TECO A510s Enhanced — Advanced Current Vector Control
Our A510s Enhanced drive brings speed, torque and position control together for demanding industrial equipment. We support applications such as cranes, lifts, presses, extruders, winding systems and machine tools, with motor tuning, PLC and PID functions to help match the drive to the job.
Choose the drive around the motor and duty
Our Australian range page identifies 400 V and 690 V, IP20 and IP00 configurations. The family catalogue and manual also cover other voltage classes. Their wider schedules are reference material, not a promise that every model is locally stocked. Select the exact voltage, output current, enclosure and duty before comparing kW or HP labels.
The collected website has 23 selection rows, with 45 PDF memberships and 44 distinct technical PDFs. A shared filter drawing appears once with its associations. One additional linked datasheet, A510-4075-SG3F-IP20-Enhanced, was unavailable in the collection. We retain that gap rather than substitute another rating.
Heavy duty is the source default. The catalogue gives 150% rated current for 60 seconds and 200% for 2 seconds in HD, and 120% for 60 seconds in ND. These overload allowances are different from the 200% starting torque at 0.5 Hz claim. The manual restricts ND to V/F and V/F+PG; do not apply ND ratings to every control mode. Select by motor current and apply carrier-frequency, ambient and altitude derating.
Motor control and commissioning
The Enhanced catalogue lists V/F, V/F+PG, SLV, SLV2, SV, PMSV and PMSLV, covering induction and permanent-magnet motor applications subject to the selected mode and feedback hardware. Our website says six modes; the Enhanced brochures say seven. We keep the edition distinction. Rotational, static and stator-resistance tuning have different conditions; choose the method for the connected motor and load.
The source distinguishes SLV starting torque at 0.5 Hz from SV holding torque. Its headline frequency range reaches 599 Hz, but the manual gives lower SLV limits by drive capacity. Neither the headline nor a torque curve authorises an unreviewed motor speed or lifting duty. Four-quadrant control is not by itself a line-regenerative power-supply specification.
Use the motor nameplate, duty and full commissioning procedure. The reference sections retain parameters for V/F patterns, feedback, torque and position control, droop, traverse, PID, PLC, motor switching, restart, protection, communications, tuning and diagnostics. Example displays and factory defaults are not recommended settings for your installation.
Integration, keypads and options
We provide built-in RS-485 Modbus communications through the specified terminals/RJ45 interface; it is not an Ethernet port simply because it uses RJ45. The source options include communications, feedback, I/O and DC 24 V control-power cards. Match the card, slot, firmware and motor feedback type before ordering.
Our local page describes an LCD keypad; the broader catalogue lists an LED display with LCD as an option, and RTC on the Enhanced LCD type. Confirm the supplied operator. PTC input, parameter locking, fault history, operating-hours monitoring and Soft PWM support commissioning and maintenance. Capacitor-life monitoring is described for software above V1.48; it is a maintenance indication, not a guaranteed remaining-life prediction.
The local page specifies a built-in EMC filter through 45 kW, with external options above that. Individual filter and outline sheets remain configuration-specific. Braking transistors, external resistors, DC reactors and DCL terminals have model-dependent ranges and exceptions. Intelligent overvoltage suppression does not establish that every regenerative load can operate without an engineered braking arrangement.
Installation and environment
IP00 is an open-frame integration option; IP20 is not weatherproof. The manual specifies indoor installation protected from rain, moisture, corrosive gases, oil mist and dust. Its normal ambient limits are −10 to +40°C for IP20/IP21, and −10 to +50°C for IP00 or the stated cover-removed arrangement. Enhanced frame 5 has its own 50°C qualification. Operation up to 60°C requires the stated current derating; enclosure changes require the complete installation procedure.
The manual specifies no altitude derating below 1, 000 m and current derating above that to a stated maximum of 3, 000 m. Keep these conditions with the relevant model; do not combine independent limits into an assumed operating envelope. The catalogue's PCB feature says Class 3C2 while its general table says Class 3C3. Those claims remain separate and do not establish universal chemical resistance.
The dimension schedules distinguish frame, enclosure, filter and installation-kit versions. Thread sizes remain thread designations; dimensions and weights cannot be transferred between drawings sharing only a power rating. The FILTER 4040–4060(F5) / INV-A510S-IP20-05F drawing is not a universal A510s outline.
Safety functions and maintenance
Our source documents describe Safe Torque Off and associated safety standards. The manual's dedicated safety section controls model applicability, installation, testing and integration. STO does not isolate hazardous voltage or provide a mechanical holding brake. A catalogue statement is not a certificate for an entire machine.
Fire override deliberately overrides commands and suppresses software protections; the manual warns that operation may continue until hardware protection operates or the drive is damaged. It is a specifically engineered emergency function, not a normal reliability or protection mode. Use the full firmware-specific instructions and confirm the safety design with qualified personnel.
Before maintenance, isolate all relevant supplies, follow the specified discharge procedure and verify the electrical state. Follow the model-specific fan, capacitor, inspection and replacement guidance. The linked DriveLink software is retained as a download reference; no software was executed to establish these specifications.
Reading the documents
The two-page summary, 20-page Enhanced catalogue, 674-page V10 manual, quick setup guide and every collected technical PDF are represented below. The catalogue filename says 2025, but its printed footer says (EN)A510s_20230323. We preserve both. Reference tables retain source values, blank cells and conditions; drawing geometry, curves and complete wiring procedures remain in the original PDFs.
Our quick guide's forward/stop–reverse/stop heading conflicts with its RUN/STOP–REV/FWD figure labels. Obtain the confirmed circuit before wiring. Several individual datasheets also say 380–460 V in the title but include 480 V in their table. We have not silently widened or narrowed those ratings.
Catalogue — Cover identity — page 1
A510s-catalog-2025.pdf · P001 · source page 1
TECO A510s Enhanced — Advanced Current Vector Control Drive.
Context: Original filename says A510s-catalog-2025; rear-cover footer visibly prints (EN)A510s_20230323. Preserve both identifiers; do not infer a 2025 revision from filename.
Catalogue — Introduction — page 2
A510s-catalog-2025.pdf · P001 · source page 2
Super represents
Super technology
Super excellence
Super evolution uper
The super evolution of A510s made it debut which combined customer responses with Innovation.
Advanced current vector control inverter - A510s. Except the Auto-tuning and support for the PM
motor, the core computing of A510s raises to 60%. The all new technologies make our inverters
better. Please feel the charming of A510s.
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Catalogue — Feature overview — page 3
A510s-catalog-2025.pdf · P001 · source page 3
7 types of motor controls: A510s can support many industries such as elevator, crane and compressor
Auto-tuning support: Advanced Rotational、Static and Stator resistance Auto-tuning modes
Wide range of applications: Easily transfer to specific parameters for dedicated application 16 V/F curves for wide range of applications
High level sensor vector mode: Support to induction motor and permanent magnet motor A510s promotes motors to optimum condition
Much faster for computing ability: Dual core processors Faster computing ability, Larger ROM and RAM.
Conformity to global standards: CE / cUL / RCM / UKCA / RoHS Built-in Safety Torque Off(STO) function
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Catalogue — PM control, tuning and torque — page 4
A510s-catalog-2025.pdf · P001 · source page 4
Core
computing
ROM
RAM
Raise 60 %
Raise 100%
Raise 530%
*Compare with A510
Simple parameter settings for permanent magnet motors control.
PM Motor Control
Surface Permanent Magnet Motor (SPM)
-Highly Efficient -Compact Size -Low Cogging Torque
Interior Permanent Magnet Motor (IPM)
-Highly Efficient -Compact Size -With Reluctance Torque
200% @0.5Hz Starting Torque
Conformity to RoHS directive and international recognized certification.
A510s is loaded with 5th generation kernel has the most advanced motor tuning function to build accurate motor equivalent model automatically.
Optimized current vector control performance provides faster commissioning.
New core processors and better computing ability
Sensor Vector Mode (SV) can output 200% holding torque. Motor Equivalent Circuit
Advanced Auto-Tuning
More Powerful in Core Computing
Conformity to Global Standards
Id
Iq
Lm
Ls R1
R2
s
s : Slip
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Motor Speed (4 poles induction motor)
0.5 Hz
1 Hz
3 Hz
5 Hz
10 Hz
20 Hz
30 Hz
40 Hz
50 Hz
60 Hz
Torque(%)
Kernel
SensorLess Vector (SLV) control mode achieves incredible 200% torque performance at extreme low speed (0.5Hz), and provides stable and reliable motor control for wide range of applications.
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Context: Torque graph: Torque(%) versus Motor Speed (4 poles induction motor); curves 0.5,1,3,5,10,20,30,40,50,60 Hz. SLV 200% at 0.5 Hz and SV 200% holding torque are distinct claims. No graph values inferred.
Context: Computing comparison against A510: core +60%, ROM +100%, RAM +530%. Historical supplier claims.
Table conditions: Source tuning conditions; motor equivalent circuit is illustrative.
Multiple auto-tuning modes — PDF page 4
| Mode | Printed load condition |
|---|---|
| Rotational mode | When the load can be uncoupled |
| Static mode | When the load can not be uncoupled |
| Static resistance measurement mode | When the motor cable is too long |
Catalogue — Design and monitoring — page 5
A510s-catalog-2025.pdf · P001 · source page 5
Instant energy recharge, DC voltage rise
Intelligent Over Voltage Suppression
Traditional PWM output
Soft PWM output
Vpn
lu
Intelligent Overvoltage Suppression
DC bus voltage
Suppress over voltage caused by regenerative loads and redirect regenerative energy back to the load. Intelligent overvoltage suppression will not only protect the drive but also no need for costly braking units.
Main Capacitor Life Monitoring
The main capacitor has a service life. Monitoring the deterioration status of the main capacitor and immediately notify the status to customers. For early to respond and to replace parts, to avoid temporary production interruptions. (This function is available above V1.48)
Fan Control and Quick Release
Lower noise and extend the life of fan.
Robust Design
PCB coating for all series to against harsh environment, to against harsh environ- ment, meet IEC 60721-3-3 Class 3C2 standard.
Motor Noise Reduction Technology
Exclusive Soft PWM control technology reduces the radio frequency interference and motor noise.
Multi-language Display
Parameters of multi-language display are essential for international product and minimize the language barrier.
Vibration-resistant structure -Wire cable for C/B and M/B
External heat sink for better cooling capability.
The air flow and all PCB board can be fully isolated to prevent any dust or oil mist penetrate.
Quick replaceable fan makes customers be easy to change it.
Soft PWM modulation method
Parameters 12-87 show the percentage of capacitor life.
More than 90% proactive alerts to notify customers.
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Catalogue — Expansion cards and STO — page 6
A510s-catalog-2025.pdf · P001 · source page 6
Without built-in STO
Power
Emergency stop switch Input contactor Emergency stop switch The contactor can be saved
With built-in STO
Support Communication Card/ IO Expansion Card/ DC24V Power Card
With integrated Safety Torque Off (STO) function, complies with: ● EN ISO 13849-1 Cat/PLd ● EN61508 SIL2 ● EN60204-1 Category 0 ● EN62061 SIL CL2
It can save contactor’s cost and install space, and provide quick and reliable protection.
Built-in STO function
Expansion Slot 1 (CN3)
For encoder feedback card installation. Please refer to accessories page for detail specification. If the motor with encode or resolver installed, by closed loop control, can provide better motor performance.
For DC24V power card installation. Catalog No .: JN5-PS-DC24V, to communicate with inverter, and setup or copy the parameter without using the main power.
Expansion Slot 1 (CN2)
For communication card installation. Please refer to accessories page for detail specification. It can improve the support of the upper controller communication protocol.
For IO expansion card installation. Catalog No .: JN5-IO-2DO1AI, to add one relay, one transistor and one analog output with -10V ~ 10V/ 4~20mA.
Safety Relay
Inverter
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Catalogue — Applications — page 7
A510s-catalog-2025.pdf · P001 · source page 7
The Complete Motor Control Solution with powers for a wide range of applications
Gravitational Handling Equipment | Crane, Elevator
Metal Processing Machine | Press, Lathes
Plastics/Rubber Processing Machine | Extruder, Injection Molding Machine
Tension Control Equipment | Printing Machine, Reeling Machine
Textile Machine | Dyeing and Finishing Machine
Wire/Cable Making Machine | Wire Drewing Machine
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Catalogue — Selection guide and catalogue number identification — page 8
A510s-catalog-2025.pdf · P001 · source page 8
Dual rating design: normal duty overload up to 120% for 60 sec; heavy duty up to 150% for 60 sec and 200% for 2 sec.
ND examples include fans, pumps and HVAC. Printed example selects A510-2002-S□ for a 3 HP pump, parameter 00-27=1; motor parameters need adjustment. HD examples include lifts, press and machine tools; printed example A510-2015-S□3 for a 15 HP conveyor, parameter 00-27=0.
Context: Blank cells are explicitly retained as [not printed], not zero or unavailable. Models with □ and (F) retain literal catalogue notation; no order codes generated. Selection values remain separate from basic specifications where they differ.
Table conditions: Source row labels apply across four columns. The 250/270 HP row and all empty cells are retained literally; no interpolation. This is the selection guide, not a reconciled master rating.
Table conditions: Code legend is source context only; 575V/690V appear in legend, not the normalized 200V/400V rating tables. Do not infer ratings or availability for those classes.
Selection matrix — PDF page 8
| Maximum motor HP | Maximum motor kW | 200V 3-phase ND model | 200V ND current A (printed) | 200V 3-phase HD model | 200V HD current A (printed) | 400V 3-phase ND model | 400V ND current A (printed) | 400V 3-phase HD model | 400V HD current A (printed) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 0.75 | [not printed] | [not printed] | A510-2001-S□ | 5A | [not printed] | [not printed] | A510-4001-S□3(F) | 3.4A |
| 1.5 | 1.1 | A510-2001-S□ | 6A | [not printed] | [not printed] | [not printed] | [not printed] | [not printed] | [not printed] |
| 2 | 1.5 | [not printed] | [not printed] | A510-2002-S□ | 8A | A510-4001-S□3(F) | 4.1A | A510-4002-S□3(F) | 4.2A |
| 3 | 2.2 | A510-2002-S□ | 9.6A | A510-2003-S□ | 11A | A510-4002-S□3(F) | 5.4A | A510-4003-S□3(F) | 5.5A |
| 5 | 3.7 | A510-2003-S□ | 12A | A510-2005-S□3 | 17.5A | A510-4003-S□3(F) | 6.9A | A510-4005-S□3(F) | 9.2A |
| 7.5 | 5.5 | A510-2005-S□3 | 22A | A510-2008-S□3 | 25A | A510-4005-S□3(F) | 12.1A | A510-4008-S□3(F) | 14.8A |
| 10 | 7.5 | A510-2008-S□3 | 30A | A510-2010-S□3 | 33A | A510-4008-S□3(F) | 17.5A | A510-4010-S□3(F) | 18A |
| 15 | 11 | A510-2010-S□3 | 42A | A510-2015-S□3 | 47A | A510-4010-S□3(F) | 23A | A510-4015-S□3(F) | 24A |
| 20 | 15 | A510-2015-S□3 | 56A | A510-2020-S□3 | 60A | A510-4015-S□3(F) | 31A | A510-4020-S□3(F) | 31A |
| 25 | 18.5 | A510-2020-S□3 | 69A | A510-2025-S□3 | 73A | A510-4020-S□3(F) | 38A | A510-4025-S□3(F) | 39A |
| 30 | 22 | A510-2025-S□3 | 80A | A510-2030-S□3 | 85A | A510-4025-S□3(F) | 44A | A510-4030-S□3(F) | 45A |
| 40 | 30 | A510-2030-S□3 | 110A | A510-2040-S□3 | 115A | A510-4030-S□3(F) | 58A | A510-4040-S□3(F) | 60A |
| 50 | 37 | A510-2040-S□3 | 138A | A510-2050-S□3 | 145A | A510-4040-S□3(F) | 73A | A510-4050-S□3(F) | 75A |
| 60 | 45 | A510-2050-S□3 | 169A | A510-2060-S□3 | 180A | A510-4050-S□3(F) | 88A | A510-4060-S□3(F) | 91A |
| 75 | 55 | A510-2060-S□3 | 200A | A510-2075-S□3 | 215A | A510-4060-S□3(F) | 103A | A510-4075-S□3 | 118A |
| 100 | 75 | A510-2075-S□3 | 250A | A510-2100-S□3 | 283A | A510-4075-S□3 | 145A | A510-4100-S□3 | 150A |
| 125 | 90 | A510-2100-S□3 | 312A | A510-2125-S□3 | 346A | A510-4100-S□3 | 168A | A510-4125-S□3 | 180A |
| 150 | 110 | A510-2125-S□3 | 400A | A510-2150-S□3 | 415A | A510-4125-S□3 | 208A | A510-4150-S□3 | 216A |
| 175 | 132 | A510-2150-S□3 | 450A | [not printed] | [not printed] | A510-4150-S□3 | 250A | A510-4175-S□3 | 260A |
| 215 | 160 | [not printed] | [not printed] | [not printed] | [not printed] | A510-4175-S□3 | 296A | A510-4215-S□3 | 295A |
| 250/270 | 200 | [not printed] | [not printed] | [not printed] | [not printed] | A510-4215-S□3 | 328A | A510-4270-S□3 | 380A |
| 300 | 220 | [not printed] | [not printed] | [not printed] | [not printed] | A510-4270-S□3 | 435A | A510-4300-S□3 | 450A |
| 335 | 250 | [not printed] | [not printed] | [not printed] | [not printed] | A510-4300-S□3 | 515A | [not printed] | [not printed] |
| 375 | 280 | [not printed] | [not printed] | [not printed] | [not printed] | [not printed] | [not printed] | A510-4375-S□3 | 523A |
| 425 | 315 | [not printed] | [not printed] | [not printed] | [not printed] | A510-4375-S□3 | 585A | A510-4425-S□3 | 585A |
Catalogue code components — PDF page 8
| Source label/context | Source value |
|---|---|
| Example printed components | A510 - 2 001 S E 3 F - B |
| Input voltage 2 | 200V Class |
| Input voltage 4 | 400V Class |
| Input voltage 5 | 575V Class |
| Input voltage 6 | 690V Class |
| Horse power code 001 | 1HP |
| Horse power code 425 | 425HP |
| S | A510s Series |
| Type E | Enhanced Type (LED Display) |
| Type G | Enhanced Type (LCD Display) |
| Power supply blank | Single/Three-Phase |
| Power supply 3 | Three-Phase |
| Noise filter blank | None |
| Noise filter F | Built-in |
| Others B | For 400V class 40HP, with built-in braking transistor model |
| Others X | For high humidity and high pollution environment |
Catalogue — Basic specifications and duty qualifications — page 9
A510s-catalog-2025.pdf · P001 · source page 9
Ratings based on standard 4-pole induction motor. Selected inverter must have a higher output current rating than the motor.
Default mode is HD. Set parameter 00-27 to 1 for ND; source says carrier frequency changes to 2kHz. HD defaults are in the carrier table. Above-default carrier settings may require derating in HD or ND.
Footnote 5: with SLV control and maximum frequency greater than 80Hz, carrier frequency range is 2–8kHz.
Context: Printed values retained independently of selection guide. Carrier table has overlapping 400V 60–175HP and 125HP rows; both retained without resolving precedence.
Table conditions: Physical merged cells for input and hardware/frame spans assigned only to visible capacity columns. HP/kW pairs split into explicitly labelled fields without conversion. These are capacity columns, not inferred model codes.
Table conditions: Shared rows printed for each voltage class; no inferred operating envelope beyond source.
Table conditions: Dashes and overlapping ranges retained literally. Footnote5 condition on SLV and frequency>80Hz retained separately; no automatic conflict resolution.
Basic rating grid transposed by capacity — PDF page 9
| Voltage class | Inverter capacity HP | HD rated kVA | HD current A | HD motor HP | HD motor kW | ND rated kVA | ND current A | ND motor HP | ND motor kW | Input voltage/phase/frequency | Braking transistor | DC reactor | Frame size |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 200V | 1 | 1.9 | 5 | 1 | 0.75 | 2.3 | 6 | 2 | 1.5 | Single/Three-Phase, 200V to 240V, 50/60Hz | Built-in | None | 1 |
| 200V | 2 | 3 | 8 | 2 | 1.5 | 3.7 | 9.6 | 3 | 2.2 | Single/Three-Phase, 200V to 240V, 50/60Hz | Built-in | None | 1 |
| 200V | 3 | 4.2 | 11 | 3 | 2.2 | 4.6 | 12 | 5 | 3.7 | Single/Three-Phase, 200V to 240V, 50/60Hz | Built-in | Option | 2 |
| 200V | 5 | 6.7 | 17.5 | 5 | 3.7 | 8.4 | 22 | 7.5 | 5.5 | Three-Phase, 200V to 240V, 50/60Hz | Built-in | Option | 2 |
| 200V | 7.5 | 9.5 | 25 | 7.5 | 5.5 | 11.4 | 30 | 10 | 7.5 | Three-Phase, 200V to 240V, 50/60Hz | Built-in | Option | 2 |
| 200V | 10 | 12.6 | 33 | 10 | 7.5 | 16.0 | 42 | 15 | 11 | Three-Phase, 200V to 240V, 50/60Hz | Built-in | Option | 3 |
| 200V | 15 | 17.9 | 47 | 15 | 11 | 21.3 | 56 | 20 | 15 | Three-Phase, 200V to 240V, 50/60Hz | Built-in | Option | 4 |
| 200V | 20 | 22.9 | 60 | 20 | 15 | 26.3 | 69 | 25 | 18.5 | Three-Phase, 200V to 240V, 50/60Hz | Built-in | Option | 4 |
| 200V | 25 | 27.8 | 73 | 25 | 18.5 | 30.1 | 80 | 30 | 22 | Three-Phase, 200V to 240V, 50/60Hz | Built-in | Option | 4 |
| 200V | 30 | 32.4 | 85 | 30 | 22 | 41.9 | 110 | 40 | 30 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Option | 5 |
| 200V | 40 | 43.8 | 115 | 40 | 30 | 52.6 | 138 | 50 | 37 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Option | 5 |
| 200V | 50 | 55.3 | 145 | 50 | 37 | 64.4 | 169 | 60 | 45 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Built-in | 6 |
| 200V | 60 | 68.6 | 180 | 60 | 45 | 76.2 | 200 | 75 | 55 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Built-in | 6 |
| 200V | 75 | 81.9 | 215 | 75 | 55 | 95.3 | 250 | 100 | 75 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Built-in | 7 |
| 200V | 100 | 108 | 283 | 100 | 75 | 118.9 | 312 | 125 | 90 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Built-in | 7 |
| 200V | 125 | 132 | 346 | 125 | 90 | 152.4 | 400 | 150 | 110 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Built-in | 8 |
| 200V | 150 | 158 | 415 | 150 | 110 | 172 | 450 | 175 | 130 | Three-Phase, 200V to 240V, 50/60Hz | Option (Braking Module) | Built-in | 8 |
| 400V | 1 | 2.6 | 3.4 | 1 | 0.75 | 3.1 | 4.1 | 2 | 1.5 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | None | 1 |
| 400V | 2 | 3.2 | 4.2 | 2 | 1.5 | 4.1 | 5.4 | 3 | 2.2 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | None | 1 |
| 400V | 3 | 4.2 | 5.5 | 3 | 2.2 | 5.3 | 6.9 | 5 | 3.7 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | None | 1 |
| 400V | 5 | 7 | 9.2 | 5 | 3.7 | 9.2 | 12.1 | 7.5 | 5.5 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | Option | 2 |
| 400V | 7.5 | 11.3 | 14.8 | 7.5 | 5.5 | 13.3 | 17.5 | 10 | 7.5 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | Option | 2 |
| 400V | 10 | 13.7 | 18 | 10 | 7.5 | 17.5 | 23 | 15 | 11 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | Option | 3 |
| 400V | 15 | 18.3 | 24 | 15 | 11 | 23.6 | 31 | 20 | 15 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | Option | 3 |
| 400V | 20 | 23.6 | 31 | 20 | 15 | 29.0 | 38 | 25 | 18.5 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | Option | 3 |
| 400V | 25 | 29.7 | 39 | 25 | 18.5 | 33.5 | 44 | 30 | 22 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | Option | 4 |
| 400V | 30 | 34.3 | 45 | 30 | 22 | 44.2 | 58 | 40 | 30 | Three-Phase, 380V to 480V, 50/60Hz | Built-in | Option | 4 |
| 400V | 40 | 45.7 | 60 | 40 | 30 | 55.6 | 73 | 50 | 37 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Option | 5 |
| 400V | 50 | 57.2 | 75 | 50 | 37 | 67.1 | 88 | 60 | 45 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Option | 5 |
| 400V | 60 | 69.3 | 91 | 60 | 45 | 78.5 | 103 | 75 | 55 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Option | 5 |
| 400V | 75 | 89.9 | 118 | 75 | 55 | 111 | 145 | 100 | 75 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Option | 5 |
| 400V | 100 | 114 | 150 | 100 | 75 | 128 | 168 | 125 | 90 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 6 |
| 400V | 125 | 137 | 180 | 125 | 90 | 159 | 208 | 150 | 110 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 6 |
| 400V | 150 | 165 | 216 | 150 | 110 | 191 | 250 | 175 | 132 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 7 |
| 400V | 175 | 198 | 260 | 175 | 132 | 226 | 296 | 215 | 160 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 7 |
| 400V | 215 | 225 | 295 | 215 | 160 | 250 | 328 | 250 | 185 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 7 |
| 400V | 270 | 290 | 380 | 270 | 200 | 332 | 435 | 300 | 220 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 8 |
| 400V | 300 | 343 | 450 | 300 | 220 | 393 | 515 | 375 | 280 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 8 |
| 400V | 375 | 400 | 523 | 375 | 280 | 446 | 585 | 425 | 315 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 8 |
| 400V | 425 | 461 | 585 | 425 | 315 | 446 | 585 | 425 | 315 | Three-Phase, 380V to 480V, 50/60Hz | Option (Braking Module) | Built-in | 8 |
Shared electrical specifications — PDF page 9
| Source label/context | Source value |
|---|---|
| 200V maximum output voltage | Three-Phase, 200V to 240V |
| 400V maximum output voltage | Three-Phase, 380V to 480V |
| Maximum output frequency | Based on parameter setting 0.1–599Hz |
| Allowable voltage fluctuation | −15% to +10% |
| Allowable frequency fluctuation | ±5% |
HD carrier frequency table — PDF page 9
| 200V capacity | 400V capacity | HD carrier range | HD carrier default |
|---|---|---|---|
| 1–20HP | 1–30HP | 2–16kHz | 8kHz |
| 25HP | – | 2–12kHz | 6kHz |
| 30–40HP | 40–50HP | 2–12kHz [footnote 5] | 5kHz |
| 50–100HP | 60–175HP | 2–10kHz [footnote 5] | 5kHz |
| – | 125HP | 2–10kHz | 4kHz |
| – | 215HP | 2–8kHz | 3kHz |
| 125–150HP | – | 2–5kHz | 5kHz |
| – | 270–375HP | 2–5kHz | 4kHz |
| – | 425HP | 2–5kHz | 2kHz |
Catalogue — Wiring annotations and notes — page 10
A510s-catalog-2025.pdf · P001 · source page 10
Wiring Diagram
Notes:
*1: Models 200V 1~25HP and 400V 1~30HP or lower ratings have a built-in braking transistor. To use this braking transistor a braking resistor can be connected between B1 and B2 .Besides, for 400V class 40HP, there is built-in braking transistor model, but without DCL terminals.
*2: Use SW6 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function digital input terminals S1~S8.
*3: Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2 (Al2). Besides please also check parameter 04-00 for proper setting.
*4: Run Permissive input SF1 and SF2 is a normally closed input. This input should be closed to enable the inverter output. To activate this input remove the jumper wire between SF1/ SF2 and SG.
*5: When using the open collector for pulse input, it doesn't need resistance because of built-in pull-up resistance.
*6: AO1/AO2 default setting is 0~+10V.
*7: Both 200V class 50HP~150HP and 400V class 100HP~425HP have built-in DC reactors.
*8: It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel connection.
*9: Only the model 200V 3~40HP and 400V 5~75HP provide P1 and P2 terminal,for external DCL connected between P1 and P2, P1 and P2 are short-circuited before shipping out from the factory.
MC NFB
P2/B1 B2
R/L1 S/L2
S1
S2
S8
S7
S6
S5
S4
S3
Analog output 1
24V Digital signal power terminal (PNP)
24VG Digital signal common (NPN)
Jog command
External base block
Source(PNP) SW6
AO1
AO2
GND
E
CN3
T/L3
U/T1 V/T2 W/T3
CN6 (RJ45)
Pulse Input
Connection terminal of shielding wire
GND Analog Signal Common
+10V Power for Analog Input +10V, 20mA
P
DOG
PI
PO
-10V Power for Analog Input
IM
R2C
R1A
R1B
R1C
R2A
SG
SF2 Run Permissive Input
32K Hz. Max.
AC input voltage
Default Setting
External Analog Inputs
-10V~0~10V/ 4~20mA
4~20mA/0~10V
0V
Grounding resistance should lower than 100Ω
Analog output 1, 2 AO1 DC 0~10V/4~20mA AO2 DC 0~10V/4~20mA
Option PG encoder card or DC24V power card
Multi-Function Relay Output 250VAC <1A 30VDC <1A
Multi-Functional transistor Digital Outputs (DC 48V/50mA, Open Collector)
Multi-function pulse output 32k Hz. Max. GND
DO1
*2
*1
*4
RS485
1 : S(+) 2 : S(-) 3 : S(+) 4 : Reserved 5 : Reserved 6 : S(-) 7 : 5V 8 : GND
*5
S(+)
P S(-)
V V V V
I I I I
*3
ON
OFF
SW5 *8
P1
Option comm. card or I/O expansion card CN2
AO1 AO2 AI1 AI2
SW1 SW2 SW3 SW4
SF1
*6
*9 Braking resistor
Fast acting fuse
Forward rotation/stop
Sink(NPN), Default setting
Analog output 2 Reverse rotation/stop
Multi-step speed command 1 Multi-step speed command 2 Multi-step speed command 3
Fault reset
Multi-Functional Digital Inputs
Screened Cable, Terminal symbol
Screened Cable, Twisted Pair P
Indicates main circuit
Indicates control circuit
AI1 — Multi-Function Analog Input: -10~10V/0~10V, 500KΩ; 4~20mA, 500Ω.
AI2 — Multi-Function Analog Input: 0~10V, 900KΩ; 4~20mA, 250Ω.
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Context: Wiring text retained as source annotations only. All nine notes qualify the drawing, including DCL terminal ranges, braking exception, sink/source, run-permissive jumper, RS485 termination and analog defaults. Original diagram remains installation authority; no topology reconstructed.
Context: Default adjacent diagram labels: S1 forward rotation/stop; S2 reverse rotation/stop; S3/S4/S5 multi-step speed commands 1/2/3; S6 fault reset; S7 jog command; S8 external base block. This transcribes label association only, not wiring topology.
Catalogue — General specifications — page 11
A510s-catalog-2025.pdf · P001 · source page 11
Notes: *1. Speed control accuracy will be influenced when the motor and installation condition are different.
General Specifications
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Table conditions: A510s general specifications. Retain duty, model, temperature and enclosure qualifications. Certification is historical supplier claim, not current verification.
Control characteristics — PDF page 11
| Parameter / source label | Printed specification |
|---|---|
| Display | LED keypad with 5-digits seven-segment display (LCD keypad option) |
| Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) |
| Output Frequency | 0.01~599.00Hz (If need higher output frequency, please contact with TECO business staff) |
| Frequency Accuracy | Digital references: ±0.01%(-10 to +40°C), Analog references: ±0.1% (25°C ±10°C) |
| Speed Control Accuracy *1 | ±0.1%(Sensor Vector Control Mode, SV),±0.5%(Sensorless Vector Control Mode, SLV) |
| Frequency Setting Resolution | Digital References:0.01Hz, Analog References: 0.03Hz at 60Hz |
| Output Frequency Resolution | 0.01Hz |
| Overload Tolerance | Heavy Duty Mode (HD.):150% rated current for 60sec, 200% rated current for 2 sec. (Factory default) Normal Duty Mode (ND.):120% rated current for 60sec |
| Frequency Setting Signal | 0 to +10V, -10V to +10V, 4 to 20mA or pulse train input |
| Acceleration / Deceleration Time | 0.0∼6000.0 sec (separately set acceleration and deceleration time ) |
| Voltage / Frequency Characteristics | 15 fixed and one customized v/f pattern |
| Braking Torque | Approximate 20% (Built-in braking transistors under 200V 25HP and 400V 40HP) |
| Main Control Functions | Auto-tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two Analog Output, Safety input contact |
| Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type |
| Efficiency | Meet IEC/EN 61800-9-2 IE2 Class |
Protection functions — PDF page 11
| Parameter / source label | Printed specification |
|---|---|
| Stall Prevention | Current level can be adjusted.(In acceleration or constant speed,it can be set separately. In deceleration,it can be set with or without stall protection) |
| Over Current (OC) and Output Short-Circuit (SC) Protection | It stops when the current exceeds 200% of the inverter rated current. |
| Inverter Overload Protection (OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Mode (HD.):150% rated current for 60sec, 200% rated current for 2 sec. (Factory default), Carrier frequency is from 2kHz to 8kHz. Normal Duty Mode (ND.):120% rated current for 60sec, Carrier frequency is 2kHz. |
| Motor Overload Protection (OL1) | Electrical overload protection curve |
| Over Voltage Protection (OV) | If the main circuit DC voltage is over 410V (200V class) / 820V (400V class), the motor stops running. |
| Under Voltage (UV) | If the main circuit DC voltage is under 190V (200V class) / 380V (400V class), the motor stops running. |
| Momentary Power Loss Restart | Power loss exceeds 15ms You can set the function of momentary power loss restart to up to 2 sec |
| Overheat Protection (OH) | Thermistor sensor on heatsink |
| Ground Fault Protection (GF) | Protection by current detection circuit |
| Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on. |
| Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically |
| Short-circuit Current Rating(SCCR) | Per UL 508C,the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms)when protected by fuses given in the fuse table |
Environment specification — PDF page 11
| Parameter / source label | Printed specification |
|---|---|
| Location | Indoor (Protected from corrosive gases and dust) |
| Ambient Temperature | -10~+40°C (IP20/IP21), -10~50°C (IP00 or top anti-dust cover removed), with de-rating, the maximum is 60°C. (Frame 5 is 50°C without de-rating) |
| Storage Temperature | -20~+70°C |
| Humidity | 95%RH or less ( no condensation ) |
| Altitude and Vibration | Altitude of 1000 meters or lower ; 1.0G, in compliance with IEC 60068-2-6 |
| Pollution Degree | Meet IEC 60721-3-3 Class 3C3 |
Communication and electromagnetic functions — PDF page 11
| Parameter / source label | Printed specification |
|---|---|
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) |
| Electromagnetic Interference (EMI) | In compliance with EN61800-3 standard, 400V 60HP or below can be built-in. |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard |
Certification source claims — PDF page 11
| Parameter / source label | Printed specification |
|---|---|
| CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1(LVD) |
| UKCA | In compliance with BS EN61800-3 (CE/RE) and BS EN61800-5-1 (LVD) |
| UL | UL508C |
Catalogue — Dimensions and enclosure variants — page 12
A510s-catalog-2025.pdf · P001 · source page 12
Context: Only labelled dimension tables normalized. Original drawing defines geometry and mounting orientation. M5/M6/M8/M10/M12 are thread designations, not millimetre values. Catalog suffix □ retained; shared cells assigned only within physical table groups.
Table conditions: Literal table values; net weight is not shipping weight. Same catalogue notation can occur in separate enclosure/figure groups with different values. No inferred model interchangeability.
Dimension table — PDF page 12
| Figure | Enclosure | Frame | Catalog No. | W mm | H mm | D mm | W1 mm | H1 mm | t mm | d thread | Net weight kg |
|---|---|---|---|---|---|---|---|---|---|---|---|
| A | IP20 | 1 | A510-2001-S□ | 130 | 215 | 150 | 118 | 203 | 5 | M5 | 2.2 |
| A | IP20 | 1 | A510-2002-S□ | 130 | 215 | 150 | 118 | 203 | 5 | M5 | 2.2 |
| A | IP20 | 1 | A510-4001-S□3 | 130 | 215 | 150 | 118 | 203 | 5 | M5 | 2.2 |
| A | IP20 | 1 | A510-4002-S□3 | 130 | 215 | 150 | 118 | 203 | 5 | M5 | 2.2 |
| A | IP20 | 1 | A510-4003-S□3 | 130 | 215 | 150 | 118 | 203 | 5 | M5 | 2.2 |
| B | IP20 | 2 | A510-2003-S□ | 140 | 279 | 181 | 122 | 267 | 1.2 | M6 | 3.8 |
| B | IP20 | 2 | A510-2005-S□3 | 140 | 279 | 181 | 122 | 267 | 1.2 | M6 | 3.8 |
| B | IP20 | 2 | A510-2008-S□3 | 140 | 279 | 181 | 122 | 267 | 1.2 | M6 | 3.8 |
| B | IP20 | 2 | A510-4005-S□3 | 140 | 279 | 181 | 122 | 267 | 1.2 | M6 | 3.8 |
| B | IP20 | 2 | A510-4008-S□3 | 140 | 279 | 181 | 122 | 267 | 1.2 | M6 | 3.8 |
| B | IP20 | 3 | A510-2010-S□3 | 210 | 300 | 215 | 192 | 286 | 1.6 | M6 | 6.2 |
| B | IP20 | 3 | A510-4010-S□3 | 210 | 300 | 215 | 192 | 286 | 1.6 | M6 | 6.2 |
| B | IP20 | 3 | A510-4015-S□3 | 210 | 300 | 215 | 192 | 286 | 1.6 | M6 | 6.2 |
| B | IP20 | 3 | A510-4020-S□3 | 210 | 300 | 215 | 192 | 286 | 1.6 | M6 | 6.2 |
| B | IP20 | 4 | A510-2015-S□3 | 265 | 500 | 225 | 245 | 340 | 1.6 | M8 | 10 |
| B | IP20 | 4 | A510-2020-S□3 | 265 | 500 | 225 | 245 | 340 | 1.6 | M8 | 10 |
| B | IP20 | 4 | A510-2025-S□3 | 265 | 500 | 225 | 245 | 340 | 1.6 | M8 | 10 |
| B | IP20 | 4 | A510-4025-S□3 | 265 | 500 | 225 | 245 | 340 | 1.6 | M8 | 10 |
| B | IP20 | 4 | A510-4030-S□3 | 265 | 500 | 225 | 245 | 340 | 1.6 | M8 | 10 |
| C | IP20 | 5 | A510-2030-S□3 | 286.5 | 525 | 272 | 160 | 505 | 3.3 | M8 | 24 |
| C | IP20 | 5 | A510-2040-S□3 | 286.5 | 525 | 272 | 160 | 505 | 3.3 | M8 | 24 |
| C | IP20 | 5 | A510-4040-S□3 | 286.5 | 525 | 272 | 160 | 505 | 3.3 | M8 | 24 |
| C | IP20 | 5 | A510-4050-S□3 | 286.5 | 525 | 272 | 160 | 505 | 3.3 | M8 | 24 |
| C | IP20 | 5 | A510-4060-S□3 | 286.5 | 525 | 272 | 160 | 505 | 3.3 | M8 | 24 |
| C | IP20 | 5 | A510-4075-S□3 | 286.5 | 525 | 272 | 160 | 505 | 3.3 | M8 | 24 |
| C | IP20 | 5 | A510-4040-S□3-B | 286.5 | 525 | 252 | 160 | 505 | 3.3 | M8 | 24 |
Catalogue — Dimensions and enclosure variants — page 13
A510s-catalog-2025.pdf · P001 · source page 13
Context: Only labelled dimension tables normalized. Original drawing defines geometry and mounting orientation. M5/M6/M8/M10/M12 are thread designations, not millimetre values. Catalog suffix □ retained; shared cells assigned only within physical table groups.
Table conditions: Literal table values; net weight is not shipping weight. Same catalogue notation can occur in separate enclosure/figure groups with different values. No inferred model interchangeability.
Dimension table — PDF page 13
| Figure | Enclosure | Frame | Catalog No. | W mm | H mm | D mm | W1 mm | H1 mm | t mm | d thread | Net weight kg |
|---|---|---|---|---|---|---|---|---|---|---|---|
| D | IP00 | 6 | A510-2050-S□3 | 344 | 580 | 300 | 250 | 560 | 3.2 | M8 | 40 |
| D | IP00 | 6 | A510-2060-S□3 | 344 | 580 | 300 | 250 | 560 | 3.2 | M8 | 40 |
| D | IP00 | 6 | A510-4100-S□3 | 344 | 580 | 300 | 250 | 560 | 3.2 | M8 | 40 |
| D | IP00 | 6 | A510-4125-S□3 | 344 | 580 | 300 | 250 | 560 | 3.2 | M8 | 40 |
| E | IP20 | 6 | A510-2050-S□3 | 348.5 | 740 | 300 | 250 | 560 | 3.2 | M8 | 44 |
| E | IP20 | 6 | A510-2060-S□3 | 348.5 | 740 | 300 | 250 | 560 | 3.2 | M8 | 44 |
| E | IP20 | 6 | A510-4100-S□3 | 348.5 | 740 | 300 | 250 | 560 | 3.2 | M8 | 44 |
| E | IP20 | 6 | A510-4125-S□3 | 348.5 | 740 | 300 | 250 | 560 | 3.2 | M8 | 44 |
| D | IP00 | 7 | A510-2075-S□3 | 459 | 790 | 324.5 | 320 | 760 | 4.2 | M10 | 74 |
| D | IP00 | 7 | A510-2100-S□3 | 459 | 790 | 324.5 | 320 | 760 | 4.2 | M10 | 74 |
| D | IP00 | 7 | A510-4150-S□3 | 459 | 790 | 324.5 | 320 | 760 | 4.2 | M10 | 74 |
| D | IP00 | 7 | A510-4175-S□3 | 459 | 790 | 324.5 | 320 | 760 | 4.2 | M10 | 74 |
| D | IP00 | 7 | A510-4215-S□3 | 459 | 790 | 324.5 | 320 | 760 | 4.2 | M10 | 74 |
| E | IP20 | 7 | A510-2075-S□3 | 463.5 | 1105 | 324.5 | 320 | 760 | 4.2 | M10 | 81 |
| E | IP20 | 7 | A510-2100-S□3 | 463.5 | 1105 | 324.5 | 320 | 760 | 4.2 | M10 | 81 |
| E | IP20 | 7 | A510-4150-S□3 | 463.5 | 1105 | 324.5 | 320 | 760 | 4.2 | M10 | 81 |
| E | IP20 | 7 | A510-4175-S□3 | 463.5 | 1105 | 324.5 | 320 | 760 | 4.2 | M10 | 81 |
| E | IP20 | 7 | A510-4215-S□3 | 463.5 | 1105 | 324.5 | 320 | 760 | 4.2 | M10 | 81 |
Catalogue — Dimensions and enclosure variants — page 14
A510s-catalog-2025.pdf · P001 · source page 14
IP00 is standard for frame6 to frame8. Purchase installation accessories when selecting IP20 enclosure.
Context: Only labelled dimension tables normalized. Original drawing defines geometry and mounting orientation. M5/M6/M8/M10/M12 are thread designations, not millimetre values. Catalog suffix □ retained; shared cells assigned only within physical table groups.
Table conditions: Literal table values; net weight is not shipping weight. Same catalogue notation can occur in separate enclosure/figure groups with different values. No inferred model interchangeability.
Table conditions: Source-required accessory association, not proof of inclusion with drive.
Dimension table — PDF page 14
| Figure | Enclosure | Frame | Catalog No. | W mm | H mm | D mm | W1 mm | W2 mm | H1 mm | t mm | d thread | Net weight kg |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| F | IP00 | 8 | A510-2125-S□3 | 690 | 1000 | 410 | 530 | 265 | 960 | 4.2 | M12 | 184 |
| F | IP00 | 8 | A510-2150-S□3 | 690 | 1000 | 410 | 530 | 265 | 960 | 4.2 | M12 | 184 |
| F | IP00 | 8 | A510-4270-S□3 | 690 | 1000 | 410 | 530 | 265 | 960 | 4.2 | M12 | 184 |
| F | IP00 | 8 | A510-4300-S□3 | 690 | 1000 | 410 | 530 | 265 | 960 | 4.2 | M12 | 184 |
| F | IP00 | 8 | A510-4375-S□3 | 690 | 1000 | 410 | 530 | 265 | 960 | 4.2 | M12 | 184 |
| F | IP00 | 8 | A510-4425-S□3 | 690 | 1000 | 410 | 530 | 265 | 960 | 4.2 | M12 | 184 |
| G | IP20 | 8 | A510-2125-S□3 | 692 | 1313 | 410 | 530 | 265 | 960 | 4.2 | M12 | 194 |
| G | IP20 | 8 | A510-2150-S□3 | 692 | 1313 | 410 | 530 | 265 | 960 | 4.2 | M12 | 194 |
| G | IP20 | 8 | A510-4270-S□3 | 692 | 1313 | 410 | 530 | 265 | 960 | 4.2 | M12 | 194 |
| G | IP20 | 8 | A510-4300-S□3 | 692 | 1313 | 410 | 530 | 265 | 960 | 4.2 | M12 | 194 |
| G | IP20 | 8 | A510-4375-S□3 | 692 | 1313 | 410 | 530 | 265 | 960 | 4.2 | M12 | 194 |
| G | IP20 | 8 | A510-4425-S□3 | 692 | 1313 | 410 | 530 | 265 | 960 | 4.2 | M12 | 194 |
IP20 installation accessories — PDF page 14
| Frame | Accessory |
|---|---|
| 6 | JN5-NK-A06 |
| 7 | JN5-NK-A07 |
| 8 | JN5-NK-A08 |
Catalogue — Dimensions and enclosure variants — page 15
A510s-catalog-2025.pdf · P001 · source page 15
Context: Only labelled dimension tables normalized. Original drawing defines geometry and mounting orientation. M5/M6/M8/M10/M12 are thread designations, not millimetre values. Catalog suffix □ retained; shared cells assigned only within physical table groups.
Table conditions: Literal table values; net weight is not shipping weight. Same catalogue notation can occur in separate enclosure/figure groups with different values. No inferred model interchangeability.
Dimension table — PDF page 15
| Figure | Enclosure | Frame | Catalog No. | W mm | H mm | D mm | W1 mm | H1 mm | H2 mm | t mm | d thread | Net weight kg |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| H | IP20 | 1 | A510-4001-S□3F | 130 | 306 | 150 | 118 | 203 | 215 | 5 | M5 | 3.5 |
| H | IP20 | 1 | A510-4002-S□3F | 130 | 306 | 150 | 118 | 203 | 215 | 5 | M5 | 3.5 |
| H | IP20 | 1 | A510-4003-S□3F | 130 | 306 | 150 | 118 | 203 | 215 | 5 | M5 | 3.5 |
| H | IP20 | 2 | A510-4005-S□3F | 140 | 400 | 177 | 122 | 267 | 279 | 1.2 | M6 | 5.5 |
| H | IP20 | 2 | A510-4008-S□3F | 140 | 400 | 177 | 122 | 267 | 279 | 1.2 | M6 | 5.5 |
| I | IP20 | 3 | A510-4010-S□3F | 210 | 416.5 | 215 | 192 | 286 | 300 | 1.6 | M6 | 8.0 |
| I | IP20 | 3 | A510-4015-S□3F | 210 | 416.5 | 215 | 192 | 286 | 300 | 1.6 | M6 | 8.0 |
| I | IP20 | 4 | A510-4020-S□3F | 265 | 500 | 225 | 245 | 340 | 360 | 1.6 | M8 | 12.5 |
| I | IP20 | 4 | A510-4025-S□3F | 265 | 500 | 225 | 245 | 340 | 360 | 1.6 | M8 | 12.5 |
| I | IP20 | 4 | A510-4030-S□3F | 265 | 500 | 225 | 245 | 340 | 360 | 1.6 | M8 | 12.5 |
| J | IP20 | 5 | A510-4040-S□3F | 286.5 | 679 | 272 | 160 | 505 | 525 | 3.3 | M8 | 29.5 |
| J | IP20 | 5 | A510-4050-S□3F | 286.5 | 679 | 272 | 160 | 505 | 525 | 3.3 | M8 | 29.5 |
| J | IP20 | 5 | A510-4060-S□3F | 286.5 | 679 | 272 | 160 | 505 | 525 | 3.3 | M8 | 29.5 |
| J | IP20 | 5 | A510-4040-S□3-B | 286.5 | 679 | 252 | 160 | 505 | 525 | 3.3 | M8 | 29.5 |
Catalogue — Accessories — page 16
A510s-catalog-2025.pdf · P001 · source page 16
Accessories
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Table conditions: Explicit shared cells expanded with source bounds. Blank notes remain blank. Middle layer case depth additions and exception for encoder-only frames 2–4 retained, not universal drive dimensions.
Accessories — PDF page 16
| Accessory group | Description | Catalog No. | Note |
|---|---|---|---|
| Cables | IP20 Digital operator extention cable | JN5-CB-01M | 1 meter |
| Cables | IP20 Digital operator extention cable | JN5-CB-02M | 2 meter |
| Cables | IP20 Digital operator extention cable | JN5-CB-03M | 3 meter |
| Cables | IP20 Digital operator extention cable | JN5-CB-05M | 5 meter |
| Cables | RJ45 to USB connecting cable | JN5-CM-USB | 1.8 meter |
| Communication Gateways | Profibus DP module | JN5-CM-PDP | |
| Communication Gateways | TCP-IP module | JN5-CM-TCPIP | |
| Communication Gateways | DeviceNet module | JN5-CM-DNET | |
| Communication Gateways | CANopen module | JN5-CM-CAN | |
| Communication Gateways | EtherNet/IP module | JN5-CM-EIP | |
| Communication Cards | Profibus DP communication card | JN5-CMHI-PDP | |
| Communication Cards | CANopen communication card | JN5-CMHI-CAN | |
| Communication Cards | EtherCAT communication card | JN5-CMHI-ECAT | |
| Communication Cards | EtherNet/IP communication card | JN5-CMHI-EIP | |
| Bluetooth Keypad | For wireless remote connection to control the inverter, which can monitor the real-time status and diagnose faults quickly | JN5-OP-BTH | With the smartphone APP ”BT DriveLink”, it can be downloaded from Apple APP Store or Google Play |
| Digital & Analog IO Expansion Card | Add one relay output, one transistor, andone -10V~10V / 4~20mA analog input after installation. | JN5-IO-2DO1AI | |
| DC24V Power Card | Use DC24V to communicate with inverter, and setup or copy the parameter without using the main power after installation. | JN5-PS-DC24V | |
| NEMA1 Kits | Mechanical device consisting of anti- dust cover on the upper part and wiring box on the bottom to meet NEMA1 | JN5-NK-A06 | For Frame 6 |
| NEMA1 Kits | Mechanical device consisting of anti- dust cover on the upper part and wiring box on the bottom to meet NEMA1 | JN5-NK-A07 | For Frame 7 |
| NEMA1 Kits | Mechanical device consisting of anti- dust cover on the upper part and wiring box on the bottom to meet NEMA1 | JN5-NK-A08 | For Frame 8 |
| Digital Operators | IP20 LED type | JN5-OP-F01 | |
| Digital Operators | IP20 LCD type | JN5-OP-F02 | |
| Digital Operators | IP20 Blank type | JN5-OP-A03 | |
| Protective Cover | Positioned on both sides of the inverter to prevent unknown objects from invading | JN5-CR-A01 | For Frame 1 |
| Protective Cover | Positioned on both sides of the inverter to prevent unknown objects from invading | JN5-CR-A02 | For Frame 2 |
| Protective Cover | Positioned on both sides of the inverter to prevent unknown objects from invading | JN5-CR-A04 | For Frame 4 |
| Middle Layer Case | For encoder feedback card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install encoder feedback card, don't need middle layer case) (After installation,the Depth will add) | JN5-MD-A01 | For Frame 1,D+44mm |
| Middle Layer Case | For encoder feedback card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install encoder feedback card, don't need middle layer case) (After installation,the Depth will add) | JN5-MD-A02 | For Frame 2,D+31mm |
| Middle Layer Case | For encoder feedback card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install encoder feedback card, don't need middle layer case) (After installation,the Depth will add) | JN5-MD-A03 | For Frame 3,D+34mm |
| Middle Layer Case | For encoder feedback card/ communication card/ Digital & Analog IO Expansion Card/ DC24V power card installation (For frame 2~4, if only install encoder feedback card, don't need middle layer case) (After installation,the Depth will add) | JN5-MD-A04 | For Frame 4,D+35mm |
| Others | Copy Module for 510 series | JN5-CU |
Catalogue — Encoder feedback cards — page 17
A510s-catalog-2025.pdf · P001 · source page 17
Encoder Feedback Card
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Table conditions: Input/output types distinct. Preserve ERN1387 versus ECN1313, 13bits/8192, suffix -24 and open collector/line-driver distinctions.
Encoder feedback cards — PDF page 17
| Catalog No. | Encoder/Resolver input type | Output type |
|---|---|---|
| JN5-PG-O | Open collector feedback card | Open Collector |
| JN5-PG-L | Line driver speed feedback card | Line Driver |
| JN5-PG-L-24 | Line driver speed feedback card | Open Collector |
| JN5-PG-PM | Synchronous motor line driver speed feedback card | Line Driver |
| JN5-PG-PMR | Speed feedback card with TAMAGAWA Resolver | Line Driver |
| JN5-PG-PMS | Speed feedback card with Heidenhain ERN 1387 Encoder Sin-Cos Incremental Encoder | Line Driver |
| JN5-PG-PMS-24 | Speed feedback card with Heidenhain ERN 1387 Encoder Sin-Cos Incremental Encoder | Open Collector |
| JN5-PG-PMC | Speed feedback card with Heidenhain ECN 1313 Encoder 8192 (13bits) Absolute Encoder | Line Driver |
| JN5-PG-PMC-24 | Speed feedback card with Heidenhain ECN 1313 Encoder 8192 (13bits) Absolute Encoder | Open Collector |
Catalogue — Blank ruled notes page — page 18
A510s-catalog-2025.pdf · P001 · source page 18
This page contains no separately transcribed product values. The source page is blank.
Catalogue — Blank ruled notes page — page 19
A510s-catalog-2025.pdf · P001 · source page 19
This page contains no separately transcribed product values. The source page is blank.
Catalogue — Historical worldwide office directory — page 20
A510s-catalog-2025.pdf · P001 · source page 20
For more information, please visit TECO website.
(EN)A510s_20230323
TECO-Westinghouse Motor Company Texas 5100 N. IH 35, Round Rock, Texas 78681, USA Tel: +1-512-255-4141, +1-800-451-8798 Fax: +1-512-244-5512 Toll Free: 1-800-451-8798 Website: www.tecowestinghouse.com E-mail: sales@tecowestinghouse.com
TECO-Westinghouse Motor Company Inc. (Canada) 18060 - 109th Ave, Edmonton, Alberta T5S 2K2 Tel: +1-780-444-8933 Fax: +1-780-486-4575 24HR Emergency ph: +1(780)994-8964 Toll Free: +1-800-661-4023 Website: www.tecowestinghouse.ca E-mail: sales@tecowestinghouse.ca
TECO-Westinghouse Motor Company, S.A. de C.V. Zeta 408, Industrial Delta, Leon, Guanajuato, CP 37545 Tel: +52-472-723-8200 Contact: Victor Iniestra E-mail: ventas@tecowestinghouse.com
Motovario Ltd. Rushock Trading Estate, Droitwich, Worcestershire WR9 0NR, United Kingdom Tel: +44 (0)1299 250 859 E-mail for LV: sales@motovario.co.uk E-mail for MV: enquiries@teco-group.eu Website: www.motovario.com
TECO Middle East Electric & Machinery Co., Ltd. 2nd Industrial City, Dammam PO Box #708, Dammam 31421 Kingdom of Saudi Arabia Tel: +966-3-812-3939 Fax: +966-3-812-4823 E-mail: sales@teco-me.com
TECO Elektrik Turkey A.S. Yesilkoy Mah. Ataturk Caddesi No:12/1, EGS Business Park, B1 Blok 3. Kat; Daire No: 177-178 34149 - Bakirkoy/ Istanbul Turkey Contact: Mehmet Ali Kocak Tel: +90 212 465 4540 Fax: +90 212 465 4599 Website: www.tecoturkey.com
TECO West Africa, East Africa, Central Africa and Southern Africa Email: sales.africa@teco.com.au Website: http://www.teco.com.au
TECO Australia Pty Limited (Head Office Sydney) 335-337 Woodpark Road, Smithfield NSW 2164 Tel: +61-2-9765-8118 Fax: +61-2-9765-8185 E-mail: sales@teco.com.au Website: www.teco.com.au
TECO Australia Pty Limited (Melbourne Office) 16 Longstaff Road,Bayswater VIC 3153 Tel: +61-3-9720-4411 Fax: +61-3-9720-5355 E-mail: vicsales@teco.com.au Website: www.teco.com.au
TECO Australia Pty Limited (Brisbane Office) 50 Murdoch Circuit, Acacia Ridge QLD 4110 Tel: +61-7-3373-9600 Fax: +61-7-3373-9699 E-mail: qldsales@teco.com.au Website: www.teco.com.au
TECO Australia Pty Limited (Perth Office) 18 Hazelhurst Street, Kewdale WA 6105 Tel: +61-8-9479-4879 Fax: +61-8-9478-3876 E-mail: sales@teco.com.au
TECO New Zealand Ltd. Unit 3, 477 Great South Road, Penrose, Auckland Tel: +64-9-526-8480 Fax: +64-9-526-8484 E-mail: sales@teco.co.nz Website: www.teco.com.au
Sankyo Co., Ltd. 29th fl., Hamamatsucho Bldg., 1-1-1, Shibaura, Minato-ku, Tokyo, Japan, 105-0023 Tel: 81-3-6809-3883 Fax: +81-3-6809-3885 Contact: Seiho Mabuchi Website: www.teco-japan.com
TECO Electric & Machinery PTE Ltd. 47 Tuas Avenue 9, Singapore 639190 Tel: +65-6265-4622 Fax: +65-6265-7354 Website: www.teco.com.sg
PT. TECO Multiguna Elektro J1. Bandengan Utara No.83/1-3, Jakarta 14440, Indonesia Tel: +62-21-6622201 Fax: +62-21-6697029 E-mail: factory@teco.id marketing@teco.id
Surabaya (East Java) Branch Jl. Berbek Industri II No. 21 Sidoarjo (Kawasan Rungkut Industri SBY / SIER) 61256, Jawa Timur, Indonesia Tel: +62-31-8431952 Fax: +62-31-8436672 E-mail: factory@teco.id marketing@teco.id
TECO Electric & Machinery Co., Ltd. New Delhi Office Tel: +91-11-2231-4654 Mobile: +91-98733-90999 Contact: Vijay Sankar kailashkharayat@teco.co.in E-mail: vijay@teco.co.in kailashkharayat@teco.co.in
TECO Electric & Machinery Co., Ltd.(China) Room 321, Building NO.6, Lane 1279 Zhongshan W.Rd, Shanghai, Post 200051,PRC Tel: +86-21-5116-8255 Fax: +86-21-3209-8761 Website: www.tecochina.net E-mail: tecosh@teco-china.com.cn
TECO Electric & Machinery SDN. BHD. -JB Office- PLO 52 (No.26), Jalan Firma 2/1, Kawasan Perindustrian Tebrau 1, 81100 Johor Bahru, Johor, Malaysia. Tel: +60-7-3548008 Fax: +60-7-3546107 E-mail: sales@teco.com.my -KL Office- No. 10, Jalan BP 4/4 Bandar Bukit Puchong 47120 Puchong, Selangor. Tel: +60-3-8062-2299 Fax: +60-3-8060-8869 E-mail: sales-p@teco.com.my
TECO Electronic & Machinery (Thai) Co.,Ltd. 128/1 Soi Watsrivareenoi, Moo 7, Bangna-Trad Rd, Km 18, Bangchalong, Bangplee, Samuthprakarn 10540 Bangkok,Thailand Tel: +66-2-337-1311-20 Fax: +66-2-337-1630-1
TECO Technology (Vietnam) Co.,Ltd. Long Thanh Industrial Zone, Tam An Commune, Long Thanh District, Dong Nai Province, Vietnam Tel: +84-9355-73376 Contact: Ms.TRUONG TU GIANG
Taian (Subic) Electric, Inc. Phase 1 Argonaut Highway cor. Braveheart St. Subic Bay Gateway Park, Subic Bay Freeport Zone -2222- Zambales, Philippines Tel: +63-47-252-1324⁄+63-47-252-1668 Fax: +63-47-252-3234 Website: www.taiansubic.com Contact: Roger De Galicia sb.rdgalicia@taiansubic.com Mobile: +63-922-818-0195
TECO Electric and Machinery GmbH Industrieweg 21, 30179 Hannover, Germany Tel: +49 (0) 511 475747 610 Fax: +49 (0) 511 475747 620 E-mail: enquiries@teco-group.eu Website: www.teco-group.eu
Motovario S.P.A. Via Quattro Passi 1/3 - 41043 Formigine (MO) Italy Phone: +39 059 579700 Fax: +39 059 579710 E-mail: info@motovario.it Website: www.motovario.com/eng/
Context: Source edition footer (EN)A510s_20230323 retained; filename 2025 is not proof of a 2025 revision. No current certification, availability or engineering approval inferred. Original drawings control geometry and connection topology.
Context: Historical worldwide office directory, not verified current. QR code and logo are not product specifications.
Catalogue — TECO-A510.pdf PDF1 — page 1
TECO-A510.pdf · P001 · source page 1
TECO Variable Speed Drives Solutions
OPTIMISED CONTROL & EFFICIENCY
TECO manufactures and stocks a comprehensive range of LV Variable Speed Drives, designed to enhance motor control, improve energy efficiency, and optimise performance across various applications. Engineered with advanced technology, our drives deliver precision, reliability, and cost savings for your operations.
To find out more click the QR code.
electricmotors.teco.com.au
Catalogue — TECO-A510.pdf PDF2 — page 2
TECO-A510.pdf · P001 · source page 2
A510s Enhanced
Enhanced Advanced Current Vector Control Drive
The sustainable and cost-effective solution for improving energy efficiency, extending motor lifespan and enhancing operational reliability.
FEATURES
Seven control modes integrated in one drive
200% 0.5Hz starting torque
Four quadrant control, speed, torque and position
control modes
Built in modbus RTU via RJ45 port
PTC Thermistor Input
Dual rating for normal and heavy duty loads
PLC and PID functions as standard
Fire override mode.
BENEFITS
Improving energy efficiency, resulting in cost savings and reducing consumption
Extending motor lifespan and enhancing operational
reliability, reducing wear and tear
Prioritising reliability for consistent performance and minimizing downtime
Precise motion control for increasing flexibility and optimising motor performance
Reducing maintenance and easy integration into existing systems
Optimising motor performance and system efficiency, delivering energy savings.
electricmotors.teco.com.au
Manual — TECO A510s Series Instruction Manual — page 1
Manual reference: physical PDF page 1. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
INSTRUCTION MANUAL
TECO INVERTER
A510s Series
Cover illustration does not establish full-family ratings or operating settings.
Manual — Contents I — page 2
Manual reference: physical PDF page 2. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
I
Table of Contents
Preface — 0-1
Chapter 1 Safety Precautions — 1-1
1.1 Before Supplying Power to the Inverter — 1-1
1.2 Wiring — 1-1
1.3 Before Operation — 1-2
1.4 Parameters Setting — 1-2
1.5 Operation — 1-2
1.6 Maintenance, Inspection and Replacement — 1-3
1.7 Disposal of the Inverter — 1-4
1.8 Guaranteed liability exemption — 1-4
Chapter 2 Model Description — 2-1
2.1 Nameplate Data — 2-1
2.2 Inverter Models – Motor Power Rating (HD-Heavy Duty) — 2-3
Chapter 3 Environment and Installation — 3-1
3.1 Environment — 3-1
3.2 Installation — 3-2
3.3 External View — 3-3
3.4 Warning Labels — 3-5
3.5 Removing the Front Cover and Keypad — 3-6
3.5.1 Without Built-in filter type — 3-6
3.5.2 Built-in filter type (400V 1 ~60HP) — 3-12
3.6 Wire Gauges and Tightening Torque — 3-13
3.7 Wiring Peripheral Power Devices — 3-16
3.8 General Wiring Diagram — 3-21
3.8.1 General Wiring Diagram (For Standard H & C type) — 3-21
3.8.2 General Wiring Diagram (For Enhanced E & G type) — 3-22
3.9 User Terminals — 3-23
3.9.1 User (Control) Terminals (For Standard H & C type) — 3-23
3.9.2 User (Control) Terminals (For Enhanced E & G type) — 3-26
Contents references use the source’s printed page labels; physical PDF page numbers may differ.
Manual — Contents II — page 3
Manual reference: physical PDF page 3. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
II
3.10 Power Terminals — 3-28
3.10.1 Power Terminals (For Standard H & C type) — 3-28
3.10.2 Power Terminals (For Enhanced E & G type) — 3-32
3.11 Input / Output Power Section Block Diagram — 3-37
3.11.1 Cooling Fan Supply Voltage Selection (400V class) — 3-41
3.12 Inverter Wiring — 3-43
3.13 Input Power and Motor Cable Length — 3-44
3.14 Cable Length vs, Carrier Frequency — 3-44
3.15 Installing an AC Line Reactor — 3-44
3.16 Power Input Wire Size, NFB and MCB Part Numbers — 3-45
3.17 Control Circuit Wiring — 3-48
3.18 Inverter Specifications — 3-50
3.19 Inverter Derating Based on Carrier Frequency — 3-57
3.20 Inverter Derating Based on Temperature — 3-60
3.21 Inverter Dimensions — 3-62
3.22 Dimensions for Models with Built-in Filter — 3-71
Chapter 4 Keypad and Programming Functions — 4-1
4.1 LED Keypad — 4-1
4.1.1 Keypad Display and Keys — 4-1
4.1.2 Seven Segment Display Description — 4-3
4.1.3 LED Indicator Description — 4-5
4.1.4 Power-up Monitor — 4-7
4.1.5 Modifying Parameters/ Set Frequency Reference — 4-8
4.1.6 Operation Control — 4-10
4.2 LCD Keypad — 4-11
4.2.1 Keypad Display and Keys — 4-11
4.2.2 Keypad Menu Structure — 4-13
4.3 Parameters — 4-18
4.4 Description of Parameters — 4-95
4.5 Built-in PLC Function — 4-374
4.5.1 Basic Command — 4-374
4.5.2 Basic Command Function — 4-375
4.5.3 Application Functions — 4-376
Contents references use the source’s printed page labels; physical PDF page numbers may differ.
Manual — Contents III — page 4
Manual reference: physical PDF page 4. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
III
4.6 Modbus Protocol Descriptions — 4-381
4.6.1 Communication Connection and Data Frame — 4-381
4.6.2 Register and Data Format — 4-385
4.6.3 Parameter Data — 4-394
Chapter 5 Check Motor Rotation and Direction — 5-1
Chapter 6 Speed Reference Command Configuration — 6-1
6.1 Reference from the Keypad — 6-1
6.2 Reference from External Analog Signal (0-10V / 4-20mA) — 6-2
6.3 Reference from Serial Communication RS485 — 6-4
6.4 Reference from Pulse Input — 6-6
6.5 Reference from two Analog Inputs — 6-7
6.6 Change Frequency Unit from Hz to rpm — 6-7
Chapter 7 Operation Method Configuration (Run / Stop) — 7-1
7.1 Run / Stop from the LED/ LCD Keypad — 7-1
7.2 Run / Stop from External Switch / Contact or Pushbutton — 7-2
7.3 Run / Stop from Serial Communication RS485 — 7-4
Chapter 8 Motor and Application Specific Settings — 8-1
8.1 Set Motor Nameplate Data — 8-1
8.2 Acceleration and Deceleration Time — 8-2
8.3 Torque Compensation Gain — 8-3
8.4 Automatic Energy Saving Functions — 8-4
8.5 Emergency Stop — 8-6
8.6 Forward and Reverse Jog — 8-7
8.7 Direct / Unattended Startup — 8-7
8.8 Analog Output Setup — 8-8
Chapter 9 Using PID Control for Constant Flow / Pressure Applications — 9-1
Contents references use the source’s printed page labels; physical PDF page numbers may differ.
Manual — Contents IV — page 5
Manual reference: physical PDF page 5. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
IV
9.1 What is PID Control — 9-1
9.2 Connect Transducer Feedback Signal — 9-3
9.3 Engineering Units — 9-4
9.4 Sleep / Wakeup Function — 9-5
Chapter 10 Troubleshooting and Fault Diagnostics — 10-1
10.1 General — 10-1
10.2 Fault Detection Function — 10-1
10.3 Warning / Self-diagnosis Detection Function — 10-7
10.4 Auto-tuning Error — 10-17
10.5 PM Motor Auto-tuning Error — 10-18
10.6 General troubleshooting — 10-19
10.7 Troubleshooting of the Inverter — 10-20
10.7.1 Quick troubleshooting of the Inverter — 10-20
10.7.2 Troubleshooting for OC, OL error displays — 10-22
10.7.3 Troubleshooting for OV, LV error — 10-23
10.7.4 The motor can not run — 10-24
10.7.5 Motor Overheating — 10-25
10.7.6 Motor runs unbalanced — 10-26
10.8 Routine and periodic inspection — 10-27
10.9 Maintenance — 10-28
Chapter 11 Inverter Peripheral Devices and Options — 11-1
11.1 Braking Resistors and Braking Units — 11-1
11.2 AC Line Reactors — 11-5
11.3 Input Noise Filters — 11-8
11.4 Input Current and Fuse Specifications — 11-11
11.5 PG Speed Feedback Card — 11-14
11.6 Other Modules — 11-20
11.7 Communication Options — 11-24
11.8 NEMA1 Kit — 11-24
11.9 PROFIBUS high speed communication expansion card — 11-25
11.9.1 Communication hardware and data structure — 11-25
11.9.2 Product specifications — 11-26
Contents references use the source’s printed page labels; physical PDF page numbers may differ.
Manual — Contents V — page 6
Manual reference: physical PDF page 6. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
V
11.9.3 Installation instructions — 11-27
11.9.4 LED indicator descriptions — 11-29
11.9.5 Driver parameter setting descriptions — 11-30
11.9.6 Connection instructions — 11-30
11.9.7 Meanings of each character — 11-31
11.9.8 PKW regional access parameters — 11-32
11.9.9 Troubleshooting — 11-34
11.9.10 GSD File — 11-35
11.10 CANopen high speed communication expansion card — 11-36
11.10.1 Communication hardware and data structure — 11-36
11.10.2 Product specifications — 11-37
11.10.3 Installation instructions — 11-38
11.10.4 Transmission rate, maximum transmission distance and cable length — 11-40
11.10.5 LED indicator descriptions — 11-40
11.10.6 Driver parameter setting descriptions — 11-41
11.10.7 Connection instructions — 11-41
11.10.8 Object index list — 11-43
11.10.9 Troubleshooting — 11-48
11.10.10 EDS file — 11-49
11.11 Introduction to the EtherCAT high speed communication expansion module — 11-50
11.11.1 Communication hardware and data structure — 11-50
11.11.2 Product specifications — 11-51
11.11.3 Installation instructions — 11-51
11.11.4 LED indicator descriptions — 11-52
11.11.5 Object index list — 11-53
11.11.6 Troubleshooting — 11-55
11.11.7 xml file — 11-55
11.12 I/O expansion card — 11-56
11.12.1 Hardware and data structure — 11-56
11.12.2 Product specifications — 11-56
11.12.3 Installation instructions — 11-57
11.12.4 Driver parameter setting descriptions — 11-57
11.13 DC reactor — 11-58
11.14 Sinusoidal output reactor — 11-60
11.15 DC24V power expansion card — 11-62
Contents references use the source’s printed page labels; physical PDF page numbers may differ.
Manual — Contents VI — page 7
Manual reference: physical PDF page 7. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
VI
11.15.1 JN5-PS-DC24V product specifications — 11-62
11.16 EtherNet/IP Communication Card (JN5-CMHI-EIP) — 11-63
11.16.1 Preparations before using the instrument — 11-63
11.16.2 Installation of a semi-finished product — 11-63
11.16.3 Connection steps — 11-64
11.16.4 Running — 11-71
11.17 JN5-CM-EIP Manual — 11-75
11.17.1 Preparations before using the instrument — 11-75
11.17.2 Installation of a semi-finished product — 11-75
11.17.3 Connection steps — 11-76
11.17.4 Running — 11-83
11.18 Bluetooth LCD KEYPAD (JN5-OP-BTH) — 11-87
11.18.1 Preparations before using the instrument — 11-87
11.18.2 Connecting the Bluetooth APP with the motor drive Bluetooth LCD operator — 11-87
Appendix A: Communication Networks — A1-1
A1.1 RS485-- Network (Modbus) — A1-1
Appendix B: UL Instructions — B-1
Safety stop function instruction manual —
IE2 document —
Contents references use the source’s printed page labels; physical PDF page numbers may differ.
Manual — Preface — page 8
Manual reference: physical PDF page 8. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Preface
The A510s product is an Inverter designed to control a three-phase induction motor. Please read this manual carefully to ensure correct operation, safety and to become familiar with the inverter functions. The A510s inverter is an electrical / electronic product and must be installed and handled by qualified service personnel. Improper handling may result in incorrect operation, shorter life cycle, or failure of this product as well as the motor. All A510s documentation is subject to change without notice. Be sure to obtain the latest editions for use or visit our website at http://industrialproducts.teco.com.tw/ Available Documentation: 1. A510s Start-up and Installation Manual 2. A510s Instruction Manual Ensure you have sound knowledge of the device and familiarize yourself with all safety information and precautions before proceeding to operate the inverter. Ensure you have sound knowledge of the inverter and familiarize yourself with all safety information and precautions before proceeding to operate the inverter.
Please pay close attention to the safety precautions indicated by the warning
and
caution
symbol.
Literal source wording retained; see safety wording flag PDM09A-001.
Warning and caution definitions — PDF page 8
| Source row | Symbol label | Source definition |
|---|---|---|
| 1 | Warning | Failure to ignore the information indicated by the warning symbol may result in death or serious injury. |
| 2 | Caution | Failure to ignore the information indicated by the caution symbol may result in minor or moderate injury and/or substantial property damage. |
Manual — Safety, before power and wiring — page 9
Manual reference: physical PDF page 9. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 1 Safety Precautions
Users are advised to carefully read the safety precautions required in this chapter before installing, testing and repairing the system. Any personnel injury and equipment loss caused by illegal operation are irrelevant to the company and bear any responsibility. 1.1 Before Supplying Power to the Inverter
Warning
The main circuit must be correctly wired. For single phase supply use input terminals (R/L1, T/L3) and for three phase supply use input terminals (R/L1, S/L2, T/L3). Terminals U/T1, V/T2, W/T3 must only be used to connect the motor. Connecting the input supply to any of the U/T1, V/T2 or W/T3 terminals will cause damage to the inverter.
Caution
To avoid the front cover from disengaging or other physical damage, do not carry the inverter by its cover. Support the unit by its heat sink when transporting. Improper handling can damage the inverter or injure personnel, and should be avoided. To avoid the risk of fire, do not install the inverter on or near flammable objects. Install on nonflammable objects such as metal surfaces. If several inverters are placed inside the same control panel, provide adequate ventilation to maintain the temperature below 40°C/104°F (50°C/122°F without a dust cover) to avoid overheating or fire. When removing or installing the digital operator, turn off the power first, and then follow the instructions in our instruction manual to avoid operator error or loss of display caused by faulty connections.
This product is sold subject to IEC 61800-3. In a domestic environment this product may cause radio interference in which case the user may need to apply corrective measures. Motor over temperature protection is provided. 1.2 Wiring
Always turn OFF the power supply before attempting inverter installation and wiring of the user terminals. Wiring must be performed by a qualified personnel / certified electrician. Make sure the inverter is properly grounded. (200V Class: Grounding impedance shall be less than 100Ω. 400V Class: Grounding impedance shall be less than 10Ω.) Make sure the inverter is properly grounded. It is required to disconnect the ground wire in the control board to avoid the sudden surge causing damage on electronic parts if it is improperly grounded. RCD is required to be in compliance with the protection norm of B-type leakage current. Please check and test emergency stop circuits after wiring. (Installer is responsible for the correct wiring.) Never touch any of the input or output power lines directly or allow any input of output power lines to
Manual — Wiring, before operation and operation — page 10
Manual reference: physical PDF page 10. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
come in contact with the inverter case. Do not perform a dielectric voltage withstand test (megger) on the inverter this will result in inverter damage to the semiconductor components.
Caution
The line voltage applied must comply with the inverter’s specified input voltage. Connect braking resistor and braking unit to the designated terminals. Do not connect a braking resistor directly to the DC terminals P (+) and N (-), otherwise fire may result. Use wire gauge recommendations and torque specifications. Never connect input power to the inverter output terminals U/T1, V/T2, W/T3. Do not connect a contactor or switch in series with the inverter and the motor. Do not connect a power factor correction capacitor or surge suppressor to the inverter output. Ensure the interference generated by the inverter and motor does not affect peripheral devices. 1.3 Before Operation
Warning
Make sure the inverter capacity matches the parameters 13-00. Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the motor is greater than 80 ft (25m). A high-frequency current can be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter, an increase in leakage current, or an inaccurate current readout. Be sure to install all covers before turning on power. Do not remove any of the covers while power to the inverter is on, otherwise electric shock may occur. Do not operate switches with wet hands, otherwise electric shock may result. Do not touch inverter terminals when energized even if inverter has stopped, otherwise electric shock may result. 1.4 Parameters Setting
Do not connect a load to the motor while performing a rotational auto-tune. Make sure the motor can freely run and there is sufficient space around the motor when performing a rotational auto-tune. 1.5 Operation
Be sure to install all covers before turning on power. Do not remove any of the covers while power to the inverter is on, otherwise electric shock may occur. Do not connect or disconnect the motor during operation. This will cause the inverter to trip and may cause damage to the inverter.
Manual — Operation and maintenance — page 11
Manual reference: physical PDF page 11. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Operations may start suddenly if an alarm or fault is reset with a run command active. Confirm that no run command is active upon resetting the alarm or fault, otherwise accidents may occur. Do not operate switches with wet hands, otherwise electric shock may result. It provides an independent external hardware emergency switch, which emergently shuts down the inverter output in the case of danger. If automatic restart after power recovery (parameter 07-00) is enabled, the inverter will start automatically after power is restored. Make sure it is safe to operate the inverter and motor before performing a rotational auto-tune. Do not touch inverter terminals when energized even if inverter has stopped, otherwise electric shock may result. Do not check signals on circuit boards while the inverter is running. After the power is turned off, the cooling fan may continue to run for some time.
Caution
Do not touch heat-generating components such as heat sinks and braking resistors. Carefully check the performance of motor or machine before operating at high speed, otherwise Injury may result. Note the parameter settings related to the braking unit when applicable. Do not use the inverter braking function for mechanical holding, otherwise injury may result. Do not check signals on circuit boards while the inverter is running. 1.6 Maintenance, Inspection and Replacement
Warning
Wait a minimum of five minutes after power has been turned OFF before starting an inspection. Also confirm that the charge light is OFF and that the DC bus voltage has dropped below 25Vdc. Never touch high voltage terminals in the inverter. Make sure power to the inverter is disconnected before disassembling the inverter. Only authorized personnel should perform maintenance, inspection, and replacement operations. (Take off metal jewelry such as watches and rings and use insulated tools.)
The Inverter can be used in an environment with a temperature range from 14° ~104(140) °F (-10~+40(60)°C) and relative humidity of 95% non-condensing. The inverter must be operated in a dust, gas, mist and moisture free environment.
Manual — Disposal and liability exemption — page 12
Manual reference: physical PDF page 12. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
1.7 Disposal of the Inverter
Caution
Please dispose of this unit with care as an industrial waste and according to your required local regulations. The capacitors of inverter main circuit and printed circuit board are considered as hazardous waste and must not be burned. The Plastic enclosure and parts of the inverter such as the top cover board will release harmful gases if burned. Equipment containing electrical components may not be disposed of together with domestic waste. It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
1.8 Guaranteed liability exemption
Loss of opportunity caused by the company's products, damage to customers of your company or your company, damage to non-company products, or compensation for other businesses, whether within the warranty period or not, is not covered by the company.
Manual — Nameplate data — page 13
Manual reference: physical PDF page 13. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 2 Model Description
2.1 Nameplate Data
It is essential to verify the A510s inverter nameplate and make sure that the A510s inverter has the
correct rating so it can be used in your application with the proper sized AC motor.
Unpack the A510s inverter and check the following: (1) The A510s inverter and start-up and installation manual are contained in the package. (2) The A510s inverter has not been damaged during transportation there should be no dents or parts missing. (3) The A510s inverter is the type you ordered. You can check the type and specifications on the main nameplate. (4) Check that the input voltage range meets the input power requirements. (5) Ensure that the motor HP matches the motor rating of the inverter.
HD: Heavy Duty (Constant Torque); ND: Normal Duty (Variable Torque) (1HP = 0.746 kW)
Product Name & Motor Rating Input Power Specifications Output Power Specifications Series No
UL and CE Marks
Code No (P/N Bar code) (S/N Bar code)
Illustrative nameplate only: PRODUCT A510-4010-SH3F; MOTOR RATING 7.5kW/11.0kW; INPUT AC 3PH 380-480V (+10%,-15%) 50/60Hz 18.7A/24.0A; OUTPUT AC 3PH 0-480V 0-400Hz 18.0A/23.0A; IP20; MODEL A510-4010-H3F. P/N and S/N barcode placeholders; TECO Electric & Machinery Co., Ltd.; CE and cULus LISTED marks, 16KJ, IND. CONT. EQ., E177007. This illustration is not an actual serial-number record or proof of current certification. PRODUCT and MODEL text differ as printed.
Manual — Model identification — page 14
Manual reference: physical PDF page 14. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Model Identification A510 - 4 010 - S H 3 F - 1
Voltage Rating 2: 200V Class 4: 400V Class 5: 575V Class 6: 690V Class
Motor Rating 001: 1HP 002: 2HP ∫ 150: 150HP 175: 175HP 215: 215HP ∫ 375: 375HP 425: 425HP
Input Blank: 1Ph or 3Ph 3: 3Ph
Noise Filter Blank: No RFI F: RFI Filter
Operator Type H: Standard Type (LED Keypad) C: Standard Type (LCD Keypad) E: Enhanced Type (LED Keypad) G: Enhanced Type (LCD Keypad)
A510s Inverter Series
Enclosure Blank: IP00/IP20 1: IP21 for frame 1~5 B: Enhanced type 400V 40HP built-in braking transistor model X: For high humidity and high pollution environment (For Frame 3~8 only)
Manual — Heavy Duty200V models — page 15
Manual reference: physical PDF page 15. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
2.2 Inverter Models – Motor Power Rating (HD – Heavy Duty)
200V Class
Section2.2 HD Heavy Duty. □ is the source operator-type placeholder, not an omitted unknown digit. ◎ is printed selection mark; blanks remain blank. No unlisted model or phase applicability inferred.
200V class — Heavy Duty motor power ratings — PDF page 15
| Source row | Voltage / phase / tolerance / frequency | A510s model pattern | Applied motor HP | Applied motor kW | Filter with | Filter without |
|---|---|---|---|---|---|---|
| 1 | 1ph/3ph, 200~240V +10%/-15% 50/60Hz | A510-2001-S□ | 1 | 0.75 | ⟦blank source cell⟧ | ◎ |
| 2 | 1ph/3ph, 200~240V +10%/-15% 50/60Hz | A510-2002-S□ | 2 | 1.5 | ⟦blank source cell⟧ | ◎ |
| 3 | 1ph/3ph, 200~240V +10%/-15% 50/60Hz | A510-2003-S□ | 3 | 2.2 | ⟦blank source cell⟧ | ◎ |
| 4 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2005-S□3 | 5 | 3.7 | ⟦blank source cell⟧ | ◎ |
| 5 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2008-S□3 | 7.5 | 5.5 | ⟦blank source cell⟧ | ◎ |
| 6 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2010-S□3 | 10 | 7.5 | ⟦blank source cell⟧ | ◎ |
| 7 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2015-S□3 | 15 | 11 | ⟦blank source cell⟧ | ◎ |
| 8 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2020-S□3 | 20 | 15 | ⟦blank source cell⟧ | ◎ |
| 9 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2025-S□3 | 25 | 18.5 | ⟦blank source cell⟧ | ◎ |
| 10 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2030-S□3 | 30 | 22 | ⟦blank source cell⟧ | ◎ |
| 11 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2040-S□3 | 40 | 30 | ⟦blank source cell⟧ | ◎ |
| 12 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2050-S□3 | 50 | 37 | ⟦blank source cell⟧ | ◎ |
| 13 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2060-S□3 | 60 | 45 | ⟦blank source cell⟧ | ◎ |
| 14 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2075-S□3 | 75 | 55 | ⟦blank source cell⟧ | ◎ |
| 15 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2100-S□3 | 100 | 75 | ⟦blank source cell⟧ | ◎ |
| 16 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2125-S□3 | 125 | 94 | ⟦blank source cell⟧ | ◎ |
| 17 | 3ph, 200~240V +10%/-15% 50/60Hz | A510-2150-S□3 | 150 | 112 | ⟦blank source cell⟧ | ◎ |
Manual — Heavy Duty400V models — page 16
Manual reference: physical PDF page 16. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
400V Class
Section2.2 HD Heavy Duty. □ is the source operator-type placeholder, not an omitted unknown digit. ◎ is printed selection mark; blanks remain blank. No unlisted model or phase applicability inferred.
400V class — Heavy Duty motor power ratings — PDF page 16
| Source row | Voltage / phase / tolerance / frequency | A510s model pattern | Applied motor HP | Applied motor kW | Filter with | Filter without |
|---|---|---|---|---|---|---|
| 1 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4001-S□3 | 1 | 0.75 | ⟦blank source cell⟧ | ◎ |
| 2 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4001-S□3F | 1 | 0.75 | ◎ | ⟦blank source cell⟧ |
| 3 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4002-S□3 | 2 | 1.5 | ⟦blank source cell⟧ | ◎ |
| 4 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4002-S□3F | 2 | 1.5 | ◎ | ⟦blank source cell⟧ |
| 5 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4003-S□3 | 3 | 2.2 | ⟦blank source cell⟧ | ◎ |
| 6 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4003-S□3F | 3 | 2.2 | ◎ | ⟦blank source cell⟧ |
| 7 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4005-S□3 | 5 | 3.7 | ⟦blank source cell⟧ | ◎ |
| 8 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4005-S□3F | 5 | 3.7 | ◎ | ⟦blank source cell⟧ |
| 9 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4008-S□3 | 7.5 | 5.5 | ⟦blank source cell⟧ | ◎ |
| 10 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4008-S□3F | 7.5 | 5.5 | ◎ | ⟦blank source cell⟧ |
| 11 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4010-S□3 | 10 | 7.5 | ⟦blank source cell⟧ | ◎ |
| 12 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4010-S□3F | 10 | 7.5 | ◎ | ⟦blank source cell⟧ |
| 13 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4015-S□3 | 15 | 11 | ⟦blank source cell⟧ | ◎ |
| 14 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4015-S□3F | 15 | 11 | ◎ | ⟦blank source cell⟧ |
| 15 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4020-S□3 | 20 | 15 | ⟦blank source cell⟧ | ◎ |
| 16 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4020-S□3F | 20 | 15 | ◎ | ⟦blank source cell⟧ |
| 17 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4025-S□3 | 25 | 18.5 | ⟦blank source cell⟧ | ◎ |
| 18 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4025-S□3F | 25 | 18.5 | ◎ | ⟦blank source cell⟧ |
| 19 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4030-S□3 | 30 | 22 | ⟦blank source cell⟧ | ◎ |
| 20 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4030-S□3F | 30 | 22 | ◎ | ⟦blank source cell⟧ |
| 21 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4040-S□3 | 40 | 30 | ⟦blank source cell⟧ | ◎ |
| 22 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4040-S□3F | 40 | 30 | ◎ | ⟦blank source cell⟧ |
| 23 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4050-S□3 | 50 | 37 | ⟦blank source cell⟧ | ◎ |
| 24 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4050-S□3F | 50 | 37 | ◎ | ⟦blank source cell⟧ |
| 25 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4060-S□3 | 60 | 45 | ⟦blank source cell⟧ | ◎ |
| 26 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4060-S□3F | 60 | 45 | ◎ | ⟦blank source cell⟧ |
| 27 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4075-S□3 | 75 | 55 | ⟦blank source cell⟧ | ◎ |
| 28 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4100-S□3 | 100 | 75 | ⟦blank source cell⟧ | ◎ |
| 29 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4125-S□3 | 125 | 94 | ⟦blank source cell⟧ | ◎ |
| 30 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4150-S□3 | 150 | 112 | ⟦blank source cell⟧ | ◎ |
| 31 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4175-S□3 | 175 | 130 | ⟦blank source cell⟧ | ◎ |
| 32 | 3ph, 380~480V +10%/-15% 50/60Hz | A510-4215-S□3 | 215 | 160 | ⟦blank source cell⟧ | ◎ |
| 33 | 3ph, 380~480V +10%/-15% 50/60Hz | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | 3ph, 380~480V +10%/-15% 50/60Hz | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | 3ph, 380~480V +10%/-15% 50/60Hz | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 36 | 3ph, 380~480V +10%/-15% 50/60Hz | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Heavy Duty575/690V models — page 17
Manual reference: physical PDF page 17. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
575/690V Class
Section2.2 HD Heavy Duty. □ is the source operator-type placeholder, not an omitted unknown digit. ◎ is printed selection mark; blanks remain blank. No unlisted model or phase applicability inferred.
575/690V class — Heavy Duty motor power ratings — PDF page 17
| Source row | Voltage / phase / tolerance / frequency | A510s model pattern | Applied motor HP | Applied motor kW | Filter with | Filter without |
|---|---|---|---|---|---|---|
| 1 | 3ph, 500~600V +10%/-15% 50/60Hz | A510-5001-S□3 | 1 | 0.75 | ⟦blank source cell⟧ | ◎ |
| 2 | 3ph, 500~600V +10%/-15% 50/60Hz | A510-5002-S□3 | 2 | 1.5 | ⟦blank source cell⟧ | ◎ |
| 3 | 3ph, 500~600V +10%/-15% 50/60Hz | A510-5003-S□3 | 3 | 2.2 | ⟦blank source cell⟧ | ◎ |
| 4 | 3ph, 500~600V +10%/-15% 50/60Hz | A510-5005-S□3 | 5 | 3.7 | ⟦blank source cell⟧ | ◎ |
| 5 | 3ph, 500~600V +10%/-15% 50/60Hz | A510-5008-S□3 | 7.5 | 5.5 | ⟦blank source cell⟧ | ◎ |
| 6 | 3ph, 500~600V +10%/-15% 50/60Hz | A510-5010-S□3 | 10 | 7.5 | ⟦blank source cell⟧ | ◎ |
| 7 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6015-S□3 | 15 | 11 | ⟦blank source cell⟧ | ◎ |
| 8 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6020-S□3 | 20 | 15 | ⟦blank source cell⟧ | ◎ |
| 9 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6025-S□3 | 25 | 18.5 | ⟦blank source cell⟧ | ◎ |
| 10 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6030-S□3 | 30 | 22 | ⟦blank source cell⟧ | ◎ |
| 11 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6040-S□3 | 40 | 30 | ⟦blank source cell⟧ | ◎ |
| 12 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6050-S□3 | 50 | 37 | ⟦blank source cell⟧ | ◎ |
| 13 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6060-S□3 | 60 | 45 | ⟦blank source cell⟧ | ◎ |
| 14 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6075-S□3 | 75 | 55 | ⟦blank source cell⟧ | ◎ |
| 15 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6100-S□3 | 100 | 75 | ⟦blank source cell⟧ | ◎ |
| 16 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6125-S□3 | 125 | 94 | ⟦blank source cell⟧ | ◎ |
| 17 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6150-S□3 | 150 | 112 | ⟦blank source cell⟧ | ◎ |
| 18 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6175-S□3 | 175 | 130 | ⟦blank source cell⟧ | ◎ |
| 19 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6215-S□3 | 215 | 160 | ⟦blank source cell⟧ | ◎ |
| 20 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6250-S□3 | 250 | 185 | ⟦blank source cell⟧ | ◎ |
| 21 | 3ph, 575~690V +10%/-15% 50/60Hz | A510-6270-S□3 | 270 | 200 | ⟦blank source cell⟧ | ◎ |
Manual — Environment — page 18
Manual reference: physical PDF page 18. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 3 Environment and Installation
3.1 Environment
The environment will directly affect the proper operation and the life span of the inverter. To ensure that the inverter will give maximum service life, please comply with the following environmental conditions:
All temperature, enclosure, frame, altitude and vibration qualifiers preserved. Shared installation-site label repeats per printed requirement. Source terms retained, not engineering acceptance.
Environment and protection — PDF page 18
| Source row | Condition | Source requirement |
|---|---|---|
| 1 | Protection Class | IP20/IP21/NEMA 1 or IP00 |
| 2 | Operating Temperature | IP20/IP21: -10°C - +40°C (14 -104 °F) IP00 or without cover: -10°C - +50°C (14-122 °F) Enhanced type frame 5 is 50°C without de-rating. The maximum operating temperature is 60°C, but it is required to derate 2% of current at each additional 1°C. If several inverters are placed in the same control panel, provide a heat removal means to maintain ambient temperatures |
| 3 | Storage Temperature | -20°C - +70°C (-4 -158 °F) |
| 4 | Humidity | 95% non-condensing Relative humidity 5% to 95%, free of moisture. (Follow IEC60068-2-78 standard) |
| 5 | Altitude | Altitude: Below 1000 m (3281 ft.) It is required to derate 1% of current at each additional 100 m. The maximum altitude is 3000 m. |
| 6 | Installation Site | Avoid exposure to rain or moisture. |
| 7 | Installation Site | Avoid direct sunlight. |
| 8 | Installation Site | Avoid oil mist and salinity. |
| 9 | Installation Site | Avoid corrosive liquid and gas. |
| 10 | Installation Site | Avoid dust, lint fibers, and small metal filings. |
| 11 | Installation Site | Keep away from radioactive and flammable materials. |
| 12 | Installation Site | Avoid electromagnetic interference (soldering machines, power machines). |
| 13 | Installation Site | Avoid vibration (stamping, punching machines etc.). Add a vibration-proof pad if the situation cannot be avoided. |
| 14 | Shock | Maximum acceleration: 1.0G (9.8m/s²), from 49.84 to 150 Hz Displacement amplitude : 0.3mm (peak value), from 10 to 49.84 Hz (Follow IEC60068-2-6 standard) |
Manual — Installation spacing — page 19
Manual reference: physical PDF page 19. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.2 Installation
When installing the inverter, ensure that inverter is installed in upright position (vertical direction) and there is adequate space around the unit to allow normal heat dissipation as per the following Fig. 3.2.1
Fig 3.2.1: A510s Installation space X = 1.18” (30mm) for inverter ratings up to 25HP X = 1.96” (50mm) for inverter ratings 30HP or higher Important Note: The inverter heatsink temperature can reach up to 194°F / 90°C during operation; make sure to use insulation material rated for this temperature.
Fig3.2.1 labels: front and side views each show 5.9in./150mm above and below the inverter; side view labels Air Flow. Ambient temperature -10 to +40°C. X marks side clearances; X=1.18 inch (30mm) up to25HP and X=1.96 inch (50mm) for30HP or higher, as stated below the figure. Keypad pictogram is illustrative, not parameter values.
Manual — External view a/b — page 20
Manual reference: physical PDF page 20. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.3 External View
(a) 200V 1 ~ 7.5 HP / 400V 1 ~ 7.5 HP / 575V 1~ 3 HP
Mounting Hole
Rings (4 rings)
Nameplate and Barcode
Terminal Cover
Digital Operator
Front Cover
Fan Cover Anti-dust Cover
(Wall-mounted type, IEC IP20) (Wall-mounted type, IEC IP20, NEMA1)
(b) 200V 10 ~ 25 HP / 400V 10 ~ 30 HP / 575V 5~10HP / 690V 15~40HP
External view(a), left IEC IP20: Fan Cover; Mounting hole; Heat sink; Nameplate and barcode; Front cover; Digital operator; Terminal cover. Applies to the source heading200V1–7.5HP /400V1–7.5HP /575V1–3HP.
External view(b), left IEC IP20: Mounting hole; Front cover; Digital operator; Nameplate and barcode; Terminal cover. Applies to200V10–25HP /400V10–30HP /575V5–10HP /690V15–40HP.
External view(b), right IEC IP20,NEMA1: Anti-dust cover; Mounting hole; Front cover; Digital operator; Nameplate and barcode; Terminal cover. Same source(b) ratings. No additional unlabeled feature inferred.
Manual — External view c/d — page 21
Manual reference: physical PDF page 21. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(c) 200V 30 ~ 40 HP / 400V 40 ~ 75 HP / 690V 50~75HP
Mounting Hole
Rings (4 rings)
Nameplate and Barcode
Terminal Cover
Digital Operator
Front Cover
(Wall-mounted type, IEC IP20, NEMA1)
(d) 200V 50 ~ 100 HP / 400V 100 ~ 215 HP / 690V 100~270HP
Anti-dust Cover
Wiring Box
(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20, NEMA1)
Manual — External view e and warning labels — page 22
Manual reference: physical PDF page 22. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(e) 200V 125 ~ 150 HP / 400V 270 ~ 425 HP
Mounting Hole
Rings (4 rings)
Nameplate and Barcode
Terminal Cover
Digital Operator
Front Cover
Nameplate and Barcode Terminal Cover
Anti-dust Cover
Wiring Box
(Wall-mounted type, IEC IP00) (Wall-mounted type, IEC IP20, NEMA1)
3.4 Warning Labels
Important: Warning information located on the front cover must be read upon installation of the inverter. (a) 200V: 1-7.5HP / 400V: 1-7.5HP /575V 1~ 3 HP (b) 200V: 10HP / 400V: 10-20HP /575V 5~10HP
(c) 200V: 15-150HP / 400V: 20(F)-425HP/690V 15~270HP
Warning label(a) for 200V1–7.5HP /400V1–7.5HP /575V1–3HP: WARNING / AVERTISSEMENT. Risk of electrical shock. shut off main power and wait for 5 minutes before servicing. Risque de choc électrique. Couper l’alimentation principale et attendre 5 minutes avant l’entretien. Hot surface. Risk of burn. Surface chaude. Risque de brûlure. CAUTION / ATTENTION. See manual before operation. Consultez le manuel avant l’opération.
Warning label(b) for 200V10HP /400V10–20HP /575V5–10HP: WARNING / AVERTISSEMENT. Risk of electrical shock. shut off main power and wait for 5 minutes before servicing. Risque de choc électrique. Couper l’alimentation principale et attendre 5 minutes avant l’entretien. CAUTION / ATTENTION. See manual before operation. Consultez le manuel avant l’opération.
Warning label(c) for 200V15–150HP /400V20(F)–425HP /690V15–270HP: WARNING / AVERTISSEMENT. Risk of electrical shock. shut off main power and wait for 15 minutes before servicing. Risque de choc électrique. Couper l’alimentation principale et attendre 15 minutes avant l’entretien. CAUTION / ATTENTION. See manual before operation. Consultez le manuel avant l’opération.
Manual — Front cover and keypad removal — page 23
Manual reference: physical PDF page 23. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.5 Removing the Front Cover and Keypad
Caution
Before making any wiring connections to the inverter the front cover needs to be removed. It is not required to remove the digital operator before making any wiring connections. Models 200V, 1 – 25 HP and 400V, 1 – 30 HP and 575V/690V 1 – 40 HP have a plastic cover. Loosen the screws and remove the cover to gain access to the terminals and make wiring connections. Place the plastic cover back and fasten screws when wiring connections have been made. Models 200V, 30 - 150HP and 400V, 40 - 425HP and 690V 50 - 270HP have a metal cover. Loosen the screws and remove the cover to gain access to the terminals and make wiring connections. Place the metal cover back and fasten screws when wiring connections have been made.
3.5.1 Without Built-in filter type
(a) 200V: 1 ~ 7.5 HP / 400V: 1 ~ 7.5 HP /575V: 1~3HP Step 1: Unscrew Step 2: Remove cover
Manual — Cover procedure a continued and b — page 24
Manual reference: physical PDF page 24. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Step 3: Make wire connections and place cover back Step 4: Fasten screw (b) 200V: 10 ~ 25 HP / 400V: 10 ~ 30 HP /575V: 5~10HP/690V 15~40HP
Step 1: Unscrew cover Step 2: Remove cover
Manual — Cover procedure b continued and c — page 25
Manual reference: physical PDF page 25. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Step 3: Make wire connections and place cover back Step 4: Fasten screw (c) 200V: 30 ~ 40 HP / 400V: 40 ~ 75 HP /690V: 50~75HP (Chassis Type)
Step 1: Unscrew cover Step 2: Remove cover
Manual — Cover procedure c continued and d — page 26
Manual reference: physical PDF page 26. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Step 3: Make wire connections and place cover back Step 4: Fasten screw (d) 200V: 50 ~ 100 HP / 400V: 100 ~ 215 HP /690V: 100~270HP (Chassis Type)
Step 1: Unscrew cover Step 2: Remove cover
Procedure(d) continues on physical page27, which is outside this part and retains its prior partial status.
Manual — Cover procedure(d)continued and(e) — page 27
Manual reference: physical PDF page 27. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Subsection (e) heading and steps 1/2 are separate from the upper-half continuation of the preceding procedure; do not associate that upper half with (e).
Continuation of subsection(d), upper page: Step 3: Make wire connections and place cover back. Step 4: Fasten screw. Lower subsection(e) heading and steps1–2 remain in the prior reviewed fields.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Subsection (e) heading and steps 1–2 are distinct from the upper continuation of (d), steps 3–4.
Partial page; continued by steps3/4 onPDF28. No torque, dimensions or safe-work procedure inferred.
Subsection(e) context — PDF page 27
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Applicability | (e) 200V:125~150HP /400V:270~425HP (Chassis Type) |
| 2 | Step1 | Unscrew cover |
| 3 | Step2 | Remove cover |
Manual — Chassis cover procedure continued — page 28
Manual reference: physical PDF page 28. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Continuation of subsection(e) onPDF27. Illustrations retain cover/screw locations. These two captions are not a complete installation or isolation procedure.
Source captions only; subsection(e) applicability supplied separately fromPDF27. No torque supplied on this page.
Printed continuation steps — PDF page 28
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Step3 | Make wire connections and place cover back |
| 2 | Step4 | Fasten screw |
Manual — Built-in filter cover procedure — page 29
Manual reference: physical PDF page 29. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.5.2 Built-in filter type (400V: 1 ~ 60 HP)
Step 1: Unscrew cover Step 2: Remove cover
Step 3: Unscrew filter section Step 4: Remove filter cover Step 5: Make connections and place filter cover back Step 6: Fasten screw
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Manual — Wire gauge and tightening torque — page 30
Manual reference: physical PDF page 30. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.6 Wire Gauges and Tightening Torque
To comply with UL standards, use UL approved copper wires (rated 75° C) and round crimp terminals (UL Listed products) as shown in table below when connecting to the main circuit terminals. TECO recommends using crimp terminals manufactured by NICHIFU Terminal Industry Co., Ltd and the terminal crimping tool recommended by the manufacturer for crimping terminals and the insulating sleeve.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Section3.6:75°C UL-approved copper wires and round crimp terminals, NICHIFU recommendation. Source values retained without checking suitability or converting torque.
Wire sizes and fastening torque — PDF page 30
| Source row | Wire size mm²(AWG) | Terminal screw size | Round crimp terminal model | Fastening torque kgf.cm(in.lbs) | Insulating sleeve model | Crimp tool model |
|---|---|---|---|---|---|---|
| 1 | 0.75 (18) | M3.5 | R1.25-3.5 | 8.2 to 10 (7.1 to 8.7) | TIC 1.25 | NH 1 |
| 2 | 0.75 (18) | M4 | R1.25-4 | 12.2 to 14 (10.4 to 12.1) | TIC 1.25 | NH 1 |
| 3 | 1.25 (16) | M3.5 | R1.25-3.5 | 8.2 to 10 (7.1 to 8.7) | TIC 1.25 | NH 1 |
| 4 | 1.25 (16) | M4 | R1.25-4 | 12.2 to 14 (10.4 to 12.1) | TIC 1.25 | NH 1 |
| 5 | 2 (14) | M3.5 | R2-3.5 | 8.2 to 10 (7.1 to 8.7) | TIC 2 | NH 1 / 9 |
| 6 | 2 (14) | M4 | R2-4 | 12.2 to 14 (10.4 to 12.1) | TIC 2 | NH 1 / 9 |
| 7 | 2 (14) | M5 | R2-5 | 22.1 to 24 (17.7 to 20.8) | TIC 2 | NH 1 / 9 |
| 8 | 2 (14) | M6 | R2-6 | 25.5 to 30.0 (22.1 to 26.0) | TIC 2 | NH 1 / 9 |
| 9 | 3.5 / 5.5 (12/10) | M4 | R5.5-4 | 12.2 to 14 (10.4 to 12.1) | TIC 5.5 | NH 1 / 9 |
| 10 | 3.5 / 5.5 (12/10) | M5 | R5.5-5 | 20.4 to 24 (17.7 to 20.8) | TIC 5.5 | NH 1 / 9 |
| 11 | 3.5 / 5.5 (12/10) | M6 | R5.5-6 | 25.5 to 30.0 (22.1 to 26.0) | TIC 5.5 | NH 1 / 9 |
| 12 | 3.5 / 5.5 (12/10) | M8 | R5.5-8 | 61.2 to 66.0 (53.0 to 57.2) | TIC 5.5 | NH 1 / 9 |
| 13 | 8 (8) | M4 | R8-4 | 12.2 to 14 (10.4 to 12.1) | TIC 8 | NOP 60 |
| 14 | 8 (8) | M5 | R8-5 | 20.4 to 24 (17.7 to 20.8) | TIC 8 | NOP 60 |
| 15 | 8 (8) | M6 | R8-6 | 25.5 to 30.0 (22.1 to 26.0) | TIC 8 | NOP 60 |
| 16 | 8 (8) | M8 | R8-8 | 61.2 to 66.0 (53.0 to 57.2) | TIC 8 | NOP 60 |
| 17 | 14 (6) | M4 | R14-4 | 12.2 to 14 (10.4 to 12.1) | TIC 14 | NH 1 / 9 |
| 18 | 14 (6) | M5 | R14-5 | 20.4 to 24 (17.7 to 20.8) | TIC 14 | NH 1 / 9 |
| 19 | 14 (6) | M6 | R14-6 | 25.5 to 30.0 (22.1 to 26.0) | TIC 14 | NH 1 / 9 |
| 20 | 14 (6) | M8 | R14-8 | 61.2 to 66.0 (53.0 to 57.2) | TIC 14 | NH 1 / 9 |
| 21 | 22 (4) | M6 | R22-6 | 25.5 to 30.0 (22.1 to 26.0) | TIC 22 | NOP 60/ 150H |
| 22 | 22 (4) | M8 | R22-8 | 61.2 to 66.0 (53.0 to 57.2) | TIC 22 | NOP 60/ 150H |
| 23 | 30 / 38 (3 /2) | M6 | R38-6 | 25.5 to 30.0 (22.1 to 26.0) | TIC 38 | NOP 60/ 150H |
| 24 | 30 / 38 (3 /2) | M8 | R38-8 | 61.2 to 66.0 (53.0 to 57.2) | TIC 38 | NOP 60/ 150H |
| 25 | 50 / 60 (1/1/0) | M8 | R60-8 | 61.2 to 66.0 (53.0 to 57.2) | TIC 60 | NOP 60/ 150H |
| 26 | 50 / 60 (1/1/0) | M10 | R60-10 | 102 to 120 (88.5 to 104) | TIC 60 | NOP 150H |
| 27 | 70 (2/0) | M8 | R70-8 | 61.2 to 66.0 (53.0 to 57.2) | TIC 60 | NOP 150H |
| 28 | 70 (2/0) | M10 | R70-10 | 102 to 120 (88.5 to 104) | TIC 60 | NOP 150H |
| 29 | 80 (3/0) | M10 | R80-10 | 102 to 120 (88.5 to 104) | TIC 80 | NOP 150H |
| 30 | 80 (3/0) | M16 | R80-16 | 255 to 280 (221 to 243) | TIC 80 | NOP 150H |
| 31 | 100 (4/0) | M10 | R100-10 | 102 to 120 (88.5 to 104) | TIC 100 | NOP 150H |
| 32 | 100 (4/0) | M12 | R100-12 | 143 to 157 (124 to 136) | TIC 100 | NOP 150H |
| 33 | 100 (4/0) | M16 | R80-16 | 255 to 280 (221 to 243) | TIC 80 | NOP 150H |
Manual — Closed-loop crimp terminals — page 31
Manual reference: physical PDF page 31. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Main Circuit Terminal Wiring
UL approval requires crimp terminals when wiring the inverter’s main circuit terminals. Use crimping tools as specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches inverter models with crimp terminals and insulation caps.
Closed-Loop Crimp Terminal Size
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Both input/output wire groups explicitly share a physical cell. A510s(F) is a separate source table; do not merge with non-F variant. Model-code suffixes preserved.
Closed-loop crimp terminal size A510s — PDF page 31
| Source row | Drive model | Wire gauge mm²(AWG/MCM), R/L1 S/L2 T/L3 and U/T1 V/T2 W/T3 | Terminal screws | Crimp terminal model | Tool machine number | Insulation cap model |
|---|---|---|---|---|---|---|
| 1 | 2001 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 2 | 2002 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 3 | 2003 | 3.5 (12) / 5.3 (10) | M4 | R3.5-4 / R5.5-4 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 4 | 2005 | 5.3 (10) | M4 | R5.5-4 | Nichifu NH 1 / 9 | TIC 5.5 |
| 5 | 2008 | 8.4 (8) | M4 | R8-4 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 6 | 2010 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 7 | 2015 | 13.3 (6) | M6 | R14-6 | Nichifu NOP 60 / 150HA | TIC 14 |
| 8 | 2020 | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 9 | 2025 | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 10 | 2030 | 33.6 (2) | M8 | R38-8 | Nichifu NOP 60 / 150HA | TIC 38 |
| 11 | 2040 | 67.4 (1/0) | M8 | R60-8 | Nichifu NOP 60 / 150HA | TIC 60 |
| 12 | 2060 | 107.2 (4/0) | M10 | R100-10 | Nichifu NOP 150HA | TIC 100 |
| 13 | 2075 | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 150HA | TIC 150 |
| 14 | 2100 | 200 (400MCM) | M10 | R200-10 | Nichifu NOP 700 & NOH300K | TIC 200 |
| 15 | 2125 | 300 (600MCM) | M12 | R325-12S | Nichifu NOP 700 & NOH300K | TIC 325 |
| 16 | 2150 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 17 | 4001 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 18 | 4002 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 19 | 4003 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 20 | 4005 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 21 | 4008 | 3.5 (12) / 5.3 (10) | M4 | R3.5-4 / R5.5-4 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 22 | 4010 | 3.5 (12) / 5.3 (10) | M4 | R3.5-4 / R5.5-4 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 23 | 4015 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 24 | 4020 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 25 | 4025 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 26 | 4030 | 13.3 (6) | M6 | R14-6 | Nichifu NOP 60 / 150HA | TIC 14 |
| 27 | 4040-B | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 28 | 4040 | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 29 | 4050 | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 30 | 4060 | 33.6 (2) | M8 | R38-8 | Nichifu NOP 60 / 150HA | TIC 38 |
| 31 | 4075 | 67.4 (2/0) | M8 | R70-8 | Nichifu NOP 60 / 150HA | TIC 70 |
| 32 | 4100 | 85 (3/0) | M10 | R80-10 | Nichifu NOP 60 / 150HA | TIC 80 |
| 33 | 4125 | 152 (300MCM) | M10 | R100-10 | Nichifu NOP 60 / 150HA | TIC 100 |
| 34 | 4150 | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
| 35 | 4175 | 200 (400MCM) | M10 | R200-10 | Nichifu NOP 700 & NOH300K | TIC 200 |
| 36 | 4215 | 250 (500MCM) | M10 | R250-10 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 37 | 4270 | 300 (600MCM) | M12 | R325-12S | Nichifu NOP 700 & NOH300K | TIC 325 |
| 38 | 4300 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 39 | 4375 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 40 | 4425 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 41 | 5001 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4 ~ R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 42 | 5002 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4 ~ R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 43 | 5003 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4 ~ R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 44 | 5005 | 2 (14) / 3.5 (12) / 5.3 (10) | M6 | R2-6 ~ R5.5-6 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 45 | 5008 | 3.5 (12) / 5.3 (10) | M6 | R3.5-6 / R5.5-6 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
Manual — Crimp terminals continued and F variants — page 32
Manual reference: physical PDF page 32. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Both input/output wire groups explicitly share a physical cell. A510s(F) is a separate source table; do not merge with non-F variant. Model-code suffixes preserved.
Closed-loop crimp terminal size A510s — PDF page 32
| Source row | Drive model | Wire gauge mm²(AWG/MCM), R/L1 S/L2 T/L3 and U/T1 V/T2 W/T3 | Terminal screws | Crimp terminal model | Tool machine number | Insulation cap model |
|---|---|---|---|---|---|---|
| 1 | 5010 | 3.5 (12) / 5.3 (10) | M6 | R3.5-6 / R5.5-6 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 2 | 6015 | 5.3 (10) | M6 | R5.5-6 | Nichifu NH 1 / 9 | TIC 5.5 |
| 3 | 6020 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 4 | 6025 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 5 | 6030 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 6 | 6040 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 7 | 6050 | 13.3 (6) | M8 | R14-8 | Nichifu NOP 60 / 150HA | TIC 14 |
| 8 | 6060 | 13.3 (6) | M8 | R14-8 | Nichifu NOP 60 / 150HA | TIC 14 |
| 9 | 6075 | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 10 | 6100 | 33.6 (2) | M10 | R38-10 | Nichifu NOP 60 / 150HA | TIC 38 |
| 11 | 6125 | 67.4 (2/0) | M10 | R70-10 | Nichifu NOP 60 / 150HA | TIC 70 |
| 12 | 6150 | 67.4 (2/0) | M10 | R70-10 | Nichifu NOP 60 / 150HA | TIC 70 |
| 13 | 6175 | 85 (3/0) | M10 | R80-10 | Nichifu NOP 60 / 150HA | TIC 80 |
| 14 | 6215 | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
| 15 | 6250 | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
| 16 | 6270 | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
Closed-loop crimp terminal size A510s(F) — PDF page 32
| Source row | Drive model | Wire gauge mm²(AWG/MCM), R/L1 S/L2 T/L3 and U/T1 V/T2 W/T3 | Terminal screws | Crimp terminal model | Tool machine number | Insulation cap model |
|---|---|---|---|---|---|---|
| 1 | 4001 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 2 | 4002 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 3 | 4003 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 4 | 4005 | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 5 | 4008 | 5.3 (10) | M4 | R5.5-4 | Nichifu NH 1 / 9 | TIC 5.5 |
| 6 | 4010 | 5.3 (10) | M6 | R5.5-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 5.5 |
| 7 | 4015 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 8 | 4020 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 9 | 4025 | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 10 | 4030 | 13.3 (6) | M6 | R14-6 | Nichifu NOP 60 / 150HA | TIC 14 |
| 11 | 4040-B | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 12 | 4040 | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 13 | 4050 | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 14 | 4060 | 33.6 (2) | M8 | R38-8 | Nichifu NOP 60 / 150HA | TIC 38 |
Manual — Peripheral wiring cautions and ground-wire illustration — page 33
Manual reference: physical PDF page 33. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.7 Wiring Peripheral Power Devices
Caution
After power is shut off to the inverter the capacitors will slowly discharge. Do NOT touch the inverter circuit or replace any components until the “CHARGE” indicator is off. Do NOT wire or connect/disconnect internal connectors of the inverter when the inverter is powered up or after power off but the “CHARGE”” indicator is on. Do NOT connect inverter output U, V and W to the AC power source. This will result in damage to the inverter. The inverter must be properly grounded. Use terminal E to connect earth ground and comply with local standards. It is required to disconnect the ground wire in the control board if the inverter is not grounded. Do NOT perform a dielectric voltage withstand test (Megger) on the inverter this will result in inverter damage to the semiconductor components. Do NOT touch any of the components on the inverter control board to prevent damage to the inverter by static electricity. 200V: 1HP~2HP/ 400V: 1HP~3HP
• Disconnect the ground wire of J1. on the control board (C/B).
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Photographs preserve highlighted ground-wire/screw callout and rating headings. Incidental tiny PCB silkscreen/firmware labels are not treated as product specifications or connection instructions.
Manual — Ground-wire illustrations by rating — page 34
Manual reference: physical PDF page 34. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V: 3HP~8HP/ 400V: 5HP~8HP/575V: 1~3HP
200V: 10HP/ 400V: 10~20HP/575V: 5~10HP
• Disconnect the ground wire of isolated metal plate.
• Disconnect the ground wire of J1 on the control board (C/B).
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Photographs preserve highlighted ground-wire/screw callout and rating headings. Incidental tiny PCB silkscreen/firmware labels are not treated as product specifications or connection instructions.
Manual — Ground-wire illustrations by rating continued — page 35
Manual reference: physical PDF page 35. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V: 15- 25HP/ 400V: 25~30HP/690V: 15~40HP
200V: 30-40HP/ 400V: 40-75HP/690V: 50~75HP
• Disconnect the ground wire of isolated metal plate.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Photographs preserve highlighted ground-wire/screw callout and rating headings. Incidental tiny PCB silkscreen/firmware labels are not treated as product specifications or connection instructions.
Manual — Ground screw and voltage-drop formula — page 36
Manual reference: physical PDF page 36. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V: 50HP/ 400V: 100HP and the above/690V: 100HP
Caution
Refer to the recommended wire size table for the appropriate wire to use. The voltage between the power supply and the input terminals of the inverter may not exceed 2%. Phase-to-phase voltage drop (V) = 3 ×resistance of wire (Ω/km) × length of line m) × current×10-3. (km=3280 x feet) / (m=3.28 x feet ) Reduce the carrier frequency (parameter 11-01) If the cable from the inverter to the motor is over 25m (82ft). A high-frequency current can be generated by stray capacitance between the cables and result in an overcurrent trip of the inverter, an increase in leakage current, or an inaccurate current readout. To protect peripheral equipment, install fast acting fuses on the input side of the inverter. Refer to section 11.4 for additional information.
• Disconnect the ground screw below the C/B and ground studs of isolated metal plate.
Printed equation: Phase-to-phase voltage drop(V)=√3 × resistance of wire(Ω/km) × length of line m) × current ×10⁻³. Printed conversion line: (km=3280 x feet)/(m=3.28 x feet). Literal source retained and unit-direction defect flagged; not a validated calculation.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Photographs preserve highlighted ground-wire/screw callout and rating headings. Incidental tiny PCB silkscreen/firmware labels are not treated as product specifications or connection instructions.
Manual — Peripheral device descriptions — page 37
Manual reference: physical PDF page 37. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
MCCB
Power supply:
•
Make sure the correct voltage is applied to avoid damaging the inverter. Molded-case circuit breaker (MCCB) or fused disconnect: • A molded-case circuit breaker or fused disconnect must be installed between the AC source and the inverter that conforms to the rated voltage and current of the inverter to control the power and protect the inverter.
Do not use the circuit breaker as the run/stop switch for the inverter. Ground fault detector / breaker:
Install a ground fault breaker to prevent problems caused by current leakage and to protect personnel. Select current range up to 200mA, and action time up to 0.1 second to prevent high frequency failure. Magnetic contactor: • Normal operations do not need a magnetic contactor. When performing functions such as external control and auto restart after power failure, or when using a brake controller, install a magnetic contactor.
Do not use the magnetic contactor as the run/stop switch for the inverter. AC line reactor for power quality: • When inverters are supplied by a high capacity power source (> 600KVA), an AC reactor can be connected to improve the power factor. Install Fast Acting Fuse: • To protect peripheral equipment, install fast acting fuses in accordance with the specifications in section 11.4 for peripheral devices. Input Noise filter: • A filter must be installed when there are inductive loads affecting the inverter. The inverter meets EN55011 Class A, category C3 when the TECO special filter is used. See section 11.3 for peripheral devices. Inverter: • Output terminals T1, T2, and T3 are connected to U, V, and W terminals of the motor. If the motor runs in reverse while the inverter is set to run forward, swap any two terminals connections for T1, T2, and T3.
To avoid damaging the inverter, do not connect the output terminals T1, T2, and T3 to AC input power.
Connect the ground terminal properly. (200V class: Rg <100Ω; 400V class: Rg <10Ω.) Output Noise filter: • An output noise filter may reduce system interference and induced noise. Motor: • If the inverter drives multiple motors the output rated current of the inverter must be greater than the total current of all the motors.
Peripheral illustration labels, top to bottom: Power Supply; Molded Circuit Breaker; Magnetic Contactor; AC Reactor; Fast Acting Fuse; Input Noise Filter; A510 Inverter; Ground; Output Noise Filter; Induction Motor; Ground. Illustration labels only, not an inferred wiring route.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Manual — General wiring Standard H&C — page 38
Manual reference: physical PDF page 38. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.8.1 General Wiring Diagram (For Standard H & C type)
Notes:
*1: Models 200V 1 ~ 25HP and 400V 1 ~ 40HP or lower ratings have a built-in braking transistor. To use this braking
transistor a braking resistor can be connected between B1 and B2.
*2: Use SW3 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function
digital input terminals S1~S8.
*3: Use SW2 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2 (AI2). Besides
please also check parameter 04-00 for proper setting.
*4: Run Permissive input F1 and F2 is a normally closed input. This input should be closed to enable the inverter output. To
activate this input remove the jumper wire between F1 and F2.
*5: Models 200V 3HP and 400V 5HP and higher ratings include terminals -10V, S(+), S(-),R2A-R2C and PO-GND.
*6: 200V 2HP and 400V 3HP and lower ratings include terminal DO2.
*7: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.
*8: AO2 default setting is 0~+10V.
*9: Both 200V class 50HP~150HP and 400V class 100HP~425HP have built-in DC reactors.
*10: It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel connection.
Please refer to Appendix A
Standard H&C general wiring diagram power labels: AC Input Voltage L1(R),L2(S),L3(T); MCCB; Magnetic Contactor; AC Reactor; Fast Acting Fuses; Braking Resistor; Main Power Section L1/R,L2/S,L3/T,B1/P,B2*1,⊖; U/T1,V/T2,W/T3; E;3Ø Induction motor; Ground<100Ω. Labels only, no connection inference.
Standard H&C digital/relay labels: Digital Input Section; Multi-Functional Digital Inputs, Factory Default: S1 FWD/STOP;S2 REV/STOP;S3 Multi-Step Speed Ref.1;S4 Multi-Step Speed Ref.2;S5 Multi-Step Speed Ref.3;S6 Fault Reset;S7 Jog Command;S8 External base block. SW32:SOURCE PNP;SINK NPN(DEFAULT).24V Power terminal for digital signal(source);24VG Digital signal common(sink). Analog Output1 AO1,Analog Output2 AO2,GND;Analog Outputs AO1:0–10VDC,AO2:0–10VDC/4-20mA;Note1. CN3 Option Card(PG). Multi-Function Relay Output:R1A,R1C,R1B,NO,NC,R2A,R2C5;Contact rating250VAC<1.0A,30VDC<1.0A. SW6*8,V,I.
Standard H&C analog/pulse/run labels: External Analog Inputs;-10V~0~10V;4~20mA/0~10V;0V;Pulse Input. +10V:Power for Analog Input(max.20mA);AI1 Multi-Function Analog Input(-10~10V/0~10V,10KΩ);AI2 Multi-Function Analog Input(0~10V,200KΩ),(4~20mA,250Ω);GND Analog Signal Common;-10V Power for Analog Input5. SW23,V,I;SW410. PI Pulse Input32kHzMax.7;F1,F2 Run Permissive Input4. DO1,DO26,DOG:Multi-Functional transistor digital outputs Open Collector48V@60mA(opto-isolated). PO,GND*5:Multi-Function pulse output32kHzMax. CN6(RJ45):1:S(+),2:S(-);RS485 Communication Port. P arrow markers retained as diagram marks; no electrical routes inferred.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Manual — General wiring Enhanced E&G — page 39
Manual reference: physical PDF page 39. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.8.2 General Wiring Diagram (For Enhanced E & G type)
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3
P2/B1 B2 *1
3Ø Induction motor
E Main Power Section
+10V: Power for Analog Input (max. 20mA)
AI1: Multi-Function Analog Input
AI2: Multi-Function Analog Input
PI Pulse Input 32kHz Max.
S1
DOG
Multi-Functional transistor digital outputs Open Collector, 48V @50mA (opto-isolated)
(R1A)
(R1C)
(R1B)
NC
NO
Multi-Function Relay Output
External Analog Inputs
Digital Input Section
+
-
Contact rating: 250 VAC < 1.0A 30 VDC < 1.0A
- Ground < 100Ω
Analog Output 1
Analog Output 2
AO1
AO2
GND
Analog Outputs AO1 : 0 – 10 VDC AO2 : 0 – 10 VDC / 4-20mA
DO1
S2
S3
S4
S5
S6
S7
S8
24V Power terminal for digital signal (source) A510s
Multi- Functional Digital Inputs
External base block
Jog Command
Multi-Step Speed Ref. 3
Fault Reset
Multi-Step Speed Ref. 2
Multi-Step Speed Ref. 1
FWD / STOP
REV / STOP
Factory Default
RS485 Communication Port
L2(S) L3(T)
AC Input Voltage Braking Resistor
Note 1
R2A
R2C
24VG Digital signal common (sink)
GND: Analog Signal Common
-10V: Power for Analog Input
Pulse Input
0V
4 ~ 20mA / 0 ~ 10V
-10V ~ 0 ~ 10V / 4~20mA
SF1
SF2 Run Permissive Input
SOURCE PNP
SINK NPN (DEFAULT)
SW6
P
CN6 (RJ45)
S(-)
S(+)
2:
1:
PO
Multi-function pulse output 32kHz Max. P
CN3 Option PG encoder card or DC24 power card
*5
*4
*6
*2
(-10~10V/0~10V, 15KΩ, 4~20mA, 500Ω)
(0~10V, 200KΩ)
SW5 *8
*3
(4~20mA, 500Ω)
*8
P1
SG
CN2 Option comm. card or I/O expansion card
ON
OFF
SW2 SW1 SW3 SW4
AO2 AI1 AI2 AO1
V
I
L1(R)
Notes:
*1: Models 200V 1 ~ 25HP and 400V 1 ~ 30HP or lower ratings have a built-in braking transistor. To use this braking
transistor a braking resistor can be connected between B1 and B2.
*2: Use SW6 to select between Sink (NPN, with 24VG common) or Source (PNP, with +24V common) for multi-function
digital input terminals S1~S8.
*3: Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2 (AI2).
Besides please also check parameter 04-00 for proper setting.
*4: Run Permissive input SF1 and SF2 is a normally closed input. This input should be closed to enable the inverter output.
To activate this input remove the jumper wire between SF1/ SF2 and SG.
*5: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.
*6: AO1/AO2 default setting is 0~+10V.
*7: Both 200V class 50HP~150HP and 400V class 100HP~425HP have built-in DC reactors.
*8: Only the model 200V 3~40HP and 400V 5~75HP provide P1 terminal, for external DCL connected between P1 and P2,
P1 and P2 are short-circuited before shipping out from the factory.
*9: It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel connection.
Enhanced E&G main-input illustration labels: MCCB; Magnetic Contactor; AC Reactor; Fast Acting Fuses; AC Input Voltage; L1(R), L2(S), L3(T). Source labels only; no wiring inference.
Enhanced E&G analogue input diagram: AI1 labelled -10~10V/0~10V,15KΩ,4~20mA,500Ω; AI2 labelled 0~10V,200KΩ and4~20mA,500Ω. These diagram-specific values conflict with page43 table; retain both with source flags.
Enhanced E&G selector block: SW1 AO1, SW2 AO2, SW3 AI1, SW4 AI2, each V/I. Selector labels retained; no switch position inferred from illustration.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Manual — User terminal layouts Standard H&C — page 40
Manual reference: physical PDF page 40. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.9.1 User (Control) Terminals (For Standard H & C type)
200V: 1 ~ 2 HP, 400V: 1 ~ 3HP 200V: 3 ~ 40 HP, 400V: 5 ~ 75HP, 575V:1~10HP, 690V: 15~75HP
R1A R1B R1C
R2A R2C RJ45
200V: 50 ~ 150 HP, 400V: 100 ~ 425HP, 690V: 100~270HP
R2A R2C R1A R1B R1C RJ45
Standard H&C terminal label layout,200V1–2HP /400V1–3HP. Left:R1A R1B R1C;RJ45 below R1C. Right top:E DO2 24VG S2 S4 S6 S8 24V +10V GND AI1 AI2. Right bottom:DO1 DOG S1 S3 S5 S7 F1 F2 PI AO1 AO2 E. Printed positions only; not wiring instructions.
Standard H&C terminal label layout,200V3–40HP /400V5–75HP /575V1–10HP /690V15–75HP. Main top:S(+) S(-) S1 S3 S5 S7 24V +10V GND -10V GND GND AI1 AI2. Main bottom:DO1 DOG S2 S4 S6 S8 24VG F1 F2 PO PI AO1 AO2 E. Relay block:R1A R1B R1C;below:R2A R2C RJ45. Printed label positions only.
Standard H&C terminal layout,200V50–150HP /400V100–425HP /690V100–270HP. Main top:S(+) S(-) S1 S3 S5 S7 24V +10V GND -10V GND GND AI1 AI2. Main bottom:DO1 DOG S2 S4 S6 S8 24VG F1 F2 PO PI AO1 AO2 E. Separate relay row:R2A R2C R1A R1B R1C;RJ45 separate. No inferred electrical equivalence.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Manual — User terminal descriptions Standard H&C — page 41
Manual reference: physical PDF page 41. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Description of User Terminals
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Source shared cells repeat only by their physical boundaries. Analog-output category continues from physical43 onto44; blank category on44 retained, not replaced. Diagram/table impedance discrepancies flagged. Read numbered notes and source variant range.
User terminal descriptions — Standard H&C — PDF page 41
| Source row | Type | Terminal | Terminal function | Signal level / information |
|---|---|---|---|---|
| 1 | Digital input signal | S1 | 2-wire forward/ stop (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 2 | Digital input signal | S2 | 2-wire reversal/ stop (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 3 | Digital input signal | S3 | Multi-speed/ position setting command 1 (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 4 | Digital input signal | S4 | Multi-speed/ position setting command 2 (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 5 | Digital input signal | S5 | Multi-speed/ position setting command 3 (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 6 | Digital input signal | S6 | Fault reset (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 7 | Digital input signal | S7 | JOG frequency command (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 8 | Digital input signal | S8 | External B.B.(Base Block) stop (coast to stop) (default) * 1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 9 | 24V Power supply | 24V | Digital signal SOURCE point (SW3 switched to SOURCE ) | ±15%, Max. output current: 250mA (The sum of all loads connected ) |
| 10 | 24V Power supply | 24VG | Common terminal of Digital signals Common point of digital signal SINK ( SW3 switched to SINK ) | ±15%, Max. output current: 250mA (The sum of all loads connected ) |
| 11 | Analog input signal | +10V | Power for external speed potentiometer | +10V (Max. current , 20mA) |
| 12 | Analog input signal | -10V | Only above 200V 3HP/ 400V 5HP (include) support this terminal function | -10V (Max. current , 20mA) |
| 13 | Analog input signal | AI1 | Multi-function analog input for speed reference (0-10V input)/(-10V~10V input) | From 0 to +10V, From -10V to +10V Input impedance : 20KΩ Resolution: 11bit + 1 |
| 14 | Analog input signal | AI2 | Multi-function analog input terminals *2, can use SW2 to switch voltage or current input (0~10V)/(4-20mA) | From 0 to +10V, Input impedance: 200KΩ From 4 to 20 mA Input impedance: 250KΩ Resolution: 11bit + 1 |
| 15 | Analog input signal | GND | Analog signal ground terminal | ---- |
| 16 | Analog input signal | E | Shielding wire’s connecting terminal (Ground) | ---- |
| 17 | Analog output signal | AO1 | Multi-function analog output terminals *2 (0~10V output) | From 0 to 10V, From 4 to 20mA (Load < 500Ω) PWM Frequency: 10KHz |
| 18 | Analog output signal | AO2 | Multi-function analog output terminals *2. can use SW6 to switch voltage or current input (0~10V / 4-20mA output) | From 0 to 10V, From 4 to 20mA (Load < 500Ω) PWM Frequency: 10KHz |
| 19 | Analog output signal | GND | Analog signals ground terminal | From 0 to 10V, From 4 to 20mA (Load < 500Ω) PWM Frequency: 10KHz |
| 20 | Pulse output signal | PO | Pulse output, Band width 32KHz, only above 200V 3HP/ 400V 5HP (include) support this terminal function. | Max. Frequency: 32KHz Open Collector output |
| 21 | Pulse output signal | GND | Analog signals ground terminal | ---- |
Manual — User terminal descriptions Standard continued — page 42
Manual reference: physical PDF page 42. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Notes:
*1:Multi-function digital input/ output can be referred to in this manual.
- Group 03: External Terminals Digital Input / Output Function Group.
*2:Multi-function analog input/ output can be referred to in this manual..
- Group 04 - External Terminal Analog Signal Input (Output) Function Group.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Source shared cells repeat only by their physical boundaries. Analog-output category continues from physical43 onto44; blank category on44 retained, not replaced. Diagram/table impedance discrepancies flagged. Read numbered notes and source variant range.
User terminal descriptions — Standard H&C — PDF page 42
| Source row | Type | Terminal | Terminal function | Signal level / information |
|---|---|---|---|---|
| 1 | Pulse input signal | PI | Pulse command input, Bandwidth: 32KHz | L: from 0.0 to 0.5V H: from 4.0 to 13.2V Max. Frequency: 0 - 32KHz Built-in pull-up resistance. When open collector input is used, it is not required to connect resistance. |
| 2 | Pulse input signal | GND | Analog signals ground terminal | ---- |
| 3 | Digital output | DO1 | Multi-function(open collector transistor) output *1 | 48Vdc, 2mA ~50mA Open-collector output |
| 4 | Digital output | DO2 200V:1-2HP 400V:1-3HP | Multi-function(open collector transistor) output *1 | 48Vdc, 2mA ~50mA Open-collector output |
| 5 | Digital output | DOG | Open collector transistor digital ground | ⟦blank source cell⟧ |
| 6 | Relay output | R1A | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1/DO2 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 7 | Relay output | R1B | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1/DO2 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 8 | Relay output | R1C | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1/DO2 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 9 | Relay output | R2A-R2C 200V:over 3HP 400V:over 5HP | With the same functions as DO1/DO2 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 10 | Run Permissive Input | F1 | On: normal operation. Off: stop. (Jumper wired between F1 and F2 has to be removed by using external contact to stop.) | 24Vdc, 8mA, pull-up |
| 11 | Run Permissive Input | F2 | On: normal operation. Off: stop. (Jumper wired between F1 and F2 has to be removed by using external contact to stop.) | 24V Ground |
| 12 | RS-485 port | S (+) | RS485/ Modbus communication protocol | Differential input and output |
| 13 | RS-485 port | S (-) | RS485/ Modbus communication protocol | Differential input and output |
| 14 | Grounding | E (G) | Grounding to earth Shield the connecting terminal | ---- |
Manual — User terminal layouts/descriptions Enhanced E&G — page 43
Manual reference: physical PDF page 43. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.9.2 User (Control) Terminals (For Enhanced E & G type)
200V: 1 ~ 2 HP, 400V: 1 ~ 3HP
200V: 3 ~ 40 HP, 400V: 5 ~ 75HP
200V: 50 ~ 150 HP, 400V: 100 ~ 425HP
Description of User Terminals
Enhanced E&G printed terminal layout 200V1–2HP /400V1–3HP. Relay labels:R1A R1B R1C R2A R2C;RJ45 below. Main top:S(+) S(-) S1 S3 S5 S7 24V 24VG +10V -10V GND GND AI1 AI2. Main bottom:DO1 DOG S2 S4 S6 S8 SF1 SG SF2 PO PI AO1 AO2 E. Label sequence only; no inferred wiring.
Enhanced E&G printed terminal layout 200V3–40HP /400V5–75HP. Relay labels:R1A R1B R1C;R2A R2C RJ45 below. Main top:S(+) S(-) S1 S3 S5 S7 24V 24VG +10V -10V GND GND AI1 AI2. Main bottom:DO1 DOG S2 S4 S6 S8 SF1 SG SF2 PO PI AO1 AO2 E. Label sequence only; no inferred wiring.
Enhanced E&G printed terminal layout 200V50–150HP /400V100–425HP. Relay labels:R2A R2C R1A R1B R1C RJ45. Main top:S(+) S(-) S1 S3 S5 S7 24V 24VG +10V -10V GND AI1 AI2. Main bottom:DO1 DOG S2 S4 S6 S8 SF1 SG SF2 PO PI AO1 AO2 E. Label sequence only; no inferred wiring.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Source shared cells repeat only by their physical boundaries. Analog-output category continues from physical43 onto44; blank category on44 retained, not replaced. Diagram/table impedance discrepancies flagged. Read numbered notes and source variant range.
User terminal descriptions — Enhanced E&G — PDF page 43
| Source row | Type | Terminal | Terminal function | Signal level / information |
|---|---|---|---|---|
| 1 | Digital input signal | S1 | 2-wire forward/ stop (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 2 | Digital input signal | S2 | 2-wire reversal/ stop (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 3 | Digital input signal | S3 | Multi-speed/ position setting command 1 (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 4 | Digital input signal | S4 | Multi-speed/ position setting command 2 (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 5 | Digital input signal | S5 | Multi-speed/ position setting command 3 (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 6 | Digital input signal | S6 | Fault reset (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 7 | Digital input signal | S7 | JOG frequency command (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 8 | Digital input signal | S8 | External B.B.(Base Block) stop (coast to stop) (default) *1 | Signal Level 24 VDC (photo isolated) Maximum current: 8mA Maximum voltage: 30 Vdc Input impedance: 4.22kΩ |
| 9 | 24V Power supply | 24V | Digital signal SOURCE point (SW6 switched to SOURCE ) | ±15%, Max. output current: 250mA (The sum of all loads connected ) |
| 10 | 24V Power supply | 24VG | Common terminal of Digital signals Common point of digital signal SINK ( SW6 switched to SINK ) | ±15%, Max. output current: 250mA (The sum of all loads connected ) |
| 11 | Analog input signal | +10V | Positive power for external speed potentiometer | +10V (Max. current , 20mA) |
| 12 | Analog input signal | -10V | Negative power for external speed potentiometer | -10V (Max. current , 20mA) |
| 13 | Analog input signal | AI1 | Multi-function analog input terminals *2, can use SW3 to switch voltage or current input (-10V~10V)/(4-20mA) | From 0 to +10V, From -10V to +10V Input impedance : 500KΩ From 4 to 20 mA Input impedance : 500KΩ Resolution: 11bit + 1 |
| 14 | Analog input signal | AI2 | Multi-function analog input terminals *2, can use SW4 to switch voltage or current input (0~10V)/(4-20mA) | From 0 to +10V, Input impedance: 900KΩ From 4 to 20 mA Input impedance: 250Ω Resolution: 11bit + 1 |
| 15 | Analog input signal | GND | Analog signal ground terminal | ---- |
| 16 | Analog input signal | E | Shielding wire’s connecting terminal (Ground) | ---- |
| 17 | Analog output signal | AO1 | Multi-function analog output terminals *2. can use SW1 to switch voltage or current input (0~10V / 4- 20mA output) | From 0 to 10V, From 4 to 20mA (Load < 500Ω) |
Manual — User terminal descriptions Enhanced continued — page 44
Manual reference: physical PDF page 44. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Notes: 1:Multi-function digital input/ output can be referred to in our instruction manual. - Group 03: External Terminals Digital Input / Output Function Group. 2:Multi-function analog input/ output can be referred to in our instruction manual.. - Group 04 - External Terminal Analog Signal Input (Output) Function Group.
Caution Maximum output current capacity for terminal 10V is 20mA. Multi-function analog output AO1 and AO2 are used for an analog output meter. Do not use these outputs for feedback control. Control board’s 24V and ±10V are to be used for internal control only, Do not use the internal power- supply to power external devices.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Source shared cells repeat only by their physical boundaries. Analog-output category continues from physical43 onto44; blank category on44 retained, not replaced. Diagram/table impedance discrepancies flagged. Read numbered notes and source variant range.
User terminal descriptions — Enhanced E&G — PDF page 44
| Source row | Type | Terminal | Terminal function | Signal level / information |
|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | AO2 | Multi-function analog output terminals *2. can use SW2 to switch voltage or current input (0~10V / 4- 20mA output) | PWM Frequency: 10KHz |
| 2 | ⟦blank source cell⟧ | GND | Analog signals ground terminal | PWM Frequency: 10KHz |
| 3 | Pulse output signal | PO | Bandwidth: 32KHz | Max. Frequency: 32KHz Open Collector output |
| 4 | Pulse output signal | GND | Analog signals ground terminal | ---- |
| 5 | Pulse input signal | PI | Pulse command input, Bandwidth: 32KHz | L: from 0.0 to 0.5V H: from 4.0 to 13.2V Max. Frequency: 0 - 32KHz Built-in pull-up resistance. When open collector input is used, it is not required to connect resistance. |
| 6 | Pulse input signal | GND | Analog signals ground terminal | ---- |
| 7 | Digital output | DO1 | Multi-function(open collector transistor) output *1 | 48Vdc, 2mA ~50mA Open-collector output |
| 8 | Digital output | DOG | Open collector transistor digital ground | 48Vdc, 2mA ~50mA Open-collector output |
| 9 | Relay output | R1A | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 10 | Relay output | R1B | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 11 | Relay output | R1C | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 12 | Relay output | R2A-R2C | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay contact common terminal, With the same functions as DO1 | Rating: 250Vac, 10 mA ~ 1A 30Vdc, 10 mA ~ 1A |
| 13 | Run Permiss ive Input | SF1 SF2 | On: normal operation. Off: stop. (Jumper wired between SF1/ SF2 and SG has to be removed by using external contact to stop.) | 24Vdc, 8mA, pull-up |
| 14 | Run Permiss ive Input | SG | Safety command common terminal | 24Vdc |
| 15 | RS-485 port | S (+) | RS485/ Modbus communication protocol | Differential input and output |
| 16 | RS-485 port | S (-) | RS485/ Modbus communication protocol | Differential input and output |
| 17 | Groundi ng | E (G) | Grounding to earth Shield the connecting terminal | ---- |
Manual — Power terminal functions/layouts Standard H&C — page 45
Manual reference: physical PDF page 45. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.10.1 Power Terminals (For Standard H & C type)
Note: The power terminal of 575V & 690V Enhanced E & G type and Standard H & C type are the same. Please refer to this quarter for 575V & 690V Enhanced E & G type power terminal information.
200V: 1 ~ 2HP, 400V: 1 ~ 3HP
200V: 3 ~ 7.5HP, 400V: 5 ~ 7.5HP, 575V: 1~3HP
200V: 10HP, 400V: 10 ~ 15HP
R/L1 S/L2 T/L3 E B1/P
B2 Power In Dynamic Brake CHARGE
U/T1 V/T2 W /T3 E To Motor
T
Standard H&C power strip label sequence for 200V1–2HP /400V1–3HP: R/L1 S/L2 T/L3 B1/P ⊖ B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 200V3–7.5HP /400V5–7.5HP /575V1–3HP: R/L1 S/L2 T/L3 ⊖ B1/P B2 U/T1 V/T2 W/T3;Power In;Dynamic Brake;To Motor;CHARGE. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 200V10HP /400V10–15HP: E R/L1 S/L2 T/L3 ⊖ B1/P B2 U/T1 V/T2 W/T3 E;earth symbols;Power In;Dynamic Brake;To Motor;CHARGE. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Ground terminal label in the source table is E/PE/[earth symbol]. Native extraction omits the drawn earth symbol; this annotation restores the visible label without changing the preserved native table cell.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Explicit source shared cells preserved. First column groups adjacent terminals only where their function cell is shared. Ground terminal symbol retained in figure. Single-phase terminal discrepancy flagged. Note:575V/690V Enhanced E&G power terminals use this Standard section.
Standard H&C; source rating scope 200V1–2HP /400V1–3HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 200V3–7.5HP /400V5–7.5HP /575V1–3HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 200V10HP /400V10–15HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Power terminal functions — Standard H&C — PDF page 45
| Source row | Terminal labels (grouped where source shared) | 200V1–25HP;400V1–40HP;575V1–10HP;690V15–40HP | 200V30–150HP;400V50–425HP;690V50–270HP |
|---|---|---|---|
| 1 | R/L1 S/L2 T/L3 | Input Power Supply (For single phase use terminals R/L1 and S/L2) | Input Power Supply (For single phase use terminals R/L1 and S/L2) |
| 2 | B1/P B2 | B1/P-B2: external braking resistor | - |
| 3 | ⊖ | B1/P-B2: external braking resistor | ⊕ -⊖: Connect braking module |
| 4 | ⊕ | - | ⊕ -⊖: Connect braking module |
| 5 | U/T1 V/T2 W/T3 | Inverter output | Inverter output |
| 6 | E/PE/ | Ground terminal | Ground terminal |
Terminal screw size — 200V1–2HP /400V1–3HP — PDF page 45
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M4 | M4 |
Terminal screw size — 200V10HP /400V10–15HP — PDF page 45
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M6 |
Manual — Power terminal layouts Standard continued — page 46
Manual reference: physical PDF page 46. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
575V: 5~10HP
400V: 20HP (Frame 3)
200V: 15~25HP, 400V: 20 ~ 30HP, 690V: 15~40HP
400V: 40HP
Terminal screw size
Standard H&C power strip label sequence for 575V5–10HP: E R S T N⊖ P B U V W;earth symbol;Power In;Dynamic Brake;To Motor;CHARGE. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 400V20HP(Frame3): R/L1 S/L2 T/L3 ⊖ B1/P B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 200V15–25HP /400V20–30HP /690V15–40HP: R/L1 S/L2 T/L3 ⊖ B1/P B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 400V40HP: R/L1 S/L2 T/L3 ⊖ B1/P B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Standard H&C; source rating scope 575V5–10HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 400V20HP(Frame3). T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 200V15–25HP /400V20–30HP /690V15–40HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 400V40HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Terminal screw size — 575V5–10HP — PDF page 46
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M6 |
Terminal screw size — 400V20HP(Frame3) — PDF page 46
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M5 |
Terminal screw size — 400V40HP — PDF page 46
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M8 |
Manual — Power terminal layouts Standard continued — page 47
Manual reference: physical PDF page 47. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V: 30 ~40HP, 400V: 50 ~ 75HP
690V: 50~75HP
200V: 50~60HP, 400V: 100HP
T
Standard H&C power strip label sequence for 200V30–40HP /400V50–75HP: R/L1 S/L2 T/L3 ⊖ ⊕ U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 690V50–75HP: earth R S T [unlabelled position] ⊕ ⊖ [unlabelled position] U V W earth. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 200V50–60HP /400V100HP: R/L1 S/L2 T/L3 - + U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Standard H&C; source rating scope 200V30–40HP /400V50–75HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 690V50–75HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 200V50–60HP /400V100HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Terminal screw size — 200V30–40HP /400V50–75HP — PDF page 47
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M8 | M8 |
Terminal screw size — 690V50–75HP — PDF page 47
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M6 |
Terminal screw size — 200V50–60HP /400V100HP — PDF page 47
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M10 | M10 |
Manual — Two terminal-layout groups and screw sizes — page 48
Manual reference: physical PDF page 48. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Upper690V100–150HP and lower400V125HP groups are separate. Upper table has only Power supply and earth-symbol columns; do not invent an upperT-column value. Original terminal geometry retained.
Earth glyph rendered as[earth symbol] in column heading; T retained literally without expanding meaning. No torque inferred from M-size.
Label inventory only; no inferred electrical connections.
Only two physical columns in source; noTcolumn present.
Applies only to lower400V125HP caption; merged heading Terminal screw size retained in table title.
Printed diagram captions and label order — PDF page 48
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Upper applicability | 690V:100~150HP |
| 2 | Upper terminals left-to-right | R; S; T; N; P; U; V; W |
| 3 | Lower applicability | 400V:125HP |
| 4 | Lower terminals left-to-right | P; N; R; S; T; U; V; W |
Upper690V table — PDF page 48
| Source row | Power supply | [earth symbol] |
|---|---|---|
| 1 | 690V100~150HP | M10 |
Lower400V125HP terminal screw size — PDF page 48
| Source row | T | [earth symbol] |
|---|---|---|
| 1 | M10 | M10 |
Manual — Standard layouts continued and Enhanced power terminal functions — page 49
Manual reference: physical PDF page 49. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V: 75~100HP, 400V: 150~215HP, 690V: 175~270HP
200V: 125~150HP, 400V: 270~425HP
Notes: For wire gauges and screw torques, please refer to the table in section 3.6.
3.10.2 Power Terminals (For Enhanced E & G type)
Standard H&C power strip label sequence for 200V75–100HP /400V150–215HP /690V175–270HP: P N R S T U V W. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Standard H&C power strip label sequence for 200V125–150HP /400V270–425HP: P N R S T U V W. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Ground terminal label in the source table is E/PE/[earth symbol]. Native extraction omits the drawn earth symbol; this annotation restores the visible label without changing the preserved native table cell.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Section3.10.2. Printed shared function regions retained; no new wiring topology inferred. Single-phase conflict retained. The top diagrams on this physical page remain the preceding Standard H&C section.
Standard H&C; source rating scope 200V75–100HP /400V150–215HP /690V175–270HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Standard H&C; source rating scope 200V125–150HP /400V270–425HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Power terminal functions — Enhanced E&G — PDF page 49
| Source row | Terminal | 200V1–2HP;400V1–3HP &40HP-B | 200V3–30HP;400V5–75HP | 200V40–150HP;400V50–425HP |
|---|---|---|---|---|
| 1 | R/L1 | Input Power Supply (For single phase use terminals R/L1 and S/L2) | Input Power Supply (For single phase use terminals R/L1 and S/L2) | Input Power Supply (For single phase use terminals R/L1 and S/L2) |
| 2 | S/L2 | Input Power Supply (For single phase use terminals R/L1 and S/L2) | Input Power Supply (For single phase use terminals R/L1 and S/L2) | Input Power Supply (For single phase use terminals R/L1 and S/L2) |
| 3 | T/L3 | Input Power Supply (For single phase use terminals R/L1 and S/L2) | Input Power Supply (For single phase use terminals R/L1 and S/L2) | Input Power Supply (For single phase use terminals R/L1 and S/L2) |
| 4 | B1/P | B1/P-B2: external braking resistor B1/P-⊖: DC link | P2/B1-B2: external braking resistor P1-P2/B1: external DCL P1-⊖: DC link | - |
| 5 | P2/B1 | B1/P-B2: external braking resistor B1/P-⊖: DC link | P2/B1-B2: external braking resistor P1-P2/B1: external DCL P1-⊖: DC link | - |
| 6 | B2 | B1/P-B2: external braking resistor B1/P-⊖: DC link | P2/B1-B2: external braking resistor P1-P2/B1: external DCL P1-⊖: DC link | - |
| 7 | ⊖ N | B1/P-B2: external braking resistor B1/P-⊖: DC link | P2/B1-B2: external braking resistor P1-P2/B1: external DCL P1-⊖: DC link | ⊕/P1-⊖/N: Connect braking module |
| 8 | ⊕ P1 | B1/P-B2: external braking resistor B1/P-⊖: DC link | P2/B1-B2: external braking resistor P1-P2/B1: external DCL P1-⊖: DC link | ⊕/P1-⊖/N: Connect braking module |
| 9 | U/T1 | Inverter output | Inverter output | Inverter output |
| 10 | V/T2 | Inverter output | Inverter output | Inverter output |
| 11 | W/T3 | Inverter output | Inverter output | Inverter output |
| 12 | E/PE/ | Ground terminal | Ground terminal | Ground terminal |
Terminal screw size — 200V75–100HP /400V150–215HP /690V175–270HP — PDF page 49
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M10 | M10 |
Terminal screw size — 200V125–150HP /400V270–425HP — PDF page 49
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M12 | M10 |
Manual — Power terminal layouts Enhanced — page 50
Manual reference: physical PDF page 50. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V : 1 ~ 2HP , 400V : 1 ~ 3HP
200V : 3 ~7.5HP , 400V : 5 ~ 7.5HP
200V : 10HP , 400V : 10 ~ 20HP
Enhanced E&G power strip label sequence for 200V1–2HP /400V1–3HP: R/L1 S/L2 T/L3 B1/P ⊖ B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Enhanced E&G power strip label sequence for 200V3–7.5HP /400V5–7.5HP: R/L1 S/L2 T/L3 ⊖ P1 P2/B1 B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Enhanced E&G power strip label sequence for 200V10HP /400V10–20HP: R/L1 S/L2 T/L3 ⊖ P1 P2/B1 B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Enhanced E&G; source rating scope 200V1–2HP /400V1–3HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Enhanced E&G; source rating scope 200V3–7.5HP /400V5–7.5HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Enhanced E&G; source rating scope 200V10HP /400V10–20HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Adjacent source context — repeated to preserve continuation:
Terminal screw size — 200V1–2HP /400V1–3HP — PDF page 50
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M4 | M4 |
Terminal screw size — 200V10HP /400V10–20HP — PDF page 50
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M6 |
Manual — Power terminal layouts Enhanced continued — page 51
Manual reference: physical PDF page 51. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V : 15~25HP , 400V : 25 ~ 30HP
200V : 30 ~40HP , 400V : 40 ~ 75HP
400V: 40HP-B
Terminal screw size
Enhanced E&G power strip label sequence for 200V15–25HP /400V25–30HP: R/L1 S/L2 T/L3 ⊖ P1 P2/B1 B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Enhanced E&G power strip label sequence for 200V30–40HP /400V40–75HP: R/L1 S/L2 T/L3 ⊖ P1 P2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Enhanced E&G power strip label sequence for 400V40HP-B: R/L1 S/L2 T/L3 ⊖ B1/P B2 U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Enhanced E&G; source rating scope 200V15–25HP /400V25–30HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Enhanced E&G; source rating scope 200V30–40HP /400V40–75HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Enhanced E&G; source rating scope 400V40HP-B. T is source diagram callout, earth symbol is visually read; no torque inferred.
Adjacent source context — repeated to preserve continuation:
Terminal screw size — 200V15–25HP /400V25–30HP — PDF page 51
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M6 |
Terminal screw size — 200V30–40HP /400V40–75HP — PDF page 51
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M8 | M8 |
Terminal screw size — 400V40HP-B — PDF page 51
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M6 | M8 |
Manual — Power terminal layouts Enhanced continued — page 52
Manual reference: physical PDF page 52. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V : 50~60HP, 400V : 100HP
400V : 125HP
200V : 75~100HP, 400V : 150~215HP
Enhanced E&G power strip label sequence for 200V50–60HP /400V100HP: R/L1 S/L2 T/L3 ⊖ ⊕ U/T1 V/T2 W/T3. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Enhanced E&G power strip label sequence for 400V125HP: P N R S T U V W. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Enhanced E&G power strip label sequence for 200V75–100HP /400V150–215HP: P N R S T U V W. Labels and printed order retained only; no wiring route inferred. Screw sizes are separate bounded tables.
Historical manual4KA72X583T61 Ver10 2021.06. Preserve Standard H&C versus Enhanced E&G and each printed rating range; read adjacent-page/safety context. No wiring topology, current standards or engineering correctness inferred.
Enhanced E&G; source rating scope 200V50–60HP /400V100HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Enhanced E&G; source rating scope 400V125HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Enhanced E&G; source rating scope 200V75–100HP /400V150–215HP. T is source diagram callout, earth symbol is visually read; no torque inferred.
Terminal screw size — 200V50–60HP /400V100HP — PDF page 52
| Source row | T | Earth symbol terminal |
|---|---|---|
| 1 | M10 | M10 |
Manual — Terminal layout and screw-size table — page 53
Manual reference: physical PDF page 53. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Caption applies to this figure/table only, not entire A510s range. Original hole and terminal geometry retained. T and earth columns kept separate; no tightening torque inferred.
Literal label sequence, not connectivity.
Source T=M12 and earth=M10; do not flatten both toM10.
Figure labels — PDF page 53
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Applicability | 200V:125~150HP,400V:270~425HP |
| 2 | Terminals left-to-right | P; N; R; S; T; U; V; W |
Terminal screw size — PDF page 53
| Source row | T | [earth symbol] |
|---|---|---|
| 1 | M12 | M10 |
Manual — Power section reference diagrams — page 54
Manual reference: physical PDF page 54. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.11 Input / Output Power Section Block Diagram
The following diagrams 1 - 8 show the basic configuration of the power sections for the range of horsepower and input voltages. This is shown for reference only and is not a detailed depiction. (For Enhanced E & G type frame 2~5, which can connect option DC reactor, please refer to General Wiring Diagram) 1-1: 200V: 1 HP / 400V: 1 ~ 2 HP (Standard type) / 400V: 1 HP (Enhanced type)
2-1: 200V: 2 ~ 25 HP (Standard Type) / 400V: 3 ~ 40 HP (Standard Type) /40 HP-B (Enhanced Type) / 575V: 1~10HP / 690V: 15~40HP
Reference power-section diagram 1-1:200V1HP /400V1–2HP Standard /400V1HP Enhanced. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;B1/P;B2;⊖;E;DC/DC Converter;Control Circuit;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Reference power-section diagram 2-1:200V2–25HP Standard /400V3–40HP Standard /40HP-B Enhanced /575V1–10HP /690V15–40HP. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;B1/P;B2;⊖;E;DC/DC Converter;Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Manual — Power section diagrams continued — page 55
Manual reference: physical PDF page 55. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
2-2: 200V: 2 HP (Enhanced Type) / 400V: 2 ~ 3 HP (Enhanced Type)
2-3: 200V: 3 ~ 25 HP (Enhanced Type) / 400V: 3 ~ 30 HP (Enhanced Type)
L1/R
L2/S
L3/T
U/T1
V/T2
W/T3
P1 P2/ B1
Main Power Section
+
-
Control Circuit
Cooling Fan
DC /DC Converter -
E
B2
3-1: 200V: 30 ~ 40 HP (Standard Type) / 400V: 50 ~ 75 HP (Standard Type)
Reference power-section diagram 2-2:200V2HP Enhanced /400V2–3HP Enhanced. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;B1/P;B2;⊖;E;DC/DC Converter;Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Reference power-section diagram 2-3:200V3–25HP Enhanced /400V3–30HP Enhanced. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;P1;P2/B1;B2;⊖;E;DC/DC Converter;Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Reference power-section diagram 3-1:200V30–40HP Standard /400V50–75HP Standard. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;+;⊖;E;DC/DC Converter(two labels);Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Manual — Power section diagrams continued — page 56
Manual reference: physical PDF page 56. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3-2: 200V: 30 ~ 40 HP (Enhanced Type) /400V: 40 ~ 75 HP (Enhanced Type)
4: 690V: 50~75HP
5: 200V: 50 ~ 60 HP / 400V: 100 ~ 215 HP
Reference power-section diagram 3-2:200V30–40HP Enhanced /400V40–75HP Enhanced. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;P1;P2;⊖;E;DC/DC Converter(two labels);Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Reference power-section diagram 4:690V50–75HP. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;+;⊖;E;DC/DC Converter;Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Reference power-section diagram 5:200V50–60HP /400V100–215HP. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;P;N;E;DC Link Reactor;Fuse;DC/DC Converter(two labels);Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Manual — Power section diagrams continued — page 57
Manual reference: physical PDF page 57. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6: 690V: 100~150HP
7: 200V: 75, 100 HP, 125, 150 HP
8: 400V: 270HP, 300HP, 375HP, 425 HP / 690V: 175~270HP
Reference power-section diagram 6:690V100–150HP. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;P;N;E;DC Link Reactor;DC/DC Converter;Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Reference power-section diagram 7:200V75,100,125,150HP. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;P;N;E;DC Link Reactor;Fuse;DC/DC Converter;AC/DC;Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Reference power-section diagram 8:400V270,300,375,425HP /690V175–270HP. Labels:L1/R,L2/S,L3/T,U/T1,V/T2,W/T3;P;N;E;DC Link Reactor;Fuse;DC/DC Converter;AC/DC;Control Circuit;Cooling Fan;Main Power Section. Earth and polarity symbols shown. Source says reference only, not detailed depiction; no circuit topology inferred.
Manual — 400V cooling fan voltage selection — page 58
Manual reference: physical PDF page 58. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.11.1 Cooling Fan Supply Voltage Selection (400V class)
The inverter input voltage range of the A510s 400V class models ranges from 380 to 480Vac. In these
models the cooling fan is directly powered from the power supply. Inverter models A510s-4215(F8)/
4270/ 4300/ 4375/ 4425 requires the user to select the correct jumper position based on the inverter
input voltage ("400V" is the default position for these models). Please select the correct position
according to the input voltage. If the voltage setting is too low, the cooling fan will not provide adequate
cooling for the inverter resulting in an over-heat error. If the input voltage is greater than 460Vac, select
the “460V” position.
(1) 400V: 270HP~425HP
400V270–425HP fan-selection board illustration labels:TB4(220V),26CN,440V,220V,25CN,36CN,DM1,4KA69X613W01,33CN,FU1,34CN,32CN,31CN,35CN,SA4(220V),2,1,TB3,TB2,S,R,+,−; jumper labels JP1 380V,JP2 400/415,JP3 440V,JP4 460V. Example caption: input460Vac,jumper pin in460Vposition. Connector labels only; no inferred wiring.
Manual — 690V cooling fan voltage selection — page 59
Manual reference: physical PDF page 59. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny embedded Chinese board descriptor/silkscreen and lower-left board mark remain unreadable after enlarged visual reading; source-image retained.
The inverter input voltage range of the A510s 600V class models ranges from 575 to 690Vac. In these models the cooling fan is directly powered from the power supply. Inverter models A510s-6175~6270 requires the user to select the correct jumper position based on the inverter input voltage ("690V" is the default position for these models). Please select the correct position according to the input voltage. If the voltage setting is too low, the cooling fan will not provide adequate cooling for the inverter resulting in an over-heat error. If the input voltage is greater than 690Vac, select the “690V” position.
(2) 690V: 175HP~270HP
690V175–270HP fan-selection board: enlarged reading identifies4KA69X77LH01;33CN,FU1,26CN,32CN,31CN,34CN,35CN,25CN,36CN,2,1,TB2,S,R,690V;JP1 575V,JP2 630V,JP3 690V,JP4 760V;board drawing190(mm)by40(mm). Small Chinese descriptor/silkscreen and lower-left board mark remain unreadable in embedded raster after enlargement; preserved source-image-only, not guessed. No wiring inferred.
690V175–270HP; paragraph conflicts with high-range table row. Historical source values, not validated electrical instructions.
Cooling fan voltage selection — PDF page 59
| Source row | Input voltage range Vac | Voltage selection board position |
|---|---|---|
| 1 | 510 ~ 600 | 575V |
| 2 | 601 ~ 660 | 630V |
| 3 | 661 ~ 720 | 690V |
| 4 | 721 ~ 759 | 760V |
Manual — Wiring precautions and grounding — page 60
Manual reference: physical PDF page 60. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.12 Inverter Wiring
Wiring Precautions
!
• Do NOT remove any protective covers or attempt any wiring while input power is applied. Connect all wiring before applying input power. When making wiring changes after power up, remove input power and wait a minimum of five minutes after power has been turned off before starting. Also confirm that the charge lamp is off and that DC voltage between terminals B1/P or (+) and (-) does not exceed 25V, otherwise electric shock may result. • Only authorized personnel should work on the equipment. (Take off metal jewelry such as watches and rings and use insulated tools.), otherwise electric shock or injury may result.
(A) Power input terminals 1. The Input power supply voltage can be connected in any phase sequence to power input terminals R/L1, S/L2, or T/L3 on the terminal block. 2. DO NOT connect the AC input power source to the output terminals U/T1, V/T2 and. W/T3. 3. Connect the output terminals U/T1, V/T2, W/T3 to motor lead wires U/T1, V/T2, and W/T3, respectively. 4. Check that the motor rotates forward with the forward run source. If it does not, swap any 2 of the output cables to change motor direction. 5. DO NOT connect phase correcting capacitors or LC/RC noise filter to the output circuit.
(B) Grounding 1. Connect the ground terminal (E) to ground having a resistance of less than 100Ω. 2. Do not share the ground wire with other devices, such as welding machines or power tools. 3. Always use a ground wire that complies with the local codes and standards for electrical equipment and minimize the length of ground wire. 4. When using more than one inverter, be careful not to loop the ground wire, as shown below in Fig. 3.12.1.
Fig. 3.12.1 Inverter Grounding
Fig3.12.1 Inverter Grounding labels:A510s(repeated),a)Correct,b)Correct,c)Incorrect,Loop;earth symbols. Diagram topology not inferred; source paragraphs retained.
Manual — Cable length and carrier frequency — page 61
Manual reference: physical PDF page 61. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.13 Input Power and Motor Cable Length
The length of the cables between the input power source and /or the motor and inverter can cause a significant phase to phase voltage reduction due to the voltage drop across the cables. The wire size shown in Tables 3.16.1 is based on a maximum voltage drop of 2%. If this value is exceeded, a wire size having larger diameter may be needed. To calculate phase tot phase voltage drop, apply the following formula:
Phase-to-phase voltage drop (V) = 3 ×resistance of wire (Ω/km) × length of line( m) × current (A) × 10-3. (km=3280 x feet) (m=3.28 x feet)
3.14 Cable Length vs. Carrier Frequency
The allowable setting of the PWM carrier frequency is also determined by motor cable length and is specified in the following Table 3.14.1.
Table 3.14.1 Cable Length vs. Carrier Frequency
3.15 Installing an AC Line Reactor
If the inverter is connected to a large-capacity power source (600kVA or more), install an optional AC reactor on the input side of the inverter. This also improves the power factor on the power supply side.
Printed equation:Phase-to-phase voltage drop(V)=√3 ×resistance of wire(Ω/km)×length of line(m)×current(A)×10⁻³. Printed conversions(km=3280 x feet),(m=3.28 x feet). Literalsource retained; conversion-direction issue flagged.
Table3.14.1; m(ft) and maximum kHz. ≥100 glyph verified visually; native may omit underline. No general override of model/control-mode derating.
Cable length vs carrier frequency — PDF page 61
| Source row | Source row heading | Printed range1 | Printed range2 | Printed range3 | Printed range4 |
|---|---|---|---|---|---|
| 1 | Cable length between the inverter and Motor in m (ft.). | < 30m (100) | 30 – 50 (100 – 165) | 50 – 100 (166 - 328) | ≥ 100 (329) |
| 2 | Recommended carrier frequency allowed Parameter 11-01 | 16kHz (max) | 10 kHz (max) | 5 kHz (max) | 2 kHz (max) |
Manual — Wiring instruments200/400V — page 62
Manual reference: physical PDF page 62. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.16 Power Input Wire Size, NFB and MCB Part Numbers
The following table shows the recommended wire size, molded case circuit breakers and magnetic contactors for each of the A510S models. It depends on the application whether or not to install a circuit breaker. The NFB must be installed between the input power supply and the inverter input (R/L1, S/L2, T/L3).
Note: When using a ground protection make sure the current setting is above 200mA and trip delay time is 0.1 sec of higher.
Table 3.16.1 Wiring instrument for 200V/400V class
Table3.16.1 continues across62–64. Source blank power groups on63are400V3phase continued from62;first64row575V3phase continued from63. Blank source cells remain blank. Notes on64 retained; source recommendations not verified sizing.
Wiring instrument recommendations — PDF page 62
| Source row | Power/phase | HP*1 | Rated kVA HD/ND | Rated current A HD/ND | Main circuit AWG(mm²)*2 | Ground E(G) AWG(mm²) | Control AWG(mm²)*3 | NFB*4 | MC*4 |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 200V 1 Ø/3Ø | 1HP | 1.9/2.3 | 5/6 | 14~10 (2~5.3) | 14~10 (2~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
| 2 | 200V 1 Ø/3Ø | 2HP | 3/3.7 | 8/9.6 | 14~10 (2~5.3) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(20A) | CU-11 |
| 3 | 200V 1 Ø/3Ø | 3HP | 4.2/4.6 | 11/12 | 11~10 (3.5~5.3) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(30A) | CU-11 |
| 4 | 200V 3 Ø | 5HP | 6.7/8.4 | 17.5/22 | 10 (5.3) | 10 (5.3) | 30~14 (0.5~2) | TO-50EC(30A) | CU-16 |
| 5 | 200V 3 Ø | 7.5HP | 9.5/11.4 | 25/30 | 8 (8.4) | 10~8 (5.3~8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-18 |
| 6 | 200V 3 Ø | 10HP | 12.6/16.0 | 33/42 | 8 (8.4) | 10~8 (5.3~8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-25 |
| 7 | 200V 3 Ø | 15HP | 17.9/21.3 | 47/56 | 6 (13.3) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(100A) | CU-50 |
| 8 | 200V 3 Ø | 20HP | 22.9/26.3 | 60/69 | 4 (21.2) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(100A) | CU-65 |
| 9 | 200V 3 Ø | 25HP | 27.8/30.1 | 73/80 | 4 (21.2) | 6 (13.3) | 30~14 (0.5~2) | TO-225S(100A) | CU-80 |
| 10 | 200V 3 Ø | 30HP | 32.4/41.9 | 85/110 | 2 (33.6) | 6 (13.3) | 30~14 (0.5~2) | TO-225S(150A) | CN-100 |
| 11 | 200V 3 Ø | 40HP | 43.8/52.6 | 115/138 | 2/0 (67.4) | 4 (21.2) | 30~14 (0.5~2) | TO-225S(175A) | CN-125 |
| 12 | 200V 3 Ø | 50HP | 55.3/64.4 | 145/169 | 3/0 (85) | 4 (21.2) | 30~14 (0.5~2) | TO-225S(200A) | CN-150 |
| 13 | 200V 3 Ø | 60HP | 68.6/76.2 | 180/200 | 4/0 (107.2) | 4 (21.2) | 30~14 (0.5~2) | TO-225S(225A) | CN-180 |
| 14 | 200V 3 Ø | 75HP | 81.9/95.3 | 215/250 | 300 (152) | 4 (21.2) | 30~14 (0.5~2) | TO-400S(300A) | CN-300 |
| 15 | 200V 3 Ø | 100HP | 108/118.9 | 283/312 | 400 (200) | 2 (33.62) | 30~14 (0.5~2) | TO-400S(400A) | CN-300 |
| 16 | 200V 3 Ø | 125HP | 132/137.2 | 346/400 | 600 (300) | 2 (33.62) | 30~14 (0.5~2) | TO-400S(400A) | SK-400 |
| 17 | 200V 3 Ø | 150HP | 158/172 | 415/450 | 500*2P (250*2P) | 1/0 (50) | 30~14 (0.5~2) | TO-800S(800A) | SK-600 |
| 18 | 400V 3 Ø | 1HP | 2.6/3.1 | 3.4/4.1 | 14~10 (2~5.3) | 14~10 (2~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
| 19 | 400V 3 Ø | 2HP | 3.2/4.1 | 4.2/5.4 | 14~10 (2~5.5) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
Manual — Wiring instruments400/575V — page 63
Manual reference: physical PDF page 63. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table3.16.1 continues across62–64. Source blank power groups on63are400V3phase continued from62;first64row575V3phase continued from63. Blank source cells remain blank. Notes on64 retained; source recommendations not verified sizing.
Wiring instrument recommendations — PDF page 63
| Source row | Power/phase | HP*1 | Rated kVA HD/ND | Rated current A HD/ND | Main circuit AWG(mm²)*2 | Ground E(G) AWG(mm²) | Control AWG(mm²)*3 | NFB*4 | MC*4 |
|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | 3HP | 4.2/5.3 | 5.5/6.9 | 14~10 (2~5.5) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
| 2 | ⟦blank source cell⟧ | 5HP | 7/9.2 | 9.2/12.1 | 14~10 (2~5.5) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-18 |
| 3 | ⟦blank source cell⟧ | 7.5HP | 11.3/13.3 | 14.8/17.5 | 10 (5.3) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(20A) | CU-18 |
| 4 | ⟦blank source cell⟧ | 10HP | 13.7/17.5 | 18/23 | 10 (5.3) | 10 (5.3) | 30~14 (0.5~2) | TO-50EC(30A) | CU-25 |
| 5 | ⟦blank source cell⟧ | 15HP | 18.3/23.6 | 24/31 | 8 (8.4) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-25 |
| 6 | ⟦blank source cell⟧ | 20HP | 23.6/29.0 | 31/38 | 8 (8.4) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-35 |
| 7 | ⟦blank source cell⟧ | 25HP | 29.7/33.5 | 39/44 | 8 (8.4) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-50 |
| 8 | ⟦blank source cell⟧ | 30HP | 34.3/44.2 | 45/58 | 6 (13.3) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(75A) | CU-50 |
| 9 | ⟦blank source cell⟧ | 40HP | 45.7/55.6 | 60/73 | 4 (21.2) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(100A) | CU-65 |
| 10 | ⟦blank source cell⟧ | 50HP | 57.2/67.1 | 75/88 | 4 (21.2) | 6 (13.3) | 30~14 (0.5~2) | TO-100S(100A) | CU-80 |
| 11 | ⟦blank source cell⟧ | 60HP | 69.3/78.5 | 91/103 | 2 (33.62) | 6 (13.3) | 30~14 (0.5~2) | TO-225S(150A) | CN-100 |
| 12 | ⟦blank source cell⟧ | 75HP | 89.9/111 | 118/145 | 2/0 (67.4) | 4 (21.2) | 30~14 (0.5~2) | TO-225S(175A) | CN-125 |
| 13 | ⟦blank source cell⟧ | 100HP | 114/128 | 150/168 | 3/0 (85) | 4 (21.2) | 30~14 (0.5~2) | TO-225S(225A) | CN-150 |
| 14 | ⟦blank source cell⟧ | 125HP | 137/159 | 180/208 | 300 (152) | 4 (21.2) | 30~14 (0.5~2) | TO-400S(300A) | CN-300 |
| 15 | ⟦blank source cell⟧ | 150HP | 165/191 | 216/250 | 300 (152) | 4 (21.2) | 30~14 (0.5~2) | TO-400S(300A) | CN-300 |
| 16 | ⟦blank source cell⟧ | 175HP | 198/226 | 260/296 | 400 (200) | 2 (33.62) | 30~14 (0.5~2) | TO-400S(400A) | CN-300 |
| 17 | ⟦blank source cell⟧ | 215HP | 225/250 | 295/328 | 500 (250) | 2 (33.62) | 30~14 (0.5~2) | TO-400S(400A) | CN-300 |
| 18 | ⟦blank source cell⟧ | 270HP | 290/332 | 380/435 | 600 (300) | 2 (33.62) | 30~14 (0.5~2) | TO-400S(400A) | SK-400 |
| 19 | ⟦blank source cell⟧ | 300HP | 343/393 | 450/515 | 500*2P (250*2P) | 1/0 (50) | 30~14 (0.5~2) | TO-800S(800A) | SK-600 (800A) |
| 20 | ⟦blank source cell⟧ | 375HP | 400/446 | 523/585 | 500*2P (250*2P) | 1/0 (50) | 30~14 (0.5~2) | TE-1000(1000A) | SK-600 (800A) |
| 21 | ⟦blank source cell⟧ | 425HP | 446/446 | 585/585 | 500*2P (250*2P) | 1/0 (50) | 30~14 (0.5~2) | TE-1000(1000A) | SK-600 (800A) |
| 22 | 575V 3 Ø | 1HP | 1.7/3.0 | 1.7/3.0 | 14~10 (2~5.3) | 14~10 (2~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
| 23 | 575V 3 Ø | 2HP | 3/4.2 | 3/4.2 | 14~10 (2~5.3) | 14~10 (2~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
| 24 | 575V 3 Ø | 3HP | 4.2/5.8 | 4.2/5.8 | 14~10 (2~5.3) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
| 25 | 575V 3 Ø | 5HP | 6.6/8.8 | 6.6/8.8 | 14~10 (2~5.3) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-11 |
| 26 | 575V 3 Ø | 7.5HP | 9.9/12.1 | 9.9/12.2 | 11~10 (3.5~5.3) | 11~10 (3.5~5.3) | 30~14 (0.5~2) | TO-50EC(15A) | CU-18 |
Manual — Wiring instruments575/690V and footnotes — page 64
Manual reference: physical PDF page 64. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
*1: Constant torque rating.
*2: The main circuit terminals: R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, B1/P, B2, ⊖, ○+
*3: Control line is the terminal wire on the control board.
*4: The NFB and MCB listed in the table are of TECO product numbers, products with same rated specification of
other brands may be used. To reduce electrical noise interference, ensure that a RC surge absorber (R: 10Ω/
5W, C: 0.1μf/1000VDC) is added to both sides of MCB coil.
Table3.16.1 continues across62–64. Source blank power groups on63are400V3phase continued from62;first64row575V3phase continued from63. Blank source cells remain blank. Notes on64 retained; source recommendations not verified sizing.
Wiring instrument recommendations — PDF page 64
| Source row | Power/phase | HP*1 | Rated kVA HD/ND | Rated current A HD/ND | Main circuit AWG(mm²)*2 | Ground E(G) AWG(mm²) | Control AWG(mm²)*3 | NFB*4 | MC*4 |
|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | 10HP | 11.4/14.4 | 11.4/14.5 | 11~10 (3.5~5.3) | 10 (5.3) | 30~14 (0.5~2) | TO-50EC(20A) | CU-25 |
| 2 | 575~690V 3 Ø | 15HP | 17.9/22.7 | 15/19 | 10 (5.3) | 8 (8.4) | 30~14 (0.5~2) | TO-50EC(30A) | CU-25 |
| 3 | 575~690V 3 Ø | 20HP | 22.7/26.3 | 19/22 | 8 (8.4) | 8 (8.4) | 30~14 (0.5~2) | TO-50EC(30A) | CU-35 |
| 4 | 575~690V 3 Ø | 25HP | 26.3/32.3 | 22/27 | 8 (8.4) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-35 |
| 5 | 575~690V 3 Ø | 30HP | 32.3/40.6 | 27/34 | 8 (8.4) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-50 |
| 6 | 575~690V 3 Ø | 40HP | 40.6/50.2 | 34/42 | 8 (8.4) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(50A) | CU-50 |
| 7 | 575~690V 3 Ø | 50HP | 50.2/62.1 | 42/52 | 6 (13.3) | 8 (8.4) | 30~14 (0.5~2) | TO-100S(75A) | CU-65 |
| 8 | 575~690V 3 Ø | 60HP | 64.5/74.1 | 54/62 | 6 (13.3) | 6 (13.3) | 30~14 (0.5~2) | TO-100S(100A) | CU-80 |
| 9 | 575~690V 3 Ø | 75HP | 74.1/95.6 | 62/80 | 4 (21.2) | 6 (13.3) | 30~14 (0.5~2) | TO-225S(150A) | CN-100 |
| 10 | 575~690V 3 Ø | 100HP | 103/118 | 86/99 | 2 (33.62) | 4 (21.2) | 30~14 (0.5~2) | TO-225S(150A) | CN-125 |
| 11 | 575~690V 3 Ø | 125HP | 114/149 | 99/125 | 2/0 (67.4) | 2 (33.62) | 30~14 (0.5~2) | TO-225S(175A) | CN-150 |
| 12 | 575~690V 3 Ø | 150HP | 157/175 | 131/147 | 2/0 (67.4) | 2/0 (67.4) | 30~14 (0.5~2) | TO-225S(175A) | CN-150 |
| 13 | 575~690V 3 Ø | 175HP | 176/194 | 147/163 | 3/0 (85) | 2/0 (67.4) | 30~14 (0.5~2) | TO-225S(225A) | CN-300 |
| 14 | 575~690V 3 Ø | 215HP | 195/253 | 163/212 | 300 (152) | 3/0 (85) | 30~14 (0.5~2) | TO-225S(225A) | CN-300 |
| 15 | 575~690V 3 Ø | 250HP | 230/258 | 192/216 | 300 (152) | 300 (152) | 30~14 (0.5~2) | TO-400S(400A) | CN-300 |
| 16 | 575~690V 3 Ø | 270HP | 258/294 | 216/246 | 300 (152) | 300 (152) | 30~14 (0.5~2) | TO-400S(400A) | CN-300 |
Manual — Control wiring and shield/relay figures — page 65
Manual reference: physical PDF page 65. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.17 Control Circuit Wiring
(1) Separate the wiring for control circuit terminals from main circuit wiring for terminals (R/L1, S/L2, T/L3, U/T1, V/T2, W/T3). (2) Separate the wiring for control circuit terminals R1A-R1B-R1C (or R2A, R2C) (Relay outputs) from wiring for terminals ① - ⑧, A01, A02, GND, DO1, DO2, DOG, +10V, (-10V), AI1, AI2 and GND wiring. (3) Use shielded twisted-pair cables (#24 - #14 AWG / 0.5 -2 mm2) shown in Fig. 3.17.1 for control circuits to minimize noise problems. The maximum wiring distance should not exceed 50m (165 ft).
Fig. 3.17.1 Shielded Twisted-Pair
(4) When the digital multi-function output terminals (DO1, DO2) are connected to an external relay, a freewheeling diode should be connected across the relay coil to prevent an inductive voltage spike from damaging the output circuitry as shown in Fig. 3.17.2 below.
- 48V max.
A510S
DO1, DO2
Free-wheeling diode (100V, > 100mA)
50 mA max.
Relay Coil
Fig. 3.17.2 Photo-Coupler Connected to an External Relay
Fig3.17.1 Shielded Twisted-Pair labels:Shield;Wrap with insulating Tape;Twisted Pair;Ground Shield at Inverter end ONLY;DO NOT Ground Shield at this end. Source labels only, not inferred connection topology.
Fig3.17.2 Photo-Coupler Connected to an External Relay labels:DO1,DO2;A510S;50mA max.;Relay Coil;+48Vmax.;Free-wheeling diode(100V,>100mA). Source labels only; no inferred polarity/route.
Manual — Sink/source interface figures — page 66
Manual reference: physical PDF page 66. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(5) In Section 3.8 the control boards referenced have a jumper SW3 that can select the digital input to terminals ① - ⑧ to be set for SINK or SOURCE. The following Fig. 3.17.3 (a.) – (d.) shows examples for the various SINK / Source interfaces.
24VG
Sink
Source
NPN
+24V
Input Digital Terminals S1 - S8 Input Digital Terminals S1 - S8
(a.) Open Collector Interface (b.) NPN Sensor Interface
Sink Configuration
Input Digital Terminals S1 - S8
(c.) Open Collector Interface
Source Configuration
(d.) PNP Sensor Interface
PNP
SW3 SW3
SW3
Fig. 3.17.3 Sink / Source Configurations
Fig3.17.3 Sink(a)Open Collector Interface labels:SW3;Source;Sink;Input Digital Terminals S1–S8;24VG. No selector position or circuit route inferred. SW3 reference conflicts with Enhanced SW6 elsewhere.
Fig3.17.3 Sink(b)NPN Sensor Interface labels:SW3;Source;Sink;+24V;NPN;Input Digital Terminals S1–S8;24VG. No selector position or circuit route inferred. SW3 reference conflicts with Enhanced SW6 elsewhere.
Fig3.17.3 Source(c)Open Collector Interface labels:SW3;Source;Sink;+24V;Input Digital Terminals S1–S8. No selector position or circuit route inferred. SW3 reference conflicts with Enhanced SW6 elsewhere.
Fig3.17.3 Source(d)PNP Sensor Interface labels:SW3;Source;Sink;+24V;PNP;Input Digital Terminals S1–S8;24VG. No selector position or circuit route inferred. SW3 reference conflicts with Enhanced SW6 elsewhere.
Manual — Basic specifications200V — page 67
Manual reference: physical PDF page 67. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.18 Inverter Specifications
Basic Specifications 200V class
Original output-rated performance, source HD150%/1min and ND120%/1min. HP and(kW) kept in same source cell. No interpolation or rating reconciliation.
Full shared cells repeat only where actual source geometry spans both positions. A split rated-input row is retained by physical regions; do not infer individual HP applicability where its border crosses capacity columns.
Basic specifications 200V table1 — PDF page 67
| Source row | Duty/source grouping | Measurement | 1 HP capacity | 2 HP capacity | 3 HP capacity | 5 HP capacity | 7.5 HP capacity | 10 HP capacity | 15 HP capacity | 20 HP capacity | 25 HP capacity |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Heavy Duty type H.D. (150%/1min) | Rated output Capacity (KVA) | 1.9 | 3 | 4.2 | 6.7 | 9.5 | 12.6 | 17.9 | 22.9 | 27.8 |
| 2 | Heavy Duty type H.D. (150%/1min) | Rated output current (A) | 5 | 8 | 11 | 17.5 | 25 | 33 | 47 | 60 | 73 |
| 3 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) | 1 (0.75) | 2 (1.5) | 3 (2.2) | 5 (3.7) | 7.5 (5.5) | 10 (7.5) | 15 (11) | 20 (15) | 25 (18.5) |
| 4 | Heavy Duty type H.D. (150%/1min) | Motor rated current (A) *1 | 3.4 | 6.1 | 8.7 | 13.5 | 20.1 | 25.1 | 36.7 | 50.3 | 62.9 |
| 5 | Normal Duty type N.D. (120%/1min) | Rated output Capacity (KVA) | 2.3 | 3.7 | 4.6 | 8.4 | 11.4 | 16.0 | 21.3 | 26.3 | 30.1 |
| 6 | Normal Duty type N.D. (120%/1min) | Rated output current (A) | 6 | 9.6 | 12 | 22 | 30 | 42 | 56 | 69 | 80 |
| 7 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) | 2 (1.5) | 3 (2.2) | 5 (3.7) | 7.5 (5.5) | 10 (7.5) | 15 (11) | 20 (15) | 25 (18.5) | 30 (22) |
| 8 | Normal Duty type N.D. (120%/1min) | Motor rated current (A) *1 | 6.1 | 8.7 | 13.5 | 20.1 | 25.1 | 36.7 | 50.3 | 62.9 | 72.9 |
Common power specifications 200V table1 — PDF page 67
| Source row | Source measurement | Left printed value region | Right printed value region |
|---|---|---|---|
| 1 | The maximum output voltage (V) | 3-phase, 200V ~ 240V | 3-phase, 200V ~ 240V |
| 2 | The maximum output frequency (Hz) | Based on parameter setting 0.1~599.0 Hz | Based on parameter setting 0.1~599.0 Hz |
| 3 | Rated voltage, frequency | Single/3-phase 200V~240V, 50/60Hz | 3-phase 200V~240V, 50/60Hz |
| 4 | Allowable voltage fluctuation | -15% ~ +10% | -15% ~ +10% |
| 5 | Allowable frequency fluctuation | ±5% | ±5% |
Basic specifications 200V table2 — PDF page 67
| Source row | Duty/source grouping | Measurement | 30 HP capacity | 40 HP capacity | 50 HP capacity | 60 HP capacity | 75 HP capacity | 100 HP capacity | 125 HP capacity | 150 HP capacity |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Heavy Duty type H.D. (150%/1min) | Rated output Capacity (KVA) | 32.4 | 43.8 | 55.3 | 68.6 | 81.9 | 108 | 132 | 158 |
| 2 | Heavy Duty type H.D. (150%/1min) | Rated output current (A) | 85 | 115 | 145 | 180 | 215 | 283 | 346 | 415 |
| 3 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) | 30 (22) | 40 (30) | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) |
| 4 | Heavy Duty type H.D. (150%/1min) | Motor rated current (A) *1 | 72.9 | 96.7 | 124 | 143.5 | 183.5 | 230 | 272 | 344 |
| 5 | Normal Duty type N.D. (120%/1min) | Rated output Capacity (KVA) | 41.9 | 52.6 | 64.4 | 76.2 | 95.3 | 118.9 | 152.4 | 172 |
| 6 | Normal Duty type N.D. (120%/1min) | Rated output current (A) | 110 | 138 | 169 | 200 | 250 | 312 | 400 | 450 |
| 7 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) | 40 (30) | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) | 175 (130) |
| 8 | Normal Duty type N.D. (120%/1min) | Motor rated current (A) *1 | 96.7 | 124 | 143.5 | 183.5 | 230 | 272 | 344 | 370 |
Manual — Basic specifications400V — page 68
Manual reference: physical PDF page 68. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Basic Specifications 400V class
Original output-rated performance, source HD150%/1min and ND120%/1min. HP and(kW) kept in same source cell. No interpolation or rating reconciliation.
Full shared cells repeat only where actual source geometry spans both positions. A split rated-input row is retained by physical regions; do not infer individual HP applicability where its border crosses capacity columns.
Basic specifications 400V table1 — PDF page 68
| Source row | Duty/source grouping | Measurement | 1 HP capacity | 2 HP capacity | 3 HP capacity | 5 HP capacity | 7.5 HP capacity | 10 HP capacity | 15 HP capacity | 20 HP capacity | 25 HP capacity | 30 HP capacity |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Heavy Duty type H.D. (150%/1min) | Rated output Capacity (KVA) | 2.6 | 3.2 | 4.2 | 7 | 11.3 | 13.7 | 18.3 | 23.6 | 29.7 | 34.3 |
| 2 | Heavy Duty type H.D. (150%/1min) | Rated output current (A) | 3.4 | 4.2 | 5.5 | 9.2 | 14.8 | 18 | 24 | 31 | 39 | 45 |
| 3 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) | 1 (0.75) | 2 (1.5) | 3 (2.2) | 5 (3.7) | 7.5 (5.5) | 10 (7.5) | 15 (11) | 20 (15) | 25 (18.5) | 30 (22) |
| 4 | Heavy Duty type H.D. (150%/1min) | Motor rated current (A)*1 | 1.7 | 3.1 | 4.2 | 7 | 10.1 | 12.6 | 18.6 | 24.8 | 31.1 | 36.3 |
| 5 | Normal Duty type N.D. (120%/1min) | Rated output Capacity (KVA) | 3.1 | 4.1 | 5.3 | 9.2 | 13.3 | 17.5 | 23.6 | 29.0 | 33.5 | 44.2 |
| 6 | Normal Duty type N.D. (120%/1min) | Rated output current (A) | 4.1 | 5.4 | 6.9 | 12.1 | 17.5 | 23 | 31 | 38 | 44 | 58 |
| 7 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) | 2 (1.5) | 3 (2.2) | 5 (3.7) | 7.5 (5.5) | 10 (7.5) | 15 (11) | 20 (15) | 25 (18.5) | 30 (22) | 40 (30) |
| 8 | Normal Duty type N.D. (120%/1min) | Motor rated current (A)*1 | 3.1 | 4.2 | 7 | 10.1 | 12.6 | 18.6 | 24.8 | 31.1 | 36.3 | 48.7 |
Common power specifications 400V table1 — PDF page 68
| Source row | Source measurement | Left printed value region | Right printed value region |
|---|---|---|---|
| 1 | The maximum output voltage (V) | 3-phase 380V~ 480V | 3-phase 380V~ 480V |
| 2 | The maximum output frequency (Hz) | Based on parameter setting 0.1~599.0 Hz | Based on parameter setting 0.1~599.0 Hz |
| 3 | Rated voltage, frequency | 3-phase 380V ~ 480V, 50/60Hz | 3-phase 380V ~ 480V, 50/60Hz |
| 4 | Allowable voltage fluctuation | -15% ~ +10% | -15% ~ +10% |
| 5 | Allowable frequency fluctuation | ±5% | ±5% |
Basic specifications 400V table2 — PDF page 68
| Source row | Duty/source grouping | Measurement | 40 HP capacity | 50 HP capacity | 60 HP capacity | 75 HP capacity | 100 HP capacity | 125 HP capacity | 150 HP capacity | 175 HP capacity | 215 HP capacity |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Heavy Duty type H.D. (150%/1min) | Rated output Capacity (KVA) | 45.7 | 57.2 | 69.3 | 89.9 | 114 | 137 | 165 | 198 | 225 |
| 2 | Heavy Duty type H.D. (150%/1min) | Rated output current (A) | 60 | 75 | 91 | 118 | 150 | 180 | 216 | 260 | 295 |
| 3 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) | 40 (30) | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) | 175 (132) | 215 (160) |
| 4 | Heavy Duty type H.D. (150%/1min) | Motor rated current (A)*1 | 48.7 | 59 | 70.5 | 88 | 114 | 145 | 175 | 205 | 248 |
| 5 | Normal Duty type N.D. (120%/1min) | Rated output Capacity (KVA) | 55.6 | 67.1 | 78.5 | 111 | 128 | 159 | 191 | 226 | 250 |
| 6 | Normal Duty type N.D. (120%/1min) | Rated output current (A) | 73 | 88 | 103 | 145 | 168 | 208 | 250 | 296 | 328 |
| 7 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) | 175 (132) | 215 (160) | 250 (185) |
| 8 | Normal Duty type N.D. (120%/1min) | Motor rated current (A)*1 | 59 | 70.5 | 88 | 114 | 145 | 175 | 205 | 248 | 270 |
Common power specifications 400V table2 — PDF page 68
| Source row | Source measurement | Left printed value region | Right printed value region |
|---|---|---|---|
| 1 | The maximum output voltage (V) | 3-phase 380V~480V | 3-phase 380V~480V |
| 2 | The maximum output frequency (Hz) | Based on parameter setting 0.1~599.0 Hz | Based on parameter setting 0.1~599.0 Hz |
| 3 | Rated voltage, frequency | 3-phase 380V ~ 480V, 50/60Hz | 3-phase 380V ~ 480V, 50/60Hz |
| 4 | Allowable voltage fluctuation | -15% ~ +10% | -15% ~ +10% |
| 5 | Allowable frequency fluctuation | ±5% | ±5% |
Manual — Basic specifications400V and575/690V — page 69
Manual reference: physical PDF page 69. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Basic Specifications 575/690V class
Original output-rated performance, source HD150%/1min and ND120%/1min. HP and(kW) kept in same source cell. No interpolation or rating reconciliation.
Full shared cells repeat only where actual source geometry spans both positions. A split rated-input row is retained by physical regions; do not infer individual HP applicability where its border crosses capacity columns.
Basic specifications 400V table1 — PDF page 69
| Source row | Duty/source grouping | Measurement | 270 HP capacity | 300 HP capacity | 375 HP capacity | 425 HP capacity |
|---|---|---|---|---|---|---|
| 1 | Heavy Duty type H.D. (150%/1min) | Rated Output capacity (KVA) | 290 | 343 | 400 | 446 |
| 2 | Heavy Duty type H.D. (150%/1min) | Rated output current (A) | 380 | 450 | 523 | 585 |
| 3 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) | 270 (200) | 300 (220) | 375 (280) | 425 (315) |
| 4 | Heavy Duty type H.D. (150%/1min) | Motor rated current (A)*1 | 300 | 348 | 465 | 500 |
| 5 | Normal Duty type N.D. (120%/1min) | Rated Output capacity (KVA) | 332 | 393 | 446 | 446 |
| 6 | Normal Duty type N.D. (120%/1min) | Rated output current (A) | 435 | 515 | 585 | 585 |
| 7 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) | 300 (220) | 335 (250) | 425 (315) | 425 (315) |
| 8 | Normal Duty type N.D. (120%/1min) | Motor rated current (A)*1 | 348 | 465 | 500 | 615 |
Common power specifications 400V table1 — PDF page 69
| Source row | Source measurement | Left printed value region | Right printed value region |
|---|---|---|---|
| 1 | The maximum output voltage (V) | 3-phase 380V~480V | 3-phase 380V~480V |
| 2 | The maximum output frequency (Hz) | Based on parameter setting 0.1~ 599.0 Hz | Based on parameter setting 0.1~ 599.0 Hz |
| 3 | Rated voltage, frequency | 3-phase 380V ~ 480V, 50/60Hz | 3-phase 380V ~ 480V, 50/60Hz |
| 4 | Allowable voltage fluctuation | -15% ~ +10% | -15% ~ +10% |
| 5 | Allowable frequency fluctuation | ±5% | ±5% |
Basic specifications 575/690V table2 — PDF page 69
| Source row | Duty/source grouping | Measurement | 1 HP capacity | 2 HP capacity | 3 HP capacity | 5 HP capacity | 7.5 HP capacity | 10 HP capacity | 15 HP capacity | 20 HP capacity | 25 HP capacity | 30 HP capacity |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Rated output Capacity (KVA) | Rated output Capacity (KVA) | 1.7 | 3.0 | 4.2 | 6.6 | 9.9 | 11.4 | 17.9 | 22.7 | 26.3 | 32.3 |
| 2 | Heavy Duty type H.D. (150%/1min) | Rated output current (A) | 1.7 | 3.0 | 4.2 | 6.6 | 9.9 | 11.4 | 15 | 19 | 22 | 27 |
| 3 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) for 575v | 1 (0.75) | 2 (1.5) | 3 (2.2) | 5 (3.7) | 7.5 (5.5) | 10 (7.5) | 10 (7.5) | 15 (11) | 20 (15) | 25 (18.5) |
| 4 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) for 690v | 1 (0.75) | 2 (1.5) | 3 (2.2) | 5 (3.7) | 7.5 (5.5) | 10 (7.5) | 15 (11) | 20 (15) | 25 (18.5) | 30 (22) |
| 5 | Rated output Capacity (KVA) | Rated output Capacity (KVA) | 3.0 | 4.2 | 5.8 | 8.8 | 12.2 | 14.5 | 22.7 | 26.3 | 32.3 | 40.6 |
| 6 | Normal Duty type N.D. (120%/1min) | Rated output current (A) | 3.0 | 4.2 | 5.8 | 8.8 | 12.2 | 14.5 | 19 | 22 | 27 | 34 |
| 7 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) for 575v | 2 (1.5) | 3 (2.2) | 5 (3) | 7.5 (5.5) | 10 (7.5) | 15 (11) | 15 11) | 20 (15) | 25 (18.5) | 30 (22) |
| 8 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) for 690v | - | - | - | - | - | - | 20 (15) | 25 (18.5) | 30 (22) | 40 (30) |
Common power specifications 575/690V table2 — PDF page 69
| Source row | Source measurement | Left printed value region | Right printed value region |
|---|---|---|---|
| 1 | The maximum output voltage (V) | 3-phase575/690V | 3-phase575/690V |
| 2 | The maximum output frequency (Hz) | Based on parameter setting 0.1~599.0 Hz | Based on parameter setting 0.1~599.0 Hz |
| 3 | Rated voltage, frequency | 3-phase 500~600V, 50/60Hz | 3-phase 575~690V, 50/60Hz |
| 4 | Allowable voltage fluctuation | -15% ~ +10% | -15% ~ +10% |
| 5 | Allowable frequency fluctuation | ±5% | ±5% |
Manual — 575/690V specifications and carrier settings — page 70
Manual reference: physical PDF page 70. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
*1: Take TECO standard 4-pole induction motor as the base.
*2: A510s model is designed to use in heavy duty conditions, the factory setting is the HD (Heavy Duty type) mode.
*3: The overload capacity of A510s model HD (Heavy Duty) is 150% / 1min, 200% / 2sec. See the table below for the carrier
frequency default setting and range.
*4: The overload capacity of A510s model ND (Normal Duty) is 120%/1min, carrier range: 2 KHz ~ 16 KHz, the default setting
is 2 KHz. The default setting is 1.5 KHz for 575/690v inverter that over 215hp
*5: If it is greater than default carrier frequency, you need to adjust the load current based on the de-rating curve.
*6: If control mode (00-00) is set to 2 (SLV mode) and maximum frequency (01-02) is larger than 80Hz, the carrier frequency
range is 2~8 KHz.
Original output-rated performance, source HD150%/1min and ND120%/1min. HP and(kW) kept in same source cell. No interpolation or rating reconciliation.
Full shared cells repeat only where actual source geometry spans both positions. A split rated-input row is retained by physical regions; do not infer individual HP applicability where its border crosses capacity columns.
Notes1–6 retained; source blank rating cells remain blank. Do not extend a neighbouring cell into blank ratings.
Basic specifications 575/690V table1 — PDF page 70
| Source row | Duty/source grouping | Measurement | 40 HP capacity | 50 HP capacity | 60 HP capacity | 75 HP capacity | 100 HP capacity | 125 HP capacity | 150 HP capacity | 175 HP capacity | 215 HP capacity | 250 HP capacity | 270 HP capacity |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Rated output Capacity (KVA) | Rated output Capacity (KVA) | 40.6 | 50.2 | 64.5 | 74.1 | 103 | 114 | 157 | 176 | 195 | 230 | 258 |
| 2 | Heavy Duty type H.D. (150%/1min) | Rated output current (A) | 34 | 42 | 54 | 62 | 86 | 99 | 131 | 147 | 163 | 192 | 216 |
| 3 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) for 575v | 30 (22) | 40 (30) | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) | 150 (110) | 200 (150) | 200 (150) |
| 4 | Heavy Duty type H.D. (150%/1min) | Maximum applicable motor *1HP (KW) for 690v | 40 (30) | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) | 175 (132) | 215 (160) | 250 (185) | 270 (202) |
| 5 | Rated output Capacity (KVA) | Rated output Capacity (KVA) | 50.2 | 64.5 | 74.1 | 95.6 | 114 | 149 | 176 | 195 | 253 | 258 | 294 |
| 6 | Normal Duty type N.D. (120%/1min) | Rated output current (A) | 42 | 52 | 62 | 80 | 99 | 125 | 147 | 163 | 212 | 216 | 246 |
| 7 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) for 575v | 40 (30) | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) | 150 (110) | 200 (150) | 200 (150) | 250 (185) |
| 8 | Normal Duty type N.D. (120%/1min) | Maximum applicable motor *1HP (KW) for 690v | 50 (37) | 60 (45) | 75 (55) | 100 (75) | 125 (90) | 150 (110) | 175 (132) | 215 (160) | 250 (185) | 270 (202) | 335 (251) |
Common power specifications 575/690V table1 — PDF page 70
| Source row | Source measurement | Left printed value region | Right printed value region |
|---|---|---|---|
| 1 | The maximum output voltage (V) | 3-phase575/690V | 3-phase575/690V |
| 2 | The maximum output frequency (Hz) | Based on parameter setting 0.1~599.0 Hz | Based on parameter setting 0.1~599.0 Hz |
| 3 | Rated voltage, frequency | 3-phase 575~690v, 50/60Hz | 3-phase 575~690v, 50/60Hz |
| 4 | Allowable voltage fluctuation | -15% ~ +10% | -15% ~ +10% |
| 5 | Allowable frequency fluctuation | ±5% | ±5% |
Carrier frequencies 200/400V — PDF page 70
| Source row | 200V class | 400V class | HD carrier frequency range | HD carrier frequency factory setting |
|---|---|---|---|---|
| 1 | 1~20HP | 1~30HP | 2~16KHz | 8KHz |
| 2 | 25HP | - | 2~12KHz | 6KHz |
| 3 | 30~40HP | 40~50HP | 2~12KHz (*6) | 5KHz |
| 4 | 50~100HP | 60~175HP | 2~10KHz (*6) | 5KHz |
| 5 | ⟦blank source cell⟧ | 125HP | 2~10KHz | 4KHz |
| 6 | ⟦blank source cell⟧ | 215HP | 2~8KHz | 3KHz |
| 7 | 125~150HP | ⟦blank source cell⟧ | 2~5KHz | 5KHz |
| 8 | ⟦blank source cell⟧ | 270-375HP | 2~5KHz | 4KHz |
| 9 | ⟦blank source cell⟧ | 425HP | 2~5KHz | 2KHz |
Carrier frequencies 575/690V — PDF page 70
| Source row | 575V class | 690V class | HD carrier frequency range | HD carrier frequency factory setting |
|---|---|---|---|---|
| 1 | 1~10HP | - | 1.5~16KHz | 8KHz |
| 2 | 15~75HP | 15~75HP | 1.5~8KHz | 4KHz |
| 3 | 100~150HP | 100~150HP | 1.5~6KHz | 3KHz |
| 4 | 175~270HP | 175~270HP | 1.5~4KHz | 2KHz |
Manual — Control mode maximum frequencies — page 71
Manual reference: physical PDF page 71. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The following table shows maximum output frequency for each control mode.
Source merged cells repeated by exact physical span; literal400V220–425HP retained as printed; no inferred correction to270HP.
Control-mode maximum output frequency — PDF page 71
| Source row | Duty cycle | Control mode | Other settings | Maximum output frequency |
|---|---|---|---|---|
| 1 | Heavy Duty (00-27=0) | V/F V/F + PG SLV2 | maximum frequency set to 599Hz | 599Hz |
| 2 | Heavy Duty (00-27=0) | SLV | 200V 1~10HP, 400V 1~15HP | 150Hz |
| 3 | Heavy Duty (00-27=0) | SLV | 200V 15~25HP, 400V 20HP | 110Hz |
| 4 | Heavy Duty (00-27=0) | SLV | 400V 25~30HP | 100Hz |
| 5 | Heavy Duty (00-27=0) | SLV | 200V 30~100HP, 400V 40~215HP, carrier (11-01) is set as 8K or below 8K | 100Hz |
| 6 | Heavy Duty (00-27=0) | SLV | 200V 125~150HP, 400V 220~425HP, carrier (11-01) is set as 5K or below 5K | 100Hz |
| 7 | Heavy Duty (00-27=0) | SLV | 200V 30~100HP, 400V 40~175HP, carrier (11-01) is above 8K | 80Hz |
| 8 | Heavy Duty (00-27=0) | SV | unlimited | 599Hz |
| 9 | Heavy Duty (00-27=0) | PMSV | unlimited | Twice of Base frequency |
| 10 | Heavy Duty (00-27=0) | PMSLV | unlimited | 599Hz |
| 11 | Normal Duty (00-27=1) | V/F V/F + PG | maximum frequency set to 120Hz | 120Hz |
| 12 | Normal Duty (00-27=1) | SLV /SV PMSV/ PMSLV SLV2 | No normal duty mode | - |
Manual — General specifications — page 72
Manual reference: physical PDF page 72. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
General Specifications
Supplier claims only. Footnote 5/SLV2 references lack local explanatory text. No current certification or engineering validation.
General specifications — PDF page 72
| Source row | Category | Parameter | Source specification |
|---|---|---|---|
| 1 | Control characteristics | Operation mode | LCD keypad with parameter copy function (Optional Seven-segment display * 5 + LED keypad) |
| 2 | Control characteristics | Control mode | V/F, V/F+PG, SLV, SV, PMSV, PMSLV, SLV2* with space vector PWM mode |
| 3 | Control characteristics | Frequency control range | 0.1Hz~599.0Hz |
| 4 | Control characteristics | Output frequency accuracy (Temperature change) | Digital references: ±0.01%(-10 to +40°C) Analog references: ±0.1% (25°C ±10°C ) |
| 5 | Control characteristics | Speed control accuracy | ±0.1% ( vector control(SV)),±0.5% ( vector control / open-loop) |
| 6 | Control characteristics | Frequency setting resolution | Digital references: 0.01Hz, Analog references: 0.03Hz/60Hz (If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz ) |
| 7 | Control characteristics | Output frequency resolution | 0.01Hz (If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz ) |
| 8 | Control characteristics | Inverter overload | Rated output current 150%/1 min, 200%/2sec (HD mode),120%/1 min (ND mode) Factory 150%/1 min, 200%/2sec |
| 9 | Control characteristics | Frequency setting signal | 0 to +10VDC / 4 to 20mA or -10V to +10VDC and pulse input command frequency |
| 10 | Control characteristics | Acceleration / deceleration time | 0.0 - 6000.0 second (separately set acceleration and deceleration time ) |
| 11 | Control characteristics | Voltage, frequency characteristics | Custom V/f curve based on parameters |
| 12 | Control characteristics | Braking torque | About 20% |
| 13 | Control characteristics | Main control functions | Auto-tuning, Zero Servo, torque control, position control, Droop, Soft-PWM, over- voltage protection, dynamic braking, speed search, frequency traversing, instantaneous power fault restart, PID control, automatic torque compensation, automatic speed regulation, RS-485 communication standard, speed feedback control, simple PLC function, 2 sets of analog outputs, safety switch. |
| 14 | Control characteristics | Other functions | Accumulated power-on / run time, 30 sets of fault history records and latest fault record state, energy-saving function setting, single phase protection, smart braking, DC braking, Dwell, S curve acceleration and deceleration, Up / Down operation, MODBUS protocol, pulse output, engineering units, SINK / SOURCE digital inputs, RTC function (only for enhanced LCD type). |
| 15 | Control characteristics | Efficiency | Meet IEC/EN 61800-9-2 IE2 Class |
| 16 | Protection functions | Stall protection | Stall prevention level can be set independently in acceleration, deceleration and constant speed. |
| 17 | Protection functions | Instantaneous over current (OC) and output short-circuit (SC) protection | Inverter stops when the output current exceeds 200% of the inverter rated current. |
| 18 | Protection functions | Inverter overload Protection (OL2) | HD mode: If inverter rated current 150%/1 min., or 200%/2sec is exceeded inverter stops, factory default carrier frequency setting is 8~2KHz. ND mode: If inverter rated current 120%/1 min is exceeded inverter stops , factory default carrier frequency is 2KHz. |
| 19 | Protection functions | Motor overload (OL1) protection | Electrical overload protection curve I²T |
| 20 | Protection functions | Over voltage(OV) protection | If the main circuit DC voltage rises over 410V (200V class) / 820V (400V class), and over 1050V (575V class) / 1230V (690V class),the motor stops running. |
| 21 | Protection functions | Under voltage (UV) | If the main circuit DC voltage falls below 190V (200V class) / 380V (400V class),and 546V (575/690V class), the motor stops running. |
| 22 | Protection functions | Automatic restart after instantaneous power fault | Power fault exceeds 15ms. Automatic restart function available after instantaneous power fault in 2sec. |
| 23 | Protection functions | Overheat protection(OH) | Uses temperature sensor for protection. |
| 24 | Protection functions | Ground Fault protection(GF) | Use current sensor for protection. |
| 25 | Protection functions | DC bus charge indicator | When main circuit DC voltage ≧50V, the CHARGE LED turns on. |
| 26 | Protection functions | Input phase loss protection (IPL) | If the IPL is detected the motor stops automatically. |
| 27 | Protection functions | Output phase loss protection (OPL) | If the OPL is detected the motor stops automatically. |
| 28 | Protection functions | Short-circuit current rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes (rms) when protected by fuses given in the fuse table |
Manual — Environment and compliance specifications — page 73
Manual reference: physical PDF page 73. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source merged category cells deliberately repeat. Certifications/standards are historical claims, not current certification evidence. Ambient/deratingconditions retained.
Environment and compliance specifications — PDF page 73
| Source row | Source grouping | Parameter/group | Parameter/subgroup | Source specification |
|---|---|---|---|---|
| 1 | Environment Specification | Location | Location | Indoor (protected from corrosive gases and dust). |
| 2 | Environment Specification | Ambient temperature | Ambient temperature | -10~+40°C (14°F~104°F) (IP20/IP21), -10~+50°C (14°F~122°F) (IP00 or top anti- dust cover removed); with de-rating, its maximum operation temperature is 60°C (140°F) (Enhanced type frame 5 is 50°C without de-rating |
| 3 | Environment Specification | Storage temperature | Storage temperature | -20~+70°C (-4°F~+158°F) |
| 4 | Environment Specification | Humidity | Humidity | 95%RH or less ( no condensation ) |
| 5 | Environment Specification | Altitude | Altitude | 1000m (3281ft) or below without de-rating ; 1000~3000m (9843ft) with de-rating |
| 6 | Environment Specification | Vibration | Vibration | 1.0G, in compliance with IEC 60068-2-6; |
| 7 | Environment Specification | Pollution degree | Pollution degree | Meet IEC 60721-3-3 Class 3C3 |
| 8 | Communication function | Communication function | Communication function | RS-485 standard (MODBUS RTU / ASCII protocol) (RJ45 & S(+), S(-) terminal) |
| 9 | PLC function | PLC function | PLC function | Built-in |
| 10 | EMI protection | EMI protection | EMI protection | The built-in noise filter complies with EN61800-3 available for inverters 400V 60HP or below. |
| 11 | EMS protection | EMS protection | EMS protection | EN61800-3 |
| 12 | Certification | Certification | CE | EN61800-3 (CE & RE) EN61800-5-1 (LVD) |
| 13 | Certification | Certification | UKCA | BS EN61800-3 (CE & RE) BS EN61800-5-1 (LVD) |
| 14 | Certification | Certification | UL | UL508C |
Manual — 200V carrier-frequency derating — page 74
Manual reference: physical PDF page 74. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.19 Inverter Derating Based on Carrier Frequency
200V Models 1 - 20 HP 25 HP
30 – 40 HP 50 - 100 HP
125 – 150 HP
Carrier-frequency derating graph 200V1–20HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,8kHz,16kHz;printed output reference labels:ND,HD,80%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 200V25HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,6kHz,12kHz;printed output reference labels:ND,HD,80%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 200V30–40HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz,12kHz;printed output reference labels:ND,HD,80%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 200V50–100HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz,10kHz;printed output reference labels:ND,HD,80%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 200V125–150HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz;printed output reference labels:ND,HD. Source graph retained; no interpolated curve values or universal rating inferred.
Manual — 400V carrier-frequency derating — page 75
Manual reference: physical PDF page 75. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
400V Models 1 - 30 HP 40 - 50 HP
60 – 100 HP & 150~175HP 125 HP
0 2kHz 4kHz 10kHz
ND
HD
70% of HD
Fc
Iout
215 HP
Carrier-frequency derating graph 400V1–30HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,8kHz,16kHz;printed output reference labels:ND,HD,60%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 400V40–50HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz,12kHz;printed output reference labels:ND,HD,80%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 400V60–100HP &150–175HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz,10kHz;printed output reference labels:ND,HD,70%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 400V125HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,4kHz,10kHz;printed output reference labels:ND,HD,70%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 400V215HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,3kHz,8kHz;printed output reference labels:ND,HD,70%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Manual — 400V and575/690V derating — page 76
Manual reference: physical PDF page 76. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
215H(Note) - 375 HP 425 HP
Note: The spec. please refer to Chapter 3.18, the rated current is 330/370A.
575/690V Models 575V 1 - 10 HP 575/690V 15 - 30 HP
575/690V 40 - 60 HP 575/690V 75HP
8kHz
83%
70%
4kHz
Carrier-frequency derating graph 400V215H(Note)–375HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,4kHz,5kHz;printed output reference labels:ND,HD,90%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 400V425HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz;printed output reference labels:ND,HD,90%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 575V1–10HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,8kHz,16kHz;printed output reference labels:ND,HD,80%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 575/690V15–30HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz,8kHz;printed output reference labels:ND,HD,83%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 575/690V40–60HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,5kHz,8kHz;printed output reference labels:ND,HD,70%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 575/690V75HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,4kHz,8kHz;printed output reference labels:ND,HD,70%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Manual — 575/690V carrier and temperature derating — page 77
Manual reference: physical PDF page 77. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
575/690V 100 - 150 HP 575/690V 175 - 270 HP
3.20 Inverter Derating Based on Temperature
0 50°C 60°C
ND
HD
Temperature
Iout
80% of ND
80% of HD
6kHz 1.5kHz 2kHz 4kHz
IP20 IP20
IP00
Carrier-frequency derating graph 575/690V100–150HP. Axis Iout;axis Fc;printed x ticks:0,2kHz,3kHz,6kHz;printed output reference labels:ND,HD,70%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Carrier-frequency derating graph 575/690V175–270HP. Axis Iout;axis Fc;printed x ticks:0,1.5kHz,2kHz,4kHz;printed output reference labels:ND,HD,70%ofHD. Source graph retained; no interpolated curve values or universal rating inferred.
Temperature derating graph IP20:axis Iout;Temperature;0,40°C,60°C;ND,HD,60%ofND,60%ofHD. Dashed ND and dotted HD source curves retained; no interpolation.
Temperature derating graph IP00:axis Iout;Temperature;0,50°C,60°C;ND,HD,80%ofND,80%ofHD. Dashed ND and dotted HD source curves retained; no interpolation.
Manual — Capacitor reforming — page 78
Manual reference: physical PDF page 78. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
◆ Capacitor reforming Guide after long storage
For correct performance of this product after long storage before use it is important that Inverter Capacitors are reformed according to the guide below:
*1:Rated voltage: please connects rated voltage according to model label of inverter.
Source≤1year,between1–2years,≥2years boundary wording retained. No inferred elapsed-time boundary or safe-work approval. Read voltage footnote and source safety context.
Capacitor reforming after long storage — PDF page 78
| Source row | Storage time | Procedure to re-apply voltage |
|---|---|---|
| 1 | ≦1year | Apply rated voltage(*1) of inverter in the normal way |
| 2 | Between 1-2 years | Apply rated voltage of inverter to the product for one hour |
| 3 | ≧2 years | Use a variable AC power supply to 1. Connecting 25% of inverter rated voltage for 30 minutes. 2. Connecting 50% of inverter rated voltage for 30 minutes. 3. Connecting 75% of inverter rated voltage for 30 minutes. 4. Connecting 100% of inverter rated voltage for 210 minutes. Once the procedures completed, inverter just can be used normally. |
Manual — Inverter dimensions — page 79
Manual reference: physical PDF page 79. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.21 Inverter Dimensions
(a) 200V: 1 – 7.5HP / 400V: 1 - 7.5HP/ 575V:1-3HP (IP20/NEMA1)
Dimension drawing labels:W,W1,H,H1,D,t,d. Drawing belongs to 200V1–7.5HP/400V1–7.5HP/575V1–3HP IP20/NEMA1. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. 200V1–7.5HP/400V1–7.5HP/575V1–3HP IP20/NEMA1
Inverter dimensions: 200V1–7.5HP/400V1–7.5HP/575V1–3HP IP20/NEMA1 — PDF page 79
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-2001-S□ | 130 (5.12) | 215 (8.46) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 5 (0.20) | M5 | 2.2 (4.9) |
| 2 | A510-2002-S□ | 130 (5.12) | 215 (8.46) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 5 (0.20) | M5 | 2.2 (4.9) |
| 3 | A510-2003-S□ | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
| 4 | A510-2005-S□3 | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
| 5 | A510-2008-S□3 | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
| 6 | A510-4001-S□3 | 130 (5.12) | 215 (8.46) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 5 (0.20) | M5 | 2.2 (4.9) |
| 7 | A510-4002-S□3 | 130 (5.12) | 215 (8.46) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 5 (0.20) | M5 | 2.2 (4.9) |
| 8 | A510-4003-S□3 | 130 (5.12) | 215 (8.46) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 5 (0.20) | M5 | 2.2 (4.9) |
| 9 | A510-4005-S□3 | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
| 10 | A510-4008-S□3 | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
| 11 | A510-5001-S□3 | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
| 12 | A510-5002-S□3 | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
| 13 | A510-5003-S□3 | 140 (5.51) | 279.5 (11.00) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 1.2 (0.05) | M6 | 3.8 (8.4) |
Manual — Inverter dimensions — page 80
Manual reference: physical PDF page 80. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(b) 200V: 10 - 25HP / 400V: 10 - 30HP / 575V: 5~10HP / 690V: 15~40HP (IP20/NEMA1)
Dimension drawing labels:W,W1,H,H1,D,t,d. Drawing belongs to 200V10–25HP/400V10–30HP/575V5–10HP/690V15–40HP IP20/NEMA1. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. 200V10–25HP/400V10–30HP/575V5–10HP/690V15–40HP IP20/NEMA1
Inverter dimensions: 200V10–25HP/400V10–30HP/575V5–10HP/690V15–40HP IP20/NEMA1 — PDF page 80
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-2010-S□3 | 210 (8.27) | 300 (11.81) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 1.6 (0.06) | M6 | 6.2 (13.67) |
| 2 | A510-2015-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 3 | A510-2020-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 4 | A510-2025-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 5 | A510-4010-S□3 | 210 (8.27) | 300 (11.81) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 1.6 (0.06) | M6 | 6.2 (13.67) |
| 6 | A510-4015-S□3 | 210 (8.27) | 300 (11.81) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 1.6 (0.06) | M6 | 6.2 (13.67) |
| 7 | A510-4020-S□3 | 210 (8.27) | 300 (11.81) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 1.6 (0.06) | M6 | 6.2 (13.67) |
| 8 | A510-4025-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 9 | A510-4030-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 10 | A510-5005-S□3 | 210 (8.27) | 300 (11.81) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 1.6 (0.06) | M6 | 6.2 (13.67) |
| 11 | A510-5008-S□3 | 210 (8.27) | 300 (11.81) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 1.6 (0.06) | M6 | 6.2 (13.67) |
| 12 | A510-5010-S□3 | 210 (8.27) | 300 (11.81) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 1.6 (0.06) | M6 | 6.2 (13.67) |
| 13 | A510-6015-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
Manual — Inverter dimensions — page 81
Manual reference: physical PDF page 81. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. 690V continuation of page80 IP20/NEMA1
Inverter dimensions: 690V continuation of page80 IP20/NEMA1 — PDF page 81
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-6020-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 2 | A510-6025-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 3 | A510-6030-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
| 4 | A510-6040-S□3 | 265 (10.43) | 360 (14.17) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 1.6 (0.06) | M8 | 10 (22.05) |
Manual — Inverter dimensions — page 82
Manual reference: physical PDF page 82. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(c) 200V: 30 - 40HP / 400V: 40 - 75HP / 690V 50~75HP (IP20/NEMA1)
Note: Standard type is 252mm (9.92 inch), Enhanced type is 272mm (10.70 inch)
Dimension drawing labels:W,W1,H,H1,D,t,d. Drawing belongs to 200V30–40HP/400V40–75HP/690V50–75HP IP20/NEMA1; D Note:Standard252mm(9.92in),Enhanced272mm(10.70in). Grouped4040SE3-B/SG3-B row retained.. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. 200V30–40HP/400V40–75HP/690V50–75HP IP20/NEMA1; D Note:Standard252mm(9.92in),Enhanced272mm(10.70in). Grouped4040SE3-B/SG3-B row retained.
Inverter dimensions: 200V30–40HP/400V40–75HP/690V50–75HP IP20/NEMA1; D Note:Standard252mm(9.92in),Enhanced272mm(10.70in). Grouped4040SE3-B/SG3-B row retained. — PDF page 82
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-2030-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 2 | A510-2040-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 3 | A510-4040-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 4 | A510-4050-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 5 | A510-4060-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 6 | A510-4075-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 7 | A510-6050-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 8 | A510-6060-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 9 | A510-6075-S□3 | 288 (11.34) | 526 (20.71) | Note | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 27 (59.52) |
| 10 | A510-4040-SE3-B A510-4040-SG3-B | 286.5 (11.28) | 526 (20.71) | 252 (9.92) | 160 (6.30) | 505 (19.88) | 3.3 (0.13) | M8 | 28 (52.91) |
Manual — Inverter dimensions — page 83
Manual reference: physical PDF page 83. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
200V: 50 - 100HP / 400V: 100 - 215HP / 690V: 100~270HP (IP00)
Dimension drawing labels:W,W1,H,H1,D,t,d. Drawing belongs to 200V50–100HP/400V100–215HP/690V100–270HP IP00. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. 200V50–100HP/400V100–215HP/690V100–270HP IP00
Inverter dimensions: 200V50–100HP/400V100–215HP/690V100–270HP IP00 — PDF page 83
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-2050-S□3 | 344 (13.54) | 580 (22.83) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 40 (88.18) |
| 2 | A510-2060-S□3 | 344 (13.54) | 580 (22.83) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 40 (88.18) |
| 3 | A510-2075-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 4 | A510-2100-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 5 | A510-4100-S□3 | 344 (13.54) | 580 (22.83) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 40 (88.18) |
| 6 | A510-4125-S□3 | 344 (13.54) | 580 (22.83) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 40 (88.18) |
| 7 | A510-4150-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 8 | A510-4175-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 9 | A510-4215-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 10 | A510-6100-S□3 | 344 (13.54) | 580 (22.83) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 40 (88.18) |
Manual — Inverter dimensions — page 84
Manual reference: physical PDF page 84. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(d) 200V: 50 - 100HP / 400V: 100 - 215HP/ 690V: 100~270HP (IP20/ NEMA1)
Dimension drawing labels:W,W1,H,H1,D,t,d. Drawing belongs to NEW IP20/NEMA1 subsection(d), whose values continue page85. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. IP00 continuation of page83; this table is ABOVE the new IP20/NEMA1 heading, so does not belong to it
Inverter dimensions: IP00 continuation of page83; this table is ABOVE the new IP20/NEMA1 heading, so does not belong to it — PDF page 84
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-6125-S□3 | 344 (13.54) | 580 (22.83) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 40 (88.18) |
| 2 | A510-6150-S□3 | 344 (13.54) | 580 (22.83) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 40 (88.18) |
| 3 | A510-6175-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 4 | A510-6215-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 5 | A510-6250-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
| 6 | A510-6270-S□3 | 459 (18.07) | 790 (31.10) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 74 (163.14) |
Manual — Inverter dimensions — page 85
Manual reference: physical PDF page 85. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. IP20/NEMA1 continuation of page84 lower heading;200V50–100HP/400V100–215HP/690V100–270HP
Inverter dimensions: IP20/NEMA1 continuation of page84 lower heading;200V50–100HP/400V100–215HP/690V100–270HP — PDF page 85
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-2050-S□3 | 348.5 (13.72) | 740 (29.13) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 44 (97.00) |
| 2 | A510-2060-S□3 | 348.5 (13.72) | 740 (29.13) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 44 (97.00) |
| 3 | A510-2075-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 4 | A510-2100-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 5 | A510-4100-S□3 | 348.5 (13.72) | 740 (29.13) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 44 (97.00) |
| 6 | A510-4125-S□3 | 348.5 (13.72) | 740 (29.13) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 44 (97.00) |
| 7 | A510-4150-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 8 | A510-4175-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 9 | A510-4215-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 10 | A510-6100-S□3 | 348.5 (13.72) | 740 (29.13) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 44 (97.00) |
| 11 | A510-6125-S□3 | 348.5 (13.72) | 740 (29.13) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 44 (97.00) |
| 12 | A510-6150-S□3 | 348.5 (13.72) | 740 (29.13) | 300 (11.81) | 250 (9.84) | 560 (22.05) | 1.6 (0.06) | M8 | 44 (97.00) |
| 13 | A510-6175-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 14 | A510-6215-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 15 | A510-6250-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
| 16 | A510-6270-S□3 | 463.5 (18.25) | 1105 (43.50) | 324.5 (12.78) | 320 (12.60) | 760 (29.92) | 1.6 (0.06) | M10 | 81 (178.57) |
Manual — Inverter dimensions — page 86
Manual reference: physical PDF page 86. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(e) 200V: 125 - 150HP / 400V: 215H - 425HP (IP00)
Dimension drawing labels:W,W1,H,H1,D,t,d,W2. Drawing belongs to 200V125–150HP/400V215H–425HP IP00;215H heading has no4215row. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. 200V125–150HP/400V215H–425HP IP00;215H heading has no4215row
Inverter dimensions: 200V125–150HP/400V215H–425HP IP00;215H heading has no4215row — PDF page 86
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | W2 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-2125-S□3 | 690 (27.17) | 1000 (39.37) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 184 (405.65) |
| 2 | A510-2150-S□3 | 690 (27.17) | 1000 (39.37) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 184 (405.65) |
| 3 | A510-4270-S□3 | 690 (27.17) | 1000 (39.37) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 184 (405.65) |
| 4 | A510-4300-S□3 | 690 (27.17) | 1000 (39.37) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 184 (405.65) |
| 5 | A510-4375-S□3 | 690 (27.17) | 1000 (39.37) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 184 (405.65) |
| 6 | A510-4425-S□3 | 690 (27.17) | 1000 (39.37) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 184 (405.65) |
Manual — Inverter dimensions — page 87
Manual reference: physical PDF page 87. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(f) 200V: 125 - 150HP / 400V: 215H - 425HP (IP20/NEMA1)
Dimension drawing labels:W,W1,H,H1,D,t,d,W2. Drawing belongs to 200V125–150HP/400V215H–425HP IP20/NEMA1;215H heading has no4215row. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. 200V125–150HP/400V215H–425HP IP20/NEMA1;215H heading has no4215row
Inverter dimensions: 200V125–150HP/400V215H–425HP IP20/NEMA1;215H heading has no4215row — PDF page 87
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | W2 mm(inch) | H1 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-2125-S□3 | 692 (27.24) | 1313 (51.69) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 194 (427.70) |
| 2 | A510-2150-S□3 | 692 (27.24) | 1313 (51.69) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 194 (427.70) |
| 3 | A510-4270-S□3 | 692 (27.24) | 1313 (51.69) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 194 (427.70) |
| 4 | A510-4300-S□3 | 692 (27.24) | 1313 (51.69) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 194 (427.70) |
| 5 | A510-4375-S□3 | 692 (27.24) | 1313 (51.69) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 194 (427.70) |
| 6 | A510-4425-S□3 | 692 (27.24) | 1313 (51.69) | 410 (16.14) | 530 (20.87) | 265 (10.43) | 960 (37.80) | 1.6 (0.06) | M12 | 194 (427.70) |
Manual — Inverter dimensions — page 88
Manual reference: physical PDF page 88. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.22 Dimensions for Models with Built-in Filter
(a) 400V: 1 - 7.5HP
Dimension drawing labels:W,W1,H,H1,D,t,d,H2. Drawing belongs to Built-in filter400V1–7.5HP. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. Built-in filter400V1–7.5HP
Inverter dimensions: Built-in filter400V1–7.5HP — PDF page 88
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | H2 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-4001-S□3F | 130 (5.12) | 306 (12.05) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 215 (8.46) | 5 (0.20) | M5 | 3.5 (7.71) |
| 2 | A510-4002-S□3F | 130 (5.12) | 306 (12.05) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 215 (8.46) | 5 (0.20) | M5 | 3.5 (7.71) |
| 3 | A510-4003-S□3F | 130 (5.12) | 306 (12.05) | 150 (5.91) | 118 (4.65) | 203 (7.99) | 215 (8.46) | 5 (0.20) | M5 | 3.5 (7.71) |
| 4 | A510-4005-S□3F | 140 (5.51) | 385.5 (15.18) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 279 (10.98) | 1.2 (0.05) | M6 | 5.5 (12.13) |
| 5 | A510-4008-S□3F | 140 (5.51) | 385.5 (15.18) | 181 (7.13) | 122 (4.80) | 267 (10.51) | 279 (10.98) | 1.2 (0.05) | M6 | 5.5 (12.13) |
Manual — Inverter dimensions — page 89
Manual reference: physical PDF page 89. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(b) 400V: 10 - 30HP
Dimension drawing labels:W,W1,H,H1,D,t,d,H2. Drawing belongs to Built-in filter400V10–30HP. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. Built-in filter400V10–30HP
Inverter dimensions: Built-in filter400V10–30HP — PDF page 89
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | H2 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-4010-S□3F | 210 (8.27) | 416.5 (16.40) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 300 (11.81) | 1.6 (0.06) | M6 | 8.0 (17.64) |
| 2 | A510-4015-S□3F | 210 (8.27) | 416.5 (16.40) | 215 (8.46) | 192 (7.56) | 286 (11.26) | 300 (11.81) | 1.6 (0.06) | M6 | 8.0 (17.64) |
| 3 | A510-4020-S□3F | 265 (10.43) | 500 (19.69) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 360 (14.17) | 1.6 (0.06) | M8 | 12.5 (27.56) |
| 4 | A510-4025-S□3F | 265 (10.43) | 500 (19.69) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 360 (14.17) | 1.6 (0.06) | M8 | 12.5 (27.56) |
| 5 | A510-4030-S□3F | 265 (10.43) | 500 (19.69) | 225 (8.86) | 245 (9.65) | 340 (13.39) | 360 (14.17) | 1.6 (0.06) | M8 | 12.5 (27.56) |
Manual — Inverter dimensions — page 90
Manual reference: physical PDF page 90. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(c) 400V: 40 - 60HP
Note: Standard type is 252mm (9.92 inch), Enhanced type is 272mm (10.70 inch)
Dimension drawing labels:W,W1,H,H1,D,t,d,H2. Drawing belongs to Built-in filter400V40–60HP;D Note:Standard252mm(9.92in),Enhanced272mm(10.70in). Grouped4040SE3F-B/SG3F-B retained.. Exact numerical values are in matching table; no dimensions inferred from scaled geometry.
Source model prefix A510- and placeholder□ retained; mm(inch) and kg(lbs) pairs literal, no conversion correction. Built-in filter400V40–60HP;D Note:Standard252mm(9.92in),Enhanced272mm(10.70in). Grouped4040SE3F-B/SG3F-B retained.
Inverter dimensions: Built-in filter400V40–60HP;D Note:Standard252mm(9.92in),Enhanced272mm(10.70in). Grouped4040SE3F-B/SG3F-B retained. — PDF page 90
| Source row | Inverter Model | W mm(inch) | H mm(inch) | D mm(inch) | W1 mm(inch) | H1 mm(inch) | H2 mm(inch) | t mm(inch) | d | Net Weight kg(lbs) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | A510-4040-S□3F | 288 (11.34) | 680 (26.77) | Note | 160 (6.30) | 505 (19.88) | 525 (20.67) | 3.3 (0.13) | M8 | 32 (70.55) |
| 2 | A510-4050-S□3F | 288 (11.34) | 680 (26.77) | Note | 160 (6.30) | 505 (19.88) | 525 (20.67) | 3.3 (0.13) | M8 | 32 (70.55) |
| 3 | A510-4060-S□3F | 288 (11.34) | 680 (26.77) | Note | 160 (6.30) | 505 (19.88) | 525 (20.67) | 3.3 (0.13) | M8 | 32 (70.55) |
| 4 | A510-4040-SE3F-B A510-4040-SG3F-B | 286.5 (11.28) | 680 (26.77) | 252 (9.92) | 160 (6.30) | 505 (19.88) | 525 (20.67 | 3.3 (0.13) | M8 | 33 (72.75) |
Manual — LED keypad display and indicators — page 91
Manual reference: physical PDF page 91. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 4 Keypad and Programming Functions
4.1 LED Keypad
4.1.1 Keypad Display and Keys
(Standard Type) (Enhanced Type) Note: For Enhanced Type sold in the mainland, the last code of the inverter product is C, and the panel is the same as the Standard Type.
Upper LED keypad labels:Forward Direction Status Indicator;Reverse Direction Status Indicator;Fault Status Indicator;External Sequence Indicator;External Reference Indicator;5 Digit,7 Segment LED Display;8 button Membrane Keypad;Run Status Indicator;Stop Status Indicator. Key legends FWD/REV,▲,DSP/FUN,◀/RESET,▼,READ/ENTER,RUN,STOP. Display005.00. Source Standard/Enhanced caption alignment is ambiguous; do not infer the missing right-side image.
Lower LED keypad labels:Forward Direction Status Indicator;Reverse Direction Status Indicator;Fault Status Indicator;Local/Remote Indicator;External Reference Indicator;External Sequence Indicator;5 Digit,7 Segment LED Display;8 button Membrane Keypad;Run Status Indicator;Stop Status Indicator. Key legends LOC/REM,▲,DSP/FUN,◀/RESET,▼,READ/ENTER,RUN,STOP. Display005.00;REMOTE label. Both images appear in left column while captionsStandard Type/Enhanced Type are side-by-side.
Source display and LED-indicator groups. Standard and Enhanced keypad context retained; no inferred availability.
LED keypad — PDF page 91
| Source row | Display/LED indicator | Description |
|---|---|---|
| 1 | 5 Digit LED Display | Monitor inverter signals, view / edit parameters, fault / alarm display. |
| 2 | FAULT | LED ON when a fault or alarm is active. |
| 3 | FWD | LED ON when inverter is running in forward direction, flashing when stopping. |
| 4 | REV | On when inverter is running in reverse direction, flashing when stopping. |
Manual — LED keypad keys — page 92
Manual reference: physical PDF page 92. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Auto-Repeat Keys Holding the ▲UP or ▼DOWN key for a longer period of time will initiate the auto-repeat function resulting in the value of the selected digit to automatically increase or decrease.
SEQ/REF continuation of page91.
Eight physical keys; alternative FWD/REV Standard versus LOC/REM Enhanced retained as separate source rows. LOC/REM enable reference differs LED11-79 vsLCD23-41; no preferred parameter inferred.
LED keypad indicator continuation — PDF page 92
| Source row | LED indicator | Description |
|---|---|---|
| 1 | SEQ | LED ON when RUN command is from the external control terminals or from serial communication |
| 2 | REF | LED ON when Frequency Reference command is from the external control terminals or from serial communication |
Key functions: LED — PDF page 92
| Source row | Key and type | Description |
|---|---|---|
| 1 | RUN | RUN Inverter in Local Mode |
| 2 | STOP | STOP Inverter |
| 3 | ▲ | Parameter navigation Up, Increase parameter or reference value |
| 4 | ▼ | Parameter navigation down, decrease parameter or reference value |
| 5 | FWD/REV (Standard Type) | Used to switch between Forward and Reverse direction |
| 6 | LOC/REM (Enhanced Type) | Used to switch between Local Mode and Remote Mode REMOTE Mode: Set by parameters, controlled by control circuit terminals, communication or other ways. LOCAL Mode: Controlled by operator. It displays REMOTE Mode at power-up. Users can switch between LOCAL and REMOTE Mode if they press LOC/ REM keys when the inverter stops. Parameter of 11-79 can determine if LOC/REM keys are enabled or not. |
| 7 | DSP/FUN | Used to scroll to next screen Frequency screen Function selectionMonitor parameter |
| 8 | ◄ / RESET | Selects active seven segment digit for editing with the ▲▼ keys Used to reset fault condition. |
| 9 | READ / ENTER | Used to read and save the value of the active parameter |
Manual — Seven-segment display description — page 93
Manual reference: physical PDF page 93. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.1.2 Seven Segment Display Description
Display output frequency Frequency Reference Set Frequency Reference
At power-up, the display will show the frequency reference setting and all LEDs are flashing. Press the ▲ (UP) or ▼ (DOWN) key to enter the frequency reference edit mode, use the ◄/RESET key to select which digit to edit (flashing). Use the ▲ (UP) or ▼ (DOWN) key to modify the value and press the READ / ENTER key to save the frequency reference and switch back to the frequency reference display mode. During run operation, the display will show the output frequency. Note: When in edit mode and the READ / ENTER is not pressed within 5 sec, the inverter will switch back to the frequency reference display mode.
Seven-segment source mapping row1: 0 → its illustrated seven-segment glyph; A → its illustrated seven-segment glyph; L → its illustrated seven-segment glyph; Y → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row2: 1 → its illustrated seven-segment glyph; B → its illustrated seven-segment glyph; n → its illustrated seven-segment glyph; - → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row3: 2 → its illustrated seven-segment glyph; C → its illustrated seven-segment glyph; o → its illustrated seven-segment glyph; ° → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row4: 3 → its illustrated seven-segment glyph; D → its illustrated seven-segment glyph; P → its illustrated seven-segment glyph; – → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row5: 4 → its illustrated seven-segment glyph; E → its illustrated seven-segment glyph; q → its illustrated seven-segment glyph; . → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row6: 5 → its illustrated seven-segment glyph; F → its illustrated seven-segment glyph; r → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row7: 6 → its illustrated seven-segment glyph; G → its illustrated seven-segment glyph; S → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row8: 7 → its illustrated seven-segment glyph; H → its illustrated seven-segment glyph; t → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row9: 8 → its illustrated seven-segment glyph; I → its illustrated seven-segment glyph; u → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Seven-segment source mapping row10: 9 → its illustrated seven-segment glyph; J → its illustrated seven-segment glyph; v → its illustrated seven-segment glyph. Glyph shape retained in bounded source; B,D,n,o,q,r,t,u,v use lower-case-style segment forms; no substitute numeric code inferred.
Display examples all005.00:output frequency LEDs on;frequency reference all LEDs flashing;set reference one active digit flashing. Vector illustrations retained.
Graphical seven-segment cells have no native text; paired visual mapping supplied in figure records; blank native text is not missing character.
Raster/vector numeral examples recorded separately; states not numeric ratings.
Seven segment character mapping — PDF page 93
| Source row | Actual1 | LED glyph1 | Actual2 | LED glyph2 | Actual3 | LED glyph3 | Actual4 | LED glyph4 |
|---|---|---|---|---|---|---|---|---|
| 1 | 0 | ⟦blank source cell⟧ | A | ⟦blank source cell⟧ | L | ⟦blank source cell⟧ | Y | ⟦blank source cell⟧ |
| 2 | 1 | ⟦blank source cell⟧ | B | ⟦blank source cell⟧ | n | ⟦blank source cell⟧ | - | ⟦blank source cell⟧ |
| 3 | 2 | ⟦blank source cell⟧ | C | ⟦blank source cell⟧ | o | ⟦blank source cell⟧ | ° | ⟦blank source cell⟧ |
| 4 | 3 | ⟦blank source cell⟧ | D | ⟦blank source cell⟧ | P | ⟦blank source cell⟧ | _ | ⟦blank source cell⟧ |
| 5 | 4 | ⟦blank source cell⟧ | E | ⟦blank source cell⟧ | q | ⟦blank source cell⟧ | . | ⟦blank source cell⟧ |
| 6 | 5 | ⟦blank source cell⟧ | F | ⟦blank source cell⟧ | r | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 7 | 6 | ⟦blank source cell⟧ | G | ⟦blank source cell⟧ | S | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 8 | 7 | ⟦blank source cell⟧ | H | ⟦blank source cell⟧ | t | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 9 | 8 | ⟦blank source cell⟧ | I | ⟦blank source cell⟧ | u | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 10 | 9 | ⟦blank source cell⟧ | J | ⟦blank source cell⟧ | V | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Display state examples — PDF page 93
| Source row | Display output frequency:LED lights on | Frequency Reference:LED flashes | Set Frequency Reference:Flashing digit |
|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — LED display examples — page 94
Manual reference: physical PDF page 94. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
LED Display Examples
LED seven-segment illustrated value:000.00. Match description row1 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:00-01. Match description row2 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:00000. Match description row3 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:220u. Match description row4 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:0011A. Match description row5 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:0310U. Match description row6 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:024°C. Match description row7 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:five illuminated zero glyphs (00000), decimal-point positions are gray/unlit in the drawing. Match description row8 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:Err1. Match description row9 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
LED seven-segment illustrated value:000P. Match description row10 in table; font renders U/u-like voltage suffix; source illustration authoritative, not rating.
Vector display glyphs transcribed separately with matching physical row bounds; not operating ratings.
LED display examples — PDF page 94
| Source row | Seven segment example | Description |
|---|---|---|
| 1 | ⟦blank source cell⟧ | 1. Displays the frequency reference at power-up. 2. Displays the actual output frequency during run operation. |
| 2 | ⟦blank source cell⟧ | Displays parameter code. |
| 3 | ⟦blank source cell⟧ | Displays the setting value of parameter. |
| 4 | ⟦blank source cell⟧ | Displays input voltage. |
| 5 | ⟦blank source cell⟧ | Displays inverter current. |
| 6 | ⟦blank source cell⟧ | Displays DC Bus Voltage. |
| 7 | ⟦blank source cell⟧ | Displays temperature. |
| 8 | ⟦blank source cell⟧ | Displays PID feedback value; The displayed digit is set by 12-01. |
| 9 | ⟦blank source cell⟧ | Error display; refer to chapter 5 Troubleshooting and Maintenance. |
| 10 | ⟦blank source cell⟧ | Displays AI1/ AI2 input (0~100%) |
Manual — LED indicator states — page 95
Manual reference: physical PDF page 95. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.1.3 LED Indicator Description
Fault LED
Forward LED
Reverse LED
RUN LED
Gray unlit indicator (Off);paired with source table1 row1.
Red solid indicator (Illuminated);paired with source table1 row2.
Gray unlit indicator (Off);paired with source table2 row1.
Red solid indicator (Illuminated);paired with source table2 row2.
Red indicator with rays (Flashing);paired with source table2 row3.
Gray unlit indicator (Off);paired with source table3 row1.
Red solid indicator (Illuminated);paired with source table3 row2.
Red indicator with rays (Flashing);paired with source table3 row3.
Gray unlit indicator (Off);paired with source table4 row1.
Red solid indicator (Illuminated);paired with source table4 row2.
Red indicator with rays (Flashing);paired with source table4 row3.
Graphical symbols:gray/off,red/illuminated,red with rays/flashing. Raw native symbol cells blank; figure evidence preserves them.
FAULT LED — PDF page 95
| Source row | State | Description | LED symbol |
|---|---|---|---|
| 1 | Off | No Fault Active | ⟦blank source cell⟧ |
| 2 | Illuminated | Fault Active | ⟦blank source cell⟧ |
FWD LED — PDF page 95
| Source row | State | Description | LED symbol |
|---|---|---|---|
| 1 | Off | Inverter in reverse direction | ⟦blank source cell⟧ |
| 2 | Illuminated | Inverter is running in forward direction | ⟦blank source cell⟧ |
| 3 | Flashing | Forward direction active, no run command | ⟦blank source cell⟧ |
REV LED — PDF page 95
| Source row | State | Description | LED symbol |
|---|---|---|---|
| 1 | Off | Inverter in forward direction | ⟦blank source cell⟧ |
| 2 | Illuminated | Inverter is running in reverse direction | ⟦blank source cell⟧ |
| 3 | Flashing | Reverse direction active, no run command | ⟦blank source cell⟧ |
RUN LED — PDF page 95
| Source row | State | Description | LED symbol |
|---|---|---|---|
| 1 | Off | Inverter stopped | ⟦blank source cell⟧ |
| 2 | Illuminated | Inverter running | ⟦blank source cell⟧ |
| 3 | Flashing | Inverter stopped or stopping | ⟦blank source cell⟧ |
Manual — SEQ/REF and run-stop status — page 96
Manual reference: physical PDF page 96. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
SEQ LED
REF LED
Run / Stop Status Indicators
Gray unlit indicator (Off);paired with source table1 row1.
Red solid indicator (Illuminated);paired with source table1 row2.
Gray unlit indicator (Off);paired with source table2 row1.
Red solid indicator (Illuminated);paired with source table2 row2.
Run/Stop Status Indicators chart:Output Frequency starts0,rises,holds,falls to0;command STOP→RUN→STOP;Frequency Setting step. Five illustrated phases left-to-right:RUN off/STOP on;RUN on/STOP flashing;RUN on/STOP off;RUN flashing/STOP on;RUN off/STOP on. LegendON red,Flashing red with rays,OFF pink. No time scale or durations inferred.
Graphical symbols:gray/off,red/illuminated,red with rays/flashing. Raw native symbol cells blank; figure evidence preserves them.
SEQ LED — PDF page 96
| Source row | State | Description | LED symbol |
|---|---|---|---|
| 1 | Off | Sequence controlled from keypad | ⟦blank source cell⟧ |
| 2 | Illuminated | Sequence set from external source | ⟦blank source cell⟧ |
REF LED — PDF page 96
| Source row | State | Description | LED symbol |
|---|---|---|---|
| 1 | Off | Frequency reference set from keypad | ⟦blank source cell⟧ |
| 2 | Illuminated | Frequency reference set from external source | ⟦blank source cell⟧ |
Manual — Power-up monitor — page 97
Manual reference: physical PDF page 97. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.1.4 Power-up Monitor
Power-up
Changing Monitor at Power-up
Example: 12- 00=【10000】
Power-up example:220u(Display at Power-up)→after3sec→005.00(Frequency Reference)→DSP/FUN Switch Mode→00-01(Parameter Selection);DSP/FUN returns to frequency reference. All flashing marks as drawn.
Example12-00=[10000]:220u display voltage class at power-up→after3sec→0000A Output Current;DSP/FUN cycles Output Current→005.00 Frequency Reference→00-01 Parameter Selection→Output Current. These are display examples, not measured values.
Five bits, each0–7. Full bit/range context retained; graphical navigation examples separately transcribed.
Changing monitor at power-up — PDF page 97
| Source row | 12-00 | Display Selection |
|---|---|---|
| 1 | Range | Highest bit -> 0 0 0 0 0 <- Lowest bit The setting range for each bit is 0 ~ 7 from the highest bit to the lowest bit. 0: No display 4: Temperature 1: Output current 5: PID feedback 2: Output voltage 6: AI1 value 3: DC voltage 7: AI2 value |
Manual — Monitor selection and modifying parameters — page 98
Manual reference: physical PDF page 98. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: 12- 00=【12345】
4.1.5 Modifying Parameters/ Set Frequency Reference
Example: Modifying Parameters
Example12-00=[12345]:220u voltage class power-up→after3sec005.00 frequency reference. DSP/FUN cycle Frequency Reference→00-01 Parameter Selection→0000A Output Current<1>→0000u Output Voltage<2>→0310U DC Voltage<3>→024°C Heatsink Temperature<4>→five illuminated zero glyphs (00000) PID Feedback<5>→Frequency Reference. Source drawn sequence only.
Modifying parameters example:005.00 Frequency Reference→DSP/FUN→00-01;◀/RESET twice moves active digit;▲ changes to00-12;READ/ENTER displays00001;▲ changes00002;READ/ENTER gives-End- flashing3sec then00002;DSP/FUN returns00-12. Example values and cursor marks are source illustrations, not recommended settings.
Manual — Set frequency reference — page 99
Manual reference: physical PDF page 99. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: Set Frequency Reference Inverter stopped: Inverter is running:
Flashing for 3 seconds
Press RUN 1x
Display Voltage Class Display Voltage Class
Output Frequency
Output frequency
Set Frequency Reference 0.01 Hz
Set Frequency Reference completed.
Display Frequency Reference
Set Frequency Reference
Set Frequency Reference 0.1 Hz Set Frequency Reference 0.1 Hz
Set Frequency Reference 1Hz Set Frequency Reference 1 Hz
Set Frequency Reference + 1Hz Set Frequency Reference +1 Hz
Press </RESET 1x
Press READ/ENTER 1x
▲
▲ ▲
▲ Press 1x
Press 1x
Press 1x Press 1x
Inverter automatically reverts back to display the output frequency if no modifications are made within 5 sec.
Note: When upper or lower limit is reached during editing of the frequency reference, the edit value will automatically rollover from the lower limit to the upper limit or from the upper limit to the lower limit.
Set Frequency Reference, inverter stopped:220u voltage class flashes3sec then005.00 reference. ▲once gives005.01;▼once restores005.00. ◀/RESET advances active digit through0.01Hz,0.1Hz,1Hz positions. ▲once at1Hz gives006.00;READ/ENTER once completes006.00. Illustrative sequence only; lower/upper rollover note retained.
Set Frequency Reference, inverter running:220u flashes3sec then005.00 reference;RUN once gives005.00 Output Frequency. ◀/RESET selects reference digits0.01Hz→0.1Hz→1Hz;▲once gives006.00;READ/ENTER once returns006.00 Output Frequency. Diagram says automatically reverts to output-frequency display if no modifications within5sec. Illustrative sequence, not inferred operating instruction.
Manual — 4.1.6 Operation Control — page 100
Manual reference: physical PDF page 100. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Qualitative diagram, exact waveform edges, durations and command alignment remain original-only. No numeric frequency/timing inferred.
Eight displayed left-to-right intervals and four indicators. Literal glyph transcription without inferring on/off meaning.
Specific source-page labels; not recommended settings.
Eight source intervals; original waveform geometry retained.
Adjacent source context — repeated to preserve continuation:
Diagram labels — PDF page 100
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Status regions | Stopped; Running; Stopping; Stopped |
| 2 | Trace | Output Frequency |
| 3 | Command arrows left-to-right | Power on; REV command; FWD command; RUN command; REV command; FWD command; Stop command |
| 4 | Indicator rows | FWD Indicator; REV Indicator; RUN Indicator; STOP Indicator |
Visible indicator glyphs by displayed interval — PDF page 100
| Source row | Interval left-to-right | FWD glyph | REV glyph | RUN glyph | STOP glyph |
|---|---|---|---|---|---|
| 1 | 1 | Red with rays | Grey | Grey | Red |
| 2 | 2 | Grey | Red with rays | Grey | Red |
| 3 | 3 | Red with rays | Grey | Grey | Red |
| 4 | 4 | Red | Grey | Red | Grey |
| 5 | 5 | Grey | Red | Red | Grey |
| 6 | 6 | Red | Grey | Red | Grey |
| 7 | 7 | Red | Grey | Red with rays | Red |
| 8 | 8 | Red with rays | Grey | Grey | Red |
Manual — LCD keypad display and indicators — page 101
Manual reference: physical PDF page 101. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.2 LCD Keypad
4.2.1 Keypad Display and Keys
(Standard Type) (Enhanced Type)
Standard Type LCD keypad:Forward Direction,Reverse Direction,Fault,External Sequence,External Reference,Run andStop status indicators;LCD Display;8 button Membrane Keypad. KeysFWD/REV,▲,DSP/FUN,◀/RESET,▼,READ/ENTER,RUN,STOP. LCD example Monitor/Fref Ref/12-16=005.00Hz/12-17=000.00Hz/12-18=0000.0A.
Enhanced Type LCD keypad:Forward Direction,Reverse Direction,Fault,Local/Remote,External Sequence,External Reference,Run andStop indicators;LCD Display;8 button Membrane Keypad. KeysLOC/REM,▲,DSP/FUN,◀/RESET,▼,READ/ENTER,RUN,STOP. Display blank in illustration;no value inferred.
Source display and LED-indicator groups. Standard and Enhanced keypad context retained; no inferred availability.
Adjacent source context — repeated to preserve continuation:
LCD keypad — PDF page 101
| Source row | Display/LED indicator | Description |
|---|---|---|
| 1 | LCD Display | Monitor inverter signals, view / edit parameters, fault / alarm display. |
| 2 | FAULT | LED ON when a fault or alarm is active. |
| 3 | FWD | LED ON when inverter is running in forward direction, flashing when stopping. |
| 4 | REV | On when inverter is running in reverse direction, flashing when stopping. |
| 5 | SEQ | LED ON when RUN command is from the external control terminals or from serial communication |
| 6 | REF | LED ON when Frequency Reference command is from the external control terminals or from serial communication |
Manual — LCD keypad keys — page 102
Manual reference: physical PDF page 102. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Auto-Repeat Keys Holding the ▲UP or ▼DOWN key for a longer period of time will initiate the auto-repeat function resulting in the value of the selected digit to automatically increase or decrease.
Eight physical keys; alternative FWD/REV Standard versus LOC/REM Enhanced retained as separate source rows. LOC/REM enable reference differs LED11-79 vsLCD23-41; no preferred parameter inferred.
Key functions: LCD — PDF page 102
| Source row | Key and type | Description |
|---|---|---|
| 1 | RUN | RUN Inverter in Local Mode |
| 2 | STOP | STOP Inverter |
| 3 | ▲ | Parameter navigation Up, Increase parameter or reference value |
| 4 | ▼ | Parameter navigation down, decrease parameter or reference value |
| 5 | FWD/REV (Standard Type) | Used to switch between Forward and Reverse direction |
| 6 | LOC/REM (Enhanced Type) | Used to switch between Local Mode and Remote Mode REMOTE Mode: Set by parameters, controlled by control circuit terminals, communication or other ways. LOCAL Mode: Controlled by operator. It displays REMOTE Mode at power-up. Users can switch between LOCAL and REMOTE Mode if they press LOC/ REM keys when the inverter stops. Parameter of 23-41 can determine if LOC/REM keys are enabled or not. |
| 7 | DSP/FUN | Used to scroll to next screen Frequency screen Function selectionMonitor parameter |
| 8 | ◄ / RESET | Selects active seven segment digit for editing with the ▲▼ keys Used to reset fault condition. |
| 9 | READ / ENTER | Used to read and save the value of the active parameter |
Manual — LCD keypad menu structure — page 103
Manual reference: physical PDF page 103. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.2.2 Keypad Menu Structure
Main Menu The A510S inverter main menu consists of two main groups (modes). The DSP/FUN key is used to switch between the monitor mode and the parameter group mode.
All the available parameter groups are listed in the Parameter Group Mode use the up and down keys to select a group and press Read/Enter key to access its parameters. Fig. 4.2.2.1 Parameter Group Structure Notes: - Always perform an auto-tune on the motor before operating the inverter in vector control (sensorless vector or flux vector). Auto-tuning mode will not be displayed when the inverter is running or when a fault is active. - To scroll through the available modes, parameter groups or parameter list press and hold the up or down key.
Main menu diagram:Power On→Power-up→Monitor Mode;DSP/FUN→Parameter Group Mode;DSP/FUN returns Monitor Mode.
Fig4.2.2.1 Parameter Group Structure:Parameter Group Mode(Select parameter group)→READ/ENTER→Parameter Mode(Select parameter)→READ/ENTER→Parameter Edit Mode(Change parameter setting). DSP/FUN moves back one level. Source-labelled navigation only.
Monitor and Parameter Group Mode; source notes and graphical mode navigation retained.
LCD main menu modes — PDF page 103
| Source row | Mode | Description |
|---|---|---|
| 1 | Monitor Mode | View inverter status, signals and fault data. |
| 2 | Parameter Group Mode | Access to available parameter groups. |
Manual — LCD monitor mode — page 104
Manual reference: physical PDF page 104. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Monitor Mode In monitor mode inverter signals can be monitored such as output frequency, output current and output voltage, etc…) as well as fault information and fault trace. See Fig 4.2.2.2 for keypad navigation.
Fig 4.2.2.2 Monitor Mode Note: - To scroll through the available monitor parameter list, press and hold the ▲ (up) or ▼ (down) key.
Fig4.2.2.2 Monitor Mode:Power ON→Monitor/Freq Ref/12-16=005.00Hz/12-17=000.00Hz/12-18=0000.0A. ▼ moves to Monitor/Flt Freq Ref/12-15=000.00Hz with same12-17/12-18;▼ then Monitor/Flt DC Voltage/12-14=0000.0V with same12-17/12-18. ▲ reverses list. DSP/FUN accesses Group00 Basic Func.,01 V/F Pattern.,02 Motor Parameter;DSP/FUN returns Monitor. No fault or operating values inferred from sample display.
Manual — Programming mode navigation — page 105
Manual reference: physical PDF page 105. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Programming Mode In programming mode inverter parameters can be read or changed. See Fig 4.2.2.3 for keypad navigation.
Power ON
DSP FUN
READ ENTER READ ENTER
READ ENTER
To parameters
Monitor Freq Ref
12-17=000.00Hz 12-18=0000.0A
12-16=005.00Hz
Control Method
Edit 00-00
0 V/F (0~4) <0>
Motor Direction
0 Forward (0~1) <0>
Run Source
0 Digital Op (0~4) <1>
Edit 00-01
Edit 00-02
Group
01 V/F Pattern 02 Motor Parameter
00 Basic Func.
02 Motor Parameter
00 Basic Fun. 01 V/F Pattern
Group 00 Basic Fun. 01 V/F Pattern
PARA 00 -00 Control Method -01 Motor Direction -02 Run Source
Parameter Group Selection Mode Parameter Group Mode
Parameter Edit Mode
Press ▼or ▲ key to edit parameter value, and press READ/ENTER
key to save the change.
Fig 4.2.2.3 Programming Mode Notes: - The parameters values can be changed from the Edit screen with the up, down and < / RESET shift key. - To save a parameter press the READ/ENTER key. - Refer to section 4.4 for parameter details. - Press the ▲ (up) or ▼ (down) key to scroll parameter groups or parameter list.
Fig4.2.2.3 Programming Mode. PowerON→Monitor Freq Ref12-16=005.00Hz,12-17=000.00Hz,12-18=0000.0A;DSP/FUN→Parameter Group Selection Mode(Group00Basic Func.,01V/F Pattern,02Motor Parameter). Up/down switchesgroups;READ/ENTER→Parameter Group Mode(PARA00:-00Control Method,-01Motor Direction,-02Run Source);up/downswitchesparameters. READ/ENTER→Parameter Edit Mode:00-00Control Method,0V/F,(0–4),<0>;00-01Motor Direction,0Forward,(0–1),<0>;00-02Run Source,0Digital Op,(0–4),<1>. Press▼or▲toeditandREAD/ENTERtosave;DSP/FUNreturnsonelevel. Source diagramrange0–4 conflictswithlater00-00table0–6;preserveexampleasprinted.
Manual — Auto-tuning mode navigation — page 106
Manual reference: physical PDF page 106. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Auto-tuning Mode In the auto-tuning mode motor parameters can be calculated and set automatically based on the selected control mode. See Fig 4.2.2.4 for keypad navigation.
Tune Mode Sel
READ ENT ER
Motor Rated Power
0 Rotational (0 ~ 2) < 0 >
5.50 KW (0.00 – 600.00) < 5.50>
Edit 17-00
000.00Hz-000.0A Auto-tuning Run
(Press Run Key)
0.0Hz – 0.0A
Autotuning
Aborted
>>>>>>>>>>>>>>>
0006.8 A (0000.9~0009.2) < 0006.8 >
Motor Sel
48.0Hz – 14.0A Autotuning
Successful
>>>>>>>>>>>>>>>>>>>>>>>
48.0Hz – 14.0A (Rotational)
Motor Data Error ATE01
Uncompleted
Edit 17-01
Edit 17-02
DSP FUN
Edit 17-10
Edit
Edit Edit
1 Enable (0~1) <0>
Autotuning ?
-01 Tune Mode Sel -02 Motor Rated Power -03 Motor Rated Curr.
PARA 17
-08 Mtr No-Load Volt -10 Auto-tuning Run -11 Auto-tuning Err
Group
17 Auto-tuning 18 Slip Compen 19 Traverse Func.
Press ▲ or ▼ key to change the value.
Warning: Do not use “0”, Rotation Auto-tune, when load is coupled with the motor.
*1HP = 0.746KW
STOP
RUN
Tuning successful
Tuning fault
READ ENT ER DSP FUN
Fig 4.2.2.4 Auto-tuning Mode Notes: - Set correct motor parameters by referring to motor nameplate. - Refer to section 4.4 for parameter details.
Fig4.2.2.4 Auto-tuning Mode. Group17Auto-tuning,18Slip Compen,19Traverse Func. PARA17menuprints-01Tune Mode Sel,-02Motor Rated Power,-03Motor Rated Curr.;editboxesinstead17-00Tune Mode Sel,0Rotational,(0–2),<0>;17-01Motor Rated Power5.50KW,(0.00–600.00),<5.50>,footnote1HP=0.746KW;17-02Motor Sel0006.8A,(0000.9–0009.2),<0006.8>. Warning:Do not use0 Rotation Auto-tune when load is coupled withmotor. LaterPARA17:-08Mtr No-Load Volt,-10Auto-tuning Run,-11Auto-tuning Err;17-10Auto-tuning Run1Enable,(0–1),<0>;READ/ENTER→Autotuning?000.00Hz-000.0A(Press Run Key);RUN→Autotuning48.0Hz–14.0A(Rotational). STOP→Aborted0.0Hz–0.0A;Tuning successful→Successful48.0Hz–14.0A;Tuningfault→ATE01Motor Data Error/Uncompleted. DSP/FUNreturns. Allvaluesillustrative,notactualratings;menu/editcodeoffsetflagged.
Manual — Auto-tuning notes — page 107
Manual reference: physical PDF page 107. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.2.2 Notes: 1. Use the up and down keys to scroll though the auto-tuning parameter list. Depending on the selected control mode in parameter 00-00, part of auto-tuning parameters will not be accessible. (Refer to the Auto-tuning Group 17 parameters). 2. After entering the motor nameplate rated output power (17-01), rated current (17-02), rated voltage (17-03), rated frequency (17-04), rated speed (17-05) and number of motor poles (17-06), select the automatic tuning mode and press the RUN key to perform the auto-tuning operation. When auto-tuning is successful the calculated motor parameters will be saved into parameter group 02 (motor parameter). 3. (a) “Rotational” will be displayed during rotational auto-tuning (17-00=0) and the motor will rotate during auto-tuning. Ensure that it is safe to operate the motor before pressing the RUN key. (b) “Stationary” will be displayed during stationary auto-tuning (17-00=1), the motor shaft does not rotate.
(c) “R1 Tuning” will be displayed during stationary auto-tuning (17-00=2), the motor shaft does not rotate. (d) The RUN LED (in the upper left corner of the RUN key) will be lit during auto-tuning. (e) The LCD display shows “>>>” or "Atund" during the auto-tuning process. 4. Press the STOP key on the keypad to abort the auto-tuning operation. 5. In case of an auto-tuning fault, a fault message and the uncompleted message are displayed on the keypad. The RUN LED will be flashing and the motor will coast to stop. (Refer to section 10.4 for the Auto-tuning Faults.) The auto-tuning fault can be cleared by pressing the RESET key after which the keypad displays the auto-tuning mode again. All motor parameters (group 02 through group 17 parameters) will revert back to their factory settings if a fault occurs. The motor data must be entered again before re-starting auto-tuning. The keypad shows “>>>” during an auto-tuning fault. 6. Upon successful completion of an auto-tune, the RUN LED will turn off. Press the DSP/FUN key to return to the main menu to select the next operation. The auto-tuning procedure takes approximately 50 seconds.
Manual — Parameter groups and attribute/software legend — page 108
Manual reference: physical PDF page 108. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.3 Parameters
Groups00–22 asprinted; no claimthislist covers lateredition groups.
The rightmergedsoftware-note cell is one shared legend,notone-to-one mappingwithleftattribute rows. 1–10 andNote1–8 are separatelegend systems.
Parameter group catalogue — PDF page 108
| Source row | Parameter group | Group Name |
|---|---|---|
| 1 | Group 00 | Basic Parameters |
| 2 | Group 01 | V/F Control Parameters |
| 3 | Group 02 | IM Motor Parameters |
| 4 | Group 03 | External Digital Input and Output Parameters |
| 5 | Group 04 | External Analog Input and Output Parameters |
| 6 | Group 05 | Multi-Speed Parameters |
| 7 | Group 06 | Automatic Program Operation Parameters |
| 8 | Group 07 | Start /Stop Parameters |
| 9 | Group 08 | Protection Parameters |
| 10 | Group 09 | Communication Parameters |
| 11 | Group 10 | PID Parameters |
| 12 | Group 11 | Auxiliary Parameters |
| 13 | Group 12 | Monitoring Parameters |
| 14 | Group 13 | Maintenance Parameters |
| 15 | Group 14 | PLC Parameters |
| 16 | Group 15 | PLC Monitoring Parameters |
| 17 | Group 16 | LCD Parameters |
| 18 | Group 17 | Automatic Tuning Parameters |
| 19 | Group 18 | Slip Compensation Parameters |
| 20 | Group 19 | Wobble Frequency Parameters |
| 21 | Group 20 | Speed Control Parameters |
| 22 | Group 21 | Torque And Position Control Parameters |
| 23 | Group 22 | PM Motor Parameters |
Parameter attribute and software-version legend — PDF page 108
| Source row | Attribute | Meaning | Software-note legend(shared region) |
|---|---|---|---|
| 1 | *1 | Parameters can be changed during run operation | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 2 | *2 | Reserved | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 3 | *3 | Parameter will not reset to default during a factory reset (initialization). | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 4 | *4 | Read-only parameter | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 5 | *5 | Parameter will be displayed in being coupled with the option card | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 6 | *6 | Parameter will be displayed only in LED keypad | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 7 | *7 | Parameter will be displayed only in LCD keypad | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 8 | *8 | When 13-08 setting is changed, the value will be also changed | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 9 | *9 | For enhanced E type & G type only | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
| 10 | *10 | Only available after I/O expansion card installed | Note1: New added or modified parameters in software V1.02 Note2: New added or modified parameters in software V1.10 Note3: New added or modified parameters in software V1.20 Note4: New added or modified parameters in software V1.30 Note5: New added or displayed parameters in software V1.30, when 00-32=8 Note6: Parameter edit available for software V1.30 above Note7: New added or modified parameters in software V1.41 Note8: New added or modified parameters in software V1.42 |
Manual — Parameter catalogue tables — page 109
Manual reference: physical PDF page 109. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 00: Basic Parameters — PDF page 109
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 00-00 | Control Mode Selection | 0: V/F | 0 | - | O | O | O | O | O | O | O | *3 |
| 2 | 00-00 | Control Mode Selection | 1: V/F+PG | 0 | - | O | O | O | O | O | O | O | *3 |
| 3 | 00-00 | Control Mode Selection | 2: SLV | 0 | - | O | O | O | O | O | O | O | *3 |
| 4 | 00-00 | Control Mode Selection | 3: SV | 0 | - | O | O | O | O | O | O | O | *3 |
| 5 | 00-00 | Control Mode Selection | 4: PMSV | 0 | - | O | O | O | O | O | O | O | *3 |
| 6 | 00-00 | Control Mode Selection | 5: PMSLV | 0 | - | O | O | O | O | O | O | O | *3 |
| 7 | 00-00 | Control Mode Selection | 6: SLV2 | 0 | - | O | O | O | O | O | O | O | *3 |
| 8 | 00-01 | Motor’s Rotation Direction | 0: Forward | 0 | - | O | O | O | O | O | O | O | *1 |
| 9 | 00-01 | Motor’s Rotation Direction | 1: Reverse | 0 | - | O | O | O | O | O | O | O | *1 |
| 10 | 00-02 | Main Run Command Source Selection | 0: Keypad | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 00-02 | Main Run Command Source Selection | 1: External Terminal (Control Circuit) | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 00-02 | Main Run Command Source Selection | 2: Communication Control (RS-485) | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 00-02 | Main Run Command Source Selection | 3: PLC | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 00-02 | Main Run Command Source Selection | 4: RTC Note8 | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 00-03 | Alternative Run Command Selection | 0: Keypad | 0 (Note4) | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 00-03 | Alternative Run Command Selection | 1: External Terminal (Control Circuit) | 0 (Note4) | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 00-03 | Alternative Run Command Selection | 2: Communication Control (RS-485) | 0 (Note4) | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 00-03 | Alternative Run Command Selection | 3: PLC | 0 (Note4) | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 00-03 | Alternative Run Command Selection | 4: RTC Note8 | 0 (Note4) | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 00-04 | Language | 0: English | 0 | - | O | O | O | O | O | O | O | *7 |
| 21 | 00-04 | Language | 1: Simplified Chinese | 0 | - | O | O | O | O | O | O | O | *7 |
| 22 | 00-04 | Language | 2: Traditional Chinese | 0 | - | O | O | O | O | O | O | O | *7 |
| 23 | 00-04 | Language | 3: Turkish | 0 | - | O | O | O | O | O | O | O | *7 |
| 24 | 00-05 | Main Frequency Command Source Selection | 0: Keypad | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 25 | 00-05 | Main Frequency Command Source Selection | 1: External Terminal (Analog 1) | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 26 | 00-05 | Main Frequency Command Source Selection | 2: Terminal Command UP/DOWN | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 27 | 00-05 | Main Frequency Command Source Selection | 3: Communication Control (RS-485) | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 28 | 00-05 | Main Frequency Command Source Selection | 4: Pulse Input | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 29 | 00-05 | Main Frequency Command Source Selection | 5: Reserved | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 30 | 00-05 | Main Frequency Command Source Selection | 6: RTC Note8 | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 31 | 00-05 | Main Frequency Command Source Selection | 7: AI2 Auxiliary Frequency | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 32 | 00-05 | Main Frequency Command Source Selection | 8: Manual Pulse Generator (MPG) Note4 | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 33 | 00-06 | Alternative Frequency Source | 0: Keypad | 0 (Note4) | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 34 | 00-06 | Alternative Frequency Source | 1: External Terminal (Analog 1) | 0 (Note4) | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 110
Manual reference: physical PDF page 110. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topcontinuation00-06 from109; blank code/default/unit/control cells remainblank; Selection isnamecontinuation.
Group 00: Basic Parameters — PDF page 110
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | Selection | 2: Terminal Command UP/DOWN | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | Selection | 3: Communication Control (RS-485) | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | Selection | 4: Pulse Input | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 4 | ⟦blank source cell⟧ | Selection | 5: Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | Selection | 6: RTC Note8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | Selection | 7: AI2 Auxiliary Frequency | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 7 | 00-07 | Main and Alternative Frequency Command Modes | 0: Main Frequency | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 00-07 | Main and Alternative Frequency Command Modes | 1: Main frequency + Alternative Frequency | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 00-08 | Communication Frequency Command Range | 0.00~599.00 | 0.00 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 00-09 | Communication Frequency Command Memory Selection | 0: Don’t save when power supply is off. (00-08) | 0 | - | O | O | O | O | O | - | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 11 | 00-09 | Communication Frequency Command Memory Selection | 1: Save when power is off. (00-08) | 0 | - | O | O | O | O | O | - | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 12 | 00-10 | Minimum frequency detection | 0:Show warning if lower than minimum frequency | 0 | - | O | O | O | O | O | O | O | Note1 |
| 13 | 00-10 | Minimum frequency detection | 1:Run as minimum frequency if lower than minimum frequency | 0 | - | O | O | O | O | O | O | O | Note1 |
| 14 | 00-11 | PID Lower Limit of Frequency Selection | 0: PID Sleep Limit is Lower Limit of Frequency | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 00-11 | PID Lower Limit of Frequency Selection | 1: PID Sleep Limit is 0Hz | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 00-12 | Upper limit Frequency | 0.1~109.0 | 100.0 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 00-13 | Lower limit Frequency | 0.0~109.0 | 0.0 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 00-14 | Acceleration Time 1 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 19 | 00-15 | Deceleration Time 1 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 20 | 00-16 | Acceleration Time 2 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 21 | 00-17 | Deceleration Time 2 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 22 | 00-18 | Jog Frequency**** | 0.00~599.00 | 6.00 | Hz | O | O | O | O | O | O | O | *1 |
| 23 | 00-19 | Jog Acceleration Time | 0.1~0600.0 | - | s | O | O | O | O | O | O | O | *1 |
Manual — Parameter catalogue tables — page 111
Manual reference: physical PDF page 111. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 00: Basic Parameters — PDF page 111
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 00-20 | Jog Deceleration Time | 0.1~0600.0 | - | s | O | O | O | O | O | O | O | *1 |
| 2 | 00-21 | Acceleration time 3 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 3 | 00-22 | Deceleration time 3 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 4 | 00-23 | Acceleration time 4 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 5 | 00-24 | Deceleration time 4 | 0.1~6000.0 | * | s | O | O | O | O | O | O | O | *1 |
| 6 | 00-25 | Switch-Over Frequency of Acc/Dec Time 1 and Time 4 | 0.00~599.00 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 00-26 | Emergency Stop Time | 0.1~6000.0 | 5.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 00-27 | HD/ND Mode Selection *** | 0: HD (Heavy Duty Mode) | 0 | - | O | O | O | O | O | O | O | *3 |
| 9 | 00-27 | HD/ND Mode Selection *** | 1: ND (Normal Duty Mode) | 0 | - | O | O | X | X | X | X | X | *3 |
| 10 | 00-28 | Command Characteristic selection of master frequency | 0: Positive Characteristic (0~10V/4~20mA is corresponding to 0~100%) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 00-28 | Command Characteristic selection of master frequency | 1: Negative Characteristic (0~10V/4~20mA is corresponding to 100~0%) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 00-29 | Zero-Speed Operation Selection | 0: Operation Based on Frequency Command | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 13 | 00-29 | Zero-Speed Operation Selection | 1: Stop | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 14 | 00-29 | Zero-Speed Operation Selection | 2: Operation Based on the Lowest Frequency | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 15 | 00-29 | Zero-Speed Operation Selection | 3: Zero-Speed Operation | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 16 | 00-30 00-31 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 17 | 00-32 | Application Selection Presets** | 0: General | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 00-32 | Application Selection Presets** | 1: Reserved | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 00-32 | Application Selection Presets** | 2: Conveyor | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 00-32 | Application Selection Presets** | 3: Exhaust Fan | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 21 | 00-32 | Application Selection Presets** | 4: Reserved | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 00-32 | Application Selection Presets** | 5: Compressor | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 23 | 00-32 | Application Selection Presets** | 6: Hoist** | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 24 | 00-32 | Application Selection Presets** | 7: Crane** | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 25 | 00-32 | Application Selection Presets** | 8: Manual Pulse Generator (MPG) Note4 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 112
Manual reference: physical PDF page 112. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
: Refer to the following attachment 1. : Before to set up 00-32 Application, it should do initialized setting (parameter 13-08) first. When setting 00-32, the I/O port function changed automatically. To avoid accident, be sure to confirm the I/O port signal of inverter and external terminal control. *** If parameter 00-27 is set to ND mode, group 02 motor 1 parameter will automatically adjust to more than 1 class of it. If parameter 00-27 is set to HD mode, group 02 motor 1 parameter will automatically adjust to the same class of it. It is suggested that parameter 00-27 be set first before motor performs auto-tuning because the parameter will make the motor parameter automatically be changed. **** If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 00: Basic Parameters — PDF page 112
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 00-33 | Modified Parameters (only for LCD keypad) | 0:Disable | 0 | - | O | O | O | O | O | O | O | *7 |
| 2 | 00-33 | Modified Parameters (only for LCD keypad) | 1:Enable | 0 | - | O | O | O | O | O | O | O | *7 |
| 3 | 00-34 ~ 00-40 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 4 | 00-41 | User parameter 0 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-41 | - | O | O | O | O | O | O | O | *7 |
| 5 | 00-42 | User parameter 1 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-42 | - | O | O | O | O | O | O | O | *7 |
| 6 | 00-43 | User parameter 2 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-43 | - | O | O | O | O | O | O | O | *7 |
| 7 | 00-44 | User parameter 3 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-44 | - | O | O | O | O | O | O | O | *7 |
| 8 | 00-45 | User parameter 4 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-45 | - | O | O | O | O | O | O | O | *7 |
| 9 | 00-46 | User parameter 5 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-46 | - | O | O | O | O | O | O | O | *7 |
| 10 | 00-47 | User parameter 6 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-47 | - | O | O | O | O | O | O | O | *7 |
| 11 | 00-48 | User parameter 7 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-48 | - | O | O | O | O | O | O | O | *7 |
| 12 | 00-49 | User parameter 8 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-49 | - | O | O | O | O | O | O | O | *7 |
| 13 | 00-50 | User parameter 9 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-50 | - | O | O | O | O | O | O | O | *7 |
| 14 | 00-51 | User parameter 10 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-51 | - | O | O | O | O | O | O | O | *7 |
| 15 | 00-52 | User parameter 11 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-52 | - | O | O | O | O | O | O | O | *7 |
| 16 | 00-53 | User parameter 12 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-53 | - | O | O | O | O | O | O | O | *7 |
| 17 | 00-54 | User parameter13 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-54 | - | O | O | O | O | O | O | O | *7 |
| 18 | 00-55 | User parameter 14 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-55 | - | O | O | O | O | O | O | O | *7 |
| 19 | 00-56 | User parameter 15 | Set 13-06 = 1, start user parameter. The setting range is 00-01 ~22-31, but except 00-41~00-56 and group 17 (only for LCD keypad) | 00-56 | - | O | O | O | O | O | O | O | *7 |
| 20 | 00-57 | SV High Speed Mode | 0: SV High Speed Mode1 | 0 | - | X | X | X | O | X | X | X | ⟦blank source cell⟧ |
| 21 | 00-57 | SV High Speed Mode | 1: SV High Speed Mode2 | 0 | - | X | X | X | O | X | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 113
Manual reference: physical PDF page 113. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 01: V/F Control Parameters — PDF page 113
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 01-00 | V/F Curve Selection | 0~FF | F | - | O | O | X | X | X | X | O | *3 |
| 2 | 01-01 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 3 | 01-02 | Maximum Output Frequency of Motor 1 | 4.8~599.0 | 50.0/ 60.0 | Hz | O | O | O | O | O | O | O | *8 |
| 4 | 01-03 | Maximum Output Voltage of Motor 1 | 200V: 0.1~255.0 | - | V | O | O | X | X | X | X | O | *8 |
| 5 | 01-03 | Maximum Output Voltage of Motor 1 | 400V: 0.2~510.0 | - | V | O | O | X | X | X | X | O | *8 |
| 6 | 01-03 | Maximum Output Voltage of Motor 1 | 575V: 0.1~670.0 | - | V | O | O | X | X | X | X | O | *8 |
| 7 | 01-03 | Maximum Output Voltage of Motor 1 | 690V: 0.1~804.0 | - | V | O | O | X | X | X | X | O | *8 |
| 8 | 01-04 | Middle Output Frequency 2 of Motor 1 | 0.0~599.0 | 0.0 | Hz | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 9 | 01-05 | Middle Output Voltage 2 of Motor 1 | 200V: 0.0~255.0 | 0.0 | V | O | O | X | X | X | X | O | *8 |
| 10 | 01-05 | Middle Output Voltage 2 of Motor 1 | 400V: 0.0~510.0 | 0.0 | V | O | O | X | X | X | X | O | *8 |
| 11 | 01-05 | Middle Output Voltage 2 of Motor 1 | 575V: 0.0~670.0 | 0.0 | V | O | O | X | X | X | X | O | *8 |
| 12 | 01-05 | Middle Output Voltage 2 of Motor 1 | 690V: 0.0~804.0 | 0.0 | V | O | O | X | X | X | X | O | *8 |
| 13 | 01-06 | Middle Output Frequency 1 of Motor 1 | 0.0~599.0 | 3.0 | Hz | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 14 | 01-07 | Middle Output Voltage 1 of Motor 1 | 200V: 0.0~255.0 | * | V | O | O | X | X | X | X | O | *8 |
| 15 | 01-07 | Middle Output Voltage 1 of Motor 1 | 400V: 0.0~510.0 | * | V | O | O | X | X | X | X | O | *8 |
| 16 | 01-07 | Middle Output Voltage 1 of Motor 1 | 575V: 0.0~670.0 | * | V | O | O | X | X | X | X | O | *8 |
| 17 | 01-07 | Middle Output Voltage 1 of Motor 1 | 690V: 0.0~804.0 | * | V | O | O | X | X | X | X | O | *8 |
| 18 | 01-08 | Minimum Output Frequency of Motor 1 | 0.0~599.0 | VF:1.5 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 01-08 | Minimum Output Frequency of Motor 1 | 0.0~599.0 | VF+PG: 1.5 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 01-08 | Minimum Output Frequency of Motor 1 | 0.0~599.0 | SLV: 0.6 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 21 | 01-08 | Minimum Output Frequency of Motor 1 | 0.0~599.0 | SV:0.1 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 01-08 | Minimum Output Frequency of Motor 1 | 0.0~599.0 | PMSV: 0.1 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 23 | 01-08 | Minimum Output Frequency of Motor 1 | 0.0~599.0 | PMSLV :9.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 24 | 01-08 | Minimum Output Frequency of Motor 1 | 0.0~599.0 | SLV2: 1.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 25 | 01-09 | Minimum Output Voltage of Motor 1 | 200V: 0.0~255.0 | 7.5 | V | O | O | X | X | X | X | O | *8 |
| 26 | 01-09 | Minimum Output Voltage of Motor 1 | 400V: 0.0~510.0 | 15.0 | V | O | O | X | X | X | X | O | *8 |
| 27 | 01-09 | Minimum Output Voltage of Motor 1 | 575V: 0.0~670.0 | 15.0 | V | O | O | X | X | X | X | O | *8 |
| 28 | 01-09 | Minimum Output Voltage of Motor 1 | 690V: 0.0~804.0 | 15.0 | V | O | O | X | X | X | X | O | *8 |
| 29 | 01-10 | Torque Compensation Gain | 0.0~2.0 | 0.5 | - | O | O | X | X | X | X | O | *1 |
Manual — Parameter catalogue tables — page 114
Manual reference: physical PDF page 114. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 01: V/F Control Parameters — PDF page 114
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 01-11 | Selection of Torque Compensation Mode | 0: Torque Compensation Mode 0 | 0 | - | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 2 | 01-11 | Selection of Torque Compensation Mode | 1: Torque Compensation Mode 1 | 0 | - | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 3 | 01-12 | Base Frequency of Motor 1 | 4.8~599.0 | 50.0/ 60.0 | Hz | O | O | O | O | O | O | O | *8 |
| 4 | 01-13 | Base Output Voltage of Motor 1 | 200V: 0.0~255.0 | - | V | O | O | X | X | X | X | O | *8 |
| 5 | 01-13 | Base Output Voltage of Motor 1 | 400V: 0.0~510.0 | - | V | O | O | X | X | X | X | O | *8 |
| 6 | 01-13 | Base Output Voltage of Motor 1 | 575V: 0.0~670.0 | - | V | O | O | X | X | X | X | O | *8 |
| 7 | 01-13 | Base Output Voltage of Motor 1 | 690V: 0.0~804.0 | - | V | O | O | X | X | X | X | O | *8 |
| 8 | 01-14 | Input Voltage Setting | 200V: 155.0~255.0 | - | V | O | O | O | O | O | O | O | *8 |
| 9 | 01-14 | Input Voltage Setting | 400V: 310.0~510.0 | - | V | O | O | O | O | O | O | O | *8 |
| 10 | 01-14 | Input Voltage Setting | 575V: 540.0~670.0 | - | V | O | O | O | O | O | O | O | *8 |
| 11 | 01-14 | Input Voltage Setting | 690V: 648.0~804.0 | - | V | O | O | O | O | O | O | O | *8 |
| 12 | 01-15 | Torque Compensation Time | 0~10000 | 200 | ms | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 13 | 01-16 | Maximum Output Frequency of Motor 2 | 4.8~599.0 | 50.0/ 60.0 | Hz | O | X | X | X | X | X | X | *8 |
| 14 | 01-17 | Maximum Output Voltage of Motor 2 | 200V: 0.1~255.0 | - | V | O | X | X | X | X | X | X | *8 |
| 15 | 01-17 | Maximum Output Voltage of Motor 2 | 400V: 0.2~510.0 | - | V | O | X | X | X | X | X | X | *8 |
| 16 | 01-17 | Maximum Output Voltage of Motor 2 | 575V: 0.1~670.0 | - | V | O | X | X | X | X | X | X | *8 |
| 17 | 01-17 | Maximum Output Voltage of Motor 2 | 690V: 0.1~804.0 | - | V | O | X | X | X | X | X | X | *8 |
| 18 | 01-18 | Middle Output Frequency 2 of Motor 2 | 0.0~599.0 | 0.0 | Hz | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 19 | 01-19 | Middle Output Voltage 2 of Motor 2 | 200V: 0.0~255.0 | 0.0 | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 20 | 01-19 | Middle Output Voltage 2 of Motor 2 | 400V: 0.0~510.0 | 0.0 | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 21 | 01-19 | Middle Output Voltage 2 of Motor 2 | 575V: 0.0~670.0 | 0.0 | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 22 | 01-19 | Middle Output Voltage 2 of Motor 2 | 690V: 0.0~804.0 | 0.0 | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 23 | 01-20 | Middle Output Frequency 1 of Motor 2 | 0.0~599.0 | 3.0 | Hz | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 24 | 01-21 | Middle Output Voltage 1 of Motor 2 | 200V: 0.0~255.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 25 | 01-21 | Middle Output Voltage 1 of Motor 2 | 400V: 0.0~510.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 26 | 01-21 | Middle Output Voltage 1 of Motor 2 | 575V: 0.0~670.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 27 | 01-21 | Middle Output Voltage 1 of Motor 2 | 690V: 0.0~804.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 28 | 01-22 | Minimum Output Frequency of Motor 2 | 0.0~599.0 | 1.5 | Hz | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 29 | 01-23 | Minimum Output Voltage of Motor 2 | 200V: 0.0~255.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 30 | 01-23 | Minimum Output Voltage of Motor 2 | 400V: 0.0~510.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 31 | 01-23 | Minimum Output Voltage of Motor 2 | 575V: 0.0~670.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 32 | 01-23 | Minimum Output Voltage of Motor 2 | 690V: 0.0~804.0 | KVA | V | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 115
Manual reference: physical PDF page 115. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
KVA: The default value of this parameter will be changed by different capacities of inverter.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 01: V/F Control Parameters — PDF page 115
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 01-24 | Base Frequency of Motor 2 | 4.8~599.0 | 50.0/ 60.0 | Hz | O | X | X | X | X | X | X | *8 |
| 2 | 01-25 | Base Output Voltage of Motor 2 | 200V: 0.0~255.0 | - | V | O | X | X | X | X | X | X | *8 |
| 3 | 01-25 | Base Output Voltage of Motor 2 | 400V: 0.0~510.0 | - | V | O | X | X | X | X | X | X | *8 |
| 4 | 01-25 | Base Output Voltage of Motor 2 | 575V: 0.0~670.0 | - | V | O | X | X | X | X | X | X | *8 |
| 5 | 01-25 | Base Output Voltage of Motor 2 | 690V: 0.0~804.0 | - | V | O | X | X | X | X | X | X | *8 |
| 6 | 01-26 | V/F Curve Selection of Motor 2 | 0~FF | F | - | O | X | X | X | X | X | X | *3 |
Group 02: IM Motor Parameters — PDF page 115
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 02-00 | No-Load Current of Motor1 | 0.01~600.00 | - | A | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 2 | 02-01 | Rated Current of Motor1 | Modes of V/F, V/F+PG are 10%~200% of inverter’s rated current. Modes of SLV, SV are 25%~200% of inverter’s rated current. | - | A | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 3 | 02-02 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 4 | 02-03 | Rated Rotation Speed of Motor1 | 0~60000 | - | Rpm | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 5 | 02-04 | Rated Voltage of Motor1 | 200V: 50.0~240.0 | - | V | O | O | O | O | X | X | O | *8 |
| 6 | 02-04 | Rated Voltage of Motor1 | 400V: 100.0~480.0 | - | V | O | O | O | O | X | X | O | *8 |
| 7 | 02-04 | Rated Voltage of Motor1 | 575V: 150.0~670.0 | - | V | O | O | O | O | X | X | O | *8 |
| 8 | 02-04 | Rated Voltage of Motor1 | 690V: 200.0~804.0 | - | V | O | O | O | O | X | X | O | *8 |
| 9 | 02-05 | Rated Power of Motor1 | 0.01~600.00 | - | kW | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 10 | 02-06 | Rated Frequency of Motor1 | 4.8~599.0 | 50.0/ 60.0 | Hz | O | O | O | O | X | X | O | *8 |
| 11 | 02-07 | Poles of Motor 1 | 2~16(Even) | 4 | - | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 12 | 02-08 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 13 | 02-09 | Excitation Current of Motor 1 | 15%~70% of Motor Rated Current | - | % | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 14 | 02-10 | Core Saturation Coefficient 1 of Motor 1 | 1~100 | - | % | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 116
Manual reference: physical PDF page 116. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 02: IM Motor Parameters — PDF page 116
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 02-11 | Core Saturation Coefficient 2 of Motor 1 | 1~100 | - | % | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 2 | 02-12 | Core Saturation Coefficient 3 of Motor 1 | 80~300 | - | % | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 3 | 02-13 | Core loss of Motor 1 | 0.0~15.0 | - | % | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 4 | 02-14 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 5 | 02-15 | Resistance between Wires of Motor 1 | 0.001~60.000 | - | Ω | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 6 | 02-16 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 7 | 02-17 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 8 | 02-18 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 9 | 02-19 | No-Load Voltage of Motor 1 | 200V: 50~240 | - | V | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 10 | 02-19 | No-Load Voltage of Motor 1 | 400V: 100~480 | - | V | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 11 | 02-19 | No-Load Voltage of Motor 1 | 575V: 420~600 | - | V | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 12 | 02-19 | No-Load Voltage of Motor 1 | 690V: 504~720 | - | V | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 13 | 02-20 | No-Load Current of Motor 2 | 0.01~600.00 | - | A | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 14 | 02-21 | Rated Current of Motor 2 | 10%~200% of inverter’s rated current | - | A | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 15 | 02-22 | Rated Rotation Speed of Motor 2 | 0~60000 | - | Rpm | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 16 | 02-23 | Rated Voltage of Motor 2 | 200V: 50.0~240.0 | - | V | O | X | X | X | X | X | X | *8 |
| 17 | 02-23 | Rated Voltage of Motor 2 | 400V: 100.0~480.0 | - | V | O | X | X | X | X | X | X | *8 |
| 18 | 02-23 | Rated Voltage of Motor 2 | 575V: 150.0~670.0 | - | V | O | X | X | X | X | X | X | *8 |
| 19 | 02-23 | Rated Voltage of Motor 2 | 690V: 200.0~804.0 | - | V | O | X | X | X | X | X | X | *8 |
| 20 | 02-24 | Rated Power of Motor 2 | 0.01~600.00 | - | kW | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 21 | 02-25 | Rated Frequency of Motor 2 | 4.8~599.0 | 50.0/ 60.0 | Hz | O | X | X | X | X | X | X | *8 |
| 22 | 02-26 | Poles of Motor 2 | 2~16 (Even) | 4 | - | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 23 | 02-27 ~ 02-31 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 24 | 02-32 | Resistance between Wires of Motor 2 | 0.001~60.000 | - | Ω | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 25 | 02-33 | Proportion of Motor 1 Leakage Inductance | 0.1~15.0 | 3.4 | % | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 117
Manual reference: physical PDF page 117. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Shared option catalogue separately retained; adjacentprintedoption slice does not limit thisparameter.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Shared S1–S8 catalogue pages117–119 orrelay03-11/03-12catalogue120–121; optionsandmodeavailability independentofverticallyadjacentterminalidentityblocks. No unsupportedper-terminalrestriction inferred.
Group 02: IM Motor Parameters — PDF page 117
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 02-34 | Motor 1 Slip Frequency | 0.10~20.00 | 1.00 | Hz | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 2 | 02-35 ~ 02-36 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 3 | 02-37 | Motor Mechanical Loss | 0.0~10.0 | 4.0 | % | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
Group 03: External Digital Input and Output Parameters / independent parameter identities/defaults — PDF page 117
| Source row | Parameter Code | Parameter Name | Default | Unit |
|---|---|---|---|---|
| 1 | 03-00 | Multi-Function Terminal Function Setting-S1 | 0 | - |
| 2 | 03-01 | Multi-Function Terminal Function Setting-S2 | 1 | - |
Group 03: External Digital Input and Output Parameters / shared setting-option catalogue — PDF page 117
| Source row | Shared setting option | V/F | V/F+PG | SLV | SV | PMSV | PMSLV | SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 0: 2-Wire Sequence (ON: Forward Run Command) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 1: 2-Wire Sequence (ON: Reverse Run Command) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 2: Multi-Speed/Position Setting Command 1 | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 3: Multi-Speed/Position Setting Command 2 | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 4: Multi-Speed/Position Setting Command 3 | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 5: Multi-Speed/Position Setting Command 4 | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 6: Forward Jog Run Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 7: Reverse Jog Run Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 8: UP Frequency Increasing Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 9: DOWN Frequency Decreasing Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 10: Acceleration/ Deceleration Time Selection 1 | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 11: Inhibit Acceleration/ Deceleration Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 12: Main/ Alternative Run Switch Function | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 13: Main/ Alternative Frequency Switch Function | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 118
Manual reference: physical PDF page 118. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Shared option catalogue separately retained; adjacentprintedoption slice does not limit thisparameter.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Shared S1–S8 catalogue pages117–119 orrelay03-11/03-12catalogue120–121; optionsandmodeavailability independentofverticallyadjacentterminalidentityblocks. No unsupportedper-terminalrestriction inferred.
Group 03: External Digital Input and Output Parameters / independent parameter identities/defaults — PDF page 118
| Source row | Parameter Code | Parameter Name | Default | Unit |
|---|---|---|---|---|
| 1 | 03-02 | Multi-Function Terminal Function Setting-S3 | 2 | - |
| 2 | 03-03 | Multi-Function Terminal Function Setting-S4 | 3 | - |
| 3 | 03-04 | Multi-Function Terminal Function Setting-S5 | 4 | - |
| 4 | 03-05 | Multi-Function Terminal Function Setting-S6 | 17 | - |
Group 03: External Digital Input and Output Parameters / shared setting-option catalogue — PDF page 118
| Source row | Shared setting option | V/F | V/F+PG | SLV | SV | PMSV | PMSLV | SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 14: Emergency Stop (decelerate to zero and stop) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 15: External Baseblock Command (rotation freely to stop) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 16: PID Control Disable | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 17: Fault Reset (RESET) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 18: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 6 | 19: Speed Search 1 (from the maximum frequency) | O | O | O | O | O | X | O | ⟦blank source cell⟧ |
| 7 | 20: Manual Energy Saving Function | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 8 | 21: PID Integral Reset | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 22~23 : Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 10 | 24: PLC Input | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 25: External Fault | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 26: 3-Wire Sequence (Forward/Reverse command) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 27: Local/ Remote Selection | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 28: Remote Mode Selection | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 29: Jog Frequency Selection | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 30: Acceleration/ Deceleration Time Selection 2 | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 31: Inverter Overheating Warning | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 32: Sync Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 33: DC Braking | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 20 | 34: Speed Search 2 (from the frequency command) | O | O | O | O | O | X | O | ⟦blank source cell⟧ |
| 21 | 35: Timing Function Input | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 36: PID Soft Start Disable | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 23 | 37: Traversing Operation | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 24 | 38: Upper Deviation of Traverse Operation | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 25 | 39: Lower Deviation of Traverse Operation | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 26 | 40: Switching between Motor 1/Motor 2 | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 27 | 41: PID Sleep | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 119
Manual reference: physical PDF page 119. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topoptions42/43continueS1–S8sharedlist. Shared option catalogue separately retained; adjacentprintedoption slice does not limit thisparameter.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topoptions42/43continueS1–S8sharedlist. Shared S1–S8 catalogue pages117–119 orrelay03-11/03-12catalogue120–121; optionsandmodeavailability independentofverticallyadjacentterminalidentityblocks. No unsupportedper-terminalrestriction inferred.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topoptions42/43continueS1–S8sharedlist.
Group 03: External Digital Input and Output Parameters / independent parameter identities/defaults — PDF page 119
| Source row | Parameter Code | Parameter Name | Default | Unit |
|---|---|---|---|---|
| 1 | 03-06 | Multi-Function Terminal Function Setting-S7 | 29* | - |
| 2 | 03-07 | Multi-Function Terminal Function Setting-S8 | 15 | - |
Group 03: External Digital Input and Output Parameters / shared setting-option catalogue — PDF page 119
| Source row | Shared setting option | V/F | V/F+PG | SLV | SV | PMSV | PMSLV | SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 42: PG Disable | X | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 2 | 43: PG Integral Reset | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 3 | 44: Mode Switching between Speed and Torque | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 4 | 45: Negative Torque Command | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 5 | 46: Zero-Servo Command | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 6 | 47: Fire mode(Forced Operation mode) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 48: KEB Acceleration | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 8 | 49: Parameters Writing Allowable | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 50: Unattended Start Protection (USP) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 51: Mode Switching between Speed and Position | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 11 | 52: Multi Position Reference Enable | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 12 | 53: 2-Wire Self Holding Mode (Stop Command) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 54: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 14 | 55: RTC Time Enable | O | O | O | O | O | O | O | Note8 |
| 15 | 56: RTC Offset Enable | O | O | O | O | O | O | O | Note8 |
| 16 | 57: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 17 | 58: Safety Function | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 59~61: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 19 | 62: EPS Function | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 63~64: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 21 | 65: Short-circuit braking | X | X | X | X | X | O | X | Note1 |
| 22 | 66: PID Disabled 2 | O | O | O | O | O | O | O | Note4 |
| 23 | 67: Manual Pulse Generator Mode Switch | O | X | X | X | X | X | X | Note4 |
| 24 | 68: External Fault 2 | O | O | O | O | O | O | O | Note4 |
| 25 | 69: External Overload | O | O | O | O | O | O | O | Note4 |
Group 03: External Digital Input and Output Parameters / other parameters — PDF page 119
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 03-08 | (S1~S8) DI Scan Time | 0: Scan Time 4ms 1: Scan Time 8ms | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 03-09 | Multi-Function Terminal S1-S4 Type Selection | xxx0b: S1 A Contact xxx1b: S1 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 03-09 | Multi-Function Terminal S1-S4 Type Selection | xx0xb: S2 A Contact xx1xb: S2 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 03-09 | Multi-Function Terminal S1-S4 Type Selection | x0xxb: S3 A Contact x1xxb: S3 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 03-09 | Multi-Function Terminal S1-S4 Type Selection | 0xxxb: S4 A Contact 1xxxb: S4 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 120
Manual reference: physical PDF page 120. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Shared option catalogue separately retained; adjacentprintedoption slice does not limit thisparameter.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Shared S1–S8 catalogue pages117–119 orrelay03-11/03-12catalogue120–121; optionsandmodeavailability independentofverticallyadjacentterminalidentityblocks. No unsupportedper-terminalrestriction inferred.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 03: External Digital Input and Output Parameters / independent parameter identities/defaults — PDF page 120
| Source row | Parameter Code | Parameter Name | Default | Unit |
|---|---|---|---|---|
| 1 | 03-11 | Relay (R1A-R1C) Output | 1 (Note4) | - |
| 2 | 03-12 (Note) | Relay (R2A-R2C) Output | 0 (Note4) | - |
Group 03: External Digital Input and Output Parameters / shared setting-option catalogue — PDF page 120
| Source row | Shared setting option | V/F | V/F+PG | SLV | SV | PMSV | PMSLV | SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 0: During Running | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 1: Fault Contact Output | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 2: Frequency Agree | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 3: Setting Frequency Agree | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 4: Frequency Detection 1 (≧03-13+03-14) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 5: Frequency Detection 2 (≦ 03-13+03-14) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 6: Automatic Restart | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 7~8: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 9 | 9: Baseblock | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 10~11: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 11 | 12: Over-Torque Detection | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 13: Current Agree | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 14: Mechanical Braking Control (03-17~18) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 15~17: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 15 | 18: PLC status | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 19: PLC Control Contact | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 20: Zero Speed | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 21: Inverter Ready | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 22: Under Voltage Detection | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 23: Source of Operation Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 21 | 24: Source of Frequency Command | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 25: Low Torque Detection | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 23 | 26: Frequency Reference Missing | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 24 | 27: Timing Function Output | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 25 | 28: Traverse Operation UP Status | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 26 | 29 : During Traverse Operation Status | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 27 | 30 : Motor 2 Selection | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Group 03: External Digital Input and Output Parameters / other parameters — PDF page 120
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 03-10 | Multi-Function Terminal S5-S8 Type Selection | xxx0b: S5 A Contact xxx1b: S5 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 03-10 | Multi-Function Terminal S5-S8 Type Selection | xx0xb: S6 A Contact xx1xb: S6 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 03-10 | Multi-Function Terminal S5-S8 Type Selection | x0xxb: S7 A Contact x1xxb: S7 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 03-10 | Multi-Function Terminal S5-S8 Type Selection | 0xxxb: S8 A Contact 1xxxb: S8 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 121
Manual reference: physical PDF page 121. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topoptions31–59continuerelay03-11/03-12sharedlist. Shared S1–S8 catalogue pages117–119 orrelay03-11/03-12catalogue120–121; optionsandmodeavailability independentofverticallyadjacentterminalidentityblocks. No unsupportedper-terminalrestriction inferred.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topoptions31–59continuerelay03-11/03-12sharedlist.
Group 03: External Digital Input and Output Parameters / shared setting-option catalogue — PDF page 121
| Source row | Shared setting option | V/F | V/F+PG | SLV | SV | PMSV | PMSLV | SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 31: Zero Speed Servo Status (Position Mode) | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 2 | 32: Communication Control Contacts | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 33: RTC Timer 1 | O | O | O | O | O | O | O | Note8 |
| 4 | 34: RTC Timer 2 | O | O | O | O | O | O | O | Note8 |
| 5 | 35: RTC Timer 3 | O | O | O | O | O | O | O | Note8 |
| 6 | 36: RTC Timer 4 | O | O | O | O | O | O | O | Note8 |
| 7 | 37: PID Feedback Loss Detection Output | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 38: Brake Release | X | X | O | O | O | X | X | ⟦blank source cell⟧ |
| 9 | 39: Frequency Detection 1 (dedicated for Crane) | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 10 | 40: Frequency Output | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 11 | 41: Position Agree (Position Mode) | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 12 | 42~44: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 13 | 45: PID sleep | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 46~49: Reserved | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 15 | 50: Frequency Detection 3 (≧ 03-44+03-45) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 51: Frequency Detection 4 (≦ 03-44+03-45) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 52: Frequency Detection 5 (≧ 03-46+03-47) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 53: Frequency Detection 6 (≦ 03-46+03-47) | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 54: Turn on short-circuit braking | X | X | X | X | X | O | X | Note1 |
| 20 | 57: Low Current Detection | O | O | O | O | O | O | O | Note2 |
| 21 | 58: Frequency Deceleration Detection | O | O | O | O | O | O | O | Note4 |
| 22 | 59: Over-Temperature Detection | O | O | O | O | O | O | O | Note4 |
Group 03: External Digital Input and Output Parameters / other parameters — PDF page 121
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 03-13 | Frequency Detection Level | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 03-14 | Frequency Detection Width | 0.1~25.5 | 2.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 03-15 | Current Agree Level | 0.1~999.9 | 0.1 | A | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 03-16 | Delay Time of Current Agree Detection | 0.1~10.0 | 0.1 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 122
Manual reference: physical PDF page 122. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 03: External Digital Input and Output Parameters — PDF page 122
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 03-17 | **Mechanical Braking Release Level | 0.00~599.00 | 0.00 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 03-18 | **Mechanical Braking Level Set | 0.00~599.00 | 0.00 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 03-19 | Relay (R1A-R2A) Type | xxx0b: R1 A Contact xxx1b: R1 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 03-19 | Relay (R1A-R2A) Type | xx0xb: R2 A Contact xx1xb: R2 C Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 03-19 | Relay (R1A-R2A) Type | 0xxxb: R4 A Contact 1xxxb: R4 B Contact | 0000b | - | O | O | O | O | O | O | O | *10 |
| 6 | 03-20 | Relay (R4A-R4C) Output | Range and definition are the same as those of 03-11, 03-12 | 2 | - | O | O | O | O | O | O | O | *10 |
| 7 | 03-21 | Photo-coupler Output Selection (DO2-DOG) | Range and definition are the same as those of 03-11, 03-12 | 3 | - | O | O | O | O | O | O | O | *10 |
| 8 | 03-22 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 9 | 03-23 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 10 | 03-24 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 11 | 03-25 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 12 | 03-26 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 13 | 03-27 | UP/DOWN Frequency Hold/Adjust Selection | 0: Hold last set frequency when stopped | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 03-27 | UP/DOWN Frequency Hold/Adjust Selection | 1: Set frequency to 0 when stopped | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 03-27 | UP/DOWN Frequency Hold/Adjust Selection | 2: Allow speed changes from last set frequency when stopped | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 03-27 | UP/DOWN Frequency Hold/Adjust Selection | 3: Refresh frequency at acceleration. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 03-28 | Photo-coupler Output (DO1-DOG) | Range and definition are the same as those of 03-11, 03-12 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 03-29 | Photo-coupler Output Selection (DO1-DOG) (DO2-DOG) | xxx0b: Photo-coupler 1 A Contact xxx1b: Photo-coupler 1 B Contact | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 03-29 | Photo-coupler Output Selection (DO1-DOG) (DO2-DOG) | xx0xb: Photo-coupler 2 A Contact xx1xb: Photo-coupler 2 B Contact | 0000b | - | O | O | O | O | O | O | O | *10 |
| 20 | 03-30 | Selection of Pulse Input | 0: General Pulse Input | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 21 | 03-30 | Selection of Pulse Input | 1: PWM | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 03-31 | Scale of Pulse Input | Depending on the setting of 03-30 | 1000 | Hz | O | O | O | O | O | O | O | *1 |
Manual — Parameter catalogue tables — page 123
Manual reference: physical PDF page 123. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Toprange03-30=0:50–32000Hz/03-30=1:10–1000Hz continues03-31from122.
Group 03: External Digital Input and Output Parameters — PDF page 123
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 03-30 = 0: 50~32000Hz 03-30 = 1:10~1000Hz | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 03-32 | Pulse Input Gain | 0.0~1000.0 | 100 | % | O | O | O | O | O | O | O | *1 |
| 3 | 03-33 | Pulse Input Bias | -100.0~100.0 | 0.0 | % | O | O | O | O | O | O | O | *1 |
| 4 | 03-34 | Filter Time of Pulse Input | 0.00~2.00 | 0.1 | Sec | O | O | O | O | O | O | O | *1 |
| 5 | 03-35 | Function Setting of Pulse Output | 1: Frequency Command | 2 | - | O | O | O | O | O | O | O | *1 |
| 6 | 03-35 | Function Setting of Pulse Output | 2: Output Frequency | 2 | - | O | O | O | O | O | O | O | *1 |
| 7 | 03-35 | Function Setting of Pulse Output | 3: Output Frequency after Soft-Start | 2 | - | O | O | O | O | O | O | O | *1 |
| 8 | 03-35 | Function Setting of Pulse Output | 4: Motor Speed | 2 | - | O | O | O | O | O | O | O | *1 |
| 9 | 03-35 | Function Setting of Pulse Output | 5: PID Feedback | 2 | - | O | O | O | O | O | O | O | *1 |
| 10 | 03-35 | Function Setting of Pulse Output | 6: PID Input | 2 | - | O | O | O | O | O | O | O | *1 |
| 11 | 03-35 | Function Setting of Pulse Output | 7: PG Output (with PG card) | 2 | - | O | O | O | O | O | O | O | *1 |
| 12 | 03-36 | Scale of Pulse Output | 1~32000 | 1000 | Hz | O | O | O | O | O | O | O | *1 |
| 13 | 03-37 | Timer ON Delay (DIO) | 0.0~6000.0 | 0.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 03-38 | Timer OFF Delay (DIO) | 0.0~6000.0 | 0.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 03-39 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 16 | 03-40 | Up/Down Frequency Width Setting | 0.00~5.00 | 0.00 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 03-41 | Torque Detection Level | 0~150 | 10 | % | X | X | O | O | O | X | X | ⟦blank source cell⟧ |
| 18 | 03-42 | Brake Release Delay Time | 0.00~65.00 | 0.00 | s | X | X | O | O | O | X | X | ⟦blank source cell⟧ |
| 19 | 03-43 | UP/DOWN Acceleration/ Deceleration Selection | 0: Acceleration/ Deceleration Time 1 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 03-43 | UP/DOWN Acceleration/ Deceleration Selection | 1: Acceleration/ Deceleration Time 2 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 21 | 03-44 | Frequency Detection Level 2 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 03-45 | Frequency Detection Width 2 | 0.1~25.5 | 2.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 23 | 03-46 | Frequency Detection Level 3 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 24 | 03-47 | Frequency Detection Width 3 | 0.1~25.5 | 2.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 25 | 03-48 | Low Current Detection Level | 0.0~999.9 | 0.1 | A | O | O | O | O | O | O | O | Note2 |
Manual — Parameter catalogue tables — page 124
Manual reference: physical PDF page 124. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- 2-wire operation mode: 29; 3-wire operation mode: 26. * *If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz Note: For frame 1, the DO2 function is setting by 03-12. Note: For standard H & C type frame 1, the DO2 function is setting by 03-12.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 03: External Digital Input and Output Parameters — PDF page 124
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 03-49 | Low Current Detection Delay Time | 0.00~655.34 (Note4) | 0.01 | Sec | O | O | O | O | O | O | O | Note2 |
| 2 | 03-50 | Frequency Detection Level 4 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | Note3 |
| 3 | 03-51 | Frequency Detection Level 5 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | Note3 |
| 4 | 03-52 | Frequency Detection Level 6 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | Note3 |
| 5 | 03-53 | Current Agree Level 2 | 0.0~999.9 | 0.1 | A | O | O | O | O | O | O | O | Note4 |
Group 04: External Analog Input and Output Parameters — PDF page 124
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 04-00 | AI Input Signal Type | 0: AI1:0~10V AI2:0~10V | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 04-00 | AI Input Signal Type | 1: AI1:0~10V AI2:4~20mA | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 04-00 | AI Input Signal Type | 2: AI1: -10~10V AI2: 0~10V | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 04-00 | AI Input Signal Type | 3: AI1: -10~10V AI2: 4~20mA | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 04-00 | AI Input Signal Type | 4: AI1: 4~20mA AI2: 0~10V | 1 | - | O | O | O | O | O | O | O | *9 |
| 6 | 04-00 | AI Input Signal Type | 5: AI1: 4~20mA AI2: 4~20mA | 1 | - | O | O | O | O | O | O | O | *9 |
| 7 | 04-01 | AI1 Signal Scanning and Filtering Time | 0.00~2.00 | 0.03 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 04-02 | AI1 Gain | 0.0~1000.0 | 100.0 | % | O | O | O | O | O | O | O | *1 |
| 9 | 04-03 | AI1 Bias | -100.0~100.0 | 0 | % | O | O | O | O | O | O | O | *1 |
| 10 | 04-04 | Negative AI | 0: Disable | 0 | - | O | O | O | O | O | O | O | Note4 |
| 11 | 04-04 | Negative AI | 1: Enable | 0 | - | O | O | O | O | O | O | O | Note4 |
| 12 | 04-05 | AI2 Function Setting | 0: Auxiliary Frequency | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 04-05 | AI2 Function Setting | 1: Frequency Reference Gain | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 125
Manual reference: physical PDF page 125. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topoptions2–17continue04-05from124.
Group 04: External Analog Input and Output Parameters — PDF page 125
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 2: Frequency Reference Bias | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 3: Output Voltage Bias | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | X | X | O | O | O | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4: Coefficient of Acceleration and Deceleration Reduction | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 5: DC Braking Current | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6: Over-Torque Detection Level | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 7: Stall Prevention Level During Running | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8: Frequency Lower Limit | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 9: Jump Frequency 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10: Added to AI1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11: Positive torque limit | ⟦blank source cell⟧ | ⟦blank source cell⟧ | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 11 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 12: Negative torque limit | ⟦blank source cell⟧ | ⟦blank source cell⟧ | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13: Regenerative Torque Limit | ⟦blank source cell⟧ | ⟦blank source cell⟧ | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14: Positive / Negative Torque Limit | ⟦blank source cell⟧ | ⟦blank source cell⟧ | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15: Torque Reference/ Torque Limit (in Speed Control) | ⟦blank source cell⟧ | ⟦blank source cell⟧ | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 16: Torque Compensation | ⟦blank source cell⟧ | ⟦blank source cell⟧ | X | X | O | O | O | X | X | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 17: PTC Overheat Protection | ⟦blank source cell⟧ | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 04-06 | AI2 Signal Scanning and Filtering Time | 0.00~2.00 | 0.03 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 04-07 | AI2 Gain | 0.0~1000.0 | 100.0 | % | O | O | O | O | O | O | O | *1 |
| 19 | 04-08 | AI2 Bias | -100.0~100.0 | 0 | % | O | O | O | O | O | O | O | *1 |
| 20 | 04-09 | AI Input Signal Type of I/O card | 0: AI3:0~10V 1: AI3:-10~10V 2: AI3:4~20mA | 0 | - | O | O | O | O | O | O | O | *10 |
| 21 | 04-10 | AI3 Function Setting | Range and definition are the same as those of 04-05 | 10 | - | O | O | O | O | O | O | O | *10 |
Manual — Parameter catalogue tables — page 126
Manual reference: physical PDF page 126. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 04: External Analog Input and Output Parameters — PDF page 126
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 04-11 | AO1 Function Setting | 0: Output Frequency | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 04-11 | AO1 Function Setting | 1: Frequency Command | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 04-11 | AO1 Function Setting | 2: Output Voltage | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 04-11 | AO1 Function Setting | 3: DC Voltage | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 04-11 | AO1 Function Setting | 4: Output Current | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 04-11 | AO1 Function Setting | 5: Output Power | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 04-11 | AO1 Function Setting | 6: Motor Speed | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 04-11 | AO1 Function Setting | 7: Output Power Factor | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 04-11 | AO1 Function Setting | 8: AI1 Input | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 04-11 | AO1 Function Setting | 9: AI2 Input | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 04-11 | AO1 Function Setting | 10: Torque Command | 0 | - | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 12 | 04-11 | AO1 Function Setting | 11: q-axis Current | 0 | - | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 13 | 04-11 | AO1 Function Setting | 12: d-axis Current | 0 | - | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 14 | 04-11 | AO1 Function Setting | 13: Speed Deviation | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 15 | 04-11 | AO1 Function Setting | 14: Reserved | 0 | - | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 16 | 04-11 | AO1 Function Setting | 15: ASR Output | 0 | - | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 17 | 04-11 | AO1 Function Setting | 16: Reserved | 0 | - | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 18 | 04-11 | AO1 Function Setting | 17: q-axis Voltage | 0 | - | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 19 | 04-11 | AO1 Function Setting | 18: d-axis Voltage | 0 | - | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 20 | 04-11 | AO1 Function Setting | 19~20: Reserved | 0 | - | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 21 | 04-11 | AO1 Function Setting | 21: PID Input | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 04-11 | AO1 Function Setting | 22: PID Output | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 23 | 04-11 | AO1 Function Setting | 23: PID Target Value | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 24 | 04-11 | AO1 Function Setting | 24: PID Feedback Value | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 25 | 04-11 | AO1 Function Setting | 25: Output Frequency of the Soft Starter | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 26 | 04-11 | AO1 Function Setting | 26: PG Feedback | 0 | - | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 27 | 04-11 | AO1 Function Setting | 27: Reserved | 0 | - | - | - | - | - | - | - | - | ⟦blank source cell⟧ |
| 28 | 04-11 | AO1 Function Setting | 28: Communication control | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 29 | 04-12 | AO1 Gain | 0.0~1000.0 | 100.0 | % | O | O | O | O | O | O | O | *1 |
| 30 | 04-13 | AO1 Bias | -100.0~100.0 | 0 | % | O | O | O | O | O | O | O | *1 |
| 31 | 04-14 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 32 | 04-15 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 33 | 04-16 | AO2 Function Setting | Range and definition are the same as those of 04-11. | 3 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 34 | 04-17 | AO2 Gain | 0.0~1000.0 | 100.0 | % | O | O | O | O | O | O | O | *1 |
| 35 | 04-18 | AO2 Bias | -100.0~100.0 | 0 | % | O | O | O | O | O | - | ⟦blank source cell⟧ | *1 |
| 36 | 04-19 | AO Output Signal Type | 0: AO1 0~10V AO2 0~10V | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 37 | 04-19 | AO Output Signal Type | 1: AO1 0~10V AO2 4~20mA | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 127
Manual reference: physical PDF page 127. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. Topoptions2/3continue04-19from126; *9 EnhancedE/Gonly.
Group 04: External Analog Input and Output Parameters — PDF page 127
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 2: AO1 4~20mA AO2 0~10V | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | *9 |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 3: AO1 4~20mA AO2 4~20mA | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | *9 |
| 3 | 04-20 | Filter Time of AO Signal Scan | 0.00~0.50 | 0.00 | s | O | O | O | O | O | O | O | *1 |
| 4 | 04-21 | AI3 Signal Scanning and Filtering Time | 0.00~2.00 | 0.03 | s | O | O | O | O | O | O | O | *10 |
| 5 | 04-22 | AI3 Gain | 0.0~1000.0 | 100.0 | % | O | O | O | O | O | O | O | *10 |
| 6 | 04-23 | AI3 Bias | -100.0~100.0 | 0 | % | O | O | O | O | O | O | O | *10 |
Group 05: Multi-Speed Parameters — PDF page 127
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 05-00 | Acceleration and Deceleration Selection of Multi-Speed | 0: Acceleration and deceleration time are set by 00-14 ~ 00-24 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 05-00 | Acceleration and Deceleration Selection of Multi-Speed | 1: Acceleration and Deceleration Time are set by 05-17 ~ 05-48 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 05-01 | *Frequency Setting of Speed-Stage 0 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 4 | 05-02 | *Frequency Setting of Speed-Stage 1 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 5 | 05-03 | *Frequency Setting of Speed-Stage 2 | 0.00~599.00 | 10.00 | Hz | O | O | O | O | O | O | O | *1 |
| 6 | 05-04 | *Frequency Setting of Speed-Stage 3 | 0.00~599.00 | 20.00 | Hz | O | O | O | O | O | O | O | *1 |
| 7 | 05-05 | *Frequency Setting of Speed-Stage 4 | 0.00~599.00 | 30.00 | Hz | O | O | O | O | O | O | O | *1 |
| 8 | 05-06 | *Frequency Setting of Speed-Stage 5 | 0.00~599.00 | 40.00 | Hz | O | O | O | O | O | O | O | *1 |
| 9 | 05-07 | *Frequency Setting of Speed-Stage 6 | 0.00~599.00 | 50.00 | Hz | O | O | O | O | O | O | O | *1 |
| 10 | 05-08 | *Frequency Setting of Speed-Stage 7 | 0.00~599.00 | 50.00 | Hz | O | O | O | O | O | O | O | *1 |
| 11 | 05-09 | *Frequency Setting of Speed-Stage 8 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 12 | 05-10 | *Frequency Setting of Speed-Stage 9 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 13 | 05-11 | *Frequency Setting of Speed-Stage 10 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
Manual — Parameter catalogue tables — page 128
Manual reference: physical PDF page 128. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability.
Group 05: Multi-Speed Parameters — PDF page 128
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 05-12 | *Frequency Setting of Speed-Stage 11 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 2 | 05-13 | *Frequency Setting of Speed-Stage 12 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 3 | 05-14 | *Frequency Setting of Speed-Stage 13 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 4 | 05-15 | *Frequency Setting of Speed-Stage 14 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 5 | 05-16 | *Frequency Setting of Speed-Stage 15 | 0.00~599.00 | 5.00 | Hz | O | O | O | O | O | O | O | *1 |
| 6 | 05-17 | Acceleration Time Setting of Multi Speed 0 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 05-18 | Deceleration Time Setting of Multi Speed 0 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 05-19 | Acceleration Time Setting of Multi Speed 1 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 05-20 | Deceleration Time Setting of Multi Speed 1 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 05-21 | Acceleration Time Setting of Multi Speed 2 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 05-22 | Deceleration Time Setting of Multi Speed 2 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 05-23 | Acceleration Time Setting of Multi Speed 3 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 05-24 | Deceleration Time Setting of Multi Speed 3 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 05-25 | Acceleration Time Setting of Multi Speed 4 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 05-26 | Deceleration Time Setting of Multi Speed 4 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 05-27 | Acceleration Time Setting of Multi Speed 5 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 05-28 | Deceleration Time Setting of Multi Speed 5 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 05-29 | Acceleration Time Setting of Multi Speed 6 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 05-30 | Deceleration Time Setting of Multi | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables — page 129
Manual reference: physical PDF page 129. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table; O,X,- andblank remainliteral availability marks. Asterisks,softwareNote1–8,defaultKVA/asterisk andvoltage/mode-specific subrows require page108legend andlocalnotes. Preserve source-cellmergegeometry; no inferreddefault oravailability. FirstSpeed6 isnamecontinuationof05-30from128.05-48 andfollowingnotesoutsidepartscope.
Group 05: Multi-Speed Parameters — PDF page 129
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | Speed 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 05-31 | Acceleration Time Setting of Multi Speed 7 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 05-32 | Deceleration Time Setting of Multi Speed 7 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 05-33 | Acceleration Time Setting of Multi Speed 8 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 05-34 | Deceleration Time Setting of Multi Speed 8 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 05-35 | Acceleration Time Setting of Multi Speed 9 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 05-36 | Deceleration Time Setting of Multi Speed 9 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 05-37 | Acceleration Time Setting of Multi Speed 10 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 05-38 | Deceleration Time Setting of Multi Speed 10 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 05-39 | Acceleration Time Setting of Multi Speed 11 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 05-40 | Deceleration Time Setting of Multi Speed 11 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 05-41 | Acceleration Time Setting of Multi Speed 12 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 05-42 | Deceleration Time Setting of Multi Speed 12 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 05-43 | Acceleration Time Setting of Multi Speed 13 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 05-44 | Deceleration Time Setting of Multi Speed 13 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 05-45 | Acceleration Time Setting of Multi Speed 14 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 05-46 | Deceleration Time Setting of Multi Speed 14 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 05-47 | Acceleration Time Setting of Multi Speed 15 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 130
Manual reference: physical PDF page 130. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. 05-48 completes Group05 from129; resolution footnote applies to starred frequencies. Group06 begins below.
Group 05: Multi-Speed Parameters — PDF page 130
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 05-48 | Deceleration Time Setting of Multi Speed 15 | 0.1~6000.0 | 10.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Group 06: Automatic Program Operation Parameters — PDF page 130
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 06-00 | Automatic Operation Mode Selection | 0: Disable | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 2 | 06-00 | Automatic Operation Mode Selection | 1: Execute a single cycle operation mode. Restart speed is based on the previous stopped speed. | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 3 | 06-00 | Automatic Operation Mode Selection | 2: Execute continuous cycle operation mode. Restart speed is based on the previous stopped speed. | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 4 | 06-00 | Automatic Operation Mode Selection | 3: After the completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the previous stopped speed. | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 5 | 06-00 | Automatic Operation Mode Selection | 4: Execute a single cycle operation mode. Restart speed will be based on the speed of stage 0. | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 6 | 06-00 | Automatic Operation Mode Selection | 5: Execute continuous cycle operation mode. Restart speed will be based on the speed of stage 0. | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 7 | 06-00 | Automatic Operation Mode Selection | 6: After the completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the speed of stage 0. | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 131
Manual reference: physical PDF page 131. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 06: Automatic Program Operation Parameters — PDF page 131
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 06-01 | *Frequency Setting of Operation-Stage 1 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 2 | 06-02 | *Frequency Setting of Operation-Stage 2 | 0.00~599.00 | 10.00 | Hz | O | O | O | X | X | X | O | *1 |
| 3 | 06-03 | *Frequency Setting of Operation-Stage 3 | 0.00~599.00 | 20.00 | Hz | O | O | O | X | X | X | O | *1 |
| 4 | 06-04 | *Frequency Setting of Operation-Stage 4 | 0.00~599.00 | 30.00 | Hz | O | O | O | X | X | X | O | *1 |
| 5 | 06-05 | *Frequency Setting of Operation-Stage 5 | 0.00~599.00 | 40.00 | Hz | O | O | O | X | X | X | O | *1 |
| 6 | 06-06 | *Frequency Setting of Operation-Stage 6 | 0.00~599.00 | 50.00 | Hz | O | O | O | X | X | X | O | *1 |
| 7 | 06-07 | *Frequency Setting of Operation-Stage 7 | 0.00~599.00 | 50.00 | Hz | O | O | O | X | X | X | O | *1 |
| 8 | 06-08 | *Frequency Setting of Operation-Stage 8 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 9 | 06-09 | *Frequency Setting of Operation-Stage 9 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 10 | 06-10 | *Frequency Setting of Operation-Stage 10 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 11 | 06-11 | *Frequency Setting of Operation-Stage 11 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 12 | 06-12 | *Frequency Setting of Operation-Stage 12 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 13 | 06-13 | *Frequency Setting of Operation-Stage 13 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 14 | 06-14 | *Frequency Setting of Operation-Stage 14 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
| 15 | 06-15 | *Frequency Setting of Operation-Stage 15 | 0.00~599.00 | 5.00 | Hz | O | O | O | X | X | X | O | *1 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 132
Manual reference: physical PDF page 132. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 06: Automatic Program Operation Parameters — PDF page 132
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 06-16 | Operation Time Setting of Speed-Stage 0 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 2 | 06-17 | Operation Time Setting of Speed-Stage 1 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 3 | 06-18 | Operation Time Setting of Speed-Stage 2 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 4 | 06-19 | Operation Time Setting of Speed-Stage 3 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 5 | 06-20 | Operation Time Setting of Speed-Stage 4 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 6 | 06-21 | Operation Time Setting of Speed-Stage 5 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 7 | 06-22 | Operation Time Setting of Speed-Stage 6 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 8 | 06-23 | Operation Time Setting of Speed-Stage 7 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 9 | 06-24 | Operation Time Setting of Speed-Stage 8 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 10 | 06-25 | Operation Time Setting of Speed-Stage 9 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 11 | 06-26 | Operation Time Setting of Speed-Stage 10 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 12 | 06-27 | Operation Time Setting of Speed-Stage 11 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 13 | 06-28 | Operation Time Setting of Speed-Stage 12 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 14 | 06-29 | Operation Time Setting of Speed-Stage 13 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 15 | 06-30 | Operation Time Setting of Speed-Stage 14 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 16 | 06-31 | Operation Time Setting of Speed-Stage 15 | 0.0~6000.0 | 0.0 | s | O | O | O | X | X | X | O | *1 |
| 17 | 06-32 | Operation Direction Selection of Speed-Stage 0 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 133
Manual reference: physical PDF page 133. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 06: Automatic Program Operation Parameters — PDF page 133
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 06-33 | Operation Direction Selection of Speed-Stage 1 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 2 | 06-34 | Operation Direction Selection of Speed-Stage 2 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 3 | 06-35 | Operation Direction Selection of Speed-Stage 3 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 4 | 06-36 | Operation Direction Selection of Speed-Stage 4 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 5 | 06-37 | Operation Direction Selection of Speed-Stage 5 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 6 | 06-38 | Operation Direction Selection of Speed-Stage 6 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 7 | 06-39 | Operation Direction Selection of Speed-Stage 7 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 8 | 06-40 | Operation Direction Selection of Speed-Stage 8 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 9 | 06-41 | Operation Direction Selection of Speed-Stage 9 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 10 | 06-42 | Operation Direction Selection of Speed-Stage 10 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 11 | 06-43 | Operation Direction Selection of Speed-Stage 11 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 12 | 06-44 | Operation Direction Selection of Speed-Stage 12 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 13 | 06-45 | Operation Direction Selection of Speed-Stage 13 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 14 | 06-46 | Operation Direction Selection of Speed-Stage 14 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 15 | 06-47 | Operation Direction Selection of Speed-Stage 15 | 0: Stop 1: Forward 2: Reverse | 0 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 134
Manual reference: physical PDF page 134. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 07: Start /Stop Parameters — PDF page 134
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 07-00 | Momentary Power Loss/Fault Restart Selection | 0: Disable | 0 | - | O | O | O | O | X | O | O | ⟦blank source cell⟧ |
| 2 | 07-00 | Momentary Power Loss/Fault Restart Selection | 1: Enable | 0 | - | O | O | O | O | X | O | O | ⟦blank source cell⟧ |
| 3 | 07-01 | Fault Auto-Restart Time | 0~7200 | 0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 07-02 | Number of Fault Auto-Restart Attempts | 0~10 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 07-03 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 6 | 07-04 | Direct Start at Power on | 0: When the external run command is enabled, direct start at power up | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 07-04 | Direct Start at Power on | 1: When the external run command is enabled, unable to direct start at power-up. | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 07-05 | Delay of Direct Start at Power on | 1.0~300.0 | 3.5 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 07-06 | DC Injection Braking Starting Frequency | 0.0~10.0 | 0.5 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 07-07 | DC Injection Braking Current | 0~100 | 50 | % | O | O | O | X | X | O | O | ⟦blank source cell⟧ |
| 11 | 07-08 | DC Injection Braking Time at Stop | 0.00~100.00 | 0.50 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 07-09 | Stop Mode Selection | 0: Deceleration to Stop | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 07-09 | Stop Mode Selection | 1: Coast to Stop | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 07-09 | Stop Mode Selection | 2: DC Braking Stop in All Fields | 0 | - | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 15 | 07-09 | Stop Mode Selection | 3: Coast to Stop with Timer | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 07-10 ~ 07-12 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 17 | 07-13 | Low Voltage Detection Level | 200V: 150~300 | 190 | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 07-13 | Low Voltage Detection Level | 400V: 250~600 | 380 | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 07-13 | Low Voltage Detection Level | 575V: 500~600 | 546 | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 07-13 | Low Voltage Detection Level | 690V: 500~600 | 546 | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 21 | 07-14 | Pre-excitation Time | 0.00~10.00 | 2.00 | s | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 22 | 07-15 | Pre-excitation Level | 50~200 | 100 | % | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 23 | 07-16 | DC Injection Braking Time at Start | 0.00~100.00 | 0.00 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 24 | 07-17 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 25 | 07-18 | Minimum Base block Time | 0.1~5.0 | - | Sec | O | O | O | O | X | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 135
Manual reference: physical PDF page 135. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 07: Start /Stop Parameters — PDF page 135
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 07-19 | Direction-Detection Speed Search Operating Current | 0~100 | 50 | % | O | X | O | X | X | X | O | ⟦blank source cell⟧ |
| 2 | 07-20 | Speed Search Operating Current | 0~100 | 20 | % | O | X | O | X | X | X | O | ⟦blank source cell⟧ |
| 3 | 07-21 | Integral Time of Speed Searching | 0.1~10.0 | 2.0 | Sec | O | X | O | X | X | X | O | ⟦blank source cell⟧ |
| 4 | 07-22 | Delay Time of Speed Searching | 0.0~20.0 | 0.2 | Sec | O | O | O | O | O | X | O | ⟦blank source cell⟧ |
| 5 | 07-23 | Voltage Recovery Time | 0.1~5.0 | 2.0 | Sec | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 6 | 07-24 | Direction-Detection Speed Search Selection | 0: Disable | 1 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 7 | 07-24 | Direction-Detection Speed Search Selection | 1: Enable | 1 | - | O | O | O | X | X | X | O | ⟦blank source cell⟧ |
| 8 | 07-25 | Low Voltage Detection Time | 0.00~1.00 | 0.02 | Sec | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 07-26 | Start-up Mode Selection of SLV Coast to Stop | 0: Start with speed search | 0 | - | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 10 | 07-26 | Start-up Mode Selection of SLV Coast to Stop | 1: Normal start | 0 | - | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 11 | 07-27 | Start Selection after Fault during SLV Mode | 0: Start with speed search | 0 | - | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 12 | 07-27 | Start Selection after Fault during SLV Mode | 1: Normal start | 0 | - | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 13 | 07-28 | Start after External Base Block | 0: Start with speed search | 0 | - | O | X | O | X | X | X | O | ⟦blank source cell⟧ |
| 14 | 07-28 | Start after External Base Block | 1: Normal start | 0 | - | O | X | O | X | X | X | O | ⟦blank source cell⟧ |
| 15 | 07-29 | Run Command Selection at the Action of DC Braking | 0: Not Allowable to Run | 0 | - | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 16 | 07-29 | Run Command Selection at the Action of DC Braking | 1: Allowable to Run | 0 | - | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 17 | 07-30 | Low Voltage Level Selection | 0: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 07-30 | Low Voltage Level Selection | 1: Enable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 07-31 | **Low Voltage Run Frequency | 0.00~599.00 | 10.00 | Hz | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 20 | 07-32 | Speed Search Mode Selection | 0: Disable | 0 | - | O | O | O | O | X | O | X | ⟦blank source cell⟧ |
| 21 | 07-32 | Speed Search Mode Selection | 1: Mode1: Execute a Speed Search at Power On | 0 | - | O | O | O | O | X | O | X | ⟦blank source cell⟧ |
| 22 | 07-32 | Speed Search Mode Selection | 2: Execute a Speed Search each time | 0 | - | O | O | O | O | X | O | X | ⟦blank source cell⟧ |
| 23 | 07-33 | Start Frequency of Speed Search Selection | 0: Maximum Output Frequency of Motor | 0 | - | O | O | O | O | X | X | X | ⟦blank source cell⟧ |
| 24 | 07-33 | Start Frequency of Speed Search Selection | 1: Frequency Command | 0 | - | O | O | O | O | X | X | X | ⟦blank source cell⟧ |
| 25 | 07-34 | Short-circuit braking time at Start | 0.00~100.00 | 0.00 | Sec | X | X | X | X | X | O | X | Note1 |
| 26 | 07-35 | Short-circuit braking time at Stop | 0.00~100.00 | 0.50 | Sec | X | X | X | X | X | O | X | Note1 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 136
Manual reference: physical PDF page 136. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
07-13 Low Voltage Detection Level, it is enable when 07-30 Low Voltage Level Selection set 0 (Enable) and lower frequency limit set to 250V.This application is for Emergency power supply (EPS) * If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. 07-30 enabling footnote contradicts table135; preserve both and flag. Lower frequency limit set to250V is source wording, not corrected.
Group 07: Start /Stop Parameters — PDF page 136
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 07-36 | Short-circuit braking current limited | 0.0~200.0 | 100.0 | % | X | X | X | X | X | O | X | Note1 |
| 2 | 07-37 ~ 07-41 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 3 | 07-42 | Voltage Limit Gain | 0.0~50.0 | 0 | % | X | X | O | O | X | X | X | Note2 |
| 4 | 07-43 | Short-circuit Braking Time of PM Speed Search | 0.00~100.00 | 0.00 | Sec | X | X | X | X | X | O | X | Note3 |
| 5 | 07-44 | DC Braking Time of PM Speed Search | 0.00~100.00 | 0.00 | Sec | X | X | X | X | X | O | X | Note3 |
| 6 | 07-45 | STP2 Function Selection | 0: STP2 Enable | 0 | - | O | O | O | O | O | O | O | Note4 |
| 7 | 07-45 | STP2 Function Selection | 1: STP2 Disable | 0 | - | O | O | O | O | O | O | O | Note4 |
| 8 | 07-46 | DC Injection Current Limit | 0~150 | 100 | % | O | X | X | X | X | X | X | Note5 |
| 9 | 07-47 | PM Speed Switching Frequency Mode | 0: Disabled | 0 | - | X | X | X | X | X | O | X | Note8 |
| 10 | 07-47 | PM Speed Switching Frequency Mode | 1: Mode 1 | 0 | - | X | X | X | X | X | O | X | Note8 |
| 11 | 07-47 | PM Speed Switching Frequency Mode | 2: Mode 2 | 0 | - | X | X | X | X | X | O | X | Note8 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 137
Manual reference: physical PDF page 137. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 08: Protection Parameters — PDF page 137
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 08-00 | Stall Prevention Function | xxx0b: Stall prevention is enabled in acceleration. | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 08-00 | Stall Prevention Function | xxx1b: Stall prevention is disabled in acceleration. | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 08-00 | Stall Prevention Function | xx0xb: Stall prevention is enabled in deceleration. | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 08-00 | Stall Prevention Function | xx1xb: Stall prevention is disabled in deceleration. | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 08-00 | Stall Prevention Function | x0xxb: Stall prevention is enabled in operation | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 08-00 | Stall Prevention Function | x1xxb: Stall prevention is disabled in operation | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 08-00 | Stall Prevention Function | 0xxxb: Stall prevention in operation is based on deceleration time of speed-stage 1. | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 08-00 | Stall Prevention Function | 1xxxb: Stall prevention in operation is based on deceleration time of speed-stage 2. | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 08-01 | Stall Prevention Level in Acceleration | 20~200 | HD:150 ND:120 | % | O | O | O | X | X | O | O | ⟦blank source cell⟧ |
| 10 | 08-02 | Stall Prevention Level in Deceleration | 200V: 330V~410V | 385V | V | O | O | O | O | X | O | O | ⟦blank source cell⟧ |
| 11 | 08-02 | Stall Prevention Level in Deceleration | 400V: 660V~820V | 770V | V | O | O | O | O | X | O | O | ⟦blank source cell⟧ |
| 12 | 08-02 | Stall Prevention Level in Deceleration | 575V: 900~1000 | 950V | V | O | O | O | O | X | O | O | ⟦blank source cell⟧ |
| 13 | 08-02 | Stall Prevention Level in Deceleration | 690V: 1080~1200 | 1140V | V | O | O | O | O | X | O | O | ⟦blank source cell⟧ |
| 14 | 08-03 | Stall Prevention Level in Operation | 30~200 | HD:160 | % | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 15 | 08-03 | Stall Prevention Level in Operation | 30~200 | ND:120 | % | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 16 | 08-04 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 17 | 08-05 | Selection for Motor Overload Protection (OL1) | xxx0b: Overload Protection is disabled. | 0001b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 08-05 | Selection for Motor Overload Protection (OL1) | xxx1b: Overload Protection is enabled. | 0001b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 08-05 | Selection for Motor Overload Protection (OL1) | xx0xb: Cold Start of Motor Overload | 0001b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 138
Manual reference: physical PDF page 138. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top options continue08-05 from137.
Group 08: Protection Parameters — PDF page 138
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | xx1xb: Hot Start of Motor Overload | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | x0xxb: Standard Motor | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | x1xxb: Inverter Duty Motor | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 0xxxb: Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1xxxb: Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 6 | 08-06 | Start-up Mode of Overload Protection Operation (OL1) | 0: Stop Output after Overload Protection | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 08-06 | Start-up Mode of Overload Protection Operation (OL1) | 1: Continuous Operation after Overload Protection. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 08-07 | Motor Overload (OL1) Protection Level | 0: Motor Overload (OL1) Protection 0 | 0 | - | O | O | O | O | O | O | O | Note2 |
| 9 | 08-07 | Motor Overload (OL1) Protection Level | 1: Motor Overload (OL1) Protection 1 | 0 | - | O | O | O | O | O | O | O | Note2 |
| 10 | 08-07 | Motor Overload (OL1) Protection Level | 2: Motor Overload (OL1) Protection 2 | 0 | - | O | O | O | O | O | O | O | Note2 |
| 11 | 08-08 | Automatic Voltage Regulation (AVR) | 0: Enable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 08-08 | Automatic Voltage Regulation (AVR) | 1: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 08-09 | Selection of Input Phase Loss Protection | 0: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 08-09 | Selection of Input Phase Loss Protection | 1: Enable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 08-10 | Selection of Output Phase Loss Protection | 0: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 08-10 | Selection of Output Phase Loss Protection | 1: Enable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 08-11 08-12 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 18 | 08-13 | Selection of Over-Torque Detection | 0: Over-Torque Detection is Disabled. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 08-13 | Selection of Over-Torque Detection | 1: Start to Detect when Reaching the Set Frequency. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 08-13 | Selection of Over-Torque Detection | 2: Start to Detect when the Operation is Begun. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 21 | 08-14 | Selection of Over-Torque Operation | 0: Deceleration to Stop when Over Torque is Detected. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 22 | 08-14 | Selection of Over-Torque Operation | 1: Display Warning when Over Torque is Detected. Go on Operation. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 23 | 08-14 | Selection of Over-Torque Operation | 2: Coast to Stop when Over Torque is Detected | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 24 | 08-15 | Level of Over-Torque | 0~300 | 150 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 139
Manual reference: physical PDF page 139. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top Detection is name continuation08-15 from138.
Group 08: Protection Parameters — PDF page 139
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | Detection | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 08-16 | Time of Over-Torque Detection | 0.0~10.0 | 0.1 | Sec | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 08-17 | Selection of Low-Torque Detection | 0: Low-Torque Detection is Disabled. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 08-17 | Selection of Low-Torque Detection | 1: Start to Detect when Reaching the Set Frequency. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 08-17 | Selection of Low-Torque Detection | 2: Start to Detect when the Operation is Begun. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 08-18 | Selection of Low-Torque Operation | 0: Deceleration to Stop when Low Torque is Detected. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 08-18 | Selection of Low-Torque Operation | 1: Display Warning when Low Torque is Detected. Go on Operation. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 08-18 | Selection of Low-Torque Operation | 2: Coast to Stop when Low Torque is Detected | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 08-19 | Level of Low-Torque Detection | 0~300 | 30 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 08-20 | Time of Low-Torque Detection | 0.0~10.0 | 0.1 | Sec | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 08-21 | Limit of Stall Prevention in Acc over Base Speed | 1~100 | 50 | % | O | O | O | X | X | O | O | ⟦blank source cell⟧ |
| 12 | 08-22 | Stall Prevention Detection Time in Operation | 2~100 | 100 | ms | O | O | O | X | X | O | O | ⟦blank source cell⟧ |
| 13 | 08-23 | Ground Fault (GF) Selection | 0: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 08-23 | Ground Fault (GF) Selection | 1: Enable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 08-24 | External Fault Operation Selection | 0: Deceleration to Stop | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 08-24 | External Fault Operation Selection | 1: Coast to Stop | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 08-24 | External Fault Operation Selection | 2: Continuous Operation | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 08-25 | Detection Selection of External Fault | 0: Immediately Detect when the Power is Supplied. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 08-25 | Detection Selection of External Fault | 1: Start to Detect when the Operation is Started. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 08-26 ~ 08-29 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 21 | 08-30 | Run Permissive | 0: Deceleration to Stop | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 140
Manual reference: physical PDF page 140. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top Function Selection and1Coast toStop continue08-30 from139.
Group 08: Protection Parameters — PDF page 140
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | Function Selection | 1: Coast to Stop | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 08-31 ~ 08-34 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 3 | 08-35 | Motor Overheating Fault Selection | 0: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 08-35 | Motor Overheating Fault Selection | 1: Deceleration to Stop | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 08-35 | Motor Overheating Fault Selection | 2: Free Run to top | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 08-35 | Motor Overheating Fault Selection | 3: Continue Running | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 08-36 | PTC Input Filter Time Constant | 0.00 ~ 5.00 | 2.00 | Sec | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 08-37 | Fan Control Function | 0: Start in operation | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 08-37 | Fan Control Function | 1: Permanent Start | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 08-37 | Fan Control Function | 2: Start in high temperature (Note) | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 08-38 | Delay Time of Fan Off | 0~600 | 60 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 08-39 | Delay Time of Motor Overheat Protection | 1~300 | 60 | sec | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 08-40 | Motor2 Acceleration Stall Prevention Level | 20~200 | HD:150 | % | O | O | O | X | X | O | O | ⟦blank source cell⟧ |
| 14 | 08-40 | Motor2 Acceleration Stall Prevention Level | 20~200 | ND:120 | % | O | O | O | X | X | O | O | ⟦blank source cell⟧ |
| 15 | 08-41 | Motor2 Acceleration Stall Prevention Limit | 1~100 | 50 | % | O | O | O | X | X | O | O | ⟦blank source cell⟧ |
| 16 | 08-42 | PTC Protection Level | 0.1~10.0V | 0.7 | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 08-43 | PTC Restart Level | 0.1~10.0V | 0.3 | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 08-44 | PTC Warning Level | 0.1~10.0V | 0.5 | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 08-45 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 20 | 08-46 | Temperature Agree Level | 0~254°C | 0 | °C | O | O | O | O | O | O | O | Note4 |
| 21 | 08-47 | Temperature Reset Level | 0~254°C | 0 | °C | O | O | O | O | O | O | O | Note4 |
| 22 | 08-48 | Selection of Fire Mode | 0: Disable 1: Enable | 0 | - | O | O | O | O | O | O | O | Note4 |
| 23 | 08-49 | Multi-Function Input Terminal Status of Fire Mode | 0:Reset after Power Off 1:Reset after Terminal Removed | 0 | - | O | O | O | O | O | O | O | Note4 |
| 24 | 08-50 | Multi-Function Terminal Status | XXX0b: S6 A contact XXX1b: S6 B contact | 0000b | - | O | O | O | O | O | O | O | Note4 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 141
Manual reference: physical PDF page 141. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Models of 200V 50HP and 400V 100HP and above don’t have this function.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top of Fire Mode continues08-50 from140. Plain Note below differs from softwareNote4.
Group 08: Protection Parameters — PDF page 141
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | of Fire Mode | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 08-51 | Motor Speed Setting Source of Fire Mode | 0:Fire Mode Speed (08-52) 1:PID Control 2:AI2 | 0 | - | O | O | O | O | O | O | O | Note4 |
| 3 | 08-52 | Motor Speed of Fire Mode | 0.00~100.00 | 100.00 | % | O | O | O | O | O | O | O | Note4 |
| 4 | 08-53 | PID Detection Level of Fire Mode | 0~100 | 0 | % | O | O | O | O | O | O | O | Note4 |
| 5 | 08-54 | Delay Time of Fire Mode PID Loss | 0.0~10.0 | 1.0 | s | O | O | O | O | O | O | O | Note4 |
| 6 | 08-55 | PID Feedback Loss Detection Selection of Fire Mode | 0:Keep Running 1:Fire Mode Speed (08-52) 2:Maximum Output Frequency (01-02) | 1 | - | O | O | O | O | O | O | O | Note4 |
| 7 | 08-56 | Detection Level of Fire Mode AI2 Signal | 0.0~100.0 | 80.0 | % | O | O | O | O | O | O | O | Note4 |
| 8 | 08-57 | Delay Time of Fire Mode AI2 Signal Loss | 0.0~10.0 | 1.0 | s | O | O | O | O | O | O | O | Note4 |
| 9 | 08-58 | Selection of Fire Mode AI2 Signal Loss | 0:Keep Running 1:Fire Mode Speed (08-52) 2:Maximum Output Frequency (01-02) | 1 | - | O | O | O | O | O | O | O | Note4 |
| 10 | 08-59 | Fire Mode Motor Direction | 0:Forward 1:Reverse | 0 | - | O | O | O | O | O | O | O | Note4 |
| 11 | 08-60 | Fire Mode Password | 00000~65534 | 0 | - | O | O | O | O | O | O | O | Note4 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 142
Manual reference: physical PDF page 142. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Parameter 09 does not be influenced by 13-08 (Restore Factory Setting)
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 09: Communication Parameters — PDF page 142
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 09-00 | INV Communication Station Address | 1~31 | 1 | - | O | O | O | O | O | O | O | *3 |
| 2 | 09-01 | Communication Mode Selection | 0: MODBUS | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *3 |
| 3 | 09-02 | Baud Rate Setting (bps) | 0: 1200 | 4 | - | O | O | O | O | O | O | O | *3 |
| 4 | 09-02 | Baud Rate Setting (bps) | 1: 2400 | 4 | - | O | O | O | O | O | O | O | *3 |
| 5 | 09-02 | Baud Rate Setting (bps) | 2: 4800 | 4 | - | O | O | O | O | O | O | O | *3 |
| 6 | 09-02 | Baud Rate Setting (bps) | 3: 9600 | 4 | - | O | O | O | O | O | O | O | *3 |
| 7 | 09-02 | Baud Rate Setting (bps) | 4: 19200 | 4 | - | O | O | O | O | O | O | O | *3 |
| 8 | 09-02 | Baud Rate Setting (bps) | 5: 38400 | 4 | - | O | O | O | O | O | O | O | *3 |
| 9 | 09-03 | Stop Bit Selection | 0: 1 Stop Bit | 0 | - | O | O | O | O | O | O | O | *3 |
| 10 | 09-03 | Stop Bit Selection | 1: 2 Stop Bit | 0 | - | O | O | O | O | O | O | O | *3 |
| 11 | 09-04 | Parity Selection | 0: No Parity | 0 | - | O | O | O | O | O | O | O | *3 |
| 12 | 09-04 | Parity Selection | 1: Even Bit | 0 | - | O | O | O | O | O | O | O | *3 |
| 13 | 09-04 | Parity Selection | 2: Odd Bit | 0 | - | O | O | O | O | O | O | O | *3 |
| 14 | 09-05 | Communication Data Bit Selection | 0: 8 Bit Data | 0 | - | O | O | O | O | O | O | O | *3 |
| 15 | 09-05 | Communication Data Bit Selection | 1: 7 Bit Data | 0 | - | O | O | O | O | O | O | O | *3 |
| 16 | 09-06 | Communication Error Detection Time | 0.0~25.5 | 0.0 | S | O | O | O | O | O | O | O | *3 |
| 17 | 09-07 | Fault Stop Selection | 0: Deceleration to Stop Based on Deceleration Time 1 when Communication Fault Occurs. | 3 | - | O | O | O | O | O | O | O | *3 |
| 18 | 09-07 | Fault Stop Selection | 1: Coast to Stop when Communication Fault Occurs. | 3 | - | O | O | O | O | O | O | O | *3 |
| 19 | 09-07 | Fault Stop Selection | 2: Deceleration to Stop Based on Deceleration Time 2 when Communication Fault Occurs. | 3 | - | O | O | O | O | O | O | O | *3 |
| 20 | 09-07 | Fault Stop Selection | 3: Keep Operating when Communication Fault Occurs. | 3 | - | O | O | O | O | O | O | O | *3 |
| 21 | 09-08 | Comm. Fault Tolerance Count | 1~20 | 1 | - | O | O | O | O | O | O | O | *3 |
| 22 | 09-09 | Waiting Time | 5~65 | 5 | ms | O | O | O | O | O | O | O | *3 |
| 23 | 09-10 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 143
Manual reference: physical PDF page 143. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 10: PID Parameters — PDF page 143
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 10-00 | PID Target Value Source Setting | 1: AI1 given | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 10-00 | PID Target Value Source Setting | 2: AI2 given | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 10-00 | PID Target Value Source Setting | 3: PI given | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 10-00 | PID Target Value Source Setting | 4:10-02 given | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 10-00 | PID Target Value Source Setting | 5: Reserved | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 10-00 | PID Target Value Source Setting | 6: Frequency Command (00-05) | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 10-01 | PID Feedback Value Source Setting | 1: AI1 given | 2 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 10-01 | PID Feedback Value Source Setting | 2: AI2 given | 2 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 10-01 | PID Feedback Value Source Setting | 3: PI given | 2 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 10-02 | PID Target Value | 0.00~100.00 | 0.00 | % | O | O | O | O | O | O | O | *1 |
| 11 | 10-03 | PID Control Mode | xxx0b: PID Disable | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 10-03 | PID Control Mode | xxx1b: PID Enable | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 10-03 | PID Control Mode | xx0xb: PID Positive Characteristic | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 10-03 | PID Control Mode | xx1xb: PID Negative Characteristic | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 10-03 | PID Control Mode | x0xxb: PID Error Value of D Control | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 10-03 | PID Control Mode | x1xxb: PID Feedback Value of D Ctrl | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 10-03 | PID Control Mode | 0xxxb: PID Output | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 10-03 | PID Control Mode | 1xxxb: PID Output + Frequency Command | 0000b | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 10-04 | Feedback Gain | 0.01~10.00 | 1.00 | - | O | O | O | O | O | O | O | *1 |
| 20 | 10-05 | Proportional Gain (P) | 0.00~10.00 | 1.00 | - | O | O | O | O | O | O | O | *1 |
| 21 | 10-06 | Integral Time (I) | 0.00~100.00 | 1.00 | s | O | O | O | O | O | O | O | *1 |
| 22 | 10-07 | Differential Time (D) | 0.00~10.00 | 0.00 | s | O | O | O | O | O | O | O | *1 |
| 23 | 10-08 | AI1 Frequency Limit | 0.00~599.00 | 0 | Hz | O | O | O | O | O | O | O | Note2 |
| 24 | 10-09 | PID Bias | -100.0~100.0 | 0 | % | O | O | O | O | O | O | O | *1 |
| 25 | 10-10 | PID Output Delay Time | 0.00~10.00 | 0.00 | s | O | O | O | O | O | O | O | *1 |
| 26 | 10-11 | PID Feedback Loss Detection Selection | 0: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 27 | 10-11 | PID Feedback Loss Detection Selection | 1: Warning | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 28 | 10-11 | PID Feedback Loss Detection Selection | 2: Fault | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 29 | 10-12 | PID Feedback Loss Det. Lev. | 0~100 | 0 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 30 | 10-13 | PID Feedback Loss Det. Time | 0.0~10.0 | 1.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 31 | 10-14 | PID Integral Limit | 0.0~100.0 | 100.0 | % | O | O | O | O | O | O | O | *1 |
| 32 | 10-15 | PID Trim Mode | 0~2 | 0 | - | O | O | O | O | O | O | O | Note2 |
| 33 | 10-16 | PID Trim Scale | 0~100 | 0 | % | O | O | O | O | O | O | O | Note2 |
| 34 | 10-17 | *Start Frequency of PID Sleep | 0.00~599.00 | 0.00 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 144
Manual reference: physical PDF page 144. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 10: PID Parameters — PDF page 144
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 10-18 | Delay Time of PID Sleep | 0.0~255.5 | 0.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 10-19 | *Frequency of PID Waking up | 0.00~599.00 | 0.00 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 10-20 | Delay Time of PID Waking up | 0.0~255.5 | 0.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 10-21 10-22 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 5 | 10-23 | PID Output Limit | 0.00~100.0 | 100.0 | % | O | O | O | O | O | O | O | *1 |
| 6 | 10-24 | PID Output Gain | 0.0~25.0 | 1.0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 10-25 | PID Reversal Output Selection | 0: No Allowing Reversal Output | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 10-25 | PID Reversal Output Selection | 1: Allow Reversal Output | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 10-26 | PID Target Acceleration/ Deceleration Time | 0.0~25.5 | 0.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 10-27 | PID Feedback Display Bias | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 10-28 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 12 | 10-29 | PID Sleep Selection | 0: Disable | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 10-29 | PID Sleep Selection | 1: Enable | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 10-29 | PID Sleep Selection | 2: set by DI | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 10-30 | Upper Limit of PID Target | 0.0 ~ 100.0 | 100.0 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 10-31 | Lower Limit of PID Target | 0.0 ~ 100.0 | 0.0 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 10-32 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 18 | 10-33 | Maximum Value of PID Feedback | 1 ~ 10000 | 999 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 19 | 10-34 | PID Decimal Width | 0 ~ 4 | 1 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 20 | 10-35 | PID Unit | 0: % | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 21 | 10-35 | PID Unit | 1: FPM | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 22 | 10-35 | PID Unit | 2: CFM | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 23 | 10-35 | PID Unit | 3: SPI | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 24 | 10-35 | PID Unit | 4: GPH | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 25 | 10-35 | PID Unit | 5: GPM | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 26 | 10-35 | PID Unit | 6: IN | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 27 | 10-35 | PID Unit | 7: FT | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 28 | 10-35 | PID Unit | 8: /s | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 29 | 10-35 | PID Unit | 9: /m | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 30 | 10-35 | PID Unit | 10: /h | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 31 | 10-35 | PID Unit | 11: °F | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 32 | 10-35 | PID Unit | 12: inW | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 33 | 10-35 | PID Unit | 13: HP | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
| 34 | 10-35 | PID Unit | 14: m/s | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *7 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 145
Manual reference: physical PDF page 145. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top15–24 unitoptions continue10-35 from144; default/unit/modes blank continuation, not zero/unavailable.
Group 10: PID Parameters — PDF page 145
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15: MPM | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 16: CMM | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 17: W | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 18: KW | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 19: m | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 20: °C | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21: RPM | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22: Bar | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 23: Pa | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 24: KPa | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 11 | 10-36 | Proportional Gain 2 (P) | 0.00~10.00 | 3.00 | - | O | O | O | O | O | O | O | Note2 |
| 12 | 10-37 | Integral Time 2 (I) | 0.00~100.00 | 0.50 | Sec | O | O | O | O | O | O | O | Note2 |
| 13 | 10-38 | Differential Time 2 (D) | 0.00~10.00 | 0.00 | Sec | O | O | O | O | O | O | O | Note2 |
| 14 | 10-39 | *Output Frequency Setting of PID Disconnection | 00.00~599.00 | 30.00 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 10-40 | Selection of PID Sleep Compensation Frequency | 0: Disable | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 10-40 | Selection of PID Sleep Compensation Frequency | 1: Enable | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 10-41 | PID Mode Switch | 0: General PID | 0 | - | O | O | O | O | O | O | O | Note2 |
| 18 | 10-41 | PID Mode Switch | 1: D Type PID | 0 | - | O | O | O | O | O | O | O | Note2 |
| 19 | 10-42 ~ 10-46 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 20 | 10-47 | Proportional Gain 3(P) | 0.00~10.00 | 1.00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note4 |
| 21 | 10-48 | Integral Time 3(I) | 0.00~100.00 | 1.00 | Sec | O | O | O | O | O | O | O | Note4 |
| 22 | 10-49 | Differential Time 3(D) | 0.00~10.00 | 0.00 | Sec | O | O | O | O | O | O | O | Note4 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 146
Manual reference: physical PDF page 146. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 11: Auxiliary Parameters — PDF page 146
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 11-00 | Direction Lock Selection | 0: Allow Forward and Reverse Rotation | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 11-00 | Direction Lock Selection | 1: Only Allow Forward Rotation | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 11-00 | Direction Lock Selection | 2: Only Allow Reverse Rotation | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 11-01 | Carrier frequency | 0: Carrier Output Frequency Tuning 1~16: 1~16KHz | * | - | O | O | O | O | O | O | O | *1 |
| 5 | 11-02 | Soft PWM Function Selection | 0: Disable | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 11-02 | Soft PWM Function Selection | 1: Soft PWM 1 enables | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 11-02 | Soft PWM Function Selection | 2: Soft PWM 2 enables | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 11-03 | Automatic carrier lowering selection | 0: Disable | 0 | - | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 9 | 11-03 | Automatic carrier lowering selection | 1: Enable | 0 | - | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 10 | 11-04 | S-curve Time Setting at the Start of Acceleration | 0.00~2.50 | 0.20 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 11-05 | S-curve Time Setting at the Stop of Acceleration | 0.00~2.50 | 0.20 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 11-06 | S-curve Time Setting at the Start of Deceleration | 0.00~2.50 | 0.20 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 11-07 | S-curve Time Setting at the Stop of Deceleration | 0.00~2.50 | 0.20 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 11-08 | Jump Frequency 1 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 11-09 | Jump Frequency 2 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 11-10 | Jump Frequency 3 | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 11-11 | Jump Frequency Width | 0.0~25.5 | 1.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 11-12 | Manual Energy Saving Gain | 0~100 | 80 | % | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 19 | 11-13 | Automatic Return Time | 0~120 | 60 | Sec | O | O | O | O | O | O | O | *1 |
| 20 | 11-14 ~ 11-17 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 21 | 11-18 | Manual Energy Saving Frequency | 0.0~599.0 | 0.00 | Hz | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 22 | 11-19 | Automatic Energy Saving Function | 0: Automatic energy saving is disabled. | 0 | - | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 23 | 11-19 | Automatic Energy Saving Function | 1: Automatic energy saving is enabled. | 0 | - | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 24 | 11-20 | Filter Time of Automatic Energy Saving | 0~200 | 140 | ms | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 25 | 11-21 | Voltage Upper | 0~100 | 100 | % | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 147
Manual reference: physical PDF page 147. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top Limit of Energy Saving Tuning continues11-21 from146.
Group 11: Auxiliary Parameters — PDF page 147
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | Limit of Energy Saving Tuning | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 11-22 | Adjustment Time of Automatic Energy Saving | 0~5000 | 20 | ms | O | X | X | X | X | X | X | *1 |
| 3 | 11-23 | Detection Level of Automatic Energy Saving | 0~100 | 10 | % | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 4 | 11-24 | Coefficient of Automatic Energy Saving | 0.00~655.34 (Note4) | - | - | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 5 | 11-25 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 6 | 11-26 | Carrier Output Frequency Tuning Upper Limit (%) | 10~100 | 80 | % | O | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 7 | 11-27 | Carrier Output Frequency Tuning Lower Limit (%) | 2~100 | 20 | % | O | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 8 | 11-28 | Frequency Gain of Over Voltage Prevention 2 | 1~200 | 100 | % | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 9 | 11-29 | Auto De-rating Selection | 0: Disable 1: Enable | 0 | - | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 10 | 11-30 | Variable Carrier Frequency Upper Limit | 2~16 | - | KHz | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 11 | 11-31 | Variable Carrier Frequency Lower Limit | 1~16 | - | KHz | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 12 | 11-32 | Variable Carrier Frequency Proportional Gain | 00~99 | 00 | - | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 13 | 11-33 | DC Voltage Filter Rise Amount | 0.1~10.0 | 0.1 | Vdc | O | O | X | X | X | X | X | *1 |
| 14 | 11-34 | DC Voltage Filter Fall Amount | 0.1~10.0 | 5.0 | Vdc | O | O | X | X | X | X | X | *1 |
| 15 | 11-35 | DC Voltage Filter Dead band Level | 0.0~99.0 | 10.0 | Vdc | O | O | X | X | X | X | X | *1 |
| 16 | 11-36 | Frequency Gain of OV Prevention | 0.000~1.000 | 0.050 | - | O | O | X | X | X | X | X | *1 |
| 17 | 11-37 | **Frequency Limit of OV Prevention | 0.00~599.00 | 5.00 | Hz | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 18 | 11-38 | Deceleration Start Voltage of OV Prevention | 200V: 200~400V | 300 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 19 | 11-38 | Deceleration Start Voltage of OV Prevention | 400V: 400~800V | 700 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 20 | 11-38 | Deceleration Start Voltage of OV Prevention | 575V: 500~1000V | 900 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 21 | 11-38 | Deceleration Start Voltage of OV Prevention | 690V: 600~1200V | 1080 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 22 | 11-39 | Deceleration Stop Voltage of OV Prevention | 200V: 300~400V | 350 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 23 | 11-39 | Deceleration Stop Voltage of OV Prevention | 400V: 600~800V | 750 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 24 | 11-39 | Deceleration Stop Voltage of OV Prevention | 575V: 500~1000V | 950 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 25 | 11-39 | Deceleration Stop Voltage of OV Prevention | 690V: 600~1200V | 1140 | V | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 148
Manual reference: physical PDF page 148. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 11: Auxiliary Parameters — PDF page 148
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 11-40 | OV Prevention Selection | 0: Disable 1: OV Prevention Mode 1 2: OV Prevention Mode 2 3: OV Prevention Mode 3 | 0 | - | O | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 2 | 11-41 | Selection of Reference Frequency Disappearance Detection | 0: Decelerate to Stop when Reference Frequency Disappears 1: Operation is set by Parameter 11-42 when Reference Frequency Disappears | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 11-42 | Disappearance Level of Reference Frequency | 0.0~100.0 | 80.0 | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 11-43 | Hold Frequency at Start | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 11-44 | Frequency Hold Time at Start | 0.0~10.0 | 0.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 11-45 | Hold Frequency at Stop | 0.0~599.0 | 0.0 | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 11-46 | Frequency Hold Time at Stop | 0.0~10.0 | 0.0 | s | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 11-47 | KEB Deceleration Time | 0.0~25.5 | 0.0 | s | O | O | X | X | X | X | O | *1 |
| 9 | 11-48 | KEB Detection Level | 200V: 190~210 | 200 | V | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 10 | 11-48 | KEB Detection Level | 400V: 380~420 | 400 | V | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 11 | 11-48 | KEB Detection Level | 575V: 540~570 | 555 | V | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 12 | 11-48 | KEB Detection Level | 690V: 540~684 | 555 | V | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 13 | 11-49 | Zero-servo Gain | 0.01~5.00 | 1.00 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 14 | 11-50 | Zero-servo Count | 0~4096 | 12 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 15 | 11-51 | Braking Selection of Zero Speed | 0: Disable 1: Enable | 0 | - | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 16 | 11-52 | Droop Control Level | 0.0~100.0% | 0.0 | % | X | X | O (Note4) | O | O | O (Note4) | X | *1 |
| 17 | 11-53 | Droop Control Delay | 0.01~2.00 | 0.2 | s | X | X | O (Note4) | O | O | O (Note4) | X | *1 |
| 18 | 11-54 | Initialization of Cumulative Energy | 0: Do not Clear Cumulative Energy 1: Clear Cumulative Energy | 0 | - | O | O | O | O | O | O | O | *1 |
| 19 | 11-55 | STOP Key Selection | 0: Stop Key is Disabled when the Operation Command is not Provided by Operator. | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 149
Manual reference: physical PDF page 149. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top1StopKeyEnabled continues11-55 from148.
Group 11: Auxiliary Parameters — PDF page 149
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1: Stop Key is Enabled when the Operation Command is not Provided by Operator. | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 11-56 | UP/DOWN Selection | 0: When UP/DOWN in Keypad is Disabled, it will be Enabled if Pressing ENTER after Frequency Modification. 1: When UP/DOWN in Keypad is Enabled, it will be Enabled upon Frequency Modification. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 11-57 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 4 | 11-58 | Record Reference Frequency | 0: Disable 1: Enable | 0 | - | O | O | O | O | O | O | O | *1 |
| 5 | 11-59 | Gain of Preventing Oscillation | 0.00~2.50 | * | ⟦blank source cell⟧ | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 6 | 11-60 | Upper Limit of Preventing Oscillation | 0~100 | * | % | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 7 | 11-61 | Time Parameter of Preventing Oscillation | 0~100 | 0 | ⟦blank source cell⟧ | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 8 | 11-62 | Selection of Preventing Oscillation | 0: Mode1 1: Mode2 2: Mode3 | 1 | ⟦blank source cell⟧ | O | O | X | X | X | X | O | ⟦blank source cell⟧ |
| 9 | 11-63 | Strong Magnetic Selection | 0: Disable 1: Enable | 1 | ⟦blank source cell⟧ | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 10 | 11-64 | Acceleration Speed Gain Adjustment | 0.1~10.0 | 1.0 | - | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 11 | 11-65 | Target Main Circuit Voltage | 200V: 200V~400V | 370 | - | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 12 | 11-65 | Target Main Circuit Voltage | 400V: 400V~800V | 740 | - | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 13 | 11-65 | Target Main Circuit Voltage | 575V: 520V~1040V | 962 | - | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 14 | 11-65 | Target Main Circuit Voltage | 690V: 624V~1248V | 1154 | - | O | X | X | X | X | X | O | ⟦blank source cell⟧ |
| 15 | 11-66 | 2 Phase/ 3 Phase PWM Switch Frequency | 6.00~60.00 | 20 | Hz | X | X | O | O | X | O | O | Note2 |
| 16 | 11-67 | Soft PWM 2 Frequency Range | 0~12000 | 0 | Hz | X | X | O | O | O | O | X | Note2 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 150
Manual reference: physical PDF page 150. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
*: Refer to the attachment 1. ** If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz Note: The parameter of 11-01 can be changed during run operation, the range is 1~16KHz.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Adjacent source context — repeated to preserve continuation:
Group 11: Auxiliary Parameters — PDF page 150
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 11-68 | Soft PWM 2 Switch Frequency | 6.00~60.00 | 20 | Hz | X | X | O | O | O | O | X | Note2 |
| 2 | 11-69 | Gain of Preventing Oscillation 3 | 0.00~200.00 | 5.00 | % | O | O | X | X | X | X | X | Note1 |
| 3 | 11-70 | Upper Limit of Preventing Oscillation 3 | 0.01~100.00 | 5.00 | % | O | O | X | X | X | X | X | Note1 |
| 4 | 11-71 | Time Parameter of Preventing Oscillation 3 | 0~30000 | 100 | ms | O | O | X | X | X | X | X | Note1 |
| 5 | 11-72 | Gain of Preventing Oscillation for switch frequency 1 | 0.01~300.00 | 30.00 | Hz | O | O | X | X | X | X | X | Note1 |
| 6 | 11-73 | Gain of Preventing Oscillation for switch frequency 2 | 0.01~300.00 | 50.00 | Hz | O | O | X | X | X | X | X | Note1 |
| 7 | 11-76 | Droop Frequency Level 1 | 0.00~599.00 | 0.00 | Hz | X | X | O | O | O | O | X | Note4 |
| 8 | 11-77 | Droop Frequency Level 2 | 0.00~599.00 | 0.00 | Hz | X | X | O | O | O | O | X | Note4 |
| 9 | 11-78 | Droop Torque Offset Value | 0.00~100.00 | 0.00 | % | X | X | O | O | O | O | X | Note4 |
| 10 | 11-79 | LOC/REM Keypad Button Selection | 0: Forward / Reverse control 1: Local / Remote control | 1 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 11-80 | Local / Remote Selection Mode | 0: Allow Switching Directly 1: Switching Prohibited at Running 2: Stop after Switching | 0 | - | O | X | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 11-81 | OVP4 Level (%) | 100~200 | 110 | % | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 13 | 11-82 | OVP4 Gain | 0~256 | 64 | - | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 151
Manual reference: physical PDF page 151. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Adjacent source context — repeated to preserve continuation:
Group 12: Monitoring Parameters — PDF page 151
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 12-00 | Display Screen Selection (LED) | 00000~77777 From the leftmost bit, it displays the screen when press DSP key in order. 0:no display 1: Output Current 2: Output Voltage 3: DC Bus Voltage 4: Heatsink Temperature* 5: PID Feedback 6: AI1 Value 7: AI2 Value | 00321 (Note4) | - | O | O | O | O | O | O | O | *1 *6 |
| 2 | 12-01 | PID Feedback Display Mode (LED) | 0: Display the Feedback Value by Integer (xxx) | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *6 |
| 3 | 12-01 | PID Feedback Display Mode (LED) | 1: Display the Feedback Value by the Value with One Decimal Place (xx.x) | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *6 |
| 4 | 12-01 | PID Feedback Display Mode (LED) | 2: Display the Feedback Value by the Value with Two Decimal Places (x.xx) | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *6 |
| 5 | 12-02 | PID Feedback Display Unit Setting (LED) | 0: xxxxx (no unit) | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *6 |
| 6 | 12-02 | PID Feedback Display Unit Setting (LED) | 1: xxxPb (pressure) | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *6 |
| 7 | 12-02 | PID Feedback Display Unit Setting (LED) | 2: xxxFL (flow) | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *6 |
| 8 | 12-03 | Line Speed Display (LED) | 0~60000 | 1500/ 1800 | RPM | O | O | O | O | O | O | O | *6 |
| 9 | 12-04 | Modes of Line Speed Display (LED) | 0: Display Inverter Output Frequency | 0 | - | O | O | O | O | O | O | O | *1 *6 |
| 10 | 12-04 | Modes of Line Speed Display (LED) | 1: Display Line Speed with integer (xxxxx) | 0 | - | O | O | O | O | O | O | O | *1 *6 |
| 11 | 12-04 | Modes of Line Speed Display (LED) | 2: Display Line Speed with the First Decimal Place (xxxx.x) | 0 | - | O | O | O | O | O | O | O | *1 *6 |
| 12 | 12-04 | Modes of Line Speed Display (LED) | 3: Display Line Speed with the Second Decimal Place (xxx.xx) | 0 | - | O | O | O | O | O | O | O | *1 *6 |
| 13 | 12-04 | Modes of Line Speed Display (LED) | 4: Display Line Speed with the Third Decimal Place (xx.xxx) | 0 | - | O | O | O | O | O | O | O | *1 *6 |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 152
Manual reference: physical PDF page 152. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
12-05 digital I/O status display. LED no input: five illuminated horizontal middle segments; decimal dots gray/unlit. Input indicators S1,S2,S3,S4,S5,S6,S7,S8 run left-to-right across upper-left and upper-right segments of first four digit positions. Output indicators R1,R2,DO1 use lower outline/middle segments in first three digit positions, as illustrated. LCD example has eleven displayed zeros; 0:OPEN,1:CLOSE. Left-to-right bit labels: Output Terminal(R1),Output Terminal(R2),Output Terminal(DO1),Input Terminal(S1),Input Terminal(S2),Input Terminal(S3),Input Terminal(S4),Input Terminal(S5),Input Terminal(S6),Input Terminal(S7),Input Terminal(S8). Figure shows status mapping, not physical wiring topology or actual operating state.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. 12-05 contains display diagrams: native cell text retained plus bounded visual figure record; do not read segment drawings as numerical motor values.
Group 12: Monitoring Parameters — PDF page 152
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 12-05 | Status Display of Digital Input & Output Terminal (LED / LCD) | LED display is shown as below no input correspondences to input and output LCD display is shown as below 0 0 0 0 0 0 0 0 Input Terminal(S8) Input Terminal(S7) Input Terminal(S6) Input Terminal(S5) Input Terminal(S4) Input Terminal(S3) Input Terminal(S2) Input Terminal(S1) 0:OPEN 1:CLOSE 0 0 0 Output Terminal(DO1) Output Terminal(R2) Output Terminal(R1) | - | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 12-06 ~ 12-10 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 3 | 12-11 | Output Current of Current Fault | Display the output current of current fault | - | A | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 12-12 | Output Voltage of Current Fault | Display the output voltage of current fault | - | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 12-13 | Output Frequency of Current Fault | Display the output frequency of current fault | - | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 12-14 | DC Voltage of Current Fault | Display the DC voltage of current fault | - | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 12-15 | Frequency Command of Current Fault | Display the frequency command of current fault | - | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 12-16 | Frequency Command | If LED enters this parameter, it only allows monitoring frequency command. | - | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 12-17 | Output Frequency | Display the current output frequency | - | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 12-18 | Output Current | Display the current output current | - | A | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 153
Manual reference: physical PDF page 153. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 12: Monitoring Parameters — PDF page 153
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 12-19 | Output Voltage | Display the current output voltage | - | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 12-20 | DC Voltage (Vdc) | Display the current DC voltage | - | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 12-21 | Output Power (kw) | Display the current output power | - | kW | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 12-22 | Motor’s Rotation Speed (rpm) | Display motor’s current rotation speed in VF/SLV mode Motor’s rotation speed = output frequency x(120/motor’s pole number) In PG/SV mode, motor’s rotation speed is calculated by feedback frequency. Max limit is 65535 | - | rpm | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 12-23 | Output Power Factor (Pfo) | Display the current output power factor | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 12-24 | Control Mode | Display control mode 0: VF 1: PG 2: SLV 3: SV 4: PSV 5: PMSLV 6: SLV2 | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 12-25 | AI1 Input | Display the current Al1 input (-10V corresponds to -100%, 10V corresponds to 100%,) | - | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 12-26 | AI2 Input | Display the current Al2 input (0V or 4mA corresponds to 0%, 10V or 20mA corresponds to 100%) | - | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 12-27 | Motor Torque | Display the current torque command (100% corresponds to motor torque ) | - | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 10 | 12-28 | Motor Torque Current (Iq) | Display the current q-axis current | - | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 11 | 12-29 | Motor Excitation Current (Id) | Display the current d-axis current | - | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 12 | 12-30 | ASR Deviation | Display deviation of speed controller (speed command - speed feedback) (100% corresponds to the | - | % | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: automatic operation, start/stop, protection, communications, PID, auxiliary and monitoring — page 154
Manual reference: physical PDF page 154. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Topmaximumfrequencysetby01-02continues12-30from153.12-41asteriskfootnotes beyondpartscope remainunresolved.
Group 12: Monitoring Parameters — PDF page 154
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | maximum frequency set by 01-02 ) | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 12-31 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 3 | 12-32 | ASR Output | Display output value of speed controller (100% corresponds to the maximum frequency set by 01-02) | - | % | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 4 | 12-33 | PG Feedback | Display feedback’s speed value of speed controller (100% corresponds to the maximum frequency set by 01-02) | - | % | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 5 | 12-34 | PG Pulse Number | Display PG pulse number of speed controller | - | Pulse | X | O | X | O | O | X | X | Note4 |
| 6 | 12-35 | Zero-speed Servo Pulse Number | When SV position mode, display the position error pulse number of the zero- speed servo (the resolution is four times of pulse number of set values of 20-27) | - | Pulse | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 7 | 12-36 | PID Input | Display input error of the PID controller (PID target value - PID feedback) (100% corresponds to the maximum frequency set by 01-02 or 01-16) | - | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 12-37 | PID Output | Display output of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) | - | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 12-38 | PID Setting | Display the target value of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) | - | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 12-39 | PID Feedback | Display the feedback value of the PID controller (100% corresponds to the maximum frequency set by 01-02 or 01-16) | - | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 12-40 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 12 | 12-41 | Heatsink Temperature* | Display the heatsink temperature of IGBT temperature** | * | ℃ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 155
Manual reference: physical PDF page 155. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
12-42 RS-485 Error Code diagram. Eight displayed zero bits. Rightmost to leftmost labels: 1CRC Error,1Data length Error,1Data Function Error,1Parity Error,1Overrun Error,1Framing Error,1Time out Error,Reserved. No bit weight or numerical error code inferred beyond source order.
12-43 Inverter Status diagram. Eight displayed zero bits. Rightmost to leftmost labels:1Inverter ready,1During running,1During zero speed,1During speed agree,1During fault detection(minor fault),1During fault detection(major fault),then two leftmost positions groupedReserved. Source status graphic only,notactualfaultorwiringtopology.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. 12-42/43 status bit diagrams retained as native source cells plus bounded visual label mapping; not wiring.
Group 12: Monitoring Parameters — PDF page 155
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 12-42 | RS-485 Error Code | 0 0 0 0 0 0 0 0 1: CRC Error 1: Data length Error 1: Data Function Error 1: Parity Error 1: Overrun Error 1: Framing Error 1: Time out Error Reserved | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 12-43 | Inverter Status | 0 0 0 0 0 0 0 0 1: Inverter ready 1: During running 1: During zero speed 1: During speed agree 1: During fault detection (minor fault) 1: During fault detection (major fault) Reserved | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 12-44 | Pulse Input Frequency | Display the frequency value of pulse input | - | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 12-45 | Recent Fault Message | Display current fault message | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 12-46 | Previous Fault Message | Display previous fault message | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 12-47 | Previous Two Fault Messages | Display previous two fault messages | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 12-48 | Previous Three Fault Messages | Display previous three fault messages | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 12-49 | Previous Four Fault Messages | Display previous four fault messages | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 12-50 | DIO Status of Current Fault | Display the DI/DO status of current fault Description is similar to 12-05 | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 12-51 | Inverter Status of Current Fault | Display the inverter status of current fault Description is similar to 12-43 | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 12-52 | Trip Time 1 of Current Fault | Display the operation time of current fault, 12-53 is the days, while 12-52 is the remaining hours. | - | Hr | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 12-53 | Trip Time 2 of Current Fault | Display the operation time of current fault, 12-53 is the days, while 12-52 is the remaining hours. | - | day | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 12-54 | Frequency Command of Previous Fault | Display frequency command of previous fault | - | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 12-55 | Output Frequency of Previous Fault | Display output frequency of previous fault | - | Hz | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 12-56 | Output Current of Previous Fault | Display output current of previous fault | - | A | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 12-57 | Output Voltage of Previous Fault | Display output voltage of previous fault | - | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 12-58 | DC Voltage of Previous Fault | Display DC voltage of previous fault | - | V | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 156
Manual reference: physical PDF page 156. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
*: Refer to the following attachment 1 ** A510s 200V 50HP (and the above) and 400V 100HP (and the above) don’t support heatsink temperature display function.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Heatsink display exclusion footnote completes12-41 on154.12-74/75/83/84 absent, not invented.
Group 12: Monitoring Parameters — PDF page 156
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 12-59 | DIO Status of Previous Fault | Display DI/DO status of previous fault Description is similar to 12-05 | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 12-60 | Inverter Status of Previous Fault | Display inverter status of previous fault Description is similar to 12-43 | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 12-61 | Trip Time 1 of Last Fault | Display the operation time of last time’s fault, 12-62 is the days, while 12-61 is the remaining hours. | - | Hr | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 12-62 | Trip Time 2 of Last Fault | Display the operation time of last time’s fault, 12-62 is the days, while 12-61 is the remaining hours. | - | day | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 12-63 | Recent Warning Messages | Display the recent warning messages | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 12-64 | Previous Warning Message | Display the previous warning message | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 12-65 | Motor Start Angle | 0~360 | - | - | X | X | X | X | O | X | X | ⟦blank source cell⟧ |
| 8 | 12-66 | Encoder Angle | 0~360 | - | - | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 9 | 12-67 | Cumulative Energy (KWHr) | 0.0 ~ 999.9 | ⟦blank source cell⟧ | kWHr | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 12-68 | Cumulative Energy (MWHr) | 0 ~ 60000 | ⟦blank source cell⟧ | MWHr | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 12-69 ~ 12-71 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 12 | 12-72 | RTC Date | 12.01.01 ~ 99.12.31 | 12.01.01 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 12-73 | RTC Time | 00:00 ~ 23:59 | 00:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 12-76 | No-Load Voltage Output | 0.0~600.0 | - | V | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 15 | 12-77 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 16 | 12-78 | Z-Phase Bias Value | -9999~9999 | - | Pulse | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 17 | 12-79 | Pulse Input Percentage | 0.0~100.0 | - | % | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 12-80 | AI1 Frequency Command | 0.0~599.0 | 0 | Hz | O | O | O | O | O | O | O | Note2 |
| 19 | 12-81 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 20 | 12-82 | Motor Load | 0~200.0 | - | % | O | O | O | O | O | O | O | Note4 |
| 21 | 12-85 | AI3 Input | Display the current Al3 input (-10V corresponds to -100%, 10V corresponds to 100%) | - | % | O | O | O | O | O | O | O | *10 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 157
Manual reference: physical PDF page 157. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 13: Maintenance Parameters — PDF page 157
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 13-00 | Inverter Capacity Selection | ---- | - | - | O | O | O | O | O | O | O | *4 |
| 2 | 13-01 | Software Version | 0.00-9.99 | - | - | O | O | O | O | O | O | O | *4 |
| 3 | 13-02 | Clear Cumulative Operation Hours | 0: Disable to Clear Cumulative Operation Hours 1: Clear Cumulative Operation Hours | 0 | - | O | O | O | O | O | O | O | *1 |
| 4 | 13-03 | Cumulative Operation Hours 1 | 0~23 | - | hr | O | O | O | O | O | O | O | *4 |
| 5 | 13-04 | Cumulative Operation Hours 2 | 0~65534 (Note4) | - | day | O | O | O | O | O | O | O | *4 |
| 6 | 13-05 | Selection of Cumulative Operation Time | 0: Cumulative time in power on 1: Cumulative time in operation | 0 | - | O | O | O | O | O | O | O | *1 |
| 7 | 13-06 | Parameters Locked | 0: Parameters are read-only except 13-06 and main frequency 1 : User defined parameters 2: All Parameters are Writable | 2 | - | O | O | O | O | O | O | O | *1 |
| 8 | 13-07 | Parameter Password Function | 00000~65534 | 00000 | - | O | O | O | O | O | O | O | Note2 |
| 9 | 13-08 | Restore Factory Setting | 0 : No initialization 2 : 2 wire initialization (60Hz)(220/440V/690V) 3 : 3 wire initialization (60Hz)(220/440V/690V) 4 : 2 wire initialization (50Hz)(230/415V) 5 : 3 wire initialization (50Hz)(230/415V) 6 : 2 wire initialization (50Hz)(200/380V/575V) 7 : 3 wire initialization (50HZ)(200/380V/575V) 8 : PLC initialization 9: 2 wire Initialization (60Hz)(230/460V) 10: 3 wire Initialization (60Hz)(230/460V) 11: 2 wire Initialization (60Hz)(230/400V) 12: 3 wire Initialization (60Hz)(230/400V) | - | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 158
Manual reference: physical PDF page 158. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top13–16 options continue13-08 from157.
Group 13: Maintenance Parameters — PDF page 158
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13: 2 wire Initialization (50Hz)(230/400V) 14: 3 wire Initialization (50Hz)(230/400V) 15: 2 wire Initialization (50Hz)(220/380V) (Note4) 16: 3 wire Initialization (50Hz)(220/380V) (Note4) | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 13-09 | Fault History Clearance Function | 0: No Clearing Fault History 1: Clear Fault History | 0 | - | O | O | O | O | O | O | O | *1 |
| 3 | 13-10 | Parameter Password Function 2 | 0 ~ 9999 | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 13-11 | C/B CPLD Ver. | 0.00~9.99 | - | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 13-12 | PG Card Id | 0~255 | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *5 |
| 6 | 13-13 | PG Card Ver. | 0.00~9.99 | - | ⟦blank source cell⟧ | O | O | O | O | O | O | O | *5 |
| 7 | 13-14 | Fault Storage Selections | 0: Fault Messages of Auto Restart are not saved. 1: Fault Messages of Auto Restart are saved. | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 13-15 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 9 | 13-21 | Last time Fault History | Exhibit Last time Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 10 | 13-22 | Previous two Fault History | Exhibit Previous two Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 11 | 13-23 | Previous three Fault History | Exhibit Previous three Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 12 | 13-24 | Previous four Fault History | Exhibit Previous four Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 13 | 13-25 | Previous five Fault History | Exhibit Previous five Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 14 | 13-26 | Previous six Fault History | Exhibit Previous six Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 15 | 13-27 | Previous seven Fault History | Exhibit Previous seven Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 16 | 13-28 | Previous eight Fault History | Exhibit Previous eight Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 17 | 13-29 | Previous nine Fault History | Exhibit Previous nine Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 18 | 13-30 | Previous ten Fault History | Exhibit Previous ten Fault History | - | - | O | O | O | O | O | O | O | Note1 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 159
Manual reference: physical PDF page 159. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Main frequency setting is 12-16 in LCD. It’s equal to Frequency Setting of Speed-Stage 0 (05-01)
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 13: Maintenance Parameters — PDF page 159
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 13-31 | Previous eleven Fault History | Exhibit Previous eleven Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 2 | 13-32 | Previous twelve Fault History | Exhibit Previous twelve Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 3 | 13-33 | Previous thirteen Fault History | Exhibit Previous thirteen Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 4 | 13-34 | Previous fourteen Fault History | Exhibit Previous fourteen Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 5 | 13-35 | Previous fifteen Fault History | Exhibit Previous fifteen Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 6 | 13-36 | Previous sixteen Fault History | Exhibit Previous sixteen Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 7 | 13-37 | Previous seventeen Fault History | Exhibit Previous seventeen Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 8 | 13-38 | Previous eighteen Fault History | Exhibit Previous eighteen Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 9 | 13-39 | Previous nineteen Fault History | Exhibit Previous nineteen Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 10 | 13-40 | Previous twenty Fault History | Exhibit Previous twenty Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 11 | 13-41 | Previous twenty one Fault History | Exhibit Previous twenty one Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 12 | 13-42 | Previous twenty two Fault History | Exhibit Previous twenty two Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 13 | 13-43 | Previous twenty three Fault History | Exhibit Previous twenty three Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 14 | 13-44 | Previous twenty four Fault History | Exhibit Previous twenty four Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 15 | 13-45 | Previous twenty five Fault History | Exhibit Previous twenty five Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 16 | 13-46 | Previous twenty six Fault History | Exhibit Previous twenty six Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 17 | 13-47 | Previous twenty seven Fault History | Exhibit Previous twenty seven Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 18 | 13-48 | Previous twenty eight Fault History | Exhibit Previous twenty eight Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 19 | 13-49 | Previous twenty nine Fault History | Exhibit Previous twenty nine Fault History | - | - | O | O | O | O | O | O | O | Note1 |
| 20 | 13-50 | Previous thirty Fault History | Exhibit Previous thirty Fault History | - | - | O | O | O | O | O | O | O | Note1 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 160
Manual reference: physical PDF page 160. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 14: PLC Setting Parameters — PDF page 160
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 14-00 | T1 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 2 | 14-01 | T1 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 3 | 14-02 | T2 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 4 | 14-03 | T2 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 5 | 14-04 | T3 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 6 | 14-05 | T3 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 7 | 14-06 | T4 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 8 | 14-07 | T4 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 9 | 14-08 | T5 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 10 | 14-09 | T5 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 11 | 14-10 | T6 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 12 | 14-11 | T6 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 13 | 14-12 | T7 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 14 | 14-13 | T7 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 15 | 14-14 | T8 Set Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 16 | 14-15 | T8 Set Value 2 (Mode 7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | Note6 |
| 17 | 14-16 | C1 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 18 | 14-17 | C2 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 19 | 14-18 | C3 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 20 | 14-19 | C4 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 21 | 14-20 | C5 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 22 | 14-21 | C6 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 23 | 14-22 | C7 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 24 | 14-23 | C8 Set Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 25 | 14-24 | AS1 Set Value 1 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 26 | 14-25 | AS1 Set Value 2 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 27 | 14-26 | AS1 Set Value 3 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 28 | 14-27 | AS2 Set Value 1 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 29 | 14-28 | AS2 Set Value 2 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 30 | 14-29 | AS2 Set Value 3 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 31 | 14-30 | AS3 Set Value 1 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 32 | 14-31 | AS3 Set Value 2 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 33 | 14-32 | AS3 Set Value 3 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 34 | 14-33 | AS4 Set Value 1 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 35 | 14-34 | AS4 Set Value 2 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
| 36 | 14-35 | AS4 Set Value 3 | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | Note6 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 161
Manual reference: physical PDF page 161. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 14: PLC Setting Parameters — PDF page 161
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 14-36 | MD1 Set Value 1 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 2 | 14-37 | MD1 Set Value 2 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 3 | 14-38 | MD1 Set Value 3 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 4 | 14-39 | MD2 Set Value 1 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 5 | 14-40 | MD2 Set Value 2 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 6 | 14-41 | MD2 Set Value 3 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 7 | 14-42 | MD3 Set Value 1 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 8 | 14-43 | MD3 Set Value 2 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 9 | 14-44 | MD3 Set Value 3 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 10 | 14-45 | MD4 Set Value 1 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 11 | 14-46 | MD4 Set Value 2 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
| 12 | 14-47 | MD4 Set Value 3 | 0~65534 (Note4) | 1 | - | O | O | O | O | O | O | O | Note6 |
Group 15: PLC Monitoring Parameters — PDF page 161
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 15-00 | T1 Current Value1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 15-01 | T1 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 15-02 | T2 Current Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 15-03 | T2 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 15-04 | T3 Current Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 15-05 | T3 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 15-06 | T4 Current Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 15-07 | T4 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 15-08 | T5 Current Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 15-09 | T5 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 15-10 | T6 Current Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 15-11 | T6 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 15-12 | T7 Current Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 15-13 | T7 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 15-14 | T8 Current Value 1 | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 16 | 15-15 | T8 Current Value 2 (Mode7) | 0~9999 | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 17 | 15-16 | C1 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 18 | 15-17 | C2 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 162
Manual reference: physical PDF page 162. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 15: PLC Monitoring Parameters — PDF page 162
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 15-18 | C3 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 15-19 | C4 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 3 | 15-20 | C5 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 4 | 15-21 | C6 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 15-22 | C7 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 15-23 | C8 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 7 | 15-24 | AS1 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 8 | 15-25 | AS2 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 9 | 15-26 | AS3 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 10 | 15-27 | AS4 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 11 | 15-28 | MD1 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 12 | 15-29 | MD2 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 13 | 15-30 | MD3 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 14 | 15-31 | MD4 Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 15 | 15-32 | TD Current Value | 0~65534 (Note4) | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Group 16: LCD Function Parameters — PDF page 162
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 16-00 | Main Screen Monitoring | 5~82 (Note4) when using LCD to operate, the monitored item displays in the first line. (default is frequency command) | 16 | - | O | O | O | O | O | O | O | *1 |
| 2 | 16-01 | Sub-Screen Monitoring 1 | 5~82 (Note4) when using LCD to operate, the monitored item displays in the second line. (default is output frequency) | 17 | - | O | O | O | O | O | O | O | *1 |
| 3 | 16-02 | Sub-Screen Monitoring 2 | 5~82 (Note4) when using LCD to operate, the monitored item displays in the third line. (default is output current) | 18 | - | O | O | O | O | O | O | O | *1 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 163
Manual reference: physical PDF page 163. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Display formatting range boundaries retained exactly; unlisted10000/20000/30000 not assigned behavior.
Group 16: LCD Function Parameters — PDF page 163
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 16-03 | Display Unit | 0~39999 Determine the display way and unit of frequency command 0: Frequency display unit is 0.01Hz 1: Frequency display unit is 0.01% 2: Frequency display unit is rpm. 3~39: Reserved 40~9999: Users specify the format, Input 0XXXX represents the display of XXXX at 100%. 10001~19999: Users specify the format; Input 1XXXX represents the display of XXX.X at 100%. 20001~29999: Users specify the format, Input 2XXXX represents the display of XX.XX at 100%. 30001~39999: Users specify the format, Input 3XXXX represents the display of X.XXX at 100%. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 164
Manual reference: physical PDF page 164. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 16: LCD Function Parameters — PDF page 164
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 16-04 | Engineering Unit | 0: without using engineering unit 1: FPM 2: CFM 3: PSI 4: GPH 5: GPM 6: IN 7: FT 8: /s 9: /m 10: /h 11: °F 12: inW 13: HP 14: m/s 15: MPM 16: CMM 17: W 18: KW 19: m 20: °C 21: RPM 22: Bar 23: Pa 24: KPa 25: PRS 26: SPM | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 2 | 16-05 | LCD Backlight | 0~7 | 5 | - | O | O | O | O | O | O | O | *1 |
| 3 | 16-06 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 4 | 16-07 | Copy Function Selection | 0: Do not copy parameters 1: Read inverter parameters and save to the operator. 2: Write the operator parameters to inverter. 3: Compare parameters of inverter and operator. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 5 | 16-08 | Selection of Allowing Reading | 0: Do not allow to read inverter parameters and save to the operator. | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
| 6 | 16-08 | Selection of Allowing Reading | 1: Allow to read inverter | 0 | - | O | O | O | O | O | O | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 165
Manual reference: physical PDF page 165. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Topparametersandsavetotheoperator continues16-08 from164. Start/stopweekdaysetting cells sharefullMon–Sun list.
Group 16: LCD Function Parameters — PDF page 165
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | parameters and save to the operator. | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 16-09 | Selection of Operator Removed (LCD) | 0: Keep operating when LCD operator is removed. 1: Display fault when LCD operator is removed | 0 | - | O | O | O | O | O | O | O | *1 |
| 3 | 16-10 | RTC Time Display Setting | 0: Hide 1: Display | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 4 | 16-11 | RTC Date Setting | 12.01.01 ~ 99.12.31 | 12.01.0 1 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 5 | 16-12 | RTC Time Setting | 00:00 ~ 23:59 | 00:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 6 | 16-13 | RTC Timer Function | 0: Disable 1: Enable 2: Set by DI | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 7 | 16-14 | P1 Start Time | 00:00 ~ 23:59 | 08:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 8 | 16-15 | P1 Stop Time | 00:00 ~ 23:59 | 18:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 9 | 16-16 | P1 Start Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 1 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 10 | 16-17 | P1 Stop Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 5 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 11 | 16-18 | P2 Start Time | 00:00 ~ 23:59 | 08:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 12 | 16-19 | P2 Stop Time | 00:00 ~ 23:59 | 18:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 13 | 16-20 | P2 Start Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 1 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 14 | 16-21 | P2 Stop Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 5 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 15 | 16-22 | P3 Start Time | 00:00 ~ 23:59 | 08:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 16 | 16-23 | P3 Stop Time | 00:00 ~ 23:59 | 18:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 17 | 16-24 | P3 Start Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 1 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 18 | 16-25 | P3 Stop Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 5 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 19 | 16-26 | P4 Start Time | 00:00 ~ 23:59 | 08:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 20 | 16-27 | P4 Stop Time | 00:00 ~ 23:59 | 18:00 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 166
Manual reference: physical PDF page 166. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. 16-32/33/34/35 share full0–31 timer option catalogue; code/default cells independent ofadjacentlist slice.
Group 16: LCD Function Parameters — PDF page 166
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 16-28 | P4 Start Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 1 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 2 | 16-29 | P4 Stop Date | 1:Mon 2:Tue 3:Wed 4:Thu 5:Fri 6:Sat 7:Sun | 5 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 3 | 16-30 | Selection of RTC Offset | 0: Disable 1: Enable 2: Set by DI | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 4 | 16-31 | RTC Offset Time Setting | 00:00 ~ 23:59 | 00:00 | - | O | O | O | O | O | O | O | Note8 |
| 5 | 16-32 | Source of Timer 1 | 0: None, 1:P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 15:P1+P2+P3+P4, 16:Off, 17:Off+P1 18:Off+P2, 19:Off+P1+P2 20:Off+P3, 21:Off+P1+P3 22:Off+P2+P3 23:Off+P1+P2+P3 24:Off+P4 25:Off+P1+P4 26:Off+P2+P4 27:Off+P1+P2+P4 28:Off+P3+P4 29:Off+P1+P3+P4 30:Off+P2+P3+P4 31:Off+P1+P2+P3+P4 | 1 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 6 | 16-33 | Source of Timer 2 | 0: None, 1:P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 15:P1+P2+P3+P4, 16:Off, 17:Off+P1 18:Off+P2, 19:Off+P1+P2 20:Off+P3, 21:Off+P1+P3 22:Off+P2+P3 23:Off+P1+P2+P3 24:Off+P4 25:Off+P1+P4 26:Off+P2+P4 27:Off+P1+P2+P4 28:Off+P3+P4 29:Off+P1+P3+P4 30:Off+P2+P3+P4 31:Off+P1+P2+P3+P4 | 2 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 7 | 16-34 | Source of Timer 3 | 0: None, 1:P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 15:P1+P2+P3+P4, 16:Off, 17:Off+P1 18:Off+P2, 19:Off+P1+P2 20:Off+P3, 21:Off+P1+P3 22:Off+P2+P3 23:Off+P1+P2+P3 24:Off+P4 25:Off+P1+P4 26:Off+P2+P4 27:Off+P1+P2+P4 28:Off+P3+P4 29:Off+P1+P3+P4 30:Off+P2+P3+P4 31:Off+P1+P2+P3+P4 | 4 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 8 | 16-35 | Source of Timer 4 | 0: None, 1:P1, 2:P2, 3:P1+P2 4:P3, 5:P1+P3, 6:P2+P3, 7:P1+P2+P3, 8:P4, 9:P1+P4, 10:P2+P4, 11:P1+P2+P4 12:P3+P4 13:P1+P3+P4, 14:P2+P3+P4 15:P1+P2+P3+P4, 16:Off, 17:Off+P1 18:Off+P2, 19:Off+P1+P2 20:Off+P3, 21:Off+P1+P3 22:Off+P2+P3 23:Off+P1+P2+P3 24:Off+P4 25:Off+P1+P4 26:Off+P2+P4 27:Off+P1+P2+P4 28:Off+P3+P4 29:Off+P1+P3+P4 30:Off+P2+P3+P4 31:Off+P1+P2+P3+P4 | 8 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
| 9 | 16-36 | Selection of RTC Speed | 0: Off 1: By Timer 1 2: By Timer 2 3: By Timer 3 4: By Timer 4 5: By Timer 1+2 | 0 | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 167
Manual reference: physical PDF page 167. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 16: LCD Function Parameters — PDF page 167
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 16-37 | Selection of RTC Rotation Direction | xxx0b: RTC Run1 Forward Rotation xxx1b: RTC Run1 Reverse Rotation xx0xb: RTC Run2 Forward Rotation xx1xb: RTC Run2 Reverse Rotation x0xxb: RTC Run3 Forward Rotation x1xxb: RTC Run3 Reverse Rotation 0xxxb: RTC Run4 Forward Rotation 1xxxb: RTC Run4 Reverse Rotation | 0000b | ⟦blank source cell⟧ | O | O | O | O | O | O | O | Note8 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 168
Manual reference: physical PDF page 168. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 17: Automatic Tuning Parameters — PDF page 168
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 17-00 | Mode Selection of Automatic Tuning* | 0: Rotation Auto-tuning 1: Static Auto-tuning 2: Stator Resistance Measurement 3: Reserved 4: Loop Tuning 5: Rotation Auto-tuning Combination (item: 4+2+0) 6: Static Auto-tuning Combination (item: 4+2+1) | VF:2 VF+PG :2 SLV:6 SV:6 SLV2:6 | - | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 2 | 17-01 | Motor Rated Output Power | 0.00~600.00 | KVA | KW | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 3 | 17-02 | Motor Rated Current | 0.1~1200.0 | KVA | A | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 4 | 17-03 | Motor Rated Voltage | 200V: 50.0~240.0 400V: 100.0~480.0 575V:150.0~670.0 690V: 180.0~804.0 | - | V | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 5 | 17-04 | Motor Rated Frequency | 4.8~599.0 | 50.0/ 60.0 | Hz | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 6 | 17-05 | Motor Rated Speed | 0~24000 | KVA | rpm | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 7 | 17-06 | Pole Number of Motor | 2~16 (Even) | 4 | Pole | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 8 | 17-07 | PG Pulse Number | 0~60000 | 1024 | ppr | X | O | X | O | X | X | X | ⟦blank source cell⟧ |
| 9 | 17-08 | Motor no-load Voltage | 200V: 50~240 400V: 100~480 575V: 420~600 690V: 504~720 | - | V | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 10 | 17-09 | Motor Excitation Current | 0.01~600.00 | - | A | X | X | O | O | X | X | X | ■1 |
| 11 | 17-10 | Automatic Tuning Start | 0: Disable 1: Enable | 0 | - | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
| 12 | 17-11 | Error History of Automatic Tuning | 0: No error 1: Motor data error 2: Stator resistance tuning error 3: Leakage induction tuning error 4: Rotor resistance tuning error 5: Mutual induction tuning error 6: Encoder error 7: DT Error 8: Motor’s acceleration error 9: Warning | 0 | - | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 169
Manual reference: physical PDF page 169. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
KVA: The default value of this parameter will be changed by different capacities of inverter. : The default value is 1 in VF/ VF+PG mode while the default value is 0 in SLV/ SV/ SLV2 mode. : It is suggested that HD/ ND mode (00-27) and application presets (00-32) be selected first before motor performs auto-tuning. Note: The value of mode selection of automatic tuning is 6 (Static Auto-tuning Combination). When do auto-tuning with no-load motor, it suggest select 17-00=5 (Rotation Auto-tuning Combination) ■1: It can be set when 17-00=1, 2, 6.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Auto-tuning defaults table168 conflict withstarfootnote here; retain both. KVAchangeswithcapacity.17-09 square1qualification explicitly17-00=1,2,6.
Group 17: Automatic Tuning Parameters — PDF page 169
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 17-12 | Proportion of Motor Leakage Inductance | 0.1~15.0 | 3.4 | % | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 2 | 17-13 | Motor Slip Frequency | 0.10~20.00 | 1.00 | Hz | X | X | O | O | X | X | X | ⟦blank source cell⟧ |
| 3 | 17-14 | Selection of Rotation Auto-tuning | 0:VF Rotation Auto-tuning 1: Vector Rotation Auto-tuning | 0 | - | O | O | O | O | X | X | O | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 170
Manual reference: physical PDF page 170. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
*: Refer to the following attachment 1.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. 18-00 default cell distinguishesVF andSLVasterisk; preserveattachment1reference.
Group 18: Slip Compensation Parameters — PDF page 170
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 18-00 | Slip Compensation Gain at Low Speed. | 0.00~2.50 | VF:0.0 0 | - | O | X | O | O | X | X | O | *1 |
| 2 | 18-00 | Slip Compensation Gain at Low Speed. | 0.00~2.50 | SLV* | - | O | X | O | O | X | X | O | *1 |
| 3 | 18-01 | Slip Compensation Gain at High Speed. | -1.00~1.00 | 0.0 | - | O | X | O | X | X | X | X | *1 |
| 4 | 18-02 | Slip Compensation Limit | 0~250 | 200 | % | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 5 | 18-03 | Slip Compensation Filter Time | 0.0~10.0 | 1.0 | Sec | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 6 | 18-04 | Regenerative Slip Compensation Selection | 0: Disable 1: Enable | 0 | - | O | X | X | X | X | X | X | ⟦blank source cell⟧ |
| 7 | 18-05 | FOC Delay Time | 1~1000 | 100 | ms | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 8 | 18-06 | FOC Gain | 0.00~2.00 | 0.1 | - | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
Group 19: Wobble Frequency Parameters — PDF page 170
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 19-00 | Center Frequency of Wobble Frequency | 5.00~100.00 | 20.00 | % | O | O | X | X | X | X | O | *1 |
| 2 | 19-01 | Amplitude of Wobble Frequency | 0.1~20.0 | 10.0 | % | O | O | X | X | X | X | O | *1 |
| 3 | 19-02 | Jump Frequency of Wobble Frequency | 0.0~50.0 | 0.0 | % | O | O | X | X | X | X | O | *1 |
| 4 | 19-03 | Jump Time of Wobble Frequency | 0~50 | 0 | ms | O | O | X | X | X | X | O | *1 |
| 5 | 19-04 | Wobble Frequency Cycle | 0.0~1000.0 | 10.0 | Sec | O | O | X | X | X | X | O | *1 |
| 6 | 19-05 | Wobble Frequency Ratio | 0.1~10.0 | 1.0 | ⟦blank source cell⟧ | O | O | X | X | X | X | O | *1 |
| 7 | 19-06 | Upper Offset Amplitude of Wobble Frequency | 0.0~20.0 | 0.0 | % | O | O | X | X | X | X | O | *1 |
| 8 | 19-07 | Lower Offset Amplitude of Wobble Frequency | 0.0~20.0 | 0.0 | % | O | O | X | X | X | X | O | *1 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 171
Manual reference: physical PDF page 171. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 20: Speed Control Parameters — PDF page 171
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 20-00 | ASR Gain 1 | 0.00~250.00 | - | - | X | O | O | O | O | O | X | *1 |
| 2 | 20-01 | ASR Integral Time 1 | 0.001~10.000 | - | Sec | X | O | O | O | O | O | X | *1 |
| 3 | 20-02 | ASR Gain 2 | 0.00~250.00 | - | - | X | O | O | O | O | O | X | *1 |
| 4 | 20-03 | ASR Integral Time 2 | 0.001~10.000 | - | Sec | X | O | O | O | O | O | X | *1 |
| 5 | 20-04 | ASR Integral Time Limit | 0~300 | 200 | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 6 | 20-05 | ASR Positive Limit | 0.1 ~ 10.0 | 5.0 | % | X | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 7 | 20-06 | ASR Negative Limit | 0.1 ~ 10.0 | 1.0 | % | X | O | X | X | X | X | X | ⟦blank source cell⟧ |
| 8 | 20-07 | Selection of Acceleration and Deceleration of P/PI | 0: PI speed control will be enabled only in constant speed. For the speed acceleration and deceleration, only use P control. 1: Speed control is enabled either in acceleration or deceleration. | 0 | - | X | O | O | O | O | X | X | ⟦blank source cell⟧ |
| 9 | 20-08 | ASR Delay Time | 0.000~0.500 | 0.004 | Sec | O | X | O | O | O | O | X | Note5 |
| 10 | 20-09 | Speed Observer Proportional (P) Gain1 | 0.00~2.55 | 0.61 | - | X | X | O | X | X | X | X | *1 |
| 11 | 20-10 | Speed Observer Integral(I) Time 1 | 0.01~10.00 | 0.05 | Sec | X | X | O | X | X | X | X | *1 |
| 12 | 20-11 | Speed Observer Proportional (P) Gain2 | 0.00~2.55 | 0.61 | - | X | X | O | X | X | X | X | *1 |
| 13 | 20-12 | Speed Observer Integral(I) Time 2 | 0.01~10.00 | 0.06 | Sec | X | X | O | X | X | X | X | *1 |
| 14 | 20-13 | Low-pass Filter Time Constant of Speed Feedback 1 | 1~1000 | 4 | ms | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 15 | 20-14 | Low-pass Filter Time Constant of Speed Feedback 2 | 1~1000 | 30 | ms | X | X | O | X | X | X | X | ⟦blank source cell⟧ |
| 16 | 20-15 | ASR Gain Change Frequency 1 | 0.0~599.0 | 4.0 | Hz | X | O | O | O | O | X | O | ⟦blank source cell⟧ |
| 17 | 20-16 | ASR Gain Change Frequency 2 | 0.0~599.0 | 8.0 | Hz | X | X | O | O | O | X | O | ⟦blank source cell⟧ |
| 18 | 20-17 | Torque Compensation Gain at Low Speed | 0.00~2.50 | 1.00 | - | X | X | O | X | X | X | X | *1 |
| 19 | 20-18 | Torque Compensation Gain at High Speed | -10~10 | 0 | % | X | X | O | X | X | X | X | *1 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 172
Manual reference: physical PDF page 172. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 20: Speed Control Parameters — PDF page 172
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 20-19 | Over Speed (OS) Selection | 0: Deceleration to stop 1: Coast to stop 2: Continue to operate | 1 | ⟦blank source cell⟧ | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 2 | 20-20 | Over Speed (OS) Detection Level | 0~120 | 115 | % | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 3 | 20-21 | Over Speed (OS) Detection Time | 0.0~2.0 | 0.5 | Sec | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 4 | 20-22 | Speed Deviation (DEV) Selection | 0: Deceleration to Stop 1: Coast to Stop 2: Continue to Operate | 2 | ⟦blank source cell⟧ | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 5 | 20-23 | Speed Deviation (DEV) Detection Level | 0~50 | 10 | % | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 6 | 20-24 | Speed Deviation (DEV) Detection Time | 0.0~10.0 | 0.5 | Sec | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 7 | 20-25 | Selection of PG Open | 0: Deceleration to Stop 1: Coast to Stop 2: Continue to Operate | 1 | - | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 8 | 20-26 | Detection Time of PG Open | 0.0~10.0 | 2.0 | Sec | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 9 | 20-27 | PG Pulse Number | 0~9999 | 1024 | ppr | O | O | X | O | O | X | X | Note5 |
| 10 | 20-28 | Selection of PG Rotation Direction | 0: Forward as Counter -Clockwise Rotation 1: Forward as Clockwise Rotation | 0 | - | O | O | X | O | O | X | X | Note5 |
| 11 | 20-29 | PG Pulse Dividing Ratio | 001~132 | 1 | - | X | O | X | O | O | X | X | ⟦blank source cell⟧ |
| 12 | 20-30 | PG Gear Ratio 1 | 1~1000 | 1 | - | X | O | X | O | X | X | X | ⟦blank source cell⟧ |
| 13 | 20-31 | PG Gear Ratio 2 | 1~1000 | 1 | - | X | O | X | O | X | X | X | ⟦blank source cell⟧ |
| 14 | 20-32 | Selection of Specific Encoder | 0: None 1: Resolver | 0 | ⟦blank source cell⟧ | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 15 | 20-33 | Detection Level at Constant Speed | 0.1~5.0 | 1.0 | ⟦blank source cell⟧ | X | O | O | O | O | O | X | *1 |
| 16 | 20-34 | Compensation Gain of Derating | 0~25600 | 0 | ⟦blank source cell⟧ | X | X | O | O | O | X | X | *1 |
| 17 | 20-35 | Compensation Time of Derating | 0~30000 | 100 | ms | X | X | O | O | O | X | X | *1 |
| 18 | 20-36~ 20-42 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 19 | 20-43 | MPG Speed Magnification Calculation | 1~500 | 20 | ⟦blank source cell⟧ | O | O | X | O | X | X | X | Note5 |
| 20 | 20-44 | MPG Speed Command Limit | 0.1~30.0 | 6.0 | Hz | O | X | X | X | X | X | X | Note5 |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 173
Manual reference: physical PDF page 173. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 21: Torque And Position Control Parameters — PDF page 173
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 21-00 | Torque Control Selection | 0: Speed Control 1: Torque Control | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 2 | 21-01 | Filter Time of Torque Reference | 0~1000 | 0 | ms | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 3 | 21-02 | Speed Limit Selection | 0: According to AI Input 1: According to the Set Value of 21-03 2: According to communication position input (2502H) | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 4 | 21-03 | Speed Limit Value | -120~120 | 0 | % | X | X | X | O | O | X | X | *1 |
| 5 | 21-04 | Speed Limit Bias | 0~120 | 10 | % | X | X | X | O | O | X | X | *1 |
| 6 | 21-05 | Positive Torque Limit | 0~300 | * | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 7 | 21-06 | Negative Torque Limit | 0~300 | * | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 8 | 21-07 | Forward Regenerative Torque Limit | 0~300 | * | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 9 | 21-08 | Reversal Regenerative Torque Limit | 0~300 | * | % | X | X | O | O | O | O | X | ⟦blank source cell⟧ |
| 10 | 21-09 | Maximum Frequency of Position Control | 0.1~100.0 | 20.0 | Hz | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 11 | 21-10 | The Command of Rotation Cycle Number of Section 0 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 12 | 21-11 | The Command of the Pulse Number of Section 0 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 13 | 21-12 | The Command of Rotation Cycle Number of Section 1 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 14 | 21-13 | The Command of the Pulse Number of Section 1 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 15 | 21-14 | The Command of Rotation Cycle Number of Section 2 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 16 | 21-15 | The Command of the Pulse Number of Section 2 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 17 | 21-16 | The Command of Rotation Cycle Number of Section | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 174
Manual reference: physical PDF page 174. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top3 continues21-16 namefrom173;21-26/27and21-28/29nameshavepulsebeforecycle unlikeadjacentpairs,retainliteral.
Group 21: Torque And Position Control Parameters — PDF page 174
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 21-17 | The Command of the Pulse Number of Section 3 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 3 | 21-18 | The Command of Rotation Cycle Number of Section 4 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 4 | 21-19 | The Command of the Pulse Number of Section 4 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 5 | 21-20 | The Command of Rotation Cycle Number of Section 5 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 6 | 21-21 | The Command of the Pulse Number of Section 5 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 7 | 21-22 | The Command of Rotation Cycle Number of Section 6 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 8 | 21-23 | The Command of the Pulse Number of Section 6 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 9 | 21-24 | The Command of Rotation Cycle Number of Section 7 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 10 | 21-25 | The Command of the Pulse Number of Section 7 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 11 | 21-26 | The Command of the Pulse Number of Section 8 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 12 | 21-27 | The Command of Rotation Cycle Number of Section 8 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 13 | 21-28 | The Command of the Pulse Number of Section 9 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 14 | 21-29 | The Command of Rotation Cycle Number of Section 9 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 15 | 21-30 | The Command of Rotation Cycle Number of Section 10 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 16 | 21-31 | The Command of the Pulse Number | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 175
Manual reference: physical PDF page 175. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Refer to the following attachment 1.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. TopofSection10 continues21-31 from174.
Group 21: Torque And Position Control Parameters — PDF page 175
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | of Section 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 21-32 | The Command of Rotation Cycle Number of Section 11 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 3 | 21-33 | The Command of the Pulse Number of Section 11 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 4 | 21-34 | The Command of Rotation Cycle Number of Section 12 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 5 | 21-35 | The Command of the Pulse Number of Section 12 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 6 | 21-36 | The Command of Rotation Cycle Number of Section 13 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 7 | 21-37 | The Command of the Pulse Number of Section 13 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 8 | 21-38 | The Command of Rotation Cycle Number of Section 14 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 9 | 21-39 | The Command of the Pulse Number of Section 14 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 10 | 21-40 | The Command of Rotation Cycle Number of Section 15 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 11 | 21-41 | The Command of the Pulse Number of Section 15 | -9999 ~ 9999 | 0 | - | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 12 | 21-42 | Pos. Mode Selection | 0: Switch to position mode when output frequency < 01-08. 1: Z Phase Locked Function | 0 | ⟦blank source cell⟧ | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
| 13 | 21-43 | Offset Angle | 0 ~9999 | 0 | Pulse | X | X | X | O | O | X | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 176
Manual reference: physical PDF page 176. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 22: PM Motor Parameters — PDF page 176
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 22-00 | PM Motor Rated Power | 0.00~600.00 | KVA | kW | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 2 | 22-01 | PM Motor Rated Voltage | 200V: 50.0~240.0 400V: 100.0~480.0 | 220.0 440.0 | V | X | X | X | X | O | O | X | Note7 |
| 3 | 22-02 | PM Motor Rated Current | 25%~200% inverter’s rated current | KVA | A | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 4 | 22-03 | PM Motor ‘s Pole Number | 2~96 | 6 | poles | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 5 | 22-04 | PM Motor’s Rotation Speed | 6~60000 | 1500 | rpm | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 6 | 22-05 | PM Motor’s Maximum Rotation Speed | 6~60000 | 1500 | rpm | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 7 | 22-06 | PM Motor Rated Frequency | 4.8~599.0 | 75.0 | Hz | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 8 | 22-07 | PM Type Selection | 0:SPM 1:IPM | 0 | ⟦blank source cell⟧ | X | X | X | X | X | O | X | Note7 |
| 9 | 22-08 | PM Encoder Type | 0: TAMAGAWA Non Wire-Saving Encoder 1: TAMAGAWA Wire-Saving Encoder 2: SUMTAK Wire-Saving Encoder 3: General Incremental Encoder 4: Sine Wave | 0 | ⟦blank source cell⟧ | X | X | X | X | O | X | X | ⟦blank source cell⟧ |
| 10 | 22-09 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 11 | 22-10 | PM SLV Start Current | 20% ~ 200% Motor Rated Current | 80 | % | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 12 | 22-11 | I/F Mode Start Frequency Switching Point | 10 ~ 100 (Note 7) | 10 | % | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 13 | 22-12 22-13 | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) | Reserved (Note4) |
| 14 | 22-14 | Armature Resistance of PM Motor | 0.001 ~ 30.000 | 1.000 | Ω | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 15 | 22-15 | D-axis Inductance of PM Motor | 0.01 ~ 300.00 | 10.00 | mH | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 16 | 22-16 | Q-axis Inductance of PM Motor | 0.01 ~ 300.00 | 10.00 | mH | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 17 | 22-17 | PM No-Load Voltage | 200V: 0~250 400V: 0~500 | 150 300 | V | X | X | X | X | O | O | X | Note7 |
| 18 | 22-18 | Flux-Weakening Limit | 0~120 | 90 | % | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 177
Manual reference: physical PDF page 177. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 22: PM Motor Parameters — PDF page 177
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 22-19 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 2 | 22-20 | Offset Angle of the Magnetic Pole and PG Origin | 0~360 | 0 | deg | X | X | X | X | O | X | X | *4 |
| 3 | 22-21 | PM Motor Tuning | 0: PM Motor Tuning is not Active. 1: Parameter Auto-tuning (for PMSLV Tuning) 2: Magnetic Pole Alignment and Loop Adjustment (for PMSV Tuning) 3: Rotation Auto-tuning | 0 | - | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 4 | 22-22 | Fault History of PM Motor Tuning | 0. No Error 1. Static Magnetic Alignment Fault 2. Without PG Option Card 3. Rotation Pole Alignment is Forced to Stop 4. Error of Encoder Feedback Direction 5. Loop Adjustment is Time out 6. Encoder Error 7. Other Errors of Motor Tuning 8. Current Abnormity Occurs when Aligning Rotation Magnetic Pole. 9. Current Abnormity Occurs while Loop Adjustment. 10.Reserved 11. Stator Resistance Measurement Timeout | 0 | - | X | X | X | X | O | O | X | *4 |
| 5 | 22-23 22-24 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 6 | 22-25 | Detection Mode Selection of Initial Magnetic Pole | 0: Upon the angle before stopping 1: Mode 1 2: Mode 2 3: Mode 3 | 2 (Note7) | - | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 7 | 22-26 | High speed control ratio enable (For PMSLV) | 0: Low Speed Open Loop Control 1: Low Speed High Frequency Estimate Control | 0 | - | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 178
Manual reference: physical PDF page 178. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends. Top2FullClosedLoopControl continues22-26 from177.22-37default0notlistedamongshownoptions;do notinvent0meaning.
Group 22: PM Motor Parameters — PDF page 178
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 2: Full Closed Loop Control | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | 22-27 | Voltage Command of Mode 2 | 5~120 (Note 7) (22-25=2 or 22-26=1 is enabled) | 50 | % | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 3 | 22-28 | Divider Ratio of Mode 2 | 0~8 (Note 7) (22-25=2 or 22-26=1 is enabled) | 2 | - | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 4 | 22-29 | Flux-weakening Voltage Command Restriction | 80~110 (Note 7) (related to parameter 22-18) | 100 | % | X | X | X | X | O | O | X | ⟦blank source cell⟧ |
| 5 | 22-30 | SPM Speed Estimation Gain (Note7) | 1~150 | 85 | % | X | X | X | X | X | O | X | Note4 |
| 6 | 22-31 | SPM Speed Estimation Filter Value (Note7) | 1~2000 | 60 | Hz | X | X | X | X | X | O | X | Note4 |
| 7 | 22-32 | MTPA Selection | 0: Disabled 1: Mode 1 | 0 | - | X | X | X | X | O | O | X | Note7 |
| 8 | 22-33 | MTPA Gain | 0~400% | 200 | % | X | X | X | X | O | O | X | Note7 |
| 9 | 22-34 | IPM Estimator Gain | 1~300.0 | 180 | - | X | X | X | X | X | O | X | Note7 |
| 10 | 22-35 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 11 | 22-36 | PM Motor Type Selection | 0: Normal PM motor 1: DVEN Motor | 0 | - | X | X | X | X | X | O | X | Note 8 |
| 12 | 22-37 | PM Motor Horse Power & RPM | 1: 0.75KW 1800RPM 4: 1.5KW 1800RPM 7: 2.2KW 1800RPM 10: 3.7KW 1800RPM 13: 5.5KW 1800RPM 16: 7.5KW 1800RPM 19: 11KW 1800RPM 22: 15KW 1800RPM 25: 18.5KW 1800RPM 28: 22KW 1800RPM | 0 | - | X | X | X | X | X | O | X | Note 8 |
| 13 | 22-38 | Open and closed loop switching point frequency width (%) | 1.0~40.0 | 5.0 | % | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 14 | 22-39 | Preliminary DC injection time | 0~20.00 | 0.10 | Sec | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 15 | 22-40 | High frequency angle finding time | 0.01~1.00 | 0.01 | - | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
Manual — Parameter catalogue tables: monitoring, maintenance, PLC, LCD, auto-tuning, slip, speed, torque and PM motors — page 179
Manual reference: physical PDF page 179. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source parameter table. O,X,- and blanks retained literally; mode/voltage/HD/ND and software/attribute qualifiers must accompany each value. Shared merged-cell geometry retained; no inferred defaults or control applicability. Page108 provides independent attribute and software legends.
Group 22: PM Motor Parameters — PDF page 179
| Source row | Code | Parameter Name | Setting Range | Default | Unit | Control mode V/F | Control mode V/F+PG | Control mode SLV | Control mode SV | Control mode PMSV | Control mode PMSLV | Control mode SLV2 | Attribute |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 22-41 | PM stop method | 0: Decelerate or stop below 22-11 and brake directly 1: Decelerate or stop below 22-11 and open loop stop | 0 | - | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 2 | 22-42 | Fully closed loop control gain Ka | 64~8192 | 100 | - | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 3 | 22-43 | Fully closed loop control gain Kb | 64~8192 | 2000 | - | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 4 | 22-44 | Fully closed loop control gain speed low pass filter | 1~256 | 4 | - | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
| 5 | 22-45 | Fully closed loop control magnetic flux | 0.01~10.00 | 0.70 | - | X | X | X | X | X | O | X | ⟦blank source cell⟧ |
Manual — Attachment1: exact model rows, frames and carrier-frequency inequalities retained. 4215 and4215H are separate. Applies to capacity-dependent parameter references in earlier catalogue. — page 180
Manual reference: physical PDF page 180. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Attachment 1: Parameters’ default value and upper limit value are adjusted by different capacities of inverter.
Attachment1: exact model rows, frames and carrier-frequency inequalities retained. 4215 and4215H are separate. Applies to capacity-dependent parameter references in earlier catalogue.
Models / Frame / Max. frequency (Hz) in SLV when carrier frequency <= 8K 11-01 / Max. frequency (Hz) in SLV when carrier frequency > 8K 11-01 / Display parameter 12-41 (Inverter temperature) / The initial value of parameter 18-00 in SLV/ SV (Slip compensation at low speed) — PDF page 180
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Models | Frame | Max. frequency (Hz) in SLV when carrier frequency <= 8K 11-01 | Max. frequency (Hz) in SLV when carrier frequency > 8K 11-01 | Display parameter 12-41 (Inverter temperature) | The initial value of parameter 18-00 in SLV/ SV (Slip compensation at low speed) |
| 2 | 2001 | 1 | 150 | 150 | Yes | 1.00 |
| 3 | 2002 | 1 | 150 | 150 | Yes | 1.00 |
| 4 | 2003 | 2 | 150 | 150 | Yes | 1.00 |
| 5 | 2005 | 2 | 150 | 150 | Yes | 1.00 |
| 6 | 2008 | 2 | 150 | 150 | Yes | 1.00 |
| 7 | 2010 | 3 | 150 | 150 | Yes | 1.00 |
| 8 | 2015 | 4 | 110 | 110 | Yes | 1.00 |
| 9 | 2020 | 4 | 110 | 110 | Yes | 1.00 |
| 10 | 2025 | 4 | 110 | 110 | Yes | 1.00 |
| 11 | 2030 | 5 | 100 | 80 | Yes | 0.70 |
| 12 | 2040 | 5 | 100 | 80 | Yes | 0.70 |
| 13 | 2050 | 6 | 100 | 80 | No | 0.70 |
| 14 | 2060 | 6 | 100 | 80 | No | 0.70 |
| 15 | 2075 | 7 | 100 | 95 | No | 0.50 |
| 16 | 2100 | 7 | 100 | 95 | No | 0.50 |
| 17 | 2125 | 8 | 100 | 80 | No | 0.50 |
| 18 | 2150 | 8 | 100 | 80 | No | 0.50 |
| 19 | 4001 | 1 | 150 | 150 | Yes | 1.00 |
| 20 | 4002 | 1 | 150 | 150 | Yes | 1.00 |
| 21 | 4003 | 1 | 150 | 150 | Yes | 1.00 |
| 22 | 4005 | 2 | 150 | 150 | Yes | 1.00 |
| 23 | 4008 | 2 | 150 | 150 | Yes | 1.00 |
| 24 | 4010 | 3 | 150 | 150 | Yes | 1.00 |
| 25 | 4015 | 3 | 150 | 150 | Yes | 1.00 |
| 26 | 4020 | 4 | 110 | 110 | Yes | 1.00 |
| 27 | 4025 | 4 | 100 | 100 | Yes | 1.00 |
| 28 | 4030 | 4 | 100 | 100 | Yes | 1.00 |
| 29 | 4040 | 5 | 100 | 80 | Yes | 0.70 |
| 30 | 4050 | 5 | 100 | 80 | Yes | 0.70 |
| 31 | 4060 | 5 | 100 | 80 | Yes | 0.70 |
| 32 | 4075 | 5 | 100 | 80 | Yes | 0.70 |
| 33 | 4100 | 6 | 100 | 80 | No | 0.70 |
| 34 | 4125 | 6 | 100 | 80 | No | 0.70 |
| 35 | 4150 | 7 | 100 | 80 | No | 0.50 |
| 36 | 4175 | 7 | 100 | 80 | No | 0.50 |
| 37 | 4215 | 7 | 100 | 80 | No | 0.50 |
| 38 | 4215H(Note) | 8 | 100 | 80 | No | 0.50 |
| 39 | 4270 | 8 | 100 | 80 | No | 0.50 |
| 40 | 4300 | 8 | 100 | 80 | No | 0.50 |
| 41 | 4375 | 8 | 100 | 80 | No | 0.50 |
| 42 | 4425 | 8 | 100 | 80 | No | 0.50 |
Manual — Attachment1 continuation: model-specific torque limits, ASR filter, stall level, acceleration/deceleration and carrier settings. Header prints00-14~00-17 &00-23~00-27; retain literal.4215H note references chapter3.18 and330/370A. — page 181
Manual reference: physical PDF page 181. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: The spec. please refer to Chapter 3.18, the rated current is 330/370A.
Attachment1 continuation: model-specific torque limits, ASR filter, stall level, acceleration/deceleration and carrier settings. Header prints00-14~00-17 &00-23~00-27; retain literal.4215H note references chapter3.18 and330/370A.
Models / The initial value of parameters 21-05 ~21-08 (Torque Limit) / The initial value (s) of parameter 20-08 (ASR Filter Time) / The initial value (V) of parameter 08-02(Stall Level in Deceleration / The initial value (s) of Accel. & Decel 00-14~00-17 & 00-23~00-27 / Default carrier in HD kHz 11-01 / Max. carrier in HD kHz (SLV, Max. > 80Hz) 11-01 / Max. carrier in HD kHz (others) 11-01 — PDF page 181
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Models | The initial value of parameters 21-05 ~21-08 (Torque Limit) | The initial value (s) of parameter 20-08 (ASR Filter Time) | The initial value (V) of parameter 08-02(Stall Level in Deceleration | The initial value (s) of Accel. & Decel 00-14~00-17 & 00-23~00-27 | Default carrier in HD kHz 11-01 | Max. carrier in HD kHz (SLV, Max. > 80Hz) 11-01 | Max. carrier in HD kHz (others) 11-01 |
| 2 | 2001 | 200% | 0.001 | 385 | 10.0 | 8 | 8 | 16 |
| 3 | 2002 | 200% | 0.001 | 385 | 10.0 | 8 | 8 | 16 |
| 4 | 2003 | 200% | 0.001 | 385 | 10.0 | 8 | 8 | 16 |
| 5 | 2005 | 200% | 0.001 | 385 | 10.0 | 8 | 8 | 16 |
| 6 | 2008 | 200% | 0.001 | 385 | 10.0 | 8 | 8 | 16 |
| 7 | 2010 | 200% | 0.001 | 385 | 10.0 | 8 | 8 | 16 |
| 8 | 2015 | 200% | 0.002 | 385 | 15.0 | 8 | 8 | 16 |
| 9 | 2020 | 200% | 0.002 | 385 | 15.0 | 8 | 8 | 16 |
| 10 | 2025 | 200% | 0.002 | 385 | 15.0 | 6 | 8 | 12 |
| 11 | 2030 | 160% | 0.002 | 385 | 20.0 | 5 | 8 | 12 |
| 12 | 2040 | 160% | 0.002 | 385 | 20.0 | 5 | 8 | 12 |
| 13 | 2050 | 160% | 0.004 | 385 | 20.0 | 5 | 8 | 10 |
| 14 | 2060 | 160% | 0.004 | 385 | 20.0 | 5 | 8 | 10 |
| 15 | 2075 | 160% | 0.004 | 385 | 20.0 | 5 | 8 | 10 |
| 16 | 2100 | 160% | 0.004 | 385 | 20.0 | 5 | 8 | 10 |
| 17 | 2125 | 160% | 0.004 | 385 | 20.0 | 5 | 8 | 5 |
| 18 | 2150 | 160% | 0.004 | 385 | 20.0 | 5 | 8 | 5 |
| 19 | 4001 | 200% | 0.001 | 770 | 10.0 | 8 | 8 | 16 |
| 20 | 4002 | 200% | 0.001 | 770 | 10.0 | 8 | 8 | 16 |
| 21 | 4003 | 200% | 0.001 | 770 | 10.0 | 8 | 8 | 16 |
| 22 | 4005 | 200% | 0.001 | 770 | 10.0 | 8 | 8 | 16 |
| 23 | 4008 | 200% | 0.001 | 770 | 10.0 | 8 | 8 | 16 |
| 24 | 4010 | 200% | 0.001 | 770 | 10.0 | 8 | 8 | 16 |
| 25 | 4015 | 200% | 0.001 | 770 | 10.0 | 8 | 8 | 16 |
| 26 | 4020 | 200% | 0.002 | 770 | 15.0 | 8 | 8 | 16 |
| 27 | 4025 | 200% | 0.002 | 770 | 15.0 | 8 | 8 | 16 |
| 28 | 4030 | 200% | 0.002 | 770 | 15.0 | 8 | 8 | 16 |
| 29 | 4040 | 160% | 0.002 | 770 | 20.0 | 5 | 8 | 12 |
| 30 | 4050 | 160% | 0.002 | 770 | 20.0 | 5 | 8 | 12 |
| 31 | 4060 | 160% | 0.002 | 770 | 20.0 | 5 | 8 | 10 |
| 32 | 4075 | 160% | 0.004 | 770 | 20.0 | 5 | 8 | 10 |
| 33 | 4100 | 160% | 0.004 | 770 | 20.0 | 5 | 8 | 10 |
| 34 | 4125 | 160% | 0.004 | 770 | 20.0 | 4 | 8 | 10 |
| 35 | 4150 | 160% | 0.004 | 770 | 20.0 | 5 | 8 | 10 |
| 36 | 4175 | 160% | 0.004 | 770 | 20.0 | 5 | 8 | 10 |
| 37 | 4215 | 160% | 0.004 | 770 | 20.0 | 3 | 8 | 8 |
| 38 | 4215H(Note) | 160% | 0.004 | 770 | 20.0 | 4 | 5 | 5 |
| 39 | 4270 | 160% | 0.004 | 770 | 20.0 | 4 | 5 | 5 |
| 40 | 4300 | 160% | 0.004 | 770 | 20.0 | 4 | 5 | 5 |
| 41 | 4375 | 160% | 0.004 | 770 | 20.0 | 4 | 5 | 5 |
| 42 | 4425 | 160% | 0.004 | 770 | 20.0 | 2 | 5 | 5 |
Manual — Attachment1 575/690V Models. Separate500x and600x models exactly as source. — page 182
Manual reference: physical PDF page 182. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
575/690V Models
Attachment1 575/690V Models. Separate500x and600x models exactly as source.
Model / Frame / Max. frequency (Hz) in SLV when carrier frequency <= 8K / Max. frequency (Hz) in SLV when carrier frequency > 8K / Display parameter 12-41 (Inverter temperature) / The initial value of parameter 18-00 in SLV/ SV (Slip compensation at low speed) — PDF page 182
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Model | Frame | Max. frequency (Hz) in SLV when carrier frequency <= 8K | Max. frequency (Hz) in SLV when carrier frequency > 8K | Display parameter 12-41 (Inverter temperature) | The initial value of parameter 18-00 in SLV/ SV (Slip compensation at low speed) |
| 2 | 5001 | 2 | 150 | 150 | Yes | 1.00 |
| 3 | 5002 | 2 | 150 | 150 | Yes | 1.00 |
| 4 | 5003 | 2 | 150 | 150 | Yes | 1.00 |
| 5 | 5005 | 3 | 150 | 150 | Yes | 1.00 |
| 6 | 5008 | 3 | 150 | 150 | Yes | 1.00 |
| 7 | 5010 | 3 | 150 | 150 | Yes | 1.00 |
| 8 | 6015 | 4 | 110 | 110 | Yes | 1.00 |
| 9 | 6020 | 4 | 110 | 110 | Yes | 1.00 |
| 10 | 6025 | 4 | 110 | 110 | Yes | 1.00 |
| 11 | 6030 | 4 | 110 | 110 | Yes | 1.00 |
| 12 | 6040 | 4 | 110 | 110 | Yes | 1.00 |
| 13 | 6050 | 5 | 100 | 80 | Yes | 0.7 |
| 14 | 6060 | 5 | 100 | 80 | Yes | 0.7 |
| 15 | 6075 | 5 | 100 | 80 | Yes | 0.7 |
| 16 | 6100 | 6 | 100 | 80 | NO | 0.7 |
| 17 | 6125 | 6 | 100 | 80 | NO | 0.7 |
| 18 | 6150 | 6 | 100 | 80 | NO | 0.7 |
| 19 | 6175 | 7 | 100 | 80 | NO | 0.5 |
| 20 | 6215 | 7 | 100 | 80 | NO | 0.5 |
| 21 | 6250 | 7 | 100 | 80 | NO | 0.5 |
| 22 | 6270 | 7 | 100 | 80 | NO | 0.5 |
Manual — Attachment1 575/690V continuation. Do not insert missing08-02 column from other voltage table. — page 183
Manual reference: physical PDF page 183. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Attachment1 575/690V continuation. Do not insert missing08-02 column from other voltage table.
Models / The initial value of parameters 21-05 ~21-08 (Torque Limit) / The initial value (s) of parameter 20-08 (ASR Filter Time) / The initial value (s) of Accel. & Decel / Default carrier in HD kHz / Max. carrier in HD kHz (others) — PDF page 183
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Models | The initial value of parameters 21-05 ~21-08 (Torque Limit) | The initial value (s) of parameter 20-08 (ASR Filter Time) | The initial value (s) of Accel. & Decel | Default carrier in HD kHz | Max. carrier in HD kHz (others) |
| 2 | 5001 | 200% | 0.002 | 10 | 8 | 16 |
| 3 | 5002 | 200% | 0.002 | 10 | 8 | 16 |
| 4 | 5003 | 200% | 0.002 | 10 | 8 | 16 |
| 5 | 5005 | 200% | 0.002 | 20 | 8 | 16 |
| 6 | 5008 | 200% | 0.002 | 20 | 8 | 16 |
| 7 | 5010 | 200% | 0.002 | 20 | 8 | 16 |
| 8 | 6015 | 160% | 0.004 | 25 | 4 | 8 |
| 9 | 6020 | 160% | 0.004 | 25 | 4 | 8 |
| 10 | 6025 | 160% | 0.004 | 25 | 4 | 8 |
| 11 | 6030 | 160% | 0.004 | 25 | 4 | 8 |
| 12 | 6040 | 160% | 0.004 | 25 | 4 | 8 |
| 13 | 6050 | 160% | 0.004 | 30 | 4 | 8 |
| 14 | 6060 | 160% | 0.004 | 30 | 4 | 8 |
| 15 | 6075 | 160% | 0.004 | 30 | 4 | 8 |
| 16 | 6100 | 160% | 0.004 | 30 | 3 | 6 |
| 17 | 6125 | 160% | 0.004 | 30 | 3 | 6 |
| 18 | 6150 | 160% | 0.004 | 30 | 3 | 6 |
| 19 | 6175 | 160% | 0.004 | 30 | 2 | 4 |
| 20 | 6215 | 160% | 0.004 | 30 | 2 | 4 |
| 21 | 6250 | 160% | 0.004 | 30 | 2 | 4 |
| 22 | 6270 | 160% | 0.004 | 30 | 2 | 4 |
Manual — Parameter descriptions and source figure labels — page 184
Manual reference: physical PDF page 184. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Low Voltage Detection Level Function:
Wiring:
Relevant parameters: 07-30 Low Voltage Level Selection set 0 (Enable) 07-13 Low Voltage Detection Level set to 250V in 400V Class. 03-00~03-07 Set EPS input (62) enable.
07-31 Set Low Voltage Run Frequency
UPS or
Battery
Timing Diagram of Magnetic Contactor
Low Voltage Detection Level Function wiring figure labels: UPS or Battery; 1-Phase UPS or Battery; 440V Vac:207~380; Vdc:292~537; AC Motor Drive; R/L1,S/L2,T/L3; three-phase symbol3~; Execute Low Voltage Detection Level Input; S1~S8;24VG; contactor markers①②③. Source diagram preserved as evidence; no inferred wiring topology or installation approval.
Timing Diagram of Magnetic Contactor labels①②③. Printed paragraph: Before inputting emergency power, magnetic contactor①and③are ON and magnetic contactor②should be OFF. Magnetic contactor③should be ON after magnetic contactor is ON. Before removing battery and turning magnetic contactor②to be ON. Magnetic contactor①and③should be OFF. Notes for the emergency power supply. Please be aware of the following condition when emergency power is ON:1.Execute Low Voltage Function ON(DI=62),Fan doesn’t run.2.Execute Low Voltage Function ON(DI=62),No phase loss.3.Execute Low Voltage Function ON(DI=62),run frequency of motor depends on the value of07-31. One contactor identifier is absent in printed after clause; not supplied by inference.
Manual — 4.4 parameter descriptions; control modes0–6. Auto-tune and cable length guidance retained. — page 185
Manual reference: physical PDF page 185. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.4 Description of Parameters
The inverter offers the following control modes:
00-00=0: V/F Mode Select the required V/F curve (01-00) based on your motor and applications. Perform a stationary auto-tune (17-00=2), if the motor cable is longer than 50m (165ft), see parameter 17-00 for details. 00-00=1: V/F with PG Select the required V/F curve (01-00) based on your motor and applications. Set number of motor poles (02-08) and encoder feedback pulses (20-27); refer to parameter group 20 for PF feedback setup. Perform a stationary auto-tune (17-00=2) if the distance between the inverter and the motor more than 50m (165ft), refer to parameter group 17 for details on auto-tuning.
4.4 parameter descriptions; control modes0–6. Auto-tune and cable length guidance retained.
00-00 / Control mode selection — PDF page 185
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-00 | Control mode selection |
| 2 | Range | 0: V/F 1: V/F+PG 2: SLV 3: SV 4: PMSV 5: PMSLV 6: SLV2 |
Value / Mode / Info / Application — PDF page 185
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Value | Mode | Info | Application |
| 2 | 0 | V/F | V/F Control without PG | General Purpose Applications which do not require high precision speed control - Auto-tuning is not required. |
| 3 | 1 | V/F+PG | V/F Control with PG (speed compensation) | Closed loop speed control for General purpose applications that require better speed control than V/F mode without PG. |
| 4 | 2 | SLV | Sensorless Vector Control without PG | General Purpose Applications that require higher precision speed control and torque response without the use of an encoder. |
| 5 | 3 | SV | Closed Loop Vector Control with PG | General Purpose Applications that require high precision speed control and torque response with the use of an encoder. |
| 6 | 4 | PMSV | PM Vector Control with PG (Permanent Magnet Vector Control) | PM Motor Applications that require high precision speed control and torque response with the use of an encoder. |
| 7 | 5 | PMSLV | Sensorless Current Vector Control without PG (for Permanent magnet motor)。 | Without PG Applications. Provide the requirements of high precision speed and torque |
| 8 | 6 | SLV2 | Voltage vector control without PG | Without PG Applications. Vector control provides high speed rotation and the requirements of higher precision speed than V/F and torque. |
Manual — Parameter descriptions and source figure labels — page 186
Manual reference: physical PDF page 186. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
00-00=2: Sensorless Vector Control Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor parameters for higher performance operation. Perform non-rotational auto-tune if it’s not possible to rotate the motor during auto-tune. Refer to parameter group 17 for details on auto-tuning. 00-00=3: Closed Loop Vector Control Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor parameters for higher performance operation. Perform non-rotational auto-tune if it’s not possible to rotate the motor during auto-tune. Refer to parameter group 17 for details on auto-tuning. 00-00=4: PM Vector Control Verify the inverter rating matches the motor rating. Set PM motor data in parameters 22-00 to 22-06 and encoder feedback pulses in parameter 20-27. Refer to parameter 22-21 for details on PM Motor tuning. Select the appropriate motor rating and braking resistor based on your motor and applications. Please install the braking module in the models of 200V 30HP/ 400V 40HP/575V/690V 50HP or the above. 00-00=5: PM Sensorless Vector Control Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor parameters for higher performance operation. Perform auto-tuning before operation to enhance the performance of PMSLV mode. Refer to parameter 22-21 for the descriptions of PM motor tuning function. Select the appropriate motor rating and braking resistor based on your motor and applications. Please install the braking module in the models of 200V 30HP/ 400V 40HP/575V/690V 50HP or the above. 00-00=6: SLV2 Vector Control Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor parameters for higher performance operation. Refer to parameter group 17 for the descriptions of motor parameter tuning function. Select the required V/F curve (01-00) based on your motor and applications. Note: Parameter 00-00 is excluded from initialization.
Use the FWD/REV key to change motor direction when Run Command Selection (00-02 = 0) is set to keypad control. In keypad control operation the direction is stored in 00-01. Direction of this function will be limited to the motor direction lock selection of parameter 11-00.
Source parameter/procedure table; all source qualifiers and cross-references retained.
00-01 / Motor’s rotation direction — PDF page 186
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-01 | Motor’s rotation direction |
| 2 | Range | 0: Forward 1: Reverse |
00-02 / Run command selection — PDF page 186
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-02 | Run command selection |
| 2 | Range | 0: Keypad control 1: External terminal control 2: Communication control 3: PLC 4: RTC |
Manual — 2-wire truth table and alternative run function12. Figure labels are not wiring instructions independently validated. — page 187
Manual reference: physical PDF page 187. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
00-02=0: Keypad Control Use the keypad to start and stop the inverter and set direction with the forward / reverse key). Refer to section 4-1 for details on the keypad. 00-02=1: External terminal control External terminals are used to start and stop the inverter and select motor direction.
00-03=0: Keypad Control Use the keypad to start and stop the inverter and set direction with the forward / reverse key). Refer to section 4-1 for details on the keypad. 00-03=1: External terminal control External terminals are used to start and stop the inverter and select motor direction. *It is required to be with multi-function digital input (12: main and alternative run switch function). The inverter can be operated in either 2-wire or 3-wire mode. ■ 2-wire operation For 2-wire operation, set 03-00 (S1 terminal selection) to 0 and 03-01 (S2 terminal selection) to 1.
Parameter 13-08 to 2, 4 or 6 for 2-wire program initialization, multi-function input terminal S1 is set to forward , operation/ stop, and S2 is set for reverse, operation / stop.
Figure 4.4.1 wiring example of 2-wire
Figure4.4.1 wiring example of2-wire. Labels:Forward,Run/Stop;Reverse,Run/Stop;S1;S2;24VG. Native truth table supplies open/closed behavior; figure topology not reconstructed.
2-wire truth table and alternative run function12. Figure labels are not wiring instructions independently validated.
00- 03 / Alternative RUN Command Selection — PDF page 187
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 03 | Alternative RUN Command Selection |
| 2 | Range | 0: Keypad control 1: External terminal control 2: Communication control 3: PLC 4: RTC |
Terminal S1 / Terminal S2 / Operation — PDF page 187
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Terminal S1 | Terminal S2 | Operation |
| 2 | Open | Open | Stop Inverter / FWD Active |
| 3 | Closed | Open | Run Forward |
| 4 | Open | Closed | Run Reverse |
| 5 | Closed | Closed | Stop Inverter, Display EF9 Alarm after 500ms |
Manual — Parameter descriptions and source figure labels — page 188
Manual reference: physical PDF page 188. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
■ 3-wire operation For 3-wire operation set any of parameters 03-02 to 03-07 (terminal S3 ~ S8) to 26 to enable 3-wire operation in combination with S1 and S2 terminals set to run command and stop command. Parameter 13-08 to 3, 5 or 7 for 3-wire program initialization, multi-function input terminal S1 is set to run operation, S2 for stop operation and S7 for forward/reverse command. Note: Terminal S1 must be closed for a minimum of 50ms to activate operation.
S1
S2
S7 Forward/Reverse selection
24VG
Operation (normally open Momentary switch)
Stop (Normally closed Momentary switch) Stop Command (Off: Stop)
Run Command (On:Run)
Figure 4.4.2 wiring example of 3-wire .
Figure 4.4.3 3-wire operation
Figure4.4.2 wiring example of3-wire labels:Operation(normally open Momentary switch);Stop(Normally closed Momentary switch);S1 Run Command(On:Run);S2 Stop Command(Off:Stop);S7 Forward/Reverse selection;24VG. No inferred connection netlist.
Figure4.4.3 3-wire operation. Four plotted labels:Run Command;Stop Command;Forward/Reverse Command;Motor Speed;time axes. Run pulse ≥50ms,On/Off;Stop Off(Stop);direction Off(forward),On(Reversal);bottom phases Stop,Forward,Reverse,Stop,Forward. Diagram has no numeric speed or additional timing scale; none inferred.
Manual — Parameter descriptions and source figure labels — page 189
Manual reference: physical PDF page 189. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
■ 2-wire operation with hold function To enable 2-wire operation with hold function, set any of parameters 03-02 to 03-07 (terminal S3 ~ S8) to 53. When this mode is enabled set terminal S1 (03-00=0) to forward and S2 (03-01=1) to reverse run command.
Note: Terminal S1, S2 and S5 must be closed for a minimum of 50ms to activate operation. Note: The inverter will display SE2 error when input terminals S1-S8 is set to 53 and 26 simultaneously.
00-02=2: Communication control The inverter is controlled by the RS-485 port. Refer to parameter group 9 for communication setup. 00-02=3: PLC control The inverter is controlled by the inverter built-in PLC logic. Refer to section 4.5.
2-wire hold-function diagram labels:Momentary switches(Push buttons);S1 Forward Run Command(On:Run Forward);S2 Reverse Run Command(On:Run Reverse);S5 Stop(On:Stop);24VG. No inferred wiring.
Hold-function timing diagram:Forward Command,Reverse Command,Stop Command,Motor Speed;Time axes;each command pulse annotated >50ms. ON/OFF states,Stop OFF(Inverter On);phases Stop,Forward,Reverse,Stop,Forward. Text above says minimum50ms; inequality distinction retained.
Manual — Shared00-05/00-06 range, but option8MPG explicitly only00-05. Analog input switch-type qualifications retained. — page 190
Manual reference: physical PDF page 190. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
00-02=4: RTC control The inverter is controlled by RTC timer when run command is set to RTC. Refer to function group 16.
It is required to be with LCD keypad to display the language selection of parameter 00-04. 00-04=0, LCD keypad displays in English. 00-04=1, LCD keypad displays in Simplified Chinese. 00-04=2, LCD keypad displays in Traditional Chinese. 00-04=3, LCD keypad displays in Turkish. Note: It will not restore to the default value when this parameter performs initialization.
00-05/00-06= 0: Keypad Use the digital operator to enter frequency reference or to set parameter 05-01 (frequency reference 1) as alternative frequency reference source. Refer to section 4.1.4 for details. 00-05/00-06= 1: External control (Analog Input) Use analog reference from analog input AI1 or AI2 to set the frequency reference (as shown in Figure 4.4.4). Refer to parameters 04-00 to select the signal type.
Shared00-05/00-06 range, but option8MPG explicitly only00-05. Analog input switch-type qualifications retained.
00- 04 / Language — PDF page 190
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 04 | Language |
| 2 | Range | 0: English 1: Simplified Chinese 2: Traditional Chinese 3: Turkish |
00-05 / Main Frequency Command Source Selection — PDF page 190
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-05 | Main Frequency Command Source Selection |
| 2 | 00-06 | Alternative Frequency Source Selection |
| 3 | Range | 0: Keypad 1: External control (analog) 2: Terminal UP / DOWN 3: Communication control 4: Pulse input 5: Reserved 6: RTC 7: AI2 Auxiliary Frequency 8: Manual Pulse Generator (MPG) (only in parameter 00-05) |
AI1 – Analog Input 1 / AI2 – Analog Input 2 / 04-00 Setting (Default = 1) / Dipswitch SW2 (H & C type) or SW4 (E & G type) (Default ‘V’) — PDF page 190
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | AI1 – Analog Input 1 | AI2 – Analog Input 2 | 04-00 Setting (Default = 1) | Dipswitch SW2 (H & C type) or SW4 (E & G type) (Default ‘V’) |
| 2 | 0 ~ 10V | 0 ~ 10V | 0 | Set to ‘V’ |
| 3 | 0 ~ 10V | 4 ~ 20mA | 1 | Set to ‘I’ |
| 4 | -10 ~ 10V | 0 ~ 10V | 2 | Set to ‘V’ |
| 5 | -10 ~ 10V | 4 ~ 20mA | 3 | Set to ‘I’ |
| 6 | 4 ~ 20mA | 0 ~ 10V | 4 | Set to ‘V’ |
| 7 | 4 ~ 20mA | 4 ~ 20mA | 5 | Set to ‘I’ |
Manual — Parameter descriptions and source figure labels — page 191
Manual reference: physical PDF page 191. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Set parameter 04-05 to 10 to add frequency reference using AI2 to AI1.
+10V
GND
SW3
-10V
2KΩ AI1
AI2
Main Speed Frequency Reference Command ( Voltage Input)
Main Speed Frequency Reference Command ( Current Input)
SW4
AI1 AI2
Figure 4.4.4 Analog input as main frequency reference command (For H & C type) 00-05/00-06= 2: Terminal UP / DOWN The inverter accelerates with the UP command closed and decelerates with the DOWN command closed. Please refer to parameter 03-00 ~ 03-07 for additional information. Note: To use this function both the UP and DOWN command have to be selected to any of the input terminals. 00-05/00-06= 3: Communication control The frequency reference command is set via the RS-485 communication port using the MODBUS RTU protocol. Refer to parameter group 9 for additional information. 00-05/00-06= 4: Pulse input To use this function a pulse train input is required to be connected to the PI input and GND (see fig. 4.4.5). Set parameter 03-30 to 0 to use the pulse input as frequency reference. Refer to parameters 03-31 to 03-34 for pulse input scaling. PI input terminal, built-in resistance, is not required to connect the resistance if open collector input mode is used.
Figure4.4.4 Analog input as main frequency reference command(For H&C type). Labels:+10V,2KΩ,AI1 Main Speed Frequency Reference Command(Voltage Input),AI2 Main Speed Frequency Reference Command(Current Input),GND,-10V;switch labelsAI1/SW3 andAI2/SW4. Figure source labels conflict with previous page table switch-type reference; no silent correction or inferred wiring.
Manual — Parameter descriptions and source figure labels — page 192
Manual reference: physical PDF page 192. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Figure 4.4.5 Frequency reference from pulse input 00-05/00-06= 6: RTC Enables RTC control, reference frequency is controlled by the RTC function, Refer to parameter group 16 for RTC setup. 00-05/00-06= 7: AI2 Auxiliary Frequency When 04-05 is set to 0 (auxiliary frequency), frequency command is provided by multi-function analog input AI2 and the maximum output frequency (01-02, Fmax) = 100%. When 04-05 is not set to 0, the frequency is 0. Refer to the parameters of 03-00~03-07 for multi-speed descriptions. 00-05= 8: Manual Pulse Generator (MPG) Frequency command depends on the manual pulse generator (MPG). The speed of MPG is multiplied by the speed magnification calculation (parameter 20-43) and limited by the speed command limit (parameter 20-44). The MPG command is required to be installed the induction motor PG card (JN5-PG-L or JN5-PG-O).
When 00-07 is set to 0, the reference frequency is set by the main reference frequency selection of parameter 00-05. When 00-07 is set to 1 the reference frequency is sum of the main reference frequency (00-05) and alternative frequency (00-06). Note: The inverter will display the SE1 error when 00-07 = 1 and parameter 00-05 and 00-06 are set to the same selection. When parameter 00-06 is set to 0 (Keypad) the alternative frequency reference is set by parameter 05-01 (Frequency setting of speed-stage 0).
Figure4.4.5 Frequency reference from pulse input. Labels:PI,GND,0V,Serial pulse input(Internal resistence:3.89K). Specification:Low Input Level0.0to0.5V;High Input Level4.0to13.5V;Duty cycle(ON/OFF)30%to70%;Pulse Input frequency range:50to32KHz. Lower endpoint unit is not separately printed; do not infer50Hz or50KHz.
Source parameter/procedure table; all source qualifiers and cross-references retained.
00- 07 / Main and Alternative Frequency Command modes — PDF page 192
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 07 | Main and Alternative Frequency Command modes |
| 2 | Range | 0: Main frequency 1: Main frequency + alternative frequency |
Manual — Parameter descriptions and source figure labels — page 193
Manual reference: physical PDF page 193. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Display the frequency reference when 00-05 or 00-06 is set to communication control (3).
Note: This parameter is only enabled in communication mode.
00-10=0: Frequency command is lower than 01-08 (Minimum Output Frequency of Motor 1), it shows STP0 warning. 00-10=1: Frequency command is lower than 01-08 (Minimum Output Frequency of Motor 1), inverter run as Minimum Output Frequency of Motor 1.
When inverter gets to sleep, 00-11=0: PID is bound to lower limit frequency (00-13). 00-11=1: PID is bound to 0 Hz. Note: Refer to descriptions of parameters 10-17~10-20 for details when inverter gets to sleep.
Set the maximum frequency reference as a percentage of the maximum output frequency. Maximum output frequency depends on motor selection. Motor 1: Maximum frequency parameter 01-02. Motor 2: Maximum frequency parameter 01-16.
Set the minimum frequency reference as a percentage of the maximum output frequency. Maximum output frequency depends on motor selection. Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum frequency is set by parameter 01-16.
Source parameter/procedure table; all source qualifiers and cross-references retained.
00- 08 / Communication frequency command – READ ONLY — PDF page 193
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 08 | Communication frequency command – READ ONLY |
| 2 | Range | 0.00~599.00 Hz |
00-09 / Communication frequency command memory — PDF page 193
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-09 | Communication frequency command memory |
| 2 | Range | 0: Don’t save when power supply is off. (00-08) 1: Save when power is off. (00-08) |
00-10 / Minimum frequency detection — PDF page 193
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-10 | Minimum frequency detection |
| 2 | Range | 0:Show warning if lower than minimum frequency 1:Run as minimum frequency if lower than minimum frequency |
00- 11 / Selection of PID Lower Limit Frequency — PDF page 193
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 11 | Selection of PID Lower Limit Frequency |
| 2 | Range | 【0】:PID is bound to lower limit frequency when inverter sleeps. 【1】:PID is bound to 0Hz when inverter sleeps. |
00-12 / Upper Limit Frequency — PDF page 193
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-12 | Upper Limit Frequency |
| 2 | Range | 0.1~109.0 % |
00-13 / Lower Limit Frequency — PDF page 193
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-13 | Lower Limit Frequency |
| 2 | Range | 0.0~109.0 % |
Manual — Parameter descriptions and source figure labels — page 194
Manual reference: physical PDF page 194. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Notes: - When the frequency lower limit is set to a value greater than 0 and the inverter is started the output frequency will accelerate to the frequency lower limit with a minimum frequency defined by parameter 01-08 for motor 1 and parameter 01-22 for motor 2. - Frequency upper limit has to greater or equal to the frequency lower limit otherwise the inverter will display a SE01 (Set range error). - Frequency upper and lower limit is active for all frequency reference modes.
Figure 4.4.6 Frequency reference upper and lower limits Note: The maximum frequency setting in the keypad is according to parameter 01-02 (Maximum Output Frequency) and 00-12 (Upper Frequency limit). The upper frequency limit is not over than 599Hz and AI frequency is 100% to parameter 01-02.
Figure4.4.6 Frequency reference upper and lower limits. Output Frequency vertical axis;Frequency Reference horizontal axis;100%on each;00-12 upper horizontal bound,00-13 lower bound. No interpolation of graph values.
Manual — Acceleration/deceleration capacity default table; actual times depend on load. — page 195
Manual reference: physical PDF page 195. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Acceleration time is the time required to accelerate from 0 to 100% of maximum output frequency. Deceleration time is the time required to decelerate from 100 to 0% of maximum output frequency. Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum frequency is set by parameter 01-16. Note: Actual acceleration and deceleration times can be affected by the inverter driven load. The default values for the acceleration, deceleration times are dependent on the inverter size.
Acceleration/deceleration capacity default table; actual times depend on load.
00-14 / Acceleration time 1 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-14 | Acceleration time 1 |
| 2 | Range | 0.1~6000.0 Sec |
00-15 / Deceleration time 1 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-15 | Deceleration time 1 |
| 2 | Range | 0.1~6000.0 Sec |
00-16 / Acceleration time 2 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-16 | Acceleration time 2 |
| 2 | Range | 0.1~6000.0 Sec |
00-17 / Deceleration time 2 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-17 | Deceleration time 2 |
| 2 | Range | 0.1~6000.0 Sec |
00-21 / Acceleration time 3 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-21 | Acceleration time 3 |
| 2 | Range | 0.1~6000.0 Sec |
00-22 / Deceleration time 3 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-22 | Deceleration time 3 |
| 2 | Range | 0.1~6000.0 Sec |
00-23 / Acceleration time 4 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-23 | Acceleration time 4 |
| 2 | Range | 0.1~6000.0 Sec |
00-24 / Deceleration time 4 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-24 | Deceleration time 4 |
| 2 | Range | 0.1~6000.0 Sec |
00-25 / Switch-Over Frequency of Acceleration and Deceleration Time 1 and Time 4 — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-25 | Switch-Over Frequency of Acceleration and Deceleration Time 1 and Time 4 |
| 2 | Range | 0.00~599.00 Hz |
Size / Acceleration / Deceleration Default Value — PDF page 195
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Size | Size | Acceleration / Deceleration Default Value |
| 2 | 200V series | 400V series | Acceleration / Deceleration Default Value |
| 3 | 1~10HP | 1~15HP | 10s |
| 4 | 15~20HP | 20~30HP | 15s |
| 5 | 30~150HP | 40~425HP | 20s |
Manual — 575/690V default table plus digital input truth table:0OFF/1ON. Preserve parameter codes and column order. — page 196
Manual reference: physical PDF page 196. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
A: Select acceleration and deceleration time via the digital input terminals The following table shows the acceleration / deceleration selected when the digital input function Accel/ Decel time 1 (#10) and Accel/Decel time 2 1(#30) are used. Table 4.4.1 acceleration / deceleration time selection
0: OFF, 1: ON
Figure 4.4.7: Terminal S5 switch between Tacc1/Tacc2 and Tdec1/Tdec2
Figure4.4.7 TerminalS5 switch betweenTacc1/Tacc2 andTdec1/Tdec2. Output Frequency andtime axes;Tacc1Rate,Tacc2Rate,Tdec2Rate,Tdec1Rate;Digital Input TerminalS5(03-04=10),S5Closed,time. Source shape only; no extra numerical rates inferred.
575/690V default table plus digital input truth table:0OFF/1ON. Preserve parameter codes and column order.
Size / Acceleration / Deceleration Default Value — PDF page 196
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Size | Size | Acceleration / Deceleration Default Value |
| 2 | 575V series | 1~3HP | 10s |
| 3 | 575V series | 5~10HP | 20s |
| 4 | 690V series | 15~40HP | 25s |
| 5 | 690V series | 50~535HP | 30s |
Accel/decel time 2 (Set 03-00 ~ 03-07 = 30) / Accel/decel time 1 (Set 03-00 to 03-07 = 10) / Acceleration time / Deceleration time — PDF page 196
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Accel/decel time 2 (Set 03-00 ~ 03-07 = 30) | Accel/decel time 1 (Set 03-00 to 03-07 = 10) | Acceleration time | Deceleration time |
| 2 | 0 | 0 | Taccc1 (00-14) | Tdec1 (00-15) |
| 3 | 0 | 1 | Taccc2 (00-16) | Tdec2 (00-17) |
| 4 | 1 | 0 | Taccc3 (00-21) | Tdec3 (00-22) |
| 5 | 1 | 1 | Taccc4 (00-23) | Tdec4 (00-24) |
Manual — Motor2 table; mode restriction V/F andV/F+PG. Automatic switching prose and graph conflict, retained. — page 197
Manual reference: physical PDF page 197. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B. Switch of Acceleration/Deceleration time according to motors 03-00~03-07 set to 40 (Switching between motor 1/motor 2), it can switch motors by digital input. This function I only for V/F control mode and V/F +PG card mode. Chose for motor1, acceleration and deceleration time of multi-speed depends on Figure 4.4.1. Chose for motor, acceleration and deceleration time of multi-speed depends on the following Figure.
C. Automatically switch acceleration/deceleration time When output frequency equals to the value of 00-25, it follows the value of 00-25 to automatically switch acceleration/ deceleration time1 and time2.Please refer to the following Figure4.4.8.
Figure 4.4.8 automatically switch Acceleration/Deceleration time ‧ When output frequency Fout <00-25 : Acceleration/deceleration time = Acceleration time1/ deceleration time 1(00-14 and 00-15). ‧ When output frequency Fout ≧ 00-25 : Acceleration/deceleration time = Acceleration time4/ deceleration time 4(00-23 and 00-24) When 03-00~03-07 set to 10 (Acceleration/ Deceleration Time Selection 1) and 03-00~03-07 set to 3 (Acceleration/ Deceleration Time Selection 2), the priority is higher than 00-25.
Jog acceleration time (00-19) is the time required to accelerate from 0 to 100% of maximum output frequency. Jog deceleration time (00-20) is the time required to decelerate from 100 to 0% of maximum output frequency. Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum frequency is set by parameter 01-16.
Figure4.4.8 automatically switch Acceleration/Deceleration time. Output Frequency vertical,time horizontal;00-25 threshold;Tacc1 Rate(00-14),Tacc4 Rate(00-23),Tdec4 Rate(00-24),Tdec1 Rate(00-15). Figure and following inequalities use times1/4; preceding sentence says time1/time2. Preserve conflict.
Motor2 table; mode restriction V/F andV/F+PG. Automatic switching prose and graph conflict, retained.
Chose motor2 — PDF page 197
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Chose motor2 | Chose motor2 | Chose motor2 |
| 2 | acceleration and deceleration time 1 (Set 03-00 to 03-07 = 10) | acceleration | deceleration |
| 3 | 0 | Taccc3(00-21) | Tdec3(00-22) |
| 4 | 1 | Taccc4(00-23) | Tdec4(00-24) |
00-18 / Jog frequency — PDF page 197
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-18 | Jog frequency |
| 2 | Range | 0.00~599.00 Hz |
00-19 / Jog acceleration time — PDF page 197
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-19 | Jog acceleration time |
| 2 | Range | 0.1~6000.0 Sec |
00-20 / Jog deceleration time — PDF page 197
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-20 | Jog deceleration time |
| 2 | Range | 0.1~6000.0 Sec |
Manual — Parameter descriptions and source figure labels — page 198
Manual reference: physical PDF page 198. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When run command selection is external terminal control (00-02=1) and the inverter uses the jog frequency (00-18, default 6.0 Hz) as its frequency reference with 03-00~03-07=6 or 7(6: Forward jog run command 7: Reverse jog run command).The motor will run by the setting.
The emergency stop time is used in combination with multi-function digital input function #14 (Emergency stop). When emergency stop input is activated the inverter will decelerate to a stop using the Emergency stop time (00-26) and display the [EM STOP] condition on the keypad. Note: To cancel the emergency stop condition the run command has to be removed and emergency stop input deactivated.
Figure 4.4.9 Emergency stop example Multi-function digital input terminals (03-00 ~ 03-07) are set to 14: When the emergency stop input is activated the inverter will decelerate to a stop using the time set in parameter 00-26. Note: After an emergency stop command the run command and emergency stop command have to be removed before the inverter can be restarted. Please refer to Figure 4.4.9. The emergency stop function can be used to stop inverter in case of an external event. Multi-function digital input terminals (03-00 ~ 03-07) set to 15: When the base block input is activated the inverter output will turn off and the motor will coast to a stop.
Figure4.4.9 Emergency stop example. Emergency stop commandS5(03-04=14),Off/On;Run Command,On;Output Frequency;time axes;Emergency stop deceleration time. Procedure distinguishes emergency stop14 from baseblock15; diagram is not proof of safety certification.
Source parameter/procedure table; all source qualifiers and cross-references retained.
00-26 / Emergency stop time — PDF page 198
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-26 | Emergency stop time |
| 2 | Range | 0.0~6000.0 Sec |
Manual — HD/ND; 599Hz headline has SLV rating/capacity exceptions. ND applies onlyV/F andV/F+PG. Source duplicate carrier condition100/80Hz retained. — page 199
Manual reference: physical PDF page 199. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The inverter overload curve, carrier frequency, stalls prevention level, rated input/output current and maximum frequency are automatically set based on the inverter duty (HD/ND) selection. Please refer to table 4.4.2 for detailed information. Table 4.4.2 Heavy Duty (Constant torque) / Normal Duty (Variable torque)
00-27= 0: Heavy Duty Mode Select V/F curve (Group 1) and enter motor data (Group 2) to match the application. In Heavy Duty mode the maximum output frequency is 599Hz for all control modes, except for SLV mode (Sensorless Vector / Open Loop Vector Mode) where the maximum output frequency is limited based on the inverter rating, see table below.
00-27= 1: Normal Duty Mode In normal duty mode only applies to control modes V/F and V/F + PG. All other modes must use the Heavy Duty settings.
HD/ND; 599Hz headline has SLV rating/capacity exceptions. ND applies onlyV/F andV/F+PG. Source duplicate carrier condition100/80Hz retained.
00-27 / HD/ND selection — PDF page 199
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-27 | HD/ND selection |
| 2 | Range | 0: HD (Heavy Duty / Constant Torque) 1: ND (Normal Duty / Variable Torque) |
00-27 / Overload capacity / Carrier frequency / Maximum output frequency / Stall prevention level / Rated input / output current — PDF page 199
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | 00-27 | Overload capacity | Carrier frequency | Maximum output frequency | Stall prevention level | Rated input / output current |
| 2 | 0 (Heavy Duty) | 150%, 1min | 2-16KHz (KVA dependent) | 599.00Hz | 150% (08-00, 08-01) | Refer to section 3.7 |
| 3 | 1 (Normal Duty) | 120%, 1min | 2-16KHz (KVA dependent) | 120.00Hz | 120% (08-00, 08-01) | Refer to section 3.7 |
Horsepower / Special circumstances / Maximum output frequency — PDF page 199
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Horsepower | Special circumstances | Maximum output frequency |
| 2 | 220V 1~10HP, 440V 1~15HP | - | 150Hz |
| 3 | 220V 15~25HP, 440V 20HP | - | 110Hz |
| 4 | 440V 25~30HP | - | 100Hz |
| 5 | 220V 30~150HP, 440V 40~425HP, | Carrier frequency (11-01) set 8KHz or below | 100Hz |
| 6 | 220V 30~100HP, 440V 40~175HP, | Carrier frequency (11-01) set 8KHz or higher | 80Hz |
| 7 | 575V 1~10HP | - | 150Hz |
| 8 | 575V/690V 15~40HP | - | 110Hz |
| 9 | 575V/690V 50~535HP | Carrier frequency (11-01) set 8KHz or below | 100Hz |
| 10 | 575V/690V 50~535HP | Carrier frequency (11-01) set 8KHz or below | 80Hz |
Manual — Parameter descriptions and source figure labels — page 200
Manual reference: physical PDF page 200. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
00-28= 0: Positive reference curve, 0 – 10V / 4 – 20mA = 0 – 100% main frequency reference. 00-28= 1: Negative reference curve, 0 – 10V / 4 – 20mA = 100 – 0% main frequency reference. Note 1: Selection applies to analog input AI1 and AI2. Note 2: AI2 will be useful for analog input frequency command when 04-05=0.
Figure 4.4.10 Positive/negative analog input as main frequency reference command.
Refer to figure 4.4.11 for zero-speed operation in sensor vector mode (SV / PMSV) (00-00=3 or 00-00=4).
Figure4.4.10 Positive/negative analog input as main frequency reference command. Left Normal/Positive Characteristics:Reference(%),Analog input signal,-10V,0V(4mA),10V(20mA),100%and-100%. Right Inverse/Negative Characteristics:Reference(%),Analog input signal,-10V,0V(4mA),10V(20mA). Right plotted apex at0V; no unprinted negative-reference value inferred.
Source parameter/procedure table; all source qualifiers and cross-references retained.
Adjacent source context — repeated to preserve continuation:
00- 28 / Command characteristic selection of master frequency — PDF page 200
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 28 | Command characteristic selection of master frequency |
| 2 | Range | 0: Positive characteristic (0-10V / 4-20mA = 0 -100%) 1: Negative / inverse characteristic (0-10V / 4~20mA = 100 - 0%) |
00-29 / Zero-speed operation selection — PDF page 200
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-29 | Zero-speed operation selection |
| 2 | Range | 0: Operation based on frequency command 1: Stop 2: Operation based on lowest frequency 3: Zero-speed operation |
Manual — Parameter descriptions and source figure labels — page 201
Manual reference: physical PDF page 201. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
time
RUN Command
Frequency Reference (Fref)
Output Frequency after softstart (Fout SFS)
Fmin (01-08)
B.B Pre-Excitation time
Fmin
B.B coast to stop 07-08
B.B
Zero Speed operation
DC braking
00-29=0
00-29=1
00-29=2
00-29=3
Pre-excitation
Figure 4.4.11 Zero-speed operation of sensor vector (SV) and PM vector (PMSV) mode DC injection braking activates when the run command is removed and output frequency falls below the DC injection braking start frequency (07-06). DC injection braking will be active for the time set in parameter 07-08 DC injection braking execution time. Refer to figure 4.4.62 for more information on the pre-excitation operation.
Figure4.4.11 Zero-speed operation of sensor vector(SV)andPMvector(PMSV)mode. Top RUN Command;Frequency Reference(Fref),Fmin(01-08);Output Frequency after softstart(Fout SFS). Four traces00-29=0,1,2,3. Each has Pre-excitation andDCbraking, B.B,07-16,07-08,time. Mode1 shows coast to stop; modes1/2/3 Fmin; mode3 Zero Speed operation before/after running. Mode0 note Pre-Excitation time. No unprinted speed/timing or safety behavior inferred.
Adjacent source context — repeated to preserve continuation:
Manual — Application presets; hoist/crane require TECO settings advice as source says. Input/output functions change automatically and source warns to confirm external controls. — page 202
Manual reference: physical PDF page 202. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: If set 00-32 back to 0, 2 wire initialization (60Hz)(230/400V) setting (13-08=11) will be executed. Note: Before to set up 00-32 Application, it should do initialized setting (parameter 13-08) first. When setting 00-32, the I/O port function changed automatically. To avoid accident, be sure to confirm the I/O port signal of inverter and external terminal control , 00-32=2: Conveyor
00-32=3: Exhaust fan
00-32=5: Compressor
Application presets; hoist/crane require TECO settings advice as source says. Input/output functions change automatically and source warns to confirm external controls.
Application presets; hoist/crane require TECO settings advice as source says. Input/output functions change automatically and source warns to confirm external controls. Application preset Conveyor00-32=2
Application presets; hoist/crane require TECO settings advice as source says. Input/output functions change automatically and source warns to confirm external controls. Application preset Exhaust fan00-32=3
Application presets; hoist/crane require TECO settings advice as source says. Input/output functions change automatically and source warns to confirm external controls. Application preset Compressor00-32=5
00-32 / Application Selection — PDF page 202
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-32 | Application Selection |
| 2 | Range | 0: General 1: Reserved 2: Conveyor 3: Exhaust fan 4: Reserved 5: Compressor 6: Hoist- * Consult TECO for the settings 7: Crane- * Consult TECO for the settings 8: Manual Pulse Generator (MPG) |
Parameter / Name / Value — PDF page 202
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Parameter | Name | Value |
| 2 | 00-00 | Control mode selection | 0: V/F |
| 3 | 00-14 | Acceleration time 1 | 3.0 sec |
| 4 | 00-15 | Deceleration time 1 | 3.0 sec |
| 5 | 00-27 | HD/ND selection | 0: HD |
| 6 | 08-00 | Stall prevention function | xx0xb: Stall prevention during deceleration |
Parameter / Name / Value — PDF page 202
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Parameter | Name | Value |
| 2 | 00-00 | Control mode selection | 0: V/F |
| 3 | 11-00 | Direction lock selection | 1: Forward direction only |
| 4 | 00-27 | HD/ND selection | 1: ND |
| 5 | 01-00 | V/F curve selection | F |
| 6 | 07-00 | Momentary power loss/ fault restart selection | 1: Enable |
| 7 | 08-00 | Stall prevention function | xx0xb: Stall prevention during deceleration |
Parameter / Name / Value — PDF page 202
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Parameter | Name | Value |
| 2 | 00-00 | Control mode selection | 0: V/F |
| 3 | 11-00 | Direction lock selection | 1: Forward direction only |
| 4 | 00-14 | Acceleration time 1 | 5.0 sec |
| 5 | 00-15 | Deceleration time 1 | 5.0 sec |
| 6 | 00-27 | HD/ND selection | 0: HD |
| 7 | 01-00 | V/F curve selection | F |
| 8 | 07-00 | Momentary power loss/ fault restart selection | 1: Enable |
| 9 | 08-00 | Stall prevention function | xx0xb: Stall prevention during deceleration |
Manual — Hoist and crane presets remain separate and subject to source Consult TECO qualifier from202. — page 203
Manual reference: physical PDF page 203. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
00-32=6: Hoist
00-32=7: Crane
Hoist and crane presets remain separate and subject to source Consult TECO qualifier from202. Application preset Hoist00-32=6
Hoist and crane presets remain separate and subject to source Consult TECO qualifier from202. Application preset Crane00-32=7
Parameter / Name / Value — PDF page 203
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Parameter | Name | Value |
| 2 | 00-00 | Control mode selection | 2: SLV |
| 3 | 00-05 | Main Frequency command source selection | 0: keypad |
| 4 | 11-43 | Hold Frequency at start | 3.0 Hz |
| 5 | 11-44 | Frequency hold Time at start | 0.3 sec |
| 6 | 00-14 | Acceleration time 1 | 3.0 sec |
| 7 | 00-15 | Deceleration time 1 | 3.0 sec |
| 8 | 11-01 | Carrier frequency | 5.0kHz |
| 9 | 05-01 | Frequency setting of speed-stage 0 | 6.0 Hz |
| 10 | 05-02 | Frequency setting of speed-stage 1 | 30.0 Hz |
| 11 | 05-03 | Frequency setting of speed-stage 2 | 60.0Hz/ 50.0 Hz |
| 12 | 03-28 | Photo-coupler output | 5 : frequency detection 2 |
| 13 | 07-18 | Minimum baseblock time | 0.3 sec |
| 14 | 08-00 | Stall prevention function | xx1x: Stall prevention ineffective in deceleration |
| 15 | 03-13 | Frequency detection level | 2.0 Hz |
| 16 | 03-14 | Frequency detection width | 0.1 Hz |
| 17 | 08-18 | Selection of low-torque operation | 0: Deceleration to stop |
| 18 | 08-19 | Level of low-torque detection | 2 % |
| 19 | 08-20 | Time of low-torque detection | 0.5 sec |
| 20 | 08-09 | Selection of input phase loss protection | 1 : Enable |
| 21 | 08-10 | Selection of output phase loss protection | 1 : Enable |
Parameter / Name / Value — PDF page 203
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Parameter | Name | Value |
| 2 | 00-00 | Control mode selection | 0: V/F |
| 3 | 00-05 | Main Frequency Command Source Selection | 0: keypad |
| 4 | 00-14 | Acceleration time 1 | 3.0 sec |
| 5 | 00-15 | Deceleration time 1 | 3.0 sec |
| 6 | 00-27 | HD/ND Mode selection | 0: HD |
| 7 | 11-01 | Carrier frequency | 5.0kHz |
| 8 | 05-01 | Frequency setting of speed-stage 0 | 6.0 Hz |
| 9 | 05-02 | Frequency setting of speed-stage 1 | 30.0 Hz |
| 10 | 05-03 | Frequency setting of speed-stage 2 | 60.0 Hz/ 50.0Hz |
| 11 | 03-04 | Multi-function terminal Function setting-S5 | 2: Multi-speed/position setting command 1 |
| 12 | 03-05 | Multi-function terminal Function setting-S6 | 3: Multi-speed/position setting command 2 |
| 13 | 03-28 | Photo-coupler output | 23: Source of operation command |
| 14 | 08-00 | Stall prevention function | xx1x : Stall prevention ineffective in deceleration |
| 15 | 08-09 | Selection of input phase loss protection | 1: Enable |
| 16 | 08-10 | Selection of output phase loss protection | 1: Enable |
Manual — MPG preset; modified-parameter feature LCD-only,250display limit; example step1 continues on later page. — page 204
Manual reference: physical PDF page 204. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
00-32=8: Manual Pulse Generator (MPG)
Note: It is only for LCD keypad. This parameter automatically lists all the adjusted parameters. When the default value is adjusted and 00-33=1, it will list all the parameters different from default values in the advanced modes and these parameters can be edited directly. The adjusted parameters list displays only when 00-33 is set from 0 to 1 or 00-33=1 at start up. If user wants to restore to the original editing interface, it is only required to set parameter 00-33=0. This function can display 250 adjusted parameters. If they are more than 250 parameters, it will list the adjusted parameters before 250. Example: Set 00-03 (alternative run command source selection) to be different from the default value.
LCD example step1:Group;00 Basic Func.(highlighted);01 V/F Pattern;02 Motor Parameter. ▲Up and▼Down selection references retained. Only step1 is on this page; sequence continues outside part.
MPG preset; modified-parameter feature LCD-only,250display limit; example step1 continues on later page. Application preset MPG00-32=8.
MPG preset; modified-parameter feature LCD-only,250display limit; example step1 continues on later page.
Parameter / Name / Value — PDF page 204
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Parameter | Name | Value |
| 2 | 00-00 | Control mode selection | 0: V/F |
| 3 | 00-02 | Main Run Command Source Selection | 1: External Terminal (Control Circuit) |
| 4 | 00-05 | Main Frequency Command Source Selection | 8: Manual Pulse Generator (MPG) |
| 5 | 00-16 | Acceleration Time 2 | 0.1 sec |
| 6 | 00-17 | Deceleration Time 2 | 0.1 sec |
| 7 | 01-00 | V/F Curve Selection | F |
| 8 | 03-07 | Multi-Function Terminal Function Setting-S8 | 67: Manual Pulse Generator Mode Switch |
| 9 | 07-09 | Stop Mode Selection | 1: Coast to Stop |
| 10 | 07-18 | Minimum Base block Time | 0.1 sec |
| 11 | 07-46 | DC Injection Current Limit | 100% |
| 12 | 08-00 | Stall Prevention Function | xx1xb: Stall prevention is disabled in deceleration. |
| 13 | 11-62 | Selection of Preventing Oscillation | 2: Mode3 |
| 14 | 20-08 | ASR Delay Time | 0 |
| 15 | 20-27 | PG Pulse Number | 100 |
| 16 | 20-43 | MPG Speed Magnification Calculation | 20 |
| 17 | 20-44 | MPG Speed Command Limit | 6.0 Hz |
00- 33 / Modified Parameters — PDF page 204
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 33 | Modified Parameters |
| 2 | Range | 0: Disable 1: Enable |
Steps / LCD Display / Descriptions — PDF page 204
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Steps | LCD Display | Descriptions |
| 2 | 1 | Group 00 Basic Func. 01 V/F Pattern 02 Motor Parameter | The starting parameter group (00) in the setting modes of ▲ (Up)/ ▼ (Down) selection groups. |
Manual — Modified-parameter example continued; LCD user parameters00-41to00-56, source duplicate00-48 retained. — page 205
Manual reference: physical PDF page 205. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Opaque LCD highlights hide some source glyphs; native layer retained but not visually verified.
User parameter setting (00-41 to 00-56) (only for LCD keypad)
‧ User parameter (00-41 ~ 00-56) can select 16 sets of parameters (group 00 ~ 22, but except 00-00/
00-41~00-56/ group 17) and put them into the list to do the fast access setting.
‧ When the access setting of parameter 13-06 is set to 1, user parameter 00-41 ~ 00-56 can be displayed and
changed.
‧ User parameter 00-41 ~ 00-56 can be changed in the advanced modes, exclusive of being in operation.
‧ Set value in the parameter of 00-41 ~ 00-56 and set 13-06 to 1.
LCD example2–6 visual reading: Step2 PARA00,-01 Motor Direction,-02 RUN Source; next highlight entirely black. Step3 Edit00-00,Sub RUN Sou ce; selected digit black,Terminal,(0~4),<2>. Step4 PARA00,black selected row,-41 UserP1,-42 UserP2. Step5 Edit00-33,Modify parameter,black selected digit,Enable,(0~1),<0>. Step6 Modify00,00-03 Sub RUN Source,next row black. Underlying native text is retained in cell records but hidden glyphs are not visually verified. Visible00-00 header differs from described00-03.
LCD table-column native text may include glyphs hidden by opaque black highlights. Entire LCD column conservatively flagged parser-only/visual-partial; visible labels separately transcribed. No hidden glyph is visually verified.
Modified-parameter example continued; LCD user parameters00-41to00-56, source duplicate00-48 retained.
2 / PARA 00 -01. Motor Direction -02. RUN Source -03. Sub RUN Source / Press READ/ ENTER key and ▲ (Up)/ ▼ (Down) to select alternative run command source (00-03). — PDF page 205
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | 2 | PARA 00 -01. Motor Direction -02. RUN Source -03. Sub RUN Source | Press READ/ ENTER key and ▲ (Up)/ ▼ (Down) to select alternative run command source (00-03). |
| 2 | 3 | Edit 00-00 Sub RUN Sou ce | Press READ/ ENTER key and adjust the value. The selected setting value will flash. |
| 3 | 3 | 1 Terminal (0 ~4) <2> | Press READ/ ENTER key and adjust the value. The selected setting value will flash. |
| 4 | 4 | PARA 00 -33. Modify parameter -41. User P1 -42. User P2 | Press DSP/ FUN to the menu of modified parameters (00-33). |
| 5 | 4 | ⟦blank source cell⟧ | Press DSP/ FUN to the menu of modified parameters (00-33). |
| 6 | 5 | Edit 00-33 Modify parameter | Press READ/ ENTER key to adjust the value to 1 (The modified parameter is enabled.) The selected setting value will flash. |
| 7 | 5 | 1 Enable (0 ~1) <0> | Press READ/ ENTER key to adjust the value to 1 (The modified parameter is enabled.) The selected setting value will flash. |
| 8 | 6 | Modify 00 00-03. Sub RUN Source 00-33. Modify parameter | Press DSP/ FUN back to the advanced modes. |
| 9 | 6 | ⟦blank source cell⟧ | Press DSP/ FUN back to the advanced modes. |
00- 41 / User parameter 0 — PDF page 205
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 41 | User parameter 0 |
| 2 | 00- 42 | User parameter 1 |
| 3 | 00- 43 | User parameter 2 |
| 4 | 00- 44 | User parameter 3 |
| 5 | 00- 45 | User parameter 4 |
| 6 | 00- 46 | User parameter 5 |
| 7 | 00- 47 | User parameter 6 |
| 8 | 00- 48 | User parameter 7 |
| 9 | 00- 48 | User parameter 8 |
| 10 | 00- 50 | User parameter 9 |
| 11 | 00- 51 | User parameter 10 |
| 12 | 00- 52 | User parameter 11 |
| 13 | 00- 53 | User parameter 12 |
| 14 | 00- 54 | User parameter 13 |
| 15 | 00- 55 | User parameter 14 |
| 16 | 00- 56 | User parameter 15 |
Manual — User parameter example1: assign03-00 to00-41. LCD black highlights obscure some source glyphs; native layer is retained separately from visible evidence. — page 206
Manual reference: physical PDF page 206. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Opaque LCD highlights hide some source glyphs; native layer retained but not visually verified.
‧ When 13-06=1, only parameter of 00-00 ~ 00-56 can be set or read in the advanced modes. 13-06=1 is
enabled in the parameter setting of 00-41~00-56.
‧ When user would like to leave the screen of user parameters, press RESET key and then DSP/FUN key to
select parameter Group 13.
Example 1: Set 03-00 (Multi-function terminal Function Setting-S1) to user parameter 0 (00-41)
LCD example1 visual labels: Step1Group00BasicFunc,01V/FPattern,02MotorParameter. Step2PARA00,selected row black,-42UserP1,-43UserP2. Step3Edit00-41,UserP0=00-41,00-41UserP0,<00-01–24-07>. Step4Edit00-41,UserP0=00-41,03-0 followed by black selected digit,S1FunctionSel,<00-01–24-07>. Step5Edit00-41,UserP0=03- 0,03-00S1FunctionSel,<00-01–24-07>. Step6Monitor,FreqRef,12-16=000.00Hz,12-17=000.00Hz,12-18=0000.0A. Hidden selected glyphs not reconstructed; step5 spacing retained as visible.
LCD table-column native text may include glyphs hidden by opaque black highlights. Entire LCD column conservatively flagged parser-only/visual-partial; visible labels separately transcribed. No hidden glyph is visually verified.
User parameter example1: assign03-00 to00-41. LCD black highlights obscure some source glyphs; native layer is retained separately from visible evidence.
Steps / LCD Display / Descriptions — PDF page 206
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Steps | LCD Display | Descriptions |
| 2 | 1 | Group 00 Basic Func. 01 V/F Pattern 02 Motor Parameter | Select the start parameter group (00) in the advanced modes. |
| 3 | 2 | PARA 00 -41. User P0 -42. User P1 -43. User P2 | Press (READ/ ENTER) key and ▲ (Up) / ▼ (Down) to select user parameter 0 (00-41). |
| 4 | 3 | Edit 00-41 User P0=00-41 | Press (READ/ ENTER) key to the screen of data setting/ read. * The selected setting value will flash. |
| 5 | 3 | 00-41 User P0 <00-01 - 24-07> | Press (READ/ ENTER) key to the screen of data setting/ read. * The selected setting value will flash. |
| 6 | 4 | Edit 00-41 User P0=00-41 | Press ◄ (Left) / ► (Right) and ▲ (Up) / ▼ (Down) key to set the value to 03-00 ( Multi-function terminal Function Setting-S1) |
| 7 | 4 | 03-00 S1 Function Sel <00-01 - 24-07> | Press ◄ (Left) / ► (Right) and ▲ (Up) / ▼ (Down) key to set the value to 03-00 ( Multi-function terminal Function Setting-S1) |
| 8 | 5 | Edit 00-41 User P0= 03- 0 | Press (READ/ ENTER) key to save 03-00 and the digit stops flashing and the screen displays User P0 = 03-00; 03-00 (Multi-function terminal Function Setting-S1) has been defined as 00-41. Few seconds later, the selected digit will flash again. |
| 9 | 5 | 03-00 S1 Function Sel <00-01 - 24-07> | Press (READ/ ENTER) key to save 03-00 and the digit stops flashing and the screen displays User P0 = 03-00; 03-00 (Multi-function terminal Function Setting-S1) has been defined as 00-41. Few seconds later, the selected digit will flash again. |
| 10 | 6 | Monitor Freq Ref | Press (DSP/ FUN) key to the display of main screen. * If users do not press BACK key in one minute, the screen will automatically display the monitor mode shown as the left figure. The automatically return time can be set via 16-06. |
| 11 | 6 | 12-16=000.00Hz --------------------------------------- 12-17=000.00Hz | Press (DSP/ FUN) key to the display of main screen. * If users do not press BACK key in one minute, the screen will automatically display the monitor mode shown as the left figure. The automatically return time can be set via 16-06. |
| 12 | 6 | 12-18=0000.0A | Press (DSP/ FUN) key to the display of main screen. * If users do not press BACK key in one minute, the screen will automatically display the monitor mode shown as the left figure. The automatically return time can be set via 16-06. |
Manual — User parameter example2steps1–9. Source LCD/description identifiers differ; literal source retained. — page 207
Manual reference: physical PDF page 207. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Opaque LCD highlights hide some source glyphs; native layer retained but not visually verified.
Example 2: After one or more parameters in 00-41 ~ 00-56 are set, user parameters settings are as follows.
LCD example2 visual labels: Step1Group13DriverStatus,14PLCSetting,15PLCMonitor. Step2PARA13,selected row black,-07Password1,-08Initialize. Step3Edit13-06,AccessLevel,1UserLevel,(0~2),<2>. Step4–ADV–G01-02,AccessLevel,black digit UserLevel,(0-2),<2>. Step5PARA13,selected row black. Step6Group,selected row black. Step7Monitor,FreqRef,12-16=000.00Hz,12-17=000.00Hz,12-18=0000.0A. Step8Group,00.UserFunction00User,selected row black. Step9PARA00,black selected identifier,S1FunctionSel. Underlying text remains native evidence, not visually verified hidden glyphs.
LCD table-column native text may include glyphs hidden by opaque black highlights. Entire LCD column conservatively flagged parser-only/visual-partial; visible labels separately transcribed. No hidden glyph is visually verified.
User parameter example2steps1–9. Source LCD/description identifiers differ; literal source retained.
Step / LCD Display / Descriptions — PDF page 207
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Step | LCD Display | Descriptions |
| 2 | 1 | Group 13 Driver Status 14 PLC Setting 15 PLC Monitor | Select the start parameter group (03) in the advanced modes. |
| 3 | 2 | PARA 13 -06. Access Level -07. Password 1 -08. Initialize | Press (READ/ ENTER) and ▲ (Up) / ▼ (Down) key to enter the access level of parameter (13-06). |
| 4 | 3 | Edit 13-06 Access Level | Press (READ/ ENTER) key to enter the screen of the data setting/ read. * The selected setting value will flash. |
| 5 | 3 | --------------------------------------- 1 User Level (0~2) | Press (READ/ ENTER) key to enter the screen of the data setting/ read. * The selected setting value will flash. |
| 6 | 3 | < 2 > | Press (READ/ ENTER) key to enter the screen of the data setting/ read. * The selected setting value will flash. |
| 7 | 4 | ─ADV─ G01-02 Access Level | Press ▲ (Up) / ▼ (Down) key to change setting value to 1 (13-06=1, user level) and Press (READ/ ENTER) key to save the setting value (03-00). Then, the digit stops flashing and the screen displays the setting value. Few seconds later, the selected digit will flash again. User level (13-06=1) can be set by one or more parameters in the user parameters of 00-41 ~ 00-56. If users do not set user parameters, 13-06 will not be set in the user level (setting value=1). |
| 8 | 4 | 1 User Level (0-2) < 2 > | Press ▲ (Up) / ▼ (Down) key to change setting value to 1 (13-06=1, user level) and Press (READ/ ENTER) key to save the setting value (03-00). Then, the digit stops flashing and the screen displays the setting value. Few seconds later, the selected digit will flash again. User level (13-06=1) can be set by one or more parameters in the user parameters of 00-41 ~ 00-56. If users do not set user parameters, 13-06 will not be set in the user level (setting value=1). |
| 9 | 5 | PARA 13 -06. Access Level | Press (DSP/FUN) key to the display of subdirectory. |
| 10 | 6 | Group 00.User Function | Press (DSP/FUN) key to the display of group directory. It is required to press ▲ (Up) key to select Group 00 User Function. |
| 11 | 7 | Monitor Freq Ref | Press (DSP/ FUN) key to enter the main screen. If user would like to leave the screen of user parameters, press RESET key and then DSP/FUN key to select parameter Group 13. Hotkeys are only enabled in inverter software V1.4. |
| 12 | 7 | 12-16=000.00Hz ----------------------- --------------- 12-17=000.00Hz | Press (DSP/ FUN) key to enter the main screen. If user would like to leave the screen of user parameters, press RESET key and then DSP/FUN key to select parameter Group 13. Hotkeys are only enabled in inverter software V1.4. |
| 13 | 7 | 12-18=0000.0A | Press (DSP/ FUN) key to enter the main screen. If user would like to leave the screen of user parameters, press RESET key and then DSP/FUN key to select parameter Group 13. Hotkeys are only enabled in inverter software V1.4. |
| 14 | 8 | Group 00. User Function00 User 13.Driver Status | 13-06 can be selected to be adjusted so leave parameters or enter parameter group 00 to edit user parameters is allowable. |
| 15 | 9 | PARA 00 -41. S1 Function Sel | Press (READ/ ENTER) key and ▲ (Up) / ▼ (Down) key to select user parameter 0 (00-41) display. |
Manual — User parameter example2steps10–12 and run-mode structuresA. Parameter-group scope differs from205. — page 208
Manual reference: physical PDF page 208. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Opaque LCD highlights hide some source glyphs; native layer retained but not visually verified.
01 V/F Pattern 00 Basic Func.
Group
[ Main Screen ] [ Main Menu] [ Subdirectory] [ READ/ ENTER ]
1 2
ENTER
Monitor Freq Ref 12 – 16 = 000 . 00Hz ------------------------------------ 12-17 = 000.00Hz 12-18 = 0000.0A
DSP FUN
02 Motor Parameter
READ
FUN DSP
PARA 00
-41 User P0 -42 User P1 -43 User P2
-54 User P13 -55 User P14 -56 User P15
FUN
DSP
Edit 00-41 User P0 ----------------------------------------- 01-00 V/F Pattern. Sel (01-00–24-06)
-00 Control Method
-01 Motor Direction
-02 RUN Source
User Parameter Run Mode Structures A. Define Parameter Group 0~24 as user parameters except parameter 00-00 and 00-41~00-56.
LCD steps10–12: Edit00-41,S1FunctionSel,0 plus black digit,2-Wire(FWD-RUN),(00~57),<00>,<03-00>; Step11same header/range,0 plus black digit,FJOG; Step12Monitor,FreqRef,12-16=000.00Hz,12-17=000.00Hz,12-18=0000.0A. Selected digits obscured; do not infer actual displayed setting.
User Parameter Run Mode StructuresA diagram labels: MainScreen;MainMenu;Subdirectory;READ/ENTER. MainMonitor:FreqRef,12-16=000.00Hz,12-17=000.00Hz,12-18=0000.0A. Group00BasicFunc,01V/FPattern,02MotorParameter. PARA00:-00ControlMethod,-01MotorDirection,-02RUNSource;PARA00:-41UserP0,-42UserP1,-43UserP2;PARA00:-54UserP13,-55UserP14,-56UserP15. Edit00-41,UserP0,01-00V/FPattern.Sel,(01-00–24-06). DSP/FUN andREAD/ENTER buttons,up/down arrows,circled1/2 continuation markers. Visible UI labels and printed scope only; no inferred missing menu entries.
LCD table-column native text may include glyphs hidden by opaque black highlights. Entire LCD column conservatively flagged parser-only/visual-partial; visible labels separately transcribed. No hidden glyph is visually verified.
User parameter example2steps10–12 and run-mode structuresA. Parameter-group scope differs from205.
Step / LCD Display / Descriptions — PDF page 208
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Step | LCD Display | Descriptions |
| 2 | 10 | Edit 00-41 S1 Function Sel | Press (READ/ ENTER) key to enter the screen of data setting/ read. *The selected setting value will flash. In this example, 03-00 (Multi-function terminal Function Setting-S1) has been defined as user parameters (00-41). The right bottom location displays the original parameter group. |
| 3 | 10 | 00 2-Wire (FWD-RUN) (00~57) < 00 > < 03-00 > | Press (READ/ ENTER) key to enter the screen of data setting/ read. *The selected setting value will flash. In this example, 03-00 (Multi-function terminal Function Setting-S1) has been defined as user parameters (00-41). The right bottom location displays the original parameter group. |
| 4 | 11 | Edit 00-41 S1 Function Sel | Press ▲ (Up) / ▼ (Down) key to change the setting value to 2. Use (READ/ ENTER) key to save the setting value. When the selected setting value does not flash again, the setting value will be saved to 00-41 and 03-00 simultaneously. |
| 5 | 11 | 06 FJOG (00~57) < 00 > < 03-00 > | Press ▲ (Up) / ▼ (Down) key to change the setting value to 2. Use (READ/ ENTER) key to save the setting value. When the selected setting value does not flash again, the setting value will be saved to 00-41 and 03-00 simultaneously. |
| 6 | 12 | Monitor Freq Ref 12-16=000.00Hz --------------------------------------- 12-17=000.00Hz 12-18=0000.0A | Press (DSP/FUN) key to the display of main screen. * If users do not press (DSP/ FUN) key in one minute, the screen will automatically display the monitor mode shown as the left figure. The automatically return time can be set via 16-06. |
Manual — User-level menu flow and00-57SV high speed mode; no physical drive execution or engineering validation. — page 209
Manual reference: physical PDF page 209. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: User level (13-06=1) can be set by one or more parameters in the user parameters of 00-41 ~ 00-56.
14 PLC Setting 13 Driver Status
Group
[Main Screen] [Main Menu] [Subdirectory] [READ/ ENTER] 1 2
ENTER
Monitor Freq Ref 12 – 16 = 000 . 00Hz ------------------------------------ 12-17 = 000.00Hz 12-18 = 0000.0A
DSP FUN
15 PLC Monitor
READ
FUN DSP
PARA 13
Edit 13-06 Access Level ----------------------------------------- 1 User Level (0~2) <2>
-00 KVA Sel
-01 S/W Version 1
-02 Elapsed Time1
-06 Access Level -07 Password 1
-08 Initialize
ENTER READ
00 User Function 13 Driver Status
FUN
DSP
PARA 00
-41 S1 Function Sel
-06 Access Level FUN
RESET < +
When the inverter runs in SV mode, SV high speed mode 2 is selected if it is required to use urgent accel./ decel.
User-level menu-flow diagram labels:MainScreen,MainMenu,Subdirectory,READ/ENTER. MonitorFreqRef,12-16=000.00Hz,12-17=000.00Hz,12-18=0000.0A. Group13DriverStatus,14PLCSetting,15PLCMonitor. PARA13:-00KVASel,-01S/WVersion1,-02ElapsedTime1;PARA13:-06AccessLevel,-07Password1,-08Initialize. Edit13-06AccessLevel,1UserLevel,(0~2),<2>. LowerPARA13:-06AccessLevel. RESET plusDSP/FUN;Group00UserFunction/13DriverStatus (two screens with alternate highlight);PARA00:-41S1FunctionSel. READ/ENTER,DSP/FUN,up/down andcircled1/2. All source labels; not a validated physical-drive procedure.
User-level menu flow and00-57SV high speed mode; no physical drive execution or engineering validation.
00- 57 / SV High Speed Mode — PDF page 209
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00- 57 | SV High Speed Mode |
| 2 | Range | 0: SV High Speed Mode 1 1: SV High Speed Mode 2 |
Manual — V/F selection01-00: control mode, voltage limits, initialization and curve selection conditions. — page 210
Manual reference: physical PDF page 210. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
01-V/F Control Parameters
The V/F curve selection is enabled for V/F mode with or without PG or SLV2 mode. Make sure to set the inverter input voltage parameter 01-14. There are three ways to set V/F curve: (1) 01-00 = 0 to E: choose any of the 15 predefined curves (0 to E). (2) 01-00 =0F, use 01-02~01-09 and 01-12~01-13, with voltage limit. (3) 01-00 = FF: use 01-02~01-09 and 01-12~01-13, without voltage limit. Refer to the following figure.
Output Voltage
Output Frequency 01-02 01-02
40 (the output frequency in the max. voltage)
The Output Voltage Limit Curve (the voltage limit of 400V class is two times.)
5V
40V
250V
(constant value) The default parameters (01-02~01-09) are the same when 01-00 is set to F (default) and 01-00 is set to 1. Parameters 01-02 to 01-13 are automatically set when any of the predefined V/F curves are selected. Note: This parameter is not affected by the initialization parameter (13-08). Consider the following items as the conditions for selecting a V/F pattern. (1) The voltage and frequency characteristic of motor. (2) The maximum speed of motor.
Output Voltage Limit Curve:verticalOutputVoltage(V),horizontalOutputFrequency;printedvoltage5V,40V,250V. Horizontal0;01-02 divided by40 (constant value);01-02 annotated outputfrequency in themax.voltage. Source note:voltagelimitof400Vclassistwotimes. Preserve plotted labels without extrapolated numerical limits or unprinted curve points.
V/F selection01-00: control mode, voltage limits, initialization and curve selection conditions.
01-00 / V/F curve selection — PDF page 210
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-00 | V/F curve selection |
| 2 | Range | 0~FF |
Manual — Table 4.4.3: 1 - 2HP V/F curve selection (200V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 211
Manual reference: physical PDF page 211. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.3: 1 - 2HP V/F curve selection (200V)
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 7.2, 13.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 7.2, 13.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 7.2, 13.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 6.5, 7.2, 35, 50, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 6.5, 7.2, 35, 50, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 7.3, 7.4, 14, 14.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 7.3, 7.4, 14, 14.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 7.2, 13.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 7.2, 13.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.3: 1 - 2HP V/F curve selection (200V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 7.2, 13.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.3: 1 - 2HP V/F curve selection (200V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 211
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General purpose | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General purpose | 50Hz | 50Hz | F (50Hz Default setting) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General purpose | 60 Hz | 60Hz Saturatio n | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General purpose | 60 Hz | 60Hz Saturatio n | F (60Hz Default setting.) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General purpose | 60 Hz | 50Hz Saturatio n | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | High Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque(Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50 Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque(Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50 Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque(Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60 Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque(Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60 Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque(Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.4: 3 - 30HP V/F curve selection (200V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 212
Manual reference: physical PDF page 212. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.4: 3 - 30HP V/F curve selection (200V)
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 6.8, 12.7, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 6.8, 12.7, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 6.8, 12.7, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 6, 6.8, 35, 50, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 6, 6.8, 35, 50, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 6.9, 7, 13.3, 13.8, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 6.9, 7, 13.3, 13.8, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 6.8, 12.7, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 6.8, 12.7, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.4: 3 - 30HP V/F curve selection (200V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 6.8, 12.7, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.4: 3 - 30HP V/F curve selection (200V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 212
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F (50Hz Default setting) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F (60Hz Default setting.) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | High Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.5: 40HP and above V/F curve selection (200V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 213
Manual reference: physical PDF page 213. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.5: 40HP and above V/F curve selection (200V)
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 7.7, 13.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 7.7, 13.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 7.7, 13.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 7.7, 36.4, 52.3, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 7.7, 36.4, 52.3, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 7.7, 8.2, 13.9, 14.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 7.7, 8.2, 13.9, 14.5, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 7.7, 13.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 7.7, 13.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.5: 40HP and above V/F curve selection (200V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 7.7, 13.6, 200. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.5: 40HP and above V/F curve selection (200V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 213
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F (50Hz Default setting) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturation | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturation | F (60Hz Default setting) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturation | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | High Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.6: 1 - 2HP V/F curve selection (220V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 214
Manual reference: physical PDF page 214. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.6: 1 - 2HP V/F curve selection (220V)
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 7.9, 14.8, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 7.9, 14.8, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 7.9, 14.8, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 7.1, 7.9, 38.5, 55, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 7.1, 7.9, 38.5, 55, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 8, 8.1, 15.4, 16.1, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 8, 8.1, 15.4, 16.1, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 7.9, 14.8, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 7.9, 14.8, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.6: 1 - 2HP V/F curve selection (220V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 7.9, 14.8, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.6: 1 - 2HP V/F curve selection (220V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 214
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.7: 3 - 30HP V/F curve selection (220V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 215
Manual reference: physical PDF page 215. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.7: 3 - 30HP V/F curve selection (220V)
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 7.5, 14, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 7.5, 14, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 7.5, 14, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 6.6, 7.5, 38.5, 55, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 6.6, 7.5, 38.5, 55, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 7.6, 7.7, 14.6, 15.2, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 7.6, 7.7, 14.6, 15.2, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 7.5, 14, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 7.5, 14, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.7: 3 - 30HP V/F curve selection (220V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 7.5, 14, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.7: 3 - 30HP V/F curve selection (220V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 215
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.8: 40HP and above V/F curve selection (220V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 216
Manual reference: physical PDF page 216. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.8: 40HP and above V/F curve selection (220V)
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 8.5, 15, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 8.5, 15, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 8.5, 15, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 8.5, 40, 57.5, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 8.5, 40, 57.5, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 8.5, 9, 15.3, 16, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 8.5, 9, 15.3, 16, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 8.5, 15, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 8.5, 15, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.8: 40HP and above V/F curve selection (220V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 8.5, 15, 220. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.8: 40HP and above V/F curve selection (220V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 216
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.9: 1 - 2HP V/F curve selection (230V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 217
Manual reference: physical PDF page 217. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.9: 1 - 2HP V/F curve selection (230V)
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 8.3, 15.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 8.3, 15.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 8.3, 15.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 7.4, 8.3, 40.3, 57.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 7.4, 8.3, 40.3, 57.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 8.4, 8.5, 16.1, 16.8, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 8.4, 8.5, 16.1, 16.8, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 8.3, 15.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 8.3, 15.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.9: 1 - 2HP V/F curve selection (230V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 8.3, 15.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.9: 1 - 2HP V/F curve selection (230V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 217
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | (Hz) 230 60 01.5 (V) (2) (1),(F) 50 8.3 3 15.5 | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | (Hz) 230 60 01.5 (V) (2) (1),(F) 50 8.3 3 15.5 | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | (Hz) 230 60 01.5 (V) (2) (1),(F) 50 8.3 3 15.5 | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | (Hz) 72 0 (V) (3) 60 1.5 3 8.3 15.5 230 | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | (Hz) 230 120 0 (V) (D) 60 1.5 8.3 3 15.5 |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | (Hz) 230 120 0 (V) (D) 60 1.5 8.3 3 15.5 |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | (Hz) 230 180 0 (V) (E) 60 1.5 8.3 3 15.5 |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | (Hz) 230 180 0 (V) (E) 60 1.5 8.3 3 15.5 |
Manual — Table 4.4.10 : 3 - 30HP V/F curve selection (230V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 218
Manual reference: physical PDF page 218. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V)
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 7.8, 14.6, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 7.8, 14.6, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 7.8, 14.6, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 6.9, 7.8, 40.3, 57.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 6.9, 7.8, 40.3, 57.5, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 7.9, 8.1, 15.3, 15.9, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 7.9, 8.7, 15.3, 15.9, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Source A/B graph prints8.7 where8/9graph prints8.1; neither value silently corrected.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 7.8, 14.6, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 7.8, 14.6, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 7.8, 14.6, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.10 : 3 - 30HP V/F curve selection (230V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 218
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.11: 40HP and above V/F curve selection (230V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 219
Manual reference: physical PDF page 219. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.11: 40HP and above V/F curve selection (230V)
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 8.9, 15.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 8.9, 15.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 8.9, 15.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 8.9, 41.8, 60.1, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 8.9, 41.8, 60.1, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 8.9, 9.4, 16, 16.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 8.9, 9.4, 16, 16.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 8.9, 15.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 8.9, 15.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.11: 40HP and above V/F curve selection (230V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 8.9, 15.7, 230. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.11: 40HP and above V/F curve selection (230V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 219
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.12:1 - 2HP V/F curve selection (380V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 220
Manual reference: physical PDF page 220. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.12:1 - 2HP V/F curve selection (380V)
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 12.3, 13.6, 66.5, 95, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 12.3, 13.6, 66.5, 95, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 13.8, 14, 26.6, 27.8, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 13.8, 14, 26.6, 27.8, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.12:1 - 2HP V/F curve selection (380V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.12:1 - 2HP V/F curve selection (380V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 220
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.13: 3 - 30HP V/F curve selection (380V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 221
Manual reference: physical PDF page 221. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.13: 3 - 30HP V/F curve selection (380V)
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 13, 24.2, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 13, 24.2, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 13, 24.2, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 11.4, 13, 66.5, 95, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 11.4, 13, 66.5, 95, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 13.1, 13.3, 25.2, 26.3, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 13.1, 13.3, 25.2, 26.3, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 13, 24.2, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 13, 24.2, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.13: 3 - 30HP V/F curve selection (380V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 13, 24.2, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.13: 3 - 30HP V/F curve selection (380V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 221
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.14: 40HP and above V/F curve selection (380V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 222
Manual reference: physical PDF page 222. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.14: 40HP and above V/F curve selection (380V)
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 14.7, 25.9, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 14.7, 25.9, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 14.7, 25.9, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 14.7, 69.1, 99.3, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 14.7, 69.1, 99.3, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 14.7, 15.5, 26.4, 27.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 14.7, 15.5, 26.4, 27.6, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 14.7, 25.9, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 14.7, 25.9, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.14: 40HP and above V/F curve selection (380V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 14.7, 25.9, 380. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.14: 40HP and above V/F curve selection (380V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 222
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.15: 1 - 2HP V/F curve selection (400V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 223
Manual reference: physical PDF page 223. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.15: 1 - 2HP V/F curve selection (400V)
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 14.4, 26.9, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 14.4, 26.9, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 14.4, 26.9, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 12.9, 14.4, 70, 100, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 12.9, 14.4, 70, 100, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 14.5, 14.7, 28, 29.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 14.5, 14.7, 28, 29.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 14.4, 26.9, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 14.4, 26.9, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.15: 1 - 2HP V/F curve selection (400V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 14.4, 26.9, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.15: 1 - 2HP V/F curve selection (400V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 223
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.16: 3 - 30HP V/F curve selection (400V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 224
Manual reference: physical PDF page 224. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.16: 3 - 30HP V/F curve selection (400V)
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 12, 13.6, 70, 100, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 12, 13.6, 70, 100, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 13.8, 14, 26.5, 27.6, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 13.8, 14, 26.5, 27.6, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.16: 3 - 30HP V/F curve selection (400V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 13.6, 25.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.16: 3 - 30HP V/F curve selection (400V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 224
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.17: 40HP and above V/F curve selection (400V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 225
Manual reference: physical PDF page 225. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.17: 40HP and above V/F curve selection (400V)
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 15.5, 27.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 15.5, 27.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 15.5, 27.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 15.5, 72.7, 104.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 15.5, 72.7, 104.5, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 15.5, 16.4, 27.8, 29.1, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 15.5, 16.4, 27.8, 29.1, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 15.5, 27.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 15.5, 27.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.17: 40HP and above V/F curve selection (400V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 15.5, 27.3, 400. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.17: 40HP and above V/F curve selection (400V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 225
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.18: 1 - 2HP V/F curve selection (415V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 226
Manual reference: physical PDF page 226. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.18: 1 - 2HP V/F curve selection (415V)
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 14.9, 27.9, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 14.9, 27.9, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 14.9, 27.9, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 13.4, 14.9, 72.6, 103.8, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 13.4, 14.9, 72.6, 103.8, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 15.1, 15.3, 29.1, 30.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 15.1, 15.3, 29.1, 30.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 14.9, 27.9, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 14.9, 27.9, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.18: 1 - 2HP V/F curve selection (415V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 14.9, 27.9, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.18: 1 - 2HP V/F curve selection (415V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 226
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.19: 3 - 30HP V/F curve selection (415V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 227
Manual reference: physical PDF page 227. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.19: 3 - 30HP V/F curve selection (415V)
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 14.1, 26.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 14.1, 26.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 14.1, 26.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 12.5, 14.1, 72.6, 103.8, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 12.5, 14.1, 72.6, 103.8, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 14.3, 14.5, 27.5, 28.7, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 14.3, 14.5, 27.5, 28.7, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 14.1, 26.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 14.1, 26.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.19: 3 - 30HP V/F curve selection (415V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 14.1, 26.4, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.19: 3 - 30HP V/F curve selection (415V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 227
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.20 : 40HP and above V/F curve selection (415V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 228
Manual reference: physical PDF page 228. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.20 : 40HP and above V/F curve selection (415V)
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 16, 28.3, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 16, 28.3, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 16, 28.3, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 16, 75.5, 108.5, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 16, 75.5, 108.5, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 16, 17, 28.9, 30.2, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 16, 17, 28.9, 30.2, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 16, 28.3, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 16, 28.3, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.20 : 40HP and above V/F curve selection (415V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 16, 28.3, 415. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.20 : 40HP and above V/F curve selection (415V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 228
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.21: 1 - 2HP V/F curve selection (440V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 229
Manual reference: physical PDF page 229. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.21: 1 - 2HP V/F curve selection (440V)
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 15.8, 29.6, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 15.8, 29.6, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 15.8, 29.6, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 14.2, 15.8, 77, 110, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 14.2, 15.8, 77, 110, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 16, 16.2, 30.8, 32.2, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 16, 16.2, 30.8, 32.2, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 15.8, 29.6, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 15.8, 29.6, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.21: 1 - 2HP V/F curve selection (440V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 15.8, 29.6, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.21: 1 - 2HP V/F curve selection (440V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 229
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.22: 3 - 30HP V/F curve selection (440V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 230
Manual reference: physical PDF page 230. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.22: 3 - 30HP V/F curve selection (440V)
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 15, 28, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 15, 28, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 15, 28, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 13.2, 15, 77, 110, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 13.2, 15, 77, 110, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 15.2, 15.4, 29.2, 30.4, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 15.2, 15.4, 29.2, 30.4, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 15, 28, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 15, 28, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.22: 3 - 30HP V/F curve selection (440V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 15, 28, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.22: 3 - 30HP V/F curve selection (440V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 230
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.23: 40HP and above V/F curve selection (440V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 231
Manual reference: physical PDF page 231. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.23: 40HP and above V/F curve selection (440V)
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 17, 30, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 17, 30, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 17, 30, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 17, 80, 115, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 17, 80, 115, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 17, 18, 30.6, 32, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 17, 18, 30.6, 32, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 17, 30, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 17, 30, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.23: 40HP and above V/F curve selection (440V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 17, 30, 440. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.23: 40HP and above V/F curve selection (440V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 231
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.24: 1 - 2HP V/F curve selection (460V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 232
Manual reference: physical PDF page 232. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.24: 1 - 2HP V/F curve selection (460V)
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 16.5, 30.9, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 16.5, 30.9, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 16.5, 30.9, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 14.8, 16.5, 80.5, 115, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 14.8, 16.5, 80.5, 115, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 16.7, 16.9, 32.2, 33.7, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 16.7, 16.9, 32.2, 33.7, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 16.5, 30.9, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 16.5, 30.9, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.24: 1 - 2HP V/F curve selection (460V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 16.5, 30.9, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.24: 1 - 2HP V/F curve selection (460V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 232
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.25: 3 - 30HP V/F curve selection (460V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 233
Manual reference: physical PDF page 233. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.25: 3 - 30HP V/F curve selection (460V)
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 15.7, 29.3, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 15.7, 29.3, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 15.7, 29.3, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 13.8, 15.7, 80.5, 115, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 13.8, 15.7, 80.5, 115, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 15.9, 16.1, 30.5, 31.8, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 15.9, 16.1, 30.5, 31.8, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 15.7, 29.3, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 15.7, 29.3, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.25: 3 - 30HP V/F curve selection (460V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 15.7, 29.3, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.25: 3 - 30HP V/F curve selection (460V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 233
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Table 4.4.26: 40HP and above V/F curve selection (460V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs. — page 234
Manual reference: physical PDF page 234. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.26: 40HP and above V/F curve selection (460V)
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column left, position 1; curve labels (0),(F). Vertical axis(V) printed nonzero labels ascending: 17.8, 31.4, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column left, position 2; curve labels (1),(F) and(2). Vertical axis(V) printed nonzero labels ascending: 17.8, 31.4, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 50, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column left, position 3; curve labels (3). Vertical axis(V) printed nonzero labels ascending: 17.8, 31.4, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 72. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column left, position 4; curve labels (4),(5). Vertical axis(V) printed nonzero labels ascending: 17.8, 83.6, 120.2, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 25, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column left, position 5; curve labels (6),(7). Vertical axis(V) printed nonzero labels ascending: 17.8, 83.6, 120.2, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 30, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column right, position 1; curve labels (8),(9). Vertical axis(V) printed nonzero labels ascending: 17.8, 18.8, 32, 33.5, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.3, 2.5, 50. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column right, position 2; curve labels (A),(B). Vertical axis(V) printed nonzero labels ascending: 17.8, 18.8, 32, 33.5, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column right, position 3; curve labels (C). Vertical axis(V) printed nonzero labels ascending: 17.8, 31.4, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 90. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column right, position 4; curve labels (D). Vertical axis(V) printed nonzero labels ascending: 17.8, 31.4, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 120. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/120 labels retained.
Table 4.4.26: 40HP and above V/F curve selection (460V). Graph column right, position 5; curve labels (E). Vertical axis(V) printed nonzero labels ascending: 17.8, 31.4, 460. Horizontal axis(Hz), with zero origin, printed labels: 0, 1.5, 3, 60, 180. Labels transcribed from this bounded source graph; no interpolation or unstated point-pair association. Broken horizontal scale shown above upper flat portion; compressed60/180 labels retained.
Table 4.4.26: 40HP and above V/F curve selection (460V); each graph retained independently. Axis-label sets are not interpolated coordinate pairs.
Type / Specification / 01-00 / V/F curve — PDF page 234
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Type | Specification | Specification | 01-00 | V/F curve | Type | Specification | Specification | 01-00 | V/F curve |
| 2 | General application | 50Hz | 50Hz | 0 | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | Low Starting Torque | 8 | ⟦blank source cell⟧ |
| 3 | General application | 50Hz | 50Hz | F ( 50Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 50Hz | High Starting Torque | 9 | ⟦blank source cell⟧ |
| 4 | General application | 60Hz | 60Hz Saturati on | 1 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 5 | General application | 60Hz | 60Hz Saturati on | F ( 60Hz Default setting ) | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | A | ⟦blank source cell⟧ |
| 6 | General application | 60Hz | 50Hz Saturati on | 2 | ⟦blank source cell⟧ | High Staring Torque‡ | 60Hz | Low Starting Torque | B | ⟦blank source cell⟧ |
| 7 | Variable Torque Characteristic | 72Hz | 72Hz | 3 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 90Hz | 90Hz | C | ⟦blank source cell⟧ |
| 8 | Variable Torque Characteristic | 50Hz | Variable Torque 1 | 4 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 9 | Variable Torque Characteristic | 50Hz | Variable Torque 2 | 5 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 120Hz | 120Hz | D | ⟦blank source cell⟧ |
| 10 | Variable Torque Characteristic | 60Hz | Variable Torque 3 | 6 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
| 11 | Variable Torque Characteristic | 60Hz | Variable Torque 4 | 7 | ⟦blank source cell⟧ | Constant-power torque (Reducer) | 180Hz | 180Hz | E | ⟦blank source cell⟧ |
Manual — Motor1 custom V/F parameter ranges: four voltage classes retained, no extrapolation. — page 235
Manual reference: physical PDF page 235. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Motor1 custom V/F parameter ranges: four voltage classes retained, no extrapolation.
01-02 / Maximum output frequency of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-02 | Maximum output frequency of motor 1 |
| 2 | Range | 4.8~599.0 Hz |
01-03 / Maximum output voltage of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-03 | Maximum output voltage of motor 1 |
| 2 | Range | 200V: 0.1~255.0 V 400V: 0.2~510.0 V 575V: 0.1~670.0 V 690V: 0.1~804.0 V |
01-04 / Middle output frequency 2 of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-04 | Middle output frequency 2 of motor 1 |
| 2 | Range | 0.0~599.0 Hz |
01-05 / Middle output voltage 2 of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-05 | Middle output voltage 2 of motor 1 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
01-06 / Middle output frequency 1 of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-06 | Middle output frequency 1 of motor 1 |
| 2 | Range | 0.0~599.0 Hz |
01-07 / Middle output voltage 1 of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-07 | Middle output voltage 1 of motor 1 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
01-08 / Minimum output frequency of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-08 | Minimum output frequency of motor 1 |
| 2 | Range | 0.0~599.0 Hz |
01-09 / Minimum output voltage of the motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-09 | Minimum output voltage of the motor 1 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
01-12 / Base frequency of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-12 | Base frequency of motor 1 |
| 2 | Range | 4.8~599.0 Hz |
01-13 / Base output voltage of motor 1 — PDF page 235
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-13 | Base output voltage of motor 1 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
Manual — Custom V/F selection and torque-boost curves, source cautions retained. — page 236
Manual reference: physical PDF page 236. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
V/F curve setting (01-02~01-09 and 01-12~01-13) Select any of the predefined V/F curves setting ‘0’ to ‘E’ that best matches your application and the load characteristic of your motor, choose a custom curve setting ‘F’ or ‘FF’ to set a custom curve. Important: Improper V/F curve selection can result in low motor torque or increased current due to excitation. For low torque or high speed applications, the motor may overheat. Make sure to provide adequate cooling when operating the motor under these conditions for a longer period of time. If the automatic torque boost function is enabled (parameter 01-10), the applied motor voltage will automatically change to provide adequate motor torque during start or operating at low frequency. Custom V/F Curve Setting: A custom curve selection allows users to set parameters 01-02 ~ 01-13 whereas a predefined curve selection does not.
Figure 4.4.12 Custom V/F curve
Figure 4.4.13 Torque boosting
Figure4.4.12CustomV/Fcurve. VerticalOutputVoltage(V):Vmax(01-03),Vbase(01-13),Vmid2(01-05),Vmid1(01-07),Vmin(01-09). HorizontalOutputFrequency(Hz):Fmin(01-08),Fmid1(01-06),Fmid2(01-04),Fbase(01-12),Fmax(01-02). Dottedprojectionlines andrisingsegments shown;no numericpoints inferred.
Figure4.4.13Torqueboosting. VerticalOutputVoltage(V):Vmax,Vmid2,Vmid1,Vmin. HorizontalFmin(01-08),Fmid1(01-06),Fmid2(01-04),Fbase(01-12),Fmax(01-02). Sourcecurve rises toVmid2thenfalls toVmid1beforerisingtoVmax; labels recorded as drawn, not corrected to monotonic voltage.
Manual — Custom V/F frequency-order inequalities and distinct SLV/SV/SLV2 behavior. — page 237
Manual reference: physical PDF page 237. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When setting the frequency related parameters for a custom V/F curve values make sure that: Fmax ≥ Fbase > Fmid2 > Fmid1 >Fmin (01-02) (01-12) (01-04) (01-06) (01-08) The ‘SE03’ V/F curve tuning error is displayed when the frequency values are set incorrectly. When 01-04 and 01-05 (or 01-18 and 01-19) are set to 0, the inverter ignores the set values of Fmid2 and Vmid2. The voltage values for 01-02~01-09 are irrelevant. The value for maximum output voltage of motor 1(01-03) and the value for base output voltage of motor 1(01-13) will depend on restore factory setting(13-08) to set the value of voltage. When the control mode is changed parameter 00-00, 01-08 (Fmin) and 01-09 (Vmin) will automatically be changed to the default setting of the selected control mode. SLV or SV Mode (Sensorless Vector or Sensor Vector Control) Enter the motor data in parameter group 17 for SV and SLV control mode (00-00) and perform auto-tuning. In the SV and SLV mode the V/F curve normally does not have to be re-adjusted after a successful auto-tune. The maximum output frequency setting 01-02 (Fmax), base frequency 01-12 (Fbase), minimum output frequency 01-08 (Fmin), maximum output voltage 01-03 (Vmax) or base output voltage 01-13 (Vbase) can be adjusted but the voltage is automatically adjusted by the internal current controller. Set the base frequency (01-12, Fbase) to the motor rated frequency on the motor nameplate. Perform the auto-tuning procedure after adjusting parameters 02-19 or 17-04 to reduce the voltage at no-load operation. Motor jitter can be reduced by lowering the no-load voltage. Please note that lowering the no-load voltage increases the current at no-load. * The setting of V/F curve in SLV2 is the same as that in VF mode.
Frequencyconstraint: Fmax(01-02) ≥ Fbase(01-12) > Fmid2(01-04) > Fmid1(01-06) > Fmin(01-08). Inequalities are source text; no inferred equalities.
Manual — Torque compensation gain and mode; high-speed mode sentence continues239. — page 238
Manual reference: physical PDF page 238. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
In V/F or V/F + PG and SLV2 mode the inverter automatically adjusts the output voltage to adjust the output torque during start or during load changes based on the calculated loss of motor voltage. Torque compensation gain (01-10) can adjust in the running time. No need to adjust in general except the following: If the wire between inverter and motor is too long, add the value of 01-10 If the capacity of motor is smaller than inverter, add the value of 01-10. If the motor vibrates, reduce the value of 01-10 Refer to the torque compensation gain adjustment shown in Figure 4.4.14.
Figure 4.4.14 Torque compensation gain to increase/decrease output torque Increase value when: The wiring between the inverter and the motor very too long The motor size is smaller than the inverter size Note: Gradually increase the torque compensation value and make sure the output current does not exceed inverter rated current. Reduce value when: When experiencing motor vibration Important: Confirm that the output current at low speed does not exceed the rated output current of the inverter.
Torque compensation mode 0 is the general mode. Torque Compensation Mode 1 is the high speed mode (120~160Hz) and the compensation amount decreases as
Figure4.4.14Torquecompensationgain. VerticalOutputVoltage,100%;horizontalBasefrequency;threeparallel risinglines,01-10,TorqueIncrease upwardarrow,TorqueDecrease downwardarrow. No numericalgainvalues inferredfromspacing.
Torque compensation gain and mode; high-speed mode sentence continues239.
01-10 / Torque compensation gain — PDF page 238
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-10 | Torque compensation gain |
| 2 | Range | 0.0~2.0 |
01-11 / Selection of Torque Compensation Mode — PDF page 238
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-11 | Selection of Torque Compensation Mode |
| 2 | Range | 0: Torque Compensation Mode 0 1: Torque Compensation Mode 1 |
Manual — Input voltage, torque-compensation time andmotor2 curveparameters. Source minimum-input statement retained. — page 239
Manual reference: physical PDF page 239. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
the increasing frequency. When the speed is at 0~120Hz, the compensation amount is the same as that in Torque compensation mode 0.
The minimum input voltage of inverter is 0.1V. Set the inverter input voltage (E.g. 200V / 208V / 230V / 240V or 380V / 415V / 440V / 460V / 480V). This parameter is used as a reference for predefined V/F curve calculation (01-00 = 0 to E), over-voltage protection level, stall prevention, etc… Note: It will depend on restore factory setting (13-08) to set the value of voltage
Set the torque compensation delay time in milliseconds. Only adjust in the following situations: Increase value when: When experiencing motor vibration Decrease value when: When motor torque response is too slow
Input voltage, torque-compensation time andmotor2 curveparameters. Source minimum-input statement retained.
01-14 / Input voltage setting — PDF page 239
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-14 | Input voltage setting |
| 2 | Range | 200V: 155.0~255.0 V 400V: 310.0~510.0 V 575V: 540.0~670.0 V 690V: 648.0~804.0 V |
01-15 / Torque compensation time — PDF page 239
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-15 | Torque compensation time |
| 2 | Range | 0~10000 ms |
01- 16 / Maximum output frequency of motor 2 — PDF page 239
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 16 | Maximum output frequency of motor 2 |
| 2 | Range | 4.8~599.0 Hz |
01- 17 / Maximum output voltage of motor 2 — PDF page 239
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 17 | Maximum output voltage of motor 2 |
| 2 | Range | 200V: .1~255.0 V 400V: .2~510.0 V 575V: 0.1~670.0 V 690V: 0.1~804.0 V |
01- 18 / Middle output frequency 2 of motor 2 — PDF page 239
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 18 | Middle output frequency 2 of motor 2 |
| 2 | Range | 0.0~599.0 Hz |
01- 19 / Middle output voltage 2 of motor 2 — PDF page 239
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 19 | Middle output voltage 2 of motor 2 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
01- 20 / Middle output frequency 1 of motor 2 — PDF page 239
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 20 | Middle output frequency 1 of motor 2 |
| 2 | Range | 0.0~599.0 Hz |
Manual — Motor2V/F curve usesmotor1settings; seeTables4.4.3–26. — page 240
Manual reference: physical PDF page 240. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Motor 2 V/F curve uses the same settings as motor 1. Note: Motor 2 V/F curve is the same as Motor 1, please refer to Table 4.4.3~26
Motor2V/F curve usesmotor1settings; seeTables4.4.3–26.
01- 21 / Middle output voltage 1 of motor 2 — PDF page 240
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 21 | Middle output voltage 1 of motor 2 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
01- 22 / Minimum output frequency of motor 2 — PDF page 240
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 22 | Minimum output frequency of motor 2 |
| 2 | Range | 0.0~599.0 Hz |
01-23 / Minimum output voltage of motor 2 — PDF page 240
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01-23 | Minimum output voltage of motor 2 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
01- 24 / Base frequency of motor 2 — PDF page 240
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 24 | Base frequency of motor 2 |
| 2 | Range | 4.8~599.0 Hz |
01- 25 / Base voltage of motor 2 — PDF page 240
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 25 | Base voltage of motor 2 |
| 2 | Range | 200V: 0.0~255.0 V 400V: 0.0~510.0 V 575V: 0.0~670.0 V 690V: 0.0~804.0 V |
01- 26 / V/F Curve Selection of Motor 2 — PDF page 240
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 01- 26 | V/F Curve Selection of Motor 2 |
| 2 | Range | 0~FF |
Manual — IMmotor1ranges; mode-dependent rated-current range and<1>autotune markers retained. — page 241
Manual reference: physical PDF page 241. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
02 - IM Motor Parameters
IMmotor1ranges; mode-dependent rated-current range and<1>autotune markers retained.
02- 00 / No-load current of motor 1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02- 00 | No-load current of motor 1 |
| 2 | Range | 0.01~600.00 A |
02- 01 / Rated current of motor 1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02- 01 | Rated current of motor 1 |
| 2 | Range | V/F and V/F+PG modes are 10%~200% of inverter’s rated current. SLV, SV modes are 25%~200% of inverter’s rated current. |
02-03 / Rated rotation speed of motor1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-03 | Rated rotation speed of motor1 |
| 2 | Range | 0~60000 rpm |
02- 04 / Rated voltage of motor1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02- 04 | Rated voltage of motor1 |
| 2 | Range | 200V: 50.0~240.0 V 400V: 100.0~480.0 V 575V: 150.0~670.0 V 690V: 200.0~804.0 V |
02- 05 / Rated power of motor 1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02- 05 | Rated power of motor 1 |
| 2 | Range | 0.01~600.00 KW |
02-06 / Rated frequency of motor 1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-06 | Rated frequency of motor 1 |
| 2 | Range | 4.8~599.0 Hz+ |
02-07 / Pole of motor 1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-07 | Pole of motor 1 |
| 2 | Range | 2~16 |
02-09 / Excitation current of motor 1 <1> — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-09 | Excitation current of motor 1 <1> |
| 2 | Range | 15.0~70.0 % |
02-10 / Core saturation coefficient 1 of motor 1 <1> — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-10 | Core saturation coefficient 1 of motor 1 <1> |
| 2 | Range | 1~100 % |
02-11 / Core saturation coefficient 2 of motor 1 <1> — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-11 | Core saturation coefficient 2 of motor 1 <1> |
| 2 | Range | 1~100 % |
02-12 / Core saturation coefficient 3 of motor 1 <1> — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-12 | Core saturation coefficient 3 of motor 1 <1> |
| 2 | Range | 80~300 % |
02-13 / Core loss of motor 1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-13 | Core loss of motor 1 |
| 2 | Range | 0.0~15.0 % |
02-15 / Resistance between wires of motor 1 — PDF page 241
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-15 | Resistance between wires of motor 1 |
| 2 | Range | 0.001~60.000 Ω |
Manual — IMmotor1manualtuning andnameplate values; sourcecross-references retained. — page 242
Manual reference: physical PDF page 242. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Motor parameters are automatically set when performing an auto-tune (17-10=1). In most case no adjustment is required after performing an auto-tune except when using the inverter in special applications (e.g. machine tool, positioning, etc…). Please refer to parameter group 22 for permanent magnet motor parameters. (1) Number of motor poles (02-07) Set the number of motor pole according to the motor nameplate. (2) Motor rated power (02-05) Set the motor power according to the motor nameplate. (3) Motor rated current (02-01) Set the motor rated current according to the motor nameplate. (4) Motor rated voltage (02-04) Set the motor rated voltage according to the motor nameplate. Set the motor rated voltage and it will adjust maximum output voltage of V/F curve. (5) Rated frequency of motor 1 (02-06) Set the motor rated frequency according to the motor nameplate. (6) Rated rotation speed of motor 1 (02-03) Set the motor rpm according to the motor nameplate. (7) No-load motor voltage (02-19) Parameter determines the rated flux during motor’s rated rotation in SLV or SV control mode. Set the value of this parameter to the same value as parameter 17-08. A value of 10~50V below the input voltage level ensures that the motor is capable of providing adequate torque performance when operating at nominal speed (or higher speed). Setting the value to small can result in a reduction in no-load current, weakened motor flux and an increase in motor current while the motor is loaded. (8) Motor excitation current (02-09) The current is obtained from rotational auto-tuning. It is required to perform manual tuning if the inverter cannot rotational auto-tune. When the manual tuning is performed, tune it from 33% and observe no-load voltage (the output value) of parameter 12-67. If parameter 12-67 is higher than no-load voltage (the setting value) of parameter 17-08, perform downward revision in parameter 02-09; if it is lower than that, perform upward revision in parameter 02-09. Tuning motor excitation current of parameter 02-09 will change motor leakage inductance of parameter 02-17 and motor mutual inductance of parameter 02-18. It is required to refer to the actual no-load voltage of parameter 12-76 to tune the motor excitation current of parameter 02-09. Change of the excitation current will also affect the relative actual no-load voltage fluctuation so it is required to tune to the similar setting value of no-load voltage (17-08). 1
IMmotor1manualtuning andnameplate values; sourcecross-references retained.
02-19 / No-Load Voltage of motor 1 — PDF page 242
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-19 | No-Load Voltage of motor 1 |
| 2 | Range | 200V: 50~240 V 400V: 100~480 V 575V: 420~600 V 690V: 504~720 V |
Manual — Core saturation/loss/no-loadcurrent andmotor2current; sourceequations retained. — page 243
Manual reference: physical PDF page 243. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(9) Setting of motor core’s saturation coefficient 1, 2 and 3 (02-10, 02-11, 02-12) These parameters are automatically set during auto-tune. No adjustment required. Parameters are set to 50% for 02-10, 75% for 02-11 and 137.5% for 02-12 to reduce the impact of core saturation. The motor core’s saturation coefficient is defined as a percentage of the motor excitation current. When the motor flux reaches 137.5% level, the core’s saturation coefficient shall be greater than 137.5%. When the motor flux is 50% or 75%, the core’s saturation coefficient is required to be less than 50% and 75%.
(10) Motor core loss (02-13) Set motor core loss as the percentage of the motor rated power. 3 × Motor core loss (watt) Motor rated power (watts, 02-05) Note: In V/F mode motor core loss (o2-13) is used to for torque compensation. (11) Motor line to line resistance (02-15) (12) Motor no-load current (02-00). Value is calculated based on the motor rated frequency (17-05) and motor rated current (17-03). In V / F control mode, the output current is greater than the no-load current with slip compensation is enabled. Note: The value of 02-01 needs to be greater than the value set in parameter 02-00, otherwise warning message "SE01" out of range error will be displayed.
Figure 4.4.15 Y-equivalent model an induction motor
% Wcore ( 02-13) = × 100%
Im : 02-09 Excitation Current Ks1: 02-10 Motor Core Saturation Coefficients 1 Ks2: 02-11 Motor Core Saturation Coefficients 2 Ks3: 02-12 Motor Core Saturation Coefficients 3
Motorcoresaturationgraph:horizontalFlux with50%,75%,100%,137.5%;verticalKs1Im,Ks2Im,Im,Ks3*Im,connectedcurve anddottedprojections. LegendIm:02-09ExcitationCurrent;Ks1:02-10MotorCoreSaturationCoefficients1;Ks2:02-11MotorCoreSaturationCoefficients2;Ks3:02-12MotorCoreSaturationCoefficients3. Sourceprose50%,75%,137.5% retained separately.
Printedcorelossformula: %Wcore(02-13) = [3 × Motorcoreloss(watt) / Motorratedpower(watts,02-05)] ×100%. Factor3andunits retained exactly;no engineering validation.
Figure4.4.15Y-equivalentmodelaninductionmotor. LabelsR1,Llkg,Iq,Id,Lm,R2/s,s:slip;arrowdirections andresistor/inductor symbols in sourceimage. Labels only;no inferred netlist or computed motorparameters.
Core saturation/loss/no-loadcurrent andmotor2current; sourceequations retained.
02-20 / No-Load Current of motor 2 — PDF page 243
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-20 | No-Load Current of motor 2 |
| 2 | Range | 0.01~600.00 A |
02-21 / Rated current of motor 2 — PDF page 243
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-21 | Rated current of motor 2 |
| 2 | Range | 10%~200% of inverter’s rated current |
Manual — Motor2parameters andmotor1leakageinductance. Motor2modefixedtoV/F. — page 244
Manual reference: physical PDF page 244. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Motor 2 V/F curve uses the same settings as motor 1. The control mode setting for motor 2 is fixed to V/F.
It is set by manual tuning function. Normally, it does not need to be adjusted because magnetic function does not exist in this adjustment.
Lr LlKg
Definition of leakage inductance proportion is the ratio of leakage inductance to rotor inductance. If the default value is set to 3.4%, adjust this ratio will affect the motor leakage inductance parameter to be changed. When the adjustment of leakage inductance proportion is larger or smaller, it will cause the motor jittering with abnormal noise and the motor cannot run. Generally, the adjusted value is 3.0%~5.0%. 4.0% is the universal adjustment value that can make the motor run normally. The adjustment of leakage inductance proportion depends on the motor rating.
Printedleakageinductanceproportionformula: ξ = Llkg / Lr. Sourceprose definesratioofleakageinductancetorotorinductance;3.4%example,3.0%–5.0%adjustment and4.0%universalstatement retained as suppliertext, notgeneralengineeringapproval.
Motor2parameters andmotor1leakageinductance. Motor2modefixedtoV/F.
02-22 / Rated rotation speed of motor 2 — PDF page 244
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-22 | Rated rotation speed of motor 2 |
| 2 | Range | 0~ 60000 rpm |
02- 23 / Rated voltage of motor 2 — PDF page 244
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02- 23 | Rated voltage of motor 2 |
| 2 | Range | 200V: 50.0~240.0 V 400V: 100.0~480.0 V 575V: 150.0~670.0 V 690V: 200.0~804.0 V |
02- 24 / Rated power of motor 2 — PDF page 244
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02- 24 | Rated power of motor 2 |
| 2 | Range | 0.01~600.00 kW |
02-25 / Rated frequency of motor 2 — PDF page 244
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-25 | Rated frequency of motor 2 |
| 2 | Range | 4.8~599.0 Hz |
02-26 / Pole of motor 2 — PDF page 244
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-26 | Pole of motor 2 |
| 2 | Range | 2~16 |
02-32 / Resistance between wires of motor 2 — PDF page 244
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-32 | Resistance between wires of motor 2 |
| 2 | Range | 0.001~60.000 Ω |
02-33 / Proportion of Motor 1 Leakage Inductance <1> — PDF page 244
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-33 | Proportion of Motor 1 Leakage Inductance <1> |
| 2 | Range | 0.1~15.0 % |
Manual — Motor1slipfrequency,mechanicalloss,andautotune<1>note; sourceexampleformulasliteral. — page 245
Manual reference: physical PDF page 245. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Normally, it is not required to be adjusted. It can be obtained via manual tuning parameter function. Such tuning does not have magnetic function. The default value of motor slip is set to 1 Hz. Motor slip is obtained from the nameplate.
Take 60Hz, 4-pole motor for example, synchronous speed: 1800 4 60 120 120 Pole Frequence N rpm
Rated speed in the nameplate is 1700 rpm, then Hz Slip 67 . 1 60 1700 1800 。
Adjusting motor slip will change the rotor resistance parameter. The motor slip is adjusted depending on the motor performance.
Adjustment range of mechanical loss is 0.0~10.0%. It is enabled only in the speed mode and the speed command being 0. If the speed command is 0 and the shaft will be at slow drift causing to be static incompletely, adjust upwards the range of mechanical loss until the shaft is completely static. Note: After executing auto-tuning, parameters which marked <1> will renew the value. Please refer Group 17: Automatic Tuning Parameters for more detail.
Printedslip example: N =120×Frequency/Pole =120×60/4 =1800rpm. Ratedspeed1700rpm; Slip =(1800−1700)/60 =1.67Hz. Sourceformula retained literally;no reinterpretation of electrical/mechanical slip or corrected denominator.
Motor1slipfrequency,mechanicalloss,andautotune<1>note; sourceexampleformulasliteral.
02-34 / Motor 1 Slip Frequency <1> — PDF page 245
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-34 | Motor 1 Slip Frequency <1> |
| 2 | Range | 0.1~20.0 Hz |
02-37 / Motor Mechanical Loss — PDF page 245
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 02-37 | Motor Mechanical Loss |
| 2 | Range | 0.0~10.0 % |
Manual — 03-00to03-07,S1toS8sharedfunctioncatalogue0–40; continues247. — page 246
Manual reference: physical PDF page 246. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03- External Digital Input and Output Parameters
03-00to03-07,S1toS8sharedfunctioncatalogue0–40; continues247.
03-00 / Multi-function terminal function setting – S1 — PDF page 246
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-00 | Multi-function terminal function setting – S1 |
| 2 | 03-01 | Multi-function terminal function setting – S2 |
| 3 | 03-02 | Multi-function terminal function setting – S3 |
| 4 | 03-03 | Multi-function terminal function setting – S4 |
| 5 | 03-04 | Multi-function terminal function setting – S5 |
| 6 | 03-05 | Multi-function terminal function setting – S6 |
| 7 | 03-06 | Multi-function terminal function setting – S7 |
| 8 | 03-07 | Multi-function terminal function setting – S8 |
| 9 | Range | 0: 2-Wire sequence (ON: Forward run command) 1: 2-Wire sequence (ON: Reverse run command) 2: Multi-speed/position setting command 1 3: Multi-speed/position setting command 2 4: Multi-speed/position setting command 3 5: Multi-speed/position setting command 4 6: Forward jog run command 7: Reverse jog run command 8: UP frequency increasing command 9: DOWN frequency decreasing command 10: Acceleration/deceleration time selection 1 11: Inhibit Acceleration/deceleration Command 12: Main/ Alternative Run Switch Function 13: Main/ Alternative Frequency Switch Function 14: Emergency stop (decelerate to zero and stop) 15: External Baseblock Command(rotation freely to stop) 16: PID control disable 17: Fault reset (RESET) 18: Reserved 19: Speed Search 1 (from the maximum frequency) 20: Manual energy saving function 21: PID integral reset 22~23: Reserved 24: PLC input 25: External fault 26: 3-Wire sequence (Forward/Reverse command) 27: Local/Remote selection 28: Remote mode selection 29: Jog frequency selection 30: Acceleration/deceleration time selection 2 31: Inverter overheating warning 32: Sync command 33: DC braking 34: Speed Search 2 (from the frequency command) 35: Time function input 36: PID Soft start disabled 37: Traversing operation 38: Upper Deviation of traverse operation 39: Lower Deviation of traverse operation 40: Switching between motor 1/motor 2 |
Manual — SharedS1toS8functioncatalogue41–69 continued from246; diagram248alreadyreviewed andpreserved. — page 247
Manual reference: physical PDF page 247. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Refer to the multi-function digital input and related parameters in the following figure 4.4.16.
SharedS1toS8functioncatalogue41–69 continued from246; diagram248alreadyreviewed andpreserved.
/ 41: PID Sleep 42: PG disable 43: PG integral reset 44: Mode switching between speed and torque 45: Negative torque command 46: Zero-Servo Command 47: Fire Mode (Forced Operation mode) 48: KEB acceleration 49: Parameter writing allowable 50: Unattended Start Protection (USP) 51: Mode switching between speed and position 52: Multi Position Reference Enable 53: 2-Wire Self Holding Mode (Stop Command) 54: Reserved 55: RTC Time Enable 56: RTC Offset Enable 57: Reserved 58: Safety Function 59: Reserved 60: Reserved 61: Reserved 62: EPS Function 63: Reserved 64: Reserved 65: Short-circuit breaking 66: PID Disabled 2 67: Manual Pulse Generator Mode Switch 68: External Fault 2 69: External Overload — PDF page 247
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | ⟦blank source cell⟧ | 41: PID Sleep 42: PG disable 43: PG integral reset 44: Mode switching between speed and torque 45: Negative torque command 46: Zero-Servo Command 47: Fire Mode (Forced Operation mode) 48: KEB acceleration 49: Parameter writing allowable 50: Unattended Start Protection (USP) 51: Mode switching between speed and position 52: Multi Position Reference Enable 53: 2-Wire Self Holding Mode (Stop Command) 54: Reserved 55: RTC Time Enable 56: RTC Offset Enable 57: Reserved 58: Safety Function 59: Reserved 60: Reserved 61: Reserved 62: EPS Function 63: Reserved 64: Reserved 65: Short-circuit breaking 66: PID Disabled 2 67: Manual Pulse Generator Mode Switch 68: External Fault 2 69: External Overload |
Manual — Figure4.4.16 Multi-function digital input and related parameters — page 248
Manual reference: physical PDF page 248. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter associations transcribed. Complete circuit topology and symbol meanings remain original-only; no parameter function values inferred from this diagram.
Source directly aligns eachSlabel with its parameter; no numeric parameter settings given.
Literal terminal label only.
Input and related parameter — PDF page 248
| Source row | Input label | Related parameter |
|---|---|---|
| 1 | S1 | 03-00 |
| 2 | S2 | 03-01 |
| 3 | S3 | 03-02 |
| 4 | S4 | 03-03 |
| 5 | S5 | 03-04 |
| 6 | S6 | 03-05 |
| 7 | S7 | 03-06 |
| 8 | S8 | 03-07 |
Other printed label — PDF page 248
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Common-side label | 24VG |
Manual — Table4.4.27digitalinputfunctions0–20. OEnable,XDisable; sevencontrolmodes preserved separately. — page 249
Manual reference: physical PDF page 249. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.27 Multi-function digital input setting (03-00 to 03-07) (“O”: Enable, “X”: Disable)
Table4.4.27digitalinputfunctions0–20. OEnable,XDisable; sevencontrolmodes preserved separately.
Value / Function / Description / Control mode — PDF page 249
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Value | Function | Function | Description | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Value | Name | LCD Display | Description | V/F | V/F+ PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 0 | 2-wire type (Forward operation) | 2-Wire (FWD-RUN) | 2- wire (ON : Forward operation command). | O | O | O | O | O | O | O |
| 4 | 1 | 2-wire type (Reverse operation) | 2-Wire (REV-RUN) | 2- wire (ON : Reverse operation command). | O | O | O | O | O | O | O |
| 5 | 2 | Multi-speed/positio n setting command 1 | Muti-Spd/Pos Ref 1 | Multi-Speed Reference /Position Reference 1 | O | O | O | O | O | O | O |
| 6 | 3 | Multi-speed/positio n setting command 2 | Muti-Spd/Pos Ref 2 | Multi-Speed Reference /Position Reference 2 | O | O | O | O | O | O | O |
| 7 | 4 | Multi-speed/positio n setting command 3 | Muti-Spd/Pos Ref 3 | Multi-speed Reference /Position Reference 3 | O | O | O | O | O | O | O |
| 8 | 5 | Multi-speed/positio n setting command 4 | Muti-Spd/Pos Ref 4 | Multi-speed Reference /Position Reference 4 | O | O | O | O | O | O | O |
| 9 | 6 | Forward jog run command | FJOG | ON: Forward operation in jog mode (00-18). | O | O | O | O | O | O | O |
| 10 | 7 | Reverse jog run command | RJOG | ON: Reverse operation in jog mode (00-18). | O | O | O | O | O | O | O |
| 11 | 8 | UP frequency increasing command | UP command | ON: Command of output frequency increasing (only used by support of DOWN command). | O | O | O | O | O | O | O |
| 12 | 9 | DOWN frequency decreasing command | DOWN command | ON: Command of output frequency decreasing (only used by support of UP command). | O | O | O | O | O | O | O |
| 13 | 10 | Acceleration/decel eration time selection 1 | Acc/Decel Time Selection 1 | Acceleration/deceleration time selection command 1 | O | O | O | O | O | O | O |
| 14 | 11 | Acceleration/decel eration Inhibition Command | ACC/DEC Inhibit | ON: Acceleration/ deceleration prohibition | O | O | O | O | O | O | O |
| 15 | 12 | Main/ Alternative Run Switch Function | Run Change Sel | Run Command Source is set in parameter of alternative frequency command (00-03) | O | O | O | O | O | O | O |
| 16 | 13 | Main/ Alternative Frequency Switch Function | Freq Change Sel | Frequency Command Source is set in parameter of alternative frequency command (00-06) | O | O | O | O | O | O | O |
| 17 | 14 | Emergency stop (decelerate to zero and stop) | E-Stop | ON: Emergency stop input | O | O | O | O | O | O | O |
| 18 | 15 | External baseblock command (rotation freely to stop | Ext. BB | ON: Inverter base interdiction | O | O | O | O | O | O | O |
| 19 | 16 | PID control disabled | PID Disable | ON: PID control disabled | O | O | O | O | O | O | O |
| 20 | 17 | Fault reset | Fault Reset | Fault reset | O | O | O | O | O | O | O |
| 21 | 18 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 22 | 19 | Speed Search 1 (from the maximum frequency) | Speed Search 1 | ON: Search the speed from the maximum output frequency | O | O | O | O | O | X | O |
| 23 | 20 | Manual energy saving function | Energy saving | ON: Manual energy saving control is based on the settings of 11-12 and 11-18. | O | O | X | X | X | X | X |
Manual — Table4.4.27continued21–38; source missing terminalidentifier in26description retained. — page 250
Manual reference: physical PDF page 250. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table4.4.27continued21–38; source missing terminalidentifier in26description retained.
Adjacent source context — repeated to preserve continuation:
Value / Function / Description / Control mode — PDF page 250
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Value | Function | Function | Description | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Value | Name | LCD Display | Description | V/F | V/F+ PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 21 | PID integral reset | PID I-Reset | ON: PID integral value reset | O | O | O | O | O | O | O |
| 4 | 22 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 5 | 23 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 6 | 24 | PLC input | PLC Input | ON: Digital PLC input | O | O | O | O | O | O | O |
| 7 | 25 | External fault | Ext. Fault | ON: External fault alarm | O | O | O | O | O | O | O |
| 8 | 26 | 3-Wire sequence (Forward/Reverse command) | 3-Wire (FWD/REV) | 3-wire control (forward/reverse command). ON: Reverse; OFF: Forward. When the parameter is set to 26, terminal S1 and terminal will become operation command and stop command respectively, and their original functions will be closed. | O | O | O | O | O | O | O |
| 9 | 27 | Local/Remote selection | Local/Remote | ON: Local mode (via the digital operator) OFF: Frequency command and operation command will be determined according to the setting of parameter (00-02 and 00-05). | O | O | O | O | O | O | O |
| 10 | 28 | Remote mode selection | Remote Mode Sel | ON: RS-485 communication OFF: Control circuit terminal | O | O | O | O | O | O | O |
| 11 | 29 | Jog frequency Selection | JOG Freq sel | ON: Select jog frequency command | O | O | O | O | O | O | O |
| 12 | 30 | Acceleration/decel eration time selection 2 | Acc/Decel Time Selection 2 | Acceleration/ deceleration time selection command 2 | O | O | O | O | O | O | O |
| 13 | 31 | Inverter overheating warning | Overheat Alarm | ON: Inverter overheat alarm (OH2) input ( will display OH2) | O | O | O | O | O | O | O |
| 14 | 32 | Sync command | Sync Command | ON: Synchronous speed start OFF: Synchronous speed close (Start other frequency command). | O | O | O | O | O | O | O |
| 15 | 33 | DC braking | DC Brake Command | ON: Perform DC braking | O | O | O | O | X | X | O |
| 16 | 34 | Speed Search 2 (from the frequency command) | Speed Search 2 | ON: Search speed from set frequency | O | O | O | O | X | O | O |
| 17 | 35 | Time function input | Time Input | .Set the time function at 03-33, 03-34 .Set the time function output at 03-11, 03-12 | O | O | O | O | O | O | O |
| 18 | 36 | PID Soft start ineffective | PID SFS Disable | ON: PID slow-start off | O | O | O | O | O | O | O |
| 19 | 37 | Traversing operation | Wobble Run | ON: Frequency wobbling operation | O | O | X | X | X | X | O |
| 20 | 38 | Upper Deviation of traverse operation | Upper Dev Run | ON: Upper offset off frequency wobbling | O | O | X | X | X | X | O |
Manual — Table4.4.27continued39–59; firemode/protections andsafetyfunction names are supplierclaims, notcertification. — page 251
Manual reference: physical PDF page 251. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table4.4.27continued39–59; firemode/protections andsafetyfunction names are supplierclaims, notcertification.
Adjacent source context — repeated to preserve continuation:
Value / Function / Description / Control mode — PDF page 251
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Value | Function | Function | Description | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Value | Name | LCD Display | Description | V/F | V/F+ PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 39 | Lower Deviation of traverse operation | Lower Dev Run | ON: Lower offset off frequency wobbling | O | O | X | X | X | X | O |
| 4 | 40 | Switching between motor 1/motor 2 | Motor 2 Switch | ON: Start motor 2 | O | O | O | O | O | O | O |
| 5 | 41 | PID Sleep | PID Sleep | ON: PID Sleep | O | O | O | O | O | O | O |
| 6 | 42 | PG disabled | PG disabled | ON: Speed control without PG | X | O | X | X | X | X | X |
| 7 | 43 | PG integral reset | I-Time Reset | ON: Integral value reset of speed control with PG | X | O | X | O | O | X | X |
| 8 | 44 | Mode switching between speed and torque | Speed/Torque change | ON: Torque control mode | X | X | X | O | O | X | X |
| 9 | 45 | Negative torque command | Reverse Tref | ON: Reverse external torque command | X | X | X | O | O | X | X |
| 10 | 46 | Zero-servo command | Zero-Servo | ON: Zero-servo operation | X | X | X | O | O | X | X |
| 11 | 47 | Fire Mode | Fire Mode | ON: Turn off hardware and software fault or alarm protection and run the inverter with value of 01-02 (a special application of HVAC) | O | O | O | O | O | O | O |
| 12 | 48 | KEB acceleration | KEB Accel. | ON: KEB acceleration start | O | O | X | X | X | X | O |
| 13 | 49 | Parameters writing allowable | Write Enabled | ON: all parameters are writable OFF: Except reference frequency (00-05) all parameters are write-protected. | O | O | O | O | O | O | O |
| 14 | 50 | Unattended Start Protection (USP) | USP | ON: After power is input, the inverter ignores the operation command OFF: After power is input, the inverter will return the operation status before power is cut off. | O | O | O | O | O | O | O |
| 15 | 51 | Mode switching between speed and position | Multi Pos. Switch | ON: Switch to position mode OFF: Switch to speed mode | X | X | X | O | O | X | X |
| 16 | 52 | Multi Position Reference Enable | Multi Pos. Enable | ON: Position reference is enabled. OFF: Position reference is disabled. | X | X | X | O | O | X | X |
| 17 | 53 | 2-Wire Self Holding Mode (Stop Command) | 2-Wire (STOP) | 2-Wire Self Holding Mode ( ON: Stop Command). | O | O | O | O | O | O | O |
| 18 | 54 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 19 | 55 | RTC Time Enable | RTC Timer Switch | ON:RTC Time Function Enabled | O | O | O | O | O | O | O |
| 20 | 56 | RTC Offset Enable | Offset Time Switch | ON:RTC Offset Enable | O | O | O | O | O | O | O |
| 21 | 57 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 22 | 58 | Safety Function | Safety Function | ON: Stop by the setting of 08-30 | O | O | O | O | O | O | O |
| 23 | 59 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
Manual — Table4.4.27continued60–69 anddigitalinputdescriptions. PM/SVmode restrictions retained. — page 252
Manual reference: physical PDF page 252. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-0X =00: 2-wire control: forward operation 03-0X =01: 2-wire control: reverse operation. Refer to the 2-wire operation mode in Figure 4.4.1. 03-0X =02: Multi-speed/position setting command 1. 03-0X =03: Multi-speed/position setting command 2. 03-0X =04: Multi-speed/position setting command 3. 03-0X =05: Multi-speed/position setting command 4 (setting =05). Select frequency reference using multi-function digital input. In SV or PMSV mode (00-00=3, 4), with 03-00~07 set to 51, multi-speed command can be used to select multiple segment positions. 03-0X =29: Jog frequency selection (setting =29). Select frequency reference using the multi-function digital input. In SV or PMSV mode (00-00=3, 4), with 03-00~07 set to 51, multi-speed command can be used to select multiple segment positions.
Table4.4.27continued60–69 anddigitalinputdescriptions. PM/SVmode restrictions retained.
Value / Function / Description / Control mode — PDF page 252
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Value | Function | Function | Description | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Value | Name | LCD Display | Description | V/F | V/F+ PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 60 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 4 | 61 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 5 | 62 | EPS function | EPS Input | ON:EPS input | X | X | X | O | O | X | X |
| 6 | 63 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 7 | 64 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 8 | 65 | Short-circuit breaking | SC Brk | ON: SC Brk turn on | X | X | X | X | X | O | X |
| 9 | 66 | PID Disabled 2 | PID Disable 2 | ON: PID control function is disabled and the last frequency integral is remembered. | O | O | O | O | O | O | O |
| 10 | 67 | Manual Pulse Generator Mode Switch | HMPG Mode Switch | ON: in general mode, the frequency command is input from analog input AI1 OFF: Manual Pulse Generator Mode | O | X | X | X | X | X | X |
| 11 | 68 | External Fault 2 | Ext. Fault 2 | ON: the alarm of external Fault | O | O | O | O | O | O | O |
| 12 | 69 | External Overload | Ext. Overload | ON: the input of external overload | O | O | O | O | O | O | O |
Manual — Table4.4.28multispeedselection,17speedrows andthreefootnotes; binaryinputstates andpriority retained. — page 253
Manual reference: physical PDF page 253. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.28 Multi-speed operation selection
0: OFF, 1: ON, -: Ignore 1. Jog frequency terminal has a higher priority than multi-speed reference 1 to 4. 2. When parameter 00-05=0 (frequency reference input = digital operator), multi-speed frequency 1 will be set by 05-01 frequency reference setting1). When parameter 00-05=1 (frequency reference input=control circuit terminal), multi-speed frequency command 1 is input through analog command terminal AI1 or AI2). *3. Default setting of analog input (AI2) is auxiliary frequency. When 04-05≠0, multi-speed frequency reference is set by 05-02. When PID control mode 10-03=xxx1b (PID Enable), even though 03-00~03-07=16 (PID Control Disable), the auxiliary frequency cannot be switched.
Table4.4.28multispeedselection,17speedrows andthreefootnotes; binaryinputstates andpriority retained.
Speed / Multi-function digital input (S1 to S8) / Frequency selection — PDF page 253
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Speed | Multi-function digital input (S1 to S8) | Multi-function digital input (S1 to S8) | Multi-function digital input (S1 to S8) | Multi-function digital input (S1 to S8) | Multi-function digital input (S1 to S8) | Frequency selection |
| 2 | Speed | Jog frequency reference | Multi-speed frequency 4 | Multi-speed frequency 3 | Multi-speed frequency 2 | Multi-speed frequency 1 | Frequency selection |
| 3 | 1 | 0 | 0 | 0 | 0 | 0 | Frequency command 0( 05-01) or main speed frequency *2 |
| 4 | 2 | 0 | 0 | 0 | 0 | 1 | Auxiliary speed frequency (04-05 = 0) or frequency reference 1 ( 05-02) *3 |
| 5 | 3 | 0 | 0 | 0 | 1 | 0 | Frequency command 2 ( 05-03) |
| 6 | 4 | 0 | 0 | 0 | 1 | 1 | Frequency command 3 ( 05-04) |
| 7 | 5 | 0 | 0 | 1 | 0 | 0 | Frequency command 4 ( 05-05) |
| 8 | 6 | 0 | 0 | 1 | 0 | 1 | Frequency command 5 ( 05-06) |
| 9 | 7 | 0 | 0 | 1 | 1 | 0 | Frequency command 6 ( 05-07) |
| 10 | 8 | 0 | 0 | 1 | 1 | 1 | Frequency command 7 ( 05-08) |
| 11 | 9 | 0 | 1 | 0 | 0 | 0 | Frequency command 8 ( 05-09) |
| 12 | 10 | 0 | 1 | 0 | 0 | 1 | Frequency command 9 ( 05-10) |
| 13 | 11 | 0 | 1 | 0 | 1 | 0 | Frequency command 10( 05-11) |
| 14 | 12 | 0 | 1 | 0 | 1 | 1 | Frequency command 11 ( 05-12) |
| 15 | 13 | 0 | 1 | 1 | 0 | 0 | Frequency command 12 ( 05-13) |
| 16 | 14 | 0 | 1 | 1 | 0 | 1 | Frequency command 13( 05-14) |
| 17 | 15 | 0 | 1 | 1 | 1 | 0 | Frequency command 14 ( 05-15) |
| 18 | 16 | 0 | 1 | 1 | 1 | 1 | Frequency command 15 ( 05-16) |
| 19 | 17 | 1 *1 | ─ | ─ | ─ | ─ | Jog frequency command (00-18) |
Manual — Nine-speed wiringexample andtimingdiagram labels; no inferred netlist or installation validation. — page 254
Manual reference: physical PDF page 254. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Wiring Example: Figure 4.4.17 and 4.4.18 show an example of a 9-speed operation selection.
Figure 4.4.17 Control Terminal Wiring Example
Figure 4.4.18: 9-speed timing diagram 1. When 00-05=1, multi-speed frequency reference is set by analog input AI1 or AI2. When 00-05=0, multi-speed frequency reference is set by 05-01. 2. When 04-05=0, multi-speed frequency reference is set by Auxiliary frequency (AI2). When 04-05≠0, multi-speed frequency reference is set by 05-02.
Figure4.4.17ControlTerminalWiringExample. S1ForwardRun/Stop(03-00=0);S2ReverseRun/Stop(03-01=1);S3ExternalFault(03-02=25);S4FaultReset(03-03=17);S5Multi-StepSpeedRef1(03-04=2);S6Multi-StepSpeedRef2(03-05=3);S7Multi-StepSpeedRef3(03-06=4);S8JogFrequencyReference(03-07=29);24VG. Source switches shown; no inferred connection netlist.
Figure4.4.18nine-speedtimingdiagram. VerticalFrequencyReference,horizontalt. Speed1–8 labels05-01,05-02,05-03,05-04,05-05,05-06,05-07,05-08;speed9=00-18. Firsttwo annotated1masterspeedrefand2aux.speedref. TerminalForwardRUN(S1) highthroughspeeds1–9thenlow. PrintedS5Multi-stepSpeedRef1 states acrossspeeds1–9:0,1,0,1,0,1,0,1,0. S6Ref2:0,0,1,1,0,0,1,1,0. S7Ref3:0,0,0,0,1,1,1,1,0. S8JOGFrequencyRef has1during speed9;othersegments drawnlow withnoextra numericlabels. No numericduration/frequencyvalues inferred fromdiagramheight.
Manual — Jog/UP/DOWNoperation,conditions,errors andwiringexample;truth-tablestates preserved. — page 255
Manual reference: physical PDF page 255. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-0X =06: Forward jog run command, uses jog frequency parameter 00-18. Note: Jog command has a higher priority than other frequency reference commands. Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms. 03-0X =07: Reverse jog run command, uses jog frequency parameter 00-18. Note: Jog command has a higher priority than other frequency reference commands. Jog command uses stop mode set in parameter 07-09 when Jog command is active > 500ms. 03-0X =08: UP frequency accelerating command; set parameter 00-05 Frequency command to 2 to activate. 03-0X =09: Down frequency decelerating command; set parameter 00-05 Frequency command to 2 to activate. Note: The inverter operates the variation of increasing/ decreasing output frequency via keypad (refer to parameter 11-56) / external multi-function digital input (terminal S1to S8) when the motor is running. It is required to use two terminals to run UP/ DOWN command when the inverter runs this command via the external multi-function digital input terminal and 00-02=1 (external terminals) & 00-05=2 (terminal command UP/DOWN) & 03-00~03-07=8 (UP command)/ 9 (DOWN command). The inverter output frequency runs UP/ DOWN command with the setting of acceleration/ deceleration time. . Note: SE02 DI terminal Error will be displayed when: - Only the UP or DOWN command function is set. - Both UP command and Inhibit Acceleration/deceleration command are activated simultaneously. - Both DOWN command and Inhibit Acceleration/deceleration command are activated simultaneously. For the examples of UP/DOWN control wiring and operation, please refer to figure 4.4.19 and 4.4.20.
24VG
S1
S5
S6
Forward Run
Up command
Down command
1: ON, 0: OFF
( 03-00 = 0 )
( 03-04 = 08 )
( 03-05 = 09 )
Figure 4.4.19 UP/DOWN wiring and operation example
Figure4.4.19UP/DOWNwiringexamplelabels:S1ForwardRun(03-00=0);S5Upcommand(03-04=08);S6Downcommand(03-05=09);24VG. Nativeadjacenttruthtable retainedseparately,1ON/0OFF. No inferred wiringapproval.
Jog/UP/DOWNoperation,conditions,errors andwiringexample;truth-tablestates preserved.
UP Command (terminal S5) / 1 / 0 — PDF page 255
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | UP Command (terminal S5) | 1 | 0 | 0 | 1 |
| 2 | DOWN Command (terminal S6) | 0 | 1 | 0 | 1 |
| 3 | Operation Status | Accel (UP) | Decel (DWN) | Hold | Hold |
Manual — UP/DOWN command retention and acceleration/deceleration inhibition. — page 256
Manual reference: physical PDF page 256. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Figure 4.4.20 Up / Down command timing diagram UP / DOWN Command Operation When the Forward Run command is active and the UP or Down command is momentarily activated the inverter will accelerate the motor up to the lower limit of the frequency reference (00-13). When using the UP / Down command, the output frequency is limited to the upper limit of frequency reference (00-12) and the lower limit of frequency reference (00-13). The UP / DOWN command uses acceleration 1 or 2 / deceleration time 1 or 2 for normal operation Tacc1 / Tdec1 (00-14, 00-15) or Tacc2 / Tdec 2 (00-16, 00-17). Refer to parameter 03-40 of UP/ Down frequency width setting for other functions of UP / Down. Frequency reference retention is active when parameter 11-58 is set to 1 and the frequency reference is saved when power is lost and retrieved when power is restored. 1: When 11-58 = 1 and the operation command is active, the output frequency will accelerate to the previously stored frequency command. *2: When 11-58 = 0 and the operation command is active, the output frequency will accelerate to the lower limit of frequency reference (00-13). 03-0X =10: Acceleration/deceleration 1 selection 03-0X =30: Acceleration/deceleration 2 selection Refer to the "multi-function digital input terminals select acceleration / deceleration time” page 4-76. 03-0X =11: Acceleration/deceleration inhibition command (hold command) When acceleration/deceleration inhibition command is active, inverter suspends the motor’s acceleration / deceleration operation and maintains the output frequency at current level. Refer to the record reference frequency (parameter 11-58).
Figure4.4.20 UP/DOWN timing. Traces: Power Supply, Forward Run, Up Command, Down Command, Output Frequency; horizontal t. FUL(00-12) and FLL(00-13); two Hold intervals. Up and Down simultaneous pulse segment holds frequency; following Up-only segment rises, no-command hold, Down-only falls. After power recovery final frequency traces are labelled1 and2, with11-58 conditions in prose. No numeric time or frequency inferred.
Manual — Inhibition retention, main/alternative run and frequency source, emergency stop and baseblock. — page 257
Manual reference: physical PDF page 257. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
1. 11-58 = 1, When acceleration / deceleration inhibition command is activated, the frequency reference is stored even when powering down the inverter. When a run command is given (e.g. run forward) and the acceleration / deceleration inhibit command is active, the inverter will accelerate to the previously stored frequency reference. 2. 11-58 = 0, When acceleration / deceleration inhibition command is ON, the motor suspends at the output frequency which is the frequency reference command. When acceleration / deceleration inhibition command is OFF or inverter stop command is active, the frequency reference command will restore to the pre-set frequency. The output frequency remains at 0 Hz when the stop command and power down reset. Note: If acceleration / deceleration inhibition command is ON before operation, STP0 signal will occur after operation because there is no record reference frequency. Refer to Figure 4.4.21. for an example.
Figure 4.4.21 Acceleration/ deceleration inhibition command operation 03-0X =12: Main/ Alternative Run Switch Function When function terminals conduct, run command source is set in alternative run command (00-03). When functional terminal is set to 27 (Local/ Remote control selection), it will be precedential to main/alternative run switch. 03-0X =13: Main/ Alternative Frequency Switch Function When function terminals conduct, frequency command source is set in alternative frequency command (00-06). When functional terminal is set to 27 (Local/ Remote control selection), it will be precedential to main/alternative frequency switch. When PID function is active(10-03=XXX1B),this function is invalid and main frequency is switched to PID function. When PID function is invalid, Main/ Alternative frequency switch function is valid then. 03-0X =14: Emergency stop (decelerate to zero and stop) Refer to the "deceleration time of emergency stop" of parameter 00-26 03-0X =15: External Baseblock Command (coast to stop) Execute the base block command by the use of ON / OFF way of multi-function digital input terminal, and prohibit
Figure4.4.21 inhibition timing. Power Supply ON/OFF/ON; Forward Run ON/OFF/ON; Inhibit ACC/DEC Command OFF/ON/OFF/ON; Frequency Reference steps downward; Output Frequency has two labelled Hold intervals. Time axes t. Prose separately distinguishes11-58=1 and0 and STP0; no drawn duration converted into time.
Manual — Baseblock operation during run, deceleration and acceleration; fault reset and power-up warning. — page 258
Manual reference: physical PDF page 258. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
the inverter output. During run: When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)", indicating the inverter output is turned off (n indicates the digital input number 1 – 8). Upon removing the base block signal, the motor will run at the frequency reference. If speed search from frequency reference is active the inverter output frequency starts from the frequency reference and searches for the coasting motor speed and continue to operate. If speed search is not active the output frequency starts at 0Hz. During deceleration: When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)", indicating the inverter output is turned off (n indicates the digital input number 1 – 8). Upon removing the base block signal, the motor is stopped or will coast to a stop and the inverter will remains in the stop condition. During acceleration: When an external base block command is activated, the keypad displays "BBn BaseBlock (Sn)", indicating the inverter output is turned off (n indicates the digital input number 1 – 8). Upon removing the base block signal, the motor will run at the frequency reference. If speed search from frequency reference is active the inverter output frequency starts from the frequency reference and searches for the coasting motor speed and continue to operate. If speed search is not active the output frequency starts at 0Hz.
Figure 4.4.22 External base block operation 03-0X =16: PID control disabled. 03-0X =17: Fault reset The output becomes active when the inverter trips on a fault. Upon an inverter fault the inverter output will turn off (base block) and the keypad displays the dedicated fault message. When fault occurs, the following actions can be used to reset the fault: 1. Program one of the multi-function digital inputs (03-00 to 03-07) to 17 (reset fault) and active input. 2. Press the reset key of the digital operator (RESET). 3. Recycle power to the inverter. Important Note: If a run command is active during power-up, the inverter will start running automatically.
Figure4.4.22 external baseblock. Traces Run Command, External Baseblock, Output Frequency; horizontal t. Two Coast to stop labels; Speed search active arrow after first baseblock removal. Second block occurs during deceleration with dotted coasting extension. No inferred numeric timings.
Manual — Digital input functions19–27, three-wire and local/remote conditions. — page 259
Manual reference: physical PDF page 259. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- To reset an active fault the run command has to be removed. 03-0X =19: Speed Search 1 (from the maximum frequency). 03-0X =34: Speed Search 2 (from the frequency command). Refer to the "speed search" function. 03-0X =20: Energy saving enabled Manual energy savings function is set with parameters 11-12 and 11-18. For the manual energy saving operation refer to Figure 4.4.88. 03-0X =21: PID integral reset 03-0X =24: PLC Input It is required to be with the software of Drive Link. PLC software program conducts the ladder diagram editing. When the signal output conducts, it will be transmitted to the inverter to be active. 03-0X =25: External fault Activating the external fault input will turn off the inverter output and the motor will coast to a stop. The keypad displays the external fault message “EFn Ext. Fault (Sn)”, where n is the input terminal number. 03-0X =26: 3-wire sequence (forward / reverse command) When digital input terminals S3~S6 are set to 26, terminals S1 and S2 will be individually changed to run command and sop command. Refer to the 3-wire operation mode in Figure 4.4.2 for details. 03-0X =27: Local / Remote selection. Switch the inverter frequency reference source between Local (keypad) or Remote (control circuit terminals or RS485). Use parameter 00-05 (Main frequency command source selection) and 00-02 (Run command selection) to select the remote source. Note: In 3-wire operation terminal S1 and S2 are reserved for run/stop operation and the Local / Remote function can only be set to digital input terminals S3 to S8 (03-02 to 03-07). Note: To switch between local and remote the inverter has to be stopped.
Digital input functions19–27, three-wire and local/remote conditions.
Input / Mode / Frequency Reference / Run/Stop Command Source — PDF page 259
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Input | Mode | Frequency Reference / Run/Stop Command Source |
| 2 | ON | Local | - Frequency reference and Run-Stop from keypad. - LEDs SEQ and REF are off. |
| 3 | OFF | Remote | - Frequency reference source selected by parameter 00-05 and Run-Stop source selected by parameter 00-02. - LEDs SEQ and REF are on. |
Manual — Remote mode, PLC input, three-wire, jog and second acceleration/deceleration selection. — page 260
Manual reference: physical PDF page 260. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-0X =28: Remote mode selection Switch between terminal source and communication (RS-422/RS-485) source for frequency reference and operation command. In Remote mode, indicators of SEQ and REF are on; you can use terminals AI1 and AI2 to control the frequency command, and use terminals S1, S2 or communication terminal RS-485 to control the operation command.
Figure 4.4.23 Remote mode operation selection To switch the frequency reference and operation command input between communication RS-485 and control terminals the following parameters have to be set: 1. 00-05=1 (use control terminal AI1 or AI2 as reference frequency source) 2. 00-02=1 (use control terminal S1 or S2 for operation command) 3. Set one of the digital input terminals (03-02 to 03-07) to 28 (Operation selection of remote mode) 03-0X =24: PLC Input It is required to match Drive Link program. Ladder diagram is edited in the PLC program. When the message output is conducted, this message will be sent to the inverter. 03-0X =26: 3-Wire Sequence (Forward/ Reverse Command) When the digital input terminals (S3~S6) is set to 26, terminal S1 and S2 will become the run command and stop command. Refer to Fig.4.4.2. 03-0X =29: Jog Frequency Selection When jog frequency selection is on, the inverter will depend on the parameter 00-18 (jog frequency) as the command. 03-0X =30: Acceleration/ Deceleration Time Selection 2 When accel./ decel. time selection 2 is ON, the inverter will depend on the parameter 00-16 acceleration time 2 and the parameter 00-17 deceleration time 2.
Figure4.4.23 remote selection. Local Mode: Keypad through ON side of selector, set one03-00 to03-07=27; OFF selects Remote Mode. Remote selector set one03-00 to03-07=28: ON RS-422/RS-485 communications; OFF Control circuit terminals. Destination Frequency Reference and Run Command. Prose setup below restricts chosen remote terminal to03-02–03-07; preserve both scopes.
Remote mode, PLC input, three-wire, jog and second acceleration/deceleration selection.
Input / Mode / Frequency Reference / Run/Stop Command Source — PDF page 260
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Input | Mode | Frequency Reference / Run/Stop Command Source |
| 2 | ON | Communication | - Frequency reference and run/stop command control via communication (RS-422/RS-485). |
| 3 | OFF | Terminal | - Frequency reference source from AI1 / AI2 input (00-05=1) and Run-Stop command from terminals S1 / S2 (00-02=1). |
Manual — Overheat warning, sync command, DC braking and timing/PID references. — page 261
Manual reference: physical PDF page 261. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-0X =31: Inverter overheat warning When input is active the inverter displays warning message "OH2" and continues operation. Deactivating the input reverts back to the original display. Warning message does not require resetting the inverter. 03-0X =32: Sync command Selects between frequency reference source from pulse input or frequency reference source selected by parameter 00-05.
Note: - Function is disabled when the Local/Remote selection (25) or Remote mode selection (26) is active. - To switch between local and remote the inverter has to be stopped. 03-0X =33: DC braking When input is active DC-Injection braking is enabled during start and stopping of the inverter. DC Injection braking is disabled when a run or jog command is active. Refer to the DC braking time diagram in Figure 4.4.24. Note: Short-circuit braking command or DC braking command can only be selected. If they are set simultaneously, SE02 error (DI Terminal Error) will occur.
Figure 4.4.24 DC braking timing diagram
03-0X =35: Timing function Refer to the "time function" parameter 03-37 and 03-38. 03-0X =36: PID Soft start disable Refer to the "PID Control" function of PID function parameter group 10. 03-0X =37: Traverse operation
Figure4.4.24 DC braking timing. Run or Jog Command OFF/ON; DC injection Braking Command OFF/ON; Output Frequency. Hatched DC injection Brake before run and after deceleration. Labels01-08(Fmin),07-06(Fdc-inj); arrow text Fout >01-08(Fmin), Fout >07-06(DC-Inj Start Freq.). Time axes t. No current or timing inferred.
Overheat warning, sync command, DC braking and timing/PID references.
Input / Ref. Source / Frequency Reference / Run/Stop Command Source — PDF page 261
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Input | Ref. Source | Frequency Reference / Run/Stop Command Source |
| 2 | ON | Pulse Input | - Frequency reference set by pulse input |
| 3 | OFF | Parameter 00-05 | - Frequency reference source selected by parameter 00-05 |
Manual — Traverse, motor selection, PG, torque, fire, KEB and parameter-write functions. — page 262
Manual reference: physical PDF page 262. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-0X =38: Upper Deviation of traverse operation 03-0X =39: Lower Deviation of traverse operation See “Wobble Frequency” function in parameter group 19 03-0X =40: Switching between motor 1 and motor 2 03-0X =41: PID Sleep Set parameter 10-29 to 2 (active by DI) and refer to the descriptions of parameters 10-17~10-20. 03-0X =42: PG disable When input is active PG feedback is disabled and speed control is set to V/F control. 03-0X =43: PG integral reset When input is active, reset PG speed control integral accumulator. Note: Only applies to closed loop control modes. 03-0X =44: Mode switching between speed and torque Active in SV (sensor vector control mode). When input is active switch control between speed and control mode. Refer to parameter group 21 for more information.
03-0X =45: Negative torque command When input is active reverses torque reference command. Refer to Figure 4.4.128 for more details. 03-0X =46: Zero-servo Command; Start: zero-servo operation. When input is active starts zero-servo operation. Refer to Figure 4.4.129 for more details. 03-0X =47: Fire mode When input is active disables all inverter warning and hardware protections. This function is commonly used in commercial applications where the inverter controls an exhaust fan and needs run to destruction in case of a fire. 03-0X =48: KEB acceleration When input is active enables KEB (Kinetic Energy Braking) during acceleration. Refer to the parameter description of 11-47 and 11-48. Note: To enable set parameter 11-47 to a value greater than 0. 03-0X =49: Parameters write-in allowed When input is active allows parameter to be changed. Note: When none of the digital input terminals are set to function 49, parameter write-in protection is controlled by parameter 13-06.
Traverse, motor selection, PG, torque, fire, KEB and parameter-write functions.
Input / Control — PDF page 262
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Input | Control |
| 2 | ON | Torque Control |
| 3 | OFF | Speed Control |
Input / Parameter Save — PDF page 262
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Input | Parameter Save |
| 2 | ON | Parameters Write Enabled |
| 3 | OFF | Parameters Write Protected |
Manual — Unattended-start protection, position, RTC, safety, EPS and short-circuit braking. — page 263
Manual reference: physical PDF page 263. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-0X =50: Unattended Start Protection (USP) When input is active prevents inverter from starting automatically when a run command is present at time of power-up. Please refer to Figure 4.4.24a for more details.
Figure 4.4.24a Unattended Start Protection 03-0X =51: Mode switching between speed and position control. Refer to the parameter description of 21-09 ~ 21-41
03-0X =52: Multi Position Reference Enable Refer to the parameter description of 21-09~21-41 03-0X =53: 2-Wire Self-holding Mode (Stop Command) Refer to parameter description of 00-02 (2-wire operation with self-holding function) 03-0X =55: RTC Time Enable When 16-13 (RTC timer function) = 2 (DI setting) and RTC Time Enable is ON, RTC timer function is enabled. 03-0X =56: RTC Offset Enable When 16-30 (Selection of RTC Offset) = 2 (DI setting) and RTC Offset Enable is ON, the inverter will run depending on RTC offset time setting (16-31). 03-0X =58: Safety function When safety function is on, the inverter will stop depending on the setting of 08-30 after the digital terminal is active. 03-0X =62: EPS function EPS input is valid when low voltage activate. Please refer to page 4-84 03-0X =65: Short-circuit braking To stop inverter by turning on Short-circuit braking with setting terminal. If executing run command or jog command, short-circuit braking command will erased and start to run. The following picture is short-circuit braking time process.
Figure4.4.24a Unattended Start Protection. Traces Power Supply, Run Command, Fault(Alarm), Fault Reset, UPS Command, Output Frequency; t axes. Captions literally use UPS: active on power-up, warning clears when run command removed; not active, after fault reset inverter restarts automatically; when run command off at power-up and UPS active inverter starts normally. Section title uses USP. Three illustrated scenarios remain separate.
Unattended-start protection, position, RTC, safety, EPS and short-circuit braking.
Input / Control — PDF page 263
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Input | Control |
| 2 | ON | Position Control |
| 3 | OFF | Speed Control |
Manual — Short-circuit braking, PID Disabled2 and MPG action sequence. — page 264
Manual reference: physical PDF page 264. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Short-circuit braking command or DC braking command can only be selected. If they are set simultaneously, SE02 error (DI Terminal Error) will occur.
03-0X =66: PID Disabled 2 When PID is disabled, the main frequency command source (00-05) is active; when PID is enabled, the previous frequency command is integrated and PID mode is active. 03-0X =67: Manual Pulse Generator Mode Switch When 00-32=8 (HMPG), MPG switch mode is enabled. The frequency command in general mode runs depending on analog input AI1 and that in MPG mode runs depending on pulse input. Please refer to the following diagram for further descriptions.
Descriptions of MPG action sequence number: ‧ 1: When run command starts, the injection current is determined by parameter 07-46 during the braking action from DC current injection motor. When run command is canceled, DC current injection stops. ‧ 2: When MPG speed is higher than the minimum output frequency of motor 1 (parameter 01-08), the inverter starts output frequency by V/f curve. If the output torque is inadequate, please set up the V/f cure parameters of 01-06、01-07、01-08、01-09. ‧ 3: When MPG speed is higher than the speed command limit of parameter 20-44, the inverter output
Short-circuit braking timing. Run Command(or Jog Command), Short Circuit Braking Command and Output Frequency; OFF/ON; t axes. Hatched Short Circuit Brake regions before run and after deceleration. Start label01-08(Fmin); ending threshold text The larger of01-08 or07-06. No engineering validation.
MPG action sequence graph. Upper bands left-to-right1,2,3,2,4,1; lower MPG Speed versus Time. Dashed thresholds20-44 and01-08; final deceleration span00-17. Speed curve rises above01-08, reaches20-44 plateau, drops below20-44, then decelerates to01-08 before falling to zero. Source numbered descriptions on264–265 retained; no invented numeric speeds/durations.
Manual — MPG action sequence continued; basic application parameter-setting flow chart. — page 265
Manual reference: physical PDF page 265. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
frequency will be limited to the set rotation speed by parameter 20-44. ‧ 4: When MPG stops running (stop pulse input), the motor speed will start to decelerate depending on the set value of deceleration time 2 (parameter 00-17). When the motor speed is lower than the minimum output frequency of motor 1, the motor will start DC current injection brake action. Note: When MPG generates pulse input to PG card, the speed command will be calculated. Then, the speed command is multiplied by the speed magnification (parameter 20-43). It is filtered by the set ASR delay time (parameter 20-08). Selection of PG rotation direction (Parameters 20-28) can be set to determine if the MPG and the motor rotation are in the same direction. Note: When V/f curve parameters 01-06, 01-07, 01-08 and 01-09 are adjusted, it is necessary to note the inverter output current (parameter 12-18) to avoid all kinds of fault conditions leading to possible industrial safety accidents. Please refer to the following flow chart for the Parameter Setting:
MPG application basic parameter-setting flow. Application Selection00-32=8 -> following parameters loaded into default values:00-02 External Terminal;00-05 Manual Pulse Generator(MPG);00-16 Acceleration Time2;00-17 Deceleration Time2;01-00 V/f Curve;03-07 Operating Mode Switching;07-09 Stop Mode Selection;07-18 Minimum bb Time;08-00 Stall Prevention Function;11-62 Oscillation Prevention Selection;20-08 ASR Delay Time;20-27 PG Pulse Number. Next input motor nameplate:02-01 Rated Current,02-03 Rated Speed,02-04 Rated Voltage,02-05 Rated Power,02-06 Rated Frequency,02-07 Number of Motor Poles. Next Perform Motor Auto-tuning:17-00=6 Static Auto-tuning Combination(item4+2+1),17-10=1 Automatic Tuning Start. Names are source labels, unspecified default numeric values not inferred.
Manual — MPG machine-tuning and feeling parameter flow charts; external fault2 and overload. — page 266
Manual reference: physical PDF page 266. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny faint fragments below Mode Selection(DI Input) are unreadable; all readable labels retained.
03-0X =68: External Fault 2 ‧ When an external fault occurs, the external fault 2 input terminal is turned on, the inverter will be turned off and the motor will free run to stop. ‧ If external input terminal S3 is set (03-02 = 68) as external fault, the message “EF3 Ext. Fault (S3)” (EF3) will be displayed. ‧ All eight input terminals (S1 to S8) can be designated as external fault input. 03-0X =69: External Overload, input terminal is normally closed. ‧ When external overload occurs, the external overload input terminal closed, the inverter will be turned off and the motor will decelerate to stop. ‧ If the external input terminal S5 is set (03-04 = 69) to external overload, “TOL Ext. OverLoad” message will
MPG Machine Tuning Parameter Setting flow. Mode Selection(DI Input) branches General Mode:00-14 Acceleration Time1,00-15 Deceleration Time1,04-02 AI1 Gain,04-03 AI1 Bias; Manual Pulse Generator Mode:07-46 DC Injection Current Limit,20-27 PG Pulse Number,20-28 PG Rotation Direction Selection. Branches rejoin Other Adjustment Parameters, modified according to machine operating conditions:01-02 Motor1 Maximum Output Frequency,01-03 Motor1 Maximum Output Voltage,01-06 Motor1 Intermediate Output Frequency1,01-07 Motor1 Intermediate Output Voltage1,01-08 Motor1 Minimum Output Frequency,01-09 Motor1 Minimum Output Voltage,08-00 Stall Prevention Function. Tiny faint fragments below DI Input are unreadable and not transcribed.
MPG Parameter setting for feeling flow:00-17 Deceleration Time2;20-08 ASR Delay Time;20-43 MPG Speed Magnification Calculation;20-44 MPG Speed Command Limit.
Narrow partial scope: faint raster fragments below Mode Selection(DI Input) cannot be read; all readable flow-chart labels and native prose preserved. No fragment reconstructed.
Manual — External overload restrictions; DI scan time and contact polarity; source warning. — page 267
Manual reference: physical PDF page 267. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
be displayed. ‧ To enable the external overload function, the fire mode must be enabled first (08-48 =1), only the external input terminal S5 can be designated as External Overload Input. ‧ Setting the external input terminal as External Overload will set the input terminal as the normally closed, therefore, before setting the external overload function, do not set the operation command from the external terminal, otherwise, it will cause unnecessary damage.
Set the digital input CPU scan time. The digital input signal needs to be present for the minimum scan time to qualify as a valid command. Note: For noisy environments select scan time of 8ms (results in a slower response time).
Parameter 03-09 and 03-10 selects the digital input type between a normally open and a normally closed switch/contact.
s4 s3 s2 s1 1: normally close switch s8 s7 s6 s5 1: normally close switch Example: S1 and S2 wired to a normally closed contact / switch set 03-09=0011.
Do not set the operation command parameter 00-02 to terminal control before setting the digital input type. Failure to comply may cause death or serious injury.
Bit diagram:03-09=0000 has left-to-right s4,s3,s2,s1;03-10=0000 has s8,s7,s6,s5. Each bit0 normally open switch,1 normally close switch. Example below sets03-09=0011 for S1 and S2 normally closed. Source warning retained; no wiring approval.
External overload restrictions; DI scan time and contact polarity; source warning.
03-08 / (S1~S8) DI scan time — PDF page 267
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-08 | (S1~S8) DI scan time |
| 2 | Range | 0: scan time 4ms 1: scan time 8ms |
03-09 / Multi-function terminal S1-S4 type selection — PDF page 267
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-09 | Multi-function terminal S1-S4 type selection |
| 2 | Range | xxx0b: S1 A contact xxx1b: S1 B contact xx0xb: S2 A contact xx1xb: S2 B contact x0xxb: S3 A contact x1xxb: S3 B contact 0xxxb: S4 A contact 1xxxb: S4 B contact |
03-10 / Multi-function terminal S5-S8 type selection — PDF page 267
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-10 | Multi-function terminal S5-S8 type selection |
| 2 | Range | xxx0b: S5 A contact xxx1b: S5 B contact xx0xb: S6 A contact xx1xb: S6 B contact x0xxb: S7 A contact x1xxb: S7 B contact 0xxxb: S8 A contact 1xxxb: S8 B contact |
Manual — Relay output parameter range catalogue03-11,03-12,03-20. — page 268
Manual reference: physical PDF page 268. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Relay output parameter range catalogue03-11,03-12,03-20.
03-11 / Relay (R1A-R1C) output — PDF page 268
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-11 | Relay (R1A-R1C) output |
| 2 | 03-12 | Relay (R2A-R2C) output |
| 3 | 03-20 | Relay (R4A-R4C) output |
| 4 | Range | 0: During Running 1: Fault contact output 2: Frequency Agree 3: Setting Frequency Agree (03-13 ± 03-14) 4: Frequency detection 1 (> 03-13, hysteresis range is the setting value of 03-14) 5: Frequency detection 2 (< 03-13, hysteresis range is the setting value of 03-14) 6: Automatic restart 7~8: Reserved 9: Baseblock 10~11: Reserved 12: Over-Torque Detection 13: Current Agree 14: Mechanical Braking Control (03-17~18) 15~17: Reserved 18: PLC status 19: PLC control contact 20: zero speed 21: Inverter Ready 22: Undervoltage Detected 23: Source of operation command 24: Source of frequency command 25: Low torque detected 26: Frequency reference missing 27: Time function output 28: Traverse operation UP status 29: During Traverse operation status 30: Motor 2 selection 31: Zero Speed Servo Status (Position Mode) 32: Communication control contacts 33: RTC Timer 1 34: RTC Timer 2 35: RTC Timer 3 36: RTC Timer 4 37: PID feedback loss detection output 38: Brake release 39: Frequency Detection 1 (dedicated for Crane) 40: Frequency Output 41: Position Agree (Position Mode) 42~44: Reserved 45: PID sleep 46~49: Reserved 50: Frequency Detection 3 (≧ 03-44+03-45) 51: Frequency Detection 4 (≦ 03-44+03-45) 52: Frequency Detection 5 (≧ 03-46+03-47) 53: Frequency Detection 6 (≦ 03-46+03-47) |
Manual — Relay/optocoupler frame mapping; Table4.4.29 output functions0–6. — page 269
Manual reference: physical PDF page 269. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: For frame 1, the DO2 function is setting by 03-12.
Figure 4.4.25 Multi-function digital output and related parameters The following table is the parameter setting in the control board and optical coupler.
Table 4.4.29 Function table of multi-function digital output
Figure4.4.25 multi-function digital output. R1A,R1B,R1C group: default Fault signal, related parameter03-11. R2A,R2C group: default During Running,03-12. Asterisk use DO2/DOG on Frame1. Source contact symbols retained as image, no inferred netlist. Separate table preserves H/C frame1 versus H/C frame2+ and all E/G frames.
Relay/optocoupler frame mapping; Table4.4.29 output functions0–6.
/ 54: Turn on short-circuit braking 57: Low Current Detection 58: Frequency Deceleration Detection 59: Over-Temperature Detection — PDF page 269
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | ⟦blank source cell⟧ | 54: Turn on short-circuit braking 57: Low Current Detection 58: Frequency Deceleration Detection 59: Over-Temperature Detection |
Terminal / Frame 1 ( for H & C type) / Frame 2 and above ( for H & C type) All frame ( for E & G type) — PDF page 269
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Terminal | Frame 1 ( for H & C type) | Frame 2 and above ( for H & C type) All frame ( for E & G type) |
| 2 | R1A-R1C | 03-11=R1A-R1C | 03-11=R1A-R1C |
| 3 | R2A-R2C | none | 03-12=R2A-R2C |
| 4 | D02(PH2) | 03-12=D02(PH2) | none |
| 5 | D01(PH1) | 03-28=D01(PH1) | 03-28=D01(PH1) |
Setting / Function / Contents / Control mode — PDF page 269
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Setting | Function | Function | Contents | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Setting | Name | LCD display | Contents | V/F | V/F + PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 0 | During Running | Running | ON: During running (Run Command is ON) | O | O | O | O | O | O | O |
| 4 | 1 | Fault contact output | Fault | ON: Fault contact output (except CF00 and CF01 ) | O | O | O | O | O | O | O |
| 5 | 2 | Frequency agree | Freq. Agree | ON: frequency agree (frequency agree width detection is set by 03-14 ) | O | O | O | O | O | O | O |
| 6 | 3 | Setting frequency agree | Setting Freq Agree | ON: Output frequency = allowed frequency detection level (03-13) ± frequency bandwidth (03-14) | O | O | O | O | O | O | O |
| 7 | 4 | Frequency detection 1 (> 03-13) | Freq. Detect 1 | ON: Output frequency > 03-13 Hysteresis range is 03-14 | O | O | O | O | O | O | O |
| 8 | 5 | Frequency detection 2 (< 03-13) | Freq. Detect 2 | OFF: Output frequency > 03-13, Hysteresis range is 03-14 | O | O | O | O | O | O | O |
| 9 | 6 | Automatic restart | Auto Restart | ON: the period of automatic restart | O | O | O | O | O | O | O |
Manual — Table4.4.29 output functions7–30 and seven control modes. — page 270
Manual reference: physical PDF page 270. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table4.4.29 output functions7–30 and seven control modes.
Setting / Function / Contents / Control mode — PDF page 270
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Setting | Function | Function | Contents | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Setting | Name | LCD display | Contents | V/F | V/F + PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 7 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 4 | 8 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 5 | 9 | Baseblock | Baseblock | ON: During baseblock | O | O | O | O | O | O | O |
| 6 | 10 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 7 | 11 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 8 | 12 | Over-Torque Detection | Over Torque | ON: Over torque detection is ON | O | O | O | O | O | O | O |
| 9 | 13 | Current Agree | Current Agree | ON: when output current > 03-15 is ON | O | O | O | O | O | O | O |
| 10 | 14 | Mechanical Braking Control (03-17~18) | Mechanical Brake Control | ON: Mechanical braking release frequency OFF: Mechanical braking run frequency | O | O | O | O | O | O | O |
| 11 | 15 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 12 | 16 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 13 | 17 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 14 | 18 | PLC status | PLC statement | ON: when 00-02 is set to 3 (PLC operation command source) | O | O | O | O | O | O | O |
| 15 | 19 | PLC control contact | Control From PLC | ON: Control from PLC | O | O | O | O | O | O | O |
| 16 | 20 | Zero speed | Zero Speed | ON: Output frequency < Minimum output frequency (Fmin) | O | O | O | O | O | O | O |
| 17 | 21 | Inverter Ready | Ready | ON: Inverter ready (after power on, no faults) | O | O | O | O | O | O | O |
| 18 | 22 | Undervoltage Detection | Low Volt Detected | ON: DC bus voltage = < Low-voltage warning detection level (07-13) | O | O | O | O | O | O | O |
| 19 | 23 | Source of operation command | Run Cmd Status | ON: operation command from LED digital operator (local mode) | O | O | O | O | O | O | O |
| 20 | 24 | Source of reference command | Freq Ref Status | ON: reference frequency from LED digital operator (local mode) | O | O | O | O | O | O | O |
| 21 | 25 | Low torque detected | Under Torque | ON: Low-torque detection is ON | O | O | O | O | O | O | O |
| 22 | 26 | Frequency reference missing | Ref. Loss. | ON: Reference frequency loss | O | O | O | O | O | O | O |
| 23 | 27 | Timing function output | Time Output | Set time function parameter to 03-33 and 03-34,and the time function input is set by parameter from 03-00 and 03-07 | O | O | O | O | O | O | O |
| 24 | 28 | Traverse operation UP Status | Traverse UP | ON: in acceleration period (when the wobbling is in operating ) | O | O | X | X | X | X | O |
| 25 | 29 | During Traverse operation status | During Traverse | ON: In the period of frequency wobbling operation (when the wobbling is in operating ) | O | O | X | X | X | X | O |
| 26 | 30 | Select motor 2 | Motor 2 Selection | ON: Switch to motor 2 | O | O | O | O | O | O | O |
Manual — Table4.4.29 output functions31–57; source omits41,55,56. — page 271
Manual reference: physical PDF page 271. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table4.4.29 output functions31–57; source omits41,55,56.
Setting / Function / Contents / Control mode — PDF page 271
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Setting | Function | Function | Contents | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Setting | Name | LCD display | Contents | V/F | V/F + PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 31 | Zero Speed Servo Status (Position Mode) | Zero Servo | ON: Zero servo function is active | X | X | X | O | O | X | X |
| 4 | 32 | Communicatio n control contacts | Control From Communication | ON: Communication control contacts (location:2507H). | O | O | O | O | O | O | O |
| 5 | 33 | RTC Timer 1 | RTC Timer 1 | ON: 16-36 (RTC Speed Selection) selects Timer 1 and 16-32 (Source of Timer 1) is active in the set time. | O | O | O | O | O | O | O |
| 6 | 34 | RTC Timer 2 | RTC Timer 2 | ON: 16-36 (RTC Speed Selection) selects Timer 2 and 16-33 (Source of Timer 2) is active in the set time. | O | O | O | O | O | O | O |
| 7 | 35 | RTC Timer 3 | RTC Timer 3 | ON: 16-36 (RTC Speed Selection) selects Timer 3 and 16-34 (Source of Timer 3) is active in the set time. | O | O | O | O | O | O | O |
| 8 | 36 | RTC Timer 4 | RTC Timer 4 | ON: 16-36 (RTC Speed Selection) selects Timer 4 and 16-35 (Source of Timer 4) is active in the set time. | O | O | O | O | O | O | O |
| 9 | 37 | PID Feedback Loss Detection Output | PID Fbk Loss | ON: PID Feedback Loss | O | O | O | O | O | O | O |
| 10 | 38 | Break Release | Brake Release | ON: Release Brake | X | X | O | O | O | X | X |
| 11 | 39 | Frequency Detection 1 (dedicated for Crane) | Freq. Detect 1 (Dedicated crane) | ON: Output frequency > 03-13, Hysteresis range : 03-14 | O | O | O | X | X | X | X |
| 12 | 40 | Frequency Output | Frequency output Ing | ON: Inverter status is at DC brake, Base Block or stop. | X | X | X | O | X | X | X |
| 13 | 42 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 14 | 43 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 15 | 44 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 16 | 45 | PID sleep | PID Sleep | ON: During PID Sleep | O | O | X | X | X | X | X |
| 17 | 46 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 18 | 47 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 19 | 48 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 20 | 49 | Reserved | Reserved | Reserved | - | - | - | - | - | - | - |
| 21 | 50 | Frequency Detection 3 | Freq. Detect 3 | ON: output frequency > 03-44,Hysteresis range :03-45 | O | O | O | O | O | O | O |
| 22 | 51 | Frequency Detection 4 | Freq. Detect 4 | OFF: output frequency > 03-44,Hysteresis range :03-45 | O | O | O | O | O | O | O |
| 23 | 52 | Frequency Detection 5 | Freq. Detect 5 | ON: output frequency > 03-46,Hysteresis range :03-47 | O | O | O | O | O | O | O |
| 24 | 53 | Frequency Detection 6 | Freq. Detect 6 | OFF: output frequency > 03-46,Hysteresis range :03-47 | O | O | O | O | O | O | O |
| 25 | 54 | Turn on short-circuit braking | SC Brk | ON: Turn on short-circuit braking | X | X | X | X | X | O | X |
| 26 | 57 | Low Current Detection | Low Current Detect | ON: Output Current ≦ 03-48 Low current detection level | O | O | O | O | O | O | O |
Manual — Output functions58–59 and detailed output operation descriptions. — page 272
Manual reference: physical PDF page 272. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-1X=0: During Running
03-1X=1: Fault contact output Output is active during fault condition. Note: Communication error (CF00, CF01) do not activate the fault contact. 03-1X=2: Frequency Agree Output is active when the output frequency falls within the frequency reference minus the frequency detection width (03-14). 03-1X=3: Setting Frequency Agree Output is active when the output frequency falls within the frequency detection width (03-14) of the set frequency detection level (03-13). 03-1X=4: Frequency detection 1 Output is active when the output frequency rises above the frequency detection level (03-13) + frequency detection width (03-14) and deactivates when the output frequency falls below frequency detection level (o3-13). 03-1X=5: Frequency detection 2 Output is active when the output frequency is below the frequency detection level (03-13) + frequency detection width (03-14) and turns off when the output frequency falls below frequency detection level. Refer to table 4.4.30 for the operation of frequency detection. 03-1X=6: Automatic restart. Output is active during an auto-restart operation. 03-1X=9: Baseblock (B.B.) Output is active when the inverter output is turned off during a Baseblock command. 03-1X=12: Over torque detected (Normally Open) Output is active during an over torque detection see parameters 08-13 ~ 08-16. 03-1X=25: Low torque detected (Normally Open) Output is active during low torque detection see parameters 08-17 ~ 08-20. 03-1X=13: Current Agree When output current > 03-15 and output current > 03-15 duration >03-16, it is ON. 03-1X=18: PLC status (setting =18) Output is active when operation command parameter (00-02) is set to 3: PLC Control. 03-1X=19: PLC control contact
Output functions58–59 and detailed output operation descriptions.
Setting / Function / Contents / Control mode — PDF page 272
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Setting | Function | Function | Contents | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Setting | Name | LCD display | Contents | V/F | V/F + PG | SLV | SV | PM SV | PM SLV | SLV 2 |
| 3 | 58 | Frequency Deceleration Detection | Freq. Decel to | ON: Output Frequency < Frequency Command – parameter 03-14 in deceleration | O | O | O | O | O | O | O |
| 4 | 59 | Over-Tempera ture Detection | OH Detect | ON: Heat Sink Temperature >08-46, hysteresis Zone 08-47 | O | O | O | O | O | O | O |
OFF / Run command is OFF and the inverter is stopped. — PDF page 272
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | OFF | Run command is OFF and the inverter is stopped. |
| 2 | ON | Run command is ON or output frequency is greater than 0. |
Manual — Zero-speed and local/remote command-source output descriptions. — page 273
Manual reference: physical PDF page 273. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Output is controlled by the PLC logic 03-1X=20: Zero-speed Output is active during zero-speed
Figure 4.4.26 Zero-speed operation 03-1X=21: Inverter Ready Output is active when no faults are active and the inverter is ready for operation. 03-1X=22: Under voltage Detection Output is active when the DC bus voltage falls below the low voltage detection level (07-13). 03-1X=23: Source of operation command Output is active in local operation command.
03-1X=24: Source of frequency command Output is active in local frequency command.
03-1X=26: Frequency reference missing
Figure4.4.26 zero-speed operation. Output Frequency falls through01-08(Fmin); Zero Speed signal changes OFF toON at dotted crossing; horizontal t. Table includes both <= active and >= off at boundary, preserved without choosing equality behavior.
Zero-speed and local/remote command-source output descriptions.
Active / Output frequency <=minimum output frequency (01-08, Fmin) — PDF page 273
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Active | Output frequency <=minimum output frequency (01-08, Fmin) |
| 2 | Off | Output frequency is>=the minimum output frequency |
OFF / Remote mode: 00-02 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is OFF. SEQ LED of the keypad is ON. — PDF page 273
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | OFF | Remote mode: 00-02 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is OFF. SEQ LED of the keypad is ON. |
| 2 | ON | Local mode: 00-02 = 0, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is active. SEQ LED of the keypad is OFF. |
OFF / Remote mode: 00-05 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is OFF. REF LED of the keypad is ON. — PDF page 273
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | OFF | Remote mode: 00-05 = 1 or 2, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is OFF. REF LED of the keypad is ON. |
| 2 | ON | Local mode: 00-05 = 0, or any one of the multi-function digital input terminals (S1 to S8) set to function 5 (LOCAL / REMOTE control) is active. REF LED of the keypad is OFF. |
Manual — Output-function descriptions and source cross-references. — page 274
Manual reference: physical PDF page 274. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Output is active when the frequency reference is lost. When parameter 11-41 is set to 0 the inverter will decelerate to a stop. When parameter 11-41 is set to 1 operation will continue at the value of parameter 11-42 times the last know frequency reference. 03-1X=27: Time function output Output is controlled by timer function see parameter 03-37 and 03-38. 03-1X=28: Traverse operation UP status Output is controlled by frequency wobbling operation; refer to Parameter group 19 for details. 03-1X=29: During Traverse operation status Output is controlled by the acceleration period or frequency wobbling operation, refer to Parameter group 19 for details. 03-1X=30: Motor 2 selected Output is active when motor 2 is selected. 03-1X=31: Zero Servo Status (Position mode) Output is active when Zero-servo operation is enabled and the load is locked into position. 03-1X=32: Communication control contacts Communication location: 2507H,control by RY3 RY2 RY1.RY3 and RY2 will execute if DO1,DO2 and DO3 all set communication control, and 2507H set 5(101) 03-1X=37: PID Feedback Loss Detection Output When PID feedback loss occurs (refer to the setting of parameters 10-11~10-13), it performs the state of ON. 03-1X=38: Brake Release The state of ON means release brake is active. Refer to parameters 03-41~03-42 for the details. 03-1X=39: Frequency Detection 1 (dedicated for Crane) 03-1X=40: Frequency Output Refer to Table 4.4.30 for the operation of frequency detection. 03-1X=41: Position Agree (Position Mode) Position search is completed at position mode, then ON. 03-1X=45: PID Sleep It will inform when PID sleep ON. 03-1X=50: Frequency Detection 3
Please refer to Table 4.4.9 Frequency detection operation 03-1X=51: Frequency Detection 4
Please refer to Table 4.4.9 Frequency detection operation 03-1X=52: Frequency Detection 5
Please refer to Table 4.4.9 Frequency detection operation 03-1X=53: Frequency Detection 6
Please refer to Table 4.4.30 Frequency detection operation 03-1X=54: Turn on short-circuit braking Output terminal is closed when Turning on short-circuit braking 03-1X=57: Low Current Detection
Manual — Frequency detection level/width ranges and output-terminal context. — page 275
Manual reference: physical PDF page 275. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When output current <=03-48, relay is active. 03-1X=58: Frequency Deceleration Detection When output frequency < frequency command- 03-14 in deceleration, the relay is active. Please refer to Table 4.3.30 Frequency detection operation 03-1X=59: Over Temperature Detection The Heat Sink Temperature > 08-46, the relay is active, the Magnetic Hysteresis Zone is set by 08-47.
Frequency detection Level: set the multi-function output terminals R1A-R1C, R2A-R2C or PH1 (03-11, 03-12 or 03-28) to the desired detection level and bandwidth for use with multi-function output functions 2 to 5. The time charts for the Frequency Agree Detection operation are shown in the following table 4.4.9.
Frequency Detection:Set R1A-R1C、R2A-R2C or PH1 (03-11, 03-12 or 03-28) to output frequency signal and then set frequency confirmation and output frequency detection 1~6. Please refer to table 4.4.30.detection operation of frequency time block
Frequency detection level/width ranges and output-terminal context.
03-13 / Frequency detection Level — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-13 | Frequency detection Level |
| 2 | Set Range | 0.0~599.0 Hz |
03-14 / Frequency detection width — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-14 | Frequency detection width |
| 2 | Range | 0.1~25.5 Hz |
03-44 / Frequency Detection Level 2 — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-44 | Frequency Detection Level 2 |
| 2 | Range | 0.0~599.0 Hz |
03-45 / Frequency Detection Width 2 — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-45 | Frequency Detection Width 2 |
| 2 | Range | 0.1~25.5 Hz |
03-46 / Frequency Detection Level 3 — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-46 | Frequency Detection Level 3 |
| 2 | Range | 0.0~599.0 Hz |
03-47 / Frequency Detection Width 3 — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-47 | Frequency Detection Width 3 |
| 2 | Range | 0.1~25.5 Hz |
03-50 / Frequency Detection Level 4 — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-50 | Frequency Detection Level 4 |
| 2 | Range | 0.0~599.0 Hz |
03-51 / Frequency Detection Level 5 — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-51 | Frequency Detection Level 5 |
| 2 | Range | 0.0~599.0 Hz |
03-52 / Frequency Detection Level 6 — PDF page 275
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-52 | Frequency Detection Level 6 |
| 2 | Range | 0.0~599.0 Hz |
Manual — Table4.4.30 frequency detection timing diagrams and source descriptions, first five rows. — page 276
Manual reference: physical PDF page 276. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.30 Frequency detection operation
Frequency agree timing: Output Frequency, FWD, REV, Freq Reference,03-14 widths, Frequency Agree Signal; time axes; OFF/ON/OFF/ON pulses within indicated bands.
Set frequency agree timing: Output Frequency,FWD,REV,03-13 thresholds,03-14 widths; Setting Frequency Agree Signal,OFF/ON/OFF/ON pulses; time axes.
Output frequency detection1 timing: threshold03-13,width03-14,return threshold03-50 on positive side; negative-side return label is03-13 as actually printed. Output Frequency Detection1 Signal OFF/ON/OFF/ON;time axes. Preserve source asymmetry.
Output frequency detection2 timing: threshold03-13,width03-14,return03-50 on both signs;Output Frequency Detection2 Signal ON/OFF/ON/OFF/ON;time axes.
Output frequency detection3 timing: threshold03-44,width03-45,return03-51 on both signs;graph signal label literally Output Frequency Detection1 Signal although row is detection3. OFF/ON/OFF/ON;time axes.
Table4.4.30 frequency detection timing diagrams and source descriptions, first five rows.
Function / Detection operation of frequency confirmation / Description — PDF page 276
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Function | Detection operation of frequency confirmation | Description |
| 2 | Frequency agree | time time ON OFF FWD REV 03-14 03-14 Freq Reference Output Frequency Frequency Agree Signal ON Freq Reference | Output is active when the output frequency falls within the frequency reference minus the frequency detection width (03-14). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 2 (Frequency agree). |
| 3 | Set frequency agree | time time ON OFF FWD REV 03-14 Output Frequency Setting Frequency Agree Signal ON 03-13 03-13 03-14 | Output is active the output frequency falls within the frequency detection width (03-14) of the set frequency detection level (03-13). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 3 (Set frequency agree). |
| 4 | Output frequency detection 1 | ON ON OFF OFF 03-14 03-14 03-13 03-13 03-50 03-13 time time Output Frequency Output Frequency Detection 1 Signal | Output is active when the output frequency rises above the frequency detection level (03-13) + frequency detection width (03-14) and deactivates when the output frequency falls below frequency detection level 4 (03-50). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 4 (Output frequency detection 1). |
| 5 | Output frequency detection 2 | OFF OFF ON ON 03-14 03-14 03-13 03-13 03-50 03-50 time time Output Frequency Output Frequency Detection 2 Signal ON | Output signal is OFF when the output frequency rises above the frequency detection level (03-13) + frequency detection width (03-14) and turns ON when the output frequency falls below the frequency detection level 4 (03-50). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 5 (Output frequency detection 2). |
| 6 | Output frequency detection 3 | ON ON OFF OFF 03-45 03-45 03-44 03-44 03-51 03-51 time time Output Frequency Output Frequency Detection 1 Signal | Output is active when the output frequency rises above the frequency detection level 2 (03-44) + frequency detection width 2 (03-45) and deactivates when the output frequency falls below frequency detection level 5(03-51). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 50 (Output frequency detection 3). |
Manual — Table4.4.30 detection4–6, crane and frequency-output timing diagrams. — page 277
Manual reference: physical PDF page 277. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Output frequency detection4 timing: threshold03-44,width03-45,return03-51 on both signs;Output Frequency Detection4 Signal ON/OFF/ON/OFF/ON;time axes.
Output frequency detection5 timing: threshold03-46,width03-47,return03-52 on both signs;Output Frequency Detection5 Signal OFF/ON/OFF/ON;time axes.
Output frequency detection6 timing: threshold03-46,width03-47,return03-52 on both signs;Output Frequency Detection6 Signal ON/OFF/ON/OFF/ON;time axes.
Crane detection1 timing: threshold03-13,width03-14,return03-50 on both signs;Output Frequency Detection1 Signal OFF/ON/OFF/ON;time axes. Source acceleration/deceleration conditions remain in adjacent cell.
Frequency Output timing: Run command OFF/ON/OFF;Base Block OFF/ON/OFF;Output Frequency ramp with DC Brake at beginning/end and zero during Base Block. Frequency Output Ing OFF during initial/final DC Brake and Base Block,ON during other output-frequency segments. No output capability or safety validation.
Table4.4.30 detection4–6, crane and frequency-output timing diagrams.
Function / Detection operation of frequency confirmation / Description — PDF page 277
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Function | Detection operation of frequency confirmation | Description |
| 2 | Output frequency detection 4 | OFF OFF ON ON 03-45 03-45 03-44 03-44 03-51 03-51 time time Output Frequency Output Frequency Detection 4 Signal ON | Output signal is OFF when the output frequency rises above the frequency detection level 2 (03-44) + frequency detection width 2 (03-45) and turns ON when the output frequency falls below frequency detection level 5 (03-51). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 51 (Output frequency detection 4). |
| 3 | Output frequency detection 5 | ON ON OFF OFF 03-47 03-47 03-46 03-46 03-52 03-52 time time Output Frequency Output Frequency Detection 5 Signal | Output is active when the output frequency rises above the frequency detection level 3 (03-46) + frequency detection width 3 (03-47) and deactivates when the output frequency falls below frequency detection level 6 (3-52). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 52 (Output frequency detection 5). |
| 4 | Output frequency detection 6 | OFF OFF ON ON 03-47 03-47 03-46 03-46 03-52 03-52 time time Output Frequency Output Frequency Detection 6 Signal ON | Output signal is OFF when the output frequency rises above the frequency detection level 3 (03-46) + frequency detection width 3 (03-47) and turns ON when the output frequency falls below frequency detection level 6 (3-52). Any of the digital outputs function (03-11, 03-12 or 03-28) can be set to 53 (Output frequency detection 6). |
| 5 | Output Frequency Detection 1 (dedicated for Crane) | ON ON OFF OFF 03-14 03-14 03-13 03-13 03-50 03-50 time time Output Frequency Output Frequency Detection 1 Signal | If the output frequency > frequency detection level (03-13) + frequency detection width (03-14) during acceleration, signal of output frequency detection 1 (dedicated for Crane) is ON. If the output frequency < frequency detection level 4 (03-50) during deceleration, signal of output frequency detection 1 (dedicated for Crane) is OFF. Set any parameters 03-11, 03-12 or 03-28 to 39 (output frequency detection – dedicated for Crane). |
| 6 | Frequency Output | DC Brake DC Brake ON ON OFF OFF Output Frequency Frequency Output Ing OFF OFF OFF OFF OFF ON ON Run command Base Block | When the inverter output frequency is active, the output terminal is closed. |
Manual — Frequency-deceleration detection and current-agree ranges/timing. — page 278
Manual reference: physical PDF page 278. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: The Maximum Value of 03-53 will be limited by Setting Value of 03-15 03-11=13, then, When the output current >03-15, relay is active. 03-15: The suggested setting value is 0.1~ the motor rated current. 03-16: The delay time performs depending on the setting value. In addition, when the Output Current is ≤ 03-53, the delay time from ON to OFF in the signal of relay is 100ms (constant). Time Diagram:
Current-agree timing diagram. I:Load current,100%,threshold03-15,horizontal T;03-16 delay from rising threshold crossing to relay ON; Constant100msec from falling threshold crossing to relay OFF. Output labelled03-11 Relay Output. Diagram threshold label03-15 retained separately from adjacent prose OFF threshold03-53.
Frequency Deceleration Detection timing: Output Frequency,FWD,REV,Freq Reference,03-14 width;lower trace literally Frequency Agree Signal,OFF/ON/OFF/ON during indicated deceleration portions;time axes. No inferred absolute-time values.
Frequency-deceleration detection and current-agree ranges/timing.
Function / Detection operation of frequency confirmation / Description — PDF page 278
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Function | Detection operation of frequency confirmation | Description |
| 2 | Frequency Deceleration Detection | time time ON OFF FWD REV 03-14 03-14 Freq Reference Output Frequency Frequency Agree Signal ON Freq Reference OFF | The Output Signal is ON, when the Frequency decelerates and the output frequency is outside the range of Frequency Reference ± Frequency Detection Width (03-14), Set the parameter of 03-11, 03-12 or 03-28 to 58 (Frequency Deceleration Detection). |
03-15 / Current Agree Level — PDF page 278
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-15 | Current Agree Level |
| 2 | Range | 0.1~999.9 A |
| 3 | 03-16 | Delay Time of Current Agree Detection |
| 4 | Range | 0.1~10.0 Sec |
| 5 | 03-53 | Current Agree Level 2 |
| 6 | Range | 0.0~999.9 A |
Manual — Low-current detection and mechanical-braking ranges/timing. — page 279
Manual reference: physical PDF page 279. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
03-11 set to 57: When output current <= 03-48 (Low current detection level), the relay works. When 03-48 set 0.0, low current detection function disabled. If the detection time is bigger than the setting time of 03-49, the relay works. Besides, the relay delay time from ON to OFF is 100ms, and it’s fixed. The timing chart:
When 03-11=14, the real frequency equal to the value of 03-17 (Mechanical Braking Release Level) in acceleration time, the relay output will execute. When 03-11=14, the real frequency equal to the value of 03-18 (Mechanical Braking Level Set) in deceleration time, the relay output will stop execute.
Low-current detection timing. I(Loading current),100%,threshold03-48,horizontal T. Operation Command ON;03-11 Relay ON after03-49 delay. Fixed100msec OFF delay. Later below-threshold interval labelled Smaller than3-49, Relay does not work. Source labels retain3-49 spelling; no computed timing.
Low-current detection and mechanical-braking ranges/timing.
03-48 / Low Current Detection Level — PDF page 279
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-48 | Low Current Detection Level |
| 2 | Range | 【0.0~999.9】 A |
| 3 | 03-49 | Low Current Detection Delay Time |
| 4 | Range | 【0.00~655.34】 Sec |
03-17 / Mechanical Braking Release Level — PDF page 279
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-17 | Mechanical Braking Release Level |
| 2 | Range | 0.00~599 Hz |
03-18 / Mechanical Braking Level Set — PDF page 279
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-18 | Mechanical Braking Level Set |
| 2 | Range | 0.00~599 Hz |
Manual — Mechanical-braking timing for both threshold orderings. — page 280
Manual reference: physical PDF page 280. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When 03-17≤03-18, the timing diagram is as follows:
When 03-17≥03-18, the timing diagram is as follows::
Mechanical-braking graph, source condition03-17≤03-18. Hz versus T;03-18 drawn above03-17. RUN/STOP trace;03-11=14 ON at rising03-17 crossing, OFF at falling03-18 crossing. No numeric thresholds inferred.
Mechanical-braking graph, source condition03-17≥03-18. Hz versus T;03-17 drawn above03-18. RUN/STOP trace;03-11=14 ON at rising03-17 crossing, OFF at falling03-18 crossing. No equality-specific behavior inferred from schematic.
Manual — Relay output polarity and UP/DOWN hold and width — page 281
Manual reference: physical PDF page 281. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter 03-19 selects the digital output type between a normally open and a normally closed contact. Each bit of 03-19 presents an output:
R2 R1 1: normally close contact Example: R1 normally open and R2 normally closed contact set 03-19=xxx01.
03-27=0: When the run command is removed the UP/DOWN frequency reference before deceleration is stored. The next time the run command is applied the output frequency will ramp up to the previously stored frequency reference. 03-27=1: When the run command is removed the UP/DOWN frequency reference command is cleared (set to 0). The next time the run command is applied the output frequency will start at 0. 03-27=2: UP/DOWN command is active when run command is not active. 03-27=3: Keep the state of frequency command not to be cleared. When run command re-sends, press UP/DOWN key before the run frequency reaches the frequency command.
When 03-40 is set to 0 Hz, Up / Down function is maintained. When 03-40 is not set to 0 Hz, frequency command is set by the run frequency plus the setting frequency of 03-40. Example: set terminal S1: 03-00=8 (Up increased frequency command), terminal S2: 03-01=9 (Down decreased frequency command) and 03-40= ΔHz. Mode 1: When 03-40 is set to 0 Hz, Up / Down function is maintained. Refer to Fig. 4.4.20. Mode 2: When 03-40 is not set to 0 Hz and terminals conduction time < 2 Sec, frequency change (ΔHz) at one conduction occurs depending on the setting of 03-40.
03-19 bit illustration: two displayed zero digits have R2 below the left digit and R1 below the right digit. Legend: 0 normally open contact; 1 normally close contact. This order is retained separately from the conflicting xxx01 example.
Relay output polarity and UP/DOWN hold and width
03-19 / Relay (R1A-R2C) type — PDF page 281
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-19 | Relay (R1A-R2C) type |
| 2 | Range | xxx0b: R1 A contact xxx1b: R1 B contact xx0xb: R2 A contact xx1xb: R2 B contact 0xxxb: R4 A contact 1xxxb: R4 B contact |
03-27 / UP/DOWN Frequency Hold/Adjust Selection — PDF page 281
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-27 | UP/DOWN Frequency Hold/Adjust Selection |
| 2 | Range | 0: Hold last set frequency when stopped 1: Set frequency to 0 when stopped 2: Allow speed changes from last set frequency when stopped 3: Refresh frequency at acceleration |
03-40 / Up/Down Frequency Width Setting — PDF page 281
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-40 | Up/Down Frequency Width Setting |
| 2 | Range | 0.00~5.00 Hz |
Manual — UP/DOWN timing and photo-coupler outputs — page 282
Manual reference: physical PDF page 282. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Mode 3: When 03-40 is not set to 0 Hz and terminals conduction time > 2 Sec, frequency changes upon general acceleration/ deceleration.
※Descriptions:
ΔH1: frequency increment setting at acceleration, t1: terminal conduction time at acceleration, ΔH2: frequency increment setting at deceleration, t2: terminal conduction time at deceleration.
UP/DOWN mode 2 timing: vertical Hz axis with upper and lower limits of frequency reference; horizontal T. Three ON pulses on terminal S1 correspond to three rising output-frequency segments; terminal S2 has three ON pulses on the falling segments. ΔHz is labelled between consecutive levels. No numerical interpolation is supplied.
UP/DOWN mode 3 timing: Hz versus T, upper and lower frequency-reference limits, output-frequency trace. Terminal S1 ON spans the initial 2 Sec and t1 before OFF; terminal S2 is initially OFF then ON across 2 Sec and t2. ΔH1 labels acceleration increase, ΔHz the initial decrement, ΔH2 the following deceleration change.
Source formulae: ΔH1 = (Upper Limit Frequency / Acceleration Time 2) × Terminal Conduction Time (t1). ΔH2 = (Upper Limit Frequency / Deceleration Time 2) × Terminal Conduction Time (t2).
UP/DOWN timing and photo-coupler outputs
03- 28 / Photo-coupler Output (DO1-DOG) — PDF page 282
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03- 28 | Photo-coupler Output (DO1-DOG) |
| 2 | 03- 21 | Photo-coupler Output 2(DO2-DOG2) |
| 3 | Range | See function selection list parameter 03-11, 03-12 |
03-29 / Photo-coupler Output Selection (DO1-DOG) — PDF page 282
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-29 | Photo-coupler Output Selection (DO1-DOG) |
| 2 | Range | xxx0b: Photo-coupler A Contact xxx1b: Photo-coupler B Contact 0xxxb: Photo-coupler 2 A Contact 1xxxb: Photo-coupler 2 B Contact |
Manual — General pulse and PWM input — page 283
Manual reference: physical PDF page 283. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
0 = Normally open (A), 1 = Normally closed (B)
There are two ways for pulse input selection: (1) General pulse input: PI= cutoff frequency divided by pulse input scale set by 03-31, corresponding to the maximum output frequency of motor 1 (01-02). Monitoring parameter 12-79 (pulse input percentage) is the proportional relationship between input signal and pulse input scale of 03-31. (2) PWM: It is required to input the correct frequency. PWM= Time of positive edge pulse divided by the time period of pulse, corresponding to the maximum output frequency of motor 1 (01-02). Monitoring parameter 12-79 (pulse input percentage) is the proportional relationship between the positive edge terminal of input signal and time period. Note: Deviation of pulse time period in PWM is ±12.5%. If it is over the deviation range, pulse input is not active. Diagram for pulse input selection:
Pulse-input selection diagrams: 03-30=0 Normal Mode shows Sample Pulse train at PI with T:Period; Frequency = 1 / T:Period. Pulse Input Command = Frequency / Scaling factor (using 03-31) × 100%(01-02). 03-30=1 PWM Mode shows PI pulse train with T:Period and T1:Period; Pulse Input Command = T1:Period / T:Period × 100%(01-02). Diagram labels retained; no waveform interpolation.
General pulse and PWM input
03- 30 / Function setting of pulse input — PDF page 283
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03- 30 | Function setting of pulse input |
| 2 | Range | 0: General Pulse Input 1: PWM |
Manual — Pulse-input scaling, gain, bias, filtering and PID setup — page 284
Manual reference: physical PDF page 284. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Pulse input scaling, 100% = Maximum pulse frequency.
Target value (03-03) in % = Pulse input frequency scaled to 100% based on maximum pulse frequency (03-31) times the gain (03-32) + bias (03-33).
- Refer to section 3.9 control circuit terminals for details. * Refer to figure 4.4.27 for the pulse input specification.
Set Pulse Input Setup as Frequency Reference Set parameter 00-05 to 4 and 03-30 to 0 to use the pulse input terminal PI as the frequency reference source. Refer to Figure 4.3.5. for details. Next set the pulse input scaling (03-31), enter the pulse input frequency to match the maximum output frequency. Adjust the pulse input filter time in case interference or noise is encountered. Example: Pulse train input maximum 10 kHz, set parameter 03-31 to 10000 when maximum frequency is set to 60.0Hz. Set Pulse Input as PID feedback value Set parameter 00-05 to 5, 03-30 to 1 and PID feedback value source 10-01 to 3, to use the pulse input terminal PI as the PID target (setpoint) value. Next set the pulse input scaling (03-31), enter the pulse input frequency to match the maximum output frequency. Adjust the pulse input filter time in case interference or noise is encountered. Refer to Figure 4.4.28.for details. Note: The inverter will display a SE09 "PI setting error" when 03-30 = 1 and 10-01 is not set to 3. Set Pulse Input as PID target value
Figure 4.4.27 Pulse input adjustment: Pulse train, PI; Filter 1/(1+ST), T: Pulse input filter time (using 03-34); Scaling 1/K, K: Scaling factor (using 03-31); Gain and Bias with 03-32 and 03-33, graph axis labels 0% and 10% as printed. Selector branches: 03-30=0 Frequency Reference; 03-30=1 PID Feedback; 03-30=2 PID Target. These selector meanings conflict with the preceding General Pulse/PWM range table.
Pulse-input scaling, gain, bias, filtering and PID setup
03-31 / Scale of pulse input — PDF page 284
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-31 | Scale of pulse input |
| 2 | Range | Depending on the setting of 03-30 03-30=0: 50~32000Hz 03-30=1: 10~1000Hz |
03- 32 / Pulse input gain — PDF page 284
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03- 32 | Pulse input gain |
| 2 | Range | 0.0~1000.0 % |
03-33 / Pulse input bias — PDF page 284
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-33 | Pulse input bias |
| 2 | Range | -100.0~100.0 % |
03-34 / Pulse input filter time — PDF page 284
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-34 | Pulse input filter time |
| 2 | Range | 0.00~2.00 Sec |
Manual — PID pulse input and pulse-output function table — page 285
Manual reference: physical PDF page 285. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Set parameter 00-05 to 5 and 03-30 to 2 to use the pulse input terminal PI as the PID target (setpoint) value. Next set the pulse input scaling (03-31), enter the pulse input frequency to match the maximum output frequency. Adjust the pulse input filter time in case interference or noise is encountered. Refer to Figure 4.4.28.for details. Note: The inverter will display a SE09 "PI setting error" if 03-30=0 and PID control is enabled (10-03 > 0).
Refer to Table 4.4.10 for pulse output function selection overview.
Pulse output scaling, 100% = Maximum pulse frequency (see table 4.4.10). Note: When setting 03-35 to 2 (output frequency) and setting 03-36 to 0 (0 Hz), PO's pulse output and the inverter output frequency are sync. Table 4.4.31 Pulse output function selection
Note: Selection 1~4 are related to the motor speed, 5 and 6 are related to PID and 7 is related to PG. Setup the pulse output Use 03-36 (pulse output scale) to set the pulse output frequency to100% signal value of the selected item. Please refer to the figure 4.4.29.
Figure 4.4.28 PID control: pulse train labelled 03-30=2 supplies Target value / Setpoint to plus input; pulse train labelled 03-30=1 supplies Feedback value to minus input. PID Regulator output is Frequency Reference. Source diagram labels only.
PID pulse input and pulse-output function table
03-35 / Function setting of pulse output — PDF page 285
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-35 | Function setting of pulse output |
| 2 | Range | 1: Frequency command 2: Output frequency 3: Output frequency after the soft start 4: Motor speed 5: PID feedback 6: PID input 7: PG output (with PG card) |
03-36 / Scale of pulse output — PDF page 285
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-36 | Scale of pulse output |
| 2 | Range | 1~32000 Hz |
03-35 / Function / Screen display (LCD) / Parameter / 100% — PDF page 285
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | 03-35 | Function | Screen display (LCD) | Parameter | 100% |
| 2 | 1 | Frequency command | Freq Ref | 12-16 | 01-02 |
| 3 | 2 | Output frequency (Fout) | Output Freq | 12-17 | 01-02 |
| 4 | 3 | Output frequency after soft-start | Output Freq (SFS) | - | 01-02 |
| 5 | 4 | Motor speed (rpm) | Motor Speed | 12-22 | 01-02 |
| 6 | 5 | PID feedback | PID Feedback | 12-39 | 01-02 |
| 7 | 6 | PID input | PID Input | 12-36 | 01-02 |
| 8 | 7 | PG output | PG Pulse Output | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Pulse-output scaling, electrical labels and external PG example — page 286
Manual reference: physical PDF page 286. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When setting 03-35 to 2 (output frequency), PO's pulse output and the inverter output frequency are sync. Scale of pulse output is equal to the value of 03-36. For the pulse output signal level, please refer to figure 4.4.30.
When 03-35 = 7 (PG pulse monitoring output), PG pulse output scaling is internally set 1:1, independent of the scaling set in parameter 03-36. Note: When pulse output function is active, it is required to use the external pull-up resistor at the terminal of PO (the upper limit current of PO is 50mA and 48V) Application examples Example A: Speed follower from external PG Use the pulse input signal as frequency reference or synchronization operation. Refer to Fig. 4.4.31.
Figure 4.4.29 Pulse output proportion: vertical Pulse output (Hz), horizontal Pulse output items; line from origin 0% to 100%, with output ordinate 03-36 at 100%.
Figure 4.4.30 Pulse output signal level: electrical labels +5V, 2.2KΩ, PO, GND and 0V. Pulse waveform labels 5V, 0V, T1, T2; Pulse duty: T1=T2. Pulse train output: 0 to 32KHz, 2.2KΩ. Labels transcribed without asserting connection suitability.
Manual — Speed-follower examples A and B — page 287
Manual reference: physical PDF page 287. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter settings: 1. Frequency reference selection: 00-05=4 (Pulse input) 2. Pulse input’s function selection: 03-30=0 (General pulse input) 3. Pulse input scale: 03-31 (set the number of pulse in Hz to match maximum output frequency, 01-02) 4. Pulse input gain: 03-32 (Set the input gain of the pulse frequency set by 03-31)
- Pulse input bias: 03-33 (Set the input bias of the pulse frequency set by 03-31) 6. Pulse input’s filter time: 03-34 (if the pulse input is unstable due to the interference, increase value.) Use the forward and reverse multi-function inputs to choose motor direction. Note: For higher accuracy use PG feedback in SV or V / f + PG control mode. Example B: Speed follower using two inverters
Inverter #1 parameter settings: Frequency reference from PI signal (Master PG) 1. Frequency reference selection: 00-05=4 (Pulse input) 2. Pulse input’s function selection: 03-30=0 (General pulse input) 3. Pulse input scale: 03-31 (set the number of pulse in Hz to match maximum output frequency, 01-02) 4. Pulse input gain: 03-32 (Set the input gain of the pulse frequency set by 03-31)
- Pulse input bias: 03-33 (Set the input bias of the pulse frequency set by 03-31)
Figure 4.4.31 Speed follower from external PG: Inverter, motor M, Fwd Run/Stop, Rev Run/Stop, S1, S2, 24VG, PI, GND, PG and (1) mark. PG pulse symbol feeds the PI/GND area; terminal labels retained without reconstructing wiring topology or resolving the unexpanded (1).
Figure 4.4.32 Speed follower using two inverters: (INV1), (INV2), motors M1/M2; each has FWD Run/Stop, REV Run/Stop, S1, S2, 24VG, PI and GND. INV1 also has PO. External labels Master PG etcs., +5V and 2.2KΩ. Diagram shows the PO-to-PI region and GND region between inverters; this transcription does not certify wiring.
Manual — Two-inverter and synchronized pulse-input examples — page 288
Manual reference: physical PDF page 288. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Pulse input’s filter time: 03-34 (if the pulse input is unstable due to the interference, increase value.) 7. Pulse output function selection: 03-35=2 (Pulse output is output frequency 8. Scale pulse output parameter 03-36 to 100% of output frequency Inverter #1 parameter settings: Frequency reference from analog signal 1. Frequency reference selection: 00-05=1 (Analog input) 2. Pulse output function selection: 03-35=2 (Pulse output is output frequency 3. Scale pulse output parameter 03-36 to 100% of output frequency Inverter #2: parameter settings: 1. Frequency reference selection: 00-05=4 (Pulse input) 2. Pulse input’s function selection: 03-30=0 (General pulse input) 3. Pulse input scale: 03-31 (set the number of pulse in Hz to match maximum output frequency, 01-02) 4. Pulse input gain: 03-32 (Set the input gain of the pulse frequency set by 03-31)
Pulse input bias: 03-33 (Set the input bias of the pulse frequency set by 03-31) 6. Pulse input’s filter time: 03-34 (if the pulse input is unstable due to the interference, increase value.) Note: When pulse output function is active, it is required to use the external pull-up resistor at the terminal of PO (the upper limit current of PO is 50mA) Example C: Synchronized operation using pulse input
Figure 4.4.33: Synchronized operation of using pulse input Connect pulse signal of an external pulse generator to the pulse input terminal PI of multiple follower inverters for output speed synchronization. Follow inverter #1 and Follower #2 parameter settings: 1. Frequency reference selection: 00-05=4 (Pulse input) 2. Pulse input’s function selection: 03-30=0 (General pulse input) 3. Set one of the Multi-function inputs Sn: 03-00 ~ 03-07=32 (Synchronization command) Example D: Synchronized operation of using pulse output master follower
Figure 4.4.33: Synchronized operation of using pulse input. Two blocks are each labelled (Slave), each with PI; common Pulse Input waveform and SYNC label. Below each are A/B, PG and IM; parenthetical Synchronized Operation. Labels and drawing association retained, not inferred wiring.
Manual — Master/follower pulse-output example and timer delay — page 289
Manual reference: physical PDF page 289. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Master inverter parameter settings: 1. Pulse output function selection: 03-35=1 (Pulse output is output frequency 2. Scale pulse output parameter 03-36 to 100% of output frequency 3. Set one of the Multi-function inputs Sn: 03-00 ~ 03-07=32 (Synchronization command) Follower inverter parameter settings: 1. Frequency reference selection: 00-05=4 (Pulse input) 2. Pulse input’s function selection: 03-30=0 (Frequency command) 3. Pulse input scale: 03-31 (set the number of pulse in Hz to match maximum output frequency, 01-02) 4. Pulse input gain: 03-32 (Set the input gain of the pulse frequency set by 03-31)
- Pulse input bias: 03-33 (Set the input bias of the pulse frequency set by 03-31) 6. Pulse input’s filter time: 03-34 (if the pulse input is unstable due to the interference, increase value.) 7. Set one of the Multi-function inputs Sn: 03-00 ~ 03-07=32 (Synchronization command)
Enable the timer function be setting one of multi-function input parameters 03-00~03-07 (S1 to S8) to 35 (timer function input) and one of multi-function output parameters 03-11, 03-12 (R1A-R1C to R4A- R4C and PH1 to PH4) to 27 (timer function output). The timer function can be used to implement a timer relay. Use timing parameter 03-37 and 03-38 to set the timer ON / OFF delay. Timer output is turned ON when the multi-function timer input is ON for the time specified in parameter 03-37.
Figure 4.4.34 Synchronized operation master follower: left (Master) with Frequency Reference, PO, Sync and 03-00~03-07=32; right (Follower) with PI, Sync and 03-00~03-07=32. Pulse Input waveform and SYNC appear between blocks. Each lower side has A/B, PG and IM; Synchronized Operation caption. No wiring certification.
Master/follower pulse-output example and timer delay
03-37 / Timer ON delay (DI/DO) — PDF page 289
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-37 | Timer ON delay (DI/DO) |
| 2 | Range | 0.0~6000.0 Sec |
03-38 / Timer OFF delay (DI/DO) — PDF page 289
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-38 | Timer OFF delay (DI/DO) |
| 2 | Range | 0.0~6000.0 Sec |
Manual — Timer timing and brake-release conditions — page 290
Manual reference: physical PDF page 290. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Timer output is turned OFF after the multi-function timer input is turned OFF for the time specified in parameter 03-38. Timing example:
Brake Release Function:
It is required to be with the frequency agree function, as the following figure: When the inverter starts running, if the output frequency > 03-13, and both frequency detection level and output torque > torque detection level (03-41), it will delay the time of 03-42 to release brake.
It is recommended to be with starting and stopping frequency locked function (11-43~11-46), shown as the following figure:
Timer timing example: Timer input and Timer output function traces with ON segments. The output ON starts after delay 03-37 from the input rising edge; OFF occurs after delay 03-38 following input OFF. The drawing also contains short intervening input pulses. All labels preserved without inferring unlabelled times.
Brake-release timing: Motor Speed (Output Frequency) versus t. Rising-side condition Output Freq >03-13 and Output Torque >03-41; falling-side condition Output Freq <03-13 or Output Torque <03-41. Lower trace DO 03-11, 03-12, 03-28 set 38 Brake Release. Both transitions are labelled 03-42 Brake Release delay time. Labels only, not a safety validation.
Timer timing and brake-release conditions
03- 41 / Torque Detection Level — PDF page 290
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03- 41 | Torque Detection Level |
| 2 | Range | 0~150 % |
| 3 | 03-42 | Brake Release Delay Time |
| 4 | Range | 0.00~65.00 Sec |
Manual — Brake-release and UP/DOWN acceleration selection — page 291
Manual reference: physical PDF page 291. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
\
Calculate the acceleration/ deceleration time of frequency command by switch the function of UP/DOWN from parameter 03-43. Ex: ΔH1 (set frequency increment at acceleration) and ΔH2 (set frequency increment at deceleration). Ex 1:
03-43=1(Acceleration/ Deceleration Time 2) Acceleration/ Deceleration Time 1 > Acceleration/ Deceleration Time 2
Notes: ΔH1: Frequency augmentation setting in acceleration, t1: Terminal conduction time in acceleration
Brake-release timing with frequency locks: Motor Speed (Output Frequency) versus t; acceleration condition Output Torque >03-41 and deceleration condition Output Torque <03-41. Left plateau vertical label 11-44 and left plateau duration also 11-44 as printed; right plateau vertical label 11-45 and duration 11-46. DO 03-11,03-12,03-28 set 38 Brake Release; both release-delay arrows 03-42. Duplicated left label is retained and flagged.
UP/DOWN Ex 1 diagram: upper trace UP/DOWN Command Slope Frequency and lower Output Frequency, each with upper/lower limit of frequency reference. Command rise labelled ΔH1,t1 and fall ΔH2,t2, with ΔHz steps; output rise ΔH3,t3 and fall ΔH4,t4. Terminal S1: Lasting ON then OFF; S2: OFF then Lasting ON. Both relevant command plateaus are labelled 2 Sec. Shapes and labels retained without numerical interpolation.
Brake-release and UP/DOWN acceleration selection
03-43 / UP/DOWN Acceleration/ Deceleration Selection — PDF page 291
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-43 | UP/DOWN Acceleration/ Deceleration Selection |
| 2 | Range | 【0】: Acceleration/Deceleration Time 1 【1】: Acceleration/Deceleration Time 2 |
Manual — UP/DOWN time-selection examples and formulae — page 292
Manual reference: physical PDF page 292. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
ΔH2: Frequency augmentation setting in deceleration, t2: Terminal conduction time in deceleration t3: Acceleration time in output ΔH3: Output frequency augmentation in acceleration, t4: Deceleration time in output ΔH4: Output frequency augmentation in deceleration
Ex2:
03-43=1(Acceleration/ Deceleration Time 2) Acceleration/ Deceleration Time 1 < Acceleration/ Deceleration Time 2
Command Slope
Notes: ΔH1: Frequency augmentation setting in acceleration t1: Terminal conduction time in acceleration ΔH2: Frequency augmentation setting in deceleration t2: Terminal conduction time in deceleration t3: Acceleration time in output ΔH3: Output frequency augmentation in acceleration, t4: Deceleration time in output ΔH4: Output frequency augmentation in deceleration
UP/DOWN Ex 1 formulae: ΔH1=(Upper Limit Frequency/Acceleration Time 2)×t1; ΔH2=(Upper Limit Frequency/Deceleration Time 2)×t2; ΔH3=(Upper Limit Frequency/Acceleration Time 1)×t3; ΔH4=(Upper Limit Frequency/Deceleration Time 1)×t4.
UP/DOWN Ex 2 diagram: UP/DOWN Command Slope Frequency above Output Frequency; upper and lower frequency-reference limits on each. Command rise ΔH1,t1 and fall ΔH2,t2 with ΔHz step; output rise ΔH3,t3 and fall ΔH4,t4. S1 Lasting ON then OFF; S2 OFF then Lasting ON; two 2 Sec markers. No unlabelled times inferred.
Manual — UP/DOWN formulae continued — page 293
Manual reference: physical PDF page 293. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Repeated UP/DOWN Ex 2 formulae: ΔH1=(Upper Limit Frequency/Acceleration Time 2)×t1; ΔH2=(Upper Limit Frequency/Deceleration Time 2)×t2; ΔH3=(Upper Limit Frequency/Acceleration Time 1)×t3; ΔH4=(Upper Limit Frequency/Deceleration Time 1)×t4.
Manual — External analogue input ranges and functions — page 294
Manual reference: physical PDF page 294. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
04-External Analog Input / Output Parameter
External analogue input ranges and functions
04-00 / AI input signal type — PDF page 294
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-00 | AI input signal type |
| 2 | Range | 0: AI1: 0~10V AI2: 0~10V 1: AI1: 0~10V AI2: 4~20mA 2: AI1: -10~10V AI2: 0~10V 3: AI1: -10~10V AI2: 4~20mA 4: AI1: 4~20mA AI2: 0~10V 5: AI1: 4~20mA AI2: 4~20mA |
04- 09 / AI Input Signal Type of I/O card — PDF page 294
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04- 09 | AI Input Signal Type of I/O card |
| 2 | Range | 0: AI3:0~10V 1: AI3:-10~10V 2: AI3:4~20mA |
04-01 / AI1 signal scanning and filtering time — PDF page 294
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-01 | AI1 signal scanning and filtering time |
| 2 | Range | 0.00~2.00 Sec |
04-02 / AI1 gain — PDF page 294
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-02 | AI1 gain |
| 2 | Range | 0.0~1000.0% |
04-03 / AI1 bias — PDF page 294
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-03 | AI1 bias |
| 2 | Range | -100~100.0% |
04- 04 / AI negative characteristics — PDF page 294
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04- 04 | AI negative characteristics |
| 2 | Range | 【0】: Disable 【1】: Enable |
04-05 / AI2 function setting — PDF page 294
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-05 | AI2 function setting |
| 2 | 04-10 | AI3 Function Setting |
| 3 | Range | 0: Auxiliary frequency 1: Frequency reference gain 2: Frequency reference bias 3: Output voltage bias 4: Coefficient of acceleration and deceleration reduction 5: DC braking current 6: Over-torque detection level 7: Stall prevention level during running 8: Frequency lower limit 9: Jump frequency 4 10: Added to AI1 11: Positive torque limit 12: Negative torque limit 13: Regenerative torque Limit 14: Positive / negative torque limit 15: Torque command/ torque limit (in speed control) 16: Torque command/ torque compensation 17: PTC overheat protection |
Manual — AI2/AI3 ranges and control-board selector instructions — page 295
Manual reference: physical PDF page 295. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Refer to the followings for 04-00 AI input signal type: (For standard H & C type) If AI1 is 0~10V, set parameter 04-00 to 0 or 1. If AI1 is -10~10V, set parameter 04-00 to 2 or 3. If AI2 is 0~10V, set parameter 04-00 to 0 or 2 and tune SW2 on the control board to V. If AI2 is 4~20mA, set parameter 04-00 to 1 or 3, tune SW2 on the control board to I. (For enhanced E & G type) If AI1 is 0~10V, set parameter 04-00 to 0 or 1, and tune SW3 on the control board to V. If AI1 is -10~10V, set parameter 04-00 to 2 or 3, and tune SW3 on the control board to V. If AI1 is 4~20mA, set parameter 04-00 to 4 or 5, and tune SW3 on the control board to I. If AI2 is 0~10V, set parameter 04-00 to 0 or 2 or 4, and tune SW4 on the control board to V. If AI2 is 4~20mA, set parameter 04-00 to 1 or 3 or 5, tune SW4 on the control board to I. (1) Analog Input Level Adjustment AI1, AI2 (04-02, 04-03, 04-04, 04-07, 04-08) Each analog input AI1and AI2 has a separate gain and bias parameter associated with it. Analog input signal AI1 can be adjusted with parameter 04-02 and 04-03; Analog input signal AI2 can be adjusted with parameter 04-07 and 04-08. Refer to Figure 4.4.35.
Figure 4.4.35 Analog inputs and related parameters (for E & G type): +10V, AI1, AI2, GND, -10V. AI1 input labels 0–10V, -10V–+10V; associated 04-00 Level Selection, 04-02 Gain, 04-03 Bias. AI2 input labels 0–10V/0–20mA and 4–20mA/2–10V; associated 04-00 Level Selection, 04-05 Function Selection, 04-07 Gain, 04-08 Bias. Selector labels AI1 SW3 V/I and AI2 SW4 V/I. Literal figure ranges retained independently of range tables.
AI2/AI3 ranges and control-board selector instructions
04-06 / AI2 signal scanning and filtering time — PDF page 295
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-06 | AI2 signal scanning and filtering time |
| 2 | Range | 0.00~2.00 Sec |
04-07 / AI2 gain — PDF page 295
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-07 | AI2 gain |
| 2 | Range | 0.0~1000.0% |
04-08 / AI2 bias — PDF page 295
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-08 | AI2 bias |
| 2 | Range | -100.0~1000.0% |
04-21 / AI3 Signal Scanning and Filtering Time — PDF page 295
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-21 | AI3 Signal Scanning and Filtering Time |
| 2 | Range | 0.00~2.00 Sec |
04-22 / AI3 Gain — PDF page 295
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-22 | AI3 Gain |
| 2 | Range | 0.0~1000.0 % |
04-23 / AI3 Bias — PDF page 295
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-23 | AI3 Bias |
| 2 | Range | -100.0~100.0 % |
Manual — Analogue gain/bias and negative characteristic — page 296
Manual reference: physical PDF page 296. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Gain setting: Sets the level in % that corresponds to a 10V, -10V or 20mA signal at the analog input. (Set the maximum output frequency 01-02 to 100 %) Bias setting: Sets the level in % that corresponds to a 0V or 4mA signal at the analog input. (Set the maximum output frequency 01-02 to 100%) Use both gain and bias setting to scale the input signal.
04-04 (AI negative characteristics) Through the following figure negative characteristics diagram find out the AI Input 10V, -10V, or 20mA input relative frequency reference to be used for the ratio of maximum output frequency (set the maximum output frequency 01-02 to 100%), the ratio will be presented in reverse.
(2) AI1 signal filtering time (04-01) (3) AI2 signal filtering time (04-06) All analog inputs (AI1, AI2) have a 1st order programmable input filter that can be adjusted when noise is present on each of the incoming analog signal to prevent erratic drive control. The filter time constant (range: 0.00 to 2.00 seconds) is defined as the time that the input step signal reaches 63% of its final value.
Figure 4.4.36 Gain and bias operations (for frequency reference signal). (a) Gain: Frequency Reference versus Terminal AI1,AI2 analog input, -10V,0V(4mA),10V(20mA); reference marks 200%,100%,-100%,-200%; curves Gain:200% and Gain:100%. (b) Bias: Frequency Reference, +100%, bottom 100% printed without minus; horizontal labels left 10V printed without minus,0V(4mA),10V(20mA); Bias=positive, Bias=0%, Bias=Negative. Potential missing signs are preserved rather than repaired.
04-04 AI negative-characteristic graph: central vertical axis reaches 100%; triangular lines fall toward -10V on the left and 10V(20mA) on the right. Origin labelled 0%,0V(4mA). Source graph only; no interpolation added.
Manual — Filter time constant and AI2 functions 0–7 — page 297
Manual reference: physical PDF page 297. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Increasing the filter time causes the drive operation to become more stable but less responsive to change to the analog input.
(4) AI2 function setting (04-05) AI2 is multi-function analog input terminal function selection. Refer to Table 4.4.11 for function overview. Table 4.4.32 Multi-function analog input list (04-05 setting)
Figure 4.4.37 Filter time constant: % versus t; unfiltered signal steps to 100 and filtered signal rises toward it. 63 marks filtered level at the dashed time line; horizontal arrow labelled Filter time constant (04-01).
Filter time constant and AI2 functions 0–7
Setting / Function / Description / Control mode — PDF page 297
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Setting | Function | Function | Description | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Setting | Name | Screen display | Description | V/F | V/F + PG | SLV | SV | PM SV | PM SLV | SLV2 |
| 3 | 0 | Auxiliary frequency | AUX.Freq Ref | Max output frequency (01-02, Fmax) = 100% | O | O | O | O | O | O | O |
| 4 | 1 | Frequency reference gain (FGAIN) | Freq Ref Gain | Aggregated gain = AI1 = 04-02 * FGAIN | O | O | O | O | O | O | O |
| 5 | 2 | Frequency reference bias (FBIAS) | Freq Ref Bias | Aggregated bias = AI1 = 04-03 * FBIAS | O | O | O | O | O | O | O |
| 6 | 3 | Output voltage bias (VBIAS) | Output Volt Bias | Aggregate output voltage =V/F curve voltage + VBIAS | O | O | X | X | O | O | O |
| 7 | 4 | Coefficient of acceleration and deceleration reduction (K) | Tacc/Tdec Scaling | Actual acceleration and deceleration time = acceleration and deceleration time | O | O | O | O | O | O | O |
| 8 | 5 | DC braking current | DC Inj Current | Adjust the DC braking current (0 ~ 100%) based on analog input. When the inverter rated current = 100%, DC braking current 07-07 is disabled. | O | O | O | X | O | X | O |
| 9 | 6 | Over-torque detection level | Over Tq Level | Change over-torque detection level based on over-torque detection level, at this time, 08-15 is disabled. | O | O | O | O | O | O | O |
| 10 | 7 | Stall prevention level during running | Run Stall Level | Adjust the action level (30% ~ 200%) of stall prevention in operation based on analog input. The inverter rated current =100%. | O | O | X | X | O | X | O |
Manual — AI2 functions 8–17 and frequency gain — page 298
Manual reference: physical PDF page 298. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
04-05=0: Auxiliary frequency When parameter 00-05 = 1 (main frequency from external control) the auxiliary speed reference frequency can be activated via the multi-speed input commands (see table 4.4.7). The auxiliary frequency command can be set via AI2. The maximum output frequency is set by 01-02, Fmax =100%. 04-05=1: Frequency reference gain (FGAIN) Multi-function analog input AI2 can be used to adjust the frequency reference gain of analog input AI1. The total frequency reference gain of terminal AI1 is the internal gain set by parameter 04-02 times FGAIN. The maximum frequency reference for AI1 is 100%.
Figure 4.4.38 Frequency gain adjustment: FGAIN versus Terminal AI2 analog input; labels -10V,0V(4mA),+10V(20mA). Trace lies at baseline through the negative-input region then rises from 0V to 100% at +10V.
AI2 functions 8–17 and frequency gain
Setting / Function / Description / Control mode — PDF page 298
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Setting | Function | Function | Description | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode | Control mode |
| 2 | Setting | Name | Screen display | Description | V/F | V/F + PG | SLV | SV | PM SV | PM SLV | SLV2 |
| 3 | 8 | Frequency lower limit | Ref. Low Bound | Adjust the lower limit (0 to 100%) of frequency command based on analog input, the maximum output = 100%. The lower limit of frequency command is the greater one of the actual frequency command’s lower limit 00-13 or the multi-function analog input. | O | O | O | O | O | O | O |
| 4 | 9 | Jump frequency 4 | Jump Freq 4 | Jump frequency 4. 100% = maximum output frequency | O | O | O | O | O | O | O |
| 5 | 10 | Added to AI1 | Add to AI1 | Added to AI1. 100% = maximum output frequency | O | O | O | O | O | O | O |
| 6 | 11 | Positive torque limit | Positive Tq Limit | 100% = motor’s rated torque | X | X | O | O | O | O | X |
| 7 | 12 | Negative torque limit | Negative Tq Limit | 100% = motor’s rated torque | X | X | O | O | O | O | X |
| 8 | 13 | Regenerative torque limit | Regen. Tq Limit | 100% = motor’s rated torque | X | X | O | O | O | O | X |
| 9 | 14 | Positive / negative torque limit | +/- Tq Limit | 100% = motor’s rated torque | X | X | O | O | O | O | X |
| 10 | 15 | Torque command/ torque limit for speed control | Tref/Tq Limit | 100% = motor’s rated torque | X | X | X | O | O | X | X |
| 11 | 16 | Torque command/ torque compensation | Tq Compensation | 100% = motor’s rated torque | X | X | X | O | O | X | X |
| 12 | 17 | PTC overheat protection | PTC overheat Stall | Use the PTC sensor in the motor to stop from overheats. | O | O | O | O | O | O | O |
Manual — Frequency-reference gain and bias examples — page 299
Manual reference: physical PDF page 299. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: When the internal gain of AI1 (04-02) is set to 100% and AI2 to 5V (for example FGAIN = 50%), the reference frequency of terminal AI1 will be 50%, as shown in Figure 4.4.39.
04-05=2: Frequency reference bias (FBIAS) Multi-function analog input terminal AI2 can be used to adjust the frequency reference bias of AI1. The total frequency reference bias of terminal AI1 is the sum of internal bias set by parameter 04-03 and FBIAS. The maximum frequency reference for AI1 is 100%.
Figure 4.4.39 Frequency reference gain adjustment (example): Frequency Reference 0%,50%,100% versus Terminal AI1 input voltage 0V,10V. Upper line 04-02=100%; lower line 04-02×FGAIN=50%.
Figure 4.4.40 Bias adjustment: FBIAS versus Terminal AI2 analog input; diagonal connects -10V/-100%,0V(4mA)/0,10V(20mA)/100%.
Manual — Reference bias, output voltage bias and acceleration coefficient — page 300
Manual reference: physical PDF page 300. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: Terminal AI1 input is 0V, 04-02 = 100% (AI1 gain), 04-03 = 0% (AI1 bias) and terminal AI2 input is 3V. The reference frequency will be 30% as shown in Figure 4.4.41.
04-05=3: Output voltage bias (VBIAS) Multi-function analog input AI2 can be used to adjust the output voltage. The total output voltage of inverter is the sum of output voltage based on the selected V/F curve and VBIAS. The maximum output voltage is set by 01-03, Vmax = 100%.
04-05=4: Acceleration and deceleration coefficient (K) Multi-function analog input AI2 can be used to adjust the acceleration and deceleration time coefficient. The actual acceleration and deceleration time is calculated as follows: Acceleration/ Deceleration time setting is 100% (00-14~00-17, 00-21~00-24).
Figure 4.4.41 Frequency Reference bias adjustment (example): Frequency Reference versus Terminal AI1 input voltage,0V and10V; 30% Bias bracket at0V and100% marker. Source line reaches100% before the10V guide; no intermediate numeric point inferred.
Figure 4.4.42 Bias adjustment: VBIAS versus Terminal AI2 analog input;-10V,0V(4mA),10V(20mA); trace stays at baseline through negative input then rises to100% at10V.
Source equation: Actual accel / decel time = Acceleration / Deceleration time (00-14~00-17,00-21,00-24) / K. The numerator punctuation is retained; nearby prose separately gives00-21~00-24.
Adjacent source context — repeated to preserve continuation:
Manual — Acceleration coefficient, DC braking and torque detection — page 301
Manual reference: physical PDF page 301. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
04-05=5: DC braking current Multi-function analog input AI2 can be used to adjust the DC Injection braking current. DC braking current parameter 07-07 setting should be set to 0% to use this function. The inverter rated current = 100%
04-05=6: Over-torque detection level Multi-function analog input AI2 can be used to adjust the over-torque detection level. 100% of inverter rated current (V/F or V/F + PG control mode) 100% motor rated torque (SLV or SV control mode) If the multi-function analog input is used to adjust the over-torque level, the internal over-torque detection level (08-15) is disabled.
Figure 4.4.43 Acceleration / deceleration time reduction coefficient: upper K plot has levels1 and10 and input ticks0V(4mA),1,2,3,4,5,6,7,8,9,10V(20mA). K trace remains at1 initially then rises to10. Lower Actual Accel / Decel time plot starts at100% then decreases as Terminal AI2 analog input increases. No unlabelled numeric values calculated.
Figure 4.4.44 DC braking current adjustment: DC Injection Braking Current versus Terminal AI2 analog input;-10V,0V(4mA),10V(20mA); baseline through negative input, rising from0V to100% at10V.
Adjacent source context — repeated to preserve continuation:
Manual — Torque detection, stall prevention and frequency lower limit — page 302
Manual reference: physical PDF page 302. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4-05=7: Stall prevention level during running Multi-function analog input AI2 can be used to adjust the stall prevention level during operation. Inverter rated current = 100%. When AI2 is set to control stall prevention level (04-05 = 7) and parameter 08-03 (Stall prevention level during operation) is used, then the lesser of the two value becomes the active stall prevention level during operation. Example: If the motor power is less than that of the inverter, the operation and the stall prevention of the motor will be based on the factory settings, multi-function analog input AI2 can be used to reduce the stall prevention level during operation.
04-05=8: Frequency lower limit Multi-function analog input AI2 can be used to adjust the lower limit of frequency reference. Maximum output frequency (Fmax, 01-02) = 100%. The actual lower limit is determined by the maximum value of 00-13 (frequency lower limit) and level of the multi-function analog input AI2.
Figure 4.4.45 Over-torque detection level adjustment: Detection Level versus Terminal AI2 analog input;-10V,0V(4mA),10V(20mA); baseline through negative input, then line reaches100% at10V.
Figure 4.4.46 Stall prevention level adjustment in operation: Stall Prevention Level versus Terminal AI2 analog input. Input labels-10V,0V(4mA),1.5V(6.4mA),10V(20mA). Trace is30% through1.5V and rises to200% at10V. Printed corner associations retained.
Manual — Lower frequency limit, jump frequency and added bias — page 303
Manual reference: physical PDF page 303. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
04-05=9: Jump frequency 4 Multi-function analog input AI2 can be used to adjust Jump frequency 4. Maximum output frequency (01-02, Fmax) = 100%. Setting 11-08 to 11-10 to 0.0Hz turns of the Jump frequency function.
04-05=10: Added to AI1 Multi-function analog input AI2 can be used as a bias level for analog input AI1.
Figure 4.4.47 Adjustment of lower limit of frequency reference: Frequency Reference Lower Bound versus Terminal AI2 analog input;-10V,0V(4mA),10V(20mA). Baseline through negative input then rises to100% at10V.
Figure 4.4.48 Jump frequency4 Setting Operation. (a) Jump Frequency4 Adjustment: Jump Frequency4 versus Terminal AI2 analog input;-10V,0V(4mA),10V(20mA),100%; trace at baseline through negative input then rises to100% at10V. (b) Jump Frequency Hierarchy: Output Frequency versus Jump Frequency Reference; ordered labels Jump Freq4 (Using analog input),Jump Freq3(11-10),Jump Freq2(11-09),Jump Freq1(11-08). Four jump-band symbols shown, no widths inferred.
Manual — AI2 addition and torque-control/PTC functions — page 304
Manual reference: physical PDF page 304. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: 04-02 (AI1 gain) = 100%, 04-03 (AI2 gain) = 0%, and terminal AI2 level is 2V. If input terminal AI1 is 0V, the internal reference frequency of terminal AI1 will be 20 %. 04-05=11: Positive torque limit Multi-function analog input AI2 can be used to adjust the positive torque limit. 04-05=12: Negative torque limit Multi-function analog input AI2 can be used to adjust the negative torque limit. 04-05=13: Regenerative torque limit Multi-function analog input AI2 can be used to adjust the regenerative torque limit. 04-05=14: Positive / negative torque limits Multi-function analog input AI2 can be used to adjust both the positive and negative torque limit. For more details on torque limits, please refer to parameter group 21 - torque and position control group. 04-05=15: Torque reference / torque limit of speed control Multi-function analog input AI2 can be used to adjust the torque reference / torque limit in closed loop vector mode. 04-05=16: Torque reference/ Torque compensation of speed control Multi-function analog input AI2 can be used to adjust the torque reference / torque compensation in closed loop vector mode. For more details on the torque control functions, please refer to parameter group 21 - torque and position control group. 04-05=17: PTC Overheat Protection Use the sensor in the motor to stop from overheats. Please refer to 08-42~08-44 description for more details.
Figure 4.4.49 Operation of being added to AI1 as bias: Frequency Reference Bias versus Terminal AI2 analog input; -10V,0V(4mA),10V(20mA); diagonal from-100% at-10V through origin to100% at10V. The minus sign on-100% is on a separate printed line.
Manual — Analogue outputs AO1/AO2 functions, gains and biases — page 305
Manual reference: physical PDF page 305. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
For the analog output and related parameters, refer to figure 4.4.50.
Analogue outputs AO1/AO2 functions, gains and biases
04-11 / AO1 function Setting — PDF page 305
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-11 | AO1 function Setting |
| 2 | Range | 0: Output frequency 1: Frequency command 2: Output voltage 3: DC voltage 4: Output current 5: Output power 6: Motor speed 7: Output power factor 8: AI1 input 9: AI2 input 10: Torque command 11: q -axis current 12: d-axis current 13: Speed deviation 14: Reserved 15: ASR output 16: Reserved 17: q-axis voltage 18: d-axis voltage 19~20: Reserved 21: PID input 22: PID output 23: PID target value 24: PID feedback value 25: Output frequency of the soft starter 26: PG feedback 27: Reserved 28: Communication control |
04-12 / AO1 gain — PDF page 305
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-12 | AO1 gain |
| 2 | Range | 0.0~1000.0% |
04-13 / AO1 bias — PDF page 305
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-13 | AO1 bias |
| 2 | Range | -100.0~100.0% |
04-16 / AO2 function setting — PDF page 305
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-16 | AO2 function setting |
| 2 | Range | See parameter 04-11 |
04-17 / AO2 gain — PDF page 305
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-17 | AO2 gain |
| 2 | Range | 0.0~1000.0% |
04-18 / AO2 bias — PDF page 305
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-18 | AO2 bias |
| 2 | Range | -100.0~100.0% |
Manual — Analogue output adjustment — page 306
Manual reference: physical PDF page 306. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Analog output AO1 and AO2 adjustment (04-12, 04-13 and 04-17, 04-18) Signal: Use parameter 04-11 to select the analog output signal for AO1 and parameter 04-16 to select the analog output signal for AO2. Gain: Use parameter 04-12 to adjust the gain for AO1 and parameter 04-17 to adjust the gain for AO2. Adjust the gain so that the analog output (10V/20mA) matches 100% of the selected analog output signal (04-11 for AO1 and 04-16 for AO2). Bias: Use parameter 04-13 to adjust the bias for AO1 and parameter 04-18 to adjust the bias for AO2. Adjust the bias so that the analog output (0V/4mA) matches 0% of the selected analog output signal (04-11 for AO1 and 04-16 for AO2).
Analog output terminal function selection (04-11 and 04-16) Refer to the following table 4.4.33.
Figure4.4.50 Analog outputs and related parameters: AO1 has04-11 Function Selection,04-12 Gain,04-13 Bias; AO2 has04-16 Function Selection,04-17 Gain,04-18 Bias.
Figure4.4.51 Analog output level adjustment: vertical Analog Output Signal labels10V(or20mA)×Gain,(20mA)10V,(4mA)0V and Bias bracket; horizontal Monitored items0% to100%. Solid trace starts above0 due to Bias, rises and then levels at10V(20mA). No unlabelled numeric points inferred.
Manual — Analogue output function/control-mode matrix and type — page 307
Manual reference: physical PDF page 307. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.33 Selection of analog output terminals function (04-11 and 04-16)
For standard H & C type: It is required to be with the setting of SW6 on the conrtol board when AO2 analog output signal is active. When 04-19=0 (AO2 is 0~10V) and SW6 on the control board is V, AO2 output signal type is voltage. When 04-19=1 (AO2 is 4~20mA and SW6 on the control board is I, AO2 output signal type is current. For enhanced E & G type: It is required to be with the setting of SW1 and SW2 on the control board when AO1 and AO2 analog output signals are active. When 04-19=0, AO1 is 0~10V, and SW1 on the control board is V, AO1 output signal type is voltage.
AO2 is 0~10V, and SW2 on the control board is V, AO2 output signal type is voltage.
Analogue output function/control-mode matrix and type
04-11, 04-16 Parameter setting / Function (Keypad display) / Monitoring Parameters Group 12 / Control Mode — PDF page 307
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 04-11, 04-16 Parameter setting | Function (Keypad display) | Monitoring Parameters Group 12 | Control Mode | Control Mode | Control Mode | Control Mode | Control Mode | Control Mode | Control Mode |
| 2 | 04-11, 04-16 Parameter setting | Function (Keypad display) | Monitoring Parameters Group 12 | VF | VF+PG | SLV | SV | PM SV | PM SLV | SLV2 |
| 3 | 0 | Output Freq | 12-17 | O | O | O | O | O | O | O |
| 4 | 1 | Freq Ref | 12-16 | O | O | O | O | O | O | O |
| 5 | 2 | Output Voltage | 12-19 | O | O | O | O | O | O | O |
| 6 | 3 | DC Voltage | 12-20 | O | O | O | O | O | O | O |
| 7 | 4 | Output Current | 12-18 | O | O | O | O | O | O | O |
| 8 | 5 | Output KW | 12-21 | O | O | O | O | O | O | O |
| 9 | 6 | Motor Speed | 12-22 | O | O | O | O | O | O | O |
| 10 | 7 | Output PF | 12-23 | O | O | O | O | O | O | O |
| 11 | 8 | AI1 Input | 12-25 | O | O | O | O | O | O | O |
| 12 | 9 | AI2 Input | 12-26 | O | O | O | O | O | O | O |
| 13 | 10 | Torque Ref | 12-27 | X | X | O | O | O | O | X |
| 14 | 11 | Current Iq | 12-28 | X | X | O | O | O | O | X |
| 15 | 12 | Current Id | 12-29 | X | X | O | O | O | O | X |
| 16 | 13 | Speed Deviation | 12-30 | X | X | X | O | O | X | X |
| 17 | 14 | Reserved | ⟦blank source cell⟧ | X | X | X | X | X | X | X |
| 18 | 15 | ASR Output | 12-32 | X | O | X | O | O | X | X |
| 19 | 16 | Reserved | - | X | X | X | X | X | X | X |
| 20 | 17 | Voltage Ref Vq | - | X | X | O | O | O | O | X |
| 21 | 18 | Voltage Ref Vd | - | X | X | O | O | O | O | X |
| 22 | 19 | Reserved | - | X | X | X | X | X | X | X |
| 23 | 20 | Reserved | - | X | X | X | X | X | X | X |
| 24 | 21 | PID Input | 12-36 | O | O | O | O | O | O | O |
| 25 | 22 | PID Output | 12-37 | O | O | O | O | O | O | O |
| 26 | 23 | PID Setpoint | 12-38 | O | O | O | O | O | O | O |
| 27 | 24 | PID Feedback | 12-39 | O | O | O | O | O | O | O |
| 28 | 25 | Output Freq (SFS) | - | O | O | O | O | O | O | O |
| 29 | 26 | PG Feedback | 12-33 | X | O | X | O | O | X | X |
| 30 | 27 | Reserved | - | X | X | X | X | X | X | X |
| 31 | 28 | Comm Control | - | O | O | O | O | O | O | O |
04-19 / AO output signal type — PDF page 307
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-19 | AO output signal type |
| 2 | Range | 【0】: AO1 0~10V; AO2 0~10V 【1】: AO1 0~10V; AO2 4~20mA 【2】: AO1 4~20mA; AO2 0~10V (For enhanced E & G type) 【3】: AO1 4~20mA; AO2 4~20mA (For enhanced E & G type) |
Manual — AO filtering and multi-speed acceleration formulae — page 308
Manual reference: physical PDF page 308. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When 04-19=1, AO1 is 0~10V, and SW1 on the control board is V, AO1 output signal type is voltage.
AO2 is 4~20mA, and SW2 on the control board is I, AO2 output signal type is current. When 04-19=2, AO1 is 4~20mA, and SW1 on the control board is I, AO1 output signal type is current.
AO2 is 0~10V, and SW2 on the control board is V, AO2 output signal type is voltage. When 04-19=3, AO1 is 4~20mA, and SW1 on the control board is I, AO1 output signal type is current.
AO2 is 4~20mA, and SW2 on the control board is I, AO2 output signal type is current.
Setting of parameter 04-20 is used for filtering momentary change in analog output signal. When it is enabled, system response will lower down and interference protection will enhance.
05- Multi-Speed Parameters
05-00=0: Standard Acceleration and deceleration times parameters 00-14 ~ 00-17 / 00-21 ~ 00-24 are used for multi-speed 0 ~ 15. 05-00=1: Each multi-speed uses a dedicated acceleration and deceleration time parameters 05-17 ~ 05-48. There are two different modes for acceleration / deceleration timing when 05-00 is set to 1, see time example on the next page. Acceleration time calculation formula Maximum output frequency: Parameter 01-00=F, maximum output frequency set by 01-02, 01-00 ≠ F, maximum output frequency determined by V/F curve selected (50.0 / 60.0 / 90.0 / 120.0 / 180.0). Example:01-00=01 (50Hz (maximum output frequency), 05-02=10 Hz (multi-step speed 0), 05-17=5.0s (Acceleration time), 05-18=20.0 sec. (Deceleration time). Acceleration time calculation formula
Source formulae: Time it takes to reach set frequency = [Acceleration time × (set frequency - output frequency)] / Maximum output frequency. Deceleration formula = [Deceleration time × (output frequency - set frequency)] / Maximum output frequency.
Example calculations as printed: acceleration time to reach set frequency = (5.0×10Hz)/50Hz =1.0sec; deceleration time = (20.0×10Hz)/50Hz =4.0sec. These are source example results, not recalculated settings.
AO filtering and multi-speed acceleration formulae
04-20 / Filter time of AO signal scan — PDF page 308
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-20 | Filter time of AO signal scan |
| 2 | Range | 【0.00~0.50】Sec |
05-00 / Acceleration and deceleration selection of multi-speed — PDF page 308
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-00 | Acceleration and deceleration selection of multi-speed |
| 2 | Range | 0: Acceleration and deceleration time 1 ~ 4 used. 1: Use independent acceleration and deceleration time for each multi-speed setting. |
Manual — Multi-speed timing mode1 — page 309
Manual reference: physical PDF page 309. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: Acceleration / deceleration timing when 05-00 is set to 1. In this example the following parameters are set: 00-02=1 (External terminal operation) 03-00=0 (Terminal S1: Forward /Stop) 03-01=1 (Terminal S2: Reversal /Stop) 03-02=2 (Terminal S3: Speed 1) 03-03=3 (Terminal S4: Speed 2) 03-03=4 (Terminal S5: Speed 3) *Speed 1 is required to confirm if AI2 function setting (04-05) is set to 0 (Auxiliary frequency). If 04-05=0, it will make the frequency of speed 1 set to AI2 auxiliary frequency and the value is determined by AI2. If function of speed 1 is generally used, set AI2 to other functions except 0 (the recommended value: set 10 ADD to AI1.) Acceleration / Deceleration Calculation Mode 1: If the run command is cycled on and off, acceleration and deceleration time (a ~ f) is calculated based on the active speed command as follows:
Acceleration/Deceleration Calculation Mode1 diagram: Hz versus T; three separated runs have Speed Command0/05-01, Speed Command1/05-02 and Speed Command2/05-03. Rising/falling durations respectively a/b,c/d,e/f. Terminal S1 Run,Stop,Run,Stop,Run,Stop; S2 Off throughout. S3 Off,On,Off; S4 Off thenOn. Stage associations retained, no undocumented values inferred.
Mode1 formulae, each in sec: a=(05-17)×(05-01)/(01-02); b=(05-18)×(05-01)/(01-02); c=(05-19)×(05-02)/(01-02); d=(05-20)×(05-02)/(01-02); e=(05-21)×(05-03)/(01-02); f=(05-22)×(05-03)/(01-02).
Manual — Multi-speed timing mode2 — page 310
Manual reference: physical PDF page 310. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Acceleration / Deceleration Calculation Mode 2: If the run command is remains on, acceleration and deceleration time (a ~ f) is calculated based on the active speed command as follows:
Mode2 timing diagram: Hz versus T; positive Speed Commands0,1,2,3 with05-01,05-02,05-03,05-04; negative Speed Command4 with05-05; positive Speed Command5 with05-06. Durations a,b,c,d,e,f,g,h,i. Terminal S1 On through stages0–3,Off for reverse stage4,On forstage5 thenStop; S2 Off,On forstage4,Off. S3 stage pattern Off,On,Off,On,Off,On; the final On trace stays high through the displayed end; S4 Off,Off,On,On,Off,Off,Off; S5 Off,Off,Off,Off,On,On,Off. Lower parameter pairs17/18,19/20,21/22,23/24,25/26,27/28,19/20. Source associations only.
Mode2 formulae as printed, in sec: a=(05-17)×(05-01)/(01-02); b=(05-19)×[(05-02)-(05-01)]/(01-02); c=(05-21)×[(05-03)-(05-02)]/(01-02); d=(05-24)×[(05-03)-(05-04)]/(01-02); e=(05-26)×(05-04)/(01-02); f=(05-25)×(05-05)/(01-02); g=(05-27)×(05-05)/(01-02); h=(05-27)×(05-06)/(01-02); i=(05-19)×(05-06)/(01-02). Retain source choices even where acceleration/deceleration parameter associations conflict with names.
Manual — Speed-stage0 frequency and independent times0–7 — page 311
Manual reference: physical PDF page 311. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Speed-stage0 frequency and independent times0–7
05-01 / Frequency setting of speed-stage 0 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-01 | Frequency setting of speed-stage 0 |
| 2 | Range | 0.0~599.00 Hz |
05-17 / Acceleration time setting for multi speed 0 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-17 | Acceleration time setting for multi speed 0 |
| 2 | Range | 0.0~6000.0 Sec |
05-18 / Deceleration time setting for multi speed 0 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-18 | Deceleration time setting for multi speed 0 |
| 2 | Range | 0.0~6000.0 Sec |
05-19 / Acceleration time setting for multi speed 1 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-19 | Acceleration time setting for multi speed 1 |
| 2 | Range | 0.0~6000.0 Sec |
05-20 / Deceleration time setting for multi speed 1 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-20 | Deceleration time setting for multi speed 1 |
| 2 | Range | 0.0~6000.0 Sec |
05-21 / Acceleration time setting for multi speed 2 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-21 | Acceleration time setting for multi speed 2 |
| 2 | Range | 0.0~6000.0 Sec |
05-22 / Deceleration time setting for multi speed 2 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-22 | Deceleration time setting for multi speed 2 |
| 2 | Range | 0.0~6000.0 Sec |
05-23 / Acceleration time setting for multi speed 3 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-23 | Acceleration time setting for multi speed 3 |
| 2 | Range | 0.0~6000.0 Sec |
05-24 / Deceleration time setting for multi speed 3 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-24 | Deceleration time setting for multi speed 3 |
| 2 | Range | 0.0~6000.0 Sec |
05-25 / Acceleration time setting for multi speed 4 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-25 | Acceleration time setting for multi speed 4 |
| 2 | Range | 0.0~6000.0 Sec |
05-26 / Deceleration time setting for multi speed 4 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-26 | Deceleration time setting for multi speed 4 |
| 2 | Range | 0.0~6000.0 Sec |
05-27 / Acceleration time setting for multi speed 5 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-27 | Acceleration time setting for multi speed 5 |
| 2 | Range | 0.0~6000.0 Sec |
05-28 / Deceleration time setting for multi speed 5 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-28 | Deceleration time setting for multi speed 5 |
| 2 | Range | 0.0~6000.0 Sec |
05-29 / Acceleration time setting for multi speed 6 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-29 | Acceleration time setting for multi speed 6 |
| 2 | Range | 0.0~6000.0 Sec |
05-30 / Deceleration time setting for multi speed 6 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-30 | Deceleration time setting for multi speed 6 |
| 2 | Range | 0.0~6000.0 Sec |
05-31 / Acceleration time setting for multi speed 7 — PDF page 311
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-31 | Acceleration time setting for multi speed 7 |
| 2 | Range | 0.0~6000.0 Sec |
Manual — Independent multi-speed times7–15 — page 312
Manual reference: physical PDF page 312. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Independent multi-speed times7–15
05-32 / Deceleration time setting for multi speed 7 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-32 | Deceleration time setting for multi speed 7 |
| 2 | Range | 0.0~6000.0 Sec |
05-33 / Acceleration time setting for multi speed 8 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-33 | Acceleration time setting for multi speed 8 |
| 2 | Range | 0.0~6000.0 Sec |
05-34 / Deceleration time setting for multi speed 8 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-34 | Deceleration time setting for multi speed 8 |
| 2 | Range | 0.0~6000.0 Sec |
05-35 / Acceleration time setting for multi speed 9 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-35 | Acceleration time setting for multi speed 9 |
| 2 | Range | 0.0~6000.0 Sec |
05-36 / Deceleration time setting for multi speed 9 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-36 | Deceleration time setting for multi speed 9 |
| 2 | Range | 0.0~6000.0 Sec |
05-37 / Acceleration time setting for multi speed 10 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-37 | Acceleration time setting for multi speed 10 |
| 2 | Range | 0.0~6000.0 Sec |
05-38 / Deceleration time setting for multi speed 10 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-38 | Deceleration time setting for multi speed 10 |
| 2 | Range | 0.0~6000.0 Sec |
05-39 / Acceleration time setting for multi speed 11 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-39 | Acceleration time setting for multi speed 11 |
| 2 | Range | 0.0~6000.0 Sec |
05-40 / Deceleration time setting for multi speed 11 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-40 | Deceleration time setting for multi speed 11 |
| 2 | Range | 0.0~6000.0 Sec |
05-41 / Acceleration time setting for multi speed 12 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-41 | Acceleration time setting for multi speed 12 |
| 2 | Range | 0.0~6000.0 Sec |
05-42 / Deceleration time setting for multi speed 12 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-42 | Deceleration time setting for multi speed 12 |
| 2 | Range | 0.0~6000.0 Sec |
05-43 / Acceleration time setting for multi speed 13 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-43 | Acceleration time setting for multi speed 13 |
| 2 | Range | 0.0~6000.0 Sec |
05-44 / Deceleration time setting for multi speed 13 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-44 | Deceleration time setting for multi speed 13 |
| 2 | Range | 0.0~6000.0 Sec |
05-45 / Acceleration time setting for multi speed 14 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-45 | Acceleration time setting for multi speed 14 |
| 2 | Range | 0.0~6000.0 Sec |
05-46 / Deceleration time setting for multi speed 14 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-46 | Deceleration time setting for multi speed 14 |
| 2 | Range | 0.0~6000.0 Sec |
05-47 / Acceleration time setting for multi speed 15 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-47 | Acceleration time setting for multi speed 15 |
| 2 | Range | 0.0~6000.0 Sec |
05-48 / Deceleration time setting for multi speed 15 — PDF page 312
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 05-48 | Deceleration time setting for multi speed 15 |
| 2 | Range | 0.0~6000.0 Sec |
Manual — Automatic operation mode and single-cycle example — page 313
Manual reference: physical PDF page 313. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
06-Automatic Program Operation Parameters
Automatic operation mode uses frequency reference parameters 05-01, 06-01~06-15, operation time parameters 06-16 ~ 06-31 and direction of operation parameters 06-32~06-47. Notes: The automatic operation mode is disabled when any of the following functions are active: - Frequency wobbling function - PID function . When automatic operation mode is active, external multi-step speed reference command 1~4 (03-00~03-07=2~5) is disabled. Example 1: Automatic operation mode – Single cycle In this example the inverter executes a single cycle and then stops. Parameter Settings: 06-00 = 1 or 4 (Single cycle operation) 06-32~06-34= 1 (Forward for multi-step speed 0 - 2) 06-47= 2 (Reverse for multi-step speed 15) 06-35~06-46= 0 (Stop for multi-step speed 3 - 14) 05-01= 15 Hz (Multi-step speed 0: 15 Hz) 06-01= 30 Hz (Multi-step speed 1: 30 Hz) 06-02= 50 Hz (Multi-step speed 2: 50 Hz) 06-15= 20Hz (Multi-step speed 15: 20 Hz) 06-16= 20 sec (Multi-step time 0: 20 sec) 06-17= 25 sec (Multi-step time 1: 25 sec) 06-18= 30 sec (Multi-step time 2: 30 sec) 06-31= 40 sec (Multi-step time 15: 40 sec)
Automatic operation mode and single-cycle example
06-00 / Automatic operation mode selection — PDF page 313
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 06-00 | Automatic operation mode selection |
| 2 | Range | 0: Disable 1: Execute a single cycle operation. Restart speed is based on the previous stopped speed. 2: Execute continuous cycle operation. Restart speed is based on the previous cycle stop speed. 3: After completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the previous stopped speed 4: Execute a single cycle operation. Restart speed is based on the Speed-Stage 0. 5: Execute continuous cycle operation. Restart speed is based on the Speed-Stage 0. 6: After completion of a single cycle, the on-going operation speed is based on the speed of the last stage. Restart speed is based on the Speed-Stage 0 |
Manual — Automatic single and continuous cycle diagrams — page 314
Manual reference: physical PDF page 314. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example 2: Automatic operation mode – Continuous cycle In this example the inverter repeats the same cycle. Parameter Settings: 06-00 = 2 or 5 (Continuous cycle operation) 06-01~06-47= Enter the same setting as that of Example 1.
Figure4.4.52 Single cycle automatic operation(stop): Freq. trace15Hz05-01 for20s06-16,30Hz06-01 for25s06-17,50Hz06-02 for30s06-18,then20Hz below baseline labelled06-15 for40s06-31,return to zero. Below-baseline magnitude label20Hz is unsigned in source.
Figure4.4.53 Periodic automatic operation: repeated trace15Hz05-01/20s06-16,30Hz06-01/25s06-17,50Hz06-02/30s06-18,20Hz below baseline06-03/40s06-19. Two cycles shown. These06-03/06-19 references differ from the preceding example’s06-15/06-31; retained literally.
Manual — Automatic continued-run and restart examples — page 315
Manual reference: physical PDF page 315. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example 3: Automatic operation mode – Single cycle and continue running at last speed of the cycle In this example the inverter executes a single cycle and continue running at last speed of the cycle. Parameter Settings: 06-00= 3 or 6 (Single cycle operation) 06-32~06-35= 1 (Forward) 06-36~06-47= 0 Other parameter = Enter same setting as that of Example 1.
06-00= 1 to 3: After a stop the inverter will restart with the incomplete step when the run command is re-applied. 06-00= 4 to 6: After a stop the inverter will restart with the first step of the cycle when the run command is re-applied.
Notes: - Acceleration/ deceleration time is set with the setting of 00-14 and 00-15 in the automatic operation mode. - If the setting value of parameters 06-16~06-31 is 0, automatic operation mode is not active.
Figure4.4.54 Single cycle automatic operation(continuous): Freq. steps15Hz05-01/20s06-16,30Hz06-01/25s06-17,50Hz06-02/30s06-18,then20Hz below baseline06-15/40s06-31 and continues. Source plot retained despite inconsistent forward-stage settings in prose.
Automatic restart comparison graphic: left06-00=1 to3, Operation Command RUN/STOP/RUN and Output Frequency versus t, caption Continue with incompleted step cycle. Right06-00=4 to6, Operation Command RUN/STOP/RUN and Output Frequency versus t, caption Start new cycle. No unlabelled speeds or times inferred.
Manual — Automatic frequency and time settings — page 316
Manual reference: physical PDF page 316. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Automatic frequency and time settings
Automatic operation frequency reference settings — PDF page 316
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Automatic operation frequency reference settings | Automatic operation frequency reference settings |
| 2 | 06-01 | Frequency setting of speed-stage 1 |
| 3 | 06-02 | Frequency setting of speed-stage 2 |
| 4 | 06-03 | Frequency setting of speed-stage 3 |
| 5 | 06-04 | Frequency setting of speed-stage 4 |
| 6 | 06-05 | Frequency setting of speed-stage 5 |
| 7 | 06-06 | Frequency setting of speed-stage 6 |
| 8 | 06-07 | Frequency setting of speed-stage 7 |
| 9 | 06-08 | Frequency setting of speed-stage 8 |
| 10 | 06-09 | Frequency setting of speed-stage 9 |
| 11 | 06-10 | Frequency setting of speed-stage 10 |
| 12 | 06-11 | Frequency setting of speed-stage 11 |
| 13 | 06-12 | Frequency setting of speed-stage 12 |
| 14 | 06-13 | Frequency setting of speed-stage 13 |
| 15 | 06-14 | Frequency setting of speed-stage 14 |
| 16 | 06-15 | Frequency setting of speed-stage 15 |
| 17 | Range | 0.00~599.00 Hz |
Automatic operation time settings — PDF page 316
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Automatic operation time settings | Automatic operation time settings |
| 2 | 06-16 | Operation time setting of speed-stage 0 |
| 3 | 06-17 | Operation time setting of speed-stage 1 |
| 4 | 06-18 | Operation time setting of speed-stage 2 |
| 5 | 06-19 | Operation time setting of speed-stage 3 |
| 6 | 06-20 | Operation time setting of speed-stage 4 |
| 7 | 06-21 | Operation time setting of speed-stage 5 |
| 8 | 06-22 | Operation time setting of speed-stage 6 |
| 9 | 06-23 | Operation time setting of speed-stage 7 |
| 10 | 06-24 | Operation time setting of speed-stage 8 |
| 11 | 06-25 | Operation time setting of speed-stage 9 |
| 12 | 06-26 | Operation time setting of speed-stage 10 |
| 13 | 06-27 | Operation time setting of speed-stage 11 |
| 14 | 06-28 | Operation time setting of speed-stage 12 |
| 15 | 06-29 | Operation time setting of speed-stage 13 |
| 16 | 06-30 | Operation time setting of speed-stage 14 |
| 17 | 06-31 | Operation time setting of speed-stage 15 |
| 18 | Range | 0.0~6000.0 Sec |
Manual — Automatic direction settings — page 317
Manual reference: physical PDF page 317. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Automatic direction settings
Automatic operation direction settings — PDF page 317
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Automatic operation direction settings | Automatic operation direction settings |
| 2 | 06-32 | Operation direction selection of speed-stage 0 |
| 3 | 06-33 | Operation direction selection of speed-stage 1 |
| 4 | 06-34 | Operation direction selection of speed-stage 2 |
| 5 | 06-35 | Operation direction selection of speed-stage 3 |
| 6 | 06-36 | Operation direction selection of speed-stage 4 |
| 7 | 06-37 | Operation direction selection of speed-stage 5 |
| 8 | 06-38 | Operation direction selection of speed-stage 6 |
| 9 | 06-39 | Operation direction selection of speed-stage 7 |
| 10 | 06-40 | Operation direction selection of speed-stage 8 |
| 11 | 06-41 | Operation direction selection of speed-stage 9 |
| 12 | 06-42 | Operation direction selection of speed-stage 10 |
| 13 | 06-43 | Operation direction selection of speed-stage 11 |
| 14 | 06-44 | Operation direction selection of speed-stage 12 |
| 15 | 06-45 | Operation direction selection of speed-stage 13 |
| 16 | 06-46 | Operation direction selection of speed-stage 14 |
| 17 | 06-47 | Operation direction selection of speed-stage 15 |
| 18 | Range | 0: Stop, 1: Forward, 2: Reverse |
Manual — Power-loss restart, reset time and attempt count — page 318
Manual reference: physical PDF page 318. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
07- Start/Stop Parameters
07-00=0: Inverter trips on “UV” fault if power loss time is greater than 8ms. 07-00=1: Inverter restarts after restarting the power at the momentary power loss. Note: When 07-00=1, inverter restore automatically the motor rotation after restarting the power even if momentary power loss occurs.
Restart time of momentary power loss is the same as Fault reset time. 07-01 <07-18: Automatic restart time interval is set by minimum baseblock time (07-18). 07-01> 07-18: Automatic restart time interval is set by fault reset time (07-01). Note: Automatic restart time interval is time of 07-18 plus 07-01 and delay time of peed search (07-22). Refer to Figure 4.4.55 for automatic restart interval.
If numbers of fault reset reaches the setting value of 07-02, then inverter stops running. So manual to restart the inverter after eliminating fault causes. When the automatic restart function is enabled the internal automatic restart attempt counter is reset based on the following actions: a) No fault occurs in 10 minutes or longer after the automatic restart b) Reset command to clear fault via input terminal or using the keypad (ex: press reset/ key) c) Power to the inverter is turned off and back on again Note: Multi-function digital output R1A-R1C, R2A-R2C, or optocoupler output can be programmed to activate during an automatic reset attempt, refer to parameter 03-11, 03-12 and 03-28.
Figure4.4.55 Automatic restart interval: ten pulses numbered1 through10; arrow07-02 points to10. First pulse-period interval labelled07-01. Native visual labels only.
Power-loss restart, reset time and attempt count
07-00 / Momentary Power Loss/Fault Restart Selection — PDF page 318
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-00 | Momentary Power Loss/Fault Restart Selection |
| 2 | Range | 0: Disable 1: Enable |
07-01 / Fault reset time — PDF page 318
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-01 | Fault reset time |
| 2 | Range | 0~7200 Sec |
07-02 / Number of restart attempts — PDF page 318
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-02 | Number of restart attempts |
| 2 | Range | 0~10 |
Manual — Automatic restart sequence and eligible fault table — page 319
Manual reference: physical PDF page 319. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Automatic restart operation: a) Fault is detected. The inverter turn off the output, displays the fault on the keypad and waits for the minimum baseblock time parameter 07-18 to expire before accepting another run / automatic restart command. b) After the minimum baseblock time (07-18) and delay time of speed search have expired, the active fault is reset and a speed search operation is performed. The time between each fault restart attempt is set by parameter 07-01. c) When the total number of restart attempts exceed the number of automatic restart attempts set in parameter 07-02, the inverter will turn off the output and the fault contact is activated. Please refer to Figure 4.4.56 for the automatic restart operation.
The automatic restart function is active for the following faults. Please note that when the fault is not listed in the table the inverter will not attempt an automatic restart.
Notes: 1. Fault restart function contains momentary power loss restart and auto reset restart. 2. Refer to chapter 10 for the details of troubleshooting and fault diagnostics. 3. Refer to speed search function (07-19~07-24) for the selection of speed search modes. Note: Automatic restart function is only active in the state of no harm to the safety or to the application devices. Warning - Excessively use of the automatic restart function will damage the inverter.
Figure4.4.56 Auto-restart operation: three stacked unlabeled traces against t. Top and middle rise and fall over the same interval; middle annotation: When07-00=1,the fault contact is active. Bottom falls to baseline during07-18,then resumes with a dip. Source provides no visible left-axis names; none inferred.
Automatic restart sequence and eligible fault table
Parameter Name / Faults / Numbers of Restart — PDF page 319
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Parameter Name | Faults | Faults | Numbers of Restart |
| 2 | 07-00 | UV (under voltage) | UV (under voltage) | Unlimited |
| 3 | 07-01 07-02 | OC (over current) OCA (over current in ACC.) OCC (over current in constant speed) OCd (over current in DEC) OL1 (motor overload) UT (Under torque detection) IPL (input phase loss) | GF (ground failure) OV (overvoltage) OL2 (Inverter overload) OT (Over-torque detection) OPL (Output phase loss) CF07 (SLV motor control setting fault) CF08 (PMSLV motor control setting fault) | Depend on parameter 07-02 |
Manual — Power-on start and DC braking in VF/SLV modes — page 320
Manual reference: physical PDF page 320. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
07-04=0, If operation switch is conducted at power up, the inverter will start automatically. 07-04=1, If operation switch is not conducted at power up, the inverter is not able to start and the warning signal of STP1 flashes. It is required to turn off the operation switch first, and then make it be conducted to start the inverter.
If 07-04=0, it will count the delay time set by 07-05 first when the inverter starts directly at power on. When the delay time is completed, it starts to run. !DANGER: When 07- 04=【0】 and the external run is set (00-02/ 00-03=1), If the operation switch is conducted at power up, the inverter starts automatically. It is suggested to turn off the power switch and operation switch at power failure to avoid the damage to the user or the machine when the inverter reconnects. Wen 07- 04=【1】 and the external run is set (00-02/ 00-03=1), If the operation switch is not conducted at power up, the inverter is not able to start and the warning signal ofSTP1 falshes. It is required to turn off the operation switch first and the delay time of direct start at power up is completed. Then make it be conducted to start th inverter.
The braking act according to the different control modes, please refer to the following descriptions: 1.Control mode: VF、VF+PG、SLV and SLV2 (00-00 = 0、1、2、6) It starts DC injection braking by the time 07-16.Deceleration to stop is according to 07-06 and 07-08. When output frequency is lower than 07-06 in deceleration time, it starts DC injection braking by the time 07-08.
Note: When 07-06 < 01-08, it starts DC injection braking by the setting frequency (01-08)
Figure4.4.57a VF,VF+PG,SLV andSLV2 DC injection braking: Output frequency versus Time; DC injection braking before acceleration for07-16 and after deceleration for07-08. Threshold label07-06(Braking start frequency) or01-08(Fmin).
Power-on start and DC braking in VF/SLV modes
07- 04 / Direct Start at Power on — PDF page 320
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07- 04 | Direct Start at Power on |
| 2 | Range | 【0】: When the external run command is enabled, direct start at power up 【1】: When the external run command is enabled, unable to direct start at power-up. |
07- 05 / Delay of Direct Start at Power on — PDF page 320
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07- 05 | Delay of Direct Start at Power on |
| 2 | Range | 【1.0~300.0】 Sec |
07-06 / DC injection braking starting frequency — PDF page 320
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-06 | DC injection braking starting frequency |
| 2 | Range | 0.0~10.0 Hz |
Manual — PMSLV short-circuit braking and SV/PMSV zero-speed operation — page 321
Manual reference: physical PDF page 321. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
2.Control mode: PMSLV (00-00=5) Set short-circuit braking time at start and DC braking time at start individually by parameter 07-34 and 07-16. Braking action at start is active to perform SC braking by the set time of 07-34 and then to perform DC braking by that of 07-16. When deceleration to stop, set short-circuit braking time at stop and DC braking time at stop individually by parameter 07-35 and 07-08. When the output frequency falls below 07-06 at deceleration, perform short-circuit braking by the set time of 07-35 and then perform DC braking by the set time of 07-08. Refer to Fig. 4.4.57b for the braking action. Note: 1. If 07-06 < 01-08, braking action is active by the set frequency of 01-08. 2. DC braking current level at start or stop is set by 07-07 on the base of inverter rated current being 100%. 3. If DC braking current level set by 07-07 is higher than the motor rated current, DC braking current level is limited to the motor rated value. 4. SC braking current level at start or stop is set by 07-36 on the base of motor rated current being 100%.
Note: When 07-06 < 01-08, it starts short-circuit braking by the setting frequency (01-08) 3. Control mode: SV and PMSV(00-00=3、4) It starts zero-speed operation by the time 07-16. Deceleration to stop is according to 07-06 and 07-08. When output frequency is lower than 07-06 in deceleration time, it starts zero-speed operation by the time 07-08.
Note: When 07-06 < 01-08, it starts zero-speed operation by the setting frequency (01-08)
Figure4.4.57b PMSLV short-circuit braking: Output Frequency versus Time. Start SC Braking07-34 then DC Braking07-16; stop SC Braking07-35 then DC Braking07-08. Threshold07-06(Braking Start Frequency) or01-08(Fmin).
Figure4.4.57c SV and PMSV zero-speed operation: Output frequency versus Time; Zero-Speed Operation before acceleration07-16 and after deceleration07-08. Threshold07-06(Braking start frequency) or01-08(Fmin).
Manual — DC braking current and times — page 322
Manual reference: physical PDF page 322. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
DC Injection braking current as percentage of the inverter rated current. Increasing this level will increase the amount of heat generated by the motor windings. Do not set this parameter higher than the level necessary to hold the motor shaft.
Duration of DC injection braking during a stop operation. DC injection braking at stop is disabled when parameter 07-08 is set to 0 sec.
Duration of DC injection braking is during a start operation. DC injection braking at start is disabled when parameter 07-16 is set to 0 sec. DC Injection Braking Operation When DC Injection braking is active DC voltage is applied to the motor, increasing the braking current and resulting in an increase in the strength of the magnetic field trying to lock the motor shaft. To enable DC injection braking during a start operation set the DC injection braking current (07-07) and the DC injection braking time (07-16) at start to a value greater than 0. DC injection braking at start can be used to prevent “wind milling effect” in fan applications. To enable DC injection braking during a stop operation set the DC injection braking current (07-07) and the DC injection braking time at stop (07-08) to a value greater than 0. Notes: - When parameter 07-16 is set to 0 sec (DC injection braking off). the inverter will start from the minimum output frequency. - Increasing the DC braking time (07-08, 07-16) can reduce the motor stop time. - Increasing the DC braking current (07-07) can reduce the motor stop time. - During stop operation: If the DC braking start frequency < minimum output frequency (01-08), DC braking is activated when the output frequency reaches the minimum output frequency level. - DC Injection braking cannot be used in sensor vector control (SV). For DC braking operation, please refer to Figure 4.4.57.
DC braking current and times
07-07 / DC injection braking current — PDF page 322
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-07 | DC injection braking current |
| 2 | Range | 0~100 % |
07-08 / DC injection braking time at stop — PDF page 322
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-08 | DC injection braking time at stop |
| 2 | Range | 0.00~100.00 Sec |
07-16 / DC injection braking time at start — PDF page 322
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-16 | DC injection braking time at start |
| 2 | Range | 0.00~100.00 Sec |
Manual — DC/short-circuit braking and stop selection — page 323
Manual reference: physical PDF page 323. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
DC braking operation can be controlled via any one of the multi-function input terminals (03-00 to 07) function 33. Refer to figure 4.4.58 for DC braking operation. DC braking current can be controlled via the multi-function analog input (04-05) function 5. Refer to Figure 4.4.44.
PMSLV is available for short-circuit braking. Short-circuit braking is the way to switch IGBT to produce braking torque. 07-06, 07-34 and 07-36 can adjust the braking process. If 07-35=0, Inverter start from the minimum frequency. The value of 07-36 is depend on differential motor rated current.(exe motor rated current is 5A, 07-36=100% is 5A) 03-00~03-07=65 can control Short-circuit braking.
When a stop command is issued the inverter stops according to the stop mode selected. There are four types of stop modes,
Figure4.4.58 DC braking operation: Output Frequency,Motor Speed andRun Command against t. Start plateau01-08(Fmin) with duration07-16. Stop threshold labelled The larger value of01-08 or07-06 and07-06; stop delay07-08; lower arrow Braking time. Run Command ends when deceleration begins. No engineering inference.
DC/short-circuit braking and stop selection
07- 34 / Start short-circuit braking time — PDF page 323
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07- 34 | Start short-circuit braking time |
| 2 | Range | 【0.00~100.00】Sec |
| 3 | 07- 35 | Stop Short-circuit braking time |
| 4 | Range | 【0.00~100.00】Sec |
| 5 | 07- 36 | Short-circuit braking current limited |
| 6 | Range | 【0.0~200.0】% |
07-09 / Stop mode selection — PDF page 323
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-09 | Stop mode selection |
| 2 | Range | 0: Deceleration to stop 1: Coast to stop 2: DC braking to stop 3: Coast to stop with timer |
Manual — Deceleration and coast-to-stop descriptions — page 324
Manual reference: physical PDF page 324. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Source clips two left trace-label beginnings in Figure4.4.59; all readable endings and other labels retained.
Note: DC braking stop (2) and coast to stop with timer (2) are not available in SV mode. 07-09=0: Deceleration to stop When a stop command is issued, the motor will decelerate to the minimum output frequency (01-08) Fmin and then stop. Deceleration rate depends on the deceleration time (factory default: 00-15). When the output frequency reaches the DC braking stop frequency (07-06) or the minimum output frequency (01-08), DC injection braking is activated and the motor stops. Note: S curve setting will add to the overall stop time
07-09=1: Coast to stop When a stop command is issued, the motor will coast to a stop. Stop time depends on motor load and friction of the system. The inverter waits for the time set in the minimum baseblock time (07-18) before accepting the next run command. In SLV mode (00-00=2) the speed search function is automatically enabled upon the next run command. Note: When using a mechanical brake set parameter 07-26 to 1 (Software version 1.3 or later).
Source formula: Deceleration time = [Output frequency when stop command is issued / Maximum output frequency Fmax(01-02)] × deceleration time setting.
Figure4.4.59 Deceleration to stop: source raster clips the beginnings of the two left trace labels; readable endings include “… Command” and “… Frequency”; preceding letters are clipped. Other labels: Run,Stop,Time,Deceleration Ramp to stop,07-06,T; T:DC Braking Time at stop(07-08). No reconstruction of clipped label beginnings; narrow partial scope retained.
Manual — Coast and DC stop diagrams — page 325
Manual reference: physical PDF page 325. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
07-09=2: DC braking to stop When a stop command is issued, the inverter will turn off the output (Baseblock) and after the minimum Baseblock time (07-18) has expired activate DC braking (07-07). Refer to Figure 4.4.61. The DC braking time (tDCDB) of Figure 4.4.61 is determined by the value of 07-08 (DC Braking start time) and the output frequency at the time the stop command was issued. (07-08) x 10 x output frequency Fmax (01-02) Note: Increase the minimum Baseblock time (07-18) in case an Overcurrent trip occurs during the DC braking.
Figure4.4.60 Coast to stop: Run Command has Run/Stop/Run versus Time; Output Frequency falls abruptly, stays at baseline through t_b.b,then rises. Minimum baseblock time(07-18) arrow spans the low-frequency interval. No unlabelled value inferred.
Source formula: t_DCDB = [(07-08) ×10 × output frequency] / Fmax(01-02).
Figure4.4.61 DC braking to stop: left Output frequency/Time traces labelled Run,Stop,t_b.b andt_DCDB; legend t_b.b:Minimum baseblock time(07-18),t_DCDB:DC braking time. Right t_DCDB versus Maximum output frequency(Fmax,01-02),10% and100%; ordinate07-08×1 at10%,07-08×10 at100%. Arrow Output frequency upon stop command. No values interpolated.
Manual — Coast-to-stop with timer — page 326
Manual reference: physical PDF page 326. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
07-09=3: Coast to stop with timer When a stop command is issued the motor will coast to a stop after the minimum Baseblock time (07-18) has expired. The inverter ignores the run command until the total time of the timer has expired. The total time of the timer is determined by the deceleration time (00-15, 17, 22 or 24) and the output frequency upon stop. Refer to Figure 4.4.62
Figure4.4.62 Coast to stop with timer: left Run/Stop/Run/Stop/Run and Output frequency versus Time; intervalT1:Total Time. RightT1 versus Maximum output frequency(Fmax,01-02) with10% and100%,minimum baseblock Time t_b.b(07-18) andDeceleration Time(e.g.00-15); arrow Output frequency upon stop command. Labels retained without calculating timers.
Manual — Low-voltage detection and pre-excitation settings — page 327
Manual reference: physical PDF page 327. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Adjust the 07-13 voltage level from 150 to 300 Vdc (200V class) or from250 to 600 Vdc (400V class). When the AC input voltage is lower than the 07-13 value (07-13/ 1.414 = AC voltage detection level) for the time specified in 07-25 the low-voltage error "UV" will displayed. If 07-25 = 0.00 sec., the UV error will be displayed immediately. Set preventive measures: - The inverter input voltage will limit the output voltage. If the input voltage drops excessively, or if the load is too big, the motor may stall. - If the input voltage drops below the value set in 07-13 then the output is turned off momentarily. The inverter will not automatically start when power is restored.
If a high starting torque is required for the application, especially for a large horsepower motors, the pre-excitation operation can be used to pre-flux (magnetize) the motor. Pre-excitation time (07-14) When an operation command (forward or reverse) is activated, the inverter will automatically start pre-excitation based on the time set in parameter 07-14. The time for the flux to reach 100% is a function value of motor’s electrical time constant (See figure 4.4.63). Electrical time constant (quadratic by-pass circuit time constant) can be calculated by motor parameter setting (group 02) Set the pre-excitation time (07-14) based on the electrical time constant T2 Pre-excitation initial level (07-15) Use the pre-excitation initial level (07-15) to provide a higher excitation current during the pre-excitation time (07-14), which will increase the speed and stability for motors. In order to quickly magnetize the motor, reduce the pre-excitation time (07-14) and set the pre-excitation level
Source formula: Electrical time constant T2 = [Motor leakage inductance(02-17) + motor mutual inductance(02-18)] / Motor rotor resistance(02-16).
Low-voltage detection and pre-excitation settings
07-13 / Low voltage detection level — PDF page 327
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-13 | Low voltage detection level |
| 2 | Range | 200V: 150~210Vdc 400V: 300~420Vdc 575V: 500~600Vdc 690V: 500~600Vdc |
07-25 / Low voltage detection time — PDF page 327
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-25 | Low voltage detection time |
| 2 | Range | 0.00~1.00 Sec |
07-14 / Pre-excitation time — PDF page 327
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-14 | Pre-excitation time |
| 2 | Range | 0.00~10.00 Sec |
07-15 / Pre-excitation level — PDF page 327
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-15 | Pre-excitation level |
| 2 | Range | 50~200 % |
Manual — Pre-excitation operation — page 328
Manual reference: physical PDF page 328. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(07-15) to a high level. If 07-15 is set greater than 100%, providing a high excitation current during the pre-excitation time (07-14), motor’s magnetization time is shorted. When the setting reaches 200%, magnetization is reduced by roughly half. A high pre-excitation level (07-15) might result in excessive motor sound during pre-excitation. When the flux reaches 100%, pre-excitation current reverts back to 100% and pre-excitation is completed.
Figure4.4.63 Pre-excitation operation: Run Command,Magnetic flux and Excitation current,Motor Speed traces versus t. Excitation current begins at Pre-excitation initial Level(07-15),then falls to100% when Magnetic flux reaches100%. Motor Speed begins rising after Pre-excitation Time07-14. No unlabelled times inferred.
Manual — Minimum baseblock and speed search currents — page 329
Manual reference: physical PDF page 329. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
In case of a momentary power failure, the inverter continues to operate after the power has been restored when parameter 07-00 is set to 1. Once the momentary power failure is detected; the inverter will automatically shut down the output and maintain B.B for a set time (07-18). It is expected that after the minimum base block time has expired the residual voltage to be almost zero. When the momentary power failure time exceeds the minimum base block time (07-18), the inverter will automatically perform a speed search upon return of power. Refer to the following figure 4.4.64.
Minimum base block time (07-18) is also used to for the DC braking function in combination with speed search as follows: - Set the minimum base block time required (07-18). - Execute speed search or DC braking function. - Increase minimum Baseblock time if over-current "OC" condition occurs. - After speed search is completed, normal operation continues.
Figure4.4.64 Minimum B.B time and momentary power loss time: paired traces Momentary power loss,Minimum B.B.Time(07-18),Inverter B.B.time versus t. Panel(a)minimum baseblock time greater than momentary power-loss time; panel(b)shorter. Both show inverter B.B. spanning the longer illustrated interval; no numeric duration inferred.
Minimum baseblock and speed search currents
07-18 / Minimum base block time — PDF page 329
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-18 | Minimum base block time |
| 2 | Range | 0.1~5.0 Sec |
07-19 / Speed Direction Search Operating Current — PDF page 329
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-19 | Speed Direction Search Operating Current |
| 2 | Range | 0~100 % |
07-20 / Speed Search Operating Current — PDF page 329
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-20 | Speed Search Operating Current |
| 2 | Range | 0~100 % |
07-21 / Integral time of speed searching — PDF page 329
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-21 | Integral time of speed searching |
| 2 | Range | 0.1~10.0 Sec |
Manual — Speed search mode settings — page 330
Manual reference: physical PDF page 330. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Speed search function is used to find the speed of a coasting motor and continue operation from that point. The speed search function is active after a momentary power loss. In V / F + PG or SV control mode (with PG control) speed search starts from the detected frequency (PG). Speed Search from Multi-function digital inputs Set the multi-function digital input to external speed search command 1 or 2. External speed search command 1 (value = 19) and 2 (value = 34) cannot be set at the same time, otherwise "SE02" (digital input terminal error) warning occurs. Speed search function must be enabled before applying the run command to ensure proper operation. See relay logic in figure 4.4.65.
Speed search mode settings
07-22 / Delay time of speed searching — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-22 | Delay time of speed searching |
| 2 | Range | 0.0~20.0 Sec |
07-23 / Voltage recovery time — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-23 | Voltage recovery time |
| 2 | Range | 0.1~5.0 Sec |
07-24 / Direction-Detection Speed Search Selection — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-24 | Direction-Detection Speed Search Selection |
| 2 | Range | 0: Disable 1: Enable |
07-26 / SLV Speed Search Function — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-26 | SLV Speed Search Function |
| 2 | Range | 0: Enable 1: Disable |
07-27 / Start Selection after fault during SLV mode — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-27 | Start Selection after fault during SLV mode |
| 2 | Range | 0: Start with speed search 1: Normal start |
07-28 / Start after external base block — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-28 | Start after external base block |
| 2 | Range | 0: Start with speed search 1: Normal start |
07-32 / Speed Search Mode Selection — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-32 | Speed Search Mode Selection |
| 2 | Range | 0: Disable 1: Mode1: Execute a Speed Search at Power On 2: Execute a Speed Search each time |
07-33 / Start Frequency of Speed Search Selection — PDF page 330
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-33 | Start Frequency of Speed Search Selection |
| 2 | Range | 0: Maximum Output Frequency of Motor 1: Frequency Command |
Manual — Speed-search command and operating restrictions — page 331
Manual reference: physical PDF page 331. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Notes: Speed Search Operation - The speed search cannot be used when the motor rated power is greater than the inverter rated power. - The speed search cannot be used when the motor rated power is two inverter sizes smaller than the inverter currently used. - The speed search cannot be used in combination with a high-speed motor. - If speed search function is used and the control mode is in V / F mode, it is necessary to perform a static auto-tune. - If speed search function is used and the control mode is in SLV mode, it is necessary to perform a rotational auto-tune. Perform a static auto-tune when using long motor leads. Speed search uses current detecting. Use parameter 07-24 to select detection direction. 07-19: Speed Direction Search Operating Current - Used in bidirectional speed search only (07-24 = 1). - Set bidirectional current level. - Increase value if speed search is not successful at low speeds (above 5Hz) Note: If value is too high may cause DC braking effect. 07-20: Speed Search Operating Current - Can be used for bidirectional (07-24 = 1) or unidirectional (07-24 = 0) speed search. - Sets speed search current Level. - The set value must be lower than the excitation current (02-09) and must equal to the no-load current. If the no-load current is unknown it is recommended to set value at 20%. - Excessive speed search current will cause inverter output to saturate. - It is recommended to use speed search in case of a momentary power loss. Increase the minimum base block time (07-18) in case of an over-current condition. 07-21: Integral time of speed searching - Can be used for bidirectional (07-24 = 1) or unidirectional (07-24 = 0) speed search. - Set the integral time during speed search. - If OV occurs, increase the set value to increase the speed search time. Decrease the value if a quick start is required 07-22: Delay time of speed searching - Use delay time when using a contactor on the inverter output side. - The inverter speed search starts after the delay time expires. - Speed search delay time is disabled when set to 0.0 sec. (07-22 = 0.0)
Figure4.4.65 Speed search and operation commands: upper relay Ry1 with Speed search command; lower contact Rv1 and relay Ry2 with Run command. Labels retain source spelling Ry1/Rv1; no circuit reconstruction.
Manual — Speed-search direction and start modes — page 332
Manual reference: physical PDF page 332. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
07-23: Voltage recovery time - Sets the voltage recovery time. - Sets the time for the inverter to restore the output voltage from 0V to the specified V/f level after speed search function is completed. 07-24: Direction-Detection Speed Search Selection 0: Disable Direction-Detection Speed Search Speed search is executed using speed search operating current defined in parameter 07-20. In case speed search is not successful (e.g. motor speed is too low) a speed search time-out warning is displayed. Set 07-19 to value greater than 0 to enable DC braking at speed search if a time-out occurs frequently. 1: Enable Direction-Detection Speed Search At start the current controller will send a step current to the motor (07-19) to determine the motor direction. Once direction is determined the current controller will perform a speed search using speed search operating current defined in parameter 07-20. Speed search is executed after a momentary power loss (external speed search command 2, 03-00 to 03-07 = 34) or from max. frequency (external speed search command 1, 03-00 to 03-07 = 19). Speed search direction will follow the speed command. 07-26: SLV Speed Search Function - In SLV mode (00-00 = 2) set the stop mode to the coast stop (07-09 = 1) or to the coast to stop with timer (07-09 = 3). After a stop command is issued (coast to stop or coast to stop with times) the speed search function is automatically activated for the next start. 0: Enable (No mechanical brake is installed) 1: Disable (Mechanical brake is installed) 07-27: Start Selection after fault during SLV mode 0: Speed search start: Speed search is executed after a fault in SLV mode. 1: Normal start: Speed search is not enabled. Note: Set the parameter to 1 (normal start) after a fault has occurred and a mechanical brake is used to stop the motor. 07-28: Start after external Baseblock 0: Speed search start: Speed search is executed after base block is removed. 1: Normal start: Speed search is not enabled. Note: Set parameter to 1 for control mode is V/F (00-00 = 0) or SLV mode (00-00 = 2) when the external base block active time is longer than the time the motor needs to come to a complete stop. After the external base block command is removed the inverter will accelerate from min. frequency.
Manual — Speed-search mode and starting timing — page 333
Manual reference: physical PDF page 333. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
07-32: Speed Search Mode Selection 0: Disable: The inverter start to run from the lowest output frequency but it won’t limit the other functions of trigger speed search. 1: Mode1: Execute a Speed Search at Power On: The inverter executes a speed search at power on when entering first run command. It start the motor from found frequency. 2: Execute a Speed Search each time: When PM motor performs speed search, it is recommended to reduce the set value of 20-00 and 20-02 at motor jittering. 07-33: Start Frequency of Speed Search Selection 0: Maximum Output Frequency of Motor: The inverter start speed search from the maximum output frequency of motor. 1: Frequency Command: The inverter start speed search from setting frequency command. ■ Speed search based on current detection (a) Speed search at starting
(b) Speed search in recovery period of momentary power failure
Figure4.4.66 Speed search at starting. Traces Run command, Search command, Output frequency, Output voltage, Output current; axes t. Labels07-18 minimum interval, Speed search decel time(07-21), V/f during speed search, Return to voltage at normal operation, Voltage recovery time(07-23), current07-20 and Speed search operation. Search command precedes run command in shown example; no extra numerical timing inferred.
Manual — Power-loss speed-search and DC-braking run selection — page 334
Manual reference: physical PDF page 334. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Notes: If the minimum base block time (07-18) is longer than the momentary power failure time, the speed search starts operation after the minimum base block time (07-18). If the minimum base block time (07-18) is too short, the speed search operation begins immediately after power has been restored.
When DC braking is active, then: 07-29=0: Inverter does not run again until DC braking stops. 07-29=1: Inverter can run again even if DC braking is in action.
When the output voltage saturation causes the abnormal motor running and then jittering, user can increase the set value of 07-42 to limit the output voltage. When the value of 07-42 is set too large, insufficient torque may occur. User can decrease the set value to improve this situation.
Figure4.4.67 Speed search in recovery period of momentary power failure. Traces Momentary power loss, Minimum b.b.time(07-18), Run command, Search command, Output frequency, Output voltage, Output current, t. Labels07-18; Speed search decel time(07-21); V/f during speed search; Return to voltage at normal operation; Voltage recovery time(07-23);07-20; Speed search operation.
Power-loss speed-search and DC-braking run selection
07-29 / Run Command Selection at the Action of DC Braking — PDF page 334
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-29 | Run Command Selection at the Action of DC Braking |
| 2 | Range | 【0】: Not Allowable to Run 【1】: Allowable to Run |
07-42 / Voltage Limit Gain — PDF page 334
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-42 | Voltage Limit Gain |
| 2 | Range | 【0.0~50.0】% |
Manual — PM speed-search braking and STP2 — page 335
Manual reference: physical PDF page 335. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
If the motor is in a rotating state due to inertia or the like and the rotation speed is far below the minimum speed control range, parameter 07-43 and 07-44 is set to perform the braking to stop motor and then restart. If the motor is in a rotating state due to inertia or the like and the rotation speed is higher than the minimum speed control range, the inverter directly finds the frequency to start regardless of the set value of 07-43 or 07-44. If parameters 07-43 and 07-44 are set to 0, the inverter finds the frequency to start after the speed search regardless of the motor’s rotation speed.
If STP2 is enabled, when 00-02=1 and external operation signal is tripped, keypad will display “Terminal STOP” error when stop command comes from keypad. If STP2 is disabled, when 00-02=1 and external operation signal is tripped, keypad will not display “Terminal STOP” error when stop command comes from keypad.
In manual pulse generator mode, when the output frequency is lower than the minimum output frequency (01-08) of motor 1, the DC current will be injected to brake, the unit of this parameter is the percentage of the motor 1 rated current (02-01).
If switch the three-speed speed switching according to the following figure, use the 00-25 (acceleration/deceleration switching frequency) ≠0 and 22-11 (I/f mode starting frequency switching point) parameters for frequency switching acceleration and deceleration: Invalid: Please refer to the 00-25 parameter frequency for speed switching. Mode 1: After the power is turned on, the speed can be switched, and the speed is switched according to the following figure. Mode 2: The speed switching of the following figure can be realized only for the first operation, but the 22-11 switching will be invalid when decelerating.
PM speed-search braking and STP2
07-43 / Short-circuit Braking Time of PM Speed Search — PDF page 335
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-43 | Short-circuit Braking Time of PM Speed Search |
| 2 | Range | 【0.00~100.00】Sec |
| 3 | 07-44 | DC Braking Time of PM Speed Search |
| 4 | Range | 【0.00~100.00】Sec |
07-45 / STP2 function selection — PDF page 335
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-45 | STP2 function selection |
| 2 | Range | 【0】:STP2 is enabled 【1】:STP2 is disabled |
07-46 / DC injection current limit — PDF page 335
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07-46 | DC injection current limit |
| 2 | Range | 0 ~ 150% |
07- 47 / PM Speed Switching Frequency Mode — PDF page 335
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 07- 47 | PM Speed Switching Frequency Mode |
| 2 | Range | 【0】: Disabled 【1】: Mode 1 【2】: Mode 2 |
Manual — PM switching-frequency timing — page 336
Manual reference: physical PDF page 336. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: When 00-25≠0, the switching frequency can't be less than the 22-11 parameter frequency setting, and this parameter is enabled only in PMSLV mode.
PM speed switching timing: Output Frequency versus time, levels00-25 and22-11. Rising intervals Tacc3 Rate(00-21),Tacc1 Rate(00-14),Tacc4 Rate(00-23); falling intervals source-labelled Tacc4 Rate(00-25),Tdec1 Rate(00-15),Tdec3 Rate(00-22). Preserve source Tacc4/00-25 on falling segment without correction.
Manual — Protection parameters and stall-prevention bits — page 337
Manual reference: physical PDF page 337. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
08-Protection Parameters
Note: Stall prevention function only can be set in V/F control mode. Stall prevention during acceleration (08-00=xxx0b) (1) Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when accelerating with heavy loads.
(2) When the inverter output current reaches the level set in parameter 08-01 minus 15% the acceleration rate starts to decrease. When the inverter output current reaches the level set in parameter 08-01 the motor stops accelerating. (3) Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the motor power is smaller than the inverter rating.
Protection parameters and stall-prevention bits
08-00 / Stall prevention function. — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-00 | Stall prevention function. |
| 2 | Range | xxx0b: Stall prevention function is enabled during acceleration. xxx1b: Stall prevention function is disabled during acceleration. xx0xb: Stall prevention function is enabled during deceleration. xx1xb: Stall prevention function is disabled during deceleration. x0xxb: Stall prevention function is enabled during operation. x1xxb: Stall prevention function is disabled during run. 0xxxb: Stall prevention function during run is based on the first deceleration time. 1xxxb: Stall prevention function during run is based on the second deceleration time. |
08-01 / Stall prevention level during acceleration — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-01 | Stall prevention level during acceleration |
| 2 | Range | 20~200 % |
08-02 / Stall prevention level during deceleration — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-02 | Stall prevention level during deceleration |
| 2 | Range | 200V: 330V~410V 400V: 660V~820V 575V: 900~1000 V 690V: 1080~1200 V |
08-03 / Stall prevention level during run — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-03 | Stall prevention level during run |
| 2 | Range | 30~200 % |
08-21 / Limit of stall prevention during acceleration — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-21 | Limit of stall prevention during acceleration |
| 2 | Range | 1~100 % |
08-22 / Stall prevention detection time during run — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-22 | Stall prevention detection time during run |
| 2 | Range | 2~100 msec |
08-40 / Motor2 acceleration stall prevention level — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-40 | Motor2 acceleration stall prevention level |
| 2 | Range | 20~200 % |
08-41 / Motor2 acceleration stall prevention limit — PDF page 337
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-41 | Motor2 acceleration stall prevention limit |
| 2 | Range | 1~100 % |
Manual — Stall-prevention acceleration and constant-power limit — page 338
Manual reference: physical PDF page 338. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
If the motor is used in the constant power (CH) region, the stall prevention level (08-01) is automatically reduced to prevent the stall. Stall prevention level during acceleration (Constant horsepower)
Parameter 08-21 is the stall prevention limit value in Constant Horsepower region. Refer to figure 4.4.69.
Motor2 Acceleration Stall Prevention Level (08-40) and Motor2 Acceleration Stall Prevention Limit (08-41) are Used when 03-00~03-07=40 (Switching between Motor 1/Motor 2) Stall prevention selection during deceleration (08-00=xx0xb) Stall prevention during deceleration automatically increases the deceleration time according based on the DC-bus voltage to prevent over-voltage during deceleration. Refer to Figure 4.4.69 for stall prevention during deceleration When the DC-bus voltage exceeds the stall prevention level deceleration will stop and the inverter will wait for the DC-bus voltage to fall below the stall prevention level before continuing deceleration. Stall prevention level can be set by 08-02, see Table 4.4.34.
Figure4.4.68 Stall prevention during acceleration: Inverter Output Current with08-01 and15% separation; Output Frequency trace; Stall prevention interval; t axes. Frequency ramp pauses during marked interval.
Source formula: Stall Prev.Lev.Acceleration(CH) = [Stall prevention level in acceleration(08-01) × Fbase(01-12)] / Output frequency.
Figure4.4.69 Stall prevention level and limit in acceleration. Vertical Stall prevention level during acceleration; horizontal Output frequency. Constant Torque region and Constant Horsepower region. Upper level08-01, lower limit08-21; descending curved extension shown dashed below limit, no unlabelled values inferred.
Manual — Deceleration and running stall prevention — page 339
Manual reference: physical PDF page 339. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.34 Stall prevention level
Note: When using external braking (braking resistor or braking module) disable stall prevention during deceleration (08-00 to xx1xb).
Stall prevention selection during run (08-00=x0xxb) Stall prevention during run can only be used in V/F or V/F + PG and SLV2control mode. This function prevents the motor from stalling by automatically reducing the output frequency during run. If the inverter output current rises above the level set in parameter 08-03 for the time specified in parameter 08-22, the inverter output frequency is automatically decreased following deceleration time 1 (00-15) or deceleration time 2 (00-17). When the inverter output current falls below the level set in parameter (08-03) minus 2%, normal operation continues and the output frequency increases to the frequency reference using the acceleration time 1 or acceleration time 2. Refer to the following figure 4.4.71. Note: The stall prevention level during run can be set by using multi-function analog input AI2 (04-05=7).
Figure4.4.70 Stall prevention selection in deceleration. Output frequency versus t; staircase descending trace and dashed straight reference. Labels Deceleration time is extended to prevent overvoltage and Deceleration time.
Deceleration and running stall prevention
Inverter model / 08-02 default value — PDF page 339
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Inverter model | 08-02 default value |
| 2 | 200V class | 385VDC |
| 3 | 400V class | 770VDC |
| 4 | 575V class | 950VDC |
| 5 | 690V class | 1140VDC |
Manual — Running stall prevention and motor-overload selection — page 340
Manual reference: physical PDF page 340. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Stall prevention level in operation is set by multi-function analog input AI2 (04-05=7).
The motor overload protection function estimates the motor overload level based on the output current, output frequency, motor characteristics and time. The motor overload trip time depends on the motor rated current when the output frequency is greater than 60Hz. On inverter power-up the motor overload protection internal thermal accumulation register is automatically reset. To use the built-in motor overload protection function parameter 02-01 (motor rated current) has to match the motor rated current on the motor nameplate. Turn off the motor overload protection when using two or more motors connected to the inverter (set 08-05 = xxx0b), and provide external overload protection for each motor (e.g. thermal overload switch).
Figure4.4.71 Stall prevention selection in operation: Load versus t, Inverter Output Current with08-03 and2%(Hysteresis), Output Frequency with two recovery traces Tdec1(00-15),Tdec2(00-17),08-22(detection time).
Running stall prevention and motor-overload selection
08-05 / Selection for motor overload protection (OL1) — PDF page 340
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-05 | Selection for motor overload protection (OL1) |
| 2 | Range | xxx0b: Motor overload is disabled xxx1b: Motor overload is enabled xx0xb: Cold start of motor overload xx1xb: Hot start of motor overload x0xxb: Standard motor x1xxb: Special motor 0xxxb: Reserved 1xxxb: Reserved |
| 3 | 08-07 | Motor Overload (OL1) Protection Level |
| 4 | Range | 【0】:Motor Overload (OL1) Protection 0 【1】:Motor Overload (OL1) Protection 1 【2】:Motor Overload (OL1) Protection 2 |
Manual — Motor-overload curves settings0 and1 — page 341
Manual reference: physical PDF page 341. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
With cold start enabled (08-05 = xx0xb), motor overload protection occurs in 5 and a half minutes when operating the motor at 150% of the motor rated current at an output frequency greater than 60Hz. With hot start enabled (08-05 = xx1xb), motor overload protection occurs in 3 and a half minutes when operating the motor at 150% of the motor rated current at an output frequency greater than 60Hz. Refer to the following figure 4.4.72 for an example of motor overload protection standard curve. And refer to the setting of 08-07 (Motor overload (OL1) protection level), the overload curve will be different. 08-07=0:
08-07=1:
Figure4.4.72 example standard-motor overload curve;08-07=0;Low Speed;Hot Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 100:7.9, 150:2.9, 200:1.5. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=0;Low Speed;Cold Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 100:12.4, 150:4.5, 200:2.4. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=0;High Speed(60Hz);Hot Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 106:28.8, 150:3.9, 200:1.7. First point labelled start activated point. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=0;High Speed(60Hz);Cold Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 106:45.2, 150:6.1, 200:2.7. First point labelled start activated point. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=1;Low Speed(1.5Hz);Hot Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 100:8.9, 150:3.2, 200:1.7. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=1;Low Speed(1.5Hz);Cold Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 100:14.9, 150:5.3, 200:2.8. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=1;High Speed(60Hz);Hot Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 116:30.9, 150:4.2, 200:1.9. First point labelled start activated point. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=1;High Speed(60Hz);Cold Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 116:51.6, 150:7.1, 200:3.2. First point labelled start activated point. These are plotted example labels, not interpolated operating ratings.
Manual — Motor-overload curves setting2 and motor types — page 342
Manual reference: physical PDF page 342. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
08-07=2:
Figure 4.4.72 Motor overload protection curve (example: standard motor) When using force cooled motors (Special inverter motor), thermal characteristics are independent of the motor speed, set 08-05 = x1xxb. When 08-05 = x1xxb, overload protection function is based on motor rated current for output frequencies between 6 and 60Hz. If the output frequency is lower than 1Hz, the overload protection function uses 83% of the motor rated current to determine an overload condition. When 08-05 = x0xxb, overload protection function is based on 70% of the motor rated current for an output frequency of 20Hz. If the output frequency is lower than 1Hz, the overload protection function uses 40% of the motor rated current to determine an overload condition. Motor overload rating at different output frequencies is shown at Figure 4.4.73.
Figure4.4.72 example standard-motor overload curve;08-07=2;Low Speed(1.5Hz);Hot Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 100:9.9, 150:3.5, 200:1.9. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=2;Low Speed(1.5Hz);Cold Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 100:17.8, 150:6.3, 200:3.4. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=2;High Speed(60Hz);Hot Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 116:34.4, 150:4.7, 200:2.1. First point labelled start activated point. These are plotted example labels, not interpolated operating ratings.
Figure4.4.72 example standard-motor overload curve;08-07=2;High Speed(60Hz);Cold Start. Horizontal Motor Load Current(%),02-01=100%; vertical Overload Protect Time(min). Printed guide intersections/current%:time min 116:61.9, 150:8.5, 200:3.8. First point labelled start activated point. These are plotted example labels, not interpolated operating ratings.
Manual — Motor-overload frequency rating and AVR — page 343
Manual reference: physical PDF page 343. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
08-06=0: When the inverter detects a motor overload the inverter output is turned off and the OL1 fault message will display on the keypad. Press RESET button on the keypad or activate the reset function through the multi-function inputs to reset the OL1 fault. 08-06=1: When the inverter detects a motor overload the inverter will continue running and the OL1 alarm message will flash on the keypad until the motor current falls within the normal operating range.
Automatic voltage regulation stabilizes the motor voltage independent of fluctuation to the input voltage. 08-08=0: Automatic voltage regulation is active. It will limit the maximum output voltage. When input three-phase voltage fluctuates and the voltage is smaller than the value of 01-14, the output voltage will fluctuate with the fluctuation of input voltage. 08-08=1: Automatic voltage regulation is not active, motor voltage follows the input voltage fluctuation. When input three-phase voltage fluctuates, the output voltage won’t fluctuate with the fluctuation of input voltage.
Figure4.4.73 Motor overload rating at different output frequencies. Vertical Motor Overload Rating0–100% in10% ticks; horizontal Output Frequency0,10,20,30,40,50,60. Solid Standard Motor(08-05=x0xxb) passes labelled graph levels40% at0,70% at20,100% at60; dashed Special Motor(08-05=x1xxb) rises to100%; no exact joining frequency is labelled on the graph; exact low-frequency threshold values are stated separately in source prose, not interpolated here.
Motor-overload frequency rating and AVR
08-06 / Start-up mode of overload protection operation (OL1) — PDF page 343
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-06 | Start-up mode of overload protection operation (OL1) |
| 2 | Range | 0: Stop output after overload protection 1: Continuous operation after overload protection. |
08-08 / Automatic voltage regulation (AVR) — PDF page 343
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-08 | Automatic voltage regulation (AVR) |
| 2 | Range | 0: AVR is enabled 1: AVR is disabled |
Manual — Phase-loss and torque-detection selections — page 344
Manual reference: physical PDF page 344. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
08-09=0: Input phase loss detection is disabled. 08-09=1: Input phase loss detection is enabled. Keypad shows "IPL input Phase Loss" (IPL), when an input phase loss is detected the inverter output is turned off and the fault contact is activated. Note: The input phase loss detection is disabled when the output current is less than 30% of the inverter rated current.
08-10=0: Output phase loss detection is disabled. 08-10=1: Output phase loss detection is enabled. Keypad shows "OPL Output Phase Loss" (OPL), when an output phase loss is detected and the inverter output is turned off and the fault contact is activated. Note: The output phase loss detection is disabled when the output current is less than 10% of the inverter rated current.
Phase-loss and torque-detection selections
08-09 / Selection of input phase loss protection — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-09 | Selection of input phase loss protection |
| 2 | Range | 0: Disable 1: Enable |
08-10 / Selection of output phase loss protection — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-10 | Selection of output phase loss protection |
| 2 | Range | 0: Disable 1: Enable |
08-13 / Selection of over-torque detection — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-13 | Selection of over-torque detection |
| 2 | Range | 0: Over-torque detection is disabled 1: Start to detect when reaching the set frequency 2: Start to detect when the operation is begun |
08-14 / Selection of over-torque action — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-14 | Selection of over-torque action |
| 2 | Range | 0: Deceleration to stop when over-torque is detected. 1: Displays warning when over-torque is detected. Continue operation. 2: Coast to stop when over-torque is detected |
08-15 / Level of over-torque detection — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-15 | Level of over-torque detection |
| 2 | Range | 0~300 % |
08-16 / Time of over-torque detection — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-16 | Time of over-torque detection |
| 2 | Range | 0.0~10.0 Sec |
08-17 / Selection of low-torque detection — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-17 | Selection of low-torque detection |
| 2 | Range | 0: Low-torque detection is disabled 1: Start to detect when reaching the set frequency 2: Start to detect when the operation is begun |
08-18 / Selection of low-torque action — PDF page 344
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-18 | Selection of low-torque action |
| 2 | Range | 0: Deceleration to stop when low-torque is detected 1: Display warning when low-torque is detected. Go on operation 2: Coast to stop when under-torque is detected |
Manual — Over-torque detection — page 345
Manual reference: physical PDF page 345. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The over torque detection function monitor the inverter output current or motor torque and can be used to detect increase in inverter current or motor torque (e.g. heavy load). The low torque detection function monitor the inverter output current or motor torque and can be used to detect a decrease in inverter current or motor torque (e.g. belt break). The torque detection levels (08-15, 08-19) are based on the inverter rated output current (100% = inverter rated output current) when operating the inverter in V/F control or V/F control + PG and motor output torque (100% = motor rated torque) when operating the inverter in SLV or SV control. Over-torque detection Parameter 08-13 selects over-torque detection function. An over-torque condition is detected when the output current / torque rises above the level set in parameter 08-15 (Over-torque detection level) for the time specified in parameter 08-06 (Over-torque detection time). 08-13=0: Over-torque detection is disabled. 08-13=1: Over-torque detection is enabled when the output frequency reaches the set frequency. 08-13=2: Over-torque detection is enabled during running. Parameter 08-14 selects the way the inverter acts when an over-torque condition is detected. 08-14=0: When an over-torque condition is detected the inverter displays and over-torque detection fault and the motor decelerates to a stop. 08-14=1: When an over-torque condition is detected the inverter displays an over-torque detection alarm and continues to run. 08-14=2: When an over-torque condition is detected the inverter displays and over-torque detection fault and the motor coasts to a stop
Figure4.4.74 Over-torque detection operation. Inverter output current(or motor output torque), Detection level(08-15),10% hysteresis width, Overtorque detection signal, t axes; each asserted output follows delay08-16.
Over-torque detection
08-19 / Level of low-torque detection — PDF page 345
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-19 | Level of low-torque detection |
| 2 | Range | 0~300% |
08-20 / Time of low-torque detection — PDF page 345
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-20 | Time of low-torque detection |
| 2 | Range | 0.0~10.0 Sec |
Manual — Low-torque detection and relay labels — page 346
Manual reference: physical PDF page 346. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Low-torque detection Parameter 08-18 selects low-torque detection function. An low-torque condition is detected when the output current / torque falls below the level set in parameter 08-19 (low-torque detection level) for the time specified in parameter 08-20 (Low-torque detection time). 08-17=0: Low-torque detection is disabled. 08-17=1: Low-torque detection is enabled when the output frequency reaches the set frequency. 08-17=2: Low-torque detection is enabled during running. Parameter 08-18 selects the way the inverter acts when an over-torque condition is detected. 08-18=0: When a low-torque condition is detected the inverter displays and low-torque detection fault and the motor decelerates to a stop. 08-18=1: When a low-torque condition is detected the inverter displays a low-torque detection alarm and continues to run. 08-18=2: When a low-torque condition is detected the inverter displays and low-torque detection fault and the motor coasts to a stop . Setting Example of less torque detection:
Over and low torque detection condition can be output to the multi-function digital outputs (R1A-R1C, R2A-R2C) by setting parameters 03-11 to 03-12 to 12 or 25. Refer to figure 4.4.76 for more information.
Figure4.4.75 Low torque detection operation. Inverter output current(or motor output torque), Detection Level(08-19),10% hysteresis width, Undertorque detection signal,t; delay08-20 marked on both low-torque intervals.
Figure4.4.76 Over-torque/low torque detection multi-function digital output terminal. Source labels R1A,R1B,R1C bracket03-11; R2A,R2C bracket03-12. Contact symbols and common paths visible; no inferred electrical wiring instructions.
Manual — Ground fault external fault and fan control — page 347
Manual reference: physical PDF page 347. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
08-23=1: If the inverter leakage current is greater than 50% of inverter rated current and the ground fault function is enabled (08-23), the keypad will display a "GF Ground Fault" (GF), motor will coast to a stop and fault contact is activated.
Select operation selection when an external fault occurs. Refer to the multi-function inputs on how to set up the inverter for an external fault input.
08-25=0: When the inverter is supplied by power, detection external fault function will execute. 08-25=1: When the inverter is start to run, detection external fault function will execute.
When 03-00~03-07=58, the inverter will stop by the set of 08-30
08-37=0: The inverter start to run and the fan will follow to run. If the inverter stop and the time is longer than the value of 08-38, the fan stop. If the temperature for heat sink is higher than the temperature of inside-detection and the inverter doesn’t run, the fan will start run automatically. 08-37=1: The inverter is supplied by power, the fan start to run. 08-37=2: The temperature for heat sink is higher than the temperature of inside-detection, the fan start to run. After the temperature for heat sink is lower than the temperature of inside-detection and the time is over 08-38, the fan stop. Note: There is no 08-37=2 for the models of 2050, 4100 or the above.
Ground fault external fault and fan control
08-23 / Ground Fault (GF) selection — PDF page 347
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-23 | Ground Fault (GF) selection |
| 2 | Range | 0: Disable 1: Enable |
08-24 / External fault operation selection — PDF page 347
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-24 | External fault operation selection |
| 2 | Range | 0: Deceleration to stop 1: Coast to stop 2: Continue operation |
08-25 / Detection selection of external fault — PDF page 347
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-25 | Detection selection of external fault |
| 2 | Range | 0: Immediately detect when the power is supplied 1: Start to detect during operation |
08-30 / Run permissive function selection — PDF page 347
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-30 | Run permissive function selection |
| 2 | Range | 0: Deceleration to stop 1: Coast to stop |
08-37 / Fan control function — PDF page 347
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-37 | Fan control function |
| 2 | Range | 0: Start in operation 1: Permanent start 2: Start in high temperature (except of the models of 2050, 4100 or the above) |
| 3 | 08-38 | Delay time of fan off |
| 4 | Range | 0~600 sec |
Manual — Motor-overheat and PTC protection — page 348
Manual reference: physical PDF page 348. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Motor overheat fault selection It execute motor overheat protection by the resistor (PTC) that built-in the motor. the resistor (PTC) is between AI2 and GND and a divided resistor R ,as the pic 4.3.65(b) 08-35=0: Motor overheats fault function is off. 08-35=1: When the motor is overheating, it decelerates to stop. 08-35=2: When the motor is overheating, it free runs to stop. 08-35=3: When the motor is overheating, it does not stop running until reach the value of 08-42. 08-35=1、2: When the temperature is getting higher for the motor and AI2 voltage level is higher than the value of 08-44, the display will show 『OH4 Motor Overheating』 and the motor will stop by 08-35=1、2. 08-35=3: When the temperature is getting higher for the motor and AI2 voltage level is higher than the value of 08-44, the display will show 『OH3 Motor Temp Warning』but the motor continues running. But AI2 voltage level is higher than the value of 08-42 and the time reach to 08-39, the motor free runs to stop. 08-35=1、2、3: When the motor cools down and AI2 voltage level is lower the value of 08-43, 『OH4 Motor overheat』will reset. Note: The resistor (PTC) conform the British Standards Institution:
When Tr is 150 ℃in Class F and is 180℃ in Class H。
Tr- 5℃:RT≦ 550Ω,put the value of RT in formula (1), the V value by calculation is the value of 08-43.
Tr+ 5℃:RT≧1330Ω,put the value of RT in formula (1), the V value by calculation is the value of 08-44. It gets reference value by using formula (1) even in the different spec of resistor (PTC).
Motor-overheat and PTC protection
08-35 / Motor overheat fault selection — PDF page 348
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-35 | Motor overheat fault selection |
| 2 | Range | 0: Disable 1: Deceleration to stop 2: Free run to top 3: Continue running |
| 3 | 08-36 | PTC input filter time constant |
| 4 | Range | 0.00 ~ 5.00 sec |
| 5 | 08-39 | Delay time of motor overheat protection |
| 6 | Range | 1~300 sec |
| 7 | 08-42 | PTC protection level |
| 8 | Range | 0.1~10.0V |
| 9 | 08-43 | PTC restart level |
| 10 | Range | 0.1~10.0V |
| 11 | 08-44 | PTC warning level |
| 12 | Range | 0.1~10.0V |
Manual — PTC formula and temperature switching — page 349
Manual reference: physical PDF page 349. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Partly overlaid Chinese glyph beside Resistor in PTC diagram; readable English and terminal/resistance labels retained.
Note: 08-47 maximum value will be limited by 08-46 set value The inverter temperature agree and reset level selection ‧ 03-11 set to【59】: ‧ 08-46: The inverter temperature is > 08-46, the relay operates. ‧ 08-47: When the output current is ≤ 08-47, the relay signal from ON to OFF. Down time frequency diagram:
Formula(1) as printed: V = (1/2)×10×[(R_PTC // 200)/(R+(R_PTC // 200))]. Double slash notation retained without conversion or inferred units.
Pic4.3.65(a)PTC Thermistor Characteristics;(b)PTC Thermistor Connections. Resistance(ohms) versus Temperature;1330 and550; ClassF150°C,ClassH180°C; Tr-5,Tr,Tr+5,Tr′; Tr:Temperature threshold value. Circuit labels Divider resistor R,PTC熱[partly overlaid Chinese fragment] Resistor,+10V,AI2,200KΩ,GND,內部線路. Readable labels checked with5x crop; Chinese fragment next to Resistor remains partly overlaid and unverified. No topology inferred.
Inverter temperature agree and reset detection: T(°C) versus Time; Frequency Converter Temperature curve crosses08-46 on rise and08-47 on fall;03-11 Relay trace has ON interval between crossings. Source temperature labels retained.
PTC formula and temperature switching
08-46 / Temperature agree level — PDF page 349
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-46 | Temperature agree level |
| 2 | Range | 【0 ~ 254】°C |
| 3 | 08-47 | Temperature reset level |
| 4 | Range | 【0 ~ 254】°C |
Manual — Fire-mode parameter selections — page 350
Manual reference: physical PDF page 350. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When 08-48=0, Fire Mode is disabled. When 08-48=1, Fire Mode is enabled. When fire mode is enabled, S6 will be defined to digital input of fire mode (03-0X=47). When fire mode is enabled, inverter will become to fire mode. No matter inverter is running or stopping, run and frequency command source will be covered by the setting of fire mode, keypad display will show “ FIRE ”, some of protect functions will be ignored, please refer the table 4.4.35, inverter will not stop. When fire mode (03-0X=47) and external overload (03-0X=69) function is triggered, the other digital inputs will be
ignored, the parameters just can be read by communication or keypad display. When 08-49=0, please disconnect the power first, remove external trigger signal and then connect the power. When 08-49=1, no need to disconnect the power, inverter will become to normal mode, run and frequency will return to original setting. Note: Only Version V1.30 and above will meet the above functions.
Fire-mode parameter selections
Adjacent source context — repeated to preserve continuation:
08-48 / Selection of Fire Mode — PDF page 350
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-48 | Selection of Fire Mode |
| 2 | Range | 【0】: Disable 【1】: Enable |
| 3 | 08-49 | Multi-Function Input Terminal Status of Fire Mode |
| 4 | Range | 【0】: Reset after Power Off 【1】: Reset after Terminal Removed |
| 5 | 08-50 | Multi-Function Terminal Status of Fire Mode |
| 6 | Range | 【xxx0b】: S6 A Contact 【xxx1b】: S6 B Contact |
| 7 | 08-51 | Motor Speed Setting Source of Fire Mode |
| 8 | Range | 【0】: Fire Mode Speed (08-52) 【1】: PID Control 【2】: AI2 |
| 9 | 08-52 | Fire Mode Motor Speed |
| 10 | Range | 【0.00~100.00】% |
| 11 | 08-59 | Fire Mode Motor Direction |
| 12 | Range | 【0】: Forward 【1】: Reverse |
| 13 | 08-60 | Fire Mode Password |
| 14 | Range | 【00000 ~ 65534】 |
Manual — Fire-mode exclusions danger and PID settings — page 351
Manual reference: physical PDF page 351. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.35 These functions will be ignored when fire mode is triggered
!Danger:
Fire mode: The drive will run at full speed either in forward or reverse direction and ignore all software protections until any one of the hardware protection is triggered or drive is damaged to achieve the requirement of smoke extraction and reduce the hazard to humans. Each bit of 08-50 presents an input: Notes: Please set 08-48=0 (fire mode disabled) before setting normal open or normal close contact. Failure to comply may cause death or serious injury. When 08-51=0, motor speed setting will follow 08-52. If the value of 08-52 is 100%, inverter output frequency will follow the value of 01-02.
When 08-51=1, motor speed setting will follow PID control; when fire mode is enabled, PID control will base on 10-47/10-48/10-49 (please refer the setting value of group 10) When 08-51=2, frequency reference will become to 4-20mA (default setting of 04-00) 08-59: Fire Mode Motor Direction When fire mode is enabled, motor direction will base on the setting of 08-59. 08-60: Fire Mode Password When fire mode is enabled, use can set password in parameter 08-60, please refer the process of parameter 13-07. In order to prevent the parameters of fire mode being modified, keypad display will just show the related parameters of fire mode when fire mode is enabled. (Parameter 08-48~08-60 will be read only). Parameter 08-60(password of fire mode) and 13-07(parameter password), only one parameter can be allowed to set at the same time.
08-50 displayed bit illustration: 08-50=0 0 0 0 0 : Normal open; below, s6 1 : Normal close. Source says each bit presents an input; preserve shown s6 association without inventing other terminal mappings.
Fire-mode exclusions danger and PID settings
Adjacent source context — repeated to preserve continuation:
0x2521H / Fault Description — PDF page 351
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 0x2521H | Fault Description |
| 2 | 4 | OH1 (Heat sink over heat) |
| 3 | 5 | OL1 (Motor overload) |
| 4 | 6 | OL2 (Inverter overload) |
| 5 | 7 | OT (Over torque) |
| 6 | 25 | FB (PID feedback signal error) |
| 7 | 26 | Keypad Removed |
| 8 | 28 | CE (Communication error) |
| 9 | 46 | OH4 (Motor over heat) |
| 10 | 49 | MtrSw (DI Motor Switch Fault) |
| 11 | 58 | PF(Protection error) |
08-53 / PID Detection Level of Fire Mode — PDF page 351
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-53 | PID Detection Level of Fire Mode |
| 2 | Range | 【0~100】% |
| 3 | 08-54 | Delay Time of Fire Mode PID Loss |
Manual — Fire-mode feedback-loss selections — page 352
Manual reference: physical PDF page 352. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When 08-51=1, PID feedback loss detection function will be opened automatically. When fire mode is enabled, if 08-51=1 and then PID feedback, inverter will be stopped after the setting value of 08-54. 08-55: PID Feedback Loss Detection Selection of Fire Mode When 08-55=0, output frequency will be fixed on current frequency. When 08-55=1, output frequency will be based on the setting value of parameter 08-52. When 08-55=2, output frequency will be based on the setting value of parameter 01-02. When PID feedback value less than 08-53 and then longer than 08-54, inverter will keep running, but the frequency reference will be switched to 08-55, output frequency will not less than the setting value of 08-52.
Notes: If there is no any feedback signal and then feedback loss level also be set to 0%, feedback loss detection function will not be triggered.
When 08-51=2 (AI2), inverter will trigger AI2 feedback loss detection function automatically. Selection of Fire Mode AI2 Signal Loss (08-58) :
When 08-58=0, output frequency will be fixed on current frequency. When 08-58=1, output frequency will be based on the setting value of parameter 08-52.
PID feedback loss detection: Feedback value versus t; level08-53; FBL detection trace,t1,08-54 intervals. Short first dip labelled t1 ends before08-54; later longer dip triggers rising FBL trace after08-54.
Fire-mode feedback-loss selections First row Range0.0–10.0Sec continues08-54heading at bottom of physical351; original physical geometry retained.
Fire-mode feedback-loss selections
Range / 【0.0~10.0】Sec — PDF page 352
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Range | 【0.0~10.0】Sec |
| 2 | 08-55 | PID Feedback Loss Detection Selection of Fire Mode |
| 3 | Range | 【0】:Keep Running 【1】:Fire Mode Speed(08-52) 【2】:Max. Output Frequency of Motor 1 (01-02) |
08-56 / Detection Level of Fire Mode AI2 Signal — PDF page 352
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-56 | Detection Level of Fire Mode AI2 Signal |
| 2 | Range | 【0~100】% |
| 3 | 08-57 | Delay Time of Fire Mode AI2 Signal Loss |
| 4 | Range | 【0.0~10.0】Sec |
| 5 | 08-58 | Selection of Fire Mode AI2 Signal Loss |
| 6 | Range | 【0】:Keep Running 【1】:Fire Mode Speed(08-52) 【2】:Max. Output Frequency of Motor 1 (01-02) |
Manual — Fire-mode AI2 loss timing — page 353
Manual reference: physical PDF page 353. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When 08-58=2, output frequency will be based on the setting value of parameter 01-02. If AI2 signal is less than the setting value of 08-56 in 360ms, and the time longer than setting value of 08-57, the frequency reference will be considered to loss.
Analog signal will compare with the previous value at 360ms, if inverter ensure the frequency reference already loss, frequency reference will base on the value of 08-58. Following is the description of the Frequency Loss Function: When the inverter is in operation and the selected analog command source AI2 disappears, the command will operate according to the setting ratio of 08-58. The following figure is the operating diagram of analog frequency instruction AI2 when the frequency Instruction is lost.
Fig4.3.77 AI2 frequency reference loss. Frequency Command versus t: By AI2 Setting before loss,By08-58 Setting after detection; threshold08-56;360ms interval; AI2 Loss Detection trace delayed by08-57. No missing interpolation values inferred.
Manual — Communication parameter selections — page 354
Manual reference: physical PDF page 354. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
09-Communication Parameters
The Modbus communication port RJ45 (S+, S-) can be used to monitor, control, program and trouble-shoot the inverter. Modbus communication can perform the following operations, independent of the frequency command selection (00-05) setting and Operation command selection (00-02) setting: Monitor inverter signals Read and write parameters. Reset fault Control multi-function inputs
Communication parameter selections
09-00 / INV Communication Station Address — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-00 | INV Communication Station Address |
| 2 | Range | 1~31 |
09-02 / Baud rate setting (bps) — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-02 | Baud rate setting (bps) |
| 2 | Range | 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 |
09-03 / Stop bit selection — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-03 | Stop bit selection |
| 2 | Range | 0: 1 stop bit 1: 2 stop bits |
09-04 / Parity selection — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-04 | Parity selection |
| 2 | Range | 0: No Parity 1: Even bit 2: Odd bit |
09-05 / Communication Data Bit Selection — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-05 | Communication Data Bit Selection |
| 2 | Range | 0: 8 Bit Data 1: 7 Bit Data |
09-06 / Communication error detection time — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-06 | Communication error detection time |
| 2 | Range | 0.0~25.5 Sec |
09-07 / Fault stop selection — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-07 | Fault stop selection |
| 2 | Range | 0: Deceleration to stop based on deceleration time 1. 1: Coast to stop when communication fault occurs. 2: Deceleration to stop based on deceleration time 2 3: Keep operating when communication fault occurs. |
09-08 / Comm. fault tolerance count — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-08 | Comm. fault tolerance count |
| 2 | Range | 1~20 |
09-09 / Waiting time — PDF page 354
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 09-09 | Waiting time |
| 2 | Range | 5~65 msec |
Manual — Modbus RS485 specification and setup — page 355
Manual reference: physical PDF page 355. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Modbus (RS-485) communication specification:
Communication wiring and setup (1) Turn off power to the inverter. (2) Connect communication lines of the controller to the inverter (RJ45). (3) Turn power on. (4) Set the required communication parameters (09-00) via the keypad. (5) Turn off power to the inverter and wait until keypad is completely off. (6) Turn power on (7) Start communication between controller and inverter. Modbus (485) communication architecture (1) Modbus communication configuration uses a master controller (PC, PLC), communicating to a maximum of 31 inverters. (2) The master controller is directly connected to the inverter via the RS-485 interface. If the master controller has a RS-232, a converter must be installed to convert signals to RS-485 to connect the master controller to the inverter. (3) A maximum 31 inverters can be connected to a network, following the Modbus communication standard. Communication Parameters: 09-00: Inverter station addresses: Range 1-31 09-02: RS-485 communication baud rate setting = 0: 1200 bps (bits / second) = 1: 2400 bps = 2: 4800 bps = 3: 9600 bps = 4: 19200 bps = 5: 38400 bps 09-03: Stop bit selection = 0: 1 stop bit = 1: 2 stop bits 09-04: Parity selection of RS-485 communication = 0: No parity. = 1: even parity. = 2: odd parity. 09-05: Communication Data Bit Selection = 0: 8 bits data = 1: 7 bits data
Modbus RS485 specification and setup
Items / Specification — PDF page 355
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Items | Specification |
| 2 | Interface | RS-485 |
| 3 | Communication type | Asynchronous (start - stop synchronization) |
| 4 | Communication parameters | Baud rate: 1200, 2400, 4800, 9600, 19200 and 38400 bps Data Length: 8 bits (Fixed) Parity: options of none, even and odd bit. For even and odd selection stop bit is fixed at 1 bit. |
| 5 | Communication protocol | Modbus RTU / ASCII |
| 6 | Number of inverters | Maximum 31 units |
Manual — RS485 error selection and message timing — page 356
Manual reference: physical PDF page 356. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
09-06: RS-485 communication error detection time 09-07: Stop selection of RS-485 communication failure = 1: Deceleration to stop by deceleration time 00-15 = 2: Coast to stop = 2: Deceleration to stop using the deceleration time of 00-26 (emergency stop time) = 3: Continue to operate (only shows a warning message, press the stop button to stop operation) 09-08: Comm. fault tolerance count When the number of communication errors exceeds the value set in parameter 09-08 the inverter will display the comm. Fault alarm. 09-09: Wait time of inverter transmission (09-09). Set the inverter response delay time. This is the time between the controller message and the start of the inverter response message. Refer to figure 4.4.78. Set the controller receive time-out to a greater value than the wait time parameter (09-09).
Figure4.4.78 Communication Message Timing: Master to Inverter Command Message then Inverter to Master Response Message on t axis. Gap is divided into24 bits long then09-09 setting. Preserve source interval labels without deriving baud-dependent duration.
Manual — PID target and feedback source selection — page 357
Manual reference: physical PDF page 357. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10-PID Parameters
When 10-00=1 or 2, Source of signal is proportional to be corresponding to PID target via analog input terminal. For example: 0~10V is corresponding to 0~100% target value. When being given 2V, 20% target value is obtained. When 10-00=3, PID target value is pulse input. The proportion of pulse input is set depending on the parameters of 03-30 (pulse input scales) ~ 03-34 (pulse input filter time). For general purpose of PID setting, set 10-00=4 to set the PID target value. When 10-00=4 10-02(PID target value) is set at percentage and PID setting is at main screen monitor (12-38). Maximum target value is set by parameter 10-33 (PID feedback maximum value), the decimals is determined by parameter10-34 (PID decimal width), and the unit is set by parameter 10-35 (PID unit). Ex: Set 10-33 = 999, 10-34 = 1, 10-35 = 3, and set 10-02 to 10% Then 9.9PSI is displayed at the main screen monitor (12-38) and can be modified at this monitor. Maximum value is 99.9 PSI (limited to the setting value of parameter 10-33). When 10-00=6 The current frequency command is proportional to be corresponding to PID target.
Note: Parameter 10-00 and 10-01 cannot be set to the same source. If both parameters are set to the same source the keypad will show a SE05 alarm.
PID target and feedback source selection
10-00 / PID target value source setting — PDF page 357
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-00 | PID target value source setting |
| 2 | Range | 1: AI1 given 2: AI2 given 3: Pulse given 4: Use 10-02 setting 5: Reserved 6: Frequency Command (00-05) |
10-01 / PID feedback value source setting — PDF page 357
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-01 | PID feedback value source setting |
| 2 | Range | 1: AI1 given 2: AI2 given 3: PI given |
Manual — PID mode bits and gains — page 358
Manual reference: physical PDF page 358. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PID target value source setting(10-00) / PID feedback value source setting(10-01) Please confirm parameter 04-00 conform the need (0V~10 V or 4mA~20 mА) if AI2 as PID target or PID feedback. And switch SW2 (for standard H & C type) or SW4 (for enhanced E & G type) from control board to the input type (V or I), please refer to wiring diagram for more detail. When 10-03= xxx1b: PID is enabled, LCD keypad will be switched automatically (16-00) and main screen monitoring displays PID target value (12-38). Sub-screen monitoring 1 (16-01) displays PID feedback value (12-39) and sub-screen monitoring 2 (16-02) displays frequency output (12-17). If PID is disabled, the keypad will switch automatically to frequency command setting as the main page. When 10-03= xx1xb: PID output is reverse. PID output is chosen to reverse, and if PID input is negative, the output frequency of PID will gain. On the contrary, PID output is chosen to forward, and if PID input is minus, the output frequency of PID will decrease. Refer to Fig. 4.4.78 & 4.4.79 when 10-03= x1xxb: feedback value differential of PID control and 10-03= x0xxb: basic PID control When 10-03= 0xxxb: PID output, it corresponds 100% to the frequency of 01-02. When 10-03= 1xxxb: PID output + frequency command, it will cumulate the output percentage of frequency command, (corresponding to 01-02 main frequency command set by parameter 00-05/ 00-06) at the beginning of running and then start PID control.
PID mode bits and gains
10-02 / PID target value — PDF page 358
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-02 | PID target value |
| 2 | Range | 0.00~100.00 % |
10-03 / PID control mode — PDF page 358
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-03 | PID control mode |
| 2 | Range | xxx0b: PID disable xxx1b: PID enable xx0xb: PID positive characteristic xx1xb: PID negative characteristic x0xxb: PID error value of D control x1xxb: PID feedback value of D control 0xxxb: PID output 1xxxb: PID output + Frequency Command |
10-04 / Feedback gain — PDF page 358
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-04 | Feedback gain |
| 2 | Range | 0.01~10.00 |
10-05 / Proportional gain (P) — PDF page 358
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-05 | Proportional gain (P) |
| 2 | Range | 0.00~10.00 |
10-06 / Integral time (I) — PDF page 358
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-06 | Integral time (I) |
| 2 | Range | 0.0~100.0 Sec |
10-07 / Differential time (D) — PDF page 358
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-07 | Differential time (D) |
| 2 | Range | 0.00~10.00 Sec |
10-09 / PID bias — PDF page 358
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-09 | PID bias |
| 2 | Range | -100~100 % |
Manual — PID limits and adjustment descriptions — page 359
Manual reference: physical PDF page 359. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PID Adjustments Gain control: The error signal (deviation) between the input command (set value) and the actual control value (feedback). This error signal or deviation is amplified by the proportional gain (P) to control the offset between the set value and the feedback value. Integral control: The output of this control is the integral of the error signal (difference between set value and feedback value) and is used to minimize the offset signal that is left over from the gain control. When the integral time (I) is increased, the system response becomes slower. Differential control: This control is the inverse from integral control and tries to guess the behavior of the error signal by multiplying the error with the differential time. The result is added to the PID input. Differential control slows down the PID controller response and may reduce system oscillation. Note: Most applications that PID control (fan and pump) do not require differential control. Refer to Figure 4.4.79 for PID control operation
Figure4.4.79 PID Control. Deviation step versus t; Control response versus t. Curves labelled PID Control,I Control,P Control andD. No numeric response values supplied.
PID limits and adjustment descriptions
10-10 / PID Primary delay time — PDF page 359
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-10 | PID Primary delay time |
| 2 | Range | 0.00~10.00 % |
10-14 / PID integral limit — PDF page 359
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-14 | PID integral limit |
| 2 | Range | 0.0~100.0 % |
10-23 / PID limit — PDF page 359
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-23 | PID limit |
| 2 | Range | 0.00~100.0 % |
10-24 / PID output gain — PDF page 359
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-24 | PID output gain |
| 2 | Range | 0.0~25.0 |
10-25 / PID reversal output selection — PDF page 359
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-25 | PID reversal output selection |
| 2 | Range | 0: Do not allow the reversal output 1: Allow the reversal output |
10-26 / PID target acceleration / deceleration time — PDF page 359
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-26 | PID target acceleration / deceleration time |
| 2 | Range | 0.0~25.5 Sec |
Manual — PID differential-feedback and basic block diagrams — page 360
Manual reference: physical PDF page 360. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PID Control Type The inverter offers two types of PID control: (a) PID control with differential feedback: (10-03 = x1xxb) Make sure to adjust the PID parameters without causing system instability. Refer to Figure 4.4.80 for PID control for feedback value differential.
(b) Basic PID control: (10-03 = x0xxb) This is the basic type of PID control. Refer to the figure 4.4.81.
PID Setup Enable PID control by setting parameter 10-03, PID target value (10-00) and PID feedback value (10-01).
Figure4.4.80 PID control for feedback differential value;10-03=x1xxb. Labels Set Value,P,I,D,Control,Feedback. Input summing node shows+set value and-feedback; feedback lower node has two+ signs. Output summing node two+ signs. Diagram labels/signs retained; no engineering reconstruction.
Figure4.4.81 Basic PID control;10-03=x0xxb. Labels Set Value,P,I,D,Control,Feedback. Input summing node +set value/-feedback; output summing node three+ signs. Source layout and signs preserved, no inferred implementation.
Manual — PID target and feedback input selection — page 361
Manual reference: physical PDF page 361. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(1) Select PID target value (10-00): 10-00: PID target value =1: analog AI1 given (default) =2: analog AI2 given =3: Pulse given =4:10-02 =6 frequency command (00-05) (2) Select PID feedback value (10-01): 10-01: PID feedback value =1: Analog AI1 given =2: Analog AI2 given =3: Pulse given
Figure4.4.82 PID input selection. Target paths AI1→10-00=1;AI2→10-00=2;Pulse input→10-00=3;10-02setting→10-00=4;Freq Command(00-05)→10-00=6. PID Target SFS10-26,ON,PID Setpoint,Target Value. Feedback paths AI1→10-01=1;source label A12→10-01=2;Pulse Input→10-01=3.10-27/10-33 PID feedback display unit conversion;PID Feedback;Feedback Value. Source A12 spelling retained.
Manual — PID control block diagram — page 362
Manual reference: physical PDF page 362. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PID Control Setting PID control block diagram. The following figure shows the PID control block diagram.
Figure4.4.83 upper control block labels:10-03=xx0xb→×1;10-03=xx1xb→-1;Bias10-09;PID output gam10-24;PID Output;±200% Limit;10-03=1xxxb and10-03=0xxxb selector;10-25=0 upper limiter+109%;10-25=1 lower limiter+109%/-109%;PID=OFF/PID=ON;Frequency Reference(Fref). PID=OFF conditions:1.10-03=0(PID Disabled),2.during JOG mode,3.multi-function digital input03-00–03-07 setting29. Summing signs as printed+, no wiring inference.
Figure4.4.83 lower control block labels:Freq Command(00-05)10-00=6;AI1 10-00=1;AI2 10-00=2;Pulse Input10-00=3;10-02 10-00=4;Target Value. Feedback Value10-01→Feedback Gain10-04;10-03=x0xxb and10-03=x1xxb;D10-07. PID Input(Deviation);P10-05;I10-06;I-Limit10-14 with both printed labels100% and100%;D10-07;10-03=x0xxb/10-03=x1xxb;Integral Reset(using Multi-function Digital Input);PID Limit10-23 with100%/-100%;Primary delay10-10. Input summing node has printed+at lower left and−at lower right; retain visible sign positions without assigning an inferred transfer equation, lower feedback sum+,+ and output sum+,+,+. Labels/signs retained without resolving engineering interpretation.
Manual — PID tuning and parameter qualifications — page 363
Manual reference: physical PDF page 363. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PID Tuning Use the following procedures to start PID control, (1) Enable PID control (set 10-03 to a value greater than "xxx0b"). (2) Increase the proportional gain (10-05) to the highest value possible without causing the system to become unstable. (3) Decrease the integral time (10-06) to the lowest value possible without causing the system to become unstable. (4) Increase the differential time (10-07) to the highest value possible without causing the system to become unstable. The PID control serves to maintain a given process within certain limits whether it is pressure, flow etc. To do this the feedback signal is compared to the set value and the difference becomes the error signal for the PID control. The PID control then responds by trying to minimize this error. The error is multiplied times the value of the Proportional gain set by parameter 10-05. An increased gain value results in a larger error. However, in any system as the gain is increased there is a point that the system will become unstable (oscillate). To correct this instability, the response time of the system may be slowed down by increasing the Integral time set by parameter 10-06. However slowing the system down too much may be unsatisfactory for the process. The end result is that these two parameters in conjunction with the acceleration time (01-14) and deceleration (01-15) times require to be adjusted to achieve optimum performance for a particular application. PID output polarity can be selected with parameter 10-03 (setting = xx0xb: PID output forward, setting = xx1xb: PID output reversal). When PID output is chosen to reverse, and if PID input is negative, the output frequency of PID will gain. On the contrary, PID output is chosen to forward, and if PID input is minus, the output frequency of PID will decrease. PID feedback value can be adjusted using parameter 10-04 (PID feedback gain) as well as with the analog input gain and bias for terminal AI1 or AI2. 10-14: PID integral limit: Used to limit the integral output to prevent motor stall or damage to the system in case of a rapid change in the feedback signal. Reduce the value of 10-14 to increase the inverter response. 10-23: PID limit: Used to limit the output of the PID control. Maximum output frequency is 100%. 10-10: Primary delay time: Low pass filter situated after the PID limit block that can be used to prevent PID output resonance. Increase the time constant to a value greater than the resonance frequency cycle and reduce time constant to increase the inverter response. 10-09: PID bias: Used to adjust the offset of the PID control. The offset value is added to the frequency reference as compensation. Use parameter 10-24 (PID output gain) to control the amount of compensation. In case the PID control output value goes negative, parameter 10-25 (PID reversal output selection) can be used to reverse the motor direction. Note: The PID output remains at zero when reverse operation is disabled. 10-26: PID target SFS: Sets the PID target value acceleration and deceleration ramp time. The PID target SFS can be disabled by setting the multi-function digital inputs 03-00 ~ 03-07 to 36 (PID target SFS is off). Reduce the acceleration / deceleration time in case load resonance or system instability is encountered.
Manual — PID fine-tuning examples — page 364
Manual reference: physical PDF page 364. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PID Fine Tuning All PID control parameters are related to each other and require to be adjusted to the appropriate values. Therefore, the procedure achieving the minimum steady-state is shown as following: (1) Increase or decrease the proportion (P) gain until the system is stable using the smallest possible control change. (2) The integral (I) reduces the system stability which is similar to increasing the gain. Adjust the integral time so that the highest possible proportional gain value can be used without affecting the system stability. An increase in the integral time reduces system response. (3) Adjust the differential time if necessary to reduce overshoot on startup. The acceleration / deceleration time can also be used for the same purpose. Fine-tuning PID control parameters:
PID fine-tuning example (1)Reduce overshoot: Output versus t; Before points to larger peak,After to lower peak. In case overshoot occurs, reduce derivative time(D) and increase integral time(I). Supplier instructions retained without validation.
PID fine-tuning example (2)Stabilize PID control: Output versus t; After points to upper peak,Before to lower curve. To quickly stabilize PID control, reduce integral time(I) and increase differential time(D) in case overshoot occurs. Supplier instructions retained without validation.
PID fine-tuning example (3)Reduce long-period oscillation: Output versus t;Before andAfter curves. Adjust integral time(I) in case of long-periodical system oscillation. Supplier instructions retained without validation.
PID fine-tuning example (4)Reduce short-period oscillation: Output versus t;Before andAfter oscillation curves. Adjust differential time(D) and proportional(P) gain when experiencing short-periodical oscillation. Supplier instructions retained without validation.
Manual — PID feedback loss detection — page 365
Manual reference: physical PDF page 365. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The PID control function provides closed-loop system control. In case PID feedback is lost, the inverter output frequency may be increase to the maximum output frequency. It is recommended to enable to the PID feedback loss when the PID function is used. PID feedback loss detection 10-11=0: Disable 10-11=1: Warning A feedback loss condition is detected when the PID feedback value falls below the value set in parameter 10-12 (PID feedback loss detection level) for the time set in parameter 10-13 (PID feedback loss detection time). PID feedback loss warning message "Pb" will be displayed on the keypad and the inverter will continue to operate. 10-11=2: Fault A feedback loss condition is detected when the PID feedback value falls below the value set in parameter 10-12 (PID feedback loss detection level) for the time set in parameter 10-13 (PID feedback loss detection time). PID feedback loss fault message "Pb" will be displayed on the keypad, the inverter stops and the fault contact is activated.
Figure4.4.84 PID feedback loss detection. Feedback Value versus t,level10-12; FBL Detection trace;short interval t1 and10-13 delay;later long low-feedback interval triggers FBL after10-13.
PID feedback loss detection
10-11 / PID feedback loss detection selection — PDF page 365
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-11 | PID feedback loss detection selection |
| 2 | Range | 0: Disable 1: Warning 2: Fault |
10-12 / PID feedback loss detection level — PDF page 365
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-12 | PID feedback loss detection level |
| 2 | Range | 0~100 % |
10-13 / PID feedback loss detection time — PDF page 365
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-13 | PID feedback loss detection time |
| 2 | Range | 0.0~10.0 Sec |
Manual — PID sleep selection and block diagram — page 366
Manual reference: physical PDF page 366. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The PID Sleep function is used to stop the inverter when the PID output falls below the PID sleep level (10-17) for the time specified in the PID sleep delay time parameter (10-18). The inverter wakes up from a sleep condition when the PID output (Reference frequency) rises above the PID wake-up frequency (10-19) for the time specified in the PID wake-up delay time (10-20). Use parameter 10-29 to enable / disable PID sleep function. 10-29 =0: PID Sleep function is disabled. 10-29 =1: PID sleep operation is based on parameters of 10-17 and 10-18. 10-29 =2: PID sleep mode is enabled by multi-function digital input Refer to figure 4.4.85 (a) and (b) for PID sleep / wakeup operation.
Figure4.4.85(a)PID control block diagram:Target Value+,Feedback Value−,PID,Freq Reference(Fref),PID Sleep/Wake-up function,10-29=0 and10-29=1or2,PID=OFF/PID=ON,Soft Start with f/t axes,Output Frequency(Fout). No unprinted control mapping inferred.
PID sleep selection and block diagram
10-17 / Start frequency of PID sleep — PDF page 366
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-17 | Start frequency of PID sleep |
| 2 | Range | 0.00~599.00 Hz |
10-18 / Delay time of PID sleep — PDF page 366
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-18 | Delay time of PID sleep |
| 2 | Range | 0.0~255.5 Sec |
10-19 / Frequency of PID wakeup — PDF page 366
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-19 | Frequency of PID wakeup |
| 2 | Range | 0.00~599.00 Hz |
10-20 / Delay time of PID wakeup — PDF page 366
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-20 | Delay time of PID wakeup |
| 2 | Range | 0.0~255.5 Sec |
10-29 / PID sleep selection — PDF page 366
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-29 | PID sleep selection |
| 2 | Range | 0: Disable 1: Enable 2: Set by DI |
10-40 / Selection of PID Sleep Compensation Frequency — PDF page 366
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-40 | Selection of PID Sleep Compensation Frequency |
| 2 | Range | 0: Disable 1: Enable |
Manual — PID sleep wakeup and compensation timing — page 367
Manual reference: physical PDF page 367. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Notes: 10-40=0, refer to Figure 4.4.85 (b) The PID sleep timer is enabled when the output frequency (Fout) falls below the PID sleep frequency (10-17). When the sleep timer reaches the set PID sleep delay time (10-18) the inverter will decelerate to a stop and enter the sleep mode. 10-40=1, refer to Figure 4.4.85 (c) When output frequency (Fout) is lower than PID sleep frequency set by 10-17, Timer of PID sleep mode will run and the output frequency changes with the reference frequency (Fref) until it reaches the minimum output frequency (Fmin) set by 01-08. When the PID sleep delay time (10-18) is completed, the motor will run gradually to the PID sleep frequency set by 10-17. Note: It should be used in the situation of being required the constant frequency. While sleep mode is active and the motor has stopped, the internal PID control is still in operating. When the reference frequency increases and exceeds the wakeup frequency parameter 10-19 for the time specified in the wakeup delay time parameter 10-20, the inverter will restart and the output frequency will ramp up to the reference frequency.
Figure4.4.85(b)Timing diagram PID sleep/wakeup:Output Frequency versus t,thin Frequency Reference(Fref),thick Output Frequency(Fout);Wake-up Frequency10-19,Sleep Frequency10-17,Fmin01-08;sleep delay10-18,wake-up delay10-20. Thick output stops after sleep delay then ramps after wake-up delay.
Figure4.4.85(c)Timing diagram of PID sleep compensation frequency wakeup:Output Frequency versus t,Frequency Reference(Fref),Output Frequency(Fout),Wake-up Frequency10-19,Sleep Frequency10-17,Fmin01-08;sleep delay10-18,wake-up delay10-20. Thick output rises from minimum to sleep-frequency plateau before final wakeup ramp.
Manual — PID sleep restrictions and feedback display scaling — page 368
Manual reference: physical PDF page 368. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: -- When wakeup frequency< sleep frequency, inverter starts by the sleep frequency and sleeps depending on wakeup frequency. -- When wakeup frequency> sleep frequency, inverter starts by the wakeup frequency and sleeps depending on sleep frequency. Example: Sleep mode only have positive direction, if set 10-25 = 1 (Allow the reversal output), the sleep mode must be closed. -- 10-00 and 10-01 can’t set to the same source, if set the same values, the keypad will display “ SE05 ” PID selection error message. -- When PID sleep selection is enabled or set by DI (10-29 = 1 or 2), and PID reversal output selection 10-25 = 1 (Allow the reversal output), the keypad will display “ SE05 ” PID selection error message. -- When PID sleep selection is enabled or set by DI (10-29 = 1 or 2), and PID control mode 10-03 = 1xxxb (PID output + Frequency Command, the keypad will display “ SE05 ” PID selection error message. -- Use parameter 10-29 to enable or disable PID sleep function. 10-29 = 0: PID disable。 = 1: PID enable, operate by parameter 10-17 and 10-18. = 2: PID set by DI.
PID Feedback Display Scaling The PID feedback signal can be scaled to represent actual engineering units. Use parameter 10-33 to set the maximum value of PID feedback and parameter 10-27 to the feedback signal minimum. Example: Feedback signal is a pressure transducer (0-10V or 4-20mA ) with a range of 1.0 – 20.0 PSI 4mA (0V) = 1.0 PSI, 20mA (10V) = 20.0 PSI. Set parameter 10-27 to 10 minimum of transducer range (0%). Set parameter 10-33 to 200 maximum of transducer range (100%). Refer to the figure 4.4.86 for displaying the unit conversion.
Figure4.4.86 Feedback signal scaling. Display unit vertical with10-27 lower endpoint at0V(4mA),10-33 upper endpoint at10V(20mA);horizontal Feedback Signal. Straight connecting line only; no intermediate values inferred.
PID sleep restrictions and feedback display scaling
10-27 / PID Feedback Display Bias — PDF page 368
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-27 | PID Feedback Display Bias |
| 2 | Range | 0~9999 |
Manual — PID display limits units and trim selections — page 369
Manual reference: physical PDF page 369. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Target value of PID will be limited to the range of upper & lower limit of PID target.
When the maximum value of PID feedback is active, it will become 100% the corresponding value of 10-02.
PID decimal width is used for rounding up setting. For example: set 10-34=1, it displays XXX.X ; set 10-34=2, it displays XX.XX.
PID unit is selected depending on user’s needs. Note: When user switches PID in LED keypad, 10-33 is required to be lower than 1000 and 10-34=1, or the keypad will show a SE05 alarm (PID setting error).
When PID feedback disconnection is in alarm, frequency command output depends on the setting value of 10-39. If the warning is lifted, PID control is restored. * When the motor’s maximum output frequency is over than 300Hz, the frequency resolution is 0.1Hz.
Signal Given and Process: When 10-41= 1 (D type PID), A510s can process the ratio conversion for external signal, and then the signal given value can correspond to the speed command.
PID display limits units and trim selections
10-30 / Upper Limit of PID Target — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-30 | Upper Limit of PID Target |
| 2 | Range | 0 ~ 100 % |
10-31 / Lower Limit of PID Target — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-31 | Lower Limit of PID Target |
| 2 | Range | 0 ~ 100 % |
10-33 / Maximum Value of PID Feedback — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-33 | Maximum Value of PID Feedback |
| 2 | Range | 1~10000 |
10-34 / PID Decimal Width — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-34 | PID Decimal Width |
| 2 | Range | 0~4 |
10-35 / PID Unit — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-35 | PID Unit |
| 2 | Range | 0~24 |
10-39 / Output Frequency Setting of PID Disconnection — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-39 | Output Frequency Setting of PID Disconnection |
| 2 | Range | 00.00~599.00 Hz |
10- 08 / AI1 Frequency Limit — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10- 08 | AI1 Frequency Limit |
| 2 | Range | 00.00~599.00 Hz |
| 3 | 10- 15 | PID Trim Mode |
| 4 | Range | 0~2 |
| 5 | 10- 16 | PID Trim Scale |
| 6 | Range | 0~100 |
10- 41 / PID Mode Switch — PDF page 369
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10- 41 | PID Mode Switch |
| 2 | Range | 【0】:General PID 【1】:D Type PID |
Manual — D-type PID setup and fire-mode gains — page 370
Manual reference: physical PDF page 370. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The Signal given corresponds to the speed command mode:
Use the follow steps to start D type PID control: (1) 10-03 (PID control mode) set to 1001b. (2) 10-00 (PID target value source) set to 4 (10-02 given). (3) 10-01 (PID feedback value source) set to 2 (AI2 given). (4) 00-05 (Main frequency command source selection) set to 1 (External terminal: Analog 1). (5) 10-29 PID sleep selection set to 0 (Disable). The maximum frequency limit is set by 10-08. 10-25 PID reversal output selection decide the output can or cannot reversal run. The first bit of 10-03 PID control mode decide to plus the frequency command. The response of PID control can be adjust 10-36 (Proportional gain 2), 10-37 (Integral Time 2) and 10-38 (Differential Time 2) 10-15 (PID trim mode) set to 1 (Proportional), use the multiple of 01-02 (Maximum output frequency of motor) and 01-12 (Base frequency of motor), then multiply the frequency of 00-05 (Main frequency command source selection), then multiply 10-16 (PID trim scale), the value can be used to modify the PID multiple. 10-15 (PID trim mode) set to 0 (Not select), use 01-02 (Maximum output frequency of motor) multiply 10-16 (PID trim scale), the value can be used to modify the PID multiple.
PID functions of ire mode, please refer to parameter group 08.
D-type PID speed-command diagram. Max.Frequency01-02 and Main Frequency Command Source Selection00-05 feed PID trim mode10-15(0=Not select,1=Proportional,2=Direct). PID trim scale10-16,PID command,PID feedback,PID;two× blocks and a+ block;Main Frequency Command Source Selection00-05 also at final+;outputSpeed command. Retain block labels and source connectors, no additional equations inferred.
D-type PID setup and fire-mode gains
10- 47 / Proportioanl Gain 3 (P) of Fire Mode — PDF page 370
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10- 47 | Proportioanl Gain 3 (P) of Fire Mode |
| 2 | Range | 【0.00~10.00】 |
| 3 | 10- 48 | Integral Time 3 (I) of Fire Mode |
| 4 | Range | 【0.0~100.0】Sec |
| 5 | 10- 49 | Differential Time 3 (D) of Fire Mode |
| 6 | Range | 【0.00~10.00】Sec |
Manual — Direction lock carrier frequency and cable limits — page 371
Manual reference: physical PDF page 371. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11-Auxiliary Parameters
If motor operation direction is set to 1 or 2, the motor can only operate in that specific direction. Run commands in the opposite direction are not accepted. Forward or reverse commands can be issued via the control terminals or keypad. Note: The Direction Lock Selection can be used in fan and pump application where reverse rotation is prohibited.
Notes: (1) Value 1 to 16 represents KHz. (2) When 11-01=0, the carrier frequency is modified by parameter 11-26~11-27 & 11-30~11-32. (3) For SLV and SV mode, the minimum value of 11-01 is 2 kHz, due to the sample rate, suggest to use 4 KHz, and the motor cable used within 100m. (4) Setting range is determined by the inverter rating (13-00) and HD/ND mode (00-27). (5) Refer to section 3 inverter derating based on carrier frequency. (6) A low carrier frequency increases motor noise but reduces motor losses and temperature. (7) A low carrier frequency decreases RFI, EMI interference and motor leakage current. Refer to the carrier frequency Table 4.4.36. Table 4.4.36 Carrier frequency settings
If cable length between the inverter and the motor is too long, the high-frequency leakage current will cause an increase in inverter output current, which might affect peripheral devices. Adjust the carrier frequency to avoid this as shown in table 4.4.37. Table 4.4.37 Cable length and carrier frequency
*. If Cable is longer than 200m, the output dv/dt filter or output reactor is required. Notes: (1) Reduce the carrier frequency if the torque does not match the speed. (2) In V/F and V/F + PG control modes, set 11-01 to 0, the carrier frequency is determined by parameters 11-30 (Carrier frequency max. limit), 11-31 (Carrier frequency lower limit) and 11-32 (Carrier frequency proportional gain).
Direction lock carrier frequency and cable limits
11-00 / Direction Lock Selection — PDF page 371
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-00 | Direction Lock Selection |
| 2 | Range | 0: Allow forward and reverse rotation 1: Only allow forward rotation 2: Only allow reverse rotation |
11-01 / Carrier frequency — PDF page 371
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-01 | Carrier frequency |
| 2 | Range | 【0】: Carrier Output Frequency Tuning 【1~16】: 1~16KHz |
Carrier Frequency / 1KHz--6KH—10KHz—16KHz — PDF page 371
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Carrier Frequency | 1KHz--6KH—10KHz—16KHz |
| 2 | Motor noise | High -------------- Low |
| 3 | Output current waveform (similar to sinusoidal wave) | Bad ------ Good ----- Bad |
| 4 | Noise interference | Low --------------- High |
| 5 | Leakage current | Low --------------- High |
| 6 | Heat loss | Low --------------- High |
Wire length / < 30 Meter (98ft) / up to 50 Meter (164 ft) / up to 100 Meter (328ft) / > 100 Meter* > 328ft — PDF page 371
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Wire length | < 30 Meter (98ft) | up to 50 Meter (164 ft) | up to 100 Meter (328ft) | > 100 Meter* > 328ft |
| 2 | Carrier frequency (11-01 value ) | Max. value 16KHz (11-01=16KHz) | Max. value 10KHz (11-01=10KHz) | Maxi. value 5KHz (11-01=5KHz) | Max. value 2KHz (11-01=2KHz) |
Manual — Soft PWM selections and restrictions — page 372
Manual reference: physical PDF page 372. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11-02=0: Soft PWM control disables. 11-02=1: Soft PWM 1 control enables. Soft PWM control can improve the ‘metal’ noise produced by the motor, more comfortable for the human ear. At the same time, Soft PWM also limits RFI noise to a minimum level. The default setting of Soft PWM control is disabled. Soft PWM 1 cannot be set if carrier frequency set in 11-01 is higher than 8 kHz. 11-02=2: Soft PWM 2 control enables. User adjusts parameter 11-66 (2 Phase/3 Phase PWM Switch Frequency), 11-67 (Soft PWM 2 Frequency Range) and 11-68 (Soft PWM 2 Switch Frequency) by his/ her own feeling to noise.
When the output frequency is higher than 11-66, the PWM mode will be switched.
When the output frequency is higher than 11-68, the noise detect function will be enabled, and according to 11-67 to modify the magnetic noise of motor. Note: 1. When 11-02=2, estimator mode (22-26) and speed search mode selection (07-32) cannot be used at the same time. 2. When 11-02=2, sum of 11-01 and 11-67 should be lower than the upper limit of carrier frequency. To avoid the error setting, please follow the rules listed as below. If error occurs when setting 11-01, it means 11-02= 2 and 11-01 + 11-67 > Upper limit of carrier frequency, please reset 11-02 or 11-67. If error occurs when setting 11-67, it means 11-02=2 and 11-01 + 11-67 > Upper limit of carrier frequency, please reset 11-02 or 11-01. When 11-02=2, if error occurs when setting 11-01 or 11-67, it means 11-01 + 11-67 > Upper limit of carrier frequency, please reset the parameter. If error occurs when setting 11-02=2, it means 11-01 + 11-67 > Upper limit of carrier frequency, please reset the parameter 11-01 or 11-67, then set 11-02=2.
Soft PWM selections and restrictions
11-02 / Soft PWM Function Selection — PDF page 372
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-02 | Soft PWM Function Selection |
| 2 | Range | 【0】: Disable 【1】: Soft PWM 1 enables 【2】: Soft PWM 2 enables |
11- 66 / 2 Phase/ 3 Phase PWM Switch Frequency — PDF page 372
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 66 | 2 Phase/ 3 Phase PWM Switch Frequency |
| 2 | Range | 【6.00~60.00】Hz |
11- 67 / Soft PWM 2 Frequency Range — PDF page 372
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 67 | Soft PWM 2 Frequency Range |
| 2 | Range | 【0~12000】 |
| 3 | 11- 68 | Soft PWM 2 Switch Frequency |
| 4 | Range | 【6.00~60.00】 |
Manual — Automatic carrier reduction and S-curves — page 373
Manual reference: physical PDF page 373. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
If inverter detects the overheating, the carrier frequency will decrease automatically. Once this temperature returns to normal, the carrier frequency will automatically return to the set value of 11-01. 11-03=0: Automatic carrier frequency reduction during an overheat condition is disabled. Carrier frequency operation depends on the set value of 11-01. 11-03=1: Automatic carrier frequency reduction during an overheat condition is enabled. Carrier frequency automatically decreases to reduce the heat loss and avoid the inverter’s trip so as to extend the period of use in inverter when the heat sink temperature is higher than the sett value.
The S curve function for acceleration / deceleration is used to reduce mechanical impact caused by the load during momentary starting and stopping of the inverter. To use the S curve function set the time for acceleration start point (11-04), acceleration end point (11-05), deceleration start point (11-06) and deceleration end point (11-07). Refer to figure 4.4.87 for more information.
Total acceleration and deceleration time when the S curve is used:
Figure4.4.87 S curve characteristic. Run Command ON/OFF versus t;Output Frequency. S1=11-04 at acceleration start,S2=11-05 at acceleration end,S3=11-06 at deceleration start,S4=11-07 at deceleration end.
Source formulae: Accelerating time=Accelerating time1(or2)+[(11-04)+(11-05)]/2. Deceleration time=Deceleration time1(or2)+[(11-06)+(11-07)]/2.
Automatic carrier reduction and S-curves
11-03 / Automatic carrier lowering selection — PDF page 373
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-03 | Automatic carrier lowering selection |
| 2 | Range | 0: Disable 1: Enable |
11-04 / S curve time setting at the start of acceleration — PDF page 373
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-04 | S curve time setting at the start of acceleration |
| 2 | 11-05 | S curve time setting at the end of acceleration |
| 3 | 11-06 | S curve time setting at the start of deceleration |
| 4 | 11-07 | S curve time setting at the end of deceleration |
| 5 | Range | 0.00~2.50 Sec |
Manual — Jump frequency bands and overlap — page 374
Manual reference: physical PDF page 374. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
These parameters allow “jumping over” of certain frequencies that can cause unstable operation due to resonance within certain applications. Note: Prohibit any operation within the jump frequency range. During acceleration and deceleration the frequency is continuous without skipping the jump frequency. To enable jump frequency 1 – 3 (11-08 – 11-10) set the frequency to a value greater than 0.0 Hz. Use the jump frequency width (11-11) to create a jump frequency range. Refer to figure 4.4.88.
Jump frequency via Analog Input. Set parameter 04-05 (AI2 function selection) to 9 (frequency jump setting 4) to control the jump frequency via analog input AI2. Refer to Figure 4.4.48. Note: When jump frequency overlap the sum of the overlapped jump frequencies will be used as the jump frequency range. Refer to figure 4.4.89.
Figure4.4.88 Jump frequency operation. Output Frequency versus Frequency Reference;ascending diagonal with jump bands11-10,11-09,11-08 in ascending order;each band width11-11. No unlabelled numeric frequencies inferred.
Figure4.4.89 Jump frequency overlap. Output Frequency versus Frequency Reference;overlapping Jump2 andJump1 bands;Actual jump width spans outer limits. Preserve plotted overlap without deriving numerical width.
Jump frequency bands and overlap
11-08 / Jump frequency 1 — PDF page 374
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-08 | Jump frequency 1 |
| 2 | 11-09 | Jump frequency 2 |
| 3 | 11-10 | Jump frequency 3 |
| 4 | Range | 0.0~599.0 Hz |
11-11 / Jump frequency width — PDF page 374
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-11 | Jump frequency width |
| 2 | Range | 0.0~25.5 Hz |
Manual — Automatic return and manual energy saving — page 375
Manual reference: physical PDF page 375. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
If the keypad is not pressed within the time specified in 16-06 (returning time of automatic back button), the keypad will automatically return to the mode screen. When it is set to 0, the automatic return function is off. Press the back button to return to the previous directory.
Manual energy savings reduces the output voltage for the purpose of saving energy. To enable manual energy savings set one of the multi-function digital input (03-00 to 03-07) to 20 and activate the input or use parameter 11-18 to set the manual energy savings activation frequency. When the output frequency rises above the value set in parameter 11-18 manual energy savings function is enabled. Setting parameter 11-18 manual energy savings frequency to 0.0 Hz disables the manual energy savings frequency activation function. Refer to figure 4.4.88 for more information. Note: Only use manual energy savings functions in combination with light loads. Manual energy saving gain (11-12) determines the output voltage of the inverter when manual energy savings is enabled. Output voltage is percentage gain times the V/F voltage. Manual energy saving control uses the voltage recovery time (07-23) to change the output voltage
Figure4.4.90 Manual energy saving operation. RUN Command OFF/ON;Manual Energy Saving Command OFF/ON;Output Frequency;Output Voltage. Labels Frequency reference≥11-18;Voltage change rated=07-23(Voltage recovery time;V/f pattern(01-02to01-09)×11-12. Missing closing parenthesis retained as source.
Automatic return and manual energy saving
11-13 / Automatic return time — PDF page 375
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-13 | Automatic return time |
| 2 | Range | 0~120 sec |
11-12 / Manual energy saving gain — PDF page 375
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-12 | Manual energy saving gain |
| 2 | Range | 0~100 % |
11-18 / Manual energy saving frequency — PDF page 375
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-18 | Manual energy saving frequency |
| 2 | Range | 0.0~599.0 Hz |
Manual — Automatic energy saving parameters — page 376
Manual reference: physical PDF page 376. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
In the V/F control mode the automatic energy saving (AES) function automatically adjusts the output voltage and reduces the output current of the inverter to optimize energy savings based on the load. The output power changes proportional to the motor load. Energy savings is minimal when the load exceeds 70% of the output power and savings become greater when the load decreases. The parameter of automatic energy saving function has been set at the factory before shipment. In general, it is no need to adjust. If the motor characteristic has significant difference from the TECO standard, please refer to the following commands for adjusting parameters: Enable Automatic Energy Savings Function (1) To enable automatic energy saving function set 11-19 to 1. (2) Filter time of automatic energy saving (11-20) (3) Commissioning parameter of energy saving (11-21 to 11-22) In AES mode, the optimum voltage value is calculated based on the load power requirement but is also affected by motor temperature and motor characteristic. In certain applications the optimum AES voltage needs to be adjusted in order to achieve optimum energy savings. Use the following AES parameters for manual adjustment: 11-21: Voltage limit value of AES commissioning operation Set the voltage upper limit during automatic energy saving. 100% corresponds to 230V or 460V or 575/690V depending on the inverter class used. Refer to the figure 4.4.91.
Automatic energy saving parameters
11-19 / Automatic energy saving function — PDF page 376
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-19 | Automatic energy saving function |
| 2 | Range | 0: Automatic energy saving is disabled 1: Automatic energy saving is enabled |
11-20 / Filter time of automatic energy saving — PDF page 376
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-20 | Filter time of automatic energy saving |
| 2 | Range | 0~200 msec |
11-21 / Voltage upper limit of energy saving tuning — PDF page 376
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-21 | Voltage upper limit of energy saving tuning |
| 2 | Range | 0~100% |
11-22 / Adjustment time of automatic energy saving — PDF page 376
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-22 | Adjustment time of automatic energy saving |
| 2 | Range | 0~5000 msec |
11-23 / Detection level of automatic energy saving — PDF page 376
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-23 | Detection level of automatic energy saving |
| 2 | Range | 0~100% |
11-24 / Coefficient of automatic energy saving — PDF page 376
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-24 | Coefficient of automatic energy saving |
| 2 | Range | 0.00~655.34 |
Manual — Energy-saving adjustment and carrier tuning — page 377
Manual reference: physical PDF page 377. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11-22: Adjustment time of automatic energy saving Sets sample time constant for measuring output power. Reduce the value of 11-22 to increase response when the load changes. Note: If the value of 11-22 is too low and the load is reduced the motor may become unstable. 11-23: Detection level of automatic energy saving Set the automatic energy saving output power detection level. 11-24: Coefficient of automatic energy saving The coefficient is used to tune the automatic energy saving. Adjust the coefficient while running the inverter on light load while monitoring the output power. A lower setting means lower output voltage. Notes: - If the coefficient is set to low the motor may stall. - Coefficient default value is based on the inverter rating. Set parameter 13-00. If the motor power does not match the inverter rating.
If 11-01=0, when the carrier frequency is adjusted with the output frequency, in addition to the carrier frequency upper and lower limits for 11-30~32 to adjust with the frequency, the specific output frequency range can be adjusted through 11-26~27, and the carrier frequency can be adjusted with the output frequency; if the limit is exceeded, no carrier frequency adjustment is performed.
The automatic de-rating function automatically reduces the output frequency by 30% of the nominal motor speed when the inverter detects an overheat condition (heatsink). Automatic de-rating function depends on the automatic carried frequency reduction selection (11-03). If automatic carrier frequency reduction is disabled (11-03=0), the output frequency is reduced by 30% of the nominal motor speed when an overheat condition is detected.
Figure4.4.91 Voltage limit value of commissioning operation. Voltage Limit versus Output Voltage. Symmetric clipping plot with upper and lower labels both11-21. No sign or numeric value added to source labels.
Energy-saving adjustment and carrier tuning
11-26 / Carrier Output Frequency Tuning Upper Limit (%) — PDF page 377
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-26 | Carrier Output Frequency Tuning Upper Limit (%) |
| 2 | Range | 10~100% |
| 3 | 11-27 | Carrier Output Frequency Tuning Lower Limit (%) |
| 4 | Range | 2~100% |
11-29 / Auto De-rating Selection — PDF page 377
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-29 | Auto De-rating Selection |
| 2 | Range | 0: Disable 1: Enable |
Manual — Variable carrier frequency and derating — page 378
Manual reference: physical PDF page 378. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
If automatic carrier frequency reduction is enabled (11-03=1), the output frequency is reduced by 30% of the nominal motor speed when the carrier frequency is at its minimum setting. 11-29=0: Auto de-rating selection disabled, carrier frequency is based on 11-01 or 11-03. 11-29=1: Auto de-rating selection is enabled.
Carrier frequency method depends on the selected control mode.
Variable carrier frequency can be adjust with parameter 11-30 ~ 11-32.
K is a coefficient; the value of K is based on the following based on the upper carrier frequency: K=1: when 11-30 < 5 KHz K=2: when 10 KHz > 11-30 ≥ 5 KHz K=3: when 11-30 ≥ 10KHz Notes: - In V/F and V/F + PG control mode if the speed and torque are constant, the variable carrier frequency mode (11-01=0) can be selected to reduce the carrier frequency based on output frequency. - If the carrier frequency proportional gain (11-32) > 6 and 11-30 < 11-31, error message "SE01" out of range will appear on the keypad. - If the lower limit (11-31) is set higher than the upper limit (11-30), the lower limit will be ignored and the carrier frequency will be set at the upper limit (11-30). - In fixed carrier frequency mode (11-01 = 2-16) parameters 11-30, 11-31 and 11-32 are not used. - In SLV and SV control mode, the upper limit of the carrier frequency is fixed at 11-30.
Variable carrier-frequency graph. Carrier Frequency(KHz) versus OutputFrequency(Fout,Hz);lower plateau11-31,upper plateau11-30;sloped segmentFout×(11-32)×K;horizontal endpointFmax01-02. No extra coordinate interpolation.
Variable carrier frequency and derating
11-30 / Variable Carrier Frequency Upper Limit — PDF page 378
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-30 | Variable Carrier Frequency Upper Limit |
| 2 | Range | 2~16 KHz |
11-31 / Variable Carrier Frequency Lower Limit — PDF page 378
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-31 | Variable Carrier Frequency Lower Limit |
| 2 | Range | 1~16 KHz |
11-32 / Variable Carrier Frequency Proportional Gain — PDF page 378
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-32 | Variable Carrier Frequency Proportional Gain |
| 2 | Range | 00~99 |
Control Mode / Variable Carrier Frequency (11-01 = 0) / Fixed Carrier Frequency (11-01 = 2-16 kHz) — PDF page 378
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Control Mode | Variable Carrier Frequency (11-01 = 0) | Fixed Carrier Frequency (11-01 = 2-16 kHz) |
| 2 | V/F and V/F + PG | Available | Available |
| 3 | SLV and SV | Not available | Available |
Manual — Overvoltage prevention parameters — page 379
Manual reference: physical PDF page 379. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Overvoltage suppression is used for the application of likely causing to energy recharge. Example: there are two situations causing excessive energy to recharge the inverter in stamping application (1) When cam clutch is not engaged, the motor will accelerate and start flywheel. When motor decelerates, the rotation speed will higher than motor speed owing to the large flywheel’s inertia and then recharge the inverter. (2) When cam clutch is engaged, the motor will start flywheel and compress the spring. When the highest point of the cam moves beyond its center, the spring will release the power to the flywheel and excessive energy output recharge the inverter.
Overvoltage prevention parameters
11-28 / Frequency Gain of Over Voltage Prevention 2 — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-28 | Frequency Gain of Over Voltage Prevention 2 |
| 2 | Range | 1~200% |
11-33 / DC Voltage Filter Rise Amount — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-33 | DC Voltage Filter Rise Amount |
| 2 | Range | 0.1~10.0 V |
11-34 / DC Voltage Filter Fall Amount — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-34 | DC Voltage Filter Fall Amount |
| 2 | Range | 0.1~1.00 V |
11-35 / DC Voltage Filter Deadband Level — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-35 | DC Voltage Filter Deadband Level |
| 2 | Range | 0.0~99.0 V |
11-36 / Frequency gain of OV prevention — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-36 | Frequency gain of OV prevention |
| 2 | Range | 0.000~1.000 |
11-37 / Frequency limit of OV prevention — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-37 | Frequency limit of OV prevention |
| 2 | Range | 0.00~599.00 Hz |
11-38 / Deceleration start voltage of OV prevention — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-38 | Deceleration start voltage of OV prevention |
| 2 | Range | 200V: 200~400 V : 400V: 400~800 V 575V: 500~1000V 690V: 600~1200V |
11-39 / Deceleration end voltage of OV prevention — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-39 | Deceleration end voltage of OV prevention |
| 2 | Range | 200V: 300~400 V 400V: 600~800 V 575V: 500~1000V 690V: 600~1200V |
11-40 / OV prevention selection — PDF page 379
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-40 | OV prevention selection |
| 2 | Range | 0: Disable 1: OV prevention Mode 1 2: OV prevention Mode 2 3: OV Prevention Mode 3 |
Manual — Stamping and overvoltage operation diagrams — page 380
Manual reference: physical PDF page 380. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Over-voltage prevention (OVP) function monitors the DC-bus voltage and adjusts the speed reference, acceleration and deceleration rate, to prevent the inverter from tripping on an overvoltage. When the speed reference is reduced, the motor will start to decelerate. When the inverter is operating at a fixed output frequency and excessive regenerative energy back to the inverter is detected the inverter will accelerate the motor in order to reduce the DC-bus voltage. Refer to figure 4.4.93.
Figure4.4.92 Stamping Operation. Labels Inverter,fout,Motor,fmotor,Gear box,FLYWHEEL,cam clutch. Text Motoring:fout>fmotor;Overhauling:fout<fmotor. Mechanical depiction retained only as source figure labels, no inferred assembly instructions.
Figure4.4.93 OVP operation. DC bus voltage;monitor12-20;DC bus filter11-33,11-34,11-35;sum+/-;11-36 Gain and multiplication;11-37 Frequency Reference Limit;OVP accel/decel time;11-28 OVP2 Gain;OVP2 accel/decel time and second11-37 limiter. Frequency Reference→SFS Fout,Output Frequency After SFS;11-40=0 bypass,11-40=1or2 path;11-40=1 upper and11-40=2 lower selection at output+node;Output Frequency. Source labels retained without creating control implementation.
Manual — OV prevention mode1 and deceleration timing — page 381
Manual reference: physical PDF page 381. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When 11-40=1: OV prevention Mode 1 1) DC voltage filter is used to provide a stable reference value for determining the change in DC voltage change during regenerative operation. - Adjust the DC voltage filtering increase rate parameter 11-33 (DC Voltage Filter Rise Amount). When the DC voltage exceeds 11-33 +11-35 (DC Voltage Filter Deadband Level), the output of the filter will increase. - Adjust the DC voltage filtering decrease rate parameter 11-34 (DC Voltage Filter Fall Amount). When the DC voltage exceeds 11-33 +11-35 (DC Voltage Filter Deadband Level), the output of the filter will decrease. - Monitor the DC voltage filter output by 12-20 (DC voltage filter value). - Set the DC voltage filter decrease rate (11-34) to a greater value than the value of the DC voltage filtering increase rate (11-33). 2) When the inverter is operation at a fixed output frequency, the OVP function will monitor the DC-bus voltage to detect regenerative operation. In case of a regenerative condition the inverter calculates the delta DC bus voltage value and multiplies the value with parameter 11-36, the result is added to the frequency reference accelerating the motor to prevent on an overvoltage condition. When the regenerative energy decreases, the inverter output frequency will return to the actual frequency reference. Deceleration rate is based on the DC voltage, as shown in Figure 4.4.94.
3) When the inverter is stopped, the deceleration rate can be set with parameter 00-15 (Tdec1). In case the DC voltage is too high, the inverter will decelerate based on the OVP deceleration time as shown in Figure 4.4.93. - Set DC-bus voltage in parameter 11-38 (start voltage of OVP deceleration) and set OVP deceleration rate in 00-22 (Tdec3). - When the DC voltage reaches this level, it is necessary to decelerate rapidly in order to prevent the delta DC voltage of becoming too large.
Figure4.4.94 OVP deceleration time. Vertical OVP Deceleration Time;horizontal DC bus voltage.00-22(Tdec3) aligns700V OVP Deceleration Start11-38;00-24(Tdec4) aligns750V OVP Deceleration Stop11-39. Ascending line; no unlabelled time values inferred.
Manual — OV prevention modes2/3 and reference loss — page 382
Manual reference: physical PDF page 382. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- When DC voltage reaches the setting of 11-39 (stop voltage of OVP deceleration), it will decelerate based on the set value of 00-24 (Tdec4) - Deceleration rate is linear based on the slope defined by the start point (11-38) and end point (11-39). 4). Enable the OVP function with parameter 11-40 set to 1 or 2. The following parameter default values will be changed when the OVP function is enabled: 00-14(Tacc1)= 5.0 Sec(the frequency reference acceleration rate when DC voltage is too high.) 00-22(Tdec3)= 20.0 Sec(low setting point of OVP deceleration rate). 00-24(Tdec4)= 100.0 Sec(high setting point of OVP deceleration rate). Note: S curve should be disabled when using the OVP function (11-04~11-07=0.0sec). When 11-40=2: OV prevention Mode 2 The process of OV prevention mode 2 is the same as that of OV prevention mode 1 but it strengthens more the part of DC BUS over the deceleration stop voltage of OV prevention (11-39) in Fig.4.4.92. It can accelerate frequency compensation to avoid OV protection by increasing frequency gain of OV prevention 2 (11-28). When 11-40=3: OV prevention Mode 3 T=The inverter raise the output frequency temporarily to avoid OV, the output frequency wont higher than the value of 01-02 (Maximum Output Frequency of Motor 1).Please adjust the value of 01-02 according to application. If it still occur OV in 11-40=3, please raise the value of 11-64 in 0.1 unit.
It will influence the speed and current if the value of 11-64 is too high. 11-65 is the target voltage of overvoltage prevention mode 3, and it is required to suppress this voltage level as much as possible.
A Reference frequency loss is detected when the frequency command falls 90% within 360ms. The action performed when a reference loss is detected is set with parameter 11-41. 11-41=0: Inverter will decelerate to a stop when a reference loss is detected. 11-41=1: Inverter will continue to operate; reference frequency is the value of Maximum Output Frequency of Motor 1 x the level set in parameter 11-42.
OV prevention modes2/3 and reference loss
11- 64 / Acceleration Speed Gain Adjustment — PDF page 382
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 64 | Acceleration Speed Gain Adjustment |
| 2 | Range | 0.1~10.0 |
11- 65 / Target Main Circuit Voltage — PDF page 382
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 65 | Target Main Circuit Voltage |
| 2 | Range | 200V: 200V~400V 400V: 400V~800V 575V: 520V~1040V 690V: 624V~1248V |
11- 41 / Reference frequency loss detection — PDF page 382
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 41 | Reference frequency loss detection |
| 2 | Range | 0: when reference frequency disappears, the deceleration will stop. 1: when reference frequency disappears, continue to operate according to the proportion of reference frequency x 11-42. |
11- 42 / Reference frequency loss level — PDF page 382
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 42 | Reference frequency loss level |
| 2 | Range | 0.0~100.0 % |
Manual — Reference frequency loss and hold settings — page 383
Manual reference: physical PDF page 383. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The inverter will return to normal operation when: (1) The reference frequency is restored while running and the reference level exceeds 80% of the master frequency command. (2) Stop command is issued. Notes: - Reference frequency loss level (11-42) is corresponding to the maximum output frequency of Motor 1 (01-02). - Reference frequency loss level is used in the analog signal (1: AI1 or 7: AI2) from the selection of main frequency source (00-05). Refer to the following Fig. 4.4.95 for the operation diagram of multi-function digital output (03-11~03-12) when the analog frequency command is in the loss of frequency command.
The hold function is used to temporarily hold the reference frequency in order to prevent stalling the motor or preventing an over current condition during starting or stopping due to load conditions. During start the inverter will operate at the hold frequency at start for the time specified in the parameter 11-44 in order to establish the magnetic flux. Note: The acceleration of deceleration time does not include the start and stop hold time. Refer to the figure 4.4.96.
Figure4.4.95 Operation in reference frequency loss. Analog Frequency Command versus t falls from100% through10% toward0;360ms interval is marked across the fall. Analog frequency command lossing digit output03-11=26or03-12=26 traceOFF→ON→OFF. Literal diagram timing retained without replacing prose recovery criterion.
Reference frequency loss and hold settings
11-43 / Hold frequency at start — PDF page 383
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-43 | Hold frequency at start |
| 2 | Range | 0.0~599.0 Hz |
11-44 / Frequency hold time at start — PDF page 383
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-44 | Frequency hold time at start |
| 2 | Range | 0.0~10.0 Sec |
11-45 / Hold frequency at stop — PDF page 383
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-45 | Hold frequency at stop |
| 2 | Range | 0.0~599.0 Hz |
11-46 / Frequency hold time at stop — PDF page 383
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-46 | Frequency hold time at stop |
| 2 | Range | 0.0~10.0 Sec |
Manual — Frequency hold and KEB settings — page 384
Manual reference: physical PDF page 384. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When the inverter is in stop mode, this function can also be used to prevent wind milling. In addition, it can be used for the purpose of braking using the motor to consume the braking energy resulting in a better controlled stop. Refer to the DC brake parameter 07-16 for DC braking during start. Notes: - The hold function at start is inactive when the hold frequency at start (11-43) is set to a value less than Fmin (01-08). - The hold function at stop is inactive when the hold frequency at stop (11-45) is set to a value less than Fmin (01-08).
KEB function can be used to keep the inverter from tripping on a under voltage condition due to a momentary power-loss. To enable the KEB function set parameter 11-47 to a value greater than 0.0 sec. Upon detection of a power-loss the inverter uses the KEB deceleration time (11-47) to decelerate the motor and using the regenerative energy from the motor to maintain the DC-bus at a nominal level. 11-48: KEB detection level If the DC-bus voltage falls below the value set in 11-48, the KEB is activated and the inverter starts decelerating according to the value set in 11-47. To accelerate back to the original output frequency one of the digital inputs (03-00 to 03-07) set for 48 (KEB acceleration) has to be activated and the DC voltage has to rise above 11-48 + delta V (Delta V = +10V for 230V series, Delta V = +20 V for 460V Series, Delta V = +26 V for 575V Series, Delta V = +30 V for 690V Series). Refer to the example in Figure 4.4.97.
Figure4.4.96 caption Reserved function. Output Frequency versus t shows hold plateau11-43 with interval11-44 at start,hold plateau11-45 with interval11-46 at stop;RUN command high during initial ascent/steady portion then low for deceleration. Caption retained although surrounding prose calls hold function.
Frequency hold and KEB settings
11- 47 / KEB Deceleration time — PDF page 384
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 47 | KEB Deceleration time |
| 2 | Range | 0.0~25.5 Sec |
11- 48 / KEB detection level — PDF page 384
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 48 | KEB detection level |
| 2 | Range | 200V: 190~210 V 400V: 380~420 V 575V: 540~570 V 690V: 540~684 V |
Manual — KEB timing and zero-servo operation — page 385
Manual reference: physical PDF page 385. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When the motor is stopped, the zero-servo function is used to maintain the motor shaft position in SV control mode. Refer to the figure 4.4.98 for zero servo operation.
Figure4.4.97 KEB operation. DC Bus,KEB Detection Level;10V for220V series,20V for440V series. Output Frequency trace shows deceleration inKEB operation andRe-acceleration;Run Command andKEB Re-acceleration Command traces. No575/690threshold shown in figure; preserve source labels independently of384prose.
Figure4.4.98 Zero servo operation. Run command;Zero-servo command03-00–07=46;Zero speed level(the greater of01-08or07-06);Motor speed;Zero-servo Completion03-11–12=31;Zero-servo status interval and11-50 delay. All traces share t axis. No unlabelled topology or numeric interval added.
KEB timing and zero-servo operation
11- 49 / Zero-servo gain — PDF page 385
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 49 | Zero-servo gain |
| 2 | Range | 0.01~5.00 |
11- 50 / Zero-servo count — PDF page 385
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 50 | Zero-servo count |
| 2 | Range | 0~4096 |
11- 51 / Braking selection of zero-speed — PDF page 385
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 51 | Braking selection of zero-speed |
| 2 | Range | 0: Zero-speed DC braking is disabled 1: Zero-speed DC braking is enabled |
Manual — Zero-servo and zero-speed braking restrictions — page 386
Manual reference: physical PDF page 386. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Use one of multi-function digital inputs (03-00 to 03-07) set to 46 to execute the zero-servo command. - If the frequency reference is lower than the zero speed level (the larger of 01-08 or 07-06 (DC braking start frequency)), zero servo operation is active (zero servo start position) and the motor shaft will remain in the same position even if the analog reference signal level is greater than 0. - Deactivating multi-function input set for zero-servo, deactivates the zero-servo operation. - Use multi-function digital outputs (03-11, 03-12 = 31) for zero-servo completed indication. - Zero-servo count 11-50 is used when one of multi-function digital outputs is set to 31 (zero-servo completed). - Zero-servo completion is enabled when the motor shaft position count falls within the zero-servo starting position ± servo counts set in parameter 11-50. - Zero-servo or normal operation command is active when zero-servo completion signal is turned off. 11-49: Zero-servo gain setting Use the zero-servo gain parameter 11-49 to adjust the holding torque in zero-servo operation. If the set value is increased, the holding torque will increase but instability may occur. When 11-49 is set to 1, if 1 circle of position error occurs, 1 rated motor speed will occur. Do not use the zero-servo function at 100% of the inverter rated current as this may cause the inverter to overheat (OH1). Zero-servo may permanently be used to maintain 50 – 60% of the inverter rated current. Increase inverter rating if more is required. 11-50: Zero-servo count Zero servo count is used to specify the zero-servo position offset from the zero-servo start position used for zero-servo completion. 11-51: Operation selection of zero-speed braking In V/F control mode, the DC braking operation (without PG feedback) can be used to the motor shaft. Set 11-51 to select zero-speed braking operation to 1 to enable this function. To use DC braking operation set parameter 00-02 (operation command selection) to 1 and parameter 00-05 (frequency reference selection) to 1, the operation command and frequency reference are now set for external control. When the frequency reference is 0V (or less than 4mA), and the operation command is turned on, the zero-speed ‘DC’ braking operation is activated and holding torque is generated using DC braking. Refer to Figure 4.3.99 for more information on zero-speed DC braking operation. Note: DC braking 07-07 is limited to 20% of the inverter rated current.
Manual — Zero-speed braking and droop settings — page 387
Manual reference: physical PDF page 387. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Droop control is used for load balancing when using two standard AC motors to drive the load in applications such as cranes and conveyors. When droop control is active the inverter reduces the speed when the torque reference rises and increases the speed when the torque reference drops. (a) Load balancing using the standard AC motors. The load torque of motor A, TA > The load torque of motor B ,TB. (b) Load balancing using high slippage AC motors. The load torque of motor A ,TA is very close to the load torque of motor B ,TB.
Figure4.4.99 Zero-speed braking operation. Run command,Frequency Reference,DC Injection Braking(20%max.)versus t;Zero speed level(the larger of01-08or07-06). Braking trace active during run before frequency rises above level and after frequency falls below level until run ends.
Zero-speed braking and droop settings
11-52 / Droop control level — PDF page 387
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-52 | Droop control level |
| 2 | Range | 0.0~100.0% |
11-53 / Droop control delay — PDF page 387
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-53 | Droop control delay |
| 2 | Range | 0.01~2.00 Sec |
11- 76 / Droop frequency level 1 — PDF page 387
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 76 | Droop frequency level 1 |
| 2 | Range | 【0.00~599.00】Hz |
| 3 | 11- 77 | Droop frequency level 2 |
| 4 | Range | 【0.00~599.00】Hz |
| 5 | 11- 78 | Droop torque offset value |
| 6 | Range | 【0.00~100.00】% |
Manual — Droop load balancing and frequency gain curves — page 388
Manual reference: physical PDF page 388. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Droop function can be used to approximate the characteristic of a high slippage motor. Set 11-52 to the percentage of the speed reduction that amounts to 100% of motor torque based on the maximum frequency (01-02). - Droop function is disabled when 11-52 is set to 0.0%.
11-53: Droop control delay This setting is used adjust the response speed of the droop function. Increase value in case of current oscillation.
‧Parameter 11-76 and 11-77 can be used to set the Droop Function starting operations when reaching the set frequency, the Speed Gain Adjustment Curve is shown in the Figure below.
Droop comparison(a):Torque versus Speed;MotorA torque characteristics,MotorB torque characteristics,Load torque,Reference Speed;TA−TB>>0 andTA>TB. Literal comparison labels;no values interpolated.
Droop comparison(b):Torque versus Speed;MotorA andMotorB torque characteristics,Load torque,Reference Speed;TA,TB,TA−TB≃0 andTA≅TB. Source near-equality symbols retained.
Droop correction frequency graph. Frequency vertical,Torque horizontal with−100%,0,100%;descending line. Endpoint differences both labelled(11-52)×(01-02);Droop correction frequency indicated from horizontal guide to line. No numerical correction inferred.
Left Speed Gain Adjustment Curve:source heading Set11-76<11-77;Gain0–1 versus absolute fref. Gain0 through11-76,rises linearly to1at11-77 thenplateau.
Right Speed Gain Adjustment Curve:source heading also Set11-76<11-77;Gain0–1 versus absolute fref. Step0to1at11-76,thenplateau. Source duplicated condition retained; no alternate comparator inferred.
Manual — Droop torque offset keypad stop and UP DOWN — page 389
Manual reference: physical PDF page 389. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
‧Parameter 11-78 can be used to set the Droop Function starting operations when reaching the set Torque Offset Value, the Torque Command Adjustment Curve is shown in the Figure below.
Reset kW-hour meter 12-67 (Accumulative Energy (kWHr)) and 12-68 (Accumulative Energy (MWHr)).
11-55= 0: Stop button disabled when operation command is set for terminals (00-02=1) or communication (00-02=3). 11-55= 1: Stop button enabled
11-56= 0: Changing the reference frequency on the keypad in UP/DOWN control requires the ENTER button to be pressed for the inverter to accept the modified reference frequency. 11-56= 1: Changing the reference frequency on the keypad in UP/DOWN control immediately changes the reference frequency and there for the output frequency. Note: The reference frequency can be changed (up or down) via the keypad or by setting one of multi-functional digital input terminals (03-00, 03-07) to 8 and 9. Refer to instructions of (03-00 - 03-07 = 8 or 9).
Torque Command Adjustment Curve. Horizontal Torque Ref.;deadband boundaries−(11-78)and11-78,flat central zero segment;upper branch labelledTorque Ref.−(11-78),lower branchTorque Ref.+(11-78). Source limits retained,no numeric interpolation.
Droop torque offset keypad stop and UP DOWN
11-54 / Output KWHr initialization — PDF page 389
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-54 | Output KWHr initialization |
| 2 | Range | 0: Do not clear output KWHr 1: Clear output KWHr |
11-55 / STOP key selection — PDF page 389
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-55 | STOP key selection |
| 2 | Range | 0: Stop key is disabled when the operation command is not provided by operator. 1: Stop key is enabled when the operation command is not provided by operator. |
11-56 / UP/DOWN selection — PDF page 389
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11-56 | UP/DOWN selection |
| 2 | Range | 0: UP/DOWN reference frequency adjustment with ENTER key. 1: UP/DOWN reference frequency adjustment without ENTER key. |
Manual — Reference frequency recording and oscillation gains — page 390
Manual reference: physical PDF page 390. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
This function is enabled only when one of multi-function digital input terminals (03-00 to 03-07) is set to 11 (Inhibit ACC / DEC command). 11-58= 0: When ACC / DEC inhibition command is enabled, the motor will stop accelerate or decelerate, and the frequency at the moment will be used as frequency command. If ACC / DEC inhibition command is disabled or stop command enabled, the frequency command will set to original frequency. Besides, when stop command enabled, or the power is cut off and reset. The frequency will be set to 0 Hz Note: If ACC / DEC inhibition command is enabled before running, it will display STP0 after running, due to there is no reference frequency record. 11-58= 1: When ACC / DEC inhibition command is enabled, the output frequency will be recorded and to be used as frequency command. When it switches to stop or the power is cut off and reset, the ACC / DEC inhibition command is still enabled, the frequency command is still recorded and the frequency command is set to the frequency that was recorded. Please refer to the following figure.
It is used to adjust preventing oscillation function. If the oscillation in driving motor occurs at normal duty, it is required to increase the setting value gradually in the unit of 0.01.
It is required to limit the preventing oscillation upper limit within the setting value.
Reference-frequency recording example:Power Supply ON/OFF/ON;Forward Run ON/OFF/ON;Inhibit ACC/DEC Command OFF/ON/OFF/ON;Frequency Reference steps down;Output Frequency has two markedHold intervals,thenstops and reramps after power interruption. Every source label retained; diagram has no explicit11-58selection label and none is assigned.
Reference frequency recording and oscillation gains
11- 58 / Record reference frequency — PDF page 390
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 58 | Record reference frequency |
| 2 | Range | 0: Disable 1: Enable |
11- 59 / Gain of Preventing Oscillation — PDF page 390
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 59 | Gain of Preventing Oscillation |
| 2 | Range | 0.00~2.50 |
11- 60 / Upper Limit of Preventing Oscillation — PDF page 390
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 60 | Upper Limit of Preventing Oscillation |
| 2 | Range | 0~100 % |
Manual — Oscillation prevention and strong magnetic selection — page 391
Manual reference: physical PDF page 391. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Adjust the response of oscillation function. (Time parameter of adjust preventing oscillation function delay.)
When 11-62=0 and 1: Mode 1 and 2, the response to preventing oscillation is slower. When 11-62=2: Mode 3, the response to preventing oscillation is faster.
11-63=0: It has no function of flux-strengthening, the no-load current of high speed and low speed are the same. 11-63=1: It has function of flux-strengthening, the torque of low speed is higher, but the no-load current is also higher, it is suitable for big load in low speed.
Adjust the response of Gain of Preventing Oscillation 3 If occur vibration with motor in ND mode, please increase by 0.01 unit to set.
It is required to limit the preventing oscillation 3 upper limit within the setting value.
Adjust the response of oscillation 3 function. (Time parameter of adjust preventing oscillation function delay.)
Refer to the following for the setting of 11-72 and 11-73.
Gain of Preventing Oscillation3 versusOutput Frequency;0baseline,upper guide11-69;Frequency1=11-72 andFrequency2=11-73. Gain descends from guide atFrequency1tozeroatFrequency2. No unlabelledgain values inferred.
Oscillation prevention and strong magnetic selection
11- 61 / Time Parameter of Preventing Oscillation — PDF page 391
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 61 | Time Parameter of Preventing Oscillation |
| 2 | Range | 0~100 |
11- 62 / Selection of Preventing Oscillation — PDF page 391
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 62 | Selection of Preventing Oscillation |
| 2 | Range | 0: Mode 1 1: Mode 2 2: Mode 3 |
11- 63 / Strong Magnetic Selection — PDF page 391
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 63 | Strong Magnetic Selection |
| 2 | Range | 0: Disable 1: Enable |
11- 69 / Gain of Preventing Oscillation 3 — PDF page 391
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 69 | Gain of Preventing Oscillation 3 |
| 2 | Range | 0.00~200.00 % |
11- 70 / Upper Limit of Preventing Oscillation 3 — PDF page 391
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 70 | Upper Limit of Preventing Oscillation 3 |
| 2 | Range | 0.01~100.00 % |
11- 71 / Time Parameter of Preventing Oscillation 3 — PDF page 391
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 71 | Time Parameter of Preventing Oscillation 3 |
| 2 | Range | 0~30000 ms |
11- 72 / Gain of Preventing Oscillation for switch frequency 1 — PDF page 391
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 72 | Gain of Preventing Oscillation for switch frequency 1 |
| 2 | Range | 0.01~300.00 Hz |
| 3 | 11- 73 | Gain of Preventing Oscillation for switch frequency 2 |
| 4 | Range | 0.01~300.00 Hz |
Manual — Local remote selection and OVP4 — page 392
Manual reference: physical PDF page 392. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The user can set the function of the LOC/ROM button according to the requirement. 11-79=0: Forward and reverse control, can be to set the direction of rotation. 11-79=1: Local and remote control, can switch the panel/external control directly, adjust with external control logic parameters.
The user switches the local / remote mode according to the requirement, in order to protect the personnel and the machine, the user can restrict the local/remote switching through the protection level between each mode to ensure the safety of the switching process.
The OVP mode is mainly used to suppress the recharge voltage generated during deceleration, which causes the driver to exceed the protection limit and generate an OV fault signal. The way of consuming and recovering the voltage in OVP mode 4 is to return the energy to the motor side as a virtual work, thereby venting the voltage to ensure that the drive can operate normally during the rapid deceleration process, but please note that this method is to recharge the energy to the motor side, it will affect the service life of the motor. Therefore, when this mode is turned on, it is necessary to evaluate whether it is suitable for the occasion.
Local remote selection and OVP4
11- 79 / LOC/REM Keypad Button Selection — PDF page 392
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 79 | LOC/REM Keypad Button Selection |
| 2 | Range | 0: Forward / Reverse control 1: Local / Remote control |
11- 80 / Local / Remote Selection Mode — PDF page 392
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 80 | Local / Remote Selection Mode |
| 2 | Range | 0: Allow Switching Directly 1: Switching Prohibited at Running 2: Stop after Switching |
11- 81 / OVP4 Level (%) — PDF page 392
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 11- 81 | OVP4 Level (%) |
| 2 | Range | 100~200% |
| 3 | 11- 82 | OVP4 gain |
| 4 | Range | 0~256 |
Manual — LED monitoring and line speed display — page 393
Manual reference: physical PDF page 393. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
12-Monitoring Parameters
Note: The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize the display sequence see chapter 4.1.3. A510s 220V 50HP and higher models and 440V 100HP and higher models, does not support heatsink temperature display function.
When 12-00=xxx5, LED preset screen will display PID feedback. Parameter 12-01 will refer to the value of 10-33 and display five-digit XXX.XX. For example, When 10-33=9999, preset screen of 12-01=0 will display 99, 12-01=1 will display 99.9, and 12-01=2 will display 99.99. If setting of 12-02 is also referred,12-01=1 and 12-02=1 will display five-digit 99.9Pb; 12-01=2 and 12-02=2 will display 9.99FL and decimal 9 will be hidden.
12-04≠0, Inverter displays the line speed at stop, operation or the modification of frequency. 12-03 is set to the maximum line speed and corresponds to the maximum output frequency. For example, if the line speed display of 12-03 is 1800, the keypad display is 900 when frequency output is 30Hz.
LED monitoring and line speed display
12-00 / Display screen selection (LED) — PDF page 393
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 12-00 | Display screen selection (LED) |
| 2 | Range | Highest bit => 0 0 0 0 0 <= lowest bit The value range of each bit is 0~7 from the highest bit to the lowest bit, 0: No display 1: Output current 2: Output voltage 3: DC bus voltage 4: Heatsink temperature 5: PID feedback 6: AI1 value 7: AI2 value |
12-01 / PID feedback display mode (LED) — PDF page 393
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 12-01 | PID feedback display mode (LED) |
| 2 | Range | 0: Display the feedback value in integer (xxx) 1: Display the feedback value with one place after the decimal point (xx.x) 2: Display the feedback value (x.xx) with two places after the decimal point |
12-02 / PID feedback display unit setting (LED) — PDF page 393
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 12-02 | PID feedback display unit setting (LED) |
| 2 | Range | 0: xxxxx (no unit) 1: xxxPb (pressure) 2: xxxFL (flow) |
12- 03 / Line Speed Display (LED) — PDF page 393
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 12- 03 | Line Speed Display (LED) |
| 2 | Range | 【0~60000】RPM |
| 3 | 12- 04 | Line Speed Display Mode (LED) |
| 4 | Range | 【0】: Display Inverter Output Frequency 【1】: Line Speed Display at Integer.(xxxxx) 【2】: Line Speed Display at One Decimal Place. (xxxx.x) 【3】: Line Speed Display at Two Decimal Places. (xxx.xx) 【4】: Line Speed Display at Three Decimal Places. (xx.xxx) |
Manual — Digital terminal status LED example — page 394
Manual reference: physical PDF page 394. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Terminals S1-S8 are represented using two segments of each digit. Segment turns on when input is active. The bottom segments of each of the first three digits are used to represent the digital outputs (R1, R2, DO1). Segments turn on when output is active. Example1: S1~S8, R1, R2 and DO1 are ON
Example1 input LED segments:allS1–S8 ON. First four digits each have upper-left/upper-right active segments;lefttoright pairs(S1,S2),(S3,S4),(S5,S6),(S7,S8). Fifth digit unlit outline. Source segment illustration retained,not converted to decimal numbers.
Example1 output LED segments:R1,R2,DO1 ON. First three digits have lower segment groups highlighted and labelledR1,R2,DO1 respectively;last two digits unlit. No fabricated numeric display or extra output mapping.
Digital terminal status LED example
12-05 / Status display of digital input terminal (LED / LCD) — PDF page 394
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 12-05 | Status display of digital input terminal (LED / LCD) |
| 2 | Range | Read-only |
Manual — Digital status LCD example and monitor qualifications — page 395
Manual reference: physical PDF page 395. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example2: S1~S8, R1, R2 and DO1 are OFF
Note: Refer to section 4.3 for monitors 12-11~12-64. Monitoring parameter 12-34: Only for JN5-PG-L, JN5-PG-O, JN5-PG-PM optional card and manual pulse generator (MPG) function. Monitoring parameter12-66: Encoder Angle Encoder PG pulse (20-27) is set to correct connection with the encoder wiring. Make the motor rotate forwardly at non-run state and the angle will accumulate to 360°at two times; if make the motor rotate reversely, the angle will regress to 360° at two times. Monitoring parameter 12-67: Cumulative Energy (KWHr) & 12-68: Cumulative Energy (MWHr) Initialization of Cumulative Energy of 11-54 can clear these monitoring parameters. Monitoring parameter 12-38: PID setting & 12-39: PID Feedback Refer to the setting of 10-33~10-35. Monitoring parameter 12-76: No-Load Voltage Output It is required to be with the descriptions of parameter 02-09 (excitation current of motor 1) and parameter 17-09 (motor excitation current). Monitoring parameter 12-78: Z-Phase Bias Value It is required to be with the parameter 21-43 (Offset Angle). Monitoring parameter 12-79: Pulse Input Percentage Refer to parameter 03-30 (Selection of pulse input) Note: It can perform run command when viewing monitoring parameters (12-05~12-82).
Example2 S1–S8,R1,R2,DO1 OFF:eleven zero bits.0:OPEN;1:CLOSE. Printed rightmost-to-leftmost mappingS8,S7,S6,S5,S4,S3,S2,S1,DO1,R2,R1;equivalently lefttorightR1,R2,DO1,S1,S2,S3,S4,S5,S6,S7,S8. These are source status labels,not wiring instructions.
Manual — Inverter model capacity codes and cumulative operation — page 396
Manual reference: physical PDF page 396. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13-Maintenance Parameters
When 13-02=1, time set of 13-03/ 13-04 will be deleted.
13-05= 0: Inverter logs the time while the inverter is powered-up. 13-05= 1: Inverter logs the time when the inverter is running.
Inverter model capacity codes and cumulative operation
Inverter model capacity codes and cumulative operation Unruled source list segmented by actual line centres and typographic column gaps; these are source text-region boundaries, not drawn grid borders.17 left and23 right model-to-code rows, with exact printedA510 model labels.
13-00 / Inverter Capacity Selection — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-00 | Inverter Capacity Selection |
| 2 | Range | ---- |
13-01 / Software version — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-01 | Software version |
| 2 | Range | ---- |
13-02 / Clear Cumulative Operation Hours — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-02 | Clear Cumulative Operation Hours |
| 2 | Range | 0: Disable to Clear Cumulative Operation Hours 1: Clear Cumulative Operation Hours |
13- 03 / Cumulative operation hours 1 — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13- 03 | Cumulative operation hours 1 |
| 2 | Range | 0~23 hours |
13- 04 / Cumulative operation hours 2 — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13- 04 | Cumulative operation hours 2 |
| 2 | Range | 0~65534 days |
13-05 / Selection of cumulative operation time — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-05 | Selection of cumulative operation time |
| 2 | Range | 0: Accumulative operation time while power on 1: Accumulative operation time when it is operating. |
Inverter model: / 13- 00 display — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Inverter model: | 13- 00 display |
| 2 | A510-2001-XXX | 201 |
| 3 | A510-2002-XXX | 202 |
| 4 | A510-2003-XXX | 203 |
| 5 | A510-2005-XXX | 205 |
| 6 | A510-2008-XXX | 208 |
| 7 | A510-2010-XXX | 210 |
| 8 | A510-2015-XXX | 215 |
| 9 | A510-2020-XXX | 220 |
| 10 | A510-2025-XXX | 225 |
| 11 | A510-2030-XXX | 230 |
| 12 | A510-2040-XXX | 240 |
| 13 | A510-2050-XXX | 250 |
| 14 | A510-2060-XXX | 260 |
| 15 | A510-2075-XXX | 275 |
| 16 | A510-2100-XXX | 2100 |
| 17 | A510-2125-XXX | 2125 |
| 18 | A510-2150-XXX | 2150 |
Inverter model: / 13- 00 display — PDF page 396
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Inverter model: | 13- 00 display |
| 2 | A510-4001-XXX | 401 |
| 3 | A510-4002-XXX | 402 |
| 4 | A510-4003-XXX | 403 |
| 5 | A510-4005-XXX | 405 |
| 6 | A510-4008-XXX | 408 |
| 7 | A510-4010-XXX | 410 |
| 8 | A510-4015-XXX | 415 |
| 9 | A510-4020-XXX | 420 |
| 10 | A510-4025-XXX | 425 |
| 11 | A510-4030-XXX | 430 |
| 12 | A510-4040-XXX | 440 |
| 13 | A510-4050-XXX | 450 |
| 14 | A510-4060-XXX | 460 |
| 15 | A510-4075-XXX | 475 |
| 16 | A510-4100-XXX | 4100 |
| 17 | A510-4125-XXX | 4125 |
| 18 | A510-4150-XXX | 4150 |
| 19 | A510-4175-XXX | 4175 |
| 20 | A510-4215-XXX | 4215 |
| 21 | A510-4270-XXX | 4270 |
| 22 | A510-4300-XXX | 4300 |
| 23 | A510-4375-XXX | 4375 |
| 24 | A510-4425-XXX | 4425 |
Manual — Parameter lock settings and first entry — page 397
Manual reference: physical PDF page 397. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When 13-06=0, only parameter 13-06 and frequency command parameter in main screen can be set but other parameters are read-only. When 13-06=1, only user parameters (00-41~00-56) are enabled. Please refer to the instruction of parameters 00-41~00-56. Note: it is only enabled in LCD keypad. When 13-06=2, all parameters are writable except for the read-only parameters. Note: Main frequency setting is 12-16. The value is equal to frequency setting of speed-stage 0 (05-01) in LCD keypad. LED Main Frequency can beset in the main frequency display
When parameter lock key code is enabled (13- 07>0), all parameter except main frequency can’t be modified. Only unlock the key code, modify the parameters is allowable. Setting parameter lock key number example: Step 1
Setting parameter lock key number example Step1:1stentry13-07→READ/ENTER→00000→up/down→12345→READ/ENTER→End→12345→DSP/FUN→13-07. Visible display texts and arrows transcribed as supplier example,not live interaction.
Parameter lock settings and first entry
13-06 / Parameters lock — PDF page 397
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-06 | Parameters lock |
| 2 | Range | 0: Parameters are read-only except 13-06 and main frequency 1: Only User Defined Parameters 2: All parameters are writable |
13- 07 / Parameter Lock Key Code — PDF page 397
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13- 07 | Parameter Lock Key Code |
| 2 | Range | 【00000~65534】 |
Manual — Password confirmation and lifting examples — page 398
Manual reference: physical PDF page 398. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Step 2:
Lifting lock key code (password):
Step2 password confirmation:2ndentry13-07→READ/ENTER→00001. Up/down branch10000→READ/ENTER→Err2,then10000on Set Password failed return path viaDSP/FUN to13-07. Lower up/down branch12345→READ/ENTER→LOC,then12345on Set Password successfully return path viaDSP/FUN to13-07. Source examples only.
Lifting lock key code(password):13-07→READ/ENTER→00002. Up/down upper branch10000→READ/ENTER→LOC,then10000on Password failed to lift return path viaDSP/FUN. Lower branch12345→READ/ENTER→End,then12345on Password successfully lifted return path viaDSP/FUN to13-07. Literal example displays;no live password or validation asserted.
Manual — Factory initialisation choices2–5 — page 399
Manual reference: physical PDF page 399. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down the modified parameters before initializing the inverter. After initialization, the value of 13-08 will return to zero automatically. 13-08=2: 2-wire initialization (60Hz) (220V/440V/690V) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to Figure 4.4.1. Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class) or 690V (660V class). When 01-00V/Curve= F, 01-02 will automatically set to 60Hz. 13-08=3: 3-wire initialization (60Hz) (220V/440V/690V) Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type operation mode. Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class) or 690V (660V class). When 01-00V/Curve= F, 01-02 will automatically set to 60Hz. 13-08=4: 2-wire initialization (50Hz) (230V/415V) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to Figure 4.4.1. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 50Hz. 13-08=5: 3-wire initialization (50Hz) (230V/415V) Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are set for 3-wire start operation and stop command. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 50Hz.
Factory initialisation choices2–5
13-08 / Restore factory setting / Initialize — PDF page 399
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-08 | Restore factory setting / Initialize |
| 2 | Range | 0 : No initialization 2 : 2 wire initialization (60Hz)(220V/440V/690V) 3 : 3 wire initialization (60Hz)(220V/440V/690V) 4 : 2 wire initialization (50Hz)(230V/415V) 5 : 3 wire initialization (50Hz)(230V/415V) 6 : 2 wire initialization (50Hz)(200V/380V/575V) 7 : 3 wire initialization (50HZ)(200V/380V/575V) 8 : PLC initialization 9 : 2 wire Initialization (60Hz)(230V/460V) 10 : 3 wire Initialization (60Hz)(230V/460V) 11 : 2 wire Initialization (60Hz)(230V/400V) 12 : 3 wire Initialization (60Hz)(230V/400V) 13 : 2 wire Initialization (50Hz)(230V/400V) 14 : 3 wire Initialization (50Hz)(230V/400V) 15 : 2 wire Initialization (50Hz)(220V/380V) 16 : 3 wire Initialization (50Hz)(220V/380V) |
Manual — Factory initialisation choices6–13 — page 400
Manual reference: physical PDF page 400. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13-08=6: 2-wire initialization (50Hz) (200V/380V/575V) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to Figure 4.4.1. Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class) or 575V (660V class). When 01-00V/Curve= F, 01-02 will automatically set to 50Hz. 13-08=7: 3-wire initialization (50Hz) (200V/380V/575V) Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are set for 3-wire start operation and stop command. Inverter input voltage (01-14) is automatically set to 200V (200V class) or 380V (400V class) or 575V (660V class). When 01-00V/Curve= F, 01-02 will automatically set to 50Hz. 13-08=8: PLC initialization Clear built-in PLC ladder logic and related values. 13-08=9: 2 wire Initialization (60Hz) (230V/460V) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to Figure 4.4.1. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 460V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 60Hz. 13-08=10: 3 wire Initialization (60Hz) (230/460V) Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type operation mode. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 460V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 60Hz. 13-08=11: 2 wire Initialization (60Hz) (230/400V) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to Figure 4.4.1. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 60Hz. 13-08=12: 3 wire Initialization (60Hz) (230/400V) Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type operation mode. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 60Hz. 13-08=13: 2 wire Initialization (50Hz) (230/400V)
Adjacent source context — repeated to preserve continuation:
Manual — Factory initialisation13–16 and preserved parameters — page 401
Manual reference: physical PDF page 401. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to Figure 4.4.1. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 50Hz. 13-08=14: 3 wire Initialization (50Hz) (230/400V) Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type operation mode. Inverter input voltage (01-14) is automatically set to 230V (200V class) or 400V (400V class). When 01-00V/Curve= F, 01-02 will automatically set to 50Hz. 13-08=15: 2 wire initialization (220V/380V, 50Hz) Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse operation / stop command. Refer to Fig.4.4.1. The input voltage (01-14) will be set to 220V (200V class) or 380V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12 will be set to 50Hz automatically. 13-08=16: 3 wire initialization (220V/380V, 50Hz) Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type operation mode. The input voltage (01-14) will be set to 220V (200V class) or 380V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12 will be set to 50Hz automatically. Parameters don’t be influenced by restore factory setting / Initialize (13-08)
Opening prose continues13-08=13(2-wire initialisation50Hz230V/400V) heading at bottom of physical400; stops before13-08=14heading. Retain source S1/S2 descriptions without engineering validation.
Factory initialisation13–16 and preserved parameters
Adjacent source context — repeated to preserve continuation:
No. / Parameters — PDF page 401
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | No. | Parameters |
| 2 | 00-00 | Control Mode Selection |
| 3 | 00-04 | Language |
| 4 | 00-27 | HD/ND Mode Selection *** |
| 5 | 01-00 | V/F Curve Selection |
| 6 | 01-26 | V/F Curve Selection of Motor 2 |
| 7 | 13-00 | Inverter Capacity Selection |
| 8 | 13-03 | Cumulative Operation Hours 1 |
| 9 | 13-04 | Cumulative Operation Hours 2 |
| 10 | 13-05 | Selection of Cumulative Operation Time |
Manual — Fault history option-card identity and storage — page 402
Manual reference: physical PDF page 402. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
13-09=1: Clears inverter fault history. Note: parameters 12-11~12-15/12-45~12-64 are cleared as well.
This parameter displays the CPLD software version on the control board. It is only displayed on the control board with CPLD.
This parameter displays the ID of option card on the control board. It is only displayed coupled with the option card. 【0】: none 【1】: PG-L 【2】: PG-O 【3】: PG-PM 【4】: PG-PMS 【5】: PG-PMR
This parameter displays the CPLD software version of the option card on the control board. It is only displayed coupled with the option card.
13-14=0, The fault messages are not saved in the fault history (12-46~12-49 & 13-21~13-50) in the process of restart when the auto reset function is active. 13-14=1, The fault messages are saved in the fault history (12-46~12-49 & 13-21~13-50) in the process of restart when the auto reset function is active. Note: Parameters 13-21~13-50 are 30 Fault History: When it detect fault, inverter will store to fault history. If the fault occurs again, parameter 13-21 will change to parameter 13-22.
Fault history option-card identity and storage
13-09 / Fault history clearance function — PDF page 402
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-09 | Fault history clearance function |
| 2 | Range | 0: Do not clear fault history 1: Clear fault history |
13-10 / Parameter Password Function 2 — PDF page 402
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-10 | Parameter Password Function 2 |
| 2 | Range | 0 ~ 9999 |
13-11 / C/B CPLD Ver. — PDF page 402
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-11 | C/B CPLD Ver. |
| 2 | Range | 0.00~9.99 |
13-12 / PG Card Id — PDF page 402
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-12 | PG Card Id |
| 2 | Range | 0~255 |
13-13 / PG Card Ver. — PDF page 402
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-13 | PG Card Ver. |
| 2 | Range | 0.00~9.99 |
13-14 / Fault Storage Selections — PDF page 402
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 13-14 | Fault Storage Selections |
| 2 | Range | 0: Fault Messages of Auto Restart are not saved. 1: Fault Messages of Auto Restart are saved. |
Manual — PLC timer counter and AS settings — page 403
Manual reference: physical PDF page 403. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
14-PLC Parameters
PLC timer counter and AS settings
14-00 / T1 set value 1 — PDF page 403
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 14-00 | T1 set value 1 |
| 2 | 14-01 | T1 set value 2 (mode 7) |
| 3 | 14-02 | T2 set value 1 |
| 4 | 14-03 | T2 set value 2 (mode 7) |
| 5 | 14-04 | T3 set value 1 |
| 6 | 14-05 | T3 set value 2 (mode 7) |
| 7 | 14-06 | T4 set value 1 |
| 8 | 14-07 | T4 set value 2 (mode 7) |
| 9 | 14-08 | T5 set value 1 |
| 10 | 14-09 | T5 set value 2 (mode 7) |
| 11 | 14-10 | T6 set value 1 |
| 12 | 14-11 | T6 set value 2 (mode 7) |
| 13 | 14-12 | T7 set value 1 |
| 14 | 14-13 | T7 set value 2 (mode 7) |
| 15 | 14-14 | T8 set value 1 |
| 16 | 14-15 | T8 set value 2 (mode 7) |
| 17 | Range | 0~9999 |
14-16 / C1 set value — PDF page 403
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 14-16 | C1 set value |
| 2 | 14-17 | C2 set value |
| 3 | 14-18 | C3 set value |
| 4 | 14-19 | C4 set value |
| 5 | 14-20 | C5 set value |
| 6 | 14-21 | C6 set value |
| 7 | 14-22 | C7 set value |
| 8 | 14-23 | C8 set value |
| 9 | Range | 0~65535 |
14-24 / AS1 set value 1 — PDF page 403
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 14-24 | AS1 set value 1 |
| 2 | 14-25 | AS1 set value 2 |
| 3 | 14-26 | AS1 set value 3 |
| 4 | 14-27 | AS2 set value 1 |
| 5 | 14-28 | AS2 set value 2 |
| 6 | 14-29 | AS2 set value 3 |
| 7 | 14- 30 | AS3 set value 1 |
| 8 | 14- 31 | AS3 set value 2 |
| 9 | 14- 32 | AS3 set value 3 |
| 10 | 14- 33 | AS4 set value 1 |
| 11 | 14- 34 | AS4 set value 2 |
| 12 | 14- 35 | AS4 set value 3 |
| 13 | Range | 0~65535 |
Manual — PLC MD settings and monitor values — page 404
Manual reference: physical PDF page 404. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Please refer to section 4.5 for built-in PLC function
15-PLC Monitoring Parameters
PLC MD settings and monitor values
14-36 / MD1 set value 1 — PDF page 404
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 14-36 | MD1 set value 1 |
| 2 | 14-37 | MD1 set value 2 |
| 3 | 14-38 | MD1 set value 3 |
| 4 | 14-39 | MD2 set value 1 |
| 5 | 14-40 | MD2 set value 2 |
| 6 | 14-41 | MD2 set value 3 |
| 7 | 14-42 | MD3 set value 1 |
| 8 | 14-43 | MD3 set value 2 |
| 9 | 14-44 | MD3 set value 3 |
| 10 | 14-45 | MD4 set value 1 |
| 11 | 14-46 | MD4 set value 2 |
| 12 | 14-47 | MD4 set value 3 |
| 13 | Range | 0~65535 |
15-00 / T1 current value 1 — PDF page 404
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 15-00 | T1 current value 1 |
| 2 | 15-01 | T1 current value 2 (mode 7) |
| 3 | 15-02 | T2 current value 1 |
| 4 | 15-03 | T2 current value 2 (mode 7) |
| 5 | 15-04 | T3 current value 1 |
| 6 | 15-05 | T3 current value 2 (mode 7) |
| 7 | 15-06 | T4 current value 1 |
| 8 | 15-07 | T4 current value 2 (mode 7) |
| 9 | 15-08 | T5 current value 1 |
| 10 | 15-09 | T5 current value 2 (mode 7) |
| 11 | 15-10 | T6 current value 1 |
| 12 | 15-11 | T6 current value 2 (mode 7) |
| 13 | 15-12 | T7 current value 1 |
| 14 | 15-13 | T7 current value 2 (mode 7) |
| 15 | 15-14 | T8 current value 1 |
| 16 | 15-15 | T8 current value 2 (mode 7) |
| 17 | Range | 0~9999 |
15-16 / C1 current value — PDF page 404
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 15-16 | C1 current value |
| 2 | 15-17 | C2 current value |
| 3 | 15-18 | C3 current value |
| 4 | 15-19 | C4 current value |
| 5 | 15-20 | C5 current value |
| 6 | 15-21 | C6 current value |
| 7 | 15-22 | C7 current value |
| 8 | 15-23 | C8 current value |
| 9 | Range | 0~65535 |
15-24 / AS1 current value — PDF page 404
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 15-24 | AS1 current value |
| 2 | 15-25 | AS2 current value |
| 3 | 15-26 | AS3 current value |
| 4 | 15-27 | AS4 current value |
| 5 | 15-28 | MD1 current value |
| 6 | 15-29 | MD2 current value |
| 7 | 15-30 | MD3 current value |
| 8 | 15-31 | MD4 current value |
| 9 | 15-32 | TD current value |
| 10 | Range | 0~65535 |
Manual — LCD monitor selection and display units — page 405
Manual reference: physical PDF page 405. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
16-LCD Function group
At power-up the inverter shows two monitor section on the display, main monitor section and the sub-screen monitor section (smaller font). Choose the monitor signal to be displayed as the main-screen monitor screen in parameter 16-00, and the monitor signals to be displayed on the sub-screen monitor in parameters 16-01 and 16-02, similar to monitor parameters 12-5 ~ 12-82.
(1). Display unit of digital operator (16-03) Set the units of the following items to be displayed, the frequency reference (05-01, 00-18, 06-01~06-15) and the monitoring frequency 12-16, 12-17 (Output frequency)
LCD monitor selection and display units
16-00 / Main screen monitoring — PDF page 405
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-00 | Main screen monitoring |
| 2 | Range | 5~82 |
16-01 / Sub-screen monitoring 1 — PDF page 405
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-01 | Sub-screen monitoring 1 |
| 2 | Range | 5~82 |
16-02 / Sub-screen monitoring 2 — PDF page 405
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-02 | Sub-screen monitoring 2 |
| 2 | Range | 5~82 |
16-03 / Display unit — PDF page 405
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-03 | Display unit |
| 2 | Range | 0: Frequency display unit is Hz (Resolution is 0.01Hz) 1: Frequency display unit is % (Resolution is 0.01%) 2: Frequency display unit is rpm. 3~39: Reserved 40~9999: 100% is XXXX with no decimals (integer only) 10001~19999: 100% is XXX.X with 1 decimal 20001~29999: 100% is XX.XX with 2 decimals 30001~39999: 100% is X.XXX with 3 decimals |
16-04 / Engineering unit — PDF page 405
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-04 | Engineering unit |
| 2 | Range | 0: No Unit 1: FPM 14: m/s 2: CFM 15: MPM 3: PSI 16: CMM 4: GPH 17: W 5: GPM 18: KW 6: IN 19: m 7: FT 20: °C 8: /s 21: RPM 9: /m 22: Bar 10: /h 23: Pa 11:°F 24: Kpa 12: inW 25: PRS 13: HP 26: SPM |
Manual — LCD engineering display scaling — page 406
Manual reference: physical PDF page 406. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(2). Display unit of engineering (16-04). When 16-03 = 00040-39999, engineering units are enabled. The displayed set range and the frequency range of unit (05-01, 06-01~06-15) as well as the monitoring frequency (12-16, 12-17) are changed by parameters 16-04 and 16-03.
Display scaling notation:five boxes □ □□□□;first box sets number of decimal places,last four full display scaling excluding decimals.00040–09999:□□□□ integer example1000;10001–19999:□□□.□ example10.0;20001–29999:□□.□□ example10.00;30001–39999:□.□□□ example10.000. Empty square placeholders retained literally.
LCD engineering display scaling
16-03 / Set / displayed contents — PDF page 406
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | 16-03 | Set / displayed contents | Set / displayed contents | Set / displayed contents | Set / displayed contents |
| 2 | 0 | 0.01 Hz | 0.01 Hz | 0.01 Hz | 0.01 Hz |
| 3 | 1 | 0.01 % (maximum output frequency 01-02=100%) | 0.01 % (maximum output frequency 01-02=100%) | 0.01 % (maximum output frequency 01-02=100%) | 0.01 % (maximum output frequency 01-02=100%) |
| 4 | 2 | Frequency display unit is rpm | Frequency display unit is rpm | Frequency display unit is rpm | Frequency display unit is rpm |
| 5 | 3 - 39 | Reserved | Reserved | Reserved | Reserved |
| 6 | 00040 - 39999 | Set the decimal point by using the fifth place. i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <example> | Set the decimal point by using the fifth place. i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <example> | Set the decimal point by using the fifth place. i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <example> | Set the decimal point by using the fifth place. i.e. □ □□□□ Sets full display scaling excluding decimals Set the number of decimal places 00040 - 09999: □□□□ (Integer only e.g. 1000 ) 10001 - 19999: □□□. □ (1 decimal place e.g. 10.0) 20001 - 29999: □□. □□ (2 decimal places, e.g. 10.00) 30001 - 39999: □. □□□ (3 decimal places, e.g. 10.000) <example> |
| 7 | 00040 - 39999 | 16-03 | Display | Display unit | Display example |
| 8 | 00040 - 39999 | 00040 – 09999 | □□□□ | use 16-04 setting | Example: 100 % speed is 0200 > set 16-03=00200 (from 05-01, 06-01 to 06-15, set range from 0040 to 9999). > set 16-04=0 (no unit) |
| 9 | 00040 - 39999 | 10001 – 19999 | □□□. □ | use 16-04 setting | Example: 100 % speed is 200.0 CFM > set 16-03=12000 (05-01, 06-01 to 06-15, set range from 0000 to 9999). > set 16-04=2 (CFM) > 60% speed will be displayed as 120.0 CFM |
| 10 | 00040 - 39999 | 20001 – 29999 | □□. □□ | use 16-04 setting | Example: 100 % speed is 65.00ºC > set 16-03=26500 (05-01, 06-01 to 06-15, set range from 0000 to 9999) > set 16-04=20 (ºC) > 60% of speed is displayed as 39.00 ºC |
| 11 | 00040 - 39999 | 30001 – 39999 | □. □□□ | use 16-04 setting | Example: 100 % speed is 2.555 m/s > set 16-03=32555 > set 16-04=14 (m/s) > 60% speed is displayed as 1.533 m/s |
Manual — LCD backlight and parameter copy permissions — page 407
Manual reference: physical PDF page 407. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Adjust the screen contrast of the digital operator. If it is set to 0, the screen backlight is turned off.
LCD digital operator with built-in memory (EEPROM) can be used to store and retrieve parameters: (1) Read: Save inverter parameters to the digital operator (INV → OP). (2) Write: Write the parameters from the digital operator to the inverter and save (OP → INV). (3) Verify: Compare the inverter parameters against the parameters in the digital operator. 16-07=0: No action 16-07=1: Read (all parameters are copied from the inverter to the keypad). 16-07=2: Write (all parameter are copied from the keypad to the inverter). 16-07=3: Verify (Compare the set value of the inverter to the parameter of the digital operator). Set 16-08 = 0, to prevent the saved parameter data stored in the digital operator from accidentally being overwritten. When parameter 16-08=0 and the read operation is executed (16-07=1) a warning message of "RDP Read Prohibited" will be displayed on the keypad and the read operation is cancelled. Refer to the following steps for copy function operation. For the write-in operation requires the following items to match. (1) Inverter type (2) Inverter rated capacity and voltage Note: 1. Inverter in V1.20 version or the above will support the data in older version written in newer version. If the version switch is completed, the power supply is restarted. 2. Data copy is not limited by parameter 00-00 (control mode selection) in the inverter in V1.20 version or the above.
LCD backlight and parameter copy permissions
16-05 / LCD backlight — PDF page 407
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-05 | LCD backlight |
| 2 | Range | 0~7 |
16-07 / Copy function selection — PDF page 407
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-07 | Copy function selection |
| 2 | Range | 0: Do not copy parameter 1: Read inverter parameters and save to the keypad 2: Write the keypad parameters to inverter 3: Compare parameters of inverter and keypad |
16-08 / Selection of allowing reading — PDF page 407
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-08 | Selection of allowing reading |
| 2 | Range | 0: Do not allow to read inverter parameters and save to the keypad 1: Allow to read inverter parameters and save to the keypad |
Manual — READ inverter parameters to keypad — page 408
Manual reference: physical PDF page 408. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
■ READ: Copy inverter parameters to the keypad
LCD source panel 1;procedure step 1: Group;14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func. selected. Printed labels only; not live control or inferred operation.
LCD source panel 2;procedure step 2: PARA16;−07:Copy Sel selected;−08:READ Sel;−09:Keypad Loss Sel. Printed labels only; not live control or inferred operation.
LCD source panel 3;procedure step 3: Edit16-07;Copy Sel;0 Normal;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD source panel 4;procedure step 4: Edit16-07;Copy Sel;1 READ;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD source panel 5;procedure step 5: −ADV−;READ;INV→OP;partly filled progress bar. Printed labels only; not live control or inferred operation.
LCD source panel 6;procedure step 6: −ADV−;READ COMPLETE;full progress bar. Printed labels only; not live control or inferred operation.
LCD source panel 7;procedure step 6: RDP;Read Prohibited. Printed labels only; not live control or inferred operation.
LCD source panel 8;procedure step 7: Edit16-07;Copy Sel;1 READ;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD image panels transcribed separately by exact row region; blank native LCD cells do not signify absent content. Step6physical merged cell spans success and error subrows; same6retained in both. Enlarged source crops confirm selected digits0/1/2/3;none inferred from descriptions.
READ inverter parameters to keypad
Steps / Keypad (English) / Description — PDF page 408
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Steps | Keypad (English) | Description |
| 2 | 1 | ⟦blank source cell⟧ | Select the copy function group (16) from the group menu. |
| 3 | 2 | ⟦blank source cell⟧ | Press the Read / Enter key and select parameter (16-07) copy sel. |
| 4 | 3 | ⟦blank source cell⟧ | Press the Read / Enter key to display the data setting / read screen (LCD display is inversed). |
| 5 | 4 | ⟦blank source cell⟧ | Change the set value to 1 (read) by using the up arrow key. |
| 6 | 5 | ⟦blank source cell⟧ | • Use Read / Enter key to enable the read operation, the display is shown as the left. • The bottom of LCD display will show a bar to indicate the read progress. |
| 7 | 6 | ⟦blank source cell⟧ | “READ COMPLETE” will be displayed on the keypad when reading was successful. |
| 8 | 6 | ⟦blank source cell⟧ | • The error message of "RDP Read Prohibited" may occur on the keypad when reading parameters from the inverter is prohibited. • If the error is displayed, press any key to remove the error message and go back to parameter 16-07. |
| 9 | 7 | ⟦blank source cell⟧ | When DSP/FUN key is pressed, the display returns to parameter 16-07. |
Manual — WRITE keypad parameters to inverter — page 409
Manual reference: physical PDF page 409. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
WRITE: Copy Keypad parameters to the Inverter
LCD source panel 1;procedure step 1: Group;14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func. selected. Printed labels only; not live control or inferred operation.
LCD source panel 2;procedure step 2: PARA16;−07:Copy Sel selected;−08:READ Sel;−09:Keypad Loss Sel. Printed labels only; not live control or inferred operation.
LCD source panel 3;procedure step 3: Edit16-07;Copy Sel;0 Normal;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD source panel 4;procedure step 4: Edit16-07;Copy Sel;2 WRITE;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD source panel 5;procedure step 5: −ADV−;WRITE;INV→OP;partly filled progress bar. Printed labels only; not live control or inferred operation.
LCD source panel 6;procedure step 6: −ADV−;WRITE COMPLETE;full progress bar. Printed labels only; not live control or inferred operation.
LCD source panel 7;procedure step 6: WRE;Write Error. Printed labels only; not live control or inferred operation.
LCD source panel 8;procedure step 7: Edit16-07;Copy Sel;2 WRITE;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD image panels transcribed separately by exact row region; blank native LCD cells do not signify absent content. Step6physical merged cell spans success and error subrows; same6retained in both. Enlarged source crops confirm selected digits0/1/2/3;none inferred from descriptions.
WRITE keypad parameters to inverter
Steps / LCD Display (English) / Description — PDF page 409
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Steps | LCD Display (English) | Description |
| 2 | 1 | ⟦blank source cell⟧ | Select the copy function group (16) from the group menu. |
| 3 | 2 | ⟦blank source cell⟧ | Press the Read / Enter key and select parameter (16-07) copy sel. |
| 4 | 3 | ⟦blank source cell⟧ | Press the Read / Enter key to display the data setting / read screen (LCD display is inversed). |
| 5 | 4 | ⟦blank source cell⟧ | Change the set value to 2 (write) by using the up arrow key. |
| 6 | 5 | ⟦blank source cell⟧ | • Use Read / Enter key to enable the read operation, the display is shown as the left. • The bottom of LCD display will show a bar to indicate the read progress. |
| 7 | 6 | ⟦blank source cell⟧ | “WRITE COMPLETE” will be displayed on the keypad when writing was successful. . Until the subsequent display of "SysInit", please power off and restart. |
| 8 | 6 | ⟦blank source cell⟧ | • The error message of “WRE Write Error " may occur on the keypad when writing parameters to the inverter is prohibited. • If the error is displayed, press any key to remove the error message and go back to parameter 16-07. |
| 9 | 7 | ⟦blank source cell⟧ | When DSP/FUN key is pressed, the display returns to parameter 16-07. |
Manual — VERIFY parameter comparison and keypad removal — page 410
Manual reference: physical PDF page 410. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
■ Verify: Compare Inverter Parameters against Keypad Parameters
16-09=0: Continue operating when keypad is removed. 16-09=1: Trip inverter when keypad is removed while operating in local mode.
LCD source panel 1;procedure step 1: Group;14 PLC Setting;15 PLC Monitor;16 LCD Keypad Func. selected. Printed labels only; not live control or inferred operation.
LCD source panel 2;procedure step 2: PARA16;−07:Copy Sel selected;−08:READ Sel;−09:Keypad Loss Sel. Printed labels only; not live control or inferred operation.
LCD source panel 3;procedure step 3: Edit16-07;Copy Sel;0 Normal;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD source panel 4;procedure step 4: Edit16-07;Copy Sel;3 VERIFY;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD source panel 5;procedure step 5: −ADV−;VERIFY;INV→OP;partly filled progress bar. Printed labels only; not live control or inferred operation.
LCD source panel 6;procedure step 6: −ADV−;VERIFY COMPLETE;full progress bar. Printed labels only; not live control or inferred operation.
LCD source panel 7;procedure step 6: VRYE;Verify Error. Printed labels only; not live control or inferred operation.
LCD source panel 8;procedure step 7: Edit16-07;Copy Sel;3 VERIFY;(0–3);<0>. Printed labels only; not live control or inferred operation.
LCD image panels transcribed separately by exact row region; blank native LCD cells do not signify absent content. Step6physical merged cell spans success and error subrows; same6retained in both. Enlarged source crops confirm selected digits0/1/2/3;none inferred from descriptions.
VERIFY parameter comparison and keypad removal
Steps / LCD Display (English) / Description — PDF page 410
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Steps | LCD Display (English) | Description |
| 2 | 1 | ⟦blank source cell⟧ | Select the copy function group (16) from the group menu. |
| 3 | 2 | ⟦blank source cell⟧ | Press the Read / Enter key and select parameter (16-07) copy sel. |
| 4 | 3 | ⟦blank source cell⟧ | Press the Read / Enter key to display the data setting / read screen (LCD display is inversed). |
| 5 | 4 | ⟦blank source cell⟧ | Change the set value to 3 (verify) by using the up arrow key. |
| 6 | 5 | ⟦blank source cell⟧ | • Use Read / Enter key to enable the read operation, the display is shown as the left. • The bottom of LCD display will show a bar to indicate the read progress. |
| 7 | 6 | ⟦blank source cell⟧ | “VERIFY COMPLETE” will be displayed on the keypad when writing was successful. |
| 8 | 6 | ⟦blank source cell⟧ | • The error message of “VRYE Verify Error " may occur on the keypad when writing parameters to the inverter is prohibited. • If the error is displayed, press any key to remove the error message and go back to parameter 16-07. |
| 9 | 7 | ⟦blank source cell⟧ | When DSP/FUN key is pressed, the display returns to parameter 16-07. |
16-09 / Selection of keypad removed (LCD) — PDF page 410
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-09 | Selection of keypad removed (LCD) |
| 2 | Range | 0: Keep operating when LCD keypad is removed. 1: Display fault when LCD keypad is removed. |
Manual — RTC display and date time settings — page 411
Manual reference: physical PDF page 411. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Set the internal clock before using the function of Real Time Clock (RTC). RTC date setting is determined by parameter 16-11 and RTC time setting is determined by parameter 16-12. RTC is displayed in the top of the keypad and refer to Fig.4.4.85 for the selection of RTC time display (16-10) is set to 1.
Notes: - RTC is not enabled if keypad does not connect with the inverter. - The counting time continues running regardless of the function being hide or display in the paramerer 16-10 (RTC Time Display Setting). Users can apply the parameters 12-72 and 12-73 to monitor the specific RTC date and time. RTC has the following characteristics: - Four times a day - Four weeks - Timer offset function (preset time) - Timer enables via multi-function digital input - Selection for constant time and speed - Timer enables multi-function digital output
Figure4.4.85 RTC display example:Monitor00:00;Freq Ref12-16=000.00Hz;12-17=000.00Hz;12-18=0000.0A. Historical example only.
RTC display and date time settings
16- 10 / RTC Time Display Setting — PDF page 411
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16- 10 | RTC Time Display Setting |
| 2 | Range | 【0】: Hide 【1】: Display |
| 3 | 16- 11 | RTC Date Setting |
| 4 | Range | 【12.01.01 ~ 99.12.31】 |
| 5 | 16- 12 | RTC Time Setting |
| 6 | Range | 【00:00 ~ 23:59】 |
Manual — RTC periods timers and offset settings — page 412
Manual reference: physical PDF page 412. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
RTC periods timers and offset settings
16- 13 / RTC Timer Function — PDF page 412
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16- 13 | RTC Timer Function |
| 2 | Range | 【0】: Disable 【1】: Enable 【2】: Set by DI |
| 3 | 16- 14 | P1 Start Time |
| 4 | 16- 15 | P1 Stop Time |
| 5 | 16- 18 | P2 Start Time |
| 6 | 16- 19 | P2 Stop Time |
| 7 | 16- 22 | P3 Start Time |
| 8 | 16- 23 | P3 Stop Time |
| 9 | 16- 26 | P4 Start Time |
| 10 | 16- 27 | P4 Stop Time |
| 11 | Range | 【00:00 ~ 23:59】 |
| 12 | 16- 16 | P1 Start Date |
| 13 | 16- 17 | P1 Stop Date |
| 14 | 16-20 | P2 Start Date |
| 15 | 16- 21 | P2 Stop Date |
| 16 | 16- 24 | P3 Start Date |
| 17 | 16- 25 | P3 Stop Date |
| 18 | 16- 28 | P4 Start Date |
| 19 | 16- 29 | P4 Stop Date |
| 20 | Range | 【1】: Mon 【2】: Tue 【3】: Wed 【4】: Thu 【5】: Fri 【6】: Sat 【7】: Sun |
| 21 | 16- 30 | Selection of RTC Offset |
| 22 | Range | 【0】: Disable 【1】: Enable 【2】: Set by DI |
| 23 | 16- 31 | RTC Offset Time Setting |
| 24 | Range | 【00:00 ~ 23:59】 |
| 25 | 16- 32 | Source of Timer 1 |
| 26 | 16- 33 | Source of Timer 2 |
| 27 | 16- 34 | Source of Timer 3 |
| 28 | 16- 35 | Source of Timer 4 |
| 29 | Range | 【0~31】: Refer to Table 4.4.13 |
| 30 | 16- 36 | Selection of RTC Speed |
| 31 | Range | 【0】: Off 【1】: By Timer 1 【2】: By Timer 2 【3】: By Timer 3 |
Manual — RTC timer structure and rotation selection — page 413
Manual reference: physical PDF page 413. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source of timer can be selected to link multiple time periods and one time period can be set to multiple timers.
Timer is set by the following steps:
Start the timer:
Timer starts via the setting of RTC timer function (16-13).
Set the time period:
Set the start & stop time and date. If the setting of start time is equal to that of stop time, timing period is off.
The timer is enabled:
Arrange time period to the specific timer (16-32~16-35).
Link to parameters:
The timer can be linked to the relay output. One relay output can be only linked to one timer( ex. 03-11, 03-12 and 03-39, 16-36).
Note: If the stop time is set to 12:00, Motor start to stop from 12:01.
Refer to Fig.4.4.86 for RTC structure.
Figure4.4.86 RTC structure:Step1 Start TimerG16-13 andOffset Time On/OffG16-30;Step2 Time Period1G16-14–17,Period2G16-18–21,Period3G16-22–25,Period4G16-26–29,Offset TimeG16-31;Step3 Timer1G16-32,Timer2G16-33,Timer3G16-34,Timer4G16-35;Step4G16-36RTC Speed Selection,G03-11RelayR1A–R1C,G03-12RelayR2A–R2C,G03-39RelayR3A–R3C. Braces retained as source grouping;no inferred circuit topology.
Opening4Timer4 and5Timer1+2 continue16-36table onphysical412.
RTC timer structure and rotation selection
/ 【4】: By Timer 4 【5】: By Timer 1+2 — PDF page 413
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | ⟦blank source cell⟧ | 【4】: By Timer 4 【5】: By Timer 1+2 |
| 2 | 16- 37 | Selection of RTC Rotation Direction |
| 3 | Range | 【xxx0 B】: RTC Run1 Forward Rotation 【xxx1 B】: RTC Run1 Reverse Rotation 【xx0x B】: RTC Run2 Forward Rotation 【xx1x B】: RTC Run2 Reverse Rotation 【x0xx B】: RTC Run3 Forward Rotation 【x1xx B】: RTC Run3 Reverse Rotation 【0xxx B】: RTC Run4 Forward Rotation 【1xxx B】: RTC Run4 Reverse Rotation |
Manual — RTC timer bit combinations and speed selection — page 414
Manual reference: physical PDF page 414. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Refer to the following Table 4.4.13 for the selection of timer operation cycle. Table 4.4.13 Arrange time period to the timer function
Reference frequency and motor rotation direction are controlled by RTC function. 16-36=0: RTC speed selection is disabled. 16-36=1: Timer 1 is enabled. Reference frequency = Frequency Setting of Speed-Stage 0 (05-01) 16-36=2: Timer 2 is enabled. Reference frequency = Frequency Setting of Speed-Stage 0 (05-01) 16-36=3: Timer 3 is enabled. Reference frequency = Frequency Setting of Speed-Stage 0 (05-01) 16-36=4: Timer 4 is enabled.
RTC timer bit combinations and speed selection
16-32 ~ 16-35 / O / P4 / P3 / P2 / P1 / Timer Function / Display — PDF page 414
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | 16-32 ~ 16-35 | O | P4 | P3 | P2 | P1 | Timer Function | Display |
| 2 | 0 | 0 | 0 | 0 | 0 | 0 | Without the selection of timer | None |
| 3 | 1 | 0 | 0 | 0 | 0 | 1 | Time Period 1 | P1 |
| 4 | 2 | 0 | 0 | 0 | 1 | 0 | Time Period 2 | P2 |
| 5 | 3 | 0 | 0 | 0 | 1 | 1 | Time Period 1 and 2 | P1+P2 |
| 6 | 4 | 0 | 0 | 1 | 0 | 0 | Time Period 3 | P3 |
| 7 | 5 | 0 | 0 | 1 | 0 | 1 | Time Period 1 and 3 | P1+P3 |
| 8 | 6 | 0 | 0 | 1 | 1 | 0 | Time Period 2 and 3 | P2+P3 |
| 9 | 7 | 0 | 0 | 1 | 1 | 1 | Time Period 1 , 2 and 3 | P1+P2+P3 |
| 10 | 8 | 0 | 1 | 0 | 0 | 0 | Time Period 4 | P4 |
| 11 | 9 | 0 | 1 | 0 | 0 | 1 | Time Period 1 and 4 | P1+P4 |
| 12 | 10 | 0 | 1 | 0 | 1 | 0 | Time Period 2 and 4 | P2+P4 |
| 13 | 11 | 0 | 1 | 0 | 1 | 1 | Time Period 1 , 2 and 4 | P1+P2+P4 |
| 14 | 12 | 0 | 1 | 1 | 0 | 0 | Time Period 3 and 4 | P3+P4 |
| 15 | 13 | 0 | 1 | 1 | 0 | 1 | Time Period 1 , 3 and 4 | P1+P3+P4 |
| 16 | 14 | 0 | 1 | 1 | 1 | 0 | Time Period 2 , 3 and 4 | P2+P3+P4 |
| 17 | 15 | 0 | 1 | 1 | 1 | 1 | Time Period 1 , 2 , 3 and 4 | P1+P2+P3+P4 |
| 18 | 16 | 1 | 0 | 0 | 0 | 0 | Offset selection | Offset (O) |
| 19 | 17 | 1 | 0 | 0 | 0 | 1 | Offset and time period 1 | O+P1 |
| 20 | 18 | 1 | 0 | 0 | 1 | 0 | Offset and time period 2 | O+P2 |
| 21 | 19 | 1 | 0 | 0 | 1 | 1 | Offset and time period 1 and 2 | O+P1+P2 |
| 22 | 20 | 1 | 0 | 1 | 0 | 0 | Offset and time period 3 | O+P3 |
| 23 | 21 | 1 | 0 | 1 | 0 | 1 | Offset and time period 1 and 3 | O+P1+P3 |
| 24 | 22 | 1 | 0 | 1 | 1 | 0 | Offset and time period 2 and 3 | O+P2+P3 |
| 25 | 23 | 1 | 0 | 1 | 1 | 1 | Offset and time period 1 , 2 and 3 | O+P1+P2+P3 |
| 26 | 24 | 1 | 1 | 0 | 0 | 0 | Offset and time period 4 | O+P4 |
| 27 | 25 | 1 | 1 | 0 | 0 | 1 | Offset and time period 1 and 4 | O+P1+P4 |
| 28 | 26 | 1 | 1 | 0 | 1 | 0 | Offset and time period 2 and 4 | O+P2+P4 |
| 29 | 27 | 1 | 1 | 0 | 1 | 1 | Offset and time period 1 , 2 an 4 | O+P1+P2+P4 |
| 30 | 28 | 1 | 1 | 1 | 0 | 0 | Offset and time period 3 and 4 | O+P3+P4 |
| 31 | 29 | 1 | 1 | 1 | 0 | 1 | Offset and time period 1 , 3 and 4 | O+P1+P3+P4 |
| 32 | 30 | 1 | 1 | 1 | 1 | 0 | Offset and time period 2 , 3 and 4 | O+P2+P3+P4 |
| 33 | 31 | 1 | 1 | 1 | 1 | 1 | Offset and time period 1 , 2 , 3 and 4 | O+P1+P2+P3+P4 |
Manual — RTC speed stages run command and weekly example — page 415
Manual reference: physical PDF page 415. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Reference frequency = Frequency Setting of Speed-Stage 0 (05-01) 16-36=5: Timer 1 and 2 are enabled. Reference frequency is enabled by the simultaneous operation of timer 1 and 2. Notes: - The inverter runs via the start of the specific timer without the influence of other timers. - The selection of RTC speed setting (16-36) is affected by the action of time period 1 to 4 (P1~P4) which is corresponding to the selection of RTC rotation direction (16-37). For example: When the selection of RTC speed is set to 5 (by timer 1+2), source of run command (00-02) and source of frequency command (00-05) are required to set to RTC. Thus, reference frequency is controlled by RTC timer 1 and 2 and the inverter continues running. Refer to Table 4.4.14 for the control of reference frequency. Note: Selection of RTC Rotation Direction (16-37) is limited by the Motor Direction Lock Selection(11-00). Note: The offset 16-37 running direction will select by the direction of the timer 1 Table 4.4.14 Reference frequency is determined by timer 1 and 2
RTC function can not run normally when: - When multi-function terminal (03-00~03-05) is set to the fire mode. - When KEB function is enabled Source of main frequency of RTC function is according to Table 4.4.14 and also can refer to main and alternative frequency command modes (00-07). If main run command source selection (00-02) is set to 0~3 (0: keypad, 1: external terminal, 2: communication control, 3: PLC), refer to Table 4.4.15 for the relationship between main run command and RTC timer status. Table 4.4.15 Relationship between main run command and RTC timer status
Take an example for RTC timer connecting with different parameters: The work time on Monday is 6:00 AM to 10:00 PM. The work time on Tuesday to Friday is 8:00 AM to 8:00 PM. The work time on Saturday is 8:00 AM to 6:00 PM.
Opening reference-frequency stage0sentence continues16-36=4heading onphysical414.
RTC speed stages run command and weekly example
Timer 1 / Timer 2 / Main Frequency Command Source Selection (00-05) / Source of frequency setting / Selection of rotation direction — PDF page 415
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Timer 1 | Timer 2 | Main Frequency Command Source Selection (00-05) | Source of frequency setting | Selection of rotation direction |
| 2 | 0 | 0 | 6(RTC) | Set by frequency setting of speed-stage 0 (05-01) | By RTC 1 (16-37) |
| 3 | 1 | 0 | 6(RTC) | Set by frequency setting of speed-stage 1 (05-02) | By RTC 2 (16-37) |
| 4 | 0 | 1 | 6(RTC) | Set by frequency setting of speed-stage 2 (05-03) | By RTC 3 (16-37) |
| 5 | 1 | 1 | 6(RTC) | Set by frequency setting of speed-stage 3 (05-04) | By RTC 4 (16-37) |
Main run command 00-02 / RTC timer x status / Inverter status — PDF page 415
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Main run command 00-02 | RTC timer x status | Inverter status |
| 2 | 0~3 | 0 | Inverter can not run (without run command) |
| 3 | 0~3 | 1 | Inverter can not run (without run command) |
| 4 | 4 | 0 | Inverter can not run (RTC timer is disabled) |
| 5 | 4 | 1 | Inverter runs and rotates depending on the function of 16-37. |
Manual — RTC weekly example schedule — page 416
Manual reference: physical PDF page 416. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The work time on Sunday is 8:00 AM to 12:00 PM. Motor runs on weekdays (Mon. to Fri.) at speed 1 and on weekends at speed 2. Start up the timer in the parameter group 16 (Set the internal time first to enable this function). Set the correct date and time in the parameters 16-11 and 16-12 and set parameter 16-13 to 1(enable RTC timer function). Set time period 1 (P1) Start time 1: 16-14 = 06:00:00 (6:00 AM) Stop time 1: 16-15 = 22:00:00 (10:00 PM) Start date 1: 16-16 = 1 (Monday) Stop date 1: 16-17 = 1 (Monday) Set time period 2 (P2) Start time 2: 16-18 = 08:00:00 (8:00 AM) Stop time 2: 16-19 = 20:00:00 (8:00 PM) Start date 2: 16-20 = 2 (Tuesday) Stop date 2: 16-21 = 5 (Friday) Set time period 3 (P3) Start time 3: 16-22 = 08:00:00 (8:00 AM) Stop time 3: 16-23 = 18:00:00 (6:00 PM) Start date 3: 16-24 = 6 (Saturday) Stop date 3: 16-25 = 6 (Saturday) Set time period 4 (P4) Start time 4: 16-26 = 08:00:00 (8:00 AM) Stop time 4: 16-27 = 12:00:00 (12:00 AM) Start date 4: 16-28 = 7 (Sunday) Stop date 4: 16-29 = 7 (Sunday)
Figure4.4.87 Weekly RTC example. Time axis00:00to24:00 in2hour increments. Mon Period1 06:00–22:00;Tue Wed Thu Fri Period2 08:00–20:00;Sat Period3 08:00–18:00;Sun Period4 08:00–12:00. Weekdays and Weekends labelled separately;no unprinted schedule inferred.
Manual — RTC offset and accuracy — page 417
Manual reference: physical PDF page 417. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Timer 1 is enabled to set all the time periods (P1, P2, P3, P4) 16-32 = 15: Source of timer 1 = P1 + P2 + P3 + P4) Selection of RTC speed is determined by timer 1 16-36 = 1: Timer 1 is enabled. Frequency setting is speed-stage 0 (05-01). Rotation direction (16-37) is set to 0000b. Then, the rotation direction of time period 1~4 (P1~P4) is corresponding to the setting of 16-37. Choose two constant speeds (speed 1 & speed 2) 16-36 = 5: Timer 1+2 is enabled. When timer 1 is enabled, frequency setting is speed-stage 1; while timer 2 is enabled, frequency setting is speed-stage 2. Rotation direction (16-37) is set to 0000b. Then, when timer 1 and timer 2 are active, direction of motor rotation is forward rotation. Note: Select RTC offset (16-30) and set RTC offset time (16-31) to enable the offset time. Inverter runs depending on the arranging time period to timer function. Refer to the following Fig.4.4.88.
Figure 4.4.88 Operation of offset time For example: Inverter runs at the time period exclusive P1: When 16-36=1 (selection of RTC speed is set to timer 1) and 16-32=17 (offset + PI), RTC offset (16-30) is set by DI and the offset time is set via 16-31. Switch on DI and RTC will immediately start up. If the source of timer is set to 15 (P1+P2+P3+P4), press “STOP” key at the time period 1 (P1). Normally, RTC will start automatically at the next time period (P2) but it can also start via the setting of 16-30 to 2 (set by DI). Inverter re-runs when switching on DI and RTC will immediately start up. Notes: If press “STOP” key at the time period and inverter can re-run at this time, user can: - Set the selection of RTC offset (16-30) to 2 (set by DI) and set DI to 56 (RTC Offset Enable). - Switch the selection of RTC offset (16-30) to be enabled. Note: RTC Accuracy:
Figure4.4.88 Offset time:Digital InputG03-00to03-05=56 pulse;Offset Time longer high trace;Time gapG16-31 marked from rising edge of input and offset trace to falling edge of offset trace. Horizontal t axes. Source timing illustration only.
RTC offset and accuracy
Temperature / Deviation — PDF page 417
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Temperature | Deviation |
| 2 | +25℃(77℉) | +/-3 sec./ day |
| 3 | -20 / +50 ℃ (-4/ 122℉) | +/-6 sec./ day |
Manual — Auto tuning motor parameter ranges — page 418
Manual reference: physical PDF page 418. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
17-Automatic Tuning Parameters
If auto tune is not executed, or not completed successfully, value of 17-07 will be overwritten by 20-27 automatically If auto tune is done successfully, 20-27 will be overwritten by 17-07.
Auto tuning motor parameter ranges
17-00 / Mode selection of automatic tuning — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-00 | Mode selection of automatic tuning |
| 2 | Range | 0: Rotational auto-tuning 1: Static auto-tuning 2: Stator resistance measurement 3: Reserved 4: Loop tuning 5: Rotational Auto-tuning Combination (Item: 4+2+0) 6: Static Auto-tuning Combination (Item: 4+2+1) |
17-01 / Motor rated output power — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-01 | Motor rated output power |
| 2 | Range | 0.00~600.00 kW |
17-02 / Motor rated current — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-02 | Motor rated current |
| 2 | Range | For VF, VF+PG modes, 10%~200% of the inverter rated current For SLV, SV modes, 25%~200% of the inverter rated current. |
17-03 / Motor rated voltage — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-03 | Motor rated voltage |
| 2 | Range | 200V: 50.0~240.0 V 400V: 100.0~480.0 V 575V: 150.0~670.0 V 690V: 180.0~804.0 V |
17-04 / Motor rated frequency — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-04 | Motor rated frequency |
| 2 | Range | 4.8~599.0 Hz |
17-05 / Motor rated speed — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-05 | Motor rated speed |
| 2 | Range | 0~24000 rpm |
17-06 / Pole number of motor — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-06 | Pole number of motor |
| 2 | Range | 2~16 pole |
17-07 / Number of PG pulse — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-07 | Number of PG pulse |
| 2 | Range | 0~60000 PPR |
17-08 / Motor no-load voltage — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-08 | Motor no-load voltage |
| 2 | Range | 200V: 50~240 V 400V: 100~480 V 575V: 420~600 V 690V: 504~720 V |
17-09 / Motor excitation current — PDF page 418
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-09 | Motor excitation current |
| 2 | Range | 15~70% motor rated current |
Manual — Auto tuning modes and motor data — page 419
Manual reference: physical PDF page 419. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Notes: - Values are for 200V class, double the values for 400V class. - In HD mode (00-27=0) the range is 0.0 to 400.0 Hz, 0.0 to 120.0Hz in for ND mode (00-27=1) and 0.0 to 599.0Hz is high frequency mode. Auto-tuning Based on the motor nameplate set the motor rated output power (17-01), motor output rated current (17-02), motor rated voltage (17-03), motor rated frequency (17-04), motor rated speed (17-05) and number of motor poles (17-06) to perform an auto-tune. Automatic tuning mode selection (17-00) Rotational auto-tuning (17-00=0) provide higher quality for motors. After executing Rotational auto-tuning (17-00), Excitation current of motor 1 (02-09)、Core saturation coefficient 1 of motor 1(02-10)、Core saturation coefficient 2 of motor 1 and Core saturation coefficient 3 of motor 1 (02-12) will renew the value. Static auto-tuning (17-00=1) won’t rotate the motor while auto-tuning. After executing Static auto-tuning (17-00=1), Proportion of motor leakage inductance (02-33) and Motor slip (02-34) will renew the value. Stator resistance measurement (17-00=2) provide for long motor leads After executing Stator resistance measurement (17-00=2), Resistance between wires of motor 1(02-15) will renew the value. Loop tuning (17-00=4) provide great response of current circuit, it can improve frequency bandwidth of current and torque. Rotation Auto-tuning Combination (17-00=5) is the auto-tuning for three in one, including Loop tuning (17-00=4)、 Stator resistance measurement (17-00=2) and Rotational auto-tuning (17-00=0). Static Auto-tune Combination (17-00=6) is the auto-tuning for three in one, including Loop tuning (17-00=4)、 Stator resistance measurement (17-00=2) and Static auto-tuning (17-00=1) Motor rated output power (17-01) Set by inverter capacity (13-00) Motor rated current (17-02) Set by inverter capacity (13-00) Set the range to 10 %~120 % of the inverter rated current.
Auto tuning modes and motor data
17-10 / Automatic tuning start — PDF page 419
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-10 | Automatic tuning start |
| 2 | Range | 0: Disable 1: Enable |
17-11 / Error history of automatic tuning — PDF page 419
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-11 | Error history of automatic tuning |
| 2 | Range | 0: No error 1: Motor data error 2: Stator resistance tuning error 3: Leakage induction tuning error 4: Rotor resistance tuning error 5: Mutual induction tuning error 6: Encoder error 7: DT Error 8: Motor’s acceleration error 9: Warning |
Manual — Auto tuning voltage frequency and encoder examples — page 420
Manual reference: physical PDF page 420. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Motor rated voltage (17-03) Motor rated frequency (17-04) Motor rated speed (17-05) When tuning a special motor (e.g. constant power motor, high-speed spindle motor), with a motor rated voltage or rated motor frequency that is lower than a standard AC motor, it is necessary to confirm the motor nameplate information or the motor test report. Prevent the inverter output voltage from saturation when the motor rated voltage is higher than the inverter input voltage (see Example 1). Example 1: Motor rated voltage (440V/60Hz) is higher than the inverter input voltage (380V/50 Hz).
Step 1: Set auto-tuning (17-00), and set motor rated output power (17-01) and the motor rated current (17-02) by label of the motor. Step 2: Set the value of motor rated voltage (17-03) =440V by label of the motor. Step 3: Set the value of motor rated frequency (17-04) =60Hz Step 4: Set the value of motor rated speed (17-05) 、pole number of motor (17-06) and PG pulse number (17-07). Beware that PG pulse number (17-07) only used in SV and V/F+PG mode. Step 5: Set the value of motor no-load voltage (17-08) =360V, the set value for torque control is 20V lower than input voltage. Step6: Execute auto-tuning. Set auto-tuning (17-10=1) and enter to standby screen. Enter RUN command to start auto-tuning. The value of selection of PG rotation direction (20-28) adjusts automatically with PG card when auto-tuning. The value of motor rated frequency (17-04) adjusts automatically to the same as the value of base frequency of motor 1.If the value of maximum output frequency of motor 1(01-02) is different form base frequency of motor 1 (01-12), the system will adjusts the value of maximum output frequency of motor 1(01-02) the same as base frequency of motor 1 (01-12) automatically. When the inverter input voltage (or frequency) is higher than the motor rated voltage (or frequency), set the motor rated voltage (17-03) and the motor rated frequency (17-04) to the rated frequency on the motor nameplate. Example 2: The inverter input voltage and frequency (460V/50Hz) are higher than the motor rated voltage and frequency (380V/33Hz), set 17-03 to 380V (rated motor voltage) and 17-04 to 33Hz (motor rated frequency). ■ Number of poles (17-06) Set the motor pole number with its range is 2, 4, 6 and 8 poles
Figure4.4.104 auto tuning example:Output voltage axis440V nameplate upperguide,17-03auto-tuning voltage lowerguide;output frequency axis17-04auto-tuning frequency lowerpoint and60Hz nameplate higherpoint. Caption inverter power380V50Hz,motor440V60Hz. No interpolated voltage or frequency.
Manual — Auto tuning motor flux and completion qualifiers — page 421
Manual reference: physical PDF page 421. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
■ Number of PG pulse (17-07) Set the pulse number of each cycle. If the control mode is SV mode and the V / F + PG mode, the encoder must be installed on the motor shaft and there is no reduction gear ratio. ■ Motor no-load voltage (17-08) a) Motor no-load voltage is mainly used in SV or SLV mode, set to value 10~50V lower than the input voltage to ensure good torque performance at the motor rated frequency. b) Set to 85 ~ 95% of the motor rated voltage. In general, the no-load voltage can be closer to the motor rated voltage for larger motors, but cannot exceed the motor rated voltage. c) The motor no-load voltage can be set to a value greater than the actual input voltage. In this case, the motor can only operates under relatively low frequency. If the motor operates at the rated frequency an over voltage condition may occur. d) The higher the motor power is, the higher the no-load voltage is. e) A smaller no-load voltage will reduce the no-load current. f) When load is applied the magnetic flux is weakened and the motor current increases. g) A higher no-load voltage results in a higher the no-load current. h) When load is applied the magnetic flux weakens and the motor current increases. Increasing the magnetic flux generates back EMF and results in poor torque control. ■ Motor excitation current (17-09) a) Motor excitation current is used for rotational auto-tune. b) Set motor excitation current to 33% of the motor rated current. Refer to parameter 02-09 for test running. c) Only the static-type or stator resistance measurement auto-tune (17-00=1 or 1700=2) can be set. d) It is required to refer to the monitoring parameter 12-76 for adjusting the motor excitation current (17-09). When the excitation current change, parameter 12-76 is also affected so it should be adjusted to the setting no-load voltage (17-08). ■ Automatic tuning start (17-10) Set parameter 17-10 to 1 and press ENTER the inverter will display “Atrdy” for Auto-tune ready. Next press RUN to start the auto-tune procedure. During auto-tune the keypad will display “Atune “for Auto-tune in progress. When the motor is successfully tuned, the keypad shows "AtEnd". ■ Error history of automatic tuning (17-11) If auto-tuning fails the keypad will display the AtErr" message and the auto-tune cause is shown in parameter 17-11. Refer to section 5 for troubleshooting and possible automatic tuning error causes. Note: The motor tuning error history (17-11) shows the tuning result of the last auto-tune. No error is displayed when auto-tune is aborted or when the last auto-tune was successful. Perform the “Stator resistance measurement” (17-00=2) auto-tune if the inverter/motor leads are longer than 167ft (50m). For the best performance in vector control perform the rotary-type automatic tune (17-00 = 0) first (using short motor leads between the inverter and motor) and a “Stator resistance measurement” (17-00=2) next. If a rotary auto-tune (17-00=0) cannot be performed, manually enter the mutual induction (02-18), excitation current (02-09), core saturation compensation factor 1-3 (02-11 - 02-13). Perform the “Stator resistance measurement” (17-00=2) in V/F control when inverter/motor leads are longer than 167ft (50m).
Manual — Auto tuning leakage slip and method selection — page 422
Manual reference: physical PDF page 422. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Only the stator resistance auto tune (17-00=2) can be set. The static non-rotational type and rotational type auto tune will automatically measure the proportion of motor leakage inductance so this parameter is not active. It is set the value to 4%. Refer to parameter 02-33 for test run to adjust.
Only the stator resistance auto tune (17-00=2) can be set. The static non-rotational type and rotational type auto tune will automatically measure the proportion of motor leakage inductance so this parameter is not active. Refer to parameter 02-34 for counting the setting value.
It can be set (17-14) only if Rotational auto-tuning (17-00=0) or Rotational Auto-tuning Combination (17-00=5). VF type rotational auto-tuning (17-14=0) applies the standard IM motor that won’t shake without loading for V/F mode. This function is highly applicable, Vector type rotational auto-tuning (17-14=1) applies the special IM motor that will shake without loading for V/F mode. This function applies for high speed motor. Vector type rotational auto-tuning (17-14=1) measures no-loading current of motor by inner current vector method. It avoid the problem appears oscillating current easily in V/F mode. If execute VF type rotational auto-tuning (17-14=0) unsuccessfully, try Vector type rotational auto-tuning (17-14=1) again.
Auto tuning leakage slip and method selection
17-12 / Proportion of Motor Leakage Inductance — PDF page 422
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-12 | Proportion of Motor Leakage Inductance |
| 2 | Range | 0.1~15.0 % |
17-13 / Motor Slip Frequency — PDF page 422
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-13 | Motor Slip Frequency |
| 2 | Range | 0.10~20.00 Hz |
17-14 / Rotational Auto-tuning — PDF page 422
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 17-14 | Rotational Auto-tuning |
| 2 | Range | 【0】: VF type rotational auto-tuning 【1】: Vector type rotational auto-tuning |
Manual — Slip compensation ranges and VF adjustment — page 423
Manual reference: physical PDF page 423. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
18-Slip Compensation Parameters
Slip compensation automatically adjusts the output frequency based on the motor load to improve the speed accuracy of the motor mainly in V/F mode. The slip compensation function compensates for the motor slip to match the actual motor speed to the reference frequency. Slip compensation adjustment in V/F mode 18-00: Slip compensation gain at low speed The adjustment of slip compensation gain at low speed follows the below procedure: 1. Set the rated slip and the motor no-load current (02-00). 2. Set the slip compensation (18-00) to1.0 (factory default setting is 0.0 in V / F control mode) 3. For the operation with a load attached, measure the speed and adjust the slip gain (18-00) accordingly (increase in steps of 0.1). - If the motor speed is lower than frequency reference, increase the value of 18-00. - If the motor speed is higher than frequency reference, decrease the value of 18-00. When the output current is greater than the no-load current (02-00), the slip compensation is enabled and the output frequency increases from f1 to f2. Refer to Figure 4.4.100., the slip compensation value is calculated as follows:
Slip compensation ranges and VF adjustment
18-00 / Slip compensation gain at low speed — PDF page 423
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 18-00 | Slip compensation gain at low speed |
| 2 | Range | 0.00~2.50 |
18-01 / Slip compensation gain at high speed — PDF page 423
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 18-01 | Slip compensation gain at high speed |
| 2 | Range | -1.00~1.00 |
18-02 / Slip compensation limit — PDF page 423
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 18-02 | Slip compensation limit |
| 2 | Range | 0~250% |
18-03 / Slip compensation filter — PDF page 423
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 18-03 | Slip compensation filter |
| 2 | Range | 0.0~10.0 Sec |
18-04 / Regenerating slip compensation selection — PDF page 423
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 18-04 | Regenerating slip compensation selection |
| 2 | Range | 0: Disable 1: Enable |
18-05 / FOC delay time — PDF page 423
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 18-05 | FOC delay time |
| 2 | Range | 1~1000 msec |
18-06 / FOC gain — PDF page 423
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 18-06 | FOC gain |
| 2 | Range | 0.00~2.00 |
Manual — Slip compensation formulas limits and regeneration — page 424
Manual reference: physical PDF page 424. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
18-02: Slip compensation limit Sets slip compensation limit in constant torque and the constant power operation (figure 4.4.106). If 18-02 is 0%, the slip compensation limit is disabled.
When the slip compensation gain 18-00 at low speed is adjusted, and the actual motor speed is still lower than the reference frequency, the motor may be limited by the slip compensation limit. Note: Make sure that the slip compensation limit 18-02 does not exceed the maximum allowed system limit. 18-03: Slip compensation filter Set slip compensation filter time in V/F mode 18-04: Regenerating slip compensation selection The selections to enable or disable the slip compensation function during regeneration. To enable slip compensation during regeneration caused by deceleration (SLV mode), set 18-04 to 1 in case speed accuracy is required. When the slip compensation function is used regenerative energy might increase temporarily (18-04= 1) therefore a braking module might be required.
Printed formula:Slip Compensation Value = Motor Rated Slip Frequency × [Output Current12-18 − No-load Current of Motor1(02-00)] / [Rated Current of Motor1(02-01) − No-load Current of Motor1(02-00)]. Preserve printed motor parameter associations.
Printed formula:Motor Rated Slip Frequency(f) = [(Motor No-load Synchronous Speed − Motor Full-load Rated Speed)(N) × Motor Poles(P)] /120. SymbolN retained in printed position.
Figure4.4.105 Slip compensation:Torque versusSpeed;SmallerLoadf1 andLargerLoadf2 curves. No numerical points interpolated.
Figure4.4.106 Slip compensation limit:verticalSlip Compensation Limit;horizontalOutput Frequency. Lowerplateau labelled18-04;upper labelled(01-02/01-12)×18-04;Fbase01-12 andFmax01-02. Printed18-04 labels retained despite surrounding18-02 limit heading.
Manual — SLV slip compensation and high speed gain — page 425
Manual reference: physical PDF page 425. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
SLV mode adjustment 18-00: Slip compensation gain a) Slip compensation can be used to control the full rang speed accuracy under load condition. b) If the speed is lower than 2 Hz and the motor speed decreases, increase the value of 18-00. c) If the speed is lower than 2 Hz and the motor speed increases, reduce the value of 18-00. Slip compensation gain uses a single value for the whole speed range. As a result the slip compensation accuracy at low speed is high but slight inaccuracies might occur at high speeds. Adjust parameter 18-02 together with the compensation value or continue to adjust 18-00 if the speed accuracy at higher speed is not acceptable. Please note adjusting these parameters might impact the accuracy at lower speeds. The impact of 18-00 on the torque and the speed are shown in figure 4.4.107.
18-01: Slip compensation gain at high speed It is not required to adjust the Slip compensation gain at high speed if the motor is loaded. After adjusting parameter 18-00 it is recommended to increase the reference frequency and check the motor speed. In case of a speed error increase the value of 18-01 to adjust the compensation. Increase the motor rated frequency (01-12 base frequency) and increase the value of 18-01 to reduce the speed error. If the speed accuracy becomes worse due to an increase in motor temperature it is recommended to use a combination of 18-00 and 18-01 for adjustment. Compared to 18-00, 18-01 serves as a variable gain for the full speed range. Parameter 18-01 determines the slip compensation at the motor rated speed and is calculated follows:
Figure4.4.107 18-00 effect on torque speed curve:Torque versusSpeed;Decrease18-00 arrow left,Increase18-00 arrow right;solid and dashed characteristic lines. No numeric torque or speed inferred.
Printed formula:Slip Compensation Gain = (Slip Compensation Gain in Low Speed + Slip Compensation Gain in High Speed) × Reference Frequency / Motor Rated Frequency(01-12). Literal formula retained.
Manual — Slip compensation gain figures FOC and SLV2 — page 426
Manual reference: physical PDF page 426. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Figure 4.4.108 18-00/18-01 Slip compensation gain versus frequency reference
Figure 4.4.109 18-01 Effect on torque speed curve 18-05: FOC (Flux Orient Control) delay time In the SLV mode, the slip compensation of the magnetic flux depends on the torque current and excitation current. If the motor load rises above 100% while running at the motor rated frequency, the motor voltage and resistance drops sharply, which may cause the inverter output to saturate and current jitter occur. The magnetic flux slip compensation will independently control the torque current and the excitation current to prevent current jitter. For slow speed or fixed speed operation, 18-05 may be increased. For fast operation adjust 18-06. 18-06: Slip compensation gain If the motor is jittering at the rated frequency under full load, the value of 18-06 may gradually be reduced to zero to reduce current jitter. SLV2 mode adjustment Default value of parameter 18-00 is 0.0. ( when 18-00 = 0.0, slip compensation function is off.) Adjustment of slip compensation gain (18-00) is the following: a) Correctly set the rated slip and no-load current (02-00). b) Set slip compensation gain (18-00). c) Run under load. Measure the speed and adjust slip compensation gain (18-00) with the unit of 0.1. Notes: ─ If the motor speed is lower than the target speed, increase the setting value of low-speed slip compensation gain (18-00). ─ If the motor speed is higher than the target speed, reduce the setting value of low-speed slip compensation gain (18-00).
Figure4.4.108 Slip compensation versusFrequency Reference:sloping line over horizontal dashed line;lower vertical portion18-00,upper addition18-01. No numeric slope inferred.
Figure4.4.109 Torque versusSpeed:two adjustment positions each showDecrease18-01 left andIncrease18-01 right;solid/dashed curves. No numeric operating points inferred.
Manual — Wobble parameter ranges and waveform — page 427
Manual reference: physical PDF page 427. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
19–Wobble Frequency Parameters
Wobble operation can be used in V/F and V/F+PG control mode to modulate the output frequency around the reference frequency for use in winding application to create an evenly wound roll. Refer to the figure 4.4.110 for the wobble operation and the related parameter settings.
Figure 4.4.110 Wobble operation and the related parameter setting In wobble operation, one of multifunction digital inputs (03-00 to 03-07) is set to 37 (wobble operation) and the run command is active. When the wobble operation is ready, the inverter output frequency reaches the center frequency (19-00). The acceleration time to the center frequency is the original pre-set acceleration time (Tacc 1 to Tacc 4). When the wobble operation is closed or the run command is removed, the deceleration time used is the original pre-set deceleration time (Tdec 1 to Tdec4).
Figure4.4.110 Wobble operation:Output frequency versus t,Center Frequency19-00;amplitude19-01,Jump frequency19-02,Jump time19-03,Wobble time19-04,upper offset19-06,lower offset19-07;tup,tdown;Wobble Ratio=tup/tdown. Source waveform labels only.
Wobble parameter ranges and waveform
19-00 / Center frequency of wobble frequency — PDF page 427
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 19-00 | Center frequency of wobble frequency |
| 2 | Range | 5.00~100.00% |
19-01 / Amplitude of wobble frequency — PDF page 427
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 19-01 | Amplitude of wobble frequency |
| 2 | Range | 0.1~20.0% |
19-03 / Jump time of wobble frequency — PDF page 427
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 19-03 | Jump time of wobble frequency |
| 2 | Range | 0~50 msec |
19-04 / Wobble frequency cycle time — PDF page 427
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 19-04 | Wobble frequency cycle time |
| 2 | Range | 0.0~1000.0 Sec |
19-05 / Wobble frequency ratio — PDF page 427
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 19-05 | Wobble frequency ratio |
| 2 | Range | 0.1~10.0 msec |
19-06 / Upper offset amplitude of wobble frequency — PDF page 427
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 19-06 | Upper offset amplitude of wobble frequency |
| 2 | Range | 0.0~20.0 % |
19-07 / Lower offset amplitude of wobble frequency — PDF page 427
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 19-07 | Lower offset amplitude of wobble frequency |
| 2 | Range | 0.0~20.0 % |
Manual — Wobble ON OFF timing — page 428
Manual reference: physical PDF page 428. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
In wobble operation, the inverter operates uses the in the wobble time (19-04, tup + tdown) and wobble frequency (19-05, tup / tdown). Set multi-function digital output terminals (R1A-R1C, R2A-R2C) to output wobble operation (in acceleration) by setting from 03-11 to 03-12 to 20 or 21. Refer to the figure 4.4.111 for the wobble ON / OFF control.
Figure 4.4.111 ON/OFF control of wobble
Figure4.4.111 ON/OFF wobble:Run Command,Traverse Run(03-00–07=37),Traverse operation interval;Output frequency19-00 with19-01,19-02,19-03,19-04,tup,tdown,taccel,tdecel. Traverse Up(03-11to03-12=28);During Traverse(03-11to03-12=29);all t axes. Diagram output28/29 retained independently from prose20/21.
Manual — Wobble upper lower deviation and limits — page 429
Manual reference: physical PDF page 429. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
In wobble operation, the center frequency can be controlled by one of multi-function digital inputs. The wobble upper and lower deviation command (03-00 to 07 = 38) and the wobble lower deviation command (03-00 to 07 = 39) cannot be active at the same time, this will result in the inverter operating at the original center frequency (19 - 00). Refer to Figure 4.4.112.
Figure 4.4.112 Upper/Lower offset operation The wobble operation can be used during acceleration and deceleration when the stall prevention function is idle. Select the appropriate inverter size to match the system requirement. The wobble operation frequency range is determined by the upper limit and lower limit of the inverter frequency. If (center frequency + amplitude) is greater than the upper frequency limit, the output frequency is limited to the upper frequency limit; if (center frequency - Amplitude) is less than the lower frequency limit the output frequency is limited to the lower frequency limit.
Figure4.4.112 Upper/Lower offset:Output frequency19-00 versus t,amplitudes19-01,upper19-06,lower19-07;Upper Deviation Command(03-00to03-07=38),Lower Deviation Command(03-00to03-07=39) pulse traces. Source diagram labels only.
Manual — ASR speed control parameter ranges — page 430
Manual reference: physical PDF page 430. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
20-Speed Control Parameters
ASR speed control parameter ranges
20-00 / ASR gain 1 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-00 | ASR gain 1 |
| 2 | Range | 0.00~250.00 |
20-01 / ASR integral time 1 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-01 | ASR integral time 1 |
| 2 | Range | 0.001~10.000 Sec |
20-02 / ASR gain 2 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-02 | ASR gain 2 |
| 2 | Range | 0.00~250.00 |
20-03 / ASR integral time 2 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-03 | ASR integral time 2 |
| 2 | Range | 0.001~10.000 Sec |
20-04 / ASR integral time limit — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-04 | ASR integral time limit |
| 2 | Range | 0~300 % |
20-05 / ASR positive limit — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-05 | ASR positive limit |
| 2 | Range | 0.1 ~ 10 % |
20-06 / ASR negative limit — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-06 | ASR negative limit |
| 2 | Range | 0.1 ~ 10 % |
20-07 / Selection of acceleration and deceleration of P/PI — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-07 | Selection of acceleration and deceleration of P/PI |
| 2 | Range | 0: PI speed control will be enabled only in constant speed. For the speed acceleration and deceleration, only use P control. 1: Speed control is enabled either in acceleration or deceleration. |
20-08 / ASR delay time — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-08 | ASR delay time |
| 2 | Range | 0.000~0.500 Sec |
20-09 / Speed Observer Proportional(P) Gain1 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-09 | Speed Observer Proportional(P) Gain1 |
| 2 | Range | 0.00~2.55 |
20-10 / Speed Observer Integral(I) Time 1 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-10 | Speed Observer Integral(I) Time 1 |
| 2 | Range | 0.01~10.00 Sec |
20-11 / Speed Observer Proportional(P) Gain2 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-11 | Speed Observer Proportional(P) Gain2 |
| 2 | Range | 0.00~2.55 |
20-12 / Speed Observer Integral(I) Time 2 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-12 | Speed Observer Integral(I) Time 2 |
| 2 | Range | 0.01~10.00 Sec |
20-13 / Low-pass filter Time constant of speed feedback 1 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-13 | Low-pass filter Time constant of speed feedback 1 |
| 2 | Range | 1~1000 msec |
20-14 / Low-pass filter Time constant of speed feedback 2 — PDF page 430
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-14 | Low-pass filter Time constant of speed feedback 2 |
| 2 | Range | 1~1000 msec |
Manual — ASR gain ranges and VF PG structure — page 431
Manual reference: physical PDF page 431. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter 20-33 is used when 20-07 is set to 0 and frequency command source is set to analog input mode. Analog input signal, owing to the noise, will cause the system to determine the operation does not reach the constant speed so the problem may occur. Thus, adjust parameter 20-33 to avoid this situation occurring.. The following figure an overview of the automatic speed regulator (ASR) block. V/F + PG control mode: The ASR function adjusts the output frequency to control the motor speed to minimize the difference between the frequency reference and actual motor speed.
Figure 4.4.113 ASR block diagram (V/F + PG) If one of the multi-function input (03-00 to 03-07) is set to 42 (PG is disabled), the input can be used to enable or disable the speed control loop system (ASR).
Figure4.4.113 ASR block diagram(V/F+PG):Frequency Reference Fref,SFS,Speed Feedback,P20-00/20-02,I20-01/20-03,ASR Limit20-05/20-06,PG valid,PG invalid03-00to03-07=42;20-07=1duringaccel/decel;20-07=0orSpeed control integral reset03-00to03-07=43;Δf,Fout Output Frequency. Sum signs and drawn switches remain in source image;no inferred control topology.
ASR gain ranges and VF PG structure
20-15 / ASR gain change frequency 1 — PDF page 431
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-15 | ASR gain change frequency 1 |
| 2 | Range | 0.0~599.0 Hz |
20-16 / ASR gain change frequency 2 — PDF page 431
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-16 | ASR gain change frequency 2 |
| 2 | Range | 0.0~599.0 Hz |
20-17 / Torque compensation gain at low speed — PDF page 431
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-17 | Torque compensation gain at low speed |
| 2 | Range | 0.00~2.50 |
20-18 / Torque compensation gain at high speed — PDF page 431
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-18 | Torque compensation gain at high speed |
| 2 | Range | -10~10% |
20-33 / Detection Level at Constant Speed — PDF page 431
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-33 | Detection Level at Constant Speed |
| 2 | Range | 0.1~5.0 % |
Manual — SLV ASR structure — page 432
Manual reference: physical PDF page 432. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
SLV control mode: The ASR function adjusts the output frequency to control the motor speed to minimize the difference between the frequency reference and actual motor speed. The ASR controller in SLV mode uses a speed estimator to estimate the motor speed. In order to reduce speed feedback signal interference, a low-pass filter and speed feedback compensator can be enabled. The ASR integrator output can be disabled or limited. The ASR output is passed through a low-pass filter.
Figure 4.4.114 ASR block diagram (SLV mode)
Figure4.4.114 ASR block diagramSLV:Frequency Reference,P20-00/20-02,I20-01/20-03,I Limit,Primary delay time20-08,Torque Limit,Torque Reference;20-07=1duringaccel/decel;20-07=0;Speed Control Integral Reset03-00to03-07=43. Feedback labelsSpeed Observer Feedback,LP Filter20-13/20-14,Speed Feedback Compensator20-17/20-18,Speed Observer,Motor Voltage Motor Current,Observer Error,P20-09/20-11,I20-10/20-12. Source label associations only,no inferred control implementation.
Manual — SV PMSV structure and VF PG gain tuning — page 433
Manual reference: physical PDF page 433. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
SV control mode and PMSV mode: The ASR function adjusts the output frequency to control the motor speed to minimize the difference between the frequency reference and actual motor speed. The ASR controller in SLV mode uses a speed estimator to estimate the motor speed. In order to reduce speed feedback signal interference, a low-pass filter and speed feedback compensator can be enabled. The ASR integrator output can be disabled or limited. The ASR output is passed through a low-pass filter.
Figure 4.4.115 Speed control block diagram (SV & PMSV mode) ASR setting in V/F +PG control mode In V/F+PG mode, set the proportional (P) gain and integral (I) time at the minimum output frequency (20-02 and 20-03) and maximum output frequency (20-00 and 20-01). Refer to the figure 4.4.116. Figure 4.4.116 ASR gain setting (V/F+PG) Tuning the speed control ASR gain: a) ASR gain tuning at minimum output frequency 1. Operate the motor at the lowest output frequency. 2. Increase the ASR proportional gain 2 (20-02) as much as possible without causing instability. 3. Decrease the ASR integral time 2(20-03) as much as possible without causing instability. 4. Check that the output current is less than 50% of the inverter rated current. If the output current is more than 50% of the inverter rated current, decrease 20-02 and increase 20-03.
Figure4.4.115 SV&PMSV speed control block:Frequency Reference,Speed Feedback;P20-00/20-02,I20-01/20-03,I Limit20-04;upperLP Filter20-35,P20-34;Primary delay time20-08;Torque Compensation fromAI;Torque Limit21-05to21-08,Torque Reference;20-07=1duringaccel/decel,20-07=0;Speed Control Integral reset03-00to03-07=43. Source labels only.
Figure4.4.116 ASR gain settingVF+PG:verticalP,I;horizontalOutput Frequency0%to100%(Fmax,01-02);lowerP=20-02,I=20-03;upperP=20-00,I=20-01;line rises between endpoints. No numeric gains inferred.
Manual — ASR maximum speed and integral tuning — page 434
Manual reference: physical PDF page 434. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
b) ASR gain tuning at maximum output frequency 1. Operate the motor at the highest output frequency (Fmax). 2. Increase the ASR proportional gain 1 (20-00) as much as possible without causing instability. 3. Decrease the ASR integral time 1(20-01) as much as possible without causing instability. c) The gain tuning of acceleration / deceleration integral control (20-07) 1. To enable during acceleration / deceleration operation set 20-07 = 1 (enabled), the integral control is enabled. 2. Integral control enables the motor speed to reach its target speed as soon as possible, but it may result in over or undershoot, as shown in Figure 4.4.114 & 4.4.115. 3. When one of multi-function digital inputs (03-00 to 03-07) is set to 43 (speed control integral reset), the input can be used to switch between P control and PI control of the speed control loop system (ASR). When the multi-function digital input is on, only P control is active and the integral is reset. a. If the speed overshoot occurs, reduce 20-00 system (ASR proportional gain) and increase the 20-01 system (ASR integral time 1). b. If the desired speed is not reached, reduce 20-02 system (ASR proportional gain 2) and increase 20-03 (ASR integral time 2). c. If you cannot eliminate the speed over or undershoot using the gain tuning described above, decrease the ASR + / - limit (20-05 / 20-06), to decrease the reference frequency compensation (∆f) limit. Since 20-05/20-06 cannot be changed during running, it is necessary to stop the inverter first and then decrease the ASR + / - limit. 4. See figure 4.4.117, observe the motor speed waveform and tune the gain at the same time.
Figure 4.4.117 Analog output setting d) ASR+/-limit (20-05, 20-06) ASR +/-limit is ASR frequency compensation limit and is set as a percentage of the maximum frequency output 01-02. Note: If the frequency limit is set too low, the actual motor speed may not reach the target speed.
Figure4.4.117 Analog output setting:Related Parameters;AO1 04-11=6Motor Speed,04-12Gain,04-13Bias;AO2 04-16=6Motor Speed,04-17Gain,04-18Bias. Terminal labels only,not verified wiring.
Manual — ASR low high speed transitions — page 435
Manual reference: physical PDF page 435. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
ASR setting (SV/SLV/PMSV control mode) In SLV mode the ASR gain is divided into a high-speed and low-speed section. The speed controller has a high-speed gain 20-00/20-01 and a low-speed gain 20-02/20-03 that can be set independently. a) The high/low switch frequency can be set with parameter 20-15 and 20-16. Similar to the ASR gain, the speed estimator has a high-speed gain 20-09/20-10 and a low-speed gain 20-11/20-12. b) The speed estimator has a low-pass filter to reduce the speed feedback interference, parameter 20-13 and 20-14 are active at high speed as well as low speed. The switch between the high-speed and the low-speed is set by parameter 20-15 and 20-16. c) 20-17 sets the low-speed compensation gain of the speed feedback. d) 20-18 sets the high-speed compensation gain of the speed feedback. e) When the frequency reference is rises above the value set in 20-16, the ASR gain used is set by parameters 20-00 and 20-01. f) When the frequency reference falls below the value set in 20-15, the ASR gain used is set by parameters 20-02 and 20-03. g) Gain time constant is adjusted linearly when the speed command falls within the range of 20-15 to 20-16, for a smooth operation.
Figure 4.4.118 ASR gain setting (SLV mode) SV and PMSV gain setting In SV and PMSV mode the ASR gain is divided into a high-speed and low-speed section. The speed controller has a high-speed gain 20-00/20-01 and a low-speed gain 20-02/20-03 that can be set independently. Tune the speed control gain During ASR gain tuning, the multi-function analog output (AO1 and AO2 terminal) can be used to monitor the output frequency and motor speed (as shown in figure 4.4.113). Use parameters 20-00 ~ 20-03 for full speed range gain tuning in SV and PMSV mode. a) Complete the parameter tuning in normal operation. b) Increase ASR proportional gain 1 (20-00), ASR proportional gain 2 (20-02), carefully monitor system stability. Use parameter 20-00 and 20-02 to adjust the speed response for each cycle. Tuning the settings of 20-00, 20-02 can increase system response, but may cause system instability. See figure 4.4.119.
Figure4.4.118 leftSLV gain graph:P,I versusFrequency Reference;lowerP20-02/I20-03,upperP20-00/I20-01;linear ramp between20-15and20-16.
Figure4.4.118 rightSLV time constant graph:upper20-14at20-15;descending ramp tolower20-13at20-16. Horizontal axis itself has20-15and20-16labels but no quantity title;no unprinted numeric values added.
Manual — ASR response curves and SLV tuning — page 436
Manual reference: physical PDF page 436. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Figure 4.4.119 System response of ASR proportion gain a) Reduce ASR integral time 1(20-01), ASR integral time 2 (20-02) and carefully monitor system stability. 1. A long integral time will result in poor system response. 2. If the integral time setting is too short, the system may become unstable Refer to the following figure. While tuning ASR P and I gain the system may overshoot and an over voltage condition can occur. A braking unit (braking resistor) can be used to avoid an over voltage condition.
Figure 4.4.120 The response of ASR integral time
SLV mode gain tuning (20-00~20-03, 20-09~20-18) and SLV2 mode gain tuning (20-15, 20-16) Tune the low-speed ASR P and I gain 20-02 ~ 20-03, make sure the reference frequency is below the value of parameter 20-15. P gain and integral time tuning is the same as for parameter 20-00 and 20-01 in SV mode. Tune the high-speed ASR PI gain 20-00~20-01, make sure the reference frequency is above parameter 20-16 value. P gain and integral time tuning is the same as for parameter 20-00 and 20-01 under SV mode. Both low-speed ASR gain and the high-speed gain can be set to the same values and only require to be adjusted in case of system instability. In case tuning of the ASR P and I gain 20-00~20-03 does not improve the system response, reduce the low-pass filter time constant 20-13~20-14 to increase the bandwidth of the feedback system and re-tune the ASR gain.
Tune low-speed low-pass filter time constant 20-14, make sure the reference frequency is below parameter 20-15 value
Tune high-speed low-pass filter time constant 20-13 at frequency reference, make sure the reference frequency is above parameter 20-16 value.
Increasing the low-pass filter time constant can limit the bandwidth of the speed feedback system and may
Figure4.4.119 ASR proportional gain response:Motor Speed versus t. Curve1=20-00setting too high(oscillation occurs);Curve2=20-00setting too low(slow response). Ascending,flat,descending command with overshoot/lag traces;no numeric timing inferred.
Figure4.4.120 integral time response:Motor Speed versus t;Curve1=20-01setting too short(oscillation occurs);Curve2=20-01setting too long(slow response). No numeric response data inferred.
Manual — ASR filter and observer qualifications — page 437
Manual reference: physical PDF page 437. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
reduce the system response. Increasing the low-pass time reduces the speed feedback signal interference but may results in sluggish system response when the load suddenly changes. Adjust the low-pass filter time if the load stays fairly constant during normal operation. The low bandwidth of the speed feedback must be supported by the low gain of ASR to ensure the stable operation.
Decreasing the low-pass filter time constant may increase the bandwidth of the speed feedback and the system response. Decreasing the low-pass time may increase the speed feedback interference resulting in system instability when the load suddenly changes. Decrease the low-pass filter time is a quick system response is required for rapidly changing loads. The high bandwidth of the speed feedback allows for a relative high ASR gain.
In case tuning 20-00 ~ 20-03 and the low-pass filter time constant 20-13 do not improve the system response time, tuning the PI gain 20-09 ~ 20-12 of the speed estimator may be required.
Setting a high gain for the speed estimator (high proportion (P) gain and small integral (I) time) increases the bandwidth of the speed feedback, but may cause speed feedback interference resulting in system instability.
Setting a low gain for the speed estimator (small proportion (P) gain and high integral (I) time) decreases the bandwidth of the speed feedback, may improve speed feedback interference resulting in a more stable system.
The default values for the ASR can be used in most applications, no adjustment is required. Adjusting the low-pass filter time and speed estimator gains requires a good understanding of the overall system. If a high-speed system response in combination with stable operation is required consider using SLV or SV control mode.
Parameter 20-15 sets the gain switch frequency at low-speed and parameter 20-16 sets the gain switch frequency at high-speed.
Operating at a speed below 20-15 will result in a larger excitation current for low-speed operation accuracy. When the frequency reference rises above 20-16, the inverter will output the rated excitation current at the no-load voltage (02-19).
For general purpose applications parameter 20-15 should be set to a value of 5 ~ 50% of the motor base frequency.
If this value is too high, the inverter output may saturate. Parameter 20-16 should be set to a value of 4Hz or more above the value of 20-08.
When experiencing speed jitter at high speed and stable operation during mid-range speed while operating a heavy load (>100%), it is recommended to reduce the no-load voltage (02-19) or tune the FOC parameters (18-05 ~ 18-06).
Parameter 20-17 and 20-18 are for compensating speed feedback at low speed and high speed.
Opening text continues436last bullet about increased low-pass-filter time constant and reduced bandwidth; preserve conditional continuation.
Manual — Torque speed compensation curves — page 438
Manual reference: physical PDF page 438. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Use parameter 20-17 to adjust the torque compensation gain for the low speed range. By tuning 20-17an offset is added to the torque-speed curve. Increase 20-17 when the no-load speed is lower than the frequency reference. Decrease 20-17 when the no-load speed is higher than the frequency reference. The effect on the torque-speed curve from 20-17 is shown as the following figure:
Figure 4.4.121 Effect on the torque-speed curve from 20-17
Use parameter 20-18 to adjust the torque compensation gain for middle to high speed range. For most general purpose applications it is not necessary to adjust the 20-18. By tuning 20-18an offset is added to the torque-speed curve. Increase 20-18 when the no-load speed is lower than the frequency reference. Decrease 20-18 when the no-load speed is higher than the frequency reference. The effect on the torque-speed curve from 20-18 is shown as the following figure 4.4.122.
Figure 4.4.122 Effect on the torque-speed curve from 20-17
①. ASR main delay time (20-08). a) Does not required to be adjusted for general purpose applications b) When the set value of 20-08 is set high, the speed response will and therefore system response will decrease improving system stability. ②. ASR integral limit (20-04) a) Setting a small value may prevent system response when the load suddenly changes.
Figure4.4.121 Torque versusSpeed:Decrease20-17left arrow,Increase20-17right arrow;vertical solid and dashed characteristic lines. No numeric torque values.
Figure4.4.122 Torque versusSpeed:two adjustment regions each labelledDecrease20-18left andIncrease20-18right. Caption says effectfrom20-17;retain caption discrepancy independently.
Manual — Overspeed deviation and encoder settings — page 439
Manual reference: physical PDF page 439. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
■ PG card is required (JN5-PG-O/JN5-PG-L/JN5-PG-PM) PG pulse divider ratio can be set parameter 20-29.
Overspeed deviation and encoder settings
20-19 / Overspeed (OS) selection — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-19 | Overspeed (OS) selection |
| 2 | Range | 0: Deceleration to stop 1: Coast to stop 2: Continue to operate |
20-20 / Overspeed (OS) detection level — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-20 | Overspeed (OS) detection level |
| 2 | Range | 0~120 % |
20-21 / Overspeed (OS) detection time — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-21 | Overspeed (OS) detection time |
| 2 | Range | 0.0~2.0 sec |
20-22 / Speed deviation (DEV) selection — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-22 | Speed deviation (DEV) selection |
| 2 | Range | 0: Deceleration to stop 1: Coast to stop 2: Continue to operate |
20-23 / Speed deviation (DEV) detection level — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-23 | Speed deviation (DEV) detection level |
| 2 | Range | 0~50 % |
20-24 / Speed deviation (DEV) detection time — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-24 | Speed deviation (DEV) detection time |
| 2 | Range | 0.0~10.0 sec |
20-25 / Selection of PG Open — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-25 | Selection of PG Open |
| 2 | Range | 0: Deceleration to stop 1: Coast to stop 2: Continue to operate |
20-26 / Detection time of PG Open — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-26 | Detection time of PG Open |
| 2 | Range | 0.0~10.0 Sec |
20-27 / PG pulse number — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-27 | PG pulse number |
| 2 | Range | 0~60000 ppr |
20-28 / Selection of PG rotation direction — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-28 | Selection of PG rotation direction |
| 2 | Range | 0: Forward as counter -clockwise rotation 1: Forward as clockwise rotation |
20-29 / PG pulse dividing ratio — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-29 | PG pulse dividing ratio |
| 2 | Range | 001~132 |
20-30 / PG gear ratio 1 — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-30 | PG gear ratio 1 |
| 2 | Range | 1~1000 |
20-31 / PG gear ratio 2 — PDF page 439
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-31 | PG gear ratio 2 |
| 2 | Range | 1~1000 |
Manual — PG failure detection and pulse settings — page 440
Manual reference: physical PDF page 440. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
■ PG feedback setting (1) Over speed operation setting (20-19 to 20-21) a) When the motor speed exceeds the tuning limit, an error is detected. If the motor speed feedback exceeds the value of 20-20 (overspeed detection level) for the time specified in 20-12 (over speed detection delay time) an over-speed (OS) condition is detected. b) Overspeed detection selection (20-19) specifies the stop method for the inverter in case of an overspeed condition. (2) PG Speed deviation setting (20-22 to 20-24) a) When the speed deviation (difference between the set speed and the actual motor speed) exceeds the tuning limit, an error is detected. b) If the speed deviation is greater than the value of 20-23 (deviation detection level) for the time specified in 20-24 (deviation detection delay time), a speed deviation (DEV) is detected. c) Speed deviation is based on the reference frequency ± speed deviation width, parameter 20-23. d) Speed deviation detection selection (20-22) specifies the stop method for the inverter in case of a speed deviation condition. (3) PG detection setting (20-25 to 20-26) a) When the inverter no longer received pulses fro, the PG feedback for the time specified in 20-26 a PG open condition is detected. b) PG open detection selection (20-25) specifies the stop method for the inverter in case of a PG open condition. Refer to figure 4.4.123 for the PG fault detection block diagram.
Figure 4.4.123 Logic diagram PG feedback failure detection (4) Set PG pulse (20-27) a) Set PG of pulse number of the encoder for phase A or phase B for each cycle b) If a gearbox is used between the motor and PG the gear ratio can be set with parameter 20-30 and 20-31. (5) PG rotation direction (20-28) Parameter is used to set the motor direction and PG direction. Make sure phase A or phase B is leading for motor forward direction operation.
Figure4.4.123 PG feedback failure detection:inputsFout(afterSFS),Speedfeedback,Duringmomentarypowerloss,DuringB.B.;ABSOLUTE,20-23;DEVDetTime20-24→DEVfault;comparison(01-08)Fminand0%SPEED;PGODetTime20-26→PGOfault;20%SPEEDand20-20comparisons;OSDetTime20-21→OSfault. Logic gate/sum symbols retained in source image;not reconstructed as valid circuit.
Manual — PG rotation and pulse dividing ratio — page 441
Manual reference: physical PDF page 441. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
20-28=0: Forward operation, phase A is leading (phase B is leading for reversal operation). 20-28=1: Forward operation, phase B is leading (phase A is leading for reversal operation).
Figure 4.4.124 PG and motor rotation direction Motor direction is determined as below: Forward: The motor direction is counter-clockwise when inverter runs in forward direction (see figure 4.4.125.)
Figure 4.4.125 Motor operation direction Forward: The motor direction is clockwise when inverter runs in forward direction (see figure 4.4.126.) Refer to the below figure 4.4.126 for PG feedback pulses.
Figure 4.4.126 PG operation direction (6) PG pulse dividing ratio (20-29) Set the pulse divider ratio between the PG input and PG output. The left most digit (3rd) represent the numerator and the last to represent the denominator. Ratio is calculated as follows: 20-29= □ □□, = n kk Range n: 0 to 1 Range k: 1 to 32 Ratio = (1+n)/k
Figure4.4.124 PG andmotor rotation:Inverter,ForwardCommand,Motor,CCW(Forward).20-28=0phaseA leadsphaseB;20-28=1phaseB leadsphaseA. Visible square-wave sequence only,no unstated phase angle or wiring.
Figure4.4.125 Motor operation direction:Inverter,ForwardCommand,Motor,CCW(Forward). Source illustration only.
Figure4.4.126 PG operation direction:PG withCW arrow;phaseA andphaseB waveforms,phaseA risingedge beforephaseB. No inferred motor/encoder installation orientation.
Manual — PG gear formula resolver and derating — page 442
Manual reference: physical PDF page 442. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Examples: 20-29=001 → n=0, k=1, proportion = (1+0)/1=1 20-29=032 → n=0, k=32, proportion = (1+0)/32=1/32 20-29=132 → n=1, k=32, proportion = (1+1)/32=1/16 (7) Gear ratio of PG and motor (20-30, 20-31). Gear ratio specifies when a gearbox is connected between the PG and the motor a) Set the gear ratio of the load side parameter 20-31. b) Set the gear ratio of the motor side parameter 20-30. Motor speed is calculated as follows:
Note: The response speed in V / F + PG mode is less than that of SV mode.
Select encoder type. Power to the inverter needs to be cycled for changes to take effect. Note: Resolver card doesn’t support position mode.
This gain effect is the same as ASR proportional gain (20-00, 20-02). And if this parameter is coupled with low-pass filter time constant (20-35), it can avoid oscillation. It is suggested that the setting value of parameter 20-34 is 30~50.
This time constant is used for suppressing the oscillation produced by 20-34. But too large compensation time constant will cause slower output response and then is unfavorable for turned compensation. It is suggested that the setting value of parameter 20-35 is 50~100ms.. Refer to Fig.4.4.113 and Fig. 4.4.114. Torque compensation function of derating can reduce the characteristics of ASR turning around under shock load.
In manual pulse generator (MPG) mode, the speed calculated by the MPG Input is multiplied by the parameter (20-43) speed multiplier, and is limited by the parameter (20-44) speed command, to perform speed command upper limit.
MotorSpeed(RPM) = [No.ofinputpulsesfromPG×60 / PGpulses(20-27)] × [No.ofPGgearteeth2(20-31) / No.ofPGgearteeth1(20-30)]. Printed formula only;no calculated rating or validated encoder ratio.
PG gear formula resolver and derating
20-32 / Special encoder selection — PDF page 442
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-32 | Special encoder selection |
| 2 | Range | 0: None 1: Resolver |
20-34 / Compensation Gain of Derating — PDF page 442
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-34 | Compensation Gain of Derating |
| 2 | Range | 0~25600 |
20-35 / Compensation Time of Derating — PDF page 442
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20-35 | Compensation Time of Derating |
| 2 | Range | 0~30000 mSec |
20- 43 / MPG speed magnification calculation — PDF page 442
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 20- 43 | MPG speed magnification calculation |
| 2 | Range | 1 ~ 500 |
| 3 | 20- 44 | MPG speed command limit |
| 4 | Range | 0.1 ~ 30.0 Hz |
Manual — Torque control selection and architecture — page 443
Manual reference: physical PDF page 443. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
21-Torque And Position Control Parameters
21-00: Torque control selection Select between speed control and torque control in SV mode. 21-00= 0: Speed control (20-00, 20-09), ASR setting 21-00= 1: Torque control (21-01 to 4), torque control setting A multi-function digital input terminal (03-00 to 03-08) set to 44 (speed / torque control switching) can be used to switch between speed and torque mode externally. When the input terminal is active torque control is selected otherwise speed control is selected. Refer to figure 4.4.114 for the speed control architecture and figure 4.4.127 for torque control architecture.
Figure 4.4.127 Block figure of the torque control
Figure4.4.127 Torque control block:TorqueReference(fromAI2),Tref;SpeedLimit(fromAI1)21-02=0;SpeedLimit(setby21-03)21-02=1;SpeedLimit(fromcommunicationaddress2502H)21-02=2;NLmt,SpeedFeedback,NFB;SpeedController&SpeedLimiter;SpeedLimitBias21-04;TorqueLimit21-05to21-08 withquadrantsII/I/III/IV,torque/rpmaxes;InternalTorqueReference;InputMethods andControlBlock. Sourcelabels,no inferred implementation.
Torque control selection and architecture
21-00 / Torque control selection — PDF page 443
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-00 | Torque control selection |
| 2 | Range | 0: Speed control 1: Torque control |
21-01 / Filter time of torque reference — PDF page 443
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-01 | Filter time of torque reference |
| 2 | Range | 0~1000 msec |
21-02 / Speed limit selection — PDF page 443
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-02 | Speed limit selection |
| 2 | Range | 0: according AI input 1: according to the set value of 21-03 2: Input by the Communication Address (2502H) |
21-03 / Speed limit value — PDF page 443
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-03 | Speed limit value |
| 2 | Range | -120~120 % |
21-04 / Speed limit bias — PDF page 443
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-04 | Speed limit bias |
| 2 | Range | 0~120 % |
Manual — Torque input and speed limit qualifications — page 444
Manual reference: physical PDF page 444. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Torque Control The torque reference command (Tref) uses analog input AI2 (04-05=15) Note: Torque reference command cannot be set via the keypad. Multi-function analog input (AI2) can used for torque reference (04-05=15) (torque) or torque compensation level (04-05=16). The direction (torque output) of the motor depends on the polarity of the analog input signal (AI2) instead of the direction of the run command. Analog input AI2: Positive voltage forward torque reference (Motor direction counter clockwise). Analog input AI2: Negative voltage reverse torque reference (Motor direction clockwise). To switch to a negative torque reference set one of the multi-function digital input (03-00 to 03-07) to 45 (negative torque command), and activate the digital input terminal (Motor direction clockwise). Table 4.4.41 Torque input method
21-01: Torque filter time Time constant used to reduce the torque signal interference and adjust the torque response. Increase filter time in case the system becomes unstable. 21-02/21-03: Speed limit input setting Limits the motor speed while operating in torque control. When the external torque reference and the system load are out of balance the speed limit may be used to prevent the motor from damaging the system. The speed limit can be set via the digital inputs or using and analog input signal to set the speed limit level. Refer to the table 4.4.17 for the speed limit input method.
Torque input and speed limit qualifications
Input / Input terminal / Parameter setting / Description — PDF page 444
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Input | Input terminal | Parameter setting | Description |
| 2 | Voltage input (0 -10V) | AI2 Selection ”V” | 04-00=0,2 | Terminal AI2 signal level: 0 - 10V |
| 3 | Voltage input (0 -10V) | AI2 Selection ”V” | 04-05=15 | AI2 used as for torque reference |
| 4 | Current input (4 - 20mA) | AI2 Selection ”I” | 04-00=1,3 | Terminal AI2 signal level: 4 - 20mA |
| 5 | Current input (4 - 20mA) | AI2 Selection ”I” | 04-05=15 | AI2 used as for torque reference |
Manual — Speed limit input methods and bias — page 445
Manual reference: physical PDF page 445. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 4.4.42 Speed limit input method
The rotation direction in speed control depends on the speed limit signal: Positive voltage: Forward, speed limit (21-03 + 21-04). Reverse speed limit is zero or reversal direction (-21-04). Negative voltage: Reverse, speed limit (-21-03-21-04). Forward, speed limit is zero or forward direction (21-04). If the speed limit bias is set to 0, the motor speed will be limited to 0 when the rotation direction of the motor and the speed limit are in reverse. Example: The speed limit analog signal is a positive voltage and the motor is in forward operation, then the effective speed range in torque control is from 0 to the analog speed limit value. 21-04: Speed limit bias setting Speed limit bias (21-04) is used to adjust the boundaries of the speed limit. The speed limit bias (21-04) can be used to set the same limit value in forward and reversal direction and is set as a percentage of the maximum output frequency (01-02).
Speed limit input methods and bias
Input method / Input terminal / Related parameter setting / Description — PDF page 445
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Input method | Input method | Input terminal | Related parameter setting | Description |
| 2 | 1 | Voltage input (-10V – 10V) | AI1 | 21-02=0 | Analog input (AI1 or AI2) as speed limit |
| 3 | 1 | Voltage input (-10V – 10V) | AI1 | 00-05=1 | Analog input (AI1 or AI2 is set by 04-05 ) as reference frequency input |
| 4 | 1 | Voltage input (-10V – 10V) | AI1 | 04-00=2,3 | Terminal AI1 signal level : -10V - 10V (if the speed limit is plus value, set 04-00=0, 1) |
| 5 | 1 | Voltage input (10V - 10V) | AI2 (Selection =” V ”) | 21-02=0 | Analog input (AI1 or AI2) as speed limit |
| 6 | 1 | Voltage input (10V - 10V) | AI2 (Selection =” V ”) | 00-05=1 | Analog input (AI1 or AI2 is set by 04-05 ) as reference frequency input |
| 7 | 1 | Voltage input (10V - 10V) | AI2 (Selection =” V ”) | 04-00=0,2 | Terminal AI2 signal level : 0V - 10V |
| 8 | 1 | Voltage input (10V - 10V) | AI2 (Selection =” V ”) | 04-05=12 | AI2 will be added to terminal AI1 as speed limit value |
| 9 | 1 | Current input (4 - 20mA) | AI2 (Selection =” I ”) | 21-02=0 | Analog input (AI1 or AI2) as speed limit |
| 10 | 1 | Current input (4 - 20mA) | AI2 (Selection =” I ”) | 00-05=1 | Analog input (AI1 or AI2 is set by 04-05 ) as reference frequency input |
| 11 | 1 | Current input (4 - 20mA) | AI2 (Selection =” I ”) | 04-00=1,3 | Terminal AI2 signal level : 4 – 20mA |
| 12 | 1 | Current input (4 - 20mA) | AI2 (Selection =” I ”) | 04-05=12 | AI2 will be added to terminal AI1 as speed limit value |
| 13 | 2 | Parameter 21-03 setting | ─ | 21-02=1 | Set the speed limit to be controlled by 21-03 |
| 14 | 2 | Parameter 21-03 setting | ─ | 21-03 | Set speed limit |
| 15 | 3 | Communication Input (2502H) | S+ & S- | 21-02=2 | Communication is used to be the speed limit. |
Manual — Speed limit examples — page 446
Manual reference: physical PDF page 446. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example 1: Set 30% speed limit in forward and reverse direction.
Figure 4.4.128 Speed limit setting Example 2: Settings: 1. Speed limit value (21-03) =100% (positive speed limit) 2. Speed limit bias (21-04) = 20% The speed range in torque control is from -20% (21-04) to 120% (21-03+21-04)
Figure 4.4.129 Speed limit setting (Example 2)
Figure4.4.128 speed limit example1:Outputtorque(T)versusMotorspeed(N),TorqueReferenceTref. Speedticks−100%,−30%,30%,100%;two21-04biasarrows. Printedsettings21-03=0,21-04=30%;speedrange−30%to30%ofmaximumoutputfrequency. Effective range oftorquecontrol markedcentrally.
Figure4.4.129 speed limit example2:Outputtorque versusMotorspeed,TorqueReferenceTref,TorqueLimitbothends;speedticks−100%,−20%,100%,120%;21-04biasbetween100and120%;Speedlimit21-03setting100%;effectiverangeofcontrolmarked−20to100%. Printedcallouts:aboveforwardlimit120%,torqueincreasesnegative,limitedbyregenerativetorquein4thquadrant;belowreverselimit−20%,torqueincreasespositive,limitedbyregenerativetorquein2ndquadrant. Preserve diagram interval independentlyfromprose−20to120%.
Manual — Winding and unwinding torque examples — page 447
Manual reference: physical PDF page 447. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example: Torque limit and speed limit operation: In this example the torque limit and speed limit are used in a winding and unwind operation. Winding operation The line speed (N) and motor torque (T) are in the same direction of the motor. Refer to Figure 4.4.130
Figure 4.4.130 Winding operation ①. Speed limit bias (-21-04) > Motor Speed > speed limit bias (+21-04) → torque based on Tref. ②. Motor speed (N) > speed limit bias +21-04 → speed limit will output negative torque to prevent the increase of motor speed. ③. Motor speed (N) <-21-04 → speed limit will output a forward torque to prevent an increase of speed. Unwinding operation The line speed (N) and motor torque (T) are in opposite direction
Figure 4.4.131 Unwind operation
Figure4.4.130 Winding operation:roll,M,line directionright;NandT arrows sameclockwisedirection. Outputtorque(T)versusMotorspeed(N),Tref plateau,SpeedLimitSetting,two21-04biasintervals,TorqueLimit21-08upperleft and21-07lowerright. BottomregionlabelsI,j,k asprinted;no engineering equivalence inferred.
Figure4.4.131 Unwind operation:roll,M,line directionright;TandNarrowoppositedirections.Outputtorque(T)versusmotorspeed(N),Tref lowerplateau,SpeedLimitSetting,two21-04biasintervals,TorqueLimit21-08upperleft,21-07lowerright. Source illustration only.
Manual — Winding unwind associations and compensation — page 448
Manual reference: physical PDF page 448. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The relationship among Tref (torque reference), NLmt (speed limit) and N (motor speed) is shown below when used in winding operation and roll-out operation.
Figure 4.4.132 Winding and roll-out operations Torque compensation Torque compensation is used to compensate for torque loss due to mechanical damage or other losses. Multi-function analog input AI2 can used for torque compensation (04-05 = 16, 04-07/08 Gain/ Bias). Set the appropriate signal level for the torque compensation. The torque compensation direction is based on the analog signal polarity, not by the direction of the run command. When Tcomp is fixed at a positive voltage (or current) results in a positive torque compensation (the rotation of motor shaft is counterclockwise).
Winding Forward T–Ncurve:21-08upperleft,21-07lowerright,Tvertical,Nright,Trefpositiveplateau,NLmtpositive,21-04atbothplateauends.
Winding Reverse T–Ncurve:21-08upperleft,21-07lowerright,Tvertical,Nright,Trefnegativeplateau,NLmtnegative,21-04atbothplateauends.
Unwind Forward T–Ncurve:21-08upperleft,21-07lowerright,Tvertical,Nright,Trefnegativeplateau,NLmtpositive,21-04atbothplateauends.
Unwind Reverse T–Ncurve:21-08upperleft,21-07lowerright,Tvertical,Nright,Trefpositiveplateau,NLmtnegative,21-04atbothplateauends.
Winding architecture:Line directionright;NandT arrowsbothclockwisearoundroll. Source illustration only.
Unwind architecture:Line directionright;TclockwisearrowatupperleftandNcounterclockwisearrowatlowerleft;sourcearrowsopposite. No inferred wiring.
Four T–Ngraphs and two architecture image cells are separately bounded figure records; empty native cells do not mean absence of source content. Winding/unwind and forward/reverse associations retained exactly.
Winding unwind associations and compensation
Operations / Winding operation / Unwind operation — PDF page 448
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Operations | Winding operation | Winding operation | Unwind operation | Unwind operation |
| 2 | T-N curve | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | Operation direction | Forward | Reverse | Forward | Reverse |
| 4 | Tref ( Torque reference) | + | − | − | + |
| 5 | NLmt ( Speed limit ) | + | − | + | − |
| 6 | Architecture | N T Line direction | N T Line direction | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Torque quadrant limits — page 449
Manual reference: physical PDF page 449. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Use the torque limit function to limit the torque applied to the load, or limit the regenerative torque. In speed control the torque limit function has a higher priority than the motor speed control and compensation. This might result in extended acceleration, deceleration times and a reduction in motor speed. Torque limit can be set in two ways: - Use torque limit parameters (21-05 to 21-08) to set a fixed torque limit. - Set the torque limit by using the multi-function analog input (AI2). There are four torque limits that can be set separately, one for each quadrant: (I) Positive torque limit in forward direction (21-05 positive torque limit) (II) Positive torque limit of reverse direction (21-06 negative torque limit) (III) Negative torque limit in reverse direction (21-07 forward regenerating torque limit) (IV) Negative torque limit in forward direction (21-08 reversal regenerating torque limit) Refer to Figure 4.4.133.
Figure 4.4.133 Torque limit setting
Figure4.4.133 Torquelimitquadrants:OutputTorque(T)vertical,MotorSpeedhorizontal;Iupperright21-05,IIupperleft21-08,IIIlowerleft21-06,IVlowerright21-07;PositiveTorqueupper,NegativeTorquelower;Reversedirectionleft,Forwarddirectionright. LegendIForwardrotationpositivetorque;IIReverserotationpositivetorque;IIIReverserotationnegativetorque;IVForwardrotationnegativetorque. Sourceplotmappingretainedseparatelyfromprose.
Torque quadrant limits
21-05 / Positive torque limit — PDF page 449
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-05 | Positive torque limit |
| 2 | Range | 0~300 % |
21-06 / Negative torque limit — PDF page 449
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-06 | Negative torque limit |
| 2 | Range | 0~300 % |
21-07 / Forward regenerating torque limit — PDF page 449
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-07 | Forward regenerating torque limit |
| 2 | Range | 0~300 % |
21-08 / Reversal regenerating torque limit — PDF page 449
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-08 | Reversal regenerating torque limit |
| 2 | Range | 0~300 % |
Manual — Analog input torque limits — page 450
Manual reference: physical PDF page 450. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Torque limit setting by using multi-function analog input AI2 (04-05) Table 4.4.43 Torque limit analog input
Set the analog input terminal (AI2) signal level (04-00), gain (04-07) and bias (04-08) The default setting for the analog input AI2 is 0 -10V representing 0 – 100% of the motor rated torque). Figure 4.4.129 shows the relationship between the output torque and the torque limit.
Figure 4.4.134 Analog input torque limit (AI2) When the analog input is set to positive torque limit (value = 11) the torque limit is active in the third and fourth quadrant.in the reverse direction (regenerative torque in the second quadrant). When the analog input is set to negative torque limit (value = 12) the torque limit is active in the third and fourth quadrant. When the analog input is set to regenerative torque limit (value = 13) the torque limit is active in the second and fourth quadrant can be controlled. When the analog input is set to positive/negative torque limit (value = 14) the torque limit is active in all four quadrants.
Figure4.4.134 AnaloginputtorquelimitAI2:OutputTorque(T)versusMotorSpeed(N).IForwarddriving21-05;IIReverseregenerating21-08;IIIReversedriving21-06;IVForwardgenerating21-07. DottedguidesPositiveTorqueLimit04-05=11;NegativeTorqueLimit04-05=12;RegenerativeTorqueLimit04-05=13;Positive/NegativeTorqueLimit04-05=14bothupper/lower. Sourcequadrantlabels only.
Analog input torque limits
Adjacent source context — repeated to preserve continuation:
04-05 (AI2) / Function — PDF page 450
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-05 (AI2) | Function |
| 2 | 11 | Positive torque limit |
| 3 | 12 | Negative torque limit |
| 4 | 13 | Regenerative torque limit (for both forward and reversal directions). |
| 5 | 14 | Positive/negative torque limit (positive and negative detection torque limit ) |
Manual — Position control sections0–7 — page 451
Manual reference: physical PDF page 451. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
When the analog input is at maximum (10V or 20mA), the torque limit is 100% of the motor rated torque. In order to increase the torque limit above 100% the analog input gain (04-07) has to set to a value greater than 100%. For example: 200.0% of the gain will result in the torque limit of 200% of motor rated torque at 10V (20mA) analog input level.
Position control sections0–7
Adjacent source context — repeated to preserve continuation:
21-09 / Maximum frequency of position control — PDF page 451
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-09 | Maximum frequency of position control |
| 2 | Range | 0.1~100 Hz |
| 3 | 21-10 | The command of rotation cycle number of section 0 |
| 4 | Range | -9999~9999 |
| 5 | 21-11 | The command of the pulse number of section 0 |
| 6 | Range | -9999~9999 |
| 7 | 21-12 | The command of rotation cycle number of section 1 |
| 8 | Range | -9999~9999 |
| 9 | 21-13 | The command of the pulse number of section 1 |
| 10 | Range | -9999~9999 |
| 11 | 21-14 | The command of rotation cycle number of section 2 |
| 12 | Range | -9999~9999 |
| 13 | 21-15 | The command of the pulse number of section 2 |
| 14 | Range | -9999~9999 |
| 15 | 21-16 | The command of rotation cycle number of section 3 |
| 16 | Range | -9999~9999 |
| 17 | 21-17 | The command of the pulse number of section 3 |
| 18 | Range | -9999~9999 |
| 19 | 21-18 | The command of rotation cycle number of section 4 |
| 20 | Range | -9999~9999 |
| 21 | 21-19 | The command of the pulse number of section 4 |
| 22 | Range | -9999~9999 |
| 23 | 21-20 | The command of rotation cycle number of section 5 |
| 24 | Range | -9999~9999 |
| 25 | 21-21 | The command of the pulse number of section 5 |
| 26 | Range | -9999~9999 |
| 27 | 21-22 | The command of rotation cycle number of section 6 |
| 28 | Range | -9999~9999 |
| 29 | 21-23 | The command of the pulse number of section 6 |
| 30 | Range | -9999~9999 |
| 31 | 21-24 | The command of rotation cycle number of section 7 |
| 32 | Range | -9999~9999 |
| 33 | 21-25 | The command of the pulse number of section 7 |
| 34 | Range | -9999~9999 |
Manual — Position sections8–15 and origin — page 452
Manual reference: physical PDF page 452. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Position sections8–15 and origin
21-26 / The command of rotation cycle number of section 8 — PDF page 452
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 21-26 | The command of rotation cycle number of section 8 |
| 2 | Range | -9999~9999 |
| 3 | 21-27 | The command of the pulse number of section 8 |
| 4 | Range | -9999~9999 |
| 5 | 21-28 | The command of rotation cycle number of section 9 |
| 6 | Range | -9999~9999 |
| 7 | 21-29 | The command of the pulse number of section 9 |
| 8 | Range | -9999~9999 |
| 9 | 21-30 | The command of rotation cycle number of section 10 |
| 10 | Range | -9999~9999 |
| 11 | 21-31 | The command of the pulse number of section 10 |
| 12 | Range | -9999~9999 |
| 13 | 21-32 | The command of rotation cycle number of section 11 |
| 14 | Range | -9999~9999 |
| 15 | 21-33 | The command of the pulse number of section 11 |
| 16 | Range | -9999~9999 |
| 17 | 21-34 | The command of rotation cycle number of section 12 |
| 18 | Range | -9999~9999 |
| 19 | 21-35 | The command of the pulse number of section 12 |
| 20 | Range | -9999~9999 |
| 21 | 21-36 | The command of rotation cycle number of section 13 |
| 22 | Range | -9999~9999 |
| 23 | 21-37 | The command of the pulse number of section 13 |
| 24 | Range | -9999~9999 |
| 25 | 21-38 | The command of rotation cycle number of section 14 |
| 26 | Range | -9999~9999 |
| 27 | 21-39 | The command of the pulse number of section 14 |
| 28 | Range | -9999~9999 |
| 29 | 21-40 | The command of rotation cycle number of section 15 |
| 30 | Range | -9999~9999 |
| 31 | 21-41 | The command of the pulse number of section 15 |
| 32 | Range | -9999~9999 |
| 33 | 21-42 | Pos. Mode Selection |
| 34 | Range | 0: Switch to position mode when output frequency < 01-08. 1: Z Phase Locked Function |
| 35 | 21-43 | Offset Angle |
| 36 | Range | 0 ~9999 Pulse |
Manual — Zero servo and position selection — page 453
Manual reference: physical PDF page 453. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
21-09 Maximum frequency for position control Maximum output frequency when moving to the next position. The position control function uses acceleration time 1 (00-14). Maximum output frequency when moving to the next position. The position control function uses deceleration time 1 (00-15). In the SV control mode, multi-function digital input terminals (03-00 to 03-07) can be used to select the position. See table 4.4.44.
Figure 4.4.135 Zero-servo positioning Table 4.4.44 Multi-position positioning function setting
Zero-servo positioning function (Zero-Servo): When the output frequency falls below Fmin and the zero-servo input is active, the position is locked in and the inverter enters zero-servo positioning mode (Zero-Servo). Positioning command PosRef is origin, as shown in figure 4.4.135. Refer to parameter 11-49 and 11-50 for zero-servo gain and zero-servo count and parameter 20-02 and 20-03 to setup the speed regulator function. Multi-position function (MultiPosRef): Parameter 21-42 is set to 0 and the speed is lower than the lowest frequency so the inverter will enter into the position mode. If input multi-speed and multi-position command switch (DI is set to 51) in the zero-servo mode,
Figure4.4.135 Zero-servopositioning:OutputfallstothresholdFmin(01-08),briefplateau,thenzero;DI(ZeroServo)risesatplateauend;Runtracehigh. Horizontalaxesarrowedwithoutnumericdurations;no timingvaluesinferred.
Zero servo and position selection
Digital Input setting 03-00~03-07 / Function — PDF page 453
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Digital Input setting 03-00~03-07 | Function |
| 2 | 02 | Multi-speed/position setting command 1 |
| 3 | 03 | Multi-speed/position setting command 2 |
| 4 | 04 | Multi-speed/position setting command 3 |
| 5 | 05 | Multi-speed/position setting command 4 |
| 6 | 46 | Zero-Servo command |
| 7 | 51 | Select between speed control and position control |
| 8 | 52 | Position command enable |
Manual — Z phase spindle and position control — page 454
Manual reference: physical PDF page 454. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
multi-speed command 1~4 is transformed to multi-position command 1~4 and the origin of zero-servo mode has 17-section position. Refer to Fig.4.4.131. Spindle Positioning Function (Z-phase locked function)
Parameter 21-42 is set to 1 and the speed is lower than the lowest frequency so the inverter will enter into the position mode when Z-phase signal appears. The origin is positioned in z phase signal and the setting value of parameter 21-43. It can be also coupled with multi-position function.
Z phase bias value of monitoring parameter 12-78 will display the bias between Z phase and the current position. User can rotate the motor at one cycle depending on the rotation direction. Z phase bias value of parameter 12-78 is the differential value between steering position Z point after capturing the position of Z point. Make the value of 12-78 input the offset angle of parameter 21-43 after the position is confirmed. Then the origin is positioned at Z phase signal + the setting value of parameter 21-43. Note: If the motor is just at power on and does not pass the Z point, parameter 12-78 will display 9999. Position control: - Activate Run command (RUN) - Activate Zero-Servo command (Zero-Srvo) - Activate Position enable command (MultiPosEn) - Select a position with the multi-function digital inputs (PosRef) Refer to figure 4.4.136.
Figure 4.4.136 Multi-positioning logic diagram Refer to parameter 20-28 to set PG motor direction.
Figure4.4.136 Multi-positionlogic:PosRef0–15staircaserisesandfalls;Zero-Servo,MultiPos.Enable,MultiPos.Switch,S4,S3,S2,S1,Runtracesversust;dashedverticalalignmentguides. Source timingillustration;no unlabelled binary-to-positiontableorlogic inferred.
Opening multi-speed/position continuation belongs453Multi-position function paragraph; spindle-position heading starts subsequent section.
Manual — Position enable absolute position and examples — page 455
Manual reference: physical PDF page 455. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
A position is defined by the number of rotations plus the number of pulses. When multi-position function is used, position command enable (Multi Pos. Enable, DI is set to 52) is required to be ON so the inverter can receive the external position command. Refer to Fig. 4.4.137.
Fig. 4.4.137 Position Enable Diagram Multi-position mode is the absolute type. If the first section is at 100 pulse and make the motor rotate at more than 100 pulse, then the second section is required to set at 200 pulse. Refer to Fig. 4.4.138.
Figure 4.4.138 the absolute type diagram Position setting(21-10~21-41):
Example: 2 Positions Motor encoder is 1024 PPR. Position 1: Rotate motor shaft in forward direction 180 degrees, set rotation cycle to 0 and pulse number to 512 (1/2 x 1024). Positive number indicated forward direction. Position 2: Rotate motor shaft 1reverse 270 degrees (-768 pulses), set rotation cycle to 0 and pulse number to -768 (- 3/4 x 1024). Negative number indicated forward direction.
Figure4.4.137 PositionEnable:ExternalPositionCommandsequentialPosition0,1,2,3,4,5;PositionCommandEnablehighduring0and1,low2,high3,low4and5. PositionCommandofInverterlabels0,1,1,3,3,3respectively. Horizontal t axes;source exampleassociationonly.
Figure4.4.138 Absolute-typeposition:Position(pulse)versusTime(t);rampto100plateau,then200plateau;firstverticalincrement100andsecondincrement100. No timingdurationgiven.
Printed formula:MotorPositionSettingofNsection = RotationCyclesCommandofNsection × PGpulse(20-27) + PulseCommandofNsection.
Manual — PM motor nameplate settings and speed formula — page 456
Manual reference: physical PDF page 456. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
22- PM Motor Parameters
The PM parameter group can be restored to factory default be initializing the inverter (13-08). 1. PM motor rated power (22-00); PM motor rated voltage (22-01); PM motor rated current (22-02) Setting the motor nameplate value. 2. PM motor pole number (22-03); PM motor rated rotation speed (22-04); PM motor rated frequency (22-06) Setting the motor nameplate value. For the PM motor rated rotation speed (22-04) and the PM motor rated frequency (22-06), just set one of the two and the program will automatically calculate the other. When setting the PM motor rated rotation speed (22-04), the PM motor’s maximum rotation speed (22-05) will synchronize and update to the same setting. When using the flux-weakening function, the PM motor’s maximum rotation speed (22-05) setting value must be revised. The formula is as follows:
Printed PM speed formula: N(PM Motor rated rotation speed) = 120 × f(PM Motor rated frequency) / P(PM Motor pole number). No calculated ratings inferred.
PM motor nameplate settings and speed formula
22-00 / PM motor rated power — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-00 | PM motor rated power |
| 2 | Range | 0.00~600.00 Kw |
22-01 / PM motor rated voltage — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-01 | PM motor rated voltage |
| 2 | Range | 200V: 【50 ~ 240】V 400V: 【100 ~ 480】V |
22-02 / PM motor rated current — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-02 | PM motor rated current |
| 2 | Range | 25%~200% inverter’s rated current |
22-03 / PM motor’s pole number — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-03 | PM motor’s pole number |
| 2 | Range | 2~96 Poles |
22-04 / PM Motor’s rated rotation speed — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-04 | PM Motor’s rated rotation speed |
| 2 | Range | 6~60000 rpm |
22-05 / PM motor’s maximum rotation speed — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-05 | PM motor’s maximum rotation speed |
| 2 | Range | 6~60000 rpm |
22-06 / PM motor rated frequency — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-06 | PM motor rated frequency |
| 2 | Range | 4.8~599.0 Hz |
22-07 / PM type selection — PDF page 456
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-07 | PM type selection |
| 2 | Range | 【0】SPM 【1】IPM |
Manual — PM encoder and tuning parameters — page 457
Manual reference: physical PDF page 457. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- PM motor’s maximum rotation speed (22-05) When using the flux-weakening function, the PM motor’s maximum rotation speed (22-05) must be set higher than the PM motor’s rated rotation speed (22-04). 4. PM type selection (22-07) When using the SPM motor, the recommended setting is 0. Related adjustable parameters are the speed estimated gain (22-30) and the speed estimated filter value (22-31). When using the IPM motor, the recommended setting is 1. Related adjustable parameters are the speed estimated gain (22-34) and the speed estimated filter value (22-35).
22-22 fault-history values0–1 begin here and continue on458.
PM encoder and tuning parameters
22-08 / PM Encoder Type — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-08 | PM Encoder Type |
| 2 | Range | 0: TAMAGAWA Non Wire-Saving Encoder 1: TAMAGAWA Wire-Saving Encoder 2: SUMTAK Wire-Saving Encoder 3: General Incremental Encoder 4: Sine Wave |
22-10 / PM SLV Start Current — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-10 | PM SLV Start Current |
| 2 | Range | 20% ~ 200% Motor Rated Current |
22-11 / I/F Mode Start Frequency Switching Point — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-11 | I/F Mode Start Frequency Switching Point |
| 2 | Range | 【10 ~ 100】% |
22-14 / Armature Resistance of PM Motor — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-14 | Armature Resistance of PM Motor |
| 2 | Range | 0.001 ~ 30.000 Ω |
22-15 / D-axis Inductance of PM Motor — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-15 | D-axis Inductance of PM Motor |
| 2 | Range | 0.01 ~ 300.00 mH |
22-16 / Q-axis Inductance of PM Motor — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-16 | Q-axis Inductance of PM Motor |
| 2 | Range | 0.01 ~ 300.00 mH |
22-17 / PM No-Load Voltage — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-17 | PM No-Load Voltage |
| 2 | Range | 200V: 【0 ~ 250】V 400V: 【0 ~ 500】V |
22-18 / Flux-weakening Current Command Restriction — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-18 | Flux-weakening Current Command Restriction |
| 2 | Range | 0 ~ 120 % |
22-20 / Offset angle of the magnetic pole and PG origin — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-20 | Offset angle of the magnetic pole and PG origin |
| 2 | Range | 0~360 deg |
22-21 / PM motor tuning — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-21 | PM motor tuning |
| 2 | Range | 0: PM Motor Tuning is not Active 1: Parameter Auto-tuning (for PMSLV Tuning) 2: Magnetic Pole Alignment and Loop Adjustment (for PMSV Tuning) 3: Rotation Auto-tuning |
22-22 / Fault history of PM motor tuning — PDF page 457
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-22 | Fault history of PM motor tuning |
| 2 | Range | 0: No error 1: Static magnetic alignment fault. |
Manual — PM fault history and startup methods — page 458
Manual reference: physical PDF page 458. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
22-08: PM Encoder Type After PM encoder type is adjusted, the inverter is required to reconnect to renew the system. If user does not need the specified encoder types, select mode 3 to avoid error occurring. When mode 3 is selected, start mode is the strong magnetic and the current is about 100% setting value of the rated current (22-02) at start. Magnetic pole search is according to parameter 22-25 or start upon the angle before stopping. If 22-25=0, inverter at the first start after power failure drives the motor in 0 degree since the angle of motor last stop does not exist and vibration my occur at start-up. Sine wave card is for Heidenhain ERN 1387, ECN 1313 and ECN413 Note: 1. Sine wave card doesn’t support position mode. 2. If PG card and PM encoder is not matched, SE07 fault will occur. 3. If PM encoder type (22-08) is reset, it is required to reconnect and then perform PM motor tuning (22-21). Find the offset angle of the magnetic pole again. If the above actions are not performed, SE08 fault will occur. 22-10: PM SLV Start Current Set torque current at start and the unit is the percentage of motor rated current. 22-11: I/F Mode Start Frequency Switching Point This function is for the switching point from open-loop to close-loop in PMSLV mode. The unit is percentage for rated speed of motor .It recommends that over 5% for 400V and over 10% for 200V. 22-14: Armature Resistance of PM Motor
First unlabelled table continues22-22 from457;bottom22-14heading continues459.
PM fault history and startup methods
/ 2: Without PG option card 3: Rotation pole alignment is forced to stop 4: Error of Encoder Feedback Direction. 5: Loop adjustment is time out 6: Encoder error 7: Other errors of motor tuning 8: Current abnormity occurs when aligning rotation magnetic pole 9: Current abnormity occurs while loop adjustment 10:Reserved 11: Stator Resistance Measurement Timeout — PDF page 458
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | ⟦blank source cell⟧ | 2: Without PG option card 3: Rotation pole alignment is forced to stop 4: Error of Encoder Feedback Direction. 5: Loop adjustment is time out 6: Encoder error 7: Other errors of motor tuning 8: Current abnormity occurs when aligning rotation magnetic pole 9: Current abnormity occurs while loop adjustment 10:Reserved 11: Stator Resistance Measurement Timeout |
22-25 / Detection Mode Selection of Initial Magnetic Pole — PDF page 458
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-25 | Detection Mode Selection of Initial Magnetic Pole |
| 2 | Range | 0: Upon the angle before stopping 1: Mode 1 2: Mode 2 3: Mode 3 |
| 3 | 22-26 | High speed control ratio enable (For PMSLV) |
| 4 | Range | 0: Low Speed Open Loop Control 1: Low Speed High Frequency Control 2: Full Closed Loop Control |
| 5 | 22-27 | Voltage Command of Mode 2 |
| 6 | Range | 【5 ~ 120】% (22-25=2 or 22-26=1 is enabled) |
| 7 | 22-28 | Divider Ratio of Mode 2 |
| 8 | Range | 【0~8】 (22-25=2 or 22-26=1 is enabled) |
| 9 | 22-29 | Flux-weakening Voltage Command Restriction |
| 10 | Range | 【80 ~ 110】% (related to parameter 22-18) |
Manual — PM motor parameter definitions and tuning warnings — page 459
Manual reference: physical PDF page 459. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Set resistor for each phase of the motor in unit of 0.001Ω. It is set automatically when the motor auto-tunes (22-21). Note: Do not be confused with line-to-line resistance. 22-15: D-axis Inductance of PM Motor Set motor’s D-axis inductance in unit of 0.001mH. It is set automatically when the motor auto-tunes (22-21). 22-16: Q-axis Inductance of PM Motor Set motor’s Q-axis Inductance in unit of 0.001mH. It is set automatically when the motor auto-tunes (22-21). 22-18: Flux-weakening Current Command Restriction 1. When the MTPA’s selected (22-32) setting is 0, the setting parameter’s (22-05) maximum motor rotation speed is higher than the parameter’s (22-04) motor rated rotation speed. This will automatically activate the flux-weakening control. Set this parameter to restrict the maximum flux-weakening capability. The unit is the motor’s rated current percentage. 2. When the MTPA’s (22-32) selected setting is 2 or 3, and the output voltage is too high, the flux-weakening voltage command restriction setting value must be raised. 22-20: Offset Angle of the Magnetic Pole and PG Origin Magnetic pole alignment offset value is stored in this parameter after tuning. 22-21: PM Motor Tuning WARNING! Sudden start: The inverter and motor may start unexpectedly during Auto-Tuning, which could result in death or serious injury. Make sure the area surrounding of the motor and load are clear before proceeding with Auto-Tuning. WARNING! Electric Shock Hazard High voltage is supplied to the motor when performing an auto-tune, even when the motor is stopped, which could result in death or serious injury. Do not touch the motor when performing magnetic pole realignment until the auto-tuning procedure is completed. WARNING! Holding Brake Do not perform a magnetic pole realignment auto-tuning procedure when the motor is connected to a brake this may result in incorrect motor data calculation. Disconnect the motor and the load and confirm that the motor can freely run. 1. Before selecting PM motor tuning, enter the motor data (22-00) - (22-06) according to the motor nameplate and the number of encoder pulses (20-27). 2. a) Use parameter 22-21 to select tuning mode. If 00-00=4 (PMSV), please set 22-21=2 to tuning. If 00-00=5 (PMSLV), please set 22-21=1 to tuning. b) When 00-00 set to 4 (PMSV), if the motor pole number (22-03) is unknown, please set 22-21=2. If PM
Opening paragraph belongs22-14heading458;finalstep2bcontinues460.
Manual — PM tuning sequence and angle detection — page 460
Manual reference: physical PDF page 460. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
encoder type (22-08) set to 4 (Sine wave, ECN1313, ECN413 and ERN1387) or specific encoder (20-32) set to 1 (Resolver) and the motor pole number (22-03) is known, please set 22-21=1 (Parameter auto-tune), then set to 3 (Magnetic pole alignment), the tuning time can be reduced. Note 1: If encoder type (22-08) set to 0 ~ 3, and set 22-21=3, PM Tune Error03 will be display. Note 2: If 22-21 set to 2 or 3 to motor tuning, and PM Tune Error04 happens, PG rotation direction (20-28) will be change automatically, please do motor tuning again by same items. If the same error happen again, please re-wire the feedback or motor phase sequence, then do motor tuning again. c) Next press the enter key to go to the PM motor tuning screen. The keypad will display the message of "IPrdy" (Ready to Tune). d) Press run to start the PM motor tuning. The keypad will display the “IPtun" message during auto-tune. e) If the motor is successfully tuned, the message of "IPEnd " will be displayed. If auto-tune is aborted with the stop key, the operator will display the message of " IPbrd "(PM motor tuning aborted). Notes: 1. Perform a magnetic pole alignment auto-tune before adjusting the speed loop. 2. It is not required to perform a magnetic pole alignment auto-tune each time the inverter is powered up. 22-22: Fault History of PM Motor Tuning If PM motor tuning has failed, the “IPErr” message is shown on the keypad (PM motor tuning failure). Refer to section 10 for the possible error causes and trouble shooting. PM motor tuning fault history (22-22) only stores the result of the last auto-tune performed .If auto-tuning was successful or aborted, no error will be displayed. 22-25: Detection Mode Selection of Initial Magnetic Pole Select the motor activation’s rotor position detection method Method 0: Do not detect rotor position, start by directly using the angle when the motor was previously stopped Method 1: Use input pulse signal to detect rotor position. Method 2: Use input continuous variable frequency signal to detect rotor position. Method 3: Input voltage pulse signal 22-26: High speed control ratio enable It is suggested to set 22-26=0 when SPM motor is used. Inverter starts in I/f mode and the relevant adjustable parameters are 22-10 & 22-11. It is suggested to set 22-26=1 when IPM motor is used and speed control mode is performed by the speed control ratio 1:50. Inverter will input the continuously variable frequency signal to motor and the relevant adjustable parameters are 22-27 & 22-28. When it is set to 2, both IPM motors and SPM motors can be used, and the relevant adjustable parameters are 22-42 to 22-45. 22-27: Voltage Command of Mode 2 When 22-25=2 or setting of parameter 22-26 is enabled, input of the voltage amplitude setting for the continuously variable frequency signal will influence the motor jittering. When the motor starts and the rotor jitter occurs, it is required to increase the voltage amplitude to ensure the accuracy of detection angle. Note: When the voltage value is set too high, overcurrent error may occur.
Opening text continues459step2b.
Manual — PM estimator gain and DVEn choices — page 461
Manual reference: physical PDF page 461. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
22-28: Divider Ratio of Mode 2 When 22-25=2 or setting of parameter 22-26 is enabled, the input of continuous signal frequency depends on the parameter (11-01) carrier setting. If the carrier setting is higher, it is required to appropriately increase the divider ratio so as to reduce the input of continuous signal frequency and ensure the accuracy of detection angle. 22-29: Flux-weakening Voltage Command Restriction It is set for preventing the saturation of the output voltage. Inverter performs flux-weakening control by the percentage of input power supply voltage as the limit of output voltage command. If flux-weakening current command restriction (22-18) is set too low, inverter output voltage may exceed the voltage command limit.
22-30: Speed Estimated Gain 22-31: Speed Estimated Filter Value When Estimator Mode 22-26 set to 0, adjust the speed response performance, the higher the setting value, the faster the motor reacts, however, if the setting value is too high, the control object will generate vibrations and become unstable, also, if the setting value is lower, the speed deviation will increase. Please adjust to the appropriate setting value according to the field equipment.
PM estimator gain and DVEn choices
22-30 / SPM Speed Estimation Gain — PDF page 461
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-30 | SPM Speed Estimation Gain |
| 2 | Range | 【1 ~ 150】% |
| 3 | 22-31 | SPM Speed Estimation Filter Value |
| 4 | Range | 【1 ~ 2000】Hz |
| 5 | 22-32 | MTPA Selection |
| 6 | Range | 【0】: Disabled 【1】: Mode 1 【2】: Mode 2 【3】: Mode 3 |
| 7 | 22-33 | MTPA Gain |
| 8 | Range | 【0 ~ 400】% |
| 9 | 22-34 | IPM Estimator Gain |
| 10 | Range | 【1 ~ 180】% |
| 11 | 22-36 | PM Motor Type Selection |
| 12 | Range | 0: Normal PM motor 1: DVEN Motor |
| 13 | 22-37 | PM Motor Horse Power & RPM |
| 14 | Range | 1: 0.75KW 1800RPM 4: 1.5KW 1800RPM 7: 2.2KW 1800RPM 10: 3.7KW 1800RPM 13: 5.5KW 1800RPM 16: 7.5KW 1800RPM 19: 11KW 1800RPM 22: 15KW 1800RPM 25: 18.5KW 1800RPM 28: 22KW 1800RPM |
Manual — MTPA and closed loop parameters — page 462
Manual reference: physical PDF page 462. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
22-32: MTPA Selection 0: MTPA invalid 1: Distribute D-Q-axis current command according to the torque command. 2: Distribute D-Q-axis current command according to the torque command and restrict output voltage (12-19) to below the motor’s rated voltage (22-01). 3: Distribute D-Q-axis current command according to the torque command and control the output voltage (12-19) to around the motor’s rated voltage (22-01). 22-33: MTPA Gain When the default value is 200%, revising the PM motor’s D-axis inductance (22-15) or Q-axis inductance (22-16) (such as completing the PM motor adjustment or directly changing the inductance value) will re-calculate the MTPA Gain (22-33). 22-34: IPM Estimator Gain When the estimator mode (22-26) setting is 1, the estimator gain is the multiple of the bandwidth. The larger the setting value, the faster the motor response. However, if the value is too high, the control item will exhibit vibration and become unstable. The smaller the setting value, the greater the speed deviation. Please adjust the appropriate setting value according to the site equipment. 22-36: PM Motor Type Selection 22-37: PM Motor Horse Power & RPM Use (22-36) to choose general PM motor or DVEN motor. After selecting, you can match the parameter PM motor horsepower and RPM (23-37), select the corresponding horsepower number, you can build the motor parameters without auto-tuning, if you choose general motor later, auto-tuning is required.
22-38: Open and closed loop switching point frequency width (%) Mainly when 22-26 = 0, open-loop control, when the (22-11) I/F mode start frequency switching point is exceeded, the open-loop switch to the closed-loop control process, through the adjustment of the switching weight ratio, the switching process can be effectively suppressed the current stability may be caused by different applications,
MTPA and closed loop parameters
22-38 / Open and closed loop switching point frequency width (%) — PDF page 462
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 22-38 | Open and closed loop switching point frequency width (%) |
| 2 | Range | 【1.0~40】% |
| 3 | 22-39 | Preliminary DC injection time |
| 4 | Range | 【0.00~20.0】s |
| 5 | 22-40 | High frequency angle finding time |
| 6 | Range | 【0.01~1.00】s |
| 7 | 22-41 | PM stop method |
| 8 | Range | 0: Decelerate or stop below 22-11 and brake directly 1: Decelerate or stop below 22-11 and open loop stop |
| 9 | 22-42 | Fully closed loop control gain Ka |
| 10 | Range | 【64~8192】 |
| 11 | 22-43 | Fully closed loop control gain Kb |
| 12 | Range | 【64~8192】 |
| 13 | 22-44 | Fully closed loop control gain speed low pass filter |
| 14 | Range | 【1~256】 |
| 15 | 22-45 | Fully closed loop control magnetic flux |
| 16 | Range | 【0.01~10.00】 |
Manual — PM startup and full closed loop context — page 463
Manual reference: physical PDF page 463. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
which enables better effects and protection in control operation. 22-39: Preliminary DC injection time When the PM motor starts, it will first estimate the angle and then run in the PMSLV mode. When this parameter is set, when the angle estimation is completed, the DC injection method will first be used to draw the motor to the angle before running, which can effectively achieve start-up stability. 22-40: High frequency angle finding time When 22-25=2, due to the PM motor angle estimation through the high frequency method during startup, high frequency sound may be generated. In order to effectively suppress the high-frequency sound, users can use this parameter to set the high frequency angle finding time according to their needs. Set to reduce the high frequency sound generation by shortening the angle finding time when the high frequency angle search can be run normally. 22-41: PM stop method In PMSLV mode, when the speed is lower than 22-11, the system will use the 22-41 parameter mode to perform different deceleration modes. When 22-41=0, the deceleration/stop is lower than 22-11 and the DC brake mode will stop. ; When 22-41=1, open loop stop when deceleration/stop is lower than 22-11. Users can choose between the modes according to their needs to achieve better operation control. 22-42: Fully closed loop control gain Ka 22-43: Fully closed loop control gain Kb 22-44: Fully closed loop control gain speed low pass filter 22-45: Fully closed loop control magnetic flux Used with 22-26 = 2 full closed loop control, and full closed loop control is mainly used for control below the low speed control ratio to achieve PMSLV full-field full closed loop control, and then applied to different low-speed occasions, through adjustment and estimation the gain of parameters 22-42~45 of the device to achieves the stability of PMSLV low speed ratio control.
Opening blue sentence continues462description22-38.
Manual — PLC commands and registers — page 464
Manual reference: physical PDF page 464. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.5 Built-in PLC Function
The PLC ladder logic can be created and downloaded using the TECO drive link software. 4.5.1 Basic Command
Description of registers V1: Set frequency Range: 0.1~599.0Hz V2: Operation frequency Range: 0.1~599.0Hz V3: AI1 input value Range: 0~1000 V4: AI2 input value Range: 0~1000 V5: Keypad input value Range: 0~1000 V6: Operation current Range: 0.1~999.9A V7: Torque value Range: 0.1~200.0% V8: PID Target Value Range: 0.1~599.0Hz
PLC basic command header glyphs left to right: bracket coil; upward SET arrow; downward RESET arrow; P; normally open contact; normally closed contact. Source symbols only; column associations preserved in physical table.
Other command symbol cells: SET upward arrow; RESET downward arrow. Native glyph encoding retained separately; no inferred ladder implementation.
Connection symbol column: horizontal line; T junction with top stem; cross; T junction with bottom stem. Adjacent source definitions retained as table cells; no inferred wiring.
PLC commands and registers
/ / / P / NO / NC — PDF page 464
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | [bracket coil symbol] | [SET upward arrow] | [RESET downward arrow] | P | [normally open contact symbol] | [normally closed contact symbol] | NO / NC |
| 2 | Inputs | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | I | i | I1~I8 / i1~i8 |
| 3 | Outputs | Q | Q | Q | Q | Q | q | Q1~Q2 / q1~q2 |
| 4 | Auxiliary command | M | M | M | M | M | m | M1~MF / m1~mF |
| 5 | Special registers | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | V1~V7 |
| 6 | Counter function | C | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | C | c | C1~C8 / c1~c8 |
| 7 | Timer function | T | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | T | t | T1~T8 / t1~t8 |
| 8 | Analog comparison function | G | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | G | g | G1~G8 / g1~g8 |
| 9 | Operation control function | F | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | F | f | F1~F8 / f1~f8 |
| 10 | summation and subtraction function | AS | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | AS1~4 |
| 11 | Multiplication and division function | MD | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | MD1~4 |
Command / Upper Differential / Lower Differential / Other command symbol — PDF page 464
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Command | Upper Differential | Lower Differential | Other command symbol |
| 2 | Differential command | D | d | ⟦blank source cell⟧ |
| 3 | SET command | ⟦blank source cell⟧ | ⟦blank source cell⟧ | [SET upward arrow] |
| 4 | RESET command | ⟦blank source cell⟧ | ⟦blank source cell⟧ | [RESET downward arrow] |
| 5 | P command | ⟦blank source cell⟧ | ⟦blank source cell⟧ | P |
Open circuit / “ “ / — PDF page 464
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Open circuit | “ “ | ⟦blank source cell⟧ |
| 2 | Short circuit | “--” | ⟦blank source cell⟧ |
Connection symbol / Definition — PDF page 464
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Connection symbol | Definition |
| 2 | ─ | Connect components on the left and right side |
| 3 | ┴ | Connects components on the left , right and top side |
| 4 | ┼ | Connects components on the left , right , top and bottom side |
| 5 | ┬ | Connects components on the left , right and bottom side |
Manual — PLC basic command timing examples — page 465
Manual reference: physical PDF page 465. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.5.2 Basic Command Function
◎ D (d) command function
D(d) command Example1 I1—D—[Q1. I1 trace OFF ON OFF; D and Q1 traces OFF, one scanning-cycle ON pulse, OFF. New scanning cycle arrow bounds the narrow pulse. Source timing illustration only.
D(d) Example2 i1—d—[Q1. I1 prime is inverse logic of i1. I1 prime OFF ON OFF; i1 ON OFF ON; d1 andQ1 OFF narrowON pulse OFF. New scanning cycle labelled; no numeric cycle duration given.
NORMAL bracket output I1—[Q1. I1 andQ1 OFF ON OFF aligned traces; no numeric delay inferred.
SET upward-arrow output I1 toQ1. I1 OFF ON OFF;Q1 OFF thenON retained afterI1 falls.
RESET downward-arrow output I1 toQ1. I1 OFF ON OFF;Q1 ON thenOFF retained afterI1 falls.
P output i1—PQ1. I1 prime inverse logic ofi1; alternating OFF ON OFF ON OFF ON OFF labels;Q1 ON OFF ON OFF toggling trace. No unprinted scan timing inferred.
Manual — Counter modes and mode1 example — page 466
Manual reference: physical PDF page 466. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.5.3 Application Functions 1: Counter Function
Counter modes: Mode 1: Counter value is locked to the set value. The value will not be retained when the power is cut off. Mode 2: Counter value is not locked. The value will not be retained when the power is cut off. Mode 3: Counter value is locked. The value will be retained when the power is cut off. Mode 4: Counter value is not locked. The value will be retained when the power is cut off. Counter mode 1 Example:
Counter function symbol:1 at top;2 upperleft;3 lowerleft;4 internal upper;5 internal lower;6 output right. Numeric callouts correspond to adjacent description table.
Counter mode1 example:compare value callout5=20. Internal value4 printed sequence0,0,0,1,1,2,2,1,1,0,[blank],19,19,20,20,20,0,20,20. Counter input pulse trace;2 OFF ON ON labels;3 ON OFF ON;6 OFF ON ON OFF. Blank source cell retained; timing topology not reconstructed.
Counter modes and mode1 example
Symbol / Description — PDF page 466
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Symbol | Description |
| 2 | | Counter mode (1 ~ 4) |
| 3 | | UP/Down counting modes can be set by (I1 ~ f8). |
| 4 | ⟦blank source cell⟧ | OFF: Count up (0, 1, 2, 3…) |
| 5 | ⟦blank source cell⟧ | ON: Count down (…3,2,1,0) |
| 6 | | Use (I1~f8) to reset counting value |
| 7 | ⟦blank source cell⟧ | ON: Internal count value is reset and counter output is OFF |
| 8 | ⟦blank source cell⟧ | OFF: Internal counter value retained |
| 9 | | Internal counter value |
| 10 | | Counter compare value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7,constant) |
| 11 | | Counter output (C1 to C8, there are a total of 8 counters) |
Manual — Counter program and mode2 example — page 467
Manual reference: physical PDF page 467. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Counter mode 2
Note: In this mode the internal counter may increase past the counter compare value, unlike mode 1 where the internal counter value is limited to the counter compare value.
Counter example ladder: I1,i2,[C3];C3,[Q1];m1,q1,[M2];M2. Callout C3 input pulse counter is determined byI1 andi2. Function inputM2 Up/down counting; internalcounter0000;countercompare0020;resetI3. C3 turns ON when counter reaches setvalue and C3 ladder input turnsON; I3 ON resets countervalue. Source callouts only.
Counter mode2:compare5=20; internal4 sequence0,19,19,20,20,21,21,20,20,19,20,18,18,19,19,20,0,20,20. Counter input pulse;2 OFF ON ON;3 OFF ON;6 OFF ON ON OFF. Actual source trace retained, no inferred timing interval.
Manual — Counter modes3 and4 retention — page 468
Manual reference: physical PDF page 468. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(1) Counter mode 3 is similar to the counter mode 1, with the exception that the counter value is saved when the drive is powered down and reloaded at power up. (2) Counter mode 4 is similar to the counter mode 2, with the exception that the counter value is saved when the drive is powered down and reloaded at power up.
Counter retention example:compare5=20. Mode1&2 row4 printed1,1,2,2,[blank poweroff interval],0,1,1,2,2. Mode3&4 row4 printed1,1,2,2,3,[blank poweroff interval],3,4,4,5,5. Counter input pulse and Power switch traces;output6 low. No numeric poweroff duration given.
Manual — Timer definition and modes0 and1 — page 469
Manual reference: physical PDF page 469. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
2: Timer Function
Timer mode description: (1) Timer mode 0 (ON-RTC mode)
(2) Timer mode 1 (ON-delay Timer mode 1)
Timer function symbol:1 top;2 upperleft;3 lowerleft;4 upperinternal;5 lowerinternal;6 rightoutput. Table supplies roles.
Timer mode0 ON-RTC:3Timer reset Internal timer value=0;4RTC mode time setting interval;Reset internal timer value and output at end. Timer start OFF ON OFF;6output OFF ON OFF. Callout says when setvalue reached timer output turns on(T1toT8). No numeric time inferred.
Timer mode1 ON-delay1:Timer reset Internal timer value=0;4Internal timer value;Reset internal timer value and output. Timer start OFF ON OFF;6output OFF thenON after intervalT thenOFF;5T=timer setvalue.
Timer definition and modes0 and1
Symbol / Description — PDF page 469
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Symbol | Description |
| 2 | | Timer mode (0-7) |
| 3 | | Timing unit: 1: 0.0~999.9 second |
| 4 | | 2: 0~9999 second |
| 5 | | 3: 0~9999 minute |
| 6 | | Use (I1~f8) to reset timing value |
| 7 | | ON: Internal timing value is reset and timer output is OFF |
| 8 | | OFF: Internal timer stays running |
| 9 | | Internal timer value |
| 10 | | Timer set value (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8,constant) |
| 11 | | Timer output (T1 to T8, there are a total of 8 timers) |
Manual — Timer example and modes2 and3 — page 470
Manual reference: physical PDF page 470. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example:
(3) Timer mode 2 (ON-delay Timer mode 2)
(4) Timer mode 3 (OFF-delay Timer mode 1)
Timer program example:ladder I1→[T5],T5→[Q1]. Callout prints When I1=0,the5th timer starts. Function program timing unit0.1second;TimerMode1;1,000.0,010.0,T5. When time reaches setvalue10.0seconds,outputT5 turnsON;Timersetvalue points010.0;Presenttimingvalue points000.0. Source text not corrected to inferred logic.
Timer mode2 ON-delay2:Timer reset Internal timer value=0;4Internal timer value;reset internal timer value/output. Timer start OFF ON(t1) OFF ON(t2) OFF;5T=t1+t2;6output OFF ON OFF;3Reset timer andoutput OFF ON OFF. T=timer setvalue.
Timer mode3 OFF-delay1 two examples:Timer reset Internal timer value=0;4Internal timer value;reset internal timer value/output. First Timer start OFF ON OFF,output OFF ON thenOFF afterT following startfall;reset staysOFF. Second shows three startpulses;outputOFF ON OFF ON OFF;resetOFF ON OFF interrupts first output;T arrows show delay intervals.5T=timer setvalue. No unprinted interval durations.
Manual — Timer modes4 through7 — page 471
Manual reference: physical PDF page 471. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
(5) Timer mode 4 (OFF-delay Timer mode 2)
(6) Timer mode 5 (FLASH Timer mode 1)
(7) Timer mode 6 (FLASH Timer mode 2)
(8) Timer mode 7 (FLASH Timer mode 3)
Timer mode4 OFF-delay2:Timer reset internalvalue0;internal timer value;reset internalvalue/output. StartOFF ON OFF;outputOFF ON afterfall thenOFF afterT;Reset timer/outputOFF. T=timer setvalue.
Timer mode5 FLASH1:Timer reset internalvalue0;Present timingvalue starts change fortiming;reset internalvalue/output. Start high during flashing;output alternates with fourT intervals;T=timer setvalue.
Timer mode6 FLASH2:Timer reset internalvalue0;Internal timer value;reset internalvalue/output. Start briefpulse;output oscillatesfourT intervals untilReset timer/outputpulse. T=timer setvalue.
Timer mode7 FLASH3:Timer reset internalvalue0;Internal timer value;reset internalvalue/output. Timerstart high interval;output alternates with first lowdurationt1 andhighdurationt2;output returns lowwhenstartends. No unstated durations inferred.
Manual — Analog comparator modes and inputs — page 472
Manual reference: physical PDF page 472. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3: Analog comparator function
The description of analog comparison mode: (1) Analog comparison mode 1 ( ≤ , ON) (2) Analog comparison mode 2 ( ≥ , ON) (3) Analog comparison mode 3 ( ≤ ≤ , ON) Input comparison value selection (V1~V7) (1) Input comparison value selection = V1: Set frequency (2) Input comparison value selection = V2: Operation frequency (3) Input comparison value selection = V3: AI1 input value (4) Input comparison value selection = V4: AI2 input value (5) Input comparison value selection = V5: Keypad input value (6) Input comparison value selection = V6: Operation current (7) Input comparison value selection = V7: Torque value (8) Input comparison value selection = V8: PID Target Value
Analog comparator symbol:1top;2leftinput;3,4,5vertical internal;6rightoutput. Source callouts refer adjacent role table.
Analog comparator modes and inputs
Symbol / Description — PDF page 472
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Symbol | Description |
| 2 | | Analog comparator mode (1~3) |
| 3 | | Input comparison value selection (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8) |
| 4 | | Current analog input value |
| 5 | | Set the reference comparison value (Upper limit) (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 6 | | Set the reference comparison value (lower limit) (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 7 | | Comparator output (G1 to G8, there are a total of 8 comparators) |
Manual — PLC operation control function — page 473
Manual reference: physical PDF page 473. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4: Operation control function
Example:
Operation control symbol:3top;1upperleft;2lowerleft;4,5,6internal;7rightoutput. Source callouts refer table.
Operation example ladder:I1,(F1);F1,(Q1). RUN/STOP ofF1 determined byON/OFF ofI1. Function program M1,M2,n,n left;10.00,10.00,60.0,30.0 internal;F1output. F1 ON inverter startsrunning and ladderF1inputON. Source labels only, not verified control implementation.
PLC operation control function
Symbol / Description — PDF page 473
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Symbol | Description |
| 2 | | Forward /Reversal control can be set by ( I1~f8 ) OFF: Forward(FWD) ON: Reversal(REV) |
| 3 | | Speed terminal control can be set by ( I1~f8 ) |
| 4 | ⟦blank source cell⟧ | OFF: Operation based on set frequency |
| 5 | ⟦blank source cell⟧ | ON: Operation based on frequency of speed |
| 6 | | Set frequency (can be constant or V3、V4,V5、V8 ) |
| 7 | | Speed frequency (can be constant or V3、V4,V5、V8) |
| 8 | | Acceleration time (ACC Time) |
| 9 | | Deceleration time (DEC Time) |
| 10 | | Operation command output (F1 to F8, there are a total of 8 operation control functions) |
Manual — PLC arithmetic functions — page 474
Manual reference: physical PDF page 474. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
5: Summation and subtraction functions
RESULT (calculation result) = V1+ V2- V3
6: Multiplication and division modes
RESULT(calculation result)=V1*V2/V3
Summation/subtraction symbol:1,2,3,4 internal top-to-bottom;5upperright errorcoil;6lowerrightmode. RESULT=V1+V2−V3 in adjacent source formula.
Multiplication/division symbol:1,2,3,4 internal top-to-bottom;5upperright errorcoil;6lowerrightmode. RESULT=V1*V2/V3 in adjacent source formula.
PLC arithmetic functions
Symbol / Description — PDF page 474
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Symbol | Description |
| 2 | | Calculation result : RESULT |
| 3 | | Addend V1(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 4 | | Addend V2(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 5 | | Subtrahend V3(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 6 | | Coil output of error signal (M1~MF) |
| 7 | | Addition and subtraction modes number (AS1~AS4) |
Symbol / Description — PDF page 474
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Symbol | Description |
| 2 | | Calculation result : RESULT |
| 3 | | Multiplier V1(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 4 | | Multiplier V2(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 5 | | Divisor V3(AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V8, constant ) |
| 6 | | Coil output of error signal(M1~MF) |
| 7 | | Multiplication and division modes number (MD1~ MD4) |
Manual — Modbus connections and CN6 pinout — page 475
Manual reference: physical PDF page 475. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.6 Modbus Protocol Descriptions
4.6.1 Communication Connection and Data Frame The inverter can communicate with a PC or PLC via RS485 or RS232 using the Modbus RTU or Modbus ACSII protocol. The maximum frame length is 80 bytes.
Network Connection
** Terminate the communications line with a (120 ohm, 1/4 watt) resistor at both ends. CN6 Pin out
For RS-485 communication use pin 1 or pin 3 for S (+) and pin 2 or pin 6 for S (-)
Network connection illustration:Controller(PLC/HMIorPC)RS-485Interface;A510s NodeAddress01,02,03,FE eachCN6 S(+) S(−);120Ω1/4w resistor drawn at each end. Dashed intermediate nodes. Label and source relation transcription only, not independently validated wiring.
CN6 pinout illustration:connector outline with top tab;visible pin numbers left-to-right8,7,6,5,4,3,2,1. Adjacent table retains each signal association; no viewing orientation inferred.
Modbus connections and CN6 pinout
PIN / Signal — PDF page 475
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | PIN | Signal | PIN | Signal |
| 2 | 1 | RS-485 S+ signal | 5 | Tx signal |
| 3 | 2 | RS-485 S- signal | 6 | RS-485 S- signal |
| 4 | 3 | RS-485 S+ signal | 7 | VCC of isolated 5V power supply |
| 5 | 4 | Rx signal | 8 | GND of isolated 5V power supply |
Manual — ASCII and RTU frames and node address — page 476
Manual reference: physical PDF page 476. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Data Format Frame
Data Frame for ASCII Mode
Data Frame for RTU Mode
Master (PLC etc.) sends request to follower (inverter), and the follower sends a response to the master (PC, PLC). The data received is illustrated here.
The data length varies depending on the command (Function).
Node Address Function Code
DATA CRC CHECK Signal Interval
** The inverter response time is 10ms. Node Address 00H: Broadcast to all the drivers 01H: to the No. 01 inverter 0FH: to the No.15 inverter 10H: to the No.16 inverter and so on...., max to No.31 (1FH)
ASCII and RTU frames and node address
STX(3AH) / Start Bit = 3AH — PDF page 476
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | STX(3AH) | Start Bit = 3AH |
| 2 | Node Address Hi | Communication Address(Station): 2-digit ASCII Code |
| 3 | Node Address Lo | Communication Address(Station): 2-digit ASCII Code |
| 4 | Function Hi | Function Code (command): 2-digit ASCII Code |
| 5 | Function Lo | Function Code (command): 2-digit ASCII Code |
| 6 | Command Start Address | Command Start byte: 4-digit ASCII Code |
| 7 | Command Start Address | Command Start byte: 4-digit ASCII Code |
| 8 | Command Start Address | Command Start byte: 4-digit ASCII Code |
| 9 | Command Start Address | Command Start byte: 4-digit ASCII Code |
| 10 | Data length | The length of the command: 4-digit ASCII Code |
| 11 | Data length | The length of the command: 4-digit ASCII Code |
| 12 | Data length | The length of the command: 4-digit ASCII Code |
| 13 | Data length | The length of the command: 4-digit ASCII Code |
| 14 | LRC Check Hi | LRC Check Code: 2-digit ASCII Code |
| 15 | LRC Check Lo | LRC Check Code: 2-digit ASCII Code |
| 16 | END Hi | End Byte: END Hi=CR(0DH), END Li = LF(0AH) |
| 17 | END Lo | End Byte: END Hi=CR(0DH), END Li = LF(0AH) |
Manual — Function codes and checksum procedures — page 477
Manual reference: physical PDF page 477. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Function Code 03H: Read the register contents 06H: Write a WORD to register 08H: Loop test 10H: Write several data to register (complex number register write)
Checksum Calculation
LRC ex. NODE ADDRESS 01H FUNCTION 03H COMMAND 01H 00H + DATA LENGTH 0AH ------------------------------------------ 0FH ------------ 2’s complement Checksum F1H CS (H) 46H (ASCII) CS (L) = 31H (ASCII) CRC CRC Check: CRC code covers the content from node address to DATA. Please calculate it according to the following methods. (1) Load a 16-bit register with FFFF hex (all1’s). Call this CRC register. (2) Exclusive OR the first 8-bit byte of the message, the low-order byte of the 16-bit CRC register, putting the result in the CRC register. (3) Shift the CRC register one bit to the right (toward the LSB), Zero-filling the MSB, Extract and examines the LSB. (4) (If the LSB was 0): Repeat Steps (3) (another shift) (If the LSB was 1): Exclusive OR the CRC register with the polynomial value A001 hex (1010 0000 0000 0001), putting the result in CRC register. (5) Repeat Steps (3) and (4) until 8 shifts been performed. When this is done, a complete 8-bit byte will be processed. (6) Repeat Steps (2) through (5) for next 8-bit byte of the message, Continue doing this until all bytes have been processed. The final content in the CRC register is the CRC value. When sending the CRC value, the Low-order byte should be sent firstly, then the High-order byte. For example, CRC value: 1241 Hex, the high-order byte should be set to 41hex and low-order byte 12hex.
Manual — CRC source code and exception tables — page 478
Manual reference: physical PDF page 478. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
CRC calculate program (C language): UWORD ch_sum (UBYTE long, UBYTE *rxdbuff ) { BYTE i = 0; UWORD wkg = 0xFFFF; while ( long-- ) { wkg ^= rxdbuff++; for ( i = 0 ; i < 8; i++ ) { if ( wkg & 0x0001 ) { wkg = ( wkg >> 1 ) ^ 0xa001; } else { wkg = wkg >> 1; } } } return( wkg ); }
During a communication error the drive will response with an Exception Code and send a message back to the main system consisting of a Function Code that is “ANDED (and 80h)” with 80 Hex.
CRC source code and exception tables
ASCII Mode — PDF page 478
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | ASCII Mode | ASCII Mode |
| 2 | STX | ‘:’ |
| 3 | Address | ‘0’ |
| 4 | Address | ‘1’ |
| 5 | Function | ‘8’ |
| 6 | Function | ‘6’ |
| 7 | Exception code | ‘5’ |
| 8 | Exception code | ‘1’ |
| 9 | LRC Check | ‘2’ |
| 10 | LRC Check | ‘8’ |
| 11 | END | ‘CR’ |
| 12 | END | ‘LF’ |
RTU Mode — PDF page 478
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | RTU Mode | RTU Mode | RTU Mode |
| 2 | Node Address | Node Address | 02H |
| 3 | Function | Function | 83H |
| 4 | Exception code | Exception code | 52H |
| 5 | CRC-16 | High | C0H |
| 6 | CRC-16 | Low | CDH |
Exception code / Content — PDF page 478
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Exception code | Content |
| 2 | 01 | Function code error |
| 3 | 02 | Register number error |
| 4 | 03 | DATA setting error |
| 5 | 04 | Register number is over 32 |
Manual — Command registers2500H–2511H — page 479
Manual reference: physical PDF page 479. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.6.2 Register and Data Format
Command Data (Read / Write)
Note: Write in zero for Not used BIT, do not write in data for the reserved register.
** If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz
2501H bit descriptions repeated below as separately bounded rows to avoid association loss from dashed rules; original parser regions retained.
Command registers2500H–2511H
Supplemental row-level transcription of dashed rules within2501H. Original complete table retained; no protocol correction.
Register No. / / Bit Content — PDF page 479
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Register No. | ⟦blank source cell⟧ | Bit Content | Bit Content | Bit Content |
| 2 | 2500H | ⟦blank source cell⟧ | Reserved | Reserved | Reserved |
| 3 | 2501H | ⟦blank source cell⟧ | Operation Signal | 0 1 2 3 | Operation Command 1 : Run 0 : Stop Reverse Command 1 : Reverse 0 : Forward External Fault 1 : Fault Fault Reset 1 : Reset |
| 4 | 2501H | ⟦blank source cell⟧ | Operation Signal | 4 5 6 7 8 9 A B C D E | Reserved Reserved Multi-function Comm S1 1 :“ON” Multi-function Comm S2 1 :“ON” Multi-function Comm S3 1 :“ON” Multi-function Comm S4 1 :“ON” Multi-function Comm S5 1 :“ON” Multi-function Comm S6 1 :“ON” Multi-function Comm S7 1 :“ON” Multi-function Comm S8 1 :“ON” Inverter mode 1 : “ON” |
| 5 | 2501H | ⟦blank source cell⟧ | Operation Signal | F | Torque Command set by Communication 1: “ON” |
| 6 | 2502H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | *Frequency Command (Unit: 0.01Hz) | *Frequency Command (Unit: 0.01Hz) |
| 7 | 2503H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Torque Command (+/-8192 corresponding to the rated torque +/-100%) | Torque Command (+/-8192 corresponding to the rated torque +/-100%) |
| 8 | 2504H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Speed limit (+/- 120 corresponding +/-120%) | Speed limit (+/- 120 corresponding +/-120%) |
| 9 | 2505H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) |
| 10 | 2506H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | AO2 (0 ~ 1000): Voltage (corresponding to 0.00~10.00V); Current ( corresponding to 4mA~20mA) | AO2 (0 ~ 1000): Voltage (corresponding to 0.00~10.00V); Current ( corresponding to 4mA~20mA) |
| 11 | 2507H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | DO | DO |
| 12 | 2508H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 13 | 2509H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 14 | 250AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 15 | 250BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 16 | 250CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 17 | 250DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 18 | 250EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 19 | 250FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved |
| 20 | 2510H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | G12-00 H-WORD | G12-00 H-WORD |
| 21 | 2511H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | G12-00 L-WORD | G12-00 L-WORD |
2501H Operation Signal / individually bounded bit rows — PDF page 479
| Source row | Bit (source) | Content (source) |
|---|---|---|
| 1 | 0 | Operation Command 1 : Run 0 : Stop |
| 2 | 1 | Reverse Command 1 : Reverse 0 : Forward |
| 3 | 2 | External Fault 1 : Fault |
| 4 | 3 | Fault Reset 1 : Reset |
| 5 | 4 | Reserved |
| 6 | 5 | Reserved |
| 7 | 6 | Multi-function Comm S1 1 :“ON” |
| 8 | 7 | Multi-function Comm S2 1 :“ON” |
| 9 | 8 | Multi-function Comm S3 1 :“ON” |
| 10 | 9 | Multi-function Comm S4 1 :“ON” |
| 11 | A | Multi-function Comm S5 1 :“ON” |
| 12 | B | Multi-function Comm S6 1 :“ON” |
| 13 | C | Multi-function Comm S7 1 :“ON” |
| 14 | D | Multi-function Comm S8 1 :“ON” |
| 15 | E | Inverter mode 1 : “ON” |
| 16 | F | Torque Command set by Communication 1: “ON” |
Manual — Read-only monitor registers2520H and2521H — page 480
Manual reference: physical PDF page 480. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Monitor Data (Read-only)
2521H table continues on481;blank printed error descriptions remain blank,not inferred.
Read-only monitor registers2520H and2521H
Register No. / / Bit Content — PDF page 480
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Register No. | ⟦blank source cell⟧ | Bit Content | Bit Content | Bit Content | Bit Content | Bit Content |
| 2 | 2520H | ⟦blank source cell⟧ | State Signal | 0 | Operation 1 : Run 0 : Stop | Operation 1 : Run 0 : Stop | Operation 1 : Run 0 : Stop |
| 3 | 2520H | ⟦blank source cell⟧ | State Signal | 1 | Direction 1 : Reverse 0 : Forward | Direction 1 : Reverse 0 : Forward | Direction 1 : Reverse 0 : Forward |
| 4 | 2520H | ⟦blank source cell⟧ | State Signal | 2 | Inverter ready 1 : ready 0 : unready | Inverter ready 1 : ready 0 : unready | Inverter ready 1 : ready 0 : unready |
| 5 | 2520H | ⟦blank source cell⟧ | State Signal | 3 | Fault 1 : Abnormal | Fault 1 : Abnormal | Fault 1 : Abnormal |
| 6 | 2520H | ⟦blank source cell⟧ | State Signal | 4 | Warning 1 :“ON” | Warning 1 :“ON” | Warning 1 :“ON” |
| 7 | 2520H | ⟦blank source cell⟧ | State Signal | 5 | Zero Speed 1 :“ON” | Zero Speed 1 :“ON” | Zero Speed 1 :“ON” |
| 8 | 2520H | ⟦blank source cell⟧ | State Signal | 6 | Is440V 1 :“ON” | Is440V 1 :“ON” | Is440V 1 :“ON” |
| 9 | 2520H | ⟦blank source cell⟧ | State Signal | 7 | Frequency Agree 1 :“ON” | Frequency Agree 1 :“ON” | Frequency Agree 1 :“ON” |
| 10 | 2520H | ⟦blank source cell⟧ | State Signal | 8 | Set Frequency Agree 1 :“ON” | Set Frequency Agree 1 :“ON” | Set Frequency Agree 1 :“ON” |
| 11 | 2520H | ⟦blank source cell⟧ | State Signal | 9 | Frequency Detection 1 1 :“ON” | Frequency Detection 1 1 :“ON” | Frequency Detection 1 1 :“ON” |
| 12 | 2520H | ⟦blank source cell⟧ | State Signal | A | Frequency Detection 2 1 :“ON” | Frequency Detection 2 1 :“ON” | Frequency Detection 2 1 :“ON” |
| 13 | 2520H | ⟦blank source cell⟧ | State Signal | B | Under Voltage 1 :“ON” | Under Voltage 1 :“ON” | Under Voltage 1 :“ON” |
| 14 | 2520H | ⟦blank source cell⟧ | State Signal | C | Baseblock 1 :“ON” | Baseblock 1 :“ON” | Baseblock 1 :“ON” |
| 15 | 2520H | ⟦blank source cell⟧ | State Signal | D | Freq Ref. not from Comm. 1 :“ON” | Freq Ref. not from Comm. 1 :“ON” | Freq Ref. not from Comm. 1 :“ON” |
| 16 | 2520H | ⟦blank source cell⟧ | State Signal | E | Seq. not from Comm. 1 :“ON” | Seq. not from Comm. 1 :“ON” | Seq. not from Comm. 1 :“ON” |
| 17 | 2520H | ⟦blank source cell⟧ | State Signal | F | Over Torque 1 :“ON” | Over Torque 1 :“ON” | Over Torque 1 :“ON” |
| 18 | 2521H | ⟦blank source cell⟧ | Error Description | 0 | ⟦blank source cell⟧ | 30 | ⟦blank source cell⟧ |
| 19 | 2521H | ⟦blank source cell⟧ | Error Description | 1 | UV | 31 | ⟦blank source cell⟧ |
| 20 | 2521H | ⟦blank source cell⟧ | Error Description | 2 | OC | 32 | ⟦blank source cell⟧ |
| 21 | 2521H | ⟦blank source cell⟧ | Error Description | 3 | OV | 33 | ⟦blank source cell⟧ |
| 22 | 2521H | ⟦blank source cell⟧ | Error Description | 4 | OH1 | 34 | ⟦blank source cell⟧ |
| 23 | 2521H | ⟦blank source cell⟧ | Error Description | 5 | OL1 | 35 | ⟦blank source cell⟧ |
| 24 | 2521H | ⟦blank source cell⟧ | Error Description | 6 | OL2 | 36 | ⟦blank source cell⟧ |
| 25 | 2521H | ⟦blank source cell⟧ | Error Description | 7 | OT | 37 | ⟦blank source cell⟧ |
| 26 | 2521H | ⟦blank source cell⟧ | Error Description | 8 | UT | 38 | CF07 |
| 27 | 2521H | ⟦blank source cell⟧ | Error Description | 9 | SC | 39 | ⟦blank source cell⟧ |
| 28 | 2521H | ⟦blank source cell⟧ | Error Description | 10 | Ground OC | 40 | ⟦blank source cell⟧ |
| 29 | 2521H | ⟦blank source cell⟧ | Error Description | 11 | Fuse broken | 41 | OLDOP |
| 30 | 2521H | ⟦blank source cell⟧ | Error Description | 12 | Input Phase Loss | 42 | ⟦blank source cell⟧ |
| 31 | 2521H | ⟦blank source cell⟧ | Error Description | 13 | Output Phase Loss | 43 | ⟦blank source cell⟧ |
| 32 | 2521H | ⟦blank source cell⟧ | Error Description | 14 | PG Overspeed | 44 | ⟦blank source cell⟧ |
| 33 | 2521H | ⟦blank source cell⟧ | Error Description | 15 | PG Open | 45 | ⟦blank source cell⟧ |
| 34 | 2521H | ⟦blank source cell⟧ | Error Description | 16 | PG Speed Deviation | 46 | ⟦blank source cell⟧ |
| 35 | 2521H | ⟦blank source cell⟧ | Error Description | 17 | External Fault 01 | 47 | SS1 |
| 36 | 2521H | ⟦blank source cell⟧ | Error Description | 18 | External Fault 02 | 48 | CF20 |
| 37 | 2521H | ⟦blank source cell⟧ | Error Description | 19 | External Fault 03 | 49 | RUN |
| 38 | 2521H | ⟦blank source cell⟧ | Error Description | 20 | External Fault 04 | 50 | OCA |
| 39 | 2521H | ⟦blank source cell⟧ | Error Description | 21 | External Fault 05 | 51 | OCD |
| 40 | 2521H | ⟦blank source cell⟧ | Error Description | 22 | External Fault 06 | 52 | OCC |
| 41 | 2521H | ⟦blank source cell⟧ | Error Description | 23 | External Fault 07 | 53 | CF08 |
| 42 | 2521H | ⟦blank source cell⟧ | Error Description | 24 | External Fault 08 | 54 | ⟦blank source cell⟧ |
| 43 | 2521H | ⟦blank source cell⟧ | Error Description | 25 | FB | 55 | PF (Protection Fault) |
| 44 | 2521H | ⟦blank source cell⟧ | Error Description | 26 | OPR | 56 | TOL (External Overload) |
| 45 | 2521H | ⟦blank source cell⟧ | Error Description | 27 | ⟦blank source cell⟧ | 57 | ⟦blank source cell⟧ |
Manual — Monitor register continuation2521H and2522H–252AH — page 481
Manual reference: physical PDF page 481. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Monitor register continuation2521H and2522H–252AH
/ 28 / CE / 58 — PDF page 481
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) | Physical column 12 (source headings retained in rows) | Physical column 13 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 28 | 28 | CE | CE | CE | 58 | 58 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 29 | 29 | STO | STO | STO | 59 | 59 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 30 | 30 | Over Torque 2 | Over Torque 2 | Over Torque 2 | 61 | 61 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 4 | 2522H | ⟦blank source cell⟧ | DI State | 0 | 0 | Terminal S1 | Terminal S1 | Terminal S1 | Terminal S1 | Terminal S1 | Terminal S1 | Terminal S1 | Terminal S1 |
| 5 | 2522H | ⟦blank source cell⟧ | DI State | 1 | 1 | Terminal S2 | Terminal S2 | Terminal S2 | Terminal S2 | Terminal S2 | Terminal S2 | Terminal S2 | Terminal S2 |
| 6 | 2522H | ⟦blank source cell⟧ | DI State | 2 | 2 | Terminal S3 | Terminal S3 | Terminal S3 | Terminal S3 | Terminal S3 | Terminal S3 | Terminal S3 | Terminal S3 |
| 7 | 2522H | ⟦blank source cell⟧ | DI State | 3 | 3 | Terminal S4 | Terminal S4 | Terminal S4 | Terminal S4 | Terminal S4 | Terminal S4 | Terminal S4 | Terminal S4 |
| 8 | 2522H | ⟦blank source cell⟧ | DI State | 4 | 4 | Terminal S5 | Terminal S5 | Terminal S5 | Terminal S5 | Terminal S5 | Terminal S5 | Terminal S5 | Terminal S5 |
| 9 | 2522H | ⟦blank source cell⟧ | DI State | 5 | 5 | Terminal S6 | Terminal S6 | Terminal S6 | Terminal S6 | Terminal S6 | Terminal S6 | Terminal S6 | Terminal S6 |
| 10 | 2522H | ⟦blank source cell⟧ | DI State | 6 | 6 | Terminal S7 | Terminal S7 | Terminal S7 | Terminal S7 | Terminal S7 | Terminal S7 | Terminal S7 | Terminal S7 |
| 11 | 2522H | ⟦blank source cell⟧ | DI State | 7 | 7 | Terminal S8 | Terminal S8 | Terminal S8 | Terminal S8 | Terminal S8 | Terminal S8 | Terminal S8 | Terminal S8 |
| 12 | 2522H | ⟦blank source cell⟧ | DI State | 8 | 8 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 13 | 2522H | ⟦blank source cell⟧ | DI State | 9 | 9 | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 14 | 2522H | ⟦blank source cell⟧ | DI State | A | A | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 15 | 2522H | ⟦blank source cell⟧ | DI State | B | B | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 16 | 2522H | ⟦blank source cell⟧ | DI State | C | C | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 17 | 2522H | ⟦blank source cell⟧ | DI State | D | D | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 18 | 2522H | ⟦blank source cell⟧ | DI State | E | E | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 19 | 2522H | ⟦blank source cell⟧ | DI State | F | F | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 20 | 2523H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) |
| 21 | 2524H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) |
| 22 | 2525H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved | Reserved |
| 23 | 2526H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) |
| 24 | 2527H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) |
| 25 | 2528H | ⟦blank source cell⟧ | Warning Description | 0 | No alarm | No alarm | 20 | EF4 | 40 | EF | EF | 60 | Reserved |
| 26 | 2528H | ⟦blank source cell⟧ | Warning Description | 1 | OV | OV | 21 | EF5 | 41 | Reserved | Reserved | 61 | RETRY |
| 27 | 2528H | ⟦blank source cell⟧ | Warning Description | 2 | UV | UV | 22 | EF6 | 42 | Reserved | Reserved | 62 | SE07 |
| 28 | 2528H | ⟦blank source cell⟧ | Warning Description | 3 | OL2 | OL2 | 23 | EF7 | 43 | RDP | RDP | 63 | SE08 |
| 29 | 2528H | ⟦blank source cell⟧ | Warning Description | 4 | OH2 | OH2 | 24 | EF8 | 44 | Reserved | Reserved | 64 | Reserved |
| 30 | 2528H | ⟦blank source cell⟧ | Warning Description | 5 | Reserved | Reserved | 25 | Reserved | 45 | OL1 | OL1 | 65 | OH1 |
| 31 | 2528H | ⟦blank source cell⟧ | Warning Description | 6 | OT | OT | 26 | CLB | 46 | HP_ER | HP_ER | 66 | FIRE |
| 32 | 2528H | ⟦blank source cell⟧ | Warning Description | 7 | Reserved | Reserved | 27 | Reserved | 47 | SE10 | SE10 | 67 | ES |
| 33 | 2528H | ⟦blank source cell⟧ | Warning Description | 8 | Reserved | Reserved | 28 | CT | 48 | 保留 | 保留 | 68 | STP1 |
| 34 | 2528H | ⟦blank source cell⟧ | Warning Description | 9 | UT | UT | 29 | USP | 49 | BB1 | BB1 | 69 | BDERR |
| 35 | 2528H | ⟦blank source cell⟧ | Warning Description | 10 | OS | OS | 30 | RDE | 50 | BB2 | BB2 | 70 | EPERR |
| 36 | 2528H | ⟦blank source cell⟧ | Warning Description | 11 | PGO | PGO | 31 | WRE | 51 | BB3 | BB3 | 71 | ADCER |
| 37 | 2528H | ⟦blank source cell⟧ | Warning Description | 12 | DEV | DEV | 32 | FB | 52 | BB4 | BB4 | 72 | Reserved |
| 38 | 2528H | ⟦blank source cell⟧ | Warning Description | 13 | CE | CE | 33 | VRYE | 53 | BB5 | BB5 | 73 | STP0 |
| 39 | 2528H | ⟦blank source cell⟧ | Warning Description | 14 | CALL | CALL | 34 | SE01 | 54 | BB6 | BB6 | 74 | ENC |
| 40 | 2528H | ⟦blank source cell⟧ | Warning Description | 15 | Reserved | Reserved | 35 | SE02 | 55 | BB7 | BB7 | 75 | STP2 |
| 41 | 2528H | ⟦blank source cell⟧ | Warning Description | 16 | EF0 | EF0 | 36 | SE03 | 56 | BB8 | BB8 | 76 | RUNER |
| 42 | 2528H | ⟦blank source cell⟧ | Warning Description | 17 | EF1 | EF1 | 37 | Reserved | 57 | Reserved | Reserved | 77 | LOC |
| 43 | 2528H | ⟦blank source cell⟧ | Warning Description | 18 | EF2 | EF2 | 38 | SE05 | 58 | Reserved | Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 44 | 2528H | ⟦blank source cell⟧ | Warning Description | 19 | EF3 | EF3 | 39 | HPERR | 59 | Reserved | Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 45 | 2529H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Digital Output State | Digital Output State | Digital Output State | Digital Output State | Digital Output State | Digital Output State | Digital Output State | Digital Output State | Digital Output State | Digital Output State |
| 46 | 252AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) |
Manual — Monitor registers252BH–252FH and resolution note — page 482
Manual reference: physical PDF page 482. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: Write in zero for Not used BIT, do not write in data for the reserved register. * If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz
Monitor registers252BH–252FH and resolution note
252BH / / AO2 (0 ~ 1000): Voltage (corresponding to 0.00~10.00V); Current (corresponding to 4mA~20mA) — PDF page 482
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | 252BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | AO2 (0 ~ 1000): Voltage (corresponding to 0.00~10.00V); Current (corresponding to 4mA~20mA) |
| 2 | 252CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Analog Input 1 (0.1%) |
| 3 | 252DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Analog Input 2 (0.1%) |
| 4 | 252EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | Reserved |
| 5 | 252FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | L510(s)/ E510(s)/ A510(s)/ F510 Check |
Manual — Read holding register03H examples — page 483
Manual reference: physical PDF page 483. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Read Holding Register [03H]
Read consecutive holding registers. The address of the first holding register is specified in the protocol Example: Read frequency command from the inverter with node address 1. ASCII Mode Command Message Response Message (Normal) Response Message (Error)
RTU Mode Command Message Response Message (Normal) Response Message (Error)
Read holding register03H examples / ASCII / Command Message
Read holding register03H examples / ASCII / Response Message Normal
Read holding register03H examples / ASCII / Response Message Error
Read holding register03H examples / RTU / Command Message
Read holding register03H examples / RTU / Response Message Normal
Read holding register03H examples / RTU / Response Message Error
ASCII / Command Message / 3AH / STX — PDF page 483
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 30H | Function |
| 5 | 33H | Function |
| 6 | 30H | Starting Register |
| 7 | 31H | Starting Register |
| 8 | 32H | Starting Register |
| 9 | 33H | Starting Register |
| 10 | 30H | Number of Registers |
| 11 | 30H | Number of Registers |
| 12 | 30H | Number of Registers |
| 13 | 31H | Number of Registers |
| 14 | ? | LRC CHECK |
| 15 | ? | LRC CHECK |
| 16 | 0DH | END |
| 17 | 0AH | END |
ASCII / Response Message Normal / 3AH / STX — PDF page 483
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 30H | Function |
| 5 | 33H | Function |
| 6 | 30H | Data Length |
| 7 | 32H | Data Length |
| 8 | 31H | Initial Save Register |
| 9 | 37H | Initial Save Register |
| 10 | 37H | Initial Save Register |
| 11 | 30H | Initial Save Register |
| 12 | ? | LRC CHECK |
| 13 | ? | LRC CHECK |
| 14 | 0DH | END |
| 15 | 0AH | END |
ASCII / Response Message Error / 3AH / STX — PDF page 483
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 38H | Function |
| 5 | 33H | Function |
| 6 | 30H | Exception code |
| 7 | 34H | Exception code |
| 8 | 34H | LRC CHECK |
| 9 | 30H | LRC CHECK |
| 10 | 0DH | END |
| 11 | 0AH | END |
RTU / Command Message / Node Address / 01 H — PDF page 483
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01 H |
| 2 | Function | Function | 03H |
| 3 | Starting Register | High | 0CH |
| 4 | Starting Register | Low | 10H |
| 5 | Number of Registers | High | 00H |
| 6 | Number of Registers | Low | 01H |
| 7 | CRC-16 | High | 86H |
| 8 | CRC-16 | Low | 9FH |
RTU / Response Message Normal / Node Address / 01H — PDF page 483
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 03H |
| 3 | Data Length | Data Length | 02H |
| 4 | Initial Save Register | High | 17H |
| 5 | Initial Save Register | Low | 70H |
| 6 | CRC-16 | High | B6H |
| 7 | CRC-16 | Low | 50H |
RTU / Response Message Error / Node Address / 01H — PDF page 483
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 83H |
| 3 | Exception code | Exception code | 04H |
| 4 | CRC-16 | High | 40H |
| 5 | CRC-16 | Low | F3H |
Manual — Loopback08H examples — page 484
Manual reference: physical PDF page 484. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Loop back test [08H]
Check the communication between the master and the follower (inverter). The data used can be arbitrary. ASCII Mode Command Message Response Message (Normal) Response Message (Error)
RTU Mode Command Message Response Message (Normal) Response Message (Error)
Loopback08H examples / ASCII / Command Message
Loopback08H examples / ASCII / Response Message Normal
Loopback08H examples / ASCII / Response Message Error
Loopback08H examples / RTU / Command Message
Loopback08H examples / RTU / Response Message Normal
Loopback08H examples / RTU / Response Message Error
ASCII / Command Message / 3AH / STX — PDF page 484
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 30H | Function |
| 5 | 38H | Function |
| 6 | 30H | Test Code |
| 7 | 30H | Test Code |
| 8 | 30H | Test Code |
| 9 | 30H | Test Code |
| 10 | 41H | DATA |
| 11 | 35H | DATA |
| 12 | 33H | DATA |
| 13 | 37H | DATA |
| 14 | 31H | LRC CHECK |
| 15 | 42H | LRC CHECK |
| 16 | 0DH | END |
| 17 | 0AH | END |
ASCII / Response Message Normal / 3AH / STX — PDF page 484
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 30H | Function |
| 5 | 38H | Function |
| 6 | 30H | Test Code |
| 7 | 30H | Test Code |
| 8 | 30H | Test Code |
| 9 | 30H | Test Code |
| 10 | 41H | DATA |
| 11 | 35H | DATA |
| 12 | 33H | DATA |
| 13 | 37H | DATA |
| 14 | 31H | LRC CHECK |
| 15 | 42H | LRC CHECK |
| 16 | 0DH 0AH | END |
ASCII / Response Message Error / 3AH / STX — PDF page 484
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 38H | Function |
| 5 | 38H | Function |
| 6 | 30H | Exception code |
| 7 | 33H | Exception code |
| 8 | 30H | LRC CHECK |
| 9 | 36H | LRC CHECK |
| 10 | 0DH | END |
| 11 | 0AH | END |
RTU / Command Message / Node Address / 01 H — PDF page 484
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01 H |
| 2 | Function | Function | 08H |
| 3 | Test Code | High | 00H |
| 4 | Test Code | Low | 00H |
| 5 | DATA | High | A5H |
| 6 | DATA | Low | 37H |
| 7 | CRC-16 | High | DAH |
| 8 | CRC-16 | Low | 8DH |
RTU / Response Message Normal / Node Address / 01H — PDF page 484
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 08H |
| 3 | Test Code | High | 00H |
| 4 | Test Code | Low | 00H |
| 5 | DATA | High | A5H |
| 6 | DATA | Low | 37H |
| 7 | CRC-16 | High | DAH |
| 8 | CRC-16 | Low | 8DH |
RTU / Response Message Error / Node Address / 01H — PDF page 484
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 88H |
| 3 | Exception code | Exception code | 03H |
| 4 | CRC-16 | High | 06H |
| 5 | CRC-16 | Low | 01H |
Manual — Write single06H examples — page 485
Manual reference: physical PDF page 485. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Write Single Holding Register [06H]
Write single holding register. The register address of the holding register is specified in the message.
Example: Write a 60.00Hz frequency command to node address 1.
ASCII Mode Command Message Response Message (Normal) Response Message (Error)
RTU Mode
Command Message Response Message (Normal) Response Message (Error)
Write single06H examples / ASCII / Command Message
Write single06H examples / ASCII / Response Message Normal
Write single06H examples / ASCII / Response Message Error
Write single06H examples / RTU / Command Message
Write single06H examples / RTU / Response Message Normal
Write single06H examples / RTU / Response Message Error
ASCII / Command Message / 3AH / STX — PDF page 485
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 30H | Function |
| 5 | 36H | Function |
| 6 | 32H | Starting Register |
| 7 | 35H | Starting Register |
| 8 | 30H | Starting Register |
| 9 | 32H | Starting Register |
| 10 | 31H | DATA |
| 11 | 37H | DATA |
| 12 | 37H | DATA |
| 13 | 30H | DATA |
| 14 | 34H | LRC CHECK |
| 15 | 42H | LRC CHECK |
| 16 | 0DH | END |
| 17 | 0AH | END |
ASCII / Response Message Normal / 3AH / STX — PDF page 485
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 30H | Function |
| 5 | 36H | Function |
| 6 | 32H | Starting Register |
| 7 | 35H | Starting Register |
| 8 | 30H | Starting Register |
| 9 | 32H | Starting Register |
| 10 | 31H | DATA |
| 11 | 37H | DATA |
| 12 | 37H | DATA |
| 13 | 30H | DATA |
| 14 | 34H | LRC CHECK |
| 15 | 42H | LRC CHECK |
| 16 | 0DH 0AH | END |
ASCII / Response Message Error / 3AH / STX — PDF page 485
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 38H | Function |
| 5 | 36H | Function |
| 6 | 30H | Exception code |
| 7 | 33H | Exception code |
| 8 | 30H | LRC CHECK |
| 9 | 32H | LRC CHECK |
| 10 | 0DH | END |
| 11 | 0AH | END |
RTU / Command Message / Node Address / 01 H — PDF page 485
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01 H |
| 2 | Function | Function | 06H |
| 3 | Start No | High | 25H |
| 4 | Start No | Low | 02H |
| 5 | DATA | High | 17H |
| 6 | DATA | Low | 70H |
| 7 | CRC-16 | High | 2DH |
| 8 | CRC-16 | Low | 12H |
RTU / Response Message Normal / Node Address / 01H — PDF page 485
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 06H |
| 3 | Start No | High | 25H |
| 4 | Start No | Low | 02H |
| 5 | DATA | High | 17H |
| 6 | DATA | Low | 70H |
| 7 | CRC-16 | High | 2DH |
| 8 | CRC-16 | Low | 12H |
RTU / Response Message Error / Node Address / 01H — PDF page 485
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 86H |
| 3 | Exception code | Exception code | 03H |
| 4 | CRC-16 | High | 02H |
| 5 | CRC-16 | Low | 61H |
Manual — Write multiple10H ASCII examples — page 486
Manual reference: physical PDF page 486. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Write Multiple Holding Register [10H]
Write multiple holding registers. The address of the first holding register is specified in the message. Example: Write a 60.00Hz frequency command to node address 1 and enable FWD run command. ASCII Mode Command Message Response Message (Normal) Response Message (Error)
- Number of bytes is register amount x 2
Write multiple10H ASCII examples / ASCII / Command Message
Write multiple10H ASCII examples / ASCII / Response Message Normal
Write multiple10H ASCII examples / ASCII / Response Message Error
ASCII / Command Message / 3AH / STX — PDF page 486
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 31H | Function |
| 5 | 30H | Function |
| 6 | 30H | Starting Register |
| 7 | 31H | Starting Register |
| 8 | 30H | Starting Register |
| 9 | 31H | Starting Register |
| 10 | 30H | Number of Registers |
| 11 | 30H | Number of Registers |
| 12 | 30H | Number of Registers |
| 13 | 32H | Number of Registers |
| 14 | 30H | Number of Bytes* |
| 15 | 34H | Number of Bytes* |
| 16 | 30H | DATA 1 |
| 17 | 30H | DATA 1 |
| 18 | 30H | DATA 1 |
| 19 | 31H | DATA 1 |
| 20 | 31H | DATA 2 |
| 21 | 37H | DATA 2 |
| 22 | 37H | DATA 2 |
| 23 | 30H | DATA 2 |
| 24 | 33H | LRC CHECK |
| 25 | 42H | LRC CHECK |
| 26 | 0DH | END |
| 27 | 0AH | END |
ASCII / Response Message Normal / 3AH / STX — PDF page 486
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 31H | Function |
| 5 | 30H | Function |
| 6 | 32H | Starting Register |
| 7 | 35H | Starting Register |
| 8 | 30H | Starting Register |
| 9 | 31H | Starting Register |
| 10 | 30H | Number of Registers |
| 11 | 30H | Number of Registers |
| 12 | 30H | Number of Registers |
| 13 | 32H | Number of Registers |
| 14 | 43H | LRC CHECK |
| 15 | 37H | LRC CHECK |
| 16 | 0DH | END |
| 17 | 0AH | END |
ASCII / Response Message Error / 3AH / STX — PDF page 486
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 3AH | STX |
| 2 | 30H | Node Address |
| 3 | 31H | Node Address |
| 4 | 39H | Function |
| 5 | 30H | Function |
| 6 | 30H | Exception code |
| 7 | 33H | Exception code |
| 8 | 30H | LRC CHECK |
| 9 | 43H | LRC CHECK |
| 10 | 0DH | END |
| 11 | 0AH | END |
Manual — Write multiple10H RTU examples — page 487
Manual reference: physical PDF page 487. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
RTU Mode Command Message Response Message (Normal) Response Message (Error)
- Data amount is register amount x 2
Write multiple10H RTU examples / RTU / Command Message
Write multiple10H RTU examples / RTU / Response Message Normal
Write multiple10H RTU examples / RTU / Response Message Error
RTU / Command Message / Node Address / 01H — PDF page 487
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 10H |
| 3 | Starting Register | High | 25H |
| 4 | Starting Register | Low | 01H |
| 5 | Number of Registers | High | 00H |
| 6 | Number of Registers | Low | 02H |
| 7 | Number of Bytes* | Number of Bytes* | 04H |
| 8 | DATA 1 | High | 00H |
| 9 | DATA 1 | Low | 01H |
| 10 | DATA 2 | High | 17H |
| 11 | DATA 2 | Low | 70H |
| 12 | CRC-16 | High | 60H |
| 13 | CRC-16 | Low | 27H |
RTU / Response Message Normal / Node Address / 01H — PDF page 487
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 10H |
| 3 | Starting Register | High | 25H |
| 4 | Starting Register | Low | 01H |
| 5 | Number of Registers | High | 00H |
| 6 | Number of Registers | Low | 02H |
| 7 | CRC-16 | High | 1BH |
| 8 | CRC-16 | Low | 04H |
RTU / Response Message Error / Node Address / 01H — PDF page 487
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Node Address | Node Address | 01H |
| 2 | Function | Function | 90H |
| 3 | Exception code | Exception code | 03H |
| 4 | CRC-16 | High | 0CH |
| 5 | CRC-16 | Low | 01H |
Manual — Parameter registers groups0and1 — page 488
Manual reference: physical PDF page 488. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
4.6.3 Parameter Data
Parameter registers groups0and1
Function / Register No — PDF page 488
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 0 | Group 0 | Group 0 | Group 0 | Group 1 | Group 1 |
| 3 | 0 – 00 | 0000H | 0 – 43 | 002BH | 1 – 00 | 0100H |
| 4 | 0 – 01 | 0001H | 0 – 44 | 002CH | 1 – 01 | 0101H |
| 5 | 0 – 02 | 0002H | 0 – 45 | 002DH | 1 – 02 | 0102H |
| 6 | 0 – 03 | 0003H | 0 – 46 | 002EH | 1 – 03 | 0103H |
| 7 | 0 – 04 | 0004H | 0 – 47 | 002FH | 1 – 04 | 0104H |
| 8 | 0 – 05 | 0005H | 0 – 48 | 0030H | 1 – 05 | 0105H |
| 9 | 0 – 06 | 0006H | 0 – 49 | 0031H | 1 – 06 | 0106H |
| 10 | 0 – 07 | 0007H | 0 – 50 | 0032H | 1 – 07 | 0107H |
| 11 | 0 – 08 | 0008H | 0 – 51 | 0033H | 1 – 08 | 0108H |
| 12 | 0 – 09 | 0009H | 0 – 52 | 0034H | 1 – 09 | 0109H |
| 13 | 0 – 10 | 000AH | 0 – 53 | 0035H | 1 – 10 | 010AH |
| 14 | 0 – 11 | 000BH | 0 – 54 | 0036H | 1 – 11 | 010BH |
| 15 | 0 – 12 | 000CH | 0 – 55 | 0037H | 1 – 12 | 010CH |
| 16 | 0 – 13 | 000DH | 0 – 56 | 0038H | 1 – 13 | 010DH |
| 17 | 0 – 14 | 000EH | 0 – 57 | 0039H | 1 – 14 | 010EH |
| 18 | 0 – 15 | 000FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 15 | 010FH |
| 19 | 0 – 16 | 0010H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 16 | 0110H |
| 20 | 0 – 17 | 0011H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 17 | 0111H |
| 21 | 0 – 18 | 0012H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 18 | 0112H |
| 22 | 0 – 19 | 0013H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 19 | 0113H |
| 23 | 0 – 20 | 0014H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 20 | 0114H |
| 24 | 0 – 21 | 0015H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 21 | 0115H |
| 25 | 0 – 22 | 0016H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 22 | 0116H |
| 26 | 0 – 23 | 0017H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 23 | 0117H |
| 27 | 0 – 24 | 0018H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 24 | 0118H |
| 28 | 0 – 25 | 0019H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 25 | 0119H |
| 29 | 0 – 26 | 001AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 1 – 26 | 011AH |
| 30 | 0 – 27 | 001BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 31 | 0 – 28 | 001CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 32 | 0 – 29 | 001DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 33 | 0 – 30 | 001EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | 0 – 31 | 001FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | 0 – 32 | 0020H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 36 | 0 – 33 | 0021H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 37 | 0 – 34 | 0022H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 38 | 0 – 35 | 0023H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 39 | 0 – 36 | 0024H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 40 | 0 – 37 | 0025H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 41 | 0 – 38 | 0026H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 42 | 0 – 39 | 0027H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 43 | 0 – 40 | 0028H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 44 | 0 – 41 | 0029H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 45 | 0 – 42 | 002AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Parameter registers groups2through4 — page 489
Manual reference: physical PDF page 489. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups2through4
Function / Register No — PDF page 489
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 2 | Group 2 | Group 3 | Group 3 | Group 3 | Group 3 | Group 4 | Group 4 |
| 3 | 2 – 00 | 0200H | 3 – 00 | 0300H | 3 – 43 | 032BH | 4 – 00 | 0400H |
| 4 | 2 – 01 | 0201H | 3 – 01 | 0301H | 3 – 44 | 032CH | 4 – 01 | 0401H |
| 5 | 2 – 02 | 0202H | 3 – 02 | 0302H | 3 – 45 | 032DH | 4 – 02 | 0402H |
| 6 | 2 – 03 | 0203H | 3 – 03 | 0303H | 3 – 46 | 032EH | 4 – 03 | 0403H |
| 7 | 2 – 04 | 0204H | 3 – 04 | 0304H | 3 – 47 | 032FH | 4 – 04 | 0404H |
| 8 | 2 – 05 | 0205H | 3 – 05 | 0305H | 3 – 48 | 0330H | 4 – 05 | 0405H |
| 9 | 2 – 06 | 0206H | 3 – 06 | 0306H | 3 – 49 | 0331H | 4 – 06 | 0406H |
| 10 | 2 – 07 | 0207H | 3 – 07 | 0307H | 3 – 50 | 0332H | 4 – 07 | 0407H |
| 11 | 2 – 08 | 0208H | 3 – 08 | 0308H | 3 – 51 | 0333H | 4 – 08 | 0408H |
| 12 | 2 – 09 | 0209H | 3 – 09 | 0309H | 3 – 52 | 0334H | 4 – 09 | 0409H |
| 13 | 2 – 10 | 020AH | 3 – 10 | 030AH | 3 – 53 | 0335H | 4 – 10 | 040AH |
| 14 | 2 – 11 | 020BH | 3 – 11 | 030BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 11 | 040BH |
| 15 | 2 – 12 | 020CH | 3 – 12 | 030CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 12 | 040CH |
| 16 | 2 – 13 | 020DH | 3 – 13 | 030DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 13 | 040DH |
| 17 | 2 – 14 | 020EH | 3 – 14 | 030EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 14 | 040EH |
| 18 | 2 – 15 | 020FH | 3 – 15 | 030FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 15 | 040FH |
| 19 | 2 – 16 | 0210H | 3 – 16 | 0310H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 16 | 0410H |
| 20 | 2 – 17 | 0211H | 3 – 17 | 0311H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 17 | 0411H |
| 21 | 2 – 18 | 0212H | 3 – 18 | 0312H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 18 | 0412H |
| 22 | 2 – 19 | 0213H | 3 – 19 | 0313H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 19 | 0413H |
| 23 | 2 – 20 | 0214H | 3 – 20 | 0314H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 4 – 20 | 0414H |
| 24 | 2 – 21 | 0215H | 3 – 21 | 0315H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 25 | 2 – 22 | 0216H | 3 – 22 | 0316H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 26 | 2 – 23 | 0217H | 3 – 23 | 0317H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 27 | 2 – 24 | 0218H | 3 – 24 | 0318H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 28 | 2 – 25 | 0219H | 3 – 25 | 0319H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 29 | 2 – 26 | 021AH | 3 – 26 | 031AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 30 | 2 – 27 | 021BH | 3 – 27 | 031BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 31 | 2 – 28 | 021CH | 3 – 28 | 031CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 32 | 2 – 29 | 021DH | 3 – 29 | 031DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 33 | 2 – 30 | 021EH | 3 – 30 | 031EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | 2 – 31 | 021FH | 3 – 31 | 031FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | 2 – 32 | 0220H | 3 – 32 | 0320H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 36 | 2 – 33 | 0221H | 3 – 33 | 0321H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 37 | 2 – 34 | 0222H | 3 – 34 | 0322H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 38 | 2 – 35 | 0223H | 3 – 35 | 0323H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 39 | 2 – 36 | 0224H | 3 – 36 | 0324H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 40 | 2 – 37 | 0225H | 3 – 37 | 0325H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 41 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 3 – 38 | 0326H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 42 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 3 – 39 | 0327H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 43 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 3 – 40 | 0328H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 44 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 3 – 41 | 0329H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 3 – 42 | 032AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Parameter registers groups5and6 — page 490
Manual reference: physical PDF page 490. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups5and6
Function / Register No — PDF page 490
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 5 | Group 5 | Group 5 | Group 5 | Group 6 | Group 6 | Group 6 | Group 6 |
| 3 | 5 – 00 | 0500H | 5 – 33 | 0521H | 6 – 00 | 0600H | 6 – 33 | 0621H |
| 4 | 5 – 01 | 0501H | 5 – 34 | 0522H | 6 – 01 | 0601H | 6 – 34 | 0622H |
| 5 | 5 – 02 | 0502H | 5 – 35 | 0523H | 6 – 02 | 0602H | 6 – 35 | 0623H |
| 6 | 5 – 03 | 0503H | 5 – 36 | 0524H | 6 – 03 | 0603H | 6 – 36 | 0624H |
| 7 | 5 – 04 | 0504H | 5 – 37 | 0525H | 6 – 04 | 0604H | 6 – 37 | 0625H |
| 8 | 5 – 05 | 0505H | 5 – 38 | 0526H | 6 – 05 | 0605H | 6 – 38 | 0626H |
| 9 | 5 – 06 | 0506H | 5 – 39 | 0527H | 6 – 06 | 0606H | 6 – 39 | 0627H |
| 10 | 5 – 07 | 0507H | 5 – 40 | 0528H | 6 – 07 | 0607H | 6 – 40 | 0628H |
| 11 | 5 – 08 | 0508H | 5 – 41 | 0529H | 6 – 08 | 0608H | 6 – 41 | 0629H |
| 12 | 5 – 09 | 0509H | 5 – 42 | 052AH | 6 – 09 | 0609H | 6 – 42 | 062AH |
| 13 | 5 – 10 | 050AH | 5 – 43 | 052BH | 6 – 10 | 060AH | 6 – 43 | 062BH |
| 14 | 5 – 11 | 050BH | 5 – 44 | 052CH | 6 – 11 | 060BH | 6 – 44 | 062CH |
| 15 | 5 – 12 | 050CH | 5 – 45 | 052DH | 6 – 12 | 060CH | 6 – 45 | 062DH |
| 16 | 5 – 13 | 050DH | 5 – 46 | 052EH | 6 – 13 | 060DH | 6 – 46 | 062EH |
| 17 | 5 – 14 | 050EH | 5 – 47 | 052FH | 6 – 14 | 060EH | 6 – 47 | 062FH |
| 18 | 5 – 15 | 050FH | 5 – 48 | 0530H | 6 – 15 | 060FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 19 | 5 – 16 | 0510H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 16 | 0610H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 20 | 5 – 17 | 0511H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 17 | 0611H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 21 | 5 – 18 | 0512H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 18 | 0612H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 22 | 5 – 19 | 0513H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 19 | 0613H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 23 | 5 – 20 | 0514H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 20 | 0614H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 24 | 5 – 21 | 0515H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 21 | 0615H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 25 | 5 – 22 | 0516H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 22 | 0616H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 26 | 5 – 23 | 0517H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 23 | 0617H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 27 | 5 – 24 | 0518H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 24 | 0618H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 28 | 5 – 25 | 0519H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 25 | 0619H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 29 | 5 – 26 | 051AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 26 | 061AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 30 | 5 – 27 | 051BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 27 | 061BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 31 | 5 – 28 | 051CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 28 | 061CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 32 | 5 – 29 | 051DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 29 | 061DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 33 | 5 – 30 | 051EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 30 | 061EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | 5 – 31 | 051FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 31 | 061FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | 5 – 32 | 0520H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 6 – 32 | 0620H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Parameter registers groups7and8 — page 491
Manual reference: physical PDF page 491. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups7and8
Function / Register No — PDF page 491
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 7 | Group 7 | Group 7 | Group 7 | Group 8 | Group 8 | Group 8 | Group 8 |
| 3 | 7 – 00 | 0700H | 7 – 41 | 0729H | 8 – 00 | 0800H | 8 – 41 | 0829H |
| 4 | 7 – 01 | 0701H | 7 – 42 | 072AH | 8 – 01 | 0801H | 8 – 42 | 082AH |
| 5 | 7 – 02 | 0702H | 7 – 43 | 072BH | 8 – 02 | 0802H | 8 – 43 | 082BH |
| 6 | 7 – 03 | 0703H | 7 – 44 | 072CH | 8 – 03 | 0803H | 8 – 44 | 082CH |
| 7 | 7 – 04 | 0704H | 7 – 45 | 072DH | 8 – 04 | 0804H | 8 – 45 | 082DH |
| 8 | 7 – 05 | 0705H | 7 – 46 | 072EH | 8 – 05 | 0805H | 8 – 46 | 082EH |
| 9 | 7 – 06 | 0706H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 06 | 0806H | 8 – 47 | 082FH |
| 10 | 7 – 07 | 0707H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 07 | 0807H | 8 – 48 | 0830H |
| 11 | 7 – 08 | 0708H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 08 | 0808H | 8 – 49 | 0831H |
| 12 | 7 – 09 | 0709H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 09 | 0809H | 8 – 50 | 0832H |
| 13 | 7 – 10 | 070AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 10 | 080AH | 8 – 51 | 0833H |
| 14 | 7 – 11 | 070BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 11 | 080BH | 8 – 52 | 0834H |
| 15 | 7 – 12 | 070CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 12 | 080CH | 8 – 53 | 0835H |
| 16 | 7 – 13 | 070DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 13 | 080DH | 8 – 54 | 0836H |
| 17 | 7 – 14 | 070EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 14 | 080EH | 8 – 55 | 0837H |
| 18 | 7 – 15 | 070FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 15 | 080FH | 8 – 56 | 0838H |
| 19 | 7 – 16 | 0710H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 16 | 0810H | 8 – 57 | 0839H |
| 20 | 7 – 17 | 0711H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 17 | 0811H | 8 – 58 | 083AH |
| 21 | 7 – 18 | 0712H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 18 | 0812H | 8 – 59 | 083BH |
| 22 | 7 – 19 | 0713H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 19 | 0813H | 8 – 60 | 083CH |
| 23 | 7 – 20 | 0714H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 20 | 0814H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 24 | 7 – 21 | 0715H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 21 | 0815H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 25 | 7 – 22 | 0716H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 22 | 0816H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 26 | 7 – 23 | 0717H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 23 | 0817H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 27 | 7 – 24 | 0718H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 24 | 0818H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 28 | 7 – 25 | 0719H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 25 | 0819H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 29 | 7 – 26 | 071AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 26 | 081AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 30 | 7 – 27 | 071BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 27 | 081BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 31 | 7 – 28 | 071CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 28 | 081CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 32 | 7 – 29 | 071DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 29 | 081DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 33 | 7 – 30 | 071EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 30 | 081EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | 7 – 31 | 071FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 31 | 081FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | 7 – 32 | 0720H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 32 | 0820H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 36 | 7 – 33 | 0721H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 33 | 0821H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 37 | 7 – 34 | 0722H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 34 | 0822H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 38 | 7 – 35 | 0723H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 35 | 0823H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 39 | 7 – 36 | 0724H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 36 | 0824H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 40 | 7 – 37 | 0725H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 37 | 0825H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 41 | 7 – 38 | 0726H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 38 | 0826H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 42 | 7 – 39 | 0727H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 39 | 0827H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 43 | 7 – 40 | 0728H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 – 40 | 0828H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Parameter registers groups9through11 — page 492
Manual reference: physical PDF page 492. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups9through11
Function / Register No — PDF page 492
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 9 | Group 9 | Group 10 | Group 10 | Group 10 | Group 10 | Group 11 | Group 11 |
| 3 | 9 – 00 | 0900H | 10 – 00 | 0A00H | 10 – 44 | 0A2CH | 11 – 00 | 0B00H |
| 4 | 9 – 01 | 0901H | 10 – 01 | 0A01H | 10 – 45 | 0A2DH | 11 – 01 | 0B01H |
| 5 | 9 – 02 | 0902H | 10 – 02 | 0A02H | 10 – 46 | 0A2EH | 11 – 02 | 0B02H |
| 6 | 9 – 03 | 0903H | 10 – 03 | 0A03H | 10 – 47 | 0A2FH | 11 – 03 | 0B03H |
| 7 | 9 – 04 | 0904H | 10 – 04 | 0A04H | 10 – 48 | 0A30H | 11 – 04 | 0B04H |
| 8 | 9 – 05 | 0905H | 10 – 05 | 0A05H | 10 – 49 | 0A31H | 11 – 05 | 0B05H |
| 9 | 9 – 06 | 0906H | 10 – 06 | 0A06H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 06 | 0B06H |
| 10 | 9 – 07 | 0907H | 10 – 07 | 0A07H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 07 | 0B07H |
| 11 | 9 – 08 | 0908H | 10 – 08 | 0A08H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 08 | 0B08H |
| 12 | 9 – 09 | 0909H | 10 – 09 | 0A09H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 09 | 0B09H |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 10 | 0A0AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 10 | 0B0AH |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 11 | 0A0BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 11 | 0B0BH |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 12 | 0A0CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 12 | 0B0CH |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 13 | 0A0DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 13 | 0B0DH |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 14 | 0A0EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 14 | 0B0EH |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 15 | 0A0FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 15 | 0B0FH |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 16 | 0A10H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 16 | 0B10H |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 17 | 0A11H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 17 | 0B11H |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 18 | 0A12H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 18 | 0B12H |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 19 | 0A13H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 19 | 0B13H |
| 23 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 20 | 0A14H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 20 | 0B14H |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 21 | 0A15H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 21 | 0B15H |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 22 | 0A16H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 22 | 0B16H |
| 26 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 23 | 0A17H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 23 | 0B17H |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 24 | 0A18H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 24 | 0B18H |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 25 | 0A19H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 25 | 0B19H |
| 29 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 26 | 0A1AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 26 | 0B1AH |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 27 | 0A1BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 27 | 0B1BH |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 28 | 0A1CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 28 | 0B1CH |
| 32 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 29 | 0A1DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 29 | 0B1DH |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 30 | 0A1EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 30 | 0B1EH |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 31 | 0A1FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 31 | 0B1FH |
| 35 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 32 | 0A20H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 - 32 | 0B20H |
| 36 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 33 | 0A21H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11– 33 | 0B21H |
| 37 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 34 | 0A22H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 34 | 0B22H |
| 38 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 35 | 0A23H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 35 | 0B23H |
| 39 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 36 | 0A24H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11– 36 | 0B24H |
| 40 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 37 | 0A25H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 37 | 0B25H |
| 41 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 38 | 0A26H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 38 | 0B26H |
| 42 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 39 | 0A27H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11– 39 | 0B27H |
| 43 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 40 | 0A28H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 40 | 0B28H |
| 44 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 41 | 0A29H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 41 | 0B29H |
| 45 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 42 | 0A2AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11– 42 | 0B2AH |
| 46 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 – 43 | 0A2BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 – 43 | 0B2BH |
Manual — Parameter registers groups11and12 — page 493
Manual reference: physical PDF page 493. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups11and12
Function / Register No — PDF page 493
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 11 | Group 11 | Group 12 | Group 12 | Group 12 | Group 12 |
| 3 | 11 – 44 | 0B2CH | 12 – 00 | High WORD: 2510H Low WORD: 2511H | 12 – 35 | 0C23H |
| 4 | 11 – 45 | 0B2DH | 12 – 01 | 0C01H | 12– 36 | 0C24H |
| 5 | 11 – 46 | 0B2EH | 12 – 02 | 0C02H | 12 – 37 | 0C25H |
| 6 | 11 – 47 | 0B2FH | 12 – 03 | 0C03H | 12 – 38 | 0C26H |
| 7 | 11 – 48 | 0B30H | 12 – 04 | 0C04H | 12– 39 | 0C27H |
| 8 | 11 – 49 | 0B31H | 12 – 05 | 0C05H | 12 – 40 | 0C28H |
| 9 | 11 - 50 | 0B32H | 12 – 06 | 0C06H | 12 – 41 | 0C29H |
| 10 | 11 - 51 | 0B33H | 12 – 07 | 0C07H | 12– 42 | 0C2AH |
| 11 | 11 – 52 | 0B34H | 12 – 08 | 0C08H | 12 – 43 | 0C2BH |
| 12 | 11 – 53 | 0B35H | 12 – 09 | 0C09H | 12 – 44 | 0C2CH |
| 13 | 11 – 54 | 0B36H | 12 – 10 | 0C0AH | 12– 45 | 0C2DH |
| 14 | 11 – 55 | 0B37H | 12 – 11 | 0C0BH | 12 – 46 | 0C2EH |
| 15 | 11 – 56 | 0B38H | 12 – 12 | 0C0CH | 12 – 47 | 0C2FH |
| 16 | 11 – 57 | 0B39H | 12 – 13 | 0C0DH | 12 – 48 | 0C30H |
| 17 | 11 – 58 | 0B3AH | 12 – 14 | 0C0EH | 12 – 49 | 0C31H |
| 18 | 11 – 59 | 0B3BH | 12 – 15 | 0C0FH | 12 - 50 | 0C32H |
| 19 | 11 – 60 | 0B3CH | 12 – 16 | 0C10H | 12 - 51 | 0C33H |
| 20 | 11 – 61 | 0B3DH | 12 – 17 | 0C11H | 12 – 52 | 0C34H |
| 21 | 11 – 62 | 0B3EH | 12 – 18 | 0C12H | 12 – 53 | 0C35H |
| 22 | 11 – 63 | 0B3FH | 12 – 19 | 0C13H | 12 – 54 | 0C36H |
| 23 | 11 – 64 | 0B40H | 12 – 20 | 0C14H | 12 – 55 | 0C37H |
| 24 | 11 – 65 | 0B41H | 12 – 21 | 0C15H | 12 – 56 | 0C38H |
| 25 | 11 – 66 | 0B42H | 12 – 22 | 0C16H | 12 – 57 | 0C39H |
| 26 | 11 – 67 | 0B43H | 12 – 23 | 0C17H | 12 – 58 | 0C3AH |
| 27 | 11 – 68 | 0B44H | 12 – 24 | 0C18H | 12 – 59 | 0C3BH |
| 28 | 11 – 69 | 0B45H | 12 – 25 | 0C19H | 12 – 60 | 0C3CH |
| 29 | 11 – 70 | 0B46H | 12 – 26 | 0C1AH | 12 – 61 | 0C3DH |
| 30 | 11 – 71 | 0B47H | 12 – 27 | 0C1BH | 12 – 62 | 0C3EH |
| 31 | 11 – 72 | 0B48H | 12 – 28 | 0C1CH | 12 – 63 | 0C3FH |
| 32 | 11 – 73 | 0B49H | 12 – 29 | 0C1DH | 12 – 64 | 0C40H |
| 33 | 11 – 74 | 0B4AH | 12 – 30 | 0C1EH | 12 – 65 | 0C41H |
| 34 | 11 – 75 | 0B4BH | 12 – 31 | 0C1FH | 12 – 66 | 0C42H |
| 35 | 11 – 76 | 0B4CH | 12 - 32 | 0C20H | 12 – 67 | 0C43H |
| 36 | 11 – 77 | 0B4DH | 12– 33 | 0C21H | 12 – 68 | 0C44H |
| 37 | 11 – 78 | 0B4EH | 12 – 34 | 0C22H | 12 – 69 | 0C45H |
Manual — Parameter registers groups12through14 — page 494
Manual reference: physical PDF page 494. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups12through14
Function / Register No — PDF page 494
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 12 | Group 12 | Group 13 | Group 13 | Group 13 | Group 13 | Group 14 | Group 14 |
| 3 | 12 – 70 | 0C46H | 13 – 00 | 0D00H | 13 – 35 | 0D23H | 14 – 00 | 0E00H |
| 4 | 12 – 71 | 0C47H | 13 – 01 | 0D01H | 13 – 36 | 0D24H | 14 – 01 | 0E01H |
| 5 | 12 – 72 | 0C48H | 13 – 02 | 0D02H | 13 – 37 | 0D25H | 14 – 02 | 0E02H |
| 6 | 12 – 73 | 0C49H | 13 – 03 | 0D03H | 13 – 38 | 0D26H | 14 – 03 | 0E03H |
| 7 | 12 – 74 | 0C4AH | 13 – 04 | 0D04H | 13 – 39 | 0D27H | 14 – 04 | 0E04H |
| 8 | 12 – 75 | 0C4BH | 13 – 05 | 0D05H | 13 – 40 | 0D28H | 14 – 05 | 0E05H |
| 9 | 12 – 76 | 0C4CH | 13 – 06 | 0D06H | 13 – 41 | 0D29H | 14 – 06 | 0E06H |
| 10 | 12 – 77 | 0C4DH | 13 – 07 | 0D07H | 13 – 42 | 0D2AH | 14 – 07 | 0E07H |
| 11 | 12 – 78 | 0C4EH | 13 – 08 | 0D08H | 13 – 43 | 0D2BH | 14 – 08 | 0E08H |
| 12 | 12 – 79 | 0C4FH | 13 – 09 | 0D09H | 13 – 44 | 0D2CH | 14 – 09 | 0E09H |
| 13 | 12 – 80 | 0C50H | 13 – 10 | 0D0AH | 13 – 45 | 0D2DH | 14 – 10 | 0E0AH |
| 14 | 12 – 81 | 0C51H | 13 – 11 | 0D0BH | 13 – 46 | 0D2EH | 14 – 11 | 0E0BH |
| 15 | 12 – 82 | 0C52H | 13 – 12 | 0D0CH | 13 – 47 | 0D2FH | 14 – 12 | 0E0CH |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 13 | 0D0DH | 13 – 48 | 0D30H | 14 – 13 | 0E0DH |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 14 | 0D0EH | 13 – 49 | 0D31H | 14 – 14 | 0E0EH |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 15 | 0D0FH | 13 – 50 | 0D32H | 14 – 15 | 0E0FH |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 16 | 0D10H | 13 – 46 | 0D2EH | 14 – 16 | 0E10H |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 17 | 0D11H | 13 – 47 | 0D2FH | 14 – 17 | 0E11H |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 18 | 0D12H | 13 – 48 | 0D30H | 14 – 18 | 0E12H |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 19 | 0D13H | 13 – 49 | 0D31H | 14 – 19 | 0E13H |
| 23 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 20 | 0D14H | 13 – 50 | 0D32H | 14 – 20 | 0E14H |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 21 | 0D15H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 21 | 0E15H |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 22 | 0D16H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 22 | 0E16H |
| 26 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 23 | 0D17H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 23 | 0E17H |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 24 | 0D18H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 24 | 0E18H |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 25 | 0D19H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 25 | 0E19H |
| 29 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 26 | 0D1AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 26 | 0E1AH |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 27 | 0D1BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 27 | 0E1BH |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 28 | 0D1CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 28 | 0E1CH |
| 32 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 29 | 0D1DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 29 | 0E1DH |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 30 | 0D1EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 30 | 0E1EH |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 31 | 0D1FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 31 | 0E1FH |
| 35 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 32 | 0D20H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 32 | 0E20H |
| 36 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 33 | 0D21H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 33 | 0E21H |
| 37 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 – 34 | 0D22H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 – 34 | 0E22H |
Manual — Parameter registers groups14through16 — page 495
Manual reference: physical PDF page 495. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups14through16
Function / Register No — PDF page 495
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 14 | Group 14 | Group 15 | Group 15 | Group 16 | Group 16 |
| 3 | 14 – 35 | 0E23H | 15 – 00 | 0F00H | 16 – 00 | 1000H |
| 4 | 14 – 36 | 0E24H | 15 – 01 | 0F01H | 16 – 01 | 1001H |
| 5 | 14 – 37 | 0E25H | 15 – 02 | 0F02H | 16 – 02 | 1002H |
| 6 | 14 – 38 | 0E26H | 15 – 03 | 0F03H | 16 – 03 | 1003H |
| 7 | 14 – 39 | 0E27H | 15 – 04 | 0F04H | 16 – 04 | 1004H |
| 8 | 14 – 40 | 0E28H | 15 – 05 | 0F05H | 16 – 05 | 1005H |
| 9 | 14 – 41 | 0E29H | 15 – 06 | 0F06H | 16 – 06 | 1006H |
| 10 | 14 – 42 | 0E2AH | 15 – 07 | 0F07H | 16– 07 | 1007H |
| 11 | 14 – 43 | 0E2BH | 15 – 08 | 0F08H | 16 – 08 | 1008H |
| 12 | 14 – 44 | 0E2CH | 15 – 09 | 0F09H | 16 – 09 | 1009H |
| 13 | 14 – 45 | 0E2DH | 15 – 10 | 0F0AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 14 | 14 – 46 | 0E2EH | 15 – 11 | 0F0BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 15 | 14 – 47 | 0E2FH | 15 – 12 | 0F0CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 13 | 0F0DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 14 | 0F0EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 15 | 0F0FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 16 | 0F10H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 17 | 0F11H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 18 | 0F12H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 19 | 0F13H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 23 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 20 | 0F14H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 21 | 0F15H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 22 | 0F16H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 26 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 23 | 0F17H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 24 | 0F18H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 25 | 0F19H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 29 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 26 | 0F1AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 27 | 0F1BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 28 | 0F1CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 32 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 29 | 0F1DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 30 | 0F1EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 31 | 0F1FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 – 32 | 0F20H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Parameter registers groups17through19 — page 496
Manual reference: physical PDF page 496. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups17through19
Function / Register No — PDF page 496
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 17 | Group 17 | Group 18 | Group 18 | Group 19 | Group 19 |
| 3 | 17 – 00 | 1100H | 18 – 00 | 1200H | 19 – 00 | 1300H |
| 4 | 17 – 01 | 1101H | 18 – 01 | 1201H | 19 – 01 | 1301H |
| 5 | 17 – 02 | 1102H | 18 – 02 | 1202H | 19 – 02 | 1302H |
| 6 | 17 – 03 | 1103H | 18 – 03 | 1203H | 19 – 03 | 1303H |
| 7 | 17 – 04 | 1104H | 18 – 04 | 1204H | 19 – 04 | 1304H |
| 8 | 17 – 05 | 1105H | 18 – 05 | 1205H | 19 – 05 | 1305H |
| 9 | 17 – 06 | 1106H | 18 – 06 | 1206H | 19 – 06 | 1306H |
| 10 | 17 – 07 | 1107H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 19– 07 | 1307H |
| 11 | 17 – 08 | 1108H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 12 | 17– 09 | 1109H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 13 | 17 – 10 | 110AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 14 | 17 – 11 | 110BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 15 | 17 – 12 | 110CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 16 | 17 – 13 | 110DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 17 | 17 – 14 | 110EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 23 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 26 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 29 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 32 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Parameter registers groups20and21 — page 497
Manual reference: physical PDF page 497. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups20and21
Function / Register No — PDF page 497
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 20 | Group 20 | Group 20 | Group 20 | Group 21 | Group 21 |
| 3 | 20 – 00 | 1400H | 20 – 37 | 1425H | 21 – 00 | 1500H |
| 4 | 20 – 01 | 1401H | 20 – 38 | 1426H | 21 – 01 | 1501H |
| 5 | 20 – 02 | 1402H | 20 – 39 | 1427H | 21 – 02 | 1502H |
| 6 | 20 – 03 | 1403H | 20 – 40 | 1428H | 21 – 03 | 1503H |
| 7 | 20 – 04 | 1404H | 20 – 41 | 1429H | 21 – 04 | 1504H |
| 8 | 20 – 05 | 1405H | 20 – 42 | 142AH | 21 – 05 | 1505H |
| 9 | 20 – 06 | 1406H | 20 – 43 | 142BH | 21 – 06 | 1506H |
| 10 | 20 – 07 | 1407H | 20 – 44 | 142CH | 21 – 07 | 1507H |
| 11 | 20 – 08 | 1408H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 08 | 1508H |
| 12 | 20 – 09 | 1409H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 09 | 1509H |
| 13 | 20 – 10 | 140AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 10 | 150AH |
| 14 | 20 – 11 | 140BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 11 | 150BH |
| 15 | 20 – 12 | 140CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 12 | 150CH |
| 16 | 20 – 13 | 140DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 13 | 150DH |
| 17 | 20 – 14 | 140EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 14 | 150EH |
| 18 | 20 – 15 | 140FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 15 | 150FH |
| 19 | 20 – 16 | 1410H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 16 | 1510H |
| 20 | 20 – 17 | 1411H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 17 | 1511H |
| 21 | 20 – 18 | 1412H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 18 | 1512H |
| 22 | 20 – 19 | 1413H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 19 | 1513H |
| 23 | 20 – 20 | 1414H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 20 | 1514H |
| 24 | 20 – 21 | 1415H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 21 | 1515H |
| 25 | 20 – 22 | 1416H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 22 | 1516H |
| 26 | 20 – 23 | 1417H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 23 | 1517H |
| 27 | 20 – 24 | 1418H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 24 | 1518H |
| 28 | 20 – 25 | 1419H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 25 | 1519H |
| 29 | 20 – 26 | 141AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 26 | 151AH |
| 30 | 20 – 27 | 141BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 27 | 151BH |
| 31 | 20 – 28 | 141CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 28 | 151CH |
| 32 | 20 – 29 | 141DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 29 | 151DH |
| 33 | 20 – 30 | 141EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 30 | 151EH |
| 34 | 20 – 31 | 141FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 31 | 151FH |
| 35 | 20 – 32 | 1420H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 – 32 | 1520H |
| 36 | 20 – 33 | 1421H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 37 | 20 – 34 | 1422H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 38 | 20 – 35 | 1423H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 39 | 20 – 36 | 1424H | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Parameter registers groups21and22 — page 498
Manual reference: physical PDF page 498. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter registers groups21and22
Function / Register No — PDF page 498
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Function | Register No | Function | Register No | Function | Register No |
| 2 | Group 21 | Group 21 | Group 22 | Group 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | 21 – 33 | 1521H | 22 – 00 | 1600H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 4 | 21 – 34 | 1522H | 22 – 01 | 1601H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 5 | 21 – 35 | 1523H | 22 – 02 | 1602H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 6 | 21 – 36 | 1524H | 22 – 03 | 1603H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 7 | 21 – 37 | 1525H | 22 – 04 | 1604H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 8 | 21 – 38 | 1526H | 22 – 05 | 1605H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 9 | 21 – 39 | 1527H | 22 – 06 | 1606H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 10 | 21 – 40 | 1528H | 22 – 07 | 1607H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 11 | 21 – 41 | 1529H | 22 – 08 | 1608H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 12 | 21 – 42 | 152AH | 22 – 09 | 1609H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 13 | 21 – 43 | 152BH | 22 – 10 | 160AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 11 | 160BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 12 | 160CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 13 | 160DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 14 | 160EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 15 | 160FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 16 | 1610H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 17 | 1611H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 18 | 1612H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 19 | 1613H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 23 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 20 | 1614H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 24 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 21 | 1615H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 25 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 22 | 1616H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 26 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 23 | 1617H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 27 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 24 | 1618H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 28 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 25 | 1619H | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 29 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 26 | 161AH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 27 | 161BH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 31 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 28 | 161CH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 32 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 29 | 161DH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 33 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 30 | 161EH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 34 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 – 31 | 161FH | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 35 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
Manual — Chapter5 motor rotation LED — page 499
Manual reference: physical PDF page 499. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 5 Check Motor Rotation and Direction
This test is to be performed solely from the inverter keypad. Apply power to the inverter after all the electrical connections have been made and protective covers have been re-attached.
Important: Motor rotation and direction only applies to standard AC motors with a base frequency of 60Hz. For 50Hz or other frequency AC motors please set the max frequency and base frequency in group 01 accordingly before running the motors. LED Keypad Display At this point, DO NOT RUN THE MOTOR, the LED keypad should display as shown below in Fig. 5.1 and all
LEDs are flashing. Next press the RUN key, all LEDs light on. See Fig 5.2. The motor should now be operating at low speed running in forward (clockwise) direction. The value shown in the screen will change from 000.00Hz to
005.00Hz. Next press STOP key to stop the motor.
Fig 5.1: LED Keypad (Stopped) Fig 5.2: LED Keypad (Running)
Figure5.1 LED Keypad(Stopped):FAULT,FWD,REV,SEQ,REF indicators;FWD red. Display has red5.00 and black inactive segment shapes;no leading black segments asserted as active digits. KeysFWD/REV,up,DSP/FUN,leftRESET,down,READ/ENTER,RUN,STOP. Source photo only.
Figure5.2 LED Keypad(Running):FWD red;red5.00 display and black inactive segment shapes;RUN indicator red. KeysFWD/REV,up,DSP/FUN,leftRESET,down,READ/ENTER,RUN,STOP. Sourcephotoonly;no assertion that inactive segments indicate active digits.
Manual — Chapter5 motor rotation LCD and safety notes — page 500
Manual reference: physical PDF page 500. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
LCD Keypad Display At this point, DO NOT RUN THE MOTOR, the LCD keypad should display as shown below in Fig. 5.3 and the speed reference 12-16=005.00Hz should be blinking at the parameter code “12-16”. Next press the RUN key, see Fig 5.4. The motor should now be operating at low speed running in forward (clockwise) direction. The parameter code 12-17 shown at the bottom left corner of the screen will change from 12-17=000.00Hz to 12-17=005.00Hz.
Next press STOP key to stop the motor.
Fig 5.3: LCD Keypad (Stopped) Fig 5.4: LCD Keypad (Running) Notes: - If the motor rotation is incorrect, power down the inverter.
- After the power has been turned OFF, wait at least ten minutes until the charge indicator
extinguishes completely before touching any wiring, circuit boards or components.
- Using Safety precaution, and referring to section 3.8 exchange any two of the three output
leads to the motor (U/T1, V/T2 and W/T3). After the wiring change, repeat this step and
recheck motor direction.
Figure5.3 LCD Keypad(Stopped):Monitor,FrefRef,12-16=005.00Hz;12-17=000.00Hz;12-18=0000.0A. FAULT,FWD,REV,SEQ,REF;FWD red;STOP red. ButtonsFWD/REV,up,DSP/FUN,leftRESET,down,READ/ENTER,RUN,STOP. No status inferred beyond caption.
Figure5.4 LCD Keypad(Running):Monitor,FrefRef,12-16=005.00Hz;12-17=005.00Hz;12-18=0001.2A. FAULT,FWD,REV,SEQ,REF;FWD red;RUN red. ButtonsFWD/REV,up,DSP/FUN,leftRESET,down,READ/ENTER,RUN,STOP. Sourcephotoonly.
Adjacent source context — repeated to preserve continuation:
Manual — Chapter6 speed reference selection — page 501
Manual reference: physical PDF page 501. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 6 Speed Reference Command Configuration
The inverter offers users several choices to set the speed reference source. The most commonly used methods are described in the next sections. Frequency reference command is selected with parameter 00-05. 00-05: Main Frequency Command (Frequency Source) This function sets the frequency command source. Setting Range: 0 to 5 To set parameter 00-05: - After power-up press the DSP/FUN key - Set Group 00 (Basic Fun), and select parameter -05 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key.
6.1 Reference from Keypad
LED Keypad: Use the </RESET, ▲ and ▼ keys to change the speed reference and then press the READ/ ENTER key. Refer to section 4.1.5 for more details. LCD Keypad: Press the READ/ ENTER key first and use the </RESET, ▲ and ▼ keys to change the speed reference.
Chapter6 speed reference selection
Adjacent source context — repeated to preserve continuation:
00-05 / Main Frequency Command Source Selection — PDF page 501
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-05 | Main Frequency Command Source Selection |
| 2 | Range | 0: Keypad 1: External control (analog) 2: Terminal command UP / DOWN 3: Communication control (RS-485) 4: Pulse input 5: Reserved 6: Reserved 7: AI2 Auxiliary Frequency 8: Manual Pulse Generator (MPG) |
Manual — External analog voltage and potentiometer diagrams — page 502
Manual reference: physical PDF page 502. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.2 Reference from External Analog Signal (0-10V / 4-20mA)
Analog Reference: 0 – 10 V (Setting 00-05 = 1)
Analog Reference: Potentiometer / Speed Pot (Setting 00-05 = 1)
AnalogReference0–10V(00-05=1) source diagram:upperterminalrowE,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2;lowerDO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. HighlightGND andAI1;blackCommon/0V,GNDlead atminus;redAnalogInputAI1lead atplus;0–10V;dashedshieldconnectedcontrolgroundterminal. ControlTerminals/UserTerminals. Source labelsanddrawnrelationsonly,notvalidatedwiring.
Potentiometer/SpeedPot(00-05=1)source diagram:sameupperrowE,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2;lowerDO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. Highlight+12V,GND,AI1. BlackCommon/0V,GND;red+12VDC,+12V;blueAnalogInputAI1towiper. Potentiometer1~5KOhm;Connectshieldtocontrolgroundterminal. Source illustration only.
Manual — Analog reference4–20mA — page 503
Manual reference: physical PDF page 503. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Connect shield to control ground terminal
Source diagram and labels retained; not a full installation procedure. No wiring geometry reconstructed. Factory-default claim applies to source SW2 setting, not every setting/model.
This main-manual terminal strip differs from safety-stop supplementPDF666; retain each source separately.
Literal source setting and polarity labels; diagram geometry remains original. No voltage substitution or extra numeric settings.
Source glyphDOG retained as printed; no forcedD0Gnormalisation. Two staggered rows are inventories, not column-aligned electrical pairs.
Analog-reference settings and labels — PDF page 503
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Reference | 4–20mA |
| 2 | Setting | 00-05=1 |
| 3 | Terminal heading | Control Terminals / User Terminals |
| 4 | Common label | Common,GND |
| 5 | Analog input label | Analog Input AI2 |
| 6 | Switch | SW2 |
| 7 | Switch positions | I; V |
| 8 | Printed switch instruction | Set switch SW2 to I (Factory Default) |
| 9 | Negative lead printed label | - |
| 10 | Positive lead printed label | + |
Terminal labels by source row — PDF page 503
| Source row | Source row | Labels left-to-right |
|---|---|---|
| 1 | Upper | E; DO2; 24VG; S2; S4; S6; S8; 24V; +12V; GND; AI1; AI2 |
| 2 | Lower | DO1; DOG; S1; S3; S5; S7; F1; F2; PI; AO1; AO2; E |
Manual — SerialRS485 speed reference — page 504
Manual reference: physical PDF page 504. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.3 Reference from Serial Communication RS485 (00-05=3)
To set the speed reference for the inverter via serial communication parameter 00-05 has be set to “3” for frequency command via serial communication. Default Communication Setting is: Address “1”, 9600 Bits/sec, 1 Start Bit, 1 Stop Bit, and No Parity The serial communication link function uses RS485 Modbus RTU protocol and allows for: 1) Monitoring (data monitoring, function data check). 2) Frequency setting. 3) Operation command (FWD, REV, and other commands for digital input). 4) Write function data. Frequency Reference Command Register Inverter Frequency Reference Register: 2502 (Hexadecimal) - Bit 0 – Bit 15: 0.00 ~ 599.00 Hz
RS485source diagram:CN6connectorpinlabels8,7,6,5,4,3,2,1lefttoright;Controlboardarrow;blueS−frompin2,redS+frompin1;CableShielddashed;RS485PortandRS485PLC/ComputerConnectionminusblueplusred. No inferred viewing orientation or independently validatedwiring.
Manual — RS485 frequency command examples — page 505
Manual reference: physical PDF page 505. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Examples:
Frequency Reference Command: 10.00 Hz (Inverter Node Address: 01) Command String (hexadecimal): 01 06 25 02 03 E8 23 B8
To set the frequency reference to 10.00, a value of ‘1000’ (03E8h) has to be send to the inverter.
Frequency Reference Command: 30.00 Hz (Inverter Node Address: 01) Command String (hexadecimal): 01 06 25 02 0B B8 24 44
To set the frequency reference to 30.00, a value of ‘3000’ (0BB8h) has to be send to the inverter.
Frequency Reference Command: 60.00 Hz (Inverter Node Address: 01) Command String (hexadecimal): 01 06 25 02 17 70 2D 12 To set the frequency reference to 60.00, a value of ‘6000’ (1770h) has to be send to the inverter
Note: The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to section 4.5 of the instruction manual for additional information.
Manual — Pulse input reference and scaling — page 506
Manual reference: physical PDF page 506. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.4 Reference from Pulse Input (00-05=4)
Set Pulse Input Setup as Frequency Reference Set parameter 00-05 to 4 and 03-30 to 0 to use the pulse input terminal PI as the frequency reference source. Next set the pulse input scaling (03-31), enter the pulse input frequency to match the maximum output frequency. Adjust the pulse input filter time in case interference or noise is encountered. Example: Pulse train input maximum 10 kHz, set parameter 03-31 to 10000 when maximum frequency is set to 60.0Hz.
Function selects source for the pulse input.
Pulse input scaling, 100% = Maximum pulse frequency.
Target value (03-03) in % = Pulse input frequency scaled to 100% based on maximum pulse frequency (O3-31) times the gain (03-32) + bias (03-33).
Pulseinputillustration:PIupperterminal,GNDlower,0Vground;Serialpulseinput(Internalresistence:3.89K);SpecificationLowInputLevel0.0to0.5V;HighInputLevel4.0to13.5V;Dutycycle(ON/OFF)30%to70%;PulseInputfrequencyrange50to32KHz exactlyasprinted. Squarewaveicon;no interpolated pulse timing.
Pulse input reference and scaling
03- 30 / Selection of Pulse Input — PDF page 506
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03- 30 | Selection of Pulse Input |
| 2 | Range | 0: General Pulse Input 1: PWM |
03-31 / Scale of pulse input — PDF page 506
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-31 | Scale of pulse input |
| 2 | Range | Depending on the setting of 03-30 03-30 = 0: 50~32000Hz 03-30 = 1:10~1000Hz |
03- 32 / Pulse input gain — PDF page 506
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03- 32 | Pulse input gain |
| 2 | Range | 0.0~1000.0 % |
03-33 / Pulse input bias — PDF page 506
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-33 | Pulse input bias |
| 2 | Range | -100.0~100.0 % |
03-34 / Pulse input filter time — PDF page 506
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 03-34 | Pulse input filter time |
| 2 | Range | 0.00~2.00 Sec |
Manual — 6.5 Two analog inputs and6.6 display units — page 507
Manual reference: physical PDF page 507. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
6.5 Reference from two Analog Inputs
Analog input AI1 is used as master frequency reference and analog input AI2 is used as auxiliary frequency reference. Analog Reference AI1: 0 – 10 V (Setting 00-05 = 1) Analog Reference AI2: 0 – 10 V (Setting 00-06 = 1, 04-05 = 1)
6.6 Change Frequency Unit from Hz to rpm
Enter the number of motor poles in 16-03 to change the display units from Hz to rpm.
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. Two analog inputs diagram:yellow GND,AI1,AI2;black Common/0V,GND and−;red Analog InputAI1 and+;blue Analog InputAI2 and+;0–10V. Control Terminals/UserTerminals;Connect shield to control ground terminal. Source labels only.
6.5 Two analog inputs and6.6 display units
AI1 – Analog Input 1 / AI2 – Analog Input 2 / 04-00 Setting (Default = 1) / Dipswitch SW2 (Default ‘V’) — PDF page 507
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | AI1 – Analog Input 1 | AI2 – Analog Input 2 | 04-00 Setting (Default = 1) | Dipswitch SW2 (Default ‘V’) |
| 2 | 0 ~ 10V | 0 ~ 10V | 0 | Set to ‘V’ |
| 3 | 0 ~ 10V | 4 ~ 20mA | 1 | Set to ‘I’ |
16-03 / Display unit — PDF page 507
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 16-03 | Display unit |
| 2 | Range | 0: Frequency display unit is Hz (Resolution is 0.01Hz) 1: Frequency display unit is % (Resolution is 0.01%) 2: Frequency display unit is rpm. 3~39: Reserved 40~9999: 100% is XXXX with no decimals (integer only) 10001~19999: 100% is XXX.X with 1 decimal 20001~29999: 100% is XX.XX with 2 decimals 30001~39999: 100% is X.XXX with 3 decimals |
Manual — 7 Operation method and keypad Run/Stop — page 508
Manual reference: physical PDF page 508. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 7 Operation Method Configuration (Run / Stop)
The inverter offers users several choices to run and stop from different sources. The most commonly used methods are described in the next sections. Operation command is selected with parameter 00-02. 00-02: Run Command Selection This function sets the frequency command source. Setting Range: 0 to 3 To set parameter 00-02: - After power-up press the DSP/FUN key - Set Group 00 (Basic Fun), and select parameter -02 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key.
7.1 Run/Stop from the LED/LCD Keypad (00-02=0)
Use the RUN key to run the drive in forward direction and the FWD/REV key to change the motor direction. (Note: to disable reverse direction set parameter 11-01 to 1) Press STOP key to stop the inverter. (Note: Stop method can be set with parameter 07-09, default is deceleration to stop).
Keypad source photo:Monitor,FrefRef,12-16=005.00Hz;12-17=000.00Hz;12-18=0000.0A. FAULT,FWD,REV,SEQ,REF;FWD red andSTOP red. ButtonsFWD/REV,up,DSP/FUN,leftRESET,down,READ/ENTER,RUN,STOP. Photo only, no actual operating-state validation.
7 Operation method and keypad Run/Stop
00-02 / Main Run Command Source Selection — PDF page 508
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-02 | Main Run Command Source Selection |
| 2 | Range | 0: Keypad control 1: External terminal control 2: Communication control (RS-485) 3: PLC |
Manual — 7.2 NPN permanent switch/contact — page 509
Manual reference: physical PDF page 509. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.2 Run/Stop from External Switch / Contact or Pushbutton
(00-02=1)
Use an external contact or switch to Run and Stop the inverter. Example: NPN wiring Permanent Switch / Contact
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. NPN permanent switch/contact:yellow24VG,S1;Common/24VG;Forward Command/FWD;Start/Stop Switch(Maintained);Control Terminals/User Terminals;Connect shield to control ground terminal. Diagram labels only.
Manual — 7.2 Momentary pushbuttons and three-wire settings — page 510
Manual reference: physical PDF page 510. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Momentary Contacts (Push Buttons) Use push button / momentary switch to Run and Stop the inverter. Set parameter 13-08 to 3, 5 or 7 for 3-wire program initialization, multi-function input terminal S1 is set to run operation, S2 for stop operation and S7 for forward/reverse command. 00-01 Operation Method = 1 03-07 Terminal S7 Function = 26
Note: Stop mode selection can be set with parameter 07-09, default is deceleration to stop.
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. Momentary contacts:yellow24VG,S2,S1,S7;Reverse direction when closed;START PUSH BUTTON(Momentary);STOP PUSHBUTTON(Momentary);Control Terminals/UserTerminals;Connect shield to control ground terminal. Source depicts wiring, no topology implementation inferred.
Manual — 7.3 RS485 Run/Stop source example — page 511
Manual reference: physical PDF page 511. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
7.3 Run/Stop from Serial Communication RS485 (00-02=3)
To control (Run/Stop) the inverter via serial communication parameter 00-02 has be set to either a “2” for communication control. Default Communication Setting is: Address “1”, 19200 Bits/sec, 1 Start Bit, 1 Stop Bit, and No Parity The serial communication link function uses RS485 Modbus RTU protocol and allows for: 1) Monitoring (data monitoring, function data check). 2) Frequency setting. 3) Operation command (FWD, REV, and other commands for digital input). 4) Write function data. Command Register Inverter Command Register: 2501 (Hexadecimal) Bit 0: Run Forward Bit 1: Run Reverse Bit 2 ~ Bit 15: Refer to the chapter XX of this manual
CN6 Control board connector numbered8,7,6,5,4,3,2,1 left to right. S−blue at2 andS+red at1;CableShield;RS485Port;RS485PLC/ComputerConnection−blue,+red. Diagram source labels retained, no wiring verification.
Manual — RS485 command string examples — page 512
Manual reference: physical PDF page 512. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Examples:
Run Forward Command (Inverter Node Address: 01) Command String (hexadecimal): 01 06 25 01 00 01 12 C6
Run Reverse Command (Inverter Node Address: 01) Command String (hexadecimal): 01 06 25 01 00 03 93 07
Stop Command (Inverter Node Address: 01)
Command String (hexadecimal): 01 06 25 01 00 00 D3 06
Note: The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to section 4.5 of the instruction manual for additional information.
Manual — 8.1 Motor nameplate settings02-05/02-01 — page 513
Manual reference: physical PDF page 513. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 8 Motor and Application Specific Settings
It is essential that before running the motor, the motor nameplate data matches the motor data in the inverter.
8.1 Set Motor Nameplate Data (02-01, 02-05)
02-05 Rated power of motor 1 The nominal motor rated capacity is set at the factory. Please verify that the motor name plate data matches the motor rated capacity shown in parameter 02-05. The setting should only be changed when driving a motor with a different capacity. Range: 0.00 to 600.00 kW (1HP = 0.746 kW) To set parameter 02-05: - After power-up press the DSP/FUN key - Set Group 02 (Motor Parameter), and select parameter -05 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key. Default values vary based on the inverter model. 02-01 Rated current of motor 1 The motor rated current is set at the factory based on the inverter model. Enter the motor rated current from the motor nameplate if it does not match the value shown in parameter 02-01. Setting range: 0.01 to 600.00A To set parameter 02-01: - After power-up press the DSP/FUN key - Set Group 02 (Motor Parameter), and select parameter -01 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key.
Manual — 8.2 Acceleration/deceleration00-14/00-15 — page 514
Manual reference: physical PDF page 514. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.2 Acceleration and Deceleration Time (00-14, 00-15)
Acceleration and Deceleration times directly control the system dynamic response. In general, the longer the acceleration and deceleration time, the slower the system response, and the shorter time, the faster the response. An excessive amount of time can result in sluggish system performance while too short of a time may result in system instability. The default values suggested normally result in good system performance for the majority of general purpose applications. If the values need to be adjusted, caution should be exercised, and the changes should be in small increments to avoid system instability.
00-14 Acceleration time 1 00-15 Deceleration time 1 These parameters set the acceleration and deceleration times of the output frequency from 0 to maximum frequency and from maximum frequency to 0. To set parameter 00-14 or 00-15: - After power-up press the DSP/FUN key - Set Group 00 (Basic Fun), and select parameter -14 or -15 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key. Acceleration and deceleration times are represented by the three most significant (high order) digits. Set acceleration and deceleration times with respect to maximum frequency. The relationship between the set frequency value and acceleration/deceleration times is as follows:
Set Frequency = Maximum Frequency Set Frequency < Maximum Frequency
Note: If the set acceleration and deceleration times are set too low, the torque limiting function or stall prevention function can become activated if the load torque and or inertia are relatively high. This will prolong the acceleration and or deceleration times and not allow the set times to be followed. In this case the acceleration and or the deceleration times should be adjusted.
Left acceleration/deceleration plot:Outputfrequency versusTime;RUN,STOP;Maximumfrequency,Setfrequency same level;Accelerationtime,Decelerationtime. Caption SetFrequency=MaximumFrequency. No numerical timing inferred.
Right acceleration/deceleration plot:Outputfrequency versusTime;RUN,STOP;Maximumfrequency dashed aboveSetfrequency;Accelerationtime,Decelerationtime. Caption SetFrequency<MaximumFrequency. No curve interpolation.
Manual — 8.3 Torque compensation01-10 — page 515
Manual reference: physical PDF page 515. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.3 Torque Compensation Gain (01-10)
This parameter sets the relationship between output frequency and output voltage. Constant torque applications have the same torque requirements at low speed as well as at high speed. Initial Setup For Variable Torque / Normal Duty applications set parameter 01-10 to an initial value of 0.5. For Constant Torque / Heavy Duty applications set parameter 01-10 to an initial value of 1.0. 01-10 Torque compensation gain
This parameter sets the torque boost for motor 1. Setting range: 0.0 to 2.0 To set parameter 01-10: - After power-up press the DSP/FUN key - Set Group 01 (V/F Pattern), and select parameter -10 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key.
Increase value when: The wiring between the inverter and the motor very too long The motor size is smaller than the inverter size Note: Gradually increase the torque compensation value and make sure the output current does not exceed inverter rated current. Reduce value when: Experiencing motor vibration Over Current Fault Overload Fault Important: Confirm that the output current at low speed does not exceed the rated output current of the inverter.
Warning: A larger than required torque compensation gain value creates over-excitation at low speeds, continued operation may cause the motor to overheat. Check the characteristics of the motor for additional information.
Manual — 8.4 Automatic energy saving11-19/11-21 — page 516
Manual reference: physical PDF page 516. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.4 Automatic Energy Saving Functions (11-19)
In the V/F control mode the automatic energy saving (AES) function automatically adjusts the output voltage and reduces the output current of the inverter to optimize energy savings based on the load. The output power changes proportional to the motor load. Energy savings is minimal when the load exceeds 70% of the output power and savings become greater when the load decreases. The parameter of automatic energy saving function has been set at the factory before shipment. In general, it is no need to adjust. If the motor characteristic has significant difference from TECO standard, please refer to the following commands for adjusting parameters: Enable Automatic Energy Savings Function To set parameters 11-19 to 11-24: - After power-up press the DSP/FUN key - Set Group 11 (Auxiliary Function Group), and select parameter -19 to -24 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key. (1) To enable automatic energy saving function set 11-19 to 1. (2) Filter time of automatic energy saving (11-20) (3) Commissioning parameter of energy saving (11-21 to 11-22) In AES mode, the optimum voltage value is calculated based on the load power requirement but is also affected by motor temperature and motor characteristic. In certain applications the optimum AES voltage needs to be adjusted in order to achieve optimum energy savings. Use the following AES parameters for manual adjustment: 11-21: Voltage limit value of AES commissioning operation Sets the voltage upper limit during automatic energy saving. 100% corresponds to 220V or 440V depending on the inverter class used.
Voltage limit value of commissioning operation graph:verticalVoltageLimit, horizontalOutputVoltage;11-21 at positive andnegative limiting levels. No numerical scale or inferred negative value.
Manual — AES11-22/11-23/11-24 continuation — page 517
Manual reference: physical PDF page 517. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11-22: Adjustment time of automatic energy saving Set sample time constant for measuring output power. Reduce the value of 11-22 to increase response when the load changes. Note: If the value of 11-22 is too low and the load is reduced the motor may become unstable. 11-23: Detection level of automatic energy saving Set the automatic energy saving output power detection level. 11-24: Coefficient of automatic energy saving The coefficient is used to tune the automatic energy saving. Adjust the coefficient while running the inverter on light load while monitoring the output power. A lower setting means lower output voltage. Notes: - If the coefficient is set to low the motor may stall. - Coefficient default value is based on the inverter rating. Set parameter 13-00. If the motor power does not match the inverter rating.
Manual — 8.5 Emergency stop00-26 — page 518
Manual reference: physical PDF page 518. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.5 Emergency Stop
The emergency stop time is used in combination with multi-function digital input function #14 (Emergency stop). When emergency stop input is activated the inverter will decelerate to a stop using the Emergency stop time (00-26) and display the [EM STOP] condition on the keypad. Note: To cancel the emergency stop condition the run command has to be removed and emergency stop input deactivated.
Example: Emergency Stop Switch with NPN wiring set for input terminal S5 (03-04 = 14).
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. EmergencyStop example:yellow24VG,S5;Common/24VG;EmergencyStop;EmergencyStopSwitch;ControlTerminals/UserTerminals;Connect shield to control ground terminal. Source diagram only.
8.5 Emergency stop00-26
00-26 / Emergency stop time — PDF page 518
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 00-26 | Emergency stop time |
| 2 | Range | 0.1~6000.0 Sec |
Manual — 8.6 Jog and8.7 unattended startup — page 519
Manual reference: physical PDF page 519. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.6 Forward and Reverse Jog
The jog forward command is used in combination with multi-function digital input function #6 (Jog Forward) and the jog reverse command is used in combination with multi-function digital input function #7 (Jog Reverse).
Example: Jog Forward input terminal S5 (03-04 = 06) and Jog Reverse input terminal S7 (03-06=7) with NPN wiring.
8.7 Direct / Unattended Startup
The unattended startup function prevents the inverter from starting automatically when a run command is present at time of power-up. To use USP command set one of the multi-function digital input functions to #50 (USP Startup).
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. Jog example:yellow24VG,S5,S7;Common/24VG;JogForwardSwitch;JogReverseSwitch;ControlTerminals/UserTerminals;Connect shield to control ground terminal.
UnattendedStartupProtection timing diagram tracks:PowerSupply,RunCommand,Fault(Alarm),FaultReset,USPCommand,OutputFrequency;each horizontal axist. Three source captions:left USP active on power-up. USP warning clears when run command is removed;middle USP not active,when fault is reset the inverter restarts automatically;right When run command is off at power-up and USP is active the inverter starts normally. Qualitative traces only;no times inferred.
Manual — 8.8 Analog output setup04-11 — page 520
Manual reference: physical PDF page 520. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
8.8 Analog Output Setup
Signal: Use parameter 04-11 to select the analog output signal for AO1 and parameter 04-16 to select the analog output signal for AO2. Gain: Use parameter 04-12 to adjust the gain for AO1 and parameter 04-17 to adjust the gain for AO2. Adjust the gain so that the analog output (10V) matches 100% of the selected analog output signal (04-11 for AO1 and 04-16 for AO2). Bias: Use parameter 04-13 to adjust the bias for AO1 and parameter 04-18 to adjust the bias for AO2. Adjust the bias so that the analog output (0V) matches 0% of the selected analog output signal (04-11 for AO1 and 04-16 for AO2).
Example: Analog Output 1 Wiring
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. AnalogOutput1 example:yellowGND,AO1;Common/GND black−;AnalogOutput1 red+;ControlTerminals/UserTerminals;Connect shield to control ground terminal.
8.8 Analog output setup04-11
04-11 / AO1 function Setting — PDF page 520
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | 04-11 | AO1 function Setting | AO1 function Setting |
| 2 | Range | 0: Output frequency 1: Frequency command 2: Output voltage 3: DC voltage 4: Output current 5: Output power 6: Motor speed 7: Output power factor 8: AI1 input 9: AI2 input 10: Torque command 11: q -axis current 12: d-axis current 13: Speed deviation 14: Reserved | 15: ASR output 16: Reserved 17: q-axis voltage 18: d-axis voltage 19: Reserved 20: Reserved 21: PID input 22: PID output 23: PID target value 24: PID feedback value 25: Output frequency of the soft starter 26: PG feedback 27: Reserved 28: Communication control |
Manual — Analog output setup04-12through04-20 — page 521
Manual reference: physical PDF page 521. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Analog output level adjustment:verticalAnalogOutputSignal ticks10V×Gain,10V,Bias,0V,Bias,−10V,(−10V)×Gain;horizontalMonitorSignal0%,100%. Solid positive andnegative saturation traces and dotted gain envelopes. No interpolation.
Analog output setup04-12through04-20
04-12 / AO1 gain — PDF page 521
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-12 | AO1 gain |
| 2 | Range | 0.0~1000.0% |
04-13 / AO1 bias — PDF page 521
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-13 | AO1 bias |
| 2 | Range | -100.0~100.0% |
04-16 / AO2 function Setting — PDF page 521
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-16 | AO2 function Setting |
| 2 | Range | See parameter 04-11 |
04-17 / AO2 gain — PDF page 521
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-17 | AO2 gain |
| 2 | Range | 0.0~1000.0% |
04-18 / AO2 bias — PDF page 521
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-18 | AO2 bias |
| 2 | Range | -100.0~100.0% |
04-19 / AO2 Output Signal Type — PDF page 521
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-19 | AO2 Output Signal Type |
| 2 | Range | 0: AO2 0~10V 1: AO2 4~20mA |
04-20 / Filter Time of AO Signal Scan — PDF page 521
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 04-20 | Filter Time of AO Signal Scan |
| 2 | Range | 0.00~0.50s |
Manual — 9.1 PID control source block diagram — page 522
Manual reference: physical PDF page 522. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 9 Using PID Control for Constant Flow / Pressure Applications
9.1 What is PID Control?
The PID function in the inverter can be used to maintain a constant process variable such as pressure,
flow, temperature by regulating the output frequency (motor speed). A feedback device (transducer)
signal is used to compare the actual process variable to a specified setpoint. The difference between
the set-point and feedback signal is called the error signal.
The PID control tries to minimize this error to maintain a constant process variable by regulating the
output frequency (motor speed).
The amplitude of the error can be adjusted with the Proportional Gain parameter 10-05 and is directly
related to the output of the PID controller, so the larger gain the larger the output correction.
PID block diagram labels:TargetValue10-00;FeedbackValue10-01;FeedbackGain10-04;10-03=x0xxb andx1xxb;D10-07;PIDInput(Deviation);P10-05;I10-06;D10-07;I-Limit10-14 with100%above and100%below as printed;no minus sign added;IntegralReset(usingMulti-functionDigitalInput);10-03=1,3,5,7 and10-03=2,4,6,8;PIDLimit10-23 with100%and−100%;Primarydelay10-10. Upper block:10-03=xx0xb ×1 andxx1xb ×−1;Bias10-09;PIDoutputgain10-24;±200%Limit;PIDOutput;10-03=3,4,7,8 and10-03=1,2,5,6;10-25=0 upper+109%limiter,10-25=1 lower+109%/−109%limiter;PID=OFF/PID=ON;FrequencyReference(Fref). PID=OFF conditions:1.10-03=0(PIDDisabled);2.duringJOGmode;3.multi-functiondigitalinput(03-00–03-07setting=29). Retain source labels and symbol polarities;no reconstructed control topology or correction of numeric mode labels.
Manual — PID gain examples and10-03 control mode — page 523
Manual reference: physical PDF page 523. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Example 1: Example 2:
Gain = 1.0 Gain = 2.0
Set-Point = 80% Set-Point = 80%
Feedback = 78% Feedback = 78%
Error = Set-point - Feedback = 2% Error = Set-point - Feedback = 2%
Control Error = Gain x Error = 2% Control Error = Gain x Error = 4%
Please note that an excessive gain can make the system unstable and oscillation may occur.
The response time of the system can be adjusted with the Integral Gain set by parameter 10-06.
Increasing the Integral Time will make the system less responsive and decreasing the Integral Gain
Time will increase response but may result in instability of the total system.
Slowing the system down too much may be unsatisfactory for the process. The end result is that these
two parameters in conjunction with the acceleration (00-14) and deceleration (00-15) times are
adjusted to achieve optimum performance for a particular application.
For typical fan and pump applications a Proportional Gain (10-05) of 2.0 and an Integral Time (10-06) of 5.0 sec is recommended. 10-03 PID control mode
PID control can be enabled by setting parameter 10-03 to ‘xxx1b’
PID gain examples and10-03 control mode
10-03 / PID control mode — PDF page 523
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 10-03 | PID control mode |
| 2 | Range | xxx0b: PID disable xxx1b: PID enable xx0xb: PID positive characteristic xx1xb: PID negative characteristic x0xxb: PID error value of D control x1xxb: PID feedback value of D control 0xxxb: PID output 1xxxb: PID output + frequency command |
Manual — PID modes and9.2 transducer4–20mA feedback — page 524
Manual reference: physical PDF page 524. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Commonly used PID control modes 0001b: Forward operation: PID operation enabled, motor speeds increases when feedback signal is smaller than set-point (most fan and pump applications) 0011b: Reverse operation: PID operation enabled, motor slows down when feedback signal is smaller than set-point (e.g. level control applications) To set parameter 10-03: - After power-up press the DSP/FUN key - Set Group 10 (PID Control), and select parameter -03 with the UP/DOWN ▲ and ▼ keys and press the READ/ ENTER key.
Important: To use the PID function parameter 00-05 (Main Frequency Command Source Selection) has to be set to 5 for PID reference.
9.2 Connect Transducer Feedback Signal (10-01)
The PID function in the inverter Depending on the type of feedback transducer used, the inverter can be setup for either 0-10V or a 4-20mA feedback transducer. Feedback Signal from AI2 (10-01 = 2), and set the input current to 4 – 20mA / SW2 = I
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. Feedback4–20mA diagram:yellowGND,AI2;Common,GND black−;AnalogInputAI2 red+;ControlTerminals/UserTerminals;Connect shield to control ground terminal. SW2 inset I,V;Set switchSW2to I. Source labels only.
Manual — Transducer0–10V feedback and9.3 engineering units — page 525
Manual reference: physical PDF page 525. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Feedback Signal from AI1 (10-01 = 1), and set the input voltage to 0 – 10V / SW2 = V
9.3 Engineering Units (only for LCD)
The PID setpoint scaling can be selected with parameter 16-03 and 16-04. Example: 0 – 200.0 PSI Setpoint, set 16-03 to 12000 (1 decimal, range 0 – 200) and 16-04 to 2 (PSI).
Upper terminal row:E,DO2,24VG,S2,S4,S6,S8,24V,+12V,GND,AI1,AI2. Lower row:DO1,DOG,S1,S3,S5,S7,F1,F2,PI,AO1,AO2,E. Feedback0–10Vdc diagram:yellowGND,AI2;Common,GND black−;AnalogInputAI2 red+;ControlTerminals/UserTerminals;Connect shield to control ground terminal. SW2 inset I,V;Set switchSW2to V. Heading saysAI1 but diagram saysAI2;both retained.
Manual — 9.4 PID sleep/wakeup — page 526
Manual reference: physical PDF page 526. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
9.4 Sleep / Wakeup Function
The PID Sleep function can be used to prevent a system from running at low speeds and is frequently used in pumping application. The PID Sleep function is turned on by parameter 10-29 set to 1. The inverter output turns off when the PID output falls below the PID sleep level (10-17) for the time specified in the PID sleep delay time parameter (10-18). The inverter wakes up from a sleep condition when the PID output (Reference frequency) rises above the PID wake-up frequency (10-19) for the time specified in the PID wake-up delay time (10-20). 10-29 =0: PID Sleep function is disabled. 10-29 =1: PID sleep operation is based on parameters of 10-17 and 10-18. 10-29 =2: PID sleep mode is enabled by multi-function digital input Refer to the following figures for PID sleep / wakeup operation.
PID sleep/wakeup block labels:TargetValue+,FeedbackValue−,PID,FreqReference(Fref),PID Sleep/Wake-upfunction,10-29=0,10-29=1or2,PID=OFF/PID=ON,SoftStart withf/tplot,OutputFrequency(Fout). No topology inferred.
PID SleepFunction plot:verticalOutputFrequency, horizontal t;Wake-upFrequency(10-19),SleepFrequency(10-17),Fmin(01-08);FrequencyReference(Fref) thin curve,OutputFrequency(Fout) heavy curve;sleepdelaytime(10-18),wakeupdelaytime(10-20). Qualitative traces without numeric interpolation.
Manual — 10.1–10.2 Fault detection;Table10.2.1 OC/OCA/OCC — page 527
Manual reference: physical PDF page 527. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 10 Troubleshooting and Fault Diagnostics
10.1 General
Inverter fault detection and early warning / self-diagnosis function. When the inverter detects a fault, a fault message is displayed on the keypad. The fault contact output energizes and the motor will coast to stop (The stop method can be selected for specific faults). When the inverter detects a warning / self-diagnostics error, the digital operator will display a warning or self-diagnostic code, the fault output does not energize in this case. Once the warning is removed, the system will automatically return to its original state.
10.2 Fault Detection Function
When a fault occurs, please refer to Table 10.2.1 for possible causes and take appropriate measures. Use one of the following methods to restart: 1. Set one of multi-function digital input terminals (03-00, 03-07) to 17 (Fault reset); activate input 2. Press the reset button on the keypad. 3. Power down inverter wait until keypad goes blank and power-up the inverter again. When a fault occurs, the fault message is stored in the fault history (see group 12 & 13). Table 10.2.1 Fault information and possible solutions
Segmented LED source glyph: OC. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: OCA. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: OCC. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Fault table first-column label and segmented glyph subcells are grouped within the original outer first-column and adjacent description-row boundaries. Other physical/shared cells retain their exact bounds. Each glyph has separate bounded image evidence. No labels are inferred from fault remedies.
10.1–10.2 Fault detection;Table10.2.1 OC/OCA/OCC
LED display / Description / Cause / Possible solutions — PDF page 527
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Cause | Possible solutions |
| 2 | OC over current | The inverter output current exceeds the overcurrent level (200% of the inverter rated current). | • Acceleration / Deceleration time is too short. • Contactor at the inverter output side. • A special motor or applicable capacity is greater than the inverter rated value. • Short circuit or ground fault. | • Extend acceleration / deceleration time. • Check the motor wiring. • Disconnect motor and try running inverter. |
| 3 | OCA over current | The inverter output current exceeds the overcurrent level in acceleration time | • Acceleration time is too short • Capacity of motor is bigger than inverter • Short circuit between winding and shell of motor • Short circuit between wire and ground of motor • IGBT broken module | • Set the longer acceleration time • Change to bigger capacity of inverter • Examine motor • Check the wire • Replace IGBT module |
| 4 | OCC over current | The inverter output current exceeds the overcurrent level in constant speed | • Instantaneous change of load • Instantaneous change of current | • Change to bigger capacity of inverter • Add reactor to power source |
Manual — Fault table OCd/SC/GF/OV/UV/IPL — page 528
Manual reference: physical PDF page 528. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: OCd. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: SC. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: GF. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: OU (row label OV). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: uU (row label UV). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: IPL. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Fault table first-column label and segmented glyph subcells are grouped within the original outer first-column and adjacent description-row boundaries. Other physical/shared cells retain their exact bounds. Each glyph has separate bounded image evidence. No labels are inferred from fault remedies.
Fault table OCd/SC/GF/OV/UV/IPL
LED display / Description / Cause / Possible solutions — PDF page 528
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Cause | Possible solutions |
| 2 | OCd over current | The inverter output current exceeds the overcurrent level in deceleration time | • Deceleration time is too short | • Set the longer acceleration time |
| 3 | SC short circuit | Inverter output short circuit or ground fault. | • Short circuit or ground fault (08-23 = 1). • Motor damaged (insulation). • Wire damage or deterioration. | • Check the motor wiring. • Disconnect motor and try running inverter. |
| 4 | GF Ground fault | The current to ground exceeds 50% of the inverter rated output current (08-23 = 1, GF function is enabled). | • Motor damaged (insulation). • Wire damage or deterioration. • Inverter DCCT sensors defect. | • Replace motor. • Check the motor wiring. • Disconnect motor and try running inverter. • Check resistance between cables and ground. • Reduce carrier frequency. |
| 5 | OV Over voltage | DC bus voltage exceeds the OV detection level: 200V class: 410Vdc 400V class: 820Vdc 575V class: 1050Vdc 690V class: 1230Vdc | • Deceleration time set too short, resulting in regenerative energy flowing back from motor to the inverter. • The inverter input voltage is too high. • Use of power factor correction capacitors. • Excessive braking load. • Braking transistor or resistor defective. • Speed search parameters set incorrectly. | • Increase deceleration time • Reduce input voltage to comply with the input voltage requirements or install an AC line reactor to lower the input voltage. • Remove the power factor correction capacitor. • Use dynamic braking unit. • Replace braking transistor or resistor. • Adjust speed search parameters. |
| 6 | UV Under voltage | DC bus voltage is lower than the UV detection level or the pre-charge contactor is not active while the inverter is running. 200V class: 190Vdc 400V class: 380Vdc 575/690V class: 546Vdc (The detection value can be adjusted by 07-13). | • The input voltage is too low. • Input phase loss. • Acceleration time set too short. • Input voltage fluctuation. • Pre-charge contactor damaged. • DC bus voltage feedback signal value not incorrect. | • Check the input voltage. • Check input wiring. • Increase acceleration time. • Check power source • Replace pre-charge contactor • Replace control board or complete inverter. |
| 7 | IPL input phase loss | Phase loss at the input side of the inverter or input voltage imbalance, active when 08-09 = 1 (enabled). | • Wiring loose in inverter input terminal. • Momentary power loss. • Input voltage imbalance. | • Check input wiring / faster screws. • Check power supply. |
Manual — Fault table OPL/OH1/OL1/OL2/OT/UT/run/OS — page 529
Manual reference: physical PDF page 529. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: OPL. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: OH1. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: OL1. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: OL2. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: ot (row label OT). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: ut (row label UT). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: run. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: OS. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Fault table first-column label and segmented glyph subcells are grouped within the original outer first-column and adjacent description-row boundaries. Other physical/shared cells retain their exact bounds. Each glyph has separate bounded image evidence. No labels are inferred from fault remedies.
Fault table OPL/OH1/OL1/OL2/OT/UT/run/OS
LED display / Description / Cause / Possible solutions — PDF page 529
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Cause | Possible solutions |
| 2 | OPL output phase loss | Phase loss at the output side of the inverter, active when 08-10 = 1 (enabled). | • Wiring loose in inverter output terminal. • Motor rated current is less than 10% of the inverter rated current. | • Check output wiring / faster screws. • Check motor & inverter rating. |
| 3 | OH1 Heatsink overheat | The temperature of the heat sink is too high. Note: when OH1 fault occurs three times within five minutes, it is required to wait 10 minutes before resetting the fault. | • Ambient temperature too high. • cooling fan failed • Carrier frequency set too high. • Load too heavy. | • Install fan or AC to cool surroundings. • Replace cooling fan. • Reduce carrier frequency. • Reduce load / Measure output current |
| 4 | OL1 Motor overload | Internal motor overload protection tripped, active when protection curve 08-05 = xxx1. | • Voltage setting V/F mode too high, resulting in over-excitation of the motor. • Motor rated current (02-01) set incorrectly. • Load too heavy. | • Check V/f curve. • Check motor rated current • Check and reduce motor load, check and operation duty cycle. |
| 5 | OL2 Inverter overload | Inverter thermal overload protection tripped. If an inverter overload occurs 4 times in five minutes, it is required to wait 4 minutes before resetting the fault. | • Voltage setting V/F mode too high, resulting in over-excitation of the motor. • Inverter rating too small. • Load too heavy. | • Check V/f curve. • Replace inverter with larger rating. • Check and reduce motor load, check and operation duty cycle. |
| 6 | OT Over torque detection | Inverter output torque is higher than 08-15 (over torque detection level) for the time specified in 08-16. Parameter 08-14 = 0 to activate. | • Load too heavy. | • Check over torque detection parameters (08-15 / 08-16). • Check and reduce motor load, check and operation duty cycle. |
| 7 | UT Under torque detection | Inverter output torque is lower than 08-19 (under torque detection level) for the time specified in 08-20. Parameter 08-18 = 0 to activate. | • Sudden drop in load. • Belt break. | • Check under torque detection parameters (08-19 / 08-20). • Check load / application. |
| 8 | run Switch for Motor1/Motor 2 | Switch for Motor1/Motor2 in running time | • Execute command for switching motor2 in running time • Execute command for switching motor in running time | • Revise the sequence control and switch motor in top time. |
| 9 | OS Over speed | Motor speed exceeds level set in 20-20 (PG Over speed Level) for the time set in 20-21 (PG over speed time). Active when 20-19 (= 0 or 1). This fault is active V/F + PG and SV control mode (00-00 = 1 or 3 or 4). Motor speed can be monitored by 12-22 | • Motor speed overshoot (ASR) • PG ppr set incorrectly. • Overspeed parameters set incorrectly. | • Check ASR parameters group 21. • Check PG parameters • Check overspeed parameters 20-20/20-12. |
Manual — Fault table PGO/DEV/CE/FB/STO/STO2/SS1/EF0 — page 530
Manual reference: physical PDF page 530. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: PGO. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: dEU (row label DEV). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: CE. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: Fb (row label FB). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: StO (row label STO). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: StO2 (row label STO2). Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: SS1. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF0. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Fault table first-column label and segmented glyph subcells are grouped within the original outer first-column and adjacent description-row boundaries. Other physical/shared cells retain their exact bounds. Each glyph has separate bounded image evidence. No labels are inferred from fault remedies.
Fault table PGO/DEV/CE/FB/STO/STO2/SS1/EF0
LED display / Description / Cause / Possible solutions — PDF page 530
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Cause | Possible solutions |
| 2 | PGO PG Open circuit | PG pulses are not received by the inverter for the time specified in 20-26 (PG open circuit detection time). This fault is active V/F + PG and SV control mode (00-00 = 1 or 3 or 4). | • PG cable disconnected. • PG has no power. • Mechanical brake active preventing motor from turning. | • Check PG wiring. • Check PG power-supply. • Make sure brake is released. |
| 3 | DEV Speed deviation | Motor speed rises above 20-23 level (PG speed deviation level) for the time specified in 20-24 (PG deviation time)...Active when parameter 20-22(=0 or 1). This fault is active V/F + PG and SV control mode (00-00 = 1 or 3 or 4). | • Load too heavy • Mechanical brake active preventing motor from turning. • PG wiring error. • PG parameters (group 20) set incorrectly. • Acceleration / deceleration time set to short. | • Check load • Make sure brake is released. • Check PG wiring. • Check PG parameters 20-23/20-24. • Increase Acceleration / deceleration time. |
| 4 | CE communicati on error | No Modbus communication received in for the time specified in 09-06 (communication error detection time). Active when 09-07(= 0 to 2). | • Connection lost or wire broken. • Host stopped communicating. | • Check connection • Check host computer / software. |
| 5 | FB PID feedback loss | PID feedback signal falls below level specified in 10-12 (PID feedback loss detection level) for the time specified in 10-13 (Feedback loss detection time). Active when parameter (10-11 = 2). | • Feedback signal wire broken • Feedback sensor broken. | • Check feedback wiring • Replace feedback sensor. |
| 6 | STO Safety switch STO2 Safety switch | Run permissive input open. | • Terminal board Input F1 and F2 are not connected (For standard H & C type) • Terminal board Input SF1 / SF2 and SG are not connected (For enhanced E & G type) • 08-30 set to 1,free run to stop, and digital terminal is open, when 03-00~03-07=58 | • Check F1 and F2 connection. (For standard H & C type) • Check SF1 / SF2 and SG connection (For enhanced E & G type) • Check if 08-30 =0 and 03-00~03-07=58 |
| 7 | SS1 Digital input Stop command | Digital input Stop command enabled | • 08-30 =0 and 03-00~03-07=58 | • Check if 08-30 =0 and 03-00~03-07=58 |
| 8 | EF0 External fault 0 | External fault (Modbus) | Modbus communication 0x2501 bit 2= "1" | • Reset Modbus communication 0x2501 bit 2= "1" |
Manual — Fault table EF1–EF8 with shared causes/actions — page 531
Manual reference: physical PDF page 531. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: EF1. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF2. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF3. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF4. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF5. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF6. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF7. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Segmented LED source glyph: EF8. Bounded first-column glyph region; associated printed fault label and descriptions retained in table. Letter shape/case transliteration only, not a separate fault designation.
Fault table first-column label and segmented glyph subcells are grouped within the original outer first-column and adjacent description-row boundaries. Other physical/shared cells retain their exact bounds. Each glyph has separate bounded image evidence. No labels are inferred from fault remedies.
Fault table EF1–EF8 with shared causes/actions
LED display / Description / Possible causes / Corrective action — PDF page 531
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | EF1 External fault (S1) | External fault (Terminal S1) Active when 03-00= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
| 3 | EF2 External fault (S2) | External fault (Terminal S2) Active when 03-01= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
| 4 | EF3 External fault (S3) | External fault (Terminal S3) Active when 03-02= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
| 5 | EF4 External fault (S4) | External fault (Terminal S4) Active when 03-03= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
| 6 | EF5 External fault (S5) | External fault (Terminal S5) Active when 03-04= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
| 7 | EF6 External fault (S6) | External fault (Terminal S6) Active when 03-05= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
| 8 | EF7 External fault (S7) | External fault (Terminal S7) Active when 03-06= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
| 9 | EF8 External fault (S8) | External fault (Terminal S8) Active when 03-07= 25 or 68, and Inverter external fault selection 08-24=0 or 1. | • Multifunction digital input external fault active. | • Multi-function input function set incorrectly. • Check wiring |
Manual — Table10.2.1 fault continuation CF07/CF08/CF00/CF01/CTER/CF20/PF/TOL — page 532
Manual reference: physical PDF page 532. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: CF07. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: CF08. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: CF00. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: CF01. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: CtEr. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: CF20. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: PF. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: tOL. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Table10.2.1 fault continuation CF07/CF08/CF00/CF01/CTER/CF20/PF/TOL
LED display / Description / Possible causes / Corrective action — PDF page 532
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | CF07 Motor control fault | Motor control fault | • SLV mode is unable to run motor. | • Perform rotational or stationary auto-tune • Increase minimum output frequency (01-08) |
| 3 | CF08 Motor control fault | Motor control fault | • Start or Run fault in PMSLV mode. | • Increase the value of 22-10 properly. • Re auto-tune (22-21) • Check if the load is too heavy to raise torque output limit. |
| 4 | CF00 Operator Communicati on Error | Errors of data transmission occur in LCD keypad. | • LCD keypad and inverter cannot transmit data after power on 5 seconds. | • Disconnect the operator and then reconnect. • Replace the control board |
| 5 | CF01 Operator Communicati on Error 2 | Errors of data transmission occur in LCD keypad. | • LCD keypad and inverter can transmit data but transmission error occurs for more than 2 seconds | • Disconnect the operator and then reconnect. • Replace the control board |
| 6 | CTER CT Failure | Errors of detecting voltages from three phase’s current transformer to detect output current. | • Errors of detecting voltages • Noises too much • Control board failure | • Check current transformer signal and the voltage on the control board. |
| 7 | CF20 Communicati on Failure | Use Profibus & Modbus Communication at the same time. | • Maybe use two kind of communication type at the same time. | • Check only use one kind of communication type. |
| 8 | PF Protection Fault | OH1 error occurs for 3 times in 5 minutes when run command in multi-function digital input terminals is not removed. | • Run command in multi-function digital input terminals is not removed. | • Remove run command in multi-function digital input terminals. |
| 9 | TOL External Overload | External overload (enabled only when firemode activated | • External overload in multi-function digital input terminals. (Ex. Fan overheat) | • Check external overload. • Reset external overload of digital input. |
Manual — 10.3 Warning/self-diagnosis;Table10.3.1 OV/UV — page 533
Manual reference: physical PDF page 533. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.3 Warning / Self-diagnosis Detection Function
When the inverter detects a warning, the keypad displays a warning code (flash). Note: The fault contact output does not energize on a warning and the inverter continues operation. When the warning is no longer active the keypad will return to its original state. When the inverter detected a programming error (for example two parameters contradict each other of are set to an invalid setting), the keypad displays a self-diagnostics code. Note: The fault contact output does not energize on a self-diagnostics error. While a self-diagnostics code is active the inverter does not accept a run command until the programming error is corrected. Note: When a warning or self- diagnostic error is active the warning or error code will flash on the keypad. When the RESET key is pressed, the warning message (flash) disappears and returns after 5 sec. If the warning or self-diagnostic error still exists. Refer to Table 10.3.1 for and overview, cause and corrective action for inverter warnings and self-diagnostic errors. Table 10.3.1 warning / self-diagnosis and corrective actions
Segmented LED source glyph: OU flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: uU flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
10.3 Warning/self-diagnosis;Table10.3.1 OV/UV
LED display / Description / Possible causes / Corrective action — PDF page 533
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | OV (flash) Over voltage | DC bus voltage exceeds the OV detection level: 200V class: 410Vdc 400V class: 820Vdc 575V class:1050Vdc 690V class: 1230Vdc (for 400V class, if input voltage 01-14 is set lower than 400V, the OV detection value will is decreased to 700Vdc) | • Deceleration time set too short, resulting in regenerative energy flowing back from motor to the inverter. • The inverter input voltage is too high. • Use of power factor correction capacitors. • Excessive braking load. • Braking transistor or resistor defective. • Speed search parameters set incorrectly. | • Increase deceleration time • Reduce input voltage to comply with the input voltage requirements or install an AC line reactor to lower the input voltage. • Remove the power factor correction capacitor. • Use dynamic braking unit. • Replace braking transistor or resistor. • Adjust speed search parameters. |
| 3 | UV (flash) under voltage | DC bus voltage is lower than the UV detection level or the pre-charge contactor is not active while the inverter is running. 190Vdc: 200V class; 380Vdc: 400V class 546Vdc:575/690V class (the detection value can be adjusted by 07-13) | • The input voltage is too low. • Input phase loss. • Acceleration time set too short. • Input voltage fluctuation. • Pre-charge contactor damaged. • DC bus voltage feedback signal value not incorrect. | • Check the input voltage. • Check input wiring. • Increase acceleration time. • Check power source • Replace pre-charge contactor • Replace control board or complete inverter. |
Manual — Warning table OH1/OH2/OT/UT/bb1–bb3 — page 534
Manual reference: physical PDF page 534. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: OH1 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: OH2 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: ot flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: ut flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bb1 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bb2 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bb3 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table OH1/OH2/OT/UT/bb1–bb3
LED display / Description / Possible causes / Corrective action — PDF page 534
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | OH1 Heatsink overheat | The temperature of the heat sink is too high. Note: when OH1 fault occurs three times within five minutes, it is required to wait 10 minutes before resetting the fault. | • Ambient temperature too high. • cooling fan failed • Carrier frequency set too high. • Load too heavy. | • Install fan or AC to cool surroundings. • Replace cooling fan. • Reduce carrier frequency. • Reduce load / Measure output current |
| 3 | OH2 (flash) Inverter over heating warning | Inverter overheat warning Multi-function digital input set to 31. (Terminal S1 ~ S8) Active when 03-00 ~ 03-07 = 31). | • Multifunction digital input overheat warning active | • Multi-function input function set incorrectly. • Check wiring |
| 4 | OT (flash) over torque detection | Inverter output torque is higher than 08-15 (over torque detection level) for the time specified in 08-16. Parameter 08-14 = 0 to activate. | • Load too heavy. | • Check over torque detection parameters (08-15 / 08-16). • Check and reduce motor load, check and operation duty cycle. |
| 5 | UT (flash) under torque detection | Inverter output torque is lower than 08-19 (under torque detection level) for the time specified in 08-20. Parameter 08-18 = 0 to activate. | • Sudden drop in load. • Belt break. | • Check under torque detection parameters (08-19 / 08-20). • Check load / application. |
| 6 | bb1 (flash) External baseblock | External base block (Terminal S1) | • Multifunction digital input external baseblock active. | • Multi-function input function set incorrectly. • Check wiring |
| 7 | bb2 (flash) External baseblock | External base block (Terminal S2) | • Multifunction digital input external baseblock active. | • Multi-function input function set incorrectly. • Check wiring |
| 8 | bb3 (flash) External baseblock | External base block (Terminal S3) | • Multifunction digital input external baseblock active. | • Multi-function input function set incorrectly. • Check wiring |
Manual — Warning table bb4–bb8;blank bb4 cause/action retained — page 535
Manual reference: physical PDF page 535. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: bb4 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bb5 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bb6 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bb7 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bb8 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table bb4–bb8;blank bb4 cause/action retained
LED display / Description / Possible causes / Corrective action — PDF page 535
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | bb4 (flash) External baseblock | External base block (Terminal S4) | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 3 | bb5 (flash) External baseblock | External base block (Terminal S5) | • Multifunction digital input external baseblock active. | • Multi-function input function set incorrectly. • Check wiring |
| 4 | bb6 (flash) External baseblock | External base block (Terminal S6) | • Multifunction digital input external baseblock active. | • Multi-function input function set incorrectly. • Check wiring |
| 5 | bb7 (flash) External baseblock | External base block (Terminal S7) | • Multifunction digital input external baseblock active. | • Multi-function input function set incorrectly. • Check wiring |
| 6 | bb8 (flash) External baseblock | External base block (Terminal S8) | • Multifunction digital input external baseblock active. | • Multi-function input function set incorrectly. • Check wiring |
Manual — Warning table OS/PGO/DEV/OL1/OL2 — page 536
Manual reference: physical PDF page 536. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: OS flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: PGO flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: dEU flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: OL1. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: OL2. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table OS/PGO/DEV/OL1/OL2
LED display / Description / Possible causes / Corrective action — PDF page 536
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | OS (flash) Motor over speed | Motor speed exceeds level set in 20-20 (PG Over speed Level) for the time set in 20-21 (PG over speed time). Active when 20-19 (= 0 or 1). This fault is active V/F + PG and SV control mode (00-00 = 1 or 3 or 4). Motor speed can be monitored by 12-22 | • Motor speed overshoot (ASR) • PG ppr set incorrectly. • Overspeed parameters set incorrectly. | • Check ASR parameters group 21. • Check PG parameters • Check overspeed parameters 20-20/20-12. |
| 3 | PGO (flash) PG open circuit | PG pulses are not received by the inverter for the time specified in 20-26 (PG open circuit detection time). This fault is active V/F + PG and SV control mode (00-00 = 1 or 3 or 4). | • PG cable disconnected. • PG has no power. • Mechanical brake active preventing motor from turning. | • Check PG wiring. • Check PG power-supply. • Make sure brake is released. |
| 4 | DEV (flash) Speed deviation | Motor speed rises above 20-23 level (PG speed deviation level) for the time specified in 20-24 (PG deviation time).Active when parameter 20-22(=0 or 1). This fault is active V/F + PG and SV control mode (00-00 = 1 or 3 or 4). | • Load too heavy • Mechanical brake active preventing motor from turning. • PG wiring error. • PG parameters (group 20) set incorrectly. • Acceleration / deceleration time set to short. | • Check load • Make sure brake is released. • Check PG wiring. • Check PG parameters 20-23/20-24. • Increase Acceleration / deceleration time. |
| 5 | OL1 Motor overload | Internal motor overload protection tripped, active when protection curve 08-05 = xxx1. | • Voltage setting V/F mode too high, resulting in over-excitation of the motor. • Motor rated current (02-01) set incorrectly. • Load too heavy. | • Check V/f curve. • Check motor rated current • Check and reduce motor load, check and operation duty cycle. |
| 6 | OL2 Inverter overload | Inverter thermal overload protection tripped. If an inverter overload occurs 4 times in five minutes, it is required to wait 4 minutes before resetting the fault. | • Voltage setting V/F mode too high, resulting in over-excitation of the motor. • Inverter rating too small. • Load too heavy. | • Check V/f curve. • Replace inverter with larger rating. • Check and reduce motor load, check and operation duty cycle. |
Manual — Warning table CE/CLA/CLB/Retry/ES — page 537
Manual reference: physical PDF page 537. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: CE flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: CLA flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: CLb flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: rEtrY flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: ES flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table CE/CLA/CLB/Retry/ES
LED display / Description / Possible causes / Corrective action — PDF page 537
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | CE (flash) communicati on error | No Modbus communication received for 2 sec. Active when 09-07=3. | • Connection lost or wire broken. • Host stopped communicating. | • Check connection • Check host computer / software. |
| 3 | CLA over current protection level A | Inverter current reaches the current protection level A. | • Inverter current too high. • Load too heavy. | • Check load and duty cycle operation. |
| 4 | CLB over current protection level B | Inverter current reaches the current protection level B. | • Inverter current too high. • Load too heavy. | • Check load and duty cycle operation. |
| 5 | Retry (flash) retry | Automatic reset activated, warning is displayed until restart delay time set (07-01) expires. | • Parameter 07-01 set to a value greater than 0. • Parameter 07-02 set to a value greater than 0. | • Warning disappears after automatic reset. |
| 6 | ES (flash) External emergency stop | External emergency stop Enabled. | • 03-00~03-08 set to 14, and the digital input enabled. | • Turn off run command, and remove external emergency stop command. |
Manual — Warning table flashing EF1–EF8;shared causes/actions — page 538
Manual reference: physical PDF page 538. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: EF1 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EF2 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EF3 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EF4 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EF5 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EF6 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EF7 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EF8 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table flashing EF1–EF8;shared causes/actions
LED display / Description / Possible causes / Corrective action — PDF page 538
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | EF1 ( flash ) External fault (S1) | External fault (Terminal S1) Active when 03-00= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
| 3 | EF2 ( flash ) External fault (S2) | External fault (Terminal S2) Active when 03-01= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
| 4 | EF3 ( flash ) External fault (S3) | External fault (Terminal S3) Active when 03-02= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
| 5 | EF4 ( flash ) External fault (S4) | External fault (Terminal S4) Active when 03-03= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
| 6 | EF5 ( flash ) External fault (S5) | External fault (Terminal S5) Active when 03-04= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
| 7 | EF6 ( flash ) External fault (S6) | External fault (Terminal S6) Active when 03-05= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
| 8 | EF7 ( flash ) External fault (S7) | External fault (Terminal S7) Active when 03-06= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
| 9 | EF8 ( flash ) External fault (S8) | External fault (Terminal S8) Active when 03-07= 25 or 68, and Inverter external fault selection 08-24=2. | • Multifunction digital input external fault active and parameter 08-24 = 2 for operation to continue. | • Multi-function input function set incorrectly. • Check wiring • Multi-function input function set incorrectly. • Check wiring |
Manual — Warning table EF9/SE01/SE02/SE03/SE05 — page 539
Manual reference: physical PDF page 539. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: EF9 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: SE01 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: SE02 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: SE03 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: SE05 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table EF9/SE01/SE02/SE03/SE05
LED display / Description / Possible causes / Corrective action — PDF page 539
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | EF9 ( flash ) error of forward/revers al rotation | Forward run and reverse run are active within 0.5 sec of each other. Stop method set by parameter 07-09. | • Forward run and reverse run active (see 2-wire control). | • Check run command wiring |
| 3 | SE01 Rang setting error | Parameter setting falls outside the allowed range. | • Some parameter ranges are determined by other inverter parameters which could cause an out of range warning when the dependency parameter is adjusted. Example: 1.02-00>02-01,or 20>02-21 2.00-12>00-13, 3.00-07 = 1,00-05=00-06 4.02-03 > 02-06 or 02-22 > 02-25 5.20-16 < 20-15 | • Check parameter setting. |
| 4 | SE02 Digital input terminal error | Multi-function input setting error. | • Multi-function digital input terminals (03-00 to 03-07) are set to the same function (not including ext. fault and not used.) or UP/DOWN commands are not set at the same time( they must be used together). UP/DOWN commands (08 and 09) and ACC/DEC commands (11) are set at the same time. Speed search 1(19,maximum frequency) and Speed search 2 (34,from the set frequency) are set at the same time. 03-00~03-07 set two-wire and three-wire in the same time. | • Check multi-function input setting. |
| 5 | SE03 V/f curve error | V/f curve setting error. | • V/F curve setting error. 01-02 > 01-12 > 01-06 >01-08; • (Fmax) (Fbase) (Fmid1) (Fmin) 01-16 > 01-24 > 01-20 > 01-22; • (Fmax2) (Fbase2)(Fmid1) (Fmin2) | • Check V/F parameters |
| 6 | SE05 PID selection error | PID selection error. | • 10-00 and10-01 set to 1(AI1) or set to 2(AI2) • 10-29 = 1 or 2 and 10-25 = 1allow to reverse. • 10-29 = 1 or 2 and 10-03 =1xxxb(PID output+ target value) | • Check10-00 and 10-01 • Check 10-29 and 10-25 • Check 10-29 and 10-03 |
Manual — Warning table HPErr/SE07/SE08/SE09/FB/USP/STP0 — page 540
Manual reference: physical PDF page 540. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: HPErr flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: SE07 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: SE08 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: SE09 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: Fb flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: uSP flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: StP0 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table HPErr/SE07/SE08/SE09/FB/USP/STP0
LED display / Description / Possible causes / Corrective action — PDF page 540
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | HPErr Model selection error | Inverter capacity setting error: Inverter capacity setting 13-00 does not match the rated voltage. | • Inverter capacity setting does not match voltage class (13-00). | • Check inverter capacity setting 13-00. |
| 3 | SE07 PG card error | Inverter PG card setting error. | • No PG feedback card installed. • Set wrong type for PM Encoder Type (22-08) | • Install PG feedback card. • Check control mode. • Set right type for PM Encoder Type (22-08) and power on again. |
| 4 | SE08 PM Motor mode error | Inverter rating does not support the PM Motor mode. | • Inverter rating does not support PM motor control mode. | • Check control mode. |
| 5 | SE09 PI setting error | Inverter PI setting error | • Inverter pulse input selection (03-30) selection conflicts with PID source (10-00 and 10-01). | • Check pulse input selection (03-30) and PID source (10-00 and 10-01). |
| 6 | FB (flash) PID feedback breaking | PID feedback signal falls below level specified in 10-12 (PID feedback loss detection level) for the time specified in 10-13 (Feedback loss detection time). Active when parameter (10-11 = 1). | • Feedback signal wire broken • Feedback sensor broken. | • Check feedback wiring • Replace feedback sensor. |
| 7 | USP (flash) Unattended Start Protection | Unattended Start Protection (USP) is enabled (enabled at power-up.) | • USP at power-up (activated by multi-function digital input) is enabled. The inverter will not accept a run command. • While the warning is active the inverter does not accept a run command. (See parameter 03-00 - 03-08 = 50). | • Remove run command or reset inverter via multi-function digital input (03-00 to 03-07 = 17) or use the RESET key on the keypad to reset inverter. • Activate USP input and re-apply the power. |
| 8 | STP0 Zero Speed Stop Error | Frequency command is smaller than 01-08 without DC brake. | • Frequency command is smaller than motor minimum output frequency. | • Adjust frequency command |
Manual — Warning table STP2/EnC/RunEr/PArEr/STP1/FirE/AdCEr — page 541
Manual reference: physical PDF page 541. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: StP2 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: EnC flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: runEr flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: PArEr flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: StP1 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: FirE flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: AdCEr flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table STP2/EnC/RunEr/PArEr/STP1/FirE/AdCEr
LED display / Description / Possible causes / Corrective action — PDF page 541
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | STP2 External Terminal Stop Error | External Terminal is main run command source selection (00-02=1) and run command executes but executes stop command from keypad. | • Run command executes from external terminal but executes stop command from keypad. | • Remove the run command from external terminal |
| 3 | EnC Encoder Error | PG card is connected but encoder signal error is detected when motor auto rotational tuning is running. | • Abnormal encoder signal | • Check encoder wiring • 17-07 PG pulse number setting is not corresponding to the encoder. • Replace the encoder. |
| 4 | RunEr Wrong running direction Error | Running direction is different from 11-00 | • Check the command among 11-00, jog and DI control to see if any difference. | • Revise the command among 11-00, jog and DI control to see if any difference |
| 5 | PArEr Parameter setting error | Parameter setting error | • The parameter setting is wrong | • Please refer to the manual for correct setting |
| 6 | STP1 Direct start warning | The inverter can’t start directly, due to 07-04=1 | • Run command from the terminal is enabled and 07-04=1 | • Remove the run command from the terminal first, and enabled later. |
| 7 | FirE Fire mode enabled | Fire mode enabled | • Fire mode enabled. | • Check the environment and confirm the fire status. If no fire, turn off the power and power on again. |
| 8 | AdCEr Voltage on C/B error | The voltage on the control board error | • Errors of detecting voltages • Noises too much • Control board failure | • Check the voltage on the control board. |
Manual — Warning table EPErr/bdErr/ParameterLock/passwordfailure — page 542
Manual reference: physical PDF page 542. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Segmented LED source glyph: EPErr flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: bdErr flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: LOC flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Segmented LED source glyph: Err2 flash. Source flash rays retained as flash annotation; associated printed fault label in table remains authoritative source spelling. Glyph shape/case transliteration only, not a separate designation.
Fault label and segmented LED glyph subcells grouped only inside original first-column bounds and adjacent description-row boundaries; shared causes/remedies retain original whole merged bounds. Separate glyph evidence retained.
Warning table EPErr/bdErr/ParameterLock/passwordfailure
LED display / Description / Possible causes / Corrective action — PDF page 542
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | LED display | Description | Possible causes | Corrective action |
| 2 | EPErr EEPROM Save error | The data save in EEPROM is wrong. | • EEPROM circuit failure • Parameter check error after power on | • Restore factory setting, then cut off the power and power on again. • If warning again, replace control board. |
| 3 | bdErr Control board error | Firmware can’t meet Control board. | • Firmware can’t meet Control board. | • Replace the control board. |
| 4 | Parameter Lock | Parameter lock key code (password) already locked | • Parameter lock key code already enable (13-07) | • Lifting the parameter lock key code, to enter the correct parameter for 13-07 |
| 5 | Set password failed | Parameter lock key code cannot enable | • To enable the parameter lock key code (password) function, but the password is not correct | • Enter the correct parameter for 13-07 to enable the parameter lock key |
Manual — 10.4 ACmotor auto-tuning faults01–09 — page 543
Manual reference: physical PDF page 543. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.4 Auto-tuning Error
When a fault occurs during auto-tuning of a standard AC motor, the display will show the “AtErr” fault and the motor stops. The fault information is displayed in parameter 17-11. Note: The fault contact output does not energize with an auto-tuning fault. Refer to Table 10.4.1, for fault information during tuning, cause and corrective action.
Table 10.4.1 Auto-tuning fault and corrective actions
10.4 ACmotor auto-tuning faults01–09
Error / Description / Cause / Corrective action — PDF page 543
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Error | Description | Cause | Corrective action |
| 2 | 01 | Motor data input error. | • Motor Input data error during auto-tuning. • Inverter output current does not match motor rated current. | • Check the motor tuning data (17-00 to 17-09). • Check inverter capacity |
| 3 | 02 | Motor lead to lead resistance R1 tuning error. | • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. | • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation. |
| 4 | 03 | Motor leakage inductance tuning error. | • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. | • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation. |
| 5 | 04 | Motor rotor resistance R2 tuning error. | • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. | • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation. |
| 6 | 05 | Motor mutual inductance Lm tuning error. | • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. | • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation. |
| 7 | 07 | Deadtime compensation detection error | • Auto-tuning is not completed within the specified time • Auto-tuning results fall outside parameter setting range. • Motor rated current exceeded. • Motor was disconnected. | • Check the motor tuning data (17-00 to 17-09). • Check motor connection. • Disconnect motor load. • Check inverter current detection circuit and DCCTs. • Check motor installation. |
| 8 | 06 | Motor encoder error | • PG feedback noise | • Check motor rated current. • Check PG card grounding. |
| 9 | 08 | Motor acceleration error (Rotational type auto-tuning only). | • Motor fails to accelerate in the specified time (00-14= 20sec). | • Increase acceleration time (00-14). • Disconnect motor load. |
| 10 | 09 | Other | • No load current is higher than 70% of the motor rated current. • Torque reference exceeds 100%. • Errors other than ATE01~ATE08. | • Check the motor tuning data (17-00 to 17-09). • Check motor connection. |
Manual — 10.5 PMmotor auto-tuning faults01–10 — page 544
Manual reference: physical PDF page 544. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.5 PM Motor Auto-tuning Error
When a fault occurs during auto-tuning of a PM motor, the display will show the “IPErr” fault and the motor stops. The fault information is displayed in parameter 22-18. Note: The fault contact output does not energize with an auto-tuning fault. Refer to Table 10.5.1, for fault information during tuning, cause and corrective action.
Table 10.5.1 Auto-tuning fault and corrective actions for PM motor
10.5 PMmotor auto-tuning faults01–10
Error / Description / Cause / Corrective action — PDF page 544
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Error | Description | Cause | Corrective action |
| 2 | 01 | Magnetic pole alignment tuning failure (static). | • Inverter output current does not match motor current. | • Check the motor tuning data (22-02). • Check inverter capacity |
| 3 | 02 | PG option missing. | • Magnetic pole cannot be aligned without PG option card. | • Install PG feedback card. |
| 4 | 03 | Magnetic pole alignment auto-tuning abort during rotational auto-tune. | • System abnormality during magnetic pole alignment. | • Check for active protection functions preventing auto-tuning. |
| 5 | 04 | Timeout during magnetic pole alignment during rotational auto-tune. | • Motor cannot rotate | • Check motor. • Check motor wiring. • Check brake released. |
| 6 | 05 | Circuit tuning time out. | • System abnormality during circuit tuning. | • Check for active protection functions preventing auto-tuning. |
| 7 | 06 | Encoder error | • PG feedback noise | • Check motor rated current. • Check PG card grounding. |
| 8 | 07 | Warning | • ·Other motor tuning error | • Check the motor tuning data (22-02). • Check motor connection. |
| 9 | 08 | Motor current out of range during magnetic pole alignment (rotational auto-tune). | • Motor cannot operate at low speeds. | • Check PG card wiring • Check motor connection. |
| 10 | 09 | Current out of range during circuit tuning. | • Inverter output current does not match motor current. | • Check the motor tuning data (22-02). • Check inverter capacity |
| 11 | 10 | Magnetic pole alignment and circuit tuning failed. | • Auto-tuning is not successful. | • Retry magnetic pole alignment and circuit tuning. |
Manual — 10.6 General troubleshooting status/check/remedy — page 545
Manual reference: physical PDF page 545. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.6 General troubleshooting
10.6 General troubleshooting status/check/remedy
Status / Checking point / Remedy — PDF page 545
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Status | Checking point | Remedy |
| 2 | Motor runs in wrong direction | Is the wiring for the output terminals correct? | Wiring must match U, V, and W terminals of the motor. |
| 3 | Motor runs in wrong direction | Is the wiring for forward and reverse signals correct? | Check for correct wiring. |
| 4 | The motor speed can not be regulated. | Is the wiring for the analog frequency inputs correct? | Check for correct wiring. |
| 5 | The motor speed can not be regulated. | Is the setting of operation mode correct? | Check the Frequency Source set in parameters 00-05/00-06. |
| 6 | The motor speed can not be regulated. | Is the load too excessive? | Reduce the load. |
| 7 | Motor running speed too high or too low | Check the motor specifications (poles, voltage…) correct? | Confirm the motor specifications. |
| 8 | Motor running speed too high or too low | Is the gear ratio correct? | Confirm the gear ratio. |
| 9 | Motor running speed too high or too low | Is the setting of the highest output frequency correct? | Confirm the highest output frequency |
| 10 | Motor speed varies unusually | Is the load too excessive? | Reduce the load. |
| 11 | Motor speed varies unusually | Does the load vary excessively? | 1.Minimize the variation of the load. 2.Consider increasing the capacities of the inverter and the motor. |
| 12 | Motor speed varies unusually | Is the input power unstable or is there a phase loss ? | 1.Consider adding an AC reactor at the power input side if using single-phase power. |
| 13 | Motor speed varies unusually | Is the input power unstable or is there a phase loss ? | 2.Check wiring if using three-phase power |
| 14 | Motor can not run | Is the power connected to the correct L1, L2, and L3 terminals? is the charging indicator lit ? | 1.Is the power applied? 2.Turn the power OFF and then ON again. 3.Make sure the power voltage is correct. 4.Make sure screws are secured firmly. |
| 15 | Motor can not run | Is there voltage across the output terminals T1, T2, and T3? | Turn the power OFF and then ON again. |
| 16 | Motor can not run | Is overload causing the motor to stall? | Reduce the load so the motor will run. |
| 17 | Motor can not run | Are there any abnormalities in the inverter? | See error descriptions to check wiring and correct if necessary. |
| 18 | Motor can not run | Is there a forward or reverse run command ? | See error descriptions to check wiring and correct if necessary. |
| 19 | Motor can not run | Has the analog frequency signal been input? | 1.Is analog frequency input signal wiring correct? 2.Is voltage of frequency input correct? |
| 20 | Motor can not run | Is the operation mode setting correct? | Operate through the digital keypad |
Manual — 10.7.1 Quick inverter troubleshooting flowchart;continues547 — page 546
Manual reference: physical PDF page 546. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.7 Troubleshooting of the Inverter
10.7.1 Quick troubleshooting of the Inverter
INV Fault
Visually check controller and Drive boards
*to next page
Check burnt and damaged parts
Consult with the supplier
Replace fuse
Check according to displayed fault messages
Replace the pre-charge resistor
Check terminals and wiring
Perform detailed check and consult with the supplier
Is fault known?
Symptoms other than burn out, damage, or fuse meltdown in the inverter?
Any Symptoms of burn out and damage?
Is the main circuit DM intact? Fault signal?
Is the fuse intact?
Is the main circuit I.G.B.T intact?
Any visual abnormalities?
Are displays and indicators of the operating unit working normally?
Is +5V control voltage correct?
Is the DC input voltage controlling the power correct Any fault display?
What the message ?
Is LED lit?
Replace control board and digital operating unit
Is the error eliminated after replacing control board?
YES
NO
NO YES
NO NO
Apply the power
Source quick-troubleshooting flowchart. Full native bounded labels retained separately. Visible branches:INVFault→Isfaultknown? YES→Symptomsotherthanburnout,damage,orfusemeltdowninthe inverter?;NO→AnySymptomsofburnoutanddamage? YES→Checkburntanddamagedparts,NO→maincircuitDMintact? NO→Consultsupplier,YES→fuseintact? NO→Replacefuse,YES→maincircuitI.G.B.Tintact? NO→Consultsupplier,YES→VisuallycheckcontrollerandDriveboards→Anyvisualabnormalities? YES→Consultsupplier,NO→Applypower. Faultsignal? YES→Checkaccordingdisplayedfaultmessages,NO→DMcheck. Applypower→Displays/indicatorsworkingnormally? NO→LEDlit? NO→Replacepre-chargeresistor,YES→DCinputvoltagecontrollingpowercorrect? NO→Checkterminals/wiring,YES→+5Vcontrolvoltagecorrect? NO→Consultsupplier,YES→Replacecontrolboardanddigitaloperatingunit→Error eliminatedafterreplacingcontrolboard? NO→Detailedcheck/consultsupplier,YESloopsApplypower. DisplaysnormalYES→Anyfaultdisplay? YES→Whatmessage?→Checkdisplayedfaultmessages,NO→nextpage. These are observed source connections, not a validated executable procedure.
Manual — Quick inverter troubleshooting flowchart continued546 — page 547
Manual reference: physical PDF page 547. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Check Inverter parameters
Replace the control board
Perform parameter initializations
Specify operation control mode
Does the FWD or REV LED light flash?
Is the frequency value displayed on the display?
Are there voltage outputs at terminals U, V and W
Is there any fault display?
Are output currents of each phase even?
The inverter is OK
Perform detailed check and consult with the supplier.
Does the control Board function after replacement
YES
NO
From previous page
Set up frequency command
Connect the motor to run
Source continuation from546:CheckInverterparameters→Performparameterinitializations→Specifyoperationcontrolmode→FWDorREVLEDflash? NO→Replacecontrolboard;YES→Setupfrequencycommand→Frequencyvaluedisplayed? NO→Replacecontrolboard;YES→VoltageoutputsU,V,W? NO→Replacecontrolboard→Controlboardfunctionafterreplacement? YES→Connectmotortorun,NO→Detailedcheck/consultsupplier. VoltageoutputsYES→Connectmotortorun→Anyfaultdisplay? YES→Detailedcheck/consultsupplier,NO→Outputcurrentsof eachphaseeven? NO→Detailedcheck/consultsupplier,YES→InverterOK. Source also prints NO on connector immediately afterConnectmotortorun;retain unexplained label,no extra branch inferred.
Manual — 10.7.2 OC/OL troubleshooting flowchart — page 548
Manual reference: physical PDF page 548. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.7.2 Troubleshooting for OC, OL error displays
The inverter displays OC, OL errors
The inverter output is OK
Is the output current of each phase even?
Any fault values displayed?
Is there Voltage at U,V and W output terminals?
Is the output frequency of the operating unit displayed?
Is FWD LED illuminated?
Is the main circuit I.G.B.T working
Any visual abnormalities?
Is the current detector OK? Any abnormal indications?
Is the inverter operation OK after board replacement ?
Replace the current controller
Replace control board
Replace faulty circuit board
Replace I.G.B.T
The inverter is faulted (Perform detailed check)
YES
NO
NO NO
Apply power
Input operation command
Input frequency command
Connect the motor to run
OC/OL sourceflowchart:MaincircuitIGBTworking? NO→ReplaceIGBT;YES→Anyvisualabnormalities? YES→Replacefaultycircuitboard;NO→Applypower→Anyabnormalindications? YES→CurrentdetectorOK? YES→Replacecurrentcontroller,NO→Replacecontrolboard. MainverticalpathcontinuesInputoperationcommand→FWDLEDilluminated? NO→Replacecontrolboard;YES→Inputfrequencycommand→Outputfrequencydisplayed? NO→Replacecontrolboard;YES→VoltageU,V,Woutputterminals? NO→Replacecontrolboard→InverteroperationOKafterboardreplacement? YES→Connectmotortorun,NO→Inverterfaulted(Performdetailedcheck). Voltagepresentpath→Connectmotortorun→Anyfaultvaluesdisplayed? YES→Inverterfaulted,NO→Outputcurrenteachphaseeven? NO→Inverterfaulted,YES→InverteroutputOK. No engineering validation;unlabelled downwardbranch afterabnormalindications retained asunlabelled.
Manual — 10.7.3 OV/LV troubleshooting flowchart — page 549
Manual reference: physical PDF page 549. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.7.3 Troubleshooting for OV, LV error
The inverter displays OV, LV
The inverter’s output is OK
Is the current on all phases even?
Any abnormal value?
Is there Voltage at T1,T2,T3 output terminals?
Is the output frequency of the operating unit displayed?
Is FWD LED still illuminated after flash
Is the main circuit fuse intact?
Any visual abnormalities?
Any abnormal indications?
Is the inverter operation OK after board replacement?
Replace the control board
Perform detailed check and consult with the supplier
YES
NO
Connect the motor to run
Input frequency commands
Input operation command
Apply power
Consult with the supplier
OV/LV sourceflowchart:Maincircuitfuseintact? NO→Consultsupplier;YES→Anyvisualabnormalities? YES→Consultsupplier;NO→Applypower→Anyabnormalindications? YES→Consultsupplier. Unlabelleddownwardbranch→Inputoperationcommand→FWDLEDstillilluminatedafterflash? NO→Consultsupplier;YES→Inputfrequencycommands→Outputfrequencydisplayed? NO→Replacecontrolboard;YES→VoltageT1,T2,T3? NO→Replacecontrolboard→InverteroperationOKafterboardreplacement? YES→Connectmotortorun,NO→Detailedcheck/consultsupplier. VoltageYES→Connectmotortorun→Anyabnormalvalue? YES→Detailedcheck/consultsupplier,NO→Currentallphaseseven? NO→Detailedcheck/consultsupplier,YES→InverteroutputOK. Source prints NO directlybelowConnectmotortorun;do notinferextra decision.
Manual — 10.7.4 Motor cannot run flowchart — page 550
Manual reference: physical PDF page 550. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.7.4 The motor can not run
The motor can not run
Is MCCB On?
Can MCCB be turned On?
Are voltages between power terminals correct?
Is LED lit?
Is the operation switch in UN? ?
Are there outputs between the U,V, and W terminals of the motor?
Are outputs between U,V,W the same?
- Motor 2. Motor faults 3. Incorrect wiring
INVfault
The operation switch is set to “RUN” position
1.The power is abnormal 2.Incorrect wiring
Short circuited wiring
NO
YES
Motorcannotrun sourceflowchart:MCCBOn? YESbypass→Powerterminalvoltagescorrect?;NO→CanMCCBturnedOn? NO→Shortcircuitedwiring;YES→Powerterminalvoltagescorrect? NO→Powerabnormal/Incorrectwiring;YES→LEDlit? NO→INVfault;YES→Operation switch in UN?? [source malformed text retained]? NO→Operationswitchsetto RUNposition;YES→OutputsbetweenmotorU,V,Wterminals? NO→INVfault;YES→OutputsbetweenU,V,Wsame? NO→INVfault;YES→1.Motor;2.Motorfaults;3.Incorrectwiring. Do not infer missing word in malformed decision.
Adjacent source context — repeated to preserve continuation:
Manual — 10.7.5 Motor overheating flowchart — page 551
Manual reference: physical PDF page 551. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.7.5 Motor Overheating
YE S
Y ES
N O
Is load or current exceeding the specified value ?
C onsider reducing the load and increasing the capacities of the inverter and m otor
M otor O verheating
Is m otor running at low speed for a long tim e?
Is m otor voltage betw een U - V ,V -W ,W -U correct?
Is there any deterrence preventing cooling of the m otor
B ad connection betw een drive and the m otor
S elect the m otor again
IN V faults
C lear the deterrence
C orrect the bad connection
Motoroverheating sourceflowchart:Loadorcurrentexceedingspecifiedvalue? YES→Considerreducingloadandincreasinginverterandmotorcapacities;NO→Motorrunningatlowspeedforlongtime? YES→Selectmotoragain;NO→MotorvoltagebetweenU-V,V-W,W-Ucorrect? NO→INVfaults;YES→Deterrencepreventingmotorcooling? YES→Cleardeterrence;NO→Badconnectionbetweendriveandmotor? YES→Correctbadconnection. No furtherNOendpoint shown;do notaddone.
Adjacent source context — repeated to preserve continuation:
Manual — 10.7.6 Motor unbalanced flowchart — page 552
Manual reference: physical PDF page 552. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.7.6 Motor runs unbalanced
NO
YES
Does it happen during eceleration?
Motor runs unevenly
Is the acceleration time correct?
Are the output voltages between U-V,V-W,W-U balanced?
Is the load fluctuating?
Any mechanical vibration or gear backlash
Increase the Acc/ Dec time
Reduce the load.Increase capacities of INV and the motor.
INV faults
Reduce the load fluctuation or add a flywheel.
Inspect the mechanical system
Motorrunsunevenly sourceflowchart:Doesithappenduringeceleration? YES→Accelerationtimecorrect? NO→IncreaseAcc/Dectime,YES→Reduceload.IncreasecapacitiesofINVandmotor. NO→OutputvoltagesU-V,V-W,W-Ubalanced? NO→INVfaults;YES→Loadfluctuating? YES→Reduceloadfluctuationoraddflywheel;NO→Mechanicalvibrationorgearbacklash? YES→Inspectmechanicalsystem;NO→INVfaults. The source spells eceleration;no intendedword inferred.
Manual — 10.8 Routine/periodic inspection schedule — page 553
Manual reference: physical PDF page 553. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.8 Routine and periodic inspection
To ensure stable and safe operations, check and maintain the inverter at regular intervals. Use the checklist below to carry out inspection. Disconnect power after approximately 5 minutes to make sure no voltage is present on the output terminals before any inspection or maintenance.
10.8 Routine/periodic inspection schedule
Items / Details / Checking period / Methods / Criteria / Remedies — PDF page 553
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Items | Details | Checking period | Checking period | Methods | Criteria | Remedies |
| 2 | Items | Details | Daily | 1Year | Methods | Criteria | Remedies |
| 3 | Environment & Ground connection | Environment & Ground connection | Environment & Ground connection | Environment & Ground connection | Environment & Ground connection | Environment & Ground connection | Environment & Ground connection |
| 4 | Ambient conditions at the installation | Confirm the temperature and humidity at the machine | ◎ | ⟦blank source cell⟧ | Measure with thermometer and hygrometer | Temperature: -10 ~40°C/50°C (14~104°F)/(122°F) Humidity: Below 95%RH | Improve the ambient or relocate the drive to a better area. |
| 5 | Installation Grounding | Is the grounding resistance correct? | ⟦blank source cell⟧ | ◎ | Measure the resistance with a multi-tester | 200Vclass: below 100Ω | Improve the grounding if needed. |
| 6 | Terminals & Wiring | Terminals & Wiring | Terminals & Wiring | Terminals & Wiring | Terminals & Wiring | Terminals & Wiring | Terminals & Wiring |
| 7 | Connection terminals | Any loose parts or terminals? | ⟦blank source cell⟧ | ◎ | Visual check Check with a screwdriver | Correct installation requirement | Secure terminals and remove rust |
| 8 | Connection terminals | Any damage to the base ? | ⟦blank source cell⟧ | ◎ | Visual check Check with a screwdriver | Correct installation requirement | Secure terminals and remove rust |
| 9 | Connection terminals | Any corroded Terminals? | ⟦blank source cell⟧ | ◎ | Visual check Check with a screwdriver | Correct installation requirement | Secure terminals and remove rust |
| 10 | Wiring | Any broken wires? | ⟦blank source cell⟧ | ◎ | Visual check | Correct wiring requirement | Rectify as necessary |
| 11 | Wiring | Any damage to the wire insulation? | ⟦blank source cell⟧ | ◎ | Visual check | Correct wiring requirement | Rectify as necessary |
| 12 | voltage | voltage | voltage | voltage | voltage | voltage | voltage |
| 13 | Input power voltage | Is the voltage of the main circuit correct? | ◎ | ⟦blank source cell⟧ | Measure the voltage with a multi-tester | Voltage must conform with the spec. | Improve input voltage if necessary. |
| 14 | Circuit boards and components | Circuit boards and components | Circuit boards and components | Circuit boards and components | Circuit boards and components | Circuit boards and components | Circuit boards and components |
| 15 | Printed circuit board | Any contamination or damage to printed circuit board? | ⟦blank source cell⟧ | ◎ | Visual check | Correct component condition | Clean or replace the circuit board |
| 16 | Power component | Any dust or debris | ⟦blank source cell⟧ | ◎ | Visual check | Correct component condition | Clean components |
| 17 | Power component | Check resistance between terminals | ⟦blank source cell⟧ | ◎ | Measure with a multi-tester | No short circuit or broken circuit in three phase output | Consult with the supplier |
| 18 | Cooling System | Cooling System | Cooling System | Cooling System | Cooling System | Cooling System | Cooling System |
| 19 | Cooling fan | Unusual vibration and noise? | ⟦blank source cell⟧ | ◎ | Visual and sound check | Correct cooling | Consult with the supplier |
| 20 | Cooling fan | Excessive dust or debris | ◎ | ⟦blank source cell⟧ | Visual check | Correct cooling | Clean the fan |
| 21 | Heat sink | Excessive dust or debris | ◎ | ⟦blank source cell⟧ | Visual check | Correct cooling | Clean up debris or dust |
| 22 | Ventilation Path | Is the ventilation path blocked? | ◎ | ⟦blank source cell⟧ | Visual check | Correct cooling | Clear the path |
Manual — 10.9 Maintenance checklist and insulationtest source diagrams — page 554
Manual reference: physical PDF page 554. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
10.9 Maintenance
To ensure long-term reliability, follow the instructions below to perform regular inspection. Turn the power off and wait for a minimum of 5 minutes before inspection to avoid potential shock hazard from the charge stored in high-capacity capacitors. 1. Maintenance Check List. Ensure that temperature and humidity around the inverters is as required in the instruction manual, installed away from any sources of heat and the correct ventilation is provided.. For replacement of a failed or damaged inverter consult with the local supplier. Ensure that the installation area is free from dust and any other contamination. Check and ensure that the ground connections are secure and correct. Terminal screws must be tight, especially on the power input and output of the inverter. Do not perform any insulation test on the control circuit. 2. Insulation test Method . Single Phase
Three Phase
InsulationtestMethod SinglePhase source diagram labels:PowerSource,L1(L),L3(N),INV,T1,T2,T3,Motor,DielectricWithstandVoltageTest,groundsymbol. Visible terminal-link shapes retained in sourceimage;no testvoltage, wiring prescription or topology inferred.
InsulationtestMethod ThreePhase source diagram labels:PowerSource,L1(L),L2,L3(N),INV,T1,T2,T3,Motor,DielectricWithstandVoltageTest,groundsymbol. Sourceimage preserves terminal-link shapes;no testvoltage or wiring implementation inferred.
Manual — 11.1 Braking resistors/units;Table11.1.1 200V — page 555
Manual reference: physical PDF page 555. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Chapter 11 Inverter Peripheral devices and Options
11.1 Braking Resistors and Braking Units
Inverters ratings 200V 1~25HP / 400V 1~40HP(For Standard H & C type) / 400V 1~30HP(For Enhanced E & G type) / 575V 1~10HP/ 690V 15~40HP have a built-in braking transistor. For applications requiring a greater braking torque an external braking resistor can be connected to terminals B1 / P and B2; for inverter ratings above 200V 30HP / 400V 50HP(For Standard H & C type) / / 400V 40HP(For Enhanced E & G type) / 600V 50HP, an external braking unit (connected to - of the inverter) and a braking resistor (connected to two ends of the detection module BR - BR) is required.
Table 11.1.1 List of braking resistors and braking units
11.1 Braking resistors/units;Table11.1.1 200V
Inverter / Braking unit / Braking resistor / Braking torque (Peak / Continues) 10%ED / Minimum Resistance*1 — PDF page 555
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) | Physical column 12 (source headings retained in rows) | Physical column 13 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Inverter | Inverter | Inverter | Braking unit | Braking unit | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking torque (Peak / Continues) 10%ED | Minimum Resistance*1 | Minimum Resistance*1 |
| 2 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 3 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 4 | 200V 1 Ø /3 Ø | 1 | 0.75 | - | - | JNBR-100W200 | 100W/200Ω | 1 | 100W/200Ω (196*28*60) | 1 | 119% | 17Ω | 1000W |
| 5 | 200V 1 Ø /3 Ø | 2 | 1.5 | - | - | JNBR-200W100 | 200W/100Ω | 1 | 200W/100Ω (274*35*76) | 1 | 119% | 17Ω | 1000W |
| 6 | 200V 1 Ø /3 Ø | 3 | 2.2 | - | - | JNBR-260W70 | 260W/70Ω | 1 | 260W/70Ω (274*40*78) | 1 | 115% | 17Ω | 1000W |
| 7 | 200V 3 Ø | 5 | 3.7 | - | - | JNBR-450W40 | 450W/40Ω | 1 | 450W/40Ω (320*40*78) | 1 | 119% | 17Ω | 1000W |
| 8 | 200V 3 Ø | 7.5 | 5.5 | - | - | JNBR-600W28 | 600W/28Ω | 1 | 600W/28Ω (395*40*78) | 1 | 115% | 17Ω | 1000W |
| 9 | 200V 3 Ø | 10 | 7.5 | - | - | JNBR-900W20 | 900W/20Ω | 1 | 900W/20Ω (470*50*100) | 1 | 119% | 10.2 Ω | 1800W |
| 10 | 200V 3 Ø | 15 | 11 | - | - | JNBR-1R5KW13R6 | 1500W/13.6Ω | 1 | 1500W/13.6Ω (615*60*110) | 1 | 117% | 10.2 Ω | 1800W |
| 11 | 200V 3 Ø | 20 | 15 | - | - | JNBR-2KW10 | 2000W/10Ω | 1 | 2000W/10Ω (722*65*115) | 1 | 119% | 6.8Ω | 2600W |
| 12 | 200V 3 Ø | 25 | 18.5 | - | - | JNBR-2R4KW8 | 2400W/8Ω | 1 | 1200W/16Ω (535*60*110) | 2 parallel | 119% | 6.8Ω | 2600W |
| 13 | 200V 3 Ø | 30 | 22 | JNTBU-230 | 1 | JNBR-3KW6R8 | 3000W/6.8Ω | 1 | 1500W/13.6Ω (615*60*110) | 2 parallel | 120% | 5.5 Ω | 3300W |
| 14 | 200V 3 Ø | 40 | 30 | JNTBU-230 | 2 | JNBR-2KW10 | 2000W/10Ω | 2 | 2000W/10Ω (722*65*115) | 1 | 122% | 5.5 Ω | 3300W |
| 15 | 200V 3 Ø | 50 | 37 | JNTBU-230 | 2 | JNBR-2KW10 | 2000W/10Ω | 2 | 2000W/10Ω (722*65*115) | 1 | 102% | 5.5 Ω | 3300W |
| 16 | 200V 3 Ø | 50 | 37 | JNTBU-260 | 1 | JNBR-6KW5 | 6000W/5Ω | 1 | 1500W/20Ω (615*60*110) | 4 parallel | 105% | 3.8 Ω | 4500W |
| 17 | 200V 3 Ø | 60 | 45 | JNTBU-230 | 2 | JNBR-3KW6R8 | 3000W/6.8Ω | 2 | 1500W/13.6Ω (615*60*110) | 2 parallel | 120% | 5.5 Ω | 3300W |
Manual — Braking resistor/unit table continuation and400V3phase — page 556
Manual reference: physical PDF page 556. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Braking resistor/unit table continuation and400V3phase
Inverter / Braking unit / Braking resistor / Braking torque (Peak / Continues) 10%ED / Minimum Resistance*1 — PDF page 556
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) | Physical column 12 (source headings retained in rows) | Physical column 13 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Inverter | Inverter | Inverter | Braking unit | Braking unit | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking torque (Peak / Continues) 10%ED | Minimum Resistance*1 | Minimum Resistance*1 |
| 2 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 3 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 4 | Input Voltage | HP | KW | JNTBU-260 | 1 | JNBR-7R5KW4 | 7500W/4Ω | 1 | 1500W/20Ω (615*60*110) | 5 parallel | 106% | 3.8 Ω | 4500W |
| 5 | Input Voltage | 75 | 55 | JNTBU-230 | 2 | JNBR-3KW6R8 | 3000W/6.8Ω | 2 | 1500W/13.6Ω (615*60*110) | 2 parallel | 100% | 5.5 Ω | 3300W |
| 6 | Input Voltage | 75 | 55 | JNTBU-260 | 2 | JNBR-4R5KW6R6 | 4500W/6.6Ω | 2 | 1500W/20Ω (615*60*110) | 3 parallel | 106% | 3.8Ω | 4500W |
| 7 | Input Voltage | 100 | 75 | JNTBU-230 | 3 | JNBR-3KW6R8 | 3000W/6.8Ω | 3 | 1500W/13.6Ω (615*60*110) | 2 parallel | 110% | 5.5Ω | 3300W |
| 8 | Input Voltage | 100 | 75 | JNTBU-260 | 2 | JNBR-6KW5 | 6000W/5Ω | 2 | 1500W/20Ω (615*60*110) | 4 parallel | 107% | 3.8 Ω | 4500W |
| 9 | Input Voltage | 125 | 90 | JNTBU-230 | 4 | JNBR-3KW6R8 | 3000W/6.8Ω | 4 | 1500W/13.6Ω (615*60*110) | 2 parallel | 116% | 5.5Ω | 3300W |
| 10 | Input Voltage | 125 | 90 | JNTBU-260 | 2 | JNBR-7R5KW4 | 7500W/4Ω | 2 | 1500W/20Ω (615*60*110) | 5 parallel | 110% | 3.8 Ω | 4500W |
| 11 | Input Voltage | 150 | 110 | JNTBU-230 | 4 | JNBR-3KW6R8 | 3000W/6.8Ω | 4 | 1500W/13.6Ω (615*60*110) | 2 parallel | 100% | 5.5Ω | 3300W |
| 12 | Input Voltage | 150 | 110 | JNTBU-260 | 2 | JNBR-7R5KW4 | 7500W/4Ω | 2 | 1500W/20Ω (615*60*110) | 5 parallel | 92% | 3.8 Ω | 4500W |
| 13 | 400V 3 Ø | 1 | 0.75 | - | - | JNBR-100W750 | 100W/750Ω | 1 | 100W/750Ω (196*28*60) | 1 | 126% | 110Ω | 700W |
| 14 | 400V 3 Ø | 2 | 1.5 | - | - | JNBR-200W400 | 200W/400Ω | 1 | 200W/400Ω (274*35*76) | 1 | 120% | 110Ω | 700W |
| 15 | 400V 3 Ø | 3 | 2.2 | - | - | JNBR-300W250 | 300W/250Ω | 1 | 300W/250Ω (320*40*78) | 1 | 126% | 93Ω | 800W |
| 16 | 400V 3 Ø | 5 | 3.7 | - | - | JNBR-500W150 | 500W/150Ω | 1 | 500W/150Ω (400*50*100) | 1 | 126% | 68Ω | 1100W |
| 17 | 400V 3 Ø | 7.5 | 5.5 | - | - | JNBR-700W110 | 700W/110Ω | 1 | 700W/110Ω (530*50*100) | 1 | 117% | 41Ω | 1800W |
| 18 | 400V 3 Ø | 10 | 7.5 | - | - | JNBR-900W80 | 900W/80Ω | 1 | 900W/80Ω (470*50*100) | 1 | 120% | 41Ω | 1800W |
| 19 | 400V 3 Ø | 15 | 11 | - | - | JNBR-1R6KW50 | 1600W/50Ω | 1 | 1600W/50Ω (615*60*110) | 1 | 126% | 41Ω | 1800W |
| 20 | 400V 3 Ø | 20 | 15 | - | - | JNBR-2KW40 | 2000W/40Ω | 1 | 2000W/40Ω (722*65*115) | 1 | 120% | 20.5 Ω | 3500W |
| 21 | 400V 3 Ø | 25 | 18.5 | - | - | JNBR-2R4KW32 | 2400W/32Ω | 1 | 1200W/64Ω (535*60*110) | 2 parallel | 120% | 13.5Ω | 5300W |
| 22 | 400V 3 Ø | 30 | 22 | - | - | JNBR-3KW27R2 | 3000W/27.2Ω | 1 | 1500W/13.6Ω (615*60*110) | 2 in series | 118% | 13.5Ω | 5300W |
| 23 | 400V 3 Ø | 40 | 30 | JNTBU-430- | 2 | JNBR-4KW20 | 4000W/20Ω | 1 | 2000W/40Ω (722*65*115) | 2 parallel | 120% | 19.2Ω | 3800W |
| 24 | 400V 3 Ø | 50 | 37 | JNTBU-430 | 2 | JNBR-2R4KW32 | 2400W/32Ω | 2 | 1200W/64Ω (535*60*110) | 2 parallel | 122% | 19.2Ω | 3800W |
Manual — Braking resistor/unit table continuation of400V rows; raw voltage blank retained — page 557
Manual reference: physical PDF page 557. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Braking resistor/unit table continuation of400V rows; raw voltage blank retained
Inverter / Braking unit / Braking resistor / Braking torque (Peak / Continues) 10%ED / Minimum Resistance*1 — PDF page 557
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) | Physical column 12 (source headings retained in rows) | Physical column 13 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Inverter | Inverter | Inverter | Braking unit | Braking unit | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking torque (Peak / Continues) 10%ED | Minimum Resistance*1 | Minimum Resistance*1 |
| 2 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 3 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 4 | Input Voltage | 60 | 45 | JNTBU-430 | 2 | JNBR-3KW27R2 | 3000W/27.2Ω | 2 | 1500W/13.6Ω (615*60*110) | 2 in series | 120% | 19.2Ω | 3800W |
| 5 | Input Voltage | 75 | 55 | JNTBU-430 | 2 | JNBR-4KW20 | 4000W/20Ω | 2 | 2000W/40Ω (722*65*115) | 2 parallel | 129% | 19.2Ω | 3800W |
| 6 | Input Voltage | 100 | 75 | JNTBU-430 | 3 | JNBR-3KW27R2 | 3000W/27.2Ω | 3 | 1500W/13.6Ω (615*60*110) | 2 in series | 110% | 19.2Ω | 3800W |
| 7 | Input Voltage | 100 | 75 | JNTBU-4120 | 1 | JNBR-9R6KW8R3 | 9600W/8.3Ω | 1 | 1600W/50Ω (615*60*110) | 6 parallel | 122% | 7.6Ω | 9000W |
| 8 | Input Voltage | 125 | 90 | JNTBU-430 | 3 | JNBR-4KW20 | 4000W/20Ω | 3 | 2000W/10Ω (722*65*115) | 2 in series | 118% | 19.2 Ω | 3800W |
| 9 | Input Voltage | 125 | 90 | JNTBU-4120 | 1 | JNBR-11R2KW7R2 | 11200W/7.2Ω | 1 | 1600W/50Ω (615*60*110) | 7 parallel | 118% | 7.6Ω | 9000W |
| 10 | Input Voltage | 150 | 110 | JNTBU-430 | 4 | JNBR-4KW20 | 4000W/20Ω | 4 | 2000W/10Ω (722*65*115) | 2 in series | 129% | 19.2 Ω | 3800W |
| 11 | Input Voltage | 150 | 110 | JNTBU-4120 | 2 | JNBR-6R4KW12R5 | 6400W/12.5Ω | 2 | 1600W/50Ω (615*60*110) | 4 parallel | 113% | 7.6Ω | 9000W |
| 12 | Input Voltage | 175 | 132 | JNTBU-430 | 4 | JNBR-4KW20 | 4000W/20Ω | 4 | 2000W/10Ω (722*65*115) | 2 in series | 113% | 19.2 Ω | 3800W |
| 13 | Input Voltage | 175 | 132 | JNTBU-4120 | 2 | JNBR-8KW10 | 8000W/10Ω | 2 | 1600W/50Ω (615*60*110) | 5 parallel | 117% | 7.6Ω | 9000W |
| 14 | Input Voltage | 215 | 160 | JNTBU-430 | 5 | JNBR-4KW20 | 4000W/20Ω | 5 | 2000W/10Ω (722*65*115) | 2 in series | 115% | 19.2 Ω | 3800W |
| 15 | Input Voltage | 215 | 160 | JNTBU-4120 | 2 | JNBR-9R6KW8R3 | 9600W/8.3Ω | 2 | 1600W/50Ω (615*60*110) | 6 parallel | 124% | 7.6Ω | 9000W |
| 16 | Input Voltage | 270 | 200 | JNTBU-430 | 6 | JNBR-4KW20 | 4000W/20Ω | 6 | 2000W/10Ω (722*65*115) | 2 in series | 111% | 19.2 Ω | 3800W |
| 17 | Input Voltage | 270 | 200 | JNTBU-4120 | 2 | JNBR-11R2KW7R2 | 11200W/7.2Ω | 2 | 1600W/50Ω (615*60*110) | 7 parallel | 115% | 7.6Ω | 9000W |
| 18 | Input Voltage | 300 | 220 | JNTBU-430 | 6 | JNBR-4KW20 | 4000W/20Ω | 6 | 2000W/10Ω (722*65*115) | 2 in series | 102% | 19.2 Ω | 3800W |
| 19 | Input Voltage | 300 | 220 | JNTBU-4120 | 3 | JNBR-9R6KW8R3 | 9600W/8.3Ω | 3 | 1600W/50Ω (615*60*110) | 6 parallel | 122% | 7.6Ω | 9000W |
| 20 | Input Voltage | 375 | 280 | JNTBU-430 | 8 | JNBR-4KW20 | 4000W/20Ω | 8 | 2000W/10Ω (722*65*115) | 2 in series | 107% | 19.2 Ω | 3800W |
| 21 | Input Voltage | 375 | 280 | JNTBU-4120 | 3 | JNBR-9R6KW8R3 | 9600W/8.3Ω | 3 | 1600W/50Ω (615*60*110) | 6 parallel | 105% | 7.6Ω | 9000W |
| 22 | Input Voltage | 425 | 315 | JNTBU-430 | 9 | JNBR-4KW20 | 4000W/20Ω | 9 | 2000W/10Ω (722*65*115) | 2 in series | 107% | 19.2 Ω | 3800W |
| 23 | Input Voltage | 425 | 315 | JNTBU-4120 | 4 | JNBR-8KW10 | 8000W/10Ω | 4 | 1600W/50Ω (615*60*110) | 5 parallel | 104% | 7.6Ω | 9000W |
Manual — A510-4040-S□3-B special braking row;575V/690V resistors;minimum-resistance footnote and heat warnings — page 558
Manual reference: physical PDF page 558. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
A510-4040-S□3-B model, please follow the table as below.
*1: Minimum resistance is the acceptable minimum value of the braking resistor for a single braking unit.
Note1: All resistors must be installed outside the drive module in a place where they can dissipate heat.
Note2: The surface temperature of the resistor is very high and air flowing from the resistor is very hot. Materials near the brake resistor must be non-flammable. Provide protection from accidental contact with the resistor
A510-4040-S□3-B special braking row;575V/690V resistors;minimum-resistance footnote and heat warnings
Inverter / Braking unit / Braking resistor / Braking torque (Peak / Continues) 10%ED / Minimum Resistance*1 — PDF page 558
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) | Physical column 12 (source headings retained in rows) | Physical column 13 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Inverter | Inverter | Inverter | Braking unit | Braking unit | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking torque (Peak / Continues) 10%ED | Minimum Resistance*1 | Minimum Resistance*1 |
| 2 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 3 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Resistor Spec.(W/Ω) & Dimensions (L*W*H)mm | Qty Req. (pcs) | Braking torque (Peak / Continues) 10%ED | (Ω) | (W) |
| 4 | 400V 3 Ø | 40 | 30 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | JNBR-4KW20 | 4000W/20Ω | 1 | 2000W/40Ω (722*65*115) | 2 parallel | 120% | 9.6Ω | 7600W |
Inverter / Braking unit / Braking resistor / Braking torque (Peak / Continues ) 10%ED / Minimum Resistance*1 — PDF page 558
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) | Physical column 12 (source headings retained in rows) | Physical column 13 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Inverter | Inverter | Inverter | Braking unit | Braking unit | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking resistor | Braking torque (Peak / Continues ) 10%ED | Minimum Resistance*1 | Minimum Resistance*1 |
| 2 | Input Voltage | HP | KW | Model | Qty Req. | Part Number | Resistor specification | Qty Req. (set) | Spec for one Resistor and dimensions (L*W*H) mm | Qty Req. (pcs) | Braking torque (Peak / Continues ) 10%ED | (Ω) | (W) |
| 3 | 575V 3Ф | 1 | 0.75 | ‐ | ‐ | ‐ | 150W/1400Ω | 1 | ⟦blank source cell⟧ | 1 | 120% | 130Ω | 1600W |
| 4 | 575V 3Ф | 2 | 1.5 | ‐ | ‐ | ‐ | 250W/800Ω | 1 | ⟦blank source cell⟧ | 1 | 120% | 130Ω | 1600W |
| 5 | 575V 3Ф | 3 | 2.2 | ‐ | ‐ | ‐ | 350W/600Ω | 1 | ⟦blank source cell⟧ | 1 | 120% | 130Ω | 1600W |
| 6 | 575V 3Ф | 5 | 3.7 | ‐ | ‐ | ‐ | 600W/350Ω | 1 | ⟦blank source cell⟧ | 1 | 120% | 130Ω | 1600W |
| 7 | 575V 3Ф | 7.5 | 5.5 | ‐ | ‐ | ‐ | 850W/240Ω | 1 | ⟦blank source cell⟧ | 1 | 120% | 130Ω | 1600W |
| 8 | 690V 3Ф | 15 | 11 | ‐ | ‐ | ‐ | 1600W/150Ω | 1 | ⟦blank source cell⟧ | 1 | 120% | 25Ω | 10000W |
| 9 | 690V 3Ф | 20 | 15 | ‐ | ‐ | ‐ | 2400W/110Ω | 1 | ⟦blank source cell⟧ | 1 | 120% | 25Ω | 10000W |
| 10 | 690V 3Ф | 25 | 18.5 | ‐ | ‐ | ‐ | 3000W/90Ω | 1 | ‐ | 1 | 120% | 25Ω | 10000W |
| 11 | 690V 3Ф | 30 | 22 | ‐ | ‐ | ‐ | 3300W/80Ω | 1 | ‐ | 1 | 120% | 25Ω | 10000W |
| 12 | 690V 3Ф | 40 | 30 | ‐ | ‐ | ‐ | 4400W/60Ω | 1 | ‐ | 1 | 120% | 25Ω | 10000W |
Manual — 11.2 AC line reactors;200V HD/ND input-side table — page 559
Manual reference: physical PDF page 559. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.2 AC Line Reactors
An AC line reactor can be used for any of the following:
- Capacity of power system is much larger than the inverter rating. - Inverter mounted close to the power system (in 33ft / 10 meters). - Reduce harmonic contribution (improve power factor) back to the power line. - Protect inverter input diode front-end by reducing short-circuit current. - Minimize overvoltage trips due to voltage transients. Please select the AC line reactor based on the inverter rating according to the following table.
Table 11.2.1 List of AC Line Reactors
11.2 AC line reactors;200V HD/ND input-side table
Model / AC reactor — PDF page 559
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | AC reactor | AC reactor |
| 2 | Input Voltage | HP | Rated Current(A) HD/ND | Inductance Value (mH) | Rated Current(A) |
| 3 | 200V 1Ø/3Ø | 1 | 5/6 | 1.7 | 15 |
| 4 | 200V 1Ø/3Ø | 2 | 8/9.6 | 1.1 | 20 |
| 5 | 200V 1Ø/3Ø | 3 | 11/12 | 0.85 | 25 |
| 6 | 200V 3Ø | 5.4 | 17.5/22 | 0.46 | 25 |
| 7 | 200V 3Ø | 7.5 | 25/30 | 0.34 | 40 |
| 8 | 200V 3Ø | 10 | 33/42 | 0.24 | 50 |
| 9 | 200V 3Ø | 15 | 47/56 | 0.18 | 70 |
| 10 | 200V 3Ø | 20 | 60/69 | 0.15 | 85 |
| 11 | 200V 3Ø | 25 | 73/79 | 0.13 | 95 |
| 12 | 200V 3Ø | 30 | 85/110 | 0.09 | 140 |
| 13 | 200V 3Ø | 40 | 115/138 | 0.07 | 170 |
| 14 | 200V 3Ø | 50 | 145/169 | 0.06 | 210 |
| 15 | 200V 3Ø | 60 | 180/200 | 0.05 | 250 |
| 16 | 200V 3Ø | 75 | 215/250 | 0.04 | 310 |
| 17 | 200V 3Ø | 100 | 283/312 | 0.03 | 390 |
| 18 | 200V 3Ø | 125 | 346/400 | 0.03 | 490 |
| 19 | 200V 3Ø | 150 | 415/450 | 0.02 | 550 |
Manual — AC line reactors400V HD/ND table — page 560
Manual reference: physical PDF page 560. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 11.2.1 List of AC Line Reactors (continued)
AC line reactors400V HD/ND table
Model / AC reactor — PDF page 560
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | AC reactor | AC reactor |
| 2 | Input Voltage | HP | Rated Current(A) HD/ND | Inductance Value (mH) | Rated Current(A) |
| 3 | 400V 3Ø | 1 | 3.4/4.1 | 4.9 | 5 |
| 4 | 400V 3Ø | 2 | 4.2/5.4 | 3.7 | 6.5 |
| 5 | 400V 3Ø | 3 | 5.5/6.9 | 2.9 | 8.5 |
| 6 | 400V 3Ø | 5.4 | 9.2/12.1 | 1.7 | 15 |
| 7 | 400V 3Ø | 7.5 | 14.8/17.5 | 1.2 | 25 |
| 8 | 400V 3Ø | 10 | 18/23 | 0.88 | 30 |
| 9 | 400V 3Ø | 15 | 24/31 | 0.65 | 40 |
| 10 | 400V 3Ø | 20 | 31/38 | 0.53 | 50 |
| 11 | 400V 3Ø | 25 | 39/44 | 0.46 | 55 |
| 12 | 400V 3Ø | 30 | 45/58 | 0.35 | 70 |
| 13 | 400V 3Ø | 40 | 60/73 | 0.28 | 90 |
| 14 | 400V 3Ø | 50 | 75/88 | 0.23 | 110 |
| 15 | 400V 3Ø | 60 | 91/103 | 0.2 | 130 |
| 16 | 400V 3Ø | 75 | 118/145 | 0.14 | 180 |
| 17 | 400V 3Ø | 100 | 150/168 | 0.12 | 210 |
| 18 | 400V 3Ø | 125 | 180/208 | 0.1 | 260 |
| 19 | 400V 3Ø | 150 | 216/250 | 0.08 | 310 |
| 20 | 400V 3Ø | 175 | 260/296 | 0.07 | 360 |
| 21 | 400V 3Ø | 215 | 295/328 | 0.06 | 400 |
| 22 | 400V 3Ø | 270 | 370/435 | 0.05 | 550 |
| 23 | 400V 3Ø | 300 | 450/515 | 0.04 | 630 |
| 24 | 400V 3Ø | 375 | 523/585 | 0.04 | 720 |
| 25 | 400V 3Ø | 425 | 585/585 | 0.04 | 720 |
Manual — AC line reactors575V/690V and built-in DC reactor note — page 561
Manual reference: physical PDF page 561. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 11.2.1 List of AC Line Reactors (continued)
Note: AC reactors listed in this table can only be used for the inverter input side. Do not connect AC reactor to the inverter
output side. Both 200V class 50HP ~ 150HP and 400V class 100HP ~ 425HP and 600V class 100HP~300HP have a built-in
DC reactors. If required by the application an AC reactor may be added.
AC line reactors575V/690V and built-in DC reactor note
Model / AC reactor — PDF page 561
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | AC reactor | AC reactor |
| 2 | Input Voltage | HP | Rated Current(A) HD/ND | Specification (mH) | Rated Current(A) |
| 3 | 575V 3Ø | 1 | 1.7/3.0 | 2.0 | 15 |
| 4 | 575V 3Ø | 2 | 3/4.2 | 2.0 | 15 |
| 5 | 575V 3Ø | 3 | 4.2/5.8 | 2.0 | 15 |
| 6 | 575V 3Ø | 5.4 | 6.6/8.8 | 2.0 | 15 |
| 7 | 575V 3Ø | 7.5 | 9.9/12.2 | 2.0 | 15 |
| 8 | 575V 3Ø | 10 | 11.4/14.5 | 2.0 | 15 |
| 9 | 690V 3Ø | 15 | 15/19 | 1.5 | 35 |
| 10 | 690V 3Ø | 20 | 19/22 | 1.5 | 35 |
| 11 | 690V 3Ø | 25 | 22/27 | 1.5 | 35 |
| 12 | 690V 3Ø | 30 | 27/34 | 1.5 | 35 |
| 13 | 690V 3Ø | 40 | 34/42 | 0.84 | 60 |
| 14 | 690V 3Ø | 50 | 42/52 | 0.84 | 60 |
| 15 | 690V 3Ø | 60 | 54/62 | 0.84 | 60 |
| 16 | 690V 3Ø | 75 | 62/80 | 0.45 | 100 |
| 17 | 690V 3Ø | 100 | 86/99 | 0.45 | 100 |
| 18 | 690V 3Ø | 125 | 99/125 | 0.30 | 200 |
| 19 | 690V 3Ø | 150 | 131/147 | 0.30 | 200 |
| 20 | 690V 3Ø | 175 | 147/163 | 0.30 | 200 |
| 21 | 690V 3Ø | 215 | 163/212 | 0.30 | 200 |
| 22 | 690V 3Ø | 250 | 192/216 | 0.15 | 300 |
| 23 | 690V 3Ø | 270 | 216/246 | 0.15 | 300 |
Manual — 11.3 Input noise filters200V/400V;20HP plug-in exception — page 562
Manual reference: physical PDF page 562. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.3 Input Noise Filters
A. Input Noise Filter on Specifications & Ratings Install a noise filter on power supply side to eliminate noise transmitted between the power line and the inverter. The inverter noise filter shown in Table 11.4.1 below meets the EN61800-3 class A specification. 400V inverter class models can be ordered with integrated noise filter.
Table 11.4.1 Input Noise Filter Specifications and Ratings
*1: This model of 20 HP is not built-in filter. If customer would like to install the filter, the plug-in mode is allowable instead of the built-in mode.
11.3 Input noise filters200V/400V;20HP plug-in exception
Inverter size / Noise filter — PDF page 562
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Inverter size | Inverter size | Noise filter | Noise filter |
| 2 | Input voltage | HP | Model | Dimension |
| 3 | 200V 1Ø | 1HP/2HP | FS32124-23-99 | 350*100*55 |
| 4 | 200V 1Ø | 3HP | FN3258-16-45 | 264*45*70 |
| 5 | 200V 3Ø | 1HP/2HP | FN3258-16-45 | 264*45*70 |
| 6 | 200V 3Ø | 3HP | FN3258-16-45 | 264*45*70 |
| 7 | 200V 3Ø | 5HP | FS3258-42-47 | 330*50*85 |
| 8 | 200V 3Ø | 7.5HP | FN3258-42-47 | 330*50*85 |
| 9 | 200V 3Ø | 10HP | FS32123-40-99 | 330*85*90 |
| 10 | 200V 3Ø | 15HP | FS32125-56-99 | 318*80*135 |
| 11 | 200V 3Ø | 20HP/25HP | FS32125-79-99 | 360*95*90 |
| 12 | 200V 3Ø | 30HP/40HP | FS32125-138-99 | 320*226.5*86 |
| 13 | 200V 3Ø | 50HP/60HP | FS32125-211-99 | 320*226.5*86 |
| 14 | 200V 3Ø | 75HP/100HP | FS32125-312-99 | 320*226.5*86 |
| 15 | 200V 3Ø | 125HP/150HP | FN3270H-1000-99 | 610*230*132 |
| 16 | 400V 3Ø | 1HP/2HP/3HP | JN5-FLT-8A | 102*130*92 |
| 17 | 400V 3Ø | 5HP/7.5HP | JN5-FLT-19A | 123*141*92 |
| 18 | 400V 3Ø | 10HP/15HP | JN5-FLT-33A | 132*206*124 |
| 19 | 400V 3Ø | 20HP*1 | FN3258-42-47 | 330*50*85 |
| 20 | 400V 3Ø | 20HP/25HP/30HP | JN5-FLT-63A | 127*260*131 |
| 21 | 400V 3Ø | 40HP/50HP/60HP | JN5-FLT-112A | 186*284*128 |
| 22 | 400V 3Ø | 75HP | FN3258-180-40 | 452*120*170 |
| 23 | 400V 3Ø | 100HP | FS32126-165-99 | 320*226.5*86 |
| 24 | 400V 3Ø | 125HP/150HP/175HP/215HP | FS32126-361-99 | 320*226.5*86 |
| 25 | 400V 3Ø | 270HP/300HP/375HP/425HP | FN3270H-1000-99 | 610*230*132 |
Manual — Input noise filter575V/690V continuation — page 563
Manual reference: physical PDF page 563. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Input noise filter575V/690V continuation
Inverter size / Noise filter — PDF page 563
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Inverter size | Inverter size | Noise filter | Noise filter |
| 2 | Input voltage | HP | Model | Dimension |
| 3 | 575V 3Ø | 1HP/2HP/3HP/5HP | FN258HV-7-29 | 255*50*126 |
| 4 | 575V 3Ø | 7.5HP/10HP | FN258HV-16-29 | 305*55*142 |
| 5 | 690V 3Ø | 15HP/20HP/25HP/30HP | FN258HV-30-33 | 335*60*150 |
| 6 | 690V 3Ø | 40HP | FN258HV-42-33 | 329*70*185 |
| 7 | 690V 3Ø | 50HP/60HP | FN258HV-55-34 | 329*80*185 |
| 8 | 690V 3Ø | 75HP | FN258HV-75-34 | 329*80*220 |
| 9 | 690V 3Ø | 100HP/125HP | FN258HV-100-35 | 379*90*220 |
| 10 | 690V 3Ø | 150HP | FN258HV-130-35 | 439*110*240 |
| 11 | 690V 3Ø | 175HP | FN3359HV-150-28 | 300*210*120 |
| 12 | 690V 3Ø | 215HP | FN3359HV-180-28 | 300*210*120 |
| 13 | 690V 3Ø | 250HP/270HP | FN3359HV-250-28 | 300*230*125 |
Manual — Input/output EMI suppression zero-phase ferrite core;frequency plot and application — page 564
Manual reference: physical PDF page 564. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Clipped final frequency exponent and tiny keypad pictogram legends.
B. Input or Output Noise Filter (EMI Suppression Zero Phase Core)
- Part Number: 4H000D0250001 - Select a matched ferrite core to suppress EMI noise according to the required power rating and wire size. - The ferrite core can attenuate high frequencies in the range of 100 kHz to 50 MHz, as shown in figure 11.4.1 below, and therefore should minimize the RFI generated by the inverter. - The zero-sequence noise ferrite core can be installed either on the input side or on the output side. The wire around the core for each phase should be wound by following the same convention and in one direction. The more turns without resulting in saturation the better the attenuation. If the wire size is too large to be wound, all the wiring can be grouped and put through several cores together in one direction.
Fig. 11.4.1 Frequency attenuation characteristics (10 windings case)
Fig. 11.4.2 Example of EMI Suppression Zero Phase Core Application
Note: All the wiring of phases U/T1, V/T2, W/T3 must pass through the same zero-phase core without crossing over.
Fig11.4.1 frequency attenuation characteristics,10 windings case. Vertical Attenuation(dB):0,−10,−20,−30,−40. Horizontal Interference Frequency(kHz):10¹,10²,10³,10⁴;rightmost label clipped after visible10,exponent not inferred. Curve preserved inimage;no interpolated attenuation or final exponent assigned.
Fig11.4.2 EMI suppression zero-phase core application. Labels InductionMotor,Ground at drive andmotor. Drive pictogram display888.88;small key legends unresolved and not used as operationalsettings. Source winding graphic retained;no topology inferred. Associated native note requires phasesU/T1,V/T2,W/T3 throughsamecorewithoutcrossing.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Clipped rightmost graph exponent and tiny drive pictogram key legends unresolved.
Manual — 11.4 Input current and fuse specifications200V — page 565
Manual reference: physical PDF page 565. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.4 Input Current and Fuse Specifications
200V class
11.4 Input current and fuse specifications200V
Model / Horse power / KVA / 100% of rated output current HD/ND / 3 phases Rated input current HD/ND / Three-phase fuse rating / Single-phase rated input current HD/ND — PDF page 565
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Model | Horse power | KVA | 100% of rated output current HD/ND | 3 phases Rated input current HD/ND | Three-phase fuse rating | Single-phase rated input current HD/ND |
| 2 | A510-2001-S□ | 1 | 1.9 | 5/6 | 5.4/6.5 | 20 | 9.4/11.3 |
| 3 | A510-2002-S□ | 2 | 3 | 8/9.6 | 8.5/10.3 | 30 | 14.7/17.9 |
| 4 | A510-2003-S□ | 3 | 4.2 | 11/12 | 11.7/12.8 | 50 | 20.3/22.1 |
| 5 | A510-2005-S□3 | 5 | 6.7 | 17.5/22 | 18.7/22.3 | 50 | X |
| 6 | A510-2008-S□3 | 7.5 | 9.5 | 25/30 | 26.3/31.6 | 63 | X |
| 7 | A510-2010-S□3 | 10 | 12.6 | 33/42 | 34.5/41.7 | 100 | X |
| 8 | A510-2015-S□3 | 15 | 17.9 | 47/56 | 51.1/60.9 | 120 | X |
| 9 | A510-2020-S□3 | 20 | 22.9 | 60/69 | 65.2/75 | 150 | X |
| 10 | A510-2025-S□3 | 25 | 28.6 | 73/80 | 79.4/85.9 | 200 | X |
| 11 | A510-2030-S□3 | 30 | 32.4 | 85/110 | 92.4/119.6 | 250 | X |
| 12 | A510-2040-S□3 | 40 | 43.8 | 115/138 | 125/150 | 300 | X |
| 13 | A510-2050-S□3 | 50 | 55.3 | 145/169 | 159/186 | 400 | X |
| 14 | A510-2060-S□3 | 60 | 68.6 | 180/200 | 186/232 | 500 | X |
| 15 | A510-2075-S□3 | 75 | 81.9 | 215/250 | 232/275 | 600 | X |
| 16 | A510-2100-S□3 | 100 | 108 | 283/312 | 275/343 | 700 | X |
| 17 | A510-2125-S□3 | 125 | 132 | 346/400 | 380/440 | 800 | X |
| 18 | A510-2150-S□3 | 150 | 158 | 415/450 | 456/495 | 800 | X |
Manual — Input current and fuse specifications400V — page 566
Manual reference: physical PDF page 566. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
400V class
Input current and fuse specifications400V
Model / Horse power / KVA / 100% of rated output current HD/ND / Rated input current HD/ND / Fuse rating — PDF page 566
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Model | Horse power | KVA | 100% of rated output current HD/ND | Rated input current HD/ND | Fuse rating |
| 2 | A510-4001-S□3(F) | 1 | 2.6 | 3.4/4.1 | 3.7/4.5 | 10 |
| 3 | A510-4002-S□3(F) | 2 | 3.2 | 4.2/5.4 | 5.3/5.9 | 16 |
| 4 | A510-4003-S□3(F) | 3 | 4.2 | 5.5/6.9 | 6.0/7.5 | 16 |
| 5 | A510-4005-S□3(F) | 5 | 7 | 9.2/12.1 | 9.6/11.6 | 25 |
| 6 | A510-4008-S□3(F) | 7.5 | 11.3 | 14.8/17.5 | 15.5/18.2 | 40 |
| 7 | A510-4010-S□3(F) | 10 | 13.7 | 18/23 | 18.7/24.0 | 50 |
| 8 | A510-4015-S□3(F) | 15 | 18.3 | 24/31 | 25.0/32.3 | 63 |
| 9 | A510-4020-S□3(F) | 20 | 23.6 | 31/38 | 33.7/41.3 | 80 |
| 10 | A510-4025-S□3(F) | 25 | 29.7 | 39/44 | 42.4/47.8 | 100 |
| 11 | A510-4030-S□3(F) | 30 | 34.3 | 45/58 | 48.9/58.7 | 120 |
| 12 | A510-4040-S□3(F) | 40 | 45.7 | 60/73 | 65.2/78.3 | 150 |
| 13 | A510-4050-S□3(F) | 50 | 57.2 | 75/88 | 81.5/95.7 | 200 |
| 14 | A510-4060-S□3(F) | 60 | 69.3 | 91/103 | 98.9/112 | 250 |
| 15 | A510-4075-S□3 | 75 | 85.4 | 118/145 | 130/159 | 300 |
| 16 | A510-4100-S□3 | 100 | 114 | 150/168 | 159/181 | 400 |
| 17 | A510-4125-S□3 | 125 | 137 | 180/208 | 181/229 | 500 |
| 18 | A510-4150-S□3 | 150 | 165 | 216/250 | 229/275 | 600 |
| 19 | A510-4175-S□3 | 175 | 198 | 260/296 | 275/325 | 700 |
| 20 | A510-4215-S□3 | 215 | 225 | 295/328 | 325/361 | 700 |
| 21 | A510-4270-S□3 | 250 | 270 | 380/435 | 407/478 | 800 |
| 22 | A510-4300-S□3 | 300 | 317 | 450/515 | 495/566 | 800 |
| 23 | A510-4375-S□3 | 375 | 400 | 523/585 | 575/643 | 1000 |
| 24 | A510-4425-S□3 | 425 | 446 | 585/585 | 643.5/643.5 | 1000 |
Manual — Input current and fuse specifications600V class;fuse-type/voltage note — page 567
Manual reference: physical PDF page 567. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
600V class
Fuse type: Choose semiconductor fuse to comply with UL. Voltage Range: For 200V class inverter, use 300V class fuse. For 400V class inverter, use 600V class fuse.
Input current and fuse specifications600V class;fuse-type/voltage note
Model / Horse power / KVA / 100% of rated output current HD/ND / Rated input current HD/ND / Fuse rating — PDF page 567
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Model | Horse power | KVA | 100% of rated output current HD/ND | Rated input current HD/ND | Fuse rating |
| 2 | A510-5001-S□3 | 1 | 1.7 | 1.7/3.0 | 1.7/3.0 | 10 |
| 3 | A510-5002-S□3 | 2 | 3 | 3/4.2 | 3/4.2 | 10 |
| 4 | A510-5003-S□3 | 3 | 4.2 | 4.2/5.8 | 4.2/5.8 | 10 |
| 5 | A510-5005-S□3 | 5 | 6.6 | 6.6/8.8 | 6.6/8.8 | 15 |
| 6 | A510-5008-S□3 | 7.5 | 9.9 | 9.9/12.2 | 9.9/12.2 | 20 |
| 7 | A510-5010-S□3 | 10 | 11.4 | 11.4/14.5 | 11.4/14.5 | 20 |
| 8 | A510-6015-S□3 | 15 | 17.9 | 15/19 | 15/19 | 30 |
| 9 | A510-6020-S□3 | 20 | 22.7 | 19/22 | 19/22 | 40 |
| 10 | A510-6025-S□3 | 25 | 26.3 | 22/27 | 22/27 | 40 |
| 11 | A510-6030-S□3 | 30 | 32.3 | 27/34 | 27/34 | 50 |
| 12 | A510-6040-S□3 | 40 | 40. | 34/42 | 34/42 | 80 |
| 13 | A510-6050-S□3 | 50 | 50.2 | 42/52 | 42/52 | 80 |
| 14 | A510-6060-S□3 | 60 | 64.5 | 54/62 | 54/62 | 100 |
| 15 | A510-6075-S□3 | 75 | 74.1 | 62/80 | 62/80 | 125 |
| 16 | A510-6100-S□3 | 100 | 103 | 86/99 | 86/99 | 150 |
| 17 | A510-6125-S□3 | 125 | 118 | 99/125 | 99/125 | 200 |
| 18 | A510-6150-S□3 | 150 | 156 | 131/147 | 131/147 | 250 |
| 19 | A510-6175-S□3 | 175 | 175 | 147/163 | 147/163 | 300 |
| 20 | A510-6215-S□3 | 215 | 194 | 163/212 | 163/212 | 300 |
| 21 | A510-6250-S□3 | 270 | 229 | 192/216 | 192/216 | 400 |
| 22 | A510-6270-S□3 | 300 | 258 | 216/246 | 216/246 | 400 |
Manual — 11.5 PG speed feedback cards;standard/enhanced applicability,wire/torque andJN5-PG-O terminals — page 568
Manual reference: physical PDF page 568. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.5 PG Speed Feedback Card
Note: For Enhanced E & G type, all size of drive can support all the PG speed feedback card installation.
Refer to specified instruction manual for installation of each option card.
Refer to the dedicated option card manual for installation instructions. A) JN5-PG-O speed feedback card: Open collector speed feedback card JN5-PG-O terminal specification:
11.5 PG speed feedback cards;standard/enhanced applicability,wire/torque andJN5-PG-O terminals
ITEM / Encoder/Resolver Input Type / Output Type / Drive Installation (For Standard H&C type) — PDF page 568
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | ITEM | Encoder/Resolver Input Type | Output Type | Drive Installation (For Standard H&C type) | Drive Installation (For Standard H&C type) |
| 2 | ITEM | Encoder/Resolver Input Type | Output Type | SIZE 1 | >=SIZE 2 |
| 3 | JN5-PG-O | Open collector feedback card | Open collector | YES | YES |
| 4 | JN5-PG-L | Line driver speed feedback card | Line Driver | YES | YES |
| 5 | JN5-PG-L-24 | Line driver speed feedback card | Open collector | YES | YES |
| 6 | JN5-PG-PM | Synchronous motor line driver speed feedback card | Line Driver | No | YES |
| 7 | JN5-PG-PMR | Speed feedback card with TAMAGAWA Resolver | Line Driver | No | YES |
| 8 | JN5-PG-PMS | Speed feedback card with Heidenhain ERN 1387 Encoder Sin-Cos Incremental Encoder | Line Driver | No | YES |
| 9 | JN5-PG-PMS-24 | Speed feedback card with Heidenhain ERN 1387 Encoder Sin-Cos Incremental Encoder | Open collector | No | YES |
| 10 | JN5-PG-PMC | Speed feedback card with Heidenhain ECN 1313 Encoder 8192 (13bits) Absolute Encoder | Line Driver | No | YES |
| 11 | JN5-PG-PMC-24 | Speed feedback card with Heidenhain ECN 1313 Encoder 8192 (13bits) Absolute Encoder | Open collector | No | YES |
JN5-PG-O JN5-PG-L JN5-PG-L-24 JN5-PG-PM JN5-PG-PMR JN5-PG-PMS JN5-PG-PMS-24 JN5-PG-PMC JN5-PG-PMC-24 / Wiring Size / 24~16 AWG (0.205~1.31mm2) — PDF page 568
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | JN5-PG-O JN5-PG-L JN5-PG-L-24 JN5-PG-PM JN5-PG-PMR JN5-PG-PMS JN5-PG-PMS-24 JN5-PG-PMC JN5-PG-PMC-24 | Wiring Size | Wiring Size | 24~16 AWG (0.205~1.31mm2) |
| 2 | JN5-PG-O JN5-PG-L JN5-PG-L-24 JN5-PG-PM JN5-PG-PMR JN5-PG-PMS JN5-PG-PMS-24 JN5-PG-PMC JN5-PG-PMC-24 | Torque | TB1 | 0.22~0.25 N.M |
| 3 | JN5-PG-O JN5-PG-L JN5-PG-L-24 JN5-PG-PM JN5-PG-PMR JN5-PG-PMS JN5-PG-PMS-24 JN5-PG-PMC JN5-PG-PMC-24 | Torque | TB2 | 0.2 N.M |
Terminal Name / Description — PDF page 568
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Terminal Name | Description |
| 2 | Vcc | Power supply for encoder. 12V or 5V ±5%, 200mA Maximum (12V or 5V input voltage selected by the Switch Jumper. Can’t use both 12V and 5V at the same time) |
| 3 | GND (0V Common Terminal) | Power supply for encoder. 12V or 5V ±5%, 200mA Maximum (12V or 5V input voltage selected by the Switch Jumper. Can’t use both 12V and 5V at the same time) |
| 4 | A, /A, B, /B, Z, /Z | Encoder input signal, two-phase input is required for correct divider ratio output. Open collector input type. |
| 5 | AO, /AO, BO, /BO, ZO, /ZO | A ,B phase divider ratio output, z phase output monitor, Open collector type: 24V, 30mA. |
| 6 | E | Grounding Terminal. |
Manual — JN5-PG-O andJN5-PG-L/L-24 block diagrams;line-driver terminalspecifications — page 569
Manual reference: physical PDF page 569. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
JN5-PG-O block diagram:
B) JN5-PG-L / JN5-PG-L-24 speed feedback card: Line driver speed feedback card JN5-PG-L / JN5-PG-L-24 terminal specification
Note: The AO, /AO, BO, /BO, ZO, /ZO of JN5-PG-L-24 are open collector type output. JN5-PG-L / JN5-PG-L-24 block diagram:
JN5-PG-O block diagram labels:AO,/AO,BO,/BO,ZO,/ZO,GND,VPP(repeated),CPLD,VCC,GND,A,/A,B,/B,Z,/Z. Three10klabels andsix300labels. Source component symbols andground marks preserved inimage;no wiringorcomponentselection inferred.
JN5-PG-L/JN5-PG-L-24 blockdiagram labels:AO,/AO,BO,/BO,ZO,/ZO;AM26LS31CDR;GND;VPP(repeated);CPLD;AM26LS32;VCC;GND;A,/A,B,/B,Z,/Z. Three1.24k andsix1klabels. Source topology not reconstructed.
JN5-PG-O andJN5-PG-L/L-24 block diagrams;line-driver terminalspecifications
Terminal Name / Description — PDF page 569
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Terminal Name | Description |
| 2 | Vcc | Power supply for encoder. 12V or 5V ±5%, 200mA Maximum (12V or 5V input voltage selected by the Switch Jumper. Can’t use both 12V and 5V at the same time) |
| 3 | GND (0V Common Terminal) | Power supply for encoder. 12V or 5V ±5%, 200mA Maximum (12V or 5V input voltage selected by the Switch Jumper. Can’t use both 12V and 5V at the same time) |
| 4 | A, /A, B, /B, Z, /Z | Encoder input signal, A correct divider ratio output requires a two-phase input. Line driver input type, RS-422 level input. |
| 5 | AO, /AO, BO, /BO, ZO, /ZO | A ,B phase divider ratio output, z phase output monitor, Line driver output type, RS-422 level output. |
| 6 | E | Grounding terminal. |
Manual — JN5-PG-PM synchronous motor feedback terminal table and raster schematic — page 570
Manual reference: physical PDF page 570. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny raster schematic component reference/value text.
C) JN5-PG-PM speed feedback card: synchronous motor line driver speed feedback card JN5-PG-PM terminal specification
JN5-PG-PM block diagram:
JN5-PG-PM raster schematic. Visible terminalsTB1:AO,/AO,BO,/BO,ZO,/ZO,E;TB2A:VCC,GND,A,/A,B,/B,Z,/Z;TB2B:U,/U,V,/V,W,/W. IC/logic and resistor/capacitor reference/value text is small,pixelated;4x crops preserve it but not all can be read reliably. Full component-level transcription remains pending;no hidden values or wiring inferred. Terminal table is separately transcribed exactly,including its different U,/U,V,/V,Z,/Z wording.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny raster schematic component references/value pairs not all readable after4x crops;terminal table and visible terminal labels preserved.
12V
IC1
IC2
IC3
R11
R12
R13
R14
R15
R16
R17
R18
R19
IC4
IC5
+5V
R20
R21
R22
R23
R24
R25
JN5-PG-PM synchronous motor feedback terminal table and raster schematic
Terminal Name / Description — PDF page 570
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Terminal Name | Description |
| 2 | Vcc | Power supply for encoder. 5V ±5%, 200mA Maximum |
| 3 | GND (0V Common Terminal) | Power supply for encoder. 5V ±5%, 200mA Maximum |
| 4 | A, /A, B, /B, Z, /Z U, /U, V, /V, Z, /Z | Encoder input signal, A correct divider ratio output requires a two-phase input. Line driver input type, RS-422 level input. |
| 5 | AO, /AO, BO, /BO, ZO, /ZO | A ,B phase divider ratio output, z phase output monitor, Line driver output type, RS-422 level output. |
| 6 | E | Grounding terminal. |
Manual — JN5-PG-PMR TAMAGAWA resolver terminals and diagram — page 571
Manual reference: physical PDF page 571. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
D) JN5-PG-PMR speed feedback card with TAMAGAWA Resolver Encoder JN5-PG-PMR terminal specification
JN5-PG-PMR source diagram labels:JN5-PG-PMR;R1,R2;S1,S3;S2,S4;Resolver;a+,a−,b+,b−,z+,z−. Diagram usesR1/R2 whiletableusesR+/R−;do notreplace either. Lines retained only as source graphic.
JN5-PG-PMR TAMAGAWA resolver terminals and diagram
Terminal Name / Description — PDF page 571
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Terminal Name | Description |
| 2 | R+, R- | Excitation signal to Resolver. 7Vrms, 10KHz. |
| 3 | S1, S3 | COS signals from Resolver. |
| 4 | S2, S4 | SIN signals from Resolver. |
| 5 | a+, a-, b+, b-, z+, z- | A,B,Z pulse Monitor signal output, Line driver output Type,RS-422 level. |
| 6 | E | Grounding terminal |
Manual — JN5-PG-PMS/PMS-24 Heidenhain ERN1387 terminalspecifications — page 572
Manual reference: physical PDF page 572. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
E) JN5-PG-PMS/JN5-PG-PMS-24 speed feedback card with Heidenhain ERN 1387 Encoder JN5-PG-PMS / JN5-PG-PMS-24 terminal specification
Note: The a+, a-, b+, b- of JN5-PG-PMS-24 are open collector type output.
Source interface diagram:ENCORDER,JN5-PG-PMS,Vi,Vo,A+,B+,R+ upperline;A−,B−,R− lowerline;A,B,R beside downwardarrow. Resistor/capacitor/amplifier symbols retained without numeric values or inferred wiring.
JN5-PG-PMS/PMS-24 Heidenhain ERN1387 terminalspecifications
Terminal Name / Description — PDF page 572
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Terminal Name | Description |
| 2 | E5V | Power supply for encoder. 5V±5%, 200mA |
| 3 | GND | 0V Common Terminal |
| 4 | C+,C- | input C pulse from the encoder, Vp-p= 0.6~1.2V |
| 5 | D+, D- | input D pulse from the encoder, Vp-p= 0.6~1.2V |
| 6 | A+, A- | input A pulse from the encoder, Vp-p= 0.6~1.2V, fmax=20KHz |
| 7 | B+, B- | input B pulse from the encoder, Vp-p= 0.6~1.2V, fmax=20KHz |
| 8 | R+, R- | input R pulse (encoder home pulse) |
| 9 | a+, a- | output a ratio of the A pulse frequency |
| 10 | b+, b- | output b ratio of the B pulse frequency |
Manual — JN5-PG-PMC/PMC-24 Heidenhain ECN1313 terminalspecifications — page 573
Manual reference: physical PDF page 573. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
F. JN5-PG-PMC/JN5-PG-PMC-24 speed feedback card with Heidenhain ECN 1313 Encoder JN5-PG-PMC / JN5-PG-PMC-24 terminal specification
Note: The a+, a-, b+, b- of JN5-PG-PMS-24 are open collector type output.
Source interface diagram:ENCORDER,JN5-PG-PMC,Vi,Vo,A+,B+ upperline,A−,B− lowerline;A,B beside downwardarrow. Component symbols retained;no unprinted values inferred.
JN5-PG-PMC/PMC-24 Heidenhain ECN1313 terminalspecifications
Terminal Name / Description — PDF page 573
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Terminal Name | Description |
| 2 | E5V | Power supply for encoder. 5V±5%, 200mA |
| 3 | GND | 0V Common Terminal |
| 4 | DATA+/- | Bi-direct data for the encoder, RS485 driver. |
| 5 | CLOCK+/- | output clock to the encoder, line driver RS422 output |
| 6 | A+, A- | input A pulse from the encoder, Vp-p= 0.6~1.2V, fmax=20KHz |
| 7 | B+, B- | input B pulse from the encoder, Vp-p= 0.6~1.2V, fmax=20KHz |
| 8 | a+/a-, b+/b- | line driver RS422 output( a ratio of the A,B pulse frequency) |
Manual — 11.6 Blank cover/keypad extension cable models and lengths — page 574
Manual reference: physical PDF page 574. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.6 Other Options
A. Blank cover and keypad extension cable When used for remote control purposes, the keypad can be removed and remotely connected with an extension cable. Extension cables are available in the following lengths: 1m (3.3ft), 2m (6.6ft), 3m (10ft), and 5m (16.4ft).
Remote control
When using a remote mount keypad a blank cover can be installed in place of the original keypad to prevent dust and debris from entering the inverter.
Remotecontrol figure shows keypad anddrive linked byextensioncable;caption Remotecontrol. No dimension orlength inferred from drawing;models/lengths in separate tables.
Blankkeypadcover outline andcaption Blankkeypadcover;no dimensions printed inthisfigure.
11.6 Blank cover/keypad extension cable models and lengths
Name / Model / Specification — PDF page 574
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Name | Model | Specification |
| 2 | LED digital operator wire with blank cover | JN5-CB-01MK | 1m (3.3ft) |
| 3 | LED digital operator wire with blank cover | JN5-CB-02MK | 2m (6.6ft) |
| 4 | LED digital operator wire with blank cover | JN5-CB-03MK | 3m (10ft) |
| 5 | LED digital operator wire with blank cover | JN5-CB-05MK | 5m (16.4ft) |
Name / Model / Specification — PDF page 574
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Name | Model | Specification |
| 2 | Blank cover | JN5-OP-A03 | Blank cover |
Name / Model / Specification — PDF page 574
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Name | Model | Specification |
| 2 | LED digital operator wire | JN5-CB-01M | 1m (3.3ft) |
| 3 | LED digital operator wire | JN5-CB-02M | 2m (6.6ft) |
| 4 | LED digital operator wire | JN5-CB-03M | 3m (10ft) |
| 5 | LED digital operator wire | JN5-CB-05M | 5m (16.4ft) |
Manual — LED/LCD keypad dimensions;JN5-CU copy unit dimensions;protectivecover — page 575
Manual reference: physical PDF page 575. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
LED/LCD keypad dimensions
B. Copy Unit (JN5-CU) The copy unit is used to copy an inverter parameter setup to another inverter. The copy unit saves time in applications with multiple inverters requiring the same parameter setup.
Copy Unit (JN5-CU) dimensions and appearance C. Option Protective Cover The installation environment will have a direct affect on the correct operation and the life span of the inverter. To obtain maximum service life inverter shall be installed in a suitable environment as specified in this manual. Chapter 3.1.
Option cover may be used to provide protection against external objects entering the unit and restrict dust ingress. No temperature derate is necessary.
LED/LCDkeypad dimension figures. Front overallwidth85.0;horizontalmounting74.0;overallheight130.0;verticalmounting119.0;4-M3. Side spans15.5 and9.9. Rear horizontalmounting74.0;vertical119.0;lowerconnectorheight21.5;bottomoffset21.2;horizontaloffset9.0 andconnectorwidth20.6. Unit not printed inthisbounded drawing;do notadd mm. Key labelsFAULT,FWD,REV,SEQ,REF;FWD/REV,uptriangle,DSP/FUN,lefttriangle/RESET,downtriangle,READ/ENTER,RUN,STOP. Sourcepicturegeometryretained.
JN5-CU copyunit dimensions andappearance:frontwidth62.0,height85.0;sidedepth14.2;lower-viewdepth22.7. Unit notprinted inboundedfigure. Display segment88888 example notoperationalvalue. LabelsSEQ,FRQ,FWD,REV,Hz/RPM,FUN,VOLT,AMP;upINV>CPM,MODE,downINV<CPM,leftarrow,RUN/CLEAR,STOP/RESET,OK/ENTER;JN5-CU CopyUnit. Physicaloutline andphotograph retained.
Manual — Protective cover models and installation;enhanced expansion cards/middle layer cases — page 576
Manual reference: physical PDF page 576. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Option cover part numbers:
D. High-speed communication expansion card & I/O expansion card & DC24V power card & Middle layer case If frame 1~4 of the enhanced inverter need to install encoder feedback card, high-speed communication expansion card, I/O expansion card or DC24V power card, middle layer case is necessary, which is option, to install between the top cover and the bottom case, for adding extra space to install the expansion card. For frame 2~4 of enhanced inverter, if only install encoder feedback card, middle layer case is not necessary to use. Table 1. Expansion card model number
ProtectiveCover→InstallationofProtectiveCover→InverterwithProtectiveCover source drawings/captions. Drawings illustrateposition withoutnewdimensions;no installationprocedure inferred fromarrows.
Protective cover models and installation;enhanced expansion cards/middle layer cases
Frame / Model — PDF page 576
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Frame | Model |
| 2 | 1 | JN5-CR-A01 |
| 3 | 2 | JN5-CR-A02 |
| 4 | 4 | JN5-CR-A04 |
Expansion card type / Model number / Reference chapter — PDF page 576
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Expansion card type | Model number | Reference chapter |
| 2 | PROFIBUS high-speed comm. | JN5-CMHI-PDP | 11.9 |
| 3 | CANopen high-speed comm. | JN5-CMHI-CAN | 11.10 |
| 4 | EtherCAT high-speed comm. | JN5-CMHI-ECAT | 11.11 |
| 5 | I/O expansion | JN5-IO-2DO1AI | 11.12 |
| 6 | DC24V power card | JN5-PS-DC24V | 11.15 |
Manual — Middle layer case models/depth increases and installation figures — page 577
Manual reference: physical PDF page 577. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Table 2. Middle layer case model number
Middlelayercaseoutline andMiddlelayercaseinstallationdiagram. Source explodedview retained;model/depthincrease table separate.
Communicationcardinstallationdiagram shows twoillustrations each labelledComm.card. Original arrows/screws shown inimage;no extraassemblyinstructions inferred.
Middle layer case models/depth increases and installation figures
Frame / Middle layer case model number / Note — PDF page 577
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Frame | Middle layer case model number | Note |
| 2 | 1 | JN5-MD-A01 | After installation, the depth (D) increases by 44mm |
| 3 | 2 | JN5-MD-A02 | After installation, the depth (D) increases by 31mm |
| 4 | 3 | JN5-MD-A03 | After installation, the depth (D) increases by 34mm |
| 5 | 4 | JN5-MD-A04 | After installation, the depth (D) increases by 35mm |
Manual — 11.7 Communication module references;11.8 NEMA1 kit — page 578
Manual reference: physical PDF page 578. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.7 Communication Modules
(a) PROFIBUS communication interface module (JN5-CM-PDP) For wiring example and communication setup refer to JN5-CM-PDP communication option manual. (b) DEVICENET communication interface module (JN5-CM-DNET) For wiring example and communication setup refer to JN5-CM-DNET communication option manual. (c) CANopen communication interface module (JN5-CM-CAN) For wiring example and communication setup refer to JN5-CM-CAN communication option manual. (d) TCP-IP communication interface module (JN5-CM-TCPIP) For wiring example and communication setup refer to JN5-CM-TCPIP communication option manual. (e) EtherNet/IP communication interface module (JN5-CM-EIP) For wiring example and communication setup refer to the contents of Chapter 11.17.
11.8 NEMA1 Kit
If NEMA1 or IP20 protective level is necessary to upgrade, it is recommended to purchase the NEMA1 kit positioned on top and bottom sides of the inverter. The drawings installed in the inverter, please refer to chapter 3.7.
11.7 Communication module references;11.8 NEMA1 kit
Frame / Model — PDF page 578
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Frame | Model |
| 2 | 6 | JN5-NK-A06 |
| 3 | 7 | JN5-NK-A07 |
| 4 | 8 | JN5-NK-A08 |
Manual — 11.9 PROFIBUS high-speed expansion card hardware — page 579
Manual reference: physical PDF page 579. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Covered board references and tiny vertical board code.
11.9 PROFIBUS high speed communication expansion card
11.9.1 Communication hardware and data structure
This product is the PROFIBUS high-speed communication expansion module; it can perform
remote setting and communication functions through the PROFIBUS bus. It is used on the TECO
A510s/F510 AC motor driver (hereinafter referred to as the “driver”), and allows the driver to
operate on the PROFIBUS network.
PROFIBUS expansion board figureJN5-CMHI-PDP. Callouts:IDaddressswitch,Expansioncardscrewhole,CN5(ConnecttoControlBoard),COMM.indicatorlight,RUNindicatorlight,ERRindicatorlight,D-SUBport,Terminalresistanceswitch,Expansioncardscrewhole. Readable silkscreen:SW1,ON,OFF,RA1,RA2,C12,C11,C20,CN1,12,2,1,CN5,C9,R19,R20,R18,R17,C24,C2,C6,C8,C1,R1,R2,C13,C7,C3,X2,LED1,COMM,RUN,ERR,LED2,R7,R9,R10,U3,C26,C23,C22,CN3,C14,C15,U2,TVS1,C17,C16,R28,C19,SW2,ON,OFF,R29,R30,C21,FAB11-202-029C,41S1497. Tiny verticalboardcode and partially covered reference text remain unresolved after4x crop;do notinfer code characters or terminal wiring.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Covered reference text and tiny vertical board code unresolved after4x crop;callouts and readable silkscreen retained.
Manual — PROFIBUS and AC motor driver ports specifications — page 580
Manual reference: physical PDF page 580. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.9.2 Product specifications
PROFIBUS ports
AC motor driver port
PROFIBUS and AC motor driver ports specifications
Item / Specifications — PDF page 580
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | DB-9 |
| 3 | Transmission rate | 9.6Kbit/s to 12Mbit/s (automatic detection of transmission rate) |
| 4 | Network protocols | PROFIBUS communication protocol |
Item / Specifications — PDF page 580
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | Communication card CN5 connector |
| 3 | Transmission method | SPI high speed communication |
| 4 | Terminal functions | 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface. |
| 5 | Communication protocols | TECO communication protocol |
Manual — PROFIBUS DB9 pin definitions and DIP address settings — page 581
Manual reference: physical PDF page 581. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.9.3 Installation instructions
PROFIBUS network connection
Definitions of PROFIBUS DP communication port pins are as shown in the figure below.
As shown in the figure below, ID addresses (1~125) correspond to SW1 b1~b7.
Network address switch setting range: 1~125 (0, 128~255 cannot be used).
DB9sourcepin diagram:frontview leftcolumn9,8,7,6;rightcolumn5,4,3,2,1. Separatecablelabels3 B-Line,8 A-Line,5 2M and shieldoutline. Pinfunctiontable separatelyretained;no unprintedconnections inferred.
DIPphotograph labelsON,DIP,1,2,3,4,5,6,7,8. Firstlever shown towardON andremainingleverslower;tabledefines addresspositionsb1–b7 separately,not inferred fromphoto. Nooperationaldeviceconfigurationperformed.
PROFIBUS DB9 pin definitions and DIP address settings
/ Pin / Definition / Description — PDF page 581
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | Pin | Definition | Description |
| 2 | ⟦blank source cell⟧ | 1~2 | Not assigned | - |
| 3 | ⟦blank source cell⟧ | 3 | RXD/TXD-P (B- Line) | Receive/Send data -P |
| 4 | ⟦blank source cell⟧ | 4 | Not assigned | - |
| 5 | ⟦blank source cell⟧ | 5 | DGND (2M) | Data reference potential |
| 6 | ⟦blank source cell⟧ | 6~7 | Not assigned | - |
| 7 | ⟦blank source cell⟧ | 8 | RXD/TXD-N (A-Line) | Receive/Send data -N |
| 8 | ⟦blank source cell⟧ | 9 | Not assigned | - |
Function / DIP switch position / DIP switch status / Description — PDF page 581
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Function | DIP switch position | DIP switch status | Description |
| 2 | Network address setting | b1~b7 | 1000000 | Network address is 1 |
| 3 | Network address setting | b1~b7 | 0100000 | Network address is 2 |
| 4 | Network address setting | b1~b7 | 1100000 | Network address is 3 |
| 5 | Network address setting | b1~b7 | ............ | ……. |
| 6 | Network address setting | b1~b7 | 1011111 | Network address is 125 |
| 7 | No function | b8 | - | - |
Manual — PROFIBUS bus termination and transmission rate/distance — page 582
Manual reference: physical PDF page 582. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny photographic resistor body codes.
PROFIBUS bus terminal resistor
The first and last station of the PROFIBUS bus must be connected to the bus, and
the bus terminal resistor must be turned on.
PROFIBUS bus termination source graphic. Schematic labels:5V;390Ω,220Ω,390Ω;V−;ON upward arrow;SW DIP-2;upper switch pins4/3,lower1/2;B+,A−;Bus Terminating Resistors. Photograph labels:ON,2,1,R29,R28,R30. Tiny resistor body codes remain ambiguous after4x crop;no codes or resistance equivalence inferred from photo. Schematic and photograph preserved separately,not a reconstructed circuit.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny photographed resistor body codes unresolved after4x;schematic labels preserved.
PROFIBUS bus termination and transmission rate/distance
Serial transmission rate(kbps) / Maximum bus length (m) — PDF page 582
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Serial transmission rate(kbps) | Maximum bus length (m) |
| 2 | 9.6 | 1200 |
| 3 | 19.2 | 1200 |
| 4 | 45.45 | 1200 |
| 5 | 93.75 | 1200 |
| 6 | 187.5 | 1000 |
| 7 | 500 | 400 |
| 8 | 1500 | 200 |
| 9 | 3000 | 100 |
| 10 | 6000 | 100 |
| 11 | 12000 | 100 |
Manual — PROFIBUS RUN/ERR and COMM indicators — page 583
Manual reference: physical PDF page 583. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.9.4 LED indicator descriptions The module has two dual-color LED indicators built-in used to quickly diagnose and monitor the communication statuses between the module itself and the bus.
Module status LED (RUN LED & ERR LED)
Used to monitor whether the equipment is operating normally.
Network status LED (COMM LED)
Used to monitor the operability of the communication module PROFIBUS network.
PROFIBUS RUN/ERR and COMM indicators
Indicator statuses / Description — PDF page 583
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Indicator statuses | Description |
| 2 | Does not light up | Power not supplied |
| 3 | Orange light lights up | Communication with the frequency converter not established |
| 4 | Red light flashes (1 Hz) | Communication error with the frequency converter |
| 5 | Red light flashes (4 Hz) | Flip-switch ID address error |
| 6 | Green light flashes (4 Hz) | Power supply normal but DP communication not established |
| 7 | Green light lights up | DP communication normal |
Indicator statuses / Description — PDF page 583
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Indicator statuses | Description |
| 2 | Does not light up | DP communication not established |
| 3 | Green light lights up | DP communication established and normal |
Manual — PROFIBUS driver parameters and PPO/PZD structure — page 584
Manual reference: physical PDF page 584. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.9.5 Driver parameter setting descriptions Used to monitor the operability of the communication module PROFIBUS network. Users must first confirm related parameter settings on the driver in order to ensure that the communication module can connect normally.
11.9.6 Connection instructions
PPO communication
PZD Structure default
User parameters of the communication module configured through the GSD file. Default values of the PZD structure are as follows: STW1 Control character; mapped to the MODBUS address 0x2501 of the driver. HSW Main setting value; mapped to the MODBUS address 0x2502 of the driver. ZSW1 Status character; mapped to the MODBUS address 0x2520 of the driver. HIW Main actual value; mapped to the MODBUS address 0x2524 of the driver. PLC Master station→ driver slave station
PPO layout:PKW spans PKE firstword,IND secondword,PWE third/fourthwords. PZD spans PZD1 STW/ZSW firstword,PZD2 HSW/HIW secondword,PZD3 third,PZD4 fourth,PZD5 fifth,PZD6 sixth,PZD7 seventh,PZD8 eighth,PZD9 ninth,PZD10 tenth. Green source spans:PPO1 PKW plusPZD1–2;PPO2 PKW plusPZD1–6;PPO3 PZD1–2;PPO4 PZD1–6;PPO5 PKW plusPZD1–10. These are literal diagram spans,not validated implementation instructions.
PROFIBUS driver parameters and PPO/PZD structure
Parameters / Parameter name / Settings / Settings descriptions — PDF page 584
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Parameters | Parameter name | Settings | Settings descriptions |
| 2 | 00-02 | Operation command source | 2 | Communication control |
| 3 | 00-05 | Frequency command source | 3 | Communication control |
PKW: Parameter address/value / STW: Control character — PDF page 584
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | PKW: Parameter address/value | STW: Control character |
| 2 | PZD: Process data | ZSW: Status character |
| 3 | PKE: Parameter address | HSW: Main settings |
| 4 | IND: Subindex | HIW: Main actual value |
| 5 | PWE: Parameter value | ⟦blank source cell⟧ |
Manual — PROFIBUS PZD mapping and STW/ZSW bits — page 585
Manual reference: physical PDF page 585. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PZD3/ PZD4: Not used. Driver slave station→ PLC master station Driver output status; mapped to the MODBUS addresses 0x2520~0x252F of the driver. The default values of PZD3/PZD4/PZD5/PZD6 are set as follows: PZD3: Default multi-function terminal block on/off status; mapped to the MODBUS address 0x2522 of the driver. PZD4: Default output current; mapped to the MODBUS address 0x2527 of the driver. PZD5: Default output current; mapped to the MODBUS address 0x2521 of the driver. PZD6: Default output current; mapped to the MODBUS address 0x2528 of the driver. 11.9.7 Meanings of each character
Control character STW
Status character ZSW
PROFIBUS PZD mapping and STW/ZSW bits
Bit / Description / 1 / 0 — PDF page 585
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Bit | Description | 1 | 0 |
| 2 | 0 | Operation command | Operate | Stop |
| 3 | 1 | Reverse command | Reverse | Forward |
| 4 | 2 | External error | Error | - |
| 5 | 3 | Error reset | Reset | - |
| 6 | 4~5 | Reserved | - | - |
| 7 | 6 | Multi-function terminal S1 | ON | OFF |
| 8 | 7 | Multi-function terminal S2 | ON | OFF |
| 9 | 8 | Multi-function terminal S3 | ON | OFF |
| 10 | 9 | Multi-function terminal S4 | ON | OFF |
| 11 | A | Multi-function terminal S5 | ON | OFF |
| 12 | B | Multi-function terminal S6 | ON | OFF |
| 13 | C | Multi-function terminal S7 | ON | OFF |
| 14 | D | Multi-function terminal S8 | ON | OFF |
| 15 | E | Controller mode | ON | OFF |
| 16 | F | Communication setting torque command | ON | ⟦blank source cell⟧ |
Bit / Meaning / 1 / 0 — PDF page 585
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Bit | Meaning | 1 | 0 |
| 2 | 0 | Operation status | Operate | Stop |
| 3 | 1 | Direction status | Reverse | Forward |
| 4 | 2 | Frequency converter operation preparation status | Preparation complete | Not yet prepared |
| 5 | 3 | Error | Abnormal | Normal |
| 6 | 4 | Warning | ON | OFF |
| 7 | 5 | Zero speed | ON | OFF |
Manual — PROFIBUS ZSW continuation and PKW layout — page 586
Manual reference: physical PDF page 586. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.9.8 PKW regional access parameters The driver can provide request and response information. Due to the request and response mechanism, the master station must send requests until a communication response is received. The 4 characters of the PKW region are as follows:
Parameters address PKE
Bit 0~11 (PNU): Parameter address/MODBUS address that includes related parameters. Parameter address/MODBUS address: Please refer to the MODBUS communication protocol description chapter in the driver manual for the register numbers, registers and data format that corresponds to the operation parameters. Bit 12~15 (AK): Includes the identification characters of requests or responses.
PKW word/bit layout:Word1 Parameter ID(PKE);bits15–12 AK,bits11–0 Parameter number(PNU). Word2 IND Reserved. Word3 PWE1:bits15–8 Reserved,bits7–0 Fault number. Word4 PWE2 Read/Write parameters. Source grouping retained;later read example differs in address placement and is separately flagged.
PROFIBUS ZSW continuation and PKW layout
6 / Model 440 / ON / OFF — PDF page 586
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | 6 | Model 440 | ON | OFF |
| 2 | 7 | Frequency reached | ON | OFF |
| 3 | 8 | Any frequency reached | ON | OFF |
| 4 | 9 | Frequency detection one | ON | OFF |
| 5 | A | Frequency detection two | ON | OFF |
| 6 | B | Low voltage | ON | OFF |
| 7 | C | Frequency converter no output | ON | OFF |
| 8 | D | Frequency not according to communication | ON | OFF |
| 9 | E | SeqNotFromComm | ON | OFF |
| 10 | F | Over-torque | ON | OFF |
Manual — PROFIBUS AK request/response/error codes and PWE — page 587
Manual reference: physical PDF page 587. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Request character AK
PLC master station→ driver slave station
Response character AK
Driver slave station→ PLC master station
Error character
If the request parameter value was not processed, then the error codes that will be kept in the low-bit PWE1 set are as follows:
Parameter Value PWE
Driver parameters are sent through PWE2 (4th word). In the following example, PWEI (3rd word) must be set as 0 in the PROFIBUS master station.
Example of the PKW mechanism: For example: Read parameters 00-05 (frequency command source). Read the values of 00-05; first set the request identification character as 1, and then refer to the MODBUS communication protocol description chapter in the driver manual to find out that the address of 00-05 is 0x0005, then the data sequences are as follows:
PROFIBUS AK request/response/error codes and PWE
Request Identifier / Description — PDF page 587
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Request Identifier | Description |
| 2 | 0 | No request |
| 3 | 1 | Read parameter value |
| 4 | 2 | Modify parameter value |
Request Identifier / Description — PDF page 587
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Request Identifier | Description |
| 2 | 0 | No response |
| 3 | 1 | Request parameter value processed |
| 4 | 7 | Request parameter value cannot process |
Error code / Description — PDF page 587
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Error code | Description |
| 2 | 0 | Parameter does not exist |
| 3 | 1 | The current status parameter cannot be read/written |
| 4 | 2 | Parameter value not within range |
| 5 | 101 | Other SP communication error occurred, such as: response timeout |
Manual — PROFIBUS parameter read example and troubleshooting — page 588
Manual reference: physical PDF page 588. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PLC master station→ driver slave station: 1000 0005 0000 0000 Driver slave station→ PLC master station: 1000 0005 0000 0004
11.9.9 Troubleshooting
There are two indicators on top of the PROFIBUS communication module; when malfunction occurs,
the cause of the malfunction can be confirmed based on the indicator statuses, and troubleshoot
the error by following the descriptions below.
Indicator troubleshooting
Module status LED
Network status LED
PROFIBUS parameter read example and troubleshooting
Request — PDF page 588
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Request | Request |
| 2 | 1st word (PKE) | 1000 |
| 3 | 2nd word (IND) | 0005 |
| 4 | 3rd word (PWE1) | 0000 |
| 5 | 4th word (PWE2) | 0000 |
Response — PDF page 588
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Response | Response |
| 2 | 1st word (PKE) | 1000 |
| 3 | 2nd word (IND) | 0005 |
| 4 | 3rd word (PWE1) | 0000 |
| 5 | 4th word (PWE2) | 0004 |
Indicator statuses / Status name / Troubleshooting method — PDF page 588
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Troubleshooting method |
| 2 | Does not light up | Power not supplied to the communicat ion module | 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver. |
| 3 | Red and green light flashes alternately | Self-check | 1. The host is under self-check; if it flashes continuously, disconnect the power and then reconnect it. 2. Confirm whether the driver communication connection parameters are properly set (19200, 8, N, 1) |
| 4 | Green light flashes | the communicat ion module standby | 1. Not yet connected with the driver. |
Indicator statuses / Status name / Description — PDF page 588
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Description |
Manual — PROFIBUS network troubleshooting and historical GSD reference — page 589
Manual reference: physical PDF page 589. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.9.10 GSD File When using the Profibus communication module, if the GSD description file (JN5-CMHI-PDP_V (latest version).GSD) is needed, please download it from the TECO official website or request for it from your purchasing sales channel.
PROFIBUS network troubleshooting and historical GSD reference
Does not light up / Power not supplied / 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver. — PDF page 589
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Does not light up | Power not supplied | 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver. |
| 2 | Does not light up | Standby | 1. Not yet connected with the PROFIBUS host terminal. |
Manual — CANopen module introduction and board label drawing — page 590
Manual reference: physical PDF page 590. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.10 CANopen high speed communication expansion card
11.10.1 Communication hardware and data structure
This product is the CANopen high-speed communication expansion module; it can perform remote
setting and communication functions through the CANopen bus. It can only be used with the TECO
A510s/F510 AC motor driver (hereinafter referred to as the “driver”), and allow the driver to operate
on the CANopen network.
CANopen board drawing labels:JN5-CMHI-CAN;41S1498;4KA69X1022W13;FAB11-202-030C;SW2,SW1,ON,OFF,RA3,C12,CN5,2,RA1,RA2,C20,C11,CN1,12,2,1,R1,R2,12,11,R20,R19,C9,C24,R17,R18,C6,C2,C4,C7,X1,C10,C13,C1,C8,R16,R15,R14,R7,R8,R9,R10,LED1,LED2,RUN,ERR,C22,C23,C14,C15,U2,U3,C21,C17,C18,C19,L1,C16,TVS1,SW3,ON,OFF,R6,C5,TB1,0V,CANL,CANH,R30,R29. Board outlines/component symbols retained inimage;no circuit topology or installed component ratings inferred.
Manual — CANopen/driver port specifications — page 591
Manual reference: physical PDF page 591. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.10.2 Product specifications
CANopen ports
AC motor driver port
CANopen/driver port specifications
Item / Specifications — PDF page 591
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | 5-pin open pluggable connector; pin spacing 5.08mm |
| 3 | Transmission rate | 10kbps, 20kbps, 50kbps, 125kbps, 250kbps, 500kbps, 800kbps, 1Mbps |
| 4 | Network protocols | CANopen communication protocol |
Item / Specifications — PDF page 591
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | Communication card CN5 connector |
| 3 | Transmission method | SPI high speed communication |
| 4 | Terminal functions | 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface. |
| 5 | Communication protocols | TECO communication protocol |
Manual — CANopen installation callouts and terminal block — page 592
Manual reference: physical PDF page 592. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny photographed component markings and partly covered references.
11.10.3 Installation instructions
Communication module contact description
As shown in the figure below, A – Terminal block (TB1)
B, C – Mounting holes
D - RUN LED
E - ERR LED
F – Control board connector (CN5)
G - Rate setting switch
H – ID address setting switch
Terminal block definition
As shown in the figure below, the contact definitions in the order from left to right are
GND, CAN_L, NC, CAN_H and NC.
CANopen board photograph callouts A,B,C,D,E,F,G,H correspond to source prose:terminal blockTB1,mounting holes,RUN LED,ERR LED,control board connectorCN5,rate switch,ID address switch. Readable board identity JN5-CMHI-CAN,41S1498,4KA69X1022T01,FAB11-202-030C. Visible switchlabels ON,DIP,1–8 and1–4;RUN,ERR,LED1,LED2. Tiny component markings and partially covered board references not fully resolved at4x;pagepartial for that residual only. Drawing590 uses W13 code;photoT01 retained as distinct source illustration,not equivalent edition inference.
CANopen terminal photograph labels GND,CAN L,CAN H;two physical terminal positions unlabelled. Native prose explicitly lists left-to-right GND,CAN_L,NC,CAN_H,NC;blank photographed positions not filled by inference. Original screws/connector image retained.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny photographed component body inscriptions and partially covered board references.
C19
C18
TVS1
L1
C16
C17
C23
C22
C14
C15
U2
C13
C10
X1
C7
C1
C8
U3
C4
R30
R29
C21
C5
R6
R7
R8
R9
R10
R16
R15
R14
C6
C2
C24
C9
R20
R19
R17
R18
C20
C11
R2
R1
RA1
RA2
RA3
CN1
SW1
SW2
Manual — CANopen SW1 address and SW2 transmission rate — page 593
Manual reference: physical PDF page 593. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
ID address setting description
As shown in the figure below, ID addresses (1~127) correspond to SW1 b1~b7.
Transmission rate corresponds to SW2 b1~b3.
Network address switch setting range: 1~127 (0, 128~255 cannot be used).
Transmission rate switch setting range: 0~7 (8~15 cannot be used).
Address DIP photograph labels ON,DIP,1,2,3,4,5,6,7,8;first lever at ON side,others opposite. Background board fragment CMHI-CAN andON/OFF partially visible. Source table independently defines b7–b1;no device setting applied.
Rate DIP photograph labels ON,DIP,1,2,3,4;first three levers at ON side,fourth opposite. Native source states SW2 b1–b3;configuration not inferred beyond source table.
CANopen SW1 address and SW2 transmission rate
Function / DIP switch position / DIP switch status 7654321 / Description — PDF page 593
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Function | DIP switch position | DIP switch status 7654321 | Description |
| 2 | Network address Setting | SW1 b7—b1 | 0000000 | Cannot be used |
| 3 | Network address Setting | SW1 b7—b1 | 0000001 | Network address is 1 |
| 4 | Network address Setting | SW1 b7—b1 | 0000010 | Network address is 2 |
| 5 | Network address Setting | SW1 b7—b1 | 0000011 | Network address is 3 |
| 6 | Network address Setting | SW1 b7—b1 | ............ | ............ |
| 7 | Network address Setting | SW1 b7—b1 | 1111110 | Network address is 126 |
| 8 | Network address Setting | SW1 b7—b1 | 1111111 | Network address is 127 |
| 9 | CANopen Transmission rate setting | SW2 b3—b1 | 000 | 10K |
| 10 | CANopen Transmission rate setting | SW2 b3—b1 | 001 | 20K |
| 11 | CANopen Transmission rate setting | SW2 b3—b1 | 010 | 50K |
| 12 | CANopen Transmission rate setting | SW2 b3—b1 | 011 | 125K |
| 13 | CANopen Transmission rate setting | SW2 b3—b1 | 100 | 250K |
| 14 | CANopen Transmission rate setting | SW2 b3—b1 | 101 | 500K |
| 15 | CANopen Transmission rate setting | SW2 b3—b1 | 110 | 800K |
| 16 | CANopen Transmission rate setting | SW2 b3—b1 | 111 | 1M |
Manual — CANopen cable types/distance and RUN indicator — page 594
Manual reference: physical PDF page 594. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.10.4 Transmission rate, maximum transmission distance and cable
length
The maximum allowable length of the bus bar mainly depends on the type of cable used. The
allowed cable types are:
•Thin cable
•Thick cable
•Flat cable
ODVA requirements for data transmission cable (Thick cable):
11.10.5 LED indicator descriptions The module has RUN (green) and ERR (red) indicators built-in used to quickly diagnose and monitor the communication statuses between the module itself and the bus.
Module status LED (RUN LED)
Used to monitor whether the equipment is operating normally.
Error status LED (ERR LED)
Used to monitor the operability of the communication module CANopen network.
CANopen cable types/distance and RUN indicator
Serial transmission rate (kbps) / Maximum bus length(m) — PDF page 594
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Serial transmission rate (kbps) | Maximum bus length(m) | Serial transmission rate (kbps) | Maximum bus length(m) |
| 2 | 1000 | 25 | 125 | 500 |
| 3 | 800 | 50 | 50 | 1000 |
| 4 | 500 | 100 | 20 | 2500 |
| 5 | 250 | 250 | 10 | 5000 |
Indicator statuses / Status name / Description — PDF page 594
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Description |
| 2 | Does not light up | Initial status | Power not supplied |
| 3 | Continuous flashing | Pre-operation | Preparation status |
| 4 | Single flash | Stop | Stopping |
| 5 | Green light lights up | Operation | Operating |
Indicator statuses / Status name / Description — PDF page 594
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Description |
| 2 | Does not light up | No error | Operating |
Manual — CANopen ERR indicator, driver parameters and SDO read request — page 595
Manual reference: physical PDF page 595. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.10.6 Driver parameter setting descriptions Used to monitor the operability of the communication module CANopen network. Users must first confirm related parameter settings on the driver in order to ensure that the communication module can connect normally.
11.10.7 Connection instructions
Service data object (SDO)
This module supports 1 SDO server, which means it can provide SDO service, and the SDO uses the sending and receiving COB-ID of the predefined connection, 0x580 + NodeID (sending) and 0x600 + NodeID (receiving). Each SDO message includes a set of COB-ID (request SDO and response SDO); it allows performing of access actions within two nodes. SDO can transmit any size of data, but segment transmission must be used once it exceeds 4 bytes. The COB IDs of SDO communication are as follows: Read: Master to slave (request code 0x40) / Master to slave: 600H + Node ID
Read: Slave response / slave to master: 580H + Node ID
CANopen ERR indicator, driver parameters and SDO read request
Single flash / Warning / Packet error — PDF page 595
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Single flash | Warning | Packet error |
| 2 | Double flash | Error | Guard/Heartbeat error |
| 3 | Red light lights up | Disconnected | Bus closed |
Parameters / Parameter name / Settings / Settings descriptions — PDF page 595
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Parameters | Parameter name | Settings | Settings descriptions |
| 2 | 00-02 | Operation command source | 2 | Communication control |
| 3 | 00-05 | Frequency command source | 3 | Communication control |
COB-ID / Byte0 / Byte1 / Byte2 / Byte3 / Byte4 / Byte5 / Byte6 / Byte7 — PDF page 595
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | COB-ID | Byte0 | Byte1 | Byte2 | Byte3 | Byte4 | Byte5 | Byte6 | Byte7 |
| 2 | (600H) + Node ID | Reque st code | Object index | Object index | Object subind ex | Request data | Request data | Request data | Request data |
| 3 | (600H) + Node ID | Reque st code | LSB | MSB | Object subind ex | Reserved | Reserved | Reserved | Reserved |
COB-ID / Byte0 / Byte1 / Byte2 / Byte3 / Byte4 / Byte5 / Byte6 / Byte7 — PDF page 595
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | COB-ID | Byte0 | Byte1 | Byte2 | Byte3 | Byte4 | Byte5 | Byte6 | Byte7 |
| 2 | (580H) + Node ID | Reque st code | Object index | Object index | Object subind ex | Request data | Request data | Request data | Request data |
| 3 | (580H) + Node ID | Reque st code | LSB | MSB | Object subind ex | bit0~ bit7 | Bit8~ bit15 | Bit16~ bit23 | Bit24~ bit31 |
Manual — CANopen SDO read response and write request/response — page 596
Manual reference: physical PDF page 596. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Response code: 43H: Read 4-byte data / 4BH: read 2-byte data / 4FH: read 1-byte data
Write: Master to slave (4-byte data maximum)
Request code: 23H: Write a 4-byte data entry 2BH: Write a 2-byte data entry 2FH: Write a 1-byte data entry Write: Slave to master (response code 0x60H)
When we use SDO to perform control to the group 25H of the driver control group, corresponding rules are as follows:
Index
25xxH (register address)
For example, when we want to perform write/read to 2501H of the control group, the corresponding SDO object index is the control group register address 2501H. Perform operation with index 2501H directly and the module will automatically convert to the A510s 2501H control group register address to perform operation.
CANopen SDO read response and write request/response
COB-ID / Byte0 / Byte1 / Byte2 / Byte3 / Byte4 / Byte5 / Byte6 / Byte7 — PDF page 596
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | COB-ID | Byte0 | Byte1 | Byte2 | Byte3 | Byte4 | Byte5 | Byte6 | Byte7 |
| 2 | (600H) + Node ID | Reque st code | Object index | Object index | Object subind ex | Request data | Request data | Request data | Request data |
| 3 | (600H) + Node ID | Reque st code | LSB | MSB | Object subind ex | bit0~ bit7 | Bit8~ bit15 | Bit16~ bit23 | Bit24~ bit31 |
COB-ID / Byte0 / Byte1 / Byte2 / Byte3 / Byte4 / Byte5 / Byte6 / Byte7 — PDF page 596
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | COB-ID | Byte0 | Byte1 | Byte2 | Byte3 | Byte4 | Byte5 | Byte6 | Byte7 |
| 2 | (580H) + Node ID | Reque st code | Object index | Object index | Object subind ex | Request data | Request data | Request data | Request data |
| 3 | (580H) + Node ID | Reque st code | LSB | MSB | Object subind ex | Reserved | Reserved | Reserved | Reserved |
Manual — CANopen basic objects and PDO mappings — page 597
Manual reference: physical PDF page 597. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.10.8 Object index list
Basic index
CANopen basic objects and PDO mappings
Index / Sub / Name / Default value / R/W / Size / Remarks — PDF page 597
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Index | Sub | Name | Default value | R/W | Size | Remarks |
| 2 | 1000H | 0 | Device type | 00010192H | R | U32 | ⟦blank source cell⟧ |
| 3 | 1001H | 0 | Error register | 0 | R | U8 | ⟦blank source cell⟧ |
| 4 | 1005H | 0 | COB-ID SYNC message | 80H | R | U32 | ⟦blank source cell⟧ |
| 5 | 1006H | 0 | Communication cycle period | 0 | RW | U32 | ⟦blank source cell⟧ |
| 6 | 1008H | 0 | Manufacturer device name | A510 | R | U32 | ⟦blank source cell⟧ |
| 7 | 1009H | 0 | Manufacturer hardware version | 1.0 | R | U32 | ⟦blank source cell⟧ |
| 8 | 100AH | 0 | Manufacturer software version | 1.00 | R | U32 | ⟦blank source cell⟧ |
| 9 | 1014H | 0 | COB-ID emergency | 00000080H+Node-I D | R | U32 | ⟦blank source cell⟧ |
| 10 | 1015H | 0 | Inhibit time EMCY | 0 | RW | U16 | ⟦blank source cell⟧ |
| 11 | 1016H | 0 | number of entries | 1 | R | U8 | ⟦blank source cell⟧ |
| 12 | 1016H | 1 | Consumer heartbeat time | 0 | RW | U32 | Not supported |
| 13 | 1017H | 0 | Producer heartbeat time | 0 | RW | U16 | ⟦blank source cell⟧ |
| 14 | 1018H | 0 | number of entries | 3 | R | U8 | ⟦blank source cell⟧ |
| 15 | 1018H | 1 | Vender ID | 00000373H | R | U32 | ⟦blank source cell⟧ |
| 16 | 1018H | 2 | Product code | 00000100H | R | U32 | ⟦blank source cell⟧ |
| 17 | 1018H | 3 | Revision | 00010000H | R | U32 | ⟦blank source cell⟧ |
| 18 | 1200H | 0 | Server SDO Parameter | 2 | R | U8 | ⟦blank source cell⟧ |
| 19 | 1200H | 1 | COB-ID Client Server | 0000600H+Node-ID | R | U32 | ⟦blank source cell⟧ |
| 20 | 1200H | 2 | COB-ID Client Server | 0000580H+Node-ID | R | U32 | ⟦blank source cell⟧ |
| 21 | 1400H | 0 | Number of entries | 2 | R | U8 | ⟦blank source cell⟧ |
| 22 | 1400H | 1 | COB-ID used by PDO | 00000200H+Node-I D | RW | U32 | ⟦blank source cell⟧ |
| 23 | 1400H | 2 | Transmission Type | 0xFF | RW | U8 | ⟦blank source cell⟧ |
| 24 | 1401H | 0 | Number of entries | 2 | R | U8 | ⟦blank source cell⟧ |
| 25 | 1401H | 1 | COB-ID used by PDO | 00000300H+Node-I D | RW | U32 | ⟦blank source cell⟧ |
| 26 | 1401H | 2 | Transmission Type | 0xFF | RW | U8 | ⟦blank source cell⟧ |
| 27 | 1600H | 0 | Number of entries | 2 | RW | U8 | ⟦blank source cell⟧ |
| 28 | 1600H | 1 | 1.Mapped Object | 60400010H | RW | U32 | ⟦blank source cell⟧ |
| 29 | 1600H | 2 | 2.Mapped Object | 60420010H | RW | U32 | ⟦blank source cell⟧ |
| 30 | 1600H | 3 | 3.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 31 | 1600H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
Manual — CANopen PDO mappings continued, duplicate subindices retained — page 598
Manual reference: physical PDF page 598. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
CANopen PDO mappings continued, duplicate subindices retained
Index / Sub / Name / Default value / R/W / Size / Remarks — PDF page 598
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Index | Sub | Name | Default value | R/W | Size | Remarks |
| 2 | 1601H | 0 | Number of entries | 2 | RW | U8 | ⟦blank source cell⟧ |
| 3 | 1601H | 1 | 1.Mapped Object | 604F0010H | RW | U32 | ⟦blank source cell⟧ |
| 4 | 1601H | 2 | 2.Mapped Object | 60500010H | RW | U32 | ⟦blank source cell⟧ |
| 5 | 1601H | 3 | 3.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 6 | 1601H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 7 | 1800H | 0 | Number of entries | 5 | R | U8 | Number of entries |
| 8 | 1800H | 1 | COB-ID used by PDO | 180H+Node-ID | RW | U32 | ⟦blank source cell⟧ |
| 9 | 1800H | 2 | Transmission Type | 0xFF | RW | U8 | Transmission type |
| 10 | 1800H | 3 | Inhibit time | 0x64 | RW | U16 | Inhibit time |
| 11 | 1800H | 4 | CMS-Priority Group | 0 | RW | U8 | ⟦blank source cell⟧ |
| 12 | 1800H | 5 | Event timer | 0x64 | RW | U16 | Event timer |
| 13 | 1801H | 0 | Number of entries | 5 | R | U8 | Number of entries |
| 14 | 1801H | 1 | COB-ID used by PDO | 00000280H+Node-I D | RW | U32 | ⟦blank source cell⟧ |
| 15 | 1801H | 2 | Transmission Type | 0xFF | RW | U8 | ⟦blank source cell⟧ |
| 16 | 1801H | 3 | Inhibit time | 0x64 | RW | U16 | Inhibit time |
| 17 | 1801H | 4 | CMS-Priority Group | 0 | RW | U8 | ⟦blank source cell⟧ |
| 18 | 1801H | 5 | Event timer | 0x64 | RW | U16 | Event time |
| 19 | 1801H | 4 | CMS-Priority Group | 0 | RW | U8 | ⟦blank source cell⟧ |
| 20 | 1801H | 5 | Event timer | 0x64 | RW | U16 | Event time |
| 21 | 1801H | 2 | Transmission Type | 0xFF | RW | U8 | ⟦blank source cell⟧ |
| 22 | 1801H | 3 | Inhibit time | 0x64 | RW | U16 | Inhibit time |
| 23 | 1801H | 4 | CMS-Priority Group | 0 | RW | U8 | ⟦blank source cell⟧ |
| 24 | 1801H | 5 | Event timer | 0x64 | RW | U16 | Event time |
| 25 | 1A00H | 0 | Number of entries | 2 | RW | U8 | ⟦blank source cell⟧ |
| 26 | 1A00H | 1 | 1.Mapped Object | 60400010 | RW | U32 | ⟦blank source cell⟧ |
| 27 | 1A00H | 2 | 2.Mapped Object | 60420010 | RW | U32 | ⟦blank source cell⟧ |
| 28 | 1A00H | 3 | 3.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 29 | 1A00H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 30 | 1A01H | 0 | Number of entries | 2 | RW | U8 | ⟦blank source cell⟧ |
| 31 | 1A01H | 1 | 1.Mapped Object | 604F0010 | RW | U32 | ⟦blank source cell⟧ |
| 32 | 1A01H | 2 | 2.Mapped Object | 60500010 | RW | U32 | ⟦blank source cell⟧ |
| 33 | 1A01H | 3 | 3.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 34 | 1A01H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
Manual — CANopen DS402 objects and driver command registers — page 599
Manual reference: physical PDF page 599. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
DS402 part
Driver control group command index
Command DATA (allows reading and writing)
CANopen DS402 objects and driver command registers
Index / Sub- Index / Name / Default value / R/W / Size / Unit / PDO MAP — PDF page 599
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Index | Sub- Index | Name | Default value | R/W | Size | Unit | PDO MAP |
| 2 | 603F | 0 | Error code | 0 | RO | U16 | ⟦blank source cell⟧ | Yes |
| 3 | 6040 | 0 | Control word | 0 | RW | U16 | ⟦blank source cell⟧ | Yes |
| 4 | 6041 | 0 | Status word | 0 | RO | U16 | ⟦blank source cell⟧ | Yes |
| 5 | 6042 | 0 | vl target velocity | 0 | RW | S16 | Hz | Yes |
| 6 | 6043 | 0 | vl velocity demand | 0 | RO | S16 | Hz | Yes |
| 7 | 604F | 0 | vl ramp function time Acceleration time | 100 | RW | U16 | 0.1S | Yes |
| 8 | 6050 | 0 | vl slow down time Deceleration time | 100 | RW | U16 | 0.1S | Yes |
Register address / / Bit / Content — PDF page 599
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Register address | ⟦blank source cell⟧ | Bit | Content |
| 2 | 2500H | Reserved | Reserved | Reserved |
| 3 | 2501H | Operation signal | 0 | Operation command 1: Operate 0: Stop |
| 4 | 2501H | Operation signal | 1 | Reverse command 1: Reverse 0: Forward |
| 5 | 2501H | Operation signal | 2 | External error 1: Error |
| 6 | 2501H | Operation signal | 3 | Error reset 1: Reset |
| 7 | 2501H | Operation signal | 4 | Reserved |
| 8 | 2501H | Operation signal | 5 | Reserved |
| 9 | 2501H | Operation signal | 6 | Multi-function terminal S1 1: “ON” |
| 10 | 2501H | Operation signal | 7 | Multi-function terminal S2 1: “ON” |
| 11 | 2501H | Operation signal | 8 | Multi-function terminal S3 1: “ON” |
| 12 | 2501H | Operation signal | 9 | Multi-function terminal S4 1: “ON” |
| 13 | 2501H | Operation signal | A | Multi-function terminal S5 1: “ON” |
| 14 | 2501H | Operation signal | B | Multi-function terminal S6 1: “ON” |
| 15 | 2501H | Operation signal | C | Multi-function terminal S7 1: “ON” |
| 16 | 2501H | Operation signal | D | Multi-function terminal S8 1: “ON” |
| 17 | 2501H | Operation signal | E | Controller mode 1: “ON” |
| 18 | 2501H | Operation signal | F | Communication setting torque command 1: “ON” |
| 19 | 2502H | ⟦blank source cell⟧ | *Frequency command (Unit: 0.01Hz) | *Frequency command (Unit: 0.01Hz) |
| 20 | 2505H | ⟦blank source cell⟧ | AO1 (0.00V ~ 10.00V) | AO1 (0.00V ~ 10.00V) |
| 21 | 2510H | ⟦blank source cell⟧ | G12-00 H-WORD | G12-00 H-WORD |
| 22 | 2511H | ⟦blank source cell⟧ | G12-00 L-WORD | G12-00 L-WORD |
Manual — CANopen status and fault registers — page 600
Manual reference: physical PDF page 600. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Monitor DATA (read only)
CANopen status and fault registers
Adjacent source context — repeated to preserve continuation:
Register address / / Bit / Content — PDF page 600
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) |
|---|---|---|---|---|---|---|
| 1 | Register address | ⟦blank source cell⟧ | Bit | Content | Content | Content |
| 2 | 2520H | Status signal | 0 | Operation status 1: Operate 0: Stop | Operation status 1: Operate 0: Stop | Operation status 1: Operate 0: Stop |
| 3 | 2520H | Status signal | 1 | Direction status 1: Reverse 0: Forward | Direction status 1: Reverse 0: Forward | Direction status 1: Reverse 0: Forward |
| 4 | 2520H | Status signal | 2 | Frequency converter operation preparation status 1: Preparation complete 0: Preparation not yet complete | Frequency converter operation preparation status 1: Preparation complete 0: Preparation not yet complete | Frequency converter operation preparation status 1: Preparation complete 0: Preparation not yet complete |
| 5 | 2520H | Status signal | 3 | Error 1: Abnormal | Error 1: Abnormal | Error 1: Abnormal |
| 6 | 2520H | Status signal | 4 | Warning 1: “ON” | Warning 1: “ON” | Warning 1: “ON” |
| 7 | 2520H | Status signal | 5 | Zero speed 1: “ON” | Zero speed 1: “ON” | Zero speed 1: “ON” |
| 8 | 2520H | Status signal | 6 | Model 440 1: “ON” | Model 440 1: “ON” | Model 440 1: “ON” |
| 9 | 2520H | Status signal | 7 | Frequency reached 1: “ON” | Frequency reached 1: “ON” | Frequency reached 1: “ON” |
| 10 | 2520H | Status signal | 8 | Any frequency reached 1: “ON” | Any frequency reached 1: “ON” | Any frequency reached 1: “ON” |
| 11 | 2520H | Status signal | 9 | Frequency detection one 1: “ON” | Frequency detection one 1: “ON” | Frequency detection one 1: “ON” |
| 12 | 2520H | Status signal | A | Frequency detection two 1: “ON” | Frequency detection two 1: “ON” | Frequency detection two 1: “ON” |
| 13 | 2520H | Status signal | B | Low voltage 1: “ON” | Low voltage 1: “ON” | Low voltage 1: “ON” |
| 14 | 2520H | Status signal | C | Frequency converter no output 1: “ON” | Frequency converter no output 1: “ON” | Frequency converter no output 1: “ON” |
| 15 | 2520H | Status signal | D | Frequency not according to communication 1: “ON” | Frequency not according to communication 1: “ON” | Frequency not according to communication 1: “ON” |
| 16 | 2520H | Status signal | E | Operation not according to communication 1: “ON” | Operation not according to communication 1: “ON” | Operation not according to communication 1: “ON” |
| 17 | 2520H | Status signal | F | Over-torque 1: “ON” | Over-torque 1: “ON” | Over-torque 1: “ON” |
| 18 | 2521H | Error description | 0 | Reserved | 31 | Reserved |
| 19 | 2521H | Error description | 1 | UV (Under-voltage) | 32 | Reserved |
| 20 | 2521H | Error description | 2 | OC (Over-current) | 33 | Reserved |
| 21 | 2521H | Error description | 3 | OV (Over-voltage) | 34 | Reserved |
| 22 | 2521H | Error description | 4 | OH1 (Heat sink overheat) | 35 | Reserved |
| 23 | 2521H | Error description | 5 | OL1 (Motor overload) | 36 | Reserved |
| 24 | 2521H | Error description | 6 | OL2 (Frequency converter overload) | 37 | Reserved |
| 25 | 2521H | Error description | 7 | OT (Over-torque) | 38 | CF07 (Motor control fault) |
| 26 | 2521H | Error description | 8 | UT (Under-torque) | 39 | Reserved |
| 27 | 2521H | Error description | 9 | SC (Short circuit) | 40 | Reserved |
| 28 | 2521H | Error description | 10 | GF (Ground fault) | 41 | Reserved |
| 29 | 2521H | Error description | 11 | FO | 42 | Reserved |
| 30 | 2521H | Error description | 12 | IPL (Input phase loss) | 43 | Reserved |
| 31 | 2521H | Error description | 13 | OPL (Output phase loss) | 44 | Reserved |
| 32 | 2521H | Error description | 14 | OS | 45 | Reserved |
| 33 | 2521H | Error description | 15 | PGO | 46 | OH4 (Motor overheat) |
Manual — CANopen fault register continuation, DI and analog registers, warning codes — page 601
Manual reference: physical PDF page 601. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
CANopen fault register continuation, DI and analog registers, warning codes
Adjacent source context — repeated to preserve continuation:
Register address / / Bit / Content — PDF page 601
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) | Physical column 11 (source headings retained in rows) | Physical column 12 (source headings retained in rows) | Physical column 13 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | Register address | ⟦blank source cell⟧ | Bit | Content | Content | Content | Content | Content | Content | Content | Content | Content | Content |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 16 | DEV | DEV | DEV | DEV | 47 | 47 | Reserved | Reserved | Reserved | Reserved |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 17 | EF1 | EF1 | EF1 | EF1 | 48 | 48 | Reserved | Reserved | Reserved | Reserved |
| 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 18 | EF2 | EF2 | EF2 | EF2 | 49 | 49 | MtrSw (DI Motor Switch Fault) | MtrSw (DI Motor Switch Fault) | MtrSw (DI Motor Switch Fault) | MtrSw (DI Motor Switch Fault) |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 19 | EF3 | EF3 | EF3 | EF3 | 50 | 50 | OCA (Acceleration over-current) | OCA (Acceleration over-current) | OCA (Acceleration over-current) | OCA (Acceleration over-current) |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 20 | EF4 | EF4 | EF4 | EF4 | 51 | 51 | OCD (Deceleration over-current) | OCD (Deceleration over-current) | OCD (Deceleration over-current) | OCD (Deceleration over-current) |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 | EF5 | EF5 | EF5 | EF5 | 52 | 52 | OCC (Operation over-current) | OCC (Operation over-current) | OCC (Operation over-current) | OCC (Operation over-current) |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 | EF6 | EF6 | EF6 | EF6 | 53 | 53 | CF08 | CF08 | CF08 | CF08 |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 23 | EF7 | EF7 | EF7 | EF7 | 54 | 54 | PTCLS | PTCLS | PTCLS | PTCLS |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 24 | EF8 | EF8 | EF8 | EF8 | 55 | 55 | PF (Protection fault) | PF (Protection fault) | PF (Protection fault) | PF (Protection fault) |
| 11 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 25 | FB (PID feedback signal error) | FB (PID feedback signal error) | FB (PID feedback signal error) | FB (PID feedback signal error) | 56 | 56 | TOL | TOL | TOL | TOL |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 26 | OPR(Keypad Removed) | OPR(Keypad Removed) | OPR(Keypad Removed) | OPR(Keypad Removed) | 57 | 57 | STO2 (Safety switch 2) | STO2 (Safety switch 2) | STO2 (Safety switch 2) | STO2 (Safety switch 2) |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 27 | Reserved | Reserved | Reserved | Reserved | 58 | 58 | Reserved | Reserved | Reserved | Reserved |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 28 | CE | CE | CE | CE | 59 | 59 | Reserved | Reserved | Reserved | Reserved |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 29 | STO (Safety switch 1) | STO (Safety switch 1) | STO (Safety switch 1) | STO (Safety switch 1) | 60 | 60 | Reserved | Reserved | Reserved | Reserved |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 30 | Reserved | Reserved | Reserved | Reserved | 61 | 61 | Reserved | Reserved | Reserved | Reserved |
| 17 | 2522H | DI status | 0 | Multi-function terminal S1 | Multi-function terminal S1 | 4 | Multi-function terminal S5 | Multi-function terminal S5 | Multi-function terminal S5 | Multi-function terminal S5 | Multi-function terminal S5 | 8~F | Reserved |
| 18 | 2522H | DI status | 1 | Multi-function terminal S2 | Multi-function terminal S2 | 5 | Multi-function terminal S6 | Multi-function terminal S6 | Multi-function terminal S6 | Multi-function terminal S6 | Multi-function terminal S6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 19 | 2522H | DI status | 2 | Multi-function terminal S3 | Multi-function terminal S3 | 6 | Multi-function terminal S7 | Multi-function terminal S7 | Multi-function terminal S7 | Multi-function terminal S7 | Multi-function terminal S7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 20 | 2522H | DI status | 3 | Multi-function terminal S4 | Multi-function terminal S4 | 7 | Multi-function terminal S8 | Multi-function terminal S8 | Multi-function terminal S8 | Multi-function terminal S8 | Multi-function terminal S8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 21 | 2523H | ⟦blank source cell⟧ | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) | Frequency command (0.01Hz) |
| 22 | 2524H | ⟦blank source cell⟧ | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) | Output frequency (0.01Hz) |
| 23 | 2526H | ⟦blank source cell⟧ | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) | DC voltage command (0.1V) |
| 24 | 2527H | ⟦blank source cell⟧ | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) | Output current (0.1A) |
| 25 | 2528H | Warning description | 0 | No alarm | 30 | RDE | RDE | RDE | 60 | 60 | Reserved | Reserved | Reserved |
| 26 | 2528H | Warning description | 1 | OV | 31 | WRE | WRE | WRE | 61 | 61 | RETRY | RETRY | RETRY |
| 27 | 2528H | Warning description | 2 | UV | 32 | FB | FB | FB | 62 | 62 | SE07 | SE07 | SE07 |
| 28 | 2528H | Warning description | 3 | OL2 | 33 | VRYE | VRYE | VRYE | 63 | 63 | Reserved | Reserved | Reserved |
| 29 | 2528H | Warning description | 4 | OH2 | 34 | SE01 | SE01 | SE01 | 64 | 64 | Reserved | Reserved | Reserved |
| 30 | 2528H | Warning description | 5 | Reserved | 35 | SE02 | SE02 | SE02 | 65 | 65 | OH1 | OH1 | OH1 |
| 31 | 2528H | Warning description | 6 | OT | 36 | SE03 | SE03 | SE03 | 66 | 66 | FIRE | FIRE | FIRE |
| 32 | 2528H | Warning description | 7 | Reserved | 37 | Reserved | Reserved | Reserved | 67 | 67 | ES | ES | ES |
Manual — CANopen warning continuation, output/analog registers and troubleshooting — page 602
Manual reference: physical PDF page 602. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.10.9 Troubleshooting
There are two indicators on top of the CANopen communication module; when malfunction occurs,
the cause of the malfunction can be confirmed based on the indicator statuses, and troubleshoot
the error by following the descriptions below.
CANopen warning continuation, output/analog registers and troubleshooting
Register address / / Bit / Content — PDF page 602
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Register address | ⟦blank source cell⟧ | Bit | Content | Content | Content | Content | Content |
| 2 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 8 | Reserved | 38 | SE05 | 68 | STP1 |
| 3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 9 | UT | 39 | HPERR | 69 | BDERR |
| 4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 10 | OS | 40 | EF | 70 | EPERR |
| 5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 11 | PGO | 41 | Reserved | 71 | Reserved |
| 6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 12 | DEV | 42 | Reserved | 72 | Reserved |
| 7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 13 | CE | 43 | RDP | 73 | STP0 |
| 8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 14 | CALL | 44 | Reserved | 74 | Reserved |
| 9 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 15 | Reserved | 45 | OL1 | 75 | STP2 |
| 10 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 16 | EF0 | 46 | Reserved | 76 | RUNER |
| 11 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 17 | EF1 | 47 | Reserved | 77 | LOC |
| 12 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 18 | EF2 | 48 | Reserved | 78 | PTCLS |
| 13 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 19 | EF3 | 49 | BB1 | 79 | Sys Init |
| 14 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 20 | EF4 | 50 | BB2 | 80 | FBLSS |
| 15 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 21 | EF5 | 51 | BB3 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 16 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 22 | EF6 | 52 | BB4 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 17 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 23 | EF7 | 53 | BB5 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 18 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 24 | EF8 | 54 | BB6 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 19 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 25 | Reserved | 55 | BB7 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 20 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 26 | Reserved | 56 | BB8 | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 21 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 27 | Reserved | 57 | Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 22 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 28 | Reserved | 58 | Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 23 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | 29 | Reserved | 59 | Reserved | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 24 | 2529H | ⟦blank source cell⟧ | DO status | DO status | DO status | DO status | DO status | DO status |
| 25 | 252AH | ⟦blank source cell⟧ | AO1 | AO1 | AO1 | AO1 | AO1 | AO1 |
| 26 | 252BH | ⟦blank source cell⟧ | AO2 | AO2 | AO2 | AO2 | AO2 | AO2 |
| 27 | 252CH | ⟦blank source cell⟧ | AI 1 input (0.1%) | AI 1 input (0.1%) | AI 1 input (0.1%) | AI 1 input (0.1%) | AI 1 input (0.1%) | AI 1 input (0.1%) |
| 28 | 252DH | ⟦blank source cell⟧ | AI 2 input (0.1%) | AI 2 input (0.1%) | AI 2 input (0.1%) | AI 2 input (0.1%) | AI 2 input (0.1%) | AI 2 input (0.1%) |
| 29 | 252FH | ⟦blank source cell⟧ | L510(s)/ E510(s)/ A510(s)/ F510 Check | L510(s)/ E510(s)/ A510(s)/ F510 Check | L510(s)/ E510(s)/ A510(s)/ F510 Check | L510(s)/ E510(s)/ A510(s)/ F510 Check | L510(s)/ E510(s)/ A510(s)/ F510 Check | L510(s)/ E510(s)/ A510(s)/ F510 Check |
Manual — CANopen troubleshooting and historical EDS reference — page 603
Manual reference: physical PDF page 603. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Indicator troubleshooting
Module status LED (RUN LED)
Error status LED (ERR LED)
11.10.10 EDS file
When using the CANopen communication module, if the EDS description file (JN5-CMHI-CAN_V
(latest version).eds) is needed, please download it from the TECO official website or request for it
from your purchasing sales channel.
CANopen troubleshooting and historical EDS reference
Indicator statuses / Status name / Troubleshooting method — PDF page 603
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Troubleshooting method |
| 2 | Does not light up | Power not supplied to the communication module | 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver. |
Indicator statuses / Status name / Description — PDF page 603
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Description |
| 2 | Single flash | CANopen packet error | Poor connection quality with the CANopen host terminal or host not connected when powered on. Continue transmission or power off inspection can be selected. Two results can be expected with continue transmission 1) Packet transmission returns to normal and the red light no longer flashes 2) Packet continues to have errors causing disconnection. When the power is off, check whether the TB1 terminal and cable are firmly connected, and whether the transmission rate, maximum transmission distance and cable length comply with ODVA specifications. |
| 3 | Double flash | Guard/Heartbeat error | User sends periodic heartbeat messages. If a message is not received after a specific time, please disconnect the power and check the connection status of that node. |
| 4 | Red light lights up | Disconnected | Cannot connect with the CANopen host terminal; disconnect the power and check whether the TB1 terminal and cable is firmly connected, and whether the transmission rate, maximum transmission distance and cable length comply with ODVA specifications. |
Manual — EtherCAT introduction and board labels — page 604
Manual reference: physical PDF page 604. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.11 Introduction to the EtherCAT high speed communication
expansion module
11.11.1 Communication hardware and data structure
This product is the EtherCAT high-speed communication expansion module (hereinafter referred to
as communication module); it can perform remote setting and communication functions through the
EtherCAT network environment. It can only be used with the TECO A510s/F510 AC motor driver
(hereinafter referred to as a driver), and allow the driver to operate on the EtherCAT network.
EtherCAT board drawing:JN5-CMHI-ECAT;41S1499;4KA69X1023W13;FAB11-202-031C;CN1,12,2,1,C72,C73,C74,R20,R19,C75,R18,R17,C14,CN5,2,1,R12,R15,R16,R13,R11,R14,C8,C1,C13,U1,X1,C10,C7,C4,R1,R2,12,11,C2,R31,C6,R32,R33,R34,R24,R23,R22,C17,C16,C19,C18,C22,C76,R30,D1,D2,R8,R9,R10,LED1,LED2,R7,U2,X2,C36,C35,R39,R40,C20,R36,U10,R68,R29,R51,R28,R41,R46,R45,R44,R43,R25,R64,R63,R62,R61,C45,C44,C43,C42,C55,C54,C53,C51,R77,R42,T1,T2,CN34,IN,OUT. Source symbols,outline and repeatedlabels preserved;no topology or unprinted component ratings reconstructed.
Manual — EtherCAT/driver ports and installation connectors — page 605
Manual reference: physical PDF page 605. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny photographed component markings and some board references.
11.11.2 Product specifications
EtherCAT ports
AC motor driver port
11.11.3 Installation instructions
Communication module contact description
As shown in the figure below, the framed part is the CN5 connector that connects to the
driver.
Communication module network socket
As shown in the figure below, the left socket is input and the right socket is output.
EtherCAT board photograph:source red frame highlights CN5 driver connector. Readable identifiers JN5-CMHI-ECAT,41S1499,FAB11-202-031C,4KA69X1023T01,V1.0;IN,OUT,LED1,LED2. Tiny component body inscriptions andsomeboardreferences remain unresolved after4x;not inferred from drawing604,which hasW13 instead ofphotoT01. Source prose specifies connectorfunction separately.
EtherCAT dual socket photograph:Input callout points to left socket;Output callout to right socket. Source prose repeats left input/right output. Image preserved;no connectorpin/wiring assignment inferred.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny photographed component body inscriptions and some board references.
Pulse
H1102FNL
EtherCAT/driver ports and installation connectors
Item / Specifications — PDF page 605
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | Dual-port network socket |
| 3 | Network protocols | EtherCAT communication protocol |
Item / Specifications — PDF page 605
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | Communication card CN5 connector |
| 3 | Terminal functions | 1. The communication module communicates with the AC motor driver through this interface. 2. The AC motor driver provides power to the communication module through this interface. |
Manual — EtherCAT driver parameters and module/network LEDs — page 606
Manual reference: physical PDF page 606. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Driver parameter setting description
Users must first confirm related parameter settings on the driver in order to ensure that the communication module can connect normally.
11.11.4 LED indicator descriptions The module has two dual-color LED indicators built-in used to quickly diagnose and monitor the communication statuses between the module itself and the EtherCAT network.
Module status LED2
Used to monitor whether the communication module is operating normally.
Network status LED1
Used to monitor the operability of the communication module EtherCAT network.
EtherCAT driver parameters and module/network LEDs
Parameters / Parameter name / Settings / Settings descriptions — PDF page 606
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Parameters | Parameter name | Settings | Settings descriptions |
| 2 | 00-02 | Operation command source | 2 | Communication control |
| 3 | 00-05 | Frequency command source | 3 | Communication control |
Indicator statuses / Status name / Description — PDF page 606
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Description |
| 2 | Does not light up | Power not supplied | Power not supplied |
| 3 | Red light flashes | Data transmitting | Driver and communication expansion module data transmitting |
| 4 | Red/green light lights up | Driver data transmission error | Data transmission error between the driver and communication expansion module |
Indicator statuses / Status name / Description — PDF page 606
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Description |
| 2 | Does not light up | Not connected / INIT | EtherCAT network not connected (INIT) |
| 3 | Green light flashes | Standby | Preparation status (Pre-OP) |
| 4 | Green light lights up | Operation status | Operation status (OP) |
| 5 | Red light lights up | Driver data transmission error | Data transmission error between the driver and communication expansion module |
Manual — EtherCAT basic object index and PDO mappings — page 607
Manual reference: physical PDF page 607. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.11.5 Object index list
Basic index
EtherCAT basic object index and PDO mappings
Index / Sub- Index / Name / Default value / R/W / Size / Remarks — PDF page 607
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Index | Sub- Index | Name | Default value | R/W | Size | Remarks |
| 2 | 1000H | 0 | Device type | 00000192H | R | U32 | ⟦blank source cell⟧ |
| 3 | 1001H | 0 | Error register | 0 | R | U8 | ⟦blank source cell⟧ |
| 4 | 1008H | 0 | Manufacturer device name | JN5-CM-CA N | R | U32 | ⟦blank source cell⟧ |
| 5 | 1009H | 0 | Manufacturer hardware version | Version | R | U32 | ⟦blank source cell⟧ |
| 6 | 100AH | 0 | Manufacturer software version | Version | R | U32 | ⟦blank source cell⟧ |
| 7 | 1018H | 0 | number of entries | 4 | R | U8 | ⟦blank source cell⟧ |
| 8 | 1018H | 1 | Vender ID | 0000081BH | R | U32 | ⟦blank source cell⟧ |
| 9 | 1018H | 2 | Product code | 00000001H | R | U32 | ⟦blank source cell⟧ |
| 10 | 1018H | 3 | Revision | 00000001H | R | U32 | ⟦blank source cell⟧ |
| 11 | 1600H | 0 | Number of entries | 2 | RW | U8 | ⟦blank source cell⟧ |
| 12 | 1600H | 1 | 1.Mapped Object | 60400010H | RW | U32 | ⟦blank source cell⟧ |
| 13 | 1600H | 2 | 2.Mapped Object | 60420010H | RW | U32 | ⟦blank source cell⟧ |
| 14 | 1600H | 3 | 3.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 15 | 1600H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 16 | 1601H | 0 | Number of entries | 2 | RW | U8 | ⟦blank source cell⟧ |
| 17 | 1601H | 1 | 1.Mapped Object | 604F0010H | RW | U32 | ⟦blank source cell⟧ |
| 18 | 1601H | 2 | 2.Mapped Object | 60500010H | RW | U32 | ⟦blank source cell⟧ |
| 19 | 1601H | 3 | 3.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 20 | 1601H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 21 | 1A00H | 0 | Number of entries | 3 | RW | U8 | ⟦blank source cell⟧ |
| 22 | 1A00H | 1 | 1.Mapped Object | 60400010 | RW | U32 | ⟦blank source cell⟧ |
| 23 | 1A00H | 2 | 2.Mapped Object | 60420010 | RW | U32 | ⟦blank source cell⟧ |
| 24 | 1A00H | 3 | 3.Mapped Object | 604F0020 | RW | U32 | ⟦blank source cell⟧ |
| 25 | 1A00H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 26 | 1A01H | 0 | Number of entries | 3 | RW | U8 | ⟦blank source cell⟧ |
| 27 | 1A01H | 1 | 1.Mapped Object | 604F0020 | RW | U32 | ⟦blank source cell⟧ |
| 28 | 1A01H | 2 | 2.Mapped Object | 60500020 | RW | U32 | ⟦blank source cell⟧ |
| 29 | 1A01H | 3 | 3.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
| 30 | 1A01H | 4 | 4.Mapped Object | 0 | RW | U32 | ⟦blank source cell⟧ |
Manual — EtherCAT object index, U32 ramp times — page 608
Manual reference: physical PDF page 608. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Object part
EtherCAT object index, U32 ramp times
Index / Sub- Index / Name / Default value / R/W / Size / Unit / PDO MAP — PDF page 608
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|
| 1 | Index | Sub- Index | Name | Default value | R/W | Size | Unit | PDO MAP |
| 2 | 603F | 0 | Error code | 0 | RO | U16 | ⟦blank source cell⟧ | Yes |
| 3 | 6040 | 0 | Control word | 0 | RW | U16 | ⟦blank source cell⟧ | Yes |
| 4 | 6041 | 0 | Status word | 0 | RO | U16 | ⟦blank source cell⟧ | Yes |
| 5 | 6042 | 0 | vl target velocity | 0 | RW | S16 | Hz | Yes |
| 6 | 6043 | 0 | vl velocity demand | 0 | RO | S16 | Hz | Yes |
| 7 | 604F | 0 | vl ramp function time Acceleration time | Driver default value | RW | U32 | 0.1S | Yes |
| 8 | 6050 | 0 | vl slow down time Deceleration time | Driver default value | RW | U32 | 0.1S | Yes |
Manual — EtherCAT troubleshooting and historical xml reference — page 609
Manual reference: physical PDF page 609. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.11.6 Troubleshooting
There are two indicators on top of the EtherCAT communication module. When a malfunction
occurs, the cause of the malfunction can be confirmed based on the indicator statuses, and
troubleshoot the error by following the descriptions below.
Indicator troubleshooting
Module status LED2
Network status LED1
11.11.7 xml file
When using the EtherCAT communication module, if the xml description file (JN5-CMHI-ECAT_V
(latest version).xml) is needed, please download it from the TECO official website or request for it
from your purchasing sales channel.
EtherCAT troubleshooting and historical xml reference
Indicator statuses / Status name / Troubleshooting method — PDF page 609
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Troubleshooting method |
| 2 | Does not light up | Power not supplied | 1. Confirm whether the driver power is normal. 2. Confirm whether the power terminal of the communication module is connected to the driver. |
| 3 | Red/green light lights up | Driver data transmission error | 1. Confirm whether the communication module has proper contact. 2. Reconnect the power of the driver and confirm whether the error has been eliminated. |
Indicator statuses / Status name / Description — PDF page 609
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Indicator statuses | Status name | Description |
| 2 | Does not light up | Not connected / INIT | 1. Confirm whether the driver power is normal. 2. If connected to EtherCAT, confirm whether it is in INIT mode. |
| 3 | Red light lights up | Driver data transmission error | 1. Confirm whether the communication module has proper contact. 2. Reconnect the power of the driver and confirm whether the error has been eliminated. |
Manual — I/O expansion card hardware and TB1 connector — page 610
Manual reference: physical PDF page 610. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Overlapping tiny board reference clusters remain unresolved after 4x review.
11.12 I/O expansion card
11.12.1 Hardware and data structure
This product is an I/O expansion module; it allows performing of I/O expansion functions through
the SPI bus. Used with the TECO A510s/F510 AC motor driver (hereinafter referred to as a driver).
11.12.2 Product specifications
I/O ports
I/O boarddrawing:JN5-IO-2DO1AI;41S1500;4KA69X1024W13;FAB11-202-032C;TB1terminalsR4A,R4B,R4C,DO2,DOG,AI3,GND. ReadablelabelsCN5,C12,C1,C5,D5,D2,D3,D1,Q1,R5,R1,R7,R8,R6,R4,C3,C13,R2,C10,C14,R9,C31,C11,IC1,C4,C32,C15,C2,TP,R18,C24,C25,C28,R22,R23,C29,C30,D7,IC2,R15,IC9,C8,C7,C6,D4,Q2,Q3,RY4,R24,C26,C21,C22,SW7,R13,C19,R10,R12,R11,PC11,C9,C16,L1,C17,C18,TVS1,TVS2,2,12,11. Tiny overlapping referencecluster abovehatchedarea andnearD6/C21not fullyresolved at4x;pagepartial forremainingcharacters. No topology inferred fromschematic.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Overlapping tiny board reference clusters remain unresolved after 4x review.
I/O expansion card hardware and TB1 connector
Item / Specifications — PDF page 610
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | TB1 7 external contacts |
Manual — I/O terminal specifications and group3/4 reference — page 611
Manual reference: physical PDF page 611. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
AC motor driver port
11.12.3 Installation instructions
Contact description
11.12.4 Driver parameter setting descriptions Please refer to group 3, 4 parameter descriptions in the manual
I/O terminal specifications and group3/4 reference
Item / Specifications — PDF page 611
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Connector | Control board CN5 connector |
| 3 | Transmission method | SPI high speed communication |
| 4 | Terminal functions | TB1 7 external contacts, applicable wire diameter: AWG 20~14 stranded wire |
Type / Terminal / Terminal functions / Signal level — PDF page 611
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Type | Terminal | Terminal functions | Signal level |
| 2 | Analog input signal | AI3 | Main speed command input; SW7 can be used to switch between voltage or current input (-10~10V)/(4-20mA) | -10V to +10V, (Input resistance 500KΩ) 4 to 20 mA (Input resistance: 500Ω) (12bit resolution) |
| 3 | Analog input signal | GND | Analog signal shared terminal | ---- |
| 4 | Relay Output | R4A- R4B- R4C | Relay A contact (multi-function output terminal) Relay B contact (multi-function output terminal) Relay shared terminal; please refer to the manual for its functions. | Terminal capacity: At 250Vac, 10 mA~1A At 30Vdc, 10 mA~1A |
| 5 | Digital Output | DO2 | Multi-function (open collector transistor) output: Operating, zero speed, frequency consistent, any frequency consistent, output frequency, preparation complete, low-voltage detection, output occlusion, operation and frequency commands, over-torque detection, abnormal, low-voltage, overheat, motor over-load, frequency converter over-load output, retrying, signal abnormal, chronograph output… | 48Vdc, 2 mA~50mA Optical coupling output |
| 6 | Digital Output | DOG | Open collector transistor shared terminal | ⟦blank source cell⟧ |
Manual — DC reactor benefits and200V/start400V HD/ND table — page 612
Manual reference: physical PDF page 612. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.13 DC reactor
Installing a DC reactor at the DC terminal of the frequency converter provides the following advantages: • Improves the input current waveform distortion caused by the rectifier in the frequency converter while maintaining continuous rectified current. • Suppresses instantaneous current surges and prevents related overheating phenomenon caused by the rectifier and voltage regulator components due to instantaneous current surges. • Reduces harmonic interference problems generated by the frequency converter. • Improves and increase power factor and reduces AC component pulses at the DC terminal. • Compared to AC reactors, the size of DC reactors are smaller and the costs are also lower. Table 6.13 DC reactor list
DC reactor benefits and200V/start400V HD/ND table
Model / DC reactor — PDF page 612
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | DC reactor | DC reactor |
| 2 | V | HP | Rated current (A) HD/ND | Inductance value (mH) | Rated current (A) |
| 3 | 200V 1 Ø /3 Ø | 1 | 5/6 | 2.9 | 10 |
| 4 | 200V 1 Ø /3 Ø | 2 | 8/9.6 | 2 | 15 |
| 5 | 200V 1 Ø /3 Ø | 3 | 11/12 | 1.2 | 20 |
| 6 | 200V 3 Ø | 5.4 | 17.5/22 | 0.78 | 35 |
| 7 | 200V 3 Ø | 7.5 | 25/30 | 0.57 | 45 |
| 8 | 200V 3 Ø | 10 | 33/42 | 0.39 | 65 |
| 9 | 200V 3 Ø | 15 | 47/56 | 0.29 | 85 |
| 10 | 200V 3 Ø | 20 | 60/69 | 0.23 | 105 |
| 11 | 200V 3 Ø | 25 | 73/79 | 0.2 | 120 |
| 12 | 200V 3 Ø | 30 | 85/110 | 0.14 | 165 |
| 13 | 200V 3 Ø | 40 | 115/138 | 0.12 | 210 |
| 14 | 200V 3 Ø | 50 (built-in) | 145/169 | 0.1 | 200 |
| 15 | 200V 3 Ø | 60 (built-in) | 180/200 | 0.08 | 260 |
| 16 | 200V 3 Ø | 75 (built-in) | 215/250 | 0.08 | 390 |
| 17 | 200V 3 Ø | 100 (built-in) | 283/312 | 0.08 | 390 |
| 18 | 200V 3 Ø | 125 (built-in) | 346/400 | 0.065 | 520 |
| 19 | 200V 3 Ø | 150 (built-in) | 415/450 | 0.05 | 800 |
| 20 | 400V 3 Ø | 1 | 3.4/4.1 | 10.2 | 6.5 |
| 21 | 400V 3 Ø | 2 | 4.2/5.4 | 7 | 8.5 |
| 22 | 400V 3 Ø | 3 | 5.5/6.9 | 4.2 | 11 |
Manual — DC reactor400V continuation;voltageblank andP1/P2note — page 613
Manual reference: physical PDF page 613. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: When using DC reactors, please first remove the short-circuit copper sheet between the P1 and P2 terminals, and then fix the current reactor on these two terminals.
DC reactor400V continuation;voltageblank andP1/P2note
Model / DC reactor — PDF page 613
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | DC reactor | DC reactor |
| 2 | V | HP | Rated current (A) HD/ND | Inductance value (mH) | Rated current (A) |
| 3 | ⟦blank source cell⟧ | 5.4 | 9.2/12.1 | 2.8 | 20 |
| 4 | ⟦blank source cell⟧ | 7.5 | 14.8/17.5 | 2.1 | 30 |
| 5 | ⟦blank source cell⟧ | 10 | 18/23 | 1.4 | 35 |
| 6 | ⟦blank source cell⟧ | 15 | 24/31 | 1.0 | 50 |
| 7 | ⟦blank source cell⟧ | 20 | 31/38 | 0.83 | 60 |
| 8 | ⟦blank source cell⟧ | 25 | 39/44 | 0.7 | 70 |
| 9 | ⟦blank source cell⟧ | 30 | 45/58 | 0.51 | 90 |
| 10 | ⟦blank source cell⟧ | 40 | 60/73 | 0.41 | 115 |
| 11 | ⟦blank source cell⟧ | 50 | 75/88 | 0.34 | 140 |
| 12 | ⟦blank source cell⟧ | 60 | 91/103 | 0.28 | 160 |
| 13 | ⟦blank source cell⟧ | 75 | 118/145 | 0.2 | 230 |
| 14 | ⟦blank source cell⟧ | 100 (built-in) | 150/168 | 0.18 | 240 |
| 15 | ⟦blank source cell⟧ | 125 (built-in) | 180/208 | 0.15 | 240 |
| 16 | ⟦blank source cell⟧ | 150 (built-in) | 216/250 | 0.22 | 290 |
| 17 | ⟦blank source cell⟧ | 175 (built-in) | 260/296 | 0.15 | 370 |
| 18 | ⟦blank source cell⟧ | 215 (built-in) | 295/328 | 0.15 | 370 |
| 19 | ⟦blank source cell⟧ | 270 (built-in) | 380/435 | 0.12 | 520 |
| 20 | ⟦blank source cell⟧ | 300 (built-in) | 450/515 | 0.08 | 800 |
| 21 | ⟦blank source cell⟧ | 375 (built-in) | 523/585 | 0.08 | 800 |
| 22 | ⟦blank source cell⟧ | 425 (built-in) | 585/585 | 0.08 | 800 |
Manual — Sinusoidal output reactor explanation;200V/400Vtable — page 614
Manual reference: physical PDF page 614. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.14 Sinusoidal output reactor
The parasitic inductance and capacitance that exist in the frequency converter and motor wiring are determined by the component switching speed and wiring of the frequency converter. The voltage of the motor terminal will reach as high as twice the DC voltage of the frequency converter. LC resonance may cause surge voltages at the motor terminal and cause danger. Installing an AC reactor at the frequency converter output can suppress voltages (dv/dt). If the wiring length is too long, suppression of surge voltages will become more difficult. Installing a sinusoidal output reactor at the output terminal of the frequency converter can prevent the motor terminal voltage from generating surges. Table 6.14 Sinusoidal output reactor list
Sinusoidal output reactor explanation;200V/400Vtable
Model / Output reactor — PDF page 614
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | Output reactor | Output reactor |
| 2 | V | HP | Rated current (A) HD/ND | Inductance value (mH) | Rated current (A) |
| 3 | 200V 1 Ø /3 Ø | 1 | 5/6 | 0.61 | 6 |
| 4 | 200V 1 Ø /3 Ø | 2 | 8/9.6 | 0.38 | 9.6 |
| 5 | 200V 1 Ø /3 Ø | 3 | 11/12 | 0.31 | 12 |
| 6 | 200V 3 Ø | 5.4 | 17.5/22 | 0.17 | 22 |
| 7 | 200V 3 Ø | 7.5 | 25/30 | 0.12 | 30 |
| 8 | 200V 3 Ø | 10 | 33/42 | 0.09 | 42 |
| 9 | 200V 3 Ø | 15 | 47/56 | 0.07 | 56 |
| 10 | 200V 3 Ø | 20 | 60/69 | 0.05 | 69 |
| 11 | 200V 3 Ø | 25 | 73/79 | 0.05 | 79 |
| 12 | 200V 3 Ø | 30 | 85/110 | 0.03 | 110 |
| 13 | 200V 3 Ø | 40 | 115/138 | 0.03 | 138 |
| 14 | 200V 3 Ø | 50 | 145/169 | 0.02 | 169 |
| 15 | 200V 3 Ø | 60 | 180/200 | 0.017 | 200 |
| 16 | 200V 3 Ø | 75 | 215/250 | 0.013 | 250 |
| 17 | 200V 3 Ø | 100 | 283/312 | 0.013 | 312 |
| 18 | 200V 3 Ø | 125 | 346/400 | 0.008 | 400 |
| 19 | 200V 3 Ø | 150 | 415/450 | 0.008 | 450 |
| 20 | 400V 3 Ø | 1 | 3.4/4.1 | 1.7 | 4.1 |
| 21 | 400V 3 Ø | 2 | 4.2/5.4 | 1.29 | 5.4 |
| 22 | 400V 3 Ø | 3 | 5.5/6.9 | 1.01 | 6.9 |
| 23 | 400V 3 Ø | 5.4 | 9.2/12.1 | 0.58 | 12.1 |
| 24 | 400V 3 Ø | 7.5 | 14.8/17.5 | 0.4 | 17.5 |
| 25 | 400V 3 Ø | 10 | 18/23 | 0.3 | 23 |
| 26 | 400V 3 Ø | 15 | 24/31 | 0.23 | 31 |
Manual — Output reactor400Vcontinuation and575V/690VNDtable — page 615
Manual reference: physical PDF page 615. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Output reactor400Vcontinuation and575V/690VNDtable
Model / Output reactor — PDF page 615
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | Output reactor | Output reactor |
| 2 | V | HP | Rated current (A) HD/ND | Inductance value (mH) | Rated current (A) |
| 3 | ⟦blank source cell⟧ | 20 | 31/38 | 0.18 | 38 |
| 4 | ⟦blank source cell⟧ | 25 | 39/44 | 0.16 | 44 |
| 5 | ⟦blank source cell⟧ | 30 | 45/58 | 0.12 | 58 |
| 6 | ⟦blank source cell⟧ | 40 | 60/73 | 0.1 | 73 |
| 7 | ⟦blank source cell⟧ | 50 | 75/88 | 0.08 | 88 |
| 8 | ⟦blank source cell⟧ | 60 | 91/103 | 0.07 | 103 |
| 9 | ⟦blank source cell⟧ | 75 | 118/145 | 0.05 | 145 |
| 10 | ⟦blank source cell⟧ | 100 | 150/168 | 0.04 | 168 |
| 11 | ⟦blank source cell⟧ | 125 | 180/208 | 0.032 | 208 |
| 12 | ⟦blank source cell⟧ | 150 | 216/250 | 0.027 | 250 |
| 13 | ⟦blank source cell⟧ | 175 | 260/296 | 0.023 | 296 |
| 14 | ⟦blank source cell⟧ | 215 | 295/328 | 0.021 | 328 |
| 15 | ⟦blank source cell⟧ | 270 | 380/435 | 0.015 | 435 |
| 16 | ⟦blank source cell⟧ | 300 | 450/515 | 0.012 | 515 |
| 17 | ⟦blank source cell⟧ | 375 | 523/585 | 0.012 | 585 |
| 18 | ⟦blank source cell⟧ | 425 | 585/585 | 0.012 | 585 |
Model / Output reactor — PDF page 615
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | Output reactor | Output reactor |
| 2 | V | HP | Rated current ND (A) | Inductance value (mH) | Rated Current (A) |
| 3 | 575V 3 Ø | 1 | 3 | 1.47 | 4 |
| 4 | 575V 3 Ø | 2 | 4.2 | 1.05 | 5 |
| 5 | 575V 3 Ø | 3 | 5.8 | 0.76 | 8 |
| 6 | 575V 3 Ø | 4 | 8.8 | 0.5 | 11 |
| 7 | 575V 3 Ø | 7.5 | 12.2 | 0.36 | 16 |
| 8 | 575V 3 Ø | 10 | 14.5 | 0.30 | 19 |
| 9 | 690V 3 Ø | 15 | 19 | 0.28 | 25 |
| 10 | 690V 3 Ø | 20 | 22 | 0.24 | 29 |
| 11 | 690V 3 Ø | 25 | 27 | 0.2 | 35 |
| 12 | 690V 3 Ø | 30 | 34 | 0.16 | 44 |
| 13 | 690V 3 Ø | 40 | 42 | 0.13 | 55 |
| 14 | 690V 3 Ø | 50 | 52 | 0.1 | 68 |
| 15 | 690V 3 Ø | 60 | 62 | 0.09 | 81 |
| 16 | 690V 3 Ø | 75 | 80 | 0.07 | 104 |
| 17 | 690V 3 Ø | 100 | 99 | 0.05 | 129 |
Manual — Output reactorNDcontinuation and24VDC expansioncard — page 616
Manual reference: physical PDF page 616. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Note: 1. The frequency converter has improved IGBT equipment and soft-switching driver circuit; compared to previous models, it can improve dv/dt by approximately 50% terminal voltage. 2. The purposes of installing sinusoidal output filters are as follows: ‧ Prolong motor life. ‧ Reduce motor interference. ‧ Reduce frequency converter pulse load. ‧ Improve system stability and efficiency.
11.15 DC24V power expansion card
This product allows parts of the communication or driver functions to operate normally before connecting power to the inverter. 11.15.1 JN5-PS-DC24V product specifications
Connection terminal
Output reactorNDcontinuation and24VDC expansioncard
Model / Output reactor — PDF page 616
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) |
|---|---|---|---|---|---|
| 1 | Model | Model | Model | Output reactor | Output reactor |
| 2 | V | HP | Rated current ND (A) | Inductance value (mH) | Rated Current (A) |
| 3 | ⟦blank source cell⟧ | 125 | 125 | 0.04 | 163 |
| 4 | ⟦blank source cell⟧ | 150 | 147 | 0.04 | 191 |
| 5 | ⟦blank source cell⟧ | 175 | 163 | 0.03 | 212 |
| 6 | ⟦blank source cell⟧ | 215 | 212 | 0.02 | 276 |
| 7 | ⟦blank source cell⟧ | 250 | 216 | 0.02 | 281 |
| 8 | ⟦blank source cell⟧ | 270 | 246 | 0.02 | 320 |
Item / Specifications — PDF page 616
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Item | Specifications |
| 2 | Input terminal | 24V: 24V±5%, 0.6A 0V: 24V reference ground |
| 3 | Notes | The terminals above cannot be connected to the power and terminals on the frequency converter itself in order to achieve the goal of safety isolation. |
Manual — JN5-CMHI-EIP preparation and internal card installation — page 617
Manual reference: physical PDF page 617. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.16 EtherNet/IP Communication Card (JN5-CMHI-EIP)
The section heading qualifies the downstream screenshot.
11.16 EtherNet/IP Communication Card (JN5-CMHI-EIP) 11.16.1 Preparations before using the instrument A510s or F510 Enhanced series inverter *1
IBM PC or compatible computer (with the following related software installed) *1
BOOTP-DHCP Tool (Rockwell IP setting software)
RSlinx Classic (Rockwell communication software)
Connected Components Workbench (Rockwell PLC software)
Molex Ethernet/IP Tool (Ethernet IP setting software)
12 pin cable (4KA97X1695T01 or 4KA97X1696T01) *1
Ethernet/IP Programmable Logic Controller (EX: Micro820) *1
CAT5e Ethernet cable *2 11.16.2 Installation of a semi-finished product Open the top cover of the inverter and install the communication card CN5 to the control board CN2 using a cable (4KA97X1695T01 or 4KA97X1696T01).
A510s / F510 Enhanced inverter parameter settings
JN5-CMHI-EIP preparation and internal card installation
Run command / Communication method / 00-02=2 — PDF page 617
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Run command | Communication method | 00-02=2 |
| 2 | Frequency command | Communication method | 00-05=5 |
| 3 | Acceleration time | 10.0s | 00-14=100 |
| 4 | Deceleration time | 10.0s | 00-15=100 |
Manual — JN5-CMHI-EIP network connection examples — page 618
Manual reference: physical PDF page 618. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Loopback address truncated in source screenshot.
11.16.3 Connection steps Connect with the PC network and set the IP (as shown in the figure below, set the PC network card IP).
Execute the Rockwell BOOTP-DHCP Tool and select the PC network card
Windows dialog 網際網路通訊協定第4版(TCP/IPv4)-內容;一般. Text:如果您的網路支援這項功能,您可以取得自動指派的IP設定。否則,您必須詢問網路系統管理員正確的IP設定。自動取得IP位址(O)unselected;使用下列的IP位址(S)selected;IP位址(I)192.168.22.1;子網路遮罩(U)255.255.255.0;預設閘道(D)blank. 自動取得DNS伺服器位址(B)unselected;使用下列的DNS伺服器位址(E)selected;慣用DNS伺服器(P)192.168.22.1;其他DNS伺服器(A)blank. 結束時確認設定(L)unchecked;進階(V)...,確定,取消. These are source example values,not applied settings.
Select Network Interface;Please select a network interface;columnsDescription/IPAddress. Npcap Loopback Adapter→169.254.223…(source ellipsis;remainingaddressunknown);Intel(R)WiFi Link5100AGN→10.101.24.35;selectedBroadcom NetXtreme Gigabit Ethernet→192.168.22.1;OK. No complete address inferred fromtruncatedloopbackrow.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Loopback address truncated in source screenshot.
Manual — JN5-CMHI-EIP DHCP relation assignment example — page 619
Manual reference: physical PDF page 619. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The Rockwell BOOTP-DHCP Tool scans the MAC Address of the communication module, then select ADD RELATION and set the CLIENT IP ADDRESS to 192.168.22.2
Set and confirm the IP status (using Micro820 as the example) of the A510s/F510 communication card (Ethernet/IP).
BootP DHCP EtherNet/IP Commissioning Tool;File,Tools,Help;AddRelation,ClearHistory. DiscoveryHistorycolumnsEthernetAddress(MAC),Type,[hr:min:sec],#,IPAddress,Hostname;EnteredRelationscolumnsEthernetAddress(MAC),Type,IPAddress,Hostname,Description;Errorsandwarnings;Relations. Discoveryrow00:02:A2:58:5A:86,DHCP,14:56:49,1,IPblank,Hostnameblank. EnteredRelationsempty. MessageUnable to service DHCP request from00:02:A2:58:5A:86. Relations0of256.
BootP DHCP EtherNet/IP Commissioning Tool;File,Tools,Help;AddRelation,ClearHistory. DiscoveryHistorycolumnsEthernetAddress(MAC),Type,[hr:min:sec],#,IPAddress,Hostname;EnteredRelationscolumnsEthernetAddress(MAC),Type,IPAddress,Hostname,Description;Errorsandwarnings;Relations. NewEntrydialog:ServerIPAddress192.168.22.1;ClientAddress(MAC)00:02:A2:58:5A:86;ClientIPAddress192.168.22.2;Hostnameblank;Descriptionblank;OK,Cancel. Backgroundremainingrowobscuredbydialog;not reconstructed. ErrorUnable to service DHCP request from00:02:A2:58:5A:86;Relations0of256.
BootP DHCP EtherNet/IP Commissioning Tool;File,Tools,Help;AddRelation,ClearHistory. DiscoveryHistorycolumnsEthernetAddress(MAC),Type,[hr:min:sec],#,IPAddress,Hostname;EnteredRelationscolumnsEthernetAddress(MAC),Type,IPAddress,Hostname,Description;Errorsandwarnings;Relations. Discoveryrow00:02:A2:58:5A:86,DHCP,15:05:49,11,192.168.22.2,Hostnameblank. EnteredRelationsrow00:02:A2:58:5A:86,DHCP,192.168.22.2,Hostnameblank,Descriptionblank. StatusSent192.168.22.2toEthernetaddress00:02:A2:58:5A:86;Relations1of256. Sourceexampleonly.
Manual — JN5-CMHI-EIP CCW PLC IP andRSLinx configuration example — page 620
Manual reference: physical PDF page 620. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny PLC illustration labels and ellipsized connection path.
Execute Connected Components Workbench, open a Project file and set the Micro800 PLC address (192.168.22.4) and subnet mask (255.255.255.0); they do not need to be changed again after the setting is completed
Check whether the network connection is successful, as shown in the figure below. Execute RSlinx Classic Lite and execute Configure Drivers
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Disconnected;Connect. Controller-Ethernet:ObtainIPaddressautomaticallyusingDHCPunselected;ConfigureIPaddressandsettingsselected;IPAddress192.168.22.4;SubnetMask255.255.255.0. NavigationGeneral,Memory,Startup/Faults,SerialPort,Ethernet,Interrupts,ModbusMapping,RealTimeClock,EmbeddedI/O,MemoryCard. TinyPLCpictureinscriptions andellipsizedconnectionpath notfullyrecoverable;preserveimagewithpartialscope.
RSLinx Classic Lite-[RSWho-1];File,View,Communications,Station,DDE/OPC,Security,Window,Help;Autobrowsechecked. CommunicationsmenuRSWho,ConfigureDrivers...(selected),ConfigureShortcuts...,ConfigureClientApplications...,ConfigureCIPOptions...,DriverDiagnostics...,CIPDiagnostics.... StatusConfigurecommunicationhardware;NUM;07/16/20;10:12AM. Backgroundtreecovered bymenu;no hiddenitem reconstructed.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny PLC illustration labels and ellipsized connection path.
Manual — EtherNet/IP driver configuration screenshot — page 621
Manual reference: physical PDF page 621. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Select Ethernet/IP Driver, Add new, and select the IP of the PC network card
Screenshot example values only; IPs are examplePCadapteraddresses, not mandatory drive orPLCdefaults. Both page associations retained even where screenshot content repeats.
Configuration-dialog labels and adapter table transcribed; incidental desktop/menu/status-bar text remains original-only.
Labels show manual example workflow; no live software operation performed.
First two headers physical; selection-state column is editorial description of highlight. IPs are source examples, not site configuration.
Configuration-dialog labels — PDF page 621
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Available Driver Types | EtherNet/IP Driver |
| 2 | Action button | Add New... |
| 3 | Configure driver | AB_ETHIP-1 |
| 4 | Settings tab | EtherNet/IP Settings |
| 5 | Selected radio option | Browse Local Subnet |
| 6 | Other radio option | Browse Remote Subnet |
Example network-adapter choices — PDF page 621
| Source row | Description | IP Address | Source selection state |
|---|---|---|---|
| 1 | Windows Default | [blank in source] | Not highlighted |
| 2 | Npcap Loopback Adapter | 169.254.223.52 | Not highlighted |
| 3 | Broadcom NetXtreme Gigabit Ethernet | 192.168.22.1 | Highlighted |
Manual — JN5-CMHI-EIP device discovery andCCWlocalvariables — page 622
Manual reference: physical PDF page 622. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Truncated variable names, types and comments; ellipsized labels.
Expand AB_ETHIP-1, the PLC (192.168.22.4) and communication card (192.168.22.2) can be seen
Open the CCW project file and confirm that the IP DHCP is assigned to the expansion card for Local Variables -> A_TarCfg.Path is 192.168.22.2
RSLinx Classic Lite-[RSWho-1];menusFile,View,Communications,Station,DDE/OPC,Security,Window,Help;Autobrowsechecked,Refresh,NotBrowsing. TreeWorkstationWG-CHRISN98-W77;LinxGateways,Ethernet;AB_ETHIP-1,Ethernet;192.168.22.2,UnrecognizedDevice,JN5-CM-EIP;192.168.22.4,Micro820,2080-LC20-20QWBselected. RighticonsBackplaneMicro80… andChannel2DF1;statusForHelp,pressF1;NUM;07/28/20;03:45PM. DeviceidentitysourceisJN5-CM-EIP despite sectionJN5-CMHI-EIP;do not substitute.
CCWprojectEIP_Assembly_100_2_vsd;Disconnected;Run-VAR,Micro820,StartPage;LocalVariablesselected. TablecolumnsName,Alias,DataType,Dimension,ProjectValue,InitialValue,Comment. VisibleRows:MSG_CIPGENERIC_1 typeMSG_CIPGEN…;SetSpeed_vsd1 BOOL;A_CtrlCfg CIPCONTROL;A_AppCfg CIPAPPCFG;A_TarCfg CIPTARGETCF…;A_TarCfg.Path STRING initialvalue'4,192.168.22.2' commentCIPdestinationpath;A_TarCfg.CipCo… USINT initial1 comment0-Unconnected,1-Class3conn…;A_TarCfg.Ucmm… UDINT initialblank commentUnconnectedmessagetimeout.;A_TarCfg.ConnM… UDINT initial0 commentConnectedmessagetimeout.;A_TarCfg.ConnC… BOOL initialblank commentTRUE:CloseCIPconnectionupon…;A_ReqData USINTdimension[1..32];A_ReqLength UINTinitial32;A_ResData USINTdimension[1..81];A_Status CIPSTATUS;A_ResLength UINTinitialblank;CatalogID STRINGdimension[1..1];R_CtrlCfg CIPCONTROL;R_AppCfg CIPAPPCFG;R_TarCfg CIPTARGETCF…;R_ReqData USINTdimension[1..64];R_ReqLength UINTinitial64;R_ResData USINTdimension[1..81]. Alias/otherindividualvaluecellsblank;collapsedstructcellsdisplayellipses. Severalnames/types/commentsclipped atsourcecolumnboundary:preserveshownprefixes,notguessedfullidentifier. Ready,INS,2020/7/16,下午01:52. Nativeprose supplies192.168.22.2alone butactualpathincludes4, prefix.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Truncated variable names, types and comments; ellipsized labels.
Manual — JN5-CMHI-EIP localvariables andbuildproject example — page 623
Manual reference: physical PDF page 623. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Truncated variable names and comments, clipped output line and tiny PLC picture.
Set the “Connected Components Workbench” communication software. Open the “Connected Components Workbench” communication software as shown in the figure below, select the connected device and select “Local Variables.” Confirm that the IP DHCP assigned to the expansion card is 192.168.22.2 for A_TarCfg.Path.
Select “Build Project”
CCWprojectEIP_Assembly_100_2_vsd;Disconnected;Run-VAR,Micro820,StartPage;LocalVariablesselected. TablecolumnsName,Alias,DataType,Dimension,ProjectValue,InitialValue,Comment. VisibleRows:MSG_CIPGENERIC_1 typeMSG_CIPGEN…;SetSpeed_vsd1 BOOL;A_CtrlCfg CIPCONTROL;A_AppCfg CIPAPPCFG;A_TarCfg CIPTARGETCF…;A_TarCfg.Path STRING initialvalue'4,192.168.22.2' commentCIPdestinationpath;A_TarCfg.CipCo… USINT initial1 comment0-Unconnected,1-Class3conn…;A_TarCfg.Ucmm… UDINT initialblank commentUnconnectedmessagetimeout.;A_TarCfg.ConnM… UDINT initial0 commentConnectedmessagetimeout.;A_TarCfg.ConnC… BOOL initialblank commentTRUE:CloseCIPconnectionupon…;A_ReqData USINTdimension[1..32];A_ReqLength UINTinitial32;A_ResData USINTdimension[1..81];A_Status CIPSTATUS;A_ResLength UINTinitialblank;CatalogID STRINGdimension[1..1];R_CtrlCfg CIPCONTROL;R_AppCfg CIPAPPCFG;R_TarCfg CIPTARGETCF…;R_ReqData USINTdimension[1..64];R_ReqLength UINTinitial64;R_ResData USINTdimension[1..81]. Alias/otherindividualvaluecellsblank;collapsedstructcellsdisplayellipses. Severalnames/types/commentsclipped atsourcecolumnboundary:preserveshownprefixes,notguessedfullidentifier. Ready,INS,2020/7/16,下午01:52. Nativeprose supplies192.168.22.2alone butactualpathincludes4, prefix.RedcalloutatRun/LocalVariables;noequivalenceassumed toanotherprojectstate.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Disconnected. RedcalloutaroundTheme;pointeronbuildicon. NativeprosesaysSelectBuildProject. OutputShowoutputfromBuild;Micro820:0error(s),0warning(s);BuildEnd;BuildTime14.3seconds;Build:1succeeded,0failed,0up-to-date,0skipped. Upperoutputlineandlowercontrollerpaneclipped;not reconstructed. Screenshotproofis historicalsupplierexample,not a buildrunhere.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Truncated variable names and comments, clipped output line and tiny PLC picture.
Manual — JN5-CMHI-EIP PLC download confirmation examples — page 624
Manual reference: physical PDF page 624. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny PLC illustration labels, ellipsized path and covered background.
Press the “Download” button to complete the USB to PLC setting.
The download will execute the connection between the communication card and PLC automatically, as shown in the figure below.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Connected/Downloading. DownloadConfirmationwarning:Theprojectinthecontrollerwillbeoverwrittenwithcurrentprojectcontent.ControllerwillbeswitchedtoProgramModetoperformtheoperation. OptionsDownload,DownloadwithProjectValues;Help,Cancel. OutputBuildprojectCONTROLLER;BuildresourceMicro820 ConfigurationMicro820;Theprojectbuilduptodate;Build0succeeded,0failed,1up-to-date,0skipped. Connectionpathandtinydeviceillustrationnotfullyreadable;imagepreserved.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. DownloadConfirmation:Downloadiscomplete.ChangethecontrollertoRemoteRuntoexecutecontrollerproject? Buttons是(Y),否(N). BackgroundMemoryCardisnotpresent;Diagnose;MemoryCardSettings;Loadonpower-upDisabled;IncludeProject&LogicalvaluesuponBackup/Restoreunchecked;RemoteLCDnavigation. Coveredbackground/ellipsizedpathnotreconstructed.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny PLC illustration labels, ellipsized path and covered background.
Manual — JN5-CMHI-EIP running example andinputassemblymapping — page 625
Manual reference: physical PDF page 625. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny PLC illustration labels, ellipsized path and clipped lower ladder block.
11.16.4 Running The connected A510s/F510 communication card (Ethernet/IP), as shown in the figure below. Confirm that Remote Run is enabled.
As shown in the figure below, select and open “RUN_POU.”
Load A_ReqData and check whether the Input Assembly content was written.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Connected;greenindicatorbesideRemoteRun,Run/Programswitch;Disconnect. Controller-MemoryCard:MemoryCardisnotpresent. OutputShowoutputfromGeneralempty. Tinydevicepictureandellipsizedpathunresolved.
CCWRun-POU screenshot;Connected;File,Edit,View,Device,Format,Tools,Communications,Window,Help. Sourcecomment:ThisSampleCodeshowshowtouseMSG_CIPGENERICinstructiontoreadthecontroller’scatalognumberinthesamesubnetnetwork. Rung1labelSetSpeed_vsd1;functionMSG_CIPGENERIC_1/MSG_CIPGENERIC;portsIN,Q,CtrlCfg,AppCfg,TargetCfg,ReqData,ReqLength,ResData,Status,ResLength. ShownA_CtrlCfgFalse;A_AppCfg16;A_TarCfg4,192.168.22.2;A_ReqData0;A_ReqLength32;A_ResData0;A_StatusFalse;A_ResLength0. Rung2partiallyshownMSG_CIPGENERIC_2/MSG_CIPGENERIC;R_CtrlCfgFalse;R_StatusFalse;remaininglowerparametersclipped. Preservevisiblelabels,not inferredladderlogic.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny PLC illustration labels, ellipsized path and clipped lower ladder block.
JN5-CMHI-EIP running example andinputassemblymapping
PLC command location / MODBUS register location / Description — PDF page 625
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | PLC command location | MODBUS register location | Description |
| 2 | A_ReqData[1] | 2501 Low Byte | RUN/STOP FWD/REV |
| 3 | A_ReqData[2] | 2501 High Byte | RUN/STOP FWD/REV |
| 4 | A_ReqData[3] | 2502 Low Byte | Frequency command |
| 5 | A_ReqData[4] | 2502 High Byte | Frequency command |
Manual — JN5-CMHI-EIP variablemonitor andoutputassemblymapping — page 626
Manual reference: physical PDF page 626. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Clipped logical-value digits in variable monitor.
Load R_ResData and check whether the Output Assembly content was read.
VariableMonitoringtabsUserGlobalVariables-Micro820,LocalVariables-Run,SystemVariables-Micro820,I/O-Micro820,DefinedWords. ColumnsName,Alias,LogicalValue,PhysicalValue,InitialValue,Lock,DataType. A_ReqDataUSINTexpandedrows[1]–[16],allPhysicalValueN/AandDataTypeUSINT,locksunchecked. Initialvalues:[1]0,[3]112,[4]23,otherdisplayedrowsblank. Logicalvalues[1]/[2]notvisible;[3]visible12and[4]visible3haveleftsideclipped;do notinfer112/23frominitialvalues. [5]–[16]logical0. Aliasesblank. Redrectanglepartlycoverslabel[5]. Closebutton. Pagepartialforhiddenlogicaldigits.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Clipped logical-value digits in variable monitor.
JN5-CMHI-EIP variablemonitor andoutputassemblymapping
PLC command location / MODBUS register location / Description — PDF page 626
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | PLC command location | MODBUS register location | Description |
| 2 | R_ResData[1] | 2520 Low Byte | Motor drive status |
| 3 | R_ResData[2] | 2520 High Byte | Motor drive status |
| 4 | R_ResData[3] | 2521 Low Byte | Error description |
| 5 | R_ResData[4] | 2521 High Byte | Error description |
| 6 | R_ResData[5] | 2522 Low Byte | DI status |
| 7 | R_ResData[6] | 2522 High Byte | DI status |
| 8 | R_ResData[7] | 2523 Low Byte | Frequency command |
| 9 | R_ResData[8] | 2523 High Byte | Frequency command |
| 10 | R_ResData[9] | 2524 Low Byte | Output frequency |
| 11 | R_ResData[10] | 2524 High Byte | Output frequency |
Manual — JN5-CMHI-EIP outputvariables andMolexidentity readexample — page 627
Manual reference: physical PDF page 627. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Logical-value digits obscured by source red outline.
Execute Molex Ethernet/IP Tool and send the UCMM read command (Get Attribute) to the A510s/F510 communication card (Ethernet/IP); the response that can be received from the communication card is as shown in the figure below.
The run command sent to the motor drive written with the PLC command is as follows Commands can be sent to the motor drive through PLC from the following switch
VariableMonitoringtabsUserGlobalVariables-Micro820,LocalVariables-Run,SystemVariables-Micro820,I/O-Micro820,DefinedWords. ColumnsName,Alias,LogicalValue,PhysicalValue,InitialValue,Lock,DataType. R_ResDataUSINTexpanded[1]–[16];PhysicalValueN/AandDataTypeUSINTallrows;aliases/initialvaluesblank;locksunchecked. Visiblelogical[1]3,[2]4,[3]0,[4]0,[5]0,[6]0,[7]1…2 withmiddledigitobscuredbyredoutline,[8]2,[9]0,[10]0,[11]0,[12]0,[13]0,[14]0,[15]0,[16]0. Redoutlinecrossesvalues;do notinferobscuredadditionaldigits. Close.
MolexEtherNet/IPToolsfromMolexInc.isprovidedfreeofchargetoODVA sourceexample. Station192.168.22.2;UCMMselected,Connected/Unconnected_sendunselected;Options,About,ViewLog;Statusok. TabsListIdentity,ExplicitMessage,Class,0x01Identity,0x06ConnectionManager,0x47DLR,0x48QoS,0xF5TCP/IP,0xF6EthernetLink. Instance1;Get_Attribute_All;ResetServiceParameter0,Reset. VendorID(attr1)283;DeviceType(attr2)2;ProductCode(attr3)2;Revision(attr4)Major1,Minor1;ProductName(attr7)JN5-CM-EIP. Status(attr5)Configuredchecked;Owned,MinorRecoverableFault,MinorUnrecoverableFault,MajorRecoverableFault,MajorUnrecoverableFaultunchecked;value0x0034(52). ExtendedDeviceStatusvalue0x3(3);NoI/Oconnectionsestablishedselected;otheroptionsSelf-TestingorUnknown,FirmwareUpdateinProgress,AtleastonefaultedI/Oconnection,Non-VolatileConfigurationbad,MajorFault,AtleastoneI/OconnectioninRunmode,AtleastoneI/Oconnectionestablished,allinidlemode. State(attr8)Operationalchecked;Nonexistent,DeviceSelfTesting,Standby,MajorRecoverableFault,MajorUnrecoverableFault,Reserved,DefaultforGetAttributesAllunselected;0x03(3). SerialNumber(attr6)0-0x00000000. ModbusIdentityInfo(attr10)VendorName,ProductCode,MajorMinorVersion,VendorUrl,ProductName,ModelName,UserAppNameempty. Get_Attribute buttons repeat. Lowresolutionimage/OCRdifferencesretained;noinferenceofactualmoduleidentityorreadsuccess.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Logical-value digits obscured by source red outline.
JN5-CMHI-EIP outputvariables andMolexidentity readexample
Class / Instance / Attribute / Name / Default Value / R/W / Size — PDF page 627
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Class | Instance | Attribute | Name | Default Value | R/W | Size |
| 2 | 0x01 | 1 | 1 | Vendor ID | 283 | R | U32 |
| 3 | 0x01 | 1 | 2 | Device Type | 2 | R | U32 |
| 4 | 0x01 | 1 | 3 | Product code | 2 | R | U32 |
| 5 | 0x01 | 1 | 4 | Major Revision | 1 | R | U32 |
| 6 | 0x01 | 1 | 5 | Minor Revision | 1 | R | U32 |
Manual — JN5-CMHI-EIP runcommands,ladderlabels andexplicitservices — page 628
Manual reference: physical PDF page 628. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Clipped previous ladder block and bottom rung edges.
A_ReqData[1] motor drive operation signal (2501H)
follows
CCWRun-POUladderexample:Connected. VisibleprecedingblockS_TarCfg4,192.168.22.3,TargetCfg;S_ReqData0,ReqData;S_ReqLength64,ReqLength;S_ResData36,ResData. Rung7Start_forward_vsd1withA_ReqData[1].0;8Start_forward_vsd2withB_ReqData[1].0;9Start_Reverse_vsd1withA_ReqData[1].1;10Start_Reverse_vsd2withB_ReqData[1].1;11Fault_Reset_vsd1withA_ReqData[1].3;12Fault_Reset_vsd2withB_ReqData[1].3. Upperpreviousblock andbottomrungedgesclipped;no missinglogic reconstructed. ScreenshotusesS_...path.3 distinctfromA_...path.2elsewhere.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Clipped previous ladder block and bottom rung edges.
JN5-CMHI-EIP runcommands,ladderlabels andexplicitservices
PLC command location / Function / Description — PDF page 628
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | PLC command location | Function | Description |
| 2 | A_ReqData[1].0 | Operation status | 1 : RUN 0 : STOP |
| 3 | A_ReqData[1].1 | Direction status | 1 : REV 0 : FWD |
| 4 | A_ReqData[1].2 | External error | 1:EF0 |
| 5 | A_ReqData[1].3 | Error reset | 1 : RESET |
Service Code No. / Service Name — PDF page 628
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Service Code No. | Service Name |
| 2 | 0E(HEX) | Get Attribute Single |
| 3 | 10(HEX) | Set Attribute Single |
Class(HEX) / 2A / 29 — PDF page 628
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Class(HEX) | 2A | 29 | 29 |
| 2 | Instance(HEX) | 1 | 1 | 1 |
| 3 | Attribute(HEX) | 8 | 3 | 3 |
| 4 | Write data(HEX) | 0~70 17 | 0~1 | 0~3 |
| 5 | Corresponding command | SPEED REFERENCE | 1:RUN FORWARD 0: STOP | 1:REVERSE RUN 0: STOP |
| 6 | Inverter action | Panel frequency 60Hz | Forward rotation | Reversed rotation |
Manual — JN5-CM-EIP separateexternalmodule preparation/installation — page 629
Manual reference: physical PDF page 629. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny photographed module housing inscriptions unresolved.
11.17 JN5-CM-EIP Manual
Heading only transcribed to qualify downstream screenshot; all other content remains pending semantic review.
11.17.1 Preparations before using the instrument 510 series inverter *1
IBM PC or compatible computer (with the following related software installed) *1
BOOTP-DHCP Tool (Rockwell IP setting software)
RSlinx Classic (Rockwell communication software)
Connected Components Workbench (Rockwell PLC software)
Molex Ethernet/IP Tool (Ethernet IP setting software)
Ethernet/IP Programmable Logic Controller (EX: Micro820) *1
CAT5e Ethernet cable *3
DC Power supply *1 11.17.2 Installation of a semi-finished product Connected the power terminal of the module to the DC power supply.
Open the top cover of the inverter, and connect the CN1 of the communication
module to the RJ45 communication port of the inverter by CAT5e cable.
510 inverter parameter settings
Note: CN1 position
JN5-CM-EIPmodulephotograph labelledbyadjacentnativeNote:CN1position. RJ45-styleopening visible;no dimensions/pinoutorunreadabletinyhousingmarkingsinferred.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny photographed module housing inscriptions unresolved.
JN5-CM-EIP separateexternalmodule preparation/installation
Run command / Communication method / 00-02=2 — PDF page 629
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Run command | Communication method | 00-02=2 |
| 2 | Frequency command | Communication method | 00-05=5 |
| 3 | Acceleration time | 10.0s | 00-14=100 |
| 4 | Deceleration time | 10.0s | 00-15=100 |
Manual — JN5-CM-EIP externalmodule PCnetwork example — page 630
Manual reference: physical PDF page 630. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Loopback address truncated in source screenshot.
11.17.3 Connection steps Connect with the PC network and set the IP (as shown in the figure below, set the PC network card IP).
Execute the Rockwell BOOTP-DHCP Tool and select the PC network card
Windows dialog 網際網路通訊協定第4版(TCP/IPv4)-內容;一般. Text:如果您的網路支援這項功能,您可以取得自動指派的IP設定。否則,您必須詢問網路系統管理員正確的IP設定。自動取得IP位址(O)unselected;使用下列的IP位址(S)selected;IP位址(I)192.168.22.1;子網路遮罩(U)255.255.255.0;預設閘道(D)blank. 自動取得DNS伺服器位址(B)unselected;使用下列的DNS伺服器位址(E)selected;慣用DNS伺服器(P)192.168.22.1;其他DNS伺服器(A)blank. 結束時確認設定(L)unchecked;進階(V)...,確定,取消. These are source example values,not applied settings.
Select Network Interface;Please select a network interface;columnsDescription/IPAddress. Npcap Loopback Adapter→169.254.223…(source ellipsis;remainingaddressunknown);Intel(R)WiFi Link5100AGN→10.101.24.35;selectedBroadcom NetXtreme Gigabit Ethernet→192.168.22.1;OK. No complete address inferred fromtruncatedloopbackrow.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Loopback address truncated in source screenshot.
Manual — JN5-CM-EIP externalmodule DHCPassignment example — page 631
Manual reference: physical PDF page 631. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
The Rockwell BOOTP-DHCP Tool scans the MAC Address of the communication module, then select ADD RELATION and set the CLIENT IP ADDRESS to 192.168.22.2
Set and confirm the IP status (using Micro820 as the example) of the 510 communication module (Ethernet/IP).
BootP DHCP EtherNet/IP Commissioning Tool;File,Tools,Help;AddRelation,ClearHistory. DiscoveryHistorycolumnsEthernetAddress(MAC),Type,[hr:min:sec],#,IPAddress,Hostname;EnteredRelationscolumnsEthernetAddress(MAC),Type,IPAddress,Hostname,Description;Errorsandwarnings;Relations. Discoveryrow00:02:A2:58:5A:86,DHCP,14:56:49,1,IPblank,Hostnameblank. EnteredRelationsempty. MessageUnable to service DHCP request from00:02:A2:58:5A:86. Relations0of256.
BootP DHCP EtherNet/IP Commissioning Tool;File,Tools,Help;AddRelation,ClearHistory. DiscoveryHistorycolumnsEthernetAddress(MAC),Type,[hr:min:sec],#,IPAddress,Hostname;EnteredRelationscolumnsEthernetAddress(MAC),Type,IPAddress,Hostname,Description;Errorsandwarnings;Relations. NewEntrydialog:ServerIPAddress192.168.22.1;ClientAddress(MAC)00:02:A2:58:5A:86;ClientIPAddress192.168.22.2;Hostnameblank;Descriptionblank;OK,Cancel. Backgroundremainingrowobscuredbydialog;not reconstructed. ErrorUnable to service DHCP request from00:02:A2:58:5A:86;Relations0of256.
BootP DHCP EtherNet/IP Commissioning Tool;File,Tools,Help;AddRelation,ClearHistory. DiscoveryHistorycolumnsEthernetAddress(MAC),Type,[hr:min:sec],#,IPAddress,Hostname;EnteredRelationscolumnsEthernetAddress(MAC),Type,IPAddress,Hostname,Description;Errorsandwarnings;Relations. Discoveryrow00:02:A2:58:5A:86,DHCP,15:05:49,11,192.168.22.2,Hostnameblank. EnteredRelationsrow00:02:A2:58:5A:86,DHCP,192.168.22.2,Hostnameblank,Descriptionblank. StatusSent192.168.22.2toEthernetaddress00:02:A2:58:5A:86;Relations1of256. Sourceexampleonly.
Manual — JN5-CM-EIP externalmodule CCW/RSLinxconfiguration — page 632
Manual reference: physical PDF page 632. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny PLC illustration labels and ellipsized connection path.
Execute Connected Components Workbench, open a Project file and set the Micro800 PLC address (192.168.22.4) and subnet mask (255.255.255.0); they do not need to be changed again after the setting is completed
Check whether the network connection is successful, as shown in the figure below. Execute RSlinx Classic Lite and execute Configure Drivers.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Disconnected;Connect. Controller-Ethernet:ObtainIPaddressautomaticallyusingDHCPunselected;ConfigureIPaddressandsettingsselected;IPAddress192.168.22.4;SubnetMask255.255.255.0. NavigationGeneral,Memory,Startup/Faults,SerialPort,Ethernet,Interrupts,ModbusMapping,RealTimeClock,EmbeddedI/O,MemoryCard. TinyPLCpictureinscriptions andellipsizedconnectionpath notfullyrecoverable;preserveimagewithpartialscope.
RSLinx Classic Lite-[RSWho-1];File,View,Communications,Station,DDE/OPC,Security,Window,Help;Autobrowsechecked. CommunicationsmenuRSWho,ConfigureDrivers...(selected),ConfigureShortcuts...,ConfigureClientApplications...,ConfigureCIPOptions...,DriverDiagnostics...,CIPDiagnostics.... StatusConfigurecommunicationhardware;NUM;07/16/20;10:12AM. Backgroundtreecovered bymenu;no hiddenitem reconstructed.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny PLC illustration labels and ellipsized connection path.
Manual — EtherNet/IP driver configuration screenshot — page 633
Manual reference: physical PDF page 633. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Select Ethernet/IP Driver, Add new, and select the IP of the PC network card
Screenshot example values only; IPs are examplePCadapteraddresses, not mandatory drive orPLCdefaults. Both page associations retained even where screenshot content repeats.
Configuration-dialog labels and adapter table transcribed; incidental desktop/menu/status-bar text remains original-only.
Labels show manual example workflow; no live software operation performed.
First two headers physical; selection-state column is editorial description of highlight. IPs are source examples, not site configuration.
Configuration-dialog labels — PDF page 633
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Available Driver Types | EtherNet/IP Driver |
| 2 | Action button | Add New... |
| 3 | Configure driver | AB_ETHIP-1 |
| 4 | Settings tab | EtherNet/IP Settings |
| 5 | Selected radio option | Browse Local Subnet |
| 6 | Other radio option | Browse Remote Subnet |
Example network-adapter choices — PDF page 633
| Source row | Description | IP Address | Source selection state |
|---|---|---|---|
| 1 | Windows Default | [blank in source] | Not highlighted |
| 2 | Npcap Loopback Adapter | 169.254.223.52 | Not highlighted |
| 3 | Broadcom NetXtreme Gigabit Ethernet | 192.168.22.1 | Highlighted |
Manual — JN5-CM-EIP external module discovery and variables — page 634
Manual reference: physical PDF page 634. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Truncated variable names/types/comments and ellipsized labels.
Expand AB_ETHIP-1, the PLC (192.168.22.4) and the communication module (192.168.22.2) can be seen.
Open the CCW project file and confirm that the IP DHCP is assigned to the expansion card for Local Variables -> A_TarCfg.Path is 192.168.22.2.
RSLinx Classic Lite-[RSWho-1];menusFile,View,Communications,Station,DDE/OPC,Security,Window,Help;Autobrowsechecked,Refresh,NotBrowsing. TreeWorkstationWG-CHRISN98-W77;LinxGateways,Ethernet;AB_ETHIP-1,Ethernet;192.168.22.2,UnrecognizedDevice,JN5-CM-EIP;192.168.22.4,Micro820,2080-LC20-20QWBselected. RighticonsBackplaneMicro80… andChannel2DF1;statusForHelp,pressF1;NUM;07/28/20;03:45PM. DeviceidentitysourceisJN5-CM-EIP despite sectionJN5-CMHI-EIP;do not substitute. This page belongs to separate external JN5-CM-EIP section; repeated image payload does not prove hardware equivalence.
CCWprojectEIP_Assembly_100_2_vsd;Disconnected;Run-VAR,Micro820,StartPage;LocalVariablesselected. TablecolumnsName,Alias,DataType,Dimension,ProjectValue,InitialValue,Comment. VisibleRows:MSG_CIPGENERIC_1 typeMSG_CIPGEN…;SetSpeed_vsd1 BOOL;A_CtrlCfg CIPCONTROL;A_AppCfg CIPAPPCFG;A_TarCfg CIPTARGETCF…;A_TarCfg.Path STRING initialvalue'4,192.168.22.2' commentCIPdestinationpath;A_TarCfg.CipCo… USINT initial1 comment0-Unconnected,1-Class3conn…;A_TarCfg.Ucmm… UDINT initialblank commentUnconnectedmessagetimeout.;A_TarCfg.ConnM… UDINT initial0 commentConnectedmessagetimeout.;A_TarCfg.ConnC… BOOL initialblank commentTRUE:CloseCIPconnectionupon…;A_ReqData USINTdimension[1..32];A_ReqLength UINTinitial32;A_ResData USINTdimension[1..81];A_Status CIPSTATUS;A_ResLength UINTinitialblank;CatalogID STRINGdimension[1..1];R_CtrlCfg CIPCONTROL;R_AppCfg CIPAPPCFG;R_TarCfg CIPTARGETCF…;R_ReqData USINTdimension[1..64];R_ReqLength UINTinitial64;R_ResData USINTdimension[1..81]. Alias/otherindividualvaluecellsblank;collapsedstructcellsdisplayellipses. Severalnames/types/commentsclipped atsourcecolumnboundary:preserveshownprefixes,notguessedfullidentifier. Ready,INS,2020/7/16,下午01:52. Nativeprose supplies192.168.22.2alone butactualpathincludes4, prefix. This page belongs to separate external JN5-CM-EIP section; repeated image payload does not prove hardware equivalence.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Truncated variable names/types/comments and ellipsized labels.
Manual — JN5-CM-EIP variable selection and build example — page 635
Manual reference: physical PDF page 635. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Clipped variable names/comments, upper output line and tiny PLC picture inscriptions.
Set the “Connected Components Workbench” communication software. Open the “Connected Components Workbench” communication software as shown in the figure below, select the connected device and select “Local Variables.” Confirm that the IP DHCP assigned to the expansion card is 192.168.22.2 for A_TarCfg.Path.
Select “Build Project”
CCWprojectEIP_Assembly_100_2_vsd;Disconnected;Run-VAR,Micro820,StartPage;LocalVariablesselected. TablecolumnsName,Alias,DataType,Dimension,ProjectValue,InitialValue,Comment. VisibleRows:MSG_CIPGENERIC_1 typeMSG_CIPGEN…;SetSpeed_vsd1 BOOL;A_CtrlCfg CIPCONTROL;A_AppCfg CIPAPPCFG;A_TarCfg CIPTARGETCF…;A_TarCfg.Path STRING initialvalue'4,192.168.22.2' commentCIPdestinationpath;A_TarCfg.CipCo… USINT initial1 comment0-Unconnected,1-Class3conn…;A_TarCfg.Ucmm… UDINT initialblank commentUnconnectedmessagetimeout.;A_TarCfg.ConnM… UDINT initial0 commentConnectedmessagetimeout.;A_TarCfg.ConnC… BOOL initialblank commentTRUE:CloseCIPconnectionupon…;A_ReqData USINTdimension[1..32];A_ReqLength UINTinitial32;A_ResData USINTdimension[1..81];A_Status CIPSTATUS;A_ResLength UINTinitialblank;CatalogID STRINGdimension[1..1];R_CtrlCfg CIPCONTROL;R_AppCfg CIPAPPCFG;R_TarCfg CIPTARGETCF…;R_ReqData USINTdimension[1..64];R_ReqLength UINTinitial64;R_ResData USINTdimension[1..81]. Alias/otherindividualvaluecellsblank;collapsedstructcellsdisplayellipses. Severalnames/types/commentsclipped atsourcecolumnboundary:preserveshownprefixes,notguessedfullidentifier. Ready,INS,2020/7/16,下午01:52. Nativeprose supplies192.168.22.2alone butactualpathincludes4, prefix.RedcalloutatRun/LocalVariables;noequivalenceassumed toanotherprojectstate. This page belongs to separate external JN5-CM-EIP section; repeated image payload does not prove hardware equivalence.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Disconnected. RedcalloutaroundTheme;pointeronbuildicon. NativeprosesaysSelectBuildProject. OutputShowoutputfromBuild;Micro820:0error(s),0warning(s);BuildEnd;BuildTime14.3seconds;Build:1succeeded,0failed,0up-to-date,0skipped. Upperoutputlineandlowercontrollerpaneclipped;not reconstructed. Screenshotproofis historicalsupplierexample,not a buildrunhere. This page belongs to separate external JN5-CM-EIP section; repeated image payload does not prove hardware equivalence.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Clipped variable names/comments, upper output line and tiny PLC picture inscriptions.
Manual — JN5-CM-EIP PC to PLC download example — page 636
Manual reference: physical PDF page 636. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny PLC picture and ellipsized connection path; covered background.
Press the “Download” button to complete the PC to PLC setting.
After download, it will execute the connection between the communication module and PLC automatically, as shown in the figure below.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Connected/Downloading. DownloadConfirmationwarning:Theprojectinthecontrollerwillbeoverwrittenwithcurrentprojectcontent.ControllerwillbeswitchedtoProgramModetoperformtheoperation. OptionsDownload,DownloadwithProjectValues;Help,Cancel. OutputBuildprojectCONTROLLER;BuildresourceMicro820 ConfigurationMicro820;Theprojectbuilduptodate;Build0succeeded,0failed,1up-to-date,0skipped. Connectionpathandtinydeviceillustrationnotfullyreadable;imagepreserved.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. DownloadConfirmation:Downloadiscomplete.ChangethecontrollertoRemoteRuntoexecutecontrollerproject? Buttons是(Y),否(N). BackgroundMemoryCardisnotpresent;Diagnose;MemoryCardSettings;Loadonpower-upDisabled;IncludeProject&LogicalvaluesuponBackup/Restoreunchecked;RemoteLCDnavigation. Coveredbackground/ellipsizedpathnotreconstructed.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny PLC picture and ellipsized connection path; covered background.
Manual — JN5-CM-EIP running example and input assembly addresses — page 637
Manual reference: physical PDF page 637. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny PLC picture/path and clipped lower ladder block.
11.17.4 Running The connected 510 communication module (Ethernet/IP), as shown in the figure below. Confirm that Remote Run is enabled.
As shown in the figure below, select and open “RUN_POU.”
Load A_ReqData and check whether the Input Assembly content was written.
Connected Components Workbench Standard Edition;projectEIP_Assembly_100_2_vsd_Copy_1;menusFile,Edit,View,Device,Tools,Communications,Window,Help;ThemeDefault;ProjectOrganizer:Micro820,Programs,Run,LocalVariables,GlobalVariables,UDFB(User-DefinedFunction...),User-DefinedFunctions,DataTypes;tabsRun-POU,Micro820,StartPage;Download,Upload,Diagnose,Secure,Help;PropertiesDevice:Micro820,Info,Comment,Description,NameMicro820. Connected;greenindicatorbesideRemoteRun,Run/Programswitch;Disconnect. Controller-MemoryCard:MemoryCardisnotpresent. OutputShowoutputfromGeneralempty. Tinydevicepictureandellipsizedpathunresolved.
CCWRun-POU screenshot;Connected;File,Edit,View,Device,Format,Tools,Communications,Window,Help. Sourcecomment:ThisSampleCodeshowshowtouseMSG_CIPGENERICinstructiontoreadthecontroller’scatalognumberinthesamesubnetnetwork. Rung1labelSetSpeed_vsd1;functionMSG_CIPGENERIC_1/MSG_CIPGENERIC;portsIN,Q,CtrlCfg,AppCfg,TargetCfg,ReqData,ReqLength,ResData,Status,ResLength. ShownA_CtrlCfgFalse;A_AppCfg16;A_TarCfg4,192.168.22.2;A_ReqData0;A_ReqLength32;A_ResData0;A_StatusFalse;A_ResLength0. Rung2partiallyshownMSG_CIPGENERIC_2/MSG_CIPGENERIC;R_CtrlCfgFalse;R_StatusFalse;remaininglowerparametersclipped. Preservevisiblelabels,not inferredladderlogic.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny PLC picture/path and clipped lower ladder block.
JN5-CM-EIP running example and input assembly addresses
PLC command address / MODBUS register address / Description — PDF page 637
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | PLC command address | MODBUS register address | Description |
| 2 | A_ReqData[1] | 2501 Low Byte | RUN/STOP FWD/REV |
| 3 | A_ReqData[2] | 2501 High Byte | RUN/STOP FWD/REV |
| 4 | A_ReqData[3] | 2502 Low Byte | Frequency command |
| 5 | A_ReqData[4] | 2502 High Byte | Frequency command |
Manual — JN5-CM-EIP readable input monitor and output assembly addresses — page 638
Manual reference: physical PDF page 638. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Red source outline covers portions of variable names; numeric values are readable on this page.
Load R_ResData and check whether the Output Assembly content was read.
VariableMonitoringtabsUserGlobalVariables-Micro820,LocalVariables-Run,SystemVariables-Micro820,I/O-Micro820,DefinedWords. ColumnsName,Alias,LogicalValue,PhysicalValue,InitialValue,Lock,DataType. A_ReqDataUSINTexpandedrows[1]–[16],allPhysicalValueN/AandDataTypeUSINT,locksunchecked. Initialvalues:[1]0,[3]112,[4]23,otherdisplayedrowsblank. Logical values [1]=0,[2]=0,[3]=112,[4]=23,[5]–[16]=0 are visible on this page. Aliasesblank. Red rectangle overlaps parts of names on rows1–4; values are outside the rectangle and legible. Close button. Name fragments beneath the source outline remain partial.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Red source outline covers portions of variable names; numeric values are readable on this page.
JN5-CM-EIP readable input monitor and output assembly addresses
PLC command address / MODBUS register address / Description — PDF page 638
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | PLC command address | MODBUS register address | Description |
| 2 | R_ResData[1] | 2520 Low Byte | Inverter status |
| 3 | R_ResData[2] | 2520 High Byte | Inverter status |
| 4 | R_ResData[3] | 2521 Low Byte | Error description |
| 5 | R_ResData[4] | 2521 High Byte | Error description |
| 6 | R_ResData[5] | 2522 Low Byte | DI status |
| 7 | R_ResData[6] | 2522 High Byte | DI status |
| 8 | R_ResData[7] | 2523 Low Byte | Frequency command |
| 9 | R_ResData[8] | 2523 High Byte | Frequency command |
| 10 | R_ResData[9] | 2524 Low Byte | Output frequency |
| 11 | R_ResData[10] | 2524 High Byte | Output frequency |
Manual — JN5-CM-EIP output monitor and identity read — page 639
Manual reference: physical PDF page 639. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Source red outline obscures output monitor logical digits.
Execute Molex Ethernet/IP Tool and send the UCMM read command (Get Attribute) to the 510 communication module (Ethernet/IP); the response that can be received from the communication module is as shown in the figure below.
The run command sent to the inverter written with the PLC command is as follows
VariableMonitoringtabsUserGlobalVariables-Micro820,LocalVariables-Run,SystemVariables-Micro820,I/O-Micro820,DefinedWords. ColumnsName,Alias,LogicalValue,PhysicalValue,InitialValue,Lock,DataType. R_ResDataUSINTexpanded[1]–[16];PhysicalValueN/AandDataTypeUSINTallrows;aliases/initialvaluesblank;locksunchecked. Visiblelogical[1]3,[2]4,[3]0,[4]0,[5]0,[6]0,[7]1…2 withmiddledigitobscuredbyredoutline,[8]2,[9]0,[10]0,[11]0,[12]0,[13]0,[14]0,[15]0,[16]0. Redoutlinecrossesvalues;do notinferobscuredadditionaldigits. Close.
MolexEtherNet/IPToolsfromMolexInc.isprovidedfreeofchargetoODVA sourceexample. Station192.168.22.2;UCMMselected,Connected/Unconnected_sendunselected;Options,About,ViewLog;Statusok. TabsListIdentity,ExplicitMessage,Class,0x01Identity,0x06ConnectionManager,0x47DLR,0x48QoS,0xF5TCP/IP,0xF6EthernetLink. Instance1;Get_Attribute_All;ResetServiceParameter0,Reset. VendorID(attr1)283;DeviceType(attr2)2;ProductCode(attr3)2;Revision(attr4)Major1,Minor1;ProductName(attr7)JN5-CM-EIP. Status(attr5)Configuredchecked;Owned,MinorRecoverableFault,MinorUnrecoverableFault,MajorRecoverableFault,MajorUnrecoverableFaultunchecked;value0x0034(52). ExtendedDeviceStatusvalue0x3(3);NoI/Oconnectionsestablishedselected;otheroptionsSelf-TestingorUnknown,FirmwareUpdateinProgress,AtleastonefaultedI/Oconnection,Non-VolatileConfigurationbad,MajorFault,AtleastoneI/OconnectioninRunmode,AtleastoneI/Oconnectionestablished,allinidlemode. State(attr8)Operationalchecked;Nonexistent,DeviceSelfTesting,Standby,MajorRecoverableFault,MajorUnrecoverableFault,Reserved,DefaultforGetAttributesAllunselected;0x03(3). SerialNumber(attr6)0-0x00000000. ModbusIdentityInfo(attr10)VendorName,ProductCode,MajorMinorVersion,VendorUrl,ProductName,ModelName,UserAppNameempty. Get_Attribute buttons repeat. Lowresolutionimage/OCRdifferencesretained;noinferenceofactualmoduleidentityorreadsuccess.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Source red outline obscures output monitor logical digits.
JN5-CM-EIP output monitor and identity read
Class / Instance / Attribute / Name / Default / R/W / Size — PDF page 639
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Class | Instance | Attribute | Name | Default | R/W | Size |
| 2 | 0x01 | 1 | 1 | Vendor ID | 283 | R | U32 |
| 3 | 0x01 | 1 | 2 | Device Type | 2 | R | U32 |
| 4 | 0x01 | 1 | 3 | Product code | 2 | R | U32 |
| 5 | 0x01 | 1 | 4 | Major Revision | 1 | R | U32 |
| 6 | 0x01 | 1 | 5 | Minor Revision | 1 | R | U32 |
Manual — JN5-CM-EIP PLC and explicit run commands — page 640
Manual reference: physical PDF page 640. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Clipped preceding ladder block and bottom rung edges.
Commands can be sent to the inverter through PLC from the following switch A_ReqData[1] inverter operation signal (2501H)
The run command sent to the inverter written with the Molex Ethernet/IP Tool is as follows
CCWRun-POUladderexample:Connected. VisibleprecedingblockS_TarCfg4,192.168.22.3,TargetCfg;S_ReqData0,ReqData;S_ReqLength64,ReqLength;S_ResData36,ResData. Rung7Start_forward_vsd1withA_ReqData[1].0;8Start_forward_vsd2withB_ReqData[1].0;9Start_Reverse_vsd1withA_ReqData[1].1;10Start_Reverse_vsd2withB_ReqData[1].1;11Fault_Reset_vsd1withA_ReqData[1].3;12Fault_Reset_vsd2withB_ReqData[1].3. Upperpreviousblock andbottomrungedgesclipped;no missinglogic reconstructed. ScreenshotusesS_...path.3 distinctfromA_...path.2elsewhere.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Clipped preceding ladder block and bottom rung edges.
JN5-CM-EIP PLC and explicit run commands
PLC command address / Function / Description — PDF page 640
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | PLC command address | Function | Description |
| 2 | A_ReqData[1].0 | Operation status | 1 : RUN 0 : STOP |
| 3 | A_ReqData[1].1 | Direction status | 1 : REV 0 : FWD |
| 4 | A_ReqData[1].2 | External error | 1:EF0 |
| 5 | A_ReqData[1].3 | Error reset | 1 : RESET |
Service Code No. / Service Name — PDF page 640
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Service Code No. | Service Name |
| 2 | 0E(HEX) | Get Attribute Single |
| 3 | 10(HEX) | Set Attribute Single |
Class(HEX) / 2A / 29 — PDF page 640
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) |
|---|---|---|---|---|
| 1 | Class(HEX) | 2A | 29 | 29 |
| 2 | Instance(HEX) | 1 | 1 | 1 |
| 3 | Attribute(HEX) | 8 | 3 | 4 |
| 4 | Write data(HEX) | 0~70 17 | 0~1 | 0~1 |
| 5 | Corresponding command | SPEED REFERENCE | 1:RUN FORWARD 0: STOP | 1:REVERSE RUN 0: STOP |
| 6 | Inverter action | Panel frequency 60Hz | Forward rotation | Reversed rotation |
Manual — Bluetooth LCD keypad JN5-OP-BTH prerequisites and enable procedure — page 641
Manual reference: physical PDF page 641. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
11.18 Bluetooth LCD KEYPAD (JN5-OP-BTH)
11.18.1 Preparations before using the instrument For A510s Enhanced & F510 Enhanced series inverter (C/B requires burning of Bluetooth LCD operator communication protocol)1 Bluetooth communication device (IOS system mobile phone or Android system mobile phone) 1 TECO “BT DriveLink” APP (Download from Apple APP Store or Google Play)
11.18.2 Connecting the Bluetooth APP with the motor drive Bluetooth LCD operator
Motor drive setting In order to ensure operational safety, the Bluetooth communication function is disabled by default; to enable the Bluetooth communication function, please set the motor drive to “09- 11 = 1 (On).” When the power is disconnected after that, Bluetooth communication mode can be selected for the motor drive. Press the LOC/REM button at the top-left to execute Bluetooth connection; when the following Bluetooth screen appears, Bluetooth APP connection can be used, as shown in the figure below:
To cancel Bluetooth communication, press the LOC/REM button at the top-left again to switch to the parameter page to perform operations to disable the Bluetooth function.
Keypad photo: REMOTE bracket; FAULT,FWD,REV,SEQ,REF; display Bluetooth Link... with Bluetooth symbol; Bluetooth word/logo; LOC/REM,up arrow,DSP/FUN,left arrow RESET,down arrow,READ/ENTER; green RUN and red STOP with pictograms. Source photo identifies interface labels; no electrical operating claim.
Manual — BLE DriveLink source login example and model selection — page 642
Manual reference: physical PDF page 642. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny icon keypad/product illustration markings and orange marketing CTA.
APP setting
Open the following APP (BLE DriveLink) from the Bluetooth communication device (IOS or Android mobile phone).
After executing the APP, the APP login screen will appear (as shown in the bottom-left figure); use the default account and password to log into the system. Default test account: demo@test.com Default password: 888888 The system will display as the bottom-right figure; perform selection according to the tester series.
Bluetooth connection setting process description The Bluetooth icon at the top-right will be displayed in gray before it’s connected (as
App icon: TECO, BLE DriveLink; tiny embedded keypad image markings unresolved.
TECO login screenshot; 中文; TECO BLE VFD Drivelink; demo@test.com; masked password dots; Login; Sign up; Forget ?. Source public demo account only; no actual login or credential validation.
TECO selection screenshot: LOOK FORWARD THINK GLOBAL; TECO High Technology Factory Automation System Solutions; orange tiny call-to-action and pictured machine/keypad markings not fully legible. A510s Enhanced type SELECT checked; F510 Pump & Fan Type SELECT checked. Preserve source labels rather than interpreting simultaneous applicability.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny icon keypad/product illustration markings and orange marketing CTA.
Manual — Bluetooth scan and station identity example — page 643
Manual reference: physical PDF page 643. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Bottom monitor row fragments clipped.
shown in the bottom-left figure).
After pressing this icon and then selecting Bluetooth Status, a screen matching the bottom-right figure will appear.
Press Bluetooth Scan on the screen in the right figure and TECO-BLE XX will appear (Note), confirming the device is online. After confirming the device to connect, press the device name at the center to start connecting. (Note) The last two digits of TECO-BLE XX is displayed according to the communication station parameter 09-00.
TECO menu with Connection status and Ble disconnection. REMOTE STATE chart Frequency(Hz),vertical0–100 by10,horizontal1,3,5,7,9,11,13,15,17,19,21,23,25; legendsFrequency andCurrent, traces shown alongzero. State -,Freq0.00(Hz),Current0.0(A); Name,Content,Value,Unit headers; lower table row clipped. Top Bluetooth icon gray; settings gear. No hidden background reconstructed.
TECO scanning dialog with close x,Bluetooth icon,Scanning,Please click the button below to start scanning for Ble devices; TECO_BLE04; RSSI:-64 | 34:81:F4:36:D5:6E; Ble Scan. Background State -,Freq0.00(Hz),Current0.0(A);Name,Content,Value,Unit; clipped2520H row. Source screenshot underscore TECO_BLE04 differs from prose TECO-BLE XX naming.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Bottom monitor row fragments clipped.
Manual — Bluetooth connection confirmation and register monitor — page 644
Manual reference: physical PDF page 644. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Bottom monitor row clipped and AO2 unit covered by settings gear.
Once the Bluetooth connection is successfully established, a prompt window as shown in the bottom-left figure will appear, meaning successfully connected. After pressing OK, scroll down the page and it can be seen that the value behind the parameter 2520H has started showing related communication data, meaning that the communication connection is successful.
TECO successful Bluetooth dialog:Successfully connected;You can start Bluetooth operation!;OK;close x. Visible Remote Dashboard,Frequency/Current chart legend;State -,Freq0.00(Hz),Current0.0(A);Name,Content,Value,Unit;bottom row clipped. Hidden chart labels not inferred.
TECO monitor screenshot:State -,Freq0.00(Hz),Current0.0(A). TableName/Content/Value/Unit; visible rows2520H Status unit-;2521H Fault unit-;2522H DI State unit-;2523H Freq command Hz;2524H Output freq Hz;2526H DC voltage V;2527H Output current A;2528H warning unit-;2529H DO State unit-;252AH AO1 V;252BH AO2 unit obscured by settings gear;252CH AI1 %. All visible Value cells blank; following row clipped. No2525H row shown,do not insert. Native prose says values behind2520H indicate communication; image has blank values.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Bottom monitor row clipped and AO2 unit covered by settings gear.
Manual — Bluetooth interface and operation control — page 645
Manual reference: physical PDF page 645. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Descriptions of basic APP functions Introduction to the interface
※ Setting icon:
To use Bluetooth to control the operation of the motor drive, the Main operation control command 00-02 parameter must be set as 2 (communication control). Press the “Setting icon” button and the control icons of the motor control will appear, including five motor drive operation control commands: Run / Stop / Forward /
Reverse / Reset. At this time, press Run Stop to perform operation control actions for the motor drive.
App interface annotated figure. Side Menu Icon:Function setting and return to real-time monitoring screen. Connection Icon:Make connection or disconnection;Gray:Disconnection;Blue:Connection. Real-time Monitoring:Monitor frequency and current status at the same time. Current:Instant current display. Setting Icon:Run,stop,forward,reverse and reset. Status:Display the status of the inverter is running or stopped. Frequency:1.Quickly set frequency;2.Real-time frequency display. TECO Remote Dashboard;REMOTE STATE chart Frequency(Hz),0–100 by10,horizontal oddticks1–25;Frequency/Current legends,zero traces;State -,Freq0.00(Hz),Current0.0(A). Visible tiny plot edge text preserved in image; no interpolation.
Manual — Bluetooth app parameter menu — page 646
Manual reference: physical PDF page 646. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Parameter settings function Press the ≡ symbol at the top-left of the APP and then press Parameter
settings, and functions that can be selected and set include General parameter settings, IM autotuning function settings, and PM autotuning function settings.
TECO510SeriesBLESystem menu:Remote Dashboard;Params Set expanded;Inv Parameters;IM Autotune;PM Autotune;FAQ;LogOut. Dimmed partially covered background chart contains right-edge oddticks15,17,19,21,23,25 and Current label;Current0.0(A),Value,Unit,settings gear. Covered content not reconstructed.
Manual — General parameter screen and IM autotuning procedure — page 647
Manual reference: physical PDF page 647. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Final00-06 parameter label clipped at screenshot edge.
General parameter settings Parameter settings can be performed directly, and be written into the connected machine.
Select the modified parameters or select all, and Write into the group to complete parameter settings.
IM autotuning function settings After setting the various motor parameters, the induction motor autotuning function can be executed. When the autotuning is completed, autotuning failed (Note) or autotuning successful will be displayed.
Press the ≡ symbol at the top-left of the APP when completed and press Real-time
monitoring to return to the monitoring screen and execute functions such as Run and Stop etc. Note: Please confirm whether there are errors with the parameter settings; refer to the explanations in the manual.
TECO parameter screen:Parameter setting->General parameters;Group00:Basic Parameters;Group Read;Group Write. TableName,Content,Value,Setting;selection boxes unchecked and pencil icons. Rows00-00 Control Mode Selection0(VF);00-01 Motor’s Rotation Direction0;00-02 Main Run Command Source Selection1;00-03 Alternative Run Command Selection0;00-04 Language0;00-05 Main Frequency Command Source Selection1;00-06 Alternative Frequency Source [remainder clipped]0. Source values are examples, not default recommendation; bottom label clipped.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Final00-06 parameter label clipped at screenshot edge.
Manual — PM autotuning and supplier FCC/IC statements — page 648
Manual reference: physical PDF page 648. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
PM autotuning function setting After setting the various motor parameters, the permanent-magnet motor autotuning function can be executed. When the autotuning is completed, autotuning failed (Note) or autotuning successful will be displayed.
Press the ≡ symbol at the top-left of the APP when completed and press Real-time
monitoring to return to the monitoring screen and execute functions such as Run and Stop etc. Note: Please confirm whether there are errors with the parameter settings; refer to the explanations in the manual.
FCC WARNING STATEMENT This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. IC WARNING STATEMENT Canada, Industry Canada (IC) Notices This Class B digita apparatus complies with Canadian ICES-003 and RSS-247. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. Radio Frequency (RF) Exposure Information The radiated output power of the Wireless Device is below the Industry Canada (IC) radio frequency exposure limits. The Wireless Device should be used in such a manner such that the potential for human contact during normal operation is minimized. This device has also been evaluated and shown compliant with the IC RF Exposure limits under mobile exposure conditions (antennas are greater than 20cm from a person's body).
Manual — Appendix A RS485 Modbus network example — page 649
Manual reference: physical PDF page 649. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
A1-1
Appendix A: Communication Networks
A1.1 RS485 –Network (Modbus)
This section shows a RS485 network consisting of several inverters communicating using the built-in Modbus RTU protocol.
Notes: - A PC / PLC controller with a built-in RS-485 interface can be connected directly to the RS-485 network. Use a RS232 to RS485 converter to connect a PC / PLC with a built-in RS-232 interface. - A maximum of 31 inverters can be connected to the network. Terminating resistors of 120 ohm must be installed at both end of the network. Refer to A510s RS-485 Modbus communication manual for more information.
Wiring diagram RS485 Modbus RTU Network. Labels Inverter#1,#2,#n;S-,S+,earth/E for each;SW4 within#1;Resistor120Ohm at each end shown;converterRS232/RS485 with-/+;PC/PLC RS232 withGND RX TX;PC/PLC RS485 with-/+. Red/blue/green drawn connections retained in image,not inferred as validated topology. Source note below limits31 inverters and120ohm terminating resistors at both ends.
Manual — Appendix B UL instructions electric shock cautions — page 650
Manual reference: physical PDF page 650. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-1
Appendix B: UL Instructions
Danger
Electric Shock Hazard Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury.
Warning
Electric Shock Hazard Do not operate equipment with covers removed. Failure to comply could result in death or serious injury. The diagrams in this section may show inverters without covers or safety shields to show details. Be sure to reinstall covers or shields before operating the inverters and run the inverters according to the instructions described in this manual. Always ground the motor-side grounding terminal. Improper equipment grounding could result in death or serious injury by contacting the motor case. Do not touch any terminals before the capacitors have fully discharged. Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the inverter before touching any components. Do not allow unqualified personnel to perform work on the inverter. Failure to comply could result in death or serious injury. Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of inverters. Do not perform work on the inverter while wearing loose clothing, jewelry, or lack of eye protection. Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning work on the inverter. Do not remove covers or touch circuit boards while the power is on. Failure to comply could result in death or serious injury.
Adjacent source context — repeated to preserve continuation:
Manual — UL fire hazard and equipment notices — page 651
Manual reference: physical PDF page 651. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-2
Warning
Fire Hazard Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections. Do not use an improper voltage source. Failure to comply could result in death or serious injury by fire. Verify that the rated voltage of the inverter matches the voltage of the incoming power supply before applying power. Do not use improper combustible materials. Failure to comply could result in death or serious injury by fire. Attach the inverter to metal or other noncombustible material.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the inverter and circuit boards. Failure to comply may result in ESD damage to the inverter circuitry. Never connect or disconnect the motor from the inverter while the inverter is outputting voltage. Improper equipment sequencing could result in damage to the inverter. Do not use unshielded cable for control wiring. Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the inverter. Do not modify the inverter circuitry. Failure to comply could result in damage to the inverter and will void warranty.Teco is not responsible for any modification of the product made by the user. This product must not be modified. Check all the wiring to ensure that all connections are correct after installing the inverter and connecting any other devices. Failure to comply could result in damage to the inverter.
Adjacent source context — repeated to preserve continuation:
Manual — Supplier UL standards statement and installation area — page 652
Manual reference: physical PDF page 652. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-3
UL Standards
The UL/cUL mark applies to products in the United States and Canada and it means that UL has performed product testing and evaluation and determined that their stringent standards for product safety
have been met. For a product to receive UL certification, all components inside that product must also receive UL certification.
UL Standards Compliance
This inverter is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued compliance when using this inverter in combination with other equipment, meet the following conditions:
■ Installation Area Do not install the inverter to an area greater than pollution severity 2 (UL standard).
Graphic c UL US LISTED; UL/cUL Mark; registered trademark glyph. Source mark illustration only,not independent certificate validation.
Manual — A510s closed-loop crimp terminal size table — page 653
Manual reference: physical PDF page 653. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-4
Main Circuit Terminal Wiring
UL approval requires crimp terminals when wiring the inverter’s main circuit terminals. Use crimping tools
as specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the insulation cap. The table below matches inverter models with crimp terminals and insulation caps.
Closed-Loop Crimp Terminal Size
A510s closed-loop crimp terminal size table
Drive Model A510s / Wire Gauge mm2 , (AWG / MCM) / Terminal / Crimp Terminal / Tool / Insulation Cap — PDF page 653
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Drive Model A510s | Wire Gauge mm2 , (AWG / MCM) | Wire Gauge mm2 , (AWG / MCM) | Terminal | Crimp Terminal | Tool | Insulation Cap |
| 2 | Drive Model A510s | R/L1 • S/L2 • T/L3 | U/T1 • V/T2 • W/T3 | Screws | Model No. | Machine No. | Model No. |
| 3 | 2001 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 4 | 2002 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 5 | 2003 | 3.5 (12) / 5.3 (10) | 3.5 (12) / 5.3 (10) | M4 | R3.5-4 / R5.5-4 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 6 | 2005 | 5.3 (10) | 5.3 (10) | M4 | R5.5-4 | Nichifu NH 1 / 9 | TIC 5.5 |
| 7 | 2008 | 8.4 (8) | 8.4 (8) | M4 | R8-4 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 8 | 2010 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 9 | 2015 | 13.3 (6) | 13.3 (6) | M6 | R14-6 | Nichifu NOP 60 / 150HA | TIC 14 |
| 10 | 2020 | 21.2 (4) | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 11 | 2025 | 21.2 (4) | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 12 | 2030 | 33.6 (2) | 33.6 (2) | M8 | R38-8 | Nichifu NOP 60 / 150HA | TIC 38 |
| 13 | 2040 | 67.4 (1/0) | 67.4 (1/0) | M8 | R60-8 | Nichifu NOP 60 / 150HA | TIC 60 |
| 14 | 2060 | 107.2 (4/0) | 107.2 (4/0) | M10 | R100-10 | Nichifu NOP 150HA | TIC 100 |
| 15 | 2075 | 152 (300MCM) | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 150HA | TIC 150 |
| 16 | 2100 | 200 (400MCM) | 200 (400MCM) | M10 | R200-10 | Nichifu NOP 700 & NOH300K | TIC 200 |
| 17 | 2125 | 300 (600MCM) | 300 (600MCM) | M12 | R325-12S | Nichifu NOP 700 & NOH300K | TIC 325 |
| 18 | 2150 | 250 (500MCM) * 2 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 19 | 4001 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 20 | 4002 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 21 | 4003 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 22 | 4005 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 23 | 4008 | 3.5 (12) / 5.3 (10) | 3.5 (12) / 5.3 (10) | M4 | R3.5-4 / R5.5-4 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 24 | 4010 | 3.5 (12) / 5.3 (10) | 3.5 (12) / 5.3 (10) | M4 | R3.5-4 / R5.5-4 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 25 | 4015 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 26 | 4020 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 27 | 4025 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 28 | 4030 | 13.3 (6) | 13.3 (6) | M6 | R14-6 | Nichifu NOP 60 / 150HA | TIC 14 |
| 29 | 4040-B | 21.2 (4) | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 30 | 4040 | 21.2 (4) | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 31 | 4050 | 21.2 (4) | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 32 | 4060 | 33.6 (2) | 33.6 (2) | M8 | R38-8 | Nichifu NOP 60 / 150HA | TIC 38 |
| 33 | 4075 | 67.4 (2/0) | 67.4 (2/0) | M8 | R70-8 | Nichifu NOP 60 / 150HA | TIC 70 |
| 34 | 4100 | 85 (3/0) | 85 (3/0) | M10 | R80-10 | Nichifu NOP 60 / 150HA | TIC 80 |
| 35 | 4125 | 152 (300MCM) | 152 (300MCM) | M10 | R100-10 | Nichifu NOP 60 / 150HA | TIC 100 |
| 36 | 4150 | 152 (300MCM) | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
| 37 | 4175 | 200 (400MCM) | 200 (400MCM) | M10 | R200-10 | Nichifu NOP 700 & NOH300K | TIC 200 |
| 38 | 4215 | 250 (500MCM) | 250 (500MCM) | M10 | R250-10 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 39 | 4270 | 300 (600MCM) | 300 (600MCM) | M12 | R325-12S | Nichifu NOP 700 & NOH300K | TIC 325 |
| 40 | 4300 | 250 (500MCM) * 2 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 41 | 4375 | 250 (500MCM) * 2 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
| 42 | 4425 | 250 (500MCM) * 2 | 250 (500MCM) * 2 | M12 | R250-12 | Nichifu NOP 700 & NOH300K | TIC 250 |
Manual — A510s and A510s(F) terminal table continuation — page 654
Manual reference: physical PDF page 654. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-5
A510s and A510s(F) terminal table continuation
Drive Model A510s / Wire Gauge mm2 , (AWG / MCM) / Terminal / Crimp Terminal / Tool / Insulation Cap — PDF page 654
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Drive Model A510s | Wire Gauge mm2 , (AWG / MCM) | Wire Gauge mm2 , (AWG / MCM) | Terminal | Crimp Terminal | Tool | Insulation Cap |
| 2 | Drive Model A510s | R/L1 • S/L2 • T/L3 | U/T1 • V/T2 • W/T3 | Screws | Model No. | Machine No. | Model No. |
| 3 | 5001 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4 ~ R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 4 | 5002 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4 ~ R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 5 | 5003 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4 ~ R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 6 | 5005 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M6 | R2-6 ~ R5.5-6 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 7 | 5008 | 3.5 (12) / 5.3 (10) | 3.5 (12) / 5.3 (10) | M6 | R3.5-6 / R5.5-6 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 8 | 5010 | 3.5 (12) / 5.3 (10) | 3.5 (12) / 5.3 (10) | M6 | R3.5-6 / R5.5-6 | Nichifu NH 1 / 9 | TIC 3.5/ 5.5 |
| 9 | 6015 | 5.3 (10) | 5.3 (10) | M6 | R5.5-6 | Nichifu NH 1 / 9 | TIC 5.5 |
| 10 | 6020 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 11 | 6025 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 12 | 6030 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 13 | 6040 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 14 | 6050 | 13.3 (6) | 13.3 (6) | M8 | R14-8 | Nichifu NOP 60 / 150HA | TIC 14 |
| 15 | 6060 | 13.3 (6) | 13.3 (6) | M8 | R14-8 | Nichifu NOP 60 / 150HA | TIC 14 |
| 16 | 6075 | 21.2 (4) | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 17 | 6100 | 33.6 (2) | 33.6 (2) | M10 | R38-10 | Nichifu NOP 60 / 150HA | TIC 38 |
| 18 | 6125 | 67.4 (2/0) | 67.4 (2/0) | M10 | R70-10 | Nichifu NOP 60 / 150HA | TIC 70 |
| 19 | 6150 | 67.4 (2/0) | 67.4 (2/0) | M10 | R70-10 | Nichifu NOP 60 / 150HA | TIC 70 |
| 20 | 6175 | 85 (3/0) | 85 (3/0) | M10 | R80-10 | Nichifu NOP 60 / 150HA | TIC 80 |
| 21 | 6215 | 152 (300MCM) | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
| 22 | 6250 | 152 (300MCM) | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
| 23 | 6270 | 152 (300MCM) | 152 (300MCM) | M10 | R150-10 | Nichifu NOP 700 & NOH300K | TIC 150 |
Drive Model A510s (F) / Wire Gauge mm2 , (AWG / MCM) / Terminal / Crimp Terminal / Tool / Insulation Cap — PDF page 654
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|
| 1 | Drive Model A510s (F) | Wire Gauge mm2 , (AWG / MCM) | Wire Gauge mm2 , (AWG / MCM) | Terminal | Crimp Terminal | Tool | Insulation Cap |
| 2 | Drive Model A510s (F) | R/L1 • S/L2 • T/L3 | U/T1 • V/T2 • W/T3 | Screws | Model No. | Machine No. | Model No. |
| 3 | 4001 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 4 | 4002 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 5 | 4003 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 6 | 4005 | 2 (14) / 3.5 (12) / 5.3 (10) | 2 (14) / 3.5 (12) / 5.3 (10) | M4 | R2-4/R3.5-4/R5.5-4 | Nichifu NH 1 / 9 | TIC 2/ 3.5/ 5.5 |
| 7 | 4008 | 5.3 (10) | 5.3 (10) | M4 | R5.5-4 | Nichifu NH 1 / 9 | TIC 5.5 |
| 8 | 4010 | 5.3 (10) | 5.3 (10) | M6 | R5.5-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 5.5 |
| 9 | 4015 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 10 | 4020 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 11 | 4025 | 8.4 (8) | 8.4 (8) | M6 | R8-6 | Nichifu NOP 60 ; NH 1 / 9 | TIC 8 |
| 12 | 4030 | 13.3 (6) | 13.3 (6) | M6 | R14-6 | Nichifu NOP 60 / 150HA | TIC 14 |
| 13 | 4040-B | 21.2 (4) | 21.2 (4) | M6 | R22-6 | Nichifu NOP 60 / 150HA | TIC 22 |
| 14 | 4040 | 21.2 (4) | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 15 | 4050 | 21.2 (4) | 21.2 (4) | M8 | R22-8 | Nichifu NOP 60 / 150HA | TIC 22 |
| 16 | 4060 | 33.6 (2) | 33.6 (2) | M8 | R38-8 | Nichifu NOP 60 / 150HA | TIC 38 |
Manual — Type1 A510 fuse tables and field terminal requirements — page 655
Manual reference: physical PDF page 655. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-6
Type 1
During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.
Motor Over-temperature Protection Motor over-temperature protection shall be provided in the end use application.
■ Field Wiring Terminals All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be used.
Raster original labels Drive Model A510;FuseType;Manufacturer:Bussmann/FERRAZSHAWMUT;Model;FuseAmpereRating(A);200VClassThree-PhaseDrives. Do not silently relabel A510s. Original headers separately preserved by source context and image.
Raster original labels Drive Model A510;FuseType;Manufacturer:Bussmann/FERRAZSHAWMUT;Model;FuseAmpereRating(A);400VClassThree-PhaseDrives. 4020rating is blue overlaid text in source. No preferred fuse inferred.
Type1 fuse table /200V Class Three-Phase Drives — PDF page 655
| Source row | Drive Model A510 | Fuse model | Fuse Ampere Rating (A) |
|---|---|---|---|
| 1 | 2001 | Bussmann 20CT | 690V 20A |
| 2 | 2002 | Bussmann 30FE | 690V 30A |
| 3 | 2003 | Bussmann 50FE | 690V 50A |
| 4 | 2005 | Bussmann 50FE | 690V 50A |
| 5 | 2008 | Bussmann 63FE | 690V 63A |
| 6 | 2010 | FERRAZ SHAWMUT A50QS100-4 | 500V 100A |
| 7 | 2015 | Bussmann 120FEE / FERRAZ A50QS150-4 | 690V 120A / 500V 150A |
| 8 | 2020 | FERRAZ SHAWMUT A50QS150-4 | 500V 150A |
| 9 | 2025 | FERRAZ SHAWMUT A50QS200-4 | 500V 200A |
| 10 | 2030 | FERRAZ SHAWMUT A50QS250-4 | 500V 250A |
| 11 | 2040 | FERRAZ SHAWMUT A50QS300-4 | 500V 300A |
| 12 | 2050 | FERRAZ SHAWMUT A50QS400-4 | 500V 400A |
| 13 | 2060 | FERRAZ SHAWMUT A50QS500-4 | 500V 500A |
| 14 | 2075 | FERRAZ SHAWMUT A50QS600-4 | 500V 600A |
| 15 | 2100 | FERRAZ SHAWMUT A50QS700-4 | 500V 700A |
Type1 fuse table /400V Class Three-Phase Drives — PDF page 655
| Source row | Drive Model A510 | Fuse model | Fuse Ampere Rating (A) |
|---|---|---|---|
| 1 | 4001 | Bussmann 10CT | 690V 10A |
| 2 | 4002 | Bussmann 16CT | 690V 16A |
| 3 | 4003 | Bussmann 16CT | 690V 16A |
| 4 | 4005 | Bussmann 25ET | 690V 25A |
| 5 | 4008 | Bussmann 40FE | 690V 40A |
| 6 | 4010 | Bussmann 50FE | 690V 50A |
| 7 | 4015 | Bussmann 63FE | 690V 63A |
| 8 | 4020 | Bussmann 80FE | 690V 80A |
| 9 | 4025 | Bussmann 100FE / FERRAZ A50QS100-4 | 690V 100A / 500V 100A |
| 10 | 4030 | Bussmann 120FEE | 690V 120A |
| 11 | 4040 | FERRAZ SHAWMUT A50QS150-4 | 500V 150A |
| 12 | 4050 | FERRAZ SHAWMUT A50QS200-4 | 500V 200A |
| 13 | 4060 | FERRAZ SHAWMUT A50QS250-4 | 500V 250A |
| 14 | 4075 | FERRAZ SHAWMUT A50QS300-4 | 500V 300A |
| 15 | 4100 | FERRAZ SHAWMUT A50QS400-4 | 500V 400A |
| 16 | 4125 | FERRAZ SHAWMUT A50QS500-4 | 500V 500A |
| 17 | 4150 | FERRAZ SHAWMUT A50QS600-4 | 500V 600A |
| 18 | 4175 | FERRAZ SHAWMUT A50QS700-4 | 500V 700A |
| 19 | 4215 | FERRAZ SHAWMUT A50QS700-4 | 500V 700A |
Manual — Short-circuit table and motor rated current protection — page 656
Manual reference: physical PDF page 656. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-7
■ Inverter Short-Circuit Rating This inverter has undergone the UL short-circuit test, which certifies that during a short circuit in the power
supply the current flow will not rise above value. Please see electrical ratings for maximum voltage and table below for current. • The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit tolerance of the power supply being used. • Suitable for use on a circuit capable of delivering not more than (A) RMS symmetrical amperes for.DiJ2.lHp in 240 / 480 V class drives motor overload protection.
Inverter Motor Overload Protection Set parameter 02-0 I (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload protection is UL listed and in accordance with the NEC and CEC.
■ 02-01 Motor Rated Current Setting Range Model Dependent Factory Default: Model Dependent The motor rated current parameter (02-0) protects the motor and allows for proper vector control when using open loop vector or flux vector control methods (00-00 = 2 or 3). The motor protection parameter 08-05 is set as factory default. Set 02-01 to the full load amps (FLA) stamped on the nameplate of the motor. The operator must enter the rated current of the motor (17-02) in the menu during auto-tuning. If the auto-tuning operation completes successfully (17-00 = 0), the value entered into 17-02 will automatically write into 02-0 I.
Raster table within UL appendix;HorsePower(Hp),Current(A),Voltage(V). Source assertions only.
Short circuit rating — PDF page 656
| Source row | Horse Power (Hp) | Current (A) | Voltage (V) |
|---|---|---|---|
| 1 | 1 - 50 | 5,000 | 240 / 480 |
| 2 | 51 - 200 | 10,000 | 240 / 480 |
| 3 | 201 - 400 | 18,000 | 240 / 480 |
| 4 | 401 - 600 | 30,000 | 240 / 480 |
Manual — 08-05 motor overload selection and application notes — page 657
Manual reference: physical PDF page 657. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-8
■ 08-05 Motor Overload Protection Selection The inverter has an electronic overload protection function (OL1) based on time, output current, and output frequency, which protects the motor from overheating. The electronic thermal overload function is
UL-recognized, so it does not require an external thermal overload relay for single motor operation. This parameter selects the motor overload curve used according to the type of motor applied.
Sets the motor overload protection function in 08-05 according to the applicable motor.
08-05 = ---OB: Disables the motor overload protection function when two or more motors are connected to a single inverter. Use an alternative method to provide separate overload protection for each motor such as connecting a thermal overload relay to 1he power line of each motor.
08-05 = --1-B: The motor overload protection function should be set to hot start protection characteristic curve when the power supply is turned on and off frequently, because the thermal values are reset each time when the power is turned off.
08-05 = -0—B: For motors without a forced cooling fan (general purpose standard motor), the heat dissipation capability is lower when in low speed operation.
08-05 = -1—B: For motors with a forced cooling fan (inverter duty or VIF motor), the heat dissipation capability is not dependent upon the rotating speed. To protect the motor from overload by using electronic overload protection, be sure to set parameter 02-01 according to the rated current value shown on the motor nameplate. Refer to the following "Motor Overload Protection Time" for the standard motor overload protection curve
example: Setting 08-05 = -0--B.
08-05 motor overload selection and application notes
08-05 / Selection for motor overload protection (OL1) — PDF page 657
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-05 | Selection for motor overload protection (OL1) |
| 2 | Range | xxx0b: Motor overload is invalid xxx1b: Motor overload is valid xx0xb: Cold start of motor overload xx1xb: Hot start of motor overload x0xxb: Standard motor x1xxb: Special motor 0xxxb: Reserved 1xxxb: Reserved |
Manual — Overload plot,08-06 selection and additional A510 fuse tables — page 658
Manual reference: physical PDF page 658. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
B-9
■ 08-06 Motor Overload Operation Selection
08-06=0: When the inverter detects a motor overload the inverter output is turned off and the OL1 fault message will flash on the keypad. Press RESET button on the keypad or activate the reset function through the multi-function inputs to reset the OL1 fault.
08-06=1: When the inverter detects a motor overload the inverter will continue running and the OL1 alarm message will flash on the keypad until the motor current falls within the normal operating range.
UL- Additional Data Recommended Input Fuse Selection
Source overload plot:Overload Protect Time(min),vertical printedlabels top-to-bottom5.5,3.0,3.5,1.0;Motor Load Current(%) (02-01=100%);horizontal100%,150%,200%;LowSpeed(<60Hz),HighSpeed(>60Hz);ColdStart dashed curve,HotStart solidcurve. Nonmonotonic3.0above3.5 retained exactly; no corrected engineering value or interpolated curve inferred.
Overload plot,08-06 selection and additional A510 fuse tables
Recommended Input Fuse Selection;DriveModelA510;FuseType;Manufacturer:Bussmann/FERRAZSHAWMUT;200VClassThree-PhaseDrives. Source model label preserved.
Recommended Input Fuse Selection;DriveModelA510;FuseType;Manufacturer:Bussmann/FERRAZSHAWMUT;400VClassThree-PhaseDrives. 4250 is literal;do not replace with4215.
08-06 / Start-up mode of overload protection operation (OL1) — PDF page 658
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | 08-06 | Start-up mode of overload protection operation (OL1) |
| 2 | Range | 0: Stop output after overload protection 1: Continuous operation after overload protection. |
Additional fuse selection /200V Class Three-Phase Drives — PDF page 658
| Source row | Drive Model A510 | Fuse model | Fuse Ampere Rating (A) |
|---|---|---|---|
| 1 | 2125 | Bussmann 170M5464 | 690V 800A |
| 2 | 2150 | Bussmann 170M5464 | 690V 800A |
Additional fuse selection /400V Class Three-Phase Drives — PDF page 658
| Source row | Drive Model A510 | Fuse model | Fuse Ampere Rating (A) |
|---|---|---|---|
| 1 | 4250 | Bussmann 170M5464 | 690V 800A |
| 2 | 4300 | Bussmann 170M5464 | 690V 800A |
| 3 | 4375 | Bussmann 170M5466 | 690V 1000A |
| 4 | 4425 | Bussmann 170M5466 | 690V 1000A |
Manual — Safety stop function instruction manual: contents — page 659
Manual reference: physical PDF page 659. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
INVERTER A510s series
Safety stop function instruction manual
CONTENTS
Introduction ................................................................................................... 3
Safety-Related Standard ............................................................................ 3
Product Information .................................................................................... 4
Safety Stop / Safety Torque OFF ............................................................. 5
Electromechanical and Safety integrated interface Comparison .. 6
Terminal designation & interface ............................................................ 7
Safety Input logic & Status ........................................................................ 9
Installation and wiring .............................................................................. 10
Safety Input Status.................................................................................... 11
Safety design and specifications .......................................................... 13
Manual — Safety stop function: warnings, cautions and attention — page 660
Manual reference: physical PDF page 660. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Compliance with the EU Machinery Directive – Functional Safety
WARNING Safe Torque off function may not be an appropriate method for stopping your machine. Activating this function will result in no output voltage to the Motor hence motor will coast down to stop under the influence of the load inertia.
WARNING Any misuse of safety function could lead to personal injury or death, property damage, or economic loss. To ensure that the system complies fully with requirement of safety, make a system-level risk assessment. TECO Electric Co. cannot assume responsibility for any system to comply with safety directive.
CAUTION The information of this manual is merely a guide for proper installation. TECO Electric Co. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
WARNING To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the P(+) and N(-) terminals or test points (refer to your drive’s User Manual for locations and discharging time). The voltage must bezero.
WARNING To avoid an electric shock hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before performing any work on the motor (refer to your drive’s User Manual for discharging time).
CAUTION In order to maintain the pollution degree 2 the devices shall be mounted in a cabinet of IP 54 type .or pollution controlled environment.
CAUTION Ensure that the external safety relay unit and the A510s drive are mounted close to each other all interconnection wiring is as short as possible and protected against open and short circuit faults. Refer EN/ISO13849-1.
CAUTION To avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check the correct function of the monitor signal. This test shall be carried out at system installation, any software changes, parameterization changes, and/or at least once per year. Refer to “Chapter 10 Troubleshooting and Fault Diagnostics”.
Manual — Safety stop introduction, historical standards and environment — page 661
Manual reference: physical PDF page 661. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Introduction
This document describes the main design specification of the A510s Safe Torque Off (STO) and the requirements for its installation and integration within safety related applications. The correct Installation and integration of the A510s STO is the responsibility of the Installer and it is expected that the installer follows the safety guide and is a trained technician and experienced in the design of safety systems. A510s STO (Safe Torque Off) The product circuit and function are designed with reference to the relevant standards: Safety Integrated category SIL2 according to EN/IEC 62061, IEC 61508, EN61800-5-2 Performance level. Category 3/ Pl(d). According to EN/ISO 13849-1 Stop category 0. According to EN60204-1
- Safety-Related Standard
2.1 Directives
2.2 Installation Environment A510s safety stop function should only be used under the following condition and environment.
Safety stop introduction, historical standards and environment
IEC/EN 61800- 5-2 : 2007 / Adjustable Speed Electrical Power Drive Systems. Part 5-2: Safety Requirements – Functional — PDF page 661
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | IEC/EN 61800- 5-2 : 2007 | Adjustable Speed Electrical Power Drive Systems. Part 5-2: Safety Requirements – Functional |
| 2 | EN ISO 13849-1: 2008 | Safety of Machinery – Safety-related parts of control systems. Part 1: General Principles for Design |
| 3 | IEC 61508- 1~7 | Functional Safety of Electrical/Electronic/Programmable Electronic Safety-related systems |
| 4 | IEC 62061: 2005 | Safety of Machinery – Functional safety of safety-related electrical, electronic and programmable electronic control systems |
| 5 | EN 60204-1 | Safety of machinery - Electrical equipment of machines. General requirements. |
Item / Condition — PDF page 661
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Item | Item | Condition |
| 2 | Temperature range | Operation | -10°C~50°C inside distributor (without dust cover) -10°C~40°C inside distributor (with dust cover) |
| 3 | Temperature range | Storage | -20°C to +60°C |
| 4 | Ambient humidity | Ambient humidity | 95%RH maximum (non-condensing) |
| 5 | Shock | Shock | 1G. (9.8m/s²) for 20Hz and below. 0.6G (5.88m/s²) from 20Hz to 50Hz (Compliance with IEC 60068- 2-6) |
| 6 | Altitude | Altitude | maximum 1000m above sea level |
| 7 | Atmosphere | Atmosphere | Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.) |
Manual — Environment, product range and model name identification — page 662
Manual reference: physical PDF page 662. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Product Information
3.1 Product models & range
230V three phase. IP20 0.75 ~ 110KW (1 ~ 150Hp) without built-in filter
400V three phase. IP20 0.75 ~ 45KW (1 ~ 60Hp) with built-in filter
400V three phase. IP20 0.75 ~ 315KW (1 ~ 425Hp) without built-in filter
575V there IP20 0.75 ~ 7.5KW (1 ~ 10Hp) without built-in filter
690V there IP20 11 ~ 200KW (15 ~ 270Hp) without built-in filter
- Please refer to Chapter 3 in the front of the installation manual for detail.
3.2 Product Identification
Model name identification diagram: example A510 - 4 010 - S H 3 F - 1. Voltage: 2 = 200V Class; 4 = 400V Class; 5 = 575V Class; 6 = 690V Class. Motor rating: 001 = 1HP; 002 = 2HP; omitted intermediate examples are indicated by ellipses; 150 = 150HP; 175 = 175HP; 215 = 215HP; ellipses; 375 = 375HP; 425 = 425HP. S = A510s Inverter Series. Operator: H = Standard Type (LED Keypad); C = Standard Type (LCD Keypad); E = Enhanced Type (LED Keypad); G = Enhanced Type (LCD Keypad). Input: blank = 1Ph or 3Ph; 3 = 3Ph. Noise filter: blank = No RFI Filter; F = RFI Filter. Enclosure: blank = IP00/IP20; 1 = IP21 for frame 1~5; B = Enhanced type (400V 40HP built-in braking transistor model). Formatting return/paragraph glyphs in this diagram are not model characters.
Environment, product range and model name identification
Over voltage category / III or less — PDF page 662
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Over voltage category | III or less |
| 2 | Pollution degree | II or less |
| 3 | Mounting | wall mounting / verticalorientation |
Manual — UL model identification and STO overview — page 663
Manual reference: physical PDF page 663. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
3.3 Model Identification
- Safety Stop / Safe Torque Off. (STO).
A510s STO is a functional safety feature that complies with the safety functions in adjustable speed drives according to IEC 61800-5-2 ( type A safety component) and when put in use within a safety control system according to the required safety standards will provide safe Torque off (no output voltage) and Prevents an unintentional restart.
Caution
The STO Function by itself is not an Emergency Stop and may be used as part of an
Emergency Stop control system but all relevant standards must be consulted.
Decision to use STO in a control system must be based on risk assessment, refer to the
relevant standards EN/IEC 62061or EN/ISO 13849-1.
In application of STO due to the coast to stop function take into consideration the
stopping time of the driven load.
For further information on STO refer to EN61800-5-2 and For stop categories Refer to
EN60204-1
Model identification schematic: A B - CDE - F - G - HIJ - K - L. A Product: 1 Inverter, 2 SERVO, 3 PLC. B UL Category: 0 UL Recognized, 1 UL Listed. C-E Serial number: 001-999 (202). F Standard voltage: 1 100-120V, 2 200-240V, 4 380-480V. G Phase: 0 Single/Three phase, 1 Single phase, 3 Three phase. H-J O/P current: 04P1 4.1Amp (1HP); 12P1 12.1Amp (5HP); 0103 103Amp (60HP). K Firmware Ver.: A A510s, F F510. L EMC Filter: blank Not built-in, F Built-in. These are literal schematic slots and examples, not expanded model applicability.
STO overview: STO Activated → IGBT outputs are shut down → Motor Speed Coasts to zero. Stop Category 0 to EN60204-1. Separate plot axes v and t, STO arrow and Safe torque Off label. Plot line retained in original image; no numeric stopping time or inferred implementation.
Manual — Electromechanical versus integrated STO examples — page 664
Manual reference: physical PDF page 664. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny hardware photograph inscriptions remain unreadable after enlargement.
- Electromechanical and Safety integrated interface Comparison
Diagrams below show simple Inverter drive configurations for comparison between safe stop
interfaces using electromechanical and Safety integrated type solutions.
Electromechanical. Without STO function
Three source comparison illustrations. First: Electromechanical. Without STO function; No SIL. Stop Category 0; Emergency stop, Safety Interlocks, Contactor, Inverter, Motor. Second: Electromechanical. Without STO function; SIL 2. Stop Category 0; Emergency stop, Safety Interlocks, Contactor, Inverter, Motor. Third: Integrated STO FUNCTION; SIL 2. Stop Category 0; Emergency stop, Safety Interlocks, Safety Relay, Motor; TECO visible on inverter photograph. Arrows and component photographs remain image evidence. Tiny inscriptions on photographs are unresolved; no inferred wiring or safety validation.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny product/contact/relay/keypad inscriptions in illustrative hardware photographs remain unreadable after enlargement.
Manual — Terminal designation, interface and safety ratings — page 665
Manual reference: physical PDF page 665. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Source limitation for this page: Tiny embedded frame1 operator inscriptions remain incomplete; terminal strip is fully transcribed.
- Terminal designation & interface
6.1 Power & Control terminals.
Frame 1. Terminal layout is shown as a typical example.
6.2 Control terminals & wiring
Table 1: Safety related terminals
Frame 1 typical terminal layout. TM1 Power terminals; TM2 Control terminals, Frame1 A510s; Ground Terminals. Arrow locations retained in source image. Tiny embedded operator/terminal inscriptions are not fully readable and are not inferred.
Control terminal strip, visible label rows. Left upper: R1A, R1B, R1C, R2A, R2C; lower RJ45. Right upper: S(+), S(-), S1, S3, S5, S7, 24V, 24VG, +10V, -10V, GND, GND, AI1, AI2. Right lower: DO1, DOG, S2, S4, S6, S8, SF1, SG, SF2, PO, PI, AO1, AO2, E. Source callout: Safety Terminals. SF1 / SF2 & SG (Common). Remove the jumper link for external interface. Original jumper/arrow geometry retained, no inferred connection topology.
PARTIAL_CONTEXT_PENDING_REMAINING_CONTENT: Tiny embedded operator inscriptions in frame1 hardware illustration remain incompletely readable; separate terminal-strip labels are fully transcribed.
LOC
REM
DSP
FUN
RESET
READ
ENTER
RUN
STOP
Terminal designation, interface and safety ratings
Terminal Symbol / Description / Rating — PDF page 665
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) |
|---|---|---|---|
| 1 | Terminal Symbol | Description | Rating |
| 2 | SF1 | The function status of SF1-SG terminal. Open: In safety stop mode. Short: Non-safety stop mode. | Input resistance:4.22kΩ Input Current:5 to 6.5 mA Input Voltage:21.6 to 26.4 V |
| 3 | SF2 | For function status of SF2-SG terminal. Open: In safety stop mode. Short: Non-safety stop mode. | Input resistance:4.22kΩ Input Current:5 to 6.5 mA Input Voltage:21.6 to 26.4 V |
| 4 | SG | Common terminal for SF1, SF2 terminals. | ⟦blank source cell⟧ |
Manual — 6.3 External24Vdc supply (Connection option) — page 666
Manual reference: physical PDF page 666. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
This page belongs to the appended A510s Safety stop function instruction manual (coverPDF659), not main-manual section6.3. Printed page8 retained.
Label inventory only; original external-supply wiring, switches and jumpers remain authoritative. No safety rating, certificate validity or system compliance inferred. Related source warning retained separately fromPDF667.
Terminal layout differs from main-manualPDF503. Do not merge+12V/F1/F2 with this supplement+10V/-10V/SF1/SF2/SG.
BothGNDlabels retained. Row inventories do not imply alignment or inferred connections; originaldiagram required.
No current rating, cable dimensions or connection topology inferred.
Printed terminal strip labels — PDF page 666
| Source row | Source group/row | Labels left-to-right |
|---|---|---|
| 1 | Left upper | R1A; R1B; R1C; R2A; R2C |
| 2 | Left lower | RJ45 |
| 3 | Main upper | S(+); S(-); S1; S3; S5; S7; 24V; 24VG; +10V; -10V; GND; GND; AI1; AI2 |
| 4 | Main lower | DO1; DOG; S2; S4; S6; S8; SF1; SG; SF2; PO; PI; AO1; AO2; E |
Supply labels — PDF page 666
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Supply | External power Supply |
| 2 | Positive label | +24V |
| 3 | Reference label | 0V |
Manual — Safety input logic and status block diagram — page 667
Manual reference: physical PDF page 667. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
WARNING: The safety stop function does not isolate electrically between drive and motor. To avoid an electric shock hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before performing any work on the motor (refer to your drive’s User Manual for discharging time).
Read the warning with physical page 666. Listed standards are historical source statements, not a present certification or compliance assertion.
- Safety Input logic & Status
TECO A510s safety stop function prevents a drive from supplying rotational energy to motors.
Dual safety channels “SF1” and “SF2” cut off the gate-drive power for IGBT to turn off.
Diagram below shows the basic block diagram design of the safety and interface for the safety
inputs.
Figure 1: A510s safety stop function diagram
WARNING
The safety stop function does not isolate electrically between drive and motor. To avoid an electric shock hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before performing any work on the motor (refer to your drive’s User Manual for discharging time).
Directives
TECO A510s safety stop function refer to the following directives and categories:
ISO13849-1:2008 Category 3/PLd
IEC62061:2005
IEC61800-5-2:2007
IEC61508 SIL2
IEC60204-1:2006 Stop category 0
Safety stop function block diagram labels: External Safety Device Approved to SIL2 / PLd; SF2; SF1; +24V (two labels); V2; V1; S2′; S1′; S2″; S1″; CPU; Gate Driver IC; Gate Driver Photo; IGBTs; Input power; M. Original circuit symbols and lines retained as source image; this is transcription of labels, not a reconstructed circuit or safety approval.
Manual — Safety installation and wiring cautions — page 668
Manual reference: physical PDF page 668. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
WARNING
The misuse of safety function leads to personal injury or death, property damage, or economic loss. To ensure that the system complies fully with requirement of safety, make a system-level risk assessment. TECO Electric Co. cannot assume responsibility for any system to comply with safety directive.
- Installation and wiring
CAUTION
The following information is merely a guide for proper installation.
TECO Electric & Machinery Co. cannot assume responsibility for the compliance or the
noncompliance to any code, national, local or otherwise for the proper installation of this
equipment. A hazard of personal injury and/or equipment damage exists if codes are
ignored during installation.
CAUTION Ensure the safety relay unit and the A510s unit is mounted closely in open type and all interconnection wiring is short and protected against open and short circuit faults. Refer EN/ISO13849-1.
Installation
TECO A510s safety stop function should be used under following condition and environment.
In order to meet safety stop, an approved safety relay unit to ISO13849-1 safety category 3. In addition, all other components with in the safety stop loop shall be ‘safety approved’ types.
To avoid an electric shock hazard, insert the magnetic contactor (MC) between power source and drive. Open the contact of MC and keep away from drive for discharging time (refer to your drive’s User Manual for information) before performing any work on the drive. And verify that the voltage on the bus capacitors has discharged before Measure the DC bus voltage at the P(+) and N(-) terminals or test points. (Refer to your drive’s User Manual for locations). The voltage must be zero.
Wiring
The safety related terminals are described in Table 1 & Figure 1.
Manual — Safety input truth table, diagnostic and self-test — page 669
Manual reference: physical PDF page 669. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Safety Input Status
Table below shows the logic level status for external safety interface, internal circuit and drive
output.
Table 2 Truth table of Safety related signals
The response time from safety stop signal input to drive shutoff is faster than 8ms.
Hold the ON or OFF status for 1ms or longer to input signal to terminal SF1 or SF2.
Signal input shorter than 1ms is not recognized.
About the electric ratings of terminals, please refer to Chapter 3 in the front of the
installation manual for detail.
Diagnostic
Safety stop function protection mechanisms: Safety stop terminal (SF1-SF2-SG)contact short wire, Disable safety stop mode, Motor running; 1. When SF1-SG open and SF2-SG short, at this time, protection signal will cut off driver unit enable pin, IGBT none PWM signal, motor free run; 2. Otherwise, When SF1-SG short and SF2-SG open, at this time, protection signal will cut off driver unit input power, IGBT none PWM signal, motor free run;
- Safety stop terminal (SF1-SF2-SG)contact short wire, the motor running ,When photo-coupler secondary side of the power supply V1 & V2 occurs suddenly OV or UV, CPU detected abnormal voltage state , sent “LO” signal to NAND logic gate cutting off gate drive enable signals, motor free run.
Self-diagnostic test
A510s does the self-diagnostic test on the power-ON.
If A510s output alarm at power-ON, please take the action described in “Diagnostic”
at above.
Safety input truth table, diagnostic and self-test
+24VDC Power supply / External Safety Input Status / Internal safety circuit logic / Safety Circuit Failure / Drive Output Status OFF = Safe State ON= Enabled / Motor status — PDF page 669
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) | Physical column 3 (source headings retained in rows) | Physical column 4 (source headings retained in rows) | Physical column 5 (source headings retained in rows) | Physical column 6 (source headings retained in rows) | Physical column 7 (source headings retained in rows) | Physical column 8 (source headings retained in rows) | Physical column 9 (source headings retained in rows) | Physical column 10 (source headings retained in rows) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | +24VDC Power supply | External Safety Input Status | External Safety Input Status | Internal safety circuit logic | Internal safety circuit logic | Internal safety circuit logic | Internal safety circuit logic | Safety Circuit Failure | Drive Output Status OFF = Safe State ON= Enabled | Motor status |
| 2 | +24VDC Power supply | SF1-SG | SF2-SG | S1’ | S2’ | S1’’ | S2’’ | Safety Circuit Failure | Drive Output Status OFF = Safe State ON= Enabled | Motor status |
| 3 | OFF | - | - | - | - | - | - | - | OFF | Stop |
| 4 | ON | OFF | OFF | L | L | H | H | Detected | OFF | Stop |
| 5 | ON | OFF | ON | L | H | H | L | Detected | OFF | Stop |
| 6 | ON | ON | OFF | H | L | L | H | Detected | OFF | Stop |
| 7 | ON | ON | ON | H | H | L | L | - | ON | Run |
Manual — Safety functionality test procedure — page 670
Manual reference: physical PDF page 670. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Test procedure for functionality
As depicted “ATTENTION” in above, the test for the
functionality is important. Please do the test following procedure.
(1) Please make each state of SF1-SG and SF2-SG depicted at Table 2.
(2) If there is any different state from Table 2, A510s has some malfunction.
(3) If there is no different state from Table 2, check the systematic performance,
such as, press the Emergency switch, press the start/restart button at the failure
detected (RUN-SE opened), and so on.
(4) Finally clear the error record of the A510s (see the user manual how to clear the
error record).
Manual — Safety design requirements and supplier reliability figures — page 671
Manual reference: physical PDF page 671. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
- Safety design and specifications
STO design main requirements
Abbreviations:
Safety design requirements and supplier reliability figures
Safety Function Requirement Specification SIL2 — PDF page 671
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Safety Function Requirement Specification SIL2 | Safety Function Requirement Specification SIL2 |
| 2 | Initiating devices | User connected sensor or other safety devices |
| 3 | Hazard | Rotation of the motor (To be derived from hazard assessment) |
| 4 | Consequence | Human harm or damage to machinery. |
| 5 | Safe State | PWM removed, therefore No Voltage output from the drive. |
| 6 | Required Action | Detect Safe input signals and remove PWM signal. |
| 7 | Response Time | 8ms (from STO input signal detection to the final action of STO) |
| 8 | Target SIL | SIL = 2, PL d, category 3 |
| 9 | Demand Rate | High demand rate |
| 10 | Mode of Operation | Continuous |
| 11 | PFHD | The PFHD of STO function shall be less than 0.5* 10-6 |
| 12 | MTBF | The MTBF of drive system shall be more than 100,000 hours |
| 13 | Trip Mode | De-energize to trip |
| 14 | MTTR | No more than 4 hours (No field repair, only change new board) |
Parameter / Value — PDF page 671
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | Parameter | Value |
| 2 | PFDAVG | 2.58×10^-4 |
| 3 | PFHD | 1.18×10^-8 |
| 4 | PL | d |
| 5 | MTBF | 8,096 years |
| 6 | DCAVG | 84% |
SIL / Safety Integrated Level — PDF page 671
| Source row | Physical column 1 (source headings retained in rows) | Physical column 2 (source headings retained in rows) |
|---|---|---|
| 1 | SIL | Safety Integrated Level |
| 2 | PFHD | Probability of Dangerous failure Per hour |
| 3 | MTBF | Mean Time Between Failures |
| 4 | MTTR | Mean Time to Repair. ( hour) |
Manual — Manufacturer statement for A510s Enhanced efficiency — page 672
Manual reference: physical PDF page 672. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
Manufacturer’s Statement for A510s Enhanced series
A510s Enhanced efficiency according to IEC/EN 61800‐9‐2 Drive models: A510s Enhanced series, please refer to the table below for the model list Efficiency class: IE2 Nominal voltage: Please refer to the tabel below Nominal frequency: 50Hz Nominal power: Please refer to the tabel below Motor control: V/f, V/f+PG, SLV, SLV2, SV, PMSV, PMSLV Nominal current: Please refer to the table below Nominal apparent power: Please refer to the table below Maximum operating temperature: 40℃ for IP20
50℃ for IP00 or top anti-dust cover removed
Frame 5 is 50℃, which is IP20 level
CDM losses and efficiency (calculated with default settings) point: As the picture right Manufacturer: TECO Electric & Machinery CO., LTD.-10F, No.3‐1, Park St., Nan‐Kang, Taipei, 115603, Taiwan
EU contact: MOTOVARIO S.p.A-Via Quattro Passi 1/3-41043-Formigine (MO)-ITALY. MOTOVARIO EORI number: IT02569681204
CDM operating point diagram: vertical axis CDM relative Torque producing current %, ticks 25, 50, 100; horizontal axis CDM relative Motor stator frequency %, ticks 25, 50, 90, 100. Numbered points printed: 1 CDM (90,100); 2 CDM (50,100); 3 CDM (0,100); 4 CDM (90,50); 5 CDM (50,50); 6 CDM (0,50); 7 CDM (50,25); 8 CDM (0,25); 9 CDM (0,0) Standby; 10 CDM (100,100). No values interpolated from lines.
Coordinates are displayed landscape PDF page coordinates after90-degree source page rotation; independent Poppler bounding boxes use this same orientation.
Manual — CDM losses and efficiency by model and operating point — page 673
Manual reference: physical PDF page 673. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
CDM losses and efficiency table
Coordinates are displayed landscape PDF page coordinates after90-degree source page rotation; independent Poppler bounding boxes use this same orientation.
Left and right original table rows have matched source vertical bounds. Right-side data fields carry the original left-row model/rating context; no value is joined by model-name similarity. The blank top-left decorative strip and220V section divider contain no model values.
CDM losses and efficiency by model and operating point
CDM model ratings; original left block — PDF page 673
| Source row | Frame | Model Name | Nominal voltage (V) | Nominal current (A) | Nominal power (kW) | Nominal apparent power (KVA) |
|---|---|---|---|---|---|---|
| 1 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 2 | Frame | Model Name | Nominal voltage (V) | Nominal current (A) | Nominal power (kW) | Nominal apparent power (KVA) |
| 3 | 380V Class | 380V Class | 380V Class | 380V Class | 380V Class | 380V Class |
| 4 | 1 | A510-4001-S□3(F) | 380 | 3.4 | 0.75 | 2.6 |
| 5 | 1 | A510-4002-S□3(F) | 380 | 4.2 | 1.5 | 3.2 |
| 6 | 1 | A510-4003-S□3(F) | 380 | 5.5 | 2.2 | 4.2 |
| 7 | 2 | A510-4005-S□3(F) | 380 | 9.2 | 3.7 | 7 |
| 8 | 2 | A510-4008-S□3(F) | 380 | 14.8 | 5.5 | 11.3 |
| 9 | 3 | A510-4010-S□3(F) | 380 | 18 | 7.5 | 13.7 |
| 10 | 3 | A510-4015-S□3(F) | 380 | 24 | 11 | 18.3 |
| 11 | 4 | A510-4020-S□3(F) | 380 | 31 | 15 | 23.6 |
| 12 | 4 | A510-4025-S□3(F) | 380 | 39 | 18.5 | 29.7 |
| 13 | 4 | A510-4030-S□3(F) | 380 | 45 | 22 | 34.3 |
| 14 | 5 | A510-4040-S□3(F) | 380 | 60 | 30 | 45.7 |
| 15 | 5 | A510-4040-S□3(F)-B | 380 | 60 | 30 | 45.7 |
| 16 | 5 | A510-4050-S□3(F) | 380 | 75 | 37 | 57.2 |
| 17 | 5 | A510-4060-S□3(F) | 380 | 91 | 45 | 69.3 |
| 18 | 5 | A510-4075-S□3 | 380 | 118 | 55 | 89.9 |
| 19 | 6 | A510-4100-S□3 | 380 | 150 | 75 | 114 |
| 20 | 6 | A510-4125-S□3 | 380 | 180 | 90 | 137 |
| 21 | 7 | A510-4150-S□3 | 380 | 216 | 110 | 165 |
| 22 | 7 | A510-4175-S□3 | 380 | 260 | 132 | 198 |
| 23 | 7 | A510-4215-S□3 | 380 | 295 | 160 | 225 |
| 24 | 8 | A510-4215-S□3H | 380 | 330 | 160 | 251 |
| 25 | 8 | A510-4270-S□3 | 380 | 380 | 200 | 290 |
| 26 | 8 | A510-4300-S□3 | 380 | 450 | 220 | 343 |
| 27 | 8 | A510-4375-S□3 | 380 | 523 | 280 | 400 |
| 28 | 8 | A510-4425-S□3 | 380 | 585 | 315 | 461 |
| 29 | 220V Class | 220V Class | 220V Class | 220V Class | 220V Class | 220V Class |
| 30 | 1 | A510-2001-S□ | 220 | 5 | 0.75 | 1.9 |
| 31 | 1 | A510-2002-S□ | 220 | 8 | 1.5 | 3 |
| 32 | 2 | A510-2003-S□ | 220 | 11 | 2.2 | 4.2 |
| 33 | 2 | A510-2005-S□3 | 220 | 17.5 | 3.7 | 6.7 |
| 34 | 2 | A510-2008-S□3 | 220 | 25 | 5.5 | 9.5 |
| 35 | 3 | A510-2010-S□3 | 220 | 33 | 7.5 | 12.6 |
| 36 | 4 | A510-2015-S□3 | 220 | 47 | 11 | 17.9 |
| 37 | 4 | A510-2020-S□3 | 220 | 60 | 15 | 22.9 |
| 38 | 4 | A510-2025-S□3 | 220 | 73 | 18.5 | 27.8 |
| 39 | 5 | A510-2030-S□3 | 220 | 85 | 22 | 32.4 |
| 40 | 5 | A510-2040-S□3 | 220 | 115 | 30 | 43.8 |
| 41 | 6 | A510-2050-S□3 | 220 | 145 | 37 | 55.3 |
| 42 | 6 | A510-2060-S□3 | 220 | 180 | 45 | 68.6 |
| 43 | 7 | A510-2075-S□3 | 220 | 215 | 55 | 81.9 |
| 44 | 7 | A510-2100-S□3 | 220 | 283 | 75 | 108 |
| 45 | 8 | A510-2125-S□3 | 220 | 346 | 90 | 132 |
| 46 | 8 | A510-2150-S□3 | 220 | 415 | 110 | 158 |
CDM losses and efficiency; original right block — PDF page 673
| Source row | ❾ / CDM STANDBY LOSS / p Loss(W) | ❽ / CDM (0,25) / p Loss(W) | ❽ / CDM (0,25) / η(%) | ❻ / CDM (0,50) / p Loss(W) | ❻ / CDM (0,50) / η(%) | ❸ / CDM (0,100) / p Loss(W) | ❸ / CDM (0,100) / η(%) | ❼ / CDM (50,25) / p Loss(W) | ❼ / CDM (50,25) / η(%) | ❺ / CDM (50,50) / p Loss(W) | ❺ / CDM (50,50) / η(%) | ❷ / CDM (50,100) / p Loss(W) | ❷ / CDM (50,100) / η(%) | ❹ / CDM (90,50) / p Loss(W) | ❹ / CDM (90,50) / η(%) | ❶ / CDM (90,100) / p Loss(W) | ❶ / CDM (90,100) / η(%) | ❿ / CDM (100,100) / p Loss(W) | ❿ / CDM (100,100) / η(%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | ❾ | ❽ | ❽ | ❻ | ❻ | ❸ | ❸ | ❼ | ❼ | ❺ | ❺ | ❷ | ❷ | ❹ | ❹ | ❶ | ❶ | ❿ | ❿ |
| 2 | CDM STANDBY LOSS | CDM (0,25) | CDM (0,25) | CDM (0,50) | CDM (0,50) | CDM (0,100) | CDM (0,100) | CDM (50,25) | CDM (50,25) | CDM (50,50) | CDM (50,50) | CDM (50,100) | CDM (50,100) | CDM (90,50) | CDM (90,50) | CDM (90,100) | CDM (90,100) | CDM (100,100) | CDM (100,100) |
| 3 | p Loss(W) | p Loss(W) | η(%) | p Loss(W) | η(%) | p Loss(W) | η(%) | p Loss(W) | η(%) | p Loss(W) | η(%) | p Loss(W) | η(%) | p Loss(W) | η(%) | p Loss(W) | η(%) | p Loss(W) | η(%) |
| 4 | 14 | 2 | 0.0 | 2 | 0.0 | 95 | 0.0 | 23 | 93.1 | 30 | 93.8 | 40 | 94.1 | 30 | 95.5 | 44 | 95.6 | 45 | 95.9 |
| 5 | 14 | 2 | 0.0 | 2 | 0.0 | 95 | 0.0 | 28 | 93.2 | 35 | 93.9 | 46 | 94.1 | 35 | 95.7 | 53 | 95.8 | 55 | 96.0 |
| 6 | 20 | 2 | 0.0 | 2 | 0.0 | 95 | 0.0 | 47 | 93.4 | 57 | 94.1 | 72 | 94.4 | 60 | 95.9 | 77 | 95.9 | 78 | 96.2 |
| 7 | 23 | 2 | 0.0 | 2 | 0.0 | 96 | 0.0 | 77 | 94.1 | 92 | 94.8 | 160 | 95.1 | 117 | 96.1 | 170 | 96.2 | 190 | 96.4 |
| 8 | 23 | 2 | 0.0 | 2 | 0.0 | 97 | 0.0 | 93 | 94.6 | 119 | 95.2 | 220 | 95.5 | 140 | 96.7 | 230 | 96.8 | 240 | 97.3 |
| 9 | 33 | 2 | 0.0 | 2 | 0.0 | 97 | 0.0 | 109 | 94.9 | 137 | 95.6 | 240 | 95.8 | 147 | 97.2 | 260 | 97.3 | 260 | 97.5 |
| 10 | 33 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 129 | 94.8 | 164 | 95.5 | 301 | 95.8 | 168 | 97.3 | 348 | 97.4 | 404 | 97.6 |
| 11 | 35 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 174 | 95.0 | 216 | 95.7 | 370 | 96.1 | 220 | 97.4 | 420 | 97.5 | 430 | 97.7 |
| 12 | 35 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 239 | 94.9 | 264 | 96.0 | 450 | 96.3 | 282 | 97.5 | 510 | 97.6 | 520 | 97.7 |
| 13 | 35 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 279 | 94.8 | 313 | 96.0 | 555 | 96.3 | 338 | 97.5 | 605 | 97.5 | 605 | 97.8 |
| 14 | 40 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 343 | 94.8 | 388 | 96.0 | 690 | 96.3 | 396 | 97.6 | 740 | 97.6 | 740 | 97.9 |
| 15 | 40 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 343 | 94.8 | 388 | 96.0 | 690 | 96.3 | 396 | 97.6 | 740 | 97.6 | 740 | 97.9 |
| 16 | 40 | 10 | 0.0 | 10 | 0.0 | 104 | 0.0 | 511 | 93.6 | 630 | 94.8 | 1190 | 95.1 | 622 | 97.0 | 1350 | 97.0 | 1350 | 97.4 |
| 17 | 40 | 10 | 0.0 | 10 | 0.0 | 104 | 0.0 | 678 | 93.7 | 826 | 94.8 | 1380 | 95.1 | 786 | 97.1 | 1480 | 97.1 | 1480 | 97.5 |
| 18 | 40 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 725 | 94.6 | 954 | 95.3 | 1630 | 95.6 | 985 | 97.2 | 1650 | 97.3 | 1660 | 97.7 |
| 19 | 42 | 50 | 0.0 | 50 | 0.0 | 96 | 0.0 | 758 | 93.7 | 1060 | 95.3 | 1888 | 95.7 | 1139 | 97.1 | 2076 | 97.4 | 2130 | 97.6 |
| 20 | 42 | 50 | 0.0 | 50 | 0.0 | 144 | 0.0 | 900 | 93.7 | 1269 | 95.3 | 2293 | 95.7 | 1364 | 97.1 | 2526 | 97.3 | 2594 | 97.5 |
| 21 | 46 | 50 | 0.0 | 50 | 0.0 | 143 | 0.0 | 1160 | 93.3 | 1624 | 95.0 | 2894 | 95.5 | 1738 | 97.0 | 3165 | 97.2 | 3243 | 97.4 |
| 22 | 46 | 50 | 0.0 | 50 | 0.0 | 143 | 0.0 | 1388 | 93.3 | 1958 | 95.0 | 3531 | 95.4 | 3778 | 96.8 | 3858 | 97.2 | 3951 | 97.4 |
| 23 | 46 | 50 | 0.0 | 50 | 0.0 | 144 | 0.0 | 1321 | 94.3 | 1881 | 95.7 | 3457 | 96.0 | 2037 | 97.4 | 3827 | 97.5 | 3934 | 97.7 |
| 24 | 56 | 50 | 0.0 | 50 | 0.0 | 144 | 0.0 | 1474 | 94.4 | 2085 | 95.8 | 3780 | 96.1 | 2259 | 97.4 | 4194 | 97.6 | 4313 | 97.7 |
| 25 | 56 | 100 | 0.0 | 100 | 0.0 | 194 | 0.0 | 1740 | 94.2 | 2458 | 95.7 | 4464 | 96.0 | 2658 | 97.4 | 4267 | 97.9 | 5078 | 97.7 |
| 26 | 56 | 100 | 0.0 | 100 | 0.0 | 194 | 0.0 | 2191 | 93.9 | 3089 | 95.4 | 5559 | 95.8 | 3326 | 97.2 | 4946 | 97.9 | 6285 | 97.6 |
| 27 | 56 | 100 | 0.0 | 100 | 0.0 | 194 | 0.0 | 2538 | 93.9 | 3600 | 95.4 | 6546 | 95.8 | 3875 | 97.2 | 5961 | 97.8 | 7391 | 97.6 |
| 28 | 56 | 100 | 0.0 | 100 | 0.0 | 195 | 0.0 | 2339 | 94.9 | 3355 | 96.2 | 6225 | 96.4 | 3663 | 97.6 | 6410 | 97.9 | 7170 | 97.9 |
| 29 | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ | ⟦blank source cell⟧ |
| 30 | 13 | 2 | 0.0 | 2 | 0.0 | 96 | 0.0 | 23 | 93.8 | 26 | 94.9 | 42 | 95.2 | 36 | 95.5 | 46 | 95.5 | 47 | 95.7 |
| 31 | 19 | 2 | 0.0 | 2 | 0.0 | 95 | 0.0 | 40 | 93.4 | 49 | 94.1 | 54 | 94.3 | 53 | 95.8 | 58 | 95.8 | 60 | 96.0 |
| 32 | 19 | 2 | 0.0 | 2 | 0.0 | 96 | 0.0 | 61 | 94.0 | 72 | 94.6 | 88 | 94.9 | 82 | 96.0 | 89 | 96.0 | 90 | 96.2 |
| 33 | 20 | 2 | 0.0 | 2 | 0.0 | 96 | 0.0 | 95 | 94.1 | 112 | 94.8 | 115 | 95.1 | 133 | 96.3 | 120 | 96.4 | 122 | 96.5 |
| 34 | 30 | 2 | 0.0 | 2 | 0.0 | 96 | 0.0 | 135 | 94.1 | 159 | 94.8 | 162 | 95.1 | 180 | 96.5 | 169 | 96.6 | 185 | 96.6 |
| 35 | 30 | 2 | 0.0 | 2 | 0.0 | 96 | 0.0 | 144 | 93.9 | 186 | 94.6 | 285 | 94.9 | 189 | 96.7 | 291 | 96.8 | 310 | 97.0 |
| 36 | 30 | 10 | 0.0 | 10 | 0.0 | 104 | 0.0 | 170 | 93.9 | 223 | 94.6 | 385 | 94.8 | 259 | 96.6 | 425 | 96.6 | 435 | 96.9 |
| 37 | 31 | 10 | 0.0 | 10 | 0.0 | 104 | 0.0 | 215 | 94.1 | 281 | 94.7 | 465 | 95.0 | 313 | 96.7 | 495 | 96.8 | 525 | 97.0 |
| 38 | 32 | 10 | 0.0 | 10 | 0.0 | 104 | 0.0 | 284 | 94.1 | 408 | 94.3 | 692 | 94.4 | 465 | 96.2 | 758 | 96.3 | 758 | 96.7 |
| 39 | 35 | 10 | 0.0 | 10 | 0.0 | 104 | 0.0 | 335 | 94.4 | 478 | 94.6 | 855 | 94.7 | 504 | 96.6 | 865 | 96.7 | 875 | 97.1 |
| 40 | 35 | 10 | 0.0 | 10 | 0.0 | 105 | 0.0 | 422 | 94.9 | 598 | 95.1 | 1035 | 95.2 | 656 | 96.8 | 1095 | 96.9 | 1125 | 97.0 |
| 41 | 36 | 50 | 0.0 | 50 | 0.0 | 143 | 0.0 | 469 | 93.0 | 655 | 94.8 | 1167 | 95.3 | 732 | 96.7 | 1164 | 97.4 | 1401 | 97.1 |
| 42 | 36 | 50 | 0.0 | 50 | 0.0 | 143 | 0.0 | 571 | 93.2 | 809 | 94.9 | 1473 | 95.2 | 904 | 96.7 | 1453 | 97.4 | 1764 | 97.1 |
| 43 | 46 | 50 | 0.0 | 50 | 0.0 | 143 | 0.0 | 663 | 93.0 | 935 | 95.0 | 1695 | 95.4 | 1048 | 96.8 | 1567 | 97.6 | 2042 | 97.2 |
| 44 | 46 | 50 | 0.0 | 50 | 0.0 | 143 | 0.0 | 859 | 93.4 | 1234 | 95.0 | 2304 | 95.3 | 1383 | 96.8 | 2031 | 97.6 | 2761 | 97.1 |
| 45 | 56 | 100 | 0.0 | 100 | 0.0 | 193 | 0.0 | 1089 | 93.2 | 1532 | 94.9 | 2768 | 95.4 | 1714 | 96.8 | 3202 | 97.0 | 3326 | 97.2 |
| 46 | 56 | 100 | 0.0 | 100 | 0.0 | 193 | 0.0 | 1253 | 93.5 | 1776 | 95.1 | 3231 | 95.5 | 1995 | 96.9 | 3752 | 97.0 | 3901 | 97.2 |
Manual — Manufacturer contacts and edition — page 674
Manual reference: physical PDF page 674. Read the complete procedure and adjacent-page conditions in the original; model and firmware applicability must be confirmed.
TECO Electric & Machinery Co., Ltd.
This manual may be modified when necessary because of improvement of the product, modification, or changes in specifications. This manual is subject to change without notice.
Historical contacts, no current validity asserted. Distributor blank. QR decoded twice locally to http://globalsa.teco.com.tw, different from printed http://industrialproducts.teco.com.tw/. Both retained; no fetch.
A510sbackcover, notF510orE510sedition.
Two local decodes at distinct scales agree; printedURL differs. No destination or currency validation.
Printed contact and edition information — PDF page 674
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Address | 10F., No.3-1, Yuancyu St., Nangang District, Taipei City115, Taiwan |
| 2 | Tel | +886-2-6615-9111 |
| 3 | Fax | +886-2-6615-0933 |
| 4 | Web | http://industrialproducts.teco.com.tw/ |
| 5 | Manual number | 4KA72X583T61 |
| 6 | Version | 10 |
| 7 | Date | 2021.06 |
| 8 | Distributor | [blank in source] |
QR code payload — PDF page 674
| Source row | Source label/context | Decoded payload |
|---|---|---|
| 1 | QR code | http://globalsa.teco.com.tw |
Quick setup guide — guide-SRC-d451e793ce817fcf-teco-a510s-enhanced-quick-set-up-guide-p0001-0002
Source edition: TECO-A510s-Enhanced-Quick-Set-up-Guide.pdf. Source key: SRC-d451e793ce817fcf. Collected product associations: P001. These attachments do not establish applicability of every model or instruction to every linked product.
Supplier source reference(s):
- Original supplier document/archive — TECO-A510s-Enhanced-Quick-Set-up-Guide.pdf
Use the instructions, warnings, model/voltage/duty conditions and safety requirements of this complete source edition together. Historical dates, contact information and certification statements are preserved as source claims, not confirmation of current validity. Diagram geometry remains in the original document; descriptions do not reconstruct wiring. Navigation headings may combine source words with organisational context and are not uniformly verbatim supplier quotations.
Editorial note: source prose, reviewed tables and bounded diagram-label descriptions are presented together, with their roles identified. Paragraph line wrapping and bullet formatting are normalized. Source wording, source contradictions and edition-specific contacts are retained. References are editorial and do not establish wiring topology.
TECO A510s Enhanced - QUICK SET-UP GUIDE
This is a quick set-up guide for configuring the TECO E510s for either of the following control requirements:
Motor Parameter Setup
Start/stop control – Keypad, External Switch or PLC
Wiring Diagram - 2-wire & 3 wire start/ stop operation
Speed/frequency control – Keypad, Pot on Keypad, External Pot.
Highlighted in the table below are the main parameter groups that are involved in this list of control requirements.
The visible introduction names TECO E510s although this source is titled A510s Enhanced. Both strings are preserved; this is not evidence of cross-product applicability.
Source table (SRC-d451e793ce817fcf-SS17-P1-T1). Generic column labels below are editorial; the first data row retains the supplier headings.
Short Press DSP/FUN to change to Parameter Group
Press ▼ Twice
Cursor Movement: </RESET to move across, Up: ▲ Down: ▼
Short Press READ/ENTER, press DSP/FUN
Source labels and bounded description (SRC-d451e793ce817fcf-F0049; PDF 1):
Motor parameter group02: -01 Motor Rated Current(A); -03 Motor Rated Speed(RPM); -05 Motor Rated Power(kW); -06 Motor Rated Frequency(Hz). Short press DSP/FUN to select group; press down twice to02; </RESET cursor; READ/ENTER then DSP/FUN per shown flow.
Original drawing geometry remains authoritative. This description does not reconstruct wiring connections.
Short Press READ/ENTER
Source labels and bounded description (SRC-d451e793ce817fcf-F0050; PDF 1):
Group00 /00-02: Keypad0; External Switch1 (Default); Communication2. Labels0DigitalOp,1Terminal,2RS-485Comm; short READ/ENTER.
For additional support, please contact us at:
TECO VSD Tech Support: 02 9765 8183
Email Address: emdproduct@teco.com.au
Page - 1
together, we empower the Future
Applicable when
Source labels and bounded description (SRC-d451e793ce817fcf-F0051; PDF 2):
Group00 Basic Func / -02RUNSource =1Terminal.
Two external switches are required, one for forward direction and the other for reverse.
Switch type: two positions, maintained type.
Wiring Diagram:
Source labels and bounded description (SRC-d451e793ce817fcf-F0052; PDF 2):
Heading says Forward/Stop – Reverse/Stop(Default), but figure labels S1(RUN/STOP), S2(REV/FWD),24V and SW6 Source(PNP)/Sink(NPN). Keep heading/figure mismatch unresolved.
The heading states Forward/Stop – Reverse/Stop (Default); its figure instead labels S1 (RUN/STOP) and S2 (REV/FWD). Both are retained. No inferred correction or wiring topology is supplied.
In this mode, two separated momentary push buttons are used for start and stop functions.
For S1 to initiate the Run command. Push button connected to S2 must be connected by a normally closed type contact (NC).
Parameter Setup: Initialize the 3-Wire.
Source labels and bounded description (SRC-d451e793ce817fcf-F0053; PDF 2):
13 Drive Status / -08Initialize =005 3-Wire,230V/415V(50Hz). S1(RUN),S2(STOP),S3(FWD/REV),24V; SW6 Source(PNP)/Sink(NPN). Prose requires S2 normally closed contact.
Parameter Setup
Source labels and bounded description (SRC-d451e793ce817fcf-F0054; PDF 2):
00 Basic Func / -05FreqSource: Keypad(Default)=0DigitalOp; External Terminal(2KΩPot)=1Analog; CommunicationControl=3RS-485Comm. Keypad operation example12-16=005.00Hz;12-17=000.00Hz;12-18=0000.0A; source illustration, not recommended operating values.
Cursor Movement: </RESET to move across, Up: ▲ Down: ▼ to set the Frequency Reference Value.
Source labels and bounded description (SRC-d451e793ce817fcf-F0055; PDF 2):
-05FreqSource=1Analog;2kΩ potentiometer; +10V;AI1 MainSpeed FrequencyReferenceCommand(VoltageInput);AI2 MainSpeed FrequencyReferenceCommand(CurrentInput);GND;-10V;AI1/SW3 andAI2/SW4 V/I switches. Original wiring geometry authoritative.
Page - 2
The product photograph contains tiny label or nameplate text that has not been transcribed. The original PDF is preserved. Source wording and historical contacts are retained without a claim of current applicability or contact validity.
Parameter groups — PDF page 1
| Source column 1 | Source column 2 |
|---|---|
| PARAMENTER GROUP No. | Description |
| Group 00 | Basic parameter |
| Group 01 | V/F Control parameters |
| Group 02 | IM Motor parameters |
| Group 03 | External digital input and output parameters |
| Group 04 | External analog input and output parameters |
| Group 05 | Multi speed parameters |
| Group 06 | Automatic program operation parameters |
| Group 07 | Start/Stop parameters |
| Group 08 | Protection parameters |
| Group 09 | Communication parameters |
| Group 10 | PID parameters |
| Group 11 | Auxiliary parameters |
| Group 12 | Monitoring parameters |
| Group 13 | Maintenance parameters |
| Group 14 | PLC parameters |
| Group 15 | PLC monitoring parameters |
| Group 16 | LCD parameters |
| Group 17 | Automatic Tuning Parameters |
| Group 18 | Slip compensation parameters |
| Group 19 | Wobble frequency parameters |
| Group 20 | Speed control parameters |
| Group 21 | Torque and position control parameters |
| Group 22 | PM Motor Paramenter |
Technical source 001 — Variable speed drive A510-4001-SG3F-IP20, 0.75KW, 1HP, 380-460V
Source download: DataSheet_of_A510-4001-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4001-SG3F-IP20, 0.75KW, 1HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 1 / 1 | Constant Torque (kW/A): 0.75 / 3.4; Variable Torque (kW/A): 1.5 / 4.1; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 0.75 | Datasheet PDF / DataSheet_of_A510-4001-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4001-SG3F-IP20, 0.75KW, 1HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 1 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 2.6 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 3.4 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 1 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 0.75 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 3.1 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 4.1 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 2 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 1.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4001-SG3F-IP20, 0.75KW, 1HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4001-SG3F-IP20, 0.75KW, 1HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4001-SG3F-IP20, 0.75KW, 1HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4001-SG3F-IP20, 0.75KW, 1HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4001-SG3F | 130 (5.12) mm (inch) | 306 (12.05 ) mm (inch) | 150 (5.91) mm (inch) | 118 (4.65) mm (inch) | 203 (7.99) mm (inch) | 215 (8.46) mm (inch) | 5 (0.20) mm (inch) | M5 mm (inch) | 3.5 (7.71) kg (lbs) | — |
Technical source 002 — Variable speed drive A510-4001-SC3F-IP20, 0.75KW, 1HP, 380-460V
Source download: datasheet-135.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4001-SC3F-IP20, 0.75KW, 1HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 1 / 1 | Constant Torque (kW/A): 0.75 / 3.4; Variable Torque (kW/A): 1.5 / 4.1; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 0.75 | Drawing PDF / datasheet-135.pdf |
P001 / Variable speed drive A510-4001-SC3F-IP20, 0.75KW, 1HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 1 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 2.6 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 3.4 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 1 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 0.75 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 3.1 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 4.1 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 2 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 1.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4001-SC3F-IP20, 0.75KW, 1HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4001-SC3F-IP20, 0.75KW, 1HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4001-SC3F-IP20, 0.75KW, 1HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4001-SC3F | 130 (5.12) mm (inch) | 306 (12.05) mm (inch) | 150 (5.91) mm (inch) | 118 (4.65) mm (inch) | 203 (7.99) mm (inch) | 215 (8.46) mm (inch) | 5 (0.20) mm (inch) | M5 mm (inch) | 3.5 (7.71) kg (lbs) | — |
Technical source 003 — Variable speed drive A510-4002-SG3F-IP20, 1.5KW, 2HP, 380-460V
Source download: DataSheet_of_A510-4002-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4002-SG3F-IP20, 1.5KW, 2HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 2 / 2 | Constant Torque (kW/A): 1.5 / 4.2; Variable Torque (kW/A): 2.2 / 5.4; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 1.50 | Datasheet PDF / DataSheet_of_A510-4002-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4002-SG3F-IP20, 1.5KW, 2HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 3.2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 4.2 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 2 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 1.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 4.1 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 5.4 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 3 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 2.2 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4002-SG3F-IP20, 1.5KW, 2HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4002-SG3F-IP20, 1.5KW, 2HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4002-SG3F-IP20, 1.5KW, 2HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4002-SG3F-IP20, 1.5KW, 2HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4002-SG3F | 130 (5.12) mm (inch) | 306 (12.05 ) mm (inch) | 150 (5.91) mm (inch) | 118 (4.65) mm (inch) | 203 (7.99) mm (inch) | 215 (8.46) mm (inch) | 5 (0.20) mm (inch) | M5 mm (inch) | 3.5 (7.71) kg (lbs) | — |
Technical source 004 — Variable speed drive A510-4002-SC3F-IP20, 1.5KW, 2HP, 380-460V
Source download: datasheet-136.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4002-SC3F-IP20, 1.5KW, 2HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 2 / 2 | Constant Torque (kW/A): 1.5 / 4.2; Variable Torque (kW/A): 2.2 / 5.4; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 1.50 | Drawing PDF / datasheet-136.pdf |
P001 / Variable speed drive A510-4002-SC3F-IP20, 1.5KW, 2HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 3.2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 4.2 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 2 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 1.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 4.1 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 5.4 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 3 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 2.2 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4002-SC3F-IP20, 1.5KW, 2HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4002-SC3F-IP20, 1.5KW, 2HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4002-SC3F-IP20, 1.5KW, 2HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4002-SC3F | 130 (5.12) mm (inch) | 306 (12.05) mm (inch) | 150 (5.91) mm (inch) | 118 (4.65) mm (inch) | 203 (7.99) mm (inch) | 215 (8.46) mm (inch) | 5 (0.20) mm (inch) | M5 mm (inch) | 3.5 (7.71) kg (lbs) | — |
Technical source 005 — Variable speed drive A510-4003-SG3F-IP20, 2.2KW, 3HP, 380-460V
Source download: DataSheet_of_A510-4003-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4003-SG3F-IP20, 2.2KW, 3HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 3 / 3 | Constant Torque (kW/A): 2.2 / 5.5; Variable Torque (kW/A): 3.7 / 6.9; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 2.20 | Datasheet PDF / DataSheet_of_A510-4003-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4003-SG3F-IP20, 2.2KW, 3HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 4.2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 5.5 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 3 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 2.2 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 5.3 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 6.9 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 5 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 3.7 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4003-SG3F-IP20, 2.2KW, 3HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4003-SG3F-IP20, 2.2KW, 3HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4003-SG3F-IP20, 2.2KW, 3HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4003-SG3F-IP20, 2.2KW, 3HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4003-SG3F | 130 (5.12) mm (inch) | 306 (12.05 ) mm (inch) | 150 (5.91) mm (inch) | 118 (4.65) mm (inch) | 203 (7.99) mm (inch) | 215 (8.46) mm (inch) | 5 (0.20) mm (inch) | M5 mm (inch) | 3.5 (7.71) kg (lbs) | — |
Technical source 006 — Variable speed drive A510-4003-SC3F-IP20, 2.2KW, 3HP, 380-460V
Source download: datasheet-137.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4003-SC3F-IP20, 2.2KW, 3HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 3 / 3 | Constant Torque (kW/A): 2.2 / 5.5; Variable Torque (kW/A): 3.7 / 6.9; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 2.20 | Drawing PDF / datasheet-137.pdf |
P001 / Variable speed drive A510-4003-SC3F-IP20, 2.2KW, 3HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 4.2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 5.5 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 3 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 2.2 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 5.3 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 6.9 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 5 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 3.7 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4003-SC3F-IP20, 2.2KW, 3HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4003-SC3F-IP20, 2.2KW, 3HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4003-SC3F-IP20, 2.2KW, 3HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4003-SC3F | 130 (5.12) mm (inch) | 306 (12.05) mm (inch) | 150 (5.91) mm (inch) | 118 (4.65) mm (inch) | 203 (7.99) mm (inch) | 215 (8.46) mm (inch) | 5 (0.20) mm (inch) | M5 mm (inch) | 3.5 (7.71) kg (lbs) | — |
Technical source 007 — Variable speed drive A510-4005-SG3F-IP20, 4KW, 5HP, 380-460V
Source download: DataSheet_of_A510-4005-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4005-SG3F-IP20, 4KW, 5HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 4 / 4 | Constant Torque (kW/A): 3.7 / 9.2; Variable Torque (kW/A): 5.5 / 12.1; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 3.70 | Datasheet PDF / DataSheet_of_A510-4005-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4005-SG3F-IP20, 4KW, 5HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 5 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 7 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 9.2 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 5 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 3.7 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 9.2 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 12.1 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 7.5 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 5.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4005-SG3F-IP20, 4KW, 5HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4005-SG3F-IP20, 4KW, 5HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4005-SG3F-IP20, 4KW, 5HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4005-SG3F-IP20, 4KW, 5HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4005-SG3F | 140 (5.51) mm (inch) | 385.5 (15.18 ) mm (inch) | 181 (7.13) mm (inch) | 122 (4.80) mm (inch) | 267 (10.51 ) mm (inch) | 279 (10.98 ) mm (inch) | 1.2 (0.05) mm (inch) | M6 mm (inch) | 5.5 (12.13 ) kg (lbs) | — |
Technical source 008 — Variable speed drive A510-4005-SC3F-IP20, 3.7KW, 5HP, 380-460V
Source download: datasheet-138.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4005-SC3F-IP20, 3.7KW, 5HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 4 / 4 | Constant Torque (kW/A): 3.7 / 9.2; Variable Torque (kW/A): 5.5 / 12.1; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 3.70 | Drawing PDF / datasheet-138.pdf |
P001 / Variable speed drive A510-4005-SC3F-IP20, 3.7KW, 5HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 5 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 7 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 9.2 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 5 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 3.7 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 9.2 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 12.1 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 7.5 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 5.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4005-SC3F-IP20, 3.7KW, 5HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4005-SC3F-IP20, 3.7KW, 5HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4005-SC3F-IP20, 3.7KW, 5HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4005-SC3F | 140 (5.51) mm (inch) | 400 (15.75) mm (inch) | 177 (6.97) mm (inch) | 122 (4.80) mm (inch) | 267 (10.51) mm (inch) | 279 (10.98) mm (inch) | 7 mm (inch) | M6 mm (inch) | 5.5 (12.13) kg (lbs) | — |
Technical source 009 — Variable speed drive A510-4008-SG3F-IP20, 5.5KW, 7.5HP, 380-460V
Source download: DataSheet_of_A510-4008-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4008-SG3F-IP20, 5.5KW, 7.5HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 5 / 5 | Constant Torque (kW/A): 5.5 / 14.8; Variable Torque (kW/A): 7.5 / 17.5; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 5.50 | Datasheet PDF / DataSheet_of_A510-4008-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4008-SG3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 7.5 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 11.3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 14.8 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 7.5 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 5.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 13.3 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 17.5 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 10 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 7.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4008-SG3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4008-SG3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4008-SG3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4008-SG3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4008-SG3F | 140 (5.51) mm (inch) | 385.5 (15.18 ) mm (inch) | 181 (7.13) mm (inch) | 122 (4.80) mm (inch) | 267 (10.51 ) mm (inch) | 279 (10.98 ) mm (inch) | 1.2 (0.05) mm (inch) | M6 mm (inch) | 5.5 (12.13 ) kg (lbs) | — |
Technical source 010 — Variable speed drive A510-4008-SC3F-IP20, 5.5KW, 7.5HP, 380-460V
Source download: datasheet-139.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4008-SC3F-IP20, 5.5KW, 7.5HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 5 / 5 | Constant Torque (kW/A): 5.5 / 14.8; Variable Torque (kW/A): 7.5 / 17.5; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 5.50 | Drawing PDF / datasheet-139.pdf |
P001 / Variable speed drive A510-4008-SC3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 7.5 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 11.3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 14.8 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 7.5 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 5.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 13.3 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 17.5 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 10 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 7.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4008-SC3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4008-SC3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4008-SC3F-IP20, 5.5KW, 7.5HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4008-SC3F | 140 (5.51) mm (inch) | 400 (15.75) mm (inch) | 177 (6.97) mm (inch) | 122 (4.80) mm (inch) | 267 (10.51) mm (inch) | 279 (10.98) mm (inch) | 7 mm (inch) | M6 mm (inch) | 5.5 (12.13) kg (lbs) | — |
Technical source 011 — Variable speed drive A510-4010-SG3F-IP20, 7.5KW, 10HP, 380-460V
Source download: DataSheet_of_A510-4010-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4010-SG3F-IP20, 7.5KW, 10HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 6 / 6 | Constant Torque (kW/A): 7.5 / 18; Variable Torque (kW/A): 11 / 23; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 7.50 | Datasheet PDF / DataSheet_of_A510-4010-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4010-SG3F-IP20, 7.5KW, 10HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 10 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 13.7 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 18 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 10 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 7.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 17.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 23 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 15 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 11 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4010-SG3F-IP20, 7.5KW, 10HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4010-SG3F-IP20, 7.5KW, 10HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4010-SG3F-IP20, 7.5KW, 10HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4010-SG3F-IP20, 7.5KW, 10HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4010-SG3F | 210 (8.27) mm (inch) | 416.5 (16.40 ) mm (inch) | 215 (8.46) mm (inch) | 192 (7.56) mm (inch) | 286 (11.26 ) mm (inch) | 300 (11.81 ) mm (inch) | 1.6 (0.06) mm (inch) | M6 mm (inch) | 8.0 (17.64 ) kg (lbs) | — |
Technical source 012 — Variable speed drive A510-4010-SC3F-IP20, 7.5KW, 10HP, 380-460V
Source download: datasheet-140.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4010-SC3F-IP20, 7.5KW, 10HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 6 / 6 | Constant Torque (kW/A): 7.5 / 18; Variable Torque (kW/A): 11 / 23; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 7.50 | Drawing PDF / datasheet-140.pdf |
P001 / Variable speed drive A510-4010-SC3F-IP20, 7.5KW, 10HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 10 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 13.7 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 18 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 10 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 7.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 17.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 23 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 15 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 11 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4010-SC3F-IP20, 7.5KW, 10HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4010-SC3F-IP20, 7.5KW, 10HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4010-SC3F-IP20, 7.5KW, 10HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4010-SC3F | 210 (8.27) mm (inch) | 416.5 (16.40) mm (inch) | 215 (8.46) mm (inch) | 192 (7.56) mm (inch) | 286 (11.26) mm (inch) | 300 (11.81) mm (inch) | 1.6 mm (inch) | M6 mm (inch) | 8.0 (17.64) kg (lbs) | — |
Technical source 013 — Variable speed drive A510-4015-SG3F-IP20, 11KW, 15HP, 380-460V
Source download: DataSheet_of_A510-4015-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4015-SG3F-IP20, 11KW, 15HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 7 / 7 | Constant Torque (kW/A): 11 / 24; Variable Torque (kW/A): 15 / 31; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 11.00 | Datasheet PDF / DataSheet_of_A510-4015-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4015-SG3F-IP20, 11KW, 15HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 15 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 18.3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 24 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 15 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 11 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 23.6 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 31 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 20 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 15 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4015-SG3F-IP20, 11KW, 15HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4015-SG3F-IP20, 11KW, 15HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4015-SG3F-IP20, 11KW, 15HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4015-SG3F-IP20, 11KW, 15HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4015-SG3F | 210 (8.27) mm (inch) | 416.5 (16.40 ) mm (inch) | 215 (8.46) mm (inch) | 192 (7.56) mm (inch) | 286 (11.26 ) mm (inch) | 300 (11.81 ) mm (inch) | 1.6 (0.06) mm (inch) | M6 mm (inch) | 8.0 (17.64 ) kg (lbs) | — |
Technical source 014 — Variable speed drive A510-4015-SC3F-IP20, 11KW, 15HP, 380-460V
Source download: datasheet-141.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4015-SC3F-IP20, 11KW, 15HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 7 / 7 | Constant Torque (kW/A): 11 / 24; Variable Torque (kW/A): 15 / 31; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 11.00 | Drawing PDF / datasheet-141.pdf |
P001 / Variable speed drive A510-4015-SC3F-IP20, 11KW, 15HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 15 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 18.3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 24 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 15 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 11 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 23.6 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 31 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 20 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 15 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4015-SC3F-IP20, 11KW, 15HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4015-SC3F-IP20, 11KW, 15HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4015-SC3F-IP20, 11KW, 15HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4015-SC3F | 210 (8.27) mm (inch) | 416.5 (16.40) mm (inch) | 215 (8.46) mm (inch) | 192 (7.56) mm (inch) | 286 (11.26) mm (inch) | 300 (11.81) mm (inch) | 1.6 mm (inch) | M6 mm (inch) | 8.0 (17.64) kg (lbs) | — |
Technical source 015 — Variable speed drive A510-4020-SG3F-IP20, 15KW, 20HP, 380-460V
Source download: DataSheet_of_A510-4020-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4020-SG3F-IP20, 15KW, 20HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 8 / 8 | Constant Torque (kW/A): 15 / 31; Variable Torque (kW/A): 18.5 / 38; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 15.00 | Datasheet PDF / DataSheet_of_A510-4020-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4020-SG3F-IP20, 15KW, 20HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 20 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 23.6 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 31 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 20 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 15 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 29 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 38 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 25 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 18.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4020-SG3F-IP20, 15KW, 20HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4020-SG3F-IP20, 15KW, 20HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4020-SG3F-IP20, 15KW, 20HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4020-SG3F-IP20, 15KW, 20HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4020-SG3F | 265 (10.43) mm (inch) | 500 (19.69 ) mm (inch) | 225 (8.86) mm (inch) | 245 (9.65) mm (inch) | 340 (13.39 ) mm (inch) | 360 (14.17 ) mm (inch) | 1.6 (0.06) mm (inch) | M8 mm (inch) | 12.5 (27.56 ) kg (lbs) | — |
Technical source 016 — Variable speed drive A510-4020-SC3F-IP20, 15KW, 20HP, 380-460V
Source download: datasheet-142.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4020-SC3F-IP20, 15KW, 20HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 8 / 8 | Constant Torque (kW/A): 15 / 31; Variable Torque (kW/A): 18.5 / 38; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 15.00 | Drawing PDF / datasheet-142.pdf |
P001 / Variable speed drive A510-4020-SC3F-IP20, 15KW, 20HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 20 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 23.6 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 31 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 20 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 15 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 29 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 38 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 25 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 18.5 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4020-SC3F-IP20, 15KW, 20HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4020-SC3F-IP20, 15KW, 20HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4020-SC3F-IP20, 15KW, 20HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4020-SC3F | 265 (10.43) mm (inch) | 500 (19.69) mm (inch) | 225 (8.86) mm (inch) | 245 (9.65) mm (inch) | 340 (13.39) mm (inch) | 360 (14.17) mm (inch) | 1.6 mm (inch) | M8 mm (inch) | 12.5 (27.56) kg (lbs) | — |
Technical source 017 — Variable speed drive A510-4025-SG3F-IP20, 18.5KW, 25HP, 380-460V
Source download: DataSheet_of_A510-4025-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4025-SG3F-IP20, 18.5KW, 25HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 9 / 9 | Constant Torque (kW/A): 18.5 / 39; Variable Torque (kW/A): 22 / 44; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 18.50 | Datasheet PDF / DataSheet_of_A510-4025-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4025-SG3F-IP20, 18.5KW, 25HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 25 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 29.7 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 39 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 25 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 18.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 33.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 44 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 30 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 22 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4025-SG3F-IP20, 18.5KW, 25HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4025-SG3F-IP20, 18.5KW, 25HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4025-SG3F-IP20, 18.5KW, 25HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4025-SG3F-IP20, 18.5KW, 25HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4025-SG3F | 265 (10.43) mm (inch) | 500 (19.69 ) mm (inch) | 225 (8.86) mm (inch) | 245 (9.65) mm (inch) | 340 (13.39 ) mm (inch) | 360 (14.17 ) mm (inch) | 1.6 (0.06) mm (inch) | M8 mm (inch) | 12.5 (27.56 ) kg (lbs) | — |
Technical source 018 — Variable speed drive A510-4025-SC3F-IP20, 18.5KW, 25HP, 380-460V
Source download: datasheet-143.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4025-SC3F-IP20, 18.5KW, 25HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 9 / 9 | Constant Torque (kW/A): 18.5 / 39; Variable Torque (kW/A): 22 / 44; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 18.50 | Drawing PDF / datasheet-143.pdf |
P001 / Variable speed drive A510-4025-SC3F-IP20, 18.5KW, 25HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 25 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 29.7 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 39 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 25 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 18.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 33.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 44 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 30 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 22 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4025-SC3F-IP20, 18.5KW, 25HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4025-SC3F-IP20, 18.5KW, 25HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4025-SC3F-IP20, 18.5KW, 25HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4025-SC3F | 265 (10.43) mm (inch) | 500 (19.69) mm (inch) | 225 (8.86) mm (inch) | 245 (9.65) mm (inch) | 340 (13.39) mm (inch) | 360 (14.17) mm (inch) | 1.6 mm (inch) | M8 mm (inch) | 12.5 (27.56) kg (lbs) | — |
Technical source 019 — Variable speed drive A510-4040-SG3F-IP20, 30KW, 40HP, 380-460V
Source download: A510-4040-SG3F-IP20-datasheet.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4040-SG3F-IP20, 30KW, 40HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 10 / 10 | Constant Torque (kW/A): 30 / 60; Variable Torque (kW/A): 37 / 73; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 30.00 | Datasheet PDF / A510-4040-SG3F-IP20-datasheet.pdf |
P001 / Variable speed drive A510-4040-SG3F-IP20, 30KW, 40HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 40 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 45.7 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 60 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 40 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 30 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 55.6 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 73 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 50 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 37 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | A510-4040-SG3F-B Built-in / A510-4040-SG3F Option | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV, RMSLV(SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4040-SG3F-IP20, 30KW, 40HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell , S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. | as printed in field/value | — |
| Protection Functions / Inverter Overload / Protection(OL2) | Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency | as printed in field/value | — |
| Protection Functions / Protection(OL2) | is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss / Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4040-SG3F-IP20, 30KW, 40HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4040-SG3F-IP20, 30KW, 40HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | W 288 (11.34) | H 680 (26.77) | D 272 (10.70) | W1 160 (6.30) | H1 505 (19.88) | H2 525 (20.67) | t 3.3 (0.13) | d M8 | NW in kg(lbs) 32 (70.55) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| A510-4040-SG3F | 288 (11.34) mm (inch) | 680 (26.77) mm (inch) | 272 (10.70) mm (inch) | 160 (6.30) mm (inch) | 505 (19.88) mm (inch) | 525 (20.67) mm (inch) | 3.3 (0.13) mm (inch) | M8 mm (inch) | 32 (70.55) kg (lbs) | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | — |
| A510-4040-SG3F-BA510-4040-SG3F-B | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | Not present in this row | 286.5 (11.28) mm (inch) | 680 (26.77) mm (inch) | 252 (9.92) mm (inch) | 160 (6.30) mm (inch) | 505 (19.88) mm (inch) | 525 (20.67) mm (inch) | 3.3 (0.13) mm (inch) | M8 mm (inch) | 33 (72.75) kg (lbs) | — |
Technical source 020 — AS510-Drawing.pdf
Source download: AS510-Drawing.pdf.
Source differences and limitations
- Website/source difference — Drawing applicability: website Linked in product drawing bundles; PDF page 1 FILTER 4040-4060(F5); INV-A510S-IP20-05F. Website row IDs: See variant mapping. Neither is automatically substituted for the other.
Conditions for this section:
- C1: Title-block identity only; dimensions are not inferred for other linked models.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 10 / 10 | Constant Torque (kW/A): 30 / 60; Variable Torque (kW/A): 37 / 73; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 30.00 | Drawing PDF / AS510-Drawing.pdf |
P001 / AS510-Drawing.pdf — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Drawing / type_as_printed | FILTER 4040-4060(F5) | unit not separately specified | C1 |
| Drawing / drawing_number_as_printed | INV-A510S-IP20-05F | unit not separately specified | C1 |
Technical source 021 — Variable speed drive A510-4030-SG3F-IP20, 22KW, 30HP, 380-460V
Source download: DataSheet_of_A510-4030-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4030-SG3F-IP20, 22KW, 30HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 11 / 11 | Constant Torque (kW/A): 22 / 45; Variable Torque (kW/A): 30 / 58; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 22.00 | Datasheet PDF / DataSheet_of_A510-4030-SG3F-IP20-Enhanced.pdf |
| 89 / 11 / 11 | Constant Torque (kW/A): 22 / 45; Variable Torque (kW/A): 30 / 58; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 22.00 | Drawing PDF / DataSheet_of_A510-4030-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4030-SG3F-IP20, 22KW, 30HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 30 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 34.3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 45 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 30 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 22 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 44.2 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 58 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 40 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 30 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4030-SG3F-IP20, 22KW, 30HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4030-SG3F-IP20, 22KW, 30HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4030-SG3F-IP20, 22KW, 30HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4030-SG3F-IP20, 22KW, 30HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4030-SG3F | 265 (10.43) mm (inch) | 500 (19.69 ) mm (inch) | 225 (8.86) mm (inch) | 245 (9.65) mm (inch) | 340 (13.39 ) mm (inch) | 360 (14.17 ) mm (inch) | 1.6 (0.06) mm (inch) | M8 mm (inch) | 12.5 (27.56 ) kg (lbs) | — |
Technical source 022 — Variable speed drive A510-4050-SG3F-IP20, 37KW, 50HP, 380-460V
Source download: DataSheet_of_A510-4050-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4050-SG3F-IP20, 37KW, 50HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 12 / 12 | Constant Torque (kW/A): 37 / 75; Variable Torque (kW/A): 45 / 88; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 37.00 | Datasheet PDF / DataSheet_of_A510-4050-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4050-SG3F-IP20, 37KW, 50HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 50 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 57.2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 75 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 50 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 37 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 67.1 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 88 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 60 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 45 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4050-SG3F-IP20, 37KW, 50HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4050-SG3F-IP20, 37KW, 50HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4050-SG3F-IP20, 37KW, 50HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4050-SG3F-IP20, 37KW, 50HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4050-SG3F | 288 (11.34) mm (inch) | 680 (26.77 ) mm (inch) | 272 (10.70 ) mm (inch) | 160 (6.30) mm (inch) | 505 (19.88 ) mm (inch) | 525 (20.67 ) mm (inch) | 3.3 (0.13) mm (inch) | M8 mm (inch) | 32 (70.55 ) kg (lbs) | — |
Technical source 023 — Variable speed drive A510-4050-SC3F-IP20, 37KW, 50HP, 380-460V
Source download: datasheet-146.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4050-SC3F-IP20, 37KW, 50HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 12 / 12 | Constant Torque (kW/A): 37 / 75; Variable Torque (kW/A): 45 / 88; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 37.00 | Drawing PDF / datasheet-146.pdf |
P001 / Variable speed drive A510-4050-SC3F-IP20, 37KW, 50HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 50 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 57.2 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 75 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 50 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 37 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 67.1 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 88 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 60 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 45 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4050-SC3F-IP20, 37KW, 50HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4050-SC3F-IP20, 37KW, 50HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4050-SC3F-IP20, 37KW, 50HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4050-SC3F | 286.5 (11.28) mm (inch) | 679 (26.73) mm (inch) | 252 (9.92) mm (inch) | 220 (8.66) mm (inch) | 505 (19.88) mm (inch) | 525 (20.67) mm (inch) | 3.3 mm (inch) | M8 mm (inch) | 29.5 (65.04) kg (lbs) | — |
Technical source 024 — Variable speed drive A510-4060-SG3F-IP20, 45KW, 60HP, 380-460V
Source download: DataSheet_of_A510-4060-SG3F-IP20-Enhanced.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4060-SG3F-IP20, 45KW, 60HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 13 / 13 | Constant Torque (kW/A): 45 / 91; Variable Torque (kW/A): 55 / 103; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 45.00 | Datasheet PDF / DataSheet_of_A510-4060-SG3F-IP20-Enhanced.pdf |
P001 / Variable speed drive A510-4060-SG3F-IP20, 45KW, 60HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 60 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 69.3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 91 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 60 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 45 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 78.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 103 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 75 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 55 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4060-SG3F-IP20, 45KW, 60HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4060-SG3F-IP20, 45KW, 60HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4060-SG3F-IP20, 45KW, 60HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4060-SG3F-IP20, 45KW, 60HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4060-SG3F | 288 (11.34) mm (inch) | 680 (26.77 ) mm (inch) | 272 (10.70 ) mm (inch) | 160 (6.30) mm (inch) | 505 (19.88 ) mm (inch) | 525 (20.67 ) mm (inch) | 3.3 (0.13) mm (inch) | M8 mm (inch) | 32 (70.55 ) kg (lbs) | — |
Technical source 025 — Variable speed drive A510-4060-SC3F-IP20, 45KW, 60HP, 380-460V
Source download: datasheet-147.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4060-SC3F-IP20, 45KW, 60HP, 380-460V, page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 13 / 13 | Constant Torque (kW/A): 45 / 91; Variable Torque (kW/A): 55 / 103; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 45.00 | Drawing PDF / datasheet-147.pdf |
P001 / Variable speed drive A510-4060-SC3F-IP20, 45KW, 60HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 60 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 69.3 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 91 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 60 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 45 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 78.5 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 103 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 75 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 55 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4060-SC3F-IP20, 45KW, 60HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4060-SC3F-IP20, 45KW, 60HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4060-SC3F-IP20, 45KW, 60HP, 380-460V — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4060-SC3F | 286.5 (11.28) mm (inch) | 679 (26.73) mm (inch) | 252 (9.92) mm (inch) | 220 (8.66) mm (inch) | 505 (19.88) mm (inch) | 525 (20.67) mm (inch) | 3.3 mm (inch) | M8 mm (inch) | 29.5 (65.04) kg (lbs) | — |
Technical source 026 — Variable speed drive A510-4075-SC3-IP20, 55KW, 75HP, 380-460V External EMC Filter.
Source download: datasheet-148.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4075-SC3-IP20, 55KW, 75HP, 380-460V External EMC Filter., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 14 / 14 | Constant Torque (kW/A): 55 / 118; Variable Torque (kW/A): 75 / 145; Supply: 380-480V 3PH; IP Rating: 20; kW Rating: 55.00 | Drawing PDF / datasheet-148.pdf |
P001 / Variable speed drive A510-4075-SC3-IP20, 55KW, 75HP, 380-460V External EMC Filter. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 75 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 89.9 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 118 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 75 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 55 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 111 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 145 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 100 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 75 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4075-SC3-IP20, 55KW, 75HP, 380-460V External EMC Filter. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4075-SC3-IP20, 55KW, 75HP, 380-460V External EMC Filter. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4075-SC3-IP20, 55KW, 75HP, 380-460V External EMC Filter. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4075-SC3 | 286.5 (11.28) mm (inch) | 525 (20.67) mm (inch) | 252 (9.92) mm (inch) | 220 (8.66) mm (inch) | 505 (19.88) mm (inch) | N/A mm (inch) | 3.3 mm (inch) | M8 mm (inch) | 24 (52.91) kg (lbs) | — |
Technical source 027 — Variable speed drive A510-4100-SG3-IP20/NEMA1, 75KW, 100HP, 380-460V
Source download: DataSheet_of_A510-4100-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4100-SG3-IP20/NEMA1, 75KW, 100HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 15 / 15 | Constant Torque (kW/A): 75 / 150; Variable Torque (kW/A): 90 / 168; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 75.00 | Datasheet PDF / DataSheet_of_A510-4100-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4100-SG3-IP20/NEMA1, 75KW, 100HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 100 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 114 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 150 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 100 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 75 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 128 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 168 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 125 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 90 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train | as printed in field/value | — |
P001 / Variable speed drive A510-4100-SG3-IP20/NEMA1, 75KW, 100HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4100-SG3-IP20/NEMA1, 75KW, 100HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4100-SG3-IP20/NEMA1, 75KW, 100HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|
| A510-4100-SG3 | 348.5 (13.72) mm (inch) | 740 (29.13 ) mm (inch) | 300 (11.81 ) mm (inch) | 250 (9.84) mm (inch) | 560 (22.05 ) mm (inch) | 1.6 (0.06) mm (inch) | M8 mm (inch) | 44 (97.00 ) kg (lbs) | — |
Technical source 028 — Variable speed drive A510-4100-SC3-IP00, 75KW, 100HP, 380-460V External EMC Filter included.
Source download: datasheet-149.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4100-SC3-IP00, 75KW, 100HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 15 / 15 | Constant Torque (kW/A): 75 / 150; Variable Torque (kW/A): 90 / 168; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 75.00 | Drawing PDF / datasheet-149.pdf |
P001 / Variable speed drive A510-4100-SC3-IP00, 75KW, 100HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 100 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 114 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 150 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 100 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 75 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 128 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 168 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 125 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 90 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4100-SC3-IP00, 75KW, 100HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4100-SC3-IP00, 75KW, 100HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4100-SC3-IP00, 75KW, 100HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4100-SC3 | 344 (13.54) mm (inch) | 580 (22.83) mm (inch) | 300 (11.81) mm (inch) | 250 (9.84) mm (inch) | 560 (22.05) mm (inch) | N/A mm (inch) | 1.6 mm (inch) | M8 mm (inch) | 40 (88.18) kg (lbs) | — |
Technical source 029 — Variable speed drive A510-4125-SG3-IP20/NEMA1, 90KW, 125HP, 380-460V
Source download: DataSheet_of_A510-4125-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4125-SG3-IP20/NEMA1, 90KW, 125HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 16 / 16 | Constant Torque (kW/A): 90 / 180; Variable Torque (kW/A): 110 / 208; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 90.00 | Datasheet PDF / DataSheet_of_A510-4125-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4125-SG3-IP20/NEMA1, 90KW, 125HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 125 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 137 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 180 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 125 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 90 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 159 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 208 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 150 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 110 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train | as printed in field/value | — |
P001 / Variable speed drive A510-4125-SG3-IP20/NEMA1, 90KW, 125HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4125-SG3-IP20/NEMA1, 90KW, 125HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4125-SG3-IP20/NEMA1, 90KW, 125HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | t | d | NW in kg(lbs ) | Conditions |
|---|---|---|---|---|---|---|---|---|---|
| A510-4125-SG3 | 348.5 (13.72) mm (inch) | 740 (29.13 ) mm (inch) | 300 (11.81 ) mm (inch) | 250 (9.84) mm (inch) | 560 (22.05 ) mm (inch) | 1.6 (0.06) mm (inch) | M8 mm (inch) | 44 (97.00 ) kg (lbs) | — |
Technical source 030 — Variable speed drive A510-4125-SC3-IP00, 90KW, 125HP, 380-460V External EMC Filter included.
Source download: datasheet-150.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4125-SC3-IP00, 90KW, 125HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 16 / 16 | Constant Torque (kW/A): 90 / 180; Variable Torque (kW/A): 110 / 208; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 90.00 | Drawing PDF / datasheet-150.pdf |
P001 / Variable speed drive A510-4125-SC3-IP00, 90KW, 125HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 125 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 137 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 180 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 125 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 90 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 159 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 208 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 150 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 110 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4125-SC3-IP00, 90KW, 125HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4125-SC3-IP00, 90KW, 125HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4125-SC3-IP00, 90KW, 125HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4125-SC3 | 344 (13.54) mm (inch) | 580 (22.83) mm (inch) | 300 (11.81) mm (inch) | 250 (9.84) mm (inch) | 560 (22.05) mm (inch) | N/A mm (inch) | 1.6 mm (inch) | M8 mm (inch) | 40 (88.18) kg (lbs) | — |
Technical source 031 — Variable speed drive A510-4150-SG3-IP20/NEMA1, 110KW, 150HP, 380-460V
Source download: DataSheet_of_A510-4150-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4150-SG3-IP20/NEMA1, 110KW, 150HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 17 / 17 | Constant Torque (kW/A): 110 / 216; Variable Torque (kW/A): 132 / 250; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 110.00 | Datasheet PDF / DataSheet_of_A510-4150-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4150-SG3-IP20/NEMA1, 110KW, 150HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 150 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 165 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 216 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 150 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 110 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 191 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 250 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 175 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 132 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4150-SG3-IP20/NEMA1, 110KW, 150HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4150-SG3-IP20/NEMA1, 110KW, 150HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4150-SG3-IP20/NEMA1, 110KW, 150HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4150-SG3-IP20/NEMA1, 110KW, 150HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|
| A510-4150-SG3 | 463.5 (18.25) mm (inch) | 1105 (43.50 ) mm (inch) | 324.5 (12.78 ) mm (inch) | 320 (12.60 ) mm (inch) | 760 (29.92 ) mm (inch) | 1.6 (0.06) mm (inch) | M10 mm (inch) | 81 (178.5 7) kg (lbs) | — |
Technical source 032 — Variable speed drive A510-4150-SC3-IP00, 110KW, 150HP, 380-460V External EMC Filter included.
Source download: datasheet-151.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4150-SC3-IP00, 110KW, 150HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 17 / 17 | Constant Torque (kW/A): 110 / 216; Variable Torque (kW/A): 132 / 250; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 110.00 | Drawing PDF / datasheet-151.pdf |
P001 / Variable speed drive A510-4150-SC3-IP00, 110KW, 150HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 150 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 165 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 216 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 150 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 110 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 191 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 250 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 175 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 132 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4150-SC3-IP00, 110KW, 150HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4150-SC3-IP00, 110KW, 150HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4150-SC3-IP00, 110KW, 150HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4150-SC3 | 459 (18.07) mm (inch) | 790 (31.10) mm (inch) | 324.5 (12.78) mm (inch) | 320 (12.60) mm (inch) | 760 (29.92) mm (inch) | N/A mm (inch) | 1.6 mm (inch) | M10 mm (inch) | 74 (163.14) kg (lbs) | — |
Technical source 033 — Variable speed drive A510-4175-SG3-IP20/NEMA1, 132KW, 175HP, 380-460V
Source download: DataSheet_of_A510-4175-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4175-SG3-IP20/NEMA1, 132KW, 175HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 18 / 18 | Constant Torque (kW/A): 132 / 260; Variable Torque (kW/A): 160 / 296; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 132.00 | Datasheet PDF / DataSheet_of_A510-4175-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4175-SG3-IP20/NEMA1, 132KW, 175HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 175 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 198 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 260 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 175 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 132 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 226 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 296 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 215 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 160 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4175-SG3-IP20/NEMA1, 132KW, 175HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4175-SG3-IP20/NEMA1, 132KW, 175HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4175-SG3-IP20/NEMA1, 132KW, 175HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4175-SG3-IP20/NEMA1, 132KW, 175HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|
| A510-4175-SG3 | 463.5 (18.25) mm (inch) | 1105 (43.50 ) mm (inch) | 324.5 (12.78 ) mm (inch) | 320 (12.60 ) mm (inch) | 760 (29.92 ) mm (inch) | 1.6 (0.06) mm (inch) | M10 mm (inch) | 81 (178.5 7) kg (lbs) | — |
Technical source 034 — Variable speed drive A510-4175-SC3-IP00, 132KW, 175HP, 380-460V External EMC Filter included.
Source download: datasheet-152.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4175-SC3-IP00, 132KW, 175HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 18 / 18 | Constant Torque (kW/A): 132 / 260; Variable Torque (kW/A): 160 / 296; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 132.00 | Drawing PDF / datasheet-152.pdf |
P001 / Variable speed drive A510-4175-SC3-IP00, 132KW, 175HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 175 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 198 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 260 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 175 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 132 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 226 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 296 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 215 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 160 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4175-SC3-IP00, 132KW, 175HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4175-SC3-IP00, 132KW, 175HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4175-SC3-IP00, 132KW, 175HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4175-SC3 | 459 (18.07) mm (inch) | 790 (31.10) mm (inch) | 324.5 (12.78) mm (inch) | 320 (12.60) mm (inch) | 760 (29.92) mm (inch) | N/A mm (inch) | 1.6 mm (inch) | M10 mm (inch) | 74 (163.14) kg (lbs) | — |
Technical source 035 — Variable speed drive A510-4215-SG3-IP20/NEMA1, 160KW, 215HP, 380-460V
Source download: DataSheet_of_A510-4215-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4215-SG3-IP20/NEMA1, 160KW, 215HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 19 / 19 | Constant Torque (kW/A): 160 / 295; Variable Torque (kW/A): 185 / 328; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 160.00 | Datasheet PDF / DataSheet_of_A510-4215-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4215-SG3-IP20/NEMA1, 160KW, 215HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 215 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 225 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 295 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 215 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 160 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 250 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 328 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 250 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 185 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4215-SG3-IP20/NEMA1, 160KW, 215HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4215-SG3-IP20/NEMA1, 160KW, 215HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4215-SG3-IP20/NEMA1, 160KW, 215HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4215-SG3-IP20/NEMA1, 160KW, 215HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|
| A510-4215-SG3 | 463.5 (18.25) mm (inch) | 1105 (43.50 ) mm (inch) | 324.5 (12.78 ) mm (inch) | 320 (12.60 ) mm (inch) | 760 (29.92 ) mm (inch) | 1.6 (0.06) mm (inch) | M10 mm (inch) | 81 (178.5 7) kg (lbs) | — |
Technical source 036 — Variable speed drive A510-4215-SC3-IP00, 160KW, 215HP, 380-460V External EMC Filter included.
Source download: datasheet-153.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4215-SC3-IP00, 160KW, 215HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 19 / 19 | Constant Torque (kW/A): 160 / 295; Variable Torque (kW/A): 185 / 328; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 160.00 | Drawing PDF / datasheet-153.pdf |
P001 / Variable speed drive A510-4215-SC3-IP00, 160KW, 215HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 215 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 225 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 295 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 215 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 160 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 250 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 328 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 250 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 185 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4215-SC3-IP00, 160KW, 215HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4215-SC3-IP00, 160KW, 215HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4215-SC3-IP00, 160KW, 215HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | H1 | H2 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4215-SC3 | 459 (18.07) mm (inch) | 790 (31.10) mm (inch) | 324.5 (12.78) mm (inch) | 320 (12.60) mm (inch) | 760 (29.92) mm (inch) | N/A mm (inch) | 1.6 mm (inch) | M10 mm (inch) | 74 (163.14) kg (lbs) | — |
Technical source 037 — Variable speed drive A510-4270-SG3-IP20/NEMA1, 200KW, 270HP, 380-460V
Source download: DataSheet_of_A510-4270-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4270-SG3-IP20/NEMA1, 200KW, 270HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 20 / 20 | Constant Torque (kW/A): 200 / 380; Variable Torque (kW/A): 220 / 435; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 200.00 | Datasheet PDF / DataSheet_of_A510-4270-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4270-SG3-IP20/NEMA1, 200KW, 270HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 270 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 290 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 380 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 270 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 200 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 332 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 435 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 300 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 220 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4270-SG3-IP20/NEMA1, 200KW, 270HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4270-SG3-IP20/NEMA1, 200KW, 270HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4270-SG3-IP20/NEMA1, 200KW, 270HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4270-SG3-IP20/NEMA1, 200KW, 270HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4270-SG3 | 692 (27.24) mm (inch) | 1313 (51.69 ) mm (inch) | 410 (16.14 ) mm (inch) | 530 (20.8 7) mm (inch) | 265 (10.43 ) mm (inch) | 960 (37.80 ) mm (inch) | 1.6 (0.06) mm (inch) | M12 mm (inch) | 194 (427.7 0) kg (lbs) | — |
Technical source 038 — Variable speed drive A510-4270-SC3-IP00, 200KW, 270HP, 380-460V External EMC Filter included.
Source download: datasheet-154.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4270-SC3-IP00, 200KW, 270HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 20 / 20 | Constant Torque (kW/A): 200 / 380; Variable Torque (kW/A): 220 / 435; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 200.00 | Drawing PDF / datasheet-154.pdf |
P001 / Variable speed drive A510-4270-SC3-IP00, 200KW, 270HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 270 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 290 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 380 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 270 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 200 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 332 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 435 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 300 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 220 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4270-SC3-IP00, 200KW, 270HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4270-SC3-IP00, 200KW, 270HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4270-SC3-IP00, 200KW, 270HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4270-SC3 | 690 (27.17) mm (inch) | 1000 (39.37) mm (inch) | 410 (16.14) mm (inch) | 530 (20.87) mm (inch) | 265 (10.43) mm (inch) | 960 (37.80) mm (inch) | 1.6 mm (inch) | M12 mm (inch) | 184 (405.65) kg (lbs) | — |
Technical source 039 — Variable speed drive A510-4300-SG3-IP20/NEMA1, 220KW, 300HP, 380-460V
Source download: DataSheet_of_A510-4300-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4300-SG3-IP20/NEMA1, 220KW, 300HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 21 / 21 | Constant Torque (kW/A): 220 / 450; Variable Torque (kW/A): 280 / 515; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 220.00 | Datasheet PDF / DataSheet_of_A510-4300-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4300-SG3-IP20/NEMA1, 220KW, 300HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 300 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 343 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 450 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 300 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 220 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 393 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 515 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 375 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 280 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4300-SG3-IP20/NEMA1, 220KW, 300HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4300-SG3-IP20/NEMA1, 220KW, 300HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4300-SG3-IP20/NEMA1, 220KW, 300HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4300-SG3-IP20/NEMA1, 220KW, 300HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4300-SG3 | 692 (27.24) mm (inch) | 1313 (51.69 ) mm (inch) | 410 (16.14 ) mm (inch) | 530 (20.8 7) mm (inch) | 265 (10.43 ) mm (inch) | 960 (37.80 ) mm (inch) | 1.6 (0.06) mm (inch) | M12 mm (inch) | 194 (427.7 0) kg (lbs) | — |
Technical source 040 — Variable speed drive A510-4300-SC3-IP00, 220KW, 300HP, 380-460V External EMC Filter included.
Source download: datasheet-155.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4300-SC3-IP00, 220KW, 300HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 21 / 21 | Constant Torque (kW/A): 220 / 450; Variable Torque (kW/A): 280 / 515; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 220.00 | Drawing PDF / datasheet-155.pdf |
P001 / Variable speed drive A510-4300-SC3-IP00, 220KW, 300HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 300 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 343 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 450 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 300 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 220 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 393 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 515 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 375 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 280 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4300-SC3-IP00, 220KW, 300HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4300-SC3-IP00, 220KW, 300HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4300-SC3-IP00, 220KW, 300HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4300-SC3 | 690 (27.17) mm (inch) | 1000 (39.37) mm (inch) | 410 (16.14) mm (inch) | 530 (20.87) mm (inch) | 265 (10.43) mm (inch) | 960 (37.80) mm (inch) | 1.6 mm (inch) | M12 mm (inch) | 184 (405.65) kg (lbs) | — |
Technical source 041 — Variable speed drive A510-4375-SG3-IP20/NEMA1, 280KW, 375HP, 380-460V
Source download: DataSheet_of_A510-4375-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4375-SG3-IP20/NEMA1, 280KW, 375HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 22 / 22 | Constant Torque (kW/A): 280 / 523; Variable Torque (kW/A): 315 / 585; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 280.00 | Datasheet PDF / DataSheet_of_A510-4375-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4375-SG3-IP20/NEMA1, 280KW, 375HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 375 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 400 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 523 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 375 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 280 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 446 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 585 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 425 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 315 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4375-SG3-IP20/NEMA1, 280KW, 375HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4375-SG3-IP20/NEMA1, 280KW, 375HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4375-SG3-IP20/NEMA1, 280KW, 375HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4375-SG3-IP20/NEMA1, 280KW, 375HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4375-SG3 | 692 (27.24) mm (inch) | 1313 (51.69 ) mm (inch) | 410 (16.14 ) mm (inch) | 530 (20.8 7) mm (inch) | 265 (10.43 ) mm (inch) | 960 (37.80 ) mm (inch) | 1.6 (0.06) mm (inch) | M12 mm (inch) | 194 (427.7 0) kg (lbs) | — |
Technical source 042 — Variable speed drive A510-4375-SC3-IP00, 280KW, 375HP, 380-460V External EMC Filter included.
Source download: datasheet-156.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4375-SC3-IP00, 280KW, 375HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 22 / 22 | Constant Torque (kW/A): 280 / 523; Variable Torque (kW/A): 315 / 585; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 280.00 | Drawing PDF / datasheet-156.pdf |
P001 / Variable speed drive A510-4375-SC3-IP00, 280KW, 375HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 375 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 400 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 523 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 375 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 280 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 446 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 585 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 425 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 315 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4375-SC3-IP00, 280KW, 375HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4375-SC3-IP00, 280KW, 375HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4375-SC3-IP00, 280KW, 375HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4375-SC3 | 690 (27.17) mm (inch) | 1000 (39.37) mm (inch) | 410 (16.14) mm (inch) | 530 (20.87) mm (inch) | 265 (10.43) mm (inch) | 960 (37.80) mm (inch) | 1.6 mm (inch) | M12 mm (inch) | 184 (405.65) kg (lbs) | — |
Technical source 043 — Variable speed drive A510-4425-SG3-IP20/NEMA1, 315KW, 425HP, 380-460V
Source download: DataSheet_of_A510-4425-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4425-SG3-IP20/NEMA1, 315KW, 425HP, 380-460V, page 7
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 23 / 23 | Constant Torque (kW/A): 315 / 585; Variable Torque (kW/A): 315 / 585; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 315.00 | Datasheet PDF / DataSheet_of_A510-4425-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf |
P001 / Variable speed drive A510-4425-SG3-IP20/NEMA1, 315KW, 425HP, 380-460V — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 425 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 461 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 585 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 425 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 315 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 446 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 585 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 425 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 315 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Built-in | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting Resolution | Digital references: 0.01Hz, Analog references: 0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode (HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode (ND): 120% rated current for 60sec. | as printed in field/value | — |
P001 / Variable speed drive A510-4425-SG3-IP20/NEMA1, 315KW, 425HP, 380-460V — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Frequency Setting Signal | 0 to +10V, -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4425-SG3-IP20/NEMA1, 315KW, 425HP, 380-460V — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/ Deceleration Time | 0.0~ 6000.0 second (separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft-PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication, Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault State Record, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell, S Curve Acceleration and Deceleration, Up / Down Operation, Modbus Communication Protocol, Output of Pulse Multiple, Display of Engineering Unit, SINK / SOURCE Selection, RTC function in Enhanced LCD type | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short- circuit(SC) Protection | It stops the motor when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage Protection(OV) | If the main circuit DC voltage is over 820V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss restart | Power loss exceeds 15ms. You can set the function of momentary power loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Input / Output Phase Loss Protection (IPL / OPL) | If the IPL / OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4425-SG3-IP20/NEMA1, 315KW, 425HP, 380-460V — source page 4 — PDF page 4
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Protection / Short-circuit Current Rating (SCCR) | Per UL 508C, the drive is suitable for use on a circuit capable of delivering not more than 100KA symmetrical amperes(rms) when protected by fuses given in the fuse table | as printed in field/value | — |
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Environment Specification / Pollution Degree | Meet 60721-3-3 Class 3C3 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard, 400V 60HP or below EMI filter built-in. | as printed in field/value | — |
| Electromagnetic Compatibility (EMS) | In compliance with EN61800-3 standard | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5- 1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Options / Communication Option Cards | Profibus DP, CANopen, EtherCAT, EtherNet/IP | as printed in field/value | — |
| Options / Encoder Cards (Induction Motors) | Open Collector, Line Driver | as printed in field/value | — |
| Options / Encoder Cards (PM Motors) | Line Driver, Resolver, Sin-Cos Incremental, Absolute | as printed in field/value | — |
| Options / Bluetooth | Bluetooth Keypad | as printed in field/value | — |
P001 / Variable speed drive A510-4425-SG3-IP20/NEMA1, 315KW, 425HP, 380-460V — source page 7 — PDF page 7
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4425-SG3 | 692 (27.24) mm (inch) | 1313 (51.69 ) mm (inch) | 410 (16.14 ) mm (inch) | 530 (20.8 7) mm (inch) | 265 (10.43 ) mm (inch) | 960 (37.80 ) mm (inch) | 1.6 (0.06) mm (inch) | M12 mm (inch) | 194 (427.7 0) kg (lbs) | — |
Technical source 044 — Variable speed drive A510-4425-SC3-IP00, 315KW, 425HP, 380-460V External EMC Filter included.
Source download: datasheet-157.pdf.
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Dimensions by printed model — P001, Variable speed drive A510-4425-SC3-IP00, 315KW, 425HP, 380-460V External EMC Filter included., page 5
No additional scalar specification fields are represented for this page. Refer to the source page for its graphical or other content; no geometry or additional rating is inferred.
Website associations for this source
| Table / row / row ID | Listed specification | Document role / member |
|---|---|---|
| 89 / 23 / 23 | Constant Torque (kW/A): 315 / 585; Variable Torque (kW/A): 315 / 585; Supply: 380-480V 3PH; IP Rating: 0; kW Rating: 315.00 | Drawing PDF / datasheet-157.pdf |
P001 / Variable speed drive A510-4425-SC3-IP00, 315KW, 425HP, 380-460V External EMC Filter included. — source page 1 — PDF page 1
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Component name | A510s | as printed in field/value | — |
| Inverter Capacity(HP) | 425 | as printed in field/value | — |
| Output Rating / HD / Rated Output Capacity(KVA) | 446 | as printed in field/value | — |
| Output Rating / HD / Rated Output Current(A) | 585 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (HP) | 425 | as printed in field/value | — |
| Output Rating / HD / Maximum Applicable Motor / (KW) | 315 | as printed in field/value | — |
| Output Rating / ND / Rated Output Capacity(KVA) | 446 | as printed in field/value | — |
| Output Rating / ND / Rated Output Current(A) | 585 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (HP) | 425 | as printed in field/value | — |
| Output Rating / ND / Maximum Applicable Motor / (KW) | 315 | as printed in field/value | — |
| Output Rating / Maximum Output Voltage(V) | Three Phase, 380~480V | as printed in field/value | — |
| Output Rating / Maximum Output Frequency(Hz) | 0.1~599.0Hz | as printed in field/value | — |
| Input Power / Rated Voltage, Frequency | Three Phase, 380V to 480V, 50/60Hz | as printed in field/value | — |
| Input Power / Allowable Voltage Fluctuation | -15% ~ +10% | as printed in field/value | — |
| Input Power / Allowable Frequency Fluctuation | ±5% | as printed in field/value | — |
| Braking transistor | Option- Braking Module | as printed in field/value | — |
| Control characteristics / Display | LCD keypad | as printed in field/value | — |
| Control characteristics / Control Modes | V/F, V/F+PG, SLV, SLV2, SV, PMSV, PMSLV (SVPWM Modulation) | as printed in field/value | — |
| Control characteristics / Output Frequency | 0.1Hz~599.0Hz | as printed in field/value | — |
| Control characteristics / Frequency Accuracy | Digital references: ±0.01%(-10~ +40 ℃), Analog references: ±0.1%(25 ℃ ± 10 ℃), | as printed in field/value | — |
| Control characteristics / Speed Control Accuracy | ±0.1% (Sensor Vector Control Mode, SV) *1 ±0.5% (Sensorless Vector Control Mode, SLV)*1 | as printed in field/value | — |
| Control characteristics / Frequency setting / Resolution | Digital references: 0.01Hz, Analog refrences:0.03Hz at 60Hz | as printed in field/value | — |
| Control characteristics / Output Frequency Resolution | 0.01Hz | as printed in field/value | — |
| Control characteristics / Overload Tolerance | Heavy Duty Mode(HD): 150% rated current for 60sec, 200% current for 2sec. (Factory default), Normal Duty Mode(ND): 120% rated current for 60sec. | as printed in field/value | — |
| Control characteristics / Frequency Setting Signal | 0 to +10V , -10V to +10V , 4 to 20mA or pulse train input | as printed in field/value | — |
P001 / Variable speed drive A510-4425-SC3-IP00, 315KW, 425HP, 380-460V External EMC Filter included. — source page 2 — PDF page 2
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Control characteristics / Acceleration/Deceleration Time | 0.0~ 6000.0 second(separately set acceleration and deceleration time) | as printed in field/value | — |
| Control characteristics / Voltage/Frequency / Characteristics | 15 fixed and one customized V/f curve based on parameters | as printed in field/value | — |
| Control characteristics / Braking Torque | Approximate 20%, braking transistor built in. | as printed in field/value | — |
| Control characteristics / Main Control Functions | Auto tuning, Zero Servo, Torque Control, Position Control, Droop, Soft- PWM, Over-Voltage Protection, Dynamic Braking, Speed Search, Frequency Traversing, Momentary Power Loss Restart, PID Control, Automatic Torque Compensation, Slip Compensation, RS-485 Communication , Close Loop Control with PG, Simple PLC Function, Two analog Outputs, Safety Input Contact. | as printed in field/value | — |
| Control characteristics / Other Functions | Records of Power ON and Operation Time, 30 Fault History Records and Latest Fault Record State, Energy-Saving Function, Phase Loss Protection, DC Braking, Dwell,S Curve Acceleration and Deceleration, Up/Down Operation, Modbus Communication protocol, Display of Engineering unit, SINK/SOURCE Selection | as printed in field/value | — |
| Protection Functions / Stall Protection | Current level can be adjusted (in acceleration or constant speed; it can be set separately. In deceleration, it can be set with or without stall protection) | as printed in field/value | — |
| Protection Functions / Over Current(OC) and Output Short-circuit(SC) Protection | It stops when the output current exceeds 200% of the inverter rated current | as printed in field/value | — |
| Protection Functions / Inverter Overload Protection(OL2) | Inverter will be stopped when the output is higher than below conditions. Heavy Duty Model (HD): 150% rated current for 60sec, 200% rated current for 2sec. (Factory default), carrier frequency is from 2KHz to 8KHz. Normal Duty Mode(ND): 120% rated current for 60sec, carrier frequency is 2KHz | as printed in field/value | — |
| Protection Functions / Motor Overload Protection(OL1) | Electrical overload protection curve | as printed in field/value | — |
| Protection Functions / Over Voltage | If the main circuit DC voltage is over 820V (400V class), the motor stops | as printed in field/value | — |
| Protection Functions / Protection(OV) | running. | as printed in field/value | — |
| Protection Functions / Under Voltage Protection(UV) | If the main circuit DC voltage falls below 380V (400V class), the motor stops running. | as printed in field/value | — |
| Protection Functions / Momentary power loss | Power loss exceeds 15ms. You can set the function of momentary power | as printed in field/value | — |
| Protection Functions / restart | loss restart up to 2sec | as printed in field/value | — |
| Protection Functions / Overheat Protection(OH) | Thermistor sensor on heatsink | as printed in field/value | — |
| Protection Functions / Ground Fault Protection(GF) | Protection by current detection circuit | as printed in field/value | — |
| Protection Functions / Charge Indicator | When main circuit DC voltage ≧50V, the CHARGE LED is on | as printed in field/value | — |
| Protection Functions / Output Phase Loss Protection(OPL) | If the OPL function acts, the motor stops rotation automatically | as printed in field/value | — |
P001 / Variable speed drive A510-4425-SC3-IP00, 315KW, 425HP, 380-460V External EMC Filter included. — source page 3 — PDF page 3
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Environment Specification / Location | Indoor (Protected from corrosive gases and dust) | as printed in field/value | — |
| Environment Specification / Ambient Temperature | -10~ +40℃ without de-rating (IP20/NEMA1), -10~ +50℃ (IP00); with de-rating, its maximum operation temperature is 60℃ | as printed in field/value | — |
| Environment Specification / Storage Temperature | -20~ +70℃ | as printed in field/value | — |
| Environment Specification / Humidity | 95% RH or less (no condensation) | as printed in field/value | — |
| Environment Specification / Altitude and Vibration | Altitude of 1000 meters or lower,1.0G, in compliance with IEC60068-2-6 | as printed in field/value | — |
| Communication Function | Built-in RS-485 as standard (Modbus protocol with standard RJ45) | as printed in field/value | — |
| Electromagnetic Interference(EMI) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Electromagnetic / Compatibility (EMS) | In compliance with EN61800-3 standard (with external EMC filter) | as printed in field/value | — |
| Certification / CE | In compliance with EN61800-3 (CE & RE) and EN61800-5-1 (LVD) | as printed in field/value | — |
| Certification / UL | UL508C | as printed in field/value | — |
| Option Card | Open Collector type (Induction Motor), Line Driver (Induction Motor), Line Driver (Permanent Magnet Motor). | as printed in field/value | — |
P001 / Variable speed drive A510-4425-SC3-IP00, 315KW, 425HP, 380-460V External EMC Filter included. — source page 5 — PDF page 5
| Configuration / printed row | W | H | D | W1 | W2 | H1 | t | d | NW in kg(lbs) | Conditions |
|---|---|---|---|---|---|---|---|---|---|---|
| A510-4425-SC3 | 690 (27.17) mm (inch) | 1000 (39.37) mm (inch) | 410 (16.14) mm (inch) | 530 (20.87) mm (inch) | 265 (10.43) mm (inch) | 960 (37.80) mm (inch) | 1.6 mm (inch) | M12 mm (inch) | 184 (405.65) kg (lbs) | — |
Selection checks and source differences
One linked A510-4075-SG3F-IP20-Enhanced datasheet was unavailable in the collected source set. All collected files and row associations remain represented; this is not a claim that the unavailable file was acquired.
Website six control modes versus Enhanced catalogue seven; catalogue filename 2025 versus printed 20230323 footer; website LCD versus catalogue LED/LCD option; PCB Class3C2 versus general-table Class3C3. Preserve model/edition qualifications.
HD/ND and maximum-frequency limits depend on control mode, rating and carrier frequency. The manual has overlapping carrier conditions; the catalogue has overlapping 400V 60–175HP and125HP carrier rows. No precedence inferred.
Quick setup forward/reverse heading differs from the S1 RUN/STOP and S2 REV/FWD figure labels. No topology reconstructed.
Individual datasheet title voltage380–460V differs from table including480V. The shared FILTER4040–4060(F5) drawing has restricted applicability; links do not prove applicability to every rating.
Catalogue I/O expansion text and part naming, repeated slot labels and historical safety/compliance statements require exact accessory and manual confirmation. No current certificate validity is inferred.
Product documents
- TECO-A510.pdf — Product page
- A510s-catalog-2025.pdf — Product page
- A510s-ManualEnglishV10.pdf — Product page
- TECO-A510s-Enhanced-Quick-Set-up-Guide.pdf — Product page
- JN5-DriveLink-setupV1.935.zip — Product page
- TAC-EMD-Standard-Conditions-of-Sale-Final-May-2022.pdf — Shared website
- ISO9001-Intertek-SAI-Global-Certificate-QEC3088-Expiry-25-May-2029.pdf — Shared website
- ISO45001-Intertek-SAI-Global-Certificate-0185118-Expiry-22-August-2027.pdf — Shared website
- DataSheet_of_A510-4001-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-135.pdf — Technical row
- DataSheet_of_A510-4002-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-136.pdf — Technical row
- DataSheet_of_A510-4003-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-137.pdf — Technical row
- DataSheet_of_A510-4005-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-138.pdf — Technical row
- DataSheet_of_A510-4008-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-139.pdf — Technical row
- DataSheet_of_A510-4010-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-140.pdf — Technical row
- DataSheet_of_A510-4015-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-141.pdf — Technical row
- DataSheet_of_A510-4020-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-142.pdf — Technical row
- DataSheet_of_A510-4025-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-143.pdf — Technical row
- A510-4040-SG3F-IP20-datasheet.pdf — Technical row
- AS510-Drawing.pdf — Technical row
- DataSheet_of_A510-4030-SG3F-IP20-Enhanced.pdf — Technical row
- DataSheet_of_A510-4050-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-146.pdf — Technical row
- DataSheet_of_A510-4060-SG3F-IP20-Enhanced.pdf — Technical row
- datasheet-147.pdf — Technical row
- datasheet-148.pdf — Technical row
- DataSheet_of_A510-4100-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-149.pdf — Technical row
- DataSheet_of_A510-4125-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-150.pdf — Technical row
- DataSheet_of_A510-4150-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-151.pdf — Technical row
- DataSheet_of_A510-4175-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-152.pdf — Technical row
- DataSheet_of_A510-4215-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-153.pdf — Technical row
- DataSheet_of_A510-4270-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-154.pdf — Technical row
- DataSheet_of_A510-4300-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-155.pdf — Technical row
- DataSheet_of_A510-4375-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-156.pdf — Technical row
- DataSheet_of_A510-4425-SG3F-IP00-Enhanced-NEMA1_IP20_KIT.pdf — Technical row
- datasheet-157.pdf — Technical row
Our company certificates and conditions of sale remain separate from the selected product’s ratings and approvals.
Talk to our team about your application, supply, motor rating and configuration.