4.7 kΩ. - ≥3.3 VDC: 3.6 kΩ
0-3 V → 0; 8-27 V → 1
Max. 37 V for 10 sec
0 VDC: 2.2 kΩ.
Control signal outputs:
Analogue, 1 channel
Output voltage/current
Min. load impedance for voltage signal 1)
Maximum load impedance for current signal 1)
Resolution
0-10 V, 2-10 V / 0-20 mA, 4-20 mA
700 Ω
700 Ω
12 bit
0-10V, 2-10V / 0-20 mA, 4-20 mA
700 Ω
750 Ω.
8 bits
Relays, 3 pcs
Contacts Relay 1 and 2: 1-pole closing contact
(NO).
Relay 3: 1-pole change-over contact
(NO/NC).
250 VAC 8A or 24 VDC 8A resistive.
250 VAC, 3A inductive. Min. 100 mA.
Relay 1 and 2 : 1-pole closing contact
(NO).
Relay 3: 1-pole change-over contact
(NO/NC).
8 A, 250 VAC or 24 VDC resistive load;
3 A, 250 VAC inductive load (PF 0.4).
Reference voltages
Output voltage
Short-circuit current(∞)
Output voltage (for AnIn)
Short-circuit current(∞)
+24 VDC+5%
Max current 50 mA
+10VDC ±5%
Max 10 mA short circuit and overload
proof.
+12 VDC ±5%
Max current 50 mA

TSA/MSF comparison specifications — PDF page 12

TSA model Recommended slow load fuse (A)
- 016 35
- 022 50
- 030 63
- 036 80
- 042 100
- 056 125
- 070 160
- 085 200

TSA/MSF comparison specifications — PDF page 12

TSA model Recommended slow load fuse (A)
- 100 250
- 140 355
- 170 400
- 200 500
- 240 630
- 300 900
- 360 1000
- 450 1400

Catalogue — TSA/MSF comparison / PDF 13 — page 13

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 13

Emotron TSA semiconductor fuses
Emotron MSF semiconductor fuses

Emotron MSF UL/cUL fuses

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Table conditions: TSA/MSF semiconductor fuse selections and MSF UL/cUL fuse table are distinct scopes. Semiconductor i²t values apply at700V. Blank and dash cells are not substituted; source certification claims only.

TSA/MSF comparison specifications — PDF page 13

TSA model Maximum value fuse (A) i²t fuse at700 V (A²s)
- 016 50 1 500
- 022 70 2 800
- 030 100 3 600
- 036 125 6 900
- 042 150 11 000
- 056 175 14 000
- 070 250 42 000
- 085 300 55 000
- 100 400 99 000
- 140 500 160 000
- 170 600 222 000
- 200 700 332 000
- 240 800 433 000
- 300 1 000 950 000
- 360 1 200 1 470 000
- 450 1 400 1 890 000

TSA/MSF comparison specifications — PDF page 13

MSF model Maximum value fuse (source heading A; cells contain part codes) i²t fuse at700 V (A²s)
- 017 FWP-80A 2 400
- 030 FWP-125A 7 300
- 045 FWP-150A 11 700
- 060 FWP-175A 16 700
- 075 FWP-250A 42 500
- 085 FWP-300A 71 200
- 110 FWP-350A 95 600
- 145 FWP-450A 250 000
- 170 FWP-700A 300 000
- 210 FWP-700A 300 000
- 250 FWP-800A 450 000
- 310 FWP-800A 450 000
- 370 FWP-1000A 600 000
- 450 FWJ-1200A 1 470 000
- 570 FWJ-1400A 1 890 000
- 710 FWJ-1800A 3 710 000
- 835 FWJ-2000A 5 320 000
- 1000 FWJ-2000A 5 320 000
- 1400 <12 000 000

TSA/MSF comparison specifications — PDF page 13

MSF model Fuse type for UL Maximum UL rating (A) Fuse type for cUL Maximum cUL rating (A)
- 017 Any UL listed fuse 80 Bussman, FWP 80
- 030 Any UL listed fuse 125 Bussman, FWP 125
- 045 Any UL listed fuse 225 Bussman, FWP 150
- 060 Any UL listed fuse 250 Bussman, FWP 175
- 075 Any UL listed fuse 300 Bussman, FWP 250
- 085 Any UL listed fuse 350 Bussman, FWP 300
- 110 Any UL listed fuse 500 Bussman, FWP 350
- 145 Any UL listed fuse 600 Bussman, FWP 450
- 170 Any UL listed fuse 800 Bussman, FWP 700
- 210 Any UL listed fuse 1000 Bussman, FWP 700
- 250 Any UL listed fuse 1000 Bussman, FWP 800
- 310 Any UL listed fuse or circuit breaker 1400 Any CSA listed fuse or circuit breaker 1400
- 370 Any UL listed fuse or circuit breaker 1800 Any CSA listed fuse or circuit breaker 1800
- 450 Any UL listed fuse or circuit breaker 2100 Any CSA listed fuse or circuit breaker 2100
- 570 Any UL listed fuse or circuit breaker 2100 Any CSA listed fuse or circuit breaker 2100
- 710 Any UL listed fuse or circuit breaker 2500 Any CSA listed fuse or circuit breaker 2500
- 835 Any UL listed fuse or circuit breaker 2800 Any CSA listed fuse or circuit breaker 2800
- 1000 - - -
- 1400 - - -

Catalogue — TSA user interface terminal table — page 14

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 14

All analogue and digital inputs/outputs are programmable; asterisk denotes default selection.

Schematic annotations: motorT1/T2/T3;control supply100–240VAC ±10%;analogue0–10V/4–20mA;RS232(non-isol.) Ext.Panel/PC;option board communication options.

Context: Terminal mapping transcribed from printed table; source diagram remains authority for topology. Page14 TSA control-supply ±10% differs from general page10 +10%/-15%.

Table conditions: Default functions only; programmable. Literal voltage and terminal identity retained.

Table conditions: Merged name/function cells expanded by terminal only. Not-printed markers retain blank columns. Wiring topology not reconstructed.

TSA control board terminals — PDF page 14

Terminal Name Function(default)
11 DigIn1 Run FWD
12 DigIn2 Stop
13 10VDC Supply voltage for analogue input
14 AnIn Process value
15 GND Signal ground(Common)
16 DigIn3 Set Ctrl1
17 DigIn4 Reset
18 +24V +24VDC supply voltage
19 AnOut 0 to motor nom.current
20 +24V +24VDC supply voltage

TSA power board terminals — PDF page 14

Terminal Name/context Contact designation Function(default)
PE [not printed] [not printed] Protective Earth
N [not printed] [not printed] Control supply100–240VAC ±10%
L [not printed] [not printed] Control supply100–240VAC ±10%
21 Relay1 NO Operation
22 Relay1 C Operation
23 Relay2 NO Not used
24 Relay2 C Not used
31 Relay3 NO Trip
32 Relay3 C Trip
33 Relay3 NC Trip
69 [not printed] [not printed] PTC thermistor input(isolated)
70 [not printed] [not printed] PTC thermistor input(isolated)

Catalogue — MSF user interface terminal table — page 15

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 15

All analogue and digital inputs/outputs are programmable; asterisk denotes default selection.

Schematic annotations: motorT1/T2/T3;control supply100–240VAC ±10%;control-supply terminal labels01/02/PE;analogue0–10V/4–20mA;current transformer1/2/common75/76/77;communication options.

Context: Source power-board table usesN/L for control supply while diagram uses01/02. No inferred equivalence. Relay3 terminal32 isNC and33 isC here, unlike TSA32C/33NC.

Table conditions: MSF separate fromTSA; terminal14 function blank in source table. Do not copy TSA process-value function.

Table conditions: Merged table cells expanded only within visible boundaries. Diagram01/02 versus tableN/L unresolved. Source exact terminal mappings, not wiring instructions.

MSF control board terminals — PDF page 15

Terminal Name Function(default)
11 DigIn1 Start
12 DigIn2 Stop
13 12VDC Supply voltage for analogue input
14 AnIn [not printed]
15 GND Signal ground
16 DigIn3 Par set1
17 DigIn4 Par set2
18 +12V +12VDC supply voltage
19 AnOut 0 to motor nominal current

MSF power board terminals — PDF page 15

Terminal Name/context Contact designation Function(default)
PE [not printed] [not printed] Protective Earth
N [not printed] [not printed] Control supply100–240VAC ±10%
L [not printed] [not printed] Control supply100–240VAC ±10%
21 Relay1 NO Operation
22 Relay1 C Operation
23 Relay2 NO Full voltage
24 Relay2 C Full voltage
31 Relay3 NO All alarms
32 Relay3 NC All alarms
33 Relay3 C All alarms
69 [not printed] [not printed] PTC thermistor input
70 [not printed] [not printed] PTC thermistor input
75 [not printed] [not printed] L1/T1 current transformer
76 [not printed] [not printed] L3/T3 current transformer
77 [not printed] [not printed] Common for75–76

Catalogue — Emotron TSA / PDF 16 — page 16

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 16

Standard options for Emotron TSA

Support for 2 option boards plus 1 communication option.

I/O board

3 extra relay outputs (230 VAC/5 A
NO/NC). 3 extra 24 V /3.2 kΩ (AC or
DC) differential digital inputs, all
programmable. Inputs providing
50 VAC/DC isolation between
channels.

Maximum 2 I/O boards can be
built -in per TSA softstarter.

Part no. 01-3876-51

PTC/PT100 board

1 PTC isolated input conforming DIN
44081/44082.
Max 6 PTC thermistors can be
connected in series to PTC input.
Also including 3 PT100 inputs,
2/3/4-wire, conforming EN 60751.

Maximum 2 PTC/PT100 boards can
be built -in per TSA softstarter

Part no. 01-3876-58

Fieldbus - Profibus

Fieldbus option module for Profibus
DP or DP V1 communication. Use
9-pin D-sub connector.
Baud rates: 9.6 kbits/s - 12 Mbits/s
supported.

Typical TSA response time = 10 ms
(not including any fieldbus delays).

Part no. 01-5385-55

Fieldbus - DeviceNet

Fieldbus option module for
DeviceNet communication.
Baud rates: 125 - 500 kbits/s
supported.
Typical TSA response time = 10 ms
(not including any fieldbus delays).

Part no. 01-5385-56

Ethernet - Modbus/TCP

Industrial Ethernet option module for
Modbus/TCP protocol. RJ45 type
connector.
Baud rates: 10 or 100 Mbits/s
supported.

Typical TSA response time = 10 ms
(not including any ethernet delays).

Part no. 01-5385-59

Ethernet - EtherCAT

Industrial Ethernet option module for
EtherCAT protocol.
Baud rate: 100 Mbits/s
Typical TSA response time = 10 ms
(not including any ethernet delays).

Part no. 01-5385-60

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Catalogue — Emotron TSA / PDF 17 — page 17

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 17

Ethernet - Profinet IO 1-port
Industrial Ethernet option module for
Profinet IO (RT) protocol.
Baud rate: 100 Mbits/s
Typical TSA response time = 10 ms
(not including any ethernet delays).

Part no. 01-5385-61

Ethernet - Profinet IO 2-port
Industrial Ethernet option module for
Profinet IO (RT) protocol.
Baud rate: 100 Mbits/s
Typical TSA response time = 10 ms
(not including any ethernet delays).

Part no. 01-5385-62

USB isolated

Isolated USB serial communication
module. For Modbus RTU
comm.protocol.
Baude rates: 2.4 - 115.2 kbits/s
supported.
Typical TSA response time = 10 ms

Part no. 01-5385-63

RS485 isolated

Isolated RS485 serial
communication module. For Modbus
RTU comm.protocol.
Baude rate: 2.4 - 115.2 kbits/s
supported.
Typical TSA response time = 10 ms

Part no. 01-5385-54

External control panel

External control panel IP54 suitable
for mounting on a cabinet door.
Kit complete with control panel,
mounting frame and 3 m cable

Part no. 01-5406-00

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Catalogue — EmoSoftCom scope ambiguous / PDF 18 — page 18

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 18

EmoSoftCom

Connect a PC with a standard RS232
cable to D-sub on top of TSA unit or
via USB/RS485 /Modbus - TCP
Comm. modules (Optional).
EmoSoftCom PC software makes it
possible to perform signal recordings

and save/load parameter backup
data, for example during
service & maintenance.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Catalogue — Emotron MSF / PDF 19 — page 19

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 19

Standard options for Emotron MSF

Support for 1 communication option.

External control panel (ECP)

External control panel IP54 suitable
for mounting on a cabinet door.
Part no. 01-3060-00

Serial communication

Modbus RTU (RS232/RS485) for
serial communication.
Part no. 01-1733-00

Fieldbus - Profibus

Fieldbus option for Profibus DP
communication.
Part no. 01-1734-01

Fieldbus - DeviceNet

Fieldbus option for DeviceNet
communication.
Part no. 01-1736-01

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Catalogue — Emotron MSF / PDF 20 — page 20

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 20

Cable entry box

Cable entry box for connection of
cable glands.
For MSF size 1 (017 - 085).
Part no. 01-2553-00

Cable set for external current transformers

Extension cable set for externally
mounted current transformers. Used
with bypass contactors.
Part no. 01-2020-00

Coated boards

All option boards are also available as
coated, recommended e.g. for sewer
pump applications (sulphide) or
installations with occasional high
humidity (if machine room
installation or tropical climate).
IEC60721-3-3 gases class 3C3, solid
particles class 3S2.

Context: All readable prose and tables; named family/duty/voltage conditions and option part-number associations retained.

Context: Shared document attaches to P035 MSF and P036 TSA; use the named family, voltage, duty and option section for each claim. EmoSoftCom page18 has conflicting family header/text.

Catalogue — CAD reference — page 21

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 21

Source states2D/3D CAD drawings for Emotron AC drives, softstarters and monitors are available viawww.emotron.com. Intended users include consultants,installers and machine builders.

Context: Website reference not followed in local-only batch; this does not prove CAD collection completeness or current availability. Small illustration is not a dimensioned drawing.

Catalogue — Lined notes page — page 22

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 22

Context: Blank ruled note area with printed page21 and document footer; no technical values to extract.

Catalogue — Brand slogan — page 23

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 23

We put all our energy into saving yours.

Context: Marketing slogan and document footer only; no technical values.

Catalogue — Source edition and contact — page 24

Emotron_Softstarter_Technical-catalogue_01-5552-01_English.pdf · P035, P036 · source page 24

Emotron is now CG.

Context: Source-era identity and contacts only; not live-verified. Printed issue:2014-09. This is not a statement that it is the current edition.

Table conditions: Printed source values, not contact verification. Website string preserved as printed, not silently split into a route.

Printed edition and source contact — PDF page 24

Source label/context Source value
Publisher CG Drives & Automation
Address Mörsaregatan12,Box22225,SE-25024 Helsingborg,Sweden
Telephone +46 42 16 99 00
Fax +46 42 16 99 49
Website string www.cgglobal.com/www.emotron.com
Document reference 01-5552-01r1
Language/date English,2014-09

Manual — COVER — page 1

Manual reference: physical PDF page 1. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Cover title, softwareversion and product illustrations; example LCDvalues not treated as specifications. Reviewedtext: Emotron TSA | Softstarter | Instruction manual | English | Software version 1.0X No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — BLANK_PAGE — page 2

Manual reference: physical PDF page 2. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Blank page visually confirmed. Reviewedtext: No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Edition/frontmatter. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 3

Manual reference: physical PDF page 3. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Emotron TSA softstarter

INSTRUCTION MANUAL - ENGLISH

Software version 1.0X

Document number: 01-5980-01

Edition: R0

Date of release: 13-05-2013

© Copyright CG Drives & Automation Sweden AB 2013

CG Drives & Automation Sweden AB retains the right to change

specifications and illustrations in the text, without prior notification.

The contents of this document may not be copied without the explicit

permission of CG Drives & Automation Sweden AB.

Manual — BLANK_PAGE — page 4

Manual reference: physical PDF page 4. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Blank page visually confirmed. Reviewedtext: No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Safety instructions. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 5

Manual reference: physical PDF page 5. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Safety instructions

Congratulations for choosing a product from CG Drives &

Automation!

Before you begin with the installation, commissioning or

powering up the unit for the first time it is very important

that you carefully study this instruction manual.

The following symbols can appear in this manual or on the

product itself. Always read these first before continuing.

Safety

The softstarter should be installed in a cabinet or in an

electrical control room.

•

The device must be installed by trained personnel.

Disconnect all power sources before servicing.

Always use standard commercial fuses, slow blow e.g.

gl, gG types, to protect the wiring and prevent short

circuiting. To protect the thyristors against short-circuit

currents, superfast semiconductor fuses can be used if

preferred. The normal guarantee is valid even if superfast

semiconductor fuses are not used.

Operating and maintenance

personnel

  1. Read the whole instruction manual before installing and

putting the equipment into operation.

  1. During all work (operation, maintenance, repairs, etc.)

observe the switch-off procedures given in this

instruction as well as any other operating instruction for

the driven machine or system. See Emergency below.

  1. The operator must avoid any working methods which

reduce the safety of the device.

  1. The operator must do what he can to ensure that no

unauthorised person is working on the device.

  1. The operator must immediately report any changes to

the device which reduce its safety to the user.

  1. The user must undertake all necessary measures to

operate the device in perfect condition only.

Phase compensation capacitor

If a phase compensation capacitor is to be used, it must be

connected at the inlet of the softstarter, not between the

motor and the softstarter.

Installation of spare parts

We expressly point out that any spare parts and accessories

not supplied by us have also not been tested or approved by

us.

Installing and/or using such products can have a negative

effect on the characteristics designed for your device. The

manufacturer is not liable for damage arising as a result of

using non-original parts and accessories.

Emergency

You can switch the device off at any time with the mains

switch connected before the softstarter (both motor and

control supply voltage must be switched off).

General warnings

Alarms

Never disregard an alarm. Always check and remedy the

cause of an alarm.

NOTE: Additional information as an aid to avoid

problems.

CAUTION!

Failure to follow these instructions can result

in malfunction or damage to the softstarter.

WARNING!

in serious injury to the user in addition to

serious damage to the softstarter.

!

Make sure that all safety measures have

been taken before starting the motor in order

to avoid personal injury.

Never operate the softstarter with the front

cover removed.

been taken before switching on the power

supply.

Manual reference: physical PDF page 6. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 2 | CG Drives & Automation 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Contents navigation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 7

Manual reference: physical PDF page 7. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Contents

Safety instructions ......................................... 1

Contents.......................................................... 3

1.

Introduction..................................................... 5

1.1

Delivery and unpacking ............................................ 5

1.2

Using of the instruction manual............................... 5

1.3

Warranty .................................................................... 5

1.4

Type code number..................................................... 5

1.5

Standards .................................................................. 6

1.5.1

Product standard for EMC ........................................ 6

1.6

Dismantling and scrapping....................................... 6

1.6.1

Disposal of old electrical and electronic

equipment ................................................................. 6

1.7

Glossary ..................................................................... 7

1.7.1

Abbreviations and symbols....................................... 7

1.7.2

Definitions.................................................................. 7

2.

Mounting......................................................... 9

2.1

Installation in a cabinet ............................................ 9

2.1.1

Cooling ....................................................................... 9

2.1.2

Mechanical specifications and drawings .............. 10

3.

Connections................................................. 11

3.1

Mains and motor connections ............................... 12

3.2

Board layout and connectors ................................. 14

3.3

Control signal connections..................................... 15

3.4

Wiring examples...................................................... 16

4.

Application guidelines ................................ 21

4.1

Softstarter dimensioning according to AC-53b..... 21

4.2

Applications rating .................................................. 21

4.3

The Application Functions List ............................... 23

4.4

Special conditions................................................... 26

4.4.1

Small motor or low load.......................................... 26

4.4.2

Ambient temperature below 0°C........................... 26

4.4.3

Pump control with softstarter and AC drive

together ................................................................... 26

4.4.4

Starting with counter-clockwise (reverse) rotating

loads......................................................................... 26

4.4.5

Running motors connected in parallel................... 26

4.4.6

Running motors linked together ............................ 26

4.4.7

Heat dissipation in cabinets................................... 26

4.4.8

Insulation test on motor ......................................... 26

4.4.9

Operation above 1,000 m ...................................... 26

4.4.10

Aggressive environment conditions....................... 26

4.4.11

IT earthing system................................................... 26

4.4.12

Earth fault relay....................................................... 27

4.4.13

Other control voltage .............................................. 27

5.

Getting started............................................. 29

5.1

Check list ................................................................. 29

5.2

Mains and motor connection ................................. 29

5.2.1

Connect the mains cables...................................... 29

5.2.2

Connect the motor cables ...................................... 29

5.2.3

Connect the control supply voltage........................ 29

5.3

Default toggle loop.................................................. 30

5.4

Remote I/O operation............................................. 30

5.5

Control panel operation.......................................... 31

6.

Operation via the control panel .................. 33

6.1

Display ..................................................................... 33

6.2

LED indicators ......................................................... 34

6.3

Control keys............................................................. 34

6.4

Function keys .......................................................... 34

6.4.1

+/- key function....................................................... 35

6.4.2

Jog key function....................................................... 35

6.5

Toggle and Loc/Rem Key ....................................... 35

6.5.1

Toggle function........................................................ 35

6.5.2

Loc/Rem function ................................................... 36

6.6

The menu structure ................................................ 37

6.6.1

The main menu ....................................................... 37

7.

Main features ............................................... 39

7.1

Setting Start, Stop and Run functions................... 39

7.1.1

Start and stop control............................................. 39

7.1.2

Start and stop methods.......................................... 39

7.1.3

Jog functions ........................................................... 40

7.1.4

Start/Stop signal priority ........................................ 40

7.1.5

Setting motor data .................................................. 40

7.1.6

Process information................................................ 40

7.2

Working with parameter sets ................................. 41

7.2.1

Control of parameter sets ...................................... 41

7.2.2

Configuration of parameter sets............................ 42

7.2.3

Handling motor data in parameter sets ................ 42

7.2.4

Using the control panel memory............................ 42

7.3

Applying limitations, alarms and autoreset........... 45

7.3.1

Alarm types and actions ......................................... 45

7.3.2

Alarm settings.......................................................... 45

7.3.3

Alarm indications .................................................... 45

7.3.4

Load monitor function ............................................ 46

7.3.5

Reset and autoreset ............................................... 50

7.4

Programmable I/O .................................................. 51

7.5

Logical functions ..................................................... 51

7.6

Remote control functions....................................... 51

7.6.1

Default settings of the Run/Stop/Reset

functions.................................................................. 51

7.6.2

Enable and Stop functions ..................................... 52

7.6.3

Reset and Autoreset operation .............................. 52

8.

Functionality................................................. 55

8.1

Preferred View [100]............................................... 56

8.1.1

1st Line [110].......................................................... 57

8.1.2

2nd Line [120] ........................................................ 57

8.2

Main Setup [200].................................................... 57

8.2.1

Operation setup [210] ............................................ 57

8.2.2

Remote signal Level/Edge [21A] ........................... 60

8.2.3

Motor Data [220] .................................................... 60

8.2.4

Motor protection [230] ........................................... 62

8.2.5

Parameter set handling [240]................................ 66

8.2.6

Autoreset [250]....................................................... 69

Manual — P036; Contents navigation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 8

Manual reference: physical PDF page 8. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.2.7

Serial Communication [260].................................. 73

8.3

Process [300].......................................................... 76

8.3.1

View Process Value [310]....................................... 76

8.3.2

Process Settings [320] ........................................... 76

8.3.3

Start setting [330]................................................... 78

8.3.4

Stop Setting [340]................................................... 80

8.3.5

Jog [350].................................................................. 83

8.4

Load Monitor and Process Protection [400]......... 84

8.4.1

Load Monitor [410]................................................. 84

8.4.2

Process protection [420]........................................ 88

8.4.3

Mains Protection [430]........................................... 89

8.5

I/O [500].................................................................. 91

8.5.1

Analogue Input [510].............................................. 91

8.5.2

Digital Inputs [520]................................................. 94

8.5.3

Analogue Output [530] ........................................... 95

8.5.4

Relays [550] ............................................................ 97

8.5.5

Virtual I/Os [560] .................................................... 99

8.6

Logical Functions and Timers [600] .................... 100

8.6.1

Comparators [610] ............................................... 100

8.6.2

Logic outputs [620]............................................... 105

8.6.3

Timers [630].......................................................... 109

8.6.4

SR Flip-flops [640] ................................................ 110

8.6.5

Counters [650]...................................................... 112

8.6.6

Clock Logic [660] .................................................. 113

8.7

Operation/Status [700]........................................ 114

8.7.1

Operation values [710]......................................... 114

8.7.2

Status [720] .......................................................... 116

8.7.3

Stored Values [730].............................................. 119

8.7.4

Real time clock settings [740] ............................. 119

8.8

View Trip Log [800] ............................................... 120

8.8.1

Trip Message Log [810]........................................ 120

8.8.2

Trip Messages [820] - [890]................................. 121

8.8.3

Reset Trip Log [8A0] ............................................. 121

8.9

System Data [900]................................................ 121

8.9.1

TSA Data [920]...................................................... 121

9.

Serial communication ............................... 123

9.1

Modbus RTU .......................................................... 123

9.2

Parameter sets...................................................... 123

9.3

Motor data............................................................. 124

9.4

Start and stop commands.................................... 124

9.5

Process value ........................................................ 124

9.6

Description of the EInt formats............................ 125

10.

Softstarter theory ...................................... 127

10.1

Background theory................................................ 127

10.2

Reduced voltage starting...................................... 128

10.3

Other starting methods......................................... 130

10.4

Use of softstarters with torque control................ 132

11.

Troubleshooting, Diagnoses and

Maintenance.............................................. 133

11.1

Trip conditions, causes and remedial action ...... 133

11.1.1

Technically qualified personnel............................ 133

11.1.2

Opening the softstarter......................................... 133

11.2

Maintenance ......................................................... 133

11.3

Troubleshooting list............................................... 134

12.

Options........................................................ 137

12.1

External control panel........................................... 137

12.2

EmoSoftCom.......................................................... 137

12.3

I/O Board ............................................................... 137

12.4

PTC/PT100............................................................ 137

12.5

Serial communication and fieldbus..................... 137

13.

Technical data............................................ 139

13.1

General electrical specifications.......................... 141

13.2

Semi-conductor fuses........................................... 141

13.3

Environmental conditions..................................... 142

13.3.1

Derating at high temperature............................... 142

13.3.2

Derating at high altitude....................................... 143

13.4

Control power- and I/O signal connectors........... 144

Index ........................................................... 145

Appendix 1: Menu List............................... 147

Appendix 2: Trip message communication data 164

Manual — P036; Introduction and source claims. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 9

Manual reference: physical PDF page 9. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1.

Introduction

The Emotron TSA softstarter is intended for controlling the

start and stop of standard three phase asynchronous motors.

A built-in powerful digital signal processor (DSP) gives the

softstarter high performance and very good control of the

starting and stopping of the application.

Several options are available, listed in chapter 12. page 137,

that enable you to customize the softstarter for your specific

needs.

Users

This instruction manual is intended for:

•

installation engineers

maintenance engineers

operators

service engineers

Motors

The softstarter is suitable for use with standard 3-phase

asynchronous motors. Contact your supplier for details.

1.1

Delivery and unpacking

Check for any visible signs of damage. Inform your supplier

immediately of any damage found. Do not install the

softstarter if damaged.

Check that all items are present and that the type number is

correct.

1.2

Using of the instruction

manual

Check that the software version number on the first page of

this manual matches the software version in the softstarter.

See chapter 8.9.1 page 121.

With help of the index and the table of contents it is easy to

track individual functions and find out how to use and set

them.

The Quick Start Guide can be put in a cabinet so that it is

always easy to access in case of an emergency.

1.3

Warranty

The warranty applies when the equipment is installed,

operated and maintained according to instructions in this

instruction manual. Duration of warranty is as per contract.

Faults that arise due to faulty installation or operation are

not covered by the warranty.

1.4

Type code number

Fig. 1 gives an example of the type code numbering used for

the Emotron TSA softstarter. This identification will be

required for type specific information when mounting and

installing. The code number is located on the product label,

on the right side of the unit (when viewed from the front).

Fig. 1

NOTE: Read this instruction manual carefully before

installing, connecting or working with the softstarter.

TSA 52 -016 -23 N N N

—

A

Position number:

10 11

Table 1

Figure1 type-code example positions1–11: TSA |52|016|23|N|N|N|—|A|A|—. The example is not a configured customer product; descriptions and option codes inTable1 govern.

Table1 type code; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Table1 type code — PDF page 9

Source row Position Configuration Description
1 1 Type TSA
2 2 Main supply voltage 52 = Max 525 V mains
69 = Max 690 V mains
3 3 Current rating 016 = 16 A
-
- 1K8 = 1800 A
4 4 Control voltage 23=230 V
5 5 Option position 1 N=No option
P=PTC/PT100
I=I/O board
6 6 Option position 2 N=No option
P=PTC/PT100
I=I/O board
7 7 Communication
option
N=No option
A=Profinet IO 1-port
B=Profinet IO 2-port
D=DeviceNet
M=Modbus/TCP
P=Profibus
R=RS485
U=USB
8 8 IT-net option — =No option
I=IT-net
9 9 Brand label A=Standard
10 10 Software A=Standard software
11 11 Standard — =CE approved

Manual — P036; Introduction and source claims. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 10

Manual reference: physical PDF page 10. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1.5

Standards

The softstarters described in this instruction manual comply

with the standards listed in Table 2. For the declarations of

conformity and manufacturer’s certificate, contact your

supplier for more information or visit www.emotron.com or

www.cgglobal.com.

1.5.1Product standard for EMC

The Emotron TSA softstarter complies with the product

standard EN(IEC) 60947-4-2: 2007. The standard

Emotron TSA softstarter is designed to meet the EMC

requirements according to category C1.

1.6

Dismantling and scrapping

The enclosures of the Emotron TSA softstarters are made

from recyclable material such as aluminium, iron and

plastic. Each softstarter contains a number of components

demanding special treatment. The circuit boards contain

small amounts of tin and lead. Any local or national

regulations in force for the disposal and recycling of these

materials must be complied with.

1.6.1Disposal of old electrical and

electronic equipment

This symbol on the product or on its packaging indicates

that this product shall be taken to the applicable collection

point for the recycling of electrical and electronic

equipment. By ensuring this product is disposed of correctly,

you will help prevent potentially negative consequences for

the environment and human health, which could otherwise

be caused by inappropriate waste handling of this product.

The recycling of materials will help to conserve natural

resources. For more detailed information about recycling

this product, please contact the local distributor of the

product.

Table 2

Table2 standards source claims; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table2 standards source claims — PDF page 10

Source row Market Standard Description
1 European EMC Directive 2004/108/EC
2 ⟦null: no independent source value⟧ Low Voltage Directive 2006/95/EC
3 ⟦null: no independent source value⟧ WEEE Directive 2002/96/EC
4 All EN 60204-1 Safety of machinery - Electrical equipment of machines
Part 1: General requirements.
5 ⟦null: no independent source value⟧ EN(IEC)60947-4-2:
2007
Contactors and motor starters
Part 3: EMC requirements and specific test methods.
EMC Directive: Declaration of Conformity and CE marking
6 ⟦null: no independent source value⟧ EN(IEC)60947-4-2:
2007
Contactors and motor starters
Safety requirements - Electrical, thermal and energy.
Low Voltage Directive: Declaration of Conformity and CE marking
7 ⟦null: no independent source value⟧ IEC 60721-3-3 Classification of environmental conditions. Air quality chemical vapours, unit in
operation. Chemical gases 3C3, Solid particles 3S1.
8 ⟦null: no independent source value⟧ UL508C UL Safety standard for Power Conversion Equipment. Pending.
9 USA UL 840 UL Safety standard for Power Conversion Equipment. Pending.

Manual — P036; Introduction and source claims. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 11

Manual reference: physical PDF page 11. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1.7

Glossary

1.7.1 Abbreviations and symbols

In this manual the following abbreviations are used:

1.7.2 Definitions

In this manual the following definitions are used:

*) Calculation of nominal motor torque:

Table 3

Abbreviations

Table 4

Definitions

Tn Nm

[

]

Pn mot kW

×

nn mot rpm


=

Tn lb ft

Pn mot hp


Table3 last symbol is a padlock: the function cannot be changed in run mode. Printed torque formulas: T_n[Nm] = 9550 × P_n_mot[kW] / n_n_mot[rpm]; T_n[lb.ft] = 5252 × P_n_mot[hp] / n_n_mot[rpm]. These are source formulas; no design calculation performed.

Table4 definitions; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Table3 abbreviations; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Table4 definitions — PDF page 11

Source row Name Description Unit
1 I
n_soft
Nominal softstarter current [A ]
rms
2 I
n_mot
Nominal motor current [A ]
rms
3 P
n_soft
Nominal softstarter power [kW] or [hp]
4 P
n_mot
Nominal motor power [kW] or [hp]
5 T
n
Nominal motor torque* [Nm] or [lb.ft]
6 n
n_mot
Nominal speed of motor [rpm]
7 cosφ
n
Nominal motor power factor (dimensionless)
8 U 3-phase mains supply voltage [V ]
rms
9 U
n_mot
Nominal motor voltage [V]

Table3 abbreviations — PDF page 11

Source row Abbreviation/
symbol
Description
1 CP Control panel, the programming and
presentation unit on the softstarter
2 CB Control board
3 I2t The amount of energy losses, heating up the
motor.
4 PTC Positive Temperature Coefficient
(temperature sensor, also known as
thermistor)
5 PB-PTC Power board PTC input
6 RMS Root Mean Square value
7 FLC Full Load Current
8 DOL Direct On-Line
9 EInt Communication format
10 UInt Communication format (Unsigned Integer)
11 Int Communication format (Integer)
12 Long Communication format (Integer Long)
13 ⟦blank source cell⟧ The function cannot be changed in run mode

Manual reference: physical PDF page 12. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 8 | Introduction | CG Drives & Automation 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Mounting specifications. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 13

Manual reference: physical PDF page 13. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2.

Mounting

This chapter describes how to mount the Emotron TSA

softstarter. Before mounting it is recommended that the

installation is planned out:

•

Be sure that the softstarter suits the mounting location.

The mounting site must support the weight of the

softstarter.

Will the softstarter continuously withstand vibrations

and/or shocks?

Consider using a vibration damper.

Check ambient conditions, ratings, required cooling air

flow, compatibility of the motor, etc.

Do you know how the softstarter will be lifted and

transported?

Make sure that the installation is performed in accordance

with the local safety regulations, and in accordance with

DIN VDE 0100 for setting up power installations.

Care must be taken to ensure that personnel do not come

into contact with live circuit components.

2.1

Installation in a cabinet

When installing the softstarter:

Ensure that the cabinet will be sufficiently ventilated

after the installation.

Keep the minimum free space, as listed inTable 5.

Ensure that air can flow freely from the bottom to the

top.

The Emotron TSA softstarters are delivered as enclosed

versions with front access cover. The units have top and

bottom entry for cables etc., see Chapter 3. page 11.

2.1.1 Cooling

WARNING!

Never operate the softstarter with the front

cover removed.

NOTE: When installing the softstarter, make sure it does

not come into contact with live components. The heat

generated must be dispersed via the cooling fins to

prevent damage to the thyristors (free circulation of air).

Table 5

Minimum free space

*) Above: Cabinet roof to softstarter or softstarter to softstarter

Table5 minimum free space; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table5 minimum free space — PDF page 13

Source row TSA frame size Minimum above[mm]* Minimum below[mm] Minimum side[mm]
1 1 100 100 0
2 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — P036; Mounting specifications. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 14

Manual reference: physical PDF page 14. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

2.1.2 Mechanical specifications and drawings

*) H1 = Height of enclosure, H2 = Total height

Fig. 2

Dimensions for Emotron TSA frame size 1 and 2.

Fig. 3

Dimensions for Emotron TSA frame size 1 and 2,

bottom view.

Mounting schemes

Emotron TSA Size 1 - 2

Fig. 4

Hole pattern for Emotron TSA frame size 1 and 2.

On our websites www.cgglobal.com and www.emotron.com

it is possible to download a full-size template for positioning

of the fixing holes.

Table 6

H1

H2

104.5

Ø 6,5 (x 4)

Figures2/3 source dimensions frame1/2: H1enclosure246mm,H2total296mm,W126mm,D188mm. Figure4 mountinghole pattern labels11mmleftoffset,104.5mmhorizontalcentres,11mmtopoffset,273mmverticalcentres,diameter6.5mm×4holes. Originalgeometry/source template governs mounting; nogeometryinferredbeyondprintedlabels.

Table6 mechanical specifications; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.

Table6 mechanical specifications — PDF page 14

Source row TSA frame size H1/H2×W×D[mm] Mounting position Weight[kg] Connection busbars/pressnut[mm] PE screw Cooling system Protection class
1 1 246/296 x 126 x 188 Vertical 5.5 15 x 4, Cu (M6) M5 Convection IP20
2 2 246/296 x 126 x 188 Vertical 5.7 15 x 4, Cu (M6) M5 Fan IP20

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 15

Manual reference: physical PDF page 15. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.

Connections

The installation description in this chapter follows the EMC

standards and the Machinery Directive.

If the softstarter is temporarily stored before being

connected, please check the technical data for environmental

conditions section 13.3, page 142. If the softstarter is moved

from a cold storage room to the location where it is to be

installed, condensation could appear on the unit. Allow the

softstarter to become fully acclimatised and wait until any

visible condensation has evaporated before connecting any

supply voltages.

Cables

Dimension the mains and motor cables according to local

regulations and the nominal current of the motor.

It is not necessary to use shielded motor cables together with

the Emotron TSA softstarter. This is due to its very low

radiated emissions.

Neither is it necessary to use shielded mains supply cables

for the Emotron TSA softstarter.

For the control connections, it is not necessary to use

shielded control cables, however with the exception of the

option board connections (see section 3.2, page 14) for

which it is recommended to use flexible wire with a braided

type of shield.

NOTE: For the Emotron TSA softstarter it is not

mandatory to use shielded cables to fulfil the EMC

regulations (section 1.5, page 6). The only exception is

when connecting option board cables, for which there is

an earthing plate that serves as an attachment for the

shielded control cables (see Fig. 9 on page 14).

NOTE: For UL-approval use 75°C copper wire only.

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 16

Manual reference: physical PDF page 16. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.1

Mains and motor connections

Fig. 5

Mains and motor connections for Emotron TSA Size 1-2.

Emotron TSA frame size 1 - 2

  1. 3-phase mains supply connection, L1, L2, L3

  2. Protective earth (PE) connection for mains supply

  3. Motor power supply connection T1, T2, T3

  4. Motor earth,

connection

Fig. 6

Mains, motor and control supply voltage connection

PE

T1

T2

T3

L1

L2

L3

WARNING!

Leakage current may occur from the

thyristors when a 3-phase mains supply is

connected. Full voltage can be detected if no

motor is connected.

Table 7

Tightening torque for bolts [Nm].

100 - 240 VAC

Figure5 labels:1 mainsL1/L2/L3;2PE mains;3motorT1/T2/T3;4motor earth. Figure6control100–240VAC terminalsL,N,PE are distinct from3phasemains. MotorU,V,W,earth shown. Source wiring image retained; not independent installation approval.

Table7 bolt tightening torque; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.

Table7 bolt tightening torque — PDF page 16

Source row TSA frame size Motor or mains cable bolt torque[Nm] PE cable bolt torque[Nm]
1 1 8 5
2 2 8 5

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 17

Manual reference: physical PDF page 17. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 7

Busbar distances Emotron TSA Size 1 and 2

When the Mains and motor cables are connected, mount

the cable covers according to Fig. 8.

Fig. 8

Mount the cable covers.

Table 8

Busbar distances.

W3

W2 W1

W1

W2

Figure7 labels W3,W2,W1 aboveandbelow theunit, pairedwithTable8dimensions. Figure8 cablecoverfasteningarrow explicitly3Nm. It is separatefromTable7motor/main8Nm,PE5Nm.

Table8 busbar distances; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.

Table8 busbar distances — PDF page 17

Source row TSA frame size Dist.W1[mm] Dist.W2[mm] Dist.W3[mm]
1 1 23 40 40
2 2 23 40 40

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 18

Manual reference: physical PDF page 18. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.2

Board layout and connectors

This section contains general information about the power

board and control board for each Emotron TSA size. For

additional information about special conditions refer to

section 4.4, page 26. For a description of the available

options, go to chapter 12. page 137.

Isolation

The control board in the Emotron TSA product is a

Separated Extra Low Voltage (SELV) circuit. This means

that this board is safely separated from other circuits that

carry higher voltages and is isolated from earth and

protective earth conductors of other circuits. The PTC

circuit on the power board is separated from the control

board SELV circuit with a separation rated for:

•

Double insulation when used in softstarters rated up to

525 VAC.

Basic insulation when used in softstarters rated up to

690 VAC.

It is recommended that the PTC/PT100 sensors are always

separated from live parts with at least basic insulation for the

relevant voltage.

Fig. 9

Board layout for Emotron TSA Size 1-2.

Emotron TSA Size 1 - 2

  1. Control supply voltage connection PE, N, L (power

board).

  1. Earthing plate with slots for tie wraps for fixation and

securing of control signal cables and option board cables.

This plate is connected to earth for earthing of shielded

cables.

  1. S1 jumper for U/I selection of analogue input

  2. Option board ribbon cable connector

  3. Communication module (option)

  4. LED indicators (visible through perforation):

  5. Red and blue for communication signals

  6. Green indicating power on

  7. Clock battery, type CR 2032, 3 V

  8. Terminals for DigIn/AnIn/AnOut signals (control

board)

  1. Terminals for relay output signals and PTC connection

(power board)

  1. RS232, using 9-pin female D-sub connector. For

temporary connection of a personal computer or

connection of external control panel (option)

WARNING!

For softstarters rated higher than 525 VAC, it

is mandatory to have at least basic insulation

from the temperature sensor towards live

voltage.

For safety reasons the protective earth (PE)

for the control supply must be connected.

Table 9

Control signal cable dimension and stripping lenght

Figure9 callouts1controlPE/N/L;2shield-earthingplate;3S1U/Ijumper;4optionribbon;5communicationsoption;6LEDs;7CR2032battery3V;8digital/analoguecontrolterminals;9relay/PTCterminals;10female9pinRS232. LabelassociationsareonlyforthesourceTSA1–2drawing.

Table9 control signal cable dimensions; TSA frame1/2only, source units and shared cells retained. Native automatic grid incorrectly merged columns; rebuilt from actual ruled rectangle bounds, not inferred values. Source engineering claims only.

Table9 control signal cable dimensions — PDF page 18

Source row TSA size Maximum cable dimension Recommended stripping length
1 1 - 2 Flexible: 1.5 mm2
Solid: 2.5 mm2
6 mm*

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 19

Manual reference: physical PDF page 19. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

3.3

Control signal connections

Fig. 10 Control board and power board connections.

WARNING!

The same external supply

voltage level (max 24 VDC or

max 250 VAC) must be used

for all three output relays

(terminals 21-33).

Do not mix AC and DC voltage.

Make sure to use the same voltage level

within this terminal section, otherwise

the softstarter may be damaged.

Table 10

Power board connections

Table 11

Control board connections

Figure10 terminalrowspowerPE,N,L;21,22,23,24,31,32,33,69,70;control11–20andS1U/Ijumper. Table10row31NO,32C,33NC is retained even thoughfunctiontextandlaterdiagramR3switcharmat33conflict. No correctedterminalassignment.

Table10 power board connections; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table11 control board connections; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Table10 power board connections — PDF page 19

Source row Terminal number Contact designation Function Electrical characteristics
1 PE ⟦blank source cell⟧ Protective Earth Protective grounding
2 N ⟦blank source cell⟧ Control supply voltage 100-240 VAC ±10%
3 L ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 21 NO Programmable relay 1. Factory setting is “Operation”
with indication by closing contact on terminals 21 to
22.
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC 8 A
resistive, 250 VAC, 3 A inductive. See Warning.
6 22 C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 23 NO Programmable relay 2. Factory setting is “Off” with
indication by closing contact on terminals 23 to 24.
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC 8 A
resistive, 250 VAC, 3 A inductive. See Warning.
8 24 C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
9 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 31 NO Programmable relay 3. Factory setting is “Trip”.
Indication by closing contact on terminals 31 to 33
and opening contact on 32 to 33.
1-pole change-over contact (NO/NC), 250 VAC 8A or 24
VDC 8A resistive, 250 VAC, 3A inductive. See Warning.
11 32 C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
12 33 NC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 69-70 ⟦blank source cell⟧ PTC Thermistor input Alarm level 2.4 kΩ. Switch back level 2.2 kΩ.

Table11 control board connections — PDF page 19

Source row Terminal number Contact designation Function Electrical characteristics
1 11 ⟦blank source cell⟧ Digital input 1. Factory setting is “Run FWD” 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec.
Impedance: <3.3 VDC: 4.7 kΩ. - >3.3 VDC: 3.6 kΩ
2 12 ⟦blank source cell⟧ Digital input 2. Factory setting is “Stop”. ⟦null: no independent source value⟧
3 13 ⟦blank source cell⟧ Control signal supply voltage to analogue input. +10 VDC ±5%. Max. current from +10 VDC: 10 mA.
Short circuit-proof and overload-proof.
4 14 ⟦blank source cell⟧ Analogue input, 0-10 V, 2-10 V, 0-20 mA and
4-20 mA. Factory setting is “4-20 mA”.
S1 jumper for U/I selection.
Impedance to terminal 15 (0 VDC) voltage signal:
20 kΩ, current signal: 250 Ω.
5 15 ⟦blank source cell⟧ GND (common) 0 VDC signal ground
6 16 ⟦blank source cell⟧ Digital input 3. Factory setting is “Set Ctrl 1” 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec.
Impedance: <3.3 VDC: 4.7 kΩ. - >3.3 VDC: 3.6 kΩ
7 17 ⟦blank source cell⟧ Digital input 4. Factory setting is “Reset” ⟦null: no independent source value⟧
8 18 ⟦blank source cell⟧ Control signal supply 1, voltage to digital input. +24 VDC ±5%. Max. current from +24 VDC = 50 mA.
Short circuit-proof and overload-proof.
9 19 ⟦blank source cell⟧ Analogue output. Factory setting is “Current”. Analogue output contact:
0-10 V, 2-10 V; min load impedance 700 Ω
0-20 mA and 4-20 mA; max load impedance 500 Ω
10 20 ⟦blank source cell⟧ Control signal supply 2, voltage to digital input. +24 VDC ±5%. Max. current from +24 VDC = 50 mA.
Short circuit-proof and overload-proof.

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 20

Manual reference: physical PDF page 20. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 11 Control cable feedthrough.

3.4

Wiring examples

Always ensure the installation complies with the appropriate

local regulations.

Minimum wiring for remote controlled start is shown in Fig.

19, page 30, in which level control is applied, menu [21A].

Example 1: Standard type of start wiring

•

Connect Protective Earth (PE) to earth bar marked PE

and Motor earth the earth bar marked

see chapter

3.1 page 12.

Connect the softstarter between the 3-phase mains

supply (L1, L2 and L3) and the motor (T1, T2 and T3).

Connect the control supply voltage (100-240 VAC) to

terminals N and L and the protective earth wire to

terminal PE.

Connect start and stop control to DigIn 1 and 2

(terminals 11 and 12) with 24 V supplied from terminal

18.

Connect relay R1 (terminals 21 and 22) to the contactor

– the softstarter then controls the mains contactor (for

factory configuration of R1).

.

Fig. 12 Standard wiring example.

NOTE: Shielded control cable must be used for option

board connections.

U I

Shielded control signal cable

Earthing

plate with

slots for tie

wraps

NOTE: If local regulations state that a mains contactor should be used, relay R1 can control this. Always use standard

commercial, slow blow fuses, e.g. gl or gG types, to protect the wiring and prevent short circuiting. To protect the thyristors

against short-circuit currents, ultrafast semiconductor fuses can be used if preferred. The normal guarantee is valid even if

ultrafast semiconductor fuses are not used. All signal inputs and outputs are galvanically insulated from the mains supply.

DigIn 1

DigIn 2

+10 V

AnIn

GND

DigIn 3

DigIn 4

+24 V

AnOut

Relay 1

Relay 2

Relay 3

Stop

Run FWD

PTC

Figure11U/Ijumper,earthplate/tiewrapslots,shieldedcontrolcable. Figure12mainsL1,L2,L3/PE;separate100–240V~±10%L,N,PE;relayR1(21,22),R2(23,24),R3(33,31,32);PTC69,70;control11DigIn1RunFWD,12DigIn2Stop,13+10V,14AnIn,15GND,16DigIn3,17DigIn4,18+24V,19AnOut,20+24V. Figureisexample,notindependentvalidatedwiring.

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 21

Manual reference: physical PDF page 21. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 2: Extended wiring

Fig. 13 gives a wiring example with the following functions:

•

Analogue start/stop via process value, see description on

page 91.

Analogue output, see section 8.5.3, page 95

Motor PTC input, see description of Thermal motor

protection in section 8.2.4, page 62.

Fig. 13 Extended wiring example, using digital and analogue inputs and outputs.

Reset

Stop

Measuring

Process value

DigIn 1

DigIn 2

+10 V

AnIn

GND

DigIn 3

DigIn 4

+24 V

AnOut

PTC

Relay 1

Relay 2

Relay 3

Run FWD

Figure13extendsstandardexample:Resetbetween17and18;processvalue+to14and−to15;Measuring+to19and−to20asdrawn;motorPTC69/70. Table11describes20as+24V,so measuredreturnlabelassociationisretainedasdiagramclaim,notapprovedconnection. RemainingterminalsandrelayssameprintedlabelsasFig12.

Extended wiring example settings; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Extended wiring example settings — PDF page 21

Source row Menu Description Setting
1 521 Digital input 1 (terminal 11) Run FWD (default)
2 522 Digital input 2 (terminal 12) Stop (default)
3 524 Digital input 4 (terminal 17) Reset (default)
4 511 Analogue input function
(terminal 14)
Process Val (default)
5 531 Analogue output function
(terminal 19)
Current (default)
6 2331 PTC alarm action (terminal 69
and 70)
Hard trip/Soft trip

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 22

Manual reference: physical PDF page 22. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 3: Reverse current brake wiring

The example in Fig. 14 shows the wiring for a reverse

current brake functionality. For further settings, see the

description for “Dynamic Vector Brake” on page 81.

The contactors have to be controlled by the relay outputs of

the softstarter. For relay settings, see menu [550] and Fig. 54,

page 99. The relay (R1) for the first mains contactor (K1) is

set to “RunSignalFWD” in menu [551], and will control the

mains contactor (K1). The second mains contactor (K2) is

controlled by another relay (R2), that is set to

“RevCurrBrake” in menu [552]. During start and full voltage

operation the first contactor (K1) will be activated (Fig. 14,

page 18). For braking R1 will open and the second contactor

(K2) will be activated via R2 to change the phase sequence.

Fig. 14 Reverse current brake wiring example.

DigIn 1

DigIn 2

+10 V

AnIn

GND

DigIn 3

DigIn 4

+24 V

AnOut

Relay 1

Relay 2

Relay 3

Run FWD

Stop

PTC

Figure14showsK1mainandK2phase-reversingcontactors controlledbyR1(21/22)andR2(23/24);R3labels33,31,32;100–240V~±10%L,N,PE;PTC69/70;RunFWD11,Stop12,24V18. MainsL1/L2/L3,motorT1/T2/T3→U/V/W/earth. Physicalwiringgeometryremainssourceonly.

Reverse current brake example settings; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Reverse current brake example settings — PDF page 22

Source row Menu Description Setting
1 521 Digital input 1 (terminal 11) Run FWD (default)
2 522 Digital input 2 (terminal 12) Stop (default)
3 551 Relay 1 (terminals 21 and 22) RunSignalFWD
4 552 Relay 2 (terminals 23 and 24) RevCurrBrake

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 23

Manual reference: physical PDF page 23. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example 4: Reverse start functionality

The digital inputs can be configured to enable starting a

motor in two different directions with the use of the

programmable relays R1 and R2. A connection example is

shown in Fig. 15. For the following description of start

forward/reverse functionality, the following settings for the

digital inputs are assumed.

.

Fig. 15 Connection for start forward/reverse.

The configuration of the relays depends on the requirements

of the application. For applications which do not use the

reverse current brake functionality, the following settings

may be used.

The functionality for both applications (with or without

reverse current functionality) is as follows:

If DigIn 1 “RunFWD” is closed and DigIn 3 “RunREV” is

open, the mains contactor (K1) for running in forward

direction will be activated by relay R1, and the motor will

start in forward direction. DigIn 1 “RunFWD” can be

opened during forward running without any effect. If DigIn

2 “Stop” is opened, the stop settings in menu group [340]

CAUTION!

Very high torque/force can arise when the

motor is reversed from running at full speed

in one direction to running at full speed in the

opposite direction.

WARNING!

If configured according to the description,

relays R1 and R2 will never be activated at

the same time. There is a time delay of 100

ms for the change-over between the relays. However, if

the relays are not configured properly, they may be

activated at the same time.

!

Run FWD

Run REV

Stop

DigIn 1

DigIn 2

+10 V

AnIn

GND

DigIn 3

DigIn 4

+24 V

AnOut

PTC

Relay 1

Relay 2

Figure15forward/reverseexample:K1/K2contactors;RunFWDinput11,Stop12,RunREV16,switchcommons+24V18;sameR1/R2/R3/PTCterminalnumbersaspreviousfigures. Sourcewarnsofhighreversingtorqueand100mschangeoverconditionaloncorrectconfiguration. Figureisnotcertifiedsafetycircuit.

Reverse start digital input example settings; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Reverse start relay settings without reverse-current brake; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Reverse start digital input example settings — PDF page 23

Source row Menu Description Setting
1 521 Digital input 1 (terminal 11) Run FWD (default)
2 522 Digital input 2 (terminal 12) Stop (default)
3 523 Digital input 3 (terminal 16) Run REV

Reverse start relay settings without reverse-current brake — PDF page 23

Source row Menu Description Setting
1 551 Relay 1 (terminals 21 and 22) Operation FWD
2 552 Relay 2 (terminals 23 and 24) Operation REV

Manual — P036; Connections and example wiring. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 24

Manual reference: physical PDF page 24. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

will be performed. When the stop is finished, the mains

contactor for running forward (K1) will be deactivated by

relay R1.

If both DigIn 1 “Stop” and DigIn 3 “RunREV” are closed

while DigIn 1 “RunFWD” is open, the mains contactor for

running in reverse direction (K2) will be activated by relay

R2 and the motor will start in reverse direction. DigIn 3

“RunREV” can be opened during reverse running without

any effect. If DigIn 2 “Stop” is opened, a stop according to

the stop settings in menu group [340] will be performed.

When the stop is finished, the mains contactor for reverse

running (K2) will be deactivated by relay R2.

If both DigIn 1 “RunFWD” and DigIn 3 “RunREV” are

closed at the same time, a stop is performed according to the

stop settings in menu group [340]. In this case no start will

be allowed.

A motor can switch from forward to reverse direction as

follows: Open DigIn 1 “RunFWD” while the motor is

running in forward direction. Then close DigIn 3

“RunREV”. As a result the voltage to the motor is switched

off and the mains contactor for forward running (K1) is

deactivated by relay R1. After a time delay of 100

milliseconds, the mains contactor for reverse running (K2)

will be activated by relay R2, and a start in reverse direction

will be performed. The motor can switch from reverse to

forward running in the same way by opening DigIn 3

“RunREV” while running in reversed direction and then

closing DigIn 1 “RunFWD”.

Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 25

Manual reference: physical PDF page 25. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.

Application guidelines

This chapter is a guide to selecting the correct softstarter

rating and softstarter functionality for different applications.

To make the right choice the following tools are used:

The AC-53 norms

The AC-53 norms are defined in the EN(IEC) 60947-4-

2:2007 standard for electronic softstarters. The purpose of

these norms is to aid in selecting a softstarter with regards to

duty cycle, starts per hour and maximum starting current.

The Applications Rating List

With this list the Emotron TSA softstarter rating type can be

selected depending on the type of application uses, see Table

12, page 22.

The Applications Function List

This table gives an overview of the most common

applications and their challenges. For each application

Emotron TSA softstarter settings are proposed, with

references to the menus used. See Table 13, page 24.

4.1

Softstarter dimensioning

according to AC-53b

The EN(IEC) 60947-4-2:2007 standard defines AC-53b as

a norm for dimensioning of softstarters for continuous

running with a bypass contactor. This is the norm for which

the Emotron TSA is designed.

AC-53b rating example

Explanation of the rating designation (see also Fig. 16):

  1. Rated current (FLC) of softstarter, [Ampere]

  2. Classification (AC-53b for all Emotron TSA models)

  3. Start current expressed as a multiple of FLC

  4. Start time, [seconds]

  5. Bypass time, [seconds]

The example concerns Emotron TSA model 52-056, used

for a pump application. The rating designation indicates a

current rating of 56 A with a start current ratio of 3.0 x FLC

(168 A) for 30 seconds, and with a 330 seconds (5.5

minutes) interval between starts (current via bypass

contactors).

Fig. 16 Duty cycle.

4.2

Applications rating

According to the AC-53b norm a softstarter can have several

current ratings. The Applications Rating List in Table 12,

page 22 shows which rating that is recommended for the

application.

The Emotron TSA model is selected depending on its model

size and on the duty cycle of the application:

AC-53b ratings for Emotron TSA size 1:

•

AC-53b 3.0-15:345 (normal duty with bypass)

AC-53b 5.0-15:345 (heavy duty with bypass)

AC-53b ratings for Emotron TSA size 2 - 6:

AC-53b 3.0-30:330 (normal duty with bypass)

AC-53b 5.0-30:330 (heavy duty with bypass)

Example:

In the previous example, in which the Emotron TSA 52-056

is used for a pump application, the recommended rating is

“normal duty” according to the Applications Rating List.

56 A: AC-53b 3.0 - 30 : 330

①

②

③

④

⑤

NOTE: To select softstarter size it is important to ensure

that not only FLC (Full Load Current) is checked but also

the starting requirements.

Start

Bypass

Time

Start current

Current

operation

Figure16dutycycle plotaxesCurrentI[A],TimeT[s];pulsesStartcurrent,StartintervalandBypassoperation. Rating56A:AC-53b3.0-30:330 examplecallouts1ratedFLC,2classification,3startcurrentmultiple,4startseconds,5bypassseconds;3×56=168A sourceexample. Noadditionalgraphthresholdsinferred.

Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 26

Manual reference: physical PDF page 26. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Applications Rating List

This list gives the typical rating type for the machine or

application, divided in “normal duty” and “heavy duty”

applications (both with bypass). If the machine or

application is not in this list, try to identify a similar

machine or application. If in doubt please contact your

Emotron TSA supplier.

Example:

If the Emotron TSA 52-056 from the previous example is

used in e.g. a roller mill application instead, it would be

rated differently according to the Applications Rating List.

Due to high starting current a roller mill is considered a

heavy duty application, which places greater demands on the

softstarter. The technical data (page 139) indicates that the

TSA 52-056 is downrated to 33 A FLC for heavy duty

applications. If an FLC current of about 56 A is required for

the roller mill, it would be recommended to choose TSA

model 52-100, for which the rated heavy duty current is 60

A.

Table 12

Table12 applications rating list; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Table12 applications rating list — PDF page 26

Source row Industry Normal duty cycle AC53b-3.0 Heavy duty cycle AC53b-5.0
1 General & Water Centrifugal pump
Submersible pump
Compressor, screw
Compressor, reciprocating
Fan
Blower
Conveyor
Mixer
Agitator
2 Metals & Mining Dust collector
Grinder
Belt conveyor
Hammer mill
Rock crusher
Roller conveyor
Roller mill
Tumbler
Wire draw machine
3 Food processing Bottle washer
Slicer
Centrifuge
Dryer
Mill
Palletiser
4 Pulp & Paper ⟦blank source cell⟧ Repulper
Shredder
Trolley
5 Lumber & Wood ⟦blank source cell⟧ Bandsaw
Chipper
Circular saw
Debarker
Planer
Sander
6 Petrochemical ⟦blank source cell⟧ Ball mill
Centrifuge
Extruder
Screw conveyor
7 Transport & Machine ⟦blank source cell⟧ Ball mill
Grinder
Material conveyor
Palletiser
Press
Roller mill
Rotary table
Trolley
Escalator

Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 27

Manual reference: physical PDF page 27. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.3

The Application Functions List

This list gives an overview of many different applications

with their challenges and a possible solution within the

functions of the Emotron TSA.

Description and use of the table:

“Application”

This column gives the various applications. If the machine

or application is not found in this list, try to identify a

similar machine or application. If in doubt please contact

your supplier.

“Challenge”

This column describes possible challenges that are familiar

for this kind of application.

“Emotron TSA Solution”

This column gives the possible solution for the challenge

using one of the functions of the Emotron TSA.

“Menu/Chapter”

This column guides you to the menu, menu group, or

manual section where you find a description of the settings

for the function.

For instance "331=Sqr Torq Ctr", means: set parameter

[331] to “Sqr Torq Ctr.”

Example: Hammer mill

•

Linear torque control (menu [331], selection ”Lin Torq

Ctr”) will give the best results.

Torque boost to overcome high breakaway torque (menu

[337], submenus [3371]and [3372]).

Overload alarm function for jamming protection (menu

[410] “Load Monitor”, with submenus for maximum

alarm)

Stop function reverse current brake (set “Stop Method”

[341] to “Brake”, and menu [344] to “Rev Curr Brk”). It is

possible to set a “Reversed Current Braking Delay” in menu

[346].

Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 28

Manual reference: physical PDF page 28. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

.

Table 13

Application Functions List

Table13 application functions; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table13 application functions — PDF page 28

Source row Application Challenge Emotron TSA Solution Menu/Chapter
1 PUMP Non-linear ramps Square torque control for square loads 331=Sqr Torq Ctr
341=Sqr Torq Ctr
2 ⟦null: no independent source value⟧ Water hammer Square torque control 340
3 ⟦null: no independent source value⟧ High current and peaks during starts Square torque control 330
4 ⟦null: no independent source value⟧ Pump is going in wrong direction Phase reversal alarm 444
5 ⟦null: no independent source value⟧ Dry running Use load monitor minimum alarm 410
6 ⟦null: no independent source value⟧ High load due to dirt in pump Use load monitor maximum alarm 410
7 COMPRESSOR Mechanical shock for compressor, motor and
transmissions
Linear torque control 330
8 ⟦null: no independent source value⟧ Small fuses and low current available. Linear torque control and current limit
at start.
331=Lin Torq Ctr
335
9 ⟦null: no independent source value⟧ Screw compressor going in wrong direction Phase reversal alarm 444
10 ⟦null: no independent source value⟧ Damaged compressor if liquid ammonia
enters the compressor screw.
Use load monitor maximum alarm 410
11 ⟦null: no independent source value⟧ Energy consumption due to compressor
running unloaded
Use load monitor minimum alarm 410
12 BLOWER Mechanical shock for blower, motor and
transmissions. High start current requires
large cables and fuses.
Torque control ensures smooth starts
that minimise mechanical stress.
Start current is minimised by torque-
controlled start.
331=Lin Torq Ctr
13 CONVEYOR Mechanical shocks for transmissions and
transported goods.
Linear torque control 330
14 ⟦null: no independent source value⟧ Loading or unloading conveyors Slow speed and accurate position
control.
350
600
15 ⟦null: no independent source value⟧ Conveyor jammed Use load monitor maximum alarm 410
16 ⟦null: no independent source value⟧ Conveyor belt or chain is off but the motor is
still running
Use load monitor minimum alarm 410
17 ⟦null: no independent source value⟧ Starting after screw conveyor has stopped
due to overload.
JOG in reverse direction and then
starting in forward.
7.1, p. 39
18 ⟦null: no independent source value⟧ Conveyor blocked when starting Locked rotor function 422
19 FAN High starting current in end of ramps Square torque control for square load
characteristics
330
20 ⟦null: no independent source value⟧ Slivering belts. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
21 ⟦null: no independent source value⟧ Fan is going in wrong direction when starting. Catching the motor and stopping
smoothly to zero speed and then
starting in right direction.
331=Sqr Torq Ctr
22 ⟦null: no independent source value⟧ Belt or coupling broken Use load monitor minimum alarm 410
23 ⟦null: no independent source value⟧ Blocked filter or closed damper. ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
24 PLANER High inertia load with high demands on
torque and current control.
Linear torque control gives linear
acceleration and low starting current.
330
25 ⟦null: no independent source value⟧ Need to stop quickly both for emergency and
production efficiency reasons.
Dynamic vector brake without contactor
for medium loads.
341=Brake
344=Dyn Vect Brk
347
26 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Reverse current brake with external
contactor for heavy loads.
341=Brake
344=Rev Curr Brk
27 ⟦null: no independent source value⟧ High speed lines Conveyor speed set from planer shaft
power analogue output.
530
28 ⟦null: no independent source value⟧ Worn out tool Use load monitor maximum alarm 410
29 ⟦null: no independent source value⟧ Broken coupling Use load monitor minimum alarm 410

Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 29

Manual reference: physical PDF page 29. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 13

Application Functions List

Table13 application functions continued; Emotron TSA software1.0X editionR0 release13-05-2013. Physical merged/null cells retain parent evidence; supplier source claims only. No inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table13 application functions continued — PDF page 29

Source row Application Challenge Emotron TSA Solution Menu/Chapter
1 ROCK CRUSHER High inertia Linear torque control gives linear
acceleration and low starting current.
330
2 ⟦null: no independent source value⟧ Heavy load when starting with material Torque boost 337
3 ⟦null: no independent source value⟧ Low power if a diesel powered generator is
used.
Current limit at start 335
4 ⟦null: no independent source value⟧ Wrong material in crusher Use load monitor maximum alarm 410
5 ⟦null: no independent source value⟧ Vibrations during stop Dynamic vector brake without contactor 341=Brake
344=Dyn Vect Brk
347
6 BANDSAW High inertia load with high demands on
torque and current control.
Linear torque ramp gives linear
acceleration and low starting current.
330
7 ⟦null: no independent source value⟧ Need to stop quickly. Dynamic vector brake without contactor
for medium loads.
341=Brake
344=Dyn Vect Brk
347
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Reverse current brake with external
contactor for heavy loads.
341=Brake
344=RevCurr Brk
9 ⟦null: no independent source value⟧ High speed lines Conveyor speed set from bandsaw
shaft power analogue output.
530
10 ⟦null: no independent source value⟧ Worn out saw blade Use load monitor maximum alarm 410
11 ⟦null: no independent source value⟧ Broken coupling, saw blade or belt Use load monitor minimum alarm 410
12 CENTRIFUGE High inertia load Linear torque control gives linear
acceleration and low starting current.
330
13 ⟦null: no independent source value⟧ Too high load or unbalanced centrifuge Use load monitor maximum alarm 410
14 ⟦null: no independent source value⟧ Controlled stop Dynamic vector brake without contactor
for medium loads.
341=Brake
344=Dyn Vect Brk
347
15 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Reverse current brake with external
contactor for heavy loads.
341=Brake
344=Rev Curr Brk
16 ⟦null: no independent source value⟧ Need to open centrifuge in a certain position. Braking down to slow speed and then
positioning control.
340, 350
600, 650
17 MIXER Different materials Linear torque control gives linear
acceleration and low starting current
330
18 ⟦null: no independent source value⟧ Need to control material viscosity Shaft power analogue output 530
19 ⟦null: no independent source value⟧ Broken or damaged blades Use load monitor maximum alarm 410
20 ⟦null: no independent source value⟧ ⟦blank source cell⟧ Use load monitor minimum alarm 410
21 HAMMER MILL Heavy load with high breakaway torque Linear torque control gives linear
acceleration and low starting current.
331=Lin Torq Ctr
22 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Torque boost in beginning of ramp. 337
23 ⟦null: no independent source value⟧ Jamming Use load monitor maximum alarm 410
24 ⟦null: no independent source value⟧ Fast stop Reverse current brake with reversing
contactor for heavy loads.
341=Brake
344=Rev Curr Brk
25 ⟦null: no independent source value⟧ Motor blocked Locked rotor function 422

Manual — P036; Application guidelines. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 30

Manual reference: physical PDF page 30. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.4

Special conditions

4.4.1 Small motor or low load

The minimum load current for the Emotron TSA softstarter

is 10% of the rated current for the softstarter. An exception

is the TSA52-016 for which the minimum load current is

2 A.

Example: TSA52-056 with rated current of 56 A has a

minimum current of 5.6 A.

Please note that this is “minimum load current” and not

minimum rated motor current.

4.4.2 Ambient temperature below

0°C

For ambient temperatures below 0 °C an electric heater or

similar must be installed in the cabinet. The softstarter can

be mounted remotely from the motor since the distance

between the motor and the softstarter is not critical.

4.4.3 Pump control with softstarter

and AC drive together

It is possible, e.g. in a pump station with two or more

pumps, to use one Emotron FDU AC drive on one pump

and softstarters on each of the other pumps. The flow of the

pumps is then controlled by the pump control function in

the Emotron FDU.

4.4.4 Starting with counter-

clockwise (reverse) rotating

loads

It is possible to start a motor clockwise (forward direction),

even if the load and motor are rotating counterclockwise

(reverse direction), e.g. fans. Depending on the speed and

the load “in the wrong direction”. Pleas note that the current

can be quite high.

4.4.5 Running motors connected in

parallel

When starting and running motors connected in parallel,

the total amount of the motor current must be equal or

lower than the rating of the connected softstarter. Please

note that it is not possible to use the internal thermal motor

protection or use other individual settings for each motor.

For instance, the start ramp can only be set for an average

starting ramp for all the connected motors. This means that

the start time may differ from motor to motor. Similarly, the

load monitor alarm levels/margins are applied for the

average shaft power value of the connected motors. In order

to work around this kind of problem, it could be necessary

to deactivate a number of functions and alarms.

For motors connected in parallel, torque control is not

recommended because of the risk of oscillation between the

motors. Voltage control with or without current limit is

recommended instead. The use of the braking functionality

is not recommended for motors connected in parallel.

4.4.6 Running motors linked

together

When starting and running motors mechanically linked

together but with one softstarter connected to each motor,

there are two kinds of operations available. The first is to

start the motors at the same time using voltage control with

or without current limit. The second is to start one motor

first with torque or voltage control and after the motor has

reached full speed, the voltage to the other motors is ramped

up using voltage control.

4.4.7 Heat dissipation in cabinets

For guidelines regarding calculation of heat dissipation in

cabinets, please contact your cabinet supplier. The required

data is found in “Technical Data”, Chapter 13. page 139.

4.4.8 Insulation test on motor

When testing the motor with high voltage e.g. insulation

test, the softstarter must be disconnected from the motor.

This is due to the fact that the softstarter will be seriously

damaged by the high test voltage.

4.4.9 Operation above 1,000 m

All ratings are stated for operation at maximum 1,000 m

over sea level.

If the softstarter is operated at 3,000 m for example, it must

be derated, and it is likely that a higher rated model than

normal is required to fulfil the task. See further information

in section 13.3.2, page 143.

4.4.10 Aggressive environment

conditions

As standard the Emotron TSA is equipped with coated

boards in order to reduce the risk for corrosion. For

specification, see section 13.3, page 142.

4.4.11 IT earthing system

Distribution systems may be equipped with an IT isolated

earthing system, which allows for one earth fault to occur

without interruption of operation. For use in these systems,

the Emotron TSA should be ordered with IT-net option.

If you have a softstarter without IT net option, the

softstarter can be rebuilt. Contact your local CG Drives &

Automation service partner.

Manual — P036; Application guidelines continuation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 31

Manual reference: physical PDF page 31. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

4.4.12Earth fault relay

It is possible to use an earth fault relay to protect motor and

cables (not for human safety). To avoid undesired tripping

due to filter capacitor charging currents, choose a short-time

delayed residual current device rated for 30 mA leakage

current.

4.4.13Other control voltage

The power board must be connected to 100-240 VAC single

phase control supply. If this is not available a transformer

must be used. This transformer should be connected as in

Fig. 17.

The transformer should be capable of supplying a power of

50 VA or more. This item is not included in the range of

CG options.

Fig. 17 Example of wiring when using transformer for 380 - 500 VAC

Transformer

Emotron TSA

Figure17 source example transformer input380–500VAC, output100–240VAC toTSA control supply. Transformer minimum50VA per adjacenttext. Wiringgeometry remainsoriginal; no design inferred.

Manual reference: physical PDF page 32. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 28 | Application guidelines | CG Drives & Automation 01-5924-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Getting started. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 33

Manual reference: physical PDF page 33. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.

Getting started

This chapter is a step by step guide that will show you the

quickest way to get the motor shaft turning. We will show

you two examples: with remote control and control panel

operation.

5.1

Check list

•

Check that the motor and supply voltage corresponds to

the values on the rating plate of the softstarter.

Mount the softstarter (Chapter 2. page 9 ).

Connect the 3-phase mains supply cables to the connec-

tions on top of the softstarter (section 3.1, page 12).

Connect the motor cables to the connections in the

bottom of the softstarter (section 3.1, page 12).

Connect control supply voltage (section 3.1, page 12).

Ensure that the installation complies with the

appropriate local regulations.

Remote (I/O) operation:

Connect the I/O control cables (section 3.3, page 15).

Switch on the 3-phase mains supply voltage and control

supply voltage.

Select language (menu [211], section 8.2.1, page 57).

Set the motor data (menu [220] - [227], section 8.2.3,

page 60).

Set real time clock (menu [740], section 8.7.4, page 119)

Perform a test run with external I/O start command.

Control panel operation:

Select keyboard control (menu [2151], section 7.1.1,

page 39).

Perform a test run from the control panel.

5.2

Mains and motor

connection

Connect the softstarter between the 3-phase mains supply

and the motor. For the respective connections, see the table

below).

Dimension the mains and motor cables according to local

regulations. The cables must be able to carry the softstarter

load current (see “Technical data” on page 139).

5.2.1 Connect the mains cables

The connection of the mains cables is shown in section 3.1,

page 12. As standard the Emotron TSA softstarter has a

built-in RFI mains filter that complies with category C1

which is suited for environment B.

5.2.2 Connect the motor cables

The connection of the motor cables is shown in section 3.1,

page 12.

5.2.3 Connect the control supply

voltage

The control supply voltage is connected to the terminals

marked N and L on the power board (Fig. 19).

WARNING!

Mounting, wiring and setting the device into

operation must be carried out by properly

trained and qualified personnel.

Table 14

Mains and motor connection

In order to work safely the mains earth must

be connected to PE and the motor earth to

.

Table14 secondrow contains earthsymbol beneathT1,T2,T3, associated withMotor earth. Warning calls mains earthPE andmotor earthsymbol. Native symbol omission is not an absent protective-earth requirement.

Table14 mains and motor connections; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Table14 mains and motor connections — PDF page 33

Source row Terminal marking Connection
1 L1, L2, L3
PE
Mains supply, 3-phase
Protective earth
2 T1, T2, T3 Motor output, 3-phase
Motor earth

Manual — P036; Getting started. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 34

Manual reference: physical PDF page 34. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

5.3

Default toggle loop

In order to make it easier to setup the initial data, there is a

default toggle loop, see Fig. 18. This loop contains the

necessary menus that need to be set before starting the

softstarter the first time. Press the Toggle key to enter e.g.

menu [740], then use the next keys to go to the submenus

([741] and so forth) and enter the parameters. When you

press the Toggle key again, the next toggle menu is

displayed.

Fig. 18 Default toggle loop

5.4

Remote I/O operation

Generally, external signals are used to control the softstarter

and the motor. This example demonstrates the set-up for a

standard motor for which an external start button will be

used.

Connect the control signal cables

The minimum wiring for a remote controlled start is shown

in Fig. 19 below. In this example the motor/softstarter will

run with forward rotation. For other wiring examples, see

section 3.4, page 16.

It is recommended to use screened control signal cables with

flexible wire up to 1.5 mm2, or solid wire up to 2.5 mm2.

Connect an external start button between terminal 18 (+24

VDC) and 11 (DigIn 1, Run FWD). Change the setting in

menu [21A] to “Level” (level control). Change setting for

DigIn 2 in menu [522] to “Off”.

Fig. 19 Minimum wiring for remote controlled start using

level control.

Switch on the voltage

Once the 3-phase mains and control supply voltage is

switched on, the softstarter is started and the internal fan

(only in model sizes 2-6) will run for 5 seconds.

Set the basic data

Fig. 20 Default toggle loop

Enter the basic data, i.e. language, time, and motor data for

the connected motor. The motor data is used in the

calculation of complete operational data in the softstarter.

Change settings using the keys on the control panel. For

further information about the control panel and menu

structure, see Chapter 6. page 33.

NOTE: Default setting is edge control (menu [21A] set to

“Edge”) in order to comply with the Machine directive.

Toggle loop

To submenus

Start /Stop

Power board

Control board

100-240V

PE

Figures18/20 toggle loop:100→211→221→222→223→224→225→227→740→100, with740submenus741→… viaNEXT. Figure19 Start/Stop switch connects18(+24V) to11;21A→Level,522→Off. Power terminalsPE,01,02; diagramcontrol100–240V. Example only.

Manual — P036; Getting started. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 35

Manual reference: physical PDF page 35. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Menu [100], “Preferred View” is displayed at start.

  1. Press

to display menu [211] “Language”.

Select Language using the

and

keys.

Confirm with

.

  1. Press

to display menu [221] “Motor Volts” and set

nominal motor voltage. Change the value using the

keys. Confirm with

Perform in a similar way the following settings:

  1. Set motor frequency [222].

  2. Set motor power [223].

  3. Set motor current [224].

  4. Set motor speed [225].

  5. Set power factor (cos φ) [227].

  6. Press

to display menu [740]”Clock setting”.

  1. Press

to display menu [741]” Time”. Change the

time using the

keys. To activate setting of

hh.mm.ss respectively, use the

or

  1. Press

to display menu [742]” Date” and set date.

  1. Switch off power supply.

  2. Connect digital and analogue inputs/outputs as in

Fig. 19.

  1. Switch on power supply.

Test run with external start command

Now the installation is finished, press the external start

button (contact closed) to start the motor.

To stop the motor, disconnect the start command (contact

open).

5.5

Control panel operation

A manual test run can be executed via the control panel.

This example demonstrates the set-up to carry out for a

standard motor.

Switch on the voltage

Once the 3-phase mains and control supply voltage is

switched on, the softstarter is started and the internal fan

(only in sizes 2-6) will run for 5 seconds.

Set the basic data

Enter the basic data, i.e. language, time, and motor data for

the connected motor. Perform this the same way as for

“Remote I/O operation” on page 30.

Follow the steps 1 - 10.

Then press

until you return to menu [100],”Preferred

View”.

Select manual control

to display menu [200], “Main Setup”.

to display menu [210], “Operation”.

  1. Press

until you get to menu [215] “Action Control”,

then press

to go to submenu [2151] “Run/Stop

Control”.

  1. Select “Int keyb” using the key

Press

to confirm.

Test run from control panel

Press the

key on the control panel to run the motor

forward.

To stop the motor, press the

key on the control panel.

NOTE: For selection of other start method than the

default “linear torque control”, see section 7.1.2, page

NOTE: When the internal bypass contactor is activated,

three distinct clicks are heard.

NOTE: For selection of other stop method than the

default “Coast”, see section 7.1.2, page 35 and menu

[341].

NQE1

TGO

Graphic-key reading: setup1Toggle→211,Plus/Minusselect,Enterconfirm;2Toggle→221,Plus/Minus,Enter;3–7menus222/223/224/225/227.8Toggle→740;9Enter→741,Plus/Minuschange,Prev/Nextselecthh.mm.ss,Enterconfirm;10Enter→742,Enterconfirm. Manualcontrol:ESCto100,Nextto200,Enterto210,Nextto215,Enterto2151,PlusIntkeyb,Enter. TestStartFWDthenStop/Reset. These are literal supplier key instructions, not revised workflow.

Manual reference: physical PDF page 36. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 32 | Getting started | CG Drives & Automation 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 37

Manual reference: physical PDF page 37. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.

Operation via the control panel

The control panel displays the status of the softstarter and is

used to set all the parameters. It is also possible to control

the motor directly from the control panel.

Fig. 21 Control panel

6.1 Display

The display is back lit and consists of 2 rows, each with

space for 16 characters. The display is divided into six areas.

The different areas in the display are described below:

Fig. 22 LC display

LCD display

LEDs

Control keys

Toggle key

Function keys

Area A:

Shows the actual menu number (3 or 4 digits).

Area B:

Shows if the menu is in the Toggle loop

(page 35), indicated with

, and/or if the soft-

starter is set for “Local” operation (page 36),

indicated with

.

Area C:

Shows the abbreviated name of the active menu,

e.g. parameter or description of the contents.

Area D:

Shows the status of the softstarter (3 charac-

ters).

The following status indications are possible:

Acc: Motor starting

Dec: Motor stopping

I2t: Active I2t motor protection

Run: Motor runs at full speed

Jog: Motor runs at jog speed

Trp: Tripped

Stp: Motor is stopped

Area E:

Shows active parameter set:

,

, or

;

and if it is a motor parameter: M1, M2, M3, or

M4.

Shows a flashing cursor when a change is being

done to the actual menu parameter.

Also shows “S” to indicate soft trip, and “A” if

max number of autoreset attempts is exceeded.

Area F:

Shows the setting or selection in the active

menu (empty at 1st level and 2nd level menus).

Shows warnings and alarm messages.

221 T

Motor Volt

Stp A M1

400V

Figure21 controls:StartREV,Stop/Reset,StartFWD;ToggleLoc/Rem;Prev,Next,ESC;MinusJogREV,PlusJogFWD,Enter. Figure22 exampleAarea221;BareaT;CareaMotorVolt;DareaStp;EareaA/M1;Farea400V. AreaB showsTtoggle/Llocal, E parameterA/B/C/D and motorM1–M4. Sourceexample400Vnotrating.

Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 38

Manual reference: physical PDF page 38. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.2 LED indicators

The three light emitting diodes below the display indicate

the operation status of the softstarter and motor/machine

(see Fig. 23). Depending on the operating mode the TRIP

and RUN indicators will also flash to alert the user about a

coming event or action. A description of the different LED

signals is given in Table 15 below.

Fig. 23 LED indicators

*) Frequency: 1 Hz=1 flash per second; 2 Hz=2 flashes per second

6.3 Control keys

The control keys are used to give the START, STOP or

RESET commands directly. As default the START and

STOP keys are disabled and the commands are set remotely

(from digital input).

To enable START commands (reverse and forward run)

from the control keys, go to the description in section 7.1.1,

page 39, menu [2151].

The RESET key is activated by default. It will remain active

as long as one of the keyboard alternatives is selected in

menu [216]).

If the “Enable” function is programmed on one of the digital

inputs, this input must be active to allow START/STOP

commands from the control panel.

6.4 Function keys

The function keys operate the menus and are also used for

programming and read-outs of all the menu settings.

RUN

(green)

TRIP

(red)

POWER

Table 15

LED indication

Table 16

Control key commands.

NOTE: It is not possible to simultaneously activate the

Run/Stop commands from the keyboard and remotely

from the terminal strip. Exception is the Jog-function

which can give a start command, see “Jog functions” on

page 40.

Table 17

Function key commands.

Table16 graphic icons correspond inroworderStartREV,Stop/Reset,StartFWD. Table17 iconsEnter,ESC,Prev,Next,MinusJogREV,PlusJogFWD. Table15 slow1Hz cell is sharedTRIPandRUN awaitingautoreset simultaneousflashing; Power hasdash. Literalgraphiccellsremainrawempty withsemanticmap.

Table15 LED indication; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Shared source cells (coordinates refer to this table):

Table17 function key commands; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Table16 control key commands; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Table15 LED indication — PDF page 38

Source row LED symbol ON Normal flashing2Hz Slow flashing1Hz OFF
1 POWER
(green)
Mains supply
power on
---------------- --------------- Power off
2 TRIP
(red)
Softstarter tripped Warning Awaiting autoreset of trip
(simultaneously flashing
RUN and TRIP LEDs)
No trip
3 RUN (green) Running at full speed Start and stop ramp ⟦null: no independent source value⟧ Softstarter not active

Table17 function key commands — PDF page 38

Source row Graphic key symbol Function key Commands
1 ⟦blank source cell⟧ ENTER Step to lower menu level.
Confirm a changed setting.
2 ⟦blank source cell⟧ ESCAPE Step to higher menu level.
Ignore a changed setting (with-
out confirming).
3 ⟦blank source cell⟧ PREVIOUS Step to previous menu within
the same level.
Move cursor one position to the
left.
4 ⟦blank source cell⟧ NEXT Step to next menu within the
same level.
Move cursor one position to the
right.
5 ⟦blank source cell⟧ - (MINUS)
or
JOG REV
Decrease a value.
Change a selection.
Or:
Start reverse jog function.
6 ⟦blank source cell⟧ + (PLUS)
or
JOG FWD
Increase a value.
Change a selection.
Or:
Start forward jog function.

Table16 control key commands — PDF page 38

Source row Graphic key symbol Control key Commands
1 ⟦blank source cell⟧ START REVERSE RUN Start with reversed
(left) rotation.
(Requires reversing
contactor).
2 ⟦blank source cell⟧ STOP/RESET Stop motor.
Reset softstarter (after
a trip).
3 ⟦blank source cell⟧ START FORWARD RUN Start with forward
(right) rotation.

Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 39

Manual reference: physical PDF page 39. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.4.1 +/- key function

To manually change a value or a selection, or to enter a new

value, the “+” and “-” keys are used. For this function to be

active, the keyboard must be unlocked (as it is by default),

menu [218].

Changing parameter selection

To change selection in a menu, press the “+” or “-” keys to

scroll between the available alternatives. The cursor to the

left (area E) is flashing while doing so. To confirm a

selection, press ENTER, and the cursor will stop flashing.

Editing parameter values

Most of the parameters can be changed during operation

without stopping the softstarter.

The parameters that can not be changed during operation

are in this manual marked with a lock symbol:

.

•

To change a parameter value, press the “+” or “-” keys.

The cursor to the left is flashing while the value is

increased or decreased. If you keep the “+” or “-” keys

pressed, the value will increase or decrease continuously.

For bigger changes you can also directly select a digit

with the cursor using the PREV and NEXT keys, and

change this with the “+” or “-” keys.

Press the Toggle key to change the sign of the entered

value (only valid for certain parameters). The sign of the

value will also change when zero is passed.

Press ENTER to confirm the value. The cursor to the

left will stop flashing.

Press ESC to leave the edit mode.

Entering lock code

The lock code in menu [218] is inserted from the right to

the left, the position indicated with a cursor. The digit is set

by scrolling with the +/- keys, and the cursor is moved with

the PREV key to the left, in order to enter the next symbol.

Then the NEXT key can be used to go to the right and

change something if needed. When finished this is

confirmed with ENTER.

This method is also used for new entries in e.g. User Unit, or

Unit Name. Digits or characters are added from right to left

in the same way as described above.

6.4.2 Jog key function

The “+” and “-” keys can be programmed for jogging,

enabling a manual jog start to be done from the control

panel by pressing and holding the key.

To activate the jog key function, see instructions in “Jog

functions” on page 40.

To deactivate the jog key function, unlock the keyboard in

6.5 Toggle and Loc/Rem Key

This key has two functions: toggling between

selected menus, and switching between local

and remote operation control.

If the key is programmed for “Toggle”

(default in menu [2171]), it will only have

the toggle function.

If the key is programmed for “Loc/Rem” in menu [2171], it

can only be used to switch between local and remote control

of the softstarter.

If the key is programmed for “Combined” in menu [2171],

the key can be used for both functions in the following

manner:

Press one second to use the toggle function.

Press and hold the toggle key for more than five seconds

to enable the choice between Local or Remote function,

see section “Loc/Rem function” on page 36.

When editing parameter values, the toggle key can be used

to change the sign of the value.

6.5.1 Toggle function

Using the toggle function makes it possible to easily step

through selected menus in a loop. The toggle loop can

contain a maximum of ten menus. As default the toggle loop

contains the menus needed for Getting Started. You can also

use the toggle loop to create a quick-menu for the

parameters that are most important to your specific

application.

Add a menu to the toggle loop

  1. Go to the menu you want to add to the loop.

  2. Press the Toggle key and keep it pressed while also press-

ing the “+” key.

  1. Check that a “

” is shown to the right of the menu

number (area B).

NOTE: If you try to change a function during operation

that only can be changed when the motor is stopped, the

message “Stop First” is displayed.

NOTE: When the control panel is locked, the only menu

in which it still is possible to use the +/- keys, is [218]

“Lock Code”.

NOTE: Do not keep the Toggle key pressed for more than

five seconds without pressing either the “+”, “-”, or ESC

key, as this may activate the Loc/Rem function of this

key instead. See menu [2171].

Padlock graphic marks parameters that cannot change whilemotoroperates. Toggleloop membership iconT appearsinareaB. Lockcodeediting remainsrighttoleft. Not an assurance of security or override authority.

Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 40

Manual reference: physical PDF page 40. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Delete a menu from the toggle loop

  1. Go to the menu you want to delete using the toggle key.

  2. Press the Toggle key and keep it pressed while pressing

the “-” key.

  1. Check that there is no longer a “

” symbol to the right

of the menu number.

Delete all menus from the toggle loop

  1. Press the Toggle key and keep it pressed while pressing

the ESC key.

  1. Confirm with ENTER.

Default toggle loop

Fig. 24 shows the default toggle loop. This loop contains the

necessary menus that need to be set before starting the

softstarter the first time. Press the Toggle key to enter e.g.

menu [211], then use the NEXT key to go to the submenus

([212] and so forth) and enter the parameters. When you

press the Toggle key again, the next toggle menu is

displayed.

Fig. 24 Default toggle loop

Indication of menus in toggle loop

Menus included in the toggle loop are indicated with a

in area B of the display.

6.5.2 Loc/Rem function

With the Loc/Rem function you can change between local

and remote control of the softstarter from the control panel.

The Loc/Rem function of the key is disabled as default.

Enable the function in menu [2171].

The function Loc/Rem can also be changed via DigIn, see

menu “Digital inputs [520]”.

Change control mode

  1. Press the Loc/Rem key for five seconds, until “Local?” or

“Remote?” is displayed,

  1. then confirm with ENTER,

  2. or cancel with ESC.

When using the LOC/REM key it is important to define

what “LOCAL” and “REMOTE” will mean:

Local mode

The “LOCAL” function is set up in the menu “Local Run

Control” [2173], for which the factory default selection is

“Keyboard”. The actual status of the softstarter will not

change, e.g. Run/Stop conditions will remain exactly the

same. When the softstarter is set to Local operation, the

display will show “

“ in area B of the display (alternating

with “

” if it is also a toggle loop menu).

Remote mode

The “REMOTE” function is defined in menu [2151]

“Run/Stop Control”, where default is “Remote”.

To monitor the actual Local or Remote status of the

softstarter control, a “Loc/Rem” signal is available for the

Relays [550]. When the softstarter is set to “LOCAL”, the

signal on the relay will be active/high. In “REMOTE” the

signal will be inactive/low.

Toggle loop

To submenus

Figure24 defaultloop100→211→221→222→223→224→225→227→740→100. NEXTfrom211to212then…;Tsymbolindicatesloop. LocalmodeLalternatesTifbothapply.

Manual — P036; Control panel operation. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 41

Manual reference: physical PDF page 41. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

6.6 The menu structure

The menu structure consists of 4 levels:

This structure is consequently independent of the number

of menus per level.

For instance, a menu can have two selectable menus (Jog

[350]), or it can have 12 selectable menus (Motor Data

[220]).

Fig. 25 Menu structure

6.6.1 The main menu

This section gives you a short description of the functions in

the main menu. For a more detailed description of the

contents under each main menu, see chapter 8. page 55.

Preferred View

Displayed at power-up, this menu shows two actual process

signals (electrical power and current as default). The menu is

programmable for many other read-outs.

Main Setup

Here you find the main settings to get the softstarter

operable, the motor data settings being the most important.

The menu group also contains protection and

communication settings.

Process

This menu contains settings more relevant to the

application, such as start, stop, and jog mode settings.

Process Protection

To protect the machine and process from damage, a number

of protection settings, such as the load monitor, can be

configured under this menu.

I/Os and Virtual Connections

Settings for inputs and outputs are entered here.

Logical Functions and Timers

A set of freely programmable blocks are available in this

section.

View Operation and Status

In this menu you can view operational data (power, torque,

current, etc.), and get status information about e.g. inputs

and outputs.

View Trip Log

Here you can see the last 9 trips in the trip memory.

System Data

This menu contains information on softstarter model and

software version.

NOTE: If there are more than 9 menus within one level,

the numbering continues with alphabetic characters (A,

B, C, ...).

Main Menu

2nd level

3rd level

4th level

Figure25 navigation main100–900;Enter400→410,Enter410→411,Enter411→4121 asprinted;ESCbacksup. NEXT/PREVcycleeachlevel;shownsubmenus420,430,4x0;412,413,414,41x;4122,412x. Diagramsourcehierarchy retained without repairing menu numbers.

Menu structure levels; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Source row Level Description
1 Main Menu
1st level
The first character in the menu number.
2 2nd level The second character in the menu number.
3 3rd level The third character in the menu number.
4 4th level The fourth character in the menu number.

Manual reference: physical PDF page 42. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 38 | Operation via the control panel | CG Drives & Automation, 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 43

Manual reference: physical PDF page 43. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.

Main features

This chapter contains descriptions of the main features of

the Emotron TSA softstarter.

7.1

Setting Start, Stop and

Run functions

7.1.1 Start and stop control

The start and stop control signals can be given from the

control panel using the control keys, via remote control (i.e.

programmable I/O), or via serial communication. The start

commands from the respective control sources depend on

which motor rotation direction that has been selected for the

motor (see Fig. 26). Follow the procedure in Fig. 27 for

setting of the start and stop signals.

Fig. 26 Rotation direction.

Fig. 27 Run/Stop decision tree

For configuration of programmable I/O, see the description

for the respective input/output. For a list of the different

possibilities, see section 7.4, page 51.

Local and remote control mode

An additional possibility for start and stop control is given

with the LOC/REM function of the toggle key (setting

“LOC/REM” in “Function Key” menu [2171]). It is up to

the user to define the “REMOTE” and “LOCAL” functions

in the menus for “Run/Stop Control” [2151] and “Local

Run Control” [2173]. In that respect the LOC/REM key

becomes a tool not just to alternate between the control

panel and I/O control, but actually to quickly change

between any two start and stop control locations. See

description in section 6.5.2, page 36.

7.1.2 Start and stop methods

The methods for starting and stopping the motor can be

configured in the menus [330] “Start Setting” and [340]

“Stop Setting”. See descriptions in section 8.3.3, page 78.

It is also possible to apply a “Start Limitation” [235] as part

of the actions used for protecting the softstarter. The

functions for doing this are mainly related to time settings,

e.g. limiting the numbers of starts per hour or securing a

minimum time delay between starts. For guidelines

regarding specific applications, refer to “The Application

Functions List” on page 23.

If the load monitor function [410] is activated (page 46), it

could be necessary to apply a load monitor start delay time

[417] in order to avoid faulty alarms during start-up due to

the high start current.

Spinbrake

Spinbrake can be selected as a digital input [520], see section

8.5.2, page 94. Braking is then initiated from an inactive or

active state (when running), by activating input. This means

the softstarter can catch a freewheeling motor and brake it

down to standstill.

FWD (right)

REV (left)

Figure26 FWDright/REVleft. Figure27 selectsrotation219 defaultFWD,run/stop2151 defaultRemote;externalRemote/VirtualI/O/Com branch21AdefaultEdge;keyboardinternal/externalbranchstartkeys2174/2175defaultFWD. BothbranchesFinished. Spinbrake appliesfrominactiveoractive state peradjacenttext.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 44

Manual reference: physical PDF page 44. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.1.3 Jog functions

The jog (slow speed) function can be activated

independently from a start or stop, via the control panel

using the jog keys, via remote I/O control, or via serial

communication.

To select the method to activate the jog function, follow the

procedure described in Fig. 28.

Fig. 28 Jog decision tree

It is necessary that the rotation direction settings for all

parameters involved in the jog function correlate to each

other. See Table 18 below.

1) Default value that can be changed in the respec-

tive menu.

7.1.4 Start/Stop signal priority

A jog command has lower priority than a normal start

command, meaning that if the softstarter is already running,

the jog command is ignored. If the softstarter is in jog mode,

a normal start command will override this and start the

motor to full speed.

An “Enable” command (setting via Digin [520]) has the

highest priority and overrides both a normal start/stop

command and a jog command. If “Enable” is inactive it will

not be possible to execute a normal start or a jog start. The

total priority order is listed in Table 19 below.

7.1.5 Setting motor data

For optimal performance the Emotron TSA softstarter

should be configured according to the motor’s rating plate.

The menus for this are found in section 8.2.3, page 60;

menu group [220]. The motor data is handled as a

parameter set (one of four: M1- M4). Motor M1 is selected

as default and the motor data entered will be valid for motor

M1. If different motors are used, the motor data must be

saved under different motor data sets, selected in menu

[212]. See also “Handling motor data in parameter sets” on

page 42.

7.1.6 Process information

To set up the softstarter for a process value, menu group

[320] is used, under which a process signal and its limits can

be configured.

This can be used to create start and stop commands from

process value levels.

All the actual operational data can be viewed in the menu

group [700] Operation Status. The softstarter is by default

set to present the operational data using SI units. If needed,

this could be changed to US units in menu [21C].

Table 18

Jog settings depending on rotation direction

NOTE: To jog with the control panel jog keys, press and

hold.

Table 19

Signal priority for digital inputs

Figure28 jogdecision:219FWDdefault;351/352jogspeeddefault10%;2152JogControldefaultRemote;externalRemote/Com/VirtualI/O→Finished,keyboardinternal/external→218LockkeyboardCode291→Finished. Sourcegraphcode291 retained as printed.

Table19 digital input signal priority; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Table18 jog settings by rotation direction; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Table19 digital input signal priority — PDF page 44

Source row Priority Digital Input selection
1 1 Enable
2 2 Spinbrake
3 3 Stop
4 4 Run FWD and Run REV
5 5 Jog FWD and Jog REV

Table18 jog settings by rotation direction — PDF page 44

Source row Menu Forward Jog Reverse Jog Forward and reverse jog
1 219 FWD REV FWD+REV
2 351 10% 1) Off 10% 1)
3 352 Off 10% (1) 10% 1)

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 45

Manual reference: physical PDF page 45. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.2

Working with parameter

sets

Parameter sets can be used to set the softstarter up for

different applications such as different motors used and

connected, start and stop methods, alarm settings, control

sources, etc.

With the four parameter sets different control options can

be configured with respect to quickly changing the

behaviour of the softstarter. It is possible to adapt the

softstarter online to altered behaviour. This is based on the

fact that at any desired moment any one of the four

parameter sets can be activated during operation; via the

digital inputs or the control panel.

A parameter set consists of virtually all changeable

parameters in the menu system. Exceptions are some

parameters that can only have one and the same value,

regardless of the selected parameter set:

[211] Language, [217] Key Functionality, [218] Lock Code,

and [260] Serial Communication. These parameter settings

are global, i.e. valid throughout the menu system.

The menus for parameter set handling are found in section

8.2.5, page 66, starting with menu [240].

The active parameter set is shown in the display to the lower

left, and can also be viewed in menu [721] TSA Status. The

detailed configuration for each set can be recorded in the

menu list that can be found in the end of this manual

alternatively be downloaded from the web at

www.cgglobal.com or www.emotron.com.

7.2.1 Control of parameter sets

The parameter sets can be changed via the control panel, via

digital inputs or via serial communication. This is decided in

menu [241] Select Set.

All digital and virtual inputs can be configured to select

parameter sets. Fig. 29 shows the way the parameter sets

could be activated via digital input, where for instance DigIn

3 [523] is set to “Set Ctrl 1” and DigIn 4 [524] is set to “Set

Ctrl 2”.

Fig. 29 Selecting the parameter sets via digital input

When the parameter sets are selected via digital inputs, they

are activated as in Table 20. Activate the parameter changes

via digital input by setting menu [241] to “DigIn”.

Example: Manual and automatic control

In an application manual control is used to prepare for

service position. After service the process is switched to

automaic control mode. This can be solved by using one set

of parameters to activate manual control mode (i.e. control

signals via I/O), and a second set of parameters to activate

running in automatic control mode (i.e. control signals from

PLC via fieldbus) .

NOTE: Actual timer values are common for all sets. When

a set is changed the timer functionality will change

according to the new set, but the timer value will stay

unchanged.

Table 20

Parameter set

NOTE: The selection via the digital inputs is immediately

activated. The new parameter settings will be activated

on-line, also during Run.

NOTE: The default parameter set is parameter set A.

{

Parameter Set A

B

C

D

DI3

DI4

Set Ctrl1

Set Ctrl2

+24 V

Run/Stop

Jog Control

Braking Method

Motor Protection

Load Monitor

Figure29 parameterA/B/C/D carriesRun/Stop,JogControl,BrakingMethod,MotorProtection,LoadMonitor. ExampleDI3SetCtrl1 andDI4SetCtrl2 connectedto+24V selectsTable20;notuniversaldefaultinputassignments.

Table20 parameter set digital input selection; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Table20 parameter set digital input selection — PDF page 45

Source row Parameter set Set Ctrl 1 Set Ctrl 2
1 A 0 0
2 B 1 0
3 C 0 1
4 D 1 1

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 46

Manual reference: physical PDF page 46. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.2.2 Configuration of parameter sets

When the parameter set selection is done in menu [241], the

settings for the particular application or control mode can be

done. Parameter set A is default, which means that all

changes done to the default settings in the menu system are

saved under parameter set A.

To reset a parameter set to the default values, go to menu

[243] Default>Set and choose the extent of the reset.

When working with several parameter sets it saves a lot of

work if menu [242] Copy Set is used for copying sets, e.g.

“A>B”, “C>D”, etc. This will copy the entire contents of a

single parameter set to another parameter set, and you only

need to change the differences in the new set.

7.2.3 Handling motor data in

parameter sets

“Motor Data” (M1-M4) is a kind of parameter set in itself,

see section 7.1.5, page 40. The motor data settings are

gathered under a designated motor and belong to this.

To change the parameter set to one that includes changes in

motor data it is therefore necessary to also change motor in

Select Motor [212]. The following cases may exist:

One motor and one parameter set

This is the most common case. As default, all entered data

will be saved under parameter set A and the motor data

under motor data M1.

One motor and two parameter sets

This case is useful if you want to alternate between for

instance two control sources, or two different starting or

braking requirements.

Once default motor M1 is selected:

  1. Select parameter set A in menu [241].

  2. Enter motor data in menu [220].

  3. Enter the settings for other parameters in set A.

  4. If there are only minor differences between the

parameter sets, you can copy parameter set A to

parameter set B, menu [242].

  1. Enter or change the settings for parameters, other than

motor data, in set B.

Two motors and two parameter sets

This is useful if you have two different motors that are not

intended to run at the same time. One motor must stop

before changing to another motor.

  1. Select motor M1 in menu [212].

  2. Enter motor data and settings for other parameters.

  3. Select parameter set B in menu [241].

  4. Select M2 in menu [212].

  5. Enter motor data and settings for other parameters.

7.2.4 Using the control panel memory

The control panel memory could come in handy when more

than one Emotron TSA unit is used. The copy/load

functions allows for transfer of data between the internal

control board of the softstarter and the control panel,

offering a quick solution for copying parameter sets and

motor data to other softstarter units. The control panel can

also be used for temporary storage or back-up copy of

settings. For description of the menu selections and the

copy/load function, see menus [244] and [245], page 67.

In order to enable transfer of data between Emotron TSA

units, there are two different set-ups.

NOTE: The two softstarters must have the same software

version. Check software version in menu [922].

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 47

Manual reference: physical PDF page 47. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Copy by moving control panel between units

To transfer data from one TSA unit to a second TSA unit via

the standard TSA control panel (see Fig. 30):

  1. Copy the settings from the internal control board of

TSA unit 1 to the control panel, menu [244].

  1. Switch off power for both TSA units, and dismount the

front covers with built in control panel.

  1. Disconnect the control panel cable connections from the

control board sockets.

  1. Connect the control panel cable of front cover 1 to TSA

unit 2, using the socket for the internal control panel.

  1. Switch on TSA unit 2 and load the desired settings from

control panel 1 to the internal control board of TSA unit

2, using menu [245].

Fig. 30 Copy and load parameters between two Emotron TSA units via the control panel.

WARNING!

Switch off all power connections before

opening the front cover.

TSA unit 1

TSA unit 2

Figure30 sourcecopysequence1menu244TSAunit1 internalCP1;2removefront;3moveIntCP1;4attachTSAunit2;5menu245load. Textrequirespoweroffbothbeforeopening; diagramnotadditionalpermission.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 48

Manual reference: physical PDF page 48. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Copy via external control panel

If an external control panel is available (option, page 137)

there is no need to dismount the front covers when copying

and loading data between two or more Emotron TSA units

(see Fig. 31). The external control panel is usually mounted

on the cabinet door.

  1. Using the external control panel, copy the settings from

the softstarter control board to the external control

panel, menu [244].

  1. Detach the external control panel from the cabinet of the

source softstarter and attach it to the cabinet with the

target softstarter.

  1. Using the external control panel, load the settings from

this to the internal control board of the target softstarter,

menu [245].

Fig. 31 Copy and load parameters between two Emotron TSA units using an external control panel (optional).

NOTE: Loading from and copying to the softstarter is

only possible when the softstarter is in stop mode.

NOTE: Another solution for copying settings and data

between different softstarter units is via PC, using the

EmoSoftCom PC tool (option). See section 12.2, page

137.

TSA unit 1

TSA unit 2

Ext CP

Figure31 externalCPcopy step1menu244TSAunit1;2moveExtCPtounit2;3menu245load. Sourceoptionalexternalcontrolpanel, stopmodeonly.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 49

Manual reference: physical PDF page 49. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.3

Applying limitations,

alarms and autoreset

In order to protect the softstarter and the connected devices,

the principal operating variables are continuously monitored

by the system. If one of these variables exceeds the safety

limit an error/warning message is displayed. In order to

avoid any possibly dangerous situations, the softstarter sets

itself into a mode called “Trip” and the cause of the trip is

shown in the display. Trips will always stop the softstarter.

7.3.1 Alarm types and actions

In general, an alarm may only be triggered when the

softstarter is active (e.g. during ramping or full speed

operation or during jogging slow speed at stop). Exceptions

are the external alarm and the communications alarm, which

are always active.

For most alarms, different alarm actions can be chosen.

Common for all alarm actions is that the alarm condition is

shown in the display, via serial communication and at any

relay programmed for the appropriate alarm functionality.

An alarm condition is indicated on the LEDs as appropriate

(see Chapter 6.2, page 34). The alarm actions are:

7.3.2 Alarm settings

To protect the motor, use the alarm settings and operation

limitations in menu [230] “Motor Protection” with

submenus. See section 8.2.4, page 62.

For protection of process, mains, and other external devices,

you find load monitor functions and alarm settings in menu

group [400]. See section 8.3, page 76.

Alarm actions for communication faults are set in menu

[264].

7.3.3 Alarm indications

Depending on which alarm condition that is active, the

following indications are given:

Warning

•

The Trip LED indicator (red triangle) on the control

panel is flashing with 2 Hz (see Table 15, page 34).

One of the status indications is displayed (area D of the

display).

The accompanying warning message is displayed (area

F). See a list of possible warning messages in Table 32,

page 117. The most recent warning message is also

displayed in menu [722] “Warning”.

The Warning relay or output is active (if selected).

Hard Trip

The softstarter is in a tripped condition and the motor

coasts down to a standstill.

The Trip LED indicator (red triangle) is lit.

The “TRP” status indication is displayed (area D of the

The accompanying trip message is displayed.

The Trip relay or output is active (if selected).

Soft Trip

stops according to the set stop method for normal

operation.

The softstarter is making a controlled stop. During the

stopping:

The accompanying trip message is displayed, including

an additional soft trip indicator “S” in area E of the

display.

The Trip LED indicator (red triangle) is flashing with 2

Hz.

After standstill is reached:

Table 21

Alarm actions

Alarm trip warning definitions; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Table21 alarm actions; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Alarm trip warning definitions — PDF page 49

Source row Term Definition
1 “Alarm” Any faulty condition
2 “Trip” Any action on a fault condition which
leads to interruption of operation.
Trips can be divided into hard and soft
trips, see Table 21
3 “Warning” Any action on a fault condition which
does not lead to interruption of
operation

Table21 alarm actions — PDF page 49

Source row Alarm action Effect
1 No action The alarm condition is ignored.
2 Warning A warning message is shown. Operation
continues as usual if no further measures
are taken.
3 Hard Trip Softstarter is tripped. Operation is
interrupted and restart is inhibited:
- if the softstarter is inactive:
Activation will not be allowed
- if the softstarter is in operation:
The motor coasts to a stop.
4 Soft Trip Softstarter is tripped. A stop is executed in
the same way as for normal operation i.e.
using the same stop method. Restart is
inhibited.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 50

Manual reference: physical PDF page 50. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Trip message

The trip message can be viewed in the menu “View Trip

Log” [800], in which the nine most recent trip messages are

stored ([810] to [890]). For every logged trip the date and

time - from real time clock [740] - is displayed, along with

the actual trip message according to the denotations in Table

32, page 117. The cause of the most recent or actual trip is

indicated in menu [810].

To facilitate troubleshooting, data is copied from the

operation and status menu groups [710] - [730] when a trip

occurs. See a list of the stored parameters in Table 33, page

  1. The stored parameters and their values are shown

under menus [8X1] “Operation”, [8X2] “Status”, and [8X3]

“Stored Values”. To view the value, go down to menu level 4,

i.e. 8XXX.

7.3.4

Load monitor function

The load monitor settings in menu [410] can be used to

protect machines and processes against mechanical overload

and underload, such as a conveyor belt or screw conveyor

jamming, a belt failure on a fan, or a pump running dry.

The load is determined by calculating the motor shaft

power, while running.

There are two overload alarms, “Max Alarm” and “Max Pre-

Alarm”, and two underload alarms, “Min Alarm” and “Min

Pre-Alarm”. The load monitor function is not active during

stop ramps, jogging or braking. For the start ramp you can

choose to delay the activation of the load monitor by using

start delay, menu [416].

It is common that the minimum and maximum alarms are

set to give a soft or hard trip, while the pre-alarms are used

to give an indication that an over- or underload situation

may be close by displaying a warning message (e.g. “Mon

MinPreAl”).

If the operation has been interrupted due to a load monitor

alarm, a reset and a new start signal is needed to continue

operation. Autoreset for the load monitor alarms can be

activated under menu [254]. For manual reset see “Manual

reset” on page 50.

Load monitor alarm levels

There are two alternative ways to set the load monitor alarm

levels:

  1. Manual configuration, in which up to four “Alarm

Levels” are set directly (Fig. ).

“Autoset” configuration, for which the alarm levels are

automatically set, based on “Normal Load” + four “Alarm

Margins” (Fig. 33).

Common for both methods is that the resulting alarm levels

are given as a percentage that refers to the nominal motor

power [223] (being 100%). However, the way to set the

levels differs between the two methods:

NOTE: When the trip is reset the trip message will be

removed from the control panel display, but remains in

the trip message log [800].

NOTE: When using the load monitor, check that the

nominal motor power is set properly in menu [223].

Adjacent source context — repeated to preserve continuation:

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 51

Manual reference: physical PDF page 51. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Manually set alarm levels

See Fig. . For the manual load monitor settings, the “Alarm

Levels” [411] - [414] are set directly as a percentage of the

nominal motor power (menu [223]). The actual shaft power

signal value is displayed together with the Alarm Level value

to facilitate setting. See example on the right.

Example:

Fig. 32 Manually set load monitor alarm levels.

4112 MaxAlarmLev

Run

(104%) 116%

Figure32: yP[%] ofPn_mot, xt[s];manualmaxlevel4112,maxprelevel4122,minprelevel4132,minlevel4142. Startdelay416;minpreDelay4133/Action4131,minDelay4143/Action4141,maxpreDelay4123/Action4121,maxDelay4113/Action4111. Legendnormalzone/prealarmzone/minmaxalarmzone, Runcommand,startdelaytimer,alarmaction. Screen4112MaxAlarmLev,RunA,(104%)116%illustrative.

Adjacent source context — repeated to preserve continuation:

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 52

Manual reference: physical PDF page 52. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Autoset function with alarm margins

See Fig. 33. The quickest way to adapt the monitor to

different load situations is to use the “Autoset” function,

which automatically applies four “Alarm Margins” to a

registered “Normal Load” level whilst the motor is running.

The “Alarm Margins” are set as a percentage added to or

subtracted from the “Normal Load”, which is the shaft

power during normal operation conditions. See calculations

in Table 24, page 86. The “Normal Load” is expressed as a

percentage of the nominal motor power (i.e. 100% normal

load equals the motor power set in menu [223]).

The “Alarm Margins” are set under menu [417], and

“Normal Load” is automatically registered when activating

the autoset function in menu [4175] AutoSet Alarm. The

actual “Normal Load” value can then be viewed in menu

[4176].

Every time a new “Autoset Alarm” command is executed, the

actual shaft power value will be updated as the “Normal

Load” value, with the alarm levels following this.

Autoset can also be activated using a remote signal (edge-

triggered) by setting the function of any digital input to

“Autoset”.

Fig. 33 Autoset load monitor alarm margins.

NOTE: A manual change of any of the “Alarm Levels” in

[411] - [414] will override the “Autoset” monitor

settings, and the “Normal Load” will be reset to “Off”.

Figure33: yP[%]ofPn_mot,xt[s];Autoset4175,NormalLoad4176. Maxmargin4171,MaxPremargin4172,MinPremargin4173,Minmargin4174. Startdelay416;minpreDelay4133Action4131;minDelay4143Action4141;maxpreDelay4123Action4121;maxDelay4113Action4111. Legendruncommand/startdelaytimer/alarmaction andthreezonefills. No inferrednumericlimits.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 53

Manual reference: physical PDF page 53. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Load monitor alarm actions

All the alarms and pre-alarms can be independently

configured to affect operation by applying an alarm action,

e.g. a trip or a warning. See section 7.3.1, page 45. The

alarm or pre-alarm status is available on one of the

programmable relays if so configured (see menu [550] for

more information).

The alarm actions for both the autoset alarm margins and

the manually set alarm levels are configured in menu [4111],

[4121], [4131] and [4141].

The corresponding “Alarm Delays”, which will affect the

alarm response time, are set in menu [4113], [4123], [4133]

and [4143].

Load monitor during start-up

To avoid faulty alarms due to initial over- or underload

situations at start, a “Start Delay” time can be applied for the

load monitor. See menu [416], page 86.

Example 1: Configuring alarm levels manually

Assume that the load monitor is intended to be blocked

during the start-up procedure. A start delay of 30 seconds is

therefore selected in menu [416], in order to allow the

process to settle before the load monitoring becomes active.

In this case a pump must be protected from both overload

and underload (e.g. cavitation) conditions, but no pre-

alarms are needed. The alarm action for the pre-alarms

([4121] and [4131]) is therefore set to “No action”.

Furthermore, the alarm actions for Max alarm [4111] and

Min alarm [4141] are set to “Soft Trip”, with the

corresponding alarm delays; 10 seconds in menu [4113]

Max Alarm Delay, and 5 seconds in [4143] Min Alarm

Delay.

Since the normal load condition (shaft power) for the pump

is 50% of the nominal motor power [223], the Max Alarm

Level [4112] is set to 70%. Finally the Min Alarm Level

[4142] is set to 10%, which is reached during e.g. pump

cavitation conditions.

This configuration results in the following sequence of

events (as illustrated in Fig. 34):

A. The load monitor function is activated when the set start

delay time (30 seconds) has expired.

B. A maximum alarm condition is triggered, but since the

load returns to a safe level within the set alarm delay

time (i.e. <10 seconds) no alarm action is performed.

C. A new maximum alarm condition is triggered.

D. When the set alarm delay time (10 seconds) has expired,

the maximum alarm action is executed (in this case a soft

trip).

Fig. 34 Example 1: Manually set load monitor function.

Example 2: Auto-setting alarm margins

To block the load monitor during the start-up, a start delay

of 30 seconds is selected in menu [416].

In this case a motor used in a conveyor application must be

protected. It is only of interest to apply a maximum alarm

and maximum pre-alarm, therefore the alarm actions for the

minimum alarm [4141] and the minimum pre-alarm [4131]

are set to “No action” (default). The Max Pre-Alarm Action

[4122] is set to “Warning” and the Max Alarm Action

[4111] is set to “Hard Trip”. Then the Max Alarm Delay

[4113] is set to 3 seconds, and the Max Pre-Alarm Delay

[4123] to 0 seconds to get an instant warning when the load

is increased. Menu [4171] Max Alarm Margin is set to 10%,

and menu [4172] Max Pre-Alarm Margin is set to 5%, to

indicate that an overload condition is close.

The motor is started and the actual shaft power is viewed to

the left in menu [4175] Autoset Alarm. When the process

has stabilised, this indicates that the normal load conditions

take place at 60% of the nominal motor power [223]. The

autoset of the alarms is done by selecting “Yes”, followed by

pressing “ENTER”. “Autoset OK!” is displayed. The motor

is now fully protected with a maximum alarm set to 70%

(Normal Load + Max Alarm Margin, 60% + 10%) and a

pre-alarm at 65% (Normal Load + Max Pre-Alarm Margin,

60% + 5%). The “Normal Load” value is viewed in menu

[4176], along with the actual shaft power value.

The following events are noted (see Fig. 35):

B. A maximum pre-alarm condition is triggered, and

immediately results in a warning message: ”Mon

MaxPreAl”, as there is no alarm delay in this case.

C. A maximum alarm condition is triggered.

D. When the set maximum alarm delay time (3 seconds)

has passed, the set maximum alarm action, a hard trip, is

executed.

NOTE: The load monitor alarms are disabled during

jogging, braking, and stop ramp.

30 s.

10 s.

Pload

Time

Max

Min

Normal

Figure34 illustrativemanuallevelsMax70%,Normal50%,Min10%,start30s,maximumalarm10s;Aactivationafter30s,Btransientoverload shorterthan10s noaction,Crenewedoverload,Dsofttripafter10s. Originalchartandprosegovern; no newparameter.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 54

Manual reference: physical PDF page 54. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 35 Example 2: Autoset load monitor function.

7.3.5 Reset and autoreset

When the softstarter is tripped due to a failure, a reset

command is required to make it possible to restart the

softstarter. The reset command can come from any of the

selected sources in menu [216] “Reset Control”, or it can be

automatically generated through settings in menu group

[250] “Autoreset”.

For the following explanations it is important to distinguish

between “reset” and “restart”. “Reset” means that the

softstarter no longer is in a tripped condition, as confirmed

by a removal of the alarm message in the display. If the

operation has been interrupted due to a tripped condition,

the softstarter is prepared for a restart.

If an alarm occurs whose alarm action is configured for

“Warning” (see description of alarm actions in Table 21,

page 45), the indication will automatically be removed as

soon as the warning condition disappears, i.e. no reset

command is needed.

If the operation has been interrupted due to a trip, a reset

signal and a new start signal may be needed to restart the

motor. However, some alarms can be automatically reset

when a new start signal is given.

Manual reset

The control source for the reset signal is selected in [216]

“Reset Control”. The RESET key on the control panel is

activated by selecting one of the keyboard alternatives

(enabled as default).

If controlled by digital input [520], or by virtual I/O [560],

this is set by selecting “Reset” signal.

An output signal can be set by a relay [550] to “ManRst

Trip” which is defined as any active trip condition that needs

a manual reset.

Autoreset

For several alarms it is possible to automatically generate a

reset command to overcome the fault condition. Providing

that all other conditions are normal, the softstarter will then

attempt to restart the operation. Only when the failure keeps

on coming back, recurring at a defined number of times and

therefore cannot be solved by the softstarter, will the unit

give an alarm to inform the operator that attention is

required.

The autoreset configuration can be done in menu group

[250] Autoreset, with submenus for Motor Protection

Autoreset [252], Communication Error Autoreset [253],

Process Protection Autoreset [254], Softstarter Protection

Autoreset [255], and Mains Failure Autoreset [256].

To enable the Autoreset function, “Reset” is selected on one

of [520] Digital Inputs. The reset input must be constantly

activated.

To activate the autoreset function via Virtual I/O [560],

“Reset” is selected in the destination menu for the internal

connection.

In the menus for Relays [550] an output signal of the

autoreset trip can be set, “AutoRst Trip”. Relay is activated

when the maximum number of autoresets is reached.

See more about remote reset control in “Reset and Autoreset

operation” on page 52.

To activate the autoreset function, Allowed Autoreset

Attempts are set in [2511]. Once the maximum number of

autoresets is reached, the softstarter will stay in fault

condition, indicating that external assistance is required.

The details of the autoreset counter can be found in

“Autoreset Attempts [251]” on page 69.

Example: Autoreset for thermal overload

A motor is protected by an internal protection for thermal

overload. When the protection is activated, the softstarter

should wait until the motor has cooled down enough before

resuming normal operation. In this case the estimated time

for cooling down is 300 seconds. When the problem has

occurred three times in a short period of time, a call for

external assistance should be required.

To do this:

•

Enable the Autoreset function by making the reset input

continuously high.

Set maximum number of restarts to 3 in menu [2511].

Activate Motor I2t to be automatically reset; set menu

3 s.

30 s.

Pload

Time

Normal

Pre-Max

Max

WARNING!

If the “Run” input signal is active (high) and

level-controlled start mode is selected, the

motor will start at the reset command.

Note that “level control” is not fulfilling the

Machine directive

Figure35 illustrativeAutosetNormal60%,PreMax65%,Max70%;start30s,maximumalarmdelay3s. Amonitoractivation,Bimmediateprewarning,Cmaximumalarmtrigger,Dhardtripafter3s. ThermalexamplecontinuesonPDF55:3restartattempts,300sMotorI2t2521,551AutoRstTrip.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 55

Manual reference: physical PDF page 55. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

[2521]to 300 s.

•

Set relay 1, menu [551] to “AutoRst Trip”; output signal

will be active when the maximum number of restarts is

reached and the softstarter stays in fault condition.

Example: Autoreset for undervoltage

In an application it is known that the main supply voltage

sometimes disappears for a very short time, a so-called “dip”.

That will cause the softstarter to trip an “Undervoltage

alarm”. Using the Autoreset function, this trip will be reset

automatically.

Enable the Autoreset function by making the reset input

continuously high.

Activate the Autoreset function in menu [2511],

Allowed Autoreset Attempts.

The autoreset for the undervoltage alarm is activated in

menu [2564]. The set delay time starts counting when

the fault is gone. If the softstarter is stopped an

undervoltage cannot be detected, and the delay time

starts counting immediately after the alarm action has

been executed.

7.4

Programmable I/O

There are a number of selectable signals for analogue and

digital inputs and outputs, gathered under section 8.5, page

91.

1 analogue input [510]

1 analogue output [530]

4 digital inputs [520], with the possibility for up to 6

extra digital inputs if extended I/O option boards (max

2) are fitted.

No digital outputs are available.

3 relay outputs [550], with the possibility for up to 6

extra relays if extended I/O option boards (max 2) are

fitted.

There are also 8 virtual I/Os [560]

Parameters for serial communication are described in section

8.2.7, page 73, menu group [260].

7.5

Logical functions

To enable logic signals to be programmed for different

controlling or signalling functions (using AND/OR/EXOR

operators), there are a number of functions available:

4 analogue comparators and 4 digital comparators [610]

4 logic functions [620]

4 timers [630]

4 SR flip-flops [640}

2 counters [650]

2 clocks [660]

See how to configure the logical functions in Chapter 8.6,

page 100.

7.6

Remote control functions

Operation of the Run/Stop/Enable/Reset functions

As default, the run/stop commands are programmed for

remote operation via the inputs on the terminal strip on the

control board. Default for the reset control is both remote

and keyboard.

With the parameter “Run/Stop Control” [2151] and “Reset

Control” [216], these functions can also be selected for

keyboard or bus communication control.

7.6.1 Default settings of the Run/

Stop/Reset functions

The default settings are shown in Fig. 36. In this example

the softstarter is started with DigIn 1 (Run FWD) and

stopped with DigIn 2 (Stop). A reset after trip can be given

with DigIn 4. The inputs are default set for edge control.

Fig. 36 Default setting Run/Reset commands

NOTE: The examples in this paragraph do not cover all

possibilities. Only the default settings (factory) and the

most relevant combinations are given.

Reset

Control board

Run FWD

DigIn 1

DigIn 2

DigIn 4

Stop

+24 V

(pulse)

Figure36 defaultedgewiring:RunFWDpulseinput11(DigIn1),Stop12(DigIn2),Reset17(DigIn4);18and20+24V. Figureconnects18tocommonRun/Stop and20Reset. Sourceexampleonly.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 56

Manual reference: physical PDF page 56. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

7.6.2 Enable and Stop functions

Both functions can be used separately or simultaneously.

The choice of which function is to be used depends on the

application and the control mode of the inputs (Level/Edge

[21A]).

Enable

The enable function is used as a start interlock. This means

that if any input is set to “Enable”, this input must be set to

active (high) to allow any run command. When the input is

low, the motor will coast to stop.

Stop

If the input is set low (open), the softstarter will stop

according to the selected stop method in menu [341].

7.6.3 Reset and Autoreset operation

If the softstarter is in stop mode due to a trip condition, the

softstarter can be remotely reset by a pulse (“low” to “high”

transition) on the “Reset” input on DigIn 4.

Depending on the selected control method, a restart takes

place as follows:

Edge controlled “Run” inputs

After the “Reset” command is given a new “Run” command

must be applied to start the softstarter again. The inputs are

set for edge control as default. This means that an input is

activated by a “low” to “high” transition or vice versa.

The “Enable” and “Stop” inputs must be closed

continuously in order to accept any run forward or run

reverse command. The last edge (RunFWD or RunREV) is

valid. If an edge-controlled start is activated it is also

necessary to use an input for the stop command according to

Fig. 36, page 51. Fig. 37 gives an example of a possible

sequence.

Fig. 37 Input and output status for edge control

NOTE: In edge control mode, at least one digital input

must be programmed to “Stop”, because the “RunFWD”

and “RunREV” commands are only able to start the

softstarter.

CAUTION!

If the Enable function is not programmed to

a digital input, it is considered to be active

internally.

!

NOTE: Edge controlled inputs comply with the Machine

Directive (see Chapter 1.5.1, page 6), if the inputs are

directly used for starting and stopping the machine.

INPUTS

Run FWD

Run REV

Forward rotation

Reversed rotation

Standstill

MOTOR OPERATION

Edge control [21A]

Figure37 qualitativeedgecontroltracesEnable,Stop,RunFWD,RunREV andForwardrotation/Reversedrotation/Standstill. No time scale or numericaldelay specified. LastRunedgevalid whileEnable/Stopclosed;lowEnablecoastspertext.

Manual — P036; Main features. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 57

Manual reference: physical PDF page 57. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Level controlled “Run” inputs

If the “Run” inputs remain in their position the softstarter

will start immediately after the “Reset” command is given.

Autoreset is enabled if the “Reset” input is continuously

active. The autoreset functions are programmed in menu

“Autoreset” [240].

Menu “[21A] Start signal” Level/Edge must be set to “Level”

to activate level control. This means that an input is

activated by making the input continuously high. This

method should be applied if a PLC is used to operate the

softstarter, for instance.

The Enable input must be continuously active in order to

accept any run forward or run reverse command. If both

RunFWD and RunREV inputs are active, then the

softstarter stops according to the selected stop method in

menu [341]. Fig. 38 gives an example of a possible sequence.

Fig. 38 Input and output status for level control

NOTE: If the control commands are programmed for

keyboard control or serial communication control,

autoreset is not possible.

CAUTION!

Level-controlled inputs DO NOT comply with

the Machine Directive, if the inputs are

directly used to start and stop the machine.

!

Enable

Stop

Run FWD

Run REV

Forward rotation

Reversed rotation

Standstill

INPUTS

MOTOR OPERATION

Level control [21A]

Figure38 qualitativelevelcontroltracesEnable,Stop,RunFWD,RunREV andthreeoperationstates. BothRunactive causesconfiguredstop;RuninputspersistingthroughReset mayrestart. No numericaltiming inferred.

Manual reference: physical PDF page 58. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 54 | Main features | CG Drives & Automation, 01-5980-01r0 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; Functionality menu overview. Installation/wiring/safety directions are supplier statements, not independently validated advice. — page 59

Manual reference: physical PDF page 59. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.

Functionality

This chapter describes the menus and parameters in the

software. You will find a short description of each function

and information about default values, ranges, etc.

A menu list with default values and the most important

communication settings is found in Appendix 1 at the end of

this manual.

At www.emotron.com or www.cgglobal.com, in the

download area, you can also find a complete communication

information list and a menu list with space for parameter set

notes.

Functionality menu overview; source software1.0X editionR0. Graphical key/earth symbols separately preserved. Nulls/physical blanks remain distinct. Source claims only.

Functionality menu overview — PDF page 59

Source row Function Menu number Description See section
1 Preferred view 100 Menu display settings. 8.1
2 Operation setup 210 Basic settings for language, key functionality, control source. 8.2.1
3 Motor data 220 Setting of electrical data for the used motor. 8.2.3
4 Motor protection 230 Motor and softstarter thermal protections. 8.2.4
5 Parameter set handling 240 Selection and configuration of parameter sets. 8.2.5
6 Autoreset 250 Automatic reset of active alarms and restart of the softstarter. 8.2.6
7 Serial communication 260 Serial communication settings for the data transfer. 8.2.7
8 Process settings 300 Process value settings for analogue signal start/stop functions. 8.3
9 Process protection 400 Protection associated with the process and mains.
Load monitor settings.
8.4
10 I/O settings 500 Input and output settings for control and monitoring. 8.5
11 Analogue input 510 ⟦blank source cell⟧ 8.5.1
12 Digital inputs 520 ⟦blank source cell⟧ 8.5.2
13 Analogue output 530 ⟦blank source cell⟧ 8.5.3
14 Relays 550 ⟦blank source cell⟧ 8.5.4
15 Virtual I/Os 560 ⟦blank source cell⟧ 8.5.5
16 Logic and timers 600 Settings for logical functions and timers. 8.6
17 Operation status 700 Viewing of operation parameter values. 8.7
18 Trip log 800 Viewing of trip messages and trip data. 8.8
19 System data 900 Emotron TSA model, software and hardware version. Service
information.
8.9

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 60

Manual reference: physical PDF page 60. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Description of menu table layout

  1. Parameter cannot be changed during operation.

  2. Parameter only for viewing.

  3. Menu information as displayed on control panel.

For explanation of display text and symbols, see section

6.1, page 33.

  1. Factory setting of parameter (also showed on display).

  2. Available settings for the menu, listed selections.

  3. Communication integer value for the selection.

For use with communication bus interface (only if

selection type parameters).

  1. Description of selection alternative or range (min - max

value).

Example:

Menu [2175] “REV key” has two available selections, “Off”

and “REV”, that indicate if the REV key is activated or not.

The factory (default) setting is “Off”.

To change selection or value via the control panel, the “+”

and “-” keys are used (see section 6.4.1, page 35).

For bus communication, the integer value 0 is used to select

“Off” in the example. Integer 1 represents “REV”.

To change selection by bus communication refer to the

description in Chapter 9. page 123.

Resolution of settings

The resolution for all range settings described in this chapter

is 3 significant digits (unless stated otherwise). Table 22

shows the resolutions for 3 significant digits.

8.1

Preferred View [100]

This menu is displayed at every power-up. During

operation, the menu [100] will automatically be displayed

when the keyboard is not operated for 5 minutes. The

automatic return function will be switched off when the

Toggle and STOP/RESET keys are pressed simultaneously

for 5 seconds. As default the electrical power and current

values are displayed (example in the figure below):

Fig. 39 Default initial display.

Menu [100], “Preferred View” displays the settings made in

menu [110], “1st Line”, and [120], “2nd Line”.

①

Read-only ②

③

Default:

④

⑤

⑥

⑦

Init Torque

Stp

10%

Table 22

Read-only

0kW

0.0A

(1st Line)

(2nd Line)

Menu legend: padlock marks value not changeable during operation; Read-only distinct; display/default/selection/communication integer/range are separate parts. Illustrative332 InitTorque10% and2175REVOff0/REV1 do not set installed configuration. Default displays100 0kW/0.0A illustrative.

Table22 three significant digit resolution; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2175 REV key; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table22 three significant digit resolution — PDF page 60

Source row 3 Digit Resolution
1 0.01-9.99 0.01
2 10.0-99.9 0.1
3 100-999 1
4 1,000-9,990 10
5 10,000-99,900 100

Parameter panel 2175 REV key — PDF page 60

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 REV key deactivated
3 REV 1 REV key activated

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 61

Manual reference: physical PDF page 61. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.1.1

1st Line [110]

This menu sets the content of the upper row in the menu

[100] “Preferred View. If “Process Value” is selected, the

menu shows the value of the selected process source in menu

[321].”

*

“Motor temp” is only visible if you have the option

PTC/PT100 board installed and a PT100 input is

selected in menu [2323].

8.1.2

2nd Line [120]

Sets the content of the lower row in the menu

[100] “Preferred View”. Same selection as in menu [110].

8.2

Main Setup [200]

The “Main Setup” menu contains the most important

settings to get the softstarter operational and set up for the

application. It includes different sub menus concerning the

control of the unit, motor data and protection, utilities and

automatic reset of faults. This menu will instantaneously

adapt to installed options and show the required settings.

8.2.1

Operation setup [210]

Selections concerning the used motor, softstarter mode,

control signals and serial communication are described in

this submenu and is used to set the softstarter up for the

application.

Language [211]

Select the language used in the control panel display. Once

the language is set, this selection will not be affected by the

“Load Default” command.

Select Motor [212]

This menu is used if you have more than one motor in your

application. Select the motor to define. It is possible to define

up to four different motors, M1 to M4, in the softstarter. For

parameter set handling including motor sets M1 - M4, see

section 8.2.5, page 66.

LCD set markersA andM1 are graphical.211 language list includes Cyrillic Russian and Greek names as source glyphs. Display120 shares110 list; MotorTemp11 conditional onPT100 option and2323.

Parameter panel 110 1st Line; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 211 Language; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 120 2nd Line; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 212 Select Motor; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 110 1st Line — PDF page 61

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ El Power
2 Dependent on menu ⟦null: no independent source value⟧ ⟦blank source cell⟧
3 Process Val 0 Process value
4 Torque 2 Torque
5 Shaft Power 4 Shaft power
6 El Power 5 Electrical power
7 Current 6 Current
8 Heatsink Tmp 10 Heatsink temperature
9 Motor Temp * 11 Motor temperature
10 SoftstStatus 12 Softstarter status
11 Run Time 13 Run Time
12 Energy 14 Energy

Parameter panel 211 Language — PDF page 61

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ English
2 English 0 English selected
3 Svenska 1 Swedish selected
4 Nederlands 2 Dutch selected
5 Deutsch 3 German selected
6 Français 4 French selected
7 Español 5 Spanish selected
8 Ρусский 6 Russian selected
9 Italiano 7 Italian selected
10 Česky 8 Czech selected
11 Türkçe 9 Turkish selected

Parameter panel 120 2nd Line — PDF page 61

Source row Label Value
1 Default: Current

Parameter panel 212 Select Motor — PDF page 61

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ M1
2 M1 0 Motor Data is connected to selected
motor.
3 M2 1 ⟦null: no independent source value⟧
4 M3 2 ⟦null: no independent source value⟧
5 M4 3 ⟦null: no independent source value⟧

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 62

Manual reference: physical PDF page 62. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Action Control [215]

This function is used to select the source for run and stop

commands and for jog control. This is described in section

7.1, page 39.

Run/Stop Control [2151]

Jog Control [2152]

In this menu the control source for the jog function is

selected. If the Jog FWD and Jog REV keys are to be used,

one of the keyboard alternatives must be selected in this

menu, and the keyboard must be locked in menu [218].

See section 7.1.3, page 40 for settings regarding the jog

functions.

Reset Control [216]

When the softstarter is in alarm condition, a reset

command is required to make it possible to restart the

softstarter. Use this function to select the source of the reset

signal. The keyboard alternatives in this menu enable both

external and internal control panels to be used. For autoreset

settings, see menu group [250] “Autoreset”. See also section

7.3.5, page 50 about reset and autoreset functions.

Key functionality [217]

Menu group that sets the functions of the keys on the control

panel. See section 6.4, page 34.

Function Key [2171]

The Toggle key on the keyboard (see section 6.5, page 35) has

two functions that can be activated in this menu. As default

the key is set to operate as a toggle key that moves you easily

through the selected menus in the toggle loop.

The “Loc/Rem” function of the key allows you to easily

switch between local and normal operation mode (see

page 36). If set to “Off”, the function is disabled.

The “Loc/Rem” function can also be changed via digital

input. See menu [520].

WARNING!

If the “Run” input signal is active (high) and

level-controlled, the motor will start at the

reset command.

Parameter panel 2151 Run/Stp Ctrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 216 Reset Ctrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2152 Jog Ctrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2171 FunctionKey; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2151 Run/Stp Ctrl — PDF page 62

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Remote
2 Remote 0 Start/stop command via digital input.
3 Int+Ext
keyb
1 Start/stop command via internal or external
control panel.
4 Com 2 Start/stop command via serial
communication.
5 Spare 3 (Reserved for future use)
6 Int keyb 5 Start/stop command via internal control
panel.
7 Ext keyb 6 Start/stop command via external control
panel.

Parameter panel 216 Reset Ctrl — PDF page 62

Source row Selection or label Communication code or merged label Description or default/range
1 Default: Remote+Keyb ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 Remote 0 Reset command via digital input.
3 Keyboard 1 Reset command via internal or external
control panel (RESET key).
4 Com 2 Reset command via serial
communication.
5 Remote+
keyb
3 Reset command via digital input or
control panel (internal or external).
6 Com+keyb 4 Reset command via serial
communication or control panel (internal
or external).
7 Rem+keyb
+com
5 Reset command via digital input, control
panel (internal or external), or serial
communication.

Parameter panel 2152 Jog Ctrl — PDF page 62

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Remote
2 Remote 0 Jog command via digital input.
3 Int+Ext
keyb
1 Jog command via internal or external
control panel.
4 Com 2 Jog command via serial communication.
5 Spare 3 (Reserved for future use)
6 Int keyb 5 Jog command via internal control panel.
7 Ext keyb 6 Jog command via external control panel.

Parameter panel 2171 FunctionKey — PDF page 62

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Toggle
2 Off 0 No function
3 Toggle 1 Toggle function
4 Loc/Rem 2 Local/Remote control mode function
5 Combined 3 Both Toggle function and
Local/Remote control mode function.
See explanation in 6.5.1.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 63

Manual reference: physical PDF page 63. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Local Run Control [2173]

The “Local” mode of the “Loc/Rem” functionality is defined

in this menu (see also page 36). When the softstarter is in

“Local” operation mode, the display shows “

“.

FWD key [2174]

The START/FWD key gives a start with forward (right)

rotation if the function is activated in this menu. The

rotation direction must also be permitted in menu [219]

“Rotation”

REV key [2175]

The REV key gives a start with reverse (left) rotation if

activated in this menu. The function requires a reversing

contactor.

The rotation direction must also be permitted in menu [219]

“Rotation”.

Lock Code [218]

To prevent the keyboard being used or to change the setup of

the softstarter and/or process control, the keyboard can be

locked with a password. This menu, “Lock Code” [218], is

used to lock and unlock the keyboard. Enter the password

“291” to lock/unlock the keyboard operation (see section

6.4.1, page 35). If the keyboard is not locked (default) the

selection “Lock Code?” will appear. If the keyboard is already

locked, the selection “Unlock Code?” will appear.

When the keyboard is locked, parameters can be viewed but

not changed. The control keys (START REV/FWD, and

STOP/RESET) and the jog keys (JOG REV/FWD) can still

be used if their functions are set to be controlled from the

keyboard.

Rotation [219]

Overall limitation of motor rotation direction

This function limits the overall rotation to reverse or forward

direction, or to allow both directions. This limit is prior to all

other selections, e.g. if the rotation is limited to forward

direction, a REV command will be ignored. To define reverse

and forward rotation we assume that the motor is connected

according to section 3.1, page 12.

In this menu you set the allowed rotation for the motor.

NOTE: When reversed rotation is selected (“REV” or

“FWD+REV” in menu [219]), this requires phase reversal

contactors. See Fig. 15, page 19.

2174/2175 key symbols show forward/right and reverse/left; reverse feature requires external reversing contactor. Lock218 default0 range0–9999, source password291. Lock does not disable configured control/jog keys.

Parameter panel 2173 LocRunCtrl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 218 Lock Code?; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2174 FWD key; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 219 Rotation; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2175 REV key; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2173 LocRunCtrl — PDF page 63

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Keyboard
2 Remote 1 Local start/stop command via digital input.
3 Keyboard 2 Local start/stop command via control
panel (internal or external).
4 Com 3 Local start/stop command via serial
communication.

Parameter panel 218 Lock Code? — PDF page 63

Source row Label Value
1 Default: 0
2 Range: 0–9999

Parameter panel 2174 FWD key — PDF page 63

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ FWD
2 Off 0 FWD key deactivated
3 FWD 1 FWD key activated

Parameter panel 219 Rotation — PDF page 63

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ FWD
2 FWD 1 Limited to forward (right) rotation.
REV key, JOG REV key, and reverse
commands are disabled.
3 REV 2 Limited to reverse (left) rotation.
FWD key, JOG FWD key, and forward
commands are disabled.
See note below.
4 FWD+REV 3 Both rotation directions allowed.
See note below.

Parameter panel 2175 REV key — PDF page 63

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 REV key deactivated
3 REV 1 REV key activated

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 64

Manual reference: physical PDF page 64. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.2.2

Remote signal Level/Edge

[21A]

In this menu you select the type of control used for the input

signals for RunFWD, RunREV and RESET that are

operated via the digital inputs on the terminal strip. The

input signals are default set for edge-control, and the input

signals will be activated by the “low to high” or “high to low”

transition of the input. When level-control is selected, the

input signals will be active as long as the input is kept high or

low. See section 7.6, page 51.

Units [21C]

In this menu you select the units which will represent the

different parameter values in the menus, including those read

via serial communication.

SI units

When “SI” is selected, the default units will be:

•

Power [kW]

Torque [Nm]

Temperature [°C]

Nominal motor frequency is preset to 50 Hz, and the

nominal values on motor data are preset according to SI

standards.

US units

The corresponding default values for US-units will be:

Power [hp]

Torque [lb.ft]

Temperature [°F]

Nominal motor frequency will be preset to 60 Hz, and the

default nominal values on motor data (e.g. voltage) are

adapted to US standards.

See also 1.7.2 Definitions, and Table 23, page 61.

8.2.3

Motor Data [220]

In this menu you enter the motor data to adapt the softstarter

to the connected motor. This will increase the control

accuracy as well as different read-outs and analogue output

signals. Some of the default motor data is derived from the

setting in menu [21C].

Motor M1 is selected as default and motor data entered will

be valid for motor M1. If you have more than one motor you

need to select the correct motor in menu [212] before

entering motor data.

NOTE: In edge control mode, at least one digital input

must be programmed to “Stop”, because the “RunFWD”

and “RunREV” commands are only able to start the

softstarter.

CAUTION!

Level controlled inputs DO NOT comply with

the Machine Directive if the inputs are

directly used to start and stop the machine.

NOTE: Edge controlled inputs can comply with the

Machine Directive (see Chapter 1.5.1 page 6) if the

inputs are directly used to start and stop the machine.

!

WARNING!

When the “Units” setting is changed, this will

also affect the factory settings of the motor.

NOTE 1: The parameters for motor data cannot be

changed during operation (marked with a lock

symbol here).

NOTE 2: The default factory settings are for a standard 4-

pole motor according to the nominal current and power

of the softstarter. The softstarter will run even if motor

data is not adapted to the actual motor, but the

performance will not be optimal.

NOTE 3: Parameter sets cannot be changed during

operation if they are set for different motors.

NOTE 4: Motor Data in the different sets M1 to M4 can

be reverted to default setting in menu [243],

Default>Set.

Enter the correct motor data to prevent

dangerous situations and assure correct

control.

Padlock on21C and motor-data heading indicates stopped-only changes. SI/US selector changes nominal default50/60Hz and units, not actual installed motor approval.

Parameter panel 21C Units; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 21A Level/Edge; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 21C Units — PDF page 64

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ SI
2 SI 0 SI-units
3 US 1 US-units

Parameter panel 21A Level/Edge — PDF page 64

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Edge
2 Level 0 The inputs are activated or deactivated
by a continuous high or low signal. Is
commonly used if, for example, a PLC is
used to operate the softstarter.
3 Edge 1 The inputs are activated by a transition;
for Run and Reset from “low” to “high”
and for Stop from "high" to "low".

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 65

Manual reference: physical PDF page 65. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

For more information about handling of motor data and

parameter sets, see section 7.2.3, page 42.

For explanation of the different abbreviations used in this

chapter, see Chapter 1.7.2 page 7

Nominal Motor Voltage [221]

Set the nominal motor voltage, Un_mot.

Nominal Motor Frequency [222]

Set the nominal motor frequency.

Nominal Motor Power [223]

The range for Pn_mot depends on the nominal softstarter

power Pn_soft. It must be set within the range 25 - 400% of

the softstarter power Pn_soft. See nominal data for CG motors

in Table 23.

NOTE: The Motor Volts value will always be stored as a 3

digit value with a resolution of 1 V.

Table 23

Nominal data for CG motors complying to IE2 class

of IEC 60034-30.

Padlocks accompany221,222,223. Table23 column associations: current[A]; SI defaultnominalpower400V[kW]; SI defaultspeed50Hz[rpm]; US defaultpower460V[hp]; US defaultspeed60Hz[rpm]. All23 bodyrows retained.

Parameter panel 223 Motor Power; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 221 Motor Volts; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Table23 CG motor nominal defaults IE2 source claim; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 222 Motor Freq; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 223 Motor Power — PDF page 65

Source row Label Value
1 Default: P
n_soft
2 Range: 25-400% x P , default see Table 23,
n_soft
page 61.
3 Resolution 3 significant digits

Parameter panel 221 Motor Volts — PDF page 65

Source row Label Value
1 Default: 400 V for SI-units
460 V for US-units
2 Range: 100-700 V
3 Resolution 1 V

Table23 CG motor nominal defaults IE2 source claim — PDF page 65

Source row Softstarter
nominal
current
[A]
Default
nominal
power
@ 400 V
SI-units
[kW]
Default
nominal
speed
@ 50 Hz
SI-units
[rpm]
Default
nominal
power
@ 460 V
US-units
[hp]
Default
nominal
speed
@ 60Hz
US-units
[rpm]
1 16 7.5 1,440 10 1,730
2 22 11 1,460 15 1,750
3 30 15 1,460 20 1,750
4 36 18.5 1,465 25 1,760
5 42 22 1,465 30 1,760
6 56 30 1,465 40 1,760
7 70 37 1,480 50 1,780
8 85 45 1,475 60 1,770
9 100 55 1,480 75 1,780
10 140 75 1,480 100 1,780
11 170 90 1,480 125 1,780
12 200 110 1,485 150 1,780
13 240 132 1,485 200 1,780
14 300 160 1,490 250 1,790
15 360 200 1,490 300 1,790
16 450 250 1,490 350 1,790
17 560 315 1,490 450 1,790
18 630 355 1,490 500 1,790
19 710 400 1,490 600 1,790
20 820 450 1,490 700 1,790
21 1,000 560 1,490 800 1,790
22 1,400 800 1,490 1,000 1,790
23 1,800 1,000 1,490 1,500 1,790

Parameter panel 222 Motor Freq — PDF page 65

Source row Label Value
1 Default: 50 Hz for SI-units
60 Hz for US-units
2 Range: 50 Hz - 60 Hz
3 Resolution 1 Hz

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 66

Manual reference: physical PDF page 66. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Nominal Motor Current [224]

Set the nominal motor current. If parallel motors, set the

value as sum of motors current.

In_soft is the nominal softstarter current, value according to

Table 23.

Nominal Motor Speed [225]

Set the nominal (full load) asynchronous motor speed.

Nominal Motor Poles [226]

This menu appears only when the nominal speed of the

motor is ≤500 rpm. Here the actual number of poles can be

entered.

Nominal Motor Cos φ [227]

Set the nominal Motor cosphi (power factor).

Motor Ventilation [228]

Parameter for setting the type of motor ventilation. This

affects the characteristics of the I2t motor protection by

lowering the actual overload current.

When the motor has no cooling fan, select “None”. For a

motor with a shaft mounted fan, select “Self”. When the

motor has an external cooling fan, select “Forced”.

8.2.4

Motor protection [230]

This function protects the motor against overload based on

the standard IEC 60947-4-2. For general information on

different alarm settings, see section 7.3, page 45.

Predictive I2t function

Based on how much the used thermal capacity (I2t) has

increased during the most recent starts, a prediction of the

next start is made. If there is no room for another start, the

start will be delayed until a start attempt results in a successful

start.

Motor I2t Alarm [231]

This function makes it possible to protect the motor from

overload as published in the standard IEC 60947-4-2.

The alarm limit is set according to the levels defined by the

“Motor I2t Class” in menu [2313]. Once exceeded, an alarm

will occur and the action chosen in menu [2311] is

performed. The alarm remains active until the I²t value is

below 95% before allowing a reset or an autoreset (see more

detailed description in menu [2521]).

NOTE: The default settings are for a standard 4-pole

motor according to the nominal power of the softstarter.

WARNING!

If level-control is used (i.e. “Level” selection

in menu [21A]), the motor will automatically

continue to make a new start attempt,

without notice.

Padlocks224–228 mark stopped-only configuration.226 condition is ≤500rpm, not <500.228 Self cell physically Normal I then t overload curve; missing2 retained. Source I²t level-control warning means automatic new start without notice; no independent safety endorsement.

Parameter panel 224 Motor Curr; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 228 Motor Vent; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 225 Motor Speed; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 226 Motor Poles; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 227 Motor Cosφ; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 224 Motor Curr — PDF page 66

Source row Label Value
1 Default: I =I (see Note 2, page 60 and
n_mot n_soft
Table 23 above)
2 Range: 25 - 200% x I [A] depending on
n_soft
Emotron TSA model.

Parameter panel 228 Motor Vent — PDF page 66

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Self
2 None 0 Limited I2t overload curve.
3 Self 1 Normal I
t overload curve.
4 Forced 2 Expanded I2t overload curve.

Parameter panel 225 Motor Speed — PDF page 66

Source row Label Value
1 Default: n (see Note 2, page 60 and Table 23)
n_mot
2 Range: 500 - 3,600 rpm
3 Resolution 1 rpm, 4 sign digits

Parameter panel 226 Motor Poles — PDF page 66

Source row Label Value
1 Default: 4
2 Range: 2-144

Parameter panel 227 Motor Cosφ — PDF page 66

Source row Label Value
1 Default: Cosφ 0.86
n
(see Note 2, page 60)
2 Range: 0.50 - 1.00

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 67

Manual reference: physical PDF page 67. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Motor I2t Alarm Action [2311]

Motor I2t Current [2312]

This menu enables both downrating and uprating (use of

motors with a service factor >1.00) of the thermal motor

protection.

Motor I2t Class [2313]

Classification according to IEC60947-4-2, defining the

starting capacities of the motor in order to avoid thermal

overload.

Used Thermal Capacity [2314)

This menu shows the used thermal capacity of the motor, i.e.

the actual I2t value divided by the maximum I2t value,

expressed in (%).

PT100 Alarm[232]

The PT100 menus are only shown if a PT100 option board

is connected.

PT100 Alarm Action [2321]

Motor Class [2322]

Only visible if the PTC/PT100 option board is installed. Set

the class of motor used. The trip levels for the PT100 sensor

will automatically be set according to the setting in this

menu.

Read-only

2314 Used Th Cap

Stp

M1:

XX%

Motor-I²t2314 read-only.2313 Size1 defaultClass10A, Size2upClass10. PT100232 only withoption; insulationclassF140°C default, FNema145°C separate.

Parameter panel 2311 Mot I2t AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2321 PT100 AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2312 Mot I2tCurr; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2313 Mot I2t Class; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2322 Motor Class; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2311 Mot I2t AA — PDF page 67

Source row Selection or label Communication code or merged label Description or default/range
1 Default: Soft Trip ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 No action 0 I2t motor protection is not active.
3 Hard Trip 1 For a definition, see Table 21, page 45
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 2321 PT100 AA — PDF page 67

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Action
2 No Action 0 For a definition, see Table 21, page 45
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 2312 Mot I2tCurr — PDF page 67

Source row Label Value
1 Default: 100%
2 Range: 0-150% of the nominal motor current
I [224]
n_mot

Parameter panel 2313 Mot I2t Class — PDF page 67

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Size 1: 10 A
Size 2 and up: 10
2 2 0 Class 2
3 3 1 Class 3
4 5 2 Class 5
5 10 A 3 Class 10 A
6 10 4 Class 10
7 20 5 Class 20
8 30 6 Class 30
9 40 7 Class 40

Parameter panel 2322 Motor Class — PDF page 67

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ F 140°C
2 A 100°C 0 ⟦blank source cell⟧
3 E 115°C 1 ⟦blank source cell⟧
4 B 120°C 2 ⟦blank source cell⟧
5 F 140°C 3 ⟦blank source cell⟧
6 F Nema
145°C
4 ⟦blank source cell⟧
7 H 165°C 5 ⟦blank source cell⟧

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 68

Manual reference: physical PDF page 68. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

PT100 Inputs [2323]

Two PT100 option boards (B1 and B2) may be connected,

enabling up to six PT100 inputs. With menu [2323] “PT100

Inputs”, you can select which PT100 inputs that should be

supervised, i.e. which are allowed to generate a trip/warning

when the temperature exceeds the limit set in menu [2322]

“Motor Class”.

PT100 input 1, 2 and 3 are equal to input 1, 2 and 3 on the

first PT100 option board (B1). PT100 input 4, 5 and 6 are

equal to input 1, 2 and 3 on the second PT100 option board

(B2).

Note that the supervised inputs must be selected in a

sequence without gaps, i.e. if you like to have only one input

supervised (selection PT100 1) you must use input 1 on

board one (B1).

If you wish to have four PT100 inputs supervised (selection

PT100 1-4) you must use input 1-3 on option board one

(corresponding to input 1-3) and the first input of board 2

(corresponding to input 4).

All PT100 inputs are displayed in operation menu [71B]

PT100 B1 1, 2, 3 and [71C] PT100 B2 1, 2, 3, regardless of

the menu selection.

PTC Alarm [233]

The PTC alarm menus are always shown as there is an

integrated PTC input on the power board (PB-PTC) as

standard.

PTC Alarm Action [2331]

PTC Inputs [2332]

Two additional PTC option inputs can be handled. The

settings are therefore “PB-PTC” for the on-board PTC, “PB-

PTC&Opt1”, and “PB-PTC&Opt1-2”.

Start Limitation [234]

The start limitation is used to protect the softstarter by

limiting the numbers of starts per hour or securing a

minimum time delay between starts.

A start limitation alarm is reset when the alarm condition is

gone and a new start signal is given.

The actual time left until the next start is allowed is shown in

the status menu [72G] “Time to Next Start”.

Start Limitation Alarm Action [2341]

Start limitation is enabled in this menu by choosing a proper

alarm action, used as thermal protection for the softstarter.

Autoreset is available for all start limitation alarms, menu

[2552].

PT1002323 contiguous channels1…3 or1…6; both71B/71C displays shown regardless monitoringselection.2341 table noSoftTrip code3; source table not expanded.

Parameter panel 2332 PTC Inputs; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2323 PT100Inputs; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2341 StartLim AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2331 PTC AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2332 PTC Inputs — PDF page 68

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ PB-PTC
2 PB-PTC 0 On-board power board PTC used for
protection
3 PB-PTC
&Opt1
1 PB-PTC and PTC input on option B1 used
for protection
4 PB-PTC
&Opt1-2
2 PB-PTC and PTC input on options B1 and
B2 used for protection

Parameter panel 2323 PT100Inputs — PDF page 68

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ PT100 1-3
2 PT100 1 0 Channel 1 used for PT100 protection
3 PT100 1-2 1 Channel 1-2 used for PT100 protection
4 PT100 1-3 2 Channel 1-3 used for PT100 protection
5 PT100 1-4 3 Channel 1-4 used for PT100 protection
6 PT100 1-5 4 Channel 1-5 used for PT100 protection
7 PT100 1-6 5 Channel 1-6 used for PT100 protection

Parameter panel 2341 StartLim AA — PDF page 68

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No action
2 No action 0 For a definition, see Table 21, page 45
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Warning 4 ⟦null: no independent source value⟧

Parameter panel 2331 PTC AA — PDF page 68

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No action
2 No action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 69

Manual reference: physical PDF page 69. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Number of starts per hour [2342]

In this menu the allowed number of starts per hour can be

set. If this number is exceeded, an alarm occurs and the

action chosen in menu [2341] is performed.

The alarm is active until the hour has expired and a new start

is allowed. The first hour is counted directly from the first

start of the motor, whereas the following hour is counted not

directly, but from the moment a new start is done, i.e. no

rolling hour.

Minimum time between starts [2343]

In this menu a minimum time between consecutive starts can

be set. If a new start attempt is made before the minimum

time is expired an alarm will occur and the action chosen in

menu [2341] is performed. The alarm remains active until

the chosen minimum time has expired and a new start is

allowed.

Time to next start [2344]

In this menu the time to the next allowed start is shown.

Counts down from set value in menu [2343].

Phase Loss

Autoreset is available for single phase loss alarm, menu

[2561].

Multiple and internal phase loss

A multiple phase loss always results in a hard trip. If there is

an external phase loss (mains supply), this is not indicated

before an alarm delay of 2 seconds. If the phase loss is internal

(thyristor problem), the trip is activated immediately in order

to prevent faulty actions from damaging the softstarter and

motor.

If the lost phases reappear within 2 seconds an automatic

restart is performed.

Single phase loss

A single phase loss results in an immediate interruption of

operation if it occurs during start, jog or stop. If, for start

and jog, the lost phase should reappear within 2 seconds, an

automatic restart is performed.

For other functions, the alarm action on single phase loss can

be set in menu [235]. This will take place if the phase loss

lasts for more than 2 seconds.

Restart

The automatic restart is usually performed as for normal

operation, and according the set start method, menu [331].

Torque boost [337] is executed if enabled, however the jog

function at start [350] is not executed in this case.

Any automatic restart within 2 seconds is not counted for in

a start limitation protection [234].

For phase loss situations exceeding 2 seconds an automatic

restart can be accomplished by using autoreset [2561].

A phase loss alarm is reset when the alarm condition is gone

and a new start signal is given.

Single Phase Loss Alarm Action [235]

The action on a single phase loss is set in this menu. The

relevant action is performed when any phase is lost for more

than 2 seconds.

NOTE: Single phase loss is only detected for incoming

phases (L1, L2, and L3), and not for phases feeding the

2344 read-only TimeToStart minutes. Singlephase235FWD/REV/L1–3 condition onlyincoming; source restartin2seconds, startlimit exception and torque-boost inclusion retained.

Parameter panel 2342 Starts/h; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2343 MinTBtwStrt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2344 TimTNxtStrt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 235 SnglPhLossAA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2342 Starts/h — PDF page 69

Source row Label Value
1 Default: 10
2 Range: 1 - 99

Parameter panel 2343 MinTBtwStrt — PDF page 69

Source row Label Value
1 Default: Off
2 Range: 1 - 60 min

Parameter panel 2344 TimTNxtStrt — PDF page 69

Source row Label Value
1 Unit minutes
2 Resolution: 1 min

Parameter panel 235 SnglPhLossAA — PDF page 69

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Hard Trip
2 No action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 70

Manual reference: physical PDF page 70. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Current Limit Alarm Action [236]

This alarm is only active if there is a current limit coupled to

the start method (settings in [331] and [335]). An alarm is

activated if the current still is at the current limit when the

start time has expired. This means that the motor has not

reached full speed. If no action is programmed, there will be

a current peak at the end of the start ramp.Autoreset is

available for this function, menu [2525].

8.2.5

Parameter set handling [240]

Parameter sets are used if an application requires different

settings for different modes. See detailed description in

"Working with parameter sets", page 41.

There are four available parameter sets that can be

individually configured and stored in the control panel.

The selected motor (M1 - M4) [212] decides the parameter

settings for the motor data in menu group [220]. See

instructions in Handling motor data in parameter sets, page

42.

Select Set [241]

Here you select the parameter set, directly or from where the

selection is going to be controlled. Every menu included in

the parameter sets is designated A, B, C or D depending on

the active parameter set. This is shown in the lower left area

of the display, i.e. with an

as default. The active set is also

showed in [721] “TSA Status”.

The parameter sets can be changed during operation.

However, if the sets are using different motors (M1 to M4)

the set will be changed only when the motor is stopped.

NOTE: The parameter set cannot be changed

during run if the parameter set includes change

of the motor set (M1-M4).

241 selection A0/B1/C2/D3/DigIn4/Com5/Option6; options conditional. Parameter A–D can be selected separately from motor M1–M4, which mustchange stopped.

Parameter panel 236 CurrLim AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 241 Select Set; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 236 CurrLim AA — PDF page 70

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Hard Trip
2 No action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 241 Select Set — PDF page 70

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦blank source cell⟧ A
2 A 0 Fixed selection of one of the 4 parameter
sets A, B, C or D.
3 B 1 ⟦null: no independent source value⟧
4 C 2 ⟦null: no independent source value⟧
5 D 3 ⟦null: no independent source value⟧
6 DigIn 4 Parameter set is selected via a digital
input. Define which digital input in menu
[520], Digital Inputs.
7 Com 5 Parameter set is selected via serial
communication.
8 Option 6 The parameter set is set via an option.
Only available if the option can control the
selection.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 71

Manual reference: physical PDF page 71. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Copy Set [242]

This function copies the content of a parameter set into

another parameter set, e.g. A>B means that the content of

parameter set A is copied into parameter set B.

Load Default Values Into Set [243]

With this function different levels of factory settings can be

selected for the four parameter sets. When loading the default

settings, all changes made on the Emotron TSA softstarter are

set to factory settings. This function also includes selections

for loading default settings to the four different motor data

sets.

Copy all settings to control panel [244]

All the settings, including the motor data, can be copied

between the control board memory and a control panel,

(external or internal). This can be useful when transferring

settings to a second softstarter unit, for instance.

To put the copy/load function into practice, see different

setups in section 7.2.4, page 42.

If two control panels are connected to the softstarter (using

an optional external control panel), only one at a time can be

used for copying or loading data. While transferring data to

one control panel, the other control panel is temporarily

disabled.

To copy settings from the control board to a control panel,

use the actual control panel and set [244] “Copy to CP” to

“Copy”. This will copy all user parameter settings stored in

the control board, and erase any corresponding settings

previously stored in the control panel. While the data is

NOTE: The actual value of menus for viewing will not be

copied into the other set.

NOTE: Start commands will be ignored during copying or

loading.

NOTE: If the on-board RS-232 port is connected to a PC

or to an external control panel this will be temporarily

locked while copying or loading data to the internal

control panel.

Padlock242 copy;243 defaults panel stopped-only.244 copy operation continuesPDF72, temporarily blocksotherCP/RS232/Start. Printed exceptions211/221–22D/261/923 retained.

Parameter panel 242 Copy Set; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 243 Default>Set; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 242 Copy Set — PDF page 71

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦blank source cell⟧ A>B
2 A>B 0 Copy set A to set B
3 A>C 1 Copy set A to set C
4 A>D 2 Copy set A to set D
5 B>A 3 Copy set B to set A
6 B>C 4 Copy set B to set C
7 B>D 5 Copy set B to set D
8 C>A 6 Copy set C to set A
9 C>B 7 Copy set C to set B
10 C>D 8 Copy set C to set D
11 D>A 9 Copy set D to set A
12 D>B 10 Copy set D to set B
13 D>C 11 Copy set D to set C

Parameter panel 243 Default>Set — PDF page 71

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ A
2 A 0 Only the selected parameter set will revert
to its default settings.
3 B 1 ⟦null: no independent source value⟧
4 C 2 ⟦null: no independent source value⟧
5 D 3 ⟦null: no independent source value⟧
6 ABCD 4 All four parameter sets will revert to the
default settings.
7 Factory 5 All settings, except [211], [221]-[22D],
[261] and [923], will revert to the default
settings.
8 M1 6 Only the selected motor set will revert to its
default settings.
9 M2 7 ⟦null: no independent source value⟧
10 M3 8 ⟦null: no independent source value⟧
11 M4 9 ⟦null: no independent source value⟧
12 M1M2M3
M4
10 All four motor sets will revert to default
settings.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 72

Manual reference: physical PDF page 72. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

transferred, “Copy” is flashing on the control panel from

which the command was activated, while the other control

panel will be temporarily inactive. When finished, “Transfer

OK!” is displayed, and it will be possible to give a new

command from any of the control panels.

Load settings from control panel [245]

This function can load single or multiple parameter sets and

motor data from the actual control panel to the softstarter

control board memory. This is carried out much in the same

way as above. The selected parameter sets from the control

panel are copied to the corresponding parameter sets in the

softstarter control board, i.e. A to A, B to B, M1 to M1, and

so on. The different choices are listed below.

If a second control panel is connected, this will not be

affected when loading from the first control panel.

NOTE: The actual value of menus for viewing will not be

copied into control panel memory set.

NOTE: Loading or copying will not affect the value in

menus for viewing.

Padlock244/245 stopped-only.245 singleA/B/C/D,ABCD,A+Mot…D+Mot,ABCD+Mot,M1…M4,allmotors,All have distinct codes0–16. Read-only values not affected.

Parameter panel 244 Copy to CP; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 245 Load from CP; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 244 Copy to CP — PDF page 72

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Copy
2 No Copy 0 Nothing will be copied
3 Copy 1 Copy all settings

Parameter panel 245 Load from CP — PDF page 72

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Copy
2 No Copy 0 Nothing will be loaded.
3 A 1 Data from parameter set A is loaded.
4 B 2 Data from parameter set B is loaded.
5 C 3 Data from parameter set C is loaded.
6 D 4 Data from parameter set D is loaded.
7 ABCD 5 Data from parameter sets A, B, C and D are
loaded.
8 A+Mot 6 Parameter set A and Motor data are
loaded.
9 B+Mot 7 Parameter set B and Motor data are
loaded.
10 C+Mot 8 Parameter set C and Motor data are
loaded.
11 D+Mot 9 Parameter set D and Motor data are
loaded.
12 ABCD+Mot 10 Parameter sets A, B, C, D and Motor data
are loaded.
13 M1 11 Data from motor 1 is loaded.
14 M2 12 Data from motor 2 is loaded.
15 M3 13 Data from motor 3 is loaded.
16 M4 14 Data from motor 4 is loaded.
17 M1M2M3
M4
15 Data from motor 1, 2, 3 and 4 are loaded.
18 All 16 All data is loaded from the control panel.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 73

Manual reference: physical PDF page 73. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.2.6

Autoreset [250]

With these menus an autoreset can be configured. The

benefit of this feature is that occasional trips that do not affect

the process will be automatically reset.

See also section 7.6.3, page 52.

Autoreset Attempts [251]

Any number set above 0 activates the autoreset. This means

that after a trip, the softstarter will restart the operation

automatically according to the number of attempts selected.

No restart attempts will take place unless all conditions are

normal.

If the counter for “Actual Autoreset Attempts” [2512]

contains more trips than the allowed number of attempts

selected in menu [2511], the autoreset cycle will be

interrupted. No autoreset will then take place.

For every 10 minutes that have passed without any new trip

the autoreset counter is counting down one count.

If the maximum number of trips has been reached, the trip

message time is marked with an “A”:

The example above shows the 3rd trip memory menu [830].

An overvoltage trip took place after running for 345 hours,

45 minutes and 12 seconds, at which time the allowed

number of autoreset attempts was exceeded.

If the autoreset counter has reached the set maximum, the

softstarter must be reset by a normal reset. See example

below:

•

Number of allowed autoreset attempts [2511]= 5.

Within 10 minutes 6 trips occur.

At the 6th trip there is no autoreset, because the

autoreset counter allows only 5 attempts to autoreset a

trip.

To reset the autoreset counter, give a new reset command

(from one of the sources for reset control selected in

menu [216]).

The autoreset counter is now zeroed.

Number of Allowed Autoreset attempts

[2511]

Number of Actual Autoreset attempts

[2512]

In this menu the status of the internal autoreset counter is

shown. If no new trips occur, the autoreset counter is

decreased with one count for every tenth minute.

Motor Protection Autoreset [252]

Menu group for automatic reset of motor protection alarms.

Motor I²t protection autoreset [2521]

The delay counter starts counting when the I²t value is low

enough to allow for a new start. This means that first the

internal thermal motor model will require time for cooling

down to a thermal capacity of 95% (if internal thermal motor

protection is enabled). Then the delay time set in this menu

is added on to this time. When the delay time has elapsed, the

alarm will be reset and a restart attempt will automatically be

made.

WARNING!

If the “Run” input signal is active (high) and

level-controlled start mode is selected, the

motor will start at the reset command.

Note that “level control” is not fulfilling the

Machine directive.

830 OVERVOLT

Trp

A 345:45:12

NOTE: An autoreset is delayed by the remaining ramp

time.

Tripdisplay example830OverVoltA345:45:12 is historicalexample. Autoreset attempts defaultOff, time defaultOff, independent coolingthreshold beforedelay. Warning glyph indicates restart may occur withRunhigh.

Parameter panel 2511 AllowedArst; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2512 ActualArst; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2521 Motor I2t; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2511 AllowedArst — PDF page 73

Source row Label Value
1 Default: Off (no autoreset)
2 Range: 0–10 attempts

Parameter panel 2512 ActualArst — PDF page 73

Source row Label Value
1 Default: 0

Parameter panel 2521 Motor I2t — PDF page 73

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3,600 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 74

Manual reference: physical PDF page 74. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

PT100 autoreset [2522]

The delay counter starts counting when all PT100 inputs are

below the set temperature in menu [2322].

PTC autoreset [2523]

The delay counter starts counting when all PTC values are

below their respective limit. This means that if e.g. only the

internal power board PTC is present, the PB-PTC resistance

has to go down to 2,260 Ohm, which decides the minimum

time before autoreset. The time set in this menu is then

added on to the time for cooling down.

For corresponding resistance limits regarding PTC option

boards, please refer to the PTC/PT100 board 2.0 instruction

manual.

Locked Rotor autoreset [2524]

In this menu the delay time for an autoreset of a locked rotor

alarm is set. As a locked rotor cannot be detected in stopped

state, the delay time starts counting immediately after the

alarm action has been executed. When the delay time has

elapsed, the alarm will be reset and a restart attempt will

automatically be made.

Current Limit autoreset [2525]

In this menu the delay time for an autoreset of a current limit

alarm is set. As a current limit fault condition cannot be

detected in stopped state, the delay time starts counting

immediately after the alarm action has been executed. When

the delay time has elapsed, the alarm will be reset and a restart

attempt will automatically be made.

Communication Error autoreset [253]

The delay counter starts counting as soon as communication

is reestablished.

Process Protection Autoreset [254]

When the load monitor function is used, menu group [410],

the following settings for autoreset can be done.

Load Monitor Max Alarm autoreset

[2541]

The delay counter starts counting immediately.

NOTE: An autoreset is delayed by the remaining ramp

time.

PTC literal2,260Ohm in prose, not rounded2.2kΩ. All sixpanel ranges Off/code0 and1–3600s distinct; delaytrigger is specific to eachalarm.

Parameter panel 2522 PT100; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2525 Curr Lim; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 253 ComErrArst; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2523 PTC; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2524 LockedRotor; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2541 MaxAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2522 PT100 — PDF page 74

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3,600 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 75

Manual reference: physical PDF page 75. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Load Monitor Max Pre-Alarm autoreset

[2542]

The delay counter starts counting immediately.

Load Monitor Min Pre-Alarm autoreset

[2543]

Load Monitor Min Alarm autoreset

[2544]

External Alarm 1 autoreset [2549]

The delay counter starts counting as soon as the relevant

external alarm input is inactive.

External Alarm 2 autoreset [254A]

Softstarter Protection autoreset [255]

For alarms that are present to protect the softstarter, the

following settings for autoreset can be done.

Overtemperature autoreset [2551]

In this menu the delay time for autoreset is set for a softstarter

overheated alarm. The delay time starts counting when the

fault is removed. This means the softstarter has to be cooled

down. When the delay time has elapsed, the alarm will be

reset and a restart attempt will automatically be made.

Start Limitation autoreset [2552]

The delay counter starts counting when the time to next

allowed start, set in menu [2354], has decreased to zero.

Time-to-start reference under2552 is visibly2354, while detailed2344 earlier remains separately retained. No correction to printedmenu supplied.

Parameter panel 254A Ext Alarm 2; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2542 MaxPAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2543 MinPAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2551 Overtemp; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2544 MinAlarm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2552 Start Limit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2549 Ext Alarm 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 254A Ext Alarm 2 — PDF page 75

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3,600 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 76

Manual reference: physical PDF page 76. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Mains failure autoreset [256]

The following menus are intended for autoreset of different

mains fault conditions.

Phase Input loss autoreset [2561]

As a phase input failure cannot be detected in a stopped state,

the delay time counter starts counting immediately after the

alarm action has been executed. When the delay time has

elapsed, the alarm will be reset and a restart attempt will

automatically be made.

Voltage Unbalance autoreset [2562]

In this menu the delay time for an autoreset of a voltage

unbalance alarm [441] is set. The delay time starts counting

when the fault is removed. Usually, the mains voltage will not

be available to the softstarter in a stopped state as the mains

contactor is deactivated. In this case a voltage unbalance

failure cannot be detected in a stopped state and the delay

time starts counting immediately after the alarm action has

been executed. When the delay time has elapsed, the alarm

will be reset and a restart attempt will automatically be made.

Overvoltage autoreset [2563]

In this menu the delay time for an autoreset of an overvoltage

alarm [442] is set. The delay time starts counting when the

fault is removed. Usually, the mains voltage will not be

available to the softstarter in a stopped state as the mains

contactor is deactivated. In this case an overvoltage failure

cannot be detected in stopped state and the delay time starts

counting immediately after the alarm action has been

executed. When the delay time has elapsed, the alarm will be

reset and a restart attempt will automatically be made.

Undervoltage autoreset [2564]

In this menu the delay time for an autoreset of an

undervoltage alarm [443] is set. The delay time starts

counting when the fault is removed. Usually, the mains

voltage will not be available to the softstarter in a stopped

state as the mains contactor is deactivated. In this case an

undervoltage failure cannot be detected in a stopped state

and the delay time starts counting immediately after the

Parameter panel 2561 Phase Input; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2564 Undervolt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2562 Volt unbal; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2563 Overvolt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2561 Phase Input — PDF page 76

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 Off
3 1–3600 1–3600 1–3,600 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 77

Manual reference: physical PDF page 77. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.2.7

Serial Communication [260]

In this menu we configure parameters for the serial

communication options.

The RS485 and USB option (com type setting USB/RS485

in menu [261]) uses the standard Modbus RTU protocol

with a selectable baudrate in menu [2621] and Modbus

address [2622].

In addition to this, there are also a number of fieldbus

options available, e.g. Profibus/DeviceNet/ModbusTCP/

Profinet IO etc. When using a fieldbus option, menu [261]

Com Type must be set to Fieldbus. The detailed fieldbus

configuration is contained in menu [263] Fieldbus and its

Submenus.

The com type RS232, is reserved for future RS232 options

but is also used to perform a soft reset of the Fieldbus

module, which is required after e.g. node address

configuration in many cases (network dependant).

For more information see Chapter 9. page 123 and respective

option manual.

There is also the onboard (CB) RS232, which is always active

with fixed baudrate 9600 and fixed address =1, see Chapter

3.2 page 14.

Communication Type [261]

Valid communication option slot.

*) Future options.

Modbus RTU [262]

Set up the parameters for Modbus/RTU) communication.

Baudrate [2621]

Set the baud rate for the communication.

Address [2622]

Enter the unit address for the softstarter.

Fieldbus [263]

Set up the parameters for fieldbus communication.

NOTE: Toggling the setting from Fieldbus to RS232 in

this menu will perform a soft reset (re-boot) of the

Fieldbus module.

NOTE: This baud rate is valid only for communication via

the RS485 and USB options.

NOTE: This address is valid only for communication via

262 Modbus RTU

Stp

263 Fieldbus

OnboardRS232 fixed9600/address1 is not2621/2622 configuration; optioncommunication tables applyonly RS485/USB. Futureoptionasterisks applyEtherCATandBluetooth.

Parameter panel 2621 Baudrate; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 261 Com Type; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2622 Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2621 Baudrate — PDF page 77

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ 9600
2 2400 0 Selected baudrate
3 4800 1 ⟦null: no independent source value⟧
4 9600 2 ⟦null: no independent source value⟧
5 19200 3 ⟦null: no independent source value⟧
6 38400 4 ⟦null: no independent source value⟧
7 57600 5 ⟦null: no independent source value⟧
8 115200 6 ⟦null: no independent source value⟧

Parameter panel 261 Com Type — PDF page 77

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ RS232
2 RS232 0 RS232 (Fieldbus reset, see note below)
3 Fieldbus 1 Fieldbus option mounted (e.g. Profibus,
DeviceNet, Modbus/TCP or EtherCAT*)
4 USB/
RS485/BT
2 USB, RS485 or Bluetooth* option
mounted

Parameter panel 2622 Address — PDF page 77

Source row Label Value
1 Default: 1
2 Selection: 1–247

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 78

Manual reference: physical PDF page 78. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Address [2631]

Enter or view the unit/node address of the softstarter. Read

& Write access for Profibus and DeviceNet. Read-only for

EtherCAT*.

*) Future option.

Process Data Mode [2632]

Enter the mode of process data (cyclic data). For further

information, see the Fieldbus option manual.

Read/Write [2633]

Select “Read/Write” to control the softstarter over a fieldbus

network. For further information, see the Fieldbus option

manual.

Additional Process Values [2634]

Define the number of additional process values sent in cyclic

messages.

Communication Fault [264]

Main menu for communication fault/warning settings. For

further details please see the Fieldbus option manual.

Communication Fault Alarm Action

[2641]

Selects action if a communication fault is detected.

The following applies:

If RS232/485 is selected, the softstarter will execute the

selected action if there is no communication for the time set

in parameter [2642] “ComFlt Time”.

If Fieldbus is selected, the softstarter will execute the selected

action if:

  1. the internal communication between the control board

and fieldbus option is lost for the time set in menu

[2642] “ComFlt Time”.

  1. a serious network error has occurred.

Communication Fault Time [2642]

Defines the delay time for the trip/warning.

NOTE: Menu [2151] or [2152] must be set to COM to

activate the communication fault function supervision.

Parameter panel 2631 Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 2632 PrData Mode; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2641 ComFlt AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2633 Read/Write; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2642 ComFlt Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2634 AddPrValues; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2631 Address — PDF page 78

Source row Label Value
1 Default: 62
2 Range: Profibus 0–126, DeviceNet 0–63
3 Node address valid for Profibus(RW), DeviceNet (RW) and
EtherCAT* (RO).
⟦null: no independent source value⟧

Parameter panel 2632 PrData Mode — PDF page 78

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦blank source cell⟧ Basic
2 None 0-3 Control/status information is not used.
3 Basic 4-7 4 byte process data control/status
information is used.

Parameter panel 2641 ComFlt AA — PDF page 78

Source row Selection or label Communication code or merged label Description or default/range
1 Default: No action ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
2 No action 0 No communication supervision.
3 Hard Trip 1 For a definition, see Table 21, page 45.
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 2633 Read/Write — PDF page 78

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ RW
2 RW 0 Read & Write
3 Read 1 Read-only
4 Valid for process data. Select “Read” (read-only) for logging
process without writing process data. Select “RW” in normal
cases to control inverter.
⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Parameter panel 2642 ComFlt Time — PDF page 78

Source row Label Value
1 Default: 0.5 s
2 Range: 0.1-15 s

Parameter panel 2634 AddPrValues — PDF page 78

Source row Label Value
1 Default: 0
2 Range: 0-8

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 79

Manual reference: physical PDF page 79. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Ethernet [265]

Settings for Ethernet module (Modbus/TCP, Profinet IO).

For further information, see the Fieldbus option manual.

IP Address [2651]

MAC Address [2652]

Subnet Mask [2653]

Gateway [2654]

DHCP [2655]

Fieldbus Signals [266]

Defines modbus mapping for additional process values. For

further information, see the Fieldbus option manual.

FB Signal 1 - 16 [2661]-[266G]

Used to create a block of parameters which are read/written

via communication. 1 to 8 read + 1 to 8 write parameters

possible. Modbus addresses are entered, the actual numbers

are found in the Fieldbus option manual.

Fieldbus Status [269]

Sub menus showing status of fieldbus parameters. For

detailed information, please see the Fieldbus option manual.

NOTE: The Ethernet module must be re-booted to

activate the below settings, for example by toggling

parameter [261] from fieldbus to RS232 and back. Non-

initialised settings are indicated by a flashing display

text.

Read-only

269 FB Status

Stp

LCD dottedaddress0.0.0.0 examples not acquireddevicevalues.2652 MACdefault uniqueEthernetmodule number; zerosdisplay is illustrative.2661–266G mapping requires externaldefinedModbusaddresses.

Parameter panel 2661 FB Signal 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2651 IP Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2652 MAC Address; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2653 Subnet Mask; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2654 Gateway; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2655 DHCP; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 2661 FB Signal 1 — PDF page 79

Source row Label Value
1 Default: 0
2 Range: 0-65535

Parameter panel 2651 IP Address — PDF page 79

Source row Label Value
1 Default: 0.0.0.0

Parameter panel 2652 MAC Address — PDF page 79

Source row Label Value
1 Default: A unique number for the Ethernet module.

Parameter panel 2655 DHCP — PDF page 79

Source row Label Value
1 Default: Off
2 Selection: On/Off

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 80

Manual reference: physical PDF page 80. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.3

Process [300]

These parameters are mainly adjusted to create a process

signal used for analogue start/stop. The input signal is

rescaled in order to be used for viewing or as a signal for the

analogue comparators. The read-out actual value depends on

the selected process source, [321}.

8.3.1

View Process Value [310]

This menu is only visible if a process source is selected in

menu [321] Process Source (i.e. by default the menu is not

shown).

When selected, the actual value of the active (on-line) process

signal is viewed here.

8.3.2

Process Settings [320]

With these settings, the softstarter process value can be set up

to fit the application. The process value in menus [110],

[120], [310], and [711] all use the process unit selected in

[322] for the application, e.g. rpm, bar, or m3/h.

Process Source [321]

Selection of the signal source for the process value used to

start and stop of the motor. The signal levels are given in

menus [324] and [325]. The process source can be set to act

as a function of the process signal on analogue input, via a

communication bus, or temperature input via a PT100

board.

The selection F(x) indicates that a process unit and scaling is

needed, set in menus [322]-[325]. This makes it possible to

e.g. use pressure sensors to measure flow etc. If F(AnIn) is

used, “Process Val” must be selected in menu [511].

Process Unit [322]

Selection of the unit for the process value. This menu is only

visible if a process source is selected in menu [321] “Process

Source”.

User-defined Unit [323]

This menu is only displayed if “User” is selected in menu

[322]. The function enables the user to define a unit with six

symbols. Use the PREV and NEXT keys to move the cursor

to the required position. Then use the + and - keys to scroll

down the character list. Confirm the character by moving the

cursor to the next position by pressing the NEXT key.

NOTE: If F (Bus) is chosen in menu [321], see

section 9.5 Process value, page 124.

322 displayed units m³/h andft³/h retain cubicmeaning although nativeplain text flattens superscript. Userunit323 has sixsymbols; code table continuesPDF81; no missingrows inferred.

Parameter panel 322 Proc Unit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 310 ProcessValue; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

User unit character codes; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 321 Proc Source; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 322 Proc Unit — PDF page 80

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 No unit selection
3 % 1 Percent
4 °C 2 Degrees Centigrade
5 °F 3 Degrees Fahrenheit
6 bar 4 Pressure in bar
7 Pa 5 Pressure in Pascal
8 Nm 6 Torque
9 Hz 7 Frequency
10 rpm 8 Revolutions per minute
11 m3/h 9 Cubic metres per hour
12 gal/h 10 Gallons per hour
13 ft3/h 11 Cubic feet per hour
14 User 12 User defined unit

Parameter panel 310 ProcessValue — PDF page 80

Source row Label Value
1 Dependent on: Process Source [321] and Process Unit
[322]
2 All modes Min according to menu [324] - max
according to menu [325]

User unit character codes — PDF page 80

Source row Character No. for serial
comm.
Character No. for serial
comm.
1 Space 0 m 58
2 0–9 1–10 n 59
3 A 11 ñ 60
4 B 12 o 61
5 C 13 ó 62
6 D 14 ô 63
7 E 15 p 64
8 F 16 q 65
9 G 17 r 66
10 H 18 s 67
11 I 19 t 68
12 J 20 u 69
13 K 21 ü 70
14 L 22 v 71
15 M 23 w 72
16 N 24 x 73

Parameter panel 321 Proc Source — PDF page 80

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Off
2 Off 0 No process source selected.
3 F(AnIn) 1 Function of analogue input. E.g. via PID
control, [380].
4 PT100 4 Temperature as process value
5 F(Bus) 7 Function of communication value.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 81

Manual reference: physical PDF page 81. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example:

Create a user unit named “kPa”.

  1. When in the menu [323] press

to show the cursor.

  1. Press

to move the cursor to the rightmost position.

  1. Press

until the character “a” is displayed.

  1. Press

.

  1. Then press the

until “P” is displayed and press

  1. Repeat until you have entered “kPa”. Confirm with

When sending a unit name you send one character at a time

starting at the rightmost position.

Process Minimum [324]

This menu is only visible if a process source is selected in

menu [321].

This function sets the process value that corresponds to the

minimum input signal.

Process Maximum [325]

The function sets process value that corresponds to the

maximum input signal.

323 kPa example keysequence:Plus showscursor;Next movesrightmost;Plus to a;Prev;Plus toP;Prev;repeat fork;Enterconfirms. Character103 degree symbol;104literal2,105literal3; code57l finalrightpair blank.324 negative range literalopenparenthesis retained.

User unit character codes continued; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 323 User Unit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 324 Process Min; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 325 Process Max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

User unit character codes continued — PDF page 81

Source row Character No. for serial
comm.
Character No. for serial
comm.
1 O 25 y 74
2 P 26 z 75
3 Q 27 å 76
4 R 28 ä 77
5 S 29 ö 78
6 T 30 ! 79
7 U 31 ¨ 80
8 Ü 32 # 81
9 V 33 $ 82
10 W 34 % 83
11 X 35 & 84
12 Y 36 · 85
13 Z 37 ( 86
14 Å 38 ) 87
15 Ä 39 * 88
16 Ö 40 + 89
17 a 41 , 90
18 á 42 - 91
19 b 43 . 92
20 c 44 / 93
21 d 45 : 94
22 e 46 ; 95
23 é 47 < 96
24 ê 48 = 97
25 ë 49 > 98
26 f 50 ? 99
27 g 51 @ 100
28 h 52 ^ 101
29 i 53 _ 102
30 í 54 ° 103
31 j 55 2 104
32 k 56 3 105
33 l 57 ⟦blank source cell⟧ ⟦blank source cell⟧

Parameter panel 323 User Unit — PDF page 81

Source row Label Value
1 Default: No characters shown

Parameter panel 324 Process Min — PDF page 81

Source row Label Value
1 Default: 0.000
2 Range: 0.000-10000
-10000– +10000 (F(AnIn, F(Bus), PT100)

Parameter panel 325 Process Max — PDF page 81

Source row Label Value
1 Default: 10.00
2 Range: 0.000-10000

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 82

Manual reference: physical PDF page 82. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.3.3

Start setting [330]

Submenu with all the functions for starting.

Start method [331]

The available start methods are:

Linear or Square Torque Control

A properly configured torque-controlled start will lead to a

linear speed increase and low starting current without current

peaks. Fig. 40 shows the torque ramps for linear torque

control and square torque control. The “Initial Torque” value

is set in menu [332] and the value for “End Torque at Start”

is set in menu [333].

Fig. 40 Torque control at start

Voltage Control

Voltage control is selected when a linear voltage ramp is

desired. The thyristor switch on time will be ramped up

linearly, from “Initial Voltage”, menu [334], up to full mains

voltage. See Fig. 41.

Fig. 41 Initial voltage and start time.

Direct on-line, DOL

If this alternative is selected the motor can be accelerated as if

it was connected directly to the mains, resulting in a very fast

ramp.

For this type of operation:

Check whether the motor can accelerate the required load

(DOL start). This function can also be used with shorted

thyristors.

Fig. 42 DOL start.

Initial Torque [332]

Used with start method linear/square torque control.

End Torque at Start [333]

Time

Torque

Start time

End torque

Nominal torque

Initial torque

1 Linear

2 Square

Voltage

Un_mot

6-7 x In_soft

FLC

Figure40 torque vsTime:curve1Linear,curve2Square;332initialtorque,333endtorque,Tnnominal,Starttime. Figure41 voltage vsTime:334initial,Un_mot,336Starttime. Figure42 DOL current6–7×In_soft peak,FLCsettled,Time;illustrative not guaranteed limit.

Parameter panel 331 Start Method; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 332 Init Torque; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 333 EndTorqueSt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 331 Start Method — PDF page 82

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦blank source cell⟧ Lin Torq Ctr
2 Lin Torq Ctr 1 The motor torque is controlled according
to a linear ramp, set in menu [332] and
[333].
3 Sqr Torq Ctr 2 The motor torque is controlled according
to a square ramp, set in menu [332] and
[333].
4 Voltage Ctr 3 The motor voltage is controlled according
to a linear voltage ramp, menu [334].
5 DOL 4 Direct online

Parameter panel 332 Init Torque — PDF page 82

Source row Label Value
1 Default: 10%
2 Range: 0 - 250% of T
n

Parameter panel 333 EndTorqueSt — PDF page 82

Source row Label Value
1 Default: 150%
2 Range: 0 - 250% of T
n

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 83

Manual reference: physical PDF page 83. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Initial Voltage [334]

Used with start method voltage control.

Current Limit [335]

A current limit can be added to all starting methods. This

regulates the current during the start ramp until full voltage

is reached. The start attempt is continued during the set start

time in menu [336]. Should the current still be at the current

limit when the start time has expired, this will be indicated

by a warning message “Current Limit” and an optional alarm

action as set in menu [236]”Current Limit Alarm Action”.

Linear or square torque ramp with current

limit

The motor torque is controlled according to either a linear or

a square ramp as selected in menu [331].

The current limit regulator is activated when the current is

reaching the chosen value in [335], and switched off when

full output voltage is reached, or the start time has expired

[336].

Should the current fall to a value below the set current limit,

the current controller will be deactivated, and the torque

ramp reactivated. The original slope remains for the

continued torque ramp, therefore the resulting total starting

time will in this case be longer than the set start time.

Voltage ramp with current limit

The voltage period is increased linearly during the set start

time, from a value corresponding to the minimum allowed

voltage period plus the value set as start voltage, to full mains

voltage.

reaching the chosen value in [335], to be switched off when

the current controller will be deactivated, and the voltage

ramp reactivated.

When the current controller is deactivated (below current

limit), the voltage ramp slope will increase above the original

slope to accomplish a start within the set start time. See Fig.

43.

Fig. 43 Voltage ramp with current limit period.

DOL with current limit

This could also be called “pure current limit start”.

The switch-on period is increased linearly during the set start

switch-on period plus the value set as start voltage, to full

voltage. The ramp time for the voltage ramp is 6 seconds.

approaching the chosen value, to be switched off when full

output voltage is reached, or the start time has expired [336].

Fig. 44 Direct on-line start in combination with current limit

at start.

If the regulator still is in active mode when the start time

expires, a “Current Limit” alarm is issued, and the alarm

action set in menu [236] is executed.

If the softstarter is not tripped for current limit time-out, the

current regulator is deactivated and the switch-on period is

increased to full-on with the slope of the 6 s ramp.

Current

Start time

Limit period

Current limit

FLC

Figure43 U[V] vs t[s],Un_mot,currentlimitperiod,Starttime; dashedand solid ramps qualitative. Figure44 I[A] vs t[s],currentlimit plateau,FLC,Starttime. DOL current-limit case6secondramp source text; graph not extra numeric evidence.

Parameter panel 334 Init Volt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 335 Curr Limit; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 334 Init Volt — PDF page 83

Source row Label Value
1 Default: 30%
2 Range: 0 - 90% of U [221]
n_mot

Parameter panel 335 Curr Limit — PDF page 83

Source row Label Value
1 Default: Off
2 Range: Off, 150 - 500% of I [224]
n_mot

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 84

Manual reference: physical PDF page 84. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Start Time [336]

The start time is defined as the time during which a start

attempt is done.

This menu is directly accessible for all start methods in menu

[331] except “DOL”. However, if combined with a current

limit in menu [335], the start time function is also available

for “DOL”.

Torque Boost [337]

In specific applications torque boost is required for the start.

The torque boost parameter enables a high torque to be

obtained by providing a high current for 0.1-2 seconds at

start. This enables a soft start of the motor even if the break

away torque is high at the start. An example is crushing mills

applications etc.

Fig. 45 Torque boost principle.

Torque boost may be activated before the start ramp. The

current regulator is activated immediately, and the current is

controlled to be at the set “Torque Boost Current Limit”

[3371] for the set “Torque Boost Time” [3372]. See Fig. 45.

The switch-on period remains at the value assigned during

torque boost if the “Start Method” [331] is set to “torque

control” (linear or square), or if a current limit is applied in

menu [335]. In this case the torque or the current regulator

respectively will handle the transition from torque boost to

ramping. If voltage control is selected as start method - with

or without current limit - the switch-on period is set to the

correct initial value for the voltage ramp.

If “torque boost” is used, the total start time is prolonged with

the “Torque Boost Time” [3372].

Torque Boost Current Limit [3371]

Torque Boost Time [3372]

8.3.4

Stop Setting [340]

Stopping is always initiated by triggering of the thyristors to

take over the current when the bypass contact is opened.

When the current is correctly flowing through the thyristors,

the selected stop method is executed.

Stop Method [341]

The available stop methods are:

Linear or Square Torque Control

A torque-controlled stop could be used when a sudden stop

of the motor could harm the application. The motor torque

is controlled according to either a linear or a square ramp,

from the actual torque value to the set “End Torque at Stop”

in menu [342]. See Fig. 46 below.

NOTE: Even though the current limit can be set as low as

150% of the nominal motor current value [224], this

minimum value cannot be used generally. If the current

limit is set too low in relation to the application’s

requirements, the motor will not be able to accelerate

the load.

NOTE: Check that the nominal motor current is set

properly in menu [224] if the current limit functionality is

used.

Torque boost time

Torque boost current limit

FLC

Figure45 I[A] vs t[s],Torque boost current limit,FLC,Torque boost time.3372 boostduration extends totalstart. Stop341 introduction continuesPDF85; Figure46 referenced there not yet read in this packet.

Parameter panel 3371 TB CurrLim; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 336 Start Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 3372 TB Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 3371 TB CurrLim — PDF page 84

Source row Label Value
1 Default: Off
2 Range: Off, 300 - 700% of I [224]
n_mot

Parameter panel 336 Start Time — PDF page 84

Source row Label Value
1 Default: 10 s
2 Range: 1 - 60 s

Parameter panel 3372 TB Time — PDF page 84

Source row Label Value
1 Default: 1.0 s
2 Range: 0.1 - 2.0 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 85

Manual reference: physical PDF page 85. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 46 Torque control at stop

Voltage Control

If a linear voltage-ramp is preferred for the stop, “voltage

control” is selected. First the voltage is reduced to the set

“Step Down Voltage at Stop” [343]. Then a linear ramp will

be followed until the minimum allowed switch-on period is

reached, the duration decided by “Stop Time” [345]. See Fig.

47, page 81.

Coast

The voltage is switched off and the motor is allowed to coast

to a stop.

Brake

Braking may be used in applications where the motor needs

to be stopped quickly. When this selection is made, the

braking method (“Dynamic Vector Brake” or “Reverse

Current Brake”) can be activated in menu [344].

End Torque at Stop [342]

This menu sets the end torque value when one of the torque

control functions is chosen in menu [341].

Step Down Voltage at Stop [343]

This setting is available when “voltage control” is chosen in

[341]. The switch-on period will step down to an

intermediate value, from where it will follow a linear voltage

ramp down to the minimum allowed switch-on period. The

duration of the ramp is set in “Stop Time” [345].

Fig. 47 Step down voltage at stop.

Braking Method [344]

This menu is available when “Brake” is chosen in [341].

Dynamic Vector Brake

With dynamic vector brake, the braking torque applied to

the motor will increase with decreasing speed. Dynamic

vector brake can be used for all loads not rotating too close to

synchronous speed when the motor voltage is switched off.

This is valid for most applications, as the load speed usually

decreases because of frictional losses in gears or belt drives

when the voltage is switched off. However, this method is less

suitable for loads with very high inertia, in which case the

reverse current brake is more efficient.

When the dynamic vector brake is used, no additional

connections or contactors are needed.

The actual speed is detected, and if this is above a certain

limit the dynamic vector brake is executed. For lower speeds

the DC brake is activated.

Time

Torque

Stop time

Nominal torque

End torque

1 Linear

2 Square

Voltage

Un_mot

Figure46 completes84: Torque vsTime,1Linear/2Square, Tn nominaltorque,342Endtorque,Stoptime. Figure47 Voltage vsTime,Un_mot,343stepdown,345Stoptime. Diagramgeometrygoverns; nointermediatevoltage inferred.

Parameter panel 342 EndTorqueStp; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 343 StepDwnVolt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 341 Stop Method; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 342 EndTorqueStp — PDF page 85

Source row Label Value
1 Default: 0%
2 Range: 0 - 100% of T
n

Parameter panel 343 StepDwnVolt — PDF page 85

Source row Label Value
1 Default: 100%
2 Range: 0 - 100% of U [221]
n_mot

Parameter panel 341 Stop Method — PDF page 85

Source row Selection or label Communication code or merged label Description or default/range
1 Default: 4 Coast
2 Lin Torq Ctr 1 The motor torque is controlled according
to a linear ramp.
3 Sqr Torq Ctr 2 The motor torque is controlled according
to a square ramp.
4 Voltage Ctr 3 The motor voltage is controlled according
to a linear voltage ramp.
5 Coast 4 The motor coasts to a stop.
6 Brake 5 Braking method as activated in menu
[344].

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 86

Manual reference: physical PDF page 86. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Reverse Current Brake

This braking method is especially suitable for quickly

stopping heavy loads with high inertia. A very high braking

torque can be applied to the motor even close to synchronous

speed. However, before applying a high braking torque it

should be checked whether the motor, the gear or belt drive,

and the load can withstand the high mechanical forces. To

avoid harmful vibrations, it is generally recommended to

select the lowest braking torque possible that still fulfils the

demands for a short braking time.

The braking is accomplished by phase-reversal of the current.

To enable this, two external mains contactors are needed

which are controlled by the relay outputs of the softstarter

The connection is showed in Fig. 14, page 18.

During start and full voltage operation the first contactor

(K1) will be activated. For braking, K1 will be opened and

the second contactor (K2) will be activated to change the

phase sequence. For security reasons it is possible to set a

delay time between these two signals in menu [346].

To activate the braking method, “Reverse Current Brake”

must also be selected in menu [344]. The actual speed is

detected, and the reverse current brake is active until the

speed is below a set limit. For lower speeds the DC brake is

activated.

DC brake (at low speed)

At low speed the DC brake mode is activated until the stop

time in [345] has elapsed. In DC-brake mode only two

phases (L2 and L3) are active.

The DC brake will automatically be deactivated when the

motor has stopped or when the stop time has expired.

Optionally an external rotation sensor can be connected via

digital input [520], using logical functions to end the DC

braking. See section 8.6, page 100.

In addition to the braking methods described here, there is

also a spinbrake. functionality available as a digital input. See

Spinbrake, page 39.

Stop Time [345]

“Stop Time” is defined as the time during which a stop

attempt is done. This function is available for all stop

methods except for “Coast”.

Reverse Current Braking Delay [346]

A delay time for the reverse current brake function can be set

in this menu. When the relay configured for

“RunSignalFWD” has been deactivated, the relay configured

for “RevCurrBrake” will not be activated until after the set

time delay.

Dynamic Vector Brake Strength [347]

The strength of the dynamic vector brake is set in this menu.

The value is expressed as a percentage of the available vector

braking power (dependent on motor characteristics).

DC Braking Strength [348]

The strength of the DC brake is set here, the value expressed

as a percentage of the maximum available DC braking power.

NOTE: If several softstarters are supplied from the same

power line and the braking functionality is used, the

softstarters should be connected with different phase

sequences, i.e. L1-L2-L3 on the first unit, L2-L3-L1 on the

next and so on.

NOTE: The stop time given in menu [345] is NOT the time

during which a full stop is completed. It is a time-out

function for a stop attempt.

344defaultDynVectBrk0,RevCurrBrk1. Source distinguishesDynamicvector,noexternalcontactors,fromreversecurrentrequiringK1/K2anddelay346. DCmodeusesL2/L3. StopTime345timeoutnotguaranteedfullstop.

Parameter panel 345 Stop Time; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 346 RevC Brk Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 344 Brake Method; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 347 Brk Strength; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 348 DCB Strength; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 345 Stop Time — PDF page 86

Source row Label Value
1 Default: 10 s
2 Range: 0 – 120s

Parameter panel 346 RevC Brk Dly — PDF page 86

Source row Label Value
1 Default: 0.5 s
2 Range: 0 – 120s

Parameter panel 344 Brake Method — PDF page 86

Source row Selection or label Communication code or merged label Description or default/range
1 Default: 0 DynVectBrk
2 DynVectBrk 0 Dynamic Vector Brake
3 RevCurrBrk 1 Reverse Current Brake

Parameter panel 347 Brk Strength — PDF page 86

Source row Label Value
1 Default: 75 %
2 Range: 0 – 100%

Parameter panel 348 DCB Strength — PDF page 86

Source row Label Value
1 Default: 15 %
2 Range: 0 – 100%

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 87

Manual reference: physical PDF page 87. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Switch to DC Brake [349]

Here you set the speed at which the braking method should

be switched to DC brake. The speed is expressed as a

percentage of the nominal motor speed.

8.3.5

Jog [350]

For setting of the jog function, see section 7.1.3, page 40.

The jog function can be activated by a start via the keyboard,

digital input (“Remote”) or communication option, menu

[2152] “Jog Control”, page 58.

For the “Remote” activation of the jog command, the digital

input must be set to “Jog FWD” and/or “Jog REV” in menu

[520].

For information about the jog keys on the control panel, see

section 6.4.2, page 35.

The Jog function will automatically generate a run command

as long as the Jog function is active. This is independent of

the settings in menu [2151] “Run/Stop Control”.

Fig. 48 Jog command

Jog Speed Forward [351]

Jog Speed Reverse [352]

NOTE: For the jog function to be available, the rotation

direction must be allowed in [219].

Jog speed

Jog command

t [s]

n [rpm]

Figure48 n[rpm] vs t[s],Jogspeeddashedline;lowerJogcommandpulses. Curvesillustratejogtimecorrespondencewithoutnumericalaccelerationtime. Allowed219andJogcontrol2152apply.

Parameter panel 349 SwitchToDCB; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 351 JogSpd FWD; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 352 JogSpd REV; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 349 SwitchToDCB — PDF page 87

Source row Label Value
1 Default: 30 %
2 Range: 0 – 100% of nominal motor speed [225]

Parameter panel 351 JogSpd FWD — PDF page 87

Source row Label Value
1 Default: 10%
2 Range: Off, 1- 30% of nominal motor speed [225]

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 88

Manual reference: physical PDF page 88. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.4

Load Monitor and Process

Protection [400]

8.4.1

Load Monitor [410]

The functions in this menu enable the softstarter to be used

as a load monitor. See explanation in section 7.3.4, page 46.

The alarm actions for alarms and pre-alarms can be chosen

independently of each other in menus [4111], [4121],

[4131], and [4141]. The corresponding alarm delays are set

in menus [4113], [4123], [4133], and [4143].

•

Manual settings of the “Alarm Levels” are done in menus

[4112], [4122], [4132], and [4142].

Settings of the Autoset “Alarm Margins” are done in

menus [4171]- [4174], and the “Autoset Alarm” is

activated in menu [4175] when running at what is

considered to be the “Normal Load”.

All alarm levels are calculated and expressed as a percentage

that refers to the nominal motor power (menu [223]), i.e.

100% equals the nominal motor power.

It is possible to choose whether the load monitor shall be

active or not during start, using the start delay function in

menu [416].

See detailed explanation of the load monitor function

(including examples) in section 7.3.4, page 46. For more

information regarding alarms, trips and warning. See section

8.2.4, page 62.

Maximum Alarm [411]

These menus contain the settings for the load monitor

maximum alarm.

Maximum Alarm Action [4111]

Setting of the wanted alarm behaviour when a “Maximum

Alarm” has been detected.

Maximum Alarm Level [4112]

In this menu the set “Maximum Alarm Level” is shown (on

the right-hand side of the display - area F). At the same time

the actual value of the shaft power (%) is viewed on the left-

hand side of the display (area F), the value within brackets.

Since the actual shaft power is always visible in this menu, it

allows you to easily setup a suitable maximum alarm level.

The value of the maximum alarm level is given as a

percentage of the nominal motor power [223], i.e. a step of

1% is equal to 1% of the nominal motor power. When the

actual shaft power (shown within brackets in the display)

exceeds the set alarm level, the “Maximum Alarm Delay”

timer, menu [4113], will start counting down. When the

delay time has elapsed, an alarm will be generated according

to the selected “Maximum Alarm Action” in menu [4111].

This menu can be set manually to the required alarm level, or

it can be set indirectly, by performing an “Autoset”.

Example:

The “Max Alarm Level” is set to 80%. This means that when

the output shaft power exceeds 80% of the nominal motor

power, the alarm delay timer starts counting down.

Maximum Alarm Delay [4113]

When the load level exceeds the alarm level for a continuous

period longer than the set “Max Alarm Delay” time, the

selected “Maximum Alarm Action” in menu [4111] is

activated.

4112display RunA,(Pshaft%)leftcurrentvalue/116%rightsetting;116%defaultnotactualpowermeasurement.0–200%nominalmotorpower223 range.

Parameter panel 4112 MaxAlarmLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4113 MaxAlarmDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4111 MaxAlarmAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 4112 MaxAlarmLev — PDF page 88

Source row Label Value
1 Default: 116%
2 Range: 0 - 200% of nominal motor power [223]

Parameter panel 4113 MaxAlarmDel — PDF page 88

Source row Label Value
1 Default: 0.5 s
2 Range: 0.1 - 90 s

Parameter panel 4111 MaxAlarmAct — PDF page 88

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Action
2 No Action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 89

Manual reference: physical PDF page 89. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Maximum Pre-Alarm [412]

These menus contain the settings for the load monitor

maximum pre-alarm.

Maximum Pre-Alarm Action [4121]

Setting of the alarm behaviour when a “Maximum Pre-

Alarm” has been detected.

Maximum Pre-Alarm Level [4122]

The value of the maximum pre-alarm level is given as a

percentage of the nominal motor power [223]. When the

actual shaft power (shown within brackets in the display)

exceeds this level, the “Maximum Pre-Alarm Delay” timer,

menu [4123], will start counting down. When the delay time

has elapsed, an alarm will be generated according to the

selected “Maximum Pre-Alarm Action” in menu [4121].

This menu can be set manually to the required alarm level, or

it can be set indirectly, by performing an “Autoset”.

Maximum Pre-Alarm Delay [4123]

When the load level exceeds the alarm level for a continuous

period longer than the set “Max Pre-Alarm Delay” time, the

selected “Maximum Pre-Alarm Action” in menu [4121] is

activated.

Minimum Pre-Alarm [413]

minimum pre-alarm.

Minimum Pre-Alarm Action [4131]

Setting of the alarm behaviour when a “Minimum Pre-

Minimum Pre-Alarm Level [4132]

The value of the minimum pre-alarm level is given as a

actual shaft power (shown within brackets in the display) falls

to a value below this level, the “Minimum Pre-Alarm Delay”

timer, menu [4133], will start counting down. When the

delay time has elapsed, an alarm will be generated according

to the selected “Minimum Pre-Alarm Action” in menu

[4131].

Example:

The “Min Pre-Alarm Level” is set to 40%. This means that

when the shaft power falls to a value below 40% of the

nominal motor power, the alarm delay timer starts counting

down.

Minimum Pre-Alarm Delay [4133]

When the load level falls below the alarm level for a

continuous period longer than the set “Min Pre-Alarm

Delay” time, the selected “Minimum Pre-Alarm Action” in

menu [4131] is activated..

Parameter panel 4121 MaxPreAlAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 4131 MinPreAlAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4122 MaxPreAlLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4132 MinPreAlLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4123 MaxPreAlDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4133 MinPreAlDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4121 MaxPreAlAct — PDF page 89

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Action
2 No Action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 4122 MaxPreAlLev — PDF page 89

Source row Label Value
1 Default: 108%
2 Range: 0 - 200% of nominal motor power [223]

Parameter panel 4132 MinPreAlLev — PDF page 89

Source row Label Value
1 Default: 92%
2 Range: 0 - 200% of nominal motor power [223]

Parameter panel 4123 MaxPreAlDel — PDF page 89

Source row Label Value
1 Default: 0.5 s
2 Range: 0.1–90 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 90

Manual reference: physical PDF page 90. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Minimum Alarm [414]

These menus contain the settings for the load monitor

minimum alarm.

Minimum Alarm Action [4141]

Setting of the alarm behaviour when a “Minimum Alarm”

has been detected.

Minimum Alarm Level [4142]

The value of the minimum alarm level is given as a

percentage of the nominal motor power [223]. When the

actual shaft power (shown within brackets in the display) falls

to a value below this level, the “Minimum Alarm Delay”

timer, menu [4143], will start counting down. When the

delay time has elapsed, an alarm will be generated according

to the selected “Minimum Alarm Action” in menu [4141].

This menu can be set manually to the required alarm level, or

it can be set indirectly, by performing an “Autoset”.

Minimum Alarm Delay [4143]

When the load level falls below the alarm level for a

continuous period longer than the set “Min Alarm Delay”

time, the selected “Minimum Alarm Action” in menu [4141]

is activated.

Start Delay [416]

This setting can be used to e.g. override an alarm during the

start-up procedure. The selected time will delay the

activation of the load monitor alarms after the run command.

Autoset [417]

This is an alternative procedure to set up the alarm levels

automatically which is based on the shaft power level at the

moment of the “Autoset”.

When autoset is performed, the actual value of the shaft

power is stored to menu [4176] Normal Load. The alarm

levels are then recalculated as follows:

After performing autoset, you can view the actual alarm level

settings in menus [4112], [4122], [4132], and [4142].

The alarm actions for all load monitor alarms, both manual

and autoset, are configured in menus [4111], [4121], [4131],

and [4141]; and the corresponding alarm delays are set in

menus [4113], [4123], [4133], and [4143].

Autoset is also available via digital input [520].

NOTE: If you have manually configured the alarm levels

in menus [4112], [4122], [4132], and [4142], you do not

need to do any settings in this menu or its sub-menus.

Table 24

Load monitor alarm levels

NOTE: Changing any alarm margin without performing

Autoset will NOT affect the alarm levels.

NOTE: A manual change of any alarm level will override

the last performed autoset, and menu [4176] Normal

Load will be set to “Off”.

Table24 physicallymergedOverloadspansmax/premax,Underloadspansmin/premin. Values4176±4171–4174add/subtractpercentagepoints; no multiplicativeinterpretation.

Parameter panel 416 Start Delay; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4141 MinAlarmAct; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table24 load monitor alarm calculations; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4142 MinAlarmLev; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4143 MinAlarmDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 416 Start Delay — PDF page 90

Source row Label Value
1 Default: 10 s
2 Range: 1 - 999 s

Parameter panel 4141 MinAlarmAct — PDF page 90

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Action
2 No Action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Table24 load monitor alarm calculations — PDF page 90

Source row ⟦blank source cell⟧ Alarm Level Calculation
1 Overload [4112] MaxAlarmLev [4176] Normal Load +
[4171] MaxAlarmMar
2 ⟦null: no independent source value⟧ [4122] MaxPreAlLev [4176] Normal Load +
[4172] MaxPreAlMar
3 Underload [4132] MinPreAlLev [4176] Normal Load -
[4173] MinPreAlMar
4 ⟦null: no independent source value⟧ [4142] MinAlarmLev [4176] Normal Load -
[4174] MinAlarmMar

Parameter panel 4142 MinAlarmLev — PDF page 90

Source row Label Value
1 Default: 84%
2 Range: 0 - 200% of nominal motor power [223]

Parameter panel 4143 MinAlarmDel — PDF page 90

Source row Label Value
1 Default: 0.5 s
2 Range: 0.1 - 90 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 91

Manual reference: physical PDF page 91. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source limitation for this page: 4172and4174 upperrange limits omitted in source; no value inferred.

Maximum Alarm Margin [4171]

This autoset menu sets the band above the Normal Load

[4176] that does not generate a maximum alarm. The set

“Max Alarm Margin” percentage is added on to the

percentage of the “Normal Load”. The resulting percentage

is where the maximum alarm level is put, related to nominal

motor power [223].

Example:

The “Maximum Alarm Margin” is set to 16%. The actual

shaft power at the moment of performing autoset is 45%.

The new maximum alarm will be set to 61%, which means

that the “Maximum Alarm Delay” timer in menu [4113] will

start counting down when the actual shaft power exceeds

61% (equal to 61% of the nominal motor power [223]).

When the alarm delay time has elapsed, a maximum alarm

could be generated, depending on the setting in menu [4111]

Max Alarm Action.

Maximum Pre-Alarm Margin [4172]

[4176] that does not generate a maximum pre-alarm. The set

Max Pre-Alarm Margin percentage is added on to the

is where the maximum pre-alarm level is put, related to

nominal motor power [223].

Minimum Pre-Alarm Margin [4173]

This autoset menu sets the band below the “Normal Load”

[4176] that does not generate a minimum pre-alarm. The set

Min Pre-Alarm Margin percentage is subtracted from the

is where the minimum pre-alarm level is put, related to

The “Min Pre-Alarm Margin” is set to 10%. In the above

example with a Normal Load of 45%, this will result in a

minimum pre-alarm level at 35% of the nominal motor

power. The “Minimum Pre-Alarm Delay” in menu [4133]

will start as soon as the actual shaft power has dropped to

below 35% of the nominal motor power [223], and the

action set in menu [4131] Min Pre-Alarm Action will be

executed when the delay time has elapsed.

Minimum Alarm Margin [4174]

This autoset menu sets the band below the Normal Load

[4176] that does not generate a minimum alarm. The set

Min Alarm Margin percentage is subtracted from the

is where the minimum alarm level is put, related to nominal

Autoset Alarm [4175]

When autoset is performed, the actual value of the shaft

power will be used as a basis when setting the alarm levels.

Autoset is performed by choosing “Yes” and confirming by

pressing “ENTER”. The message “Autoset OK!” is displayed

(alternatively “Failed!” if the command does not succeed). To

return to the menu display, press any key.

When autoset is performed, the actual shaft power, shown to

the left in the menu display, is stored to menu [4176] Normal

Load, and the alarm levels are recalculated according to the

description for menu [417] Autoset. A new autoset

command will overwrite previously used alarm levels.

Autoset can also be triggered by a remote signal, setting the

function of any digital input to “Autoset”. Note that this

signal is edge-triggered.

NOTE: Changing any margin without performing autoset

will NOT affect the alarm levels.

4172and4174rangevisibly0 - of nominal motor power[223]. Missingupperlimit leftunresolved;16/8%defaultsremainreadable. Example45+16=61,45−10=35isnotnewdefault.

Parameter panel 4173 MinPreAlMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4171 MaxAlarmMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4174 MinAlarmMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4172 MaxPreAlMar; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4173 MinPreAlMar — PDF page 91

Source row Label Value
1 Default: 8%
2 Range: 0 - 100% of nominal motor power [223]

Parameter panel 4171 MaxAlarmMar — PDF page 91

Source row Label Value
1 Default: 16%
2 Range: 0–100% of nominal motor power [223]

Parameter panel 4174 MinAlarmMar — PDF page 91

Source row Label Value
1 Default: 16%
2 Range: 0 - of nominal motor power [223]

Parameter panel 4172 MaxPreAlMar — PDF page 91

Source row Label Value
1 Default: 8%
2 Range: 0 - of nominal motor power [223]

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 92

Manual reference: physical PDF page 92. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

When performing an autoset the motor must be running

with the load that needs to be recorded.

Normal Load [4176]

This menu is read-only. If the menu shows “Off”, the

Autoset settings are deactivated, and the manually set alarm

levels in menu [4112], [4122], [4132], and [4142] are

applied.

If the menu shows a number, this is equal to the load level

(shaft power) at the time of performing the autoset. The

alarm levels have also been calculated based on this level ± the

autoset margins.

Example:

The menu shows 78%. This means that an autoset command

was last performed at a load level of 78% of the nominal

motor power [223], and the corresponding alarm levels have

been setup according to the margins set in menus [4171] -

[4174].

8.4.2

Process protection [420]

External Alarm [421]

The external alarm functionality is used to generate an alarm

depending on the state of an external alarm signal. Each of

the digital inputs can be configured for “Ext. Alarm 1” or

“Ext. Alarm 2”. If any digital input is configured for an

external alarm signal, activating (high) this input will cause

an external alarm to occur if the external alarm is enabled in

the corresponding menu ([4211] or [4212]).

External Alarm 1 Alarm Action [4211]

The following alarm actions are available for external alarm:

External Alarm 2 Alarm Action [4212]

Rotor Locked [422]

This alarm is used to avoid high motor current due to a

mechanically locked rotor. If the operation has been

interrupted due to a locked rotor alarm, the operation must

be reset to restart the motor. An autoreset command can be

set for the locked rotor alarm. See menu [2524].

NOTE: The motor must be running for the Autoset

procedure to succeed. A non-running motor or an

unfinished start delay generates a "Failed!" message.

NOTE: If more than one digital input is configured for the

same external alarm signal, activating (high) any of

these inputs will generate an alarm if this is enabled in

the corresponding menu for the external alarm.

4211/4212LCDNoAction andDefaultHardTrip remainseparate.4175No0/Yes1;4176read-onlyOff or0–200%. Sourcehigh-activeexternalalarmparagraph retaineddespiteoppositeselectionnotes99.

Parameter panel 4175 AutoSet Alrm; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 4211 ExtAlarm1AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4176 Normal Load; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4212 ExtAlarm2AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4175 AutoSet Alrm — PDF page 92

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No
2 No 0 ⟦blank source cell⟧
3 Yes 1 ⟦blank source cell⟧

Parameter panel 4211 ExtAlarm1AA — PDF page 92

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Hard Trip
2 No Action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 4176 Normal Load — PDF page 92

Source row Label Value
1 Default: Off
2 Range: Off (Autoset deactivated)
0 - 200% of nominal motor power [223]

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 93

Manual reference: physical PDF page 93. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Locked Rotor Alarm Action [4221]

Locked Rotor Time [4222]

In this menu the time delay for detection of a locked rotor is

set. If the motor current exceeds its upper limit (menu

[4223]) for longer than the set “Locked Rotor Time”, this

will cause an alarm and the action selected in menu [4221]

will be executed.

Locked Rotor Current [4223]

The current limit is normally 4.8 times the nominal motor

current (menu [224]) but can be changed here.

8.4.3

Mains Protection [430]

The Emotron TSA continuously monitors the mains

voltage. This means the motor can easily be protected from

over- and undervoltage as well as from voltage unbalance

conditions. A phase reversal alarm is also available.

Voltage Unbalance Alarm [431]

Under this menu the settings for a voltage unbalance alarm

are selected.

Voltage Unbalance Alarm Action [4311]

In this menu the alarm action for a voltage unbalance alarm

is selected. The following alarm actions are available:

Voltage Unbalance Level [4312]

This menu is available if the voltage unbalance alarm is

enabled in menu [4311]. Here the maximum allowed voltage

unbalance level is entered, expressed as a percentage of the

nominal motor voltage. As soon as the difference between

any two line voltages exceeds this voltage level for a time

period equal to the delay time set in menu [4313], a voltage

unbalance alarm will occur and the action selected in menu

[4311] will be executed.

Voltage Unbalance Alarm Delay [4313]

In this menu the response delay for the voltage unbalance

alarm, as set in [4311] and [4312], is selected.

Parameter panel 4221 LockRot AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 4311 VoltUnbal AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4222 LockRotTime; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4223 LockRotCurr; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4312 UnbalLevel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4313 VoltUnbDel; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4221 LockRot AA — PDF page 93

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Action
2 No Action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 4222 LockRotTime — PDF page 93

Source row Label Value
1 Default: 5 s
2 Range: 0.1 - 10 s

Parameter panel 4223 LockRotCurr — PDF page 93

Source row Label Value
1 Default: 480% (4.8 x I )
n_mot
2 Range: 100% - 1000% (1.0 x I - 10.0 x I )
n_mot n_mot

Parameter panel 4312 UnbalLevel — PDF page 93

Source row Label Value
1 Default: 10% of the nominal motor voltage [221].
2 Range: 2 - 25% of the nominal motor voltage [221].

Parameter panel 4313 VoltUnbDel — PDF page 93

Source row Label Value
1 Default: 1 s
2 Range: 1 - 90 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 94

Manual reference: physical PDF page 94. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Over-Voltage Alarm [432]

Under this menu the settings for an overvoltage alarm are

selected.

Over-Voltage Alarm Action [4321]

In this menu the alarm action for an overvoltage alarm is

selected. The following alarm actions are available:

Over-Voltage Level [4322]

This menu is available if overvoltage alarm is enabled in

menu [4321]. Here the voltage level for an overvoltage alarm

is entered, expressed as a percentage of the nominal motor

voltage. As soon as any line voltage exceeds this voltage level

for a time period equal to the set delay time in menu [4323],

an overvoltage alarm will occur and the action selected in

menu [4321] will be executed.

Over-Voltage Alarm Delay [4323]

In this menu the response delay for the voltage unbalance

alarm, as set in [4321] and [4322], is selected.

Under-Voltage Alarm [433]

In this menu group the settings for an undervoltage alarm are

Under-Voltage Alarm Action [4331]

In this menu the alarm action for the undervoltage alarm is

Under-Voltage Level [4332]

This menu is available if the undervoltage alarm is enabled in

menu [4331]. Here the voltage level for an undervoltage

alarm is entered, expressed as a percentage of the nominal

motor voltage. As soon as any line voltage falls below this

voltage level for a time period equal to the set delay time in

menu [4333], an undervoltage alarm will occur and the

action selected in menu [4331] will be executed.

Under-Voltage Alarm Delay [4333]

alarm, as set in [4431] and [4432], is selected

4333description literal4431/4432 andvoltageunbalance;4323alsoliteralunbalance. Tabledefaults/rangeskeptunderphysicalover/undervoltageheadings.

Parameter panel 4321 OverVolt AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 4331 UnderVolt AA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4322 OverV Level; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4332 UnderV Level; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4323 OverV Del; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4333 UnderV Del; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4321 OverVolt AA — PDF page 94

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Action
2 No Action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 4322 OverV Level — PDF page 94

Source row Label Value
1 Default: 115% of nominal motor voltage [221].
2 Range: 100 - 150% of nominal motor voltage [221].

Parameter panel 4332 UnderV Level — PDF page 94

Source row Label Value
1 Default: 85% of nominal motor voltage [221].
2 Range: 75 - 100% of nominal motor voltage [221].

Parameter panel 4323 OverV Del — PDF page 94

Source row Label Value
1 Default: 1s
2 Range: 1 - 90 s

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 95

Manual reference: physical PDF page 95. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Phase Reversal Alarm [434]

If this function is activated, an alarm will be issued if the

wrong phase sequence is detected prior to a start.

Phase Reversal Alarm Action [4341]

In this menu the alarm action for a phase reversal alarm is

selected. The softstarter will detect the phase sequence prior

to each start attempt. If the actual phase sequence does not

match the allowed phase sequence set in menu [4342], the

action chosen in this menu will be executed.

To enable the phase reversal alarm, a motor has to be

connected and the mains voltage has to be switched on. The

alarm is only valid at starting attempts.

Allowed Phase Sequence [4342]

In this menu the allowed phase sequence is selected.

8.5

I/O [500]

Main menu with all the settings of the standard inputs and

outputs of the softstarter.

8.5.1

Analogue Input [510]

Submenu with all settings for the analogue inputs.

Analogue Input Function [511]

Sets the function for the Analogue input. Scale and range are

defined by “AnIn Advanced” settings in menu [513].

Analogue Input Setup [512]

The analogue input setup is used to configure the analogue

input in accordance with the signal used that will be

connected to the analogue input. With this selection the

input can be determined as current (4-20 mA) or voltage

(0-10 V) controlled input. Other selections are available for

using a threshold (live zero), or a user defined input range.

Fig. 49 Select voltage or current input with jumper S1.

NOTE: When “AnIn Fc” is set to ”Off”, the connected

signal will still be available for “Comparators” [610].

NOTE: The selection of voltage or current input is done

with S1. When the jumper is in voltage mode only the

voltage menu items are selectable. With the jumper in

current mode only the current menu items are

selectable.

S1

Figure49S1selectsU/I voltage/current. Illustrationterminalnumbers11–20,21–24,31–33,69–70 andPE/N/L remainoriginalgeometry; no topologyinferred. Correct511tableDefaultProcessVal;Off0;ProcessVal3.

Parameter panel 511 AnIn Fc; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 4341 PhaseRevAA; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 4342 AllowedSequ; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 511 AnIn Fc — PDF page 95

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Process Val
2 Off 0 Input is not active.
3 Process Val 3 The input value equals an actual process
value and can be used as comparator
input for creating a start signal. It can also
be used to display and view the actual
process value.

Parameter panel 4341 PhaseRevAA — PDF page 95

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No Action
2 No Action 0 For a definition, see Table 21, page 45.
3 Hard Trip 1 ⟦null: no independent source value⟧
4 Soft Trip 3 ⟦null: no independent source value⟧
5 Warning 4 ⟦null: no independent source value⟧

Parameter panel 4342 AllowedSequ — PDF page 95

Source row Label Value
1 Default: L123
2 Selection: L123 and L321

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 96

Manual reference: physical PDF page 96. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 50 Normal full-scale configuration

Fig. 51 2–10 V/4–20 mA (Live Zero)

Analogue Input Advanced [513]

AnIn Min [5131]

Parameter to set the minimum value of the external

reference signal. Only visible if [512] = “User mA/V”.

AnIn Max [5132]

Parameter to set the maximum value of the external

reference signal. Only visible if [512] = “User mA/V.”

Special function: Inverted signal

If the AnIn minimum value is higher than the AnIn

maximum value, the input will act as an inverted input. See

Fig. 52.

NOTE: Always check the needed set up when the setting

of S1 is changed; selection will not adapt automatically.

Reference input signal

NOTE: The different menus will automatically be set to

either “mA” or “V”, based on the selection in “AnIn

Setup” [512].

513 AnIn Advan

Stp

Figure50 fullscale n[rpm]0–100% against0–10V/0–20mA. Figure51livezero n[rpm]0–100% from2V/4mAto10V/20mA. Graphlabelsretainedasprinted,notgeneralconversionclaim. S1change needsselectioncheck.

Parameter panel 512 AnIn Setup; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 5131 AnIn Min; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5132 AnIn Max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 512 AnIn Setup — PDF page 96

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ 4-20 mA
2 Dependent on ⟦null: no independent source value⟧ Setting of jumper S1
3 4–20mA 0 The current input has a fixed threshold
(Live Zero) of 4 mA and controls the full
range for the input signal. See Fig. 51.
4 0–20mA 1 Normal full current scale configuration of
the input that controls the full range for the
input signal. See Fig. 50.
5 User mA 2 The scale of the current controlled input,
that controls the full range for the input
signal. Can be defined by the advanced
AnIn Min and AnIn Max menus.
6 0–10V 4 Normal full voltage scale configuration of
the input that controls the full range for the
input signal. See Fig. 50.
7 2–10V 5 The voltage input has a fixed threshold
(Live Zero) of 2 V and controls the full range
for the input signal. See Fig. 51.
8 User V 6 The scale of the voltage controlled input,
that controls the full range for the input
signal. Can be defined by the advanced
AnIn Min and AnIn Max menus.

Parameter panel 5131 AnIn Min — PDF page 96

Source row Label Value
1 Default: Min (0 V/4.00 mA)
2 Range: 0.00–20.00 mA
0–10.00 V

Parameter panel 5132 AnIn Max — PDF page 96

Source row Label Value
1 Default: Max (10.00 V/20.00 mA)
2 Range: 0.00–20.00 mA
0–10.00 V

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 97

Manual reference: physical PDF page 97. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 52 Inverted input

AnIn Function Min [5134]

With “AnIn Function Min” the physical minimum value is

scaled to selected process unit. The default scaling is

dependent of the selected function of AnIn [511].

AnIn Function Value Min [5135]

With “AnIn Function VaMin” you define a user-defined

value for the signal. Only visible when user-defined is

selected in menu [5134].

AnIn Function Max [5136]

With “AnIn Function Max” the physical maximum value is

AnIn Function Value Max [5137]

With “AnIn Function VaMax” you define a user-defined

selected in menu [5136].

Example:

Process sensor is a sensor with the following specification:

Range:

0–3 bar

Output:

2–10 mA

Analogue input should be set up according to:

[512] AnIn Setup = User mA

[5131] AnIn Min = 2 mA

[5132] AnIn Max = 10 mA

[5134] AnIn Function Min = User-defined

[5135] AnIn VaMin = 0.000 bar

[5136] AnIn Function Max = User-defined

[5137] AnIn VaMax = 3.000 bar

Input signal

Inverted signal:

AnIn Min > AnIn Max

NOTE: With “AnIn Min”, “AnIn Max”, “AnIn Function Min”

and “AnIn Function Max” settings, loss of feedback

signals (e.g. voltage drop due to long sensor wiring) can

be compensated to ensure an accurate process signal.

Figure52 invertedinput: n[rpm]100%atleft0,descendingtoright10V/20mA;AnInMin>AnInMax. Sourcegraphqualitative; noadditionalpointvalues.

Parameter panel 5136 AnIn FcMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 5137 AnIn VaMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5134 AnIn FcMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5135 AnIn VaMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5136 AnIn FcMax — PDF page 97

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Max
2 Min 0 Min value
3 Max 1 Max value
4 User-defined 2 Define user value in menu [5137]

Parameter panel 5137 AnIn VaMax — PDF page 97

Source row Label Value
1 Default: 0.000
2 Range: -10,000.000 – 10,000.000

Parameter panel 5134 AnIn FcMin — PDF page 97

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Min
2 Min 0 Min value
3 Max 1 Max value
4 User-
defined
2 Define user value in menu [5135]

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 98

Manual reference: physical PDF page 98. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

AnIn Filter [5139]

If the input signal is unstable (e.g. fluctuation reference

value), the filter can be used to stabilise the signal. See Fig.

  1. This will result in a 63% change of the input signal

within the set “AnIn Filter time” (T). After 5 times the set

time (i.e. 5xT), AnIn will have reached 100% of the input

change.

Fig. 53

AnIn Enable [513A]

Parameter for enable/disable analogue input selection via

digital inputs (DigIn set to function “AnIn Select”).

8.5.2

Digital Inputs [520]

Submenu with all the settings for the digital inputs.

Digital Input 1 [521]

To select the function of the digital input.

On the standard control board there are four digital inputs.

If the same function is programmed for more than one input,

that function will be activated according to “OR” logic if

nothing else is stated.

T

AnIn change

Original AnIn signal

Filtered AnIn signal

NOTE: Additional inputs will become available when the

I/O option boards are connected.

Figure53 AnInchange100%,63%;originalstepversusfilteredcurve;Tand5×T on t[s]. Sourceclaims100%at5T;notaltered. InputStop/EnableAND; otherfunctionsORunlessstated.

Parameter panel 5139 AnIn Filt; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 521 DigIn 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 513A AnIn Enabl; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5139 AnIn Filt — PDF page 98

Source row Label Value
1 Default: 0.100 s
2 Range: 0.001 – 10.0 s

Parameter panel 521 DigIn 1 — PDF page 98

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Run FWD
2 Off 0 The input is not active.
3 Stop 1 Stop command according to the selected
Stop mode in menu [340].
NOTE: The Stop command is active low.
NOTE: Activated according to “AND” logic.
4 Reset 2 Reset command. To reset a Trip condition
and to enable the Autoreset function.
5 Enable 3 Enable command. General start condition
to run the softstarter. If made low during
running, the output of the softstarter is cut
off immediately, causing the motor to coast
to zero speed.
NOTE: If none of the digital inputs are
programmed to “Enable”, the internal
enable signal is set active.
NOTE: Activated according to “AND” logic.
6 Run FWD 4 Run forward command (positive speed).
The output of the softstarter will be a
clockwise rotary field.
7 Run REV 5 Run reverse command (negative speed).
The output of the softstarter will be a
counter-clockwise rotary field. External
contactors required.
8 Jog FWD 6 Activates the Jog forward function. Gives a
run command with set Jog speed and
direction, menu [350].
NOTE: Always level controlled even though
edge control may be chosen in menu [21A].
9 Jog REV 7 Activates the Jog reverse function. Gives a
run command with set Jog speed and
direction, menu [350].
NOTE: Always level controlled even though
edge control may be chosen in menu [21A].
10 Set Ctrl 1 8 Activates other parameter set. See Table
25 for selection possibilities.
11 Set Ctrl 2 9 Activates other parameter set. See Table
25 for selection possibilities.
12 Loc/Rem 10 Activates local mode defined in [2173].

Parameter panel 513A AnIn Enabl — PDF page 98

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ On
2 On 0 AnIn is always active
3 !DigIn 1 AnIn is only active if the digital input is low.
4 DigIn 2 AnIn is only active if the digital input is high.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 99

Manual reference: physical PDF page 99. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Digital Input 2 [522] to Digital Input 4

[524]

Same function as DigIn 1[521]. Default setting for DigIn 2

[522] is “Stop”. For DigIn 3 [523] the default is “Set Ctrl 1”

and for DigIn 4 [524] the default is “Reset”.

Additional digital inputs [529] to [52E]

Additional digital inputs with I/O option board installed,

“B1 DigIn 1” [529] - “B2 DigIn 3” [52E]. “B” stands for

“board”, 1 and 2 is the number of the board which is related

to the position of the I/O option board on the option

mounting plate. The functions and selections are the same as

for “DigIn 1” [521]. Default settings are “Off”.

8.5.3

Analogue Output [530]

Submenu with all settings for the analogue output.

Selections can be made from application and softstarter

values, in order to visualise actual status. Analogue output

can also be used as a mirror of the analogue input.

Analogue Output Function [531]

Sets the function for the analogue output. Scale and range are

defined by “AnOut Advanced” settings [533].

Table 25

NOTE: To activate the parameter set selection, menu

241 must be set to DigIn.

Digital521continuation includescodes11,12,13,14reserved,16–21;no15. Timerrowsliteralreferences6343/6313/6323/6333 preserved. Table25 A00,B10,C01,D11;241mustDigIn.

Digital input521 continuation; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 531 AnOut Fc; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table25 parameter set controls; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Digital input521 continuation — PDF page 99

Source row Selection or label Communication code or merged label Description or default/range
1 AnIn Select 11 Activates/deactivates analogue input
defined in [513A].
2 Autoset 12 Activates autoset of load monitor alarm
levels according to menu group [417].
NOTE: Always level controlled even though
edge control may be chosen in menu [21A].
3 Spinbrake 13 See description Spinbrake, page 39. Can
be activated either from inactive state
(softstarter stopped but motor rotating) or
active state (when running).
4 --- 14 (Reserved for future use).
5 Ext. Alarm 1 16 Be aware that if there is nothing connected
to the input, the softstarter will trip at
“External Alarm 1” immediately.
NOTE: The External Trip is active low.
NOTE: Activated according to “AND” logic.
See menu [2549].
6 Ext. Alarm 2 17 Be aware that if there is nothing connected
to the input, the softstarter will trip at
“External Alarm 2” immediately.
NOTE: The External Alarm 2 is active low.
See menu [254A].
7 Timer 1 18 Timer 1 Delay [6343] will be activated on
the rising edge of this signal.
8 Timer 2 19 Timer 1 Delay [6313] will be activated on
the rising edge of this signal.
9 Timer 3 20 Timer 2 Delay [6323] will be activated on
the rising edge of this signal.
10 Timer 4 21 Timer 1 Delay [6333] will be activated on
the rising edge of this signal.

Parameter panel 531 AnOut Fc — PDF page 99

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Current
2 Off 0 Analogue output not active.
3 Torque 2 Actual torque.
4 Process Val 3 Actual process value according to
Process feedback signal.
5 Shaft Power 4 Actual shaft power.
6 Current 6 Actual current.
7 El power 7 Actual electrical power.
8 AnIn 10 Mirror of received signal value on AnIn.
9 Line Voltage 14 Mains supply
10 Therm Cap 15 Used thermal capacity

Table25 parameter set controls — PDF page 99

Source row Parameter Set Set Ctrl 1 Set Ctrl 2
1 A 0 0
2 B 1 0
3 C 0 1
4 D 1 1

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 100

Manual reference: physical PDF page 100. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Output Setup [532]

Preset scaling and offset of the output configuration.

Analogue Output Advanced [533]

With the functions in the “AnOut Advanced” menu, the

output can be completely defined according to the

application needs. The menus will automatically be adapted

to “mA” or “V”, according to the selection in “AnOut Setup”

[532].

Analogue Output Minimum [5331]

This parameter is automatically displayed if “User mA” or

“User V” is selected in menu “AnOut Setup” [532]. The

menu will automatically adapt to current or voltage setting

according to the selected setup. Only visible if [532] = “User

mA/V”.

Analogue Output Maximum [5332]

AnOut Function Minimum [5334]

With “AnOut Function Min” the physical minimum value is

scaled to selected presentation. The default scaling is

dependent of the selected function of AnOut [531].

Table 26, page 96 shows corresponding values for the min

and max selections depending on the function of the

analogue output [531].

NOTE: When “AnIn” is selected, the setup of the “AnOut”

[532] has to be set to 0-10 V or 0-20 mA. When the

“AnOut Setup” is set to e.g. 4-20 mA, the mirroring is not

working correctly.

533 AnOut Advan

Stp

Table 26

Table26 rangeforProcessValue324→325,ShaftPower0%→223,Current0A→224,ElPower0W→223,OutputVoltage0V→221,Torque0%→250%,AnInFunctionMin→FunctionMax. Thesearefunctionscalesnotallproductratings.

Parameter panel 5331 AnOut Min; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 532 AnOut Setup; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5332 AnOut Max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5334 AnOutFcMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Table26 analogue output min/max; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Adjacent source context — repeated to preserve continuation:

Parameter panel 5331 AnOut Min — PDF page 100

Source row Label Value
1 Default: 4.00 mA
2 Range: 0.00 – 20.00 mA, 0 – 10.00 V

Parameter panel 532 AnOut Setup — PDF page 100

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦blank source cell⟧ 4-20mA
2 4–20mA 0 The current output has a fixed threshold
(Live Zero) of 4 mA and controls the full
range for the output signal. See Fig. 51.
3 0–20mA 1 Normal full current scale configuration of
the output that controls the full range for
the output signal. See Fig. 50.
4 User mA 2 The scale of the current controlled output
that controls the full range for the output
signal. Can be defined by the advanced
AnOut Min and AnOut Max menus.
5 0 - 10V 4 Normal full voltage scale configuration of
the output that controls the full range for
the output signal. See Fig. 50.
6 2–10V 5 The voltage output has a fixed threshold
(Live Zero) of 2 V and controls the full
range for the output signal. See Fig. 51.
7 User V 6 The scale of the voltage controlled output
that controls the full range for the output
signal. Can be defined by the advanced
AnOut Min and AnOut Max menus.

Parameter panel 5332 AnOut Max — PDF page 100

Source row Label Value
1 Default: 20.00 mA
2 Range: 0.00–20.00 mA, 0–10.00 V

Parameter panel 5334 AnOutFcMin — PDF page 100

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Min
2 Min 0 Min value
3 Max 1 Max value
4 User-defined 2 Define user value in menu [5335]

Table26 analogue output min/max — PDF page 100

Source row AnOut
Function
Min Value Max Value
1 Process Value Process Min [324] Process Max [325]
2 Shaft Power 0% Motor Power [223]
3 Current 0 A Motor Current [224]
4 El Power 0 W Motor Power [223]
5 Output Voltage 0 V Motor Voltage [221]
6 Torque 0 % 250 %
7 AnIn AnIn Function Min AnIn Function Max

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 101

Manual reference: physical PDF page 101. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example

Set the AnOut function for “Motor Current” to 0 A, set

”AnOut Function Min” [5334] to “User-defined” and

“AnOut Function Value Min” [5335] = 0.0. This results in an

analogue output signal from 0/4 mA to 20mA: from 0 A to

the value for “Motor Current” that is set in menu [224].

This principle is valid for all Min to Max settings.

AnOut Function Value Minimum [5335]

With “AnOutVaMin” you define a user-defined value for the

signal. Only visible when “User-defined” is selected in menu

[5334].

AnOut Function Maximum [5336]

With “AnOut Function Min” the physical minimum value is

scaled to selected presentation. The default scaling is

dependent on the selected function of AnOut [531]. See

Table 26, page 96.

AnOut Function Value Maximum [5337]

With “AnOut FunctionVaMax” you define a user-defined

value for the signal. Only visible when “User-defined” is

selected in menu [5334].

8.5.4

Relays [550]

Submenu with all the settings for the relay outputs. The relay

mode selection makes it possible to establish a “fail safe” relay

operation by using the normal closed contact to function as

the normal open contact.

Relay 1 [551]

Sets the function for the relay output 1.

NOTE: It is possible to set AnOut up as an inverted

output signal by setting “AnOut Min” > “AnOut Max”.

See Fig. 52.

NOTE: Additional relays will become available when I/O

option boards are connected. Maximum 2 boards with 3

relays each.

551LCDTrip versusDefaultOperation; selectionscontinue102.5336sourcewordingFunctionMinand5337reference5334retained; noautomaticediting.

Parameter panel 5335 AnOutVaMin; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 551 Relay 1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 5336 AnOutFcMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 5337 AnOutVaMax; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Adjacent source context — repeated to preserve continuation:

Parameter panel 5335 AnOutVaMin — PDF page 101

Source row Label Value
1 Default: 0.000
2 Range: -10,000.000–10,000.000

Parameter panel 551 Relay 1 — PDF page 101

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Operation
2 Off 0 Output is not active and constantly
low.
3 On 1 Output is made constantly high, i.e.
for checking circuits and trouble
shooting.
4 Operation 2 See Fig. 54
5 No Operation 3 Inverted operation
6 Bypass mode 4 See Fig. 54
7 Acc/Dec 5 The speed is increasing or decreasing
along the acc. ramp/dec. ramp.
8 No Trip 6 No Trip condition active.
9 Trip 7 A Trip condition is active.
10 AutoRst Trip 8 Autoreset trip condition active.
11 Warning 9 A Warning condition is active.
12 Ready 10 The softstarter is ready for operation
and to accept a start command. This
means that the softstarter is powered
up and in good working condition.
13 I>I
n_mot
11 The output current is higher than the
motor nominal current [224], reduced
according to Motor ventilation [228].
See Fig. 8.2.4.
14 RevCurrBrake 12 The output is used to control a reverse
current brake.
15 LoadMonAlarm 13 Max or min alarm condition active
(trip or warning).
16 Pre Alarm 14 Max or min pre-alarm condition active
(trip or warning).
17 Max Alarm 15 Max alarm condition active (trip or
warning).
18 Max PreAlarm 16 Max pre-alarm condition active (trip or
warning).
19 Min Alarm 17 Min alarm condition active (trip or
warning).

Parameter panel 5336 AnOutFcMax — PDF page 101

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Max
2 Min 0 Min value
3 Max 1 Max value
4 User defined 2 Define user value in menu [5337 ]

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 102

Manual reference: physical PDF page 102. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Relay551 continuation codes18–60left,61–81then90/97/98/101/103–107/112right. OperationREVliteralnegative speed<0.5%;missingminus notinferred. I²t105labelmayflattennative.

Relay551 selections continuation; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Relay551 selections continuation — PDF page 102

Source row Selection or label Communication code or merged label Description or default/range
1 Min PreAlarm 18 Min pre-alarm condition active (trip or
warning).
2 CA 1 19 Analogue comparator 1 output.
3 !A1 20 Analogue comp 1 inverted output.
4 CA 2 21 Analogue comparator 2 output.
5 !A2 22 Analogue comp 2 inverted output.
6 CA 3 23 Analogue comparator 3 output.
7 !A3 24 Analogue comp 3 inverted output.
8 CA 4 25 Analogue comparator 4 output.
9 !A4 26 Analogue comp 4 inverted output.
10 CD 1 27 Digital comparator 1 output.
11 !D1 28 Digital comp 1 inverted output.
12 CD 2 29 Digital comparator 2 output.
13 !D2 30 Digital comp 2 inverted output.
14 CD 3 31 Digital comparator 3 output.
15 !D3 32 Digital comp 3 inverted output.
16 CD 4 33 Digital comparator 4 output.
17 !D4 34 Digital comp 4 inverted output.
18 T1Q 35 Logic timer 1 output
19 !T1Q 36 Inverted logic timer 1 output
20 T2Q 37 Logic timer 2 output
21 !T2Q 38 Inverted logic timer 2 output
22 T3Q 39 Logic timer 3 output
23 !T3Q 40 Inverted logic timer 3 output
24 T4Q 41 Logic timer 4 output
25 !T4Q 42 Inverted logic timer 4 output
26 L1 43 Logic output 1.
27 !L1 44 Logic output 1 inverted.
28 L2 45 Logic output 2.
29 !L2 46 Logic output 2 inverted.
30 L3 47 Logic output 3.
31 !L3 48 Logic output 3 inverted.
32 L4 49 Logic output 4.
33 !L4 50 Logic output 4 inverted.
34 F1 51 Flip-flop output 1.
35 !F1 52 Flip-flop output 1 inverted.
36 F2 53 Flip-flop output 2.
37 !F2 54 Flip-flop output 2 inverted.
38 F3 55 Flip-flop output 3.
39 !F3 56 Flip-flop output 3 inverted.
40 F4 57 Flip-flop output 4.
41 !F4 58 Flip-flop output 4 inverted.
42 CTR1 59 Counter output 1.
43 !CTR1 60 Counter output 1 inverted.

Relay551 selections continuation — PDF page 102

Source row Selection or label Communication code or merged label Description or default/range
1 CTR2 61 Counter output 2.
2 !CTR2 62 Counter output 2 inverted.
3 CLK1 63 Clock output 1 (Clock logic [660]).
4 !CLK1 64 Clock output 1 inverted.
5 CLK2 65 Clock output 2 (Clock logic [660]).
6 !CLK2 66 Clock output 2 inverted.
7 Run Signal 67 Run command is active. The signal
can be used to control the mains
contactor
8 Loc/Rem 68 Local/Rem function is active
9 Acc 69 Acceleration along the acc. ramp
10 Dec 70 Deceleration along the dec. ramp
11 DigIn 1 71 Digital input 1
12 DigIn 2 72 Digital input 2
13 DigIn 3 73 Digital input 3
14 DigIn 4 74 Digital input 4
15 RunSignalFWD 75 Relay signal used together with
Run FWD signal
16 RunSignalREV 76 Relay signal used together with
Run REV signal
17 OperationFWD 77 Positive speed (>0.5%), i.e. forward/
clockwise direction.
18 OperationREV 78 Negative speed (<0.5%), i.e. reverse
counter clockwise direction.
19 ManRst Trip 79 Any active trip condition that needs a
manual reset
20 Alarm 80 Alarm triggered
21 Alarm (ex LM) 81 Alarm triggered (except load monitor)
22 Overvolt 90 Overvoltage alarm active (trip or
warning)
23 Com Error 97 Communication error active (trip or
warning)
24 Com Active 98 Fieldbus communication active.
25 Overtemp 101 Softstarter overtemperature condition
is active (trip)
26 PTC Alarm 103 PTC alarm active (trip or warning)
27 PT100 Alarm 104 PT100 alarm active (trip or warning)
28 I2t 105 I2t alarm active (trip or warning)
29 Ext Alarm 1 106 Output active
30 Ext Alarm 2 107 Output active
31 Option 112 Failure occurred in built-in option
board

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 103

Manual reference: physical PDF page 103. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 54 Relay functions.

Relay 2 [552]

This menu sets the function for the relay output 2.

Relay 3 [553]

This menu sets the function for the relay output 3.

Board Relay [554] to [559]

These additional relays are only visible if an I/O option board

is fitted in slot 1 or 2. The outputs are named “B1 Relay 1” -

“B1 Relay 3” and “B2 Relay 1” - “B2 Relay 3”. “B” stands for

“board” and 1 and 2 is the number of the board which is

related to the position of the I/O option board on the option

mounting plate. The functions and selections are the same as

for “Relay 1” [551]. Default settings are “Off”.

Relay Advanced [55D]

This function makes it possible to ensure that the relay will

be closed also when the softstarter is malfunctioning or

powered down.

Relay 1 Mode [55D1]

Relay Modes [55D2] to [55DC]

Same function as for “Relay 1 Mode” [55D1]. Default

settings are “N.O”.

8.5.5

Virtual I/Os [560]

Virtual connections are used for wireless connection of a

digital output function to a digital input function. The

available signals and control functions can be used to create

your own specific functions.

In these menus you find functions to enable eight internal

connections of comparators, timers, SR flip-flops, counters,

and digital signals, without occupying physical digital inputs

or relay outputs.

NOTE: The definitions described here are valid for the

active output condition.

Bypass mode

Motor voltage

Operation

Reverse

Run

Stop time

Start time

Delay

Full voltage

current rake

NOTE: Visible only if optional board is detected or if any

input/output is activated.

55D Relay Advan

Stp

Figure54:Motorvoltage,Operation,Bypassmode,Run,Reverse current rake;all t[s]. Delay0.1s thenStarttime,Fullvoltage,Stoptime. Operationhighstartthroughstop;Bypasshighfullvoltage;Runhighstart/full;reversecurrenthighstop. Diagramillustrationnotuniversalmechanicalstopproof.

Parameter panel 55D1 Relay1 Mode; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Parameter panel 552 Relay 2; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 553 Relay 3; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 55D1 Relay1 Mode — PDF page 103

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ N.O
2 N.O 0 The normal open contact of the relay will
be activated when the function is active.
3 N.C 1 The normally closed contact of the relay
will act as a normal open contact. The
contact will be opened when function is
not active and closed when function is
active.

Parameter panel 552 Relay 2 — PDF page 103

Source row Label Value
1 Default: Off
2 Selection: Same selection as in menu Relay 1 [551],
page 97.

Parameter panel 553 Relay 3 — PDF page 103

Source row Label Value
1 Default: Trip
2 Selection: Same selection as in menu Relay 1 [551],
page 97.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 104

Manual reference: physical PDF page 104. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Example: Start delay

The motor will start in forward direction 10 seconds after

DigIn1 is activated (high). DigIn1 has a time delay of 10 s.

Virtual Connection 1 Destination [561]

With this function the destination of the virtual connection

is established. When a function can be controlled by several

sources, e.g. “VIO Destination” or “Digital Input”, the

function will be controlled in conformity with “OR logic”.

See section 8.5.2, page 94 (Digital Input) for descriptions of

the different selections.

Virtual Connection 1 Source [562]

With this function the source of the virtual connection is

defined. See "Relays [550]", page 97 for description of the

different selections.

Virtual Connections 2-8 [563] to [56G]

Same function as “Virtual Connection 1” [561] and [562].

Default settings are “Off”.

8.6

Logical Functions and

Timers [600]

In the “Logic&Timers” menu [600] you access comparators,

logic functions, SR flip-flops, timers, and counters, enabling

conditional signals to be programmed for control or

signalling features. This gives you the ability to compare

different signals and values in order to generate monitoring/

controlling features.

All these functions are updated in 8 milliseconds intervals.

8.6.1

Comparators [610]

The comparator function makes it possible to monitor

different internal signals and values, and to visualise (via

digital relay outputs) when a specific value or status is reached

or established. The output signals of the comparators can be

logically tied together to yield a logical output signal.

All the output signals can be programmed to the digital or

relay outputs or used as a source for the virtual connections

[560].

For each digital and analogue comparator it is possible to

apply a “Set Delay”, a “Reset Delay”, and a “Timer Value”;

functions that could be used to extend or delay the output

signal.

Analogue Comparator Setup [611] - [614]

There are 4 analogue comparators that compare any

available analogue value with two adjustable levels. The two

levels available are “Level HI” and “Level LO”. There are also

two analogue comparator types, selected in menu

“Comparator Type”, an analogue comparator with hysteresis

and an analogue window comparator.

The analogue hysteresis type comparator uses the two

available levels to create a hysteresis for the comparator

between setting and resetting the output. This function gives

a clear difference in switching levels, which lets the process

adapt until a certain action is started. With such a hysteresis,

even an unstable analogue signal can be monitored without

getting a nervous comparator output signal. Another feature

is the possibility to get a fixed indication that a certain level

has been passed. The comparator can latch by setting “Level

LO” to a higher value than “Level HI”.

The analogue window comparator uses the two available

levels to define the window in which the analogue value

should be within for setting the comparator output.

Digital Comparator Setup [615] - [618]

There are also 4 digital comparators that compare any

available digital signals.

NOTE: When a digital input and a virtual destination are

set to the same function, this function will act as an OR

logic function.

Example521Timer1,561RunFWD,562T1Q,6311DigIn1,6312Delay,63130:00:10. Eightinternalvirtualconnections distinguishfromphysicalrelays. Comparatorshysteresis/window distinct.

Start delay example; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 561 VIO 1 Dest; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 562 VIO 1 Source; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Start delay example — PDF page 104

Source row Menu Parameter Setting
1 [521] DigIn1 Timer 1
2 [561] VIO 1 Dest Run FWD
3 [562] VIO 1 Source T1Q
4 [6311] Timer1 Trig DigIn 1
5 [6312] Timer1 Mode Delay
6 [6313] Timer1 Delay 0:00:10

Parameter panel 561 VIO 1 Dest — PDF page 104

Source row Label Value
1 Default: Off
2 Selection: Same selections as in menu Digital Input 1
[521], page 94.

Parameter panel 562 VIO 1 Source — PDF page 104

Source row Label Value
1 Default: Off
2 Selection: Same selection as in menu Relay 1 [551],
page 97.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 105

Manual reference: physical PDF page 105. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Setup Analogue Comparator 1 [611]

Analogue comparator 1, parameter group.

Analogue Comparator 1, Value [6111]

Selection of the analogue value for “Analogue Comparator 1”

(CA1).

The analogue comparator compares the selectable analogue

value in menu [6111] with the constant “Level HI” in menu

[6112], and the constant “Level LO” in menu [6113].

In menu Comparator Type [6114] “Hysteresis” or

“Window” can be selected. For the hysteresis function, when

the value exceeds the upper limit level high, the output signal

CA1 is set high and !A1 low. See Fig. 55. When the value

decreases below the lower limit, the output signal CA1 is set

low and !A1 high.

Fig. 55 Analogue comparator type “Hysteresis”

For the window type comparator, when the value is between

the lower and upper levels, the output signal value CA1 is set

high and !A1 low. See Fig. 56. When the value is outside the

band of lower and upper levels, the output CA1 is set low and

!A1 high.

Fig. 56 Analogue comparator type “Window”

The output signal can be programmed as a virtual

connection source and to the relay outputs.

Example:

An analogue level sensor with current signal, 4-20 mA, is

connected to the analogue input. See table below.

When the signal on AnIn goes above 60%, the CA output

signal is activated (high), and when the signal on AnIn goes

below 40%, the CA output signal is deactivated (low) again.

The output of CA1 is used as a virtual connection source that

controls the virtual connection destination Run FWD.

CA1 Value [6111]

CA1 Level HI [6112]

CA1 Level LO [6113]

CA1

AND

Figure55 CA1Value6111,LevelHI6112,LevelLO6113 selector0/1 feedinghysteresisandCA1. Figure56high/lowcomparatorsAND→CA1. OutputCA1/!A1oppositeperprose;noelectricalwiringinferred.

Parameter panel 6111 CA1 Value; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Shared source cells (coordinates refer to this table):

Comparator current sensor example; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6111 CA1 Value — PDF page 105

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Current
2 Process Val 0 ⟦blank source cell⟧
3 Torque 1 %
4 Shaft Power 2 kW
5 El Power 3 kW
6 Current 4 A
7 Heatsink Tmp 5 °C
8 PT100_1 6 °C
9 PT100_2 7 °C
10 PT100_3 8 °C
11 Energy 9 kWh
12 Run Time 10 h
13 Mains Time 11 h
14 AnIn 12 %
15 PT100_4 13 °C
16 PT100_5 14 °C
17 PT100_6 15 °C

Comparator current sensor example — PDF page 105

Source row Menu Function Setting
1 511 AnIn Function Process value
2 512 AnIn Setup 4-20 mA
3 6111 CA1 Value AnIn 1
4 6112 CA1 Level HI 60% (12 mA/20 mA x 100%)
5 6113 CA1 Level LO 40% (8 mA/20 mA x 100%)
6 6114 CA1 Type Hysteresis
7 561 VIO 1 Dest Run FWD
8 562 VIO 1 Source CA1
9 2151 Run/Stp Ctrl Remote

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 106

Manual reference: physical PDF page 106. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 57

Analogue Comparator 1,

Level High [6112]

Sets the analogue comparator high level, with range

according to the selected value in menu [6111].

Example

This example describes, both for hysteresis and window type

comparators, the normal use of the constant level high and

low. The function is used for temperature control. Follow the

step by step explanation in Table 27 and Table 28.

Fig. 58

t [s]

CA1 Level HI

CA1 Level LO

Reference signal AnIn

CA1

Mode

RUN

STOP

Max

Temp.

50°C

40°C

CA1 output

High

Low

Hysteresis

Window

Hysteresis/

window band

Figure57 referenceAnIn[mA],20/12/8/4,LevelHI12/LO8,t[s],events1–4;CA1andModeRUN/STOPtraces. Row1modeRUN conflictsplottedSTOP. Figure58MaxTemp50°C/40°Cband,t[s],events1–8;hysteresis/windowHigh/Lowtraces. Adjacenttable27/28governnumberedstates.

Parameter panel 6112 CA1 LevelHI; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Temperature control example; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Figure57 numbered states; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6112 CA1 LevelHI — PDF page 106

Source row Label Value
1 Default: 30.0
2 Range: 1=1 W, 0.1 A, 0.1 V, 1%, 0.1°C, 1 kWh, 1h,
or 0.001 in [322]

Temperature control example — PDF page 106

Source row Menu Function Setting
1 325 Process Max Temperature: 100°C
2 6111 CA1 Value PT100_1 (°C)
3 6112 CA1 Level HI 50°C
4 6113 CA1 Level LO 40°C
5 6114 CA1 Type Window
6 561 VC1 Dest Timer 1
7 562 VC1 Source CA1

Figure57 numbered states — PDF page 106

Source row No. Description
1 1 The reference signal passes the Level LO value from
below (positive edge), the comparator CA1 output stays
low, mode = RUN.
2 2 The reference signal passes the Level HI value from
below (positive edge), the comparator CA1 output is set
high, mode = RUN.
3 3 The reference signal passes the Level HI value from
above (negative edge), the comparator CA1 output stays
high, mode = RUN.
4 4 The reference signal passes the Level LO value from
above (negative edge), the comparator CA1 output =
STOP.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 107

Manual reference: physical PDF page 107. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 27

Comments to Fig. 58 regarding “Hysteresis”

selection.

Table 28

Comments to Fig. 58 regarding “Window”

Table27 Hysteresis columnrow1–8 graphics:horizontalstroke,up,stroke,down,stroke,up,stroke,down. Table28Windowrow1–8:up,down,up,down,up,down,up,down. Nativeemptycells mappedtoexplicitgraphics,notemptydata.

Table27 hysteresis states; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Table28 window states; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Table27 hysteresis states — PDF page 107

Source row No. Description Hysteresis
1 1 The reference signal passes the Level LO
value from below (positive edge), the
comparator CA1 does not change, output
stays low.
⟦blank source cell⟧
2 2 The reference signal passes the Level HI
value from below (positive edge), the
comparator CA1 output is set high.
⟦blank source cell⟧
3 3 The reference signal passes the Level HI
value from above (negative edge), the
comparator CA1 does not change, output
stays high.
⟦blank source cell⟧
4 4 The reference signal passes the Level LO
value from above (negative edge), the
comparator CA1 is reset, output is set low.
⟦blank source cell⟧
5 5 The reference signal passes the Level LO
value from below (positive edge), the
comparator CA1 does not change, output
stays low.
⟦blank source cell⟧
6 6 The reference signal passes the Level HI
value from below (positive edge), the
comparator CA1 output is set high.
⟦blank source cell⟧
7 7 The reference signal passes the Level HI
value from above (negative edge), the
comparator CA1 does not change, output
stays high.
⟦blank source cell⟧
8 8 The reference signal passes the Level LO
value from above (negative edge), the
comparator CA1 is reset, output is set low.
⟦blank source cell⟧

Table28 window states — PDF page 107

Source row No. Description Window
1 1 The reference signal passes the Level LO
value from below (signal inside Window
band), the comparator CA1 output is set high.
⟦blank source cell⟧
2 2 The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
⟦blank source cell⟧
3 3 The reference signal passes the Level HI
value from above (signal inside Window
band), the comparator CA1 output is set high.
⟦blank source cell⟧
4 4 The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
⟦blank source cell⟧
5 5 The reference signal passes the Level LO
value from below (signal inside Window
band), the comparator CA1 output is set high.
⟦blank source cell⟧
6 6 The reference signal passes the Level HI
value from below (signal outside Window
band),the comparator CA1 is reset, output is
set low.
⟦blank source cell⟧
7 7 The reference signal passes the Level HI
value from above (signal inside Window
band), the comparator CA1 output is set high.
⟦blank source cell⟧
8 8 The reference signal passes the Level LO
value from above (signal outside Window
band), the comparator CA1 is reset, output is
set low.
⟦blank source cell⟧

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 108

Manual reference: physical PDF page 108. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Comparator 1

Level Low [6113]

Sets the analogue comparator low level, with unit and range

according to the selected value in menu [6111].

Analogue Comparator 1 Type [6114]

Selects the analogue comparator type, i.e. hysteresis or

window type. See Fig. 55 and Fig. 56, page 101.

Analogue Comparator 1 Set Delay

[6116]

The output signal for the analogue comparator 1 is delayed

with the set value in this menu. See Fig. 59.

Fig. 59 Set/reset delay of output signal.

Analogue Comparator 1 Reset Delay

[6117]

The reset of the output signal for the analogue comparator 1

is delayed with the set time in this menu. See Fig. 59..

Analogue Comparator 1 Timer Value

[6118]

The actual timer value for analogue comparator 1 is viewed

in this menu.

Setup Analogue comparators 1 - 4

[612] - [614]

Refer to the descriptions for analogue comparator 1.

Setup Digital Comparator 1 [615]

Digital comparators, parameter group.

Digital Comparator 1 Input

[6151]page 120

Selection of the input signal for digital comparator 1 (CD1).

The output signal CD1 is set high if the selected input

signal is active. See Fig. 60.

The output signal can be programmed to the relay outputs or

used as a source for the virtual connections [560].

Set delay

Reset delay

Figure59 originalpulse anddelayedoutput withSetdelay/Resetdelayarrows;no numericaldelaydrawn.6151CD1defaultOperation.6118actualtimerdisplaydistinctfromset/resetvalues.

Parameter panel 6113 CA1 LevelLO; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6117 CA1 Res Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6114 CA1 Type; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6118 CA1 Tmr Val; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6116 CA1 Set Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6151 CD1; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6113 CA1 LevelLO — PDF page 108

Source row Label Value
1 Default: 20.0
2 Range: See [6112].

Parameter panel 6117 CA1 Res Dly — PDF page 108

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Parameter panel 6114 CA1 Type — PDF page 108

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦blank source cell⟧ Hysteresis
2 Hysteresis 0 Hysteresis type comparator
3 Window 1 Window type comparator

Parameter panel 6151 CD1 — PDF page 108

Source row Label Value
1 Default: Operation
2 Selection: Same selection as in menu Relay 1
[551], page 97.

Manual — P036; functionality settings. Source defaults depend on model,units,installedoptions and selectedmotor. Supplier instructions not independently validated advice. — page 109

Manual reference: physical PDF page 109. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 60 Digital comparator.

Digital Comparator 1 Set Delay [6152]

The activation of the output signal for the digital comparator

1 is delayed with the set value in this menu. See also Fig. 59,

page 104.

Digital Comparator 1 Reset Delay

[6153]

The reset of the output signal for the digital comparator 1 is

delayed with the set value in this menu. See also Fig. 59, page

104.

Digital Comparator 1 Timer Value

[6154]

The actual timer value for digital comparator 1 is viewed in

this menu.

Setup Digital Comparators 2 - 4 [616]-

[618]

Refer to the description of Digital Comparator 1. Default for

CD2 [6161] is “DigIn 1”. For CD3 [6171] the default is

“Trip”, and for CD4 [6181] the default is “Ready”.

8.6.2

Logic outputs [620]

Logic 1 [621]

By means of an expression editor, the input signals can be

logically combined into the logics function to create a logic

output signal.

The expression editor has the following features:

•

The following input signals can be used:

CA1-CA4, CD1-CD4, L1-L4, T1Q-T4Q, F1-F4, and

CTR1-CTR2.

The following inverted input signals can be used:

!A1-!A4, !D1-!D4, !L1- !L4, !T1Q-!T4Q, !F1-!F4, and

!CTR1-!CTR2.

The following logical operators are available:

"+" : OR operator

"&" : AND operator

"^" : EXOR operator

Expressions according to the following truth table can be

made (see also the example below):

The output signal can be programmed to the relay outputs or

used as a virtual connection source [560].

The logic expression must be programmed by means of the

menus [6211] to [621B], and its actual appearance can be

viewed in menu [621], with example below:

Input signal for CD1 [6151]

Digital comparator 1

CD1

Read-only

621 Logic 1

Stp

((1&2)&3)&4

Figure60 inputsignal6151→Digitalcomparator1→CD1;symbol+/−. Logic621readonlyexample((1&2)&3)&4;truth tableA/Binputs andAND/OR/EXORoutputs. No configurationsbeyondthispage inferred.

Parameter panel 6152 CD1 Set Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Logic truth table; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6153 CD1 Res Dly; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6154 CD1 Tmr Val; software1.0X editionR0. First source row is LCD/display context, not separate model rating. Default/range rows and communication integers retained separately. Physical merged/null cells retain parent association; no inferred applicability or engineering validation.

Parameter panel 6152 CD1 Set Dly — PDF page 109

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Logic truth table — PDF page 109

Source row A B & (AND) + (OR) ^(EXOR)
1 0 0 0 0 0
2 0 1 0 1 1
3 1 0 0 1 1
4 1 1 1 1 0

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 110

Manual reference: physical PDF page 110. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Logic 1 Expression [6211]

Selection of execution order of the logic expression for the

Logic 1 function:

•

Parentheses ( ) show the order in which the Logic 1

Inputs are combined, according to [6211].

1, 2, 3, and 4, represent the Logic 1 Input signals

selected in menu [6212], [6214], [6216], and [6218].

The dots stand for the Logic 1 Operators (&, +, or ^),

whose values are selected in menus [6213], [6215], and

[6217].

To build the Logic 1 expression using the default selection in

menu [6211], the execution order is as follows:

  1. Input 1 is combined with Input 2 using Operator 1.

  2. Input 3 is combined with the expression (1.2), using

Operator 2.

  1. Input 4 is combined with the result of (1.2).3, using

Operator 3.

The alternative execution order leads to:

  1. Input 3 is combined with Input 4 using Operator 3.

  2. Expression (1.2) is combined with expression (3.4),

using Operator 2.

Example:

Input 1 = CA1, set in menu [6212]

Input 2 = F1, menu [6214]

Input 3 = T1Q, menu [6216]

Input 4 = !A2, menu [6218]

Operator 1 = & (AND), set in menu [6213]

Operator 2 = + (OR), menu [6215]

Operator 3 = & (AND), menu [6217]

The following expression is created, using the menus above:

CA1&F1+T1Q&!A2

With the default setting for L1 Expression this is viewed in

[621] as:

representing:

((CA1&F1)+T1Q)&!A2

Let’s use the following values on the input signals as an

example:

CA1=1 (active/high)

F1= 1 (active/high)

T1Q = 1 (active/high)

!A2 = 0 (inactive/low)

With the respective values inserted the resulting logic

expression is:

((1&1)+1)&0

which is equal to 0.

With the alternative execution order for the L1 Expression

the expression is viewed in [621] as:

(CA1&F1)+(T1Q&!A2)

With the above values inserted the resulting logic expression

now becomes:

(1&1)+(1&0)

which is equal to 1.

621 Logic 1

Stp

((1&2)+3)&4

(1&2)+(3&4)

The LCD examples show ((1&2)+3)&4 and (1&2)+(3&4). The black A badge denotes the displayed parameter set; it is separate from the logic input labels.

Parameter panel 6211 L1 Expr; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 6211 L1 Expr — PDF page 110

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ ((1.2).3).4
2 ((1.2).3).4 0 Default execution order, see
explanation below.
3 (1.2).(3.4) 1 Alternative execution order, see
explanation below.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 111

Manual reference: physical PDF page 111. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Logic 1 Input 1 [6212]

In this menu the first input for the Logic 1 function is

selected. The same selections are valid for [6214] L1 Input 2,

[6216] L1 Input 3, and [6218] L1 Input 4.

This table is also valid for the input signals in logic functions

2 [622], 3 [623], and 4 [624], however default values vary.

See Menu List in Appendix 1.

Note that a logic function can not directly use itself as an

input signal, e.g. for the L1 Input, it will not be possible to

choose L1 or !L1.

Logic 1 Operator 1 [6213]

In this menu the first operator for the Logic 1 function is

selected.

Logic 1 Input 2 [6214]

In this menu the second input for the Logic 1 function is

6212 source sequence: code0 CA1,1 !A1,2 CA2,3 !A2,4 CA1,5 !A1,6 CA2,7 !A2. Descriptions for4/5 refer comparator3 and6/7 comparator4. Continuation at upper right startsT2Q26 and ends!CTR243; no row omitted.

Logic6212 continuation; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6212 L1 Input 1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 6213 L1 Op 1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6214 L1 Input 2; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Logic6212 continuation — PDF page 111

Source row Input signal Communication code Description
1 T2Q 26 Logic timer 2 output
2 !T2Q 27 Inverted logic timer 2 output
3 T3Q 28 Logic timer 3 output
4 !T3Q 29 Inverted logic timer 3 output
5 T4Q 30 Logic timer 4 output
6 !T4Q 31 Inverted logic timer 4 output
7 F1 32 Flip-flop output 1.
8 !F1 33 Flip-flop output 1 inverted.
9 F2 34 Flip-flop output 2.
10 !F2 35 Flip-flop output 2 inverted.
11 F3 36 Flip-flop output 3.
12 !F3 37 Flip-flop output 3 inverted.
13 F4 38 Flip-flop output 4.
14 !F4 39 Flip-flop output 4 inverted.
15 CTR1 40 Counter output 1.
16 !CTR1 41 Counter output 1 inverted.
17 CTR2 42 Counter 2 output.
18 !CTR2 43 Counter output 2 inverted.

Parameter panel 6212 L1 Input 1 — PDF page 111

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ CA1
2 CA1 0 Analogue comparator 1 output.
3 !A1 1 Analogue comp 1 inverted output.
4 CA2 2 Analogue comparator 2 output.
5 !A2 3 Analogue comp 2 inverted output.
6 CA1 4 Analogue comparator 3 output.
7 !A1 5 Analogue comp 3 inverted output.
8 CA2 6 Analogue comparator 4 output.
9 !A2 7 Analogue comp 4 inverted output.
10 CD1 8 Digital comparator 1 output.
11 !D1 9 Digital comp 1 inverted output.
12 CD2 10 Digital comparator 2 output.
13 !D2 11 Digital comp 2 inverted output.
14 CD3 12 Digital comparator 3 output.
15 !D3 13 Digital comp 3 inverted output.
16 CD4 14 Digital comparator 4 output.
17 !D4 15 Digital comp 4 inverted output.
18 L1 16 Logic output 1.
Not used for Logic 1.
19 !L1 17 Logic output 1 inverted.
Not used for Logic 1.
20 L2 18 Logic output 2.
Not used for Logic 2.
21 !L2 19 Logic output 2 inverted.
Not used for Logic 2.
22 L3 20 Logic output 3.
Not used for Logic 3.
23 !L3 21 Logic output 3 inverted.
Not used for Logic 3.
24 L4 22 Logic output 4.
Not used for Logic 4.
25 !L4 23 Logic output 4 inverted.
Not used for Logic 4.
26 T1Q 24 Logic timer 1 output
27 !T1Q 25 Inverted logic timer 1 output

Parameter panel 6213 L1 Op 1 — PDF page 111

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ &
2 · 0 When · (dot) is selected, the Logic 1
expression is finished (when two or
three expressions are tied together).
3 & 1 &=AND
4 + 2 +=OR
5 ^ 3 ^=EXOR

Parameter panel 6214 L1 Input 2 — PDF page 111

Source row Label Value
1 Default: !A2
2 Selection: Same selection as in menu Logic 1 Input 1
[6212], page 107.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 112

Manual reference: physical PDF page 112. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Logic 1 Operator 2 [6215]

In this menu the second operator for the Logic 1 function is

selected.

Logic 1 Input 3 [6216]

In this menu the third input for the Logic 1 function is

Logic 1 Operator 3 [6217]

In this menu the third operator for the Logic 1 function is

Logic 1 Input 4 [6218]

In this menu the fourth input for the Logic 1 function is

Logic 1 Set Delay [6219]

The activation of the output signal for the Logic 1 function

is delayed with the set value in this menu. Compare to Fig.

59, page 104.

Logic 1 Reset Delay [621A]

The reset of the output signal for the Logic 1 function is

delayed with the set value in this menu. Compare to Fig. 59,

page 104.

Logic 1 Timer Value [621B]

The actual timer value for logic 1 is viewed in this menu.

Logic 2 - 4 [622] - [624]

Refer to the descriptions for Logic 1. For default values see

Menu List in Appendix 1.

Parameter panel 6215 L1 Op 2; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 6218 L1 Input 4; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6219 L1 Set Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6216 L1 Input 3; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 621A L1 Res Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6217 L1 Op 3; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 621B L1 Tmr Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6215 L1 Op 2 — PDF page 112

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ &
2 · 0 When · (dot) is selected, the Logic 1
expression is finished (when two or
three expressions are tied together).
3 & 1 &=AND
4 + 2 +=OR
5 ^ 3 ^=EXOR

Parameter panel 6218 L1 Input 4 — PDF page 112

Source row Label Value
1 Default: CA4
2 Selection: Same selection as in menu Logic 1 Input 1
[6212], page 107.

Parameter panel 6219 L1 Set Dly — PDF page 112

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Parameter panel 6216 L1 Input 3 — PDF page 112

Source row Label Value
1 Default: CA3
2 Selection: Same selection as in menu Logic 1 Input 1
[6212], page 107.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 113

Manual reference: physical PDF page 113. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.6.3

Timers [630]

The timer function can be used as a delay timer, as an interval

timer with separate “on” and “off “ times (alternate mode), or

as a way to prolong a signal (on-time mode). The selected

trigger signal starts the timer function, and the signal is

converted according to the mode settings, resulting in the

timer output signal (T1Q - T4Q).

In “Delay” mode, the activation of the timer output signal

will be delayed in comparison to the trigger signal. The timer

output signal is activated (high) when the set delay time has

expired. See Fig. 61. The timer output signal will however

follow the trigger signal when this is deactivated (low) again.

Fig. 61 Delay timer mode.

In “Alternate” mode, the timer output signal will switch

automatically between high (Timer T1) and low (Timer T2),

according to set interval times. See Fig. 62. When the trigger

signal is deactivated (low) again, the timer output signal will

also be deactivated (low).

Fig. 62 Alternate timer mode.

The function of the “On-time” mode is to extend an

activated (high) timer output signal in comparison to the

trigger signal. See Fig. 63.

Fig. 63 On-time timer mode.

The timer output signals (T1Q - T4Q) can be programmed

to the relay outputs used in logic functions [620], or be used

as a virtual connection source [560].

Timer 1 [631]

Parameter group for Timer 1.

Timer 1 Trigger [6311]

Selection of the trigger signal for the timer function.

Timer 1 Mode [6312]

Selection of the conversion of the trigger signal, according to

the descriptions in Fig. 61 - Fig. 63.

Timer 1 Delay [6313]

This menu is only visible when “Timer Mode “[6312] is set

to “Delay”. When Timer 1 is triggered in menu [6311], the

set value in this menu will delay the activation of the Timer

1 output signal, T1Q.

Timer1 Trig

T1Q

Timer 1 Delay

Timer T2

Timer T1 Timer T2 Timer T1

Timer T1

NOTE: The actual timers are common for all parameter

sets. If the actual parameter set is changed, the timer

functionality will change according to the settings, but

the timer value will stay unchanged. So initialisation of

the timer might differ for a set change compared to

normal triggering of a timer.

Fig61 Timer1 Trig andT1Q: output rising edge delayed byTimer1Delay; fallingedges align. Fig62 alternating T2-low/T1-high intervals. Fig63 shorttriggerpulse leads T1Q highforTimerT1. Graphs are qualitative, withoutscalevalues.

Parameter panel 6311 Timer1 Trig; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6312 Timer1 Mode; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 6313 Timer1 Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6311 Timer1 Trig — PDF page 113

Source row Label Value
1 Default: Off
2 Selection: Same selections as in menu Relay 1 [551], page
97.

Parameter panel 6312 Timer1 Mode — PDF page 113

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Delay
2 Off 0 Timer off.
3 Delay 1 Delays the activation of the output
signal according to menu [6313].
4 Alternate 2 Interval timer for output signal
according to menus [6314] and
[6315].
5 On-time 3 Prolongs the activation of the output
signal according to menu [6314].

Parameter panel 6313 Timer1 Dly — PDF page 113

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 114

Manual reference: physical PDF page 114. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Timer 1 T1 [6314]

This menu sets the “on” time for the “Alternate” and “On-

time” modes in menu [6312] (only visible when one of these

two modes has been selected).

If “Alternate” mode is selected and Timer 1 is triggered on

signal set up in [6311], the timer will automatically keep

switching from the “on” time ([6314] “Timer 1 T1”) to the

“off” time ([6315]”Timer 1 T2”). Hence the output signal

T1Q will alternate between active, “on”, and inactive, “off”.

See Fig. 62.

If “On-time” mode is selected in [6312] and Timer 1 is

triggered in [6311], the timer will extend the activation (“on”

time) of the output signal T1Q to the set value in

[6314]“Timer 1 T1”. See Fig. 63.

Timer 1 T2 [6315]

In this menu the “off” time in the “Alternate” mode is set.

Timer 1 Value [6316]

This menu shows the actual value of the timer.

Timer 2 - 4 [632] - [634]

Refer to the descriptions for Timer 1.

8.6.4

SR Flip-flops [640]

The flip-flop function is a memory circuit that can be used to

store data concerning state. The output from a flip-flop is

dependent not only on its current input, but also on its state

at the moment this is received (hence previous input status

also matters).

The set/reset flip-flop circuit has two input signals, SET and

RESET, that control the state of an output signal, OUT. The

flip-flop will only change output value when the input signal

is at a positive edge.

When none of the input signals are active (i.e. both are =0),

the output signal is consequently inactive (=0). In this case

the flip-flop will keep its current value.

When only one of the input signals is active (=1), this will

directly decide the status of the output signal. Consequently

if SET=1 (active) and RESET=0 (inactive), the SET

command is given to the output signal, OUT. This will result

in a signal change from inactive to active (=1), if not already

in an active state.

Conversely, if SET=0 (inactive) and RESET=1 (active), the

RESET command is given to the output signal, OUT,

causing this to be deactivated (=0).

Flip-flop priority mode

When both input signals are in an active state simultaneously,

i.e. SET=1 and RESET=1, a priority function decides which

signal will influence the output signal. There are three

different priority settings available for the flip-flop function,

selected in the menu for “Flip-flop Mode”. Examples of the

different priority settings are presented in Fig. 64.

Fig. 64 Programmable flip-flop modes.

RESET

SET

OUT

Reset priority

Set priority

Edge controlled without priority

Fig64 shows three separate timing diagrams labelled Reset priority, Set priority, Edge controlled without priority. Each has SET,RESET,OUT traces; no numeric time scale.

Parameter panel 6314 Timer1 T1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6315 Timer1 T2; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6316 Timer1 Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6314 Timer1 T1 — PDF page 114

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 115

Manual reference: physical PDF page 115. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Reset priority

“Reset priority” means that if both input signals are active, it

will be the RESET command that is obeyed, causing the

output signal to become inactive (=0). See Table 29.

Set priority

For “Set priority” the determining input signal is SET should

both input signals be active, resulting in an activated (=1)

output signal. See Table 30.

Edge controlled without priority

The third setting is “Edge controlled”, for which no input

signal has priority over the other. The output signal follows

any of the two input signals (still providing they are at a

positive edge). The most recent registered activity decides the

output. See Table 31.

Should both inputs become activated simultaneously, there

will not be any change; the output signal will just keep its

earlier status.

Flip-flop 1 [641]

Functions for SR flip-flop 1.

Flip-flop 1 Mode [6411]

Priority setting of input signals for flip-flop 1.

Flip-flop 1 Set [6412]

Selection of SET input signal for flip-flop 1.

Flip-flop 1 Reset [6413]

Selection of RESET input signal for flip-flop 1.

Flip-flop 1 Set Delay [6414]

The SET input signal for flip-flop 1 is delayed with the set

value in this menu.

Table 29

Truth table for Reset priority

Table 30

Truth table for Set priority

Table 31

Truth table for Edge control without priority

Table31 rising-edge glyph ↗ appears before1 in SETrow2, RESETrow3 and bothSET/RESETrow4; row2otherinput0/1,OUT1(set);row3otherinput0/1,OUT0(reset);row4OUTNochange. Raw private-use arrowglyph preserved in tablecells.

Table29 reset priority truth table; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6411 F1 Mode; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 6412 F1 Set; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table30 set priority truth table; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6413 F1 Reset; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table31 edge control truth table; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6414 F1 Set Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table29 reset priority truth table — PDF page 115

Source row SET RESET OUT
1 0 0 0 (reset)
2 0 1 0 (reset)
3 1 0 1 (set)
4 1 1 0 (reset)

Parameter panel 6411 F1 Mode — PDF page 115

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ Reset
2 Reset 0 Reset priority.
3 Set 1 Set priority.
4 Edge 2 Edge controlled without priority.

Parameter panel 6412 F1 Set — PDF page 115

Source row Label Value
1 Default: Off
2 Selection: Same selections as in menu Relay 1 [551], page
97.

Table30 set priority truth table — PDF page 115

Source row SET RESET OUT
1 0 0 0 (reset)
2 0 1 0 (reset)
3 1 0 1 (set)
4 1 1 1 (set)

Table31 edge control truth table — PDF page 115

Source row SET RESET OUT
1 0 0 0 (reset)
2 ↗
1
0/1 1 (set)
3 0/1 ↗
1
0 (reset)
4 ↗
1
↗
1
No change

Parameter panel 6414 F1 Set Dly — PDF page 115

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 116

Manual reference: physical PDF page 116. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Flip-flop 1 Reset Delay [6415]

The RESET input signal for Flip-flop 1 is delayed with the

set value in this menu.

Flip-flop 1 Timer Value [6416]

This menu shows the actual value of the flip-flop 1 timer.

Flip-flop 2 - 4 [642] - [644]

Refer to the descriptions for flip-flop 1. Default for

[6421]”F2 Mode” is “Reset”. For [6431]”F3 Mode” the

default is “Set”, and for [6441] “F4 Mode” the default is

“Edge”.

8.6.5

Counters [650]

The counter function counts pulses and can signal on a

selected output when the counter reaches a specified level.

The counter counts up on the positive edges of the trigger

signal, and it is zeroed when the reset signal is active.

When the counter value equals the trip value, the counter

output signal (CTR1 or CTR2) is activated. See Fig. 65.

Fig. 65 Counters, principle.

Counter 1 [651]

Counter 1 parameter group.

Counter 1 Trigger [6511]

The selected signal is used as a trigger signal for counter 1.

Counter 1 is incremented by 1 on every positive edge of the

trigger signal.

NOTE: Maximum counting frequency is 8 Hz.

CTR1

CTR1= Counter 1 output signal

6511= Counter 1 Trigger

6512= Counter 1 Reset

6513= Counter 1 Trip Value

6519= Counter 1 Value

651 Counter 1

Stp

Fig65 printed waveform labels6513threshold,6519count,6511trigger,6512reset,CTR1output. Legend literally6519=Counter1Value; next page displays6514. No reference corrected.

Parameter panel 6415 F1 Res Dly; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6416 F1 Tmr Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6511 C1 Trig; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6415 F1 Res Dly — PDF page 116

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Parameter panel 6511 C1 Trig — PDF page 116

Source row Label Value
1 Default: Off
2 Selection: Same selections as in menu Relay 1 [551],
page 97.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 117

Manual reference: physical PDF page 117. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Counter 1 Reset [6512]

The selected signal is used as a reset signal for counter 1.

When the reset signal is activated (high), this will zero

counter 1, and the counter will remain at zero as long as the

reset signal is active (high).

Counter 1 Trip Value [6513]

In this menu counter 1 is set to a trip value. When the

counter value equals the trip value, the counter 1 output

signal (CTR1) is activated (high).

Counter 1 Value [6514]

This menu shows the actual value of counter 1.

Counter 2 [652]

Refer to description for Counter 1 [651].

8.6.6

Clock Logic [660]

Clock 1 [661]

The actual value of clock 1 is viewed in this menu.

Clock 1 Time On [6611]

Time when the clock is activated.

Clock 1 Time Off [6612]

Time when the clock is deactivated.

Clock 1 Date On [6613]

Date when the clock is activated.

Clock 1 Date Off [6614]

Date when the clock is deactivated. Note that if

“Clk1DateOff” is set to an earlier date than “Clk1DateOn”,

the result will be that the clock is not deactivated at the set

date.

NOTE: Reset input has top priority.

NOTE: Value 0 means that counter output is always high.

NOTE: Counter 1 value is common for all parameter sets.

NOTE: The value is lost at power down.

Clock1 actual661 source body has separate Range label and0:00:00.0(hours:minutes:seconds) value; no numeric upperbound isprinted. Counter6514readonly;On/Off6611/6612 ranges are not rewritten.

Parameter panel Read-only 661 Clock 1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6512 C1 Reset; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6611 Clk1TimeOn; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6513 C1 Trip Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6612 Clk1TimeOff; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6613 Clk1DateOn; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6514 C1 Value; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6614 Clk1DateOff; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel Read-only 661 Clock 1 — PDF page 117

Source row Label Value
1 Range: 0:00:00.0 (hours:minutes:seconds)

Parameter panel 6512 C1 Reset — PDF page 117

Source row Label Value
1 Default: Off
2 Selection: Same selections as in menu Relay 1 [551],
page 97.

Parameter panel 6611 Clk1TimeOn — PDF page 117

Source row Label Value
1 Default: 0:00:00.0 (hours:minutes:seconds)
2 Range: 0:00:00.0–9:59:59.9

Parameter panel 6513 C1 Trip Val — PDF page 117

Source row Label Value
1 Default: 0
2 Range: 0 - 10,000

Parameter panel 6613 Clk1DateOn — PDF page 117

Source row Label Value
1 Default: 2013-01-01
2 Range: YYYY-MM-DD (year-month-day)

Parameter panel 6614 Clk1DateOff — PDF page 117

Source row Label Value
1 Default: 2013-01-01
2 Range: YYYY-MM-DD

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 118

Manual reference: physical PDF page 118. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Clock 1 Weekday [6615]

Weekdays when the clock function is active. Having entered

the editing mode, select or unselect the desired weekdays

with the cursor using the PREV and NEXT keys on the

control panel. Confirm by pressing ENTER. Exit the editing

mode and the activated weekdays will be viewed in the menu

display. The deactivated weekdays are replaced by a dash

mark “-” (e.g. “MTWTF - -”).

Clock 2 [662]

Refer to the description for Clock 1 [661].

8.7

Operation/Status [700]

Menu with parameters for viewing all actual operational data,

such as speed, torque, power, etc.

8.7.1

Operation values [710]

Process Value [711]

This menu displays the actual value of the active process

signal, i.e. the same value as in menu [310].

Torque [713]-[714]

This menu displays the actual shaft torque, expressed with

different units in the two menus:

Shaft power [715]- [716]

This menu displays the actual shaft power, expressed with

NOTE: Please make sure that the correct time and date

settings are done for the real time clock, menu group

[740] “Clock”.

6615 Default MTWTFSS(allactivated),Range Monday throughSunday. Deactivated weekdays use dash, e.g.MTWTF--.713 and715 units are absolute Nm/W;714 and716 arepercent.

Parameter panel 6615 Clk1Weekday; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 711 Process Val; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 713 Torque; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 714 Torque; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 715 Shaft Power; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 716 Shaft Power; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 6615 Clk1Weekday — PDF page 118

Source row Label Value
1 Default: MTWTFSS (all activated)
2 Range: Monday, Tuesday, Wednesday, Thursday,
Friday, Saturday, Sunday.

Parameter panel 711 Process Val — PDF page 118

Source row Label Value
1 Unit Depends on selected process unit [322].
2 Resolution Speed: 1 rpm, 4 digits
Other units: 3 digits

Parameter panel 713 Torque — PDF page 118

Source row Label Value
1 Unit: Nm
2 Resolution: 0.1 Nm

Parameter panel 714 Torque — PDF page 118

Source row Label Value
1 Unit: %
2 Resolution: 1 %

Parameter panel 715 Shaft Power — PDF page 118

Source row Label Value
1 Unit: W
2 Resolution: 1W

Parameter panel 716 Shaft Power — PDF page 118

Source row Label Value
1 Unit: %
2 Resolution: 1%

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 119

Manual reference: physical PDF page 119. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Electrical Power [717]

This menu displays the actual electrical output power.

RMS Current [718]

This menu displays the RMS value of the output current.

Line Main Voltage [719]

This menu displays the RMS value of the mains voltage.

Heatsink Temperature [71A]

This menu displays the actual measured heatsink

temperature.

PT100B1 123 [71B]

This menu displays the actual PT100 temperature for the

first PT100 option board (B1), corresponding to input 1, 2,

and 3. See menu PT100 Inputs [2323], page 64.

PT100B2 123 [71C]

second PT100 option board (B2), corresponding to input 4,

5, and 6. See menu PT100 Inputs [2323], page 64.

Current I1- I3 [71D]-[71F]

This menu displays the actual output current in the three

phases.

L12, L13 and L23 Voltage [71G]-[71I]

This menu displays the actual voltage.

Phase Sequence [71J]

This menu displays the phase sequence of the mains voltage.

Used Thermal Capacity [71K]

This menu displays the used thermal capacity.

PT100B2 123 LCD label belongs to secondboard71C;prose saysinputs4,5,6. PhaseSequence71J Range valuecell and descriptioncellsL123/L321 are blank; displayedL123 is example status.

Parameter panel 717 El Power; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 71C PT100B2 123; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 718 RMS Current; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 71D Current I1; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 719 L Main Volt; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 71G L12 Voltage; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 71A Heatsink Tmp; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 71J Phase Seq; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 71B PT100B1 123; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 71K Used Th Cap; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 717 El Power — PDF page 119

Source row Label Value
1 Unit: kW
2 Resolution: 1 W

Parameter panel 71C PT100B2 123 — PDF page 119

Source row Label Value
1 Unit: °C
2 Resolution: 1°C

Parameter panel 718 RMS Current — PDF page 119

Source row Label Value
1 Unit: A
2 Resolution: 0.1 A

Parameter panel 719 L Main Volt — PDF page 119

Source row Label Value
1 Unit: V
2 Resolution: 1 V

Parameter panel 71A Heatsink Tmp — PDF page 119

Source row Label Value
1 Unit: °C
2 Resolution: 0.1°C

Parameter panel 71J Phase Seq — PDF page 119

Source row Selection or label Communication code or merged label Description or default/range
1 Range: ⟦null: no independent source value⟧ ⟦blank source cell⟧
2 L - - - 0 Can not be detected.
3 L123 1 ⟦blank source cell⟧
4 L321 2 ⟦blank source cell⟧

Parameter panel 71K Used Th Cap — PDF page 119

Source row Label Value
1 Unit: %
2 Resolution: 1%

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 120

Manual reference: physical PDF page 120. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.7.2

Status [720]

TSA Status [721]

This menu indicates the overall status of the softstarter.

Fig. 66 Softstarter status

Integer values and bits used:

Example: “A/- - - /Key”

This means:

A:

Parameter Set A is active.

---:

Operation is stopped.

Key:

Run/Stop command source is both internal and

external keyboard (in this example bit 7-5 → 1).

Integer interpretation for “A/---/Key” is “0/0/1”.

In bit format this is presented as:

Warning [722]

This menu displays the actual or last warning condition. A

warning occurs if the softstarter is close to a trip condition

but still in operation. During a warning condition the red

trip LED will flash, as long as the warning is active.

The active warning message is displayed in menu [722]. If no

warning is active the message “No Error” is displayed.

The following warning or trip messages are possible:

Read-only

721 TSA Status

Stp

1/222/333

Warning

(warning message)

Figure66 bit-number columns7,6,5,4,3,2,1,0LSB hold0,0,1,0,0,0,0,0. Group7–5Key(1),4–2stopped(0),1–0A(0). Mergedgroupcells retained without copying values into blank/null placeholders.

Figure66 bit-format example; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

TSA721 status display positions; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

TSA721 status bit assignments; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Figure66 bit-format example — PDF page 120

Source row 7 6 5 4 3 2 1 0 LSB
1 0 0 1 0 0 0 0 0
2 Key (1) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ - - - (0) ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ A (0) ⟦null: no independent source value⟧
3 Source of Run/Stop
command =
Int + Ext keyboard (1)
⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Operation =
Stopped (0)
⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Parameter Set=
A (0)
⟦null: no independent source value⟧

TSA721 status display positions — PDF page 120

Source row Display
position
Function Status value
1 1 Parameter Set A, B, C, D
2 222 Operation - - - (stopped)
-Thy (ramp/brake with
thyristors)
-Bpy (full speed reached,
running with bypass enabled)
3 333 Source of Run/
Stop command
-Rem (remote)
-Key (keyboard - external or
internal or both)
-Com (communication option)

TSA721 status bit assignments — PDF page 120

Source row Bit Integer representation
1 1 - 0 Active Parameter Set, where:
0=A, 1=B, 2=C, 3=D.
2 4 - 2 Operation:
0=Stopped
1=Thyristor driven motor
2=Bypass driven motor
3 7 - 5 Source of Run/Stop command, where:
0=Rem, 1=Keyboard (internal + external), 2=Com,
3=Spare, 4=VIO, 5=Internal keyboard, 6=External
keyboard.
4 15 - 8 Reserved for future use.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 121

Manual reference: physical PDF page 121. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Digital Input Status [723]

This menu indicates the status of the digital inputs. See

example in Fig. 67.

DigIn 1

DigIn 2

DigIn 3

DigIn 4

The positions 1 - 4 (on the display, from left to right) indicate

the status of the associated input (DigIn 1 - DigIn 4):

High

Low

The example in Fig. 67 indicates that DigIn 2 and DigIn 4

are active at this moment.

Fig. 67 Digital input status example

Relay Status [724]

This menu indicates the status of the relays. See Fig. 68.

RE indicates the status of the relays on position:

Relay1

Relay2

Relay3

The status of the associated output is shown.

The example in Fig. 68 indicates that Relay 1 is active. Relay

2 and Relay 3 are not active.

Fig. 68 Relay status example

Analogue Input Status [725]

This menu indicates the status of the analogue input.

Fig. 69 Analogue input status example

The status of the input is shown in [%], so the example in

Fig. 69 indicates that AnIn is active and has a 65% input

value.

Table 32

Trip and warning messages

Read-only

NOTE: The shown percentage is an absolute value based

on the maximum value of the in- or output; so related to

either to 10 V or 20 mA.

723 DigIn Status

Stp

724 RelayStatus

RE 100

725 AnalogueIn

65%

Figures67–69 show723DigInStatus0101,724RelayStatusRE100,725AnalogueIn65%. Read-only examples, notdefaultsettings.

Table32 trip and warning messages; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table32 trip and warning messages — PDF page 121

Source row Communication
integer value
Trip / warning message
1 0 No Error
2 1 Motor I²t
3 2 PTC
4 3 Locked rotor
5 4 Ext Alarm 1
6 5 Ext Alarm 2
7 6 Curr limit (current limit)
8 7 Start limit
9 8 Comm error (communication error)
10 9 Pt100
11 10 Bypass open
12 11 BypassClosed
13 12 Mon MaxAlarm (load monitor max alarm)
14 13 Mon MaxPreAl (load monitor max pre-
alarm)
15 14 Mon MinPreAl (load monitor min pre-
alarm)
16 15 Mon MinAlarm (load monitor min alarm)
17 16 Over temp (over temperature)
18 17 Thyr open (thyristor open)
19 18 Thyr short (thyristor short)
20 19 Phase loss (single phase loss)
21 20 M Phase loss (multiple phase loss)
22 21 Under voltag (undervoltage)
23 22 Mot termOpen (motor terminal open)
24 23 Current Unbal (current unbalance)
25 24 CtrlSupFault (control voltage supply
fault)
26 25 Spare25 (reserved for future use)
27 26 Int error1 (internal error 1)
28 27 Phase rev (phase reversal)
29 28 Spare28 (reserved for future use)
30 29 Int error2 (internal error 2)
31 30 Over voltag (overvoltage)
32 31 Volt Unbal (voltage unbalance)

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 122

Manual reference: physical PDF page 122. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Analogue Output Status [726]

This menu indicates the status of the analogue output. Fig.

70.

Fig. 70 Analogue output status example

The status of the output is shown in [%], so the example in

Fig. 70 indicates that AnOut is active and has a 65% output

value.

If 4-20 mA output is used for example, the value 20% equals

4 mA.

I/O Board Status B1 - B2 [727] - [728]

This menu indicates the status for the additional I/O on

option boards 1 (B1) and 2 (B2).

Fig. 71 I/O board status example

Analogue comparator status 1 - 4 [72A]

This menu indicates the active analogue comparators (CA1 -

CA4).

Digital comparator status 1 - 4 [72B]

This menu indicates the active digital comparators (CD1 -

CD4).

Logic function status 1 - 4 [72C]

This menu indicates the active logic outputs (L1 - L4).

Timer status 1- 4 [72D]

This menu indicates the active timers (T1Q - T4Q).

SR Flip-flop status 1 - 4 [72E]

This menu indicates the active flip-flops (F1 - F4).

Counter status 1 - 2 [72F]

This menu indicates the active counters (CTR1 - CTR2).

Time to next start [72G]

This menu indicates the time left to the next allowed start if

at least one of the choices under menu [235] Start Limitation

is activated (i.e. number of starts per hour or minimum time

between starts.

Read-only

NOTE: The shown percentage is an absolute value based

on the maximum value of the in- or output, so related to

either to 10 V or 20 mA.

726 AnalogueOut

Stp

65%

728 IO StatusB2

RE 000 DI100

72A CA1-4

72B CD1-4

72C Logic 1-4

72D Timer 1-4

72E FlipFlop1-4

72F Counter 1-2

72G TtoNxtStart

0Min

Figure70AnalogueOut65%;Figure71IOStatusB2RE000DI100. StatusLCDs72A/72B/72C/72D/72E0000;72F00;72G0Min. Read-onlyexamples.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 123

Manual reference: physical PDF page 123. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.7.3

Stored Values [730]

The shown values are the actual values built up over time.

Values are stored at power down and updated again at power

up.

Run Time [731]

This menu displays the total time that the softstarter has been

in the run mode.

Reset Run Time [7311]

This menu resets the run time counter. The stored

information will be erased and a new registration period will

start.

Mains time [732]

connected to the mains supply. This timer cannot be reset.

Energy [733]

This menu displays the total energy consumption since the

last energy reset [7331] took place.

Reset Energy [7331]

This menu resets the energy counter. The stored information

will be erased and a new registration period will start.

8.7.4

Real time clock settings [740]

This menu group displays information on actual time and

date. The menus are quickly accessed from the default toggle

loop. See Fig. 24, page 36.

Time [741]

Actual time, displayed as HH:MM:SS. Adjustable setting.

Date [742]

Actual date, displayed as YYYY-MM-DD. Adjustable setting.

Weekday [743]

Display of actual weekday.

NOTE: After reset the setting automatically reverts to

“No”.

Unit:

hh:mm:ss (hours: minutes: seconds)

YYYY-MM-DD (year-month-day)

Read-only

741 Time

Stp

00:00:00

742 Date


743 Weekday

Monday

741TimeLCD00:00:00 andUnit hh:mm:ss;742DateLCD--- andUnitYYYY-MM-DD;743WeekdayLCDMonday,readonly. These single-bodyrow boxes are preserved in native text context.

Parameter panel 7331 Rst Energy; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 731 Run Time; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 7311 Reset RunTm; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 732 Mains Time; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 733 Energy; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 7331 Rst Energy — PDF page 123

Source row Label Value
1 Default: No
2 Selection: No, Yes

Parameter panel 731 Run Time — PDF page 123

Source row Label Value
1 Unit: h: mm:ss (hours: minutes: seconds)
2 Range: 00: 00: 00–262143: 59: 59

Parameter panel 7311 Reset RunTm — PDF page 123

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No
2 No 0 ⟦blank source cell⟧
3 Yes 1 ⟦blank source cell⟧

Parameter panel 732 Mains Time — PDF page 123

Source row Label Value
1 Unit: hh: mm:ss (hours: minutes: seconds)
2 Range: 00: 00: 00–262143: 59: 59

Parameter panel 733 Energy — PDF page 123

Source row Label Value
1 Unit: Wh (shows Wh, kWh, MWh or GWh)
2 Range: 0 Wh–999,999 GWh

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 124

Manual reference: physical PDF page 124. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.8

View Trip Log [800]

Main menu with parameters for viewing all the logged trip

data. In total the softstarter saves the last 9 trips in the trip

memory. The trip memory refreshes on the FIFO principle

(First In, First Out). Every trip in the memory is logged on

the time of the Run Time [731] counter. At every trip, the

actual values of several parameters are stored and available for

troubleshooting.

See section 7.3.1, page 45 for an explanation of the different

alarm types.

8.8.1

Trip Message Log [810]

The trip log displays the cause of the trip and what time it

occurred (based on the actual time in [740]). The display is

showing actual trip message and alternates between showing

date and time when the trip occured.

See a list of the possible trip messages in Table 32, page 117.

When a trip occurs the operation and status menus [710] and

[720]are copied to the trip message log. There are nine trip

message logs [810]–[890]. When the tenth trip occurs the

oldest trip message will be erased.

Example:

The display is showing actual trip message and alternates

between showing date and time when the trip occurred

For fieldbus integer value of trip message, see Table 32, page

117 (menu [722]).

Trip message [8111]-[8133]

The information from the status menus are copied to the trip

message log when a trip occurs.

NOTE: After the reset of a trip, the trip message will be

removed and menu [100] will appear.

830 Locked Rotor

Trp

09:12:14

2013-04-17

Table 33

Stored trip message parameters

Tripdisplayexample830LockedRotor alternates09:12:14 and2013-04-17. Table33 sectionheaderrows separateOperation710 andStatus720; table continues125.

Table33 trip-message mappings first page; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 8x0 Trip Message; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table33 trip-message mappings first page — PDF page 124

Source row Trip menu Copied from Description
1 ⟦blank source cell⟧ 8.7.1 Operation values [710] ⟦null: no independent source value⟧
2 8111 711 Process Value
3 8113 713 Torque (Nm)
4 8114 714 Torque (%)
5 8115 715 Shaft Power (W)
6 8116 716 Shaft Power (%)
7 8117 717 El Power
8 8118 718 RMS Current
9 8119 719 L Main Volt
10 811A 71A Heatsink Temp
11 811B 71B PT100B1 123
12 811C 71C PT100B2 123
13 811D 71D Current I1
14 811E 71E Current I2
15 811F 71F Current I3
16 811G 71G L12 Voltage
17 811H 71H L13 Voltage
18 811I 71I L23 Voltage
19 811J 71J Phase Seq
20 811K 71K Used Thermal Cap
21 ⟦blank source cell⟧ 8.7.2 Status [720] ⟦null: no independent source value⟧
22 8121 721 TSA Status
23 8122 723 Digital input status
24 8123 724 Relay status
25 8124 725 Analogue input status
26 8125 726 Analogue output status
27 8126 727 I/O status option board B1
28 8127 728 I/O status option board B2
29 8129 72A Analogue comparator 1 - 4
30 812A 72B Digital comparator 1 - 4
31 812B 72C Logic function status 1-4
32 812C 72D Timer status 1-4
33 812D 72E Flip-flop status 1-4
34 812E 72F Counter status 1-2

Parameter panel 8x0 Trip Message — PDF page 124

Source row Label Value
1 Unit:
Alternating
hh:mm:ss (hours: minutes: seconds)
YYYY-MM-DD (year-month-day)

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 125

Manual reference: physical PDF page 125. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

8.8.2

Trip Messages [820] - [890]

Same information as for menu [810].

8.8.3

Reset Trip Log [8A0]

This menu resets the content of the 10 trip memories.

8.9

System Data [900]

Main menu for viewing all the softstarter system data.

8.9.1

TSA Data [920]

TSA Type [921]

This menu shows the Emotron TSA type according to the

type code. The options are indicated on the product label of

the softstarter. See section 1.4, page 5.

Fig. 72 Type number example.

Example:

TSA-series suited for 525 V mains supply, and a rated output

current of 16 A.

Software [922]

This menu shows the software version number of the

softstarter. Fig. 73 gives an example.

Fig. 73 Software version example.

NOTE: After the reset the setting goes automatically

back to “NO”. The message “OK” is displayed for 2 sec.

Table 33

Stored trip message parameters

NOTE: If the control board is not configured, then type

shown is TSA52-XXX.

Table 34

Information for Modbus and Profibus number,

software version

Table 35

option version

TSA

Stp

TSA52-016

922 Software

V1.00

Table34 release-type codes0Vrelease,1Ppre-release,2βBeta,3αAlpha. Table35 minoroption07 andmajor03 retain leadingzeros. These areexamples, notinstalledfirmware evidence.

Table33 trip-message mappings continued; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Shared source cells (coordinates refer to this table):

Parameter panel 8A0 Reset Trip L; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table34 software version fieldbus bits; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table35 option version fieldbus bits; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Table33 trip-message mappings continued — PDF page 125

Source row Trip menu Copied from Description
1 812F 72G Time to next start
2 ⟦blank source cell⟧ 8.7.3 Stored Values [730] ⟦null: no independent source value⟧
3 8131 731 Run time
4 8132 732 Mains time

Parameter panel 8A0 Reset Trip L — PDF page 125

Source row Selection or label Communication code or merged label Description or default/range
1 Default: ⟦null: no independent source value⟧ No
2 No 0 ⟦blank source cell⟧
3 Yes 1 ⟦blank source cell⟧

Table34 software version fieldbus bits — PDF page 125

Source row Bit Example Description
1 7–0 30 Minor version
2 13–8 4 Major version
3 15–14 0 Release type:
0: V, release version
1: P, pre-release version
2: β, Beta version
3: α, Alpha version

Table35 option version fieldbus bits — PDF page 125

Source row Bit Example Description
1 7–0 07 Minor option version
2 15–8 03 Major option version

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 126

Manual reference: physical PDF page 126. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Build Info [9221]

Unit Name [923]

Option to enter a name of the unit for service use or

customer identity. The function enables the user to define a

name with max 12 characters. Press the + / - keys to enter

graphic symbols from the same list as for User-defined Unit

[323], page 76. See also "Editing parameter values", page 35.

NOTE: It is important that the software version displayed

in menu [922] is the same software version number as

the software version number written on the title page of

this instruction manual. If not, the functionality as

described in this manual may differ from the

functionality of the softstarter.

Parameter panel 9221 Build Info; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 923 USER 15; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter panel 9221 Build Info — PDF page 126

Source row Label Value
1 Default: YY:MM:DD:HH:MM:SS

Parameter panel 923 USER 15 — PDF page 126

Source row Label Value
1 Default: No characters shown

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 127

Manual reference: physical PDF page 127. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

9.

Serial communication

The softstarter provides the possibility of different types of

serial communication.

•

Modbus RTU via RS232, RS485, USB and BT

Fieldbuses such as Profibus DP and DeviceNet

Industrial Ethernet such as Modbus/TCP, Profinet IO

and EtherCAT

See “12. Options” on page 137 for available communication

option boards.

9.1

Modbus RTU

There is an asynchronous unisolated RS232 serial

communication interface on top of the Emotron TSA unit.

It is also possible to use the isolated RS485 or USB option

boards (if installed).

The protocol used for data exchange is based on the Modbus

RTU protocol, originally developed by Modicon. The

softstarter acts as a slave with address 1 in a master-slave

configuration. The communication is half-duplex. It has a

standard non return zero (NRZ) format.

The baud rate is fixed to 9600 with fixed address = 1

(on-board RS232 port), but it is adjustable for the USB and

RS485 option boards.

The character frame format (always 11 bits) has:

one start bit

eight data bits

two stop bits

no parity

It is possible to temporarily connect a personal computer

with for example the software EmoSoftCom (programming

and monitoring software) to the RS232 connector on top of

the Emotron TSA unit. This can be useful when copying

parameters between softstarters, etc. For permanent

connection of a personal computer you have to use one of

the communication option boards RS485 or USB.

9.2

Parameter sets

Communication information for the different parameter

sets.

The different parameter sets in the softstarter have the

following DeviceNet instance numbers, Profibus slot/index

numbers, Profinet IO index and EtherCAT index numbers:

Parameter set A contains parameters 43001 to 43899. The

parameter sets B, C and D contain the same type of

information. For example parameter 43123 in parameter set

A contains the same type of information as 44123 in

parameter set B.

NOTE: This RS232 port is not galvanically isolated.

WARNING!

Correct and safe use of a RS232 connection

depends on the ground pins of both ports

having the same potential. Problems can

occur when connecting two ports of e.g. machinery and

computers where both ground pins have not the same

potential. This may cause hazardous ground loops that

can destroy the RS232 ports.

The on-board RS232 connection is not galvanically

isolated.

The RS485 and USB option boards from CG Drives &

Automation are galvanically isolated.

Note that the on-board RS232 connection can safely be

used in combination with commercially available

isolated USB to RS232 converters.

Fivecolumn parameter-set table retains Param.set /Modbus-DeviceNetInstance/ProfibusSlot-Index/ProfinetIOindex/EtherCAThex. C endpoint5706 is visiblyprinted; no calculation substituted.

Parameter set communication address mappings; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Parameter set communication address mappings — PDF page 127

Source row Param.
set
Modbus/
DeviceNet
Instance
number
Profibus
Slot/Index
Profinet IO
index
EtherCAT
index
(hex)
1 A 43001–
43899
168/160 to
172/38
19385 -
20283
4bb9 - 4f3b
2 B 44001–
44899
172/140 to
176/18
20385 -
21283
4fa1 - 5323
3 C 45001–
45899
176/120 to
179/253
21385 -
22283
5389 - 5706
4 D 46001–
46899
180/100 to
183/233
22385 -
23283
5771 - 5af3

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 128

Manual reference: physical PDF page 128. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

9.3

Motor data

Communication information for the different motors.

M1 contains parameters 43041 to 43048. The M2, M3, and

M4 contain the same type of information. For example

parameter 43043 in motor M1 contains the same type of

information as 44043 in M2.

9.4

Start and stop commands

Set start and stop commands via serial communication.

Requires that menu [2151] Run/Stop Control is set to

“Com”.

9.5

Process value

It is also possible to send the Process value feedback

signal over a bus (e.g. from a process or temperature sensor).

Set menu “Process Source [321 ]” to F(Bus). Use following

parameter data for the process value:

Communication information

MotorM2Profibuscell visibly172/180 to174/187. Processvalueencodingtable beginsDefault0; communicationtable beginsModbus/DeviceNet42906. Both firstrowsaredata, notheaders.

Motor data communication address mappings; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Process value feedback encoding; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Process value communication information; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Serial start stop commands; software1.0X editionR0. Display examples separate from defaults. Communication integers, units, merged/null cells and literal source wording retained; no inferred engineering validity.

Motor data communication address mappings — PDF page 128

Source row Motor Modbus/
DeviceNet
Instance
number
Profibus
Slot/
Index
Profinet IO
index
EtherCAT
index
(hex)
1 M1 43041–
43048
168/200
to
168/207
19425 -
19432
4be1 - 4be8
2 M2 44041–
44048
172/180
to
174/187
20425 -
20432
4fc9 - 4fd0
3 M3 45041–
45048
176/160
to
176/167
21425 -
21432
53b1 - 53b8
4 M4 46041–
46048
180/140
to
180/147
22425 -
22432
5799 - 57a0

Process value feedback encoding — PDF page 128

Source row Label Value
1 Default 0
2 Range -16384 to 16384
3 Corresponding to -100% to 100% process value

Process value communication information — PDF page 128

Source row Label Value
1 Modbus /DeviceNet Instance number 42906
2 Profibus slot /Index 168/65
3 Profinet IO index 19290
4 Fieldbus format Int
5 Modbus format Int

Serial start stop commands — PDF page 128

Source row Modbus/DeviceNet
Instance number
Function
1 42901 Reset
2 42902 Run, active together with either
Run FWD or Run REV to perform
start.
3 42903 Run FWD
4 42904 Run REV

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 129

Manual reference: physical PDF page 129. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

9.6

Description of the EInt

formats

A parameter with Eint format can be represented in two

different formats (F), either as a 15 bit unsigned integer

format (F= 0) or a Emotron floating point format (F=1).

The most significant bit (B15) indicates the format used.

See detailed description below.

All parameters written to a register may be rounded to the

number of significant digits used in the internal system.

The matrix below describes the contents of the 16-bit word

for the two different EInt formats:

If the format bit (B15) is 0, then all bits may be treated as a

standard unsigned integer (UInt).

If the format bit is 1, then the number is interpreted as:

Value = M * 10^E, where M=m10..m0 represents a

two- complement signed mantissa and E= e3..e0 represents a

two- complement signed exponent.

Example, resolution

If you write the value 1004 to a register and this register has

3 significant digits, it will be stored as 1000.

In the Emotron floating point format (F=1), one 16-bit

word is used to represent large (or very small numbers) with

3 significant digits.

If data is read or written as a fixed point (i.e. no decimals)

number between 0-32767, the 15 bit Unsigned integer

format (F=0) may be used.

Detailed description of Emotron floating point

format

A signed number should be represented as a two-

complement binary number, like below:

Value Binary

The value represented by the Emotron floating point format

is m·10e.

To convert a value from the Emotron floating point format

to a floating point value, use the formula above.

To convert a floating point value to the Emotron floating

point format, see the C-code example below.

Example, floating point format

The number 1.23 would be represented by this in Emotron

floating point format,

The value is then 123x10-2 = 1.23

Example 15bit unsigned integer format

The value 72.0 can be represented as the fixed point number

  1. It is within the range 0-32767, which means that the

15-bit fixed point format may be used.

The value will then be represented as:

Where bit 15 indicates that we are using the fixed point

format (F=0).

NOTE: Parameters with EInt format may return values

both as 15 bit unsigned integer (F=0) or in Emotron

floating point (F=1).

e3-e0 4-bit signed exponent. Gives a value

range:

-8..+7 (binary 1000 .. 0111)

m10-m0 11-bit signed mantissa. Gives a

value range:

-1024..+1023 (binary

10000000000..01111111111)

B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0

F=1 e3 e2 e1 e0 m10 m9 m8 m7 m6 m5 m4 m3 m2 m1 m0

F=0 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0

-8 1000

-7 1001

..

-2 1110

-1 1111

0 0000

1 0001

2 0010

6 0110

7 0111

F EEEE MMMMMMMMMMM

1 1110 00001111011

F=1 -> floating point format used

E=-2

M=123

0 0 0 0 0 0 0 0 0 1 0 0 1 0 0 0

Bit matrix F=1: B15F,B14e3,B13e2,B12e1,B11e0,B10m10 throughB0m0. F=0: B15F,B14..B0unsignedbits. Signedbinary examplepairs−8:1000,−7:1001,..,−2:1110,−1:1111,0:0000,1:0001,2:0010,..,6:0110,7:0111. Ellipsesretainomissions.1.23=123×10⁻²;72binary0000000001001000.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 130

Manual reference: physical PDF page 130. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Programming example:

typedef struct

{

int m:11; // mantissa, -1024..1023

int e: 4; // exponent -8..7

unsigned int f: 1; // format, 1->special emoint format

}

eint16;

//---------------------------------------------------------------------------

unsigned short int float_to_eint16(float value)

eint16 etmp;

int dec=0;

while (floor(value) != value && dec<16)

dec++; value*=10;

if (value>=0 && value<=32767 && dec==0)

(short int )&etmp=(short int)value;

else if (value>=-1000 && value<0 && dec==0)

etmp.e=0;

etmp.f=1;

etmp.m=(short int)value;

else

etmp.m=0;

etmp.e=-dec;

if (value>=0)

etmp.m=1; // Set sign

etmp.m=-1; // Set sign

value=fabs(value);

while (value>1000)

etmp.e++; // increase exponent

value=value/10;

value+=0.5; // round

etmp.m=etmp.m*value; // make signed

return ((unsigned short int )&etmp);

float eint16_to_float(unsigned short int value)

float f;

eint16 evalue;

evalue=(eint16 )&value;

if (evalue.f)

if (evalue.e>=0)

f=(int)evalue.m*pow10(evalue.e);

f=(int)evalue.m/pow10(abs(evalue.e));

f=value;

return f;

Rendered firstfunction return statement is lowercase return ((unsigned short int )&etmp);. NativeRreturn retained as raw, not propagated as codevalue. Code is supplier example only, notexecuted.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 131

Manual reference: physical PDF page 131. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

10.

Softstarter theory

In this chapter different starting methods for induction

motors are explained and compared. The functionality of

softstarters with torque control and their advantages and

limitations compared to other starting methods are

explained.

First a brief account of the background theory of starting

induction motors will be given in section 10.1. Thereafter

the different starting methods based on the usage of reduced

voltage will be described and compared. This chapter will

also cover softstarters with torque control. In section 10.3,

some common starting methods based on other physical

principles are explained. With this information some

limitations of the reduced voltage starters will become clear.

In section 10.4 there is a brief analysis of which applications

may benefit from using a softstarter.

10.1 Background theory

The following two sections deal with motors with squirrel-

cage rotors. In contrast to a wound rotor, the squirrel-cage

rotor consists of straight conductors, which are short-

circuited together at both ends.

When such a motor is connected directly to the line voltage

it will typically draw a starting current of about 5 to 8 times

its nominal current while the resulting starting torque will

be about 0.5 to 1.5 times its nominal torque. In the

following picture a typical starting characteristic is shown.

The x-axis represents the speed relative to the synchronous

speed while the y-axis shows the torque and the current

respectively, with those quantities normalised to their

nominal values. The dashed line indicates the nominal

values.

Fig. 74 Typical torque characteristics for the DOL start

Fig. 75 Typical current characteristics for the DOL start

For many industrial applications direct on-line starting is

not convenient, as the supply in this case has to be

dimensioned to deliver the unnecessarily high starting

current. Moreover, most applications do not gain anything

from the high starting torque. Instead there is a risk of

mechanical wear or even damage because of the resulting

jerk at speedup.

The acceleration torque is determined by the difference

between motor and load torque. The figure below shows

some typical torque characteristics for constant speed

applications. For comparative purposes, the induction

motors’ torque characteristic is added to the diagram.

Fig. 76 Typical load torque characteristics

0,5

1,5

2,5

Torque

T/Tn

n/ns

Current

I/In

Fig74torqueverticalT/Tn0,0.5,1,1.5,2,2.5;Fig75currentI/In0–8integersteps;bothhorizontaln/ns0,0.5,1. Fig76usesT/Tn sameaxiswithloadcurves;no curvevalues digitized.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 132

Manual reference: physical PDF page 132. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Typical applications with constant load are elevators, cranes

and conveyors. Linear load characteristics are typical for

calender rollers and various smoothing machines, whereas

quadratic correlation between speed and torque is typical for

pumps and fans. Some applications like conveyors or screws

may need an initial torque boost. However, for many

applications it can be seen that the torque needed is much

lower than the torque delivered by the induction motor in a

DOL start.

A common method to reduce both starting torque and

current is to decrease the motor voltage during starting. The

following figure shows how the motor’s torque and current

characteristics are changed when the supply voltage is

reduced.

Fig. 77 Reduced voltage start

A general rule of thumb is that the torque at each operating

point is roughly proportional to the square of the current.

This means when the motor current is decreased by a factor

of two by means of reducing the supply voltage, the torque

delivered by the motor will be decreased by a factor of four

(approximately).

This relationship is the base for any starting method using

reduced voltage. It can be seen that the possibility of

reducing the starting current depends on the correlation

between the motor’s and the load’s torque characteristic. For

the combination of an application with very low starting

load and a motor with very high starting torque, the starting

current may be reduced significantly by means of decreasing

the voltage during start. However, for applications with high

starting load it may – depending on the actual motor – not

be possible to reduce the starting current at all.

10.2 Reduced voltage starting

This section describes different starting methods which are

based on the reduced-voltage principle explained above. A

pump and its quadratic torque characteristic are used as an

example.

The star-delta starter is the simplest example of a reduced

voltage starter. The motor phases are first star connected; at

about 75% of nominal speed the phase connection is then

changed to delta. To enable star-delta start, both ends of all

three motor windings have to be available for connection.

Moreover, the motor has to be dimensioned for the (higher)

voltage in the delta connection. The following figure shows

the resulting torque and current characteristics.

0,5

1,5

2,5

Torque

T/Tn

n/ns

Current

I/In

Un

U2<Un

U3<U2

T ~ I 2

ILV = 1/2 IDOL → TLV ≈ 1/4 TDOL

ILV = 1/3 IDOL → TLV ≈ 1/9 TDOL

LV=low voltage

DOL=Direct on line

Fig77 pairedT/Tn0–2.5halfsteps andI/In0–8integersteps versusn/ns0,0.5,1;curve labelsUn,U2<Un,U3<U2. Formula T~I²; I_LV=1/2 I_DOL→T_LV≈1/4 T_DOL;1/3→1/9. LVlowvoltage,DOLdirectonline.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 133

Manual reference: physical PDF page 133. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 78 Star-delta start

The disadvantage of the star-delta start is that it cannot be

adapted to a special application. Both the voltage in star and

in delta connections are defined by the supply, and the

resulting starting performance depends on the motor’s DOL

characteristic. For some applications the star-delta starter

cannot be used as the resulting torque in a star connection is

too low to start rotating the load. On the other hand for low

load applications further savings of starting current are

impossible even though a big torque reserve is available.

Moreover, the resulting abrupt rise of torque first at start and

later when changing from star to delta connection may

contribute to mechanical wear. The high transient currents

during start-delta transition create unnecessary excess heat in

the motor.

Better performance is achieved with a voltage ramp start,

which a simple electronic softstarter can provide. The

voltage is increased linearly from an initial value to the full

supply voltage by means of phase angle control. The

resulting torque and current characteristics are shown in the

following figure.

Fig. 79 Soft starting – voltage ramp

Obviously a much smoother start is realised compared to the

star-delta start and the starting current is decreased.

A softstarter is often used to keep the starting current below

a desired level. For the example above, setting a current limit

of three times the nominal current may be desirable. The

following figure shows the resulting torque and current

characteristics.

0,5

I/In

n/ns

1,5

2,5

Torque

T/Tn

Current

Fig78star-deltastart(left) and79softstartingvoltage-ramp(right): torqueT/Tn0–2.5halfsteps/currentI/In0–8integersteps vsn/ns0,0.5,1. Curvesillustrative, unlabelledtracegeometryremainsPDF.

Manual — P036; functionality, serial communications and starting theory. Model/option and software edition conditions retained. Supplier instructions not engineering approval. — page 134

Manual reference: physical PDF page 134. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 80 Soft starting – voltage ramp with current limit

Once again the figure illustrates that the resulting

performance depends on the combination of motor and load

characteristics. In the example above the motor torque is

close to the load torque at about half speed. This means for

some other applications with different load characteristics

(for example a linear torque-speed correlation) this

particular motor would need more than three times the

nominal current to start.

The most sophisticated electronic softstarters use torque

control, which results in an almost constant acceleration

during the start. A low starting current is also achieved.

However, this start method also uses reduced motor voltage

and the quadratic correlation between current and torque

described in the first section of this chapter is still valid. This

means, the lowest possible starting current is determined by

the combination of motor and load characteristics.

Fig. 81 Soft starting – torque control

For optimal starting performance, correct setting of the

softstarter’s parameters such as initial torque and end torque

at start and start time is important. The choice of parameters

is explained in detail in section 8.3.3, page 78.

10.3 Other starting methods

In contrast to the preceding sections of this chapter, which

focused on squirrel-cage motors, slip-ring motors are dealt

with later on. A slip-ring motor is equipped with a wound

rotor; one end of each rotor winding is available for external

connection via slip-rings. These motors are often optimised

for rotor resistance starting, i.e. with short-circuited rotor

windings they develop a very low torque at an extremely

high current. For starting, external resistances are connected

to the rotor windings. During the start, the resistance value

is decreased in several steps until the rotor windings are

short-circuited at nominal speed. The following figure

shows typical torque and current characteristics for a slip-

ring motor during the start with an external rotor-resistance

starter.

0,5

1,5

2,5

I/In

n/ns

Torque

T/Tn

Current

Fig80softstartingvoltage-rampwithcurrentlimit(left) and81torquecontrol(right);sameT/Tn0–2.5/I/In0–8,n/ns0,0.5,1axes. Currentlimitexamplelineat3; not productmaximum. Slip-ring illustration referred to is onnextpage135.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 135

Manual reference: physical PDF page 135. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Fig. 82 Rotor-resistance starting

Because of the low starting torque it is often not possible to

short-circuit the rotor windings and replace the rotor-

resistance starter with a softstarter. However, it is always

possible to use a frequency inverter instead. The following

illustration shows how the torque and current characteristics

are affected when the stator frequency is changed.

Fig. 83 Voltage/frequency regulation

Thus, such a motor can be started with a quite simple

frequency inverter with voltage-frequency regulation. This

solution is also valid for all other applications, which for

some reason (high load torque compared to motor torque

etc.) cannot be started by a softstarter.

0,5

1,5

2,5

I/In

n/ns

Torque

T/Tn

Current

f3<f2

f2<fn

fn

Figures82/83: torque T/Tn axis0,0.5,1,1.5,2,2.5; current I/In axis0–8integer; speed n/ns0,0.5,1. Fig83 shows f3<f2, f2<fn, fn. Qualitative curves; no interpolated values.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 136

Manual reference: physical PDF page 136. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

10.4 Use of softstarters with

torque control

To determine if a specific application benefits from using a

softstarter at all, the correlation between the motor’s torque

characteristic during the start and the load’s requirements

has to be evaluated. As it can be seen from the examples

above, the application will only benefit from using a

softstarter if the load torque during the start is clearly below

the motor’s starting capacity. However, loads with a high

initial release torque may also benefit from a softstarter. In

this case an initial torque boost can be used, thereafter the

start ramp is continued reducing the starting current

considerably.

The benefit can be maximised when using a softstarter with

torque control. To be able to configure the torque control

parameters for optimal performance, the load characteristics

(linear, square or constant load, need of initial release

torque) must be known. In this case a proper torque control

method (linear or square) can be chosen and torque boost

can be enabled if needed.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 137

Manual reference: physical PDF page 137. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.

Troubleshooting, Diagnoses and Maintenance

For a description of the different alarm states, see “Alarm

indications” on page 45.

11.1 Trip conditions, causes and

remedial action

The table later on in this section must be seen as a basic aid

to find the cause of a system failure and how to solve any

problems that arise. Although the softstarter gives a certain

trip message it is not always easy to find the right cause of

the failure. Good knowledge of the complete system is

therefore necessary. Contact your supplier if you have any

questions.

The softstarter is designed in such a way that it tries to avoid

trips by limiting torque, overvoltage etc.

Failures occurring during commissioning or shortly after

commissioning are most likely to be caused by incorrect

settings or even bad connections.

Failures or problems occurring after a reasonable period of

failure-free operation can be caused by changes in the system

or in its environment (e.g. wear).

Failures that occur regularly for no obvious reasons are

generally caused by electromagnetic interference. Be sure

that the installation fulfils the demands for installation

stipulated in the EMC directives. See section 1.5.1, page 6.

Sometimes the so-called “Trial and error” method is a

quicker way to determine the cause of the failure. This can

be done at any level, from changing settings and functions to

disconnecting single control cables or replacing entire units.

The “Trip Message Log” [800] can be useful for determining

why certain trips recur at certain moments. The trip log

records the time of the trip in relation to the run time

counter. Under each trip message the values of a number of

parameters are saved. See Table 33, page 120.

11.1.1Technically qualified personnel

Installation, commissioning, demounting, making

measurements, etc., of or at the softstarter may only be

carried out by personnel technically qualified for the task.

11.1.2Opening the softstarter

The connections for the control signals and the switches are

isolated from the mains voltage. Always take adequate

precautions before opening the softstarter.

11.2 Maintenance

The Emotron TSA softstarter is designed to require a

minimum of servicing and maintenance. There are however

some things which must be checked regularly:

For model size 2 and up there is an internal fan that should

be inspected and cleaned from dust if necessary.

If softstarters are built into cabinets, also check and clean the

dust filters of the cabinets regularly.

Check external wiring, connections and control signals.

Tighten terminal screws if necessary. For more information

on maintenance, please contact your CG Drives &

Automation service partner.

Precautions to take with a connected motor

If work must be carried out on a connected motor or on the

driven machine, the mains voltage must always first be

disconnected from the softstarter.

WARNING!

If it is necessary to open the softstarter or

any part of the system (motor cable housing,

conduits, electrical panels, cabinets, etc.) in

order to inspect or take measurements as suggested in

this instruction manual, it is absolutely necessary to

read and follow the safety instructions in the manual.

Always switch off the mains and control

supply voltage if it is necessary to open the

softstarter.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 138

Manual reference: physical PDF page 138. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

11.3 Troubleshooting list

Table 36

Alarms with possible causes and remedies.

Table36 alarm troubleshooting; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Shared source cells (coordinates refer to this table):

Table36 alarm troubleshooting — PDF page 138

Source row Trip/warning message Alarm action Menu Possible cause Remedy
1 Bypass closed Hard trip ⟦blank source cell⟧ Bypass contactor is permanently
shortcircuited .
Service needed. Contact your local Emotron TSA supplier.
2 Bypass open Hard trip ⟦blank source cell⟧ Bypass contactor or its control is
malfunctioning.
Service needed. Contact your local Emotron TSA supplier.
3 Comm error No action
Hard trip
Soft trip
Warning
2641 Error on serial communication/
Fieldbus (option).
Check cables and connection of the serial communication.
Check all settings with regard to the communication.
Restart the equipment including the softstarter. For
details, see Fieldbus Manual.
4 CP locked! ⟦blank source cell⟧ ⟦blank source cell⟧ Control panel is locked for
settings.
Unlock control panel in menu [218]. Enter unlock code
“291”.
5 CtrlSupFault Hard trip ⟦blank source cell⟧ Control voltage supply fault. Check control supply voltage level.
6 Curr limit No action
Hard trip
Soft trip
Warning
236 Current limit parameters are
perhaps not matched to the load
and motor.
Increase the start time (menu [336]) and/or the current
limit at start (menu [335]).
7 Curr Unbal ⟦blank source cell⟧ ⟦blank source cell⟧ Bypass or thyristor fault Service needed. Contact your local Emotron TSA supplier.
8 Ext Alarm 1 No action
Hard trip
Soft trip
Warning
4211 External trip connected to digital
input active:
active low function on the input.
Check the equipment that initiates the external input.
Check the programming of the digital inputs, menu [520].
9 Ext Alarm 2 No action
Hard trip
Soft trip
Warning
4212 External trip connected to digital
input active:
active low function on the input.
Check the equipment that initiates the external input.
Check the programming of the digital inputs, menu [520].
10 Int phase loss ⟦blank source cell⟧ ⟦blank source cell⟧ Internal phase loss. Service needed. Contact your local Emotron TSA supplier.
11 Internal alarm Hard trip ⟦blank source cell⟧ ⟦blank source cell⟧ Service needed. Contact your local Emotron TSA supplier.
12 Locked rotor No action
Hard trip
Soft trip
Warning
422 Torque limit at motor standstill:
Mechanical blocking of the rotor.
Check for mechanical problems at the motor or the
machinery connected to the motor.
Set [4221] Locked rotor alarm to “No action”. Adjust
Locked Rotor time [4222] and Locked Rotor Current
[4223]
13 Mon MaxAlarm No action
Hard trip
Soft trip
Warning
⟦blank source cell⟧ Max alarm level (overload) has
been reached [4112].
Check the load condition of the machine.
Check the monitor setting in section 8.4, page 84.
14 Mon MaxPreAl No action
Hard trip
Soft trip
Warning
⟦blank source cell⟧ Max pre-alarm level (overload) has
been reached [4122].
⟦null: no independent source value⟧
15 Mon MinAlarm No action
Hard trip
Soft trip
Warning
⟦blank source cell⟧ Min alarm level (underload) has
been reached [4142].
⟦null: no independent source value⟧
16 Mon MinPreAl No action
Hard trip
Soft trip
Warning
⟦blank source cell⟧ Min pre-alarm level (underload)
has been reached [4132].
⟦null: no independent source value⟧
17 Motor I2t
(Area D: I2t)
No action
Hard trip
Soft trip
Warning
2311 I2t value is exceeded.
Overload on the motor according
to the prog-rammed I2t settings.
Check for mechanical overload on the motor or the
machinery (bearings, gearboxes, chains, belts, etc.).
Change the Motor I2t Current setting in menu [2312]

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 139

Manual reference: physical PDF page 139. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Table 36

Alarms with possible causes and remedies.

Table36 alarm troubleshooting; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Table36 alarm troubleshooting — PDF page 139

Source row Trip/warning message Alarm action Menu Possible cause Remedy
1 Motor term
open (motor
terminal open)
Hard trip ⟦blank source cell⟧ Open motor contact, cable or
motor winding.
Check wiring between softstarter and motor.
Initiate a restart. If the alarm appears again, contact your
local Emotron TSA supplier.
2 Mul phase loss ⟦blank source cell⟧ ⟦blank source cell⟧ 2 or 3 phases lost in mains supply
voltage.
Check fuses and mains supply.
3 Over temp Hard trip ⟦blank source cell⟧ Heatsink temperature too high:
Too high ambient temperature of
the softstarter.
Insufficient cooling.
Too high current.
Blocked or stuffed fans.
Check the cooling of the softstarter cabinet.
Check the functionality of the built-in fans. The fans must
switch on automatically if the heatsink temperature gets
too high. At power up the fans are briefly switched on.
Check softstarter and motor rating.
Clean fans.
4 Over voltage No action
Hard trip
Soft trip
Warning
4321 Too high 3-phase mains supply
voltage.
Check the 3-phase main supply voltage.
Remove the interference cause or use other main supply
lines.
5 Phase loss No action
Hard trip
Soft trip
Warning
235 Single phase loss.
Fuse broken.
Check fuses and mains supply.
Check that terminal screws are tightened.
6 Phase rev No action
Hard trip
Soft trip
Warning
4341 Incorrect phase sequence on 3-
phase main supply.
Swap L2 and L3 input phases.
7 PT100 No action
Hard trip
Soft trip
Warning
2321 Motor PT100 elements exceeds
maximum level.
NOTE: Only valid if option board
PTC/PT100 is used.
Check on mechanical overload on the motor or the
machinery (bearings, gearboxes, chains, belts, etc.).
Check the motor cooling system.
Self-cooled motor at low speed, too high load. Set alarm
action to “Off”.
8 PTC No action
Hard trip
Soft trip
Warning
2331 Motor thermistor (PTC) exceeds
maximum level.
If motor overheated, wait for it to cool down. Check on
mechanical overload on the motor or the machinery
(bearings, gearboxes, chains, belts, etc.)
Check the motor cooling system.
Self-cooled motor at low speed, too high load.
Set alarm action to “No action”.
9 Start limit No action
Hard trip
Soft trip
Warning
2341 Number of starts per hour
exceeded, min time between
starts not kept.
Wait and start again.
Perhaps the number of starts per hour could be decreased
in menu [2342] or the min time between starts could be
increased (menu [2343]).
10 Stop first! ⟦blank source cell⟧ ⟦blank source cell⟧ During start, stop and jog,
changing parameters is not
permitted.
Set parameters during standstill.
11 Thyristor open Hard trip ⟦blank source cell⟧ Damaged thyristor or control
wiring.
Service needed. Contact your local Emotron TSA supplier.
12 Thyristor short Hard trip ⟦blank source cell⟧ Damaged thyristor. Service needed. Contact your local Emotron TSA supplier.
13 Under voltage No action
Hard trip
Soft trip
Warning
4331 Too low 3-phase mains supply
voltage.
Mains voltage dip due to starting
other major power consuming
machines on the same line.
Make sure all three phases are properly connected and
that the terminal screws are tightened.
Check that the 3-phase mains supply voltage is within the
limits set in menu group [433].
Use other mains supply lines if dip is caused by other
machinery.
14 Volt unbalance No action
Hard trip
Soft trip
Warning
4311 Mains supply voltage unbalance. Check 3-phase mains supply.
Check settings in menu [4312] and [4313].

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 140

Manual reference: physical PDF page 140. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Troubleshooting matrix; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Shared source cells (coordinates refer to this table):

Troubleshooting matrix — PDF page 140

Source row Observation Fault indication Cause Solution
1 The display is not
illuminated.
None No control supply voltage. Switch on the control supply voltage.
2 Softstarter does not
react to start
command
- - - - Start command comes perhaps
from incorrect control source. (I.e.
start from control panel when
remote control is selected).
Give start command from correct
control source as configured in menu
[2151] and [2152].
3 The motor jerks etc. When starting, motor reaches
full speed but it jerks or
vibrates.
If “Torque control” is selected, it is
necessary to input motor data into
the system.
Configure nominal motor data in
menu group [220]. Select the proper
torque control alternative in menu
[331] (linear or square) according to
the load characteristic.
Select a correct initial- and end
torque at start in menus [332] and
[333].
4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Start time too short. Increase start time [336].
5 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ If voltage control is used as start
method, the initial voltage at start
may be too low. Starting voltage
incorrectly set.
Adjust initial voltage at start [334].
6 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Motor too small in relation to rated
current of softstarter.
Use a smaller model of the
softstarter.
7 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Motor too large in relation to load
of softstarter.
Use larger model of softstarter.
8 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Starting voltage not set
correctly.
Readjust the start ramp.
9 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Select the current limit function.
10 ⟦null: no independent source value⟧ Starting or stopping time too
long.
Ramp times not set correctly. Readjust the start and/or stop ramp
time.
11 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Motor too large or too small in
relation to load.
Change to another motor size.
12 The monitor function
does not work.
No or false alarm or pre-alarm. It is necessary to input nominal
motor data for this function. Set
alarm levels not valid.
Input nominal motor data in menus
[221]-[228]. Adjust alarm levels and
response delays.
13 The alarm can not
be reset.
⟦blank source cell⟧ ⟦blank source cell⟧ Check reset control in menu [216].
The alarm can only be reset if the
alarm condition is removed.
e.g. PTC, PT100 or heatsink
temperature alarm can only be reset
after the temperature is decreased.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 141

Manual reference: physical PDF page 141. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

12.

Options

The available standard options are briefly described here.

Some of the options have their own instruction or

installation manual. For more information please contact

your supplier.

12.1

External control panel

These options may be useful, for example for mounting

control panel in a cabinet door (Fig. 84). Maximum distance

between softstarter and external control panel is 3 metres.

Fig. 84 External control panel in mounting cassette.

12.2

EmoSoftCom

EmoSoftCom is an optional software that runs on a personal

computer. It can also be used to load parameter settings

from the softstarter to the PC for backup and printing.

Recording can be made in oscilloscope mode. Please contact

CG Drives & Automation sales for further information.

12.3

I/O Board

Each I/O option board 2.0 provides three extra relay outputs

and three extra isolated digital inputs (24V). This option is

described in a separate manual. Maximum two option

boards can be mounted (I/O or PTC/PT100)

12.4

PTC/PT100

The PTC/PT100 2.0 option board for connecting motor

thermistors and max 3 PT100 elements to the softstarter is

12.5

Serial communication

and fieldbus

For communication with the softstarter there are several

option modules. There are different options for Fieldbus

communication and one serial communication option with

RS485 interface which has galvanic isolation. These options

are described in a separate manual.

NOTE: Emotron TSA softstarters have as standard

coated control boards and coated option boards.

RITTAL

Softstarter

cabinet

Fig84: softstarter cabinet and external control panel in mounting cassette. Connection illustration only; dimensions not inferred.

Options part numbers; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Options part numbers — PDF page 141

Source row Part number Description
1 01-3876-51 I/O option board 2.0

Options part numbers — PDF page 141

Source row Part number Description
1 01-5406-00 Panel kit complete including panel

Options part numbers — PDF page 141

Source row Part number Description
1 01-3876-58 PTC/PT100 2.0 option board

Options part numbers — PDF page 141

Source row Part number Description
1 01-5385-54 TSA Isolated RS485 module
2 01-5385-55 TSA Profibus module
3 01-5385-56 TSA DeviceNet module
4 01-5385-59 TSA Modbus/TCP module
5 01-5385-60 TSA EtherCAT module
6 01-5385-61
01-5385-62
TSA Profinet IO 1-port module
TSA Profinet IO 2-port module
7 01-5385-63 TSA Isolated USB module

Manual reference: physical PDF page 142. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Bodyblank; onlysection/page/document footer present. Reviewedtext: 138 | Options | CG Drives & Automation 01-5980-01r00 No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 143

Manual reference: physical PDF page 143. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.

Technical data

1)

Normal duty: Start current = 3 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour,

Heavy duty: Start current = 5 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour.

2) Fuse data for Semi-conductor fuses, see Table 41.

3) H1=Height of enclosure, H2= Total height.

Table 37

Table 38

Table37 model and duty ratings; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Shared source cells (coordinates refer to this table):

Table38 model and duty ratings; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Table37 model and duty ratings — PDF page 143

Source row Parameter / units TSA52-016 — Normal TSA52-016 — Heavy TSA52-022 — Normal TSA52-022 — Heavy TSA52-030 — Normal TSA52-030 — Heavy
1 Rated current I [A]
n_soft
16 10 22 12 30 18
2 Motor size P 400 V [kW]
n_mot
7.5 4 11 5.5 15 7.5
3 Motor size P 460 V [hp]
n_mot
10 5 15 7.5 20 10
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 Recommended load fuses [A](2) 20 20 25 25 35 35
6 Power loss at rated motor power,
bypass mode [W]
20 20 20 20 20 20
7 Average power loss if 10 starts/hour [W] 20 21 21 22 21 23
8 Power consumption control supply [VA] 20 20 20 20 20 20
9 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 Dimensions H1/H2 x W x D [mm](3) 246/296 x 126 x 188 ⟦null: no independent source value⟧ 246/296 x 126 x 188 ⟦null: no independent source value⟧ 246/296 x 126 x 188 ⟦null: no independent source value⟧
11 Mounting position Vertical ⟦null: no independent source value⟧ Vertical ⟦null: no independent source value⟧ Vertical ⟦null: no independent source value⟧
12 Weight [kg] 5.5 ⟦null: no independent source value⟧ 5.5 ⟦null: no independent source value⟧ 5.5 ⟦null: no independent source value⟧
13 Busbar connection [mm] 15 x 4, Cu (M6) ⟦null: no independent source value⟧ 15 x 4, Cu (M6) ⟦null: no independent source value⟧ 15 x 4, Cu (M6) ⟦null: no independent source value⟧
14 Cooling system Convection ⟦null: no independent source value⟧ Convection ⟦null: no independent source value⟧ Convection ⟦null: no independent source value⟧
15 Protection class IP20 ⟦null: no independent source value⟧ IP20 ⟦null: no independent source value⟧ IP20 ⟦null: no independent source value⟧

Table38 model and duty ratings — PDF page 143

Source row Parameter / units TSA52-036 — Normal TSA52-036 — Heavy TSA52-042 — Normal TSA52-042 — Heavy TSA52-056 — Normal TSA52-056 — Heavy
1 Rated current I [A]
n_soft
36 21 42 25 56 33
2 Motor size P 400 V [kW]
n_mot
18.5 7.5 22 11 30 15
3 Motor size P 460 V [hp]
n_mot
25 15 30 20 40 25
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 Recommended load fuses [A](2) 40 40 50 50 63 63
6 Power loss at rated motor power,
bypass mode [W]
20 20 20 20 20 20
7 Average power loss if 10 starts/hour [W] 22 24 22 26 23 27
8 Power consumption control supply [VA] 20 20 20 20 20 20
9 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 Dimensions H1/H2 x W x D [mm](3) 246/296 x 126 x 188 ⟦null: no independent source value⟧ 246/296 x 126 x 188 ⟦null: no independent source value⟧ 246/296 x 126 x 188 ⟦null: no independent source value⟧
11 Mounting position Vertical ⟦null: no independent source value⟧ Vertical ⟦null: no independent source value⟧ Vertical ⟦null: no independent source value⟧
12 Weight [kg] 5.5 ⟦null: no independent source value⟧ 5.5 ⟦null: no independent source value⟧ 5.5 ⟦null: no independent source value⟧
13 Busbar connection [mm] 15 x 4, Cu (M6) ⟦null: no independent source value⟧ 15 x 4, Cu (M6) ⟦null: no independent source value⟧ 15 x 4, Cu (M6) ⟦null: no independent source value⟧
14 Cooling system Convection ⟦null: no independent source value⟧ Convection ⟦null: no independent source value⟧ Convection ⟦null: no independent source value⟧
15 Protection class IP20 ⟦null: no independent source value⟧ IP20 ⟦null: no independent source value⟧ IP20 ⟦null: no independent source value⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 144

Manual reference: physical PDF page 144. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

1)

Normal duty: Start current = 3 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour,

Heavy duty: Start current = 5 x In_soft , Start time = 15 s (Size 1) or 30 s (Size 2-6), 10 starts/hour.

2) Fuse data for Semi-conductor fuses, see Table 41.

3) H1=Height of enclosure, H2= Total height.

Table 39

Table39 model and duty ratings; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Shared source cells (coordinates refer to this table):

Table39 model and duty ratings — PDF page 144

Source row Parameter / units TSA52-070 — Normal TSA52-070 — Heavy TSA52-085 — Normal TSA52-085 — Heavy TSA52-100 — Normal TSA52-100 — Heavy
1 Rated current I [A]
n_soft
70 42 85 51 100 60
2 Motor size P 400 V [kW]
n_mot
37 22 45 22 55 30
3 Motor size P 460 V [hp]
n_mot
50 30 60 40 75 40
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 Recommended load fuses [A](2) 80 80 80 80 100 100
6 Power loss at rated motor power,
bypass mode [W]
25 25 25 25 25 25
7 Average power loss if 10 starts/hour [W] 33 44 37 51 38 55
8 Power consumption control supply [VA] 25 25 25 25 25 25
9 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 Dimensions H1/H2 x W x D [mm](3) 246/296 x 126 x 188 ⟦null: no independent source value⟧ 246/296 x 126 x 188 ⟦null: no independent source value⟧ 246/296 x 126 x 188 ⟦null: no independent source value⟧
11 Mounting position Vertical/Horizontal ⟦null: no independent source value⟧ Vertical/Horizontal ⟦null: no independent source value⟧ Vertical/Horizontal ⟦null: no independent source value⟧
12 Weight [kg] 5.7 ⟦null: no independent source value⟧ 5.7 ⟦null: no independent source value⟧ 5.7 ⟦null: no independent source value⟧
13 Busbar connection [mm] 15 x 4, Cu (M6) ⟦null: no independent source value⟧ 15 x 4, Cu (M6) ⟦null: no independent source value⟧ 15 x 4, Cu (M6) ⟦null: no independent source value⟧
14 Cooling system Fan ⟦null: no independent source value⟧ Fan ⟦null: no independent source value⟧ Fan ⟦null: no independent source value⟧
15 Protection class IP20 ⟦null: no independent source value⟧ IP20 ⟦null: no independent source value⟧ IP20 ⟦null: no independent source value⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 145

Manual reference: physical PDF page 145. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.1 General electrical specifications

13.2 Semi-conductor fuses

Always use standard commercial fuses to protect the wiring

and prevent short circuiting. To protect the thyristors

against short-circuit currents, superfast semiconductor fuses

can be used if preferred.

Use fuses with I2t values lower or equal to Table 41.

Table 40

Parameter

Description

General

Control signal inputs

Control signal outputs

Control signal supply

Table 41

Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Technical data source table — PDF page 145

Source row Parameter Description
1 Mains supply voltage 200-525 V, +10%/-15%
200-690 V, +10%/-15%
2 Mains and Control supply frequency 50/60 Hz, ±10%
3 Number of fully controlled phases 3
4 Control supply voltage 100-240 V +10%/-15%, Single phase
5 Recommended fuse for control supply Max 10 A

Technical data source table — PDF page 145

Source row Parameter Description
1 Digital input voltage 0-4 V->0, 8 -27 V->1
2 Digital input impedance to GND (0 VDC) <3.3 VDC: 4.7 kΩ
≥3.3 VDC: 3.6 kΩ
3 Analogue input voltage/current 0-10 V, 2-10 V, 0-20 mA, 4-20 mA
4 Analogue input impedance to GND (0 VDC) Voltage signal 20 kΩ, Current signal 250 Ω

Technical data source table — PDF page 145

Source row Parameter Description
1 Output relays contact 8 A, 250 VAC or 24 VDC resistive load; 3 A, 250 VAC inductive load
2 Analogue output voltage/current 0-10 V, 2-10 V, 0-20 mA, 4-20 mA
3 Analogue output load impedance Voltage signal min. load 700 Ω, current signal max. load 500 ΩΩ

Technical data source table — PDF page 145

Source row Parameter Description
1 +24 VDC +24 VDC+5%. Max current 50 mA. Short circuit and overload proof.

Technical data source table — PDF page 145

Source row TSA model Semiconductor fuse A I²t fuse at 700 V
1 -016 50 1,500
2 -022 70 2,800
3 -030 100 3,600
4 -036 125 6,900
5 -042 150 11,000
6 -056 175 14,000
7 -070 250 42,000
8 -085 300 55,000
9 -100 400 99,000

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 146

Manual reference: physical PDF page 146. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.3 Environmental conditions

13.3.1Derating at high temperature

The Emotron TSA softstarter is made for operating at

maximum 40°C ambient temperature without derating.

Above this temperature it is necessary to ensure that

insufficient cooling does not impair the performance of the

softstarter, therefore a derating is done.

At temperatures of above 40°C, the derating of the nominal

current is 2% per centigrade. The Emotron TSA softstarter

can be operated at an ambient temperature of up to 55°C, in

which case it can only be operated at 70% of the nominal

current.

Example:

A motor with the following data is going to be used in an

ambient temperature of 50°C:

Voltage: 400 V

Current: 70 A (normal duty)

Power: 37 kW

Due to the high temperature the TSA model 52-070 will no

longer be adequate for the purpose.

Derating 2%/°C is calculated for a temperature of 10°C

above the rated:

10°C x 2% = 20%

Hence the nominal current must be derated by 20%.

To select a model that is adapted to the derating demands,

the next higher rated model is checked, TSA52-085, rated

for 85 A nominal current:

85 A - (20% x 85 A) = 68 A, which is lower than the

required 70 A.

An even higher rated model is checked, TSA52-100, rated

for 100 A nominal current:

100 A - (20% x 100 A) = 80 A, which is well above the

required 70 A, and therefore TSA52-100 is the model to be

selected in this case.

WARNING!

To resist temperatures above 40°C, the clock

battery (see 3.2, page 14) must be changed

to a BR2032 type battery.

Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Normal operation

Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Storage

Shared source cells (coordinates refer to this table):

Technical data source table — PDF page 146

Source row Condition Specification
1 Ambient temperature 0°C to 40°C
(Max 55°C by derating 2%/°C in excess of 40°C, see 13.3.1).
2 Atmospheric pressure 86 - 106 kPa
3 Relative humidity Max 95%, non-condensing
4 Altitude Max 1,000 m
(Max 4,000 m by derating 1%/100 m in excess of 1,000 m; with I/O board max 2,000 m, see 13.3.2).
5 Vibrations According to IEC 60721-3-3:
Mechanical conditions, class 3M4 (2 - 9 Hz, 3.0 mm and 9 - 20 Hz, acc. 1 g (10 m/s2))
6 Contamination According to IEC 60721-3-3:
Chemically active substances, class 3C3 (conformal coating - all printed circuit boards are coated)
Mechanically active substances, class 3S1 (no sand; dust <0.01 mg/m3, deposited <0.4 mg/(m2*h))
Biological conditions, class 3B1 (no risk for harmful biological attacks - mould, fungus, animals, etc)
7 Storage ⟦null: no independent source value⟧
8 Ambient temperature -25°C to +70°C
9 Atmospheric pressure 86 - 106 kPa
10 Relative humidity Max 95%, non-condensing

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 147

Manual reference: physical PDF page 147. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.3.2Derating at high altitude

The Emotron TSA softstarter can operate at an altitude up

to 1,000 m without derating.

Above 1,000 m the thinner air will have several negative

effects on the performance of the softstarter, therefore a

derating is done.

For elevations in excess of 1,000 m, the derating of the

nominal current is 1% per 100 m. The Emotron TSA

softstarter can be operated up to 4,000 m, in which case it

can only be operated at 70% of the nominal current it was

originally constructed for.

Example:

A motor with the following data is going to be used at

2,100 m altitude:

Voltage: 400 V

Current: 42 A (normal duty)

Power: 22 kW

Due to the high altitude the TSA model 52-042 will no

longer be adequate for the purpose.

The derating 1%/100 m is calculated for the altitude above

the rated:

2,100 - 1,000 = 1,100 meters above rated altitude, that

gives:

(1,100 m/100 m) x 1% = 11%

Hence the nominal current must be derated by 11%.

The next higher rated model, TSA52-056, rated for 56 A

nominal current, will be derated to:

56 A - (11% x 56 A) = 49.8 A, which is well above the

required 42 A, and therefore TSA52-056 could be selected

in this case.

NOTE: If the unit has an I/O board the maximum altitude

with derating is 2,000 m.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 148

Manual reference: physical PDF page 148. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

13.4 Control power- and I/O signal connectors

Table 42

Power board connections

Table 43

Control board connections

WARNING!

The same external supply voltage level (max

24 VDC or max 250 VAC) must be used for all

three output relays (terminals 21-33).

Do not mix AC and DC voltage.

Make sure to use the same voltage level within this

terminal section, otherwise the softstarter may be

damaged.

Technical data source table; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Shared source cells (coordinates refer to this table):

Technical data source table — PDF page 148

Source row Terminal Contact designation Function Electrical characteristics
1 PE ⟦blank source cell⟧ Protective Earth Protective grounding
2 N ⟦blank source cell⟧ Control supply voltage 100-240 VAC ±10%
3 L ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
4 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
5 21 NO Programmable relay 1. Factory setting is
“Operation” with indication by closing contact on
terminals 21 to 22.
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC
8 A resistive, 250 VAC, 3 A inductive. See Warning.
6 22 C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
7 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
8 23 NO Programmable relay 2. Factory setting is “Off” with
indication by closing contact on terminals 23 to 24.
1-pole closing contact (NO), 250 VAC 8 A or 24 VDC
8 A resistive, 250 VAC, 3 A inductive. See Warning.
9 24 C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
10 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
11 31 NO Programmable relay 3. Factory setting is “Trip”.
Indication by closing contact on terminals 31 to 33
and opening contact on 32 to 33.
1-pole change-over contact (NO/NC), 250 VAC 8A or
24 VDC 8A resistive, 250 VAC, 3A inductive. See
Warning.
12 32 C ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
13 33 NC ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
14 ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧
15 69-70 ⟦blank source cell⟧ PTC Thermistor input Alarm level 2.4 kΩ. Switch back level 2.2 kΩ.

Technical data source table — PDF page 148

Source row Terminal Contact designation Function Electrical characteristics
1 11 ⟦blank source cell⟧ Digital input 1. Factory setting is “Run FWD” 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec.
Impedance: <3.3 VDC: 4.7 kΩ. - ≥3.3 VDC: 3.6 kΩ
2 12 ⟦blank source cell⟧ Digital input 2. Factory setting is “Stop”. ⟦null: no independent source value⟧
3 13 ⟦blank source cell⟧ Control signal supply voltage to analogue input. +10 VDC ±5%. Max. current from +10 VDC: 10 mA.
Short circuit-proof and overload-proof.
4 14 ⟦blank source cell⟧ Analogue input, 0-10 V, 2-10 V, 0-20 mA and
4-20 mA/digital input. S1 jumper for U/I selection.
Impedance to terminal 15 (0 VDC) voltage signal:
20 kΩ, current signal: 250 Ω.
5 15 ⟦blank source cell⟧ GND (common) 0 VDC signal ground
6 16 ⟦blank source cell⟧ Digital input 3. Factory setting is “Set Ctrl 1” 0-4 V --> 0; 8-27 V--> 1. Max. 37 V for 10 sec.
Impedance: <3.3 VDC: 4.7 kΩ. - ≥3.3 VDC: 3.6 kΩ
7 17 ⟦blank source cell⟧ Digital input 4. Factory setting is “Reset” ⟦null: no independent source value⟧
8 18 ⟦blank source cell⟧ Control signal supply 1, voltage to digital input. +24 VDC ±5%. Max. current from +24 VDC = 50 mA.
Short circuit-proof and overload-proof.
9 19 ⟦blank source cell⟧ Analogue output. Factory setting is “Current”. Analogue output contact:
0-10 V, 2-10 V; min load impedance 700 Ω
0-20 mA and 4-20 mA; max load impedance 500 Ω
10 20 ⟦blank source cell⟧ Control signal supply 2, voltage to digital input. +24 VDC ±5%. Max. current from +24 VDC = 50 mA.
Short circuit-proof and overload-proof.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 149

Manual reference: physical PDF page 149. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Index

A

Abbreviations .....................................7

Aggressive environment conditions ..26

Alarm ...............................................45

Action ..45, 49, 63, 65, 84, 89, 90

Autoreset ..................................50

Autoset ...............................48, 87

Delay ........................................84

External ....................................88

Indication .................................45

Load monitor ...........................84

Mains .......................................89

Maximum ...........................84, 87

Minimum ...........................86, 87

Motor .......................................62

Over voltage .............................90

Phase reversal ............................91

PT100 ......................................63

PTC .........................................64

Reset .........................................50

Type .........................................45

Under voltage ...........................90

Ambient temperature below 0×C .....26

Analogue comparators ...................100

Analogue input ................................91

Configuration ...........................92

Status ......................................117

Analogue output ..............................95

Configuration ...........................96

Status ......................................118

AND operator ...............................105

Applications and functions selection 21

Autoreset ...................................52, 69

Autoset ................................48, 86, 87

B

Background theory ........................127

Bandsaw ..........................................25

Baudrate ..........................................74

Blower .............................................24

Brake ...............................................81

DC ...........................................82

Dynamic vector ........................81

Reversed current .......................81

Spinbrake .................................95

Brake chopper ................................137

Braking ............................................81

Busbar distances ...............................13

C

Cabinet mounting .............................9

CE-marking .......................................6

Centrifuge .......................................25

Checklist ..........................................29

Clock logic ....................................113

Clock settings ................................119

Clockwise rotary field ......................94

Coast ...............................................81

Com Type .......................................73

Comparator

Analogue .................................101

Digital ....................................104

Hysteresis type ........101, 102, 104

Window type ..........101, 102, 104

Comparators ..................................100

Compressor ......................................24

Connections .....................................11

Mains supply ............................29

Motor earth ..............................29

Motor output ............................29

Safety earth ...............................29

Virtual ......................................99

Control keys .....................................34

Control Panel memory .....................67

Control signals

Edge-controlled ........................60

Level-controlled ........................60

Conveyor .........................................24

Cooling ........................................9, 10

Counter-clockwise rotary field .........94

Counters ........................................112

Current ..........................................115

Current limit ....................................79

D

Date ...............................................119

DC brake .........................................82

Declaration of Conformity .................6

Default .............................................67

Definitions .........................................7

Derating

Altitude ...................................143

Temperature ...........................142

Derating at higher temperature ......142

Description ....................................127

Digital comparators ........................100

Digital inputs

Additional .................................95

Board Relay ..............................99

DigIn 1 .....................................94

DigIn 2 .....................................95

Dimensions ......................................10

Direct on-line, DOL ........................78

Dismantling and scrapping ................6

Display .............................................33

DOL ................................................78

Dynamic vector brake ................81, 82

E

Earth fault relay ................................27

ECP ...............................................137

Edge control ...............................52, 60

Electrical specifications ...................139

Emergency .........................................1

EN60204-1 ........................................6

EN61800-3 ........................................6

EN61800-5-1 .................................... 6

Enable ................................. 34, 51, 94

Energy consumption ..................... 119

ENTER key .................................... 34

Environmental conditions ............. 142

EtherCAT ..................................... 123

EXOR operator ............................. 105

Expression ..................................... 105

External Control Panel .................. 137

F

Factory settings .......................... 60, 67

Fan .................................................. 24

Fieldbus ........................... 73, 123, 137

Flip-flop

Status ..................................... 118

Flip-flops ....................................... 110

Function key ................................... 58

Function keys .................................. 34

Fuses and power losses ................... 141

G

General electrical specifications ..... 141

H

Hammer mill .................................. 25

Heatsink temperature .................... 115

Hole pattern .................................... 10

Hysteresis .............................. 100, 101

I

I/O Board ...................................... 137

I/O board status ............................ 118

I2t protection

Motor I2t Current ................... 63

Industrial Ethernet ........................ 123

Input

Logic .............................. 107, 108

Insulation test on motor .................. 26

IT earthing system ........................... 26

J

Jog ....................................... 40, 58, 83

JOG FWD key ......................... 34

JOG REV key .......................... 34

K

Keys ................................................ 34

L

Language ......................................... 57

LCD display .................................... 34

Level control ............................. 53, 60

Load default .................................... 67

Load monitor ............................ 46, 84

LOC/REM key ............................... 35

Local control ................................... 59

Logic ..................................... 100, 105

Low Voltage Directive ....................... 6

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 150

Manual reference: physical PDF page 150. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

M

Machine Directive .............................6

Mains supply ...................................29

Maintenance ..............................1, 136

Memory ...........................................42

Menu

100 ...........................................56

110 ...........................................57

234 ...........................................64

2341 .........................................64

2342 .........................................65

2343 .........................................65

235 ...........................................65

236 ...........................................66

Main menu ...............................37

Menu structure .........................37

Mixer ...............................................25

Modbus .........................................123

Modbus/TCP ........................123, 137

Monitor function

Auto set ....................................87

Motor ..........................................5, 57

Motor cos phi (power factor) ...........62

Motor data ..........................40, 42, 60

Motor poles .....................................62

Motor speed ....................................62

Motor ventilation ............................62

Mounting ..........................................9

Mounting schemes ...........................10

N

Nominal data ...................................61

Normal Load ...................................84

Normal load ....................................88

O

Operation ................................57, 114

Operation above 1000 m .................26

Options .........................................137

Brake chopper ........................137

External Control Panel (ECP) 137

I/O Board ...............................137

OR operator ..................................105

Over voltage ....................................90

P

Parameter sets ............................41, 66

Configuration ...........................42

Copy ........................................43

Copy settings ............................67

Default values ...........................67

DigIn .......................................95

Load settings .............................68

Motor .................................42, 60

PCB Terminals ........................15, 144

Phase compensation capacitor ............1

Phase loss .........................................65

Phase reversal ...................................91

Phase sequence .........................91, 115

Planer ..............................................24

Power- and signal connectors .........144

Product standard, EMC .....................6

Protection class ................................10

PT100 ..............................................64

PT100 temperature ........................115

PTC .................................................64

Q

Quick Setup Guide ............................5

R

Reduced voltage starting ................128

Relay output ....................................97

Relay 1 ......................................97

Relay 2 ......................................99

Relay 3 ......................................99

Status ......................................117

Remote control ................................51

Reset ................................................58

Resolution ........................................56

Reversed current brake ...............81, 82

Rock crusher ....................................25

Rotor ...............................................64

RS232/485 .......................................73

RUN ................................................34

Run command .................................34

Run time ........................................119

Running motors connected in

parallel .............................................26

Running motors linked together ......26

S

Safety .................................................1

Semi-conductor fuses .....................144

Service information ........................121

Set/reset delay ................................104

Shaft power ..............................47, 114

Shaft torque ...................................114

Shielded motor cable ........................26

Signal priority ..................................40

Small motor or low load ...................26

Soft trip ...........................................45

Softstarter rating ..............................21

Software .........................................121

Spare parts .........................................1

Special conditions ............................26

Spinbrake ...................................39, 95

SR Flip-flops ..................................110

Standards ...................................6, 144

Start limitation .................................64

Start right/left functionality ..............19

Start settings ....................................78

Starting with counter-clockwise

rotating loads ...................................26

Status .............................................116

Status indications .............................33

Step-up transformer for high

voltage motor ...................................26

Stop command .................................94

Stop settings .....................................80

STOP/RESET key ...........................34

T

Technical data ............................... 139

The Application Functions List ....... 23

Thermal capacity ............... 63, 69, 115

Thermal motor protection ... 33, 63, 69

Time ............................................. 119

Time to next start .......................... 118

Timer

logic ....................................... 109

status ...................................... 118

Toggle ............................................. 58

Toggle Key ...................................... 35

Torque

Actual ..................................... 114

Analogue output ...................... 95

Boost ........................................ 80

Braking .................................... 82

Control .............................. 78, 80

Initial ....................................... 78

Ramp ....................................... 78

Shaft ...................................... 114

Tightening ............................... 12

Units ........................................ 60

Torque control .............................. 132

Trip ........................................... 34, 45

Trip Message log ........................... 120

TSA Data ...................................... 121

Type code number ............................ 5

U

Unit ................................................ 76

Unit name ..................................... 122

Unlock Code ................................... 59

V

Ventilation ...................................... 62

Virtual I/O ...................................... 99

Voltage .......................................... 115

Voltage control .......................... 78, 81

Voltage unbalance ........................... 89

W

Warning .............................. 1, 45, 116

Weekday ....................................... 119

Weight ............................................ 10

Wireless connection ......................... 99

Wiring examples .............................. 16

Adjacent source context — repeated to preserve continuation:

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 151

Manual reference: physical PDF page 151. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1: Menu List

This is a list of the Emotron TSA menu parameters and their

factory settings, along with communication settings for the

most important bus formats.

Complete lists with communication data and parameter set

information could be downloaded from www. cgglobal.com

or www.emotron.com.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 100 StartWindow; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 110 1st Line; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 120 2nd Line; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 200 Main Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 210 Operation; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 211 Language; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 212 Select Motor; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 215 Action Ctrl; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 2151 Run/Stp Ctr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 2152 JogCtrl; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 215 Action Ctrl; displayed row association 216 Reset Ctrl; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 217 Key Func; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2171 FunctionKey; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2173 LocRunCtrl; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2174 FWD key; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 2175 REV key; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 218 Lock Code?; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 219 Rotation; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 21A Level/Edge; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 21C Units; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 220 Motor Data; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 221 Motor Volts; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 222 Motor Freq; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 223 Motor Power; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 224 Motor Curr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 225 Motor Speed; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 226 Motor Poles; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 227 Motor Cosφ; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 228 Motor Vent; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 217 Key Func; displayed row association 230 Mot Protect; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 231 Mot I²t Alrm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2311 Mot I²t AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2312 MotI²tCurr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2313 MotI²tClass; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 231 Mot I²t Alrm; displayed row association 2314 Used Th Cap; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 232 PT100 Alarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 2321 PT100 AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 2322 Motor Class; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 232 PT100 Alarm; displayed row association 2323 PT100Inputs; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 233 PTC Alarm; displayed row association 233 PTC Alarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 233 PTC Alarm; displayed row association 2331 PTC AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 233 PTC Alarm; displayed row association 2332 PTC Inputs; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Adjacent source context — repeated to preserve continuation:

Appendix 1 menu list — PDF page 151

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 100 StartWindow ⟦null: no independent source value⟧ 9999 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 56
2 110 1st Line El Power 43001 UInt UInt ⟦blank source cell⟧
3 120 2nd Line Current 43002 UInt UInt ⟦blank source cell⟧
4 200 Main Setup ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 57
5 210 Operation ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 57
6 211 Language English 43011 UInt UInt ⟦blank source cell⟧
7 212 Select Motor M1 43012 UInt UInt ⟦blank source cell⟧
8 215 Action Ctrl ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
9 2151 Run/Stp Ctr Remote 43015 UInt UInt ⟦blank source cell⟧
10 2152 JogCtrl Remote 43008 UInt UInt ⟦blank source cell⟧
11 216 Reset Ctrl Remote+Keyb 43016 UInt UInt ⟦blank source cell⟧
12 217 Key Func ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
13 2171 FunctionKey Toggle 43735 UInt UInt ⟦blank source cell⟧
14 2173 LocRunCtrl Keyboard 43010 UInt UInt ⟦blank source cell⟧
15 2174 FWD key FWD 43736 UInt UInt ⟦blank source cell⟧
16 2175 REV key Off 43737 UInt UInt ⟦blank source cell⟧
17 218 Lock Code? 0 43018 UInt, 1=1 UInt ⟦blank source cell⟧
18 219 Rotation FWD 43019 UInt UInt ⟦blank source cell⟧
19 21A Level/Edge Edge 43020 UInt UInt ⟦blank source cell⟧
20 21C Units SI 43750 UInt UInt ⟦blank source cell⟧
21 220 Motor Data ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 60
22 221 Motor Volts [Motor] V 43041 Long, 1=0.1V EInt ⟦blank source cell⟧
23 222 Motor Freq 50Hz 43042 Long, 1=1Hz EInt ⟦blank source cell⟧
24 223 Motor Power [Motor] W 43043 Long, 1=1W EInt ⟦blank source cell⟧
25 224 Motor Curr [Motor] A 43044 Long, 1=0.1A EInt ⟦blank source cell⟧
26 225 Motor Speed [Motor] rpm 43045 UInt, 1=1rpm UInt ⟦blank source cell⟧
27 226 Motor Poles [Motor] 43046 Long, 1=1 EInt ⟦blank source cell⟧
28 227 Motor Cosφ [Motor] 43047 Long, 1=0.01 EInt ⟦blank source cell⟧
29 228 Motor Vent Self 43048 UInt UInt ⟦blank source cell⟧
30 230 Mot Protect ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 62
31 231 Mot I²t Alrm ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
32 2311 Mot I²t AA Soft Trip 43061 UInt UInt ⟦blank source cell⟧
33 2312 MotI²tCurr 100% 43062 Long, 1=1% EInt ⟦blank source cell⟧
34 2313 MotI²tClass 10 43758 UInt UInt ⟦blank source cell⟧
35 2314 Used Th Cap ⟦blank source cell⟧ 31021 Long, 1=0.1% EInt ⟦blank source cell⟧
36 232 PT100 Alarm ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
37 2321 PT100 AA No action 43064 UInt UInt ⟦blank source cell⟧
38 2322 Motor Class F 140°C 43065 UInt UInt ⟦blank source cell⟧
39 2323 PT100Inputs PT100 1-3 43761 UInt UInt ⟦blank source cell⟧
40 233 PTC Alarm ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
41 2331 PTC AA No action 43762 UInt UInt ⟦blank source cell⟧
42 2332 PTC Inputs PbPTC 43763 UInt UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 152

Manual reference: physical PDF page 152. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 234 StartLimit; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2341 StartLim AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2342 Starts/h; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2343 MinTBtwStrt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 2344 TimTNxtStrt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 235 SnglPhLossAA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 236 CurrLim AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 240 Set Handling; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 241 Select Set; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 242 Copy Set; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 243 Default>Set; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 244 Copy to CP; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 245 Load from CP; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 234 StartLimit; displayed row association 250 Autoreset; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 251 AutorstAtt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2511 AllowedArst; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2512 ActualArst; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 252 MotProtArst; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2521 Motor I²t; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2522 PT100; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2523 PTC; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2524 LockedRotor; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 2525 Curr Lim; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 251 AutorstAtt; displayed row association 253 ComErrArst; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 254 ProcProtArst; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2541 MaxAlarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2542 MaxPAlarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2543 MinPAlarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2544 MinAlarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 2549 Ext Alarm 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 254 ProcProtArst; displayed row association 254A Ext Alarm 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 255 SoftStrtProt; displayed row association 255 SoftStrtProt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 255 SoftStrtProt; displayed row association 2551 Over temp; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 255 SoftStrtProt; displayed row association 2552 Start limit; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 256 MainsFailure; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2561 Phase input; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2562 Volt Unbal; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2563 OverVolt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 2564 Undervolt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 260 Serial Com; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 256 MainsFailure; displayed row association 261 Com Type; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 262 Modbus RTU; displayed row association 262 Modbus RTU; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 262 Modbus RTU; displayed row association 2621 Baudrate; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 262 Modbus RTU; displayed row association 2622 Address; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 263 Fieldbus; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2631 Address; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2632 PrData Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2633 Read/Write; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 263 Fieldbus; displayed row association 2634 AddPrValues; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 152

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 234 StartLimit ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
2 2341 StartLim AA No action 43751 UInt UInt ⟦blank source cell⟧
3 2342 Starts/h 10 43752 UInt, 1=1 UInt ⟦blank source cell⟧
4 2343 MinTBtwStrt Off 43753 UInt, 1=1min UInt ⟦blank source cell⟧
5 2344 TimTNxtStrt min 43754 UInt, 1=1min UInt ⟦blank source cell⟧
6 235 SnglPhLossAA Hard Trip 43755 UInt UInt ⟦blank source cell⟧
7 236 CurrLim AA Hard Trip 43756 UInt UInt ⟦blank source cell⟧
8 240 Set Handling ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 69
9 241 Select Set A 43022 UInt UInt ⟦blank source cell⟧
10 242 Copy Set A>B 43021 UInt UInt ⟦blank source cell⟧
11 243 Default>Set A 43023 UInt UInt ⟦blank source cell⟧
12 244 Copy to CP No Copy 43024 UInt UInt ⟦blank source cell⟧
13 245 Load from CP No Copy 43025 UInt UInt ⟦blank source cell⟧
14 250 Autoreset ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 69
15 251 AutorstAtt ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
16 2511 AllowedArst Off 43071 UInt, 1=1 UInt ⟦blank source cell⟧
17 2512 ActualArst 0 43069 UInt, 1=1 UInt ⟦blank source cell⟧
18 252 MotProtArst ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
19 2521 Motor I²t Off 43073 Long, 1=1s EInt ⟦blank source cell⟧
20 2522 PT100 Off 43078 Long, 1=1s EInt ⟦blank source cell⟧
21 2523 PTC Off 43084 Long, 1=1s EInt ⟦blank source cell⟧
22 2524 LockedRotor Off 43086 Long, 1=1s EInt ⟦blank source cell⟧
23 2525 Curr Lim Off 43772 Long, 1=1s EInt ⟦blank source cell⟧
24 253 ComErrArst Off 43089 Long, 1=1s EInt ⟦blank source cell⟧
25 254 ProcProtArst ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
26 2541 MaxAlarm Off 43093 Long, 1=1s EInt ⟦blank source cell⟧
27 2542 MaxPAlarm Off 43099 Long, 1=1s EInt ⟦blank source cell⟧
28 2543 MinPAlarm Off 43070 Long, 1=1s EInt ⟦blank source cell⟧
29 2544 MinAlarm Off 43091 Long, 1=1s EInt ⟦blank source cell⟧
30 2549 Ext Alarm 1 Off 43080 Long, 1=1s EInt ⟦blank source cell⟧
31 254A Ext Alarm 2 Off 43097 Long, 1=1s EInt ⟦blank source cell⟧
32 255 SoftStrtProt ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
33 2551 Over temp Off 43072 Long, 1=1s EInt ⟦blank source cell⟧
34 2552 Start limit Off 43771 Long, 1=1s EInt ⟦blank source cell⟧
35 256 MainsFailure ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
36 2561 Phase input Off 43773 Long, 1=1s EInt ⟦blank source cell⟧
37 2562 Volt Unbal Off 43096 Long, 1=1s EInt ⟦blank source cell⟧
38 2563 OverVolt Off 43077 Long, 1=1s EInt ⟦blank source cell⟧
39 2564 Undervolt Off 43088 Long, 1=1s EInt ⟦blank source cell⟧
40 260 Serial Com ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 73
41 261 Com Type RS232 43031 UInt UInt ⟦blank source cell⟧
42 262 Modbus RTU ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
43 2621 Baudrate 9600 43032 UInt UInt ⟦blank source cell⟧
44 2622 Address 1 43033 UInt, 1=1 UInt ⟦blank source cell⟧
45 263 Fieldbus ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
46 2631 Address 62 43034 UInt, 1=1 UInt ⟦blank source cell⟧
47 2632 PrData Mode Basic 43035 UInt UInt ⟦blank source cell⟧
48 2633 Read/Write RW 43036 UInt UInt ⟦blank source cell⟧
49 2634 AddPrValues 0 43039 UInt, 1=1 UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 153

Manual reference: physical PDF page 153. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 264 Com Fault; displayed row association 264 Com Fault; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 264 Com Fault; displayed row association 2641 ComFltAA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 264 Com Fault; displayed row association 2642 ComFlt Time; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 265 Ethernet; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2651 IP Address; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2652 MAC Address; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2653 Subnet Mask; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2654 Gateway; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 265 Ethernet; displayed row association 2655 DHCP; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266 FB Signal; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2661 FB Signal 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2662 FB Signal 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2663 FB Signal 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2664 FB Signal 4; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2665 FB Signal 5; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2666 FB Signal 6; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2667 FB Signal 7; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2668 FB Signal 8; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 2669 FB Signal 9; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266A FB Signal10; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266B FB Signal11; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266C FB Signal12; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266D FB Signal13; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266E FB Signal14; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266F FB Signal15; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 266 FB Signal; displayed row association 266G FB Signal16; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 269 FB Status; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2691 Board Type; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2692 SUP-bit; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2693 State FB; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2694 Serial Nbr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2695 FirmwareVer; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2696 CRC errors; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2697 MSG errors; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 269 FB Status; displayed row association 2698 TOUT ctr; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 153

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 264 Com Fault ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 74
2 2641 ComFltAA No action 43037 UInt UInt ⟦blank source cell⟧
3 2642 ComFlt Time 0,5s 43038 Long, 1=0.1s EInt ⟦blank source cell⟧
4 265 Ethernet ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 75
5 2651 IP Address 0.0.0.0 42701 UInt, 1=1 UInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42702 UInt, 1=1 UInt ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42703 UInt, 1=1 UInt ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42704 UInt, 1=1 UInt ⟦blank source cell⟧
9 2652 MAC Address 000000000000 42705 UInt, 1=1 UInt ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ 000000000000 42706 UInt, 1=1 UInt ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ 000000000000 42707 UInt, 1=1 UInt ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ 000000000000 42708 UInt, 1=1 UInt ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ 000000000000 42709 UInt, 1=1 UInt ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ 000000000000 42710 UInt, 1=1 UInt ⟦blank source cell⟧
15 2653 Subnet Mask 0.0.0.0 42711 UInt, 1=1 UInt ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42712 UInt, 1=1 UInt ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42713 UInt, 1=1 UInt ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42714 UInt, 1=1 UInt ⟦blank source cell⟧
19 2654 Gateway 0.0.0.0 42715 UInt, 1=1 UInt ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42716 UInt, 1=1 UInt ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42717 UInt, 1=1 UInt ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧ 0.0.0.0 42718 UInt, 1=1 UInt ⟦blank source cell⟧
23 2655 DHCP Off 42719 UInt UInt ⟦blank source cell⟧
24 266 FB Signal ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 75
25 2661 FB Signal 1 0 42801 UInt, 1=1 UInt ⟦blank source cell⟧
26 2662 FB Signal 2 0 42802 UInt, 1=1 UInt ⟦blank source cell⟧
27 2663 FB Signal 3 0 42803 UInt, 1=1 UInt ⟦blank source cell⟧
28 2664 FB Signal 4 0 42804 UInt, 1=1 UInt ⟦blank source cell⟧
29 2665 FB Signal 5 0 42805 UInt, 1=1 UInt ⟦blank source cell⟧
30 2666 FB Signal 6 0 42806 UInt, 1=1 UInt ⟦blank source cell⟧
31 2667 FB Signal 7 0 42807 UInt, 1=1 UInt ⟦blank source cell⟧
32 2668 FB Signal 8 0 42808 UInt, 1=1 UInt ⟦blank source cell⟧
33 2669 FB Signal 9 0 42809 UInt, 1=1 UInt ⟦blank source cell⟧
34 266A FB Signal10 0 42810 UInt, 1=1 UInt ⟦blank source cell⟧
35 266B FB Signal11 0 42811 UInt, 1=1 UInt ⟦blank source cell⟧
36 266C FB Signal12 0 42812 UInt, 1=1 UInt ⟦blank source cell⟧
37 266D FB Signal13 0 42813 UInt, 1=1 UInt ⟦blank source cell⟧
38 266E FB Signal14 0 42814 UInt, 1=1 UInt ⟦blank source cell⟧
39 266F FB Signal15 0 42815 UInt, 1=1 UInt ⟦blank source cell⟧
40 266G FB Signal16 0 42816 UInt, 1=1 UInt ⟦blank source cell⟧
41 269 FB Status ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 75
42 2691 Board Type ⟦blank source cell⟧ 31081 UInt, 1=1 UInt ⟦blank source cell⟧
43 2692 SUP-bit ⟦blank source cell⟧ 31082 UInt, 1=1 UInt ⟦blank source cell⟧
44 2693 State FB ⟦blank source cell⟧ 31083 UInt, 1=1 UInt ⟦blank source cell⟧
45 2694 Serial Nbr ⟦blank source cell⟧ 31084 UInt, 1=1 UInt ⟦blank source cell⟧
46 2695 FirmwareVer ⟦blank source cell⟧ 31085 UInt, 1=1 UInt ⟦blank source cell⟧
47 2696 CRC errors ⟦blank source cell⟧ 31086 UInt, 1=1 UInt ⟦blank source cell⟧
48 2697 MSG errors ⟦blank source cell⟧ 31087 UInt, 1=1 UInt ⟦blank source cell⟧
49 2698 TOUT ctr ⟦blank source cell⟧ 31088 UInt, 1=1 UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 154

Manual reference: physical PDF page 154. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 2699 FB Input; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 269A FB Output; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 269B Last instno; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 300 Process; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 310 ProcessValue; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 320 Proc Setting; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 321 Proc Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 322 Proc Unit; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 323 User Unit; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 324 Process Min; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 325 Process Max; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 330 StartSetting; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 331 Start Method; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 332 Init Torque; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 333 EndTorqueSt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 334 Init Volt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 335 Curr Limit; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 320 Proc Setting; displayed row association 336 Start Time; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 337 Torque Boost; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 3371 TB CurrLim; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 3372 TB Time; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 340 StopSetting; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 341 Stop Method; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 342 EndTorqueStp; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 343 StepDwnVolt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 344 BrakeMethod; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 345 Stop Time; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 346 RevC Brk Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 347 Brk Strength; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 348 DCB Strength; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 349 SwitchToDCB; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 34A DCBrkPhases; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 350 Jog; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 351 JogSpd FWD; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 352 JogSpd REV; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 337 Torque Boost; displayed row association 400 Monitor/Prot; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 410 Load Monitor; displayed row association 410 Load Monitor; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 411 Max Alarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 4111 MaxAlarmAct; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 4112 MaxAlarmLev; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 411 Max Alarm; displayed row association 4113 MaxAlarmDel; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 154

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 2699 FB Input ⟦blank source cell⟧ 31089 UInt, 1=1 UInt ⟦blank source cell⟧
2 269A FB Output ⟦blank source cell⟧ 31090 UInt, 1=1 UInt ⟦blank source cell⟧
3 269B Last instno ⟦blank source cell⟧ 31091 UInt, 1=1 UInt ⟦blank source cell⟧
4 300 Process ⟦null: no independent source value⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 76
5 310 ProcessValue ⟦blank source cell⟧ 31002 Long, 1= see
Notes
EInt 1=0.001, 1rpm, 1%, 1°C, 0.001
as set in [322]
6 320 Proc Setting ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
7 321 Proc Source Off 43302 UInt UInt ⟦blank source cell⟧
8 322 Proc Unit Off 43303 UInt UInt ⟦blank source cell⟧
9 323 User Unit 0 43304 UInt UInt ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43305 UInt UInt ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43306 UInt UInt ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43307 UInt UInt ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43308 UInt UInt ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43309 UInt UInt ⟦blank source cell⟧
15 324 Process Min 0 43310 Long, 1= see
Notes
EInt 1=0.001, 1rpm, 1%, 1°C, 0.001
as set in [322]
16 325 Process Max 10 43311 Long, 1= see
Notes
EInt 1=0.001, 1rpm, 1%, 1°C, 0.001
as set in [322]
17 330 StartSetting ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 78
18 331 Start Method Lin Torq Ctr 43701 UInt, 1=1 UInt ⟦blank source cell⟧
19 332 Init Torque 10% 43702 UInt, 1=1% UInt ⟦blank source cell⟧
20 333 EndTorqueSt 150% 43703 UInt, 1=1% UInt ⟦blank source cell⟧
21 334 Init Volt 30% 43704 UInt, 1=1% UInt ⟦blank source cell⟧
22 335 Curr Limit Off 43705 UInt, 1=1% UInt ⟦blank source cell⟧
23 336 Start Time 10s 43706 UInt, 1=1s UInt ⟦blank source cell⟧
24 337 Torque Boost ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
25 3371 TB CurrLim Off 43707 UInt, 1=1% UInt ⟦blank source cell⟧
26 3372 TB Time 1s 43708 UInt, 1=0.1s UInt ⟦blank source cell⟧
27 340 StopSetting ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 80
28 341 Stop Method Coast 43721 UInt, 1=1 UInt ⟦blank source cell⟧
29 342 EndTorqueStp 0% 43722 UInt, 1=1% UInt ⟦blank source cell⟧
30 343 StepDwnVolt 100% 43723 UInt, 1=1% UInt ⟦blank source cell⟧
31 344 BrakeMethod DynVectBrk 43724 UInt, 1=1 UInt ⟦blank source cell⟧
32 345 Stop Time 10s 43725 UInt, 1=1s UInt ⟦blank source cell⟧
33 346 RevC Brk Dly 0,5s 43726 UInt, UInt ⟦blank source cell⟧
34 347 Brk Strength 75% 43727 UInt, 1=1% UInt ⟦blank source cell⟧
35 348 DCB Strength 15% 43728 UInt, 1=1% UInt ⟦blank source cell⟧
36 349 SwitchToDCB 30% 43729 UInt, 1=1% UInt ⟦blank source cell⟧
37 34A DCBrkPhases ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
38 350 Jog ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 83
39 351 JogSpd FWD 10% 43731 UInt, 1=1% UInt ⟦blank source cell⟧
40 352 JogSpd REV 10% 43732 UInt, 1=1% UInt ⟦blank source cell⟧
41 400 Monitor/Prot ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 84
42 410 Load Monitor ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
43 411 Max Alarm ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
44 4111 MaxAlarmAct No action 43775 UInt UInt ⟦blank source cell⟧
45 4112 MaxAlarmLev 116% 43776 Long, 1=1% EInt ⟦blank source cell⟧
46 4113 MaxAlarmDel 0,5s 43330 Long, 1=0.1s EInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 155

Manual reference: physical PDF page 155. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 412 MaxPreAlarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4121 MaxPreAlAct; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4122 MaxPreAlLev; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4123 MaxPreAlDel; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 413 MinPreAlarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4131 MinPreAlAct; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4132 MinPreAlLev; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 412 MaxPreAlarm; displayed row association 4133 MinPreAlDel; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 414 Min Alarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 4141 MinAlarmAct; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 4142 MinAlarmLev; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 4143 MinAlarmDel; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 414 Min Alarm; displayed row association 416 Start Delay; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 417 Autoset; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4171 MaxAlarmMar; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4172 MaxPreAlMar; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4173 MinPreAlMar; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4174 MinAlarmMar; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4175 AutosetAlrm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 4176 Normal Load; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 417 Autoset; displayed row association 420 Process prot; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 421 Ext Alarm; displayed row association 421 Ext Alarm; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 421 Ext Alarm; displayed row association 4211 ExtAlarm1AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 421 Ext Alarm; displayed row association 4212 ExtAlarm2AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 422 Rotor Locked; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 4221 LockRot AA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 4222 LockRotTime; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 4223 LockRotCurr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 422 Rotor Locked; displayed row association 430 Mains Prot; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 431 Volt Unbal; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 4311 VoltUnbalAA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 4312 UnbalLevel; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 431 Volt Unbal; displayed row association 4313 VoltUnbDel; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 432 OverVolt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 4321 OverVoltAA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 4322 OverV Level; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 432 OverVolt; displayed row association 4323 OverV Del; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 433 UnderVolt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4331 UnderVoltAA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4332 UnderVLevel; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4333 UnderV Del; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 434 PhseReversal; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4341 PhaseRevAA; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 4342 AllowedSequ; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 500 I/Os; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 510 An Inputs; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 511 AnIn Fc; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 433 UnderVolt; displayed row association 512 AnIn Setup; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 155

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 412 MaxPreAlarm ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 85
2 4121 MaxPreAlAct No action 43777 UInt UInt ⟦blank source cell⟧
3 4122 MaxPreAlLev 108% 43778 Long, 1=1% EInt ⟦blank source cell⟧
4 4123 MaxPreAlDel 0,5s 43331 Long, 1=0.1s EInt ⟦blank source cell⟧
5 413 MinPreAlarm ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
6 4131 MinPreAlAct No action 43779 UInt UInt ⟦blank source cell⟧
7 4132 MinPreAlLev 92% 43742 Long, 1=1% EInt ⟦blank source cell⟧
8 4133 MinPreAlDel 0,5s 43332 Long, 1=0.1s EInt ⟦blank source cell⟧
9 414 Min Alarm ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 86
10 4141 MinAlarmAct No action 43743 UInt UInt ⟦blank source cell⟧
11 4142 MinAlarmLev 84% 43744 Long, 1=1% EInt ⟦blank source cell⟧
12 4143 MinAlarmDel 0,5s 43333 Long, 1=0.1s EInt ⟦blank source cell⟧
13 416 Start Delay 10s 43324 Long, 1=1s EInt ⟦blank source cell⟧
14 417 Autoset ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
15 4171 MaxAlarmMar 16% 43326 Long, 1=1% EInt ⟦blank source cell⟧
16 4172 MaxPreAlMar 8% 43327 Long, 1=1% EInt ⟦blank source cell⟧
17 4173 MinPreAlMar 8% 43328 Long, 1=1% EInt ⟦blank source cell⟧
18 4174 MinAlarmMar 16% 43329 Long, 1=1% EInt ⟦blank source cell⟧
19 4175 AutosetAlrm No 43334 UInt UInt ⟦blank source cell⟧
20 4176 Normal Load Off 43335 UInt, 1=1 UInt ⟦blank source cell⟧
21 420 Process prot ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 88
22 421 Ext Alarm ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
23 4211 ExtAlarm1AA Hard Trip 43081 UInt UInt ⟦blank source cell⟧
24 4212 ExtAlarm2AA Hard Trip 43764 UInt UInt ⟦blank source cell⟧
25 422 Rotor Locked ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
26 4221 LockRot AA No action 43362 UInt UInt ⟦blank source cell⟧
27 4222 LockRotTime 5,0s 43757 UInt, 1=0.1s UInt ⟦blank source cell⟧
28 4223 LockRotCurr 480% 43759 UInt, 1=1% UInt ⟦blank source cell⟧
29 430 Mains Prot ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 89
30 431 Volt Unbal ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
31 4311 VoltUnbalAA No action 43765 UInt UInt ⟦blank source cell⟧
32 4312 UnbalLevel 10% 43560 UInt, 1=1% UInt ⟦blank source cell⟧
33 4313 VoltUnbDel 1s 43561 UInt, 1=1s UInt ⟦blank source cell⟧
34 432 OverVolt ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
35 4321 OverVoltAA No action 43766 UInt UInt ⟦blank source cell⟧
36 4322 OverV Level 115% 43562 UInt, 1=1% UInt ⟦blank source cell⟧
37 4323 OverV Del 1s 43563 UInt, 1=1s UInt ⟦blank source cell⟧
38 433 UnderVolt ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
39 4331 UnderVoltAA No action 43767 UInt UInt ⟦blank source cell⟧
40 4332 UnderVLevel 85% 43564 UInt, 1=1% UInt ⟦blank source cell⟧
41 4333 UnderV Del 1s 43565 UInt, 1=1s UInt ⟦blank source cell⟧
42 434 PhseReversal ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
43 4341 PhaseRevAA No action 43768 UInt UInt ⟦blank source cell⟧
44 4342 AllowedSequ L123 43566 1=1 ⟦blank source cell⟧ ⟦blank source cell⟧
45 500 I/Os ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 91
46 510 An Inputs ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 91
47 511 AnIn Fc Process Val 43201 UInt UInt ⟦blank source cell⟧
48 512 AnIn Setup 4-20mA 43202 UInt UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 156

Manual reference: physical PDF page 156. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 513 AnIn Advan; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5131 AnIn Min; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5132 AnIn Max; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5134 AnIn FcMin; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5135 AnIn VaMin; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5136 AnIn FcMax; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5137 AnIn VaMax; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 5139 AnIn Filt; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 513A AnIn Enabl; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 520 Dig Inputs; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 521 DigIn 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 522 DigIn 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 523 DigIn 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 524 DigIn 4; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 529 B1 DigIn 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52A B1 DigIn 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52B B1 DigIn 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52C B2 DigIn 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52D B2 DigIn 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 52E B2 DigIn 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 530 An Outputs; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 531 AnOut Fc; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 513 AnIn Advan; displayed row association 532 AnOut Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 533 AnOut Advan; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5331 AnOut Min; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5332 AnOut Max; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5334 AnOutFcMin; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5335 AnOutVaMin; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5336 AnOutFcMax; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 5337 AnOutVaMax; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 550 Relays; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 551 Relay 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 552 Relay 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 553 Relay 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 554 B1 Relay 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 555 B1 Relay 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 556 B1 Relay 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 557 B2 Relay 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 558 B2 Relay 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 533 AnOut Advan; displayed row association 559 B2 Relay 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D Relay Advan; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D1 Relay1 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D2 Relay2 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D3 Relay3 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D4 B1R1 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 55D Relay Advan; displayed row association 55D5 B1R2 Mode; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 156

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 513 AnIn Advan ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
2 5131 AnIn Min 4mA 43203 Long, 1=0.01 EInt ⟦blank source cell⟧
3 5132 AnIn Max 20mA 43204 Long, 1=0.01 EInt ⟦blank source cell⟧
4 5134 AnIn FcMin Min 43206 UInt UInt ⟦blank source cell⟧
5 5135 AnIn VaMin 0 43541 Long, 1= see
Notes
EInt 1=0.001, 1rpm, 1%, 1°C, 0.001
as set in [322]
6 5136 AnIn FcMax Max 43207 UInt UInt ⟦blank source cell⟧
7 5137 AnIn VaMax 0 43551 Long, 1= see
Notes
EInt 1=0.001, 1rpm, 1%, 1°C, 0.001
as set in [322]
8 5139 AnIn Filt 0,1s 43209 Long, 1=
0.001s
EInt ⟦blank source cell⟧
9 513A AnIn Enabl On 43210 UInt UInt ⟦blank source cell⟧
10 520 Dig Inputs ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 94
11 521 DigIn 1 Run FWD 43241 UInt UInt ⟦blank source cell⟧
12 522 DigIn 2 Stop 43242 UInt UInt ⟦blank source cell⟧
13 523 DigIn 3 Set Ctrl 1 43243 UInt UInt ⟦blank source cell⟧
14 524 DigIn 4 Reset 43244 UInt UInt ⟦blank source cell⟧
15 529 B1 DigIn 1 Off 43501 UInt UInt ⟦blank source cell⟧
16 52A B1 DigIn 2 Off 43502 UInt UInt ⟦blank source cell⟧
17 52B B1 DigIn 3 Off 43503 UInt UInt ⟦blank source cell⟧
18 52C B2 DigIn 1 Off 43504 UInt UInt ⟦blank source cell⟧
19 52D B2 DigIn 2 Off 43505 UInt UInt ⟦blank source cell⟧
20 52E B2 DigIn 3 Off 43506 UInt UInt ⟦blank source cell⟧
21 530 An Outputs ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 95
22 531 AnOut Fc Current 43251 UInt UInt ⟦blank source cell⟧
23 532 AnOut Setup 4-20mA 43252 UInt UInt ⟦blank source cell⟧
24 533 AnOut Advan ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
25 5331 AnOut Min 4mA 43253 Long, 1=0.01 EInt ⟦blank source cell⟧
26 5332 AnOut Max 20mA 43254 Long, 1=0.01 EInt ⟦blank source cell⟧
27 5334 AnOutFcMin Min 43256 UInt UInt ⟦blank source cell⟧
28 5335 AnOutVaMin 0 43545 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1% or
0.001 as set in [322]
29 5336 AnOutFcMax Max 43257 UInt UInt ⟦blank source cell⟧
30 5337 AnOutVaMax 0 43555 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1% or
0.001 as set in [322]
31 550 Relays ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 97
32 551 Relay 1 Operation 43273 UInt UInt ⟦blank source cell⟧
33 552 Relay 2 Off 43274 UInt UInt ⟦blank source cell⟧
34 553 Relay 3 Trip 43275 UInt UInt ⟦blank source cell⟧
35 554 B1 Relay 1 Off 43511 UInt UInt ⟦blank source cell⟧
36 555 B1 Relay 2 Off 43512 UInt UInt ⟦blank source cell⟧
37 556 B1 Relay 3 Off 43513 UInt UInt ⟦blank source cell⟧
38 557 B2 Relay 1 Off 43514 UInt UInt ⟦blank source cell⟧
39 558 B2 Relay 2 Off 43515 UInt UInt ⟦blank source cell⟧
40 559 B2 Relay 3 Off 43516 UInt UInt ⟦blank source cell⟧
41 55D Relay Advan ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
42 55D1 Relay1 Mode N.O 43276 UInt UInt ⟦blank source cell⟧
43 55D2 Relay2 Mode N.O 43277 UInt UInt ⟦blank source cell⟧
44 55D3 Relay3 Mode N.O 43278 UInt UInt ⟦blank source cell⟧
45 55D4 B1R1 Mode N.O 43521 UInt UInt ⟦blank source cell⟧
46 55D5 B1R2 Mode N.O 43522 UInt UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 157

Manual reference: physical PDF page 157. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D6 B1R3 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D7 B2R1 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D8 B2R2 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 55D9 B2R3 Mode; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 560 Virtual I/Os; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 561 VIO 1 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 562 VIO 1 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 563 VIO 2 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 564 VIO 2 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 565 VIO 3 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 566 VIO 3 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 567 VIO 4 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 568 VIO 4 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 569 VIO 5 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56A VIO 5 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56B VIO 6 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56C VIO 6 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56D VIO 7 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56E VIO 7 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56F VIO 8 Dest; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 56G VIO 8 Source; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 600 Logic&Timers; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 610 Comparators; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 611 CA1 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6111 CA1 Value; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6112 CA1 LevelHI; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6113 CA1 LevelLO; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6114 CA1 Type; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6116 CA1 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6117 CA1 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 611 CA1 Setup; displayed row association 6118 CA1 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 612 CA2 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6121 CA2 Value; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6122 CA2 LevelHI; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6123 CA2 LevelLO; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6124 CA2 Type; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 612 CA2 Setup; displayed row association 6126 CA2 Set Dly; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 157

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 55D6 B1R3 Mode N.O 43523 UInt UInt ⟦blank source cell⟧
2 55D7 B2R1 Mode N.O 43524 UInt UInt ⟦blank source cell⟧
3 55D8 B2R2 Mode N.O 43525 UInt UInt ⟦blank source cell⟧
4 55D9 B2R3 Mode N.O 43526 UInt UInt ⟦blank source cell⟧
5 560 Virtual I/Os ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 99
6 561 VIO 1 Dest Off 43281 UInt UInt ⟦blank source cell⟧
7 562 VIO 1 Source Off 43282 UInt UInt ⟦blank source cell⟧
8 563 VIO 2 Dest Off 43283 UInt UInt ⟦blank source cell⟧
9 564 VIO 2 Source Off 43284 UInt UInt ⟦blank source cell⟧
10 565 VIO 3 Dest Off 43285 UInt UInt ⟦blank source cell⟧
11 566 VIO 3 Source Off 43286 UInt UInt ⟦blank source cell⟧
12 567 VIO 4 Dest Off 43287 UInt UInt ⟦blank source cell⟧
13 568 VIO 4 Source Off 43288 UInt UInt ⟦blank source cell⟧
14 569 VIO 5 Dest Off 43289 UInt UInt ⟦blank source cell⟧
15 56A VIO 5 Source Off 43290 UInt UInt ⟦blank source cell⟧
16 56B VIO 6 Dest Off 43291 UInt UInt ⟦blank source cell⟧
17 56C VIO 6 Source Off 43292 UInt UInt ⟦blank source cell⟧
18 56D VIO 7 Dest Off 43293 UInt UInt ⟦blank source cell⟧
19 56E VIO 7 Source Off 43294 UInt UInt ⟦blank source cell⟧
20 56F VIO 8 Dest Off 43295 UInt UInt ⟦blank source cell⟧
21 56G VIO 8 Source Off 43296 UInt UInt ⟦blank source cell⟧
22 600 Logic&Timers ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 100
23 610 Comparators ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
24 611 CA1 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
25 6111 CA1 Value Current 43400 UInt UInt ⟦blank source cell⟧
26 6112 CA1 LevelHI 30 43401 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
27 6113 CA1 LevelLO 20 43402 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
28 6114 CA1 Type Hysteresis 43403 UInt UInt ⟦blank source cell⟧
29 6116 CA1 Set Dly 00:00:00 43405 UInt, 1=1h UInt ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43406 UInt, 1=1m UInt ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43407 UInt, 1=0.1s UInt ⟦blank source cell⟧
32 6117 CA1 Res Dly 00:00:00 43408 UInt, 1=1h UInt ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43409 UInt, 1=1m UInt ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43410 UInt, 1=0.1s UInt ⟦blank source cell⟧
35 6118 CA1 Tmr Val 00:00:00 42600 UInt, 1=1h UInt ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42601 UInt, 1=1m UInt ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42602 UInt, 1=0.1s UInt ⟦blank source cell⟧
38 612 CA2 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 104
39 6121 CA2 Value Current 43411 UInt UInt ⟦blank source cell⟧
40 6122 CA2 LevelHI 30 43412 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
41 6123 CA2 LevelLO 20 43413 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
42 6124 CA2 Type Hysteresis 43414 UInt UInt ⟦blank source cell⟧
43 6126 CA2 Set Dly 00:00:00 43416 UInt, 1=1h UInt ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43417 UInt, 1=1m UInt ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43418 UInt, 1=0.1s UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 158

Manual reference: physical PDF page 158. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6127 CA2 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6128 CA2 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 613 CA3 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6131 CA3 Value; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6132 CA3 LevelHI; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6133 CA3 LevelLO; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6134 CA3 Type; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6136 CA3 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6137 CA3 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 613 CA3 Setup; displayed row association 6138 CA3 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 614 CA4 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6141 CA4 Value; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6142 CA4 LevelHI; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6143 CA4 LevelLO; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6144 CA4 Type; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6146 CA4 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6147 CA4 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 614 CA4 Setup; displayed row association 6148 CA4 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 615 CD1 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6151 CD1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6152 CD1 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6153 CD1 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 615 CD1 Setup; displayed row association 6154 CD1 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 616 CD2 Setup; displayed row association 616 CD2 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 616 CD2 Setup; displayed row association 6161 CD2; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 158

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 6127 CA2 Res Dly 00:00:00 43419 UInt, 1=1h UInt ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43420 UInt, 1=1m UInt ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43421 UInt, 1=0.1s UInt ⟦blank source cell⟧
4 6128 CA2 Tmr Val 00:00:00 42603 UInt, 1=1h UInt ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42604 UInt, 1=1m UInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42605 UInt, 1=0.1s UInt ⟦blank source cell⟧
7 613 CA3 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 104
8 6131 CA3 Value Current 43422 UInt UInt ⟦blank source cell⟧
9 6132 CA3 LevelHI 30 43423 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
10 6133 CA3 LevelLO 20 43424 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
11 6134 CA3 Type Hysteresis 43425 UInt UInt ⟦blank source cell⟧
12 6136 CA3 Set Dly 00:00:00 43427 UInt, 1=1h UInt ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43428 UInt, 1=1m UInt ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43429 UInt, 1=0.1s UInt ⟦blank source cell⟧
15 6137 CA3 Res Dly 00:00:00 43430 UInt, 1=1h UInt ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43431 UInt, 1=1m UInt ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43432 UInt, 1=0.1s UInt ⟦blank source cell⟧
18 6138 CA3 Tmr Val 00:00:00 42606 UInt, 1=1h UInt ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42607 UInt, 1=1m UInt ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42608 UInt, 1=0.1s UInt ⟦blank source cell⟧
21 614 CA4 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 104
22 6141 CA4 Value Current 43433 UInt UInt ⟦blank source cell⟧
23 6142 CA4 LevelHI 30 43434 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
24 6143 CA4 LevelLO 20 43435 Long, 1= see
Notes
EInt 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, 0.1°C,
1kWh, 1h or 0.001 as set in [322]
25 6144 CA4 Type Hysteresis 43436 UInt UInt ⟦blank source cell⟧
26 6146 CA4 Set Dly 00:00:00 43438 UInt, 1=1h UInt ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43439 UInt, 1=1m UInt ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43440 UInt, 1=0.1s UInt ⟦blank source cell⟧
29 6147 CA4 Res Dly 00:00:00 43441 UInt, 1=1h UInt ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43442 UInt, 1=1m UInt ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43443 UInt, 1=0.1s UInt ⟦blank source cell⟧
32 6148 CA4 Tmr Val 00:00:00 42609 UInt, 1=1h UInt ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42610 UInt, 1=1m UInt ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42611 UInt, 1=0.1s UInt ⟦blank source cell⟧
35 615 CD1 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 104
36 6151 CD1 Operation 43444 UInt UInt ⟦blank source cell⟧
37 6152 CD1 Set Dly 00:00:00 43445 UInt, 1=1h UInt ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43446 UInt, 1=1m UInt ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43447 UInt, 1=0.1s UInt ⟦blank source cell⟧
40 6153 CD1 Res Dly 00:00:00 43448 UInt, 1=1h UInt ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43449 UInt, 1=1m UInt ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43450 UInt, 1=0.1s UInt ⟦blank source cell⟧
43 6154 CD1 Tmr Val 00:00:00 42612 UInt, 1=1h UInt ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42613 UInt, 1=1m UInt ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42614 UInt, 1=0.1s UInt ⟦blank source cell⟧
46 616 CD2 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 105
47 6161 CD2 DigIn 1 43451 UInt UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 159

Manual reference: physical PDF page 159. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6162 CD2 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6163 CD2 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 6164 CD2 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 617 CD3 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6171 CD3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6172 CD3 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6173 CD3 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 617 CD3 Setup; displayed row association 6174 CD3 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 618 CD4 Setup; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6181 CD4; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6182 CD4 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6183 CD4 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 6184 CD4 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 618 CD4 Setup; displayed row association 620 Logics; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 621 Logic 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6211 L1 Expr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6212 L1 Input 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6213 L1 Op 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6214 L1 Input 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6215 L1 Op 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6216 L1 Input 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6217 L1 Op 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6218 L1 Input 4; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 6219 L1 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 621 Logic 1; displayed row association 621A L1 Res Dly; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 159

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 6162 CD2 Set Dly 00:00:00 43452 UInt, 1=1h UInt ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43453 UInt, 1=1m UInt ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43454 UInt, 1=0.1s UInt ⟦blank source cell⟧
4 6163 CD2 Res Dly 00:00:00 43455 UInt, 1=1h UInt ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43456 UInt, 1=1m UInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43457 UInt, 1=0.1s UInt ⟦blank source cell⟧
7 6164 CD2 Tmr Val 00:00:00 42615 UInt, 1=1h UInt ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42616 UInt, 1=1m UInt ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42617 UInt, 1=0.1s UInt ⟦blank source cell⟧
10 617 CD3 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 105
11 6171 CD3 Trip 43458 UInt UInt ⟦blank source cell⟧
12 6172 CD3 Set Dly 00:00:00 43459 UInt, 1=1h UInt ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43460 UInt, 1=1m UInt ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43461 UInt, 1=0.1s UInt ⟦blank source cell⟧
15 6173 CD3 Res Dly 00:00:00 43462 UInt, 1=1h UInt ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43463 UInt, 1=1m UInt ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43464 UInt, 1=0.1s UInt ⟦blank source cell⟧
18 6174 CD3 Tmr Val 00:00:00 42618 UInt, 1=1h UInt ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42619 UInt, 1=1m UInt ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42620 UInt, 1=0.1s UInt ⟦blank source cell⟧
21 618 CD4 Setup ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 105
22 6181 CD4 Ready 43465 UInt UInt ⟦blank source cell⟧
23 6182 CD4 Set Dly 00:00:00 43466 UInt, 1=1h UInt ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43467 UInt, 1=1m UInt ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43468 UInt, 1=0.1s UInt ⟦blank source cell⟧
26 6183 CD4 Res Dly 00:00:00 43469 UInt, 1=1h UInt ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43470 UInt, 1=1m UInt ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43471 UInt, 1=0.1s UInt ⟦blank source cell⟧
29 6184 CD4 Tmr Val 00:00:00 42621 UInt, 1=1h UInt ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42622 UInt, 1=1m UInt ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42623 UInt, 1=0.1s UInt ⟦blank source cell⟧
32 620 Logics ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 105
33 621 Logic 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
34 6211 L1 Expr ((1.2).3).4 43472 UInt UInt ⟦blank source cell⟧
35 6212 L1 Input 1 CA1 43473 UInt UInt ⟦blank source cell⟧
36 6213 L1 Op 1 & 43474 UInt UInt ⟦blank source cell⟧
37 6214 L1 Input 2 !A2 43475 UInt UInt ⟦blank source cell⟧
38 6215 L1 Op 2 & 43476 UInt UInt ⟦blank source cell⟧
39 6216 L1 Input 3 CA3 43477 UInt UInt ⟦blank source cell⟧
40 6217 L1 Op 3 & 43478 UInt UInt ⟦blank source cell⟧
41 6218 L1 Input 4 CA4 43479 UInt UInt ⟦blank source cell⟧
42 6219 L1 Set Dly 00:00:00 43480 UInt, 1=1h UInt ⟦blank source cell⟧
43 ⟦blank source cell⟧ ⟦blank source cell⟧ 00:00:00 43481 UInt, 1=1m UInt ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ 00:00:00 43482 UInt, 1=0.1s UInt ⟦blank source cell⟧
45 621A L1 Res Dly ⟦blank source cell⟧ 43483 UInt, 1=1h UInt ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43484 UInt, 1=1m UInt ⟦blank source cell⟧
47 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43485 UInt, 1=0.1s UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 160

Manual reference: physical PDF page 160. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuing from prior page; displayed row association 621B L1 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 622 Logic 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6221 L2 Expr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6222 L2 Input 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6223 L2 Op 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6224 L2 Input 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6225 L2 Op 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6226 L2 Input 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6227 L2 Op 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6228 L2 Input 4; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 6229 L2 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 622A L2 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 622 Logic 2; displayed row association 622B L2 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 623 Logic 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6231 L3 Expr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6232 L3 Input 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6233 L3 Op 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6234 L3 Input 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6235 L3 Op 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6236 L3 Input 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6237 L3 Op 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6238 L3 Input 4; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 6239 L3 Set Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 623A L3 Res Dly; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 623 Logic 3; displayed row association 623B L3 Tmr Val; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 624 Logic 4; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6241 L4 Expr; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6242 L4 Input 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6243 L4 Op 1; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6244 L4 Input 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6245 L4 Op 2; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6246 L4 Input 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6247 L4 Op 3; blanks remain unfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 624 Logic 4; displayed row association 6248 L4 Input 4; blanks remain unfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 160

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 621B L1 Tmr Val ⟦blank source cell⟧ 42624 UInt, 1=1h UInt ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42625 UInt, 1=1m UInt ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42626 UInt, 1=0.1s UInt ⟦blank source cell⟧
4 622 Logic 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 108
5 6221 L2 Expr ((1.2).3).4 43486 UInt UInt ⟦blank source cell⟧
6 6222 L2 Input 1 CA1 43487 UInt UInt ⟦blank source cell⟧
7 6223 L2 Op 1 & 43488 UInt UInt ⟦blank source cell⟧
8 6224 L2 Input 2 !A2 43489 UInt UInt ⟦blank source cell⟧
9 6225 L2 Op 2 & 43490 UInt UInt ⟦blank source cell⟧
10 6226 L2 Input 3 CA1 43491 UInt UInt ⟦blank source cell⟧
11 6227 L2 Op 3 & 43492 UInt UInt ⟦blank source cell⟧
12 6228 L2 Input 4 !A2 43493 UInt UInt ⟦blank source cell⟧
13 6229 L2 Set Dly 00:00:00 43494 UInt, 1=1h UInt ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43495 UInt, 1=1m UInt ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43496 UInt, 1=0.1s UInt ⟦blank source cell⟧
16 622A L2 Res Dly 00:00:00 43497 UInt, 1=1h UInt ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43498 UInt, 1=1m UInt ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43499 UInt, 1=0.1s UInt ⟦blank source cell⟧
19 622B L2 Tmr Val 00:00:00 42627 UInt, 1=1h UInt ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42628 UInt, 1=1m UInt ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42629 UInt, 1=0.1s UInt ⟦blank source cell⟧
22 623 Logic 3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 108
23 6231 L3 Expr ((1.2).3).4 43780 UInt UInt ⟦blank source cell⟧
24 6232 L3 Input 1 CA1 43781 UInt UInt ⟦blank source cell⟧
25 6233 L3 Op 1 & 43782 UInt UInt ⟦blank source cell⟧
26 6234 L3 Input 2 !A2 43783 UInt UInt ⟦blank source cell⟧
27 6235 L3 Op 2 & 43784 UInt UInt ⟦blank source cell⟧
28 6236 L3 Input 3 CA3 43785 UInt UInt ⟦blank source cell⟧
29 6237 L3 Op 3 & 43786 UInt UInt ⟦blank source cell⟧
30 6238 L3 Input 4 CA4 43787 UInt UInt ⟦blank source cell⟧
31 6239 L3 Set Dly 00:00:00 43788 UInt, 1=1h UInt ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43789 UInt, 1=1m UInt ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43790 UInt, 1=0.1s UInt ⟦blank source cell⟧
34 623A L3 Res Dly 00:00:00 43791 UInt, 1=1h UInt ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43792 UInt, 1=1m UInt ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43793 UInt, 1=0.1s UInt ⟦blank source cell⟧
37 623B L3 Tmr Val 00:00:00 42630 UInt, 1=1h UInt ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42631 UInt, 1=1m UInt ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42632 UInt, 1=0.1s UInt ⟦blank source cell⟧
40 624 Logic 4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 108
41 6241 L4 Expr ((1.2).3).4 43794 UInt UInt ⟦blank source cell⟧
42 6242 L4 Input 1 CA1 43795 UInt UInt ⟦blank source cell⟧
43 6243 L4 Op 1 & 43796 UInt UInt ⟦blank source cell⟧
44 6244 L4 Input 2 !A2 43797 UInt UInt ⟦blank source cell⟧
45 6245 L4 Op 2 & 43798 UInt UInt ⟦blank source cell⟧
46 6246 L4 Input 3 CA1 43799 UInt UInt ⟦blank source cell⟧
47 6247 L4 Op 3 & 43800 UInt UInt ⟦blank source cell⟧
48 6248 L4 Input 4 !A2 43801 UInt UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 161

Manual reference: physical PDF page 161. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 6249 L4 Set Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 624A L4 Res Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 624B L4 Tmr Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 630 Timers; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 631 Timer1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6311 Timer1 Trig; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6312 Timer1 Mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6313 Timer1 Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6314 Timer1 T1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6315 Timer1 T2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 631 Timer1; displayed association 6316 Timer1 Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 632 Timer2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6321 Timer2 Trig; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6322 Timer2 Mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6323 Timer2 Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6324 Timer2 T1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6325 Timer2 T2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 632 Timer2; displayed association 6326 Timer2 Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 633 Timer3; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6331 Timer3 Trig; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6332 Timer3 Mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6333 Timer3 Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 633 Timer3; displayed association 6334 Timer3 T1; blank values remainunfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 161

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 6249 L4 Set Dly 00:00:00 43802 UInt, 1=1h UInt ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43803 UInt, 1=1m UInt ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43804 UInt, 1=0.1s UInt ⟦blank source cell⟧
4 624A L4 Res Dly 00:00:00 43805 UInt, 1=1h UInt ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43806 UInt, 1=1m UInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43807 UInt, 1=0.1s UInt ⟦blank source cell⟧
7 624B L4 Tmr Val 00:00:00 42633 UInt, 1=1h UInt ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42634 UInt, 1=1m UInt ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42635 UInt, 1=0.1s UInt ⟦blank source cell⟧
10 630 Timers ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 109
11 631 Timer1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
12 6311 Timer1 Trig Off 43808 UInt UInt ⟦blank source cell⟧
13 6312 Timer1 Mode Delay 43809 UInt UInt ⟦blank source cell⟧
14 6313 Timer1 Dly 00:00:00 43810 UInt, 1=1h UInt ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43811 UInt, 1=1m UInt ⟦blank source cell⟧
16 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43812 UInt, 1=0.1s UInt ⟦blank source cell⟧
17 6314 Timer1 T1 00:00:00 43813 UInt, 1=1h UInt ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43814 UInt, 1=1m UInt ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43815 UInt, 1=0.1s UInt ⟦blank source cell⟧
20 6315 Timer1 T2 00:00:00 43816 UInt, 1=1h UInt ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43817 UInt, 1=1m UInt ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43818 UInt, 1=0.1s UInt ⟦blank source cell⟧
23 6316 Timer1 Val 00:00:00 42636 UInt, 1=1h UInt ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42637 UInt, 1=1m UInt ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42638 UInt, 1=0.1s UInt ⟦blank source cell⟧
26 632 Timer2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 110
27 6321 Timer2 Trig Off 43819 UInt UInt ⟦blank source cell⟧
28 6322 Timer2 Mode Delay 43820 UInt UInt ⟦blank source cell⟧
29 6323 Timer2 Dly 00:00:00 43821 UInt, 1=1h UInt ⟦blank source cell⟧
30 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43822 UInt, 1=1m UInt ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43823 UInt, 1=0.1s UInt ⟦blank source cell⟧
32 6324 Timer2 T1 00:00:00 43824 UInt, 1=1h UInt ⟦blank source cell⟧
33 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43825 UInt, 1=1m UInt ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43826 UInt, 1=0.1s UInt ⟦blank source cell⟧
35 6325 Timer2 T2 00:00:00 43827 UInt, 1=1h UInt ⟦blank source cell⟧
36 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43828 UInt, 1=1m UInt ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43829 UInt, 1=0.1s UInt ⟦blank source cell⟧
38 6326 Timer2 Val 00:00:00 42639 UInt, 1=1h UInt ⟦blank source cell⟧
39 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42640 UInt, 1=1m UInt ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42641 UInt, 1=0.1s UInt ⟦blank source cell⟧
41 633 Timer3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 110
42 6331 Timer3 Trig Off 43830 UInt UInt ⟦blank source cell⟧
43 6332 Timer3 Mode Delay 43831 UInt UInt ⟦blank source cell⟧
44 6333 Timer3 Dly 00:00:00 43832 UInt, 1=1h UInt ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43833 UInt, 1=1m UInt ⟦blank source cell⟧
46 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43834 UInt, 1=0.1s UInt ⟦blank source cell⟧
47 6334 Timer3 T1 00:00:00 43835 UInt, 1=1h UInt ⟦blank source cell⟧
48 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43836 UInt, 1=1m UInt ⟦blank source cell⟧
49 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43837 UInt, 1=0.1s UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 162

Manual reference: physical PDF page 162. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 6335 Timer3 T2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 6336 Timer3 Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 634 Timer4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6341 Timer4 Trig; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6342 Timer4 Mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6343 Timer4 Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6344 Timer4 T1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6345 Timer4 T2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 6346 Timer4 Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 634 Timer4; displayed association 640 Flip flops; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 641 Flip flop 1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6411 F1 mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6412 F1 set; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6413 F1 reset; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6414 F1 Set Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6415 F1 Res Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 641 Flip flop 1; displayed association 6416 F1 Tmr Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 642 Flip flop 2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6421 F2 mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6422 F2 set; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6423 F2 reset; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6424 F2 Set Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6425 F2 Res Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 642 Flip flop 2; displayed association 6426 F2 Tmr Val; blank values remainunfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 162

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 6335 Timer3 T2 00:00:00 43838 UInt, 1=1h UInt ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43839 UInt, 1=1m UInt ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43840 UInt, 1=0.1s UInt ⟦blank source cell⟧
4 6336 Timer3 Val 00:00:00 42642 UInt, 1=1h UInt ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42643 UInt, 1=1m UInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42644 UInt, 1=0.1s UInt ⟦blank source cell⟧
7 634 Timer4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 110
8 6341 Timer4 Trig Off 43841 UInt UInt ⟦blank source cell⟧
9 6342 Timer4 Mode Delay 43842 UInt UInt ⟦blank source cell⟧
10 6343 Timer4 Dly 00:00:00 43843 UInt, 1=1h UInt ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43844 UInt, 1=1m UInt ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43845 UInt, 1=0.1s UInt ⟦blank source cell⟧
13 6344 Timer4 T1 00:00:00 43846 UInt, 1=1h UInt ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43847 UInt, 1=1m UInt ⟦blank source cell⟧
15 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43848 UInt, 1=0.1s UInt ⟦blank source cell⟧
16 6345 Timer4 T2 00:00:00 43849 UInt, 1=1h UInt ⟦blank source cell⟧
17 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43850 UInt, 1=1m UInt ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43851 UInt, 1=0.1s UInt ⟦blank source cell⟧
19 6346 Timer4 Val 00:00:00 42645 UInt, 1=1h UInt ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42646 UInt, 1=1m UInt ⟦blank source cell⟧
21 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42647 UInt, 1=0.1s UInt ⟦blank source cell⟧
22 640 Flip flops ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 110
23 641 Flip flop 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
24 6411 F1 mode Reset 43852 UInt UInt ⟦blank source cell⟧
25 6412 F1 set Off 43853 UInt UInt ⟦blank source cell⟧
26 6413 F1 reset Off 43854 UInt UInt ⟦blank source cell⟧
27 6414 F1 Set Dly 00:00:00 43855 UInt, 1=1h UInt ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43856 UInt, 1=1m UInt ⟦blank source cell⟧
29 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43857 UInt, 1=0.1s UInt ⟦blank source cell⟧
30 6415 F1 Res Dly 00:00:00 43858 UInt, 1=1h UInt ⟦blank source cell⟧
31 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43859 UInt, 1=1m UInt ⟦blank source cell⟧
32 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43860 UInt, 1=0.1s UInt ⟦blank source cell⟧
33 6416 F1 Tmr Val 00:00:00 42648 UInt, 1=1h UInt ⟦blank source cell⟧
34 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42649 UInt, 1=1m UInt ⟦blank source cell⟧
35 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42650 UInt, 1=0.1s UInt ⟦blank source cell⟧
36 642 Flip flop 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 112
37 6421 F2 mode Reset 43861 UInt UInt ⟦blank source cell⟧
38 6422 F2 set Off 43862 UInt UInt ⟦blank source cell⟧
39 6423 F2 reset Off 43863 UInt UInt ⟦blank source cell⟧
40 6424 F2 Set Dly 00:00:00 43864 UInt, 1=1h UInt ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43865 UInt, 1=1m UInt ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43866 UInt, 1=0.1s UInt ⟦blank source cell⟧
43 6425 F2 Res Dly 00:00:00 43867 UInt, 1=1h UInt ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43868 UInt, 1=1m UInt ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43869 UInt, 1=0.1s UInt ⟦blank source cell⟧
46 6426 F2 Tmr Val 00:00:00 42651 UInt, 1=1h UInt ⟦blank source cell⟧
47 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42652 UInt, 1=1m UInt ⟦blank source cell⟧
48 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42653 UInt, 1=0.1s UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 163

Manual reference: physical PDF page 163. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 643 Flip flop 3; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6431 F3 mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6432 F3 set; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6433 F3 reset; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6434 F3 Set Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6435 F3 Res Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 643 Flip flop 3; displayed association 6436 F3 Tmr Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 644 Flip flop 4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6441 F4 mode; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6442 F4 set; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6443 F4 reset; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6444 F4 Set Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6445 F4 Res Dly; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 6446 F4 Tmr Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 644 Flip flop 4; displayed association 650 Counters; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 651 Counter 1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6511 C1 Trig; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6512 C1 Reset; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6513 C1 Trip val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 651 Counter 1; displayed association 6514 C1 Value; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 652 Counter 2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6521 C2 Trig; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6522 C2 Reset; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6523 C2 Trip val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 6524 C2 Value; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 652 Counter 2; displayed association 660 Clock logic; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 661 Clock 1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6611 Clk1TimeON; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6612 Clk1TimeOff; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6613 Clk1DateOn; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6614 Clk1DateOff; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 661 Clock 1; displayed association 6615 Clk1Weekday; blank values remainunfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 163

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 643 Flip flop 3 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 112
2 6431 F3 mode Set 43870 UInt UInt ⟦blank source cell⟧
3 6432 F3 set Off 43871 UInt UInt ⟦blank source cell⟧
4 6433 F3 reset Off 43872 UInt UInt ⟦blank source cell⟧
5 6434 F3 Set Dly 00:00:00 43873 UInt, 1=1h UInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43874 UInt, 1=1m UInt ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43875 UInt, 1=0.1s UInt ⟦blank source cell⟧
8 6435 F3 Res Dly 00:00:00 43876 UInt, 1=1h UInt ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43877 UInt, 1=1m UInt ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43878 UInt, 1=0.1s UInt ⟦blank source cell⟧
11 6436 F3 Tmr Val 00:00:00 42654 UInt, 1=1h UInt ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42655 UInt, 1=1m UInt ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42656 UInt, 1=0.1s UInt ⟦blank source cell⟧
14 644 Flip flop 4 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 112
15 6441 F4 mode Edge 43879 UInt UInt ⟦blank source cell⟧
16 6442 F4 set Off 43880 UInt UInt ⟦blank source cell⟧
17 6443 F4 reset Off 43881 UInt UInt ⟦blank source cell⟧
18 6444 F4 Set Dly 00:00:00 43882 UInt, 1=1h UInt ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43883 UInt, 1=1m UInt ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43884 UInt, 1=0.1s UInt ⟦blank source cell⟧
21 6445 F4 Res Dly 00:00:00 43885 UInt, 1=1h UInt ⟦blank source cell⟧
22 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43886 UInt, 1=1m UInt ⟦blank source cell⟧
23 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43887 UInt, 1=0.1s UInt ⟦blank source cell⟧
24 6446 F4 Tmr Val 00:00:00 42657 UInt, 1=1h UInt ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42658 UInt, 1=1m UInt ⟦blank source cell⟧
26 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42659 UInt, 1=0.1s UInt ⟦blank source cell⟧
27 650 Counters ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 112
28 651 Counter 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
29 6511 C1 Trig Off 43888 UInt UInt ⟦blank source cell⟧
30 6512 C1 Reset Off 43889 UInt UInt ⟦blank source cell⟧
31 6513 C1 Trip val 0 43890 UInt, 1=1 UInt ⟦blank source cell⟧
32 6514 C1 Value ⟦blank source cell⟧ 31070 UInt, 1=1 UInt ⟦blank source cell⟧
33 652 Counter 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
34 6521 C2 Trig Off 43891 UInt UInt ⟦blank source cell⟧
35 6522 C2 Reset Off 43892 UInt UInt ⟦blank source cell⟧
36 6523 C2 Trip val 0 43893 UInt, 1=1 UInt ⟦blank source cell⟧
37 6524 C2 Value ⟦blank source cell⟧ 31071 UInt, 1=1 UInt ⟦blank source cell⟧
38 660 Clock logic ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 113
39 661 Clock 1 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
40 6611 Clk1TimeON 00:00:00 43600 Long, 1=1h EInt ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43601 Long, 1=1m EInt ⟦blank source cell⟧
42 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43602 Long, 1=1s EInt ⟦blank source cell⟧
43 6612 Clk1TimeOff 00:00:00 43603 Long, 1=1h EInt ⟦blank source cell⟧
44 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43604 Long, 1=1m EInt ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43605 Long, 1=1s EInt ⟦blank source cell⟧
46 6613 Clk1DateOn 0 43606 Long, 1=1 EInt ⟦blank source cell⟧
47 6614 Clk1DateOff 0 43609 Long, 1=1 EInt ⟦blank source cell⟧
48 6615 Clk1Weekday 0 43612 UInt, 1=1 UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 164

Manual reference: physical PDF page 164. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 662 Clock 2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6621 Clk2TimeON; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6622 Clk2TimeOff; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6623 Clk2DateOn; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6624 Clk2DateOff; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 6625 Clk2Weekday; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 700 Oper/Status; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 710 Operation; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71X Set/View ref; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 711 Process Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 713 Torque; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 714 Torque; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 715 Shaft Power; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 716 Shaft Power; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 717 El Power; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 718 RMS Current; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 719 L main volt; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71A Heatsnk Tmp; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71B PT100B1 123; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71C PT100B2 123; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71D Current I1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71E Current I2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71F Current I3; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71G L12 voltage; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71H L13 voltage; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71I L23 voltage; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71J Phase seq.; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 71K Used Th Cap; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 720 Status; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 721 TSA Status; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 722 Warning; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 723 DigInStatus; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 724 RelayStatus; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 725 AnalogueIn; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 726 AnalogueOut; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 727 IO StatusB1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 728 IO StatusB2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 72A CA1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 662 Clock 2; displayed association 72B CD1-4; blank values remainunfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 164

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 662 Clock 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 114
2 6621 Clk2TimeON 00:00:00 43615 Long, 1=1h EInt ⟦blank source cell⟧
3 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43616 Long, 1=1m EInt ⟦blank source cell⟧
4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43617 Long, 1=1s EInt ⟦blank source cell⟧
5 6622 Clk2TimeOff 00:00:00 43618 Long, 1=1h EInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43619 Long, 1=1m EInt ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 43620 Long, 1=1s EInt ⟦blank source cell⟧
8 6623 Clk2DateOn 0 43621 Long, 1=1 EInt ⟦blank source cell⟧
9 6624 Clk2DateOff 0 43624 Long, 1=1 EInt ⟦blank source cell⟧
10 6625 Clk2Weekday 0 43627 Long, 1=1 EInt ⟦blank source cell⟧
11 700 Oper/Status ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 114
12 710 Operation ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
13 71X Set/View ref ⟦blank source cell⟧ 31000 Long, 1= see
Notes
EInt 1rpm, 1%, 1°C, 0.001 as set in [322]
14 711 Process Val ⟦blank source cell⟧ 31002 Long, 1= see
Notes
EInt 1rpm, 1%, 1°C, 0.001 as set in [322]
15 713 Torque ⟦blank source cell⟧ 31003 Long,
1=0.1Nm
EInt ⟦blank source cell⟧
16 714 Torque ⟦blank source cell⟧ 31004 Long, 1=1% EInt ⟦blank source cell⟧
17 715 Shaft Power ⟦blank source cell⟧ 31005 Long, 1=1W EInt ⟦blank source cell⟧
18 716 Shaft Power ⟦blank source cell⟧ 31006 UInt, 1=1% UInt ⟦blank source cell⟧
19 717 El Power ⟦blank source cell⟧ 31007 Long, 1=1W EInt ⟦blank source cell⟧
20 718 RMS Current ⟦blank source cell⟧ 31008 Long, 1=0.1A EInt ⟦blank source cell⟧
21 719 L main volt ⟦blank source cell⟧ 31009 Long, 1=0.1V EInt ⟦blank source cell⟧
22 71A Heatsnk Tmp ⟦blank source cell⟧ 31010 Long,
1=0.1°C
EInt ⟦blank source cell⟧
23 71B PT100B1 123 ⟦blank source cell⟧ 31011 Long, 1=1°C EInt ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31012 Long, 1=1°C EInt ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31013 Long, 1=1°C EInt ⟦blank source cell⟧
26 71C PT100B2 123 ⟦blank source cell⟧ 31014 Long, 1=1°C EInt ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31015 Long, 1=1°C EInt ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31016 Long, 1=1°C EInt ⟦blank source cell⟧
29 71D Current I1 ⟦blank source cell⟧ 31017 Long, 1=0.1A EInt ⟦blank source cell⟧
30 71E Current I2 ⟦blank source cell⟧ 31018 Long, 1=0.1A EInt ⟦blank source cell⟧
31 71F Current I3 ⟦blank source cell⟧ 31019 Long, 1=0.1A EInt ⟦blank source cell⟧
32 71G L12 voltage ⟦blank source cell⟧ 31020 Long, 1=0.1V EInt ⟦blank source cell⟧
33 71H L13 voltage ⟦blank source cell⟧ 31021 Long, 1=0.1V EInt ⟦blank source cell⟧
34 71I L23 voltage ⟦blank source cell⟧ 31022 Long, 1=0.1V EInt ⟦blank source cell⟧
35 71J Phase seq. ⟦blank source cell⟧ 31023 UInt UInt ⟦blank source cell⟧
36 71K Used Th Cap ⟦blank source cell⟧ 31024 Long, 1=0.1% EInt ⟦blank source cell⟧
37 720 Status ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 116
38 721 TSA Status ⟦blank source cell⟧ 31025 UInt UInt ⟦blank source cell⟧
39 722 Warning ⟦blank source cell⟧ 31026 UInt UInt ⟦blank source cell⟧
40 723 DigInStatus ⟦blank source cell⟧ 31027 UInt, 1=1 UInt ⟦blank source cell⟧
41 724 RelayStatus ⟦blank source cell⟧ 31028 UInt, 1=1 UInt ⟦blank source cell⟧
42 725 AnalogueIn ⟦blank source cell⟧ 31029 Long, 1=1% EInt ⟦blank source cell⟧
43 726 AnalogueOut ⟦blank source cell⟧ 31030 Long, 1=1% EInt ⟦blank source cell⟧
44 727 IO StatusB1 ⟦blank source cell⟧ 31031 UInt, 1=1 UInt ⟦blank source cell⟧
45 728 IO StatusB2 ⟦blank source cell⟧ 31032 UInt, 1=1 UInt ⟦blank source cell⟧
46 72A CA1-4 ⟦blank source cell⟧ 31050 UInt, 1=1 UInt ⟦blank source cell⟧
47 72B CD1-4 ⟦blank source cell⟧ 31051 UInt, 1=1 UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 165

Manual reference: physical PDF page 165. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72C Logic 1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72D Timer 1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72E FlipFlop1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72F Counter 1-2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 72G TtoNxtStart; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 730 Stored Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 731 Run Time; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 7311 Reset RunTm; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 732 Mains Time; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 733 Energy; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 7331 Rst Energy; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 740 Clock; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 741 Time; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 742 Date; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 743 Weekday; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 744 DST; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 800 View TripLog; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 810 (Trip log list 1); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 810 Trip Message; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811 Operation; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8111 Process Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8113 Torque; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8114 Torque; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8115 Shaft Power; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8116 ShaftPower%; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8117 El Power; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8118 RMS Current; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 8119 L main volt; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811A Heatsnk Tmp; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811B PT100B1 123; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811C PT100B2 123; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811D Current I1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811E Current I2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811F Current I3; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811G L12 voltage; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811H L13 voltage; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 811 Operation; displayed association 811I L23 voltage; blank values remainunfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 165

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 72C Logic 1-4 ⟦blank source cell⟧ 31052 UInt, 1=1 UInt ⟦blank source cell⟧
2 72D Timer 1-4 ⟦blank source cell⟧ 31053 UInt, 1=1 UInt ⟦blank source cell⟧
3 72E FlipFlop1-4 ⟦blank source cell⟧ 31072 UInt, 1=1 UInt ⟦blank source cell⟧
4 72F Counter 1-2 ⟦blank source cell⟧ 31073 UInt, 1=1 UInt ⟦blank source cell⟧
5 72G TtoNxtStart ⟦blank source cell⟧ 31036 UInt, 1=1min UInt ⟦blank source cell⟧
6 730 Stored Val ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 119
7 731 Run Time 00:00:00 31074 Long, 1=1h EInt ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31075 Long, 1=1m EInt ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31076 Long, 1=1s EInt ⟦blank source cell⟧
10 7311 Reset RunTm No 7 UInt UInt ⟦blank source cell⟧
11 732 Mains Time 00:00:00 31077 Long, 1=1h EInt ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31078 Long, 1=1m EInt ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31079 Long, 1=1s EInt ⟦blank source cell⟧
14 733 Energy ...kWh 31080 Long, 1=1Wh EInt ⟦blank source cell⟧
15 7331 Rst Energy No 6 UInt UInt ⟦blank source cell⟧
16 740 Clock ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 119
17 741 Time 00:00:00 42920 Long, 1=1h EInt ⟦blank source cell⟧
18 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42921 Long, 1=1m EInt ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42922 Long, 1=1s EInt ⟦blank source cell⟧
20 742 Date 0 42923 Long, 1=1 EInt ⟦blank source cell⟧
21 743 Weekday Monday 42926 Long EInt ⟦blank source cell⟧
22 744 DST No 43058 UInt UInt ⟦blank source cell⟧
23 800 View TripLog ⟦blank source cell⟧ See Appendix 2 ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 120
24 810 (Trip log list 1) ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
25 810 Trip Message ⟦blank source cell⟧ 31101 UInt, 1=1 UInt ⟦blank source cell⟧
26 811 Operation ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
27 8111 Process Val ⟦blank source cell⟧ 31102 Long, 1= see
Notes
EInt 1rpm, 1%, 1°C, 0.001 as set in [322]
28 8113 Torque ⟦blank source cell⟧ 31104 Long,
1=0.1Nm
EInt ⟦blank source cell⟧
29 8114 Torque ⟦blank source cell⟧ 31105 Long, 1=1% EInt ⟦blank source cell⟧
30 8115 Shaft Power ⟦blank source cell⟧ 31106 Long, 1=1W EInt Page 120
31 8116 ShaftPower% ⟦blank source cell⟧ 31107 UInt, 1=1% UInt ⟦blank source cell⟧
32 8117 El Power ⟦blank source cell⟧ 31108 Long, 1=1W EInt ⟦blank source cell⟧
33 8118 RMS Current ⟦blank source cell⟧ 31109 Long, 1=0.1A EInt ⟦blank source cell⟧
34 8119 L main volt ⟦blank source cell⟧ 31110 Long, 1=0.1V EInt ⟦blank source cell⟧
35 811A Heatsnk Tmp ⟦blank source cell⟧ 31111 Long,
1=0.1°C
EInt ⟦blank source cell⟧
36 811B PT100B1 123 ⟦blank source cell⟧ 31112 Long, 1=1°C EInt ⟦blank source cell⟧
37 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31113 Long, 1=1°C EInt ⟦blank source cell⟧
38 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31114 Long, 1=1°C EInt ⟦blank source cell⟧
39 811C PT100B2 123 ⟦blank source cell⟧ 31115 Long, 1=1°C EInt ⟦blank source cell⟧
40 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31116 Long, 1=1°C EInt ⟦blank source cell⟧
41 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31117 Long, 1=1°C EInt ⟦blank source cell⟧
42 811D Current I1 ⟦blank source cell⟧ 31118 Long, 1=0.1A EInt ⟦blank source cell⟧
43 811E Current I2 ⟦blank source cell⟧ 31119 Long, 1=0.1A EInt ⟦blank source cell⟧
44 811F Current I3 ⟦blank source cell⟧ 31120 Long, 1=0.1A EInt ⟦blank source cell⟧
45 811G L12 voltage ⟦blank source cell⟧ 31121 Long, 1=0.1V EInt ⟦blank source cell⟧
46 811H L13 voltage ⟦blank source cell⟧ 31122 Long, 1=0.1V EInt ⟦blank source cell⟧
47 811I L23 voltage ⟦blank source cell⟧ 31123 Long, 1=0.1V EInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 166

Manual reference: physical PDF page 166. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 811J Phase seq.; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 811K Used Th Cap; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812 Status; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8121 TSA Status; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8122 DigInStatus; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8123 RelayStatus; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8124 AnalogueIn; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8125 AnalogueOut; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8126 IO StatusB1; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8127 IO StatusB2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 8129 CA1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812A CD1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812B Logic 1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812C Timer 1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812D FlipFlop1-4; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812E Counter 1-2; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812F TtoNxtStart; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812G Time; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 812 Status; displayed association 812H Date; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 813 Stored Val; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 8131 Run Time; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 8132 Mains Time; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 813 Stored Val; displayed association 820 (Trip log list 2); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 830 (Trip log list 3); displayed association 830 (Trip log list 3); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 840 (Trip log list 4); displayed association 840 (Trip log list 4); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 850 (Trip log list 5); displayed association 850 (Trip log list 5); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 860 (Trip log list 6); displayed association 860 (Trip log list 6); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 870 (Trip log list 7); displayed association 870 (Trip log list 7); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 880 (Trip log list 8); displayed association 880 (Trip log list 8); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 890 (Trip log list 9); blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 8A0 Reset Trip L; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 900 System Data; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 910 Service Info; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 911 Next Service; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 912 Service Cont; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 920 TSA Data; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 921 TSA Type; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 922 Software; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 890 (Trip log list 9); displayed association 9221 Build Info; blank values remainunfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 166

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 811J Phase seq. ⟦blank source cell⟧ 31124 UInt UInt ⟦blank source cell⟧
2 811K Used Th Cap ⟦blank source cell⟧ 31125 Long, 1=0.1% EInt ⟦blank source cell⟧
3 812 Status ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 120
4 8121 TSA Status ⟦blank source cell⟧ 31126 UInt UInt ⟦blank source cell⟧
5 8122 DigInStatus ⟦blank source cell⟧ 31127 UInt, 1=1 UInt ⟦blank source cell⟧
6 8123 RelayStatus ⟦blank source cell⟧ 31128 UInt, 1=1 UInt ⟦blank source cell⟧
7 8124 AnalogueIn ⟦blank source cell⟧ 31129 Long, 1=1% EInt ⟦blank source cell⟧
8 8125 AnalogueOut ⟦blank source cell⟧ 31130 Long, 1=1% EInt ⟦blank source cell⟧
9 8126 IO StatusB1 ⟦blank source cell⟧ 31131 UInt, 1=1 UInt ⟦blank source cell⟧
10 8127 IO StatusB2 ⟦blank source cell⟧ 31132 UInt, 1=1 UInt ⟦blank source cell⟧
11 8129 CA1-4 ⟦blank source cell⟧ 31134 UInt, 1=1 UInt ⟦blank source cell⟧
12 812A CD1-4 ⟦blank source cell⟧ 31135 UInt, 1=1 UInt ⟦blank source cell⟧
13 812B Logic 1-4 ⟦blank source cell⟧ 31136 UInt, 1=1 UInt ⟦blank source cell⟧
14 812C Timer 1-4 ⟦blank source cell⟧ 31137 UInt, 1=1 UInt ⟦blank source cell⟧
15 812D FlipFlop1-4 ⟦blank source cell⟧ 31138 UInt, 1=1 UInt ⟦blank source cell⟧
16 812E Counter 1-2 ⟦blank source cell⟧ 31139 UInt, 1=1 UInt ⟦blank source cell⟧
17 812F TtoNxtStart ⟦blank source cell⟧ 31140 UInt, 1=1min UInt ⟦blank source cell⟧
18 812G Time 00:00:00 31141 Long, 1=1h EInt ⟦blank source cell⟧
19 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31142 Long, 1=1m EInt ⟦blank source cell⟧
20 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31143 Long, 1=1s EInt ⟦blank source cell⟧
21 812H Date ⟦blank source cell⟧ 31144 Long, 1=1 EInt ⟦blank source cell⟧
22 813 Stored Val ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 120
23 8131 Run Time 00:00:00 31147 Long, 1=1h EInt ⟦blank source cell⟧
24 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31148 Long, 1=1m EInt ⟦blank source cell⟧
25 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31149 Long, 1=1s EInt ⟦blank source cell⟧
26 8132 Mains Time 00:00:00 31150 Long, 1=1h EInt ⟦blank source cell⟧
27 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31151 Long, 1=1m EInt ⟦blank source cell⟧
28 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31152 Long, 1=1s EInt ⟦blank source cell⟧
29 820 (Trip log list 2) ⟦blank source cell⟧ Same parameters as for menu group 810 (Trip
log list 1).
Communication data in Appendix 2.
⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 121
30 830 (Trip log list 3) ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
31 840 (Trip log list 4) ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
32 850 (Trip log list 5) ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
33 860 (Trip log list 6) ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
34 870 (Trip log list 7) ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
35 880 (Trip log list 8) ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
36 890 (Trip log list 9) ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
37 8A0 Reset Trip L No 8 UInt UInt Page 121
38 900 System Data ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ Page 121
39 910 Service Info ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
40 911 Next Service ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
41 912 Service Cont ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
42 920 TSA Data ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧
43 921 TSA Type - 42300 UInt, 1=1 UInt ⟦blank source cell⟧
44 922 Software ⟦blank source cell⟧ 31038 UInt UInt ⟦blank source cell⟧
45 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31039 UInt UInt ⟦blank source cell⟧
46 9221 Build Info ⟦blank source cell⟧ 31040 UInt UInt ⟦blank source cell⟧
47 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31041 UInt UInt ⟦blank source cell⟧
48 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31042 UInt UInt ⟦blank source cell⟧
49 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31043 UInt UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 167

Manual reference: physical PDF page 167. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 9221 Build Info continuation from PDF166; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Appendix continuation; displayed association 923 Unit Name; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 924 Hardware; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9241 Power Board; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9242 CT; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9243 CTscale; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9244 Bypass; blank values remainunfilled

Appendix 1 menu list; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: 924 Hardware; displayed association 9245 Thyristor; blank values remainunfilled

Shared source cells (coordinates refer to this table):

Appendix 1 menu list — PDF page 167

Source row Menu number Menu parameter Default settings Modbus Inst. DeviceNet no. Fieldbus format Modbus format Notes
1 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31044 UInt UInt ⟦blank source cell⟧
2 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 31045 UInt UInt ⟦blank source cell⟧
3 923 Unit Name 0 42301 UInt UInt ⟦blank source cell⟧
4 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42302 UInt UInt ⟦blank source cell⟧
5 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42303 UInt UInt ⟦blank source cell⟧
6 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42304 UInt UInt ⟦blank source cell⟧
7 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42305 UInt UInt ⟦blank source cell⟧
8 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42306 UInt UInt ⟦blank source cell⟧
9 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42307 UInt UInt ⟦blank source cell⟧
10 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42308 UInt UInt ⟦blank source cell⟧
11 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42309 UInt UInt ⟦blank source cell⟧
12 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42310 UInt UInt ⟦blank source cell⟧
13 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42311 UInt UInt ⟦blank source cell⟧
14 ⟦blank source cell⟧ ⟦blank source cell⟧ ⟦blank source cell⟧ 42312 UInt UInt ⟦blank source cell⟧
15 924 Hardware ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦null: no independent source value⟧ ⟦blank source cell⟧
16 9241 Power Board ⟦blank source cell⟧ 33101 UInt, 1=1 UInt ⟦blank source cell⟧
17 9242 CT ⟦blank source cell⟧ 33102 UInt, 1=1 UInt ⟦blank source cell⟧
18 9243 CTscale ⟦blank source cell⟧ 33105 Long, 1=1 EInt ⟦blank source cell⟧
19 9244 Bypass ⟦blank source cell⟧ 33103 UInt, 1=1 UInt ⟦blank source cell⟧
20 9245 Thyristor ⟦blank source cell⟧ 33104 UInt, 1=1 UInt ⟦blank source cell⟧

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 168

Manual reference: physical PDF page 168. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Appendix 2: Trip message

communication data

Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval.

Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Modbus Instance no/

DeviceNet no:: 810 → 31101-31154; 820 → 31201-31254; 830 → 31301-31354; 840 → 31401-31454; 850 → 31501-31554; 860 → 31601-31654; 870 → 31701-31754; 880 → 31801-31854; 890 → 31901-31954

Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Profibus slot/index: 810 → 121/245-122/43; 820 → 122/90-122/143; 830 → 122/190-122/243; 840 → 123/35-123/88; 850 → 123/135--123/188; 860 → 123/235-124/33; 870 → 124/80-124/133; 880 → 124/180-124/233; 890 → 125/25-125/78

Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Profinet IO index: 810 → 1101-1154; 820 → 1201-1254; 830 → 1301-1354; 840 → 1401-1454; 850 → 1501-1554; 860 → 1601-1654; 870 → 1701-1754; 880 → 1801-1854; 890 → 1901-1954

Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Fieldbus format shares source merged See respective parameter.

Appendix 2 trip communication mapping; software1.0X editionR0. Model, duty, units and communication register context retained. Blank, dash and merged regions distinct. Supplier source claims not engineering approval. Row group: Modbus format shares source merged See respective parameter.

Shared source cells (coordinates refer to this table):

Appendix 2 trip communication mapping — PDF page 168

Source row Protocol or format Source address ranges or format Source trip log list
1 Modbus Instance no/
DeviceNet no:
31101-31154
31201-31254
31301-31354
31401-31454
31501-31554
31601-31654
31701-31754
31801-31854
31901-31954
Trip log list
810
820
830
840
850
860
870
880
890
2 Profibus slot/index 121/245-122/43
122/90-122/143
122/190-122/243
123/35-123/88
123/135--123/188
123/235-124/33
124/80-124/133
124/180-124/233
125/25-125/78
Trip log list
810
820
830
840
850
860
870
880
890
3 Profinet IO index 1101-1154
1201-1254
1301-1354
1401-1454
1501-1554
1601-1654
1701-1754
1801-1854
1901-1954
Trip log list
810
820
830
840
850
860
870
880
890
4 Fieldbus format See respective parameter. ⟦null: no independent source value⟧
5 Modbus format ⟦null: no independent source value⟧ ⟦null: no independent source value⟧

Manual — BLANK_PAGE — page 169

Manual reference: physical PDF page 169. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

Source page content: Blank page visually confirmed. Reviewedtext: No engineering specifications or applicability inferred from coverillustrations or blankpagebodies. Originalimages andpages retained.

Manual — P036; model/duty, option, supply and edition-specific conditions govern. Navigation index is not proof of a feature. Warnings and source contradictions preserved. — page 170

Manual reference: physical PDF page 170. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.

CG Drives & Automation Sweden AB

Mörsaregatan 12

Box 222 25

SE-250 24 Helsingborg

Sweden

T +46 42 16 99 00

F +46 42 16 99 49

www.emotron.com/www.cgglobal.com

CG Drives & Automation, 01-5980-01r0, 2013-05-13

Selection checks and source differences

Website repeats MSF facts despite linking TSA manual. TSA guide built from named TSA sources; product naming/identity remains supplier clarification.

TSA catalogue246/340mm versus manual246/296mm size1 total height. Control supply+10%/-15% versus±10%. No edition reconciliation by inference.

Catalogue broad16–820/1000–1800A feature groups exceed detailed16–450 schedule. Do not invent larger-model ratings or dimensions.

TSA cULus logo Pending retained; source part options, response times and slot counts are conditional. MSF hardware/terminals not substituted.

Shared EmoSoftCom section header says MSF but text says TSA. Menu/example/communication differences remain in source context and local exception ledger.

Product documents